Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745

Simulation Timestamp: 2023-10-16 09:03:03


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 9193.99 810.38 810.38
Net Site Energy 9193.99 810.38 810.38
Total Source Energy 22866.57 2015.51 2015.51
Net Source Energy 22866.57 2015.51 2015.51


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 392.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1689.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 543.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 174.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1728.14 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 641.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 611.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 134.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 150.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 475.79 819.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 43.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 6193.13 3000.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 392.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 1689.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 543.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 174.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 952.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 8.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 4.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 22.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 616.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 611.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 134.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 150.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.75 819.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
  Other 385.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 7.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 15.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 20.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 392.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 1689.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 543.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 174.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1728.14 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 641.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 611.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 134.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 150.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 475.79 819.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 43.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 63.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 256.60 106.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 225.97 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 545.88 264.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 63.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 256.60 106.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 225.97 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 545.88 264.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 6193.126 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 6193.126 100.00
     
Total On-Site and Utility Electric Sources 6193.126 100.00
Total Electricity End Uses 6193.126 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 499.55 64.66
Air to Air Heat Recovery for Heating 272.99 35.34
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 772.53 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 76.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 7330.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWHSYSLAUNDRY HPWH TANK | SWHSYS1 HPWH TANK |

DaylightingReportMonthly

| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| SWHSYS1 HPWH FAN | SWHSYSLAUNDRY HPWH FAN | FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02
RunPeriod RUNPERIOD 1
Weather File Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Latitude [deg] 32.17
Longitude [deg] -110.9
Elevation [m] 809.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 5.9798 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 8.7295 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 8.7295 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 4.1656 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 3.6813 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 5.1344 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 8.3313 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 8.1375 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 3.9719 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 3.9719 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 3.9719 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 3.9719 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 3.9719 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 3.9719 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 3.9719 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 3.9719 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 3.9719 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 3.9719 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 8.3313 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 8.3313 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 10.5594 4.65 2931.5031
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 3.9719 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 5.2589 7.07 41.0437
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 5.2589 7.07 41.0437
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 5.9798 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 8.7295 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 8.7295 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 4.1656 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 3.6813 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 5.1344 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 8.3313 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 8.1375 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 3.9719 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 3.9719 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 3.9719 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 3.9719 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 3.9719 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 3.9719 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 3.9719 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 3.9719 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 3.9719 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 3.9719 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 8.3313 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 8.3313 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 10.5594 4.65 2931.5031  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 3.9719 18.58 0.0000  
Total 11345.29             5.2589 3.54 41.0437  
Conditioned Total 11345.29             5.2589 3.54 41.0437  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 3.3293 8.82 37.1717
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 29-JUN-19:30 07-DEC-20:00 - - - - - - - - - - 24-JAN-21:00
Heating 0.00 127860.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 163272.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 45424.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 11096.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 87982.85 89710.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 31572.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 40833.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 6314.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 39568.85 80105.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 1670.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 437675.20 297676.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 127860.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 163272.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 45424.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 11096.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 58308.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 49984.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 277.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 156.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1268.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 30153.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 150.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 40833.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 6314.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 3932.42 80105.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 241.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 769.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 660.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 425.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 5349.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1722.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 552.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5473.02 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2031.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1936.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 427.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 475.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 1506.82 888.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 138.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 19613.63 3252.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 37.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 471.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 151.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 48.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 482.40 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 179.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 170.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 37.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 41.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 132.81 78.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 12.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1728.79 286.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 37.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 471.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 151.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 48.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 482.40 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 179.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 170.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 37.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 41.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 132.81 78.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 12.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1728.79 286.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.35 0.641157 0.500000 1.18 1.00 0.500000 0.000594 0.000049 1.18 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.368816 0.138574 0.500000 0.184408 0.500000 0.500000 0.002749 0.000029 0.184408 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.256356 0.230865 0.500000 0.128178 0.615640 0.500000 0.001650 0.000013 0.128178 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.246191 0.508359 0.500000 0.123095 1.00 0.500000 0.000749 0.000020 0.123095 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.135714 0.532048 0.500000 0.067857 1.00 0.500000 0.000716 0.000012 0.067857 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.64 0.064844 0.500000 1.82 0.500000 0.500000 0.023316 0.000096 1.82 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.56 0.092187 0.500000 0.780549 0.500000 0.500000 0.004133 0.000086 0.780549 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 5.15 0.193547 0.500000 2.58 0.516125 0.500000 0.001969 0.000238 2.58 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.40 0.845454 0.500000 0.701934 1.00 0.500000 0.000451 0.000105 0.701934 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.43 0.104097 0.500000 1.21 0.500000 0.500000 0.003660 0.000099 1.21 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.54 0.099330 0.500000 1.27 0.500000 0.500000 0.003836 0.000102 1.27 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.42 0.058618 0.500000 1.21 0.500000 0.500000 0.011690 0.000071 1.21 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.806287 0.389488 0.500000 0.403144 1.00 0.500000 0.000978 0.000067 0.403144 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 5636.53 0.000049 117.54
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 3350.08 0.000029 81.91
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1466.36 0.000013 32.96
MECH_FLR_1 VAV BOX REHEAT COIL 2260.59 0.000020 55.41
STORAGE_FLR_1 VAV BOX REHEAT COIL 1335.69 0.000012 33.32
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 10927.93 0.000096 230.91
CAFE_FLR_1 VAV BOX REHEAT COIL 9799.95 0.000086 223.27
LOBBY_FLR_1 VAV BOX REHEAT COIL 27159.03 0.000238 604.15
ROOM_1_FLR_3 FAN COIL HEATING COIL 5394.73 0.000047 154.17
ROOM_2_FLR_3 FAN COIL HEATING COIL 5398.46 0.000047 154.28
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 30986.17 0.000271 885.50
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 31074.58 0.000272 888.02
ROOM_5_FLR_3 FAN COIL HEATING COIL 5386.51 0.000047 153.93
ROOM_6_FLR_3 FAN COIL HEATING COIL 5390.25 0.000047 154.04
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 12031.39 0.000105 290.24
ROOM_1_FLR_6 FAN COIL HEATING COIL 1639.59 0.000014 46.85
ROOM_2_FLR_6 FAN COIL HEATING COIL 1640.02 0.000014 46.87
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 7877.01 0.000069 225.09
BANQUET_FLR_6 VAV BOX REHEAT COIL 11271.28 0.000099 247.11
DINING_FLR_6 VAV BOX REHEAT COIL 11669.80 0.000102 255.52
KITCHEN_FLR_6 VAV BOX REHEAT COIL 8098.04 0.000071 172.44
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 7641.14 0.000067 188.78
VAV WITH REHEAT HEATING COIL 123843.92 0.001083 2173.01
FLR_3_DOAS HEATING COIL 10951.44 0.000096 192.16
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ZoneExhaust

User-Specified Maximum Flow Rate [m3/s]
LOBBY_FLR_1 EXHAUST FAN 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 1.20 0.000047 0.000428
ROOM_2_FLR_3 FAN COIL 1.19 0.000047 0.000424
ROOM_3_MULT19_FLR_3 FAN COIL 6.55 0.000271 0.002333
ROOM_4_MULT19_FLR_3 FAN COIL 7.09 0.000272 0.002620
ROOM_5_FLR_3 FAN COIL 1.05 0.000047 0.000374
ROOM_6_FLR_3 FAN COIL 1.04 0.000047 0.000371
ROOM_1_FLR_6 FAN COIL 0.320201 0.000014 0.000114
ROOM_2_FLR_6 FAN COIL 0.317616 0.000014 0.000113
ROOM_3_MULT9_FLR_6 FAN COIL 1.40 0.000069 0.000504
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 1.20
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 1.19
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 6.55
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 7.09
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 1.05
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 1.04
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.320201
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.317616
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 1.40
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 21.74 6.70 0.008478 12.80 0.008478 0.000428 1.20  
ROOM_2_FLR_3 FAN COIL COOLING COIL 21.74 6.70 0.008477 12.80 0.008477 0.000424 1.19  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 21.74 6.70 0.008415 12.80 0.008415 0.002333 6.55  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 21.74 6.70 0.008634 12.80 0.008500 0.002620 7.09  
ROOM_5_FLR_3 FAN COIL COOLING COIL 21.74 6.70 0.008473 12.80 0.008473 0.000374 1.05  
ROOM_6_FLR_3 FAN COIL COOLING COIL 21.74 6.70 0.008473 12.80 0.008473 0.000371 1.04  
ROOM_1_FLR_6 FAN COIL COOLING COIL 21.74 6.70 0.008479 12.80 0.008479 0.000114 0.320201  
ROOM_2_FLR_6 FAN COIL COOLING COIL 21.74 6.70 0.008479 12.80 0.008479 0.000113 0.317616  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21.74 6.70 0.008541 12.80 0.008500 0.000504 1.40  
VAV WITH REHEAT COOLING COIL 32.44 6.70 0.007619 10.79 0.007619 0.019984 23.20 559492.50
FLR_3_DOAS COOLING COIL 40.80 6.70 0.005631 11.84 0.005631 0.002355 2.05 65945.86
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 11.65 11.65 23.31 11.65 23.20 23.20 0.300000 0.502366 23.20
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 23.20  
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV WITH REHEAT OA HEAT RECOVERY 11.66
FLR_3_DOAS OA HEAT RECOVERY 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 23.20
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.019984 0.000024
VAV WITH REHEAT_HEATC_CONTROLLER 0.001083  
FLR_3_DOAS_COOLC_CONTROLLER 0.002355 0.000202
FLR_3_DOAS_HEATC_CONTROLLER 0.000096  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:WaterHeating:AirToWaterHeatPump:Pumped

Design Size Rated Evaporator Air Flow Rate [m3/s] Design Size Rated Condenser Water Flow Rate [m3/s]
SWHSYSLAUNDRY HPWH DXCOIL 4.90 0.004370
SWHSYS1 HPWH DXCOIL 3.87 0.003451
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:SystemModel

Design Size Design Maximum Air Flow Rate [m3/s] Design Electric Power Consumption [W]
SWHSYSLAUNDRY HPWH FAN 4.90 700.51
SWHSYS1 HPWH FAN 3.87 553.22
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:HeatPump:PumpedCondenser

Condenser water flow rate [m3/s] Evaporator air flow rate [m3/s]
SWHSYS1 HPWH 0.003451 3.87
SWHSYSLAUNDRY HPWH 0.004370 4.90
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.029621 6043.44  
HEATSYS1 PUMP 0.002994 892.73 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.002994 0.359278
COOLSYS1 0.029621 3.55
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 342230.51 342230.51 0.002994
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.029621 4184.08
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.029621 829321.15 829958.35 94.62
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Stratified

Use Side Design Flow Rate [m3/s]
SWHSYS1 HPWH TANK 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 20.90 15.40 11.90 14.80 12.70 15.40 23.30 26.30 31.20 30.40 29.80 27.80


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 32.17 -110.88 -7.00 809.00 91976 1.0932


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 21.66 19.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 5.980 5.380 0.000 0.000 0.000 0.000 11.360 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 8.730 10.760 0.000 0.000 0.000 0.000 19.490 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 8.730 10.760 0.000 0.000 0.000 0.000 19.490 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 4.166 5.380 0.000 0.000 0.000 0.000 9.546 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 3.681 2.690 0.000 0.000 0.000 0.000 6.371 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 5.134 61.680 535.850 0.000 0.000 0.000 602.664 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 8.331 5.380 0.000 0.000 0.000 0.000 13.711 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 8.138 8.070 0.000 0.000 0.000 0.000 16.208 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 3.972 6.750 0.000 0.000 0.000 0.000 10.722 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 3.972 6.750 0.000 0.000 0.000 0.000 10.722 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 3.972 10.520 0.000 0.000 0.000 0.000 14.492 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 3.972 10.520 0.000 0.000 0.000 0.000 14.492 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 3.972 6.750 0.000 0.000 0.000 0.000 10.722 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 3.972 6.750 0.000 0.000 0.000 0.000 10.722 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 3.972 0.000 0.000 0.000 0.000 0.000 3.972 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 3.972 6.750 0.000 0.000 0.000 0.000 10.722 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 3.972 6.750 0.000 0.000 0.000 0.000 10.722 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 3.972 10.520 0.000 0.000 0.000 0.000 14.492 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 8.331 67.820 0.000 0.000 0.000 0.000 76.151 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 8.331 67.820 0.000 0.000 0.000 0.000 76.151 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 10.559 512.243 2419.260 0.000 0.000 0.000 2942.062 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 3.972 0.000 0.000 0.000 0.000 0.000 3.972 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 11832.934 5.980 111.108 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 11832.934
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 585.501 8.730 54.068 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 585.501
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 678.012 8.730 54.068 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 678.012
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 684.177 4.166 257.985 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 684.177
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 348.833 3.681 170.996 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 348.833
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 400.685 5.134 47.701 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 400.685
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 1573.457 8.331 11.057 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1573.457
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 10645.380 8.138 25.200 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 10645.380
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 154.991 3.972 103.327 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 154.991
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 154.973 3.972 103.315 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 154.973
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 97.406 3.972 64.937 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 97.406
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 97.432 3.972 64.955 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 97.432
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 154.991 3.972 103.327 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 154.991
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 154.973 3.972 103.315 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 154.973
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 1546.669 3.972 73.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1546.669
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 154.991 3.972 103.327 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 154.991
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 154.973 3.972 103.315 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 154.973
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 97.432 3.972 64.955 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 97.432
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 2763.123 8.331 11.057 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2763.123
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 2763.123 8.331 11.057 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2763.123
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1090.832 10.559 49.053 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1090.832
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 1636.910 3.972 73.801 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1636.910


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 277.500 2.686 12.479 0.000 0.250 0.000 0.750 ReachInFreezer 277.500 277.500
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 156.700 1.517 7.046 0.000 0.250 0.000 0.750 ReachInRefrigerator 156.700 156.700


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.760 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 1.287 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 1.608 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 1.684 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 1.370 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 1.442 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.5681
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.6100
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.4545
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.4264
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.5624
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.5260
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.7602615 1.7602615 1.7602615  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
21 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
22 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
23 0 21.361010 0.87247630E-01 5.4456762  
24 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
25 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
26 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
27 0 21.361010 0.87247630E-01 5.4456762  
28 9 0.16691074E-14 0.45207920E-16 -0.13282787E-09 -0.59403108E-17
29 8 0.19494068E-07 0.16957001E-12 0.35230437E-03 -0.22165426E-09
30 7 -0.11479370E-01 0.90467759E-08 -0.21987867E-01 0.13052461E-03
31 6 0.38463807 0.31869432E-05 0.45441076 -0.45036152E-02
32 5 -4.9884079 0.12028467E-03 -4.3052891 0.60677235E-01
33 4 32.108494 0.99355415E-03 20.908458 -0.41024850
34 3 -109.32288 0.21841230E-02 -54.572312 1.4876971
35 2 195.24423 0.12380226E-02 76.910992 -2.8707534
36 1 -170.46733 0.13310261E-03 -54.975783 2.7333683
37 0 57.057407 0.76355891E-06 15.605832  
38 9 0.14115123E-14 0.53960859E-16 -0.11739578E-09 -0.22900007E-17
39 8 0.17311930E-07 0.20639465E-12 0.32798840E-03 -0.19684260E-09
40 7 -0.10748946E-01 0.11327704E-07 -0.20934514E-01 0.12221941E-03
41 6 0.36478417 0.40360747E-05 0.43737925 -0.42695883E-02
42 5 -4.7945715 0.15382307E-03 -4.1739388 0.58273831E-01
43 4 31.250576 0.12816568E-02 20.393829 -0.39885853
44 3 -107.49604 0.28390629E-02 -53.554356 1.4613070
45 2 193.43186 0.16201491E-02 75.979619 -2.8419759
46 1 -169.79719 0.17527083E-03 -54.709122 2.7216233
47 0 57.057407 0.10123612E-05 15.653272  
48 9 0.65135446E-15 0.56204292E-16 -0.11372497E-09 -0.53489081E-17
49 8 0.16791160E-07 0.21454591E-12 0.32203280E-03 -0.19092129E-09
50 7 -0.10569524E-01 0.11862766E-07 -0.20675571E-01 0.12017931E-03
51 6 0.35990649 0.42391557E-05 0.43318136 -0.42120931E-02
52 5 -4.7469406 0.16196889E-03 -4.1415055 0.57683257E-01
53 4 31.039704 0.13525358E-02 20.266625 -0.39605902
54 3 -107.04684 0.30019179E-02 -53.302690 1.4548183
55 2 192.98603 0.17160237E-02 75.749609 -2.8348971
56 1 -169.63227 0.18593554E-03 -54.643729 2.7187328
57 0 57.057407 0.10758168E-05 15.665287  
58 9 0.10314710E-14 0.47183642E-16 -0.12881513E-09 -0.40099708E-17
59 8 0.18927665E-07 0.17950474E-12 0.34608657E-03 -0.21521408E-09
60 7 -0.11292911E-01 0.96443222E-08 -0.21719088E-01 0.12840450E-03
61 6 0.37957032 0.34070209E-05 0.45007157 -0.44438791E-02
62 5 -4.9389364 0.12890179E-03 -4.2718596 0.60063826E-01
63 4 31.889569 0.10670331E-02 20.777560 -0.40734193
64 3 -108.85680 0.23501275E-02 -54.313423 1.4809641
65 2 194.78196 0.13343675E-02 76.673975 -2.8634131
66 1 -170.29645 0.14368413E-03 -54.907648 2.7303734
67 0 57.057407 0.82565881E-06 15.617726  
68 9 0.86975537E-15 0.52023775E-16 -0.12536948E-09 -0.54620444E-17
69 8 0.18440443E-07 0.18784465E-12 0.34068694E-03 -0.20967419E-09
70 7 -0.11130813E-01 0.10155400E-07 -0.21485363E-01 0.12656138E-03
71 6 0.37516444 0.35965268E-05 0.44629465 -0.43919449E-02
72 5 -4.8959230 0.13636263E-03 -4.2427425 0.59530495E-01
73 4 31.699203 0.11309484E-02 20.663505 -0.40481456
74 3 -108.45147 0.24950915E-02 -54.087828 1.4751087
75 2 194.37988 0.14187814E-02 76.467519 -2.8570287
76 1 -170.14779 0.15298304E-03 -54.848449 2.7277680
77 0 57.057407 0.88039223E-06 15.628184  
78 7 -0.15963512E-14 -0.15187529E-16 -0.22427203E-13 0.56155309E-15
79 6 0.17983713E-10 0.23594901E-11 0.52322926E-09 -0.18637893E-10
80 5 -0.60139213E-07 0.11510628E-07 -0.21924491E-05 0.17161312E-06
81 4 0.62746279E-04 0.43399923E-05 0.17681060E-02 -0.28244642E-03
82 3 -0.90508353E-02 0.15320797E-03 -0.21560640 0.43341486E-01
83 2 0.12836503 0.66328859E-03 2.9007871 -0.61911613
84 1 -0.32478029 0.41934727E-03 -7.1379041 1.5697129
85 0 0.20664896 0.54311639E-05 4.4522013  
86 7 -0.22427203E-13 -0.15187529E-16 -0.15963512E-14 0.56155309E-15
87 6 0.52322926E-09 0.23594901E-11 0.17983713E-10 -0.18637893E-10
88 5 -0.21924491E-05 0.11510628E-07 -0.60139213E-07 0.17161312E-06
89 4 0.17681060E-02 0.43399923E-05 0.62746279E-04 -0.28244642E-03
90 3 -0.21560640 0.15320797E-03 -0.90508353E-02 0.43341486E-01
91 2 2.9007871 0.66328859E-03 0.12836503 -0.61911613
92 1 -7.1379041 0.41934727E-03 -0.32478029 1.5697129
93 0 4.4522013 0.54311639E-05 0.20664896  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
103 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
104 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
105 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
106 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
107 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
108 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
109 0 1.0055995 0.48413807E-04 60.838472  
110 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
111 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
112 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
113 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
114 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
115 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
116 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
117 0 1.0055995 0.48413807E-04 60.838472  
118 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
119 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
120 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
121 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
122 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
123 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
124 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
125 0 1.0055995 0.48413807E-04 60.838472  
126 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
127 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
128 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
129 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
130 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
131 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
132 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
133 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.4619_SHGC_0.25 37 1 VerySmooth 2.626 2.626 1.000 0.251    
2 RESWINDOW_U_0.4619_SHGC_0.25 38 1 VerySmooth 2.626 2.626 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   2.51406E-002 0.16139 0.61584 0.61584 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11972 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   2.51406E-002 0.16139 0.61584 0.61584 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11972 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CAFE_FLR_1 1 0
2 LOBBY_FLR_1 1 0
3 BANQUET_FLR_6 1 0
4 DINING_FLR_6 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CAFE_FLR_1 0  
2 LOBBY_FLR_1 0  
3 BANQUET_FLR_6 0  
4 DINING_FLR_6 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 2.320
2 RACK2 1 0 Zone Air-Cooled 6.980


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473


Heat Pump Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor "DX Coil Total Cooling Rate {W HPWH Only}"
1 WaterHeater:HeatPump:PumpedCondenser SWHSYSLAUNDRY HPWH 1.1400 74956.0 48.891 1.6882 76621  
2 WaterHeater:HeatPump:PumpedCondenser SWHSYS1 HPWH 2.8400 61437.9 4.627 9.4219 53264  


Water Heater Stratified Node Information

Node Number Height {m} Volume {m3} Maximum Capacity {W} Off-Cycle UA {W/K} On-Cycle UA {W/K} Number Of Inlets Number Of Outlets
1 1 0.2683 0.4733 0.000 2.4569 2.4569 0 1
2 2 0.2683 0.4733 33820.860 1.5573 1.5573 0 0
3 3 0.2683 0.4733 0.000 1.5573 1.5573 0 0
4 4 0.2683 0.4733 0.000 1.5573 1.5573 0 0
5 5 0.2683 0.4733 0.000 1.5573 1.5573 0 1
6 6 0.2683 0.4733 0.000 2.4569 2.4569 2 0


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 7.058E-002 1.052E-003 5.193E-004 0.956 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 2.724E-002 3.507E-004 9.551E-004 0.319 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 6.438E-002 3.920E-004 1.025E-003 0.356 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 3.715E-002 3.920E-004 8.507E-004 0.356 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 8.791E-002 1.127E-003 1.002E-003 1.023 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 0.156 8.261E-004 4.549E-004 0.751 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.446 3.407E-004 6.517E-004 0.310 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 4.096E-002 1.050E-003 1.025E-003 1.240 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 4.095E-002 1.050E-003 1.025E-003 1.240 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 1.143E-002 4.660E-004 1.025E-003 0.550 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.143E-002 4.660E-004 1.025E-003 0.550 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 4.096E-002 1.050E-003 1.025E-003 1.240 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 4.095E-002 1.050E-003 1.025E-003 1.240 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 4.953E-002 1.272E-004 1.025E-003 0.150 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 4.096E-002 1.050E-003 5.186E-004 1.240 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 4.095E-002 1.050E-003 5.186E-004 1.240 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 2.096E-002 8.543E-004 4.660E-004 1.009 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 0.100 3.015E-004 2.330E-004 0.356 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 0.100 3.015E-004 2.330E-004 0.356 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 8.953E-002 8.667E-004 4.697E-004 1.024 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 8.763E-002 2.126E-004 1.761E-004 0.251 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 8.7310E-002
2 Clear Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 3.8709E-002
3 Clear Turbid Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 9.7087E-002
4 Clear Turbid Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 4.2189E-002
5 Intermediate Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 6.5660E-002
6 Intermediate Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 2.4295E-002
7 Overcast Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 2.6511E-002
8 Overcast Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 8.7811E-003
9 Clear Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 9.8430E-002
10 Clear Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 4.7382E-002
11 Clear Turbid Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1097
12 Clear Turbid Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 5.1591E-002
13 Intermediate Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 7.2656E-002
14 Intermediate Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 3.0684E-002
15 Overcast Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 2.9789E-002
16 Overcast Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 1.2036E-002
17 Clear Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.1147E-002
18 Clear Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.2078E-002
19 Clear Turbid Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.6306E-002
20 Clear Turbid Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 9.1307E-003
21 Intermediate Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.5594E-002
22 Intermediate Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 6.2294E-003
23 Overcast Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.6108E-002
24 Overcast Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 9.2309E-003
25 Clear Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.1147E-002
26 Clear Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.2078E-002
27 Clear Turbid Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.6306E-002
28 Clear Turbid Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 9.1307E-003
29 Intermediate Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.5594E-002
30 Intermediate Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 6.2294E-003
31 Overcast Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.6108E-002
32 Overcast Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 9.2309E-003


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 29385.03001 29385.03001 2.35179 2.35179 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 21:40:00 32.15500 5.61779E-003 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 0.85446   00:10:00 0.50000 4.31558E-003 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 4608.12023 4608.12023 0.36882 0.36882 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 40.80000 5.63111E-003 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 2467.08866 2467.08866 0.11647 0.11647 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 0.50000 4.31558E-003 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 3202.81781 3202.81781 0.25636 0.25636 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 37.27550 5.62563E-003 77.66889 12.54000 9.17347E-002 0.00000
6 RETAIL_2_FLR_1 Heating 852.61573 852.61573 4.02546E-002 9.17347E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 0.50000 4.31558E-003 77.66889 12.54000 9.17347E-002 0.00000
7 MECH_FLR_1 Cooling 3076.51658 3076.51658 0.24619 0.24619 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 36.94300 5.62512E-003 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 1671.28756 1671.28756 7.89064E-002 7.89064E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 0.50000 4.31558E-003 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1695.93451 1695.93451 0.13571 0.13571 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 38.05133 5.62683E-003 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 1010.82151 1010.82151 4.77239E-002 5.77652E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 0.50000 4.31558E-003 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 45472.57422 45472.57422 3.63910 3.63910 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 40.00200 5.62986E-003 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 2218.13291 2218.13291 0.10472 0.10472 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 0.50000 4.31558E-003 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 19487.96049 19487.96049 1.56110 1.56110 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 40.80000 5.63111E-003 188.86188 142.30000 0.67639 0.00000
14 CAFE_FLR_1 Heating 6062.09902 6062.09902 0.28620 0.67639 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 0.50000 4.31558E-003 188.86188 142.30000 0.67639 0.00000
15 LOBBY_FLR_1 Cooling 64328.34052 64328.34052 5.15037 5.15037 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 40.80000 5.63111E-003 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 14828.15282 14828.15282 0.70008 1.89399 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 0.50000 4.31558E-003 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 11127.85728 11127.85728 1.20000 1.20000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 39.11533 5.62848E-003 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 5394.85623 5394.85623 0.25619 0.25619 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 0.50000 4.31558E-003 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 11046.95574 11046.95574 1.19128 1.19128 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 38.93800 5.62821E-003 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 5398.58833 5398.58833 0.25637 0.25637 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 0.50000 4.31558E-003 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 60724.71143 60724.71143 6.54831 6.54831 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 40.80000 5.63111E-003 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 30986.53334 30986.53334 1.47154 1.47154 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 0.50000 4.31558E-003 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 65736.33021 65736.33021 7.08930 7.08930 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 40.26800 5.63027E-003 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 31074.94285 31074.94285 1.47574 1.47574 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 0.50000 4.31558E-003 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 9731.70093 9731.70093 1.04944 1.04944 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 36.74350 5.62481E-003 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 5386.63968 5386.63968 0.25580 0.25580 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 0.50000 4.31558E-003 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 9664.76972 9664.76972 1.04222 1.04222 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 36.41100 5.62429E-003 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 5390.37386 5390.37386 0.25598 0.25598 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 0.50000 4.31558E-003 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 17541.62489 17541.62489 1.40387 1.40387 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 40.40100 5.63048E-003 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 8669.45538 8669.45538 0.40932 0.47476 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 2969.29324 2969.29324 0.32020 0.32020 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 39.11533 5.62848E-003 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 1639.63181 1639.63181 7.78623E-002 7.78623E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 0.50000 4.31558E-003 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2945.32337 2945.32337 0.31762 0.31762 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 38.93800 5.62821E-003 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 1640.05880 1640.05880 7.78826E-002 7.78826E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 0.50000 4.31558E-003 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 12979.35154 12979.35154 1.39971 1.39971 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 40.80000 5.63111E-003 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 7877.08900 7877.08900 0.37407 0.37407 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 30297.17293 30297.17293 2.42777 2.42777 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 40.66700 5.63090E-003 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 5456.83577 5456.83577 0.25763 1.18780 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 0.50000 4.31558E-003 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 31751.73870 31751.73870 2.54428 2.54428 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 40.66700 5.63090E-003 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 5576.22822 5576.22822 0.26327 1.18780 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 0.50000 4.31558E-003 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 30100.94432 30100.94432 2.41535 2.41535 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 39.60300 5.62924E-003 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 2324.30134 2324.30134 0.10972 0.36735 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 0.50000 4.31558E-003 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 10074.88827 10074.88827 0.80629 0.80629 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 40.80000 5.63111E-003 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 5709.86637 5709.86637 0.26958 0.26958 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 0.50000 4.31558E-003 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 500471.20 23.19723 23.19723 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 131007.29 7.36170 7.36170 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00
3 FLR_3_DOAS Cooling Sensible 63092.52 19.67809 2.05125 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 FLR_3_DOAS Heating Sensible 36503.53 4.50144 2.05125 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.35179
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.64116
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50000
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.17590
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.94238E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.93108E-005
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.17590
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5636.53228
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.93108E-005
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 117.54016
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.36882
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13857
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50000
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.18441
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.50000
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.74943E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.93079E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.18441
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3350.07529
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.93079E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 81.90666
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.25636
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.23087
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50000
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.12818
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.61564
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.65031E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.28284E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.12818
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1466.36278
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.28284E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 32.96455
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.24619
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.50836
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50000
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.12310
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.49471E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.97766E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.12310
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2260.59230
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.97766E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 55.41418
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.13571
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.53205
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50000
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 6.78572E-002
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.16101E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.16852E-005
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.78572E-002
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1335.69440
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.16852E-005
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 33.32443
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.63910
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.48440E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50000
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.81955
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.50000
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.33158E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.56023E-005
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.81955
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10927.93315
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.56023E-005
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 230.91395
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.56110
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.21869E-002
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50000
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.78055
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.50000
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.13291E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.57342E-005
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.78055
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9799.94702
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.57342E-005
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 223.26544
99 Fan:ZoneExhaust LOBBY_FLR_1 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.15037
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19355
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50000
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.57519
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51612
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.96852E-003
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.37599E-004
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.57519
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
110 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 27159.03141
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.37599E-004
113 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 604.15387
114 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
115 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.20000
116 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.20000
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.71954E-005
118 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.27596E-004
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.74179
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.47772E-003
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.47772E-003
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.27596E-004
125 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.20000
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5394.72927
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.71954E-005
128 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 154.16859
129 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
130 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.19128
131 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.19128
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.72281E-005
133 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.24487E-004
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.74179
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.47747E-003
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.47747E-003
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.24487E-004
140 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.19128
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5398.46129
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.72281E-005
143 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 154.27521
144 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
145 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 6.54831
146 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 6.54831
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.71081E-004
148 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.33314E-003
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.74198
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.41460E-003
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.41460E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.33314E-003
155 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 6.54831
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 30986.16828
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.71081E-004
158 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 885.49848
159 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
160 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 7.08930
161 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 7.08930
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.71854E-004
163 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.62002E-003
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.74107
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.63362E-003
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.62002E-003
170 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 7.08930
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 31074.57679
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.71854E-004
173 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 888.02437
174 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
175 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.04944
176 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.04944
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.71236E-005
178 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.73945E-004
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.74180
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.47339E-003
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.47339E-003
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.73945E-004
185 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.04944
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5386.51290
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.71236E-005
188 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 153.93385
189 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
190 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.04222
191 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.04222
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.71562E-005
193 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.71373E-004
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.74180
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.47308E-003
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.47308E-003
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.71373E-004
200 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.04222
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5390.24700
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.71562E-005
203 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 154.04053
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.40387
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.84545
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50000
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.70193
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.50645E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.05256E-004
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.70193
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
214 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12031.39344
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.05256E-004
217 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 290.24174
218 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
219 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.32020
220 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.32020
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.43439E-005
222 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.14097E-004
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.74178
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.47905E-003
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.47905E-003
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.14097E-004
229 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.32020
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1639.59447
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.43439E-005
232 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 46.85343
233 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
234 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.31762
235 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.31762
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.43476E-005
237 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.13176E-004
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.74178
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.47880E-003
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.47880E-003
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.13176E-004
244 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.31762
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1640.02146
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.43476E-005
247 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 46.86563
248 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
249 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.39971
250 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.39971
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 6.89115E-005
252 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 5.04386E-004
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.74140
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.54051E-003
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.04386E-004
259 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.39971
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 7877.01115
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 6.89115E-005
262 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 225.09365
263 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.42777
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10410
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50000
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.21388
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.50000
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.66005E-003
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.86061E-005
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.21388
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
273 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
274 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11271.28134
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.86061E-005
276 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 247.11456
277 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.54428
278 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.93297E-002
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50000
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.27214
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.50000
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.83571E-003
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.02093E-004
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.27214
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
287 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
288 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11669.80274
289 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.02093E-004
290 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 255.52270
291 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.41535
292 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 5.86184E-002
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50000
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.20768
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.50000
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.16905E-002
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.08452E-005
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.20768
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
301 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
302 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8098.03680
303 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.08452E-005
304 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 172.44332
305 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.80629
306 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.38949
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50000
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.40314
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.78208E-004
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.68480E-005
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.40314
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
315 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
316 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7641.13964
317 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.68480E-005
318 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 188.77997
319 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 11.65350
320 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 11.65350
321 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 23.30700
322 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 11.65350
323 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 23.19723
324 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 23.19723
325 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
326 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.50237
327 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
328 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
329 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
333 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
334 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
335 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 23.19723
336 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
337 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 23.19723
338 HeatExchanger:AirToAir:SensibleAndLatent VAV WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 11.66146
339 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 32.43996
340 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
341 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.78860
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.61887E-003
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.61887E-003
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 559492.50099
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.99838E-002
346 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 23.19723
347 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 123843.92334
348 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.08344E-003
349 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 2173.01460
350 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 23.19723
351 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.99838E-002
352 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 2.38289E-005
353 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.08344E-003
354 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
355 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
356 HeatExchanger:AirToAir:SensibleAndLatent FLR_3_DOAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.05125
357 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 40.80000
358 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
359 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.83593
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 5.63111E-003
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 5.63111E-003
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 65945.85541
363 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.35543E-003
364 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
365 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 10951.44367
366 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 9.58080E-005
367 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 192.15837
368 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
369 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 2.35543E-003
370 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 2.02167E-004
371 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 9.58080E-005
372 Coil:WaterHeating:AirToWaterHeatPump:Pumped SWHSYSLAUNDRY HPWH DXCOIL Design Size Rated Evaporator Air Flow Rate [m3/s] 4.90359
373 Coil:WaterHeating:AirToWaterHeatPump:Pumped SWHSYSLAUNDRY HPWH DXCOIL Design Size Rated Condenser Water Flow Rate [m3/s] 4.36989E-003
374 Fan:SystemModel SWHSYSLAUNDRY HPWH FAN Design Size Design Maximum Air Flow Rate [m3/s] 4.90359
375 Fan:SystemModel SWHSYSLAUNDRY HPWH FAN Design Electric Power Consumption [W] 700.51236
376 Coil:WaterHeating:AirToWaterHeatPump:Pumped SWHSYS1 HPWH DXCOIL Design Size Rated Evaporator Air Flow Rate [m3/s] 3.87257
377 Coil:WaterHeating:AirToWaterHeatPump:Pumped SWHSYS1 HPWH DXCOIL Design Size Rated Condenser Water Flow Rate [m3/s] 3.45109E-003
378 Fan:SystemModel SWHSYS1 HPWH FAN Design Size Design Maximum Air Flow Rate [m3/s] 3.87257
379 Fan:SystemModel SWHSYS1 HPWH FAN Design Electric Power Consumption [W] 553.22422
380 WaterHeater:HeatPump:PumpedCondenser SWHSYS1 HPWH Condenser water flow rate [m3/s] 3.45109E-003
381 WaterHeater:HeatPump:PumpedCondenser SWHSYS1 HPWH Evaporator air flow rate [m3/s] 3.87257
382 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 2.96214E-002
383 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 6043.44438
384 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 2.99398E-003
385 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.35928
386 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 2.99398E-003
387 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 892.72856
388 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
389 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 342230.51222
390 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 342230.51000
391 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 2.99398E-003
392 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 2.96214E-002
393 PlantLoop COOLSYS1 Plant Loop Volume [m3] 3.55457
394 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 2.96214E-002
395 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 4184.08038
396 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 2.96214E-002
397 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 829321.14812
398 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 829958.35000
399 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 94.61525
400 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
401 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
402 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
403 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
404 WaterHeater:Stratified SWHSYS1 HPWH TANK Use Side Design Flow Rate [m3/s] 3.75036E-004
405 WaterHeater:HeatPump:PumpedCondenser SWHSYSLAUNDRY HPWH Condenser water flow rate [m3/s] 4.36989E-003
406 WaterHeater:HeatPump:PumpedCondenser SWHSYSLAUNDRY HPWH Evaporator air flow rate [m3/s] 4.90359


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 5665.88
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 3364.99
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1473.46
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 2270.64
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 1341.54
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 10984.24
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 9846.82
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 27291.59
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 5811.80
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 5815.82
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 33381.62
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 33476.85
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 5802.95
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 5806.97
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 12085.60
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 1766.30
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 1766.76
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 8485.72
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 11327.79
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 11728.37
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 8139.51
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 7674.86
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 99741.28
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 8820.06


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 19923.35 15527.68 4395.67 0.78 2762.10 28.01
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 19778.99 15415.14 4363.85 0.78 2742.31 27.81
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 109419.02 85229.29 24189.74 0.78 15494.90 157.16
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 120245.48 92664.37 27581.11 0.77 16359.72 165.93
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 17431.27 13584.93 3846.35 0.78 2420.05 24.55
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 17311.92 13491.87 3820.04 0.78 2403.72 24.38
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 5315.52 4142.81 1172.71 0.78 736.60 7.47
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 5272.74 4109.46 1163.28 0.78 730.73 7.41
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 23357.91 18143.07 5214.83 0.78 3203.76 32.49
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 660362.05 415215.44 245146.61 0.63 98541.05 999.46
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 54169.20 34464.63 19704.58 0.64 5364.64 54.41


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 4.32 14.74


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.940 0.824   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.760 1.760   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.287 1.079   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.608 1.296   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.608 1.296   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.608 1.296   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.608 1.296   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.442 1.186   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.442 1.186   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.442 1.186   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.442 1.186   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.442 1.186   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.684 1.345   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4619_SHGC_0.25 N/A 2.626 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 1.6385816137E-002 2.1092505897E-002 Pass Pass 4.1393240640E-003 1.2654183016E-002 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 4.5698354407E-002 6.5813946193E-002 Pass Pass 0.2104291494 1.0477230339 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 2.5564329664E-002 2.5044190596E-002 Pass Pass 5.7740496865E-003 1.4586561666E-002 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 2.7993814969E-003 6.9053129615E-003 Pass Pass 5.2107236045E-002 8.1931154934E-002 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 4.1425646909E-004 2.9684449150E-004 Pass Pass 0.1888917467 0.6584415041 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 6.6505901775E-002 0.1933371978 Pass Pass 1.9329361816E-002 5.2597062705E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 5.3204181543E-002 6.4679787164E-002 Pass Pass 1.3445612880E-002 1.8687098784E-002 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 3.4652393170E-002 3.6902953897E-002 Pass Pass 6.3246247878E-003 1.3408879618E-002 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 5.5770722794E-002 0.1974577480 Pass Pass 0.2712098638 1.1950965840 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 7.6573488596E-002 0.2280953177 Pass Pass 0.3310390111 2.2228382739 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 2.5481038942E-002 4.7747269011E-002 Pass Pass 6.9717769433E-002 0.2238999083 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 1.5811338211E-002 3.8614702510E-002 Pass Pass 0.1573466878 0.4424018127 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 5.2451808803E-002 0.1906400833 Pass Pass 0.1560908620 0.3801852792 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 4.0923542155E-002 0.1199091981 Pass Pass 0.4090825797 3.3815343619 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 8.3381649544E-003 9.4028255897E-003 Pass Pass 1.9962598074E-002 3.7717984043E-002 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 6.2682966019E-002 0.2279912310 Pass Pass 0.2128634877 0.5544882704 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 8.7858497188E-002 0.2556859101 Pass Pass 0.2356822958 0.9534273750 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 7.5182590585E-002 0.2808797704 Pass Pass 0.2117299230 0.6579511489 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 4.2554044753E-002 8.0848776749E-002 Pass Pass 1.0000935717E-002 2.9522484067E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 3.3523832038E-002 6.6066376824E-002 Pass Pass 1.1232881754E-002 3.4291090152E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 3.0629308903E-002 9.2616368164E-002 Pass Pass 2.1868903405E-002 4.1181935411E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 8.8333161233E-003 1.4491895165E-002 Pass Pass 0.1071777039 0.2425496753 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 2713.05 74.05 440.84 2306.58 7457.42 12991.95



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 0.50 0.00 0.50 Wetbulb [C] 2.10 140.00
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 40.80 13.30 18.50 Wetbulb [C] 4.80 310.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 3.00 2      
Feb 34.00 28      
Mar 40.00 18      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 81.00 18      
Aug 71.00 20      
Sep 27.00 12      
Oct 9.00 6      
Nov 35.00 14      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.845 0.940 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.079 1.287 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.079 1.287 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.079 1.287 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.079 1.287 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 1.079 1.287 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 1.079 1.287 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.55 0.221 0.228 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.137 1.370 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.137 1.370 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.137 1.370 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.137 1.370 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.137 1.370 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.137 1.370 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.137 1.370 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.137 1.370 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.137 1.370 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.137 1.370 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 1.296 1.608 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 1.296 1.608 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 1.296 1.608 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 1.296 1.608 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.186 1.442 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.186 1.442 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 1.186 1.442 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.186 1.442 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.186 1.442 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.345 1.684 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 1.345 1.684 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.55 0.221 0.228 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.55 0.221 0.228 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.186 0.196 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.186 0.196 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.186 0.196 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.186 0.196 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.186 0.196 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.186 0.196 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.186 0.196 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.186 0.196 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.186 0.196 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.186 0.196 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.185 0.196 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.185 0.196 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.185 0.196 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.188 0.196 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.4619_SHGC_0.25   23.26 0.00 0.00 23.26 23.26 2.626 0.251 0.251             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.4619_SHGC_0.25   65.50 0.00 0.00 65.50 65.50 2.626 0.251 0.251             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.4619_SHGC_0.25   85.08 0.00 0.00 85.08 85.08 2.626 0.251 0.251             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.4619_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.626 0.251 0.251             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.4619_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.626 0.251 0.251             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.4619_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.626 0.251 0.251             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.4619_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.626 0.251 0.251             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.4619_SHGC_0.25   3.68 0.00 0.00 3.68 279.56 2.626 0.251 0.251             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.4619_SHGC_0.25   3.68 0.00 0.00 3.68 279.65 2.626 0.251 0.251             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.4619_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.626 0.251 0.251             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.4619_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.626 0.251 0.251             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.4619_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.626 0.251 0.251             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.4619_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.626 0.251 0.251             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.4619_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 2.626 0.251 0.251             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.4619_SHGC_0.25   2.15 0.00 0.00 2.15 8.59 2.626 0.251 0.251             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.4619_SHGC_0.25   2.15 0.00 0.00 2.15 8.58 2.626 0.251 0.251             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.4619_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 2.626 0.251 0.251             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.4619_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.626 0.251 0.251             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.4619_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 2.626 0.251 0.251             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.4619_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.626 0.251 0.251             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.4619_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 2.626 0.251 0.251             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.4619_SHGC_0.25   6.74 0.00 0.00 6.74 60.70 2.626 0.251 0.251             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.4619_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 2.626 0.251 0.251             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.4619_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 2.626 0.251 0.251             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.4619_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.626 0.251 0.251             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.4619_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 2.626 0.251 0.251             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.4619_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.626 0.251 0.251             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.4619_SHGC_0.25   5.82 0.00 0.00 5.82 5.82 2.626 0.251 0.251             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.4619_SHGC_0.25   5.21 0.00 0.00 5.21 5.21 2.626 0.251 0.251             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.4619_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 2.626 0.251 0.251             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 2.626 0.251 0.251                      
North Total or Average             432.95 2.626 0.251 0.251                      
Non-North Total or Average             780.84 2.626 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.393 1.760 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 5.9798 1978.83 11832.93 LightsWired LTG_SCH_BASEMENT 45.99 168.00 45.94 0.0000 Y 102.03
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 8.7295 67.07 585.50 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 5.64
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 8.7295 77.67 678.01 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 6.53
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 4.1656 164.24 684.18 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 7.53
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 3.6813 94.76 348.83 LightsWired LTG_SCH_STORAGE 25.68 168.00 25.65 0.0000 Y 1.68
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 5.1344 78.04 400.68 LightsWired LTG_SCH_LAUNDRY 58.69 168.00 58.63 0.0000 Y 4.41
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 8.3313 188.86 1573.46 LightsWired LTG_SCH_DINING 58.69 168.00 39.51 0.0000 Y 11.67
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 8.1375 1308.19 10645.38 LightsWired LTG_SCH_LOBBY 58.69 168.00 55.43 0.0000 Y 110.76
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 3.9719 156.09 619.96 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 5.55
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 3.9719 156.07 619.89 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 5.55
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 3.9719 1863.81 7402.84 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 66.32
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 3.9719 1864.32 7404.86 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 66.33
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 3.9719 156.09 619.96 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 5.55
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 3.9719 156.07 619.89 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 5.55
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 3.9719 1557.62 6186.67 LightsWired LTG_SCH_CORRIDOR 44.02 168.00 43.97 0.0000 Y 51.06
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 3.9719 39.02 154.99 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.39
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 3.9719 39.02 154.97 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.39
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 3.9719 220.77 876.89 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 7.86
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 8.3313 331.66 2763.12 LightsWired LTG_SCH_DINING 58.69 168.00 49.56 0.0000 Y 25.71
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 8.3313 331.66 2763.12 LightsWired LTG_SCH_DINING 58.69 168.00 49.56 0.0000 Y 25.71
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 10.5594 103.30 1090.83 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 12.00
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 3.9719 412.12 1636.91 LightsWired LTG_SCH_CORRIDOR 44.02 168.00 43.97 0.0000 Y 13.51
Interior Lighting Total       5.2589 11345.29 59663.90               350.88


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
LOBBY_FLR_1_DAYLREFPT1 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.07 10645.38 745.18
LOBBY_FLR_1_DAYLREFPT2 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.07 10645.38 745.18
CAFE_FLR_1_DAYLREFPT1 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1573.46 613.65
CAFE_FLR_1_DAYLREFPT2 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1573.46 613.65
DINING_FLR_6_DAYLREFPT1 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2763.12 552.62
DINING_FLR_6_DAYLREFPT2 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2763.12 552.62
BANQUET_FLR_6_DAYLREFPT1 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2763.12 552.62
BANQUET_FLR_6_DAYLREFPT2 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2763.12 552.62


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 11096.45 AstronomicalClock -   83.79 83.79 174.52
Exterior Lighting Total 11096.45           174.52



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 342230.51 0.80        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 829958.35 3.26 830104.24 3.26 4.32 14.74


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11971.77 19923.35 15527.68 4395.67 0.78 - 2762.10 28.01
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11884.73 19778.99 15415.14 4363.85 0.78 - 2742.31 27.81
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 65322.88 109419.02 85229.29 24189.74 0.78 - 15494.90 157.16
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 73355.04 120245.48 92664.37 27581.11 0.77 - 16359.72 165.93
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 10469.65 17431.27 13584.93 3846.35 0.78 - 2420.05 24.55
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 10397.64 17311.92 13491.87 3820.04 0.78 - 2403.72 24.38
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3194.48 5315.52 4142.81 1172.71 0.78 - 736.60 7.47
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3168.70 5272.74 4109.46 1163.28 0.78 - 730.73 7.41
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 14121.72 23357.91 18143.07 5214.83 0.78 - 3203.76 32.49
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 559492.50 660362.05 415215.44 245146.61 0.63 - 98541.05 999.46
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 65945.86 54169.20 34464.63 19704.58 0.64 - 5364.64 54.41
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 5636.53 5665.88 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 3350.08 3364.99 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1466.36 1473.46 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2260.59 2270.64 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1335.69 1341.54 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 10927.93 10984.24 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 9799.95 9846.82 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 27159.03 27291.59 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5394.73 5811.80 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5398.46 5815.82 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 30986.17 33381.62 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 31074.58 33476.85 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5386.51 5802.95 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5390.25 5806.97 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 12031.39 12085.60 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1639.59 1766.30 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1640.02 1766.76 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 7877.01 8485.72 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 11271.28 11327.79 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 11669.80 11728.37 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 8098.04 8139.51 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 7641.14 7674.86 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 123843.92 99741.28 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 10951.44 8820.06 -
SWHSYSLAUNDRY HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped   75921.46 3.40
SWHSYS1 HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped   54370.95 3.40
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.24 76.61 324.68 1.00 2.78 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.20 844.36 703.64 1.00 1.15 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.19 838.22 703.64 1.00 1.16 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 6.55 4607.63 703.64 1.00 0.95 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 7.09 4988.29 703.64 1.00 0.95 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.05 738.42 703.64 1.00 1.19 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.04 733.35 703.64 1.00 1.19 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.32 225.31 703.64 1.00 1.67 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.32 223.49 703.64 1.00 1.67 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.40 984.89 703.64 1.00 1.12 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 1.89 612.92 324.68 1.00 1.48 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 23.20 51976.61 2240.64 1.00 1.11 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
SWHSYSLAUNDRY HPWH FAN Fan:SystemModel 0.70 100.00 4.90 700.51 142.86 0.00 2.78 General    
SWHSYS1 HPWH FAN Fan:SystemModel 0.70 100.00 3.87 553.22 142.86 0.00 2.84 General    


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.029621 6043.44 204022.71 0.91 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.002994 892.73 298174.34 0.91 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.029621 4184.08 141251.80 0.91 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWHSYSLAUNDRY HPWH WaterHeater:HeatPump:PumpedCondenser 1.14 74956.02 0.80 48.89 1.69
SWHSYS1 HPWH WaterHeater:HeatPump:PumpedCondenser 2.84 61437.95 0.80 4.63 9.42



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 29385.03 29385.03 14.85 2.352 2.352 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 21:40:00 24.00 24.00 0.00932 32.15 0.00562 0.854 0.00
RETAIL_1_FLR_1 4608.12 4608.12 68.70 0.369 0.369 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 24.00 0.00889 40.80 0.00563 0.079 0.00
RETAIL_2_FLR_1 3202.82 3202.82 41.24 0.256 0.256 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 24.00 24.00 0.00930 37.28 0.00563 0.092 0.00
MECH_FLR_1 3076.52 3076.52 18.73 0.246 0.246 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 24.00 24.00 0.00852 36.94 0.00563 0.000 0.00
STORAGE_FLR_1 1695.93 1695.93 17.90 0.136 0.136 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 24.00 24.00 0.00858 38.05 0.00563 0.058 0.00
LAUNDRY_FLR_1 45472.57 45472.57 582.69 3.639 3.639 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 24.00 24.00 0.00853 40.00 0.00563 0.000 0.00
CAFE_FLR_1 19487.96 19487.96 103.19 1.561 1.561 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 23.99 0.01005 40.80 0.00563 0.676 0.00
LOBBY_FLR_1 64328.34 64328.34 49.17 5.150 5.150 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 23.99 0.00990 40.80 0.00563 1.894 0.00
ROOM_1_FLR_3 11127.86 11127.86 285.17 1.200 1.200 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 21.11 21.11 0.00848 39.12 0.00563 0.062 0.00
ROOM_2_FLR_3 11046.96 11046.96 283.13 1.191 1.191 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 21.11 21.11 0.00848 38.94 0.00563 0.062 0.00
ROOM_3_MULT19_FLR_3 60724.71 60724.71 2476.15 6.548 6.548 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 21.11 21.11 0.00841 40.80 0.00563 0.837 0.00
ROOM_4_MULT19_FLR_3 65736.33 65736.33 2679.77 7.089 7.089 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 21.11 21.11 0.00863 40.27 0.00563 0.837 0.00
ROOM_5_FLR_3 9731.70 9731.70 249.39 1.049 1.049 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 21.11 21.11 0.00847 36.74 0.00562 0.062 0.00
ROOM_6_FLR_3 9664.77 9664.77 247.70 1.042 1.042 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 21.11 21.11 0.00847 36.41 0.00562 0.062 0.00
CORRIDOR_FLR_3 17541.62 17541.62 45.05 1.404 1.404 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 24.00 24.00 0.00946 40.40 0.00563 0.475 0.00
ROOM_1_FLR_6 2969.29 2969.29 76.09 0.320 0.320 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 21.11 21.11 0.00848 39.12 0.00563 0.015 0.00
ROOM_2_FLR_6 2945.32 2945.32 75.49 0.318 0.318 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 21.11 21.11 0.00848 38.94 0.00563 0.015 0.00
ROOM_3_MULT9_FLR_6 12979.35 12979.35 529.11 1.400 1.400 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 21.11 21.11 0.00854 40.80 0.00563 0.099 0.00
BANQUET_FLR_6 30297.17 30297.17 91.35 2.428 2.428 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 24.00 23.98 0.01032 40.67 0.00563 1.188 0.00
DINING_FLR_6 31751.74 31751.74 95.74 2.544 2.544 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 24.00 23.98 0.01024 40.67 0.00563 1.188 0.00
KITCHEN_FLR_6 30100.94 30100.94 291.38 2.415 2.415 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 24.00 23.97 0.01007 39.60 0.00563 0.367 0.00
CORRIDOR_FLR_6 10074.89 10074.89 24.45 0.806 0.806 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 24.00 24.00 0.00892 40.80 0.00563 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 0.854   00:10:00 21.00 23.73 0.00432 0.50 0.00432 0.854 0.00
RETAIL_1_FLR_1 2467.09 2467.09 36.78 0.116 0.116 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 21.00 21.00 0.00749 0.50 0.00432 0.079 0.00
RETAIL_2_FLR_1 852.62 852.62 10.98 0.040 0.092 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 21.00 21.00 0.00744 0.50 0.00432 0.092 0.00
MECH_FLR_1 1671.29 1671.29 10.18 0.079 0.079 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 21.00 21.00 0.00734 0.50 0.00432 0.000 0.00
STORAGE_FLR_1 1010.82 1010.82 10.67 0.048 0.058 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 21.00 21.00 0.00737 0.50 0.00432 0.058 0.00
LAUNDRY_FLR_1 2218.13 2218.13 28.42 0.105 0.105 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 21.00 21.00 0.00733 0.50 0.00432 0.000 0.00
CAFE_FLR_1 6062.10 6062.10 32.10 0.286 0.676 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 21.00 21.00 0.00753 0.50 0.00432 0.676 0.00
LOBBY_FLR_1 14828.15 14828.15 11.33 0.700 1.894 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.00 21.00 0.00747 0.50 0.00432 1.894 0.00
ROOM_1_FLR_3 5394.86 5394.86 138.25 0.256 0.256 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.11 21.11 0.00746 0.50 0.00432 0.062 0.00
ROOM_2_FLR_3 5398.59 5398.59 138.36 0.256 0.256 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.11 21.11 0.00746 0.50 0.00432 0.062 0.00
ROOM_3_MULT19_FLR_3 30986.53 30986.53 1263.53 1.472 1.472 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.11 21.11 0.00750 0.50 0.00432 0.837 0.00
ROOM_4_MULT19_FLR_3 31074.94 31074.94 1266.79 1.476 1.476 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.11 21.11 0.00750 0.50 0.00432 0.837 0.00
ROOM_5_FLR_3 5386.64 5386.64 138.04 0.256 0.256 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.11 21.11 0.00746 0.50 0.00432 0.062 0.00
ROOM_6_FLR_3 5390.37 5390.37 138.15 0.256 0.256 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.11 21.11 0.00746 0.50 0.00432 0.062 0.00
CORRIDOR_FLR_3 8669.46 8669.46 22.26 0.409 0.475 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00758 0.50 0.00432 0.475 0.00
ROOM_1_FLR_6 1639.63 1639.63 42.02 0.078 0.078 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.11 21.11 0.00755 0.50 0.00432 0.015 0.00
ROOM_2_FLR_6 1640.06 1640.06 42.03 0.078 0.078 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.11 21.11 0.00755 0.50 0.00432 0.015 0.00
ROOM_3_MULT9_FLR_6 7877.09 7877.09 321.11 0.374 0.374 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00756 0.50 0.00432 0.099 0.00
BANQUET_FLR_6 5456.84 5456.84 16.45 0.258 1.188 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.00 21.00 0.00766 0.50 0.00432 1.188 0.00
DINING_FLR_6 5576.23 5576.23 16.81 0.263 1.188 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.00 21.00 0.00766 0.50 0.00432 1.188 0.00
KITCHEN_FLR_6 2324.30 2324.30 22.50 0.110 0.367 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 21.00 21.00 0.00691 0.50 0.00432 0.367 0.00
CORRIDOR_FLR_6 5709.87 5709.87 13.85 0.270 0.270 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.00 21.00 0.00771 0.50 0.00432 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 23.20 23.20 7.36 7.36 23.1972 11.6535 23.1972 0.5024 0.3000
FLR_3_DOAS 19.68 2.05 4.50 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 5636.532 5636.532 1.175896 0.00004931 117.540   12/21 00:10:00   12/21 00:10:00 5636.53 5636.53 1.175896 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00800000 46.9512 0.00 0.00 5668.21 5668.21
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 3350.075 3350.075 0.184408 0.00002931 81.907 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 3350.08 3350.08 0.184408 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00748860 43.9873 2467.09 0.00 3367.47 3367.47
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1466.363 1466.363 0.128178 0.00001283 32.965 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 1466.36 1466.36 0.128178 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00743791 43.6920 852.62 0.00 1474.29 1474.29
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 2260.592 2260.592 0.123095 0.00001978 55.414 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 2260.59 2260.59 0.123095 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00734289 43.1404 1671.29 0.00 2272.32 2272.32
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 1335.694 1335.694 0.067857 0.00001169 33.324 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 1335.69 1335.69 0.067857 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00736798 43.2861 1010.82 0.00 1342.58 1342.58
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10927.933 10927.933 1.819549 0.00009560 230.914 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 10927.93 10927.93 1.819549 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00732744 43.0517 2218.13 0.00 10989.07 10989.07
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 9799.947 9799.947 0.780549 0.00008573 223.265 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 9799.95 9799.95 0.780549 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00753344 44.2472 6062.10 0.00 9852.68 9852.68
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 27159.031 27159.031 2.575187 0.00023760 604.154 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 27159.03 27159.03 2.575187 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00746637 43.8575 14828.15 0.00 27306.50 27306.50
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 11971.769 -999.000 1.200000 0.00042760 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 unknown 7/21 16:50:00 11971.77 11971.77 1.200000 21.74 14.59 0.00847772 12.80 11.21 0.00847772 39.12 0.00562848 18.06 0.0000 21.11 0.00847772 49.3789 11127.86 0.00 13173.75 12889.85
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 5394.729 5394.729 0.256189 0.00004720 154.169 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 5394.73 5394.73 0.256189 21.11 13.47 0.00746433 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00746433 43.5497 5394.86 0.00 5815.61 5815.61
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 11884.727 -999.000 1.191276 0.00042449 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown 7/21 17:00:00 11884.73 11884.73 1.191276 21.74 14.59 0.00847747 12.80 11.21 0.00847747 38.94 0.00562821 18.00 0.0000 21.11 0.00847747 49.3775 11046.96 0.00 13078.01 12796.62
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 5398.461 5398.461 0.256366 0.00004723 154.275 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 5398.46 5398.46 0.256366 21.11 13.47 0.00746468 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00746468 43.5517 5398.59 0.00 5819.63 5819.63
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 65322.883 -999.000 6.548308 0.00233314 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 unknown 7/21 14:30:00 65322.88 65322.88 6.548308 21.74 14.54 0.00841460 12.80 11.15 0.00841460 40.80 0.00563111 18.58 0.0000 21.11 0.00841460 49.0158 60724.71 0.00 71939.89 71939.89
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 30986.168 30986.168 1.471541 0.00027108 885.498 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 30986.17 30986.17 1.471541 21.11 13.50 0.00750001 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00750001 43.7538 30986.53 0.00 33403.91 33403.91
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 73355.035 -999.000 7.089300 0.00262002 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 unknown 7/21 15:40:00 73355.04 71309.08 7.089300 21.74 14.73 0.00863362 12.80 11.23 0.00850000 40.27 0.00563027 18.42 0.0000 21.11 0.00863362 50.2762 65736.33 0.00 80571.93 76138.57
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 31074.577 31074.577 1.475739 0.00027185 888.024 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 31074.58 31074.58 1.475739 21.11 13.50 0.00750112 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00750112 43.7602 31074.94 0.00 33499.22 33499.22
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 10469.651 -999.000 1.049441 0.00037394 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 unknown 7/21 10:30:00 10469.65 10469.65 1.049441 21.74 14.59 0.00847339 12.80 11.21 0.00847339 36.74 0.00562481 17.31 0.0000 21.11 0.00847339 49.3540 9731.70 0.00 11521.45 11280.05
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 5386.513 5386.513 0.255799 0.00004712 153.934 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 5386.51 5386.51 0.255799 21.11 13.47 0.00746363 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00746363 43.5457 5386.64 0.00 5806.75 5806.75
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 10397.638 -999.000 1.042223 0.00037137 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 unknown 7/21 10:20:00 10397.64 10397.64 1.042223 21.74 14.59 0.00847308 12.80 11.21 0.00847308 36.41 0.00562429 17.20 0.0000 21.11 0.00847308 49.3523 9664.77 0.00 11442.25 11202.99
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 5390.247 5390.247 0.255976 0.00004716 154.041 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 5390.25 5390.25 0.255976 21.11 13.47 0.00746399 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00746399 43.5477 5390.37 0.00 5810.77 5810.77
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 12031.393 12031.393 0.701934 0.00010526 290.242 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 12031.39 12031.39 0.701934 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00757960 44.5141 8669.46 0.00 12094.18 12094.18
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 3194.485 -999.000 0.320201 0.00011410 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 unknown 7/21 16:50:00 3194.48 3194.48 0.320201 21.74 14.59 0.00847905 12.80 11.21 0.00847905 39.12 0.00562848 18.06 0.0000 21.11 0.00847905 49.3866 2969.29 0.00 3515.16 3438.76
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 1639.594 1639.594 0.077862 0.00001434 46.853 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 1639.59 1639.59 0.077862 21.11 13.54 0.00754763 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00754763 44.0298 1639.63 0.00 1767.51 1767.51
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 3168.696 -999.000 0.317616 0.00011318 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown 7/21 17:00:00 3168.70 3168.70 0.317616 21.74 14.59 0.00847880 12.80 11.21 0.00847880 38.94 0.00562821 18.00 0.0000 21.11 0.00847880 49.3852 2945.32 0.00 3486.79 3411.12
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 1640.021 1640.021 0.077883 0.00001435 46.866 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 1640.02 1640.02 0.077883 21.11 13.54 0.00754776 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00754776 44.0306 1640.06 0.00 1767.97 1767.97
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 14121.716 -999.000 1.399714 0.00050439 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 unknown 7/21 14:30:00 14121.72 13999.93 1.399714 21.74 14.65 0.00854051 12.80 11.23 0.00850000 40.80 0.00563111 18.58 0.0000 21.11 0.00854051 49.7407 12979.35 0.00 15528.83 14999.69
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 7877.011 7877.011 0.374074 0.00006891 225.094 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 7877.01 7877.01 0.374074 21.11 13.56 0.00756421 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00756421 44.1248 7877.09 0.00 8491.58 8491.58
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 11271.281 11271.281 1.213883 0.00009861 247.115 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 11271.28 11271.28 1.213883 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00765506 44.9525 5456.84 0.00 11333.64 11333.64
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 11669.803 11669.803 1.272141 0.00010209 255.523 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 11669.80 11669.80 1.272141 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00766177 44.9914 5576.23 0.00 11734.39 11734.39
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 8098.037 8098.037 1.207677 0.00007085 172.443 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 8098.04 8098.04 1.207677 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00690728 40.6153 2324.30 0.00 8143.22 8143.22
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 7641.140 7641.140 0.403144 0.00006685 188.780 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 7641.14 7641.14 0.403144 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00770669 45.2516 5709.87 0.00 7680.67 7680.67
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 559492.501 -999.000 23.197232 0.01998378 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 559492.50 559492.49 23.197232 32.44 17.49 0.00761887 10.79 9.51 0.00761887 40.80 0.00563111 18.58 50.2709 23.99 0.00960390 46.8737 289655.46 0.00 596888.39 585277.27
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 123843.923 123843.923 6.959169 0.00108344 2173.015 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 123843.92 123843.92 6.959169 0.50 0.50 0.00431558 16.70 12.29 0.00800000 0.50 0.00431558 0.50 167.5697 21.53 0.00693754 39.4884 56501.82 0.00 120693.93 120693.93
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 65945.855 -999.000 2.051317 0.00235543 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 65945.86 65945.86 2.051317 40.80 18.58 0.00563111 11.84 7.85 0.00563111 40.80 0.00563111 18.58 99.9965 21.11 0.00852784 49.6676 181821.95 0.00 66000.58 66000.58
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 10951.444 10951.444 0.615395 0.00009581 192.158 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 10951.44 10951.44 0.615395 0.50 0.50 0.00431558 16.70 12.29 0.00800000 0.50 0.00431558 0.50 333.3216 21.11 0.00750089 43.7589 94788.32 0.00 10672.89 10672.89
SWHSYSLAUNDRY HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped unknown unknown 63116.212 46453.532 4.903586 -999.0 -999.000 unknown unknown unknown unknown 75921.46 -999.00 -999.0 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.00 -999.0 -999.00 -999.0000 -999.00 -999.0 -999.0000 -999.00 0.00 -999.00 -999.00
SWHSYS1 HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped unknown unknown 49873.925 36707.209 3.872570 -999.0 -999.000 unknown unknown unknown unknown 54370.95 -999.00 -999.0 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.00 -999.0 -999.00 -999.0000 -999.00 -999.0 -999.0000 -999.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 5636.532 5636.532 1.175896 0.00004931 117.540 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 1.6145 1.646999   12/21 00:10:00 unknown unknown   12/21 00:10:00 Sensible 5636.53 5636.53 1.0000 1.28548254 1.175896 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.04930581 60.00 32.22 27.78 0.000 5636.53 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 46.9512 0.00 0.00 5668.21 5668.21 1.28548254 16.60 13.15 0.00800000 36934.7 20.92 14.82 0.00800000 41344.1
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 3350.075 3350.075 0.184408 0.00002931 81.907 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 0.9596 0.978894 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 Sensible 3350.08 3350.08 1.0000 0.20159402 0.184408 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.02930493 60.00 32.22 27.78 0.000 3350.08 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00748860 21.00 0.00748860 43.9873 2467.09 0.00 3367.47 3367.47 0.20159402 16.60 13.15 0.00800000 36934.7 32.98 19.02 0.00800000 53639.0
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1466.363 1466.363 0.128178 0.00001283 32.965 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 0.4200 0.428472 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 Sensible 1466.36 1466.36 1.0000 0.14012359 0.128178 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.01282707 60.00 32.22 27.78 0.000 1466.36 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00743791 21.00 0.00743791 43.6920 852.62 0.00 1474.29 1474.29 0.14012359 16.60 13.15 0.00800000 36934.7 26.92 16.99 0.00800000 47456.1
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 2260.592 2260.592 0.123095 0.00001978 55.414 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 0.6475 0.660547 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 Sensible 2260.59 2260.59 1.0000 0.13456726 0.123095 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.01977463 60.00 32.22 27.78 0.000 2260.59 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00734289 21.00 0.00734289 43.1404 1671.29 0.00 2272.32 2272.32 0.13456726 16.60 13.15 0.00800000 36934.7 33.16 19.07 0.00800000 53820.9
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 1335.694 1335.694 0.067857 0.00001169 33.324 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 0.3826 0.390291 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 Sensible 1335.69 1335.69 1.0000 0.07418106 0.067857 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.01168405 60.00 32.22 27.78 0.000 1335.69 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00736798 21.00 0.00736798 43.2861 1010.82 0.00 1342.58 1342.58 0.07418106 16.60 13.15 0.00800000 36934.7 34.35 19.45 0.00800000 55033.5
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 10927.933 10927.933 1.819549 0.00009560 230.914 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 3.1302 3.193150 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 Sensible 10927.93 10927.93 1.0000 1.98912075 1.819549 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.09559257 60.00 32.22 27.78 0.000 10927.93 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00732744 21.00 0.00732744 43.0517 2218.13 0.00 10989.07 10989.07 1.98912075 16.60 13.15 0.00800000 36934.7 22.02 15.23 0.00800000 42459.3
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 9799.947 9799.947 0.780549 0.00008573 223.265 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 2.8071 2.863552 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 12:00:00 Sensible 9799.95 9799.95 1.0000 0.85329162 0.780549 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.08572547 60.00 32.22 27.78 0.000 9799.95 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00753344 21.00 0.00753344 44.2472 6062.10 0.00 9852.68 9852.68 0.85329162 16.60 13.15 0.00800000 36934.7 27.92 17.33 0.00800000 48481.4
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 27159.031 27159.031 2.575187 0.00023760 604.154 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 7.7793 7.935888 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 27159.03 27159.03 1.0000 2.81517932 2.575187 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.23757482 60.00 32.22 27.78 0.000 27159.03 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00746637 21.00 0.00746637 43.8575 14828.15 0.00 27306.50 27306.50 2.81517932 16.60 13.15 0.00800000 36934.7 26.11 16.71 0.00800000 46634.5
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 11971.769 -999.000 1.200000 0.00042760 -999.000 -999.0000 1.00000 1.00000 1020.5996 1004.8586 1.0932 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.200000 1.31183310   4197.9300 999.8980 29.61840817 13.37 6.70 6.67 829321.15 1.4436 1.443535 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 unknown unknown unknown 7/21 16:50:00 Sensible 11971.77 11971.77 1.0000 1.31183310 1.200000 21.74 14.59 0.00847772 43391.9 12.80 11.21 0.00847772 34265.9 0.42755223 6.70 13.37 6.67 0.000 11971.77 39.12 0.00562848 18.06 0.00000000 0.0000 21.11 0.00847772 21.11 0.00847772 49.3789 11127.86 0.00 13173.75 12889.85 1.31183310 21.74 15.56 0.00847772 43391.9 12.11 11.71 0.00839195 33349.7
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 5394.729 5394.729 0.256189 0.00004720 154.169 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.200000 1.31183310   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 1.5452 1.576344 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 5394.73 5394.73 1.0000 0.28006435 0.256189 21.11 13.47 0.00746433 40172.8 40.00 20.06 0.00800000 60796.0 0.04719063 60.00 32.22 27.78 0.000 5394.73 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00746433 21.11 0.00746433 43.5497 5394.86 0.00 5815.61 5815.61 0.28006435 16.60 12.63 0.00746433 35578.5 36.98 19.87 0.00746433 56343.8
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 11884.727 -999.000 1.191276 0.00042449 -999.000 -999.0000 1.00000 1.00000 1020.5992 1004.8586 1.0932 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.191276 1.30229581   4197.9300 999.8980 29.61840817 13.37 6.70 6.67 829321.15 1.4331 1.433040 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown unknown unknown 7/21 17:00:00 Sensible 11884.73 11884.73 1.0000 1.30229581 1.191276 21.74 14.59 0.00847747 43391.3 12.80 11.21 0.00847747 34265.3 0.42444367 6.70 13.37 6.67 0.000 11884.73 38.94 0.00562821 18.00 0.00000000 0.0000 21.11 0.00847747 21.11 0.00847747 49.3775 11046.96 0.00 13078.01 12796.62 1.30229581 21.74 15.56 0.00847747 43391.3 12.11 11.71 0.00839184 33349.0
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 5398.461 5398.461 0.256366 0.00004723 154.275 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.191276 1.30229581   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 1.5463 1.577434 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 5398.46 5398.46 1.0000 0.28025809 0.256366 21.11 13.47 0.00746468 40173.7 40.00 20.06 0.00800000 60796.0 0.04722328 60.00 32.22 27.78 0.000 5398.46 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00746468 21.11 0.00746468 43.5517 5398.59 0.00 5819.63 5819.63 0.28025809 16.60 12.63 0.00746468 35579.4 36.98 19.87 0.00746468 56344.7
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 65322.883 -999.000 6.548308 0.00233314 -999.000 -999.0000 1.00000 1.00000 1020.4823 1004.8586 1.0932 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 6.548308 7.15857200   4197.9300 999.8980 29.61840817 13.37 6.70 6.67 829321.15 7.8767 7.876522 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 unknown unknown unknown 7/21 14:30:00 Sensible 65322.88 65322.88 1.0000 7.15857200 6.548308 21.74 14.54 0.00841460 43231.7 12.80 11.15 0.00841460 34106.6 2.33290046 6.70 13.37 6.67 0.000 65322.88 40.80 0.00563111 18.58 0.00000000 0.0000 21.11 0.00841460 21.11 0.00841460 49.0158 60724.71 0.00 71939.89 71939.89 7.15857200 21.74 15.50 0.00841460 43231.7 11.89 11.64 0.00841460 33182.2
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 30986.168 30986.168 1.471541 0.00027108 885.498 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 6.548308 7.15857200   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 8.8756 9.054180 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 30986.17 30986.17 1.0000 1.60867973 1.471541 21.11 13.50 0.00750001 40264.0 40.00 20.06 0.00800000 60796.0 0.27105286 60.00 32.22 27.78 0.000 30986.17 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00750001 21.11 0.00750001 43.7538 30986.53 0.00 33403.91 33403.91 1.60867973 16.60 12.66 0.00750001 35668.8 36.98 19.90 0.00750001 56433.6
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 73355.035 -999.000 7.089300 0.00262002 -999.000 -999.0000 1.00000 1.00000 1020.8895 1004.8586 1.0932 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 7.089300 7.74998171   4197.9300 999.8980 29.61840817 13.37 6.70 6.67 829321.15 8.8452 8.845025 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 unknown unknown unknown 7/21 15:40:00 Sensible 73355.04 71309.08 1.0000 7.74998171 7.089300 21.74 14.73 0.00863362 43787.4 12.80 11.23 0.00850000 34322.2 2.61975569 6.70 13.37 6.67 0.000 73355.04 40.27 0.00563027 18.42 0.00000000 0.0000 21.11 0.00863362 21.11 0.00863362 50.2762 65736.33 0.00 80571.93 76138.57 7.74998171 21.74 15.69 0.00863362 43787.4 12.12 11.72 0.00840692 33391.0
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 31074.577 31074.577 1.475739 0.00027185 888.024 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 7.089300 7.74998171   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 8.9009 9.080014 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 31074.58 31074.58 1.0000 1.61326955 1.475739 21.11 13.50 0.00750112 40266.9 40.00 20.06 0.00800000 60796.0 0.27182622 60.00 32.22 27.78 0.000 31074.58 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00750112 21.11 0.00750112 43.7602 31074.94 0.00 33499.22 33499.22 1.61326955 16.60 12.66 0.00750112 35671.7 36.98 19.90 0.00750112 56436.5
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 10469.651 -999.000 1.049441 0.00037394 -999.000 -999.0000 1.00000 1.00000 1020.5916 1004.8586 1.0932 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.049441 1.14724241   4197.9300 999.8980 29.61840817 13.37 6.70 6.67 829321.15 1.2624 1.262413 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 unknown unknown unknown 7/21 10:30:00 Sensible 10469.65 10469.65 1.0000 1.14724241 1.049441 21.74 14.59 0.00847339 43380.9 12.80 11.21 0.00847339 34255.0 0.37390653 6.70 13.37 6.67 0.000 10469.65 36.74 0.00562481 17.31 0.00000000 0.0000 21.11 0.00847339 21.11 0.00847339 49.3540 9731.70 0.00 11521.45 11280.05 1.14724241 21.74 15.55 0.00847339 43380.9 12.11 11.70 0.00839000 33338.2
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 5386.513 5386.513 0.255799 0.00004712 153.934 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.049441 1.14724241   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 1.5429 1.573943 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 5386.51 5386.51 1.0000 0.27963780 0.255799 21.11 13.47 0.00746363 40171.1 40.00 20.06 0.00800000 60796.0 0.04711876 60.00 32.22 27.78 0.000 5386.51 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00746363 21.11 0.00746363 43.5457 5386.64 0.00 5806.75 5806.75 0.27963780 16.60 12.63 0.00746363 35576.8 36.98 19.87 0.00746363 56342.0
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 10397.638 -999.000 1.042223 0.00037137 -999.000 -999.0000 1.00000 1.00000 1020.5910 1004.8586 1.0932 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.042223 1.13935197   4197.9300 999.8980 29.61840817 13.37 6.70 6.67 829321.15 1.2538 1.253730 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 unknown unknown unknown 7/21 10:20:00 Sensible 10397.64 10397.64 1.0000 1.13935197 1.042223 21.74 14.59 0.00847308 43380.2 12.80 11.21 0.00847308 34254.2 0.37133474 6.70 13.37 6.67 0.000 10397.64 36.41 0.00562429 17.20 0.00000000 0.0000 21.11 0.00847308 21.11 0.00847308 49.3523 9664.77 0.00 11442.25 11202.99 1.13935197 21.74 15.55 0.00847308 43380.2 12.11 11.70 0.00838987 33337.4
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 5390.247 5390.247 0.255976 0.00004716 154.041 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.042223 1.13935197   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 1.5440 1.575034 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 5390.25 5390.25 1.0000 0.27983165 0.255976 21.11 13.47 0.00746399 40171.9 40.00 20.06 0.00800000 60796.0 0.04715142 60.00 32.22 27.78 0.000 5390.25 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00746399 21.11 0.00746399 43.5477 5390.37 0.00 5810.77 5810.77 0.27983165 16.60 12.63 0.00746399 35577.7 36.98 19.87 0.00746399 56342.9
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 12031.393 12031.393 0.701934 0.00010526 290.242 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 3.4462 3.515582 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 12031.39 12031.39 1.0000 0.76734987 0.701934 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.10524514 60.00 32.22 27.78 0.000 12031.39 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00757960 21.00 0.00757960 44.5141 8669.46 0.00 12094.18 12094.18 0.76734987 16.60 13.15 0.00800000 36934.7 32.06 18.72 0.00800000 52695.7
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 3194.485 -999.000 0.320201 0.00011410 -999.000 -999.0000 1.00000 1.00000 1020.6021 1004.8586 1.0932 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.320201 0.35004203   4197.9300 999.8980 29.61840817 13.37 6.70 6.67 829321.15 0.3852 0.385186 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 unknown unknown unknown 7/21 16:50:00 Sensible 3194.48 3194.48 1.0000 0.35004203 0.320201 21.74 14.59 0.00847905 43395.3 12.80 11.21 0.00847905 34269.3 0.11408583 6.70 13.37 6.67 0.000 3194.48 39.12 0.00562848 18.06 0.00000000 0.0000 21.11 0.00847905 21.11 0.00847905 49.3866 2969.29 0.00 3515.16 3438.76 0.35004203 21.74 15.56 0.00847905 43395.3 12.12 11.71 0.00839256 33353.2
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 1639.594 1639.594 0.077862 0.00001434 46.853 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.320201 0.35004203   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 0.4696 0.479091 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 1639.59 1639.59 1.0000 0.08511863 0.077862 21.11 13.54 0.00754763 40384.4 40.00 20.06 0.00800000 60796.0 0.01434242 60.00 32.22 27.78 0.000 1639.59 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00754763 21.11 0.00754763 44.0298 1639.63 0.00 1767.51 1767.51 0.08511863 16.60 12.71 0.00754763 35789.4 36.98 19.93 0.00754763 56554.7
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 3168.696 -999.000 0.317616 0.00011318 -999.000 -999.0000 1.00000 1.00000 1020.6017 1004.8586 1.0932 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.317616 0.34721628   4197.9300 999.8980 29.61840817 13.37 6.70 6.67 829321.15 0.3821 0.382076 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown unknown unknown 7/21 17:00:00 Sensible 3168.70 3168.70 1.0000 0.34721628 0.317616 21.74 14.59 0.00847880 43394.7 12.80 11.21 0.00847880 34268.7 0.11316482 6.70 13.37 6.67 0.000 3168.70 38.94 0.00562821 18.00 0.00000000 0.0000 21.11 0.00847880 21.11 0.00847880 49.3852 2945.32 0.00 3486.79 3411.12 0.34721628 21.74 15.56 0.00847880 43394.7 12.12 11.71 0.00839244 33352.6
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 1640.021 1640.021 0.077883 0.00001435 46.866 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.317616 0.34721628   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 0.4698 0.479215 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 1640.02 1640.02 1.0000 0.08514079 0.077883 21.11 13.54 0.00754776 40384.7 40.00 20.06 0.00800000 60796.0 0.01434616 60.00 32.22 27.78 0.000 1640.02 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00754776 21.11 0.00754776 44.0306 1640.06 0.00 1767.97 1767.97 0.08514079 16.60 12.71 0.00754776 35789.8 36.98 19.93 0.00754776 56555.0
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 14121.716 -999.000 1.399714 0.00050439 -999.000 -999.0000 1.00000 1.00000 1020.7164 1004.8586 1.0932 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.399714 1.53015928   4197.9300 999.8980 29.61840817 13.37 6.70 6.67 829321.15 1.7028 1.702772 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 unknown unknown unknown 7/21 14:30:00 Sensible 14121.72 13999.93 1.0000 1.53015928 1.399714 21.74 14.65 0.00854051 43551.1 12.80 11.23 0.00850000 34322.2 0.50433409 6.70 13.37 6.67 0.000 14121.72 40.80 0.00563111 18.58 0.00000000 0.0000 21.11 0.00854051 21.11 0.00854051 49.7407 12979.35 0.00 15528.83 14999.69 1.53015928 21.74 15.61 0.00854051 43551.1 12.14 11.73 0.00840348 33402.6
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 7877.011 7877.011 0.374074 0.00006891 225.094 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.399714 1.53015928   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 2.2563 2.301668 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 7877.01 7877.01 1.0000 0.40893557 0.374074 21.11 13.56 0.00756421 40426.8 40.00 20.06 0.00800000 60796.0 0.06890450 60.00 32.22 27.78 0.000 7877.01 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00756421 21.11 0.00756421 44.1248 7877.09 0.00 8491.58 8491.58 0.40893557 16.60 12.73 0.00756421 35831.4 36.98 19.94 0.00756421 56596.5
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 11271.281 11271.281 1.213883 0.00009861 247.115 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 3.2285 3.293476 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 11271.28 11271.28 1.0000 1.32701009 1.213883 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.09859603 60.00 32.22 27.78 0.000 11271.28 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00765506 21.00 0.00765506 44.9525 5456.84 0.00 11333.64 11333.64 1.32701009 16.60 13.15 0.00800000 36934.7 24.98 16.30 0.00800000 45475.5
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 11669.803 11669.803 1.272141 0.00010209 255.523 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 3.3427 3.409925 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 11669.80 11669.80 1.0000 1.39069765 1.272141 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.10208211 60.00 32.22 27.78 0.000 11669.80 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00766177 21.00 0.00766177 44.9914 5576.23 0.00 11734.39 11734.39 1.39069765 16.60 13.15 0.00800000 36934.7 24.87 16.27 0.00800000 45372.5
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 8098.037 8098.037 1.207677 0.00007085 172.443 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 2.3196 2.366252 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 Sensible 8098.04 8098.04 1.0000 1.32022532 1.207677 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.07083793 60.00 32.22 27.78 0.000 8098.04 0.50 0.00431558 0.50 0.00000000 0.0000 20.56 0.00690728 21.00 0.00690728 40.6153 2324.30 0.00 8143.22 8143.22 1.32022532 16.60 13.15 0.00800000 36934.7 22.65 15.46 0.00800000 43102.8
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 7641.140 7641.140 0.403144 0.00006685 188.780 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 2.1887 2.232746 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 7641.14 7641.14 1.0000 0.44071426 0.403144 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.06684120 60.00 32.22 27.78 0.000 7641.14 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00770669 21.00 0.00770669 45.2516 5709.87 0.00 7680.67 7680.67 0.44071426 16.60 13.15 0.00800000 36934.7 33.69 19.24 0.00800000 54362.5
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 559492.501 -999.000 23.197232 0.01998378 -999.000 -999.0000 1.00000 1.00000 1019.0031 1004.8586 1.0932 VAV WITH REHEAT FAN Fan:VariableVolume 23.197232 25.35907940   4197.9300 999.8980 29.61840817 13.37 6.70 6.67 829321.15 67.4639 67.463913 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 Sensible 559492.50 559492.49 1.0000 25.35907940 23.197232 32.44 17.49 0.00761887 52110.7 10.79 9.51 0.00761887 30047.9 19.98173723 6.70 13.37 6.67 51976.613 507515.89 40.80 0.00563111 18.58 11.66146000 50.2709 23.99 0.00962828 23.99 0.00960390 46.8737 289655.46 0.00 596888.39 585277.27 25.35907940 32.44 18.54 0.00761887 52110.7 9.79 9.70 0.00743711 28573.3
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 123843.923 123843.923 6.959169 0.00108344 2173.015 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 VAV WITH REHEAT FAN Fan:VariableVolume 23.197232 25.35907940   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 35.4734 36.187283 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 123843.92 123843.92 1.0000 7.60772382 6.959169 0.50 0.50 0.00431558 11299.5 16.70 12.29 0.00800000 37036.7 1.08333014 60.00 32.22 27.78 0.000 123843.92 0.50 0.00431558 0.50 11.66146000 167.5697 18.54 0.00715333 21.53 0.00693754 39.4884 56501.82 0.00 120693.93 120693.93 7.60772382 2.80 2.38 0.00431558 13629.0 18.46 10.16 0.00431558 29493.7
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 65945.855 -999.000 2.051317 0.00235543 -999.000 -999.0000 1.00000 1.00000 1015.3079 1004.8586 1.0932 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.24240930   4197.9300 999.8980 29.61840817 13.37 6.70 6.67 829321.15 7.9518 7.951788 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 Sensible 65945.86 65945.86 1.0000 2.24248814 2.051317 40.80 18.58 0.00563111 55507.6 11.84 7.85 0.00563111 26100.2 2.35519288 6.70 13.37 6.67 2195.006 63750.85 40.80 0.00563111 18.58 2.05124512 99.9965 21.11 0.00851674 21.11 0.00852784 49.6676 181821.95 0.00 66000.58 66000.58 2.24248814 40.80 19.66 0.00563111 55507.6 11.81 8.61 0.00563111 26075.8
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 10951.444 10951.444 0.615395 0.00009581 192.158 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.24240930   4197.9300 999.8980 2.99367640 54.44 82.22 27.78 349118.04 3.1369 3.200020 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 10951.44 10951.44 1.0000 0.67274644 0.615395 0.50 0.50 0.00431558 11299.5 16.70 12.29 0.00800000 37036.7 0.09579823 60.00 32.22 27.78 0.000 10951.44 0.50 0.00431558 0.50 2.05124512 333.3216 21.11 0.00749921 21.11 0.00750089 43.7589 94788.32 0.00 10672.89 10672.89 0.67274644 2.80 2.38 0.00431558 13629.0 18.46 10.16 0.00431558 29493.7
SWHSYSLAUNDRY HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped unknown unknown unknown N/A N/A N/A N/A No No unknown No 63116.212 46453.532 4.903586 -999.0 -999.000 -999.0000 1.00000 1.00000 1004.8586 1004.8586 1.0932 SWHSYSLAUNDRY HPWH FAN Fan:SystemModel 4.903586 5.36057240   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 unknown unknown unknown unknown unknown unknown Sensible 75921.46 -999.00 1.0000 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0 -999.0 -999.00 -999.00 -999.00 0.000 75921.46 -999.00 -999.0 -999.00 -999.0 -999.0000 -999.00 -999.0 -999.00 -999.0 -999.0000 -999.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
SWHSYS1 HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped unknown unknown unknown N/A N/A N/A N/A No No unknown No 49873.925 36707.209 3.872570 -999.0 -999.000 -999.0000 1.00000 1.00000 1004.8586 1004.8586 1.0932 SWHSYS1 HPWH FAN Fan:SystemModel 3.872570 4.23347064   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 unknown unknown unknown unknown unknown unknown Sensible 54370.95 -999.00 1.0000 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0 -999.0 -999.00 -999.00 -999.00 0.000 54370.95 -999.00 -999.0 -999.00 -999.0 -999.0000 -999.00 -999.0 -999.00 -999.0 -999.0000 -999.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 23.20 -      
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 1696.33 6633.67 642.00
RETAIL_1_FLR_1 2966.67 4849.67 580.17
RETAIL_2_FLR_1 2160.33 5580.50 684.17
MECH_FLR_1 1808.00 6183.00 260.00
STORAGE_FLR_1 1738.17 6434.50 370.33
LAUNDRY_FLR_1 7744.17 3413.50 3020.33
CAFE_FLR_1 4488.67 3291.83 1112.17
LOBBY_FLR_1 2871.67 4273.83 997.67
ROOM_1_FLR_3 359.17 8088.33 277.33
ROOM_2_FLR_3 747.17 8121.17 675.33
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 334.50 8755.83 334.50
ROOM_5_FLR_3 325.50 7966.00 266.00
ROOM_6_FLR_3 818.67 7817.83 640.67
CORRIDOR_FLR_3 1704.17 7145.83 898.17
ROOM_1_FLR_6 787.00 7905.67 581.00
ROOM_2_FLR_6 1315.83 7976.83 1153.17
ROOM_3_MULT9_FLR_6 236.00 7864.50 140.17
BANQUET_FLR_6 4597.83 2446.00 1096.17
DINING_FLR_6 5319.33 1585.67 1028.83
KITCHEN_FLR_6 8404.00 6716.50 6664.50
CORRIDOR_FLR_6 2027.67 6049.50 552.50
Facility 8714.17 8760.00 7330.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 0.00 0.00 0.00
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 0.00 16.67 0.00 16.67
ROOM_2_FLR_3 0.00 15.33 0.00 15.33
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 12.00 0.00 12.00
ROOM_5_FLR_3 0.00 12.83 0.00 12.83
ROOM_6_FLR_3 0.00 33.67 0.00 33.67
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 23.33 0.00 23.33
ROOM_2_FLR_6 0.00 24.83 0.00 24.83
ROOM_3_MULT9_FLR_6 0.00 26.00 0.00 26.00
BANQUET_FLR_6 0.00 0.00 0.00 0.00
DINING_FLR_6 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 0.00 76.00 0.00 76.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.79 106.50 4826.41 0.853 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 2.406 0.240 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 1.427 0.080 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.629 0.089 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.591 0.089 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 21.992 0.257 0.000 0.000
CAFE_FLR_1 82.56 142.30 748.35 3.730 0.189 0.000 0.000
LOBBY_FLR_1 245.09 422.44 5183.56 1.756 0.078 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.355 0.310 0.000 0.052
ROOM_2_FLR_3 0.95 1.50 118.93 0.355 0.311 0.000 0.051
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.403 0.138 0.000 0.080
ROOM_5_FLR_3 0.95 1.50 118.94 0.355 0.310 0.000 0.052
ROOM_6_FLR_3 0.95 1.50 118.93 0.355 0.311 0.000 0.051
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.482 0.038 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.355 0.310 0.000 0.061
ROOM_2_FLR_6 0.95 1.50 118.93 0.355 0.311 0.000 0.058
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.403 0.253 0.000 0.097
BANQUET_FLR_6 144.99 249.90 1010.89 4.801 0.090 0.000 0.000
DINING_FLR_6 144.99 249.90 1010.89 5.150 0.090 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 20.633 0.259 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 1.078 0.063 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.79 106.50 4826.41 0.501 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 1.416 0.004 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 0.965 0.001 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.484 0.001 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.426 0.001 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 11.397 0.004 0.000 0.000
CAFE_FLR_1 82.56 142.30 748.35 2.640 0.003 0.000 0.000
LOBBY_FLR_1 245.09 422.44 5183.56 1.178 0.001 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.000 0.005 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.000 0.005 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.000 0.002 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.000 0.005 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.000 0.005 0.000 0.000
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.298 0.001 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.000 0.005 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.000 0.005 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.000 0.004 0.000 0.000
BANQUET_FLR_6 144.99 249.90 1010.89 3.436 0.001 0.000 0.000
DINING_FLR_6 144.99 249.90 1010.89 3.628 0.001 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 8.915 0.004 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 0.678 0.001 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.79 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.28 12.54 307.76 77.67 0.0000 0.092
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.56 142.30 748.35 188.86 0.0000 0.676
LOBBY_FLR_1 VAV WITH REHEAT 245.09 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.16 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 144.99 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 144.99 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.90 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.87 22.18 1256.16 412.12 0.0000 0.126
Total Facility   873.25 1604.23 35184.81 11345.29 0.0000 137.584


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 35342185.32 0.00 35342185.32 0.00 35342185.32 26946214.98 855.52 98.04 7806.44 0.00
RETAIL_1_FLR_1 5500456.04 0.00 5500456.04 549390.10 6049846.14 2498216.28 0.00 0.00 8760.00 0.00
RETAIL_2_FLR_1 3770049.42 0.00 3770049.42 212065.27 3982114.69 2892943.94 111.22 44.35 8604.43 0.00
MECH_FLR_1 3523660.34 0.00 3523660.34 501196.32 4024856.66 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 1910609.59 0.00 1910609.59 289162.67 2199772.26 1821682.01 3621.44 220.44 4918.12 0.00
LAUNDRY_FLR_1 58462542.29 0.00 58462542.29 684357.98 59146900.27 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 23916111.64 0.00 23916111.64 1214457.92 25130569.56 21330615.53 2765.26 229.66 5765.08 0.00
LOBBY_FLR_1 77991532.53 0.00 77991532.53 3469983.66 81461516.20 59728886.00 153.11 42.27 8564.62 0.00
ROOM_1_FLR_3 1460156.71 53574.19 1513730.90 318881.11 1832612.02 1946875.62 2190.00 5876.17 693.83 0.00
ROOM_2_FLR_3 1459985.63 52429.65 1512415.29 318856.78 1831272.07 1946647.51 2190.00 5880.07 689.93 0.00
ROOM_3_MULT19_FLR_3 1099911.97 0.00 1099911.97 88971.41 1188883.38 26397887.27 8395.00 365.00 0.00 365.00
ROOM_4_MULT19_FLR_3 19803829.30 51355.53 19855184.83 88995.74 19944180.56 26405105.73 2190.00 5908.88 661.12 0.00
ROOM_5_FLR_3 1460156.71 53686.25 1513842.96 318881.11 1832724.07 1946875.62 2190.00 5876.17 693.83 0.00
ROOM_6_FLR_3 1459985.63 52019.20 1512004.83 318856.78 1830861.61 1946647.51 2190.00 5876.67 693.33 0.00
CORRIDOR_FLR_3 19686529.60 0.00 19686529.60 385591.42 20072121.02 14972100.18 168.58 48.09 8543.33 0.00
ROOM_1_FLR_6 365039.18 62508.23 427547.41 318945.54 746492.95 486718.90 2021.80 5878.95 859.24 0.00
ROOM_2_FLR_6 364996.41 59049.52 424045.93 318921.20 742967.13 486661.88 2045.01 5888.09 826.90 0.00
ROOM_3_MULT9_FLR_6 2345190.31 62732.30 2407922.61 163183.70 2571106.31 3126920.42 2190.00 5876.17 693.83 0.00
BANQUET_FLR_6 41526711.44 0.00 41526711.44 778784.84 42305496.28 37458366.31 2336.17 1032.02 5391.81 0.00
DINING_FLR_6 44545606.02 0.00 44545606.02 778784.84 45324390.86 37458366.31 415.20 258.87 8085.93 0.00
KITCHEN_FLR_6 55639790.54 0.00 55639790.54 697192.99 56336983.53 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 11647708.10 0.00 11647708.10 682373.60 12330081.69 3961413.96 0.00 0.00 8760.00 0.00
Total Facility 0.21E+10 5436005.91 0.21E+10 32134041.92 0.21E+10 0.43E+10 8760.00 6802.01 8760.00 365.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.1207 0.0000 1.1207 0.0000 1.1207 0.8545 855.52 98.04 7806.44
RETAIL_1_FLR_1 0.1744 0.0000 0.1744 0.0174 0.1918 0.0792 0.00 0.00 8760.00
RETAIL_2_FLR_1 0.1195 0.0000 0.1195 0.0067 0.1263 0.0917 111.22 44.35 8604.43
MECH_FLR_1 0.1117 0.0000 0.1117 0.0159 0.1276 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.0606 0.0000 0.0606 0.0092 0.0698 0.0578 3621.44 220.44 4918.12
LAUNDRY_FLR_1 1.8538 0.0000 1.8538 0.0217 1.8755 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 0.7584 0.0000 0.7584 0.0385 0.7969 0.6764 2765.26 229.66 5765.08
LOBBY_FLR_1 2.4731 0.0000 2.4731 0.1100 2.5831 1.8940 153.11 42.27 8564.62
ROOM_1_FLR_3 0.0463 0.0017 0.0480 0.0101 0.0581 0.0617 2190.00 5876.17 693.83
ROOM_2_FLR_3 0.0463 0.0017 0.0480 0.0101 0.0581 0.0617 2190.00 5880.07 689.93
ROOM_4_MULT19_FLR_3 0.6280 0.0016 0.6296 0.0028 0.6324 0.8373 2190.00 5908.88 661.12
ROOM_5_FLR_3 0.0463 0.0017 0.0480 0.0101 0.0581 0.0617 2190.00 5876.17 693.83
ROOM_6_FLR_3 0.0463 0.0016 0.0479 0.0101 0.0581 0.0617 2190.00 5876.67 693.33
CORRIDOR_FLR_3 0.6243 0.0000 0.6243 0.0122 0.6365 0.4748 168.58 48.09 8543.33
ROOM_1_FLR_6 0.0116 0.0020 0.0136 0.0101 0.0237 0.0154 2021.80 5878.95 859.24
ROOM_2_FLR_6 0.0116 0.0019 0.0134 0.0101 0.0236 0.0154 2045.01 5888.09 826.90
ROOM_3_MULT9_FLR_6 0.0744 0.0020 0.0764 0.0052 0.0815 0.0992 2190.00 5876.17 693.83
BANQUET_FLR_6 1.3168 0.0000 1.3168 0.0247 1.3415 1.1878 2336.17 1032.02 5391.81
DINING_FLR_6 1.4125 0.0000 1.4125 0.0247 1.4372 1.1878 415.20 258.87 8085.93
KITCHEN_FLR_6 1.7643 0.0000 1.7643 0.0221 1.7864 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.3693 0.0000 0.3693 0.0216 0.3910 0.1256 0.00 0.00 8760.00
Total Facility 63.1917 0.1724 63.3640 0.8045 64.1686 73.9670 8760.00 6802.01 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.46E+09 0.00 0.46E+09 0.22E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 35636200.53 447354.87 36083555.41 64690340.46 8760.00 0.00 0.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 14.5316 0.0000 14.5316 6.9969 0.00 0.00 8760.00
FLR_3_DOAS 1.1300 0.0142 1.1442 2.0513 8760.00 0.00 0.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 0.00 4693.17 0.00 0.00 0.00 4066.83 0.00 0.00 0.00
FLR_3_DOAS 0.00 0.00 0.00 0.00 6935.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 0.0000 15.4533 0.0000 0.0000 0.0000 13.4712 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 0.0000 0.0000 0.0000 1.4274 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1363
Defaulted Fields 1208
Fields with Defaults 4115
Autosized Fields 353
Autosizable Fields 407
Autocalculated Fields 289
Autocalculatable Fields 549



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 6193.13 67247.62 08-MAR-02:50 437675.20 29-JUN-19:30
Electricity:Building 2278.97 30456.19 02-JAN-02:10 133648.28 02-JAN-20:10
Electricity:Zone:BASEMENT 245.14 2955.01 02-JAN-02:10 17976.64 02-JAN-20:10
Electricity:SpaceType:GENERAL 2271.88 30315.04 02-JAN-02:10 133406.95 02-JAN-20:10
InteriorLights:Electricity 543.74 5032.86 02-JAN-02:10 45424.10 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 102.03 927.11 02-JAN-02:10 8344.11 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 543.74 5032.86 02-JAN-02:10 45424.10 02-JAN-20:10
LightsWired:InteriorLights:Electricity 543.74 5032.86 02-JAN-02:10 45424.10 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 102.03 927.11 02-JAN-02:10 8344.11 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 543.74 5032.86 02-JAN-02:10 45424.10 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 15.82 195.57 02-JAN-02:10 1146.69 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 5.64 51.23 02-JAN-02:10 461.08 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 5.64 51.23 02-JAN-02:10 461.08 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 18.32 226.47 02-JAN-02:10 1327.87 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 6.53 59.33 02-JAN-02:10 533.93 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 6.53 59.33 02-JAN-02:10 533.93 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 20.00 245.14 02-JAN-02:10 1455.21 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 7.53 68.42 02-JAN-02:10 615.76 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 7.53 68.42 02-JAN-02:10 615.76 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 5.28 66.24 02-JAN-02:10 379.51 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 1.68 15.26 02-JAN-02:10 137.35 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 1.68 15.26 02-JAN-02:10 137.35 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 72.35 1002.76 02-JAN-02:10 4933.42 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.41 40.07 02-JAN-02:10 360.62 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.41 40.07 02-JAN-02:10 360.62 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 26.01 360.56 02-JAN-02:10 2381.38 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 11.67 69.23 01-JAN-13:10 1416.11 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 11.67 69.23 01-JAN-13:10 1416.11 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 259.76 3175.95 02-JAN-02:10 19610.05 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 110.76 1064.54 02-JAN-02:10 9580.84 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 110.76 1064.54 02-JAN-02:10 9580.84 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 17.85 257.74 01-JAN-02:10 1187.62 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 5.55 47.02 01-JAN-02:10 427.46 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 5.55 47.02 01-JAN-02:10 427.46 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 17.84 257.71 01-JAN-02:10 1187.48 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 5.55 47.01 01-JAN-02:10 427.41 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 5.55 47.01 01-JAN-02:10 427.41 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 295.07 4482.89 01-JAN-02:10 20504.95 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 66.32 561.43 01-JAN-02:10 5104.26 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 66.32 561.43 01-JAN-02:10 5104.26 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 295.15 4484.12 01-JAN-02:10 20510.57 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 66.33 561.58 01-JAN-02:10 5105.65 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 66.33 561.58 01-JAN-02:10 5105.65 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 17.85 257.74 01-JAN-02:10 1187.62 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 5.55 47.02 01-JAN-02:10 427.46 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 5.55 47.02 01-JAN-02:10 427.46 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 17.84 257.71 01-JAN-02:10 1187.48 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 5.55 47.01 01-JAN-02:10 427.41 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 5.55 47.01 01-JAN-02:10 427.41 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 51.07 464.00 02-JAN-02:10 4176.01 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 51.07 464.00 02-JAN-02:10 4176.01 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 51.07 464.00 02-JAN-02:10 4176.01 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 4.46 64.43 01-JAN-02:10 296.90 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.39 11.75 01-JAN-02:10 106.87 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.39 11.75 01-JAN-02:10 106.87 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 4.46 64.43 01-JAN-02:10 296.87 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.39 11.75 01-JAN-02:10 106.85 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.39 11.75 01-JAN-02:10 106.85 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 34.95 531.01 01-JAN-02:10 2428.88 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 7.86 66.50 01-JAN-02:10 604.62 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 7.86 66.50 01-JAN-02:10 604.62 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 201.56 2525.61 02-JAN-02:10 9234.71 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 25.71 276.31 02-JAN-02:10 2486.81 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 25.71 276.31 02-JAN-02:10 2486.81 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 201.56 2525.61 02-JAN-02:10 9234.71 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 25.71 276.31 02-JAN-02:10 2486.81 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 25.71 276.31 02-JAN-02:10 2486.81 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 443.12 5932.71 02-JAN-02:10 18599.73 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 12.01 109.08 02-JAN-02:10 981.75 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 12.01 109.08 02-JAN-02:10 981.75 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 13.51 122.77 02-JAN-02:10 1104.91 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 13.51 122.77 02-JAN-02:10 1104.91 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 13.51 122.77 02-JAN-02:10 1104.91 02-JAN-20:10
InteriorEquipment:Electricity 1728.14 25282.18 02-JAN-02:10 88863.15 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1728.14 25282.18 02-JAN-02:10 88863.15 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 952.41 15101.09 02-JAN-02:10 59188.31 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 952.41 15101.09 02-JAN-02:10 59188.31 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 424.02 5682.48 01-JAN-00:10 16179.04 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
Refrigeration:Electricity 43.82 732.79 23-APR-22:30 2790.51 12-NOV-11:20
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
Electricity:Plant 2336.54 2223.08 12-DEC-01:50 234862.41 28-JUN-18:20
LowTempRefrigeration:Refrigeration:Electricity 15.77 0.00 01-JAN-11:10 1308.17 17-JUN-10:50
MedTempRefrigeration:Refrigeration:Electricity 20.96 610.13 07-DEC-04:10 716.75 13-NOV-14:10
WaterSystems:Electricity 475.79 1086.56 04-AUG-00:40 44847.95 01-NOV-18:40
Electricity:HVAC 784.07 12218.33 12-FEB-15:00 60975.80 07-SEP-21:10
Fans:Electricity 611.35 11423.93 29-JAN-03:50 50202.41 07-SEP-21:10
General:Fans:Electricity 611.35 11423.93 29-JAN-03:50 50202.41 07-SEP-21:10
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ExteriorEquipment:Electricity 641.45 9451.13 02-JAN-02:20 39153.57 02-JAN-07:20
Transformer:ExteriorEquipment:Electricity 22.42 386.32 02-JAN-02:20 1279.09 02-JAN-21:10
ElectricityPurchased:Facility 6193.13 67247.62 08-MAR-02:50 437675.20 29-JUN-19:30
ElectricityPurchased:Plant 6193.13 67247.62 08-MAR-02:50 437675.20 29-JUN-19:30
Cogeneration:ElectricityPurchased 6193.13 67247.62 08-MAR-02:50 437675.20 29-JUN-19:30
General:Cogeneration:ElectricityPurchased 6193.13 67247.62 08-MAR-02:50 437675.20 29-JUN-19:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 6193.13 67247.62 08-MAR-02:50 437675.20 29-JUN-19:30
ElectricityNet:Plant 6193.13 67247.62 08-MAR-02:50 437675.20 29-JUN-19:30
Cogeneration:ElectricityNet 6193.13 67247.62 08-MAR-02:50 437675.20 29-JUN-19:30
General:Cogeneration:ElectricityNet 6193.13 67247.62 08-MAR-02:50 437675.20 29-JUN-19:30
ExteriorLights:Electricity 174.52 0.00 01-JAN-07:30 11096.45 01-JAN-00:10
General:ExteriorLights:Electricity 174.52 0.00 01-JAN-07:30 11096.45 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 616.11 9046.01 01-JAN-00:10 37691.69 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 2.91 18.80 01-JAN-00:10 188.00 01-JAN-07:10
HeatRecovery:Electricity 150.30 0.00 01-JAN-11:10 9938.94 01-APR-09:00
General:HeatRecovery:Electricity 150.30 0.00 01-JAN-11:10 9938.94 01-APR-09:00
Water Heater:WaterSystems:Electricity 90.75 1086.56 04-AUG-00:40 4738.76 05-OCT-18:10
Water Heater Parasitic:WaterSystems:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 1689.08 0.00 01-JAN-00:10 188698.43 28-JUN-18:10
General:Cooling:Electricity 1689.08 0.00 01-JAN-00:10 188698.43 28-JUN-18:10
Pumps:Electricity 134.94 48.12 24-MAR-14:50 6743.74 28-JUN-19:10
General:Pumps:Electricity 134.94 48.12 24-MAR-14:50 6743.74 28-JUN-19:10
WIRED_LTG_ELECTRICITY 19.14 0.00 01-JAN-00:10 1598.93 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 3000.86 29270.80 11-MAR-02:10 297676.92 07-DEC-21:00
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 1212.03 15908.90 05-JAN-11:10 248946.80 16-DEC-23:40
WaterSystems:NaturalGas 819.38 15908.90 01-JAN-09:10 83451.25 31-DEC-21:00
Water Heater:WaterSystems:NaturalGas 819.38 15908.90 01-JAN-09:10 83451.25 31-DEC-21:00
Heating:NaturalGas 392.65 0.00 02-JAN-19:20 186036.48 01-JAN-00:10
Boiler:Heating:NaturalGas 392.65 0.00 02-JAN-19:20 186036.48 01-JAN-00:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 5376.87 0.00 01-JAN-00:10 598761.53 10-SEP-22:00
PlantLoopCoolingDemand:HVAC 5376.87 0.00 01-JAN-00:10 598761.53 10-SEP-22:00
CoolingCoils:PlantLoopCoolingDemand 5376.87 0.00 01-JAN-00:10 598761.53 10-SEP-22:00


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 24-JAN-22:00
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 24-JAN-22:00
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 24-JAN-22:00
Water Heater:WaterSystems:Water 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:20
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 24-JAN-22:00
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 24-JAN-22:00
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 24-JAN-22:00
Water Heater:WaterSystems:MainsWater 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:20
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 04-APR-06:40
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 04-APR-06:40


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 27083.55 119820.48 06-MAR-11:30 2387254.25 13-JUL-18:20
EnergyTransfer:Building 5875.95 86196.34 12-FEB-15:00 390308.45 28-JUN-18:20
EnergyTransfer:Zone:KITCHEN_FLR_6 721.23 10289.60 07-DEC-04:00 35505.96 13-AUG-10:40
Refrigeration:EnergyTransfer 181.60 4016.05 23-APR-22:20 10366.86 04-AUG-06:30
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 90.80 2008.03 23-APR-22:20 5183.43 04-AUG-06:30
General:Refrigeration:EnergyTransfer 90.80 2008.03 23-APR-22:20 5183.43 04-AUG-06:30
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 90.80 2008.03 23-APR-22:20 5183.43 04-AUG-06:30
EnergyTransfer:Plant 13647.02 17102.43 24-MAR-14:50 1378041.68 10-SEP-22:00
LowTempRefrigeration:Refrigeration:EnergyTransfer 21.56 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 69.24 1815.73 07-DEC-04:10 2559.91 13-NOV-14:10
EnergyTransfer:HVAC 7560.58 372.03 24-MAR-14:20 798271.57 13-JUL-18:20
CoolingCoils:EnergyTransfer 6505.50 0.00 01-JAN-00:10 677961.63 02-SEP-20:30
EnergyTransfer:Zone:BASEMENT 368.36 7698.31 27-MAR-14:00 21680.88 20-SEP-21:00
Heating:EnergyTransfer 19.93 0.00 01-JAN-11:10 29888.41 07-DEC-06:00
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 19.93 0.00 01-JAN-11:10 29888.41 07-DEC-06:00
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 5765.22 81862.95 01-JAN-06:00 386765.84 28-JUN-18:20
Cooling:EnergyTransfer:Zone:BASEMENT 368.36 7698.31 27-MAR-14:00 21680.88 20-SEP-21:00
General:Cooling:EnergyTransfer 5765.22 81862.95 01-JAN-06:00 386765.84 28-JUN-18:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 368.36 7698.31 27-MAR-14:00 21680.88 20-SEP-21:00
EnergyTransfer:Zone:RETAIL_1_FLR_1 54.38 0.35 26-MAR-02:40 3946.58 02-OCT-12:40
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.02 0.00 01-JAN-00:10 386.94 16-DEC-07:20
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.02 0.00 01-JAN-00:10 386.94 16-DEC-07:20
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 54.36 0.00 01-JAN-05:30 3946.58 02-OCT-12:40
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 54.36 0.00 01-JAN-05:30 3946.58 02-OCT-12:40
EnergyTransfer:Zone:RETAIL_2_FLR_1 40.60 767.79 12-FEB-16:00 2550.53 28-JUN-20:40
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 40.60 767.79 12-FEB-16:00 2550.53 28-JUN-20:40
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 40.60 767.79 12-FEB-16:00 2550.53 28-JUN-20:40
EnergyTransfer:Zone:MECH_FLR_1 34.53 1.49 07-DEC-03:50 2615.74 28-JUN-20:00
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 57.73 07-DEC-05:00
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 57.73 07-DEC-05:00
Cooling:EnergyTransfer:Zone:MECH_FLR_1 34.53 0.00 07-DEC-03:50 2615.74 28-JUN-20:00
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 34.53 0.00 07-DEC-03:50 2615.74 28-JUN-20:00
EnergyTransfer:Zone:STORAGE_FLR_1 18.26 0.03 06-DEC-05:40 1314.73 28-JUN-18:50
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.00 0.00 01-JAN-00:10 89.31 07-DEC-05:00
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.00 0.00 01-JAN-00:10 89.31 07-DEC-05:00
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 18.26 0.00 01-JAN-04:20 1314.73 28-JUN-18:50
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 18.26 0.00 01-JAN-04:20 1314.73 28-JUN-18:50
EnergyTransfer:Zone:LAUNDRY_FLR_1 618.91 9700.14 07-DEC-05:00 40074.74 28-JUN-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 618.91 9700.14 07-DEC-05:00 40074.74 28-JUN-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 618.91 9700.14 07-DEC-05:00 40074.74 28-JUN-20:00
EnergyTransfer:Zone:CAFE_FLR_1 262.35 2736.75 12-FEB-16:00 14213.89 01-NOV-15:10
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 262.35 2736.75 12-FEB-16:00 14213.89 01-NOV-15:10
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 262.35 2736.75 12-FEB-16:00 14213.89 01-NOV-15:10
EnergyTransfer:Zone:LOBBY_FLR_1 863.06 16314.22 12-FEB-16:00 47581.75 28-JUN-21:10
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 863.06 16314.22 12-FEB-16:00 47581.75 28-JUN-21:10
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 863.06 16314.22 12-FEB-16:00 47581.75 28-JUN-21:10
EnergyTransfer:Zone:ROOM_1_FLR_3 93.29 0.00 01-JAN-08:10 13017.83 27-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 2.21 0.00 01-JAN-08:10 2824.24 07-DEC-06:00
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 2.21 0.00 01-JAN-08:10 2824.24 07-DEC-06:00
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 91.08 0.00 01-JAN-00:10 13017.83 27-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 91.08 0.00 01-JAN-00:10 13017.83 27-JUN-18:10
EnergyTransfer:Zone:ROOM_2_FLR_3 79.90 0.00 01-JAN-08:10 13283.21 27-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 4.11 0.00 01-JAN-08:10 4419.37 07-DEC-09:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 4.11 0.00 01-JAN-08:10 4419.37 07-DEC-09:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 75.79 0.00 01-JAN-00:10 13283.21 27-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 75.79 0.00 01-JAN-00:10 13283.21 27-JUN-18:10
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 490.09 0.00 01-JAN-00:10 50084.80 20-NOV-14:30
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 721.34 09-JAN-08:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 721.34 09-JAN-08:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 490.09 0.00 01-JAN-00:10 50084.80 20-NOV-14:30
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 490.09 0.00 01-JAN-00:10 50084.80 20-NOV-14:30
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 570.16 0.00 01-JAN-08:10 79584.72 26-JUN-18:20
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 3.25 0.00 01-JAN-08:10 15827.15 07-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 3.25 0.00 01-JAN-08:10 15827.15 07-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 566.92 0.00 01-JAN-00:10 79584.72 26-JUN-18:20
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 566.92 0.00 01-JAN-00:10 79584.72 26-JUN-18:20
EnergyTransfer:Zone:ROOM_5_FLR_3 96.31 0.00 01-JAN-08:10 10638.92 19-JUN-08:10
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 2.21 0.00 01-JAN-08:10 2840.65 07-DEC-06:00
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 2.21 0.00 01-JAN-08:10 2840.65 07-DEC-06:00
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 94.10 0.00 01-JAN-00:10 10638.92 19-JUN-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 94.10 0.00 01-JAN-00:10 10638.92 19-JUN-08:10
EnergyTransfer:Zone:ROOM_6_FLR_3 82.24 0.00 01-JAN-08:10 11972.11 01-JUL-08:20
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 3.98 0.00 01-JAN-08:10 3551.37 07-DEC-06:00
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 3.98 0.00 01-JAN-08:10 3551.37 07-DEC-06:00
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 78.26 0.00 01-JAN-00:10 11972.11 01-JUL-08:20
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 78.26 0.00 01-JAN-00:10 11972.11 01-JUL-08:20
EnergyTransfer:Zone:CORRIDOR_FLR_3 197.23 552.33 18-DEC-07:10 13562.06 28-JUN-18:30
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 197.23 552.33 18-DEC-07:10 13562.06 28-JUN-18:30
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 197.23 552.33 18-DEC-07:10 13562.06 28-JUN-18:30
EnergyTransfer:Zone:ROOM_1_FLR_6 24.18 0.00 01-JAN-08:10 3506.03 27-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 1.17 0.00 01-JAN-08:10 997.37 07-DEC-06:00
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 1.17 0.00 01-JAN-08:10 997.37 07-DEC-06:00
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 23.01 0.00 01-JAN-00:10 3506.03 27-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 23.01 0.00 01-JAN-00:10 3506.03 27-JUN-18:10
EnergyTransfer:Zone:ROOM_2_FLR_6 21.32 0.00 01-JAN-08:10 3569.78 27-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 1.92 0.00 01-JAN-08:10 1212.92 07-DEC-09:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 1.92 0.00 01-JAN-08:10 1212.92 07-DEC-09:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 19.40 0.00 01-JAN-00:10 3569.78 27-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 19.40 0.00 01-JAN-00:10 3569.78 27-JUN-18:10
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 141.27 0.00 01-JAN-08:10 16568.90 18-OCT-15:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 1.05 0.00 01-JAN-00:10 2786.58 27-MAR-08:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 1.05 0.00 01-JAN-00:10 2786.58 27-MAR-08:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 140.22 0.00 01-JAN-01:20 16568.90 18-OCT-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 140.22 0.00 01-JAN-01:20 16568.90 18-OCT-15:10
EnergyTransfer:Zone:BANQUET_FLR_6 472.92 8948.31 07-DEC-09:50 24852.60 28-JUN-21:20
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 472.92 8948.31 07-DEC-09:50 24852.60 28-JUN-21:20
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 472.92 8948.31 07-DEC-09:50 24852.60 28-JUN-21:20
EnergyTransfer:Zone:DINING_FLR_6 509.62 9930.37 07-DEC-10:10 26035.81 28-JUN-21:20
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DINING_FLR_6 509.62 9930.37 07-DEC-10:10 26035.81 28-JUN-21:20
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 509.62 9930.37 07-DEC-10:10 26035.81 28-JUN-21:20
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 630.43 8230.89 07-DEC-04:00 30420.69 13-AUG-10:40
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 630.43 8230.89 07-DEC-04:00 30420.69 13-AUG-10:40
EnergyTransfer:Zone:CORRIDOR_FLR_6 115.74 0.14 17-DEC-04:30 7817.70 28-JUN-18:10
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.01 0.00 01-JAN-00:10 665.30 07-DEC-07:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.01 0.00 01-JAN-00:10 665.30 07-DEC-07:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 115.73 0.00 01-JAN-05:10 7817.70 28-JUN-18:10
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 115.73 0.00 01-JAN-05:10 7817.70 28-JUN-18:10
PlantLoopHeatingDemand:Facility 2384.59 6709.43 25-JUL-00:20 286159.54 16-DEC-22:50
PlantLoopHeatingDemand:Plant 2102.04 6709.43 25-JUL-00:20 199686.11 03-APR-20:40
WaterSystems:PlantLoopHeatingDemand 2102.04 6709.43 25-JUL-00:20 199686.11 03-APR-20:40
General:WaterSystems:PlantLoopHeatingDemand 601.64 6705.93 25-JUL-00:10 47140.96 24-JAN-07:10
HeatingCoils:EnergyTransfer 282.55 0.00 02-JAN-19:20 150227.63 01-JAN-00:10
PlantLoopHeatingDemand:HVAC 282.55 0.00 02-JAN-19:20 150227.63 01-JAN-00:10
HeatingCoils:PlantLoopHeatingDemand 282.55 0.00 02-JAN-19:20 150227.63 01-JAN-00:10
HeatRecoveryForHeating:EnergyTransfer 272.99 0.00 01-JAN-11:10 307388.31 05-DEC-07:00
HeatRecoveryForCooling:EnergyTransfer 499.55 0.00 01-JAN-00:10 170936.50 17-JUN-16:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 1500.40 0.00 01-JAN-00:10 165700.75 03-APR-20:40
WaterSystems:EnergyTransfer 601.64 6705.93 25-JUL-00:10 47140.96 24-JAN-07:10
WaterUse:WaterSystems:EnergyTransfer 601.64 6705.93 25-JUL-00:10 47140.96 24-JAN-07:10
Boilers:EnergyTransfer 279.96 0.00 02-JAN-19:20 153038.25 01-JAN-00:10
Chillers:EnergyTransfer 5492.77 0.00 01-JAN-00:10 607345.13 10-SEP-22:00
HeatRejection:EnergyTransfer 7181.86 0.00 01-JAN-00:10 743008.09 10-SEP-22:00
General:HeatRejection:EnergyTransfer 7181.86 0.00 01-JAN-00:10 743008.09 10-SEP-22:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.000 -368.364 0.000 0.000 139.859 102.033 143.105 0.000 0.000 0.000 0.001 0.000 0.000 0.000 0.000 -16.634
RETAIL_1_FLR_1 0.000 0.000 0.015 -54.361 0.000 0.000 14.634 5.638 10.186 26.079 0.000 1.644 5.282 0.000 -6.569 0.000 -2.548 -0.000
RETAIL_2_FLR_1 0.000 0.000 0.000 -40.596 0.000 0.000 16.269 6.529 11.795 0.000 0.000 0.641 6.461 0.000 0.000 0.000 -1.098 -0.000
MECH_FLR_1 0.000 0.000 0.000 -34.528 0.000 0.000 3.592 7.530 12.471 0.000 0.000 1.551 11.644 0.000 0.000 0.000 -2.260 -0.000
STORAGE_FLR_1 0.000 0.000 0.002 -18.259 0.000 0.000 2.777 1.680 3.598 0.000 0.000 0.899 10.587 0.000 0.000 0.000 -1.284 -0.000
LAUNDRY_FLR_1 0.000 0.000 0.000 -618.910 0.000 0.000 11.134 4.410 658.131 0.000 0.000 2.217 0.000 0.000 0.000 0.000 -3.562 -53.419
CAFE_FLR_1 0.000 0.000 0.000 -262.353 0.000 0.000 182.506 11.670 14.341 72.547 0.000 3.621 4.473 0.000 -20.269 0.000 -6.535 -0.000
LOBBY_FLR_1 0.000 0.000 0.000 -863.064 0.000 0.000 538.855 110.757 148.998 96.713 0.000 10.394 2.939 0.000 -26.678 0.000 -18.915 -0.000
ROOM_1_FLR_3 3.731 -80.778 0.000 -11.825 0.000 0.000 9.648 5.554 12.292 56.941 0.000 5.091 18.770 0.000 -13.446 0.000 -5.978 -0.000
ROOM_2_FLR_3 6.226 -65.806 0.000 -12.104 0.000 0.000 9.587 5.553 12.291 44.087 0.000 4.973 15.311 0.000 -13.900 0.000 -6.219 -0.001
ROOM_3_MULT19_FLR_3 0.000 -473.840 0.000 -16.241 0.000 0.000 0.000 66.316 228.754 289.257 0.000 12.352 59.530 0.000 -114.984 0.000 -51.146 -0.001
ROOM_4_MULT19_FLR_3 12.306 -413.265 0.000 -162.709 0.000 0.000 182.692 66.334 228.817 135.693 0.000 27.041 37.698 0.000 -73.108 0.000 -41.499 -0.008
ROOM_5_FLR_3 3.701 -83.755 0.000 -11.831 0.000 0.000 9.638 5.554 12.292 58.746 0.000 5.085 19.448 0.000 -12.838 0.000 -6.041 -0.001
ROOM_6_FLR_3 5.931 -68.084 0.000 -12.129 0.000 0.000 9.578 5.553 12.291 45.281 0.000 4.955 15.645 0.000 -12.757 0.000 -6.263 -0.001
CORRIDOR_FLR_3 0.000 0.000 0.000 -197.230 0.000 0.000 112.530 51.065 0.000 50.759 0.000 4.677 3.261 0.000 -17.838 0.000 -7.225 -0.000
ROOM_1_FLR_6 1.675 -20.563 0.000 -2.956 0.000 0.000 2.413 1.388 3.073 14.177 0.000 1.265 4.347 0.000 -3.301 0.000 -1.519 -0.000
ROOM_2_FLR_6 2.550 -17.008 0.000 -3.016 0.000 0.000 2.401 1.388 3.073 10.997 0.000 1.236 3.343 0.000 -3.396 0.000 -1.566 -0.000
ROOM_3_MULT9_FLR_6 2.280 -122.420 0.000 -19.026 0.000 0.000 21.678 7.855 27.097 71.709 0.000 5.911 28.090 0.000 -15.269 0.000 -7.906 -0.000
BANQUET_FLR_6 0.000 0.000 0.000 -472.928 0.000 0.000 315.199 25.706 175.857 13.104 0.000 2.240 0.000 0.000 -11.099 0.000 -4.433 -43.647
DINING_FLR_6 0.000 0.000 0.000 -509.621 0.000 0.000 314.585 25.706 175.857 12.810 0.000 2.233 0.001 0.000 -11.461 0.000 -4.478 -5.631
KITCHEN_FLR_6 0.000 0.000 0.000 -630.414 0.000 0.000 28.241 12.005 540.650 27.503 0.000 1.997 32.072 0.000 -8.084 0.000 -3.970 -0.001
CORRIDOR_FLR_6 0.000 0.000 0.011 -115.733 0.000 0.000 29.983 13.511 0.000 24.136 0.000 2.014 57.201 0.000 -7.987 0.000 -3.135 -0.000
Total Facility 38.401 -1345.518 0.029 -4438.199 0.000 0.000 1957.799 543.736 2434.967 1050.540 0.000 102.037 336.102 0.000 -372.983 0.000 -187.578 -119.345


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 20-SEP-21:00 0.00 0.00 0.00 -21683.07 0.00 0.00 5924.36 7417.00 9125.55 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -783.84
RETAIL_1_FLR_1 02-OCT-12:40 0.00 0.00 0.00 -3946.68 0.00 0.00 150.60 128.08 252.59 4115.96 0.00 185.46 0.00 0.00 -0.00 0.00 0.00 -886.00
RETAIL_2_FLR_1 28-JUN-20:40 0.00 0.00 0.00 -2550.22 0.00 0.00 697.62 474.61 752.15 0.00 0.00 82.75 543.10 0.00 -0.00 0.00 0.00 0.00
MECH_FLR_1 28-JUN-20:00 0.00 0.00 0.00 -2615.22 0.00 0.00 129.09 615.76 839.45 0.00 0.00 216.98 813.95 0.00 -0.00 0.00 0.00 0.00
STORAGE_FLR_1 28-JUN-18:40 0.00 0.00 0.00 -1314.60 0.00 0.00 99.30 122.09 229.41 0.00 0.00 155.82 707.98 0.00 -0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 28-JUN-20:00 0.00 0.00 0.00 -40067.37 0.00 0.00 408.91 360.62 44299.38 0.00 0.00 296.31 0.00 0.00 -0.00 0.00 0.00 -5297.85
CAFE_FLR_1 01-NOV-15:03 0.00 0.00 0.00 -14229.08 0.00 0.00 4947.93 86.54 355.63 10241.48 0.00 201.28 0.00 0.00 -0.00 0.00 0.00 -1603.78
LOBBY_FLR_1 28-JUN-21:10 0.00 0.00 0.00 -47579.00 0.00 0.00 26440.45 6387.23 7389.94 1187.04 0.00 1242.24 4932.11 0.00 -0.00 0.00 0.00 0.00
ROOM_1_FLR_3 27-JUN-18:02 0.00 -14108.28 0.00 -679.26 0.00 0.00 335.50 380.45 516.26 7397.47 0.00 718.78 5439.09 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_3 01-JUL-08:61 0.00 -15759.20 0.00 -818.79 0.00 0.00 109.58 239.35 653.15 1157.97 0.00 117.65 14300.29 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 20-NOV-14:30 0.00 -50083.62 0.00 0.00 0.00 0.00 0.00 1429.19 5097.90 54276.09 0.00 67.06 0.00 0.00 -0.00 0.00 0.00 -10786.63
ROOM_4_MULT19_FLR_3 01-JUL-08:61 0.00 -93367.56 0.00 -10668.99 0.00 0.00 2238.95 2859.17 12159.85 8677.56 0.00 730.84 77370.19 0.00 -0.00 0.00 0.00 0.00
ROOM_5_FLR_3 01-JUL-08:61 0.00 -12506.30 0.00 -687.90 0.00 0.00 130.71 239.38 653.23 6967.05 0.00 202.09 5001.73 0.00 -0.00 0.00 0.00 0.00
ROOM_6_FLR_3 21-MAY-08:61 0.00 -14953.53 0.00 -942.17 0.00 0.00 89.64 239.35 653.15 7244.13 0.00 0.00 7725.37 0.00 -0.00 0.00 -55.94 0.00
CORRIDOR_FLR_3 28-JUN-18:25 0.00 0.00 0.00 -13564.49 0.00 0.00 4080.30 3712.00 0.00 4120.49 0.00 837.02 814.67 0.00 -0.00 0.00 0.00 0.00
ROOM_1_FLR_6 27-JUN-18:02 0.00 -3763.68 0.00 -169.81 0.00 0.00 83.87 95.11 129.07 1838.51 0.00 179.11 1607.82 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_6 01-JUL-08:61 0.00 -4129.91 0.00 -200.09 0.00 0.00 27.91 59.84 163.29 296.70 0.00 31.72 3750.54 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 18-OCT-15:01 0.00 -16733.13 0.00 -1108.41 0.00 0.00 529.39 169.29 603.86 8090.22 0.00 352.20 8096.58 0.00 -0.00 0.00 0.00 0.00
BANQUET_FLR_6 28-JUN-21:20 0.00 0.00 0.00 -24852.43 0.00 0.00 15617.93 1657.87 6747.90 490.43 0.00 267.65 70.64 0.00 -0.00 0.00 0.00 0.00
DINING_FLR_6 28-JUN-21:20 0.00 0.00 0.00 -26035.71 0.00 0.00 15616.83 1657.87 6747.90 476.87 0.00 267.64 1268.59 0.00 -0.00 0.00 0.00 0.00
KITCHEN_FLR_6 13-AUG-10:50 0.00 0.00 0.00 -30414.78 0.00 0.00 462.87 327.25 23951.61 3055.87 0.00 229.19 2387.99 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 28-JUN-18:04 0.00 0.00 0.00 -7824.75 0.00 0.00 1079.64 982.15 0.00 1710.65 0.00 376.09 3676.22 0.00 -0.00 0.00 0.00 0.00
Total Facility 27-JUN-18:02 0.00 -194984.86 0.00 -220313.14 0.00 0.00 74262.07 36672.72 121562.63 81275.35 0.00 16735.94 84789.28 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 16-DEC-07:20 0.00 0.00 386.89 0.00 0.00 0.00 447.54 153.69 288.68 0.00 0.00 0.00 120.72 0.00 -993.58 0.00 -403.93 0.00
RETAIL_2_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MECH_FLR_1 07-DEC-05:00 0.00 0.00 57.73 0.00 0.00 0.00 197.29 68.42 176.73 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -419.50 -80.67
STORAGE_FLR_1 07-DEC-05:00 0.00 0.00 89.32 0.00 0.00 0.00 151.77 15.26 50.98 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -242.03 -65.29
LAUNDRY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 07-DEC-09:01 8242.30 343.96 0.00 -343.96 0.00 0.00 104.56 188.08 453.05 1441.44 0.00 0.00 0.00 0.00 -0.00 0.00 -655.92 -9773.50
ROOM_2_FLR_3 06-DEC-09:01 8474.53 277.06 0.00 -277.06 0.00 0.00 108.88 188.06 452.99 0.00 0.00 0.00 0.00 0.00 -892.87 0.00 -619.18 -7712.42
ROOM_3_MULT19_FLR_3 09-JAN-08:10 1442.65 0.00 0.00 0.00 0.00 0.00 0.00 2245.87 8431.14 9130.47 0.00 0.00 0.00 0.00 -0.00 0.00 -4290.58 -16959.56
ROOM_4_MULT19_FLR_3 07-DEC-09:01 46912.85 4950.85 0.00 -4950.85 0.00 0.00 1928.32 2246.49 8433.45 0.00 0.00 0.00 0.00 0.00 -5322.14 0.00 -3556.08 -50642.88
ROOM_5_FLR_3 12-FEB-19:02 7425.56 378.78 0.00 -378.78 0.00 0.00 335.46 427.46 516.26 0.00 0.00 0.00 0.00 0.00 -1020.20 0.00 -419.13 -7265.41
ROOM_6_FLR_3 07-DEC-16:01 7851.21 372.99 0.00 -372.99 0.00 0.00 277.09 119.68 273.90 0.00 0.00 0.00 0.00 0.00 -583.87 0.00 -679.02 -7258.99
CORRIDOR_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 06-DEC-09:01 2462.13 77.19 0.00 -77.19 0.00 0.00 26.86 47.02 113.26 399.46 0.00 0.00 0.00 0.00 -0.00 0.00 -161.01 -2887.73
ROOM_2_FLR_6 06-DEC-09:01 2503.09 70.44 0.00 -70.44 0.00 0.00 27.22 47.02 113.25 0.00 0.00 0.00 0.00 0.00 -211.93 0.00 -156.33 -2322.31
ROOM_3_MULT9_FLR_6 27-MAR-08:62 11058.80 604.78 0.00 -604.78 0.00 0.00 230.87 266.03 998.70 233.26 0.00 0.00 0.00 0.00 -0.00 0.00 -609.36 -12178.29
BANQUET_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 07-DEC-07:05 0.00 0.00 665.46 0.00 0.00 0.00 733.29 613.84 0.00 0.00 0.00 0.00 0.00 0.00 -1349.76 0.00 -507.07 -155.76
Total Facility 07-DEC-09:01 -41867.10 106613.63 14.63 -106613.63 0.00 0.00 22704.08 18329.68 87870.62 70468.54 0.00 0.00 0.00 0.00 -8025.17 0.00 -18715.08 -130780.20



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 23.3070 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 23.1972 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 11.6535 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.6535 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.000000 12.5400 0.001181 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.000000 142.3000 0.003581 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.001045 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.3518 2.3518 1.1759 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3688 0.3688 0.1844 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2564 0.2564 0.1282 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2462 0.2462 0.1231 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1357 0.1357 0.0679 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.6391 3.6391 1.8195 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5611 1.5611 0.7805 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.1504 5.1504 2.5752 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4039 1.4039 0.7019 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.4278 2.4278 1.2139 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5443 2.5443 1.2721 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.4154 2.4154 1.2077 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8063 0.8063 0.4031 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 23.3070 23.1972 23.3070 11.6535 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1759 1.1759 1.1759 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1844 0.1844 0.1844 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1282 0.1282 0.1282 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1231 0.1231 0.1231 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0679 0.0679 0.0679 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.8195 1.8195 1.8195 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7805 0.7805 0.7805 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5752 2.5752 2.5752 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7019 0.7019 0.7019 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2139 1.2139 1.2139 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2721 1.2721 1.2721 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2077 1.2077 1.2077 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4031 0.4031 0.4031 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 11.6535 11.6535 11.6535 11.6535 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 76.00
Number of hours not met 76.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 392.65 186036.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 1689.08 188698.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 543.74 45424.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 174.52 11096.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 952.41 59188.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 8.75 277.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 4.94 156.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 22.42 1279.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 616.11 37691.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 2.91 188.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 611.35 50202.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 134.94 6743.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 150.30 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.75 4738.76 819.38 83451.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Other 0.00 40109.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.09 2093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 15.77 1308.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 20.96 716.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1771.96 6193.13
Natural Gas 1788.84 3000.86
Additional 0.00 0.00
Total 3560.80 9193.99


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 47.93
Space Heating 0.00
Space Cooling 148.88
Fans (All) 53.89
Service Water Heating 41.94
Receptacle Equipment 152.32
Miscellaneous (All) 545.88
Subtotal 545.88


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 34.61
Service Water Heating 72.22
Miscellaneous (All) 264.50
Subtotal 264.50


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 5.91
Space Heating 4.27
Space Cooling 18.37
Fans (All) 6.65
Service Water Heating 14.09
Receptacle Equipment 38.25
Miscellaneous 12.45


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2398. 8760.
LTG_SCH_LOBBY 3061. 8760.
LTG_SCH_STORAGE 1339. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 3061. 8760.
LTG_SCH_GUESTROOM 2482. 8760.
LTG_SCH_CORRIDOR 2295. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_2 1591. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3737. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 5740. 6205.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 0. 0.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 15.56 365 15.56 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 26.67 365 26.67 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8322.00 438.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8757.50 2.50 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8322.00 0.00 0.00 0.00 0.00
Max 8760.00 438.00 0.00 0.00 0.00
Average 8739.98 20.02 0.00 0.00 0.00
Sum 192279.50 440.50 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 0.00 0.00 0.00 0.00
Average 288887.05 0.00 0.00 0.00 0.00
Sum 6355515.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8747.33 12.67 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8221.33 538.67 0.00 0.00 0.00
LOBBY_FLR_1 8347.50 412.50 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8744.83 15.17 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8154.50 605.50 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8754.83 5.17 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8726.17 33.83 0.00 0.00 0.00
CORRIDOR_FLR_3 8648.50 111.50 0.00 0.00 0.00
ROOM_1_FLR_6 8759.33 0.67 0.00 0.00 0.00
ROOM_2_FLR_6 8743.33 16.67 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8759.83 0.17 0.00 0.00 0.00
BANQUET_FLR_6 8265.00 495.00 0.00 0.00 0.00
DINING_FLR_6 8305.33 454.67 0.00 0.00 0.00
KITCHEN_FLR_6 8727.50 32.50 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8154.50 0.00 0.00 0.00 0.00
Max 8760.00 605.50 0.00 0.00 0.00
Average 8635.70 124.30 0.00 0.00 0.00
Sum 189985.33 2734.67 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59017.67 138.33 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 646172.83 64244.17 0.00 0.00 0.00
LOBBY_FLR_1 1969793.50 145635.50 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4150.33 3.67 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4152.17 1.83 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4150.50 3.50 0.00 0.00 0.00
CORRIDOR_FLR_3 98418.33 1939.67 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4150.00 4.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1142247.50 103467.50 0.00 0.00 0.00
DINING_FLR_6 1149615.50 96099.50 0.00 0.00 0.00
KITCHEN_FLR_6 108027.67 241.33 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 1969793.50 145635.50 0.00 0.00 0.00
Average 270169.82 18717.23 0.00 0.00 0.00
Sum 5943736.00 411779.00 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:03:03

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 8760.00 0.00 0.00
LOBBY_FLR_1 0.00 8760.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 8760.00 0.00 0.00
DINING_FLR_6 0.00 8760.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 1592.73 0.00 0.00
Sum 0.00 35040.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 710417.00 0.00 0.00
LOBBY_FLR_1 0.00 2115429.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 1245715.00 0.00 0.00
DINING_FLR_6 0.00 1245715.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 2115429.00 0.00 0.00
Average 0.00 241694.36 0.00 0.00
Sum 0.00 5317276.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

For: Environment

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B

For: Environment

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON

For: Environment

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.289497E+11 14006.18 20-JAN-22:00 13.30 10.27 0.799088E+10 4837.08 27-JAN-22:19 11.67 4.41
February 0.229889E+11 12045.86 01-FEB-22:00 10.00 5.32 0.665323E+10 4836.94 01-FEB-22:19 9.33 4.99
March 0.233525E+11 10688.80 01-MAR-21:00 15.50 11.31 0.691660E+10 4439.42 01-MAR-22:10 14.30 10.92
April 0.247833E+11 11953.78 30-APR-10:33 30.00 11.09 0.692779E+10 4459.12 21-APR-22:10 30.00 11.09
May 0.248376E+11 11598.97 04-MAY-18:10 33.67 13.32 0.693779E+10 4384.09 01-MAY-22:10 33.67 13.32
June 0.259680E+11 12622.55 28-JUN-18:10 40.83 17.83 0.694571E+10 4436.77 13-JUN-22:10 40.83 17.83
July 0.315993E+11 16060.55 14-JUL-21:00 28.00 20.32 0.802823E+10 4837.13 07-JUL-22:10 28.00 20.32
August 0.351071E+11 18522.66 04-AUG-21:00 23.00 18.90 0.821754E+10 4837.08 21-AUG-00:20 26.00 16.49
September 0.390186E+11 21680.88 20-SEP-21:00 28.30 17.23 0.797177E+10 4837.12 15-SEP-03:09 28.30 17.23
October 0.392465E+11 21257.09 19-OCT-21:00 20.00 8.80 0.823198E+10 4837.25 19-OCT-21:00 20.00 11.28
November 0.369414E+11 20936.10 22-NOV-22:00 8.80 1.39 0.796067E+10 4837.23 01-NOV-01:39 8.80 1.39
December 0.355687E+11 20099.51 01-DEC-22:00 10.00 4.18 0.822005E+10 4837.35 12-DEC-22:10 12.83 9.59
                     
Annual Sum or Average 0.368362E+12         0.910022E+11        
Minimum of Months 0.229889E+11 10688.80   8.80 1.39 0.665323E+10 4384.09   8.80 1.39
Maximum of Months 0.392465E+11 21680.88   40.83 20.32 0.823198E+10 4837.35   40.83 20.32



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.427772E+10 3521.93 14-JAN-13:40 26.67 10.98 0.705078E+09 459.50 19-JAN-22:19 14.33 6.76
February 0.259851E+10 2491.68 01-FEB-14:00 16.00 7.74 0.591069E+09 429.94 01-FEB-00:10 16.00 7.74
March 0.321325E+10 2656.38 18-MAR-13:40 26.27 12.12 0.674469E+09 473.73 16-MAR-21:30 26.27 12.12
April 0.459690E+10 3114.38 14-APR-14:10 34.17 14.15 0.746877E+09 491.85 12-APR-23:10 34.17 14.15
May 0.479845E+10 2625.40 31-MAY-18:15 35.33 13.34 0.789310E+09 491.86 10-MAY-23:10 35.33 13.34
June 0.564041E+10 3504.82 28-JUN-18:13 40.67 17.68 0.798714E+09 491.86 09-JUN-23:19 40.67 17.68
July 0.559898E+10 3229.85 21-JUL-18:30 38.00 19.28 0.820573E+09 491.86 01-JUL-00:10 38.00 19.28
August 0.577296E+10 3682.42 28-AUG-12:30 37.00 20.85 0.819944E+09 491.84 27-AUG-23:30 37.00 20.85
September 0.550748E+10 3936.80 28-SEP-13:30 36.10 16.03 0.786333E+09 491.84 19-SEP-21:19 36.10 16.03
October 0.494349E+10 3946.58 02-OCT-12:40 34.00 19.29 0.756905E+09 491.85 19-OCT-21:49 20.00 10.88
November 0.401968E+10 3716.97 21-NOV-13:40 25.00 10.74 0.679959E+09 491.33 01-NOV-21:19 25.00 10.74
December 0.339302E+10 3392.75 25-DEC-13:30 25.50 11.81 0.671432E+09 455.17 26-DEC-22:19 14.67 7.12
                     
Annual Sum or Average 0.543608E+11         0.884066E+10        
Minimum of Months 0.259851E+10 2491.68   16.00 7.74 0.591069E+09 429.94   14.33 6.76
Maximum of Months 0.577296E+10 3946.58   40.67 20.85 0.820573E+09 491.86   40.67 20.85



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.293819E+10 1544.21 27-JAN-21:10 16.17 6.63 0.900152E+09 569.55 27-JAN-22:19 11.67 4.41
February 0.242151E+10 1288.98 01-FEB-21:00 11.00 5.83 0.770259E+09 569.51 01-FEB-22:19 9.33 4.99
March 0.282043E+10 1619.35 17-MAR-21:00 21.60 12.64 0.880347E+09 569.55 22-MAR-21:40 12.00 6.59
April 0.343005E+10 2222.83 14-APR-20:40 29.67 13.44 0.920248E+09 569.56 16-APR-23:10 18.83 12.52
May 0.374746E+10 2175.68 19-MAY-20:10 30.67 12.42 0.960315E+09 569.57 10-MAY-23:19 30.67 12.42
June 0.417705E+10 2550.53 28-JUN-20:40 35.67 14.90 0.938790E+09 569.57 09-JUN-23:19 35.67 14.90
July 0.413458E+10 2403.65 20-JUL-20:10 35.17 18.52 0.965007E+09 569.56 01-JUL-00:10 35.17 18.52
August 0.411570E+10 2447.72 15-AUG-20:10 34.67 18.05 0.968429E+09 569.55 04-AUG-22:10 34.67 18.05
September 0.379683E+10 2399.50 07-SEP-21:00 33.30 19.43 0.933720E+09 569.55 21-SEP-22:10 20.92 16.58
October 0.339218E+10 2197.55 05-OCT-20:10 26.50 13.28 0.937683E+09 569.57 19-OCT-21:00 20.00 11.28
November 0.288773E+10 1848.56 01-NOV-20:10 20.50 13.68 0.875598E+09 569.55 02-NOV-22:10 19.83 16.01
December 0.273433E+10 1443.37 26-DEC-22:00 15.00 7.29 0.863942E+09 569.52 26-DEC-22:10 14.83 7.20
                     
Annual Sum or Average 0.405960E+11         0.109145E+11        
Minimum of Months 0.242151E+10 1288.98   11.00 5.83 0.770259E+09 569.51   9.33 4.41
Maximum of Months 0.417705E+10 2550.53   35.67 19.43 0.968429E+09 569.57   35.67 18.52



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.221534E+10 1087.04 08-JAN-11:33 20.33 13.54 0.163125E+09 104.83 27-JAN-22:10 11.83 4.49
February 0.180984E+10 988.46 01-FEB-21:00 11.00 5.83 0.141462E+09 101.00 01-FEB-00:10 11.00 5.83
March 0.220743E+10 1176.39 18-MAR-18:10 25.13 12.09 0.163878E+09 110.08 17-MAR-21:19 25.13 12.09
April 0.280369E+10 1512.28 14-APR-20:00 31.00 13.66 0.182269E+09 120.45 14-APR-21:19 28.33 13.07
May 0.322654E+10 1818.16 19-MAY-20:00 31.00 12.54 0.198931E+09 120.46 10-MAY-23:30 31.00 12.54
June 0.405634E+10 2615.74 28-JUN-20:00 37.00 15.57 0.198971E+09 120.46 09-JUN-23:40 37.00 15.57
July 0.404284E+10 2501.02 21-JUL-20:00 37.00 20.84 0.204528E+09 120.46 07-JUL-22:10 37.00 20.84
August 0.381745E+10 2357.90 15-AUG-20:00 35.00 18.06 0.204562E+09 120.46 30-AUG-21:19 31.67 17.46
September 0.339383E+10 2217.87 08-SEP-20:00 33.80 19.77 0.196216E+09 120.46 19-SEP-21:19 27.73 15.69
October 0.283228E+10 1971.04 02-OCT-19:50 27.50 19.95 0.184397E+09 120.46 06-OCT-22:10 26.00 14.45
November 0.227366E+10 1208.48 02-NOV-18:06 23.67 15.30 0.161463E+09 112.01 02-NOV-21:10 20.00 15.60
December 0.184824E+10 1026.93 26-DEC-21:00 15.00 6.89 0.156920E+09 102.27 26-DEC-22:10 14.83 7.20
                     
Annual Sum or Average 0.345275E+11         0.215672E+10        
Minimum of Months 0.180984E+10 988.46   11.00 5.83 0.141462E+09 101.00   11.00 4.49
Maximum of Months 0.405634E+10 2615.74   37.00 20.84 0.204562E+09 120.46   37.00 20.84



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.119853E+10 598.06 08-JAN-11:33 20.33 13.54 0.124112E+09 78.09 27-JAN-22:19 11.67 4.41
February 0.948884E+09 540.79 18-FEB-11:33 19.33 14.12 0.107658E+09 76.55 01-FEB-00:10 19.33 14.12
March 0.117795E+10 638.99 18-MAR-17:40 26.07 12.43 0.124462E+09 82.30 17-MAR-21:40 26.07 12.43
April 0.151820E+10 769.58 15-APR-10:33 28.00 13.04 0.138137E+09 91.92 14-APR-21:40 28.00 13.04
May 0.171178E+10 801.72 31-MAY-18:10 35.67 13.49 0.151154E+09 92.66 18-MAY-21:19 35.67 13.49
June 0.211860E+10 1314.73 28-JUN-18:50 40.17 17.22 0.152837E+09 92.66 09-JUN-23:40 40.17 17.22
July 0.210823E+10 1216.87 21-JUL-19:10 37.83 19.56 0.157121E+09 92.66 07-JUL-22:10 37.83 19.56
August 0.199097E+10 1122.43 15-AUG-19:40 35.67 18.27 0.156902E+09 92.66 27-AUG-23:49 30.17 17.39
September 0.177583E+10 1043.16 08-SEP-19:40 34.37 19.90 0.150076E+09 92.66 19-SEP-21:19 27.73 15.69
October 0.152033E+10 889.18 03-OCT-21:00 30.00 18.69 0.140038E+09 92.66 06-OCT-22:10 26.00 14.45
November 0.123048E+10 652.21 02-NOV-18:06 23.67 15.30 0.122605E+09 83.73 02-NOV-22:10 19.83 16.01
December 0.959523E+09 567.03 25-DEC-11:33 22.33 10.13 0.119624E+09 76.52 26-DEC-22:40 14.33 6.96
                     
Annual Sum or Average 0.182593E+11         0.164472E+10        
Minimum of Months 0.948884E+09 540.79   19.33 10.13 0.107658E+09 76.52   11.67 4.41
Maximum of Months 0.211860E+10 1314.73   40.17 19.90 0.157121E+09 92.66   40.17 19.56



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.502827E+11 37727.31 27-JAN-21:00 17.00 6.99 0.594357E+09 381.76 10-JAN-22:10 17.00 6.99
February 0.447414E+11 37292.37 22-FEB-21:00 13.00 10.72 0.534442E+09 381.75 16-FEB-22:10 13.00 10.72
March 0.505214E+11 38160.02 16-MAR-20:00 22.20 12.56 0.595663E+09 381.73 21-MAR-21:10 18.62 10.88
April 0.515510E+11 39213.00 14-APR-20:00 31.00 13.66 0.583875E+09 381.80 14-APR-21:10 28.67 13.19
May 0.542517E+11 39332.35 18-MAY-20:00 30.00 12.86 0.606355E+09 381.83 09-MAY-21:10 30.00 12.86
June 0.540926E+11 40074.74 28-JUN-20:00 37.00 15.57 0.590722E+09 381.90 23-JUN-21:10 37.00 15.57
July 0.552316E+11 39896.83 21-JUL-20:00 37.00 20.84 0.607440E+09 381.89 07-JUL-21:10 37.00 20.84
August 0.552110E+11 39772.08 15-AUG-20:00 35.00 18.06 0.607895E+09 382.20 09-AUG-21:10 35.00 18.06
September 0.525381E+11 39593.85 08-SEP-20:00 33.80 19.77 0.585773E+09 381.94 19-SEP-21:10 28.02 15.82
October 0.523148E+11 39148.75 03-OCT-20:00 30.00 18.25 0.600674E+09 381.88 06-OCT-21:10 26.00 13.09
November 0.489335E+11 38119.13 01-NOV-20:00 21.00 13.76 0.576014E+09 381.80 01-NOV-21:10 18.00 13.11
December 0.492362E+11 37400.89 22-DEC-21:00 14.00 5.51 0.591595E+09 381.80 12-DEC-22:10 14.00 5.51
                     
Annual Sum or Average 0.618906E+12         0.707480E+10        
Minimum of Months 0.447414E+11 37292.37   13.00 5.51 0.534442E+09 381.73   13.00 5.51
Maximum of Months 0.552316E+11 40074.74   37.00 20.84 0.607895E+09 382.20   37.00 20.84



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.215908E+11 13769.61 14-JAN-13:30 26.50 10.97 0.106512E+11 6462.45 30-JAN-22:10 12.83 5.60
February 0.160721E+11 10453.01 01-FEB-16:03 15.83 6.96 0.915414E+10 6463.27 01-FEB-01:10 15.83 6.96
March 0.182820E+11 10784.06 16-MAR-15:15 28.80 13.79 0.103274E+11 6462.61 16-MAR-22:10 19.80 12.35
April 0.215898E+11 12143.92 14-APR-21:10 28.67 13.19 0.104923E+11 6462.69 26-APR-22:10 15.83 9.46
May 0.223815E+11 11692.02 09-MAY-21:10 28.83 12.76 0.108580E+11 6462.04 06-MAY-01:19 28.83 12.76
June 0.243855E+11 13321.30 28-JUN-21:10 34.67 14.46 0.106176E+11 6462.33 05-JUN-04:19 34.67 14.46
July 0.248981E+11 13209.92 21-JUL-21:10 33.83 20.81 0.109305E+11 6462.12 07-JUL-04:19 33.83 20.81
August 0.254669E+11 13104.78 15-AUG-21:10 32.67 17.73 0.109739E+11 6462.63 04-AUG-22:10 32.67 17.73
September 0.245740E+11 13997.98 28-SEP-15:03 37.52 15.49 0.106004E+11 6462.58 21-SEP-22:10 37.52 15.49
October 0.232909E+11 13924.86 05-OCT-15:03 34.00 15.75 0.108010E+11 6462.70 19-OCT-22:10 19.83 11.29
November 0.203319E+11 14228.08 01-NOV-15:03 28.83 16.12 0.102550E+11 6462.58 01-NOV-22:10 17.67 13.01
December 0.194868E+11 13279.69 25-DEC-13:00 25.00 11.61 0.103011E+11 6461.96 26-DEC-00:20 9.67 3.36
                     
Annual Sum or Average 0.262350E+12         0.125963E+12        
Minimum of Months 0.160721E+11 10453.01   15.83 6.96 0.915414E+10 6461.96   9.67 3.36
Maximum of Months 0.254669E+11 14228.08   37.52 20.81 0.109739E+11 6463.27   37.52 20.81



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.652219E+11 35047.05 31-JAN-19:06 23.00 8.93 0.318096E+11 19185.83 27-JAN-22:19 23.00 8.93
February 0.536329E+11 30935.06 01-FEB-22:10 9.67 5.16 0.277569E+11 19189.49 01-FEB-01:10 9.67 5.16
March 0.617494E+11 35809.78 17-MAR-21:10 21.42 12.50 0.312520E+11 19186.08 22-MAR-21:40 12.00 6.59
April 0.716991E+11 42474.73 14-APR-21:10 28.67 13.19 0.312533E+11 19186.17 26-APR-22:10 15.83 9.46
May 0.774530E+11 42018.62 09-MAY-21:10 28.83 12.76 0.323854E+11 19185.69 26-MAY-03:09 21.00 13.54
June 0.836774E+11 47581.75 28-JUN-21:10 34.67 14.46 0.315860E+11 19186.06 05-JUN-04:19 34.67 14.46
July 0.853619E+11 46881.30 21-JUL-20:10 36.50 20.90 0.325079E+11 19185.49 07-JUL-04:19 36.50 20.90
August 0.851628E+11 46376.66 15-AUG-20:10 34.67 18.05 0.326620E+11 19186.04 04-AUG-22:10 34.67 18.05
September 0.806828E+11 46264.11 07-SEP-21:10 32.75 19.42 0.315328E+11 19185.98 21-SEP-22:10 20.92 16.58
October 0.738353E+11 44172.60 03-OCT-21:10 29.50 18.57 0.322777E+11 19186.33 19-OCT-22:10 19.83 11.29
November 0.636837E+11 38443.39 01-NOV-20:10 20.50 13.68 0.307898E+11 19185.96 01-NOV-22:10 17.67 13.01
December 0.608957E+11 33991.72 26-DEC-22:10 14.83 7.20 0.310581E+11 19185.16 26-DEC-00:20 14.83 7.20
                     
Annual Sum or Average 0.863056E+12         0.376872E+12        
Minimum of Months 0.536329E+11 30935.06   9.67 5.16 0.277569E+11 19185.16   9.67 5.16
Maximum of Months 0.853619E+11 47581.75   36.50 20.90 0.326620E+11 19189.49   36.50 20.90



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.927742E+09 3639.41 31-JAN-16:01 29.00 10.73 98255232.52 56.69 18-JAN-22:10 29.00 10.73
February 0.324077E+09 3347.73 28-FEB-16:01 19.00 8.42 87571843.68 56.69 01-FEB-01:10 19.00 8.42
March 0.751158E+09 3618.40 16-MAR-15:01 28.80 13.75 97960930.04 56.69 22-MAR-21:30 12.45 6.77
April 0.227008E+10 3680.74 14-APR-18:01 33.50 13.96 95713523.15 56.70 24-APR-23:19 26.67 12.88
May 0.271877E+10 3658.00 03-MAY-15:01 33.17 12.99 99129666.61 56.70 10-MAY-23:30 25.50 14.96
June 0.348394E+10 3696.87 27-JUN-18:02 39.83 15.83 96141501.97 56.70 29-JUN-21:30 34.50 16.25
July 0.318559E+10 3676.15 05-JUL-18:02 37.83 16.08 99132032.75 56.70 20-JUL-23:19 32.67 18.65
August 0.312533E+10 3681.43 26-AUG-15:02 41.00 16.32 99255227.45 56.70 11-AUG-21:00 41.00 16.32
September 0.273387E+10 3680.18 28-SEP-15:02 37.52 15.49 95917494.22 56.70 08-SEP-22:10 37.52 15.49
October 0.184375E+10 3674.36 15-OCT-15:01 31.00 12.59 98741103.00 56.70 03-OCT-00:40 31.00 12.59
November 0.936842E+09 3664.81 20-NOV-16:01 26.83 12.13 95054938.80 56.69 01-NOV-21:00 26.83 12.13
December 0.469299E+09 3610.89 25-DEC-16:01 25.67 11.87 97467265.65 56.69 26-DEC-22:19 14.67 7.12
                     
Annual Sum or Average 0.227704E+11         0.116034E+10        
Minimum of Months 0.324077E+09 3347.73   19.00 8.42 87571843.68 56.69   12.45 6.77
Maximum of Months 0.348394E+10 3696.87   41.00 16.32 99255227.45 56.70   41.00 18.65



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.299023E+09 3557.33 31-JAN-16:01 29.00 10.73 98923983.32 65.11 31-JAN-22:10 14.48 5.13
February 0.100307E+09 3268.37 28-FEB-16:01 19.00 8.42 87036267.57 56.69 21-FEB-22:10 19.00 8.42
March 0.397231E+09 3561.89 16-MAR-15:01 28.80 13.75 0.100412E+09 72.26 17-MAR-21:10 21.42 12.50
April 0.191134E+10 3705.07 26-APR-08:41 25.67 12.21 98396481.79 76.73 20-APR-18:10 25.67 12.21
May 0.257486E+10 4003.06 08-MAY-08:61 27.17 12.22 0.100700E+09 57.01 13-MAY-21:00 22.00 7.76
June 0.346469E+10 4033.51 14-JUN-08:61 27.67 11.24 97611382.39 56.70 30-JUN-21:40 33.47 15.37
July 0.314942E+10 4144.52 01-JUL-08:61 27.50 10.46 99742450.98 56.70 20-JUL-23:19 32.67 18.65
August 0.292337E+10 3840.76 24-AUG-08:21 27.50 13.17 0.100610E+09 78.50 04-AUG-21:10 27.50 13.17
September 0.239377E+10 3621.88 28-SEP-15:02 37.52 15.49 97661774.93 75.68 21-SEP-21:10 37.52 15.49
October 0.123799E+10 3607.25 06-OCT-15:02 35.00 14.90 0.101671E+09 73.85 17-OCT-21:10 20.67 7.69
November 0.381918E+09 3582.56 20-NOV-16:01 26.83 12.13 96308408.78 71.16 01-NOV-21:30 26.83 12.13
December 0.114578E+09 3519.09 25-DEC-16:01 25.67 11.87 96302796.96 56.73 26-DEC-21:40 15.00 7.15
                     
Annual Sum or Average 0.189485E+11         0.117538E+10        
Minimum of Months 0.100307E+09 3268.37   19.00 8.42 87036267.57 56.69   14.48 5.13
Maximum of Months 0.346469E+10 4144.52   37.52 15.49 0.101671E+09 78.50   37.52 18.65



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.558278E+09 630.65 14-JAN-13:50 26.83 10.99 0.00 0.00 01-JAN-00:10 26.83 10.99
February 0.186993E+09 475.30 01-FEB-15:30 15.50 6.96 0.00 0.00 01-FEB-00:10 15.50 6.96
March 0.226214E+09 447.12 18-MAR-14:10 26.28 11.98 0.00 0.00 01-MAR-00:10 26.28 11.98
April 0.528259E+09 466.63 14-APR-13:40 34.00 14.40 0.00 0.00 01-APR-00:10 34.00 14.40
May 0.534876E+09 376.91 09-MAY-17:20 34.67 14.40 0.00 0.00 01-MAY-00:10 34.67 14.40
June 0.699746E+09 473.91 28-JUN-17:15 41.67 18.88 0.00 0.00 01-JUN-00:10 41.67 18.88
July 0.707038E+09 448.02 21-JUL-19:10 37.83 19.56 0.00 0.00 01-JUL-00:10 37.83 19.56
August 0.748407E+09 536.82 27-AUG-14:00 40.00 18.27 0.00 0.00 01-AUG-00:10 40.00 18.27
September 0.744934E+09 612.10 28-SEP-13:40 36.47 16.05 0.00 0.00 01-SEP-00:10 36.47 16.05
October 0.644542E+09 632.37 18-OCT-13:50 30.83 12.20 0.00 0.00 01-OCT-00:10 30.83 12.20
November 0.475255E+09 659.01 20-NOV-14:30 27.00 11.68 0.00 0.00 01-NOV-00:10 27.00 11.68
December 0.393954E+09 624.13 25-DEC-13:40 25.67 11.87 0.00 0.00 01-DEC-00:10 25.67 11.87
                     
Annual Sum or Average 0.644850E+10         0.00        
Minimum of Months 0.186993E+09 376.91   15.50 6.96 0.00 0.00   15.50 6.96
Maximum of Months 0.748407E+09 659.01   41.67 19.56 0.00 0.00   41.67 19.56



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.222827E+09 1195.62 27-JAN-16:01 26.83 9.65 97857042.35 67.03 27-JAN-22:10 11.83 4.49
February 0.178037E+09 1065.68 09-FEB-16:01 20.83 9.61 87376247.27 61.74 09-FEB-22:40 14.67 8.47
March 0.308421E+09 1232.00 15-MAR-18:01 26.55 12.82 99586367.36 70.92 23-MAR-21:10 14.80 7.70
April 0.675005E+09 1237.46 12-APR-15:01 33.00 14.97 97146270.34 71.48 26-APR-21:49 16.17 9.55
May 0.896567E+09 1327.45 20-MAY-08:61 26.50 11.05 0.100177E+09 56.69 10-MAY-23:00 26.50 11.05
June 0.116751E+10 1357.06 11-JUN-08:61 26.33 12.62 97065669.00 56.70 15-JUN-21:19 33.67 14.96
July 0.114148E+10 1368.91 01-JUL-08:61 27.50 10.46 99504991.36 56.69 25-JUL-22:19 28.00 17.83
August 0.104282E+10 1255.80 24-AUG-08:21 27.50 13.17 0.100203E+09 76.27 04-AUG-21:10 27.50 13.17
September 0.903371E+09 1247.39 29-SEP-08:21 27.75 14.34 97205977.77 74.22 21-SEP-21:10 27.75 14.34
October 0.535602E+09 1236.75 06-OCT-18:01 31.67 14.16 0.100526E+09 70.66 11-OCT-21:19 15.00 6.77
November 0.257320E+09 1207.47 20-NOV-16:01 26.83 12.13 95418419.25 69.93 02-NOV-21:49 26.83 12.13
December 0.130507E+09 1167.91 25-DEC-16:01 25.67 11.87 96329448.14 58.31 26-DEC-21:40 15.00 7.15
                     
Annual Sum or Average 0.745947E+10         0.116840E+10        
Minimum of Months 0.130507E+09 1065.68   20.83 9.61 87376247.27 56.69   11.83 4.49
Maximum of Months 0.116751E+10 1368.91   33.00 14.97 0.100526E+09 76.27   33.67 17.83



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.883829E+09 3194.21 31-JAN-16:01 29.00 10.73 98560492.73 56.69 19-JAN-22:30 29.00 10.73
February 0.376077E+09 2973.90 09-FEB-16:01 20.83 9.61 88055631.89 56.69 21-FEB-22:49 14.00 12.80
March 0.787057E+09 3193.97 16-MAR-15:01 28.80 13.75 98419475.86 56.69 22-MAR-21:30 12.45 6.77
April 0.230838E+10 3237.75 13-APR-15:01 34.00 14.95 95939308.32 56.70 25-APR-00:00 25.00 12.85
May 0.281301E+10 3294.33 17-MAY-08:61 27.17 13.67 99207230.96 56.70 10-MAY-23:49 27.17 13.67
June 0.356713E+10 3290.67 14-JUN-08:61 27.67 11.24 96065002.19 56.70 27-JUN-21:10 35.50 14.88
July 0.339749E+10 3298.57 01-JUL-08:61 27.50 10.46 99141663.18 56.70 07-JUL-21:00 32.00 16.73
August 0.330208E+10 3258.50 27-AUG-08:61 29.67 14.57 99249445.43 56.70 17-AUG-22:00 29.67 14.57
September 0.282874E+10 3237.92 28-SEP-15:02 37.52 15.49 95953849.80 56.70 07-SEP-22:40 37.52 15.49
October 0.191355E+10 3227.79 06-OCT-15:02 35.00 14.90 98974934.59 56.70 02-OCT-21:10 35.00 14.90
November 0.871968E+09 3200.61 20-NOV-16:01 26.83 12.13 95281882.81 56.69 01-NOV-21:30 26.83 12.13
December 0.475209E+09 3161.64 25-DEC-16:01 25.67 11.87 97852174.14 56.69 26-DEC-22:10 14.83 7.20
                     
Annual Sum or Average 0.235245E+11         0.116270E+10        
Minimum of Months 0.376077E+09 2973.90   20.83 9.61 88055631.89 56.69   12.45 6.77
Maximum of Months 0.356713E+10 3298.57   37.52 15.49 99249445.43 56.70   37.52 16.73



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.292023E+09 3119.26 31-JAN-16:01 29.00 10.73 98476980.35 63.90 31-JAN-22:10 14.48 5.13
February 0.148398E+09 2802.46 09-FEB-16:01 20.83 9.61 87198491.62 57.37 09-FEB-22:30 15.00 8.57
March 0.450340E+09 3147.10 16-MAR-15:01 28.80 13.75 0.100220E+09 70.52 16-MAR-21:10 20.92 12.27
April 0.190436E+10 3744.95 14-APR-08:41 26.50 12.19 98873129.50 73.09 19-APR-21:30 20.50 9.19
May 0.259240E+10 3974.01 21-MAY-08:61 25.33 11.05 0.102038E+09 56.70 10-MAY-23:49 25.33 11.05
June 0.352317E+10 3772.57 14-JUN-08:61 27.67 11.24 98009485.10 58.56 19-JUN-05:00 23.00 10.71
July 0.334918E+10 3781.11 01-JUL-08:61 27.50 10.46 99980087.80 56.98 05-JUL-05:00 23.00 11.31
August 0.308249E+10 3762.07 24-AUG-08:21 27.50 13.17 0.100901E+09 78.20 04-AUG-21:10 27.50 13.17
September 0.246250E+10 3420.92 15-SEP-08:51 25.00 16.27 98081983.24 75.60 21-SEP-21:10 22.02 16.74
October 0.128564E+10 3562.99 17-OCT-08:51 24.00 9.54 0.101906E+09 72.61 10-OCT-21:00 24.00 9.54
November 0.348681E+09 3289.83 10-NOV-09:51 23.00 9.98 95833207.26 69.46 02-NOV-21:30 23.00 9.98
December 0.126050E+09 3085.53 25-DEC-16:01 25.67 11.87 96135561.98 56.69 13-DEC-00:20 25.67 11.87
                     
Annual Sum or Average 0.195652E+11         0.117765E+10        
Minimum of Months 0.126050E+09 2802.46   20.83 9.54 87198491.62 56.69   14.48 5.13
Maximum of Months 0.352317E+10 3974.01   29.00 16.27 0.102038E+09 78.20   27.50 16.74



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.346471E+10 1644.18 29-JAN-11:33 21.33 8.67 0.134625E+10 847.88 31-JAN-22:40 13.83 4.56
February 0.276955E+10 1522.85 01-FEB-11:35 13.67 6.91 0.114318E+10 839.00 01-FEB-00:10 13.67 6.91
March 0.337362E+10 1722.49 18-MAR-17:40 26.07 12.43 0.132469E+10 850.94 20-MAR-22:10 19.03 10.57
April 0.408547E+10 2050.82 15-APR-10:33 28.00 13.04 0.146125E+10 951.84 14-APR-21:40 28.00 13.04
May 0.451061E+10 2085.28 18-MAY-18:10 34.67 14.15 0.157427E+10 951.87 10-MAY-23:40 34.67 14.15
June 0.532050E+10 3391.19 28-JUN-18:25 40.50 17.53 0.156959E+10 951.87 09-JUN-23:49 40.50 17.53
July 0.521561E+10 3017.71 20-JUL-18:30 38.00 19.12 0.161319E+10 951.86 07-JUL-22:10 38.00 19.12
August 0.512480E+10 2903.19 15-AUG-18:15 37.67 18.63 0.161419E+10 951.85 27-AUG-23:49 30.17 17.39
September 0.470222E+10 2772.02 08-SEP-18:15 35.90 20.02 0.155373E+10 951.85 20-SEP-21:19 27.20 17.73
October 0.421414E+10 2478.28 05-OCT-18:03 31.50 15.38 0.150057E+10 951.86 06-OCT-23:19 25.67 15.00
November 0.345124E+10 1757.72 01-NOV-18:10 23.67 14.38 0.132260E+10 877.18 02-NOV-22:10 19.83 16.01
December 0.307465E+10 1566.81 25-DEC-11:33 22.33 10.13 0.127308E+10 823.00 26-DEC-22:40 14.33 6.96
                     
Annual Sum or Average 0.493071E+11         0.172966E+11        
Minimum of Months 0.276955E+10 1522.85   13.67 6.91 0.114318E+10 823.00   13.67 4.56
Maximum of Months 0.532050E+10 3391.19   40.50 20.02 0.161419E+10 951.87   40.50 19.12



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.849000E+09 3862.11 31-JAN-16:01 29.00 10.73 98044321.46 56.70 07-JAN-01:00 29.00 10.73
February 0.292818E+09 3553.33 28-FEB-16:01 19.00 8.42 87321604.03 56.69 16-FEB-22:40 19.00 8.42
March 0.724602E+09 3844.30 16-MAR-15:01 28.80 13.75 97780221.67 56.69 24-MAR-21:10 12.52 4.62
April 0.230180E+10 3916.12 14-APR-18:01 33.50 13.96 95628566.39 56.70 14-APR-23:49 23.50 11.85
May 0.277802E+10 3893.49 03-MAY-15:01 33.17 12.99 99092126.26 56.70 10-MAY-23:10 25.83 15.07
June 0.366558E+10 3933.48 27-JUN-18:02 39.83 15.83 96179628.11 56.70 29-JUN-21:19 34.67 16.35
July 0.333425E+10 3907.74 05-JUL-18:02 37.83 16.08 99130061.52 56.70 11-JUL-21:40 31.00 19.81
August 0.325431E+10 3924.49 26-AUG-15:02 41.00 16.32 99257848.48 56.70 17-AUG-21:30 41.00 16.32
September 0.277631E+10 3875.19 18-SEP-15:02 36.00 16.76 95891616.22 56.70 07-SEP-21:00 36.00 16.76
October 0.176201E+10 3903.46 15-OCT-15:01 31.00 12.59 98586808.07 56.70 06-OCT-22:10 31.00 12.59
November 0.848799E+09 3897.32 20-NOV-16:01 26.83 12.13 94820676.48 56.69 10-NOV-03:00 26.83 12.13
December 0.426155E+09 3834.17 25-DEC-16:01 25.67 11.87 97167276.75 56.69 26-DEC-22:49 14.17 6.88
                     
Annual Sum or Average 0.230137E+11         0.115890E+10        
Minimum of Months 0.292818E+09 3553.33   19.00 8.42 87321604.03 56.69   12.52 4.62
Maximum of Months 0.366558E+10 3933.48   41.00 16.76 99257848.48 56.70   41.00 19.81



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.249911E+09 3763.24 31-JAN-16:01 29.00 10.73 98429955.53 63.02 31-JAN-22:10 14.48 5.13
February 83110141.60 3458.42 28-FEB-16:01 19.00 8.42 86679966.10 56.69 21-FEB-22:19 19.00 8.42
March 0.370976E+09 3779.23 16-MAR-15:01 28.80 13.75 0.100338E+09 72.52 17-MAR-21:19 21.23 12.36
April 0.195820E+10 3879.20 26-APR-08:41 25.67 12.21 98204295.56 79.27 20-APR-18:10 25.67 12.21
May 0.265952E+10 4189.12 08-MAY-08:61 27.17 12.22 0.100344E+09 56.70 10-MAY-23:10 25.83 15.07
June 0.366538E+10 4217.64 14-JUN-08:61 27.67 11.24 97488896.89 56.70 29-JUN-21:30 34.50 16.25
July 0.330538E+10 4330.02 01-JUL-08:61 27.50 10.46 99653592.42 56.70 20-JUL-22:40 33.00 18.53
August 0.306090E+10 4004.16 24-AUG-08:21 27.50 13.17 0.100481E+09 78.30 04-AUG-21:10 27.50 13.17
September 0.244913E+10 3848.46 28-SEP-15:02 37.52 15.49 97399993.71 74.73 21-SEP-21:10 37.52 15.49
October 0.117882E+10 3825.17 06-OCT-15:02 35.00 14.90 0.101099E+09 72.69 17-OCT-21:10 20.67 7.69
November 0.321741E+09 3797.76 20-NOV-16:01 26.83 12.13 95737018.78 70.87 01-NOV-21:30 26.83 12.13
December 95920297.89 3722.45 25-DEC-16:01 25.67 11.87 95765147.89 56.69 26-DEC-22:10 14.83 7.20
                     
Annual Sum or Average 0.193990E+11         0.117162E+10        
Minimum of Months 83110141.60 3458.42   19.00 8.42 86679966.10 56.69   14.48 5.13
Maximum of Months 0.366538E+10 4330.02   37.52 15.49 0.101099E+09 79.27   37.52 18.53



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.118269E+10 1975.29 14-JAN-16:01 26.67 10.69 98816161.51 56.69 04-JAN-22:10 26.67 10.69
February 0.510331E+09 1829.62 09-FEB-16:01 20.83 9.61 88407931.33 56.69 21-FEB-22:10 14.00 12.80
March 0.650112E+09 1952.31 16-MAR-15:01 28.80 13.75 98378228.87 56.69 16-MAR-21:00 20.00 12.36
April 0.131407E+10 1963.01 13-APR-15:01 34.00 14.95 95667035.36 56.69 25-APR-00:30 25.50 13.09
May 0.139758E+10 1940.98 03-MAY-15:01 33.17 12.99 99083752.74 56.70 10-MAY-23:19 25.67 15.01
June 0.177489E+10 1943.05 27-JUN-15:02 41.00 15.93 96030913.68 56.70 30-JUN-21:30 33.85 15.58
July 0.178704E+10 1941.14 01-JUL-08:61 27.50 10.46 99122641.87 56.70 20-JUL-23:40 32.33 18.59
August 0.184190E+10 1961.25 26-AUG-15:02 41.00 16.32 99217568.01 56.70 07-AUG-21:30 41.00 16.32
September 0.176737E+10 1960.25 18-SEP-15:02 36.00 16.76 95952550.60 56.70 05-SEP-21:40 36.00 16.76
October 0.144588E+10 1982.41 18-OCT-15:01 30.00 11.77 98899784.99 56.70 03-OCT-22:10 30.00 11.77
November 0.103484E+10 1981.74 20-NOV-16:01 26.83 12.13 95506587.94 56.69 10-NOV-22:40 26.83 12.13
December 0.873044E+09 1964.25 25-DEC-16:01 25.67 11.87 98515068.96 56.69 26-DEC-22:00 14.00 6.79
                     
Annual Sum or Average 0.155798E+11         0.116360E+10        
Minimum of Months 0.510331E+09 1829.62   20.83 9.61 88407931.33 56.69   14.00 6.79
Maximum of Months 0.184190E+10 1982.41   41.00 16.76 99217568.01 56.70   41.00 18.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.343599E+11 18854.98 06-JAN-22:10 17.67 9.28 0.191034E+11 11348.39 30-JAN-22:10 12.83 5.60
February 0.302786E+11 18402.59 21-FEB-23:00 14.00 12.80 0.172283E+11 11349.65 01-FEB-00:00 14.00 12.80
March 0.355163E+11 20556.38 17-MAR-21:53 20.50 11.82 0.192268E+11 11348.77 16-MAR-22:10 20.50 11.82
April 0.401424E+11 22797.28 14-APR-21:10 28.67 13.19 0.186921E+11 11348.95 26-APR-22:10 15.83 9.46
May 0.439962E+11 23078.06 09-MAY-21:10 28.83 12.76 0.193431E+11 11354.38 26-MAY-21:19 25.00 9.45
June 0.464519E+11 24852.60 28-JUN-21:20 34.33 14.34 0.187605E+11 11379.38 09-JUN-21:19 34.33 14.34
July 0.471299E+11 24474.13 21-JUL-21:20 33.67 20.69 0.193091E+11 11373.52 07-JUL-21:19 33.67 20.69
August 0.463093E+11 23969.11 15-AUG-21:10 32.67 17.73 0.193891E+11 11357.47 10-AUG-21:19 32.67 17.73
September 0.432711E+11 23766.85 07-SEP-21:10 32.75 19.42 0.187050E+11 11363.54 19-SEP-21:19 27.73 15.69
October 0.391404E+11 22885.91 03-OCT-21:10 29.50 18.57 0.192419E+11 11348.93 19-OCT-22:10 19.83 11.29
November 0.339239E+11 20407.82 02-NOV-21:53 20.00 16.05 0.185113E+11 11348.73 01-NOV-22:10 20.00 16.05
December 0.324035E+11 18407.67 26-DEC-22:30 14.50 7.04 0.189982E+11 11348.15 19-DEC-04:19 14.50 7.04
                     
Annual Sum or Average 0.472923E+12         0.226509E+12        
Minimum of Months 0.302786E+11 18402.59   14.00 7.04 0.172283E+11 11348.15   12.83 5.60
Maximum of Months 0.471299E+11 24852.60   34.33 20.69 0.193891E+11 11379.38   34.33 20.69



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.377371E+11 20588.81 06-JAN-22:10 17.67 9.28 0.192065E+11 11348.40 30-JAN-22:10 12.83 5.60
February 0.335524E+11 20162.73 21-FEB-23:00 14.00 12.80 0.173435E+11 11349.92 01-FEB-00:00 14.00 12.80
March 0.390842E+11 22052.06 17-MAR-21:10 21.42 12.50 0.193172E+11 11348.78 16-MAR-22:10 21.42 12.50
April 0.430988E+11 24004.85 14-APR-21:10 28.67 13.19 0.187096E+11 11348.95 26-APR-22:10 15.83 9.46
May 0.468910E+11 24270.79 09-MAY-21:20 28.67 12.70 0.193488E+11 11370.80 26-MAY-21:19 25.00 9.45
June 0.491554E+11 26035.81 28-JUN-21:20 34.33 14.34 0.187613E+11 11385.42 09-JUN-21:19 34.33 14.34
July 0.498875E+11 25653.76 21-JUL-21:20 33.67 20.69 0.193100E+11 11378.33 05-JUL-21:19 33.67 20.69
August 0.490676E+11 25150.23 10-AUG-21:20 32.67 17.86 0.193909E+11 11362.14 10-AUG-21:19 32.67 17.86
September 0.459225E+11 24913.60 07-SEP-21:10 32.75 19.42 0.187091E+11 11370.73 19-SEP-21:19 27.73 15.69
October 0.421936E+11 24051.61 03-OCT-21:10 29.50 18.57 0.192817E+11 11348.93 19-OCT-22:10 19.83 11.29
November 0.371773E+11 21814.74 02-NOV-21:53 20.00 16.05 0.185991E+11 11348.74 01-NOV-22:10 20.00 16.05
December 0.358491E+11 20036.07 26-DEC-22:10 14.83 7.20 0.191455E+11 11348.20 19-DEC-04:19 14.83 7.20
                     
Annual Sum or Average 0.509616E+12         0.227123E+12        
Minimum of Months 0.335524E+11 20036.07   14.00 7.20 0.173435E+11 11348.20   12.83 5.60
Maximum of Months 0.498875E+11 26035.81   34.33 20.69 0.193909E+11 11385.42   34.33 20.69



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.498125E+11 26831.10 29-JAN-11:50 21.67 8.74 0.188199E+11 11319.61 14-JAN-18:19 21.67 8.74
February 0.442306E+11 26689.33 18-FEB-11:33 19.33 14.12 0.169992E+11 11319.57 11-FEB-18:19 19.33 14.12
March 0.502598E+11 27769.42 18-MAR-10:45 24.12 14.75 0.188328E+11 11319.67 18-MAR-17:19 26.63 12.71
April 0.529117E+11 29280.80 30-APR-10:33 30.00 11.09 0.182471E+11 11319.67 08-APR-17:19 30.00 11.09
May 0.560558E+11 29521.36 20-MAY-10:50 31.67 12.61 0.188634E+11 11319.67 06-MAY-17:19 31.67 12.61
June 0.568723E+11 30410.76 18-JUN-10:50 35.67 17.76 0.182650E+11 11319.65 10-JUN-17:19 35.67 17.76
July 0.581477E+11 30418.88 22-JUL-10:37 35.67 19.48 0.188671E+11 11319.67 29-JUL-17:19 35.90 19.14
August 0.577927E+11 30428.27 13-AUG-10:37 33.67 21.36 0.188734E+11 11319.65 12-AUG-17:19 33.67 21.36
September 0.546860E+11 30158.27 09-SEP-10:50 33.62 20.75 0.182580E+11 11319.67 23-SEP-17:19 33.27 17.89
October 0.529749E+11 29336.59 02-OCT-10:45 32.67 19.11 0.188450E+11 11319.66 14-OCT-17:19 30.00 11.31
November 0.484600E+11 27656.71 01-NOV-10:45 24.67 16.10 0.182164E+11 11319.58 04-NOV-17:19 17.67 8.15
December 0.482267E+11 26683.87 25-DEC-11:50 22.67 10.24 0.188074E+11 11319.65 30-DEC-18:19 16.07 7.26
                     
Annual Sum or Average 0.630431E+12         0.221895E+12        
Minimum of Months 0.442306E+11 26683.87   19.33 8.74 0.169992E+11 11319.57   16.07 7.26
Maximum of Months 0.581477E+11 30428.27   35.67 21.36 0.188734E+11 11319.67   35.90 21.36



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.763260E+10 3801.14 31-JAN-17:20 27.67 10.33 0.138681E+10 874.97 31-JAN-22:19 14.27 4.94
February 0.608291E+10 3531.89 26-FEB-11:33 15.33 10.16 0.119405E+10 858.09 01-FEB-00:10 15.33 10.16
March 0.748290E+10 4234.65 18-MAR-17:12 26.63 12.71 0.138672E+10 919.68 17-MAR-21:40 26.63 12.71
April 0.962646E+10 6230.78 14-APR-15:03 35.00 14.57 0.154795E+10 1007.40 14-APR-23:30 24.50 12.18
May 0.108337E+11 5935.19 09-MAY-15:03 35.00 14.52 0.166186E+10 1007.44 10-MAY-23:19 25.67 15.01
June 0.132076E+11 7825.09 28-JUN-18:04 40.83 17.83 0.165490E+10 1007.44 09-JUN-23:30 40.83 17.83
July 0.130921E+11 7147.31 20-JUL-15:03 39.83 20.05 0.170405E+10 1007.43 01-JUL-00:10 39.83 20.05
August 0.128043E+11 7371.01 11-AUG-15:30 38.00 21.21 0.170407E+10 1007.41 21-AUG-00:10 26.00 16.49
September 0.114725E+11 7397.26 07-SEP-15:03 37.28 19.77 0.163480E+10 1007.41 19-SEP-21:19 27.73 15.69
October 0.953567E+10 6879.81 02-OCT-13:20 34.33 19.52 0.154246E+10 1007.42 06-OCT-23:19 25.67 15.00
November 0.760177E+10 4214.22 01-NOV-17:12 25.33 14.39 0.135600E+10 929.56 01-NOV-21:30 18.00 13.11
December 0.636030E+10 3668.99 25-DEC-11:50 22.67 10.24 0.132372E+10 857.50 26-DEC-22:40 14.33 6.96
                     
Annual Sum or Average 0.115733E+12         0.180974E+11        
Minimum of Months 0.608291E+10 3531.89   15.33 10.16 0.119405E+10 857.50   14.27 4.94
Maximum of Months 0.132076E+11 7825.09   40.83 21.21 0.170407E+10 1007.44   40.83 20.05



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 4.27
February 0.00 0.00 01-FEB-00:05 11.90
March 0.00 0.00 01-MAR-00:05 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:05 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:05 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:05 17.23
December 0.00 0.00 01-DEC-00:05 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 143233.01 57.52 01-JAN-06:00 0.80
February 62720.85 82.51 13-FEB-07:05 8.33
March 5054698.76 318.60 27-MAR-06:05 1.97
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:05 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:05 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:05 17.23
December 9846938.57 386.94 16-DEC-07:20 1.33
         
Annual Sum or Average 15107591.20      
Minimum of Months 0.00 0.00   0.80
Maximum of Months 9846938.57 386.94   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 4.27
February 0.00 0.00 01-FEB-00:05 11.90
March 0.00 0.00 01-MAR-00:05 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:05 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:05 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:05 17.23
December 0.00 0.00 01-DEC-00:05 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 4.27
February 0.00 0.00 01-FEB-00:05 11.90
March 0.00 0.00 01-MAR-00:05 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:05 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:05 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:05 17.23
December 159765.07 57.73 07-DEC-05:00 -1.1
         
Annual Sum or Average 159765.07      
Minimum of Months 0.00 0.00   -1.1
Maximum of Months 159765.07 57.73   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 437145.30 53.05 01-JAN-06:00 0.80
February 0.00 0.00 01-FEB-00:05 11.90
March 0.00 0.00 01-MAR-00:05 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:05 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:05 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:05 17.23
December 1823137.93 89.31 07-DEC-05:00 -1.1
         
Annual Sum or Average 2260283.23      
Minimum of Months 0.00 0.00   -1.1
Maximum of Months 1823137.93 89.31   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 4.27
February 0.00 0.00 01-FEB-00:05 11.90
March 0.00 0.00 01-MAR-00:05 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:05 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:05 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:05 17.23
December 0.00 0.00 01-DEC-00:05 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 4.27
February 0.00 0.00 01-FEB-00:05 11.90
March 0.00 0.00 01-MAR-00:05 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:05 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:05 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:05 17.23
December 0.00 0.00 01-DEC-00:05 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 4.27
February 0.00 0.00 01-FEB-00:05 11.90
March 0.00 0.00 01-MAR-00:05 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:05 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:05 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:05 17.23
December 0.00 0.00 01-DEC-00:05 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 57442195.93 1966.90 01-JAN-09:01 5.90
February 0.127913E+09 1938.36 12-FEB-16:02 14.00
March 85182855.67 2003.40 26-MAR-08:62 7.75
April 1423859.74 1045.95 07-APR-08:03 14.67
May 1236322.83 706.70 02-MAY-08:04 24.33
June 103719.66 346.61 13-JUN-08:04 25.50
July 381155.85 767.74 27-JUL-08:04 25.33
August 676253.68 847.66 07-AUG-08:04 23.50
September 1020923.56 859.18 26-SEP-08:04 23.85
October 9632328.84 1200.29 29-OCT-08:03 13.50
November 41905674.89 1112.07 25-NOV-19:03 15.00
December 0.225467E+09 2060.61 07-DEC-09:01 6.67
         
Annual Sum or Average 0.552385E+09      
Minimum of Months 103719.66 346.61   5.90
Maximum of Months 0.225467E+09 2060.61   25.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.140973E+09 2106.16 01-JAN-09:01 5.90
February 0.216885E+09 2009.94 09-FEB-09:02 8.50
March 0.114057E+09 2017.76 26-MAR-08:62 7.75
April 1544994.05 1280.74 05-APR-08:53 25.00
May 719352.02 917.11 19-MAY-08:14 26.67
June 138624.87 1178.69 13-JUN-08:14 26.00
July 167829.66 491.54 18-JUL-08:04 27.17
August 435432.83 774.74 24-AUG-08:24 27.50
September 410136.74 887.94 16-SEP-08:54 26.60
October 18288798.88 1675.12 25-OCT-08:62 8.50
November 95315605.37 2042.28 24-NOV-09:01 9.00
December 0.438392E+09 2118.67 06-DEC-09:01 6.50
         
Annual Sum or Average 0.102733E+10      
Minimum of Months 138624.87 491.54   5.90
Maximum of Months 0.438392E+09 2118.67   27.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 5694.78 18.98 09-JAN-08:10 9.50
February 0.00 0.00 01-FEB-00:05 11.90
March 0.00 0.00 01-MAR-00:05 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:05 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:05 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:05 17.23
December 0.00 0.00 01-DEC-00:05 9.20
         
Annual Sum or Average 5694.78      
Minimum of Months 0.00 0.00   9.20
Maximum of Months 5694.78 18.98   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 6077414.66 407.66 16-JAN-16:04 24.00
February 2187418.40 600.34 05-FEB-16:03 15.83
March 2434008.86 548.12 12-MAR-15:04 16.18
April 693183.37 365.18 01-APR-08:53 24.00
May 335191.86 311.14 02-MAY-08:44 25.67
June 38983.53 95.77 27-JUN-08:06 31.17
July 28026.54 97.94 27-JUL-08:16 25.67
August 110623.92 216.68 22-AUG-08:06 27.50
September 29181.70 163.65 23-SEP-08:55 26.10
October 811367.41 440.50 12-OCT-15:04 19.00
November 3096810.15 447.27 25-NOV-16:03 17.00
December 26857189.88 617.29 07-DEC-09:01 6.67
         
Annual Sum or Average 42699400.28      
Minimum of Months 28026.54 95.77   6.67
Maximum of Months 26857189.88 617.29   31.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 68281171.06 957.28 20-JAN-16:04 21.32
February 0.121515E+09 1856.41 12-FEB-19:02 12.00
March 80957621.43 992.33 07-MAR-19:03 18.80
April 125625.64 651.39 29-APR-08:04 24.33
May 113172.39 788.14 26-MAY-08:04 24.50
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 34972.07 349.72 05-AUG-18:05 17.17
September 21557.39 160.79 03-SEP-18:05 27.02
October 8178969.00 917.53 27-OCT-15:04 21.00
November 50221005.76 995.63 08-NOV-19:04 18.83
December 0.223693E+09 1195.08 11-DEC-09:02 13.17
         
Annual Sum or Average 0.553143E+09      
Minimum of Months 0.00 0.00   12.00
Maximum of Months 0.223693E+09 1856.41   27.73



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.158228E+09 1936.54 01-JAN-19:02 11.03
February 0.189475E+09 1899.03 12-FEB-16:02 14.00
March 0.107968E+09 1099.49 08-MAR-16:03 19.30
April 530030.84 758.54 27-APR-21:54 21.00
May 51710.07 734.68 25-MAY-08:14 25.67
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 660.49 11.01 05-AUG-08:56 25.00
September 126759.89 404.80 20-SEP-06:05 24.30
October 16554573.96 1017.35 22-OCT-15:04 15.83
November 0.108971E+09 1545.37 23-NOV-19:02 8.83
December 0.412453E+09 1962.85 07-DEC-16:01 15.67
         
Annual Sum or Average 0.994358E+09      
Minimum of Months 0.00 0.00   8.83
Maximum of Months 0.412453E+09 1962.85   27.73



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 4.27
February 0.00 0.00 01-FEB-00:05 11.90
March 0.00 0.00 01-MAR-00:05 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:05 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:05 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:05 17.23
December 0.00 0.00 01-DEC-00:05 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.152366E+09 2451.22 01-JAN-09:01 5.90
February 0.262895E+09 2337.98 09-FEB-09:02 8.50
March 0.174012E+09 2391.34 26-MAR-08:62 7.75
April 2586815.14 1115.24 18-APR-08:03 20.50
May 1468461.89 1455.28 09-MAY-08:03 26.33
June 176954.24 881.37 14-JUN-08:03 27.67
July 421287.06 770.80 27-JUL-08:04 25.33
August 723938.66 807.38 07-AUG-08:04 23.50
September 1295847.07 822.61 14-SEP-08:04 23.67
October 39860416.07 2232.87 25-OCT-08:62 8.50
November 0.116917E+09 2369.78 24-NOV-09:01 9.00
December 0.416539E+09 2462.18 06-DEC-09:01 6.50
         
Annual Sum or Average 0.116926E+10      
Minimum of Months 176954.24 770.80   5.90
Maximum of Months 0.416539E+09 2462.18   27.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.303438E+09 2503.13 01-JAN-09:01 5.90
February 0.401063E+09 2385.09 09-FEB-09:02 8.50
March 0.215580E+09 2405.54 26-MAR-08:62 7.75
April 2289776.16 1403.92 24-APR-08:53 26.00
May 937365.40 1543.21 14-MAY-08:43 25.92
June 221085.24 865.79 13-JUN-08:14 26.00
July 305102.65 935.86 02-JUL-08:14 27.07
August 439167.16 693.32 30-AUG-08:04 26.67
September 875609.06 930.27 25-SEP-08:24 25.25
October 62490693.42 2364.79 25-OCT-08:62 8.50
November 0.216784E+09 2436.59 23-NOV-09:02 5.45
December 0.719805E+09 2503.14 06-DEC-09:01 6.50
         
Annual Sum or Average 0.192423E+10      
Minimum of Months 221085.24 693.32   5.45
Maximum of Months 0.719805E+09 2503.14   27.07



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 6835860.54 339.02 01-JAN-19:05 11.03
February 26211261.48 738.23 07-FEB-16:04 16.00
March 29028006.44 1228.78 27-MAR-08:62 9.77
April 737882.18 478.99 19-APR-08:03 19.50
May 989995.49 470.49 16-MAY-08:04 25.50
June 357285.73 455.76 13-JUN-08:04 25.50
July 470406.29 435.01 03-JUL-08:04 28.50
August 522269.20 483.01 17-AUG-08:04 28.33
September 305319.05 420.45 29-SEP-08:04 26.65
October 1448863.18 493.24 12-OCT-08:03 12.33
November 7050840.25 395.21 04-NOV-08:03 9.50
December 42680633.04 609.03 15-DEC-16:04 12.83
         
Annual Sum or Average 0.116639E+09      
Minimum of Months 305319.05 339.02   9.50
Maximum of Months 42680633.04 1228.78   28.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 4.27
February 0.00 0.00 01-FEB-00:05 11.90
March 0.00 0.00 01-MAR-00:05 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:05 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:05 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:05 17.23
December 0.00 0.00 01-DEC-00:05 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 4.27
February 0.00 0.00 01-FEB-00:05 11.90
March 0.00 0.00 01-MAR-00:05 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:05 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:05 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:05 17.23
December 0.00 0.00 01-DEC-00:05 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 4.27
February 0.00 0.00 01-FEB-00:05 11.90
March 0.00 0.00 01-MAR-00:05 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:05 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:05 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:05 17.23
December 0.00 0.00 01-DEC-00:05 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 816890.16 161.13 01-JAN-06:00 0.80
February 0.00 0.00 01-FEB-00:05 11.90
March 0.00 0.00 01-MAR-00:05 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:05 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:05 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:05 17.23
December 10438255.77 665.49 07-DEC-07:05 1.33
         
Annual Sum or Average 11255145.93      
Minimum of Months 0.00 0.00   0.80
Maximum of Months 10438255.77 665.49   29.40



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.866285E+10 8344.11 02-JAN-20:10 0.121516E+11 9632.53 02-JAN-20:10
February 0.782177E+10 8344.11 01-FEB-20:10 0.109726E+11 9632.53 01-FEB-20:10
March 0.868956E+10 8344.11 01-MAR-20:10 0.121771E+11 9632.53 01-MAR-20:10
April 0.836914E+10 8344.11 03-APR-19:10 0.117446E+11 9632.53 03-APR-19:10
May 0.867788E+10 8344.11 01-MAY-19:10 0.121662E+11 9632.53 01-MAY-19:10
June 0.840753E+10 8344.11 01-JUN-19:10 0.117829E+11 9632.53 01-JUN-19:10
July 0.863949E+10 8344.11 03-JUL-19:10 0.121279E+11 9632.53 03-JUL-19:10
August 0.869290E+10 8344.11 01-AUG-19:10 0.121808E+11 9632.53 01-AUG-19:10
September 0.837248E+10 8344.11 01-SEP-19:10 0.117482E+11 9632.53 01-SEP-19:10
October 0.865952E+10 8344.11 02-OCT-19:10 0.121479E+11 9632.53 02-OCT-19:10
November 0.840085E+10 8344.11 01-NOV-19:10 0.117774E+11 9632.53 01-NOV-19:10
December 0.863949E+10 8344.11 01-DEC-20:10 0.121279E+11 9632.53 01-DEC-20:10
             
Annual Sum or Average 0.102033E+12     0.143105E+12    
Minimum of Months 0.782177E+10 8344.11   0.109726E+11 9632.53  
Maximum of Months 0.869290E+10 8344.11   0.121808E+11 9632.53  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.478695E+09 461.08 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.432218E+09 461.08 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.480171E+09 461.08 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.462465E+09 461.08 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.479525E+09 461.08 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.464586E+09 461.08 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.477404E+09 461.08 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.480355E+09 461.08 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.462650E+09 461.08 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.478511E+09 461.08 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.464217E+09 461.08 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.477404E+09 461.08 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.563820E+10     0.101856E+11    
Minimum of Months 0.432218E+09 461.08   0.780982E+09 685.60  
Maximum of Months 0.480355E+09 461.08   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.554331E+09 533.93 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.500510E+09 533.93 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.556040E+09 533.93 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.535537E+09 533.93 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.555292E+09 533.93 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.537993E+09 533.93 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.552836E+09 533.93 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.556253E+09 533.93 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.535750E+09 533.93 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.554117E+09 533.93 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.537566E+09 533.93 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.552836E+09 533.93 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.652906E+10     0.117950E+11    
Minimum of Months 0.500510E+09 533.93   0.904380E+09 793.93  
Maximum of Months 0.556253E+09 533.93   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.639281E+09 615.76 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.577212E+09 615.76 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.641251E+09 615.76 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.617606E+09 615.76 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.640389E+09 615.76 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.620439E+09 615.76 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.637557E+09 615.76 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.641498E+09 615.76 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.617853E+09 615.76 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.639035E+09 615.76 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.619946E+09 615.76 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.637557E+09 615.76 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.752962E+10     0.124712E+11    
Minimum of Months 0.577212E+09 615.76   0.956227E+09 839.45  
Maximum of Months 0.641498E+09 615.76   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.142601E+09 137.35 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.128756E+09 137.35 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.143041E+09 137.35 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.137766E+09 137.35 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.142848E+09 137.35 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.138398E+09 137.35 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.142217E+09 137.35 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.143096E+09 137.35 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.137821E+09 137.35 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.142546E+09 137.35 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.138288E+09 137.35 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.142217E+09 137.35 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.167960E+10     0.359760E+10    
Minimum of Months 0.128756E+09 137.35   0.275845E+09 242.16  
Maximum of Months 0.143096E+09 137.35   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.374392E+09 360.62 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.338042E+09 360.62 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.375546E+09 360.62 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.361698E+09 360.62 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.375041E+09 360.62 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.363357E+09 360.62 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.373382E+09 360.62 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.375690E+09 360.62 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.361842E+09 360.62 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.374247E+09 360.62 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.363068E+09 360.62 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.373382E+09 360.62 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.440969E+10     0.679355E+11    
Minimum of Months 0.338042E+09 360.62   0.520895E+10 4572.80  
Maximum of Months 0.375690E+09 360.62   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.108770E+10 1416.11 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.976596E+09 1416.11 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.100980E+10 1416.11 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.920387E+09 1416.11 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.906806E+09 1416.11 01-MAY-19:10 0.121917E+10 965.27 01-MAY-19:10
June 0.816973E+09 1416.11 01-JUN-19:19 0.118076E+10 965.27 01-JUN-19:10
July 0.863816E+09 1416.11 03-JUL-19:30 0.121533E+10 965.27 03-JUL-19:10
August 0.955966E+09 1416.11 01-AUG-19:19 0.122063E+10 965.27 01-AUG-19:10
September 0.954911E+09 1416.11 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.104060E+10 1416.11 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.104134E+10 1416.11 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.109538E+10 1416.11 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.116703E+11     0.143405E+11    
Minimum of Months 0.816973E+09 1416.11   0.109956E+10 965.27  
Maximum of Months 0.109538E+10 1416.11   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.948818E+10 9580.84 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.857628E+10 9580.84 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.944828E+10 9580.84 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.904072E+10 9580.84 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.933403E+10 9580.84 01-MAY-19:10 0.126672E+11 10029.21 01-MAY-19:10
June 0.900083E+10 9580.84 01-JUN-19:19 0.122682E+11 10029.21 01-JUN-19:10
July 0.926915E+10 9580.84 03-JUL-19:30 0.126273E+11 10029.21 03-JUL-19:10
August 0.940571E+10 9580.84 01-AUG-19:19 0.126824E+11 10029.21 01-AUG-19:10
September 0.908263E+10 9580.84 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.944395E+10 9580.84 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.919119E+10 9580.84 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.947627E+10 9580.84 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.110757E+12     0.148998E+12    
Minimum of Months 0.857628E+10 9580.84   0.114244E+11 10029.21  
Maximum of Months 0.948818E+10 9580.84   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.118113E+09 106.87 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.106667E+09 106.87 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.117174E+09 106.87 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.114438E+09 106.87 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.117643E+09 106.87 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.113531E+09 106.87 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.118566E+09 106.87 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.117174E+09 106.87 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.114469E+09 106.87 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.118097E+09 106.87 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.113984E+09 106.87 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.118582E+09 106.87 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.138844E+10     0.307301E+10    
Minimum of Months 0.106667E+09 106.87   0.235798E+09 237.06  
Maximum of Months 0.118582E+09 106.87   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.118099E+09 106.85 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.106655E+09 106.85 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.117160E+09 106.85 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.114425E+09 106.85 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.117629E+09 106.85 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.113517E+09 106.85 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.118553E+09 106.85 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.117160E+09 106.85 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.114456E+09 106.85 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.118083E+09 106.85 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.113971E+09 106.85 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.118568E+09 106.85 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.138828E+10     0.307265E+10    
Minimum of Months 0.106655E+09 106.85   0.235770E+09 237.03  
Maximum of Months 0.118568E+09 106.85   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 74229181.22 67.16 01-JAN-19:10 0.255708E+09 232.19 01-JAN-08:09
February 67036196.95 67.16 01-FEB-20:10 0.230956E+09 232.19 01-FEB-07:10
March 73639243.64 67.16 01-MAR-20:10 0.255355E+09 232.19 01-MAR-07:10
April 71920171.51 67.16 01-APR-18:10 0.247516E+09 232.19 01-APR-07:10
May 73934212.43 67.16 01-MAY-19:10 0.255532E+09 232.19 01-MAY-06:10
June 71349576.37 67.16 01-JUN-19:10 0.247163E+09 232.19 01-JUN-06:10
July 74514478.79 67.16 01-JUL-18:10 0.255885E+09 232.19 01-JUL-07:10
August 73639243.64 67.16 01-AUG-19:10 0.255355E+09 232.19 01-AUG-06:10
September 71939513.95 67.16 01-SEP-19:10 0.247516E+09 232.19 01-SEP-06:10
October 74219510.00 67.16 01-OCT-18:10 0.255708E+09 232.19 01-OCT-07:10
November 71634873.94 67.16 01-NOV-19:10 0.247340E+09 232.19 01-NOV-06:10
December 74524150.01 67.16 01-DEC-20:10 0.255885E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.872580E+09     0.300992E+10    
Minimum of Months 67036196.95 67.16   0.230956E+09 232.19  
Maximum of Months 74524150.01 67.16   0.255885E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 74249479.06 67.18 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 67054527.88 67.18 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 73659380.16 67.18 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 71939837.95 67.18 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 73954429.61 67.18 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 71369086.78 67.18 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 74534854.64 67.18 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 73659380.16 67.18 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 71959185.68 67.18 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 74239805.19 67.18 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 71654462.37 67.18 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 74544528.51 67.18 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.872819E+09     0.301074E+10    
Minimum of Months 67054527.88 67.18   0.231020E+09 232.26  
Maximum of Months 74544528.51 67.18   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.118113E+09 106.87 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.106667E+09 106.87 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.117174E+09 106.87 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.114438E+09 106.87 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.117643E+09 106.87 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.113531E+09 106.87 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.118566E+09 106.87 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.117174E+09 106.87 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.114469E+09 106.87 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.118097E+09 106.87 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.113984E+09 106.87 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.118582E+09 106.87 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.138844E+10     0.307301E+10    
Minimum of Months 0.106667E+09 106.87   0.235798E+09 237.06  
Maximum of Months 0.118582E+09 106.87   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.118099E+09 106.85 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.106655E+09 106.85 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.117160E+09 106.85 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.114425E+09 106.85 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.117629E+09 106.85 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.113517E+09 106.85 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.118553E+09 106.85 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.117160E+09 106.85 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.114456E+09 106.85 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.118083E+09 106.85 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.113971E+09 106.85 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.118568E+09 106.85 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.138828E+10     0.307265E+10    
Minimum of Months 0.106655E+09 106.85   0.235770E+09 237.03  
Maximum of Months 0.118568E+09 106.85   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.108388E+10 1044.00 02-JAN-20:10 0.00 0.00
February 0.978647E+09 1044.00 01-FEB-20:10 0.00 0.00
March 0.108722E+10 1044.00 01-MAR-20:10 0.00 0.00
April 0.104713E+10 1044.00 03-APR-19:10 0.00 0.00
May 0.108576E+10 1044.00 01-MAY-19:10 0.00 0.00
June 0.105194E+10 1044.00 01-JUN-19:10 0.00 0.00
July 0.108096E+10 1044.00 03-JUL-19:10 0.00 0.00
August 0.108764E+10 1044.00 01-AUG-19:10 0.00 0.00
September 0.104755E+10 1044.00 01-SEP-19:10 0.00 0.00
October 0.108346E+10 1044.00 02-OCT-19:10 0.00 0.00
November 0.105110E+10 1044.00 01-NOV-19:10 0.00 0.00
December 0.108096E+10 1044.00 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.127663E+11     0.00 0.00
Minimum of Months 0.978647E+09 1044.00   0.00 0.00
Maximum of Months 0.108764E+10 1044.00   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.118113E+09 106.87 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.106667E+09 106.87 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.117174E+09 106.87 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.114438E+09 106.87 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.117643E+09 106.87 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.113531E+09 106.87 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.118566E+09 106.87 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.117174E+09 106.87 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.114469E+09 106.87 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.118097E+09 106.87 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.113984E+09 106.87 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.118582E+09 106.87 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.138844E+10     0.307301E+10    
Minimum of Months 0.106667E+09 106.87   0.235798E+09 237.06  
Maximum of Months 0.118582E+09 106.87   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.118099E+09 106.85 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.106655E+09 106.85 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.117160E+09 106.85 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.114425E+09 106.85 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.117629E+09 106.85 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.113517E+09 106.85 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.118553E+09 106.85 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.117160E+09 106.85 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.114456E+09 106.85 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.118083E+09 106.85 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.113971E+09 106.85 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.118568E+09 106.85 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.138828E+10     0.307265E+10    
Minimum of Months 0.106655E+09 106.85   0.235770E+09 237.03  
Maximum of Months 0.118568E+09 106.85   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 74249479.06 67.18 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 67054527.88 67.18 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 73659380.16 67.18 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 71939837.95 67.18 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 73954429.61 67.18 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 71369086.78 67.18 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 74534854.64 67.18 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 73659380.16 67.18 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 71959185.68 67.18 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 74239805.19 67.18 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 71654462.37 67.18 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 74544528.51 67.18 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.872819E+09     0.301074E+10    
Minimum of Months 67054527.88 67.18   0.231020E+09 232.26  
Maximum of Months 74544528.51 67.18   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.232262E+10 2486.81 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.207615E+10 2486.81 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.221234E+10 2486.81 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.205172E+10 2486.81 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.205514E+10 2486.81 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.192029E+10 2486.81 01-JUN-19:19 0.144540E+11 6747.90 01-JUN-06:10
July 0.200786E+10 2486.81 03-JUL-19:30 0.149358E+11 6747.90 01-JUL-06:10
August 0.213003E+10 2486.81 01-AUG-19:19 0.149358E+11 6747.90 01-AUG-06:10
September 0.209741E+10 2486.81 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.227261E+10 2486.81 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.223592E+10 2486.81 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.232388E+10 2486.81 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.257060E+11     0.175857E+12    
Minimum of Months 0.192029E+10 2486.81   0.134904E+11 6747.90  
Maximum of Months 0.232388E+10 2486.81   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.232262E+10 2486.81 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.207615E+10 2486.81 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.221234E+10 2486.81 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.205172E+10 2486.81 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.205514E+10 2486.81 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.192029E+10 2486.81 01-JUN-19:19 0.144540E+11 6747.90 01-JUN-06:10
July 0.200786E+10 2486.81 03-JUL-19:30 0.149358E+11 6747.90 01-JUL-06:10
August 0.213003E+10 2486.81 01-AUG-19:19 0.149358E+11 6747.90 01-AUG-06:10
September 0.209741E+10 2486.81 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.227261E+10 2486.81 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.223592E+10 2486.81 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.232388E+10 2486.81 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.257060E+11     0.175857E+12    
Minimum of Months 0.192029E+10 2486.81   0.134904E+11 6747.90  
Maximum of Months 0.232388E+10 2486.81   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.101925E+10 981.75 02-JAN-20:10 0.360126E+11 16179.04 01-JAN-07:10
February 0.920291E+09 981.75 01-FEB-20:10 0.325275E+11 16179.04 01-FEB-07:10
March 0.102239E+10 981.75 01-MAR-20:10 0.360126E+11 16179.04 01-MAR-07:10
April 0.984694E+09 981.75 03-APR-19:10 0.348509E+11 16179.04 01-APR-06:10
May 0.102102E+10 981.75 01-MAY-19:10 0.360126E+11 16179.04 01-MAY-06:10
June 0.989210E+09 981.75 01-JUN-19:10 0.348509E+11 16179.04 01-JUN-06:10
July 0.101650E+10 981.75 03-JUL-19:10 0.360126E+11 16179.04 01-JUL-06:10
August 0.102279E+10 981.75 01-AUG-19:10 0.360126E+11 16179.04 01-AUG-06:10
September 0.985086E+09 981.75 01-SEP-19:10 0.348509E+11 16179.04 01-SEP-06:10
October 0.101886E+10 981.75 02-OCT-19:10 0.360126E+11 16179.04 01-OCT-06:10
November 0.988424E+09 981.75 01-NOV-19:10 0.348509E+11 16179.04 01-NOV-06:10
December 0.101650E+10 981.75 01-DEC-20:10 0.360126E+11 16179.04 01-DEC-07:10
             
Annual Sum or Average 0.120050E+11     0.424019E+12    
Minimum of Months 0.920291E+09 981.75   0.325275E+11 16179.04  
Maximum of Months 0.102279E+10 981.75   0.360126E+11 16179.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.114712E+10 1104.91 02-JAN-20:10 0.00 0.00
February 0.103575E+10 1104.91 01-FEB-20:10 0.00 0.00
March 0.115066E+10 1104.91 01-MAR-20:10 0.00 0.00
April 0.110823E+10 1104.91 03-APR-19:10 0.00 0.00
May 0.114911E+10 1104.91 01-MAY-19:10 0.00 0.00
June 0.111331E+10 1104.91 01-JUN-19:10 0.00 0.00
July 0.114403E+10 1104.91 03-JUL-19:10 0.00 0.00
August 0.115110E+10 1104.91 01-AUG-19:10 0.00 0.00
September 0.110867E+10 1104.91 01-SEP-19:10 0.00 0.00
October 0.114668E+10 1104.91 02-OCT-19:10 0.00 0.00
November 0.111243E+10 1104.91 01-NOV-19:10 0.00 0.00
December 0.114403E+10 1104.91 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.135111E+11     0.00 0.00
Minimum of Months 0.103575E+10 1104.91   0.00 0.00
Maximum of Months 0.115110E+10 1104.91   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.866285E+10 0.121516E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.782177E+10 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.868956E+10 0.121771E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.836914E+10 0.117446E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.867788E+10 0.121662E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.840753E+10 0.117829E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.863949E+10 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.869290E+10 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.837248E+10 0.117482E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.865952E+10 0.121479E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.840085E+10 0.117774E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.863949E+10 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.102033E+12 0.143105E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.782177E+10 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.869290E+10 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.478695E+09 0.864900E+09 0.00 0.00 0.00 0.00 4243426.49 0.418914E+09
February 0.179968E+10 0.432218E+09 0.780982E+09 0.00 0.00 0.00 0.00 1987.13 0.433433E+09
March 0.199990E+10 0.480171E+09 0.866718E+09 0.00 0.00 0.00 0.00 13322648.08 0.358907E+09
April 0.192973E+10 0.462465E+09 0.835931E+09 0.00 0.00 0.00 0.00 0.117231E+09 0.116249E+09
May 0.199475E+10 0.479525E+09 0.865939E+09 0.00 0.00 0.00 0.00 0.200662E+09 55935533.56
June 0.193394E+10 0.464586E+09 0.838659E+09 0.00 0.00 0.00 0.00 0.361530E+09 8823688.02
July 0.199054E+10 0.477404E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.335578E+09 5350721.22
August 0.199896E+10 0.480355E+09 0.866978E+09 0.00 0.00 0.00 0.00 0.309462E+09 7351922.70
September 0.192879E+10 0.462650E+09 0.836191E+09 0.00 0.00 0.00 0.00 0.214471E+09 18474472.52
October 0.199148E+10 0.478511E+09 0.864640E+09 0.00 0.00 0.00 0.00 78491068.92 0.199287E+09
November 0.192552E+10 0.464217E+09 0.838269E+09 0.00 0.00 0.00 0.00 8109971.55 0.372182E+09
December 0.199054E+10 0.477404E+09 0.863211E+09 0.00 0.00 0.00 0.00 1171282.61 0.552894E+09
                   
Annual Sum or Average 0.234744E+11 0.563820E+10 0.101856E+11 0.00 0.00 0.00 0.00 0.164427E+10 0.254780E+10
Minimum of Months 0.179968E+10 0.432218E+09 0.780982E+09 0.00 0.00 0.00 0.00 1987.13 5350721.22
Maximum of Months 0.199990E+10 0.480355E+09 0.866978E+09 0.00 0.00 0.00 0.00 0.361530E+09 0.552894E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.554331E+09 0.100156E+10 0.00 0.00 0.00 0.00 3335774.37 0.175116E+09
February 0.208403E+10 0.500510E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 0.182265E+09
March 0.231589E+10 0.556040E+09 0.100366E+10 0.00 0.00 0.00 0.00 6114773.98 0.157733E+09
April 0.223463E+10 0.535537E+09 0.968011E+09 0.00 0.00 0.00 0.00 47197694.08 55966057.01
May 0.230993E+10 0.555292E+09 0.100276E+10 0.00 0.00 0.00 0.00 77513250.00 29623974.27
June 0.223950E+10 0.537993E+09 0.971170E+09 0.00 0.00 0.00 0.00 0.139190E+09 5162441.63
July 0.230505E+10 0.552836E+09 0.999601E+09 0.00 0.00 0.00 0.00 0.128625E+09 3279118.38
August 0.231480E+10 0.556253E+09 0.100396E+10 0.00 0.00 0.00 0.00 0.118645E+09 4971964.76
September 0.223354E+10 0.535750E+09 0.968312E+09 0.00 0.00 0.00 0.00 83047444.54 10862471.79
October 0.230614E+10 0.554117E+09 0.100126E+10 0.00 0.00 0.00 0.00 32045247.18 88181597.47
November 0.222975E+10 0.537566E+09 0.970719E+09 0.00 0.00 0.00 0.00 4270359.00 0.158617E+09
December 0.230505E+10 0.552836E+09 0.999601E+09 0.00 0.00 0.00 0.00 1063156.91 0.226605E+09
                   
Annual Sum or Average 0.271834E+11 0.652906E+10 0.117950E+11 0.00 0.00 0.00 0.00 0.641047E+09 0.109838E+10
Minimum of Months 0.208403E+10 0.500510E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 3279118.38
Maximum of Months 0.231589E+10 0.556253E+09 0.100396E+10 0.00 0.00 0.00 0.00 0.139190E+09 0.226605E+09



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.639281E+09 0.105898E+10 0.00 0.00 0.00 0.00 16152251.81 0.352130E+09
February 0.440737E+09 0.577212E+09 0.956227E+09 0.00 0.00 0.00 0.00 103714.83 0.376154E+09
March 0.489771E+09 0.641251E+09 0.106120E+10 0.00 0.00 0.00 0.00 19903649.72 0.323526E+09
April 0.472586E+09 0.617606E+09 0.102351E+10 0.00 0.00 0.00 0.00 0.123066E+09 0.114986E+09
May 0.488511E+09 0.640389E+09 0.106025E+10 0.00 0.00 0.00 0.00 0.185100E+09 63773997.60
June 0.473617E+09 0.620439E+09 0.102685E+10 0.00 0.00 0.00 0.00 0.326008E+09 12063963.42
July 0.487480E+09 0.637557E+09 0.105691E+10 0.00 0.00 0.00 0.00 0.300710E+09 7546936.82
August 0.489542E+09 0.641498E+09 0.106152E+10 0.00 0.00 0.00 0.00 0.278619E+09 11042906.28
September 0.472357E+09 0.617853E+09 0.102382E+10 0.00 0.00 0.00 0.00 0.196020E+09 23682512.11
October 0.487709E+09 0.639035E+09 0.105866E+10 0.00 0.00 0.00 0.00 82675850.39 0.181915E+09
November 0.471555E+09 0.619946E+09 0.102637E+10 0.00 0.00 0.00 0.00 16531877.48 0.321311E+09
December 0.487480E+09 0.637557E+09 0.105691E+10 0.00 0.00 0.00 0.00 5871988.32 0.471649E+09
                   
Annual Sum or Average 0.574883E+10 0.752962E+10 0.124712E+11 0.00 0.00 0.00 0.00 0.155076E+10 0.225978E+10
Minimum of Months 0.440737E+09 0.577212E+09 0.956227E+09 0.00 0.00 0.00 0.00 103714.83 7546936.82
Maximum of Months 0.489771E+09 0.641498E+09 0.106152E+10 0.00 0.00 0.00 0.00 0.326008E+09 0.471649E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.142601E+09 0.305485E+09 0.00 0.00 0.00 0.00 9068671.78 0.200635E+09
February 0.339028E+09 0.128756E+09 0.275845E+09 0.00 0.00 0.00 0.00 57244.76 0.214999E+09
March 0.376747E+09 0.143041E+09 0.306128E+09 0.00 0.00 0.00 0.00 11497266.03 0.183922E+09
April 0.363528E+09 0.137766E+09 0.295253E+09 0.00 0.00 0.00 0.00 72151225.88 64136434.54
May 0.375778E+09 0.142848E+09 0.305852E+09 0.00 0.00 0.00 0.00 0.108323E+09 35206063.88
June 0.364321E+09 0.138398E+09 0.296217E+09 0.00 0.00 0.00 0.00 0.188252E+09 6718795.77
July 0.374985E+09 0.142217E+09 0.304889E+09 0.00 0.00 0.00 0.00 0.173698E+09 4210726.03
August 0.376571E+09 0.143096E+09 0.306219E+09 0.00 0.00 0.00 0.00 0.161147E+09 5972785.56
September 0.363352E+09 0.137821E+09 0.295345E+09 0.00 0.00 0.00 0.00 0.113815E+09 12864085.69
October 0.375161E+09 0.142546E+09 0.305393E+09 0.00 0.00 0.00 0.00 48087529.59 0.102223E+09
November 0.362735E+09 0.138288E+09 0.296079E+09 0.00 0.00 0.00 0.00 9403016.41 0.182509E+09
December 0.374985E+09 0.142217E+09 0.304889E+09 0.00 0.00 0.00 0.00 3266915.48 0.270211E+09
                   
Annual Sum or Average 0.442217E+10 0.167960E+10 0.359760E+10 0.00 0.00 0.00 0.00 0.898767E+09 0.128361E+10
Minimum of Months 0.339028E+09 0.128756E+09 0.275845E+09 0.00 0.00 0.00 0.00 57244.76 4210726.03
Maximum of Months 0.376747E+09 0.143096E+09 0.306219E+09 0.00 0.00 0.00 0.00 0.188252E+09 0.270211E+09



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.374392E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 10834577.83 0.569602E+09
February 0.139600E+10 0.338042E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 0.624068E+09
March 0.155131E+10 0.375546E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 17754043.32 0.531523E+09
April 0.149688E+10 0.361698E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 0.159384E+09 0.162672E+09
May 0.154732E+10 0.375041E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 0.260470E+09 75061635.94
June 0.150015E+10 0.363357E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 0.478821E+09 9442135.75
July 0.154405E+10 0.373382E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.448524E+09 6314702.68
August 0.155059E+10 0.375690E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 0.416297E+09 10673434.85
September 0.149615E+10 0.361842E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 0.293845E+09 23778989.88
October 0.154478E+10 0.374247E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 0.113324E+09 0.275099E+09
November 0.149361E+10 0.363068E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 14225683.29 0.513736E+09
December 0.154405E+10 0.373382E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 3248039.72 0.760094E+09
                   
Annual Sum or Average 0.182090E+11 0.440969E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 0.221673E+10 0.356207E+10
Minimum of Months 0.139600E+10 0.338042E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 6314702.68
Maximum of Months 0.155131E+10 0.375690E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 0.478821E+09 0.760094E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.108770E+10 0.121771E+10 0.00 0.00 0.00 0.00 9261832.08 0.105784E+10
February 0.236489E+11 0.976596E+09 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.109637E+10
March 0.262800E+11 0.100980E+10 0.122027E+10 0.00 0.00 0.00 0.00 25696707.44 0.933958E+09
April 0.253579E+11 0.920387E+09 0.117692E+10 0.00 0.00 0.00 0.00 0.255775E+09 0.314351E+09
May 0.262123E+11 0.906806E+09 0.121917E+10 0.00 0.00 0.00 0.00 0.443535E+09 0.162878E+09
June 0.254132E+11 0.816973E+09 0.118076E+10 0.00 0.00 0.00 0.00 0.803860E+09 28830599.32
July 0.261570E+11 0.863816E+09 0.121533E+10 0.00 0.00 0.00 0.00 0.740278E+09 18370578.97
August 0.262677E+11 0.955966E+09 0.122063E+10 0.00 0.00 0.00 0.00 0.680545E+09 27210862.85
September 0.253456E+11 0.954911E+09 0.117729E+10 0.00 0.00 0.00 0.00 0.471082E+09 59868627.17
October 0.261693E+11 0.104060E+10 0.121734E+10 0.00 0.00 0.00 0.00 0.171767E+09 0.519319E+09
November 0.253025E+11 0.104134E+10 0.118021E+10 0.00 0.00 0.00 0.00 17212323.07 0.947885E+09
December 0.261570E+11 0.109538E+10 0.121533E+10 0.00 0.00 0.00 0.00 2415330.75 0.136851E+10
                   
Annual Sum or Average 0.308468E+12 0.116703E+11 0.143405E+11 0.00 0.00 0.00 0.00 0.362143E+10 0.653540E+10
Minimum of Months 0.236489E+11 0.816973E+09 0.109956E+10 0.00 0.00 0.00 0.00 0.00 18370578.97
Maximum of Months 0.262800E+11 0.109538E+10 0.122063E+10 0.00 0.00 0.00 0.00 0.803860E+09 0.136851E+10



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.948818E+10 0.126520E+11 0.00 0.00 0.00 0.00 33463188.93 0.302107E+10
February 0.702046E+11 0.857628E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.317788E+10
March 0.780153E+11 0.944828E+10 0.126786E+11 0.00 0.00 0.00 0.00 85081613.80 0.273467E+10
April 0.752779E+11 0.904072E+10 0.122282E+11 0.00 0.00 0.00 0.00 0.758064E+09 0.930706E+09
May 0.778146E+11 0.933403E+10 0.126672E+11 0.00 0.00 0.00 0.00 0.126900E+10 0.487033E+09
June 0.754422E+11 0.900083E+10 0.122682E+11 0.00 0.00 0.00 0.00 0.228726E+10 84353040.92
July 0.776503E+11 0.926915E+10 0.126273E+11 0.00 0.00 0.00 0.00 0.210742E+10 54029213.57
August 0.779788E+11 0.940571E+10 0.126824E+11 0.00 0.00 0.00 0.00 0.193954E+10 83514604.63
September 0.752414E+11 0.908263E+10 0.122320E+11 0.00 0.00 0.00 0.00 0.134771E+10 0.180058E+09
October 0.776868E+11 0.944395E+10 0.126482E+11 0.00 0.00 0.00 0.00 0.502166E+09 0.150614E+10
November 0.751137E+11 0.919119E+10 0.122624E+11 0.00 0.00 0.00 0.00 54416371.47 0.273033E+10
December 0.776503E+11 0.947627E+10 0.126273E+11 0.00 0.00 0.00 0.00 9896923.81 0.392481E+10
                   
Annual Sum or Average 0.915726E+12 0.110757E+12 0.148998E+12 0.00 0.00 0.00 0.00 0.103940E+11 0.189146E+11
Minimum of Months 0.702046E+11 0.857628E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 54029213.57
Maximum of Months 0.780153E+11 0.948818E+10 0.126824E+11 0.00 0.00 0.00 0.00 0.228726E+10 0.392481E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.118113E+09 0.261068E+09 0.00 0.00 0.00 0.00 6152101.41 0.220495E+09
February 0.273974E+09 0.106667E+09 0.235798E+09 0.00 0.00 0.00 0.00 4077.10 0.244774E+09
March 0.303685E+09 0.117174E+09 0.260708E+09 0.00 0.00 0.00 0.00 10749663.09 0.202667E+09
April 0.293479E+09 0.114438E+09 0.252705E+09 0.00 0.00 0.00 0.00 93805780.78 52208613.23
May 0.303504E+09 0.117643E+09 0.260888E+09 0.00 0.00 0.00 0.00 0.150605E+09 19707092.98
June 0.293842E+09 0.113531E+09 0.252344E+09 0.00 0.00 0.00 0.00 0.262017E+09 983483.68
July 0.303141E+09 0.118566E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.250964E+09 782284.06
August 0.303685E+09 0.117174E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.233480E+09 1060281.73
September 0.293479E+09 0.114469E+09 0.252705E+09 0.00 0.00 0.00 0.00 0.171768E+09 3549442.12
October 0.303322E+09 0.118097E+09 0.261068E+09 0.00 0.00 0.00 0.00 65746970.75 96040062.26
November 0.293661E+09 0.113984E+09 0.252524E+09 0.00 0.00 0.00 0.00 8141537.08 0.195898E+09
December 0.303141E+09 0.118582E+09 0.261248E+09 0.00 0.00 0.00 0.00 1689823.33 0.305863E+09
                   
Annual Sum or Average 0.357224E+10 0.138844E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.125512E+10 0.134403E+10
Minimum of Months 0.273974E+09 0.106667E+09 0.235798E+09 0.00 0.00 0.00 0.00 4077.10 782284.06
Maximum of Months 0.303685E+09 0.118582E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.262017E+09 0.305863E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.118099E+09 0.261038E+09 0.00 0.00 0.00 0.00 6894887.49 0.219485E+09
February 0.273974E+09 0.106655E+09 0.235770E+09 0.00 0.00 0.00 0.00 11071.93 0.239973E+09
March 0.303685E+09 0.117160E+09 0.260677E+09 0.00 0.00 0.00 0.00 10112508.20 0.205993E+09
April 0.293479E+09 0.114425E+09 0.252675E+09 0.00 0.00 0.00 0.00 91700778.38 57373789.74
May 0.303504E+09 0.117629E+09 0.260857E+09 0.00 0.00 0.00 0.00 0.147999E+09 23341197.48
June 0.293842E+09 0.113517E+09 0.252315E+09 0.00 0.00 0.00 0.00 0.258604E+09 2221881.94
July 0.303141E+09 0.118553E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.249615E+09 1398959.94
August 0.303685E+09 0.117160E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.231079E+09 2725515.30
September 0.293479E+09 0.114456E+09 0.252675E+09 0.00 0.00 0.00 0.00 0.168602E+09 6130487.30
October 0.303322E+09 0.118083E+09 0.261038E+09 0.00 0.00 0.00 0.00 64186802.39 0.100888E+09
November 0.293661E+09 0.113971E+09 0.252495E+09 0.00 0.00 0.00 0.00 8291255.16 0.197026E+09
December 0.303141E+09 0.118568E+09 0.261218E+09 0.00 0.00 0.00 0.00 2202592.27 0.297919E+09
                   
Annual Sum or Average 0.357224E+10 0.138828E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.123930E+10 0.135447E+10
Minimum of Months 0.273974E+09 0.106655E+09 0.235770E+09 0.00 0.00 0.00 0.00 11071.93 1398959.94
Maximum of Months 0.303685E+09 0.118568E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.258604E+09 0.297919E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 74229181.22 0.255708E+09 0.00 0.00 0.00 0.00 85515.63 0.102606E+09
February 0.00 67036196.95 0.230956E+09 0.00 0.00 0.00 0.00 0.00 0.106016E+09
March 0.00 73639243.64 0.255355E+09 0.00 0.00 0.00 0.00 228831.07 95185873.60
April 0.00 71920171.51 0.247516E+09 0.00 0.00 0.00 0.00 9208781.85 37486340.26
May 0.00 73934212.43 0.255532E+09 0.00 0.00 0.00 0.00 18326400.00 22493033.24
June 0.00 71349576.37 0.247163E+09 0.00 0.00 0.00 0.00 40718162.17 6368949.35
July 0.00 74514478.79 0.255885E+09 0.00 0.00 0.00 0.00 34755507.26 5112636.76
August 0.00 73639243.64 0.255355E+09 0.00 0.00 0.00 0.00 32010315.21 7378828.92
September 0.00 71939513.95 0.247516E+09 0.00 0.00 0.00 0.00 20349346.78 12654997.59
October 0.00 74219510.00 0.255708E+09 0.00 0.00 0.00 0.00 6715436.13 56764167.16
November 0.00 71634873.94 0.247340E+09 0.00 0.00 0.00 0.00 122635.28 93618213.25
December 0.00 74524150.01 0.255885E+09 0.00 0.00 0.00 0.00 0.00 0.127283E+09
                   
Annual Sum or Average 0.00 0.872580E+09 0.300992E+10 0.00 0.00 0.00 0.00 0.162521E+09 0.672967E+09
Minimum of Months 0.00 67036196.95 0.230956E+09 0.00 0.00 0.00 0.00 0.00 5112636.76
Maximum of Months 0.00 74524150.01 0.255885E+09 0.00 0.00 0.00 0.00 40718162.17 0.127283E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 74249479.06 0.255778E+09 0.00 0.00 0.00 0.00 2526717.00 60676415.64
February 0.273974E+09 67054527.88 0.231020E+09 0.00 0.00 0.00 0.00 1355.28 67571650.08
March 0.303685E+09 73659380.16 0.255425E+09 0.00 0.00 0.00 0.00 3064257.92 57168348.36
April 0.293479E+09 71939837.95 0.247584E+09 0.00 0.00 0.00 0.00 26025930.26 15334413.79
May 0.303504E+09 73954429.61 0.255602E+09 0.00 0.00 0.00 0.00 41626782.59 6208222.84
June 0.293842E+09 71369086.78 0.247231E+09 0.00 0.00 0.00 0.00 72527495.41 465633.85
July 0.303141E+09 74534854.64 0.255955E+09 0.00 0.00 0.00 0.00 69875771.41 323206.77
August 0.303685E+09 73659380.16 0.255425E+09 0.00 0.00 0.00 0.00 64773031.40 626317.70
September 0.293479E+09 71959185.68 0.247584E+09 0.00 0.00 0.00 0.00 47340758.59 1508963.56
October 0.303322E+09 74239805.19 0.255778E+09 0.00 0.00 0.00 0.00 18384245.32 27584294.91
November 0.293661E+09 71654462.37 0.247408E+09 0.00 0.00 0.00 0.00 2758817.26 54390008.37
December 0.303141E+09 74544528.51 0.255955E+09 0.00 0.00 0.00 0.00 848660.33 83457387.83
                   
Annual Sum or Average 0.357224E+10 0.872819E+09 0.301074E+10 0.00 0.00 0.00 0.00 0.349754E+09 0.375315E+09
Minimum of Months 0.273974E+09 67054527.88 0.231020E+09 0.00 0.00 0.00 0.00 1355.28 323206.77
Maximum of Months 0.303685E+09 74544528.51 0.255955E+09 0.00 0.00 0.00 0.00 72527495.41 83457387.83



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.118113E+09 0.261068E+09 0.00 0.00 0.00 0.00 6159183.24 0.222102E+09
February 0.273974E+09 0.106667E+09 0.235798E+09 0.00 0.00 0.00 0.00 4008.99 0.247550E+09
March 0.303685E+09 0.117174E+09 0.260708E+09 0.00 0.00 0.00 0.00 10666434.96 0.205537E+09
April 0.293479E+09 0.114438E+09 0.252705E+09 0.00 0.00 0.00 0.00 93656490.34 53102704.81
May 0.303504E+09 0.117643E+09 0.260888E+09 0.00 0.00 0.00 0.00 0.150338E+09 19970453.99
June 0.293842E+09 0.113531E+09 0.252344E+09 0.00 0.00 0.00 0.00 0.261915E+09 983666.74
July 0.303141E+09 0.118566E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.250702E+09 787067.94
August 0.303685E+09 0.117174E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.233337E+09 1106511.26
September 0.293479E+09 0.114469E+09 0.252705E+09 0.00 0.00 0.00 0.00 0.171625E+09 3671143.03
October 0.303322E+09 0.118097E+09 0.261068E+09 0.00 0.00 0.00 0.00 65723168.29 97246586.48
November 0.293661E+09 0.113984E+09 0.252524E+09 0.00 0.00 0.00 0.00 8097443.10 0.197009E+09
December 0.303141E+09 0.118582E+09 0.261248E+09 0.00 0.00 0.00 0.00 1688356.29 0.307936E+09
                   
Annual Sum or Average 0.357224E+10 0.138844E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.125391E+10 0.135700E+10
Minimum of Months 0.273974E+09 0.106667E+09 0.235798E+09 0.00 0.00 0.00 0.00 4008.99 787067.94
Maximum of Months 0.303685E+09 0.118582E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.261915E+09 0.307936E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.118099E+09 0.261038E+09 0.00 0.00 0.00 0.00 6573350.97 0.219302E+09
February 0.273974E+09 0.106655E+09 0.235770E+09 0.00 0.00 0.00 0.00 4105.43 0.242038E+09
March 0.303685E+09 0.117160E+09 0.260677E+09 0.00 0.00 0.00 0.00 9850046.42 0.208058E+09
April 0.293479E+09 0.114425E+09 0.252675E+09 0.00 0.00 0.00 0.00 91013590.68 60633615.92
May 0.303504E+09 0.117629E+09 0.260857E+09 0.00 0.00 0.00 0.00 0.147077E+09 27855408.47
June 0.293842E+09 0.113517E+09 0.252315E+09 0.00 0.00 0.00 0.00 0.257973E+09 3267403.09
July 0.303141E+09 0.118553E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.249201E+09 1962914.08
August 0.303685E+09 0.117160E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.230552E+09 3550966.61
September 0.293479E+09 0.114456E+09 0.252675E+09 0.00 0.00 0.00 0.00 0.167874E+09 7487349.50
October 0.303322E+09 0.118083E+09 0.261038E+09 0.00 0.00 0.00 0.00 63727529.88 0.103416E+09
November 0.293661E+09 0.113971E+09 0.252495E+09 0.00 0.00 0.00 0.00 8104299.98 0.196602E+09
December 0.303141E+09 0.118568E+09 0.261218E+09 0.00 0.00 0.00 0.00 2075168.91 0.298048E+09
                   
Annual Sum or Average 0.357224E+10 0.138828E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.123403E+10 0.137222E+10
Minimum of Months 0.273974E+09 0.106655E+09 0.235770E+09 0.00 0.00 0.00 0.00 4105.43 1962914.08
Maximum of Months 0.303685E+09 0.118568E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.257973E+09 0.298048E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.108388E+10 0.00 0.00 0.00 0.00 0.00 8499401.37 0.285292E+09
February 0.348285E+10 0.978647E+09 0.00 0.00 0.00 0.00 0.00 63900.65 0.298308E+09
March 0.387034E+10 0.108722E+10 0.00 0.00 0.00 0.00 0.00 13404856.64 0.257134E+09
April 0.373454E+10 0.104713E+10 0.00 0.00 0.00 0.00 0.00 90360273.48 91761097.80
May 0.386038E+10 0.108576E+10 0.00 0.00 0.00 0.00 0.00 0.140638E+09 49835616.85
June 0.374269E+10 0.105194E+10 0.00 0.00 0.00 0.00 0.00 0.250401E+09 9258989.50
July 0.385223E+10 0.108096E+10 0.00 0.00 0.00 0.00 0.00 0.231083E+09 5843820.61
August 0.386853E+10 0.108764E+10 0.00 0.00 0.00 0.00 0.00 0.213752E+09 8520274.29
September 0.373273E+10 0.104755E+10 0.00 0.00 0.00 0.00 0.00 0.148918E+09 18642042.55
October 0.385404E+10 0.108346E+10 0.00 0.00 0.00 0.00 0.00 58928092.89 0.148851E+09
November 0.372639E+10 0.105110E+10 0.00 0.00 0.00 0.00 0.00 9896174.00 0.259534E+09
December 0.385223E+10 0.108096E+10 0.00 0.00 0.00 0.00 0.00 3216082.16 0.373218E+09
                   
Annual Sum or Average 0.454292E+11 0.127663E+11 0.00 0.00 0.00 0.00 0.00 0.116916E+10 0.180620E+10
Minimum of Months 0.348285E+10 0.978647E+09 0.00 0.00 0.00 0.00 0.00 63900.65 5843820.61
Maximum of Months 0.387034E+10 0.108764E+10 0.00 0.00 0.00 0.00 0.00 0.250401E+09 0.373218E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.118113E+09 0.261068E+09 0.00 0.00 0.00 0.00 5959403.60 0.221184E+09
February 0.273974E+09 0.106667E+09 0.235798E+09 0.00 0.00 0.00 0.00 3336.61 0.245134E+09
March 0.303685E+09 0.117174E+09 0.260708E+09 0.00 0.00 0.00 0.00 10521665.84 0.203369E+09
April 0.293479E+09 0.114438E+09 0.252705E+09 0.00 0.00 0.00 0.00 92813627.27 52601168.02
May 0.303504E+09 0.117643E+09 0.260888E+09 0.00 0.00 0.00 0.00 0.149348E+09 20068732.24
June 0.293842E+09 0.113531E+09 0.252344E+09 0.00 0.00 0.00 0.00 0.260351E+09 1043800.43
July 0.303141E+09 0.118566E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.249309E+09 824952.71
August 0.303685E+09 0.117174E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.231823E+09 1115378.45
September 0.293479E+09 0.114469E+09 0.252705E+09 0.00 0.00 0.00 0.00 0.170285E+09 3640345.91
October 0.303322E+09 0.118097E+09 0.261068E+09 0.00 0.00 0.00 0.00 65044118.56 96402583.31
November 0.293661E+09 0.113984E+09 0.252524E+09 0.00 0.00 0.00 0.00 7961426.22 0.196423E+09
December 0.303141E+09 0.118582E+09 0.261248E+09 0.00 0.00 0.00 0.00 1620149.14 0.306213E+09
                   
Annual Sum or Average 0.357224E+10 0.138844E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.124504E+10 0.134802E+10
Minimum of Months 0.273974E+09 0.106667E+09 0.235798E+09 0.00 0.00 0.00 0.00 3336.61 824952.71
Maximum of Months 0.303685E+09 0.118582E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.260351E+09 0.306213E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.118099E+09 0.261038E+09 0.00 0.00 0.00 0.00 6943808.95 0.219284E+09
February 0.273974E+09 0.106655E+09 0.235770E+09 0.00 0.00 0.00 0.00 8913.49 0.239796E+09
March 0.303685E+09 0.117160E+09 0.260677E+09 0.00 0.00 0.00 0.00 9876410.19 0.206788E+09
April 0.293479E+09 0.114425E+09 0.252675E+09 0.00 0.00 0.00 0.00 90844950.61 57335356.10
May 0.303504E+09 0.117629E+09 0.260857E+09 0.00 0.00 0.00 0.00 0.146949E+09 22795276.59
June 0.293842E+09 0.113517E+09 0.252315E+09 0.00 0.00 0.00 0.00 0.257157E+09 2036709.48
July 0.303141E+09 0.118553E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.248068E+09 1295219.12
August 0.303685E+09 0.117160E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.229600E+09 2550941.65
September 0.293479E+09 0.114456E+09 0.252675E+09 0.00 0.00 0.00 0.00 0.167371E+09 5678882.12
October 0.303322E+09 0.118083E+09 0.261038E+09 0.00 0.00 0.00 0.00 63704249.48 0.100084E+09
November 0.293661E+09 0.113971E+09 0.252495E+09 0.00 0.00 0.00 0.00 8235198.26 0.196306E+09
December 0.303141E+09 0.118568E+09 0.261218E+09 0.00 0.00 0.00 0.00 2243903.99 0.297167E+09
                   
Annual Sum or Average 0.357224E+10 0.138828E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.123100E+10 0.135112E+10
Minimum of Months 0.273974E+09 0.106655E+09 0.235770E+09 0.00 0.00 0.00 0.00 8913.49 1295219.12
Maximum of Months 0.303685E+09 0.118568E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.257157E+09 0.297167E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 74249479.06 0.255778E+09 0.00 0.00 0.00 0.00 3005604.23 0.115015E+09
February 0.273974E+09 67054527.88 0.231020E+09 0.00 0.00 0.00 0.00 1607.45 0.128390E+09
March 0.303685E+09 73659380.16 0.255425E+09 0.00 0.00 0.00 0.00 5319026.02 0.105878E+09
April 0.293479E+09 71939837.95 0.247584E+09 0.00 0.00 0.00 0.00 47460100.59 26980022.77
May 0.303504E+09 73954429.61 0.255602E+09 0.00 0.00 0.00 0.00 76460637.17 10267868.78
June 0.293842E+09 71369086.78 0.247231E+09 0.00 0.00 0.00 0.00 0.133451E+09 533903.58
July 0.303141E+09 74534854.64 0.255955E+09 0.00 0.00 0.00 0.00 0.127587E+09 421985.49
August 0.303685E+09 73659380.16 0.255425E+09 0.00 0.00 0.00 0.00 0.118673E+09 572871.01
September 0.293479E+09 71959185.68 0.247584E+09 0.00 0.00 0.00 0.00 87014425.32 1891093.38
October 0.303322E+09 74239805.19 0.255778E+09 0.00 0.00 0.00 0.00 33151176.72 50051079.62
November 0.293661E+09 71654462.37 0.247408E+09 0.00 0.00 0.00 0.00 3976013.20 0.102076E+09
December 0.303141E+09 74544528.51 0.255955E+09 0.00 0.00 0.00 0.00 815675.22 0.160056E+09
                   
Annual Sum or Average 0.357224E+10 0.872819E+09 0.301074E+10 0.00 0.00 0.00 0.00 0.636915E+09 0.702135E+09
Minimum of Months 0.273974E+09 67054527.88 0.231020E+09 0.00 0.00 0.00 0.00 1607.45 421985.49
Maximum of Months 0.303685E+09 74544528.51 0.255955E+09 0.00 0.00 0.00 0.00 0.133451E+09 0.160056E+09



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.232262E+10 0.149358E+11 0.00 0.00 0.00 0.00 7425908.28 0.696626E+09
February 0.415303E+11 0.207615E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.758697E+09
March 0.461508E+11 0.221234E+10 0.149358E+11 0.00 0.00 0.00 0.00 14010436.62 0.655690E+09
April 0.445315E+11 0.205172E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.156068E+09 0.217340E+09
May 0.460320E+11 0.205514E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.266077E+09 0.113398E+09
June 0.446286E+11 0.192029E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.499916E+09 19981942.37
July 0.459349E+11 0.200786E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.458977E+09 12889068.32
August 0.461292E+11 0.213003E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.422732E+09 20030718.08
September 0.445099E+11 0.209741E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.292732E+09 42741579.62
October 0.459565E+11 0.227261E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.108870E+09 0.349955E+09
November 0.444343E+11 0.223592E+10 0.144540E+11 0.00 0.00 0.00 0.00 11378669.55 0.632573E+09
December 0.459349E+11 0.232388E+10 0.149358E+11 0.00 0.00 0.00 0.00 2176491.03 0.912996E+09
                   
Annual Sum or Average 0.541708E+12 0.257060E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.224036E+10 0.443292E+10
Minimum of Months 0.415303E+11 0.192029E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 12889068.32
Maximum of Months 0.461508E+11 0.232388E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.499916E+09 0.912996E+09



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.232262E+10 0.149358E+11 0.00 0.00 0.00 0.00 6222733.75 0.703983E+09
February 0.415303E+11 0.207615E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.768105E+09
March 0.461508E+11 0.221234E+10 0.149358E+11 0.00 0.00 0.00 0.00 13180179.67 0.662953E+09
April 0.445315E+11 0.205172E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.154948E+09 0.218083E+09
May 0.460320E+11 0.205514E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.265500E+09 0.113436E+09
June 0.446286E+11 0.192029E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.499838E+09 19982450.37
July 0.459349E+11 0.200786E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.458894E+09 12889492.48
August 0.461292E+11 0.213003E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.422556E+09 20034763.82
September 0.445099E+11 0.209741E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.292327E+09 42775793.98
October 0.459565E+11 0.227261E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.107852E+09 0.352754E+09
November 0.444343E+11 0.223592E+10 0.144540E+11 0.00 0.00 0.00 0.00 10185226.53 0.638840E+09
December 0.459349E+11 0.232388E+10 0.149358E+11 0.00 0.00 0.00 0.00 1678346.04 0.923674E+09
                   
Annual Sum or Average 0.541708E+12 0.257060E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.223318E+10 0.447751E+10
Minimum of Months 0.415303E+11 0.192029E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 12889492.48
Maximum of Months 0.461508E+11 0.232388E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.499838E+09 0.923674E+09



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.101925E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 4982205.78 0.624045E+09
February 0.369574E+10 0.920291E+09 0.293798E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.684533E+09
March 0.410691E+10 0.102239E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 11441414.55 0.587864E+09
April 0.396281E+10 0.984694E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 0.138413E+09 0.191389E+09
May 0.409635E+10 0.102102E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.237715E+09 99160337.68
June 0.397146E+10 0.989210E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 0.447688E+09 17571945.37
July 0.408770E+10 0.101650E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.411070E+09 11269289.80
August 0.410499E+10 0.102279E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.378497E+09 17422158.68
September 0.396089E+10 0.985086E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 0.261771E+09 37325929.80
October 0.408962E+10 0.101886E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 96178124.06 0.311879E+09
November 0.395417E+10 0.988424E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 8416271.90 0.565625E+09
December 0.408770E+10 0.101650E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 1224665.42 0.821882E+09
                   
Annual Sum or Average 0.482060E+11 0.120050E+11 0.382987E+12 0.359593E+12 0.00 0.00 0.00 0.199740E+10 0.396997E+10
Minimum of Months 0.369574E+10 0.920291E+09 0.293798E+11 0.275852E+11 0.00 0.00 0.00 0.00 11269289.80
Maximum of Months 0.410691E+10 0.102279E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.447688E+09 0.821882E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.114712E+10 0.00 0.00 0.00 0.00 0.00 11788514.50 0.493772E+09
February 0.368610E+10 0.103575E+10 0.00 0.00 0.00 0.00 0.00 1624.22 0.528166E+09
March 0.409620E+10 0.115066E+10 0.00 0.00 0.00 0.00 0.00 19714328.61 0.452064E+09
April 0.395248E+10 0.110823E+10 0.00 0.00 0.00 0.00 0.00 0.147064E+09 0.157606E+09
May 0.408566E+10 0.114911E+10 0.00 0.00 0.00 0.00 0.00 0.239051E+09 83864462.01
June 0.396110E+10 0.111331E+10 0.00 0.00 0.00 0.00 0.00 0.439327E+09 14995444.10
July 0.407704E+10 0.114403E+10 0.00 0.00 0.00 0.00 0.00 0.404063E+09 9489850.67
August 0.409429E+10 0.115110E+10 0.00 0.00 0.00 0.00 0.00 0.373344E+09 13856776.15
September 0.395056E+10 0.110867E+10 0.00 0.00 0.00 0.00 0.00 0.259451E+09 30413241.14
October 0.407896E+10 0.114668E+10 0.00 0.00 0.00 0.00 0.00 0.101320E+09 0.248139E+09
November 0.394385E+10 0.111243E+10 0.00 0.00 0.00 0.00 0.00 14930252.95 0.445830E+09
December 0.407704E+10 0.114403E+10 0.00 0.00 0.00 0.00 0.00 3992340.18 0.657068E+09
                   
Annual Sum or Average 0.480803E+11 0.135111E+11 0.00 0.00 0.00 0.00 0.00 0.201405E+10 0.313526E+10
Minimum of Months 0.368610E+10 0.103575E+10 0.00 0.00 0.00 0.00 0.00 1624.22 9489850.67
Maximum of Months 0.409620E+10 0.115110E+10 0.00 0.00 0.00 0.00 0.00 0.439327E+09 0.657068E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 8344.11 02-JAN-20:10 9632.53 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 8344.11 01-FEB-20:10 9632.53 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 8344.11 01-MAR-20:10 9632.53 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 8344.11 03-APR-19:10 9632.53 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 8344.11 01-MAY-19:10 9632.53 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 8344.11 01-JUN-19:10 9632.53 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 8344.11 03-JUL-19:10 9632.53 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 8344.11 01-AUG-19:10 9632.53 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 8344.11 01-SEP-19:10 9632.53 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 8344.11 02-OCT-19:10 9632.53 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 8344.11 01-NOV-19:10 9632.53 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 8344.11 01-DEC-20:10 9632.53 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   8344.11   9632.53   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   8344.11   9632.53   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 461.08 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 94.54 31-JAN-16:00 427.08 01-JAN-08:00
February 1169.53 01-FEB-00:10 461.08 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 2.25 18-FEB-16:00 327.81 28-FEB-07:00
March 1169.53 01-MAR-00:10 461.08 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 106.43 20-MAR-17:00 425.65 26-MAR-06:00
April 1169.53 01-APR-00:10 461.08 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 202.53 14-APR-16:00 262.88 21-APR-04:03
May 1169.53 01-MAY-00:10 461.08 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 238.26 31-MAY-17:00 199.62 01-MAY-04:00
June 1169.53 01-JUN-00:10 461.08 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 325.11 28-JUN-16:00 95.70 21-JUN-05:00
July 1169.53 01-JUL-00:10 461.08 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 292.68 19-JUL-13:00 99.42 01-JUL-05:55
August 1169.53 01-AUG-00:10 461.08 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 309.44 25-AUG-14:00 114.89 05-AUG-18:00
September 1169.53 01-SEP-00:10 461.08 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 262.26 08-SEP-15:00 108.75 22-SEP-06:00
October 1169.53 01-OCT-23:10 461.08 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 239.13 01-OCT-13:00 325.80 25-OCT-07:00
November 1169.53 01-NOV-00:10 461.08 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 94.14 01-NOV-15:00 438.27 23-NOV-06:40
December 1169.53 01-DEC-00:10 461.08 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 38.51 02-DEC-15:00 460.74 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   461.08   685.60   0.00 0.00 0.00 0.00 2.25   95.70  
Maximum of Months 1169.53   461.08   685.60   0.00 0.00 0.00 0.00 325.11   460.74  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 533.93 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 41.80 31-JAN-16:00 173.11 01-JAN-08:00
February 1354.32 01-FEB-00:10 533.93 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 143.12 01-FEB-05:30
March 1354.32 01-MAR-00:10 533.93 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 42.71 20-MAR-17:00 172.68 26-MAR-04:00
April 1354.32 01-APR-00:10 533.93 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 79.62 14-APR-15:00 120.14 21-APR-04:30
May 1354.32 01-MAY-00:10 533.93 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 93.93 15-MAY-17:00 90.77 01-MAY-04:00
June 1354.32 01-JUN-00:10 533.93 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 125.50 28-JUN-16:00 45.02 21-JUN-06:00
July 1354.32 01-JUL-00:10 533.93 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 115.48 19-JUL-13:00 45.35 01-JUL-06:00
August 1354.32 01-AUG-00:10 533.93 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 119.60 25-AUG-14:00 52.08 05-AUG-18:00
September 1354.32 01-SEP-00:10 533.93 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 101.23 08-SEP-15:00 54.93 22-SEP-06:00
October 1354.32 01-OCT-23:10 533.93 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 94.45 01-OCT-13:00 141.04 25-OCT-06:00
November 1354.32 01-NOV-00:10 533.93 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 39.59 01-NOV-15:00 182.92 23-NOV-06:20
December 1354.32 01-DEC-00:10 533.93 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 24.17 21-DEC-15:00 188.94 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   533.93   793.93   0.00 0.00 0.00 0.00 0.00   45.02  
Maximum of Months 1354.32   533.93   793.93   0.00 0.00 0.00 0.00 125.50   188.94  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 615.76 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 122.12 31-JAN-16:50 389.61 01-JAN-08:00
February 286.42 01-FEB-00:10 615.76 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 11.97 18-FEB-14:00 310.80 01-FEB-07:30
March 286.42 01-MAR-00:10 615.76 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 114.75 16-MAR-15:40 388.26 26-MAR-06:00
April 286.42 01-APR-00:10 615.76 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 195.12 14-APR-15:50 264.19 21-APR-04:30
May 286.42 01-MAY-00:10 615.76 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 227.79 15-MAY-17:00 201.41 01-MAY-04:00
June 286.42 01-JUN-00:10 615.76 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 296.59 28-JUN-16:00 106.42 21-JUN-06:00
July 286.42 01-JUL-00:10 615.76 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 267.00 19-JUL-13:00 107.18 01-JUL-06:00
August 286.42 01-AUG-00:10 615.76 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 282.29 25-AUG-14:00 121.25 05-AUG-18:00
September 286.42 01-SEP-00:10 615.76 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 239.25 08-SEP-15:00 125.19 22-SEP-06:00
October 286.42 01-OCT-23:10 615.76 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 220.17 01-OCT-13:00 315.03 25-OCT-06:20
November 286.42 01-NOV-00:10 615.76 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 112.92 01-NOV-15:00 406.87 23-NOV-06:10
December 286.42 01-DEC-00:10 615.76 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 81.92 21-DEC-15:00 420.31 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   615.76   839.45   0.00 0.00 0.00 0.00 11.97   106.42  
Maximum of Months 286.42   615.76   839.45   0.00 0.00 0.00 0.00 296.59   420.31  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 137.35 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 69.45 31-JAN-17:00 224.79 01-JAN-08:00
February 220.32 01-FEB-00:10 137.35 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 6.67 18-FEB-14:00 177.42 01-FEB-05:20
March 220.32 01-MAR-00:10 137.35 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 65.62 20-MAR-17:00 224.01 26-MAR-06:00
April 220.32 01-APR-00:10 137.35 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 112.22 14-APR-16:30 150.54 21-APR-04:03
May 220.32 01-MAY-00:10 137.35 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 130.86 15-MAY-17:00 114.63 01-MAY-04:00
June 220.32 01-JUN-00:10 137.35 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 171.12 28-JUN-16:00 59.91 21-JUN-06:00
July 220.32 01-JUL-00:10 137.35 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 154.05 19-JUL-13:00 61.57 01-JUL-06:00
August 220.32 01-AUG-00:10 137.35 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 162.87 25-AUG-14:00 67.16 05-AUG-18:00
September 220.32 01-SEP-00:10 137.35 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 138.04 08-SEP-15:00 69.88 22-SEP-06:00
October 220.32 01-OCT-23:10 137.35 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 126.61 01-OCT-13:00 179.17 25-OCT-06:00
November 220.32 01-NOV-00:10 137.35 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 64.39 01-NOV-15:00 232.52 23-NOV-06:03
December 220.32 01-DEC-00:10 137.35 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 46.28 21-DEC-15:00 242.50 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   137.35   242.16   0.00 0.00 0.00 0.00 6.67   59.91  
Maximum of Months 220.32   137.35   242.16   0.00 0.00 0.00 0.00 171.12   242.50  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 360.62 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 148.85 31-JAN-17:00 609.69 01-JAN-08:00
February 907.20 01-FEB-00:10 360.62 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 0.00 01-FEB-00:05 484.68 28-FEB-07:00
March 907.20 01-MAR-00:10 360.62 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 150.89 20-MAR-17:00 596.61 26-MAR-06:10
April 907.20 01-APR-00:10 360.62 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 289.69 14-APR-17:00 396.09 21-APR-05:10
May 907.20 01-MAY-00:10 360.62 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 335.20 15-MAY-17:00 272.62 01-MAY-06:00
June 907.20 01-JUN-00:10 360.62 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 443.25 28-JUN-17:00 145.30 21-JUN-06:00
July 907.20 01-JUL-00:10 360.62 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 386.53 19-JUL-13:00 146.19 01-JUL-06:00
August 907.20 01-AUG-00:10 360.62 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 423.43 25-AUG-17:00 171.48 05-AUG-18:00
September 907.20 01-SEP-00:10 360.62 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 359.69 08-SEP-16:00 181.23 22-SEP-06:00
October 907.20 01-OCT-23:10 360.62 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 330.03 01-OCT-13:00 481.96 25-OCT-07:00
November 907.20 01-NOV-00:10 360.62 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 138.59 01-NOV-15:20 611.64 23-NOV-07:10
December 907.20 01-DEC-00:10 360.62 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 81.66 25-DEC-16:00 651.81 05-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   360.62   4572.80   39726.58   0.00 0.00 0.00 0.00   145.30  
Maximum of Months 907.20   360.62   4572.80   39726.58   0.00 0.00 0.00 443.25   651.81  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 1416.11 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 209.06 31-JAN-17:00 999.63 01-JAN-08:00
February 15368.40 01-FEB-00:10 1416.11 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 834.52 01-FEB-05:20
March 15368.40 01-MAR-00:10 1416.11 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 209.83 20-MAR-17:00 971.02 26-MAR-04:00
April 15368.40 01-APR-00:10 1416.11 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 447.80 14-APR-16:00 688.86 21-APR-04:10
May 15368.40 01-MAY-00:10 1416.11 01-MAY-19:10 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 526.79 31-MAY-17:00 525.90 01-MAY-04:00
June 15368.40 01-JUN-00:10 1416.11 01-JUN-19:19 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 718.77 28-JUN-16:00 257.37 21-JUN-05:00
July 15368.40 01-JUL-00:10 1416.11 03-JUL-19:30 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 647.02 19-JUL-13:00 259.63 01-JUL-06:00
August 15368.40 01-AUG-00:10 1416.11 01-AUG-19:19 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 684.06 25-AUG-14:00 276.73 05-AUG-18:00
September 15368.40 01-SEP-00:10 1416.11 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 579.79 08-SEP-15:00 307.56 22-SEP-06:00
October 15368.40 01-OCT-23:10 1416.11 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 528.65 01-OCT-13:00 796.14 25-OCT-06:00
November 15368.40 01-NOV-00:10 1416.11 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 208.21 01-NOV-15:00 1023.37 23-NOV-06:10
December 15368.40 01-DEC-00:10 1416.11 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 84.41 21-DEC-15:00 1098.67 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   1416.11   965.27   0.00 0.00 0.00 0.00 0.00   257.37  
Maximum of Months 15368.40   1416.11   965.27   0.00 0.00 0.00 0.00 718.77   1098.67  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 9580.84 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 612.33 31-JAN-16:00 2932.62 01-JAN-08:00
February 45622.98 01-FEB-00:10 9580.84 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 2431.45 01-FEB-05:40
March 45622.98 01-MAR-00:10 9580.84 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 654.52 20-MAR-17:00 2902.88 26-MAR-06:00
April 45622.98 01-APR-00:10 9580.84 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 1289.08 14-APR-17:00 2033.17 21-APR-04:30
May 45622.98 01-MAY-00:10 9580.84 01-MAY-19:10 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 1536.16 15-MAY-17:00 1511.59 01-MAY-04:00
June 45622.98 01-JUN-00:10 9580.84 01-JUN-19:19 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 2053.54 28-JUN-16:00 736.66 21-JUN-06:00
July 45622.98 01-JUL-00:10 9580.84 03-JUL-19:30 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 1879.65 19-JUL-13:00 741.96 01-JUL-06:00
August 45622.98 01-AUG-00:10 9580.84 01-AUG-19:19 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 1956.82 26-AUG-16:00 869.18 05-AUG-18:00
September 45622.98 01-SEP-00:10 9580.84 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 1656.52 08-SEP-15:00 919.03 22-SEP-06:00
October 45622.98 01-OCT-23:10 9580.84 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 1533.81 01-OCT-13:00 2388.01 25-OCT-06:00
November 45622.98 01-NOV-00:10 9580.84 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 594.80 01-NOV-15:00 3054.04 23-NOV-06:40
December 45622.98 01-DEC-00:10 9580.84 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 310.05 21-DEC-15:00 3209.25 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   9580.84   10029.21   0.00 0.00 0.00 0.00 0.00   736.66  
Maximum of Months 45622.98   9580.84   10029.21   0.00 0.00 0.00 0.00 2053.54   3209.25  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 106.87 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 86.12 31-JAN-17:00 249.74 01-JAN-08:00
February 180.00 01-FEB-00:10 106.87 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 5.70 18-FEB-16:10 192.07 28-FEB-07:00
March 180.00 01-MAR-00:10 106.87 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 83.58 16-MAR-15:10 248.88 26-MAR-06:00
April 180.00 01-APR-00:10 106.87 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 147.98 14-APR-16:00 154.25 21-APR-04:07
May 180.00 01-MAY-00:10 106.87 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 168.58 31-MAY-17:00 105.99 01-MAY-04:00
June 180.00 01-JUN-00:10 106.87 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 218.30 16-JUN-16:00 35.60 21-JUN-06:00
July 180.00 01-JUL-00:10 106.87 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 197.65 20-JUL-15:10 35.86 01-JUL-06:00
August 180.00 01-AUG-00:10 106.87 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 209.48 25-AUG-15:10 72.79 05-AUG-18:00
September 180.00 01-SEP-00:10 106.87 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 182.23 08-SEP-16:00 52.00 22-SEP-06:00
October 180.00 01-OCT-00:10 106.87 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 148.37 03-OCT-16:00 190.93 25-OCT-07:00
November 180.00 01-NOV-00:10 106.87 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 83.99 01-NOV-15:10 256.21 23-NOV-06:10
December 180.00 01-DEC-00:10 106.87 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 49.89 25-DEC-16:07 269.28 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   106.87   237.06   0.00 0.00 0.00 0.00 5.70   35.60  
Maximum of Months 180.00   106.87   237.06   0.00 0.00 0.00 0.00 218.30   269.28  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 106.85 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 86.12 31-JAN-16:50 249.72 01-JAN-08:00
February 180.00 01-FEB-00:10 106.85 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 5.70 18-FEB-16:10 192.06 28-FEB-07:00
March 180.00 01-MAR-00:10 106.85 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 83.57 16-MAR-15:07 248.85 26-MAR-06:00
April 180.00 01-APR-00:10 106.85 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 147.97 14-APR-16:00 154.24 21-APR-04:07
May 180.00 01-MAY-00:10 106.85 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 168.57 31-MAY-17:00 105.98 01-MAY-04:00
June 180.00 01-JUN-00:10 106.85 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 218.28 16-JUN-16:00 56.75 21-JUN-06:00
July 180.00 01-JUL-00:10 106.85 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 197.71 20-JUL-15:10 56.23 01-JUL-06:00
August 180.00 01-AUG-00:10 106.85 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 209.47 25-AUG-15:10 72.36 05-AUG-18:00
September 180.00 01-SEP-00:10 106.85 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 182.43 08-SEP-15:10 61.17 22-SEP-06:00
October 180.00 01-OCT-00:10 106.85 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 148.36 03-OCT-16:00 190.91 25-OCT-07:00
November 180.00 01-NOV-00:10 106.85 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 83.98 01-NOV-15:10 256.19 23-NOV-06:10
December 180.00 01-DEC-00:10 106.85 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 49.88 25-DEC-16:07 269.26 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   106.85   237.03   0.00 0.00 0.00 0.00 5.70   56.23  
Maximum of Months 180.00   106.85   237.03   0.00 0.00 0.00 0.00 218.28   269.26  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 67.16 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 7.01 31-JAN-16:00 83.98 01-JAN-08:00
February 0.00 01-FEB-00:10 67.16 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 71.77 01-FEB-08:00
March 0.00 01-MAR-00:10 67.16 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 6.37 16-MAR-15:00 81.05 26-MAR-04:00
April 0.00 01-APR-00:10 67.16 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 24.72 14-APR-15:00 58.81 21-APR-04:00
May 0.00 01-MAY-00:10 67.16 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 30.54 31-MAY-17:00 47.23 01-MAY-04:00
June 0.00 01-JUN-00:10 67.16 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 44.72 28-JUN-16:00 27.42 21-JUN-06:00
July 0.00 01-JUL-00:10 67.16 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 39.37 19-JUL-13:00 27.62 01-JUL-05:55
August 0.00 01-AUG-00:10 67.16 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 42.12 25-AUG-14:00 30.92 05-AUG-18:00
September 0.00 01-SEP-00:10 67.16 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 34.42 08-SEP-15:00 32.20 22-SEP-06:00
October 0.00 01-OCT-00:10 67.16 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 30.65 01-OCT-13:00 71.27 25-OCT-07:00
November 0.00 01-NOV-00:10 67.16 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 6.98 01-NOV-15:00 85.78 23-NOV-06:20
December 0.00 01-DEC-00:10 67.16 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 89.26 05-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   67.16   232.19   0.00 0.00 0.00 0.00 0.00   27.42  
Maximum of Months 0.00   67.16   232.19   0.00 0.00 0.00 0.00 44.72   89.26  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 67.18 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 24.04 31-JAN-16:40 69.70 01-JAN-08:00
February 180.00 01-FEB-00:10 67.18 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 1.59 18-FEB-16:09 53.60 28-FEB-07:00
March 180.00 01-MAR-00:10 67.18 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 23.33 16-MAR-15:10 69.46 26-MAR-06:00
April 180.00 01-APR-00:10 67.18 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 41.30 14-APR-15:50 43.05 21-APR-04:07
May 180.00 01-MAY-00:10 67.18 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 47.05 31-MAY-17:00 29.58 01-MAY-04:00
June 180.00 01-JUN-00:10 67.18 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 60.99 28-JUN-16:00 14.30 21-JUN-06:00
July 180.00 01-JUL-00:10 67.18 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 55.21 20-JUL-15:10 13.32 01-JUL-06:00
August 180.00 01-AUG-00:10 67.18 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 58.46 25-AUG-15:50 18.28 05-AUG-18:00
September 180.00 01-SEP-00:10 67.18 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 50.93 08-SEP-15:10 17.01 22-SEP-06:00
October 180.00 01-OCT-00:10 67.18 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 41.41 03-OCT-16:00 53.29 25-OCT-07:00
November 180.00 01-NOV-00:10 67.18 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 23.44 01-NOV-15:09 71.51 23-NOV-06:10
December 180.00 01-DEC-00:10 67.18 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 13.92 25-DEC-16:07 75.15 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   67.18   232.26   0.00 0.00 0.00 0.00 1.59   13.32  
Maximum of Months 180.00   67.18   232.26   0.00 0.00 0.00 0.00 60.99   75.15  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 106.87 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 86.13 31-JAN-17:00 249.74 01-JAN-08:00
February 180.00 01-FEB-00:10 106.87 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 5.70 18-FEB-16:07 192.07 28-FEB-07:00
March 180.00 01-MAR-00:10 106.87 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 83.58 16-MAR-15:07 248.88 26-MAR-06:00
April 180.00 01-APR-00:10 106.87 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 147.98 14-APR-15:10 154.25 21-APR-04:07
May 180.00 01-MAY-00:10 106.87 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 168.58 31-MAY-17:00 105.99 01-MAY-04:00
June 180.00 01-JUN-00:10 106.87 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 218.50 28-JUN-16:00 35.60 21-JUN-05:55
July 180.00 01-JUL-00:10 106.87 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 197.68 20-JUL-15:10 35.86 01-JUL-05:55
August 180.00 01-AUG-00:10 106.87 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 209.48 25-AUG-15:50 72.79 05-AUG-18:00
September 180.00 01-SEP-00:10 106.87 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 182.30 08-SEP-15:50 52.00 22-SEP-06:00
October 180.00 01-OCT-00:10 106.87 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 148.37 03-OCT-16:00 190.93 25-OCT-07:00
November 180.00 01-NOV-00:10 106.87 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 83.99 01-NOV-15:10 256.21 23-NOV-06:10
December 180.00 01-DEC-00:10 106.87 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 49.89 25-DEC-16:10 269.28 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   106.87   237.06   0.00 0.00 0.00 0.00 5.70   35.60  
Maximum of Months 180.00   106.87   237.06   0.00 0.00 0.00 0.00 218.50   269.28  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 106.85 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 86.12 31-JAN-16:50 249.72 01-JAN-08:00
February 180.00 01-FEB-00:10 106.85 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 5.70 18-FEB-16:10 192.06 28-FEB-07:00
March 180.00 01-MAR-00:10 106.85 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 83.57 16-MAR-15:07 248.86 26-MAR-06:00
April 180.00 01-APR-00:10 106.85 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 147.97 14-APR-16:00 154.24 21-APR-04:07
May 180.00 01-MAY-00:10 106.85 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 168.55 31-MAY-17:00 105.98 01-MAY-04:00
June 180.00 01-JUN-00:10 106.85 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 218.47 28-JUN-16:10 63.63 21-JUN-06:00
July 180.00 01-JUL-00:10 106.85 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 197.73 20-JUL-15:10 60.68 01-JUL-06:00
August 180.00 01-AUG-00:10 106.85 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 209.47 25-AUG-15:10 73.84 05-AUG-18:00
September 180.00 01-SEP-00:10 106.85 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 182.47 08-SEP-15:10 61.14 22-SEP-06:00
October 180.00 01-OCT-00:10 106.85 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 148.36 03-OCT-16:00 190.91 25-OCT-07:00
November 180.00 01-NOV-00:10 106.85 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 83.98 01-NOV-15:07 256.19 23-NOV-06:07
December 180.00 01-DEC-00:10 106.85 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 49.88 25-DEC-16:07 269.26 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   106.85   237.03   0.00 0.00 0.00 0.00 5.70   60.68  
Maximum of Months 180.00   106.85   237.03   0.00 0.00 0.00 0.00 218.47   269.26  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 1044.00 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 81.81 31-JAN-16:00 300.38 01-JAN-08:00
February 2263.36 01-FEB-00:10 1044.00 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 7.82 18-FEB-14:00 248.21 01-FEB-05:03
March 2263.36 01-MAR-00:10 1044.00 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 83.94 16-MAR-15:00 304.16 26-MAR-04:00
April 2263.36 01-APR-00:10 1044.00 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 144.86 14-APR-17:00 211.63 21-APR-04:03
May 2263.36 01-MAY-00:10 1044.00 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 171.44 15-MAY-17:00 157.84 01-MAY-04:00
June 2263.36 01-JUN-00:10 1044.00 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 227.64 28-JUN-16:00 81.05 21-JUN-05:00
July 2263.36 01-JUL-00:10 1044.00 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 204.87 19-JUL-13:00 82.17 01-JUL-06:00
August 2263.36 01-AUG-00:10 1044.00 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 216.63 25-AUG-14:00 91.49 05-AUG-18:00
September 2263.36 01-SEP-00:10 1044.00 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 183.52 08-SEP-15:00 95.72 22-SEP-06:00
October 2263.36 01-OCT-23:10 1044.00 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 168.46 01-OCT-13:00 246.71 25-OCT-06:00
November 2263.36 01-NOV-00:10 1044.00 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 78.87 01-NOV-15:00 321.75 23-NOV-06:00
December 2263.36 01-DEC-00:10 1044.00 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 56.20 21-DEC-15:00 330.28 05-DEC-04:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   1044.00   0.00 0.00 0.00 0.00 0.00 7.82   81.05  
Maximum of Months 2263.36   1044.00   0.00 0.00 0.00 0.00 0.00 227.64   330.28  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 106.87 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 85.49 31-JAN-17:00 250.50 01-JAN-08:00
February 180.00 01-FEB-00:10 106.87 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 5.04 18-FEB-16:07 192.82 28-FEB-07:00
March 180.00 01-MAR-00:10 106.87 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 82.95 16-MAR-15:10 249.65 26-MAR-06:00
April 180.00 01-APR-00:10 106.87 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 147.36 14-APR-15:10 154.98 21-APR-04:07
May 180.00 01-MAY-00:10 106.87 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 167.98 31-MAY-17:00 106.70 01-MAY-04:00
June 180.00 01-JUN-00:10 106.87 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 217.72 16-JUN-16:00 36.28 21-JUN-05:55
July 180.00 01-JUL-00:10 106.87 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 196.03 20-JUL-15:10 36.54 01-JUL-06:00
August 180.00 01-AUG-00:10 106.87 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 208.89 25-AUG-15:10 71.68 05-AUG-18:00
September 180.00 01-SEP-00:10 106.87 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 181.56 08-SEP-16:00 52.68 22-SEP-06:00
October 180.00 01-OCT-00:10 106.87 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 147.76 03-OCT-16:00 191.67 25-OCT-07:00
November 180.00 01-NOV-00:10 106.87 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 83.34 01-NOV-15:10 256.99 23-NOV-06:10
December 180.00 01-DEC-00:10 106.87 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 49.24 25-DEC-16:07 270.06 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   106.87   237.06   0.00 0.00 0.00 0.00 5.04   36.28  
Maximum of Months 180.00   106.87   237.06   0.00 0.00 0.00 0.00 217.72   270.06  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 106.85 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 85.48 31-JAN-16:50 250.49 01-JAN-08:00
February 180.00 01-FEB-00:10 106.85 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 5.04 18-FEB-16:07 192.80 28-FEB-07:00
March 180.00 01-MAR-00:10 106.85 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 82.94 16-MAR-15:10 249.63 26-MAR-06:00
April 180.00 01-APR-00:10 106.85 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 147.36 14-APR-16:00 154.96 21-APR-04:07
May 180.00 01-MAY-00:10 106.85 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 167.97 31-MAY-17:00 106.69 01-MAY-04:00
June 180.00 01-JUN-00:10 106.85 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 217.71 16-JUN-16:00 53.19 21-JUN-06:00
July 180.00 01-JUL-00:10 106.85 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 196.63 20-JUL-15:10 53.16 01-JUL-06:00
August 180.00 01-AUG-00:10 106.85 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 208.87 25-AUG-15:10 70.84 05-AUG-18:00
September 180.00 01-SEP-00:10 106.85 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 181.65 08-SEP-16:00 56.88 22-SEP-06:00
October 180.00 01-OCT-00:10 106.85 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 147.75 03-OCT-16:00 191.65 25-OCT-07:00
November 180.00 01-NOV-00:10 106.85 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 83.35 01-NOV-15:10 256.97 23-NOV-06:10
December 180.00 01-DEC-00:10 106.85 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 49.24 25-DEC-16:07 270.04 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   106.85   237.03   0.00 0.00 0.00 0.00 5.04   53.16  
Maximum of Months 180.00   106.85   237.03   0.00 0.00 0.00 0.00 217.71   270.04  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 67.18 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 43.74 31-JAN-17:00 128.17 01-JAN-08:00
February 180.00 01-FEB-00:10 67.18 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 2.58 18-FEB-16:09 98.65 28-FEB-07:00
March 180.00 01-MAR-00:10 67.18 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 42.44 16-MAR-15:10 127.73 26-MAR-06:00
April 180.00 01-APR-00:10 67.18 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 75.40 14-APR-16:00 79.29 21-APR-04:10
May 180.00 01-MAY-00:10 67.18 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 85.94 31-MAY-17:00 54.59 01-MAY-04:00
June 180.00 01-JUN-00:10 67.18 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 111.49 28-JUN-16:10 18.56 21-JUN-05:55
July 180.00 01-JUL-00:10 67.18 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 100.71 20-JUL-15:10 18.69 01-JUL-06:00
August 180.00 01-AUG-00:10 67.18 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 106.88 25-AUG-16:30 35.49 05-AUG-18:00
September 180.00 01-SEP-00:10 67.18 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 92.95 08-SEP-16:00 26.96 22-SEP-06:00
October 180.00 01-OCT-00:10 67.18 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 75.60 03-OCT-16:00 98.07 25-OCT-07:00
November 180.00 01-NOV-00:10 67.18 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 39.79 01-NOV-15:10 131.48 23-NOV-06:10
December 180.00 01-DEC-00:10 67.18 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 25.19 25-DEC-16:10 138.17 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   67.18   232.26   0.00 0.00 0.00 0.00 2.58   18.56  
Maximum of Months 180.00   67.18   232.26   0.00 0.00 0.00 0.00 111.49   138.17  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 2486.81 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 132.14 31-JAN-16:00 696.84 01-JAN-08:00
February 26988.77 01-FEB-00:10 2486.81 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 554.58 28-FEB-07:00
March 26988.77 01-MAR-00:10 2486.81 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 125.45 16-MAR-15:00 692.14 26-MAR-06:00
April 26988.77 01-APR-00:10 2486.81 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 284.51 14-APR-16:00 461.06 21-APR-04:10
May 26988.77 01-MAY-00:10 2486.81 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 335.17 31-MAY-17:00 342.03 01-MAY-04:00
June 26988.77 01-JUN-00:10 2486.81 01-JUN-19:19 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 458.32 28-JUN-16:00 168.09 21-JUN-06:00
July 26988.77 01-JUL-00:10 2486.81 03-JUL-19:30 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 412.26 19-JUL-13:00 169.30 01-JUL-06:00
August 26988.77 01-AUG-00:10 2486.81 01-AUG-19:19 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 436.03 25-AUG-14:00 197.89 05-AUG-18:00
September 26988.77 01-SEP-00:10 2486.81 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 369.15 08-SEP-15:00 209.03 22-SEP-06:00
October 26988.77 01-OCT-23:10 2486.81 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 336.35 01-OCT-13:00 551.16 25-OCT-06:00
November 26988.77 01-NOV-00:10 2486.81 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 130.81 01-NOV-15:00 712.77 23-NOV-07:00
December 26988.77 01-DEC-00:10 2486.81 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 72.51 21-DEC-15:00 745.00 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   2486.81   6747.90   0.00 0.00 0.00 0.00 0.00   168.09  
Maximum of Months 26988.77   2486.81   6747.90   0.00 0.00 0.00 0.00 458.32   745.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 2486.81 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 131.35 31-JAN-17:00 696.85 01-JAN-08:00
February 26988.77 01-FEB-00:10 2486.81 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 554.59 28-FEB-07:00
March 26988.77 01-MAR-00:10 2486.81 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 125.45 16-MAR-15:00 694.46 26-MAR-06:00
April 26988.77 01-APR-00:10 2486.81 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 284.51 14-APR-16:00 461.06 21-APR-04:10
May 26988.77 01-MAY-00:10 2486.81 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 335.17 31-MAY-17:00 342.04 01-MAY-04:00
June 26988.77 01-JUN-00:10 2486.81 01-JUN-19:19 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 458.32 28-JUN-16:00 168.09 21-JUN-06:00
July 26988.77 01-JUL-00:10 2486.81 03-JUL-19:30 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 412.26 19-JUL-13:00 169.30 01-JUL-06:00
August 26988.77 01-AUG-00:10 2486.81 01-AUG-19:19 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 436.03 25-AUG-14:00 197.89 05-AUG-18:00
September 26988.77 01-SEP-00:10 2486.81 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 369.15 08-SEP-15:00 209.03 22-SEP-06:00
October 26988.77 01-OCT-23:10 2486.81 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 336.35 01-OCT-13:00 551.16 25-OCT-06:00
November 26988.77 01-NOV-00:10 2486.81 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 130.81 01-NOV-15:00 712.81 23-NOV-07:00
December 26988.77 01-DEC-00:10 2486.81 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 63.48 21-DEC-15:00 745.01 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   2486.81   6747.90   0.00 0.00 0.00 0.00 0.00   168.09  
Maximum of Months 26988.77   2486.81   6747.90   0.00 0.00 0.00 0.00 458.32   745.01  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 981.75 02-JAN-20:10 14604.56 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 117.91 31-JAN-16:40 623.67 01-JAN-08:00
February 2401.70 01-FEB-00:10 981.75 01-FEB-20:10 14604.56 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 0.00 01-FEB-00:05 496.39 28-FEB-07:00
March 2401.70 01-MAR-00:10 981.75 01-MAR-20:10 14604.56 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 112.57 16-MAR-15:40 621.55 26-MAR-06:00
April 2401.70 01-APR-00:10 981.75 03-APR-19:10 14604.56 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 255.03 14-APR-15:40 412.75 21-APR-04:07
May 2401.70 01-MAY-00:10 981.75 01-MAY-19:10 14604.56 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 300.36 31-MAY-17:00 296.66 01-MAY-04:00
June 2401.70 01-JUN-00:10 981.75 01-JUN-19:10 14604.56 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 410.59 28-JUN-16:00 150.38 21-JUN-05:55
July 2401.70 01-JUL-00:10 981.75 03-JUL-19:10 14604.56 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 369.30 19-JUL-13:00 151.45 01-JUL-06:00
August 2401.70 01-AUG-00:10 981.75 01-AUG-19:10 14604.56 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 390.54 25-AUG-14:00 176.87 05-AUG-18:00
September 2401.70 01-SEP-00:10 981.75 01-SEP-19:10 14604.56 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 330.69 08-SEP-15:00 187.03 22-SEP-06:00
October 2401.70 01-OCT-23:10 981.75 02-OCT-19:10 14604.56 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 301.36 01-OCT-13:00 493.40 25-OCT-06:10
November 2401.70 01-NOV-00:10 981.75 01-NOV-19:10 14604.56 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 117.33 01-NOV-15:00 637.98 23-NOV-07:00
December 2401.70 01-DEC-00:10 981.75 01-DEC-20:10 14604.56 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 46.21 21-DEC-15:00 666.80 05-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   981.75   14604.56   22492.83   0.00 0.00 0.00 0.00   150.38  
Maximum of Months 2401.70   981.75   14604.56   22492.83   0.00 0.00 0.00 410.59   666.80  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 1104.91 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 136.53 31-JAN-17:00 533.14 01-JAN-08:00
February 2395.44 01-FEB-00:10 1104.91 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 1.05 18-FEB-14:00 422.52 01-FEB-05:03
March 2395.44 01-MAR-00:10 1104.91 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 134.67 15-MAR-15:00 531.29 26-MAR-06:00
April 2395.44 01-APR-00:10 1104.91 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 249.22 14-APR-15:00 353.06 21-APR-04:00
May 2395.44 01-MAY-00:10 1104.91 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 293.60 31-MAY-17:00 271.55 01-MAY-04:00
June 2395.44 01-JUN-00:10 1104.91 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 401.51 28-JUN-16:00 135.30 21-JUN-05:00
July 2395.44 01-JUL-00:10 1104.91 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 361.19 19-JUL-13:00 139.32 01-JUL-05:55
August 2395.44 01-AUG-00:10 1104.91 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 382.02 25-AUG-14:00 161.95 05-AUG-18:00
September 2395.44 01-SEP-00:10 1104.91 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 323.41 08-SEP-15:00 157.46 22-SEP-06:00
October 2395.44 01-OCT-23:10 1104.91 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 294.67 01-OCT-13:00 414.95 25-OCT-06:00
November 2395.44 01-NOV-00:10 1104.91 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 122.07 01-NOV-15:00 546.98 23-NOV-06:40
December 2395.44 01-DEC-00:10 1104.91 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 82.49 21-DEC-15:00 574.93 05-DEC-04:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   1104.91   0.00 0.00 0.00 0.00 0.00 1.05   135.30  
Maximum of Months 2395.44   1104.91   0.00 0.00 0.00 0.00 0.00 401.51   574.93  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 14006.18 20-JAN-22:00 10223.90 7417.00 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
February 12045.86 01-FEB-22:00 10223.90 7417.00 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
March 10688.80 01-MAR-21:00 8945.92 8344.11 9632.53 0.00 0.00 0.00 0.00 0.00 0.00
April 11953.78 30-APR-10:33 11501.89 8343.99 12167.41 0.00 0.00 0.00 0.00 0.00 0.00
May 11598.97 04-MAY-18:10 62621.41 51919.01 63878.88 0.00 0.00 0.00 0.00 0.00 0.00
June 12622.55 28-JUN-18:10 44729.58 37085.01 45627.77 0.00 0.00 0.00 0.00 0.00 0.00
July 16060.55 14-JUL-21:00 10223.90 7417.00 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
August 18522.66 04-AUG-21:00 10223.90 7417.00 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
September 21680.88 20-SEP-21:00 10223.90 7417.00 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
October 21257.09 19-OCT-21:00 10223.90 7417.00 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
November 20936.10 22-NOV-22:00 10223.90 7417.00 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
December 20099.51 01-DEC-22:00 10223.90 7417.00 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 10688.80   8945.92 7417.00 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21680.88   62621.41 51919.01 63878.88 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3521.93 14-JAN-13:40 389.84 128.08 252.59 0.00 0.00 0.00 0.00 50.93 0.00
February 2491.68 01-FEB-14:00 259.90 128.08 252.59 0.00 0.00 0.00 0.00 0.00 157.44
March 2656.38 18-MAR-13:40 389.84 128.08 252.59 0.00 0.00 0.00 0.00 43.31 0.00
April 3114.38 14-APR-14:10 389.84 128.08 252.59 0.00 0.00 0.00 0.00 187.86 0.00
May 2625.40 31-MAY-18:15 1819.27 819.70 1299.04 0.00 0.00 0.00 0.00 208.52 0.00
June 3504.82 28-JUN-18:13 2728.91 1229.55 1948.56 0.00 0.00 0.00 0.00 301.79 0.00
July 3229.85 21-JUL-18:30 909.64 409.85 649.52 0.00 0.00 0.00 0.00 256.14 0.00
August 3682.42 28-AUG-12:30 259.90 128.08 252.59 0.00 0.00 0.00 0.00 239.14 0.00
September 3936.80 28-SEP-13:30 259.90 128.08 252.59 0.00 0.00 0.00 0.00 223.40 0.00
October 3946.58 02-OCT-12:40 259.90 128.08 252.59 0.00 0.00 0.00 0.00 185.46 0.00
November 3716.97 21-NOV-13:40 259.90 128.08 252.59 0.00 0.00 0.00 0.00 19.03 0.00
December 3392.75 25-DEC-13:30 259.90 102.46 216.51 0.00 0.00 0.00 0.00 28.56 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2491.68   259.90 102.46 216.51 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3946.58   2728.91 1229.55 1948.56 0.00 0.00 0.00 0.00 301.79 157.44



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1544.21 27-JAN-21:10 1203.84 474.61 752.15 0.00 0.00 0.00 0.00 0.00 59.57
February 1288.98 01-FEB-21:00 1053.36 533.93 793.93 0.00 0.00 0.00 0.00 0.00 99.51
March 1619.35 17-MAR-21:00 1203.84 474.61 752.15 0.00 0.00 0.00 0.00 0.00 17.96
April 2222.83 14-APR-20:40 1203.84 474.61 752.15 0.00 0.00 0.00 0.00 40.89 0.00
May 2175.68 19-MAY-20:10 1203.84 474.61 752.15 0.00 0.00 0.00 0.00 48.15 0.00
June 2550.53 28-JUN-20:40 1203.84 474.61 752.15 0.00 0.00 0.00 0.00 82.75 0.00
July 2403.65 20-JUL-20:10 1203.84 474.61 752.15 0.00 0.00 0.00 0.00 79.66 0.00
August 2447.72 15-AUG-20:10 1203.84 474.61 752.15 0.00 0.00 0.00 0.00 76.07 0.00
September 2399.50 07-SEP-21:00 1203.84 474.61 752.15 0.00 0.00 0.00 0.00 66.93 0.00
October 2197.55 05-OCT-20:10 1203.84 474.61 752.15 0.00 0.00 0.00 0.00 18.24 0.00
November 1848.56 01-NOV-20:10 1203.84 474.61 752.15 0.00 0.00 0.00 0.00 0.00 26.19
December 1443.37 26-DEC-22:00 1203.84 474.61 752.15 0.00 0.00 0.00 0.00 0.00 68.82
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1288.98   1053.36 474.61 752.15 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2550.53   1203.84 533.93 793.93 0.00 0.00 0.00 0.00 82.75 99.51



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1087.04 08-JAN-11:33 286.42 615.76 1060.35 0.00 0.00 0.00 0.00 0.00 30.48
February 988.46 01-FEB-21:00 222.77 615.76 839.45 0.00 0.00 0.00 0.00 0.00 202.06
March 1176.39 18-MAR-18:10 1145.66 2873.54 4241.42 0.00 0.00 0.00 0.00 44.63 0.00
April 1512.28 14-APR-20:00 222.77 615.76 839.45 0.00 0.00 0.00 0.00 118.86 0.00
May 1818.16 19-MAY-20:00 222.77 615.76 839.45 0.00 0.00 0.00 0.00 119.34 0.00
June 2615.74 28-JUN-20:00 222.77 615.76 839.45 0.00 0.00 0.00 0.00 216.98 0.00
July 2501.02 21-JUL-20:00 222.77 615.76 839.45 0.00 0.00 0.00 0.00 217.80 0.00
August 2357.90 15-AUG-20:00 222.77 615.76 839.45 0.00 0.00 0.00 0.00 185.15 0.00
September 2217.87 08-SEP-20:00 222.77 615.76 839.45 0.00 0.00 0.00 0.00 166.06 0.00
October 1971.04 02-OCT-19:50 222.77 615.76 839.45 0.00 0.00 0.00 0.00 60.30 0.00
November 1208.48 02-NOV-18:06 1559.38 3831.39 5566.86 0.00 0.00 0.00 0.00 15.02 0.00
December 1026.93 26-DEC-21:00 222.77 615.76 839.45 0.00 0.00 0.00 0.00 0.00 131.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 988.46   222.77 615.76 839.45 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2615.74   1559.38 3831.39 5566.86 0.00 0.00 0.00 0.00 217.80 202.06



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 598.06 08-JAN-11:33 220.32 137.35 305.88 0.00 0.00 0.00 0.00 0.00 17.42
February 540.79 18-FEB-11:33 220.32 114.47 267.65 0.00 0.00 0.00 0.00 0.00 19.54
March 638.99 18-MAR-17:40 293.76 183.14 356.86 0.00 0.00 0.00 0.00 36.99 0.00
April 769.58 15-APR-10:33 220.32 114.47 267.65 0.00 0.00 0.00 0.00 46.60 0.00
May 801.72 31-MAY-18:10 1028.16 732.55 1376.47 0.00 0.00 0.00 0.00 114.47 0.00
June 1314.73 28-JUN-18:50 171.36 122.09 229.41 0.00 0.00 0.00 0.00 154.31 0.00
July 1216.87 21-JUL-19:10 171.36 137.35 242.16 0.00 0.00 0.00 0.00 133.29 0.00
August 1122.43 15-AUG-19:40 171.36 137.35 242.16 0.00 0.00 0.00 0.00 113.09 0.00
September 1043.16 08-SEP-19:40 171.36 137.35 242.16 0.00 0.00 0.00 0.00 101.16 0.00
October 889.18 03-OCT-21:00 195.84 122.09 229.41 0.00 0.00 0.00 0.00 59.32 0.00
November 652.21 02-NOV-18:06 1199.52 854.64 1605.89 0.00 0.00 0.00 0.00 10.53 0.00
December 567.03 25-DEC-11:33 220.32 137.35 305.88 0.00 0.00 0.00 0.00 7.56 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 540.79   171.36 114.47 229.41 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1314.73   1199.52 854.64 1605.89 0.00 0.00 0.00 0.00 154.31 19.54



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 37727.31 27-JAN-21:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 171.36
February 37292.37 22-FEB-21:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 272.17
March 38160.02 16-MAR-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 43.25
April 39213.00 14-APR-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 162.25 0.00
May 39332.35 18-MAY-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 140.29 0.00
June 40074.74 28-JUN-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 296.31 0.00
July 39896.83 21-JUL-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 297.40 0.00
August 39772.08 15-AUG-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 252.80 0.00
September 39593.85 08-SEP-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 226.76 0.00
October 39148.75 03-OCT-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 140.16 0.00
November 38119.13 01-NOV-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 72.33
December 37400.89 22-DEC-21:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 247.31
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 37292.37   705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 40074.74   705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 297.40 272.17



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 13769.61 14-JAN-13:30 5122.80 86.54 355.63 0.00 0.00 0.00 0.00 105.68 0.00
February 10453.01 01-FEB-16:03 59766.00 605.78 2489.39 0.00 0.00 0.00 0.00 0.00 355.11
March 10784.06 16-MAR-15:15 17076.00 173.08 711.25 0.00 0.00 0.00 0.00 199.77 0.00
April 12143.92 14-APR-21:10 15368.40 944.07 711.25 0.00 0.00 0.00 0.00 193.63 0.00
May 11692.02 09-MAY-21:10 15368.40 944.07 711.25 0.00 0.00 0.00 0.00 200.84 0.00
June 13321.30 28-JUN-21:10 15368.40 944.07 711.25 0.00 0.00 0.00 0.00 434.86 0.00
July 13209.92 21-JUL-21:10 15368.40 944.07 711.25 0.00 0.00 0.00 0.00 403.94 0.00
August 13104.78 15-AUG-21:10 15368.40 944.07 711.25 0.00 0.00 0.00 0.00 356.73 0.00
September 13997.98 28-SEP-15:03 51228.00 519.24 2133.76 0.00 0.00 0.00 0.00 548.10 0.00
October 13924.86 05-OCT-15:03 51228.00 519.24 2133.76 0.00 0.00 0.00 0.00 408.88 0.00
November 14228.08 01-NOV-15:03 59766.00 605.78 2489.39 0.00 0.00 0.00 0.00 201.28 0.00
December 13279.69 25-DEC-13:00 5122.80 103.85 406.43 0.00 0.00 0.00 0.00 42.18 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 10453.01   5122.80 86.54 355.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14228.08   59766.00 944.07 2489.39 0.00 0.00 0.00 0.00 548.10 355.11



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 35047.05 31-JAN-19:06 248391.78 59614.13 66509.49 0.00 0.00 0.00 0.00 0.00 122.22
February 30935.06 01-FEB-22:10 45622.98 6387.23 7389.94 0.00 0.00 0.00 0.00 0.00 1822.87
March 35809.78 17-MAR-21:10 45622.98 6387.23 7389.94 0.00 0.00 0.00 0.00 0.00 316.43
April 42474.73 14-APR-21:10 45622.98 6387.23 7389.94 0.00 0.00 0.00 0.00 552.99 0.00
May 42018.62 09-MAY-21:10 45622.98 6387.23 7389.94 0.00 0.00 0.00 0.00 573.59 0.00
June 47581.75 28-JUN-21:10 45622.98 6387.23 7389.94 0.00 0.00 0.00 0.00 1242.24 0.00
July 46881.30 21-JUL-20:10 40553.76 8516.30 9501.36 0.00 0.00 0.00 0.00 1452.83 0.00
August 46376.66 15-AUG-20:10 40553.76 8516.30 9501.36 0.00 0.00 0.00 0.00 1244.80 0.00
September 46264.11 07-SEP-21:10 45622.98 6387.23 7389.94 0.00 0.00 0.00 0.00 1032.21 0.00
October 44172.60 03-OCT-21:10 45622.98 6387.23 7389.94 0.00 0.00 0.00 0.00 653.74 0.00
November 38443.39 01-NOV-20:10 40553.76 8516.30 9501.36 0.00 0.00 0.00 0.00 0.00 428.36
December 33991.72 26-DEC-22:10 45622.98 6387.23 7389.94 0.00 0.00 0.00 0.00 0.00 1147.32
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 30935.06   40553.76 6387.23 7389.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 47581.75   248391.78 59614.13 66509.49 0.00 0.00 0.00 0.00 1452.83 1822.87



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3639.41 31-JAN-16:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 70.09 0.00
February 3347.73 28-FEB-16:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 0.00 40.36
March 3618.40 16-MAR-15:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 68.46 0.00
April 3680.74 14-APR-18:01 970.20 665.78 903.46 0.00 0.00 0.00 0.00 115.61 0.00
May 3658.00 03-MAY-15:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 113.57 0.00
June 3696.87 27-JUN-18:02 831.60 570.67 774.39 0.00 0.00 0.00 0.00 179.69 0.00
July 3676.15 05-JUL-18:02 831.60 570.67 774.39 0.00 0.00 0.00 0.00 160.99 0.00
August 3681.43 26-AUG-15:02 324.00 211.60 458.31 0.00 0.00 0.00 0.00 192.58 0.00
September 3680.18 28-SEP-15:02 583.20 179.54 410.90 0.00 0.00 0.00 0.00 157.66 0.00
October 3674.36 15-OCT-15:01 378.00 246.87 534.70 0.00 0.00 0.00 0.00 90.50 0.00
November 3664.81 20-NOV-16:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 45.77 0.00
December 3610.89 25-DEC-16:01 378.00 246.87 534.70 0.00 0.00 0.00 0.00 33.89 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3347.73   324.00 179.54 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3696.87   970.20 665.78 903.46 0.00 0.00 0.00 0.00 192.58 40.36



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3557.33 31-JAN-16:01 680.40 209.43 479.33 0.00 0.00 0.00 0.00 71.89 0.00
February 3268.37 28-FEB-16:01 680.40 209.43 479.33 0.00 0.00 0.00 0.00 0.00 38.53
March 3561.89 16-MAR-15:01 680.40 209.43 479.33 0.00 0.00 0.00 0.00 69.44 0.00
April 3705.07 26-APR-08:41 360.00 470.16 1132.48 0.00 0.00 0.00 0.00 27.61 0.00
May 4003.06 08-MAY-08:61 360.00 470.16 1132.48 0.00 0.00 0.00 0.00 32.37 0.00
June 4033.51 14-JUN-08:61 360.00 470.16 1132.48 0.00 0.00 0.00 0.00 36.22 0.00
July 4144.52 01-JUL-08:61 540.00 598.38 1632.88 0.00 0.00 0.00 0.00 29.41 0.00
August 3840.76 24-AUG-08:21 360.00 470.16 1132.48 0.00 0.00 0.00 0.00 43.53 0.00
September 3621.88 28-SEP-15:02 583.20 179.51 410.85 0.00 0.00 0.00 0.00 158.65 0.00
October 3607.25 06-OCT-15:02 583.20 179.51 410.85 0.00 0.00 0.00 0.00 132.63 0.00
November 3582.56 20-NOV-16:01 680.40 209.43 479.33 0.00 0.00 0.00 0.00 47.57 0.00
December 3519.09 25-DEC-16:01 378.00 246.84 534.64 0.00 0.00 0.00 0.00 36.01 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3268.37   360.00 179.51 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4144.52   680.40 598.38 1632.88 0.00 0.00 0.00 0.00 158.65 38.53



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 630.65 14-JAN-13:50 0.00 22.16 74.82 0.00 0.00 0.00 0.00 0.37 0.00
February 475.30 01-FEB-15:30 0.00 18.81 67.08 0.00 0.00 0.00 0.00 0.00 35.74
March 447.12 18-MAR-14:10 0.00 22.16 74.82 0.00 0.00 0.00 0.00 0.00 1.32
April 466.63 14-APR-13:40 0.00 18.81 67.08 0.00 0.00 0.00 0.00 21.85 0.00
May 376.91 09-MAY-17:20 0.00 135.00 394.73 0.00 0.00 0.00 0.00 23.75 0.00
June 473.91 28-JUN-17:15 0.00 90.00 263.15 0.00 0.00 0.00 0.00 43.73 0.00
July 448.02 21-JUL-19:10 0.00 67.16 170.27 0.00 0.00 0.00 0.00 32.98 0.00
August 536.82 27-AUG-14:00 0.00 22.16 74.82 0.00 0.00 0.00 0.00 39.15 0.00
September 612.10 28-SEP-13:40 0.00 18.81 67.08 0.00 0.00 0.00 0.00 29.13 0.00
October 632.37 18-OCT-13:50 0.00 18.81 67.08 0.00 0.00 0.00 0.00 12.54 0.00
November 659.01 20-NOV-14:30 0.00 18.81 67.08 0.00 0.00 0.00 0.00 0.88 0.00
December 624.13 25-DEC-13:40 0.00 22.16 74.82 0.00 0.00 0.00 0.00 0.00 3.23
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 376.91   0.00 18.81 67.08 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 659.01   0.00 135.00 394.73 0.00 0.00 0.00 0.00 43.73 35.74



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1195.62 27-JAN-16:01 680.40 131.67 469.67 0.00 0.00 0.00 0.00 13.74 0.00
February 1065.68 09-FEB-16:01 680.40 131.67 469.67 0.00 0.00 0.00 0.00 0.00 2.21
March 1232.00 15-MAR-18:01 970.20 418.53 885.15 0.00 0.00 0.00 0.00 11.61 0.00
April 1237.46 12-APR-15:01 680.40 131.67 469.67 0.00 0.00 0.00 0.00 30.75 0.00
May 1327.45 20-MAY-08:61 540.00 376.21 1599.98 0.00 0.00 0.00 0.00 7.86 0.00
June 1357.06 11-JUN-08:61 540.00 376.21 1599.98 0.00 0.00 0.00 0.00 6.36 0.00
July 1368.91 01-JUL-08:61 540.00 376.21 1599.98 0.00 0.00 0.00 0.00 9.62 0.00
August 1255.80 24-AUG-08:21 360.00 295.59 1109.66 0.00 0.00 0.00 0.00 13.85 0.00
September 1247.39 29-SEP-08:21 324.00 266.03 998.70 0.00 0.00 0.00 0.00 14.86 0.00
October 1236.75 06-OCT-18:01 970.20 418.53 885.15 0.00 0.00 0.00 0.00 26.63 0.00
November 1207.47 20-NOV-16:01 680.40 131.67 469.67 0.00 0.00 0.00 0.00 13.33 0.00
December 1167.91 25-DEC-16:01 378.00 155.19 523.86 0.00 0.00 0.00 0.00 10.90 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1065.68   324.00 131.67 469.67 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1368.91   970.20 418.53 1599.98 0.00 0.00 0.00 0.00 30.75 2.21



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3194.21 31-JAN-16:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 70.51 0.00
February 2973.90 09-FEB-16:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 0.00 17.73
March 3193.97 16-MAR-15:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 68.22 0.00
April 3237.75 13-APR-15:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 121.61 0.00
May 3294.33 17-MAY-08:61 360.00 470.21 1132.61 0.00 0.00 0.00 0.00 47.10 0.00
June 3290.67 14-JUN-08:61 360.00 470.21 1132.61 0.00 0.00 0.00 0.00 52.51 0.00
July 3298.57 01-JUL-08:61 540.00 598.45 1633.07 0.00 0.00 0.00 0.00 50.52 0.00
August 3258.50 27-AUG-08:61 378.00 418.92 1143.15 0.00 0.00 0.00 0.00 75.28 0.00
September 3237.92 28-SEP-15:02 583.20 179.54 410.90 0.00 0.00 0.00 0.00 157.79 0.00
October 3227.79 06-OCT-15:02 583.20 179.54 410.90 0.00 0.00 0.00 0.00 131.66 0.00
November 3200.61 20-NOV-16:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 46.76 0.00
December 3161.64 25-DEC-16:01 378.00 246.87 534.70 0.00 0.00 0.00 0.00 34.58 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2973.90   360.00 179.54 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3298.57   680.40 598.45 1633.07 0.00 0.00 0.00 0.00 157.79 17.73



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3119.26 31-JAN-16:01 680.40 209.43 479.33 0.00 0.00 0.00 0.00 72.45 0.00
February 2802.46 09-FEB-16:01 680.40 209.43 479.33 0.00 0.00 0.00 0.00 0.00 9.82
March 3147.10 16-MAR-15:01 680.40 209.43 479.33 0.00 0.00 0.00 0.00 69.15 0.00
April 3744.95 14-APR-08:41 360.00 470.16 1132.48 0.00 0.00 0.00 0.00 13.89 0.00
May 3974.01 21-MAY-08:61 378.00 418.87 1143.02 0.00 0.00 0.00 0.00 0.00 13.99
June 3772.57 14-JUN-08:61 360.00 470.16 1132.48 0.00 0.00 0.00 0.00 26.23 0.00
July 3781.11 01-JUL-08:61 540.00 598.38 1632.88 0.00 0.00 0.00 0.00 24.12 0.00
August 3762.07 24-AUG-08:21 360.00 470.16 1132.48 0.00 0.00 0.00 0.00 25.02 0.00
September 3420.92 15-SEP-08:51 360.00 470.16 1132.48 0.00 0.00 0.00 0.00 0.00 3.24
October 3562.99 17-OCT-08:51 360.00 470.16 1132.48 0.00 0.00 0.00 0.00 0.00 8.51
November 3289.83 10-NOV-09:51 324.00 423.14 1019.23 0.00 0.00 0.00 0.00 0.00 7.11
December 3085.53 25-DEC-16:01 378.00 246.84 534.64 0.00 0.00 0.00 0.00 36.58 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2802.46   324.00 209.43 479.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3974.01   680.40 598.38 1632.88 0.00 0.00 0.00 0.00 72.45 13.99



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1644.18 29-JAN-11:33 2263.36 1044.00 0.00 0.00 0.00 0.00 0.00 0.00 15.50
February 1522.85 01-FEB-11:35 1005.94 580.00 0.00 0.00 0.00 0.00 0.00 0.00 119.96
March 1722.49 18-MAR-17:40 3017.81 1392.00 0.00 0.00 0.00 0.00 0.00 44.09 0.00
April 2050.82 15-APR-10:33 2263.36 870.00 0.00 0.00 0.00 0.00 0.00 57.64 0.00
May 2085.28 18-MAY-18:10 10562.33 5568.01 0.00 0.00 0.00 0.00 0.00 138.63 0.00
June 3391.19 28-JUN-18:25 3520.78 1856.00 0.00 0.00 0.00 0.00 0.00 209.25 0.00
July 3017.71 20-JUL-18:30 1760.39 928.00 0.00 0.00 0.00 0.00 0.00 179.50 0.00
August 2903.19 15-AUG-18:15 3520.78 1856.00 0.00 0.00 0.00 0.00 0.00 175.10 0.00
September 2772.02 08-SEP-18:15 3520.78 1856.00 0.00 0.00 0.00 0.00 0.00 153.52 0.00
October 2478.28 05-OCT-18:03 10562.33 5568.01 0.00 0.00 0.00 0.00 0.00 97.50 0.00
November 1757.72 01-NOV-18:10 12322.72 6496.01 0.00 0.00 0.00 0.00 0.00 9.01 0.00
December 1566.81 25-DEC-11:33 2263.36 1044.00 0.00 0.00 0.00 0.00 0.00 2.61 0.00
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1522.85   1005.94 580.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3391.19   12322.72 6496.01 0.00 0.00 0.00 0.00 0.00 209.25 119.96



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3862.11 31-JAN-16:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 69.76 0.00
February 3553.33 28-FEB-16:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 0.00 40.76
March 3844.30 16-MAR-15:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 67.99 0.00
April 3916.12 14-APR-18:01 970.20 665.78 903.46 0.00 0.00 0.00 0.00 115.00 0.00
May 3893.49 03-MAY-15:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 112.91 0.00
June 3933.48 27-JUN-18:02 831.60 570.67 774.39 0.00 0.00 0.00 0.00 179.11 0.00
July 3907.74 05-JUL-18:02 831.60 570.67 774.39 0.00 0.00 0.00 0.00 160.50 0.00
August 3924.49 26-AUG-15:02 324.00 211.60 458.31 0.00 0.00 0.00 0.00 191.79 0.00
September 3875.19 18-SEP-15:02 583.20 179.54 410.90 0.00 0.00 0.00 0.00 143.07 0.00
October 3903.46 15-OCT-15:01 378.00 246.87 534.70 0.00 0.00 0.00 0.00 90.05 0.00
November 3897.32 20-NOV-16:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 45.19 0.00
December 3834.17 25-DEC-16:01 378.00 246.87 534.70 0.00 0.00 0.00 0.00 33.47 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3553.33   324.00 179.54 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3933.48   970.20 665.78 903.46 0.00 0.00 0.00 0.00 191.79 40.76



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3763.24 31-JAN-16:01 680.40 209.43 479.33 0.00 0.00 0.00 0.00 71.81 0.00
February 3458.42 28-FEB-16:01 680.40 209.43 479.33 0.00 0.00 0.00 0.00 0.00 38.70
March 3779.23 16-MAR-15:01 680.40 209.43 479.33 0.00 0.00 0.00 0.00 69.04 0.00
April 3879.20 26-APR-08:41 360.00 470.16 1132.48 0.00 0.00 0.00 0.00 29.27 0.00
May 4189.12 08-MAY-08:61 360.00 470.16 1132.48 0.00 0.00 0.00 0.00 34.29 0.00
June 4217.64 14-JUN-08:61 360.00 470.16 1132.48 0.00 0.00 0.00 0.00 38.29 0.00
July 4330.02 01-JUL-08:61 540.00 598.38 1632.88 0.00 0.00 0.00 0.00 31.72 0.00
August 4004.16 24-AUG-08:21 360.00 470.16 1132.48 0.00 0.00 0.00 0.00 46.03 0.00
September 3848.46 28-SEP-15:02 583.20 179.51 410.85 0.00 0.00 0.00 0.00 158.12 0.00
October 3825.17 06-OCT-15:02 583.20 179.51 410.85 0.00 0.00 0.00 0.00 132.31 0.00
November 3797.76 20-NOV-16:01 680.40 209.43 479.33 0.00 0.00 0.00 0.00 47.26 0.00
December 3722.45 25-DEC-16:01 378.00 246.84 534.64 0.00 0.00 0.00 0.00 35.93 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3458.42   360.00 179.51 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4330.02   680.40 598.38 1632.88 0.00 0.00 0.00 0.00 158.12 38.70



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1975.29 14-JAN-16:01 378.00 155.19 523.86 0.00 0.00 0.00 0.00 21.05 0.00
February 1829.62 09-FEB-16:01 680.40 131.67 469.67 0.00 0.00 0.00 0.00 0.00 10.80
March 1952.31 16-MAR-15:01 680.40 131.67 469.67 0.00 0.00 0.00 0.00 33.47 0.00
April 1963.01 13-APR-15:01 680.40 131.67 469.67 0.00 0.00 0.00 0.00 61.28 0.00
May 1940.98 03-MAY-15:01 680.40 131.67 469.67 0.00 0.00 0.00 0.00 57.54 0.00
June 1943.05 27-JUN-15:02 583.20 112.86 402.58 0.00 0.00 0.00 0.00 98.05 0.00
July 1941.14 01-JUL-08:61 540.00 376.21 1599.98 0.00 0.00 0.00 0.00 26.64 0.00
August 1961.25 26-AUG-15:02 324.00 133.02 449.03 0.00 0.00 0.00 0.00 97.76 0.00
September 1960.25 18-SEP-15:02 583.20 112.86 402.58 0.00 0.00 0.00 0.00 72.13 0.00
October 1982.41 18-OCT-15:01 680.40 131.67 469.67 0.00 0.00 0.00 0.00 39.13 0.00
November 1981.74 20-NOV-16:01 680.40 131.67 469.67 0.00 0.00 0.00 0.00 21.70 0.00
December 1964.25 25-DEC-16:01 378.00 155.19 523.86 0.00 0.00 0.00 0.00 15.28 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1829.62   324.00 112.86 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1982.41   680.40 376.21 1599.98 0.00 0.00 0.00 0.00 98.05 10.80



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 18854.98 06-JAN-22:10 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 179.37
February 18402.59 21-FEB-23:00 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 283.69
March 20556.38 17-MAR-21:53 188921.38 11605.12 47235.32 0.00 0.00 0.00 0.00 0.00 99.44
April 22797.28 14-APR-21:10 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 121.49 0.00
May 23078.06 09-MAY-21:10 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 126.10 0.00
June 24852.60 28-JUN-21:20 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 267.65 0.00
July 24474.13 21-JUL-21:20 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 251.95 0.00
August 23969.11 15-AUG-21:10 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 226.09 0.00
September 23766.85 07-SEP-21:10 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 229.04 0.00
October 22885.91 03-OCT-21:10 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 144.08 0.00
November 20407.82 02-NOV-21:53 161932.61 9947.24 40487.42 0.00 0.00 0.00 0.00 0.00 112.95
December 18407.67 26-DEC-22:30 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 269.83
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 18402.59   26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24852.60   188921.38 11605.12 47235.32 0.00 0.00 0.00 0.00 267.65 283.69



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 20588.81 06-JAN-22:10 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 179.38
February 20162.73 21-FEB-23:00 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 283.70
March 22052.06 17-MAR-21:10 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 73.72
April 24004.85 14-APR-21:10 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 121.48 0.00
May 24270.79 09-MAY-21:20 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 121.65 0.00
June 26035.81 28-JUN-21:20 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 267.64 0.00
July 25653.76 21-JUL-21:20 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 251.93 0.00
August 25150.23 10-AUG-21:20 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 225.81 0.00
September 24913.60 07-SEP-21:10 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 228.95 0.00
October 24051.61 03-OCT-21:10 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 144.08 0.00
November 21814.74 02-NOV-21:53 161932.61 9947.24 40487.42 0.00 0.00 0.00 0.00 0.00 112.95
December 20036.07 26-DEC-22:10 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 260.27
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 20036.07   26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 26035.81   161932.61 9947.24 40487.42 0.00 0.00 0.00 0.00 267.64 283.70



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 26831.10 29-JAN-11:50 800.57 327.25 14604.56 18744.03 0.00 0.00 0.00 0.00 59.94
February 26689.33 18-FEB-11:33 2401.70 818.12 43813.67 56232.08 0.00 0.00 0.00 0.00 117.53
March 27769.42 18-MAR-10:45 1601.14 545.42 29209.11 37488.05 0.00 0.00 0.00 0.55 0.00
April 29280.80 30-APR-10:33 2401.70 981.75 43813.67 56232.08 0.00 0.00 0.00 140.86 0.00
May 29521.36 20-MAY-10:50 800.57 272.71 14604.56 18744.03 0.00 0.00 0.00 179.93 0.00
June 30410.76 18-JUN-10:50 800.57 327.25 14604.56 18744.03 0.00 0.00 0.00 269.19 0.00
July 30418.88 22-JUL-10:37 2401.70 818.12 43813.67 56232.08 0.00 0.00 0.00 270.64 0.00
August 30428.27 13-AUG-10:37 2401.70 981.75 43813.67 56232.08 0.00 0.00 0.00 225.59 0.00
September 30158.27 09-SEP-10:50 800.57 272.71 14604.56 18744.03 0.00 0.00 0.00 225.53 0.00
October 29336.59 02-OCT-10:45 1067.42 545.42 29209.11 37488.05 0.00 0.00 0.00 202.92 0.00
November 27656.71 01-NOV-10:45 1067.42 545.42 29209.11 37488.05 0.00 0.00 0.00 13.92 0.00
December 26683.87 25-DEC-11:50 800.57 327.25 14604.56 18744.03 0.00 0.00 0.00 0.00 34.87
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 26683.87   800.57 272.71 14604.56 18744.03 0.00 0.00 0.00 0.00 0.00
Maximum of Months 30428.27   2401.70 981.75 43813.67 56232.08 0.00 0.00 0.00 270.64 117.53



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3801.14 31-JAN-17:20 1330.80 306.92 0.00 0.00 0.00 0.00 0.00 107.65 0.00
February 3531.89 26-FEB-11:33 2395.44 1104.91 0.00 0.00 0.00 0.00 0.00 0.00 164.66
March 4234.65 18-MAR-17:12 6387.84 2946.44 0.00 0.00 0.00 0.00 0.00 75.28 0.00
April 6230.78 14-APR-15:03 7984.80 1841.52 0.00 0.00 0.00 0.00 0.00 249.21 0.00
May 5935.19 09-MAY-15:03 7984.80 1841.52 0.00 0.00 0.00 0.00 0.00 249.48 0.00
June 7825.09 28-JUN-18:04 9315.60 4910.73 0.00 0.00 0.00 0.00 0.00 376.09 0.00
July 7147.31 20-JUL-15:03 7984.80 1841.52 0.00 0.00 0.00 0.00 0.00 356.50 0.00
August 7371.01 11-AUG-15:30 1330.80 306.92 0.00 0.00 0.00 0.00 0.00 316.37 0.00
September 7397.26 07-SEP-15:03 7984.80 1841.52 0.00 0.00 0.00 0.00 0.00 301.20 0.00
October 6879.81 02-OCT-13:20 532.32 306.92 0.00 0.00 0.00 0.00 0.00 235.26 0.00
November 4214.22 01-NOV-17:12 5323.20 2946.44 0.00 0.00 0.00 0.00 0.00 43.62 0.00
December 3668.99 25-DEC-11:50 798.48 368.30 0.00 0.00 0.00 0.00 0.00 7.72 0.00
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 3531.89   532.32 306.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7825.09   9315.60 4910.73 0.00 0.00 0.00 0.00 0.00 376.09 164.66



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.428317E+12 295017.09 31-JAN-19:10 0.315597E+12 259039.04 01-JAN-19:10
February 0.345825E+12 266717.32 09-FEB-20:19 0.301027E+12 268608.24 04-FEB-18:00
March 0.420581E+12 321304.74 20-MAR-18:40 0.290708E+12 247250.53 07-MAR-07:10
April 0.513770E+12 377703.09 14-APR-19:19 0.218765E+12 175759.91 21-APR-06:10
May 0.574343E+12 384854.75 09-MAY-19:10 0.214557E+12 150705.65 01-MAY-17:40
June 0.638417E+12 437675.20 29-JUN-19:30 0.196993E+12 135455.87 01-JUN-17:10
July 0.665410E+12 437604.16 21-JUL-19:49 0.197979E+12 126227.72 01-JUL-17:49
August 0.658138E+12 421121.90 15-AUG-19:10 0.199163E+12 128402.69 31-AUG-17:19
September 0.612502E+12 426493.46 08-SEP-19:10 0.197623E+12 136815.50 30-SEP-17:40
October 0.508963E+12 392522.28 03-OCT-19:19 0.238519E+12 212672.71 25-OCT-07:40
November 0.421367E+12 324708.65 01-NOV-18:10 0.276334E+12 276512.70 23-NOV-20:19
December 0.405493E+12 278904.83 26-DEC-20:10 0.353601E+12 297676.92 07-DEC-20:00
             
Annual Sum or Average 0.619313E+13     0.300086E+13    
Minimum of Months 0.345825E+12 266717.32   0.196993E+12 126227.72  
Maximum of Months 0.665410E+12 437675.20   0.353601E+12 297676.92  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.466537E+11 0.170908E+11 0.146779E+12 0.544793E+11 0.441908E+11 0.108461E+11 0.00 0.581470E+11 0.00 0.00 0.480544E+10 0.416263E+11 0.00
February 0.420886E+11 0.146606E+11 0.132565E+12 0.492072E+11 0.370657E+11 0.841864E+10 0.00 0.186456E+11 0.00 0.00 0.228502E+10 0.375255E+11 0.00
March 0.462569E+11 0.150734E+11 0.146789E+12 0.544810E+11 0.426516E+11 0.105714E+11 0.00 0.544503E+11 0.00 0.00 0.520993E+10 0.413860E+11 0.00
April 0.444708E+11 0.134023E+11 0.142011E+12 0.527213E+11 0.496601E+11 0.114725E+11 0.00 0.144547E+12 0.00 0.00 0.128858E+11 0.390214E+11 0.00
May 0.457578E+11 0.128297E+11 0.146789E+12 0.544797E+11 0.543392E+11 0.119625E+11 0.00 0.187604E+12 0.00 0.00 0.168455E+11 0.400325E+11 0.00
June 0.440333E+11 0.119908E+11 0.142058E+12 0.527229E+11 0.612521E+11 0.121843E+11 0.00 0.250710E+12 0.00 0.00 0.219891E+11 0.378651E+11 0.00
July 0.455886E+11 0.125501E+11 0.146742E+12 0.544777E+11 0.612229E+11 0.126912E+11 0.00 0.265582E+12 0.00 0.00 0.240847E+11 0.387218E+11 0.00
August 0.460026E+11 0.133890E+11 0.146800E+12 0.544809E+11 0.614739E+11 0.126499E+11 0.00 0.258192E+12 0.00 0.00 0.226535E+11 0.387255E+11 0.00
September 0.446490E+11 0.140614E+11 0.142022E+12 0.527215E+11 0.588258E+11 0.122221E+11 0.00 0.227341E+12 0.00 0.00 0.193894E+11 0.376217E+11 0.00
October 0.464538E+11 0.157658E+11 0.146768E+12 0.544791E+11 0.524520E+11 0.118008E+11 0.00 0.127568E+12 0.00 0.00 0.952265E+10 0.404341E+11 0.00
November 0.451200E+11 0.162918E+11 0.142074E+12 0.527224E+11 0.447494E+11 0.105397E+11 0.00 0.617852E+11 0.00 0.00 0.446377E+10 0.400344E+11 0.00
December 0.466611E+11 0.174170E+11 0.146742E+12 0.544784E+11 0.434643E+11 0.958493E+10 0.00 0.345104E+11 0.00 0.00 0.616137E+10 0.427935E+11 0.00
                           
Annual Sum or Average 0.543736E+12 0.174523E+12 0.172814E+13 0.641451E+12 0.611348E+12 0.134944E+12 0.00 0.168908E+13 0.00 0.00 0.150296E+12 0.475788E+12 0.00
Minimum of Months 0.420886E+11 0.119908E+11 0.132565E+12 0.492072E+11 0.370657E+11 0.841864E+10 0.00 0.186456E+11 0.00 0.00 0.228502E+10 0.375255E+11 0.00
Maximum of Months 0.466611E+11 0.174170E+11 0.146800E+12 0.544810E+11 0.614739E+11 0.126912E+11 0.00 0.265582E+12 0.00 0.00 0.240847E+11 0.427935E+11 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.732478E+11 0.00 0.904307E+11 0.00 0.00
February 0.137204E+12 0.00 0.835989E+11 0.00 0.802243E+11 0.00 0.00
March 0.152024E+12 0.00 0.547436E+11 0.00 0.839404E+11 0.00 0.00
April 0.146956E+12 0.00 0.266919E+10 0.00 0.691406E+11 0.00 0.00
May 0.151978E+12 0.00 0.143110E+09 0.00 0.624352E+11 0.00 0.00
June 0.147114E+12 0.00 23261178.36 0.00 0.498559E+11 0.00 0.00
July 0.151820E+12 0.00 39399393.08 0.00 0.461191E+11 0.00 0.00
August 0.152039E+12 0.00 56688803.15 0.00 0.470673E+11 0.00 0.00
September 0.146971E+12 0.00 56009579.40 0.00 0.505958E+11 0.00 0.00
October 0.151903E+12 0.00 0.182430E+11 0.00 0.683725E+11 0.00 0.00
November 0.147091E+12 0.00 0.512764E+11 0.00 0.779667E+11 0.00 0.00
December 0.151820E+12 0.00 0.108549E+12 0.00 0.932316E+11 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.392646E+12 0.00 0.819380E+12 0.00 0.00
Minimum of Months 0.137204E+12 0.00 23261178.36 0.00 0.461191E+11 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.108549E+12 0.00 0.932316E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 45424.10 02-JAN-20:10 11096.45 01-JAN-00:10 88863.15 02-JAN-07:10 39153.57 02-JAN-07:19 31806.27 31-JAN-22:10 4779.11 01-JAN-09:20 0.00 01-JAN-00:10
February 45424.10 01-FEB-20:10 11096.45 01-FEB-00:10 88863.15 01-FEB-07:10 39153.57 01-FEB-07:19 26614.50 21-FEB-21:19 4753.45 08-FEB-07:10 0.00 01-FEB-00:10
March 45424.10 01-MAR-20:10 11096.45 01-MAR-00:10 88863.15 01-MAR-07:10 39153.57 13-MAR-06:19 32442.47 16-MAR-21:00 5187.30 17-MAR-18:10 0.00 01-MAR-00:10
April 45424.10 03-APR-19:10 11096.45 01-APR-00:10 88863.15 03-APR-06:10 39153.57 03-APR-06:19 39708.73 25-APR-21:10 5588.24 25-APR-19:10 0.00 01-APR-00:10
May 45424.10 01-MAY-19:10 11096.45 01-MAY-00:10 88863.15 01-MAY-06:10 39153.18 26-MAY-06:19 40743.42 09-MAY-21:10 5197.00 29-MAY-20:49 0.00 01-MAY-00:10
June 45424.10 01-JUN-19:19 11096.45 01-JUN-00:10 88863.15 01-JUN-06:10 39152.12 27-JUN-06:19 47147.45 30-JUN-20:10 6743.74 28-JUN-19:10 0.00 01-JUN-00:10
July 45424.10 03-JUL-19:30 11096.45 01-JUL-00:10 88863.15 03-JUL-06:10 39153.04 17-JUL-06:19 47131.68 21-JUL-21:10 5995.02 07-JUL-20:19 0.00 01-JUL-00:10
August 45424.10 01-AUG-19:19 11096.45 01-AUG-00:10 88863.15 01-AUG-06:10 39153.50 30-AUG-06:19 48033.53 15-AUG-21:10 6179.45 27-AUG-18:10 0.00 01-AUG-00:10
September 45424.10 01-SEP-19:10 11096.45 01-SEP-00:10 88863.15 01-SEP-06:10 39153.57 14-SEP-06:19 50202.41 07-SEP-21:10 6127.29 18-SEP-18:19 0.00 01-SEP-00:10
October 45424.10 02-OCT-19:10 11096.45 01-OCT-00:10 88863.15 02-OCT-06:10 39153.57 02-OCT-06:19 48482.58 06-OCT-21:10 5686.48 05-OCT-20:19 0.00 01-OCT-00:10
November 45424.10 01-NOV-19:10 11096.45 01-NOV-00:10 88863.15 01-NOV-06:10 39153.57 01-NOV-06:19 36513.54 01-NOV-21:00 5320.76 01-NOV-18:10 0.00 01-NOV-00:10
December 45424.10 01-DEC-20:10 11096.45 01-DEC-00:10 88863.15 01-DEC-07:10 39153.57 01-DEC-07:19 31360.76 26-DEC-22:10 4786.31 07-DEC-09:09 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 45424.10   11096.45   88863.15   39152.12   26614.50   4753.45   0.00  
Maximum of Months 45424.10   11096.45   88863.15   39153.57   50202.41   6743.74   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 95079.96 31-JAN-16:10 0.00 0.00 9938.94 01-JAN-00:20 42597.28 02-JAN-19:00 0.00
February 59178.97 22-FEB-16:10 0.00 0.00 9938.94 01-FEB-07:10 42835.31 17-FEB-19:10 0.00
March 91988.17 16-MAR-15:09 0.00 0.00 9938.94 09-MAR-13:50 43955.68 30-MAR-20:49 0.00
April 127895.76 14-APR-15:09 0.00 0.00 9938.94 01-APR-08:50 44294.73 26-APR-20:40 0.00
May 140866.06 31-MAY-18:10 0.00 0.00 9938.94 01-MAY-09:39 44167.62 30-MAY-20:49 0.00
June 188698.43 28-JUN-18:10 0.00 0.00 9938.94 01-JUN-00:10 43288.09 30-JUN-20:49 0.00
July 168834.12 20-JUL-18:10 0.00 0.00 9938.94 01-JUL-00:10 42805.76 25-JUL-20:30 0.00
August 169741.69 25-AUG-15:09 0.00 0.00 9938.94 01-AUG-00:10 42841.05 01-AUG-20:30 0.00
September 157889.02 08-SEP-18:30 0.00 0.00 9938.94 01-SEP-00:10 42995.91 01-SEP-20:49 0.00
October 135230.43 02-OCT-18:10 0.00 0.00 9938.94 01-OCT-00:10 44572.48 06-OCT-20:49 0.00
November 101064.04 01-NOV-15:09 0.00 0.00 9938.94 01-NOV-12:09 44847.95 01-NOV-18:40 0.00
December 80481.00 25-DEC-16:10 0.00 0.00 9938.94 02-DEC-13:09 43597.71 04-DEC-19:40 0.00
                   
Annual Sum or Average     0.00 0.00         0.00
Minimum of Months 59178.97   0.00 0.00 9938.94   42597.28   0.00
Maximum of Months 188698.43   0.00 0.00 9938.94   44847.95   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 295017.09 31-JAN-19:10 40391.24 78653.57 11096.45 31357.01 26311.84 4598.41 0.00 74395.96 0.00
February 266717.32 09-FEB-20:19 45424.10 87982.85 11096.45 31573.56 21866.78 4273.03 0.00 22016.94 0.00
March 321304.74 20-MAR-18:40 40391.24 78653.57 11096.45 31363.95 25171.98 4636.46 0.00 75723.66 0.00
April 377703.09 14-APR-19:19 45424.10 87982.85 11096.45 31573.56 34520.56 4732.56 0.00 110835.27 0.00
May 384854.75 09-MAY-19:10 45424.10 87982.85 11096.45 31569.36 34123.27 4756.15 0.00 118348.62 0.00
June 437675.20 29-JUN-19:30 45424.10 87982.85 11096.45 31572.57 40833.89 6314.03 0.00 163272.77 0.00
July 437604.16 21-JUL-19:49 45424.10 87982.85 11096.45 31573.56 41106.15 5426.44 0.00 164665.88 0.00
August 421121.90 15-AUG-19:10 45424.10 87982.85 11096.45 31569.36 39973.00 5352.13 0.00 149035.68 0.00
September 426493.46 08-SEP-19:10 45424.10 87982.85 11096.45 31569.36 41057.74 5386.87 0.00 153363.38 0.00
October 392522.28 03-OCT-19:19 45424.10 87982.85 11096.45 31573.56 39364.60 5081.94 0.00 120163.60 0.00
November 324708.65 01-NOV-18:10 40391.24 78653.57 11096.45 31357.01 29843.55 5320.76 0.00 84835.94 0.00
December 278904.83 26-DEC-20:10 45424.10 87982.85 11096.45 31569.36 26270.23 4305.86 0.00 28666.38 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 266717.32   40391.24 78653.57 11096.45 31357.01 21866.78 4273.03 0.00 22016.94 0.00
Maximum of Months 437675.20   45424.10 87982.85 11096.45 31573.56 41106.15 6314.03 0.00 164665.88 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 186036.48 01-JAN-00:10 0.00 78547.73 23-JAN-20:40 0.00
February 104248.32 01-FEB-18:10 0.00 171872.65 28-FEB-06:49 0.00 77383.69 01-FEB-23:30 0.00
March 104248.32 01-MAR-18:10 0.00 168763.10 07-MAR-07:10 0.00 72751.09 01-MAR-19:10 0.00
April 104248.32 01-APR-17:10 0.00 97272.48 21-APR-06:10 0.00 57583.74 01-APR-17:10 0.00
May 104248.32 01-MAY-17:10 0.00 7435.45 01-MAY-03:00 0.00 46490.34 01-MAY-19:49 0.00
June 104248.32 01-JUN-17:10 0.00 4481.22 20-JUN-08:09 0.00 31230.08 01-JUN-20:30 0.00
July 104248.32 01-JUL-17:10 0.00 4395.14 03-JUL-08:09 0.00 21979.44 01-JUL-20:19 0.00
August 104248.32 01-AUG-17:10 0.00 5284.24 29-AUG-08:09 0.00 24154.42 31-AUG-22:40 0.00
September 104248.32 01-SEP-17:10 0.00 3462.41 03-SEP-18:10 0.00 32567.36 30-SEP-20:00 0.00
October 104248.32 02-OCT-17:10 0.00 132603.78 30-OCT-06:10 0.00 53613.02 31-OCT-20:00 0.00
November 104248.32 01-NOV-17:10 0.00 169177.15 05-NOV-04:10 0.00 68736.95 30-NOV-22:30 0.00
December 104248.32 01-DEC-18:10 0.00 170194.04 24-DEC-03:00 0.00 83451.25 31-DEC-20:00 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 3462.41   0.00 21979.44   0.00
Maximum of Months 104248.32   0.00 186036.48   0.00 83451.25   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 21.86 0.33 21.86
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 7.17 21.91 7.17 21.91
July 0.00 0.00 0.00 0.00 1.50 21.79 1.50 21.79
August 0.00 0.00 0.00 0.00 5.17 21.83 5.17 21.83
September 0.00 0.00 0.00 0.00 1.67 21.81 1.67 21.81
October 0.00 0.00 0.00 0.00 0.83 21.84 0.83 21.84
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   16.67 21.86 16.67 21.86
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 7.17 21.91 7.17 21.91



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 22.03 0.17 22.03
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 9.17 21.94 9.17 21.94
July 0.00 0.00 0.00 0.00 1.67 21.79 1.67 21.79
August 0.00 0.00 0.00 0.00 3.33 21.79 3.33 21.79
September 0.00 0.00 0.00 0.00 0.83 21.70 0.83 21.70
October 0.00 0.00 0.00 0.00 0.17 21.74 0.17 21.74
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   15.33 21.88 15.33 21.88
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 9.17 22.03 9.17 22.03



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 21.69 0.33 21.69
May 0.00 0.00 0.00 0.00 0.50 21.74 0.50 21.74
June 0.00 0.00 0.00 0.00 5.50 21.83 5.50 21.83
July 0.00 0.00 0.00 0.00 2.17 21.74 2.17 21.74
August 0.00 0.00 0.00 0.00 1.83 21.78 1.83 21.78
September 0.00 0.00 0.00 0.00 1.50 21.77 1.50 21.77
October 0.00 0.00 0.00 0.00 0.17 21.75 0.17 21.75
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   12.00 21.79 12.00 21.79
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 5.50 21.83 5.50 21.83



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.74 0.17 21.74
May 0.00 0.00 0.00 0.00 0.33 21.88 0.33 21.88
June 0.00 0.00 0.00 0.00 6.33 21.86 6.33 21.86
July 0.00 0.00 0.00 0.00 1.67 21.75 1.67 21.75
August 0.00 0.00 0.00 0.00 2.33 21.79 2.33 21.79
September 0.00 0.00 0.00 0.00 1.50 21.76 1.50 21.76
October 0.00 0.00 0.00 0.00 0.50 21.79 0.50 21.79
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   12.83 21.82 12.83 21.82
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 6.33 21.88 6.33 21.88



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.33 21.85 0.33 21.85
April 0.00 0.00 0.00 0.00 4.83 22.05 4.83 22.05
May 0.00 0.00 0.00 0.00 5.17 22.15 5.17 22.15
June 0.00 0.00 0.00 0.00 11.50 21.98 11.50 21.98
July 0.00 0.00 0.00 0.00 2.67 21.89 2.67 21.89
August 0.00 0.00 0.00 0.00 3.50 21.93 3.50 21.93
September 0.00 0.00 0.00 0.00 3.33 22.06 3.33 22.06
October 0.00 0.00 0.00 0.00 2.33 22.04 2.33 22.04
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   33.67 22.01 33.67 22.01
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 11.50 22.15 11.50 22.15



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 21.95 0.33 21.95
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 11.17 21.93 11.17 21.93
July 0.00 0.00 0.00 0.00 1.50 21.84 1.50 21.84
August 0.00 0.00 0.00 0.00 7.17 21.87 7.17 21.87
September 0.00 0.00 0.00 0.00 1.83 21.86 1.83 21.86
October 0.00 0.00 0.00 0.00 1.17 21.84 1.17 21.84
November 0.00 0.00 0.00 0.00 0.17 21.70 0.17 21.70
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   23.33 21.90 23.33 21.90
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 11.17 21.95 11.17 21.95



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 21.94 0.33 21.94
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 16.17 21.92 16.17 21.92
July 0.00 0.00 0.00 0.00 2.00 21.80 2.00 21.80
August 0.00 0.00 0.00 0.00 5.00 21.81 5.00 21.81
September 0.00 0.00 0.00 0.00 1.00 21.74 1.00 21.74
October 0.00 0.00 0.00 0.00 0.33 21.70 0.33 21.70
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   24.83 21.88 24.83 21.88
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 16.17 21.94 16.17 21.94



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 2.17 21.96 2.17 21.96
February 0.00 0.00 0.00 0.00 0.17 21.76 0.17 21.76
March 0.00 0.00 0.00 0.00 0.50 21.78 0.50 21.78
April 0.00 0.00 0.00 0.00 1.00 21.90 1.00 21.90
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 4.17 21.79 4.17 21.79
July 0.00 0.00 0.00 0.00 1.83 21.78 1.83 21.78
August 0.00 0.00 0.00 0.00 2.67 21.86 2.67 21.86
September 0.00 0.00 0.00 0.00 6.00 21.93 6.00 21.93
October 0.00 0.00 0.00 0.00 4.83 22.00 4.83 22.00
November 0.00 0.00 0.00 0.00 2.00 21.86 2.00 21.86
December 0.00 0.00 0.00 0.00 0.67 21.70 0.67 21.70
                 
Annual Sum or Average 0.00   0.00   26.00 21.89 26.00 21.89
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 6.00 22.00 6.00 22.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 698.83 23.58 4.17 23.58 0.00 23.58
February 672.00 22.72 0.00 22.72 0.00 22.72
March 744.00 22.05 0.00 22.05 0.00 22.05
April 720.00 22.42 0.00 22.42 0.00 22.42
May 744.00 22.10 0.00 22.10 0.00 22.10
June 720.00 22.42 0.50 22.42 0.50 22.42
July 416.17 23.60 357.33 23.74 214.67 23.78
August 300.00 23.95 509.33 23.94 224.17 23.95
September 144.17 24.00 534.83 23.99 138.67 23.99
October 340.17 23.99 141.00 23.99 26.67 23.99
November 421.83 23.99 144.00 23.99 37.33 23.99
December 712.50 23.96 5.17 23.96 0.00 23.96
             
Annual Sum or Average 6633.67 23.02 1696.33 23.21 642.00 23.26
Minimum of Months 144.17 22.05 0.00 22.05 0.00 22.05
Maximum of Months 744.00 24.00 534.83 23.99 224.17 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 545.17 22.01 89.67 22.29 0.00 22.29
February 606.50 21.46 17.50 21.53 0.00 21.53
March 677.83 21.68 37.50 21.72 18.83 21.71
April 401.83 22.61 78.67 22.84 0.00 22.84
May 379.67 22.85 11.67 22.88 0.00 22.88
June 117.50 23.24 397.00 23.81 0.00 23.81
July 197.00 23.51 629.33 23.76 152.67 23.73
August 200.33 23.41 654.17 23.71 163.17 23.67
September 191.50 23.25 599.67 23.67 134.67 23.64
October 394.67 22.34 230.67 22.92 21.50 22.94
November 527.83 21.93 121.50 22.17 32.50 22.13
December 609.83 21.65 99.33 21.74 56.83 21.69
             
Annual Sum or Average 4849.67 22.18 2966.67 22.78 580.17 22.80
Minimum of Months 117.50 21.46 11.67 21.53 0.00 21.53
Maximum of Months 677.83 23.51 654.17 23.81 163.17 23.81



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 699.67 23.03 0.00 23.03 0.00 23.03
February 657.50 22.45 0.67 22.45 0.67 22.45
March 697.67 22.67 0.00 22.67 0.00 22.67
April 465.67 23.47 11.83 23.48 0.00 23.48
May 442.17 23.61 6.50 23.61 0.00 23.61
June 110.00 23.64 199.00 23.86 0.00 23.86
July 256.83 23.95 556.50 23.93 201.67 23.94
August 234.33 23.94 604.00 23.92 222.50 23.93
September 182.33 23.93 558.33 23.91 175.50 23.92
October 475.67 23.31 143.83 23.45 34.50 23.48
November 619.33 23.03 79.67 23.07 49.33 23.07
December 739.33 22.65 0.00 22.65 0.00 22.65
             
Annual Sum or Average 5580.50 23.09 2160.33 23.32 684.17 23.36
Minimum of Months 110.00 22.45 0.00 22.45 0.00 22.45
Maximum of Months 739.33 23.95 604.00 23.93 222.50 23.94



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.64 13.33 21.63 13.33 21.61
February 672.00 21.24 0.00 21.24 0.00 21.24
March 744.00 21.61 35.00 21.58 35.00 21.56
April 711.17 23.00 0.00 23.00 0.00 23.00
May 715.17 23.57 0.00 23.57 0.00 23.57
June 222.33 23.95 52.50 23.96 0.00 23.96
July 106.33 23.98 523.17 23.97 19.83 23.97
August 73.00 23.82 547.50 23.93 4.50 23.93
September 125.50 23.71 398.17 23.85 32.50 23.85
October 605.50 22.58 86.17 22.75 2.67 22.75
November 720.00 21.85 11.67 21.84 11.67 21.83
December 744.00 21.28 140.50 21.24 140.50 21.21
             
Annual Sum or Average 6183.00 22.24 1808.00 22.55 260.00 22.52
Minimum of Months 73.00 21.24 0.00 21.24 0.00 21.21
Maximum of Months 744.00 23.98 547.50 23.97 140.50 23.97



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.56 12.50 21.55 12.50 21.54
February 672.00 21.16 0.00 21.16 0.00 21.16
March 744.00 21.51 33.67 21.49 33.67 21.47
April 718.50 22.88 0.00 22.88 0.00 22.88
May 739.00 23.47 0.00 23.47 0.00 23.47
June 269.83 23.92 43.50 23.93 0.00 23.93
July 142.83 23.93 511.17 23.95 43.50 23.94
August 122.83 23.74 518.83 23.89 30.50 23.88
September 192.83 23.64 353.17 23.78 54.33 23.77
October 624.67 22.49 74.17 22.64 4.67 22.65
November 720.00 21.75 22.67 21.75 22.67 21.74
December 744.00 21.22 168.50 21.18 168.50 21.15
             
Annual Sum or Average 6434.50 22.21 1738.17 22.49 370.33 22.47
Minimum of Months 122.83 21.16 0.00 21.16 0.00 21.15
Maximum of Months 744.00 23.93 518.83 23.95 168.50 23.94



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 244.17 23.20 606.17 23.41 174.67 23.51
February 253.67 23.42 578.17 23.38 203.33 23.50
March 269.83 23.41 614.50 23.43 213.33 23.54
April 244.83 23.69 625.33 23.53 215.83 23.62
May 251.17 23.86 655.67 23.58 236.83 23.67
June 310.50 23.97 686.83 23.56 310.50 23.66
July 367.83 23.91 732.33 23.52 367.33 23.61
August 369.00 23.92 734.83 23.50 369.00 23.60
September 346.67 23.94 711.50 23.50 346.67 23.61
October 275.17 23.62 663.67 23.47 238.83 23.58
November 250.50 23.44 602.00 23.45 201.00 23.55
December 230.17 22.94 533.17 23.37 143.00 23.47
             
Annual Sum or Average 3413.50 23.65 7744.17 23.48 3020.33 23.58
Minimum of Months 230.17 22.94 533.17 23.37 143.00 23.47
Maximum of Months 369.00 23.97 734.83 23.58 369.00 23.67



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 232.50 23.04 252.17 23.51 10.83 23.50
February 416.00 22.53 156.00 22.86 40.50 22.89
March 447.67 22.64 135.33 22.93 5.50 22.94
April 156.83 23.05 245.33 23.61 0.00 23.61
May 155.00 23.06 225.33 23.61 0.00 23.61
June 28.67 23.32 534.67 23.93 9.33 23.93
July 308.17 23.90 676.00 23.88 300.17 23.89
August 343.17 23.87 710.00 23.87 339.67 23.88
September 271.50 23.88 702.00 23.90 271.50 23.89
October 201.17 23.29 401.50 23.73 56.33 23.74
November 272.17 23.03 329.00 23.40 78.33 23.35
December 459.00 22.91 121.33 23.14 0.00 23.14
             
Annual Sum or Average 3291.83 23.16 4488.67 23.58 1112.17 23.61
Minimum of Months 28.67 22.53 121.33 22.86 0.00 22.89
Maximum of Months 459.00 23.90 710.00 23.93 339.67 23.93



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 442.17 23.40 30.17 23.43 10.00 23.43
February 515.50 22.91 68.17 23.01 31.50 23.04
March 509.83 22.96 32.33 23.02 4.67 23.02
April 318.50 23.47 39.67 23.53 0.00 23.53
May 284.50 23.47 28.17 23.51 0.00 23.51
June 61.17 23.46 338.50 23.90 5.50 23.90
July 284.50 23.95 619.00 23.91 269.83 23.93
August 310.67 23.96 665.33 23.92 308.83 23.93
September 240.33 23.96 665.00 23.93 240.33 23.93
October 261.33 23.52 218.00 23.71 51.33 23.74
November 404.00 23.40 167.33 23.49 75.67 23.48
December 641.33 23.23 0.00 23.23 0.00 23.23
             
Annual Sum or Average 4273.83 23.39 2871.67 23.60 997.67 23.63
Minimum of Months 61.17 22.91 0.00 23.01 0.00 23.02
Maximum of Months 641.33 23.96 665.33 23.93 308.83 23.93



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 737.00 21.61 12.67 21.60 12.67 21.59
February 670.33 21.39 1.83 21.39 1.83 21.38
March 740.00 21.52 32.83 21.50 32.83 21.48
April 689.67 21.64 0.00 21.64 0.00 21.64
May 708.33 21.66 0.00 21.66 0.00 21.66
June 622.83 21.53 9.17 21.55 0.00 21.55
July 611.00 21.41 16.50 21.46 0.17 21.46
August 595.33 21.36 29.00 21.46 1.00 21.46
September 584.50 21.38 27.67 21.46 5.50 21.48
October 687.50 21.55 4.17 21.56 0.00 21.56
November 699.17 21.56 62.17 21.55 60.17 21.53
December 742.67 21.50 163.17 21.42 163.17 21.36
             
Annual Sum or Average 8088.33 21.51 359.17 21.52 277.33 21.51
Minimum of Months 584.50 21.36 0.00 21.39 0.00 21.36
Maximum of Months 742.67 21.66 163.17 21.66 163.17 21.66



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 743.67 21.56 51.00 21.52 51.00 21.48
February 672.00 21.22 29.83 21.19 29.83 21.16
March 734.33 21.62 57.33 21.58 54.83 21.54
April 690.67 21.87 6.83 21.91 0.00 21.91
May 704.83 21.86 0.00 21.86 0.00 21.86
June 603.17 21.63 13.83 21.67 0.00 21.67
July 608.83 21.47 19.67 21.53 5.67 21.55
August 601.50 21.54 39.33 21.66 17.00 21.72
September 597.00 21.64 35.00 21.75 24.50 21.81
October 707.00 21.81 10.00 21.82 8.83 21.82
November 714.17 21.63 118.67 21.59 118.00 21.55
December 744.00 21.23 365.67 21.12 365.67 21.07
             
Annual Sum or Average 8121.17 21.59 747.17 21.58 675.33 21.55
Minimum of Months 597.00 21.22 0.00 21.12 0.00 21.07
Maximum of Months 744.00 21.87 365.67 21.91 365.67 21.91



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.42 17.33 21.41 17.33 21.41
February 672.00 21.30 2.83 21.29 2.83 21.29
March 744.00 21.60 10.67 21.59 10.67 21.58
April 720.00 21.83 0.00 21.83 0.00 21.83
May 744.00 21.87 0.00 21.87 0.00 21.87
June 719.83 21.86 0.00 21.86 0.00 21.86
July 743.50 21.78 2.50 21.79 2.50 21.79
August 741.67 21.83 10.33 21.85 10.33 21.88
September 718.83 21.88 13.17 21.90 13.17 21.92
October 744.00 21.77 2.67 21.77 2.67 21.77
November 720.00 21.51 57.33 21.52 57.33 21.52
December 744.00 21.23 217.67 21.19 217.67 21.16
             
Annual Sum or Average 8755.83 21.66 334.50 21.65 334.50 21.63
Minimum of Months 672.00 21.23 0.00 21.19 0.00 21.16
Maximum of Months 744.00 21.88 217.67 21.90 217.67 21.92



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.67 14.67 21.66 14.67 21.65
February 672.00 21.49 2.67 21.49 2.67 21.49
March 740.83 21.62 26.00 21.60 26.00 21.59
April 694.67 21.69 0.00 21.69 0.00 21.69
May 728.17 21.72 0.00 21.72 0.00 21.72
June 561.67 21.33 5.67 21.35 0.00 21.35
July 569.67 21.28 19.67 21.35 0.00 21.35
August 553.83 21.22 21.83 21.30 0.50 21.30
September 558.50 21.30 14.33 21.35 2.83 21.36
October 686.17 21.59 1.33 21.59 0.00 21.59
November 712.50 21.63 70.17 21.60 70.17 21.57
December 744.00 21.57 149.17 21.49 149.17 21.43
             
Annual Sum or Average 7966.00 21.53 325.50 21.53 266.00 21.52
Minimum of Months 553.83 21.22 0.00 21.30 0.00 21.30
Maximum of Months 744.00 21.72 149.17 21.72 149.17 21.72



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.57 57.33 21.53 57.33 21.50
February 672.00 21.30 18.83 21.28 18.83 21.27
March 742.83 21.74 41.67 21.70 41.17 21.67
April 671.33 21.89 23.17 22.02 0.00 22.02
May 673.33 21.81 40.33 22.05 0.50 22.06
June 518.33 21.35 35.83 21.57 0.17 21.58
July 557.83 21.32 27.67 21.46 5.33 21.49
August 542.17 21.37 42.83 21.58 16.67 21.67
September 546.00 21.53 45.00 21.76 22.33 21.85
October 687.50 21.85 13.33 21.90 5.83 21.90
November 718.50 21.63 130.00 21.57 129.83 21.52
December 744.00 21.23 342.67 21.15 342.67 21.11
             
Annual Sum or Average 7817.83 21.56 818.67 21.61 640.67 21.59
Minimum of Months 518.33 21.23 13.33 21.15 0.00 21.11
Maximum of Months 744.00 21.89 342.67 22.05 342.67 22.06



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 22.09 0.00 22.09 0.00 22.09
February 672.00 21.46 0.00 21.46 0.00 21.46
March 744.00 21.84 0.00 21.84 0.00 21.84
April 719.50 23.19 0.00 23.19 0.00 23.19
May 737.67 23.62 0.00 23.62 0.00 23.62
June 391.33 23.92 34.67 23.92 0.00 23.92
July 377.17 23.93 503.83 23.93 249.00 23.93
August 362.00 23.86 542.00 23.88 279.17 23.88
September 303.17 23.81 422.00 23.85 221.33 23.84
October 631.00 23.01 91.00 23.12 38.00 23.16
November 720.00 22.23 64.17 22.22 64.17 22.21
December 744.00 21.55 46.50 21.53 46.50 21.50
             
Annual Sum or Average 7145.83 22.67 1704.17 22.88 898.17 22.95
Minimum of Months 303.17 21.46 0.00 21.46 0.00 21.46
Maximum of Months 744.00 23.93 542.00 23.93 279.17 23.93



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 729.83 21.56 42.00 21.53 42.00 21.50
February 667.50 21.33 37.00 21.30 37.00 21.27
March 734.00 21.48 65.83 21.43 65.83 21.40
April 662.67 21.56 6.83 21.56 6.33 21.55
May 685.33 21.60 0.00 21.60 0.00 21.60
June 579.33 21.42 27.00 21.50 0.00 21.50
July 588.33 21.34 49.33 21.49 0.83 21.50
August 575.50 21.31 65.17 21.52 2.00 21.52
September 570.00 21.33 59.00 21.51 10.17 21.52
October 679.17 21.50 38.50 21.52 25.67 21.50
November 693.50 21.51 128.00 21.47 122.83 21.43
December 740.50 21.44 268.33 21.33 268.33 21.27
             
Annual Sum or Average 7905.67 21.45 787.00 21.47 581.00 21.45
Minimum of Months 570.00 21.31 0.00 21.30 0.00 21.27
Maximum of Months 740.50 21.60 268.33 21.60 268.33 21.60



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 743.50 21.49 148.67 21.39 148.67 21.32
February 671.50 21.15 94.83 21.08 94.83 21.02
March 730.17 21.57 97.83 21.53 92.33 21.46
April 672.33 21.79 12.17 21.84 3.67 21.84
May 689.00 21.79 0.00 21.79 0.00 21.79
June 563.33 21.54 31.17 21.63 0.00 21.63
July 585.67 21.40 49.17 21.55 8.00 21.57
August 580.33 21.47 67.83 21.67 20.17 21.73
September 585.00 21.58 59.33 21.74 33.33 21.82
October 699.50 21.72 57.00 21.68 55.17 21.64
November 712.50 21.54 207.17 21.44 206.33 21.38
December 744.00 21.14 490.67 21.03 490.67 20.98
             
Annual Sum or Average 7976.83 21.51 1315.83 21.49 1153.17 21.44
Minimum of Months 563.33 21.14 0.00 21.03 0.00 20.98
Maximum of Months 744.00 21.79 490.67 21.84 490.67 21.84



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 640.83 21.45 3.33 21.46 0.00 21.46
February 628.00 21.43 0.00 21.43 0.00 21.43
March 723.67 21.57 26.50 21.55 26.50 21.54
April 682.00 21.62 3.50 21.62 3.50 21.61
May 742.17 21.73 0.00 21.73 0.00 21.73
June 660.50 21.61 0.00 21.61 0.00 21.61
July 631.17 21.47 0.50 21.47 0.50 21.47
August 603.33 21.38 18.17 21.44 2.00 21.44
September 580.33 21.37 47.33 21.51 6.83 21.52
October 643.67 21.47 23.00 21.53 0.00 21.53
November 641.33 21.48 61.67 21.51 48.83 21.50
December 687.50 21.53 52.00 21.50 52.00 21.48
             
Annual Sum or Average 7864.50 21.52 236.00 21.53 140.17 21.53
Minimum of Months 580.33 21.37 0.00 21.43 0.00 21.43
Maximum of Months 742.17 21.73 61.67 21.73 52.00 21.73



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 258.17 23.36 94.83 23.52 9.50 23.53
February 224.83 23.31 283.00 23.67 51.00 23.70
March 171.50 23.28 275.33 23.71 5.33 23.72
April 16.50 23.60 252.00 23.97 0.00 23.97
May 0.00 0.00 327.83 23.99 0.00 23.99
June 9.67 24.00 666.67 24.00 9.67 24.00
July 286.67 24.00 698.17 23.99 286.67 23.99
August 332.33 24.00 721.33 23.99 332.33 23.99
September 264.67 23.99 719.83 23.99 264.67 23.99
October 135.50 23.62 317.67 23.87 58.00 23.88
November 270.17 23.55 231.50 23.71 79.00 23.73
December 476.00 23.46 9.67 23.47 0.00 23.47
             
Annual Sum or Average 2446.00 23.64 4597.83 23.86 1096.17 23.88
Minimum of Months 0.00 0.00 9.67 23.47 0.00 23.47
Maximum of Months 476.00 24.00 721.33 24.00 332.33 24.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 102.67 23.41 170.83 23.76 8.00 23.76
February 93.83 23.57 396.50 23.88 39.33 23.89
March 66.67 23.47 405.33 23.90 4.50 23.91
April 2.50 23.60 354.83 23.99 0.00 23.99
May 0.00 0.00 441.50 24.00 0.00 24.00
June 8.17 24.00 693.67 24.00 8.17 24.00
July 273.33 24.00 709.50 24.00 273.33 24.00
August 313.50 24.00 730.33 23.99 313.50 24.00
September 248.00 24.00 720.00 23.99 248.00 23.99
October 89.67 23.78 405.00 23.95 56.00 23.95
November 148.17 23.70 279.33 23.86 78.00 23.87
December 239.17 23.45 12.50 23.47 0.00 23.47
             
Annual Sum or Average 1585.67 23.79 5319.33 23.94 1028.83 23.95
Minimum of Months 0.00 0.00 12.50 23.47 0.00 23.47
Maximum of Months 313.50 24.00 730.33 24.00 313.50 24.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 506.83 23.97 671.67 23.93 502.00 23.94
February 471.50 23.99 646.17 23.89 470.50 23.92
March 518.83 23.97 705.50 23.91 513.33 23.93
April 510.67 23.99 712.33 23.96 510.67 23.97
May 534.33 23.99 743.17 23.97 534.33 23.98
June 559.00 23.99 720.00 23.99 559.00 23.99
July 694.17 23.99 744.00 23.99 694.17 23.99
August 706.17 23.98 744.00 23.98 706.17 23.98
September 643.83 23.99 720.00 23.98 643.83 23.98
October 547.00 23.99 721.00 23.95 546.83 23.96
November 519.17 23.96 662.00 23.92 514.83 23.94
December 505.00 23.87 614.17 23.91 468.83 23.93
             
Annual Sum or Average 6716.50 23.97 8404.00 23.95 6664.50 23.96
Minimum of Months 471.50 23.87 614.17 23.89 468.83 23.92
Maximum of Months 706.17 23.99 744.00 23.99 706.17 23.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.91 0.00 21.91 0.00 21.91
February 672.00 21.41 0.00 21.41 0.00 21.41
March 744.00 21.80 0.00 21.80 0.00 21.80
April 627.83 23.16 0.00 23.16 0.00 23.16
May 541.00 23.53 0.00 23.53 0.00 23.53
June 120.83 23.68 119.83 23.84 0.00 23.84
July 186.00 23.82 578.33 23.92 136.50 23.91
August 187.00 23.74 615.83 23.87 149.50 23.85
September 177.17 23.61 484.33 23.80 120.33 23.79
October 589.67 22.65 103.33 22.84 20.17 22.86
November 716.00 22.00 27.67 21.99 27.67 21.99
December 744.00 21.47 98.33 21.42 98.33 21.37
             
Annual Sum or Average 6049.50 22.35 2027.67 22.70 552.50 22.73
Minimum of Months 120.83 21.41 0.00 21.41 0.00 21.37
Maximum of Months 744.00 23.82 615.83 23.92 149.50 23.91



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.59316 26.65345 0.14182 5.59166
February 672.00000 22.72375 41.08002 0.01200 5.18093
March 744.00000 22.05465 33.86427 -0.2026 6.08464
April 720.00000 22.42295 25.11913 -0.1626 5.75541
May 744.00000 22.10310 24.86994 -1.3453 42.72544
June 720.00000 22.41839 36.38637 -1.1583 33.46026
July 744.00000 23.63954 50.49982 -0.6228 13.92467
August 744.00000 23.88017 52.39569 -0.5132 10.69524
September 720.00000 23.98484 50.54075 -0.4695 9.71923
October 744.00000 23.98731 30.90834 0.29570 7.01243
November 720.00000 23.99036 30.23486 0.28883 6.95669
December 744.00000 23.96491 18.95957 0.19774 5.85442
           
Annual Sum or Average 8760.00000 23.23471 35.07221 -0.2965 12.79550
Minimum of Months 672.00000 22.05465 18.95957 -1.3453 5.18093
Maximum of Months 744.00000 23.99036 52.39569 0.29570 42.72544



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.52445 26.24636 0.00202 7.02718
February 672.00000 21.68246 41.75613 -0.1685 6.83546
March 744.00000 21.86237 32.37454 -0.1662 6.94249
April 720.00000 23.18110 22.10791 0.14532 6.67774
May 744.00000 23.36841 21.26981 -0.7371 17.77705
June 720.00000 23.80853 31.29469 -0.4691 10.21786
July 744.00000 23.79156 48.34713 -0.3691 8.49456
August 744.00000 23.74179 51.19294 -0.3579 8.44253
September 720.00000 23.69425 50.44356 -0.3791 8.92102
October 744.00000 23.06035 31.24182 0.18710 7.92938
November 720.00000 22.45116 31.99123 0.01461 7.03926
December 744.00000 22.06885 19.37693 -0.1853 8.04195
           
Annual Sum or Average 8760.00000 22.94277 33.90638 -0.2077 8.71611
Minimum of Months 672.00000 21.68246 19.37693 -0.7371 6.67774
Maximum of Months 744.00000 23.80853 51.19294 0.18710 17.77705



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.07649 27.39159 0.06227 5.42336
February 672.00000 22.47982 41.68799 -0.0038 5.37248
March 744.00000 22.74313 32.77390 0.01012 5.60536
April 720.00000 23.64187 23.41351 0.19232 6.07434
May 744.00000 23.76286 22.57630 -0.6878 15.24998
June 720.00000 23.91720 32.71471 -0.5382 11.28337
July 744.00000 23.89635 49.44760 -0.4390 9.30418
August 744.00000 23.88759 52.19405 -0.4242 8.96424
September 720.00000 23.87133 51.42820 -0.4422 9.29406
October 744.00000 23.51980 32.40565 0.22025 6.66726
November 720.00000 23.13548 32.58563 0.11267 5.80169
December 744.00000 22.66032 20.82554 -0.0883 5.59896
           
Annual Sum or Average 8760.00000 23.38727 34.89748 -0.1702 7.90479
Minimum of Months 672.00000 22.47982 20.82554 -0.6878 5.37248
Maximum of Months 744.00000 23.91720 52.19405 0.22025 15.24998



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.14538 22.97999 0.66511 16.73072
February 672.00000 23.08133 36.11530 0.72050 18.46219
March 744.00000 23.11761 27.96217 0.69411 17.60104
April 720.00000 23.24220 19.90505 0.72783 18.37457
May 744.00000 23.28010 19.28771 0.07777 9.45338
June 720.00000 23.30813 30.49518 0.20631 9.99438
July 744.00000 23.29653 47.47253 0.29753 10.91512
August 744.00000 23.27081 50.34934 0.30371 11.05893
September 720.00000 23.26587 49.31680 0.27273 10.76910
October 744.00000 23.21753 28.93301 0.76238 19.58138
November 720.00000 23.15917 28.28151 0.70823 18.10430
December 744.00000 23.09700 16.22601 0.58887 14.71043
           
Annual Sum or Average 8760.00000 23.20743 31.39923 0.50055 14.61861
Minimum of Months 672.00000 23.08133 16.22601 0.07777 9.45338
Maximum of Months 744.00000 23.30813 50.34934 0.76238 19.58138



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.63247 30.30622 0.33270 7.98811
February 672.00000 22.97660 44.62573 0.20329 6.81924
March 744.00000 23.08962 36.13453 0.18526 6.69196
April 720.00000 23.72191 26.92669 0.33953 7.89299
May 744.00000 23.70859 26.27181 -0.5438 11.74518
June 720.00000 23.84841 36.23050 -0.3715 8.29735
July 744.00000 23.86091 52.80188 -0.2571 6.77788
August 744.00000 23.86788 55.38014 -0.2264 6.42316
September 720.00000 23.89299 54.38944 -0.2216 6.42901
October 744.00000 23.74825 35.40930 0.41981 9.52165
November 720.00000 23.55148 35.68112 0.33932 8.21861
December 744.00000 23.29582 24.08315 0.17620 6.73775
           
Annual Sum or Average 8760.00000 23.60301 38.13247 0.03001 7.80420
Minimum of Months 672.00000 22.97660 24.08315 -0.5438 6.42316
Maximum of Months 744.00000 23.89299 55.38014 0.41981 11.74518



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.60245 29.69621 0.22914 6.31915
February 672.00000 23.12239 43.42111 0.18263 6.12085
March 744.00000 23.24663 35.03718 0.16546 6.13601
April 720.00000 23.73428 26.01341 0.25802 6.61831
May 744.00000 23.76773 25.15126 -0.6291 13.58010
June 720.00000 23.88484 35.26241 -0.4873 10.21681
July 744.00000 23.88882 51.79462 -0.3752 8.22958
August 744.00000 23.89998 54.48295 -0.3539 7.79270
September 720.00000 23.91514 53.55787 -0.3583 7.83861
October 744.00000 23.77812 34.65177 0.32958 7.69932
November 720.00000 23.59959 34.78995 0.26457 6.85907
December 744.00000 23.32336 23.39128 0.10616 5.58810
           
Annual Sum or Average 8760.00000 23.64976 37.21880 -0.0574 7.76181
Minimum of Months 672.00000 23.12239 23.39128 -0.6291 5.58810
Maximum of Months 744.00000 23.91514 54.48295 0.32958 13.58010



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.62133 32.86884 -0.2664 7.45263
February 672.00000 21.39454 47.55733 -0.2929 7.39436
March 744.00000 21.53226 37.85055 -0.2789 7.44317
April 720.00000 21.71347 27.86297 -0.1764 6.68022
May 744.00000 21.73694 26.82496 -1.2243 37.70613
June 720.00000 21.76535 35.62174 -1.0893 31.55719
July 744.00000 21.75115 45.74669 -1.0686 30.58741
August 744.00000 21.75324 47.94396 -1.0596 30.28703
September 720.00000 21.74486 49.29467 -1.0755 30.98020
October 744.00000 21.68577 35.75037 -0.1682 6.77342
November 720.00000 21.61008 37.78794 -0.2351 7.20129
December 744.00000 21.50134 25.38567 -0.3913 9.17898
           
Annual Sum or Average 8760.00000 21.65234 37.45788 -0.6128 17.84083
Minimum of Months 672.00000 21.39454 25.38567 -1.2243 6.68022
Maximum of Months 744.00000 21.76535 49.29467 -0.1682 37.70613



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.56445 32.98715 -0.3459 8.20640
February 672.00000 21.22171 47.99849 -0.3687 8.24434
March 744.00000 21.66456 37.68275 -0.2829 7.64126
April 720.00000 21.96323 27.59697 -0.1477 6.59668
May 744.00000 21.94490 26.58398 -1.1750 35.39456
June 720.00000 21.92649 35.43454 -1.0406 29.50341
July 744.00000 21.81619 45.77244 -1.0510 29.81774
August 744.00000 21.88815 48.08966 -1.0340 29.22178
September 720.00000 21.94236 49.77568 -1.0429 29.57813
October 744.00000 21.89879 35.64648 -0.1672 6.79039
November 720.00000 21.64439 38.04250 -0.2819 7.72755
December 744.00000 21.22582 25.69974 -0.5138 11.19304
           
Annual Sum or Average 8760.00000 21.72765 37.52268 -0.6229 17.55955
Minimum of Months 672.00000 21.22171 25.69974 -1.1750 6.59668
Maximum of Months 744.00000 21.96323 49.77568 -0.1477 35.39456



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.42218 32.68124 -0.3948 8.45023
February 672.00000 21.29711 47.00959 -0.3418 7.62027
March 744.00000 21.59501 37.14988 -0.3120 7.46348
April 720.00000 21.82546 27.45273 -0.2697 7.11760
May 744.00000 21.86957 26.50655 -1.3468 43.33406
June 720.00000 21.86297 36.06093 -1.2443 38.32558
July 744.00000 21.78304 46.59375 -1.2162 36.97715
August 744.00000 21.83831 48.90103 -1.2000 36.27709
September 720.00000 21.88204 50.47524 -1.1908 35.82963
October 744.00000 21.77332 35.29343 -0.2528 7.03262
November 720.00000 21.51468 37.27683 -0.3356 7.91985
December 744.00000 21.23117 25.23252 -0.5022 10.44740
           
Annual Sum or Average 8760.00000 21.65963 37.47219 -0.7199 20.65367
Minimum of Months 672.00000 21.23117 25.23252 -1.3468 7.03262
Maximum of Months 744.00000 21.88204 50.47524 -0.2528 43.33406



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.67272 32.77894 -0.2568 7.37452
February 672.00000 21.49402 47.08941 -0.2627 7.20143
March 744.00000 21.62840 37.67846 -0.2500 7.22393
April 720.00000 21.74902 27.85946 -0.1614 6.65827
May 744.00000 21.75468 26.83814 -1.2045 36.88306
June 720.00000 21.76865 35.73419 -1.0758 31.10024
July 744.00000 21.76016 45.65847 -1.0435 29.65099
August 744.00000 21.75951 47.74525 -1.0391 29.51957
September 720.00000 21.75400 49.10544 -1.0621 30.47528
October 744.00000 21.72582 35.63288 -0.1515 6.72719
November 720.00000 21.64858 37.83572 -0.2307 7.13847
December 744.00000 21.56794 25.32805 -0.3735 8.88580
           
Annual Sum or Average 8760.00000 21.69147 37.35894 -0.5949 17.47130
Minimum of Months 672.00000 21.49402 25.32805 -1.2045 6.65827
Maximum of Months 744.00000 21.76865 49.10544 -0.1515 36.88306



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.56801 32.98436 -0.3472 8.05364
February 672.00000 21.29549 47.62812 -0.3421 7.81172
March 744.00000 21.73984 37.48506 -0.2582 7.25405
April 720.00000 22.09859 27.42373 -0.1132 6.80411
May 744.00000 22.12666 26.50350 -1.1084 33.85728
June 720.00000 21.98463 35.53475 -1.0110 28.94623
July 744.00000 21.84904 45.71398 -1.0189 28.82145
August 744.00000 21.93336 47.92129 -1.0016 28.31009
September 720.00000 22.01441 49.43070 -1.0114 28.87605
October 744.00000 21.99730 35.37245 -0.1388 6.76702
November 720.00000 21.63572 38.08850 -0.2886 7.63365
December 744.00000 21.23276 25.66698 -0.5076 10.85608
           
Annual Sum or Average 8760.00000 21.79214 37.39450 -0.5976 17.06312
Minimum of Months 672.00000 21.23276 25.66698 -1.1084 6.76702
Maximum of Months 744.00000 22.12666 49.43070 -0.1132 33.85728



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.58913 33.22589 -0.2937 7.96838
February 672.00000 21.34617 48.38930 -0.3220 7.94325
March 744.00000 21.50198 38.24728 -0.2985 7.86256
April 720.00000 21.70243 27.94538 -0.1780 6.91040
May 744.00000 21.73323 26.82877 -1.2199 37.75453
June 720.00000 21.76929 35.72759 -1.0672 30.89901
July 744.00000 21.75144 45.95635 -1.0504 30.03656
August 744.00000 21.75389 48.27511 -1.0434 29.86158
September 720.00000 21.74183 49.85528 -1.0686 30.90180
October 744.00000 21.66189 36.04342 -0.1851 7.12802
November 720.00000 21.57310 38.38483 -0.2611 7.67068
December 744.00000 21.45321 25.62674 -0.4280 10.01086
           
Annual Sum or Average 8760.00000 21.63310 37.78796 -0.6201 17.98127
Minimum of Months 672.00000 21.34617 25.62674 -1.2199 6.91040
Maximum of Months 744.00000 21.76929 49.85528 -0.1780 37.75453



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.49519 33.44754 -0.3855 8.96322
February 672.00000 21.15400 48.88687 -0.4047 8.98729
March 744.00000 21.63778 38.09389 -0.3020 8.13112
April 720.00000 21.93277 27.72352 -0.1516 6.82987
May 744.00000 21.90406 26.65986 -1.1795 35.77765
June 720.00000 21.91430 35.59383 -1.0218 28.92815
July 744.00000 21.80802 45.95814 -1.0350 29.32997
August 744.00000 21.87518 48.38303 -1.0213 28.87741
September 720.00000 21.91195 50.30038 -1.0435 29.71924
October 744.00000 21.82906 36.01194 -0.1942 7.20887
November 720.00000 21.56105 38.71337 -0.3208 8.42455
December 744.00000 21.13789 26.01974 -0.5629 12.44074
           
Annual Sum or Average 8760.00000 21.68278 37.89196 -0.6371 17.86657
Minimum of Months 672.00000 21.13789 26.01974 -1.1795 6.82987
Maximum of Months 744.00000 21.93277 50.30038 -0.1516 35.77765



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.70884 34.00935 -0.1860 7.16548
February 672.00000 21.55496 47.78091 -0.2180 6.99720
March 744.00000 21.62278 38.67035 -0.2459 7.35154
April 720.00000 21.70871 29.55772 -0.2018 7.03186
May 744.00000 21.72994 28.68084 -1.2934 41.09995
June 720.00000 21.75182 37.35775 -1.1755 35.44935
July 744.00000 21.74927 46.51380 -1.1260 33.17768
August 744.00000 21.74962 48.66845 -1.1047 32.37464
September 720.00000 21.75135 50.02593 -1.0935 31.99100
October 744.00000 21.71685 36.75678 -0.1441 6.88456
November 720.00000 21.68320 38.55457 -0.1779 7.00478
December 744.00000 21.66822 26.95129 -0.2763 8.09924
           
Annual Sum or Average 8760.00000 21.70056 38.54937 -0.6061 18.79720
Minimum of Months 672.00000 21.55496 26.95129 -1.2934 6.88456
Maximum of Months 744.00000 21.75182 50.02593 -0.1441 41.09995



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.74584 30.62579 0.28458 6.95104
February 672.00000 23.68775 43.26429 0.34682 7.86457
March 744.00000 23.77282 35.06847 0.33492 7.64412
April 720.00000 23.95297 26.44704 0.38489 8.23342
May 744.00000 23.98426 25.51725 -0.4273 8.92491
June 720.00000 23.99462 35.80009 -0.2977 6.98042
July 744.00000 23.99429 52.06625 -0.1957 6.00152
August 744.00000 23.99202 54.84103 -0.1901 5.88549
September 720.00000 23.98656 54.03203 -0.2178 6.11937
October 744.00000 23.88916 35.40718 0.40621 8.90279
November 720.00000 23.78061 35.49212 0.33501 7.80212
December 744.00000 23.64270 24.49542 0.19382 6.09609
           
Annual Sum or Average 8760.00000 23.86946 37.70740 0.07792 7.27905
Minimum of Months 672.00000 23.64270 24.49542 -0.4273 5.88549
Maximum of Months 744.00000 23.99462 54.84103 0.40621 8.92491



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.86038 29.80589 0.34641 7.67700
February 672.00000 23.82651 42.26314 0.41781 8.89081
March 744.00000 23.88143 34.22452 0.39684 8.49067
April 720.00000 23.97942 25.93481 0.41999 8.80758
May 744.00000 23.99281 25.09438 -0.3858 8.21311
June 720.00000 23.99577 35.45379 -0.2611 6.55712
July 744.00000 23.99546 51.70813 -0.1594 5.73504
August 744.00000 23.99454 54.46869 -0.1531 5.62219
September 720.00000 23.99286 53.62990 -0.1794 5.79886
October 744.00000 23.94086 34.80808 0.44805 9.56958
November 720.00000 23.88424 34.68550 0.39373 8.60650
December 744.00000 23.79153 23.63396 0.26625 6.67552
           
Annual Sum or Average 8760.00000 23.92843 37.09737 0.12721 7.54389
Minimum of Months 672.00000 23.79153 23.63396 -0.3858 5.62219
Maximum of Months 744.00000 23.99577 54.46869 0.44805 9.56958



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.78288 29.13967 0.98245 27.76744
February 672.00000 23.77890 41.28203 1.04577 30.25398
March 744.00000 23.80687 33.63971 1.02702 29.49406
April 720.00000 23.92485 25.98977 1.09002 31.94656
May 744.00000 23.95614 25.35343 0.58317 16.18886
June 720.00000 23.98717 35.66050 0.73315 19.83823
July 744.00000 23.98737 51.44711 0.82053 22.53604
August 744.00000 23.98344 54.09175 0.82460 22.69386
September 720.00000 23.97649 53.21559 0.78271 21.29625
October 744.00000 23.88929 34.45451 1.10455 32.76473
November 720.00000 23.80243 34.01694 1.02523 29.52696
December 744.00000 23.72842 22.85944 0.89737 24.72059
           
Annual Sum or Average 8760.00000 23.88412 36.72037 0.90862 25.71640
Minimum of Months 672.00000 23.72842 22.85944 0.58317 16.18886
Maximum of Months 744.00000 23.98737 54.09175 1.10455 32.76473



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.55579 26.18729 -0.3445 7.65144
February 672.00000 21.15595 41.39604 -0.3553 7.76122
March 744.00000 21.51264 31.59749 -0.3229 7.59500
April 720.00000 22.88352 21.03365 -0.0516 5.43341
May 744.00000 23.47454 19.71707 -0.8748 21.39724
June 720.00000 23.96626 29.71698 -0.6214 13.22009
July 744.00000 23.95139 46.73234 -0.5120 10.68835
August 744.00000 23.88255 49.62034 -0.5217 10.86871
September 720.00000 23.77546 49.10879 -0.5667 11.92907
October 744.00000 22.70743 30.39235 -0.0302 6.33607
November 720.00000 21.75312 31.56326 -0.2606 7.02578
December 744.00000 21.22082 18.87825 -0.4741 9.85425
           
Annual Sum or Average 8760.00000 22.66076 32.92780 -0.4122 10.00462
Minimum of Months 672.00000 21.15595 18.87825 -0.8748 5.43341
Maximum of Months 744.00000 23.96626 49.62034 -0.0302 21.39724



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.08552 29.56904 -0.2247 6.25480
February 672.00000 21.45690 44.77898 -0.2900 6.84051
March 744.00000 21.84191 35.12336 -0.2500 6.64945
April 720.00000 23.18617 25.12212 0.01666 5.34821
May 744.00000 23.61903 24.12269 -0.8404 20.07624
June 720.00000 23.95085 33.97491 -0.6479 13.92526
July 744.00000 23.93041 50.74852 -0.5433 11.36892
August 744.00000 23.88741 53.63584 -0.5399 11.23420
September 720.00000 23.85858 52.95322 -0.5564 11.61647
October 744.00000 23.14955 34.00903 0.06987 6.05138
November 720.00000 22.23311 34.97243 -0.1539 5.87157
December 744.00000 21.55357 22.61644 -0.3968 8.57531
           
Annual Sum or Average 8760.00000 22.90341 36.73716 -0.3640 9.50931
Minimum of Months 672.00000 21.45690 22.61644 -0.8404 5.34821
Maximum of Months 744.00000 23.95085 53.63584 0.06987 20.07624



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.91261 27.02321 -0.2412 6.58433
February 672.00000 21.40669 42.13422 -0.2808 6.84790
March 744.00000 21.80303 32.40653 -0.2347 6.69983
April 720.00000 23.26383 22.07899 0.07222 5.66323
May 744.00000 23.65101 21.06084 -0.7631 17.71976
June 720.00000 23.93281 31.24444 -0.5655 11.89962
July 744.00000 23.93628 47.79367 -0.4561 9.62697
August 744.00000 23.88830 50.67361 -0.4571 9.60528
September 720.00000 23.82556 50.01124 -0.4933 10.35934
October 744.00000 22.90532 31.42263 0.04572 6.49730
November 720.00000 22.00818 32.44623 -0.1815 6.41659
December 744.00000 21.47209 19.94285 -0.4000 8.74205
           
Annual Sum or Average 8760.00000 22.84089 33.95400 -0.3304 8.90862
Minimum of Months 672.00000 21.40669 19.94285 -0.7631 5.66323
Maximum of Months 744.00000 23.93628 50.67361 0.07222 17.71976



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.63603 25.71897 -0.3269 7.44895
February 672.00000 21.23537 40.86957 -0.3368 7.53806
March 744.00000 21.61104 31.08060 -0.3003 7.35410
April 720.00000 23.01046 20.53362 -0.0212 5.44229
May 744.00000 23.59004 19.25820 -0.8313 19.84280
June 720.00000 23.98181 29.39557 -0.6051 12.79240
July 744.00000 23.96423 46.33389 -0.4976 10.38065
August 744.00000 23.91197 49.17004 -0.5029 10.45485
September 720.00000 23.83357 48.56589 -0.5401 11.30564
October 744.00000 22.82042 29.86321 -0.0028 6.31516
November 720.00000 21.85362 31.02278 -0.2379 6.84113
December 744.00000 21.28355 18.48157 -0.4597 9.60504
           
Annual Sum or Average 8760.00000 22.73510 32.45749 -0.3894 9.63276
Minimum of Months 672.00000 21.23537 18.48157 -0.8313 5.44229
Maximum of Months 744.00000 23.98181 49.17004 -0.0028 19.84280



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.581470E+11 111445.89 31-JAN-16:01 685.15 0.189243E+12 0.00 0.247390E+12 3.09 4.16 31-JAN-19:01 0.00 0.00
February 0.186456E+11 70808.01 09-FEB-16:01 528.65 0.615216E+11 0.00 0.801672E+11 2.68 4.07 09-FEB-16:01 0.00 0.00
March 0.544503E+11 105663.07 16-MAR-15:03 671.32 0.173316E+12 0.00 0.227767E+12 2.99 4.13 03-MAR-16:01 0.00 0.00
April 0.144547E+12 141599.60 14-APR-18:03 719.75 0.469569E+12 0.00 0.614116E+12 3.26 4.12 03-APR-21:51 0.00 0.00
May 0.187604E+12 153589.21 31-MAY-18:03 744.00 0.598986E+12 0.00 0.786589E+12 3.19 4.03 13-MAY-21:51 0.00 0.00
June 0.250710E+12 190697.88 28-JUN-18:04 720.00 0.770244E+12 0.00 0.102095E+13 3.11 3.89 20-JUN-06:41 0.00 0.00
July 0.265582E+12 174489.18 20-JUL-18:03 744.00 0.870349E+12 0.00 0.113593E+13 3.30 4.40 14-JUL-01:00 0.00 0.00
August 0.258192E+12 181421.86 25-AUG-15:03 744.00 0.848422E+12 0.00 0.110661E+13 3.32 4.51 18-AUG-22:00 0.00 0.00
September 0.227341E+12 167695.37 08-SEP-18:03 720.00 0.775380E+12 0.00 0.100272E+13 3.41 4.63 03-SEP-08:53 0.00 0.00
October 0.127568E+12 149163.27 02-OCT-18:03 736.08 0.422058E+12 0.00 0.549626E+12 3.29 4.19 03-OCT-03:00 0.00 0.00
November 0.617852E+11 110368.47 01-NOV-15:03 668.37 0.201931E+12 0.00 0.263716E+12 3.11 4.56 12-NOV-16:02 0.00 0.00
December 0.345104E+11 93272.93 25-DEC-16:03 595.98 0.111753E+12 0.00 0.146263E+12 2.71 4.16 02-DEC-16:01 0.00 0.00
                         
Annual Sum or Average 0.168908E+13     8277.31 0.549277E+13 0.00 0.718186E+13 3.12     0.00 0.00
Minimum of Months 0.186456E+11 70808.01   528.65 0.615216E+11 0.00 0.801672E+11 2.68 3.89   0.00 0.00
Maximum of Months 0.265582E+12 190697.88   744.00 0.870349E+12 0.00 0.113593E+13 3.41 4.63   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.522493E+11 0.00 414.29 153038.25 01-JAN-00:10 0.00 45.10 65.71 0.12 0.00 0.06 0.45 01-JAN-00:10
February 0.593167E+11 0.00 557.13 129376.60 03-FEB-07:05 0.00 43.90 73.17 0.15 0.00 0.07 0.38 03-FEB-07:05
March 0.395670E+11 0.00 381.21 141317.24 26-MAR-08:03 0.00 41.03 60.13 0.09 0.00 0.04 0.41 26-MAR-08:03
April 0.189051E+10 0.00 33.79 78856.42 21-APR-06:05 0.00 45.03 46.97 0.00 0.00 0.00 0.23 21-APR-06:05
May 94145143.99 0.00 3.89 36987.42 02-MAY-08:44 0.00 52.19 52.35 0.00 0.00 0.00 0.11 02-MAY-08:44
June 14481253.82 0.00 0.85 13087.83 27-JUN-08:06 0.00 57.03 57.06 0.00 0.00 0.00 0.04 27-JUN-08:06
July 24528104.41 0.00 1.51 12243.17 03-JUL-08:06 0.00 59.71 59.74 0.00 0.00 0.00 0.04 03-JUL-08:06
August 35291632.03 0.00 1.99 15781.92 22-AUG-08:06 0.00 60.68 60.73 0.00 0.00 0.00 0.05 22-AUG-08:06
September 34870762.77 0.00 2.42 13355.82 23-SEP-08:55 0.00 61.06 61.12 0.00 0.00 0.00 0.04 23-SEP-08:55
October 0.126883E+11 0.00 140.73 124926.18 25-OCT-08:03 0.00 51.16 58.21 0.03 0.00 0.01 0.37 25-OCT-08:03
November 0.357855E+11 0.00 346.17 129653.99 23-NOV-19:03 0.00 45.39 62.48 0.08 0.00 0.04 0.38 23-NOV-19:03
December 0.782579E+11 0.00 589.93 162599.47 06-DEC-09:01 0.00 46.29 73.93 0.19 0.00 0.09 0.48 06-DEC-09:01
                           
Annual Sum or Average 0.279959E+12 0.00 2473.90     0.00 50.75 60.91 0.06 0.00 0.03    
Minimum of Months 14481253.82 0.00 0.85 12243.17   0.00 41.03 46.97 0.00 0.00 0.00 0.04  
Maximum of Months 0.782579E+11 0.00 589.93 162599.47   0.00 61.06 73.93 0.19 0.00 0.09 0.48  



Table of Contents

Report: DXReportMonthly

For: SWHSYS1 HPWH DXCOIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.479448E+11 0.00 387.56 0.479448E+11 -0.0 0.00 1.00 01-JAN-06:15 0.00 01-JAN-00:10 50005.68 23-JAN-08:50 50005.68 23-JAN-06:50 0.00 03-JAN-07:30 0.00 0.00 01-JAN-00:10
February 0.429777E+11 0.00 352.25 0.412571E+11 0.172057E+10 0.00 1.00 01-FEB-06:15 0.00 01-FEB-00:05 50632.36 01-FEB-06:15 48540.52 01-FEB-21:20 2094.91 01-FEB-06:15 0.00 0.00 01-FEB-00:05
March 0.451658E+11 0.00 378.40 0.451658E+11 -0.0 0.00 1.00 01-MAR-06:15 0.00 01-MAR-00:05 51140.41 01-MAR-06:15 51140.41 01-MAR-07:15 0.00 28-MAR-06:30 0.00 0.00 01-MAR-00:05
April 0.408598E+11 0.00 349.65 0.408598E+11 -0.0 0.00 1.00 01-APR-05:17 0.00 01-APR-00:10 55691.74 01-APR-05:17 55691.74 01-APR-10:04 0.00 05-APR-10:30 0.00 0.00 01-APR-00:10
May 0.380775E+11 0.00 359.76 0.380775E+11 -0.0 0.00 1.00 01-MAY-06:15 0.00 01-MAY-00:05 56749.03 01-MAY-06:15 56749.03 01-MAY-07:14 0.00 24-MAY-06:15 0.00 0.00 01-MAY-00:05
June 0.341349E+11 0.00 336.75 0.341349E+11 0.00 0.00 1.00 01-JUN-05:10 0.00 01-JUN-00:05 60458.41 01-JUN-05:10 60458.41 01-JUN-05:10 0.00 29-JUN-10:18 0.00 0.00 01-JUN-00:05
July 0.338582E+11 0.00 347.17 0.338582E+11 -0.0 0.00 1.00 01-JUL-05:08 0.00 01-JUL-00:20 62130.92 01-JUL-05:08 62130.92 01-JUL-07:12 0.00 03-JUL-17:17 0.00 0.00 01-JUL-00:10
August 0.344209E+11 0.00 346.21 0.344209E+11 0.00 0.00 1.00 01-AUG-05:10 0.00 01-AUG-00:05 62274.97 31-AUG-05:10 62274.97 31-AUG-07:15 0.00 15-AUG-10:37 0.00 0.00 01-AUG-00:05
September 0.357718E+11 0.00 336.66 0.357718E+11 -0.0 0.00 1.00 01-SEP-05:10 0.00 01-SEP-00:05 62074.83 30-SEP-05:08 62074.83 30-SEP-07:15 0.00 24-SEP-08:54 0.00 0.00 01-SEP-00:05
October 0.396390E+11 0.00 357.95 0.396390E+11 0.00 0.00 1.00 01-OCT-05:10 0.00 01-OCT-00:20 54713.42 31-OCT-05:15 54713.42 31-OCT-07:13 0.00 29-OCT-07:30 0.00 0.00 01-OCT-00:10
November 0.416766E+11 0.00 362.28 0.416766E+11 -0.0 0.00 1.00 01-NOV-05:15 0.00 01-NOV-00:05 50952.66 30-NOV-06:15 50952.66 30-NOV-11:37 0.00 28-NOV-00:10 0.00 0.00 01-NOV-00:05
December 0.450274E+11 0.00 393.34 0.450274E+11 0.00 0.00 1.00 01-DEC-04:10 0.00 01-DEC-00:05 45484.54 31-DEC-02:10 45484.54 31-DEC-07:20 0.00 03-DEC-08:30 0.00 0.00 01-DEC-00:05
                                       
Annual Sum or Average 0.479554E+12 0.00 4307.99 0.477834E+12 0.172057E+10 0.00                     0.00    
Minimum of Months 0.338582E+11 0.00 336.66 0.338582E+11 -0.0 0.00 1.00   0.00   45484.54   45484.54   0.00   0.00 0.00  
Maximum of Months 0.479448E+11 0.00 393.34 0.479448E+11 0.172057E+10 0.00 1.00   0.00   62274.97   62274.97   2094.91   0.00 0.00  



Table of Contents

Report: DXReportMonthly

For: SWHSYSLAUNDRY HPWH DXCOIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.501268E+11 0.00 354.97 0.501268E+11 -0.0 0.00 1.00 01-JAN-17:10 0.00 01-JAN-00:10 63283.04 23-JAN-17:10 63283.04 23-JAN-17:30 0.00 06-JAN-19:30 0.00 0.00 01-JAN-00:10
February 0.457469E+11 0.00 338.43 0.439298E+11 0.181714E+10 0.00 1.00 01-FEB-17:10 0.00 01-FEB-00:10 64076.57 01-FEB-17:10 61448.63 01-FEB-20:00 2629.37 01-FEB-17:10 0.00 0.00 01-FEB-00:05
March 0.509446E+11 0.00 349.19 0.509446E+11 -0.0 0.00 1.00 01-MAR-17:10 0.00 01-MAR-00:10 64719.88 01-MAR-17:10 64719.88 01-MAR-17:10 0.00 26-MAR-22:10 0.00 0.00 01-MAR-00:05
April 0.536847E+11 0.00 336.79 0.536847E+11 -0.0 0.00 1.00 01-APR-16:10 0.00 01-APR-00:20 70482.94 01-APR-16:10 70482.94 01-APR-16:10 0.00 05-APR-22:10 0.00 0.00 01-APR-00:10
May 0.566123E+11 0.00 345.34 0.566123E+11 -0.0 0.00 1.00 01-MAY-16:10 0.00 01-MAY-00:05 71821.71 01-MAY-19:20 71821.71 01-MAY-16:50 0.00 08-MAY-22:10 0.00 0.00 01-MAY-00:05
June 0.585014E+11 0.00 324.97 0.585014E+11 0.00 0.00 1.00 01-JUN-16:10 0.00 01-JUN-00:05 76518.66 01-JUN-16:10 76518.66 01-JUN-16:10 0.00 02-JUN-16:30 0.00 0.00 01-JUN-00:05
July 0.623813E+11 0.00 337.75 0.623813E+11 -0.0 0.00 1.00 01-JUL-16:10 0.00 01-JUL-00:10 78636.46 01-JUL-19:10 78636.46 01-JUL-19:10 0.00 11-JUL-16:20 0.00 0.00 01-JUL-00:10
August 0.623611E+11 0.00 338.32 0.623611E+11 0.00 0.00 1.00 01-AUG-16:10 0.00 01-AUG-00:05 78818.87 31-AUG-16:10 78818.87 31-AUG-16:10 0.00 22-AUG-17:40 0.00 0.00 01-AUG-00:05
September 0.598770E+11 0.00 327.66 0.598770E+11 -0.0 0.00 1.00 01-SEP-16:10 0.00 01-SEP-00:05 78565.43 30-SEP-16:10 78565.43 30-SEP-16:20 0.00 04-SEP-16:10 0.00 0.00 01-SEP-00:05
October 0.543738E+11 0.00 348.46 0.543738E+11 0.00 0.00 1.00 01-OCT-16:10 0.00 01-OCT-00:20 69244.15 31-OCT-16:10 69244.15 31-OCT-16:10 0.00 06-OCT-17:25 0.00 0.00 01-OCT-00:10
November 0.490453E+11 0.00 337.69 0.490453E+11 -0.0 0.00 1.00 01-NOV-16:10 0.00 01-NOV-00:05 64482.14 30-NOV-17:10 64482.14 30-NOV-21:10 0.00 15-NOV-23:20 0.00 0.00 01-NOV-00:05
December 0.454228E+11 0.00 375.71 0.454228E+11 0.00 0.00 1.00 01-DEC-17:10 0.00 01-DEC-00:10 57558.21 31-DEC-21:13 57558.21 31-DEC-21:05 0.00 05-DEC-18:00 0.00 0.00 01-DEC-00:05
                                       
Annual Sum or Average 0.649078E+12 0.00 4115.28 0.647261E+12 0.181714E+10 0.00                     0.00    
Minimum of Months 0.454228E+11 0.00 324.97 0.439298E+11 -0.0 0.00 1.00   0.00   57558.21   57558.21   0.00   0.00 0.00  
Maximum of Months 0.623813E+11 0.00 375.71 0.623813E+11 0.181714E+10 0.00 1.00   0.00   78818.87   78818.87   2629.37   0.00 0.00  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.104113E+12 0.00 376.36 0.103683E+12 0.00 0.00 0.00 0.00 175247.19 31-JAN-16:30 175247.19 31-JAN-16:30 0.00 0.00 0.00
February 0.254135E+11 0.00 218.50 0.253868E+11 0.00 0.00 0.00 0.00 103488.11 18-FEB-14:00 103488.11 18-FEB-14:00 0.00 0.00 0.00
March 0.113067E+12 0.00 421.06 0.113067E+12 0.00 0.00 0.00 0.00 191576.16 20-MAR-18:10 191576.16 20-MAR-18:10 0.00 0.00 0.00
April 0.312352E+12 0.00 658.67 0.312352E+12 0.00 0.00 0.00 0.00 256058.23 14-APR-18:03 256058.23 14-APR-18:03 0.00 0.00 0.00
May 0.407289E+12 0.00 734.83 0.407289E+12 0.00 0.00 0.00 0.00 267662.90 31-MAY-18:20 267662.90 31-MAY-18:20 0.00 0.00 0.00
June 0.517999E+12 0.00 720.00 0.517076E+12 0.00 0.00 0.00 0.00 331934.51 17-JUN-17:17 317522.75 28-JUN-18:40 0.00 0.00 0.00
July 0.601837E+12 0.00 744.00 0.523581E+12 0.00 0.00 0.00 0.00 397546.17 13-JUL-18:03 305650.47 21-JUL-20:10 0.00 0.00 0.00
August 0.587308E+12 0.00 744.00 0.515820E+12 0.00 0.00 0.00 0.00 428459.16 18-AUG-22:00 296813.64 25-AUG-18:20 0.00 0.00 0.00
September 0.539199E+12 0.00 720.00 0.463913E+12 0.00 0.00 0.00 0.00 456570.15 10-SEP-20:40 294506.61 08-SEP-20:10 0.00 0.00 0.00
October 0.274308E+12 0.00 604.50 0.266176E+12 0.00 0.00 0.00 0.00 328698.51 02-OCT-20:00 268286.74 04-OCT-18:15 0.00 0.00 0.00
November 0.118824E+12 0.00 421.79 0.105397E+12 0.00 0.00 0.00 0.00 194134.92 01-NOV-18:04 194134.92 01-NOV-18:04 0.00 0.00 0.00
December 0.554235E+11 0.00 293.76 0.554235E+11 0.00 0.00 0.00 0.00 151356.41 22-DEC-16:08 151356.41 22-DEC-16:08 0.00 0.00 0.00
                               
Annual Sum or Average 0.365713E+13 0.00 6657.47 0.340916E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.254135E+11 0.00 218.50 0.253868E+11 0.00 0.00 0.00 0.00 103488.11   103488.11   0.00 0.00 0.00
Maximum of Months 0.601837E+12 0.00 744.00 0.523581E+12 0.00 0.00 0.00 0.00 456570.15   317522.75   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.673483E+10 0.00 239.17 0.667920E+10 0.00 0.00 0.00 0.00 17033.11 31-JAN-16:01 17033.11 31-JAN-16:01 0.00 0.00 0.00
February 0.173087E+10 0.00 131.50 0.173087E+10 0.00 0.00 0.00 0.00 13753.19 18-FEB-14:00 13753.19 18-FEB-14:00 0.00 0.00 0.00
March 0.788829E+10 0.00 282.00 0.788829E+10 0.00 0.00 0.00 0.00 17335.41 16-MAR-15:01 17335.41 16-MAR-15:01 0.00 0.00 0.00
April 0.209353E+11 0.00 514.83 0.209353E+11 0.00 0.00 0.00 0.00 19381.36 14-APR-15:02 19381.36 14-APR-15:02 0.00 0.00 0.00
May 0.271398E+11 0.00 580.50 0.271398E+11 0.00 0.00 0.00 0.00 19739.01 31-MAY-15:02 19739.01 31-MAY-15:02 0.00 0.00 0.00
June 0.322302E+11 0.00 570.00 0.321956E+11 0.00 0.00 0.00 0.00 23390.50 17-JUN-16:00 21846.18 28-JUN-15:02 0.00 0.00 0.00
July 0.381408E+11 0.00 589.00 0.329353E+11 0.00 0.00 0.00 0.00 30505.29 27-JUL-06:50 21327.50 19-JUL-13:00 0.00 0.00 0.00
August 0.378353E+11 0.00 589.00 0.325800E+11 0.00 0.00 0.00 0.00 34897.84 05-AUG-08:10 21421.42 25-AUG-15:02 0.00 0.00 0.00
September 0.358848E+11 0.00 570.00 0.298955E+11 0.00 0.00 0.00 0.00 38778.16 02-SEP-21:51 20640.11 08-SEP-15:02 0.00 0.00 0.00
October 0.181404E+11 0.00 461.33 0.174558E+11 0.00 0.00 0.00 0.00 28988.59 03-OCT-08:61 20196.64 01-OCT-13:00 0.00 0.00 0.00
November 0.850451E+10 0.00 283.00 0.712220E+10 0.00 0.00 0.00 0.00 24612.65 12-NOV-13:40 17436.07 01-NOV-15:01 0.00 0.00 0.00
December 0.357415E+10 0.00 152.17 0.357415E+10 0.00 0.00 0.00 0.00 15816.12 25-DEC-16:01 15816.12 25-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.238739E+12 0.00 4962.50 0.220132E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.173087E+10 0.00 131.50 0.173087E+10 0.00 0.00 0.00 0.00 13753.19   13753.19   0.00 0.00 0.00
Maximum of Months 0.381408E+11 0.00 589.00 0.329353E+11 0.00 0.00 0.00 0.00 38778.16   21846.18   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.329611E+10 0.00 452.67 0.312237E+10 0.00 0.00 0.00 0.00 15754.45 14-JAN-16:01 15754.45 14-JAN-16:01 0.00 0.00 0.00
February 0.103762E+10 0.00 203.83 0.840036E+09 0.00 0.00 0.00 0.00 14984.97 09-FEB-16:01 14984.97 09-FEB-16:01 0.00 0.00 0.00
March 0.255717E+10 0.00 400.47 0.217631E+10 0.00 0.00 0.00 0.00 15771.97 16-MAR-15:01 15771.97 16-MAR-15:01 0.00 0.00 0.00
April 0.856984E+10 0.00 674.03 0.838302E+10 0.00 0.00 0.00 0.00 15776.38 25-APR-15:02 15776.38 25-APR-15:02 0.00 0.00 0.00
May 0.103449E+11 0.00 713.92 0.102701E+11 0.00 0.00 0.00 0.00 15770.49 10-MAY-18:02 15770.49 10-MAY-18:02 0.00 0.00 0.00
June 0.136647E+11 0.00 704.95 0.127924E+11 0.00 0.00 0.00 0.00 15778.25 22-JUN-08:62 15778.25 22-JUN-08:62 0.00 0.00 0.00
July 0.134399E+11 0.00 724.72 0.990940E+10 0.00 0.00 0.00 0.00 17326.61 27-JUL-08:61 15774.75 05-JUL-18:02 0.00 0.00 0.00
August 0.132283E+11 0.00 722.52 0.946548E+10 0.00 0.00 0.00 0.00 17524.44 04-AUG-08:61 15771.28 25-AUG-18:02 0.00 0.00 0.00
September 0.115249E+11 0.00 694.88 0.777417E+10 0.00 0.00 0.00 0.00 18513.58 04-SEP-08:61 15779.14 28-SEP-15:02 0.00 0.00 0.00
October 0.708136E+10 0.00 621.40 0.587925E+10 0.00 0.00 0.00 0.00 16801.33 03-OCT-08:61 15778.30 20-OCT-15:02 0.00 0.00 0.00
November 0.339622E+10 0.00 464.33 0.279351E+10 0.00 0.00 0.00 0.00 17262.23 12-NOV-16:02 15761.75 20-NOV-16:01 0.00 0.00 0.00
December 0.158942E+10 0.00 277.37 0.158844E+10 0.00 0.00 0.00 0.00 15652.64 25-DEC-16:01 15652.64 25-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.897304E+11 0.00 6655.08 0.749946E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.103762E+10 0.00 203.83 0.840036E+09 0.00 0.00 0.00 0.00 14984.97   14984.97   0.00 0.00 0.00
Maximum of Months 0.136647E+11 0.00 724.72 0.127924E+11 0.00 0.00 0.00 0.00 18513.58   15779.14   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.759514E+09 0.00 156.79 0.712087E+09 0.00 0.00 0.00 0.00 15638.67 14-JAN-16:01 15638.67 14-JAN-16:01 0.00 0.00 0.00
February 0.192908E+09 0.00 58.63 0.157466E+09 0.00 0.00 0.00 0.00 14608.27 28-FEB-16:01 14608.27 28-FEB-16:01 0.00 0.00 0.00
March 0.105003E+10 0.00 205.94 0.863321E+09 0.00 0.00 0.00 0.00 15658.15 16-MAR-15:01 15658.15 16-MAR-15:01 0.00 0.00 0.00
April 0.701342E+10 0.00 577.00 0.686176E+10 0.00 0.00 0.00 0.00 16067.60 26-APR-08:41 16067.60 26-APR-08:41 0.00 0.00 0.00
May 0.970403E+10 0.00 633.44 0.964531E+10 0.00 0.00 0.00 0.00 17330.45 08-MAY-08:61 17330.45 08-MAY-08:61 0.00 0.00 0.00
June 0.135659E+11 0.00 664.53 0.127242E+11 0.00 0.00 0.00 0.00 17448.66 14-JUN-08:61 17448.66 14-JUN-08:61 0.00 0.00 0.00
July 0.132667E+11 0.00 703.94 0.980455E+10 0.00 0.00 0.00 0.00 19507.59 27-JUL-08:11 17896.31 01-JUL-08:61 0.00 0.00 0.00
August 0.122921E+11 0.00 676.72 0.875982E+10 0.00 0.00 0.00 0.00 19587.47 28-AUG-18:31 16732.09 25-AUG-07:31 0.00 0.00 0.00
September 0.992510E+10 0.00 619.60 0.657654E+10 0.00 0.00 0.00 0.00 19965.47 04-SEP-08:51 15663.74 29-SEP-15:02 0.00 0.00 0.00
October 0.446806E+10 0.00 435.56 0.349845E+10 0.00 0.00 0.00 0.00 19474.70 03-OCT-08:61 15663.48 20-OCT-15:02 0.00 0.00 0.00
November 0.104709E+10 0.00 214.59 0.783906E+09 0.00 0.00 0.00 0.00 17360.35 13-NOV-16:01 15647.17 20-NOV-16:01 0.00 0.00 0.00
December 0.229621E+09 0.00 53.96 0.229508E+09 0.00 0.00 0.00 0.00 15538.70 25-DEC-16:01 15538.70 25-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.735145E+11 0.00 5000.70 0.606169E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.192908E+09 0.00 53.96 0.157466E+09 0.00 0.00 0.00 0.00 14608.27   14608.27   0.00 0.00 0.00
Maximum of Months 0.135659E+11 0.00 703.94 0.127242E+11 0.00 0.00 0.00 0.00 19965.47   17896.31   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.428116E+11 0.00 566.17 0.422562E+11 0.00 0.00 0.00 0.00 50051.37 14-JAN-13:50 50051.37 14-JAN-13:50 0.00 0.00 0.00
February 0.137627E+11 0.00 319.57 0.120945E+11 0.00 0.00 0.00 0.00 37257.07 01-FEB-14:20 37257.07 01-FEB-14:20 0.00 0.00 0.00
March 0.166165E+11 0.00 431.13 0.155726E+11 0.00 0.00 0.00 0.00 35158.70 18-MAR-13:50 34509.23 18-MAR-15:03 0.00 0.00 0.00
April 0.404277E+11 0.00 674.53 0.402191E+11 0.00 0.00 0.00 0.00 36751.51 14-APR-13:40 36751.51 14-APR-13:40 0.00 0.00 0.00
May 0.409313E+11 0.00 733.41 0.409313E+11 0.00 0.00 0.00 0.00 29724.55 09-MAY-17:20 29724.55 09-MAY-17:20 0.00 0.00 0.00
June 0.539388E+11 0.00 720.00 0.520781E+11 0.00 0.00 0.00 0.00 37318.23 28-JUN-17:15 37318.23 28-JUN-17:15 0.00 0.00 0.00
July 0.574046E+11 0.00 744.00 0.365001E+11 0.00 0.00 0.00 0.00 36565.36 23-JUL-08:00 32467.50 07-JUL-17:20 0.00 0.00 0.00
August 0.606380E+11 0.00 742.75 0.383410E+11 0.00 0.00 0.00 0.00 44698.93 28-AUG-12:30 42246.51 27-AUG-14:00 0.00 0.00 0.00
September 0.605291E+11 0.00 720.00 0.410281E+11 0.00 0.00 0.00 0.00 49017.14 28-SEP-13:30 48593.34 28-SEP-13:40 0.00 0.00 0.00
October 0.501088E+11 0.00 664.98 0.437793E+11 0.00 0.00 0.00 0.00 50188.51 18-OCT-13:50 50188.51 18-OCT-13:50 0.00 0.00 0.00
November 0.365164E+11 0.00 541.16 0.329734E+11 0.00 0.00 0.00 0.00 52279.83 20-NOV-14:30 52279.83 20-NOV-14:30 0.00 0.00 0.00
December 0.298966E+11 0.00 460.74 0.297814E+11 0.00 0.00 0.00 0.00 49552.87 25-DEC-13:40 49552.87 25-DEC-13:40 0.00 0.00 0.00
                               
Annual Sum or Average 0.503582E+12 0.00 7318.43 0.425555E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.137627E+11 0.00 319.57 0.120945E+11 0.00 0.00 0.00 0.00 29724.55   29724.55   0.00 0.00 0.00
Maximum of Months 0.606380E+11 0.00 744.00 0.520781E+11 0.00 0.00 0.00 0.00 52279.83   52279.83   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.730109E+10 0.00 279.60 0.655732E+10 0.00 0.00 0.00 0.00 91840.99 27-JAN-16:01 91840.99 27-JAN-16:01 0.00 0.00 0.00
February 0.614641E+10 0.00 260.38 0.339814E+10 0.00 0.00 0.00 0.00 83937.34 18-FEB-16:01 82330.78 09-FEB-16:01 0.00 0.00 0.00
March 0.130380E+11 0.00 333.62 0.105506E+11 0.00 0.00 0.00 0.00 94177.33 16-MAR-15:01 94177.33 16-MAR-15:01 0.00 0.00 0.00
April 0.397296E+11 0.00 515.49 0.388675E+11 0.00 0.00 0.00 0.00 94210.62 25-APR-15:02 94210.62 25-APR-15:02 0.00 0.00 0.00
May 0.560950E+11 0.00 596.61 0.558059E+11 0.00 0.00 0.00 0.00 99554.07 20-MAY-08:61 99554.07 20-MAY-08:61 0.00 0.00 0.00
June 0.783339E+11 0.00 646.58 0.730647E+11 0.00 0.00 0.00 0.00 101572.92 11-JUN-08:61 101572.92 11-JUN-08:61 0.00 0.00 0.00
July 0.834699E+11 0.00 680.00 0.625755E+11 0.00 0.00 0.00 0.00 110338.33 27-JUL-08:11 102433.01 01-JUL-08:61 0.00 0.00 0.00
August 0.755523E+11 0.00 652.20 0.539590E+11 0.00 0.00 0.00 0.00 115898.68 28-AUG-18:31 95113.00 26-AUG-07:11 0.00 0.00 0.00
September 0.637333E+11 0.00 588.64 0.431307E+11 0.00 0.00 0.00 0.00 113258.32 04-SEP-08:51 94247.36 29-SEP-08:21 0.00 0.00 0.00
October 0.303180E+11 0.00 454.59 0.243818E+11 0.00 0.00 0.00 0.00 109791.66 03-OCT-08:61 94207.97 06-OCT-15:02 0.00 0.00 0.00
November 0.105451E+11 0.00 287.16 0.749942E+10 0.00 0.00 0.00 0.00 98136.77 13-NOV-16:01 92681.29 20-NOV-16:01 0.00 0.00 0.00
December 0.328537E+10 0.00 161.14 0.324031E+10 0.00 0.00 0.00 0.00 89932.30 25-DEC-16:01 89932.30 25-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.467548E+12 0.00 5456.02 0.383031E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.328537E+10 0.00 161.14 0.324031E+10 0.00 0.00 0.00 0.00 83937.34   82330.78   0.00 0.00 0.00
Maximum of Months 0.834699E+11 0.00 680.00 0.730647E+11 0.00 0.00 0.00 0.00 115898.68   102433.01   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.313128E+10 0.00 460.80 0.295795E+10 0.00 0.00 0.00 0.00 13785.41 14-JAN-16:01 13785.41 14-JAN-16:01 0.00 0.00 0.00
February 0.124973E+10 0.00 263.09 0.940675E+09 0.00 0.00 0.00 0.00 13112.48 09-FEB-16:01 13112.48 09-FEB-16:01 0.00 0.00 0.00
March 0.268518E+10 0.00 454.23 0.223740E+10 0.00 0.00 0.00 0.00 13801.46 16-MAR-15:01 13801.46 16-MAR-15:01 0.00 0.00 0.00
April 0.872733E+10 0.00 698.20 0.855249E+10 0.00 0.00 0.00 0.00 13805.68 25-APR-15:02 13805.68 25-APR-15:02 0.00 0.00 0.00
May 0.107425E+11 0.00 731.40 0.106809E+11 0.00 0.00 0.00 0.00 13800.08 10-MAY-18:02 13800.08 10-MAY-18:02 0.00 0.00 0.00
June 0.140170E+11 0.00 712.86 0.133729E+11 0.00 0.00 0.00 0.00 13806.74 21-JUN-18:02 13806.74 21-JUN-18:02 0.00 0.00 0.00
July 0.143522E+11 0.00 734.03 0.111290E+11 0.00 0.00 0.00 0.00 14177.43 09-JUL-08:61 13804.11 05-JUL-18:02 0.00 0.00 0.00
August 0.139996E+11 0.00 732.38 0.105750E+11 0.00 0.00 0.00 0.00 15227.59 04-AUG-08:61 13806.29 27-AUG-08:61 0.00 0.00 0.00
September 0.119586E+11 0.00 703.89 0.846719E+10 0.00 0.00 0.00 0.00 15763.48 03-SEP-08:61 13806.30 29-SEP-15:02 0.00 0.00 0.00
October 0.738676E+10 0.00 649.06 0.625552E+10 0.00 0.00 0.00 0.00 13806.42 20-OCT-15:02 13806.42 20-OCT-15:02 0.00 0.00 0.00
November 0.312494E+10 0.00 465.42 0.260635E+10 0.00 0.00 0.00 0.00 15582.49 13-NOV-16:01 13792.29 20-NOV-16:01 0.00 0.00 0.00
December 0.160238E+10 0.00 290.00 0.159491E+10 0.00 0.00 0.00 0.00 13696.61 25-DEC-16:01 13696.61 25-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.929774E+11 0.00 6895.37 0.793704E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.124973E+10 0.00 263.09 0.940675E+09 0.00 0.00 0.00 0.00 13112.48   13112.48   0.00 0.00 0.00
Maximum of Months 0.143522E+11 0.00 734.03 0.133729E+11 0.00 0.00 0.00 0.00 15763.48   13806.74   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.722099E+09 0.00 164.68 0.660865E+09 0.00 0.00 0.00 0.00 13690.08 14-JAN-16:01 13690.08 14-JAN-16:01 0.00 0.00 0.00
February 0.355271E+09 0.00 87.11 0.221937E+09 0.00 0.00 0.00 0.00 12429.67 09-FEB-16:01 12429.67 09-FEB-16:01 0.00 0.00 0.00
March 0.124233E+10 0.00 253.60 0.997063E+09 0.00 0.00 0.00 0.00 13707.02 16-MAR-15:01 13707.02 16-MAR-15:01 0.00 0.00 0.00
April 0.697595E+10 0.00 597.19 0.683296E+10 0.00 0.00 0.00 0.00 15795.19 14-APR-08:41 15795.19 14-APR-08:41 0.00 0.00 0.00
May 0.977124E+10 0.00 646.69 0.972326E+10 0.00 0.00 0.00 0.00 17203.91 21-MAY-08:61 17203.91 21-MAY-08:61 0.00 0.00 0.00
June 0.138127E+11 0.00 673.84 0.131743E+11 0.00 0.00 0.00 0.00 17041.83 13-JUN-07:52 17041.83 13-JUN-07:52 0.00 0.00 0.00
July 0.141252E+11 0.00 712.85 0.109503E+11 0.00 0.00 0.00 0.00 17730.22 27-JUL-08:11 17201.16 01-JUL-07:42 0.00 0.00 0.00
August 0.129789E+11 0.00 685.42 0.965962E+10 0.00 0.00 0.00 0.00 17436.54 28-AUG-18:31 15871.20 24-AUG-08:21 0.00 0.00 0.00
September 0.102597E+11 0.00 627.21 0.704191E+10 0.00 0.00 0.00 0.00 18743.75 04-SEP-08:51 14436.23 15-SEP-08:51 0.00 0.00 0.00
October 0.467521E+10 0.00 467.23 0.370896E+10 0.00 0.00 0.00 0.00 17794.70 03-OCT-08:61 15097.24 17-OCT-08:51 0.00 0.00 0.00
November 0.916822E+09 0.00 197.64 0.691117E+09 0.00 0.00 0.00 0.00 15043.34 13-NOV-16:01 14102.75 10-NOV-09:51 0.00 0.00 0.00
December 0.243553E+09 0.00 64.73 0.241943E+09 0.00 0.00 0.00 0.00 13602.85 25-DEC-16:01 13602.85 25-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.760790E+11 0.00 5178.18 0.639042E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.243553E+09 0.00 64.73 0.221937E+09 0.00 0.00 0.00 0.00 12429.67   12429.67   0.00 0.00 0.00
Maximum of Months 0.141252E+11 0.00 712.85 0.131743E+11 0.00 0.00 0.00 0.00 18743.75   17203.91   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.768928E+09 0.00 378.91 0.735741E+09 0.00 0.00 0.00 0.00 4203.09 14-JAN-16:01 4203.09 14-JAN-16:01 0.00 0.00 0.00
February 0.244785E+09 0.00 167.57 0.202265E+09 0.00 0.00 0.00 0.00 3997.80 09-FEB-16:01 3997.80 09-FEB-16:01 0.00 0.00 0.00
March 0.629867E+09 0.00 351.41 0.542883E+09 0.00 0.00 0.00 0.00 4207.78 16-MAR-15:01 4207.78 16-MAR-15:01 0.00 0.00 0.00
April 0.217993E+10 0.00 660.39 0.213141E+10 0.00 0.00 0.00 0.00 4208.97 25-APR-15:02 4208.97 25-APR-15:02 0.00 0.00 0.00
May 0.265007E+10 0.00 712.26 0.263061E+10 0.00 0.00 0.00 0.00 4207.33 10-MAY-18:02 4207.33 10-MAY-18:02 0.00 0.00 0.00
June 0.361201E+10 0.00 704.07 0.337249E+10 0.00 0.00 0.00 0.00 4209.11 04-JUN-18:02 4209.11 04-JUN-18:02 0.00 0.00 0.00
July 0.352819E+10 0.00 724.59 0.259303E+10 0.00 0.00 0.00 0.00 4793.99 27-JUL-08:61 4208.50 05-JUL-18:02 0.00 0.00 0.00
August 0.345140E+10 0.00 721.40 0.246039E+10 0.00 0.00 0.00 0.00 4849.37 04-AUG-08:61 4207.48 25-AUG-18:02 0.00 0.00 0.00
September 0.292631E+10 0.00 692.66 0.194366E+10 0.00 0.00 0.00 0.00 5176.47 04-SEP-08:61 4209.33 29-SEP-15:02 0.00 0.00 0.00
October 0.169627E+10 0.00 578.35 0.139032E+10 0.00 0.00 0.00 0.00 4677.36 03-OCT-08:61 4209.49 20-OCT-15:02 0.00 0.00 0.00
November 0.778248E+09 0.00 395.03 0.648690E+09 0.00 0.00 0.00 0.00 4607.63 12-NOV-16:02 4205.06 20-NOV-16:01 0.00 0.00 0.00
December 0.370822E+09 0.00 226.14 0.370756E+09 0.00 0.00 0.00 0.00 4175.88 25-DEC-16:01 4175.88 25-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.228368E+11 0.00 6312.77 0.190222E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.244785E+09 0.00 167.57 0.202265E+09 0.00 0.00 0.00 0.00 3997.80   3997.80   0.00 0.00 0.00
Maximum of Months 0.361201E+10 0.00 724.59 0.337249E+10 0.00 0.00 0.00 0.00 5176.47   4209.49   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.161627E+09 0.00 105.61 0.155307E+09 0.00 0.00 0.00 0.00 4168.87 14-JAN-16:01 4168.87 14-JAN-16:01 0.00 0.00 0.00
February 40547484.80 0.00 36.21 33477486.24 0.00 0.00 0.00 0.00 3908.96 09-FEB-16:01 3908.96 09-FEB-16:01 0.00 0.00 0.00
March 0.251363E+09 0.00 162.61 0.208248E+09 0.00 0.00 0.00 0.00 4173.98 16-MAR-15:01 4173.98 16-MAR-15:01 0.00 0.00 0.00
April 0.180650E+10 0.00 569.47 0.176549E+10 0.00 0.00 0.00 0.00 4241.85 26-APR-08:41 4241.85 26-APR-08:41 0.00 0.00 0.00
May 0.251760E+10 0.00 635.23 0.250166E+10 0.00 0.00 0.00 0.00 4572.53 08-MAY-08:61 4572.53 08-MAY-08:61 0.00 0.00 0.00
June 0.360752E+10 0.00 664.72 0.337225E+10 0.00 0.00 0.00 0.00 4601.13 14-JUN-08:61 4601.13 14-JUN-08:61 0.00 0.00 0.00
July 0.349350E+10 0.00 704.20 0.257573E+10 0.00 0.00 0.00 0.00 5262.68 27-JUL-08:11 4714.06 01-JUL-08:61 0.00 0.00 0.00
August 0.322769E+10 0.00 677.26 0.228902E+10 0.00 0.00 0.00 0.00 5290.81 28-AUG-18:31 4373.67 24-AUG-08:21 0.00 0.00 0.00
September 0.254267E+10 0.00 619.88 0.166012E+10 0.00 0.00 0.00 0.00 5444.32 04-SEP-08:51 4175.52 29-SEP-15:02 0.00 0.00 0.00
October 0.106801E+10 0.00 397.29 0.820019E+09 0.00 0.00 0.00 0.00 5295.25 03-OCT-08:61 4175.47 20-OCT-15:02 0.00 0.00 0.00
November 0.219824E+09 0.00 152.29 0.168781E+09 0.00 0.00 0.00 0.00 4700.06 13-NOV-16:01 4171.11 20-NOV-16:01 0.00 0.00 0.00
December 48464492.11 0.00 34.80 48464492.11 0.00 0.00 0.00 0.00 4142.19 25-DEC-16:01 4142.19 25-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.189853E+11 0.00 4759.56 0.155986E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 40547484.80 0.00 34.80 33477486.24 0.00 0.00 0.00 0.00 3908.96   3908.96   0.00 0.00 0.00
Maximum of Months 0.360752E+10 0.00 704.20 0.337225E+10 0.00 0.00 0.00 0.00 5444.32   4714.06   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.100092E+11 0.00 614.16 0.962246E+10 0.00 0.00 0.00 0.00 18409.92 14-JAN-16:01 18409.92 14-JAN-16:01 0.00 0.00 0.00
February 0.407910E+10 0.00 384.39 0.324475E+10 0.00 0.00 0.00 0.00 17510.56 09-FEB-16:01 17510.56 09-FEB-16:01 0.00 0.00 0.00
March 0.504670E+10 0.00 498.48 0.423207E+10 0.00 0.00 0.00 0.00 18428.26 16-MAR-15:01 18428.26 16-MAR-15:01 0.00 0.00 0.00
April 0.108396E+11 0.00 670.98 0.105204E+11 0.00 0.00 0.00 0.00 18426.04 12-APR-18:01 18426.04 12-APR-18:01 0.00 0.00 0.00
May 0.114508E+11 0.00 705.99 0.113594E+11 0.00 0.00 0.00 0.00 18425.83 10-MAY-18:02 18425.83 10-MAY-18:02 0.00 0.00 0.00
June 0.151459E+11 0.00 698.48 0.138571E+11 0.00 0.00 0.00 0.00 18428.17 16-JUN-08:61 18428.17 16-JUN-08:61 0.00 0.00 0.00
July 0.166655E+11 0.00 720.50 0.123382E+11 0.00 0.00 0.00 0.00 20777.39 27-JUL-08:61 18427.65 03-JUL-18:02 0.00 0.00 0.00
August 0.172799E+11 0.00 720.01 0.126056E+11 0.00 0.00 0.00 0.00 21167.39 04-AUG-08:61 18427.12 25-AUG-18:02 0.00 0.00 0.00
September 0.165638E+11 0.00 694.79 0.117511E+11 0.00 0.00 0.00 0.00 21926.66 04-SEP-08:61 18427.68 18-SEP-15:02 0.00 0.00 0.00
October 0.125328E+11 0.00 664.76 0.109093E+11 0.00 0.00 0.00 0.00 19559.93 03-OCT-08:61 18418.30 19-OCT-15:01 0.00 0.00 0.00
November 0.882525E+10 0.00 575.96 0.781353E+10 0.00 0.00 0.00 0.00 20178.02 12-NOV-09:02 18416.98 20-NOV-16:01 0.00 0.00 0.00
December 0.730529E+10 0.00 491.27 0.727561E+10 0.00 0.00 0.00 0.00 18287.81 25-DEC-16:01 18287.81 25-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.135744E+12 0.00 7439.76 0.115529E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.407910E+10 0.00 384.39 0.324475E+10 0.00 0.00 0.00 0.00 17510.56   17510.56   0.00 0.00 0.00
Maximum of Months 0.172799E+11 0.00 720.50 0.138571E+11 0.00 0.00 0.00 0.00 21926.66   18428.26   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 835.71 667.64 168.07 1286.65 372.79 0.00 0.00 0.00
February 521.47 349.59 171.87 735.59 344.34 0.00 0.00 0.00
March 431.69 218.75 212.94 662.75 312.36 0.00 0.00 0.00
April 378.88 156.07 222.81 724.38 179.52 0.00 0.00 0.00
May 253.16 44.04 209.12 537.01 121.04 0.00 0.00 0.00
June 214.28 16.35 197.94 596.06 45.88 0.00 0.00 0.00
July 217.14 20.65 196.50 588.53 29.79 0.00 0.00 0.00
August 268.51 75.62 192.88 678.70 39.75 0.00 0.00 0.00
September 381.40 161.20 220.20 813.60 61.93 0.00 0.00 0.00
October 612.22 423.82 188.40 1038.82 223.07 0.00 0.00 0.00
November 719.63 552.71 166.92 1099.17 331.79 0.00 0.00 0.00
December 778.28 616.61 161.67 1150.88 443.46 0.00 0.00 0.00
                 
Annual Sum or Average 467.74 275.23 192.51 826.95 208.29 0.00 0.00 0.00
Minimum of Months 214.28 16.35 161.67 537.01 29.79 0.00 0.00 0.00
Maximum of Months 835.71 667.64 222.81 1286.65 443.46 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2353.32 1880.03 473.29 3576.23 1148.56 0.00 0.00 0.00
February 1468.41 984.43 483.99 2022.75 1092.53 0.00 0.00 0.00
March 1215.60 615.98 599.62 1813.93 985.64 0.00 0.00 0.00
April 1066.89 439.48 627.41 2014.82 542.66 0.00 0.00 0.00
May 712.87 124.01 588.87 1497.02 361.48 0.00 0.00 0.00
June 603.41 46.04 557.38 1681.30 130.27 0.00 0.00 0.00
July 611.46 58.14 553.32 1654.43 89.18 0.00 0.00 0.00
August 756.09 212.94 543.15 1904.22 120.91 0.00 0.00 0.00
September 1074.00 453.93 620.07 2276.49 187.00 0.00 0.00 0.00
October 1723.96 1193.45 530.51 2890.99 682.98 0.00 0.00 0.00
November 2026.44 1556.40 470.05 3049.44 1030.29 0.00 0.00 0.00
December 2191.58 1736.32 455.26 3191.08 1362.92 0.00 0.00 0.00
                 
Annual Sum or Average 1317.12 775.03 542.09 2300.45 642.74 0.00 0.00 0.00
Minimum of Months 603.41 46.04 455.26 1497.02 89.18 0.00 0.00 0.00
Maximum of Months 2353.32 1880.03 627.41 3576.23 1362.92 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 3057.09 2442.27 614.83 4748.49 1497.51 0.00 0.00 0.00
February 1907.55 1278.83 628.73 2690.52 1463.26 0.00 0.00 0.00
March 1579.13 800.19 778.94 2412.22 1317.42 0.00 0.00 0.00
April 1385.95 570.91 815.04 2696.58 710.85 0.00 0.00 0.00
May 926.06 161.09 764.97 2006.00 476.44 0.00 0.00 0.00
June 783.87 59.80 724.06 2259.32 169.47 0.00 0.00 0.00
July 794.32 75.52 718.79 2223.33 114.58 0.00 0.00 0.00
August 982.21 276.63 705.58 2552.23 153.72 0.00 0.00 0.00
September 1395.19 589.68 805.51 3040.86 236.86 0.00 0.00 0.00
October 2239.52 1550.35 689.17 3844.70 891.39 0.00 0.00 0.00
November 2632.46 2021.85 610.62 4046.82 1352.81 0.00 0.00 0.00
December 2846.99 2255.58 591.41 4236.39 1797.28 0.00 0.00 0.00
                 
Annual Sum or Average 1711.02 1006.81 704.21 3066.76 845.95 0.00 0.00 0.00
Minimum of Months 783.87 59.80 591.41 2006.00 114.58 0.00 0.00 0.00
Maximum of Months 3057.09 2442.27 815.04 4748.49 1797.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 165.24 132.00 33.23 259.36 69.03 0.00 0.00 0.00
February 103.10 69.12 33.98 147.49 66.63 0.00 0.00 0.00
March 85.35 43.25 42.10 132.36 60.33 0.00 0.00 0.00
April 74.91 30.86 44.05 149.94 28.26 0.00 0.00 0.00
May 50.05 8.71 41.35 115.89 16.91 0.00 0.00 0.00
June 42.37 3.23 39.14 135.33 4.39 0.00 0.00 0.00
July 42.93 4.08 38.85 135.31 2.73 0.00 0.00 0.00
August 53.09 14.95 38.14 150.63 3.08 0.00 0.00 0.00
September 75.41 31.87 43.54 174.55 5.38 0.00 0.00 0.00
October 121.05 83.80 37.25 212.29 37.09 0.00 0.00 0.00
November 142.28 109.28 33.00 221.39 61.02 0.00 0.00 0.00
December 153.88 121.91 31.97 232.41 85.12 0.00 0.00 0.00
                 
Annual Sum or Average 92.48 54.42 38.06 172.47 36.55 0.00 0.00 0.00
Minimum of Months 42.37 3.23 31.97 115.89 2.73 0.00 0.00 0.00
Maximum of Months 165.24 132.00 44.05 259.36 85.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 127.00 79.12 47.88 187.34 141.79 0.00 0.00 0.00
February 102.87 49.92 52.94 124.91 134.27 0.00 0.00 0.00
March 136.12 65.10 71.02 194.24 115.06 0.00 0.00 0.00
April 208.46 118.98 89.48 371.15 52.46 0.00 0.00 0.00
May 209.22 117.24 91.97 402.35 31.26 0.00 0.00 0.00
June 221.79 130.41 91.37 491.99 7.94 0.00 0.00 0.00
July 161.33 75.18 86.15 385.81 4.98 0.00 0.00 0.00
August 154.44 77.66 76.78 360.89 5.63 0.00 0.00 0.00
September 134.39 56.51 77.89 298.96 10.14 0.00 0.00 0.00
October 138.07 79.18 58.89 237.55 73.99 0.00 0.00 0.00
November 126.39 76.26 50.13 184.26 124.56 0.00 0.00 0.00
December 101.41 57.49 43.91 134.22 175.92 0.00 0.00 0.00
                 
Annual Sum or Average 151.96 82.04 69.93 281.81 72.93 0.00 0.00 0.00
Minimum of Months 101.41 49.92 43.91 124.91 4.98 0.00 0.00 0.00
Maximum of Months 221.79 130.41 91.97 491.99 175.92 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.04 0.00 20.04 19.73 74.94 0.00 0.00 0.00
February 22.83 0.00 22.83 14.59 71.45 0.00 0.00 0.00
March 30.35 0.00 30.35 33.70 63.44 0.00 0.00 0.00
April 37.17 0.55 36.63 69.78 27.81 0.00 0.00 0.00
May 43.60 3.70 39.90 96.38 15.18 0.00 0.00 0.00
June 50.36 9.20 41.15 148.27 3.90 0.00 0.00 0.00
July 43.08 4.63 38.45 133.22 2.47 0.00 0.00 0.00
August 34.66 0.85 33.81 109.14 3.15 0.00 0.00 0.00
September 32.69 0.02 32.67 91.08 5.76 0.00 0.00 0.00
October 25.27 0.00 25.27 44.51 40.55 0.00 0.00 0.00
November 21.06 0.00 21.06 20.19 66.63 0.00 0.00 0.00
December 18.72 0.00 18.72 12.85 92.27 0.00 0.00 0.00
                 
Annual Sum or Average 31.68 1.58 30.10 66.37 38.84 0.00 0.00 0.00
Minimum of Months 18.72 0.00 18.72 12.85 2.47 0.00 0.00 0.00
Maximum of Months 50.36 9.20 41.15 148.27 92.27 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 127.00 79.12 47.88 193.63 138.75 0.00 0.00 0.00
February 102.87 49.92 52.94 129.40 130.85 0.00 0.00 0.00
March 136.12 65.10 71.02 196.65 115.30 0.00 0.00 0.00
April 208.46 118.98 89.48 371.59 53.60 0.00 0.00 0.00
May 209.22 117.24 91.97 400.92 31.73 0.00 0.00 0.00
June 221.79 130.41 91.37 489.98 8.28 0.00 0.00 0.00
July 161.33 75.18 86.15 385.28 5.13 0.00 0.00 0.00
August 154.44 77.66 76.78 361.02 6.18 0.00 0.00 0.00
September 134.39 56.51 77.89 299.62 10.73 0.00 0.00 0.00
October 138.07 79.18 58.89 240.71 74.47 0.00 0.00 0.00
November 126.39 76.26 50.13 189.07 122.73 0.00 0.00 0.00
December 101.41 57.49 43.91 141.09 170.56 0.00 0.00 0.00
                 
Annual Sum or Average 151.96 82.04 69.93 283.92 72.14 0.00 0.00 0.00
Minimum of Months 101.41 49.92 43.91 129.40 5.13 0.00 0.00 0.00
Maximum of Months 221.79 130.41 91.97 489.98 170.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 132.16 105.58 26.58 192.44 80.82 0.00 0.00 0.00
February 82.47 55.29 27.18 105.38 80.93 0.00 0.00 0.00
March 68.27 34.59 33.67 91.69 72.61 0.00 0.00 0.00
April 59.92 24.68 35.24 105.18 41.53 0.00 0.00 0.00
May 40.04 6.96 33.07 76.11 29.10 0.00 0.00 0.00
June 33.89 2.59 31.30 86.29 12.23 0.00 0.00 0.00
July 34.34 3.26 31.07 83.43 9.60 0.00 0.00 0.00
August 42.46 11.96 30.50 98.56 12.92 0.00 0.00 0.00
September 60.32 25.49 34.82 119.50 17.86 0.00 0.00 0.00
October 96.82 67.02 29.79 153.89 50.60 0.00 0.00 0.00
November 113.80 87.41 26.40 162.70 74.19 0.00 0.00 0.00
December 123.08 97.51 25.57 171.31 95.01 0.00 0.00 0.00
                 
Annual Sum or Average 73.97 43.53 30.44 120.69 47.98 0.00 0.00 0.00
Minimum of Months 33.89 2.59 25.57 76.11 9.60 0.00 0.00 0.00
Maximum of Months 132.16 105.58 35.24 192.44 95.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.03 0.00 16.03 16.79 59.40 0.00 0.00 0.00
February 18.27 0.00 18.27 11.78 58.59 0.00 0.00 0.00
March 24.29 0.00 24.28 28.08 50.50 0.00 0.00 0.00
April 29.74 0.44 29.30 60.44 20.30 0.00 0.00 0.00
May 34.89 2.96 31.92 82.56 10.67 0.00 0.00 0.00
June 40.29 7.36 32.93 126.14 2.29 0.00 0.00 0.00
July 34.47 3.70 30.76 113.19 1.55 0.00 0.00 0.00
August 27.73 0.68 27.05 93.65 1.92 0.00 0.00 0.00
September 26.15 0.02 26.14 78.05 3.60 0.00 0.00 0.00
October 20.22 0.00 20.22 38.49 31.00 0.00 0.00 0.00
November 16.85 0.00 16.85 17.28 52.55 0.00 0.00 0.00
December 14.98 0.00 14.98 10.38 74.98 0.00 0.00 0.00
                 
Annual Sum or Average 25.35 1.27 24.08 56.62 30.50 0.00 0.00 0.00
Minimum of Months 14.98 0.00 14.98 10.38 1.55 0.00 0.00 0.00
Maximum of Months 40.29 7.36 32.93 126.14 74.98 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 120.94 75.91 45.03 162.94 128.66 0.00 0.00 0.00
February 120.23 69.17 51.05 144.34 125.73 0.00 0.00 0.00
March 149.29 76.81 72.48 206.49 106.77 0.00 0.00 0.00
April 212.74 126.76 85.99 374.71 47.06 0.00 0.00 0.00
May 220.85 131.04 89.80 420.28 27.45 0.00 0.00 0.00
June 229.78 142.76 87.03 509.16 6.96 0.00 0.00 0.00
July 194.36 109.67 84.69 444.20 4.46 0.00 0.00 0.00
August 184.63 105.48 79.14 412.42 5.40 0.00 0.00 0.00
September 151.29 72.97 78.32 326.89 9.50 0.00 0.00 0.00
October 151.83 92.35 59.47 254.91 68.28 0.00 0.00 0.00
November 116.83 70.11 46.72 156.69 114.47 0.00 0.00 0.00
December 106.72 64.54 42.18 127.22 161.20 0.00 0.00 0.00
                 
Annual Sum or Average 163.49 94.92 68.57 295.75 66.93 0.00 0.00 0.00
Minimum of Months 106.72 64.54 42.18 127.22 4.46 0.00 0.00 0.00
Maximum of Months 229.78 142.76 89.80 509.16 161.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 165.24 132.00 33.23 258.44 68.43 0.00 0.00 0.00
February 103.10 69.12 33.98 145.92 66.65 0.00 0.00 0.00
March 85.35 43.25 42.10 130.71 60.14 0.00 0.00 0.00
April 74.91 30.86 44.05 149.06 28.09 0.00 0.00 0.00
May 50.05 8.71 41.35 114.96 16.70 0.00 0.00 0.00
June 42.37 3.23 39.14 134.63 4.18 0.00 0.00 0.00
July 42.93 4.08 38.85 134.13 2.66 0.00 0.00 0.00
August 53.09 14.95 38.14 149.66 3.06 0.00 0.00 0.00
September 75.41 31.87 43.54 173.89 5.34 0.00 0.00 0.00
October 121.05 83.80 37.25 211.14 36.83 0.00 0.00 0.00
November 142.28 109.28 33.00 220.70 60.34 0.00 0.00 0.00
December 153.88 121.91 31.97 231.32 84.84 0.00 0.00 0.00
                 
Annual Sum or Average 92.48 54.42 38.06 171.44 36.32 0.00 0.00 0.00
Minimum of Months 42.37 3.23 31.97 114.96 2.66 0.00 0.00 0.00
Maximum of Months 165.24 132.00 44.05 258.44 84.84 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.04 0.00 20.04 18.76 73.85 0.00 0.00 0.00
February 22.83 0.00 22.83 13.53 71.77 0.00 0.00 0.00
March 30.35 0.00 30.35 32.12 63.14 0.00 0.00 0.00
April 37.17 0.55 36.63 68.07 27.60 0.00 0.00 0.00
May 43.60 3.70 39.90 94.11 14.94 0.00 0.00 0.00
June 50.36 9.20 41.15 147.17 3.75 0.00 0.00 0.00
July 43.08 4.63 38.45 131.85 2.41 0.00 0.00 0.00
August 34.66 0.85 33.81 107.83 3.14 0.00 0.00 0.00
September 32.69 0.02 32.67 89.98 5.77 0.00 0.00 0.00
October 25.27 0.00 25.27 43.04 40.45 0.00 0.00 0.00
November 21.06 0.00 21.06 19.40 65.46 0.00 0.00 0.00
December 18.72 0.00 18.72 12.08 91.79 0.00 0.00 0.00
                 
Annual Sum or Average 31.68 1.58 30.10 65.07 38.54 0.00 0.00 0.00
Minimum of Months 18.72 0.00 18.72 12.08 2.41 0.00 0.00 0.00
Maximum of Months 50.36 9.20 41.15 147.17 91.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 120.94 75.91 45.03 169.60 124.84 0.00 0.00 0.00
February 120.23 69.17 51.05 149.15 122.22 0.00 0.00 0.00
March 149.29 76.81 72.48 209.04 106.66 0.00 0.00 0.00
April 212.74 126.76 85.99 373.15 47.85 0.00 0.00 0.00
May 220.85 131.04 89.80 415.62 27.62 0.00 0.00 0.00
June 229.78 142.76 87.03 505.78 7.05 0.00 0.00 0.00
July 194.36 109.67 84.69 443.12 4.50 0.00 0.00 0.00
August 184.63 105.48 79.14 411.73 5.84 0.00 0.00 0.00
September 151.29 72.97 78.32 326.27 9.93 0.00 0.00 0.00
October 151.83 92.35 59.47 257.04 68.60 0.00 0.00 0.00
November 116.83 70.11 46.72 161.41 111.63 0.00 0.00 0.00
December 106.72 64.54 42.18 134.16 154.96 0.00 0.00 0.00
                 
Annual Sum or Average 163.49 94.92 68.57 297.05 65.75 0.00 0.00 0.00
Minimum of Months 106.72 64.54 42.18 134.16 4.50 0.00 0.00 0.00
Maximum of Months 229.78 142.76 89.80 505.78 154.96 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 25.38 0.00 25.38 23.46 102.56 0.00 0.00 0.00
February 28.92 0.00 28.92 17.87 96.92 0.00 0.00 0.00
March 38.44 0.00 38.44 43.57 84.16 0.00 0.00 0.00
April 47.08 0.69 46.38 88.76 41.18 0.00 0.00 0.00
May 55.22 4.69 50.53 119.82 25.44 0.00 0.00 0.00
June 63.77 11.65 52.12 181.89 8.20 0.00 0.00 0.00
July 54.55 5.86 48.69 158.74 5.52 0.00 0.00 0.00
August 43.90 1.08 42.82 129.83 7.49 0.00 0.00 0.00
September 41.39 0.03 41.37 108.18 12.93 0.00 0.00 0.00
October 32.01 0.00 32.01 53.35 59.53 0.00 0.00 0.00
November 26.67 0.00 26.67 24.45 92.03 0.00 0.00 0.00
December 23.71 0.00 23.71 14.56 125.18 0.00 0.00 0.00
                 
Annual Sum or Average 40.13 2.00 38.12 80.66 54.93 0.00 0.00 0.00
Minimum of Months 23.71 0.00 23.71 14.56 5.52 0.00 0.00 0.00
Maximum of Months 63.77 11.65 52.12 181.89 125.18 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.36 0.00 9.36 8.65 37.81 0.00 0.00 0.00
February 10.66 0.00 10.66 6.59 35.73 0.00 0.00 0.00
March 14.17 0.00 14.17 16.06 31.02 0.00 0.00 0.00
April 17.35 0.26 17.10 32.72 15.18 0.00 0.00 0.00
May 20.36 1.73 18.63 44.17 9.38 0.00 0.00 0.00
June 23.51 4.30 19.21 67.05 3.02 0.00 0.00 0.00
July 20.11 2.16 17.95 58.52 2.04 0.00 0.00 0.00
August 16.18 0.40 15.78 47.86 2.76 0.00 0.00 0.00
September 15.26 0.01 15.25 39.88 4.77 0.00 0.00 0.00
October 11.80 0.00 11.80 19.67 21.95 0.00 0.00 0.00
November 9.83 0.00 9.83 9.01 33.93 0.00 0.00 0.00
December 8.74 0.00 8.74 5.37 46.15 0.00 0.00 0.00
                 
Annual Sum or Average 14.79 0.74 14.05 29.74 20.25 0.00 0.00 0.00
Minimum of Months 8.74 0.00 8.74 5.37 2.04 0.00 0.00 0.00
Maximum of Months 23.51 4.30 19.21 67.05 46.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.10 61.59 15.51 122.04 34.00 0.00 0.00 0.00
February 48.11 32.25 15.86 69.62 32.47 0.00 0.00 0.00
March 39.82 20.18 19.64 62.68 29.66 0.00 0.00 0.00
April 34.95 14.40 20.56 70.15 15.72 0.00 0.00 0.00
May 23.36 4.06 19.29 53.04 10.51 0.00 0.00 0.00
June 19.77 1.51 18.26 60.55 3.47 0.00 0.00 0.00
July 20.03 1.90 18.13 59.34 2.25 0.00 0.00 0.00
August 24.77 6.98 17.79 67.21 2.92 0.00 0.00 0.00
September 35.19 14.87 20.31 78.80 4.73 0.00 0.00 0.00
October 56.48 39.10 17.38 98.43 20.26 0.00 0.00 0.00
November 66.39 50.99 15.40 104.00 30.57 0.00 0.00 0.00
December 71.80 56.88 14.92 109.45 41.09 0.00 0.00 0.00
                 
Annual Sum or Average 43.15 25.39 17.76 79.70 18.92 0.00 0.00 0.00
Minimum of Months 19.77 1.51 14.92 53.04 2.25 0.00 0.00 0.00
Maximum of Months 77.10 61.59 20.56 122.04 41.09 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 209.26 167.17 42.09 331.24 92.30 0.00 0.00 0.00
February 130.57 87.54 43.04 188.97 88.13 0.00 0.00 0.00
March 108.09 54.77 53.32 170.13 80.50 0.00 0.00 0.00
April 94.87 39.08 55.79 190.39 42.67 0.00 0.00 0.00
May 63.39 11.03 52.36 143.96 28.53 0.00 0.00 0.00
June 53.66 4.09 49.56 164.33 9.42 0.00 0.00 0.00
July 54.37 5.17 49.20 161.07 6.11 0.00 0.00 0.00
August 67.23 18.94 48.30 182.41 7.92 0.00 0.00 0.00
September 95.50 40.36 55.14 213.87 12.83 0.00 0.00 0.00
October 153.30 106.12 47.17 267.16 54.98 0.00 0.00 0.00
November 180.19 138.40 41.80 282.28 82.97 0.00 0.00 0.00
December 194.88 154.40 40.48 297.08 111.54 0.00 0.00 0.00
                 
Annual Sum or Average 117.12 68.92 48.20 216.33 51.35 0.00 0.00 0.00
Minimum of Months 53.66 4.09 40.48 143.96 6.11 0.00 0.00 0.00
Maximum of Months 209.26 167.17 55.79 331.24 111.54 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 165.24 132.00 33.23 258.02 68.25 0.00 0.00 0.00
February 103.10 69.12 33.98 146.57 65.89 0.00 0.00 0.00
March 85.35 43.25 42.10 131.29 59.86 0.00 0.00 0.00
April 74.91 30.86 44.05 148.96 27.43 0.00 0.00 0.00
May 50.05 8.71 41.35 115.79 16.09 0.00 0.00 0.00
June 42.37 3.23 39.14 135.61 3.99 0.00 0.00 0.00
July 42.93 4.08 38.85 135.44 2.55 0.00 0.00 0.00
August 53.09 14.95 38.14 150.52 2.81 0.00 0.00 0.00
September 75.41 31.87 43.54 174.07 4.90 0.00 0.00 0.00
October 121.05 83.80 37.25 211.23 36.09 0.00 0.00 0.00
November 142.28 109.28 33.00 220.17 60.21 0.00 0.00 0.00
December 153.88 121.91 31.97 231.63 84.31 0.00 0.00 0.00
                 
Annual Sum or Average 92.48 54.42 38.06 171.83 35.92 0.00 0.00 0.00
Minimum of Months 42.37 3.23 31.97 115.79 2.55 0.00 0.00 0.00
Maximum of Months 165.24 132.00 44.05 258.02 84.31 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 127.00 79.12 47.88 186.06 139.49 0.00 0.00 0.00
February 102.87 49.92 52.94 123.58 132.28 0.00 0.00 0.00
March 136.12 65.10 71.02 192.45 113.73 0.00 0.00 0.00
April 208.46 118.98 89.48 368.50 50.90 0.00 0.00 0.00
May 209.22 117.24 91.97 400.54 29.84 0.00 0.00 0.00
June 221.79 130.41 91.37 490.33 7.31 0.00 0.00 0.00
July 161.33 75.18 86.15 384.82 4.70 0.00 0.00 0.00
August 154.44 77.66 76.78 359.94 5.23 0.00 0.00 0.00
September 134.39 56.51 77.89 298.16 9.35 0.00 0.00 0.00
October 138.07 79.18 58.89 236.43 71.79 0.00 0.00 0.00
November 126.39 76.26 50.13 182.92 122.41 0.00 0.00 0.00
December 101.41 57.49 43.91 133.39 173.38 0.00 0.00 0.00
                 
Annual Sum or Average 151.96 82.04 69.93 280.44 71.47 0.00 0.00 0.00
Minimum of Months 101.41 49.92 43.91 123.58 4.70 0.00 0.00 0.00
Maximum of Months 221.79 130.41 91.97 490.33 173.38 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.04 0.00 20.04 20.22 73.40 0.00 0.00 0.00
February 22.83 0.00 22.83 14.66 70.24 0.00 0.00 0.00
March 30.35 0.00 30.35 33.58 62.88 0.00 0.00 0.00
April 37.17 0.55 36.63 69.66 27.10 0.00 0.00 0.00
May 43.60 3.70 39.90 96.63 14.51 0.00 0.00 0.00
June 50.36 9.20 41.15 148.39 3.62 0.00 0.00 0.00
July 43.08 4.63 38.45 133.33 2.33 0.00 0.00 0.00
August 34.66 0.85 33.81 109.30 2.94 0.00 0.00 0.00
September 32.69 0.02 32.67 91.36 5.28 0.00 0.00 0.00
October 25.27 0.00 25.27 44.95 39.18 0.00 0.00 0.00
November 21.06 0.00 21.06 20.59 65.20 0.00 0.00 0.00
December 18.72 0.00 18.72 13.32 90.57 0.00 0.00 0.00
                 
Annual Sum or Average 31.68 1.58 30.10 66.58 37.98 0.00 0.00 0.00
Minimum of Months 18.72 0.00 18.72 13.32 2.33 0.00 0.00 0.00
Maximum of Months 50.36 9.20 41.15 148.39 90.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 127.00 79.12 47.88 193.19 135.88 0.00 0.00 0.00
February 102.87 49.92 52.94 128.59 128.55 0.00 0.00 0.00
March 136.12 65.10 71.02 195.03 114.14 0.00 0.00 0.00
April 208.46 118.98 89.48 369.04 52.11 0.00 0.00 0.00
May 209.22 117.24 91.97 399.29 30.14 0.00 0.00 0.00
June 221.79 130.41 91.37 488.35 7.57 0.00 0.00 0.00
July 161.33 75.18 86.15 384.32 4.81 0.00 0.00 0.00
August 154.44 77.66 76.78 360.15 5.72 0.00 0.00 0.00
September 134.39 56.51 77.89 299.00 9.81 0.00 0.00 0.00
October 138.07 79.18 58.89 240.12 71.94 0.00 0.00 0.00
November 126.39 76.26 50.13 188.50 120.06 0.00 0.00 0.00
December 101.41 57.49 43.91 141.12 167.49 0.00 0.00 0.00
                 
Annual Sum or Average 151.96 82.04 69.93 282.90 70.47 0.00 0.00 0.00
Minimum of Months 101.41 49.92 43.91 128.59 4.81 0.00 0.00 0.00
Maximum of Months 221.79 130.41 91.97 488.35 167.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 242.33 193.60 48.74 373.26 103.86 0.00 0.00 0.00
February 151.21 101.37 49.84 210.36 101.03 0.00 0.00 0.00
March 125.18 63.43 61.75 190.01 89.15 0.00 0.00 0.00
April 109.86 45.26 64.61 221.58 38.79 0.00 0.00 0.00
May 73.41 12.77 60.64 175.47 22.00 0.00 0.00 0.00
June 62.14 4.74 57.40 207.54 4.83 0.00 0.00 0.00
July 62.97 5.99 56.98 205.12 3.29 0.00 0.00 0.00
August 77.86 21.93 55.93 226.15 3.68 0.00 0.00 0.00
September 110.60 46.74 63.85 258.03 6.74 0.00 0.00 0.00
October 177.53 122.90 54.63 308.13 53.74 0.00 0.00 0.00
November 208.67 160.27 48.40 318.84 91.22 0.00 0.00 0.00
December 225.68 178.80 46.88 333.09 129.42 0.00 0.00 0.00
                 
Annual Sum or Average 135.63 79.81 55.82 252.65 53.80 0.00 0.00 0.00
Minimum of Months 62.14 4.74 46.88 175.47 3.29 0.00 0.00 0.00
Maximum of Months 242.33 193.60 64.61 373.26 129.42 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 140.27 0.00 140.27 102.53 646.66 0.00 0.00 0.00
February 159.84 0.00 159.84 66.84 653.59 0.00 0.00 0.00
March 212.46 0.01 212.45 191.03 555.18 0.00 0.00 0.00
April 260.20 3.83 256.37 450.88 258.39 0.00 0.00 0.00
May 305.21 25.92 279.29 628.03 155.82 0.00 0.00 0.00
June 352.47 64.40 288.07 978.82 51.99 0.00 0.00 0.00
July 301.52 32.40 269.12 847.53 37.16 0.00 0.00 0.00
August 242.62 5.96 236.66 691.29 51.60 0.00 0.00 0.00
September 228.79 0.14 228.65 575.02 84.78 0.00 0.00 0.00
October 176.90 0.00 176.90 271.82 365.05 0.00 0.00 0.00
November 147.39 0.00 147.39 107.12 584.70 0.00 0.00 0.00
December 131.03 0.00 131.03 56.33 793.96 0.00 0.00 0.00
                 
Annual Sum or Average 221.78 11.08 210.70 415.54 351.96 0.00 0.00 0.00
Minimum of Months 131.03 0.00 131.03 56.33 37.16 0.00 0.00 0.00
Maximum of Months 352.47 64.40 288.07 978.82 793.96 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 140.27 0.00 140.27 93.55 665.50 0.00 0.00 0.00
February 159.84 0.00 159.84 59.15 677.47 0.00 0.00 0.00
March 212.46 0.01 212.45 179.36 572.09 0.00 0.00 0.00
April 260.20 3.83 256.37 441.30 266.18 0.00 0.00 0.00
May 305.21 25.92 279.29 618.39 160.84 0.00 0.00 0.00
June 352.47 64.40 288.07 968.38 54.34 0.00 0.00 0.00
July 301.52 32.40 269.12 836.95 39.37 0.00 0.00 0.00
August 242.62 5.96 236.66 681.51 54.89 0.00 0.00 0.00
September 228.79 0.14 228.65 565.98 89.41 0.00 0.00 0.00
October 176.90 0.00 176.90 262.99 376.37 0.00 0.00 0.00
November 147.39 0.00 147.39 98.52 602.90 0.00 0.00 0.00
December 131.03 0.00 131.03 49.39 818.10 0.00 0.00 0.00
                 
Annual Sum or Average 221.78 11.08 210.70 406.21 363.44 0.00 0.00 0.00
Minimum of Months 131.03 0.00 131.03 49.39 39.37 0.00 0.00 0.00
Maximum of Months 352.47 64.40 288.07 968.38 818.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.04 0.00 20.04 22.33 85.60 0.00 0.00 0.00
February 22.83 0.00 22.83 14.88 85.95 0.00 0.00 0.00
March 30.35 0.00 30.35 36.96 75.37 0.00 0.00 0.00
April 37.17 0.55 36.63 80.34 36.83 0.00 0.00 0.00
May 43.60 3.70 39.90 108.83 24.55 0.00 0.00 0.00
June 50.36 9.20 41.15 159.64 9.82 0.00 0.00 0.00
July 43.08 4.63 38.45 140.45 7.25 0.00 0.00 0.00
August 34.66 0.85 33.81 118.20 9.25 0.00 0.00 0.00
September 32.69 0.02 32.67 100.99 13.72 0.00 0.00 0.00
October 25.27 0.00 25.27 51.19 49.67 0.00 0.00 0.00
November 21.06 0.00 21.06 23.07 77.00 0.00 0.00 0.00
December 18.72 0.00 18.72 13.89 103.94 0.00 0.00 0.00
                 
Annual Sum or Average 31.68 1.58 30.10 72.84 48.09 0.00 0.00 0.00
Minimum of Months 18.72 0.00 18.72 13.89 7.25 0.00 0.00 0.00
Maximum of Months 50.36 9.20 41.15 159.64 103.94 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 241.87 151.81 90.06 353.16 293.50 0.00 0.00 0.00
February 240.43 138.34 102.10 304.55 297.78 0.00 0.00 0.00
March 298.56 153.60 144.96 436.63 259.94 0.00 0.00 0.00
April 425.45 253.49 171.96 794.48 132.35 0.00 0.00 0.00
May 441.66 262.07 179.60 885.88 91.28 0.00 0.00 0.00
June 459.53 285.49 174.04 1056.38 36.76 0.00 0.00 0.00
July 388.70 219.32 169.38 916.92 27.03 0.00 0.00 0.00
August 369.23 210.95 158.27 860.55 34.62 0.00 0.00 0.00
September 302.56 145.93 156.63 692.99 50.64 0.00 0.00 0.00
October 303.63 184.69 118.94 546.92 173.30 0.00 0.00 0.00
November 233.65 140.21 93.44 337.94 266.87 0.00 0.00 0.00
December 213.43 129.08 84.35 275.99 355.19 0.00 0.00 0.00
                 
Annual Sum or Average 326.95 189.82 137.13 623.39 167.72 0.00 0.00 0.00
Minimum of Months 213.43 129.08 84.35 275.99 27.03 0.00 0.00 0.00
Maximum of Months 459.53 285.49 179.60 1056.38 355.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 165.24 132.00 33.23 267.36 78.29 0.00 0.00 0.00
February 103.10 69.12 33.98 151.33 78.93 0.00 0.00 0.00
March 85.35 43.25 42.10 137.68 72.57 0.00 0.00 0.00
April 74.91 30.86 44.05 160.66 37.92 0.00 0.00 0.00
May 50.05 8.71 41.35 127.10 26.32 0.00 0.00 0.00
June 42.37 3.23 39.14 145.19 10.35 0.00 0.00 0.00
July 42.93 4.08 38.85 142.27 7.53 0.00 0.00 0.00
August 53.09 14.95 38.14 159.79 9.36 0.00 0.00 0.00
September 75.41 31.87 43.54 184.69 13.67 0.00 0.00 0.00
October 121.05 83.80 37.25 221.64 46.61 0.00 0.00 0.00
November 142.28 109.28 33.00 228.76 70.72 0.00 0.00 0.00
December 153.88 121.91 31.97 239.11 93.98 0.00 0.00 0.00
                 
Annual Sum or Average 92.48 54.42 38.06 180.71 45.38 0.00 0.00 0.00
Minimum of Months 42.37 3.23 31.97 127.10 7.53 0.00 0.00 0.00
Maximum of Months 165.24 132.00 44.05 267.36 93.98 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 25.38 0.00 25.38 21.50 102.76 0.00 0.00 0.00
February 28.92 0.00 28.92 15.67 98.84 0.00 0.00 0.00
March 38.44 0.00 38.44 40.61 85.56 0.00 0.00 0.00
April 47.08 0.69 46.38 84.32 42.46 0.00 0.00 0.00
May 55.22 4.69 50.53 115.65 26.38 0.00 0.00 0.00
June 63.77 11.65 52.12 177.46 8.79 0.00 0.00 0.00
July 54.55 5.86 48.69 153.63 6.14 0.00 0.00 0.00
August 43.90 1.08 42.82 125.17 8.40 0.00 0.00 0.00
September 41.39 0.03 41.37 104.25 14.05 0.00 0.00 0.00
October 32.01 0.00 32.01 51.22 58.91 0.00 0.00 0.00
November 26.67 0.00 26.67 22.56 91.93 0.00 0.00 0.00
December 23.71 0.00 23.71 12.83 126.30 0.00 0.00 0.00
                 
Annual Sum or Average 40.13 2.00 38.12 77.36 55.71 0.00 0.00 0.00
Minimum of Months 23.71 0.00 23.71 12.83 6.14 0.00 0.00 0.00
Maximum of Months 63.77 11.65 52.12 177.46 126.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.71 0.00 22.71 19.24 91.93 0.00 0.00 0.00
February 25.87 0.00 25.87 14.02 88.44 0.00 0.00 0.00
March 34.39 0.00 34.39 36.34 76.55 0.00 0.00 0.00
April 42.12 0.62 41.50 75.45 37.99 0.00 0.00 0.00
May 49.41 4.20 45.21 103.48 23.61 0.00 0.00 0.00
June 57.06 10.43 46.63 158.78 7.86 0.00 0.00 0.00
July 48.81 5.24 43.56 137.45 5.49 0.00 0.00 0.00
August 39.27 0.96 38.31 111.99 7.52 0.00 0.00 0.00
September 37.04 0.02 37.01 93.27 12.57 0.00 0.00 0.00
October 28.64 0.00 28.64 45.83 52.71 0.00 0.00 0.00
November 23.86 0.00 23.86 20.18 82.25 0.00 0.00 0.00
December 21.21 0.00 21.21 11.48 112.98 0.00 0.00 0.00
                 
Annual Sum or Average 35.90 1.79 34.11 69.21 49.84 0.00 0.00 0.00
Minimum of Months 21.21 0.00 21.21 11.48 5.49 0.00 0.00 0.00
Maximum of Months 57.06 10.43 46.63 158.78 112.98 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 616.87 492.81 124.06 964.36 273.49 0.00 0.00 0.00
February 384.91 258.05 126.87 546.08 265.55 0.00 0.00 0.00
March 318.65 161.47 157.18 489.01 242.28 0.00 0.00 0.00
April 279.66 115.20 164.46 545.30 129.69 0.00 0.00 0.00
May 186.87 32.51 154.36 411.51 86.79 0.00 0.00 0.00
June 158.17 12.07 146.11 472.04 29.37 0.00 0.00 0.00
July 160.28 15.24 145.04 459.71 19.76 0.00 0.00 0.00
August 198.20 55.82 142.38 523.02 25.93 0.00 0.00 0.00
September 281.53 118.99 162.54 616.30 40.93 0.00 0.00 0.00
October 451.90 312.84 139.06 776.75 161.03 0.00 0.00 0.00
November 531.19 407.98 123.21 821.29 245.23 0.00 0.00 0.00
December 574.48 455.14 119.34 864.81 332.03 0.00 0.00 0.00
                 
Annual Sum or Average 345.26 203.16 142.10 624.94 153.90 0.00 0.00 0.00
Minimum of Months 158.17 12.07 119.34 411.51 19.76 0.00 0.00 0.00
Maximum of Months 616.87 492.81 164.46 964.36 332.03 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.223838E+10 0.178821E+10 0.450171E+09 0.344615E+10 0.998473E+09
February 0.126153E+10 0.845731E+09 0.415798E+09 0.177955E+10 0.833035E+09
March 0.115623E+10 0.585894E+09 0.570335E+09 0.177511E+10 0.836636E+09
April 0.982044E+09 0.404532E+09 0.577512E+09 0.187759E+10 0.465311E+09
May 0.678057E+09 0.117952E+09 0.560105E+09 0.143832E+10 0.324184E+09
June 0.555427E+09 42376069.35 0.513050E+09 0.154499E+10 0.118922E+09
July 0.581591E+09 55297824.35 0.526293E+09 0.157633E+10 79792522.46
August 0.719166E+09 0.202544E+09 0.516622E+09 0.181783E+10 0.106469E+09
September 0.988595E+09 0.417832E+09 0.570763E+09 0.210885E+10 0.160522E+09
October 0.163976E+10 0.113516E+10 0.504604E+09 0.278237E+10 0.597458E+09
November 0.186529E+10 0.143263E+10 0.432667E+09 0.284904E+10 0.860010E+09
December 0.208454E+10 0.165152E+10 0.433026E+09 0.308252E+10 0.118777E+10
           
Annual Sum or Average 0.147506E+11 0.867966E+10 0.607095E+10 0.260786E+11 0.656858E+10
Minimum of Months 0.555427E+09 42376069.35 0.415798E+09 0.143832E+10 79792522.46
Maximum of Months 0.223838E+10 0.178821E+10 0.577512E+09 0.344615E+10 0.118777E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.630312E+10 0.503547E+10 0.126765E+10 0.957856E+10 0.307630E+10
February 0.355238E+10 0.238152E+10 0.117086E+10 0.489343E+10 0.264305E+10
March 0.325586E+10 0.164984E+10 0.160603E+10 0.485843E+10 0.263994E+10
April 0.276537E+10 0.113914E+10 0.162624E+10 0.522241E+10 0.140659E+10
May 0.190936E+10 0.332145E+09 0.157722E+10 0.400961E+10 0.968175E+09
June 0.156404E+10 0.119328E+09 0.144472E+10 0.435793E+10 0.337671E+09
July 0.163772E+10 0.155715E+09 0.148201E+10 0.443123E+10 0.238849E+09
August 0.202512E+10 0.570351E+09 0.145477E+10 0.510027E+10 0.323834E+09
September 0.278382E+10 0.117659E+10 0.160723E+10 0.590065E+10 0.484691E+09
October 0.461746E+10 0.319653E+10 0.142093E+10 0.774322E+10 0.182929E+10
November 0.525254E+10 0.403418E+10 0.121836E+10 0.790414E+10 0.267051E+10
December 0.586993E+10 0.465056E+10 0.121937E+10 0.854699E+10 0.365044E+10
           
Annual Sum or Average 0.415367E+11 0.244414E+11 0.170954E+11 0.725469E+11 0.202693E+11
Minimum of Months 0.156404E+10 0.119328E+09 0.117086E+10 0.400961E+10 0.238849E+09
Maximum of Months 0.630312E+10 0.503547E+10 0.162624E+10 0.957856E+10 0.365044E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.818812E+10 0.654136E+10 0.164675E+10 0.127184E+11 0.401093E+10
February 0.461475E+10 0.309374E+10 0.152101E+10 0.650890E+10 0.353992E+10
March 0.422955E+10 0.214323E+10 0.208632E+10 0.646088E+10 0.352858E+10
April 0.359238E+10 0.147980E+10 0.211257E+10 0.698953E+10 0.184253E+10
May 0.248037E+10 0.431476E+09 0.204890E+10 0.537288E+10 0.127611E+10
June 0.203178E+10 0.155014E+09 0.187677E+10 0.585616E+10 0.439275E+09
July 0.212749E+10 0.202283E+09 0.192521E+10 0.595496E+10 0.306900E+09
August 0.263075E+10 0.740919E+09 0.188983E+10 0.683589E+10 0.411725E+09
September 0.361634E+10 0.152845E+10 0.208788E+10 0.788192E+10 0.613953E+09
October 0.599834E+10 0.415247E+10 0.184587E+10 0.102976E+11 0.238749E+10
November 0.682335E+10 0.524063E+10 0.158272E+10 0.104893E+11 0.350648E+10
December 0.762538E+10 0.604134E+10 0.158404E+10 0.113468E+11 0.481384E+10
           
Annual Sum or Average 0.539586E+11 0.317507E+11 0.222079E+11 0.967132E+11 0.266777E+11
Minimum of Months 0.203178E+10 0.155014E+09 0.152101E+10 0.537288E+10 0.306900E+09
Maximum of Months 0.818812E+10 0.654136E+10 0.211257E+10 0.127184E+11 0.481384E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.442566E+09 0.353559E+09 89007348.67 0.694665E+09 0.184881E+09
February 0.249427E+09 0.167216E+09 82211105.16 0.356818E+09 0.161198E+09
March 0.228607E+09 0.115841E+09 0.112766E+09 0.354505E+09 0.161594E+09
April 0.194169E+09 79982898.78 0.114186E+09 0.388644E+09 73247186.25
May 0.134065E+09 23321164.89 0.110744E+09 0.310398E+09 45293818.10
June 0.109819E+09 8378476.71 0.101441E+09 0.350777E+09 11386945.92
July 0.114992E+09 10933329.61 0.104059E+09 0.362408E+09 7304744.41
August 0.142193E+09 40046470.60 0.102146E+09 0.403453E+09 8237695.84
September 0.195463E+09 82612529.72 0.112851E+09 0.452429E+09 13955623.17
October 0.324210E+09 0.224440E+09 99769849.61 0.568600E+09 99354615.45
November 0.368801E+09 0.283255E+09 85546508.11 0.573844E+09 0.158162E+09
December 0.412151E+09 0.326533E+09 85617432.54 0.622491E+09 0.227984E+09
           
Annual Sum or Average 0.291646E+10 0.171612E+10 0.120034E+10 0.543903E+10 0.115260E+10
Minimum of Months 0.109819E+09 8378476.71 82211105.16 0.310398E+09 7304744.41
Maximum of Months 0.442566E+09 0.353559E+09 0.114186E+09 0.694665E+09 0.227984E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.340154E+09 0.211926E+09 0.128229E+09 0.501769E+09 0.379772E+09
February 0.248858E+09 0.120775E+09 0.128083E+09 0.302176E+09 0.324832E+09
March 0.364588E+09 0.174372E+09 0.190216E+09 0.520244E+09 0.308182E+09
April 0.540336E+09 0.308393E+09 0.231943E+09 0.962031E+09 0.135966E+09
May 0.560366E+09 0.314023E+09 0.246343E+09 0.107765E+10 83732692.12
June 0.574867E+09 0.338034E+09 0.236833E+09 0.127524E+10 20581844.20
July 0.432114E+09 0.201359E+09 0.230755E+09 0.103337E+10 13351401.88
August 0.413642E+09 0.208000E+09 0.205642E+09 0.966597E+09 15089462.75
September 0.348351E+09 0.146469E+09 0.201882E+09 0.774892E+09 26284509.98
October 0.369811E+09 0.212073E+09 0.157738E+09 0.636244E+09 0.198176E+09
November 0.327596E+09 0.197665E+09 0.129932E+09 0.477609E+09 0.322863E+09
December 0.271608E+09 0.153993E+09 0.117616E+09 0.359485E+09 0.471178E+09
           
Annual Sum or Average 0.479229E+10 0.258708E+10 0.220521E+10 0.888730E+10 0.230001E+10
Minimum of Months 0.248858E+09 0.120775E+09 0.117616E+09 0.302176E+09 13351401.88
Maximum of Months 0.574867E+09 0.338034E+09 0.246343E+09 0.127524E+10 0.471178E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53674072.02 0.00 53674072.02 52837478.77 0.200728E+09
February 55241433.50 0.00 55241433.50 35291653.23 0.172848E+09
March 81295770.76 3216.16 81292554.60 90274098.04 0.169930E+09
April 96350800.51 1418628.78 94932171.74 0.180864E+09 72079428.85
May 0.116786E+09 9916509.70 0.106870E+09 0.258132E+09 40648567.08
June 0.130521E+09 23848337.92 0.106672E+09 0.384307E+09 10110829.60
July 0.115375E+09 12397170.40 0.102978E+09 0.356825E+09 6602779.74
August 92836668.46 2279405.50 90557262.96 0.292315E+09 8438969.16
September 84720382.40 52432.38 84667950.02 0.236075E+09 14923324.96
October 67690153.51 0.00 67690153.51 0.119222E+09 0.108606E+09
November 54578999.93 0.00 54578999.93 52320865.40 0.172696E+09
December 50136496.34 0.00 50136496.34 34429785.83 0.247144E+09
           
Annual Sum or Average 0.999207E+09 49915700.83 0.949291E+09 0.209289E+10 0.122476E+10
Minimum of Months 50136496.34 0.00 50136496.34 34429785.83 6602779.74
Maximum of Months 0.130521E+09 23848337.92 0.106870E+09 0.384307E+09 0.247144E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.340154E+09 0.211926E+09 0.128229E+09 0.518625E+09 0.371637E+09
February 0.248858E+09 0.120775E+09 0.128083E+09 0.313036E+09 0.316558E+09
March 0.364588E+09 0.174372E+09 0.190216E+09 0.526716E+09 0.308824E+09
April 0.540336E+09 0.308393E+09 0.231943E+09 0.963153E+09 0.138926E+09
May 0.560366E+09 0.314023E+09 0.246343E+09 0.107382E+10 84987211.56
June 0.574867E+09 0.338034E+09 0.236833E+09 0.127002E+10 21453394.63
July 0.432114E+09 0.201359E+09 0.230755E+09 0.103193E+10 13729523.86
August 0.413642E+09 0.208000E+09 0.205642E+09 0.966962E+09 16549047.55
September 0.348351E+09 0.146469E+09 0.201882E+09 0.776604E+09 27815376.19
October 0.369811E+09 0.212073E+09 0.157738E+09 0.644705E+09 0.199447E+09
November 0.327596E+09 0.197665E+09 0.129932E+09 0.490062E+09 0.318105E+09
December 0.271608E+09 0.153993E+09 0.117616E+09 0.377905E+09 0.456832E+09
           
Annual Sum or Average 0.479229E+10 0.258708E+10 0.220521E+10 0.895355E+10 0.227486E+10
Minimum of Months 0.248858E+09 0.120775E+09 0.117616E+09 0.313036E+09 13729523.86
Maximum of Months 0.574867E+09 0.338034E+09 0.246343E+09 0.127002E+10 0.456832E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.353983E+09 0.282791E+09 71191720.82 0.515427E+09 0.216473E+09
February 0.199502E+09 0.133746E+09 65755807.07 0.254931E+09 0.195788E+09
March 0.182850E+09 92654621.17 90194909.73 0.245587E+09 0.194482E+09
April 0.155304E+09 63973596.40 91330373.15 0.272617E+09 0.107637E+09
May 0.107231E+09 18653222.29 88577606.46 0.203861E+09 77940440.26
June 87837819.98 6701448.63 81136371.35 0.223671E+09 31694479.29
July 91975290.32 8744924.55 83230365.76 0.223455E+09 25718572.16
August 0.113732E+09 32030806.41 81700800.92 0.263983E+09 34614846.93
September 0.156339E+09 66076882.86 90262586.66 0.309741E+09 46291136.88
October 0.259316E+09 0.179516E+09 79800009.62 0.412189E+09 0.135520E+09
November 0.294982E+09 0.226559E+09 68423598.87 0.421723E+09 0.192298E+09
December 0.329655E+09 0.261175E+09 68480327.14 0.458834E+09 0.254488E+09
           
Annual Sum or Average 0.233271E+10 0.137262E+10 0.960084E+09 0.380602E+10 0.151294E+10
Minimum of Months 87837819.98 6701448.63 65755807.07 0.203861E+09 25718572.16
Maximum of Months 0.353983E+09 0.282791E+09 91330373.15 0.515427E+09 0.254488E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 42944949.46 0.00 42944949.46 44969283.45 0.159105E+09
February 44199004.85 0.00 44199004.85 28505234.56 0.141751E+09
March 65045237.58 2573.27 65042664.31 75209227.30 0.135265E+09
April 77090857.89 1135053.46 75955804.43 0.156673E+09 52622517.15
May 93441433.49 7934259.35 85507174.14 0.221138E+09 28578151.11
June 0.104430E+09 19081199.32 85349110.47 0.326954E+09 5932446.51
July 92312481.83 9919050.97 82393430.86 0.303174E+09 4151725.71
August 74279179.59 1823766.12 72455413.47 0.250834E+09 5135567.25
September 67785290.05 41951.47 67743338.59 0.202303E+09 9337060.59
October 54159300.98 0.00 54159300.98 0.103089E+09 83022949.90
November 43668987.75 0.00 43668987.75 44793566.67 0.136219E+09
December 40114513.77 0.00 40114513.77 27791154.22 0.200822E+09
           
Annual Sum or Average 0.799472E+09 39937853.95 0.759534E+09 0.178543E+10 0.961943E+09
Minimum of Months 40114513.77 0.00 40114513.77 27791154.22 4151725.71
Maximum of Months 0.104430E+09 19081199.32 85507174.14 0.326954E+09 0.200822E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.323939E+09 0.203319E+09 0.120620E+09 0.436421E+09 0.344600E+09
February 0.290851E+09 0.167343E+09 0.123508E+09 0.349189E+09 0.304168E+09
March 0.399855E+09 0.205717E+09 0.194139E+09 0.553071E+09 0.285986E+09
April 0.551427E+09 0.328551E+09 0.222876E+09 0.971257E+09 0.121987E+09
May 0.591518E+09 0.350985E+09 0.240533E+09 0.112567E+10 73532071.19
June 0.595597E+09 0.370022E+09 0.225575E+09 0.131975E+10 18034708.24
July 0.520577E+09 0.293732E+09 0.226845E+09 0.118975E+10 11949007.10
August 0.494504E+09 0.282527E+09 0.211977E+09 0.110463E+10 14468939.71
September 0.392148E+09 0.189135E+09 0.203013E+09 0.847312E+09 24615420.31
October 0.406651E+09 0.247359E+09 0.159292E+09 0.682747E+09 0.182885E+09
November 0.302834E+09 0.181731E+09 0.121103E+09 0.406134E+09 0.296694E+09
December 0.285842E+09 0.172873E+09 0.112970E+09 0.340746E+09 0.431761E+09
           
Annual Sum or Average 0.515574E+10 0.299329E+10 0.216245E+10 0.932669E+10 0.211068E+10
Minimum of Months 0.285842E+09 0.167343E+09 0.112970E+09 0.340746E+09 11949007.10
Maximum of Months 0.595597E+09 0.370022E+09 0.240533E+09 0.131975E+10 0.431761E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.442566E+09 0.353559E+09 89007348.67 0.692219E+09 0.183283E+09
February 0.249427E+09 0.167216E+09 82211105.16 0.353006E+09 0.161237E+09
March 0.228607E+09 0.115841E+09 0.112766E+09 0.350088E+09 0.161067E+09
April 0.194169E+09 79982898.78 0.114186E+09 0.386370E+09 72805465.95
May 0.134065E+09 23321164.89 0.110744E+09 0.307903E+09 44720205.63
June 0.109819E+09 8378476.71 0.101441E+09 0.348959E+09 10844433.77
July 0.114992E+09 10933329.61 0.104059E+09 0.359241E+09 7130579.91
August 0.142193E+09 40046470.60 0.102146E+09 0.400854E+09 8203992.83
September 0.195463E+09 82612529.72 0.112851E+09 0.450719E+09 13832082.06
October 0.324210E+09 0.224440E+09 99769849.61 0.565506E+09 98642573.21
November 0.368801E+09 0.283255E+09 85546508.11 0.572045E+09 0.156399E+09
December 0.412151E+09 0.326533E+09 85617432.54 0.619576E+09 0.227241E+09
           
Annual Sum or Average 0.291646E+10 0.171612E+10 0.120034E+10 0.540649E+10 0.114541E+10
Minimum of Months 0.109819E+09 8378476.71 82211105.16 0.307903E+09 7130579.91
Maximum of Months 0.442566E+09 0.353559E+09 0.114186E+09 0.692219E+09 0.227241E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53674072.02 0.00 53674072.02 50248873.00 0.197806E+09
February 55241433.50 0.00 55241433.50 32728258.72 0.173626E+09
March 81295770.76 3216.16 81292554.60 86040357.35 0.169105E+09
April 96350800.51 1418628.78 94932171.74 0.176433E+09 71530154.34
May 0.116786E+09 9916509.70 0.106870E+09 0.252074E+09 40013865.83
June 0.130521E+09 23848337.92 0.106672E+09 0.381462E+09 9718777.43
July 0.115375E+09 12397170.40 0.102978E+09 0.353157E+09 6462275.36
August 92836668.46 2279405.50 90557262.96 0.288802E+09 8421278.39
September 84720382.40 52432.38 84667950.02 0.233222E+09 14957815.04
October 67690153.51 0.00 67690153.51 0.115269E+09 0.108331E+09
November 54578999.93 0.00 54578999.93 50293085.47 0.169665E+09
December 50136496.34 0.00 50136496.34 32349607.32 0.245849E+09
           
Annual Sum or Average 0.999207E+09 49915700.83 0.949291E+09 0.205208E+10 0.121549E+10
Minimum of Months 50136496.34 0.00 50136496.34 32349607.32 6462275.36
Maximum of Months 0.130521E+09 23848337.92 0.106870E+09 0.381462E+09 0.245849E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.323939E+09 0.203319E+09 0.120620E+09 0.454268E+09 0.334381E+09
February 0.290851E+09 0.167343E+09 0.123508E+09 0.360825E+09 0.295667E+09
March 0.399855E+09 0.205717E+09 0.194139E+09 0.559891E+09 0.285675E+09
April 0.551427E+09 0.328551E+09 0.222876E+09 0.967215E+09 0.124040E+09
May 0.591518E+09 0.350985E+09 0.240533E+09 0.111321E+10 73970729.55
June 0.595597E+09 0.370022E+09 0.225575E+09 0.131098E+10 18278181.01
July 0.520577E+09 0.293732E+09 0.226845E+09 0.118685E+10 12041891.72
August 0.494504E+09 0.282527E+09 0.211977E+09 0.110279E+10 15645937.59
September 0.392148E+09 0.189135E+09 0.203013E+09 0.845692E+09 25747950.90
October 0.406651E+09 0.247359E+09 0.159292E+09 0.688455E+09 0.183725E+09
November 0.302834E+09 0.181731E+09 0.121103E+09 0.418379E+09 0.289343E+09
December 0.285842E+09 0.172873E+09 0.112970E+09 0.359329E+09 0.415038E+09
           
Annual Sum or Average 0.515574E+10 0.299329E+10 0.216245E+10 0.936788E+10 0.207355E+10
Minimum of Months 0.285842E+09 0.167343E+09 0.112970E+09 0.359329E+09 12041891.72
Maximum of Months 0.595597E+09 0.370022E+09 0.240533E+09 0.131098E+10 0.415038E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 67974825.56 0.00 67974825.56 62835363.54 0.274683E+09
February 69959789.98 0.00 69959789.98 43222815.33 0.234458E+09
March 0.102956E+09 4073.06 0.102952E+09 0.116707E+09 0.225405E+09
April 0.122022E+09 1796603.83 0.120226E+09 0.230070E+09 0.106729E+09
May 0.147902E+09 12558633.84 0.135344E+09 0.320933E+09 68143526.67
June 0.165296E+09 30202415.22 0.135094E+09 0.471455E+09 21260307.29
July 0.146116E+09 15700234.09 0.130415E+09 0.425178E+09 14788985.41
August 0.117572E+09 2886723.24 0.114685E+09 0.347744E+09 20055893.45
September 0.107293E+09 66402.30 0.107227E+09 0.280393E+09 33505536.18
October 85725308.41 0.00 85725308.41 0.142896E+09 0.159454E+09
November 69120859.66 0.00 69120859.66 63372232.06 0.238541E+09
December 63494709.17 0.00 63494709.17 38989201.31 0.335288E+09
           
Annual Sum or Average 0.126543E+10 63215085.59 0.120222E+10 0.254380E+10 0.173231E+10
Minimum of Months 63494709.17 0.00 63494709.17 38989201.31 14788985.41
Maximum of Months 0.165296E+09 30202415.22 0.135344E+09 0.471455E+09 0.335288E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 25058335.32 0.00 25058335.32 23163716.81 0.101260E+09
February 25790075.39 0.00 25790075.39 15933719.45 86430812.91
March 37953831.47 1501.50 37952329.97 43023005.56 83093625.28
April 44982438.94 662302.56 44320136.38 84813246.62 39344756.43
May 54522983.56 4629632.44 49893351.11 0.118309E+09 25120525.53
June 60934981.96 11133860.83 49801121.12 0.173798E+09 7837429.59
July 53864241.38 5787756.38 48076485.00 0.156738E+09 5451832.38
August 43341827.45 1064165.72 42277661.74 0.128193E+09 7393432.78
September 39552649.37 24478.64 39528170.73 0.103365E+09 12351527.99
October 31601898.29 0.00 31601898.29 52677268.60 58781537.67
November 25480810.94 0.00 25480810.94 23361628.77 87936116.28
December 23406778.91 0.00 23406778.91 14373034.02 0.123601E+09
           
Annual Sum or Average 0.466491E+09 23303698.08 0.443187E+09 0.937748E+09 0.638602E+09
Minimum of Months 23406778.91 0.00 23406778.91 14373034.02 5451832.38
Maximum of Months 60934981.96 11133860.83 49893351.11 0.173798E+09 0.123601E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.206500E+09 0.164969E+09 41530470.22 0.326866E+09 91077597.39
February 0.116382E+09 78022138.43 38359370.38 0.168427E+09 78554207.36
March 0.106667E+09 54051088.25 52616188.64 0.167889E+09 79442167.38
April 90598271.93 37319698.27 53278573.67 0.181822E+09 40751638.83
May 62554278.62 10881561.56 51672717.06 0.142064E+09 28155532.11
June 51241154.51 3909363.47 47331791.04 0.156935E+09 8995313.15
July 53654793.16 5101447.54 48553345.62 0.158941E+09 6028291.86
August 66346579.02 18685521.81 47661057.22 0.180003E+09 7814630.31
September 91202342.18 38546673.46 52655668.72 0.204242E+09 12251540.42
October 0.151275E+09 0.104723E+09 46552209.79 0.263632E+09 54259198.68
November 0.172081E+09 0.132165E+09 39915655.96 0.269567E+09 79230908.83
December 0.192308E+09 0.152359E+09 39948749.01 0.293159E+09 0.110065E+09
           
Annual Sum or Average 0.136081E+10 0.800734E+09 0.560076E+09 0.251355E+10 0.596626E+09
Minimum of Months 51241154.51 3909363.47 38359370.38 0.142064E+09 6028291.86
Maximum of Months 0.206500E+09 0.164969E+09 53278573.67 0.326866E+09 0.110065E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.560483E+09 0.447760E+09 0.112722E+09 0.887181E+09 0.247203E+09
February 0.315883E+09 0.211768E+09 0.104115E+09 0.457146E+09 0.213212E+09
March 0.289517E+09 0.146706E+09 0.142811E+09 0.455685E+09 0.215622E+09
April 0.245902E+09 0.101293E+09 0.144609E+09 0.493502E+09 0.110608E+09
May 0.169785E+09 29534783.85 0.140250E+09 0.385590E+09 76419873.22
June 0.139079E+09 10610812.10 0.128468E+09 0.425954E+09 24415119.84
July 0.145630E+09 13846372.09 0.131784E+09 0.431399E+09 16362017.17
August 0.180078E+09 50716328.22 0.129362E+09 0.488565E+09 21210505.10
September 0.247542E+09 0.104624E+09 0.142918E+09 0.554355E+09 33253186.70
October 0.410591E+09 0.284239E+09 0.126352E+09 0.715552E+09 0.147271E+09
November 0.467063E+09 0.358724E+09 0.108339E+09 0.731661E+09 0.215049E+09
December 0.521963E+09 0.413534E+09 0.108429E+09 0.795693E+09 0.298738E+09
           
Annual Sum or Average 0.369352E+10 0.217336E+10 0.152016E+10 0.682228E+10 0.161936E+10
Minimum of Months 0.139079E+09 10610812.10 0.104115E+09 0.385590E+09 16362017.17
Maximum of Months 0.560483E+09 0.447760E+09 0.144609E+09 0.887181E+09 0.298738E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.442566E+09 0.353559E+09 89007348.67 0.691092E+09 0.182810E+09
February 0.249427E+09 0.167216E+09 82211105.16 0.354573E+09 0.159389E+09
March 0.228607E+09 0.115841E+09 0.112766E+09 0.351652E+09 0.160334E+09
April 0.194169E+09 79982898.78 0.114186E+09 0.386093E+09 71086432.67
May 0.134065E+09 23321164.89 0.110744E+09 0.310129E+09 43100156.02
June 0.109819E+09 8378476.71 0.101441E+09 0.351492E+09 10329360.97
July 0.114992E+09 10933329.61 0.104059E+09 0.362771E+09 6826456.69
August 0.142193E+09 40046470.60 0.102146E+09 0.403164E+09 7538194.66
September 0.195463E+09 82612529.72 0.112851E+09 0.451181E+09 12703384.60
October 0.324210E+09 0.224440E+09 99769849.61 0.565746E+09 96674450.41
November 0.368801E+09 0.283255E+09 85546508.11 0.570674E+09 0.156075E+09
December 0.412151E+09 0.326533E+09 85617432.54 0.620386E+09 0.225813E+09
           
Annual Sum or Average 0.291646E+10 0.171612E+10 0.120034E+10 0.541895E+10 0.113268E+10
Minimum of Months 0.109819E+09 8378476.71 82211105.16 0.310129E+09 6826456.69
Maximum of Months 0.442566E+09 0.353559E+09 0.114186E+09 0.691092E+09 0.225813E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.340154E+09 0.211926E+09 0.128229E+09 0.498332E+09 0.373608E+09
February 0.248858E+09 0.120775E+09 0.128083E+09 0.298969E+09 0.320019E+09
March 0.364588E+09 0.174372E+09 0.190216E+09 0.515451E+09 0.304606E+09
April 0.540336E+09 0.308393E+09 0.231943E+09 0.955157E+09 0.131944E+09
May 0.560366E+09 0.314023E+09 0.246343E+09 0.107280E+10 79918236.34
June 0.574867E+09 0.338034E+09 0.236833E+09 0.127094E+10 18942652.11
July 0.432114E+09 0.201359E+09 0.230755E+09 0.103070E+10 12597294.22
August 0.413642E+09 0.208000E+09 0.205642E+09 0.964073E+09 13995131.58
September 0.348351E+09 0.146469E+09 0.201882E+09 0.772843E+09 24225575.64
October 0.369811E+09 0.212073E+09 0.157738E+09 0.633249E+09 0.192270E+09
November 0.327596E+09 0.197665E+09 0.129932E+09 0.474117E+09 0.317297E+09
December 0.271608E+09 0.153993E+09 0.117616E+09 0.357278E+09 0.464385E+09
           
Annual Sum or Average 0.479229E+10 0.258708E+10 0.220521E+10 0.884391E+10 0.225381E+10
Minimum of Months 0.248858E+09 0.120775E+09 0.117616E+09 0.298969E+09 12597294.22
Maximum of Months 0.574867E+09 0.338034E+09 0.246343E+09 0.127094E+10 0.464385E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53674072.02 0.00 53674072.02 54154783.44 0.196606E+09
February 55241433.50 0.00 55241433.50 35462314.07 0.169927E+09
March 81295770.76 3216.16 81292554.60 89928589.19 0.168405E+09
April 96350800.51 1418628.78 94932171.74 0.180567E+09 70253488.17
May 0.116786E+09 9916509.70 0.106870E+09 0.258816E+09 38867831.25
June 0.130521E+09 23848337.92 0.106672E+09 0.384634E+09 9372017.85
July 0.115375E+09 12397170.40 0.102978E+09 0.357105E+09 6244048.19
August 92836668.46 2279405.50 90557262.96 0.292751E+09 7873337.27
September 84720382.40 52432.38 84667950.02 0.236809E+09 13680340.02
October 67690153.51 0.00 67690153.51 0.120385E+09 0.104942E+09
November 54578999.93 0.00 54578999.93 53362221.56 0.168989E+09
December 50136496.34 0.00 50136496.34 35665104.24 0.242596E+09
           
Annual Sum or Average 0.999207E+09 49915700.83 0.949291E+09 0.209964E+10 0.119776E+10
Minimum of Months 50136496.34 0.00 50136496.34 35462314.07 6244048.19
Maximum of Months 0.130521E+09 23848337.92 0.106870E+09 0.384634E+09 0.242596E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.340154E+09 0.211926E+09 0.128229E+09 0.517443E+09 0.363941E+09
February 0.248858E+09 0.120775E+09 0.128083E+09 0.311092E+09 0.310994E+09
March 0.364588E+09 0.174372E+09 0.190216E+09 0.522372E+09 0.305721E+09
April 0.540336E+09 0.308393E+09 0.231943E+09 0.956554E+09 0.135059E+09
May 0.560366E+09 0.314023E+09 0.246343E+09 0.106945E+10 80724014.47
June 0.574867E+09 0.338034E+09 0.236833E+09 0.126579E+10 19620814.81
July 0.432114E+09 0.201359E+09 0.230755E+09 0.102936E+10 12886749.94
August 0.413642E+09 0.208000E+09 0.205642E+09 0.964614E+09 15328690.24
September 0.348351E+09 0.146469E+09 0.201882E+09 0.775000E+09 25424381.99
October 0.369811E+09 0.212073E+09 0.157738E+09 0.643141E+09 0.192676E+09
November 0.327596E+09 0.197665E+09 0.129932E+09 0.488584E+09 0.311196E+09
December 0.271608E+09 0.153993E+09 0.117616E+09 0.377973E+09 0.448613E+09
           
Annual Sum or Average 0.479229E+10 0.258708E+10 0.220521E+10 0.892138E+10 0.222219E+10
Minimum of Months 0.248858E+09 0.120775E+09 0.117616E+09 0.311092E+09 12886749.94
Maximum of Months 0.574867E+09 0.338034E+09 0.246343E+09 0.126579E+10 0.448613E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.649066E+09 0.518528E+09 0.130538E+09 0.999741E+09 0.278183E+09
February 0.365808E+09 0.245238E+09 0.120570E+09 0.508914E+09 0.244404E+09
March 0.335275E+09 0.169892E+09 0.165382E+09 0.508935E+09 0.238779E+09
April 0.284767E+09 0.117303E+09 0.167464E+09 0.574325E+09 0.100553E+09
May 0.196619E+09 34202726.45 0.162417E+09 0.469984E+09 58937734.31
June 0.161060E+09 12287840.18 0.148772E+09 0.537932E+09 12518009.60
July 0.168647E+09 16034777.14 0.152612E+09 0.549401E+09 8815810.18
August 0.208539E+09 58731992.40 0.149807E+09 0.605727E+09 9847902.11
September 0.286666E+09 0.121159E+09 0.165506E+09 0.668822E+09 17477789.56
October 0.475485E+09 0.329163E+09 0.146322E+09 0.825307E+09 0.143943E+09
November 0.540882E+09 0.415420E+09 0.125462E+09 0.826441E+09 0.236441E+09
December 0.604458E+09 0.478892E+09 0.125566E+09 0.892158E+09 0.346644E+09
           
Annual Sum or Average 0.427727E+10 0.251685E+10 0.176042E+10 0.796769E+10 0.169654E+10
Minimum of Months 0.161060E+09 12287840.18 0.120570E+09 0.469984E+09 8815810.18
Maximum of Months 0.649066E+09 0.518528E+09 0.167464E+09 0.999741E+09 0.346644E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.375704E+09 0.00 0.375704E+09 0.274615E+09 0.173201E+10
February 0.386675E+09 0.00 0.386675E+09 0.161711E+09 0.158116E+10
March 0.569049E+09 22512.27 0.569026E+09 0.511658E+09 0.148698E+10
April 0.674430E+09 9930025.34 0.664500E+09 0.116867E+10 0.669740E+09
May 0.817473E+09 69412938.91 0.748060E+09 0.168212E+10 0.417349E+09
June 0.913609E+09 0.166932E+09 0.746677E+09 0.253710E+10 0.134757E+09
July 0.807597E+09 86776906.14 0.720820E+09 0.227002E+10 99533346.31
August 0.649832E+09 15955234.21 0.633877E+09 0.185156E+10 0.138196E+09
September 0.593020E+09 367012.78 0.592653E+09 0.149046E+10 0.219743E+09
October 0.473813E+09 0.00 0.473813E+09 0.728050E+09 0.977737E+09
November 0.382039E+09 0.00 0.382039E+09 0.277655E+09 0.151554E+10
December 0.350942E+09 0.00 0.350942E+09 0.150861E+09 0.212655E+10
           
Annual Sum or Average 0.699418E+10 0.349397E+09 0.664479E+10 0.131045E+11 0.110993E+11
Minimum of Months 0.350942E+09 0.00 0.350942E+09 0.150861E+09 99533346.31
Maximum of Months 0.913609E+09 0.166932E+09 0.748060E+09 0.253710E+10 0.212655E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.375704E+09 0.00 0.375704E+09 0.250570E+09 0.178247E+10
February 0.386675E+09 0.00 0.386675E+09 0.143100E+09 0.163894E+10
March 0.569049E+09 22512.27 0.569026E+09 0.480399E+09 0.153228E+10
April 0.674430E+09 9930025.34 0.664500E+09 0.114386E+10 0.689936E+09
May 0.817473E+09 69412938.91 0.748060E+09 0.165629E+10 0.430795E+09
June 0.913609E+09 0.166932E+09 0.746677E+09 0.251004E+10 0.140860E+09
July 0.807597E+09 86776906.14 0.720820E+09 0.224168E+10 0.105448E+09
August 0.649832E+09 15955234.21 0.633877E+09 0.182535E+10 0.147004E+09
September 0.593020E+09 367012.78 0.592653E+09 0.146702E+10 0.231752E+09
October 0.473813E+09 0.00 0.473813E+09 0.704404E+09 0.100806E+10
November 0.382039E+09 0.00 0.382039E+09 0.255353E+09 0.156271E+10
December 0.350942E+09 0.00 0.350942E+09 0.132286E+09 0.219119E+10
           
Annual Sum or Average 0.699418E+10 0.349397E+09 0.664479E+10 0.128104E+11 0.114614E+11
Minimum of Months 0.350942E+09 0.00 0.350942E+09 0.132286E+09 0.105448E+09
Maximum of Months 0.913609E+09 0.166932E+09 0.748060E+09 0.251004E+10 0.219119E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53674072.02 0.00 53674072.02 59818890.50 0.229261E+09
February 55241433.50 0.00 55241433.50 36000024.24 0.207932E+09
March 81295770.76 3216.16 81292554.60 98980526.22 0.201878E+09
April 96350800.51 1418628.78 94932171.74 0.208246E+09 95472978.54
May 0.116786E+09 9916509.70 0.106870E+09 0.291480E+09 65746083.42
June 0.130521E+09 23848337.92 0.106672E+09 0.413792E+09 25446915.31
July 0.115375E+09 12397170.40 0.102978E+09 0.376177E+09 19420047.86
August 92836668.46 2279405.50 90557262.96 0.316599E+09 24779302.70
September 84720382.40 52432.38 84667950.02 0.261766E+09 35568313.02
October 67690153.51 0.00 67690153.51 0.137120E+09 0.133035E+09
November 54578999.93 0.00 54578999.93 59802201.93 0.199588E+09
December 50136496.34 0.00 50136496.34 37207154.19 0.278381E+09
           
Annual Sum or Average 0.999207E+09 49915700.83 0.949291E+09 0.229699E+10 0.151651E+10
Minimum of Months 50136496.34 0.00 50136496.34 36000024.24 19420047.86
Maximum of Months 0.130521E+09 23848337.92 0.106870E+09 0.413792E+09 0.278381E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.647832E+09 0.406608E+09 0.241223E+09 0.945909E+09 0.786116E+09
February 0.581660E+09 0.334662E+09 0.246998E+09 0.736769E+09 0.720383E+09
March 0.799654E+09 0.411405E+09 0.388250E+09 0.116946E+10 0.696216E+09
April 0.110278E+10 0.657056E+09 0.445720E+09 0.205928E+10 0.343050E+09
May 0.118295E+10 0.701920E+09 0.481032E+09 0.237275E+10 0.244477E+09
June 0.119111E+10 0.739991E+09 0.451119E+09 0.273813E+10 95286102.54
July 0.104108E+10 0.587423E+09 0.453658E+09 0.245587E+10 72402116.89
August 0.988937E+09 0.565014E+09 0.423923E+09 0.230489E+10 92736010.00
September 0.784240E+09 0.378243E+09 0.405997E+09 0.179622E+10 0.131253E+09
October 0.813243E+09 0.494683E+09 0.318561E+09 0.146488E+10 0.464178E+09
November 0.605626E+09 0.363437E+09 0.242189E+09 0.875946E+09 0.691719E+09
December 0.571644E+09 0.345721E+09 0.225923E+09 0.739222E+09 0.951347E+09
           
Annual Sum or Average 0.103108E+11 0.598616E+10 0.432459E+10 0.196593E+11 0.528916E+10
Minimum of Months 0.571644E+09 0.334662E+09 0.225923E+09 0.736769E+09 72402116.89
Maximum of Months 0.119111E+10 0.739991E+09 0.481032E+09 0.273813E+10 0.951347E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.442566E+09 0.353559E+09 89007348.67 0.716085E+09 0.209700E+09
February 0.249427E+09 0.167216E+09 82211105.16 0.366101E+09 0.190955E+09
March 0.228607E+09 0.115841E+09 0.112766E+09 0.368767E+09 0.194382E+09
April 0.194169E+09 79982898.78 0.114186E+09 0.416432E+09 98289897.73
May 0.134065E+09 23321164.89 0.110744E+09 0.340426E+09 70504609.14
June 0.109819E+09 8378476.71 0.101441E+09 0.376340E+09 26833289.79
July 0.114992E+09 10933329.61 0.104059E+09 0.381061E+09 20179051.68
August 0.142193E+09 40046470.60 0.102146E+09 0.427977E+09 25066245.57
September 0.195463E+09 82612529.72 0.112851E+09 0.478714E+09 35423831.48
October 0.324210E+09 0.224440E+09 99769849.61 0.593631E+09 0.124851E+09
November 0.368801E+09 0.283255E+09 85546508.11 0.592949E+09 0.183297E+09
December 0.412151E+09 0.326533E+09 85617432.54 0.640428E+09 0.251706E+09
           
Annual Sum or Average 0.291646E+10 0.171612E+10 0.120034E+10 0.569891E+10 0.143119E+10
Minimum of Months 0.109819E+09 8378476.71 82211105.16 0.340426E+09 20179051.68
Maximum of Months 0.442566E+09 0.353559E+09 0.114186E+09 0.716085E+09 0.251706E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 67974825.56 0.00 67974825.56 57582953.50 0.275241E+09
February 69959789.98 0.00 69959789.98 37905466.71 0.239125E+09
March 0.102956E+09 4073.06 0.102952E+09 0.108776E+09 0.229165E+09
April 0.122022E+09 1796603.83 0.120226E+09 0.218569E+09 0.110055E+09
May 0.147902E+09 12558633.84 0.135344E+09 0.309768E+09 70666027.33
June 0.165296E+09 30202415.22 0.135094E+09 0.459984E+09 22775878.43
July 0.146116E+09 15700234.09 0.130415E+09 0.411482E+09 16439998.88
August 0.117572E+09 2886723.24 0.114685E+09 0.335267E+09 22502449.29
September 0.107293E+09 66402.30 0.107227E+09 0.270214E+09 36412519.70
October 85725308.41 0.00 85725308.41 0.137187E+09 0.157779E+09
November 69120859.66 0.00 69120859.66 58469399.15 0.238283E+09
December 63494709.17 0.00 63494709.17 34354383.82 0.338278E+09
           
Annual Sum or Average 0.126543E+10 63215085.59 0.120222E+10 0.243956E+10 0.175672E+10
Minimum of Months 63494709.17 0.00 63494709.17 34354383.82 16439998.88
Maximum of Months 0.165296E+09 30202415.22 0.135344E+09 0.459984E+09 0.338278E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 60817333.99 0.00 60817333.99 51519686.68 0.246229E+09
February 62593289.17 0.00 62593289.17 33914164.69 0.213946E+09
March 92115091.26 3644.19 92111447.08 97322673.45 0.205035E+09
April 0.109174E+09 1607428.26 0.107566E+09 0.195555E+09 98466203.95
May 0.132329E+09 11236257.28 0.121093E+09 0.277151E+09 63225162.40
June 0.147891E+09 27022215.34 0.120869E+09 0.411550E+09 20377664.73
July 0.130730E+09 14047058.93 0.116683E+09 0.368154E+09 14708929.28
August 0.105192E+09 2582762.23 0.102609E+09 0.299964E+09 20133026.64
September 95995470.41 59410.39 95936060.02 0.241761E+09 32578419.34
October 76698758.25 0.00 76698758.25 0.122742E+09 0.141168E+09
November 61842695.04 0.00 61842695.04 52312792.96 0.213183E+09
December 56808956.88 0.00 56808956.88 30736997.37 0.302616E+09
           
Annual Sum or Average 0.113219E+10 56558776.60 0.107563E+10 0.218268E+10 0.157167E+10
Minimum of Months 56808956.88 0.00 56808956.88 30736997.37 14708929.28
Maximum of Months 0.147891E+09 27022215.34 0.121093E+09 0.411550E+09 0.302616E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.165223E+10 0.131994E+10 0.332291E+09 0.258295E+10 0.732516E+09
February 0.931184E+09 0.624266E+09 0.306919E+09 0.132108E+10 0.642410E+09
March 0.853459E+09 0.432470E+09 0.420989E+09 0.130976E+10 0.648917E+09
April 0.724889E+09 0.298600E+09 0.426289E+09 0.141341E+10 0.336153E+09
May 0.500505E+09 87064857.88 0.413440E+09 0.110218E+10 0.232466E+09
June 0.409987E+09 31279350.23 0.378708E+09 0.122353E+10 76132272.91
July 0.429299E+09 40817377.39 0.388482E+09 0.123129E+10 52920675.31
August 0.530848E+09 0.149505E+09 0.381343E+09 0.140086E+10 69454160.10
September 0.729722E+09 0.308417E+09 0.421305E+09 0.159745E+10 0.106089E+09
October 0.121037E+10 0.837901E+09 0.372471E+09 0.208045E+10 0.431295E+09
November 0.137684E+10 0.105747E+10 0.319371E+09 0.212877E+10 0.635647E+09
December 0.153868E+10 0.121905E+10 0.319635E+09 0.231630E+10 0.889322E+09
           
Annual Sum or Average 0.108880E+11 0.640678E+10 0.448124E+10 0.197080E+11 0.485332E+10
Minimum of Months 0.409987E+09 31279350.23 0.306919E+09 0.110218E+10 52920675.31
Maximum of Months 0.165223E+10 0.131994E+10 0.426289E+09 0.258295E+10 0.889322E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1286.65 372.79 835.71 667.64 168.07 0.00 0.00
February 735.59 344.34 521.47 349.59 171.87 0.00 0.00
March 662.75 312.36 431.69 218.75 212.94 0.00 0.00
April 724.38 179.52 378.88 156.07 222.81 0.00 0.00
May 537.01 121.04 253.16 44.04 209.12 0.00 0.00
June 596.06 45.88 214.28 16.35 197.94 0.00 0.00
July 588.53 29.79 217.14 20.65 196.50 0.00 0.00
August 678.70 39.75 268.51 75.62 192.88 0.00 0.00
September 813.60 61.93 381.40 161.20 220.20 0.00 0.00
October 1038.82 223.07 612.22 423.82 188.40 0.00 0.00
November 1099.17 331.79 719.63 552.71 166.92 0.00 0.00
December 1150.88 443.46 778.28 616.61 161.67 0.00 0.00
               
Annual Sum or Average 826.95 208.29 467.74 275.23 192.51 0.00 0.00
Minimum of Months 537.01 29.79 214.28 16.35 161.67 0.00 0.00
Maximum of Months 1286.65 443.46 835.71 667.64 222.81 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3576.23 1148.56 2353.32 1880.03 473.29 0.00 0.00
February 2022.75 1092.53 1468.41 984.43 483.99 0.00 0.00
March 1813.93 985.64 1215.60 615.98 599.62 0.00 0.00
April 2014.82 542.66 1066.89 439.48 627.41 0.00 0.00
May 1497.02 361.48 712.87 124.01 588.87 0.00 0.00
June 1681.30 130.27 603.41 46.04 557.38 0.00 0.00
July 1654.43 89.18 611.46 58.14 553.32 0.00 0.00
August 1904.22 120.91 756.09 212.94 543.15 0.00 0.00
September 2276.49 187.00 1074.00 453.93 620.07 0.00 0.00
October 2890.99 682.98 1723.96 1193.45 530.51 0.00 0.00
November 3049.44 1030.29 2026.44 1556.40 470.05 0.00 0.00
December 3191.08 1362.92 2191.58 1736.32 455.26 0.00 0.00
               
Annual Sum or Average 2300.45 642.74 1317.12 775.03 542.09 0.00 0.00
Minimum of Months 1497.02 89.18 603.41 46.04 455.26 0.00 0.00
Maximum of Months 3576.23 1362.92 2353.32 1880.03 627.41 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 4748.49 1497.51 3057.09 2442.27 614.83 0.00 0.00
February 2690.52 1463.26 1907.55 1278.83 628.73 0.00 0.00
March 2412.22 1317.42 1579.13 800.19 778.94 0.00 0.00
April 2696.58 710.85 1385.95 570.91 815.04 0.00 0.00
May 2006.00 476.44 926.06 161.09 764.97 0.00 0.00
June 2259.32 169.47 783.87 59.80 724.06 0.00 0.00
July 2223.33 114.58 794.32 75.52 718.79 0.00 0.00
August 2552.23 153.72 982.21 276.63 705.58 0.00 0.00
September 3040.86 236.86 1395.19 589.68 805.51 0.00 0.00
October 3844.70 891.39 2239.52 1550.35 689.17 0.00 0.00
November 4046.82 1352.81 2632.46 2021.85 610.62 0.00 0.00
December 4236.39 1797.28 2846.99 2255.58 591.41 0.00 0.00
               
Annual Sum or Average 3066.76 845.95 1711.02 1006.81 704.21 0.00 0.00
Minimum of Months 2006.00 114.58 783.87 59.80 591.41 0.00 0.00
Maximum of Months 4748.49 1797.28 3057.09 2442.27 815.04 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 438.97 203.09 292.23 211.13 81.11 0.00 0.00
February 266.91 195.42 205.97 119.04 86.93 0.00 0.00
March 324.55 173.35 221.47 108.35 113.12 0.00 0.00
April 520.93 80.55 283.37 149.84 133.54 0.00 0.00
May 518.24 48.17 259.27 125.95 133.32 0.00 0.00
June 627.32 12.33 264.15 133.65 130.51 0.00 0.00
July 521.12 7.71 204.27 79.26 125.00 0.00 0.00
August 511.51 8.70 207.52 92.61 114.91 0.00 0.00
September 473.49 15.51 209.80 88.38 121.42 0.00 0.00
October 447.33 108.58 259.12 162.98 96.14 0.00 0.00
November 399.14 179.07 268.67 185.54 83.13 0.00 0.00
December 356.30 250.71 255.29 179.41 75.88 0.00 0.00
               
Annual Sum or Average 451.39 106.59 244.44 136.45 107.99 0.00 0.00
Minimum of Months 266.91 7.71 204.27 79.26 75.88 0.00 0.00
Maximum of Months 627.32 250.71 292.23 211.13 133.54 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 212.64 212.98 147.04 79.12 67.91 0.00 0.00
February 142.58 200.89 125.70 49.92 75.78 0.00 0.00
March 228.72 177.10 166.47 65.10 101.37 0.00 0.00
April 441.15 81.19 245.64 119.53 126.11 0.00 0.00
May 495.79 45.40 252.82 120.95 131.87 0.00 0.00
June 637.36 11.29 272.14 139.62 132.53 0.00 0.00
July 518.19 7.28 204.41 79.81 124.60 0.00 0.00
August 470.01 9.18 189.10 78.51 110.59 0.00 0.00
September 390.69 16.48 167.08 56.53 110.55 0.00 0.00
October 284.69 114.49 163.34 79.18 84.17 0.00 0.00
November 208.33 188.43 147.44 76.26 71.18 0.00 0.00
December 152.85 261.73 120.13 57.49 62.63 0.00 0.00
               
Annual Sum or Average 349.50 110.19 183.65 83.62 100.03 0.00 0.00
Minimum of Months 142.58 7.28 120.13 49.92 62.63 0.00 0.00
Maximum of Months 637.36 261.73 272.14 139.62 132.53 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 192.44 80.82 132.16 105.58 26.58 0.00 0.00
February 105.38 80.93 82.47 55.29 27.18 0.00 0.00
March 91.69 72.61 68.27 34.59 33.67 0.00 0.00
April 105.18 41.53 59.92 24.68 35.24 0.00 0.00
May 76.11 29.10 40.04 6.96 33.07 0.00 0.00
June 86.29 12.23 33.89 2.59 31.30 0.00 0.00
July 83.43 9.60 34.34 3.26 31.07 0.00 0.00
August 98.56 12.92 42.46 11.96 30.50 0.00 0.00
September 119.50 17.86 60.32 25.49 34.82 0.00 0.00
October 153.89 50.60 96.82 67.02 29.79 0.00 0.00
November 162.70 74.19 113.80 87.41 26.40 0.00 0.00
December 171.31 95.01 123.08 97.51 25.57 0.00 0.00
               
Annual Sum or Average 120.69 47.98 73.97 43.53 30.44 0.00 0.00
Minimum of Months 76.11 9.60 33.89 2.59 25.57 0.00 0.00
Maximum of Months 192.44 95.01 132.16 105.58 35.24 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 16.79 59.40 16.03 0.00 16.03 0.00 0.00
February 11.78 58.59 18.27 0.00 18.27 0.00 0.00
March 28.08 50.50 24.29 0.00 24.28 0.00 0.00
April 60.44 20.30 29.74 0.44 29.30 0.00 0.00
May 82.56 10.67 34.89 2.96 31.92 0.00 0.00
June 126.14 2.29 40.29 7.36 32.93 0.00 0.00
July 113.19 1.55 34.47 3.70 30.76 0.00 0.00
August 93.65 1.92 27.73 0.68 27.05 0.00 0.00
September 78.05 3.60 26.15 0.02 26.14 0.00 0.00
October 38.49 31.00 20.22 0.00 20.22 0.00 0.00
November 17.28 52.55 16.85 0.00 16.85 0.00 0.00
December 10.38 74.98 14.98 0.00 14.98 0.00 0.00
               
Annual Sum or Average 56.62 30.50 25.35 1.27 24.08 0.00 0.00
Minimum of Months 10.38 1.55 14.98 0.00 14.98 0.00 0.00
Maximum of Months 126.14 74.98 40.29 7.36 32.93 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 419.97 195.67 286.18 207.91 78.27 0.00 0.00
February 288.19 190.31 223.33 138.29 85.04 0.00 0.00
March 333.89 163.60 234.64 120.06 114.59 0.00 0.00
April 520.91 72.28 287.65 157.61 130.04 0.00 0.00
May 533.34 42.26 270.90 139.75 131.15 0.00 0.00
June 643.39 10.74 272.15 145.99 126.16 0.00 0.00
July 578.08 6.87 237.29 113.75 123.55 0.00 0.00
August 561.93 8.31 237.72 120.44 117.28 0.00 0.00
September 500.56 14.61 226.70 104.84 121.86 0.00 0.00
October 465.08 104.15 272.87 176.15 96.72 0.00 0.00
November 375.73 173.15 259.12 179.39 79.73 0.00 0.00
December 355.96 243.46 260.60 186.46 74.14 0.00 0.00
               
Annual Sum or Average 465.71 101.77 255.97 149.33 106.63 0.00 0.00
Minimum of Months 288.19 6.87 223.33 104.84 74.14 0.00 0.00
Maximum of Months 643.39 243.46 287.65 207.91 131.15 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 181.88 192.21 140.98 75.91 65.07 0.00 0.00
February 156.63 187.94 143.06 69.17 73.89 0.00 0.00
March 235.76 164.39 179.64 76.81 102.83 0.00 0.00
April 439.16 73.39 249.91 127.30 122.61 0.00 0.00
May 509.57 42.39 264.45 134.75 129.71 0.00 0.00
June 652.95 10.80 280.14 151.96 128.18 0.00 0.00
July 574.96 6.89 237.44 114.30 123.14 0.00 0.00
August 519.54 8.96 219.29 106.33 112.95 0.00 0.00
September 415.87 15.33 183.98 72.99 110.99 0.00 0.00
October 296.45 105.42 177.10 92.35 84.75 0.00 0.00
November 175.19 171.46 137.89 70.11 67.78 0.00 0.00
December 137.98 238.49 125.44 64.54 60.90 0.00 0.00
               
Annual Sum or Average 358.96 101.13 195.17 96.50 98.67 0.00 0.00
Minimum of Months 137.98 6.89 125.44 64.54 60.90 0.00 0.00
Maximum of Months 652.95 238.49 280.14 151.96 129.71 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 475.51 256.79 321.09 228.77 92.33 0.00 0.00
February 275.77 245.98 218.26 119.79 98.47 0.00 0.00
March 290.77 223.66 200.53 74.96 125.57 0.00 0.00
April 381.84 114.57 194.25 54.43 139.83 0.00 0.00
May 359.04 71.91 162.32 21.51 140.82 0.00 0.00
June 472.58 22.88 160.71 21.55 139.16 0.00 0.00
July 437.19 15.44 149.07 15.10 133.97 0.00 0.00
August 427.07 20.85 152.08 27.39 124.70 0.00 0.00
September 440.68 35.21 187.34 55.27 132.07 0.00 0.00
October 435.16 153.28 253.58 145.22 108.36 0.00 0.00
November 410.87 230.62 283.08 189.39 93.69 0.00 0.00
December 413.08 310.58 299.12 211.28 87.84 0.00 0.00
               
Annual Sum or Average 402.39 141.41 215.19 97.05 118.14 0.00 0.00
Minimum of Months 275.77 15.44 149.07 15.10 87.84 0.00 0.00
Maximum of Months 475.51 310.58 321.09 228.77 140.82 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 436.86 200.53 292.23 211.13 81.11 0.00 0.00
February 264.96 192.98 205.97 119.04 86.93 0.00 0.00
March 321.75 171.60 221.47 108.35 113.12 0.00 0.00
April 517.29 78.16 283.37 149.84 133.54 0.00 0.00
May 516.32 45.93 259.27 125.95 133.32 0.00 0.00
June 625.94 11.29 264.15 133.65 130.51 0.00 0.00
July 520.26 7.25 204.27 79.26 125.00 0.00 0.00
August 510.46 8.03 207.52 92.61 114.91 0.00 0.00
September 472.22 14.23 209.80 88.38 121.42 0.00 0.00
October 445.37 105.60 259.12 162.98 96.14 0.00 0.00
November 396.93 176.48 268.67 185.54 83.13 0.00 0.00
December 355.28 247.95 255.29 179.41 75.88 0.00 0.00
               
Annual Sum or Average 449.55 104.66 244.44 136.45 107.99 0.00 0.00
Minimum of Months 264.96 7.25 204.27 79.26 75.88 0.00 0.00
Maximum of Months 625.94 247.95 292.23 211.13 133.54 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 212.70 208.57 147.04 79.12 67.91 0.00 0.00
February 141.83 197.37 125.70 49.92 75.78 0.00 0.00
March 226.91 175.32 166.47 65.10 101.37 0.00 0.00
April 438.47 78.98 245.64 119.53 126.11 0.00 0.00
May 494.52 43.26 252.82 120.95 131.87 0.00 0.00
June 635.98 10.42 272.14 139.62 132.53 0.00 0.00
July 517.37 6.86 204.41 79.81 124.60 0.00 0.00
August 469.32 8.53 189.10 78.51 110.59 0.00 0.00
September 390.35 15.08 167.08 56.53 110.55 0.00 0.00
October 284.57 110.62 163.34 79.18 84.17 0.00 0.00
November 208.17 184.34 147.44 76.26 71.18 0.00 0.00
December 153.40 257.04 120.13 57.49 62.63 0.00 0.00
               
Annual Sum or Average 348.72 107.69 183.65 83.62 100.03 0.00 0.00
Minimum of Months 141.83 6.86 120.13 49.92 62.63 0.00 0.00
Maximum of Months 635.98 257.04 272.14 139.62 132.53 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 373.26 103.86 242.33 193.60 48.74 0.00 0.00
February 210.36 101.03 151.21 101.37 49.84 0.00 0.00
March 190.01 89.15 125.18 63.43 61.75 0.00 0.00
April 221.58 38.79 109.86 45.26 64.61 0.00 0.00
May 175.47 22.00 73.41 12.77 60.64 0.00 0.00
June 207.54 4.83 62.14 4.74 57.40 0.00 0.00
July 205.12 3.29 62.97 5.99 56.98 0.00 0.00
August 226.15 3.68 77.86 21.93 55.93 0.00 0.00
September 258.03 6.74 110.60 46.74 63.85 0.00 0.00
October 308.13 53.74 177.53 122.90 54.63 0.00 0.00
November 318.84 91.22 208.67 160.27 48.40 0.00 0.00
December 333.09 129.42 225.68 178.80 46.88 0.00 0.00
               
Annual Sum or Average 252.65 53.80 135.63 79.81 55.82 0.00 0.00
Minimum of Months 175.47 3.29 62.14 4.74 46.88 0.00 0.00
Maximum of Months 373.26 129.42 242.33 193.60 64.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 102.53 646.66 140.27 0.00 140.27 0.00 0.00
February 66.84 653.59 159.84 0.00 159.84 0.00 0.00
March 191.03 555.18 212.46 0.01 212.45 0.00 0.00
April 450.88 258.39 260.20 3.83 256.37 0.00 0.00
May 628.03 155.82 305.21 25.92 279.29 0.00 0.00
June 978.82 51.99 352.47 64.40 288.07 0.00 0.00
July 847.53 37.16 301.52 32.40 269.12 0.00 0.00
August 691.29 51.60 242.62 5.96 236.66 0.00 0.00
September 575.02 84.78 228.79 0.14 228.65 0.00 0.00
October 271.82 365.05 176.90 0.00 176.90 0.00 0.00
November 107.12 584.70 147.39 0.00 147.39 0.00 0.00
December 56.33 793.96 131.03 0.00 131.03 0.00 0.00
               
Annual Sum or Average 415.54 351.96 221.78 11.08 210.70 0.00 0.00
Minimum of Months 56.33 37.16 131.03 0.00 131.03 0.00 0.00
Maximum of Months 978.82 793.96 352.47 64.40 288.07 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 93.55 665.50 140.27 0.00 140.27 0.00 0.00
February 59.15 677.47 159.84 0.00 159.84 0.00 0.00
March 179.36 572.09 212.46 0.01 212.45 0.00 0.00
April 441.30 266.18 260.20 3.83 256.37 0.00 0.00
May 618.39 160.84 305.21 25.92 279.29 0.00 0.00
June 968.38 54.34 352.47 64.40 288.07 0.00 0.00
July 836.95 39.37 301.52 32.40 269.12 0.00 0.00
August 681.51 54.89 242.62 5.96 236.66 0.00 0.00
September 565.98 89.41 228.79 0.14 228.65 0.00 0.00
October 262.99 376.37 176.90 0.00 176.90 0.00 0.00
November 98.52 602.90 147.39 0.00 147.39 0.00 0.00
December 49.39 818.10 131.03 0.00 131.03 0.00 0.00
               
Annual Sum or Average 406.21 363.44 221.78 11.08 210.70 0.00 0.00
Minimum of Months 49.39 39.37 131.03 0.00 131.03 0.00 0.00
Maximum of Months 968.38 818.10 352.47 64.40 288.07 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 634.53 449.07 427.15 283.81 143.33 0.00 0.00
February 462.02 453.91 366.37 207.46 158.92 0.00 0.00
March 602.46 399.08 414.26 196.85 217.41 0.00 0.00
April 1031.20 202.82 537.54 284.90 252.64 0.00 0.00
May 1119.69 140.02 535.32 274.48 260.84 0.00 0.00
June 1360.69 56.41 552.26 297.92 254.33 0.00 0.00
July 1199.29 41.47 474.70 228.03 246.68 0.00 0.00
August 1138.36 53.05 456.98 226.75 230.22 0.00 0.00
September 978.24 77.60 410.66 177.82 232.84 0.00 0.00
October 815.53 265.37 449.95 268.49 181.46 0.00 0.00
November 581.83 406.64 396.99 249.50 147.50 0.00 0.00
December 516.75 540.86 386.03 250.99 135.03 0.00 0.00
               
Annual Sum or Average 872.11 256.36 451.12 245.82 205.30 0.00 0.00
Minimum of Months 462.02 41.47 366.37 177.82 135.03 0.00 0.00
Maximum of Months 1360.69 540.86 552.26 297.92 260.84 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 990.58 453.67 664.96 492.81 172.15 0.00 0.00
February 564.61 441.67 439.71 258.05 181.66 0.00 0.00
March 563.30 401.73 391.48 161.47 230.01 0.00 0.00
April 704.78 209.85 368.86 116.51 252.35 0.00 0.00
May 627.24 133.38 291.49 41.39 250.10 0.00 0.00
June 805.81 43.55 279.00 34.15 244.86 0.00 0.00
July 749.84 30.43 263.64 26.35 237.30 0.00 0.00
August 759.71 41.37 281.37 57.86 223.51 0.00 0.00
September 813.75 67.47 359.96 119.04 240.92 0.00 0.00
October 868.88 267.72 512.54 312.84 199.71 0.00 0.00
November 850.99 406.37 581.72 407.98 173.74 0.00 0.00
December 868.91 551.12 619.39 455.14 164.25 0.00 0.00
               
Annual Sum or Average 765.34 253.28 421.29 206.96 214.33 0.00 0.00
Minimum of Months 563.30 30.43 263.64 26.35 164.25 0.00 0.00
Maximum of Months 990.58 551.12 664.96 492.81 252.35 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.344615E+10 0.998473E+09 0.223838E+10 0.178821E+10 0.450171E+09 0.00 0.00
February 0.177955E+10 0.833035E+09 0.126153E+10 0.845731E+09 0.415798E+09 0.00 0.00
March 0.177511E+10 0.836636E+09 0.115623E+10 0.585894E+09 0.570335E+09 0.00 0.00
April 0.187759E+10 0.465311E+09 0.982044E+09 0.404532E+09 0.577512E+09 0.00 0.00
May 0.143832E+10 0.324184E+09 0.678057E+09 0.117952E+09 0.560105E+09 0.00 0.00
June 0.154499E+10 0.118922E+09 0.555427E+09 42376069.35 0.513050E+09 0.00 0.00
July 0.157633E+10 79792522.46 0.581591E+09 55297824.35 0.526293E+09 0.00 0.00
August 0.181783E+10 0.106469E+09 0.719166E+09 0.202544E+09 0.516622E+09 0.00 0.00
September 0.210885E+10 0.160522E+09 0.988595E+09 0.417832E+09 0.570763E+09 0.00 0.00
October 0.278237E+10 0.597458E+09 0.163976E+10 0.113516E+10 0.504604E+09 0.00 0.00
November 0.284904E+10 0.860010E+09 0.186529E+10 0.143263E+10 0.432667E+09 0.00 0.00
December 0.308252E+10 0.118777E+10 0.208454E+10 0.165152E+10 0.433026E+09 0.00 0.00
               
Annual Sum or Average 0.260786E+11 0.656858E+10 0.147506E+11 0.867966E+10 0.607095E+10 0.00 0.00
Minimum of Months 0.143832E+10 79792522.46 0.555427E+09 42376069.35 0.415798E+09 0.00 0.00
Maximum of Months 0.344615E+10 0.118777E+10 0.223838E+10 0.178821E+10 0.577512E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.957856E+10 0.307630E+10 0.630312E+10 0.503547E+10 0.126765E+10 0.00 0.00
February 0.489343E+10 0.264305E+10 0.355238E+10 0.238152E+10 0.117086E+10 0.00 0.00
March 0.485843E+10 0.263994E+10 0.325586E+10 0.164984E+10 0.160603E+10 0.00 0.00
April 0.522241E+10 0.140659E+10 0.276537E+10 0.113914E+10 0.162624E+10 0.00 0.00
May 0.400961E+10 0.968175E+09 0.190936E+10 0.332145E+09 0.157722E+10 0.00 0.00
June 0.435793E+10 0.337671E+09 0.156404E+10 0.119328E+09 0.144472E+10 0.00 0.00
July 0.443123E+10 0.238849E+09 0.163772E+10 0.155715E+09 0.148201E+10 0.00 0.00
August 0.510027E+10 0.323834E+09 0.202512E+10 0.570351E+09 0.145477E+10 0.00 0.00
September 0.590065E+10 0.484691E+09 0.278382E+10 0.117659E+10 0.160723E+10 0.00 0.00
October 0.774322E+10 0.182929E+10 0.461746E+10 0.319653E+10 0.142093E+10 0.00 0.00
November 0.790414E+10 0.267051E+10 0.525254E+10 0.403418E+10 0.121836E+10 0.00 0.00
December 0.854699E+10 0.365044E+10 0.586993E+10 0.465056E+10 0.121937E+10 0.00 0.00
               
Annual Sum or Average 0.725469E+11 0.202693E+11 0.415367E+11 0.244414E+11 0.170954E+11 0.00 0.00
Minimum of Months 0.400961E+10 0.238849E+09 0.156404E+10 0.119328E+09 0.117086E+10 0.00 0.00
Maximum of Months 0.957856E+10 0.365044E+10 0.630312E+10 0.503547E+10 0.162624E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.127184E+11 0.401093E+10 0.818812E+10 0.654136E+10 0.164675E+10 0.00 0.00
February 0.650890E+10 0.353992E+10 0.461475E+10 0.309374E+10 0.152101E+10 0.00 0.00
March 0.646088E+10 0.352858E+10 0.422955E+10 0.214323E+10 0.208632E+10 0.00 0.00
April 0.698953E+10 0.184253E+10 0.359238E+10 0.147980E+10 0.211257E+10 0.00 0.00
May 0.537288E+10 0.127611E+10 0.248037E+10 0.431476E+09 0.204890E+10 0.00 0.00
June 0.585616E+10 0.439275E+09 0.203178E+10 0.155014E+09 0.187677E+10 0.00 0.00
July 0.595496E+10 0.306900E+09 0.212749E+10 0.202283E+09 0.192521E+10 0.00 0.00
August 0.683589E+10 0.411725E+09 0.263075E+10 0.740919E+09 0.188983E+10 0.00 0.00
September 0.788192E+10 0.613953E+09 0.361634E+10 0.152845E+10 0.208788E+10 0.00 0.00
October 0.102976E+11 0.238749E+10 0.599834E+10 0.415247E+10 0.184587E+10 0.00 0.00
November 0.104893E+11 0.350648E+10 0.682335E+10 0.524063E+10 0.158272E+10 0.00 0.00
December 0.113468E+11 0.481384E+10 0.762538E+10 0.604134E+10 0.158404E+10 0.00 0.00
               
Annual Sum or Average 0.967132E+11 0.266777E+11 0.539586E+11 0.317507E+11 0.222079E+11 0.00 0.00
Minimum of Months 0.537288E+10 0.306900E+09 0.203178E+10 0.155014E+09 0.152101E+10 0.00 0.00
Maximum of Months 0.127184E+11 0.481384E+10 0.818812E+10 0.654136E+10 0.211257E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.117574E+10 0.543957E+09 0.782721E+09 0.565485E+09 0.217236E+09 0.00 0.00
February 0.645720E+09 0.472756E+09 0.498285E+09 0.287991E+09 0.210294E+09 0.00 0.00
March 0.869269E+09 0.464296E+09 0.593196E+09 0.290214E+09 0.302982E+09 0.00 0.00
April 0.135024E+10 0.208775E+09 0.734505E+09 0.388376E+09 0.346129E+09 0.00 0.00
May 0.138805E+10 0.129024E+09 0.694431E+09 0.337345E+09 0.357087E+09 0.00 0.00
June 0.162601E+10 31966378.67 0.684686E+09 0.346412E+09 0.338274E+09 0.00 0.00
July 0.139577E+10 20655235.49 0.547106E+09 0.212292E+09 0.334813E+09 0.00 0.00
August 0.137004E+10 23311634.47 0.555835E+09 0.248047E+09 0.307788E+09 0.00 0.00
September 0.122728E+10 40201487.18 0.543814E+09 0.229081E+09 0.314733E+09 0.00 0.00
October 0.119812E+10 0.290808E+09 0.694021E+09 0.436513E+09 0.257508E+09 0.00 0.00
November 0.103458E+10 0.464154E+09 0.696397E+09 0.480919E+09 0.215478E+09 0.00 0.00
December 0.954320E+09 0.671506E+09 0.683759E+09 0.480526E+09 0.203233E+09 0.00 0.00
               
Annual Sum or Average 0.142351E+11 0.336141E+10 0.770875E+10 0.430320E+10 0.340555E+10 0.00 0.00
Minimum of Months 0.645720E+09 20655235.49 0.498285E+09 0.212292E+09 0.203233E+09 0.00 0.00
Maximum of Months 0.162601E+10 0.671506E+09 0.782721E+09 0.565485E+09 0.357087E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.569548E+09 0.570450E+09 0.393828E+09 0.211926E+09 0.181903E+09 0.00 0.00
February 0.344923E+09 0.486001E+09 0.304099E+09 0.120775E+09 0.183324E+09 0.00 0.00
March 0.612593E+09 0.474358E+09 0.445884E+09 0.174376E+09 0.271508E+09 0.00 0.00
April 0.114347E+10 0.210456E+09 0.636687E+09 0.309812E+09 0.326875E+09 0.00 0.00
May 0.132793E+10 0.121610E+09 0.677152E+09 0.323940E+09 0.353213E+09 0.00 0.00
June 0.165204E+10 29271833.55 0.705388E+09 0.361882E+09 0.343505E+09 0.00 0.00
July 0.138792E+10 19495420.10 0.547489E+09 0.213756E+09 0.333733E+09 0.00 0.00
August 0.125889E+10 24595735.77 0.506479E+09 0.210280E+09 0.296199E+09 0.00 0.00
September 0.101266E+10 42724492.66 0.433071E+09 0.146521E+09 0.286550E+09 0.00 0.00
October 0.762524E+09 0.306650E+09 0.437501E+09 0.212073E+09 0.225428E+09 0.00 0.00
November 0.539988E+09 0.488407E+09 0.382175E+09 0.197665E+09 0.184511E+09 0.00 0.00
December 0.409384E+09 0.701024E+09 0.321745E+09 0.153993E+09 0.167752E+09 0.00 0.00
               
Annual Sum or Average 0.110219E+11 0.347504E+10 0.579150E+10 0.263700E+10 0.315450E+10 0.00 0.00
Minimum of Months 0.344923E+09 19495420.10 0.304099E+09 0.120775E+09 0.167752E+09 0.00 0.00
Maximum of Months 0.165204E+10 0.701024E+09 0.705388E+09 0.361882E+09 0.353213E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.515427E+09 0.216473E+09 0.353983E+09 0.282791E+09 71191720.82 0.00 0.00
February 0.254931E+09 0.195788E+09 0.199502E+09 0.133746E+09 65755807.07 0.00 0.00
March 0.245587E+09 0.194482E+09 0.182850E+09 92654621.17 90194909.73 0.00 0.00
April 0.272617E+09 0.107637E+09 0.155304E+09 63973596.40 91330373.15 0.00 0.00
May 0.203861E+09 77940440.26 0.107231E+09 18653222.29 88577606.46 0.00 0.00
June 0.223671E+09 31694479.29 87837819.98 6701448.63 81136371.35 0.00 0.00
July 0.223455E+09 25718572.16 91975290.32 8744924.55 83230365.76 0.00 0.00
August 0.263983E+09 34614846.93 0.113732E+09 32030806.41 81700800.92 0.00 0.00
September 0.309741E+09 46291136.88 0.156339E+09 66076882.86 90262586.66 0.00 0.00
October 0.412189E+09 0.135520E+09 0.259316E+09 0.179516E+09 79800009.62 0.00 0.00
November 0.421723E+09 0.192298E+09 0.294982E+09 0.226559E+09 68423598.87 0.00 0.00
December 0.458834E+09 0.254488E+09 0.329655E+09 0.261175E+09 68480327.14 0.00 0.00
               
Annual Sum or Average 0.380602E+10 0.151294E+10 0.233271E+10 0.137262E+10 0.960084E+09 0.00 0.00
Minimum of Months 0.203861E+09 25718572.16 87837819.98 6701448.63 65755807.07 0.00 0.00
Maximum of Months 0.515427E+09 0.254488E+09 0.353983E+09 0.282791E+09 91330373.15 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 44969283.45 0.159105E+09 42944949.46 0.00 42944949.46 0.00 0.00
February 28505234.56 0.141751E+09 44199004.85 0.00 44199004.85 0.00 0.00
March 75209227.30 0.135265E+09 65045237.58 2573.27 65042664.31 0.00 0.00
April 0.156673E+09 52622517.15 77090857.89 1135053.46 75955804.43 0.00 0.00
May 0.221138E+09 28578151.11 93441433.49 7934259.35 85507174.14 0.00 0.00
June 0.326954E+09 5932446.51 0.104430E+09 19081199.32 85349110.47 0.00 0.00
July 0.303174E+09 4151725.71 92312481.83 9919050.97 82393430.86 0.00 0.00
August 0.250834E+09 5135567.25 74279179.59 1823766.12 72455413.47 0.00 0.00
September 0.202303E+09 9337060.59 67785290.05 41951.47 67743338.59 0.00 0.00
October 0.103089E+09 83022949.90 54159300.98 0.00 54159300.98 0.00 0.00
November 44793566.67 0.136219E+09 43668987.75 0.00 43668987.75 0.00 0.00
December 27791154.22 0.200822E+09 40114513.77 0.00 40114513.77 0.00 0.00
               
Annual Sum or Average 0.178543E+10 0.961943E+09 0.799472E+09 39937853.95 0.759534E+09 0.00 0.00
Minimum of Months 27791154.22 4151725.71 40114513.77 0.00 40114513.77 0.00 0.00
Maximum of Months 0.326954E+09 0.200822E+09 0.104430E+09 19081199.32 85507174.14 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.112484E+10 0.524079E+09 0.766505E+09 0.556878E+09 0.209627E+09 0.00 0.00
February 0.697192E+09 0.460402E+09 0.540277E+09 0.334558E+09 0.205719E+09 0.00 0.00
March 0.894294E+09 0.438188E+09 0.628463E+09 0.321558E+09 0.306905E+09 0.00 0.00
April 0.135019E+10 0.187357E+09 0.745596E+09 0.408534E+09 0.337062E+09 0.00 0.00
May 0.142850E+10 0.113176E+09 0.725583E+09 0.374306E+09 0.351277E+09 0.00 0.00
June 0.166768E+10 27842868.77 0.705417E+09 0.378400E+09 0.327016E+09 0.00 0.00
July 0.154833E+10 18410556.48 0.635569E+09 0.304666E+09 0.330904E+09 0.00 0.00
August 0.150507E+10 22260150.69 0.636696E+09 0.322574E+09 0.314123E+09 0.00 0.00
September 0.129745E+10 37866460.45 0.587611E+09 0.271747E+09 0.315864E+09 0.00 0.00
October 0.124567E+10 0.278946E+09 0.730860E+09 0.471799E+09 0.259061E+09 0.00 0.00
November 0.973891E+09 0.448806E+09 0.671635E+09 0.464986E+09 0.206650E+09 0.00 0.00
December 0.953391E+09 0.652071E+09 0.697993E+09 0.499406E+09 0.198587E+09 0.00 0.00
               
Annual Sum or Average 0.146865E+11 0.320941E+10 0.807221E+10 0.470941E+10 0.336279E+10 0.00 0.00
Minimum of Months 0.697192E+09 18410556.48 0.540277E+09 0.271747E+09 0.198587E+09 0.00 0.00
Maximum of Months 0.166768E+10 0.652071E+09 0.766505E+09 0.556878E+09 0.351277E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.487148E+09 0.514817E+09 0.377613E+09 0.203319E+09 0.174294E+09 0.00 0.00
February 0.378912E+09 0.454653E+09 0.346092E+09 0.167343E+09 0.178749E+09 0.00 0.00
March 0.631451E+09 0.440300E+09 0.481151E+09 0.205720E+09 0.275431E+09 0.00 0.00
April 0.113830E+10 0.190217E+09 0.647778E+09 0.329970E+09 0.317808E+09 0.00 0.00
May 0.136484E+10 0.113547E+09 0.708304E+09 0.360901E+09 0.347403E+09 0.00 0.00
June 0.169244E+10 27992835.43 0.726118E+09 0.393870E+09 0.332248E+09 0.00 0.00
July 0.153997E+10 18462762.21 0.635953E+09 0.306130E+09 0.329823E+09 0.00 0.00
August 0.139153E+10 24005927.81 0.587340E+09 0.284806E+09 0.302534E+09 0.00 0.00
September 0.107793E+10 39724144.68 0.476868E+09 0.189187E+09 0.287681E+09 0.00 0.00
October 0.794021E+09 0.282353E+09 0.474341E+09 0.247359E+09 0.226982E+09 0.00 0.00
November 0.454083E+09 0.444419E+09 0.357413E+09 0.181731E+09 0.175682E+09 0.00 0.00
December 0.369568E+09 0.638777E+09 0.335979E+09 0.172873E+09 0.163106E+09 0.00 0.00
               
Annual Sum or Average 0.113202E+11 0.318927E+10 0.615495E+10 0.304321E+10 0.311174E+10 0.00 0.00
Minimum of Months 0.369568E+09 18462762.21 0.335979E+09 0.167343E+09 0.163106E+09 0.00 0.00
Maximum of Months 0.169244E+10 0.638777E+09 0.726118E+09 0.393870E+09 0.347403E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.127361E+10 0.687790E+09 0.860015E+09 0.612730E+09 0.247286E+09 0.00 0.00
February 0.667146E+09 0.595072E+09 0.528015E+09 0.289790E+09 0.238224E+09 0.00 0.00
March 0.778795E+09 0.599054E+09 0.537094E+09 0.200762E+09 0.336332E+09 0.00 0.00
April 0.989734E+09 0.296960E+09 0.503505E+09 0.141072E+09 0.362433E+09 0.00 0.00
May 0.961651E+09 0.192594E+09 0.434765E+09 57604611.69 0.377160E+09 0.00 0.00
June 0.122493E+10 59295807.78 0.416551E+09 55856451.63 0.360695E+09 0.00 0.00
July 0.117097E+10 41345615.89 0.399265E+09 40435810.09 0.358829E+09 0.00 0.00
August 0.114387E+10 55840361.70 0.407338E+09 73352738.99 0.333986E+09 0.00 0.00
September 0.114225E+10 91256314.32 0.485590E+09 0.143261E+09 0.342329E+09 0.00 0.00
October 0.116554E+10 0.410546E+09 0.679193E+09 0.388962E+09 0.290232E+09 0.00 0.00
November 0.106498E+10 0.597777E+09 0.733746E+09 0.490890E+09 0.242857E+09 0.00 0.00
December 0.110639E+10 0.831866E+09 0.801172E+09 0.565893E+09 0.235279E+09 0.00 0.00
               
Annual Sum or Average 0.126899E+11 0.445940E+10 0.678625E+10 0.306061E+10 0.372564E+10 0.00 0.00
Minimum of Months 0.667146E+09 41345615.89 0.399265E+09 40435810.09 0.235279E+09 0.00 0.00
Maximum of Months 0.127361E+10 0.831866E+09 0.860015E+09 0.612730E+09 0.377160E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.117009E+10 0.537088E+09 0.782721E+09 0.565485E+09 0.217236E+09 0.00 0.00
February 0.640996E+09 0.466862E+09 0.498285E+09 0.287991E+09 0.210294E+09 0.00 0.00
March 0.861773E+09 0.459610E+09 0.593196E+09 0.290214E+09 0.302982E+09 0.00 0.00
April 0.134081E+10 0.202592E+09 0.734505E+09 0.388376E+09 0.346129E+09 0.00 0.00
May 0.138292E+10 0.123011E+09 0.694431E+09 0.337345E+09 0.357087E+09 0.00 0.00
June 0.162243E+10 29269275.41 0.684686E+09 0.346412E+09 0.338274E+09 0.00 0.00
July 0.139347E+10 19423595.23 0.547106E+09 0.212292E+09 0.334813E+09 0.00 0.00
August 0.136722E+10 21517376.02 0.555835E+09 0.248047E+09 0.307788E+09 0.00 0.00
September 0.122399E+10 36893692.40 0.543814E+09 0.229081E+09 0.314733E+09 0.00 0.00
October 0.119288E+10 0.282826E+09 0.694021E+09 0.436513E+09 0.257508E+09 0.00 0.00
November 0.102884E+10 0.457424E+09 0.696397E+09 0.480919E+09 0.215478E+09 0.00 0.00
December 0.951578E+09 0.664113E+09 0.683759E+09 0.480526E+09 0.203233E+09 0.00 0.00
               
Annual Sum or Average 0.141770E+11 0.330063E+10 0.770875E+10 0.430320E+10 0.340555E+10 0.00 0.00
Minimum of Months 0.640996E+09 19423595.23 0.498285E+09 0.212292E+09 0.203233E+09 0.00 0.00
Maximum of Months 0.162243E+10 0.664113E+09 0.782721E+09 0.565485E+09 0.357087E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.569694E+09 0.558644E+09 0.393828E+09 0.211926E+09 0.181903E+09 0.00 0.00
February 0.343120E+09 0.477487E+09 0.304099E+09 0.120775E+09 0.183324E+09 0.00 0.00
March 0.607761E+09 0.469586E+09 0.445884E+09 0.174376E+09 0.271508E+09 0.00 0.00
April 0.113651E+10 0.204705E+09 0.636687E+09 0.309812E+09 0.326875E+09 0.00 0.00
May 0.132453E+10 0.115855E+09 0.677152E+09 0.323940E+09 0.353213E+09 0.00 0.00
June 0.164845E+10 27017860.61 0.705388E+09 0.361882E+09 0.343505E+09 0.00 0.00
July 0.138572E+10 18385255.04 0.547489E+09 0.213756E+09 0.333733E+09 0.00 0.00
August 0.125702E+10 22852889.94 0.506479E+09 0.210280E+09 0.296199E+09 0.00 0.00
September 0.101180E+10 39093983.89 0.433071E+09 0.146521E+09 0.286550E+09 0.00 0.00
October 0.762181E+09 0.296273E+09 0.437501E+09 0.212073E+09 0.225428E+09 0.00 0.00
November 0.539570E+09 0.477809E+09 0.382175E+09 0.197665E+09 0.184511E+09 0.00 0.00
December 0.410875E+09 0.688445E+09 0.321745E+09 0.153993E+09 0.167752E+09 0.00 0.00
               
Annual Sum or Average 0.109972E+11 0.339615E+10 0.579150E+10 0.263700E+10 0.315450E+10 0.00 0.00
Minimum of Months 0.343120E+09 18385255.04 0.304099E+09 0.120775E+09 0.167752E+09 0.00 0.00
Maximum of Months 0.164845E+10 0.688445E+09 0.705388E+09 0.361882E+09 0.353213E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.999741E+09 0.278183E+09 0.649066E+09 0.518528E+09 0.130538E+09 0.00 0.00
February 0.508914E+09 0.244404E+09 0.365808E+09 0.245238E+09 0.120570E+09 0.00 0.00
March 0.508935E+09 0.238779E+09 0.335275E+09 0.169892E+09 0.165382E+09 0.00 0.00
April 0.574325E+09 0.100553E+09 0.284767E+09 0.117303E+09 0.167464E+09 0.00 0.00
May 0.469984E+09 58937734.31 0.196619E+09 34202726.45 0.162417E+09 0.00 0.00
June 0.537932E+09 12518009.60 0.161060E+09 12287840.18 0.148772E+09 0.00 0.00
July 0.549401E+09 8815810.18 0.168647E+09 16034777.14 0.152612E+09 0.00 0.00
August 0.605727E+09 9847902.11 0.208539E+09 58731992.40 0.149807E+09 0.00 0.00
September 0.668822E+09 17477789.56 0.286666E+09 0.121159E+09 0.165506E+09 0.00 0.00
October 0.825307E+09 0.143943E+09 0.475485E+09 0.329163E+09 0.146322E+09 0.00 0.00
November 0.826441E+09 0.236441E+09 0.540882E+09 0.415420E+09 0.125462E+09 0.00 0.00
December 0.892158E+09 0.346644E+09 0.604458E+09 0.478892E+09 0.125566E+09 0.00 0.00
               
Annual Sum or Average 0.796769E+10 0.169654E+10 0.427727E+10 0.251685E+10 0.176042E+10 0.00 0.00
Minimum of Months 0.469984E+09 8815810.18 0.161060E+09 12287840.18 0.120570E+09 0.00 0.00
Maximum of Months 0.999741E+09 0.346644E+09 0.649066E+09 0.518528E+09 0.167464E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.274615E+09 0.173201E+10 0.375704E+09 0.00 0.375704E+09 0.00 0.00
February 0.161711E+09 0.158116E+10 0.386675E+09 0.00 0.386675E+09 0.00 0.00
March 0.511658E+09 0.148698E+10 0.569049E+09 22512.27 0.569026E+09 0.00 0.00
April 0.116867E+10 0.669740E+09 0.674430E+09 9930025.34 0.664500E+09 0.00 0.00
May 0.168212E+10 0.417349E+09 0.817473E+09 69412938.91 0.748060E+09 0.00 0.00
June 0.253710E+10 0.134757E+09 0.913609E+09 0.166932E+09 0.746677E+09 0.00 0.00
July 0.227002E+10 99533346.31 0.807597E+09 86776906.14 0.720820E+09 0.00 0.00
August 0.185156E+10 0.138196E+09 0.649832E+09 15955234.21 0.633877E+09 0.00 0.00
September 0.149046E+10 0.219743E+09 0.593020E+09 367012.78 0.592653E+09 0.00 0.00
October 0.728050E+09 0.977737E+09 0.473813E+09 0.00 0.473813E+09 0.00 0.00
November 0.277655E+09 0.151554E+10 0.382039E+09 0.00 0.382039E+09 0.00 0.00
December 0.150861E+09 0.212655E+10 0.350942E+09 0.00 0.350942E+09 0.00 0.00
               
Annual Sum or Average 0.131045E+11 0.110993E+11 0.699418E+10 0.349397E+09 0.664479E+10 0.00 0.00
Minimum of Months 0.150861E+09 99533346.31 0.350942E+09 0.00 0.350942E+09 0.00 0.00
Maximum of Months 0.253710E+10 0.212655E+10 0.913609E+09 0.166932E+09 0.748060E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.250570E+09 0.178247E+10 0.375704E+09 0.00 0.375704E+09 0.00 0.00
February 0.143100E+09 0.163894E+10 0.386675E+09 0.00 0.386675E+09 0.00 0.00
March 0.480399E+09 0.153228E+10 0.569049E+09 22512.27 0.569026E+09 0.00 0.00
April 0.114386E+10 0.689936E+09 0.674430E+09 9930025.34 0.664500E+09 0.00 0.00
May 0.165629E+10 0.430795E+09 0.817473E+09 69412938.91 0.748060E+09 0.00 0.00
June 0.251004E+10 0.140860E+09 0.913609E+09 0.166932E+09 0.746677E+09 0.00 0.00
July 0.224168E+10 0.105448E+09 0.807597E+09 86776906.14 0.720820E+09 0.00 0.00
August 0.182535E+10 0.147004E+09 0.649832E+09 15955234.21 0.633877E+09 0.00 0.00
September 0.146702E+10 0.231752E+09 0.593020E+09 367012.78 0.592653E+09 0.00 0.00
October 0.704404E+09 0.100806E+10 0.473813E+09 0.00 0.473813E+09 0.00 0.00
November 0.255353E+09 0.156271E+10 0.382039E+09 0.00 0.382039E+09 0.00 0.00
December 0.132286E+09 0.219119E+10 0.350942E+09 0.00 0.350942E+09 0.00 0.00
               
Annual Sum or Average 0.128104E+11 0.114614E+11 0.699418E+10 0.349397E+09 0.664479E+10 0.00 0.00
Minimum of Months 0.132286E+09 0.105448E+09 0.350942E+09 0.00 0.350942E+09 0.00 0.00
Maximum of Months 0.251004E+10 0.219119E+10 0.913609E+09 0.166932E+09 0.748060E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.169952E+10 0.120278E+10 0.114407E+10 0.760168E+09 0.383905E+09 0.00 0.00
February 0.111771E+10 0.109811E+10 0.886328E+09 0.501877E+09 0.384451E+09 0.00 0.00
March 0.161362E+10 0.106888E+10 0.110956E+10 0.527249E+09 0.582308E+09 0.00 0.00
April 0.267286E+10 0.525716E+09 0.139330E+10 0.738458E+09 0.654838E+09 0.00 0.00
May 0.299897E+10 0.375037E+09 0.143380E+10 0.735158E+09 0.698645E+09 0.00 0.00
June 0.352690E+10 0.146205E+09 0.143145E+10 0.772218E+09 0.659232E+09 0.00 0.00
July 0.321218E+10 0.111076E+09 0.127145E+10 0.610754E+09 0.660695E+09 0.00 0.00
August 0.304898E+10 0.142096E+09 0.122397E+10 0.607340E+09 0.616627E+09 0.00 0.00
September 0.253560E+10 0.201142E+09 0.106442E+10 0.460908E+09 0.603516E+09 0.00 0.00
October 0.218433E+10 0.710764E+09 0.120514E+10 0.719123E+09 0.486021E+09 0.00 0.00
November 0.150810E+10 0.105400E+10 0.102901E+10 0.646691E+09 0.382315E+09 0.00 0.00
December 0.138407E+10 0.144865E+10 0.103393E+10 0.672254E+09 0.361677E+09 0.00 0.00
               
Annual Sum or Average 0.275028E+11 0.808447E+10 0.142264E+11 0.775220E+10 0.647423E+10 0.00 0.00
Minimum of Months 0.111771E+10 0.111076E+09 0.886328E+09 0.460908E+09 0.361677E+09 0.00 0.00
Maximum of Months 0.352690E+10 0.144865E+10 0.143380E+10 0.772218E+09 0.698645E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.265317E+10 0.121510E+10 0.178102E+10 0.131994E+10 0.461083E+09 0.00 0.00
February 0.136591E+10 0.106849E+10 0.106374E+10 0.624266E+09 0.439472E+09 0.00 0.00
March 0.150875E+10 0.107601E+10 0.104853E+10 0.432478E+09 0.616053E+09 0.00 0.00
April 0.182678E+10 0.543927E+09 0.956085E+09 0.302004E+09 0.654081E+09 0.00 0.00
May 0.167999E+10 0.357246E+09 0.780737E+09 0.110860E+09 0.669877E+09 0.00 0.00
June 0.208867E+10 0.112893E+09 0.723175E+09 88503980.79 0.634671E+09 0.00 0.00
July 0.200836E+10 81504069.35 0.706145E+09 70564670.40 0.635580E+09 0.00 0.00
August 0.203480E+10 0.110798E+09 0.753612E+09 0.154975E+09 0.598637E+09 0.00 0.00
September 0.210923E+10 0.174886E+09 0.933011E+09 0.308543E+09 0.624468E+09 0.00 0.00
October 0.232720E+10 0.717060E+09 0.137280E+10 0.837901E+09 0.534895E+09 0.00 0.00
November 0.220576E+10 0.105332E+10 0.150781E+10 0.105747E+10 0.450334E+09 0.00 0.00
December 0.232729E+10 0.147611E+10 0.165898E+10 0.121905E+10 0.439939E+09 0.00 0.00
               
Annual Sum or Average 0.241359E+11 0.798734E+10 0.132856E+11 0.652656E+10 0.675909E+10 0.00 0.00
Minimum of Months 0.136591E+10 81504069.35 0.706145E+09 70564670.40 0.439472E+09 0.00 0.00
Maximum of Months 0.265317E+10 0.147611E+10 0.178102E+10 0.131994E+10 0.669877E+09 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 14.83 7.47 -0.8 2.99 -0.8 34.08 283.26 0.00
February 12.72 9.35 6.24 2.64 2.53 52.02 191.85 0.02
March 15.42 8.67 1.96 3.53 3.02 74.19 207.67 0.01
April 23.31 10.14 -4.1 3.42 6.81 72.47 350.22 0.00
May 26.31 11.07 -4.9 3.62 8.60 75.22 359.64 0.00
June 31.20 14.28 0.18 3.69 15.53 67.31 396.02 0.00
July 30.42 17.99 9.86 3.72 19.28 82.46 278.62 0.02
August 29.82 18.15 11.14 3.33 18.26 71.82 270.19 0.02
September 27.75 17.59 11.45 3.72 17.29 82.54 200.28 0.01
October 20.87 10.99 1.63 3.42 6.03 49.01 269.00 0.00
November 15.43 8.80 1.49 3.02 1.83 40.49 251.35 0.01
December 11.86 4.25 -5.9 2.21 -4.3 34.74 244.35 0.00
                 
Annual Sum or Average 21.70 11.57 2.33 3.28 7.86 61.39 275.62 0.01
Minimum of Months 11.86 4.25 -5.9 2.21 -4.3 34.08 191.85 0.00
Maximum of Months 31.20 18.15 11.45 3.72 19.28 82.54 396.02 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 29.00 31-JAN-15:00 10.73 -14.0 2.10 7.75 109.00 697.00
February 22.00 18-FEB-14:09 14.42 9.67 5.20 14.10 264.00 225.33
March 28.80 16-MAR-15:20 13.79 1.47 3.77 14.35 156.17 666.17
April 35.00 14-APR-14:00 14.57 -4.0 1.50 19.70 150.00 819.50
May 37.00 15-MAY-16:00 15.57 -2.0 4.60 20.75 127.50 679.00
June 42.00 16-JUN-15:00 16.74 -5.0 5.70 25.49 135.00 753.50
July 40.00 12-JUL-13:00 19.40 7.00 2.10 27.95 147.00 3.00
August 41.00 25-AUG-14:09 17.27 -0.7 3.43 25.74 162.33 768.67
September 38.30 08-SEP-14:00 19.81 10.00 3.00 25.82 142.00 699.00
October 37.00 01-OCT-12:00 19.01 9.00 4.10 27.14 262.50 136.00
November 29.00 01-NOV-14:00 16.20 8.00 2.60 16.49 73.50 907.50
December 26.00 21-DEC-14:00 10.90 -5.0 2.60 7.35 68.50 756.50
                 
Annual Sum or Average                
Minimum of Months 22.00   10.73 -14.0 1.50 7.35 68.50 3.00
Maximum of Months 42.00   19.81 10.00 5.70 27.95 264.00 907.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 0.50 01-JAN-07:00 -1.2 -3.3 3.30 -16.2 17.50 352.00
February 5.00 01-FEB-04:00 3.59 2.00 3.10 -10.7 0.00 0.00
March 0.50 26-MAR-03:00 -2.4 -6.7 2.50 -17.0 0.00 0.00
April 8.00 21-APR-03:00 0.42 -14.0 1.00 -11.7 0.00 0.00
May 12.00 01-MAY-03:00 3.97 -7.0 2.60 -6.2 0.00 0.00
June 18.00 21-JUN-04:00 8.24 -2.0 1.50 3.48 0.00 0.00
July 18.00 01-JUL-05:00 6.53 -9.0 3.10 -1.2 16.00 325.00
August 17.00 05-AUG-17:00 15.02 14.00 5.70 11.46 29.00 0.00
September 16.60 22-SEP-05:00 13.83 12.20 3.00 4.92 0.00 0.00
October 5.00 25-OCT-05:00 0.48 -6.0 3.10 -12.7 0.00 0.00
November 0.00 23-NOV-05:00 -2.5 -6.0 2.10 -17.3 0.00 0.00
December -1.1 07-DEC-04:00 -5.6 -16.0 3.10 -20.8 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -1.1   -5.6 -16.0 1.00 -20.8 0.00 0.00
Maximum of Months 18.00   15.02 14.00 5.70 11.46 29.00 352.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.66 08-JAN-15:00 18.00 16.00 4.60 11.46 102.00 332.00
February 14.73 18-FEB-17:00 16.00 14.00 6.20 10.50 0.00 0.00
March 15.18 17-MAR-10:00 25.50 8.30 2.50 18.46 167.50 459.00
April 15.71 11-APR-14:00 33.00 3.00 2.10 15.94 178.50 758.00
May 15.57 15-MAY-16:00 37.00 -2.0 4.60 20.75 127.50 679.00
June 23.18 17-JUN-15:00 41.00 16.00 3.60 31.13 257.00 9.00
July 23.11 13-JUL-17:00 26.00 22.00 4.60 22.13 79.00 56.50
August 22.19 16-AUG-10:00 35.00 17.00 2.10 24.33 140.50 837.00
September 22.23 01-SEP-11:00 34.40 17.20 4.60 23.82 193.50 725.50
October 21.53 01-OCT-17:00 32.00 17.00 2.10 25.33 30.50 1.50
November 18.59 12-NOV-14:00 20.00 18.00 3.10 15.39 115.00 0.00
December 12.06 12-DEC-12:00 20.00 6.00 1.50 12.60 182.50 6.00
                 
Annual Sum or Average                
Minimum of Months 12.06   16.00 -2.0 1.50 10.50 0.00 0.00
Maximum of Months 23.18   41.00 22.00 6.20 31.13 257.00 837.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.00 08-JAN-15:00 18.00 16.66 4.60 11.46 102.00 332.00
February 14.00 18-FEB-17:00 16.00 14.73 6.20 10.50 0.00 0.00
March 13.30 06-MAR-10:00 14.40 13.70 6.10 10.69 254.50 82.00
April 8.00 15-APR-20:00 23.00 14.00 6.20 7.75 0.00 0.00
May 9.00 26-MAY-02:00 21.00 13.75 3.60 16.30 0.00 0.00
June 16.00 17-JUN-15:00 41.00 23.18 3.60 31.13 257.00 9.00
July 22.00 13-JUL-17:00 26.00 23.11 4.60 22.13 79.00 56.50
August 20.00 09-AUG-17:00 25.00 21.44 5.10 19.17 35.00 0.00
September 20.50 02-SEP-22:10 22.62 21.05 3.18 20.17 0.00 0.00
October 19.00 03-OCT-02:00 23.00 20.15 2.10 10.30 0.00 0.00
November 18.00 12-NOV-14:00 20.00 18.59 3.10 15.39 115.00 0.00
December 10.00 12-DEC-23:00 12.00 10.87 1.50 7.55 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 8.00   12.00 10.87 1.50 7.55 0.00 0.00
Maximum of Months 22.00   41.00 23.18 6.20 31.13 257.00 332.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 18.65 31.23 0.00
February 18.00 13.00 16.00 19.06 29.93 0.00
March 18.00 13.00 16.00 20.99 39.76 0.00
April 18.00 13.00 16.00 24.03 60.89 0.00
May 18.00 13.00 16.00 27.32 65.75 0.00
June 18.00 13.00 16.00 29.99 69.24 0.00
July 18.00 13.00 16.00 31.31 56.42 0.00
August 18.00 13.00 16.00 30.91 52.05 0.00
September 18.00 13.00 16.00 28.91 42.71 0.00
October 18.00 13.00 16.00 25.85 39.20 0.00
November 18.00 13.00 16.00 22.56 30.64 0.00
December 18.00 13.00 16.00 19.93 27.41 0.00
             
Annual Sum or Average 18.00 13.00 16.00 24.99 45.50 0.00
Minimum of Months 18.00 13.00 16.00 18.65 27.41 0.00
Maximum of Months 18.00 13.00 16.00 31.31 69.24 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770478E+10 -0.754279E+10 0.00 0.00 744.00 0.00 -161987629.2 81.21 0.00 0.00
February 0.696230E+10 -0.681597E+10 0.00 0.00 672.00 0.00 -146321798.8 81.21 0.00 0.00
March 0.770338E+10 -0.754146E+10 0.00 0.00 744.00 0.00 -161921234.8 81.21 0.00 0.00
April 0.746496E+10 -0.730858E+10 0.00 0.00 720.00 0.00 -156382444.0 81.21 0.00 0.00
May 0.770430E+10 -0.754279E+10 0.00 0.00 744.00 0.00 -161509746.8 81.21 0.00 0.00
June 0.745674E+10 -0.730053E+10 0.00 0.00 720.00 0.00 -156217636.7 81.21 0.00 0.00
July 0.771227E+10 -0.755085E+10 0.00 0.00 744.00 0.00 -161424234.7 81.21 0.00 0.00
August 0.770424E+10 -0.754281E+10 0.00 0.00 744.00 0.00 -161435283.3 81.21 0.00 0.00
September 0.746618E+10 -0.730993E+10 0.00 0.00 720.00 0.00 -156246270.3 81.21 0.00 0.00
October 0.770313E+10 -0.754144E+10 0.00 0.00 744.00 0.00 -161693552.3 81.21 0.00 0.00
November 0.744914E+10 -0.729243E+10 0.00 0.00 720.00 0.00 -156710094.1 81.21 0.00 0.00
December 0.771300E+10 -0.755086E+10 0.00 0.00 744.00 0.00 -162140399.1 81.21 0.00 0.00
                     
Annual Sum or Average 0.907444E+11 -0.888404E+11 0.00 0.00 8760.00 0.00 -0.190399E+10 81.21 0.00 0.00
Minimum of Months 0.696230E+10 -0.755086E+10 0.00 0.00 672.00 0.00 -162140399.1 81.21 0.00 0.00
Maximum of Months 0.771300E+10 -0.681597E+10 0.00 0.00 744.00 0.00 -146321798.8 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYSLAUNDRY HPWH TANK

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.382773E+11 -0.104633E+12 0.00 0.00 744.00 0.00 -775173231.5 81.67 0.00 0.00
February 0.334173E+11 -0.938768E+11 0.00 0.00 672.00 0.00 -714761227.6 81.68 0.00 0.00
March 0.330274E+11 -0.100666E+12 0.00 0.00 744.00 0.00 -770119075.9 81.67 0.00 0.00
April 0.219693E+11 -0.924524E+11 0.00 0.00 720.00 0.00 -686430617.7 81.68 0.00 0.00
May 0.152680E+11 -0.899623E+11 0.00 0.00 744.00 0.00 -686890165.5 81.67 0.00 0.00
June 0.621109E+10 -0.827034E+11 0.00 0.00 720.00 0.00 -627528271.4 81.68 0.00 0.00
July 0.208187E+10 -0.832655E+11 0.00 0.00 744.00 0.00 -654731490.1 81.68 0.00 0.00
August 0.286586E+10 -0.839337E+11 0.00 0.00 744.00 0.00 -659691541.9 81.68 0.00 0.00
September 0.692823E+10 -0.844744E+11 0.00 0.00 720.00 0.00 -654031456.3 81.67 0.00 0.00
October 0.203719E+11 -0.924481E+11 0.00 0.00 744.00 0.00 -728036071.1 81.68 0.00 0.00
November 0.293439E+11 -0.948505E+11 0.00 0.00 720.00 0.00 -745358706.1 81.67 0.00 0.00
December 0.405699E+11 -0.102466E+12 0.00 0.00 744.00 0.00 -797549778.7 81.67 0.00 0.00
                     
Annual Sum or Average 0.250332E+12 -0.110573E+13 0.00 0.00 8760.00 0.00 -0.850030E+10 81.68 0.00 0.00
Minimum of Months 0.208187E+10 -0.104633E+12 0.00 0.00 672.00 0.00 -797549778.7 81.67 0.00 0.00
Maximum of Months 0.405699E+11 -0.827034E+11 0.00 0.00 744.00 0.00 -627528271.4 81.68 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 HPWH TANK

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January -0.230704E+10 -0.603625E+11 0.00 0.00 744.00 0.00 -0.119291E+10 59.36 0.00 0.00
February -0.206131E+10 -0.539864E+11 0.00 0.00 672.00 0.00 -0.111283E+10 59.37 0.00 0.00
March -0.214362E+10 -0.569923E+11 0.00 0.00 744.00 0.00 -0.118204E+10 59.40 0.00 0.00
April -0.202927E+10 -0.508397E+11 0.00 0.00 720.00 0.00 -0.100333E+10 59.43 0.00 0.00
May -0.171256E+10 -0.477275E+11 0.00 0.00 744.00 0.00 -984788288.7 59.48 0.00 0.00
June -0.146481E+10 -0.424280E+11 0.00 0.00 720.00 0.00 -864693561.9 59.51 0.00 0.00
July -0.139935E+10 -0.418751E+11 0.00 0.00 744.00 0.00 -909120989.6 59.53 0.00 0.00
August -0.144585E+10 -0.425041E+11 0.00 0.00 744.00 0.00 -920923976.3 59.53 0.00 0.00
September -0.160212E+10 -0.439386E+11 0.00 0.00 720.00 0.00 -927844080.2 59.50 0.00 0.00
October -0.185524E+10 -0.498465E+11 0.00 0.00 744.00 0.00 -0.108275E+10 59.46 0.00 0.00
November -0.195891E+10 -0.528857E+11 0.00 0.00 720.00 0.00 -0.114485E+10 59.42 0.00 0.00
December -0.207638E+10 -0.584832E+11 0.00 0.00 744.00 0.00 -0.124729E+10 59.38 0.00 0.00
                     
Annual Sum or Average -0.220565E+11 -0.601870E+12 0.00 0.00 8760.00 0.00 -0.125734E+11 59.45 0.00 0.00
Minimum of Months -0.230704E+10 -0.603625E+11 0.00 0.00 672.00 0.00 -0.124729E+10 59.36 0.00 0.00
Maximum of Months -0.139935E+10 -0.418751E+11 0.00 0.00 744.00 0.00 -864693561.9 59.53 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.87 0.86 01-JAN-07:49 7548.65 38.83 306.67 291.83 1049.88 27.72 175.83 285.67
February 241.00 0.87 0.86 01-FEB-07:49 4376.20 32.33 187.33 264.83 538.29 23.04 122.00 199.33
March 344.33 0.87 0.86 01-MAR-07:49 1012.94 19.32 11.50 321.50 384.40 20.69 124.00 245.67
April 380.33 0.88 0.86 01-APR-08:39 701.83 18.92 0.00 329.83 305.99 20.68 122.67 245.33
May 403.17 0.87 0.86 01-MAY-07:00 566.05 18.71 0.00 352.67 250.58 20.50 53.50 182.83
June 418.17 0.88 0.86 01-JUN-08:09 458.03 18.07 0.00 354.67 208.58 19.90 8.83 81.00
July 399.50 0.88 0.86 01-JUL-09:09 564.08 18.14 0.00 356.00 240.66 19.94 40.33 154.17
August 361.83 0.88 0.86 01-AUG-08:50 629.07 18.52 0.00 333.00 267.69 20.29 62.83 173.17
September 350.17 0.87 0.86 01-SEP-07:19 927.38 18.84 0.00 317.83 371.98 20.61 128.50 253.50
October 348.00 0.87 0.86 01-OCT-07:49 2543.93 25.40 135.17 318.67 414.12 21.33 111.83 263.17
November 288.50 0.87 0.86 01-NOV-07:49 7196.60 37.59 282.50 286.00 822.19 26.25 149.50 261.50
December 290.67 0.86 0.86 01-DEC-07:40 6943.82 38.65 287.33 280.17 1201.32 28.46 172.67 271.17
                         
Annual Sum or Average 4135.50 0.87     2463.19 24.24 1210.50 3807.00 470.50 22.13 1272.50 2616.50
Minimum of Months 241.00 0.86 0.86   458.03 18.07 0.00 264.83 208.58 19.90 8.83 81.00
Maximum of Months 418.17 0.88 0.86   7548.65 38.83 306.67 356.00 1201.32 28.46 175.83 285.67



Table of Contents

Report: DaylightingReportMonthly

For: CAFE_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.25 0.22 01-JAN-07:49 7971.05 38.88 306.67 294.50 1469.74 27.24 157.17 291.50
February 241.00 0.26 0.22 01-FEB-07:49 4690.33 32.30 187.33 271.67 852.00 22.97 122.17 241.33
March 344.33 0.27 0.22 01-MAR-07:30 1228.41 19.82 15.00 336.17 600.44 21.02 161.17 300.83
April 380.33 0.28 0.22 01-APR-07:19 879.80 19.53 6.50 341.33 483.58 21.07 181.50 315.67
May 403.17 0.26 0.22 01-MAY-06:00 692.89 19.54 0.00 373.33 377.09 21.09 159.00 333.17
June 418.17 0.27 0.22 01-JUN-06:49 563.05 18.98 0.00 378.17 313.32 20.58 59.67 332.17
July 399.50 0.27 0.22 01-JUL-07:19 675.12 19.06 0.00 380.50 351.37 20.61 123.50 319.50
August 361.83 0.27 0.22 01-AUG-07:30 769.63 19.31 0.17 352.17 407.88 20.85 123.00 305.50
September 350.17 0.27 0.22 01-SEP-06:00 1118.13 19.48 10.00 330.33 562.20 21.03 172.67 299.33
October 348.00 0.26 0.22 01-OCT-07:19 2836.22 25.50 135.17 325.00 705.54 21.33 121.50 305.17
November 288.50 0.24 0.22 01-NOV-07:30 7574.02 37.66 282.67 290.83 1200.00 25.90 140.83 274.83
December 290.67 0.24 0.22 01-DEC-07:30 7361.07 38.71 287.67 284.50 1616.80 28.02 162.67 277.33
                         
Annual Sum or Average 4135.50 0.26     2689.86 24.74 1231.17 3958.50 696.63 22.37 1684.83 3596.33
Minimum of Months 241.00 0.24 0.22   563.05 18.98 0.00 271.67 313.32 20.58 59.67 241.33
Maximum of Months 418.17 0.28 0.22   7971.05 38.88 306.67 380.50 1616.80 28.02 181.50 333.17



Table of Contents

Report: DaylightingReportMonthly

For: DINING_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.70 0.60 01-JAN-10:39 242.49 13.26 0.00 196.50 134.54 16.92 0.00 15.67
February 241.00 0.68 0.60 02-FEB-14:39 315.97 14.16 0.00 210.00 158.01 17.58 0.00 59.00
March 344.33 0.66 0.60 01-MAR-08:09 372.30 15.40 0.00 302.83 179.12 18.67 0.00 134.83
April 380.33 0.63 0.60 01-APR-09:09 417.91 16.43 0.00 339.00 213.58 19.70 11.17 215.00
May 403.17 0.61 0.60 01-MAY-06:10 522.00 18.09 23.33 391.83 272.37 21.68 75.50 324.17
June 418.17 0.61 0.60 01-JUN-05:49 556.90 19.39 60.67 401.50 304.18 23.23 119.33 310.67
July 399.50 0.62 0.60 01-JUL-05:49 541.48 18.86 47.83 399.17 280.91 22.69 101.83 295.83
August 361.83 0.63 0.60 01-AUG-06:19 434.93 16.38 0.00 354.67 213.67 19.94 16.17 181.83
September 350.17 0.64 0.60 01-SEP-06:00 431.51 15.92 0.00 321.50 204.29 19.13 0.00 186.17
October 348.00 0.69 0.60 01-OCT-07:49 286.69 14.27 0.00 224.83 148.91 17.74 0.00 60.67
November 288.50 0.69 0.60 01-NOV-08:39 271.55 13.83 0.00 210.17 142.47 17.43 0.00 29.50
December 290.67 0.70 0.60 01-DEC-12:20 251.40 13.39 0.00 191.00 135.46 17.08 0.00 13.33
                         
Annual Sum or Average 4135.50 0.65     400.85 16.05 131.83 3543.00 206.28 19.59 324.00 1826.67
Minimum of Months 241.00 0.61 0.60   242.49 13.26 0.00 191.00 134.54 16.92 0.00 13.33
Maximum of Months 418.17 0.70 0.60   556.90 19.39 60.67 401.50 304.18 23.23 119.33 324.17



Table of Contents

Report: DaylightingReportMonthly

For: BANQUET_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.70 0.60 01-JAN-10:39 242.49 13.26 0.00 196.50 134.54 16.92 0.00 15.67
February 241.00 0.68 0.60 02-FEB-14:39 315.97 14.16 0.00 210.00 158.01 17.58 0.00 59.00
March 344.33 0.66 0.60 01-MAR-08:09 372.30 15.40 0.00 302.83 179.12 18.67 0.00 134.83
April 380.33 0.63 0.60 01-APR-09:09 417.91 16.43 0.00 339.00 213.58 19.70 11.17 215.00
May 403.17 0.61 0.60 01-MAY-06:10 522.00 18.09 23.33 391.83 272.37 21.68 75.50 324.17
June 418.17 0.61 0.60 01-JUN-05:49 556.90 19.39 60.67 401.50 304.18 23.23 119.33 310.67
July 399.50 0.62 0.60 01-JUL-05:49 541.48 18.86 47.83 399.17 280.91 22.69 101.83 295.83
August 361.83 0.63 0.60 01-AUG-06:19 434.93 16.38 0.00 354.67 213.67 19.94 16.17 181.83
September 350.17 0.64 0.60 01-SEP-06:00 431.51 15.92 0.00 321.50 204.29 19.13 0.00 186.17
October 348.00 0.69 0.60 01-OCT-07:49 286.69 14.27 0.00 224.83 148.91 17.74 0.00 60.67
November 288.50 0.69 0.60 01-NOV-08:39 271.55 13.83 0.00 210.17 142.47 17.43 0.00 29.50
December 290.67 0.70 0.60 01-DEC-12:20 251.40 13.39 0.00 191.00 135.46 17.08 0.00 13.33
                         
Annual Sum or Average 4135.50 0.65     400.85 16.05 131.83 3543.00 206.28 19.59 324.00 1826.67
Minimum of Months 241.00 0.61 0.60   242.49 13.26 0.00 191.00 134.54 16.92 0.00 13.33
Maximum of Months 418.17 0.70 0.60   556.90 19.39 60.67 401.50 304.18 23.23 119.33 324.17



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.470862E+11 132540.70 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.515978E+11 118582.95 02-FEB-07:20 0.00 0.00 0.00 0.00 0.00
March 0.348975E+11 121688.82 25-MAR-23:10 0.00 0.00 0.00 0.00 0.00
April 0.176759E+10 75279.70 21-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 18787969.24 9187.62 01-MAY-04:00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.119255E+11 113531.24 25-OCT-07:30 0.00 0.00 0.00 0.00 0.00
November 0.322999E+11 119591.84 04-NOV-06:20 0.00 0.00 0.00 0.00 0.00
December 0.625171E+11 119223.25 16-DEC-23:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.242110E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.625171E+11 132540.70   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.121547E+09 1161.77 01-JAN-06:00 0.00 0.00 0.00 0.00 0.00
February 0.518533E+09 1192.14 13-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 0.371022E+09 1421.58 27-MAR-06:05 0.00 0.00 0.00 0.00 0.00
April 2543979.26 246.82 21-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 40691634.05 691.54 25-OCT-06:30 0.00 0.00 0.00 0.00 0.00
November 0.113292E+09 867.25 23-NOV-07:00 0.00 0.00 0.00 0.00 0.00
December 0.467570E+09 1486.64 16-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.163520E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.518533E+09 1486.64   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 2001.00 3.34 12-FEB-16:00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2001.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 2001.00 3.34   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 59319165.52 696.37 01-JAN-06:00 0.00 0.00 0.00 0.00 0.00
February 0.100254E+09 452.79 13-FEB-11:33 0.00 0.00 0.00 0.00 0.00
March 71925324.66 662.14 27-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 9597857.86 331.38 24-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.269802E+09 792.19 07-DEC-05:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.510899E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.269802E+09 792.19   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 39782279.59 459.32 01-JAN-06:00 0.00 0.00 0.00 0.00 0.00
February 89635843.52 273.05 12-FEB-18:00 0.00 0.00 0.00 0.00 0.00
March 58828038.59 386.01 27-MAR-06:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 8681590.65 203.17 24-NOV-06:00 0.00 0.00 0.00 0.00 0.00
December 0.197283E+09 494.22 07-DEC-05:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.394211E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.197283E+09 494.22   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 13245836.98 1057.66 02-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 24255521.32 1003.08 13-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 15061398.31 1019.39 27-MAR-04:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 1349165.22 333.71 23-OCT-04:00 0.00 0.00 0.00 0.00 0.00
November 10432699.96 927.11 24-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 52413087.53 1160.43 07-DEC-05:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.116758E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 52413087.53 1160.43   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 49607490.91 1962.28 12-FEB-16:00 0.00 0.00 0.00 0.00 0.00
March 8931317.78 1653.30 27-MAR-08:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 170876.58 284.79 13-NOV-11:50 0.00 0.00 0.00 0.00 0.00
December 1174336.58 535.66 12-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 59884021.84     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 49607490.91 1962.28   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 68279192.49 2827.75 02-JAN-07:20 0.00 0.00 0.00 0.00 0.00
February 0.246537E+09 3214.22 12-FEB-16:00 0.00 0.00 0.00 0.00 0.00
March 4470882.70 1104.61 27-MAR-08:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.356957E+09 3667.07 18-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.676244E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.356957E+09 3667.07   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.152044E+09 2574.70 01-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.361126E+09 1795.19 13-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 0.215803E+09 2253.21 27-MAR-06:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 2396164.65 532.78 26-OCT-06:30 0.00 0.00 0.00 0.00 0.00
November 58283703.58 1708.25 24-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.814344E+09 3068.62 07-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.160400E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.814344E+09 3068.62   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 7757.08 0.27 08-JAN-02:30 0.00 0.00 0.00 0.00 0.00
February 4447.77 0.27 25-FEB-14:00 0.00 0.00 0.00 0.00 0.00
March 11148.34 0.27 15-MAR-16:00 0.00 0.00 0.00 0.00 0.00
April 20059.15 0.27 17-APR-09:10 0.00 0.00 0.00 0.00 0.00
May 20155.90 0.27 06-MAY-08:49 0.00 0.00 0.00 0.00 0.00
June 13501.22 0.27 08-JUN-17:00 0.00 0.00 0.00 0.00 0.00
July 14404.88 0.27 21-JUL-22:40 0.00 0.00 0.00 0.00 0.00
August 10694.92 0.27 15-AUG-01:10 0.00 0.00 0.00 0.00 0.00
September 9250.09 0.27 27-SEP-01:05 0.00 0.00 0.00 0.00 0.00
October 13116.32 0.27 01-OCT-06:20 0.00 0.00 0.00 0.00 0.00
November 12677.87 0.27 03-NOV-15:40 0.00 0.00 0.00 0.00 0.00
December 1143834.25 111.49 07-DEC-05:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1281047.79     0.00 0.00 0.00 0.00 0.00
Minimum of Months 4447.77 0.27   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1143834.25 111.49   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.412392E+09 8248.53 01-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.821395E+09 8452.26 12-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.542210E+09 8523.38 26-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 7512776.68 4302.18 07-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 5913841.81 3202.89 02-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 743171.09 1815.60 13-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 2254866.43 3425.05 27-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 3472805.98 3738.36 07-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 5036730.89 3783.03 26-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 91757679.10 4907.34 29-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.305938E+09 4553.11 25-NOV-19:03 0.00 0.00 0.00 0.00 0.00
December 0.122670E+10 8644.84 06-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.342532E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 743171.09 1815.60   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.122670E+10 8644.84   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.872715E+09 8772.41 01-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.125814E+10 8544.11 09-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.688677E+09 8557.59 26-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 7848510.48 5398.07 05-APR-08:53 0.00 0.00 0.00 0.00 0.00
May 3493644.53 4012.67 19-MAY-08:14 0.00 0.00 0.00 0.00 0.00
June 724714.54 4997.26 13-JUN-08:14 0.00 0.00 0.00 0.00 0.00
July 1174682.37 2366.53 18-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 2554765.22 3465.72 24-AUG-08:24 0.00 0.00 0.00 0.00 0.00
September 2502225.90 3895.28 16-SEP-08:54 0.00 0.00 0.00 0.00 0.00
October 0.154199E+09 7073.69 25-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.600248E+09 8667.73 23-NOV-09:02 0.00 0.00 0.00 0.00 0.00
December 0.216850E+10 8795.13 06-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.576077E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 724714.54 2366.53   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.216850E+10 8795.13   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.173501E+10 35774.81 26-JAN-16:04 0.00 0.00 0.00 0.00 0.00
February 0.153755E+10 45927.54 05-FEB-16:03 0.00 0.00 0.00 0.00 0.00
March 0.902097E+09 43700.79 12-MAR-15:04 0.00 0.00 0.00 0.00 0.00
April 94573985.22 33718.01 01-APR-08:53 0.00 0.00 0.00 0.00 0.00
May 44031620.68 29812.33 02-MAY-08:44 0.00 0.00 0.00 0.00 0.00
June 7148784.18 14061.79 27-JUN-08:06 0.00 0.00 0.00 0.00 0.00
July 11808256.74 14338.53 27-JUL-08:16 0.00 0.00 0.00 0.00 0.00
August 22928617.10 22939.80 22-AUG-08:06 0.00 0.00 0.00 0.00 0.00
September 19389619.55 19091.83 23-SEP-08:55 0.00 0.00 0.00 0.00 0.00
October 0.162760E+09 37020.28 12-OCT-15:04 0.00 0.00 0.00 0.00 0.00
November 0.107479E+10 36616.13 25-NOV-16:03 0.00 0.00 0.00 0.00 0.00
December 0.564258E+10 49492.66 06-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.112547E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 7148784.18 14061.79   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.564258E+10 49492.66   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.473810E+09 4183.00 20-JAN-16:04 0.00 0.00 0.00 0.00 0.00
February 0.772723E+09 8049.26 12-FEB-19:02 0.00 0.00 0.00 0.00 0.00
March 0.510305E+09 4236.71 07-MAR-19:03 0.00 0.00 0.00 0.00 0.00
April 3017686.85 2992.33 29-APR-08:04 0.00 0.00 0.00 0.00 0.00
May 519778.82 3528.94 26-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 9715.20 97.15 16-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 202876.85 1712.57 05-AUG-18:05 0.00 0.00 0.00 0.00 0.00
September 193334.01 1118.68 03-SEP-18:05 0.00 0.00 0.00 0.00 0.00
October 85812891.83 4028.04 27-OCT-15:04 0.00 0.00 0.00 0.00 0.00
November 0.359916E+09 4257.72 08-NOV-19:04 0.00 0.00 0.00 0.00 0.00
December 0.121867E+10 5124.00 11-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.342518E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.121867E+10 8049.26   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.926023E+09 8228.86 01-JAN-19:02 0.00 0.00 0.00 0.00 0.00
February 0.111214E+10 8231.71 12-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.637109E+09 4660.59 08-MAR-16:03 0.00 0.00 0.00 0.00 0.00
April 5172345.02 3401.42 27-APR-21:54 0.00 0.00 0.00 0.00 0.00
May 270091.72 3292.31 25-MAY-08:14 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 509.88 5.10 16-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 50488.59 563.04 05-AUG-08:56 0.00 0.00 0.00 0.00 0.00
September 803318.40 2056.34 20-SEP-06:05 0.00 0.00 0.00 0.00 0.00
October 0.138959E+09 4236.73 22-OCT-15:04 0.00 0.00 0.00 0.00 0.00
November 0.659324E+09 6521.45 23-NOV-19:02 0.00 0.00 0.00 0.00 0.00
December 0.204811E+10 8280.74 07-DEC-17:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.552796E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.204811E+10 8280.74   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.218315E+09 2591.05 01-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.350215E+09 2530.01 12-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.236674E+09 2560.05 26-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 5883990.05 1182.38 18-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 1723866.44 1519.68 09-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 290221.46 960.53 14-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 594836.60 862.03 27-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 915192.94 897.94 07-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 1541844.62 912.38 14-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 63318323.64 2398.98 25-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.170783E+09 2514.84 24-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.506548E+09 2599.33 06-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.155680E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 290221.46 862.03   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.506548E+09 2599.33   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.393981E+09 2618.43 01-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.499760E+09 2557.70 09-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.283939E+09 2568.08 26-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 4799969.67 1469.68 24-APR-08:53 0.00 0.00 0.00 0.00 0.00
May 1112344.26 1604.76 14-MAY-08:43 0.00 0.00 0.00 0.00 0.00
June 293019.98 954.56 13-JUN-08:14 0.00 0.00 0.00 0.00 0.00
July 418300.70 1018.60 02-JUL-08:14 0.00 0.00 0.00 0.00 0.00
August 624555.80 788.36 30-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 1152502.24 1016.10 25-SEP-08:24 0.00 0.00 0.00 0.00 0.00
October 92039054.43 2537.91 25-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.286143E+09 2605.27 23-NOV-09:02 0.00 0.00 0.00 0.00 0.00
December 0.822012E+09 2611.22 16-DEC-09:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.238628E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 293019.98 788.36   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.822012E+09 2618.43   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.157883E+09 3466.04 01-JAN-19:05 0.00 0.00 0.00 0.00 0.00
February 0.519397E+09 6969.60 07-FEB-16:04 0.00 0.00 0.00 0.00 0.00
March 0.491779E+09 11824.81 27-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 14221834.12 4879.14 19-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 11185341.99 4882.12 16-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 4235309.87 4753.58 13-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 6059957.19 4572.10 03-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 6373650.94 4992.52 17-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 4111427.96 4449.79 29-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 57734465.49 4794.44 12-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.165882E+09 3927.59 04-NOV-08:03 0.00 0.00 0.00 0.00 0.00
December 0.662584E+09 5795.86 15-DEC-16:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.210145E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 4111427.96 3466.04   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.662584E+09 11824.81   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: SWHSYS1 HPWH DXCOIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.479448E+11 0.479448E+11 50005.68 23-JAN-08:50 50005.68 0.00
February 0.00 0.00 0.429777E+11 0.412571E+11 50632.36 01-FEB-06:15 48537.44 0.00
March 0.00 0.00 0.451658E+11 0.451658E+11 51140.41 01-MAR-06:15 51140.41 0.00
April 0.00 0.00 0.408598E+11 0.408598E+11 55691.74 01-APR-05:17 55691.74 0.00
May 0.00 0.00 0.380775E+11 0.380775E+11 56749.03 01-MAY-06:15 56749.03 0.00
June 0.00 0.00 0.341349E+11 0.341349E+11 60458.41 01-JUN-05:10 60458.41 0.00
July 0.00 0.00 0.338582E+11 0.338582E+11 62130.92 01-JUL-05:08 62130.92 0.00
August 0.00 0.00 0.344209E+11 0.344209E+11 62274.97 31-AUG-05:10 62274.97 0.00
September 0.00 0.00 0.357718E+11 0.357718E+11 62074.83 30-SEP-05:08 62074.83 0.00
October 0.00 0.00 0.396390E+11 0.396390E+11 54713.42 31-OCT-05:15 54713.42 0.00
November 0.00 0.00 0.416766E+11 0.416766E+11 50952.66 30-NOV-06:15 50952.66 0.00
December 0.00 0.00 0.450274E+11 0.450274E+11 45484.54 31-DEC-02:10 45484.54 0.00
                 
Annual Sum or Average 0.00 0.00 0.479554E+12 0.477834E+12       0.00
Minimum of Months 0.00 0.00 0.338582E+11 0.338582E+11 45484.54   45484.54 0.00
Maximum of Months 0.00 0.00 0.479448E+11 0.479448E+11 62274.97   62274.97 0.00



Table of Contents

Report: CoilReportMonthly

For: SWHSYSLAUNDRY HPWH DXCOIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.501268E+11 0.501268E+11 63283.04 23-JAN-17:10 63283.04 0.00
February 0.00 0.00 0.457469E+11 0.439298E+11 64076.57 01-FEB-17:10 61447.19 0.00
March 0.00 0.00 0.509446E+11 0.509446E+11 64719.88 01-MAR-17:10 64719.88 0.00
April 0.00 0.00 0.536847E+11 0.536847E+11 70482.94 01-APR-16:10 70482.94 0.00
May 0.00 0.00 0.566123E+11 0.566123E+11 71821.71 01-MAY-19:20 71821.71 0.00
June 0.00 0.00 0.585014E+11 0.585014E+11 76518.66 01-JUN-16:10 76518.66 0.00
July 0.00 0.00 0.623813E+11 0.623813E+11 78636.46 01-JUL-19:10 78636.46 0.00
August 0.00 0.00 0.623611E+11 0.623611E+11 78818.87 31-AUG-16:10 78818.87 0.00
September 0.00 0.00 0.598770E+11 0.598770E+11 78565.43 30-SEP-16:10 78565.43 0.00
October 0.00 0.00 0.543738E+11 0.543738E+11 69244.15 31-OCT-16:10 69244.15 0.00
November 0.00 0.00 0.490453E+11 0.490453E+11 64482.14 30-NOV-17:10 64482.14 0.00
December 0.00 0.00 0.454228E+11 0.454228E+11 57558.21 31-DEC-21:13 57558.21 0.00
                 
Annual Sum or Average 0.00 0.00 0.649078E+12 0.647261E+12       0.00
Minimum of Months 0.00 0.00 0.454228E+11 0.439298E+11 57558.21   57558.21 0.00
Maximum of Months 0.00 0.00 0.623813E+11 0.623813E+11 78818.87   78818.87 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.104113E+12 0.103683E+12 175247.19 31-JAN-16:30 175247.19 0.02
February 0.00 0.00 0.254135E+11 0.253868E+11 103488.11 18-FEB-14:00 103488.11 0.11
March 0.00 0.00 0.113067E+12 0.113067E+12 191576.16 20-MAR-18:10 191576.16 0.06
April 0.00 0.00 0.312352E+12 0.312352E+12 256058.23 14-APR-18:03 256058.23 0.03
May 0.00 0.00 0.407289E+12 0.407289E+12 267662.90 31-MAY-18:20 267662.90 0.01
June 0.00 0.00 0.517999E+12 0.517076E+12 331934.51 17-JUN-17:17 269326.11 0.30
July 0.00 0.00 0.601837E+12 0.523581E+12 397546.17 13-JUL-18:03 216471.21 0.81
August 0.00 0.00 0.587308E+12 0.515820E+12 428459.16 18-AUG-22:00 200323.79 0.86
September 0.00 0.00 0.539199E+12 0.463913E+12 456570.15 10-SEP-20:40 201614.08 0.86
October 0.00 0.00 0.274308E+12 0.266176E+12 328698.51 02-OCT-20:00 244364.00 0.26
November 0.00 0.00 0.118824E+12 0.105397E+12 194134.92 01-NOV-18:04 194134.92 0.21
December 0.00 0.00 0.554235E+11 0.554235E+11 151356.41 22-DEC-16:08 151356.41 0.00
                 
Annual Sum or Average 0.00 0.00 0.365713E+13 0.340916E+13       0.29
Minimum of Months 0.00 0.00 0.254135E+11 0.253868E+11 103488.11   103488.11 0.00
Maximum of Months 0.00 0.00 0.601837E+12 0.523581E+12 456570.15   269326.11 0.86



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.673483E+10 0.667920E+10 17033.11 31-JAN-16:01 17033.11 0.01
February 0.00 0.00 0.173087E+10 0.173087E+10 13753.19 18-FEB-14:00 13753.19 0.06
March 0.00 0.00 0.788829E+10 0.788829E+10 17335.41 16-MAR-15:01 17335.41 0.04
April 0.00 0.00 0.209353E+11 0.209353E+11 19381.36 14-APR-15:02 19381.36 0.02
May 0.00 0.00 0.271398E+11 0.271398E+11 19739.01 31-MAY-15:02 19739.01 0.01
June 0.00 0.00 0.322302E+11 0.321956E+11 23390.50 17-JUN-16:00 19483.95 0.12
July 0.00 0.00 0.381408E+11 0.329353E+11 30505.29 27-JUL-06:50 15040.28 0.62
August 0.00 0.00 0.378353E+11 0.325800E+11 34897.84 05-AUG-08:10 15756.33 0.68
September 0.00 0.00 0.358848E+11 0.298955E+11 38778.16 02-SEP-21:51 14928.22 0.67
October 0.00 0.00 0.181404E+11 0.174558E+11 28988.59 03-OCT-08:61 17333.13 0.19
November 0.00 0.00 0.850451E+10 0.712220E+10 24612.65 12-NOV-13:40 13863.56 0.17
December 0.00 0.00 0.357415E+10 0.357415E+10 15816.12 25-DEC-16:01 15816.12 0.00
                 
Annual Sum or Average 0.00 0.00 0.238739E+12 0.220132E+12       0.22
Minimum of Months 0.00 0.00 0.173087E+10 0.173087E+10 13753.19   13753.19 0.00
Maximum of Months 0.00 0.00 0.381408E+11 0.329353E+11 38778.16   19739.01 0.68



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.329611E+10 0.312237E+10 15754.45 14-JAN-16:01 15754.45 0.10
February 0.00 0.00 0.103762E+10 0.840036E+09 14984.97 09-FEB-16:01 14984.97 0.15
March 0.00 0.00 0.255717E+10 0.217631E+10 15771.97 16-MAR-15:01 15771.97 0.21
April 0.00 0.00 0.856984E+10 0.838302E+10 15776.38 25-APR-15:02 15776.38 0.07
May 0.00 0.00 0.103449E+11 0.102701E+11 15770.49 10-MAY-18:02 15770.49 0.03
June 0.00 0.00 0.136647E+11 0.127924E+11 15778.25 22-JUN-08:62 15778.25 0.34
July 0.00 0.00 0.134399E+11 0.990940E+10 17326.61 27-JUL-08:61 13047.06 0.78
August 0.00 0.00 0.132283E+11 0.946548E+10 17524.44 04-AUG-08:61 12294.90 0.86
September 0.00 0.00 0.115249E+11 0.777417E+10 18513.58 04-SEP-08:61 11824.44 0.93
October 0.00 0.00 0.708136E+10 0.587925E+10 16801.33 03-OCT-08:61 13571.56 0.36
November 0.00 0.00 0.339622E+10 0.279351E+10 17262.23 12-NOV-16:02 10727.77 0.25
December 0.00 0.00 0.158942E+10 0.158844E+10 15652.64 25-DEC-16:01 15652.64 0.00
                 
Annual Sum or Average 0.00 0.00 0.897304E+11 0.749946E+11       0.34
Minimum of Months 0.00 0.00 0.103762E+10 0.840036E+09 14984.97   10727.77 0.00
Maximum of Months 0.00 0.00 0.136647E+11 0.127924E+11 18513.58   15778.25 0.93



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.759514E+09 0.712087E+09 15638.67 14-JAN-16:01 15638.67 0.04
February 0.00 0.00 0.192908E+09 0.157466E+09 14608.27 28-FEB-16:01 14608.27 0.04
March 0.00 0.00 0.105003E+10 0.863321E+09 15658.15 16-MAR-15:01 15658.15 0.11
April 0.00 0.00 0.701342E+10 0.686176E+10 16067.60 26-APR-08:41 16067.60 0.06
May 0.00 0.00 0.970403E+10 0.964531E+10 17330.45 08-MAY-08:61 17330.45 0.02
June 0.00 0.00 0.135659E+11 0.127242E+11 17448.66 14-JUN-08:61 17448.66 0.33
July 0.00 0.00 0.132667E+11 0.980455E+10 19507.59 27-JUL-08:11 12657.10 0.77
August 0.00 0.00 0.122921E+11 0.875982E+10 19587.47 28-AUG-18:31 13761.79 0.81
September 0.00 0.00 0.992510E+10 0.657654E+10 19965.47 04-SEP-08:51 11553.34 0.83
October 0.00 0.00 0.446806E+10 0.349845E+10 19474.70 03-OCT-08:61 13424.94 0.28
November 0.00 0.00 0.104709E+10 0.783906E+09 17360.35 13-NOV-16:01 11291.22 0.14
December 0.00 0.00 0.229621E+09 0.229508E+09 15538.70 25-DEC-16:01 15538.70 0.00
                 
Annual Sum or Average 0.00 0.00 0.735145E+11 0.606169E+11       0.29
Minimum of Months 0.00 0.00 0.192908E+09 0.157466E+09 14608.27   11291.22 0.00
Maximum of Months 0.00 0.00 0.135659E+11 0.127242E+11 19965.47   17448.66 0.83



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.428116E+11 0.422562E+11 50051.37 14-JAN-13:50 50051.37 0.03
February 0.00 0.00 0.137627E+11 0.120945E+11 37257.07 01-FEB-14:20 37257.07 0.15
March 0.00 0.00 0.166165E+11 0.155726E+11 35158.70 18-MAR-13:50 30163.44 0.07
April 0.00 0.00 0.404277E+11 0.402191E+11 36751.51 14-APR-13:40 36751.51 0.01
May 0.00 0.00 0.409313E+11 0.409313E+11 29724.55 09-MAY-17:20 29724.55 0.00
June 0.00 0.00 0.539388E+11 0.520781E+11 37318.23 28-JUN-17:15 37318.23 0.09
July 0.00 0.00 0.574046E+11 0.365001E+11 36565.36 23-JUL-08:00 22836.89 0.76
August 0.00 0.00 0.606380E+11 0.383410E+11 44698.93 28-AUG-12:30 40218.28 0.85
September 0.00 0.00 0.605291E+11 0.410281E+11 49017.14 28-SEP-13:30 41234.74 0.80
October 0.00 0.00 0.501088E+11 0.437793E+11 50188.51 18-OCT-13:50 50188.51 0.28
November 0.00 0.00 0.365164E+11 0.329734E+11 52279.83 20-NOV-14:30 52279.83 0.22
December 0.00 0.00 0.298966E+11 0.297814E+11 49552.87 25-DEC-13:40 49552.87 0.01
                 
Annual Sum or Average 0.00 0.00 0.503582E+12 0.425555E+12       0.27
Minimum of Months 0.00 0.00 0.137627E+11 0.120945E+11 29724.55   22836.89 0.00
Maximum of Months 0.00 0.00 0.606380E+11 0.520781E+11 52279.83   52279.83 0.85



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.730109E+10 0.655732E+10 91840.99 27-JAN-16:01 91840.99 0.07
February 0.00 0.00 0.614641E+10 0.339814E+10 83937.34 18-FEB-16:01 81490.88 0.28
March 0.00 0.00 0.130380E+11 0.105506E+11 94177.33 16-MAR-15:01 94177.33 0.22
April 0.00 0.00 0.397296E+11 0.388675E+11 94210.62 25-APR-15:02 94210.62 0.06
May 0.00 0.00 0.560950E+11 0.558059E+11 99554.07 20-MAY-08:61 99554.07 0.02
June 0.00 0.00 0.783339E+11 0.730647E+11 101572.92 11-JUN-08:61 101572.92 0.34
July 0.00 0.00 0.834699E+11 0.625755E+11 110338.33 27-JUL-08:11 76907.32 0.74
August 0.00 0.00 0.755523E+11 0.539590E+11 115898.68 28-AUG-18:31 76400.19 0.78
September 0.00 0.00 0.637333E+11 0.431307E+11 113258.32 04-SEP-08:51 72638.84 0.79
October 0.00 0.00 0.303180E+11 0.243818E+11 109791.66 03-OCT-08:61 80615.12 0.26
November 0.00 0.00 0.105451E+11 0.749942E+10 98136.77 13-NOV-16:01 68070.89 0.17
December 0.00 0.00 0.328537E+10 0.324031E+10 89932.30 25-DEC-16:01 89932.30 0.01
                 
Annual Sum or Average 0.00 0.00 0.467548E+12 0.383031E+12       0.31
Minimum of Months 0.00 0.00 0.328537E+10 0.324031E+10 83937.34   68070.89 0.01
Maximum of Months 0.00 0.00 0.834699E+11 0.730647E+11 115898.68   101572.92 0.79



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.313128E+10 0.295795E+10 13785.41 14-JAN-16:01 13785.41 0.10
February 0.00 0.00 0.124973E+10 0.940675E+09 13112.48 09-FEB-16:01 13112.48 0.22
March 0.00 0.00 0.268518E+10 0.223740E+10 13801.46 16-MAR-15:01 13801.46 0.24
April 0.00 0.00 0.872733E+10 0.855249E+10 13805.68 25-APR-15:02 13805.68 0.08
May 0.00 0.00 0.107425E+11 0.106809E+11 13800.08 10-MAY-18:02 13800.08 0.03
June 0.00 0.00 0.140170E+11 0.133729E+11 13806.74 21-JUN-18:02 13806.74 0.35
July 0.00 0.00 0.143522E+11 0.111290E+11 14177.43 09-JUL-08:61 12195.76 0.79
August 0.00 0.00 0.139996E+11 0.105750E+11 15227.59 04-AUG-08:61 10821.42 0.87
September 0.00 0.00 0.119586E+11 0.846719E+10 15763.48 03-SEP-08:61 10102.80 0.94
October 0.00 0.00 0.738676E+10 0.625552E+10 13806.42 20-OCT-15:02 13806.42 0.37
November 0.00 0.00 0.312494E+10 0.260635E+10 15582.49 13-NOV-16:01 9342.06 0.24
December 0.00 0.00 0.160238E+10 0.159491E+10 13696.61 25-DEC-16:01 13696.61 0.00
                 
Annual Sum or Average 0.00 0.00 0.929774E+11 0.793704E+11       0.35
Minimum of Months 0.00 0.00 0.124973E+10 0.940675E+09 13112.48   9342.06 0.00
Maximum of Months 0.00 0.00 0.143522E+11 0.133729E+11 15763.48   13806.74 0.94



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.722099E+09 0.660865E+09 13690.08 14-JAN-16:01 13690.08 0.04
February 0.00 0.00 0.355271E+09 0.221937E+09 12429.67 09-FEB-16:01 12429.67 0.09
March 0.00 0.00 0.124233E+10 0.997063E+09 13707.02 16-MAR-15:01 13707.02 0.15
April 0.00 0.00 0.697595E+10 0.683296E+10 15795.19 14-APR-08:41 15795.19 0.07
May 0.00 0.00 0.977124E+10 0.972326E+10 17203.91 21-MAY-08:61 17203.91 0.02
June 0.00 0.00 0.138127E+11 0.131743E+11 17041.83 13-JUN-07:52 17041.83 0.35
July 0.00 0.00 0.141252E+11 0.109503E+11 17730.22 27-JUL-08:11 12943.07 0.78
August 0.00 0.00 0.129789E+11 0.965962E+10 17436.54 28-AUG-18:31 12087.82 0.82
September 0.00 0.00 0.102597E+11 0.704191E+10 18743.75 04-SEP-08:51 12056.88 0.84
October 0.00 0.00 0.467521E+10 0.370896E+10 17794.70 03-OCT-08:61 13022.24 0.30
November 0.00 0.00 0.916822E+09 0.691117E+09 15043.34 13-NOV-16:01 8552.59 0.12
December 0.00 0.00 0.243553E+09 0.241943E+09 13602.85 25-DEC-16:01 13602.85 0.00
                 
Annual Sum or Average 0.00 0.00 0.760790E+11 0.639042E+11       0.30
Minimum of Months 0.00 0.00 0.243553E+09 0.221937E+09 12429.67   8552.59 0.00
Maximum of Months 0.00 0.00 0.141252E+11 0.131743E+11 18743.75   17203.91 0.84



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.768928E+09 0.735741E+09 4203.09 14-JAN-16:01 4203.09 0.08
February 0.00 0.00 0.244785E+09 0.202265E+09 3997.80 09-FEB-16:01 3997.80 0.12
March 0.00 0.00 0.629867E+09 0.542883E+09 4207.78 16-MAR-15:01 4207.78 0.18
April 0.00 0.00 0.217993E+10 0.213141E+10 4208.97 25-APR-15:02 4208.97 0.07
May 0.00 0.00 0.265007E+10 0.263061E+10 4207.33 10-MAY-18:02 4207.33 0.03
June 0.00 0.00 0.361201E+10 0.337249E+10 4209.11 04-JUN-18:02 4209.11 0.34
July 0.00 0.00 0.352819E+10 0.259303E+10 4793.99 27-JUL-08:61 3374.73 0.78
August 0.00 0.00 0.345140E+10 0.246039E+10 4849.37 04-AUG-08:61 3171.39 0.86
September 0.00 0.00 0.292631E+10 0.194366E+10 5176.47 04-SEP-08:61 3003.08 0.93
October 0.00 0.00 0.169627E+10 0.139032E+10 4677.36 03-OCT-08:61 3501.51 0.35
November 0.00 0.00 0.778248E+09 0.648690E+09 4607.63 12-NOV-16:02 2765.03 0.21
December 0.00 0.00 0.370822E+09 0.370756E+09 4175.88 25-DEC-16:01 4175.88 0.00
                 
Annual Sum or Average 0.00 0.00 0.228368E+11 0.190222E+11       0.33
Minimum of Months 0.00 0.00 0.244785E+09 0.202265E+09 3997.80   2765.03 0.00
Maximum of Months 0.00 0.00 0.361201E+10 0.337249E+10 5176.47   4209.11 0.93



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.161627E+09 0.155307E+09 4168.87 14-JAN-16:01 4168.87 0.02
February 0.00 0.00 40547484.80 33477486.24 3908.96 09-FEB-16:01 3908.96 0.02
March 0.00 0.00 0.251363E+09 0.208248E+09 4173.98 16-MAR-15:01 4173.98 0.09
April 0.00 0.00 0.180650E+10 0.176549E+10 4241.85 26-APR-08:41 4241.85 0.06
May 0.00 0.00 0.251760E+10 0.250166E+10 4572.53 08-MAY-08:61 4572.53 0.02
June 0.00 0.00 0.360752E+10 0.337225E+10 4601.13 14-JUN-08:61 4601.13 0.33
July 0.00 0.00 0.349350E+10 0.257573E+10 5262.68 27-JUL-08:11 3267.67 0.77
August 0.00 0.00 0.322769E+10 0.228902E+10 5290.81 28-AUG-18:31 3611.55 0.81
September 0.00 0.00 0.254267E+10 0.166012E+10 5444.32 04-SEP-08:51 2972.18 0.83
October 0.00 0.00 0.106801E+10 0.820019E+09 5295.25 03-OCT-08:61 3407.90 0.27
November 0.00 0.00 0.219824E+09 0.168781E+09 4700.06 13-NOV-16:01 2965.02 0.10
December 0.00 0.00 48464492.11 48464492.11 4142.19 25-DEC-16:01 4142.19 0.00
                 
Annual Sum or Average 0.00 0.00 0.189853E+11 0.155986E+11       0.28
Minimum of Months 0.00 0.00 40547484.80 33477486.24 3908.96   2965.02 0.00
Maximum of Months 0.00 0.00 0.360752E+10 0.337225E+10 5444.32   4601.13 0.83



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.100092E+11 0.962246E+10 18409.92 14-JAN-16:01 18409.92 0.15
February 0.00 0.00 0.407910E+10 0.324475E+10 17510.56 09-FEB-16:01 17510.56 0.35
March 0.00 0.00 0.504670E+10 0.423207E+10 18428.26 16-MAR-15:01 18428.26 0.32
April 0.00 0.00 0.108396E+11 0.105204E+11 18426.04 12-APR-18:01 18426.04 0.11
May 0.00 0.00 0.114508E+11 0.113594E+11 18425.83 10-MAY-18:02 18425.83 0.03
June 0.00 0.00 0.151459E+11 0.138571E+11 18428.17 16-JUN-08:61 18428.17 0.42
July 0.00 0.00 0.166655E+11 0.123382E+11 20777.39 27-JUL-08:61 14963.58 0.79
August 0.00 0.00 0.172799E+11 0.126056E+11 21167.39 04-AUG-08:61 13988.83 0.86
September 0.00 0.00 0.165638E+11 0.117511E+11 21926.66 04-SEP-08:61 13689.46 0.95
October 0.00 0.00 0.125328E+11 0.109093E+11 19559.93 03-OCT-08:61 15937.97 0.38
November 0.00 0.00 0.882525E+10 0.781353E+10 20178.02 12-NOV-09:02 12166.79 0.30
December 0.00 0.00 0.730529E+10 0.727561E+10 18287.81 25-DEC-16:01 18287.81 0.01
                 
Annual Sum or Average 0.00 0.00 0.135744E+12 0.115529E+12       0.39
Minimum of Months 0.00 0.00 0.407910E+10 0.324475E+10 17510.56   12166.79 0.01
Maximum of Months 0.00 0.00 0.172799E+11 0.138571E+11 21926.66   18428.26 0.95



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 19507.67 153038.25 01-JAN-00:10
February 0.00 0.00 01-FEB-00:05 24519.15 129376.60 03-FEB-07:05
March 0.00 0.00 01-MAR-00:05 14772.63 141317.24 26-MAR-08:03
April 0.00 0.00 01-APR-00:10 729.37 78856.42 21-APR-06:05
May 0.00 0.00 01-MAY-00:05 35.15 36987.42 02-MAY-08:44
June 0.00 0.00 01-JUN-00:05 5.59 13087.83 27-JUN-08:06
July 0.00 0.00 01-JUL-00:10 9.16 12243.17 03-JUL-08:06
August 0.00 0.00 01-AUG-00:05 13.18 15781.92 22-AUG-08:06
September 0.00 0.00 01-SEP-00:05 13.45 13355.82 23-SEP-08:55
October 0.00 0.00 01-OCT-00:10 4737.28 124926.18 25-OCT-08:03
November 0.00 0.00 01-NOV-00:05 13806.15 129653.99 23-NOV-19:03
December 0.00 0.00 01-DEC-00:05 29218.14 162599.47 06-DEC-09:01
             
Annual Sum or Average 0.00     8877.43    
Minimum of Months 0.00 0.00   5.59 12243.17  
Maximum of Months 0.00 0.00   29218.14 162599.47  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 70655.22 409434.49 31-JAN-16:01 0.00 0.00 01-JAN-00:10
February 25430.57 288047.93 09-FEB-16:01 0.00 0.00 01-FEB-00:05
March 64708.87 388609.42 15-MAR-18:01 0.00 0.00 01-MAR-00:05
April 181160.81 472343.03 14-APR-18:03 0.00 0.00 01-APR-00:10
May 223635.64 483834.53 31-MAY-18:03 0.00 0.00 01-MAY-00:05
June 297162.08 552617.69 01-JUN-18:07 0.00 0.00 01-JUN-00:05
July 324951.02 627285.99 13-JUL-18:03 0.00 0.00 01-JUL-00:10
August 316764.52 575686.59 09-AUG-18:03 0.00 0.00 01-AUG-00:05
September 299143.60 654878.94 10-SEP-21:52 0.00 0.00 01-SEP-00:05
October 157578.43 518055.06 01-OCT-18:03 0.00 0.00 01-OCT-00:10
November 77905.53 406666.31 01-NOV-15:03 0.00 0.00 01-NOV-00:05
December 41723.72 364509.58 21-DEC-16:01 0.00 0.00 01-DEC-00:05
             
Annual Sum or Average 174174.68     0.00    
Minimum of Months 25430.57 288047.93   0.00 0.00  
Maximum of Months 324951.02 654878.94   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 22560.38 47235.72 23-JAN-07:40
February 0.00 0.00 01-FEB-00:05 22340.51 47144.79 01-FEB-07:40
March 0.00 0.00 01-MAR-00:05 21300.56 45774.42 01-MAR-07:40
April 0.00 0.00 01-APR-00:10 19629.82 42466.12 03-APR-07:00
May 0.00 0.00 01-MAY-00:05 17834.70 38979.10 01-MAY-06:30
June 0.00 0.00 01-JUN-00:05 16382.63 35369.71 01-JUN-06:30
July 0.00 0.00 01-JUL-00:10 15649.29 32965.93 03-JUL-06:40
August 0.00 0.00 01-AUG-00:05 15884.09 33931.48 31-AUG-06:40
September 0.00 0.00 01-SEP-00:05 16966.62 36761.59 29-SEP-06:40
October 0.00 0.00 01-OCT-00:10 18628.46 40734.79 31-OCT-07:00
November 0.00 0.00 01-NOV-00:05 20424.42 44227.33 30-NOV-07:30
December 0.00 0.00 01-DEC-00:05 21862.94 46590.18 29-DEC-07:40
             
Annual Sum or Average 0.00     19104.03    
Minimum of Months 0.00 0.00   15649.29 32965.93  
Maximum of Months 0.00 0.00   22560.38 47235.72  



Table of Contents

Report: FanReportMonthly

For: SWHSYS1 HPWH FAN

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.564829E+09 0.06 553.22 01-JAN-06:15 0.11
February 0.503216E+09 0.06 553.22 01-FEB-06:15 0.11
March 0.527714E+09 0.06 553.22 01-MAR-06:15 0.11
April 0.445219E+09 0.06 553.22 01-APR-05:17 0.11
May 0.414241E+09 0.06 553.22 01-MAY-06:15 0.11
June 0.352637E+09 0.06 553.22 01-JUN-05:10 0.11
July 0.342246E+09 0.06 553.22 01-JUL-05:08 0.11
August 0.346799E+09 0.06 553.22 01-AUG-05:10 0.11
September 0.359518E+09 0.06 553.22 01-SEP-05:10 0.11
October 0.442719E+09 0.06 553.22 01-OCT-05:10 0.11
November 0.491470E+09 0.06 553.22 01-NOV-05:15 0.11
December 0.583871E+09 0.06 553.22 01-DEC-04:10 0.11
           
Annual Sum or Average 0.537448E+10 0.06      
Minimum of Months 0.342246E+09 0.06 553.22   0.11
Maximum of Months 0.583871E+09 0.06 553.22   0.11



Table of Contents

Report: FanReportMonthly

For: SWHSYSLAUNDRY HPWH FAN

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.557204E+09 0.06 700.51 01-JAN-17:10 0.11
February 0.503205E+09 0.06 700.51 01-FEB-17:10 0.11
March 0.557180E+09 0.06 700.51 01-MAR-17:10 0.11
April 0.540487E+09 0.06 700.51 01-APR-16:10 0.11
May 0.559702E+09 0.06 700.51 01-MAY-16:10 0.11
June 0.541281E+09 0.06 700.51 01-JUN-16:10 0.11
July 0.559020E+09 0.05 700.51 01-JUL-16:10 0.11
August 0.558912E+09 0.06 700.51 01-AUG-16:10 0.11
September 0.540367E+09 0.06 700.51 01-SEP-16:10 0.11
October 0.557540E+09 0.06 700.51 01-OCT-16:10 0.11
November 0.539145E+09 0.06 700.51 01-NOV-16:10 0.11
December 0.557749E+09 0.06 700.51 01-DEC-17:10 0.11
           
Annual Sum or Average 0.657179E+10 0.06      
Minimum of Months 0.503205E+09 0.05 700.51   0.11
Maximum of Months 0.559702E+09 0.06 700.51   0.11



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.271000E+10 0.76 1299.30 03-JAN-16:01 0.97
February 0.244774E+10 0.76 1299.30 10-FEB-19:03 0.96
March 0.271000E+10 0.76 1299.30 04-MAR-09:03 0.96
April 0.262258E+10 0.77 1299.30 03-APR-21:52 0.97
May 0.271000E+10 0.77 1299.30 04-MAY-18:04 0.97
June 0.262258E+10 0.76 1299.30 01-JUN-18:07 0.96
July 0.271000E+10 0.76 1299.30 01-JUL-08:13 0.97
August 0.271000E+10 0.76 1299.30 03-AUG-19:41 0.96
September 0.262258E+10 0.76 1299.30 02-SEP-21:54 0.96
October 0.271000E+10 0.76 1299.30 01-OCT-08:15 0.96
November 0.262258E+10 0.76 1299.30 01-NOV-08:52 0.96
December 0.271000E+10 0.77 1299.30 03-DEC-19:12 0.97
           
Annual Sum or Average 0.319080E+11 0.76      
Minimum of Months 0.244774E+10 0.76 1299.30   0.96
Maximum of Months 0.271000E+10 0.77 1299.30   0.97



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.351513E+11 0.88 24718.19 19-JAN-22:10 1.27
February 0.302624E+11 0.85 20612.11 22-FEB-22:10 1.13
March 0.346638E+11 0.87 26608.29 16-MAR-21:10 1.32
April 0.382987E+11 0.94 32860.89 14-APR-21:10 1.51
May 0.414597E+11 0.96 33070.97 09-MAY-21:10 1.52
June 0.455737E+11 1.03 37304.93 29-JUN-21:10 1.63
July 0.461046E+11 1.01 38040.28 21-JUL-21:10 1.64
August 0.467846E+11 1.02 39246.81 15-AUG-21:10 1.67
September 0.452927E+11 1.02 41407.90 07-SEP-21:10 1.73
October 0.414731E+11 0.96 40126.64 06-OCT-21:10 1.71
November 0.362198E+11 0.90 31191.12 01-NOV-21:10 1.46
December 0.349692E+11 0.88 26333.48 26-DEC-22:10 1.32
           
Annual Sum or Average 0.476254E+12 0.94      
Minimum of Months 0.302624E+11 0.85 20612.11   1.13
Maximum of Months 0.467846E+11 1.03 41407.90   1.73



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205205E+09 0.29 76.61 01-JAN-00:10 0.29
February 0.185347E+09 0.29 76.61 01-FEB-00:05 0.29
March 0.205205E+09 0.29 76.61 01-MAR-00:05 0.29
April 0.198586E+09 0.29 76.61 01-APR-00:10 0.29
May 0.205205E+09 0.29 76.61 01-MAY-00:05 0.29
June 0.198586E+09 0.29 76.61 01-JUN-00:05 0.29
July 0.205205E+09 0.29 76.61 01-JUL-00:10 0.29
August 0.205205E+09 0.29 76.61 01-AUG-00:05 0.29
September 0.198586E+09 0.29 76.61 01-SEP-00:05 0.29
October 0.205205E+09 0.29 76.61 01-OCT-00:10 0.29
November 0.198586E+09 0.29 76.61 01-NOV-00:05 0.29
December 0.205205E+09 0.29 76.61 01-DEC-00:05 0.29
           
Annual Sum or Average 0.241613E+10 0.29      
Minimum of Months 0.185347E+09 0.29 76.61   0.29
Maximum of Months 0.205205E+09 0.29 76.61   0.29



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:10 0.00
February 0.00 0.00 0.00 01-FEB-00:05 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:05 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:10 0.00
February 0.00 0.00 0.00 01-FEB-00:05 0.00
March 0.00 -0.0 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:05 0.00
September 0.00 -0.0 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:05 0.00
December 0.00 -0.0 0.00 01-DEC-00:05 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:10 0.00
February 0.00 -0.0 0.00 01-FEB-00:05 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 -0.0 0.00 01-DEC-00:05 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116283E+10 0.21 612.92 01-JAN-07:05 0.29
February 0.105030E+10 0.21 612.92 01-FEB-07:05 0.29
March 0.116283E+10 0.21 612.92 01-MAR-07:05 0.29
April 0.112532E+10 0.21 612.92 01-APR-06:05 0.29
May 0.116283E+10 0.21 612.92 01-MAY-06:05 0.29
June 0.112532E+10 0.21 612.92 01-JUN-06:05 0.29
July 0.116283E+10 0.21 612.92 01-JUL-06:05 0.29
August 0.116283E+10 0.21 612.92 01-AUG-06:10 0.29
September 0.112532E+10 0.21 612.92 01-SEP-06:10 0.29
October 0.116283E+10 0.21 612.92 01-OCT-06:10 0.29
November 0.112532E+10 0.21 612.92 01-NOV-06:05 0.29
December 0.116283E+10 0.21 612.92 01-DEC-07:05 0.29
           
Annual Sum or Average 0.136914E+11 0.21      
Minimum of Months 0.105030E+10 0.21 612.92   0.29
Maximum of Months 0.116283E+10 0.21 612.92   0.29



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.242220E+09 0.55 844.36 01-JAN-16:01 0.63
February 0.145456E+09 0.48 844.36 01-FEB-16:01 0.63
March 0.212236E+09 0.52 844.36 01-MAR-16:01 0.63
April 0.471379E+09 0.60 844.36 01-APR-08:62 0.63
May 0.550608E+09 0.61 844.36 01-MAY-08:62 0.64
June 0.754745E+09 0.62 844.36 01-JUN-08:61 0.63
July 0.661050E+09 0.62 844.36 01-JUL-08:61 0.64
August 0.660342E+09 0.61 844.36 01-AUG-08:62 0.63
September 0.570126E+09 0.61 844.36 01-SEP-08:61 0.63
October 0.397975E+09 0.58 844.36 01-OCT-08:61 0.63
November 0.231680E+09 0.54 844.36 01-NOV-08:62 0.63
December 0.198849E+09 0.52 844.36 01-DEC-16:01 0.63
           
Annual Sum or Average 0.509666E+10 0.57      
Minimum of Months 0.145456E+09 0.48 844.36   0.63
Maximum of Months 0.754745E+09 0.62 844.36   0.64



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.126344E+09 0.40 838.22 01-JAN-09:01 0.63
February 0.121353E+09 0.41 838.22 01-FEB-16:01 0.63
March 0.129908E+09 0.37 838.22 01-MAR-16:01 0.63
April 0.388506E+09 0.51 838.22 01-APR-08:51 0.63
May 0.513526E+09 0.54 838.22 01-MAY-08:51 0.64
June 0.753670E+09 0.58 838.22 01-JUN-07:21 0.63
July 0.653604E+09 0.60 838.22 01-JUL-08:61 0.64
August 0.609916E+09 0.57 838.22 01-AUG-08:62 0.63
September 0.486462E+09 0.54 838.22 01-SEP-08:61 0.63
October 0.260596E+09 0.44 838.22 01-OCT-08:61 0.63
November 0.119584E+09 0.39 838.22 01-NOV-15:01 0.63
December 0.171542E+09 0.41 838.22 01-DEC-16:01 0.63
           
Annual Sum or Average 0.433501E+10 0.48      
Minimum of Months 0.119584E+09 0.37 838.22   0.63
Maximum of Months 0.753670E+09 0.60 838.22   0.64



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.174997E+10 0.48 2248.50 09-JAN-15:00 0.63
February 0.633522E+09 0.30 1397.73 01-FEB-14:40 0.63
March 0.772018E+09 0.37 1310.98 18-MAR-14:00 0.63
April 0.165120E+10 0.60 1287.50 14-APR-13:40 0.64
May 0.169670E+10 0.63 1079.48 09-MAY-17:20 0.64
June 0.210187E+10 0.63 1340.61 30-JUN-17:13 0.63
July 0.209604E+10 0.63 1249.89 21-JUL-19:10 0.63
August 0.219625E+10 0.63 1463.85 28-AUG-12:30 0.63
September 0.221262E+10 0.63 2558.21 28-SEP-13:30 0.63
October 0.200301E+10 0.57 2445.48 09-OCT-13:40 0.63
November 0.151640E+10 0.48 2346.18 01-NOV-15:03 0.63
December 0.126553E+10 0.39 2119.60 25-DEC-13:30 0.64
           
Annual Sum or Average 0.198951E+11 0.53      
Minimum of Months 0.633522E+09 0.30 1079.48   0.63
Maximum of Months 0.221262E+10 0.63 2558.21   0.64



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.678473E+09 0.36 4988.29 03-JAN-16:01 0.64
February 0.589144E+09 0.40 4988.29 01-FEB-16:01 0.63
March 0.931587E+09 0.36 4988.29 01-MAR-09:02 0.63
April 0.224308E+10 0.46 4988.29 01-APR-08:51 0.64
May 0.307984E+10 0.51 4988.29 01-MAY-08:51 0.64
June 0.444503E+10 0.57 4988.29 01-JUN-07:21 0.63
July 0.415250E+10 0.58 4988.29 01-JUL-08:61 0.64
August 0.371541E+10 0.55 4988.29 01-AUG-08:62 0.63
September 0.320284E+10 0.52 4988.29 01-SEP-08:61 0.63
October 0.169288E+10 0.40 4988.29 01-OCT-07:42 0.63
November 0.748964E+09 0.35 4988.29 01-NOV-08:52 0.63
December 0.724276E+09 0.40 4988.29 01-DEC-16:01 0.63
           
Annual Sum or Average 0.262040E+11 0.45      
Minimum of Months 0.589144E+09 0.35 4988.29   0.63
Maximum of Months 0.444503E+10 0.58 4988.29   0.64



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.226974E+09 0.57 738.42 01-JAN-16:01 0.63
February 0.144824E+09 0.51 738.42 01-FEB-09:02 0.63
March 0.208821E+09 0.55 738.42 01-MAR-16:01 0.63
April 0.477289E+09 0.62 738.42 01-APR-08:62 0.63
May 0.573438E+09 0.62 738.42 01-MAY-08:62 0.64
June 0.777464E+09 0.63 738.42 01-JUN-08:61 0.63
July 0.713137E+09 0.62 738.42 01-JUL-08:61 0.64
August 0.693692E+09 0.62 738.42 01-AUG-08:62 0.63
September 0.593852E+09 0.62 738.42 01-SEP-08:61 0.63
October 0.412979E+09 0.60 738.42 01-OCT-08:61 0.63
November 0.215328E+09 0.56 738.42 01-NOV-08:62 0.63
December 0.187117E+09 0.52 738.42 01-DEC-09:02 0.63
           
Annual Sum or Average 0.522491E+10 0.59      
Minimum of Months 0.144824E+09 0.51 738.42   0.63
Maximum of Months 0.777464E+09 0.63 738.42   0.64



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.118028E+09 0.39 733.35 01-JAN-19:02 0.63
February 0.109848E+09 0.40 733.35 01-FEB-09:02 0.63
March 0.130023E+09 0.39 733.35 01-MAR-16:01 0.63
April 0.383631E+09 0.53 733.35 01-APR-08:51 0.63
May 0.520476E+09 0.55 733.35 01-MAY-08:51 0.64
June 0.773757E+09 0.59 733.35 01-JUN-07:21 0.63
July 0.704441E+09 0.60 733.35 01-JUL-07:42 0.64
August 0.643768E+09 0.58 733.35 01-AUG-08:62 0.63
September 0.508370E+09 0.55 733.35 01-SEP-07:02 0.63
October 0.267504E+09 0.46 733.35 01-OCT-07:42 0.63
November 0.109099E+09 0.37 733.35 01-NOV-08:52 0.63
December 0.149653E+09 0.40 733.35 01-DEC-09:02 0.63
           
Annual Sum or Average 0.441860E+10 0.48      
Minimum of Months 0.109099E+09 0.37 733.35   0.63
Maximum of Months 0.773757E+09 0.60 733.35   0.64



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 64632788.36 0.55 225.31 01-JAN-09:01 0.63
February 43315297.72 0.49 225.31 01-FEB-16:01 0.63
March 58093009.19 0.52 225.31 01-MAR-16:01 0.63
April 0.120514E+09 0.60 225.31 01-APR-15:01 0.64
May 0.141867E+09 0.61 225.31 01-MAY-15:01 0.64
June 0.200135E+09 0.62 225.31 01-JUN-08:61 0.63
July 0.174443E+09 0.62 225.31 01-JUL-08:61 0.64
August 0.173305E+09 0.61 225.31 01-AUG-08:62 0.63
September 0.145984E+09 0.61 225.31 01-SEP-08:61 0.63
October 98802871.19 0.58 225.31 01-OCT-08:61 0.63
November 60141316.51 0.54 225.31 01-NOV-15:01 0.63
December 57817181.29 0.52 225.31 01-DEC-16:01 0.63
           
Annual Sum or Average 0.133905E+10 0.57      
Minimum of Months 43315297.72 0.49 225.31   0.63
Maximum of Months 0.200135E+09 0.62 225.31   0.64



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 39102210.79 0.40 223.49 01-JAN-09:01 0.63
February 38637734.21 0.40 223.49 01-FEB-09:02 0.63
March 37598272.63 0.38 223.49 01-MAR-16:01 0.63
April 0.100404E+09 0.51 223.49 01-APR-15:01 0.64
May 0.133732E+09 0.54 223.49 01-MAY-08:51 0.64
June 0.200686E+09 0.58 223.49 01-JUN-07:21 0.63
July 0.172795E+09 0.60 223.49 01-JUL-08:61 0.64
August 0.161745E+09 0.57 223.49 01-AUG-08:62 0.63
September 0.125629E+09 0.54 223.49 01-SEP-08:61 0.63
October 66026399.58 0.44 223.49 01-OCT-08:61 0.63
November 34972729.52 0.38 223.49 01-NOV-15:01 0.63
December 53990362.70 0.41 223.49 01-DEC-09:02 0.63
           
Annual Sum or Average 0.116532E+10 0.48      
Minimum of Months 34972729.52 0.38 223.49   0.63
Maximum of Months 0.200686E+09 0.60 223.49   0.64



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.593659E+09 0.59 984.89 01-JAN-09:01 0.63
February 0.287359E+09 0.54 984.89 01-FEB-09:02 0.63
March 0.344673E+09 0.55 984.89 01-MAR-16:01 0.63
April 0.593206E+09 0.60 984.89 01-APR-08:62 0.63
May 0.617336E+09 0.60 984.89 01-MAY-08:62 0.64
June 0.830605E+09 0.61 984.89 01-JUN-08:61 0.63
July 0.811048E+09 0.61 984.89 01-JUL-08:61 0.64
August 0.851109E+09 0.61 984.89 01-AUG-08:62 0.63
September 0.840897E+09 0.61 984.89 01-SEP-08:61 0.63
October 0.700898E+09 0.60 984.89 01-OCT-08:61 0.63
November 0.516312E+09 0.58 984.89 01-NOV-08:62 0.63
December 0.466610E+09 0.58 984.89 01-DEC-09:02 0.63
           
Annual Sum or Average 0.745371E+10 0.59      
Minimum of Months 0.287359E+09 0.54 984.89   0.63
Maximum of Months 0.851109E+09 0.61 984.89   0.64



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.258877E+09 0.235320E+09 609.71 01-JAN-00:10 554.22 554.22 47.23 1.11
February 0.299515E+09 0.272259E+09 536.93 03-FEB-07:10 488.07 488.07 44.39 0.85
March 0.198660E+09 0.180582E+09 555.40 25-MAR-23:10 504.86 504.86 45.25 0.91
April 8877895.78 8070007.27 321.83 21-APR-06:10 292.54 292.54 34.02 0.40
May 712214.38 647402.87 204.61 02-MAY-08:44 185.99 185.99 41.84 0.24
June 146489.57 133159.02 131.49 27-JUN-08:06 119.53 119.53 57.61 0.14
July 286830.01 260728.48 133.12 27-JUL-08:16 121.00 121.00 61.19 0.15
August 420907.94 382605.32 176.17 22-AUG-08:06 160.13 160.13 60.30 0.20
September 430811.01 391607.21 157.92 23-SEP-08:55 143.55 143.55 61.16 0.17
October 61436280.60 55845579.07 487.49 25-OCT-08:03 443.12 443.12 38.34 0.72
November 0.179874E+09 0.163505E+09 534.99 04-NOV-06:20 486.31 486.31 44.43 0.85
December 0.408607E+09 0.371424E+09 613.38 06-DEC-09:01 557.56 557.56 45.32 1.12
                 
Annual Sum or Average 0.141784E+10 0.128882E+10            
Minimum of Months 146489.57 133159.02 131.49   119.53 119.53 34.02 0.14
Maximum of Months 0.408607E+09 0.371424E+09 613.38   557.56 557.56 61.19 1.12



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.138706E+09 0.126083E+09 523.51 31-JAN-16:01 475.87 475.87 6.73 10.62
February 40291502.07 36624975.39 420.04 18-FEB-16:01 381.82 381.82 7.46 9.61
March 0.132594E+09 0.120528E+09 1113.82 17-MAR-18:03 1012.46 1012.46 7.11 14.79
April 0.498101E+09 0.452774E+09 1356.25 25-APR-19:10 1232.83 1232.83 6.73 16.09
May 0.626855E+09 0.569811E+09 965.01 29-MAY-20:50 877.19 877.19 6.73 13.91
June 0.121487E+10 0.110432E+10 2511.75 28-JUN-19:10 2283.18 2283.18 6.73 20.79
July 0.135596E+10 0.123257E+10 1763.03 07-JUL-20:20 1602.59 1602.59 6.73 17.96
August 0.131456E+10 0.119493E+10 2024.35 27-AUG-18:02 1840.13 1840.13 6.73 19.03
September 0.125239E+10 0.113843E+10 2015.04 18-SEP-18:05 1831.67 1831.67 6.73 18.99
October 0.523648E+09 0.475996E+09 1454.49 05-OCT-20:20 1322.13 1322.13 6.82 16.57
November 0.168079E+09 0.152784E+09 1229.77 01-NOV-18:03 1117.86 1117.86 7.17 15.43
December 70977514.30 64518560.49 459.12 21-DEC-16:01 417.34 417.34 7.00 10.01
                 
Annual Sum or Average 0.733704E+10 0.666937E+10            
Minimum of Months 40291502.07 36624975.39 420.04   381.82 381.82 6.73 9.61
Maximum of Months 0.135596E+10 0.123257E+10 2511.75   2283.18 2283.18 7.46 20.79



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.103202E+11 0.938110E+10 4184.08 01-JAN-00:20 3803.33 3803.33 8.40 29.62
February 0.796293E+10 0.723831E+10 4184.08 01-FEB-00:05 3803.33 3803.33 8.56 29.62
March 0.101119E+11 0.919170E+10 4184.08 01-MAR-00:05 3803.33 3803.33 8.44 29.62
April 0.108414E+11 0.985481E+10 4184.08 01-APR-00:10 3803.33 3803.33 8.57 29.62
May 0.112066E+11 0.101868E+11 4184.08 01-MAY-00:05 3803.33 3803.33 8.81 29.62
June 0.108451E+11 0.985823E+10 4184.08 01-JUN-00:05 3803.33 3803.33 8.70 29.62
July 0.112066E+11 0.101868E+11 4184.08 01-JUL-00:10 3803.33 3803.33 8.97 29.62
August 0.112066E+11 0.101868E+11 4184.08 01-AUG-00:05 3803.33 3803.33 9.21 29.62
September 0.108451E+11 0.985823E+10 4184.08 01-SEP-00:05 3803.33 3803.33 8.84 29.62
October 0.110874E+11 0.100784E+11 4184.08 01-OCT-00:10 3803.33 3803.33 8.80 29.62
November 0.100675E+11 0.915138E+10 4184.08 01-NOV-00:05 3803.33 3803.33 8.73 29.62
December 0.897703E+10 0.816012E+10 4184.08 01-DEC-00:05 3803.33 3803.33 8.43 29.62
                 
Annual Sum or Average 0.124679E+12 0.113333E+12            
Minimum of Months 0.796293E+10 0.723831E+10 4184.08   3803.33 3803.33 8.40 29.62
Maximum of Months 0.112066E+11 0.101868E+11 4184.08   3803.33 3803.33 9.21 29.62



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:10 14.37 14.37 50.72 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:05 14.37 14.37 51.30 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:05 14.37 14.37 51.55 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 54.18 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:05 14.37 14.37 54.51 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:05 14.37 14.37 55.01 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 55.48 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:05 14.37 14.37 55.42 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:05 14.37 14.37 55.21 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 54.34 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:05 14.37 14.37 54.26 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:05 14.37 14.37 51.81 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 50.72 0.37
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 55.48 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 47.23 80.36 19507.67 153038.25 01-JAN-00:10
February 0.00 0.00 01-FEB-00:05 44.90 79.40 24519.15 129376.60 03-FEB-07:05
March 0.00 0.00 01-MAR-00:05 56.66 79.40 14772.63 141317.24 26-MAR-08:03
April 0.00 0.00 01-APR-00:10 52.96 52.96 729.37 78856.42 21-APR-06:05
May 0.00 0.00 01-MAY-00:05 45.41 45.41 35.15 36987.42 02-MAY-08:44
June 0.00 0.00 01-JUN-00:05 56.21 56.21 5.59 13087.83 27-JUN-08:06
July 0.00 0.00 01-JUL-00:10 57.83 57.83 9.16 12243.17 03-JUL-08:06
August 0.00 0.00 01-AUG-00:05 61.19 61.19 13.18 15781.92 22-AUG-08:06
September 0.00 0.00 01-SEP-00:05 59.41 59.41 13.45 13355.82 23-SEP-08:55
October 0.00 0.00 01-OCT-00:10 60.26 60.26 4737.28 124926.18 25-OCT-08:03
November 0.00 0.00 01-NOV-00:05 43.46 43.46 13806.15 129653.99 23-NOV-19:03
December 0.00 0.00 01-DEC-00:05 34.88 79.53 29218.14 162599.47 06-DEC-09:01
                 
Annual Sum or Average 0.00         8877.43    
Minimum of Months 0.00 0.00   34.88 43.46 5.59 12243.17  
Maximum of Months 0.00 0.00   61.19 80.36 29218.14 162599.47  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 70655.22 409434.49 31-JAN-16:01 10.00 6.70 0.00 0.00 01-JAN-00:10
February 25430.57 288047.93 09-FEB-16:01 9.90 7.58 0.00 0.00 01-FEB-00:05
March 64708.87 388609.42 15-MAR-18:01 9.85 6.72 0.00 0.00 01-MAR-00:05
April 181160.81 472343.03 14-APR-18:03 10.51 6.70 0.00 0.00 01-APR-00:10
May 223635.64 483834.53 31-MAY-18:03 10.60 6.70 0.00 0.00 01-MAY-00:05
June 297162.08 552617.69 01-JUN-18:07 11.15 6.70 0.00 0.00 01-JUN-00:05
July 324951.02 627285.99 13-JUL-18:03 11.86 6.81 0.00 0.00 01-JUL-00:10
August 316764.52 575686.59 09-AUG-18:03 11.55 6.91 0.00 0.00 01-AUG-00:05
September 299143.60 654878.94 10-SEP-21:52 12.42 7.14 0.00 0.00 01-SEP-00:05
October 157578.43 518055.06 01-OCT-18:03 10.87 6.70 0.00 0.00 01-OCT-00:10
November 77905.53 406666.31 01-NOV-15:03 9.98 6.70 0.00 0.00 01-NOV-00:05
December 41723.72 364509.58 21-DEC-16:01 9.94 7.01 0.00 0.00 01-DEC-00:05
                 
Annual Sum or Average 174174.68         0.00    
Minimum of Months 25430.57 288047.93   9.85 6.70 0.00 0.00  
Maximum of Months 324951.02 654878.94   12.42 7.58 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 50.72 59.99 22560.38 47235.72 23-JAN-07:40
February 0.00 0.00 01-FEB-00:05 51.30 59.99 22340.51 47144.79 01-FEB-07:40
March 0.00 0.00 01-MAR-00:05 51.55 59.99 21300.56 45774.42 01-MAR-07:40
April 0.00 0.00 01-APR-00:10 54.18 59.99 19629.82 42466.12 03-APR-07:00
May 0.00 0.00 01-MAY-00:05 54.51 60.00 17834.70 38979.10 01-MAY-06:30
June 0.00 0.00 01-JUN-00:05 55.01 59.98 16382.63 35369.71 01-JUN-06:30
July 0.00 0.00 01-JUL-00:10 55.48 59.97 15649.29 32965.93 03-JUL-06:40
August 0.00 0.00 01-AUG-00:05 55.42 59.98 15884.09 33931.48 31-AUG-06:40
September 0.00 0.00 01-SEP-00:05 55.21 59.97 16966.62 36761.59 29-SEP-06:40
October 0.00 0.00 01-OCT-00:10 54.34 59.97 18628.46 40734.79 31-OCT-07:00
November 0.00 0.00 01-NOV-00:05 54.26 59.99 20424.42 44227.33 30-NOV-07:30
December 0.00 0.00 01-DEC-00:05 51.81 59.97 21862.94 46590.18 29-DEC-07:40
                 
Annual Sum or Average 0.00         19104.03    
Minimum of Months 0.00 0.00   50.72 59.97 15649.29 32965.93  
Maximum of Months 0.00 0.00   55.48 60.00 22560.38 47235.72  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.475404E+11 0.00 0.104113E+12 0.351513E+11 0.00 0.00
February 0.529878E+11 0.00 0.254135E+11 0.302624E+11 0.00 0.00
March 0.356435E+11 0.00 0.113067E+12 0.346638E+11 0.00 0.00
April 0.177013E+10 0.00 0.312352E+12 0.382987E+11 0.00 0.00
May 18787969.24 0.00 0.407289E+12 0.414597E+11 0.00 0.00
June 0.00 0.00 0.517999E+12 0.455737E+11 0.00 0.00
July 0.00 0.00 0.601837E+12 0.461046E+11 0.00 0.00
August 0.00 0.00 0.587308E+12 0.467846E+11 0.00 0.00
September 0.00 0.00 0.539199E+12 0.452927E+11 0.00 0.00
October 0.119699E+11 0.00 0.274308E+12 0.414731E+11 0.00 0.00
November 0.325003E+11 0.00 0.118824E+12 0.362198E+11 0.00 0.00
December 0.646766E+11 0.00 0.554235E+11 0.349692E+11 0.00 0.00
             
Annual Sum or Average 0.247108E+12 0.00 0.365713E+13 0.476254E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.254135E+11 0.302624E+11 0.00 0.00
Maximum of Months 0.646766E+11 0.00 0.601837E+12 0.467846E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 7757.08 0.00 0.673483E+10 0.271000E+10 0.00 0.00
February 4447.77 0.00 0.173087E+10 0.244774E+10 0.00 0.00
March 11148.34 0.00 0.788829E+10 0.271000E+10 0.00 0.00
April 20059.15 0.00 0.209353E+11 0.262258E+10 0.00 0.00
May 20155.90 0.00 0.271398E+11 0.271000E+10 0.00 0.00
June 13501.22 0.00 0.322302E+11 0.262258E+10 0.00 0.00
July 14404.88 0.00 0.381408E+11 0.271000E+10 0.00 0.00
August 10694.92 0.00 0.378353E+11 0.271000E+10 0.00 0.00
September 9250.09 0.00 0.358848E+11 0.262258E+10 0.00 0.00
October 13116.32 0.00 0.181404E+11 0.271000E+10 0.00 0.00
November 12677.87 0.00 0.850451E+10 0.262258E+10 0.00 0.00
December 1143834.25 0.00 0.357415E+10 0.271000E+10 0.00 0.00
             
Annual Sum or Average 1281047.79 0.00 0.238739E+12 0.319080E+11 0.00 0.00
Minimum of Months 4447.77 0.00 0.173087E+10 0.244774E+10 0.00 0.00
Maximum of Months 1143834.25 0.00 0.381408E+11 0.271000E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.351513E+11 0.104113E+12 0.475404E+11 0.153135E+11 0.272373E+09 0.00 0.00 0.00
February 0.302624E+11 0.254135E+11 0.529878E+11 0.154968E+10 0.00 0.00 0.00 0.00
March 0.346638E+11 0.113067E+12 0.356435E+11 0.194415E+11 0.944986E+09 0.00 0.00 0.00
April 0.382987E+11 0.312352E+12 0.177013E+10 0.104693E+11 0.208326E+11 0.00 0.00 0.00
May 0.414597E+11 0.407289E+12 18787969.24 0.136889E+11 0.397826E+11 0.00 0.00 0.00
June 0.455737E+11 0.517999E+12 0.00 0.239555E+11 0.760526E+11 0.00 0.00 0.00
July 0.461046E+11 0.601837E+12 0.00 0.113214E+11 0.104512E+12 0.00 0.00 0.00
August 0.467846E+11 0.587308E+12 0.00 0.130861E+11 0.912816E+11 0.00 0.00 0.00
September 0.452927E+11 0.539199E+12 0.00 0.114277E+11 0.672399E+11 0.00 0.00 0.00
October 0.414731E+11 0.274308E+12 0.119699E+11 0.787444E+10 0.180903E+11 0.00 0.00 0.00
November 0.362198E+11 0.118824E+12 0.325003E+11 0.138718E+11 0.556333E+09 0.00 0.00 0.00
December 0.349692E+11 0.554235E+11 0.646766E+11 0.682606E+11 26471929.19 0.00 0.00 0.00
                 
Annual Sum or Average 0.476254E+12 0.365713E+13 0.247108E+12 0.210261E+12 0.419592E+12 0.00 0.00 0.00
Minimum of Months 0.302624E+11 0.254135E+11 0.00 0.154968E+10 0.00 0.00 0.00 0.00
Maximum of Months 0.467846E+11 0.601837E+12 0.646766E+11 0.682606E+11 0.104512E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.271000E+10 0.673483E+10 7757.08 0.106506E+11 26409250.95 0.00 0.00 0.00
February 0.244774E+10 0.173087E+10 4447.77 0.995077E+10 0.00 0.00 0.00 0.00
March 0.271000E+10 0.788829E+10 11148.34 0.901147E+10 0.125806E+09 0.00 0.00 0.00
April 0.262258E+10 0.209353E+11 20059.15 0.139925E+10 0.257348E+10 0.00 0.00 0.00
May 0.271000E+10 0.271398E+11 20155.90 0.108394E+10 0.488519E+10 0.00 0.00 0.00
June 0.262258E+10 0.322302E+11 13501.22 0.994597E+09 0.108349E+11 0.00 0.00 0.00
July 0.271000E+10 0.381408E+11 14404.88 0.261646E+09 0.226615E+11 0.00 0.00 0.00
August 0.271000E+10 0.378353E+11 10694.92 0.227527E+09 0.202570E+11 0.00 0.00 0.00
September 0.262258E+10 0.358848E+11 9250.09 0.283852E+09 0.150677E+11 0.00 0.00 0.00
October 0.271000E+10 0.181404E+11 13116.32 0.285604E+10 0.339428E+10 0.00 0.00 0.00
November 0.262258E+10 0.850451E+10 12677.87 0.815553E+10 0.118395E+09 0.00 0.00 0.00
December 0.271000E+10 0.357415E+10 1143834.25 0.178494E+11 9109897.35 0.00 0.00 0.00
                 
Annual Sum or Average 0.319080E+11 0.238739E+12 1281047.79 0.627246E+11 0.799537E+11 0.00 0.00 0.00
Minimum of Months 0.244774E+10 0.173087E+10 4447.77 0.227527E+09 0.00 0.00 0.00 0.00
Maximum of Months 0.271000E+10 0.381408E+11 1143834.25 0.178494E+11 0.226615E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.351513E+11 0.475404E+11 0.104113E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.302624E+11 0.529878E+11 0.254135E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.346638E+11 0.356435E+11 0.113067E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.382987E+11 0.177013E+10 0.312352E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.414597E+11 18787969.24 0.407289E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.455737E+11 0.00 0.517999E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.461046E+11 0.00 0.601837E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.467846E+11 0.00 0.587308E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.452927E+11 0.00 0.539199E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.414731E+11 0.119699E+11 0.274308E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.362198E+11 0.325003E+11 0.118824E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.349692E+11 0.646766E+11 0.554235E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.476254E+12 0.247108E+12 0.365713E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.302624E+11 0.00 0.254135E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.467846E+11 0.646766E+11 0.601837E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.271000E+10 7757.08 0.673483E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.244774E+10 4447.77 0.173087E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.271000E+10 11148.34 0.788829E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.262258E+10 20059.15 0.209353E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.271000E+10 20155.90 0.271398E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.262258E+10 13501.22 0.322302E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.271000E+10 14404.88 0.381408E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.271000E+10 10694.92 0.378353E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.262258E+10 9250.09 0.358848E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.271000E+10 13116.32 0.181404E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.262258E+10 12677.87 0.850451E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.271000E+10 1143834.25 0.357415E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.319080E+11 1281047.79 0.238739E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.244774E+10 4447.77 0.173087E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.271000E+10 1143834.25 0.381408E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.118588E+11 0.00 0.00 14974946.74 1159387.49 0.00 0.251426E+11 0.00 0.84
February 0.369299E+11 0.00 0.00 617066.40 0.00 0.00 0.137883E+10 0.00 0.82
March 0.335454E+11 0.00 0.00 0.00 11618973.18 0.00 0.00 0.00 0.83
April 0.161232E+11 0.00 0.00 0.00 0.539809E+09 0.00 0.00 0.00 0.81
May 0.109088E+11 0.00 0.00 0.00 0.117879E+10 0.00 0.00 0.00 0.78
June 0.484418E+10 0.00 0.00 0.00 0.272902E+10 0.00 0.00 0.00 0.67
July 0.101795E+10 0.217315E+10 0.00 9890864.35 0.313459E+10 0.00 0.123575E+10 0.00 0.67
August 1117210.21 0.406820E+10 0.00 28407595.71 0.630867E+09 0.00 0.309865E+10 0.00 0.75
September 0.00 0.481465E+10 0.00 41897097.80 23251208.68 0.00 0.615916E+10 0.00 0.94
October 2530.77 0.691420E+09 0.00 83897689.49 1706158.38 0.00 0.301231E+11 0.00 1.06
November 2058473.45 15239049.12 0.00 85734044.92 0.00 0.00 0.434014E+11 0.00 1.06
December 0.123218E+09 0.00 0.00 73455398.70 0.00 0.00 0.505136E+11 0.00 0.98
                   
Annual Sum or Average 0.115354E+12 0.117627E+11 0.00 0.338875E+09 0.825082E+10 0.00 0.161053E+12 0.00 0.85
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.67
Maximum of Months 0.369299E+11 0.481465E+10 0.00 85734044.92 0.313459E+10 0.00 0.505136E+11 0.00 1.06



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.464700E+10 330754.11 0.00 4609375.32 0.00 15231450.00 0.121956E+10 0.00 2.63
February 0.554046E+10 0.00 0.00 760006.48 0.00 4218185.08 0.494936E+09 0.00 2.36
March 0.496173E+10 1251227.13 0.00 684506.76 694434.92 87395462.32 0.214043E+09 0.00 2.38
April 0.184971E+10 0.109846E+09 0.00 2948224.82 539427.04 0.00 0.686293E+09 0.00 2.45
May 0.115319E+10 0.201910E+09 0.00 2263597.35 5410643.73 0.00 0.563354E+09 0.00 2.32
June 0.163177E+09 0.542856E+09 0.00 3260902.69 1880427.69 0.00 0.615574E+09 0.00 2.19
July 82800854.89 0.910978E+09 0.00 1824544.57 36142107.18 0.00 0.276978E+09 0.00 2.11
August 0.119236E+09 0.833561E+09 0.00 2068244.43 32585636.12 0.00 0.321828E+09 0.00 2.26
September 0.259390E+09 0.673741E+09 0.00 2400462.11 0.108652E+09 0.00 0.445084E+09 0.00 2.45
October 0.256038E+10 0.149582E+09 0.00 4220386.67 1480019.58 0.00 0.958639E+09 0.00 2.65
November 0.416024E+10 286641.35 0.00 3787971.19 2224382.81 0.00 0.110657E+10 0.00 2.60
December 0.542609E+10 0.00 0.00 2714652.62 0.00 0.186673E+09 0.914317E+09 0.00 2.47
                   
Annual Sum or Average 0.309234E+11 0.342434E+10 0.00 31542874.99 0.189609E+09 0.293518E+09 0.781718E+10 0.00 2.41
Minimum of Months 82800854.89 0.00 0.00 684506.76 0.00 0.00 0.214043E+09 0.00 2.11
Maximum of Months 0.554046E+10 0.910978E+09 0.00 4609375.32 0.108652E+09 0.186673E+09 0.121956E+10 0.00 2.65



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.275719E+10 0.00 0.00 1002504.57 126378.64 0.00 0.124760E+10 0.00 1.43
February 0.377305E+10 0.00 0.00 182740.17 0.00 0.00 0.402449E+09 0.00 1.41
March 0.291702E+10 0.00 0.00 676333.52 1266522.28 0.00 0.749012E+09 0.00 1.43
April 0.276911E+09 37116499.01 0.00 3944247.99 21814932.10 0.00 0.159908E+10 0.00 1.50
May 49581164.51 0.100317E+09 0.00 4358371.98 29048119.06 0.00 0.125545E+10 0.00 1.49
June 456560.61 0.303068E+09 0.00 5018434.51 10981273.17 0.00 0.665598E+09 0.00 1.39
July 588324.39 0.597840E+09 0.00 2677600.69 36327534.38 0.00 0.301607E+09 0.00 1.32
August 4840335.29 0.488544E+09 0.00 3082810.96 40298967.91 0.00 0.357194E+09 0.00 1.36
September 8251716.76 0.438759E+09 0.00 3172662.65 44531366.95 0.00 0.541305E+09 0.00 1.43
October 0.103013E+10 67578950.28 0.00 3212319.11 5625679.59 0.00 0.148763E+10 0.00 1.50
November 0.230291E+10 63503.10 0.00 1189354.64 1595842.72 0.00 0.129787E+10 0.00 1.45
December 0.385115E+10 0.00 0.00 335082.55 0.00 0.00 0.617971E+09 0.00 1.41
                   
Annual Sum or Average 0.169721E+11 0.203329E+10 0.00 28852463.34 0.191617E+09 0.00 0.105228E+11 0.00 1.43
Minimum of Months 456560.61 0.00 0.00 182740.17 0.00 0.00 0.301607E+09 0.00 1.32
Maximum of Months 0.385115E+10 0.597840E+09 0.00 5018434.51 44531366.95 0.00 0.159908E+10 0.00 1.50



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.382457E+10 0.00 0.00 0.00 121367.34 0.00 0.00 0.00 0.64
February 0.401009E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.64
March 0.351161E+10 0.00 0.00 0.00 1216300.79 0.00 0.00 0.00 0.64
April 0.159859E+10 193174.29 0.00 259467.21 56315224.20 0.00 89723588.81 0.00 0.63
May 0.781556E+09 29020944.81 0.00 1293909.60 94474019.92 0.00 0.371360E+09 0.00 0.62
June 2598059.78 0.324452E+09 0.00 4611192.83 2929320.52 0.00 0.581000E+09 0.00 0.63
July 10030910.71 0.607424E+09 0.00 2422106.37 26546484.10 0.00 0.260549E+09 0.00 0.61
August 40997586.33 0.462548E+09 0.00 2329002.77 49519822.37 0.00 0.268939E+09 0.00 0.60
September 0.152180E+09 0.330356E+09 0.00 1656867.70 0.123368E+09 0.00 0.326240E+09 0.00 0.61
October 0.219186E+10 46777926.44 0.00 503517.01 22493459.95 0.00 0.135710E+09 0.00 0.65
November 0.342448E+10 0.00 0.00 0.00 1593547.67 0.00 0.00 0.00 0.65
December 0.427548E+10 0.00 0.00 0.00 0.00 12737217.98 0.00 0.00 0.63
                   
Annual Sum or Average 0.238240E+11 0.180077E+10 0.00 13076063.49 0.378577E+09 12737217.98 0.203352E+10 0.00 0.63
Minimum of Months 2598059.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.60
Maximum of Months 0.427548E+10 0.607424E+09 0.00 4611192.83 0.123368E+09 12737217.98 0.581000E+09 0.00 0.65



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.209486E+10 0.00 0.00 0.00 66904.52 13457812.45 0.00 0.00 0.61
February 0.221059E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.61
March 0.193580E+10 0.00 0.00 0.00 670493.55 0.00 0.00 0.00 0.62
April 0.922388E+09 1801.92 0.00 21462.58 31148812.02 0.00 8007772.40 0.00 0.60
May 0.539203E+09 12555571.78 0.00 323469.30 55468879.86 0.00 90544467.09 0.00 0.59
June 19748266.14 0.178279E+09 0.00 2047984.84 2854708.82 0.00 0.281577E+09 0.00 0.57
July 10523510.88 0.317351E+09 0.00 1108851.62 19089433.97 0.00 0.128729E+09 0.00 0.55
August 40051662.92 0.235647E+09 0.00 920444.19 37027050.33 0.00 0.124140E+09 0.00 0.54
September 0.141587E+09 0.154292E+09 0.00 528357.26 87124769.02 0.00 0.115931E+09 0.00 0.56
October 0.124262E+10 23532738.53 0.00 146133.18 13834032.77 0.00 38854130.20 0.00 0.61
November 0.188776E+10 0.00 0.00 0.00 878453.29 0.00 0.00 0.00 0.62
December 0.230951E+10 0.00 0.00 0.00 0.00 54401699.37 0.00 0.00 0.61
                   
Annual Sum or Average 0.133546E+11 0.921660E+09 0.00 5096702.97 0.248164E+09 67859511.82 0.787783E+09 0.00 0.59
Minimum of Months 10523510.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.54
Maximum of Months 0.230951E+10 0.317351E+09 0.00 2047984.84 87124769.02 54401699.37 0.281577E+09 0.00 0.62



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.189273E+09 1794004.69 0.00 0.106723E+09 0.00 0.00 0.672117E+11 0.00 23.66
February 0.197018E+09 0.00 0.00 87431333.49 0.00 0.00 0.693773E+11 0.00 23.29
March 0.176748E+09 17978883.33 0.00 0.108143E+09 0.00 0.00 0.610067E+11 0.00 23.90
April 9659609.62 0.841420E+09 0.00 0.105844E+09 0.00 0.00 0.284957E+11 0.00 23.07
May 0.00 0.187242E+10 0.00 92548839.75 0.00 0.00 0.187063E+11 0.00 22.23
June 0.00 0.451910E+10 0.00 62614659.55 0.00 0.00 0.807421E+10 0.00 18.83
July 0.00 0.934038E+10 0.00 32014244.13 0.00 0.00 0.372816E+10 0.00 18.44
August 0.00 0.787861E+10 0.00 39931664.38 0.00 0.00 0.465971E+10 0.00 19.21
September 0.00 0.725935E+10 0.00 50464587.89 0.00 0.00 0.763636E+10 0.00 20.75
October 76670826.47 0.107225E+10 0.00 0.103949E+09 0.00 0.00 0.404823E+11 0.00 23.50
November 0.160471E+09 23555199.39 0.00 0.103950E+09 0.00 0.00 0.602621E+11 0.00 23.94
December 0.195082E+09 0.00 0.00 0.100203E+09 0.00 0.00 0.754422E+11 0.00 23.17
                   
Annual Sum or Average 0.100492E+10 0.328269E+11 0.00 0.993818E+09 0.00 0.00 0.445083E+12 0.00 21.99
Minimum of Months 0.00 0.00 0.00 32014244.13 0.00 0.00 0.372816E+10 0.00 18.44
Maximum of Months 0.197018E+09 0.934038E+10 0.00 0.108143E+09 0.00 0.00 0.754422E+11 0.00 23.94



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.308455E+10 1235083.93 0.00 40491326.08 0.00 0.00 0.224688E+11 0.00 4.03
February 0.805151E+10 0.00 0.00 15912804.35 0.00 0.00 0.176871E+11 0.00 3.60
March 0.627357E+10 7993427.62 0.00 19930342.14 267366.87 0.00 0.162037E+11 0.00 3.64
April 0.137521E+10 0.414733E+09 0.00 29833934.25 2033187.01 0.00 0.101915E+11 0.00 3.86
May 0.510052E+09 0.794402E+09 0.00 24591549.77 21479789.44 0.00 0.754141E+10 0.00 3.72
June 34268749.02 0.193435E+10 0.00 24213673.23 36796376.13 0.00 0.391912E+10 0.00 3.38
July 9666264.46 0.374856E+10 0.00 14229935.04 0.115438E+09 0.00 0.179016E+10 0.00 3.30
August 27313868.55 0.330306E+10 0.00 17090179.36 67687984.99 0.00 0.220908E+10 0.00 3.50
September 84635140.70 0.308948E+10 0.00 19494074.31 66587322.35 0.00 0.344058E+10 0.00 3.83
October 0.181136E+10 0.559066E+09 0.00 36517485.93 3674005.41 0.00 0.140567E+11 0.00 4.11
November 0.237954E+10 1100032.44 0.00 35446095.81 9399951.57 0.00 0.205323E+11 0.00 3.99
December 0.539865E+10 0.00 0.00 26902740.44 0.00 0.00 0.226136E+11 0.00 3.79
                   
Annual Sum or Average 0.290403E+11 0.138540E+11 0.00 0.304654E+09 0.323364E+09 0.00 0.142654E+12 0.00 3.73
Minimum of Months 9666264.46 0.00 0.00 14229935.04 0.00 0.00 0.179016E+10 0.00 3.30
Maximum of Months 0.805151E+10 0.374856E+10 0.00 40491326.08 0.115438E+09 0.00 0.226136E+11 0.00 4.11



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.170357E+11 2539033.84 0.00 74825185.48 0.00 0.00 0.662752E+11 0.00 1.76
February 0.396367E+11 0.00 0.00 29441046.13 0.00 0.00 0.448940E+11 0.00 1.70
March 0.263855E+11 6696071.00 0.00 49419264.07 18749232.18 0.00 0.485059E+11 0.00 1.74
April 0.294616E+10 0.108735E+10 0.00 96972606.79 96430230.67 0.00 0.371084E+11 0.00 1.85
May 0.563705E+09 0.236348E+10 0.00 98070687.36 0.229513E+09 0.00 0.279644E+11 0.00 1.85
June 21470400.54 0.594967E+10 0.00 99883239.03 0.270777E+09 0.00 0.141680E+11 0.00 1.67
July 2757033.68 0.123585E+11 0.00 56907590.59 0.548547E+09 0.00 0.647917E+10 0.00 1.63
August 13346072.48 0.101905E+11 0.00 66611487.91 0.522488E+09 0.00 0.782469E+10 0.00 1.68
September 85805747.14 0.970091E+10 0.00 72397767.94 0.362105E+09 0.00 0.122819E+11 0.00 1.81
October 0.763440E+10 0.150964E+10 0.00 0.103120E+09 20999992.31 0.00 0.459876E+11 0.00 1.88
November 0.131191E+11 2174683.08 0.00 74086742.98 31165319.08 0.00 0.619941E+11 0.00 1.79
December 0.339122E+11 0.00 0.00 43333746.35 0.00 0.00 0.570911E+11 0.00 1.70
                   
Annual Sum or Average 0.141357E+12 0.431715E+11 0.00 0.865069E+09 0.210078E+10 0.00 0.430574E+12 0.00 1.76
Minimum of Months 2757033.68 0.00 0.00 29441046.13 0.00 0.00 0.647917E+10 0.00 1.63
Maximum of Months 0.396367E+11 0.123585E+11 0.00 0.103120E+09 0.548547E+09 0.00 0.662752E+11 0.00 1.88



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 5070070.01 358710.98 14459.55 9250179.58 0.00 0.301460E+09 0.769108E+09 1719.46 0.35
February 43568509.11 41223.64 0.00 3843727.97 0.00 0.549462E+09 0.498378E+09 0.00 0.36
March 30414801.98 298251.43 0.00 7924409.54 0.00 0.354433E+09 0.648378E+09 0.00 0.36
April 0.00 14033970.06 0.00 12558226.01 0.00 863675.98 0.538674E+09 259.56 0.35
May 0.00 28708054.71 4524.02 11372326.86 0.00 251749.60 0.344107E+09 2704.23 0.35
June 0.00 90486150.31 0.00 9078746.81 0.00 16156.59 0.104155E+09 52.08 0.36
July 0.00 0.481276E+09 190858.13 2303242.46 0.00 7204.31 39270754.44 12764.65 0.36
August 0.00 0.436386E+09 178425.20 1914516.04 0.00 41292.67 26182883.84 22746.44 0.36
September 0.00 0.351201E+09 150857.47 3426891.51 0.00 60700.97 51042017.81 18134.03 0.36
October 4254173.26 60948645.33 21332.52 10104440.72 0.00 69347976.05 0.592921E+09 5337.52 0.36
November 7040006.47 4114261.59 1265.26 8521818.10 310079.10 0.221722E+09 0.719860E+09 2798.44 0.35
December 26574236.91 0.00 0.00 4954528.25 401365.07 0.628734E+09 0.519079E+09 0.00 0.35
                   
Annual Sum or Average 0.116922E+09 0.146785E+10 561722.14 85253053.85 711444.17 0.212640E+10 0.485116E+10 66516.42 0.36
Minimum of Months 0.00 0.00 0.00 1914516.04 0.00 7204.31 26182883.84 0.00 0.35
Maximum of Months 43568509.11 0.481276E+09 190858.13 12558226.01 401365.07 0.628734E+09 0.769108E+09 22746.44 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.159204E+09 82471.43 12786.84 2758290.84 276197.51 0.559168E+09 0.363630E+09 3390.27 0.35
February 0.142479E+09 41218.81 0.00 1351094.75 0.00 0.767222E+09 0.184072E+09 0.00 0.36
March 0.199333E+09 298216.49 0.00 3695878.51 0.00 0.423826E+09 0.414173E+09 0.00 0.36
April 95196532.91 13957903.98 2487.52 9542432.35 69485.03 641044.51 0.446652E+09 2708.78 0.35
May 73305972.33 28698181.44 4267.57 8877120.00 3157.95 45676.09 0.273461E+09 6311.59 0.35
June 27982158.02 90466309.08 0.00 7245590.41 9291.54 10769.41 77998586.17 0.00 0.36
July 9194637.63 0.474604E+09 132435.21 1844607.24 6678788.99 0.00 30537084.51 8037.43 0.36
August 7804957.79 0.421010E+09 189542.45 1309304.17 15314095.50 0.00 19021133.73 22102.40 0.36
September 17264862.19 0.318556E+09 259854.97 2543167.54 32495693.57 3032.50 34712159.13 17420.90 0.36
October 0.152068E+09 57682812.35 30513.62 5505795.31 3241016.78 0.119731E+09 0.399243E+09 13828.47 0.36
November 0.182175E+09 2579469.61 4742.03 3109013.40 1839816.28 0.406150E+09 0.365597E+09 3857.61 0.36
December 0.136620E+09 0.00 0.00 1317196.72 401318.04 0.889154E+09 0.152111E+09 0.00 0.35
                   
Annual Sum or Average 0.120263E+10 0.140798E+10 636630.19 49099491.23 60328861.17 0.316595E+10 0.276121E+10 77657.47 0.36
Minimum of Months 7804957.79 0.00 0.00 1309304.17 0.00 0.00 19021133.73 0.00 0.35
Maximum of Months 0.199333E+09 0.474604E+09 259854.97 9542432.35 32495693.57 0.889154E+09 0.446652E+09 22102.40 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 7735.34 0.00 7002149.49 0.00 0.00 0.671541E+09 0.00 0.02
February 0.259380E+09 0.00 0.00 2284608.18 0.00 0.00 0.833219E+09 0.00 0.02
March 0.150530E+09 0.00 0.00 2615466.77 0.00 0.00 0.578083E+09 0.00 0.02
April 0.00 33023610.05 0.00 2680322.75 0.00 0.00 97270353.60 0.00 0.02
May 0.00 57085898.46 0.00 1047163.40 0.00 0.00 15798481.57 0.00 0.02
June 0.00 0.209012E+09 0.00 42869.40 0.00 0.00 135079.31 0.00 0.02
July 0.00 0.312068E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.02
August 0.00 0.334504E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.02
September 0.00 0.281709E+09 0.00 750633.68 0.00 0.00 5909090.99 0.00 0.02
October 0.00 52022977.83 0.00 4494751.26 0.00 0.00 0.336408E+09 0.00 0.02
November 8132998.50 981973.44 0.00 5295291.49 0.00 0.00 0.674230E+09 0.00 0.02
December 44560601.64 0.00 0.00 5141808.41 0.00 0.00 0.818015E+09 0.00 0.02
                   
Annual Sum or Average 0.462604E+09 0.128042E+10 0.00 31355064.84 0.00 0.00 0.403061E+10 0.00 0.02
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
Maximum of Months 0.259380E+09 0.334504E+09 0.00 7002149.49 0.00 0.00 0.833219E+09 0.00 0.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.216010E+10 1118675.52 219208.48 40916131.41 3746453.58 0.885194E+09 0.116279E+11 224.31 0.40
February 0.193264E+10 559108.40 0.00 33005753.09 0.00 0.599930E+09 0.122891E+11 0.00 0.40
March 0.273423E+10 4016969.99 22935.59 59711185.78 0.00 0.559715E+09 0.107673E+11 5222.21 0.40
April 0.133348E+10 0.179637E+09 1505170.59 85565624.27 8941690.81 6649924.74 0.606228E+10 259797.80 0.40
May 0.100002E+10 0.388801E+09 474639.05 76919425.35 42835.74 819471.41 0.374696E+10 141817.93 0.40
June 0.379561E+09 0.122698E+10 127848.08 60908063.70 126034.12 78088.69 0.109545E+10 14425.22 0.40
July 0.124720E+09 0.643783E+10 1771503.44 14688903.52 90593765.99 1199.34 0.424548E+09 19767.66 0.40
August 0.105870E+09 0.571107E+10 2460288.06 9828207.18 0.207727E+09 0.00 0.265942E+09 93694.17 0.40
September 0.234187E+09 0.432049E+10 1518572.46 22386440.55 0.443529E+09 0.00 0.483001E+09 29480.21 0.40
October 0.207678E+10 0.768261E+09 810859.05 63016015.91 57787427.66 43566942.53 0.699361E+10 137004.71 0.40
November 0.249142E+10 34750651.96 86057.41 43071753.48 25212646.60 0.554087E+09 0.989298E+10 12254.98 0.40
December 0.185317E+10 0.00 0.00 22384819.31 5443638.48 0.428542E+10 0.983421E+10 0.00 0.40
                   
Annual Sum or Average 0.164262E+11 0.190735E+11 8997082.22 0.532402E+09 0.843150E+09 0.693546E+10 0.734833E+11 713689.20 0.40
Minimum of Months 0.105870E+09 0.00 0.00 9828207.18 0.00 0.00 0.265942E+09 0.00 0.40
Maximum of Months 0.273423E+10 0.643783E+10 2460288.06 85565624.27 0.443529E+09 0.428542E+10 0.122891E+11 259797.80 0.40



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 4800030.96 358710.98 12509.04 9207640.07 0.00 0.321407E+09 0.749473E+09 3669.97 0.35
February 31472089.04 41223.64 0.00 4560419.33 0.00 0.502664E+09 0.556556E+09 0.00 0.36
March 23238773.78 298251.43 0.00 8442240.20 0.00 0.323362E+09 0.686107E+09 0.00 0.36
April 0.00 14034229.62 0.00 13752457.67 0.00 153576.98 0.538190E+09 0.00 0.35
May 0.00 28715282.96 0.00 12761067.25 0.00 13652.61 0.342957E+09 0.00 0.35
June 0.00 90486202.40 0.00 9625627.24 0.00 0.00 0.103625E+09 0.00 0.36
July 0.00 0.481480E+09 0.00 2361516.09 0.00 0.00 39219685.13 0.00 0.36
August 0.00 0.436587E+09 0.00 1873039.06 0.00 40316.90 26225336.60 0.00 0.36
September 0.00 0.351323E+09 45517.14 3521882.91 0.00 0.00 51007727.39 820.30 0.36
October 675509.48 60975315.36 0.00 10738227.69 0.00 73856719.01 0.591357E+09 0.00 0.36
November 7302457.26 4110007.28 6254.48 8542470.96 310079.10 0.255477E+09 0.685822E+09 2063.53 0.35
December 24715528.49 0.00 0.00 5414086.87 401365.07 0.618969E+09 0.530242E+09 0.00 0.35
                   
Annual Sum or Average 92204389.00 0.146841E+10 64280.65 90800675.33 711444.17 0.209594E+10 0.490078E+10 6553.80 0.36
Minimum of Months 0.00 0.00 0.00 1873039.06 0.00 0.00 26225336.60 0.00 0.35
Maximum of Months 31472089.04 0.481480E+09 45517.14 13752457.67 401365.07 0.618969E+09 0.749473E+09 3669.97 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.159544E+09 82471.43 13301.85 3095267.43 276197.51 0.550768E+09 0.371354E+09 2875.26 0.35
February 0.142829E+09 41218.81 0.00 1801841.77 0.00 0.652332E+09 0.298161E+09 0.00 0.36
March 0.195639E+09 296979.21 0.00 4612943.04 0.00 0.376121E+09 0.464655E+09 1237.28 0.36
April 92631289.88 14001029.99 3643.11 10060766.29 26436.59 428645.89 0.448911E+09 1475.62 0.35
May 71512921.72 28708760.59 0.00 9102746.14 3157.95 5438.76 0.275069E+09 0.00 0.35
June 27361563.98 90466309.08 0.00 7283503.28 9291.54 0.00 78592036.74 0.00 0.36
July 9136614.85 0.474828E+09 0.00 1814726.54 6595277.27 0.00 30624987.99 0.00 0.36
August 7788109.76 0.421378E+09 18930.71 1217985.89 15139010.13 0.00 19129300.04 43.08 0.36
September 17193383.81 0.319313E+09 128740.46 2506913.48 31882704.46 2506.96 34820417.10 4065.15 0.36
October 0.149830E+09 57857749.43 2875.15 5993416.67 3104458.58 0.114635E+09 0.406091E+09 3088.06 0.36
November 0.182172E+09 2579469.61 4473.14 3166251.58 1839816.28 0.407000E+09 0.364693E+09 4126.50 0.36
December 0.136620E+09 0.00 0.00 1299442.04 401318.04 0.835905E+09 0.205379E+09 0.00 0.35
                   
Annual Sum or Average 0.119226E+10 0.140955E+10 171964.42 51955804.15 59277668.36 0.293720E+10 0.299748E+10 16910.95 0.36
Minimum of Months 7788109.76 0.00 0.00 1217985.89 0.00 0.00 19129300.04 0.00 0.35
Maximum of Months 0.195639E+09 0.474828E+09 128740.46 10060766.29 31882704.46 0.835905E+09 0.464655E+09 4126.50 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.218090E+11 0.00 0.00 0.00 692079.28 0.00 0.00 0.00 0.50
February 0.228670E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.50
March 0.200244E+11 0.00 0.00 0.00 6935774.88 0.00 0.00 0.00 0.50
April 0.936729E+10 15589598.28 0.00 621792.55 0.306641E+09 0.00 0.256955E+09 0.00 0.49
May 0.487092E+10 0.177688E+09 0.00 4340943.21 0.525987E+09 0.00 0.164428E+10 0.00 0.48
June 0.253585E+09 0.170406E+10 0.00 17081124.30 0.101420E+09 0.00 0.285089E+10 0.00 0.46
July 0.134132E+09 0.290343E+10 0.00 8979421.07 0.415347E+09 0.00 0.128909E+10 0.00 0.43
August 0.385024E+09 0.223251E+10 0.00 9390724.09 0.555480E+09 0.00 0.133339E+10 0.00 0.44
September 0.911836E+09 0.165225E+10 0.00 7451369.38 0.868597E+09 0.00 0.177539E+10 0.00 0.47
October 0.124468E+11 0.276186E+09 0.00 2509748.36 0.122025E+09 0.00 0.828587E+09 0.00 0.51
November 0.195276E+11 0.00 0.00 0.00 9086969.27 0.00 0.00 0.00 0.51
December 0.244529E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.50
                   
Annual Sum or Average 0.137050E+12 0.896171E+10 0.00 50375122.97 0.291221E+10 0.00 0.997858E+10 0.00 0.48
Minimum of Months 0.134132E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.43
Maximum of Months 0.244529E+11 0.290343E+10 0.00 17081124.30 0.868597E+09 0.00 0.285089E+10 0.00 0.51



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 1398344.26 89677.74 3682.11 2106183.01 0.00 0.127029E+09 0.140689E+09 362.64 0.35
February 10526715.20 10305.91 0.00 896622.85 0.00 0.173843E+09 88546610.76 0.00 0.36
March 7565075.21 74562.86 0.00 1890875.86 0.00 0.120728E+09 0.130104E+09 0.00 0.36
April 0.00 3508492.52 0.00 2929626.33 0.00 3228202.57 0.131866E+09 64.89 0.35
May 0.00 7177013.68 200.19 2632847.76 0.00 65385.59 86234623.44 1606.88 0.35
June 0.00 22621537.58 0.00 2167407.62 0.00 5939.56 26139246.05 13.02 0.36
July 0.00 0.120326E+09 40343.36 543873.93 0.00 2583.42 9848842.96 3549.60 0.36
August 0.00 0.109096E+09 44924.48 452114.78 0.00 10901.65 6571656.71 6090.62 0.36
September 0.00 87809280.42 27477.81 792114.30 0.00 19324.50 12820963.77 5699.70 0.36
October 1575045.11 15237161.33 4854.21 2257112.81 0.00 40313725.59 0.125011E+09 1813.30 0.36
November 2685508.88 1029151.44 67.90 1893517.50 77519.77 96880527.40 0.137826E+09 361.98 0.35
December 7083635.02 0.00 0.00 1121667.01 100341.27 0.192501E+09 94129430.62 0.00 0.35
                   
Annual Sum or Average 30834323.67 0.366979E+09 121550.07 19683963.77 177861.04 0.754627E+09 0.989788E+09 19562.61 0.36
Minimum of Months 0.00 0.00 0.00 452114.78 0.00 2583.42 6571656.71 0.00 0.35
Maximum of Months 10526715.20 0.120326E+09 44924.48 2929626.33 100341.27 0.192501E+09 0.140689E+09 6090.62 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 39804205.60 20617.86 3207.32 582302.71 69049.38 0.184241E+09 46562257.75 836.96 0.35
February 35688957.55 0.00 10291.78 299105.73 0.00 0.210093E+09 27699435.07 12.92 0.36
March 49743353.44 74554.12 0.00 835489.34 0.00 0.134215E+09 75463057.93 0.00 0.36
April 23525280.15 3488741.56 0.00 2240225.63 17371.26 2243818.42 0.109999E+09 2033.51 0.35
May 18326493.08 7174555.89 1289.84 2100473.45 789.49 15511.97 68479958.50 1344.42 0.35
June 6995539.50 22616577.27 0.00 1763540.27 2322.88 4923.07 19545273.16 0.00 0.36
July 2298659.41 0.118655E+09 27865.05 445354.17 1669697.25 383.38 7649685.39 3308.07 0.36
August 1951239.45 0.105260E+09 40238.52 314639.79 3828523.87 0.00 4767969.69 5768.03 0.36
September 4316215.55 79639227.85 60007.52 593498.09 8123923.39 5097.77 8715993.93 9007.14 0.36
October 38087140.42 14399863.13 7177.00 1178346.38 830678.12 53939128.61 75932485.16 4324.55 0.36
November 45555269.83 645523.28 952.12 631359.67 459954.07 0.133810E+09 59261378.03 541.91 0.36
December 34248730.61 0.00 0.00 272564.45 100329.51 0.242026E+09 18253095.55 0.00 0.35
                   
Annual Sum or Average 0.300541E+09 0.351974E+09 151029.16 11256899.69 15102639.22 0.960595E+09 0.522329E+09 27177.52 0.36
Minimum of Months 1951239.45 0.00 0.00 272564.45 0.00 0.00 4767969.69 0.00 0.35
Maximum of Months 49743353.44 0.118655E+09 60007.52 2240225.63 8123923.39 0.242026E+09 0.109999E+09 9007.14 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 602119.17 0.00 23019973.18 0.00 96900320.57 0.162254E+10 0.00 0.40
February 22950992.62 66210.21 0.00 11018064.23 0.00 0.386649E+09 0.133849E+10 0.00 0.41
March 14873218.61 479028.29 0.00 14308326.53 0.00 0.326875E+09 0.131616E+10 0.00 0.40
April 0.00 22540272.77 0.00 16471873.03 0.00 6161490.04 0.864101E+09 416.89 0.40
May 0.00 46119078.45 0.00 13977348.64 0.00 413490.66 0.556957E+09 1178.89 0.40
June 0.00 0.145324E+09 4383.94 10912222.85 0.00 62694.83 0.170919E+09 3307.68 0.40
July 0.00 0.772501E+09 780348.05 2734857.15 0.00 14556.67 64035082.19 34177.13 0.40
August 0.00 0.700487E+09 685025.85 2401159.84 0.00 66183.62 42726839.14 41221.92 0.40
September 0.00 0.563976E+09 353736.10 4861343.32 0.00 46003.94 82673877.79 13146.66 0.40
October 0.00 97878172.70 50124.52 17728426.77 0.00 42034068.65 0.102698E+10 5518.70 0.40
November 1944964.46 6610320.08 1318.84 19542555.39 498024.97 0.118803E+09 0.139700E+10 2895.31 0.40
December 3833059.37 0.00 0.00 16833909.22 644641.40 0.425298E+09 0.144820E+10 0.00 0.40
                   
Annual Sum or Average 43602235.06 0.235658E+10 1874937.30 0.153810E+09 1142666.37 0.140332E+10 0.993079E+10 101863.18 0.40
Minimum of Months 0.00 0.00 0.00 2401159.84 0.00 14556.67 42726839.14 0.00 0.40
Maximum of Months 22950992.62 0.772501E+09 780348.05 23019973.18 644641.40 0.425298E+09 0.162254E+10 41221.92 0.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.756370E+09 1196841.53 0.00 67127738.31 0.00 0.00 0.433104E+11 0.00 4.64
February 0.995122E+09 0.00 0.00 53443774.59 0.00 0.00 0.437577E+11 0.00 4.53
March 0.554711E+09 12285474.66 0.00 71654753.19 0.00 0.00 0.406916E+11 0.00 4.79
April 26964835.89 0.626036E+09 0.00 79876402.22 93881.62 0.00 0.226192E+11 0.00 5.20
May 0.00 0.143244E+10 0.00 76179363.45 0.00 0.00 0.163142E+11 0.00 5.27
June 0.00 0.351439E+10 0.00 59607391.82 0.00 0.00 0.783554E+10 0.00 4.72
July 0.00 0.705153E+10 0.00 32879508.42 0.00 0.00 0.356062E+10 0.00 4.58
August 0.00 0.576611E+10 0.00 39134804.74 0.00 0.00 0.428351E+10 0.00 4.67
September 0.00 0.536564E+10 0.00 43871537.18 0.00 0.00 0.673831E+10 0.00 4.96
October 0.252633E+09 0.775133E+09 0.00 74802056.79 0.00 0.00 0.287079E+11 0.00 5.05
November 0.458616E+09 15741389.90 0.00 66680779.75 4352.83 0.00 0.393867E+11 0.00 4.76
December 0.175381E+10 0.00 0.00 55939556.18 0.00 0.00 0.453833E+11 0.00 4.42
                   
Annual Sum or Average 0.479823E+10 0.245605E+11 0.00 0.721198E+09 98234.44 0.00 0.302589E+12 0.00 4.80
Minimum of Months 0.00 0.00 0.00 32879508.42 0.00 0.00 0.356062E+10 0.00 4.42
Maximum of Months 0.175381E+10 0.705153E+10 0.00 79876402.22 93881.62 0.00 0.453833E+11 0.00 5.27



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.250847E+09 1260515.11 0.00 81162284.72 0.00 0.00 0.476592E+11 0.00 5.03
February 0.237066E+09 0.00 0.00 66471465.52 0.00 0.00 0.486528E+11 0.00 4.94
March 0.144352E+09 13481084.40 0.00 85655453.31 0.00 0.00 0.447672E+11 0.00 5.21
April 4021906.74 0.680100E+09 0.00 88813966.78 0.00 0.00 0.241442E+11 0.00 5.57
May 0.00 0.154443E+10 0.00 81908910.48 0.00 0.00 0.172285E+11 0.00 5.61
June 0.00 0.375659E+10 0.00 62829538.60 0.00 0.00 0.820170E+10 0.00 5.00
July 0.00 0.750765E+10 0.00 34603743.33 0.00 0.00 0.373057E+10 0.00 4.84
August 0.00 0.615838E+10 0.00 41283870.30 0.00 0.00 0.449369E+10 0.00 4.95
September 0.00 0.572373E+10 0.00 46936940.53 0.00 0.00 0.708973E+10 0.00 5.27
October 82408591.03 0.829607E+09 0.00 84554781.01 0.00 0.00 0.310505E+11 0.00 5.42
November 0.159450E+09 16564273.28 0.00 80030368.62 0.00 0.00 0.431321E+11 0.00 5.16
December 0.774425E+09 0.00 0.00 70882248.99 0.00 0.00 0.506959E+11 0.00 4.81
                   
Annual Sum or Average 0.165257E+10 0.262318E+11 0.00 0.825134E+09 0.00 0.00 0.330846E+12 0.00 5.15
Minimum of Months 0.00 0.00 0.00 34603743.33 0.00 0.00 0.373057E+10 0.00 4.81
Maximum of Months 0.774425E+09 0.750765E+10 0.00 88813966.78 0.00 0.00 0.506959E+11 0.00 5.61



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 2278679.47 0.00 0.123184E+09 0.00 0.00 0.556009E+11 0.00 21.70
February 0.00 0.00 0.00 99816941.82 0.00 0.00 0.602926E+11 0.00 21.28
March 0.00 22964560.52 0.00 0.121820E+09 0.00 0.00 0.510676E+11 0.00 21.83
April 0.00 0.110695E+10 0.00 0.112008E+09 0.00 0.00 0.230227E+11 0.00 21.63
May 0.00 0.241736E+10 0.00 95503598.72 0.00 0.00 0.148922E+11 0.00 21.07
June 0.00 0.559752E+10 0.00 63853508.69 0.00 0.00 0.649591E+10 0.00 18.45
July 0.00 0.101517E+11 0.00 33082736.21 0.00 0.00 0.298003E+10 0.00 18.17
August 0.00 0.888620E+10 0.00 40399321.52 0.00 0.00 0.370274E+10 0.00 18.73
September 0.00 0.772082E+10 0.00 51536984.84 0.00 0.00 0.616893E+10 0.00 19.93
October 0.00 0.125260E+10 0.00 0.112929E+09 0.00 0.00 0.335249E+11 0.00 21.83
November 0.00 27229812.42 0.00 0.118351E+09 0.00 0.00 0.504646E+11 0.00 21.92
December 0.00 0.00 0.00 0.114145E+09 0.00 0.00 0.636115E+11 0.00 21.10
                   
Annual Sum or Average 0.00 0.371857E+11 0.00 0.108663E+10 0.00 0.00 0.371825E+12 0.00 20.63
Minimum of Months 0.00 0.00 0.00 33082736.21 0.00 0.00 0.298003E+10 0.00 18.17
Maximum of Months 0.00 0.101517E+11 0.00 0.123184E+09 0.00 0.00 0.636115E+11 0.00 21.92



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.124832E+11 0.00 0.00 0.00 397483.89 42411276.65 0.00 0.00 1.09
February 0.131332E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.08
March 0.114947E+11 0.00 0.00 4260.75 3983443.59 0.00 5939111.43 0.00 1.09
April 0.488730E+10 0.178199E+09 0.00 2500854.20 23270757.36 0.00 0.641130E+09 0.00 1.08
May 0.254455E+10 0.450330E+09 0.00 4807031.23 14981808.91 0.00 0.120180E+10 0.00 1.08
June 0.293534E+09 0.132635E+10 0.00 8283409.56 482327.57 0.00 0.143215E+10 0.00 1.07
July 0.166398E+09 0.217506E+10 0.00 4839084.41 44840368.64 0.00 0.630396E+09 0.00 1.03
August 0.249447E+09 0.184201E+10 0.00 4807876.78 59484791.75 0.00 0.715090E+09 0.00 1.05
September 0.623578E+09 0.137574E+10 0.00 4517517.39 0.227880E+09 0.00 0.908841E+09 0.00 1.07
October 0.707817E+10 0.244264E+09 0.00 1788438.38 14560936.38 0.00 0.536989E+09 0.00 1.11
November 0.112094E+11 74662.90 0.00 20212.29 5144282.37 0.00 5908393.12 0.00 1.10
December 0.138012E+11 0.00 0.00 0.00 0.00 0.242913E+09 0.00 0.00 1.08
                   
Annual Sum or Average 0.779648E+11 0.759203E+10 0.00 31568685.00 0.395026E+09 0.285324E+09 0.607824E+10 0.00 1.08
Minimum of Months 0.166398E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.03
Maximum of Months 0.138012E+11 0.217506E+10 0.00 8283409.56 0.227880E+09 0.242913E+09 0.143215E+10 0.00 1.11



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 09:03:03

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.147919E+12 0.146810E+11 0.907387E+11 0.424536E+12 0.281739E+12
February 0.185161E+12 0.147859E+11 0.103141E+12 0.421095E+12 0.115926E+12
March 0.246604E+12 0.137196E+11 0.865155E+11 0.393376E+12 0.256359E+12
April 0.294133E+12 0.529601E+10 0.289627E+11 0.172222E+12 0.628966E+12
May 0.299716E+12 0.249615E+10 0.915974E+10 0.914536E+11 0.801121E+12
June 0.313723E+12 -0.145121E+10 -0.229294E+11 -0.236074E+11 0.103486E+13
July 0.298037E+12 -0.608980E+10 -0.441497E+11 -0.147450E+12 0.114967E+13
August 0.249687E+12 -0.497054E+10 -0.360300E+11 -0.117672E+12 0.112084E+13
September 0.210394E+12 -0.313512E+10 -0.205953E+11 -0.664536E+11 0.101689E+13
October 0.189950E+12 0.741678E+10 0.460637E+11 0.240424E+12 0.569375E+12
November 0.160978E+12 0.130113E+11 0.833607E+11 0.389825E+12 0.292210E+12
December 0.116746E+12 0.182925E+11 0.116604E+12 0.528634E+12 0.189438E+12
           
Annual Sum or Average 0.271305E+13 0.740524E+11 0.440842E+12 0.230638E+13 0.745740E+13
Minimum of Months 0.116746E+12 -0.608980E+10 -0.441497E+11 -0.147450E+12 0.115926E+12
Maximum of Months 0.313723E+12 0.182925E+11 0.116604E+12 0.528634E+12 0.114967E+13