Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 09:02:47
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 9161.32 | 807.50 | 807.50 |
Net Site Energy | 9161.32 | 807.50 | 807.50 |
Total Source Energy | 22091.65 | 1947.21 | 1947.21 |
Net Source Energy | 22091.65 | 1947.21 | 1947.21 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 580.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1368.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 174.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 641.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 590.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 122.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 141.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 483.38 | 953.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 43.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5838.11 | 3323.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 580.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1368.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 174.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 952.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 22.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 590.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 122.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 141.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.75 | 953.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Other | 392.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 20.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 580.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1368.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 543.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 174.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 641.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 590.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 122.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 141.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 483.38 | 953.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 43.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 63.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 226.07 | 135.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 225.20 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 514.58 | 292.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 63.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 226.07 | 135.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 225.20 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 514.58 | 292.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5838.109 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5838.109 | 100.00 |
Total On-Site and Utility Electric Sources | 5838.109 | 100.00 |
Total Electricity End Uses | 5838.109 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 273.94 | 23.15 |
Air to Air Heat Recovery for Heating | 909.26 | 76.85 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 1183.20 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 81.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7592.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYSLAUNDRY HPWH TANK | SWHSYS1 HPWH TANK |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| SWHSYS1 HPWH FAN | SWHSYSLAUNDRY HPWH FAN | FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 5.9798 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 8.7295 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 8.7295 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.1656 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 3.6813 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.1344 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 8.3313 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 8.1375 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 3.9719 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 3.9719 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 3.9719 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 3.9719 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 8.3313 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 8.3313 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 10.5594 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 3.9719 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.2589 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.2589 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.9798 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 8.7295 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 8.7295 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.1656 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 3.6813 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.1344 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 8.3313 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 8.1375 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 3.9719 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 3.9719 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 3.9719 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 3.9719 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 3.9719 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 3.9719 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 3.9719 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 3.9719 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 3.9719 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 3.9719 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 8.3313 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 8.3313 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 10.5594 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 3.9719 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.2589 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.2589 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.3293 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 05-JUN-19:10 | 27-JAN-19:10 | - | - | - | - | - | - | - | - | - | - | 07-FEB-21:49 |
Heating | 0.00 | 157640.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 145562.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 45424.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 87982.85 | 87619.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31568.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 33311.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 5844.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 39669.30 | 98999.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1668.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 412066.93 | 344259.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 157640.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 145562.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 45424.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58308.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1264.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 33311.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 5844.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4013.31 | 98999.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 768.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 658.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 629.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4335.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1722.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 552.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5473.02 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2031.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1870.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 386.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 448.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1530.86 | 1033.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 138.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 18489.29 | 3602.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 55.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 382.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 151.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 164.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 34.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 39.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 134.93 | 91.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1629.69 | 317.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 55.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 382.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 151.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 164.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 34.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 39.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 134.93 | 91.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1629.69 | 317.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.31 | 0.652036 | 0.501000 | 1.16 | 1.00 | 0.500000 | 0.000584 | 0.000046 | 1.16 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.341665 | 0.149586 | 0.501000 | 0.171174 | 0.501000 | 0.500000 | 0.002547 | 0.000028 | 0.171174 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.250689 | 0.236084 | 0.501000 | 0.125595 | 0.629557 | 0.500000 | 0.001614 | 0.000012 | 0.125595 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.224261 | 0.558069 | 0.501000 | 0.112355 | 1.00 | 0.500000 | 0.000683 | 0.000018 | 0.112355 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.121897 | 0.592356 | 0.501000 | 0.061070 | 1.00 | 0.500000 | 0.000643 | 0.000011 | 0.061070 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.76 | 0.062696 | 0.501000 | 1.89 | 0.501000 | 0.500000 | 0.024114 | 0.000093 | 1.89 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.53 | 0.094046 | 0.501000 | 0.766646 | 0.501000 | 0.500000 | 0.004051 | 0.000085 | 0.766646 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.11 | 0.195021 | 0.501000 | 2.56 | 0.520057 | 0.500000 | 0.001954 | 0.000230 | 2.56 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.32 | 0.898692 | 0.501000 | 0.661672 | 1.00 | 0.500000 | 0.000424 | 0.000103 | 0.661672 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.47 | 0.102245 | 0.501000 | 1.24 | 0.501000 | 0.500000 | 0.003726 | 0.000100 | 1.24 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.59 | 0.097434 | 0.501000 | 1.30 | 0.501000 | 0.500000 | 0.003910 | 0.000104 | 1.30 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.47 | 0.057232 | 0.501000 | 1.24 | 0.501000 | 0.500000 | 0.011974 | 0.000070 | 1.24 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.777146 | 0.404093 | 0.501000 | 0.389350 | 1.00 | 0.500000 | 0.000943 | 0.000070 | 0.389350 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 5305.35 | 0.000046 | 110.63 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3239.16 | 0.000028 | 80.95 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1388.82 | 0.000012 | 31.27 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2021.65 | 0.000018 | 49.87 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1227.07 | 0.000011 | 31.18 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10596.53 | 0.000093 | 223.61 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 9703.64 | 0.000085 | 222.94 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 26288.67 | 0.000230 | 586.16 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 5313.34 | 0.000046 | 151.81 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 5307.67 | 0.000046 | 151.64 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 30868.44 | 0.000270 | 881.93 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 30776.99 | 0.000269 | 879.32 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 5302.65 | 0.000046 | 151.50 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 5296.99 | 0.000046 | 151.34 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 11780.35 | 0.000103 | 289.82 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1680.92 | 0.000015 | 48.02 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1680.21 | 0.000015 | 48.00 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8127.84 | 0.000071 | 232.22 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 11477.66 | 0.000100 | 252.83 |
DINING_FLR_6 VAV BOX REHEAT COIL | 11891.80 | 0.000104 | 261.58 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8056.43 | 0.000070 | 171.75 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7979.58 | 0.000070 | 203.98 |
VAV WITH REHEAT HEATING COIL | 159759.88 | 0.001398 | 2712.09 |
FLR_3_DOAS HEATING COIL | 14143.00 | 0.000124 | 240.09 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.09 | 0.000046 | 0.000379 |
ROOM_2_FLR_3 FAN COIL | 1.08 | 0.000046 | 0.000376 |
ROOM_3_MULT19_FLR_3 FAN COIL | 5.98 | 0.000270 | 0.002043 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.58 | 0.000269 | 0.002395 |
ROOM_5_FLR_3 FAN COIL | 0.953191 | 0.000046 | 0.000333 |
ROOM_6_FLR_3 FAN COIL | 0.946030 | 0.000046 | 0.000330 |
ROOM_1_FLR_6 FAN COIL | 0.291266 | 0.000015 | 0.000101 |
ROOM_2_FLR_6 FAN COIL | 0.288632 | 0.000015 | 0.000100 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.27 | 0.000071 | 0.000452 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.09 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.08 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.98 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.58 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 0.953191 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.946030 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.291266 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.288632 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.27 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008570 | 12.80 | 0.008500 | 0.000379 | 1.09 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008571 | 12.80 | 0.008500 | 0.000376 | 1.08 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008492 | 12.80 | 0.008492 | 0.002043 | 5.98 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008739 | 12.80 | 0.008500 | 0.002395 | 6.58 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008580 | 12.80 | 0.008500 | 0.000333 | 0.953191 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008580 | 12.80 | 0.008500 | 0.000330 | 0.946030 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008565 | 12.80 | 0.008500 | 0.000101 | 0.291266 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008566 | 12.80 | 0.008500 | 0.000100 | 0.288632 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008642 | 12.80 | 0.008500 | 0.000452 | 1.27 | |
VAV WITH REHEAT COOLING COIL | 31.09 | 6.70 | 0.008295 | 10.70 | 0.008295 | 0.017983 | 23.17 | 503486.67 |
FLR_3_DOAS COOLING COIL | 38.10 | 6.70 | 0.006871 | 11.79 | 0.006871 | 0.002048 | 2.05 | 57348.72 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.67 | 11.67 | 23.29 | 11.67 | 23.17 | 23.17 | 0.300000 | 0.503637 | 23.17 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 23.17 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 23.17 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.017983 | 0.000026 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001398 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002048 | 0.000232 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000124 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Size Rated Evaporator Air Flow Rate [m3/s] | Design Size Rated Condenser Water Flow Rate [m3/s] | |
SWHSYSLAUNDRY HPWH DXCOIL | 4.90 | 0.004370 |
SWHSYS1 HPWH DXCOIL | 3.87 | 0.003451 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
SWHSYSLAUNDRY HPWH FAN | 4.90 | 700.51 |
SWHSYS1 HPWH FAN | 3.87 | 553.22 |
Condenser water flow rate [m3/s] | Evaporator air flow rate [m3/s] | |
SWHSYS1 HPWH | 0.003451 | 3.87 |
SWHSYSLAUNDRY HPWH | 0.004370 | 4.90 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.026542 | 5415.09 | |
HEATSYS1 PUMP | 0.003318 | 989.20 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003318 | 0.398104 |
COOLSYS1 | 0.026542 | 3.18 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 379214.65 | 379214.65 | 0.003318 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.026542 | 3749.05 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.026542 | 743094.23 | 743730.93 | 84.79 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 HPWH TANK | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 5.980 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 11.360 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 8.730 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 19.490 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 8.730 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 19.490 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.166 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 9.546 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 3.681 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.371 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.134 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.664 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 8.331 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 13.711 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 8.138 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.208 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 3.972 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.492 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 3.972 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.492 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 3.972 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.972 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 3.972 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.492 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 8.331 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 76.151 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 8.331 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 76.151 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 10.559 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2942.062 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 3.972 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.972 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 11832.934 | 5.980 | 111.108 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11832.934 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 585.501 | 8.730 | 54.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 585.501 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 678.012 | 8.730 | 54.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 678.012 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 684.177 | 4.166 | 257.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 684.177 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 348.833 | 3.681 | 170.996 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 348.833 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 400.685 | 5.134 | 47.701 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 400.685 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1573.457 | 8.331 | 11.057 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1573.457 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 10645.380 | 8.138 | 25.200 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10645.380 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 154.991 | 3.972 | 103.327 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.991 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 154.973 | 3.972 | 103.315 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.973 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 97.406 | 3.972 | 64.937 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 97.406 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 97.432 | 3.972 | 64.955 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 97.432 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 154.991 | 3.972 | 103.327 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.991 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 154.973 | 3.972 | 103.315 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.973 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1546.669 | 3.972 | 73.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1546.669 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 154.991 | 3.972 | 103.327 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.991 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 154.973 | 3.972 | 103.315 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.973 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 97.432 | 3.972 | 64.955 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 97.432 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 2763.123 | 8.331 | 11.057 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2763.123 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 2763.123 | 8.331 | 11.057 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2763.123 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1090.832 | 10.559 | 49.053 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1090.832 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1636.910 | 3.972 | 73.801 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1636.910 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 1.067 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.370 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.442 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.217 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.286 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7702 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5624 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5260 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6546 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6103 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | -0.55514967E-15 | 0.35055860E-16 | -0.14326465E-09 | 0.28783368E-17 |
29 | 8 | 0.20966873E-07 | 0.14258959E-12 | 0.36819155E-03 | -0.23840058E-09 |
30 | 7 | -0.11954852E-01 | 0.74774803E-08 | -0.22672946E-01 | 0.13593102E-03 |
31 | 6 | 0.39755982 | 0.26159305E-05 | 0.46545104 | -0.46559307E-02 |
32 | 5 | -5.1145337 | 0.98147117E-04 | -4.3902405 | 0.62241115E-01 |
33 | 4 | 32.666535 | 0.80637729E-03 | 21.240866 | -0.41765750 |
34 | 3 | -110.51061 | 0.17642800E-02 | -55.229641 | 1.5048560 |
35 | 2 | 196.42192 | 0.99585215E-03 | 77.513220 | -2.8894543 |
36 | 1 | -170.90254 | 0.10665179E-03 | -55.149704 | 2.7409959 |
37 | 0 | 57.057407 | 0.60929387E-06 | 15.576129 | |
38 | 9 | 0.10314710E-14 | 0.47183642E-16 | -0.12881513E-09 | -0.40099708E-17 |
39 | 8 | 0.18927665E-07 | 0.17950474E-12 | 0.34608657E-03 | -0.21521408E-09 |
40 | 7 | -0.11292911E-01 | 0.96443222E-08 | -0.21719088E-01 | 0.12840450E-03 |
41 | 6 | 0.37957032 | 0.34070209E-05 | 0.45007157 | -0.44438791E-02 |
42 | 5 | -4.9389364 | 0.12890179E-03 | -4.2718596 | 0.60063826E-01 |
43 | 4 | 31.889569 | 0.10670331E-02 | 20.777560 | -0.40734193 |
44 | 3 | -108.85680 | 0.23501275E-02 | -54.313423 | 1.4809641 |
45 | 2 | 194.78196 | 0.13343675E-02 | 76.673975 | -2.8634131 |
46 | 1 | -170.29645 | 0.14368413E-03 | -54.907648 | 2.7303734 |
47 | 0 | 57.057407 | 0.82565881E-06 | 15.617726 | |
48 | 9 | 0.86975537E-15 | 0.52023775E-16 | -0.12536948E-09 | -0.54620444E-17 |
49 | 8 | 0.18440443E-07 | 0.18784465E-12 | 0.34068694E-03 | -0.20967419E-09 |
50 | 7 | -0.11130813E-01 | 0.10155400E-07 | -0.21485363E-01 | 0.12656138E-03 |
51 | 6 | 0.37516444 | 0.35965268E-05 | 0.44629465 | -0.43919449E-02 |
52 | 5 | -4.8959230 | 0.13636263E-03 | -4.2427425 | 0.59530495E-01 |
53 | 4 | 31.699203 | 0.11309484E-02 | 20.663505 | -0.40481456 |
54 | 3 | -108.45147 | 0.24950915E-02 | -54.087828 | 1.4751087 |
55 | 2 | 194.37988 | 0.14187814E-02 | 76.467519 | -2.8570287 |
56 | 1 | -170.14779 | 0.15298304E-03 | -54.848449 | 2.7277680 |
57 | 0 | 57.057407 | 0.88039223E-06 | 15.628184 | |
58 | 9 | 0.12430042E-14 | 0.43603463E-16 | -0.13615479E-09 | -0.52742981E-17 |
59 | 8 | 0.19963588E-07 | 0.16114398E-12 | 0.35741204E-03 | -0.22699287E-09 |
60 | 7 | -0.11632381E-01 | 0.85488282E-08 | -0.22208377E-01 | 0.13226440E-03 |
61 | 6 | 0.38879653 | 0.30047059E-05 | 0.45796739 | -0.45526330E-02 |
62 | 5 | -5.0290001 | 0.11318598E-03 | -4.3326723 | 0.61180550E-01 |
63 | 4 | 32.288109 | 0.93328928E-03 | 21.015642 | -0.41263319 |
64 | 3 | -109.70522 | 0.20484795E-02 | -54.784283 | 1.4932205 |
65 | 2 | 195.62339 | 0.11595496E-02 | 77.105128 | -2.8767741 |
66 | 1 | -170.60747 | 0.12450863E-03 | -55.031726 | 2.7358244 |
67 | 0 | 57.057407 | 0.71328115E-06 | 15.596176 | |
68 | 9 | 0.10418955E-14 | 0.45554749E-16 | -0.13285794E-09 | -0.34221686E-17 |
69 | 8 | 0.19498290E-07 | 0.16949498E-12 | 0.35235048E-03 | -0.22170227E-09 |
70 | 7 | -0.11480752E-01 | 0.90423087E-08 | -0.21989859E-01 | 0.13054032E-03 |
71 | 6 | 0.38467563 | 0.31853038E-05 | 0.45444290 | -0.45040579E-02 |
72 | 5 | -4.9887746 | 0.12022067E-03 | -4.3055366 | 0.60681782E-01 |
73 | 4 | 32.110117 | 0.99300969E-03 | 20.909427 | -0.41027004 |
74 | 3 | -109.32633 | 0.21828955E-02 | -54.574228 | 1.4877470 |
75 | 2 | 195.24766 | 0.12373115E-02 | 76.912747 | -2.8708078 |
76 | 1 | -170.46860 | 0.13302463E-03 | -54.976289 | 2.7333905 |
77 | 0 | 57.057407 | 0.76310210E-06 | 15.605744 | |
78 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
79 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
80 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
81 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
82 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
83 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
84 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
85 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
86 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
87 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
88 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
89 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
90 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
91 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
92 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
93 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.4295_SHGC_0.25 | 37 | 1 | VerySmooth | 2.441 | 2.441 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.4295_SHGC_0.25 | 38 | 1 | VerySmooth | 2.441 | 2.441 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.91738E-002 | 0.16139 | 0.61970 | 0.61970 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12244 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.91738E-002 | 0.16139 | 0.61970 | 0.61970 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12244 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | "DX Coil Total Cooling Rate {W | HPWH Only}" | |
1 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | 1.1400 | 73637.3 | 48.891 | 1.6822 | 76621 | |
2 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | 2.8400 | 60651.4 | 4.618 | 9.2460 | 53264 |
Node Number | Height {m} | Volume {m3} | Maximum Capacity {W} | Off-Cycle UA {W/K} | On-Cycle UA {W/K} | Number Of Inlets | Number Of Outlets | |
1 | 1 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 0 | 1 |
2 | 2 | 0.2683 | 0.4733 | 39204.770 | 1.5573 | 1.5573 | 0 | 0 |
3 | 3 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
4 | 4 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
5 | 5 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 1 |
6 | 6 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 2 | 0 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 9.802E-003 | 1.461E-004 | 7.212E-005 | 0.133 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 3.784E-003 | 4.872E-005 | 1.327E-004 | 4.426E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 8.942E-003 | 5.445E-005 | 1.424E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 5.159E-003 | 5.445E-005 | 1.182E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 1.221E-002 | 1.565E-004 | 1.392E-004 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 2.167E-002 | 1.147E-004 | 6.318E-005 | 0.104 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 6.191E-002 | 4.733E-005 | 9.051E-005 | 4.300E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.587E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.588E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 6.879E-003 | 1.766E-005 | 1.424E-004 | 2.086E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 2.910E-003 | 1.186E-004 | 6.472E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1.243E-002 | 1.204E-004 | 6.523E-005 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1.217E-002 | 2.953E-005 | 2.446E-005 | 3.488E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 8.5405E-002 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.8071E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.4529E-002 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.1339E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 6.5404E-002 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.4194E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.6511E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.7811E-003 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 9.6576E-002 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.6681E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1072 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.0654E-002 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.2445E-002 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.0583E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 2.9789E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.2036E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.0964E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.1972E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.6150E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.0418E-003 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.5433E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.1646E-003 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.6108E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.2309E-003 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.0964E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.1972E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.6150E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.0418E-003 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.5433E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.1646E-003 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.6108E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.2309E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 27603.10237 | 27603.10237 | 2.31255 | 2.31255 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 30.43000 | 6.85931E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4077.79443 | 4077.79443 | 0.34166 | 0.34166 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2455.53049 | 2455.53049 | 0.12136 | 0.12136 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 2991.92885 | 2991.92885 | 0.25069 | 0.25069 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 35.19667 | 6.86684E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 813.84552 | 813.84552 | 4.02226E-002 | 9.17347E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2677.14474 | 2677.14474 | 0.22426 | 0.22426 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:10:00 | 31.40500 | 6.86084E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1507.32717 | 1507.32717 | 7.44964E-002 | 7.44964E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1455.14825 | 1455.14825 | 0.12190 | 0.12190 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 35.63000 | 6.86752E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 947.50269 | 947.50269 | 4.68283E-002 | 5.77652E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44926.07986 | 44926.07986 | 3.76376 | 3.76376 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 36.28000 | 6.86857E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1965.04644 | 1965.04644 | 9.71174E-002 | 9.71174E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 18246.90290 | 18246.90290 | 1.53023 | 1.53023 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 6193.82122 | 6193.82122 | 0.30611 | 0.67639 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 60985.44664 | 60985.44664 | 5.11143 | 5.11143 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 14565.02731 | 14565.02731 | 0.71985 | 1.89399 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 9633.30373 | 9633.30373 | 1.08750 | 1.08750 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5313.35240 | 5313.35240 | 0.26414 | 0.26414 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 9555.57341 | 9555.57341 | 1.07873 | 1.07873 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5307.68798 | 5307.68798 | 0.26386 | 0.26386 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 53003.19424 | 53003.19424 | 5.98324 | 5.98324 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 30868.47683 | 30868.47683 | 1.53457 | 1.53457 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 58268.24331 | 58268.24331 | 6.57813 | 6.57813 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 37.71000 | 6.87086E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 30777.03341 | 30777.03341 | 1.53003 | 1.53003 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 8443.55324 | 8443.55324 | 0.95319 | 0.95319 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 33.48500 | 6.86412E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5302.66677 | 5302.66677 | 0.26361 | 0.26361 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 8380.12104 | 8380.12104 | 0.94603 | 0.94603 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 33.16000 | 6.86360E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5297.00099 | 5297.00099 | 0.26333 | 0.26333 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 15764.60344 | 15764.60344 | 1.32070 | 1.32070 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 37.84000 | 6.87107E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 8750.97470 | 8750.97470 | 0.43250 | 0.47476 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2580.09283 | 2580.09283 | 0.29127 | 0.29127 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80000 | 6.86940E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1680.92845 | 1680.92845 | 8.35637E-002 | 8.35637E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2556.75998 | 2556.75998 | 0.28863 | 0.28863 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1680.21877 | 1680.21877 | 8.35285E-002 | 8.35285E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 11280.75462 | 11280.75462 | 1.27352 | 1.27352 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 8127.85476 | 8127.85476 | 0.40406 | 0.40406 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29465.18446 | 29465.18446 | 2.47175 | 2.47175 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.87148E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5807.89761 | 5807.89761 | 0.28704 | 1.18780 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30920.61377 | 30920.61377 | 2.59380 | 2.59380 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.87148E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 5942.07318 | 5942.07318 | 0.29367 | 1.18780 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 29447.62768 | 29447.62768 | 2.47385 | 2.47385 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 36.93000 | 6.86961E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2389.64020 | 2389.64020 | 0.11809 | 0.36735 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -5.20000 | 2.80840E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 9276.52989 | 9276.52989 | 0.77715 | 0.77715 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 38.10000 | 6.87148E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 6196.89441 | 6196.89441 | 0.30627 | 0.30627 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 444750.29 | 23.17176 | 23.17176 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 169866.32 | 7.39128 | 7.39128 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 54460.49 | 17.99005 | 2.05125 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 47141.68 | 4.69069 | 2.05125 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.31255 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.65204 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50100 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.15859 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.84324E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.64135E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.15859 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5305.34834 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.64135E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 110.63389 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.34166 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14959 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50100 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17117 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50100 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.54703E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.83376E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17117 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3239.16439 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.83376E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 80.95081 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.25069 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23608 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50100 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12560 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62956 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.61383E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21500E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12560 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1388.81882 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21500E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 31.27148 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22426 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.55807 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50100 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11235 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.82711E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.76863E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11235 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2021.65162 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.76863E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 49.86750 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.12190 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.59236 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50100 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.10705E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.43194E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.07349E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.10705E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1227.07047 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.07349E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 31.18426 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.76376 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.26962E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50100 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.88564 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50100 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.41145E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.27031E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.88564 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10596.53058 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.27031E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 223.60824 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.53023 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.40464E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50100 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76665 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50100 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.05119E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.48917E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.76665 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9703.63960 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.48917E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 222.94009 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.11143 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19502 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50100 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.56083 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52006 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.95363E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.29985E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.56083 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26288.66528 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.29985E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 586.16221 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.08750 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.08750 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.64834E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.78635E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77070 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57017E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.78635E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.08750 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5313.33766 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.64834E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 151.80680 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.07873 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.07873 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.64338E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.75631E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77069 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57067E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.75631E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.07873 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5307.67326 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.64338E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 151.64497 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.98324 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.98324 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.70051E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.04346E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77117 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.49238E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.49238E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.04346E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.98324 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 30868.43598 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.70051E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 881.93475 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.57813 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.57813 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.69251E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.39533E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77018 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.73881E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.39533E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.57813 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 30776.99267 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.69251E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 879.32233 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.95319 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.95319 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.63899E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.32745E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77068 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57984E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.32745E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.95319 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5302.65206 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.63899E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 151.50153 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.94603 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.94603 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.63403E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.30297E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77068 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58042E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.30297E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.94603 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5296.98629 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.63403E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 151.33966 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.32070 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.89869 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50100 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.66167 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.23950E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.03060E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.66167 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11780.35448 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03060E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 289.81695 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.29127 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.29127 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.47055E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.01281E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77071 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56549E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.01281E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.29127 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1680.92400 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.47055E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 48.02481 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.28863 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.28863 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.46992E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.00382E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77070 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56611E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.00382E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.28863 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1680.21432 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.46992E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 48.00454 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.27352 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.27352 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.11059E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.52103E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.77036 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.64239E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.52103E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.27352 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8127.83773 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.11059E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 232.21576 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.47175 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10224 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50100 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.23835 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50100 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.72636E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00412E-004 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.23835 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11477.66226 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00412E-004 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 252.82594 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.59380 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.74337E-002 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50100 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.29949 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50100 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.91035E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.04035E-004 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.29949 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11891.80224 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.04035E-004 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 261.57683 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.47385 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.72324E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50100 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.23940 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50100 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19736E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.04811E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.23940 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8056.42774 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.04811E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 171.74584 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77715 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.40409 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50100 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.38935 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.42852E-004 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.98088E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.38935 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7979.57997 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.98088E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 203.97816 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.67016 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.67016 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 23.29373 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.67016 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 23.17176 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 23.17176 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.50364 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 23.17176 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 23.17176 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 31.09001 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.69708 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.29523E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.29523E-003 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 503486.66760 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.79834E-002 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 23.17176 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 159759.87902 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.39765E-003 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2712.08887 |
350 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 23.17176 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.79834E-002 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.64795E-005 |
353 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.39765E-003 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
356 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 38.10000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.79311 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.87148E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.87148E-003 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 57348.72296 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.04836E-003 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 14143.00265 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.23729E-004 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 240.09207 |
368 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.04836E-003 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.32474E-004 |
371 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.23729E-004 |
372 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 4.90359 |
373 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 4.36989E-003 |
374 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.90359 |
375 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Electric Power Consumption [W] | 700.51236 |
376 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 3.87257 |
377 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 3.45109E-003 |
378 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.87257 |
379 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Electric Power Consumption [W] | 553.22422 |
380 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Condenser water flow rate [m3/s] | 3.45109E-003 |
381 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Evaporator air flow rate [m3/s] | 3.87257 |
382 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.65416E-002 |
383 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 5415.08996 |
384 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.31754E-003 |
385 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.39810 |
386 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.31754E-003 |
387 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 989.20387 |
388 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
389 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 379214.65141 |
390 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 379214.65000 |
391 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.31754E-003 |
392 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.65416E-002 |
393 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.18499 |
394 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.65416E-002 |
395 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3749.04942 |
396 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.65416E-002 |
397 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 743094.22615 |
398 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 743730.93000 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 84.78533 |
400 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
401 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
402 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
403 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
404 | WaterHeater:Stratified | SWHSYS1 HPWH TANK | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
405 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Condenser water flow rate [m3/s] | 4.36989E-003 |
406 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Evaporator air flow rate [m3/s] | 4.90359 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 5333.08 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3253.63 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1395.60 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2030.77 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1232.49 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10651.46 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 9750.33 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 26418.00 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 5723.98 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 5717.88 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 33254.05 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 33155.54 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 5712.47 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 5706.36 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 11833.57 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1810.82 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1810.05 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8755.92 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 11534.67 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 11950.93 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8097.90 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8014.69 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 120319.28 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 10651.46 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 18431.71 | 13918.75 | 4512.96 | 0.76 | 2951.17 | 29.93 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 18284.59 | 13807.00 | 4477.59 | 0.76 | 2927.38 | 29.69 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 100230.91 | 76190.46 | 24040.45 | 0.76 | 16289.13 | 165.21 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 114740.82 | 85342.51 | 29398.31 | 0.74 | 17932.90 | 181.89 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 16182.63 | 12209.27 | 3973.35 | 0.75 | 2587.08 | 26.24 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 16062.67 | 12118.12 | 3944.55 | 0.75 | 2567.67 | 26.04 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4932.52 | 3726.45 | 1206.07 | 0.76 | 790.36 | 8.02 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4888.45 | 3692.94 | 1195.51 | 0.76 | 783.22 | 7.94 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21859.26 | 16397.06 | 5462.20 | 0.75 | 3464.18 | 35.14 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 620084.31 | 384358.21 | 235726.10 | 0.62 | 88900.55 | 901.68 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 51198.70 | 32051.32 | 19147.38 | 0.63 | 5018.41 | 50.90 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.370 | 1.137 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.370 | 1.137 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.370 | 1.137 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.370 | 1.137 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.6990754550E-002 | 2.3158509014E-002 | Pass | Pass | 6.6179366100E-003 | 1.7953422759E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.7660555681E-002 | 7.8740988627E-002 | Pass | Pass | 1.9056962082E-002 | 2.0346374891E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.4956117895E-002 | 2.8595076000E-002 | Pass | Pass | 7.1112204118E-003 | 1.7652664875E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.3058183122E-002 | 1.4808516921E-002 | Pass | Pass | 7.7732825505E-003 | 2.1702843378E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.4030919860E-003 | 8.9356555754E-003 | Pass | Pass | 7.6269804845E-003 | 2.1765036219E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.6157491423E-002 | 0.1957359437 | Pass | Pass | 1.9422629788E-002 | 5.1108771720E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.8743887693E-002 | 7.1339267484E-002 | Pass | Pass | 1.5194074434E-002 | 2.1561299947E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.1520394675E-002 | 4.0768347587E-002 | Pass | Pass | 9.1460302071E-003 | 1.9270634066E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.3356502083E-002 | 0.2311526992 | Pass | Pass | 0.1599215267 | 0.3741077335 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.7344395774E-002 | 0.1800208287 | Pass | Pass | 0.2721274707 | 1.3530422053 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.6193242057E-003 | 1.8704338285E-002 | Pass | Pass | 0.1005018652 | 0.2653839765 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.4333609030E-002 | 0.1369769463 | Pass | Pass | 0.2335516941 | 1.5726421286 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.3616960428E-002 | 0.2347033250 | Pass | Pass | 0.3262447555 | 1.6242876855 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.4202130109E-002 | 6.6888218122E-002 | Pass | Pass | 0.3001165743 | 0.8543224563 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.1800577345E-002 | 1.1106541994E-002 | Pass | Pass | 7.6238640871E-003 | 2.0535680337E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.6782151464E-002 | 0.2064816138 | Pass | Pass | 0.1179941762 | 0.2174588081 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.6709508621E-002 | 0.1924952450 | Pass | Pass | 0.1227453138 | 0.2693391935 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.2753714127E-002 | 0.2936559740 | Pass | Pass | 0.1791312336 | 0.7275442263 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.4787151905E-002 | 6.2408995391E-002 | Pass | Pass | 1.4375850596E-002 | 4.2762021127E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.6787532647E-002 | 4.8615551282E-002 | Pass | Pass | 1.4334717432E-002 | 4.1386731237E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.1504965409E-002 | 6.2658510114E-002 | Pass | Pass | 2.0888306950E-002 | 4.2038537839E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.0098613250E-002 | 2.0917853243E-002 | Pass | Pass | 1.2289232795E-002 | 2.2742141246E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3227.13 | 19.74 | 781.04 | 3882.75 | 5978.32 | 13889.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.441 | 0.251 | 0.251 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.441 | 0.251 | 0.251 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.441 | 0.251 | 0.251 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.441 | 0.251 | 0.251 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.441 | 0.251 | 0.251 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.441 | 0.251 | 0.251 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.441 | 0.251 | 0.251 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.441 | 0.251 | 0.251 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.441 | 0.251 | 0.251 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.441 | 0.251 | 0.251 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.441 | 0.251 | 0.251 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.441 | 0.251 | 0.251 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.441 | 0.251 | 0.251 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.441 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.441 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.441 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.441 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.441 | 0.251 | 0.251 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.441 | 0.251 | 0.251 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.441 | 0.251 | 0.251 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.441 | 0.251 | 0.251 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.441 | 0.251 | 0.251 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.441 | 0.251 | 0.251 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.441 | 0.251 | 0.251 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.441 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.441 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.441 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.441 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.441 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.441 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.441 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 432.95 | 2.441 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.441 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.9798 | 1978.83 | 11832.93 | LightsWired | LTG_SCH_BASEMENT | 45.99 | 168.00 | 45.94 | 0.0000 | Y | 102.03 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 8.7295 | 67.07 | 585.50 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 5.64 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 8.7295 | 77.67 | 678.01 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 6.53 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.1656 | 164.24 | 684.18 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 7.53 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 3.6813 | 94.76 | 348.83 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 1.68 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.1344 | 78.04 | 400.68 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.41 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 8.3313 | 188.86 | 1573.46 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.73 | 0.0000 | Y | 11.73 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 8.1375 | 1308.19 | 10645.38 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 55.44 | 0.0000 | Y | 110.78 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 3.9719 | 156.09 | 619.96 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 5.55 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 3.9719 | 156.07 | 619.89 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 5.55 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 3.9719 | 1863.81 | 7402.84 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 66.32 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 3.9719 | 1864.32 | 7404.86 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 66.33 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 3.9719 | 156.09 | 619.96 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 5.55 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 3.9719 | 156.07 | 619.89 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 5.55 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 3.9719 | 1557.62 | 6186.67 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 51.06 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 3.9719 | 39.02 | 154.99 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.39 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 3.9719 | 39.02 | 154.97 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.39 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 3.9719 | 220.77 | 876.89 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 7.86 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 8.3313 | 331.66 | 2763.12 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.52 | 0.0000 | Y | 25.69 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 8.3313 | 331.66 | 2763.12 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.52 | 0.0000 | Y | 25.69 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 10.5594 | 103.30 | 1090.83 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.00 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 3.9719 | 412.12 | 1636.91 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 13.51 |
Interior Lighting Total | 5.2589 | 11345.29 | 59663.90 | 350.93 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 10645.38 | 745.18 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 10645.38 | 745.18 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1573.46 | 613.65 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1573.46 | 613.65 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2763.12 | 552.62 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2763.12 | 552.62 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2763.12 | 552.62 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2763.12 | 552.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 11096.45 | AstronomicalClock | - | 83.77 | 83.77 | 174.48 | |
Exterior Lighting Total | 11096.45 | 174.48 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 379214.65 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 743730.93 | 2.96 | 743861.66 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10600.96 | 18431.71 | 13918.75 | 4512.96 | 0.76 | - | 2951.17 | 29.93 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10516.85 | 18284.59 | 13807.00 | 4477.59 | 0.76 | - | 2927.38 | 29.69 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 57212.48 | 100230.91 | 76190.46 | 24040.45 | 0.76 | - | 16289.13 | 165.21 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 67064.17 | 114740.82 | 85342.51 | 29398.31 | 0.74 | - | 17932.90 | 181.89 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9316.14 | 16182.63 | 12209.27 | 3973.35 | 0.75 | - | 2587.08 | 26.24 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9247.61 | 16062.67 | 12118.12 | 3944.55 | 0.75 | - | 2567.67 | 26.04 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2835.64 | 4932.52 | 3726.45 | 1206.07 | 0.76 | - | 790.36 | 8.02 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2810.47 | 4888.45 | 3692.94 | 1195.51 | 0.76 | - | 783.22 | 7.94 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 12657.91 | 21859.26 | 16397.06 | 5462.20 | 0.75 | - | 3464.18 | 35.14 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 503486.67 | 620084.31 | 384358.21 | 235726.10 | 0.62 | - | 88900.55 | 901.68 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 57348.72 | 51198.70 | 32051.32 | 19147.38 | 0.63 | - | 5018.41 | 50.90 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 5305.35 | 5333.08 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3239.16 | 3253.63 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1388.82 | 1395.60 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2021.65 | 2030.77 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1227.07 | 1232.49 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10596.53 | 10651.46 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9703.64 | 9750.33 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 26288.67 | 26418.00 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5313.34 | 5723.98 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5307.67 | 5717.88 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 30868.44 | 33254.05 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 30776.99 | 33155.54 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5302.65 | 5712.47 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5296.99 | 5706.36 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 11780.35 | 11833.57 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1680.92 | 1810.82 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1680.21 | 1810.05 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 8127.84 | 8755.92 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11477.66 | 11534.67 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11891.80 | 11950.93 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8056.43 | 8097.90 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7979.58 | 8014.69 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 159759.88 | 120319.28 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 14143.00 | 10651.46 | - |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 75921.46 | 3.40 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 54370.95 | 3.40 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.09 | 765.20 | 703.64 | 1.00 | 1.18 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.08 | 759.03 | 703.64 | 1.00 | 1.18 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.98 | 4210.02 | 703.64 | 1.00 | 0.96 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.58 | 4628.61 | 703.64 | 1.00 | 0.95 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.95 | 670.70 | 703.64 | 1.00 | 1.21 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.95 | 665.66 | 703.64 | 1.00 | 1.21 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.29 | 204.95 | 703.64 | 1.00 | 1.73 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.29 | 203.09 | 703.64 | 1.00 | 1.74 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.27 | 896.09 | 703.64 | 1.00 | 1.14 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 23.17 | 51919.53 | 2240.64 | 1.00 | 1.11 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 4.90 | 700.51 | 142.86 | 0.00 | 2.78 | General | ||
SWHSYS1 HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 3.87 | 553.22 | 142.86 | 0.00 | 2.84 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.026542 | 5415.09 | 204022.71 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003318 | 989.20 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.026542 | 3749.05 | 141251.80 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYSLAUNDRY HPWH | WaterHeater:HeatPump:PumpedCondenser | 1.14 | 73637.31 | 0.80 | 48.89 | 1.68 |
SWHSYS1 HPWH | WaterHeater:HeatPump:PumpedCondenser | 2.84 | 60651.44 | 0.80 | 4.62 | 9.25 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 27603.10 | 27603.10 | 13.95 | 2.313 | 2.313 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 24.00 | 24.00 | 0.00937 | 30.43 | 0.00686 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4077.79 | 4077.79 | 60.80 | 0.342 | 0.342 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00909 | 37.99 | 0.00687 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 2991.93 | 2991.93 | 38.52 | 0.251 | 0.251 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 24.00 | 24.00 | 0.00944 | 35.20 | 0.00687 | 0.092 | 0.00 |
MECH_FLR_1 | 2677.14 | 2677.14 | 16.30 | 0.224 | 0.224 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:10:00 | 24.00 | 24.00 | 0.00871 | 31.41 | 0.00686 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1455.15 | 1455.15 | 15.36 | 0.122 | 0.122 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00880 | 35.63 | 0.00687 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44926.08 | 44926.08 | 575.68 | 3.764 | 3.764 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00854 | 36.28 | 0.00687 | 0.000 | 0.00 |
CAFE_FLR_1 | 18246.90 | 18246.90 | 96.62 | 1.530 | 1.530 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 23.99 | 0.01025 | 37.99 | 0.00687 | 0.676 | 0.00 |
LOBBY_FLR_1 | 60985.45 | 60985.45 | 46.62 | 5.111 | 5.111 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.99 | 0.01006 | 38.10 | 0.00687 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 9633.30 | 9633.30 | 246.87 | 1.088 | 1.088 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00857 | 36.63 | 0.00687 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 9555.57 | 9555.57 | 244.91 | 1.079 | 1.079 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00857 | 36.63 | 0.00687 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 53003.19 | 53003.19 | 2161.29 | 5.983 | 5.983 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 21.11 | 21.11 | 0.00849 | 38.10 | 0.00687 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 58268.24 | 58268.24 | 2375.33 | 6.578 | 6.578 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 21.11 | 21.11 | 0.00874 | 37.71 | 0.00687 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 8443.55 | 8443.55 | 216.38 | 0.953 | 0.953 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 21.11 | 21.11 | 0.00858 | 33.48 | 0.00686 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 8380.12 | 8380.12 | 214.78 | 0.946 | 0.946 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 21.11 | 21.11 | 0.00858 | 33.16 | 0.00686 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 15764.60 | 15764.60 | 40.48 | 1.321 | 1.321 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00970 | 37.84 | 0.00687 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2580.09 | 2580.09 | 66.12 | 0.291 | 0.291 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 21.11 | 21.11 | 0.00857 | 36.80 | 0.00687 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2556.76 | 2556.76 | 65.53 | 0.289 | 0.289 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00857 | 36.63 | 0.00687 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11280.75 | 11280.75 | 459.87 | 1.274 | 1.274 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 21.11 | 21.11 | 0.00864 | 38.10 | 0.00687 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29465.18 | 29465.18 | 88.84 | 2.472 | 2.472 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 23.98 | 0.01041 | 38.10 | 0.00687 | 1.188 | 0.00 |
DINING_FLR_6 | 30920.61 | 30920.61 | 93.23 | 2.594 | 2.594 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 23.98 | 0.01032 | 38.10 | 0.00687 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 29447.63 | 29447.63 | 285.06 | 2.474 | 2.474 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01014 | 36.93 | 0.00687 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9276.53 | 9276.53 | 22.51 | 0.777 | 0.777 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00903 | 38.10 | 0.00687 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 22.26 | 0.00281 | -5.20 | 0.00281 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2455.53 | 2455.53 | 36.61 | 0.121 | 0.121 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00789 | -5.20 | 0.00281 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 813.85 | 813.85 | 10.48 | 0.040 | 0.092 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00787 | -5.20 | 0.00281 | 0.092 | 0.00 |
MECH_FLR_1 | 1507.33 | 1507.33 | 9.18 | 0.074 | 0.074 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00784 | -5.20 | 0.00281 | 0.000 | 0.00 |
STORAGE_FLR_1 | 947.50 | 947.50 | 10.00 | 0.047 | 0.058 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00785 | -5.20 | 0.00281 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1965.05 | 1965.05 | 25.18 | 0.097 | 0.097 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00783 | -5.20 | 0.00281 | 0.000 | 0.00 |
CAFE_FLR_1 | 6193.82 | 6193.82 | 32.80 | 0.306 | 0.676 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00790 | -5.20 | 0.00281 | 0.676 | 0.00 |
LOBBY_FLR_1 | 14565.03 | 14565.03 | 11.13 | 0.720 | 1.894 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00788 | -5.20 | 0.00281 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5313.35 | 5313.35 | 136.16 | 0.264 | 0.264 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00788 | -5.20 | 0.00281 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5307.69 | 5307.69 | 136.03 | 0.264 | 0.264 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00788 | -5.20 | 0.00281 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 30868.48 | 30868.48 | 1258.71 | 1.535 | 1.535 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00789 | -5.20 | 0.00281 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 30777.03 | 30777.03 | 1254.64 | 1.530 | 1.530 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00789 | -5.20 | 0.00281 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5302.67 | 5302.67 | 135.89 | 0.264 | 0.264 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00788 | -5.20 | 0.00281 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5297.00 | 5297.00 | 135.76 | 0.263 | 0.263 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00788 | -5.20 | 0.00281 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 8750.97 | 8750.97 | 22.47 | 0.432 | 0.475 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00791 | -5.20 | 0.00281 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1680.93 | 1680.93 | 43.08 | 0.084 | 0.084 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00791 | -5.20 | 0.00281 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1680.22 | 1680.22 | 43.06 | 0.084 | 0.084 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00791 | -5.20 | 0.00281 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8127.85 | 8127.85 | 331.34 | 0.404 | 0.404 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00791 | -5.20 | 0.00281 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5807.90 | 5807.90 | 17.51 | 0.287 | 1.188 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00793 | -5.20 | 0.00281 | 1.188 | 0.00 |
DINING_FLR_6 | 5942.07 | 5942.07 | 17.92 | 0.294 | 1.188 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00793 | -5.20 | 0.00281 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 2389.64 | 2389.64 | 23.13 | 0.118 | 0.367 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00738 | -5.20 | 0.00281 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 6196.89 | 6196.89 | 15.04 | 0.306 | 0.306 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00794 | -5.20 | 0.00281 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 23.17 | 23.17 | 7.39 | 7.39 | 23.1718 | 11.6702 | 23.1718 | 0.5036 | 0.3000 |
FLR_3_DOAS | 17.99 | 2.05 | 4.69 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 5305.348 | 5305.348 | 1.158590 | 0.00004641 | 110.634 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5305.35 | 5305.35 | 1.158590 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 0.00 | 0.00 | 5335.17 | 5335.17 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3239.164 | 3239.164 | 0.171174 | 0.00002834 | 80.951 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3239.16 | 3239.16 | 0.171174 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00788828 | 44.2347 | 2455.53 | 0.00 | 3255.86 | 3255.86 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1388.819 | 1388.819 | 0.125595 | 0.00001215 | 31.271 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1388.82 | 1388.82 | 0.125595 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00787032 | 44.1349 | 813.85 | 0.00 | 1396.32 | 1396.32 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2021.652 | 2021.652 | 0.112355 | 0.00001769 | 49.867 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2021.65 | 2021.65 | 0.112355 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00783564 | 43.9429 | 1507.33 | 0.00 | 2032.12 | 2032.12 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1227.070 | 1227.070 | 0.061070 | 0.00001073 | 31.184 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1227.07 | 1227.07 | 0.061070 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00784876 | 44.0155 | 947.50 | 0.00 | 1233.37 | 1233.37 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10596.531 | 10596.531 | 1.885645 | 0.00009270 | 223.608 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10596.53 | 10596.53 | 1.885645 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00782815 | 43.9017 | 1965.05 | 0.00 | 10655.84 | 10655.84 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 9703.640 | 9703.640 | 0.766646 | 0.00008489 | 222.940 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 9703.64 | 9703.64 | 0.766646 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00790183 | 44.3096 | 6193.82 | 0.00 | 9755.70 | 9755.70 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 26288.665 | 26288.665 | 2.560826 | 0.00022998 | 586.162 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 26288.67 | 26288.67 | 2.560826 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00788118 | 44.1950 | 14565.03 | 0.00 | 26431.27 | 26431.27 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 10600.958 | -999.000 | 1.087500 | 0.00037863 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 10600.96 | 10452.55 | 1.087500 | 21.77 | 14.22 | 0.00857017 | 12.80 | 10.82 | 0.00850000 | 36.63 | 0.00686912 | 17.72 | 0.0000 | 21.11 | 0.00857017 | 47.6807 | 9633.30 | 0.00 | 12259.43 | 11647.52 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5313.338 | 5313.338 | 0.264142 | 0.00004648 | 151.807 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5313.34 | 5313.34 | 0.264142 | 21.11 | 13.39 | 0.00788100 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00788100 | 43.8941 | 5313.35 | 0.00 | 5727.95 | 5727.95 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 10516.853 | -999.000 | 1.078726 | 0.00037563 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 10516.85 | 10368.59 | 1.078726 | 21.77 | 14.22 | 0.00857067 | 12.80 | 10.82 | 0.00850000 | 36.63 | 0.00686912 | 17.72 | 0.0000 | 21.11 | 0.00857067 | 47.6835 | 9555.57 | 0.00 | 12162.05 | 11553.62 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5307.673 | 5307.673 | 0.263860 | 0.00004643 | 151.645 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5307.67 | 5307.67 | 0.263860 | 21.11 | 13.39 | 0.00788088 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00788088 | 43.8935 | 5307.69 | 0.00 | 5721.84 | 5721.84 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 57212.482 | -999.000 | 5.983237 | 0.00204346 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | 7/21 14:10:00 | 57212.48 | 57212.48 | 5.983237 | 21.77 | 14.16 | 0.00849238 | 12.80 | 10.81 | 0.00849238 | 38.10 | 0.00687148 | 18.17 | 0.0000 | 21.11 | 0.00849238 | 47.2526 | 53003.19 | 0.00 | 66264.20 | 64092.65 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 30868.436 | 30868.436 | 1.534572 | 0.00027005 | 881.935 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 30868.44 | 30868.44 | 1.534572 | 21.11 | 13.40 | 0.00789119 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00789119 | 43.9498 | 30868.48 | 0.00 | 33277.23 | 33277.23 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 67064.169 | -999.000 | 6.578132 | 0.00239533 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | unknown | 7/21 15:30:00 | 67064.17 | 63973.01 | 6.578132 | 21.77 | 14.36 | 0.00873881 | 12.80 | 10.82 | 0.00850000 | 37.71 | 0.00687086 | 18.05 | 0.0000 | 21.11 | 0.00873881 | 48.6069 | 58268.24 | 0.00 | 77321.26 | 70631.68 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 30776.993 | 30776.993 | 1.530026 | 0.00026925 | 879.322 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 30776.99 | 30776.99 | 1.530026 | 21.11 | 13.40 | 0.00789084 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00789084 | 43.9479 | 30777.03 | 0.00 | 33178.65 | 33178.65 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 9316.144 | -999.000 | 0.953191 | 0.00033274 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | unknown | 7/21 10:10:00 | 9316.14 | 9168.04 | 0.953191 | 21.77 | 14.23 | 0.00857984 | 12.80 | 10.82 | 0.00850000 | 33.48 | 0.00686412 | 16.74 | 0.0000 | 21.11 | 0.00857984 | 47.7338 | 8443.55 | 0.00 | 10771.55 | 10210.38 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5302.652 | 5302.652 | 0.263611 | 0.00004639 | 151.502 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5302.65 | 5302.65 | 0.263611 | 21.11 | 13.39 | 0.00788076 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00788076 | 43.8928 | 5302.67 | 0.00 | 5716.43 | 5716.43 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 9247.609 | -999.000 | 0.946030 | 0.00033030 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | 7/21 10:00:00 | 9247.61 | 9099.55 | 0.946030 | 21.77 | 14.23 | 0.00858042 | 12.80 | 10.82 | 0.00850000 | 33.16 | 0.00686360 | 16.64 | 0.0000 | 21.11 | 0.00858042 | 47.7370 | 8380.12 | 0.00 | 10692.19 | 10133.76 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5296.986 | 5296.986 | 0.263329 | 0.00004634 | 151.340 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5296.99 | 5296.99 | 0.263329 | 21.11 | 13.39 | 0.00788065 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00788065 | 43.8922 | 5297.00 | 0.00 | 5710.32 | 5710.32 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 11780.354 | 11780.354 | 0.661672 | 0.00010306 | 289.817 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 11780.35 | 11780.35 | 0.661672 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00791155 | 44.3631 | 8750.97 | 0.00 | 11841.39 | 11841.39 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2835.638 | -999.000 | 0.291266 | 0.00010128 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | 7/21 16:30:00 | 2835.64 | 2798.56 | 0.291266 | 21.77 | 14.22 | 0.00856549 | 12.80 | 10.82 | 0.00850000 | 36.80 | 0.00686940 | 17.78 | 0.0000 | 21.11 | 0.00856549 | 47.6550 | 2580.09 | 0.00 | 3279.57 | 3119.36 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1680.924 | 1680.924 | 0.083564 | 0.00001471 | 48.025 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1680.92 | 1680.92 | 0.083564 | 21.11 | 13.41 | 0.00790548 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00790548 | 44.0287 | 1680.93 | 0.00 | 1812.09 | 1812.09 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2810.473 | -999.000 | 0.288632 | 0.00010038 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 2810.47 | 2773.38 | 0.288632 | 21.77 | 14.22 | 0.00856611 | 12.80 | 10.82 | 0.00850000 | 36.63 | 0.00686912 | 17.72 | 0.0000 | 21.11 | 0.00856611 | 47.6584 | 2556.76 | 0.00 | 3250.42 | 3091.17 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1680.214 | 1680.214 | 0.083528 | 0.00001470 | 48.005 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1680.21 | 1680.21 | 0.083528 | 21.11 | 13.41 | 0.00790545 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00790545 | 44.0286 | 1680.22 | 0.00 | 1811.32 | 1811.32 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 12657.914 | -999.000 | 1.273518 | 0.00045210 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | 7/21 14:10:00 | 12657.91 | 12303.44 | 1.273518 | 21.77 | 14.28 | 0.00864239 | 12.80 | 10.82 | 0.00850000 | 38.10 | 0.00687148 | 18.17 | 0.0000 | 21.11 | 0.00864239 | 48.0777 | 11280.75 | 0.00 | 14620.92 | 13655.74 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 8127.838 | 8127.838 | 0.404060 | 0.00007111 | 232.216 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 8127.84 | 8127.84 | 0.404060 | 21.11 | 13.42 | 0.00790991 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00790991 | 44.0530 | 8127.85 | 0.00 | 8762.08 | 8762.08 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11477.662 | 11477.662 | 1.238347 | 0.00010041 | 252.826 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 11477.66 | 11477.66 | 1.238347 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00793246 | 44.4790 | 5807.90 | 0.00 | 11540.23 | 11540.23 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11891.802 | 11891.802 | 1.299491 | 0.00010403 | 261.577 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 11891.80 | 11891.80 | 1.299491 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00793396 | 44.4873 | 5942.07 | 0.00 | 11956.67 | 11956.67 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 8056.428 | 8056.428 | 1.239397 | 0.00007048 | 171.746 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 8056.43 | 8056.43 | 1.239397 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00737699 | 41.4048 | 2389.64 | 0.00 | 8101.36 | 8101.36 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7979.580 | 7979.580 | 0.389350 | 0.00006981 | 203.978 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 7979.58 | 7979.58 | 0.389350 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00794440 | 44.5450 | 6196.89 | 0.00 | 8020.47 | 8020.47 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 503486.668 | -999.000 | 23.171755 | 0.01798338 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 503486.67 | 503486.66 | 23.171755 | 31.09 | 17.09 | 0.00829523 | 10.70 | 9.77 | 0.00829523 | 38.10 | 0.00687148 | 18.17 | 50.3262 | 23.99 | 0.00973372 | 45.3766 | 276385.72 | 0.00 | 555614.42 | 515540.51 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 159759.879 | 159759.879 | 6.951527 | 0.00139765 | 2712.089 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 159759.88 | 159759.88 | 6.951527 | -5.20 | -5.20 | 0.00280840 | 16.70 | 11.86 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 167.7539 | 21.23 | 0.00698408 | 38.6642 | 57180.22 | 0.00 | 145490.93 | 145490.93 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 57348.723 | -999.000 | 2.051317 | 0.00204836 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 57348.72 | 57348.72 | 2.051317 | 38.10 | 18.17 | 0.00687148 | 11.79 | 8.78 | 0.00687148 | 38.10 | 0.00687148 | 18.17 | 99.9965 | 21.11 | 0.00862172 | 47.9635 | 159019.79 | 0.00 | 51614.51 | 51614.51 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 14143.003 | 14143.003 | 0.615395 | 0.00012373 | 240.092 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 14143.00 | 14143.00 | 0.615395 | -5.20 | -5.20 | 0.00280840 | 16.70 | 11.86 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 333.3216 | 21.11 | 0.00789113 | 43.9495 | 94355.22 | 0.00 | 12879.82 | 12879.82 |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 54914.715 | 40417.230 | 4.903586 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 75921.46 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 43396.857 | 31940.086 | 3.872570 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 54370.95 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 5305.348 | 5305.348 | 1.158590 | 0.00004641 | 110.634 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 1.3714 | 1.399036 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5305.35 | 5305.35 | 1.0000 | 1.20995185 | 1.158590 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.04640877 | 60.00 | 32.22 | 27.78 | 0.000 | 5305.35 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 0.00 | 0.00 | 5335.17 | 5335.17 | 1.20995185 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3239.164 | 3239.164 | 0.171174 | 0.00002834 | 80.951 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 0.8373 | 0.854177 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3239.16 | 3239.16 | 1.0000 | 0.17876260 | 0.171174 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.02833473 | 60.00 | 32.22 | 27.78 | 0.000 | 3239.16 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00788828 | 21.00 | 0.00788828 | 44.2347 | 2455.53 | 0.00 | 3255.86 | 3255.86 | 0.17876260 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.46 | 19.49 | 0.00800000 | 55148.1 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1388.819 | 1388.819 | 0.125595 | 0.00001215 | 31.271 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 0.3590 | 0.366236 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1388.82 | 1388.82 | 1.0000 | 0.13116328 | 0.125595 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01214875 | 60.00 | 32.22 | 27.78 | 0.000 | 1388.82 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00787032 | 21.00 | 0.00787032 | 44.1349 | 813.85 | 0.00 | 1396.32 | 1396.32 | 0.13116328 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.04 | 17.03 | 0.00800000 | 47580.4 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2021.652 | 2021.652 | 0.112355 | 0.00001769 | 49.867 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 0.5226 | 0.533115 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2021.65 | 2021.65 | 1.0000 | 0.11733575 | 0.112355 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01768449 | 60.00 | 32.22 | 27.78 | 0.000 | 2021.65 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00783564 | 21.00 | 0.00783564 | 43.9429 | 1507.33 | 0.00 | 2032.12 | 2032.12 | 0.11733575 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 33.58 | 19.21 | 0.00800000 | 54253.6 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1227.070 | 1227.070 | 0.061070 | 0.00001073 | 31.184 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 0.3172 | 0.323582 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1227.07 | 1227.07 | 1.0000 | 0.06377783 | 0.061070 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01073385 | 60.00 | 32.22 | 27.78 | 0.000 | 1227.07 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00784876 | 21.00 | 0.00784876 | 44.0155 | 947.50 | 0.00 | 1233.37 | 1233.37 | 0.06377783 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.56 | 19.83 | 0.00800000 | 56273.2 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10596.531 | 10596.531 | 1.885645 | 0.00009270 | 223.608 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 2.7392 | 2.794336 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10596.53 | 10596.53 | 1.0000 | 1.96923843 | 1.885645 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.09269362 | 60.00 | 32.22 | 27.78 | 0.000 | 10596.53 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00782815 | 21.00 | 0.00782815 | 43.9017 | 1965.05 | 0.00 | 10655.84 | 10655.84 | 1.96923843 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.91 | 15.19 | 0.00800000 | 42345.9 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9703.640 | 9703.640 | 0.766646 | 0.00008489 | 222.940 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 2.5084 | 2.558878 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 9703.64 | 9703.64 | 1.0000 | 0.80063289 | 0.766646 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.08488301 | 60.00 | 32.22 | 27.78 | 0.000 | 9703.64 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00790183 | 21.00 | 0.00790183 | 44.3096 | 6193.82 | 0.00 | 9755.70 | 9755.70 | 0.80063289 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.55 | 17.55 | 0.00800000 | 49119.7 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26288.665 | 26288.665 | 2.560826 | 0.00022998 | 586.162 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 6.7956 | 6.932397 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 26288.67 | 26288.67 | 1.0000 | 2.67435162 | 2.560826 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.22996125 | 60.00 | 32.22 | 27.78 | 0.000 | 26288.67 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00788118 | 21.00 | 0.00788118 | 44.1950 | 14565.03 | 0.00 | 26431.27 | 26431.27 | 2.67435162 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.29 | 16.77 | 0.00800000 | 46818.0 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10600.958 | -999.000 | 1.087500 | 0.00037863 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7715 | 1004.8586 | 1.0443 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.087500 | 1.13571122 | 4197.9300 | 999.8980 | 26.53889648 | 13.37 | 6.70 | 6.67 | 743094.23 | 1.4266 | 1.426570 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | Sensible | 10600.96 | 10452.55 | 1.0000 | 1.13571122 | 1.087500 | 21.77 | 14.22 | 0.00857017 | 43656.4 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.37859595 | 6.70 | 13.37 | 6.67 | 0.000 | 10600.96 | 36.63 | 0.00686912 | 17.72 | 0.00000000 | 0.0000 | 21.11 | 0.00857017 | 21.11 | 0.00857017 | 47.6807 | 9633.30 | 0.00 | 12259.43 | 11647.52 | 1.13571122 | 21.77 | 15.65 | 0.00857017 | 43656.4 | 11.72 | 11.51 | 0.00835660 | 32861.9 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5313.338 | 5313.338 | 0.264142 | 0.00004648 | 151.807 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.087500 | 1.13571122 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 1.3735 | 1.401143 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5313.34 | 5313.34 | 1.0000 | 0.27585159 | 0.264142 | 21.11 | 13.39 | 0.00788100 | 41232.1 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.04647865 | 60.00 | 32.22 | 27.78 | 0.000 | 5313.34 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00788100 | 21.11 | 0.00788100 | 43.8941 | 5313.35 | 0.00 | 5727.95 | 5727.95 | 0.27585159 | 16.60 | 13.03 | 0.00788100 | 36633.4 | 36.97 | 20.18 | 0.00788100 | 57398.0 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10516.853 | -999.000 | 1.078726 | 0.00037563 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7725 | 1004.8586 | 1.0443 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.078726 | 1.12654746 | 4197.9300 | 999.8980 | 26.53889648 | 13.37 | 6.70 | 6.67 | 743094.23 | 1.4153 | 1.415252 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | Sensible | 10516.85 | 10368.59 | 1.0000 | 1.12654746 | 1.078726 | 21.77 | 14.22 | 0.00857067 | 43657.7 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.37559229 | 6.70 | 13.37 | 6.67 | 0.000 | 10516.85 | 36.63 | 0.00686912 | 17.72 | 0.00000000 | 0.0000 | 21.11 | 0.00857067 | 21.11 | 0.00857067 | 47.6835 | 9555.57 | 0.00 | 12162.05 | 11553.62 | 1.12654746 | 21.77 | 15.65 | 0.00857067 | 43657.7 | 11.72 | 11.51 | 0.00835659 | 32861.8 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5307.673 | 5307.673 | 0.263860 | 0.00004643 | 151.645 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.078726 | 1.12654746 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 1.3720 | 1.399649 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5307.67 | 5307.67 | 1.0000 | 0.27555751 | 0.263860 | 21.11 | 13.39 | 0.00788088 | 41231.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.04642910 | 60.00 | 32.22 | 27.78 | 0.000 | 5307.67 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00788088 | 21.11 | 0.00788088 | 43.8935 | 5307.69 | 0.00 | 5721.84 | 5721.84 | 0.27555751 | 16.60 | 13.03 | 0.00788088 | 36633.1 | 36.97 | 20.18 | 0.00788088 | 57397.7 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 57212.482 | -999.000 | 5.983237 | 0.00204346 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6269 | 1004.8586 | 1.0443 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.983237 | 6.24848438 | 4197.9300 | 999.8980 | 26.53889648 | 13.37 | 6.70 | 6.67 | 743094.23 | 7.6992 | 7.699079 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | unknown | unknown | 7/21 14:10:00 | Sensible | 57212.48 | 57212.48 | 1.0000 | 6.24848438 | 5.983237 | 21.77 | 14.16 | 0.00849238 | 43459.2 | 12.80 | 10.81 | 0.00849238 | 34303.0 | 2.04325066 | 6.70 | 13.37 | 6.67 | 0.000 | 57212.48 | 38.10 | 0.00687148 | 18.17 | 0.00000000 | 0.0000 | 21.11 | 0.00849238 | 21.11 | 0.00849238 | 47.2526 | 53003.19 | 0.00 | 66264.20 | 64092.65 | 6.24848438 | 21.77 | 15.58 | 0.00849238 | 43459.2 | 11.72 | 11.50 | 0.00835462 | 32854.3 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30868.436 | 30868.436 | 1.534572 | 0.00027005 | 881.935 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.983237 | 6.24848438 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 7.9795 | 8.140096 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 30868.44 | 30868.44 | 1.0000 | 1.60260200 | 1.534572 | 21.11 | 13.40 | 0.00789119 | 41258.1 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.27002300 | 60.00 | 32.22 | 27.78 | 0.000 | 30868.44 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00789119 | 21.11 | 0.00789119 | 43.9498 | 30868.48 | 0.00 | 33277.23 | 33277.23 | 1.60260200 | 16.60 | 13.04 | 0.00789119 | 36659.2 | 36.97 | 20.19 | 0.00789119 | 57423.7 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 67064.169 | -999.000 | 6.578132 | 0.00239533 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0850 | 1004.8586 | 1.0443 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.578132 | 6.86975156 | 4197.9300 | 999.8980 | 26.53889648 | 13.37 | 6.70 | 6.67 | 743094.23 | 9.0250 | 9.024820 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | unknown | unknown | unknown | 7/21 15:30:00 | Sensible | 67064.17 | 63973.01 | 1.0000 | 6.86975156 | 6.578132 | 21.77 | 14.36 | 0.00873881 | 44084.4 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 2.39508765 | 6.70 | 13.37 | 6.67 | 0.000 | 67064.17 | 37.71 | 0.00687086 | 18.05 | 0.00000000 | 0.0000 | 21.11 | 0.00873881 | 21.11 | 0.00873881 | 48.6069 | 58268.24 | 0.00 | 77321.26 | 70631.68 | 6.86975156 | 21.77 | 15.80 | 0.00873881 | 44084.4 | 11.70 | 11.49 | 0.00835280 | 32829.1 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30776.993 | 30776.993 | 1.530026 | 0.00026925 | 879.322 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.578132 | 6.86975156 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 7.9559 | 8.115982 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 30776.99 | 30776.99 | 1.0000 | 1.59785452 | 1.530026 | 21.11 | 13.40 | 0.00789084 | 41257.3 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.26922309 | 60.00 | 32.22 | 27.78 | 0.000 | 30776.99 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00789084 | 21.11 | 0.00789084 | 43.9479 | 30777.03 | 0.00 | 33178.65 | 33178.65 | 1.59785452 | 16.60 | 13.04 | 0.00789084 | 36658.4 | 36.97 | 20.19 | 0.00789084 | 57422.9 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9316.144 | -999.000 | 0.953191 | 0.00033274 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7895 | 1004.8586 | 1.0443 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.953191 | 0.99544727 | 4197.9300 | 999.8980 | 26.53889648 | 13.37 | 6.70 | 6.67 | 743094.23 | 1.2537 | 1.253673 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | unknown | unknown | unknown | 7/21 10:10:00 | Sensible | 9316.14 | 9168.04 | 1.0000 | 0.99544727 | 0.953191 | 21.77 | 14.23 | 0.00857984 | 43680.9 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.33271093 | 6.70 | 13.37 | 6.67 | 0.000 | 9316.14 | 33.48 | 0.00686412 | 16.74 | 0.00000000 | 0.0000 | 21.11 | 0.00857984 | 21.11 | 0.00857984 | 47.7338 | 8443.55 | 0.00 | 10771.55 | 10210.38 | 0.99544727 | 21.77 | 15.66 | 0.00857984 | 43680.9 | 11.72 | 11.51 | 0.00835638 | 32860.1 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5302.652 | 5302.652 | 0.263611 | 0.00004639 | 151.502 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.953191 | 0.99544727 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 1.3707 | 1.398325 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5302.65 | 5302.65 | 1.0000 | 0.27529683 | 0.263611 | 21.11 | 13.39 | 0.00788076 | 41231.5 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.04638518 | 60.00 | 32.22 | 27.78 | 0.000 | 5302.65 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00788076 | 21.11 | 0.00788076 | 43.8928 | 5302.67 | 0.00 | 5716.43 | 5716.43 | 0.27529683 | 16.60 | 13.03 | 0.00788076 | 36632.8 | 36.97 | 20.18 | 0.00788076 | 57397.4 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9247.609 | -999.000 | 0.946030 | 0.00033030 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7906 | 1004.8586 | 1.0443 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.946030 | 0.98796903 | 4197.9300 | 999.8980 | 26.53889648 | 13.37 | 6.70 | 6.67 | 743094.23 | 1.2445 | 1.244450 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | unknown | unknown | 7/21 10:00:00 | Sensible | 9247.61 | 9099.55 | 1.0000 | 0.98796903 | 0.946030 | 21.77 | 14.23 | 0.00858042 | 43682.4 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.33026329 | 6.70 | 13.37 | 6.67 | 0.000 | 9247.61 | 33.16 | 0.00686360 | 16.64 | 0.00000000 | 0.0000 | 21.11 | 0.00858042 | 21.11 | 0.00858042 | 47.7370 | 8380.12 | 0.00 | 10692.19 | 10133.76 | 0.98796903 | 21.77 | 15.66 | 0.00858042 | 43682.4 | 11.72 | 11.51 | 0.00835636 | 32860.0 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5296.986 | 5296.986 | 0.263329 | 0.00004634 | 151.340 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.946030 | 0.98796903 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 1.3693 | 1.396831 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5296.99 | 5296.99 | 1.0000 | 0.27500268 | 0.263329 | 21.11 | 13.39 | 0.00788065 | 41231.2 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.04633562 | 60.00 | 32.22 | 27.78 | 0.000 | 5296.99 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00788065 | 21.11 | 0.00788065 | 43.8922 | 5297.00 | 0.00 | 5710.32 | 5710.32 | 0.27500268 | 16.60 | 13.03 | 0.00788065 | 36632.6 | 36.97 | 20.18 | 0.00788065 | 57397.2 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11780.354 | 11780.354 | 0.661672 | 0.00010306 | 289.817 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 3.0452 | 3.106514 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 11780.35 | 11780.35 | 1.0000 | 0.69100557 | 0.661672 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.10304917 | 60.00 | 32.22 | 27.78 | 0.000 | 11780.35 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00791155 | 21.00 | 0.00791155 | 44.3631 | 8750.97 | 0.00 | 11841.39 | 11841.39 | 0.69100557 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 33.41 | 19.15 | 0.00800000 | 54071.2 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2835.638 | -999.000 | 0.291266 | 0.00010128 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7628 | 1004.8586 | 1.0443 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.291266 | 0.30417800 | 4197.9300 | 999.8980 | 26.53889648 | 13.37 | 6.70 | 6.67 | 743094.23 | 0.3816 | 0.381592 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | unknown | unknown | 7/21 16:30:00 | Sensible | 2835.64 | 2798.56 | 1.0000 | 0.30417800 | 0.291266 | 21.77 | 14.22 | 0.00856549 | 43644.5 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.10127019 | 6.70 | 13.37 | 6.67 | 0.000 | 2835.64 | 36.80 | 0.00686940 | 17.78 | 0.00000000 | 0.0000 | 21.11 | 0.00856549 | 21.11 | 0.00856549 | 47.6550 | 2580.09 | 0.00 | 3279.57 | 3119.36 | 0.30417800 | 21.77 | 15.64 | 0.00856549 | 43644.5 | 11.72 | 11.51 | 0.00835671 | 32862.8 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1680.924 | 1680.924 | 0.083564 | 0.00001471 | 48.025 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.291266 | 0.30417800 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 0.4345 | 0.443265 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1680.92 | 1680.92 | 1.0000 | 0.08726826 | 0.083564 | 21.11 | 13.41 | 0.00790548 | 41294.3 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01470396 | 60.00 | 32.22 | 27.78 | 0.000 | 1680.92 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00790548 | 21.11 | 0.00790548 | 44.0287 | 1680.93 | 0.00 | 1812.09 | 1812.09 | 0.08726826 | 16.60 | 13.06 | 0.00790548 | 36695.4 | 36.97 | 20.20 | 0.00790548 | 57460.0 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2810.473 | -999.000 | 0.288632 | 0.00010038 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7640 | 1004.8586 | 1.0443 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.288632 | 0.30142720 | 4197.9300 | 999.8980 | 26.53889648 | 13.37 | 6.70 | 6.67 | 743094.23 | 0.3782 | 0.378205 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | Sensible | 2810.47 | 2773.38 | 1.0000 | 0.30142720 | 0.288632 | 21.77 | 14.22 | 0.00856611 | 43646.1 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.10037148 | 6.70 | 13.37 | 6.67 | 0.000 | 2810.47 | 36.63 | 0.00686912 | 17.72 | 0.00000000 | 0.0000 | 21.11 | 0.00856611 | 21.11 | 0.00856611 | 47.6584 | 2556.76 | 0.00 | 3250.42 | 3091.17 | 0.30142720 | 21.77 | 15.64 | 0.00856611 | 43646.1 | 11.72 | 11.51 | 0.00835669 | 32862.6 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1680.214 | 1680.214 | 0.083528 | 0.00001470 | 48.005 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.288632 | 0.30142720 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 0.4343 | 0.443077 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1680.21 | 1680.21 | 1.0000 | 0.08723141 | 0.083528 | 21.11 | 13.41 | 0.00790545 | 41294.2 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01469775 | 60.00 | 32.22 | 27.78 | 0.000 | 1680.21 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00790545 | 21.11 | 0.00790545 | 44.0286 | 1680.22 | 0.00 | 1811.32 | 1811.32 | 0.08723141 | 16.60 | 13.06 | 0.00790545 | 36695.4 | 36.97 | 20.20 | 0.00790545 | 57459.9 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12657.914 | -999.000 | 1.273518 | 0.00045210 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9058 | 1004.8586 | 1.0443 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.273518 | 1.32997554 | 4197.9300 | 999.8980 | 26.53889648 | 13.37 | 6.70 | 6.67 | 743094.23 | 1.7034 | 1.703375 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | unknown | unknown | 7/21 14:10:00 | Sensible | 12657.91 | 12303.44 | 1.0000 | 1.32997554 | 1.273518 | 21.77 | 14.28 | 0.00864239 | 43839.6 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.45205680 | 6.70 | 13.37 | 6.67 | 0.000 | 12657.91 | 38.10 | 0.00687148 | 18.17 | 0.00000000 | 0.0000 | 21.11 | 0.00864239 | 21.11 | 0.00864239 | 48.0777 | 11280.75 | 0.00 | 14620.92 | 13655.74 | 1.32997554 | 21.77 | 15.71 | 0.00864239 | 43839.6 | 11.71 | 11.50 | 0.00835472 | 32846.2 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8127.838 | 8127.838 | 0.404060 | 0.00007111 | 232.216 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.273518 | 1.32997554 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 2.1010 | 2.143334 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 8127.84 | 8127.84 | 1.0000 | 0.42197264 | 0.404060 | 21.11 | 13.42 | 0.00790991 | 41305.6 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.07109862 | 60.00 | 32.22 | 27.78 | 0.000 | 8127.84 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00790991 | 21.11 | 0.00790991 | 44.0530 | 8127.85 | 0.00 | 8762.08 | 8762.08 | 0.42197264 | 16.60 | 13.06 | 0.00790991 | 36706.7 | 36.97 | 20.20 | 0.00790991 | 57471.2 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11477.662 | 11477.662 | 1.238347 | 0.00010041 | 252.826 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 2.9670 | 3.026693 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 11477.66 | 11477.66 | 1.0000 | 1.29324496 | 1.238347 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.10040135 | 60.00 | 32.22 | 27.78 | 0.000 | 11477.66 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00793246 | 21.00 | 0.00793246 | 44.4790 | 5807.90 | 0.00 | 11540.23 | 11540.23 | 1.29324496 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.35 | 16.44 | 0.00800000 | 45858.2 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11891.802 | 11891.802 | 1.299491 | 0.00010403 | 261.577 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 3.0740 | 3.135903 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 11891.80 | 11891.80 | 1.0000 | 1.35710003 | 1.299491 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.10402406 | 60.00 | 32.22 | 27.78 | 0.000 | 11891.80 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00793396 | 21.00 | 0.00793396 | 44.4873 | 5942.07 | 0.00 | 11956.67 | 11956.67 | 1.35710003 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.24 | 16.40 | 0.00800000 | 45745.2 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8056.428 | 8056.428 | 1.239397 | 0.00007048 | 171.746 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 2.0826 | 2.124503 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 8056.43 | 8056.43 | 1.0000 | 1.29434128 | 1.239397 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.07047395 | 60.00 | 32.22 | 27.78 | 0.000 | 8056.43 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.58 | 0.00737699 | 21.00 | 0.00737699 | 41.4048 | 2389.64 | 0.00 | 8101.36 | 8101.36 | 1.29434128 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.74 | 15.50 | 0.00800000 | 43193.8 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7979.580 | 7979.580 | 0.389350 | 0.00006981 | 203.978 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 2.0627 | 2.104238 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 7979.58 | 7979.58 | 1.0000 | 0.40661051 | 0.389350 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.06980173 | 60.00 | 32.22 | 27.78 | 0.000 | 7979.58 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00794440 | 21.00 | 0.00794440 | 44.5450 | 6196.89 | 0.00 | 8020.47 | 8020.47 | 0.40661051 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.94 | 19.95 | 0.00800000 | 56659.9 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 503486.668 | -999.000 | 23.171755 | 0.01798338 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2604 | 1004.8586 | 1.0443 | VAV WITH REHEAT FAN | Fan:VariableVolume | 23.171755 | 24.19899915 | 4197.9300 | 999.8980 | 26.53889648 | 13.37 | 6.70 | 6.67 | 743094.23 | 67.7554 | 67.755427 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | Sensible | 503486.67 | 503486.66 | 1.0000 | 24.19899915 | 23.171755 | 31.09 | 17.09 | 0.00829523 | 52465.8 | 10.70 | 9.77 | 0.00829523 | 31659.7 | 17.98154269 | 6.70 | 13.37 | 6.67 | 51919.529 | 451567.14 | 38.10 | 0.00687148 | 18.17 | 11.66146000 | 50.3262 | 23.99 | 0.00973768 | 23.99 | 0.00973372 | 45.3766 | 276385.72 | 0.00 | 555614.42 | 515540.51 | 24.19899915 | 31.09 | 18.63 | 0.00829523 | 52465.8 | 10.21 | 10.10 | 0.00763806 | 29505.6 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 159759.879 | 159759.879 | 6.951527 | 0.00139765 | 2712.089 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | VAV WITH REHEAT FAN | Fan:VariableVolume | 23.171755 | 24.19899915 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 41.2980 | 42.129142 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 159759.88 | 159759.88 | 1.0000 | 7.25969974 | 6.951527 | -5.20 | -5.20 | 0.00280840 | 1771.3 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 1.39750654 | 60.00 | 32.22 | 27.78 | 0.000 | 159759.88 | -5.20 | 0.00280840 | -5.20 | 11.66146000 | 167.7539 | 18.55 | 0.00729208 | 21.23 | 0.00698408 | 38.6642 | 57180.22 | 0.00 | 145490.93 | 145490.93 | 7.25969974 | 2.80 | 0.24 | 0.00280840 | 9851.8 | 22.64 | 10.36 | 0.00280840 | 29892.7 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 57348.723 | -999.000 | 2.051317 | 0.00204836 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.6137 | 1004.8586 | 1.0443 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.14218037 | 4197.9300 | 999.8980 | 26.53889648 | 13.37 | 6.70 | 6.67 | 743094.23 | 7.7176 | 7.717557 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 57348.72 | 57348.72 | 1.0000 | 2.14225568 | 2.051317 | 38.10 | 18.17 | 0.00687148 | 55956.2 | 11.79 | 8.78 | 0.00687148 | 29186.0 | 2.04815455 | 6.70 | 13.37 | 6.67 | 2195.006 | 55153.72 | 38.10 | 0.00687148 | 18.17 | 2.05124512 | 99.9965 | 21.11 | 0.00861412 | 21.11 | 0.00862172 | 47.9635 | 159019.79 | 0.00 | 51614.51 | 51614.51 | 2.14225568 | 38.10 | 19.77 | 0.00687148 | 55956.2 | 14.42 | 11.12 | 0.00687148 | 31862.7 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 14143.003 | 14143.003 | 0.615395 | 0.00012373 | 240.092 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.14218037 | 4197.9300 | 999.8980 | 3.31719678 | 54.44 | 82.22 | 27.78 | 386846.50 | 3.6560 | 3.729551 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 14143.00 | 14143.00 | 1.0000 | 0.64267671 | 0.615395 | -5.20 | -5.20 | 0.00280840 | 1771.3 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 0.12371654 | 60.00 | 32.22 | 27.78 | 0.000 | 14143.00 | -5.20 | 0.00280840 | -5.20 | 2.05124512 | 333.3216 | 21.11 | 0.00789087 | 21.11 | 0.00789113 | 43.9495 | 94355.22 | 0.00 | 12879.82 | 12879.82 | 0.64267671 | 2.80 | 0.24 | 0.00280840 | 9851.8 | 22.64 | 10.36 | 0.00280840 | 29892.7 | |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 54914.715 | 40417.230 | 4.903586 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 1.0443 | SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 4.903586 | 5.12097098 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 75921.46 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 75921.46 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 43396.857 | 31940.086 | 3.872570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 1.0443 | SWHSYS1 HPWH FAN | Fan:SystemModel | 3.872570 | 4.04424726 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 54370.95 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54370.95 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 23.17 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1814.50 | 6862.50 | 1051.50 |
RETAIL_1_FLR_1 | 3117.17 | 5440.17 | 951.50 |
RETAIL_2_FLR_1 | 2631.33 | 5897.33 | 1060.00 |
MECH_FLR_1 | 1852.00 | 6444.50 | 561.50 |
STORAGE_FLR_1 | 1707.17 | 6693.17 | 695.67 |
LAUNDRY_FLR_1 | 7672.67 | 3427.67 | 2991.33 |
CAFE_FLR_1 | 4347.33 | 4533.50 | 1784.50 |
LOBBY_FLR_1 | 3305.83 | 5318.50 | 1593.83 |
ROOM_1_FLR_3 | 332.17 | 8037.67 | 233.83 |
ROOM_2_FLR_3 | 1092.33 | 7915.83 | 923.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 384.17 | 8738.67 | 381.67 |
ROOM_5_FLR_3 | 273.33 | 7858.67 | 245.00 |
ROOM_6_FLR_3 | 1197.33 | 7721.67 | 970.83 |
CORRIDOR_FLR_3 | 2155.00 | 7343.50 | 1501.33 |
ROOM_1_FLR_6 | 1038.00 | 7910.17 | 767.67 |
ROOM_2_FLR_6 | 2047.50 | 7827.17 | 1763.83 |
ROOM_3_MULT9_FLR_6 | 171.33 | 7887.83 | 74.83 |
BANQUET_FLR_6 | 4296.33 | 3779.83 | 1712.17 |
DINING_FLR_6 | 4714.83 | 2494.50 | 1601.83 |
KITCHEN_FLR_6 | 8304.33 | 6705.17 | 6651.67 |
CORRIDOR_FLR_6 | 2486.50 | 6369.67 | 910.00 |
Facility | 8700.00 | 8760.00 | 7592.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 15.33 | 0.00 | 15.33 |
ROOM_2_FLR_3 | 0.00 | 16.33 | 0.00 | 16.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 8.83 | 0.00 | 8.83 |
ROOM_5_FLR_3 | 0.00 | 4.50 | 0.00 | 4.50 |
ROOM_6_FLR_3 | 0.00 | 40.17 | 0.00 | 40.17 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 19.17 | 0.00 | 19.17 |
ROOM_2_FLR_6 | 0.00 | 22.50 | 0.00 | 22.50 |
ROOM_3_MULT9_FLR_6 | 0.00 | 17.33 | 0.00 | 17.33 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 81.00 | 0.00 | 81.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.886 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.353 | 0.034 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.499 | 0.011 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.606 | 0.013 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.563 | 0.013 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 24.717 | 0.036 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 3.917 | 0.027 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.888 | 0.011 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.044 | 0.000 | 0.055 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.044 | 0.000 | 0.059 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.403 | 0.019 | 0.000 | 0.090 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.044 | 0.000 | 0.056 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.044 | 0.000 | 0.056 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.484 | 0.005 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.355 | 0.044 | 0.000 | 0.066 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.044 | 0.000 | 0.068 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.403 | 0.036 | 0.000 | 0.105 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 5.272 | 0.013 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 5.672 | 0.013 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 22.832 | 0.036 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.098 | 0.009 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.505 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.541 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.082 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.465 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.432 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 13.856 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 2.757 | 0.000 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.310 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.000 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.329 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 3.898 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.121 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 10.007 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.746 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.80 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.58 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.14 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.39 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 36823538.96 | 0.00 | 36823538.96 | 0.00 | 36823538.96 | 26946214.98 | 245.30 | 19.57 | 8495.13 | 0.00 |
RETAIL_1_FLR_1 | 5390531.11 | 0.00 | 5390531.11 | 77456.53 | 5467987.64 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3965469.64 | 0.00 | 3965469.64 | 29898.32 | 3995367.96 | 2892943.94 | 0.17 | 1.00 | 8758.83 | 0.00 |
MECH_FLR_1 | 3403842.08 | 0.00 | 3403842.08 | 70661.86 | 3474503.94 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1823812.95 | 0.00 | 1823812.95 | 40768.00 | 1864580.95 | 1821682.01 | 4142.57 | 1088.58 | 3528.84 | 0.00 |
LAUNDRY_FLR_1 | 65850435.74 | 0.00 | 65850435.74 | 96485.16 | 65946920.90 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 25158074.97 | 0.00 | 25158074.97 | 171222.03 | 25329297.00 | 21330615.53 | 177.76 | 23.26 | 8558.98 | 0.00 |
LOBBY_FLR_1 | 83980498.91 | 0.00 | 83980498.91 | 489220.46 | 84469719.37 | 59728886.00 | 1.00 | 0.76 | 8758.24 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 57056.74 | 1517213.45 | 44957.98 | 1562171.43 | 1946875.62 | 2190.00 | 5876.83 | 693.17 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 60080.30 | 1520065.93 | 44954.55 | 1565020.48 | 1946647.51 | 2190.00 | 5879.34 | 690.66 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 0.00 | 1099911.97 | 12543.78 | 1112455.75 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.00 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 57965.75 | 19861795.04 | 12547.21 | 19874342.25 | 26405105.73 | 2190.00 | 5929.36 | 640.64 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 57189.87 | 1517346.59 | 44957.98 | 1562304.57 | 1946875.62 | 2190.00 | 5876.83 | 693.17 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 57525.83 | 1517511.46 | 44954.55 | 1562466.01 | 1946647.51 | 2190.00 | 5880.25 | 689.75 | 0.00 |
CORRIDOR_FLR_3 | 19782564.89 | 0.00 | 19782564.89 | 54363.24 | 19836928.13 | 14972100.18 | 21.50 | 19.50 | 8719.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 67696.83 | 432736.01 | 44967.18 | 477703.19 | 486718.90 | 2055.03 | 5876.55 | 828.42 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 69527.09 | 434523.50 | 44963.75 | 479487.25 | 486661.88 | 2053.44 | 5881.06 | 825.50 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 67740.14 | 2412930.45 | 23006.78 | 2435937.23 | 3126920.42 | 2190.00 | 5874.00 | 696.00 | 0.00 |
BANQUET_FLR_6 | 45686452.42 | 0.00 | 45686452.42 | 109798.56 | 45796250.98 | 37458366.31 | 814.58 | 996.62 | 6948.80 | 0.00 |
DINING_FLR_6 | 49157278.01 | 0.00 | 49157278.01 | 109798.56 | 49267076.56 | 37458366.31 | 2.83 | 2.50 | 8754.67 | 0.00 |
KITCHEN_FLR_6 | 61690385.62 | 0.00 | 61690385.62 | 98295.17 | 61788680.79 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 11899927.78 | 0.00 | 11899927.78 | 96205.82 | 11996133.60 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 6079692.96 | 0.21E+10 | 4530471.06 | 0.21E+10 | 0.43E+10 | 8760.00 | 6933.87 | 8760.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.1677 | 0.0000 | 1.1677 | 0.0000 | 1.1677 | 0.8545 | 245.30 | 19.57 | 8495.13 |
RETAIL_1_FLR_1 | 0.1709 | 0.0000 | 0.1709 | 0.0025 | 0.1734 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1257 | 0.0000 | 0.1257 | 0.0009 | 0.1267 | 0.0917 | 0.17 | 1.00 | 8758.83 |
MECH_FLR_1 | 0.1079 | 0.0000 | 0.1079 | 0.0022 | 0.1102 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0578 | 0.0000 | 0.0578 | 0.0013 | 0.0591 | 0.0578 | 4142.57 | 1088.58 | 3528.84 |
LAUNDRY_FLR_1 | 2.0881 | 0.0000 | 2.0881 | 0.0031 | 2.0912 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7978 | 0.0000 | 0.7978 | 0.0054 | 0.8032 | 0.6764 | 177.76 | 23.26 | 8558.98 |
LOBBY_FLR_1 | 2.6630 | 0.0000 | 2.6630 | 0.0155 | 2.6785 | 1.8940 | 1.00 | 0.76 | 8758.24 |
ROOM_1_FLR_3 | 0.0463 | 0.0018 | 0.0481 | 0.0014 | 0.0495 | 0.0617 | 2190.00 | 5876.83 | 693.17 |
ROOM_2_FLR_3 | 0.0463 | 0.0019 | 0.0482 | 0.0014 | 0.0496 | 0.0617 | 2190.00 | 5879.34 | 690.66 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0018 | 0.6298 | 0.0004 | 0.6302 | 0.8373 | 2190.00 | 5929.36 | 640.64 |
ROOM_5_FLR_3 | 0.0463 | 0.0018 | 0.0481 | 0.0014 | 0.0495 | 0.0617 | 2190.00 | 5876.83 | 693.17 |
ROOM_6_FLR_3 | 0.0463 | 0.0018 | 0.0481 | 0.0014 | 0.0495 | 0.0617 | 2190.00 | 5880.25 | 689.75 |
CORRIDOR_FLR_3 | 0.6273 | 0.0000 | 0.6273 | 0.0017 | 0.6290 | 0.4748 | 21.50 | 19.50 | 8719.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0021 | 0.0137 | 0.0014 | 0.0151 | 0.0154 | 2055.03 | 5876.55 | 828.42 |
ROOM_2_FLR_6 | 0.0116 | 0.0022 | 0.0138 | 0.0014 | 0.0152 | 0.0154 | 2053.44 | 5881.06 | 825.50 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0021 | 0.0765 | 0.0007 | 0.0772 | 0.0992 | 2190.00 | 5874.00 | 696.00 |
BANQUET_FLR_6 | 1.4487 | 0.0000 | 1.4487 | 0.0035 | 1.4522 | 1.1878 | 814.58 | 996.62 | 6948.80 |
DINING_FLR_6 | 1.5588 | 0.0000 | 1.5588 | 0.0035 | 1.5622 | 1.1878 | 2.83 | 2.50 | 8754.67 |
KITCHEN_FLR_6 | 1.9562 | 0.0000 | 1.9562 | 0.0031 | 1.9593 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3773 | 0.0000 | 0.3773 | 0.0031 | 0.3804 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 64.1885 | 0.1928 | 64.3813 | 0.1134 | 64.4947 | 73.9670 | 8760.00 | 6933.87 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.45E+09 | 0.00 | 0.45E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 32521733.86 | 494782.55 | 33016516.41 | 64690340.46 | 8759.83 | 0.17 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 14.3388 | 0.0000 | 14.3388 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.0313 | 0.0157 | 1.0469 | 2.0513 | 8759.83 | 0.17 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 4812.78 | 0.00 | 0.00 | 0.00 | 3947.22 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 14.8325 | 0.0000 | 0.0000 | 0.0000 | 13.7405 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.3026 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1363 |
Defaulted Fields | 1208 |
Fields with Defaults | 4115 |
Autosized Fields | 353 |
Autosizable Fields | 407 |
Autocalculated Fields | 289 |
Autocalculatable Fields | 549 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5838.11 | 67567.23 | 31-MAR-02:30 | 412066.93 | 05-JUN-19:10 |
Electricity:Building | 2279.02 | 30456.19 | 02-JAN-02:10 | 133648.28 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 245.14 | 2955.01 | 02-JAN-02:10 | 17976.64 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2271.92 | 30315.04 | 02-JAN-02:10 | 133406.95 | 02-JAN-20:10 |
InteriorLights:Electricity | 543.78 | 5032.86 | 02-JAN-02:10 | 45424.10 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 102.03 | 927.11 | 02-JAN-02:10 | 8344.11 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 543.78 | 5032.86 | 02-JAN-02:10 | 45424.10 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 543.78 | 5032.86 | 02-JAN-02:10 | 45424.10 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 102.03 | 927.11 | 02-JAN-02:10 | 8344.11 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 543.78 | 5032.86 | 02-JAN-02:10 | 45424.10 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 15.82 | 195.57 | 02-JAN-02:10 | 1146.69 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 5.64 | 51.23 | 02-JAN-02:10 | 461.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 5.64 | 51.23 | 02-JAN-02:10 | 461.08 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 18.32 | 226.47 | 02-JAN-02:10 | 1327.87 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 6.53 | 59.33 | 02-JAN-02:10 | 533.93 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 6.53 | 59.33 | 02-JAN-02:10 | 533.93 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.00 | 245.14 | 02-JAN-02:10 | 1455.21 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 7.53 | 68.42 | 02-JAN-02:10 | 615.76 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 7.53 | 68.42 | 02-JAN-02:10 | 615.76 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.28 | 66.24 | 02-JAN-02:10 | 379.51 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.68 | 15.26 | 02-JAN-02:10 | 137.35 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.68 | 15.26 | 02-JAN-02:10 | 137.35 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.35 | 1002.76 | 02-JAN-02:10 | 4933.42 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.41 | 40.07 | 02-JAN-02:10 | 360.62 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.41 | 40.07 | 02-JAN-02:10 | 360.62 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 26.08 | 360.56 | 02-JAN-02:10 | 2381.38 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 11.73 | 69.23 | 01-JAN-13:10 | 1416.11 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 11.73 | 69.23 | 01-JAN-13:10 | 1416.11 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 259.78 | 3175.95 | 02-JAN-02:10 | 19610.05 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.78 | 1064.54 | 02-JAN-02:10 | 9580.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.78 | 1064.54 | 02-JAN-02:10 | 9580.84 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 17.85 | 257.74 | 01-JAN-02:10 | 1187.62 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 5.55 | 47.02 | 01-JAN-02:10 | 427.46 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 5.55 | 47.02 | 01-JAN-02:10 | 427.46 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 17.84 | 257.71 | 01-JAN-02:10 | 1187.48 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 5.55 | 47.01 | 01-JAN-02:10 | 427.41 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 5.55 | 47.01 | 01-JAN-02:10 | 427.41 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 295.07 | 4482.89 | 01-JAN-02:10 | 20504.95 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 66.32 | 561.43 | 01-JAN-02:10 | 5104.26 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 66.32 | 561.43 | 01-JAN-02:10 | 5104.26 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 295.15 | 4484.12 | 01-JAN-02:10 | 20510.57 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 66.33 | 561.58 | 01-JAN-02:10 | 5105.65 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 66.33 | 561.58 | 01-JAN-02:10 | 5105.65 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 17.85 | 257.74 | 01-JAN-02:10 | 1187.62 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 5.55 | 47.02 | 01-JAN-02:10 | 427.46 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 5.55 | 47.02 | 01-JAN-02:10 | 427.46 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 17.84 | 257.71 | 01-JAN-02:10 | 1187.48 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 5.55 | 47.01 | 01-JAN-02:10 | 427.41 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 5.55 | 47.01 | 01-JAN-02:10 | 427.41 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 51.07 | 464.00 | 02-JAN-02:10 | 4176.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 51.07 | 464.00 | 02-JAN-02:10 | 4176.01 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 51.07 | 464.00 | 02-JAN-02:10 | 4176.01 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.46 | 64.43 | 01-JAN-02:10 | 296.90 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.39 | 11.75 | 01-JAN-02:10 | 106.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.39 | 11.75 | 01-JAN-02:10 | 106.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.46 | 64.43 | 01-JAN-02:10 | 296.87 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.39 | 11.75 | 01-JAN-02:10 | 106.85 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.39 | 11.75 | 01-JAN-02:10 | 106.85 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 34.95 | 531.01 | 01-JAN-02:10 | 2428.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 7.86 | 66.50 | 01-JAN-02:10 | 604.62 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 7.86 | 66.50 | 01-JAN-02:10 | 604.62 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 201.54 | 2525.61 | 02-JAN-02:10 | 9234.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 25.69 | 276.31 | 02-JAN-02:10 | 2486.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 25.69 | 276.31 | 02-JAN-02:10 | 2486.81 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 201.54 | 2525.61 | 02-JAN-02:10 | 9234.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 25.69 | 276.31 | 02-JAN-02:10 | 2486.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 25.69 | 276.31 | 02-JAN-02:10 | 2486.81 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 443.12 | 5932.71 | 02-JAN-02:10 | 18599.73 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.01 | 109.08 | 02-JAN-02:10 | 981.75 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.01 | 109.08 | 02-JAN-02:10 | 981.75 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 13.51 | 122.77 | 02-JAN-02:10 | 1104.91 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 13.51 | 122.77 | 02-JAN-02:10 | 1104.91 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 13.51 | 122.77 | 02-JAN-02:10 | 1104.91 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 43.83 | 732.82 | 03-APR-22:30 | 2788.79 | 24-SEP-10:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 2011.09 | 2177.77 | 29-MAR-00:30 | 204637.89 | 05-JUN-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 15.77 | 0.00 | 01-JAN-11:10 | 1307.41 | 02-JUL-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 20.97 | 613.62 | 20-DEC-04:00 | 715.89 | 16-OCT-13:10 |
WaterSystems:Electricity | 483.38 | 1086.56 | 22-JUN-00:20 | 44361.98 | 06-OCT-20:50 |
Electricity:HVAC | 754.49 | 12362.36 | 15-JAN-15:00 | 57846.48 | 07-AUG-21:10 |
Fans:Electricity | 590.50 | 11489.55 | 19-FEB-03:30 | 47073.09 | 07-AUG-21:10 |
General:Fans:Electricity | 590.50 | 11489.55 | 19-FEB-03:30 | 47073.09 | 07-AUG-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ExteriorEquipment:Electricity | 641.45 | 9451.13 | 02-JAN-02:20 | 39153.57 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 22.42 | 386.32 | 02-JAN-02:20 | 1279.09 | 24-MAY-20:10 |
ElectricityPurchased:Facility | 5838.11 | 67567.23 | 31-MAR-02:30 | 412066.93 | 05-JUN-19:10 |
ElectricityPurchased:Plant | 5838.11 | 67567.23 | 31-MAR-02:30 | 412066.93 | 05-JUN-19:10 |
Cogeneration:ElectricityPurchased | 5838.11 | 67567.23 | 31-MAR-02:30 | 412066.93 | 05-JUN-19:10 |
General:Cogeneration:ElectricityPurchased | 5838.11 | 67567.23 | 31-MAR-02:30 | 412066.93 | 05-JUN-19:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5838.11 | 67567.23 | 31-MAR-02:30 | 412066.93 | 05-JUN-19:10 |
ElectricityNet:Plant | 5838.11 | 67567.23 | 31-MAR-02:30 | 412066.93 | 05-JUN-19:10 |
Cogeneration:ElectricityNet | 5838.11 | 67567.23 | 31-MAR-02:30 | 412066.93 | 05-JUN-19:10 |
General:Cogeneration:ElectricityNet | 5838.11 | 67567.23 | 31-MAR-02:30 | 412066.93 | 05-JUN-19:10 |
ExteriorLights:Electricity | 174.48 | 0.00 | 01-JAN-07:20 | 11096.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 174.48 | 0.00 | 01-JAN-07:20 | 11096.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 141.57 | 0.00 | 01-JAN-08:10 | 9938.94 | 18-APR-16:20 |
General:HeatRecovery:Electricity | 141.57 | 0.00 | 01-JAN-08:10 | 9938.94 | 18-APR-16:20 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.56 | 22-JUN-00:20 | 4738.77 | 24-AUG-18:10 |
Water Heater Parasitic:WaterSystems:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1368.84 | 0.00 | 01-JAN-04:00 | 157879.72 | 14-JUN-18:10 |
General:Cooling:Electricity | 1368.84 | 0.00 | 01-JAN-04:00 | 157879.72 | 14-JUN-18:10 |
Pumps:Electricity | 122.13 | 47.91 | 27-FEB-12:00 | 5961.89 | 05-JUN-18:20 |
General:Pumps:Electricity | 122.13 | 47.91 | 27-FEB-12:00 | 5961.89 | 05-JUN-18:20 |
WIRED_LTG_ELECTRICITY | 19.14 | 0.00 | 01-JAN-00:10 | 1598.93 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 3323.21 | 29270.80 | 16-MAR-01:10 | 344259.27 | 27-JAN-19:10 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 1534.37 | 15908.90 | 17-APR-15:10 | 256639.50 | 27-JAN-19:10 |
WaterSystems:NaturalGas | 953.38 | 15908.90 | 01-JAN-16:10 | 100722.14 | 30-DEC-19:20 |
Water Heater:WaterSystems:NaturalGas | 953.38 | 15908.90 | 01-JAN-16:10 | 100722.14 | 30-DEC-19:20 |
Heating:NaturalGas | 580.99 | 0.00 | 01-JAN-11:40 | 174026.15 | 29-JAN-01:10 |
Boiler:Heating:NaturalGas | 580.99 | 0.00 | 01-JAN-11:40 | 174026.15 | 29-JAN-01:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 4180.29 | 0.00 | 01-JAN-04:00 | 618226.44 | 21-JUL-21:00 |
PlantLoopCoolingDemand:HVAC | 4180.29 | 0.00 | 01-JAN-04:00 | 618226.44 | 21-JUL-21:00 |
CoolingCoils:PlantLoopCoolingDemand | 4180.29 | 0.00 | 01-JAN-04:00 | 618226.44 | 21-JUL-21:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 07-FEB-21:50 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 07-FEB-21:50 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 07-FEB-21:50 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 07-FEB-21:50 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 07-FEB-21:50 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 07-FEB-21:50 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 21-APR-06:20 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 21-APR-06:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 23391.83 | 119144.69 | 29-NOV-14:10 | 2421220.07 | 21-JUL-21:00 |
EnergyTransfer:Building | 5331.87 | 83228.11 | 26-DEC-15:00 | 340209.52 | 15-JUN-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 709.40 | 10569.56 | 19-DEC-04:00 | 34864.37 | 02-JUL-10:40 |
Refrigeration:EnergyTransfer | 181.78 | 4016.67 | 08-MAR-23:10 | 10361.60 | 15-AUG-06:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.89 | 2008.33 | 08-MAR-23:10 | 5180.80 | 15-AUG-06:30 |
General:Refrigeration:EnergyTransfer | 90.89 | 2008.33 | 08-MAR-23:10 | 5180.80 | 15-AUG-06:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.89 | 2008.33 | 08-MAR-23:10 | 5180.80 | 15-AUG-06:30 |
EnergyTransfer:Plant | 11117.55 | 16869.61 | 29-MAR-00:20 | 1427902.62 | 21-JUL-21:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.56 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.32 | 1840.07 | 20-DEC-04:00 | 2553.93 | 16-OCT-13:10 |
EnergyTransfer:HVAC | 6942.40 | 950.69 | 25-FEB-15:50 | 767187.08 | 21-JUL-18:20 |
CoolingCoils:EnergyTransfer | 5332.67 | 0.00 | 01-JAN-04:10 | 700494.68 | 20-JUL-22:00 |
EnergyTransfer:Zone:BASEMENT | 326.73 | 4890.63 | 26-MAR-15:00 | 19881.44 | 22-SEP-21:00 |
Heating:EnergyTransfer | 29.22 | 0.00 | 01-JAN-08:10 | 33352.38 | 26-DEC-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 29.22 | 0.00 | 01-JAN-08:10 | 33352.38 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 5211.76 | 79665.00 | 26-DEC-15:00 | 336734.01 | 15-JUN-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 326.73 | 4890.63 | 26-MAR-15:00 | 19881.44 | 22-SEP-21:00 |
General:Cooling:EnergyTransfer | 5211.76 | 79665.00 | 26-DEC-15:00 | 336734.01 | 15-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 326.73 | 4890.63 | 26-MAR-15:00 | 19881.44 | 22-SEP-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 46.09 | 0.12 | 26-DEC-15:50 | 3526.29 | 18-OCT-13:00 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 600.44 | 27-DEC-07:30 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 600.44 | 27-DEC-07:30 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 46.07 | 0.00 | 26-JAN-07:10 | 3526.29 | 18-OCT-13:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 46.07 | 0.00 | 26-JAN-07:10 | 3526.29 | 18-OCT-13:00 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.29 | 744.19 | 26-DEC-15:00 | 2248.32 | 15-JUN-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.29 | 744.19 | 26-DEC-15:00 | 2248.32 | 15-JUN-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.29 | 744.19 | 26-DEC-15:00 | 2248.32 | 15-JUN-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 29.16 | 197.44 | 27-DEC-10:40 | 2058.23 | 15-JUN-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 29.16 | 197.44 | 27-DEC-10:40 | 2058.23 | 15-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 29.16 | 197.44 | 27-DEC-10:40 | 2058.23 | 15-JUN-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 15.20 | 41.03 | 27-DEC-10:20 | 945.74 | 15-JUN-21:00 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 15.20 | 41.03 | 27-DEC-10:20 | 945.74 | 15-JUN-21:00 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 15.20 | 41.03 | 27-DEC-10:20 | 945.74 | 15-JUN-21:00 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 612.29 | 9964.43 | 27-DEC-05:00 | 39337.55 | 15-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 612.29 | 9964.43 | 27-DEC-05:00 | 39337.55 | 15-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 612.29 | 9964.43 | 27-DEC-05:00 | 39337.55 | 15-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 241.52 | 2621.95 | 26-DEC-11:30 | 12779.25 | 11-NOV-11:00 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 241.52 | 2621.95 | 26-DEC-11:30 | 12779.25 | 11-NOV-11:00 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 241.52 | 2621.95 | 26-DEC-11:30 | 12779.25 | 11-NOV-11:00 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 812.57 | 15927.29 | 26-DEC-15:00 | 43649.78 | 07-AUG-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 812.57 | 15927.29 | 26-DEC-15:00 | 43649.78 | 07-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 812.57 | 15927.29 | 26-DEC-15:00 | 43649.78 | 07-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 74.47 | 0.00 | 01-JAN-08:10 | 10538.08 | 05-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 3.01 | 0.00 | 01-JAN-00:10 | 3653.81 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 3.01 | 0.00 | 01-JAN-00:10 | 3653.81 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 71.46 | 0.00 | 01-JAN-03:40 | 10538.08 | 05-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 71.46 | 0.00 | 01-JAN-03:40 | 10538.08 | 05-OCT-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 62.56 | 0.00 | 01-JAN-08:10 | 10548.28 | 25-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 5.75 | 0.00 | 01-JAN-08:10 | 4083.22 | 27-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 5.75 | 0.00 | 01-JAN-08:10 | 4083.22 | 27-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 56.81 | 0.00 | 01-JAN-00:10 | 10548.28 | 25-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 56.81 | 0.00 | 01-JAN-00:10 | 10548.28 | 25-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 408.94 | 0.00 | 01-JAN-02:00 | 45960.28 | 22-OCT-13:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 408.94 | 0.00 | 01-JAN-02:00 | 45960.28 | 22-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 408.94 | 0.00 | 01-JAN-02:00 | 45960.28 | 22-OCT-13:20 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 457.93 | 0.00 | 01-JAN-08:10 | 69271.45 | 14-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 4.88 | 0.00 | 01-JAN-00:10 | 16115.92 | 22-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 4.88 | 0.00 | 01-JAN-00:10 | 16115.92 | 22-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 453.05 | 0.00 | 01-JAN-08:10 | 69271.45 | 14-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 453.05 | 0.00 | 01-JAN-08:10 | 69271.45 | 14-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 75.68 | 0.00 | 01-JAN-08:10 | 9478.87 | 17-JUN-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 3.15 | 0.00 | 01-JAN-00:10 | 3787.82 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 3.15 | 0.00 | 01-JAN-00:10 | 3787.82 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 72.53 | 0.00 | 01-JAN-00:50 | 9478.87 | 17-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 72.53 | 0.00 | 01-JAN-00:50 | 9478.87 | 17-JUN-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 63.08 | 0.00 | 01-JAN-08:10 | 11239.38 | 20-MAY-09:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 5.77 | 0.00 | 01-JAN-08:10 | 3982.09 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 5.77 | 0.00 | 01-JAN-08:10 | 3982.09 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 57.31 | 0.00 | 01-JAN-00:10 | 11239.38 | 20-MAY-09:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 57.31 | 0.00 | 01-JAN-00:10 | 11239.38 | 20-MAY-09:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 169.52 | 29.66 | 26-DEC-15:50 | 10656.49 | 15-JUN-18:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 817.91 | 27-DEC-07:30 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 817.91 | 27-DEC-07:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 169.51 | 0.00 | 26-DEC-09:10 | 10656.49 | 15-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 169.51 | 0.00 | 26-DEC-09:10 | 10656.49 | 15-JUN-18:30 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 19.27 | 0.00 | 01-JAN-08:10 | 2852.66 | 14-JUN-16:50 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 1.76 | 0.00 | 01-JAN-08:10 | 1151.63 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 1.76 | 0.00 | 01-JAN-08:10 | 1151.63 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 17.51 | 0.00 | 01-JAN-00:10 | 2852.66 | 14-JUN-16:50 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 17.51 | 0.00 | 01-JAN-00:10 | 2852.66 | 14-JUN-16:50 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 17.06 | 0.00 | 01-JAN-08:10 | 2880.20 | 25-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 2.86 | 0.00 | 01-JAN-08:10 | 1334.37 | 27-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 2.86 | 0.00 | 01-JAN-08:10 | 1334.37 | 27-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 14.19 | 0.00 | 01-JAN-00:10 | 2880.20 | 25-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 14.19 | 0.00 | 01-JAN-00:10 | 2880.20 | 25-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 111.90 | 0.00 | 01-JAN-08:10 | 14244.47 | 18-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 1.97 | 0.00 | 01-JAN-00:10 | 4036.76 | 27-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 1.97 | 0.00 | 01-JAN-00:10 | 4036.76 | 27-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 109.93 | 0.00 | 01-JAN-08:10 | 14244.47 | 18-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 109.93 | 0.00 | 01-JAN-08:10 | 14244.47 | 18-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 452.81 | 8627.28 | 26-DEC-15:00 | 23585.63 | 15-JUN-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 452.81 | 8627.28 | 26-DEC-15:00 | 23585.63 | 15-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 452.81 | 8627.28 | 26-DEC-15:00 | 23585.63 | 15-JUN-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 490.41 | 9631.30 | 26-DEC-15:00 | 24773.83 | 15-JUN-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 490.41 | 9631.30 | 26-DEC-15:00 | 24773.83 | 15-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 490.41 | 9631.30 | 26-DEC-15:00 | 24773.83 | 15-JUN-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 618.51 | 8455.54 | 27-DEC-04:00 | 29780.76 | 02-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 618.51 | 8455.54 | 27-DEC-04:00 | 29780.76 | 02-JUL-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 97.99 | 0.09 | 26-DEC-11:00 | 6630.49 | 03-JUL-12:50 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.05 | 0.00 | 01-JAN-00:10 | 1215.75 | 27-DEC-07:30 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.05 | 0.00 | 01-JAN-00:10 | 1215.75 | 27-DEC-07:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 97.94 | 0.00 | 07-JAN-07:10 | 6630.49 | 03-JUL-12:50 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 97.94 | 0.00 | 07-JAN-07:10 | 6630.49 | 03-JUL-12:50 |
PlantLoopHeatingDemand:Facility | 2624.66 | 7607.59 | 31-JUL-01:20 | 291667.13 | 01-FEB-19:00 |
PlantLoopHeatingDemand:Plant | 2198.13 | 7607.59 | 31-JUL-01:20 | 205865.05 | 01-MAY-20:30 |
WaterSystems:PlantLoopHeatingDemand | 2198.13 | 7607.59 | 31-JUL-01:20 | 205865.05 | 01-MAY-20:30 |
General:WaterSystems:PlantLoopHeatingDemand | 665.43 | 7603.85 | 31-JUL-00:10 | 51239.01 | 02-FEB-07:10 |
HeatingCoils:EnergyTransfer | 426.53 | 0.00 | 01-JAN-11:40 | 125636.99 | 20-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 426.53 | 0.00 | 01-JAN-11:40 | 125636.99 | 20-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 426.53 | 0.00 | 01-JAN-11:40 | 125636.99 | 20-DEC-07:10 |
HeatRecoveryForHeating:EnergyTransfer | 909.26 | 0.00 | 01-JAN-08:10 | 362632.48 | 03-FEB-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 273.94 | 0.00 | 01-JAN-00:10 | 164081.59 | 21-JUL-18:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 1532.70 | 0.00 | 01-JAN-00:10 | 170605.56 | 01-MAY-20:30 |
WaterSystems:EnergyTransfer | 665.43 | 7603.85 | 31-JUL-00:10 | 51239.01 | 02-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 665.43 | 7603.85 | 31-JUL-00:10 | 51239.01 | 02-FEB-07:10 |
Boilers:EnergyTransfer | 422.64 | 0.00 | 01-JAN-11:40 | 127100.87 | 20-DEC-09:10 |
Chillers:EnergyTransfer | 4284.87 | 0.00 | 01-JAN-04:00 | 622013.54 | 21-JUL-21:00 |
HeatRejection:EnergyTransfer | 5653.72 | 0.00 | 01-JAN-04:00 | 773782.08 | 21-JUL-21:00 |
General:HeatRejection:EnergyTransfer | 5653.72 | 0.00 | 01-JAN-04:00 | 773782.08 | 21-JUL-21:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -326.730 | 0.000 | 0.000 | 142.137 | 102.033 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -60.546 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.013 | -46.073 | 0.000 | 0.000 | 14.704 | 5.638 | 10.186 | 23.676 | 0.000 | 0.117 | 0.353 | 0.000 | -8.074 | 0.000 | -0.540 | -0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -37.295 | 0.000 | 0.000 | 16.262 | 6.529 | 11.795 | 0.000 | 0.000 | 0.046 | 2.888 | 0.000 | 0.000 | 0.000 | -0.226 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -29.162 | 0.000 | 0.000 | 3.596 | 7.530 | 12.471 | 0.000 | 0.000 | 0.111 | 5.939 | 0.000 | 0.000 | 0.000 | -0.485 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.000 | -15.198 | 0.000 | 0.000 | 2.787 | 1.680 | 3.598 | 0.000 | 0.000 | 0.065 | 7.344 | 0.000 | 0.000 | 0.000 | -0.276 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -612.295 | 0.000 | 0.000 | 11.143 | 4.410 | 658.131 | 0.000 | 0.000 | 0.164 | 0.000 | 0.000 | 0.000 | 0.000 | -0.727 | -60.826 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -241.521 | 0.000 | 0.000 | 182.529 | 11.735 | 14.341 | 65.773 | 0.000 | 0.260 | 0.000 | 0.000 | -24.586 | 0.000 | -1.329 | -7.200 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -812.575 | 0.000 | 0.000 | 538.629 | 110.778 | 148.998 | 87.492 | 0.000 | 0.751 | 0.000 | 0.000 | -32.606 | 0.000 | -3.837 | -37.629 |
ROOM_1_FLR_3 | 4.683 | -62.249 | 0.000 | -10.878 | 0.000 | 0.000 | 9.657 | 5.554 | 12.292 | 50.896 | 0.000 | 0.498 | 8.012 | 0.000 | -16.800 | 0.000 | -1.665 | -0.002 |
ROOM_2_FLR_3 | 8.066 | -47.871 | 0.000 | -11.256 | 0.000 | 0.000 | 9.568 | 5.553 | 12.291 | 38.126 | 0.000 | 0.400 | 4.713 | 0.000 | -17.582 | 0.000 | -2.008 | -0.001 |
ROOM_3_MULT19_FLR_3 | 0.000 | -393.914 | 0.000 | -15.023 | 0.000 | 0.000 | 0.000 | 66.316 | 228.754 | 260.282 | 0.000 | 0.743 | 0.004 | 0.000 | -135.936 | 0.000 | -9.745 | -1.477 |
ROOM_4_MULT19_FLR_3 | 18.351 | -316.048 | 0.000 | -150.461 | 0.000 | 0.000 | 182.615 | 66.334 | 228.817 | 100.157 | 0.000 | 2.730 | 0.002 | 0.000 | -94.790 | 0.000 | -18.458 | -19.247 |
ROOM_5_FLR_3 | 4.817 | -63.307 | 0.000 | -10.882 | 0.000 | 0.000 | 9.648 | 5.554 | 12.292 | 51.010 | 0.000 | 0.497 | 8.229 | 0.000 | -16.177 | 0.000 | -1.679 | -0.002 |
ROOM_6_FLR_3 | 8.005 | -48.263 | 0.000 | -11.287 | 0.000 | 0.000 | 9.560 | 5.553 | 12.291 | 37.591 | 0.000 | 0.402 | 4.493 | 0.000 | -16.395 | 0.000 | -1.949 | -0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.004 | -169.514 | 0.000 | 0.000 | 113.457 | 51.065 | 0.000 | 43.002 | 0.000 | 0.334 | 0.000 | 0.000 | -22.329 | 0.000 | -1.507 | -14.512 |
ROOM_1_FLR_6 | 2.334 | -15.367 | 0.000 | -2.718 | 0.000 | 0.000 | 2.417 | 1.388 | 3.073 | 12.665 | 0.000 | 0.128 | 0.638 | 0.000 | -4.122 | 0.000 | -0.437 | -0.000 |
ROOM_2_FLR_6 | 3.562 | -12.085 | 0.000 | -2.803 | 0.000 | 0.000 | 2.397 | 1.388 | 3.073 | 9.505 | 0.000 | 0.101 | 0.000 | 0.000 | -4.304 | 0.000 | -0.522 | -0.312 |
ROOM_3_MULT9_FLR_6 | 3.669 | -94.121 | 0.000 | -17.510 | 0.000 | 0.000 | 21.691 | 7.855 | 27.097 | 63.919 | 0.000 | 0.732 | 8.518 | 0.000 | -19.147 | 0.000 | -2.704 | -0.001 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -452.819 | 0.000 | 0.000 | 315.526 | 25.687 | 175.857 | 9.653 | 0.000 | 0.157 | 0.000 | 0.000 | -13.853 | 0.000 | -0.885 | -59.323 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -490.416 | 0.000 | 0.000 | 314.749 | 25.687 | 175.857 | 9.414 | 0.000 | 0.156 | 0.000 | 0.000 | -14.302 | 0.000 | -0.893 | -20.253 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -618.495 | 0.000 | 0.000 | 28.233 | 12.005 | 540.650 | 24.080 | 0.000 | 0.140 | 23.784 | 0.000 | -9.599 | 0.000 | -0.797 | -0.001 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.051 | -97.944 | 0.000 | 0.000 | 30.343 | 13.511 | 0.000 | 20.807 | 0.000 | 0.142 | 43.646 | 0.000 | -9.901 | 0.000 | -0.653 | 0.000 |
Total Facility | 53.487 | -1053.225 | 0.068 | -4182.856 | 0.000 | 0.000 | 1961.649 | 543.784 | 2434.967 | 908.045 | 0.000 | 8.675 | 118.563 | 0.000 | -460.502 | 0.000 | -51.324 | -281.333 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 22-SEP-21:00 | 0.00 | 0.00 | 0.00 | -19881.78 | 0.00 | 0.00 | 5924.45 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2585.23 |
RETAIL_1_FLR_1 | 18-OCT-13:00 | 0.00 | 0.00 | 0.00 | -3526.17 | 0.00 | 0.00 | 150.60 | 128.08 | 252.59 | 4397.46 | 0.00 | 9.59 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1412.16 |
RETAIL_2_FLR_1 | 15-JUN-21:00 | 0.00 | 0.00 | 0.00 | -2248.39 | 0.00 | 0.00 | 697.61 | 474.61 | 752.15 | 0.00 | 0.00 | 8.85 | 315.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 15-JUN-20:00 | 0.00 | 0.00 | 0.00 | -2058.38 | 0.00 | 0.00 | 129.08 | 615.76 | 839.45 | 0.00 | 0.00 | 22.12 | 451.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 15-JUN-21:00 | 0.00 | 0.00 | 0.00 | -945.79 | 0.00 | 0.00 | 113.48 | 122.09 | 229.41 | 0.00 | 0.00 | 12.07 | 468.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 15-JUN-20:00 | 0.00 | 0.00 | 0.00 | -39338.08 | 0.00 | 0.00 | 408.86 | 360.62 | 44299.38 | 0.00 | 0.00 | 30.20 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5760.97 |
CAFE_FLR_1 | 11-NOV-11:00 | 0.00 | 0.00 | 0.00 | -12773.68 | 0.00 | 0.00 | 4948.61 | 103.85 | 406.43 | 12584.67 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -45.78 | -5224.10 |
LOBBY_FLR_1 | 07-AUG-21:10 | 0.00 | 0.00 | 0.00 | -43656.00 | 0.00 | 0.00 | 26440.07 | 6387.23 | 7389.94 | 804.47 | 0.00 | 114.17 | 2520.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 11-MAY-15:01 | 0.00 | -13020.10 | 0.00 | -642.76 | 0.00 | 0.00 | 235.29 | 119.69 | 273.93 | 7494.00 | 0.00 | 36.36 | 5503.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 14-JUN-08:11 | 0.00 | -14223.40 | 0.00 | -746.45 | 0.00 | 0.00 | 78.21 | 188.06 | 452.99 | 1514.36 | 0.00 | 21.63 | 12714.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 22-OCT-13:15 | 0.00 | -45961.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1684.44 | 5686.12 | 50601.93 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -23.26 | -11987.32 |
ROOM_4_MULT19_FLR_3 | 14-JUN-08:11 | 0.00 | -85547.27 | 0.00 | -9570.62 | 0.00 | 0.00 | 1600.92 | 2246.49 | 8433.45 | 9492.10 | 0.00 | 133.09 | 73211.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 14-JUN-08:61 | 0.00 | -11533.05 | 0.00 | -649.65 | 0.00 | 0.00 | 87.14 | 188.08 | 453.05 | 7461.82 | 0.00 | 28.11 | 3964.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 14-JUN-07:52 | 0.00 | -14154.68 | 0.00 | 0.00 | 0.00 | 0.00 | 126.51 | 188.06 | 452.99 | 7266.21 | 0.00 | 3.23 | 6117.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 15-JUN-18:25 | 0.00 | 0.00 | 0.00 | -10657.12 | 0.00 | 0.00 | 4080.26 | 3712.00 | 0.00 | 2645.03 | 0.00 | 79.01 | 140.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 17-MAY-15:01 | 0.00 | -3487.03 | 0.00 | -160.76 | 0.00 | 0.00 | 58.82 | 29.92 | 68.48 | 1856.95 | 0.00 | 9.77 | 1623.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 14-JUN-08:11 | 0.00 | -3771.97 | 0.00 | -184.58 | 0.00 | 0.00 | 19.64 | 47.02 | 113.25 | 381.75 | 0.00 | 5.50 | 3389.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 14-APR-15:01 | 0.00 | -15386.27 | 0.00 | -1034.94 | 0.00 | 0.00 | 529.39 | 169.29 | 603.86 | 3953.80 | 0.00 | 34.11 | 11130.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 15-JUN-21:20 | 0.00 | 0.00 | 0.00 | -23588.73 | 0.00 | 0.00 | 15612.95 | 1657.87 | 6747.90 | 250.16 | 0.00 | 27.12 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -707.28 |
DINING_FLR_6 | 15-JUN-21:20 | 0.00 | 0.00 | 0.00 | -24777.20 | 0.00 | 0.00 | 15608.51 | 1657.87 | 6747.90 | 237.10 | 0.00 | 27.12 | 498.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 02-JUL-10:40 | 0.00 | 0.00 | 0.00 | -29771.35 | 0.00 | 0.00 | 464.25 | 327.25 | 23951.61 | 2642.53 | 0.00 | 25.54 | 2360.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 03-JUL-12:50 | 0.00 | 0.00 | 0.00 | -6629.39 | 0.00 | 0.00 | 308.46 | 306.92 | 0.00 | 1934.88 | 0.00 | 37.79 | 4041.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 26-JUL-18:02 | 0.00 | -159561.54 | 0.00 | -204931.69 | 0.00 | 0.00 | 73937.37 | 37442.83 | 121562.63 | 49228.72 | 0.00 | 1403.37 | 80918.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 27-DEC-07:30 | 0.00 | 0.00 | 600.23 | 0.00 | 0.00 | 0.00 | 357.98 | 256.16 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1161.31 | 0.00 | -71.09 | -414.98 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 27-DEC-09:01 | 8195.99 | 295.79 | 0.00 | -295.79 | 0.00 | 0.00 | 107.10 | 188.08 | 453.05 | 1200.49 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -134.88 | -10009.83 |
ROOM_2_FLR_3 | 27-DEC-09:01 | 8299.03 | 266.57 | 0.00 | -266.57 | 0.00 | 0.00 | 108.88 | 188.06 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1092.67 | 0.00 | -131.99 | -7824.31 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 27-JAN-09:01 | 46241.32 | 4943.23 | 0.00 | -4943.23 | 0.00 | 0.00 | 1908.11 | 2246.49 | 8433.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8450.00 | 0.00 | -768.57 | -49610.80 |
ROOM_5_FLR_3 | 26-DEC-16:01 | 7959.40 | 270.20 | 0.00 | -270.20 | 0.00 | 0.00 | 293.39 | 119.69 | 273.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1503.97 | 0.00 | -112.61 | -7029.83 |
ROOM_6_FLR_3 | 26-DEC-16:01 | 7978.86 | 265.00 | 0.00 | -265.00 | 0.00 | 0.00 | 293.98 | 119.68 | 273.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1520.10 | 0.00 | -112.10 | -7034.22 |
CORRIDOR_FLR_3 | 27-DEC-07:30 | 0.00 | 0.00 | 817.77 | 0.00 | 0.00 | 0.00 | 2771.54 | 2320.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3403.51 | 0.00 | -199.92 | -2305.88 |
ROOM_1_FLR_6 | 27-DEC-09:01 | 2506.87 | 69.33 | 0.00 | -69.33 | 0.00 | 0.00 | 27.22 | 47.02 | 113.26 | 315.72 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -33.36 | -2976.72 |
ROOM_2_FLR_6 | 27-DEC-09:01 | 2530.30 | 67.85 | 0.00 | -67.85 | 0.00 | 0.00 | 27.22 | 47.02 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -263.14 | 0.00 | -33.22 | -2421.42 |
ROOM_3_MULT9_FLR_6 | 26-DEC-09:01 | 11517.71 | 567.92 | 0.00 | -567.92 | 0.00 | 0.00 | 231.97 | 266.03 | 998.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -460.32 | 0.00 | -159.87 | -12394.22 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 27-DEC-07:30 | 0.00 | 0.00 | 1215.45 | 0.00 | 0.00 | 0.00 | 733.27 | 613.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1516.33 | 0.00 | -88.66 | -957.58 |
Total Facility | 26-DEC-16:01 | 8485.08 | 92564.05 | 0.00 | -92564.05 | 0.00 | 0.00 | 59245.67 | 11852.74 | 76844.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -39580.27 | 0.00 | -3173.13 | -113674.21 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 23.2937 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 23.1718 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6702 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6702 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3126 | 2.3126 | 1.1586 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3417 | 0.3417 | 0.1712 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2507 | 0.2507 | 0.1256 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2243 | 0.2243 | 0.1124 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1219 | 0.1219 | 0.0611 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7638 | 3.7638 | 1.8856 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5302 | 1.5302 | 0.7666 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1114 | 5.1114 | 2.5608 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3207 | 1.3207 | 0.6617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4718 | 2.4718 | 1.2383 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5938 | 2.5938 | 1.2995 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4738 | 2.4738 | 1.2394 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7771 | 0.7771 | 0.3893 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 23.2937 | 23.1718 | 23.2937 | 11.6702 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1586 | 1.1586 | 1.1586 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1712 | 0.1712 | 0.1712 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1256 | 0.1256 | 0.1256 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1124 | 0.1124 | 0.1124 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0611 | 0.0611 | 0.0611 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8856 | 1.8856 | 1.8856 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7666 | 0.7666 | 0.7666 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5608 | 2.5608 | 2.5608 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6617 | 0.6617 | 0.6617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2383 | 1.2383 | 1.2383 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2995 | 1.2995 | 1.2995 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2394 | 1.2394 | 1.2394 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3893 | 0.3893 | 0.3893 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6702 | 11.6702 | 11.6702 | 11.6702 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 81.00 |
Number of hours not met | 81.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 580.99 | 174026.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1368.84 | 157879.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 543.78 | 45424.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 174.48 | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 952.41 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 22.42 | 1279.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 590.50 | 47073.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 122.13 | 5961.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 141.57 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4738.77 | 953.38 | 100722.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Other | 0.00 | 39623.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.77 | 1307.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 20.97 | 715.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1771.97 | 5838.11 |
Natural Gas | 1788.84 | 3323.21 |
Additional | 0.00 | 0.00 |
Total | 3560.81 | 9161.32 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 47.93 |
Space Heating | 0.00 |
Space Cooling | 120.65 |
Fans (All) | 52.05 |
Service Water Heating | 42.61 |
Receptacle Equipment | 152.32 |
Miscellaneous (All) | 514.58 |
Subtotal | 514.58 |
Natural Gas [MJ/m2] | |
Space Heating | 51.21 |
Service Water Heating | 84.03 |
Miscellaneous (All) | 292.92 |
Subtotal | 292.92 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.94 |
Space Heating | 6.34 |
Space Cooling | 14.94 |
Fans (All) | 6.45 |
Service Water Heating | 15.68 |
Receptacle Equipment | 38.39 |
Miscellaneous | 12.26 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2398. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 2482. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8708.83 | 51.17 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8718.83 | 41.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8708.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 51.17 | 0.00 | 0.00 | 0.00 |
Average | 8755.80 | 4.20 | 0.00 | 0.00 | 0.00 |
Sum | 192627.67 | 92.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8748.50 | 11.50 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8187.17 | 572.83 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8338.33 | 421.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8725.50 | 34.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8631.67 | 128.33 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8753.33 | 6.67 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8634.83 | 125.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8610.50 | 149.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8720.83 | 39.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8298.50 | 461.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8336.50 | 423.50 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8748.83 | 11.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8187.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 572.83 | 0.00 | 0.00 | 0.00 |
Average | 8651.56 | 108.44 | 0.00 | 0.00 | 0.00 |
Sum | 190334.33 | 2385.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59031.50 | 124.50 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 642299.67 | 68117.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1966125.83 | 149303.17 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4153.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4153.33 | 0.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 97794.33 | 2563.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4150.33 | 3.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1148851.50 | 96863.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1156001.00 | 89714.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108217.67 | 51.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1966125.83 | 149303.17 | 0.00 | 0.00 | 0.00 |
Average | 270398.73 | 18488.31 | 0.00 | 0.00 | 0.00 |
Sum | 5948772.17 | 406742.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.261577E+11 | 11718.02 | 06-JAN-22:00 | 4.40 | -0.9 | 0.785459E+10 | 4837.00 | 27-JAN-22:19 | 2.97 | -2.4 |
February | 0.203618E+11 | 10922.41 | 01-FEB-21:00 | 3.30 | -1.9 | 0.635421E+10 | 4724.83 | 01-FEB-22:10 | 1.78 | -2.6 |
March | 0.195655E+11 | 9418.81 | 01-MAR-21:00 | 1.70 | -3.0 | 0.646533E+10 | 4189.91 | 01-MAR-22:10 | 1.02 | -3.3 |
April | 0.200046E+11 | 10026.62 | 30-APR-10:33 | 24.07 | 13.08 | 0.627762E+10 | 4046.79 | 07-APR-22:10 | 24.07 | 13.08 |
May | 0.223738E+11 | 10584.76 | 21-MAY-10:33 | 29.47 | 14.38 | 0.671918E+10 | 4186.88 | 12-MAY-22:10 | 29.47 | 14.38 |
June | 0.233718E+11 | 11385.07 | 15-JUN-18:10 | 35.92 | 14.47 | 0.675426E+10 | 4346.47 | 23-JUN-22:10 | 23.40 | 15.27 |
July | 0.279417E+11 | 12893.89 | 26-JUL-18:10 | 33.77 | 19.75 | 0.777451E+10 | 4837.09 | 19-JUL-22:10 | 33.77 | 19.75 |
August | 0.320189E+11 | 17180.18 | 24-AUG-21:00 | 26.70 | 16.71 | 0.819569E+10 | 4837.22 | 22-AUG-00:10 | 26.70 | 16.71 |
September | 0.353148E+11 | 19881.44 | 22-SEP-21:00 | 25.00 | 17.90 | 0.796088E+10 | 4837.32 | 19-SEP-04:10 | 25.00 | 17.90 |
October | 0.359278E+11 | 19770.76 | 06-OCT-21:00 | 11.70 | 9.48 | 0.822455E+10 | 4837.28 | 10-OCT-21:19 | 13.87 | 9.12 |
November | 0.331358E+11 | 19296.76 | 01-NOV-21:00 | 10.00 | 7.90 | 0.795058E+10 | 4837.42 | 01-NOV-01:10 | 10.00 | 7.90 |
December | 0.305538E+11 | 17594.45 | 01-DEC-22:00 | 7.20 | 2.26 | 0.819295E+10 | 4837.11 | 13-DEC-00:40 | 7.57 | 6.48 |
Annual Sum or Average | 0.326728E+12 | 0.887243E+11 | ||||||||
Minimum of Months | 0.195655E+11 | 9418.81 | 1.70 | -3.0 | 0.627762E+10 | 4046.79 | 1.02 | -3.3 | ||
Maximum of Months | 0.359278E+11 | 19881.44 | 35.92 | 19.75 | 0.822455E+10 | 4837.42 | 33.77 | 19.75 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292038E+10 | 2781.30 | 12-JAN-13:50 | 18.03 | 9.58 | 0.668802E+09 | 444.01 | 12-JAN-22:19 | 9.47 | 5.03 |
February | 0.285529E+10 | 2826.90 | 07-FEB-13:30 | 20.30 | 9.54 | 0.613271E+09 | 463.90 | 06-FEB-22:30 | 20.30 | 9.54 |
March | 0.316941E+10 | 2186.94 | 16-MAR-13:20 | 22.40 | 9.11 | 0.688166E+09 | 466.96 | 16-MAR-21:30 | 16.65 | 6.00 |
April | 0.361844E+10 | 2270.33 | 04-APR-13:30 | 26.95 | 10.78 | 0.716150E+09 | 491.84 | 28-APR-22:10 | 21.52 | 12.87 |
May | 0.406494E+10 | 2216.71 | 31-MAY-18:03 | 30.92 | 15.25 | 0.779949E+09 | 491.84 | 17-MAY-22:10 | 30.92 | 15.25 |
June | 0.448176E+10 | 2593.65 | 15-JUN-18:03 | 35.92 | 14.47 | 0.790154E+09 | 491.86 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.466080E+10 | 2591.44 | 26-JUL-18:03 | 33.77 | 19.75 | 0.814189E+09 | 491.84 | 05-JUL-22:10 | 33.77 | 19.75 |
August | 0.473684E+10 | 2756.61 | 27-AUG-12:00 | 33.30 | 15.93 | 0.812620E+09 | 491.86 | 22-AUG-00:10 | 33.30 | 15.93 |
September | 0.481038E+10 | 3398.53 | 20-SEP-12:50 | 32.12 | 17.95 | 0.780359E+09 | 491.84 | 19-SEP-23:10 | 32.12 | 17.95 |
October | 0.452291E+10 | 3526.29 | 18-OCT-13:00 | 27.80 | 18.14 | 0.766233E+09 | 491.85 | 05-OCT-23:49 | 27.80 | 18.14 |
November | 0.355562E+10 | 3348.37 | 10-NOV-12:10 | 20.45 | 11.93 | 0.681330E+09 | 491.00 | 09-NOV-22:19 | 20.45 | 11.93 |
December | 0.267568E+10 | 2527.86 | 16-DEC-13:30 | 14.45 | 3.99 | 0.659053E+09 | 427.06 | 15-DEC-22:30 | 14.45 | 3.99 |
Annual Sum or Average | 0.460724E+11 | 0.877028E+10 | ||||||||
Minimum of Months | 0.267568E+10 | 2186.94 | 14.45 | 3.99 | 0.613271E+09 | 427.06 | 9.47 | 3.99 | ||
Maximum of Months | 0.481038E+10 | 3526.29 | 35.92 | 19.75 | 0.814189E+09 | 491.86 | 33.77 | 19.75 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.260152E+10 | 1290.59 | 12-JAN-22:00 | 10.60 | 5.73 | 0.873747E+09 | 569.52 | 04-JAN-22:19 | 10.60 | 5.73 |
February | 0.241499E+10 | 1457.44 | 21-FEB-22:00 | 14.40 | 4.35 | 0.800300E+09 | 569.54 | 22-FEB-22:19 | 14.40 | 4.92 |
March | 0.274366E+10 | 1520.82 | 16-MAR-21:00 | 17.20 | 5.94 | 0.901230E+09 | 569.55 | 16-MAR-22:10 | 15.27 | 5.99 |
April | 0.297981E+10 | 1849.48 | 28-APR-20:55 | 22.80 | 12.84 | 0.906625E+09 | 569.66 | 17-APR-01:10 | 22.80 | 12.84 |
May | 0.340364E+10 | 2027.93 | 19-MAY-21:00 | 30.00 | 13.65 | 0.955191E+09 | 569.57 | 18-MAY-00:10 | 30.00 | 13.65 |
June | 0.364347E+10 | 2248.32 | 15-JUN-21:00 | 33.30 | 13.72 | 0.934455E+09 | 569.57 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.375692E+10 | 2209.13 | 26-JUL-21:00 | 28.90 | 18.16 | 0.962349E+09 | 569.55 | 19-JUL-22:10 | 28.90 | 18.16 |
August | 0.371189E+10 | 2245.92 | 07-AUG-21:00 | 31.70 | 16.85 | 0.965570E+09 | 569.57 | 22-AUG-00:10 | 24.22 | 16.48 |
September | 0.352467E+10 | 2134.65 | 20-SEP-20:10 | 25.40 | 15.25 | 0.932585E+09 | 569.58 | 19-SEP-04:10 | 25.40 | 15.25 |
October | 0.323733E+10 | 2055.06 | 05-OCT-20:10 | 23.80 | 16.56 | 0.947631E+09 | 569.56 | 10-OCT-21:10 | 14.13 | 9.16 |
November | 0.273260E+10 | 1700.78 | 09-NOV-22:00 | 18.90 | 11.06 | 0.880029E+09 | 569.55 | 09-NOV-23:10 | 16.70 | 10.07 |
December | 0.254385E+10 | 1205.73 | 07-DEC-21:00 | 9.40 | 3.58 | 0.861370E+09 | 565.49 | 07-DEC-22:30 | 5.55 | 1.60 |
Annual Sum or Average | 0.372944E+11 | 0.109211E+11 | ||||||||
Minimum of Months | 0.241499E+10 | 1205.73 | 9.40 | 3.58 | 0.800300E+09 | 565.49 | 5.55 | 1.60 | ||
Maximum of Months | 0.375692E+10 | 2248.32 | 33.30 | 18.16 | 0.965570E+09 | 569.66 | 30.00 | 18.16 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185448E+10 | 907.23 | 03-JAN-21:00 | 14.40 | 6.79 | 0.158945E+09 | 102.59 | 03-JAN-22:10 | 12.43 | 6.06 |
February | 0.175810E+10 | 957.12 | 21-FEB-21:00 | 15.00 | 4.44 | 0.146808E+09 | 106.01 | 23-FEB-22:10 | 11.93 | 4.94 |
March | 0.206420E+10 | 1011.20 | 16-MAR-18:09 | 19.82 | 7.14 | 0.168006E+09 | 109.18 | 16-MAR-21:10 | 17.02 | 5.96 |
April | 0.232673E+10 | 1194.93 | 30-APR-10:33 | 24.07 | 13.08 | 0.176728E+09 | 118.96 | 21-APR-22:10 | 24.07 | 13.08 |
May | 0.273983E+10 | 1654.71 | 31-MAY-21:00 | 28.30 | 13.66 | 0.196487E+09 | 120.45 | 24-MAY-21:49 | 28.30 | 13.66 |
June | 0.310955E+10 | 2058.23 | 15-JUN-20:00 | 33.90 | 14.00 | 0.197570E+09 | 120.46 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.323081E+10 | 2045.68 | 03-JUL-20:00 | 28.30 | 19.12 | 0.203551E+09 | 120.46 | 05-JUL-22:10 | 27.70 | 17.66 |
August | 0.306998E+10 | 1993.32 | 07-AUG-20:00 | 31.70 | 17.36 | 0.202978E+09 | 120.46 | 22-AUG-00:10 | 24.22 | 16.48 |
September | 0.274967E+10 | 1644.79 | 22-SEP-20:00 | 26.10 | 18.64 | 0.192966E+09 | 120.46 | 20-SEP-22:10 | 26.10 | 18.64 |
October | 0.249640E+10 | 1419.20 | 05-OCT-21:00 | 23.30 | 16.16 | 0.187039E+09 | 120.45 | 03-OCT-21:19 | 23.30 | 16.16 |
November | 0.203178E+10 | 1055.24 | 10-NOV-11:33 | 20.93 | 12.02 | 0.164314E+09 | 112.48 | 10-NOV-22:10 | 15.50 | 8.35 |
December | 0.173008E+10 | 880.87 | 10-DEC-11:33 | 15.93 | 7.48 | 0.157311E+09 | 100.48 | 11-DEC-22:10 | 8.80 | 4.97 |
Annual Sum or Average | 0.291616E+11 | 0.215270E+10 | ||||||||
Minimum of Months | 0.173008E+10 | 880.87 | 14.40 | 4.44 | 0.146808E+09 | 100.48 | 8.80 | 4.94 | ||
Maximum of Months | 0.323081E+10 | 2058.23 | 33.90 | 19.12 | 0.203551E+09 | 120.46 | 28.43 | 18.64 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.960742E+09 | 479.77 | 01-JAN-11:33 | 13.87 | 8.54 | 0.120206E+09 | 76.37 | 03-JAN-22:40 | 11.33 | 5.60 |
February | 0.923338E+09 | 519.27 | 20-FEB-11:33 | 20.37 | 8.19 | 0.111027E+09 | 78.88 | 07-FEB-23:10 | 20.37 | 8.19 |
March | 0.109076E+10 | 539.74 | 16-MAR-10:33 | 20.03 | 8.28 | 0.126866E+09 | 81.36 | 16-MAR-21:49 | 16.28 | 6.02 |
April | 0.124044E+10 | 644.18 | 30-APR-10:33 | 24.07 | 13.08 | 0.133675E+09 | 88.82 | 21-APR-22:10 | 24.07 | 13.08 |
May | 0.144422E+10 | 706.60 | 31-MAY-21:00 | 28.30 | 13.66 | 0.148953E+09 | 92.66 | 31-MAY-21:19 | 27.97 | 13.53 |
June | 0.159498E+10 | 945.74 | 15-JUN-21:00 | 33.30 | 13.72 | 0.151432E+09 | 92.66 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.165409E+10 | 938.40 | 03-JUL-18:30 | 34.45 | 19.49 | 0.156126E+09 | 92.66 | 05-JUL-22:10 | 27.70 | 17.66 |
August | 0.158366E+10 | 922.55 | 07-AUG-21:00 | 31.70 | 16.85 | 0.155161E+09 | 92.66 | 21-AUG-23:49 | 25.23 | 16.56 |
September | 0.144143E+10 | 696.14 | 22-SEP-21:00 | 25.00 | 17.90 | 0.146545E+09 | 92.66 | 20-SEP-22:10 | 25.00 | 17.90 |
October | 0.132701E+10 | 670.41 | 05-OCT-10:33 | 27.60 | 18.63 | 0.141518E+09 | 92.29 | 05-OCT-22:10 | 22.98 | 16.25 |
November | 0.107048E+10 | 571.09 | 10-NOV-11:33 | 20.93 | 12.02 | 0.124103E+09 | 83.60 | 10-NOV-22:40 | 15.20 | 8.25 |
December | 0.866897E+09 | 475.77 | 10-DEC-11:33 | 15.93 | 7.48 | 0.119150E+09 | 74.64 | 15-DEC-23:10 | 13.80 | 4.57 |
Annual Sum or Average | 0.151980E+11 | 0.163476E+10 | ||||||||
Minimum of Months | 0.866897E+09 | 475.77 | 13.87 | 7.48 | 0.111027E+09 | 74.64 | 11.33 | 4.57 | ||
Maximum of Months | 0.165409E+10 | 945.74 | 34.45 | 19.49 | 0.156126E+09 | 92.66 | 28.43 | 17.90 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.495284E+11 | 37443.35 | 12-JAN-21:00 | 12.80 | 7.31 | 0.593897E+09 | 381.75 | 03-JAN-22:10 | 12.80 | 7.31 |
February | 0.452728E+11 | 37798.03 | 21-FEB-20:55 | 15.00 | 4.44 | 0.538185E+09 | 381.76 | 06-FEB-22:10 | 15.00 | 4.44 |
March | 0.508247E+11 | 37927.26 | 16-MAR-20:00 | 17.20 | 5.94 | 0.598460E+09 | 381.75 | 15-MAR-21:10 | 17.20 | 5.94 |
April | 0.505519E+11 | 38676.19 | 28-APR-20:00 | 25.00 | 12.84 | 0.582243E+09 | 381.76 | 18-APR-21:10 | 25.00 | 12.84 |
May | 0.533765E+11 | 38976.80 | 30-MAY-20:00 | 28.90 | 14.28 | 0.604100E+09 | 381.80 | 23-MAY-21:10 | 28.90 | 14.28 |
June | 0.526482E+11 | 39337.55 | 15-JUN-20:00 | 33.90 | 14.00 | 0.586581E+09 | 381.87 | 27-JUN-21:10 | 28.62 | 16.18 |
July | 0.541307E+11 | 39327.45 | 03-JUL-20:00 | 28.30 | 19.12 | 0.603933E+09 | 381.81 | 28-JUL-21:10 | 29.03 | 16.95 |
August | 0.540549E+11 | 39209.76 | 04-AUG-20:00 | 33.30 | 17.89 | 0.604791E+09 | 381.90 | 22-AUG-21:10 | 29.22 | 13.60 |
September | 0.517808E+11 | 38930.19 | 20-SEP-20:00 | 25.60 | 15.27 | 0.583350E+09 | 381.92 | 19-SEP-21:10 | 25.60 | 15.27 |
October | 0.520418E+11 | 38704.40 | 05-OCT-20:00 | 23.90 | 16.65 | 0.600127E+09 | 381.85 | 31-OCT-21:10 | 10.60 | 4.71 |
November | 0.488791E+11 | 38028.35 | 09-NOV-21:00 | 20.00 | 11.27 | 0.577627E+09 | 381.83 | 09-NOV-22:10 | 18.53 | 10.92 |
December | 0.492016E+11 | 37207.98 | 15-DEC-21:00 | 14.40 | 4.76 | 0.593079E+09 | 381.80 | 07-DEC-22:10 | 14.40 | 4.76 |
Annual Sum or Average | 0.612291E+12 | 0.706637E+10 | ||||||||
Minimum of Months | 0.452728E+11 | 37207.98 | 12.80 | 4.44 | 0.538185E+09 | 381.75 | 10.60 | 4.44 | ||
Maximum of Months | 0.541307E+11 | 39337.55 | 33.90 | 19.12 | 0.604791E+09 | 381.92 | 29.22 | 16.95 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.179399E+11 | 11422.82 | 01-JAN-11:00 | 12.80 | 8.11 | 0.103609E+11 | 6461.65 | 13-JAN-02:20 | 5.53 | 2.39 |
February | 0.166405E+11 | 11320.41 | 20-FEB-13:00 | 21.10 | 8.39 | 0.946566E+10 | 6462.29 | 22-FEB-22:19 | 14.40 | 4.92 |
March | 0.180920E+11 | 10168.26 | 14-MAR-15:03 | 23.98 | 9.90 | 0.105591E+11 | 6462.47 | 16-MAR-22:10 | 15.27 | 5.99 |
April | 0.190068E+11 | 10916.76 | 19-APR-21:10 | 28.12 | 12.29 | 0.103956E+11 | 6463.24 | 17-APR-01:10 | 28.12 | 12.29 |
May | 0.206891E+11 | 11246.07 | 31-MAY-21:10 | 28.13 | 13.59 | 0.108250E+11 | 6462.68 | 17-MAY-22:10 | 28.13 | 13.59 |
June | 0.217915E+11 | 11815.04 | 15-JUN-21:10 | 32.57 | 13.55 | 0.105737E+11 | 6462.67 | 23-JUN-22:10 | 23.40 | 15.27 |
July | 0.226204E+11 | 11776.41 | 26-JUL-21:10 | 28.62 | 18.19 | 0.108958E+11 | 6462.61 | 19-JUL-22:10 | 28.62 | 18.19 |
August | 0.229128E+11 | 12212.34 | 07-AUG-21:10 | 31.25 | 17.07 | 0.109499E+11 | 6462.67 | 11-AUG-22:10 | 22.80 | 17.38 |
September | 0.227814E+11 | 12103.68 | 19-SEP-15:03 | 33.40 | 16.39 | 0.105969E+11 | 6462.68 | 06-SEP-22:10 | 33.40 | 16.39 |
October | 0.222939E+11 | 12731.71 | 22-OCT-12:00 | 23.90 | 13.84 | 0.108446E+11 | 6462.68 | 05-OCT-22:10 | 23.90 | 13.84 |
November | 0.193011E+11 | 12779.25 | 11-NOV-11:00 | 16.10 | 7.51 | 0.102359E+11 | 6462.44 | 09-NOV-23:10 | 16.10 | 7.51 |
December | 0.174493E+11 | 11064.02 | 16-DEC-13:30 | 14.45 | 3.99 | 0.102365E+11 | 6461.84 | 18-DEC-00:20 | 10.93 | 2.97 |
Annual Sum or Average | 0.241519E+12 | 0.125940E+12 | ||||||||
Minimum of Months | 0.166405E+11 | 10168.26 | 12.80 | 3.99 | 0.946566E+10 | 6461.65 | 5.53 | 2.39 | ||
Maximum of Months | 0.229128E+11 | 12779.25 | 33.40 | 18.19 | 0.109499E+11 | 6463.24 | 33.40 | 18.19 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.588235E+11 | 32099.71 | 12-JAN-22:10 | 10.03 | 5.38 | 0.313053E+11 | 19185.00 | 02-JAN-00:20 | 10.03 | 5.38 |
February | 0.543641E+11 | 33417.88 | 07-FEB-22:10 | 15.10 | 7.63 | 0.284966E+11 | 19185.63 | 22-FEB-22:19 | 14.40 | 4.92 |
March | 0.611814E+11 | 34278.03 | 16-MAR-21:10 | 17.02 | 5.96 | 0.317435E+11 | 19185.86 | 16-MAR-22:10 | 15.27 | 5.99 |
April | 0.652086E+11 | 37771.34 | 21-APR-21:10 | 24.90 | 9.61 | 0.310563E+11 | 19189.55 | 17-APR-01:10 | 24.90 | 9.61 |
May | 0.728615E+11 | 40682.81 | 31-MAY-21:10 | 28.13 | 13.59 | 0.322756E+11 | 19186.11 | 17-MAY-22:10 | 28.13 | 13.59 |
June | 0.762434E+11 | 43099.70 | 15-JUN-21:10 | 32.57 | 13.55 | 0.314474E+11 | 19186.07 | 22-JUN-22:10 | 23.22 | 16.10 |
July | 0.790547E+11 | 42917.62 | 26-JUL-21:10 | 28.62 | 18.19 | 0.324018E+11 | 19186.04 | 19-JUL-22:10 | 28.62 | 18.19 |
August | 0.786481E+11 | 43649.78 | 07-AUG-21:10 | 31.25 | 17.07 | 0.325585E+11 | 19186.10 | 11-AUG-22:10 | 22.80 | 17.38 |
September | 0.751108E+11 | 42002.39 | 21-SEP-21:10 | 26.10 | 17.46 | 0.314878E+11 | 19186.13 | 06-SEP-22:10 | 26.10 | 17.46 |
October | 0.717779E+11 | 41364.96 | 05-OCT-21:10 | 23.22 | 16.17 | 0.323747E+11 | 19186.11 | 05-OCT-22:10 | 22.98 | 16.25 |
November | 0.616858E+11 | 37598.95 | 09-NOV-22:10 | 18.53 | 10.92 | 0.308672E+11 | 19186.06 | 01-NOV-01:10 | 18.53 | 10.92 |
December | 0.576072E+11 | 30285.81 | 15-DEC-22:10 | 14.32 | 4.61 | 0.310823E+11 | 19185.41 | 23-DEC-00:20 | 5.20 | 0.42 |
Annual Sum or Average | 0.812567E+12 | 0.377097E+12 | ||||||||
Minimum of Months | 0.543641E+11 | 30285.81 | 10.03 | 4.61 | 0.284966E+11 | 19185.00 | 5.20 | 0.42 | ||
Maximum of Months | 0.790547E+11 | 43649.78 | 32.57 | 18.19 | 0.325585E+11 | 19189.55 | 28.62 | 18.19 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.297114E+09 | 2992.41 | 10-JAN-16:01 | 16.60 | 5.62 | 96934649.89 | 56.69 | 03-JAN-22:19 | 16.60 | 5.62 |
February | 0.424155E+09 | 3298.91 | 20-FEB-16:01 | 23.12 | 8.59 | 88043124.10 | 56.69 | 06-FEB-22:10 | 23.12 | 8.59 |
March | 0.743347E+09 | 3315.99 | 21-MAR-15:01 | 24.50 | 9.45 | 98095451.73 | 56.69 | 16-MAR-23:10 | 24.50 | 9.45 |
April | 0.152054E+10 | 3410.73 | 15-APR-15:01 | 27.20 | 11.79 | 95537818.01 | 56.69 | 18-APR-21:10 | 22.02 | 14.14 |
May | 0.219080E+10 | 3415.73 | 11-MAY-15:01 | 28.90 | 13.77 | 99036587.00 | 56.69 | 28-MAY-00:30 | 20.85 | 16.76 |
June | 0.264455E+10 | 3328.02 | 14-JUN-08:61 | 27.57 | 12.11 | 96050309.77 | 56.70 | 19-JUN-04:49 | 22.80 | 15.92 |
July | 0.264091E+10 | 3081.72 | 25-JUL-08:61 | 27.07 | 19.24 | 99109497.87 | 56.70 | 11-JUL-21:10 | 27.07 | 19.24 |
August | 0.250165E+10 | 3083.23 | 26-AUG-08:61 | 26.88 | 14.99 | 99171615.70 | 56.70 | 04-AUG-21:30 | 26.88 | 14.99 |
September | 0.232631E+10 | 3172.58 | 24-SEP-18:01 | 20.73 | 10.13 | 95857323.39 | 56.69 | 23-SEP-03:30 | 20.73 | 10.13 |
October | 0.165715E+10 | 3266.24 | 31-OCT-15:01 | 21.60 | 7.74 | 98777034.44 | 56.69 | 02-OCT-04:10 | 21.60 | 7.74 |
November | 0.716790E+09 | 3237.89 | 08-NOV-16:01 | 23.12 | 11.05 | 94709252.24 | 56.69 | 01-NOV-02:39 | 23.12 | 11.05 |
December | 0.201496E+09 | 2997.77 | 23-DEC-16:01 | 16.73 | 6.11 | 96676714.83 | 56.69 | 13-DEC-00:20 | 16.73 | 6.11 |
Annual Sum or Average | 0.178648E+11 | 0.115800E+10 | ||||||||
Minimum of Months | 0.201496E+09 | 2992.41 | 16.60 | 5.62 | 88043124.10 | 56.69 | 16.60 | 5.62 | ||
Maximum of Months | 0.264455E+10 | 3415.73 | 28.90 | 19.24 | 99171615.70 | 56.70 | 27.07 | 19.24 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 72000420.33 | 2913.95 | 30-JAN-16:01 | 15.60 | 6.01 | 95329288.14 | 56.69 | 06-JAN-04:19 | 15.60 | 6.01 |
February | 0.131434E+09 | 3233.15 | 20-FEB-16:01 | 23.12 | 8.59 | 87612722.79 | 63.96 | 22-FEB-22:10 | 14.40 | 4.90 |
March | 0.345635E+09 | 3254.70 | 21-MAR-15:01 | 24.50 | 9.45 | 0.100177E+09 | 69.77 | 16-MAR-21:40 | 24.50 | 9.45 |
April | 0.118756E+10 | 3569.26 | 17-APR-18:01 | 14.13 | 8.88 | 99213245.78 | 75.62 | 28-APR-21:40 | 22.07 | 12.89 |
May | 0.201744E+10 | 3627.50 | 20-MAY-08:51 | 26.70 | 12.19 | 0.102131E+09 | 79.70 | 23-MAY-21:10 | 22.02 | 16.25 |
June | 0.256506E+10 | 3742.47 | 14-JUN-08:11 | 27.93 | 12.20 | 98380796.90 | 79.54 | 23-JUN-21:19 | 23.30 | 15.34 |
July | 0.252696E+10 | 3156.77 | 25-JUL-06:51 | 25.60 | 18.41 | 0.101629E+09 | 76.21 | 21-JUL-21:00 | 25.60 | 18.41 |
August | 0.225382E+10 | 3280.61 | 26-AUG-08:11 | 27.07 | 15.12 | 0.102108E+09 | 80.06 | 11-AUG-21:10 | 27.07 | 15.12 |
September | 0.182857E+10 | 3252.92 | 29-SEP-21:51 | 19.40 | 9.20 | 0.100053E+09 | 79.15 | 13-SEP-21:10 | 19.40 | 9.20 |
October | 0.989825E+09 | 3198.35 | 31-OCT-15:01 | 21.60 | 7.74 | 0.104027E+09 | 80.89 | 05-OCT-21:10 | 21.60 | 7.74 |
November | 0.245240E+09 | 3180.99 | 08-NOV-16:01 | 23.12 | 11.05 | 94727332.08 | 68.71 | 09-NOV-22:40 | 17.43 | 10.49 |
December | 39607712.25 | 2919.26 | 16-DEC-16:01 | 14.72 | 4.08 | 94799110.25 | 56.69 | 22-DEC-04:19 | -2.2 | -4.3 |
Annual Sum or Average | 0.142032E+11 | 0.118019E+10 | ||||||||
Minimum of Months | 39607712.25 | 2913.95 | 14.13 | 4.08 | 87612722.79 | 56.69 | -2.2 | -4.3 | ||
Maximum of Months | 0.256506E+10 | 3742.47 | 27.93 | 18.41 | 0.104027E+09 | 80.89 | 27.07 | 18.41 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.300342E+09 | 533.80 | 12-JAN-14:25 | 18.60 | 9.87 | 0.00 | 0.00 | 01-JAN-00:10 | 18.60 | 9.87 |
February | 0.299319E+09 | 500.10 | 07-FEB-13:40 | 20.20 | 9.50 | 0.00 | 0.00 | 01-FEB-00:10 | 20.20 | 9.50 |
March | 0.281563E+09 | 395.61 | 07-MAR-13:40 | 21.33 | 8.79 | 0.00 | 0.00 | 01-MAR-00:10 | 21.33 | 8.79 |
April | 0.370859E+09 | 370.02 | 03-APR-14:00 | 26.70 | 11.71 | 0.00 | 0.00 | 01-APR-00:10 | 26.70 | 11.71 |
May | 0.442928E+09 | 313.25 | 31-MAY-20:20 | 29.03 | 14.28 | 0.00 | 0.00 | 01-MAY-00:10 | 29.03 | 14.28 |
June | 0.542920E+09 | 359.87 | 15-JUN-17:17 | 36.83 | 15.02 | 0.00 | 0.00 | 01-JUN-00:10 | 36.83 | 15.02 |
July | 0.571720E+09 | 364.04 | 26-JUL-17:20 | 35.20 | 19.91 | 0.00 | 0.00 | 01-JUL-00:10 | 35.20 | 19.91 |
August | 0.597214E+09 | 418.97 | 27-AUG-13:50 | 34.40 | 16.35 | 0.00 | 0.00 | 01-AUG-00:10 | 34.40 | 16.35 |
September | 0.661863E+09 | 526.76 | 19-SEP-13:30 | 33.35 | 16.80 | 0.00 | 0.00 | 01-SEP-00:10 | 33.35 | 16.80 |
October | 0.605939E+09 | 604.76 | 22-OCT-13:15 | 25.97 | 14.61 | 0.00 | 0.00 | 01-OCT-00:10 | 25.97 | 14.61 |
November | 0.442352E+09 | 571.15 | 09-NOV-13:50 | 23.22 | 12.39 | 0.00 | 0.00 | 01-NOV-00:10 | 23.22 | 12.39 |
December | 0.263805E+09 | 462.56 | 16-DEC-13:40 | 14.63 | 4.10 | 0.00 | 0.00 | 01-DEC-00:10 | 14.63 | 4.10 |
Annual Sum or Average | 0.538082E+10 | 0.00 | ||||||||
Minimum of Months | 0.263805E+09 | 313.25 | 14.63 | 4.10 | 0.00 | 0.00 | 14.63 | 4.10 | ||
Maximum of Months | 0.661863E+09 | 604.76 | 36.83 | 19.91 | 0.00 | 0.00 | 36.83 | 19.91 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115052E+09 | 981.85 | 03-JAN-16:01 | 20.10 | 7.84 | 95834951.85 | 56.69 | 03-JAN-22:19 | 12.07 | 5.91 |
February | 0.163771E+09 | 1091.15 | 20-FEB-16:01 | 23.12 | 8.59 | 87386679.90 | 67.44 | 22-FEB-22:10 | 14.40 | 4.90 |
March | 0.276425E+09 | 1134.24 | 22-MAR-15:01 | 23.90 | 8.87 | 98487929.44 | 70.37 | 09-MAR-22:10 | 23.90 | 8.87 |
April | 0.515871E+09 | 1182.82 | 21-APR-18:01 | 29.95 | 11.64 | 97364847.72 | 72.62 | 25-APR-21:49 | 18.22 | 11.64 |
May | 0.760180E+09 | 1228.33 | 20-MAY-08:51 | 26.70 | 12.19 | 0.101037E+09 | 74.58 | 23-MAY-21:10 | 22.02 | 16.25 |
June | 0.930164E+09 | 1251.55 | 14-JUN-08:11 | 27.93 | 12.20 | 97621033.77 | 74.78 | 23-JUN-21:10 | 23.30 | 15.34 |
July | 0.943948E+09 | 1116.57 | 06-JUL-08:61 | 26.38 | 18.59 | 0.100919E+09 | 71.55 | 18-JUL-21:00 | 19.40 | 19.40 |
August | 0.837523E+09 | 1120.88 | 26-AUG-08:11 | 27.07 | 15.12 | 0.101280E+09 | 76.81 | 14-AUG-21:10 | 27.07 | 15.12 |
September | 0.665562E+09 | 1110.44 | 29-SEP-21:51 | 19.40 | 9.20 | 98576783.59 | 73.55 | 13-SEP-21:10 | 19.40 | 9.20 |
October | 0.466689E+09 | 1137.40 | 30-OCT-15:01 | 24.32 | 11.43 | 0.101479E+09 | 74.45 | 05-OCT-21:10 | 24.32 | 11.43 |
November | 0.200456E+09 | 1099.71 | 09-NOV-16:02 | 23.22 | 12.98 | 93837294.87 | 68.26 | 09-NOV-22:49 | 17.07 | 10.34 |
December | 85554762.14 | 945.46 | 16-DEC-09:01 | 8.48 | 2.42 | 95578569.66 | 56.69 | 13-DEC-00:20 | 8.48 | 2.42 |
Annual Sum or Average | 0.596120E+10 | 0.116940E+10 | ||||||||
Minimum of Months | 85554762.14 | 945.46 | 8.48 | 2.42 | 87386679.90 | 56.69 | 8.48 | 2.42 | ||
Maximum of Months | 0.943948E+09 | 1251.55 | 29.95 | 18.59 | 0.101479E+09 | 76.81 | 27.07 | 19.40 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.271604E+09 | 2638.98 | 31-JAN-09:01 | 10.78 | 4.13 | 97216461.05 | 56.69 | 03-JAN-22:19 | 10.78 | 4.13 |
February | 0.474531E+09 | 2893.31 | 20-FEB-16:01 | 23.12 | 8.59 | 88486699.92 | 56.69 | 06-FEB-23:19 | 23.12 | 8.59 |
March | 0.759914E+09 | 2920.93 | 21-MAR-15:01 | 24.50 | 9.45 | 98480049.77 | 56.69 | 16-MAR-22:00 | 24.50 | 9.45 |
April | 0.159229E+10 | 3010.60 | 21-APR-15:01 | 32.02 | 15.38 | 95859016.02 | 56.69 | 18-APR-21:19 | 32.02 | 15.38 |
May | 0.224087E+10 | 3001.59 | 11-MAY-15:01 | 28.90 | 13.77 | 99190238.07 | 56.69 | 23-MAY-00:49 | 22.20 | 15.41 |
June | 0.272189E+10 | 3045.69 | 14-JUN-08:61 | 27.57 | 12.11 | 96031663.46 | 56.69 | 04-JUN-02:39 | 27.57 | 12.11 |
July | 0.271108E+10 | 2780.98 | 12-JUL-08:61 | 25.97 | 18.19 | 99133539.11 | 56.70 | 27-JUL-21:30 | 28.60 | 18.35 |
August | 0.256166E+10 | 2757.89 | 03-AUG-08:61 | 26.28 | 20.18 | 99209439.59 | 56.70 | 03-AUG-21:49 | 27.98 | 18.45 |
September | 0.234096E+10 | 2808.97 | 24-SEP-18:01 | 20.73 | 10.13 | 95943033.22 | 56.69 | 01-SEP-01:49 | 20.73 | 10.13 |
October | 0.155883E+10 | 2865.50 | 31-OCT-15:01 | 21.60 | 7.74 | 98858529.75 | 56.69 | 02-OCT-23:49 | 21.60 | 7.74 |
November | 0.687819E+09 | 2881.83 | 08-NOV-16:01 | 23.12 | 11.05 | 94909645.83 | 56.69 | 09-NOV-22:30 | 17.80 | 10.64 |
December | 0.209998E+09 | 2649.84 | 23-DEC-16:01 | 16.73 | 6.11 | 96959459.78 | 56.69 | 19-DEC-04:19 | 16.73 | 6.11 |
Annual Sum or Average | 0.181314E+11 | 0.116028E+10 | ||||||||
Minimum of Months | 0.209998E+09 | 2638.98 | 10.78 | 4.13 | 88486699.92 | 56.69 | 10.78 | 4.13 | ||
Maximum of Months | 0.272189E+10 | 3045.69 | 32.02 | 20.18 | 99209439.59 | 56.70 | 32.02 | 18.45 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 59466054.70 | 2499.77 | 31-JAN-09:01 | 10.78 | 4.13 | 95157690.12 | 56.69 | 06-JAN-04:19 | 10.78 | 4.13 |
February | 0.183927E+09 | 2834.05 | 20-FEB-16:01 | 23.12 | 8.59 | 87617442.73 | 65.50 | 22-FEB-22:10 | 14.40 | 4.90 |
March | 0.405353E+09 | 2867.37 | 21-MAR-15:01 | 24.50 | 9.45 | 99592448.43 | 67.82 | 15-MAR-21:30 | 24.50 | 9.45 |
April | 0.125194E+10 | 3352.60 | 21-APR-08:51 | 21.70 | 8.90 | 99238009.61 | 74.05 | 28-APR-21:40 | 22.07 | 12.89 |
May | 0.200594E+10 | 3535.28 | 20-MAY-08:51 | 26.70 | 12.19 | 0.103184E+09 | 75.63 | 17-MAY-21:30 | 26.70 | 12.19 |
June | 0.259140E+10 | 3538.68 | 14-JUN-07:52 | 27.20 | 12.01 | 99322706.80 | 78.46 | 23-JUN-21:10 | 23.30 | 15.34 |
July | 0.255324E+10 | 3181.50 | 24-JUL-08:61 | 24.78 | 18.10 | 0.102505E+09 | 74.47 | 21-JUL-21:00 | 24.78 | 18.10 |
August | 0.226618E+10 | 3222.60 | 26-AUG-08:11 | 27.07 | 15.12 | 0.102906E+09 | 80.12 | 11-AUG-21:10 | 27.07 | 15.12 |
September | 0.178636E+10 | 3137.93 | 19-SEP-08:51 | 26.10 | 16.81 | 0.100868E+09 | 77.28 | 06-SEP-21:10 | 26.10 | 16.81 |
October | 0.934857E+09 | 3034.61 | 05-OCT-08:51 | 25.00 | 17.90 | 0.102744E+09 | 78.65 | 05-OCT-21:10 | 23.22 | 16.17 |
November | 0.246397E+09 | 2937.53 | 09-NOV-09:51 | 18.30 | 8.77 | 94345235.78 | 67.68 | 09-NOV-22:40 | 17.43 | 10.49 |
December | 43239235.83 | 2551.11 | 16-DEC-09:01 | 8.48 | 2.42 | 94759760.11 | 56.69 | 21-DEC-05:19 | 1.13 | -2.2 |
Annual Sum or Average | 0.143283E+11 | 0.118224E+10 | ||||||||
Minimum of Months | 43239235.83 | 2499.77 | 8.48 | 2.42 | 87617442.73 | 56.69 | 1.13 | -2.2 | ||
Maximum of Months | 0.259140E+10 | 3538.68 | 27.20 | 18.10 | 0.103184E+09 | 80.12 | 27.07 | 18.10 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.267152E+10 | 1376.85 | 01-JAN-11:33 | 13.87 | 8.54 | 0.125213E+10 | 800.10 | 03-JAN-22:40 | 11.33 | 5.60 |
February | 0.263825E+10 | 1458.29 | 20-FEB-11:33 | 20.37 | 8.19 | 0.116506E+10 | 826.73 | 22-FEB-22:49 | 14.40 | 4.99 |
March | 0.310012E+10 | 1512.79 | 16-MAR-18:09 | 19.82 | 7.14 | 0.133930E+10 | 851.06 | 16-MAR-21:49 | 16.28 | 6.02 |
April | 0.347871E+10 | 1771.84 | 30-APR-10:33 | 24.07 | 13.08 | 0.140686E+10 | 911.31 | 21-APR-21:49 | 24.07 | 13.08 |
May | 0.399205E+10 | 1878.28 | 31-MAY-18:05 | 30.92 | 15.25 | 0.155237E+10 | 951.82 | 31-MAY-21:19 | 27.97 | 13.53 |
June | 0.437730E+10 | 2664.22 | 15-JUN-18:25 | 35.55 | 14.53 | 0.156189E+10 | 951.86 | 27-JUN-22:10 | 27.12 | 17.05 |
July | 0.443018E+10 | 2481.95 | 26-JUL-18:15 | 33.13 | 19.73 | 0.160466E+10 | 951.86 | 05-JUL-22:10 | 33.13 | 19.73 |
August | 0.433285E+10 | 2465.52 | 07-AUG-18:15 | 33.50 | 18.31 | 0.160122E+10 | 951.85 | 11-AUG-22:10 | 22.80 | 17.38 |
September | 0.407781E+10 | 2196.25 | 20-SEP-18:03 | 31.05 | 16.15 | 0.154001E+10 | 951.85 | 06-SEP-22:10 | 31.05 | 16.15 |
October | 0.374940E+10 | 1866.40 | 05-OCT-10:33 | 27.60 | 18.63 | 0.149748E+10 | 951.85 | 05-OCT-22:10 | 22.98 | 16.25 |
November | 0.305734E+10 | 1597.51 | 10-NOV-11:33 | 20.93 | 12.02 | 0.131702E+10 | 885.49 | 01-NOV-00:10 | 20.93 | 12.02 |
December | 0.247272E+10 | 1308.89 | 10-DEC-11:33 | 15.93 | 7.48 | 0.122682E+10 | 754.03 | 15-DEC-23:10 | 13.80 | 4.57 |
Annual Sum or Average | 0.423783E+11 | 0.170648E+11 | ||||||||
Minimum of Months | 0.247272E+10 | 1308.89 | 13.87 | 7.14 | 0.116506E+10 | 754.03 | 11.33 | 4.57 | ||
Maximum of Months | 0.443018E+10 | 2664.22 | 35.55 | 19.73 | 0.160466E+10 | 951.86 | 33.13 | 19.73 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230152E+09 | 3176.36 | 30-JAN-16:01 | 15.60 | 6.01 | 96387671.84 | 56.69 | 03-JAN-22:10 | 15.60 | 6.01 |
February | 0.349047E+09 | 3512.32 | 20-FEB-16:01 | 23.12 | 8.59 | 87658347.29 | 56.69 | 19-FEB-00:20 | 23.12 | 8.59 |
March | 0.645196E+09 | 3527.18 | 21-MAR-15:01 | 24.50 | 9.45 | 97781325.59 | 56.70 | 22-MAR-23:00 | 10.00 | 3.92 |
April | 0.147578E+10 | 3640.81 | 15-APR-15:01 | 27.20 | 11.79 | 95399724.42 | 56.69 | 18-APR-00:00 | 8.30 | 5.23 |
May | 0.219408E+10 | 3647.81 | 17-MAY-15:01 | 29.40 | 13.34 | 98975576.42 | 56.70 | 24-MAY-21:49 | 20.87 | 16.52 |
June | 0.274547E+10 | 3526.08 | 14-JUN-08:61 | 27.57 | 12.11 | 96061606.89 | 56.70 | 23-JUN-23:10 | 23.72 | 14.97 |
July | 0.274383E+10 | 3282.81 | 26-JUL-08:61 | 29.08 | 18.80 | 99099069.37 | 56.70 | 24-JUL-21:10 | 29.08 | 18.80 |
August | 0.256183E+10 | 3249.99 | 07-AUG-08:61 | 28.48 | 17.49 | 99143357.27 | 56.70 | 07-AUG-21:40 | 29.90 | 17.57 |
September | 0.230799E+10 | 3367.68 | 24-SEP-18:01 | 20.73 | 10.13 | 95797115.59 | 56.70 | 15-SEP-22:40 | 20.73 | 10.13 |
October | 0.152046E+10 | 3470.73 | 31-OCT-15:01 | 21.60 | 7.74 | 98571341.66 | 56.70 | 17-OCT-21:49 | 21.60 | 7.74 |
November | 0.581311E+09 | 3440.18 | 08-NOV-16:01 | 23.12 | 11.05 | 94288094.75 | 56.69 | 01-NOV-02:09 | 23.12 | 11.05 |
December | 0.152931E+09 | 3182.89 | 23-DEC-16:01 | 16.73 | 6.11 | 96113345.52 | 56.69 | 29-DEC-04:19 | 1.10 | -1.6 |
Annual Sum or Average | 0.175081E+11 | 0.115528E+10 | ||||||||
Minimum of Months | 0.152931E+09 | 3176.36 | 15.60 | 6.01 | 87658347.29 | 56.69 | 1.10 | -1.6 | ||
Maximum of Months | 0.274547E+10 | 3647.81 | 29.40 | 18.80 | 99143357.27 | 56.70 | 29.90 | 18.80 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 50468190.08 | 3007.63 | 30-JAN-16:01 | 15.60 | 6.01 | 94567606.53 | 56.69 | 24-JAN-04:19 | 15.60 | 6.01 |
February | 92374639.68 | 3433.13 | 20-FEB-16:01 | 23.12 | 8.59 | 87028942.45 | 61.26 | 22-FEB-22:10 | 14.40 | 4.90 |
March | 0.265693E+09 | 3454.61 | 21-MAR-15:01 | 24.50 | 9.45 | 99802772.04 | 69.12 | 16-MAR-21:40 | 24.50 | 9.45 |
April | 0.115732E+10 | 3796.42 | 17-APR-18:01 | 14.13 | 8.88 | 99012586.52 | 75.59 | 28-APR-21:40 | 22.07 | 12.89 |
May | 0.205007E+10 | 3853.52 | 20-MAY-08:51 | 26.70 | 12.19 | 0.101810E+09 | 79.30 | 23-MAY-21:10 | 22.02 | 16.25 |
June | 0.269491E+10 | 3956.55 | 14-JUN-08:11 | 27.93 | 12.20 | 98158361.01 | 79.04 | 23-JUN-21:19 | 23.30 | 15.34 |
July | 0.265714E+10 | 3312.48 | 25-JUL-06:51 | 25.60 | 18.41 | 0.101397E+09 | 75.79 | 21-JUL-21:00 | 25.60 | 18.41 |
August | 0.233972E+10 | 3387.72 | 26-AUG-08:11 | 27.07 | 15.12 | 0.101795E+09 | 79.73 | 11-AUG-21:10 | 27.07 | 15.12 |
September | 0.183491E+10 | 3422.62 | 29-SEP-21:51 | 19.40 | 9.20 | 99565039.94 | 78.53 | 13-SEP-21:19 | 19.40 | 9.20 |
October | 0.864268E+09 | 3388.67 | 31-OCT-15:01 | 21.60 | 7.74 | 0.103623E+09 | 80.47 | 05-OCT-21:10 | 21.60 | 7.74 |
November | 0.155991E+09 | 3348.60 | 07-NOV-16:01 | 21.52 | 10.29 | 94031969.52 | 67.35 | 09-NOV-22:40 | 17.43 | 10.49 |
December | 28419158.11 | 3095.53 | 16-DEC-16:01 | 14.72 | 4.08 | 94066811.85 | 56.69 | 19-DEC-04:19 | -3.9 | -7.3 |
Annual Sum or Average | 0.141913E+11 | 0.117486E+10 | ||||||||
Minimum of Months | 28419158.11 | 3007.63 | 14.13 | 4.08 | 87028942.45 | 56.69 | -3.9 | -7.3 | ||
Maximum of Months | 0.269491E+10 | 3956.55 | 27.93 | 18.41 | 0.103623E+09 | 80.47 | 27.07 | 18.41 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.606289E+09 | 1634.58 | 07-JAN-16:01 | 15.40 | 6.90 | 98100664.68 | 56.69 | 03-JAN-22:19 | 15.40 | 6.90 |
February | 0.607364E+09 | 1787.28 | 20-FEB-16:01 | 23.12 | 8.59 | 88837717.56 | 56.69 | 06-FEB-23:40 | 23.12 | 8.59 |
March | 0.621046E+09 | 1796.74 | 14-MAR-15:01 | 23.98 | 9.90 | 98409682.02 | 56.69 | 06-MAR-22:00 | 23.98 | 9.90 |
April | 0.884092E+09 | 1824.60 | 14-APR-15:01 | 27.80 | 12.33 | 95497998.63 | 56.69 | 24-APR-21:49 | 18.40 | 6.85 |
May | 0.110730E+10 | 1779.97 | 05-MAY-15:01 | 25.10 | 10.78 | 98953513.31 | 56.69 | 27-MAY-23:40 | 21.47 | 16.89 |
June | 0.136426E+10 | 1791.79 | 16-JUN-08:61 | 28.77 | 12.28 | 95959690.18 | 56.69 | 19-JUN-03:00 | 22.80 | 15.92 |
July | 0.142561E+10 | 1661.81 | 11-JUL-08:61 | 27.48 | 17.81 | 99082718.43 | 56.70 | 17-JUL-21:10 | 24.72 | 19.54 |
August | 0.143516E+10 | 1661.26 | 26-AUG-08:61 | 26.88 | 14.99 | 99137597.49 | 56.70 | 09-AUG-21:19 | 26.88 | 14.99 |
September | 0.147075E+10 | 1707.33 | 24-SEP-18:01 | 20.73 | 10.13 | 95832995.10 | 56.70 | 21-SEP-22:10 | 20.73 | 10.13 |
October | 0.127691E+10 | 1774.05 | 31-OCT-15:01 | 21.60 | 7.74 | 98858826.46 | 56.70 | 04-OCT-21:19 | 21.60 | 7.74 |
November | 0.862127E+09 | 1747.97 | 14-NOV-16:01 | 20.92 | 8.21 | 95289997.61 | 56.69 | 01-NOV-01:49 | 20.92 | 8.21 |
December | 0.554017E+09 | 1640.00 | 23-DEC-16:01 | 16.73 | 6.11 | 98114225.62 | 56.69 | 13-DEC-00:20 | 16.73 | 6.11 |
Annual Sum or Average | 0.122149E+11 | 0.116208E+10 | ||||||||
Minimum of Months | 0.554017E+09 | 1634.58 | 15.40 | 6.11 | 88837717.56 | 56.69 | 15.40 | 6.11 | ||
Maximum of Months | 0.147075E+10 | 1824.60 | 28.77 | 17.81 | 99137597.49 | 56.70 | 26.88 | 19.54 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.318050E+11 | 17842.35 | 03-JAN-22:10 | 12.43 | 6.06 | 0.189669E+11 | 11347.77 | 23-JAN-00:20 | 5.00 | 3.64 |
February | 0.298496E+11 | 18954.33 | 07-FEB-23:00 | 15.60 | 8.35 | 0.172303E+11 | 11348.11 | 22-FEB-22:19 | 14.40 | 4.92 |
March | 0.347215E+11 | 19831.44 | 15-MAR-21:53 | 19.40 | 7.29 | 0.192256E+11 | 11348.49 | 16-MAR-22:10 | 15.27 | 5.99 |
April | 0.376971E+11 | 21799.22 | 19-APR-22:00 | 27.20 | 11.76 | 0.186645E+11 | 11349.82 | 17-APR-01:10 | 27.20 | 11.76 |
May | 0.424381E+11 | 22944.48 | 31-MAY-21:20 | 27.97 | 13.53 | 0.193323E+11 | 11356.22 | 31-MAY-21:19 | 27.97 | 13.53 |
June | 0.440618E+11 | 23585.63 | 15-JUN-21:20 | 31.83 | 13.36 | 0.187579E+11 | 11375.81 | 15-JUN-21:19 | 31.83 | 13.36 |
July | 0.452449E+11 | 23341.47 | 26-JUL-21:20 | 28.33 | 18.21 | 0.193067E+11 | 11352.63 | 26-JUL-21:19 | 28.33 | 18.21 |
August | 0.441736E+11 | 23503.22 | 07-AUG-21:20 | 30.80 | 17.26 | 0.193826E+11 | 11363.94 | 07-AUG-21:19 | 30.80 | 17.26 |
September | 0.408387E+11 | 22331.98 | 22-SEP-22:00 | 25.00 | 17.90 | 0.186934E+11 | 11348.98 | 06-SEP-22:10 | 25.00 | 17.90 |
October | 0.383740E+11 | 21798.04 | 05-OCT-21:52 | 22.80 | 16.23 | 0.192495E+11 | 11348.98 | 05-OCT-22:10 | 22.98 | 16.25 |
November | 0.325674E+11 | 19765.54 | 09-NOV-22:10 | 18.53 | 10.92 | 0.184638E+11 | 11348.43 | 09-NOV-23:10 | 16.70 | 10.07 |
December | 0.310427E+11 | 17763.15 | 15-DEC-23:00 | 13.90 | 4.56 | 0.189080E+11 | 11347.71 | 19-DEC-04:19 | -3.9 | -7.3 |
Annual Sum or Average | 0.452815E+12 | 0.226181E+12 | ||||||||
Minimum of Months | 0.298496E+11 | 17763.15 | 12.43 | 4.56 | 0.172303E+11 | 11347.71 | -3.9 | -7.3 | ||
Maximum of Months | 0.452449E+11 | 23585.63 | 31.83 | 18.21 | 0.193826E+11 | 11375.81 | 31.83 | 18.21 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.353721E+11 | 19667.04 | 03-JAN-22:10 | 12.43 | 6.06 | 0.191325E+11 | 11347.81 | 23-JAN-00:20 | 5.00 | 3.64 |
February | 0.330928E+11 | 20638.00 | 06-FEB-22:30 | 18.05 | 6.79 | 0.173485E+11 | 11348.14 | 22-FEB-22:19 | 14.40 | 4.92 |
March | 0.383507E+11 | 21470.14 | 15-MAR-21:53 | 19.40 | 7.29 | 0.193204E+11 | 11348.50 | 16-MAR-22:10 | 15.27 | 5.99 |
April | 0.409302E+11 | 23209.20 | 19-APR-21:20 | 27.93 | 12.19 | 0.186977E+11 | 11350.03 | 17-APR-01:10 | 27.93 | 12.19 |
May | 0.454213E+11 | 24140.16 | 31-MAY-21:20 | 27.97 | 13.53 | 0.193443E+11 | 11363.75 | 31-MAY-21:19 | 27.97 | 13.53 |
June | 0.467573E+11 | 24773.83 | 15-JUN-21:20 | 31.83 | 13.36 | 0.187599E+11 | 11380.25 | 15-JUN-21:19 | 31.83 | 13.36 |
July | 0.480222E+11 | 24519.60 | 26-JUL-21:20 | 28.33 | 18.21 | 0.193089E+11 | 11356.49 | 26-JUL-21:19 | 28.33 | 18.21 |
August | 0.469618E+11 | 24670.49 | 07-AUG-21:20 | 30.80 | 17.26 | 0.193889E+11 | 11366.44 | 07-AUG-21:19 | 30.80 | 17.26 |
September | 0.435621E+11 | 23460.86 | 22-SEP-22:00 | 25.00 | 17.90 | 0.187042E+11 | 11348.99 | 06-SEP-22:10 | 25.00 | 17.90 |
October | 0.414756E+11 | 22944.58 | 05-OCT-21:52 | 22.80 | 16.23 | 0.192869E+11 | 11348.99 | 05-OCT-22:10 | 22.98 | 16.25 |
November | 0.358799E+11 | 21301.02 | 09-NOV-22:10 | 18.53 | 10.92 | 0.185709E+11 | 11348.44 | 09-NOV-23:10 | 16.70 | 10.07 |
December | 0.345850E+11 | 19652.19 | 15-DEC-23:00 | 13.90 | 4.56 | 0.190960E+11 | 11347.71 | 19-DEC-04:19 | -3.9 | -7.3 |
Annual Sum or Average | 0.490411E+12 | 0.226959E+12 | ||||||||
Minimum of Months | 0.330928E+11 | 19652.19 | 12.43 | 4.56 | 0.173485E+11 | 11347.71 | -3.9 | -7.3 | ||
Maximum of Months | 0.480222E+11 | 24773.83 | 31.83 | 18.21 | 0.193889E+11 | 11380.25 | 31.83 | 18.21 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.479142E+11 | 25952.94 | 01-JAN-11:50 | 14.13 | 8.64 | 0.188166E+11 | 11319.54 | 28-JAN-18:19 | 11.50 | 4.01 |
February | 0.442897E+11 | 27023.04 | 20-FEB-11:50 | 20.73 | 8.30 | 0.170022E+11 | 11319.55 | 04-FEB-18:19 | 20.73 | 8.30 |
March | 0.501579E+11 | 27214.79 | 19-MAR-10:33 | 18.67 | 7.01 | 0.188383E+11 | 11319.57 | 25-MAR-17:19 | 21.10 | 8.62 |
April | 0.513475E+11 | 28924.60 | 30-APR-10:50 | 24.53 | 12.98 | 0.182449E+11 | 11319.64 | 15-APR-17:19 | 24.53 | 12.98 |
May | 0.550712E+11 | 29068.83 | 21-MAY-10:33 | 29.47 | 14.38 | 0.188641E+11 | 11319.65 | 06-MAY-17:19 | 29.47 | 14.38 |
June | 0.551493E+11 | 29634.37 | 18-JUN-10:37 | 32.43 | 16.35 | 0.182641E+11 | 11319.80 | 10-JUN-17:19 | 32.43 | 16.35 |
July | 0.568830E+11 | 29786.80 | 02-JUL-10:37 | 32.23 | 20.13 | 0.188664E+11 | 11319.66 | 15-JUL-17:19 | 32.20 | 17.96 |
August | 0.562782E+11 | 29717.66 | 06-AUG-10:33 | 31.67 | 18.03 | 0.188723E+11 | 11319.64 | 12-AUG-17:19 | 33.70 | 18.99 |
September | 0.536289E+11 | 29277.16 | 17-SEP-10:50 | 30.03 | 15.56 | 0.182552E+11 | 11319.79 | 23-SEP-17:19 | 17.80 | 17.32 |
October | 0.525674E+11 | 28753.75 | 05-OCT-10:33 | 27.60 | 18.63 | 0.188501E+11 | 11319.69 | 28-OCT-17:19 | 22.23 | 13.64 |
November | 0.477754E+11 | 26850.21 | 10-NOV-11:50 | 21.02 | 12.06 | 0.182175E+11 | 11319.75 | 25-NOV-18:19 | 7.93 | 3.72 |
December | 0.474495E+11 | 25931.81 | 10-DEC-11:50 | 16.32 | 7.64 | 0.188114E+11 | 11319.55 | 30-DEC-18:19 | 7.97 | 2.46 |
Annual Sum or Average | 0.618512E+12 | 0.221903E+12 | ||||||||
Minimum of Months | 0.442897E+11 | 25931.81 | 14.13 | 7.01 | 0.170022E+11 | 11319.54 | 7.93 | 2.46 | ||
Maximum of Months | 0.568830E+11 | 29786.80 | 32.43 | 20.13 | 0.188723E+11 | 11319.80 | 33.70 | 18.99 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.530572E+10 | 3191.43 | 01-JAN-11:33 | 13.87 | 8.54 | 0.129325E+10 | 817.77 | 12-JAN-22:30 | 8.90 | 4.67 |
February | 0.553706E+10 | 3515.70 | 20-FEB-11:33 | 20.37 | 8.19 | 0.119736E+10 | 852.35 | 22-FEB-22:40 | 14.40 | 4.97 |
March | 0.678797E+10 | 3539.27 | 16-MAR-17:12 | 20.73 | 7.71 | 0.136903E+10 | 886.97 | 16-MAR-21:40 | 16.47 | 6.01 |
April | 0.808778E+10 | 4302.16 | 30-APR-10:33 | 24.07 | 13.08 | 0.146691E+10 | 984.05 | 21-APR-21:40 | 24.07 | 13.08 |
May | 0.953969E+10 | 5350.82 | 30-MAY-15:02 | 34.32 | 17.72 | 0.163483E+10 | 1007.39 | 31-MAY-00:20 | 27.73 | 13.23 |
June | 0.110406E+11 | 6205.02 | 17-JUN-17:13 | 36.10 | 16.68 | 0.164906E+10 | 1007.44 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.113311E+11 | 6630.49 | 03-JUL-12:50 | 36.52 | 18.58 | 0.169672E+10 | 1007.42 | 05-JUL-22:10 | 27.70 | 17.66 |
August | 0.108648E+11 | 6504.56 | 07-AUG-15:03 | 35.37 | 18.63 | 0.168973E+10 | 1007.44 | 22-AUG-00:10 | 24.22 | 16.48 |
September | 0.984792E+10 | 5989.78 | 21-SEP-14:10 | 31.78 | 18.05 | 0.160294E+10 | 1007.41 | 20-SEP-22:10 | 31.78 | 18.05 |
October | 0.858900E+10 | 5501.68 | 05-OCT-15:03 | 30.68 | 17.34 | 0.153595E+10 | 1007.40 | 05-OCT-22:10 | 22.98 | 16.25 |
November | 0.640925E+10 | 3821.37 | 10-NOV-11:33 | 20.93 | 12.02 | 0.132029E+10 | 905.61 | 09-NOV-22:40 | 20.93 | 12.02 |
December | 0.460322E+10 | 3115.68 | 16-DEC-11:33 | 12.77 | 3.51 | 0.128155E+10 | 793.32 | 15-DEC-22:40 | 12.77 | 3.51 |
Annual Sum or Average | 0.979441E+11 | 0.177376E+11 | ||||||||
Minimum of Months | 0.460322E+10 | 3115.68 | 12.77 | 3.51 | 0.119736E+10 | 793.32 | 8.90 | 3.51 | ||
Maximum of Months | 0.113311E+11 | 6630.49 | 36.52 | 18.63 | 0.169672E+10 | 1007.44 | 31.78 | 18.05 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 689160.53 | 155.32 | 27-JAN-07:30 | -4.2 |
February | 291131.79 | 86.90 | 02-FEB-07:10 | -4.0 |
March | 90568.42 | 59.42 | 02-MAR-07:10 | -1.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 470292.00 | 88.46 | 28-NOV-05:00 | -0.6 |
December | 11941293.66 | 600.44 | 27-DEC-07:30 | -4.2 |
Annual Sum or Average | 13482446.40 | |||
Minimum of Months | 0.00 | 0.00 | -4.2 | |
Maximum of Months | 11941293.66 | 600.44 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201805E+09 | 2014.83 | 27-JAN-09:01 | -1.2 |
February | 0.112943E+09 | 2003.13 | 02-FEB-09:01 | 1.38 |
March | 45265416.09 | 2015.33 | 02-MAR-09:01 | 0.47 |
April | 2406637.10 | 955.41 | 01-APR-08:03 | 16.47 |
May | 1413862.65 | 980.21 | 26-MAY-08:04 | 20.37 |
June | 879284.60 | 832.75 | 28-JUN-08:04 | 19.18 |
July | 955861.08 | 856.25 | 19-JUL-08:04 | 20.78 |
August | 1323172.70 | 878.71 | 30-AUG-08:04 | 21.47 |
September | 1479250.69 | 886.38 | 26-SEP-08:04 | 20.78 |
October | 2197365.96 | 931.36 | 06-OCT-08:04 | 12.30 |
November | 82825426.15 | 2003.99 | 28-NOV-09:01 | 4.18 |
December | 0.299865E+09 | 2049.07 | 27-DEC-09:01 | -0.7 |
Annual Sum or Average | 0.753360E+09 | |||
Minimum of Months | 879284.60 | 832.75 | -1.2 | |
Maximum of Months | 0.299865E+09 | 2049.07 | 21.47 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.405774E+09 | 2073.59 | 27-JAN-09:01 | -1.2 |
February | 0.224886E+09 | 2055.18 | 02-FEB-09:01 | 1.38 |
March | 77232955.21 | 2034.77 | 02-MAR-09:01 | 0.47 |
April | 3191479.85 | 1097.52 | 02-APR-08:53 | 22.00 |
May | 1090894.55 | 1232.66 | 08-MAY-08:53 | 24.40 |
June | 513450.41 | 999.43 | 11-JUN-08:34 | 25.53 |
July | 336829.59 | 649.59 | 29-JUL-06:54 | 25.00 |
August | 665619.71 | 850.79 | 19-AUG-08:54 | 24.40 |
September | 878196.40 | 834.21 | 27-SEP-08:53 | 21.10 |
October | 2275952.28 | 1030.32 | 22-OCT-08:53 | 19.40 |
November | 0.151749E+09 | 2020.29 | 28-NOV-09:01 | 4.18 |
December | 0.568999E+09 | 2074.83 | 27-DEC-09:01 | -0.7 |
Annual Sum or Average | 0.143759E+10 | |||
Minimum of Months | 336829.59 | 649.59 | -1.2 | |
Maximum of Months | 0.568999E+09 | 2074.83 | 25.53 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14188532.50 | 608.45 | 27-JAN-09:01 | -1.2 |
February | 9722009.67 | 580.16 | 02-FEB-16:02 | 10.60 |
March | 2628810.91 | 422.88 | 12-MAR-15:04 | 18.90 |
April | 538467.22 | 415.18 | 11-APR-15:04 | 16.78 |
May | 294350.67 | 288.46 | 16-MAY-08:55 | 24.40 |
June | 56491.20 | 146.33 | 13-JUN-08:35 | 26.87 |
July | 22052.46 | 112.77 | 25-JUL-08:06 | 27.07 |
August | 115530.67 | 129.19 | 17-AUG-08:56 | 19.40 |
September | 197430.02 | 234.13 | 28-SEP-15:06 | 28.98 |
October | 378222.01 | 385.43 | 20-OCT-08:53 | 18.30 |
November | 3425109.62 | 464.39 | 30-NOV-16:03 | 17.33 |
December | 32637196.93 | 607.34 | 27-DEC-09:01 | -0.7 |
Annual Sum or Average | 64204203.89 | |||
Minimum of Months | 22052.46 | 112.77 | -1.2 | |
Maximum of Months | 32637196.93 | 608.45 | 28.98 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.221276E+09 | 1907.42 | 14-JAN-16:01 | 7.88 |
February | 0.108718E+09 | 1008.79 | 10-FEB-16:04 | 16.60 |
March | 49838172.82 | 1709.58 | 02-MAR-09:01 | 0.47 |
April | 2090718.67 | 959.12 | 11-APR-15:04 | 16.78 |
May | 156054.75 | 586.39 | 01-MAY-18:04 | 19.72 |
June | 56894.54 | 568.95 | 29-JUN-08:05 | 18.58 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 305745.86 | 885.70 | 16-AUG-08:04 | 20.60 |
September | 191459.30 | 582.54 | 24-SEP-18:04 | 20.73 |
October | 1111354.38 | 799.77 | 07-OCT-15:04 | 17.88 |
November | 93999418.30 | 1941.13 | 27-NOV-09:01 | 3.98 |
December | 0.310094E+09 | 1989.89 | 26-DEC-16:01 | 2.12 |
Annual Sum or Average | 0.787838E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.47 | |
Maximum of Months | 0.310094E+09 | 1989.89 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.420847E+09 | 1919.72 | 26-JAN-16:01 | 7.20 |
February | 0.201457E+09 | 1877.98 | 01-FEB-16:01 | 9.90 |
March | 85485032.07 | 1951.01 | 02-MAR-09:01 | 0.47 |
April | 3056643.39 | 1028.54 | 11-APR-15:04 | 16.78 |
May | 383693.81 | 758.07 | 04-MAY-21:54 | 20.60 |
June | 31640.98 | 474.61 | 22-JUN-21:54 | 23.30 |
July | 57706.93 | 280.18 | 19-JUL-08:55 | 21.70 |
August | 262359.87 | 745.04 | 17-AUG-21:54 | 22.80 |
September | 230016.14 | 614.52 | 24-SEP-21:34 | 15.00 |
October | 2069436.41 | 827.06 | 07-OCT-15:04 | 17.88 |
November | 0.166387E+09 | 1945.94 | 27-NOV-09:01 | 3.98 |
December | 0.561213E+09 | 1994.75 | 26-DEC-16:01 | 2.12 |
Annual Sum or Average | 0.144148E+10 | |||
Minimum of Months | 31640.98 | 280.18 | 0.47 | |
Maximum of Months | 0.561213E+09 | 1994.75 | 23.30 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 1002503.31 | 204.48 | 27-DEC-07:30 | -4.2 |
Annual Sum or Average | 1002503.31 | |||
Minimum of Months | 0.00 | 0.00 | -4.2 | |
Maximum of Months | 1002503.31 | 204.48 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.456876E+09 | 2486.80 | 27-JAN-09:01 | -1.2 |
February | 0.283919E+09 | 2473.98 | 02-FEB-09:01 | 1.38 |
March | 0.153597E+09 | 2480.90 | 02-MAR-09:01 | 0.47 |
April | 17698552.11 | 1941.82 | 11-APR-08:61 | 6.88 |
May | 1611340.48 | 939.79 | 06-MAY-08:03 | 17.48 |
June | 944027.08 | 768.07 | 30-JUN-08:04 | 22.38 |
July | 1099008.08 | 837.80 | 05-JUL-08:04 | 22.57 |
August | 1384624.62 | 838.76 | 31-AUG-08:04 | 20.87 |
September | 1669272.23 | 836.10 | 16-SEP-08:04 | 22.07 |
October | 4254371.61 | 887.62 | 07-OCT-18:04 | 17.62 |
November | 0.228168E+09 | 2465.46 | 28-NOV-09:01 | 4.18 |
December | 0.605883E+09 | 2506.95 | 27-DEC-09:01 | -0.7 |
Annual Sum or Average | 0.175710E+10 | |||
Minimum of Months | 944027.08 | 768.07 | -1.2 | |
Maximum of Months | 0.605883E+09 | 2506.95 | 22.57 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.774587E+09 | 2524.64 | 27-JAN-09:01 | -1.2 |
February | 0.472456E+09 | 2506.93 | 02-FEB-09:01 | 1.38 |
March | 0.216544E+09 | 2497.20 | 02-MAR-09:01 | 0.47 |
April | 18798334.38 | 2129.33 | 11-APR-08:61 | 6.88 |
May | 1423013.07 | 1074.21 | 05-MAY-21:54 | 21.70 |
June | 679197.03 | 952.93 | 14-JUN-08:14 | 27.93 |
July | 320395.41 | 683.81 | 31-JUL-08:34 | 26.27 |
August | 850067.76 | 888.05 | 26-AUG-08:14 | 27.07 |
September | 1094574.87 | 1126.89 | 12-SEP-08:53 | 24.40 |
October | 6742442.83 | 929.51 | 23-OCT-08:03 | 16.05 |
November | 0.379496E+09 | 2475.90 | 28-NOV-09:01 | 4.18 |
December | 0.991532E+09 | 2530.37 | 27-DEC-09:01 | -0.7 |
Annual Sum or Average | 0.286452E+10 | |||
Minimum of Months | 320395.41 | 683.81 | -1.2 | |
Maximum of Months | 0.991532E+09 | 2530.37 | 27.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 50391487.72 | 1238.29 | 15-JAN-16:01 | 10.00 |
February | 31521168.16 | 576.66 | 25-FEB-16:04 | 14.40 |
March | 21050285.21 | 1077.42 | 02-MAR-09:01 | 0.47 |
April | 2257004.47 | 636.51 | 11-APR-15:04 | 16.78 |
May | 847699.17 | 482.58 | 15-MAY-08:04 | 23.40 |
June | 601572.73 | 474.89 | 13-JUN-08:04 | 25.47 |
July | 412991.83 | 381.79 | 11-JUL-08:04 | 27.48 |
August | 454837.32 | 394.00 | 16-AUG-18:04 | 18.98 |
September | 66736.16 | 175.95 | 27-SEP-08:05 | 19.27 |
October | 396635.35 | 403.18 | 07-OCT-18:04 | 17.62 |
November | 28531022.05 | 1263.00 | 27-NOV-09:01 | 3.98 |
December | 82171900.32 | 1279.79 | 26-DEC-09:01 | -0.5 |
Annual Sum or Average | 0.218703E+09 | |||
Minimum of Months | 66736.16 | 175.95 | -0.5 | |
Maximum of Months | 82171900.32 | 1279.79 | 27.48 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5569018.62 | 645.26 | 27-JAN-07:30 | -4.2 |
February | 6998729.01 | 784.28 | 03-FEB-07:10 | -5.1 |
March | 2167287.36 | 422.38 | 02-MAR-07:05 | -1.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 15420.41 | 31.22 | 28-NOV-07:10 | 0.87 |
December | 35983196.98 | 1215.75 | 27-DEC-07:30 | -4.2 |
Annual Sum or Average | 50733652.39 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 35983196.98 | 1215.75 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.866285E+10 | 8344.11 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.782177E+10 | 8344.11 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.868956E+10 | 8344.11 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.836914E+10 | 8344.11 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.867788E+10 | 8344.11 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.840753E+10 | 8344.11 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.863949E+10 | 8344.11 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.869290E+10 | 8344.11 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.837248E+10 | 8344.11 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.865952E+10 | 8344.11 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.840085E+10 | 8344.11 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.863949E+10 | 8344.11 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.102033E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.782177E+10 | 8344.11 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.869290E+10 | 8344.11 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.478695E+09 | 461.08 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.432218E+09 | 461.08 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.480171E+09 | 461.08 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.462465E+09 | 461.08 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.479525E+09 | 461.08 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.464586E+09 | 461.08 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.477404E+09 | 461.08 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.480355E+09 | 461.08 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.462650E+09 | 461.08 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.478511E+09 | 461.08 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.464217E+09 | 461.08 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.477404E+09 | 461.08 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.563820E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.432218E+09 | 461.08 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.480355E+09 | 461.08 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.554331E+09 | 533.93 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.500510E+09 | 533.93 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.556040E+09 | 533.93 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.535537E+09 | 533.93 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.555292E+09 | 533.93 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.537993E+09 | 533.93 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.552836E+09 | 533.93 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.556253E+09 | 533.93 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.535750E+09 | 533.93 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.554117E+09 | 533.93 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.537566E+09 | 533.93 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.552836E+09 | 533.93 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.652906E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.500510E+09 | 533.93 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.556253E+09 | 533.93 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.639281E+09 | 615.76 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.577212E+09 | 615.76 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.641251E+09 | 615.76 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.617606E+09 | 615.76 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.640389E+09 | 615.76 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.620439E+09 | 615.76 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.637557E+09 | 615.76 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.641498E+09 | 615.76 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.617853E+09 | 615.76 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.639035E+09 | 615.76 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.619946E+09 | 615.76 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.637557E+09 | 615.76 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.752962E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.577212E+09 | 615.76 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.641498E+09 | 615.76 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142601E+09 | 137.35 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.128756E+09 | 137.35 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.143041E+09 | 137.35 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.137766E+09 | 137.35 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.142848E+09 | 137.35 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.138398E+09 | 137.35 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.142217E+09 | 137.35 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.143096E+09 | 137.35 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.137821E+09 | 137.35 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.142546E+09 | 137.35 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.138288E+09 | 137.35 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.142217E+09 | 137.35 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.167960E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.128756E+09 | 137.35 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.143096E+09 | 137.35 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.374392E+09 | 360.62 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.338042E+09 | 360.62 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.375546E+09 | 360.62 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.361698E+09 | 360.62 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.375041E+09 | 360.62 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.363357E+09 | 360.62 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.373382E+09 | 360.62 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.375690E+09 | 360.62 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.361842E+09 | 360.62 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.374247E+09 | 360.62 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.363068E+09 | 360.62 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.373382E+09 | 360.62 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.440969E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.338042E+09 | 360.62 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.375690E+09 | 360.62 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.109899E+10 | 1416.11 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.956126E+09 | 1416.11 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.101236E+10 | 1416.11 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.916829E+09 | 1416.11 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.920218E+09 | 1416.11 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.860916E+09 | 1416.11 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.888240E+09 | 1416.11 | 03-JUL-19:19 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.949865E+09 | 1416.11 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.950663E+09 | 1416.11 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.106045E+10 | 1416.11 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.102881E+10 | 1416.11 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.109151E+10 | 1416.11 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.117350E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.860916E+09 | 1416.11 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.109899E+10 | 1416.11 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.950725E+10 | 9580.84 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.854473E+10 | 9580.84 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.945028E+10 | 9580.84 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.903935E+10 | 9580.84 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.933954E+10 | 9580.84 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.902689E+10 | 9580.84 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.928656E+10 | 9580.84 | 03-JUL-19:19 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.939004E+10 | 9580.84 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.908589E+10 | 9580.84 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.946150E+10 | 9580.84 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.917420E+10 | 9580.84 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.947171E+10 | 9580.84 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.110778E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.854473E+10 | 9580.84 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.950725E+10 | 9580.84 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118113E+09 | 106.87 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.106667E+09 | 106.87 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.117174E+09 | 106.87 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.114438E+09 | 106.87 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.117643E+09 | 106.87 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113531E+09 | 106.87 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.118566E+09 | 106.87 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.117174E+09 | 106.87 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.114469E+09 | 106.87 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.118097E+09 | 106.87 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113984E+09 | 106.87 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.118582E+09 | 106.87 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.138844E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.106667E+09 | 106.87 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.118582E+09 | 106.87 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118099E+09 | 106.85 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.106655E+09 | 106.85 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.117160E+09 | 106.85 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.114425E+09 | 106.85 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.117629E+09 | 106.85 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113517E+09 | 106.85 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.118553E+09 | 106.85 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.117160E+09 | 106.85 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.114456E+09 | 106.85 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.118083E+09 | 106.85 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113971E+09 | 106.85 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.118568E+09 | 106.85 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.138828E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.106655E+09 | 106.85 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.118568E+09 | 106.85 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 74229181.22 | 67.16 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 67036196.95 | 67.16 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 73639243.64 | 67.16 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 71920171.51 | 67.16 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 73934212.43 | 67.16 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 71349576.37 | 67.16 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 74514478.79 | 67.16 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 73639243.64 | 67.16 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 71939513.95 | 67.16 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 74219510.00 | 67.16 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 71634873.94 | 67.16 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 74524150.01 | 67.16 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.872580E+09 | 0.300992E+10 | ||||
Minimum of Months | 67036196.95 | 67.16 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 74524150.01 | 67.16 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 74249479.06 | 67.18 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 67054527.88 | 67.18 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 73659380.16 | 67.18 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 71939837.95 | 67.18 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 73954429.61 | 67.18 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 71369086.78 | 67.18 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 74534854.64 | 67.18 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 73659380.16 | 67.18 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 71959185.68 | 67.18 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 74239805.19 | 67.18 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 71654462.37 | 67.18 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 74544528.51 | 67.18 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.872819E+09 | 0.301074E+10 | ||||
Minimum of Months | 67054527.88 | 67.18 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 74544528.51 | 67.18 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118113E+09 | 106.87 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.106667E+09 | 106.87 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.117174E+09 | 106.87 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.114438E+09 | 106.87 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.117643E+09 | 106.87 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113531E+09 | 106.87 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.118566E+09 | 106.87 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.117174E+09 | 106.87 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.114469E+09 | 106.87 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.118097E+09 | 106.87 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113984E+09 | 106.87 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.118582E+09 | 106.87 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.138844E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.106667E+09 | 106.87 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.118582E+09 | 106.87 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118099E+09 | 106.85 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.106655E+09 | 106.85 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.117160E+09 | 106.85 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.114425E+09 | 106.85 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.117629E+09 | 106.85 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113517E+09 | 106.85 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.118553E+09 | 106.85 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.117160E+09 | 106.85 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.114456E+09 | 106.85 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.118083E+09 | 106.85 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113971E+09 | 106.85 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.118568E+09 | 106.85 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.138828E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.106655E+09 | 106.85 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.118568E+09 | 106.85 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.108388E+10 | 1044.00 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.978647E+09 | 1044.00 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.108722E+10 | 1044.00 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.104713E+10 | 1044.00 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.108576E+10 | 1044.00 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.105194E+10 | 1044.00 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.108096E+10 | 1044.00 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.108764E+10 | 1044.00 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.104755E+10 | 1044.00 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.108346E+10 | 1044.00 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.105110E+10 | 1044.00 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.108096E+10 | 1044.00 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.127663E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.978647E+09 | 1044.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108764E+10 | 1044.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118113E+09 | 106.87 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.106667E+09 | 106.87 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.117174E+09 | 106.87 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.114438E+09 | 106.87 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.117643E+09 | 106.87 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113531E+09 | 106.87 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.118566E+09 | 106.87 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.117174E+09 | 106.87 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.114469E+09 | 106.87 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.118097E+09 | 106.87 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113984E+09 | 106.87 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.118582E+09 | 106.87 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.138844E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.106667E+09 | 106.87 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.118582E+09 | 106.87 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118099E+09 | 106.85 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.106655E+09 | 106.85 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.117160E+09 | 106.85 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.114425E+09 | 106.85 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.117629E+09 | 106.85 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113517E+09 | 106.85 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.118553E+09 | 106.85 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.117160E+09 | 106.85 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.114456E+09 | 106.85 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.118083E+09 | 106.85 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113971E+09 | 106.85 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.118568E+09 | 106.85 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.138828E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.106655E+09 | 106.85 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.118568E+09 | 106.85 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 74249479.06 | 67.18 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 67054527.88 | 67.18 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 73659380.16 | 67.18 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 71939837.95 | 67.18 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 73954429.61 | 67.18 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 71369086.78 | 67.18 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 74534854.64 | 67.18 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 73659380.16 | 67.18 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 71959185.68 | 67.18 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 74239805.19 | 67.18 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 71654462.37 | 67.18 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 74544528.51 | 67.18 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.872819E+09 | 0.301074E+10 | ||||
Minimum of Months | 67054527.88 | 67.18 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 74544528.51 | 67.18 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.231292E+10 | 2486.81 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.204526E+10 | 2486.81 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.221543E+10 | 2486.81 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.204595E+10 | 2486.81 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.207140E+10 | 2486.81 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.197312E+10 | 2486.81 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.203053E+10 | 2486.81 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.211526E+10 | 2486.81 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.210811E+10 | 2486.81 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.225963E+10 | 2486.81 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.221189E+10 | 2486.81 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.229779E+10 | 2486.81 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.256873E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.197312E+10 | 2486.81 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.231292E+10 | 2486.81 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.231292E+10 | 2486.81 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.204526E+10 | 2486.81 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.221543E+10 | 2486.81 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.204595E+10 | 2486.81 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.207140E+10 | 2486.81 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.197312E+10 | 2486.81 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.203053E+10 | 2486.81 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.211526E+10 | 2486.81 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.210811E+10 | 2486.81 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.225963E+10 | 2486.81 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.221189E+10 | 2486.81 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.229779E+10 | 2486.81 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.256873E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.197312E+10 | 2486.81 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.231292E+10 | 2486.81 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101925E+10 | 981.75 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.920291E+09 | 981.75 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.102239E+10 | 981.75 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.984694E+09 | 981.75 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.102102E+10 | 981.75 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.989210E+09 | 981.75 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.101650E+10 | 981.75 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.102279E+10 | 981.75 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.985086E+09 | 981.75 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.101886E+10 | 981.75 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.988424E+09 | 981.75 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.101650E+10 | 981.75 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.120050E+11 | 0.424019E+12 | ||||
Minimum of Months | 0.920291E+09 | 981.75 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.102279E+10 | 981.75 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.114712E+10 | 1104.91 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.103575E+10 | 1104.91 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.115066E+10 | 1104.91 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.110823E+10 | 1104.91 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.114911E+10 | 1104.91 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.111331E+10 | 1104.91 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.114403E+10 | 1104.91 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.115110E+10 | 1104.91 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.110867E+10 | 1104.91 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.114668E+10 | 1104.91 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.111243E+10 | 1104.91 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.114403E+10 | 1104.91 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.135111E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.103575E+10 | 1104.91 | 0.00 | 0.00 | |
Maximum of Months | 0.115110E+10 | 1104.91 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.866285E+10 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.782177E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.868956E+10 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.836914E+10 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.867788E+10 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.840753E+10 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.863949E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.869290E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.837248E+10 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.865952E+10 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.840085E+10 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.863949E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.102033E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.782177E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.869290E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.478695E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100364E+09 |
February | 0.179968E+10 | 0.432218E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77255655.60 |
March | 0.199990E+10 | 0.480171E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64638.26 | 68691040.54 |
April | 0.192973E+10 | 0.462465E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5733223.53 | 30223596.34 |
May | 0.199475E+10 | 0.479525E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15685406.31 | 12103624.98 |
June | 0.193394E+10 | 0.464586E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30147947.04 | 3507191.62 |
July | 0.199054E+10 | 0.477404E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27785648.86 | 2195199.27 |
August | 0.199896E+10 | 0.480355E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22334121.03 | 4909335.52 |
September | 0.192879E+10 | 0.462650E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12237740.71 | 14519362.72 |
October | 0.199148E+10 | 0.478511E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2917998.16 | 37393656.50 |
November | 0.192552E+10 | 0.464217E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78715044.37 |
December | 0.199054E+10 | 0.477404E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110163E+09 |
Annual Sum or Average | 0.234744E+11 | 0.563820E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116907E+09 | 0.540040E+09 |
Minimum of Months | 0.179968E+10 | 0.432218E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2195199.27 |
Maximum of Months | 0.199990E+10 | 0.480355E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30147947.04 | 0.110163E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.554331E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40883426.37 |
February | 0.208403E+10 | 0.500510E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1079.25 | 31782396.87 |
March | 0.231589E+10 | 0.556040E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75991.55 | 28998784.81 |
April | 0.223463E+10 | 0.535537E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2431104.75 | 13690086.38 |
May | 0.230993E+10 | 0.555292E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6097077.58 | 5917105.43 |
June | 0.223950E+10 | 0.537993E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11724420.89 | 1819309.25 |
July | 0.230505E+10 | 0.552836E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10757760.78 | 1255510.26 |
August | 0.231480E+10 | 0.556253E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8760377.73 | 2532336.25 |
September | 0.223354E+10 | 0.535750E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4998834.33 | 6429502.19 |
October | 0.230614E+10 | 0.554117E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1276988.19 | 15895444.77 |
November | 0.222975E+10 | 0.537566E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3118.09 | 32391983.83 |
December | 0.230505E+10 | 0.552836E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44646045.04 |
Annual Sum or Average | 0.271834E+11 | 0.652906E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46126753.15 | 0.226242E+09 |
Minimum of Months | 0.208403E+10 | 0.500510E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1255510.26 |
Maximum of Months | 0.231589E+10 | 0.556253E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11724420.89 | 44646045.04 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.639281E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87582669.99 |
February | 0.440737E+09 | 0.577212E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 118686.43 | 67495354.46 |
March | 0.489771E+09 | 0.641251E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 549353.05 | 61489415.26 |
April | 0.472586E+09 | 0.617606E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6899102.86 | 28893635.39 |
May | 0.488511E+09 | 0.640389E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14796699.74 | 12900724.79 |
June | 0.473617E+09 | 0.620439E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27337676.88 | 4197620.07 |
July | 0.487480E+09 | 0.637557E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25039448.25 | 2883780.80 |
August | 0.489542E+09 | 0.641498E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20616408.97 | 5735784.66 |
September | 0.472357E+09 | 0.617853E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12325165.72 | 14388022.93 |
October | 0.487709E+09 | 0.639035E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3689271.33 | 33978294.24 |
November | 0.471555E+09 | 0.619946E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81854.86 | 69208846.04 |
December | 0.487480E+09 | 0.637557E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96738318.32 |
Annual Sum or Average | 0.574883E+10 | 0.752962E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111454E+09 | 0.485492E+09 |
Minimum of Months | 0.440737E+09 | 0.577212E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2883780.80 |
Maximum of Months | 0.489771E+09 | 0.641498E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27337676.88 | 96738318.32 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.142601E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50017309.18 |
February | 0.339028E+09 | 0.128756E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63857.51 | 38473435.26 |
March | 0.376747E+09 | 0.143041E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 314029.09 | 34895426.27 |
April | 0.363528E+09 | 0.137766E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4060946.53 | 16230724.70 |
May | 0.375778E+09 | 0.142848E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8725899.66 | 7144473.91 |
June | 0.364321E+09 | 0.138398E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15814072.94 | 2338136.49 |
July | 0.374985E+09 | 0.142217E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14489869.99 | 1601940.16 |
August | 0.376571E+09 | 0.143096E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11971262.08 | 3158911.04 |
September | 0.363352E+09 | 0.137821E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7213648.86 | 7982876.79 |
October | 0.375161E+09 | 0.142546E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2158409.01 | 19087286.83 |
November | 0.362735E+09 | 0.138288E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46493.77 | 39371818.98 |
December | 0.374985E+09 | 0.142217E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55354196.33 |
Annual Sum or Average | 0.442217E+10 | 0.167960E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64858489.45 | 0.275657E+09 |
Minimum of Months | 0.339028E+09 | 0.128756E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1601940.16 |
Maximum of Months | 0.376747E+09 | 0.143096E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15814072.94 | 55354196.33 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.374392E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135343E+09 |
February | 0.139600E+10 | 0.338042E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 20019.61 | 0.104757E+09 |
March | 0.155131E+10 | 0.375546E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 226600.81 | 95062130.02 |
April | 0.149688E+10 | 0.361698E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 8174594.82 | 42571159.29 |
May | 0.154732E+10 | 0.375041E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 21142729.30 | 16731588.18 |
June | 0.150015E+10 | 0.363357E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 41040779.94 | 4234029.60 |
July | 0.154405E+10 | 0.373382E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 38452910.30 | 2624154.68 |
August | 0.155059E+10 | 0.375690E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 31479496.05 | 6201151.67 |
September | 0.149615E+10 | 0.361842E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 18346812.69 | 17750945.88 |
October | 0.154478E+10 | 0.374247E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 5206421.54 | 48623542.27 |
November | 0.149361E+10 | 0.363068E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 23750.61 | 0.104531E+09 |
December | 0.154405E+10 | 0.373382E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148626E+09 |
Annual Sum or Average | 0.182090E+11 | 0.440969E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.164114E+09 | 0.727056E+09 |
Minimum of Months | 0.139600E+10 | 0.338042E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2624154.68 |
Maximum of Months | 0.155131E+10 | 0.375690E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 41040779.94 | 0.148626E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.109899E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242606E+09 |
February | 0.236489E+11 | 0.956126E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189299E+09 |
March | 0.262800E+11 | 0.101236E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86780.51 | 0.171576E+09 |
April | 0.253579E+11 | 0.916829E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12162159.65 | 78536099.58 |
May | 0.262123E+11 | 0.920218E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34649567.92 | 32971916.06 |
June | 0.254132E+11 | 0.860916E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67600578.58 | 9919960.47 |
July | 0.261570E+11 | 0.888240E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61995620.14 | 6810655.37 |
August | 0.262677E+11 | 0.949865E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49675165.80 | 13745611.94 |
September | 0.253456E+11 | 0.950663E+09 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27282414.32 | 36197407.47 |
October | 0.261693E+11 | 0.106045E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6441181.98 | 92285055.45 |
November | 0.253025E+11 | 0.102881E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190402E+09 |
December | 0.261570E+11 | 0.109151E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264800E+09 |
Annual Sum or Average | 0.308468E+12 | 0.117350E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259893E+09 | 0.132915E+10 |
Minimum of Months | 0.236489E+11 | 0.860916E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6810655.37 |
Maximum of Months | 0.262800E+11 | 0.109899E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67600578.58 | 0.264800E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.950725E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697316E+09 |
February | 0.702046E+11 | 0.854473E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543108E+09 |
March | 0.780153E+11 | 0.945028E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 750603.46 | 0.494108E+09 |
April | 0.752779E+11 | 0.903935E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38168911.65 | 0.229921E+09 |
May | 0.778146E+11 | 0.933954E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99676947.17 | 97798266.92 |
June | 0.754422E+11 | 0.902689E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192873E+09 | 29676000.05 |
July | 0.776503E+11 | 0.928656E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176799E+09 | 20533474.18 |
August | 0.779788E+11 | 0.939004E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143193E+09 | 41585018.10 |
September | 0.752414E+11 | 0.908589E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80259949.21 | 0.105476E+09 |
October | 0.776868E+11 | 0.946150E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19247861.43 | 0.266684E+09 |
November | 0.751137E+11 | 0.917420E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4416.16 | 0.549384E+09 |
December | 0.776503E+11 | 0.947171E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761903E+09 |
Annual Sum or Average | 0.915726E+12 | 0.110778E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750974E+09 | 0.383749E+10 |
Minimum of Months | 0.702046E+11 | 0.854473E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20533474.18 |
Maximum of Months | 0.780153E+11 | 0.950725E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192873E+09 | 0.761903E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118113E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55979145.30 |
February | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36420.01 | 42713928.94 |
March | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 212093.83 | 37962573.32 |
April | 0.293479E+09 | 0.114438E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5049778.43 | 15238493.38 |
May | 0.303504E+09 | 0.117643E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12791316.77 | 4904526.24 |
June | 0.293842E+09 | 0.113531E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23419356.87 | 804786.45 |
July | 0.303141E+09 | 0.118566E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22647532.73 | 257097.34 |
August | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18732927.70 | 1271789.32 |
September | 0.293479E+09 | 0.114469E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10803738.00 | 4979689.95 |
October | 0.303322E+09 | 0.118097E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3099888.23 | 17375249.78 |
November | 0.293661E+09 | 0.113984E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46811.51 | 42270562.74 |
December | 0.303141E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62012325.19 |
Annual Sum or Average | 0.357224E+10 | 0.138844E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96839864.06 | 0.285770E+09 |
Minimum of Months | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257097.34 |
Maximum of Months | 0.303685E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23419356.87 | 62012325.19 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118099E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54578583.63 |
February | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9397.98 | 41991543.92 |
March | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 129055.01 | 38269014.30 |
April | 0.293479E+09 | 0.114425E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4820392.00 | 16177377.04 |
May | 0.303504E+09 | 0.117629E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12410179.91 | 5754918.24 |
June | 0.293842E+09 | 0.113517E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22880877.68 | 1321698.82 |
July | 0.303141E+09 | 0.118553E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21964429.42 | 696187.26 |
August | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18219601.63 | 1971280.77 |
September | 0.293479E+09 | 0.114456E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10379586.00 | 6081824.56 |
October | 0.303322E+09 | 0.118083E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2794702.18 | 18711345.61 |
November | 0.293661E+09 | 0.113971E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9082.72 | 41820616.08 |
December | 0.303141E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60418178.26 |
Annual Sum or Average | 0.357224E+10 | 0.138828E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93617304.54 | 0.287793E+09 |
Minimum of Months | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 696187.26 |
Maximum of Months | 0.303685E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22880877.68 | 60418178.26 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 74229181.22 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21368239.42 |
February | 0.00 | 67036196.95 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17123681.18 |
March | 0.00 | 73639243.64 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16218098.03 |
April | 0.00 | 71920171.51 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 260899.54 | 8494807.51 |
May | 0.00 | 73934212.43 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1088638.33 | 4354720.65 |
June | 0.00 | 71349576.37 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2938217.13 | 1832334.42 |
July | 0.00 | 74514478.79 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2481438.36 | 1643445.59 |
August | 0.00 | 73639243.64 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1929831.37 | 2495457.42 |
September | 0.00 | 71939513.95 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 906690.32 | 4582764.93 |
October | 0.00 | 74219510.00 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 164196.77 | 9770026.21 |
November | 0.00 | 71634873.94 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17282722.92 |
December | 0.00 | 74524150.01 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23053610.17 |
Annual Sum or Average | 0.00 | 0.872580E+09 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9769911.82 | 0.128220E+09 |
Minimum of Months | 0.00 | 67036196.95 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1643445.59 |
Maximum of Months | 0.00 | 74524150.01 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2938217.13 | 23053610.17 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 74249479.06 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15338083.58 |
February | 0.273974E+09 | 67054527.88 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11481.86 | 11710367.31 |
March | 0.303685E+09 | 73659380.16 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60231.98 | 10513312.09 |
April | 0.293479E+09 | 71939837.95 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1399582.71 | 4351454.87 |
May | 0.303504E+09 | 73954429.61 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3509534.81 | 1511530.60 |
June | 0.293842E+09 | 71369086.78 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6436636.94 | 317136.07 |
July | 0.303141E+09 | 74534854.64 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6172992.85 | 142686.86 |
August | 0.303685E+09 | 73659380.16 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5132528.75 | 484852.63 |
September | 0.293479E+09 | 71959185.68 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2958715.62 | 1584603.10 |
October | 0.303322E+09 | 74239805.19 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 844943.88 | 4989035.87 |
November | 0.293661E+09 | 71654462.37 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16011.80 | 11546823.06 |
December | 0.303141E+09 | 74544528.51 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17017183.58 |
Annual Sum or Average | 0.357224E+10 | 0.872819E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26542661.20 | 79507069.62 |
Minimum of Months | 0.273974E+09 | 67054527.88 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142686.86 |
Maximum of Months | 0.303685E+09 | 74544528.51 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6436636.94 | 17017183.58 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118113E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56210923.18 |
February | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36506.31 | 43048983.65 |
March | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 214609.09 | 38302315.28 |
April | 0.293479E+09 | 0.114438E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5046740.64 | 15465506.79 |
May | 0.303504E+09 | 0.117643E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12774576.25 | 4998792.87 |
June | 0.293842E+09 | 0.113531E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23408742.35 | 823887.96 |
July | 0.303141E+09 | 0.118566E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22614053.35 | 264535.00 |
August | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18712065.47 | 1294527.86 |
September | 0.293479E+09 | 0.114469E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10800354.13 | 5036886.63 |
October | 0.303322E+09 | 0.118097E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3107751.24 | 17447796.10 |
November | 0.293661E+09 | 0.113984E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47328.51 | 42407240.99 |
December | 0.303141E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62220551.13 |
Annual Sum or Average | 0.357224E+10 | 0.138844E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96762727.34 | 0.287522E+09 |
Minimum of Months | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264535.00 |
Maximum of Months | 0.303685E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23408742.35 | 62220551.13 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118099E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54531614.09 |
February | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11923.96 | 42143885.75 |
March | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 132931.13 | 38376972.29 |
April | 0.293479E+09 | 0.114425E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4805179.16 | 16508084.49 |
May | 0.303504E+09 | 0.117629E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12355953.08 | 6431873.30 |
June | 0.293842E+09 | 0.113517E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22820038.18 | 1787458.55 |
July | 0.303141E+09 | 0.118553E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21881139.88 | 1079147.41 |
August | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18144701.65 | 2394123.27 |
September | 0.293479E+09 | 0.114456E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10311271.90 | 6635924.32 |
October | 0.303322E+09 | 0.118083E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2818621.01 | 18456270.27 |
November | 0.293661E+09 | 0.113971E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17152.58 | 41714482.92 |
December | 0.303141E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60402366.82 |
Annual Sum or Average | 0.357224E+10 | 0.138828E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93298912.52 | 0.290462E+09 |
Minimum of Months | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1079147.41 |
Maximum of Months | 0.303685E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22820038.18 | 60402366.82 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.108388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67614845.76 |
February | 0.348285E+10 | 0.978647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41009.71 | 52408009.66 |
March | 0.387034E+10 | 0.108722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270596.52 | 47921217.55 |
April | 0.373454E+10 | 0.104713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4965697.43 | 22569300.42 |
May | 0.386038E+10 | 0.108576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11119939.01 | 9951853.87 |
June | 0.374269E+10 | 0.105194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20810817.16 | 3235858.19 |
July | 0.385223E+10 | 0.108096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19188291.39 | 2190365.27 |
August | 0.386853E+10 | 0.108764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15692217.71 | 4376250.25 |
September | 0.373273E+10 | 0.104755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8899969.27 | 11295325.32 |
October | 0.385404E+10 | 0.108346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2462797.42 | 26760658.07 |
November | 0.372639E+10 | 0.105110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30180.73 | 54269950.62 |
December | 0.385223E+10 | 0.108096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74173738.41 |
Annual Sum or Average | 0.454292E+11 | 0.127663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83481516.35 | 0.376767E+09 |
Minimum of Months | 0.348285E+10 | 0.978647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2190365.27 |
Maximum of Months | 0.387034E+10 | 0.108764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20810817.16 | 74173738.41 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118113E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55837496.01 |
February | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34089.22 | 42670450.26 |
March | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 202844.33 | 37977601.85 |
April | 0.293479E+09 | 0.114438E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4964724.84 | 15301780.10 |
May | 0.303504E+09 | 0.117643E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12640693.49 | 4956634.64 |
June | 0.293842E+09 | 0.113531E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23212126.78 | 826301.27 |
July | 0.303141E+09 | 0.118566E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22430316.23 | 269363.94 |
August | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18539434.35 | 1299060.39 |
September | 0.293479E+09 | 0.114469E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10661876.77 | 5036768.38 |
October | 0.303322E+09 | 0.118097E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3044504.81 | 17434586.75 |
November | 0.293661E+09 | 0.113984E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44398.27 | 42232603.99 |
December | 0.303141E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61867053.51 |
Annual Sum or Average | 0.357224E+10 | 0.138844E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95775009.09 | 0.285710E+09 |
Minimum of Months | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269363.94 |
Maximum of Months | 0.303685E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23212126.78 | 61867053.51 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118099E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54260089.40 |
February | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9295.81 | 41818874.90 |
March | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 123418.61 | 38234321.48 |
April | 0.293479E+09 | 0.114425E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4741129.49 | 16204668.90 |
May | 0.303504E+09 | 0.117629E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12273383.03 | 5696896.80 |
June | 0.293842E+09 | 0.113517E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22696043.84 | 1264729.75 |
July | 0.303141E+09 | 0.118553E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21775381.67 | 645316.29 |
August | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18052413.76 | 1898600.73 |
September | 0.293479E+09 | 0.114456E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10264261.39 | 5975754.09 |
October | 0.303322E+09 | 0.118083E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2749943.22 | 18687851.66 |
November | 0.293661E+09 | 0.113971E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8000.91 | 41600134.86 |
December | 0.303141E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60122179.52 |
Annual Sum or Average | 0.357224E+10 | 0.138828E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92693271.73 | 0.286409E+09 |
Minimum of Months | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 645316.29 |
Maximum of Months | 0.303685E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22696043.84 | 60122179.52 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 74249479.06 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29199582.22 |
February | 0.273974E+09 | 67054527.88 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17112.58 | 22267139.44 |
March | 0.303685E+09 | 73659380.16 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 103450.37 | 19704305.84 |
April | 0.293479E+09 | 71939837.95 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2539712.61 | 7878261.81 |
May | 0.303504E+09 | 73954429.61 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6478582.74 | 2534823.19 |
June | 0.293842E+09 | 71369086.78 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11907375.93 | 420754.10 |
July | 0.303141E+09 | 74534854.64 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11487787.67 | 137641.51 |
August | 0.303685E+09 | 73659380.16 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9490865.46 | 666330.71 |
September | 0.293479E+09 | 71959185.68 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5452557.56 | 2589104.25 |
October | 0.303322E+09 | 74239805.19 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1545049.71 | 9013399.41 |
November | 0.293661E+09 | 71654462.37 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20879.65 | 21949980.16 |
December | 0.303141E+09 | 74544528.51 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32392888.71 |
Annual Sum or Average | 0.357224E+10 | 0.872819E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49043374.28 | 0.148754E+09 |
Minimum of Months | 0.273974E+09 | 67054527.88 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137641.51 |
Maximum of Months | 0.303685E+09 | 74544528.51 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11907375.93 | 32392888.71 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.231292E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159922E+09 |
February | 0.415303E+11 | 0.204526E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125073E+09 |
March | 0.461508E+11 | 0.221543E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61476.30 | 0.115127E+09 |
April | 0.445315E+11 | 0.204595E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7112102.78 | 53894096.17 |
May | 0.460320E+11 | 0.207140E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19924939.82 | 23005279.34 |
June | 0.446286E+11 | 0.197312E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40952726.86 | 7060737.08 |
July | 0.459349E+11 | 0.203053E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37439788.61 | 4962366.49 |
August | 0.461292E+11 | 0.211526E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30366206.57 | 9990802.57 |
September | 0.445099E+11 | 0.210811E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16987677.47 | 24374183.54 |
October | 0.459565E+11 | 0.225963E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4041120.61 | 61394039.14 |
November | 0.444343E+11 | 0.221189E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1228.60 | 0.125269E+09 |
December | 0.459349E+11 | 0.229779E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174725E+09 |
Annual Sum or Average | 0.541708E+12 | 0.256873E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156887E+09 | 0.884797E+09 |
Minimum of Months | 0.415303E+11 | 0.197312E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4962366.49 |
Maximum of Months | 0.461508E+11 | 0.231292E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40952726.86 | 0.174725E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.231292E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161622E+09 |
February | 0.415303E+11 | 0.204526E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126364E+09 |
March | 0.461508E+11 | 0.221543E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45688.97 | 0.116269E+09 |
April | 0.445315E+11 | 0.204595E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7004326.35 | 54245878.98 |
May | 0.460320E+11 | 0.207140E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19842961.73 | 23100870.69 |
June | 0.446286E+11 | 0.197312E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40934595.11 | 7069125.09 |
July | 0.459349E+11 | 0.203053E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37414166.53 | 4966767.53 |
August | 0.461292E+11 | 0.211526E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30319215.96 | 10036078.31 |
September | 0.445099E+11 | 0.210811E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16880079.52 | 24425771.44 |
October | 0.459565E+11 | 0.225963E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3970966.14 | 61830922.99 |
November | 0.444343E+11 | 0.221189E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31.57 | 0.126466E+09 |
December | 0.459349E+11 | 0.229779E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176589E+09 |
Annual Sum or Average | 0.541708E+12 | 0.256873E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156412E+09 | 0.892985E+09 |
Minimum of Months | 0.415303E+11 | 0.197312E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4966767.53 |
Maximum of Months | 0.461508E+11 | 0.231292E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40934595.11 | 0.176589E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.101925E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144687E+09 |
February | 0.369574E+10 | 0.920291E+09 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112791E+09 |
March | 0.410691E+10 | 0.102239E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 36469.07 | 0.103613E+09 |
April | 0.396281E+10 | 0.984694E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 6253813.10 | 48140499.96 |
May | 0.409635E+10 | 0.102102E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 17767215.57 | 20447250.52 |
June | 0.397146E+10 | 0.989210E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 36662490.41 | 6250186.73 |
July | 0.408770E+10 | 0.101650E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 33511168.33 | 4379170.89 |
August | 0.410499E+10 | 0.102279E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 27147054.00 | 8878114.56 |
September | 0.396089E+10 | 0.985086E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 15080899.15 | 21652425.78 |
October | 0.408962E+10 | 0.101886E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3534928.48 | 55005112.97 |
November | 0.395417E+10 | 0.988424E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112857E+09 |
December | 0.408770E+10 | 0.101650E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158145E+09 |
Annual Sum or Average | 0.482060E+11 | 0.120050E+11 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.139994E+09 | 0.796847E+09 |
Minimum of Months | 0.369574E+10 | 0.920291E+09 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4379170.89 |
Maximum of Months | 0.410691E+10 | 0.102279E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 36662490.41 | 0.158145E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.114712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118769E+09 |
February | 0.368610E+10 | 0.103575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17037.12 | 91557949.29 |
March | 0.409620E+10 | 0.115066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366390.36 | 82856545.31 |
April | 0.395248E+10 | 0.110823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7828851.03 | 38695072.95 |
May | 0.408566E+10 | 0.114911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18519262.99 | 16960294.09 |
June | 0.396110E+10 | 0.111331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36011653.15 | 5489177.27 |
July | 0.407704E+10 | 0.114403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33052177.06 | 3716243.90 |
August | 0.409429E+10 | 0.115110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26877740.34 | 7414032.74 |
September | 0.395056E+10 | 0.110867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15142866.58 | 18827000.33 |
October | 0.407896E+10 | 0.114668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3906344.36 | 45168779.63 |
November | 0.394385E+10 | 0.111243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27664.11 | 92702801.09 |
December | 0.407704E+10 | 0.114403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131248E+09 |
Annual Sum or Average | 0.480803E+11 | 0.135111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141750E+09 | 0.653405E+09 |
Minimum of Months | 0.368610E+10 | 0.103575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3716243.90 |
Maximum of Months | 0.409620E+10 | 0.115110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36011653.15 | 0.131248E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 8344.11 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 8344.11 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 8344.11 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 8344.11 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 8344.11 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 8344.11 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 8344.11 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 8344.11 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 8344.11 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 8344.11 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 8344.11 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 8344.11 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 8344.11 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 8344.11 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 461.08 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 71.56 | 27-JAN-07:00 |
February | 1169.53 | 01-FEB-00:10 | 461.08 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 75.20 | 03-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 461.08 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 | 21-MAR-16:00 | 70.74 | 02-MAR-05:40 |
April | 1169.53 | 01-APR-00:10 | 461.08 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.23 | 21-APR-14:00 | 48.16 | 12-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 461.08 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.09 | 21-MAY-14:00 | 32.39 | 02-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 461.08 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.16 | 02-JUN-16:00 | 20.96 | 13-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 461.08 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.84 | 02-JUL-16:00 | 12.57 | 05-JUL-06:00 |
August | 1169.53 | 01-AUG-00:10 | 461.08 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.27 | 07-AUG-16:00 | 16.37 | 31-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 461.08 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.40 | 19-SEP-14:00 | 37.15 | 30-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 461.08 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.81 | 01-OCT-15:00 | 39.92 | 11-OCT-06:00 |
November | 1169.53 | 01-NOV-00:10 | 461.08 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 60.64 | 28-NOV-05:00 |
December | 1169.53 | 01-DEC-00:10 | 461.08 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 71.82 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 461.08 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.57 | |||||
Maximum of Months | 1169.53 | 461.08 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 36.16 | 75.20 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 533.93 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 29.18 | 27-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 533.93 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 | 20-FEB-15:00 | 30.72 | 03-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 533.93 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.09 | 22-MAR-13:00 | 28.91 | 02-MAR-05:30 |
April | 1354.32 | 01-APR-00:10 | 533.93 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 | 21-APR-14:00 | 20.83 | 12-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 533.93 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.95 | 19-MAY-14:00 | 14.67 | 02-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 533.93 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.19 | 02-JUN-16:00 | 9.12 | 13-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 533.93 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.82 | 02-JUL-16:00 | 6.24 | 05-JUL-06:00 |
August | 1354.32 | 01-AUG-00:10 | 533.93 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.46 | 07-AUG-16:00 | 7.41 | 31-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 533.93 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.66 | 19-SEP-14:00 | 16.18 | 30-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 533.93 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.76 | 01-OCT-15:00 | 17.69 | 25-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 533.93 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 | 03-NOV-15:55 | 25.48 | 17-NOV-04:00 |
December | 1354.32 | 01-DEC-00:10 | 533.93 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 29.18 | 19-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 533.93 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.24 | |||||
Maximum of Months | 1354.32 | 533.93 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 14.19 | 30.72 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 615.76 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 65.27 | 27-JAN-07:00 |
February | 286.42 | 01-FEB-00:10 | 615.76 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 | 20-FEB-15:00 | 68.59 | 03-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 615.76 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.92 | 21-MAR-16:00 | 64.53 | 02-MAR-05:20 |
April | 286.42 | 01-APR-00:10 | 615.76 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.74 | 21-APR-14:00 | 46.65 | 12-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 615.76 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 19-MAY-16:00 | 33.01 | 02-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 615.76 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.53 | 02-JUN-16:00 | 21.39 | 13-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 615.76 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.25 | 01-JUL-17:00 | 14.30 | 05-JUL-06:00 |
August | 286.42 | 01-AUG-00:10 | 615.76 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.46 | 07-AUG-16:00 | 17.06 | 31-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 615.76 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.38 | 19-SEP-14:00 | 36.75 | 30-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 615.76 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.98 | 01-OCT-15:00 | 39.61 | 11-OCT-06:00 |
November | 286.42 | 01-NOV-00:10 | 615.76 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 | 08-NOV-15:00 | 56.50 | 17-NOV-04:00 |
December | 286.42 | 01-DEC-00:10 | 615.76 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 65.52 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.30 | |||||
Maximum of Months | 286.42 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 33.53 | 68.59 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 137.35 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 37.66 | 27-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 137.35 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 20-FEB-15:00 | 39.57 | 03-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 137.35 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.51 | 21-MAR-16:00 | 37.23 | 02-MAR-06:00 |
April | 220.32 | 01-APR-00:10 | 137.35 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.97 | 21-APR-14:00 | 26.53 | 12-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 137.35 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.92 | 19-MAY-14:00 | 18.70 | 02-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 137.35 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.26 | 02-JUN-16:00 | 12.11 | 13-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 137.35 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.49 | 01-JUL-17:00 | 8.04 | 05-JUL-06:00 |
August | 220.32 | 01-AUG-00:10 | 137.35 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.98 | 07-AUG-16:00 | 9.55 | 31-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 137.35 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.45 | 19-SEP-14:00 | 20.84 | 30-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 137.35 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.60 | 01-OCT-15:00 | 22.47 | 11-OCT-06:00 |
November | 220.32 | 01-NOV-00:10 | 137.35 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.25 | 08-NOV-15:00 | 32.38 | 17-NOV-04:00 |
December | 220.32 | 01-DEC-00:10 | 137.35 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 37.80 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 137.35 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.04 | |||||
Maximum of Months | 220.32 | 137.35 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 19.26 | 39.57 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 360.62 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 99.62 | 27-JAN-07:00 |
February | 907.20 | 01-FEB-00:10 | 360.62 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 2.14 | 20-FEB-16:20 | 104.19 | 03-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 360.62 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 7.62 | 21-MAR-16:00 | 97.00 | 02-MAR-06:10 |
April | 907.20 | 01-APR-00:10 | 360.62 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 28.06 | 21-APR-15:20 | 70.13 | 12-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 360.62 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 38.87 | 21-MAY-16:00 | 48.42 | 02-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 360.62 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 50.36 | 02-JUN-16:30 | 28.08 | 13-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 360.62 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 50.46 | 02-JUL-16:00 | 20.13 | 05-JUL-06:00 |
August | 907.20 | 01-AUG-00:10 | 360.62 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 45.22 | 07-AUG-16:00 | 23.91 | 31-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 360.62 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 35.23 | 19-SEP-16:00 | 51.52 | 30-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 360.62 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 32.22 | 01-OCT-15:20 | 58.55 | 25-OCT-06:00 |
November | 907.20 | 01-NOV-00:10 | 360.62 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 4.24 | 03-NOV-16:00 | 84.42 | 17-NOV-06:10 |
December | 907.20 | 01-DEC-00:10 | 360.62 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 99.99 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 20.13 | ||||||
Maximum of Months | 907.20 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 50.46 | 104.19 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1416.11 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 165.94 | 27-JAN-07:00 |
February | 15368.40 | 01-FEB-00:10 | 1416.11 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 174.15 | 03-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 1416.11 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.57 | 21-MAR-16:00 | 167.60 | 02-MAR-05:20 |
April | 15368.40 | 01-APR-00:10 | 1416.11 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.71 | 21-APR-14:00 | 117.39 | 12-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 1416.11 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.24 | 19-MAY-14:00 | 82.38 | 02-MAY-06:00 |
June | 15368.40 | 01-JUN-00:10 | 1416.11 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.95 | 02-JUN-16:00 | 52.20 | 13-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1416.11 | 03-JUL-19:19 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.88 | 02-JUL-16:00 | 35.57 | 05-JUL-06:00 |
August | 15368.40 | 01-AUG-00:10 | 1416.11 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.35 | 07-AUG-16:00 | 42.42 | 31-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 1416.11 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.95 | 19-SEP-14:00 | 90.96 | 30-SEP-06:00 |
October | 15368.40 | 01-OCT-23:10 | 1416.11 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.23 | 01-OCT-15:00 | 100.34 | 25-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1416.11 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 148.21 | 17-NOV-04:00 |
December | 15368.40 | 01-DEC-00:10 | 1416.11 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 169.29 | 19-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1416.11 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.57 | |||||
Maximum of Months | 15368.40 | 1416.11 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 79.95 | 174.15 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9580.84 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 490.51 | 27-JAN-07:00 |
February | 45622.98 | 01-FEB-00:10 | 9580.84 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 514.05 | 03-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 9580.84 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.99 | 22-MAR-13:00 | 489.60 | 02-MAR-05:40 |
April | 45622.98 | 01-APR-00:10 | 9580.84 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.31 | 21-APR-14:00 | 349.75 | 12-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 9580.84 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.32 | 19-MAY-14:00 | 245.53 | 02-MAY-06:00 |
June | 45622.98 | 01-JUN-00:10 | 9580.84 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.13 | 02-JUN-16:00 | 149.19 | 13-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 9580.84 | 03-JUL-19:19 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.39 | 02-JUL-16:00 | 102.06 | 05-JUL-06:00 |
August | 45622.98 | 01-AUG-00:10 | 9580.84 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.83 | 07-AUG-16:00 | 121.24 | 31-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 9580.84 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.00 | 19-SEP-14:00 | 266.39 | 30-SEP-06:00 |
October | 45622.98 | 01-OCT-23:10 | 9580.84 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.08 | 01-OCT-15:00 | 296.45 | 25-OCT-06:00 |
November | 45622.98 | 01-NOV-00:10 | 9580.84 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.79 | 08-NOV-15:00 | 429.60 | 17-NOV-04:00 |
December | 45622.98 | 01-DEC-00:10 | 9580.84 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 493.15 | 19-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9580.84 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.06 | |||||
Maximum of Months | 45622.98 | 9580.84 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 231.13 | 514.05 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.87 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 41.78 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 106.87 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.92 | 20-FEB-16:07 | 43.89 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 106.87 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.62 | 21-MAR-16:00 | 41.31 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 106.87 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.54 | 21-APR-15:07 | 28.19 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 106.87 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.72 | 19-MAY-16:00 | 18.17 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 106.87 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 02-JUN-16:00 | 9.38 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 106.87 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.25 | 02-JUL-16:00 | 5.08 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 106.87 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.77 | 07-AUG-16:00 | 7.30 | 14-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 106.87 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.19 | 19-SEP-16:00 | 20.05 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 106.87 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.38 | 01-OCT-15:10 | 22.80 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 106.87 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 03-NOV-16:00 | 35.45 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 106.87 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 41.94 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.08 | |||||
Maximum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 43.89 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.85 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 41.78 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 106.85 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.92 | 20-FEB-16:09 | 43.89 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 106.85 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.63 | 21-MAR-16:00 | 41.30 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 106.85 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.54 | 21-APR-15:07 | 28.19 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 106.85 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.72 | 19-MAY-16:00 | 18.17 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 106.85 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 02-JUN-16:00 | 9.85 | 13-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 106.85 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.25 | 02-JUL-16:00 | 7.16 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 106.85 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.77 | 07-AUG-16:00 | 8.60 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 106.85 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.21 | 19-SEP-16:00 | 20.04 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 106.85 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 01-OCT-15:10 | 22.80 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 106.85 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 | 03-NOV-15:07 | 35.44 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 106.85 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 41.93 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.16 | |||||
Maximum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 43.89 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 67.16 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 13.59 | 27-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 67.16 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 14.27 | 03-FEB-07:00 |
March | 0.00 | 01-MAR-00:10 | 67.16 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 13.17 | 02-MAR-05:00 |
April | 0.00 | 01-APR-00:10 | 67.16 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.19 | 21-APR-14:00 | 10.06 | 12-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 67.16 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.31 | 21-MAY-14:00 | 7.46 | 02-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 67.16 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.79 | 02-JUN-16:00 | 4.98 | 13-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 67.16 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.57 | 02-JUL-16:00 | 3.76 | 05-JUL-06:00 |
August | 0.00 | 01-AUG-00:10 | 67.16 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.15 | 07-AUG-16:00 | 4.26 | 31-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 67.16 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.87 | 19-SEP-14:00 | 8.01 | 30-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 67.16 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.44 | 01-OCT-15:00 | 8.81 | 25-OCT-06:00 |
November | 0.00 | 01-NOV-00:10 | 67.16 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 12.03 | 17-NOV-04:00 |
December | 0.00 | 01-DEC-00:10 | 67.16 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 13.49 | 19-DEC-04:15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 67.16 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.76 | |||||
Maximum of Months | 0.00 | 67.16 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 4.79 | 14.27 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 67.18 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 11.66 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 67.18 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 | 20-FEB-16:07 | 12.25 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 67.18 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.57 | 21-MAR-16:00 | 11.53 | 02-MAR-05:07 |
April | 180.00 | 01-APR-00:10 | 67.18 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.34 | 21-APR-15:09 | 7.87 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 67.18 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 19-MAY-16:00 | 5.07 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 67.18 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.98 | 02-JUN-16:00 | 2.62 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 67.18 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.77 | 02-JUL-16:00 | 1.88 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 67.18 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.35 | 07-AUG-16:00 | 2.43 | 16-AUG-21:40 |
September | 180.00 | 01-SEP-00:10 | 67.18 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.08 | 19-SEP-16:00 | 5.59 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 67.18 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.61 | 01-OCT-15:09 | 6.36 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 67.18 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 | 03-NOV-15:07 | 9.89 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 67.18 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 11.70 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 67.18 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.88 | |||||
Maximum of Months | 180.00 | 67.18 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6.98 | 12.25 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.87 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 41.78 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 106.87 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.92 | 20-FEB-16:09 | 43.89 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 106.87 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.63 | 21-MAR-16:00 | 41.31 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 106.87 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.54 | 21-APR-15:07 | 28.19 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 106.87 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.72 | 19-MAY-16:00 | 18.17 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 106.87 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 02-JUN-16:00 | 9.38 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 106.87 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.25 | 02-JUL-16:00 | 5.28 | 05-JUL-07:10 |
August | 180.00 | 01-AUG-00:10 | 106.87 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.77 | 07-AUG-16:00 | 7.63 | 30-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 106.87 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.21 | 19-SEP-16:00 | 20.05 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 106.87 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 01-OCT-15:10 | 22.80 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 106.87 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 03-NOV-16:00 | 35.45 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 106.87 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 41.94 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.28 | |||||
Maximum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 43.89 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.85 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 41.78 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 106.85 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.92 | 20-FEB-16:06 | 43.89 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 106.85 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.63 | 21-MAR-16:00 | 41.31 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 106.85 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.54 | 21-APR-15:10 | 28.19 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 106.85 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.71 | 19-MAY-16:00 | 18.17 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 106.85 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 02-JUN-16:00 | 10.40 | 13-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 106.85 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.25 | 02-JUL-16:00 | 8.55 | 05-JUL-06:40 |
August | 180.00 | 01-AUG-00:10 | 106.85 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.77 | 07-AUG-16:00 | 9.44 | 30-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 106.85 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.21 | 19-SEP-16:00 | 20.04 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 106.85 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 01-OCT-15:10 | 22.80 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 106.85 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 | 03-NOV-15:07 | 35.45 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 106.85 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 41.93 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.55 | |||||
Maximum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 43.89 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1044.00 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 50.30 | 27-JAN-07:00 |
February | 2263.36 | 01-FEB-00:10 | 1044.00 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.92 | 20-FEB-15:00 | 52.86 | 03-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1044.00 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.69 | 21-MAR-16:00 | 49.83 | 02-MAR-05:03 |
April | 2263.36 | 01-APR-00:10 | 1044.00 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.53 | 21-APR-14:00 | 36.16 | 12-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1044.00 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.41 | 19-MAY-14:00 | 25.46 | 02-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 1044.00 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.39 | 02-JUN-16:00 | 16.43 | 13-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1044.00 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.57 | 02-JUL-16:00 | 10.97 | 05-JUL-06:00 |
August | 2263.36 | 01-AUG-00:10 | 1044.00 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.57 | 07-AUG-16:00 | 13.01 | 31-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1044.00 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.05 | 19-SEP-14:00 | 28.47 | 30-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 1044.00 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.75 | 01-OCT-15:00 | 30.59 | 25-OCT-06:00 |
November | 2263.36 | 01-NOV-00:10 | 1044.00 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.23 | 08-NOV-15:00 | 44.35 | 17-NOV-04:00 |
December | 2263.36 | 01-DEC-00:10 | 1044.00 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 50.49 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1044.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.97 | ||||
Maximum of Months | 2263.36 | 1044.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.39 | 52.86 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.87 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 41.89 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 106.87 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 20-FEB-16:07 | 44.00 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 106.87 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.54 | 21-MAR-16:00 | 41.42 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 106.87 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.46 | 21-APR-15:07 | 28.29 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 106.87 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.63 | 19-MAY-16:00 | 18.26 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 106.87 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.92 | 02-JUN-16:00 | 9.47 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 106.87 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 02-JUL-16:00 | 5.17 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 106.87 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.68 | 07-AUG-16:00 | 6.90 | 14-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 106.87 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.07 | 19-SEP-16:00 | 20.14 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 106.87 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.32 | 01-OCT-15:10 | 22.90 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 106.87 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 | 03-NOV-16:00 | 35.55 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 106.87 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 42.04 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | |||||
Maximum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 24.92 | 44.00 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.85 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 41.88 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 106.85 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 20-FEB-16:09 | 44.00 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 106.85 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.54 | 21-MAR-16:00 | 41.41 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 106.85 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.46 | 21-APR-15:07 | 28.29 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 106.85 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.63 | 19-MAY-16:00 | 18.26 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 106.85 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.91 | 02-JUN-16:00 | 9.47 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 106.85 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.16 | 02-JUL-16:00 | 6.88 | 18-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 106.85 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.68 | 07-AUG-16:00 | 8.09 | 16-AUG-21:30 |
September | 180.00 | 01-SEP-00:10 | 106.85 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.13 | 19-SEP-16:00 | 20.14 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 106.85 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.42 | 01-OCT-15:10 | 22.89 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 106.85 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 | 03-NOV-15:07 | 35.55 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 106.85 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 42.04 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.88 | |||||
Maximum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 24.91 | 44.00 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 67.18 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 21.43 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 67.18 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.45 | 20-FEB-16:09 | 22.51 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 67.18 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21-MAR-16:00 | 21.19 | 02-MAR-05:10 |
April | 180.00 | 01-APR-00:10 | 67.18 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.91 | 21-APR-15:10 | 14.47 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 67.18 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.05 | 19-MAY-16:00 | 9.34 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 67.18 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.75 | 02-JUN-16:00 | 4.84 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 67.18 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.37 | 02-JUL-16:00 | 2.64 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 67.18 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.61 | 07-AUG-16:00 | 3.53 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 67.18 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.28 | 19-SEP-16:00 | 10.31 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 67.18 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.25 | 01-OCT-15:10 | 11.71 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 67.18 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.03 | 03-NOV-16:00 | 18.19 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 67.18 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 21.51 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 67.18 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.64 | |||||
Maximum of Months | 180.00 | 67.18 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 12.75 | 22.51 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2486.81 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 113.79 | 27-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 2486.81 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 118.91 | 03-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2486.81 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 22-MAR-13:00 | 112.75 | 02-MAR-05:10 |
April | 26988.77 | 01-APR-00:10 | 2486.81 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.32 | 21-APR-14:00 | 80.20 | 12-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2486.81 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.04 | 21-MAY-14:00 | 55.48 | 02-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2486.81 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.92 | 02-JUN-16:00 | 33.85 | 13-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2486.81 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.04 | 02-JUL-16:00 | 23.27 | 05-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 2486.81 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.40 | 07-AUG-16:00 | 27.58 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2486.81 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.24 | 19-SEP-14:00 | 60.17 | 30-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2486.81 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 | 01-OCT-15:00 | 67.02 | 25-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2486.81 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 | 08-NOV-15:00 | 98.28 | 28-NOV-05:00 |
December | 26988.77 | 01-DEC-00:10 | 2486.81 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 114.05 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2486.81 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.27 | |||||
Maximum of Months | 26988.77 | 2486.81 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 50.92 | 118.91 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2486.81 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 113.79 | 27-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 2486.81 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 118.99 | 03-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2486.81 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.70 | 22-MAR-13:00 | 112.75 | 02-MAR-05:10 |
April | 26988.77 | 01-APR-00:10 | 2486.81 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.32 | 21-APR-14:00 | 80.20 | 12-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2486.81 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.04 | 21-MAY-14:00 | 55.48 | 02-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2486.81 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.92 | 02-JUN-16:00 | 33.85 | 13-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2486.81 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.04 | 02-JUL-16:00 | 23.27 | 05-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 2486.81 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.40 | 07-AUG-16:00 | 27.58 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2486.81 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.24 | 19-SEP-14:00 | 60.17 | 30-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2486.81 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 | 01-OCT-15:00 | 67.02 | 25-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2486.81 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 | 08-NOV-15:00 | 98.28 | 28-NOV-05:00 |
December | 26988.77 | 01-DEC-00:10 | 2486.81 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 114.22 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2486.81 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.27 | |||||
Maximum of Months | 26988.77 | 2486.81 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 50.92 | 118.99 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 981.75 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 101.85 | 27-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 981.75 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 106.51 | 03-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 981.75 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 2.92 | 21-MAR-16:00 | 99.28 | 02-MAR-06:10 |
April | 2401.70 | 01-APR-00:10 | 981.75 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 25.38 | 21-APR-14:00 | 71.78 | 12-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 981.75 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 34.08 | 21-MAY-14:00 | 49.65 | 02-MAY-06:00 |
June | 2401.70 | 01-JUN-00:10 | 981.75 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 45.63 | 02-JUN-16:00 | 30.30 | 13-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 981.75 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 43.95 | 02-JUL-16:00 | 20.82 | 05-JUL-06:00 |
August | 2401.70 | 01-AUG-00:10 | 981.75 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 40.69 | 07-AUG-16:00 | 24.68 | 31-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 981.75 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 30.68 | 19-SEP-14:00 | 53.85 | 30-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 981.75 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 27.40 | 01-OCT-15:00 | 59.98 | 25-OCT-06:00 |
November | 2401.70 | 01-NOV-00:10 | 981.75 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 87.08 | 17-NOV-06:00 |
December | 2401.70 | 01-DEC-00:10 | 981.75 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 102.23 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 981.75 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 20.82 | ||||||
Maximum of Months | 2401.70 | 981.75 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 45.63 | 106.51 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1104.91 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 89.23 | 27-JAN-07:00 |
February | 2395.44 | 01-FEB-00:10 | 1104.91 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.73 | 20-FEB-16:00 | 93.75 | 03-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1104.91 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.56 | 21-MAR-16:00 | 88.22 | 02-MAR-06:00 |
April | 2395.44 | 01-APR-00:10 | 1104.91 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.56 | 21-APR-14:00 | 60.66 | 12-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1104.91 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.33 | 21-MAY-14:00 | 43.05 | 02-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 1104.91 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.61 | 02-JUN-16:00 | 28.04 | 13-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1104.91 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.97 | 02-JUL-16:00 | 18.18 | 05-JUL-06:00 |
August | 2395.44 | 01-AUG-00:10 | 1104.91 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.77 | 07-AUG-16:00 | 21.87 | 31-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1104.91 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 19-SEP-14:00 | 47.98 | 30-SEP-06:00 |
October | 2395.44 | 01-OCT-23:10 | 1104.91 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.78 | 01-OCT-15:00 | 51.11 | 11-OCT-06:00 |
November | 2395.44 | 01-NOV-00:10 | 1104.91 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.12 | 08-NOV-15:00 | 75.68 | 28-NOV-05:00 |
December | 2395.44 | 01-DEC-00:10 | 1104.91 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 89.57 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1104.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.18 | ||||
Maximum of Months | 2395.44 | 1104.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.61 | 93.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11718.02 | 06-JAN-22:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10922.41 | 01-FEB-21:00 | 8945.92 | 8344.11 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9418.81 | 01-MAR-21:00 | 8945.92 | 8344.11 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10026.62 | 30-APR-10:33 | 11501.89 | 8343.99 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10584.76 | 21-MAY-10:33 | 11501.89 | 8343.99 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11385.07 | 15-JUN-18:10 | 53675.50 | 44502.01 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 12893.89 | 26-JUL-18:10 | 53675.50 | 44502.01 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17180.18 | 24-AUG-21:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19881.44 | 22-SEP-21:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19770.76 | 06-OCT-21:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19296.76 | 01-NOV-21:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17594.45 | 01-DEC-22:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 9418.81 | 8945.92 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19881.44 | 53675.50 | 44502.01 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2781.30 | 12-JAN-13:50 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.64 |
February | 2826.90 | 07-FEB-13:30 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 |
March | 2186.94 | 16-MAR-13:20 | 519.79 | 256.16 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.08 |
April | 2270.33 | 04-APR-13:30 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 7.44 | 0.00 |
May | 2216.71 | 31-MAY-18:03 | 5457.82 | 2459.10 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 17.23 | 0.00 |
June | 2593.65 | 15-JUN-18:03 | 5457.82 | 2459.10 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 29.12 | 0.00 |
July | 2591.44 | 26-JUL-18:03 | 5457.82 | 2459.10 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 24.16 | 0.00 |
August | 2756.61 | 27-AUG-12:00 | 389.84 | 153.69 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 23.09 | 0.00 |
September | 3398.53 | 20-SEP-12:50 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 20.16 | 0.00 |
October | 3526.29 | 18-OCT-13:00 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 9.59 | 0.00 |
November | 3348.37 | 10-NOV-12:10 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 |
December | 2527.86 | 16-DEC-13:30 | 389.84 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2186.94 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3526.29 | 5457.82 | 2459.10 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 29.12 | 25.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1290.59 | 12-JAN-22:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.91 |
February | 1457.44 | 21-FEB-22:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.77 |
March | 1520.82 | 16-MAR-21:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.82 |
April | 1849.48 | 28-APR-20:55 | 2407.68 | 949.22 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 |
May | 2027.93 | 19-MAY-21:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.77 | 0.00 |
June | 2248.32 | 15-JUN-21:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 | 0.00 |
July | 2209.13 | 26-JUL-21:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 4.75 | 0.00 |
August | 2245.92 | 07-AUG-21:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 7.40 | 0.00 |
September | 2134.65 | 20-SEP-20:10 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.37 | 0.00 |
October | 2055.06 | 05-OCT-20:10 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
November | 1700.78 | 09-NOV-22:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.09 |
December | 1205.73 | 07-DEC-21:00 | 1053.36 | 533.93 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1205.73 | 1053.36 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2248.32 | 2407.68 | 949.22 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 | 14.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 907.23 | 03-JAN-21:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.77 |
February | 957.12 | 21-FEB-21:00 | 445.54 | 1231.52 | 1678.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.14 |
March | 1011.20 | 16-MAR-18:09 | 1559.38 | 3831.39 | 5566.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.28 |
April | 1194.93 | 30-APR-10:33 | 286.42 | 615.76 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 | 0.00 |
May | 1654.71 | 31-MAY-21:00 | 254.59 | 547.34 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 9.85 | 0.00 |
June | 2058.23 | 15-JUN-20:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 22.12 | 0.00 |
July | 2045.68 | 03-JUL-20:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 9.85 | 0.00 |
August | 1993.32 | 07-AUG-20:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 17.43 | 0.00 |
September | 1644.79 | 22-SEP-20:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 0.00 |
October | 1419.20 | 05-OCT-21:00 | 254.59 | 547.34 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.64 |
November | 1055.24 | 10-NOV-11:33 | 190.94 | 513.13 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 |
December | 880.87 | 10-DEC-11:33 | 286.42 | 615.76 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 880.87 | 190.94 | 513.13 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2058.23 | 1559.38 | 3831.39 | 5566.86 | 0.00 | 0.00 | 0.00 | 0.00 | 22.12 | 18.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 479.77 | 01-JAN-11:33 | 220.32 | 137.35 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.73 |
February | 519.27 | 20-FEB-11:33 | 220.32 | 137.35 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.84 |
March | 539.74 | 16-MAR-10:33 | 146.88 | 114.47 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 |
April | 644.18 | 30-APR-10:33 | 220.32 | 137.35 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 | 0.00 |
May | 706.60 | 31-MAY-21:00 | 195.84 | 122.09 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 5.68 | 0.00 |
June | 945.74 | 15-JUN-21:00 | 195.84 | 122.09 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 12.07 | 0.00 |
July | 938.40 | 03-JUL-18:30 | 171.36 | 122.09 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 13.54 | 0.00 |
August | 922.55 | 07-AUG-21:00 | 195.84 | 122.09 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 10.09 | 0.00 |
September | 696.14 | 22-SEP-21:00 | 195.84 | 122.09 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 0.00 |
October | 670.41 | 05-OCT-10:33 | 146.88 | 114.47 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 | 0.00 |
November | 571.09 | 10-NOV-11:33 | 146.88 | 114.47 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.26 |
December | 475.77 | 10-DEC-11:33 | 220.32 | 137.35 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 475.77 | 146.88 | 114.47 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 945.74 | 220.32 | 137.35 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 13.54 | 10.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37443.35 | 12-JAN-21:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 37.23 |
February | 37798.03 | 21-FEB-20:55 | 1411.20 | 721.23 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 29.53 |
March | 37927.26 | 16-MAR-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 22.01 |
April | 38676.19 | 28-APR-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 3.15 | 0.00 |
May | 38976.80 | 30-MAY-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 15.31 | 0.00 |
June | 39337.55 | 15-JUN-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 30.20 | 0.00 |
July | 39327.45 | 03-JUL-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 13.45 | 0.00 |
August | 39209.76 | 04-AUG-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 28.59 | 0.00 |
September | 38930.19 | 20-SEP-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 5.04 | 0.00 |
October | 38704.40 | 05-OCT-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
November | 38028.35 | 09-NOV-21:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 12.85 |
December | 37207.98 | 15-DEC-21:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 31.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37207.98 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39337.55 | 1411.20 | 721.23 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 30.20 | 37.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11422.82 | 01-JAN-11:00 | 8538.00 | 103.85 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.06 |
February | 11320.41 | 20-FEB-13:00 | 5122.80 | 103.85 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.60 |
March | 10168.26 | 14-MAR-15:03 | 59766.00 | 605.78 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 |
April | 10916.76 | 19-APR-21:10 | 15368.40 | 944.07 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 22.84 | 0.00 |
May | 11246.07 | 31-MAY-21:10 | 15368.40 | 944.07 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 22.99 | 0.00 |
June | 11815.04 | 15-JUN-21:10 | 15368.40 | 944.07 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 46.81 | 0.00 |
July | 11776.41 | 26-JUL-21:10 | 15368.40 | 944.07 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 25.69 | 0.00 |
August | 12212.34 | 07-AUG-21:10 | 15368.40 | 944.07 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 39.97 | 0.00 |
September | 12103.68 | 19-SEP-15:03 | 51228.00 | 519.24 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 51.24 | 0.00 |
October | 12731.71 | 22-OCT-12:00 | 5122.80 | 103.85 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
November | 12779.25 | 11-NOV-11:00 | 8538.00 | 103.85 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.78 |
December | 11064.02 | 16-DEC-13:30 | 5122.80 | 86.54 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10168.26 | 5122.80 | 86.54 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12779.25 | 59766.00 | 944.07 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 51.24 | 66.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 32099.71 | 12-JAN-22:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.65 |
February | 33417.88 | 07-FEB-22:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.25 |
March | 34278.03 | 16-MAR-21:10 | 91245.96 | 12774.46 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.77 |
April | 37771.34 | 21-APR-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 14.30 | 0.00 |
May | 40682.81 | 31-MAY-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 65.64 | 0.00 |
June | 43099.70 | 15-JUN-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 133.70 | 0.00 |
July | 42917.62 | 26-JUL-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 73.37 | 0.00 |
August | 43649.78 | 07-AUG-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 114.17 | 0.00 |
September | 42002.39 | 21-SEP-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 33.57 | 0.00 |
October | 41364.96 | 05-OCT-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 |
November | 37598.95 | 09-NOV-22:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.31 |
December | 30285.81 | 15-DEC-22:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 30285.81 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43649.78 | 91245.96 | 12774.46 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 133.70 | 237.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2992.41 | 10-JAN-16:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.89 |
February | 3298.91 | 20-FEB-16:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 | 0.00 |
March | 3315.99 | 21-MAR-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 2.85 | 0.00 |
April | 3410.73 | 15-APR-15:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 6.71 | 0.00 |
May | 3415.73 | 11-MAY-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 | 0.00 |
June | 3328.02 | 14-JUN-08:61 | 252.00 | 329.15 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 | 0.00 |
July | 3081.72 | 25-JUL-08:61 | 252.00 | 329.15 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 0.00 |
August | 3083.23 | 26-AUG-08:61 | 378.00 | 418.92 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.55 | 0.00 |
September | 3172.58 | 24-SEP-18:01 | 819.00 | 748.06 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.54 |
October | 3266.24 | 31-OCT-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 |
November | 3237.89 | 08-NOV-16:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 | 0.00 |
December | 2997.77 | 23-DEC-16:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2992.41 | 252.00 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3415.73 | 819.00 | 748.06 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 | 8.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2913.95 | 30-JAN-16:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.26 |
February | 3233.15 | 20-FEB-16:01 | 378.00 | 246.84 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 | 0.00 |
March | 3254.70 | 21-MAR-15:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 3.03 | 0.00 |
April | 3569.26 | 17-APR-18:01 | 1386.00 | 951.00 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 |
May | 3627.50 | 20-MAY-08:51 | 540.00 | 598.38 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 4.29 | 0.00 |
June | 3742.47 | 14-JUN-08:11 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 | 0.00 |
July | 3156.77 | 25-JUL-06:51 | 774.00 | 598.38 | 2370.31 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 0.00 |
August | 3280.61 | 26-AUG-08:11 | 540.00 | 598.38 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 4.65 | 0.00 |
September | 3252.92 | 29-SEP-21:51 | 1440.00 | 572.74 | 737.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 |
October | 3198.35 | 31-OCT-15:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 |
November | 3180.99 | 08-NOV-16:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 | 0.00 |
December | 2919.26 | 16-DEC-16:01 | 378.00 | 246.84 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2913.95 | 360.00 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3742.47 | 1440.00 | 951.00 | 2370.31 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 | 17.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 533.80 | 12-JAN-14:25 | 0.00 | 37.61 | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.44 |
February | 500.10 | 07-FEB-13:40 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.70 |
March | 395.61 | 07-MAR-13:40 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.23 |
April | 370.02 | 03-APR-14:00 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
May | 313.25 | 31-MAY-20:20 | 0.00 | 59.77 | 180.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 | 0.00 |
June | 359.87 | 15-JUN-17:17 | 0.00 | 135.00 | 394.73 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 | 0.00 |
July | 364.04 | 26-JUL-17:20 | 0.00 | 135.00 | 394.73 | 0.00 | 0.00 | 0.00 | 0.00 | 3.37 | 0.00 |
August | 418.97 | 27-AUG-13:50 | 0.00 | 22.16 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 3.07 | 0.00 |
September | 526.76 | 19-SEP-13:30 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 | 0.00 |
October | 604.76 | 22-OCT-13:15 | 0.00 | 44.33 | 149.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
November | 571.15 | 09-NOV-13:50 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.44 |
December | 462.56 | 16-DEC-13:40 | 0.00 | 22.16 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 313.25 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 604.76 | 0.00 | 135.00 | 394.73 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 | 5.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 981.85 | 03-JAN-16:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
February | 1091.15 | 20-FEB-16:01 | 378.00 | 155.19 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 | 0.00 |
March | 1134.24 | 22-MAR-15:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 | 0.00 |
April | 1182.82 | 21-APR-18:01 | 970.20 | 418.53 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.87 | 0.00 |
May | 1228.33 | 20-MAY-08:51 | 540.00 | 376.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.35 | 0.00 |
June | 1251.55 | 14-JUN-08:11 | 360.00 | 295.59 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 1.75 | 0.00 |
July | 1116.57 | 06-JUL-08:61 | 360.00 | 295.59 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 |
August | 1120.88 | 26-AUG-08:11 | 540.00 | 376.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 | 0.00 |
September | 1110.44 | 29-SEP-21:51 | 1440.00 | 360.09 | 722.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 |
October | 1137.40 | 30-OCT-15:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 | 0.00 |
November | 1099.71 | 09-NOV-16:02 | 583.20 | 112.86 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 | 0.00 |
December | 945.46 | 16-DEC-09:01 | 378.00 | 263.34 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 945.46 | 360.00 | 112.86 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1251.55 | 1440.00 | 418.53 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2.87 | 5.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2638.98 | 31-JAN-09:01 | 252.00 | 329.15 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.04 |
February | 2893.31 | 20-FEB-16:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 |
March | 2920.93 | 21-MAR-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 2.90 | 0.00 |
April | 3010.60 | 21-APR-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 | 0.00 |
May | 3001.59 | 11-MAY-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 0.00 |
June | 3045.69 | 14-JUN-08:61 | 252.00 | 329.15 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 7.03 | 0.00 |
July | 2780.98 | 12-JUL-08:61 | 252.00 | 329.15 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 0.00 |
August | 2757.89 | 03-AUG-08:61 | 360.00 | 470.21 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 4.89 | 0.00 |
September | 2808.97 | 24-SEP-18:01 | 819.00 | 748.06 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 |
October | 2865.50 | 31-OCT-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.51 |
November | 2881.83 | 08-NOV-16:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 |
December | 2649.84 | 23-DEC-16:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2638.98 | 252.00 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3045.69 | 819.00 | 748.06 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 | 18.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2499.77 | 31-JAN-09:01 | 252.00 | 329.11 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.15 |
February | 2834.05 | 20-FEB-16:01 | 378.00 | 246.84 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 | 0.00 |
March | 2867.37 | 21-MAR-15:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 3.08 | 0.00 |
April | 3352.60 | 21-APR-08:51 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.12 |
May | 3535.28 | 20-MAY-08:51 | 540.00 | 598.38 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2.01 | 0.00 |
June | 3538.68 | 14-JUN-07:52 | 464.40 | 282.09 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | 0.00 |
July | 3181.50 | 24-JUL-08:61 | 252.00 | 329.11 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.14 |
August | 3222.60 | 26-AUG-08:11 | 540.00 | 598.38 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 | 0.00 |
September | 3137.93 | 19-SEP-08:51 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 | 0.00 |
October | 3034.61 | 05-OCT-08:51 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
November | 2937.53 | 09-NOV-09:51 | 324.00 | 423.14 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.05 |
December | 2551.11 | 16-DEC-09:01 | 378.00 | 418.87 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2499.77 | 252.00 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3538.68 | 680.40 | 598.38 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 3.08 | 21.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1376.85 | 01-JAN-11:33 | 2263.36 | 1044.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.19 |
February | 1458.29 | 20-FEB-11:33 | 2263.36 | 1044.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 |
March | 1512.79 | 16-MAR-18:09 | 12322.72 | 6496.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.13 |
April | 1771.84 | 30-APR-10:33 | 2263.36 | 1044.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.71 | 0.00 |
May | 1878.28 | 31-MAY-18:05 | 10562.33 | 5568.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.31 | 0.00 |
June | 2664.22 | 15-JUN-18:25 | 3520.78 | 1856.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.75 | 0.00 |
July | 2481.95 | 26-JUL-18:15 | 3520.78 | 1856.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.82 | 0.00 |
August | 2465.52 | 07-AUG-18:15 | 3520.78 | 1856.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.41 | 0.00 |
September | 2196.25 | 20-SEP-18:03 | 10562.33 | 5568.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 | 0.00 |
October | 1866.40 | 05-OCT-10:33 | 1508.90 | 870.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 | 0.00 |
November | 1597.51 | 10-NOV-11:33 | 1508.90 | 870.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.59 |
December | 1308.89 | 10-DEC-11:33 | 2263.36 | 1044.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1308.89 | 1508.90 | 870.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2664.22 | 12322.72 | 6496.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.75 | 15.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3176.36 | 30-JAN-16:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.54 |
February | 3512.32 | 20-FEB-16:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 | 0.00 |
March | 3527.18 | 21-MAR-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 0.00 |
April | 3640.81 | 15-APR-15:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 6.63 | 0.00 |
May | 3647.81 | 17-MAY-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 9.77 | 0.00 |
June | 3526.08 | 14-JUN-08:61 | 252.00 | 329.15 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 7.64 | 0.00 |
July | 3282.81 | 26-JUL-08:61 | 252.00 | 329.15 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 0.00 |
August | 3249.99 | 07-AUG-08:61 | 252.00 | 329.15 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 8.77 | 0.00 |
September | 3367.68 | 24-SEP-18:01 | 819.00 | 748.06 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 |
October | 3470.73 | 31-OCT-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.64 |
November | 3440.18 | 08-NOV-16:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 | 0.00 |
December | 3182.89 | 23-DEC-16:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3176.36 | 252.00 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3647.81 | 819.00 | 748.06 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 9.77 | 10.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3007.63 | 30-JAN-16:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.73 |
February | 3433.13 | 20-FEB-16:01 | 378.00 | 246.84 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 |
March | 3454.61 | 21-MAR-15:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 3.02 | 0.00 |
April | 3796.42 | 17-APR-18:01 | 1386.00 | 951.00 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.04 |
May | 3853.52 | 20-MAY-08:51 | 540.00 | 598.38 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 4.27 | 0.00 |
June | 3956.55 | 14-JUN-08:11 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 0.00 |
July | 3312.48 | 25-JUL-06:51 | 774.00 | 598.38 | 2370.31 | 0.00 | 0.00 | 0.00 | 0.00 | 3.74 | 0.00 |
August | 3387.72 | 26-AUG-08:11 | 540.00 | 598.38 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 0.00 |
September | 3422.62 | 29-SEP-21:51 | 1440.00 | 572.74 | 737.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 |
October | 3388.67 | 31-OCT-15:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 |
November | 3348.60 | 07-NOV-16:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 |
December | 3095.53 | 16-DEC-16:01 | 378.00 | 246.84 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3007.63 | 360.00 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3956.55 | 1440.00 | 951.00 | 2370.31 | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 17.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1634.58 | 07-JAN-16:01 | 378.00 | 155.19 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.85 |
February | 1787.28 | 20-FEB-16:01 | 378.00 | 155.19 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 | 0.00 |
March | 1796.74 | 14-MAR-15:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 | 0.00 |
April | 1824.60 | 14-APR-15:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 3.79 | 0.00 |
May | 1779.97 | 05-MAY-15:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 1.86 | 0.00 |
June | 1791.79 | 16-JUN-08:61 | 252.00 | 206.91 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 4.64 | 0.00 |
July | 1661.81 | 11-JUL-08:61 | 252.00 | 206.91 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 3.70 | 0.00 |
August | 1661.26 | 26-AUG-08:61 | 378.00 | 263.34 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 3.21 | 0.00 |
September | 1707.33 | 24-SEP-18:01 | 819.00 | 470.26 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 |
October | 1774.05 | 31-OCT-15:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 |
November | 1747.97 | 14-NOV-16:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 |
December | 1640.00 | 23-DEC-16:01 | 378.00 | 155.19 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1634.58 | 252.00 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1824.60 | 819.00 | 470.26 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 4.64 | 5.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17842.35 | 03-JAN-22:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.61 |
February | 18954.33 | 07-FEB-23:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.29 |
March | 19831.44 | 15-MAR-21:53 | 161932.61 | 9947.24 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.16 |
April | 21799.22 | 19-APR-22:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 11.06 | 0.00 |
May | 22944.48 | 31-MAY-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 13.78 | 0.00 |
June | 23585.63 | 15-JUN-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 27.12 | 0.00 |
July | 23341.47 | 26-JUL-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 15.11 | 0.00 |
August | 23503.22 | 07-AUG-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 23.70 | 0.00 |
September | 22331.98 | 22-SEP-22:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 3.25 | 0.00 |
October | 21798.04 | 05-OCT-21:52 | 242898.91 | 14920.86 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 |
November | 19765.54 | 09-NOV-22:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.40 |
December | 17763.15 | 15-DEC-23:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17763.15 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23585.63 | 242898.91 | 14920.86 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 27.12 | 43.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19667.04 | 03-JAN-22:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.62 |
February | 20638.00 | 06-FEB-22:30 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.18 |
March | 21470.14 | 15-MAR-21:53 | 161932.61 | 9947.24 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.16 |
April | 23209.20 | 19-APR-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 13.64 | 0.00 |
May | 24140.16 | 31-MAY-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 | 0.00 |
June | 24773.83 | 15-JUN-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 27.12 | 0.00 |
July | 24519.60 | 26-JUL-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 15.11 | 0.00 |
August | 24670.49 | 07-AUG-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 23.70 | 0.00 |
September | 23460.86 | 22-SEP-22:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 3.25 | 0.00 |
October | 22944.58 | 05-OCT-21:52 | 242898.91 | 14920.86 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 |
November | 21301.02 | 09-NOV-22:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.40 |
December | 19652.19 | 15-DEC-23:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19652.19 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24773.83 | 242898.91 | 14920.86 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 27.12 | 43.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25952.94 | 01-JAN-11:50 | 800.57 | 327.25 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 33.53 |
February | 27023.04 | 20-FEB-11:50 | 800.57 | 327.25 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 11.05 |
March | 27214.79 | 19-MAR-10:33 | 2401.70 | 981.75 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 17.75 |
April | 28924.60 | 30-APR-10:50 | 800.57 | 327.25 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 1.44 | 0.00 |
May | 29068.83 | 21-MAY-10:33 | 2401.70 | 981.75 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 17.07 | 0.00 |
June | 29634.37 | 18-JUN-10:37 | 2401.70 | 981.75 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 26.35 | 0.00 |
July | 29786.80 | 02-JUL-10:37 | 2401.70 | 981.75 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 25.57 | 0.00 |
August | 29717.66 | 06-AUG-10:33 | 2401.70 | 981.75 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 23.99 | 0.00 |
September | 29277.16 | 17-SEP-10:50 | 800.57 | 327.25 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 18.90 | 0.00 |
October | 28753.75 | 05-OCT-10:33 | 1601.14 | 818.12 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 11.23 | 0.00 |
November | 26850.21 | 10-NOV-11:50 | 533.71 | 272.71 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 10.02 |
December | 25931.81 | 10-DEC-11:50 | 800.57 | 327.25 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 25.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 25931.81 | 533.71 | 272.71 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29786.80 | 2401.70 | 981.75 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 26.35 | 33.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3191.43 | 01-JAN-11:33 | 2395.44 | 1104.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.69 |
February | 3515.70 | 20-FEB-11:33 | 2395.44 | 1104.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.28 |
March | 3539.27 | 16-MAR-17:12 | 5323.20 | 2946.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.35 |
April | 4302.16 | 30-APR-10:33 | 2395.44 | 1104.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 | 0.00 |
May | 5350.82 | 30-MAY-15:02 | 7984.80 | 1841.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.34 | 0.00 |
June | 6205.02 | 17-JUN-17:13 | 4790.88 | 2209.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.48 | 0.00 |
July | 6630.49 | 03-JUL-12:50 | 532.32 | 306.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.79 | 0.00 |
August | 6504.56 | 07-AUG-15:03 | 7984.80 | 1841.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.42 | 0.00 |
September | 5989.78 | 21-SEP-14:10 | 798.48 | 306.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.69 | 0.00 |
October | 5501.68 | 05-OCT-15:03 | 7984.80 | 1841.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.39 | 0.00 |
November | 3821.37 | 10-NOV-11:33 | 1596.96 | 920.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 |
December | 3115.68 | 16-DEC-11:33 | 2395.44 | 920.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3115.68 | 532.32 | 306.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6630.49 | 7984.80 | 2946.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.79 | 30.02 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.388564E+12 | 263392.52 | 03-JAN-19:10 | 0.399311E+12 | 344259.27 | 27-JAN-19:10 |
February | 0.361798E+12 | 285956.54 | 06-FEB-20:19 | 0.324833E+12 | 340066.17 | 01-FEB-18:00 |
March | 0.410831E+12 | 301458.63 | 15-MAR-19:10 | 0.332504E+12 | 313577.86 | 01-MAR-17:00 |
April | 0.465456E+12 | 361641.26 | 19-APR-19:19 | 0.254607E+12 | 239372.56 | 10-APR-20:00 |
May | 0.546975E+12 | 385879.42 | 19-MAY-19:19 | 0.225284E+12 | 161521.18 | 01-MAY-17:40 |
June | 0.595503E+12 | 412066.93 | 05-JUN-19:10 | 0.205944E+12 | 147023.07 | 01-JUN-17:19 |
July | 0.643709E+12 | 410192.52 | 25-JUL-19:10 | 0.206016E+12 | 136892.76 | 01-JUL-17:49 |
August | 0.607279E+12 | 405203.74 | 04-AUG-19:19 | 0.208683E+12 | 139711.53 | 31-AUG-17:00 |
September | 0.550973E+12 | 386051.52 | 22-SEP-19:19 | 0.210347E+12 | 150547.22 | 30-SEP-05:00 |
October | 0.479037E+12 | 379433.29 | 04-OCT-19:19 | 0.250809E+12 | 196612.80 | 25-OCT-06:10 |
November | 0.397614E+12 | 308401.73 | 09-NOV-20:19 | 0.324306E+12 | 318347.90 | 27-NOV-17:00 |
December | 0.390371E+12 | 261994.86 | 15-DEC-20:30 | 0.380566E+12 | 343072.35 | 28-DEC-18:00 |
Annual Sum or Average | 0.583811E+13 | 0.332321E+13 | ||||
Minimum of Months | 0.361798E+12 | 261994.86 | 0.205944E+12 | 136892.76 | ||
Maximum of Months | 0.643709E+12 | 412066.93 | 0.399311E+12 | 344259.27 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.466647E+11 | 0.171374E+11 | 0.146779E+12 | 0.544793E+11 | 0.420873E+11 | 0.888943E+10 | 0.00 | 0.151494E+11 | 0.00 | 0.00 | 0.103085E+11 | 0.433750E+11 | 0.00 |
February | 0.419748E+11 | 0.146606E+11 | 0.132565E+12 | 0.492071E+11 | 0.387044E+11 | 0.872334E+10 | 0.00 | 0.264629E+11 | 0.00 | 0.00 | 0.736544E+10 | 0.388029E+11 | 0.00 |
March | 0.462677E+11 | 0.150668E+11 | 0.146789E+12 | 0.544810E+11 | 0.436041E+11 | 0.101187E+11 | 0.00 | 0.421559E+11 | 0.00 | 0.00 | 0.620587E+10 | 0.424525E+11 | 0.00 |
April | 0.444543E+11 | 0.134090E+11 | 0.142011E+12 | 0.527213E+11 | 0.468564E+11 | 0.102236E+11 | 0.00 | 0.104373E+12 | 0.00 | 0.00 | 0.832685E+10 | 0.395030E+11 | 0.00 |
May | 0.458093E+11 | 0.128497E+11 | 0.146789E+12 | 0.544797E+11 | 0.529835E+11 | 0.108650E+11 | 0.00 | 0.165622E+12 | 0.00 | 0.00 | 0.140061E+11 | 0.398422E+11 | 0.00 |
June | 0.442090E+11 | 0.119309E+11 | 0.142058E+12 | 0.527230E+11 | 0.564556E+11 | 0.109584E+11 | 0.00 | 0.216750E+12 | 0.00 | 0.00 | 0.189149E+11 | 0.378724E+11 | 0.00 |
July | 0.456757E+11 | 0.125501E+11 | 0.146742E+12 | 0.544778E+11 | 0.576174E+11 | 0.115092E+11 | 0.00 | 0.251897E+12 | 0.00 | 0.00 | 0.208615E+11 | 0.386140E+11 | 0.00 |
August | 0.459513E+11 | 0.134090E+11 | 0.146800E+12 | 0.544809E+11 | 0.575783E+11 | 0.113172E+11 | 0.00 | 0.217768E+12 | 0.00 | 0.00 | 0.171793E+11 | 0.390229E+11 | 0.00 |
September | 0.446694E+11 | 0.140614E+11 | 0.142022E+12 | 0.527215E+11 | 0.552634E+11 | 0.107713E+11 | 0.00 | 0.177838E+12 | 0.00 | 0.00 | 0.118485E+11 | 0.381328E+11 | 0.00 |
October | 0.464653E+11 | 0.157525E+11 | 0.146768E+12 | 0.544791E+11 | 0.521641E+11 | 0.106473E+11 | 0.00 | 0.103205E+12 | 0.00 | 0.00 | 0.543260E+10 | 0.403823E+11 | 0.00 |
November | 0.450425E+11 | 0.162652E+11 | 0.142074E+12 | 0.527223E+11 | 0.448182E+11 | 0.922194E+10 | 0.00 | 0.351137E+11 | 0.00 | 0.00 | 0.747826E+10 | 0.413046E+11 | 0.00 |
December | 0.466005E+11 | 0.173904E+11 | 0.146742E+12 | 0.544784E+11 | 0.423708E+11 | 0.888104E+10 | 0.00 | 0.125065E+11 | 0.00 | 0.00 | 0.136384E+11 | 0.440750E+11 | 0.00 |
Annual Sum or Average | 0.543784E+12 | 0.174483E+12 | 0.172814E+13 | 0.641451E+12 | 0.590504E+12 | 0.122126E+12 | 0.00 | 0.136884E+13 | 0.00 | 0.00 | 0.141566E+12 | 0.483379E+12 | 0.00 |
Minimum of Months | 0.419748E+11 | 0.119309E+11 | 0.132565E+12 | 0.492071E+11 | 0.387044E+11 | 0.872334E+10 | 0.00 | 0.125065E+11 | 0.00 | 0.00 | 0.543260E+10 | 0.378724E+11 | 0.00 |
Maximum of Months | 0.466647E+11 | 0.173904E+11 | 0.146800E+12 | 0.544810E+11 | 0.576174E+11 | 0.115092E+11 | 0.00 | 0.251897E+12 | 0.00 | 0.00 | 0.208615E+11 | 0.440750E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.140728E+12 | 0.00 | 0.106664E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.932011E+11 | 0.00 | 0.944279E+11 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.820100E+11 | 0.00 | 0.984703E+11 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.262909E+11 | 0.00 | 0.813604E+11 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.204328E+10 | 0.00 | 0.712624E+11 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 59076437.80 | 0.00 | 0.587715E+11 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 49160381.93 | 0.00 | 0.541469E+11 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 86309313.79 | 0.00 | 0.565583E+11 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.277005E+10 | 0.00 | 0.606064E+11 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.241368E+11 | 0.00 | 0.747688E+11 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.868040E+11 | 0.00 | 0.904111E+11 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.122815E+12 | 0.00 | 0.105931E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.580994E+12 | 0.00 | 0.953380E+12 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 49160381.93 | 0.00 | 0.541469E+11 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.140728E+12 | 0.00 | 0.106664E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 45424.10 | 02-JAN-20:10 | 11096.45 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 39153.57 | 02-JAN-07:19 | 28517.77 | 12-JAN-22:10 | 4325.11 | 28-JAN-10:39 | 0.00 | 01-JAN-00:10 |
February | 45424.10 | 01-FEB-20:10 | 11096.45 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 39153.57 | 01-FEB-07:19 | 31558.55 | 21-FEB-22:10 | 4327.78 | 05-FEB-09:09 | 0.00 | 01-FEB-00:10 |
March | 45424.10 | 01-MAR-20:10 | 11096.45 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 39153.57 | 13-MAR-06:19 | 31909.85 | 07-MAR-22:10 | 4302.45 | 24-MAR-08:09 | 0.00 | 01-MAR-00:10 |
April | 45424.10 | 03-APR-19:10 | 11096.45 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 39153.17 | 04-APR-06:19 | 36953.61 | 19-APR-21:19 | 5044.10 | 28-APR-20:10 | 0.00 | 01-APR-00:10 |
May | 45424.10 | 01-MAY-19:10 | 11096.45 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 39153.08 | 03-MAY-06:19 | 40229.11 | 31-MAY-21:10 | 5524.78 | 19-MAY-18:10 | 0.00 | 01-MAY-00:10 |
June | 45424.10 | 01-JUN-19:10 | 11096.45 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 39151.94 | 28-JUN-06:19 | 44390.55 | 15-JUN-21:10 | 5961.89 | 05-JUN-18:19 | 0.00 | 01-JUN-00:10 |
July | 45424.10 | 03-JUL-19:19 | 11096.45 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 39152.30 | 19-JUL-06:19 | 43573.11 | 26-JUL-21:10 | 5879.17 | 21-JUL-20:00 | 0.00 | 01-JUL-00:10 |
August | 45424.10 | 01-AUG-19:10 | 11096.45 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 39153.17 | 14-AUG-06:19 | 47073.09 | 07-AUG-21:10 | 5456.07 | 22-AUG-18:19 | 0.00 | 01-AUG-00:10 |
September | 45424.10 | 01-SEP-19:10 | 11096.45 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 39153.49 | 28-SEP-06:19 | 46567.78 | 21-SEP-21:19 | 5274.75 | 27-SEP-18:10 | 0.00 | 01-SEP-00:10 |
October | 45424.10 | 02-OCT-19:10 | 11096.45 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 39153.57 | 02-OCT-06:19 | 44654.07 | 05-OCT-21:00 | 5303.74 | 01-OCT-19:30 | 0.00 | 01-OCT-00:10 |
November | 45424.10 | 01-NOV-19:10 | 11096.45 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 39153.57 | 01-NOV-06:19 | 37562.03 | 09-NOV-22:10 | 4337.50 | 25-NOV-09:09 | 0.00 | 01-NOV-00:10 |
December | 45424.10 | 01-DEC-20:10 | 11096.45 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 39153.57 | 11-DEC-07:19 | 29712.34 | 15-DEC-22:10 | 4336.55 | 31-DEC-10:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 45424.10 | 11096.45 | 88863.15 | 39151.94 | 28517.77 | 4302.45 | 0.00 | |||||||
Maximum of Months | 45424.10 | 11096.45 | 88863.15 | 39153.57 | 47073.09 | 5961.89 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 50969.04 | 03-JAN-16:10 | 0.00 | 0.00 | 9938.94 | 01-JAN-07:10 | 41320.58 | 03-JAN-19:30 | 0.00 |
February | 72771.29 | 20-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:40 | 41283.04 | 23-FEB-19:19 | 0.00 |
March | 75645.36 | 22-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-01:19 | 42332.83 | 29-MAR-18:40 | 0.00 |
April | 109167.85 | 21-APR-15:09 | 0.00 | 0.00 | 9938.94 | 01-APR-12:09 | 43186.06 | 26-APR-20:00 | 0.00 |
May | 130809.08 | 19-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 02-MAY-15:20 | 43790.59 | 31-MAY-20:00 | 0.00 |
June | 157879.72 | 14-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-00:10 | 43092.07 | 27-JUN-20:30 | 0.00 |
July | 156030.80 | 26-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUL-00:10 | 42560.84 | 28-JUL-20:49 | 0.00 |
August | 146946.74 | 04-AUG-18:10 | 0.00 | 0.00 | 9938.94 | 01-AUG-00:10 | 42988.45 | 11-AUG-20:49 | 0.00 |
September | 130885.70 | 20-SEP-15:20 | 0.00 | 0.00 | 9938.94 | 01-SEP-08:30 | 43367.39 | 07-SEP-20:30 | 0.00 |
October | 125107.69 | 04-OCT-18:10 | 0.00 | 0.00 | 9938.94 | 01-OCT-09:50 | 44361.98 | 06-OCT-20:49 | 0.00 |
November | 77898.88 | 03-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 03-NOV-15:39 | 43718.54 | 01-NOV-18:40 | 0.00 |
December | 30543.20 | 23-DEC-14:00 | 0.00 | 0.00 | 9938.94 | 01-DEC-03:30 | 42128.03 | 05-DEC-19:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 30543.20 | 0.00 | 0.00 | 9938.94 | 41283.04 | 0.00 | |||
Maximum of Months | 157879.72 | 0.00 | 0.00 | 9938.94 | 44361.98 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 263392.52 | 03-JAN-19:10 | 40391.24 | 78653.57 | 11096.45 | 31357.01 | 21713.50 | 3878.57 | 0.00 | 34494.00 | 0.00 |
February | 285956.54 | 06-FEB-20:19 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 24629.88 | 3881.53 | 0.00 | 39657.91 | 0.00 |
March | 301458.63 | 15-MAR-19:10 | 45424.10 | 87982.85 | 11096.45 | 31569.36 | 24293.58 | 3929.57 | 0.00 | 54469.12 | 0.00 |
April | 361641.26 | 19-APR-19:19 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 29491.16 | 4253.44 | 0.00 | 100260.40 | 0.00 |
May | 385879.42 | 19-MAY-19:19 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 34236.13 | 4371.38 | 0.00 | 120163.59 | 0.00 |
June | 412066.93 | 05-JUN-19:10 | 45424.10 | 87982.85 | 11096.45 | 31568.43 | 33311.86 | 5844.72 | 0.00 | 145562.25 | 0.00 |
July | 410192.52 | 25-JUL-19:10 | 45424.10 | 87982.85 | 11096.45 | 31568.34 | 35343.17 | 4775.68 | 0.00 | 143628.06 | 0.00 |
August | 405203.74 | 04-AUG-19:19 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 37906.82 | 4674.33 | 0.00 | 135968.06 | 0.00 |
September | 386051.52 | 22-SEP-19:19 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 37833.54 | 4737.79 | 0.00 | 116610.01 | 0.00 |
October | 379433.29 | 04-OCT-19:19 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 34063.08 | 4670.47 | 0.00 | 112782.99 | 0.00 |
November | 308401.73 | 09-NOV-20:19 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 30062.39 | 3955.38 | 0.00 | 54691.45 | 0.00 |
December | 261994.86 | 15-DEC-20:30 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 24200.61 | 3845.41 | 0.00 | 15509.71 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 261994.86 | 40391.24 | 78653.57 | 11096.45 | 31357.01 | 21713.50 | 3845.41 | 0.00 | 15509.71 | 0.00 | |
Maximum of Months | 412066.93 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 37906.82 | 5844.72 | 0.00 | 145562.25 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 174026.15 | 29-JAN-01:10 | 0.00 | 99007.92 | 30-JAN-19:40 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 153171.56 | 17-FEB-23:00 | 0.00 | 96337.17 | 01-FEB-18:49 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 161392.26 | 25-MAR-01:30 | 0.00 | 91186.42 | 01-MAR-23:30 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 147605.29 | 11-APR-02:39 | 0.00 | 73705.33 | 01-APR-18:19 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 82356.53 | 02-MAY-04:00 | 0.00 | 57273.07 | 01-MAY-18:00 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 6257.71 | 09-JUN-08:09 | 0.00 | 43057.51 | 01-JUN-19:00 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 4229.51 | 25-JUL-08:09 | 0.00 | 32644.54 | 01-JUL-22:40 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 4225.72 | 17-AUG-08:00 | 0.00 | 35603.16 | 31-AUG-19:19 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 92919.31 | 30-SEP-05:00 | 0.00 | 45051.68 | 30-SEP-20:00 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 118526.28 | 25-OCT-05:49 | 0.00 | 62272.84 | 31-OCT-16:00 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 151173.59 | 27-NOV-16:10 | 0.00 | 85721.86 | 30-NOV-17:30 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 173454.74 | 20-DEC-09:09 | 0.00 | 100722.14 | 30-DEC-19:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 4225.72 | 0.00 | 32644.54 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 174026.15 | 0.00 | 100722.14 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.77 | 0.17 | 21.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.73 | 1.67 | 21.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.82 | 5.17 | 21.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.71 | 1.67 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.75 | 2.83 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.80 | 2.33 | 21.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.75 | 1.33 | 21.75 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.75 | 0.17 | 21.75 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 15.33 | 21.77 | 15.33 | 21.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.82 | 5.17 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.86 | 0.50 | 21.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.73 | 2.00 | 21.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 21.84 | 7.67 | 21.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.72 | 3.00 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.72 | 2.33 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.71 | 0.67 | 21.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.33 | 21.78 | 16.33 | 21.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 21.86 | 7.67 | 21.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.76 | 0.17 | 21.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.71 | 1.50 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.75 | 3.17 | 21.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.77 | 2.00 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.77 | 1.33 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.72 | 0.67 | 21.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.83 | 21.75 | 8.83 | 21.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.77 | 3.17 | 21.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.73 | 0.67 | 21.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.88 | 0.33 | 21.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.79 | 2.17 | 21.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.68 | 0.50 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.70 | 0.50 | 21.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.87 | 0.17 | 21.87 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.50 | 21.76 | 4.50 | 21.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.88 | 2.17 | 21.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 22.11 | 2.33 | 22.11 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 22.25 | 6.00 | 22.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 22.12 | 10.83 | 22.12 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 22.15 | 7.00 | 22.15 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 22.12 | 6.17 | 22.12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 22.17 | 6.33 | 22.17 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.09 | 1.33 | 22.09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.97 | 0.17 | 21.97 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 40.17 | 22.15 | 40.17 | 22.15 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 22.25 | 10.83 | 22.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.89 | 0.17 | 21.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.75 | 1.67 | 21.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 21.86 | 7.50 | 21.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.77 | 2.50 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.79 | 3.17 | 21.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.81 | 3.17 | 21.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.81 | 0.83 | 21.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 19.17 | 21.82 | 19.17 | 21.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 21.89 | 7.50 | 21.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.82 | 0.67 | 21.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.77 | 2.17 | 21.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 21.86 | 12.50 | 21.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.75 | 4.00 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.77 | 2.33 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.73 | 0.67 | 21.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 22.50 | 21.82 | 22.50 | 21.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 21.86 | 12.50 | 21.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.81 | 1.33 | 21.81 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.85 | 0.50 | 21.85 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.77 | 0.67 | 21.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.73 | 1.83 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.76 | 4.33 | 21.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.89 | 5.17 | 21.89 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.93 | 2.00 | 21.93 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.87 | 0.67 | 21.87 |
Annual Sum or Average | 0.00 | 0.00 | 17.33 | 21.82 | 17.33 | 21.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.93 | 5.17 | 21.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 742.67 | 23.40 | 0.00 | 23.40 | 0.00 | 23.40 |
February | 672.00 | 22.26 | 0.00 | 22.26 | 0.00 | 22.26 |
March | 744.00 | 21.40 | 37.50 | 21.38 | 37.50 | 21.37 |
April | 720.00 | 21.46 | 1.17 | 21.46 | 1.17 | 21.46 |
May | 744.00 | 21.79 | 11.17 | 21.79 | 11.17 | 21.80 |
June | 720.00 | 22.14 | 61.83 | 22.16 | 61.83 | 22.17 |
July | 665.83 | 23.23 | 421.67 | 23.32 | 391.67 | 23.35 |
August | 297.83 | 23.88 | 500.50 | 23.90 | 263.17 | 23.91 |
September | 237.50 | 23.99 | 482.33 | 23.97 | 223.17 | 23.97 |
October | 177.00 | 23.95 | 287.67 | 23.96 | 61.83 | 23.96 |
November | 495.17 | 23.95 | 10.67 | 23.95 | 0.00 | 23.95 |
December | 646.50 | 23.89 | 0.00 | 23.89 | 0.00 | 23.89 |
Annual Sum or Average | 6862.50 | 22.69 | 1814.50 | 22.90 | 1051.50 | 22.97 |
Minimum of Months | 177.00 | 21.40 | 0.00 | 21.38 | 0.00 | 21.37 |
Maximum of Months | 744.00 | 23.99 | 500.50 | 23.97 | 391.67 | 23.97 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 642.17 | 21.67 | 38.17 | 21.73 | 17.50 | 21.71 |
February | 580.83 | 21.82 | 15.00 | 21.81 | 11.67 | 21.80 |
March | 675.17 | 21.93 | 18.33 | 21.90 | 18.33 | 21.88 |
April | 566.83 | 22.48 | 27.33 | 22.55 | 0.17 | 22.54 |
May | 394.50 | 22.79 | 157.33 | 23.08 | 9.17 | 23.08 |
June | 125.00 | 23.20 | 482.33 | 23.68 | 44.17 | 23.66 |
July | 332.50 | 23.52 | 735.67 | 23.65 | 331.33 | 23.62 |
August | 240.83 | 23.30 | 649.33 | 23.60 | 201.33 | 23.56 |
September | 290.17 | 23.22 | 577.00 | 23.57 | 202.50 | 23.54 |
October | 391.67 | 22.50 | 287.00 | 23.07 | 45.50 | 23.09 |
November | 543.17 | 21.96 | 78.17 | 22.13 | 18.33 | 22.09 |
December | 657.33 | 21.59 | 51.50 | 21.55 | 51.50 | 21.51 |
Annual Sum or Average | 5440.17 | 22.27 | 3117.17 | 22.77 | 951.50 | 22.81 |
Minimum of Months | 125.00 | 21.59 | 15.00 | 21.55 | 0.17 | 21.51 |
Maximum of Months | 675.17 | 23.52 | 735.67 | 23.68 | 331.33 | 23.66 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 740.17 | 22.74 | 0.00 | 22.74 | 0.00 | 22.74 |
February | 668.67 | 22.88 | 0.00 | 22.88 | 0.00 | 22.88 |
March | 741.83 | 22.98 | 0.00 | 22.98 | 0.00 | 22.98 |
April | 584.33 | 23.33 | 7.50 | 23.34 | 0.00 | 23.34 |
May | 328.00 | 23.46 | 146.67 | 23.60 | 21.17 | 23.61 |
June | 157.00 | 23.75 | 392.17 | 23.88 | 70.17 | 23.89 |
July | 388.50 | 23.93 | 713.00 | 23.89 | 384.33 | 23.90 |
August | 270.17 | 23.88 | 644.83 | 23.87 | 266.33 | 23.88 |
September | 275.67 | 23.87 | 511.33 | 23.87 | 240.00 | 23.89 |
October | 344.83 | 23.40 | 213.33 | 23.57 | 78.00 | 23.59 |
November | 654.17 | 23.11 | 2.50 | 23.12 | 0.00 | 23.12 |
December | 744.00 | 22.61 | 0.00 | 22.61 | 0.00 | 22.61 |
Annual Sum or Average | 5897.33 | 23.16 | 2631.33 | 23.38 | 1060.00 | 23.44 |
Minimum of Months | 157.00 | 22.61 | 0.00 | 22.61 | 0.00 | 22.61 |
Maximum of Months | 744.00 | 23.93 | 713.00 | 23.89 | 384.33 | 23.90 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.37 | 25.00 | 21.36 | 25.00 | 21.35 |
February | 672.00 | 21.57 | 23.83 | 21.55 | 23.83 | 21.53 |
March | 744.00 | 21.84 | 10.17 | 21.83 | 10.17 | 21.82 |
April | 720.00 | 22.69 | 0.00 | 22.69 | 0.00 | 22.69 |
May | 567.00 | 23.35 | 35.00 | 23.38 | 0.00 | 23.38 |
June | 163.17 | 23.78 | 219.83 | 23.87 | 10.17 | 23.87 |
July | 205.17 | 23.90 | 685.00 | 23.91 | 200.50 | 23.91 |
August | 160.00 | 23.64 | 455.67 | 23.81 | 108.83 | 23.80 |
September | 348.83 | 23.52 | 311.50 | 23.65 | 129.67 | 23.67 |
October | 656.33 | 22.87 | 43.00 | 22.92 | 10.33 | 22.93 |
November | 720.00 | 22.01 | 0.00 | 22.01 | 0.00 | 22.01 |
December | 744.00 | 21.29 | 43.00 | 21.27 | 43.00 | 21.26 |
Annual Sum or Average | 6444.50 | 22.30 | 1852.00 | 22.61 | 561.50 | 22.66 |
Minimum of Months | 160.00 | 21.29 | 0.00 | 21.27 | 0.00 | 21.26 |
Maximum of Months | 744.00 | 23.90 | 685.00 | 23.91 | 200.50 | 23.91 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.24 | 29.50 | 21.23 | 29.50 | 21.22 |
February | 672.00 | 21.44 | 31.67 | 21.42 | 31.67 | 21.40 |
March | 744.00 | 21.68 | 14.50 | 21.67 | 14.50 | 21.66 |
April | 720.00 | 22.54 | 0.00 | 22.54 | 0.00 | 22.54 |
May | 624.33 | 23.25 | 11.50 | 23.26 | 1.33 | 23.26 |
June | 183.50 | 23.74 | 173.83 | 23.82 | 14.83 | 23.81 |
July | 253.83 | 23.85 | 677.33 | 23.87 | 249.50 | 23.87 |
August | 208.33 | 23.59 | 416.67 | 23.74 | 131.17 | 23.73 |
September | 397.83 | 23.40 | 266.00 | 23.51 | 153.17 | 23.52 |
October | 681.33 | 22.74 | 29.67 | 22.78 | 13.50 | 22.79 |
November | 720.00 | 21.86 | 0.00 | 21.86 | 0.00 | 21.86 |
December | 744.00 | 21.17 | 56.50 | 21.16 | 56.50 | 21.15 |
Annual Sum or Average | 6693.17 | 22.22 | 1707.17 | 22.50 | 695.67 | 22.55 |
Minimum of Months | 183.50 | 21.17 | 0.00 | 21.16 | 0.00 | 21.15 |
Maximum of Months | 744.00 | 23.85 | 677.33 | 23.87 | 249.50 | 23.87 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 226.17 | 23.07 | 575.50 | 23.38 | 151.17 | 23.48 |
February | 205.00 | 23.10 | 510.67 | 23.42 | 138.50 | 23.52 |
March | 228.67 | 23.13 | 589.83 | 23.41 | 154.00 | 23.50 |
April | 237.67 | 23.54 | 611.67 | 23.49 | 195.50 | 23.59 |
May | 291.83 | 23.83 | 676.67 | 23.51 | 274.17 | 23.62 |
June | 322.67 | 23.92 | 702.67 | 23.47 | 321.00 | 23.58 |
July | 424.00 | 23.74 | 744.00 | 23.42 | 424.00 | 23.50 |
August | 364.50 | 23.87 | 740.50 | 23.44 | 364.50 | 23.55 |
September | 369.33 | 23.80 | 701.00 | 23.44 | 368.33 | 23.54 |
October | 310.67 | 23.81 | 686.83 | 23.48 | 294.17 | 23.59 |
November | 225.00 | 23.27 | 591.50 | 23.44 | 165.00 | 23.53 |
December | 222.17 | 22.98 | 541.83 | 23.39 | 141.00 | 23.49 |
Annual Sum or Average | 3427.67 | 23.58 | 7672.67 | 23.44 | 2991.33 | 23.54 |
Minimum of Months | 205.00 | 22.98 | 510.67 | 23.38 | 138.50 | 23.48 |
Maximum of Months | 424.00 | 23.92 | 744.00 | 23.51 | 424.00 | 23.62 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 486.00 | 22.94 | 86.83 | 23.10 | 0.00 | 23.10 |
February | 432.67 | 23.11 | 63.67 | 23.22 | 1.00 | 23.22 |
March | 477.00 | 23.07 | 48.50 | 23.16 | 0.00 | 23.16 |
April | 282.50 | 23.15 | 166.17 | 23.43 | 0.00 | 23.43 |
May | 201.67 | 23.37 | 388.00 | 23.65 | 83.50 | 23.67 |
June | 196.50 | 23.78 | 612.33 | 23.80 | 177.83 | 23.81 |
July | 562.67 | 23.84 | 743.17 | 23.81 | 562.50 | 23.82 |
August | 433.33 | 23.79 | 738.67 | 23.81 | 432.67 | 23.80 |
September | 364.17 | 23.87 | 686.17 | 23.90 | 357.33 | 23.90 |
October | 232.17 | 23.51 | 540.17 | 23.79 | 168.17 | 23.80 |
November | 310.00 | 22.93 | 205.00 | 23.35 | 1.50 | 23.35 |
December | 554.83 | 22.94 | 68.67 | 23.05 | 0.00 | 23.05 |
Annual Sum or Average | 4533.50 | 23.33 | 4347.33 | 23.59 | 1784.50 | 23.63 |
Minimum of Months | 196.50 | 22.93 | 48.50 | 23.05 | 0.00 | 23.05 |
Maximum of Months | 562.67 | 23.87 | 743.17 | 23.90 | 562.50 | 23.90 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 628.50 | 23.26 | 0.00 | 23.26 | 0.00 | 23.26 |
February | 598.67 | 23.38 | 3.50 | 23.39 | 0.00 | 23.39 |
March | 648.50 | 23.35 | 9.33 | 23.36 | 0.00 | 23.36 |
April | 438.00 | 23.42 | 50.67 | 23.48 | 0.00 | 23.48 |
May | 246.17 | 23.46 | 234.17 | 23.66 | 63.67 | 23.69 |
June | 173.67 | 23.78 | 481.50 | 23.86 | 133.67 | 23.87 |
July | 516.83 | 23.90 | 735.67 | 23.86 | 516.83 | 23.87 |
August | 397.00 | 23.87 | 723.33 | 23.85 | 397.00 | 23.86 |
September | 343.33 | 23.93 | 637.17 | 23.91 | 342.17 | 23.92 |
October | 209.17 | 23.69 | 394.50 | 23.83 | 140.50 | 23.84 |
November | 413.67 | 23.40 | 36.00 | 23.45 | 0.00 | 23.45 |
December | 705.00 | 23.26 | 0.00 | 23.26 | 0.00 | 23.26 |
Annual Sum or Average | 5318.50 | 23.50 | 3305.83 | 23.64 | 1593.83 | 23.68 |
Minimum of Months | 173.67 | 23.26 | 0.00 | 23.26 | 0.00 | 23.26 |
Maximum of Months | 705.00 | 23.93 | 735.67 | 23.91 | 516.83 | 23.92 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 741.00 | 21.39 | 57.17 | 21.35 | 57.17 | 21.33 |
February | 669.67 | 21.48 | 30.00 | 21.46 | 30.00 | 21.44 |
March | 743.00 | 21.55 | 8.33 | 21.55 | 8.33 | 21.54 |
April | 690.00 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
May | 664.83 | 21.53 | 3.67 | 21.54 | 0.00 | 21.54 |
June | 603.00 | 21.45 | 18.67 | 21.51 | 0.00 | 21.51 |
July | 610.50 | 21.40 | 23.67 | 21.47 | 2.83 | 21.47 |
August | 613.33 | 21.40 | 23.67 | 21.47 | 1.33 | 21.47 |
September | 585.33 | 21.37 | 24.67 | 21.45 | 1.33 | 21.46 |
October | 670.67 | 21.51 | 16.17 | 21.54 | 6.67 | 21.55 |
November | 702.33 | 21.49 | 17.00 | 21.47 | 17.00 | 21.45 |
December | 744.00 | 21.36 | 109.17 | 21.30 | 109.17 | 21.26 |
Annual Sum or Average | 8037.67 | 21.46 | 332.17 | 21.47 | 233.83 | 21.46 |
Minimum of Months | 585.33 | 21.36 | 0.00 | 21.30 | 0.00 | 21.26 |
Maximum of Months | 744.00 | 21.61 | 109.17 | 21.61 | 109.17 | 21.61 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.06 | 199.50 | 20.99 | 199.50 | 20.95 |
February | 672.00 | 21.30 | 132.00 | 21.23 | 132.00 | 21.18 |
March | 733.00 | 21.61 | 34.17 | 21.58 | 33.50 | 21.55 |
April | 680.00 | 21.85 | 8.83 | 21.90 | 0.00 | 21.90 |
May | 639.00 | 21.77 | 18.50 | 21.84 | 3.17 | 21.85 |
June | 555.17 | 21.57 | 56.00 | 21.79 | 8.67 | 21.82 |
July | 581.83 | 21.64 | 84.83 | 21.92 | 48.17 | 22.06 |
August | 598.67 | 21.69 | 69.00 | 21.91 | 41.83 | 22.01 |
September | 590.50 | 21.83 | 72.17 | 22.03 | 58.67 | 22.14 |
October | 661.17 | 21.87 | 41.17 | 21.97 | 22.33 | 22.00 |
November | 716.50 | 21.42 | 52.83 | 21.38 | 51.83 | 21.34 |
December | 744.00 | 20.98 | 323.33 | 20.91 | 323.33 | 20.87 |
Annual Sum or Average | 7915.83 | 21.53 | 1092.33 | 21.56 | 923.00 | 21.54 |
Minimum of Months | 555.17 | 20.98 | 8.83 | 20.91 | 0.00 | 20.87 |
Maximum of Months | 744.00 | 21.87 | 323.33 | 22.03 | 323.33 | 22.14 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.15 | 85.00 | 21.13 | 85.00 | 21.11 |
February | 672.00 | 21.28 | 60.50 | 21.25 | 60.50 | 21.22 |
March | 744.00 | 21.48 | 3.67 | 21.48 | 3.67 | 21.48 |
April | 720.00 | 21.78 | 0.00 | 21.78 | 0.00 | 21.78 |
May | 743.50 | 21.90 | 0.00 | 21.90 | 0.00 | 21.90 |
June | 712.50 | 21.91 | 0.50 | 21.91 | 0.17 | 21.91 |
July | 734.83 | 21.91 | 41.67 | 21.99 | 39.83 | 22.06 |
August | 739.83 | 21.93 | 25.33 | 21.97 | 25.00 | 22.01 |
September | 720.00 | 21.97 | 42.83 | 22.03 | 42.83 | 22.08 |
October | 744.00 | 21.83 | 7.83 | 21.84 | 7.83 | 21.85 |
November | 720.00 | 21.31 | 8.33 | 21.30 | 8.33 | 21.29 |
December | 744.00 | 21.11 | 108.50 | 21.08 | 108.50 | 21.05 |
Annual Sum or Average | 8738.67 | 21.63 | 384.17 | 21.63 | 381.67 | 21.63 |
Minimum of Months | 672.00 | 21.11 | 0.00 | 21.08 | 0.00 | 21.05 |
Maximum of Months | 744.00 | 21.97 | 108.50 | 22.03 | 108.50 | 22.08 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.45 | 60.83 | 21.41 | 60.83 | 21.38 |
February | 672.00 | 21.57 | 29.83 | 21.55 | 29.83 | 21.53 |
March | 744.00 | 21.64 | 12.83 | 21.63 | 12.83 | 21.62 |
April | 696.00 | 21.68 | 0.00 | 21.68 | 0.00 | 21.68 |
May | 649.33 | 21.52 | 0.83 | 21.52 | 0.00 | 21.52 |
June | 551.17 | 21.28 | 5.83 | 21.30 | 0.00 | 21.30 |
July | 559.00 | 21.23 | 12.00 | 21.28 | 1.50 | 21.28 |
August | 573.83 | 21.28 | 6.17 | 21.30 | 1.33 | 21.30 |
September | 551.17 | 21.27 | 6.00 | 21.29 | 0.00 | 21.29 |
October | 657.17 | 21.49 | 11.33 | 21.50 | 11.00 | 21.51 |
November | 717.00 | 21.56 | 21.50 | 21.54 | 21.50 | 21.51 |
December | 744.00 | 21.41 | 106.17 | 21.35 | 106.17 | 21.31 |
Annual Sum or Average | 7858.67 | 21.46 | 273.33 | 21.46 | 245.00 | 21.44 |
Minimum of Months | 551.17 | 21.23 | 0.00 | 21.28 | 0.00 | 21.28 |
Maximum of Months | 744.00 | 21.68 | 106.17 | 21.68 | 106.17 | 21.68 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.05 | 193.67 | 21.00 | 193.67 | 20.98 |
February | 672.00 | 21.34 | 121.00 | 21.28 | 121.00 | 21.24 |
March | 744.00 | 21.68 | 43.83 | 21.64 | 43.83 | 21.60 |
April | 677.83 | 21.93 | 15.17 | 22.01 | 0.00 | 22.01 |
May | 581.50 | 21.70 | 53.83 | 22.04 | 5.83 | 22.08 |
June | 496.00 | 21.45 | 68.83 | 21.92 | 15.17 | 22.03 |
July | 537.50 | 21.63 | 83.00 | 22.06 | 48.17 | 22.28 |
August | 543.00 | 21.62 | 82.17 | 22.02 | 43.17 | 22.18 |
September | 555.33 | 21.91 | 83.50 | 22.28 | 58.67 | 22.48 |
October | 708.67 | 21.94 | 42.00 | 22.00 | 31.83 | 22.01 |
November | 717.83 | 21.40 | 67.00 | 21.35 | 66.17 | 21.31 |
December | 744.00 | 20.97 | 343.33 | 20.92 | 343.33 | 20.89 |
Annual Sum or Average | 7721.67 | 21.54 | 1197.33 | 21.63 | 970.83 | 21.63 |
Minimum of Months | 496.00 | 20.97 | 15.17 | 20.92 | 0.00 | 20.89 |
Maximum of Months | 744.00 | 21.94 | 343.33 | 22.28 | 343.33 | 22.48 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.38 | 18.17 | 21.37 | 18.17 | 21.36 |
February | 672.00 | 21.65 | 1.67 | 21.65 | 1.67 | 21.64 |
March | 744.00 | 21.95 | 0.67 | 21.95 | 0.67 | 21.95 |
April | 720.00 | 22.79 | 0.00 | 22.79 | 0.00 | 22.79 |
May | 619.50 | 23.41 | 52.50 | 23.43 | 45.50 | 23.44 |
June | 257.83 | 23.84 | 245.83 | 23.86 | 103.33 | 23.85 |
July | 513.67 | 23.84 | 706.50 | 23.85 | 513.67 | 23.85 |
August | 404.17 | 23.72 | 532.33 | 23.76 | 360.83 | 23.76 |
September | 515.00 | 23.71 | 448.00 | 23.76 | 327.83 | 23.77 |
October | 689.33 | 23.07 | 123.83 | 23.11 | 104.17 | 23.13 |
November | 720.00 | 22.19 | 0.00 | 22.19 | 0.00 | 22.19 |
December | 744.00 | 21.20 | 25.50 | 21.19 | 25.50 | 21.19 |
Annual Sum or Average | 7343.50 | 22.54 | 2155.00 | 22.81 | 1501.33 | 22.93 |
Minimum of Months | 257.83 | 21.20 | 0.00 | 21.19 | 0.00 | 21.19 |
Maximum of Months | 744.00 | 23.84 | 706.50 | 23.86 | 513.67 | 23.85 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 740.33 | 21.29 | 141.67 | 21.21 | 141.67 | 21.15 |
February | 667.83 | 21.40 | 127.67 | 21.34 | 127.67 | 21.29 |
March | 741.00 | 21.49 | 73.17 | 21.45 | 73.17 | 21.41 |
April | 677.50 | 21.55 | 19.83 | 21.55 | 16.00 | 21.54 |
May | 645.00 | 21.47 | 17.83 | 21.52 | 0.50 | 21.52 |
June | 575.50 | 21.37 | 47.33 | 21.52 | 0.33 | 21.52 |
July | 588.83 | 21.34 | 67.17 | 21.53 | 7.50 | 21.55 |
August | 594.00 | 21.34 | 66.50 | 21.52 | 9.00 | 21.52 |
September | 571.83 | 21.32 | 75.33 | 21.53 | 15.33 | 21.54 |
October | 664.17 | 21.46 | 60.17 | 21.53 | 35.83 | 21.54 |
November | 700.17 | 21.41 | 94.17 | 21.35 | 93.50 | 21.30 |
December | 744.00 | 21.26 | 247.17 | 21.17 | 247.17 | 21.12 |
Annual Sum or Average | 7910.17 | 21.39 | 1038.00 | 21.42 | 767.67 | 21.38 |
Minimum of Months | 571.83 | 21.26 | 17.83 | 21.17 | 0.33 | 21.12 |
Maximum of Months | 744.00 | 21.55 | 247.17 | 21.55 | 247.17 | 21.55 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.92 | 362.50 | 20.84 | 362.50 | 20.80 |
February | 670.50 | 21.18 | 282.50 | 21.08 | 282.50 | 21.02 |
March | 731.33 | 21.53 | 121.33 | 21.45 | 120.00 | 21.38 |
April | 672.17 | 21.80 | 26.83 | 21.84 | 16.00 | 21.82 |
May | 628.17 | 21.72 | 32.17 | 21.82 | 5.67 | 21.83 |
June | 534.83 | 21.51 | 78.00 | 21.78 | 10.50 | 21.81 |
July | 568.33 | 21.59 | 120.33 | 21.93 | 56.00 | 22.07 |
August | 583.33 | 21.63 | 103.00 | 21.90 | 51.33 | 22.00 |
September | 580.33 | 21.75 | 107.50 | 21.98 | 72.50 | 22.07 |
October | 653.17 | 21.78 | 84.83 | 21.90 | 59.50 | 21.92 |
November | 717.00 | 21.31 | 186.83 | 21.21 | 185.67 | 21.14 |
December | 744.00 | 20.84 | 541.67 | 20.79 | 541.67 | 20.77 |
Annual Sum or Average | 7827.17 | 21.44 | 2047.50 | 21.45 | 1763.83 | 21.39 |
Minimum of Months | 534.83 | 20.84 | 26.83 | 20.79 | 5.67 | 20.77 |
Maximum of Months | 744.00 | 21.80 | 541.67 | 21.98 | 541.67 | 22.07 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 692.33 | 21.46 | 9.67 | 21.46 | 8.50 | 21.46 |
February | 634.50 | 21.54 | 8.33 | 21.53 | 8.33 | 21.53 |
March | 732.83 | 21.60 | 6.83 | 21.60 | 6.83 | 21.59 |
April | 692.00 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
May | 702.50 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
June | 635.00 | 21.52 | 0.00 | 21.52 | 0.00 | 21.52 |
July | 633.17 | 21.46 | 8.33 | 21.47 | 8.33 | 21.49 |
August | 628.00 | 21.44 | 4.00 | 21.44 | 4.00 | 21.45 |
September | 584.50 | 21.37 | 42.33 | 21.49 | 5.67 | 21.50 |
October | 626.33 | 21.41 | 58.33 | 21.56 | 5.50 | 21.57 |
November | 627.83 | 21.38 | 10.17 | 21.40 | 4.33 | 21.39 |
December | 698.83 | 21.50 | 23.33 | 21.48 | 23.33 | 21.46 |
Annual Sum or Average | 7887.83 | 21.50 | 171.33 | 21.52 | 74.83 | 21.52 |
Minimum of Months | 584.50 | 21.37 | 0.00 | 21.40 | 0.00 | 21.39 |
Maximum of Months | 732.83 | 21.61 | 58.33 | 21.61 | 23.33 | 21.61 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 466.83 | 23.38 | 15.83 | 23.40 | 0.00 | 23.40 |
February | 374.33 | 23.46 | 33.50 | 23.50 | 0.00 | 23.50 |
March | 288.50 | 23.43 | 15.33 | 23.46 | 0.00 | 23.46 |
April | 61.33 | 23.54 | 198.17 | 23.88 | 0.00 | 23.88 |
May | 79.17 | 23.94 | 523.50 | 23.98 | 72.00 | 23.98 |
June | 151.00 | 23.99 | 678.17 | 23.99 | 151.00 | 23.99 |
July | 539.83 | 23.99 | 744.00 | 23.99 | 539.83 | 23.99 |
August | 417.17 | 23.99 | 744.00 | 23.98 | 417.17 | 23.98 |
September | 371.67 | 23.99 | 706.00 | 23.98 | 371.67 | 23.98 |
October | 188.17 | 23.87 | 554.83 | 23.92 | 160.50 | 23.93 |
November | 298.50 | 23.41 | 83.00 | 23.53 | 0.00 | 23.53 |
December | 543.33 | 23.39 | 0.00 | 23.39 | 0.00 | 23.39 |
Annual Sum or Average | 3779.83 | 23.67 | 4296.33 | 23.84 | 1712.17 | 23.86 |
Minimum of Months | 61.33 | 23.38 | 0.00 | 23.39 | 0.00 | 23.39 |
Maximum of Months | 543.33 | 23.99 | 744.00 | 23.99 | 539.83 | 23.99 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 222.00 | 23.33 | 92.50 | 23.53 | 0.00 | 23.53 |
February | 137.33 | 23.40 | 53.33 | 23.57 | 0.00 | 23.57 |
March | 105.33 | 23.41 | 36.50 | 23.56 | 0.00 | 23.56 |
April | 16.00 | 23.48 | 279.67 | 23.96 | 0.00 | 23.96 |
May | 64.33 | 24.00 | 582.50 | 23.99 | 64.33 | 23.99 |
June | 133.00 | 24.00 | 690.67 | 23.99 | 133.00 | 23.99 |
July | 510.17 | 24.00 | 744.00 | 23.99 | 510.17 | 24.00 |
August | 395.67 | 23.99 | 744.00 | 23.99 | 395.67 | 23.99 |
September | 352.50 | 24.00 | 718.33 | 23.99 | 352.50 | 23.99 |
October | 148.33 | 23.98 | 627.17 | 23.97 | 146.17 | 23.98 |
November | 119.00 | 23.40 | 130.50 | 23.70 | 0.00 | 23.70 |
December | 290.83 | 23.36 | 15.67 | 23.39 | 0.00 | 23.39 |
Annual Sum or Average | 2494.50 | 23.77 | 4714.83 | 23.91 | 1601.83 | 23.93 |
Minimum of Months | 16.00 | 23.33 | 15.67 | 23.39 | 0.00 | 23.39 |
Maximum of Months | 510.17 | 24.00 | 744.00 | 23.99 | 510.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.83 | 23.95 | 649.33 | 23.93 | 480.83 | 23.94 |
February | 451.33 | 23.96 | 592.83 | 23.94 | 443.33 | 23.95 |
March | 496.83 | 23.98 | 672.33 | 23.95 | 493.00 | 23.96 |
April | 505.67 | 23.99 | 699.00 | 23.96 | 505.67 | 23.97 |
May | 550.17 | 23.99 | 743.00 | 23.97 | 550.17 | 23.98 |
June | 591.33 | 23.99 | 720.00 | 23.99 | 591.33 | 23.99 |
July | 740.00 | 23.98 | 744.00 | 23.98 | 740.00 | 23.98 |
August | 679.50 | 23.98 | 744.00 | 23.98 | 679.50 | 23.98 |
September | 645.83 | 23.98 | 720.00 | 23.97 | 645.83 | 23.97 |
October | 562.50 | 23.99 | 744.00 | 23.94 | 562.50 | 23.96 |
November | 489.67 | 23.98 | 651.50 | 23.94 | 485.67 | 23.95 |
December | 498.50 | 23.91 | 624.33 | 23.93 | 473.83 | 23.94 |
Annual Sum or Average | 6705.17 | 23.97 | 8304.33 | 23.96 | 6651.67 | 23.97 |
Minimum of Months | 451.33 | 23.91 | 592.83 | 23.93 | 443.33 | 23.94 |
Maximum of Months | 740.00 | 23.99 | 744.00 | 23.99 | 740.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.22 | 31.67 | 21.21 | 31.67 | 21.20 |
February | 672.00 | 21.45 | 11.67 | 21.44 | 11.67 | 21.44 |
March | 744.00 | 21.69 | 13.33 | 21.68 | 13.33 | 21.67 |
April | 703.50 | 22.68 | 0.00 | 22.68 | 0.00 | 22.68 |
May | 440.00 | 23.22 | 105.00 | 23.34 | 7.33 | 23.34 |
June | 95.83 | 23.66 | 375.17 | 23.87 | 36.67 | 23.86 |
July | 322.00 | 23.79 | 738.67 | 23.86 | 322.00 | 23.84 |
August | 215.50 | 23.62 | 588.00 | 23.77 | 191.17 | 23.75 |
September | 348.83 | 23.38 | 464.17 | 23.59 | 196.50 | 23.58 |
October | 620.00 | 22.69 | 98.67 | 22.82 | 39.50 | 22.84 |
November | 720.00 | 21.75 | 0.00 | 21.75 | 0.00 | 21.75 |
December | 744.00 | 21.14 | 60.17 | 21.13 | 60.17 | 21.12 |
Annual Sum or Average | 6369.67 | 22.16 | 2486.50 | 22.59 | 910.00 | 22.66 |
Minimum of Months | 95.83 | 21.14 | 0.00 | 21.13 | 0.00 | 21.12 |
Maximum of Months | 744.00 | 23.79 | 738.67 | 23.87 | 322.00 | 23.86 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.40198 | 25.48827 | 0.07801 | 5.26635 |
February | 672.00000 | 22.25683 | 23.58985 | -0.2205 | 6.24446 |
March | 744.00000 | 21.40320 | 22.79026 | -0.4375 | 9.13868 |
April | 720.00000 | 21.45788 | 26.70509 | -0.3994 | 8.50546 |
May | 744.00000 | 21.78846 | 37.90753 | -1.3823 | 44.69787 |
June | 720.00000 | 22.13981 | 47.20408 | -1.1978 | 35.39476 |
July | 744.00000 | 23.28185 | 59.03430 | -0.7085 | 15.96192 |
August | 744.00000 | 23.83984 | 53.50473 | -0.5322 | 11.06554 |
September | 720.00000 | 23.95643 | 49.58740 | -0.4992 | 10.33980 |
October | 744.00000 | 23.96764 | 40.27292 | 0.34696 | 7.64277 |
November | 720.00000 | 23.96246 | 24.74863 | 0.23360 | 6.20546 |
December | 744.00000 | 23.89994 | 22.59665 | 0.19306 | 5.85555 |
Annual Sum or Average | 8760.00000 | 22.95276 | 36.21180 | -0.3775 | 13.90876 |
Minimum of Months | 672.00000 | 21.40320 | 22.59665 | -1.3823 | 5.26635 |
Maximum of Months | 744.00000 | 23.96764 | 59.03430 | 0.34696 | 44.69787 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.98559 | 25.79911 | -0.2115 | 7.78555 |
February | 672.00000 | 22.10939 | 22.46404 | -0.1890 | 7.43078 |
March | 744.00000 | 22.11194 | 20.77098 | -0.1942 | 7.18579 |
April | 720.00000 | 22.76193 | 23.61827 | 0.00967 | 6.31445 |
May | 744.00000 | 23.23448 | 33.70584 | -0.7367 | 17.95670 |
June | 720.00000 | 23.68056 | 42.01972 | -0.4921 | 10.63957 |
July | 744.00000 | 23.70180 | 56.17544 | -0.3859 | 8.53871 |
August | 744.00000 | 23.64192 | 52.79072 | -0.4274 | 9.60104 |
September | 720.00000 | 23.63554 | 49.63326 | -0.4389 | 10.26386 |
October | 744.00000 | 23.15272 | 41.47128 | 0.25266 | 7.78626 |
November | 720.00000 | 22.44891 | 26.00115 | -0.0621 | 7.35135 |
December | 744.00000 | 21.86533 | 23.76094 | -0.2654 | 8.22899 |
Annual Sum or Average | 8760.00000 | 22.86405 | 34.94758 | -0.2625 | 9.10880 |
Minimum of Months | 672.00000 | 21.86533 | 20.77098 | -0.7367 | 6.31445 |
Maximum of Months | 744.00000 | 23.70180 | 56.17544 | 0.25266 | 17.95670 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.74458 | 26.58184 | -0.0479 | 5.37452 |
February | 672.00000 | 22.88132 | 23.34610 | -0.0321 | 5.31340 |
March | 744.00000 | 22.98485 | 21.70488 | -0.0136 | 5.35061 |
April | 720.00000 | 23.44301 | 24.59696 | 0.13141 | 5.73572 |
May | 744.00000 | 23.68132 | 34.41748 | -0.6529 | 14.46194 |
June | 720.00000 | 23.82397 | 42.89166 | -0.5246 | 11.05156 |
July | 744.00000 | 23.84045 | 56.93965 | -0.4223 | 8.88503 |
August | 744.00000 | 23.82512 | 53.53088 | -0.4542 | 9.50328 |
September | 720.00000 | 23.84209 | 50.48036 | -0.4713 | 9.90083 |
October | 744.00000 | 23.62719 | 42.02171 | 0.30224 | 7.18669 |
November | 720.00000 | 23.18378 | 26.83928 | 0.07169 | 5.55303 |
December | 744.00000 | 22.61171 | 24.65197 | -0.0952 | 5.47395 |
Annual Sum or Average | 8760.00000 | 23.37598 | 35.76230 | -0.1852 | 7.83377 |
Minimum of Months | 672.00000 | 22.61171 | 21.70488 | -0.6529 | 5.31340 |
Maximum of Months | 744.00000 | 23.84209 | 56.93965 | 0.30224 | 14.46194 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.12665 | 21.45392 | 0.62060 | 15.43832 |
February | 672.00000 | 23.15271 | 18.38188 | 0.62136 | 15.40470 |
March | 744.00000 | 23.15727 | 16.85279 | 0.62782 | 15.60527 |
April | 720.00000 | 23.21261 | 20.37205 | 0.69932 | 17.55149 |
May | 744.00000 | 23.23250 | 31.03512 | 0.11537 | 9.89912 |
June | 720.00000 | 23.23004 | 40.35789 | 0.20933 | 10.34051 |
July | 744.00000 | 23.22958 | 54.89911 | 0.29974 | 10.99378 |
August | 744.00000 | 23.21467 | 51.34975 | 0.26434 | 10.78699 |
September | 720.00000 | 23.21167 | 48.17384 | 0.22867 | 10.42097 |
October | 744.00000 | 23.19432 | 38.59547 | 0.81079 | 21.05887 |
November | 720.00000 | 23.18074 | 22.20453 | 0.66166 | 16.52107 |
December | 744.00000 | 23.11526 | 19.44765 | 0.59791 | 14.87016 |
Annual Sum or Average | 8760.00000 | 23.18823 | 32.02901 | 0.47891 | 14.06734 |
Minimum of Months | 672.00000 | 23.11526 | 16.85279 | 0.11537 | 9.89912 |
Maximum of Months | 744.00000 | 23.23250 | 54.89911 | 0.81079 | 21.05887 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.27890 | 30.02807 | 0.16457 | 6.51363 |
February | 672.00000 | 23.39504 | 26.87906 | 0.18271 | 6.37062 |
March | 744.00000 | 23.36446 | 25.40724 | 0.16421 | 6.22763 |
April | 720.00000 | 23.57488 | 28.27221 | 0.26697 | 7.02365 |
May | 744.00000 | 23.64033 | 38.27612 | -0.5191 | 11.27871 |
June | 720.00000 | 23.75943 | 46.59776 | -0.3756 | 8.31131 |
July | 744.00000 | 23.79074 | 60.53126 | -0.2653 | 6.71423 |
August | 744.00000 | 23.80978 | 56.95204 | -0.2798 | 6.99179 |
September | 720.00000 | 23.89390 | 53.60716 | -0.2618 | 6.92968 |
October | 744.00000 | 23.76790 | 45.06395 | 0.46960 | 10.18411 |
November | 720.00000 | 23.50830 | 30.19819 | 0.25794 | 7.49009 |
December | 744.00000 | 23.18422 | 28.13843 | 0.11914 | 6.25623 |
Annual Sum or Average | 8760.00000 | 23.58105 | 39.25804 | -0.0077 | 7.53473 |
Minimum of Months | 672.00000 | 23.18422 | 25.40724 | -0.5191 | 6.22763 |
Maximum of Months | 744.00000 | 23.89390 | 60.53126 | 0.46960 | 11.27871 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.36583 | 28.91441 | 0.13472 | 5.68579 |
February | 672.00000 | 23.44472 | 25.79980 | 0.13833 | 5.65263 |
March | 744.00000 | 23.43230 | 24.24343 | 0.12915 | 5.64944 |
April | 720.00000 | 23.61911 | 27.07678 | 0.21508 | 6.25086 |
May | 744.00000 | 23.70557 | 36.85738 | -0.5877 | 12.68040 |
June | 720.00000 | 23.79652 | 45.33243 | -0.4722 | 9.98012 |
July | 744.00000 | 23.82205 | 59.32247 | -0.3655 | 7.95239 |
August | 744.00000 | 23.83207 | 55.83599 | -0.3887 | 8.31414 |
September | 720.00000 | 23.88587 | 52.72162 | -0.3943 | 8.43079 |
October | 744.00000 | 23.81416 | 44.03028 | 0.39379 | 8.45143 |
November | 720.00000 | 23.62575 | 29.12327 | 0.21737 | 6.31379 |
December | 744.00000 | 23.29425 | 27.06106 | 0.10057 | 5.51833 |
Annual Sum or Average | 8760.00000 | 23.63705 | 38.12119 | -0.0746 | 7.58726 |
Minimum of Months | 672.00000 | 23.29425 | 24.24343 | -0.5877 | 5.51833 |
Maximum of Months | 744.00000 | 23.88587 | 59.32247 | 0.39379 | 12.68040 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.39506 | 40.58927 | -0.3689 | 8.61524 |
February | 672.00000 | 21.48284 | 35.56295 | -0.3509 | 8.40558 |
March | 744.00000 | 21.55568 | 32.64220 | -0.3154 | 7.95494 |
April | 720.00000 | 21.67766 | 34.69191 | -0.1995 | 6.92167 |
May | 744.00000 | 21.72327 | 41.38982 | -1.1812 | 35.78868 |
June | 720.00000 | 21.75213 | 45.63917 | -1.0911 | 31.60543 |
July | 744.00000 | 21.74523 | 49.68379 | -1.0773 | 30.95180 |
August | 744.00000 | 21.73886 | 49.58864 | -1.0941 | 31.74564 |
September | 720.00000 | 21.73649 | 49.36191 | -1.1042 | 32.35535 |
October | 744.00000 | 21.68868 | 48.17761 | -0.1076 | 6.20241 |
November | 720.00000 | 21.53609 | 38.90912 | -0.2872 | 7.80211 |
December | 744.00000 | 21.36011 | 38.49850 | -0.4078 | 9.20606 |
Annual Sum or Average | 8760.00000 | 21.61645 | 42.11367 | -0.6340 | 18.19260 |
Minimum of Months | 672.00000 | 21.36011 | 32.64220 | -1.1812 | 6.20241 |
Maximum of Months | 744.00000 | 21.75213 | 49.68379 | -0.1076 | 35.78868 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.05826 | 41.29587 | -0.4929 | 10.42196 |
February | 672.00000 | 21.29862 | 35.86754 | -0.4401 | 9.64344 |
March | 744.00000 | 21.65644 | 32.46820 | -0.3323 | 8.27413 |
April | 720.00000 | 21.97873 | 34.31792 | -0.1581 | 6.81183 |
May | 744.00000 | 22.03141 | 40.99583 | -1.1010 | 32.30840 |
June | 720.00000 | 22.02524 | 45.48502 | -1.0119 | 28.47212 |
July | 744.00000 | 22.02566 | 50.09175 | -0.9942 | 27.82489 |
August | 744.00000 | 22.04097 | 50.07202 | -1.0175 | 28.68168 |
September | 720.00000 | 22.12968 | 50.27705 | -1.0220 | 28.90870 |
October | 744.00000 | 22.09725 | 48.51984 | -0.0606 | 6.26240 |
November | 720.00000 | 21.43564 | 39.06650 | -0.3651 | 8.60590 |
December | 744.00000 | 20.97824 | 39.29998 | -0.5416 | 11.42085 |
Annual Sum or Average | 8760.00000 | 21.73144 | 42.36640 | -0.6295 | 17.35615 |
Minimum of Months | 672.00000 | 20.97824 | 32.46820 | -1.1010 | 6.26240 |
Maximum of Months | 744.00000 | 22.12968 | 50.27705 | -0.0606 | 32.30840 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.14656 | 36.96123 | -0.4697 | 9.71578 |
February | 672.00000 | 21.27647 | 31.87237 | -0.4526 | 9.44598 |
March | 744.00000 | 21.48193 | 28.80805 | -0.4013 | 8.58516 |
April | 720.00000 | 21.77695 | 31.14420 | -0.2799 | 7.22478 |
May | 744.00000 | 21.90484 | 39.42314 | -1.2735 | 39.72625 |
June | 720.00000 | 21.92954 | 45.44108 | -1.1947 | 36.03798 |
July | 744.00000 | 21.94077 | 51.99569 | -1.1533 | 34.22264 |
August | 744.00000 | 21.93961 | 51.42506 | -1.1758 | 35.13705 |
September | 720.00000 | 21.96744 | 51.21797 | -1.1933 | 35.88670 |
October | 744.00000 | 21.83062 | 46.69771 | -0.1814 | 6.20464 |
November | 720.00000 | 21.30593 | 35.42045 | -0.4189 | 8.86307 |
December | 744.00000 | 21.10804 | 34.89190 | -0.4991 | 10.27944 |
Annual Sum or Average | 8760.00000 | 21.63578 | 40.50801 | -0.7262 | 20.17771 |
Minimum of Months | 672.00000 | 21.10804 | 28.80805 | -1.2735 | 6.20464 |
Maximum of Months | 744.00000 | 21.96744 | 51.99569 | -0.1814 | 39.72625 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.45001 | 40.46965 | -0.3606 | 8.48854 |
February | 672.00000 | 21.57134 | 35.42893 | -0.3229 | 8.13207 |
March | 744.00000 | 21.63694 | 32.60084 | -0.2925 | 7.82195 |
April | 720.00000 | 21.73578 | 34.55675 | -0.1768 | 6.82966 |
May | 744.00000 | 21.75083 | 41.27827 | -1.1635 | 34.99013 |
June | 720.00000 | 21.75957 | 45.74129 | -1.0775 | 31.07630 |
July | 744.00000 | 21.75548 | 49.71732 | -1.0645 | 30.48213 |
August | 744.00000 | 21.74970 | 49.58203 | -1.0821 | 31.28994 |
September | 720.00000 | 21.75191 | 49.29226 | -1.0950 | 31.99533 |
October | 744.00000 | 21.70428 | 48.47793 | -0.1087 | 6.25737 |
November | 720.00000 | 21.56960 | 38.90935 | -0.2822 | 7.75233 |
December | 744.00000 | 21.40925 | 38.44664 | -0.3960 | 8.99117 |
Annual Sum or Average | 8760.00000 | 21.65385 | 42.09521 | -0.6205 | 17.90484 |
Minimum of Months | 672.00000 | 21.40925 | 32.60084 | -1.1635 | 6.25737 |
Maximum of Months | 744.00000 | 21.75957 | 49.71732 | -0.1087 | 34.99013 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.04509 | 41.23861 | -0.4981 | 10.38802 |
February | 672.00000 | 21.33625 | 35.78386 | -0.4215 | 9.23235 |
March | 744.00000 | 21.67903 | 32.51021 | -0.3214 | 7.96642 |
April | 720.00000 | 22.06647 | 34.07943 | -0.1300 | 6.76429 |
May | 744.00000 | 22.21391 | 40.89628 | -1.0378 | 30.95444 |
June | 720.00000 | 22.16156 | 45.58214 | -0.9599 | 27.87736 |
July | 744.00000 | 22.14251 | 50.01853 | -0.9502 | 27.35797 |
August | 744.00000 | 22.16552 | 49.87184 | -0.9727 | 28.07989 |
September | 720.00000 | 22.29016 | 49.69388 | -0.9724 | 28.23015 |
October | 744.00000 | 22.02756 | 48.74940 | -0.0807 | 6.16785 |
November | 720.00000 | 21.40516 | 39.17390 | -0.3738 | 8.57986 |
December | 744.00000 | 20.97279 | 39.24191 | -0.5402 | 11.33699 |
Annual Sum or Average | 8760.00000 | 21.79385 | 42.29085 | -0.6063 | 16.96399 |
Minimum of Months | 672.00000 | 20.97279 | 32.51021 | -1.0378 | 6.16785 |
Maximum of Months | 744.00000 | 22.29016 | 50.01853 | -0.0807 | 30.95444 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.29857 | 41.59309 | -0.4200 | 9.57204 |
February | 672.00000 | 21.41012 | 36.26284 | -0.3940 | 9.22937 |
March | 744.00000 | 21.50055 | 33.11634 | -0.3499 | 8.60252 |
April | 720.00000 | 21.65614 | 34.86950 | -0.2121 | 7.25659 |
May | 744.00000 | 21.71559 | 41.55019 | -1.1841 | 36.16364 |
June | 720.00000 | 21.75437 | 45.82365 | -1.0778 | 31.28584 |
July | 744.00000 | 21.74529 | 50.08240 | -1.0635 | 30.57943 |
August | 744.00000 | 21.73631 | 50.15926 | -1.0855 | 31.59886 |
September | 720.00000 | 21.72923 | 50.16150 | -1.1062 | 32.72935 |
October | 744.00000 | 21.65728 | 49.36859 | -0.1240 | 6.44147 |
November | 720.00000 | 21.46592 | 39.74692 | -0.3314 | 8.57202 |
December | 744.00000 | 21.26263 | 39.41529 | -0.4608 | 10.28409 |
Annual Sum or Average | 8760.00000 | 21.57824 | 42.73218 | -0.6526 | 18.58696 |
Minimum of Months | 672.00000 | 21.26263 | 33.11634 | -1.1841 | 6.44147 |
Maximum of Months | 744.00000 | 21.75437 | 50.16150 | -0.1240 | 36.16364 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.91870 | 42.46837 | -0.5556 | 11.86424 |
February | 672.00000 | 21.19022 | 36.68095 | -0.4930 | 10.81872 |
March | 744.00000 | 21.58821 | 33.03104 | -0.3699 | 9.04423 |
April | 720.00000 | 21.94650 | 34.51878 | -0.1712 | 7.15394 |
May | 744.00000 | 21.99281 | 41.14691 | -1.1105 | 32.91670 |
June | 720.00000 | 22.00140 | 45.61394 | -1.0047 | 28.32420 |
July | 744.00000 | 22.00287 | 50.39212 | -0.9859 | 27.58987 |
August | 744.00000 | 22.00697 | 50.53849 | -1.0169 | 28.78626 |
September | 720.00000 | 22.07363 | 51.01685 | -1.0374 | 29.68975 |
October | 744.00000 | 22.04273 | 49.76722 | -0.0814 | 6.50517 |
November | 720.00000 | 21.31896 | 40.07842 | -0.4233 | 9.70062 |
December | 744.00000 | 20.84401 | 40.37812 | -0.6047 | 12.99764 |
Annual Sum or Average | 8760.00000 | 21.66254 | 43.02273 | -0.6558 | 17.99947 |
Minimum of Months | 672.00000 | 20.84401 | 33.03104 | -1.1105 | 6.50517 |
Maximum of Months | 744.00000 | 22.07363 | 51.01685 | -0.0814 | 32.91670 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.59460 | 40.75698 | -0.2666 | 7.82998 |
February | 672.00000 | 21.63699 | 35.73871 | -0.2719 | 7.87333 |
March | 744.00000 | 21.63026 | 32.71291 | -0.2936 | 7.98418 |
April | 720.00000 | 21.68073 | 35.03959 | -0.2266 | 7.28695 |
May | 744.00000 | 21.70940 | 42.15779 | -1.2562 | 39.31608 |
June | 720.00000 | 21.73688 | 46.67826 | -1.1699 | 35.12906 |
July | 744.00000 | 21.73933 | 51.04061 | -1.1402 | 33.75303 |
August | 744.00000 | 21.73435 | 50.44469 | -1.1444 | 34.05222 |
September | 720.00000 | 21.73649 | 50.29195 | -1.1314 | 33.81762 |
October | 744.00000 | 21.70792 | 48.26074 | -0.0991 | 6.44607 |
November | 720.00000 | 21.63271 | 39.02653 | -0.2266 | 7.52440 |
December | 744.00000 | 21.60747 | 38.86043 | -0.2850 | 8.07994 |
Annual Sum or Average | 8760.00000 | 21.67908 | 42.63845 | -0.6282 | 19.16302 |
Minimum of Months | 672.00000 | 21.59460 | 32.71291 | -1.2562 | 6.44607 |
Maximum of Months | 744.00000 | 21.73933 | 51.04061 | -0.0991 | 39.31608 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.59766 | 29.48255 | 0.19799 | 6.18198 |
February | 672.00000 | 23.68958 | 26.27474 | 0.21546 | 6.24979 |
March | 744.00000 | 23.76406 | 24.45826 | 0.24285 | 6.43351 |
April | 720.00000 | 23.91290 | 27.05534 | 0.34931 | 7.74522 |
May | 744.00000 | 23.96797 | 36.66112 | -0.3776 | 8.26881 |
June | 720.00000 | 23.99146 | 45.14826 | -0.2633 | 6.59355 |
July | 744.00000 | 23.99114 | 59.01049 | -0.1702 | 5.62337 |
August | 744.00000 | 23.98237 | 55.74000 | -0.2137 | 6.01619 |
September | 720.00000 | 23.96847 | 53.01220 | -0.2667 | 6.67663 |
October | 744.00000 | 23.89573 | 44.51486 | 0.45974 | 9.67438 |
November | 720.00000 | 23.72167 | 29.87299 | 0.25603 | 6.64570 |
December | 744.00000 | 23.55188 | 27.74882 | 0.16414 | 5.93021 |
Annual Sum or Average | 8760.00000 | 23.83676 | 38.34097 | 0.04848 | 6.84057 |
Minimum of Months | 672.00000 | 23.55188 | 24.45826 | -0.3776 | 5.62337 |
Maximum of Months | 744.00000 | 23.99146 | 59.01049 | 0.45974 | 9.67438 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.76506 | 28.53031 | 0.27752 | 6.84019 |
February | 672.00000 | 23.83147 | 25.38473 | 0.28779 | 6.90299 |
March | 744.00000 | 23.88004 | 23.63240 | 0.30790 | 7.09316 |
April | 720.00000 | 23.96119 | 26.42707 | 0.39322 | 8.39140 |
May | 744.00000 | 23.98632 | 36.18790 | -0.3309 | 7.54789 |
June | 720.00000 | 23.99431 | 44.76743 | -0.2257 | 6.21449 |
July | 744.00000 | 23.99425 | 58.62289 | -0.1326 | 5.38697 |
August | 744.00000 | 23.99185 | 55.31770 | -0.1733 | 5.68720 |
September | 720.00000 | 23.98549 | 52.53651 | -0.2228 | 6.20747 |
October | 744.00000 | 23.94715 | 43.85554 | 0.50204 | 10.49292 |
November | 720.00000 | 23.84432 | 29.01745 | 0.32141 | 7.33200 |
December | 744.00000 | 23.73412 | 26.79281 | 0.24794 | 6.51094 |
Annual Sum or Average | 8760.00000 | 23.90987 | 37.68316 | 0.10328 | 7.05200 |
Minimum of Months | 672.00000 | 23.73412 | 23.63240 | -0.3309 | 5.38697 |
Maximum of Months | 744.00000 | 23.99431 | 58.62289 | 0.50204 | 10.49292 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.76898 | 27.56201 | 0.91582 | 25.04272 |
February | 672.00000 | 23.79467 | 24.57727 | 0.92709 | 25.42404 |
March | 744.00000 | 23.83115 | 23.09400 | 0.95086 | 26.31239 |
April | 720.00000 | 23.91488 | 26.28844 | 1.05504 | 30.49716 |
May | 744.00000 | 23.95954 | 36.16223 | 0.62959 | 17.57990 |
June | 720.00000 | 23.98307 | 44.67901 | 0.75013 | 20.35835 |
July | 744.00000 | 23.98461 | 58.15606 | 0.83693 | 22.91300 |
August | 744.00000 | 23.97924 | 54.86152 | 0.79367 | 21.63631 |
September | 720.00000 | 23.96425 | 51.99381 | 0.74363 | 20.36759 |
October | 744.00000 | 23.91147 | 43.26394 | 1.15596 | 34.76521 |
November | 720.00000 | 23.80704 | 28.22292 | 0.96223 | 26.83962 |
December | 744.00000 | 23.74507 | 25.75863 | 0.88736 | 24.04914 |
Annual Sum or Average | 8760.00000 | 23.88742 | 37.14603 | 0.88374 | 24.64387 |
Minimum of Months | 672.00000 | 23.74507 | 23.09400 | 0.62959 | 17.57990 |
Maximum of Months | 744.00000 | 23.98461 | 58.15606 | 1.15596 | 34.76521 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.23702 | 25.27716 | -0.4426 | 9.20443 |
February | 672.00000 | 21.43563 | 21.61378 | -0.4147 | 8.74864 |
March | 744.00000 | 21.68453 | 19.70449 | -0.3643 | 7.93537 |
April | 720.00000 | 22.54465 | 22.44464 | -0.1356 | 5.70664 |
May | 744.00000 | 23.31195 | 32.04243 | -0.8585 | 21.14965 |
June | 720.00000 | 23.83474 | 40.28322 | -0.6139 | 13.06925 |
July | 744.00000 | 23.86110 | 54.38818 | -0.5071 | 10.43514 |
August | 744.00000 | 23.73750 | 51.18553 | -0.5761 | 12.11493 |
September | 720.00000 | 23.50521 | 48.76541 | -0.6764 | 14.98923 |
October | 744.00000 | 22.81213 | 40.79689 | 0.04954 | 5.42357 |
November | 720.00000 | 21.85909 | 25.26615 | -0.2882 | 7.06343 |
December | 744.00000 | 21.16787 | 23.09726 | -0.4757 | 9.79429 |
Annual Sum or Average | 8760.00000 | 22.58817 | 33.83348 | -0.4423 | 10.48657 |
Minimum of Months | 672.00000 | 21.16787 | 19.70449 | -0.8585 | 5.42357 |
Maximum of Months | 744.00000 | 23.86110 | 54.38818 | 0.04954 | 21.14965 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.37602 | 29.47305 | -0.4083 | 8.61190 |
February | 672.00000 | 21.64710 | 25.79670 | -0.3623 | 7.86637 |
March | 744.00000 | 21.95240 | 23.89492 | -0.2988 | 7.01564 |
April | 720.00000 | 22.79390 | 26.73068 | -0.0747 | 5.36610 |
May | 744.00000 | 23.46603 | 36.46251 | -0.8160 | 19.54270 |
June | 720.00000 | 23.87824 | 44.67582 | -0.6112 | 12.97444 |
July | 744.00000 | 23.85808 | 58.84759 | -0.5222 | 10.74486 |
August | 744.00000 | 23.78603 | 55.57922 | -0.5716 | 11.97774 |
September | 720.00000 | 23.75771 | 52.69262 | -0.6013 | 12.81581 |
October | 744.00000 | 23.12189 | 44.72411 | 0.12504 | 5.62045 |
November | 720.00000 | 22.18762 | 29.33736 | -0.2078 | 6.28979 |
December | 744.00000 | 21.19614 | 27.42012 | -0.4661 | 9.58005 |
Annual Sum or Average | 8760.00000 | 22.75643 | 38.06534 | -0.4019 | 9.88914 |
Minimum of Months | 672.00000 | 21.19614 | 23.89492 | -0.8160 | 5.36610 |
Maximum of Months | 744.00000 | 23.87824 | 58.84759 | 0.12504 | 19.54270 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.21939 | 26.41636 | -0.4391 | 9.17749 |
February | 672.00000 | 21.45001 | 22.79073 | -0.3968 | 8.52059 |
March | 744.00000 | 21.68910 | 20.86600 | -0.3438 | 7.74817 |
April | 720.00000 | 22.70720 | 23.39732 | -0.0682 | 5.72636 |
May | 744.00000 | 23.47065 | 32.98078 | -0.7584 | 18.02401 |
June | 720.00000 | 23.89192 | 41.17274 | -0.5342 | 11.19932 |
July | 744.00000 | 23.88842 | 55.22472 | -0.4396 | 9.11280 |
August | 744.00000 | 23.79512 | 52.05407 | -0.5007 | 10.48018 |
September | 720.00000 | 23.63510 | 49.46213 | -0.5825 | 12.73669 |
October | 744.00000 | 22.86783 | 41.84181 | 0.09178 | 5.84059 |
November | 720.00000 | 21.74762 | 26.59598 | -0.2975 | 7.36290 |
December | 744.00000 | 21.13574 | 24.25706 | -0.4797 | 9.88681 |
Annual Sum or Average | 8760.00000 | 22.63044 | 34.84891 | -0.3960 | 9.66495 |
Minimum of Months | 672.00000 | 21.13574 | 20.86600 | -0.7584 | 5.72636 |
Maximum of Months | 744.00000 | 23.89192 | 55.22472 | 0.09178 | 18.02401 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.37169 | 24.64528 | -0.4132 | 8.71630 |
February | 672.00000 | 21.57094 | 21.01052 | -0.3855 | 8.29773 |
March | 744.00000 | 21.83834 | 19.09113 | -0.3306 | 7.48580 |
April | 720.00000 | 22.69070 | 21.81153 | -0.1024 | 5.57349 |
May | 744.00000 | 23.44697 | 31.31073 | -0.8113 | 19.50979 |
June | 720.00000 | 23.87049 | 39.71070 | -0.5945 | 12.58251 |
July | 744.00000 | 23.89015 | 53.80580 | -0.4897 | 10.07618 |
August | 744.00000 | 23.80008 | 50.51218 | -0.5493 | 11.46636 |
September | 720.00000 | 23.62478 | 47.95619 | -0.6333 | 13.79448 |
October | 744.00000 | 22.95981 | 39.99708 | 0.08330 | 5.52856 |
November | 720.00000 | 22.01090 | 24.59899 | -0.2547 | 6.72488 |
December | 744.00000 | 21.28761 | 22.51218 | -0.4488 | 9.31153 |
Annual Sum or Average | 8760.00000 | 22.70226 | 33.17458 | -0.4112 | 9.93843 |
Minimum of Months | 672.00000 | 21.28761 | 19.09113 | -0.8113 | 5.52856 |
Maximum of Months | 744.00000 | 23.89015 | 53.80580 | 0.08330 | 19.50979 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.151494E+11 | 66508.78 | 03-JAN-16:01 | 608.33 | 0.471561E+11 | 0.00 | 0.623055E+11 | 2.59 | 3.68 | 03-JAN-16:01 | 0.00 | 0.00 |
February | 0.264629E+11 | 85277.72 | 20-FEB-16:03 | 608.47 | 0.794261E+11 | 0.00 | 0.105889E+12 | 2.83 | 3.81 | 22-FEB-16:01 | 0.00 | 0.00 |
March | 0.421559E+11 | 91015.22 | 21-MAR-15:01 | 713.03 | 0.124889E+12 | 0.00 | 0.167045E+12 | 2.96 | 3.81 | 16-MAR-15:03 | 0.00 | 0.00 |
April | 0.104373E+12 | 123522.28 | 21-APR-15:03 | 718.56 | 0.316116E+12 | 0.00 | 0.420489E+12 | 3.03 | 3.82 | 27-APR-21:52 | 0.00 | 0.00 |
May | 0.165622E+12 | 140266.59 | 19-MAY-18:03 | 744.00 | 0.504099E+12 | 0.00 | 0.669720E+12 | 3.02 | 3.87 | 24-MAY-21:52 | 0.00 | 0.00 |
June | 0.216750E+12 | 184099.67 | 05-JUN-18:07 | 720.00 | 0.649158E+12 | 0.00 | 0.865907E+12 | 3.00 | 3.82 | 23-JUN-21:53 | 0.00 | 0.00 |
July | 0.251897E+12 | 165123.80 | 26-JUL-18:03 | 744.00 | 0.825233E+12 | 0.00 | 0.107713E+13 | 3.29 | 4.53 | 18-JUL-21:52 | 0.00 | 0.00 |
August | 0.217768E+12 | 156432.83 | 27-AUG-15:05 | 744.00 | 0.688632E+12 | 0.00 | 0.906400E+12 | 3.15 | 4.21 | 01-AUG-21:51 | 0.00 | 0.00 |
September | 0.177838E+12 | 138614.34 | 20-SEP-15:03 | 720.00 | 0.580226E+12 | 0.00 | 0.758064E+12 | 3.23 | 4.40 | 03-SEP-21:52 | 0.00 | 0.00 |
October | 0.103205E+12 | 138411.12 | 04-OCT-18:03 | 744.00 | 0.324317E+12 | 0.00 | 0.427522E+12 | 3.11 | 4.36 | 03-OCT-21:53 | 0.00 | 0.00 |
November | 0.351137E+11 | 90563.04 | 03-NOV-15:01 | 645.00 | 0.106343E+12 | 0.00 | 0.141457E+12 | 2.79 | 3.81 | 03-NOV-15:01 | 0.00 | 0.00 |
December | 0.125065E+11 | 53165.28 | 10-DEC-16:02 | 610.07 | 0.392786E+11 | 0.00 | 0.517851E+11 | 2.60 | 3.39 | 10-DEC-16:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.136884E+13 | 8319.46 | 0.428487E+13 | 0.00 | 0.565372E+13 | 2.97 | 0.00 | 0.00 | ||||
Minimum of Months | 0.125065E+11 | 53165.28 | 608.33 | 0.392786E+11 | 0.00 | 0.517851E+11 | 2.59 | 3.39 | 0.00 | 0.00 | ||
Maximum of Months | 0.251897E+12 | 184099.67 | 744.00 | 0.825233E+12 | 0.00 | 0.107713E+13 | 3.29 | 4.53 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.102141E+12 | 0.00 | 680.90 | 150175.38 | 26-JAN-16:01 | 0.00 | 43.09 | 76.36 | 0.24 | 0.00 | 0.10 | 0.40 | 26-JAN-16:01 |
February | 0.675222E+11 | 0.00 | 523.34 | 145300.30 | 09-FEB-19:03 | 0.00 | 41.00 | 70.61 | 0.17 | 0.00 | 0.07 | 0.38 | 09-FEB-19:03 |
March | 0.603044E+11 | 0.00 | 574.86 | 135700.87 | 27-MAR-08:07 | 0.00 | 36.36 | 69.27 | 0.13 | 0.00 | 0.06 | 0.36 | 27-MAR-08:07 |
April | 0.199240E+11 | 0.00 | 187.35 | 131667.01 | 11-APR-08:04 | 0.00 | 32.19 | 44.53 | 0.04 | 0.00 | 0.02 | 0.35 | 11-APR-08:04 |
May | 0.149598E+10 | 0.00 | 25.41 | 58475.74 | 02-MAY-06:00 | 0.00 | 37.96 | 39.61 | 0.00 | 0.00 | 0.00 | 0.15 | 02-MAY-06:00 |
June | 36778054.72 | 0.00 | 1.67 | 17667.94 | 13-JUN-08:35 | 0.00 | 54.65 | 54.70 | 0.00 | 0.00 | 0.00 | 0.05 | 13-JUN-08:35 |
July | 30604811.06 | 0.00 | 2.11 | 11740.71 | 25-JUL-08:06 | 0.00 | 60.14 | 60.20 | 0.00 | 0.00 | 0.00 | 0.03 | 25-JUL-08:06 |
August | 53731890.13 | 0.00 | 2.96 | 12566.14 | 22-AUG-08:55 | 0.00 | 60.63 | 60.70 | 0.00 | 0.00 | 0.00 | 0.03 | 22-AUG-08:55 |
September | 0.216073E+10 | 0.00 | 25.32 | 73403.30 | 30-SEP-06:00 | 0.00 | 53.46 | 55.07 | 0.00 | 0.00 | 0.00 | 0.19 | 30-SEP-06:00 |
October | 0.174140E+11 | 0.00 | 173.82 | 103294.89 | 24-OCT-08:05 | 0.00 | 32.30 | 44.08 | 0.03 | 0.00 | 0.02 | 0.27 | 24-OCT-08:05 |
November | 0.628888E+11 | 0.00 | 500.67 | 150220.72 | 28-NOV-16:01 | 0.00 | 40.84 | 67.26 | 0.14 | 0.00 | 0.06 | 0.40 | 28-NOV-16:01 |
December | 0.886705E+11 | 0.00 | 702.43 | 156849.00 | 20-DEC-09:01 | 0.00 | 45.86 | 77.63 | 0.22 | 0.00 | 0.09 | 0.41 | 20-DEC-09:01 |
Annual Sum or Average | 0.422643E+12 | 0.00 | 3400.84 | 0.00 | 44.90 | 59.96 | 0.08 | 0.00 | 0.04 | ||||
Minimum of Months | 30604811.06 | 0.00 | 1.67 | 11740.71 | 0.00 | 32.19 | 39.61 | 0.00 | 0.00 | 0.00 | 0.03 | ||
Maximum of Months | 0.102141E+12 | 0.00 | 702.43 | 156849.00 | 0.00 | 60.63 | 77.63 | 0.24 | 0.00 | 0.10 | 0.41 |
Report: DXReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.502956E+11 | 0.00 | 419.76 | 0.502956E+11 | -0.0 | 0.00 | 1.00 | 01-JAN-06:15 | 0.00 | 01-JAN-00:10 | 43581.40 | 30-JAN-07:05 | 43581.40 | 30-JAN-07:15 | 0.00 | 28-JAN-10:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.458969E+11 | 0.00 | 375.79 | 0.458969E+11 | -0.0 | 0.00 | 1.00 | 01-FEB-05:07 | 0.00 | 01-FEB-00:10 | 45186.83 | 01-FEB-05:07 | 45186.83 | 01-FEB-05:07 | 0.00 | 03-FEB-19:01 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 0.494518E+11 | 0.00 | 405.76 | 0.494518E+11 | -0.0 | 0.00 | 1.00 | 01-MAR-05:07 | 0.00 | 01-MAR-00:10 | 47237.07 | 01-MAR-07:30 | 47237.07 | 01-MAR-06:07 | 0.00 | 01-MAR-06:40 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 0.459433E+11 | 0.00 | 364.29 | 0.459433E+11 | 0.00 | 0.00 | 1.00 | 01-APR-05:17 | 0.00 | 01-APR-00:10 | 53772.39 | 01-APR-08:00 | 53772.39 | 01-APR-17:30 | 0.00 | 02-APR-09:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.442101E+11 | 0.00 | 363.26 | 0.442101E+11 | 0.00 | 0.00 | 1.00 | 01-MAY-06:15 | 0.00 | 01-MAY-00:05 | 58111.34 | 01-MAY-06:15 | 58111.34 | 01-MAY-07:55 | 0.00 | 29-MAY-06:35 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.396586E+11 | 0.00 | 346.44 | 0.396547E+11 | 3941020.40 | 0.00 | 1.00 | 01-JUN-05:17 | 0.00 | 01-JUN-00:05 | 61225.74 | 01-JUN-07:35 | 61225.74 | 01-JUN-06:20 | 2206.78 | 30-JUN-23:20 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.392089E+11 | 0.00 | 350.95 | 0.342467E+11 | 0.496225E+10 | 0.00 | 1.00 | 01-JUL-07:15 | 0.00 | 01-JUL-00:10 | 63296.29 | 01-JUL-10:33 | 55162.69 | 01-JUL-08:15 | 8144.88 | 01-JUL-17:17 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.389474E+11 | 0.00 | 356.36 | 0.375776E+11 | 0.136980E+10 | 0.00 | 1.00 | 01-AUG-04:10 | 0.00 | 01-AUG-00:05 | 61292.36 | 31-AUG-06:20 | 59007.66 | 31-AUG-09:06 | 2285.54 | 31-AUG-17:06 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.394971E+11 | 0.00 | 344.16 | 0.367175E+11 | 0.277954E+10 | 0.00 | 1.00 | 01-SEP-05:17 | 0.00 | 01-SEP-00:05 | 59716.61 | 30-SEP-05:08 | 55267.26 | 30-SEP-08:53 | 4455.84 | 30-SEP-17:15 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.437077E+11 | 0.00 | 360.80 | 0.437077E+11 | -0.0 | 0.00 | 1.00 | 01-OCT-05:07 | 0.00 | 01-OCT-00:20 | 55290.69 | 31-OCT-07:45 | 55290.69 | 31-OCT-15:18 | 0.00 | 23-OCT-06:15 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.441518E+11 | 0.00 | 383.22 | 0.441518E+11 | 0.00 | 0.00 | 1.00 | 01-NOV-04:07 | 0.00 | 01-NOV-00:05 | 46173.98 | 30-NOV-06:15 | 46173.98 | 30-NOV-16:06 | 0.00 | 02-NOV-10:15 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.474867E+11 | 0.00 | 421.71 | 0.474867E+11 | -0.0 | 0.00 | 1.00 | 01-DEC-06:15 | 0.00 | 01-DEC-00:05 | 41309.24 | 31-DEC-02:07 | 41309.24 | 31-DEC-08:25 | 0.00 | 01-DEC-10:05 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.528456E+12 | 0.00 | 4492.49 | 0.519341E+12 | 0.911552E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.389474E+11 | 0.00 | 344.16 | 0.342467E+11 | -0.0 | 0.00 | 1.00 | 0.00 | 41309.24 | 41309.24 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.502956E+11 | 0.00 | 421.71 | 0.502956E+11 | 0.496225E+10 | 0.00 | 1.00 | 0.00 | 63296.29 | 61225.74 | 8144.88 | 0.00 | 0.00 |
Report: DXReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.437180E+11 | 0.00 | 380.73 | 0.437180E+11 | -0.0 | 0.00 | 1.00 | 01-JAN-17:10 | 0.00 | 01-JAN-00:10 | 55148.40 | 30-JAN-17:10 | 55148.40 | 30-JAN-17:40 | 0.00 | 13-JAN-19:40 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.409484E+11 | 0.00 | 328.58 | 0.409484E+11 | -0.0 | 0.00 | 1.00 | 01-FEB-17:10 | 0.00 | 01-FEB-00:10 | 57181.24 | 01-FEB-18:30 | 57181.24 | 01-FEB-18:50 | 0.00 | 08-FEB-18:13 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 0.471733E+11 | 0.00 | 358.95 | 0.471733E+11 | -0.0 | 0.00 | 1.00 | 01-MAR-17:10 | 0.00 | 01-MAR-00:10 | 59777.34 | 01-MAR-21:10 | 59777.34 | 01-MAR-17:10 | 0.00 | 12-MAR-18:00 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 0.518181E+11 | 0.00 | 336.70 | 0.518181E+11 | 0.00 | 0.00 | 1.00 | 01-APR-16:10 | 0.00 | 01-APR-00:20 | 68052.58 | 01-APR-16:10 | 68052.58 | 01-APR-16:20 | 0.00 | 01-APR-16:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.578880E+11 | 0.00 | 345.91 | 0.578880E+11 | 0.00 | 0.00 | 1.00 | 01-MAY-16:10 | 0.00 | 01-MAY-00:05 | 73546.72 | 01-MAY-16:10 | 73546.72 | 01-MAY-21:50 | 0.00 | 09-MAY-22:40 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.592106E+11 | 0.00 | 324.28 | 0.592072E+11 | 3396672.63 | 0.00 | 1.00 | 01-JUN-16:05 | 0.00 | 01-JUN-00:05 | 77490.29 | 01-JUN-16:05 | 77490.29 | 01-JUN-16:35 | 5561.03 | 30-JUN-23:10 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.634304E+11 | 0.00 | 336.54 | 0.554157E+11 | 0.801471E+10 | 0.00 | 1.00 | 01-JUL-16:10 | 0.00 | 01-JUL-00:10 | 80112.09 | 01-JUL-16:10 | 69834.39 | 01-JUL-16:10 | 10292.96 | 01-JUL-17:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.613864E+11 | 0.00 | 357.99 | 0.592475E+11 | 0.213891E+10 | 0.00 | 1.00 | 01-AUG-16:10 | 0.00 | 01-AUG-00:05 | 77574.64 | 31-AUG-16:10 | 74706.13 | 31-AUG-18:00 | 2869.46 | 31-AUG-17:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.576147E+11 | 0.00 | 336.90 | 0.535758E+11 | 0.403883E+10 | 0.00 | 1.00 | 01-SEP-16:10 | 0.00 | 01-SEP-00:05 | 75579.37 | 30-SEP-16:10 | 69964.61 | 30-SEP-21:51 | 5618.02 | 30-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.549324E+11 | 0.00 | 349.98 | 0.549324E+11 | -0.0 | 0.00 | 1.00 | 01-OCT-16:10 | 0.00 | 01-OCT-00:20 | 69975.11 | 31-OCT-16:30 | 69975.11 | 31-OCT-18:00 | 0.00 | 01-OCT-17:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.445127E+11 | 0.00 | 351.26 | 0.445127E+11 | 0.00 | 0.00 | 1.00 | 01-NOV-16:10 | 0.00 | 01-NOV-00:05 | 58431.21 | 30-NOV-17:50 | 58431.21 | 30-NOV-17:10 | 0.00 | 23-NOV-21:20 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.412914E+11 | 0.00 | 382.56 | 0.412914E+11 | -0.0 | 0.00 | 1.00 | 01-DEC-17:10 | 0.00 | 01-DEC-00:10 | 52271.29 | 31-DEC-17:40 | 52271.29 | 31-DEC-22:30 | 0.00 | 08-DEC-18:40 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.623924E+12 | 0.00 | 4190.38 | 0.609728E+12 | 0.141958E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.409484E+11 | 0.00 | 324.28 | 0.409484E+11 | -0.0 | 0.00 | 1.00 | 0.00 | 52271.29 | 52271.29 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.634304E+11 | 0.00 | 382.56 | 0.592475E+11 | 0.801471E+10 | 0.00 | 1.00 | 0.00 | 80112.09 | 77490.29 | 10292.96 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.642902E+10 | 0.00 | 211.67 | 0.642902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88484.69 | 03-JAN-17:00 | 88484.69 | 03-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.327012E+11 | 0.00 | 257.60 | 0.327012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 122631.28 | 21-FEB-16:17 | 122631.28 | 21-FEB-16:17 | 0.00 | 0.00 | 0.00 |
March | 0.664433E+11 | 0.00 | 360.85 | 0.664433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 155042.16 | 14-MAR-18:07 | 155042.16 | 14-MAR-18:07 | 0.00 | 0.00 | 0.00 |
April | 0.206560E+12 | 0.00 | 556.94 | 0.206560E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 227985.57 | 19-APR-21:00 | 227985.57 | 19-APR-21:00 | 0.00 | 0.00 | 0.00 |
May | 0.342895E+12 | 0.00 | 711.33 | 0.341104E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 254803.99 | 19-MAY-20:10 | 254803.99 | 19-MAY-20:10 | 0.00 | 0.00 | 0.00 |
June | 0.444600E+12 | 0.00 | 720.00 | 0.439222E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 300640.42 | 19-JUN-18:03 | 279008.31 | 02-JUN-18:17 | 0.00 | 0.00 | 0.00 |
July | 0.597339E+12 | 0.00 | 744.00 | 0.457876E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 500101.87 | 21-JUL-21:00 | 266365.69 | 03-JUL-18:03 | 0.00 | 0.00 | 0.00 |
August | 0.481229E+12 | 0.00 | 744.00 | 0.427960E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 432043.80 | 01-AUG-20:50 | 273612.36 | 04-AUG-20:10 | 0.00 | 0.00 | 0.00 |
September | 0.393129E+12 | 0.00 | 692.17 | 0.336481E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 325691.67 | 09-SEP-20:10 | 252972.50 | 19-SEP-18:20 | 0.00 | 0.00 | 0.00 |
October | 0.193994E+12 | 0.00 | 536.00 | 0.185120E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 371374.57 | 03-OCT-19:55 | 234679.91 | 04-OCT-20:10 | 0.00 | 0.00 | 0.00 |
November | 0.405207E+11 | 0.00 | 318.45 | 0.405207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 145211.24 | 03-NOV-15:45 | 145211.24 | 03-NOV-15:45 | 0.00 | 0.00 | 0.00 |
December | 0.373143E+10 | 0.00 | 243.82 | 0.373143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49192.85 | 09-DEC-13:00 | 49192.85 | 09-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.280957E+13 | 0.00 | 6096.84 | 0.254415E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.373143E+10 | 0.00 | 211.67 | 0.373143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49192.85 | 49192.85 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.597339E+12 | 0.00 | 744.00 | 0.457876E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 500101.87 | 279008.31 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.424273E+09 | 0.00 | 40.67 | 0.424273E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11015.35 | 03-JAN-17:00 | 11015.35 | 03-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.213296E+10 | 0.00 | 104.33 | 0.213296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14306.39 | 20-FEB-16:01 | 14306.39 | 20-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.440437E+10 | 0.00 | 187.50 | 0.440437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14861.84 | 22-MAR-15:01 | 14861.84 | 22-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.144291E+11 | 0.00 | 416.17 | 0.144291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17663.28 | 21-APR-15:01 | 17663.28 | 21-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.237049E+11 | 0.00 | 559.50 | 0.232460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20731.76 | 24-MAY-13:00 | 18530.64 | 19-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.293775E+11 | 0.00 | 570.00 | 0.284061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24602.30 | 27-JUN-24:00 | 19667.71 | 15-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.398593E+11 | 0.00 | 589.00 | 0.299764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39000.15 | 21-JUL-08:10 | 19635.99 | 02-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.333129E+11 | 0.00 | 589.00 | 0.282020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33593.25 | 01-AUG-21:51 | 19065.47 | 06-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.283146E+11 | 0.00 | 543.50 | 0.220359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32023.54 | 22-SEP-08:04 | 18180.37 | 19-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.135551E+11 | 0.00 | 400.67 | 0.123159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27870.90 | 03-OCT-20:20 | 17911.03 | 01-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.268469E+10 | 0.00 | 138.17 | 0.268469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14525.56 | 09-NOV-16:02 | 14525.56 | 09-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.217497E+09 | 0.00 | 33.00 | 0.217497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5697.71 | 10-DEC-14:00 | 5697.71 | 10-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192417E+12 | 0.00 | 4171.50 | 0.168475E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.217497E+09 | 0.00 | 33.00 | 0.217497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5697.71 | 5697.71 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.398593E+11 | 0.00 | 589.00 | 0.299764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39000.15 | 19667.71 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.950315E+09 | 0.00 | 213.87 | 0.807515E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13363.75 | 09-JAN-16:01 | 13363.75 | 09-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.138591E+10 | 0.00 | 283.98 | 0.136374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14194.88 | 20-FEB-16:01 | 14194.88 | 20-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.253544E+10 | 0.00 | 432.28 | 0.249474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14344.35 | 21-MAR-15:01 | 14344.35 | 21-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.558333E+10 | 0.00 | 623.21 | 0.492586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14638.51 | 01-APR-15:01 | 14638.51 | 01-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.852412E+10 | 0.00 | 699.17 | 0.661682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14637.83 | 11-MAY-15:01 | 14637.83 | 11-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.107044E+11 | 0.00 | 692.68 | 0.788237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14632.82 | 14-JUN-08:61 | 14632.82 | 14-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.112505E+11 | 0.00 | 716.12 | 0.740440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16010.52 | 19-JUL-08:61 | 13548.18 | 25-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.104761E+11 | 0.00 | 709.75 | 0.690032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14778.42 | 02-AUG-08:61 | 13583.33 | 26-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.972482E+10 | 0.00 | 687.02 | 0.649196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15118.34 | 09-SEP-08:61 | 13918.09 | 24-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.652531E+10 | 0.00 | 672.31 | 0.441329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14635.53 | 04-OCT-08:61 | 13993.76 | 31-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.251522E+10 | 0.00 | 411.15 | 0.222653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14203.74 | 08-NOV-16:01 | 14203.74 | 08-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.600530E+09 | 0.00 | 165.79 | 0.568198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13417.29 | 23-DEC-16:01 | 13417.29 | 23-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.707760E+11 | 0.00 | 6307.33 | 0.520958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.600530E+09 | 0.00 | 165.79 | 0.568198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13363.75 | 13363.75 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.112505E+11 | 0.00 | 716.12 | 0.788237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16010.52 | 14638.51 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.168576E+09 | 0.00 | 46.20 | 0.140748E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13110.18 | 04-JAN-16:01 | 13110.18 | 04-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.267424E+09 | 0.00 | 90.75 | 0.262020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14080.15 | 20-FEB-16:01 | 14080.15 | 20-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.879893E+09 | 0.00 | 233.37 | 0.855620E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14228.91 | 21-MAR-15:01 | 14228.91 | 21-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.412449E+10 | 0.00 | 493.96 | 0.355168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15422.04 | 17-APR-18:01 | 15422.04 | 17-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.772159E+10 | 0.00 | 592.07 | 0.603340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15666.76 | 28-MAY-08:51 | 15554.80 | 20-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.103009E+11 | 0.00 | 618.18 | 0.775829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16368.79 | 04-JUN-08:51 | 16018.53 | 14-JUN-08:11 | 0.00 | 0.00 | 0.00 |
July | 0.106455E+11 | 0.00 | 634.76 | 0.721716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18002.70 | 22-JUL-08:31 | 14004.10 | 11-JUL-07:51 | 0.00 | 0.00 | 0.00 |
August | 0.928664E+10 | 0.00 | 607.70 | 0.620537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17695.42 | 03-AUG-08:61 | 14350.39 | 27-AUG-07:51 | 0.00 | 0.00 | 0.00 |
September | 0.740939E+10 | 0.00 | 544.88 | 0.477160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17034.35 | 03-SEP-08:51 | 14247.85 | 29-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.350047E+10 | 0.00 | 470.69 | 0.200180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15356.28 | 05-OCT-08:51 | 13880.91 | 31-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.627700E+09 | 0.00 | 187.63 | 0.492854E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14090.46 | 08-NOV-16:01 | 14090.46 | 08-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 78581646.84 | 0.00 | 20.04 | 73402767.72 | 0.00 | 0.00 | 0.00 | 0.00 | 13121.43 | 16-DEC-16:01 | 13121.43 | 16-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.550112E+11 | 0.00 | 4540.22 | 0.393640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 78581646.84 | 0.00 | 20.04 | 73402767.72 | 0.00 | 0.00 | 0.00 | 0.00 | 13110.18 | 13110.18 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.106455E+11 | 0.00 | 634.76 | 0.775829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18002.70 | 16018.53 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.227076E+11 | 0.00 | 418.34 | 0.226374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42456.75 | 12-JAN-14:25 | 42456.75 | 12-JAN-14:25 | 0.00 | 0.00 | 0.00 |
February | 0.226305E+11 | 0.00 | 445.11 | 0.223738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39783.78 | 07-FEB-13:40 | 39783.78 | 07-FEB-13:40 | 0.00 | 0.00 | 0.00 |
March | 0.210716E+11 | 0.00 | 514.45 | 0.210528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31212.62 | 07-MAR-13:40 | 31212.62 | 07-MAR-13:40 | 0.00 | 0.00 | 0.00 |
April | 0.281599E+11 | 0.00 | 642.38 | 0.235914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29280.10 | 03-APR-14:00 | 29145.92 | 03-APR-13:40 | 0.00 | 0.00 | 0.00 |
May | 0.340279E+11 | 0.00 | 733.89 | 0.182197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24989.86 | 31-MAY-20:20 | 17683.70 | 06-MAY-20:10 | 0.00 | 0.00 | 0.00 |
June | 0.421831E+11 | 0.00 | 720.00 | 0.217539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28482.64 | 15-JUN-17:17 | 27691.47 | 15-JUN-17:03 | 0.00 | 0.00 | 0.00 |
July | 0.456093E+11 | 0.00 | 743.83 | 0.225371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29906.71 | 26-JUL-16:20 | 21514.59 | 26-JUL-17:20 | 0.00 | 0.00 | 0.00 |
August | 0.471949E+11 | 0.00 | 744.00 | 0.252011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33429.83 | 27-AUG-13:40 | 28032.24 | 27-AUG-13:50 | 0.00 | 0.00 | 0.00 |
September | 0.524454E+11 | 0.00 | 720.00 | 0.331054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42065.32 | 19-SEP-13:30 | 39305.66 | 18-SEP-13:05 | 0.00 | 0.00 | 0.00 |
October | 0.473289E+11 | 0.00 | 708.53 | 0.342970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48209.15 | 22-OCT-13:15 | 40537.62 | 30-OCT-15:03 | 0.00 | 0.00 | 0.00 |
November | 0.339552E+11 | 0.00 | 511.29 | 0.319717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45343.00 | 09-NOV-13:50 | 45343.00 | 09-NOV-13:50 | 0.00 | 0.00 | 0.00 |
December | 0.198136E+11 | 0.00 | 405.77 | 0.198136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36523.58 | 16-DEC-13:40 | 36523.58 | 16-DEC-13:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.417128E+12 | 0.00 | 7307.58 | 0.296555E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.198136E+11 | 0.00 | 405.77 | 0.182197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24989.86 | 17683.70 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.524454E+11 | 0.00 | 744.00 | 0.342970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48209.15 | 45343.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.282604E+10 | 0.00 | 181.79 | 0.254623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76019.25 | 03-JAN-16:01 | 76019.25 | 03-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.551905E+10 | 0.00 | 250.38 | 0.511090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83362.78 | 20-FEB-16:01 | 83362.78 | 20-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.114758E+11 | 0.00 | 367.41 | 0.111147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86300.14 | 22-MAR-15:01 | 86300.14 | 22-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.286107E+11 | 0.00 | 453.30 | 0.261203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89723.59 | 21-APR-18:01 | 89723.59 | 21-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.480497E+11 | 0.00 | 536.30 | 0.388085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91718.65 | 20-MAY-08:51 | 91718.65 | 20-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.636494E+11 | 0.00 | 587.87 | 0.486979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94153.54 | 16-JUN-07:21 | 94153.54 | 16-JUN-07:21 | 0.00 | 0.00 | 0.00 |
July | 0.693453E+11 | 0.00 | 602.95 | 0.465661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105306.90 | 22-JUL-08:31 | 86066.08 | 11-JUL-07:51 | 0.00 | 0.00 | 0.00 |
August | 0.589842E+11 | 0.00 | 557.90 | 0.385546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102467.25 | 03-AUG-08:61 | 84281.55 | 11-AUG-07:51 | 0.00 | 0.00 | 0.00 |
September | 0.449438E+11 | 0.00 | 482.63 | 0.284537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99493.69 | 03-SEP-08:51 | 84239.89 | 29-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.271272E+11 | 0.00 | 411.54 | 0.180339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93584.44 | 03-OCT-21:51 | 86699.34 | 30-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.716806E+10 | 0.00 | 295.84 | 0.598611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84472.85 | 09-NOV-16:02 | 84472.85 | 09-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.195537E+10 | 0.00 | 135.49 | 0.187496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75215.34 | 09-DEC-09:02 | 75215.34 | 09-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.369655E+12 | 0.00 | 4863.41 | 0.271868E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.195537E+10 | 0.00 | 135.49 | 0.187496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75215.34 | 75215.34 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.693453E+11 | 0.00 | 602.95 | 0.486979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105306.90 | 94153.54 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.849987E+09 | 0.00 | 208.21 | 0.712731E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11706.13 | 10-JAN-16:01 | 11706.13 | 10-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.158609E+10 | 0.00 | 324.88 | 0.152734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12452.64 | 20-FEB-16:01 | 12452.64 | 20-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.260622E+10 | 0.00 | 469.75 | 0.255810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12584.42 | 21-MAR-15:01 | 12584.42 | 21-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.589031E+10 | 0.00 | 662.65 | 0.523721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12838.27 | 03-APR-15:01 | 12838.27 | 03-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.873098E+10 | 0.00 | 725.79 | 0.686550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12839.92 | 11-MAY-15:01 | 12839.92 | 11-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.110204E+11 | 0.00 | 707.25 | 0.828937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12834.84 | 14-JUN-08:61 | 12834.84 | 14-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.115541E+11 | 0.00 | 729.26 | 0.778692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14105.14 | 19-JUL-08:61 | 11869.38 | 18-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.107271E+11 | 0.00 | 724.41 | 0.723006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12472.70 | 14-AUG-08:62 | 11713.59 | 18-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.979269E+10 | 0.00 | 703.01 | 0.658785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12534.48 | 22-SEP-08:61 | 12206.12 | 24-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.608615E+10 | 0.00 | 675.07 | 0.409383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13294.93 | 14-OCT-15:01 | 12276.25 | 31-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.241170E+10 | 0.00 | 421.35 | 0.215730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12459.41 | 08-NOV-16:01 | 12459.41 | 08-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.625983E+09 | 0.00 | 161.40 | 0.556050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11766.92 | 23-DEC-16:01 | 11766.92 | 23-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.718818E+11 | 0.00 | 6513.03 | 0.536023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.625983E+09 | 0.00 | 161.40 | 0.556050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11706.13 | 11706.13 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.115541E+11 | 0.00 | 729.26 | 0.828937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14105.14 | 12839.92 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.111179E+09 | 0.00 | 42.07 | 74422192.90 | 0.00 | 0.00 | 0.00 | 0.00 | 11119.02 | 31-JAN-09:01 | 11119.02 | 31-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.450143E+09 | 0.00 | 121.34 | 0.409359E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12359.21 | 20-FEB-16:01 | 12359.21 | 20-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.112935E+10 | 0.00 | 269.05 | 0.110283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12490.00 | 21-MAR-15:01 | 12490.00 | 21-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.440325E+10 | 0.00 | 537.01 | 0.385332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14060.04 | 21-APR-08:51 | 14060.04 | 21-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.766170E+10 | 0.00 | 613.06 | 0.592730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14710.64 | 20-MAY-08:51 | 14710.64 | 20-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.104140E+11 | 0.00 | 629.66 | 0.792076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16226.27 | 14-JUN-07:52 | 16226.27 | 14-JUN-07:52 | 0.00 | 0.00 | 0.00 |
July | 0.107838E+11 | 0.00 | 643.93 | 0.739686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16603.99 | 04-JUL-08:62 | 13668.34 | 04-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.935768E+10 | 0.00 | 621.43 | 0.626396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15768.62 | 03-AUG-08:61 | 13461.26 | 26-AUG-08:11 | 0.00 | 0.00 | 0.00 |
September | 0.727271E+10 | 0.00 | 560.39 | 0.461884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15779.61 | 23-SEP-08:51 | 13088.62 | 19-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.329742E+10 | 0.00 | 481.94 | 0.197505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14572.63 | 05-OCT-08:51 | 12665.89 | 05-OCT-08:51 | 0.00 | 0.00 | 0.00 |
November | 0.633563E+09 | 0.00 | 167.76 | 0.527619E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12574.69 | 09-NOV-09:51 | 12574.69 | 09-NOV-09:51 | 0.00 | 0.00 | 0.00 |
December | 74770543.92 | 0.00 | 27.61 | 59019809.51 | 0.00 | 0.00 | 0.00 | 0.00 | 11320.54 | 16-DEC-09:01 | 11320.54 | 16-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.555895E+11 | 0.00 | 4715.24 | 0.401293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 74770543.92 | 0.00 | 27.61 | 59019809.51 | 0.00 | 0.00 | 0.00 | 0.00 | 11119.02 | 11119.02 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.107838E+11 | 0.00 | 643.93 | 0.792076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16603.99 | 16226.27 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.190740E+09 | 0.00 | 146.43 | 0.163089E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3578.14 | 09-JAN-16:01 | 3578.14 | 09-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.297413E+09 | 0.00 | 198.43 | 0.293596E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3800.64 | 20-FEB-16:01 | 3800.64 | 20-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.564324E+09 | 0.00 | 331.30 | 0.556135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3840.57 | 21-MAR-15:01 | 3840.57 | 21-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.136084E+10 | 0.00 | 587.60 | 0.119467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3918.50 | 03-APR-15:01 | 3918.50 | 03-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.213556E+10 | 0.00 | 693.66 | 0.163645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3977.57 | 28-MAY-08:61 | 3918.96 | 17-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.278761E+10 | 0.00 | 693.26 | 0.203591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3919.42 | 04-JUN-08:61 | 3917.32 | 14-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.293012E+10 | 0.00 | 716.26 | 0.191087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4532.23 | 19-JUL-08:61 | 3631.74 | 26-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.268595E+10 | 0.00 | 709.61 | 0.175510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4116.49 | 02-AUG-08:61 | 3593.55 | 07-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.241083E+10 | 0.00 | 682.87 | 0.158140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4244.61 | 09-SEP-08:61 | 3725.58 | 24-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.149306E+10 | 0.00 | 616.39 | 0.997762E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4088.97 | 04-OCT-08:61 | 3746.79 | 31-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.515712E+09 | 0.00 | 316.78 | 0.455612E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3802.81 | 08-NOV-16:01 | 3802.81 | 08-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.120803E+09 | 0.00 | 105.38 | 0.113629E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3592.40 | 23-DEC-16:01 | 3592.40 | 23-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174930E+11 | 0.00 | 5798.00 | 0.126942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.120803E+09 | 0.00 | 105.38 | 0.113629E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3578.14 | 3578.14 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.293012E+10 | 0.00 | 716.26 | 0.203591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4532.23 | 3918.96 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 29510887.60 | 0.00 | 26.72 | 23028262.38 | 0.00 | 0.00 | 0.00 | 0.00 | 3419.26 | 30-JAN-16:01 | 3419.26 | 30-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 44993977.33 | 0.00 | 52.23 | 43812721.50 | 0.00 | 0.00 | 0.00 | 0.00 | 3766.22 | 20-FEB-16:01 | 3766.22 | 20-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.166859E+09 | 0.00 | 156.16 | 0.162859E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3806.14 | 21-MAR-15:01 | 3806.14 | 21-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.101117E+10 | 0.00 | 466.13 | 0.867036E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4124.63 | 17-APR-18:01 | 4124.63 | 17-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.196770E+10 | 0.00 | 591.99 | 0.152020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4197.87 | 28-MAY-08:51 | 4161.98 | 20-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.271879E+10 | 0.00 | 620.30 | 0.204080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4411.59 | 04-JUN-08:51 | 4267.71 | 14-JUN-08:11 | 0.00 | 0.00 | 0.00 |
July | 0.280875E+10 | 0.00 | 636.89 | 0.189956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4902.63 | 22-JUL-08:31 | 3708.11 | 11-JUL-07:51 | 0.00 | 0.00 | 0.00 |
August | 0.241775E+10 | 0.00 | 609.77 | 0.160475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4809.30 | 03-AUG-08:61 | 3804.22 | 27-AUG-07:51 | 0.00 | 0.00 | 0.00 |
September | 0.185869E+10 | 0.00 | 545.06 | 0.117892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4642.89 | 03-SEP-08:51 | 3782.83 | 29-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.750572E+09 | 0.00 | 410.88 | 0.423879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4161.07 | 05-OCT-08:51 | 3712.95 | 31-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 94928695.89 | 0.00 | 98.99 | 71387226.96 | 0.00 | 0.00 | 0.00 | 0.00 | 3715.22 | 07-NOV-16:01 | 3715.22 | 07-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 13517306.43 | 0.00 | 12.64 | 12385036.40 | 0.00 | 0.00 | 0.00 | 0.00 | 3509.75 | 16-DEC-16:01 | 3509.75 | 16-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138832E+11 | 0.00 | 4227.76 | 0.984862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 13517306.43 | 0.00 | 12.64 | 12385036.40 | 0.00 | 0.00 | 0.00 | 0.00 | 3419.26 | 3419.26 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.280875E+10 | 0.00 | 636.89 | 0.204080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4902.63 | 4267.71 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.498352E+10 | 0.00 | 423.74 | 0.455005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15749.82 | 09-JAN-16:01 | 15749.82 | 09-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.491816E+10 | 0.00 | 438.74 | 0.479998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16728.84 | 20-FEB-16:01 | 16728.84 | 20-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.482509E+10 | 0.00 | 511.25 | 0.472469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16904.50 | 21-MAR-15:01 | 16904.50 | 21-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.705511E+10 | 0.00 | 619.42 | 0.613025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17244.12 | 04-APR-15:01 | 17244.12 | 04-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.926213E+10 | 0.00 | 691.79 | 0.667045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17175.80 | 28-MAY-08:61 | 16999.20 | 05-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.120760E+11 | 0.00 | 686.93 | 0.831266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17243.54 | 16-JUN-08:61 | 17243.54 | 16-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.135468E+11 | 0.00 | 710.63 | 0.843069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20496.55 | 20-JUL-08:61 | 16003.11 | 16-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.133683E+11 | 0.00 | 707.67 | 0.870832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18195.05 | 02-AUG-08:61 | 15958.49 | 26-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.137074E+11 | 0.00 | 688.31 | 0.936490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18577.72 | 09-SEP-08:61 | 16385.94 | 24-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.113432E+11 | 0.00 | 678.96 | 0.842885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17563.46 | 04-OCT-08:61 | 16490.23 | 31-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.725445E+10 | 0.00 | 508.90 | 0.677446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16405.13 | 14-NOV-16:01 | 16405.13 | 14-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.454817E+10 | 0.00 | 396.72 | 0.430954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15812.55 | 23-DEC-16:01 | 15812.55 | 23-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106888E+12 | 0.00 | 7063.05 | 0.812048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.454817E+10 | 0.00 | 396.72 | 0.430954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15749.82 | 15749.82 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.137074E+11 | 0.00 | 710.63 | 0.936490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20496.55 | 17244.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 706.15 | 535.07 | 171.08 | 953.16 | 477.19 | 0.00 | 0.00 | 0.00 |
February | 664.38 | 471.17 | 193.21 | 915.95 | 421.85 | 0.00 | 0.00 | 0.00 |
March | 519.74 | 294.46 | 225.28 | 742.09 | 366.67 | 0.00 | 0.00 | 0.00 |
April | 362.15 | 135.95 | 226.20 | 586.63 | 217.05 | 0.00 | 0.00 | 0.00 |
May | 257.00 | 37.69 | 219.31 | 466.76 | 122.94 | 0.00 | 0.00 | 0.00 |
June | 219.82 | 13.83 | 205.99 | 484.59 | 58.52 | 0.00 | 0.00 | 0.00 |
July | 223.23 | 19.79 | 203.44 | 492.51 | 43.59 | 0.00 | 0.00 | 0.00 |
August | 281.79 | 71.59 | 210.20 | 579.96 | 66.64 | 0.00 | 0.00 | 0.00 |
September | 446.25 | 231.85 | 214.40 | 827.31 | 147.75 | 0.00 | 0.00 | 0.00 |
October | 612.55 | 416.17 | 196.38 | 973.66 | 241.20 | 0.00 | 0.00 | 0.00 |
November | 737.24 | 563.91 | 173.33 | 1040.18 | 405.03 | 0.00 | 0.00 | 0.00 |
December | 724.95 | 544.65 | 180.31 | 960.19 | 513.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 478.50 | 276.88 | 201.63 | 750.76 | 256.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 219.82 | 13.83 | 171.08 | 466.76 | 43.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 737.24 | 563.91 | 226.20 | 1040.18 | 513.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1988.48 | 1506.73 | 481.75 | 2639.37 | 1463.46 | 0.00 | 0.00 | 0.00 |
February | 1870.85 | 1326.79 | 544.06 | 2531.09 | 1300.26 | 0.00 | 0.00 | 0.00 |
March | 1463.55 | 829.18 | 634.37 | 2041.01 | 1135.03 | 0.00 | 0.00 | 0.00 |
April | 1019.80 | 382.82 | 636.98 | 1618.06 | 671.28 | 0.00 | 0.00 | 0.00 |
May | 723.68 | 106.13 | 617.55 | 1296.31 | 372.71 | 0.00 | 0.00 | 0.00 |
June | 618.99 | 38.95 | 580.04 | 1363.43 | 169.73 | 0.00 | 0.00 | 0.00 |
July | 628.60 | 55.73 | 572.87 | 1383.49 | 127.33 | 0.00 | 0.00 | 0.00 |
August | 793.51 | 201.60 | 591.90 | 1624.49 | 197.69 | 0.00 | 0.00 | 0.00 |
September | 1256.61 | 652.87 | 603.74 | 2313.86 | 428.33 | 0.00 | 0.00 | 0.00 |
October | 1724.89 | 1171.91 | 552.99 | 2713.87 | 725.17 | 0.00 | 0.00 | 0.00 |
November | 2076.02 | 1587.93 | 488.09 | 2887.20 | 1229.86 | 0.00 | 0.00 | 0.00 |
December | 2041.42 | 1533.69 | 507.73 | 2653.43 | 1564.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1347.44 | 779.68 | 567.76 | 2085.64 | 779.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 618.99 | 38.95 | 481.75 | 1296.31 | 127.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2076.02 | 1587.93 | 636.98 | 2887.20 | 1564.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2583.15 | 1957.32 | 625.82 | 3499.83 | 1951.06 | 0.00 | 0.00 | 0.00 |
February | 2430.34 | 1723.58 | 706.76 | 3361.16 | 1727.69 | 0.00 | 0.00 | 0.00 |
March | 1901.24 | 1077.15 | 824.09 | 2714.65 | 1511.55 | 0.00 | 0.00 | 0.00 |
April | 1324.78 | 497.31 | 827.47 | 2160.22 | 889.97 | 0.00 | 0.00 | 0.00 |
May | 940.11 | 137.87 | 802.24 | 1731.35 | 492.68 | 0.00 | 0.00 | 0.00 |
June | 804.10 | 50.59 | 753.51 | 1828.90 | 221.98 | 0.00 | 0.00 | 0.00 |
July | 816.59 | 72.40 | 744.19 | 1855.14 | 165.73 | 0.00 | 0.00 | 0.00 |
August | 1030.81 | 261.90 | 768.91 | 2173.91 | 256.72 | 0.00 | 0.00 | 0.00 |
September | 1632.41 | 848.12 | 784.29 | 3081.42 | 554.43 | 0.00 | 0.00 | 0.00 |
October | 2240.73 | 1522.37 | 718.36 | 3597.81 | 950.42 | 0.00 | 0.00 | 0.00 |
November | 2696.87 | 2062.81 | 634.06 | 3821.10 | 1633.53 | 0.00 | 0.00 | 0.00 |
December | 2651.92 | 1992.35 | 659.58 | 3516.77 | 2091.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1750.40 | 1012.84 | 737.56 | 2774.34 | 1033.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 804.10 | 50.59 | 625.82 | 1731.35 | 165.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2696.87 | 2062.81 | 827.47 | 3821.10 | 2091.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 191.22 | 92.20 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 183.85 | 80.87 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 147.78 | 70.33 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 119.06 | 37.39 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 99.13 | 17.65 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 108.71 | 6.18 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 109.99 | 3.47 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 125.49 | 6.95 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 170.76 | 20.69 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 197.53 | 40.44 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 209.49 | 75.81 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 193.53 | 99.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 154.50 | 45.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 99.13 | 3.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 209.49 | 99.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 116.71 | 189.44 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 141.89 | 166.04 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 215.86 | 135.84 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 294.54 | 68.94 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 359.11 | 32.61 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 401.55 | 11.45 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 362.00 | 6.30 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 334.05 | 12.86 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 315.18 | 39.07 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 233.98 | 79.07 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 156.27 | 156.08 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 104.49 | 208.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 253.46 | 91.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 104.49 | 6.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 401.55 | 208.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 5.24 | 102.05 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 12.87 | 89.57 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 25.02 | 74.66 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 49.14 | 37.58 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 81.80 | 17.15 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 113.71 | 6.18 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 106.02 | 3.59 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 83.43 | 7.21 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 60.48 | 21.98 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 32.59 | 44.37 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 9.51 | 84.72 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 3.81 | 112.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 48.82 | 49.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 3.81 | 3.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 113.71 | 112.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 122.67 | 183.75 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 147.23 | 162.31 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 218.66 | 135.43 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 294.67 | 70.75 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 357.27 | 34.14 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 398.75 | 12.02 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 359.33 | 6.86 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 332.71 | 13.87 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 315.70 | 40.97 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 235.85 | 81.17 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 161.31 | 152.76 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 110.50 | 202.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 255.02 | 91.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 110.50 | 6.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 398.75 | 202.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.67 | 84.62 | 27.06 | 139.79 | 101.55 | 0.00 | 0.00 | 0.00 |
February | 105.07 | 74.51 | 30.55 | 133.51 | 91.38 | 0.00 | 0.00 | 0.00 |
March | 82.19 | 46.57 | 35.63 | 104.60 | 80.35 | 0.00 | 0.00 | 0.00 |
April | 57.27 | 21.50 | 35.77 | 81.95 | 50.54 | 0.00 | 0.00 | 0.00 |
May | 40.64 | 5.96 | 34.68 | 63.76 | 30.28 | 0.00 | 0.00 | 0.00 |
June | 34.76 | 2.19 | 32.58 | 67.76 | 15.79 | 0.00 | 0.00 | 0.00 |
July | 35.30 | 3.13 | 32.17 | 68.54 | 13.44 | 0.00 | 0.00 | 0.00 |
August | 44.56 | 11.32 | 33.24 | 82.80 | 18.70 | 0.00 | 0.00 | 0.00 |
September | 70.57 | 36.67 | 33.91 | 123.12 | 34.07 | 0.00 | 0.00 | 0.00 |
October | 96.87 | 65.81 | 31.06 | 144.47 | 53.78 | 0.00 | 0.00 | 0.00 |
November | 116.59 | 89.18 | 27.41 | 154.26 | 85.80 | 0.00 | 0.00 | 0.00 |
December | 114.65 | 86.13 | 28.51 | 140.81 | 106.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 43.79 | 31.89 | 108.60 | 56.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.76 | 2.19 | 27.06 | 63.76 | 13.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 116.59 | 89.18 | 35.77 | 154.26 | 106.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.32 | 0.00 | 16.32 | 3.96 | 83.82 | 0.00 | 0.00 | 0.00 |
February | 19.93 | 0.00 | 19.93 | 10.59 | 72.67 | 0.00 | 0.00 | 0.00 |
March | 26.09 | 0.00 | 26.09 | 21.36 | 59.10 | 0.00 | 0.00 | 0.00 |
April | 30.29 | 0.39 | 29.91 | 42.51 | 28.34 | 0.00 | 0.00 | 0.00 |
May | 35.78 | 2.64 | 33.15 | 70.05 | 12.29 | 0.00 | 0.00 | 0.00 |
June | 38.05 | 4.74 | 33.31 | 96.84 | 4.00 | 0.00 | 0.00 | 0.00 |
July | 35.16 | 3.45 | 31.71 | 90.41 | 2.09 | 0.00 | 0.00 | 0.00 |
August | 29.73 | 0.71 | 29.03 | 71.86 | 4.72 | 0.00 | 0.00 | 0.00 |
September | 25.87 | 0.03 | 25.84 | 52.44 | 15.50 | 0.00 | 0.00 | 0.00 |
October | 21.44 | 0.00 | 21.44 | 28.51 | 33.32 | 0.00 | 0.00 | 0.00 |
November | 17.31 | 0.00 | 17.31 | 8.26 | 67.54 | 0.00 | 0.00 | 0.00 |
December | 16.19 | 0.00 | 16.19 | 2.72 | 93.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.04 | 1.00 | 25.04 | 41.79 | 39.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.19 | 0.00 | 16.19 | 2.72 | 2.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.05 | 4.74 | 33.31 | 96.84 | 93.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.70 | 55.11 | 46.60 | 98.78 | 180.24 | 0.00 | 0.00 | 0.00 |
February | 136.50 | 77.83 | 58.67 | 156.71 | 155.00 | 0.00 | 0.00 | 0.00 |
March | 168.25 | 92.64 | 75.61 | 212.74 | 125.50 | 0.00 | 0.00 | 0.00 |
April | 202.82 | 112.49 | 90.33 | 311.61 | 62.71 | 0.00 | 0.00 | 0.00 |
May | 209.08 | 113.58 | 95.50 | 365.96 | 29.81 | 0.00 | 0.00 | 0.00 |
June | 209.17 | 116.31 | 92.86 | 419.28 | 10.70 | 0.00 | 0.00 | 0.00 |
July | 187.70 | 98.13 | 89.57 | 381.01 | 6.05 | 0.00 | 0.00 | 0.00 |
August | 178.80 | 91.56 | 87.24 | 348.04 | 12.13 | 0.00 | 0.00 | 0.00 |
September | 177.40 | 101.30 | 76.10 | 314.87 | 35.84 | 0.00 | 0.00 | 0.00 |
October | 135.78 | 73.14 | 62.64 | 202.50 | 74.23 | 0.00 | 0.00 | 0.00 |
November | 121.58 | 70.62 | 50.96 | 137.76 | 145.73 | 0.00 | 0.00 | 0.00 |
December | 101.78 | 53.93 | 47.85 | 94.50 | 197.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.90 | 88.01 | 72.89 | 253.98 | 86.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.70 | 53.93 | 46.60 | 94.50 | 6.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.17 | 116.31 | 95.50 | 419.28 | 197.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 190.50 | 91.70 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 182.33 | 80.68 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 146.33 | 69.87 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 117.76 | 37.24 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 98.22 | 17.42 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 107.99 | 6.00 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 109.36 | 3.34 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 124.95 | 6.81 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 170.17 | 20.38 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 197.15 | 39.71 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 208.80 | 75.19 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 192.74 | 99.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 153.65 | 45.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 98.22 | 3.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 208.80 | 99.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 4.92 | 101.64 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 12.03 | 89.70 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 23.98 | 74.17 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 47.43 | 37.22 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 79.70 | 16.84 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 112.12 | 6.04 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 104.67 | 3.48 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 82.08 | 7.06 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 59.02 | 21.82 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 32.07 | 42.93 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 8.95 | 83.77 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 3.44 | 112.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 47.72 | 49.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 3.44 | 3.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 112.12 | 112.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.70 | 55.11 | 46.60 | 103.83 | 172.88 | 0.00 | 0.00 | 0.00 |
February | 136.50 | 77.83 | 58.67 | 161.79 | 150.32 | 0.00 | 0.00 | 0.00 |
March | 168.25 | 92.64 | 75.61 | 215.94 | 124.35 | 0.00 | 0.00 | 0.00 |
April | 202.82 | 112.49 | 90.33 | 311.10 | 64.21 | 0.00 | 0.00 | 0.00 |
May | 209.08 | 113.58 | 95.50 | 361.44 | 31.14 | 0.00 | 0.00 | 0.00 |
June | 209.17 | 116.31 | 92.86 | 414.15 | 11.16 | 0.00 | 0.00 | 0.00 |
July | 187.70 | 98.13 | 89.57 | 376.49 | 6.55 | 0.00 | 0.00 | 0.00 |
August | 178.80 | 91.56 | 87.24 | 344.58 | 12.92 | 0.00 | 0.00 | 0.00 |
September | 177.40 | 101.30 | 76.10 | 312.72 | 37.39 | 0.00 | 0.00 | 0.00 |
October | 135.78 | 73.14 | 62.64 | 204.72 | 75.31 | 0.00 | 0.00 | 0.00 |
November | 121.58 | 70.62 | 50.96 | 142.64 | 141.22 | 0.00 | 0.00 | 0.00 |
December | 101.78 | 53.93 | 47.85 | 98.84 | 189.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.90 | 88.01 | 72.89 | 254.33 | 84.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.70 | 53.93 | 46.60 | 98.84 | 6.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.17 | 116.31 | 95.50 | 414.15 | 189.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.83 | 0.00 | 25.83 | 5.26 | 139.05 | 0.00 | 0.00 | 0.00 |
February | 31.55 | 0.00 | 31.55 | 15.25 | 121.67 | 0.00 | 0.00 | 0.00 |
March | 41.29 | 0.00 | 41.29 | 32.04 | 99.77 | 0.00 | 0.00 | 0.00 |
April | 47.95 | 0.61 | 47.34 | 63.07 | 52.70 | 0.00 | 0.00 | 0.00 |
May | 56.64 | 4.17 | 52.47 | 102.06 | 27.28 | 0.00 | 0.00 | 0.00 |
June | 60.23 | 7.51 | 52.73 | 139.17 | 12.37 | 0.00 | 0.00 | 0.00 |
July | 55.65 | 5.46 | 50.19 | 128.89 | 8.72 | 0.00 | 0.00 | 0.00 |
August | 47.06 | 1.12 | 45.94 | 100.96 | 14.29 | 0.00 | 0.00 | 0.00 |
September | 40.94 | 0.05 | 40.89 | 74.16 | 35.44 | 0.00 | 0.00 | 0.00 |
October | 33.94 | 0.00 | 33.94 | 39.46 | 63.36 | 0.00 | 0.00 | 0.00 |
November | 27.40 | 0.00 | 27.40 | 10.21 | 118.23 | 0.00 | 0.00 | 0.00 |
December | 25.63 | 0.00 | 25.63 | 3.69 | 152.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.22 | 1.58 | 39.64 | 59.75 | 70.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.63 | 0.00 | 25.63 | 3.69 | 8.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.23 | 7.51 | 52.73 | 139.17 | 152.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.52 | 0.00 | 9.52 | 1.94 | 51.26 | 0.00 | 0.00 | 0.00 |
February | 11.63 | 0.00 | 11.63 | 5.62 | 44.85 | 0.00 | 0.00 | 0.00 |
March | 15.22 | 0.00 | 15.22 | 11.81 | 36.78 | 0.00 | 0.00 | 0.00 |
April | 17.68 | 0.23 | 17.45 | 23.25 | 19.43 | 0.00 | 0.00 | 0.00 |
May | 20.88 | 1.54 | 19.34 | 37.62 | 10.06 | 0.00 | 0.00 | 0.00 |
June | 22.20 | 2.77 | 19.44 | 51.30 | 4.56 | 0.00 | 0.00 | 0.00 |
July | 20.51 | 2.01 | 18.50 | 47.51 | 3.21 | 0.00 | 0.00 | 0.00 |
August | 17.35 | 0.41 | 16.94 | 37.22 | 5.27 | 0.00 | 0.00 | 0.00 |
September | 15.09 | 0.02 | 15.07 | 27.34 | 13.06 | 0.00 | 0.00 | 0.00 |
October | 12.51 | 0.00 | 12.51 | 14.55 | 23.36 | 0.00 | 0.00 | 0.00 |
November | 10.10 | 0.00 | 10.10 | 3.76 | 43.59 | 0.00 | 0.00 | 0.00 |
December | 9.45 | 0.00 | 9.45 | 1.36 | 56.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.20 | 0.58 | 14.61 | 22.03 | 25.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.45 | 0.00 | 9.45 | 1.36 | 3.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.20 | 2.77 | 19.44 | 51.30 | 56.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.15 | 49.36 | 15.78 | 89.95 | 44.74 | 0.00 | 0.00 | 0.00 |
February | 61.29 | 43.47 | 17.82 | 86.49 | 39.54 | 0.00 | 0.00 | 0.00 |
March | 47.95 | 27.17 | 20.78 | 69.73 | 34.64 | 0.00 | 0.00 | 0.00 |
April | 33.41 | 12.54 | 20.87 | 55.92 | 19.87 | 0.00 | 0.00 | 0.00 |
May | 23.71 | 3.48 | 20.23 | 45.31 | 10.81 | 0.00 | 0.00 | 0.00 |
June | 20.28 | 1.28 | 19.00 | 48.26 | 4.77 | 0.00 | 0.00 | 0.00 |
July | 20.59 | 1.83 | 18.77 | 48.69 | 3.38 | 0.00 | 0.00 | 0.00 |
August | 26.00 | 6.60 | 19.39 | 56.48 | 5.48 | 0.00 | 0.00 | 0.00 |
September | 41.17 | 21.39 | 19.78 | 78.68 | 12.91 | 0.00 | 0.00 | 0.00 |
October | 56.51 | 38.39 | 18.12 | 91.83 | 21.99 | 0.00 | 0.00 | 0.00 |
November | 68.01 | 52.02 | 15.99 | 97.97 | 38.05 | 0.00 | 0.00 | 0.00 |
December | 66.88 | 50.25 | 16.63 | 90.99 | 48.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.14 | 25.54 | 18.60 | 71.59 | 23.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.28 | 1.28 | 15.78 | 45.31 | 3.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.01 | 52.02 | 20.87 | 97.97 | 48.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 176.82 | 133.98 | 42.84 | 244.15 | 121.44 | 0.00 | 0.00 | 0.00 |
February | 166.36 | 117.98 | 48.38 | 234.76 | 107.33 | 0.00 | 0.00 | 0.00 |
March | 130.14 | 73.73 | 56.41 | 189.26 | 94.01 | 0.00 | 0.00 | 0.00 |
April | 90.68 | 34.04 | 56.64 | 151.79 | 53.93 | 0.00 | 0.00 | 0.00 |
May | 64.35 | 9.44 | 54.91 | 122.99 | 29.34 | 0.00 | 0.00 | 0.00 |
June | 55.04 | 3.46 | 51.58 | 130.97 | 12.95 | 0.00 | 0.00 | 0.00 |
July | 55.90 | 4.96 | 50.94 | 132.15 | 9.17 | 0.00 | 0.00 | 0.00 |
August | 70.56 | 17.93 | 52.63 | 153.30 | 14.87 | 0.00 | 0.00 | 0.00 |
September | 111.74 | 58.05 | 53.69 | 213.56 | 35.03 | 0.00 | 0.00 | 0.00 |
October | 153.38 | 104.21 | 49.17 | 249.24 | 59.68 | 0.00 | 0.00 | 0.00 |
November | 184.60 | 141.20 | 43.40 | 265.92 | 103.28 | 0.00 | 0.00 | 0.00 |
December | 181.53 | 136.38 | 45.15 | 246.97 | 130.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.82 | 69.33 | 50.49 | 194.30 | 64.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 55.04 | 3.46 | 42.84 | 122.99 | 9.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 184.60 | 141.20 | 56.64 | 265.92 | 130.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 190.38 | 91.09 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 182.93 | 79.77 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 146.74 | 69.36 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 118.13 | 36.53 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 98.81 | 16.90 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 108.69 | 5.78 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 109.67 | 3.21 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 124.95 | 6.54 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 169.67 | 19.97 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 196.41 | 39.54 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 208.71 | 74.53 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 193.07 | 98.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 153.80 | 45.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 98.81 | 3.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 208.71 | 98.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 116.00 | 186.75 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 140.93 | 163.43 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 214.17 | 133.62 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 292.45 | 67.24 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 357.07 | 31.19 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 399.93 | 10.76 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 360.29 | 5.81 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 332.42 | 12.11 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 313.32 | 37.69 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 232.71 | 77.08 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 155.50 | 153.00 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 104.21 | 205.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 252.07 | 89.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 104.21 | 5.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 399.93 | 205.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 5.61 | 100.30 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 13.21 | 87.94 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 25.25 | 73.55 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 48.98 | 36.83 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 81.73 | 16.50 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 113.55 | 5.83 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 105.69 | 3.34 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 83.35 | 6.82 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 60.31 | 21.19 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 32.71 | 43.39 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 10.01 | 82.81 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 4.14 | 110.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 48.90 | 48.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 4.14 | 3.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 113.55 | 110.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 122.82 | 180.70 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 147.00 | 159.40 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 217.38 | 133.26 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 292.67 | 69.23 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 355.35 | 32.73 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 397.19 | 11.29 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 357.67 | 6.35 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 331.24 | 13.07 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 314.15 | 39.45 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 234.90 | 79.25 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 161.45 | 149.13 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 111.04 | 199.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 254.03 | 89.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 111.04 | 6.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 397.19 | 199.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 204.76 | 155.16 | 49.61 | 272.56 | 139.86 | 0.00 | 0.00 | 0.00 |
February | 192.65 | 136.63 | 56.02 | 262.73 | 121.71 | 0.00 | 0.00 | 0.00 |
March | 150.71 | 85.38 | 65.33 | 212.21 | 103.28 | 0.00 | 0.00 | 0.00 |
April | 105.01 | 39.42 | 65.59 | 174.52 | 52.50 | 0.00 | 0.00 | 0.00 |
May | 74.52 | 10.93 | 63.59 | 149.58 | 23.34 | 0.00 | 0.00 | 0.00 |
June | 63.74 | 4.01 | 59.73 | 165.96 | 7.49 | 0.00 | 0.00 | 0.00 |
July | 64.73 | 5.74 | 58.99 | 166.66 | 3.98 | 0.00 | 0.00 | 0.00 |
August | 81.71 | 20.76 | 60.95 | 187.60 | 8.78 | 0.00 | 0.00 | 0.00 |
September | 129.40 | 67.23 | 62.17 | 250.57 | 28.22 | 0.00 | 0.00 | 0.00 |
October | 177.62 | 120.68 | 56.94 | 286.60 | 58.49 | 0.00 | 0.00 | 0.00 |
November | 213.78 | 163.52 | 50.26 | 301.25 | 113.36 | 0.00 | 0.00 | 0.00 |
December | 210.22 | 157.93 | 52.28 | 275.58 | 151.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 138.75 | 80.29 | 58.47 | 225.21 | 67.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.74 | 4.01 | 49.61 | 149.58 | 3.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 213.78 | 163.52 | 65.59 | 301.25 | 151.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.78 | 0.00 | 142.78 | 14.78 | 885.03 | 0.00 | 0.00 | 0.00 |
February | 174.35 | 0.00 | 174.35 | 60.37 | 770.58 | 0.00 | 0.00 | 0.00 |
March | 228.22 | 0.01 | 228.21 | 139.95 | 630.34 | 0.00 | 0.00 | 0.00 |
April | 265.01 | 3.38 | 261.64 | 306.95 | 332.22 | 0.00 | 0.00 | 0.00 |
May | 313.05 | 23.07 | 289.98 | 528.50 | 168.79 | 0.00 | 0.00 | 0.00 |
June | 332.91 | 41.48 | 291.42 | 745.12 | 76.80 | 0.00 | 0.00 | 0.00 |
July | 307.56 | 30.17 | 277.39 | 686.72 | 57.52 | 0.00 | 0.00 | 0.00 |
August | 260.12 | 6.19 | 253.93 | 534.59 | 90.22 | 0.00 | 0.00 | 0.00 |
September | 226.30 | 0.29 | 226.02 | 393.33 | 205.34 | 0.00 | 0.00 | 0.00 |
October | 187.59 | 0.00 | 187.59 | 196.22 | 382.99 | 0.00 | 0.00 | 0.00 |
November | 151.44 | 0.00 | 151.44 | 40.96 | 725.91 | 0.00 | 0.00 | 0.00 |
December | 141.68 | 0.00 | 141.68 | 10.25 | 964.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 227.84 | 8.76 | 219.09 | 306.09 | 439.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.68 | 0.00 | 141.68 | 10.25 | 57.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 332.91 | 41.48 | 291.42 | 745.12 | 964.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.78 | 0.00 | 142.78 | 11.32 | 914.50 | 0.00 | 0.00 | 0.00 |
February | 174.35 | 0.00 | 174.35 | 53.68 | 794.48 | 0.00 | 0.00 | 0.00 |
March | 228.22 | 0.01 | 228.21 | 129.59 | 648.64 | 0.00 | 0.00 | 0.00 |
April | 265.01 | 3.38 | 261.64 | 296.75 | 342.54 | 0.00 | 0.00 | 0.00 |
May | 313.05 | 23.07 | 289.98 | 518.80 | 174.78 | 0.00 | 0.00 | 0.00 |
June | 332.91 | 41.48 | 291.42 | 735.95 | 80.24 | 0.00 | 0.00 | 0.00 |
July | 307.56 | 30.17 | 277.39 | 677.60 | 60.94 | 0.00 | 0.00 | 0.00 |
August | 260.12 | 6.19 | 253.93 | 525.63 | 94.61 | 0.00 | 0.00 | 0.00 |
September | 226.30 | 0.29 | 226.02 | 386.05 | 212.19 | 0.00 | 0.00 | 0.00 |
October | 187.59 | 0.00 | 187.59 | 188.18 | 394.41 | 0.00 | 0.00 | 0.00 |
November | 151.44 | 0.00 | 151.44 | 35.30 | 748.02 | 0.00 | 0.00 | 0.00 |
December | 141.68 | 0.00 | 141.68 | 7.97 | 995.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 227.84 | 8.76 | 219.09 | 298.51 | 453.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.68 | 0.00 | 141.68 | 7.97 | 60.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 332.91 | 41.48 | 291.42 | 735.95 | 995.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 5.03 | 113.58 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 14.51 | 99.70 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 28.86 | 83.26 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 59.90 | 45.21 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 96.05 | 25.19 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 130.03 | 12.81 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 122.38 | 10.04 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 99.59 | 14.14 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 76.97 | 27.43 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 41.93 | 49.34 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 11.77 | 92.59 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 3.69 | 123.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 57.78 | 57.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 3.69 | 10.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 130.03 | 123.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 203.40 | 110.21 | 93.19 | 210.10 | 390.06 | 0.00 | 0.00 | 0.00 |
February | 272.98 | 155.65 | 117.32 | 337.21 | 340.02 | 0.00 | 0.00 | 0.00 |
March | 336.47 | 185.26 | 151.21 | 456.34 | 284.42 | 0.00 | 0.00 | 0.00 |
April | 405.62 | 224.97 | 180.65 | 671.83 | 159.94 | 0.00 | 0.00 | 0.00 |
May | 418.14 | 227.15 | 190.99 | 784.53 | 93.59 | 0.00 | 0.00 | 0.00 |
June | 418.31 | 232.60 | 185.71 | 894.17 | 47.89 | 0.00 | 0.00 | 0.00 |
July | 375.38 | 196.25 | 179.13 | 817.50 | 37.98 | 0.00 | 0.00 | 0.00 |
August | 357.58 | 183.11 | 174.47 | 754.53 | 53.00 | 0.00 | 0.00 | 0.00 |
September | 354.77 | 202.59 | 152.18 | 696.06 | 99.03 | 0.00 | 0.00 | 0.00 |
October | 271.54 | 146.27 | 125.28 | 449.23 | 176.94 | 0.00 | 0.00 | 0.00 |
November | 243.14 | 141.22 | 101.92 | 299.25 | 316.28 | 0.00 | 0.00 | 0.00 |
December | 203.55 | 107.86 | 95.69 | 201.70 | 420.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 321.77 | 176.00 | 145.77 | 548.42 | 201.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 203.40 | 107.86 | 93.19 | 201.70 | 37.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 418.31 | 232.60 | 190.99 | 894.17 | 420.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 196.98 | 101.07 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 190.46 | 89.61 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 154.92 | 78.82 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 129.68 | 45.97 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 111.41 | 26.36 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 122.88 | 12.98 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 124.43 | 10.18 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 140.80 | 14.37 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 187.61 | 27.31 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 209.76 | 47.34 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 218.00 | 82.72 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 199.67 | 107.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 165.36 | 53.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 111.41 | 10.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 218.00 | 107.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.83 | 0.00 | 25.83 | 4.35 | 140.43 | 0.00 | 0.00 | 0.00 |
February | 31.55 | 0.00 | 31.55 | 13.84 | 122.05 | 0.00 | 0.00 | 0.00 |
March | 41.29 | 0.00 | 41.29 | 30.38 | 99.29 | 0.00 | 0.00 | 0.00 |
April | 47.95 | 0.61 | 47.34 | 60.08 | 53.13 | 0.00 | 0.00 | 0.00 |
May | 56.64 | 4.17 | 52.47 | 98.19 | 28.17 | 0.00 | 0.00 | 0.00 |
June | 60.23 | 7.51 | 52.73 | 134.69 | 13.31 | 0.00 | 0.00 | 0.00 |
July | 55.65 | 5.46 | 50.19 | 124.02 | 9.85 | 0.00 | 0.00 | 0.00 |
August | 47.06 | 1.12 | 45.94 | 96.69 | 15.43 | 0.00 | 0.00 | 0.00 |
September | 40.94 | 0.05 | 40.89 | 71.21 | 36.14 | 0.00 | 0.00 | 0.00 |
October | 33.94 | 0.00 | 33.94 | 37.38 | 63.06 | 0.00 | 0.00 | 0.00 |
November | 27.40 | 0.00 | 27.40 | 9.34 | 116.33 | 0.00 | 0.00 | 0.00 |
December | 25.63 | 0.00 | 25.63 | 3.05 | 154.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.22 | 1.58 | 39.64 | 57.16 | 70.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.63 | 0.00 | 25.63 | 3.05 | 9.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.23 | 7.51 | 52.73 | 134.69 | 154.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.11 | 0.00 | 23.11 | 3.90 | 125.64 | 0.00 | 0.00 | 0.00 |
February | 28.22 | 0.00 | 28.22 | 12.38 | 109.20 | 0.00 | 0.00 | 0.00 |
March | 36.94 | 0.00 | 36.94 | 27.18 | 88.83 | 0.00 | 0.00 | 0.00 |
April | 42.90 | 0.55 | 42.35 | 53.76 | 47.54 | 0.00 | 0.00 | 0.00 |
May | 50.68 | 3.73 | 46.94 | 87.85 | 25.21 | 0.00 | 0.00 | 0.00 |
June | 53.89 | 6.72 | 47.17 | 120.51 | 11.91 | 0.00 | 0.00 | 0.00 |
July | 49.79 | 4.88 | 44.90 | 110.96 | 8.81 | 0.00 | 0.00 | 0.00 |
August | 42.11 | 1.00 | 41.11 | 86.51 | 13.81 | 0.00 | 0.00 | 0.00 |
September | 36.63 | 0.05 | 36.59 | 63.71 | 32.33 | 0.00 | 0.00 | 0.00 |
October | 30.37 | 0.00 | 30.37 | 33.44 | 56.42 | 0.00 | 0.00 | 0.00 |
November | 24.51 | 0.00 | 24.51 | 8.36 | 104.08 | 0.00 | 0.00 | 0.00 |
December | 22.93 | 0.00 | 22.93 | 2.73 | 138.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.88 | 1.42 | 35.46 | 51.14 | 63.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.93 | 0.00 | 22.93 | 2.73 | 8.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.89 | 6.72 | 47.17 | 120.51 | 138.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 521.24 | 394.96 | 126.28 | 709.51 | 359.69 | 0.00 | 0.00 | 0.00 |
February | 490.41 | 347.79 | 142.61 | 681.92 | 316.80 | 0.00 | 0.00 | 0.00 |
March | 383.64 | 217.35 | 166.29 | 548.20 | 275.96 | 0.00 | 0.00 | 0.00 |
April | 267.32 | 100.35 | 166.97 | 435.86 | 160.63 | 0.00 | 0.00 | 0.00 |
May | 189.70 | 27.82 | 161.88 | 350.46 | 89.32 | 0.00 | 0.00 | 0.00 |
June | 162.26 | 10.21 | 152.05 | 373.37 | 41.00 | 0.00 | 0.00 | 0.00 |
July | 164.78 | 14.61 | 150.17 | 375.26 | 30.63 | 0.00 | 0.00 | 0.00 |
August | 208.00 | 52.85 | 155.16 | 438.10 | 47.43 | 0.00 | 0.00 | 0.00 |
September | 329.40 | 171.14 | 158.26 | 618.24 | 105.53 | 0.00 | 0.00 | 0.00 |
October | 452.15 | 307.19 | 144.96 | 724.65 | 175.44 | 0.00 | 0.00 | 0.00 |
November | 544.19 | 416.24 | 127.94 | 777.35 | 299.38 | 0.00 | 0.00 | 0.00 |
December | 535.12 | 402.02 | 133.09 | 718.12 | 387.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 353.20 | 204.38 | 148.83 | 561.73 | 190.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.26 | 10.21 | 126.28 | 350.46 | 30.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 544.19 | 416.24 | 166.97 | 777.35 | 387.40 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189136E+10 | 0.143314E+10 | 0.458222E+09 | 0.255293E+10 | 0.127810E+10 |
February | 0.160727E+10 | 0.113986E+10 | 0.467406E+09 | 0.221586E+10 | 0.102055E+10 |
March | 0.139207E+10 | 0.788679E+09 | 0.603391E+09 | 0.198760E+10 | 0.982087E+09 |
April | 0.938702E+09 | 0.352379E+09 | 0.586322E+09 | 0.152055E+10 | 0.562595E+09 |
May | 0.688337E+09 | 0.100947E+09 | 0.587390E+09 | 0.125017E+10 | 0.329292E+09 |
June | 0.569764E+09 | 35850177.24 | 0.533914E+09 | 0.125606E+10 | 0.151693E+09 |
July | 0.597898E+09 | 53010019.83 | 0.544888E+09 | 0.131914E+10 | 0.116748E+09 |
August | 0.754750E+09 | 0.191758E+09 | 0.562992E+09 | 0.155337E+10 | 0.178480E+09 |
September | 0.115668E+10 | 0.600953E+09 | 0.555729E+09 | 0.214437E+10 | 0.382964E+09 |
October | 0.164065E+10 | 0.111467E+10 | 0.525978E+09 | 0.260786E+10 | 0.646029E+09 |
November | 0.191093E+10 | 0.146165E+10 | 0.449279E+09 | 0.269615E+10 | 0.104983E+10 |
December | 0.194172E+10 | 0.145878E+10 | 0.482936E+09 | 0.257176E+10 | 0.137586E+10 |
Annual Sum or Average | 0.150901E+11 | 0.873168E+10 | 0.635845E+10 | 0.236758E+11 | 0.807423E+10 |
Minimum of Months | 0.569764E+09 | 35850177.24 | 0.449279E+09 | 0.125017E+10 | 0.116748E+09 |
Maximum of Months | 0.194172E+10 | 0.146165E+10 | 0.603391E+09 | 0.269615E+10 | 0.137586E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.532594E+10 | 0.403562E+10 | 0.129032E+10 | 0.706929E+10 | 0.391973E+10 |
February | 0.452597E+10 | 0.320978E+10 | 0.131618E+10 | 0.612320E+10 | 0.314560E+10 |
March | 0.391998E+10 | 0.222087E+10 | 0.169911E+10 | 0.546665E+10 | 0.304007E+10 |
April | 0.264332E+10 | 0.992277E+09 | 0.165105E+10 | 0.419402E+10 | 0.173995E+10 |
May | 0.193831E+10 | 0.284261E+09 | 0.165405E+10 | 0.347203E+10 | 0.998263E+09 |
June | 0.160442E+10 | 0.100952E+09 | 0.150347E+10 | 0.353401E+10 | 0.439928E+09 |
July | 0.168364E+10 | 0.149273E+09 | 0.153437E+10 | 0.370555E+10 | 0.341053E+09 |
August | 0.212533E+10 | 0.539978E+09 | 0.158535E+10 | 0.435105E+10 | 0.529502E+09 |
September | 0.325714E+10 | 0.169224E+10 | 0.156490E+10 | 0.599751E+10 | 0.111023E+10 |
October | 0.461996E+10 | 0.313884E+10 | 0.148112E+10 | 0.726882E+10 | 0.194230E+10 |
November | 0.538106E+10 | 0.411592E+10 | 0.126514E+10 | 0.748362E+10 | 0.318779E+10 |
December | 0.546774E+10 | 0.410783E+10 | 0.135992E+10 | 0.710694E+10 | 0.419150E+10 |
Annual Sum or Average | 0.424928E+11 | 0.245878E+11 | 0.179050E+11 | 0.657727E+11 | 0.245859E+11 |
Minimum of Months | 0.160442E+10 | 0.100952E+09 | 0.126514E+10 | 0.347203E+10 | 0.341053E+09 |
Maximum of Months | 0.546774E+10 | 0.411592E+10 | 0.169911E+10 | 0.748362E+10 | 0.419150E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.691870E+10 | 0.524250E+10 | 0.167620E+10 | 0.937396E+10 | 0.522573E+10 |
February | 0.587949E+10 | 0.416969E+10 | 0.170980E+10 | 0.813132E+10 | 0.417964E+10 |
March | 0.509227E+10 | 0.288503E+10 | 0.220724E+10 | 0.727092E+10 | 0.404853E+10 |
April | 0.343383E+10 | 0.128902E+10 | 0.214480E+10 | 0.559928E+10 | 0.230680E+10 |
May | 0.251798E+10 | 0.369271E+09 | 0.214871E+10 | 0.463724E+10 | 0.131959E+10 |
June | 0.208423E+10 | 0.131142E+09 | 0.195309E+10 | 0.474050E+10 | 0.575363E+09 |
July | 0.218715E+10 | 0.193914E+09 | 0.199323E+10 | 0.496880E+10 | 0.443892E+09 |
August | 0.276092E+10 | 0.701462E+09 | 0.205946E+10 | 0.582261E+10 | 0.687600E+09 |
September | 0.423121E+10 | 0.219832E+10 | 0.203289E+10 | 0.798705E+10 | 0.143707E+10 |
October | 0.600158E+10 | 0.407753E+10 | 0.192406E+10 | 0.963638E+10 | 0.254562E+10 |
November | 0.699030E+10 | 0.534681E+10 | 0.164349E+10 | 0.990430E+10 | 0.423412E+10 |
December | 0.710291E+10 | 0.533630E+10 | 0.176661E+10 | 0.941930E+10 | 0.560223E+10 |
Annual Sum or Average | 0.552006E+11 | 0.319410E+11 | 0.232596E+11 | 0.874917E+11 | 0.326062E+11 |
Minimum of Months | 0.208423E+10 | 0.131142E+09 | 0.164349E+10 | 0.463724E+10 | 0.443892E+09 |
Maximum of Months | 0.710291E+10 | 0.534681E+10 | 0.220724E+10 | 0.990430E+10 | 0.560223E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.512160E+09 | 0.246951E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.444762E+09 | 0.195634E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.395819E+09 | 0.188368E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.308597E+09 | 96916419.68 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.265497E+09 | 47269911.71 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.281772E+09 | 16009881.43 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.294600E+09 | 9304678.39 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.336109E+09 | 18617627.26 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.442599E+09 | 53616545.05 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.529069E+09 | 0.108308E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.543000E+09 | 0.196500E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.518339E+09 | 0.267623E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.487232E+10 | 0.144512E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.265497E+09 | 9304678.39 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.543000E+09 | 0.267623E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.312594E+09 | 0.507401E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.343254E+09 | 0.401682E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.578161E+09 | 0.363843E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.763439E+09 | 0.178689E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.961840E+09 | 87346404.03 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.104083E+10 | 29684746.78 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.969587E+09 | 16867942.68 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.894719E+09 | 34453522.65 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.816948E+09 | 0.101257E+09 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.626705E+09 | 0.211782E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.405040E+09 | 0.404570E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.279858E+09 | 0.558564E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.799297E+10 | 0.289614E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.279858E+09 | 16867942.68 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.104083E+10 | 0.558564E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 14029595.76 | 0.273340E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 31131038.83 | 0.216684E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 67025541.30 | 0.199968E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.127380E+09 | 97399145.48 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.219088E+09 | 45943257.26 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.294737E+09 | 16031274.89 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.283969E+09 | 9615299.05 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.223456E+09 | 19306536.62 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.156763E+09 | 56965593.41 |
October | 71778804.06 | 0.00 | 71778804.06 | 87286179.40 | 0.118835E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 24650492.32 | 0.219583E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 10206204.41 | 0.301574E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.153972E+10 | 0.157524E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 10206204.41 | 9615299.05 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.294737E+09 | 0.301574E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.328572E+09 | 0.492146E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.356187E+09 | 0.392649E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.585660E+09 | 0.362723E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.763788E+09 | 0.183373E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.956917E+09 | 91431540.37 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.103355E+10 | 31164973.79 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.962426E+09 | 18378597.71 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.891139E+09 | 37157001.41 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.818299E+09 | 0.106201E+09 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.631688E+09 | 0.217414E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.418106E+09 | 0.395952E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.295964E+09 | 0.542176E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.804229E+10 | 0.287077E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.295964E+09 | 18378597.71 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.103355E+10 | 0.542176E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.299104E+09 | 0.226640E+09 | 72464826.42 | 0.374421E+09 | 0.271989E+09 |
February | 0.254178E+09 | 0.180261E+09 | 73917324.87 | 0.322980E+09 | 0.221057E+09 |
March | 0.220146E+09 | 0.124724E+09 | 95422629.83 | 0.280152E+09 | 0.215200E+09 |
April | 0.148450E+09 | 55726088.50 | 92723544.22 | 0.212405E+09 | 0.130995E+09 |
May | 0.108857E+09 | 15964013.69 | 92892545.85 | 0.170768E+09 | 81109259.32 |
June | 90105188.78 | 5669429.11 | 84435759.67 | 0.175640E+09 | 40915079.89 |
July | 94554156.30 | 8383125.91 | 86171030.39 | 0.183576E+09 | 36004677.40 |
August | 0.119359E+09 | 30325060.49 | 89033931.16 | 0.221769E+09 | 50073828.02 |
September | 0.182921E+09 | 95036114.58 | 87885276.20 | 0.319126E+09 | 88311679.90 |
October | 0.259457E+09 | 0.176276E+09 | 83180150.54 | 0.386958E+09 | 0.144051E+09 |
November | 0.302200E+09 | 0.231149E+09 | 71050625.13 | 0.399835E+09 | 0.222390E+09 |
December | 0.307068E+09 | 0.230695E+09 | 76373138.43 | 0.377135E+09 | 0.286531E+09 |
Annual Sum or Average | 0.238640E+10 | 0.138085E+10 | 0.100555E+10 | 0.342476E+10 | 0.178863E+10 |
Minimum of Months | 90105188.78 | 5669429.11 | 71050625.13 | 0.170768E+09 | 36004677.40 |
Maximum of Months | 0.307068E+09 | 0.231149E+09 | 95422629.83 | 0.399835E+09 | 0.286531E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 43713969.60 | 0.00 | 43713969.60 | 10593630.19 | 0.224497E+09 |
February | 48213648.10 | 0.00 | 48213648.10 | 25627392.16 | 0.175808E+09 |
March | 69870982.94 | 2765.95 | 69868216.99 | 57200069.18 | 0.158301E+09 |
April | 78518344.10 | 1000279.47 | 77518064.63 | 0.110179E+09 | 73465893.92 |
May | 95843144.60 | 7063304.15 | 88779840.45 | 0.187619E+09 | 32907015.29 |
June | 98633813.54 | 12290815.53 | 86342998.01 | 0.251022E+09 | 10366504.70 |
July | 94160895.41 | 9236150.10 | 84924745.31 | 0.242162E+09 | 5598061.00 |
August | 79637162.39 | 1894638.37 | 77742524.03 | 0.192470E+09 | 12639644.95 |
September | 67049393.63 | 84739.01 | 66964654.62 | 0.135918E+09 | 40169660.21 |
October | 57430655.00 | 0.00 | 57430655.00 | 76362186.58 | 89251440.42 |
November | 44867884.08 | 0.00 | 44867884.08 | 21405304.93 | 0.175076E+09 |
December | 43375413.74 | 0.00 | 43375413.74 | 7292380.31 | 0.249155E+09 |
Annual Sum or Average | 0.821315E+09 | 31572692.58 | 0.789743E+09 | 0.131785E+10 | 0.124724E+10 |
Minimum of Months | 43375413.74 | 0.00 | 43375413.74 | 7292380.31 | 5598061.00 |
Maximum of Months | 98633813.54 | 12290815.53 | 88779840.45 | 0.251022E+09 | 0.249155E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272406E+09 | 0.147604E+09 | 0.124803E+09 | 0.264565E+09 | 0.482767E+09 |
February | 0.330219E+09 | 0.188293E+09 | 0.141926E+09 | 0.379113E+09 | 0.374970E+09 |
March | 0.450634E+09 | 0.248122E+09 | 0.202511E+09 | 0.569796E+09 | 0.336129E+09 |
April | 0.525720E+09 | 0.291582E+09 | 0.234138E+09 | 0.807691E+09 | 0.162552E+09 |
May | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.980190E+09 | 79843768.66 |
June | 0.542173E+09 | 0.301473E+09 | 0.240700E+09 | 0.108678E+10 | 27740419.07 |
July | 0.502747E+09 | 0.262839E+09 | 0.239908E+09 | 0.102051E+10 | 16214303.82 |
August | 0.478911E+09 | 0.245239E+09 | 0.233671E+09 | 0.932191E+09 | 32486399.63 |
September | 0.459814E+09 | 0.262571E+09 | 0.197243E+09 | 0.816152E+09 | 92886905.62 |
October | 0.363675E+09 | 0.195894E+09 | 0.167781E+09 | 0.542372E+09 | 0.198825E+09 |
November | 0.315129E+09 | 0.183035E+09 | 0.132093E+09 | 0.357063E+09 | 0.377745E+09 |
December | 0.272612E+09 | 0.144459E+09 | 0.128153E+09 | 0.253113E+09 | 0.530154E+09 |
Annual Sum or Average | 0.507405E+10 | 0.277533E+10 | 0.229871E+10 | 0.800953E+10 | 0.271231E+10 |
Minimum of Months | 0.272406E+09 | 0.144459E+09 | 0.124803E+09 | 0.253113E+09 | 16214303.82 |
Maximum of Months | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.108678E+10 | 0.530154E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.510230E+09 | 0.245604E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.441101E+09 | 0.195170E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.391940E+09 | 0.187137E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.305231E+09 | 96525752.82 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.263063E+09 | 46665259.60 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.279899E+09 | 15559145.39 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.292910E+09 | 8941365.60 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.334659E+09 | 18250925.55 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.441089E+09 | 52825823.03 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.528046E+09 | 0.106369E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.541209E+09 | 0.194905E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.516222E+09 | 0.266759E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.484560E+10 | 0.143471E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.263063E+09 | 8941365.60 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.541209E+09 | 0.266759E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 13164373.41 | 0.272223E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 29098910.71 | 0.217000E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 64222422.78 | 0.198645E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.122942E+09 | 96464343.60 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.213480E+09 | 45096371.97 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.290626E+09 | 15652883.24 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.280358E+09 | 9312198.72 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.219834E+09 | 18901225.59 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.152967E+09 | 56549319.84 |
October | 71778804.06 | 0.00 | 71778804.06 | 85907623.51 | 0.114985E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 23207438.30 | 0.217143E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 9204525.20 | 0.301280E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.150501E+10 | 0.156325E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 9204525.20 | 9312198.72 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.290626E+09 | 0.301280E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272406E+09 | 0.147604E+09 | 0.124803E+09 | 0.278102E+09 | 0.463043E+09 |
February | 0.330219E+09 | 0.188293E+09 | 0.141926E+09 | 0.391400E+09 | 0.363653E+09 |
March | 0.450634E+09 | 0.248122E+09 | 0.202511E+09 | 0.578366E+09 | 0.333057E+09 |
April | 0.525720E+09 | 0.291582E+09 | 0.234138E+09 | 0.806366E+09 | 0.166428E+09 |
May | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.968068E+09 | 83408525.65 |
June | 0.542173E+09 | 0.301473E+09 | 0.240700E+09 | 0.107349E+10 | 28924355.98 |
July | 0.502747E+09 | 0.262839E+09 | 0.239908E+09 | 0.100838E+10 | 17555537.71 |
August | 0.478911E+09 | 0.245239E+09 | 0.233671E+09 | 0.922923E+09 | 34613285.53 |
September | 0.459814E+09 | 0.262571E+09 | 0.197243E+09 | 0.810567E+09 | 96914262.87 |
October | 0.363675E+09 | 0.195894E+09 | 0.167781E+09 | 0.548326E+09 | 0.201712E+09 |
November | 0.315129E+09 | 0.183035E+09 | 0.132093E+09 | 0.369712E+09 | 0.366033E+09 |
December | 0.272612E+09 | 0.144459E+09 | 0.128153E+09 | 0.264734E+09 | 0.507917E+09 |
Annual Sum or Average | 0.507405E+10 | 0.277533E+10 | 0.229871E+10 | 0.802043E+10 | 0.266326E+10 |
Minimum of Months | 0.272406E+09 | 0.144459E+09 | 0.124803E+09 | 0.264734E+09 | 17555537.71 |
Maximum of Months | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.107349E+10 | 0.507917E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69192058.57 | 0.00 | 69192058.57 | 14100826.09 | 0.372420E+09 |
February | 76314313.11 | 0.00 | 76314313.11 | 36887262.12 | 0.294347E+09 |
March | 0.110594E+09 | 4378.05 | 0.110590E+09 | 85815284.02 | 0.267211E+09 |
April | 0.124282E+09 | 1583278.67 | 0.122698E+09 | 0.163470E+09 | 0.136588E+09 |
May | 0.151704E+09 | 11180054.31 | 0.140524E+09 | 0.273366E+09 | 73071838.32 |
June | 0.156121E+09 | 19454349.17 | 0.136667E+09 | 0.360732E+09 | 32054496.08 |
July | 0.149041E+09 | 14619313.80 | 0.134422E+09 | 0.345221E+09 | 23343758.17 |
August | 0.126053E+09 | 2998902.41 | 0.123054E+09 | 0.270423E+09 | 38281914.15 |
September | 0.106128E+09 | 134127.98 | 0.105994E+09 | 0.192220E+09 | 91860257.51 |
October | 90903326.35 | 0.00 | 90903326.35 | 0.105695E+09 | 0.169692E+09 |
November | 71018516.32 | 0.00 | 71018516.32 | 26457171.48 | 0.306458E+09 |
December | 68656180.07 | 0.00 | 68656180.07 | 9873312.56 | 0.408591E+09 |
Annual Sum or Average | 0.130001E+10 | 49974404.39 | 0.125003E+10 | 0.188426E+10 | 0.221392E+10 |
Minimum of Months | 68656180.07 | 0.00 | 68656180.07 | 9873312.56 | 23343758.17 |
Maximum of Months | 0.156121E+09 | 19454349.17 | 0.140524E+09 | 0.360732E+09 | 0.408591E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 25507057.81 | 0.00 | 25507057.81 | 5198148.37 | 0.137290E+09 |
February | 28132615.74 | 0.00 | 28132615.74 | 13598172.20 | 0.108508E+09 |
March | 40769649.09 | 1613.93 | 40768035.16 | 31635067.02 | 98505151.83 |
April | 45815375.73 | 583662.08 | 45231713.65 | 60261758.71 | 50352036.76 |
May | 55924379.60 | 4121430.95 | 51802948.65 | 0.100774E+09 | 26937305.27 |
June | 57552732.16 | 7171678.64 | 50381053.51 | 0.132981E+09 | 11816614.53 |
July | 54942788.87 | 5389284.40 | 49553504.47 | 0.127263E+09 | 8605475.85 |
August | 46468205.09 | 1105519.60 | 45362685.49 | 99688942.74 | 14112298.69 |
September | 39123254.53 | 49445.13 | 39073809.41 | 70860200.62 | 33863494.55 |
October | 33510730.10 | 0.00 | 33510730.10 | 38963389.54 | 62555344.15 |
November | 26180365.76 | 0.00 | 26180365.76 | 9753208.91 | 0.112973E+09 |
December | 25309510.80 | 0.00 | 25309510.80 | 3639711.83 | 0.150623E+09 |
Annual Sum or Average | 0.479237E+09 | 18422634.73 | 0.460814E+09 | 0.694616E+09 | 0.816142E+09 |
Minimum of Months | 25309510.80 | 0.00 | 25309510.80 | 3639711.83 | 8605475.85 |
Maximum of Months | 57552732.16 | 7171678.64 | 51802948.65 | 0.132981E+09 | 0.150623E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174486E+09 | 0.132213E+09 | 42273150.31 | 0.240931E+09 | 0.119838E+09 |
February | 0.148278E+09 | 0.105157E+09 | 43120481.20 | 0.209248E+09 | 95663731.29 |
March | 0.128425E+09 | 72758842.37 | 55665836.43 | 0.186762E+09 | 92767331.05 |
April | 86599719.45 | 32508424.18 | 54091295.27 | 0.144951E+09 | 51505927.91 |
May | 63502666.49 | 9312782.27 | 54189884.22 | 0.121372E+09 | 28949636.66 |
June | 52563848.94 | 3307323.58 | 49256525.36 | 0.125077E+09 | 12365106.38 |
July | 55159202.88 | 4890388.33 | 50268814.55 | 0.130411E+09 | 9048334.18 |
August | 69629375.31 | 17690456.23 | 51938919.07 | 0.151278E+09 | 14669246.07 |
September | 0.106709E+09 | 55440358.52 | 51268838.62 | 0.203943E+09 | 33455434.60 |
October | 0.151357E+09 | 0.102833E+09 | 48524052.02 | 0.245952E+09 | 58888164.38 |
November | 0.176291E+09 | 0.134843E+09 | 41448160.50 | 0.253944E+09 | 98626277.68 |
December | 0.179131E+09 | 0.134578E+09 | 44553106.94 | 0.243714E+09 | 0.128846E+09 |
Annual Sum or Average | 0.139213E+10 | 0.805533E+09 | 0.586599E+09 | 0.225758E+10 | 0.744623E+09 |
Minimum of Months | 52563848.94 | 3307323.58 | 41448160.50 | 0.121372E+09 | 9048334.18 |
Maximum of Months | 0.179131E+09 | 0.134843E+09 | 55665836.43 | 0.253944E+09 | 0.128846E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.473590E+09 | 0.358852E+09 | 0.114738E+09 | 0.653935E+09 | 0.325265E+09 |
February | 0.402456E+09 | 0.285418E+09 | 0.117038E+09 | 0.567943E+09 | 0.259651E+09 |
March | 0.348571E+09 | 0.197482E+09 | 0.151088E+09 | 0.506909E+09 | 0.251790E+09 |
April | 0.235049E+09 | 88234512.68 | 0.146815E+09 | 0.393427E+09 | 0.139798E+09 |
May | 0.172359E+09 | 25276795.96 | 0.147082E+09 | 0.329427E+09 | 78575235.41 |
June | 0.142669E+09 | 8976752.69 | 0.133692E+09 | 0.339486E+09 | 33561427.94 |
July | 0.149713E+09 | 13273514.24 | 0.136440E+09 | 0.353963E+09 | 24559029.76 |
August | 0.188988E+09 | 48015516.72 | 0.140973E+09 | 0.410599E+09 | 39815334.35 |
September | 0.289631E+09 | 0.150476E+09 | 0.139154E+09 | 0.553542E+09 | 90804892.68 |
October | 0.410813E+09 | 0.279109E+09 | 0.131704E+09 | 0.667564E+09 | 0.159835E+09 |
November | 0.478491E+09 | 0.365992E+09 | 0.112499E+09 | 0.689256E+09 | 0.267692E+09 |
December | 0.486199E+09 | 0.365273E+09 | 0.120926E+09 | 0.661490E+09 | 0.349715E+09 |
Annual Sum or Average | 0.377853E+10 | 0.218638E+10 | 0.159215E+10 | 0.612754E+10 | 0.202106E+10 |
Minimum of Months | 0.142669E+09 | 8976752.69 | 0.112499E+09 | 0.329427E+09 | 24559029.76 |
Maximum of Months | 0.486199E+09 | 0.365992E+09 | 0.151088E+09 | 0.689256E+09 | 0.349715E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.509908E+09 | 0.243962E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.442555E+09 | 0.192982E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.393030E+09 | 0.185779E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.306187E+09 | 94674230.48 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.264650E+09 | 45278338.95 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.281712E+09 | 14969796.21 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.293739E+09 | 8596593.38 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.334669E+09 | 17517070.61 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.439778E+09 | 51752474.31 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.526062E+09 | 0.105913E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.540983E+09 | 0.193194E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.517120E+09 | 0.264403E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.485039E+10 | 0.141902E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.264650E+09 | 8596593.38 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.540983E+09 | 0.264403E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.310696E+09 | 0.500184E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.340938E+09 | 0.395375E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.573629E+09 | 0.357877E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.758035E+09 | 0.174281E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.956364E+09 | 83537961.56 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.103661E+10 | 27877955.90 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.965009E+09 | 15571242.24 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.890362E+09 | 32446333.19 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.812125E+09 | 97685898.24 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.623295E+09 | 0.206459E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.403062E+09 | 0.396564E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.279105E+09 | 0.550191E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.794923E+10 | 0.283805E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.279105E+09 | 15571242.24 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.103661E+10 | 0.550191E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 15013502.26 | 0.268637E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 31956010.07 | 0.212750E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 67618462.09 | 0.197000E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.126951E+09 | 95457985.21 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.218916E+09 | 44198283.26 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.294309E+09 | 15109879.88 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.283089E+09 | 8954357.32 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.223242E+09 | 18254344.92 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.156326E+09 | 54915344.74 |
October | 71778804.06 | 0.00 | 71778804.06 | 87605544.83 | 0.116226E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 25933533.99 | 0.214645E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 11096954.84 | 0.296381E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.154206E+10 | 0.154253E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 11096954.84 | 8954357.32 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.294309E+09 | 0.296381E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.328961E+09 | 0.483980E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.355624E+09 | 0.385614E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.582226E+09 | 0.356925E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.758603E+09 | 0.179446E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.951770E+09 | 87673182.97 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.102952E+10 | 29255285.39 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.957990E+09 | 17013042.13 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.887187E+09 | 35014136.42 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.814281E+09 | 0.102246E+09 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.629169E+09 | 0.212276E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.418472E+09 | 0.386557E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.297400E+09 | 0.533239E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.801120E+10 | 0.280924E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.297400E+09 | 17013042.13 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.102952E+10 | 0.533239E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.548441E+09 | 0.415568E+09 | 0.132872E+09 | 0.730024E+09 | 0.374595E+09 |
February | 0.466063E+09 | 0.330528E+09 | 0.135536E+09 | 0.635595E+09 | 0.294451E+09 |
March | 0.403662E+09 | 0.228694E+09 | 0.174968E+09 | 0.568390E+09 | 0.276620E+09 |
April | 0.272199E+09 | 0.102180E+09 | 0.170019E+09 | 0.452368E+09 | 0.136080E+09 |
May | 0.199600E+09 | 29271767.90 | 0.170329E+09 | 0.400627E+09 | 62520938.89 |
June | 0.165218E+09 | 10395519.34 | 0.154822E+09 | 0.430171E+09 | 19411361.27 |
July | 0.173375E+09 | 15371379.69 | 0.158004E+09 | 0.446386E+09 | 10648968.87 |
August | 0.218858E+09 | 55604320.39 | 0.163253E+09 | 0.502481E+09 | 23527041.40 |
September | 0.335406E+09 | 0.174259E+09 | 0.161147E+09 | 0.649482E+09 | 73141308.29 |
October | 0.475742E+09 | 0.323222E+09 | 0.152520E+09 | 0.767637E+09 | 0.156673E+09 |
November | 0.554116E+09 | 0.423837E+09 | 0.130279E+09 | 0.780851E+09 | 0.293833E+09 |
December | 0.563043E+09 | 0.423004E+09 | 0.140039E+09 | 0.738113E+09 | 0.405964E+09 |
Annual Sum or Average | 0.437572E+10 | 0.253194E+10 | 0.184379E+10 | 0.710213E+10 | 0.212746E+10 |
Minimum of Months | 0.165218E+09 | 10395519.34 | 0.130279E+09 | 0.400627E+09 | 10648968.87 |
Maximum of Months | 0.563043E+09 | 0.423837E+09 | 0.174968E+09 | 0.780851E+09 | 0.405964E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.382432E+09 | 0.00 | 0.382432E+09 | 39594857.05 | 0.237047E+10 |
February | 0.421798E+09 | 0.00 | 0.421798E+09 | 0.146042E+09 | 0.186419E+10 |
March | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.374834E+09 | 0.168832E+10 |
April | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.795621E+09 | 0.861127E+09 |
May | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.141554E+10 | 0.452092E+09 |
June | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.193134E+10 | 0.199055E+09 |
July | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.183930E+10 | 0.154066E+09 |
August | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.143184E+10 | 0.241645E+09 |
September | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.101951E+10 | 0.532254E+09 |
October | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.525558E+09 | 0.102580E+10 |
November | 0.392527E+09 | 0.00 | 0.392527E+09 | 0.106176E+09 | 0.188155E+10 |
December | 0.379470E+09 | 0.00 | 0.379470E+09 | 27448927.33 | 0.258268E+10 |
Annual Sum or Average | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.965281E+10 | 0.138532E+11 |
Minimum of Months | 0.379470E+09 | 0.00 | 0.379470E+09 | 27448927.33 | 0.154066E+09 |
Maximum of Months | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.193134E+10 | 0.258268E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.382432E+09 | 0.00 | 0.382432E+09 | 30328224.99 | 0.244938E+10 |
February | 0.421798E+09 | 0.00 | 0.421798E+09 | 0.129854E+09 | 0.192201E+10 |
March | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.347095E+09 | 0.173732E+10 |
April | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.769187E+09 | 0.887868E+09 |
May | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.138956E+10 | 0.468122E+09 |
June | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.190759E+10 | 0.207973E+09 |
July | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.181488E+10 | 0.163222E+09 |
August | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.140785E+10 | 0.253397E+09 |
September | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.100065E+10 | 0.549991E+09 |
October | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.504017E+09 | 0.105638E+10 |
November | 0.392527E+09 | 0.00 | 0.392527E+09 | 91500224.86 | 0.193887E+10 |
December | 0.379470E+09 | 0.00 | 0.379470E+09 | 21343497.87 | 0.266705E+10 |
Annual Sum or Average | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.941385E+10 | 0.143016E+11 |
Minimum of Months | 0.379470E+09 | 0.00 | 0.379470E+09 | 21343497.87 | 0.163222E+09 |
Maximum of Months | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.190759E+10 | 0.266705E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 13463234.76 | 0.304213E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 35113358.55 | 0.241188E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 77300691.04 | 0.222991E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.155273E+09 | 0.117189E+09 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.257252E+09 | 67472678.50 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.337046E+09 | 33204260.86 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.327795E+09 | 26902439.02 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.266752E+09 | 37878950.68 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.199507E+09 | 71088204.96 |
October | 71778804.06 | 0.00 | 71778804.06 | 0.112298E+09 | 0.132163E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 30516507.03 | 0.239982E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 9871017.44 | 0.329526E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.182219E+10 | 0.182380E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 9871017.44 | 26902439.02 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.337046E+09 | 0.329526E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.544774E+09 | 0.295186E+09 | 0.249587E+09 | 0.562720E+09 | 0.104473E+10 |
February | 0.660391E+09 | 0.376560E+09 | 0.283831E+09 | 0.815790E+09 | 0.822585E+09 |
March | 0.901204E+09 | 0.496210E+09 | 0.404994E+09 | 0.122225E+10 | 0.761778E+09 |
April | 0.105137E+10 | 0.583122E+09 | 0.468243E+09 | 0.174139E+10 | 0.414569E+09 |
May | 0.111994E+10 | 0.608399E+09 | 0.511536E+09 | 0.210127E+10 | 0.250663E+09 |
June | 0.108427E+10 | 0.602903E+09 | 0.481366E+09 | 0.231768E+10 | 0.124143E+09 |
July | 0.100542E+10 | 0.525641E+09 | 0.479782E+09 | 0.218959E+10 | 0.101737E+09 |
August | 0.957753E+09 | 0.490444E+09 | 0.467309E+09 | 0.202094E+10 | 0.141955E+09 |
September | 0.919563E+09 | 0.525105E+09 | 0.394458E+09 | 0.180419E+10 | 0.256677E+09 |
October | 0.727299E+09 | 0.391760E+09 | 0.335538E+09 | 0.120321E+10 | 0.473918E+09 |
November | 0.630213E+09 | 0.366045E+09 | 0.264168E+09 | 0.775659E+09 | 0.819802E+09 |
December | 0.545185E+09 | 0.288898E+09 | 0.256287E+09 | 0.540225E+09 | 0.112610E+10 |
Annual Sum or Average | 0.101474E+11 | 0.555027E+10 | 0.459710E+10 | 0.172949E+11 | 0.633866E+10 |
Minimum of Months | 0.544774E+09 | 0.288898E+09 | 0.249587E+09 | 0.540225E+09 | 0.101737E+09 |
Maximum of Months | 0.111994E+10 | 0.608399E+09 | 0.511536E+09 | 0.231768E+10 | 0.112610E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.527589E+09 | 0.270695E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.460754E+09 | 0.216795E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.414937E+09 | 0.211105E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.336137E+09 | 0.119161E+09 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.298409E+09 | 70605286.87 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.318498E+09 | 33648049.76 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.333268E+09 | 27268168.08 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.377112E+09 | 38495947.28 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.486278E+09 | 70787646.01 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.561834E+09 | 0.126789E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.565056E+09 | 0.214419E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.534797E+09 | 0.288517E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.521467E+10 | 0.168829E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.298409E+09 | 27268168.08 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.565056E+09 | 0.288517E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69192058.57 | 0.00 | 69192058.57 | 11662502.28 | 0.376115E+09 |
February | 76314313.11 | 0.00 | 76314313.11 | 33480784.33 | 0.295262E+09 |
March | 0.110594E+09 | 4378.05 | 0.110590E+09 | 81365438.30 | 0.265934E+09 |
April | 0.124282E+09 | 1583278.67 | 0.122698E+09 | 0.155733E+09 | 0.137722E+09 |
May | 0.151704E+09 | 11180054.31 | 0.140524E+09 | 0.263003E+09 | 75462570.43 |
June | 0.156121E+09 | 19454349.17 | 0.136667E+09 | 0.349119E+09 | 34502365.11 |
July | 0.149041E+09 | 14619313.80 | 0.134422E+09 | 0.332164E+09 | 26388429.30 |
August | 0.126053E+09 | 2998902.41 | 0.123054E+09 | 0.258968E+09 | 41331460.14 |
September | 0.106128E+09 | 134127.98 | 0.105994E+09 | 0.184574E+09 | 93670519.09 |
October | 90903326.35 | 0.00 | 90903326.35 | 0.100105E+09 | 0.168888E+09 |
November | 71018516.32 | 0.00 | 71018516.32 | 24214782.21 | 0.301534E+09 |
December | 68656180.07 | 0.00 | 68656180.07 | 8178067.64 | 0.414178E+09 |
Annual Sum or Average | 0.130001E+10 | 49974404.39 | 0.125003E+10 | 0.180257E+10 | 0.223099E+10 |
Minimum of Months | 68656180.07 | 0.00 | 68656180.07 | 8178067.64 | 26388429.30 |
Maximum of Months | 0.156121E+09 | 19454349.17 | 0.140524E+09 | 0.349119E+09 | 0.414178E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61906396.97 | 0.00 | 61906396.97 | 10434484.98 | 0.336511E+09 |
February | 68278705.09 | 0.00 | 68278705.09 | 29955384.60 | 0.264172E+09 |
March | 98949165.36 | 3917.06 | 98945248.31 | 72797965.94 | 0.237932E+09 |
April | 0.111195E+09 | 1416565.43 | 0.109779E+09 | 0.139335E+09 | 0.123220E+09 |
May | 0.135730E+09 | 10002836.96 | 0.125727E+09 | 0.235310E+09 | 67516647.69 |
June | 0.139682E+09 | 17405879.91 | 0.122276E+09 | 0.312359E+09 | 30869396.80 |
July | 0.133348E+09 | 13079955.45 | 0.120268E+09 | 0.297188E+09 | 23609827.68 |
August | 0.112780E+09 | 2683129.35 | 0.110097E+09 | 0.231700E+09 | 36979413.99 |
September | 94953316.23 | 120004.81 | 94833311.42 | 0.165139E+09 | 83807368.35 |
October | 81331550.52 | 0.00 | 81331550.52 | 89564620.91 | 0.151105E+09 |
November | 63540535.64 | 0.00 | 63540535.64 | 21665057.40 | 0.269784E+09 |
December | 61426944.44 | 0.00 | 61426944.44 | 7316948.11 | 0.370550E+09 |
Annual Sum or Average | 0.116312E+10 | 44712288.96 | 0.111841E+10 | 0.161276E+10 | 0.199606E+10 |
Minimum of Months | 61426944.44 | 0.00 | 61426944.44 | 7316948.11 | 23609827.68 |
Maximum of Months | 0.139682E+09 | 17405879.91 | 0.125727E+09 | 0.312359E+09 | 0.370550E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139608E+10 | 0.105785E+10 | 0.338233E+09 | 0.190035E+10 | 0.963390E+09 |
February | 0.118639E+10 | 0.841376E+09 | 0.345013E+09 | 0.164969E+10 | 0.766393E+09 |
March | 0.102754E+10 | 0.582153E+09 | 0.445390E+09 | 0.146830E+10 | 0.739128E+09 |
April | 0.692896E+09 | 0.260104E+09 | 0.432792E+09 | 0.112974E+10 | 0.416357E+09 |
May | 0.508093E+09 | 74512840.84 | 0.433581E+09 | 0.938676E+09 | 0.239231E+09 |
June | 0.420571E+09 | 26462346.95 | 0.394108E+09 | 0.967773E+09 | 0.106272E+09 |
July | 0.441336E+09 | 39128663.92 | 0.402208E+09 | 0.100509E+10 | 82026623.92 |
August | 0.557114E+09 | 0.141544E+09 | 0.415570E+09 | 0.117340E+10 | 0.127049E+09 |
September | 0.853795E+09 | 0.443586E+09 | 0.410209E+09 | 0.160249E+10 | 0.273536E+09 |
October | 0.121103E+10 | 0.822779E+09 | 0.388248E+09 | 0.194091E+10 | 0.469909E+09 |
November | 0.141053E+10 | 0.107890E+10 | 0.331632E+09 | 0.201488E+10 | 0.775986E+09 |
December | 0.143326E+10 | 0.107678E+10 | 0.356475E+09 | 0.192340E+10 | 0.103762E+10 |
Annual Sum or Average | 0.111386E+11 | 0.644518E+10 | 0.469346E+10 | 0.177147E+11 | 0.599690E+10 |
Minimum of Months | 0.420571E+09 | 26462346.95 | 0.331632E+09 | 0.938676E+09 | 82026623.92 |
Maximum of Months | 0.143326E+10 | 0.107890E+10 | 0.445390E+09 | 0.201488E+10 | 0.103762E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 953.16 | 477.19 | 706.15 | 535.07 | 171.08 | 0.00 | 0.00 |
February | 915.95 | 421.85 | 664.38 | 471.17 | 193.21 | 0.00 | 0.00 |
March | 742.09 | 366.67 | 519.74 | 294.46 | 225.28 | 0.00 | 0.00 |
April | 586.63 | 217.05 | 362.15 | 135.95 | 226.20 | 0.00 | 0.00 |
May | 466.76 | 122.94 | 257.00 | 37.69 | 219.31 | 0.00 | 0.00 |
June | 484.59 | 58.52 | 219.82 | 13.83 | 205.99 | 0.00 | 0.00 |
July | 492.51 | 43.59 | 223.23 | 19.79 | 203.44 | 0.00 | 0.00 |
August | 579.96 | 66.64 | 281.79 | 71.59 | 210.20 | 0.00 | 0.00 |
September | 827.31 | 147.75 | 446.25 | 231.85 | 214.40 | 0.00 | 0.00 |
October | 973.66 | 241.20 | 612.55 | 416.17 | 196.38 | 0.00 | 0.00 |
November | 1040.18 | 405.03 | 737.24 | 563.91 | 173.33 | 0.00 | 0.00 |
December | 960.19 | 513.69 | 724.95 | 544.65 | 180.31 | 0.00 | 0.00 |
Annual Sum or Average | 750.76 | 256.03 | 478.50 | 276.88 | 201.63 | 0.00 | 0.00 |
Minimum of Months | 466.76 | 43.59 | 219.82 | 13.83 | 171.08 | 0.00 | 0.00 |
Maximum of Months | 1040.18 | 513.69 | 737.24 | 563.91 | 226.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2639.37 | 1463.46 | 1988.48 | 1506.73 | 481.75 | 0.00 | 0.00 |
February | 2531.09 | 1300.26 | 1870.85 | 1326.79 | 544.06 | 0.00 | 0.00 |
March | 2041.01 | 1135.03 | 1463.55 | 829.18 | 634.37 | 0.00 | 0.00 |
April | 1618.06 | 671.28 | 1019.80 | 382.82 | 636.98 | 0.00 | 0.00 |
May | 1296.31 | 372.71 | 723.68 | 106.13 | 617.55 | 0.00 | 0.00 |
June | 1363.43 | 169.73 | 618.99 | 38.95 | 580.04 | 0.00 | 0.00 |
July | 1383.49 | 127.33 | 628.60 | 55.73 | 572.87 | 0.00 | 0.00 |
August | 1624.49 | 197.69 | 793.51 | 201.60 | 591.90 | 0.00 | 0.00 |
September | 2313.86 | 428.33 | 1256.61 | 652.87 | 603.74 | 0.00 | 0.00 |
October | 2713.87 | 725.17 | 1724.89 | 1171.91 | 552.99 | 0.00 | 0.00 |
November | 2887.20 | 1229.86 | 2076.02 | 1587.93 | 488.09 | 0.00 | 0.00 |
December | 2653.43 | 1564.93 | 2041.42 | 1533.69 | 507.73 | 0.00 | 0.00 |
Annual Sum or Average | 2085.64 | 779.61 | 1347.44 | 779.68 | 567.76 | 0.00 | 0.00 |
Minimum of Months | 1296.31 | 127.33 | 618.99 | 38.95 | 481.75 | 0.00 | 0.00 |
Maximum of Months | 2887.20 | 1564.93 | 2076.02 | 1587.93 | 636.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3499.83 | 1951.06 | 2583.15 | 1957.32 | 625.82 | 0.00 | 0.00 |
February | 3361.16 | 1727.69 | 2430.34 | 1723.58 | 706.76 | 0.00 | 0.00 |
March | 2714.65 | 1511.55 | 1901.24 | 1077.15 | 824.09 | 0.00 | 0.00 |
April | 2160.22 | 889.97 | 1324.78 | 497.31 | 827.47 | 0.00 | 0.00 |
May | 1731.35 | 492.68 | 940.11 | 137.87 | 802.24 | 0.00 | 0.00 |
June | 1828.90 | 221.98 | 804.10 | 50.59 | 753.51 | 0.00 | 0.00 |
July | 1855.14 | 165.73 | 816.59 | 72.40 | 744.19 | 0.00 | 0.00 |
August | 2173.91 | 256.72 | 1030.81 | 261.90 | 768.91 | 0.00 | 0.00 |
September | 3081.42 | 554.43 | 1632.41 | 848.12 | 784.29 | 0.00 | 0.00 |
October | 3597.81 | 950.42 | 2240.73 | 1522.37 | 718.36 | 0.00 | 0.00 |
November | 3821.10 | 1633.53 | 2696.87 | 2062.81 | 634.06 | 0.00 | 0.00 |
December | 3516.77 | 2091.63 | 2651.92 | 1992.35 | 659.58 | 0.00 | 0.00 |
Annual Sum or Average | 2774.34 | 1033.94 | 1750.40 | 1012.84 | 737.56 | 0.00 | 0.00 |
Minimum of Months | 1731.35 | 165.73 | 804.10 | 50.59 | 625.82 | 0.00 | 0.00 |
Maximum of Months | 3821.10 | 2091.63 | 2696.87 | 2062.81 | 827.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 295.35 | 269.07 | 247.02 | 166.33 | 80.69 | 0.00 | 0.00 |
February | 315.99 | 237.16 | 252.26 | 157.31 | 94.95 | 0.00 | 0.00 |
March | 359.91 | 202.44 | 267.73 | 146.67 | 121.05 | 0.00 | 0.00 |
April | 412.75 | 105.49 | 260.91 | 128.99 | 131.92 | 0.00 | 0.00 |
May | 458.17 | 50.19 | 255.11 | 116.78 | 138.32 | 0.00 | 0.00 |
June | 510.26 | 17.63 | 242.25 | 109.47 | 132.78 | 0.00 | 0.00 |
July | 471.94 | 9.72 | 220.68 | 91.63 | 129.05 | 0.00 | 0.00 |
August | 459.50 | 19.77 | 226.65 | 101.24 | 125.41 | 0.00 | 0.00 |
September | 485.74 | 59.55 | 263.72 | 143.81 | 119.91 | 0.00 | 0.00 |
October | 429.57 | 117.56 | 272.32 | 170.80 | 101.51 | 0.00 | 0.00 |
November | 356.46 | 222.60 | 271.93 | 188.26 | 83.67 | 0.00 | 0.00 |
December | 282.51 | 292.96 | 245.09 | 162.93 | 82.16 | 0.00 | 0.00 |
Annual Sum or Average | 403.48 | 133.18 | 252.05 | 140.19 | 111.87 | 0.00 | 0.00 |
Minimum of Months | 282.51 | 9.72 | 220.68 | 91.63 | 80.69 | 0.00 | 0.00 |
Maximum of Months | 510.26 | 292.96 | 272.32 | 188.26 | 138.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 124.15 | 282.04 | 127.80 | 60.54 | 67.26 | 0.00 | 0.00 |
February | 157.22 | 249.00 | 145.81 | 64.15 | 81.66 | 0.00 | 0.00 |
March | 241.45 | 207.85 | 197.57 | 88.46 | 109.11 | 0.00 | 0.00 |
April | 343.02 | 107.52 | 227.17 | 102.60 | 124.57 | 0.00 | 0.00 |
May | 438.33 | 50.55 | 249.02 | 112.63 | 136.39 | 0.00 | 0.00 |
June | 512.11 | 17.86 | 246.35 | 112.66 | 133.68 | 0.00 | 0.00 |
July | 465.13 | 10.23 | 220.48 | 92.03 | 128.45 | 0.00 | 0.00 |
August | 415.95 | 20.89 | 208.10 | 87.97 | 120.13 | 0.00 | 0.00 |
September | 376.13 | 62.90 | 207.82 | 98.01 | 109.81 | 0.00 | 0.00 |
October | 267.62 | 124.72 | 178.00 | 88.52 | 89.48 | 0.00 | 0.00 |
November | 167.91 | 234.57 | 147.80 | 76.76 | 71.03 | 0.00 | 0.00 |
December | 109.96 | 310.67 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Annual Sum or Average | 302.24 | 139.38 | 190.00 | 86.70 | 103.30 | 0.00 | 0.00 |
Minimum of Months | 109.96 | 10.23 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Maximum of Months | 512.11 | 310.67 | 249.02 | 112.66 | 136.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 139.79 | 101.55 | 111.67 | 84.62 | 27.06 | 0.00 | 0.00 |
February | 133.51 | 91.38 | 105.07 | 74.51 | 30.55 | 0.00 | 0.00 |
March | 104.60 | 80.35 | 82.19 | 46.57 | 35.63 | 0.00 | 0.00 |
April | 81.95 | 50.54 | 57.27 | 21.50 | 35.77 | 0.00 | 0.00 |
May | 63.76 | 30.28 | 40.64 | 5.96 | 34.68 | 0.00 | 0.00 |
June | 67.76 | 15.79 | 34.76 | 2.19 | 32.58 | 0.00 | 0.00 |
July | 68.54 | 13.44 | 35.30 | 3.13 | 32.17 | 0.00 | 0.00 |
August | 82.80 | 18.70 | 44.56 | 11.32 | 33.24 | 0.00 | 0.00 |
September | 123.12 | 34.07 | 70.57 | 36.67 | 33.91 | 0.00 | 0.00 |
October | 144.47 | 53.78 | 96.87 | 65.81 | 31.06 | 0.00 | 0.00 |
November | 154.26 | 85.80 | 116.59 | 89.18 | 27.41 | 0.00 | 0.00 |
December | 140.81 | 106.98 | 114.65 | 86.13 | 28.51 | 0.00 | 0.00 |
Annual Sum or Average | 108.60 | 56.72 | 75.67 | 43.79 | 31.89 | 0.00 | 0.00 |
Minimum of Months | 63.76 | 13.44 | 34.76 | 2.19 | 27.06 | 0.00 | 0.00 |
Maximum of Months | 154.26 | 106.98 | 116.59 | 89.18 | 35.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.96 | 83.82 | 16.32 | 0.00 | 16.32 | 0.00 | 0.00 |
February | 10.59 | 72.67 | 19.93 | 0.00 | 19.93 | 0.00 | 0.00 |
March | 21.36 | 59.10 | 26.09 | 0.00 | 26.09 | 0.00 | 0.00 |
April | 42.51 | 28.34 | 30.29 | 0.39 | 29.91 | 0.00 | 0.00 |
May | 70.05 | 12.29 | 35.78 | 2.64 | 33.15 | 0.00 | 0.00 |
June | 96.84 | 4.00 | 38.05 | 4.74 | 33.31 | 0.00 | 0.00 |
July | 90.41 | 2.09 | 35.16 | 3.45 | 31.71 | 0.00 | 0.00 |
August | 71.86 | 4.72 | 29.73 | 0.71 | 29.03 | 0.00 | 0.00 |
September | 52.44 | 15.50 | 25.87 | 0.03 | 25.84 | 0.00 | 0.00 |
October | 28.51 | 33.32 | 21.44 | 0.00 | 21.44 | 0.00 | 0.00 |
November | 8.26 | 67.54 | 17.31 | 0.00 | 17.31 | 0.00 | 0.00 |
December | 2.72 | 93.02 | 16.19 | 0.00 | 16.19 | 0.00 | 0.00 |
Annual Sum or Average | 41.79 | 39.55 | 26.04 | 1.00 | 25.04 | 0.00 | 0.00 |
Minimum of Months | 2.72 | 2.09 | 16.19 | 0.00 | 16.19 | 0.00 | 0.00 |
Maximum of Months | 96.84 | 93.02 | 38.05 | 4.74 | 33.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 281.75 | 264.42 | 241.32 | 160.90 | 80.42 | 0.00 | 0.00 |
February | 334.20 | 230.83 | 267.86 | 170.99 | 96.87 | 0.00 | 0.00 |
March | 354.88 | 191.18 | 271.01 | 150.86 | 120.15 | 0.00 | 0.00 |
April | 425.75 | 96.33 | 274.43 | 139.37 | 135.06 | 0.00 | 0.00 |
May | 462.68 | 45.73 | 259.90 | 121.04 | 138.86 | 0.00 | 0.00 |
June | 527.01 | 16.45 | 252.63 | 119.04 | 133.59 | 0.00 | 0.00 |
July | 490.27 | 9.29 | 231.84 | 102.05 | 129.80 | 0.00 | 0.00 |
August | 472.67 | 18.63 | 234.52 | 105.72 | 128.80 | 0.00 | 0.00 |
September | 483.83 | 55.00 | 265.63 | 147.14 | 118.49 | 0.00 | 0.00 |
October | 398.86 | 113.16 | 256.89 | 155.42 | 101.47 | 0.00 | 0.00 |
November | 341.85 | 216.22 | 267.34 | 182.11 | 85.23 | 0.00 | 0.00 |
December | 277.15 | 287.45 | 245.12 | 161.62 | 83.50 | 0.00 | 0.00 |
Annual Sum or Average | 404.38 | 128.24 | 255.51 | 142.75 | 112.76 | 0.00 | 0.00 |
Minimum of Months | 277.15 | 9.29 | 231.84 | 102.05 | 80.42 | 0.00 | 0.00 |
Maximum of Months | 527.01 | 287.45 | 274.43 | 182.11 | 138.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 100.56 | 266.33 | 122.10 | 55.11 | 66.99 | 0.00 | 0.00 |
February | 164.99 | 231.19 | 161.41 | 77.83 | 83.58 | 0.00 | 0.00 |
March | 233.01 | 191.61 | 200.85 | 92.64 | 108.21 | 0.00 | 0.00 |
April | 355.57 | 98.46 | 240.68 | 112.98 | 127.71 | 0.00 | 0.00 |
May | 440.85 | 47.69 | 253.81 | 116.88 | 136.93 | 0.00 | 0.00 |
June | 526.26 | 17.18 | 256.73 | 122.24 | 134.50 | 0.00 | 0.00 |
July | 481.11 | 9.98 | 231.64 | 102.44 | 129.20 | 0.00 | 0.00 |
August | 426.55 | 19.87 | 215.97 | 92.45 | 123.52 | 0.00 | 0.00 |
September | 370.00 | 57.48 | 209.73 | 101.34 | 108.39 | 0.00 | 0.00 |
October | 234.25 | 115.69 | 162.58 | 73.14 | 89.44 | 0.00 | 0.00 |
November | 144.14 | 217.54 | 143.21 | 70.62 | 72.60 | 0.00 | 0.00 |
December | 92.40 | 292.24 | 122.02 | 53.93 | 68.09 | 0.00 | 0.00 |
Annual Sum or Average | 298.00 | 129.97 | 193.45 | 89.26 | 104.19 | 0.00 | 0.00 |
Minimum of Months | 92.40 | 9.98 | 122.02 | 53.93 | 66.99 | 0.00 | 0.00 |
Maximum of Months | 526.26 | 292.24 | 256.73 | 122.24 | 136.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 322.31 | 337.49 | 277.32 | 183.34 | 93.98 | 0.00 | 0.00 |
February | 328.35 | 299.62 | 270.83 | 161.45 | 109.38 | 0.00 | 0.00 |
March | 298.81 | 261.16 | 234.60 | 100.90 | 133.70 | 0.00 | 0.00 |
April | 293.60 | 145.51 | 189.72 | 47.42 | 142.30 | 0.00 | 0.00 |
May | 306.95 | 76.44 | 165.58 | 18.63 | 146.95 | 0.00 | 0.00 |
June | 369.17 | 34.11 | 157.76 | 15.01 | 142.75 | 0.00 | 0.00 |
July | 356.76 | 23.99 | 152.65 | 14.25 | 138.40 | 0.00 | 0.00 |
August | 347.69 | 39.63 | 160.97 | 26.06 | 134.90 | 0.00 | 0.00 |
September | 393.45 | 96.16 | 208.95 | 79.51 | 129.43 | 0.00 | 0.00 |
October | 392.25 | 165.55 | 256.34 | 142.60 | 113.74 | 0.00 | 0.00 |
November | 363.18 | 288.47 | 290.12 | 193.22 | 96.89 | 0.00 | 0.00 |
December | 318.80 | 363.25 | 283.49 | 186.62 | 96.87 | 0.00 | 0.00 |
Annual Sum or Average | 340.90 | 177.01 | 220.38 | 97.04 | 123.34 | 0.00 | 0.00 |
Minimum of Months | 293.60 | 23.99 | 152.65 | 14.25 | 93.98 | 0.00 | 0.00 |
Maximum of Months | 393.45 | 363.25 | 290.12 | 193.22 | 146.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 294.35 | 265.81 | 247.02 | 166.33 | 80.69 | 0.00 | 0.00 |
February | 314.54 | 233.88 | 252.26 | 157.31 | 94.95 | 0.00 | 0.00 |
March | 357.32 | 199.39 | 267.73 | 146.67 | 121.05 | 0.00 | 0.00 |
April | 409.75 | 102.94 | 260.91 | 128.99 | 131.92 | 0.00 | 0.00 |
May | 455.80 | 48.02 | 255.11 | 116.78 | 138.32 | 0.00 | 0.00 |
June | 508.61 | 16.53 | 242.25 | 109.47 | 132.78 | 0.00 | 0.00 |
July | 469.90 | 8.97 | 220.68 | 91.63 | 129.05 | 0.00 | 0.00 |
August | 457.33 | 18.61 | 226.65 | 101.24 | 125.41 | 0.00 | 0.00 |
September | 482.81 | 57.47 | 263.72 | 143.81 | 119.91 | 0.00 | 0.00 |
October | 427.35 | 114.86 | 272.32 | 170.80 | 101.51 | 0.00 | 0.00 |
November | 355.41 | 218.73 | 271.93 | 188.26 | 83.67 | 0.00 | 0.00 |
December | 282.47 | 289.33 | 245.09 | 162.93 | 82.16 | 0.00 | 0.00 |
Annual Sum or Average | 401.60 | 130.72 | 252.05 | 140.19 | 111.87 | 0.00 | 0.00 |
Minimum of Months | 282.47 | 8.97 | 220.68 | 91.63 | 80.69 | 0.00 | 0.00 |
Maximum of Months | 508.61 | 289.33 | 272.32 | 188.26 | 138.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 124.88 | 277.45 | 127.80 | 60.54 | 67.26 | 0.00 | 0.00 |
February | 157.47 | 244.60 | 145.81 | 64.15 | 81.66 | 0.00 | 0.00 |
March | 240.38 | 204.57 | 197.57 | 88.46 | 109.11 | 0.00 | 0.00 |
April | 340.84 | 105.25 | 227.17 | 102.60 | 124.57 | 0.00 | 0.00 |
May | 436.38 | 48.53 | 249.02 | 112.63 | 136.39 | 0.00 | 0.00 |
June | 510.43 | 16.81 | 246.35 | 112.66 | 133.68 | 0.00 | 0.00 |
July | 463.18 | 9.51 | 220.48 | 92.03 | 128.45 | 0.00 | 0.00 |
August | 414.42 | 19.72 | 208.10 | 87.97 | 120.13 | 0.00 | 0.00 |
September | 374.41 | 60.59 | 207.82 | 98.01 | 109.81 | 0.00 | 0.00 |
October | 266.78 | 121.82 | 178.00 | 88.52 | 89.48 | 0.00 | 0.00 |
November | 168.66 | 229.16 | 147.80 | 76.76 | 71.03 | 0.00 | 0.00 |
December | 111.14 | 305.71 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Annual Sum or Average | 301.40 | 136.46 | 190.00 | 86.70 | 103.30 | 0.00 | 0.00 |
Minimum of Months | 111.14 | 9.51 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Maximum of Months | 510.43 | 305.71 | 249.02 | 112.66 | 136.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 272.56 | 139.86 | 204.76 | 155.16 | 49.61 | 0.00 | 0.00 |
February | 262.73 | 121.71 | 192.65 | 136.63 | 56.02 | 0.00 | 0.00 |
March | 212.21 | 103.28 | 150.71 | 85.38 | 65.33 | 0.00 | 0.00 |
April | 174.52 | 52.50 | 105.01 | 39.42 | 65.59 | 0.00 | 0.00 |
May | 149.58 | 23.34 | 74.52 | 10.93 | 63.59 | 0.00 | 0.00 |
June | 165.96 | 7.49 | 63.74 | 4.01 | 59.73 | 0.00 | 0.00 |
July | 166.66 | 3.98 | 64.73 | 5.74 | 58.99 | 0.00 | 0.00 |
August | 187.60 | 8.78 | 81.71 | 20.76 | 60.95 | 0.00 | 0.00 |
September | 250.57 | 28.22 | 129.40 | 67.23 | 62.17 | 0.00 | 0.00 |
October | 286.60 | 58.49 | 177.62 | 120.68 | 56.94 | 0.00 | 0.00 |
November | 301.25 | 113.36 | 213.78 | 163.52 | 50.26 | 0.00 | 0.00 |
December | 275.58 | 151.57 | 210.22 | 157.93 | 52.28 | 0.00 | 0.00 |
Annual Sum or Average | 225.21 | 67.46 | 138.75 | 80.29 | 58.47 | 0.00 | 0.00 |
Minimum of Months | 149.58 | 3.98 | 63.74 | 4.01 | 49.61 | 0.00 | 0.00 |
Maximum of Months | 301.25 | 151.57 | 213.78 | 163.52 | 65.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 14.78 | 885.03 | 142.78 | 0.00 | 142.78 | 0.00 | 0.00 |
February | 60.37 | 770.58 | 174.35 | 0.00 | 174.35 | 0.00 | 0.00 |
March | 139.95 | 630.34 | 228.22 | 0.01 | 228.21 | 0.00 | 0.00 |
April | 306.95 | 332.22 | 265.01 | 3.38 | 261.64 | 0.00 | 0.00 |
May | 528.50 | 168.79 | 313.05 | 23.07 | 289.98 | 0.00 | 0.00 |
June | 745.12 | 76.80 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
July | 686.72 | 57.52 | 307.56 | 30.17 | 277.39 | 0.00 | 0.00 |
August | 534.59 | 90.22 | 260.12 | 6.19 | 253.93 | 0.00 | 0.00 |
September | 393.33 | 205.34 | 226.30 | 0.29 | 226.02 | 0.00 | 0.00 |
October | 196.22 | 382.99 | 187.59 | 0.00 | 187.59 | 0.00 | 0.00 |
November | 40.96 | 725.91 | 151.44 | 0.00 | 151.44 | 0.00 | 0.00 |
December | 10.25 | 964.26 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Annual Sum or Average | 306.09 | 439.28 | 227.84 | 8.76 | 219.09 | 0.00 | 0.00 |
Minimum of Months | 10.25 | 57.52 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Maximum of Months | 745.12 | 964.26 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 11.32 | 914.50 | 142.78 | 0.00 | 142.78 | 0.00 | 0.00 |
February | 53.68 | 794.48 | 174.35 | 0.00 | 174.35 | 0.00 | 0.00 |
March | 129.59 | 648.64 | 228.22 | 0.01 | 228.21 | 0.00 | 0.00 |
April | 296.75 | 342.54 | 265.01 | 3.38 | 261.64 | 0.00 | 0.00 |
May | 518.80 | 174.78 | 313.05 | 23.07 | 289.98 | 0.00 | 0.00 |
June | 735.95 | 80.24 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
July | 677.60 | 60.94 | 307.56 | 30.17 | 277.39 | 0.00 | 0.00 |
August | 525.63 | 94.61 | 260.12 | 6.19 | 253.93 | 0.00 | 0.00 |
September | 386.05 | 212.19 | 226.30 | 0.29 | 226.02 | 0.00 | 0.00 |
October | 188.18 | 394.41 | 187.59 | 0.00 | 187.59 | 0.00 | 0.00 |
November | 35.30 | 748.02 | 151.44 | 0.00 | 151.44 | 0.00 | 0.00 |
December | 7.97 | 995.76 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Annual Sum or Average | 298.51 | 453.50 | 227.84 | 8.76 | 219.09 | 0.00 | 0.00 |
Minimum of Months | 7.97 | 60.94 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Maximum of Months | 735.95 | 995.76 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 392.66 | 585.26 | 363.41 | 216.00 | 147.41 | 0.00 | 0.00 |
February | 527.01 | 514.16 | 429.25 | 248.81 | 180.43 | 0.00 | 0.00 |
March | 629.57 | 435.94 | 471.84 | 243.48 | 228.35 | 0.00 | 0.00 |
April | 855.83 | 245.54 | 515.08 | 252.33 | 262.75 | 0.00 | 0.00 |
May | 990.26 | 143.42 | 513.67 | 237.90 | 275.77 | 0.00 | 0.00 |
June | 1146.81 | 73.42 | 509.34 | 241.26 | 268.07 | 0.00 | 0.00 |
July | 1064.17 | 58.07 | 463.46 | 204.47 | 258.98 | 0.00 | 0.00 |
August | 994.60 | 81.19 | 450.46 | 198.15 | 252.31 | 0.00 | 0.00 |
September | 958.78 | 151.90 | 475.33 | 248.47 | 226.86 | 0.00 | 0.00 |
October | 698.20 | 270.91 | 419.45 | 228.55 | 190.90 | 0.00 | 0.00 |
November | 516.30 | 478.87 | 410.54 | 252.72 | 157.82 | 0.00 | 0.00 |
December | 379.31 | 625.45 | 367.13 | 215.55 | 151.58 | 0.00 | 0.00 |
Annual Sum or Average | 763.56 | 304.37 | 448.93 | 231.99 | 216.94 | 0.00 | 0.00 |
Minimum of Months | 379.31 | 58.07 | 363.41 | 198.15 | 147.41 | 0.00 | 0.00 |
Maximum of Months | 1146.81 | 625.45 | 515.08 | 252.72 | 275.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 689.11 | 597.11 | 570.18 | 394.96 | 175.23 | 0.00 | 0.00 |
February | 687.37 | 527.27 | 550.17 | 347.79 | 202.38 | 0.00 | 0.00 |
March | 599.54 | 457.86 | 461.88 | 217.35 | 244.52 | 0.00 | 0.00 |
April | 549.05 | 260.66 | 358.17 | 101.51 | 256.66 | 0.00 | 0.00 |
May | 534.65 | 140.85 | 297.02 | 35.73 | 261.29 | 0.00 | 0.00 |
June | 627.50 | 65.15 | 276.38 | 24.43 | 251.95 | 0.00 | 0.00 |
July | 609.26 | 48.32 | 270.21 | 24.95 | 245.26 | 0.00 | 0.00 |
August | 620.76 | 76.15 | 297.17 | 54.97 | 242.20 | 0.00 | 0.00 |
September | 752.76 | 173.60 | 406.97 | 171.23 | 235.74 | 0.00 | 0.00 |
October | 791.28 | 290.73 | 516.45 | 307.19 | 209.26 | 0.00 | 0.00 |
November | 773.75 | 498.50 | 596.10 | 416.24 | 179.86 | 0.00 | 0.00 |
December | 687.01 | 643.49 | 583.68 | 402.02 | 181.66 | 0.00 | 0.00 |
Annual Sum or Average | 659.78 | 313.95 | 431.31 | 207.38 | 223.93 | 0.00 | 0.00 |
Minimum of Months | 534.65 | 48.32 | 270.21 | 24.43 | 175.23 | 0.00 | 0.00 |
Maximum of Months | 791.28 | 643.49 | 596.10 | 416.24 | 261.29 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.255293E+10 | 0.127810E+10 | 0.189136E+10 | 0.143314E+10 | 0.458222E+09 | 0.00 | 0.00 |
February | 0.221586E+10 | 0.102055E+10 | 0.160727E+10 | 0.113986E+10 | 0.467406E+09 | 0.00 | 0.00 |
March | 0.198760E+10 | 0.982087E+09 | 0.139207E+10 | 0.788679E+09 | 0.603391E+09 | 0.00 | 0.00 |
April | 0.152055E+10 | 0.562595E+09 | 0.938702E+09 | 0.352379E+09 | 0.586322E+09 | 0.00 | 0.00 |
May | 0.125017E+10 | 0.329292E+09 | 0.688337E+09 | 0.100947E+09 | 0.587390E+09 | 0.00 | 0.00 |
June | 0.125606E+10 | 0.151693E+09 | 0.569764E+09 | 35850177.24 | 0.533914E+09 | 0.00 | 0.00 |
July | 0.131914E+10 | 0.116748E+09 | 0.597898E+09 | 53010019.83 | 0.544888E+09 | 0.00 | 0.00 |
August | 0.155337E+10 | 0.178480E+09 | 0.754750E+09 | 0.191758E+09 | 0.562992E+09 | 0.00 | 0.00 |
September | 0.214437E+10 | 0.382964E+09 | 0.115668E+10 | 0.600953E+09 | 0.555729E+09 | 0.00 | 0.00 |
October | 0.260786E+10 | 0.646029E+09 | 0.164065E+10 | 0.111467E+10 | 0.525978E+09 | 0.00 | 0.00 |
November | 0.269615E+10 | 0.104983E+10 | 0.191093E+10 | 0.146165E+10 | 0.449279E+09 | 0.00 | 0.00 |
December | 0.257176E+10 | 0.137586E+10 | 0.194172E+10 | 0.145878E+10 | 0.482936E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.236758E+11 | 0.807423E+10 | 0.150901E+11 | 0.873168E+10 | 0.635845E+10 | 0.00 | 0.00 |
Minimum of Months | 0.125017E+10 | 0.116748E+09 | 0.569764E+09 | 35850177.24 | 0.449279E+09 | 0.00 | 0.00 |
Maximum of Months | 0.269615E+10 | 0.137586E+10 | 0.194172E+10 | 0.146165E+10 | 0.603391E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.706929E+10 | 0.391973E+10 | 0.532594E+10 | 0.403562E+10 | 0.129032E+10 | 0.00 | 0.00 |
February | 0.612320E+10 | 0.314560E+10 | 0.452597E+10 | 0.320978E+10 | 0.131618E+10 | 0.00 | 0.00 |
March | 0.546665E+10 | 0.304007E+10 | 0.391998E+10 | 0.222087E+10 | 0.169911E+10 | 0.00 | 0.00 |
April | 0.419402E+10 | 0.173995E+10 | 0.264332E+10 | 0.992277E+09 | 0.165105E+10 | 0.00 | 0.00 |
May | 0.347203E+10 | 0.998263E+09 | 0.193831E+10 | 0.284261E+09 | 0.165405E+10 | 0.00 | 0.00 |
June | 0.353401E+10 | 0.439928E+09 | 0.160442E+10 | 0.100952E+09 | 0.150347E+10 | 0.00 | 0.00 |
July | 0.370555E+10 | 0.341053E+09 | 0.168364E+10 | 0.149273E+09 | 0.153437E+10 | 0.00 | 0.00 |
August | 0.435105E+10 | 0.529502E+09 | 0.212533E+10 | 0.539978E+09 | 0.158535E+10 | 0.00 | 0.00 |
September | 0.599751E+10 | 0.111023E+10 | 0.325714E+10 | 0.169224E+10 | 0.156490E+10 | 0.00 | 0.00 |
October | 0.726882E+10 | 0.194230E+10 | 0.461996E+10 | 0.313884E+10 | 0.148112E+10 | 0.00 | 0.00 |
November | 0.748362E+10 | 0.318779E+10 | 0.538106E+10 | 0.411592E+10 | 0.126514E+10 | 0.00 | 0.00 |
December | 0.710694E+10 | 0.419150E+10 | 0.546774E+10 | 0.410783E+10 | 0.135992E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.657727E+11 | 0.245859E+11 | 0.424928E+11 | 0.245878E+11 | 0.179050E+11 | 0.00 | 0.00 |
Minimum of Months | 0.347203E+10 | 0.341053E+09 | 0.160442E+10 | 0.100952E+09 | 0.126514E+10 | 0.00 | 0.00 |
Maximum of Months | 0.748362E+10 | 0.419150E+10 | 0.546774E+10 | 0.411592E+10 | 0.169911E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.937396E+10 | 0.522573E+10 | 0.691870E+10 | 0.524250E+10 | 0.167620E+10 | 0.00 | 0.00 |
February | 0.813132E+10 | 0.417964E+10 | 0.587949E+10 | 0.416969E+10 | 0.170980E+10 | 0.00 | 0.00 |
March | 0.727092E+10 | 0.404853E+10 | 0.509227E+10 | 0.288503E+10 | 0.220724E+10 | 0.00 | 0.00 |
April | 0.559928E+10 | 0.230680E+10 | 0.343383E+10 | 0.128902E+10 | 0.214480E+10 | 0.00 | 0.00 |
May | 0.463724E+10 | 0.131959E+10 | 0.251798E+10 | 0.369271E+09 | 0.214871E+10 | 0.00 | 0.00 |
June | 0.474050E+10 | 0.575363E+09 | 0.208423E+10 | 0.131142E+09 | 0.195309E+10 | 0.00 | 0.00 |
July | 0.496880E+10 | 0.443892E+09 | 0.218715E+10 | 0.193914E+09 | 0.199323E+10 | 0.00 | 0.00 |
August | 0.582261E+10 | 0.687600E+09 | 0.276092E+10 | 0.701462E+09 | 0.205946E+10 | 0.00 | 0.00 |
September | 0.798705E+10 | 0.143707E+10 | 0.423121E+10 | 0.219832E+10 | 0.203289E+10 | 0.00 | 0.00 |
October | 0.963638E+10 | 0.254562E+10 | 0.600158E+10 | 0.407753E+10 | 0.192406E+10 | 0.00 | 0.00 |
November | 0.990430E+10 | 0.423412E+10 | 0.699030E+10 | 0.534681E+10 | 0.164349E+10 | 0.00 | 0.00 |
December | 0.941930E+10 | 0.560223E+10 | 0.710291E+10 | 0.533630E+10 | 0.176661E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.874917E+11 | 0.326062E+11 | 0.552006E+11 | 0.319410E+11 | 0.232596E+11 | 0.00 | 0.00 |
Minimum of Months | 0.463724E+10 | 0.443892E+09 | 0.208423E+10 | 0.131142E+09 | 0.164349E+10 | 0.00 | 0.00 |
Maximum of Months | 0.990430E+10 | 0.560223E+10 | 0.710291E+10 | 0.534681E+10 | 0.220724E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.791072E+09 | 0.720671E+09 | 0.661628E+09 | 0.445502E+09 | 0.216126E+09 | 0.00 | 0.00 |
February | 0.764437E+09 | 0.573738E+09 | 0.610259E+09 | 0.380562E+09 | 0.229697E+09 | 0.00 | 0.00 |
March | 0.963989E+09 | 0.542220E+09 | 0.717083E+09 | 0.392853E+09 | 0.324229E+09 | 0.00 | 0.00 |
April | 0.106986E+10 | 0.273425E+09 | 0.676285E+09 | 0.334351E+09 | 0.341935E+09 | 0.00 | 0.00 |
May | 0.122716E+10 | 0.134436E+09 | 0.683278E+09 | 0.312791E+09 | 0.370487E+09 | 0.00 | 0.00 |
June | 0.132260E+10 | 45690962.25 | 0.627908E+09 | 0.283748E+09 | 0.344161E+09 | 0.00 | 0.00 |
July | 0.126404E+10 | 26027800.74 | 0.591061E+09 | 0.245426E+09 | 0.345635E+09 | 0.00 | 0.00 |
August | 0.123072E+10 | 52961109.32 | 0.607067E+09 | 0.271168E+09 | 0.335899E+09 | 0.00 | 0.00 |
September | 0.125903E+10 | 0.154361E+09 | 0.683569E+09 | 0.372750E+09 | 0.310819E+09 | 0.00 | 0.00 |
October | 0.115055E+10 | 0.314871E+09 | 0.729374E+09 | 0.457483E+09 | 0.271891E+09 | 0.00 | 0.00 |
November | 0.923942E+09 | 0.576973E+09 | 0.704840E+09 | 0.487965E+09 | 0.216875E+09 | 0.00 | 0.00 |
December | 0.756671E+09 | 0.784661E+09 | 0.656450E+09 | 0.436397E+09 | 0.220053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127241E+11 | 0.420004E+10 | 0.794880E+10 | 0.442100E+10 | 0.352781E+10 | 0.00 | 0.00 |
Minimum of Months | 0.756671E+09 | 26027800.74 | 0.591061E+09 | 0.245426E+09 | 0.216126E+09 | 0.00 | 0.00 |
Maximum of Months | 0.132260E+10 | 0.784661E+09 | 0.729374E+09 | 0.487965E+09 | 0.370487E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.332531E+09 | 0.755416E+09 | 0.342309E+09 | 0.162146E+09 | 0.180162E+09 | 0.00 | 0.00 |
February | 0.380358E+09 | 0.602373E+09 | 0.352733E+09 | 0.155192E+09 | 0.197541E+09 | 0.00 | 0.00 |
March | 0.646687E+09 | 0.556693E+09 | 0.529172E+09 | 0.236921E+09 | 0.292251E+09 | 0.00 | 0.00 |
April | 0.889100E+09 | 0.278703E+09 | 0.588821E+09 | 0.265930E+09 | 0.322892E+09 | 0.00 | 0.00 |
May | 0.117402E+10 | 0.135389E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
June | 0.132738E+10 | 46291886.12 | 0.638530E+09 | 0.292021E+09 | 0.346509E+09 | 0.00 | 0.00 |
July | 0.124581E+10 | 27407254.37 | 0.590530E+09 | 0.246488E+09 | 0.344041E+09 | 0.00 | 0.00 |
August | 0.111409E+10 | 55959453.07 | 0.557372E+09 | 0.235622E+09 | 0.321750E+09 | 0.00 | 0.00 |
September | 0.974941E+09 | 0.163045E+09 | 0.538673E+09 | 0.254037E+09 | 0.284635E+09 | 0.00 | 0.00 |
October | 0.716782E+09 | 0.334055E+09 | 0.476768E+09 | 0.237094E+09 | 0.239674E+09 | 0.00 | 0.00 |
November | 0.435228E+09 | 0.608007E+09 | 0.383093E+09 | 0.198972E+09 | 0.184121E+09 | 0.00 | 0.00 |
December | 0.294510E+09 | 0.832090E+09 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.953143E+10 | 0.439543E+10 | 0.599172E+10 | 0.273405E+10 | 0.325767E+10 | 0.00 | 0.00 |
Minimum of Months | 0.294510E+09 | 27407254.37 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Maximum of Months | 0.132738E+10 | 0.832090E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.374421E+09 | 0.271989E+09 | 0.299104E+09 | 0.226640E+09 | 72464826.42 | 0.00 | 0.00 |
February | 0.322980E+09 | 0.221057E+09 | 0.254178E+09 | 0.180261E+09 | 73917324.87 | 0.00 | 0.00 |
March | 0.280152E+09 | 0.215200E+09 | 0.220146E+09 | 0.124724E+09 | 95422629.83 | 0.00 | 0.00 |
April | 0.212405E+09 | 0.130995E+09 | 0.148450E+09 | 55726088.50 | 92723544.22 | 0.00 | 0.00 |
May | 0.170768E+09 | 81109259.32 | 0.108857E+09 | 15964013.69 | 92892545.85 | 0.00 | 0.00 |
June | 0.175640E+09 | 40915079.89 | 90105188.78 | 5669429.11 | 84435759.67 | 0.00 | 0.00 |
July | 0.183576E+09 | 36004677.40 | 94554156.30 | 8383125.91 | 86171030.39 | 0.00 | 0.00 |
August | 0.221769E+09 | 50073828.02 | 0.119359E+09 | 30325060.49 | 89033931.16 | 0.00 | 0.00 |
September | 0.319126E+09 | 88311679.90 | 0.182921E+09 | 95036114.58 | 87885276.20 | 0.00 | 0.00 |
October | 0.386958E+09 | 0.144051E+09 | 0.259457E+09 | 0.176276E+09 | 83180150.54 | 0.00 | 0.00 |
November | 0.399835E+09 | 0.222390E+09 | 0.302200E+09 | 0.231149E+09 | 71050625.13 | 0.00 | 0.00 |
December | 0.377135E+09 | 0.286531E+09 | 0.307068E+09 | 0.230695E+09 | 76373138.43 | 0.00 | 0.00 |
Annual Sum or Average | 0.342476E+10 | 0.178863E+10 | 0.238640E+10 | 0.138085E+10 | 0.100555E+10 | 0.00 | 0.00 |
Minimum of Months | 0.170768E+09 | 36004677.40 | 90105188.78 | 5669429.11 | 71050625.13 | 0.00 | 0.00 |
Maximum of Months | 0.399835E+09 | 0.286531E+09 | 0.307068E+09 | 0.231149E+09 | 95422629.83 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 10593630.19 | 0.224497E+09 | 43713969.60 | 0.00 | 43713969.60 | 0.00 | 0.00 |
February | 25627392.16 | 0.175808E+09 | 48213648.10 | 0.00 | 48213648.10 | 0.00 | 0.00 |
March | 57200069.18 | 0.158301E+09 | 69870982.94 | 2765.95 | 69868216.99 | 0.00 | 0.00 |
April | 0.110179E+09 | 73465893.92 | 78518344.10 | 1000279.47 | 77518064.63 | 0.00 | 0.00 |
May | 0.187619E+09 | 32907015.29 | 95843144.60 | 7063304.15 | 88779840.45 | 0.00 | 0.00 |
June | 0.251022E+09 | 10366504.70 | 98633813.54 | 12290815.53 | 86342998.01 | 0.00 | 0.00 |
July | 0.242162E+09 | 5598061.00 | 94160895.41 | 9236150.10 | 84924745.31 | 0.00 | 0.00 |
August | 0.192470E+09 | 12639644.95 | 79637162.39 | 1894638.37 | 77742524.03 | 0.00 | 0.00 |
September | 0.135918E+09 | 40169660.21 | 67049393.63 | 84739.01 | 66964654.62 | 0.00 | 0.00 |
October | 76362186.58 | 89251440.42 | 57430655.00 | 0.00 | 57430655.00 | 0.00 | 0.00 |
November | 21405304.93 | 0.175076E+09 | 44867884.08 | 0.00 | 44867884.08 | 0.00 | 0.00 |
December | 7292380.31 | 0.249155E+09 | 43375413.74 | 0.00 | 43375413.74 | 0.00 | 0.00 |
Annual Sum or Average | 0.131785E+10 | 0.124724E+10 | 0.821315E+09 | 31572692.58 | 0.789743E+09 | 0.00 | 0.00 |
Minimum of Months | 7292380.31 | 5598061.00 | 43375413.74 | 0.00 | 43375413.74 | 0.00 | 0.00 |
Maximum of Months | 0.251022E+09 | 0.249155E+09 | 98633813.54 | 12290815.53 | 88779840.45 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.754647E+09 | 0.708223E+09 | 0.646361E+09 | 0.430960E+09 | 0.215402E+09 | 0.00 | 0.00 |
February | 0.808505E+09 | 0.558432E+09 | 0.648005E+09 | 0.413664E+09 | 0.234341E+09 | 0.00 | 0.00 |
March | 0.950519E+09 | 0.512049E+09 | 0.725871E+09 | 0.404058E+09 | 0.321813E+09 | 0.00 | 0.00 |
April | 0.110354E+10 | 0.249691E+09 | 0.711319E+09 | 0.361253E+09 | 0.350066E+09 | 0.00 | 0.00 |
May | 0.123924E+10 | 0.122495E+09 | 0.696105E+09 | 0.324180E+09 | 0.371925E+09 | 0.00 | 0.00 |
June | 0.136602E+10 | 42641808.33 | 0.654827E+09 | 0.308561E+09 | 0.346266E+09 | 0.00 | 0.00 |
July | 0.131314E+10 | 24881461.19 | 0.620963E+09 | 0.273320E+09 | 0.347643E+09 | 0.00 | 0.00 |
August | 0.126600E+10 | 49885373.53 | 0.628139E+09 | 0.283153E+09 | 0.344986E+09 | 0.00 | 0.00 |
September | 0.125409E+10 | 0.142564E+09 | 0.688511E+09 | 0.381390E+09 | 0.307121E+09 | 0.00 | 0.00 |
October | 0.106832E+10 | 0.303093E+09 | 0.688060E+09 | 0.416283E+09 | 0.271777E+09 | 0.00 | 0.00 |
November | 0.886070E+09 | 0.560447E+09 | 0.692953E+09 | 0.472029E+09 | 0.220924E+09 | 0.00 | 0.00 |
December | 0.742330E+09 | 0.769908E+09 | 0.656523E+09 | 0.432885E+09 | 0.223638E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127524E+11 | 0.404431E+10 | 0.805764E+10 | 0.450174E+10 | 0.355590E+10 | 0.00 | 0.00 |
Minimum of Months | 0.742330E+09 | 24881461.19 | 0.620963E+09 | 0.273320E+09 | 0.215402E+09 | 0.00 | 0.00 |
Maximum of Months | 0.136602E+10 | 0.769908E+09 | 0.725871E+09 | 0.472029E+09 | 0.371925E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.269338E+09 | 0.713338E+09 | 0.327041E+09 | 0.147604E+09 | 0.179438E+09 | 0.00 | 0.00 |
February | 0.399152E+09 | 0.559307E+09 | 0.390478E+09 | 0.188293E+09 | 0.202185E+09 | 0.00 | 0.00 |
March | 0.624087E+09 | 0.513201E+09 | 0.537961E+09 | 0.248126E+09 | 0.289835E+09 | 0.00 | 0.00 |
April | 0.921625E+09 | 0.255210E+09 | 0.623855E+09 | 0.292832E+09 | 0.331023E+09 | 0.00 | 0.00 |
May | 0.118078E+10 | 0.127742E+09 | 0.679796E+09 | 0.313049E+09 | 0.366746E+09 | 0.00 | 0.00 |
June | 0.136407E+10 | 44533342.14 | 0.665449E+09 | 0.316834E+09 | 0.348614E+09 | 0.00 | 0.00 |
July | 0.128860E+10 | 26733276.86 | 0.620433E+09 | 0.274383E+09 | 0.346050E+09 | 0.00 | 0.00 |
August | 0.114246E+10 | 53216824.83 | 0.578444E+09 | 0.247607E+09 | 0.330837E+09 | 0.00 | 0.00 |
September | 0.959047E+09 | 0.148977E+09 | 0.543615E+09 | 0.262677E+09 | 0.280938E+09 | 0.00 | 0.00 |
October | 0.627408E+09 | 0.309871E+09 | 0.435454E+09 | 0.195894E+09 | 0.239560E+09 | 0.00 | 0.00 |
November | 0.373605E+09 | 0.563861E+09 | 0.371206E+09 | 0.183035E+09 | 0.188171E+09 | 0.00 | 0.00 |
December | 0.247487E+09 | 0.782746E+09 | 0.326824E+09 | 0.144459E+09 | 0.182365E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.939766E+10 | 0.409873E+10 | 0.610055E+10 | 0.281479E+10 | 0.328576E+10 | 0.00 | 0.00 |
Minimum of Months | 0.247487E+09 | 26733276.86 | 0.326824E+09 | 0.144459E+09 | 0.179438E+09 | 0.00 | 0.00 |
Maximum of Months | 0.136407E+10 | 0.782746E+09 | 0.679796E+09 | 0.316834E+09 | 0.366746E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.863286E+09 | 0.903934E+09 | 0.742775E+09 | 0.491065E+09 | 0.251710E+09 | 0.00 | 0.00 |
February | 0.794348E+09 | 0.724842E+09 | 0.655180E+09 | 0.390575E+09 | 0.264605E+09 | 0.00 | 0.00 |
March | 0.800331E+09 | 0.699483E+09 | 0.628360E+09 | 0.270247E+09 | 0.358112E+09 | 0.00 | 0.00 |
April | 0.761016E+09 | 0.377151E+09 | 0.491746E+09 | 0.122910E+09 | 0.368836E+09 | 0.00 | 0.00 |
May | 0.822133E+09 | 0.204728E+09 | 0.443490E+09 | 49891063.49 | 0.393599E+09 | 0.00 | 0.00 |
June | 0.956878E+09 | 88400204.53 | 0.408907E+09 | 38910104.08 | 0.369997E+09 | 0.00 | 0.00 |
July | 0.955553E+09 | 64252278.24 | 0.408857E+09 | 38172500.78 | 0.370684E+09 | 0.00 | 0.00 |
August | 0.931254E+09 | 0.106145E+09 | 0.431139E+09 | 69810394.97 | 0.361328E+09 | 0.00 | 0.00 |
September | 0.101983E+10 | 0.249245E+09 | 0.541591E+09 | 0.206100E+09 | 0.335491E+09 | 0.00 | 0.00 |
October | 0.105060E+10 | 0.443398E+09 | 0.686584E+09 | 0.381942E+09 | 0.304642E+09 | 0.00 | 0.00 |
November | 0.941365E+09 | 0.747703E+09 | 0.751982E+09 | 0.500836E+09 | 0.251146E+09 | 0.00 | 0.00 |
December | 0.853883E+09 | 0.972941E+09 | 0.759297E+09 | 0.499852E+09 | 0.259445E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107505E+11 | 0.558222E+10 | 0.694991E+10 | 0.306031E+10 | 0.388960E+10 | 0.00 | 0.00 |
Minimum of Months | 0.761016E+09 | 64252278.24 | 0.408857E+09 | 38172500.78 | 0.251146E+09 | 0.00 | 0.00 |
Maximum of Months | 0.105060E+10 | 0.972941E+09 | 0.759297E+09 | 0.500836E+09 | 0.393599E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.788390E+09 | 0.711933E+09 | 0.661628E+09 | 0.445502E+09 | 0.216126E+09 | 0.00 | 0.00 |
February | 0.760928E+09 | 0.565792E+09 | 0.610259E+09 | 0.380562E+09 | 0.229697E+09 | 0.00 | 0.00 |
March | 0.957041E+09 | 0.534038E+09 | 0.717083E+09 | 0.392853E+09 | 0.324229E+09 | 0.00 | 0.00 |
April | 0.106208E+10 | 0.266810E+09 | 0.676285E+09 | 0.334351E+09 | 0.341935E+09 | 0.00 | 0.00 |
May | 0.122083E+10 | 0.128628E+09 | 0.683278E+09 | 0.312791E+09 | 0.370487E+09 | 0.00 | 0.00 |
June | 0.131832E+10 | 42843036.90 | 0.627908E+09 | 0.283748E+09 | 0.344161E+09 | 0.00 | 0.00 |
July | 0.125859E+10 | 24013292.99 | 0.591061E+09 | 0.245426E+09 | 0.345635E+09 | 0.00 | 0.00 |
August | 0.122492E+10 | 49848481.52 | 0.607067E+09 | 0.271168E+09 | 0.335899E+09 | 0.00 | 0.00 |
September | 0.125143E+10 | 0.148967E+09 | 0.683569E+09 | 0.372750E+09 | 0.310819E+09 | 0.00 | 0.00 |
October | 0.114462E+10 | 0.307635E+09 | 0.729374E+09 | 0.457483E+09 | 0.271891E+09 | 0.00 | 0.00 |
November | 0.921233E+09 | 0.566946E+09 | 0.704840E+09 | 0.487965E+09 | 0.216875E+09 | 0.00 | 0.00 |
December | 0.756572E+09 | 0.774941E+09 | 0.656450E+09 | 0.436397E+09 | 0.220053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.126649E+11 | 0.412240E+10 | 0.794880E+10 | 0.442100E+10 | 0.352781E+10 | 0.00 | 0.00 |
Minimum of Months | 0.756572E+09 | 24013292.99 | 0.591061E+09 | 0.245426E+09 | 0.216126E+09 | 0.00 | 0.00 |
Maximum of Months | 0.131832E+10 | 0.774941E+09 | 0.729374E+09 | 0.487965E+09 | 0.370487E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.334492E+09 | 0.743134E+09 | 0.342309E+09 | 0.162146E+09 | 0.180162E+09 | 0.00 | 0.00 |
February | 0.380950E+09 | 0.591735E+09 | 0.352733E+09 | 0.155192E+09 | 0.197541E+09 | 0.00 | 0.00 |
March | 0.643840E+09 | 0.547920E+09 | 0.529172E+09 | 0.236921E+09 | 0.292251E+09 | 0.00 | 0.00 |
April | 0.883466E+09 | 0.272816E+09 | 0.588821E+09 | 0.265930E+09 | 0.322892E+09 | 0.00 | 0.00 |
May | 0.116880E+10 | 0.129987E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
June | 0.132304E+10 | 43576082.94 | 0.638530E+09 | 0.292021E+09 | 0.346509E+09 | 0.00 | 0.00 |
July | 0.124058E+10 | 25470961.25 | 0.590530E+09 | 0.246488E+09 | 0.344041E+09 | 0.00 | 0.00 |
August | 0.110997E+10 | 52811848.09 | 0.557372E+09 | 0.235622E+09 | 0.321750E+09 | 0.00 | 0.00 |
September | 0.970483E+09 | 0.157037E+09 | 0.538673E+09 | 0.254037E+09 | 0.284635E+09 | 0.00 | 0.00 |
October | 0.714544E+09 | 0.326272E+09 | 0.476768E+09 | 0.237094E+09 | 0.239674E+09 | 0.00 | 0.00 |
November | 0.437176E+09 | 0.593972E+09 | 0.383093E+09 | 0.198972E+09 | 0.184121E+09 | 0.00 | 0.00 |
December | 0.297685E+09 | 0.818807E+09 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.950503E+10 | 0.430354E+10 | 0.599172E+10 | 0.273405E+10 | 0.325767E+10 | 0.00 | 0.00 |
Minimum of Months | 0.297685E+09 | 25470961.25 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Maximum of Months | 0.132304E+10 | 0.818807E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.730024E+09 | 0.374595E+09 | 0.548441E+09 | 0.415568E+09 | 0.132872E+09 | 0.00 | 0.00 |
February | 0.635595E+09 | 0.294451E+09 | 0.466063E+09 | 0.330528E+09 | 0.135536E+09 | 0.00 | 0.00 |
March | 0.568390E+09 | 0.276620E+09 | 0.403662E+09 | 0.228694E+09 | 0.174968E+09 | 0.00 | 0.00 |
April | 0.452368E+09 | 0.136080E+09 | 0.272199E+09 | 0.102180E+09 | 0.170019E+09 | 0.00 | 0.00 |
May | 0.400627E+09 | 62520938.89 | 0.199600E+09 | 29271767.90 | 0.170329E+09 | 0.00 | 0.00 |
June | 0.430171E+09 | 19411361.27 | 0.165218E+09 | 10395519.34 | 0.154822E+09 | 0.00 | 0.00 |
July | 0.446386E+09 | 10648968.87 | 0.173375E+09 | 15371379.69 | 0.158004E+09 | 0.00 | 0.00 |
August | 0.502481E+09 | 23527041.40 | 0.218858E+09 | 55604320.39 | 0.163253E+09 | 0.00 | 0.00 |
September | 0.649482E+09 | 73141308.29 | 0.335406E+09 | 0.174259E+09 | 0.161147E+09 | 0.00 | 0.00 |
October | 0.767637E+09 | 0.156673E+09 | 0.475742E+09 | 0.323222E+09 | 0.152520E+09 | 0.00 | 0.00 |
November | 0.780851E+09 | 0.293833E+09 | 0.554116E+09 | 0.423837E+09 | 0.130279E+09 | 0.00 | 0.00 |
December | 0.738113E+09 | 0.405964E+09 | 0.563043E+09 | 0.423004E+09 | 0.140039E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.710213E+10 | 0.212746E+10 | 0.437572E+10 | 0.253194E+10 | 0.184379E+10 | 0.00 | 0.00 |
Minimum of Months | 0.400627E+09 | 10648968.87 | 0.165218E+09 | 10395519.34 | 0.130279E+09 | 0.00 | 0.00 |
Maximum of Months | 0.780851E+09 | 0.405964E+09 | 0.563043E+09 | 0.423837E+09 | 0.174968E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 39594857.05 | 0.237047E+10 | 0.382432E+09 | 0.00 | 0.382432E+09 | 0.00 | 0.00 |
February | 0.146042E+09 | 0.186419E+10 | 0.421798E+09 | 0.00 | 0.421798E+09 | 0.00 | 0.00 |
March | 0.374834E+09 | 0.168832E+10 | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.00 | 0.00 |
April | 0.795621E+09 | 0.861127E+09 | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.00 | 0.00 |
May | 0.141554E+10 | 0.452092E+09 | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.00 | 0.00 |
June | 0.193134E+10 | 0.199055E+09 | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.00 | 0.00 |
July | 0.183930E+10 | 0.154066E+09 | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.00 | 0.00 |
August | 0.143184E+10 | 0.241645E+09 | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.00 | 0.00 |
September | 0.101951E+10 | 0.532254E+09 | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.00 | 0.00 |
October | 0.525558E+09 | 0.102580E+10 | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.00 | 0.00 |
November | 0.106176E+09 | 0.188155E+10 | 0.392527E+09 | 0.00 | 0.392527E+09 | 0.00 | 0.00 |
December | 27448927.33 | 0.258268E+10 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.965281E+10 | 0.138532E+11 | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.00 | 0.00 |
Minimum of Months | 27448927.33 | 0.154066E+09 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Maximum of Months | 0.193134E+10 | 0.258268E+10 | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 30328224.99 | 0.244938E+10 | 0.382432E+09 | 0.00 | 0.382432E+09 | 0.00 | 0.00 |
February | 0.129854E+09 | 0.192201E+10 | 0.421798E+09 | 0.00 | 0.421798E+09 | 0.00 | 0.00 |
March | 0.347095E+09 | 0.173732E+10 | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.00 | 0.00 |
April | 0.769187E+09 | 0.887868E+09 | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.00 | 0.00 |
May | 0.138956E+10 | 0.468122E+09 | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.00 | 0.00 |
June | 0.190759E+10 | 0.207973E+09 | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.00 | 0.00 |
July | 0.181488E+10 | 0.163222E+09 | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.00 | 0.00 |
August | 0.140785E+10 | 0.253397E+09 | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.00 | 0.00 |
September | 0.100065E+10 | 0.549991E+09 | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.00 | 0.00 |
October | 0.504017E+09 | 0.105638E+10 | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.00 | 0.00 |
November | 91500224.86 | 0.193887E+10 | 0.392527E+09 | 0.00 | 0.392527E+09 | 0.00 | 0.00 |
December | 21343497.87 | 0.266705E+10 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.941385E+10 | 0.143016E+11 | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.00 | 0.00 |
Minimum of Months | 21343497.87 | 0.163222E+09 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Maximum of Months | 0.190759E+10 | 0.266705E+10 | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105169E+10 | 0.156755E+10 | 0.973364E+09 | 0.578542E+09 | 0.394822E+09 | 0.00 | 0.00 |
February | 0.127495E+10 | 0.124386E+10 | 0.103844E+10 | 0.601931E+09 | 0.436505E+09 | 0.00 | 0.00 |
March | 0.168625E+10 | 0.116763E+10 | 0.126377E+10 | 0.652149E+09 | 0.611620E+09 | 0.00 | 0.00 |
April | 0.221832E+10 | 0.636434E+09 | 0.133510E+10 | 0.654044E+09 | 0.681055E+09 | 0.00 | 0.00 |
May | 0.265233E+10 | 0.384131E+09 | 0.137582E+10 | 0.637186E+09 | 0.738635E+09 | 0.00 | 0.00 |
June | 0.297253E+10 | 0.190306E+09 | 0.132020E+10 | 0.625352E+09 | 0.694846E+09 | 0.00 | 0.00 |
July | 0.285029E+10 | 0.155544E+09 | 0.124132E+10 | 0.547666E+09 | 0.693659E+09 | 0.00 | 0.00 |
August | 0.266392E+10 | 0.217452E+09 | 0.120652E+10 | 0.530726E+09 | 0.675789E+09 | 0.00 | 0.00 |
September | 0.248515E+10 | 0.393728E+09 | 0.123206E+10 | 0.644030E+09 | 0.588031E+09 | 0.00 | 0.00 |
October | 0.187007E+10 | 0.725602E+09 | 0.112346E+10 | 0.612150E+09 | 0.511313E+09 | 0.00 | 0.00 |
November | 0.133825E+10 | 0.124122E+10 | 0.106411E+10 | 0.655039E+09 | 0.409076E+09 | 0.00 | 0.00 |
December | 0.101595E+10 | 0.167520E+10 | 0.983308E+09 | 0.577324E+09 | 0.405984E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.240797E+11 | 0.959866E+10 | 0.141575E+11 | 0.731614E+10 | 0.684134E+10 | 0.00 | 0.00 |
Minimum of Months | 0.101595E+10 | 0.155544E+09 | 0.973364E+09 | 0.530726E+09 | 0.394822E+09 | 0.00 | 0.00 |
Maximum of Months | 0.297253E+10 | 0.167520E+10 | 0.137582E+10 | 0.655039E+09 | 0.738635E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.184572E+10 | 0.159929E+10 | 0.152718E+10 | 0.105785E+10 | 0.469332E+09 | 0.00 | 0.00 |
February | 0.166288E+10 | 0.127558E+10 | 0.133098E+10 | 0.841376E+09 | 0.489606E+09 | 0.00 | 0.00 |
March | 0.160580E+10 | 0.122634E+10 | 0.123709E+10 | 0.582162E+09 | 0.654925E+09 | 0.00 | 0.00 |
April | 0.142314E+10 | 0.675629E+09 | 0.928373E+09 | 0.263104E+09 | 0.665269E+09 | 0.00 | 0.00 |
May | 0.143202E+10 | 0.377241E+09 | 0.795528E+09 | 95695732.11 | 0.699832E+09 | 0.00 | 0.00 |
June | 0.162647E+10 | 0.168864E+09 | 0.716374E+09 | 63322576.03 | 0.653051E+09 | 0.00 | 0.00 |
July | 0.163184E+10 | 0.129418E+09 | 0.723725E+09 | 66827933.17 | 0.656897E+09 | 0.00 | 0.00 |
August | 0.166265E+10 | 0.203947E+09 | 0.795946E+09 | 0.147226E+09 | 0.648721E+09 | 0.00 | 0.00 |
September | 0.195115E+10 | 0.449961E+09 | 0.105488E+10 | 0.443840E+09 | 0.611036E+09 | 0.00 | 0.00 |
October | 0.211936E+10 | 0.778689E+09 | 0.138326E+10 | 0.822779E+09 | 0.560482E+09 | 0.00 | 0.00 |
November | 0.200556E+10 | 0.129211E+10 | 0.154509E+10 | 0.107890E+10 | 0.466191E+09 | 0.00 | 0.00 |
December | 0.184008E+10 | 0.172353E+10 | 0.156334E+10 | 0.107678E+10 | 0.486559E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.208067E+11 | 0.990060E+10 | 0.136018E+11 | 0.653986E+10 | 0.706190E+10 | 0.00 | 0.00 |
Minimum of Months | 0.142314E+10 | 0.129418E+09 | 0.716374E+09 | 63322576.03 | 0.466191E+09 | 0.00 | 0.00 |
Maximum of Months | 0.211936E+10 | 0.172353E+10 | 0.156334E+10 | 0.107890E+10 | 0.699832E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770482E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162026163.0 | 81.21 | 0.00 | 0.00 |
February | 0.696226E+10 | -0.681598E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146281682.4 | 81.21 | 0.00 | 0.00 |
March | 0.770331E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161853630.4 | 81.21 | 0.00 | 0.00 |
April | 0.746499E+10 | -0.730858E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156409002.1 | 81.21 | 0.00 | 0.00 |
May | 0.770429E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161500425.5 | 81.21 | 0.00 | 0.00 |
June | 0.745676E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156228724.6 | 81.21 | 0.00 | 0.00 |
July | 0.771228E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161432066.3 | 81.21 | 0.00 | 0.00 |
August | 0.770425E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161446994.9 | 81.21 | 0.00 | 0.00 |
September | 0.746621E+10 | -0.730993E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156278969.6 | 81.21 | 0.00 | 0.00 |
October | 0.770306E+10 | -0.754143E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161632460.3 | 81.21 | 0.00 | 0.00 |
November | 0.744912E+10 | -0.729242E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156697874.7 | 81.21 | 0.00 | 0.00 |
December | 0.771296E+10 | -0.755087E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162093102.7 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907443E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190388E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696226E+10 | -0.755087E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162093102.7 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771296E+10 | -0.681598E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146281682.4 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYSLAUNDRY HPWH TANK
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.513132E+11 | -0.110535E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -826131063.8 | 81.67 | 0.00 | 0.00 |
February | 0.447808E+11 | -0.997722E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -731573889.4 | 81.67 | 0.00 | 0.00 |
March | 0.447073E+11 | -0.107758E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -792495272.3 | 81.67 | 0.00 | 0.00 |
April | 0.319343E+11 | -0.996727E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -716459475.2 | 81.68 | 0.00 | 0.00 |
May | 0.224940E+11 | -0.974754E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -705575051.9 | 81.68 | 0.00 | 0.00 |
June | 0.134153E+11 | -0.896973E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -652729655.7 | 81.67 | 0.00 | 0.00 |
July | 0.862089E+10 | -0.899348E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -677002417.9 | 81.67 | 0.00 | 0.00 |
August | 0.106462E+11 | -0.899545E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -687027294.7 | 81.68 | 0.00 | 0.00 |
September | 0.151141E+11 | -0.897560E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -686526451.6 | 81.68 | 0.00 | 0.00 |
October | 0.255846E+11 | -0.975587E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -747921787.9 | 81.68 | 0.00 | 0.00 |
November | 0.393575E+11 | -0.997534E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -776621048.9 | 81.67 | 0.00 | 0.00 |
December | 0.507338E+11 | -0.107819E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -837313144.8 | 81.67 | 0.00 | 0.00 |
Annual Sum or Average | 0.358702E+12 | -0.117969E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.883738E+10 | 81.68 | 0.00 | 0.00 |
Minimum of Months | 0.862089E+10 | -0.110535E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -837313144.8 | 81.67 | 0.00 | 0.00 |
Maximum of Months | 0.513132E+11 | -0.896973E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -652729655.7 | 81.68 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 HPWH TANK
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | -0.196269E+10 | -0.654271E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.131372E+10 | 59.30 | 0.00 | 0.00 |
February | -0.190472E+10 | -0.590591E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.115174E+10 | 59.31 | 0.00 | 0.00 |
March | -0.222005E+10 | -0.631055E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.123382E+10 | 59.33 | 0.00 | 0.00 |
April | -0.221724E+10 | -0.570718E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.107387E+10 | 59.37 | 0.00 | 0.00 |
May | -0.224219E+10 | -0.542201E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102729E+10 | 59.41 | 0.00 | 0.00 |
June | -0.184687E+10 | -0.484840E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -923396497.3 | 59.45 | 0.00 | 0.00 |
July | -0.178489E+10 | -0.476684E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -960897602.7 | 59.48 | 0.00 | 0.00 |
August | -0.176313E+10 | -0.477369E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -985167842.0 | 59.49 | 0.00 | 0.00 |
September | -0.184793E+10 | -0.485117E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.100445E+10 | 59.46 | 0.00 | 0.00 |
October | -0.216102E+10 | -0.542588E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.112907E+10 | 59.41 | 0.00 | 0.00 |
November | -0.201453E+10 | -0.571074E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.121854E+10 | 59.37 | 0.00 | 0.00 |
December | -0.181983E+10 | -0.630804E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.134157E+10 | 59.33 | 0.00 | 0.00 |
Annual Sum or Average | -0.237851E+11 | -0.665731E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.133635E+11 | 59.39 | 0.00 | 0.00 |
Minimum of Months | -0.224219E+10 | -0.654271E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.134157E+10 | 59.30 | 0.00 | 0.00 |
Maximum of Months | -0.176313E+10 | -0.476684E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -923396497.3 | 59.49 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.86 | 0.86 | 01-JAN-08:09 | 7206.50 | 38.27 | 274.17 | 278.00 | 949.80 | 26.84 | 164.83 | 257.17 |
February | 268.33 | 0.87 | 0.86 | 01-FEB-07:49 | 5842.96 | 33.62 | 210.83 | 270.83 | 596.94 | 23.71 | 144.50 | 237.17 |
March | 351.83 | 0.87 | 0.86 | 01-MAR-07:10 | 1032.16 | 19.53 | 12.00 | 317.83 | 398.13 | 20.87 | 123.83 | 242.50 |
April | 373.83 | 0.87 | 0.86 | 01-APR-07:10 | 746.19 | 19.06 | 0.00 | 335.17 | 316.76 | 20.82 | 122.83 | 235.50 |
May | 408.83 | 0.88 | 0.86 | 01-MAY-07:10 | 624.18 | 18.70 | 0.00 | 359.00 | 269.25 | 20.45 | 85.17 | 234.33 |
June | 398.00 | 0.87 | 0.86 | 01-JUN-07:49 | 547.31 | 18.62 | 0.00 | 349.50 | 242.61 | 20.43 | 37.33 | 166.67 |
July | 400.17 | 0.88 | 0.86 | 01-JUL-07:49 | 599.84 | 18.49 | 0.00 | 356.67 | 257.08 | 20.27 | 73.83 | 184.33 |
August | 377.83 | 0.87 | 0.86 | 01-AUG-07:30 | 702.43 | 18.82 | 0.00 | 346.00 | 297.01 | 20.57 | 125.67 | 230.33 |
September | 365.83 | 0.88 | 0.86 | 01-SEP-09:20 | 806.86 | 18.93 | 0.00 | 314.83 | 341.27 | 20.72 | 128.67 | 224.33 |
October | 318.83 | 0.87 | 0.86 | 01-OCT-07:19 | 2910.30 | 26.00 | 124.83 | 312.50 | 466.70 | 21.79 | 115.83 | 273.00 |
November | 295.83 | 0.87 | 0.86 | 01-NOV-12:39 | 7457.25 | 37.43 | 288.17 | 288.17 | 727.39 | 25.69 | 136.67 | 266.67 |
December | 289.50 | 0.86 | 0.86 | 01-DEC-07:19 | 6497.88 | 37.79 | 284.33 | 276.50 | 1060.41 | 27.46 | 184.33 | 266.50 |
Annual Sum or Average | 4125.67 | 0.87 | 2543.52 | 24.34 | 1194.33 | 3805.00 | 460.33 | 22.15 | 1443.50 | 2818.50 | ||
Minimum of Months | 268.33 | 0.86 | 0.86 | 547.31 | 18.49 | 0.00 | 270.83 | 242.61 | 20.27 | 37.33 | 166.67 | |
Maximum of Months | 408.83 | 0.88 | 0.86 | 7457.25 | 38.27 | 288.17 | 359.00 | 1060.41 | 27.46 | 184.33 | 273.00 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.24 | 0.22 | 01-JAN-07:00 | 7610.17 | 38.33 | 274.50 | 284.33 | 1352.56 | 26.47 | 156.83 | 270.50 |
February | 268.33 | 0.24 | 0.22 | 01-FEB-07:49 | 6205.02 | 33.63 | 210.83 | 278.67 | 958.55 | 23.49 | 138.50 | 257.00 |
March | 351.83 | 0.26 | 0.22 | 01-MAR-06:00 | 1286.02 | 19.88 | 20.67 | 333.83 | 651.44 | 21.06 | 143.67 | 302.50 |
April | 373.83 | 0.26 | 0.22 | 01-APR-06:49 | 920.68 | 19.70 | 7.67 | 350.50 | 490.82 | 21.24 | 177.00 | 312.67 |
May | 408.83 | 0.27 | 0.22 | 01-MAY-06:19 | 752.17 | 19.52 | 0.17 | 376.50 | 396.87 | 21.05 | 208.83 | 340.50 |
June | 398.00 | 0.26 | 0.22 | 01-JUN-06:19 | 661.81 | 19.52 | 0.00 | 369.83 | 356.78 | 21.09 | 144.50 | 331.67 |
July | 400.17 | 0.27 | 0.22 | 01-JUL-06:30 | 716.11 | 19.37 | 0.00 | 377.00 | 372.99 | 20.91 | 169.33 | 327.50 |
August | 377.83 | 0.27 | 0.22 | 01-AUG-06:30 | 847.90 | 19.58 | 1.50 | 362.33 | 442.08 | 21.11 | 183.17 | 318.00 |
September | 365.83 | 0.27 | 0.22 | 01-SEP-07:10 | 1017.82 | 19.43 | 8.50 | 333.50 | 551.77 | 21.02 | 148.83 | 296.50 |
October | 318.83 | 0.25 | 0.22 | 01-OCT-06:00 | 3229.67 | 26.08 | 127.17 | 317.50 | 785.09 | 21.76 | 130.50 | 300.00 |
November | 295.83 | 0.24 | 0.22 | 01-NOV-12:39 | 7834.17 | 37.51 | 288.17 | 293.83 | 1104.66 | 25.34 | 129.83 | 280.83 |
December | 289.50 | 0.24 | 0.22 | 01-DEC-07:10 | 6887.49 | 37.85 | 284.50 | 281.83 | 1451.83 | 27.17 | 168.83 | 274.83 |
Annual Sum or Average | 4125.67 | 0.26 | 2777.70 | 24.81 | 1223.67 | 3959.67 | 694.22 | 22.38 | 1899.83 | 3612.50 | ||
Minimum of Months | 268.33 | 0.24 | 0.22 | 661.81 | 19.37 | 0.00 | 278.67 | 356.78 | 20.91 | 129.83 | 257.00 | |
Maximum of Months | 408.83 | 0.27 | 0.22 | 7834.17 | 38.33 | 288.17 | 377.00 | 1451.83 | 27.17 | 208.83 | 340.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.68 | 0.60 | 01-JAN-09:09 | 282.51 | 14.00 | 0.00 | 221.33 | 148.80 | 17.64 | 0.00 | 33.83 |
February | 268.33 | 0.66 | 0.60 | 01-FEB-11:09 | 319.80 | 14.70 | 0.00 | 229.33 | 166.71 | 18.22 | 0.00 | 66.17 |
March | 351.83 | 0.65 | 0.60 | 01-MAR-08:09 | 383.61 | 15.50 | 0.00 | 301.00 | 188.13 | 18.82 | 0.00 | 130.50 |
April | 373.83 | 0.63 | 0.60 | 01-APR-07:10 | 462.52 | 16.65 | 0.00 | 353.33 | 221.28 | 19.90 | 9.17 | 208.50 |
May | 408.83 | 0.62 | 0.60 | 01-MAY-06:10 | 601.05 | 17.37 | 5.33 | 388.67 | 257.13 | 20.48 | 73.50 | 350.33 |
June | 398.00 | 0.61 | 0.60 | 01-JUN-05:00 | 649.91 | 20.42 | 82.83 | 384.33 | 274.53 | 20.93 | 76.83 | 347.83 |
July | 400.17 | 0.61 | 0.60 | 01-JUL-05:49 | 620.53 | 18.61 | 39.33 | 395.67 | 292.41 | 21.45 | 78.33 | 323.17 |
August | 377.83 | 0.62 | 0.60 | 01-AUG-05:00 | 511.22 | 16.84 | 0.00 | 367.67 | 242.84 | 20.10 | 26.17 | 279.17 |
September | 365.83 | 0.65 | 0.60 | 01-SEP-14:20 | 377.61 | 15.82 | 0.00 | 317.67 | 190.57 | 19.13 | 0.00 | 140.33 |
October | 318.83 | 0.66 | 0.60 | 01-OCT-14:50 | 337.61 | 15.04 | 0.00 | 284.67 | 173.22 | 18.47 | 0.00 | 75.17 |
November | 295.83 | 0.68 | 0.60 | 01-NOV-13:09 | 269.97 | 14.03 | 0.00 | 230.33 | 143.33 | 17.64 | 0.00 | 14.50 |
December | 289.50 | 0.68 | 0.60 | 01-DEC-09:50 | 289.86 | 14.04 | 0.00 | 231.00 | 150.74 | 17.64 | 0.00 | 26.33 |
Annual Sum or Average | 4125.67 | 0.64 | 442.92 | 16.32 | 127.50 | 3705.00 | 210.63 | 19.37 | 264.00 | 1995.83 | ||
Minimum of Months | 268.33 | 0.61 | 0.60 | 269.97 | 14.00 | 0.00 | 221.33 | 143.33 | 17.64 | 0.00 | 14.50 | |
Maximum of Months | 408.83 | 0.68 | 0.60 | 649.91 | 20.42 | 82.83 | 395.67 | 292.41 | 21.45 | 78.33 | 350.33 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.68 | 0.60 | 01-JAN-09:09 | 282.51 | 14.00 | 0.00 | 221.33 | 148.80 | 17.64 | 0.00 | 33.83 |
February | 268.33 | 0.66 | 0.60 | 01-FEB-11:09 | 319.80 | 14.70 | 0.00 | 229.33 | 166.71 | 18.22 | 0.00 | 66.17 |
March | 351.83 | 0.65 | 0.60 | 01-MAR-08:09 | 383.61 | 15.50 | 0.00 | 301.00 | 188.13 | 18.82 | 0.00 | 130.50 |
April | 373.83 | 0.63 | 0.60 | 01-APR-07:10 | 462.52 | 16.65 | 0.00 | 353.33 | 221.28 | 19.90 | 9.17 | 208.50 |
May | 408.83 | 0.62 | 0.60 | 01-MAY-06:10 | 601.05 | 17.37 | 5.33 | 388.67 | 257.13 | 20.48 | 73.50 | 350.33 |
June | 398.00 | 0.61 | 0.60 | 01-JUN-05:00 | 649.91 | 20.42 | 82.83 | 384.33 | 274.53 | 20.93 | 76.83 | 347.83 |
July | 400.17 | 0.61 | 0.60 | 01-JUL-05:49 | 620.53 | 18.61 | 39.33 | 395.67 | 292.41 | 21.45 | 78.33 | 323.17 |
August | 377.83 | 0.62 | 0.60 | 01-AUG-05:00 | 511.22 | 16.84 | 0.00 | 367.67 | 242.84 | 20.10 | 26.17 | 279.17 |
September | 365.83 | 0.65 | 0.60 | 01-SEP-14:20 | 377.61 | 15.82 | 0.00 | 317.67 | 190.57 | 19.13 | 0.00 | 140.33 |
October | 318.83 | 0.66 | 0.60 | 01-OCT-14:50 | 337.61 | 15.04 | 0.00 | 284.67 | 173.22 | 18.47 | 0.00 | 75.17 |
November | 295.83 | 0.68 | 0.60 | 01-NOV-13:09 | 269.97 | 14.03 | 0.00 | 230.33 | 143.33 | 17.64 | 0.00 | 14.50 |
December | 289.50 | 0.68 | 0.60 | 01-DEC-09:50 | 289.86 | 14.04 | 0.00 | 231.00 | 150.74 | 17.64 | 0.00 | 26.33 |
Annual Sum or Average | 4125.67 | 0.64 | 442.92 | 16.32 | 127.50 | 3705.00 | 210.63 | 19.37 | 264.00 | 1995.83 | ||
Minimum of Months | 268.33 | 0.61 | 0.60 | 269.97 | 14.00 | 0.00 | 221.33 | 143.33 | 17.64 | 0.00 | 14.50 | |
Maximum of Months | 408.83 | 0.68 | 0.60 | 649.91 | 20.42 | 82.83 | 395.67 | 292.41 | 21.45 | 78.33 | 350.33 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.876383E+11 | 116698.06 | 21-JAN-23:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.596001E+11 | 113566.89 | 01-FEB-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.565997E+11 | 108967.21 | 13-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196544E+11 | 108440.87 | 13-APR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141257E+10 | 58727.38 | 02-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.214112E+10 | 73253.51 | 30-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174125E+11 | 97737.56 | 25-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.569397E+11 | 119842.52 | 21-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.672895E+11 | 115159.93 | 24-DEC-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.368688E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.876383E+11 | 119842.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.401853E+09 | 2727.39 | 13-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 92058110.94 | 2836.72 | 01-APR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 835084.69 | 1733.97 | 01-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.494746E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.401853E+09 | 2836.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.391023E+09 | 1130.32 | 27-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.223660E+09 | 1063.71 | 02-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162574E+09 | 1036.16 | 02-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13821858.53 | 453.41 | 12-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 245463.19 | 201.54 | 14-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187951E+09 | 1068.59 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.527308E+09 | 1577.09 | 27-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.150658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.527308E+09 | 1577.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 30864079.84 | 407.03 | 28-JAN-11:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17017120.77 | 405.67 | 03-FEB-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8404846.34 | 366.39 | 02-MAR-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11746961.03 | 344.52 | 28-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121012E+09 | 533.59 | 27-DEC-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.121012E+09 | 533.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 40841642.47 | 265.21 | 28-JAN-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20517288.18 | 227.28 | 03-FEB-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9388531.79 | 238.22 | 02-MAR-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14993091.15 | 219.79 | 28-NOV-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118657E+09 | 332.37 | 27-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204397E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.118657E+09 | 332.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 11662175.02 | 654.57 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5876620.76 | 428.78 | 03-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1544924.69 | 428.65 | 02-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5091107.51 | 649.85 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23017764.02 | 831.82 | 27-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47192592.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23017764.02 | 831.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 37143305.00 | 1672.14 | 15-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6332156.73 | 592.59 | 13-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 342886.81 | 430.08 | 24-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 24304414.01 | 1634.94 | 27-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28113416.71 | 2179.84 | 26-DEC-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96236179.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37143305.00 | 2179.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.441549E+09 | 3412.51 | 27-JAN-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 46587410.46 | 2762.75 | 03-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 39526165.51 | 2232.56 | 02-MAR-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146843E+09 | 2400.60 | 28-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.858338E+09 | 4592.41 | 27-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.858338E+09 | 4592.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106704E+10 | 2861.25 | 27-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.503099E+09 | 3004.88 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.235162E+09 | 2643.82 | 02-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.393919E+09 | 2259.19 | 28-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168148E+10 | 3437.28 | 27-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.388069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.168148E+10 | 3437.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 28433854.80 | 1323.39 | 27-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 49880578.71 | 1786.39 | 03-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15237317.16 | 1131.66 | 02-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19055.34 | 0.30 | 29-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18267.15 | 0.30 | 24-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15420.29 | 0.30 | 28-JUN-01:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 18069.78 | 0.30 | 01-JUL-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14409.20 | 0.30 | 22-AUG-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15520.91 | 0.30 | 04-SEP-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10850.97 | 0.30 | 02-OCT-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5541.32 | 0.30 | 13-NOV-16:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 91449007.75 | 1329.67 | 27-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5541.32 | 0.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 91449007.75 | 1786.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115586E+10 | 8442.12 | 27-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.686847E+09 | 8390.12 | 02-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.337621E+09 | 8422.19 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27079895.64 | 3988.61 | 01-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6575308.37 | 4218.05 | 26-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4372781.51 | 3607.43 | 28-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4917143.32 | 3735.67 | 19-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6335041.79 | 3848.60 | 30-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6911726.11 | 3860.27 | 26-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10842926.63 | 3870.99 | 06-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.508738E+09 | 8366.32 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157888E+10 | 8538.07 | 27-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.433498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4372781.51 | 3607.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.157888E+10 | 8538.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.207987E+10 | 8584.23 | 27-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122728E+10 | 8523.38 | 02-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.519369E+09 | 8464.45 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32434406.32 | 4695.95 | 02-APR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5285266.39 | 5212.23 | 08-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2607552.95 | 4308.92 | 11-JUN-08:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2041203.90 | 2971.96 | 29-JUL-06:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3607127.24 | 3746.02 | 19-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4669410.52 | 3685.02 | 27-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12145469.15 | 4385.39 | 22-OCT-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.889449E+09 | 8403.33 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.274441E+10 | 8571.30 | 27-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.752316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2041203.90 | 2971.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.274441E+10 | 8584.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.453298E+10 | 48808.18 | 27-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.254903E+10 | 47016.11 | 02-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.728624E+09 | 36113.37 | 31-MAR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 85720660.30 | 34411.92 | 11-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 47391550.11 | 27863.76 | 16-MAY-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13314606.11 | 17475.10 | 13-JUN-08:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13959316.20 | 15010.87 | 25-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33177932.75 | 15586.42 | 17-AUG-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45649741.16 | 23959.93 | 29-SEP-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 56527996.75 | 33908.54 | 20-OCT-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160464E+10 | 38073.82 | 30-NOV-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.715820E+10 | 48732.46 | 27-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 13314606.11 | 15010.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.715820E+10 | 48808.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.124259E+10 | 7966.60 | 14-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.660087E+09 | 4230.96 | 10-FEB-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.360970E+09 | 7164.34 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 26176222.36 | 4139.44 | 12-APR-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 859402.48 | 2686.36 | 01-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 259666.05 | 2596.66 | 29-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 56815.65 | 405.90 | 19-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1538806.82 | 3875.65 | 16-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 900769.45 | 2705.88 | 24-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10629607.46 | 3442.18 | 07-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.571367E+09 | 8091.95 | 27-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161783E+10 | 8242.18 | 26-DEC-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.449327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 56815.65 | 405.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161783E+10 | 8242.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.214663E+10 | 8055.64 | 26-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110425E+10 | 7998.37 | 01-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.543143E+09 | 8155.98 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33825044.95 | 4319.42 | 11-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2153166.50 | 3371.00 | 04-MAY-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 165120.76 | 2309.71 | 22-JUN-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 479898.40 | 1554.71 | 19-JUL-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1381620.77 | 3342.15 | 17-AUG-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1248337.21 | 2672.15 | 24-SEP-21:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22140912.46 | 3575.59 | 07-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.946278E+09 | 8104.91 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271262E+10 | 8243.39 | 26-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.751432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 165120.76 | 1554.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.271262E+10 | 8243.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.554714E+09 | 2617.56 | 27-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.361895E+09 | 2603.23 | 02-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.217676E+09 | 2607.83 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31042348.07 | 2034.65 | 11-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2227810.96 | 988.03 | 06-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1168303.65 | 857.17 | 30-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1369439.32 | 924.23 | 05-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1665213.57 | 924.69 | 31-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1951549.65 | 922.51 | 16-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14179123.79 | 945.33 | 07-OCT-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.293028E+09 | 2589.36 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.708295E+09 | 2627.65 | 27-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1168303.65 | 857.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.708295E+09 | 2627.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.884080E+09 | 2625.43 | 27-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.561380E+09 | 2615.14 | 10-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.290451E+09 | 2610.00 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32213655.60 | 2234.62 | 11-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1735280.56 | 1149.34 | 08-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 850540.11 | 1029.83 | 14-JUN-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 545008.34 | 773.80 | 31-JUL-08:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1073080.09 | 972.55 | 26-AUG-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1382578.71 | 1202.98 | 12-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19423830.47 | 972.78 | 23-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.468967E+09 | 2589.66 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109904E+10 | 2621.58 | 27-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.336114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 545008.34 | 773.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109904E+10 | 2625.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.808641E+09 | 11739.85 | 15-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.522926E+09 | 5509.27 | 25-FEB-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.381842E+09 | 10221.31 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 67557391.61 | 6110.15 | 11-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11166886.97 | 4968.56 | 15-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7115152.46 | 4900.78 | 13-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5244735.53 | 4078.01 | 11-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5723201.88 | 4094.08 | 16-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1325345.35 | 2230.95 | 27-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6837874.73 | 4129.05 | 07-OCT-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.451069E+09 | 11962.62 | 27-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114724E+10 | 12136.22 | 26-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.341669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1325345.35 | 2230.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114724E+10 | 12136.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.502956E+11 | 0.502956E+11 | 43581.40 | 30-JAN-07:05 | 43581.40 | 0.00 |
February | 0.00 | 0.00 | 0.458969E+11 | 0.458969E+11 | 45186.83 | 01-FEB-05:07 | 45186.83 | 0.00 |
March | 0.00 | 0.00 | 0.494518E+11 | 0.494518E+11 | 47237.07 | 01-MAR-07:30 | 47237.07 | 0.00 |
April | 0.00 | 0.00 | 0.459433E+11 | 0.459433E+11 | 53772.39 | 01-APR-08:00 | 53772.39 | 0.00 |
May | 0.00 | 0.00 | 0.442101E+11 | 0.442101E+11 | 58111.34 | 01-MAY-06:15 | 58111.34 | 0.00 |
June | 0.00 | 0.00 | 0.396586E+11 | 0.396547E+11 | 61225.74 | 01-JUN-07:35 | 61225.74 | 0.00 |
July | 0.00 | 0.00 | 0.392089E+11 | 0.342467E+11 | 63296.29 | 01-JUL-10:33 | 55159.47 | 0.00 |
August | 0.00 | 0.00 | 0.389474E+11 | 0.375776E+11 | 61292.36 | 31-AUG-06:20 | 59007.14 | 0.00 |
September | 0.00 | 0.00 | 0.394971E+11 | 0.367175E+11 | 59716.61 | 30-SEP-05:08 | 55264.66 | 0.00 |
October | 0.00 | 0.00 | 0.437077E+11 | 0.437077E+11 | 55290.69 | 31-OCT-07:45 | 55290.69 | 0.00 |
November | 0.00 | 0.00 | 0.441518E+11 | 0.441518E+11 | 46173.98 | 30-NOV-06:15 | 46173.98 | 0.00 |
December | 0.00 | 0.00 | 0.474867E+11 | 0.474867E+11 | 41309.24 | 31-DEC-02:07 | 41309.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.528456E+12 | 0.519341E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.389474E+11 | 0.342467E+11 | 41309.24 | 41309.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.502956E+11 | 0.502956E+11 | 63296.29 | 61225.74 | 0.00 |
Report: CoilReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.437180E+11 | 0.437180E+11 | 55148.40 | 30-JAN-17:10 | 55148.40 | 0.00 |
February | 0.00 | 0.00 | 0.409484E+11 | 0.409484E+11 | 57181.24 | 01-FEB-18:30 | 57181.24 | 0.00 |
March | 0.00 | 0.00 | 0.471733E+11 | 0.471733E+11 | 59777.34 | 01-MAR-21:10 | 59777.34 | 0.00 |
April | 0.00 | 0.00 | 0.518181E+11 | 0.518181E+11 | 68052.58 | 01-APR-16:10 | 68052.58 | 0.00 |
May | 0.00 | 0.00 | 0.578880E+11 | 0.578880E+11 | 73546.72 | 01-MAY-16:10 | 73546.72 | 0.00 |
June | 0.00 | 0.00 | 0.592106E+11 | 0.592072E+11 | 77490.29 | 01-JUN-16:05 | 77490.29 | 0.00 |
July | 0.00 | 0.00 | 0.634304E+11 | 0.554157E+11 | 80112.09 | 01-JUL-16:10 | 69834.39 | 0.00 |
August | 0.00 | 0.00 | 0.613864E+11 | 0.592475E+11 | 77574.64 | 31-AUG-16:10 | 74705.97 | 0.00 |
September | 0.00 | 0.00 | 0.576147E+11 | 0.535758E+11 | 75579.37 | 30-SEP-16:10 | 69962.71 | 0.00 |
October | 0.00 | 0.00 | 0.549324E+11 | 0.549324E+11 | 69975.11 | 31-OCT-16:30 | 69975.11 | 0.00 |
November | 0.00 | 0.00 | 0.445127E+11 | 0.445127E+11 | 58431.21 | 30-NOV-17:50 | 58431.21 | 0.00 |
December | 0.00 | 0.00 | 0.412914E+11 | 0.412914E+11 | 52271.29 | 31-DEC-17:40 | 52271.29 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.623924E+12 | 0.609728E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.409484E+11 | 0.409484E+11 | 52271.29 | 52271.29 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.634304E+11 | 0.592475E+11 | 80112.09 | 77490.29 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.642902E+10 | 0.642902E+10 | 88484.69 | 03-JAN-17:00 | 88484.69 | 0.00 |
February | 0.00 | 0.00 | 0.327012E+11 | 0.327012E+11 | 122631.28 | 21-FEB-16:17 | 122631.28 | 0.00 |
March | 0.00 | 0.00 | 0.664433E+11 | 0.664433E+11 | 155042.16 | 14-MAR-18:07 | 155042.16 | 0.00 |
April | 0.00 | 0.00 | 0.206560E+12 | 0.206560E+12 | 227985.57 | 19-APR-21:00 | 227985.57 | 0.06 |
May | 0.00 | 0.00 | 0.342895E+12 | 0.341104E+12 | 254803.99 | 19-MAY-20:10 | 254803.99 | 0.33 |
June | 0.00 | 0.00 | 0.444600E+12 | 0.439222E+12 | 300640.42 | 19-JUN-18:03 | 200919.59 | 0.68 |
July | 0.00 | 0.00 | 0.597339E+12 | 0.457876E+12 | 500101.87 | 21-JUL-21:00 | 209032.65 | 1.00 |
August | 0.00 | 0.00 | 0.481229E+12 | 0.427960E+12 | 432043.80 | 01-AUG-20:50 | 201388.58 | 0.97 |
September | 0.00 | 0.00 | 0.393129E+12 | 0.336481E+12 | 325691.67 | 09-SEP-20:10 | 182589.73 | 0.80 |
October | 0.00 | 0.00 | 0.193994E+12 | 0.185120E+12 | 371374.57 | 03-OCT-19:55 | 201861.04 | 0.41 |
November | 0.00 | 0.00 | 0.405207E+11 | 0.405207E+11 | 145211.24 | 03-NOV-15:45 | 145211.24 | 0.02 |
December | 0.00 | 0.00 | 0.373143E+10 | 0.373143E+10 | 49192.85 | 09-DEC-13:00 | 49192.85 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.280957E+13 | 0.254415E+13 | 0.36 | |||
Minimum of Months | 0.00 | 0.00 | 0.373143E+10 | 0.373143E+10 | 49192.85 | 49192.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.597339E+12 | 0.457876E+12 | 500101.87 | 254803.99 | 1.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.424273E+09 | 0.424273E+09 | 11015.35 | 03-JAN-17:00 | 11015.35 | 0.00 |
February | 0.00 | 0.00 | 0.213296E+10 | 0.213296E+10 | 14306.39 | 20-FEB-16:01 | 14306.39 | 0.00 |
March | 0.00 | 0.00 | 0.440437E+10 | 0.440437E+10 | 14861.84 | 22-MAR-15:01 | 14861.84 | 0.00 |
April | 0.00 | 0.00 | 0.144291E+11 | 0.144291E+11 | 17663.28 | 21-APR-15:01 | 17663.28 | 0.05 |
May | 0.00 | 0.00 | 0.237049E+11 | 0.232460E+11 | 20731.76 | 24-MAY-13:00 | 16284.41 | 0.28 |
June | 0.00 | 0.00 | 0.293775E+11 | 0.284061E+11 | 24602.30 | 27-JUN-24:00 | 12152.12 | 0.56 |
July | 0.00 | 0.00 | 0.398593E+11 | 0.299764E+11 | 39000.15 | 21-JUL-08:10 | 13821.69 | 0.79 |
August | 0.00 | 0.00 | 0.333129E+11 | 0.282020E+11 | 33593.25 | 01-AUG-21:51 | 14428.63 | 0.78 |
September | 0.00 | 0.00 | 0.283146E+11 | 0.220359E+11 | 32023.54 | 22-SEP-08:04 | 14826.82 | 0.64 |
October | 0.00 | 0.00 | 0.135551E+11 | 0.123159E+11 | 27870.90 | 03-OCT-20:20 | 14079.23 | 0.32 |
November | 0.00 | 0.00 | 0.268469E+10 | 0.268469E+10 | 14525.56 | 09-NOV-16:02 | 14525.56 | 0.01 |
December | 0.00 | 0.00 | 0.217497E+09 | 0.217497E+09 | 5697.71 | 10-DEC-14:00 | 5697.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.192417E+12 | 0.168475E+12 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 0.217497E+09 | 0.217497E+09 | 5697.71 | 5697.71 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.398593E+11 | 0.299764E+11 | 39000.15 | 17663.28 | 0.79 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.950315E+09 | 0.807515E+09 | 13363.75 | 09-JAN-16:01 | 13363.75 | 0.09 |
February | 0.00 | 0.00 | 0.138591E+10 | 0.136374E+10 | 14194.88 | 20-FEB-16:01 | 14194.88 | 0.02 |
March | 0.00 | 0.00 | 0.253544E+10 | 0.249474E+10 | 14344.35 | 21-MAR-15:01 | 14344.35 | 0.03 |
April | 0.00 | 0.00 | 0.558333E+10 | 0.492586E+10 | 14638.51 | 01-APR-15:01 | 14638.51 | 0.27 |
May | 0.00 | 0.00 | 0.852412E+10 | 0.661682E+10 | 14637.83 | 11-MAY-15:01 | 14637.83 | 0.62 |
June | 0.00 | 0.00 | 0.107044E+11 | 0.788237E+10 | 14632.82 | 14-JUN-08:61 | 14632.82 | 0.88 |
July | 0.00 | 0.00 | 0.112505E+11 | 0.740440E+10 | 16010.52 | 19-JUL-08:61 | 10883.96 | 0.96 |
August | 0.00 | 0.00 | 0.104761E+11 | 0.690032E+10 | 14778.42 | 02-AUG-08:61 | 12264.90 | 0.95 |
September | 0.00 | 0.00 | 0.972482E+10 | 0.649196E+10 | 15118.34 | 09-SEP-08:61 | 11637.98 | 0.93 |
October | 0.00 | 0.00 | 0.652531E+10 | 0.441329E+10 | 14635.53 | 04-OCT-08:61 | 11800.85 | 0.74 |
November | 0.00 | 0.00 | 0.251522E+10 | 0.222653E+10 | 14203.74 | 08-NOV-16:01 | 14203.74 | 0.15 |
December | 0.00 | 0.00 | 0.600530E+09 | 0.568198E+09 | 13417.29 | 23-DEC-16:01 | 13417.29 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.707760E+11 | 0.520958E+11 | 0.48 | |||
Minimum of Months | 0.00 | 0.00 | 0.600530E+09 | 0.568198E+09 | 13363.75 | 10883.96 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.112505E+11 | 0.788237E+10 | 16010.52 | 14638.51 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.168576E+09 | 0.140748E+09 | 13110.18 | 04-JAN-16:01 | 13110.18 | 0.02 |
February | 0.00 | 0.00 | 0.267424E+09 | 0.262020E+09 | 14080.15 | 20-FEB-16:01 | 14080.15 | 0.01 |
March | 0.00 | 0.00 | 0.879893E+09 | 0.855620E+09 | 14228.91 | 21-MAR-15:01 | 14228.91 | 0.02 |
April | 0.00 | 0.00 | 0.412449E+10 | 0.355168E+10 | 15422.04 | 17-APR-18:01 | 15422.04 | 0.23 |
May | 0.00 | 0.00 | 0.772159E+10 | 0.603340E+10 | 15666.76 | 28-MAY-08:51 | 12188.09 | 0.56 |
June | 0.00 | 0.00 | 0.103009E+11 | 0.775829E+10 | 16368.79 | 04-JUN-08:51 | 12667.14 | 0.80 |
July | 0.00 | 0.00 | 0.106455E+11 | 0.721716E+10 | 18002.70 | 22-JUL-08:31 | 11892.52 | 0.85 |
August | 0.00 | 0.00 | 0.928664E+10 | 0.620537E+10 | 17695.42 | 03-AUG-08:61 | 12512.02 | 0.82 |
September | 0.00 | 0.00 | 0.740939E+10 | 0.477160E+10 | 17034.35 | 03-SEP-08:51 | 11844.98 | 0.74 |
October | 0.00 | 0.00 | 0.350047E+10 | 0.200180E+10 | 15356.28 | 05-OCT-08:51 | 12201.54 | 0.54 |
November | 0.00 | 0.00 | 0.627700E+09 | 0.492854E+09 | 14090.46 | 08-NOV-16:01 | 14090.46 | 0.08 |
December | 0.00 | 0.00 | 78581646.84 | 73402767.72 | 13121.43 | 16-DEC-16:01 | 13121.43 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.550112E+11 | 0.393640E+11 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 78581646.84 | 73402767.72 | 13110.18 | 11844.98 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.106455E+11 | 0.775829E+10 | 18002.70 | 15422.04 | 0.85 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.227076E+11 | 0.226374E+11 | 42456.75 | 12-JAN-14:25 | 42456.75 | 0.00 |
February | 0.00 | 0.00 | 0.226305E+11 | 0.223738E+11 | 39783.78 | 07-FEB-13:40 | 39783.78 | 0.02 |
March | 0.00 | 0.00 | 0.210716E+11 | 0.210528E+11 | 31212.62 | 07-MAR-13:40 | 31212.62 | 0.00 |
April | 0.00 | 0.00 | 0.281599E+11 | 0.235914E+11 | 29280.10 | 03-APR-14:00 | 24416.03 | 0.25 |
May | 0.00 | 0.00 | 0.340279E+11 | 0.182197E+11 | 24989.86 | 31-MAY-20:20 | 16128.13 | 0.80 |
June | 0.00 | 0.00 | 0.421831E+11 | 0.217539E+11 | 28482.64 | 15-JUN-17:17 | 23225.19 | 0.99 |
July | 0.00 | 0.00 | 0.456093E+11 | 0.225371E+11 | 29906.71 | 26-JUL-16:20 | 20976.45 | 1.00 |
August | 0.00 | 0.00 | 0.471949E+11 | 0.252011E+11 | 33429.83 | 27-AUG-13:40 | 28025.81 | 1.00 |
September | 0.00 | 0.00 | 0.524454E+11 | 0.331054E+11 | 42065.32 | 19-SEP-13:30 | 30751.13 | 0.98 |
October | 0.00 | 0.00 | 0.473289E+11 | 0.342970E+11 | 48209.15 | 22-OCT-13:15 | 38999.12 | 0.74 |
November | 0.00 | 0.00 | 0.339552E+11 | 0.319717E+11 | 45343.00 | 09-NOV-13:50 | 45343.00 | 0.14 |
December | 0.00 | 0.00 | 0.198136E+11 | 0.198136E+11 | 36523.58 | 16-DEC-13:40 | 36523.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.417128E+12 | 0.296555E+12 | 0.50 | |||
Minimum of Months | 0.00 | 0.00 | 0.198136E+11 | 0.182197E+11 | 24989.86 | 16128.13 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.524454E+11 | 0.342970E+11 | 48209.15 | 45343.00 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.282604E+10 | 0.254623E+10 | 76019.25 | 03-JAN-16:01 | 76019.25 | 0.04 |
February | 0.00 | 0.00 | 0.551905E+10 | 0.511090E+10 | 83362.78 | 20-FEB-16:01 | 83362.78 | 0.05 |
March | 0.00 | 0.00 | 0.114758E+11 | 0.111147E+11 | 86300.14 | 22-MAR-15:01 | 86300.14 | 0.03 |
April | 0.00 | 0.00 | 0.286107E+11 | 0.261203E+11 | 89723.59 | 21-APR-18:01 | 89723.59 | 0.15 |
May | 0.00 | 0.00 | 0.480497E+11 | 0.388085E+11 | 91718.65 | 20-MAY-08:51 | 91718.65 | 0.45 |
June | 0.00 | 0.00 | 0.636494E+11 | 0.486979E+11 | 94153.54 | 16-JUN-07:21 | 94153.54 | 0.70 |
July | 0.00 | 0.00 | 0.693453E+11 | 0.465661E+11 | 105306.90 | 22-JUL-08:31 | 72857.89 | 0.81 |
August | 0.00 | 0.00 | 0.589842E+11 | 0.385546E+11 | 102467.25 | 03-AUG-08:61 | 77407.87 | 0.75 |
September | 0.00 | 0.00 | 0.449438E+11 | 0.284537E+11 | 99493.69 | 03-SEP-08:51 | 72072.09 | 0.64 |
October | 0.00 | 0.00 | 0.271272E+11 | 0.180339E+11 | 93584.44 | 03-OCT-21:51 | 70888.68 | 0.42 |
November | 0.00 | 0.00 | 0.716806E+10 | 0.598611E+10 | 84472.85 | 09-NOV-16:02 | 84472.85 | 0.11 |
December | 0.00 | 0.00 | 0.195537E+10 | 0.187496E+10 | 75215.34 | 09-DEC-09:02 | 75215.34 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.369655E+12 | 0.271868E+12 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 0.195537E+10 | 0.187496E+10 | 75215.34 | 70888.68 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.693453E+11 | 0.486979E+11 | 105306.90 | 94153.54 | 0.81 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.849987E+09 | 0.712731E+09 | 11706.13 | 10-JAN-16:01 | 11706.13 | 0.10 |
February | 0.00 | 0.00 | 0.158609E+10 | 0.152734E+10 | 12452.64 | 20-FEB-16:01 | 12452.64 | 0.04 |
March | 0.00 | 0.00 | 0.260622E+10 | 0.255810E+10 | 12584.42 | 21-MAR-15:01 | 12584.42 | 0.04 |
April | 0.00 | 0.00 | 0.589031E+10 | 0.523721E+10 | 12838.27 | 03-APR-15:01 | 12838.27 | 0.28 |
May | 0.00 | 0.00 | 0.873098E+10 | 0.686550E+10 | 12839.92 | 11-MAY-15:01 | 12839.92 | 0.63 |
June | 0.00 | 0.00 | 0.110204E+11 | 0.828937E+10 | 12834.84 | 14-JUN-08:61 | 12834.84 | 0.90 |
July | 0.00 | 0.00 | 0.115541E+11 | 0.778692E+10 | 14105.14 | 19-JUL-08:61 | 9519.15 | 0.98 |
August | 0.00 | 0.00 | 0.107271E+11 | 0.723006E+10 | 12472.70 | 14-AUG-08:62 | 9791.12 | 0.97 |
September | 0.00 | 0.00 | 0.979269E+10 | 0.658785E+10 | 12534.48 | 22-SEP-08:61 | 10883.00 | 0.95 |
October | 0.00 | 0.00 | 0.608615E+10 | 0.409383E+10 | 13294.93 | 14-OCT-15:01 | 9812.56 | 0.75 |
November | 0.00 | 0.00 | 0.241170E+10 | 0.215730E+10 | 12459.41 | 08-NOV-16:01 | 12459.41 | 0.15 |
December | 0.00 | 0.00 | 0.625983E+09 | 0.556050E+09 | 11766.92 | 23-DEC-16:01 | 11766.92 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.718818E+11 | 0.536023E+11 | 0.49 | |||
Minimum of Months | 0.00 | 0.00 | 0.625983E+09 | 0.556050E+09 | 11706.13 | 9519.15 | 0.04 | |
Maximum of Months | 0.00 | 0.00 | 0.115541E+11 | 0.828937E+10 | 14105.14 | 12839.92 | 0.98 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.111179E+09 | 74422192.90 | 11119.02 | 31-JAN-09:01 | 11119.02 | 0.03 |
February | 0.00 | 0.00 | 0.450143E+09 | 0.409359E+09 | 12359.21 | 20-FEB-16:01 | 12359.21 | 0.03 |
March | 0.00 | 0.00 | 0.112935E+10 | 0.110283E+10 | 12490.00 | 21-MAR-15:01 | 12490.00 | 0.02 |
April | 0.00 | 0.00 | 0.440325E+10 | 0.385332E+10 | 14060.04 | 21-APR-08:51 | 14060.04 | 0.24 |
May | 0.00 | 0.00 | 0.766170E+10 | 0.592730E+10 | 14710.64 | 20-MAY-08:51 | 14710.64 | 0.58 |
June | 0.00 | 0.00 | 0.104140E+11 | 0.792076E+10 | 16226.27 | 14-JUN-07:52 | 16226.27 | 0.82 |
July | 0.00 | 0.00 | 0.107838E+11 | 0.739686E+10 | 16603.99 | 04-JUL-08:62 | 13668.34 | 0.87 |
August | 0.00 | 0.00 | 0.935768E+10 | 0.626396E+10 | 15768.62 | 03-AUG-08:61 | 12184.37 | 0.84 |
September | 0.00 | 0.00 | 0.727271E+10 | 0.461884E+10 | 15779.61 | 23-SEP-08:51 | 11928.18 | 0.76 |
October | 0.00 | 0.00 | 0.329742E+10 | 0.197505E+10 | 14572.63 | 05-OCT-08:51 | 12665.89 | 0.56 |
November | 0.00 | 0.00 | 0.633563E+09 | 0.527619E+09 | 12574.69 | 09-NOV-09:51 | 12574.69 | 0.08 |
December | 0.00 | 0.00 | 74770543.92 | 59019809.51 | 11320.54 | 16-DEC-09:01 | 11320.54 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.555895E+11 | 0.401293E+11 | 0.41 | |||
Minimum of Months | 0.00 | 0.00 | 74770543.92 | 59019809.51 | 11119.02 | 11119.02 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.107838E+11 | 0.792076E+10 | 16603.99 | 16226.27 | 0.87 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.190740E+09 | 0.163089E+09 | 3578.14 | 09-JAN-16:01 | 3578.14 | 0.06 |
February | 0.00 | 0.00 | 0.297413E+09 | 0.293596E+09 | 3800.64 | 20-FEB-16:01 | 3800.64 | 0.01 |
March | 0.00 | 0.00 | 0.564324E+09 | 0.556135E+09 | 3840.57 | 21-MAR-15:01 | 3840.57 | 0.02 |
April | 0.00 | 0.00 | 0.136084E+10 | 0.119467E+10 | 3918.50 | 03-APR-15:01 | 3918.50 | 0.26 |
May | 0.00 | 0.00 | 0.213556E+10 | 0.163645E+10 | 3977.57 | 28-MAY-08:61 | 3181.45 | 0.62 |
June | 0.00 | 0.00 | 0.278761E+10 | 0.203591E+10 | 3919.42 | 04-JUN-08:61 | 3307.03 | 0.88 |
July | 0.00 | 0.00 | 0.293012E+10 | 0.191087E+10 | 4532.23 | 19-JUL-08:61 | 2707.87 | 0.96 |
August | 0.00 | 0.00 | 0.268595E+10 | 0.175510E+10 | 4116.49 | 02-AUG-08:61 | 3188.24 | 0.95 |
September | 0.00 | 0.00 | 0.241083E+10 | 0.158140E+10 | 4244.61 | 09-SEP-08:61 | 2996.24 | 0.92 |
October | 0.00 | 0.00 | 0.149306E+10 | 0.997762E+09 | 4088.97 | 04-OCT-08:61 | 2950.73 | 0.68 |
November | 0.00 | 0.00 | 0.515712E+09 | 0.455612E+09 | 3802.81 | 08-NOV-16:01 | 3802.81 | 0.12 |
December | 0.00 | 0.00 | 0.120803E+09 | 0.113629E+09 | 3592.40 | 23-DEC-16:01 | 3592.40 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.174930E+11 | 0.126942E+11 | 0.46 | |||
Minimum of Months | 0.00 | 0.00 | 0.120803E+09 | 0.113629E+09 | 3578.14 | 2707.87 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.293012E+10 | 0.203591E+10 | 4532.23 | 3918.50 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 29510887.60 | 23028262.38 | 3419.26 | 30-JAN-16:01 | 3419.26 | 0.01 |
February | 0.00 | 0.00 | 44993977.33 | 43812721.50 | 3766.22 | 20-FEB-16:01 | 3766.22 | 0.00 |
March | 0.00 | 0.00 | 0.166859E+09 | 0.162859E+09 | 3806.14 | 21-MAR-15:01 | 3806.14 | 0.01 |
April | 0.00 | 0.00 | 0.101117E+10 | 0.867036E+09 | 4124.63 | 17-APR-18:01 | 4124.63 | 0.23 |
May | 0.00 | 0.00 | 0.196770E+10 | 0.152020E+10 | 4197.87 | 28-MAY-08:51 | 3217.03 | 0.56 |
June | 0.00 | 0.00 | 0.271879E+10 | 0.204080E+10 | 4411.59 | 04-JUN-08:51 | 3367.98 | 0.80 |
July | 0.00 | 0.00 | 0.280875E+10 | 0.189956E+10 | 4902.63 | 22-JUL-08:31 | 3124.26 | 0.86 |
August | 0.00 | 0.00 | 0.241775E+10 | 0.160475E+10 | 4809.30 | 03-AUG-08:61 | 3246.10 | 0.82 |
September | 0.00 | 0.00 | 0.185869E+10 | 0.117892E+10 | 4642.89 | 03-SEP-08:51 | 3080.42 | 0.74 |
October | 0.00 | 0.00 | 0.750572E+09 | 0.423879E+09 | 4161.07 | 05-OCT-08:51 | 3171.05 | 0.48 |
November | 0.00 | 0.00 | 94928695.89 | 71387226.96 | 3715.22 | 07-NOV-16:01 | 3715.22 | 0.05 |
December | 0.00 | 0.00 | 13517306.43 | 12385036.40 | 3509.75 | 16-DEC-16:01 | 3509.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.138832E+11 | 0.984862E+10 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 13517306.43 | 12385036.40 | 3419.26 | 3080.42 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.280875E+10 | 0.204080E+10 | 4902.63 | 4124.63 | 0.86 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.498352E+10 | 0.455005E+10 | 15749.82 | 09-JAN-16:01 | 15749.82 | 0.19 |
February | 0.00 | 0.00 | 0.491816E+10 | 0.479998E+10 | 16728.84 | 20-FEB-16:01 | 16728.84 | 0.07 |
March | 0.00 | 0.00 | 0.482509E+10 | 0.472469E+10 | 16904.50 | 21-MAR-15:01 | 16904.50 | 0.04 |
April | 0.00 | 0.00 | 0.705511E+10 | 0.613025E+10 | 17244.12 | 04-APR-15:01 | 17244.12 | 0.30 |
May | 0.00 | 0.00 | 0.926213E+10 | 0.667045E+10 | 17175.80 | 28-MAY-08:61 | 14253.45 | 0.64 |
June | 0.00 | 0.00 | 0.120760E+11 | 0.831266E+10 | 17243.54 | 16-JUN-08:61 | 17243.54 | 0.88 |
July | 0.00 | 0.00 | 0.135468E+11 | 0.843069E+10 | 20496.55 | 20-JUL-08:61 | 12420.28 | 0.96 |
August | 0.00 | 0.00 | 0.133683E+11 | 0.870832E+10 | 18195.05 | 02-AUG-08:61 | 14055.16 | 0.95 |
September | 0.00 | 0.00 | 0.137074E+11 | 0.936490E+10 | 18577.72 | 09-SEP-08:61 | 13330.66 | 0.93 |
October | 0.00 | 0.00 | 0.113432E+11 | 0.842885E+10 | 17563.46 | 04-OCT-08:61 | 13688.70 | 0.76 |
November | 0.00 | 0.00 | 0.725445E+10 | 0.677446E+10 | 16405.13 | 14-NOV-16:01 | 16405.13 | 0.20 |
December | 0.00 | 0.00 | 0.454817E+10 | 0.430954E+10 | 15812.55 | 23-DEC-16:01 | 15812.55 | 0.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.106888E+12 | 0.812048E+11 | 0.51 | |||
Minimum of Months | 0.00 | 0.00 | 0.454817E+10 | 0.430954E+10 | 15749.82 | 12420.28 | 0.04 | |
Maximum of Months | 0.00 | 0.00 | 0.137074E+11 | 0.936490E+10 | 20496.55 | 17244.12 | 0.96 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 38135.24 | 150175.38 | 26-JAN-16:01 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 27910.95 | 145300.30 | 09-FEB-19:03 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 22515.10 | 135700.87 | 27-MAR-08:07 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7686.72 | 131667.01 | 11-APR-08:04 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 558.54 | 58475.74 | 02-MAY-06:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.19 | 17667.94 | 13-JUN-08:35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.43 | 11740.71 | 25-JUL-08:06 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.06 | 12566.14 | 22-AUG-08:55 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 833.62 | 73403.30 | 30-SEP-06:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 6501.64 | 103294.89 | 24-OCT-08:05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 24262.65 | 150220.72 | 28-NOV-16:01 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 33105.79 | 156849.00 | 20-DEC-09:01 |
Annual Sum or Average | 0.00 | 13401.93 | ||||
Minimum of Months | 0.00 | 0.00 | 11.43 | 11740.71 | ||
Maximum of Months | 0.00 | 0.00 | 38135.24 | 156849.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 17606.09 | 244822.47 | 03-JAN-16:01 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 32831.57 | 321945.89 | 22-FEB-16:01 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 46628.36 | 336522.59 | 22-MAR-15:01 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 121958.26 | 391456.88 | 21-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 188208.84 | 430927.10 | 19-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 250446.67 | 521594.49 | 05-JUN-18:07 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 308106.64 | 636939.56 | 20-JUL-21:53 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 257105.88 | 594505.08 | 01-AUG-21:51 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 223852.56 | 469834.43 | 03-SEP-21:52 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 121086.14 | 493955.64 | 04-OCT-18:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 41027.44 | 344852.79 | 03-NOV-15:01 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 14664.96 | 180335.83 | 10-DEC-16:02 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 135872.46 | 0.00 | ||||
Minimum of Months | 14664.96 | 180335.83 | 0.00 | 0.00 | ||
Maximum of Months | 308106.64 | 636939.56 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 24471.98 | 51477.51 | 27-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 24450.33 | 51443.25 | 01-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 23591.37 | 50397.12 | 01-MAR-07:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22037.60 | 47437.99 | 03-APR-06:40 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20258.33 | 44057.59 | 01-MAY-06:30 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18718.50 | 40366.24 | 01-JUN-06:55 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 17811.27 | 37641.62 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17837.37 | 37795.25 | 31-AUG-06:50 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18731.72 | 40320.87 | 29-SEP-06:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 20276.40 | 44120.23 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 22060.48 | 47768.04 | 30-NOV-07:40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 23595.42 | 50333.00 | 29-DEC-07:30 |
Annual Sum or Average | 0.00 | 21134.70 | ||||
Minimum of Months | 0.00 | 0.00 | 17811.27 | 37641.62 | ||
Maximum of Months | 0.00 | 0.00 | 24471.98 | 51477.51 |
Report: FanReportMonthly
For: SWHSYS1 HPWH FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.670164E+09 | 0.07 | 553.22 | 01-JAN-06:15 | 0.11 |
February | 0.591202E+09 | 0.07 | 553.22 | 01-FEB-05:07 | 0.12 |
March | 0.615174E+09 | 0.07 | 553.22 | 01-MAR-05:07 | 0.12 |
April | 0.510618E+09 | 0.06 | 553.22 | 01-APR-05:17 | 0.11 |
May | 0.461474E+09 | 0.06 | 553.22 | 01-MAY-06:15 | 0.11 |
June | 0.398525E+09 | 0.06 | 553.22 | 01-JUN-05:17 | 0.11 |
July | 0.382912E+09 | 0.06 | 553.22 | 01-JUL-07:15 | 0.11 |
August | 0.392398E+09 | 0.06 | 553.22 | 01-AUG-04:10 | 0.11 |
September | 0.405623E+09 | 0.06 | 553.22 | 01-SEP-05:17 | 0.11 |
October | 0.477236E+09 | 0.06 | 553.22 | 01-OCT-05:07 | 0.11 |
November | 0.566265E+09 | 0.07 | 553.22 | 01-NOV-04:07 | 0.11 |
December | 0.670850E+09 | 0.07 | 553.22 | 01-DEC-06:15 | 0.12 |
Annual Sum or Average | 0.614244E+10 | 0.06 | |||
Minimum of Months | 0.382912E+09 | 0.06 | 553.22 | 0.11 | |
Maximum of Months | 0.670850E+09 | 0.07 | 553.22 | 0.12 |
Report: FanReportMonthly
For: SWHSYSLAUNDRY HPWH FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.558299E+09 | 0.07 | 700.51 | 01-JAN-17:10 | 0.11 |
February | 0.504438E+09 | 0.06 | 700.51 | 01-FEB-17:10 | 0.12 |
March | 0.558166E+09 | 0.06 | 700.51 | 01-MAR-17:10 | 0.12 |
April | 0.539867E+09 | 0.06 | 700.51 | 01-APR-16:10 | 0.11 |
May | 0.558653E+09 | 0.06 | 700.51 | 01-MAY-16:10 | 0.11 |
June | 0.541189E+09 | 0.06 | 700.51 | 01-JUN-16:05 | 0.11 |
July | 0.558485E+09 | 0.06 | 700.51 | 01-JUL-16:10 | 0.11 |
August | 0.558191E+09 | 0.06 | 700.51 | 01-AUG-16:10 | 0.11 |
September | 0.539844E+09 | 0.06 | 700.51 | 01-SEP-16:10 | 0.11 |
October | 0.557077E+09 | 0.06 | 700.51 | 01-OCT-16:10 | 0.11 |
November | 0.540235E+09 | 0.06 | 700.51 | 01-NOV-16:10 | 0.11 |
December | 0.558889E+09 | 0.07 | 700.51 | 01-DEC-17:10 | 0.12 |
Annual Sum or Average | 0.657333E+10 | 0.06 | |||
Minimum of Months | 0.504438E+09 | 0.06 | 700.51 | 0.11 | |
Maximum of Months | 0.558889E+09 | 0.07 | 700.51 | 0.12 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.80 | 1299.30 | 01-JAN-16:13 | 1.01 |
February | 0.244774E+10 | 0.80 | 1299.30 | 03-FEB-16:07 | 1.02 |
March | 0.271000E+10 | 0.80 | 1299.30 | 01-MAR-16:03 | 1.01 |
April | 0.262258E+10 | 0.80 | 1299.30 | 02-APR-15:07 | 1.01 |
May | 0.271000E+10 | 0.80 | 1299.30 | 01-MAY-15:06 | 1.01 |
June | 0.262258E+10 | 0.80 | 1299.30 | 01-JUN-16:35 | 1.01 |
July | 0.271000E+10 | 0.79 | 1299.30 | 01-JUL-18:07 | 1.00 |
August | 0.271000E+10 | 0.79 | 1299.30 | 01-AUG-15:08 | 1.00 |
September | 0.262258E+10 | 0.79 | 1299.30 | 01-SEP-15:08 | 1.00 |
October | 0.271000E+10 | 0.80 | 1299.30 | 01-OCT-12:50 | 1.01 |
November | 0.262258E+10 | 0.80 | 1299.30 | 03-NOV-15:07 | 1.00 |
December | 0.271000E+10 | 0.80 | 1299.30 | 01-DEC-10:05 | 1.01 |
Annual Sum or Average | 0.319080E+11 | 0.80 | |||
Minimum of Months | 0.244774E+10 | 0.79 | 1299.30 | 1.00 | |
Maximum of Months | 0.271000E+10 | 0.80 | 1299.30 | 1.02 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.340959E+11 | 0.90 | 23957.85 | 03-JAN-22:10 | 1.31 |
February | 0.314410E+11 | 0.92 | 26303.47 | 06-FEB-22:10 | 1.39 |
March | 0.356202E+11 | 0.93 | 27292.08 | 15-MAR-21:10 | 1.42 |
April | 0.373183E+11 | 0.97 | 31038.50 | 21-APR-21:10 | 1.53 |
May | 0.413245E+11 | 1.00 | 33385.22 | 31-MAY-21:10 | 1.59 |
June | 0.434038E+11 | 1.04 | 36184.57 | 15-JUN-21:10 | 1.68 |
July | 0.444647E+11 | 1.03 | 35638.24 | 26-JUL-21:10 | 1.65 |
August | 0.450283E+11 | 1.04 | 38981.71 | 07-AUG-21:10 | 1.74 |
September | 0.435298E+11 | 1.04 | 39794.06 | 21-SEP-21:20 | 1.77 |
October | 0.417982E+11 | 1.00 | 38725.06 | 05-OCT-21:10 | 1.74 |
November | 0.364877E+11 | 0.95 | 33600.30 | 09-NOV-22:10 | 1.60 |
December | 0.343435E+11 | 0.91 | 25300.76 | 15-DEC-22:10 | 1.36 |
Annual Sum or Average | 0.468856E+12 | 0.98 | |||
Minimum of Months | 0.314410E+11 | 0.90 | 23957.85 | 1.31 | |
Maximum of Months | 0.450283E+11 | 1.04 | 39794.06 | 1.77 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.31 | 76.61 | 01-JAN-00:10 | 0.31 |
February | 0.185347E+09 | 0.31 | 76.61 | 01-FEB-00:05 | 0.31 |
March | 0.205205E+09 | 0.31 | 76.61 | 01-MAR-00:05 | 0.31 |
April | 0.198586E+09 | 0.31 | 76.61 | 01-APR-00:10 | 0.31 |
May | 0.205205E+09 | 0.31 | 76.61 | 01-MAY-00:05 | 0.31 |
June | 0.198586E+09 | 0.30 | 76.61 | 01-JUN-00:05 | 0.31 |
July | 0.205205E+09 | 0.30 | 76.61 | 01-JUL-00:10 | 0.30 |
August | 0.205205E+09 | 0.30 | 76.61 | 01-AUG-00:05 | 0.30 |
September | 0.198586E+09 | 0.30 | 76.61 | 01-SEP-00:05 | 0.30 |
October | 0.205205E+09 | 0.30 | 76.61 | 01-OCT-00:10 | 0.31 |
November | 0.198586E+09 | 0.31 | 76.61 | 01-NOV-00:05 | 0.31 |
December | 0.205205E+09 | 0.31 | 76.61 | 01-DEC-00:05 | 0.31 |
Annual Sum or Average | 0.241613E+10 | 0.31 | |||
Minimum of Months | 0.185347E+09 | 0.30 | 76.61 | 0.30 | |
Maximum of Months | 0.205205E+09 | 0.31 | 76.61 | 0.31 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.22 | 612.92 | 01-JAN-07:10 | 0.31 |
February | 0.105030E+10 | 0.22 | 612.92 | 01-FEB-07:05 | 0.31 |
March | 0.116283E+10 | 0.22 | 612.92 | 01-MAR-07:05 | 0.31 |
April | 0.112532E+10 | 0.22 | 612.92 | 01-APR-06:05 | 0.31 |
May | 0.116283E+10 | 0.22 | 612.92 | 01-MAY-06:05 | 0.31 |
June | 0.112532E+10 | 0.22 | 612.92 | 01-JUN-06:05 | 0.31 |
July | 0.116283E+10 | 0.21 | 612.92 | 01-JUL-06:10 | 0.30 |
August | 0.116283E+10 | 0.21 | 612.92 | 01-AUG-06:10 | 0.30 |
September | 0.112532E+10 | 0.21 | 612.92 | 01-SEP-06:05 | 0.30 |
October | 0.116283E+10 | 0.22 | 612.92 | 01-OCT-06:10 | 0.31 |
November | 0.112532E+10 | 0.22 | 612.92 | 01-NOV-06:05 | 0.30 |
December | 0.116283E+10 | 0.22 | 612.92 | 01-DEC-07:05 | 0.31 |
Annual Sum or Average | 0.136914E+11 | 0.22 | |||
Minimum of Months | 0.105030E+10 | 0.21 | 612.92 | 0.30 | |
Maximum of Months | 0.116283E+10 | 0.22 | 612.92 | 0.31 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157318E+09 | 0.51 | 765.20 | 01-JAN-16:01 | 0.66 |
February | 0.145414E+09 | 0.53 | 765.20 | 01-FEB-09:01 | 0.66 |
March | 0.189115E+09 | 0.55 | 765.20 | 01-MAR-16:01 | 0.66 |
April | 0.320751E+09 | 0.60 | 765.20 | 01-APR-15:01 | 0.66 |
May | 0.465490E+09 | 0.62 | 765.20 | 01-MAY-08:62 | 0.66 |
June | 0.565522E+09 | 0.64 | 765.20 | 01-JUN-08:61 | 0.66 |
July | 0.542766E+09 | 0.64 | 765.20 | 01-JUL-08:62 | 0.66 |
August | 0.517560E+09 | 0.63 | 765.20 | 01-AUG-08:61 | 0.66 |
September | 0.487218E+09 | 0.63 | 765.20 | 01-SEP-08:61 | 0.66 |
October | 0.360099E+09 | 0.60 | 765.20 | 01-OCT-08:61 | 0.66 |
November | 0.197169E+09 | 0.56 | 765.20 | 01-NOV-15:02 | 0.66 |
December | 0.158355E+09 | 0.51 | 765.20 | 01-DEC-16:01 | 0.66 |
Annual Sum or Average | 0.410678E+10 | 0.58 | |||
Minimum of Months | 0.145414E+09 | 0.51 | 765.20 | 0.66 | |
Maximum of Months | 0.565522E+09 | 0.64 | 765.20 | 0.66 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.162900E+09 | 0.46 | 759.03 | 01-JAN-16:01 | 0.66 |
February | 0.112989E+09 | 0.43 | 759.03 | 01-FEB-09:01 | 0.66 |
March | 0.105815E+09 | 0.42 | 759.03 | 01-MAR-09:02 | 0.66 |
April | 0.241044E+09 | 0.48 | 759.03 | 01-APR-15:01 | 0.66 |
May | 0.423273E+09 | 0.53 | 759.03 | 01-MAY-08:51 | 0.66 |
June | 0.552244E+09 | 0.57 | 759.03 | 01-JUN-08:31 | 0.66 |
July | 0.519696E+09 | 0.56 | 759.03 | 01-JUL-08:62 | 0.66 |
August | 0.456165E+09 | 0.54 | 759.03 | 01-AUG-07:51 | 0.66 |
September | 0.366128E+09 | 0.50 | 759.03 | 01-SEP-08:51 | 0.65 |
October | 0.193851E+09 | 0.42 | 759.03 | 01-OCT-08:51 | 0.66 |
November | 0.116330E+09 | 0.45 | 759.03 | 01-NOV-15:02 | 0.66 |
December | 0.189183E+09 | 0.46 | 759.03 | 01-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.343962E+10 | 0.49 | |||
Minimum of Months | 0.105815E+09 | 0.42 | 759.03 | 0.65 | |
Maximum of Months | 0.552244E+09 | 0.57 | 759.03 | 0.66 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.978047E+09 | 0.37 | 2313.89 | 02-JAN-14:00 | 0.66 |
February | 0.960254E+09 | 0.44 | 1776.43 | 07-FEB-13:40 | 0.66 |
March | 0.928887E+09 | 0.46 | 1146.35 | 07-MAR-13:40 | 0.66 |
April | 0.121197E+10 | 0.59 | 1159.31 | 03-APR-13:50 | 0.66 |
May | 0.143475E+10 | 0.65 | 906.65 | 31-MAY-20:20 | 0.66 |
June | 0.167239E+10 | 0.66 | 1133.94 | 15-JUN-17:13 | 0.66 |
July | 0.171676E+10 | 0.66 | 1041.18 | 26-JUL-17:20 | 0.66 |
August | 0.179440E+10 | 0.66 | 1179.42 | 27-AUG-13:50 | 0.66 |
September | 0.200467E+10 | 0.66 | 2031.26 | 19-SEP-13:30 | 0.66 |
October | 0.198768E+10 | 0.63 | 2340.42 | 31-OCT-12:50 | 0.66 |
November | 0.145777E+10 | 0.47 | 2369.82 | 10-NOV-13:10 | 0.66 |
December | 0.855068E+09 | 0.36 | 1369.75 | 17-DEC-13:50 | 0.66 |
Annual Sum or Average | 0.170027E+11 | 0.55 | |||
Minimum of Months | 0.855068E+09 | 0.36 | 906.65 | 0.66 | |
Maximum of Months | 0.200467E+10 | 0.66 | 2369.82 | 0.66 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.633009E+09 | 0.46 | 4628.61 | 01-JAN-09:02 | 0.66 |
February | 0.606458E+09 | 0.42 | 4628.61 | 02-FEB-16:02 | 0.66 |
March | 0.809100E+09 | 0.39 | 4628.61 | 03-MAR-16:01 | 0.66 |
April | 0.163231E+10 | 0.42 | 4628.61 | 01-APR-08:51 | 0.66 |
May | 0.264488E+10 | 0.48 | 4628.61 | 01-MAY-08:51 | 0.67 |
June | 0.334338E+10 | 0.54 | 4628.61 | 01-JUN-08:31 | 0.66 |
July | 0.335075E+10 | 0.53 | 4628.61 | 01-JUL-08:62 | 0.66 |
August | 0.287430E+10 | 0.50 | 4628.61 | 01-AUG-07:51 | 0.66 |
September | 0.223202E+10 | 0.44 | 4628.61 | 01-SEP-08:51 | 0.66 |
October | 0.143883E+10 | 0.37 | 4628.61 | 01-OCT-08:51 | 0.66 |
November | 0.652856E+09 | 0.42 | 4628.61 | 01-NOV-08:62 | 0.66 |
December | 0.740308E+09 | 0.46 | 4628.61 | 01-DEC-19:02 | 0.66 |
Annual Sum or Average | 0.209582E+11 | 0.45 | |||
Minimum of Months | 0.606458E+09 | 0.37 | 4628.61 | 0.66 | |
Maximum of Months | 0.335075E+10 | 0.54 | 4628.61 | 0.67 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.145775E+09 | 0.51 | 670.70 | 01-JAN-09:02 | 0.66 |
February | 0.149847E+09 | 0.55 | 670.70 | 01-FEB-09:01 | 0.66 |
March | 0.190688E+09 | 0.58 | 670.70 | 01-MAR-09:02 | 0.66 |
April | 0.335278E+09 | 0.63 | 670.70 | 01-APR-08:62 | 0.66 |
May | 0.466155E+09 | 0.65 | 670.70 | 01-MAY-08:62 | 0.66 |
June | 0.577909E+09 | 0.65 | 670.70 | 01-JUN-08:61 | 0.66 |
July | 0.560855E+09 | 0.65 | 670.70 | 01-JUL-08:62 | 0.66 |
August | 0.526398E+09 | 0.64 | 670.70 | 01-AUG-08:61 | 0.66 |
September | 0.490305E+09 | 0.64 | 670.70 | 01-SEP-08:61 | 0.66 |
October | 0.332823E+09 | 0.61 | 670.70 | 01-OCT-08:61 | 0.66 |
November | 0.193609E+09 | 0.58 | 670.70 | 01-NOV-15:02 | 0.66 |
December | 0.149454E+09 | 0.49 | 670.70 | 01-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.411910E+10 | 0.60 | |||
Minimum of Months | 0.145775E+09 | 0.49 | 670.70 | 0.66 | |
Maximum of Months | 0.577909E+09 | 0.65 | 670.70 | 0.66 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147855E+09 | 0.46 | 665.66 | 02-JAN-09:02 | 0.66 |
February | 0.106819E+09 | 0.43 | 665.66 | 01-FEB-16:01 | 0.66 |
March | 0.115665E+09 | 0.43 | 665.66 | 01-MAR-09:02 | 0.66 |
April | 0.253840E+09 | 0.52 | 665.66 | 01-APR-08:51 | 0.66 |
May | 0.410585E+09 | 0.55 | 665.66 | 01-MAY-08:51 | 0.66 |
June | 0.549883E+09 | 0.58 | 665.66 | 01-JUN-08:12 | 0.66 |
July | 0.528153E+09 | 0.57 | 665.66 | 01-JUL-08:62 | 0.66 |
August | 0.459724E+09 | 0.55 | 665.66 | 01-AUG-07:51 | 0.66 |
September | 0.358685E+09 | 0.51 | 665.66 | 01-SEP-08:51 | 0.66 |
October | 0.183412E+09 | 0.45 | 665.66 | 01-OCT-08:51 | 0.66 |
November | 0.110581E+09 | 0.43 | 665.66 | 02-NOV-15:01 | 0.66 |
December | 0.169384E+09 | 0.46 | 665.66 | 01-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.339459E+10 | 0.50 | |||
Minimum of Months | 0.106819E+09 | 0.43 | 665.66 | 0.66 | |
Maximum of Months | 0.549883E+09 | 0.58 | 665.66 | 0.66 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 48770684.18 | 0.51 | 204.95 | 01-JAN-16:01 | 0.66 |
February | 43192676.25 | 0.52 | 204.95 | 01-FEB-09:01 | 0.66 |
March | 51084914.39 | 0.54 | 204.95 | 01-MAR-09:02 | 0.66 |
April | 80687822.12 | 0.60 | 204.95 | 01-APR-15:01 | 0.66 |
May | 0.117492E+09 | 0.62 | 204.95 | 01-MAY-15:01 | 0.66 |
June | 0.149134E+09 | 0.64 | 204.95 | 01-JUN-08:61 | 0.66 |
July | 0.143585E+09 | 0.64 | 204.95 | 01-JUL-08:62 | 0.66 |
August | 0.134225E+09 | 0.63 | 204.95 | 01-AUG-08:61 | 0.66 |
September | 0.122414E+09 | 0.63 | 204.95 | 01-SEP-08:61 | 0.66 |
October | 84280031.92 | 0.59 | 204.95 | 01-OCT-08:61 | 0.66 |
November | 52004800.24 | 0.55 | 204.95 | 02-NOV-15:01 | 0.66 |
December | 51353375.21 | 0.50 | 204.95 | 01-DEC-16:01 | 0.66 |
Annual Sum or Average | 0.107822E+10 | 0.58 | |||
Minimum of Months | 43192676.25 | 0.50 | 204.95 | 0.66 | |
Maximum of Months | 0.149134E+09 | 0.64 | 204.95 | 0.66 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 54522848.09 | 0.47 | 203.09 | 01-JAN-16:01 | 0.66 |
February | 38276742.70 | 0.43 | 203.09 | 01-FEB-09:01 | 0.66 |
March | 32035816.64 | 0.42 | 203.09 | 01-MAR-09:02 | 0.66 |
April | 61112111.94 | 0.48 | 203.09 | 01-APR-15:01 | 0.66 |
May | 0.108952E+09 | 0.53 | 203.09 | 01-MAY-08:51 | 0.66 |
June | 0.146846E+09 | 0.57 | 203.09 | 01-JUN-08:31 | 0.66 |
July | 0.138938E+09 | 0.56 | 203.09 | 01-JUL-08:62 | 0.66 |
August | 0.120457E+09 | 0.54 | 203.09 | 01-AUG-07:51 | 0.66 |
September | 92901390.08 | 0.50 | 203.09 | 01-SEP-08:51 | 0.65 |
October | 43299919.95 | 0.42 | 203.09 | 01-OCT-08:51 | 0.66 |
November | 37583482.64 | 0.45 | 203.09 | 02-NOV-15:01 | 0.66 |
December | 62179186.53 | 0.47 | 203.09 | 01-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.937105E+09 | 0.49 | |||
Minimum of Months | 32035816.64 | 0.42 | 203.09 | 0.65 | |
Maximum of Months | 0.146846E+09 | 0.57 | 203.09 | 0.66 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.356777E+09 | 0.58 | 896.09 | 01-JAN-09:02 | 0.66 |
February | 0.321103E+09 | 0.59 | 896.09 | 01-FEB-16:01 | 0.66 |
March | 0.310165E+09 | 0.58 | 896.09 | 01-MAR-16:01 | 0.66 |
April | 0.404180E+09 | 0.61 | 896.09 | 01-APR-08:62 | 0.66 |
May | 0.489232E+09 | 0.62 | 896.09 | 01-MAY-15:01 | 0.66 |
June | 0.608293E+09 | 0.63 | 896.09 | 01-JUN-08:61 | 0.66 |
July | 0.631851E+09 | 0.63 | 896.09 | 01-JUL-08:62 | 0.66 |
August | 0.638104E+09 | 0.63 | 896.09 | 01-AUG-08:61 | 0.66 |
September | 0.687336E+09 | 0.63 | 896.09 | 01-SEP-08:61 | 0.66 |
October | 0.629302E+09 | 0.61 | 896.09 | 01-OCT-08:61 | 0.66 |
November | 0.459609E+09 | 0.59 | 896.09 | 01-NOV-15:02 | 0.66 |
December | 0.344248E+09 | 0.58 | 896.09 | 01-DEC-09:02 | 0.66 |
Annual Sum or Average | 0.588020E+10 | 0.61 | |||
Minimum of Months | 0.310165E+09 | 0.58 | 896.09 | 0.66 | |
Maximum of Months | 0.687336E+09 | 0.63 | 896.09 | 0.66 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.522910E+09 | 0.475326E+09 | 551.19 | 19-JAN-09:03 | 501.03 | 501.03 | 49.04 | 0.82 |
February | 0.342146E+09 | 0.311011E+09 | 573.33 | 05-FEB-09:03 | 521.16 | 521.16 | 52.19 | 0.88 |
March | 0.281850E+09 | 0.256201E+09 | 529.56 | 24-MAR-08:05 | 481.37 | 481.37 | 48.56 | 0.77 |
April | 85829410.74 | 78018934.36 | 507.51 | 11-APR-08:04 | 461.33 | 461.33 | 36.62 | 0.73 |
May | 6556661.26 | 5960005.09 | 240.52 | 02-MAY-06:00 | 218.63 | 218.63 | 29.62 | 0.28 |
June | 343637.52 | 312366.51 | 154.47 | 13-JUN-08:35 | 140.41 | 140.41 | 54.51 | 0.17 |
July | 363978.18 | 330856.16 | 141.42 | 25-JUL-08:06 | 128.55 | 128.55 | 61.16 | 0.15 |
August | 644692.67 | 586025.64 | 144.52 | 17-AUG-08:56 | 131.37 | 131.37 | 60.51 | 0.16 |
September | 9444796.50 | 8585320.02 | 299.92 | 30-SEP-06:00 | 272.63 | 272.63 | 31.31 | 0.36 |
October | 72992117.34 | 66349834.66 | 409.35 | 25-OCT-06:10 | 372.09 | 372.09 | 36.95 | 0.54 |
November | 0.311170E+09 | 0.282854E+09 | 552.94 | 16-NOV-09:03 | 502.62 | 502.62 | 54.36 | 0.83 |
December | 0.497393E+09 | 0.452130E+09 | 589.67 | 02-DEC-09:05 | 536.01 | 536.01 | 48.81 | 0.93 |
Annual Sum or Average | 0.213164E+10 | 0.193766E+10 | ||||||
Minimum of Months | 343637.52 | 312366.51 | 141.42 | 128.55 | 128.55 | 29.62 | 0.15 | |
Maximum of Months | 0.522910E+09 | 0.475326E+09 | 589.67 | 536.01 | 536.01 | 61.16 | 0.93 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 27886021.44 | 25348393.49 | 313.36 | 12-JAN-16:01 | 284.84 | 284.84 | 7.91 | 7.91 |
February | 53007080.57 | 48183436.23 | 411.27 | 20-FEB-16:01 | 373.84 | 373.84 | 7.25 | 8.97 |
March | 85081625.22 | 77339197.32 | 416.85 | 14-MAR-15:01 | 378.92 | 378.92 | 7.15 | 9.02 |
April | 0.315522E+09 | 0.286809E+09 | 1247.14 | 28-APR-20:10 | 1133.65 | 1133.65 | 7.03 | 14.58 |
May | 0.688649E+09 | 0.625982E+09 | 1812.14 | 19-MAY-18:05 | 1647.24 | 1647.24 | 6.73 | 17.04 |
June | 0.111636E+10 | 0.101477E+10 | 2347.33 | 05-JUN-18:15 | 2133.72 | 2133.72 | 6.73 | 18.95 |
July | 0.133912E+10 | 0.121726E+10 | 2082.21 | 21-JUL-21:00 | 1892.73 | 1892.73 | 7.15 | 18.05 |
August | 0.114675E+10 | 0.104240E+10 | 1787.56 | 26-AUG-18:03 | 1624.89 | 1624.89 | 6.73 | 16.95 |
September | 0.920103E+09 | 0.836373E+09 | 1637.33 | 27-SEP-18:03 | 1488.33 | 1488.33 | 6.75 | 16.34 |
October | 0.404496E+09 | 0.367687E+09 | 1506.79 | 01-OCT-19:30 | 1369.67 | 1369.67 | 6.73 | 15.78 |
November | 81242858.22 | 73849758.12 | 499.16 | 03-NOV-15:03 | 453.74 | 453.74 | 7.23 | 9.79 |
December | 21488110.43 | 19532692.38 | 200.27 | 09-DEC-16:01 | 182.05 | 182.05 | 8.25 | 6.41 |
Annual Sum or Average | 0.619971E+10 | 0.563553E+10 | ||||||
Minimum of Months | 21488110.43 | 19532692.38 | 200.27 | 182.05 | 182.05 | 6.73 | 6.41 | |
Maximum of Months | 0.133912E+10 | 0.121726E+10 | 2347.33 | 2133.72 | 2133.72 | 8.25 | 18.95 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.821032E+10 | 0.746318E+10 | 3749.05 | 01-JAN-00:10 | 3407.89 | 3407.89 | 8.45 | 26.54 |
February | 0.821229E+10 | 0.746497E+10 | 3749.05 | 01-FEB-00:05 | 3407.89 | 3407.89 | 8.41 | 26.54 |
March | 0.962348E+10 | 0.874774E+10 | 3749.05 | 01-MAR-00:05 | 3407.89 | 3407.89 | 8.43 | 26.54 |
April | 0.969809E+10 | 0.881557E+10 | 3749.05 | 01-APR-00:10 | 3407.89 | 3407.89 | 8.47 | 26.54 |
May | 0.100415E+11 | 0.912768E+10 | 3749.05 | 01-MAY-00:05 | 3407.89 | 3407.89 | 8.91 | 26.54 |
June | 0.971754E+10 | 0.883324E+10 | 3749.05 | 01-JUN-00:05 | 3407.89 | 3407.89 | 8.98 | 26.54 |
July | 0.100415E+11 | 0.912768E+10 | 3749.05 | 01-JUL-00:10 | 3407.89 | 3407.89 | 8.86 | 26.54 |
August | 0.100415E+11 | 0.912768E+10 | 3749.05 | 01-AUG-00:05 | 3407.89 | 3407.89 | 9.27 | 26.54 |
September | 0.971754E+10 | 0.883324E+10 | 3749.05 | 01-SEP-00:05 | 3407.89 | 3407.89 | 9.12 | 26.54 |
October | 0.100415E+11 | 0.912768E+10 | 3749.05 | 01-OCT-00:10 | 3407.89 | 3407.89 | 8.90 | 26.54 |
November | 0.870535E+10 | 0.791316E+10 | 3749.05 | 01-NOV-00:05 | 3407.89 | 3407.89 | 8.58 | 26.54 |
December | 0.823385E+10 | 0.748457E+10 | 3749.05 | 01-DEC-00:05 | 3407.89 | 3407.89 | 8.42 | 26.54 |
Annual Sum or Average | 0.112284E+12 | 0.102066E+12 | ||||||
Minimum of Months | 0.821032E+10 | 0.746318E+10 | 3749.05 | 3407.89 | 3407.89 | 8.41 | 26.54 | |
Maximum of Months | 0.100415E+11 | 0.912768E+10 | 3749.05 | 3407.89 | 3407.89 | 9.27 | 26.54 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 49.97 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:05 | 14.37 | 14.37 | 50.52 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 50.70 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 53.51 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 53.80 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 54.32 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 54.85 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 54.82 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 54.68 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 53.80 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 53.77 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:05 | 14.37 | 14.37 | 51.18 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 49.97 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.85 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 37.56 | 79.95 | 38135.24 | 150175.38 | 26-JAN-16:01 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 37.43 | 80.00 | 27910.95 | 145300.30 | 09-FEB-19:03 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 37.59 | 79.85 | 22515.10 | 135700.87 | 27-MAR-08:07 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.17 | 79.40 | 7686.72 | 131667.01 | 11-APR-08:04 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 27.57 | 27.57 | 558.54 | 58475.74 | 02-MAY-06:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 49.42 | 49.42 | 14.19 | 17667.94 | 13-JUN-08:35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.24 | 58.24 | 11.43 | 11740.71 | 25-JUL-08:06 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 61.12 | 61.12 | 20.06 | 12566.14 | 22-AUG-08:55 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 61.10 | 61.10 | 833.62 | 73403.30 | 30-SEP-06:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 30.51 | 30.51 | 6501.64 | 103294.89 | 24-OCT-08:05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 28.24 | 79.40 | 24262.65 | 150220.72 | 28-NOV-16:01 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 35.95 | 79.58 | 33105.79 | 156849.00 | 20-DEC-09:01 |
Annual Sum or Average | 0.00 | 13401.93 | ||||||
Minimum of Months | 0.00 | 0.00 | 27.17 | 27.57 | 11.43 | 11740.71 | ||
Maximum of Months | 0.00 | 0.00 | 61.12 | 80.00 | 38135.24 | 156849.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 17606.09 | 244822.47 | 03-JAN-16:01 | 9.89 | 7.69 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 32831.57 | 321945.89 | 22-FEB-16:01 | 10.21 | 7.31 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 46628.36 | 336522.59 | 22-MAR-15:01 | 10.15 | 7.12 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 121958.26 | 391456.88 | 21-APR-18:03 | 10.22 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 188208.84 | 430927.10 | 19-MAY-18:03 | 10.58 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 250446.67 | 521594.49 | 05-JUN-18:07 | 11.39 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 308106.64 | 636939.56 | 20-JUL-21:53 | 13.27 | 7.54 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 257105.88 | 594505.08 | 01-AUG-21:51 | 12.64 | 7.29 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 223852.56 | 469834.43 | 03-SEP-21:52 | 11.93 | 7.71 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 121086.14 | 493955.64 | 04-OCT-18:03 | 11.14 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 41027.44 | 344852.79 | 03-NOV-15:01 | 10.30 | 7.20 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 14664.96 | 180335.83 | 10-DEC-16:02 | 9.76 | 8.14 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 135872.46 | 0.00 | ||||||
Minimum of Months | 14664.96 | 180335.83 | 9.76 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 308106.64 | 636939.56 | 13.27 | 8.14 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 49.97 | 59.99 | 24471.98 | 51477.51 | 27-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 50.52 | 59.97 | 24450.33 | 51443.25 | 01-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 50.70 | 59.97 | 23591.37 | 50397.12 | 01-MAR-07:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 53.51 | 59.99 | 22037.60 | 47437.99 | 03-APR-06:40 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 53.80 | 59.99 | 20258.33 | 44057.59 | 01-MAY-06:30 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 54.32 | 60.00 | 18718.50 | 40366.24 | 01-JUN-06:55 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 54.85 | 59.99 | 17811.27 | 37641.62 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 54.82 | 59.97 | 17837.37 | 37795.25 | 31-AUG-06:50 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 54.68 | 59.99 | 18731.72 | 40320.87 | 29-SEP-06:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.80 | 59.97 | 20276.40 | 44120.23 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 53.77 | 59.97 | 22060.48 | 47768.04 | 30-NOV-07:40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 51.18 | 59.99 | 23595.42 | 50333.00 | 29-DEC-07:30 |
Annual Sum or Average | 0.00 | 21134.70 | ||||||
Minimum of Months | 0.00 | 0.00 | 49.97 | 59.97 | 17811.27 | 37641.62 | ||
Maximum of Months | 0.00 | 0.00 | 54.85 | 60.00 | 24471.98 | 51477.51 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.896584E+11 | 0.00 | 0.642902E+10 | 0.340959E+11 | 0.00 | 0.00 |
February | 0.604232E+11 | 0.00 | 0.327012E+11 | 0.314410E+11 | 0.00 | 0.00 |
March | 0.574585E+11 | 0.00 | 0.664433E+11 | 0.356202E+11 | 0.00 | 0.00 |
April | 0.197603E+11 | 0.00 | 0.206560E+12 | 0.373183E+11 | 0.00 | 0.00 |
May | 0.141341E+10 | 0.00 | 0.342895E+12 | 0.413245E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.444600E+12 | 0.434038E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.597339E+12 | 0.444647E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.481229E+12 | 0.450283E+11 | 0.00 | 0.00 |
September | 0.214112E+10 | 0.00 | 0.393129E+12 | 0.435298E+11 | 0.00 | 0.00 |
October | 0.174128E+11 | 0.00 | 0.193994E+12 | 0.417982E+11 | 0.00 | 0.00 |
November | 0.577245E+11 | 0.00 | 0.405207E+11 | 0.364877E+11 | 0.00 | 0.00 |
December | 0.706475E+11 | 0.00 | 0.373143E+10 | 0.343435E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.376640E+12 | 0.00 | 0.280957E+13 | 0.468856E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.373143E+10 | 0.314410E+11 | 0.00 | 0.00 |
Maximum of Months | 0.896584E+11 | 0.00 | 0.597339E+12 | 0.450283E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 28433854.80 | 0.00 | 0.424273E+09 | 0.271000E+10 | 0.00 | 0.00 |
February | 49880578.71 | 0.00 | 0.213296E+10 | 0.244774E+10 | 0.00 | 0.00 |
March | 15237317.16 | 0.00 | 0.440437E+10 | 0.271000E+10 | 0.00 | 0.00 |
April | 19055.34 | 0.00 | 0.144291E+11 | 0.262258E+10 | 0.00 | 0.00 |
May | 18267.15 | 0.00 | 0.237049E+11 | 0.271000E+10 | 0.00 | 0.00 |
June | 15420.29 | 0.00 | 0.293775E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 18069.78 | 0.00 | 0.398593E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 14409.20 | 0.00 | 0.333129E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 15520.91 | 0.00 | 0.283146E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 10850.97 | 0.00 | 0.135551E+11 | 0.271000E+10 | 0.00 | 0.00 |
November | 5541.32 | 0.00 | 0.268469E+10 | 0.262258E+10 | 0.00 | 0.00 |
December | 91449007.75 | 0.00 | 0.217497E+09 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.185118E+09 | 0.00 | 0.192417E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 5541.32 | 0.00 | 0.217497E+09 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 91449007.75 | 0.00 | 0.398593E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.340959E+11 | 0.642902E+10 | 0.896584E+11 | 0.157318E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.314410E+11 | 0.327012E+11 | 0.604232E+11 | 0.112735E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.356202E+11 | 0.664433E+11 | 0.574585E+11 | 0.718667E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.373183E+11 | 0.206560E+12 | 0.197603E+11 | 0.150674E+11 | 0.482993E+10 | 0.00 | 0.00 | 0.00 |
May | 0.413245E+11 | 0.342895E+12 | 0.141341E+10 | 0.194643E+11 | 0.206378E+11 | 0.00 | 0.00 | 0.00 |
June | 0.434038E+11 | 0.444600E+12 | 0.00 | 0.256769E+11 | 0.491977E+11 | 0.00 | 0.00 | 0.00 |
July | 0.444647E+11 | 0.597339E+12 | 0.00 | 0.100152E+11 | 0.837146E+11 | 0.00 | 0.00 | 0.00 |
August | 0.450283E+11 | 0.481229E+12 | 0.00 | 0.120187E+11 | 0.410859E+11 | 0.00 | 0.00 | 0.00 |
September | 0.435298E+11 | 0.393129E+12 | 0.214112E+10 | 0.741330E+10 | 0.233069E+11 | 0.00 | 0.00 | 0.00 |
October | 0.417982E+11 | 0.193994E+12 | 0.174128E+11 | 0.552924E+10 | 0.420289E+10 | 0.00 | 0.00 | 0.00 |
November | 0.364877E+11 | 0.405207E+11 | 0.577245E+11 | 0.101338E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.343435E+11 | 0.373143E+10 | 0.706475E+11 | 0.242413E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.468856E+12 | 0.280957E+13 | 0.376640E+12 | 0.780855E+12 | 0.226976E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.314410E+11 | 0.373143E+10 | 0.00 | 0.552924E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.450283E+11 | 0.597339E+12 | 0.896584E+11 | 0.242413E+12 | 0.837146E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.424273E+09 | 28433854.80 | 0.281747E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.213296E+10 | 49880578.71 | 0.200036E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.440437E+10 | 15237317.16 | 0.158882E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.144291E+11 | 19055.34 | 0.534497E+10 | 0.270140E+09 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.237049E+11 | 18267.15 | 0.228215E+10 | 0.244609E+10 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.293775E+11 | 15420.29 | 0.723616E+09 | 0.664005E+10 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.398593E+11 | 18069.78 | 290142.96 | 0.193869E+11 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.333129E+11 | 14409.20 | 0.123836E+09 | 0.112204E+11 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.283146E+11 | 15520.91 | 0.772325E+09 | 0.574472E+10 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.135551E+11 | 10850.97 | 0.349585E+10 | 0.125429E+10 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.268469E+10 | 5541.32 | 0.185302E+11 | 3091895.47 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.217497E+09 | 91449007.75 | 0.330657E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.192417E+12 | 0.185118E+09 | 0.128405E+12 | 0.469657E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.217497E+09 | 5541.32 | 290142.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.398593E+11 | 91449007.75 | 0.330657E+11 | 0.193869E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.340959E+11 | 0.896584E+11 | 0.642902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.314410E+11 | 0.604232E+11 | 0.327012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.356202E+11 | 0.574585E+11 | 0.664433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.373183E+11 | 0.197603E+11 | 0.206560E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.413245E+11 | 0.141341E+10 | 0.342895E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.434038E+11 | 0.00 | 0.444600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.444647E+11 | 0.00 | 0.597339E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.450283E+11 | 0.00 | 0.481229E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.435298E+11 | 0.214112E+10 | 0.393129E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.417982E+11 | 0.174128E+11 | 0.193994E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.364877E+11 | 0.577245E+11 | 0.405207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.343435E+11 | 0.706475E+11 | 0.373143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.468856E+12 | 0.376640E+12 | 0.280957E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.314410E+11 | 0.00 | 0.373143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.450283E+11 | 0.896584E+11 | 0.597339E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 28433854.80 | 0.424273E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 49880578.71 | 0.213296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 15237317.16 | 0.440437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 19055.34 | 0.144291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 18267.15 | 0.237049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 15420.29 | 0.293775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 18069.78 | 0.398593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 14409.20 | 0.333129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 15520.91 | 0.283146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 10850.97 | 0.135551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 5541.32 | 0.268469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 91449007.75 | 0.217497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.185118E+09 | 0.192417E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 5541.32 | 0.217497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 91449007.75 | 0.398593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.344589E+11 | 0.00 | 0.00 | 5673169.40 | 0.00 | 0.00 | 0.114972E+11 | 0.00 | 0.83 |
February | 0.372241E+11 | 0.00 | 0.00 | 70758.87 | 0.00 | 0.00 | 0.255883E+09 | 0.00 | 0.83 |
March | 0.381426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 |
April | 0.236526E+11 | 0.00 | 0.00 | 0.00 | 86829195.79 | 0.00 | 0.00 | 0.00 | 0.84 |
May | 0.140018E+11 | 0.00 | 0.00 | 0.00 | 0.509605E+09 | 0.00 | 0.00 | 0.00 | 0.84 |
June | 0.727272E+10 | 0.00 | 0.00 | 0.00 | 0.147293E+10 | 0.00 | 0.00 | 0.00 | 0.78 |
July | 0.163052E+10 | 0.151136E+10 | 0.00 | 1344891.25 | 0.504595E+10 | 0.00 | 0.283199E+09 | 0.00 | 0.78 |
August | 0.185736E+09 | 0.115462E+10 | 0.00 | 37840642.88 | 0.721393E+09 | 0.00 | 0.693191E+10 | 0.00 | 0.87 |
September | 12711959.46 | 0.124763E+10 | 0.00 | 65655196.59 | 45816034.47 | 0.00 | 0.149754E+11 | 0.00 | 1.04 |
October | 35708712.70 | 0.214689E+09 | 0.00 | 78230193.94 | 2609851.05 | 0.00 | 0.351203E+11 | 0.00 | 1.06 |
November | 0.175946E+09 | 0.00 | 0.00 | 67766339.77 | 0.00 | 0.00 | 0.491218E+11 | 0.00 | 1.01 |
December | 0.228935E+10 | 0.00 | 0.00 | 49442675.86 | 0.00 | 0.00 | 0.465209E+11 | 0.00 | 0.91 |
Annual Sum or Average | 0.159083E+12 | 0.412830E+10 | 0.00 | 0.306024E+09 | 0.788514E+10 | 0.00 | 0.164707E+12 | 0.00 | 0.89 |
Minimum of Months | 12711959.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 |
Maximum of Months | 0.381426E+11 | 0.151136E+10 | 0.00 | 78230193.94 | 0.504595E+10 | 0.00 | 0.491218E+11 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.567154E+10 | 0.00 | 0.00 | 1714545.19 | 0.00 | 17425257.08 | 0.126944E+10 | 0.00 | 2.29 |
February | 0.467772E+10 | 0.00 | 0.00 | 1737129.79 | 0.00 | 9945640.87 | 0.941079E+09 | 0.00 | 2.32 |
March | 0.510069E+10 | 0.00 | 0.00 | 1096351.68 | 0.00 | 7518804.53 | 0.543925E+09 | 0.00 | 2.27 |
April | 0.298561E+10 | 14278104.99 | 0.00 | 1747653.02 | 212483.90 | 0.00 | 0.510212E+09 | 0.00 | 2.30 |
May | 0.143713E+10 | 75666574.73 | 0.00 | 2156827.72 | 3611383.77 | 0.00 | 0.635714E+09 | 0.00 | 2.28 |
June | 0.383416E+09 | 0.246640E+09 | 0.00 | 3132993.69 | 3030333.44 | 0.00 | 0.703943E+09 | 0.00 | 2.22 |
July | 68099471.87 | 0.836182E+09 | 0.00 | 1559912.17 | 0.187261E+09 | 0.00 | 0.218302E+09 | 0.00 | 2.22 |
August | 0.398103E+09 | 0.285640E+09 | 0.00 | 3594214.47 | 25202602.26 | 0.00 | 0.580238E+09 | 0.00 | 2.37 |
September | 0.787081E+09 | 0.215032E+09 | 0.00 | 5327538.77 | 8570346.36 | 0.00 | 0.938299E+09 | 0.00 | 2.62 |
October | 0.257912E+10 | 40312091.53 | 0.00 | 6013699.84 | 937780.97 | 0.00 | 0.160637E+10 | 0.00 | 2.61 |
November | 0.440430E+10 | 0.00 | 0.00 | 3814398.64 | 0.00 | 29196623.22 | 0.181940E+10 | 0.00 | 2.48 |
December | 0.527425E+10 | 0.00 | 0.00 | 1348463.96 | 0.00 | 0.196861E+09 | 0.119562E+10 | 0.00 | 2.26 |
Annual Sum or Average | 0.337671E+11 | 0.171375E+10 | 0.00 | 33243728.94 | 0.228826E+09 | 0.260947E+09 | 0.109625E+11 | 0.00 | 2.35 |
Minimum of Months | 68099471.87 | 0.00 | 0.00 | 1096351.68 | 0.00 | 0.00 | 0.218302E+09 | 0.00 | 2.22 |
Maximum of Months | 0.567154E+10 | 0.836182E+09 | 0.00 | 6013699.84 | 0.187261E+09 | 0.196861E+09 | 0.181940E+10 | 0.00 | 2.62 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.415130E+10 | 0.00 | 0.00 | 368606.11 | 0.00 | 0.00 | 0.831269E+09 | 0.00 | 1.40 |
February | 0.307224E+10 | 0.00 | 0.00 | 529433.95 | 0.00 | 0.00 | 0.998860E+09 | 0.00 | 1.42 |
March | 0.277120E+10 | 0.00 | 0.00 | 880117.92 | 0.00 | 0.00 | 0.138301E+10 | 0.00 | 1.44 |
April | 0.898462E+09 | 1217641.90 | 0.00 | 2660275.94 | 8194965.52 | 0.00 | 0.173889E+10 | 0.00 | 1.50 |
May | 0.178503E+09 | 34054115.26 | 0.00 | 4442007.58 | 21225415.82 | 0.00 | 0.147154E+10 | 0.00 | 1.56 |
June | 20185907.76 | 0.149523E+09 | 0.00 | 4894642.90 | 14593776.46 | 0.00 | 0.906264E+09 | 0.00 | 1.53 |
July | 640120.99 | 0.696322E+09 | 0.00 | 2619911.71 | 86148459.02 | 0.00 | 0.247565E+09 | 0.00 | 1.52 |
August | 38084885.51 | 0.190551E+09 | 0.00 | 4553828.89 | 24747916.97 | 0.00 | 0.775475E+09 | 0.00 | 1.57 |
September | 48582061.53 | 0.116230E+09 | 0.00 | 5161351.09 | 19847434.49 | 0.00 | 0.136813E+10 | 0.00 | 1.65 |
October | 0.706267E+09 | 18862646.01 | 0.00 | 3665766.45 | 3757465.48 | 0.00 | 0.241910E+10 | 0.00 | 1.55 |
November | 0.257820E+10 | 0.00 | 0.00 | 1243331.16 | 0.00 | 0.00 | 0.180384E+10 | 0.00 | 1.44 |
December | 0.420794E+10 | 0.00 | 0.00 | 202042.26 | 0.00 | 0.00 | 0.592233E+09 | 0.00 | 1.40 |
Annual Sum or Average | 0.186716E+11 | 0.120676E+10 | 0.00 | 31221315.96 | 0.178515E+09 | 0.00 | 0.145362E+11 | 0.00 | 1.50 |
Minimum of Months | 640120.99 | 0.00 | 0.00 | 202042.26 | 0.00 | 0.00 | 0.247565E+09 | 0.00 | 1.40 |
Maximum of Months | 0.420794E+10 | 0.696322E+09 | 0.00 | 5161351.09 | 86148459.02 | 0.00 | 0.241910E+10 | 0.00 | 1.65 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.445519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
February | 0.363464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
March | 0.369890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
April | 0.228094E+10 | 0.00 | 0.00 | 12005.39 | 8420309.40 | 0.00 | 12762929.17 | 0.00 | 0.61 |
May | 0.101984E+10 | 1742332.72 | 0.00 | 1057344.44 | 47676884.70 | 0.00 | 0.349321E+09 | 0.00 | 0.61 |
June | 95130324.69 | 0.121918E+09 | 0.00 | 3643465.64 | 24916984.49 | 0.00 | 0.662298E+09 | 0.00 | 0.61 |
July | 6374031.34 | 0.493382E+09 | 0.00 | 2045985.55 | 0.180938E+09 | 0.00 | 0.196564E+09 | 0.00 | 0.61 |
August | 0.180761E+09 | 0.140093E+09 | 0.00 | 2542665.89 | 46371874.99 | 0.00 | 0.475767E+09 | 0.00 | 0.62 |
September | 0.688930E+09 | 33217616.85 | 0.00 | 1238180.09 | 83033806.32 | 0.00 | 0.427415E+09 | 0.00 | 0.62 |
October | 0.256038E+10 | 4686852.16 | 0.00 | 170940.67 | 14182472.46 | 0.00 | 85150701.75 | 0.00 | 0.61 |
November | 0.387050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
December | 0.429431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Annual Sum or Average | 0.267859E+11 | 0.795040E+09 | 0.00 | 10710587.68 | 0.405540E+09 | 0.00 | 0.220928E+10 | 0.00 | 0.61 |
Minimum of Months | 6374031.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.445519E+10 | 0.493382E+09 | 0.00 | 3643465.64 | 0.180938E+09 | 0.00 | 0.662298E+09 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.242162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
February | 0.197561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
March | 0.201054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
April | 0.124675E+10 | 0.00 | 0.00 | 0.00 | 4576858.20 | 0.00 | 0.00 | 0.00 | 0.57 |
May | 0.671017E+09 | 234788.28 | 0.00 | 143204.87 | 26627021.64 | 0.00 | 67124652.22 | 0.00 | 0.57 |
June | 0.102715E+09 | 61537829.22 | 0.00 | 1353295.17 | 17201253.50 | 0.00 | 0.291466E+09 | 0.00 | 0.55 |
July | 13087044.41 | 0.211682E+09 | 0.00 | 868712.00 | 0.139839E+09 | 0.00 | 91333355.19 | 0.00 | 0.55 |
August | 0.172437E+09 | 64358123.95 | 0.00 | 817978.55 | 33102119.86 | 0.00 | 0.175167E+09 | 0.00 | 0.56 |
September | 0.525008E+09 | 11706257.57 | 0.00 | 191866.43 | 50799343.45 | 0.00 | 75271179.05 | 0.00 | 0.57 |
October | 0.142767E+10 | 1274019.11 | 0.00 | 15785.28 | 8679118.22 | 0.00 | 9383696.07 | 0.00 | 0.58 |
November | 0.210381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
December | 0.233417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
Annual Sum or Average | 0.150044E+11 | 0.350793E+09 | 0.00 | 3390842.29 | 0.280825E+09 | 0.00 | 0.709746E+09 | 0.00 | 0.56 |
Minimum of Months | 13087044.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.242162E+10 | 0.211682E+09 | 0.00 | 1353295.17 | 0.139839E+09 | 0.00 | 0.291466E+09 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.183138E+09 | 0.00 | 0.00 | 99309832.49 | 0.00 | 0.00 | 0.888416E+11 | 0.00 | 24.74 |
February | 0.133682E+09 | 0.00 | 0.00 | 91850806.97 | 0.00 | 0.00 | 0.726275E+11 | 0.00 | 25.06 |
March | 73356113.64 | 0.00 | 0.00 | 0.109402E+09 | 0.00 | 0.00 | 0.741983E+11 | 0.00 | 25.39 |
April | 5161433.40 | 0.141318E+09 | 0.00 | 0.120085E+09 | 0.00 | 0.00 | 0.451044E+11 | 0.00 | 25.50 |
May | 0.00 | 0.834830E+09 | 0.00 | 0.118129E+09 | 0.00 | 0.00 | 0.263079E+11 | 0.00 | 25.24 |
June | 0.00 | 0.256035E+10 | 0.00 | 87217669.86 | 0.00 | 0.00 | 0.131418E+11 | 0.00 | 23.01 |
July | 0.00 | 0.124998E+11 | 0.00 | 33292162.40 | 0.00 | 0.00 | 0.336318E+10 | 0.00 | 22.82 |
August | 0.00 | 0.344851E+10 | 0.00 | 82877567.59 | 0.00 | 0.00 | 0.119244E+11 | 0.00 | 23.96 |
September | 3110464.57 | 0.213036E+10 | 0.00 | 97890440.60 | 0.00 | 0.00 | 0.215868E+11 | 0.00 | 25.37 |
October | 11280590.51 | 0.382083E+09 | 0.00 | 0.113834E+09 | 0.00 | 0.00 | 0.523703E+11 | 0.00 | 25.68 |
November | 93547803.29 | 0.00 | 0.00 | 0.102807E+09 | 0.00 | 0.00 | 0.778312E+11 | 0.00 | 25.17 |
December | 0.195102E+09 | 0.00 | 0.00 | 98164637.74 | 0.00 | 0.00 | 0.850413E+11 | 0.00 | 24.71 |
Annual Sum or Average | 0.698378E+09 | 0.219972E+11 | 0.00 | 0.115486E+10 | 0.00 | 0.00 | 0.572339E+12 | 0.00 | 24.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 33292162.40 | 0.00 | 0.00 | 0.336318E+10 | 0.00 | 22.82 |
Maximum of Months | 0.195102E+09 | 0.124998E+11 | 0.00 | 0.120085E+09 | 0.00 | 0.00 | 0.888416E+11 | 0.00 | 25.68 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.640018E+10 | 0.00 | 0.00 | 23538685.47 | 0.00 | 0.00 | 0.252696E+11 | 0.00 | 3.71 |
February | 0.399464E+10 | 0.00 | 0.00 | 23690929.71 | 0.00 | 0.00 | 0.217181E+11 | 0.00 | 3.77 |
March | 0.518930E+10 | 0.00 | 0.00 | 24843524.49 | 0.00 | 0.00 | 0.206623E+11 | 0.00 | 3.71 |
April | 0.249220E+10 | 60685787.43 | 0.00 | 29342623.19 | 332926.34 | 0.00 | 0.140577E+11 | 0.00 | 3.87 |
May | 0.923115E+09 | 0.324999E+09 | 0.00 | 28857039.77 | 13661034.83 | 0.00 | 0.942212E+10 | 0.00 | 3.94 |
June | 0.181388E+09 | 0.975741E+09 | 0.00 | 26994217.78 | 28152358.81 | 0.00 | 0.559265E+10 | 0.00 | 3.81 |
July | 10557887.49 | 0.439332E+10 | 0.00 | 14812160.14 | 0.348594E+09 | 0.00 | 0.156122E+10 | 0.00 | 3.80 |
August | 0.244680E+09 | 0.127621E+10 | 0.00 | 28300034.38 | 58945831.90 | 0.00 | 0.492242E+10 | 0.00 | 4.02 |
September | 0.258237E+09 | 0.885829E+09 | 0.00 | 36540825.04 | 27022402.83 | 0.00 | 0.862677E+10 | 0.00 | 4.35 |
October | 0.160047E+10 | 0.160545E+09 | 0.00 | 44214822.57 | 2467565.29 | 0.00 | 0.186465E+11 | 0.00 | 4.31 |
November | 0.366106E+10 | 0.00 | 0.00 | 34618903.52 | 0.00 | 0.00 | 0.251143E+11 | 0.00 | 4.03 |
December | 0.669677E+10 | 0.00 | 0.00 | 20302779.93 | 0.00 | 0.00 | 0.235921E+11 | 0.00 | 3.67 |
Annual Sum or Average | 0.316526E+11 | 0.807733E+10 | 0.00 | 0.336057E+09 | 0.479177E+09 | 0.00 | 0.179186E+12 | 0.00 | 3.92 |
Minimum of Months | 10557887.49 | 0.00 | 0.00 | 14812160.14 | 0.00 | 0.00 | 0.156122E+10 | 0.00 | 3.67 |
Maximum of Months | 0.669677E+10 | 0.439332E+10 | 0.00 | 44214822.57 | 0.348594E+09 | 0.00 | 0.252696E+11 | 0.00 | 4.35 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.390635E+11 | 0.00 | 0.00 | 45185223.82 | 0.00 | 0.00 | 0.645382E+11 | 0.00 | 1.74 |
February | 0.265650E+11 | 0.00 | 0.00 | 48256379.23 | 0.00 | 0.00 | 0.585441E+11 | 0.00 | 1.77 |
March | 0.262999E+11 | 0.00 | 0.00 | 58752567.80 | 0.00 | 0.00 | 0.613006E+11 | 0.00 | 1.80 |
April | 0.886696E+10 | 0.144168E+09 | 0.00 | 85756173.96 | 47750175.74 | 0.00 | 0.484332E+11 | 0.00 | 1.91 |
May | 0.238663E+10 | 0.889859E+09 | 0.00 | 0.106854E+09 | 0.237082E+09 | 0.00 | 0.344416E+11 | 0.00 | 1.99 |
June | 0.379897E+09 | 0.307528E+10 | 0.00 | 0.105560E+09 | 0.250131E+09 | 0.00 | 0.202074E+11 | 0.00 | 1.92 |
July | 8859862.04 | 0.151678E+11 | 0.00 | 56456402.07 | 0.126450E+10 | 0.00 | 0.556655E+10 | 0.00 | 1.91 |
August | 0.544733E+09 | 0.406434E+10 | 0.00 | 0.102069E+09 | 0.391526E+09 | 0.00 | 0.176955E+11 | 0.00 | 1.99 |
September | 0.428007E+09 | 0.253886E+10 | 0.00 | 0.120991E+09 | 0.268450E+09 | 0.00 | 0.310207E+11 | 0.00 | 2.08 |
October | 0.514801E+10 | 0.445418E+09 | 0.00 | 0.124474E+09 | 21420570.51 | 0.00 | 0.640005E+11 | 0.00 | 2.00 |
November | 0.151245E+11 | 0.00 | 0.00 | 81624873.44 | 0.00 | 0.00 | 0.786313E+11 | 0.00 | 1.83 |
December | 0.427375E+11 | 0.00 | 0.00 | 37922533.74 | 0.00 | 0.00 | 0.562646E+11 | 0.00 | 1.72 |
Annual Sum or Average | 0.167553E+12 | 0.263257E+11 | 0.00 | 0.973903E+09 | 0.248086E+10 | 0.00 | 0.540644E+12 | 0.00 | 1.89 |
Minimum of Months | 8859862.04 | 0.00 | 0.00 | 37922533.74 | 0.00 | 0.00 | 0.556655E+10 | 0.00 | 1.72 |
Maximum of Months | 0.427375E+11 | 0.151678E+11 | 0.00 | 0.124474E+09 | 0.126450E+10 | 0.00 | 0.786313E+11 | 0.00 | 2.08 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 68265409.29 | 0.00 | 0.00 | 3526537.50 | 0.00 | 0.773856E+09 | 0.608712E+09 | 0.00 | 0.35 |
February | 44604231.80 | 0.00 | 0.00 | 4769124.74 | 0.00 | 0.469771E+09 | 0.707024E+09 | 0.00 | 0.35 |
March | 48512101.82 | 0.00 | 0.00 | 8442605.15 | 0.00 | 0.254178E+09 | 0.969827E+09 | 0.00 | 0.35 |
April | 10330037.40 | 3044671.17 | 352.65 | 14781807.08 | 0.00 | 18015038.86 | 0.839454E+09 | 842.81 | 0.35 |
May | 0.00 | 33655142.00 | 0.00 | 13784337.12 | 0.00 | 671139.34 | 0.502194E+09 | 1934.85 | 0.36 |
June | 0.00 | 90044968.32 | 16466.59 | 9197455.59 | 0.00 | 216647.52 | 0.133646E+09 | 2615.10 | 0.36 |
July | 0.00 | 0.624485E+09 | 320074.64 | 165161.40 | 0.00 | 591.79 | 585892.53 | 38388.09 | 0.35 |
August | 0.00 | 0.300917E+09 | 107230.03 | 3526389.02 | 0.00 | 217514.11 | 44264276.27 | 19152.45 | 0.35 |
September | 0.00 | 0.271406E+09 | 52864.88 | 7985039.35 | 0.00 | 443882.05 | 0.245664E+09 | 18503.87 | 0.36 |
October | 6125134.65 | 41537838.62 | 0.00 | 13181564.15 | 0.00 | 3395844.70 | 0.803617E+09 | 914.63 | 0.35 |
November | 19149812.50 | 26952.12 | 0.00 | 7473532.81 | 0.00 | 0.356133E+09 | 0.921408E+09 | 0.00 | 0.35 |
December | 69394019.82 | 0.00 | 0.00 | 2611373.22 | 0.00 | 0.893752E+09 | 0.502341E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.266381E+09 | 0.136512E+10 | 496988.79 | 89444927.14 | 0.00 | 0.277065E+10 | 0.627874E+10 | 82351.80 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 165161.40 | 0.00 | 591.79 | 585892.53 | 0.00 | 0.35 |
Maximum of Months | 69394019.82 | 0.624485E+09 | 320074.64 | 14781807.08 | 0.00 | 0.893752E+09 | 0.969827E+09 | 38388.09 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.111629E+09 | 0.00 | 0.00 | 1264516.89 | 0.00 | 0.112944E+10 | 0.211858E+09 | 0.00 | 0.35 |
February | 0.157731E+09 | 0.00 | 0.00 | 1588072.66 | 0.00 | 0.714623E+09 | 0.352083E+09 | 0.00 | 0.35 |
March | 0.201185E+09 | 0.00 | 0.00 | 3786021.17 | 0.00 | 0.383852E+09 | 0.691987E+09 | 0.00 | 0.35 |
April | 0.153604E+09 | 2943057.13 | 229.61 | 11426106.81 | 101257.31 | 23285985.58 | 0.694161E+09 | 965.70 | 0.35 |
May | 97059524.44 | 31452223.29 | 14387.83 | 11170773.27 | 2175501.07 | 606949.30 | 0.407752E+09 | 11021.25 | 0.36 |
June | 35453603.88 | 87568470.77 | 9200.78 | 6905987.49 | 2459020.83 | 11707.59 | 0.100672E+09 | 16805.31 | 0.36 |
July | 646196.09 | 0.542979E+09 | 267646.51 | 64423.17 | 81503500.48 | 0.00 | 40938.40 | 20094.54 | 0.36 |
August | 24434864.52 | 0.268697E+09 | 163622.24 | 2232120.44 | 32120506.55 | 26311.12 | 21309258.46 | 27640.71 | 0.36 |
September | 78979420.70 | 0.236766E+09 | 161167.90 | 5437439.44 | 34488103.81 | 404355.33 | 0.169242E+09 | 31111.77 | 0.36 |
October | 0.169662E+09 | 36125486.06 | 40630.02 | 7220414.81 | 5355682.75 | 4128812.37 | 0.645212E+09 | 12087.55 | 0.36 |
November | 0.157325E+09 | 25352.07 | 0.00 | 2794353.89 | 1596.89 | 0.593217E+09 | 0.550675E+09 | 0.00 | 0.35 |
December | 0.112207E+09 | 0.00 | 0.00 | 756428.41 | 0.00 | 0.123497E+10 | 0.119993E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.129992E+10 | 0.120656E+10 | 656884.89 | 54646658.44 | 0.158205E+09 | 0.408456E+10 | 0.396499E+10 | 119726.83 | 0.35 |
Minimum of Months | 646196.09 | 0.00 | 0.00 | 64423.17 | 0.00 | 0.00 | 40938.40 | 0.00 | 0.35 |
Maximum of Months | 0.201185E+09 | 0.542979E+09 | 267646.51 | 11426106.81 | 81503500.48 | 0.123497E+10 | 0.694161E+09 | 31111.77 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.274957E+09 | 0.00 | 0.00 | 3733675.43 | 0.00 | 0.00 | 0.139058E+10 | 0.00 | 0.02 |
February | 0.110547E+09 | 0.00 | 0.00 | 3268474.51 | 0.00 | 0.00 | 0.122488E+10 | 0.00 | 0.02 |
March | 74030773.90 | 0.00 | 0.00 | 3314452.15 | 0.00 | 0.00 | 0.127277E+10 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.00 | 3421533.82 | 0.00 | 0.00 | 0.657474E+09 | 0.00 | 0.02 |
May | 0.00 | 24360391.79 | 0.00 | 2338104.69 | 0.00 | 0.00 | 0.249551E+09 | 0.00 | 0.02 |
June | 0.00 | 42930873.91 | 0.00 | 1971666.54 | 0.00 | 0.00 | 50055089.87 | 0.00 | 0.02 |
July | 0.00 | 0.437243E+09 | 0.00 | 104680.47 | 0.00 | 0.00 | 678531.66 | 0.00 | 0.02 |
August | 0.00 | 0.205366E+09 | 0.00 | 580027.04 | 0.00 | 0.00 | 2372374.14 | 0.00 | 0.02 |
September | 0.00 | 0.176119E+09 | 0.00 | 2014805.25 | 0.00 | 0.00 | 73497153.52 | 0.00 | 0.02 |
October | 0.00 | 59499723.58 | 0.00 | 4435229.66 | 0.00 | 0.00 | 0.691061E+09 | 0.00 | 0.02 |
November | 0.232128E+09 | 0.00 | 0.00 | 4569031.08 | 0.00 | 0.00 | 0.109226E+10 | 0.00 | 0.02 |
December | 0.220042E+09 | 0.00 | 0.00 | 3189979.38 | 0.00 | 0.00 | 0.148210E+10 | 0.00 | 0.02 |
Annual Sum or Average | 0.911704E+09 | 0.945519E+09 | 0.00 | 32941660.01 | 0.00 | 0.00 | 0.818728E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 104680.47 | 0.00 | 0.00 | 678531.66 | 0.00 | 0.02 |
Maximum of Months | 0.274957E+09 | 0.437243E+09 | 0.00 | 4569031.08 | 0.00 | 0.00 | 0.148210E+10 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.151418E+10 | 0.00 | 0.00 | 20399051.72 | 0.00 | 0.389964E+10 | 0.142910E+11 | 0.00 | 0.40 |
February | 0.213952E+10 | 0.00 | 0.00 | 30034525.87 | 0.00 | 0.233679E+10 | 0.121239E+11 | 0.00 | 0.40 |
March | 0.273601E+10 | 0.00 | 0.00 | 56558313.64 | 0.00 | 0.444100E+09 | 0.141367E+11 | 0.00 | 0.40 |
April | 0.216548E+10 | 33995829.61 | 213705.28 | 0.113299E+09 | 7078477.97 | 22265952.11 | 0.966923E+10 | 22499.99 | 0.40 |
May | 0.136727E+10 | 0.417825E+09 | 840083.16 | 0.102950E+09 | 37760374.74 | 5329754.14 | 0.553167E+10 | 59024.17 | 0.40 |
June | 0.480907E+09 | 0.118029E+10 | 1181416.97 | 60092332.46 | 40002042.82 | 86190.93 | 0.139921E+10 | 48137.19 | 0.40 |
July | 8765262.28 | 0.735299E+10 | 4359709.37 | 657412.09 | 0.111727E+10 | 0.00 | 771754.33 | 17890.54 | 0.40 |
August | 0.331444E+09 | 0.361124E+10 | 4048042.05 | 21619599.77 | 0.467631E+09 | 208909.17 | 0.297853E+09 | 78808.79 | 0.40 |
September | 0.112101E+10 | 0.316783E+10 | 1531960.39 | 50529876.62 | 0.512612E+09 | 2283321.18 | 0.227239E+10 | 23914.53 | 0.40 |
October | 0.237041E+10 | 0.466639E+09 | 522248.78 | 81484206.52 | 96198890.36 | 19790122.67 | 0.873554E+10 | 22307.30 | 0.40 |
November | 0.216669E+10 | 52246.10 | 9101.65 | 37525796.18 | 301400.86 | 0.919646E+09 | 0.145643E+11 | 2797.95 | 0.40 |
December | 0.152201E+10 | 0.00 | 0.00 | 15144375.52 | 0.00 | 0.686388E+10 | 0.115105E+11 | 0.00 | 0.40 |
Annual Sum or Average | 0.179237E+11 | 0.162309E+11 | 12706267.65 | 0.590294E+09 | 0.227886E+10 | 0.145140E+11 | 0.945331E+11 | 275380.46 | 0.40 |
Minimum of Months | 8765262.28 | 0.00 | 0.00 | 657412.09 | 0.00 | 0.00 | 771754.33 | 0.00 | 0.40 |
Maximum of Months | 0.273601E+10 | 0.735299E+10 | 4359709.37 | 0.113299E+09 | 0.111727E+10 | 0.686388E+10 | 0.145643E+11 | 78808.79 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 68808366.84 | 0.00 | 0.00 | 3694426.91 | 0.00 | 0.796558E+09 | 0.585299E+09 | 0.00 | 0.35 |
February | 37664266.29 | 0.00 | 0.00 | 5589654.55 | 0.00 | 0.451318E+09 | 0.731597E+09 | 0.00 | 0.35 |
March | 23778086.64 | 0.00 | 0.00 | 8589381.86 | 0.00 | 0.289921E+09 | 0.958671E+09 | 0.00 | 0.35 |
April | 0.00 | 3044671.17 | 686.75 | 15967169.75 | 0.00 | 18924158.03 | 0.847689E+09 | 508.70 | 0.35 |
May | 0.00 | 33644727.45 | 8712.50 | 15412576.03 | 0.00 | 69702.46 | 0.501167E+09 | 3636.90 | 0.36 |
June | 0.00 | 90064050.01 | 0.00 | 10490433.29 | 0.00 | 27382.89 | 0.132542E+09 | 0.00 | 0.36 |
July | 0.00 | 0.624844E+09 | 0.00 | 202984.35 | 0.00 | 0.00 | 548661.37 | 0.00 | 0.35 |
August | 0.00 | 0.301008E+09 | 32262.07 | 4084334.31 | 0.00 | 99910.37 | 43823934.72 | 3341.39 | 0.35 |
September | 0.00 | 0.271478E+09 | 0.00 | 8631805.72 | 0.00 | 135415.23 | 0.245326E+09 | 0.00 | 0.36 |
October | 6709953.92 | 41538753.25 | 0.00 | 12559640.77 | 0.00 | 1964160.12 | 0.805086E+09 | 0.00 | 0.35 |
November | 19434379.31 | 26952.12 | 0.00 | 7670558.80 | 0.00 | 0.394169E+09 | 0.882891E+09 | 0.00 | 0.35 |
December | 74353591.76 | 0.00 | 0.00 | 2976170.78 | 0.00 | 0.858006E+09 | 0.532763E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.230749E+09 | 0.136565E+10 | 41661.32 | 95869137.10 | 0.00 | 0.281119E+10 | 0.626740E+10 | 7487.00 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 202984.35 | 0.00 | 0.00 | 548661.37 | 0.00 | 0.35 |
Maximum of Months | 74353591.76 | 0.624844E+09 | 32262.07 | 15967169.75 | 0.00 | 0.858006E+09 | 0.958671E+09 | 3636.90 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112045E+09 | 0.00 | 0.00 | 753710.07 | 0.00 | 0.111112E+10 | 0.230269E+09 | 0.00 | 0.35 |
February | 0.157227E+09 | 0.00 | 0.00 | 2229642.08 | 0.00 | 0.633052E+09 | 0.433517E+09 | 0.00 | 0.35 |
March | 0.194390E+09 | 0.00 | 0.00 | 4612841.70 | 0.00 | 0.395996E+09 | 0.685811E+09 | 0.00 | 0.35 |
April | 0.137586E+09 | 2943057.13 | 534.14 | 12546063.89 | 101257.31 | 22281271.56 | 0.710064E+09 | 661.17 | 0.35 |
May | 93311179.55 | 31481903.81 | 32456.28 | 11770145.90 | 2133654.37 | 375355.02 | 0.411132E+09 | 5118.98 | 0.36 |
June | 34702969.81 | 87476969.87 | 153.57 | 7387423.69 | 2574489.93 | 0.00 | 0.100952E+09 | 1884.32 | 0.36 |
July | 646196.09 | 0.545386E+09 | 155707.02 | 70351.20 | 79226854.68 | 0.00 | 35010.37 | 2588.23 | 0.36 |
August | 23917564.54 | 0.269427E+09 | 73270.08 | 2345698.15 | 31496859.45 | 14287.21 | 21725004.65 | 11117.62 | 0.36 |
September | 78066869.68 | 0.238343E+09 | 30318.80 | 5644716.09 | 33069052.82 | 185554.77 | 0.170166E+09 | 4063.37 | 0.36 |
October | 0.158088E+09 | 36227455.63 | 22772.05 | 7379751.92 | 5279700.70 | 13399276.70 | 0.647356E+09 | 3958.01 | 0.36 |
November | 0.157703E+09 | 25352.07 | 0.00 | 3106310.04 | 1596.89 | 0.572355E+09 | 0.570847E+09 | 0.00 | 0.35 |
December | 0.112207E+09 | 0.00 | 0.00 | 579127.10 | 0.00 | 0.118099E+10 | 0.174155E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.125989E+10 | 0.121131E+10 | 315211.94 | 58425781.82 | 0.153883E+09 | 0.392977E+10 | 0.415603E+10 | 29391.69 | 0.35 |
Minimum of Months | 646196.09 | 0.00 | 0.00 | 70351.20 | 0.00 | 0.00 | 35010.37 | 0.00 | 0.35 |
Maximum of Months | 0.194390E+09 | 0.545386E+09 | 155707.02 | 12546063.89 | 79226854.68 | 0.118099E+10 | 0.710064E+09 | 11117.62 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.262372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
February | 0.214049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
March | 0.217833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
April | 0.135080E+11 | 0.00 | 0.00 | 0.00 | 49588301.79 | 0.00 | 0.00 | 0.00 | 0.49 |
May | 0.678241E+10 | 33237450.16 | 0.00 | 2325543.59 | 0.257799E+09 | 0.00 | 0.121517E+10 | 0.00 | 0.49 |
June | 0.105880E+10 | 0.732456E+09 | 0.00 | 13803979.62 | 0.129223E+09 | 0.00 | 0.324986E+10 | 0.00 | 0.48 |
July | 0.145696E+09 | 0.199967E+10 | 0.00 | 7529492.87 | 0.178485E+10 | 0.00 | 0.977027E+09 | 0.00 | 0.47 |
August | 0.175416E+10 | 0.760002E+09 | 0.00 | 9269676.02 | 0.297322E+09 | 0.00 | 0.203037E+10 | 0.00 | 0.48 |
September | 0.406392E+10 | 0.346610E+09 | 0.00 | 7232900.79 | 0.335746E+09 | 0.00 | 0.247775E+10 | 0.00 | 0.50 |
October | 0.151516E+11 | 41936611.80 | 0.00 | 870435.68 | 65901375.77 | 0.00 | 0.422215E+09 | 0.00 | 0.49 |
November | 0.227939E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
December | 0.251490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140777E+09 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.159833E+12 | 0.391392E+10 | 0.00 | 41032028.57 | 0.292043E+10 | 0.140777E+09 | 0.103724E+11 | 0.00 | 0.48 |
Minimum of Months | 0.145696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.262372E+11 | 0.199967E+10 | 0.00 | 13803979.62 | 0.178485E+10 | 0.140777E+09 | 0.324986E+10 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 18464662.58 | 0.00 | 0.00 | 718531.55 | 0.00 | 0.247163E+09 | 97243823.57 | 0.00 | 0.35 |
February | 11508898.27 | 0.00 | 0.00 | 1007548.57 | 0.00 | 0.177838E+09 | 0.116188E+09 | 0.00 | 0.35 |
March | 12322388.43 | 0.00 | 0.00 | 1889702.28 | 0.00 | 0.134182E+09 | 0.171845E+09 | 0.00 | 0.35 |
April | 3171400.05 | 761167.79 | 183.56 | 3504383.95 | 0.00 | 25048445.69 | 0.188921E+09 | 115.30 | 0.35 |
May | 0.00 | 8413785.50 | 0.00 | 3250418.89 | 0.00 | 599988.44 | 0.125312E+09 | 483.71 | 0.36 |
June | 0.00 | 22513813.01 | 1604.22 | 2223683.28 | 0.00 | 54161.88 | 33487059.57 | 595.27 | 0.36 |
July | 0.00 | 0.156114E+09 | 86122.60 | 39069.26 | 0.00 | 147.95 | 148694.23 | 11174.35 | 0.35 |
August | 0.00 | 75224869.17 | 30707.99 | 817326.10 | 0.00 | 54378.53 | 11130340.23 | 5343.37 | 0.35 |
September | 0.00 | 67851611.26 | 12140.78 | 1835642.36 | 0.00 | 122248.00 | 61565341.50 | 5701.41 | 0.36 |
October | 2024526.32 | 10380629.65 | 3437.26 | 2908498.94 | 0.00 | 13073707.96 | 0.188573E+09 | 621.41 | 0.35 |
November | 5611778.73 | 6738.03 | 0.00 | 1521185.37 | 0.00 | 0.148857E+09 | 0.170051E+09 | 0.00 | 0.35 |
December | 19871306.82 | 0.00 | 0.00 | 533847.47 | 0.00 | 0.269456E+09 | 77163827.03 | 0.00 | 0.35 |
Annual Sum or Average | 72974961.19 | 0.341266E+09 | 134196.41 | 20249838.01 | 0.00 | 0.101645E+10 | 0.124163E+10 | 24034.83 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 39069.26 | 0.00 | 147.95 | 148694.23 | 0.00 | 0.35 |
Maximum of Months | 19871306.82 | 0.156114E+09 | 86122.60 | 3504383.95 | 0.00 | 0.269456E+09 | 0.188921E+09 | 11174.35 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 27713346.69 | 0.00 | 0.00 | 223066.63 | 0.00 | 0.308940E+09 | 26670681.17 | 0.00 | 0.35 |
February | 39432715.23 | 0.00 | 0.00 | 286272.29 | 0.00 | 0.226238E+09 | 40548892.50 | 0.00 | 0.35 |
March | 50541278.75 | 0.00 | 0.00 | 767041.15 | 0.00 | 0.163888E+09 | 0.105006E+09 | 0.00 | 0.35 |
April | 38442882.60 | 735764.28 | 153.19 | 2706515.66 | 25314.33 | 24926676.97 | 0.154543E+09 | 145.64 | 0.35 |
May | 24210992.34 | 7866363.61 | 1197.08 | 2673452.71 | 543875.27 | 187582.92 | 0.102075E+09 | 1847.41 | 0.36 |
June | 8863400.97 | 21910163.53 | 3116.36 | 1717940.05 | 595725.67 | 8439.95 | 25170933.37 | 4368.87 | 0.36 |
July | 161549.02 | 0.135725E+09 | 86851.57 | 17015.17 | 20375875.12 | 0.00 | 9325.23 | 4463.43 | 0.36 |
August | 6108716.13 | 67179800.02 | 34695.26 | 535324.15 | 8030126.64 | 13005.14 | 5343593.22 | 7480.70 | 0.36 |
September | 19771197.31 | 59186620.04 | 45314.57 | 1246476.23 | 8622025.95 | 92069.34 | 42406046.31 | 7540.99 | 0.36 |
October | 42602239.51 | 9048210.59 | 15097.10 | 1447233.26 | 1317000.41 | 17378322.54 | 0.145128E+09 | 3163.50 | 0.36 |
November | 39550362.48 | 6338.02 | 0.00 | 496586.68 | 399.22 | 0.215827E+09 | 70129065.47 | 0.00 | 0.35 |
December | 27378177.92 | 0.00 | 0.00 | 128595.41 | 0.00 | 0.323925E+09 | 15550207.98 | 0.00 | 0.35 |
Annual Sum or Average | 0.324777E+09 | 0.301659E+09 | 186425.13 | 12245519.39 | 39510342.60 | 0.128142E+10 | 0.732581E+09 | 29010.53 | 0.35 |
Minimum of Months | 161549.02 | 0.00 | 0.00 | 17015.17 | 0.00 | 0.00 | 9325.23 | 0.00 | 0.35 |
Maximum of Months | 50541278.75 | 0.135725E+09 | 86851.57 | 2706515.66 | 20375875.12 | 0.323925E+09 | 0.154543E+09 | 7540.99 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 22366147.93 | 0.00 | 0.00 | 12783806.28 | 0.00 | 0.663273E+09 | 0.163746E+10 | 0.00 | 0.40 |
February | 10146229.74 | 0.00 | 0.00 | 12851827.09 | 0.00 | 0.433255E+09 | 0.151312E+10 | 0.00 | 0.40 |
March | 15268253.93 | 0.00 | 0.00 | 14401693.55 | 0.00 | 0.296780E+09 | 0.173093E+10 | 0.00 | 0.40 |
April | 1997198.83 | 4892034.42 | 0.00 | 19352788.23 | 0.00 | 48292817.06 | 0.134789E+10 | 0.00 | 0.40 |
May | 0.00 | 54025875.65 | 25877.38 | 16512379.50 | 0.00 | 3863372.99 | 0.809426E+09 | 5629.86 | 0.40 |
June | 0.00 | 0.144618E+09 | 26375.71 | 11461473.83 | 0.00 | 288065.48 | 0.218022E+09 | 9126.48 | 0.40 |
July | 0.00 | 0.100310E+10 | 432184.69 | 231620.90 | 0.00 | 0.00 | 975614.07 | 39945.72 | 0.40 |
August | 0.00 | 0.483293E+09 | 196692.06 | 4817924.56 | 0.00 | 274726.48 | 72014358.19 | 23363.20 | 0.40 |
September | 0.00 | 0.436021E+09 | 5028.32 | 11510247.99 | 0.00 | 351692.24 | 0.396242E+09 | 284.94 | 0.40 |
October | 8850160.70 | 66716319.39 | 0.00 | 22402333.83 | 0.00 | 2635832.22 | 0.129328E+10 | 0.00 | 0.40 |
November | 24014427.41 | 43288.41 | 0.00 | 18002316.39 | 0.00 | 0.328639E+09 | 0.172399E+10 | 0.00 | 0.40 |
December | 24400453.58 | 0.00 | 0.00 | 11868369.69 | 0.00 | 0.830023E+09 | 0.149165E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.107043E+09 | 0.219271E+10 | 686158.16 | 0.156197E+09 | 0.00 | 0.260768E+10 | 0.122350E+11 | 78350.21 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 231620.90 | 0.00 | 0.00 | 975614.07 | 0.00 | 0.40 |
Maximum of Months | 24400453.58 | 0.100310E+10 | 432184.69 | 22402333.83 | 0.00 | 0.830023E+09 | 0.173093E+10 | 39945.72 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.238013E+10 | 0.00 | 0.00 | 51565927.14 | 0.00 | 0.00 | 0.521753E+11 | 0.00 | 4.66 |
February | 0.143752E+10 | 0.00 | 0.00 | 52795032.73 | 0.00 | 0.00 | 0.443388E+11 | 0.00 | 4.81 |
March | 0.842472E+09 | 0.00 | 0.00 | 68984314.14 | 0.00 | 0.00 | 0.478216E+11 | 0.00 | 5.02 |
April | 0.147867E+09 | 99418634.64 | 0.00 | 87877758.89 | 0.00 | 0.00 | 0.327671E+11 | 0.00 | 5.48 |
May | 990568.45 | 0.617252E+09 | 0.00 | 92434277.62 | 0.00 | 0.00 | 0.214177E+11 | 0.00 | 5.80 |
June | 0.00 | 0.191864E+10 | 0.00 | 76313250.27 | 0.00 | 0.00 | 0.117739E+11 | 0.00 | 5.59 |
July | 0.00 | 0.924979E+10 | 0.00 | 33825370.78 | 0.00 | 0.00 | 0.315999E+10 | 0.00 | 5.53 |
August | 0.00 | 0.245185E+10 | 0.00 | 70925836.40 | 0.00 | 0.00 | 0.102163E+11 | 0.00 | 5.66 |
September | 7398817.39 | 0.148696E+10 | 0.00 | 76851660.65 | 0.00 | 0.00 | 0.171524E+11 | 0.00 | 5.77 |
October | 0.114403E+09 | 0.240671E+09 | 0.00 | 84204002.77 | 0.00 | 0.00 | 0.372332E+11 | 0.00 | 5.44 |
November | 0.988634E+09 | 0.00 | 0.00 | 60411457.06 | 0.00 | 0.00 | 0.483274E+11 | 0.00 | 4.89 |
December | 0.290634E+10 | 0.00 | 0.00 | 48120439.08 | 0.00 | 0.00 | 0.487405E+11 | 0.00 | 4.60 |
Annual Sum or Average | 0.882575E+10 | 0.160646E+11 | 0.00 | 0.804309E+09 | 0.00 | 0.00 | 0.375124E+12 | 0.00 | 5.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 33825370.78 | 0.00 | 0.00 | 0.315999E+10 | 0.00 | 4.60 |
Maximum of Months | 0.290634E+10 | 0.924979E+10 | 0.00 | 92434277.62 | 0.00 | 0.00 | 0.521753E+11 | 0.00 | 5.80 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.803571E+09 | 0.00 | 0.00 | 66393721.75 | 0.00 | 0.00 | 0.588180E+11 | 0.00 | 5.09 |
February | 0.408782E+09 | 0.00 | 0.00 | 66335987.72 | 0.00 | 0.00 | 0.496698E+11 | 0.00 | 5.25 |
March | 0.206066E+09 | 0.00 | 0.00 | 83557855.85 | 0.00 | 0.00 | 0.529371E+11 | 0.00 | 5.47 |
April | 4160199.36 | 0.109057E+09 | 0.00 | 0.100034E+09 | 0.00 | 0.00 | 0.354787E+11 | 0.00 | 5.93 |
May | 0.00 | 0.668170E+09 | 0.00 | 0.100855E+09 | 0.00 | 0.00 | 0.227593E+11 | 0.00 | 6.19 |
June | 0.00 | 0.205810E+10 | 0.00 | 81050725.92 | 0.00 | 0.00 | 0.123787E+11 | 0.00 | 5.93 |
July | 0.00 | 0.986192E+10 | 0.00 | 35618000.44 | 0.00 | 0.00 | 0.331270E+10 | 0.00 | 5.86 |
August | 0.00 | 0.261977E+10 | 0.00 | 76043040.99 | 0.00 | 0.00 | 0.107764E+11 | 0.00 | 6.01 |
September | 0.00 | 0.159433E+10 | 0.00 | 83815866.11 | 0.00 | 0.00 | 0.181975E+11 | 0.00 | 6.14 |
October | 3223238.15 | 0.257548E+09 | 0.00 | 95148157.57 | 0.00 | 0.00 | 0.401783E+11 | 0.00 | 5.85 |
November | 0.307082E+09 | 0.00 | 0.00 | 74206249.13 | 0.00 | 0.00 | 0.534160E+11 | 0.00 | 5.31 |
December | 0.103527E+10 | 0.00 | 0.00 | 63299344.66 | 0.00 | 0.00 | 0.553386E+11 | 0.00 | 5.01 |
Annual Sum or Average | 0.276816E+10 | 0.171689E+11 | 0.00 | 0.926358E+09 | 0.00 | 0.00 | 0.413261E+12 | 0.00 | 5.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 35618000.44 | 0.00 | 0.00 | 0.331270E+10 | 0.00 | 5.01 |
Maximum of Months | 0.103527E+10 | 0.986192E+10 | 0.00 | 0.100855E+09 | 0.00 | 0.00 | 0.588180E+11 | 0.00 | 6.19 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.109640E+09 | 0.00 | 0.00 | 0.783072E+11 | 0.00 | 22.00 |
February | 0.00 | 0.00 | 0.00 | 0.103161E+09 | 0.00 | 0.00 | 0.633911E+11 | 0.00 | 22.57 |
March | 0.00 | 0.00 | 0.00 | 0.122685E+09 | 0.00 | 0.00 | 0.635410E+11 | 0.00 | 23.01 |
April | 0.00 | 0.184857E+09 | 0.00 | 0.134897E+09 | 0.00 | 0.00 | 0.382127E+11 | 0.00 | 23.61 |
May | 0.00 | 0.108622E+10 | 0.00 | 0.125921E+09 | 0.00 | 0.00 | 0.216118E+11 | 0.00 | 23.67 |
June | 0.00 | 0.314039E+10 | 0.00 | 93104651.45 | 0.00 | 0.00 | 0.109182E+11 | 0.00 | 22.23 |
July | 0.00 | 0.128528E+11 | 0.00 | 34128317.79 | 0.00 | 0.00 | 0.271052E+10 | 0.00 | 22.10 |
August | 0.00 | 0.368585E+10 | 0.00 | 90305726.02 | 0.00 | 0.00 | 0.100045E+11 | 0.00 | 22.82 |
September | 0.00 | 0.244475E+10 | 0.00 | 0.104021E+09 | 0.00 | 0.00 | 0.176875E+11 | 0.00 | 23.76 |
October | 0.00 | 0.397389E+09 | 0.00 | 0.130141E+09 | 0.00 | 0.00 | 0.446486E+11 | 0.00 | 23.61 |
November | 0.00 | 0.00 | 0.00 | 0.114864E+09 | 0.00 | 0.00 | 0.678804E+11 | 0.00 | 22.69 |
December | 0.00 | 0.00 | 0.00 | 0.108021E+09 | 0.00 | 0.00 | 0.756407E+11 | 0.00 | 21.91 |
Annual Sum or Average | 0.00 | 0.237923E+11 | 0.00 | 0.127089E+10 | 0.00 | 0.00 | 0.494554E+12 | 0.00 | 22.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 34128317.79 | 0.00 | 0.00 | 0.271052E+10 | 0.00 | 21.91 |
Maximum of Months | 0.00 | 0.128528E+11 | 0.00 | 0.134897E+09 | 0.00 | 0.00 | 0.783072E+11 | 0.00 | 23.76 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.153222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116670E+09 | 0.00 | 0.00 | 1.06 |
February | 0.124696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125770E+09 | 0.00 | 0.00 | 1.07 |
March | 0.127504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67662979.54 | 0.00 | 0.00 | 1.08 |
April | 0.781962E+10 | 13502292.32 | 0.00 | 403262.14 | 15682409.11 | 0.00 | 0.128624E+09 | 0.00 | 1.09 |
May | 0.359704E+10 | 0.168305E+09 | 0.00 | 4439733.77 | 20808035.37 | 0.00 | 0.111183E+10 | 0.00 | 1.10 |
June | 0.695247E+09 | 0.646454E+09 | 0.00 | 9666696.99 | 1886954.48 | 0.00 | 0.180282E+10 | 0.00 | 1.13 |
July | 0.130584E+09 | 0.209923E+10 | 0.00 | 4266582.61 | 0.338584E+09 | 0.00 | 0.528190E+09 | 0.00 | 1.12 |
August | 0.998484E+09 | 0.661185E+09 | 0.00 | 7543198.76 | 57988964.06 | 0.00 | 0.121719E+10 | 0.00 | 1.13 |
September | 0.270078E+10 | 0.391722E+09 | 0.00 | 5783093.95 | 54122260.03 | 0.00 | 0.112972E+10 | 0.00 | 1.15 |
October | 0.881776E+10 | 63348335.28 | 0.00 | 1401453.37 | 6532098.13 | 0.00 | 0.343748E+09 | 0.00 | 1.10 |
November | 0.134087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3956058.58 | 0.00 | 0.00 | 1.08 |
December | 0.142708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.610520E+09 | 0.00 | 0.00 | 1.06 |
Annual Sum or Average | 0.929811E+11 | 0.404374E+10 | 0.00 | 33504021.58 | 0.495604E+09 | 0.924578E+09 | 0.626213E+10 | 0.00 | 1.10 |
Minimum of Months | 0.130584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 |
Maximum of Months | 0.153222E+11 | 0.209923E+10 | 0.00 | 9666696.99 | 0.338584E+09 | 0.610520E+09 | 0.180282E+10 | 0.00 | 1.15 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.190856E+12 | 0.336908E+10 | 0.148666E+12 | 0.687220E+12 | 0.113513E+12 |
February | 0.198187E+12 | 0.289671E+10 | 0.115463E+12 | 0.548888E+12 | 0.143003E+12 |
March | 0.318046E+12 | 0.296755E+10 | 0.108189E+12 | 0.520519E+12 | 0.201824E+12 |
April | 0.330189E+12 | 0.179197E+10 | 0.578053E+11 | 0.296335E+12 | 0.440744E+12 |
May | 0.362396E+12 | 0.970532E+09 | 0.277902E+11 | 0.166200E+12 | 0.685434E+12 |
June | 0.344684E+12 | 0.215581E+09 | 0.121738E+10 | 0.458661E+11 | 0.880686E+12 |
July | 0.333664E+12 | -994998105.5 | -0.365092E+11 | -0.154747E+12 | 0.109243E+13 |
August | 0.303504E+12 | -116711974.6 | 23381691.37 | 0.983052E+10 | 0.921666E+12 |
September | 0.259585E+12 | 0.374152E+09 | 0.156474E+11 | 0.996534E+11 | 0.773989E+12 |
October | 0.243791E+12 | 0.170829E+10 | 0.636050E+11 | 0.329507E+12 | 0.448569E+12 |
November | 0.187685E+12 | 0.291254E+10 | 0.117822E+12 | 0.578946E+12 | 0.177955E+12 |
December | 0.154546E+12 | 0.364947E+10 | 0.161324E+12 | 0.754361E+12 | 0.984822E+11 |
Annual Sum or Average | 0.322713E+13 | 0.197442E+11 | 0.781043E+12 | 0.388258E+13 | 0.597830E+13 |
Minimum of Months | 0.154546E+12 | -994998105.5 | -0.365092E+11 | -0.154747E+12 | 0.984822E+11 |