Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:01
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 09:01:52
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 11160.59 | 983.72 | 983.72 |
Net Site Energy | 11160.59 | 983.72 | 983.72 |
Total Source Energy | 22000.15 | 1939.14 | 1939.14 |
Net Source Energy | 22000.15 | 1939.14 | 1939.14 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1355.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 677.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 602.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 174.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 641.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 521.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 99.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 173.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.75 | 3262.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 43.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4753.76 | 6406.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1355.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 677.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 602.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 174.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 952.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 22.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 521.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 99.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 173.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.75 | 3262.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 20.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1355.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 677.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 602.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 174.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 641.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 521.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 99.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 173.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.75 | 3262.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 43.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 122.47 | 407.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 228.04 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 419.01 | 564.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 122.47 | 407.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 228.04 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 419.01 | 564.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 4753.756 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 4753.756 | 100.00 |
Total On-Site and Utility Electric Sources | 4753.756 | 100.00 |
Total Electricity End Uses | 4753.756 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 150.75 | 3.66 |
Air to Air Heat Recovery for Heating | 3964.11 | 96.34 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 4114.86 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1.17 |
Time Setpoint Not Met During Occupied Cooling | 80.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7786.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:01 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 6.6442 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 9.6995 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 9.6995 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 4.0903 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.7049 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 9.2569 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 9.0417 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 4.4132 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.4132 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.7327 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 4.4132 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8432 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8432 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.6442 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 4.0903 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.7049 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 9.2569 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 9.0417 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 4.4132 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.4132 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.7327 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 4.4132 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.8432 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.8432 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.6992 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 20-JUL-19:49 | 06-FEB-19:10 | - | - | - | - | - | - | - | - | - | - | 05-JUN-20:10 |
Heating | 0.00 | 273364.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 148752.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 50471.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 87982.85 | 87619.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31577.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28453.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6296.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3931.88 | 269273.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1683.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 380185.47 | 630256.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 273364.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 148752.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 50471.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58308.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1273.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 28453.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 6296.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3931.88 | 269273.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 771.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 670.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1469.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2147.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1909.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 551.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5473.02 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2031.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1650.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 315.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 550.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.41 | 3536.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 138.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 15055.14 | 6945.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 129.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 189.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 145.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 27.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 48.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 311.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1327.00 | 612.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 129.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 189.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 145.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 27.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 48.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 311.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1327.00 | 612.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.17 | 0.694558 | 0.547000 | 1.19 | 1.00 | 0.500000 | 0.000549 | 0.000066 | 1.19 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.369072 | 0.138478 | 0.547000 | 0.201882 | 0.547000 | 0.500000 | 0.002751 | 0.000035 | 0.201882 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.219109 | 0.270110 | 0.547000 | 0.119853 | 0.720294 | 0.500000 | 0.001411 | 0.000014 | 0.119853 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.177647 | 0.704507 | 0.547000 | 0.097173 | 1.00 | 0.500000 | 0.000541 | 0.000020 | 0.097173 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.095536 | 0.755808 | 0.547000 | 0.052258 | 1.00 | 0.500000 | 0.000504 | 0.000013 | 0.052380 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.33 | 0.070864 | 0.547000 | 1.82 | 0.547000 | 0.500000 | 0.021335 | 0.000102 | 1.82 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.57 | 0.091785 | 0.547000 | 0.857659 | 0.547000 | 0.500000 | 0.004151 | 0.000105 | 0.857659 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.80 | 0.207864 | 0.547000 | 2.62 | 0.554304 | 0.500000 | 0.001833 | 0.000273 | 2.62 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.25 | 0.948530 | 0.547000 | 0.684467 | 1.00 | 0.500000 | 0.000402 | 0.000126 | 0.684467 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.16 | 0.117159 | 0.547000 | 1.18 | 0.547000 | 0.500000 | 0.003252 | 0.000114 | 1.18 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.27 | 0.111568 | 0.547000 | 1.24 | 0.547000 | 0.500000 | 0.003415 | 0.000118 | 1.24 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.23 | 0.063620 | 0.547000 | 1.22 | 0.547000 | 0.500000 | 0.010771 | 0.000083 | 1.22 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.698795 | 0.449401 | 0.547000 | 0.382241 | 1.00 | 0.500000 | 0.000848 | 0.000081 | 0.382241 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 7594.79 | 0.000066 | 160.39 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4028.87 | 0.000035 | 99.05 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1601.27 | 0.000014 | 36.43 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2307.89 | 0.000020 | 59.54 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1460.85 | 0.000013 | 39.87 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11712.72 | 0.000102 | 247.45 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 11990.87 | 0.000105 | 274.72 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 31215.50 | 0.000273 | 698.77 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 6832.37 | 0.000060 | 195.21 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 6831.96 | 0.000060 | 195.20 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 39336.35 | 0.000344 | 1123.89 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 39347.65 | 0.000344 | 1124.21 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 6806.90 | 0.000060 | 194.48 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 6806.49 | 0.000060 | 194.47 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 14445.40 | 0.000126 | 360.25 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 2123.08 | 0.000019 | 60.66 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 2122.93 | 0.000019 | 60.65 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 10193.69 | 0.000089 | 291.24 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 13052.77 | 0.000114 | 289.53 |
DINING_FLR_6 VAV BOX REHEAT COIL | 13517.09 | 0.000118 | 299.33 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 9504.01 | 0.000083 | 203.66 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 9297.83 | 0.000081 | 241.69 |
VAV WITH REHEAT HEATING COIL | 247703.09 | 0.002167 | 3894.46 |
FLR_3_DOAS HEATING COIL | 23955.95 | 0.000210 | 376.64 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.10 | 0.000060 | 0.000428 |
ROOM_2_FLR_3 FAN COIL | 1.06 | 0.000060 | 0.000414 |
ROOM_3_MULT19_FLR_3 FAN COIL | 6.38 | 0.000344 | 0.002445 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.38 | 0.000344 | 0.002217 |
ROOM_5_FLR_3 FAN COIL | 0.994227 | 0.000060 | 0.000389 |
ROOM_6_FLR_3 FAN COIL | 0.961998 | 0.000060 | 0.000377 |
ROOM_1_FLR_6 FAN COIL | 0.287050 | 0.000019 | 0.000112 |
ROOM_2_FLR_6 FAN COIL | 0.276354 | 0.000019 | 0.000108 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.33 | 0.000089 | 0.000528 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.10 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.06 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.38 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.38 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 0.994227 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.961998 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.287050 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.276354 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.33 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008593 | 12.80 | 0.008500 | 0.000428 | 1.10 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008596 | 12.80 | 0.008500 | 0.000414 | 1.06 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008522 | 12.80 | 0.008500 | 0.002445 | 6.38 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008793 | 12.80 | 0.008500 | 0.002217 | 5.38 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008602 | 12.80 | 0.008500 | 0.000389 | 0.994227 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008606 | 12.80 | 0.008500 | 0.000377 | 0.961998 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008589 | 12.80 | 0.008500 | 0.000112 | 0.287050 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008592 | 12.80 | 0.008500 | 0.000108 | 0.276354 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008650 | 12.80 | 0.008500 | 0.000528 | 1.33 | |
VAV WITH REHEAT COOLING COIL | 27.46 | 6.70 | 0.011724 | 10.94 | 0.008500 | 0.022311 | 21.21 | 624648.76 |
FLR_3_DOAS COOLING COIL | 30.30 | 6.70 | 0.013367 | 11.91 | 0.008500 | 0.002684 | 2.05 | 75158.60 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.66 | 11.66 | 21.32 | 11.66 | 21.21 | 21.21 | 0.300000 | 0.549920 | 21.21 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 21.21 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 21.21 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.022311 | 0.000021 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.002167 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002684 | 0.000177 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000210 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.032013 | 6531.45 | |
HEATSYS1 PUMP | 0.004582 | 1366.34 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.004582 | 0.549882 |
COOLSYS1 | 0.032013 | 3.84 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 523790.33 | 523790.33 | 0.004582 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.032013 | 4521.94 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.032013 | 896288.62 | 896882.99 | 102.24 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 6.644 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.024 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 4.090 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.780 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.705 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.235 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 9.257 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.637 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 9.042 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.112 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.733 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2943.236 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 13147.704 | 6.644 | 123.454 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13147.704 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 650.557 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 650.557 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 753.347 | 9.699 | 60.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 753.347 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 387.592 | 4.090 | 189.996 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 387.592 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 445.205 | 5.705 | 53.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 445.205 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1748.285 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1748.285 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 11828.200 | 9.042 | 28.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11828.200 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 108.229 | 4.413 | 72.152 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.229 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1718.521 | 4.413 | 82.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1718.521 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1212.035 | 11.733 | 54.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1212.035 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1818.789 | 4.413 | 82.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1818.789 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.8226 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.107 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.174 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.031 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.097 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.048 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7359 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6841 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8028 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7445 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.17638513E-14 | 0.32473881E-16 | -0.15472737E-09 | 0.39084990E-16 |
29 | 8 | 0.22578286E-07 | 0.11136169E-12 | 0.38514655E-03 | -0.25672286E-09 |
30 | 7 | -0.12460867E-01 | 0.57383191E-08 | -0.23401545E-01 | 0.14168460E-03 |
31 | 6 | 0.41130930 | 0.19934685E-05 | 0.47716306 | -0.48180040E-02 |
32 | 5 | -5.2487139 | 0.74343025E-04 | -4.4802041 | 0.63904887E-01 |
33 | 4 | 33.260058 | 0.60748543E-03 | 21.592533 | -0.42553784 |
34 | 3 | -111.77343 | 0.13226915E-02 | -55.924898 | 1.5231004 |
35 | 2 | 197.67353 | 0.74337769E-03 | 78.150831 | -2.9093300 |
36 | 1 | -171.36487 | 0.79295509E-04 | -55.335031 | 2.7490988 |
37 | 0 | 57.057407 | 0.45097929E-06 | 15.545453 | |
38 | 9 | -0.19728226E-15 | 0.38070760E-16 | -0.14134637E-09 | 0.10329039E-17 |
39 | 8 | 0.20696804E-07 | 0.14765672E-12 | 0.36530744E-03 | -0.23532978E-09 |
40 | 7 | -0.11868633E-01 | 0.77667999E-08 | -0.22548754E-01 | 0.13495068E-03 |
41 | 6 | 0.39521686 | 0.27204939E-05 | 0.46345169 | -0.46283129E-02 |
42 | 5 | -5.0916664 | 0.10217830E-03 | -4.3748670 | 0.61957574E-01 |
43 | 4 | 32.565369 | 0.84029717E-03 | 21.180735 | -0.41631434 |
44 | 3 | -110.29532 | 0.18400486E-02 | -55.110745 | 1.5017457 |
45 | 2 | 196.20849 | 0.10394005E-02 | 77.404245 | -2.8860650 |
46 | 1 | -170.82368 | 0.11139293E-03 | -55.118150 | 2.7396138 |
47 | 0 | 57.057407 | 0.63685742E-06 | 15.581450 | |
48 | 9 | 0.13059652E-14 | 0.41030072E-16 | -0.13816519E-09 | -0.47111965E-17 |
49 | 8 | 0.20247126E-07 | 0.15597406E-12 | 0.36047671E-03 | -0.23021680E-09 |
50 | 7 | -0.11724123E-01 | 0.82470298E-08 | -0.22340566E-01 | 0.13330755E-03 |
51 | 6 | 0.39128975 | 0.28947446E-05 | 0.46009809 | -0.45820219E-02 |
52 | 5 | -5.0533361 | 0.10891817E-03 | -4.3490697 | 0.61482301E-01 |
53 | 4 | 32.395785 | 0.89717001E-03 | 21.079809 | -0.41406279 |
54 | 3 | -109.93440 | 0.19673976E-02 | -54.911173 | 1.4965315 |
55 | 2 | 195.85064 | 0.11127485E-02 | 77.221372 | -2.8803827 |
56 | 1 | -170.69145 | 0.11939355E-03 | -55.065279 | 2.7372963 |
57 | 0 | 57.057407 | 0.68346468E-06 | 15.590432 | |
58 | 9 | -0.20590843E-15 | 0.37601014E-16 | -0.14495918E-09 | 0.53749011E-17 |
59 | 8 | 0.21205398E-07 | 0.13808064E-12 | 0.37072834E-03 | -0.24111267E-09 |
60 | 7 | -0.12030653E-01 | 0.72214098E-08 | -0.22782120E-01 | 0.13679291E-03 |
61 | 6 | 0.39961963 | 0.25236359E-05 | 0.46720788 | -0.46802108E-02 |
62 | 5 | -5.1346368 | 0.94596970E-04 | -4.4037454 | 0.62490383E-01 |
63 | 4 | 32.755467 | 0.77656360E-03 | 21.293679 | -0.41883826 |
64 | 3 | -110.69986 | 0.16977958E-02 | -55.334066 | 1.5075900 |
65 | 2 | 196.60952 | 0.95769584E-03 | 77.608945 | -2.8924333 |
66 | 1 | -170.97185 | 0.10250317E-03 | -55.177451 | 2.7422106 |
67 | 0 | 57.057407 | 0.58520576E-06 | 15.571474 | |
68 | 9 | -0.13316196E-15 | 0.35962645E-16 | -0.14184186E-09 | 0.33595795E-17 |
69 | 8 | 0.20766565E-07 | 0.14634888E-12 | 0.36605364E-03 | -0.23612300E-09 |
70 | 7 | -0.11890945E-01 | 0.76921302E-08 | -0.22580893E-01 | 0.13520437E-03 |
71 | 6 | 0.39582317 | 0.26934781E-05 | 0.46396918 | -0.46354598E-02 |
72 | 5 | -5.0975841 | 0.10113583E-03 | -4.3788466 | 0.62030949E-01 |
73 | 4 | 32.591550 | 0.83151862E-03 | 21.196301 | -0.41666193 |
74 | 3 | -110.35104 | 0.18204263E-02 | -55.141525 | 1.5025506 |
75 | 2 | 196.26372 | 0.10281160E-02 | 77.432455 | -2.8869422 |
76 | 1 | -170.84409 | 0.11016374E-03 | -55.126315 | 2.7399715 |
77 | 0 | 57.057407 | 0.62970739E-06 | 15.580070 | |
78 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
79 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
80 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
81 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
82 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
83 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
84 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
85 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
86 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
87 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
88 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
89 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
90 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
91 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
92 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
93 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3672_SHGC_0.38 | 37 | 1 | VerySmooth | 2.086 | 2.086 | 1.000 | 0.381 | ||
2 | RESWINDOW_U_0.3672_SHGC_0.38 | 38 | 1 | VerySmooth | 2.086 | 2.086 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.58639E-002 | 0.29373 | 0.49994 | 0.49994 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11691 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.58639E-002 | 0.29373 | 0.49994 | 0.49994 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11691 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.263 | 2.9576E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 9.802E-003 | 1.461E-004 | 7.212E-005 | 0.133 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 3.784E-003 | 4.872E-005 | 1.327E-004 | 4.426E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 8.942E-003 | 5.445E-005 | 1.424E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 5.159E-003 | 5.445E-005 | 1.182E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 1.221E-002 | 1.565E-004 | 1.392E-004 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 2.167E-002 | 1.147E-004 | 6.318E-005 | 0.104 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 6.191E-002 | 4.733E-005 | 9.051E-005 | 4.300E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.587E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.588E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 6.879E-003 | 1.766E-005 | 1.424E-004 | 2.086E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 2.910E-003 | 1.186E-004 | 6.472E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1.243E-002 | 1.204E-004 | 6.523E-005 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1.217E-002 | 2.953E-005 | 2.446E-005 | 3.488E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1427 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 7.2937E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1615 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.2766E-002 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.9379E-002 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.8978E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 3.9974E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.3280E-002 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1616 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 8.7631E-002 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1834 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 9.9103E-002 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1099 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.8713E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 4.4888E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.8161E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.4362E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.9817E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.6432E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.4965E-002 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.5386E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0156E-002 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.9348E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3953E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.4362E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.9817E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.6432E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.4965E-002 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.5386E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0156E-002 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.9348E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3953E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 29129.10248 | 29129.10248 | 2.17098 | 2.17098 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 25.99100 | 1.33593E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1482.62898 | 1482.62898 | 6.51870E-002 | 0.85446 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4951.51841 | 4951.51841 | 0.36907 | 0.36907 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.06750 | 1.33665E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2990.07836 | 2990.07836 | 0.13146 | 0.13146 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -16.30000 | 9.24091E-004 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 2939.56122 | 2939.56122 | 0.21911 | 0.21911 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 29.83500 | 1.33661E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 984.56318 | 984.56318 | 4.32881E-002 | 9.17347E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2383.82265 | 2383.82265 | 0.17765 | 0.17765 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 26.90550 | 1.33609E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1807.93070 | 1807.93070 | 7.94887E-002 | 7.94887E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1281.97139 | 1281.97139 | 9.55356E-002 | 9.55356E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 30.20700 | 1.33668E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1191.34517 | 1191.34517 | 5.23795E-002 | 5.77652E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44679.98409 | 44679.98409 | 3.32996 | 3.32996 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.30000 | 1.33670E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2341.89743 | 2341.89743 | 0.10296 | 0.10296 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 21018.26513 | 21018.26513 | 1.56793 | 1.56793 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.06750 | 1.33665E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 7577.60633 | 7577.60633 | 0.33316 | 0.67639 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 64320.12353 | 64320.12353 | 4.79563 | 4.79563 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 17717.28853 | 17717.28853 | 0.77897 | 1.89399 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 10909.22864 | 10909.22864 | 1.09560 | 1.09560 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.99800 | 1.33646E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 6832.39334 | 6832.39334 | 0.30216 | 0.30216 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -16.30000 | 9.24091E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10532.04894 | 10532.04894 | 1.05772 | 1.05772 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 6831.98394 | 6831.98394 | 0.30214 | 0.30214 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -16.30000 | 9.24091E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 63546.42006 | 63546.42006 | 6.38157 | 6.38157 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 39336.42461 | 39336.42461 | 1.73965 | 1.73965 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -16.30000 | 9.24091E-004 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 53596.94225 | 53596.94225 | 5.38284 | 5.38284 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 30.20700 | 1.33668E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 39347.72726 | 39347.72726 | 1.74015 | 1.74015 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -16.30000 | 9.24091E-004 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 9899.77840 | 9899.77840 | 0.99423 | 0.99423 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 26.50250 | 1.33602E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 6806.92481 | 6806.92481 | 0.30103 | 0.30103 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -16.30000 | 9.24091E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9578.86823 | 9578.86823 | 0.96200 | 0.96200 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.97550 | 1.33593E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 6806.51636 | 6806.51636 | 0.30101 | 0.30101 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -16.30000 | 9.24091E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 16789.84779 | 16789.84779 | 1.25131 | 1.25131 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 30.30000 | 1.33670E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 10922.98406 | 10922.98406 | 0.48025 | 0.48025 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2858.23661 | 2858.23661 | 0.28705 | 0.28705 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.99800 | 1.33646E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2123.08579 | 2123.08579 | 9.38921E-002 | 9.38921E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -16.30000 | 9.24091E-004 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2751.73497 | 2751.73497 | 0.27635 | 0.27635 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2122.94032 | 2122.94032 | 9.38857E-002 | 9.38857E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -16.30000 | 9.24091E-004 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 13241.45734 | 13241.45734 | 1.32986 | 1.32986 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 10193.72253 | 10193.72253 | 0.45081 | 0.45081 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -16.30000 | 9.24091E-004 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 28907.36348 | 28907.36348 | 2.15710 | 2.15710 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.30000 | 1.33670E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 6980.41860 | 6980.41860 | 0.30691 | 1.18780 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -16.30000 | 9.24091E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30356.47739 | 30356.47739 | 2.26520 | 2.26520 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.30000 | 1.33670E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 7140.46529 | 7140.46529 | 0.31394 | 1.18780 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -16.30000 | 9.24091E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 29782.36714 | 29782.36714 | 2.22545 | 2.22545 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 29.46300 | 1.33655E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 3246.87265 | 3246.87265 | 0.14274 | 0.36735 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -16.30000 | 9.24091E-004 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 9376.38843 | 9376.38843 | 0.69879 | 0.69879 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 30.30000 | 1.33670E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 7330.61713 | 7330.61713 | 0.32230 | 0.32230 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -16.30000 | 9.24091E-004 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 366733.06 | 21.21050 | 21.21050 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 289379.20 | 7.43375 | 7.43375 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 42344.89 | 16.55289 | 2.05125 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 79850.37 | 5.32474 | 2.05125 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.17098 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.69456 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.18752 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.48550E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.64425E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.18752 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7594.78850 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.64425E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 160.39412 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.36907 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13848 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20188 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54700 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.75133E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.52463E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20188 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4028.86925 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.52463E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 99.04769 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.21911 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27011 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11985 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72029 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.41053E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.40086E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11985 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1601.27227 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.40086E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 36.43075 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.17765 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.70451 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 9.71727E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.40804E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.01904E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.71727E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2307.89123 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.01904E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 59.54049 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.55356E-002 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.75581 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.22580E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.04096E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.27802E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.23795E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1460.85492 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.27802E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 39.86964 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.32996 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.08639E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.82149 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54700 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.13351E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.02468E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.82149 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11712.71615 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.02468E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 247.44862 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.56793 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.17851E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.85766 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54700 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.15100E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.04901E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.85766 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11990.87090 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.04901E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 274.71909 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.79563 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20786 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.62321 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55430 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.83293E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.73087E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.62321 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 31215.50371 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.73087E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 698.76907 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.09560 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.09560 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.97725E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.28001E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69767 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.59274E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.28001E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.09560 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6832.36814 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.97725E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 195.20981 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.05772 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.05772 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.97690E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.13565E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69766 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.59594E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.13565E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.05772 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6831.95874 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.97690E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 195.19811 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.38157 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.38157 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.44132E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.44480E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69818 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.52167E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.44480E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.38157 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 39336.35077 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.44132E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1123.88703 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.38284 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.38284 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.44230E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.21732E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69723 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.79254E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.21732E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.38284 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 39347.65341 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.44230E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1124.20996 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.99423 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.99423 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.95497E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.89413E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69765 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60233E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.89413E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.99423 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6806.89968 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.95497E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 194.48220 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.96200 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.96200 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.95462E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.77154E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69764 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60588E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.77154E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.96200 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6806.49123 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.95462E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 194.47053 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.25131 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.94853 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.68447 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.01674E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.26375E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.68447 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14445.39606 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.26375E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 360.25095 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.28705 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.28705 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.85736E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.12009E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69768 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58856E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.12009E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.28705 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2123.07850 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.85736E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 60.65815 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.27635 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.27635 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.85723E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.07933E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69767 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.59187E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.07933E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.27635 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2122.93303 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.85723E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 60.65400 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.32986 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.32986 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.91789E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.27661E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69741 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.65034E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.27661E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.32986 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 10193.69421 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.91789E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 291.24194 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.15710 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11716 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.17993 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54700 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.25200E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.14191E-004 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.17993 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13052.76974 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.14191E-004 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 289.52987 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.26520 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11157 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.23906 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54700 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.41496E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.18253E-004 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.23906 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13517.09149 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.18253E-004 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 299.33139 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.22545 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.36204E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.21732 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54700 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07713E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.31452E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.21732 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9504.01269 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.31452E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 203.66021 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69879 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.44940 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.38224 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.47796E-004 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.13415E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.38224 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9297.82837 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.13415E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 241.69355 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.66407 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.66407 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.32371 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.66407 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.21050 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 21.21050 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.54992 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 21.21050 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.21050 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.45899 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.94085 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.17240E-002 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 624648.75977 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.23110E-002 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 21.21050 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 247703.08895 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.16701E-003 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 3894.46081 |
350 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 21.21050 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.23110E-002 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.13433E-005 |
353 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.16701E-003 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
356 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 30.30000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.91477 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.33670E-002 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 75158.60084 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.68449E-003 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 23955.95238 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.09577E-004 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 376.64253 |
368 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.68449E-003 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.77386E-004 |
371 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.09577E-004 |
372 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 3.20134E-002 |
373 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 6531.45095 |
374 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.58235E-003 |
375 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.54988 |
376 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.58235E-003 |
377 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1366.33810 |
378 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
379 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 523790.33432 |
380 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 523790.33000 |
381 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.58235E-003 |
382 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 3.20134E-002 |
383 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.84160 |
384 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 3.20134E-002 |
385 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 4521.94378 |
386 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 3.20134E-002 |
387 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 896288.61537 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 896882.99000 |
389 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 102.24466 |
390 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
391 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
392 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
393 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
394 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 7633.64 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4046.20 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1608.81 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2317.23 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1466.43 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11772.61 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 12046.91 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 31364.72 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 7358.53 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 7358.09 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 42365.66 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 42377.83 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 7331.10 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 7330.66 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 14506.68 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2286.56 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2286.40 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 10978.61 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 13115.74 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 13582.41 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 9552.00 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 9335.13 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 165687.26 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 16024.01 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 18219.40 | 14594.39 | 3625.01 | 0.80 | 2126.90 | 21.57 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 17599.50 | 14094.57 | 3504.92 | 0.80 | 2054.32 | 20.84 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 104777.19 | 84366.61 | 20410.58 | 0.81 | 12261.61 | 124.36 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 92626.00 | 73183.31 | 19442.69 | 0.79 | 10748.09 | 109.01 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 16561.66 | 13257.35 | 3304.31 | 0.80 | 1932.76 | 19.60 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 16034.88 | 12832.40 | 3202.48 | 0.80 | 1871.07 | 18.98 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4769.97 | 3822.07 | 947.91 | 0.80 | 556.92 | 5.65 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4594.94 | 3680.94 | 914.00 | 0.80 | 536.42 | 5.44 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 22339.55 | 17821.79 | 4517.76 | 0.80 | 2603.02 | 26.40 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 605148.30 | 399232.69 | 205915.61 | 0.66 | 73142.77 | 741.85 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 61333.89 | 39815.52 | 21518.37 | 0.65 | 7074.24 | 71.75 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 4.12 | 14.07 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.107 | 0.950 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.107 | 0.950 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.107 | 0.950 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.107 | 0.950 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.38 | N/A | 2.086 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.6286689296E-002 | 2.1557744506E-002 | Pass | Pass | 3.7480115484E-003 | 8.9527033155E-003 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.7414956417E-003 | 1.3715050677E-003 | Pass | Pass | 0.1777727449 | 0.5112826642 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.5523487191E-002 | 2.3190717461E-002 | Pass | Pass | 1.5653022713E-002 | 4.7890173531E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.3472384907E-004 | 2.9508467203E-004 | Pass | Pass | 7.1680364817E-002 | 0.1219018627 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.7676818548E-004 | 2.7357253006E-004 | Pass | Pass | 0.1968576361 | 0.5822302335 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.4732999420E-002 | 0.2201834254 | Pass | Pass | 1.9028976756E-002 | 4.9917656928E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.8557906716E-003 | 3.2406685389E-002 | Pass | Pass | 3.4726640436E-002 | 0.1021915849 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.5019575021E-002 | 4.5670261074E-002 | Pass | Pass | 1.3532687945E-002 | 3.6225764425E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.9820750848E-002 | 0.3149458216 | Pass | Pass | 7.3948526235E-002 | 0.2078175360 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.0506120004E-002 | 0.3178911318 | Pass | Pass | 7.0071644777E-002 | 0.2039217822 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.9983223349E-002 | 3.0864593578E-002 | Pass | Pass | 5.2008435135E-002 | 0.1991142769 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.3477628550E-002 | 7.4630485280E-002 | Pass | Pass | 0.3856951112 | 1.6882433148 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.8835847486E-002 | 0.3106566136 | Pass | Pass | 7.5061715108E-002 | 0.2053679761 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.9484994612E-002 | 0.3137433606 | Pass | Pass | 7.5627567839E-002 | 0.2092210359 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.7590771792E-004 | 3.0612950318E-004 | Pass | Pass | 0.2970965579 | 1.6659287296 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2647282117E-002 | 0.3481642778 | Pass | Pass | 0.1455650309 | 0.7241379056 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2626460458E-002 | 0.3492281124 | Pass | Pass | 0.1893739434 | 0.8479327500 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.9510925810E-002 | 0.2786856569 | Pass | Pass | 7.8434605876E-002 | 0.2110125041 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.5467010098E-002 | 8.5137824317E-002 | Pass | Pass | 9.7335524853E-003 | 2.5109702457E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.5254155231E-002 | 6.8531162399E-002 | Pass | Pass | 1.0239765166E-002 | 3.0978434735E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.3518339718E-002 | 0.1001825662 | Pass | Pass | 2.1262382926E-002 | 3.9144279832E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.6401937437E-004 | 6.4079160937E-004 | Pass | Pass | 0.6275002885 | 3.8160305413 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4394.80 | 38.94 | 1831.18 | 8035.77 | 3535.13 | 17835.82 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.086 | 0.381 | 0.381 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.086 | 0.381 | 0.381 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.086 | 0.381 | 0.381 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.086 | 0.381 | 0.381 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.086 | 0.381 | 0.381 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.086 | 0.381 | 0.381 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.086 | 0.381 | 0.381 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.086 | 0.381 | 0.381 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.086 | 0.381 | 0.381 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.086 | 0.381 | 0.381 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.086 | 0.381 | 0.381 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.086 | 0.381 | 0.381 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.086 | 0.381 | 0.381 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.086 | 0.381 | 0.381 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.086 | 0.381 | 0.381 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.086 | 0.381 | 0.381 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.086 | 0.381 | 0.381 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.086 | 0.381 | 0.381 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.086 | 0.381 | 0.381 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.086 | 0.381 | 0.381 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.086 | 0.381 | 0.381 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.38 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.086 | 0.381 | 0.381 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.086 | 0.381 | 0.381 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.086 | 0.381 | 0.381 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.086 | 0.381 | 0.381 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.086 | 0.381 | 0.381 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.086 | 0.381 | 0.381 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.086 | 0.381 | 0.381 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.086 | 0.381 | 0.381 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.38 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.086 | 0.381 | 0.381 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.086 | 0.381 | 0.381 | |||||||||||||||||
North Total or Average | 432.95 | 2.086 | 0.381 | 0.381 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.086 | 0.381 | 0.381 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.6442 | 1978.83 | 13147.70 | LightsWired | LTG_SCH_BASEMENT | 45.99 | 168.00 | 45.94 | 0.0000 | Y | 113.37 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 9.6995 | 67.07 | 650.56 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 6.26 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 9.6995 | 77.67 | 753.35 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.25 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 4.0903 | 94.76 | 387.59 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 1.87 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.7049 | 78.04 | 445.21 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.90 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 9.2569 | 188.86 | 1748.29 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 38.99 | 0.0000 | Y | 12.79 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 9.0417 | 1308.19 | 11828.20 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 55.30 | 0.0000 | Y | 122.77 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.4132 | 1863.81 | 8225.38 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 73.68 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.4132 | 1864.32 | 8227.62 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 73.70 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 4.4132 | 1557.62 | 6874.08 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 56.74 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.21 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.54 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.19 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.54 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.4132 | 220.77 | 974.32 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 8.73 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 48.87 | 0.0000 | Y | 28.16 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 48.87 | 0.0000 | Y | 28.16 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.7327 | 103.30 | 1212.04 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.34 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 4.4132 | 412.12 | 1818.79 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 15.01 |
Interior Lighting Total | 5.8432 | 11345.29 | 66293.22 | 388.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 11096.45 | AstronomicalClock | - | 83.67 | 83.67 | 174.28 | |
Exterior Lighting Total | 11096.45 | 174.28 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 523790.33 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 896882.99 | 3.11 | 897040.64 | 3.11 | 4.12 | 14.07 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11983.12 | 18219.40 | 14594.39 | 3625.01 | 0.80 | - | 2126.90 | 21.57 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11578.93 | 17599.50 | 14094.57 | 3504.92 | 0.80 | - | 2054.32 | 20.84 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 68449.10 | 104777.19 | 84366.61 | 20410.58 | 0.81 | - | 12261.61 | 124.36 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 62080.21 | 92626.00 | 73183.31 | 19442.69 | 0.79 | - | 10748.09 | 109.01 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10902.74 | 16561.66 | 13257.35 | 3304.31 | 0.80 | - | 1932.76 | 19.60 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10559.51 | 16034.88 | 12832.40 | 3202.48 | 0.80 | - | 1871.07 | 18.98 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3136.03 | 4769.97 | 3822.07 | 947.91 | 0.80 | - | 556.92 | 5.65 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3021.90 | 4594.94 | 3680.94 | 914.00 | 0.80 | - | 536.42 | 5.44 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 14773.39 | 22339.55 | 17821.79 | 4517.76 | 0.80 | - | 2603.02 | 26.40 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 624648.76 | 605148.30 | 399232.69 | 205915.61 | 0.66 | - | 73142.77 | 741.85 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 75158.60 | 61333.89 | 39815.52 | 21518.37 | 0.65 | - | 7074.24 | 71.75 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 7594.79 | 7633.64 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4028.87 | 4046.20 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1601.27 | 1608.81 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2307.89 | 2317.23 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1460.85 | 1466.43 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11712.72 | 11772.61 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11990.87 | 12046.91 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 31215.50 | 31364.72 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6832.37 | 7358.53 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6831.96 | 7358.09 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 39336.35 | 42365.66 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 39347.65 | 42377.83 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6806.90 | 7331.10 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6806.49 | 7330.66 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 14445.40 | 14506.68 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2123.08 | 2286.56 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2122.93 | 2286.40 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 10193.69 | 10978.61 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 13052.77 | 13115.74 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 13517.09 | 13582.41 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 9504.01 | 9552.00 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 9297.83 | 9335.13 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 247703.09 | 165687.26 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 23955.95 | 16024.01 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.10 | 770.91 | 703.64 | 1.00 | 1.17 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.06 | 744.25 | 703.64 | 1.00 | 1.18 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.38 | 4490.30 | 703.64 | 1.00 | 0.96 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.38 | 3787.56 | 703.64 | 1.00 | 0.97 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.99 | 699.57 | 703.64 | 1.00 | 1.20 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.96 | 676.90 | 703.64 | 1.00 | 1.21 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.29 | 201.98 | 703.64 | 1.00 | 1.74 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.28 | 194.45 | 703.64 | 1.00 | 1.77 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.33 | 935.74 | 703.64 | 1.00 | 1.13 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 21.21 | 47525.05 | 2240.64 | 1.00 | 1.11 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.032013 | 6531.45 | 204022.71 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.004582 | 1366.34 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.032013 | 4521.94 | 141251.80 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 29129.10 | 29129.10 | 14.72 | 2.171 | 2.171 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 24.00 | 24.00 | 0.00933 | 25.99 | 0.01336 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4951.52 | 4951.52 | 73.82 | 0.369 | 0.369 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00902 | 30.07 | 0.01337 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 2939.56 | 2939.56 | 37.85 | 0.219 | 0.219 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00948 | 29.84 | 0.01337 | 0.092 | 0.00 |
MECH_FLR_1 | 2383.82 | 2383.82 | 14.51 | 0.178 | 0.178 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 24.00 | 24.00 | 0.00881 | 26.91 | 0.01336 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1281.97 | 1281.97 | 13.53 | 0.096 | 0.096 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00892 | 30.21 | 0.01337 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44679.98 | 44679.98 | 572.53 | 3.330 | 3.330 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00855 | 30.30 | 0.01337 | 0.000 | 0.00 |
CAFE_FLR_1 | 21018.27 | 21018.27 | 111.29 | 1.568 | 1.568 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.01004 | 30.07 | 0.01337 | 0.676 | 0.00 |
LOBBY_FLR_1 | 64320.12 | 64320.12 | 49.17 | 4.796 | 4.796 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 23.99 | 0.01000 | 30.14 | 0.01337 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 10909.23 | 10909.23 | 279.57 | 1.096 | 1.096 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00859 | 29.00 | 0.01336 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10532.05 | 10532.05 | 269.93 | 1.058 | 1.058 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00860 | 28.84 | 0.01336 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 63546.42 | 63546.42 | 2591.21 | 6.382 | 6.382 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00852 | 30.14 | 0.01337 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 53596.94 | 53596.94 | 2184.91 | 5.383 | 5.383 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 21.11 | 21.11 | 0.00879 | 30.21 | 0.01337 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9899.78 | 9899.78 | 253.70 | 0.994 | 0.994 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 21.11 | 21.11 | 0.00860 | 26.50 | 0.01336 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9578.87 | 9578.87 | 245.50 | 0.962 | 0.962 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 21.11 | 21.11 | 0.00861 | 25.98 | 0.01336 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 16789.85 | 16789.85 | 43.12 | 1.251 | 1.251 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00966 | 30.30 | 0.01337 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2858.24 | 2858.24 | 73.25 | 0.287 | 0.287 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00859 | 29.00 | 0.01336 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2751.73 | 2751.73 | 70.53 | 0.276 | 0.276 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00859 | 28.84 | 0.01336 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13241.46 | 13241.46 | 539.79 | 1.330 | 1.330 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00865 | 30.14 | 0.01337 | 0.099 | 0.00 |
BANQUET_FLR_6 | 28907.36 | 28907.36 | 87.16 | 2.157 | 2.157 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 23.98 | 0.01046 | 30.30 | 0.01337 | 1.188 | 0.00 |
DINING_FLR_6 | 30356.48 | 30356.48 | 91.53 | 2.265 | 2.265 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 23.98 | 0.01036 | 30.30 | 0.01337 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 29782.37 | 29782.37 | 288.30 | 2.225 | 2.225 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01013 | 29.46 | 0.01337 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9376.39 | 9376.39 | 22.75 | 0.699 | 0.699 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00906 | 30.30 | 0.01337 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1482.63 | 1482.63 | 0.75 | 0.065 | 0.854 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00796 | -16.30 | 0.00092 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2990.08 | 2990.08 | 44.58 | 0.131 | 0.131 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00785 | -16.30 | 0.00092 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 984.56 | 984.56 | 12.68 | 0.043 | 0.092 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00783 | -16.30 | 0.00092 | 0.092 | 0.00 |
MECH_FLR_1 | 1807.93 | 1807.93 | 11.01 | 0.079 | 0.079 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00778 | -16.30 | 0.00092 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1191.35 | 1191.35 | 12.57 | 0.052 | 0.058 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00781 | -16.30 | 0.00092 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2341.90 | 2341.90 | 30.01 | 0.103 | 0.103 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00777 | -16.30 | 0.00092 | 0.000 | 0.00 |
CAFE_FLR_1 | 7577.61 | 7577.61 | 40.12 | 0.333 | 0.676 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00787 | -16.30 | 0.00092 | 0.676 | 0.00 |
LOBBY_FLR_1 | 17717.29 | 17717.29 | 13.54 | 0.779 | 1.894 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00784 | -16.30 | 0.00092 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 6832.39 | 6832.39 | 175.09 | 0.302 | 0.302 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00785 | -16.30 | 0.00092 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 6831.98 | 6831.98 | 175.10 | 0.302 | 0.302 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00785 | -16.30 | 0.00092 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 39336.42 | 39336.42 | 1604.01 | 1.740 | 1.740 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00786 | -16.30 | 0.00092 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 39347.73 | 39347.73 | 1604.03 | 1.740 | 1.740 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00786 | -16.30 | 0.00092 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 6806.92 | 6806.92 | 174.44 | 0.301 | 0.301 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00785 | -16.30 | 0.00092 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 6806.52 | 6806.52 | 174.45 | 0.301 | 0.301 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00785 | -16.30 | 0.00092 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 10922.98 | 10922.98 | 28.05 | 0.480 | 0.480 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00789 | -16.30 | 0.00092 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2123.09 | 2123.09 | 54.41 | 0.094 | 0.094 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00788 | -16.30 | 0.00092 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2122.94 | 2122.94 | 54.41 | 0.094 | 0.094 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00788 | -16.30 | 0.00092 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10193.72 | 10193.72 | 415.55 | 0.451 | 0.451 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00788 | -16.30 | 0.00092 | 0.099 | 0.00 |
BANQUET_FLR_6 | 6980.42 | 6980.42 | 21.05 | 0.307 | 1.188 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00791 | -16.30 | 0.00092 | 1.188 | 0.00 |
DINING_FLR_6 | 7140.47 | 7140.47 | 21.53 | 0.314 | 1.188 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00791 | -16.30 | 0.00092 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 3246.87 | 3246.87 | 31.43 | 0.143 | 0.367 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00744 | -16.30 | 0.00092 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 7330.62 | 7330.62 | 17.79 | 0.322 | 0.322 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00792 | -16.30 | 0.00092 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 21.21 | 21.21 | 7.43 | 7.43 | 21.2105 | 11.6641 | 21.2105 | 0.5499 | 0.3000 |
FLR_3_DOAS | 16.55 | 2.05 | 5.32 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 7594.789 | 7594.789 | 1.187524 | 0.00006644 | 160.394 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7594.79 | 7594.79 | 1.187524 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00795781 | 50.1560 | 1482.63 | 0.00 | 7637.28 | 7637.28 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4028.869 | 4028.869 | 0.201882 | 0.00003525 | 99.048 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 4028.87 | 4028.87 | 0.201882 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00785280 | 49.5036 | 2990.08 | 0.00 | 4049.75 | 4049.75 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1601.272 | 1601.272 | 0.119853 | 0.00001401 | 36.431 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1601.27 | 1601.27 | 0.119853 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00782807 | 49.3490 | 984.56 | 0.00 | 1609.89 | 1609.89 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2307.891 | 2307.891 | 0.097173 | 0.00002019 | 59.540 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2307.89 | 2307.89 | 0.097173 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00778024 | 49.0513 | 1807.93 | 0.00 | 2319.54 | 2319.54 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1460.855 | 1460.855 | 0.052380 | 0.00001278 | 39.870 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1460.85 | 1460.85 | 0.052380 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00780685 | 49.2169 | 1191.35 | 0.00 | 1468.10 | 1468.10 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11712.716 | 11712.716 | 1.821487 | 0.00010247 | 247.449 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11712.72 | 11712.72 | 1.821487 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00776873 | 48.9806 | 2341.90 | 0.00 | 11778.24 | 11778.24 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 11990.871 | 11990.871 | 0.857659 | 0.00010490 | 274.719 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11990.87 | 11990.87 | 0.857659 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00787126 | 49.6185 | 7577.61 | 0.00 | 12055.27 | 12055.27 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 31215.504 | 31215.504 | 2.623208 | 0.00027309 | 698.769 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 31215.50 | 31215.50 | 2.623208 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00784332 | 49.4439 | 17717.29 | 0.00 | 31384.58 | 31384.58 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 11983.117 | -999.000 | 1.095604 | 0.00042800 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 11983.12 | 11724.86 | 1.095604 | 21.70 | 15.39 | 0.00859274 | 12.80 | 11.87 | 0.00850000 | 29.00 | 0.01336465 | 21.45 | 0.0000 | 21.11 | 0.00859274 | 53.7372 | 10909.23 | 0.00 | 12274.72 | 11791.69 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 6832.368 | 6832.368 | 0.302158 | 0.00005977 | 195.210 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 6832.37 | 6832.37 | 0.302158 | 21.11 | 14.51 | 0.00785134 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.11 | 0.00785134 | 49.1583 | 6832.39 | 0.00 | 7365.48 | 7365.48 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 11578.931 | -999.000 | 1.057725 | 0.00041356 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 11578.93 | 11320.95 | 1.057725 | 21.70 | 15.39 | 0.00859594 | 12.80 | 11.87 | 0.00850000 | 28.84 | 0.01336437 | 21.41 | 0.0000 | 21.11 | 0.00859594 | 53.7570 | 10532.05 | 0.00 | 11860.58 | 11385.48 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 6831.959 | 6831.959 | 0.302140 | 0.00005977 | 195.198 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 6831.96 | 6831.96 | 0.302140 | 21.11 | 14.51 | 0.00785134 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.11 | 0.00785134 | 49.1583 | 6831.98 | 0.00 | 7365.04 | 7365.04 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 68449.099 | -999.000 | 6.381570 | 0.00244480 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 68449.10 | 68098.62 | 6.381570 | 21.70 | 15.32 | 0.00852167 | 12.80 | 11.87 | 0.00850000 | 30.14 | 0.01336669 | 21.78 | 0.0000 | 21.11 | 0.00852167 | 53.2973 | 63546.42 | 0.00 | 70130.88 | 68485.45 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 39336.351 | 39336.351 | 1.739652 | 0.00034413 | 1123.887 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 39336.35 | 39336.35 | 1.739652 | 21.11 | 14.52 | 0.00786289 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.11 | 0.00786289 | 49.2290 | 39336.42 | 0.00 | 42405.86 | 42405.86 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 62080.213 | -999.000 | 5.382837 | 0.00221732 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | unknown | 7/21 15:10:00 | 62080.21 | 58046.83 | 5.382837 | 21.70 | 15.56 | 0.00879254 | 12.80 | 11.87 | 0.00850000 | 30.21 | 0.01336679 | 21.80 | 0.0000 | 21.11 | 0.00879254 | 54.9700 | 53596.94 | 0.00 | 63551.78 | 58382.46 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 39347.653 | 39347.653 | 1.740152 | 0.00034423 | 1124.210 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 39347.65 | 39347.65 | 1.740152 | 21.11 | 14.52 | 0.00786290 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.11 | 0.00786290 | 49.2290 | 39347.73 | 0.00 | 42418.05 | 42418.05 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 10902.737 | -999.000 | 0.994227 | 0.00038941 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | unknown | 7/21 09:50:00 | 10902.74 | 10644.04 | 0.994227 | 21.70 | 15.40 | 0.00860233 | 12.80 | 11.87 | 0.00850000 | 26.50 | 0.01336023 | 20.72 | 0.0000 | 21.11 | 0.00860233 | 53.7963 | 9899.78 | 0.00 | 11167.71 | 10704.74 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 6806.900 | 6806.900 | 0.301032 | 0.00005955 | 194.482 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 6806.90 | 6806.90 | 0.301032 | 21.11 | 14.51 | 0.00785080 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.11 | 0.00785080 | 49.1549 | 6806.92 | 0.00 | 7338.03 | 7338.03 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10559.513 | -999.000 | 0.961998 | 0.00037715 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | unknown | 7/21 09:30:00 | 10559.51 | 10300.47 | 0.961998 | 21.70 | 15.40 | 0.00860588 | 12.80 | 11.87 | 0.00850000 | 25.98 | 0.01335930 | 20.56 | 0.0000 | 21.11 | 0.00860588 | 53.8183 | 9578.87 | 0.00 | 10816.02 | 10359.22 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 6806.491 | 6806.491 | 0.301014 | 0.00005955 | 194.471 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 6806.49 | 6806.49 | 0.301014 | 21.11 | 14.51 | 0.00785080 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.11 | 0.00785080 | 49.1549 | 6806.52 | 0.00 | 7337.59 | 7337.59 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 14445.396 | 14445.396 | 0.684467 | 0.00012637 | 360.251 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 14445.40 | 14445.40 | 0.684467 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00788633 | 49.7114 | 10922.98 | 0.00 | 14519.91 | 14519.91 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3136.025 | -999.000 | 0.287050 | 0.00011201 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3136.03 | 3071.42 | 0.287050 | 21.70 | 15.38 | 0.00858856 | 12.80 | 11.87 | 0.00850000 | 29.00 | 0.01336465 | 21.45 | 0.0000 | 21.11 | 0.00858856 | 53.7114 | 2858.24 | 0.00 | 3212.38 | 3088.92 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2123.078 | 2123.078 | 0.093892 | 0.00001857 | 60.658 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2123.08 | 2123.08 | 0.093892 | 21.11 | 14.54 | 0.00787988 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.11 | 0.00787988 | 49.3347 | 2123.09 | 0.00 | 2288.74 | 2288.74 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3021.896 | -999.000 | 0.276354 | 0.00010793 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 3021.90 | 2957.37 | 0.276354 | 21.70 | 15.39 | 0.00859187 | 12.80 | 11.87 | 0.00850000 | 28.84 | 0.01336437 | 21.41 | 0.0000 | 21.11 | 0.00859187 | 53.7318 | 2751.73 | 0.00 | 3095.44 | 2974.22 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2122.933 | 2122.933 | 0.093886 | 0.00001857 | 60.654 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2122.93 | 2122.93 | 0.093886 | 21.11 | 14.54 | 0.00787988 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.11 | 0.00787988 | 49.3347 | 2122.94 | 0.00 | 2288.58 | 2288.58 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 14773.393 | -999.000 | 1.329859 | 0.00052766 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 14773.39 | 14264.05 | 1.329859 | 21.70 | 15.44 | 0.00865034 | 12.80 | 11.87 | 0.00850000 | 30.14 | 0.01336669 | 21.78 | 0.0000 | 21.11 | 0.00865034 | 54.0931 | 13241.46 | 0.00 | 15130.14 | 14345.63 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 10193.694 | 10193.694 | 0.450813 | 0.00008918 | 291.242 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 10193.69 | 10193.69 | 0.450813 | 21.11 | 14.54 | 0.00788472 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.11 | 0.00788472 | 49.3644 | 10193.72 | 0.00 | 10989.11 | 10989.11 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 13052.770 | 13052.770 | 1.179933 | 0.00011419 | 289.530 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 13052.77 | 13052.77 | 1.179933 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00790988 | 49.8582 | 6980.42 | 0.00 | 13123.72 | 13123.72 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 13517.091 | 13517.091 | 1.239062 | 0.00011825 | 299.331 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 13517.09 | 13517.09 | 1.239062 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00791188 | 49.8707 | 7140.47 | 0.00 | 13590.62 | 13590.62 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 9504.013 | 9504.013 | 1.217323 | 0.00008315 | 203.660 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 9504.01 | 9504.01 | 1.217323 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00744292 | 46.9542 | 3246.87 | 0.00 | 9556.94 | 9556.94 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 9297.828 | 9297.828 | 0.382241 | 0.00008134 | 241.694 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 9297.83 | 9297.83 | 0.382241 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00792465 | 49.9500 | 7330.62 | 0.00 | 9344.62 | 9344.62 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 624648.760 | -999.000 | 21.210495 | 0.02231101 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 624648.76 | 417476.63 | 21.210495 | 27.46 | 19.83 | 0.01172403 | 10.94 | 10.94 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 54.9797 | 23.99 | 0.00971004 | 50.8837 | 284368.72 | 0.00 | 634143.51 | 412736.54 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 247703.089 | 247703.089 | 6.363149 | 0.00216701 | 3894.461 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 247703.09 | 247703.09 | 6.363149 | -16.30 | -16.30 | 0.00092409 | 16.70 | 12.95 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 183.2656 | 21.00 | 0.00786711 | 49.5921 | 71217.47 | 0.00 | 200313.63 | 200313.63 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 75158.601 | -999.000 | 2.051317 | 0.00268449 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 75158.60 | 45858.12 | 2.051317 | 30.30 | 21.83 | 0.01336696 | 11.91 | 11.51 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 99.9965 | 21.11 | 0.00864732 | 54.0734 | 164823.09 | 0.00 | 76128.50 | 46083.04 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 23955.952 | 23955.952 | 0.615395 | 0.00020958 | 376.643 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 23955.95 | 23955.95 | 0.615395 | -16.30 | -16.30 | 0.00092409 | 16.70 | 12.95 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 333.3216 | 21.11 | 0.00786302 | 49.2298 | 120401.72 | 0.00 | 19372.81 | 19372.81 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 7594.789 | 7594.789 | 1.187524 | 0.00006644 | 160.394 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 1.4214 | 1.449967 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7594.79 | 7594.79 | 1.0000 | 1.39406409 | 1.187524 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.06643575 | 60.00 | 32.22 | 27.78 | 0.000 | 7594.79 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00795781 | 21.00 | 0.00795781 | 50.1560 | 1482.63 | 0.00 | 7637.28 | 7637.28 | 1.39406409 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.97 | 15.21 | 0.00800000 | 42413.2 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4028.869 | 4028.869 | 0.201882 | 0.00003525 | 99.048 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 0.7540 | 0.769176 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 4028.87 | 4028.87 | 1.0000 | 0.23699452 | 0.201882 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.03524271 | 60.00 | 32.22 | 27.78 | 0.000 | 4028.87 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00785280 | 21.00 | 0.00785280 | 49.5036 | 2990.08 | 0.00 | 4049.75 | 4049.75 | 0.23699452 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 33.36 | 19.14 | 0.00800000 | 54022.7 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1601.272 | 1601.272 | 0.119853 | 0.00001401 | 36.431 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 0.2997 | 0.305709 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1601.27 | 1601.27 | 1.0000 | 0.14069825 | 0.119853 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.01400720 | 60.00 | 32.22 | 27.78 | 0.000 | 1601.27 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00782807 | 21.00 | 0.00782807 | 49.3490 | 984.56 | 0.00 | 1609.89 | 1609.89 | 0.14069825 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.82 | 17.30 | 0.00800000 | 48376.9 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2307.891 | 2307.891 | 0.097173 | 0.00002019 | 59.540 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 0.4319 | 0.440614 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2307.89 | 2307.89 | 1.0000 | 0.11407352 | 0.097173 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.02018838 | 60.00 | 32.22 | 27.78 | 0.000 | 2307.89 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00778024 | 21.00 | 0.00778024 | 49.0513 | 1807.93 | 0.00 | 2319.54 | 2319.54 | 0.11407352 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 36.54 | 20.14 | 0.00800000 | 57268.4 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1460.855 | 1460.855 | 0.052380 | 0.00001278 | 39.870 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 0.2734 | 0.278901 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1460.85 | 1460.85 | 1.0000 | 0.06148965 | 0.052380 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.01277889 | 60.00 | 32.22 | 27.78 | 0.000 | 1460.85 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00780685 | 21.00 | 0.00780685 | 49.2169 | 1191.35 | 0.00 | 1468.10 | 1468.10 | 0.06148965 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60810.3 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11712.716 | 11712.716 | 1.821487 | 0.00010247 | 247.449 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 2.1920 | 2.236146 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11712.72 | 11712.72 | 1.0000 | 2.13829017 | 1.821487 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.10245750 | 60.00 | 32.22 | 27.78 | 0.000 | 11712.72 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00776873 | 21.00 | 0.00776873 | 48.9806 | 2341.90 | 0.00 | 11778.24 | 11778.24 | 2.13829017 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.00 | 15.22 | 0.00800000 | 42443.0 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11990.871 | 11990.871 | 0.857659 | 0.00010490 | 274.719 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 2.2441 | 2.289250 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11990.87 | 11990.87 | 1.0000 | 1.00682703 | 0.857659 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.10489067 | 60.00 | 32.22 | 27.78 | 0.000 | 11990.87 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00787126 | 21.00 | 0.00787126 | 49.6185 | 7577.61 | 0.00 | 12055.27 | 12055.27 | 1.00682703 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.34 | 17.48 | 0.00800000 | 48908.3 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 31215.504 | 31215.504 | 2.623208 | 0.00027309 | 698.769 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 5.8420 | 5.959542 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 31215.50 | 31215.50 | 1.0000 | 3.07945012 | 2.623208 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.27305899 | 60.00 | 32.22 | 27.78 | 0.000 | 31215.50 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00784332 | 21.00 | 0.00784332 | 49.4439 | 17717.29 | 0.00 | 31384.58 | 31384.58 | 3.07945012 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.59 | 16.88 | 0.00800000 | 47126.4 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11983.117 | -999.000 | 1.095604 | 0.00042800 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8135 | 1004.8586 | 1.1739 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.095604 | 1.28615728 | 4197.9300 | 999.8980 | 32.01008694 | 13.37 | 6.70 | 6.67 | 896288.62 | 1.3370 | 1.336946 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 11983.12 | 11724.86 | 1.0000 | 1.28615728 | 1.095604 | 21.70 | 15.39 | 0.00859274 | 43639.2 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.42795752 | 6.70 | 13.37 | 6.67 | 0.000 | 11983.12 | 29.00 | 0.01336465 | 21.45 | 0.00000000 | 0.0000 | 21.11 | 0.00859274 | 21.11 | 0.00859274 | 53.7372 | 10909.23 | 0.00 | 12274.72 | 11791.69 | 1.28615728 | 21.70 | 15.64 | 0.00859274 | 43639.2 | 12.72 | 12.01 | 0.00844398 | 34095.5 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6832.368 | 6832.368 | 0.302158 | 0.00005977 | 195.210 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.095604 | 1.28615728 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 1.2787 | 1.304409 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 6832.37 | 6832.37 | 1.0000 | 0.35471085 | 0.302158 | 21.11 | 14.51 | 0.00785134 | 41156.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.05976644 | 60.00 | 32.22 | 27.78 | 0.000 | 6832.37 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.11 | 0.00785134 | 21.11 | 0.00785134 | 49.1583 | 6832.39 | 0.00 | 7365.48 | 7365.48 | 0.35471085 | 16.60 | 13.01 | 0.00785134 | 36558.4 | 36.97 | 20.16 | 0.00785134 | 57323.1 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11578.931 | -999.000 | 1.057725 | 0.00041356 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8194 | 1004.8586 | 1.1739 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.057725 | 1.24168993 | 4197.9300 | 999.8980 | 32.01008694 | 13.37 | 6.70 | 6.67 | 896288.62 | 1.2919 | 1.291851 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 11578.93 | 11320.95 | 1.0000 | 1.24168993 | 1.057725 | 21.70 | 15.39 | 0.00859594 | 43647.3 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.41352269 | 6.70 | 13.37 | 6.67 | 0.000 | 11578.93 | 28.84 | 0.01336437 | 21.41 | 0.00000000 | 0.0000 | 21.11 | 0.00859594 | 21.11 | 0.00859594 | 53.7570 | 10532.05 | 0.00 | 11860.58 | 11385.48 | 1.24168993 | 21.70 | 15.64 | 0.00859594 | 43647.3 | 12.72 | 12.01 | 0.00844439 | 34095.4 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6831.959 | 6831.959 | 0.302140 | 0.00005977 | 195.198 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.057725 | 1.24168993 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 1.2786 | 1.304331 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 6831.96 | 6831.96 | 1.0000 | 0.35468959 | 0.302140 | 21.11 | 14.51 | 0.00785134 | 41156.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.05976286 | 60.00 | 32.22 | 27.78 | 0.000 | 6831.96 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.11 | 0.00785134 | 21.11 | 0.00785134 | 49.1583 | 6831.98 | 0.00 | 7365.04 | 7365.04 | 0.35468959 | 16.60 | 13.01 | 0.00785134 | 36558.4 | 36.97 | 20.16 | 0.00785134 | 57323.1 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 68449.099 | -999.000 | 6.381570 | 0.00244480 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6814 | 1004.8586 | 1.1739 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.381570 | 7.49148649 | 4197.9300 | 999.8980 | 32.01008694 | 13.37 | 6.70 | 6.67 | 896288.62 | 7.6369 | 7.636806 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 68449.10 | 68098.62 | 1.0000 | 7.49148649 | 6.381570 | 21.70 | 15.32 | 0.00852167 | 43459.1 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 2.44454817 | 6.70 | 13.37 | 6.67 | 0.000 | 68449.10 | 30.14 | 0.01336669 | 21.78 | 0.00000000 | 0.0000 | 21.11 | 0.00852167 | 21.11 | 0.00852167 | 53.2973 | 63546.42 | 0.00 | 70130.88 | 68485.45 | 7.49148649 | 21.70 | 15.58 | 0.00852167 | 43459.1 | 12.74 | 12.01 | 0.00843467 | 34097.7 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 39336.351 | 39336.351 | 1.739652 | 0.00034413 | 1123.887 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.381570 | 7.49148649 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 7.3618 | 7.509942 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 39336.35 | 39336.35 | 1.0000 | 2.04222160 | 1.739652 | 21.11 | 14.52 | 0.00786289 | 41186.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.34409645 | 60.00 | 32.22 | 27.78 | 0.000 | 39336.35 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.11 | 0.00786289 | 21.11 | 0.00786289 | 49.2290 | 39336.42 | 0.00 | 42405.86 | 42405.86 | 2.04222160 | 16.60 | 13.02 | 0.00786289 | 36587.6 | 36.97 | 20.17 | 0.00786289 | 57352.2 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 62080.213 | -999.000 | 5.382837 | 0.00221732 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1849 | 1004.8586 | 1.1739 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.382837 | 6.31904870 | 4197.9300 | 999.8980 | 32.01008694 | 13.37 | 6.70 | 6.67 | 896288.62 | 6.9264 | 6.926235 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | unknown | unknown | unknown | 7/21 15:10:00 | Sensible | 62080.21 | 58046.83 | 1.0000 | 6.31904870 | 5.382837 | 21.70 | 15.56 | 0.00879254 | 44146.5 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 2.21709376 | 6.70 | 13.37 | 6.67 | 0.000 | 62080.21 | 30.21 | 0.01336679 | 21.80 | 0.00000000 | 0.0000 | 21.11 | 0.00879254 | 21.11 | 0.00879254 | 54.9700 | 53596.94 | 0.00 | 63551.78 | 58382.46 | 6.31904870 | 21.70 | 15.82 | 0.00879254 | 44146.5 | 12.65 | 12.01 | 0.00846849 | 34089.3 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 39347.653 | 39347.653 | 1.740152 | 0.00034423 | 1124.210 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.382837 | 6.31904870 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 7.3639 | 7.512100 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 39347.65 | 39347.65 | 1.0000 | 2.04280840 | 1.740152 | 21.11 | 14.52 | 0.00786290 | 41186.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.34419532 | 60.00 | 32.22 | 27.78 | 0.000 | 39347.65 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.11 | 0.00786290 | 21.11 | 0.00786290 | 49.2290 | 39347.73 | 0.00 | 42418.05 | 42418.05 | 2.04280840 | 16.60 | 13.02 | 0.00786290 | 36587.6 | 36.97 | 20.17 | 0.00786290 | 57352.2 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10902.737 | -999.000 | 0.994227 | 0.00038941 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8313 | 1004.8586 | 1.1739 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.994227 | 1.16714816 | 4197.9300 | 999.8980 | 32.01008694 | 13.37 | 6.70 | 6.67 | 896288.62 | 1.2164 | 1.216409 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | unknown | unknown | unknown | 7/21 09:50:00 | Sensible | 10902.74 | 10644.04 | 1.0000 | 1.16714816 | 0.994227 | 21.70 | 15.40 | 0.00860233 | 43663.5 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.38937351 | 6.70 | 13.37 | 6.67 | 0.000 | 10902.74 | 26.50 | 0.01336023 | 20.72 | 0.00000000 | 0.0000 | 21.11 | 0.00860233 | 21.11 | 0.00860233 | 53.7963 | 9899.78 | 0.00 | 11167.71 | 10704.74 | 1.16714816 | 21.70 | 15.65 | 0.00860233 | 43663.5 | 12.71 | 12.01 | 0.00844521 | 34095.2 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6806.900 | 6806.900 | 0.301032 | 0.00005955 | 194.482 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.994227 | 1.16714816 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 1.2739 | 1.299547 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 6806.90 | 6806.90 | 1.0000 | 0.35338862 | 0.301032 | 21.11 | 14.51 | 0.00785080 | 41155.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.05954365 | 60.00 | 32.22 | 27.78 | 0.000 | 6806.90 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.11 | 0.00785080 | 21.11 | 0.00785080 | 49.1549 | 6806.92 | 0.00 | 7338.03 | 7338.03 | 0.35338862 | 16.60 | 13.01 | 0.00785080 | 36557.0 | 36.97 | 20.16 | 0.00785080 | 57321.7 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10559.513 | -999.000 | 0.961998 | 0.00037715 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8379 | 1004.8586 | 1.1739 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.961998 | 1.12931426 | 4197.9300 | 999.8980 | 32.01008694 | 13.37 | 6.70 | 6.67 | 896288.62 | 1.1781 | 1.178116 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | unknown | unknown | unknown | 7/21 09:30:00 | Sensible | 10559.51 | 10300.47 | 1.0000 | 1.12931426 | 0.961998 | 21.70 | 15.40 | 0.00860588 | 43672.6 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.37711582 | 6.70 | 13.37 | 6.67 | 0.000 | 10559.51 | 25.98 | 0.01335930 | 20.56 | 0.00000000 | 0.0000 | 21.11 | 0.00860588 | 21.11 | 0.00860588 | 53.8183 | 9578.87 | 0.00 | 10816.02 | 10359.22 | 1.12931426 | 21.70 | 15.65 | 0.00860588 | 43672.6 | 12.71 | 12.01 | 0.00844566 | 34095.1 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6806.491 | 6806.491 | 0.301014 | 0.00005955 | 194.471 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.961998 | 1.12931426 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 1.2738 | 1.299469 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 6806.49 | 6806.49 | 1.0000 | 0.35336741 | 0.301014 | 21.11 | 14.51 | 0.00785080 | 41155.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.05954008 | 60.00 | 32.22 | 27.78 | 0.000 | 6806.49 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.11 | 0.00785080 | 21.11 | 0.00785080 | 49.1549 | 6806.52 | 0.00 | 7337.59 | 7337.59 | 0.35336741 | 16.60 | 13.01 | 0.00785080 | 36557.0 | 36.97 | 20.16 | 0.00785080 | 57321.7 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14445.396 | 14445.396 | 0.684467 | 0.00012637 | 360.251 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 2.7035 | 2.757858 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 14445.40 | 14445.40 | 1.0000 | 0.80351262 | 0.684467 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.12636173 | 60.00 | 32.22 | 27.78 | 0.000 | 14445.40 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00788633 | 21.00 | 0.00788633 | 49.7114 | 10922.98 | 0.00 | 14519.91 | 14519.91 | 0.80351262 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.32 | 19.44 | 0.00800000 | 55005.3 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3136.025 | -999.000 | 0.287050 | 0.00011201 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8057 | 1004.8586 | 1.1739 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.287050 | 0.33697524 | 4197.9300 | 999.8980 | 32.01008694 | 13.37 | 6.70 | 6.67 | 896288.62 | 0.3499 | 0.349884 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 3136.03 | 3071.42 | 1.0000 | 0.33697524 | 0.287050 | 21.70 | 15.38 | 0.00858856 | 43628.6 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.11199803 | 6.70 | 13.37 | 6.67 | 0.000 | 3136.03 | 29.00 | 0.01336465 | 21.45 | 0.00000000 | 0.0000 | 21.11 | 0.00858856 | 21.11 | 0.00858856 | 53.7114 | 2858.24 | 0.00 | 3212.38 | 3088.92 | 0.33697524 | 21.70 | 15.64 | 0.00858856 | 43628.6 | 12.72 | 12.01 | 0.00844344 | 34095.6 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2123.078 | 2123.078 | 0.093892 | 0.00001857 | 60.658 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.287050 | 0.33697524 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 0.3973 | 0.405330 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 2123.08 | 2123.08 | 1.0000 | 0.11022231 | 0.093892 | 21.11 | 14.54 | 0.00787988 | 41229.1 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.01857172 | 60.00 | 32.22 | 27.78 | 0.000 | 2123.08 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.11 | 0.00787988 | 21.11 | 0.00787988 | 49.3347 | 2123.09 | 0.00 | 2288.74 | 2288.74 | 0.11022231 | 16.60 | 13.03 | 0.00787988 | 36630.6 | 36.97 | 20.18 | 0.00787988 | 57395.4 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3021.896 | -999.000 | 0.276354 | 0.00010793 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8119 | 1004.8586 | 1.1739 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.276354 | 0.32441929 | 4197.9300 | 999.8980 | 32.01008694 | 13.37 | 6.70 | 6.67 | 896288.62 | 0.3372 | 0.337150 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 3021.90 | 2957.37 | 1.0000 | 0.32441929 | 0.276354 | 21.70 | 15.39 | 0.00859187 | 43637.0 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.10792210 | 6.70 | 13.37 | 6.67 | 0.000 | 3021.90 | 28.84 | 0.01336437 | 21.41 | 0.00000000 | 0.0000 | 21.11 | 0.00859187 | 21.11 | 0.00859187 | 53.7318 | 2751.73 | 0.00 | 3095.44 | 2974.22 | 0.32441929 | 21.70 | 15.64 | 0.00859187 | 43637.0 | 12.72 | 12.01 | 0.00844386 | 34095.5 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2122.933 | 2122.933 | 0.093886 | 0.00001857 | 60.654 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.276354 | 0.32441929 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 0.3973 | 0.405302 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 2122.93 | 2122.93 | 1.0000 | 0.11021476 | 0.093886 | 21.11 | 14.54 | 0.00787988 | 41229.1 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.01857045 | 60.00 | 32.22 | 27.78 | 0.000 | 2122.93 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.11 | 0.00787988 | 21.11 | 0.00787988 | 49.3347 | 2122.94 | 0.00 | 2288.58 | 2288.58 | 0.11021476 | 16.60 | 13.03 | 0.00787988 | 36630.6 | 36.97 | 20.18 | 0.00787988 | 57395.4 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14773.393 | -999.000 | 1.329859 | 0.00052766 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9205 | 1004.8586 | 1.1739 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.329859 | 1.56115499 | 4197.9300 | 999.8980 | 32.01008694 | 13.37 | 6.70 | 6.67 | 896288.62 | 1.6483 | 1.648254 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 14773.39 | 14264.05 | 1.0000 | 1.56115499 | 1.329859 | 21.70 | 15.44 | 0.00865034 | 43785.3 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.52760767 | 6.70 | 13.37 | 6.67 | 0.000 | 14773.39 | 30.14 | 0.01336669 | 21.78 | 0.00000000 | 0.0000 | 21.11 | 0.00865034 | 21.11 | 0.00865034 | 54.0931 | 13241.46 | 0.00 | 15130.14 | 14345.63 | 1.56115499 | 21.70 | 15.69 | 0.00865034 | 43785.3 | 12.70 | 12.01 | 0.00845129 | 34093.7 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10193.694 | 10193.694 | 0.450813 | 0.00008918 | 291.242 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.329859 | 1.56115499 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 1.9077 | 1.946140 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 10193.69 | 10193.69 | 1.0000 | 0.52922101 | 0.450813 | 21.11 | 14.54 | 0.00788472 | 41241.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.08916979 | 60.00 | 32.22 | 27.78 | 0.000 | 10193.69 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.11 | 0.00788472 | 21.11 | 0.00788472 | 49.3644 | 10193.72 | 0.00 | 10989.11 | 10989.11 | 0.52922101 | 16.60 | 13.04 | 0.00788472 | 36642.9 | 36.97 | 20.18 | 0.00788472 | 57407.5 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13052.770 | 13052.770 | 1.179933 | 0.00011419 | 289.530 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 2.4428 | 2.491984 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 13052.77 | 13052.77 | 1.0000 | 1.38515293 | 1.179933 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.11417968 | 60.00 | 32.22 | 27.78 | 0.000 | 13052.77 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00790988 | 21.00 | 0.00790988 | 49.8582 | 6980.42 | 0.00 | 13123.72 | 13123.72 | 1.38515293 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.89 | 16.63 | 0.00800000 | 46409.3 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13517.091 | 13517.091 | 1.239062 | 0.00011825 | 299.331 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 2.5297 | 2.580630 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 13517.09 | 13517.09 | 1.0000 | 1.45456618 | 1.239062 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.11824135 | 60.00 | 32.22 | 27.78 | 0.000 | 13517.09 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00791188 | 21.00 | 0.00791188 | 49.8707 | 7140.47 | 0.00 | 13590.62 | 13590.62 | 1.45456618 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.76 | 16.58 | 0.00800000 | 46278.1 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9504.013 | 9504.013 | 1.217323 | 0.00008315 | 203.660 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 1.7787 | 1.814469 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 9504.01 | 9504.01 | 1.0000 | 1.42904676 | 1.217323 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.08313677 | 60.00 | 32.22 | 27.78 | 0.000 | 9504.01 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.69 | 0.00744292 | 21.00 | 0.00744292 | 46.9542 | 3246.87 | 0.00 | 9556.94 | 9556.94 | 1.42904676 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.16 | 15.65 | 0.00800000 | 43622.4 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9297.828 | 9297.828 | 0.382241 | 0.00008134 | 241.694 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 1.7401 | 1.775105 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 9297.83 | 9297.83 | 1.0000 | 0.44872222 | 0.382241 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.08133316 | 60.00 | 32.22 | 27.78 | 0.000 | 9297.83 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.00 | 0.00792465 | 21.00 | 0.00792465 | 49.9500 | 7330.62 | 0.00 | 9344.62 | 9344.62 | 0.44872222 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 37.02 | 20.28 | 0.00800000 | 57759.7 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 624648.760 | -999.000 | 21.210495 | 0.02231101 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.6344 | 1004.8586 | 1.1739 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.210495 | 24.89953740 | 4197.9300 | 999.8980 | 32.01008694 | 13.37 | 6.70 | 6.67 | 896288.62 | 69.6928 | 69.692814 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 624648.76 | 417476.63 | 1.0000 | 24.89953740 | 21.210495 | 27.46 | 19.83 | 0.01172403 | 57511.4 | 10.94 | 10.94 | 0.00850000 | 32424.7 | 22.30873043 | 6.70 | 13.37 | 6.67 | 47525.055 | 577123.71 | 30.30 | 0.01336696 | 21.83 | 11.66146000 | 54.9797 | 23.99 | 0.00971713 | 23.99 | 0.00971004 | 50.8837 | 284368.72 | 0.00 | 634143.51 | 412736.54 | 24.89953740 | 27.46 | 20.11 | 0.01172403 | 57511.4 | 11.31 | 11.17 | 0.00819821 | 32043.3 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 247703.089 | 247703.089 | 6.363149 | 0.00216701 | 3894.461 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.210495 | 24.89953740 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 46.3575 | 47.290504 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 247703.09 | 247703.09 | 1.0000 | 7.46986122 | 6.363149 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 2.16679362 | 60.00 | 32.22 | 27.78 | 0.000 | 247703.09 | -16.30 | 0.00092409 | -16.30 | 11.66146000 | 183.2656 | 20.98 | 0.00786653 | 21.00 | 0.00786711 | 49.5921 | 71217.47 | 0.00 | 200313.63 | 200313.63 | 7.46986122 | 2.80 | -2.91 | 0.00092409 | 5129.5 | 29.44 | 11.28 | 0.00092409 | 31945.7 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 75158.601 | -999.000 | 2.051317 | 0.00268449 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1029.6885 | 1004.8586 | 1.1739 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.40800857 | 4197.9300 | 999.8980 | 32.01008694 | 13.37 | 6.70 | 6.67 | 896288.62 | 8.3855 | 8.385536 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 75158.60 | 45858.12 | 1.0000 | 2.40809323 | 2.051317 | 30.30 | 21.83 | 0.01336696 | 64629.5 | 11.91 | 11.51 | 0.00850000 | 33418.7 | 2.68421723 | 6.70 | 13.37 | 6.67 | 2195.006 | 72963.59 | 30.30 | 0.01336696 | 21.83 | 2.05124512 | 99.9965 | 21.11 | 0.00864305 | 21.11 | 0.00864732 | 54.0734 | 164823.09 | 0.00 | 76128.50 | 46083.04 | 2.40809323 | 30.30 | 22.13 | 0.01336696 | 64629.5 | 11.72 | 11.57 | 0.00842116 | 33015.9 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 23955.952 | 23955.952 | 0.615395 | 0.00020958 | 376.643 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.40800857 | 4197.9300 | 999.8980 | 4.58187890 | 54.44 | 82.22 | 27.78 | 534331.82 | 4.4833 | 4.573577 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 23955.95 | 23955.95 | 1.0000 | 0.72242797 | 0.615395 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 0.20955574 | 60.00 | 32.22 | 27.78 | 0.000 | 23955.95 | -16.30 | 0.00092409 | -16.30 | 2.05124512 | 333.3216 | 21.11 | 0.00786266 | 21.11 | 0.00786302 | 49.2298 | 120401.72 | 0.00 | 19372.81 | 19372.81 | 0.72242797 | 2.80 | -2.91 | 0.00092409 | 5129.5 | 29.44 | 11.28 | 0.00092409 | 31945.7 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 21.21 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 216.00 | 7562.83 | 29.83 |
RETAIL_1_FLR_1 | 2750.33 | 7664.50 | 2101.17 |
RETAIL_2_FLR_1 | 1249.83 | 7302.50 | 539.00 |
MECH_FLR_1 | 1613.33 | 7953.67 | 1460.17 |
STORAGE_FLR_1 | 1716.67 | 8320.33 | 1679.50 |
LAUNDRY_FLR_1 | 6323.83 | 3521.00 | 2394.83 |
CAFE_FLR_1 | 2606.83 | 6588.33 | 1182.33 |
LOBBY_FLR_1 | 1811.00 | 6498.67 | 602.00 |
ROOM_1_FLR_3 | 2522.83 | 8309.67 | 2477.67 |
ROOM_2_FLR_3 | 3396.17 | 8057.33 | 3095.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1703.50 | 8710.33 | 1693.50 |
ROOM_5_FLR_3 | 2435.33 | 8239.50 | 2418.17 |
ROOM_6_FLR_3 | 3197.83 | 8080.83 | 3012.00 |
CORRIDOR_FLR_3 | 1727.00 | 8325.00 | 1703.00 |
ROOM_1_FLR_6 | 3166.17 | 8215.50 | 3048.50 |
ROOM_2_FLR_6 | 4004.33 | 8001.00 | 3678.17 |
ROOM_3_MULT9_FLR_6 | 2030.83 | 8227.83 | 1974.50 |
BANQUET_FLR_6 | 3586.00 | 4064.00 | 624.17 |
DINING_FLR_6 | 4340.83 | 2905.83 | 557.83 |
KITCHEN_FLR_6 | 7872.17 | 6421.33 | 5928.17 |
CORRIDOR_FLR_6 | 2047.67 | 7678.50 | 1591.33 |
Facility | 8717.33 | 8760.00 | 7786.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 8.67 | 0.00 | 8.67 |
ROOM_2_FLR_3 | 0.00 | 13.00 | 0.00 | 13.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1.17 | 48.83 | 1.17 | 48.83 |
ROOM_5_FLR_3 | 0.00 | 2.67 | 0.00 | 2.67 |
ROOM_6_FLR_3 | 0.00 | 24.33 | 0.00 | 24.33 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 12.00 | 0.00 | 12.00 |
ROOM_2_FLR_6 | 0.00 | 19.67 | 0.00 | 19.67 |
ROOM_3_MULT9_FLR_6 | 0.00 | 10.33 | 0.00 | 10.33 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1.17 | 80.33 | 1.17 | 80.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.74 | 106.50 | 4826.41 | 0.914 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.787 | 0.035 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.436 | 0.012 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.546 | 0.013 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.508 | 0.013 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 24.436 | 0.037 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.49 | 142.30 | 748.35 | 4.222 | 0.027 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.88 | 422.44 | 5183.56 | 1.886 | 0.011 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.045 | 0.000 | 0.063 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.045 | 0.000 | 0.055 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.403 | 0.020 | 0.000 | 0.101 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.045 | 0.000 | 0.063 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.045 | 0.000 | 0.064 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.526 | 0.005 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.355 | 0.045 | 0.000 | 0.076 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.045 | 0.000 | 0.061 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.403 | 0.037 | 0.000 | 0.121 |
BANQUET_FLR_6 | 144.86 | 249.90 | 1010.89 | 4.844 | 0.013 | 0.000 | 0.000 |
DINING_FLR_6 | 144.86 | 249.90 | 1010.89 | 5.225 | 0.013 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 21.407 | 0.038 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 1.112 | 0.009 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.74 | 106.50 | 4826.41 | 0.840 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.596 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.362 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.522 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.487 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 20.677 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.49 | 142.30 | 748.35 | 4.012 | 0.000 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.88 | 422.44 | 5183.56 | 1.774 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.000 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.494 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.86 | 249.90 | 1010.89 | 4.093 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 144.86 | 249.90 | 1010.89 | 4.304 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 13.614 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 1.064 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.74 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.49 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.88 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.15 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.86 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.86 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.89 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.86 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 872.55 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 37956001.80 | 0.00 | 37956001.80 | 0.00 | 37956001.80 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 6408255.52 | 0.00 | 6408255.52 | 79874.09 | 6488129.61 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3809425.12 | 0.00 | 3809425.12 | 30831.50 | 3840256.62 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 3068883.56 | 0.00 | 3068883.56 | 72867.35 | 3141750.91 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1648136.93 | 0.00 | 1648136.93 | 42040.45 | 1690177.38 | 1821682.01 | 8756.50 | 1.50 | 2.00 | 0.00 |
LAUNDRY_FLR_1 | 65115456.06 | 0.00 | 65115456.06 | 99496.64 | 65214952.70 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 27223385.33 | 0.00 | 27223385.33 | 176566.20 | 27399951.53 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 84126264.59 | 0.00 | 84126264.59 | 504489.96 | 84630754.54 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 64197.68 | 1524354.39 | 46361.43 | 1570715.82 | 1946875.62 | 2190.00 | 5930.00 | 640.00 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 55536.83 | 1515522.47 | 46357.89 | 1561880.35 | 1946647.51 | 2190.00 | 6026.97 | 543.03 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 613.98 | 1100525.95 | 12935.36 | 1113461.31 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 368.83 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 64759.42 | 19868588.71 | 12938.89 | 19881527.61 | 26405105.73 | 2190.00 | 5932.08 | 637.92 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 64257.59 | 1524414.30 | 46361.43 | 1570775.73 | 1946875.62 | 2190.00 | 5930.00 | 640.00 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 64813.71 | 1524799.35 | 46357.89 | 1571157.24 | 1946647.51 | 2190.00 | 5932.94 | 637.06 | 0.00 |
CORRIDOR_FLR_3 | 21585296.03 | 0.00 | 21585296.03 | 56060.29 | 21641356.32 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 77895.82 | 442934.99 | 46371.22 | 489306.22 | 486718.90 | 2022.65 | 5930.37 | 806.99 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 62140.22 | 427136.63 | 46367.69 | 473504.31 | 486661.88 | 2064.10 | 6061.28 | 634.63 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 77851.07 | 2423041.38 | 23725.14 | 2446766.52 | 3126920.42 | 2190.00 | 5929.00 | 641.00 | 0.00 |
BANQUET_FLR_6 | 41980471.69 | 0.00 | 41980471.69 | 113226.87 | 42093698.56 | 37458366.31 | 0.00 | 4552.55 | 4207.45 | 0.00 |
DINING_FLR_6 | 45264583.75 | 0.00 | 45264583.75 | 113226.87 | 45377810.62 | 37458366.31 | 0.00 | 0.00 | 8760.00 | 0.00 |
KITCHEN_FLR_6 | 57797006.25 | 0.00 | 57797006.25 | 101364.30 | 57898370.55 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12073766.95 | 0.00 | 12073766.95 | 99209.72 | 12172976.67 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 6804296.92 | 0.21E+10 | 4671897.99 | 0.21E+10 | 0.43E+10 | 8760.00 | 8034.62 | 8760.00 | 368.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.2036 | 0.0000 | 1.2036 | 0.0000 | 1.2036 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.2032 | 0.0000 | 0.2032 | 0.0025 | 0.2057 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1208 | 0.0000 | 0.1208 | 0.0010 | 0.1218 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.0973 | 0.0000 | 0.0973 | 0.0023 | 0.0996 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0523 | 0.0000 | 0.0523 | 0.0013 | 0.0536 | 0.0578 | 8756.50 | 1.50 | 2.00 |
LAUNDRY_FLR_1 | 2.0648 | 0.0000 | 2.0648 | 0.0032 | 2.0680 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.8632 | 0.0000 | 0.8632 | 0.0056 | 0.8688 | 0.6764 | 0.00 | 0.00 | 8760.00 |
LOBBY_FLR_1 | 2.6676 | 0.0000 | 2.6676 | 0.0160 | 2.6836 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0020 | 0.0483 | 0.0015 | 0.0498 | 0.0617 | 2190.00 | 5930.00 | 640.00 |
ROOM_2_FLR_3 | 0.0463 | 0.0018 | 0.0481 | 0.0015 | 0.0495 | 0.0617 | 2190.00 | 6026.97 | 543.03 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0021 | 0.6300 | 0.0004 | 0.6304 | 0.8373 | 2190.00 | 5932.08 | 637.92 |
ROOM_5_FLR_3 | 0.0463 | 0.0020 | 0.0483 | 0.0015 | 0.0498 | 0.0617 | 2190.00 | 5930.00 | 640.00 |
ROOM_6_FLR_3 | 0.0463 | 0.0021 | 0.0484 | 0.0015 | 0.0498 | 0.0617 | 2190.00 | 5932.94 | 637.06 |
CORRIDOR_FLR_3 | 0.6845 | 0.0000 | 0.6845 | 0.0018 | 0.6862 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0025 | 0.0140 | 0.0015 | 0.0155 | 0.0154 | 2022.65 | 5930.37 | 806.99 |
ROOM_2_FLR_6 | 0.0116 | 0.0020 | 0.0135 | 0.0015 | 0.0150 | 0.0154 | 2064.10 | 6061.28 | 634.63 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0025 | 0.0768 | 0.0008 | 0.0776 | 0.0992 | 2190.00 | 5929.00 | 641.00 |
BANQUET_FLR_6 | 1.3312 | 0.0000 | 1.3312 | 0.0036 | 1.3348 | 1.1878 | 0.00 | 4552.55 | 4207.45 |
DINING_FLR_6 | 1.4353 | 0.0000 | 1.4353 | 0.0036 | 1.4389 | 1.1878 | 0.00 | 0.00 | 8760.00 |
KITCHEN_FLR_6 | 1.8327 | 0.0000 | 1.8327 | 0.0032 | 1.8359 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3829 | 0.0000 | 0.3829 | 0.0031 | 0.3860 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 64.1521 | 0.2143 | 64.3664 | 0.1170 | 64.4834 | 73.9670 | 8760.00 | 8034.62 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.56E+09 | 0.00 | 0.56E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 41093930.13 | 532066.31 | 41625996.44 | 64690340.46 | 8747.33 | 6.11 | 6.56 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 17.8318 | 0.0000 | 17.8318 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.3031 | 0.0169 | 1.3200 | 2.0513 | 8747.33 | 6.11 | 6.56 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 3755.67 | 0.00 | 0.00 | 0.00 | 5004.33 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 18.2558 | 0.0000 | 0.0000 | 0.0000 | 17.5172 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.6460 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1333 |
Defaulted Fields | 1181 |
Fields with Defaults | 4005 |
Autosized Fields | 349 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 4753.76 | 68926.48 | 16-NOV-03:50 | 380185.47 | 20-JUL-19:50 |
Electricity:Building | 2338.13 | 30667.77 | 10-JUN-05:00 | 138695.41 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 256.48 | 3058.02 | 02-JAN-02:10 | 18903.76 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2331.03 | 30526.62 | 10-JUN-05:00 | 138454.08 | 02-JAN-20:10 |
InteriorLights:Electricity | 602.89 | 5244.45 | 10-JUN-05:00 | 50471.22 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 113.37 | 1030.12 | 02-JAN-02:10 | 9271.23 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 602.89 | 5244.45 | 10-JUN-05:00 | 50471.22 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 602.89 | 5244.45 | 10-JUN-05:00 | 50471.22 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 113.37 | 1030.12 | 02-JAN-02:10 | 9271.23 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 602.89 | 5244.45 | 10-JUN-05:00 | 50471.22 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 16.45 | 201.26 | 02-JAN-02:10 | 1197.92 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 19.05 | 233.06 | 02-JAN-02:10 | 1387.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.46 | 67.94 | 02-JAN-02:10 | 394.77 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.87 | 16.96 | 02-JAN-02:10 | 152.61 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.87 | 16.96 | 02-JAN-02:10 | 152.61 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.84 | 1007.22 | 02-JAN-02:10 | 4973.49 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 27.13 | 302.57 | 03-JUN-05:00 | 2538.73 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 12.79 | 76.92 | 01-JAN-13:10 | 1573.46 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 12.79 | 76.92 | 01-JAN-13:10 | 1573.46 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 271.77 | 3231.92 | 03-JUN-05:00 | 20674.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 122.78 | 1120.51 | 03-JUN-05:00 | 10645.38 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 122.78 | 1120.51 | 03-JUN-05:00 | 10645.38 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 18.46 | 262.96 | 01-JAN-02:10 | 1214.21 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 18.46 | 262.93 | 01-JAN-02:10 | 1214.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 302.44 | 4545.27 | 01-JAN-02:10 | 20822.55 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 73.68 | 623.81 | 01-JAN-02:10 | 5671.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 73.68 | 623.81 | 01-JAN-02:10 | 5671.40 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 302.52 | 4546.52 | 01-JAN-02:10 | 20828.25 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 73.70 | 623.98 | 01-JAN-02:10 | 5672.95 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 73.70 | 623.98 | 01-JAN-02:10 | 5672.95 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 18.46 | 262.96 | 01-JAN-02:10 | 1214.21 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 18.46 | 262.93 | 01-JAN-02:10 | 1214.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.62 | 65.74 | 01-JAN-02:10 | 303.55 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.74 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.74 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.62 | 65.73 | 01-JAN-02:10 | 303.52 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.73 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.73 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 35.82 | 538.40 | 01-JAN-02:10 | 2466.50 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 8.73 | 73.89 | 01-JAN-02:10 | 671.80 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 8.73 | 73.89 | 01-JAN-02:10 | 671.80 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 204.02 | 2449.08 | 10-JUN-05:00 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.16 | 199.78 | 10-JUN-05:00 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.16 | 199.78 | 10-JUN-05:00 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 204.02 | 2449.08 | 10-JUN-05:00 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.16 | 199.78 | 10-JUN-05:00 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.16 | 199.78 | 10-JUN-05:00 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 444.45 | 5944.83 | 02-JAN-02:10 | 18636.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 43.77 | 732.86 | 06-FEB-23:30 | 2789.94 | 17-SEP-10:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 905.08 | 2170.94 | 07-APR-01:20 | 164963.17 | 20-JUL-18:30 |
LowTempRefrigeration:Refrigeration:Electricity | 15.70 | 0.00 | 01-JAN-11:10 | 1306.86 | 16-JUL-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 20.98 | 601.59 | 07-FEB-04:00 | 716.74 | 17-MAY-13:10 |
Fans:Electricity | 521.05 | 12063.79 | 11-DEC-08:10 | 34158.96 | 17-JUL-22:00 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 717.25 | 13042.30 | 05-NOV-05:00 | 44875.15 | 10-AUG-21:10 |
ExteriorEquipment:Electricity | 641.49 | 9451.24 | 02-JAN-02:20 | 39155.93 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 22.46 | 386.39 | 10-JUN-05:00 | 1283.34 | 05-JUN-20:10 |
ElectricityPurchased:Facility | 4753.76 | 68926.48 | 16-NOV-03:50 | 380185.47 | 20-JUL-19:50 |
ElectricityPurchased:Plant | 4753.76 | 68926.48 | 16-NOV-03:50 | 380185.47 | 20-JUL-19:50 |
Cogeneration:ElectricityPurchased | 4753.76 | 68926.48 | 16-NOV-03:50 | 380185.47 | 20-JUL-19:50 |
General:Cogeneration:ElectricityPurchased | 4753.76 | 68926.48 | 16-NOV-03:50 | 380185.47 | 20-JUL-19:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 4753.76 | 68926.48 | 16-NOV-03:50 | 380185.47 | 20-JUL-19:50 |
ElectricityNet:Plant | 4753.76 | 68926.48 | 16-NOV-03:50 | 380185.47 | 20-JUL-19:50 |
Cogeneration:ElectricityNet | 4753.76 | 68926.48 | 16-NOV-03:50 | 380185.47 | 20-JUL-19:50 |
General:Cogeneration:ElectricityNet | 4753.76 | 68926.48 | 16-NOV-03:50 | 380185.47 | 20-JUL-19:50 |
General:Fans:Electricity | 521.05 | 12063.79 | 11-DEC-08:10 | 34158.96 | 17-JUL-22:00 |
ExteriorLights:Electricity | 174.28 | 0.00 | 01-JAN-08:00 | 11096.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 174.28 | 0.00 | 01-JAN-08:00 | 11096.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 173.74 | 0.00 | 11-JAN-11:10 | 9938.94 | 27-JUN-08:20 |
General:HeatRecovery:Electricity | 173.74 | 0.00 | 11-JAN-11:10 | 9938.94 | 27-JUN-08:20 |
WaterSystems:Electricity | 90.75 | 1086.59 | 17-JUN-00:10 | 4738.75 | 11-SEP-18:10 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.59 | 17-JUN-00:10 | 4738.75 | 11-SEP-18:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 677.95 | 0.00 | 01-JAN-00:10 | 153064.00 | 20-JUL-18:20 |
General:Cooling:Electricity | 677.95 | 0.00 | 01-JAN-00:10 | 153064.00 | 20-JUL-18:20 |
Pumps:Electricity | 99.69 | 49.18 | 23-OCT-14:10 | 6827.19 | 21-JUL-20:00 |
General:Pumps:Electricity | 99.69 | 49.18 | 23-OCT-14:10 | 6827.19 | 21-JUL-20:00 |
WIRED_LTG_ELECTRICITY | 21.22 | 0.00 | 01-JAN-00:10 | 1776.59 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 6406.83 | 29270.80 | 16-MAR-01:10 | 630256.95 | 06-FEB-19:10 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 4617.99 | 15908.90 | 23-JUN-10:10 | 542637.17 | 06-FEB-19:10 |
WaterSystems:NaturalGas | 3262.51 | 15908.90 | 02-JAN-16:10 | 297125.46 | 13-FEB-21:50 |
Water Heater:WaterSystems:NaturalGas | 3262.51 | 15908.90 | 02-JAN-16:10 | 297125.46 | 13-FEB-21:50 |
Heating:NaturalGas | 1355.48 | 0.00 | 14-MAR-10:10 | 303857.23 | 06-FEB-09:10 |
Boiler:Heating:NaturalGas | 1355.48 | 0.00 | 14-MAR-10:10 | 303857.23 | 06-FEB-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 2227.68 | 0.00 | 01-JAN-00:10 | 628567.35 | 21-JUL-20:00 |
PlantLoopCoolingDemand:HVAC | 2227.68 | 0.00 | 01-JAN-00:10 | 628567.35 | 21-JUL-20:00 |
CoolingCoils:PlantLoopCoolingDemand | 2227.68 | 0.00 | 01-JAN-00:10 | 628567.35 | 21-JUL-20:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JUN-20:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JUN-20:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JUN-20:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JUN-20:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JUN-20:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JUN-20:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 31-MAY-07:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 31-MAY-07:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 19178.66 | 130545.60 | 10-NOV-11:10 | 2534618.30 | 20-JUL-21:00 |
EnergyTransfer:Building | 4687.78 | 78763.90 | 25-JAN-11:10 | 319117.62 | 18-JUL-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 680.90 | 9516.49 | 07-FEB-04:00 | 35102.76 | 16-JUL-10:40 |
Refrigeration:EnergyTransfer | 181.97 | 3988.40 | 07-FEB-04:00 | 10371.81 | 25-AUG-06:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.98 | 1994.20 | 07-FEB-04:00 | 5185.91 | 25-AUG-06:30 |
General:Refrigeration:EnergyTransfer | 90.98 | 1994.20 | 07-FEB-04:00 | 5185.91 | 25-AUG-06:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.98 | 1994.20 | 07-FEB-04:00 | 5185.91 | 25-AUG-06:30 |
EnergyTransfer:Plant | 7165.97 | 18646.95 | 21-OCT-01:20 | 1435217.05 | 21-JUL-20:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.58 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.41 | 1756.07 | 07-FEB-04:00 | 2559.87 | 17-MAY-13:10 |
EnergyTransfer:Zone:BASEMENT | 345.61 | 8207.11 | 08-MAY-14:00 | 18483.60 | 13-OCT-21:00 |
Heating:EnergyTransfer | 213.73 | 0.00 | 11-JAN-18:10 | 92456.99 | 06-FEB-09:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 213.73 | 0.00 | 11-JAN-18:10 | 92456.99 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4383.06 | 63622.39 | 06-FEB-11:10 | 316413.00 | 18-JUL-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 345.61 | 8207.11 | 08-MAY-14:00 | 18483.60 | 13-OCT-21:00 |
General:Cooling:EnergyTransfer | 4383.06 | 63622.39 | 06-FEB-11:10 | 316413.00 | 18-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 345.61 | 8207.11 | 08-MAY-14:00 | 18483.60 | 13-OCT-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 35.87 | 0.14 | 27-MAR-02:30 | 4131.44 | 21-SEP-13:00 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 2.04 | 0.00 | 01-JAN-20:50 | 1555.02 | 07-FEB-07:20 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 2.04 | 0.00 | 01-JAN-20:50 | 1555.02 | 07-FEB-07:20 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 33.82 | 0.00 | 01-JAN-00:10 | 4131.44 | 21-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 33.82 | 0.00 | 01-JAN-00:10 | 4131.44 | 21-SEP-13:00 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 31.69 | 121.63 | 06-FEB-13:00 | 1925.47 | 10-AUG-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 31.69 | 121.63 | 06-FEB-13:00 | 1925.47 | 10-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 31.69 | 121.63 | 06-FEB-13:00 | 1925.47 | 10-AUG-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 20.58 | 0.04 | 08-JAN-03:30 | 1656.08 | 21-JUL-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.53 | 0.00 | 01-JAN-00:10 | 632.28 | 07-FEB-11:00 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.53 | 0.00 | 01-JAN-00:10 | 632.28 | 07-FEB-11:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 20.05 | 0.00 | 01-JAN-13:10 | 1656.08 | 21-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 20.05 | 0.00 | 01-JAN-13:10 | 1656.08 | 21-JUL-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 10.59 | 0.00 | 04-DEC-02:40 | 683.50 | 21-JUL-21:00 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.99 | 0.00 | 01-JAN-20:00 | 538.25 | 07-FEB-11:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.99 | 0.00 | 01-JAN-20:00 | 538.25 | 07-FEB-11:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 9.60 | 0.00 | 01-JAN-00:10 | 683.50 | 21-JUL-21:00 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 9.60 | 0.00 | 01-JAN-00:10 | 683.50 | 21-JUL-21:00 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 591.96 | 8869.58 | 07-FEB-05:00 | 38711.16 | 21-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 591.96 | 8869.58 | 07-FEB-05:00 | 38711.16 | 21-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 591.96 | 8869.58 | 07-FEB-05:00 | 38711.16 | 21-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 218.52 | 8.38 | 13-FEB-09:40 | 14367.80 | 11-OCT-12:30 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 1183.43 | 06-FEB-09:20 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 1183.43 | 06-FEB-09:20 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 218.51 | 0.00 | 06-FEB-09:10 | 14367.80 | 11-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 218.51 | 0.00 | 06-FEB-09:10 | 14367.80 | 11-OCT-12:30 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 749.32 | 6567.92 | 06-FEB-13:30 | 40459.29 | 20-JUL-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 749.32 | 6567.92 | 06-FEB-13:30 | 40459.29 | 20-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 749.32 | 6567.92 | 06-FEB-13:30 | 40459.29 | 20-JUL-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 62.55 | 0.00 | 01-JAN-08:10 | 11192.84 | 21-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 22.62 | 0.00 | 01-JAN-08:10 | 6799.61 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 22.62 | 0.00 | 01-JAN-08:10 | 6799.61 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 39.93 | 0.00 | 01-JAN-00:10 | 11192.84 | 21-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 39.93 | 0.00 | 01-JAN-00:10 | 11192.84 | 21-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 55.65 | 0.00 | 01-JAN-08:10 | 11350.17 | 08-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 26.76 | 0.00 | 01-JAN-08:10 | 6927.78 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 26.76 | 0.00 | 01-JAN-08:10 | 6927.78 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 28.89 | 0.00 | 01-JAN-00:10 | 11350.17 | 08-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 28.89 | 0.00 | 01-JAN-00:10 | 11350.17 | 08-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 222.98 | 0.00 | 01-JAN-07:10 | 54046.80 | 11-OCT-12:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 4.79 | 0.00 | 01-JAN-07:10 | 19648.56 | 07-FEB-05:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 4.79 | 0.00 | 01-JAN-07:10 | 19648.56 | 07-FEB-05:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 218.19 | 0.00 | 01-JAN-00:10 | 54046.80 | 11-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 218.19 | 0.00 | 01-JAN-00:10 | 54046.80 | 11-OCT-12:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 342.91 | 0.00 | 01-JAN-08:10 | 65136.80 | 27-JUL-15:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 56.23 | 0.00 | 01-JAN-08:10 | 44023.58 | 06-FEB-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 56.23 | 0.00 | 01-JAN-08:10 | 44023.58 | 06-FEB-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 286.68 | 0.00 | 01-JAN-00:10 | 65136.80 | 27-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 286.68 | 0.00 | 01-JAN-00:10 | 65136.80 | 27-JUL-15:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 61.96 | 0.00 | 01-JAN-08:10 | 10033.00 | 05-AUG-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 22.26 | 0.00 | 01-JAN-08:10 | 6795.80 | 06-FEB-19:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 22.26 | 0.00 | 01-JAN-08:10 | 6795.80 | 06-FEB-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 39.70 | 0.00 | 01-JAN-00:10 | 10033.00 | 05-AUG-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 39.70 | 0.00 | 01-JAN-00:10 | 10033.00 | 05-AUG-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 55.51 | 0.00 | 01-JAN-08:10 | 10885.36 | 05-AUG-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 26.26 | 0.00 | 01-JAN-08:10 | 7138.46 | 06-FEB-19:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 26.26 | 0.00 | 01-JAN-08:10 | 7138.46 | 06-FEB-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 29.25 | 0.00 | 01-JAN-00:10 | 10885.36 | 05-AUG-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 29.25 | 0.00 | 01-JAN-00:10 | 10885.36 | 05-AUG-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 134.85 | 0.08 | 24-FEB-12:40 | 8849.81 | 21-JUL-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 4.61 | 0.00 | 01-JAN-00:10 | 5157.97 | 06-FEB-09:20 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 4.61 | 0.00 | 01-JAN-00:10 | 5157.97 | 06-FEB-09:20 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 130.23 | 0.00 | 01-JAN-08:10 | 8849.81 | 21-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 130.23 | 0.00 | 01-JAN-08:10 | 8849.81 | 21-JUL-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 18.42 | 0.00 | 01-JAN-08:10 | 2983.06 | 21-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 8.66 | 0.00 | 01-JAN-08:10 | 2189.84 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 8.66 | 0.00 | 01-JAN-08:10 | 2189.84 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 9.76 | 0.00 | 01-JAN-00:10 | 2983.06 | 21-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 9.76 | 0.00 | 01-JAN-00:10 | 2983.06 | 21-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 17.16 | 0.00 | 01-JAN-08:10 | 3021.31 | 10-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.98 | 0.00 | 01-JAN-08:10 | 2220.50 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.98 | 0.00 | 01-JAN-08:10 | 2220.50 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.18 | 0.00 | 01-JAN-00:10 | 3021.31 | 10-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.18 | 0.00 | 01-JAN-00:10 | 3021.31 | 10-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 84.46 | 0.00 | 01-JAN-08:10 | 15244.19 | 21-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 24.01 | 0.00 | 01-JAN-08:10 | 9169.23 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 24.01 | 0.00 | 01-JAN-08:10 | 9169.23 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 60.45 | 0.00 | 01-JAN-00:10 | 15244.19 | 21-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 60.45 | 0.00 | 01-JAN-00:10 | 15244.19 | 21-SEP-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 416.19 | 7584.87 | 06-FEB-15:00 | 22783.89 | 20-JUL-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 416.19 | 7584.87 | 06-FEB-15:00 | 22783.89 | 20-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 416.19 | 7584.87 | 06-FEB-15:00 | 22783.89 | 20-JUL-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 456.14 | 8596.67 | 06-FEB-15:00 | 24012.47 | 20-JUL-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 456.14 | 8596.67 | 06-FEB-15:00 | 24012.47 | 20-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 456.14 | 8596.67 | 06-FEB-15:00 | 24012.47 | 20-JUL-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 589.91 | 7522.29 | 07-FEB-04:00 | 30013.84 | 16-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 589.91 | 7522.29 | 07-FEB-04:00 | 30013.84 | 16-JUL-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 73.96 | 0.02 | 30-DEC-24:00 | 6012.15 | 21-JUL-13:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 3.98 | 0.00 | 01-JAN-00:10 | 3418.01 | 07-FEB-07:20 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 3.98 | 0.00 | 01-JAN-00:10 | 3418.01 | 07-FEB-07:20 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 69.98 | 0.00 | 01-JAN-00:50 | 6012.15 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 69.98 | 0.00 | 01-JAN-00:50 | 6012.15 | 21-JUL-13:30 |
PlantLoopHeatingDemand:Facility | 1785.32 | 9470.18 | 17-AUG-01:30 | 281126.22 | 06-FEB-09:10 |
PlantLoopHeatingDemand:Plant | 802.94 | 9470.18 | 17-AUG-01:30 | 59827.19 | 13-FEB-08:00 |
WaterSystems:PlantLoopHeatingDemand | 802.94 | 9470.18 | 17-AUG-01:30 | 59827.19 | 13-FEB-08:00 |
General:WaterSystems:PlantLoopHeatingDemand | 802.94 | 9470.18 | 17-AUG-01:30 | 59827.19 | 13-FEB-08:00 |
EnergyTransfer:HVAC | 7324.91 | 2154.04 | 12-MAR-17:40 | 847908.65 | 20-JUL-21:00 |
HeatingCoils:EnergyTransfer | 982.38 | 0.00 | 14-MAR-10:10 | 246788.75 | 06-FEB-09:10 |
PlantLoopHeatingDemand:HVAC | 982.38 | 0.00 | 14-MAR-10:10 | 246788.75 | 06-FEB-09:10 |
HeatingCoils:PlantLoopHeatingDemand | 982.38 | 0.00 | 14-MAR-10:10 | 246788.75 | 06-FEB-09:10 |
CoolingCoils:EnergyTransfer | 2227.68 | 0.00 | 01-JAN-00:10 | 628567.35 | 21-JUL-20:00 |
HeatRecoveryForHeating:EnergyTransfer | 3964.11 | 0.00 | 11-JAN-11:10 | 521389.94 | 11-DEC-06:00 |
HeatRecoveryForCooling:EnergyTransfer | 150.75 | 0.00 | 01-JAN-00:10 | 249302.83 | 21-JUL-02:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 802.94 | 9470.18 | 17-AUG-01:30 | 59827.19 | 13-FEB-08:00 |
WaterUse:WaterSystems:EnergyTransfer | 802.94 | 9470.18 | 17-AUG-01:30 | 59827.19 | 13-FEB-08:00 |
Boilers:EnergyTransfer | 972.85 | 0.00 | 14-MAR-10:10 | 248819.81 | 06-FEB-09:10 |
Chillers:EnergyTransfer | 2310.63 | 0.00 | 01-JAN-00:10 | 629198.02 | 21-JUL-20:00 |
HeatRejection:EnergyTransfer | 2988.58 | 0.00 | 01-JAN-00:10 | 774983.83 | 21-JUL-20:00 |
General:HeatRejection:EnergyTransfer | 2988.58 | 0.00 | 01-JAN-00:10 | 774983.83 | 21-JUL-20:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -345.615 | 0.000 | 0.000 | 142.210 | 113.371 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -53.071 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 2.042 | -33.824 | 0.000 | 0.000 | 15.718 | 6.265 | 10.186 | 20.911 | 0.000 | 0.018 | 0.000 | 0.000 | -11.657 | 0.000 | -1.253 | -8.405 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -31.693 | 0.000 | 0.000 | 17.194 | 7.255 | 11.795 | 0.000 | 0.000 | 0.007 | 0.000 | 0.000 | 0.000 | 0.000 | -0.512 | -4.046 |
MECH_FLR_1 | 0.000 | 0.000 | 0.531 | -20.052 | 0.000 | 0.000 | 3.748 | 8.366 | 12.471 | 0.000 | 0.000 | 0.016 | 0.000 | 0.000 | 0.000 | 0.000 | -1.172 | -3.908 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.988 | -9.605 | 0.000 | 0.000 | 2.906 | 1.866 | 3.598 | 0.000 | 0.000 | 0.010 | 0.907 | 0.000 | 0.000 | 0.000 | -0.670 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -591.964 | 0.000 | 0.000 | 11.372 | 4.900 | 658.131 | 0.000 | 0.000 | 0.029 | 0.000 | 0.000 | 0.000 | 0.000 | -1.709 | -80.759 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.011 | -218.510 | 0.000 | 0.000 | 195.975 | 12.794 | 14.341 | 58.035 | 0.000 | 0.038 | 0.000 | 0.000 | -34.516 | 0.000 | -2.917 | -25.251 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -749.321 | 0.000 | 0.000 | 564.290 | 122.775 | 148.998 | 76.468 | 0.000 | 0.110 | 0.000 | 0.000 | -47.320 | 0.000 | -8.603 | -107.398 |
ROOM_1_FLR_3 | 27.183 | -33.664 | 0.000 | -10.825 | 0.000 | 0.000 | 9.744 | 6.171 | 12.292 | 41.077 | 0.000 | 0.180 | 0.000 | 0.000 | -26.870 | 0.000 | -3.559 | -21.729 |
ROOM_2_FLR_3 | 31.599 | -22.361 | 0.000 | -11.363 | 0.000 | 0.000 | 9.605 | 6.170 | 12.291 | 29.834 | 0.000 | 0.075 | 0.000 | 0.000 | -28.076 | 0.000 | -3.934 | -23.839 |
ROOM_3_MULT19_FLR_3 | 4.790 | -205.577 | 0.003 | -12.610 | 0.000 | 0.000 | 0.000 | 73.685 | 228.754 | 233.145 | 0.000 | 0.037 | 0.001 | 0.000 | -168.389 | 0.000 | -18.371 | -135.467 |
ROOM_4_MULT19_FLR_3 | 99.238 | -178.121 | 0.000 | -151.559 | 0.000 | 0.000 | 183.182 | 73.705 | 228.817 | 79.045 | 0.000 | 0.790 | 0.000 | 0.000 | -158.566 | 0.000 | -33.537 | -142.993 |
ROOM_5_FLR_3 | 26.773 | -33.381 | 0.000 | -10.833 | 0.000 | 0.000 | 9.737 | 6.171 | 12.292 | 40.946 | 0.000 | 0.180 | 0.000 | 0.000 | -26.413 | 0.000 | -3.569 | -21.903 |
ROOM_6_FLR_3 | 31.065 | -22.762 | 0.000 | -11.286 | 0.000 | 0.000 | 9.635 | 6.170 | 12.291 | 29.520 | 0.000 | 0.076 | 0.000 | 0.000 | -27.326 | 0.000 | -4.018 | -23.365 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 4.613 | -130.234 | 0.000 | 0.000 | 119.385 | 56.739 | 0.000 | 36.350 | 0.000 | 0.048 | 0.000 | 0.000 | -34.855 | 0.000 | -3.586 | -48.461 |
ROOM_1_FLR_6 | 9.915 | -8.318 | 0.000 | -2.703 | 0.000 | 0.000 | 2.440 | 1.543 | 3.073 | 10.207 | 0.000 | 0.050 | 0.000 | 0.000 | -6.685 | 0.000 | -0.923 | -8.599 |
ROOM_2_FLR_6 | 11.282 | -5.640 | 0.000 | -2.847 | 0.000 | 0.000 | 2.401 | 1.543 | 3.073 | 7.407 | 0.000 | 0.020 | 0.000 | 0.000 | -7.000 | 0.000 | -1.006 | -9.231 |
ROOM_3_MULT9_FLR_6 | 30.390 | -49.353 | 0.000 | -17.483 | 0.000 | 0.000 | 21.862 | 8.728 | 27.097 | 53.854 | 0.000 | 0.379 | 0.000 | 0.000 | -31.274 | 0.000 | -5.192 | -39.007 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -416.190 | 0.000 | 0.000 | 319.000 | 28.164 | 175.857 | 8.075 | 0.000 | 0.018 | 0.000 | 0.000 | -21.182 | 0.000 | -2.044 | -91.700 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -456.141 | 0.000 | 0.000 | 317.051 | 28.164 | 175.857 | 7.864 | 0.000 | 0.018 | 0.000 | 0.000 | -21.807 | 0.000 | -2.064 | -48.944 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -589.898 | 0.000 | 0.000 | 28.687 | 13.339 | 540.650 | 19.761 | 0.000 | 0.016 | 3.350 | 0.000 | -14.057 | 0.000 | -1.848 | -0.001 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 3.981 | -69.982 | 0.000 | 0.000 | 31.695 | 15.012 | 0.000 | 17.627 | 0.000 | 0.018 | 18.882 | 0.000 | -15.646 | 0.000 | -1.588 | -0.001 |
Total Facility | 272.234 | -559.177 | 12.169 | -3894.536 | 0.000 | 0.000 | 2017.837 | 602.894 | 2434.967 | 770.128 | 0.000 | 2.134 | 23.139 | 0.000 | -681.638 | 0.000 | -102.074 | -898.078 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 13-OCT-21:00 | 0.00 | 0.00 | 0.00 | -18482.40 | 0.00 | 0.00 | 5924.50 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4808.77 |
RETAIL_1_FLR_1 | 21-SEP-13:00 | 0.00 | 0.00 | 0.00 | -4131.21 | 0.00 | 0.00 | 150.60 | 142.31 | 252.59 | 5932.38 | 0.00 | 2.86 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2349.54 |
RETAIL_2_FLR_1 | 10-AUG-21:00 | 0.00 | 0.00 | 0.00 | -1925.53 | 0.00 | 0.00 | 697.61 | 527.34 | 752.15 | 0.00 | 0.00 | 2.30 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -53.86 |
MECH_FLR_1 | 21-JUL-20:00 | 0.00 | 0.00 | 0.00 | -1656.11 | 0.00 | 0.00 | 129.08 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 5.25 | 0.00 | -0.00 | 0.00 | -1.84 | 0.00 |
STORAGE_FLR_1 | 21-JUL-21:00 | 0.00 | 0.00 | 0.00 | -683.53 | 0.00 | 0.00 | 113.48 | 135.66 | 229.41 | 0.00 | 0.00 | 0.00 | 206.80 | 0.00 | -0.00 | 0.00 | -1.82 | 0.00 |
LAUNDRY_FLR_1 | 21-JUL-20:00 | 0.00 | 0.00 | 0.00 | -38713.98 | 0.00 | 0.00 | 408.75 | 400.68 | 44299.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2.53 | -6392.31 |
CAFE_FLR_1 | 11-OCT-12:30 | 0.00 | 0.00 | 0.00 | -14369.66 | 0.00 | 0.00 | 1979.02 | 96.16 | 355.63 | 19039.17 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -13.10 | -7087.21 |
LOBBY_FLR_1 | 20-JUL-21:10 | 0.00 | 0.00 | 0.00 | -40466.38 | 0.00 | 0.00 | 26439.85 | 7096.92 | 7389.94 | 108.85 | 0.00 | 27.04 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -596.21 |
ROOM_1_FLR_3 | 18-JUL-18:02 | 0.00 | -12153.96 | 0.00 | -737.06 | 0.00 | 0.00 | 335.50 | 422.72 | 516.26 | 7504.69 | 0.00 | 24.55 | 4087.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 14-JUN-20:11 | 0.00 | -12527.33 | 0.00 | -678.49 | 0.00 | 0.00 | 336.77 | 422.67 | 737.43 | 0.00 | 0.00 | 0.00 | 13009.94 | 0.00 | -1229.58 | 0.00 | -71.41 | 0.00 |
ROOM_3_MULT19_FLR_3 | 11-OCT-12:30 | 0.00 | -54047.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1587.99 | 5097.90 | 79941.25 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -169.29 | -32410.55 |
ROOM_4_MULT19_FLR_3 | 09-AUG-15:02 | 0.00 | -63042.77 | 0.00 | -10157.04 | 0.00 | 0.00 | 4470.40 | 1588.43 | 5099.29 | 17884.59 | 0.00 | 223.64 | 43933.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 21-JUL-18:02 | 0.00 | -10898.92 | 0.00 | -723.30 | 0.00 | 0.00 | 335.50 | 422.72 | 516.26 | 1033.12 | 0.00 | 39.31 | 9275.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 05-AUG-08:32 | 0.00 | -12430.17 | 0.00 | -1031.99 | 0.00 | 0.00 | 90.35 | 265.95 | 653.15 | 9569.10 | 0.00 | 0.00 | 2906.68 | 0.00 | -0.00 | 0.00 | -23.07 | 0.00 |
CORRIDOR_FLR_3 | 21-JUL-10:35 | 0.00 | 0.00 | 0.00 | -8860.46 | 0.00 | 0.00 | 1197.72 | 1288.89 | 0.00 | 6044.68 | 0.00 | 42.86 | 286.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 10-AUG-18:02 | 0.00 | -3190.25 | 0.00 | -183.18 | 0.00 | 0.00 | 83.87 | 105.68 | 129.07 | 1199.38 | 0.00 | 6.80 | 1848.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 14-JUN-20:11 | 0.00 | -3345.06 | 0.00 | -176.41 | 0.00 | 0.00 | 81.13 | 105.67 | 184.36 | 0.00 | 0.00 | 0.00 | 3492.84 | 0.00 | -323.92 | 0.00 | -18.60 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10-AUG-15:02 | 0.00 | -14980.27 | 0.00 | -1190.99 | 0.00 | 0.00 | 529.38 | 188.10 | 603.86 | 6426.28 | 0.00 | 52.36 | 8371.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 20-JUL-21:20 | 0.00 | 0.00 | 0.00 | -22789.13 | 0.00 | 0.00 | 15638.25 | 1842.08 | 6747.90 | 58.57 | 0.00 | 5.26 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1502.92 |
DINING_FLR_6 | 20-JUL-21:20 | 0.00 | 0.00 | 0.00 | -24018.10 | 0.00 | 0.00 | 15629.40 | 1842.08 | 6747.90 | 46.12 | 0.00 | 5.25 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -252.66 |
KITCHEN_FLR_6 | 16-JUL-10:40 | 0.00 | 0.00 | 0.00 | -29996.73 | 0.00 | 0.00 | 464.23 | 363.61 | 23951.61 | 3893.45 | 0.00 | 15.67 | 1308.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 21-JUL-13:30 | 0.00 | 0.00 | 0.00 | -6012.84 | 0.00 | 0.00 | 308.45 | 341.02 | 0.00 | 3182.34 | 0.00 | 24.50 | 2156.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 09-AUG-18:02 | 0.00 | -153206.80 | 0.00 | -193912.66 | 0.00 | 0.00 | 74961.65 | 40659.92 | 121562.63 | 34665.37 | 0.00 | 783.85 | 74486.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 07-FEB-07:15 | 0.00 | 0.00 | 1555.01 | 0.00 | 0.00 | 0.00 | 358.01 | 284.62 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1538.23 | 0.00 | -125.01 | -967.42 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 07-FEB-11:03 | 0.00 | 0.00 | 643.18 | 0.00 | 0.00 | 0.00 | 43.84 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -102.32 | -1084.02 |
STORAGE_FLR_1 | 07-FEB-11:03 | 0.00 | 0.00 | 538.23 | 0.00 | 0.00 | 0.00 | 33.72 | 42.39 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -59.03 | -644.53 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 06-FEB-09:03 | 0.00 | 0.00 | 1185.87 | 0.00 | 0.00 | 0.00 | 2351.72 | 153.85 | 508.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3062.71 | 0.00 | -263.79 | -872.97 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 11-DEC-09:01 | 10569.82 | 296.77 | 0.00 | -296.77 | 0.00 | 0.00 | 108.88 | 208.98 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1992.54 | 0.00 | -257.98 | -9090.21 |
ROOM_2_FLR_3 | 07-FEB-09:01 | 10555.76 | 293.04 | 0.00 | -293.04 | 0.00 | 0.00 | 108.88 | 208.96 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1979.30 | 0.00 | -269.74 | -9077.55 |
ROOM_3_MULT19_FLR_3 | 07-FEB-05:00 | 19648.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 623.81 | 3921.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16636.45 | 0.00 | -1283.41 | -6273.91 |
ROOM_4_MULT19_FLR_3 | 06-FEB-16:01 | 58500.20 | 3734.42 | 0.00 | -3734.42 | 0.00 | 0.00 | 5585.69 | 1588.43 | 5099.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -13215.79 | 0.00 | -1328.89 | -56228.92 |
ROOM_5_FLR_3 | 11-DEC-09:01 | 10312.00 | 296.96 | 0.00 | -296.96 | 0.00 | 0.00 | 108.88 | 208.98 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1614.57 | 0.00 | -258.00 | -9210.35 |
ROOM_6_FLR_3 | 06-FEB-16:01 | 10326.90 | 291.04 | 0.00 | -291.04 | 0.00 | 0.00 | 293.99 | 132.97 | 273.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2350.98 | 0.00 | -252.18 | -8424.60 |
CORRIDOR_FLR_3 | 06-FEB-09:15 | 0.00 | 0.00 | 5185.43 | 0.00 | 0.00 | 0.00 | 1385.78 | 2062.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3285.55 | 0.00 | -335.42 | -5012.46 |
ROOM_1_FLR_6 | 11-DEC-09:01 | 3163.02 | 74.95 | 0.00 | -74.95 | 0.00 | 0.00 | 27.22 | 52.25 | 113.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -499.20 | 0.00 | -64.70 | -2791.85 |
ROOM_2_FLR_6 | 07-FEB-09:01 | 3152.30 | 73.95 | 0.00 | -73.95 | 0.00 | 0.00 | 27.22 | 52.24 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -498.38 | 0.00 | -67.64 | -2779.00 |
ROOM_3_MULT9_FLR_6 | 11-DEC-09:01 | 14896.30 | 484.00 | 0.00 | -484.00 | 0.00 | 0.00 | 244.99 | 295.59 | 998.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1898.02 | 0.00 | -298.13 | -14239.43 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 07-FEB-07:15 | 0.00 | 0.00 | 3426.83 | 0.00 | 0.00 | 0.00 | 733.28 | 682.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2053.11 | 0.00 | -155.70 | -2633.34 |
Total Facility | 06-FEB-09:02 | 57031.74 | 77411.28 | 11305.33 | -77411.28 | 0.00 | 0.00 | 24028.24 | 20415.33 | 87870.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -58583.34 | 0.00 | -6701.57 | -135366.37 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 21.3237 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 21.2105 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6641 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6641 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1710 | 2.1710 | 1.1875 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3691 | 0.3691 | 0.2019 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2191 | 0.2191 | 0.1199 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1776 | 0.1776 | 0.0972 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0955 | 0.0955 | 0.0523 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3300 | 3.3300 | 1.8215 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5679 | 1.5679 | 0.8577 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7956 | 4.7956 | 2.6232 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2513 | 1.2513 | 0.6845 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1571 | 2.1571 | 1.1799 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2652 | 2.2652 | 1.2391 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2255 | 2.2255 | 1.2173 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6988 | 0.6988 | 0.3822 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 21.3237 | 21.2105 | 21.3237 | 11.6641 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1875 | 1.1875 | 1.1875 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2019 | 0.2019 | 0.2019 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1199 | 0.1199 | 0.1199 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0972 | 0.0972 | 0.0972 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0523 | 0.0523 | 0.0523 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8215 | 1.8215 | 1.8215 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8577 | 0.8577 | 0.8577 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6232 | 2.6232 | 2.6232 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6845 | 0.6845 | 0.6845 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1799 | 1.1799 | 1.1799 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2391 | 1.2391 | 1.2391 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2173 | 1.2173 | 1.2173 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3822 | 0.3822 | 0.3822 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6641 | 11.6641 | 11.6641 | 11.6641 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 1.17 |
Number of hours cooling loads not met | 80.33 |
Number of hours not met | 81.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1355.48 | 303857.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 677.95 | 153064.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 602.89 | 50471.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 174.28 | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 952.41 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 22.46 | 1283.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 521.05 | 34158.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 99.69 | 6827.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 173.74 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4738.75 | 3262.51 | 297125.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.70 | 1306.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 20.98 | 716.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1771.91 | 4753.76 |
Natural Gas | 1788.84 | 6406.83 |
Additional | 0.00 | 0.00 |
Total | 3560.75 | 11160.59 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 53.14 |
Space Heating | 0.00 |
Space Cooling | 59.76 |
Fans (All) | 45.93 |
Service Water Heating | 8.00 |
Receptacle Equipment | 152.32 |
Miscellaneous (All) | 419.01 |
Subtotal | 419.01 |
Natural Gas [MJ/m2] | |
Space Heating | 119.48 |
Service Water Heating | 287.57 |
Miscellaneous (All) | 564.71 |
Subtotal | 564.71 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.40 |
Space Heating | 12.15 |
Space Cooling | 6.07 |
Fans (All) | 4.67 |
Service Water Heating | 30.05 |
Receptacle Equipment | 31.51 |
Miscellaneous | 10.15 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2398. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 2482. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8700.50 | 59.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7893.33 | 866.67 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8736.83 | 23.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8664.33 | 95.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7893.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 866.67 | 0.00 | 0.00 | 0.00 |
Average | 8712.50 | 47.50 | 0.00 | 0.00 | 0.00 |
Sum | 191675.00 | 1045.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4136.67 | 17.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4117.83 | 36.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 36.17 | 0.00 | 0.00 | 0.00 |
Average | 288884.61 | 2.43 | 0.00 | 0.00 | 0.00 |
Sum | 6355461.50 | 53.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8712.83 | 47.17 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8301.17 | 458.83 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8271.50 | 488.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8549.83 | 210.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7442.67 | 1317.33 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8682.00 | 78.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8586.00 | 174.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8497.17 | 262.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8193.67 | 566.33 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8262.83 | 497.17 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8688.00 | 72.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7442.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1317.33 | 0.00 | 0.00 | 0.00 |
Average | 8569.63 | 190.37 | 0.00 | 0.00 | 0.00 |
Sum | 188531.83 | 4188.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 58645.17 | 510.83 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 653482.50 | 56934.50 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1942408.67 | 173020.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4058.33 | 95.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4117.33 | 36.67 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4097.50 | 56.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100197.67 | 160.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4025.00 | 129.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1129739.67 | 115975.33 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1142424.67 | 103290.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 107665.33 | 603.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1942408.67 | 173020.33 | 0.00 | 0.00 | 0.00 |
Average | 268395.54 | 20491.51 | 0.00 | 0.00 | 0.00 |
Sum | 5904701.83 | 450813.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:01:52
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.281874E+11 | 12316.43 | 11-JAN-21:00 | 2.20 | -0.8 | 0.756698E+10 | 4703.66 | 13-JAN-22:10 | 2.80 | -2.1 |
February | 0.245357E+11 | 12050.61 | 01-FEB-21:00 | 0.60 | 0.37 | 0.666133E+10 | 4637.37 | 01-FEB-22:10 | 0.60 | 0.17 |
March | 0.252422E+11 | 11709.42 | 15-MAR-18:10 | 23.43 | 15.50 | 0.696814E+10 | 4479.70 | 01-MAR-22:10 | 23.43 | 15.50 |
April | 0.241043E+11 | 11688.06 | 22-APR-10:33 | 11.33 | 5.08 | 0.659314E+10 | 4219.68 | 28-APR-22:10 | 8.30 | 7.47 |
May | 0.251178E+11 | 11896.32 | 27-MAY-10:33 | 19.43 | 12.21 | 0.676005E+10 | 4194.02 | 19-MAY-22:10 | 19.43 | 12.21 |
June | 0.268883E+11 | 12999.20 | 18-JUN-10:33 | 25.40 | 21.05 | 0.691232E+10 | 4438.95 | 15-JUN-22:10 | 25.40 | 21.05 |
July | 0.297938E+11 | 13921.36 | 16-JUL-10:33 | 28.50 | 22.06 | 0.741549E+10 | 4634.57 | 28-JUL-22:10 | 21.10 | 19.56 |
August | 0.318194E+11 | 14573.72 | 19-AUG-10:33 | 22.93 | 15.19 | 0.787553E+10 | 4837.10 | 22-AUG-22:10 | 16.42 | 12.93 |
September | 0.324129E+11 | 17040.56 | 22-SEP-21:00 | 16.10 | 11.97 | 0.784185E+10 | 4837.18 | 07-SEP-21:00 | 16.10 | 11.97 |
October | 0.343816E+11 | 18483.60 | 13-OCT-21:00 | 8.90 | 6.98 | 0.817596E+10 | 4837.34 | 25-OCT-21:10 | 13.12 | 11.98 |
November | 0.322733E+11 | 18178.10 | 01-NOV-21:00 | 4.40 | 3.43 | 0.788542E+10 | 4837.08 | 08-NOV-00:20 | 5.00 | 4.00 |
December | 0.308565E+11 | 16431.58 | 01-DEC-22:00 | 6.10 | 3.26 | 0.799520E+10 | 4837.09 | 01-DEC-01:10 | 6.10 | 3.26 |
Annual Sum or Average | 0.345613E+12 | 0.886514E+11 | ||||||||
Minimum of Months | 0.241043E+11 | 11688.06 | 0.60 | -0.8 | 0.659314E+10 | 4194.02 | 0.60 | -2.1 | ||
Maximum of Months | 0.343816E+11 | 18483.60 | 28.50 | 22.06 | 0.817596E+10 | 4837.34 | 25.40 | 21.05 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.533108E+09 | 1962.90 | 15-JAN-13:50 | 4.90 | 2.20 | 0.621197E+09 | 364.19 | 02-JAN-04:00 | 4.90 | 2.20 |
February | 0.549799E+09 | 1983.10 | 28-FEB-13:40 | 0.00 | -2.9 | 0.561923E+09 | 364.16 | 07-FEB-03:49 | 0.00 | -2.9 |
March | 0.210824E+10 | 2844.54 | 15-MAR-13:30 | 25.55 | 15.84 | 0.634112E+09 | 432.11 | 15-MAR-21:30 | 17.80 | 13.45 |
April | 0.266117E+10 | 2353.61 | 22-APR-13:10 | 14.60 | 6.58 | 0.615267E+09 | 402.66 | 07-APR-21:30 | 14.60 | 6.58 |
May | 0.373581E+10 | 2178.52 | 27-MAY-10:50 | 19.72 | 12.27 | 0.650478E+09 | 427.63 | 23-MAY-21:40 | 19.72 | 12.27 |
June | 0.441660E+10 | 2435.88 | 27-JUN-13:20 | 29.47 | 23.48 | 0.674744E+09 | 461.73 | 27-JUN-21:30 | 21.95 | 20.56 |
July | 0.504268E+10 | 3028.85 | 21-JUL-13:30 | 31.15 | 21.91 | 0.731601E+09 | 477.93 | 19-JUL-21:30 | 31.15 | 21.91 |
August | 0.505039E+10 | 3365.74 | 18-AUG-13:30 | 29.70 | 20.75 | 0.730198E+09 | 482.37 | 10-AUG-21:30 | 29.70 | 20.75 |
September | 0.439776E+10 | 4131.44 | 21-SEP-13:00 | 25.00 | 16.50 | 0.666435E+09 | 470.69 | 21-SEP-21:30 | 17.75 | 15.84 |
October | 0.312707E+10 | 4031.29 | 11-OCT-12:30 | 21.95 | 13.79 | 0.644141E+09 | 450.01 | 11-OCT-21:40 | 15.60 | 10.74 |
November | 0.173724E+10 | 2391.26 | 03-NOV-12:30 | 8.35 | 4.56 | 0.604940E+09 | 382.76 | 01-NOV-00:10 | 8.35 | 4.56 |
December | 0.464326E+09 | 2107.58 | 17-DEC-11:35 | 1.50 | -0.3 | 0.621462E+09 | 364.16 | 08-DEC-03:20 | 1.50 | -0.3 |
Annual Sum or Average | 0.338242E+11 | 0.775650E+10 | ||||||||
Minimum of Months | 0.464326E+09 | 1962.90 | 0.00 | -2.9 | 0.561923E+09 | 364.16 | 0.00 | -2.9 | ||
Maximum of Months | 0.505039E+10 | 4131.44 | 31.15 | 23.48 | 0.731601E+09 | 482.37 | 31.15 | 21.91 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.197822E+10 | 1061.85 | 17-JAN-21:00 | 4.40 | 3.64 | 0.751793E+09 | 495.26 | 17-JAN-23:10 | 4.32 | 3.30 |
February | 0.178226E+10 | 1069.98 | 22-FEB-21:00 | 9.40 | 5.14 | 0.679456E+09 | 498.69 | 22-FEB-23:10 | 6.83 | 5.85 |
March | 0.246248E+10 | 1340.02 | 15-MAR-18:10 | 23.43 | 15.50 | 0.810131E+09 | 569.55 | 15-MAR-22:10 | 16.78 | 13.11 |
April | 0.255989E+10 | 1282.18 | 21-APR-20:00 | 7.80 | 3.65 | 0.810680E+09 | 556.15 | 21-APR-21:40 | 6.30 | 3.16 |
May | 0.288279E+10 | 1356.87 | 31-MAY-18:10 | 20.82 | 13.97 | 0.878563E+09 | 569.56 | 26-MAY-21:49 | 20.82 | 13.97 |
June | 0.309643E+10 | 1767.43 | 27-JUN-21:00 | 22.20 | 20.99 | 0.894696E+09 | 569.55 | 30-JUN-22:10 | 17.73 | 11.83 |
July | 0.340296E+10 | 1893.65 | 19-JUL-21:00 | 26.70 | 22.02 | 0.940566E+09 | 569.55 | 06-JUL-22:10 | 26.70 | 22.02 |
August | 0.337527E+10 | 1925.47 | 10-AUG-21:00 | 26.10 | 18.56 | 0.943221E+09 | 569.56 | 08-AUG-21:49 | 26.10 | 18.56 |
September | 0.300528E+10 | 1781.34 | 21-SEP-21:00 | 18.30 | 16.18 | 0.883908E+09 | 569.55 | 07-SEP-22:10 | 18.30 | 16.18 |
October | 0.272588E+10 | 1465.20 | 11-OCT-21:00 | 15.60 | 10.58 | 0.854493E+09 | 569.55 | 11-OCT-21:00 | 15.60 | 10.82 |
November | 0.240273E+10 | 1228.27 | 01-NOV-20:00 | 7.20 | 5.15 | 0.785218E+09 | 542.08 | 01-NOV-22:10 | 4.32 | 3.43 |
December | 0.201832E+10 | 1085.10 | 01-DEC-21:00 | 6.10 | 3.90 | 0.756463E+09 | 500.94 | 01-DEC-23:10 | 5.50 | 3.14 |
Annual Sum or Average | 0.316925E+11 | 0.998919E+10 | ||||||||
Minimum of Months | 0.178226E+10 | 1061.85 | 4.40 | 3.64 | 0.679456E+09 | 495.26 | 4.32 | 3.14 | ||
Maximum of Months | 0.340296E+10 | 1925.47 | 26.70 | 22.02 | 0.943221E+09 | 569.56 | 26.70 | 22.02 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.429336E+09 | 750.54 | 17-JAN-21:00 | 4.40 | 3.64 | 0.151833E+09 | 93.04 | 17-JAN-22:10 | 4.40 | 3.43 |
February | 0.350193E+09 | 732.68 | 22-FEB-21:00 | 9.40 | 5.14 | 0.137234E+09 | 91.64 | 22-FEB-22:10 | 7.70 | 4.64 |
March | 0.119753E+10 | 988.77 | 15-MAR-18:10 | 23.43 | 15.50 | 0.156636E+09 | 108.49 | 15-MAR-21:19 | 18.17 | 13.56 |
April | 0.172988E+10 | 948.28 | 09-APR-10:33 | 14.80 | 10.96 | 0.155095E+09 | 102.46 | 21-APR-21:19 | 6.50 | 3.28 |
May | 0.215704E+10 | 1055.37 | 27-MAY-10:33 | 19.43 | 12.21 | 0.173508E+09 | 110.77 | 31-MAY-22:10 | 17.55 | 13.48 |
June | 0.239721E+10 | 1193.07 | 27-JUN-21:00 | 22.20 | 20.99 | 0.182993E+09 | 120.45 | 28-JUN-21:19 | 19.23 | 18.23 |
July | 0.268572E+10 | 1656.08 | 21-JUL-20:00 | 23.30 | 21.68 | 0.196815E+09 | 120.45 | 24-JUL-21:19 | 20.93 | 17.61 |
August | 0.263185E+10 | 1379.26 | 10-AUG-21:00 | 26.10 | 18.56 | 0.196545E+09 | 120.45 | 08-AUG-21:00 | 26.10 | 18.56 |
September | 0.230803E+10 | 1167.78 | 16-SEP-10:33 | 25.37 | 19.22 | 0.179395E+09 | 118.81 | 15-SEP-21:19 | 25.37 | 19.22 |
October | 0.199681E+10 | 977.08 | 12-OCT-20:00 | 16.10 | 14.43 | 0.167098E+09 | 109.98 | 12-OCT-21:10 | 15.40 | 14.18 |
November | 0.156977E+10 | 890.79 | 05-NOV-10:33 | 18.30 | 12.89 | 0.151858E+09 | 101.60 | 01-NOV-21:10 | 18.30 | 12.89 |
December | 0.598382E+09 | 777.58 | 01-DEC-21:00 | 6.10 | 3.90 | 0.152001E+09 | 94.84 | 01-DEC-22:10 | 6.02 | 3.25 |
Annual Sum or Average | 0.200518E+11 | 0.200101E+10 | ||||||||
Minimum of Months | 0.350193E+09 | 732.68 | 4.40 | 3.64 | 0.137234E+09 | 91.64 | 4.40 | 3.25 | ||
Maximum of Months | 0.268572E+10 | 1656.08 | 26.10 | 21.68 | 0.196815E+09 | 120.45 | 26.10 | 19.22 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58877320.93 | 348.43 | 17-JAN-22:00 | 4.40 | 3.43 | 0.116691E+09 | 68.57 | 23-JAN-05:40 | -3.7 | -5.5 |
February | 43387002.01 | 307.82 | 22-FEB-22:00 | 7.80 | 4.32 | 0.105501E+09 | 68.57 | 16-FEB-05:10 | 7.80 | 4.32 |
March | 0.463119E+09 | 518.68 | 15-MAR-18:10 | 23.43 | 15.50 | 0.119247E+09 | 80.89 | 15-MAR-22:10 | 16.78 | 13.11 |
April | 0.835266E+09 | 502.99 | 09-APR-10:33 | 14.80 | 10.96 | 0.116829E+09 | 76.35 | 09-APR-23:10 | 8.30 | 7.74 |
May | 0.112642E+10 | 560.77 | 27-MAY-10:33 | 19.43 | 12.21 | 0.130464E+09 | 82.41 | 23-MAY-22:10 | 19.43 | 12.21 |
June | 0.125900E+10 | 632.57 | 29-JUN-10:35 | 24.63 | 19.77 | 0.137997E+09 | 90.29 | 27-JUN-22:10 | 24.63 | 19.77 |
July | 0.140361E+10 | 683.50 | 21-JUL-21:00 | 22.80 | 21.20 | 0.148959E+09 | 92.66 | 21-JUL-21:19 | 22.60 | 21.00 |
August | 0.137759E+10 | 656.82 | 10-AUG-10:35 | 28.53 | 20.68 | 0.148407E+09 | 92.07 | 10-AUG-22:10 | 25.03 | 19.46 |
September | 0.120850E+10 | 622.37 | 16-SEP-10:33 | 25.37 | 19.22 | 0.135005E+09 | 88.32 | 15-SEP-22:10 | 25.37 | 19.22 |
October | 0.102059E+10 | 514.33 | 22-OCT-10:33 | 20.60 | 13.20 | 0.125234E+09 | 81.65 | 12-OCT-22:10 | 20.60 | 13.20 |
November | 0.686131E+09 | 471.26 | 05-NOV-10:33 | 18.30 | 12.89 | 0.114733E+09 | 74.60 | 05-NOV-23:10 | 9.50 | 7.69 |
December | 0.122180E+09 | 389.46 | 01-DEC-21:00 | 6.10 | 3.90 | 0.116699E+09 | 69.70 | 01-DEC-23:10 | 5.50 | 3.14 |
Annual Sum or Average | 0.960468E+10 | 0.151577E+10 | ||||||||
Minimum of Months | 43387002.01 | 307.82 | 4.40 | 3.43 | 0.105501E+09 | 68.57 | -3.7 | -5.5 | ||
Maximum of Months | 0.140361E+10 | 683.50 | 28.53 | 21.20 | 0.148959E+09 | 92.66 | 25.37 | 21.00 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.473063E+11 | 36349.24 | 17-JAN-21:00 | 4.40 | 3.64 | 0.572859E+09 | 381.60 | 20-JAN-22:10 | -2.9 | -3.9 |
February | 0.426941E+11 | 36351.32 | 22-FEB-21:00 | 9.40 | 5.14 | 0.517348E+09 | 381.63 | 22-FEB-23:10 | 6.83 | 5.85 |
March | 0.490981E+11 | 37968.19 | 15-MAR-20:00 | 21.10 | 14.48 | 0.579334E+09 | 381.67 | 14-MAR-21:10 | 21.10 | 14.48 |
April | 0.484239E+11 | 37543.41 | 07-APR-20:00 | 17.20 | 9.45 | 0.561956E+09 | 381.70 | 07-APR-21:10 | 15.92 | 10.46 |
May | 0.513897E+11 | 37990.90 | 23-MAY-20:00 | 21.10 | 12.98 | 0.583474E+09 | 381.72 | 09-MAY-21:40 | 21.10 | 12.98 |
June | 0.509894E+11 | 38453.89 | 27-JUN-20:00 | 23.90 | 21.99 | 0.567092E+09 | 381.79 | 19-JUN-21:10 | 23.90 | 21.99 |
July | 0.531881E+11 | 38711.16 | 21-JUL-20:00 | 23.30 | 21.68 | 0.585821E+09 | 381.76 | 06-JUL-21:10 | 23.30 | 21.68 |
August | 0.531712E+11 | 38621.05 | 10-AUG-20:00 | 25.60 | 18.99 | 0.587188E+09 | 381.74 | 31-AUG-21:10 | 13.93 | 11.97 |
September | 0.502983E+11 | 38222.72 | 15-SEP-20:00 | 22.20 | 20.62 | 0.565683E+09 | 381.80 | 07-SEP-21:10 | 22.20 | 20.62 |
October | 0.503418E+11 | 37855.02 | 11-OCT-20:00 | 16.10 | 11.00 | 0.582082E+09 | 381.73 | 03-OCT-21:10 | 16.10 | 11.00 |
November | 0.476926E+11 | 37140.80 | 16-NOV-21:00 | 8.30 | 6.92 | 0.560885E+09 | 381.62 | 13-NOV-22:10 | 8.30 | 6.92 |
December | 0.473683E+11 | 36558.16 | 01-DEC-21:00 | 6.10 | 3.90 | 0.573114E+09 | 381.63 | 12-DEC-22:10 | 0.00 | -0.5 |
Annual Sum or Average | 0.591962E+12 | 0.683683E+10 | ||||||||
Minimum of Months | 0.426941E+11 | 36349.24 | 4.40 | 3.64 | 0.517348E+09 | 381.60 | -2.9 | -3.9 | ||
Maximum of Months | 0.531881E+11 | 38711.16 | 25.60 | 21.99 | 0.587188E+09 | 381.80 | 23.90 | 21.99 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129587E+11 | 8859.82 | 15-JAN-13:00 | 4.40 | 1.94 | 0.850403E+10 | 5646.06 | 06-JAN-22:40 | 4.40 | 1.94 |
February | 0.119513E+11 | 8534.00 | 28-FEB-13:40 | 0.00 | -2.9 | 0.769308E+10 | 5854.50 | 22-FEB-22:40 | 0.00 | -2.9 |
March | 0.173986E+11 | 10821.71 | 15-MAR-13:30 | 25.55 | 15.84 | 0.923968E+10 | 6462.52 | 15-MAR-22:10 | 16.78 | 13.11 |
April | 0.178992E+11 | 10361.86 | 22-APR-13:00 | 14.40 | 6.45 | 0.913952E+10 | 6412.21 | 07-APR-21:40 | 14.40 | 6.45 |
May | 0.202220E+11 | 9670.05 | 27-MAY-10:33 | 19.43 | 12.21 | 0.985221E+10 | 6462.72 | 23-MAY-22:10 | 19.43 | 12.21 |
June | 0.213272E+11 | 10405.97 | 27-JUN-21:10 | 22.12 | 20.85 | 0.997839E+10 | 6462.80 | 30-JUN-22:10 | 17.73 | 11.83 |
July | 0.234133E+11 | 11256.98 | 20-JUL-21:10 | 25.50 | 24.00 | 0.105193E+11 | 6462.78 | 06-JUL-22:10 | 25.50 | 24.00 |
August | 0.234781E+11 | 12064.44 | 17-AUG-15:03 | 28.90 | 16.32 | 0.105874E+11 | 6462.79 | 22-AUG-22:10 | 16.42 | 12.93 |
September | 0.216422E+11 | 14314.38 | 21-SEP-15:03 | 26.10 | 16.73 | 0.996532E+10 | 6462.67 | 21-SEP-22:10 | 17.12 | 15.29 |
October | 0.194558E+11 | 14367.80 | 11-OCT-12:30 | 21.95 | 13.79 | 0.964170E+10 | 6462.41 | 11-OCT-21:00 | 15.60 | 10.82 |
November | 0.160151E+11 | 9858.59 | 03-NOV-12:30 | 8.35 | 4.56 | 0.884292E+10 | 6259.12 | 01-NOV-00:10 | 8.35 | 4.56 |
December | 0.127457E+11 | 9477.78 | 17-DEC-11:35 | 1.50 | -0.3 | 0.853026E+10 | 5637.64 | 04-DEC-22:40 | 1.50 | -0.3 |
Annual Sum or Average | 0.218507E+12 | 0.112494E+12 | ||||||||
Minimum of Months | 0.119513E+11 | 8534.00 | 0.00 | -2.9 | 0.769308E+10 | 5637.64 | 0.00 | -2.9 | ||
Maximum of Months | 0.234781E+11 | 14367.80 | 28.90 | 24.00 | 0.105874E+11 | 6462.80 | 25.50 | 24.00 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.510617E+11 | 24890.23 | 17-JAN-22:00 | 4.40 | 3.43 | 0.270721E+11 | 17991.06 | 17-JAN-23:10 | 4.32 | 3.30 |
February | 0.461525E+11 | 25241.16 | 22-FEB-22:00 | 7.80 | 4.32 | 0.244461E+11 | 18168.87 | 22-FEB-23:10 | 6.83 | 5.85 |
March | 0.587637E+11 | 33444.74 | 15-MAR-21:10 | 18.53 | 13.66 | 0.290284E+11 | 19185.90 | 15-MAR-22:10 | 16.78 | 13.11 |
April | 0.598766E+11 | 29325.11 | 07-APR-21:55 | 15.00 | 10.09 | 0.287796E+11 | 19185.53 | 07-APR-22:10 | 14.90 | 10.09 |
May | 0.666091E+11 | 33310.55 | 23-MAY-21:52 | 20.60 | 13.34 | 0.308532E+11 | 19186.33 | 26-MAY-21:49 | 13.58 | 11.12 |
June | 0.705104E+11 | 38111.18 | 27-JUN-21:10 | 22.12 | 20.85 | 0.307372E+11 | 19186.31 | 30-JUN-22:10 | 17.73 | 11.83 |
July | 0.770790E+11 | 40459.29 | 20-JUL-21:10 | 25.50 | 24.00 | 0.319615E+11 | 19186.25 | 06-JUL-22:10 | 25.50 | 24.00 |
August | 0.768189E+11 | 40339.12 | 10-AUG-21:10 | 26.02 | 18.64 | 0.321422E+11 | 19186.28 | 22-AUG-22:10 | 16.42 | 12.93 |
September | 0.696871E+11 | 38849.40 | 21-SEP-21:10 | 18.12 | 16.07 | 0.306726E+11 | 19186.21 | 07-SEP-22:10 | 18.12 | 16.07 |
October | 0.641679E+11 | 35512.13 | 11-OCT-21:10 | 15.60 | 10.62 | 0.303727E+11 | 19185.75 | 11-OCT-21:00 | 15.60 | 10.82 |
November | 0.571182E+11 | 28379.09 | 01-NOV-21:20 | 4.40 | 3.43 | 0.281665E+11 | 19183.06 | 01-NOV-21:49 | 4.40 | 3.43 |
December | 0.514702E+11 | 25354.95 | 01-DEC-22:00 | 6.10 | 3.26 | 0.272041E+11 | 18171.00 | 01-DEC-23:10 | 5.50 | 3.14 |
Annual Sum or Average | 0.749315E+12 | 0.351436E+12 | ||||||||
Minimum of Months | 0.461525E+11 | 24890.23 | 4.40 | 3.26 | 0.244461E+11 | 17991.06 | 4.32 | 3.14 | ||
Maximum of Months | 0.770790E+11 | 40459.29 | 26.02 | 24.00 | 0.321422E+11 | 19186.33 | 25.50 | 24.00 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7700120.30 | 2362.27 | 12-JAN-16:01 | -6.2 | -8.3 | 92968559.06 | 56.69 | 31-JAN-04:19 | -11.7 | -12.6 |
February | 15351177.37 | 2851.82 | 28-FEB-16:02 | 0.40 | -2.4 | 84152911.21 | 56.69 | 05-FEB-02:20 | 0.40 | -2.4 |
March | 0.204753E+09 | 3000.26 | 15-MAR-15:02 | 25.50 | 16.19 | 95862691.36 | 56.69 | 15-MAR-22:30 | 16.95 | 13.18 |
April | 0.436688E+09 | 2895.63 | 23-APR-15:02 | 15.00 | 9.35 | 93930899.22 | 56.69 | 07-APR-21:10 | 15.00 | 9.35 |
May | 0.107906E+10 | 3077.56 | 27-MAY-18:01 | 18.80 | 10.20 | 98428005.99 | 56.69 | 31-MAY-21:40 | 17.67 | 13.17 |
June | 0.193385E+10 | 3118.14 | 17-JUN-18:02 | 27.47 | 22.71 | 95798395.13 | 56.70 | 20-JUN-22:49 | 20.28 | 15.48 |
July | 0.236218E+10 | 3222.71 | 18-JUL-18:02 | 26.52 | 19.40 | 99011561.96 | 56.70 | 19-JUL-22:00 | 26.70 | 22.02 |
August | 0.215403E+10 | 3141.61 | 04-AUG-18:02 | 27.12 | 16.51 | 99023284.70 | 56.70 | 18-AUG-22:40 | 21.70 | 17.67 |
September | 0.134685E+10 | 2983.71 | 02-SEP-18:01 | 16.83 | 10.26 | 95428608.41 | 56.69 | 20-SEP-21:19 | 16.33 | 13.85 |
October | 0.377724E+09 | 2964.56 | 22-OCT-15:01 | 21.60 | 14.51 | 96781676.17 | 56.69 | 11-OCT-21:49 | 21.60 | 14.51 |
November | 57094484.30 | 2521.20 | 14-NOV-16:01 | 9.82 | 7.93 | 91971636.88 | 56.69 | 27-NOV-04:19 | 17.40 | 11.98 |
December | 6507793.65 | 2669.05 | 04-DEC-16:01 | -0.9 | -3.5 | 92960603.01 | 56.69 | 12-DEC-04:19 | -10.7 | -11.0 |
Annual Sum or Average | 0.998179E+10 | 0.113632E+10 | ||||||||
Minimum of Months | 6507793.65 | 2362.27 | -6.2 | -8.3 | 84152911.21 | 56.69 | -11.7 | -12.6 | ||
Maximum of Months | 0.236218E+10 | 3222.71 | 27.47 | 22.71 | 99023284.70 | 56.70 | 26.70 | 22.02 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2125713.50 | 975.06 | 11-JAN-16:04 | 11.60 | 10.09 | 92527049.14 | 56.69 | 13-JAN-04:19 | -7.8 | -9.2 |
February | 4596559.97 | 1882.78 | 28-FEB-16:02 | 0.40 | -2.4 | 83684168.28 | 56.69 | 01-FEB-00:20 | 0.40 | -2.4 |
March | 0.106777E+09 | 2879.06 | 15-MAR-15:02 | 25.50 | 16.19 | 95026858.60 | 67.84 | 15-MAR-21:10 | 18.53 | 13.66 |
April | 0.277940E+09 | 3249.11 | 19-APR-18:11 | 13.67 | 8.82 | 93677243.81 | 66.59 | 19-APR-18:10 | 13.67 | 8.82 |
May | 0.758311E+09 | 3294.47 | 03-MAY-18:01 | 14.22 | 6.76 | 0.102618E+09 | 88.71 | 31-MAY-18:10 | 20.82 | 13.97 |
June | 0.148013E+10 | 3301.43 | 14-JUN-20:11 | 14.43 | 8.19 | 0.106678E+09 | 93.82 | 19-JUN-18:10 | 22.70 | 15.33 |
July | 0.193421E+10 | 3155.54 | 06-JUL-21:51 | 16.70 | 12.85 | 0.107754E+09 | 90.11 | 06-JUL-18:10 | 16.70 | 12.85 |
August | 0.164789E+10 | 3209.66 | 02-AUG-21:51 | 17.20 | 12.20 | 0.107320E+09 | 91.98 | 02-AUG-18:10 | 17.20 | 12.20 |
September | 0.813715E+09 | 2944.11 | 16-SEP-15:02 | 26.70 | 19.57 | 0.101500E+09 | 78.66 | 11-SEP-18:10 | 26.70 | 19.57 |
October | 0.168895E+09 | 2941.83 | 11-OCT-15:01 | 22.12 | 14.59 | 96667748.21 | 67.86 | 11-OCT-21:30 | 15.60 | 10.70 |
November | 24611892.91 | 2365.56 | 05-NOV-15:01 | 17.38 | 13.77 | 91057478.08 | 56.69 | 27-NOV-04:19 | 17.40 | 11.98 |
December | 3350059.16 | 990.97 | 14-DEC-19:04 | 3.72 | 3.72 | 92550663.54 | 56.69 | 19-DEC-04:19 | 1.70 | 1.02 |
Annual Sum or Average | 0.722255E+10 | 0.117106E+10 | ||||||||
Minimum of Months | 2125713.50 | 975.06 | 0.40 | -2.4 | 83684168.28 | 56.69 | -7.8 | -9.2 | ||
Maximum of Months | 0.193421E+10 | 3301.43 | 26.70 | 19.57 | 0.107754E+09 | 93.82 | 26.70 | 19.57 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3827874.37 | 95.07 | 15-JAN-15:20 | 5.40 | 1.48 | 0.00 | 0.00 | 01-JAN-00:10 | 5.40 | 1.48 |
February | 3421701.77 | 79.42 | 18-FEB-15:20 | 2.60 | 0.38 | 0.00 | 0.00 | 01-FEB-00:10 | 2.60 | 0.38 |
March | 53008670.05 | 492.88 | 15-MAR-13:30 | 25.55 | 15.84 | 0.00 | 0.00 | 01-MAR-00:10 | 25.55 | 15.84 |
April | 0.134654E+09 | 416.22 | 22-APR-13:00 | 14.40 | 6.45 | 0.00 | 0.00 | 01-APR-00:10 | 14.40 | 6.45 |
May | 0.286552E+09 | 380.32 | 14-MAY-13:40 | 24.63 | 17.99 | 0.00 | 0.00 | 01-MAY-00:10 | 24.63 | 17.99 |
June | 0.437421E+09 | 429.37 | 12-JUN-13:20 | 29.80 | 19.89 | 0.00 | 0.00 | 01-JUN-00:10 | 29.80 | 19.89 |
July | 0.587025E+09 | 491.26 | 21-JUL-13:30 | 31.15 | 21.91 | 0.00 | 0.00 | 01-JUL-00:10 | 31.15 | 21.91 |
August | 0.592615E+09 | 557.76 | 18-AUG-13:30 | 29.70 | 20.75 | 0.00 | 0.00 | 01-AUG-00:10 | 29.70 | 20.75 |
September | 0.485111E+09 | 699.07 | 21-SEP-13:00 | 25.00 | 16.50 | 0.00 | 0.00 | 01-SEP-00:10 | 25.00 | 16.50 |
October | 0.232197E+09 | 711.14 | 11-OCT-12:30 | 21.95 | 13.79 | 0.00 | 0.00 | 01-OCT-00:10 | 21.95 | 13.79 |
November | 50964038.60 | 405.89 | 03-NOV-12:30 | 8.35 | 4.56 | 0.00 | 0.00 | 01-NOV-00:10 | 8.35 | 4.56 |
December | 4117841.59 | 108.72 | 04-DEC-15:20 | -0.2 | -3.0 | 0.00 | 0.00 | 01-DEC-00:10 | -0.2 | -3.0 |
Annual Sum or Average | 0.287092E+10 | 0.00 | ||||||||
Minimum of Months | 3421701.77 | 79.42 | -0.2 | -3.0 | 0.00 | 0.00 | -0.2 | -3.0 | ||
Maximum of Months | 0.592615E+09 | 711.14 | 31.15 | 21.91 | 0.00 | 0.00 | 31.15 | 21.91 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13484797.55 | 585.15 | 15-JAN-09:01 | 0.87 | 0.15 | 94282011.66 | 56.69 | 17-JAN-00:20 | 2.77 | 0.69 |
February | 11196979.69 | 691.57 | 19-FEB-09:01 | 2.07 | -1.4 | 85267889.30 | 56.69 | 01-FEB-04:19 | 2.07 | -1.4 |
March | 0.124670E+09 | 927.15 | 15-MAR-15:02 | 25.50 | 16.19 | 96059641.49 | 70.62 | 15-MAR-21:00 | 16.70 | 13.08 |
April | 0.244473E+09 | 857.70 | 07-APR-15:02 | 18.22 | 9.77 | 93895335.79 | 65.39 | 07-APR-21:49 | 15.18 | 10.17 |
May | 0.446249E+09 | 917.99 | 13-MAY-15:01 | 22.80 | 14.82 | 99857818.09 | 73.45 | 26-MAY-21:19 | 14.43 | 11.21 |
June | 0.624434E+09 | 959.18 | 12-JUN-15:02 | 29.72 | 20.02 | 0.100844E+09 | 77.28 | 19-JUN-21:40 | 18.90 | 15.17 |
July | 0.775588E+09 | 959.71 | 21-JUL-15:02 | 30.40 | 22.63 | 0.104646E+09 | 79.50 | 17-JUL-21:10 | 30.40 | 22.63 |
August | 0.684501E+09 | 963.14 | 09-AUG-15:02 | 29.40 | 18.17 | 0.104159E+09 | 75.94 | 01-AUG-21:49 | 29.40 | 18.17 |
September | 0.461943E+09 | 933.23 | 16-SEP-18:02 | 24.82 | 19.37 | 98610956.50 | 75.82 | 15-SEP-21:10 | 24.82 | 19.37 |
October | 0.254589E+09 | 865.73 | 22-OCT-15:01 | 21.60 | 14.51 | 97222930.87 | 67.24 | 12-OCT-21:30 | 21.60 | 14.51 |
November | 0.112524E+09 | 805.37 | 05-NOV-15:01 | 17.38 | 13.77 | 92713562.46 | 56.69 | 27-NOV-04:10 | 17.30 | 11.94 |
December | 18479901.13 | 749.62 | 03-DEC-09:01 | 1.10 | -1.3 | 94382504.91 | 56.69 | 13-DEC-00:20 | 1.30 | 0.70 |
Annual Sum or Average | 0.377213E+10 | 0.116194E+10 | ||||||||
Minimum of Months | 11196979.69 | 585.15 | 0.87 | -1.4 | 85267889.30 | 56.69 | 1.30 | -1.4 | ||
Maximum of Months | 0.775588E+09 | 963.14 | 30.40 | 22.63 | 0.104646E+09 | 79.50 | 30.40 | 22.63 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7788877.04 | 1538.20 | 15-JAN-16:01 | 4.82 | 1.15 | 93020488.03 | 56.69 | 14-JAN-04:19 | 4.82 | 1.15 |
February | 16848612.93 | 2452.82 | 28-FEB-09:01 | -7.2 | -8.1 | 84250655.32 | 56.69 | 07-FEB-04:19 | -7.2 | -8.1 |
March | 0.190930E+09 | 2787.52 | 15-MAR-15:02 | 25.50 | 16.19 | 96014099.25 | 56.69 | 15-MAR-23:10 | 17.20 | 13.28 |
April | 0.465052E+09 | 2641.10 | 23-APR-15:02 | 15.00 | 9.35 | 94243983.38 | 56.69 | 07-APR-21:10 | 15.00 | 9.35 |
May | 0.106765E+10 | 2872.31 | 14-MAY-15:02 | 25.92 | 17.84 | 98632771.18 | 56.69 | 10-MAY-21:40 | 25.92 | 17.84 |
June | 0.182539E+10 | 2899.36 | 12-JUN-08:61 | 25.28 | 18.91 | 95906931.99 | 56.70 | 28-JUN-21:40 | 19.07 | 18.18 |
July | 0.235708E+10 | 2905.47 | 21-JUL-18:02 | 28.62 | 21.70 | 99110855.08 | 56.70 | 19-JUL-22:00 | 28.62 | 21.70 |
August | 0.213114E+10 | 2899.09 | 10-AUG-18:02 | 26.93 | 20.08 | 99149092.97 | 56.70 | 14-AUG-21:30 | 24.15 | 21.43 |
September | 0.137538E+10 | 2842.17 | 15-SEP-15:02 | 24.22 | 20.37 | 95563114.14 | 56.70 | 21-SEP-21:00 | 17.20 | 15.48 |
October | 0.403639E+09 | 2772.60 | 22-OCT-15:01 | 21.60 | 14.51 | 97037047.79 | 56.69 | 11-OCT-21:40 | 21.60 | 14.51 |
November | 74401665.72 | 2360.50 | 05-NOV-15:01 | 17.38 | 13.77 | 92017265.40 | 56.69 | 27-NOV-04:19 | 17.40 | 11.98 |
December | 9733513.00 | 1000.67 | 14-DEC-19:04 | 3.72 | 3.72 | 92946379.77 | 56.69 | 19-DEC-04:19 | 1.70 | 1.02 |
Annual Sum or Average | 0.992502E+10 | 0.113789E+10 | ||||||||
Minimum of Months | 7788877.04 | 1000.67 | -7.2 | -8.1 | 84250655.32 | 56.69 | -7.2 | -8.1 | ||
Maximum of Months | 0.235708E+10 | 2905.47 | 28.62 | 21.70 | 99149092.97 | 56.70 | 28.62 | 21.70 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2041144.74 | 936.70 | 07-JAN-09:04 | 1.93 | 1.40 | 92570163.29 | 56.69 | 27-JAN-04:19 | -4.6 | -5.9 |
February | 4760076.35 | 1388.96 | 28-FEB-09:01 | -7.2 | -8.1 | 83729950.20 | 56.69 | 07-FEB-04:19 | -7.2 | -8.1 |
March | 99156703.24 | 2648.65 | 15-MAR-15:02 | 25.50 | 16.19 | 95101532.09 | 67.73 | 15-MAR-21:30 | 17.80 | 13.45 |
April | 0.295786E+09 | 2544.94 | 08-APR-15:01 | 19.13 | 13.03 | 94033872.18 | 63.11 | 07-APR-21:49 | 19.13 | 13.03 |
May | 0.801308E+09 | 2885.47 | 31-MAY-08:51 | 17.80 | 13.21 | 0.101099E+09 | 74.17 | 23-MAY-21:10 | 17.80 | 13.21 |
June | 0.144901E+10 | 3254.37 | 30-JUN-08:32 | 19.63 | 14.65 | 0.103084E+09 | 78.73 | 12-JUN-21:40 | 19.63 | 14.65 |
July | 0.191431E+10 | 3262.69 | 14-JUL-08:32 | 22.40 | 16.80 | 0.107228E+09 | 83.24 | 17-JUL-21:10 | 22.20 | 19.60 |
August | 0.162800E+10 | 3365.82 | 05-AUG-08:32 | 23.30 | 17.42 | 0.106374E+09 | 78.18 | 02-AUG-21:40 | 23.30 | 17.42 |
September | 0.891458E+09 | 2955.86 | 09-SEP-08:51 | 18.90 | 14.02 | 99954388.06 | 75.20 | 15-SEP-21:10 | 21.60 | 20.41 |
October | 0.192350E+09 | 2661.31 | 11-OCT-15:01 | 22.12 | 14.59 | 96716621.81 | 65.20 | 11-OCT-21:30 | 15.60 | 10.70 |
November | 30791195.07 | 2219.74 | 05-NOV-15:01 | 17.38 | 13.77 | 91080955.44 | 56.69 | 27-NOV-04:19 | 17.40 | 11.98 |
December | 2807484.86 | 1044.48 | 17-DEC-09:03 | 0.60 | -0.9 | 92564015.93 | 56.69 | 14-DEC-00:20 | 0.60 | -0.9 |
Annual Sum or Average | 0.731178E+10 | 0.116354E+10 | ||||||||
Minimum of Months | 2041144.74 | 936.70 | -7.2 | -8.1 | 83729950.20 | 56.69 | -7.2 | -8.1 | ||
Maximum of Months | 0.191431E+10 | 3365.82 | 25.50 | 17.42 | 0.107228E+09 | 83.24 | 23.30 | 20.41 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.432798E+09 | 960.31 | 17-JAN-22:20 | 4.40 | 3.43 | 0.119882E+10 | 704.44 | 23-JAN-05:49 | -3.8 | -5.5 |
February | 0.443961E+09 | 1123.77 | 22-FEB-23:10 | 6.83 | 5.85 | 0.108387E+10 | 705.95 | 22-FEB-22:49 | 6.83 | 5.85 |
March | 0.209612E+10 | 1658.67 | 15-MAR-18:10 | 23.43 | 15.50 | 0.121998E+10 | 799.64 | 15-MAR-21:49 | 17.07 | 13.21 |
April | 0.290960E+10 | 1678.18 | 22-APR-10:33 | 11.33 | 5.08 | 0.120759E+10 | 784.33 | 24-APR-21:40 | 6.47 | 5.18 |
May | 0.373277E+10 | 1869.91 | 27-MAY-10:33 | 19.43 | 12.21 | 0.134927E+10 | 856.14 | 31-MAY-21:40 | 17.67 | 13.17 |
June | 0.419380E+10 | 2098.92 | 29-JUN-10:35 | 24.63 | 19.77 | 0.143388E+10 | 930.90 | 30-JUN-21:40 | 17.97 | 11.44 |
July | 0.465160E+10 | 2215.04 | 21-JUL-10:35 | 29.03 | 21.82 | 0.154313E+10 | 951.85 | 21-JUL-22:10 | 22.30 | 20.72 |
August | 0.456516E+10 | 2185.76 | 10-AUG-10:35 | 28.53 | 20.68 | 0.153594E+10 | 944.23 | 11-AUG-21:40 | 18.17 | 14.56 |
September | 0.397676E+10 | 2010.06 | 16-SEP-10:45 | 25.73 | 19.32 | 0.138917E+10 | 905.35 | 21-SEP-21:40 | 17.57 | 15.72 |
October | 0.312750E+10 | 1678.97 | 11-OCT-10:33 | 18.50 | 13.21 | 0.125615E+10 | 809.15 | 11-OCT-22:10 | 15.68 | 10.85 |
November | 0.191892E+10 | 1443.48 | 05-NOV-10:33 | 18.30 | 12.89 | 0.116638E+10 | 751.05 | 01-NOV-00:10 | 18.30 | 12.89 |
December | 0.509270E+09 | 1053.72 | 17-DEC-13:00 | 2.20 | 0.48 | 0.119882E+10 | 704.43 | 11-DEC-05:49 | 2.20 | 0.48 |
Annual Sum or Average | 0.325583E+11 | 0.155830E+11 | ||||||||
Minimum of Months | 0.432798E+09 | 960.31 | 2.20 | 0.48 | 0.108387E+10 | 704.43 | -3.8 | -5.5 | ||
Maximum of Months | 0.465160E+10 | 2215.04 | 29.03 | 21.82 | 0.154313E+10 | 951.85 | 22.30 | 20.72 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6073078.71 | 2486.24 | 15-JAN-16:01 | 4.82 | 1.15 | 92584233.25 | 56.69 | 13-JAN-04:19 | 4.82 | 1.15 |
February | 12874596.98 | 2958.45 | 28-FEB-16:02 | 0.40 | -2.4 | 83772131.80 | 56.69 | 07-FEB-04:19 | 0.40 | -2.4 |
March | 0.183633E+09 | 3134.65 | 14-MAR-15:01 | 24.32 | 16.47 | 95266079.05 | 56.69 | 15-MAR-22:19 | 16.87 | 13.15 |
April | 0.418676E+09 | 3031.59 | 23-APR-15:02 | 15.00 | 9.35 | 93591532.33 | 56.69 | 07-APR-21:40 | 15.00 | 9.35 |
May | 0.104274E+10 | 3219.54 | 27-MAY-18:01 | 18.80 | 10.20 | 98282520.35 | 56.69 | 31-MAY-21:30 | 17.70 | 13.06 |
June | 0.193590E+10 | 3227.28 | 19-JUN-18:02 | 22.70 | 15.33 | 95732282.54 | 56.70 | 01-JUN-21:49 | 22.70 | 15.33 |
July | 0.239240E+10 | 3361.28 | 10-JUL-18:02 | 26.93 | 18.82 | 98966439.53 | 56.70 | 20-JUL-21:40 | 25.20 | 23.91 |
August | 0.213924E+10 | 3373.38 | 10-AUG-18:02 | 26.93 | 20.08 | 98953281.15 | 56.70 | 14-AUG-21:00 | 23.90 | 21.19 |
September | 0.126320E+10 | 3168.52 | 15-SEP-15:02 | 24.22 | 20.37 | 95267515.33 | 56.70 | 01-SEP-01:00 | 24.22 | 20.37 |
October | 0.323814E+09 | 3060.50 | 22-OCT-15:01 | 21.60 | 14.51 | 96340180.84 | 56.69 | 22-OCT-00:40 | 21.60 | 14.51 |
November | 40540288.33 | 2646.98 | 14-NOV-16:01 | 9.82 | 7.93 | 91371791.38 | 56.69 | 27-NOV-04:19 | 17.40 | 11.98 |
December | 5784766.52 | 2344.76 | 04-DEC-16:01 | -0.9 | -3.5 | 92595236.31 | 56.69 | 01-DEC-04:19 | -0.9 | -3.5 |
Annual Sum or Average | 0.976488E+10 | 0.113272E+10 | ||||||||
Minimum of Months | 5784766.52 | 2344.76 | -0.9 | -3.5 | 83772131.80 | 56.69 | -0.9 | -3.5 | ||
Maximum of Months | 0.239240E+10 | 3373.38 | 26.93 | 20.37 | 98966439.53 | 56.70 | 25.20 | 23.91 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1905978.17 | 1047.48 | 17-JAN-19:04 | 7.43 | 6.38 | 92353429.06 | 56.69 | 28-JAN-00:20 | -5.2 | -6.3 |
February | 2521057.16 | 962.39 | 15-FEB-09:04 | 6.70 | 4.64 | 83478464.52 | 56.69 | 01-FEB-04:19 | 6.70 | 4.64 |
March | 85206291.19 | 3051.42 | 15-MAR-15:02 | 25.50 | 16.19 | 94519616.14 | 68.64 | 15-MAR-21:30 | 17.80 | 13.45 |
April | 0.259413E+09 | 3490.66 | 19-APR-18:11 | 13.67 | 8.82 | 93327325.01 | 69.47 | 19-APR-18:10 | 13.67 | 8.82 |
May | 0.724690E+09 | 3477.12 | 03-MAY-18:01 | 14.22 | 6.76 | 0.103125E+09 | 94.02 | 31-MAY-18:10 | 20.82 | 13.97 |
June | 0.153196E+10 | 3521.45 | 14-JUN-20:11 | 14.43 | 8.19 | 0.107860E+09 | 100.14 | 19-JUN-18:10 | 22.70 | 15.33 |
July | 0.201350E+10 | 3405.50 | 06-JUL-21:51 | 16.70 | 12.85 | 0.108240E+09 | 94.91 | 06-JUL-18:10 | 16.70 | 12.85 |
August | 0.167234E+10 | 3401.66 | 02-AUG-21:51 | 17.20 | 12.20 | 0.107742E+09 | 98.34 | 02-AUG-18:10 | 17.20 | 12.20 |
September | 0.743000E+09 | 3073.99 | 11-SEP-19:31 | 14.60 | 10.96 | 0.101852E+09 | 84.19 | 11-SEP-18:10 | 14.60 | 10.96 |
October | 0.125978E+09 | 3049.56 | 11-OCT-15:01 | 22.12 | 14.59 | 96130453.35 | 68.49 | 11-OCT-21:30 | 15.60 | 10.70 |
November | 18259984.77 | 2180.68 | 05-NOV-15:01 | 17.38 | 13.77 | 90412725.31 | 56.69 | 27-NOV-04:19 | 17.40 | 11.98 |
December | 2767813.80 | 1040.19 | 01-DEC-16:04 | 7.20 | 5.30 | 92319513.61 | 56.69 | 01-DEC-04:19 | 7.20 | 5.30 |
Annual Sum or Average | 0.718154E+10 | 0.117136E+10 | ||||||||
Minimum of Months | 1905978.17 | 962.39 | 6.70 | 4.64 | 83478464.52 | 56.69 | -5.2 | -6.3 | ||
Maximum of Months | 0.201350E+10 | 3521.45 | 25.50 | 16.19 | 0.108240E+09 | 100.14 | 22.70 | 15.33 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 43481209.41 | 1619.80 | 12-JAN-16:01 | -6.2 | -8.3 | 94392124.34 | 56.69 | 23-JAN-00:20 | 0.40 | -0.6 |
February | 44004538.31 | 1614.27 | 28-FEB-16:02 | 0.40 | -2.4 | 85293535.18 | 56.69 | 23-FEB-00:20 | 0.40 | -2.4 |
March | 0.279970E+09 | 1682.06 | 15-MAR-18:02 | 23.43 | 15.50 | 96944466.27 | 56.69 | 15-MAR-21:40 | 17.43 | 13.33 |
April | 0.370156E+09 | 1592.92 | 22-APR-18:02 | 13.53 | 6.08 | 94311803.82 | 56.69 | 07-APR-21:00 | 13.53 | 6.08 |
May | 0.642731E+09 | 1697.26 | 16-MAY-18:02 | 20.50 | 11.28 | 98365866.70 | 56.69 | 26-MAY-22:10 | 13.30 | 10.67 |
June | 0.978966E+09 | 1755.01 | 20-JUN-18:02 | 25.92 | 17.29 | 95642448.90 | 56.69 | 29-JUN-21:00 | 20.00 | 18.86 |
July | 0.132076E+10 | 1770.84 | 20-JUL-18:02 | 29.32 | 22.77 | 98943299.22 | 56.70 | 20-JUL-21:10 | 25.50 | 24.00 |
August | 0.129020E+10 | 1796.78 | 10-AUG-15:02 | 29.90 | 19.74 | 98959431.00 | 56.69 | 18-AUG-23:10 | 21.60 | 17.65 |
September | 0.100376E+10 | 1754.71 | 21-SEP-15:02 | 26.10 | 16.73 | 95508574.43 | 56.69 | 22-SEP-21:19 | 15.93 | 12.02 |
October | 0.508733E+09 | 1706.31 | 11-OCT-15:01 | 22.12 | 14.59 | 97617233.78 | 56.69 | 11-OCT-21:30 | 15.60 | 10.70 |
November | 0.189357E+09 | 1532.55 | 16-NOV-16:01 | 17.38 | 13.61 | 93133858.39 | 56.69 | 27-NOV-03:49 | 16.93 | 11.59 |
December | 45042536.46 | 1601.30 | 11-DEC-16:01 | -9.3 | -9.8 | 94018900.77 | 56.69 | 29-DEC-04:19 | -8.0 | -8.6 |
Annual Sum or Average | 0.671717E+10 | 0.114313E+10 | ||||||||
Minimum of Months | 43481209.41 | 1532.55 | -9.3 | -9.8 | 85293535.18 | 56.69 | -8.0 | -8.6 | ||
Maximum of Months | 0.132076E+10 | 1796.78 | 29.90 | 22.77 | 98959431.00 | 56.70 | 25.50 | 24.00 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288768E+11 | 16496.04 | 17-JAN-23:00 | 4.40 | 3.43 | 0.182829E+11 | 11347.87 | 02-JAN-00:20 | 4.40 | 3.43 |
February | 0.260930E+11 | 16441.34 | 22-FEB-23:00 | 7.20 | 6.11 | 0.165240E+11 | 11347.92 | 03-FEB-00:20 | 7.20 | 6.11 |
March | 0.319609E+11 | 20308.17 | 15-MAR-21:10 | 18.53 | 13.66 | 0.188015E+11 | 11348.62 | 15-MAR-22:10 | 16.78 | 13.11 |
April | 0.333079E+11 | 19288.26 | 07-APR-21:55 | 15.00 | 10.09 | 0.184164E+11 | 11347.96 | 07-APR-22:10 | 14.90 | 10.09 |
May | 0.378119E+11 | 20817.12 | 23-MAY-21:52 | 20.60 | 13.34 | 0.192131E+11 | 11349.22 | 31-MAY-22:10 | 17.55 | 13.48 |
June | 0.400232E+11 | 22086.53 | 27-JUN-21:20 | 22.03 | 20.71 | 0.187052E+11 | 11357.69 | 30-JUN-21:19 | 18.13 | 11.21 |
July | 0.431825E+11 | 22783.89 | 20-JUL-21:20 | 25.40 | 23.97 | 0.192803E+11 | 11360.32 | 21-JUL-21:19 | 22.60 | 21.00 |
August | 0.421827E+11 | 22453.26 | 10-AUG-22:00 | 25.60 | 18.99 | 0.193452E+11 | 11357.58 | 11-AUG-21:19 | 18.53 | 14.68 |
September | 0.375767E+11 | 21280.76 | 15-SEP-21:53 | 21.10 | 19.92 | 0.186009E+11 | 11348.97 | 21-SEP-22:10 | 17.12 | 15.29 |
October | 0.345990E+11 | 19600.89 | 12-OCT-21:44 | 14.60 | 13.81 | 0.189926E+11 | 11348.36 | 11-OCT-21:00 | 14.60 | 13.81 |
November | 0.313391E+11 | 17867.50 | 16-NOV-23:00 | 7.80 | 5.20 | 0.182001E+11 | 11348.03 | 13-NOV-00:20 | 7.80 | 5.20 |
December | 0.292329E+11 | 16847.96 | 01-DEC-23:00 | 5.60 | 3.21 | 0.183452E+11 | 11347.89 | 05-DEC-00:20 | -4.8 | -5.8 |
Annual Sum or Average | 0.416187E+12 | 0.222707E+12 | ||||||||
Minimum of Months | 0.260930E+11 | 16441.34 | 4.40 | 3.21 | 0.165240E+11 | 11347.87 | -4.8 | -5.8 | ||
Maximum of Months | 0.431825E+11 | 22783.89 | 25.60 | 23.97 | 0.193452E+11 | 11360.32 | 22.60 | 21.00 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.321149E+11 | 18522.55 | 17-JAN-23:00 | 4.40 | 3.43 | 0.186348E+11 | 11347.98 | 13-JAN-00:20 | 4.40 | 3.43 |
February | 0.290133E+11 | 18480.50 | 22-FEB-23:00 | 7.20 | 6.11 | 0.168525E+11 | 11348.06 | 01-FEB-00:20 | 7.20 | 6.11 |
March | 0.355144E+11 | 22035.70 | 15-MAR-21:10 | 18.53 | 13.66 | 0.190365E+11 | 11348.63 | 15-MAR-22:10 | 16.78 | 13.11 |
April | 0.369475E+11 | 21140.44 | 07-APR-21:55 | 15.00 | 10.09 | 0.185681E+11 | 11348.02 | 16-APR-23:19 | -3.0 | -4.7 |
May | 0.414514E+11 | 22398.39 | 23-MAY-21:52 | 20.60 | 13.34 | 0.192883E+11 | 11349.23 | 31-MAY-22:10 | 17.55 | 13.48 |
June | 0.431841E+11 | 23447.78 | 27-JUN-21:20 | 22.03 | 20.71 | 0.187349E+11 | 11385.41 | 30-JUN-21:19 | 18.13 | 11.21 |
July | 0.461614E+11 | 24012.47 | 20-JUL-21:20 | 25.40 | 23.97 | 0.192966E+11 | 11378.66 | 25-JUL-21:19 | 22.40 | 18.49 |
August | 0.452026E+11 | 23729.20 | 10-AUG-21:20 | 25.93 | 18.71 | 0.193687E+11 | 11377.94 | 08-AUG-21:19 | 25.93 | 18.71 |
September | 0.408108E+11 | 22773.51 | 15-SEP-21:20 | 21.50 | 20.31 | 0.186561E+11 | 11367.83 | 15-SEP-21:19 | 21.50 | 20.31 |
October | 0.382995E+11 | 21288.25 | 12-OCT-21:44 | 14.60 | 13.81 | 0.191481E+11 | 11348.38 | 11-OCT-21:00 | 14.60 | 13.81 |
November | 0.349046E+11 | 19870.69 | 16-NOV-22:10 | 8.22 | 6.21 | 0.183961E+11 | 11348.07 | 13-NOV-00:20 | 8.22 | 6.21 |
December | 0.325325E+11 | 18868.32 | 01-DEC-23:00 | 5.60 | 3.21 | 0.186757E+11 | 11347.99 | 26-DEC-00:20 | -11.1 | -12.1 |
Annual Sum or Average | 0.456137E+12 | 0.224656E+12 | ||||||||
Minimum of Months | 0.290133E+11 | 18480.50 | 4.40 | 3.21 | 0.168525E+11 | 11347.98 | -11.1 | -12.1 | ||
Maximum of Months | 0.461614E+11 | 24012.47 | 25.93 | 23.97 | 0.193687E+11 | 11385.41 | 25.93 | 20.31 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.444335E+11 | 25217.72 | 15-JAN-11:40 | 3.87 | 2.17 | 0.187661E+11 | 11319.65 | 28-JAN-18:19 | -6.7 | -8.3 |
February | 0.402949E+11 | 24846.86 | 28-FEB-11:35 | -1.5 | -3.8 | 0.169488E+11 | 11319.63 | 11-FEB-18:19 | -1.5 | -3.8 |
March | 0.478045E+11 | 27872.75 | 14-MAR-10:45 | 21.73 | 17.44 | 0.187941E+11 | 11319.73 | 11-MAR-18:19 | 21.73 | 17.44 |
April | 0.484065E+11 | 28262.33 | 22-APR-10:33 | 11.33 | 5.08 | 0.181983E+11 | 11319.68 | 15-APR-17:19 | 11.33 | 5.08 |
May | 0.524894E+11 | 28944.90 | 27-MAY-10:33 | 19.43 | 12.21 | 0.188238E+11 | 11319.67 | 27-MAY-17:19 | 20.03 | 11.03 |
June | 0.530903E+11 | 29433.28 | 12-JUN-10:40 | 28.53 | 19.62 | 0.182350E+11 | 11319.68 | 10-JUN-17:19 | 28.53 | 19.62 |
July | 0.560649E+11 | 30020.37 | 16-JUL-10:33 | 28.50 | 22.06 | 0.188452E+11 | 11319.68 | 08-JUL-17:19 | 28.50 | 22.06 |
August | 0.553466E+11 | 29912.19 | 10-AUG-10:40 | 28.53 | 20.68 | 0.188487E+11 | 11319.68 | 12-AUG-17:19 | 24.43 | 16.84 |
September | 0.515157E+11 | 29023.95 | 09-SEP-10:33 | 21.10 | 14.97 | 0.182236E+11 | 11319.65 | 16-SEP-17:19 | 25.73 | 19.64 |
October | 0.498484E+11 | 27955.56 | 11-OCT-10:50 | 18.95 | 13.43 | 0.188090E+11 | 11319.68 | 14-OCT-17:19 | 5.00 | 4.51 |
November | 0.460438E+11 | 26395.49 | 05-NOV-10:50 | 18.30 | 12.85 | 0.181868E+11 | 11319.62 | 04-NOV-17:19 | 18.30 | 12.85 |
December | 0.445761E+11 | 25096.15 | 16-DEC-11:50 | 4.13 | 1.57 | 0.187690E+11 | 11319.65 | 09-DEC-18:19 | 4.13 | 1.57 |
Annual Sum or Average | 0.589915E+12 | 0.221448E+12 | ||||||||
Minimum of Months | 0.402949E+11 | 24846.86 | -1.5 | -3.8 | 0.169488E+11 | 11319.62 | -6.7 | -8.3 | ||
Maximum of Months | 0.560649E+11 | 30020.37 | 28.53 | 22.06 | 0.188487E+11 | 11319.73 | 28.53 | 22.06 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.649647E+09 | 2601.00 | 15-JAN-11:50 | 4.13 | 2.34 | 0.126882E+10 | 745.62 | 12-JAN-04:10 | 4.13 | 2.34 |
February | 0.670646E+09 | 2521.20 | 18-FEB-14:30 | 2.80 | 0.63 | 0.114715E+10 | 745.63 | 07-FEB-04:49 | 2.80 | 0.63 |
March | 0.397375E+10 | 3958.35 | 15-MAR-17:12 | 24.63 | 15.85 | 0.129225E+10 | 878.22 | 15-MAR-21:40 | 17.43 | 13.33 |
April | 0.613354E+10 | 3841.06 | 22-APR-10:33 | 11.33 | 5.08 | 0.126909E+10 | 828.84 | 07-APR-21:40 | 11.33 | 5.08 |
May | 0.829724E+10 | 4306.77 | 27-MAY-10:33 | 19.43 | 12.21 | 0.141385E+10 | 900.10 | 23-MAY-21:40 | 19.43 | 12.21 |
June | 0.932544E+10 | 4813.83 | 29-JUN-10:35 | 24.63 | 19.77 | 0.150257E+10 | 987.31 | 27-JUN-21:40 | 24.63 | 19.77 |
July | 0.105353E+11 | 6012.15 | 21-JUL-13:30 | 31.15 | 21.91 | 0.162816E+10 | 1007.40 | 21-JUL-22:10 | 22.30 | 20.72 |
August | 0.102166E+11 | 5578.88 | 09-AUG-15:03 | 29.40 | 18.17 | 0.160751E+10 | 1007.38 | 10-AUG-21:49 | 25.68 | 18.92 |
September | 0.866256E+10 | 4577.08 | 16-SEP-10:50 | 25.73 | 19.32 | 0.143481E+10 | 944.48 | 21-SEP-21:40 | 17.57 | 15.72 |
October | 0.657357E+10 | 3905.28 | 11-OCT-10:50 | 18.95 | 13.43 | 0.131933E+10 | 865.04 | 11-OCT-21:49 | 15.60 | 10.78 |
November | 0.404695E+10 | 3382.58 | 27-NOV-11:33 | 14.63 | 10.55 | 0.123294E+10 | 783.62 | 01-NOV-00:10 | 14.63 | 10.55 |
December | 0.896159E+09 | 2910.56 | 17-DEC-11:35 | 1.50 | -0.3 | 0.126888E+10 | 745.63 | 01-DEC-04:49 | 1.50 | -0.3 |
Annual Sum or Average | 0.699815E+11 | 0.163854E+11 | ||||||||
Minimum of Months | 0.649647E+09 | 2521.20 | 1.50 | -0.3 | 0.114715E+10 | 745.62 | 1.50 | -0.3 | ||
Maximum of Months | 0.105353E+11 | 6012.15 | 31.15 | 21.91 | 0.162816E+10 | 1007.40 | 25.68 | 20.72 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.678718E+09 | 1208.02 | 24-JAN-07:40 | -12.0 |
February | 0.603012E+09 | 1555.08 | 07-FEB-07:20 | -16.3 |
March | 86232538.01 | 774.81 | 05-MAR-06:00 | -11.1 |
April | 7452186.33 | 311.67 | 17-APR-06:10 | -4.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 710930.07 | 149.25 | 30-OCT-06:10 | -0.4 |
November | 27696516.69 | 485.62 | 24-NOV-07:10 | -3.2 |
December | 0.637819E+09 | 1223.85 | 11-DEC-07:15 | -16.1 |
Annual Sum or Average | 0.204164E+10 | |||
Minimum of Months | 0.00 | 0.00 | -16.3 | |
Maximum of Months | 0.678718E+09 | 1555.08 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166762E+09 | 414.21 | 31-JAN-13:00 | -10.6 |
February | 0.188896E+09 | 643.19 | 07-FEB-11:03 | -13.0 |
March | 17275512.71 | 233.96 | 07-MAR-05:00 | -13.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.53 |
December | 0.157905E+09 | 476.29 | 11-DEC-10:15 | -12.9 |
Annual Sum or Average | 0.530838E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.188896E+09 | 643.19 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.325656E+09 | 414.18 | 31-JAN-18:00 | -12.2 |
February | 0.327734E+09 | 538.25 | 07-FEB-11:00 | -13.3 |
March | 57937304.86 | 265.26 | 07-MAR-05:00 | -13.3 |
April | 133446.47 | 28.66 | 17-APR-09:07 | 0.87 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 979461.76 | 61.43 | 23-NOV-18:00 | 0.60 |
December | 0.275923E+09 | 454.38 | 11-DEC-10:05 | -13.1 |
Annual Sum or Average | 0.988362E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.327734E+09 | 538.25 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -1.0 |
February | 10333865.28 | 1185.98 | 06-FEB-09:03 | -15.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.53 |
December | 470160.69 | 180.42 | 11-DEC-09:30 | -13.6 |
Annual Sum or Average | 10804025.97 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 10333865.28 | 1185.98 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149951E+10 | 2635.93 | 31-JAN-19:01 | -11.8 |
February | 0.130048E+10 | 2641.81 | 07-FEB-09:01 | -15.3 |
March | 0.526848E+09 | 2589.79 | 06-MAR-09:01 | -8.1 |
April | 0.169693E+09 | 2530.77 | 16-APR-08:61 | -2.9 |
May | 6369889.75 | 1288.37 | 17-MAY-15:04 | 16.70 |
June | 1437373.97 | 1025.49 | 22-JUN-08:04 | 15.37 |
July | 888639.06 | 1001.77 | 06-JUL-08:04 | 15.97 |
August | 1402304.63 | 917.24 | 18-AUG-08:04 | 22.57 |
September | 5240829.62 | 1108.91 | 06-SEP-15:04 | 16.78 |
October | 0.164340E+09 | 2501.57 | 17-OCT-08:61 | -0.0 |
November | 0.523634E+09 | 2549.65 | 24-NOV-09:01 | -1.5 |
December | 0.145528E+10 | 2642.52 | 11-DEC-09:01 | -13.8 |
Annual Sum or Average | 0.565512E+10 | |||
Minimum of Months | 888639.06 | 917.24 | -15.3 | |
Maximum of Months | 0.149951E+10 | 2642.52 | 22.57 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.173275E+10 | 2626.67 | 31-JAN-19:01 | -11.8 |
February | 0.149359E+10 | 2639.00 | 07-FEB-09:01 | -15.3 |
March | 0.714666E+09 | 2609.73 | 07-MAR-09:01 | -9.0 |
April | 0.214801E+09 | 2517.25 | 16-APR-08:61 | -2.9 |
May | 7276364.82 | 1288.64 | 25-MAY-15:04 | 16.93 |
June | 946197.75 | 790.78 | 15-JUN-08:05 | 14.60 |
July | 277011.45 | 623.43 | 06-JUL-08:04 | 15.97 |
August | 658060.75 | 743.19 | 24-AUG-08:05 | 15.10 |
September | 6019984.85 | 1244.21 | 06-SEP-15:04 | 16.78 |
October | 0.232106E+09 | 2530.43 | 17-OCT-08:61 | -0.0 |
November | 0.651650E+09 | 2549.37 | 24-NOV-09:01 | -1.5 |
December | 0.163628E+10 | 2634.16 | 11-DEC-09:01 | -13.8 |
Annual Sum or Average | 0.669103E+10 | |||
Minimum of Months | 277011.45 | 623.43 | -15.3 | |
Maximum of Months | 0.173275E+10 | 2639.00 | 16.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26159196.59 | 200.79 | 04-JAN-05:00 | -12.2 |
February | 29744881.63 | 258.53 | 07-FEB-05:00 | -15.6 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.53 |
December | 7153451.71 | 106.52 | 10-DEC-06:00 | -13.3 |
Annual Sum or Average | 63057529.93 | |||
Minimum of Months | 0.00 | 0.00 | -15.6 | |
Maximum of Months | 29744881.63 | 258.53 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230877E+09 | 768.10 | 31-JAN-16:01 | -12.1 |
February | 0.203037E+09 | 769.75 | 06-FEB-16:01 | -13.4 |
March | 82853515.98 | 757.93 | 06-MAR-16:01 | -6.8 |
April | 2199223.71 | 311.11 | 22-APR-15:05 | 15.68 |
May | 321568.52 | 594.86 | 29-MAY-15:06 | 16.28 |
June | 101219.44 | 468.58 | 09-JUN-15:06 | 17.12 |
July | 194.98 | 2.92 | 18-JUL-21:58 | 22.80 |
August | 19326.21 | 92.99 | 22-AUG-08:56 | 18.30 |
September | 75262.48 | 130.51 | 18-SEP-15:07 | 17.88 |
October | 2017711.25 | 436.51 | 10-OCT-15:05 | 17.70 |
November | 16128204.93 | 707.17 | 29-NOV-16:01 | 2.80 |
December | 0.202218E+09 | 769.20 | 11-DEC-16:01 | -9.3 |
Annual Sum or Average | 0.739848E+09 | |||
Minimum of Months | 194.98 | 2.92 | -13.4 | |
Maximum of Months | 0.230877E+09 | 769.75 | 22.80 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144634E+10 | 2577.30 | 31-JAN-19:01 | -11.8 |
February | 0.126232E+10 | 2573.72 | 06-FEB-16:01 | -13.4 |
March | 0.536386E+09 | 2531.35 | 04-MAR-19:01 | -5.1 |
April | 0.168295E+09 | 2452.24 | 16-APR-08:61 | -2.9 |
May | 10003669.21 | 1206.10 | 02-MAY-15:04 | 16.10 |
June | 691053.04 | 695.73 | 03-JUN-08:05 | 12.38 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 414726.65 | 754.74 | 30-AUG-08:05 | 19.40 |
September | 5101177.76 | 690.06 | 14-SEP-08:05 | 20.50 |
October | 0.160364E+09 | 2399.74 | 24-OCT-08:61 | 2.30 |
November | 0.523806E+09 | 2490.62 | 23-NOV-19:01 | -0.6 |
December | 0.145068E+10 | 2578.07 | 11-DEC-09:01 | -13.8 |
Annual Sum or Average | 0.556440E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.8 | |
Maximum of Months | 0.145068E+10 | 2578.07 | 20.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167130E+10 | 2569.77 | 31-JAN-16:01 | -12.1 |
February | 0.144756E+10 | 2581.77 | 06-FEB-16:01 | -13.4 |
March | 0.728049E+09 | 2543.16 | 06-MAR-19:01 | -9.5 |
April | 0.209755E+09 | 2438.64 | 16-APR-08:61 | -2.9 |
May | 12026234.05 | 1283.07 | 02-MAY-15:04 | 16.10 |
June | 490076.45 | 773.72 | 13-JUN-08:05 | 8.90 |
July | 55409.01 | 365.98 | 04-JUL-21:55 | 22.80 |
August | 166035.75 | 535.02 | 24-AUG-08:05 | 15.10 |
September | 6261696.55 | 850.29 | 28-SEP-15:03 | 11.52 |
October | 0.218298E+09 | 2391.86 | 24-OCT-08:61 | 2.30 |
November | 0.641857E+09 | 2478.88 | 23-NOV-19:01 | -0.6 |
December | 0.162989E+10 | 2574.36 | 11-DEC-16:01 | -9.3 |
Annual Sum or Average | 0.656571E+10 | |||
Minimum of Months | 55409.01 | 365.98 | -13.4 | |
Maximum of Months | 0.167130E+10 | 2581.77 | 22.80 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.389090E+09 | 904.54 | 25-JAN-09:03 | -9.1 |
February | 0.322623E+09 | 1296.39 | 06-FEB-09:15 | -15.0 |
March | 5007426.54 | 326.82 | 07-MAR-07:05 | -12.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 11440199.12 | 310.74 | 30-NOV-15:00 | 3.90 |
December | 0.425137E+09 | 1095.17 | 11-DEC-09:03 | -13.8 |
Annual Sum or Average | 0.115330E+10 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.425137E+09 | 1296.39 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217430E+10 | 3156.38 | 31-JAN-19:01 | -11.8 |
February | 0.189341E+10 | 3162.43 | 07-FEB-09:01 | -15.3 |
March | 0.875444E+09 | 3095.84 | 06-MAR-09:01 | -8.1 |
April | 0.345518E+09 | 3048.27 | 16-APR-08:61 | -2.9 |
May | 33434968.85 | 1309.94 | 17-MAY-15:04 | 16.70 |
June | 2111208.00 | 916.96 | 21-JUN-08:04 | 20.73 |
July | 1064792.78 | 753.78 | 25-JUL-08:04 | 20.87 |
August | 1783631.87 | 967.05 | 10-AUG-08:04 | 22.25 |
September | 15780975.08 | 1076.71 | 06-SEP-15:04 | 16.78 |
October | 0.342135E+09 | 3019.50 | 17-OCT-08:61 | -0.0 |
November | 0.868452E+09 | 3045.08 | 24-NOV-09:01 | -1.5 |
December | 0.210604E+10 | 3163.10 | 11-DEC-09:01 | -13.8 |
Annual Sum or Average | 0.865948E+10 | |||
Minimum of Months | 1064792.78 | 753.78 | -15.3 | |
Maximum of Months | 0.217430E+10 | 3163.10 | 22.25 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245228E+10 | 3139.64 | 31-JAN-19:01 | -11.8 |
February | 0.212485E+10 | 3152.38 | 07-FEB-09:01 | -15.3 |
March | 0.111560E+10 | 3112.92 | 07-MAR-09:01 | -9.0 |
April | 0.414634E+09 | 3027.00 | 16-APR-08:61 | -2.9 |
May | 36544030.32 | 1263.99 | 17-MAY-15:04 | 16.70 |
June | 1352611.52 | 765.99 | 14-JUN-08:03 | 11.20 |
July | 266468.44 | 836.34 | 06-JUL-08:04 | 15.97 |
August | 738388.68 | 1015.15 | 31-AUG-18:14 | 14.80 |
September | 17824317.78 | 1253.76 | 06-SEP-15:04 | 16.78 |
October | 0.450469E+09 | 3020.18 | 17-OCT-08:61 | -0.0 |
November | 0.104202E+10 | 3036.65 | 24-NOV-09:01 | -1.5 |
December | 0.231976E+10 | 3146.94 | 11-DEC-09:01 | -13.8 |
Annual Sum or Average | 0.997634E+10 | |||
Minimum of Months | 266468.44 | 765.99 | -15.3 | |
Maximum of Months | 0.245228E+10 | 3152.38 | 16.78 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.716081E+09 | 1654.37 | 03-JAN-16:01 | -6.2 |
February | 0.647972E+09 | 1653.04 | 13-FEB-09:01 | -8.9 |
March | 0.213764E+09 | 1609.42 | 20-MAR-08:61 | -2.7 |
April | 78589538.94 | 1579.44 | 16-APR-08:61 | -2.9 |
May | 3872223.35 | 781.63 | 28-MAY-18:04 | 15.68 |
June | 575037.53 | 484.24 | 14-JUN-08:03 | 11.20 |
July | 330470.56 | 482.03 | 06-JUL-08:04 | 15.97 |
August | 399147.12 | 341.42 | 21-AUG-18:05 | 19.90 |
September | 1555156.81 | 421.45 | 26-SEP-18:05 | 18.12 |
October | 53424292.38 | 1441.19 | 24-OCT-08:61 | 2.30 |
November | 0.213571E+09 | 1590.13 | 30-NOV-16:01 | 3.90 |
December | 0.737248E+09 | 1655.20 | 11-DEC-09:01 | -13.8 |
Annual Sum or Average | 0.266738E+10 | |||
Minimum of Months | 330470.56 | 341.42 | -13.8 | |
Maximum of Months | 0.737248E+09 | 1655.20 | 19.90 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130142E+10 | 2476.48 | 10-JAN-07:05 | -11.4 |
February | 0.120937E+10 | 3426.77 | 07-FEB-07:15 | -16.3 |
March | 0.203125E+09 | 1985.76 | 07-MAR-07:10 | -12.9 |
April | 2529241.33 | 493.01 | 17-APR-06:05 | -4.2 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.65 |
October | 249098.20 | 121.10 | 17-OCT-06:30 | -2.8 |
November | 8541091.15 | 696.82 | 24-NOV-07:10 | -3.2 |
December | 0.125598E+10 | 3079.67 | 11-DEC-07:10 | -16.4 |
Annual Sum or Average | 0.398121E+10 | |||
Minimum of Months | 0.00 | 0.00 | -16.4 | |
Maximum of Months | 0.130142E+10 | 3426.77 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.962539E+10 | 9271.23 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.869085E+10 | 9271.23 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.965507E+10 | 9271.23 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.929905E+10 | 9271.23 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.964208E+10 | 9271.23 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.934170E+10 | 9271.23 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.959943E+10 | 9271.23 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.965878E+10 | 9271.23 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.930276E+10 | 9271.23 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.962169E+10 | 9271.23 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.933428E+10 | 9271.23 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.959943E+10 | 9271.23 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.113371E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.869085E+10 | 9271.23 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.965878E+10 | 9271.23 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.531884E+09 | 512.31 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.480243E+09 | 512.31 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.533523E+09 | 512.31 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.513850E+09 | 512.31 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.532806E+09 | 512.31 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.516207E+09 | 512.31 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.530449E+09 | 512.31 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.533728E+09 | 512.31 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.514055E+09 | 512.31 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.531679E+09 | 512.31 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.515797E+09 | 512.31 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.530449E+09 | 512.31 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.626467E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.480243E+09 | 512.31 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.533728E+09 | 512.31 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.615923E+09 | 593.26 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.556123E+09 | 593.26 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.617822E+09 | 593.26 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.595041E+09 | 593.26 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.616991E+09 | 593.26 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.597770E+09 | 593.26 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.614262E+09 | 593.26 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.618059E+09 | 593.26 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.595278E+09 | 593.26 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.615686E+09 | 593.26 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.597295E+09 | 593.26 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.614262E+09 | 593.26 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.725451E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.556123E+09 | 593.26 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.618059E+09 | 593.26 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.158446E+09 | 152.61 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.143062E+09 | 152.61 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.158934E+09 | 152.61 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.153074E+09 | 152.61 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.158720E+09 | 152.61 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.153776E+09 | 152.61 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.158018E+09 | 152.61 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.158995E+09 | 152.61 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.153135E+09 | 152.61 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.158385E+09 | 152.61 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.153654E+09 | 152.61 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.158018E+09 | 152.61 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.186622E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.143062E+09 | 152.61 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.158995E+09 | 152.61 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.415991E+09 | 400.68 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.375602E+09 | 400.68 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.417273E+09 | 400.68 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.401887E+09 | 400.68 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.416712E+09 | 400.68 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.403730E+09 | 400.68 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.414869E+09 | 400.68 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.417433E+09 | 400.68 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.402047E+09 | 400.68 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.415830E+09 | 400.68 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.403409E+09 | 400.68 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.414869E+09 | 400.68 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.489965E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.375602E+09 | 400.68 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.417433E+09 | 400.68 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.125891E+10 | 1573.46 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.109128E+10 | 1573.46 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.112019E+10 | 1573.46 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.983094E+09 | 1573.46 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.932822E+09 | 1573.46 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.846055E+09 | 1573.46 | 01-JUN-19:49 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.885296E+09 | 1573.46 | 03-JUL-19:00 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.961536E+09 | 1573.46 | 01-AUG-19:40 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.105012E+10 | 1573.46 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.118569E+10 | 1573.46 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.121224E+10 | 1573.46 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.126719E+10 | 1573.46 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.127944E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.846055E+09 | 1573.46 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.126719E+10 | 1573.46 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.106155E+11 | 10645.38 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.952843E+10 | 10645.38 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.104878E+11 | 10645.38 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.999745E+10 | 10645.38 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.102769E+11 | 10645.38 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.988425E+10 | 10645.38 | 01-JUN-19:49 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.101769E+11 | 10645.38 | 03-JUL-19:00 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.103178E+11 | 10645.38 | 01-AUG-19:40 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.100751E+11 | 10645.38 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.105263E+11 | 10645.38 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.102855E+11 | 10645.38 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.106033E+11 | 10645.38 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.122775E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.952843E+10 | 10645.38 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.106155E+11 | 10645.38 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82476868.03 | 74.62 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 74484663.28 | 74.62 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 81821381.83 | 74.62 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 79911301.67 | 74.62 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 82149124.93 | 74.62 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 79277307.08 | 74.62 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 82793865.32 | 74.62 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 81821381.83 | 74.62 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 79932793.28 | 74.62 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 82466122.22 | 74.62 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 79594304.38 | 74.62 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 82804611.13 | 74.62 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.969534E+09 | 0.300992E+10 | ||||
Minimum of Months | 74484663.28 | 74.62 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 82804611.13 | 74.62 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82499421.18 | 74.64 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 74505030.97 | 74.64 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 81843755.73 | 74.64 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 79933153.27 | 74.64 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 82171588.45 | 74.64 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 79298985.31 | 74.64 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 82816505.16 | 74.64 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 81843755.73 | 74.64 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 79954650.76 | 74.64 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 82488672.43 | 74.64 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 79616069.29 | 74.64 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 82827253.90 | 74.64 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.969799E+09 | 0.301074E+10 | ||||
Minimum of Months | 74505030.97 | 74.64 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 82827253.90 | 74.64 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.120431E+10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.108739E+10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.120803E+10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.116348E+10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.120640E+10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.116882E+10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.120107E+10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.120849E+10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.116395E+10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.120385E+10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.116789E+10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.120107E+10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.141847E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.108739E+10 | 1160.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120849E+10 | 1160.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82499421.18 | 74.64 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 74505030.97 | 74.64 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 81843755.73 | 74.64 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 79933153.27 | 74.64 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 82171588.45 | 74.64 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 79298985.31 | 74.64 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 82816505.16 | 74.64 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 81843755.73 | 74.64 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 79954650.76 | 74.64 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 82488672.43 | 74.64 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 79616069.29 | 74.64 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 82827253.90 | 74.64 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.969799E+09 | 0.301074E+10 | ||||
Minimum of Months | 74505030.97 | 74.64 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 82827253.90 | 74.64 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.257152E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.226884E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.243501E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.224263E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.223236E+10 | 2763.12 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.209886E+10 | 2763.12 | 01-JUN-19:49 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.217404E+10 | 2763.12 | 03-JUL-19:00 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.226513E+10 | 2763.12 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.231382E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.249581E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.248827E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.257768E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.281640E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.209886E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.257768E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.257152E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.226884E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.243501E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.224263E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.223236E+10 | 2763.12 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.209886E+10 | 2763.12 | 01-JUN-19:49 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.217404E+10 | 2763.12 | 03-JUL-19:00 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.226513E+10 | 2763.12 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.231382E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.249581E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.248827E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.257768E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.281640E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.209886E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.257768E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113250E+10 | 1090.83 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.102255E+10 | 1090.83 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.113599E+10 | 1090.83 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.109410E+10 | 1090.83 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.113446E+10 | 1090.83 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.109912E+10 | 1090.83 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.112945E+10 | 1090.83 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.113643E+10 | 1090.83 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.109454E+10 | 1090.83 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.113207E+10 | 1090.83 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.109825E+10 | 1090.83 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.112945E+10 | 1090.83 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.133389E+11 | 0.424019E+12 | ||||
Minimum of Months | 0.102255E+10 | 1090.83 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.113643E+10 | 1090.83 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.127458E+10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.115083E+10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.127851E+10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.123137E+10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.127679E+10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.123701E+10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.127114E+10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.127900E+10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.123186E+10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.127409E+10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.123603E+10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.127114E+10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.150123E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.115083E+10 | 1227.68 | 0.00 | 0.00 | |
Maximum of Months | 0.127900E+10 | 1227.68 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.962539E+10 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.869085E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.965507E+10 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.929905E+10 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.964208E+10 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.934170E+10 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.959943E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.965878E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.930276E+10 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.962169E+10 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.933428E+10 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.959943E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.113371E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.869085E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.965878E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.531884E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207714E+09 |
February | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194698E+09 |
March | 0.199990E+10 | 0.533523E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 203488.37 | 0.157158E+09 |
April | 0.192973E+10 | 0.513850E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109242E+09 |
May | 0.199475E+10 | 0.532806E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 224956.89 | 62830367.69 |
June | 0.193394E+10 | 0.516207E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3615490.15 | 31080182.23 |
July | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7843868.99 | 13349770.37 |
August | 0.199896E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5664845.91 | 21309640.91 |
September | 0.192879E+10 | 0.514055E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 680049.34 | 43953512.16 |
October | 0.199148E+10 | 0.531679E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95682271.56 |
November | 0.192552E+10 | 0.515797E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120116E+09 |
December | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196130E+09 |
Annual Sum or Average | 0.234744E+11 | 0.626467E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18232699.64 | 0.125326E+10 |
Minimum of Months | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13349770.37 |
Maximum of Months | 0.199990E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7843868.99 | 0.207714E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.615923E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81025781.51 |
February | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75886156.27 |
March | 0.231589E+10 | 0.617822E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 124030.75 | 62713073.57 |
April | 0.223463E+10 | 0.595041E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45024356.08 |
May | 0.230993E+10 | 0.616991E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 111172.16 | 27982305.85 |
June | 0.223950E+10 | 0.597770E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1250055.02 | 15078615.03 |
July | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2916759.47 | 7533843.88 |
August | 0.231480E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2245915.62 | 10918634.26 |
September | 0.223354E+10 | 0.595278E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 258041.08 | 20067094.55 |
October | 0.230614E+10 | 0.615686E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40135439.23 |
November | 0.222975E+10 | 0.597295E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48887027.38 |
December | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76709260.29 |
Annual Sum or Average | 0.271834E+11 | 0.725451E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6905974.10 | 0.511962E+09 |
Minimum of Months | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7533843.88 |
Maximum of Months | 0.231589E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2916759.47 | 81025781.51 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189072E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177171E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 380632.04 | 0.142958E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100359E+09 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 354555.55 | 62092802.24 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3057258.20 | 34076671.14 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6682905.81 | 17415887.03 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5264760.43 | 25263939.85 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 684065.27 | 45198263.89 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3950.33 | 89965510.26 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110309E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178553E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16428127.62 | 0.117244E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17415887.03 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6682905.81 | 0.189072E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.158446E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109059E+09 |
February | 0.339028E+09 | 0.143062E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102202E+09 |
March | 0.376747E+09 | 0.158934E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 220753.91 | 82141301.41 |
April | 0.363528E+09 | 0.153074E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57201905.76 |
May | 0.375778E+09 | 0.158720E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 208883.83 | 34980901.58 |
June | 0.364321E+09 | 0.153776E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1834976.60 | 19001415.43 |
July | 0.374985E+09 | 0.158018E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3986396.67 | 9552330.53 |
August | 0.376571E+09 | 0.158995E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3148901.54 | 13967671.80 |
September | 0.363352E+09 | 0.153135E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 421763.67 | 25285449.15 |
October | 0.375161E+09 | 0.158385E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2626.62 | 50914419.05 |
November | 0.362735E+09 | 0.153654E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63051026.51 |
December | 0.374985E+09 | 0.158018E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102960E+09 |
Annual Sum or Average | 0.442217E+10 | 0.186622E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9824302.84 | 0.670318E+09 |
Minimum of Months | 0.339028E+09 | 0.143062E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9552330.53 |
Maximum of Months | 0.376747E+09 | 0.158995E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3986396.67 | 0.109059E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.415991E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275978E+09 |
February | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257960E+09 |
March | 0.155131E+10 | 0.417273E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 388691.40 | 0.211371E+09 |
April | 0.149688E+10 | 0.401887E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150651E+09 |
May | 0.154732E+10 | 0.416712E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 455536.87 | 91414537.96 |
June | 0.150015E+10 | 0.403730E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 4968043.51 | 45843865.55 |
July | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 12093869.31 | 20836513.46 |
August | 0.155059E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 9506114.38 | 31476320.40 |
September | 0.149615E+10 | 0.402047E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 1365280.13 | 62373364.25 |
October | 0.154478E+10 | 0.415830E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133222E+09 |
November | 0.149361E+10 | 0.403409E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165964E+09 |
December | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261436E+09 |
Annual Sum or Average | 0.182090E+11 | 0.489965E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 28777535.61 | 0.170853E+10 |
Minimum of Months | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20836513.46 |
Maximum of Months | 0.155131E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 12093869.31 | 0.275978E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.125891E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464320E+09 |
February | 0.236489E+11 | 0.109128E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435034E+09 |
March | 0.262800E+11 | 0.112019E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 378942.91 | 0.360886E+09 |
April | 0.253579E+11 | 0.983094E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256887E+09 |
May | 0.262123E+11 | 0.932822E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 396832.20 | 0.157554E+09 |
June | 0.254132E+11 | 0.846055E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7263273.63 | 82774564.90 |
July | 0.261570E+11 | 0.885296E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16683184.46 | 40132093.34 |
August | 0.262677E+11 | 0.961536E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12114733.71 | 59404493.08 |
September | 0.253456E+11 | 0.105012E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1146772.50 | 0.113662E+09 |
October | 0.261693E+11 | 0.118569E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228528E+09 |
November | 0.253025E+11 | 0.121224E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278624E+09 |
December | 0.261570E+11 | 0.126719E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438894E+09 |
Annual Sum or Average | 0.308468E+12 | 0.127944E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37983739.41 | 0.291670E+10 |
Minimum of Months | 0.236489E+11 | 0.846055E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40132093.34 |
Maximum of Months | 0.262800E+11 | 0.126719E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16683184.46 | 0.464320E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.106155E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135282E+10 |
February | 0.702046E+11 | 0.952843E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126599E+10 |
March | 0.780153E+11 | 0.104878E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1611349.03 | 0.105455E+10 |
April | 0.752779E+11 | 0.999745E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759599E+09 |
May | 0.778146E+11 | 0.102769E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1503182.01 | 0.475974E+09 |
June | 0.754422E+11 | 0.988425E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19970777.42 | 0.254307E+09 |
July | 0.776503E+11 | 0.101769E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47440126.61 | 0.126452E+09 |
August | 0.779788E+11 | 0.103178E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35905762.98 | 0.182902E+09 |
September | 0.752414E+11 | 0.100751E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3445204.21 | 0.341487E+09 |
October | 0.776868E+11 | 0.105263E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681684E+09 |
November | 0.751137E+11 | 0.102855E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826477E+09 |
December | 0.776503E+11 | 0.106033E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128122E+10 |
Annual Sum or Average | 0.915726E+12 | 0.122775E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109876E+09 | 0.860346E+10 |
Minimum of Months | 0.702046E+11 | 0.952843E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126452E+09 |
Maximum of Months | 0.780153E+11 | 0.106155E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47440126.61 | 0.135282E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118630E+09 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111407E+09 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 164325.40 | 90778364.46 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63787652.14 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 238542.58 | 37086904.50 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2920442.45 | 17041874.06 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6954927.57 | 6046974.80 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5166293.96 | 10302099.66 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 827292.55 | 24022346.05 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8323.66 | 55164405.96 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69222297.00 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111935E+09 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16280148.15 | 0.715426E+09 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6046974.80 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6954927.57 | 0.118630E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118123E+09 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110864E+09 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 170828.99 | 89680645.93 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63327301.68 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 165547.77 | 38532393.99 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2453633.25 | 20522284.72 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6263148.07 | 8695528.97 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4665228.22 | 12975065.23 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 568901.75 | 26035362.00 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1086.21 | 54613196.72 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68339895.82 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111496E+09 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14288374.25 | 0.723205E+09 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8695528.97 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6263148.07 | 0.118123E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 82476868.03 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29082475.52 |
February | 0.00 | 74484663.28 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27189191.95 |
March | 0.00 | 81821381.83 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30073551.90 |
April | 0.00 | 79911301.67 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23643914.82 |
May | 0.00 | 82149124.93 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16657865.40 |
June | 0.00 | 79277307.08 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60067.98 | 10065231.55 |
July | 0.00 | 82793865.32 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 237712.13 | 6161848.42 |
August | 0.00 | 81821381.83 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 192220.53 | 7871779.27 |
September | 0.00 | 79932793.28 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1594.54 | 12636283.25 |
October | 0.00 | 82466122.22 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21905561.68 |
November | 0.00 | 79594304.38 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24057315.67 |
December | 0.00 | 82804611.13 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27674293.07 |
Annual Sum or Average | 0.00 | 0.969534E+09 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 491595.18 | 0.237019E+09 |
Minimum of Months | 0.00 | 74484663.28 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6161848.42 |
Maximum of Months | 0.00 | 82804611.13 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 237712.13 | 30073551.90 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 82499421.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33405974.59 |
February | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31344869.84 |
March | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50556.50 | 25309221.90 |
April | 0.293479E+09 | 79933153.27 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17767962.51 |
May | 0.303504E+09 | 82171588.45 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50282.61 | 10441657.80 |
June | 0.293842E+09 | 79298985.31 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 700469.36 | 5147034.65 |
July | 0.303141E+09 | 82816505.16 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1773402.21 | 2129459.59 |
August | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1335228.92 | 3309812.40 |
September | 0.293479E+09 | 79954650.76 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 175012.15 | 6935892.70 |
October | 0.303322E+09 | 82488672.43 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 995.03 | 15405483.17 |
November | 0.293661E+09 | 79616069.29 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19469559.06 |
December | 0.303141E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31569721.75 |
Annual Sum or Average | 0.357224E+10 | 0.969799E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4085946.78 | 0.202237E+09 |
Minimum of Months | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2129459.59 |
Maximum of Months | 0.303685E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1773402.21 | 33405974.59 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118695E+09 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111539E+09 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 163538.18 | 91087100.14 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64165122.53 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 239687.89 | 37280212.69 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2920693.09 | 17132735.05 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6954582.94 | 6122401.51 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5171436.47 | 10398575.98 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 829183.73 | 24130301.15 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8608.51 | 55445201.58 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69255038.58 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111915E+09 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16287730.80 | 0.717166E+09 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6122401.51 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6954582.94 | 0.118695E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118168E+09 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110934E+09 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 153577.27 | 89939101.58 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63847695.28 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 165257.43 | 38212026.57 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2445686.61 | 19532133.40 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6235767.19 | 8855441.34 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4639760.42 | 12966658.93 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 567956.92 | 25591963.74 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1181.01 | 54894915.15 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68359572.49 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111503E+09 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14209186.85 | 0.722805E+09 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8855441.34 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6235767.19 | 0.118168E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.120431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145684E+09 |
February | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136517E+09 |
March | 0.387034E+10 | 0.120803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298124.43 | 0.109586E+09 |
April | 0.373454E+10 | 0.116348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76842929.68 |
May | 0.386038E+10 | 0.120640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233925.38 | 47241922.93 |
June | 0.374269E+10 | 0.116882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2247888.07 | 26024030.12 |
July | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4967162.61 | 13152464.29 |
August | 0.386853E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3822490.62 | 18956230.22 |
September | 0.373273E+10 | 0.116395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516237.48 | 34048948.22 |
October | 0.385404E+10 | 0.120385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1114.48 | 66925373.10 |
November | 0.372639E+10 | 0.116789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83852152.92 |
December | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137547E+09 |
Annual Sum or Average | 0.454292E+11 | 0.141847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12086943.07 | 0.896378E+09 |
Minimum of Months | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13152464.29 |
Maximum of Months | 0.387034E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4967162.61 | 0.145684E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118548E+09 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111309E+09 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 158924.00 | 90495640.31 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63769077.75 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 228763.32 | 37252407.52 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2846915.81 | 17191858.79 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6813931.98 | 6150774.87 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5057863.30 | 10418888.46 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 798468.61 | 24147680.15 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7210.40 | 55067135.43 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68960647.22 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111903E+09 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15912077.43 | 0.715214E+09 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6150774.87 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6813931.98 | 0.118548E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118281E+09 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110963E+09 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 162519.48 | 89473509.88 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63294903.85 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 158168.47 | 38930581.26 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2398271.54 | 21052271.61 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6149768.01 | 8954554.71 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4576643.97 | 13218789.01 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 549013.97 | 26333198.85 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 990.75 | 54434150.99 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68044984.36 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111602E+09 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13995376.18 | 0.724583E+09 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8954554.71 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6149768.01 | 0.118281E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 82499421.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61615468.88 |
February | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57768370.20 |
March | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80306.22 | 47169089.60 |
April | 0.293479E+09 | 79933153.27 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32998880.58 |
May | 0.303504E+09 | 82171588.45 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 117358.68 | 19116665.25 |
June | 0.293842E+09 | 79298985.31 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1463730.06 | 8774877.39 |
July | 0.303141E+09 | 82816505.16 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3492720.13 | 3141000.15 |
August | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2593064.17 | 5338700.82 |
September | 0.293479E+09 | 79954650.76 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 406496.42 | 12451311.83 |
October | 0.303322E+09 | 82488672.43 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3012.12 | 28746744.27 |
November | 0.293661E+09 | 79616069.29 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36082573.86 |
December | 0.303141E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57977143.87 |
Annual Sum or Average | 0.357224E+10 | 0.969799E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8156687.80 | 0.371181E+09 |
Minimum of Months | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3141000.15 |
Maximum of Months | 0.303685E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3492720.13 | 61615468.88 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.257152E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319505E+09 |
February | 0.415303E+11 | 0.226884E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298668E+09 |
March | 0.461508E+11 | 0.243501E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 192821.05 | 0.248562E+09 |
April | 0.445315E+11 | 0.224263E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181511E+09 |
May | 0.460320E+11 | 0.223236E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135378.83 | 0.115504E+09 |
June | 0.446286E+11 | 0.209886E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2958176.38 | 61709739.33 |
July | 0.459349E+11 | 0.217404E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8269198.80 | 31040014.63 |
August | 0.461292E+11 | 0.226513E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6337524.41 | 43962203.56 |
September | 0.445099E+11 | 0.231382E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 532242.44 | 81425545.83 |
October | 0.459565E+11 | 0.249581E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161383E+09 |
November | 0.444343E+11 | 0.248827E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197007E+09 |
December | 0.459349E+11 | 0.257768E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303409E+09 |
Annual Sum or Average | 0.541708E+12 | 0.281640E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 18425341.90 | 0.204369E+10 |
Minimum of Months | 0.415303E+11 | 0.209886E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31040014.63 |
Maximum of Months | 0.461508E+11 | 0.257768E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8269198.80 | 0.319505E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.257152E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322714E+09 |
February | 0.415303E+11 | 0.226884E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301636E+09 |
March | 0.461508E+11 | 0.243501E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 157445.63 | 0.250970E+09 |
April | 0.445315E+11 | 0.224263E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183283E+09 |
May | 0.460320E+11 | 0.223236E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119053.11 | 0.116527E+09 |
June | 0.446286E+11 | 0.209886E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2879501.97 | 62104583.51 |
July | 0.459349E+11 | 0.217404E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8158853.26 | 31192104.51 |
August | 0.461292E+11 | 0.226513E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6227666.02 | 44234236.94 |
September | 0.445099E+11 | 0.231382E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 493635.15 | 82161302.70 |
October | 0.459565E+11 | 0.249581E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163174E+09 |
November | 0.444343E+11 | 0.248827E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199155E+09 |
December | 0.459349E+11 | 0.257768E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306465E+09 |
Annual Sum or Average | 0.541708E+12 | 0.281640E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 18036155.14 | 0.206362E+10 |
Minimum of Months | 0.415303E+11 | 0.209886E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31192104.51 |
Maximum of Months | 0.461508E+11 | 0.257768E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8158853.26 | 0.322714E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113250E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291328E+09 |
February | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271967E+09 |
March | 0.410691E+10 | 0.113599E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 116581.84 | 0.225098E+09 |
April | 0.396281E+10 | 0.109410E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163206E+09 |
May | 0.409635E+10 | 0.113446E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 106310.04 | 0.103126E+09 |
June | 0.397146E+10 | 0.109912E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 2542262.53 | 54609584.85 |
July | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 7278895.39 | 27099341.04 |
August | 0.410499E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 5508515.65 | 38726956.83 |
September | 0.396089E+10 | 0.109454E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 428035.99 | 72660806.90 |
October | 0.408962E+10 | 0.113207E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145598E+09 |
November | 0.395417E+10 | 0.109825E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178447E+09 |
December | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276518E+09 |
Annual Sum or Average | 0.482060E+11 | 0.133389E+11 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 15980601.45 | 0.184838E+10 |
Minimum of Months | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27099341.04 |
Maximum of Months | 0.410691E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 7278895.39 | 0.291328E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.127458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258452E+09 |
February | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242165E+09 |
March | 0.409620E+10 | 0.127851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383957.54 | 0.194643E+09 |
April | 0.395248E+10 | 0.123137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136464E+09 |
May | 0.408566E+10 | 0.127679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274377.06 | 83790719.91 |
June | 0.396110E+10 | 0.123701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3338011.02 | 45655336.76 |
July | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7645625.55 | 22992065.13 |
August | 0.409429E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5954868.90 | 32755121.95 |
September | 0.395056E+10 | 0.123186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 707440.78 | 58897592.25 |
October | 0.407896E+10 | 0.127409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118746E+09 |
November | 0.394385E+10 | 0.123603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149046E+09 |
December | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244051E+09 |
Annual Sum or Average | 0.480803E+11 | 0.150123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18304280.85 | 0.158766E+10 |
Minimum of Months | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22992065.13 |
Maximum of Months | 0.409620E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7645625.55 | 0.258452E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 9271.23 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 9271.23 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 9271.23 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 9271.23 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 9271.23 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 9271.23 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 9271.23 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 9271.23 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 9271.23 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 9271.23 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 9271.23 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 9271.23 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 512.31 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 115.20 | 31-JAN-02:00 |
February | 1169.53 | 01-FEB-00:10 | 512.31 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 126.43 | 07-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 512.31 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 | 15-MAR-17:00 | 115.46 | 07-MAR-05:10 |
April | 1169.53 | 01-APR-00:10 | 512.31 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 81.22 | 17-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 512.31 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.23 | 10-MAY-15:00 | 59.78 | 01-MAY-05:30 |
June | 1169.53 | 01-JUN-00:10 | 512.31 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.74 | 17-JUN-17:00 | 43.74 | 10-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 512.31 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.51 | 21-JUL-14:00 | 29.18 | 03-JUL-04:20 |
August | 1169.53 | 01-AUG-00:10 | 512.31 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.48 | 10-AUG-14:00 | 32.15 | 01-AUG-05:00 |
September | 1169.53 | 01-SEP-00:10 | 512.31 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.08 | 16-SEP-13:00 | 45.85 | 05-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 512.31 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 75.98 | 17-OCT-06:30 |
November | 1169.53 | 01-NOV-00:10 | 512.31 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 79.02 | 24-NOV-06:00 |
December | 1169.53 | 01-DEC-00:10 | 512.31 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 135.36 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.18 | |||||
Maximum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 21.51 | 135.36 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 593.26 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 44.75 | 31-JAN-02:00 |
February | 1354.32 | 01-FEB-00:10 | 593.26 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 48.80 | 07-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 593.26 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.86 | 15-MAR-14:00 | 45.18 | 07-MAR-05:40 |
April | 1354.32 | 01-APR-00:10 | 593.26 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 32.26 | 17-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 593.26 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.03 | 10-MAY-14:00 | 24.87 | 01-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 593.26 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.21 | 27-JUN-13:00 | 19.45 | 06-JUN-04:30 |
July | 1354.32 | 01-JUL-00:10 | 593.26 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 21-JUL-14:00 | 13.79 | 03-JUL-04:40 |
August | 1354.32 | 01-AUG-00:10 | 593.26 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.78 | 10-AUG-14:00 | 14.74 | 01-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 593.26 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.44 | 16-SEP-13:00 | 20.39 | 05-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 593.26 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 30.74 | 17-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 593.26 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 31.17 | 24-NOV-06:00 |
December | 1354.32 | 01-DEC-00:10 | 593.26 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 52.25 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.79 | |||||
Maximum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 52.25 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 105.08 | 31-JAN-02:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 115.33 | 07-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 | 15-MAR-14:00 | 105.32 | 07-MAR-05:40 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 74.10 | 17-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.71 | 10-MAY-14:00 | 56.46 | 01-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.25 | 12-JUN-14:00 | 44.56 | 04-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.12 | 21-JUL-14:00 | 31.57 | 13-JUL-04:40 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.21 | 10-AUG-14:00 | 34.27 | 01-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 | 16-SEP-13:00 | 46.34 | 05-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 | 11-OCT-13:00 | 70.00 | 17-OCT-06:40 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 72.07 | 24-NOV-06:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 123.48 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.57 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 20.12 | 123.48 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 152.61 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 60.63 | 31-JAN-02:00 |
February | 220.32 | 01-FEB-00:10 | 152.61 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 66.53 | 07-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 152.61 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 | 15-MAR-14:00 | 60.76 | 07-MAR-05:10 |
April | 220.32 | 01-APR-00:10 | 152.61 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 42.75 | 17-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 152.61 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.18 | 10-MAY-14:00 | 32.14 | 01-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 152.61 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.12 | 12-JUN-14:00 | 25.33 | 14-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 152.61 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.60 | 21-JUL-14:00 | 17.92 | 03-JUL-05:00 |
August | 220.32 | 01-AUG-00:10 | 152.61 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.53 | 10-AUG-14:00 | 19.35 | 01-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 152.61 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.06 | 16-SEP-13:00 | 26.26 | 05-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 152.61 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 | 11-OCT-13:00 | 39.99 | 17-OCT-06:50 |
November | 220.32 | 01-NOV-00:10 | 152.61 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 41.59 | 24-NOV-06:00 |
December | 220.32 | 01-DEC-00:10 | 152.61 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 71.24 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.92 | |||||
Maximum of Months | 220.32 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 11.60 | 71.24 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 400.68 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 153.45 | 04-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 400.68 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 168.72 | 07-FEB-07:10 |
March | 907.20 | 01-MAR-00:10 | 400.68 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 11.95 | 15-MAR-14:00 | 155.15 | 07-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 400.68 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 112.41 | 17-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 400.68 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 14.88 | 14-MAY-15:20 | 85.92 | 01-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 400.68 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 28.90 | 27-JUN-13:00 | 64.53 | 14-JUN-05:30 |
July | 907.20 | 01-JUL-00:10 | 400.68 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 32.97 | 16-JUL-16:00 | 44.86 | 03-JUL-05:10 |
August | 907.20 | 01-AUG-00:10 | 400.68 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 29.44 | 13-AUG-15:20 | 48.52 | 03-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 400.68 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 17.38 | 16-SEP-13:00 | 68.56 | 05-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 400.68 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 106.56 | 17-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 400.68 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 107.16 | 24-NOV-07:10 |
December | 907.20 | 01-DEC-00:10 | 400.68 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 175.21 | 11-DEC-06:08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 44.86 | ||||||
Maximum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 32.97 | 175.21 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1573.46 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 256.90 | 31-JAN-02:00 |
February | 15368.40 | 01-FEB-00:10 | 1573.46 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 279.48 | 07-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 1573.46 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.19 | 15-MAR-14:00 | 259.00 | 07-MAR-05:20 |
April | 15368.40 | 01-APR-00:10 | 1573.46 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 180.67 | 17-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 1573.46 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.91 | 14-MAY-15:00 | 142.16 | 01-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 1573.46 | 01-JUN-19:49 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.64 | 27-JUN-13:00 | 110.34 | 10-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1573.46 | 03-JUL-19:00 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.55 | 21-JUL-14:00 | 78.01 | 13-JUL-04:20 |
August | 15368.40 | 01-AUG-00:10 | 1573.46 | 01-AUG-19:40 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 10-AUG-14:00 | 83.59 | 01-AUG-05:00 |
September | 15368.40 | 01-SEP-00:10 | 1573.46 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.07 | 16-SEP-13:00 | 115.97 | 06-SEP-05:00 |
October | 15368.40 | 01-OCT-23:10 | 1573.46 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 175.64 | 17-OCT-04:30 |
November | 15368.40 | 01-NOV-00:10 | 1573.46 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 178.86 | 24-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 1573.46 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 299.21 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.01 | |||||
Maximum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 47.55 | 299.21 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 10645.38 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 751.00 | 31-JAN-02:00 |
February | 45622.98 | 01-FEB-00:10 | 10645.38 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 806.99 | 07-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 10645.38 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.65 | 15-MAR-14:00 | 757.76 | 07-MAR-05:40 |
April | 45622.98 | 01-APR-00:10 | 10645.38 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 540.03 | 17-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 10645.38 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.75 | 10-MAY-14:00 | 421.13 | 01-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 10645.38 | 01-JUN-19:49 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.13 | 27-JUN-13:00 | 328.70 | 06-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 10645.38 | 03-JUL-19:00 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.57 | 21-JUL-14:00 | 232.59 | 03-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 10645.38 | 01-AUG-19:40 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.03 | 10-AUG-14:00 | 246.14 | 03-AUG-04:10 |
September | 45622.98 | 01-SEP-00:10 | 10645.38 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.10 | 16-SEP-13:00 | 342.66 | 06-SEP-05:00 |
October | 45622.98 | 01-OCT-23:10 | 10645.38 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 519.42 | 17-OCT-04:40 |
November | 45622.98 | 01-NOV-00:10 | 10645.38 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 528.54 | 24-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 10645.38 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 873.83 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 10645.38 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.59 | |||||
Maximum of Months | 45622.98 | 10645.38 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 144.57 | 873.83 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 67.15 | 31-JAN-02:00 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 73.67 | 07-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 15-MAR-15:08 | 67.31 | 07-MAR-06:06 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 47.43 | 17-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.78 | 14-MAY-15:10 | 34.97 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 | 12-JUN-15:10 | 25.66 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.88 | 19-JUL-15:10 | 16.43 | 03-JUL-04:20 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.25 | 13-AUG-15:10 | 17.63 | 03-AUG-04:10 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 | 16-SEP-15:10 | 26.89 | 05-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 | 11-OCT-15:10 | 44.38 | 17-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 46.14 | 24-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 78.86 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.43 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 15.88 | 78.86 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 67.15 | 31-JAN-02:00 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 73.67 | 07-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 15-MAR-15:10 | 67.30 | 07-MAR-06:06 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 47.42 | 17-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.78 | 14-MAY-15:08 | 34.97 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 | 12-JUN-15:10 | 25.66 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 | 19-JUL-15:10 | 16.43 | 03-JUL-04:40 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 13-AUG-15:10 | 17.63 | 03-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 | 16-SEP-15:10 | 26.88 | 05-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 | 11-OCT-15:10 | 44.38 | 17-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 46.14 | 24-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 78.86 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.43 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 | 78.86 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 74.62 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 16.06 | 30-JAN-19:00 |
February | 0.00 | 01-FEB-00:10 | 74.62 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 17.54 | 07-FEB-07:00 |
March | 0.00 | 01-MAR-00:10 | 74.62 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 19.35 | 07-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 74.62 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 14.56 | 03-APR-07:00 |
May | 0.00 | 01-MAY-00:10 | 74.62 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 12.23 | 01-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 74.62 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.76 | 27-JUN-13:00 | 9.77 | 06-JUN-05:20 |
July | 0.00 | 01-JUL-00:10 | 74.62 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.26 | 21-JUL-14:00 | 7.28 | 03-JUL-04:40 |
August | 0.00 | 01-AUG-00:10 | 74.62 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.76 | 10-AUG-14:00 | 7.64 | 03-AUG-05:30 |
September | 0.00 | 01-SEP-00:10 | 74.62 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 | 16-SEP-13:00 | 10.27 | 05-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 74.62 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 14.69 | 17-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 74.62 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 13.97 | 18-NOV-22:00 |
December | 0.00 | 01-DEC-00:10 | 74.62 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 18.95 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 74.62 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.28 | |||||
Maximum of Months | 0.00 | 74.62 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 2.26 | 19.35 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 74.64 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 18.74 | 31-JAN-02:00 |
February | 180.00 | 01-FEB-00:10 | 74.64 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 20.56 | 07-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 74.64 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 15-MAR-15:10 | 18.78 | 07-MAR-06:10 |
April | 180.00 | 01-APR-00:10 | 74.64 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 13.24 | 17-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 74.64 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 14-MAY-15:10 | 9.76 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 74.64 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.88 | 12-JUN-15:10 | 7.16 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 74.64 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.44 | 19-JUL-15:10 | 4.59 | 03-JUL-04:40 |
August | 180.00 | 01-AUG-00:10 | 74.64 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 | 13-AUG-15:10 | 4.92 | 03-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 74.64 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 | 16-SEP-15:10 | 7.50 | 05-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 74.64 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 | 11-OCT-15:09 | 12.39 | 17-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 74.64 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 12.88 | 24-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 74.64 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 22.01 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.59 | |||||
Maximum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4.44 | 22.01 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 67.15 | 31-JAN-02:00 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 73.67 | 07-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 15-MAR-15:08 | 67.31 | 07-MAR-06:06 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 47.43 | 17-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.78 | 14-MAY-15:10 | 34.97 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 | 12-JUN-15:10 | 25.66 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.90 | 19-JUL-15:10 | 16.43 | 03-JUL-04:10 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 13-AUG-15:10 | 18.40 | 31-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 | 16-SEP-15:10 | 26.89 | 05-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 | 11-OCT-15:10 | 44.38 | 17-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 46.14 | 24-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 78.86 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.43 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 15.90 | 78.86 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 67.15 | 31-JAN-02:00 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 73.67 | 07-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 15-MAR-15:08 | 67.30 | 07-MAR-06:06 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 47.42 | 17-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.78 | 14-MAY-15:08 | 34.97 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 | 12-JUN-15:10 | 25.66 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 | 19-JUL-15:10 | 16.43 | 03-JUL-04:50 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 13-AUG-15:08 | 18.39 | 31-AUG-07:17 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 | 16-SEP-15:10 | 26.88 | 05-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 | 11-OCT-15:09 | 44.38 | 17-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 46.14 | 24-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 78.86 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.43 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 | 78.86 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 80.95 | 31-JAN-02:00 |
February | 2263.36 | 01-FEB-00:10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 88.83 | 07-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.23 | 15-MAR-14:00 | 81.13 | 07-MAR-05:30 |
April | 2263.36 | 01-APR-00:10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 57.10 | 17-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.78 | 10-MAY-14:00 | 42.72 | 01-MAY-05:00 |
June | 2263.36 | 01-JUN-00:10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.39 | 12-JUN-14:00 | 34.27 | 14-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.25 | 21-JUL-14:00 | 24.38 | 03-JUL-04:05 |
August | 2263.36 | 01-AUG-00:10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.43 | 10-AUG-14:00 | 26.06 | 03-AUG-04:03 |
September | 2263.36 | 01-SEP-00:10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.93 | 16-SEP-13:00 | 35.35 | 05-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 | 11-OCT-13:00 | 53.42 | 17-OCT-06:50 |
November | 2263.36 | 01-NOV-00:10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 55.55 | 24-NOV-06:00 |
December | 2263.36 | 01-DEC-00:10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 95.10 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.38 | ||||
Maximum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.25 | 95.10 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 67.28 | 31-JAN-02:00 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 73.81 | 07-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.08 | 15-MAR-15:10 | 67.44 | 07-MAR-06:06 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 47.55 | 17-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.68 | 14-MAY-15:10 | 35.08 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.78 | 12-JUN-15:10 | 25.77 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.80 | 19-JUL-15:10 | 16.54 | 03-JUL-04:10 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.16 | 13-AUG-15:10 | 17.74 | 03-AUG-04:07 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 | 16-SEP-15:10 | 27.00 | 05-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 11-OCT-15:10 | 44.50 | 17-OCT-06:15 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 46.26 | 24-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 79.00 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 15.80 | 79.00 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 67.28 | 31-JAN-02:00 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 73.80 | 07-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.08 | 15-MAR-15:08 | 67.43 | 07-MAR-06:06 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 47.54 | 17-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.68 | 14-MAY-15:10 | 35.08 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.73 | 12-JUN-15:10 | 25.77 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.79 | 19-JUL-15:10 | 16.54 | 03-JUL-04:30 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 13-AUG-15:10 | 17.74 | 03-AUG-04:07 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 | 16-SEP-15:10 | 27.00 | 05-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 11-OCT-15:07 | 44.50 | 17-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 46.26 | 24-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 78.99 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 15.79 | 78.99 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 74.64 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 34.42 | 31-JAN-02:00 |
February | 180.00 | 01-FEB-00:10 | 74.64 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 37.76 | 07-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 74.64 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 | 15-MAR-15:10 | 34.50 | 07-MAR-06:10 |
April | 180.00 | 01-APR-00:10 | 74.64 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 24.33 | 17-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 74.64 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.93 | 14-MAY-15:10 | 17.95 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 74.64 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 | 12-JUN-15:10 | 13.18 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 74.64 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.08 | 19-JUL-15:10 | 8.46 | 03-JUL-04:10 |
August | 180.00 | 01-AUG-00:10 | 74.64 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.25 | 13-AUG-15:10 | 9.08 | 03-AUG-04:10 |
September | 180.00 | 01-SEP-00:10 | 74.64 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.62 | 16-SEP-15:10 | 13.81 | 05-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 74.64 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 | 11-OCT-15:40 | 22.77 | 17-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 74.64 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 23.67 | 24-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 74.64 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 40.42 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.46 | |||||
Maximum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 8.08 | 40.42 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 175.40 | 31-JAN-02:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 189.56 | 07-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 15-MAR-14:00 | 175.95 | 07-MAR-05:30 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 128.78 | 17-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 | 10-MAY-14:00 | 98.34 | 01-MAY-05:10 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:49 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 27-JUN-13:00 | 75.42 | 10-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:00 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.09 | 21-JUL-14:00 | 52.63 | 03-JUL-04:10 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.79 | 10-AUG-14:00 | 55.68 | 03-AUG-05:10 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.46 | 16-SEP-13:00 | 78.50 | 05-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 121.70 | 17-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 125.75 | 24-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 203.06 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.63 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 30.09 | 203.06 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 176.55 | 31-JAN-02:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 190.80 | 07-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.36 | 15-MAR-14:00 | 176.94 | 07-MAR-05:40 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 129.18 | 17-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.96 | 14-MAY-15:00 | 98.34 | 01-MAY-05:10 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:49 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.77 | 27-JUN-13:00 | 75.42 | 10-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:00 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.09 | 21-JUL-14:00 | 52.63 | 03-JUL-04:10 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.79 | 10-AUG-14:00 | 55.68 | 03-AUG-05:10 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.46 | 16-SEP-13:00 | 78.50 | 05-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 121.70 | 17-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 125.92 | 24-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 204.06 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.63 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 30.09 | 204.06 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1090.83 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 156.72 | 04-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 1090.83 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 173.58 | 07-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1090.83 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 7.23 | 15-MAR-14:00 | 159.73 | 07-MAR-06:10 |
April | 2401.70 | 01-APR-00:10 | 1090.83 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 115.62 | 17-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1090.83 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 7.16 | 14-MAY-15:00 | 88.00 | 01-MAY-06:00 |
June | 2401.70 | 01-JUN-00:10 | 1090.83 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 23.10 | 27-JUN-13:00 | 67.25 | 06-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1090.83 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 26.97 | 21-JUL-14:00 | 46.78 | 03-JUL-05:10 |
August | 2401.70 | 01-AUG-00:10 | 1090.83 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 23.12 | 10-AUG-14:00 | 49.83 | 03-AUG-05:10 |
September | 2401.70 | 01-SEP-00:10 | 1090.83 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 11.19 | 16-SEP-13:00 | 70.26 | 05-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1090.83 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 108.94 | 17-OCT-06:15 |
November | 2401.70 | 01-NOV-00:10 | 1090.83 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 112.30 | 24-NOV-06:10 |
December | 2401.70 | 01-DEC-00:10 | 1090.83 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 179.04 | 11-DEC-06:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 46.78 | ||||||
Maximum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 26.97 | 179.04 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 143.50 | 31-JAN-02:00 |
February | 2395.44 | 01-FEB-00:10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 157.45 | 07-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 | 15-MAR-14:00 | 143.83 | 07-MAR-05:50 |
April | 2395.44 | 01-APR-00:10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 101.29 | 17-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.86 | 10-MAY-15:00 | 74.64 | 01-MAY-05:30 |
June | 2395.44 | 01-JUN-00:10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 | 12-JUN-14:00 | 58.23 | 06-JUN-04:00 |
July | 2395.44 | 01-JUL-00:10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.36 | 21-JUL-14:00 | 41.35 | 03-JUL-04:00 |
August | 2395.44 | 01-AUG-00:10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.59 | 10-AUG-14:00 | 44.71 | 01-AUG-05:00 |
September | 2395.44 | 01-SEP-00:10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.25 | 16-SEP-13:00 | 60.09 | 05-SEP-06:00 |
October | 2395.44 | 01-OCT-23:10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 94.78 | 17-OCT-06:50 |
November | 2395.44 | 01-NOV-00:10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 98.54 | 24-NOV-06:00 |
December | 2395.44 | 01-DEC-00:10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 168.55 | 11-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.35 | ||||
Maximum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.36 | 168.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 12316.43 | 11-JAN-21:00 | 8945.92 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12050.61 | 01-FEB-21:00 | 8945.92 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11709.42 | 15-MAR-18:10 | 53675.50 | 49446.67 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11688.06 | 22-APR-10:33 | 11501.89 | 7726.12 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11896.32 | 27-MAY-10:33 | 11501.89 | 7726.12 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12999.20 | 18-JUN-10:33 | 11501.89 | 9271.10 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13921.36 | 16-JUL-10:33 | 11501.89 | 9271.10 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14573.72 | 19-AUG-10:33 | 11501.89 | 7726.12 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17040.56 | 22-SEP-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18483.60 | 13-OCT-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18178.10 | 01-NOV-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16431.58 | 01-DEC-22:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11688.06 | 8945.92 | 7726.12 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18483.60 | 53675.50 | 49446.67 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1962.90 | 15-JAN-13:50 | 259.90 | 113.85 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.37 |
February | 1983.10 | 28-FEB-13:40 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.49 |
March | 2844.54 | 15-MAR-13:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 | 0.00 |
April | 2353.61 | 22-APR-13:10 | 779.69 | 284.62 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.69 |
May | 2178.52 | 27-MAY-10:50 | 779.69 | 284.62 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.16 |
June | 2435.88 | 27-JUN-13:20 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 15.35 | 0.00 |
July | 3028.85 | 21-JUL-13:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 20.01 | 0.00 |
August | 3365.74 | 18-AUG-13:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 16.02 | 0.00 |
September | 4131.44 | 21-SEP-13:00 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 2.86 | 0.00 |
October | 4031.29 | 11-OCT-12:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.93 |
November | 2391.26 | 03-NOV-12:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.20 |
December | 2107.58 | 17-DEC-11:35 | 779.69 | 341.54 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1962.90 | 259.90 | 113.85 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4131.44 | 779.69 | 341.54 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 20.01 | 74.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1061.85 | 17-JAN-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.14 |
February | 1069.98 | 22-FEB-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.76 |
March | 1340.02 | 15-MAR-18:10 | 6320.16 | 3164.06 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 0.00 |
April | 1282.18 | 21-APR-20:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.36 |
May | 1356.87 | 31-MAY-18:10 | 6320.16 | 3164.06 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.63 |
June | 1767.43 | 27-JUN-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 |
July | 1893.65 | 19-JUL-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.96 | 0.00 |
August | 1925.47 | 10-AUG-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.30 | 0.00 |
September | 1781.34 | 21-SEP-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 |
October | 1465.20 | 11-OCT-21:00 | 2407.68 | 1054.69 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.52 |
November | 1228.27 | 01-NOV-20:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.65 |
December | 1085.10 | 01-DEC-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1061.85 | 1053.36 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1925.47 | 6320.16 | 3164.06 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 2.96 | 21.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 750.54 | 17-JAN-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.34 |
February | 732.68 | 22-FEB-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.77 |
March | 988.77 | 15-MAR-18:10 | 1336.61 | 3648.94 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 2.92 | 0.00 |
April | 948.28 | 09-APR-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.09 |
May | 1055.37 | 27-MAY-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.44 |
June | 1193.07 | 27-JUN-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.73 |
July | 1656.08 | 21-JUL-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.84 |
August | 1379.26 | 10-AUG-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 | 0.00 |
September | 1167.78 | 16-SEP-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 | 0.00 |
October | 977.08 | 12-OCT-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.35 |
November | 890.79 | 05-NOV-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.01 |
December | 777.58 | 01-DEC-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 732.68 | 222.77 | 570.15 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1656.08 | 1336.61 | 3648.94 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 | 47.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 348.43 | 17-JAN-22:00 | 195.84 | 135.66 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 |
February | 307.82 | 22-FEB-22:00 | 195.84 | 135.66 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.71 |
March | 518.68 | 15-MAR-18:10 | 1028.16 | 813.94 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 0.00 |
April | 502.99 | 09-APR-10:33 | 220.32 | 152.61 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.84 |
May | 560.77 | 27-MAY-10:33 | 220.32 | 127.18 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.12 |
June | 632.57 | 29-JUN-10:35 | 97.92 | 84.79 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 2.29 | 0.00 |
July | 683.50 | 21-JUL-21:00 | 195.84 | 135.66 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.82 |
August | 656.82 | 10-AUG-10:35 | 97.92 | 84.79 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 0.00 |
September | 622.37 | 16-SEP-10:33 | 220.32 | 127.18 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 3.47 | 0.00 |
October | 514.33 | 22-OCT-10:33 | 220.32 | 152.61 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 |
November | 471.26 | 05-NOV-10:33 | 220.32 | 152.61 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.01 |
December | 389.46 | 01-DEC-21:00 | 171.36 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 307.82 | 97.92 | 84.79 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 683.50 | 1028.16 | 813.94 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 26.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36349.24 | 17-JAN-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 74.89 |
February | 36351.32 | 22-FEB-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 53.86 |
March | 37968.19 | 15-MAR-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 10.45 |
April | 37543.41 | 07-APR-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 24.87 |
May | 37990.90 | 23-MAY-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 10.46 |
June | 38453.89 | 27-JUN-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
July | 38711.16 | 21-JUL-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2.53 |
August | 38621.05 | 10-AUG-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 5.67 | 0.00 |
September | 38222.72 | 15-SEP-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 |
October | 37855.02 | 11-OCT-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 28.84 |
November | 37140.80 | 16-NOV-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 58.64 |
December | 36558.16 | 01-DEC-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 67.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36349.24 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38711.16 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 5.67 | 74.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8859.82 | 15-JAN-13:00 | 5122.80 | 115.39 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.28 |
February | 8534.00 | 28-FEB-13:40 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.37 |
March | 10821.71 | 15-MAR-13:30 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 9.75 | 0.00 |
April | 10361.86 | 22-APR-13:00 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.55 |
May | 9670.05 | 27-MAY-10:33 | 15368.40 | 288.47 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.23 |
June | 10405.97 | 27-JUN-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.98 |
July | 11256.98 | 20-JUL-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.48 | 0.00 |
August | 12064.44 | 17-AUG-15:03 | 51228.00 | 576.93 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 30.62 | 0.00 |
September | 14314.38 | 21-SEP-15:03 | 51228.00 | 576.93 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 0.00 |
October | 14367.80 | 11-OCT-12:30 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.10 |
November | 9858.59 | 03-NOV-12:30 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.34 |
December | 9477.78 | 17-DEC-11:35 | 10245.60 | 230.77 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8534.00 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14367.80 | 51228.00 | 1048.97 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 30.62 | 165.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24890.23 | 17-JAN-22:00 | 40553.76 | 9462.56 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.64 |
February | 25241.16 | 22-FEB-22:00 | 40553.76 | 9462.56 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.12 |
March | 33444.74 | 15-MAR-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.66 |
April | 29325.11 | 07-APR-21:55 | 182491.92 | 28387.68 | 29559.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.36 |
May | 33310.55 | 23-MAY-21:52 | 410606.82 | 63872.28 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.19 |
June | 38111.18 | 27-JUN-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.27 |
July | 40459.29 | 20-JUL-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 27.04 | 0.00 |
August | 40339.12 | 10-AUG-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 36.19 | 0.00 |
September | 38849.40 | 21-SEP-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.22 |
October | 35512.13 | 11-OCT-21:10 | 91245.96 | 14193.84 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.68 |
November | 28379.09 | 01-NOV-21:20 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.47 |
December | 25354.95 | 01-DEC-22:00 | 40553.76 | 9462.56 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24890.23 | 40553.76 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40459.29 | 410606.82 | 63872.28 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 36.19 | 376.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2362.27 | 12-JAN-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.24 |
February | 2851.82 | 28-FEB-16:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.74 |
March | 3000.26 | 15-MAR-15:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 4.92 | 0.00 |
April | 2895.63 | 23-APR-15:02 | 324.00 | 235.11 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.80 |
May | 3077.56 | 27-MAY-18:01 | 819.00 | 831.18 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 |
June | 3118.14 | 17-JUN-18:02 | 702.00 | 712.44 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 8.21 | 0.00 |
July | 3222.71 | 18-JUL-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 | 0.00 |
August | 3141.61 | 04-AUG-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 7.09 | 0.00 |
September | 2983.71 | 02-SEP-18:01 | 819.00 | 831.18 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.02 |
October | 2964.56 | 22-OCT-15:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.69 |
November | 2521.20 | 14-NOV-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.20 |
December | 2669.05 | 04-DEC-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2362.27 | 324.00 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3222.71 | 831.60 | 831.18 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 8.21 | 51.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 975.06 | 11-JAN-16:04 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.26 |
February | 1882.78 | 28-FEB-16:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.51 |
March | 2879.06 | 15-MAR-15:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 4.99 | 0.00 |
April | 3249.11 | 19-APR-18:11 | 1386.00 | 1056.67 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.73 |
May | 3294.47 | 03-MAY-18:01 | 1386.00 | 1056.67 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.11 |
June | 3301.43 | 14-JUN-20:11 | 1602.00 | 1056.67 | 1843.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.85 |
July | 3155.54 | 06-JUL-21:51 | 1800.00 | 795.47 | 921.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 |
August | 3209.66 | 02-AUG-21:51 | 1800.00 | 795.47 | 921.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 |
September | 2944.11 | 16-SEP-15:02 | 324.00 | 235.08 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6.57 | 0.00 |
October | 2941.83 | 11-OCT-15:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.95 |
November | 2365.56 | 05-NOV-15:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.56 |
December | 990.97 | 14-DEC-19:04 | 970.20 | 739.67 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 975.06 | 324.00 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3301.43 | 1800.00 | 1056.67 | 1843.57 | 0.00 | 0.00 | 0.00 | 0.00 | 6.57 | 37.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 95.07 | 15-JAN-15:20 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.70 |
February | 79.42 | 18-FEB-15:20 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.55 |
March | 492.88 | 15-MAR-13:30 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
April | 416.22 | 22-APR-13:00 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.88 |
May | 380.32 | 14-MAY-13:40 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.95 |
June | 429.37 | 12-JUN-13:20 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 | 0.00 |
July | 491.26 | 21-JUL-13:30 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 2.01 | 0.00 |
August | 557.76 | 18-AUG-13:30 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 | 0.00 |
September | 699.07 | 21-SEP-13:00 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.80 |
October | 711.14 | 11-OCT-12:30 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.23 |
November | 405.89 | 03-NOV-12:30 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.97 |
December | 108.72 | 04-DEC-15:20 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 79.42 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 711.14 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 2.01 | 12.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 585.15 | 15-JAN-09:01 | 378.00 | 292.60 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.38 |
February | 691.57 | 19-FEB-09:01 | 378.00 | 292.60 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 |
March | 927.15 | 15-MAR-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | 0.00 |
April | 857.70 | 07-APR-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.95 |
May | 917.99 | 13-MAY-15:01 | 378.00 | 172.43 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
June | 959.18 | 12-JUN-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 3.06 | 0.00 |
July | 959.71 | 21-JUL-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 3.38 | 0.00 |
August | 963.14 | 09-AUG-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2.94 | 0.00 |
September | 933.23 | 16-SEP-18:02 | 702.00 | 447.86 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 | 0.00 |
October | 865.73 | 22-OCT-15:01 | 378.00 | 172.43 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
November | 805.37 | 05-NOV-15:01 | 378.00 | 172.43 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.21 |
December | 749.62 | 03-DEC-09:01 | 378.00 | 292.60 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 585.15 | 378.00 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 963.14 | 702.00 | 447.86 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 3.38 | 10.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1538.20 | 15-JAN-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.41 |
February | 2452.82 | 28-FEB-09:01 | 252.00 | 365.72 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.67 |
March | 2787.52 | 15-MAR-15:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 4.86 | 0.00 |
April | 2641.10 | 23-APR-15:02 | 324.00 | 235.11 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.79 |
May | 2872.31 | 14-MAY-15:02 | 324.00 | 235.11 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 5.52 | 0.00 |
June | 2899.36 | 12-JUN-08:61 | 252.00 | 365.72 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 | 0.00 |
July | 2905.47 | 21-JUL-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 0.00 |
August | 2899.09 | 10-AUG-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 7.12 | 0.00 |
September | 2842.17 | 15-SEP-15:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 | 0.00 |
October | 2772.60 | 22-OCT-15:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.68 |
November | 2360.50 | 05-NOV-15:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.41 |
December | 1000.67 | 14-DEC-19:04 | 970.20 | 739.76 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1000.67 | 252.00 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2905.47 | 970.20 | 739.76 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 53.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 936.70 | 07-JAN-09:04 | 378.00 | 465.41 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.86 |
February | 1388.96 | 28-FEB-09:01 | 252.00 | 365.68 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.84 |
March | 2648.65 | 15-MAR-15:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 | 0.00 |
April | 2544.94 | 08-APR-15:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.86 |
May | 2885.47 | 31-MAY-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.10 |
June | 3254.37 | 30-JUN-08:32 | 216.00 | 313.44 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.20 |
July | 3262.69 | 14-JUL-08:32 | 180.00 | 261.20 | 566.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.40 |
August | 3365.82 | 05-AUG-08:32 | 324.00 | 398.92 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.77 |
September | 2955.86 | 09-SEP-08:51 | 540.00 | 664.87 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.09 |
October | 2661.31 | 11-OCT-15:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 |
November | 2219.74 | 05-NOV-15:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.93 |
December | 1044.48 | 17-DEC-09:03 | 378.00 | 465.41 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 936.70 | 180.00 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3365.82 | 680.40 | 664.87 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 | 52.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 960.31 | 17-JAN-22:20 | 2263.36 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.85 |
February | 1123.77 | 22-FEB-23:10 | 2263.36 | 386.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.85 |
March | 1658.67 | 15-MAR-18:10 | 10562.33 | 6186.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 | 0.00 |
April | 1678.18 | 22-APR-10:33 | 2263.36 | 966.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 |
May | 1869.91 | 27-MAY-10:33 | 2263.36 | 966.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.91 |
June | 2098.92 | 29-JUN-10:35 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.72 | 0.00 |
July | 2215.04 | 21-JUL-10:35 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.72 | 0.00 |
August | 2185.76 | 10-AUG-10:35 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.04 | 0.00 |
September | 2010.06 | 16-SEP-10:45 | 1508.90 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.60 | 0.00 |
October | 1678.97 | 11-OCT-10:33 | 1508.90 | 966.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.69 |
November | 1443.48 | 05-NOV-10:33 | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 |
December | 1053.72 | 17-DEC-13:00 | 754.45 | 386.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 960.31 | 754.45 | 386.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2215.04 | 10562.33 | 6186.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.72 | 40.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2486.24 | 15-JAN-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.93 |
February | 2958.45 | 28-FEB-16:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.74 |
March | 3134.65 | 14-MAR-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 2.85 | 0.00 |
April | 3031.59 | 23-APR-15:02 | 324.00 | 235.11 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.93 |
May | 3219.54 | 27-MAY-18:01 | 819.00 | 831.18 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.80 |
June | 3227.28 | 19-JUN-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
July | 3361.28 | 10-JUL-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 6.63 | 0.00 |
August | 3373.38 | 10-AUG-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 6.80 | 0.00 |
September | 3168.52 | 15-SEP-15:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 | 0.00 |
October | 3060.50 | 22-OCT-15:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 |
November | 2646.98 | 14-NOV-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.05 |
December | 2344.76 | 04-DEC-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2344.76 | 324.00 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3373.38 | 831.60 | 831.18 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 6.80 | 40.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1047.48 | 17-JAN-19:04 | 970.20 | 739.67 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.23 |
February | 962.39 | 15-FEB-09:04 | 252.00 | 365.68 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.14 |
March | 3051.42 | 15-MAR-15:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 | 0.00 |
April | 3490.66 | 19-APR-18:11 | 1386.00 | 1056.67 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.65 |
May | 3477.12 | 03-MAY-18:01 | 1386.00 | 1056.67 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 |
June | 3521.45 | 14-JUN-20:11 | 1602.00 | 1056.67 | 1843.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.60 |
July | 3405.50 | 06-JUL-21:51 | 1800.00 | 795.47 | 921.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.49 |
August | 3401.66 | 02-AUG-21:51 | 1800.00 | 795.47 | 921.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.91 |
September | 3073.99 | 11-SEP-19:31 | 1386.00 | 1187.26 | 1738.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.69 |
October | 3049.56 | 11-OCT-15:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 |
November | 2180.68 | 05-NOV-15:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.45 |
December | 1040.19 | 01-DEC-16:04 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 962.39 | 252.00 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3521.45 | 1800.00 | 1187.26 | 1843.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 | 25.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1619.80 | 12-JAN-16:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 |
February | 1614.27 | 28-FEB-16:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.59 |
March | 1682.06 | 15-MAR-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 0.00 |
April | 1592.92 | 22-APR-18:02 | 702.00 | 447.86 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.94 |
May | 1697.26 | 16-MAY-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.75 |
June | 1755.01 | 20-JUN-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 | 0.00 |
July | 1770.84 | 20-JUL-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 5.54 | 0.00 |
August | 1796.78 | 10-AUG-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 5.82 | 0.00 |
September | 1754.71 | 21-SEP-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 | 0.00 |
October | 1706.31 | 11-OCT-15:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 |
November | 1532.55 | 16-NOV-16:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.42 |
December | 1601.30 | 11-DEC-16:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1532.55 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1796.78 | 831.60 | 447.86 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 5.82 | 31.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16496.04 | 17-JAN-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.64 |
February | 16441.34 | 22-FEB-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.58 |
March | 20308.17 | 15-MAR-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 |
April | 19288.26 | 07-APR-21:55 | 107955.07 | 7368.33 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.21 |
May | 20817.12 | 23-MAY-21:52 | 242898.91 | 16578.74 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.37 |
June | 22086.53 | 27-JUN-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.44 |
July | 22783.89 | 20-JUL-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 | 0.00 |
August | 22453.26 | 10-AUG-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 6.06 | 0.00 |
September | 21280.76 | 15-SEP-21:53 | 188921.38 | 12894.57 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.35 |
October | 19600.89 | 12-OCT-21:44 | 134943.84 | 9210.41 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.75 |
November | 17867.50 | 16-NOV-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.51 |
December | 16847.96 | 01-DEC-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16441.34 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22783.89 | 242898.91 | 16578.74 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 6.06 | 85.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18522.55 | 17-JAN-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.64 |
February | 18480.50 | 22-FEB-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.58 |
March | 22035.70 | 15-MAR-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 |
April | 21140.44 | 07-APR-21:55 | 107955.07 | 7368.33 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.21 |
May | 22398.39 | 23-MAY-21:52 | 242898.91 | 16578.74 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.37 |
June | 23447.78 | 27-JUN-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.47 |
July | 24012.47 | 20-JUL-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 5.25 | 0.00 |
August | 23729.20 | 10-AUG-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.37 | 0.00 |
September | 22773.51 | 15-SEP-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.70 |
October | 21288.25 | 12-OCT-21:44 | 134943.84 | 9210.41 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.75 |
November | 19870.69 | 16-NOV-22:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.64 |
December | 18868.32 | 01-DEC-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18480.50 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24012.47 | 242898.91 | 16578.74 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 7.37 | 85.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25217.72 | 15-JAN-11:40 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 79.84 |
February | 24846.86 | 28-FEB-11:35 | 1067.42 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 101.90 |
March | 27872.75 | 14-MAR-10:45 | 1067.42 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 8.66 |
April | 28262.33 | 22-APR-10:33 | 2401.70 | 909.03 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 48.35 |
May | 28944.90 | 27-MAY-10:33 | 2401.70 | 909.03 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 17.39 |
June | 29433.28 | 12-JUN-10:40 | 1067.42 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 15.87 | 0.00 |
July | 30020.37 | 16-JUL-10:33 | 2401.70 | 1090.83 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 15.72 | 0.00 |
August | 29912.19 | 10-AUG-10:40 | 1067.42 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 15.91 | 0.00 |
September | 29023.95 | 09-SEP-10:33 | 2401.70 | 909.03 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 11.02 |
October | 27955.56 | 11-OCT-10:50 | 533.71 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 19.07 |
November | 26395.49 | 05-NOV-10:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 20.95 |
December | 25096.15 | 16-DEC-11:50 | 800.57 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 77.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 24846.86 | 533.71 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30020.37 | 2401.70 | 1090.83 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 15.91 | 101.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2601.00 | 15-JAN-11:50 | 798.48 | 409.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.50 |
February | 2521.20 | 18-FEB-14:30 | 1596.96 | 682.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.07 |
March | 3958.35 | 15-MAR-17:12 | 5323.20 | 3273.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.19 | 0.00 |
April | 3841.06 | 22-APR-10:33 | 2395.44 | 1023.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.08 |
May | 4306.77 | 27-MAY-10:33 | 2395.44 | 1023.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.74 |
June | 4813.83 | 29-JUN-10:35 | 1064.64 | 682.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.58 | 0.00 |
July | 6012.15 | 21-JUL-13:30 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 0.00 |
August | 5578.88 | 09-AUG-15:03 | 7984.80 | 2046.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 | 0.00 |
September | 4577.08 | 16-SEP-10:50 | 1596.96 | 682.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.97 | 0.00 |
October | 3905.28 | 11-OCT-10:50 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.63 |
November | 3382.58 | 27-NOV-11:33 | 1596.96 | 1023.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.72 |
December | 2910.56 | 17-DEC-11:35 | 1596.96 | 818.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2521.20 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6012.15 | 7984.80 | 3273.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 75.62 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.351119E+12 | 222767.01 | 17-JAN-20:10 | 0.719091E+12 | 587598.43 | 31-JAN-19:10 |
February | 0.315723E+12 | 217720.21 | 06-FEB-20:10 | 0.663840E+12 | 630256.95 | 06-FEB-19:10 |
March | 0.357993E+12 | 274883.96 | 15-MAR-19:49 | 0.594231E+12 | 551594.39 | 06-MAR-19:10 |
April | 0.346921E+12 | 240856.34 | 07-APR-19:00 | 0.505114E+12 | 516402.87 | 12-APR-17:00 |
May | 0.385010E+12 | 275351.27 | 23-MAY-19:40 | 0.505426E+12 | 500839.84 | 11-MAY-17:10 |
June | 0.456210E+12 | 355078.30 | 27-JUN-19:00 | 0.427212E+12 | 416110.41 | 13-JUN-21:10 |
July | 0.549952E+12 | 380185.47 | 20-JUL-19:49 | 0.413143E+12 | 350428.99 | 03-JUL-17:10 |
August | 0.509577E+12 | 351403.20 | 14-AUG-19:30 | 0.414631E+12 | 349456.38 | 04-AUG-17:10 |
September | 0.420043E+12 | 331498.16 | 15-SEP-19:00 | 0.440455E+12 | 434321.63 | 28-SEP-17:10 |
October | 0.366217E+12 | 249639.12 | 11-OCT-19:10 | 0.523344E+12 | 495197.33 | 26-OCT-16:00 |
November | 0.343395E+12 | 229463.34 | 01-NOV-19:49 | 0.516765E+12 | 501667.02 | 15-NOV-19:19 |
December | 0.351596E+12 | 223913.56 | 01-DEC-20:10 | 0.683580E+12 | 578667.76 | 11-DEC-19:19 |
Annual Sum or Average | 0.475376E+13 | 0.640683E+13 | ||||
Minimum of Months | 0.315723E+12 | 217720.21 | 0.413143E+12 | 349456.38 | ||
Maximum of Months | 0.549952E+12 | 380185.47 | 0.719091E+12 | 630256.95 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.519426E+11 | 0.183025E+11 | 0.146779E+12 | 0.544823E+11 | 0.404501E+11 | 0.197241E+10 | 0.00 | 0.334836E+09 | 0.00 | 0.00 | 0.254750E+11 | 0.770546E+10 | 0.00 |
February | 0.466945E+11 | 0.152732E+11 | 0.132565E+12 | 0.492098E+11 | 0.365137E+11 | 0.181867E+10 | 0.00 | 0.333251E+09 | 0.00 | 0.00 | 0.230349E+11 | 0.696301E+10 | 0.00 |
March | 0.513382E+11 | 0.151733E+11 | 0.146789E+12 | 0.544839E+11 | 0.409326E+11 | 0.607107E+10 | 0.00 | 0.103985E+11 | 0.00 | 0.00 | 0.214052E+11 | 0.770398E+10 | 0.00 |
April | 0.492505E+11 | 0.129296E+11 | 0.142011E+12 | 0.527241E+11 | 0.405579E+11 | 0.875225E+10 | 0.00 | 0.135016E+11 | 0.00 | 0.00 | 0.161461E+11 | 0.746558E+10 | 0.00 |
May | 0.505708E+11 | 0.118177E+11 | 0.146789E+12 | 0.544824E+11 | 0.447757E+11 | 0.124676E+11 | 0.00 | 0.474784E+11 | 0.00 | 0.00 | 0.519783E+10 | 0.770496E+10 | 0.00 |
June | 0.486779E+11 | 0.106925E+11 | 0.142058E+12 | 0.527255E+11 | 0.472139E+11 | 0.124836E+11 | 0.00 | 0.125368E+12 | 0.00 | 0.00 | 0.589642E+10 | 0.745711E+10 | 0.00 |
July | 0.503435E+11 | 0.113450E+11 | 0.146742E+12 | 0.544804E+11 | 0.512916E+11 | 0.133623E+11 | 0.00 | 0.201365E+12 | 0.00 | 0.00 | 0.955060E+10 | 0.771277E+10 | 0.00 |
August | 0.506772E+11 | 0.126699E+11 | 0.146800E+12 | 0.544835E+11 | 0.505130E+11 | 0.130945E+11 | 0.00 | 0.162028E+12 | 0.00 | 0.00 | 0.783848E+10 | 0.770456E+10 | 0.00 |
September | 0.495491E+11 | 0.139283E+11 | 0.142022E+12 | 0.527243E+11 | 0.455547E+11 | 0.122567E+11 | 0.00 | 0.894368E+11 | 0.00 | 0.00 | 0.347168E+10 | 0.746669E+10 | 0.00 |
October | 0.516192E+11 | 0.161919E+11 | 0.146768E+12 | 0.544821E+11 | 0.430156E+11 | 0.100326E+11 | 0.00 | 0.212931E+11 | 0.00 | 0.00 | 0.113898E+11 | 0.770361E+10 | 0.00 |
November | 0.502694E+11 | 0.172306E+11 | 0.142074E+12 | 0.527253E+11 | 0.397644E+11 | 0.541195E+10 | 0.00 | 0.602865E+10 | 0.00 | 0.00 | 0.188635E+11 | 0.744970E+10 | 0.00 |
December | 0.519611E+11 | 0.187219E+11 | 0.146742E+12 | 0.544815E+11 | 0.404621E+11 | 0.197045E+10 | 0.00 | 0.386167E+09 | 0.00 | 0.00 | 0.254747E+11 | 0.771361E+10 | 0.00 |
Annual Sum or Average | 0.602894E+12 | 0.174276E+12 | 0.172814E+13 | 0.641485E+12 | 0.521045E+12 | 0.996940E+11 | 0.00 | 0.677952E+12 | 0.00 | 0.00 | 0.173744E+12 | 0.907511E+11 | 0.00 |
Minimum of Months | 0.466945E+11 | 0.106925E+11 | 0.132565E+12 | 0.492098E+11 | 0.365137E+11 | 0.181867E+10 | 0.00 | 0.333251E+09 | 0.00 | 0.00 | 0.347168E+10 | 0.696301E+10 | 0.00 |
Maximum of Months | 0.519611E+11 | 0.187219E+11 | 0.146800E+12 | 0.544839E+11 | 0.512916E+11 | 0.133623E+11 | 0.00 | 0.201365E+12 | 0.00 | 0.00 | 0.254750E+11 | 0.771361E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.269968E+12 | 0.00 | 0.297205E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.255741E+12 | 0.00 | 0.270895E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.144673E+12 | 0.00 | 0.297534E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.787137E+11 | 0.00 | 0.279444E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.759536E+11 | 0.00 | 0.277494E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.225910E+11 | 0.00 | 0.257507E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.368739E+10 | 0.00 | 0.257635E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.816552E+10 | 0.00 | 0.254426E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.444936E+11 | 0.00 | 0.248990E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.105992E+12 | 0.00 | 0.265449E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.101853E+12 | 0.00 | 0.267821E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.243648E+12 | 0.00 | 0.288111E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.135548E+13 | 0.00 | 0.326251E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.368739E+10 | 0.00 | 0.248990E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.269968E+12 | 0.00 | 0.297534E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 50471.22 | 02-JAN-20:10 | 11096.45 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 39155.93 | 02-JAN-07:19 | 21356.65 | 23-JAN-19:10 | 5244.84 | 30-JAN-16:30 | 0.00 | 01-JAN-00:10 |
February | 50471.22 | 01-FEB-20:10 | 11096.45 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 39155.93 | 01-FEB-07:19 | 22150.07 | 06-FEB-19:10 | 5179.91 | 08-FEB-16:10 | 0.00 | 01-FEB-00:10 |
March | 50471.22 | 01-MAR-20:10 | 11096.45 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 39155.93 | 13-MAR-06:19 | 29054.95 | 15-MAR-21:00 | 5139.57 | 07-MAR-09:09 | 0.00 | 01-MAR-00:10 |
April | 50471.22 | 03-APR-19:10 | 11096.45 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 39155.38 | 10-APR-06:19 | 25849.35 | 07-APR-21:00 | 5058.18 | 28-APR-22:40 | 0.00 | 01-APR-00:10 |
May | 50471.22 | 01-MAY-19:10 | 11096.45 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 39154.79 | 12-MAY-06:19 | 30147.35 | 23-MAY-21:00 | 5141.80 | 31-MAY-15:09 | 0.00 | 01-MAY-00:10 |
June | 50471.22 | 01-JUN-19:49 | 11096.45 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 39154.51 | 26-JUN-06:19 | 33246.51 | 12-JUN-21:00 | 6266.34 | 17-JUN-18:00 | 0.00 | 01-JUN-00:10 |
July | 50471.22 | 03-JUL-19:00 | 11096.45 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 39154.98 | 21-JUL-06:19 | 34158.96 | 17-JUL-21:00 | 6827.19 | 21-JUL-19:00 | 0.00 | 01-JUL-00:10 |
August | 50471.22 | 01-AUG-19:40 | 11096.45 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 39155.44 | 28-AUG-06:19 | 34099.16 | 10-AUG-21:10 | 5891.56 | 14-AUG-21:00 | 0.00 | 01-AUG-00:10 |
September | 50471.22 | 01-SEP-19:10 | 11096.45 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 39155.93 | 26-SEP-06:19 | 33970.37 | 21-SEP-21:00 | 5782.92 | 15-SEP-19:00 | 0.00 | 01-SEP-00:10 |
October | 50471.22 | 02-OCT-19:10 | 11096.45 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 39155.93 | 02-OCT-06:19 | 31621.66 | 11-OCT-21:49 | 5133.85 | 11-OCT-15:09 | 0.00 | 01-OCT-00:10 |
November | 50471.22 | 01-NOV-19:10 | 11096.45 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 39155.93 | 01-NOV-06:19 | 23332.15 | 01-NOV-21:10 | 5080.15 | 10-NOV-17:19 | 0.00 | 01-NOV-00:10 |
December | 50471.22 | 01-DEC-20:10 | 11096.45 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 39155.93 | 01-DEC-07:19 | 21871.28 | 01-DEC-21:10 | 5305.47 | 10-DEC-16:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 50471.22 | 11096.45 | 88863.15 | 39154.51 | 21356.65 | 5058.18 | 0.00 | |||||||
Maximum of Months | 50471.22 | 11096.45 | 88863.15 | 39155.93 | 34158.96 | 6827.19 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 5138.05 | 15-JAN-16:10 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 4738.27 | 10-JAN-07:19 | 0.00 |
February | 6792.91 | 28-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:20 | 4738.64 | 06-FEB-19:10 | 0.00 |
March | 85169.37 | 15-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:20 | 4738.36 | 27-MAR-18:10 | 0.00 |
April | 55604.00 | 08-APR-15:09 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 4738.42 | 26-APR-18:10 | 0.00 |
May | 91324.60 | 10-MAY-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAY-00:10 | 4738.68 | 15-MAY-18:10 | 0.00 |
June | 136891.58 | 27-JUN-20:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-15:30 | 4738.32 | 07-JUN-18:10 | 0.00 |
July | 153064.00 | 20-JUL-18:19 | 0.00 | 0.00 | 9938.94 | 01-JUL-15:30 | 4738.29 | 10-JUL-18:10 | 0.00 |
August | 145653.31 | 13-AUG-15:20 | 0.00 | 0.00 | 9938.94 | 01-AUG-12:00 | 4738.26 | 10-AUG-06:30 | 0.00 |
September | 114971.28 | 15-SEP-20:19 | 0.00 | 0.00 | 9938.94 | 03-SEP-02:49 | 4738.75 | 11-SEP-18:10 | 0.00 |
October | 76011.86 | 11-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 02-OCT-03:30 | 4738.63 | 02-OCT-18:10 | 0.00 |
November | 36611.42 | 05-NOV-08:00 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 4738.31 | 09-NOV-19:19 | 0.00 |
December | 4285.35 | 01-DEC-19:10 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 4738.06 | 21-DEC-07:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4285.35 | 0.00 | 0.00 | 9938.94 | 4738.06 | 0.00 | |||
Maximum of Months | 153064.00 | 0.00 | 0.00 | 9938.94 | 4738.75 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 222767.01 | 17-JAN-20:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 19685.91 | 4742.29 | 0.00 | 1956.85 | 0.00 |
February | 217720.21 | 06-FEB-20:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 20342.26 | 853.07 | 0.00 | 0.00 | 0.00 |
March | 274883.96 | 15-MAR-19:49 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 22694.10 | 4876.80 | 0.00 | 60427.80 | 0.00 |
April | 240856.34 | 07-APR-19:00 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 21029.55 | 4627.09 | 0.00 | 28983.74 | 0.00 |
May | 275351.27 | 23-MAY-19:40 | 50471.22 | 87982.85 | 11096.45 | 31577.52 | 22549.35 | 4742.67 | 0.00 | 61676.19 | 0.00 |
June | 355078.30 | 27-JUN-19:00 | 50471.22 | 87982.85 | 11096.45 | 31577.59 | 28962.29 | 5944.62 | 0.00 | 124036.17 | 0.00 |
July | 380185.47 | 20-JUL-19:49 | 50471.22 | 87982.85 | 11096.45 | 31577.74 | 28453.54 | 6296.88 | 0.00 | 148752.47 | 0.00 |
August | 351403.20 | 14-AUG-19:30 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 27684.83 | 5841.67 | 0.00 | 121105.82 | 0.00 |
September | 331498.16 | 15-SEP-19:00 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 24683.85 | 5782.92 | 0.00 | 114927.69 | 0.00 |
October | 249639.12 | 11-OCT-19:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 23674.93 | 4667.86 | 0.00 | 34886.24 | 0.00 |
November | 229463.34 | 01-NOV-19:49 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 21840.41 | 4623.38 | 0.00 | 6332.90 | 0.00 |
December | 223913.56 | 01-DEC-20:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 20656.07 | 4712.99 | 0.00 | 2387.35 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 217720.21 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 19685.91 | 853.07 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 380185.47 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 28962.29 | 6296.88 | 0.00 | 148752.47 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 265355.18 | 31-JAN-16:10 | 0.00 | 296596.15 | 31-JAN-21:49 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 303857.23 | 06-FEB-09:09 | 0.00 | 297125.46 | 13-FEB-21:49 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 194896.16 | 07-MAR-07:19 | 0.00 | 296653.94 | 01-MAR-21:40 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 164250.98 | 29-APR-22:40 | 0.00 | 291555.16 | 06-APR-20:40 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 146927.14 | 11-MAY-20:10 | 0.00 | 285001.61 | 01-MAY-20:00 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 145374.02 | 13-JUN-08:09 | 0.00 | 256170.13 | 02-JUN-20:00 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 58324.93 | 13-JUL-03:00 | 0.00 | 246821.76 | 03-JUL-20:40 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 88108.29 | 31-AUG-04:00 | 0.00 | 245900.34 | 04-AUG-20:10 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 136013.01 | 30-SEP-06:30 | 0.00 | 246752.83 | 29-SEP-20:30 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 169927.53 | 19-OCT-08:39 | 0.00 | 256369.36 | 31-OCT-20:30 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 172985.60 | 13-NOV-16:10 | 0.00 | 284020.44 | 29-NOV-21:00 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 278056.18 | 11-DEC-09:09 | 0.00 | 291968.84 | 29-DEC-21:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 58324.93 | 0.00 | 245900.34 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 303857.23 | 0.00 | 297125.46 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.75 | 0.50 | 21.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.80 | 1.00 | 21.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.76 | 1.33 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.75 | 1.00 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.77 | 3.17 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.82 | 1.50 | 21.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.67 | 21.77 | 8.67 | 21.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.82 | 3.17 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.78 | 0.33 | 21.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 22.04 | 1.67 | 22.04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.84 | 4.00 | 21.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.76 | 4.00 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.78 | 2.17 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.80 | 0.83 | 21.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 13.00 | 21.83 | 13.00 | 21.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 22.04 | 4.00 | 22.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.52 | 0.17 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
February | 0.33 | 20.52 | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.76 | 0.17 | 21.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.78 | 3.50 | 21.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 21.85 | 11.83 | 21.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 21.84 | 17.50 | 21.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 21.81 | 10.67 | 21.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.80 | 4.83 | 21.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 20.53 | 0.67 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Annual Sum or Average | 1.17 | 20.53 | 1.17 | 20.53 | 48.83 | 21.77 | 48.83 | 21.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.53 | 0.67 | 20.53 | 17.50 | 21.85 | 17.50 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.75 | 0.50 | 21.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.72 | 1.00 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.74 | 0.67 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.67 | 21.73 | 2.67 | 21.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.75 | 1.00 | 21.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 22.01 | 0.50 | 22.01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 22.10 | 5.67 | 22.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 22.22 | 10.17 | 22.22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 22.23 | 7.17 | 22.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 22.08 | 0.67 | 22.08 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 24.33 | 22.19 | 24.33 | 22.19 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 22.23 | 10.17 | 22.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.80 | 0.50 | 21.80 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.79 | 1.00 | 21.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.76 | 2.83 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.76 | 2.33 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.82 | 3.50 | 21.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.85 | 1.67 | 21.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.00 | 21.79 | 12.00 | 21.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.85 | 3.50 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.91 | 0.33 | 21.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 22.17 | 2.17 | 22.17 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 21.89 | 6.00 | 21.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 21.80 | 6.17 | 21.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.81 | 4.00 | 21.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.99 | 1.00 | 21.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 19.67 | 21.88 | 19.67 | 21.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 22.17 | 6.17 | 22.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.75 | 0.50 | 21.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.81 | 1.00 | 21.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.71 | 0.67 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.74 | 3.17 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.85 | 2.67 | 21.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 22.05 | 1.83 | 22.05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.82 | 0.17 | 21.82 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.33 | 21.83 | 10.33 | 21.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 22.05 | 3.17 | 22.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 23.01 | 0.00 | 23.01 | 0.00 | 23.01 |
February | 672.00 | 22.74 | 0.00 | 22.74 | 0.00 | 22.74 |
March | 744.00 | 22.13 | 0.00 | 22.13 | 0.00 | 22.13 |
April | 720.00 | 21.94 | 0.00 | 21.94 | 0.00 | 21.94 |
May | 744.00 | 21.85 | 0.00 | 21.85 | 0.00 | 21.85 |
June | 720.00 | 22.38 | 3.50 | 22.38 | 3.50 | 22.38 |
July | 744.00 | 22.80 | 1.83 | 22.80 | 1.83 | 22.80 |
August | 479.33 | 23.21 | 33.83 | 23.25 | 7.67 | 23.25 |
September | 267.00 | 23.56 | 156.50 | 23.70 | 16.83 | 23.70 |
October | 401.50 | 23.78 | 20.33 | 23.79 | 0.00 | 23.79 |
November | 591.33 | 23.80 | 0.00 | 23.80 | 0.00 | 23.80 |
December | 735.67 | 23.60 | 0.00 | 23.60 | 0.00 | 23.60 |
Annual Sum or Average | 7562.83 | 22.79 | 216.00 | 22.82 | 29.83 | 22.83 |
Minimum of Months | 267.00 | 21.85 | 0.00 | 21.85 | 0.00 | 21.85 |
Maximum of Months | 744.00 | 23.80 | 156.50 | 23.80 | 16.83 | 23.80 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 741.67 | 21.05 | 611.00 | 21.03 | 611.00 | 21.02 |
February | 669.67 | 21.06 | 516.17 | 21.03 | 516.17 | 21.02 |
March | 720.00 | 21.21 | 216.67 | 21.19 | 209.50 | 21.15 |
April | 692.17 | 21.25 | 27.00 | 21.24 | 27.00 | 21.23 |
May | 703.67 | 21.45 | 9.00 | 21.48 | 0.00 | 21.48 |
June | 578.83 | 21.91 | 70.83 | 22.08 | 0.00 | 22.08 |
July | 416.17 | 22.18 | 213.67 | 22.65 | 0.00 | 22.65 |
August | 451.17 | 22.10 | 199.67 | 22.58 | 0.00 | 22.58 |
September | 559.33 | 21.73 | 111.50 | 22.07 | 0.00 | 22.07 |
October | 685.17 | 21.28 | 47.50 | 21.41 | 10.17 | 21.41 |
November | 706.67 | 21.12 | 155.00 | 21.10 | 155.00 | 21.08 |
December | 740.00 | 21.05 | 572.33 | 21.03 | 572.33 | 21.02 |
Annual Sum or Average | 7664.50 | 21.39 | 2750.33 | 21.45 | 2101.17 | 21.37 |
Minimum of Months | 416.17 | 21.05 | 9.00 | 21.03 | 0.00 | 21.02 |
Maximum of Months | 741.67 | 22.18 | 611.00 | 22.65 | 611.00 | 22.65 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.32 | 121.17 | 21.28 | 121.17 | 21.24 |
February | 672.00 | 21.32 | 69.67 | 21.29 | 69.67 | 21.26 |
March | 736.83 | 21.91 | 0.00 | 21.91 | 0.00 | 21.91 |
April | 720.00 | 22.28 | 0.00 | 22.28 | 0.00 | 22.28 |
May | 714.33 | 22.71 | 1.50 | 22.72 | 0.00 | 22.72 |
June | 463.67 | 23.03 | 178.17 | 23.25 | 56.17 | 23.28 |
July | 273.83 | 23.28 | 383.50 | 23.61 | 100.67 | 23.64 |
August | 283.00 | 23.18 | 298.17 | 23.53 | 73.00 | 23.56 |
September | 509.67 | 22.97 | 115.17 | 23.11 | 40.00 | 23.14 |
October | 721.17 | 22.46 | 4.17 | 22.47 | 0.00 | 22.47 |
November | 720.00 | 22.00 | 0.00 | 22.00 | 0.00 | 22.00 |
December | 744.00 | 21.37 | 78.33 | 21.34 | 78.33 | 21.31 |
Annual Sum or Average | 7302.50 | 22.16 | 1249.83 | 22.32 | 539.00 | 22.32 |
Minimum of Months | 273.83 | 21.32 | 0.00 | 21.28 | 0.00 | 21.24 |
Maximum of Months | 744.00 | 23.28 | 383.50 | 23.61 | 121.17 | 23.64 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 465.33 | 21.00 | 465.33 | 21.00 |
February | 672.00 | 21.00 | 441.33 | 21.00 | 441.33 | 21.00 |
March | 744.00 | 21.22 | 223.67 | 21.17 | 223.67 | 21.14 |
April | 720.00 | 21.43 | 11.33 | 21.43 | 11.33 | 21.42 |
May | 744.00 | 22.19 | 0.00 | 22.19 | 0.00 | 22.19 |
June | 633.00 | 22.94 | 7.83 | 22.96 | 0.00 | 22.96 |
July | 335.67 | 23.24 | 111.33 | 23.41 | 0.00 | 23.41 |
August | 468.50 | 23.27 | 34.00 | 23.31 | 0.00 | 23.31 |
September | 684.50 | 22.82 | 0.00 | 22.82 | 0.00 | 22.82 |
October | 744.00 | 21.84 | 0.00 | 21.84 | 0.00 | 21.84 |
November | 720.00 | 21.27 | 4.50 | 21.27 | 4.50 | 21.27 |
December | 744.00 | 21.01 | 314.00 | 21.01 | 314.00 | 21.01 |
Annual Sum or Average | 7953.67 | 21.82 | 1613.33 | 21.72 | 1460.17 | 21.63 |
Minimum of Months | 335.67 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 23.27 | 465.33 | 23.41 | 465.33 | 23.41 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 513.17 | 21.00 | 513.17 | 21.00 |
February | 672.00 | 21.00 | 496.17 | 21.00 | 496.17 | 21.00 |
March | 744.00 | 21.14 | 268.50 | 21.10 | 268.50 | 21.08 |
April | 720.00 | 21.26 | 25.33 | 21.25 | 25.33 | 21.25 |
May | 744.00 | 21.98 | 0.00 | 21.98 | 0.00 | 21.98 |
June | 698.83 | 22.83 | 0.00 | 22.83 | 0.00 | 22.83 |
July | 474.33 | 23.18 | 37.17 | 23.23 | 0.00 | 23.23 |
August | 605.50 | 23.18 | 0.00 | 23.18 | 0.00 | 23.18 |
September | 709.67 | 22.65 | 0.00 | 22.65 | 0.00 | 22.65 |
October | 744.00 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
November | 720.00 | 21.13 | 16.83 | 21.13 | 16.83 | 21.12 |
December | 744.00 | 21.00 | 359.50 | 21.00 | 359.50 | 21.00 |
Annual Sum or Average | 8320.33 | 21.77 | 1716.67 | 21.65 | 1679.50 | 21.55 |
Minimum of Months | 474.33 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 23.18 | 513.17 | 23.23 | 513.17 | 23.23 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 347.67 | 22.38 | 353.50 | 23.05 | 123.67 | 23.19 |
February | 289.00 | 22.37 | 307.83 | 23.08 | 108.83 | 23.22 |
March | 274.17 | 22.79 | 443.00 | 23.21 | 156.50 | 23.35 |
April | 258.67 | 22.98 | 514.17 | 23.21 | 167.67 | 23.35 |
May | 295.83 | 23.31 | 593.83 | 23.25 | 226.67 | 23.40 |
June | 290.50 | 23.76 | 653.00 | 23.26 | 268.50 | 23.42 |
July | 307.50 | 23.93 | 715.50 | 23.25 | 304.00 | 23.41 |
August | 306.00 | 23.91 | 698.50 | 23.28 | 299.50 | 23.44 |
September | 294.67 | 23.68 | 641.33 | 23.28 | 264.33 | 23.43 |
October | 277.83 | 23.19 | 566.83 | 23.25 | 200.17 | 23.39 |
November | 253.83 | 22.84 | 470.17 | 23.22 | 149.17 | 23.35 |
December | 325.33 | 22.42 | 366.17 | 23.08 | 125.83 | 23.22 |
Annual Sum or Average | 3521.00 | 23.12 | 6323.83 | 23.21 | 2394.83 | 23.36 |
Minimum of Months | 253.83 | 22.37 | 307.83 | 23.05 | 108.83 | 23.19 |
Maximum of Months | 347.67 | 23.93 | 715.50 | 23.28 | 304.00 | 23.44 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 737.67 | 21.32 | 207.00 | 21.26 | 204.67 | 21.22 |
February | 663.17 | 21.32 | 155.33 | 21.26 | 154.50 | 21.22 |
March | 663.83 | 21.85 | 40.67 | 21.93 | 6.00 | 21.93 |
April | 652.00 | 22.10 | 18.50 | 22.15 | 0.00 | 22.15 |
May | 597.00 | 22.44 | 65.50 | 22.54 | 14.67 | 22.55 |
June | 379.67 | 22.90 | 327.50 | 23.19 | 132.17 | 23.28 |
July | 299.50 | 23.46 | 601.17 | 23.52 | 243.17 | 23.57 |
August | 250.67 | 23.19 | 535.50 | 23.52 | 147.83 | 23.57 |
September | 348.50 | 22.72 | 357.83 | 23.19 | 101.50 | 23.24 |
October | 576.83 | 22.09 | 107.17 | 22.36 | 6.33 | 22.37 |
November | 685.17 | 21.84 | 15.17 | 21.88 | 0.83 | 21.88 |
December | 734.33 | 21.32 | 175.50 | 21.28 | 170.67 | 21.24 |
Annual Sum or Average | 6588.33 | 22.01 | 2606.83 | 22.31 | 1182.33 | 22.33 |
Minimum of Months | 250.67 | 21.32 | 15.17 | 21.26 | 0.00 | 21.22 |
Maximum of Months | 737.67 | 23.46 | 601.17 | 23.52 | 243.17 | 23.57 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.83 | 4.67 | 21.82 | 4.67 | 21.82 |
February | 672.00 | 21.82 | 12.67 | 21.81 | 12.67 | 21.79 |
March | 703.50 | 22.39 | 20.50 | 22.44 | 0.00 | 22.44 |
April | 684.17 | 22.68 | 0.50 | 22.69 | 0.00 | 22.69 |
May | 542.00 | 22.88 | 50.17 | 22.96 | 14.50 | 22.98 |
June | 343.83 | 23.24 | 300.17 | 23.53 | 118.17 | 23.59 |
July | 273.50 | 23.75 | 548.50 | 23.78 | 225.67 | 23.82 |
August | 202.83 | 23.55 | 511.67 | 23.76 | 128.33 | 23.79 |
September | 300.50 | 23.22 | 297.67 | 23.54 | 93.67 | 23.59 |
October | 579.17 | 22.78 | 63.67 | 22.89 | 3.50 | 22.89 |
November | 709.17 | 22.51 | 0.00 | 22.51 | 0.00 | 22.51 |
December | 744.00 | 21.87 | 0.83 | 21.87 | 0.83 | 21.86 |
Annual Sum or Average | 6498.67 | 22.50 | 1811.00 | 22.79 | 602.00 | 22.86 |
Minimum of Months | 202.83 | 21.82 | 0.00 | 21.81 | 0.00 | 21.79 |
Maximum of Months | 744.00 | 23.75 | 548.50 | 23.78 | 225.67 | 23.82 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.62 | 696.67 | 20.60 | 696.67 | 20.60 |
February | 672.00 | 20.67 | 600.67 | 20.64 | 600.67 | 20.62 |
March | 740.67 | 21.14 | 245.17 | 21.06 | 245.17 | 21.02 |
April | 714.33 | 21.36 | 28.17 | 21.34 | 28.17 | 21.31 |
May | 710.00 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
June | 631.67 | 21.49 | 7.83 | 21.51 | 1.50 | 21.51 |
July | 613.67 | 21.40 | 15.67 | 21.44 | 1.33 | 21.45 |
August | 627.33 | 21.42 | 20.17 | 21.48 | 1.17 | 21.48 |
September | 657.50 | 21.51 | 6.33 | 21.53 | 1.00 | 21.53 |
October | 734.50 | 21.33 | 20.50 | 21.31 | 20.33 | 21.30 |
November | 720.00 | 21.02 | 232.50 | 20.91 | 232.50 | 20.84 |
December | 744.00 | 20.63 | 649.17 | 20.59 | 649.17 | 20.58 |
Annual Sum or Average | 8309.67 | 21.16 | 2522.83 | 21.05 | 2477.67 | 20.96 |
Minimum of Months | 613.67 | 20.62 | 0.00 | 20.59 | 0.00 | 20.58 |
Maximum of Months | 744.00 | 21.54 | 696.67 | 21.54 | 696.67 | 21.54 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.52 | 727.50 | 20.51 | 727.50 | 20.51 |
February | 672.00 | 20.54 | 649.67 | 20.53 | 649.67 | 20.53 |
March | 744.00 | 20.93 | 370.33 | 20.82 | 370.33 | 20.76 |
April | 716.33 | 21.26 | 49.83 | 21.22 | 49.17 | 21.19 |
May | 679.00 | 21.70 | 38.83 | 21.92 | 5.67 | 21.97 |
June | 548.33 | 22.09 | 134.83 | 22.74 | 50.67 | 22.96 |
July | 553.83 | 21.98 | 140.00 | 22.53 | 65.83 | 22.72 |
August | 577.50 | 21.99 | 106.00 | 22.42 | 53.00 | 22.59 |
September | 618.33 | 21.81 | 79.17 | 22.14 | 25.67 | 22.19 |
October | 740.00 | 21.22 | 60.67 | 21.18 | 58.50 | 21.13 |
November | 720.00 | 20.83 | 333.33 | 20.73 | 333.33 | 20.68 |
December | 744.00 | 20.54 | 706.00 | 20.53 | 706.00 | 20.52 |
Annual Sum or Average | 8057.33 | 21.23 | 3396.17 | 21.22 | 3095.33 | 21.13 |
Minimum of Months | 548.33 | 20.52 | 38.83 | 20.51 | 5.67 | 20.51 |
Maximum of Months | 744.00 | 22.09 | 727.50 | 22.74 | 727.50 | 22.96 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.84 | 487.67 | 20.79 | 487.67 | 20.77 |
February | 672.00 | 20.87 | 454.33 | 20.83 | 454.33 | 20.81 |
March | 744.00 | 21.13 | 211.00 | 21.06 | 211.00 | 21.01 |
April | 720.00 | 21.35 | 1.00 | 21.35 | 1.00 | 21.35 |
May | 744.00 | 21.71 | 0.00 | 21.71 | 0.00 | 21.71 |
June | 702.83 | 22.08 | 30.67 | 22.14 | 27.50 | 22.18 |
July | 720.17 | 22.16 | 67.50 | 22.30 | 60.83 | 22.40 |
August | 737.50 | 22.13 | 44.00 | 22.21 | 44.00 | 22.28 |
September | 717.83 | 21.89 | 23.83 | 21.94 | 23.67 | 21.99 |
October | 744.00 | 21.36 | 1.50 | 21.36 | 1.50 | 21.36 |
November | 720.00 | 21.14 | 18.50 | 21.12 | 18.50 | 21.10 |
December | 744.00 | 20.87 | 363.50 | 20.80 | 363.50 | 20.76 |
Annual Sum or Average | 8710.33 | 21.46 | 1703.50 | 21.39 | 1693.50 | 21.33 |
Minimum of Months | 672.00 | 20.84 | 0.00 | 20.79 | 0.00 | 20.76 |
Maximum of Months | 744.00 | 22.16 | 487.67 | 22.30 | 487.67 | 22.40 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.64 | 676.50 | 20.61 | 676.50 | 20.60 |
February | 672.00 | 20.69 | 586.83 | 20.66 | 586.83 | 20.65 |
March | 742.33 | 21.21 | 237.83 | 21.14 | 237.83 | 21.09 |
April | 719.67 | 21.46 | 21.17 | 21.45 | 21.17 | 21.43 |
May | 716.00 | 21.60 | 0.00 | 21.60 | 0.00 | 21.60 |
June | 613.83 | 21.46 | 3.50 | 21.47 | 0.83 | 21.47 |
July | 585.00 | 21.32 | 8.17 | 21.35 | 1.17 | 21.35 |
August | 609.67 | 21.39 | 7.83 | 21.41 | 0.83 | 21.41 |
September | 633.83 | 21.47 | 1.50 | 21.47 | 1.00 | 21.47 |
October | 739.17 | 21.40 | 16.00 | 21.39 | 16.00 | 21.38 |
November | 720.00 | 21.03 | 227.33 | 20.91 | 227.33 | 20.84 |
December | 744.00 | 20.62 | 648.67 | 20.59 | 648.67 | 20.58 |
Annual Sum or Average | 8239.50 | 21.18 | 2435.33 | 21.06 | 2418.17 | 20.98 |
Minimum of Months | 585.00 | 20.62 | 0.00 | 20.59 | 0.00 | 20.58 |
Maximum of Months | 744.00 | 21.60 | 676.50 | 21.60 | 676.50 | 21.60 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.53 | 721.67 | 20.52 | 721.67 | 20.52 |
February | 672.00 | 20.56 | 649.17 | 20.55 | 649.17 | 20.55 |
March | 744.00 | 20.98 | 366.33 | 20.89 | 366.33 | 20.85 |
April | 720.00 | 21.39 | 33.17 | 21.37 | 33.17 | 21.35 |
May | 730.00 | 21.84 | 2.83 | 21.85 | 0.33 | 21.85 |
June | 553.33 | 21.95 | 81.00 | 22.28 | 31.67 | 22.37 |
July | 495.67 | 21.91 | 141.00 | 22.53 | 69.50 | 22.77 |
August | 530.83 | 21.86 | 105.50 | 22.30 | 49.33 | 22.44 |
September | 683.00 | 21.99 | 31.17 | 22.08 | 24.83 | 22.13 |
October | 744.00 | 21.30 | 39.17 | 21.27 | 39.17 | 21.25 |
November | 720.00 | 20.83 | 328.67 | 20.73 | 328.67 | 20.68 |
December | 744.00 | 20.54 | 698.17 | 20.52 | 698.17 | 20.52 |
Annual Sum or Average | 8080.83 | 21.26 | 3197.83 | 21.19 | 3012.00 | 21.10 |
Minimum of Months | 495.67 | 20.53 | 2.83 | 20.52 | 0.33 | 20.52 |
Maximum of Months | 744.00 | 21.99 | 721.67 | 22.53 | 721.67 | 22.77 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 464.50 | 21.00 | 464.50 | 21.00 |
February | 672.00 | 21.00 | 413.33 | 21.00 | 413.33 | 21.00 |
March | 744.00 | 21.10 | 158.17 | 21.08 | 158.17 | 21.07 |
April | 720.00 | 21.32 | 0.00 | 21.32 | 0.00 | 21.32 |
May | 744.00 | 22.06 | 0.00 | 22.06 | 0.00 | 22.06 |
June | 696.67 | 22.95 | 59.83 | 22.97 | 59.83 | 22.98 |
July | 496.83 | 23.35 | 146.83 | 23.40 | 128.17 | 23.42 |
August | 579.50 | 23.26 | 86.50 | 23.28 | 81.17 | 23.29 |
September | 720.00 | 22.69 | 41.17 | 22.69 | 41.17 | 22.70 |
October | 744.00 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
November | 720.00 | 21.04 | 24.17 | 21.04 | 24.17 | 21.04 |
December | 744.00 | 21.00 | 332.50 | 21.00 | 332.50 | 21.00 |
Annual Sum or Average | 8325.00 | 21.78 | 1727.00 | 21.72 | 1703.00 | 21.68 |
Minimum of Months | 496.83 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 23.35 | 464.50 | 23.40 | 464.50 | 23.42 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.54 | 729.50 | 20.53 | 729.50 | 20.53 |
February | 672.00 | 20.58 | 647.83 | 20.56 | 647.83 | 20.56 |
March | 738.50 | 21.01 | 349.67 | 20.92 | 349.67 | 20.87 |
April | 708.33 | 21.28 | 93.17 | 21.21 | 93.17 | 21.16 |
May | 698.17 | 21.48 | 5.00 | 21.49 | 2.00 | 21.49 |
June | 613.33 | 21.43 | 29.67 | 21.50 | 5.83 | 21.51 |
July | 598.83 | 21.35 | 47.17 | 21.48 | 8.33 | 21.50 |
August | 610.00 | 21.36 | 45.00 | 21.49 | 5.17 | 21.50 |
September | 638.83 | 21.43 | 37.17 | 21.47 | 25.67 | 21.47 |
October | 729.50 | 21.23 | 98.83 | 21.18 | 98.17 | 21.15 |
November | 720.00 | 20.90 | 373.50 | 20.79 | 373.50 | 20.74 |
December | 744.00 | 20.56 | 709.67 | 20.54 | 709.67 | 20.54 |
Annual Sum or Average | 8215.50 | 21.08 | 3166.17 | 20.97 | 3048.50 | 20.89 |
Minimum of Months | 598.83 | 20.54 | 5.00 | 20.53 | 2.00 | 20.53 |
Maximum of Months | 744.00 | 21.48 | 729.50 | 21.50 | 729.50 | 21.51 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.49 | 741.50 | 20.49 | 741.50 | 20.49 |
February | 672.00 | 20.50 | 665.00 | 20.50 | 665.00 | 20.50 |
March | 742.67 | 20.82 | 452.83 | 20.71 | 452.83 | 20.67 |
April | 713.83 | 21.18 | 129.50 | 21.10 | 128.17 | 21.04 |
May | 671.33 | 21.71 | 49.83 | 22.00 | 14.17 | 22.10 |
June | 544.50 | 22.22 | 153.67 | 22.95 | 72.00 | 23.25 |
July | 543.67 | 22.01 | 162.00 | 22.62 | 84.33 | 22.85 |
August | 561.00 | 21.98 | 131.00 | 22.50 | 66.67 | 22.70 |
September | 605.17 | 21.78 | 118.33 | 22.18 | 55.83 | 22.25 |
October | 738.83 | 21.12 | 174.67 | 21.04 | 171.67 | 20.98 |
November | 720.00 | 20.70 | 493.50 | 20.63 | 493.50 | 20.60 |
December | 744.00 | 20.50 | 732.50 | 20.49 | 732.50 | 20.49 |
Annual Sum or Average | 8001.00 | 21.19 | 4004.33 | 21.19 | 3678.17 | 21.11 |
Minimum of Months | 543.67 | 20.49 | 49.83 | 20.49 | 14.17 | 20.49 |
Maximum of Months | 744.00 | 22.22 | 741.50 | 22.95 | 741.50 | 23.25 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 741.00 | 20.91 | 573.33 | 20.83 | 573.33 | 20.79 |
February | 672.00 | 20.94 | 493.00 | 20.86 | 493.00 | 20.83 |
March | 736.17 | 21.36 | 167.00 | 21.29 | 165.83 | 21.24 |
April | 692.83 | 21.40 | 19.83 | 21.39 | 19.83 | 21.37 |
May | 696.17 | 21.50 | 0.00 | 21.50 | 0.00 | 21.50 |
June | 639.00 | 21.48 | 4.50 | 21.49 | 4.50 | 21.50 |
July | 633.00 | 21.44 | 11.83 | 21.46 | 11.17 | 21.49 |
August | 635.83 | 21.43 | 24.83 | 21.50 | 5.33 | 21.51 |
September | 628.67 | 21.45 | 26.67 | 21.52 | 2.33 | 21.53 |
October | 700.83 | 21.40 | 14.00 | 21.42 | 3.33 | 21.42 |
November | 711.50 | 21.22 | 151.67 | 21.12 | 151.67 | 21.06 |
December | 740.83 | 20.83 | 544.17 | 20.75 | 544.17 | 20.71 |
Annual Sum or Average | 8227.83 | 21.27 | 2030.83 | 21.18 | 1974.50 | 21.11 |
Minimum of Months | 628.67 | 20.83 | 0.00 | 20.75 | 0.00 | 20.71 |
Maximum of Months | 741.00 | 21.50 | 573.33 | 21.52 | 573.33 | 21.53 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 688.83 | 22.97 | 0.00 | 22.97 | 0.00 | 22.97 |
February | 624.50 | 22.99 | 0.00 | 22.99 | 0.00 | 22.99 |
March | 501.33 | 23.15 | 99.17 | 23.28 | 1.83 | 23.28 |
April | 256.00 | 23.11 | 114.17 | 23.38 | 0.00 | 23.38 |
May | 94.50 | 23.32 | 400.83 | 23.82 | 17.33 | 23.83 |
June | 127.50 | 23.95 | 625.17 | 23.95 | 120.83 | 23.95 |
July | 231.67 | 24.00 | 740.50 | 23.96 | 231.67 | 23.97 |
August | 137.50 | 24.00 | 732.17 | 23.94 | 137.50 | 23.95 |
September | 122.00 | 23.84 | 605.00 | 23.91 | 102.67 | 23.92 |
October | 257.50 | 23.09 | 228.83 | 23.51 | 12.33 | 23.52 |
November | 390.33 | 23.05 | 40.17 | 23.13 | 0.00 | 23.13 |
December | 632.33 | 22.94 | 0.00 | 22.94 | 0.00 | 22.94 |
Annual Sum or Average | 4064.00 | 23.17 | 3586.00 | 23.53 | 624.17 | 23.57 |
Minimum of Months | 94.50 | 22.94 | 0.00 | 22.94 | 0.00 | 22.94 |
Maximum of Months | 688.83 | 24.00 | 740.50 | 23.96 | 231.67 | 23.97 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 564.67 | 23.11 | 4.50 | 23.12 | 0.00 | 23.12 |
February | 508.50 | 23.12 | 5.00 | 23.13 | 0.00 | 23.13 |
March | 329.33 | 23.19 | 179.50 | 23.45 | 0.00 | 23.45 |
April | 116.00 | 23.15 | 263.17 | 23.73 | 0.00 | 23.73 |
May | 22.50 | 23.71 | 530.33 | 23.95 | 13.00 | 23.95 |
June | 110.50 | 23.99 | 690.33 | 23.97 | 109.00 | 23.97 |
July | 213.50 | 24.00 | 743.83 | 23.98 | 213.50 | 23.98 |
August | 123.33 | 24.00 | 743.83 | 23.96 | 123.33 | 23.97 |
September | 93.17 | 23.99 | 673.33 | 23.95 | 92.67 | 23.95 |
October | 108.00 | 23.17 | 349.17 | 23.78 | 6.33 | 23.78 |
November | 232.17 | 23.08 | 139.33 | 23.41 | 0.00 | 23.41 |
December | 484.17 | 23.03 | 18.50 | 23.07 | 0.00 | 23.07 |
Annual Sum or Average | 2905.83 | 23.28 | 4340.83 | 23.69 | 557.83 | 23.71 |
Minimum of Months | 22.50 | 23.03 | 4.50 | 23.07 | 0.00 | 23.07 |
Maximum of Months | 564.67 | 24.00 | 743.83 | 23.98 | 213.50 | 23.98 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 534.50 | 23.50 | 573.33 | 23.74 | 403.67 | 23.81 |
February | 494.50 | 23.49 | 516.00 | 23.73 | 374.33 | 23.80 |
March | 551.50 | 23.73 | 623.00 | 23.82 | 479.17 | 23.87 |
April | 508.00 | 23.94 | 638.50 | 23.90 | 495.33 | 23.93 |
May | 533.17 | 23.99 | 721.50 | 23.89 | 533.17 | 23.92 |
June | 547.00 | 23.99 | 716.83 | 23.92 | 547.00 | 23.94 |
July | 585.00 | 23.99 | 744.00 | 23.94 | 585.00 | 23.95 |
August | 573.33 | 23.99 | 744.00 | 23.93 | 573.33 | 23.95 |
September | 531.33 | 23.99 | 718.33 | 23.90 | 531.33 | 23.92 |
October | 524.50 | 23.95 | 685.67 | 23.89 | 514.33 | 23.92 |
November | 509.17 | 23.87 | 608.50 | 23.88 | 475.83 | 23.92 |
December | 529.33 | 23.56 | 582.50 | 23.76 | 415.67 | 23.82 |
Annual Sum or Average | 6421.33 | 23.84 | 7872.17 | 23.86 | 5928.17 | 23.90 |
Minimum of Months | 494.50 | 23.49 | 516.00 | 23.73 | 374.33 | 23.80 |
Maximum of Months | 585.00 | 23.99 | 744.00 | 23.94 | 585.00 | 23.95 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 506.17 | 21.00 | 506.17 | 21.00 |
February | 672.00 | 21.00 | 470.17 | 21.00 | 470.17 | 21.00 |
March | 744.00 | 21.13 | 203.67 | 21.10 | 203.67 | 21.08 |
April | 720.00 | 21.32 | 12.33 | 21.31 | 12.33 | 21.31 |
May | 744.00 | 22.03 | 0.00 | 22.03 | 0.00 | 22.03 |
June | 556.00 | 22.76 | 42.50 | 22.83 | 0.00 | 22.83 |
July | 209.33 | 23.04 | 275.17 | 23.49 | 0.00 | 23.49 |
August | 391.50 | 22.96 | 134.17 | 23.19 | 0.00 | 23.19 |
September | 689.67 | 22.46 | 4.50 | 22.47 | 0.00 | 22.47 |
October | 744.00 | 21.37 | 0.00 | 21.37 | 0.00 | 21.37 |
November | 720.00 | 21.05 | 11.17 | 21.05 | 11.17 | 21.05 |
December | 744.00 | 21.00 | 387.83 | 21.00 | 387.83 | 21.00 |
Annual Sum or Average | 7678.50 | 21.60 | 2047.67 | 21.60 | 1591.33 | 21.52 |
Minimum of Months | 209.33 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 23.04 | 506.17 | 23.49 | 506.17 | 23.49 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.01287 | 23.63395 | -0.0325 | 5.16124 |
February | 672.00000 | 22.73864 | 24.08120 | -0.0987 | 5.35389 |
March | 744.00000 | 22.12856 | 32.18078 | -0.2007 | 6.03630 |
April | 720.00000 | 21.93797 | 36.02240 | -0.2253 | 6.22688 |
May | 744.00000 | 21.85327 | 41.90150 | -1.3393 | 42.42099 |
June | 720.00000 | 22.37615 | 52.95325 | -1.0800 | 29.87281 |
July | 744.00000 | 22.79642 | 60.09973 | -0.8788 | 21.52475 |
August | 744.00000 | 23.37645 | 55.15988 | -0.6993 | 15.56010 |
September | 720.00000 | 23.73708 | 48.94292 | -0.6058 | 12.94239 |
October | 744.00000 | 23.86428 | 37.16776 | 0.28615 | 6.80109 |
November | 720.00000 | 23.83149 | 31.33593 | 0.23476 | 6.22360 |
December | 744.00000 | 23.60082 | 26.10804 | 0.13501 | 5.51912 |
Annual Sum or Average | 8760.00000 | 22.93911 | 39.22112 | -0.3772 | 13.70304 |
Minimum of Months | 672.00000 | 21.85327 | 23.63395 | -1.3393 | 5.16124 |
Maximum of Months | 744.00000 | 23.86428 | 60.09973 | 0.28615 | 42.42099 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.06026 | 23.88637 | -0.6038 | 13.06634 |
February | 672.00000 | 21.06871 | 24.10320 | -0.5931 | 12.85522 |
March | 744.00000 | 21.29397 | 31.67427 | -0.3859 | 9.38812 |
April | 720.00000 | 21.33913 | 35.43897 | -0.3162 | 8.07297 |
May | 744.00000 | 21.55306 | 40.86563 | -1.2917 | 41.03846 |
June | 720.00000 | 22.17495 | 51.65764 | -0.9549 | 26.22552 |
July | 744.00000 | 22.69289 | 58.81760 | -0.7001 | 16.98629 |
August | 744.00000 | 22.63757 | 55.70850 | -0.7414 | 18.87101 |
September | 720.00000 | 22.14541 | 51.67001 | -0.9710 | 27.98121 |
October | 744.00000 | 21.47980 | 40.44150 | -0.2329 | 7.74411 |
November | 720.00000 | 21.16830 | 34.14718 | -0.4186 | 9.40395 |
December | 744.00000 | 21.06166 | 27.56541 | -0.5854 | 12.63350 |
Annual Sum or Average | 8760.00000 | 21.64360 | 39.75354 | -0.6499 | 17.04662 |
Minimum of Months | 672.00000 | 21.06026 | 23.88637 | -1.2917 | 7.74411 |
Maximum of Months | 744.00000 | 22.69289 | 58.81760 | -0.2329 | 41.03846 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.32149 | 25.95110 | -0.4242 | 9.01498 |
February | 672.00000 | 21.31830 | 26.16809 | -0.4237 | 9.00882 |
March | 744.00000 | 21.92274 | 32.90548 | -0.2125 | 6.67796 |
April | 720.00000 | 22.27988 | 36.05913 | -0.0991 | 5.67902 |
May | 744.00000 | 22.75486 | 40.71404 | -0.9626 | 25.19417 |
June | 720.00000 | 23.26891 | 51.09400 | -0.6954 | 15.96777 |
July | 744.00000 | 23.51991 | 58.42535 | -0.5460 | 11.65614 |
August | 744.00000 | 23.50267 | 55.37419 | -0.5747 | 12.38450 |
September | 720.00000 | 23.18997 | 51.13556 | -0.7278 | 16.88338 |
October | 744.00000 | 22.50273 | 40.63924 | -0.0100 | 5.56074 |
November | 720.00000 | 21.99880 | 35.06118 | -0.1815 | 6.10706 |
December | 744.00000 | 21.37456 | 29.46878 | -0.3888 | 8.47077 |
Annual Sum or Average | 8760.00000 | 22.41892 | 40.33158 | -0.4374 | 11.06603 |
Minimum of Months | 672.00000 | 21.31830 | 25.95110 | -0.9626 | 5.56074 |
Maximum of Months | 744.00000 | 23.51991 | 58.42535 | -0.0100 | 25.19417 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.69589 | 19.80345 | 0.45199 | 12.24923 |
February | 672.00000 | 22.68796 | 20.02411 | 0.45080 | 12.26348 |
March | 744.00000 | 22.78464 | 27.00464 | 0.56255 | 14.74198 |
April | 720.00000 | 22.82715 | 30.39412 | 0.61894 | 15.90793 |
May | 744.00000 | 22.85946 | 35.72776 | -0.0485 | 10.80364 |
June | 720.00000 | 22.87177 | 47.48972 | 0.07444 | 10.84115 |
July | 744.00000 | 22.88081 | 55.80144 | 0.15179 | 10.94357 |
August | 744.00000 | 22.88269 | 52.57673 | 0.12690 | 10.93955 |
September | 720.00000 | 22.88334 | 47.21211 | 0.05666 | 10.74404 |
October | 744.00000 | 22.86655 | 35.22983 | 0.66748 | 17.19177 |
November | 720.00000 | 22.83065 | 28.97497 | 0.59108 | 15.15691 |
December | 744.00000 | 22.70167 | 23.12808 | 0.47725 | 12.75866 |
Annual Sum or Average | 8760.00000 | 22.81500 | 35.37050 | 0.34775 | 12.88044 |
Minimum of Months | 672.00000 | 22.68796 | 19.80345 | -0.0485 | 10.74404 |
Maximum of Months | 744.00000 | 22.88334 | 55.80144 | 0.66748 | 17.19177 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.33783 | 28.71807 | -0.4238 | 9.37926 |
February | 672.00000 | 21.34632 | 28.91804 | -0.4135 | 9.26101 |
March | 744.00000 | 22.03470 | 35.76291 | -0.1193 | 6.76366 |
April | 720.00000 | 22.22744 | 39.10117 | -0.0282 | 6.05423 |
May | 744.00000 | 22.61743 | 43.96997 | -0.8627 | 22.00938 |
June | 720.00000 | 23.05135 | 54.62269 | -0.5913 | 13.62220 |
July | 744.00000 | 23.34644 | 61.92784 | -0.4035 | 9.18736 |
August | 744.00000 | 23.36762 | 58.79647 | -0.4189 | 9.84655 |
September | 720.00000 | 23.13759 | 54.22912 | -0.5611 | 13.56961 |
October | 744.00000 | 22.43358 | 43.68230 | 0.07021 | 6.73959 |
November | 720.00000 | 21.92303 | 38.06419 | -0.1493 | 6.56266 |
December | 744.00000 | 21.35220 | 32.26100 | -0.4032 | 9.10452 |
Annual Sum or Average | 8760.00000 | 22.35360 | 43.42163 | -0.3586 | 10.18496 |
Minimum of Months | 672.00000 | 21.33783 | 28.71807 | -0.8627 | 6.05423 |
Maximum of Months | 744.00000 | 23.36762 | 61.92784 | 0.07021 | 22.00938 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.82676 | 28.07329 | -0.2747 | 7.09771 |
February | 672.00000 | 21.82076 | 28.27692 | -0.2745 | 7.08457 |
March | 744.00000 | 22.46905 | 34.87957 | -0.0467 | 5.85100 |
April | 720.00000 | 22.74105 | 38.03066 | 0.05020 | 5.60858 |
May | 744.00000 | 23.12119 | 42.72192 | -0.7812 | 18.64866 |
June | 720.00000 | 23.43600 | 53.21610 | -0.5712 | 12.59808 |
July | 744.00000 | 23.59000 | 60.57720 | -0.4480 | 9.58647 |
August | 744.00000 | 23.60525 | 57.46302 | -0.4657 | 9.94447 |
September | 720.00000 | 23.47756 | 52.93665 | -0.5619 | 12.26836 |
October | 744.00000 | 22.99117 | 42.42414 | 0.15082 | 6.11686 |
November | 720.00000 | 22.53118 | 36.94669 | -0.0186 | 5.65022 |
December | 744.00000 | 21.86645 | 31.48012 | -0.2428 | 6.85615 |
Annual Sum or Average | 8760.00000 | 22.79485 | 42.33385 | -0.2906 | 8.95689 |
Minimum of Months | 672.00000 | 21.82076 | 28.07329 | -0.7812 | 5.60858 |
Maximum of Months | 744.00000 | 23.60525 | 60.57720 | 0.15082 | 18.64866 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.62239 | 40.94095 | -0.6850 | 15.32832 |
February | 672.00000 | 20.66541 | 40.98343 | -0.6661 | 14.81521 |
March | 744.00000 | 21.15185 | 45.84625 | -0.4295 | 9.68495 |
April | 720.00000 | 21.37997 | 48.64472 | -0.3055 | 7.81623 |
May | 744.00000 | 21.62011 | 50.27344 | -1.2891 | 40.93428 |
June | 720.00000 | 21.71346 | 53.15905 | -1.1316 | 33.56452 |
July | 744.00000 | 21.73221 | 54.86078 | -1.0772 | 31.11349 |
August | 744.00000 | 21.71818 | 54.96436 | -1.1035 | 32.32877 |
September | 720.00000 | 21.66638 | 56.51714 | -1.1958 | 36.54965 |
October | 744.00000 | 21.35316 | 53.06645 | -0.2914 | 7.54552 |
November | 720.00000 | 21.01920 | 48.48150 | -0.4694 | 10.17490 |
December | 744.00000 | 20.62751 | 44.30291 | -0.6630 | 14.75383 |
Annual Sum or Average | 8760.00000 | 21.27559 | 49.37950 | -0.7765 | 21.26123 |
Minimum of Months | 672.00000 | 20.62239 | 40.94095 | -1.2891 | 7.54552 |
Maximum of Months | 744.00000 | 21.73221 | 56.51714 | -0.2914 | 40.93428 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.52057 | 41.19263 | -0.7281 | 16.66095 |
February | 672.00000 | 20.54361 | 41.28268 | -0.7131 | 16.16993 |
March | 744.00000 | 20.92709 | 46.48914 | -0.5069 | 11.29431 |
April | 720.00000 | 21.28012 | 48.90662 | -0.3487 | 8.27508 |
May | 744.00000 | 21.95569 | 49.72119 | -1.2149 | 38.91842 |
June | 720.00000 | 22.61632 | 52.04680 | -0.8800 | 26.82115 |
July | 744.00000 | 22.47631 | 54.86324 | -0.8677 | 24.57778 |
August | 744.00000 | 22.42084 | 54.87990 | -0.9176 | 26.43126 |
September | 720.00000 | 22.18400 | 56.73676 | -1.0794 | 32.68317 |
October | 744.00000 | 21.23903 | 53.69342 | -0.3436 | 8.15678 |
November | 720.00000 | 20.82569 | 49.04027 | -0.5313 | 11.24526 |
December | 744.00000 | 20.53874 | 44.53462 | -0.6987 | 15.78279 |
Annual Sum or Average | 8760.00000 | 21.46529 | 49.49158 | -0.7363 | 19.78079 |
Minimum of Months | 672.00000 | 20.52057 | 41.19263 | -1.2149 | 8.15678 |
Maximum of Months | 744.00000 | 22.61632 | 56.73676 | -0.3436 | 38.91842 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.84167 | 36.55867 | -0.5859 | 12.46441 |
February | 672.00000 | 20.86945 | 36.70410 | -0.5773 | 12.18749 |
March | 744.00000 | 21.13106 | 42.11787 | -0.4456 | 9.69576 |
April | 720.00000 | 21.35123 | 45.06064 | -0.3423 | 7.69788 |
May | 744.00000 | 21.70506 | 46.64156 | -1.3524 | 43.50091 |
June | 720.00000 | 22.12801 | 52.40006 | -1.1297 | 33.24215 |
July | 744.00000 | 22.21838 | 56.79550 | -1.0518 | 30.03085 |
August | 744.00000 | 22.14693 | 55.58111 | -1.0996 | 31.88733 |
September | 720.00000 | 21.90137 | 54.43879 | -1.2301 | 37.69461 |
October | 744.00000 | 21.36002 | 49.44022 | -0.3119 | 7.27550 |
November | 720.00000 | 21.13528 | 44.50221 | -0.4258 | 8.89182 |
December | 744.00000 | 20.87267 | 39.88626 | -0.5555 | 11.75291 |
Annual Sum or Average | 8760.00000 | 21.47499 | 46.73267 | -0.7602 | 20.58050 |
Minimum of Months | 672.00000 | 20.84167 | 36.55867 | -1.3524 | 7.27550 |
Maximum of Months | 744.00000 | 22.21838 | 56.79550 | -0.3119 | 43.50091 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.63533 | 40.88005 | -0.6772 | 15.08470 |
February | 672.00000 | 20.69440 | 40.90767 | -0.6556 | 14.49655 |
March | 744.00000 | 21.21536 | 45.60637 | -0.4168 | 9.45284 |
April | 720.00000 | 21.46249 | 48.44239 | -0.2826 | 7.65087 |
May | 744.00000 | 21.66150 | 49.96510 | -1.2750 | 40.33832 |
June | 720.00000 | 21.73371 | 52.97193 | -1.1338 | 33.73683 |
July | 744.00000 | 21.74887 | 54.51027 | -1.0716 | 30.94876 |
August | 744.00000 | 21.73809 | 54.57544 | -1.0987 | 32.18200 |
September | 720.00000 | 21.68997 | 55.90141 | -1.1861 | 36.15952 |
October | 744.00000 | 21.41280 | 52.70510 | -0.2750 | 7.41448 |
November | 720.00000 | 21.02654 | 48.46507 | -0.4655 | 10.11882 |
December | 744.00000 | 20.62353 | 44.29389 | -0.6631 | 14.75629 |
Annual Sum or Average | 8760.00000 | 21.30664 | 49.14373 | -0.7677 | 21.07228 |
Minimum of Months | 672.00000 | 20.62353 | 40.88005 | -1.2750 | 7.41448 |
Maximum of Months | 744.00000 | 21.74887 | 55.90141 | -0.2750 | 40.33832 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.52962 | 41.14939 | -0.7213 | 16.44593 |
February | 672.00000 | 20.55872 | 41.23526 | -0.7054 | 15.90761 |
March | 744.00000 | 20.98439 | 46.23004 | -0.4955 | 10.99044 |
April | 720.00000 | 21.39463 | 48.63046 | -0.3196 | 7.91849 |
May | 744.00000 | 21.88414 | 49.57248 | -1.2337 | 38.43673 |
June | 720.00000 | 22.39188 | 52.44951 | -0.9529 | 27.24232 |
July | 744.00000 | 22.51706 | 54.63500 | -0.8544 | 24.37139 |
August | 744.00000 | 22.42404 | 54.63732 | -0.9171 | 26.07974 |
September | 720.00000 | 22.08336 | 56.36687 | -1.1052 | 32.72001 |
October | 744.00000 | 21.29851 | 53.30986 | -0.3273 | 7.82711 |
November | 720.00000 | 20.83016 | 49.01297 | -0.5277 | 11.20643 |
December | 744.00000 | 20.54016 | 44.51126 | -0.6981 | 15.78796 |
Annual Sum or Average | 8760.00000 | 21.45798 | 49.35284 | -0.7386 | 19.60589 |
Minimum of Months | 672.00000 | 20.52962 | 41.14939 | -1.2337 | 7.82711 |
Maximum of Months | 744.00000 | 22.51706 | 56.36687 | -0.3196 | 38.43673 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.54047 | 41.93580 | -0.7495 | 17.34275 |
February | 672.00000 | 20.57713 | 41.99568 | -0.7311 | 16.78491 |
March | 744.00000 | 21.03144 | 47.23445 | -0.4834 | 10.91571 |
April | 720.00000 | 21.31369 | 49.99737 | -0.3352 | 8.43175 |
May | 744.00000 | 21.59717 | 51.28983 | -1.3044 | 41.90814 |
June | 720.00000 | 21.70439 | 54.03827 | -1.1320 | 33.80626 |
July | 744.00000 | 21.72750 | 55.90391 | -1.0708 | 31.03972 |
August | 744.00000 | 21.70851 | 56.26507 | -1.1033 | 32.54047 |
September | 720.00000 | 21.64078 | 58.21420 | -1.2117 | 37.51850 |
October | 744.00000 | 21.27103 | 54.73580 | -0.3266 | 8.15245 |
November | 720.00000 | 20.89921 | 49.97891 | -0.5234 | 11.42657 |
December | 744.00000 | 20.55608 | 45.42226 | -0.7229 | 16.56360 |
Annual Sum or Average | 8760.00000 | 21.21726 | 50.62779 | -0.8086 | 22.24060 |
Minimum of Months | 672.00000 | 20.54047 | 41.93580 | -1.3044 | 8.15245 |
Maximum of Months | 744.00000 | 21.72750 | 58.21420 | -0.3266 | 41.90814 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.48755 | 42.08748 | -0.7835 | 18.47739 |
February | 672.00000 | 20.50005 | 42.20616 | -0.7702 | 18.00111 |
March | 744.00000 | 20.82232 | 47.89553 | -0.5595 | 12.69842 |
April | 720.00000 | 21.21087 | 50.30155 | -0.3805 | 8.96592 |
May | 744.00000 | 21.98327 | 50.65823 | -1.2124 | 39.74624 |
June | 720.00000 | 22.68959 | 52.42697 | -0.8481 | 27.18302 |
July | 744.00000 | 22.49997 | 55.39246 | -0.8481 | 24.59938 |
August | 744.00000 | 22.43474 | 55.70770 | -0.9063 | 26.81324 |
September | 720.00000 | 22.19530 | 58.23864 | -1.0813 | 33.57944 |
October | 744.00000 | 21.13905 | 55.50656 | -0.3841 | 8.95520 |
November | 720.00000 | 20.69789 | 50.60862 | -0.5884 | 12.69946 |
December | 744.00000 | 20.49533 | 45.60787 | -0.7535 | 17.52620 |
Annual Sum or Average | 8760.00000 | 21.43436 | 50.59610 | -0.7600 | 20.79497 |
Minimum of Months | 672.00000 | 20.48755 | 42.08748 | -1.2124 | 8.95520 |
Maximum of Months | 744.00000 | 22.68959 | 58.23864 | -0.3805 | 39.74624 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.92399 | 40.95325 | -0.5854 | 13.11730 |
February | 672.00000 | 20.93977 | 40.99936 | -0.5785 | 12.81652 |
March | 744.00000 | 21.38107 | 45.60611 | -0.3531 | 8.79047 |
April | 720.00000 | 21.47337 | 48.57902 | -0.2830 | 7.76663 |
May | 744.00000 | 21.62102 | 50.09680 | -1.3217 | 42.68166 |
June | 720.00000 | 21.69168 | 54.12629 | -1.2026 | 36.89466 |
July | 744.00000 | 21.72207 | 56.13638 | -1.1316 | 33.60147 |
August | 744.00000 | 21.70959 | 55.61916 | -1.1446 | 34.31937 |
September | 720.00000 | 21.68409 | 55.70405 | -1.1973 | 36.93706 |
October | 744.00000 | 21.50952 | 52.06203 | -0.2317 | 7.23015 |
November | 720.00000 | 21.24231 | 48.02261 | -0.3889 | 9.19361 |
December | 744.00000 | 20.84560 | 44.17773 | -0.5902 | 13.19056 |
Annual Sum or Average | 8760.00000 | 21.39769 | 49.38393 | -0.7519 | 21.43420 |
Minimum of Months | 672.00000 | 20.84560 | 40.95325 | -1.3217 | 7.23015 |
Maximum of Months | 744.00000 | 21.72207 | 56.13638 | -0.2317 | 42.68166 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.05016 | 29.16828 | 0.02113 | 5.98157 |
February | 672.00000 | 23.05790 | 29.38411 | 0.02461 | 5.90950 |
March | 744.00000 | 23.38735 | 35.43596 | 0.18827 | 6.70306 |
April | 720.00000 | 23.63163 | 38.00749 | 0.29831 | 7.24095 |
May | 744.00000 | 23.81008 | 42.22468 | -0.4704 | 9.99810 |
June | 720.00000 | 23.90968 | 52.49855 | -0.3060 | 7.25949 |
July | 744.00000 | 23.95034 | 59.92236 | -0.2101 | 6.00506 |
August | 744.00000 | 23.92492 | 57.14950 | -0.2557 | 6.49844 |
September | 720.00000 | 23.84032 | 52.86519 | -0.3684 | 8.19131 |
October | 744.00000 | 23.61897 | 42.62896 | 0.32997 | 7.72434 |
November | 720.00000 | 23.45724 | 37.21704 | 0.22338 | 6.58180 |
December | 744.00000 | 23.09917 | 32.25562 | 0.05839 | 6.10367 |
Annual Sum or Average | 8760.00000 | 23.56399 | 42.47328 | -0.0394 | 7.02223 |
Minimum of Months | 672.00000 | 23.05016 | 29.16828 | -0.4704 | 5.90950 |
Maximum of Months | 744.00000 | 23.95034 | 59.92236 | 0.32997 | 9.99810 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.31759 | 28.21343 | 0.12596 | 6.09486 |
February | 672.00000 | 23.33122 | 28.43524 | 0.13085 | 6.05503 |
March | 744.00000 | 23.59366 | 34.39613 | 0.27727 | 7.34107 |
April | 720.00000 | 23.79170 | 36.95985 | 0.37555 | 8.19533 |
May | 744.00000 | 23.90285 | 41.34264 | -0.3867 | 8.36066 |
June | 720.00000 | 23.95389 | 51.81967 | -0.2466 | 6.50801 |
July | 744.00000 | 23.97441 | 59.36551 | -0.1624 | 5.61189 |
August | 744.00000 | 23.95967 | 56.53954 | -0.2033 | 5.95903 |
September | 720.00000 | 23.91220 | 52.05041 | -0.2970 | 7.09188 |
October | 744.00000 | 23.77572 | 41.57298 | 0.40568 | 8.74165 |
November | 720.00000 | 23.64963 | 36.10683 | 0.30961 | 7.36604 |
December | 744.00000 | 23.35571 | 31.24626 | 0.16066 | 6.34933 |
Annual Sum or Average | 8760.00000 | 23.71168 | 41.58154 | 0.04013 | 6.97696 |
Minimum of Months | 672.00000 | 23.31759 | 28.21343 | -0.3867 | 5.61189 |
Maximum of Months | 744.00000 | 23.97441 | 59.36551 | 0.40568 | 8.74165 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.54399 | 27.08008 | 0.78329 | 21.30512 |
February | 672.00000 | 23.53133 | 27.25121 | 0.78480 | 21.49345 |
March | 744.00000 | 23.63772 | 33.26108 | 0.92112 | 26.17886 |
April | 720.00000 | 23.70667 | 36.08703 | 1.00425 | 28.99810 |
May | 744.00000 | 23.78733 | 40.81376 | 0.52338 | 16.12186 |
June | 720.00000 | 23.85668 | 51.40747 | 0.68651 | 19.70033 |
July | 744.00000 | 23.89420 | 58.89299 | 0.78586 | 22.23178 |
August | 744.00000 | 23.87974 | 56.03111 | 0.73892 | 20.91555 |
September | 720.00000 | 23.82406 | 51.32842 | 0.62634 | 18.22669 |
October | 744.00000 | 23.73136 | 40.60219 | 1.03764 | 30.19021 |
November | 720.00000 | 23.66764 | 35.04685 | 0.93736 | 26.27188 |
December | 744.00000 | 23.55748 | 30.08398 | 0.80908 | 22.07347 |
Annual Sum or Average | 8760.00000 | 23.71922 | 40.73657 | 0.80325 | 22.81438 |
Minimum of Months | 672.00000 | 23.53133 | 27.08008 | 0.52338 | 16.12186 |
Maximum of Months | 744.00000 | 23.89420 | 58.89299 | 1.03764 | 30.19021 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00017 | 23.25884 | -0.5723 | 11.92968 |
February | 672.00000 | 21.00017 | 23.43788 | -0.5738 | 11.95420 |
March | 744.00000 | 21.13865 | 31.00167 | -0.4580 | 9.86810 |
April | 720.00000 | 21.26384 | 34.75028 | -0.3862 | 8.31659 |
May | 744.00000 | 21.98395 | 39.07809 | -1.2828 | 39.61721 |
June | 720.00000 | 22.84729 | 49.13838 | -0.9133 | 23.15366 |
July | 744.00000 | 23.34244 | 56.05569 | -0.6907 | 15.25555 |
August | 744.00000 | 23.25895 | 53.08173 | -0.7412 | 16.78184 |
September | 720.00000 | 22.65869 | 49.41637 | -0.9789 | 25.73077 |
October | 744.00000 | 21.60635 | 39.36562 | -0.2665 | 6.88243 |
November | 720.00000 | 21.12842 | 33.46609 | -0.4317 | 9.02637 |
December | 744.00000 | 21.00059 | 26.95344 | -0.5442 | 11.28432 |
Annual Sum or Average | 8760.00000 | 21.85813 | 38.33436 | -0.6537 | 15.84036 |
Minimum of Months | 672.00000 | 21.00017 | 23.25884 | -1.2828 | 6.88243 |
Maximum of Months | 744.00000 | 23.34244 | 56.05569 | -0.2665 | 39.61721 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00050 | 27.17281 | -0.5523 | 11.43709 |
February | 672.00000 | 21.00054 | 27.35248 | -0.5490 | 11.35300 |
March | 744.00000 | 21.10243 | 35.03743 | -0.4481 | 9.50745 |
April | 720.00000 | 21.32464 | 38.55469 | -0.3635 | 7.94419 |
May | 744.00000 | 22.05677 | 42.88772 | -1.2591 | 38.43879 |
June | 720.00000 | 22.97125 | 52.84898 | -0.8714 | 21.45338 |
July | 744.00000 | 23.44081 | 59.71910 | -0.6574 | 14.20144 |
August | 744.00000 | 23.34664 | 56.90211 | -0.7109 | 15.84666 |
September | 720.00000 | 22.68621 | 53.37357 | -0.9692 | 25.27432 |
October | 744.00000 | 21.39283 | 43.74843 | -0.3128 | 7.35156 |
November | 720.00000 | 21.04319 | 37.50453 | -0.4523 | 9.33563 |
December | 744.00000 | 21.00051 | 30.84150 | -0.5310 | 10.96083 |
Annual Sum or Average | 8760.00000 | 21.86940 | 42.24631 | -0.6402 | 15.28265 |
Minimum of Months | 672.00000 | 21.00050 | 27.17281 | -1.2591 | 7.35156 |
Maximum of Months | 744.00000 | 23.44081 | 59.71910 | -0.3128 | 38.43879 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00126 | 24.22529 | -0.5710 | 11.90321 |
February | 672.00000 | 21.00100 | 24.43833 | -0.5682 | 11.82519 |
March | 744.00000 | 21.12740 | 32.02695 | -0.4429 | 9.59362 |
April | 720.00000 | 21.31608 | 35.64781 | -0.3509 | 7.86133 |
May | 744.00000 | 22.03396 | 39.90692 | -1.2213 | 36.77820 |
June | 720.00000 | 22.94197 | 49.72223 | -0.8278 | 20.34969 |
July | 744.00000 | 23.47432 | 56.43775 | -0.5866 | 12.60932 |
August | 744.00000 | 23.29282 | 53.86100 | -0.6721 | 15.07919 |
September | 720.00000 | 22.50892 | 50.73390 | -0.9803 | 26.13212 |
October | 744.00000 | 21.36600 | 40.83584 | -0.3037 | 7.34973 |
November | 720.00000 | 21.05114 | 34.56357 | -0.4443 | 9.22280 |
December | 744.00000 | 21.00185 | 27.91341 | -0.5465 | 11.34661 |
Annual Sum or Average | 8760.00000 | 21.84876 | 39.27595 | -0.6265 | 15.02066 |
Minimum of Months | 672.00000 | 21.00100 | 24.22529 | -1.2213 | 7.34973 |
Maximum of Months | 744.00000 | 23.47432 | 56.43775 | -0.3037 | 36.77820 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00596 | 22.73594 | -0.5582 | 11.59606 |
February | 672.00000 | 21.00411 | 22.92418 | -0.5604 | 11.63483 |
March | 744.00000 | 21.21755 | 30.32108 | -0.4339 | 9.49570 |
April | 720.00000 | 21.43365 | 33.89517 | -0.3464 | 7.76764 |
May | 744.00000 | 22.18614 | 38.10454 | -1.2173 | 36.39990 |
June | 720.00000 | 23.02969 | 48.08585 | -0.8524 | 20.91444 |
July | 744.00000 | 23.49597 | 54.98861 | -0.6377 | 13.78481 |
August | 744.00000 | 23.43376 | 51.98432 | -0.6817 | 15.01447 |
September | 720.00000 | 22.86161 | 48.30069 | -0.9119 | 23.09593 |
October | 744.00000 | 21.83868 | 38.32888 | -0.2140 | 6.36901 |
November | 720.00000 | 21.27136 | 32.68135 | -0.3954 | 8.44897 |
December | 744.00000 | 21.01347 | 26.42166 | -0.5292 | 10.95035 |
Annual Sum or Average | 8760.00000 | 21.98888 | 37.48001 | -0.6118 | 14.64248 |
Minimum of Months | 672.00000 | 21.00411 | 22.73594 | -1.2173 | 6.36901 |
Maximum of Months | 744.00000 | 23.49597 | 54.98861 | -0.2140 | 36.39990 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.334836E+09 | 8858.52 | 15-JAN-09:01 | 46.24 | 0.112028E+10 | 0.00 | 0.145512E+10 | 0.21 | 3.35 | 06-JAN-16:06 | 0.00 | 0.00 |
February | 0.333251E+09 | 12344.48 | 28-FEB-16:05 | 43.07 | 0.111497E+10 | 0.00 | 0.144822E+10 | 0.21 | 3.35 | 01-FEB-16:04 | 0.00 | 0.00 |
March | 0.103985E+11 | 93725.51 | 15-MAR-15:03 | 325.98 | 0.325894E+11 | 0.00 | 0.429880E+11 | 1.45 | 3.66 | 14-MAR-15:03 | 0.00 | 0.00 |
April | 0.135016E+11 | 62957.70 | 08-APR-15:03 | 507.64 | 0.439690E+11 | 0.00 | 0.574706E+11 | 2.34 | 3.45 | 08-APR-15:03 | 0.00 | 0.00 |
May | 0.474784E+11 | 99808.61 | 10-MAY-15:03 | 734.16 | 0.148610E+12 | 0.00 | 0.196088E+12 | 3.19 | 3.70 | 16-MAY-15:03 | 0.00 | 0.00 |
June | 0.125368E+12 | 146947.54 | 17-JUN-18:03 | 720.00 | 0.422183E+12 | 0.00 | 0.547551E+12 | 3.29 | 4.42 | 27-JUN-21:52 | 0.00 | 0.00 |
July | 0.201365E+12 | 161652.95 | 20-JUL-18:03 | 744.00 | 0.718308E+12 | 0.00 | 0.919672E+12 | 3.48 | 4.50 | 27-JUL-21:52 | 0.00 | 0.00 |
August | 0.162028E+12 | 147987.19 | 13-AUG-15:03 | 744.00 | 0.554788E+12 | 0.00 | 0.716815E+12 | 3.34 | 4.38 | 25-AUG-21:53 | 0.00 | 0.00 |
September | 0.894368E+11 | 118464.90 | 15-SEP-21:53 | 714.25 | 0.299421E+12 | 0.00 | 0.388857E+12 | 3.25 | 4.45 | 15-SEP-21:53 | 0.00 | 0.00 |
October | 0.212931E+11 | 82708.67 | 11-OCT-15:03 | 580.36 | 0.678365E+11 | 0.00 | 0.891296E+11 | 2.57 | 3.79 | 11-OCT-15:03 | 0.00 | 0.00 |
November | 0.602865E+10 | 55681.82 | 04-NOV-15:01 | 294.70 | 0.193969E+11 | 0.00 | 0.254256E+11 | 1.35 | 3.35 | 01-NOV-09:40 | 0.00 | 0.00 |
December | 0.386167E+09 | 9821.68 | 01-DEC-19:02 | 51.59 | 0.129143E+10 | 0.00 | 0.167759E+10 | 0.23 | 3.35 | 04-DEC-09:45 | 0.00 | 0.00 |
Annual Sum or Average | 0.677952E+12 | 5505.99 | 0.231063E+13 | 0.00 | 0.298858E+13 | 2.09 | 0.00 | 0.00 | ||||
Minimum of Months | 0.333251E+09 | 8858.52 | 43.07 | 0.111497E+10 | 0.00 | 0.144822E+10 | 0.21 | 3.35 | 0.00 | 0.00 | ||
Maximum of Months | 0.201365E+12 | 161652.95 | 744.00 | 0.718308E+12 | 0.00 | 0.919672E+12 | 3.48 | 4.50 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.198214E+12 | 0.00 | 744.00 | 245028.14 | 31-JAN-16:03 | 0.00 | 47.12 | 81.52 | 0.51 | 0.00 | 0.14 | 0.47 | 31-JAN-16:03 |
February | 0.187860E+12 | 0.00 | 672.00 | 281202.49 | 06-FEB-09:03 | 0.00 | 45.90 | 81.60 | 0.52 | 0.00 | 0.15 | 0.54 | 06-FEB-09:03 |
March | 0.100384E+12 | 0.00 | 707.22 | 211126.24 | 06-MAR-19:01 | 0.00 | 47.44 | 78.61 | 0.26 | 0.00 | 0.07 | 0.40 | 06-MAR-19:01 |
April | 0.546224E+11 | 0.00 | 640.91 | 139169.16 | 25-APR-15:05 | 0.00 | 45.79 | 74.55 | 0.14 | 0.00 | 0.04 | 0.27 | 25-APR-15:05 |
May | 0.545386E+11 | 0.00 | 435.59 | 118121.91 | 18-MAY-08:04 | 0.00 | 32.06 | 59.09 | 0.10 | 0.00 | 0.04 | 0.23 | 18-MAY-08:04 |
June | 0.176051E+11 | 0.00 | 156.36 | 120739.62 | 13-JUN-08:05 | 0.00 | 28.43 | 39.44 | 0.03 | 0.00 | 0.01 | 0.23 | 13-JUN-08:05 |
July | 0.293056E+10 | 0.00 | 44.23 | 46659.94 | 13-JUL-04:00 | 0.00 | 31.15 | 34.26 | 0.00 | 0.00 | 0.00 | 0.09 | 13-JUL-04:00 |
August | 0.627687E+10 | 0.00 | 85.78 | 57701.00 | 01-AUG-06:00 | 0.00 | 29.23 | 35.28 | 0.01 | 0.00 | 0.00 | 0.11 | 01-AUG-06:00 |
September | 0.323602E+11 | 0.00 | 266.32 | 108067.91 | 30-SEP-06:30 | 0.00 | 31.74 | 50.06 | 0.06 | 0.00 | 0.02 | 0.21 | 30-SEP-06:30 |
October | 0.730974E+11 | 0.00 | 626.20 | 161591.63 | 19-OCT-08:62 | 0.00 | 43.09 | 72.98 | 0.17 | 0.00 | 0.05 | 0.31 | 19-OCT-08:62 |
November | 0.683485E+11 | 0.00 | 707.56 | 184018.07 | 24-NOV-09:01 | 0.00 | 51.74 | 79.70 | 0.21 | 0.00 | 0.05 | 0.35 | 24-NOV-09:01 |
December | 0.176607E+12 | 0.00 | 744.00 | 263474.56 | 11-DEC-09:03 | 0.00 | 48.35 | 81.30 | 0.47 | 0.00 | 0.13 | 0.50 | 11-DEC-09:03 |
Annual Sum or Average | 0.972845E+12 | 0.00 | 5830.17 | 0.00 | 40.13 | 63.92 | 0.21 | 0.00 | 0.06 | ||||
Minimum of Months | 0.293056E+10 | 0.00 | 44.23 | 46659.94 | 0.00 | 28.43 | 34.26 | 0.00 | 0.00 | 0.00 | 0.09 | ||
Maximum of Months | 0.198214E+12 | 0.00 | 744.00 | 281202.49 | 0.00 | 51.74 | 81.60 | 0.52 | 0.00 | 0.15 | 0.54 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.143017E+11 | 0.00 | 51.83 | 0.140469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 199834.33 | 14-MAR-10:45 | 178784.76 | 15-MAR-18:10 | 0.00 | 0.00 | 0.00 |
April | 0.824425E+10 | 0.00 | 77.02 | 0.824425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 102314.88 | 08-APR-13:00 | 102314.88 | 08-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.675017E+11 | 0.00 | 336.53 | 0.662702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 181804.83 | 10-MAY-15:30 | 164727.04 | 23-MAY-18:03 | 0.00 | 0.00 | 0.00 |
June | 0.275839E+12 | 0.00 | 574.87 | 0.202072E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 507585.37 | 27-JUN-20:08 | 207305.26 | 17-JUN-17:15 | 0.00 | 0.00 | 0.00 |
July | 0.513129E+12 | 0.00 | 710.33 | 0.323198E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 507216.55 | 21-JUL-20:04 | 239147.95 | 20-JUL-19:10 | 0.00 | 0.00 | 0.00 |
August | 0.375044E+12 | 0.00 | 670.50 | 0.271710E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 441919.64 | 14-AUG-22:00 | 229004.81 | 09-AUG-18:40 | 0.00 | 0.00 | 0.00 |
September | 0.181601E+12 | 0.00 | 482.27 | 0.134371E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 414252.61 | 15-SEP-20:10 | 191844.30 | 16-SEP-21:00 | 0.00 | 0.00 | 0.00 |
October | 0.223274E+11 | 0.00 | 144.23 | 0.223274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 129462.64 | 11-OCT-15:15 | 129462.64 | 11-OCT-15:15 | 0.00 | 0.00 | 0.00 |
November | 0.709649E+10 | 0.00 | 59.83 | 0.709649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76601.74 | 05-NOV-10:50 | 76601.74 | 05-NOV-10:50 | 0.00 | 0.00 | 0.00 |
December | 5785851.23 | 0.00 | 1.00 | 5785851.23 | 0.00 | 0.00 | 0.00 | 0.00 | 3359.53 | 01-DEC-11:00 | 3359.53 | 01-DEC-11:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146509E+13 | 0.00 | 3108.42 | 0.104934E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.513129E+12 | 0.00 | 710.33 | 0.323198E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 507585.37 | 239147.95 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.106379E+10 | 0.00 | 37.50 | 0.101811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21341.77 | 14-MAR-12:20 | 17416.30 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.441673E+09 | 0.00 | 42.50 | 0.441673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13334.55 | 08-APR-13:00 | 13334.55 | 08-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.486239E+10 | 0.00 | 220.67 | 0.463851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21425.28 | 10-MAY-15:02 | 17601.23 | 14-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.222930E+11 | 0.00 | 435.67 | 0.153159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42332.09 | 18-JUN-08:62 | 19490.92 | 27-JUN-13:00 | 0.00 | 0.00 | 0.00 |
July | 0.404864E+11 | 0.00 | 556.00 | 0.246713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41906.99 | 17-JUL-18:10 | 19558.37 | 19-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.296902E+11 | 0.00 | 514.83 | 0.202919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40422.42 | 14-AUG-08:62 | 19230.24 | 13-AUG-13:00 | 0.00 | 0.00 | 0.00 |
September | 0.147656E+11 | 0.00 | 355.50 | 0.100051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37046.77 | 15-SEP-20:00 | 18097.60 | 16-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.151434E+10 | 0.00 | 101.00 | 0.151412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14829.46 | 11-OCT-15:01 | 14829.46 | 11-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.566793E+09 | 0.00 | 41.67 | 0.566793E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8665.51 | 05-NOV-13:00 | 8665.51 | 05-NOV-13:00 | 0.00 | 0.00 | 0.00 |
December | 850142.93 | 0.00 | 0.67 | 850142.93 | 0.00 | 0.00 | 0.00 | 0.00 | 572.22 | 01-DEC-11:00 | 572.22 | 01-DEC-11:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115685E+12 | 0.00 | 2306.00 | 0.784642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.404864E+11 | 0.00 | 556.00 | 0.246713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42332.09 | 19558.37 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 12305601.01 | 0.00 | 2.67 | 8831516.85 | 0.00 | 0.00 | 0.00 | 0.00 | 10637.86 | 12-JAN-16:01 | 10637.86 | 12-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 36346354.07 | 0.00 | 7.20 | 31004518.04 | 0.00 | 0.00 | 0.00 | 0.00 | 12899.15 | 28-FEB-16:02 | 12899.15 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.677186E+09 | 0.00 | 116.32 | 0.472503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14447.41 | 14-MAR-15:01 | 13185.25 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.148888E+10 | 0.00 | 237.51 | 0.108532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12939.13 | 30-APR-15:02 | 12904.24 | 23-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.388982E+10 | 0.00 | 546.95 | 0.269559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14675.62 | 17-MAY-15:01 | 13512.17 | 16-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.791596E+10 | 0.00 | 664.56 | 0.513636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16920.32 | 18-JUN-08:62 | 13700.83 | 17-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.100816E+11 | 0.00 | 704.77 | 0.628696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16761.69 | 17-JUL-08:62 | 13688.18 | 21-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.898332E+10 | 0.00 | 693.03 | 0.562766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17130.14 | 14-AUG-08:62 | 13575.00 | 24-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.528751E+10 | 0.00 | 618.23 | 0.301814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16662.65 | 13-SEP-18:02 | 13083.27 | 15-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.121414E+10 | 0.00 | 249.77 | 0.649176E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14798.28 | 01-OCT-08:62 | 12920.86 | 22-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.109491E+09 | 0.00 | 37.54 | 57916374.71 | 0.00 | 0.00 | 0.00 | 0.00 | 13671.51 | 04-NOV-15:01 | 11494.39 | 05-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 9396450.74 | 0.00 | 1.47 | 6752028.67 | 0.00 | 0.00 | 0.00 | 0.00 | 12104.49 | 04-DEC-16:01 | 12104.49 | 04-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.397060E+11 | 0.00 | 3880.01 | 0.250762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9396450.74 | 0.00 | 1.47 | 6752028.67 | 0.00 | 0.00 | 0.00 | 0.00 | 10637.86 | 10637.86 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.100816E+11 | 0.00 | 704.77 | 0.628696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17130.14 | 13700.83 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 4637043.45 | 0.00 | 0.57 | 3283151.11 | 0.00 | 0.00 | 0.00 | 0.00 | 4325.25 | 11-JAN-16:04 | 3408.08 | 16-JAN-19:04 | 0.00 | 0.00 | 0.00 |
February | 8346076.31 | 0.00 | 2.24 | 6761623.44 | 0.00 | 0.00 | 0.00 | 0.00 | 8270.46 | 18-FEB-16:01 | 8112.40 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.287524E+09 | 0.00 | 66.22 | 0.177041E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15810.81 | 14-MAR-15:01 | 12689.93 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.866674E+09 | 0.00 | 155.57 | 0.621482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13969.82 | 19-APR-18:11 | 13969.82 | 19-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.245279E+10 | 0.00 | 407.09 | 0.152293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14220.94 | 17-MAY-18:01 | 14173.31 | 03-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.569824E+10 | 0.00 | 482.41 | 0.357266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19450.11 | 18-JUN-08:21 | 14184.18 | 14-JUN-20:11 | 0.00 | 0.00 | 0.00 |
July | 0.788983E+10 | 0.00 | 525.77 | 0.504733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19549.39 | 16-JUL-08:21 | 13499.12 | 06-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.649722E+10 | 0.00 | 508.79 | 0.401305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19076.50 | 14-AUG-08:21 | 13681.80 | 02-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.274220E+10 | 0.00 | 424.61 | 0.130062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16520.74 | 17-SEP-08:51 | 12720.49 | 22-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.376079E+09 | 0.00 | 117.82 | 0.168932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14153.44 | 01-OCT-08:62 | 12666.38 | 11-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 27241933.52 | 0.00 | 5.56 | 16610333.60 | 0.00 | 0.00 | 0.00 | 0.00 | 12310.07 | 05-NOV-15:01 | 10747.15 | 05-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 5357442.05 | 0.00 | 0.73 | 3561567.33 | 0.00 | 0.00 | 0.00 | 0.00 | 4575.53 | 14-DEC-19:04 | 3450.32 | 23-DEC-19:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.268561E+11 | 0.00 | 2697.39 | 0.164543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4637043.45 | 0.00 | 0.57 | 3283151.11 | 0.00 | 0.00 | 0.00 | 0.00 | 4325.25 | 3408.08 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.788983E+10 | 0.00 | 525.77 | 0.504733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19549.39 | 14184.18 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.313904E+10 | 0.00 | 104.99 | 0.172434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42925.00 | 15-MAR-13:30 | 36080.47 | 15-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.956244E+10 | 0.00 | 273.37 | 0.789545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32891.14 | 22-APR-13:00 | 32891.14 | 22-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.216262E+11 | 0.00 | 556.94 | 0.126887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32089.61 | 14-MAY-13:30 | 28419.50 | 05-MAY-13:30 | 0.00 | 0.00 | 0.00 |
June | 0.342163E+11 | 0.00 | 684.06 | 0.164965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36010.64 | 27-JUN-13:00 | 27444.74 | 12-JUN-13:10 | 0.00 | 0.00 | 0.00 |
July | 0.467895E+11 | 0.00 | 744.00 | 0.245637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41387.52 | 30-JUL-12:30 | 35255.63 | 21-JUL-13:30 | 0.00 | 0.00 | 0.00 |
August | 0.467812E+11 | 0.00 | 740.12 | 0.264978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44809.75 | 18-AUG-12:40 | 42545.15 | 17-AUG-13:20 | 0.00 | 0.00 | 0.00 |
September | 0.379898E+11 | 0.00 | 659.21 | 0.222123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55589.01 | 21-SEP-13:00 | 46143.87 | 21-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.172974E+11 | 0.00 | 399.74 | 0.112612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56601.38 | 11-OCT-12:30 | 53036.67 | 31-OCT-12:30 | 0.00 | 0.00 | 0.00 |
November | 0.302593E+10 | 0.00 | 102.50 | 0.222391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32081.69 | 03-NOV-12:30 | 32081.69 | 03-NOV-12:30 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220428E+12 | 0.00 | 4264.95 | 0.125564E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.467895E+11 | 0.00 | 744.00 | 0.264978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56601.38 | 53036.67 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.102399E+09 | 0.00 | 6.96 | 82046476.21 | 0.00 | 0.00 | 0.00 | 0.00 | 44527.93 | 15-JAN-09:01 | 44527.93 | 15-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 83889361.17 | 0.00 | 3.95 | 82058330.44 | 0.00 | 0.00 | 0.00 | 0.00 | 52690.24 | 19-FEB-09:01 | 52690.24 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.498884E+10 | 0.00 | 150.38 | 0.295238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76044.78 | 14-MAR-15:01 | 67377.28 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.989810E+10 | 0.00 | 338.97 | 0.704165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64407.01 | 07-APR-15:02 | 64407.01 | 07-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.242260E+11 | 0.00 | 456.52 | 0.177871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74959.32 | 10-MAY-15:02 | 66265.43 | 13-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.399824E+11 | 0.00 | 431.10 | 0.286595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100116.72 | 18-JUN-08:21 | 69179.62 | 12-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.532835E+11 | 0.00 | 483.25 | 0.371007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100598.94 | 16-JUL-08:21 | 69507.64 | 25-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.451365E+11 | 0.00 | 460.10 | 0.311498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98818.58 | 14-AUG-08:21 | 69562.11 | 18-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.268847E+11 | 0.00 | 405.93 | 0.169283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85410.73 | 15-SEP-21:51 | 67669.40 | 16-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.102962E+11 | 0.00 | 352.80 | 0.562704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68454.50 | 01-OCT-08:62 | 62558.31 | 22-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.263219E+10 | 0.00 | 158.21 | 0.163888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61863.43 | 04-NOV-15:01 | 60674.19 | 05-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.156690E+09 | 0.00 | 11.39 | 0.103718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57576.25 | 03-DEC-09:01 | 57576.25 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217671E+12 | 0.00 | 3259.56 | 0.149153E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 83889361.17 | 0.00 | 3.95 | 82046476.21 | 0.00 | 0.00 | 0.00 | 0.00 | 44527.93 | 44527.93 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.532835E+11 | 0.00 | 483.25 | 0.371007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100598.94 | 69562.11 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 7395147.93 | 0.00 | 1.54 | 5604546.70 | 0.00 | 0.00 | 0.00 | 0.00 | 6517.84 | 15-JAN-16:01 | 6022.95 | 15-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 35137383.88 | 0.00 | 8.74 | 33920973.15 | 0.00 | 0.00 | 0.00 | 0.00 | 10930.63 | 28-FEB-09:01 | 10930.63 | 28-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.612417E+09 | 0.00 | 110.94 | 0.411493E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12778.62 | 14-MAR-08:62 | 12109.57 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.159462E+10 | 0.00 | 264.30 | 0.113697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11937.13 | 30-APR-15:02 | 11725.31 | 23-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.385876E+10 | 0.00 | 573.07 | 0.255746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13271.27 | 17-MAY-15:01 | 12476.30 | 14-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.746437E+10 | 0.00 | 679.44 | 0.468117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14935.45 | 08-JUN-08:62 | 12471.88 | 20-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.100994E+11 | 0.00 | 721.54 | 0.634183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15177.35 | 05-JUL-18:02 | 12517.12 | 18-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.890887E+10 | 0.00 | 710.99 | 0.559974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15417.28 | 14-AUG-08:62 | 12511.03 | 08-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.544417E+10 | 0.00 | 632.61 | 0.315351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15139.56 | 17-SEP-08:61 | 12320.19 | 15-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.131857E+10 | 0.00 | 275.38 | 0.701358E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13601.36 | 01-OCT-08:62 | 11994.28 | 22-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.169614E+09 | 0.00 | 46.91 | 89852205.64 | 0.00 | 0.00 | 0.00 | 0.00 | 12261.76 | 04-NOV-15:01 | 10615.50 | 05-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 17302079.07 | 0.00 | 5.76 | 10535534.55 | 0.00 | 0.00 | 0.00 | 0.00 | 4670.71 | 14-DEC-19:04 | 3416.84 | 14-DEC-19:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.395306E+11 | 0.00 | 4031.21 | 0.247234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7395147.93 | 0.00 | 1.54 | 5604546.70 | 0.00 | 0.00 | 0.00 | 0.00 | 4670.71 | 3416.84 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.100994E+11 | 0.00 | 721.54 | 0.634183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15417.28 | 12517.12 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3960360.98 | 0.00 | 0.57 | 2897021.51 | 0.00 | 0.00 | 0.00 | 0.00 | 3744.70 | 11-JAN-19:04 | 3219.92 | 07-JAN-09:04 | 0.00 | 0.00 | 0.00 |
February | 6835412.89 | 0.00 | 1.81 | 6197474.39 | 0.00 | 0.00 | 0.00 | 0.00 | 5755.90 | 28-FEB-09:01 | 5755.90 | 28-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.260352E+09 | 0.00 | 68.46 | 0.142278E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13694.60 | 14-MAR-15:01 | 11536.83 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.925866E+09 | 0.00 | 179.20 | 0.649107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11366.43 | 09-APR-08:62 | 11350.22 | 23-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.267046E+10 | 0.00 | 452.12 | 0.168784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13234.17 | 17-MAY-18:01 | 12056.10 | 31-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.558560E+10 | 0.00 | 502.74 | 0.350357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18104.73 | 18-JUN-08:21 | 13945.64 | 30-JUN-08:32 | 0.00 | 0.00 | 0.00 |
July | 0.784411E+10 | 0.00 | 536.05 | 0.499412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18378.83 | 17-JUL-08:32 | 14183.88 | 14-JUL-08:32 | 0.00 | 0.00 | 0.00 |
August | 0.644212E+10 | 0.00 | 524.29 | 0.394286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17445.40 | 14-AUG-08:21 | 14377.33 | 05-AUG-08:32 | 0.00 | 0.00 | 0.00 |
September | 0.312506E+10 | 0.00 | 463.55 | 0.161463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16048.71 | 16-SEP-08:51 | 12334.48 | 09-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.461815E+09 | 0.00 | 134.14 | 0.221599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13109.88 | 01-OCT-08:62 | 11546.12 | 11-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 37757523.29 | 0.00 | 15.66 | 17798934.77 | 0.00 | 0.00 | 0.00 | 0.00 | 11300.78 | 05-NOV-15:01 | 9936.17 | 05-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 4732136.64 | 0.00 | 0.64 | 3255615.74 | 0.00 | 0.00 | 0.00 | 0.00 | 4371.07 | 14-DEC-09:04 | 3768.56 | 17-DEC-09:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.273687E+11 | 0.00 | 2879.23 | 0.167861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3960360.98 | 0.00 | 0.57 | 2897021.51 | 0.00 | 0.00 | 0.00 | 0.00 | 3744.70 | 3219.92 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.784411E+10 | 0.00 | 536.05 | 0.499412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18378.83 | 14377.33 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3839323.17 | 0.00 | 1.89 | 2755924.31 | 0.00 | 0.00 | 0.00 | 0.00 | 2822.60 | 15-JAN-16:01 | 2822.60 | 15-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 9324433.07 | 0.00 | 5.53 | 7959376.74 | 0.00 | 0.00 | 0.00 | 0.00 | 3378.01 | 28-FEB-16:02 | 3378.01 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.157525E+09 | 0.00 | 97.39 | 0.109562E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3763.58 | 16-MAR-15:01 | 3447.04 | 14-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.376432E+09 | 0.00 | 190.55 | 0.279167E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3421.97 | 30-APR-15:02 | 3379.37 | 23-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.964846E+09 | 0.00 | 469.39 | 0.694230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3864.03 | 17-MAY-15:01 | 3538.22 | 16-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.199143E+10 | 0.00 | 646.36 | 0.130778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4620.01 | 18-JUN-08:62 | 3550.01 | 17-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.256002E+10 | 0.00 | 702.78 | 0.159832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4659.05 | 29-JUL-08:61 | 3576.91 | 20-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.223089E+10 | 0.00 | 686.26 | 0.140181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4777.81 | 14-AUG-08:62 | 3611.14 | 10-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.124228E+10 | 0.00 | 559.26 | 0.731010E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4565.24 | 17-SEP-08:61 | 3492.43 | 15-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.273061E+09 | 0.00 | 184.52 | 0.155196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3902.36 | 01-OCT-15:02 | 3350.56 | 03-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 21905522.36 | 0.00 | 19.61 | 13040226.91 | 0.00 | 0.00 | 0.00 | 0.00 | 3625.82 | 04-NOV-15:01 | 3027.63 | 26-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 3291549.84 | 0.00 | 1.55 | 2272543.68 | 0.00 | 0.00 | 0.00 | 0.00 | 2644.89 | 04-DEC-16:01 | 2644.89 | 04-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.983485E+10 | 0.00 | 3565.10 | 0.630310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3291549.84 | 0.00 | 1.55 | 2272543.68 | 0.00 | 0.00 | 0.00 | 0.00 | 2644.89 | 2644.89 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.256002E+10 | 0.00 | 702.78 | 0.159832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4777.81 | 3611.14 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1606283.93 | 0.00 | 0.81 | 1104128.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1275.40 | 11-JAN-19:04 | 955.64 | 12-JAN-16:04 | 0.00 | 0.00 | 0.00 |
February | 1760115.63 | 0.00 | 0.90 | 1352961.52 | 0.00 | 0.00 | 0.00 | 0.00 | 1011.15 | 20-FEB-09:04 | 777.27 | 28-FEB-19:04 | 0.00 | 0.00 | 0.00 |
March | 60457793.26 | 0.00 | 51.73 | 34955285.47 | 0.00 | 0.00 | 0.00 | 0.00 | 4123.25 | 14-MAR-15:01 | 3368.38 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.217260E+09 | 0.00 | 123.81 | 0.155609E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3758.44 | 19-APR-18:11 | 3758.44 | 19-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.605478E+09 | 0.00 | 347.98 | 0.388264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3785.68 | 31-MAY-21:51 | 3751.71 | 03-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.148586E+10 | 0.00 | 479.51 | 0.942565E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5266.96 | 18-JUN-08:21 | 3793.65 | 14-JUN-20:11 | 0.00 | 0.00 | 0.00 |
July | 0.206314E+10 | 0.00 | 527.08 | 0.132762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5311.27 | 16-JUL-08:21 | 3650.45 | 06-JUL-21:51 | 0.00 | 0.00 | 0.00 |
August | 0.165095E+10 | 0.00 | 506.59 | 0.102646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5213.21 | 14-AUG-08:21 | 3628.93 | 02-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.618144E+09 | 0.00 | 381.55 | 0.298509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4436.33 | 17-SEP-08:51 | 3313.90 | 11-SEP-19:31 | 0.00 | 0.00 | 0.00 |
October | 70744180.66 | 0.00 | 77.12 | 33638612.46 | 0.00 | 0.00 | 0.00 | 0.00 | 3783.79 | 01-OCT-15:02 | 3296.87 | 11-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 6542346.30 | 0.00 | 4.40 | 3999915.85 | 0.00 | 0.00 | 0.00 | 0.00 | 2885.40 | 05-NOV-15:01 | 2398.66 | 15-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 2090086.07 | 0.00 | 1.00 | 1272825.76 | 0.00 | 0.00 | 0.00 | 0.00 | 1384.39 | 01-DEC-16:04 | 865.72 | 01-DEC-16:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.678403E+10 | 0.00 | 2502.49 | 0.421535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1606283.93 | 0.00 | 0.81 | 1104128.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1011.15 | 777.27 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.206314E+10 | 0.00 | 527.08 | 0.132762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5311.27 | 3793.65 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.297006E+09 | 0.00 | 39.23 | 0.262158E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15769.69 | 06-JAN-16:01 | 15769.69 | 06-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.295655E+09 | 0.00 | 39.47 | 0.270962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15775.67 | 22-FEB-16:02 | 15775.67 | 22-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.219535E+10 | 0.00 | 224.58 | 0.176479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17145.28 | 16-MAR-15:01 | 16180.28 | 15-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.281490E+10 | 0.00 | 313.64 | 0.202845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16009.36 | 30-APR-15:02 | 15763.24 | 19-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.499251E+10 | 0.00 | 547.38 | 0.333147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18010.51 | 17-MAY-15:01 | 16512.84 | 16-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.879294E+10 | 0.00 | 640.99 | 0.517846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21439.57 | 27-JUN-08:62 | 16792.60 | 20-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.126314E+11 | 0.00 | 698.44 | 0.763114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21982.80 | 28-JUL-18:02 | 16885.29 | 20-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.120267E+11 | 0.00 | 691.16 | 0.752373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22708.64 | 14-AUG-08:62 | 16792.87 | 04-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.896432E+10 | 0.00 | 631.21 | 0.572928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21205.12 | 17-SEP-08:61 | 16442.87 | 16-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.404991E+10 | 0.00 | 392.89 | 0.270387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17730.72 | 01-OCT-08:62 | 15625.13 | 11-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.133296E+10 | 0.00 | 177.84 | 0.876350E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17370.73 | 04-NOV-15:01 | 15253.22 | 16-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.325667E+09 | 0.00 | 38.74 | 0.259513E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15765.29 | 11-DEC-16:01 | 15765.29 | 11-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.587193E+11 | 0.00 | 4435.56 | 0.375602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.295655E+09 | 0.00 | 38.74 | 0.259513E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15765.29 | 15253.22 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.126314E+11 | 0.00 | 698.44 | 0.763114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22708.64 | 16885.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 557.21 | 325.42 | 231.79 | 450.05 | 697.25 | 0.00 | 0.00 | 0.00 |
February | 631.03 | 301.80 | 329.23 | 503.56 | 678.78 | 0.00 | 0.00 | 0.00 |
March | 775.39 | 435.63 | 339.76 | 769.44 | 483.76 | 0.00 | 0.00 | 0.00 |
April | 641.30 | 255.68 | 385.62 | 673.80 | 364.26 | 0.00 | 0.00 | 0.00 |
May | 565.52 | 166.71 | 398.81 | 660.80 | 222.38 | 0.00 | 0.00 | 0.00 |
June | 544.34 | 113.98 | 430.36 | 706.99 | 135.63 | 0.00 | 0.00 | 0.00 |
July | 553.29 | 131.07 | 422.21 | 788.96 | 86.83 | 0.00 | 0.00 | 0.00 |
August | 619.54 | 196.60 | 422.95 | 858.63 | 119.54 | 0.00 | 0.00 | 0.00 |
September | 725.19 | 351.94 | 373.25 | 924.52 | 200.22 | 0.00 | 0.00 | 0.00 |
October | 697.37 | 398.71 | 298.66 | 770.34 | 336.22 | 0.00 | 0.00 | 0.00 |
November | 500.22 | 283.03 | 217.20 | 482.09 | 450.39 | 0.00 | 0.00 | 0.00 |
December | 465.94 | 241.51 | 224.43 | 356.81 | 679.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 606.20 | 266.73 | 339.47 | 663.09 | 369.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 465.94 | 113.98 | 217.20 | 356.81 | 86.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 775.39 | 435.63 | 430.36 | 924.52 | 697.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1569.08 | 916.37 | 652.71 | 1249.71 | 1999.93 | 0.00 | 0.00 | 0.00 |
February | 1776.95 | 849.85 | 927.10 | 1397.05 | 1945.30 | 0.00 | 0.00 | 0.00 |
March | 2183.46 | 1226.71 | 956.75 | 2136.33 | 1423.86 | 0.00 | 0.00 | 0.00 |
April | 1805.87 | 719.99 | 1085.87 | 1866.04 | 1094.23 | 0.00 | 0.00 | 0.00 |
May | 1592.46 | 469.45 | 1123.01 | 1822.16 | 695.08 | 0.00 | 0.00 | 0.00 |
June | 1532.82 | 320.96 | 1211.86 | 1957.34 | 429.44 | 0.00 | 0.00 | 0.00 |
July | 1558.02 | 369.09 | 1188.92 | 2196.62 | 276.68 | 0.00 | 0.00 | 0.00 |
August | 1744.59 | 553.60 | 1190.99 | 2393.39 | 377.95 | 0.00 | 0.00 | 0.00 |
September | 2042.09 | 991.05 | 1051.05 | 2571.45 | 631.10 | 0.00 | 0.00 | 0.00 |
October | 1963.76 | 1122.74 | 841.02 | 2138.74 | 1021.54 | 0.00 | 0.00 | 0.00 |
November | 1408.59 | 796.99 | 611.61 | 1334.06 | 1338.44 | 0.00 | 0.00 | 0.00 |
December | 1312.06 | 680.08 | 631.98 | 989.53 | 1954.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1707.02 | 751.08 | 955.94 | 1840.29 | 1094.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1312.06 | 320.96 | 611.61 | 989.53 | 276.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2183.46 | 1226.71 | 1211.86 | 2571.45 | 1999.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2038.32 | 1190.42 | 847.90 | 1639.37 | 2738.23 | 0.00 | 0.00 | 0.00 |
February | 2308.35 | 1104.00 | 1204.35 | 1833.85 | 2659.07 | 0.00 | 0.00 | 0.00 |
March | 2836.44 | 1593.56 | 1242.87 | 2819.76 | 1939.80 | 0.00 | 0.00 | 0.00 |
April | 2345.92 | 935.31 | 1410.61 | 2458.33 | 1502.25 | 0.00 | 0.00 | 0.00 |
May | 2068.69 | 609.84 | 1458.85 | 2399.18 | 961.17 | 0.00 | 0.00 | 0.00 |
June | 1991.23 | 416.95 | 1574.28 | 2580.55 | 589.40 | 0.00 | 0.00 | 0.00 |
July | 2023.95 | 479.47 | 1544.48 | 2905.78 | 374.39 | 0.00 | 0.00 | 0.00 |
August | 2266.32 | 719.16 | 1547.16 | 3165.47 | 508.78 | 0.00 | 0.00 | 0.00 |
September | 2652.80 | 1287.43 | 1365.37 | 3395.04 | 859.28 | 0.00 | 0.00 | 0.00 |
October | 2551.04 | 1458.51 | 1092.53 | 2811.14 | 1407.21 | 0.00 | 0.00 | 0.00 |
November | 1829.85 | 1035.33 | 794.51 | 1750.25 | 1853.47 | 0.00 | 0.00 | 0.00 |
December | 1704.44 | 883.46 | 820.98 | 1297.29 | 2686.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2217.52 | 975.70 | 1241.82 | 2424.80 | 1500.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1704.44 | 416.95 | 794.51 | 1297.29 | 374.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2836.44 | 1593.56 | 1574.28 | 3395.04 | 2738.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.17 | 64.34 | 45.83 | 89.54 | 141.55 | 0.00 | 0.00 | 0.00 |
February | 124.77 | 59.67 | 65.10 | 99.20 | 139.11 | 0.00 | 0.00 | 0.00 |
March | 153.31 | 86.13 | 67.18 | 151.81 | 98.18 | 0.00 | 0.00 | 0.00 |
April | 126.80 | 50.55 | 76.24 | 132.19 | 74.36 | 0.00 | 0.00 | 0.00 |
May | 111.81 | 32.96 | 78.85 | 128.94 | 44.64 | 0.00 | 0.00 | 0.00 |
June | 107.63 | 22.54 | 85.09 | 139.50 | 24.97 | 0.00 | 0.00 | 0.00 |
July | 109.39 | 25.92 | 83.48 | 159.07 | 13.91 | 0.00 | 0.00 | 0.00 |
August | 122.49 | 38.87 | 83.62 | 172.39 | 19.91 | 0.00 | 0.00 | 0.00 |
September | 143.38 | 69.59 | 73.80 | 184.37 | 37.42 | 0.00 | 0.00 | 0.00 |
October | 137.88 | 78.83 | 59.05 | 152.90 | 66.34 | 0.00 | 0.00 | 0.00 |
November | 98.90 | 55.96 | 42.94 | 95.83 | 90.02 | 0.00 | 0.00 | 0.00 |
December | 92.12 | 47.75 | 44.37 | 70.67 | 138.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.86 | 52.74 | 67.12 | 131.56 | 73.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 92.12 | 22.54 | 42.94 | 70.67 | 13.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.31 | 86.13 | 85.09 | 184.37 | 141.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.23 | 17.73 | 57.50 | 19.84 | 295.00 | 0.00 | 0.00 | 0.00 |
February | 122.17 | 31.64 | 90.52 | 50.38 | 278.79 | 0.00 | 0.00 | 0.00 |
March | 191.26 | 82.14 | 109.12 | 151.72 | 190.16 | 0.00 | 0.00 | 0.00 |
April | 233.17 | 95.52 | 137.65 | 221.98 | 133.85 | 0.00 | 0.00 | 0.00 |
May | 275.37 | 124.58 | 150.79 | 311.05 | 80.58 | 0.00 | 0.00 | 0.00 |
June | 331.83 | 155.93 | 175.90 | 422.22 | 45.49 | 0.00 | 0.00 | 0.00 |
July | 296.61 | 129.84 | 166.77 | 407.51 | 25.81 | 0.00 | 0.00 | 0.00 |
August | 268.13 | 113.66 | 154.48 | 359.53 | 36.92 | 0.00 | 0.00 | 0.00 |
September | 210.80 | 90.93 | 119.86 | 252.03 | 69.48 | 0.00 | 0.00 | 0.00 |
October | 137.26 | 48.62 | 88.64 | 122.66 | 128.51 | 0.00 | 0.00 | 0.00 |
November | 80.88 | 23.20 | 57.68 | 47.50 | 177.82 | 0.00 | 0.00 | 0.00 |
December | 69.98 | 15.08 | 54.90 | 18.52 | 283.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.37 | 77.63 | 113.74 | 199.56 | 144.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.98 | 15.08 | 54.90 | 18.52 | 25.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 331.83 | 155.93 | 175.90 | 422.22 | 295.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.59 | 0.00 | 25.59 | 0.08 | 165.18 | 0.00 | 0.00 | 0.00 |
February | 38.98 | 0.00 | 38.98 | 1.96 | 156.60 | 0.00 | 0.00 | 0.00 |
March | 47.28 | 0.00 | 47.28 | 16.10 | 108.37 | 0.00 | 0.00 | 0.00 |
April | 60.37 | 0.34 | 60.03 | 33.78 | 73.20 | 0.00 | 0.00 | 0.00 |
May | 69.94 | 2.91 | 67.04 | 58.09 | 41.88 | 0.00 | 0.00 | 0.00 |
June | 84.37 | 7.31 | 77.06 | 94.38 | 25.13 | 0.00 | 0.00 | 0.00 |
July | 78.58 | 5.46 | 73.12 | 104.53 | 14.73 | 0.00 | 0.00 | 0.00 |
August | 67.97 | 1.34 | 66.63 | 84.97 | 20.98 | 0.00 | 0.00 | 0.00 |
September | 51.47 | 0.03 | 51.44 | 49.87 | 39.43 | 0.00 | 0.00 | 0.00 |
October | 38.44 | 0.00 | 38.44 | 20.87 | 70.13 | 0.00 | 0.00 | 0.00 |
November | 25.83 | 0.00 | 25.83 | 5.94 | 96.72 | 0.00 | 0.00 | 0.00 |
December | 23.95 | 0.00 | 23.95 | 0.34 | 157.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 51.12 | 1.45 | 49.66 | 39.48 | 80.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.95 | 0.00 | 23.95 | 0.08 | 14.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.37 | 7.31 | 77.06 | 104.53 | 165.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.23 | 17.73 | 57.50 | 21.12 | 292.66 | 0.00 | 0.00 | 0.00 |
February | 122.17 | 31.64 | 90.52 | 52.54 | 276.85 | 0.00 | 0.00 | 0.00 |
March | 191.26 | 82.14 | 109.12 | 156.01 | 187.56 | 0.00 | 0.00 | 0.00 |
April | 233.17 | 95.52 | 137.65 | 224.97 | 132.81 | 0.00 | 0.00 | 0.00 |
May | 275.37 | 124.58 | 150.79 | 309.85 | 81.82 | 0.00 | 0.00 | 0.00 |
June | 331.83 | 155.93 | 175.90 | 416.36 | 49.90 | 0.00 | 0.00 | 0.00 |
July | 296.61 | 129.84 | 166.77 | 403.36 | 29.28 | 0.00 | 0.00 | 0.00 |
August | 268.13 | 113.66 | 154.48 | 356.69 | 40.48 | 0.00 | 0.00 | 0.00 |
September | 210.80 | 90.93 | 119.86 | 251.59 | 72.04 | 0.00 | 0.00 | 0.00 |
October | 137.26 | 48.62 | 88.64 | 126.22 | 127.05 | 0.00 | 0.00 | 0.00 |
November | 80.88 | 23.20 | 57.68 | 50.24 | 175.54 | 0.00 | 0.00 | 0.00 |
December | 69.98 | 15.08 | 54.90 | 19.74 | 281.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.37 | 77.63 | 113.74 | 199.86 | 144.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.98 | 15.08 | 54.90 | 19.74 | 29.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 331.83 | 155.93 | 175.90 | 416.36 | 292.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.12 | 51.46 | 36.66 | 73.80 | 100.94 | 0.00 | 0.00 | 0.00 |
February | 99.79 | 47.73 | 52.07 | 82.81 | 98.10 | 0.00 | 0.00 | 0.00 |
March | 122.62 | 68.89 | 53.73 | 112.39 | 96.46 | 0.00 | 0.00 | 0.00 |
April | 101.42 | 40.43 | 60.98 | 94.93 | 80.91 | 0.00 | 0.00 | 0.00 |
May | 89.43 | 26.36 | 63.07 | 91.25 | 55.41 | 0.00 | 0.00 | 0.00 |
June | 86.08 | 18.03 | 68.06 | 98.43 | 35.39 | 0.00 | 0.00 | 0.00 |
July | 87.50 | 20.73 | 66.77 | 112.83 | 24.50 | 0.00 | 0.00 | 0.00 |
August | 97.98 | 31.09 | 66.89 | 125.08 | 31.73 | 0.00 | 0.00 | 0.00 |
September | 114.68 | 55.66 | 59.03 | 135.87 | 49.78 | 0.00 | 0.00 | 0.00 |
October | 110.28 | 63.05 | 47.23 | 110.86 | 77.21 | 0.00 | 0.00 | 0.00 |
November | 79.11 | 44.76 | 34.35 | 69.56 | 94.47 | 0.00 | 0.00 | 0.00 |
December | 73.69 | 38.19 | 35.49 | 58.41 | 100.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 95.87 | 42.18 | 53.69 | 97.28 | 70.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.69 | 18.03 | 34.35 | 58.41 | 24.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.62 | 68.89 | 68.06 | 135.87 | 100.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.47 | 0.00 | 20.47 | 0.00 | 138.72 | 0.00 | 0.00 | 0.00 |
February | 31.19 | 0.00 | 31.19 | 1.04 | 131.01 | 0.00 | 0.00 | 0.00 |
March | 37.83 | 0.00 | 37.83 | 12.25 | 89.06 | 0.00 | 0.00 | 0.00 |
April | 48.30 | 0.27 | 48.03 | 27.29 | 59.50 | 0.00 | 0.00 | 0.00 |
May | 55.96 | 2.32 | 53.64 | 49.32 | 32.98 | 0.00 | 0.00 | 0.00 |
June | 67.50 | 5.85 | 61.66 | 80.51 | 18.33 | 0.00 | 0.00 | 0.00 |
July | 62.87 | 4.37 | 58.51 | 88.08 | 10.38 | 0.00 | 0.00 | 0.00 |
August | 54.38 | 1.07 | 53.31 | 71.96 | 15.31 | 0.00 | 0.00 | 0.00 |
September | 41.18 | 0.02 | 41.16 | 42.19 | 30.17 | 0.00 | 0.00 | 0.00 |
October | 30.76 | 0.00 | 30.76 | 16.40 | 57.85 | 0.00 | 0.00 | 0.00 |
November | 20.67 | 0.00 | 20.67 | 4.18 | 81.70 | 0.00 | 0.00 | 0.00 |
December | 19.16 | 0.00 | 19.16 | 0.17 | 132.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.90 | 1.16 | 39.73 | 32.98 | 66.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.16 | 0.00 | 19.16 | 0.00 | 10.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.50 | 5.85 | 61.66 | 88.08 | 138.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.36 | 28.13 | 59.22 | 31.24 | 286.25 | 0.00 | 0.00 | 0.00 |
February | 128.97 | 39.07 | 89.90 | 56.62 | 270.83 | 0.00 | 0.00 | 0.00 |
March | 185.06 | 77.82 | 107.24 | 142.99 | 186.98 | 0.00 | 0.00 | 0.00 |
April | 243.61 | 107.60 | 136.00 | 231.46 | 129.22 | 0.00 | 0.00 | 0.00 |
May | 272.93 | 120.76 | 152.18 | 306.33 | 76.94 | 0.00 | 0.00 | 0.00 |
June | 304.56 | 134.47 | 170.09 | 384.37 | 42.23 | 0.00 | 0.00 | 0.00 |
July | 292.50 | 128.62 | 163.88 | 400.96 | 23.51 | 0.00 | 0.00 | 0.00 |
August | 264.19 | 110.66 | 153.53 | 352.55 | 34.72 | 0.00 | 0.00 | 0.00 |
September | 220.07 | 97.63 | 122.45 | 263.22 | 66.55 | 0.00 | 0.00 | 0.00 |
October | 149.26 | 61.66 | 87.60 | 135.36 | 124.89 | 0.00 | 0.00 | 0.00 |
November | 84.61 | 27.09 | 57.52 | 51.33 | 174.98 | 0.00 | 0.00 | 0.00 |
December | 68.16 | 14.12 | 54.04 | 15.86 | 279.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 192.06 | 79.16 | 112.90 | 198.47 | 140.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.16 | 14.12 | 54.04 | 15.86 | 23.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 304.56 | 134.47 | 170.09 | 400.96 | 286.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.17 | 64.34 | 45.83 | 89.14 | 141.60 | 0.00 | 0.00 | 0.00 |
February | 124.77 | 59.67 | 65.10 | 98.66 | 139.07 | 0.00 | 0.00 | 0.00 |
March | 153.31 | 86.13 | 67.18 | 150.80 | 97.64 | 0.00 | 0.00 | 0.00 |
April | 126.80 | 50.55 | 76.24 | 130.90 | 74.01 | 0.00 | 0.00 | 0.00 |
May | 111.81 | 32.96 | 78.85 | 128.09 | 44.15 | 0.00 | 0.00 | 0.00 |
June | 107.63 | 22.54 | 85.09 | 139.11 | 24.34 | 0.00 | 0.00 | 0.00 |
July | 109.39 | 25.92 | 83.48 | 158.53 | 13.52 | 0.00 | 0.00 | 0.00 |
August | 122.49 | 38.87 | 83.62 | 171.97 | 19.61 | 0.00 | 0.00 | 0.00 |
September | 143.38 | 69.59 | 73.80 | 183.64 | 37.07 | 0.00 | 0.00 | 0.00 |
October | 137.88 | 78.83 | 59.05 | 152.02 | 66.21 | 0.00 | 0.00 | 0.00 |
November | 98.90 | 55.96 | 42.94 | 95.55 | 89.95 | 0.00 | 0.00 | 0.00 |
December | 92.12 | 47.75 | 44.37 | 70.57 | 138.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.86 | 52.74 | 67.12 | 130.94 | 73.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 92.12 | 22.54 | 42.94 | 70.57 | 13.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.31 | 86.13 | 85.09 | 183.64 | 141.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.59 | 0.00 | 25.59 | 0.07 | 165.41 | 0.00 | 0.00 | 0.00 |
February | 38.98 | 0.00 | 38.98 | 1.82 | 156.79 | 0.00 | 0.00 | 0.00 |
March | 47.28 | 0.00 | 47.28 | 15.45 | 108.13 | 0.00 | 0.00 | 0.00 |
April | 60.37 | 0.34 | 60.03 | 32.58 | 73.15 | 0.00 | 0.00 | 0.00 |
May | 69.94 | 2.91 | 67.04 | 57.81 | 41.26 | 0.00 | 0.00 | 0.00 |
June | 84.37 | 7.31 | 77.06 | 94.93 | 23.80 | 0.00 | 0.00 | 0.00 |
July | 78.58 | 5.46 | 73.12 | 103.62 | 14.12 | 0.00 | 0.00 | 0.00 |
August | 67.97 | 1.34 | 66.63 | 84.29 | 20.31 | 0.00 | 0.00 | 0.00 |
September | 51.47 | 0.03 | 51.44 | 49.26 | 38.45 | 0.00 | 0.00 | 0.00 |
October | 38.44 | 0.00 | 38.44 | 20.04 | 70.00 | 0.00 | 0.00 | 0.00 |
November | 25.83 | 0.00 | 25.83 | 5.67 | 96.63 | 0.00 | 0.00 | 0.00 |
December | 23.95 | 0.00 | 23.95 | 0.33 | 157.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 51.12 | 1.45 | 49.66 | 39.05 | 80.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.95 | 0.00 | 23.95 | 0.07 | 14.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.37 | 7.31 | 77.06 | 103.62 | 165.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.36 | 28.13 | 59.22 | 32.08 | 283.20 | 0.00 | 0.00 | 0.00 |
February | 128.97 | 39.07 | 89.90 | 58.31 | 268.19 | 0.00 | 0.00 | 0.00 |
March | 185.06 | 77.82 | 107.24 | 145.96 | 182.97 | 0.00 | 0.00 | 0.00 |
April | 243.61 | 107.60 | 136.00 | 234.07 | 128.08 | 0.00 | 0.00 | 0.00 |
May | 272.93 | 120.76 | 152.18 | 306.44 | 77.77 | 0.00 | 0.00 | 0.00 |
June | 304.56 | 134.47 | 170.09 | 380.96 | 45.56 | 0.00 | 0.00 | 0.00 |
July | 292.50 | 128.62 | 163.88 | 396.18 | 26.64 | 0.00 | 0.00 | 0.00 |
August | 264.19 | 110.66 | 153.53 | 349.43 | 37.76 | 0.00 | 0.00 | 0.00 |
September | 220.07 | 97.63 | 122.45 | 263.74 | 68.31 | 0.00 | 0.00 | 0.00 |
October | 149.26 | 61.66 | 87.60 | 138.70 | 123.15 | 0.00 | 0.00 | 0.00 |
November | 84.61 | 27.09 | 57.52 | 53.39 | 172.01 | 0.00 | 0.00 | 0.00 |
December | 68.16 | 14.12 | 54.04 | 16.36 | 277.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 192.06 | 79.16 | 112.90 | 198.73 | 140.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.16 | 14.12 | 54.04 | 16.36 | 26.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 304.56 | 134.47 | 170.09 | 396.18 | 283.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.40 | 0.00 | 32.40 | 0.00 | 225.06 | 0.00 | 0.00 | 0.00 |
February | 49.37 | 0.00 | 49.37 | 1.27 | 212.22 | 0.00 | 0.00 | 0.00 |
March | 59.88 | 0.00 | 59.88 | 19.24 | 144.17 | 0.00 | 0.00 | 0.00 |
April | 76.46 | 0.43 | 76.03 | 43.34 | 96.26 | 0.00 | 0.00 | 0.00 |
May | 88.58 | 3.68 | 84.90 | 77.45 | 55.82 | 0.00 | 0.00 | 0.00 |
June | 106.85 | 9.26 | 97.59 | 124.11 | 33.60 | 0.00 | 0.00 | 0.00 |
July | 99.52 | 6.91 | 92.61 | 133.18 | 21.51 | 0.00 | 0.00 | 0.00 |
August | 86.08 | 1.69 | 84.38 | 108.50 | 30.58 | 0.00 | 0.00 | 0.00 |
September | 65.18 | 0.04 | 65.14 | 64.14 | 54.15 | 0.00 | 0.00 | 0.00 |
October | 48.69 | 0.00 | 48.69 | 25.69 | 94.04 | 0.00 | 0.00 | 0.00 |
November | 32.72 | 0.00 | 32.72 | 6.50 | 131.30 | 0.00 | 0.00 | 0.00 |
December | 30.33 | 0.00 | 30.33 | 0.24 | 215.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 64.73 | 1.84 | 62.89 | 50.61 | 108.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.33 | 0.00 | 30.33 | 0.00 | 21.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.85 | 9.26 | 97.59 | 133.18 | 225.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.95 | 0.00 | 11.95 | 0.00 | 82.97 | 0.00 | 0.00 | 0.00 |
February | 18.20 | 0.00 | 18.20 | 0.47 | 78.23 | 0.00 | 0.00 | 0.00 |
March | 22.07 | 0.00 | 22.07 | 7.09 | 53.15 | 0.00 | 0.00 | 0.00 |
April | 28.19 | 0.16 | 28.03 | 15.98 | 35.48 | 0.00 | 0.00 | 0.00 |
May | 32.65 | 1.36 | 31.30 | 28.55 | 20.58 | 0.00 | 0.00 | 0.00 |
June | 39.39 | 3.41 | 35.98 | 45.75 | 12.39 | 0.00 | 0.00 | 0.00 |
July | 36.69 | 2.55 | 34.14 | 49.10 | 7.93 | 0.00 | 0.00 | 0.00 |
August | 31.73 | 0.62 | 31.11 | 40.00 | 11.27 | 0.00 | 0.00 | 0.00 |
September | 24.03 | 0.01 | 24.01 | 23.65 | 19.96 | 0.00 | 0.00 | 0.00 |
October | 17.95 | 0.00 | 17.95 | 9.47 | 34.67 | 0.00 | 0.00 | 0.00 |
November | 12.06 | 0.00 | 12.06 | 2.40 | 48.40 | 0.00 | 0.00 | 0.00 |
December | 11.18 | 0.00 | 11.18 | 0.09 | 79.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.86 | 0.68 | 23.18 | 18.66 | 40.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.18 | 0.00 | 11.18 | 0.00 | 7.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 39.39 | 3.41 | 35.98 | 49.10 | 82.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.41 | 30.02 | 21.38 | 40.78 | 69.81 | 0.00 | 0.00 | 0.00 |
February | 58.22 | 27.84 | 30.37 | 45.15 | 68.20 | 0.00 | 0.00 | 0.00 |
March | 71.53 | 40.19 | 31.34 | 71.09 | 47.27 | 0.00 | 0.00 | 0.00 |
April | 59.16 | 23.59 | 35.58 | 62.54 | 35.69 | 0.00 | 0.00 | 0.00 |
May | 52.17 | 15.38 | 36.79 | 61.30 | 22.19 | 0.00 | 0.00 | 0.00 |
June | 50.22 | 10.52 | 39.70 | 65.52 | 13.65 | 0.00 | 0.00 | 0.00 |
July | 51.04 | 12.09 | 38.95 | 73.59 | 8.62 | 0.00 | 0.00 | 0.00 |
August | 57.16 | 18.14 | 39.02 | 80.14 | 11.82 | 0.00 | 0.00 | 0.00 |
September | 66.90 | 32.47 | 34.43 | 86.35 | 19.77 | 0.00 | 0.00 | 0.00 |
October | 64.34 | 36.78 | 27.55 | 71.95 | 32.36 | 0.00 | 0.00 | 0.00 |
November | 46.15 | 26.11 | 20.04 | 44.68 | 44.17 | 0.00 | 0.00 | 0.00 |
December | 42.99 | 22.28 | 20.70 | 32.14 | 68.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.92 | 24.61 | 31.32 | 61.36 | 36.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.99 | 10.52 | 20.04 | 32.14 | 8.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.53 | 40.19 | 39.70 | 86.35 | 69.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.52 | 81.49 | 58.04 | 110.68 | 189.47 | 0.00 | 0.00 | 0.00 |
February | 158.01 | 75.57 | 82.44 | 122.54 | 185.10 | 0.00 | 0.00 | 0.00 |
March | 194.16 | 109.08 | 85.08 | 192.95 | 128.29 | 0.00 | 0.00 | 0.00 |
April | 160.58 | 64.02 | 96.56 | 169.76 | 96.88 | 0.00 | 0.00 | 0.00 |
May | 141.60 | 41.74 | 99.86 | 166.37 | 60.22 | 0.00 | 0.00 | 0.00 |
June | 136.30 | 28.54 | 107.76 | 177.85 | 37.06 | 0.00 | 0.00 | 0.00 |
July | 138.54 | 32.82 | 105.72 | 199.73 | 23.39 | 0.00 | 0.00 | 0.00 |
August | 155.13 | 49.23 | 105.91 | 217.52 | 32.07 | 0.00 | 0.00 | 0.00 |
September | 181.59 | 88.13 | 93.46 | 234.37 | 53.67 | 0.00 | 0.00 | 0.00 |
October | 174.62 | 99.84 | 74.78 | 195.28 | 87.83 | 0.00 | 0.00 | 0.00 |
November | 125.25 | 70.87 | 54.39 | 121.27 | 119.88 | 0.00 | 0.00 | 0.00 |
December | 116.67 | 60.47 | 56.20 | 87.24 | 185.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.79 | 66.79 | 85.00 | 166.55 | 99.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.67 | 28.54 | 54.39 | 87.24 | 23.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 194.16 | 109.08 | 107.76 | 234.37 | 189.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.17 | 64.34 | 45.83 | 89.37 | 141.30 | 0.00 | 0.00 | 0.00 |
February | 124.77 | 59.67 | 65.10 | 98.71 | 139.14 | 0.00 | 0.00 | 0.00 |
March | 153.31 | 86.13 | 67.18 | 151.22 | 97.88 | 0.00 | 0.00 | 0.00 |
April | 126.80 | 50.55 | 76.24 | 131.27 | 74.18 | 0.00 | 0.00 | 0.00 |
May | 111.81 | 32.96 | 78.85 | 127.75 | 44.40 | 0.00 | 0.00 | 0.00 |
June | 107.63 | 22.54 | 85.09 | 138.26 | 24.67 | 0.00 | 0.00 | 0.00 |
July | 109.39 | 25.92 | 83.48 | 157.90 | 13.56 | 0.00 | 0.00 | 0.00 |
August | 122.49 | 38.87 | 83.62 | 171.26 | 19.49 | 0.00 | 0.00 | 0.00 |
September | 143.38 | 69.59 | 73.80 | 183.38 | 36.88 | 0.00 | 0.00 | 0.00 |
October | 137.88 | 78.83 | 59.05 | 152.30 | 65.77 | 0.00 | 0.00 | 0.00 |
November | 98.90 | 55.96 | 42.94 | 95.68 | 89.28 | 0.00 | 0.00 | 0.00 |
December | 92.12 | 47.75 | 44.37 | 70.42 | 138.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.86 | 52.74 | 67.12 | 130.82 | 73.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 92.12 | 22.54 | 42.94 | 70.42 | 13.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.31 | 86.13 | 85.09 | 183.38 | 141.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.23 | 17.73 | 57.50 | 19.96 | 294.64 | 0.00 | 0.00 | 0.00 |
February | 122.17 | 31.64 | 90.52 | 50.27 | 278.85 | 0.00 | 0.00 | 0.00 |
March | 191.26 | 82.14 | 109.12 | 151.00 | 189.41 | 0.00 | 0.00 | 0.00 |
April | 233.17 | 95.52 | 137.65 | 220.21 | 133.29 | 0.00 | 0.00 | 0.00 |
May | 275.37 | 124.58 | 150.79 | 308.46 | 79.98 | 0.00 | 0.00 | 0.00 |
June | 331.83 | 155.93 | 175.90 | 418.95 | 44.88 | 0.00 | 0.00 | 0.00 |
July | 296.61 | 129.84 | 166.77 | 404.84 | 25.15 | 0.00 | 0.00 | 0.00 |
August | 268.13 | 113.66 | 154.48 | 357.38 | 36.13 | 0.00 | 0.00 | 0.00 |
September | 210.80 | 90.93 | 119.86 | 250.45 | 68.34 | 0.00 | 0.00 | 0.00 |
October | 137.26 | 48.62 | 88.64 | 122.16 | 127.33 | 0.00 | 0.00 | 0.00 |
November | 80.88 | 23.20 | 57.68 | 47.72 | 176.14 | 0.00 | 0.00 | 0.00 |
December | 69.98 | 15.08 | 54.90 | 18.57 | 282.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.37 | 77.63 | 113.74 | 198.30 | 144.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.98 | 15.08 | 54.90 | 18.57 | 25.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 331.83 | 155.93 | 175.90 | 418.95 | 294.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.59 | 0.00 | 25.59 | 0.09 | 164.97 | 0.00 | 0.00 | 0.00 |
February | 38.98 | 0.00 | 38.98 | 2.00 | 156.40 | 0.00 | 0.00 | 0.00 |
March | 47.28 | 0.00 | 47.28 | 16.25 | 107.90 | 0.00 | 0.00 | 0.00 |
April | 60.37 | 0.34 | 60.03 | 33.61 | 72.88 | 0.00 | 0.00 | 0.00 |
May | 69.94 | 2.91 | 67.04 | 57.20 | 41.87 | 0.00 | 0.00 | 0.00 |
June | 84.37 | 7.31 | 77.06 | 93.07 | 25.54 | 0.00 | 0.00 | 0.00 |
July | 78.58 | 5.46 | 73.12 | 103.61 | 14.84 | 0.00 | 0.00 | 0.00 |
August | 67.97 | 1.34 | 66.63 | 84.31 | 21.02 | 0.00 | 0.00 | 0.00 |
September | 51.47 | 0.03 | 51.44 | 49.52 | 39.31 | 0.00 | 0.00 | 0.00 |
October | 38.44 | 0.00 | 38.44 | 21.12 | 69.37 | 0.00 | 0.00 | 0.00 |
November | 25.83 | 0.00 | 25.83 | 6.21 | 95.51 | 0.00 | 0.00 | 0.00 |
December | 23.95 | 0.00 | 23.95 | 0.37 | 157.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 51.12 | 1.45 | 49.66 | 39.18 | 80.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.95 | 0.00 | 23.95 | 0.09 | 14.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.37 | 7.31 | 77.06 | 103.61 | 164.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.23 | 17.73 | 57.50 | 21.09 | 292.64 | 0.00 | 0.00 | 0.00 |
February | 122.17 | 31.64 | 90.52 | 52.24 | 277.12 | 0.00 | 0.00 | 0.00 |
March | 191.26 | 82.14 | 109.12 | 155.54 | 186.92 | 0.00 | 0.00 | 0.00 |
April | 233.17 | 95.52 | 137.65 | 223.41 | 132.19 | 0.00 | 0.00 | 0.00 |
May | 275.37 | 124.58 | 150.79 | 306.80 | 81.73 | 0.00 | 0.00 | 0.00 |
June | 331.83 | 155.93 | 175.90 | 412.20 | 50.54 | 0.00 | 0.00 | 0.00 |
July | 296.61 | 129.84 | 166.77 | 400.28 | 29.35 | 0.00 | 0.00 | 0.00 |
August | 268.13 | 113.66 | 154.48 | 354.28 | 40.42 | 0.00 | 0.00 | 0.00 |
September | 210.80 | 90.93 | 119.86 | 249.81 | 71.56 | 0.00 | 0.00 | 0.00 |
October | 137.26 | 48.62 | 88.64 | 126.11 | 125.70 | 0.00 | 0.00 | 0.00 |
November | 80.88 | 23.20 | 57.68 | 50.73 | 173.78 | 0.00 | 0.00 | 0.00 |
December | 69.98 | 15.08 | 54.90 | 19.72 | 281.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.37 | 77.63 | 113.74 | 198.48 | 144.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.98 | 15.08 | 54.90 | 19.72 | 29.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 331.83 | 155.93 | 175.90 | 412.20 | 292.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 161.58 | 94.36 | 67.21 | 125.47 | 214.46 | 0.00 | 0.00 | 0.00 |
February | 182.98 | 87.51 | 95.47 | 139.00 | 210.46 | 0.00 | 0.00 | 0.00 |
March | 224.84 | 126.32 | 98.52 | 215.85 | 147.62 | 0.00 | 0.00 | 0.00 |
April | 185.96 | 74.14 | 111.82 | 189.85 | 110.34 | 0.00 | 0.00 | 0.00 |
May | 163.98 | 48.34 | 115.64 | 187.83 | 64.58 | 0.00 | 0.00 | 0.00 |
June | 157.84 | 33.05 | 124.79 | 205.83 | 34.48 | 0.00 | 0.00 | 0.00 |
July | 160.44 | 38.01 | 122.43 | 234.61 | 18.56 | 0.00 | 0.00 | 0.00 |
August | 179.65 | 57.01 | 122.64 | 253.06 | 27.58 | 0.00 | 0.00 | 0.00 |
September | 210.29 | 102.05 | 108.23 | 267.94 | 54.29 | 0.00 | 0.00 | 0.00 |
October | 202.22 | 115.61 | 86.60 | 218.97 | 100.02 | 0.00 | 0.00 | 0.00 |
November | 145.05 | 82.07 | 62.98 | 135.93 | 137.09 | 0.00 | 0.00 | 0.00 |
December | 135.11 | 70.03 | 65.08 | 98.98 | 209.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 175.78 | 77.34 | 98.44 | 189.74 | 110.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 135.11 | 33.05 | 62.98 | 98.98 | 18.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 224.84 | 126.32 | 124.79 | 267.94 | 214.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 179.10 | 0.00 | 179.10 | 0.00 | 1353.59 | 0.00 | 0.00 | 0.00 |
February | 272.88 | 0.00 | 272.88 | 3.59 | 1279.92 | 0.00 | 0.00 | 0.00 |
March | 330.96 | 0.00 | 330.96 | 84.63 | 893.84 | 0.00 | 0.00 | 0.00 |
April | 422.60 | 2.38 | 420.21 | 197.58 | 615.54 | 0.00 | 0.00 | 0.00 |
May | 489.58 | 20.34 | 469.24 | 375.30 | 355.19 | 0.00 | 0.00 | 0.00 |
June | 590.57 | 51.17 | 539.40 | 644.47 | 205.48 | 0.00 | 0.00 | 0.00 |
July | 550.04 | 38.19 | 511.84 | 708.87 | 129.04 | 0.00 | 0.00 | 0.00 |
August | 475.75 | 9.36 | 466.39 | 575.65 | 182.43 | 0.00 | 0.00 | 0.00 |
September | 360.26 | 0.20 | 360.06 | 326.68 | 332.85 | 0.00 | 0.00 | 0.00 |
October | 269.10 | 0.00 | 269.10 | 112.58 | 606.49 | 0.00 | 0.00 | 0.00 |
November | 180.83 | 0.00 | 180.83 | 23.77 | 840.52 | 0.00 | 0.00 | 0.00 |
December | 167.63 | 0.00 | 167.63 | 0.67 | 1301.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 357.79 | 10.18 | 347.61 | 256.07 | 671.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 167.63 | 0.00 | 167.63 | 0.00 | 129.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 590.57 | 51.17 | 539.40 | 708.87 | 1353.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 179.10 | 0.00 | 179.10 | 0.00 | 1390.45 | 0.00 | 0.00 | 0.00 |
February | 272.88 | 0.00 | 272.88 | 2.52 | 1316.19 | 0.00 | 0.00 | 0.00 |
March | 330.96 | 0.00 | 330.96 | 78.57 | 919.84 | 0.00 | 0.00 | 0.00 |
April | 422.60 | 2.38 | 420.21 | 186.50 | 633.25 | 0.00 | 0.00 | 0.00 |
May | 489.58 | 20.34 | 469.24 | 362.62 | 365.25 | 0.00 | 0.00 | 0.00 |
June | 590.57 | 51.17 | 539.40 | 633.60 | 211.51 | 0.00 | 0.00 | 0.00 |
July | 550.04 | 38.19 | 511.84 | 699.89 | 133.72 | 0.00 | 0.00 | 0.00 |
August | 475.75 | 9.36 | 466.39 | 566.98 | 188.61 | 0.00 | 0.00 | 0.00 |
September | 360.26 | 0.20 | 360.06 | 317.50 | 343.28 | 0.00 | 0.00 | 0.00 |
October | 269.10 | 0.00 | 269.10 | 104.22 | 626.26 | 0.00 | 0.00 | 0.00 |
November | 180.83 | 0.00 | 180.83 | 20.98 | 869.28 | 0.00 | 0.00 | 0.00 |
December | 167.63 | 0.00 | 167.63 | 0.50 | 1337.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 357.79 | 10.18 | 347.61 | 249.38 | 691.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 167.63 | 0.00 | 167.63 | 0.00 | 133.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 590.57 | 51.17 | 539.40 | 699.89 | 1390.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.59 | 0.00 | 25.59 | 0.18 | 170.09 | 0.00 | 0.00 | 0.00 |
February | 38.98 | 0.00 | 38.98 | 2.08 | 161.26 | 0.00 | 0.00 | 0.00 |
March | 47.28 | 0.00 | 47.28 | 19.57 | 110.89 | 0.00 | 0.00 | 0.00 |
April | 60.37 | 0.34 | 60.03 | 42.43 | 76.71 | 0.00 | 0.00 | 0.00 |
May | 69.94 | 2.91 | 67.04 | 75.60 | 45.30 | 0.00 | 0.00 | 0.00 |
June | 84.37 | 7.31 | 77.06 | 119.51 | 27.43 | 0.00 | 0.00 | 0.00 |
July | 78.58 | 5.46 | 73.12 | 131.02 | 17.25 | 0.00 | 0.00 | 0.00 |
August | 67.97 | 1.34 | 66.63 | 109.55 | 22.99 | 0.00 | 0.00 | 0.00 |
September | 51.47 | 0.03 | 51.44 | 67.11 | 39.56 | 0.00 | 0.00 | 0.00 |
October | 38.44 | 0.00 | 38.44 | 27.39 | 72.05 | 0.00 | 0.00 | 0.00 |
November | 25.83 | 0.00 | 25.83 | 7.91 | 99.81 | 0.00 | 0.00 | 0.00 |
December | 23.95 | 0.00 | 23.95 | 0.51 | 162.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 51.12 | 1.45 | 49.66 | 50.54 | 83.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.95 | 0.00 | 23.95 | 0.18 | 17.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.37 | 7.31 | 77.06 | 131.02 | 170.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 174.70 | 56.27 | 118.44 | 67.54 | 585.13 | 0.00 | 0.00 | 0.00 |
February | 257.93 | 78.13 | 179.80 | 121.75 | 557.43 | 0.00 | 0.00 | 0.00 |
March | 370.10 | 155.64 | 214.46 | 313.39 | 380.94 | 0.00 | 0.00 | 0.00 |
April | 487.18 | 215.19 | 271.98 | 510.26 | 274.12 | 0.00 | 0.00 | 0.00 |
May | 545.83 | 241.49 | 304.34 | 679.65 | 170.42 | 0.00 | 0.00 | 0.00 |
June | 609.09 | 268.93 | 340.16 | 852.97 | 102.98 | 0.00 | 0.00 | 0.00 |
July | 584.95 | 257.21 | 327.74 | 894.88 | 64.72 | 0.00 | 0.00 | 0.00 |
August | 528.34 | 221.31 | 307.03 | 793.78 | 85.93 | 0.00 | 0.00 | 0.00 |
September | 440.12 | 195.24 | 244.88 | 599.24 | 143.88 | 0.00 | 0.00 | 0.00 |
October | 298.49 | 123.31 | 175.18 | 310.85 | 257.30 | 0.00 | 0.00 | 0.00 |
November | 169.22 | 54.18 | 115.03 | 118.43 | 358.96 | 0.00 | 0.00 | 0.00 |
December | 136.32 | 28.24 | 108.08 | 35.45 | 577.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 384.08 | 158.31 | 225.78 | 443.28 | 295.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.32 | 28.24 | 108.08 | 35.45 | 64.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 609.09 | 268.93 | 340.16 | 894.88 | 585.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.17 | 64.34 | 45.83 | 91.30 | 145.87 | 0.00 | 0.00 | 0.00 |
February | 124.77 | 59.67 | 65.10 | 100.67 | 144.14 | 0.00 | 0.00 | 0.00 |
March | 153.31 | 86.13 | 67.18 | 159.68 | 100.95 | 0.00 | 0.00 | 0.00 |
April | 126.80 | 50.55 | 76.24 | 143.06 | 77.80 | 0.00 | 0.00 | 0.00 |
May | 111.81 | 32.96 | 78.85 | 145.03 | 48.24 | 0.00 | 0.00 | 0.00 |
June | 107.63 | 22.54 | 85.09 | 160.61 | 29.18 | 0.00 | 0.00 | 0.00 |
July | 109.39 | 25.92 | 83.48 | 182.44 | 18.10 | 0.00 | 0.00 | 0.00 |
August | 122.49 | 38.87 | 83.62 | 195.02 | 23.61 | 0.00 | 0.00 | 0.00 |
September | 143.38 | 69.59 | 73.80 | 202.67 | 39.62 | 0.00 | 0.00 | 0.00 |
October | 137.88 | 78.83 | 59.05 | 163.61 | 69.02 | 0.00 | 0.00 | 0.00 |
November | 98.90 | 55.96 | 42.94 | 100.79 | 93.77 | 0.00 | 0.00 | 0.00 |
December | 92.12 | 47.75 | 44.37 | 71.93 | 143.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.86 | 52.74 | 67.12 | 143.32 | 77.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 92.12 | 22.54 | 42.94 | 71.93 | 18.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.31 | 86.13 | 85.09 | 202.67 | 145.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.40 | 0.00 | 32.40 | 0.00 | 229.16 | 0.00 | 0.00 | 0.00 |
February | 49.37 | 0.00 | 49.37 | 0.99 | 216.02 | 0.00 | 0.00 | 0.00 |
March | 59.88 | 0.00 | 59.88 | 17.73 | 147.33 | 0.00 | 0.00 | 0.00 |
April | 76.46 | 0.43 | 76.03 | 40.62 | 98.18 | 0.00 | 0.00 | 0.00 |
May | 88.58 | 3.68 | 84.90 | 73.92 | 56.93 | 0.00 | 0.00 | 0.00 |
June | 106.85 | 9.26 | 97.59 | 120.16 | 34.49 | 0.00 | 0.00 | 0.00 |
July | 99.52 | 6.91 | 92.61 | 128.80 | 22.62 | 0.00 | 0.00 | 0.00 |
August | 86.08 | 1.69 | 84.38 | 105.07 | 31.58 | 0.00 | 0.00 | 0.00 |
September | 65.18 | 0.04 | 65.14 | 61.73 | 54.49 | 0.00 | 0.00 | 0.00 |
October | 48.69 | 0.00 | 48.69 | 23.71 | 96.20 | 0.00 | 0.00 | 0.00 |
November | 32.72 | 0.00 | 32.72 | 5.74 | 134.64 | 0.00 | 0.00 | 0.00 |
December | 30.33 | 0.00 | 30.33 | 0.19 | 218.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 64.73 | 1.84 | 62.89 | 48.51 | 111.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.33 | 0.00 | 30.33 | 0.00 | 22.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.85 | 9.26 | 97.59 | 128.80 | 229.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.99 | 0.00 | 28.99 | 0.00 | 205.02 | 0.00 | 0.00 | 0.00 |
February | 44.17 | 0.00 | 44.17 | 0.88 | 193.27 | 0.00 | 0.00 | 0.00 |
March | 53.58 | 0.00 | 53.57 | 15.87 | 131.82 | 0.00 | 0.00 | 0.00 |
April | 68.41 | 0.39 | 68.02 | 36.34 | 87.84 | 0.00 | 0.00 | 0.00 |
May | 79.25 | 3.29 | 75.96 | 66.14 | 50.94 | 0.00 | 0.00 | 0.00 |
June | 95.60 | 8.28 | 87.32 | 107.51 | 30.86 | 0.00 | 0.00 | 0.00 |
July | 89.04 | 6.18 | 82.85 | 115.24 | 20.24 | 0.00 | 0.00 | 0.00 |
August | 77.01 | 1.51 | 75.50 | 94.00 | 28.25 | 0.00 | 0.00 | 0.00 |
September | 58.32 | 0.03 | 58.28 | 55.23 | 48.75 | 0.00 | 0.00 | 0.00 |
October | 43.56 | 0.00 | 43.56 | 21.21 | 86.07 | 0.00 | 0.00 | 0.00 |
November | 29.27 | 0.00 | 29.27 | 5.13 | 120.47 | 0.00 | 0.00 | 0.00 |
December | 27.14 | 0.00 | 27.14 | 0.17 | 195.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.92 | 1.65 | 56.27 | 43.40 | 99.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.14 | 0.00 | 27.14 | 0.00 | 20.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 95.60 | 8.28 | 87.32 | 115.24 | 205.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 411.30 | 240.21 | 171.09 | 320.75 | 567.91 | 0.00 | 0.00 | 0.00 |
February | 465.79 | 222.77 | 243.02 | 353.43 | 555.00 | 0.00 | 0.00 | 0.00 |
March | 572.35 | 321.56 | 250.79 | 558.09 | 385.49 | 0.00 | 0.00 | 0.00 |
April | 473.37 | 188.73 | 284.64 | 489.17 | 291.77 | 0.00 | 0.00 | 0.00 |
May | 417.43 | 123.06 | 294.38 | 478.26 | 181.89 | 0.00 | 0.00 | 0.00 |
June | 401.80 | 84.13 | 317.67 | 511.22 | 112.22 | 0.00 | 0.00 | 0.00 |
July | 408.40 | 96.75 | 311.65 | 574.22 | 72.54 | 0.00 | 0.00 | 0.00 |
August | 457.31 | 145.11 | 312.20 | 629.07 | 97.79 | 0.00 | 0.00 | 0.00 |
September | 535.29 | 259.78 | 275.51 | 681.30 | 159.64 | 0.00 | 0.00 | 0.00 |
October | 514.76 | 294.30 | 220.46 | 565.71 | 264.83 | 0.00 | 0.00 | 0.00 |
November | 369.23 | 208.91 | 160.32 | 350.69 | 362.58 | 0.00 | 0.00 | 0.00 |
December | 343.93 | 178.27 | 165.66 | 252.08 | 557.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 447.46 | 196.88 | 250.58 | 481.07 | 299.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 343.93 | 84.13 | 160.32 | 252.08 | 72.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 572.35 | 321.56 | 317.67 | 681.30 | 567.91 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.149244E+10 | 0.871616E+09 | 0.620826E+09 | 0.120541E+10 | 0.186750E+10 |
February | 0.152659E+10 | 0.730113E+09 | 0.796480E+09 | 0.121822E+10 | 0.164211E+10 |
March | 0.207681E+10 | 0.116679E+10 | 0.910020E+09 | 0.206088E+10 | 0.129571E+10 |
April | 0.166226E+10 | 0.662735E+09 | 0.999522E+09 | 0.174650E+10 | 0.944171E+09 |
May | 0.151468E+10 | 0.446521E+09 | 0.106816E+10 | 0.176989E+10 | 0.595631E+09 |
June | 0.141093E+10 | 0.295438E+09 | 0.111549E+10 | 0.183253E+10 | 0.351565E+09 |
July | 0.148192E+10 | 0.351066E+09 | 0.113085E+10 | 0.211315E+10 | 0.232570E+09 |
August | 0.165938E+10 | 0.526561E+09 | 0.113282E+10 | 0.229976E+10 | 0.320185E+09 |
September | 0.187970E+10 | 0.912236E+09 | 0.967463E+09 | 0.239636E+10 | 0.518969E+09 |
October | 0.186785E+10 | 0.106791E+10 | 0.799941E+09 | 0.206327E+10 | 0.900541E+09 |
November | 0.129658E+10 | 0.733608E+09 | 0.562970E+09 | 0.124958E+10 | 0.116740E+10 |
December | 0.124798E+10 | 0.646864E+09 | 0.601115E+09 | 0.955685E+09 | 0.182022E+10 |
Annual Sum or Average | 0.191171E+11 | 0.841146E+10 | 0.107057E+11 | 0.209112E+11 | 0.116566E+11 |
Minimum of Months | 0.124798E+10 | 0.295438E+09 | 0.562970E+09 | 0.955685E+09 | 0.232570E+09 |
Maximum of Months | 0.207681E+10 | 0.116679E+10 | 0.113282E+10 | 0.239636E+10 | 0.186750E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.420262E+10 | 0.245441E+10 | 0.174821E+10 | 0.334722E+10 | 0.535661E+10 |
February | 0.429879E+10 | 0.205595E+10 | 0.224284E+10 | 0.337974E+10 | 0.470607E+10 |
March | 0.584817E+10 | 0.328562E+10 | 0.256256E+10 | 0.572195E+10 | 0.381366E+10 |
April | 0.468081E+10 | 0.186622E+10 | 0.281459E+10 | 0.483679E+10 | 0.283624E+10 |
May | 0.426524E+10 | 0.125737E+10 | 0.300787E+10 | 0.488047E+10 | 0.186169E+10 |
June | 0.397308E+10 | 0.831935E+09 | 0.314115E+10 | 0.507342E+10 | 0.111311E+10 |
July | 0.417299E+10 | 0.988579E+09 | 0.318441E+10 | 0.588342E+10 | 0.741060E+09 |
August | 0.467271E+10 | 0.148276E+10 | 0.318995E+10 | 0.641045E+10 | 0.101229E+10 |
September | 0.529311E+10 | 0.256880E+10 | 0.272431E+10 | 0.666520E+10 | 0.163580E+10 |
October | 0.525974E+10 | 0.300716E+10 | 0.225258E+10 | 0.572840E+10 | 0.273610E+10 |
November | 0.365108E+10 | 0.206579E+10 | 0.158529E+10 | 0.345787E+10 | 0.346924E+10 |
December | 0.351423E+10 | 0.182153E+10 | 0.169270E+10 | 0.265036E+10 | 0.523441E+10 |
Annual Sum or Average | 0.538326E+11 | 0.236861E+11 | 0.301464E+11 | 0.580353E+11 | 0.345163E+11 |
Minimum of Months | 0.351423E+10 | 0.831935E+09 | 0.158529E+10 | 0.265036E+10 | 0.741060E+09 |
Maximum of Months | 0.584817E+10 | 0.328562E+10 | 0.318995E+10 | 0.666520E+10 | 0.535661E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.545944E+10 | 0.318842E+10 | 0.227102E+10 | 0.439090E+10 | 0.733408E+10 |
February | 0.558437E+10 | 0.267080E+10 | 0.291357E+10 | 0.443644E+10 | 0.643283E+10 |
March | 0.759711E+10 | 0.426820E+10 | 0.332891E+10 | 0.755246E+10 | 0.519556E+10 |
April | 0.608063E+10 | 0.242432E+10 | 0.365631E+10 | 0.637198E+10 | 0.389384E+10 |
May | 0.554079E+10 | 0.163340E+10 | 0.390739E+10 | 0.642597E+10 | 0.257441E+10 |
June | 0.516126E+10 | 0.108073E+10 | 0.408053E+10 | 0.668877E+10 | 0.152773E+10 |
July | 0.542095E+10 | 0.128422E+10 | 0.413673E+10 | 0.778285E+10 | 0.100277E+10 |
August | 0.607012E+10 | 0.192619E+10 | 0.414393E+10 | 0.847839E+10 | 0.136273E+10 |
September | 0.687605E+10 | 0.333701E+10 | 0.353904E+10 | 0.879994E+10 | 0.222725E+10 |
October | 0.683270E+10 | 0.390647E+10 | 0.292623E+10 | 0.752937E+10 | 0.376907E+10 |
November | 0.474296E+10 | 0.268358E+10 | 0.205938E+10 | 0.453666E+10 | 0.480419E+10 |
December | 0.456518E+10 | 0.236627E+10 | 0.219891E+10 | 0.347467E+10 | 0.719524E+10 |
Annual Sum or Average | 0.699316E+11 | 0.307696E+11 | 0.391619E+11 | 0.764684E+11 | 0.473197E+11 |
Minimum of Months | 0.456518E+10 | 0.108073E+10 | 0.205938E+10 | 0.347467E+10 | 0.100277E+10 |
Maximum of Months | 0.759711E+10 | 0.426820E+10 | 0.414393E+10 | 0.879994E+10 | 0.733408E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295082E+09 | 0.172333E+09 | 0.122749E+09 | 0.239815E+09 | 0.379116E+09 |
February | 0.301835E+09 | 0.144356E+09 | 0.157479E+09 | 0.239986E+09 | 0.336537E+09 |
March | 0.410623E+09 | 0.230695E+09 | 0.179928E+09 | 0.406605E+09 | 0.262959E+09 |
April | 0.328659E+09 | 0.131034E+09 | 0.197624E+09 | 0.342636E+09 | 0.192754E+09 |
May | 0.299481E+09 | 88284801.45 | 0.211196E+09 | 0.345358E+09 | 0.119576E+09 |
June | 0.278967E+09 | 58413251.87 | 0.220554E+09 | 0.361597E+09 | 64728547.43 |
July | 0.293003E+09 | 69411819.14 | 0.223592E+09 | 0.426050E+09 | 37243259.85 |
August | 0.328090E+09 | 0.104110E+09 | 0.223980E+09 | 0.461717E+09 | 53329471.95 |
September | 0.371650E+09 | 0.180365E+09 | 0.191286E+09 | 0.477886E+09 | 96992869.12 |
October | 0.369307E+09 | 0.211144E+09 | 0.158163E+09 | 0.409534E+09 | 0.177676E+09 |
November | 0.256356E+09 | 0.145047E+09 | 0.111309E+09 | 0.248402E+09 | 0.233324E+09 |
December | 0.246747E+09 | 0.127896E+09 | 0.118851E+09 | 0.189275E+09 | 0.370175E+09 |
Annual Sum or Average | 0.377980E+10 | 0.166309E+10 | 0.211671E+10 | 0.414886E+10 | 0.232441E+10 |
Minimum of Months | 0.246747E+09 | 58413251.87 | 0.111309E+09 | 0.189275E+09 | 37243259.85 |
Maximum of Months | 0.410623E+09 | 0.230695E+09 | 0.223980E+09 | 0.477886E+09 | 0.379116E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201500E+09 | 47495878.30 | 0.154004E+09 | 53147721.74 | 0.790129E+09 |
February | 0.295544E+09 | 76547281.39 | 0.218996E+09 | 0.121879E+09 | 0.674452E+09 |
March | 0.512275E+09 | 0.219998E+09 | 0.292277E+09 | 0.406376E+09 | 0.509324E+09 |
April | 0.604369E+09 | 0.247592E+09 | 0.356777E+09 | 0.575364E+09 | 0.346942E+09 |
May | 0.737547E+09 | 0.333676E+09 | 0.403871E+09 | 0.833107E+09 | 0.215838E+09 |
June | 0.860098E+09 | 0.404159E+09 | 0.455939E+09 | 0.109441E+10 | 0.117906E+09 |
July | 0.794440E+09 | 0.347755E+09 | 0.446684E+09 | 0.109148E+10 | 69118833.41 |
August | 0.718166E+09 | 0.304420E+09 | 0.413746E+09 | 0.962975E+09 | 98887910.24 |
September | 0.546382E+09 | 0.235695E+09 | 0.310687E+09 | 0.653254E+09 | 0.180092E+09 |
October | 0.367649E+09 | 0.130229E+09 | 0.237420E+09 | 0.328538E+09 | 0.344198E+09 |
November | 0.209628E+09 | 60128040.21 | 0.149500E+09 | 0.123115E+09 | 0.460898E+09 |
December | 0.187434E+09 | 40382403.54 | 0.147052E+09 | 49598606.21 | 0.757998E+09 |
Annual Sum or Average | 0.603503E+10 | 0.244808E+10 | 0.358695E+10 | 0.629324E+10 | 0.456578E+10 |
Minimum of Months | 0.187434E+09 | 40382403.54 | 0.147052E+09 | 49598606.21 | 69118833.41 |
Maximum of Months | 0.860098E+09 | 0.404159E+09 | 0.455939E+09 | 0.109441E+10 | 0.790129E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68530415.20 | 0.00 | 68530415.20 | 217590.59 | 0.442430E+09 |
February | 94310011.14 | 0.00 | 94310011.14 | 4750034.80 | 0.378852E+09 |
March | 0.126641E+09 | 1824.39 | 0.126639E+09 | 43109222.13 | 0.290248E+09 |
April | 0.156487E+09 | 882160.03 | 0.155605E+09 | 87559716.24 | 0.189739E+09 |
May | 0.187336E+09 | 7782830.51 | 0.179553E+09 | 0.155598E+09 | 0.112172E+09 |
June | 0.218686E+09 | 18947034.31 | 0.199739E+09 | 0.244639E+09 | 65139715.08 |
July | 0.210467E+09 | 14614645.10 | 0.195853E+09 | 0.279976E+09 | 39462456.27 |
August | 0.182042E+09 | 3580014.66 | 0.178462E+09 | 0.227580E+09 | 56179521.30 |
September | 0.133406E+09 | 75507.70 | 0.133330E+09 | 0.129267E+09 | 0.102197E+09 |
October | 0.102968E+09 | 0.00 | 0.102968E+09 | 55894125.06 | 0.187834E+09 |
November | 66959962.50 | 0.00 | 66959962.50 | 15396266.51 | 0.250703E+09 |
December | 64142384.00 | 0.00 | 64142384.00 | 917800.56 | 0.422647E+09 |
Annual Sum or Average | 0.161198E+10 | 45884016.69 | 0.156609E+10 | 0.124490E+10 | 0.253760E+10 |
Minimum of Months | 64142384.00 | 0.00 | 64142384.00 | 217590.59 | 39462456.27 |
Maximum of Months | 0.218686E+09 | 18947034.31 | 0.199739E+09 | 0.279976E+09 | 0.442430E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201500E+09 | 47495878.30 | 0.154004E+09 | 56579857.54 | 0.783862E+09 |
February | 0.295544E+09 | 76547281.39 | 0.218996E+09 | 0.127099E+09 | 0.669756E+09 |
March | 0.512275E+09 | 0.219998E+09 | 0.292277E+09 | 0.417864E+09 | 0.502360E+09 |
April | 0.604369E+09 | 0.247592E+09 | 0.356777E+09 | 0.583114E+09 | 0.344250E+09 |
May | 0.737547E+09 | 0.333676E+09 | 0.403871E+09 | 0.829891E+09 | 0.219134E+09 |
June | 0.860098E+09 | 0.404159E+09 | 0.455939E+09 | 0.107921E+10 | 0.129335E+09 |
July | 0.794440E+09 | 0.347755E+09 | 0.446684E+09 | 0.108037E+10 | 78413145.15 |
August | 0.718166E+09 | 0.304420E+09 | 0.413746E+09 | 0.955363E+09 | 0.108423E+09 |
September | 0.546382E+09 | 0.235695E+09 | 0.310687E+09 | 0.652133E+09 | 0.186735E+09 |
October | 0.367649E+09 | 0.130229E+09 | 0.237420E+09 | 0.338060E+09 | 0.340289E+09 |
November | 0.209628E+09 | 60128040.21 | 0.149500E+09 | 0.130212E+09 | 0.455007E+09 |
December | 0.187434E+09 | 40382403.54 | 0.147052E+09 | 52871737.36 | 0.753086E+09 |
Annual Sum or Average | 0.603503E+10 | 0.244808E+10 | 0.358695E+10 | 0.630276E+10 | 0.457065E+10 |
Minimum of Months | 0.187434E+09 | 40382403.54 | 0.147052E+09 | 52871737.36 | 78413145.15 |
Maximum of Months | 0.860098E+09 | 0.404159E+09 | 0.455939E+09 | 0.108037E+10 | 0.783862E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.236019E+09 | 0.137839E+09 | 98179314.65 | 0.197661E+09 | 0.270362E+09 |
February | 0.241420E+09 | 0.115462E+09 | 0.125958E+09 | 0.200333E+09 | 0.237335E+09 |
March | 0.328433E+09 | 0.184520E+09 | 0.143914E+09 | 0.301020E+09 | 0.258352E+09 |
April | 0.262875E+09 | 0.104806E+09 | 0.158068E+09 | 0.246054E+09 | 0.209730E+09 |
May | 0.239537E+09 | 70613797.98 | 0.168923E+09 | 0.244413E+09 | 0.148399E+09 |
June | 0.223129E+09 | 46721309.88 | 0.176408E+09 | 0.255134E+09 | 91738107.33 |
July | 0.234356E+09 | 55518414.20 | 0.178838E+09 | 0.302214E+09 | 65608682.13 |
August | 0.262420E+09 | 83271556.86 | 0.179149E+09 | 0.335027E+09 | 84974419.12 |
September | 0.297261E+09 | 0.144263E+09 | 0.152998E+09 | 0.352175E+09 | 0.129032E+09 |
October | 0.295387E+09 | 0.168881E+09 | 0.126505E+09 | 0.296929E+09 | 0.206795E+09 |
November | 0.205044E+09 | 0.116014E+09 | 89029868.95 | 0.180304E+09 | 0.244860E+09 |
December | 0.197359E+09 | 0.102297E+09 | 95062038.89 | 0.156439E+09 | 0.268461E+09 |
Annual Sum or Average | 0.302324E+10 | 0.133021E+10 | 0.169303E+10 | 0.306770E+10 | 0.221565E+10 |
Minimum of Months | 0.197359E+09 | 46721309.88 | 89029868.95 | 0.156439E+09 | 65608682.13 |
Maximum of Months | 0.328433E+09 | 0.184520E+09 | 0.179149E+09 | 0.352175E+09 | 0.270362E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54831599.44 | 0.00 | 54831599.44 | 13109.76 | 0.371535E+09 |
February | 75458009.98 | 0.00 | 75458009.98 | 2511383.78 | 0.316929E+09 |
March | 0.101326E+09 | 1459.70 | 0.101325E+09 | 32816300.04 | 0.238525E+09 |
April | 0.125206E+09 | 705821.57 | 0.124501E+09 | 70724945.71 | 0.154236E+09 |
May | 0.149888E+09 | 6227089.73 | 0.143661E+09 | 0.132097E+09 | 88325059.15 |
June | 0.174972E+09 | 15159636.67 | 0.159813E+09 | 0.208690E+09 | 47509688.56 |
July | 0.168396E+09 | 11693265.88 | 0.156703E+09 | 0.235917E+09 | 27790560.62 |
August | 0.145653E+09 | 2864391.37 | 0.142789E+09 | 0.192736E+09 | 41004934.97 |
September | 0.106739E+09 | 60414.17 | 0.106678E+09 | 0.109360E+09 | 78189872.55 |
October | 82385417.85 | 0.00 | 82385417.85 | 43912810.04 | 0.154959E+09 |
November | 53575070.74 | 0.00 | 53575070.74 | 10838290.13 | 0.211756E+09 |
December | 51320709.15 | 0.00 | 51320709.15 | 445513.05 | 0.355636E+09 |
Annual Sum or Average | 0.128975E+10 | 36712079.10 | 0.125304E+10 | 0.104006E+10 | 0.208640E+10 |
Minimum of Months | 51320709.15 | 0.00 | 51320709.15 | 13109.76 | 27790560.62 |
Maximum of Months | 0.174972E+09 | 15159636.67 | 0.159813E+09 | 0.235917E+09 | 0.371535E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233977E+09 | 75355657.08 | 0.158622E+09 | 83673886.40 | 0.766688E+09 |
February | 0.312010E+09 | 94512709.61 | 0.217497E+09 | 0.136986E+09 | 0.655186E+09 |
March | 0.495671E+09 | 0.208446E+09 | 0.287225E+09 | 0.382989E+09 | 0.500816E+09 |
April | 0.631427E+09 | 0.278911E+09 | 0.352516E+09 | 0.599950E+09 | 0.334934E+09 |
May | 0.731029E+09 | 0.323430E+09 | 0.407599E+09 | 0.820475E+09 | 0.206066E+09 |
June | 0.789431E+09 | 0.348558E+09 | 0.440873E+09 | 0.996283E+09 | 0.109452E+09 |
July | 0.783424E+09 | 0.344484E+09 | 0.438939E+09 | 0.107394E+10 | 62957840.40 |
August | 0.707599E+09 | 0.296396E+09 | 0.411203E+09 | 0.944265E+09 | 93000893.23 |
September | 0.570434E+09 | 0.253046E+09 | 0.317388E+09 | 0.682278E+09 | 0.172499E+09 |
October | 0.399768E+09 | 0.165145E+09 | 0.234623E+09 | 0.362539E+09 | 0.334501E+09 |
November | 0.219319E+09 | 70227577.39 | 0.149092E+09 | 0.133041E+09 | 0.453542E+09 |
December | 0.182568E+09 | 37820722.34 | 0.144747E+09 | 42484378.72 | 0.749636E+09 |
Annual Sum or Average | 0.605666E+10 | 0.249633E+10 | 0.356032E+10 | 0.625891E+10 | 0.443928E+10 |
Minimum of Months | 0.182568E+09 | 37820722.34 | 0.144747E+09 | 42484378.72 | 62957840.40 |
Maximum of Months | 0.789431E+09 | 0.348558E+09 | 0.440873E+09 | 0.107394E+10 | 0.766688E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295082E+09 | 0.172333E+09 | 0.122749E+09 | 0.238741E+09 | 0.379250E+09 |
February | 0.301835E+09 | 0.144356E+09 | 0.157479E+09 | 0.238674E+09 | 0.336448E+09 |
March | 0.410623E+09 | 0.230695E+09 | 0.179928E+09 | 0.403912E+09 | 0.261506E+09 |
April | 0.328659E+09 | 0.131034E+09 | 0.197624E+09 | 0.339288E+09 | 0.191834E+09 |
May | 0.299481E+09 | 88284801.45 | 0.211196E+09 | 0.343086E+09 | 0.118243E+09 |
June | 0.278967E+09 | 58413251.87 | 0.220554E+09 | 0.360579E+09 | 63094080.86 |
July | 0.293003E+09 | 69411819.14 | 0.223592E+09 | 0.424605E+09 | 36216318.66 |
August | 0.328090E+09 | 0.104110E+09 | 0.223980E+09 | 0.460596E+09 | 52523164.73 |
September | 0.371650E+09 | 0.180365E+09 | 0.191286E+09 | 0.475989E+09 | 96084701.28 |
October | 0.369307E+09 | 0.211144E+09 | 0.158163E+09 | 0.407165E+09 | 0.177329E+09 |
November | 0.256356E+09 | 0.145047E+09 | 0.111309E+09 | 0.247672E+09 | 0.233162E+09 |
December | 0.246747E+09 | 0.127896E+09 | 0.118851E+09 | 0.189006E+09 | 0.369980E+09 |
Annual Sum or Average | 0.377980E+10 | 0.166309E+10 | 0.211671E+10 | 0.412931E+10 | 0.231567E+10 |
Minimum of Months | 0.246747E+09 | 58413251.87 | 0.111309E+09 | 0.189006E+09 | 36216318.66 |
Maximum of Months | 0.410623E+09 | 0.230695E+09 | 0.223980E+09 | 0.475989E+09 | 0.379250E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68530415.20 | 0.00 | 68530415.20 | 176192.35 | 0.443033E+09 |
February | 94310011.14 | 0.00 | 94310011.14 | 4398004.96 | 0.379303E+09 |
March | 0.126641E+09 | 1824.39 | 0.126639E+09 | 41378490.32 | 0.289623E+09 |
April | 0.156487E+09 | 882160.03 | 0.155605E+09 | 84443358.87 | 0.189601E+09 |
May | 0.187336E+09 | 7782830.51 | 0.179553E+09 | 0.154844E+09 | 0.110522E+09 |
June | 0.218686E+09 | 18947034.31 | 0.199739E+09 | 0.246068E+09 | 61692858.31 |
July | 0.210467E+09 | 14614645.10 | 0.195853E+09 | 0.277529E+09 | 37823823.46 |
August | 0.182042E+09 | 3580014.66 | 0.178462E+09 | 0.225769E+09 | 54410315.42 |
September | 0.133406E+09 | 75507.70 | 0.133330E+09 | 0.127690E+09 | 99654761.12 |
October | 0.102968E+09 | 0.00 | 0.102968E+09 | 53675179.89 | 0.187496E+09 |
November | 66959962.50 | 0.00 | 66959962.50 | 14704211.92 | 0.250467E+09 |
December | 64142384.00 | 0.00 | 64142384.00 | 876998.95 | 0.422795E+09 |
Annual Sum or Average | 0.161198E+10 | 45884016.69 | 0.156609E+10 | 0.123155E+10 | 0.252642E+10 |
Minimum of Months | 64142384.00 | 0.00 | 64142384.00 | 176192.35 | 37823823.46 |
Maximum of Months | 0.218686E+09 | 18947034.31 | 0.199739E+09 | 0.277529E+09 | 0.443033E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233977E+09 | 75355657.08 | 0.158622E+09 | 85936081.73 | 0.758528E+09 |
February | 0.312010E+09 | 94512709.61 | 0.217497E+09 | 0.141057E+09 | 0.648809E+09 |
March | 0.495671E+09 | 0.208446E+09 | 0.287225E+09 | 0.390943E+09 | 0.490057E+09 |
April | 0.631427E+09 | 0.278911E+09 | 0.352516E+09 | 0.606700E+09 | 0.331971E+09 |
May | 0.731029E+09 | 0.323430E+09 | 0.407599E+09 | 0.820782E+09 | 0.208297E+09 |
June | 0.789431E+09 | 0.348558E+09 | 0.440873E+09 | 0.987460E+09 | 0.118092E+09 |
July | 0.783424E+09 | 0.344484E+09 | 0.438939E+09 | 0.106113E+10 | 71339295.22 |
August | 0.707599E+09 | 0.296396E+09 | 0.411203E+09 | 0.935911E+09 | 0.101146E+09 |
September | 0.570434E+09 | 0.253046E+09 | 0.317388E+09 | 0.683606E+09 | 0.177050E+09 |
October | 0.399768E+09 | 0.165145E+09 | 0.234623E+09 | 0.371506E+09 | 0.329842E+09 |
November | 0.219319E+09 | 70227577.39 | 0.149092E+09 | 0.138385E+09 | 0.445847E+09 |
December | 0.182568E+09 | 37820722.34 | 0.144747E+09 | 43817309.44 | 0.742891E+09 |
Annual Sum or Average | 0.605666E+10 | 0.249633E+10 | 0.356032E+10 | 0.626724E+10 | 0.442387E+10 |
Minimum of Months | 0.182568E+09 | 37820722.34 | 0.144747E+09 | 43817309.44 | 71339295.22 |
Maximum of Months | 0.789431E+09 | 0.348558E+09 | 0.440873E+09 | 0.106113E+10 | 0.758528E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86789446.82 | 0.00 | 86789446.82 | 2429.61 | 0.602814E+09 |
February | 0.119438E+09 | 0.00 | 0.119438E+09 | 3081567.44 | 0.513412E+09 |
March | 0.160383E+09 | 2310.47 | 0.160381E+09 | 51528033.51 | 0.386136E+09 |
April | 0.198181E+09 | 1117200.01 | 0.197064E+09 | 0.112336E+09 | 0.249495E+09 |
May | 0.237249E+09 | 9856463.77 | 0.227392E+09 | 0.207436E+09 | 0.149503E+09 |
June | 0.276953E+09 | 23995223.46 | 0.252957E+09 | 0.321683E+09 | 87097888.38 |
July | 0.266544E+09 | 18508525.88 | 0.248035E+09 | 0.356708E+09 | 57604230.50 |
August | 0.230545E+09 | 4533862.69 | 0.226011E+09 | 0.290603E+09 | 81903424.52 |
September | 0.168950E+09 | 95625.74 | 0.168854E+09 | 0.166259E+09 | 0.140361E+09 |
October | 0.130403E+09 | 0.00 | 0.130403E+09 | 68807877.34 | 0.251880E+09 |
November | 84800567.57 | 0.00 | 84800567.57 | 16846616.48 | 0.340330E+09 |
December | 81232282.17 | 0.00 | 81232282.17 | 632458.22 | 0.576061E+09 |
Annual Sum or Average | 0.204147E+10 | 58109212.02 | 0.198336E+10 | 0.159592E+10 | 0.343660E+10 |
Minimum of Months | 81232282.17 | 0.00 | 81232282.17 | 2429.61 | 57604230.50 |
Maximum of Months | 0.276953E+09 | 23995223.46 | 0.252957E+09 | 0.356708E+09 | 0.602814E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 31994183.77 | 0.00 | 31994183.77 | 895.66 | 0.222222E+09 |
February | 44029673.81 | 0.00 | 44029673.81 | 1135993.36 | 0.189265E+09 |
March | 59123826.66 | 851.74 | 59122974.93 | 18995366.76 | 0.142346E+09 |
April | 73057843.33 | 411846.18 | 72645997.15 | 41411644.33 | 91974207.23 |
May | 87459788.61 | 3633500.67 | 83826287.94 | 76469423.59 | 55113025.57 |
June | 0.102096E+09 | 8845632.93 | 93250550.55 | 0.118586E+09 | 32107888.10 |
July | 98258997.70 | 6823009.02 | 91435988.69 | 0.131497E+09 | 21235304.57 |
August | 84988325.95 | 1671369.52 | 83316956.43 | 0.107128E+09 | 30192993.63 |
September | 62281914.85 | 35251.61 | 62246663.24 | 61289920.28 | 51742981.70 |
October | 48071809.42 | 0.00 | 48071809.42 | 25365432.70 | 92853653.89 |
November | 31261000.52 | 0.00 | 31261000.52 | 6210360.40 | 0.125460E+09 |
December | 29945582.77 | 0.00 | 29945582.77 | 233150.29 | 0.212360E+09 |
Annual Sum or Average | 0.752569E+09 | 21421461.66 | 0.731148E+09 | 0.588323E+09 | 0.126687E+10 |
Minimum of Months | 29945582.77 | 0.00 | 29945582.77 | 895.66 | 21235304.57 |
Maximum of Months | 0.102096E+09 | 8845632.93 | 93250550.55 | 0.131497E+09 | 0.222222E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137684E+09 | 80410099.32 | 57273978.71 | 0.109219E+09 | 0.186972E+09 |
February | 0.140835E+09 | 67355863.12 | 73478917.38 | 0.109225E+09 | 0.164978E+09 |
March | 0.191595E+09 | 0.107641E+09 | 83953688.63 | 0.190400E+09 | 0.126595E+09 |
April | 0.153351E+09 | 61140012.77 | 92210720.89 | 0.162113E+09 | 92515038.87 |
May | 0.139736E+09 | 41193332.60 | 98543115.21 | 0.164178E+09 | 59424399.92 |
June | 0.130165E+09 | 27255387.93 | 0.102910E+09 | 0.169839E+09 | 35388506.11 |
July | 0.136714E+09 | 32387275.10 | 0.104327E+09 | 0.197095E+09 | 23077250.07 |
August | 0.153086E+09 | 48577374.90 | 0.104508E+09 | 0.214654E+09 | 31649381.81 |
September | 0.173411E+09 | 84157492.03 | 89253060.55 | 0.223819E+09 | 51254503.97 |
October | 0.172317E+09 | 98518817.23 | 73798234.82 | 0.192707E+09 | 86672414.68 |
November | 0.119615E+09 | 67678273.20 | 51936549.34 | 0.115811E+09 | 0.114483E+09 |
December | 0.115131E+09 | 59675840.18 | 55455481.75 | 86087106.48 | 0.183248E+09 |
Annual Sum or Average | 0.176364E+10 | 0.775991E+09 | 0.987649E+09 | 0.193515E+10 | 0.115626E+10 |
Minimum of Months | 0.115131E+09 | 27255387.93 | 51936549.34 | 86087106.48 | 23077250.07 |
Maximum of Months | 0.191595E+09 | 0.107641E+09 | 0.104508E+09 | 0.223819E+09 | 0.186972E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373703E+09 | 0.218249E+09 | 0.155453E+09 | 0.296444E+09 | 0.507480E+09 |
February | 0.382254E+09 | 0.182818E+09 | 0.199437E+09 | 0.296460E+09 | 0.447784E+09 |
March | 0.520028E+09 | 0.292161E+09 | 0.227867E+09 | 0.516784E+09 | 0.343606E+09 |
April | 0.416225E+09 | 0.165947E+09 | 0.250279E+09 | 0.440007E+09 | 0.251105E+09 |
May | 0.379273E+09 | 0.111807E+09 | 0.267466E+09 | 0.445613E+09 | 0.161290E+09 |
June | 0.353294E+09 | 73976697.82 | 0.279318E+09 | 0.460978E+09 | 96051644.14 |
July | 0.371070E+09 | 87905689.30 | 0.283165E+09 | 0.534956E+09 | 62636377.03 |
August | 0.415506E+09 | 0.131849E+09 | 0.283657E+09 | 0.582614E+09 | 85902895.96 |
September | 0.470672E+09 | 0.228421E+09 | 0.242251E+09 | 0.607489E+09 | 0.139115E+09 |
October | 0.467704E+09 | 0.267400E+09 | 0.200304E+09 | 0.523048E+09 | 0.235247E+09 |
November | 0.324659E+09 | 0.183693E+09 | 0.140966E+09 | 0.314335E+09 | 0.310730E+09 |
December | 0.312490E+09 | 0.161972E+09 | 0.150518E+09 | 0.233658E+09 | 0.497374E+09 |
Annual Sum or Average | 0.478688E+10 | 0.210620E+10 | 0.268068E+10 | 0.525239E+10 | 0.313832E+10 |
Minimum of Months | 0.312490E+09 | 73976697.82 | 0.140966E+09 | 0.233658E+09 | 62636377.03 |
Maximum of Months | 0.520028E+09 | 0.292161E+09 | 0.283657E+09 | 0.607489E+09 | 0.507480E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295082E+09 | 0.172333E+09 | 0.122749E+09 | 0.239362E+09 | 0.378452E+09 |
February | 0.301835E+09 | 0.144356E+09 | 0.157479E+09 | 0.238789E+09 | 0.336608E+09 |
March | 0.410623E+09 | 0.230695E+09 | 0.179928E+09 | 0.405020E+09 | 0.262151E+09 |
April | 0.328659E+09 | 0.131034E+09 | 0.197624E+09 | 0.340262E+09 | 0.192268E+09 |
May | 0.299481E+09 | 88284801.45 | 0.211196E+09 | 0.342171E+09 | 0.118911E+09 |
June | 0.278967E+09 | 58413251.87 | 0.220554E+09 | 0.358359E+09 | 63939820.74 |
July | 0.293003E+09 | 69411819.14 | 0.223592E+09 | 0.422920E+09 | 36322732.11 |
August | 0.328090E+09 | 0.104110E+09 | 0.223980E+09 | 0.458710E+09 | 52208267.14 |
September | 0.371650E+09 | 0.180365E+09 | 0.191286E+09 | 0.475310E+09 | 95583440.09 |
October | 0.369307E+09 | 0.211144E+09 | 0.158163E+09 | 0.407930E+09 | 0.176157E+09 |
November | 0.256356E+09 | 0.145047E+09 | 0.111309E+09 | 0.248012E+09 | 0.231407E+09 |
December | 0.246747E+09 | 0.127896E+09 | 0.118851E+09 | 0.188606E+09 | 0.369756E+09 |
Annual Sum or Average | 0.377980E+10 | 0.166309E+10 | 0.211671E+10 | 0.412545E+10 | 0.231376E+10 |
Minimum of Months | 0.246747E+09 | 58413251.87 | 0.111309E+09 | 0.188606E+09 | 36322732.11 |
Maximum of Months | 0.410623E+09 | 0.230695E+09 | 0.223980E+09 | 0.475310E+09 | 0.378452E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201500E+09 | 47495878.30 | 0.154004E+09 | 53470831.42 | 0.789160E+09 |
February | 0.295544E+09 | 76547281.39 | 0.218996E+09 | 0.121615E+09 | 0.674605E+09 |
March | 0.512275E+09 | 0.219998E+09 | 0.292277E+09 | 0.404441E+09 | 0.507315E+09 |
April | 0.604369E+09 | 0.247592E+09 | 0.356777E+09 | 0.570786E+09 | 0.345495E+09 |
May | 0.737547E+09 | 0.333676E+09 | 0.403871E+09 | 0.826167E+09 | 0.214228E+09 |
June | 0.860098E+09 | 0.404159E+09 | 0.455939E+09 | 0.108593E+10 | 0.116322E+09 |
July | 0.794440E+09 | 0.347755E+09 | 0.446684E+09 | 0.108431E+10 | 67353993.04 |
August | 0.718166E+09 | 0.304420E+09 | 0.413746E+09 | 0.957214E+09 | 96768409.90 |
September | 0.546382E+09 | 0.235695E+09 | 0.310687E+09 | 0.649163E+09 | 0.177139E+09 |
October | 0.367649E+09 | 0.130229E+09 | 0.237420E+09 | 0.327181E+09 | 0.341032E+09 |
November | 0.209628E+09 | 60128040.21 | 0.149500E+09 | 0.123692E+09 | 0.456546E+09 |
December | 0.187434E+09 | 40382403.54 | 0.147052E+09 | 49743526.13 | 0.757077E+09 |
Annual Sum or Average | 0.603503E+10 | 0.244808E+10 | 0.358695E+10 | 0.625372E+10 | 0.454304E+10 |
Minimum of Months | 0.187434E+09 | 40382403.54 | 0.147052E+09 | 49743526.13 | 67353993.04 |
Maximum of Months | 0.860098E+09 | 0.404159E+09 | 0.455939E+09 | 0.108593E+10 | 0.789160E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68530415.20 | 0.00 | 68530415.20 | 249908.93 | 0.441843E+09 |
February | 94310011.14 | 0.00 | 94310011.14 | 4843178.06 | 0.378362E+09 |
March | 0.126641E+09 | 1824.39 | 0.126639E+09 | 43521080.55 | 0.288986E+09 |
April | 0.156487E+09 | 882160.03 | 0.155605E+09 | 87127036.75 | 0.188901E+09 |
May | 0.187336E+09 | 7782830.51 | 0.179553E+09 | 0.153217E+09 | 0.112142E+09 |
June | 0.218686E+09 | 18947034.31 | 0.199739E+09 | 0.241237E+09 | 66210529.54 |
July | 0.210467E+09 | 14614645.10 | 0.195853E+09 | 0.277498E+09 | 39751183.45 |
August | 0.182042E+09 | 3580014.66 | 0.178462E+09 | 0.225807E+09 | 56308329.43 |
September | 0.133406E+09 | 75507.70 | 0.133330E+09 | 0.128344E+09 | 0.101888E+09 |
October | 0.102968E+09 | 0.00 | 0.102968E+09 | 56557135.41 | 0.185803E+09 |
November | 66959962.50 | 0.00 | 66959962.50 | 16096835.77 | 0.247567E+09 |
December | 64142384.00 | 0.00 | 64142384.00 | 985486.00 | 0.421436E+09 |
Annual Sum or Average | 0.161198E+10 | 45884016.69 | 0.156609E+10 | 0.123548E+10 | 0.252920E+10 |
Minimum of Months | 64142384.00 | 0.00 | 64142384.00 | 249908.93 | 39751183.45 |
Maximum of Months | 0.218686E+09 | 18947034.31 | 0.199739E+09 | 0.277498E+09 | 0.441843E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201500E+09 | 47495878.30 | 0.154004E+09 | 56486078.88 | 0.783812E+09 |
February | 0.295544E+09 | 76547281.39 | 0.218996E+09 | 0.126389E+09 | 0.670402E+09 |
March | 0.512275E+09 | 0.219998E+09 | 0.292277E+09 | 0.416585E+09 | 0.500650E+09 |
April | 0.604369E+09 | 0.247592E+09 | 0.356777E+09 | 0.579080E+09 | 0.342636E+09 |
May | 0.737547E+09 | 0.333676E+09 | 0.403871E+09 | 0.821722E+09 | 0.218906E+09 |
June | 0.860098E+09 | 0.404159E+09 | 0.455939E+09 | 0.106843E+10 | 0.131001E+09 |
July | 0.794440E+09 | 0.347755E+09 | 0.446684E+09 | 0.107211E+10 | 78607298.40 |
August | 0.718166E+09 | 0.304420E+09 | 0.413746E+09 | 0.948903E+09 | 0.108248E+09 |
September | 0.546382E+09 | 0.235695E+09 | 0.310687E+09 | 0.647502E+09 | 0.185489E+09 |
October | 0.367649E+09 | 0.130229E+09 | 0.237420E+09 | 0.337764E+09 | 0.336668E+09 |
November | 0.209628E+09 | 60128040.21 | 0.149500E+09 | 0.131498E+09 | 0.450440E+09 |
December | 0.187434E+09 | 40382403.54 | 0.147052E+09 | 52825692.69 | 0.752648E+09 |
Annual Sum or Average | 0.603503E+10 | 0.244808E+10 | 0.358695E+10 | 0.625929E+10 | 0.455951E+10 |
Minimum of Months | 0.187434E+09 | 40382403.54 | 0.147052E+09 | 52825692.69 | 78607298.40 |
Maximum of Months | 0.860098E+09 | 0.404159E+09 | 0.455939E+09 | 0.107211E+10 | 0.783812E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.432766E+09 | 0.252744E+09 | 0.180023E+09 | 0.336071E+09 | 0.574408E+09 |
February | 0.442669E+09 | 0.211712E+09 | 0.230958E+09 | 0.336270E+09 | 0.509140E+09 |
March | 0.602218E+09 | 0.338337E+09 | 0.263882E+09 | 0.578140E+09 | 0.395386E+09 |
April | 0.482009E+09 | 0.192174E+09 | 0.289835E+09 | 0.492096E+09 | 0.286010E+09 |
May | 0.439217E+09 | 0.129478E+09 | 0.309739E+09 | 0.503091E+09 | 0.172961E+09 |
June | 0.409132E+09 | 85668639.80 | 0.323464E+09 | 0.533509E+09 | 89377058.46 |
July | 0.429718E+09 | 0.101799E+09 | 0.327918E+09 | 0.628374E+09 | 49710948.80 |
August | 0.481176E+09 | 0.152688E+09 | 0.328488E+09 | 0.677799E+09 | 73871085.00 |
September | 0.545061E+09 | 0.264522E+09 | 0.280539E+09 | 0.694491E+09 | 0.140711E+09 |
October | 0.541624E+09 | 0.309663E+09 | 0.231961E+09 | 0.586492E+09 | 0.267900E+09 |
November | 0.375971E+09 | 0.212725E+09 | 0.163246E+09 | 0.352322E+09 | 0.355327E+09 |
December | 0.361879E+09 | 0.187572E+09 | 0.174307E+09 | 0.265103E+09 | 0.560106E+09 |
Annual Sum or Average | 0.554344E+10 | 0.243908E+10 | 0.310436E+10 | 0.598376E+10 | 0.347491E+10 |
Minimum of Months | 0.361879E+09 | 85668639.80 | 0.163246E+09 | 0.265103E+09 | 49710948.80 |
Maximum of Months | 0.602218E+09 | 0.338337E+09 | 0.328488E+09 | 0.694491E+09 | 0.574408E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.479695E+09 | 0.00 | 0.479695E+09 | 0.00 | 0.362547E+10 |
February | 0.660145E+09 | 0.00 | 0.660145E+09 | 8677293.46 | 0.309638E+10 |
March | 0.886455E+09 | 12770.23 | 0.886442E+09 | 0.226665E+09 | 0.239406E+10 |
April | 0.109537E+10 | 6174886.32 | 0.108919E+10 | 0.512133E+09 | 0.159549E+10 |
May | 0.131130E+10 | 54477750.25 | 0.125682E+10 | 0.100519E+10 | 0.951351E+09 |
June | 0.153075E+10 | 0.132624E+09 | 0.139812E+10 | 0.167046E+10 | 0.532608E+09 |
July | 0.147322E+10 | 0.102299E+09 | 0.137092E+10 | 0.189863E+10 | 0.345609E+09 |
August | 0.127425E+10 | 25059153.55 | 0.124919E+10 | 0.154182E+10 | 0.488620E+09 |
September | 0.933804E+09 | 528533.88 | 0.933276E+09 | 0.846761E+09 | 0.862740E+09 |
October | 0.720750E+09 | 0.00 | 0.720750E+09 | 0.301529E+09 | 0.162441E+10 |
November | 0.468702E+09 | 0.00 | 0.468702E+09 | 61612828.13 | 0.217863E+10 |
December | 0.448980E+09 | 0.00 | 0.448980E+09 | 1791039.99 | 0.348621E+10 |
Annual Sum or Average | 0.112834E+11 | 0.321176E+09 | 0.109622E+11 | 0.807528E+10 | 0.211816E+11 |
Minimum of Months | 0.448980E+09 | 0.00 | 0.448980E+09 | 0.00 | 0.345609E+09 |
Maximum of Months | 0.153075E+10 | 0.132624E+09 | 0.139812E+10 | 0.189863E+10 | 0.362547E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.479695E+09 | 0.00 | 0.479695E+09 | 0.00 | 0.372419E+10 |
February | 0.660145E+09 | 0.00 | 0.660145E+09 | 6097551.12 | 0.318412E+10 |
March | 0.886455E+09 | 12770.23 | 0.886442E+09 | 0.210437E+09 | 0.246369E+10 |
April | 0.109537E+10 | 6174886.32 | 0.108919E+10 | 0.483416E+09 | 0.164138E+10 |
May | 0.131130E+10 | 54477750.25 | 0.125682E+10 | 0.971229E+09 | 0.978289E+09 |
June | 0.153075E+10 | 0.132624E+09 | 0.139812E+10 | 0.164229E+10 | 0.548234E+09 |
July | 0.147322E+10 | 0.102299E+09 | 0.137092E+10 | 0.187460E+10 | 0.358154E+09 |
August | 0.127425E+10 | 25059153.55 | 0.124919E+10 | 0.151859E+10 | 0.505168E+09 |
September | 0.933804E+09 | 528533.88 | 0.933276E+09 | 0.822954E+09 | 0.889773E+09 |
October | 0.720750E+09 | 0.00 | 0.720750E+09 | 0.279148E+09 | 0.167737E+10 |
November | 0.468702E+09 | 0.00 | 0.468702E+09 | 54372302.76 | 0.225317E+10 |
December | 0.448980E+09 | 0.00 | 0.448980E+09 | 1343089.03 | 0.358312E+10 |
Annual Sum or Average | 0.112834E+11 | 0.321176E+09 | 0.109622E+11 | 0.786447E+10 | 0.218067E+11 |
Minimum of Months | 0.448980E+09 | 0.00 | 0.448980E+09 | 0.00 | 0.358154E+09 |
Maximum of Months | 0.153075E+10 | 0.132624E+09 | 0.139812E+10 | 0.187460E+10 | 0.372419E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68530415.20 | 0.00 | 68530415.20 | 482436.93 | 0.455572E+09 |
February | 94310011.14 | 0.00 | 94310011.14 | 5035753.52 | 0.390122E+09 |
March | 0.126641E+09 | 1824.39 | 0.126639E+09 | 52418353.53 | 0.297003E+09 |
April | 0.156487E+09 | 882160.03 | 0.155605E+09 | 0.109991E+09 | 0.198823E+09 |
May | 0.187336E+09 | 7782830.51 | 0.179553E+09 | 0.202499E+09 | 0.121328E+09 |
June | 0.218686E+09 | 18947034.31 | 0.199739E+09 | 0.309780E+09 | 71107296.13 |
July | 0.210467E+09 | 14614645.10 | 0.195853E+09 | 0.350912E+09 | 46202817.43 |
August | 0.182042E+09 | 3580014.66 | 0.178462E+09 | 0.293422E+09 | 61563641.55 |
September | 0.133406E+09 | 75507.70 | 0.133330E+09 | 0.173949E+09 | 0.102552E+09 |
October | 0.102968E+09 | 0.00 | 0.102968E+09 | 73371908.71 | 0.192970E+09 |
November | 66959962.50 | 0.00 | 66959962.50 | 20511481.05 | 0.258698E+09 |
December | 64142384.00 | 0.00 | 64142384.00 | 1373581.59 | 0.436418E+09 |
Annual Sum or Average | 0.161198E+10 | 45884016.69 | 0.156609E+10 | 0.159375E+10 | 0.263236E+10 |
Minimum of Months | 64142384.00 | 0.00 | 64142384.00 | 482436.93 | 46202817.43 |
Maximum of Months | 0.218686E+09 | 18947034.31 | 0.199739E+09 | 0.350912E+09 | 0.455572E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.467921E+09 | 0.150701E+09 | 0.317221E+09 | 0.180892E+09 | 0.156722E+10 |
February | 0.623975E+09 | 0.189012E+09 | 0.434963E+09 | 0.294538E+09 | 0.134855E+10 |
March | 0.991272E+09 | 0.416862E+09 | 0.574409E+09 | 0.839392E+09 | 0.102031E+10 |
April | 0.126276E+10 | 0.557782E+09 | 0.704981E+09 | 0.132259E+10 | 0.710512E+09 |
May | 0.146195E+10 | 0.646815E+09 | 0.815139E+09 | 0.182038E+10 | 0.456440E+09 |
June | 0.157875E+10 | 0.697066E+09 | 0.881683E+09 | 0.221090E+10 | 0.266914E+09 |
July | 0.156674E+10 | 0.688920E+09 | 0.877817E+09 | 0.239684E+10 | 0.173359E+09 |
August | 0.141510E+10 | 0.592750E+09 | 0.822347E+09 | 0.212606E+10 | 0.230151E+09 |
September | 0.114079E+10 | 0.506056E+09 | 0.634732E+09 | 0.155324E+10 | 0.372933E+09 |
October | 0.799480E+09 | 0.330267E+09 | 0.469212E+09 | 0.832590E+09 | 0.689141E+09 |
November | 0.438607E+09 | 0.140445E+09 | 0.298162E+09 | 0.306977E+09 | 0.930421E+09 |
December | 0.365110E+09 | 75636073.19 | 0.289474E+09 | 94953848.57 | 0.154667E+10 |
Annual Sum or Average | 0.121125E+11 | 0.499231E+10 | 0.712014E+10 | 0.139794E+11 | 0.931262E+10 |
Minimum of Months | 0.365110E+09 | 75636073.19 | 0.289474E+09 | 94953848.57 | 0.173359E+09 |
Maximum of Months | 0.157875E+10 | 0.697066E+09 | 0.881683E+09 | 0.239684E+10 | 0.156722E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295082E+09 | 0.172333E+09 | 0.122749E+09 | 0.244542E+09 | 0.390694E+09 |
February | 0.301835E+09 | 0.144356E+09 | 0.157479E+09 | 0.243539E+09 | 0.348703E+09 |
March | 0.410623E+09 | 0.230695E+09 | 0.179928E+09 | 0.427675E+09 | 0.270389E+09 |
April | 0.328659E+09 | 0.131034E+09 | 0.197624E+09 | 0.370800E+09 | 0.201655E+09 |
May | 0.299481E+09 | 88284801.45 | 0.211196E+09 | 0.388445E+09 | 0.129193E+09 |
June | 0.278967E+09 | 58413251.87 | 0.220554E+09 | 0.416300E+09 | 75635662.45 |
July | 0.293003E+09 | 69411819.14 | 0.223592E+09 | 0.488646E+09 | 48476751.35 |
August | 0.328090E+09 | 0.104110E+09 | 0.223980E+09 | 0.522345E+09 | 63239748.71 |
September | 0.371650E+09 | 0.180365E+09 | 0.191286E+09 | 0.525308E+09 | 0.102694E+09 |
October | 0.369307E+09 | 0.211144E+09 | 0.158163E+09 | 0.438222E+09 | 0.184866E+09 |
November | 0.256356E+09 | 0.145047E+09 | 0.111309E+09 | 0.261246E+09 | 0.243047E+09 |
December | 0.246747E+09 | 0.127896E+09 | 0.118851E+09 | 0.192664E+09 | 0.384649E+09 |
Annual Sum or Average | 0.377980E+10 | 0.166309E+10 | 0.211671E+10 | 0.451973E+10 | 0.244324E+10 |
Minimum of Months | 0.246747E+09 | 58413251.87 | 0.111309E+09 | 0.192664E+09 | 48476751.35 |
Maximum of Months | 0.410623E+09 | 0.230695E+09 | 0.223980E+09 | 0.525308E+09 | 0.390694E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86789446.82 | 0.00 | 86789446.82 | 0.00 | 0.613771E+09 |
February | 0.119438E+09 | 0.00 | 0.119438E+09 | 2387869.43 | 0.522593E+09 |
March | 0.160383E+09 | 2310.47 | 0.160381E+09 | 47499864.13 | 0.394618E+09 |
April | 0.198181E+09 | 1117200.01 | 0.197064E+09 | 0.105292E+09 | 0.254491E+09 |
May | 0.237249E+09 | 9856463.77 | 0.227392E+09 | 0.197995E+09 | 0.152493E+09 |
June | 0.276953E+09 | 23995223.46 | 0.252957E+09 | 0.311457E+09 | 89396255.63 |
July | 0.266544E+09 | 18508525.88 | 0.248035E+09 | 0.344972E+09 | 60583147.99 |
August | 0.230545E+09 | 4533862.69 | 0.226011E+09 | 0.281410E+09 | 84575911.60 |
September | 0.168950E+09 | 95625.74 | 0.168854E+09 | 0.160005E+09 | 0.141241E+09 |
October | 0.130403E+09 | 0.00 | 0.130403E+09 | 63492551.77 | 0.257660E+09 |
November | 84800567.57 | 0.00 | 84800567.57 | 14870402.77 | 0.348999E+09 |
December | 81232282.17 | 0.00 | 81232282.17 | 517417.16 | 0.586492E+09 |
Annual Sum or Average | 0.204147E+10 | 58109212.02 | 0.198336E+10 | 0.152990E+10 | 0.350691E+10 |
Minimum of Months | 81232282.17 | 0.00 | 81232282.17 | 0.00 | 60583147.99 |
Maximum of Months | 0.276953E+09 | 23995223.46 | 0.252957E+09 | 0.344972E+09 | 0.613771E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77650846.92 | 0.00 | 77650846.92 | 0.00 | 0.549129E+09 |
February | 0.106861E+09 | 0.00 | 0.106861E+09 | 2136435.82 | 0.467568E+09 |
March | 0.143495E+09 | 2067.19 | 0.143493E+09 | 42498308.41 | 0.353066E+09 |
April | 0.177314E+09 | 999563.08 | 0.176314E+09 | 94204784.17 | 0.227694E+09 |
May | 0.212268E+09 | 8818615.48 | 0.203449E+09 | 0.177147E+09 | 0.136436E+09 |
June | 0.247791E+09 | 21468617.35 | 0.226322E+09 | 0.278661E+09 | 79983168.64 |
July | 0.238478E+09 | 16559648.24 | 0.221918E+09 | 0.308648E+09 | 54203972.06 |
August | 0.206269E+09 | 4056464.12 | 0.202213E+09 | 0.251778E+09 | 75670388.56 |
September | 0.151160E+09 | 85556.71 | 0.151075E+09 | 0.143157E+09 | 0.126369E+09 |
October | 0.116672E+09 | 0.00 | 0.116672E+09 | 56807026.64 | 0.230530E+09 |
November | 75871389.11 | 0.00 | 75871389.11 | 13304605.70 | 0.312245E+09 |
December | 72678830.65 | 0.00 | 72678830.65 | 462935.09 | 0.524725E+09 |
Annual Sum or Average | 0.182651E+10 | 51990532.17 | 0.177452E+10 | 0.136880E+10 | 0.313762E+10 |
Minimum of Months | 72678830.65 | 0.00 | 72678830.65 | 0.00 | 54203972.06 |
Maximum of Months | 0.247791E+09 | 21468617.35 | 0.226322E+09 | 0.308648E+09 | 0.549129E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110163E+10 | 0.643372E+09 | 0.458257E+09 | 0.859088E+09 | 0.152110E+10 |
February | 0.112684E+10 | 0.538923E+09 | 0.587915E+09 | 0.855016E+09 | 0.134265E+10 |
March | 0.153298E+10 | 0.861254E+09 | 0.671725E+09 | 0.149479E+10 | 0.103251E+10 |
April | 0.122698E+10 | 0.489190E+09 | 0.737791E+09 | 0.126794E+10 | 0.756268E+09 |
May | 0.111805E+10 | 0.329593E+09 | 0.788457E+09 | 0.128097E+10 | 0.487170E+09 |
June | 0.104147E+10 | 0.218074E+09 | 0.823394E+09 | 0.132509E+10 | 0.290885E+09 |
July | 0.109387E+10 | 0.259135E+09 | 0.834734E+09 | 0.153799E+10 | 0.194278E+09 |
August | 0.122486E+10 | 0.388674E+09 | 0.836185E+09 | 0.168491E+10 | 0.261908E+09 |
September | 0.138748E+10 | 0.673356E+09 | 0.714126E+09 | 0.176593E+10 | 0.413783E+09 |
October | 0.137873E+10 | 0.788262E+09 | 0.590470E+09 | 0.151519E+10 | 0.709311E+09 |
November | 0.957055E+09 | 0.541503E+09 | 0.415551E+09 | 0.908999E+09 | 0.939803E+09 |
December | 0.921181E+09 | 0.477475E+09 | 0.443707E+09 | 0.675177E+09 | 0.149452E+10 |
Annual Sum or Average | 0.141111E+11 | 0.620881E+10 | 0.790231E+10 | 0.151711E+11 | 0.944418E+10 |
Minimum of Months | 0.921181E+09 | 0.218074E+09 | 0.415551E+09 | 0.675177E+09 | 0.194278E+09 |
Maximum of Months | 0.153298E+10 | 0.861254E+09 | 0.836185E+09 | 0.176593E+10 | 0.152110E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 450.05 | 697.25 | 557.21 | 325.42 | 231.79 | 0.00 | 0.00 |
February | 503.56 | 678.78 | 631.03 | 301.80 | 329.23 | 0.00 | 0.00 |
March | 769.44 | 483.76 | 775.39 | 435.63 | 339.76 | 0.00 | 0.00 |
April | 673.80 | 364.26 | 641.30 | 255.68 | 385.62 | 0.00 | 0.00 |
May | 660.80 | 222.38 | 565.52 | 166.71 | 398.81 | 0.00 | 0.00 |
June | 706.99 | 135.63 | 544.34 | 113.98 | 430.36 | 0.00 | 0.00 |
July | 788.96 | 86.83 | 553.29 | 131.07 | 422.21 | 0.00 | 0.00 |
August | 858.63 | 119.54 | 619.54 | 196.60 | 422.95 | 0.00 | 0.00 |
September | 924.52 | 200.22 | 725.19 | 351.94 | 373.25 | 0.00 | 0.00 |
October | 770.34 | 336.22 | 697.37 | 398.71 | 298.66 | 0.00 | 0.00 |
November | 482.09 | 450.39 | 500.22 | 283.03 | 217.20 | 0.00 | 0.00 |
December | 356.81 | 679.59 | 465.94 | 241.51 | 224.43 | 0.00 | 0.00 |
Annual Sum or Average | 663.09 | 369.63 | 606.20 | 266.73 | 339.47 | 0.00 | 0.00 |
Minimum of Months | 356.81 | 86.83 | 465.94 | 113.98 | 217.20 | 0.00 | 0.00 |
Maximum of Months | 924.52 | 697.25 | 775.39 | 435.63 | 430.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1249.71 | 1999.93 | 1569.08 | 916.37 | 652.71 | 0.00 | 0.00 |
February | 1397.05 | 1945.30 | 1776.95 | 849.85 | 927.10 | 0.00 | 0.00 |
March | 2136.33 | 1423.86 | 2183.46 | 1226.71 | 956.75 | 0.00 | 0.00 |
April | 1866.04 | 1094.23 | 1805.87 | 719.99 | 1085.87 | 0.00 | 0.00 |
May | 1822.16 | 695.08 | 1592.46 | 469.45 | 1123.01 | 0.00 | 0.00 |
June | 1957.34 | 429.44 | 1532.82 | 320.96 | 1211.86 | 0.00 | 0.00 |
July | 2196.62 | 276.68 | 1558.02 | 369.09 | 1188.92 | 0.00 | 0.00 |
August | 2393.39 | 377.95 | 1744.59 | 553.60 | 1190.99 | 0.00 | 0.00 |
September | 2571.45 | 631.10 | 2042.09 | 991.05 | 1051.05 | 0.00 | 0.00 |
October | 2138.74 | 1021.54 | 1963.76 | 1122.74 | 841.02 | 0.00 | 0.00 |
November | 1334.06 | 1338.44 | 1408.59 | 796.99 | 611.61 | 0.00 | 0.00 |
December | 989.53 | 1954.30 | 1312.06 | 680.08 | 631.98 | 0.00 | 0.00 |
Annual Sum or Average | 1840.29 | 1094.50 | 1707.02 | 751.08 | 955.94 | 0.00 | 0.00 |
Minimum of Months | 989.53 | 276.68 | 1312.06 | 320.96 | 611.61 | 0.00 | 0.00 |
Maximum of Months | 2571.45 | 1999.93 | 2183.46 | 1226.71 | 1211.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1639.37 | 2738.23 | 2038.32 | 1190.42 | 847.90 | 0.00 | 0.00 |
February | 1833.85 | 2659.07 | 2308.35 | 1104.00 | 1204.35 | 0.00 | 0.00 |
March | 2819.76 | 1939.80 | 2836.44 | 1593.56 | 1242.87 | 0.00 | 0.00 |
April | 2458.33 | 1502.25 | 2345.92 | 935.31 | 1410.61 | 0.00 | 0.00 |
May | 2399.18 | 961.17 | 2068.69 | 609.84 | 1458.85 | 0.00 | 0.00 |
June | 2580.55 | 589.40 | 1991.23 | 416.95 | 1574.28 | 0.00 | 0.00 |
July | 2905.78 | 374.39 | 2023.95 | 479.47 | 1544.48 | 0.00 | 0.00 |
August | 3165.47 | 508.78 | 2266.32 | 719.16 | 1547.16 | 0.00 | 0.00 |
September | 3395.04 | 859.28 | 2652.80 | 1287.43 | 1365.37 | 0.00 | 0.00 |
October | 2811.14 | 1407.21 | 2551.04 | 1458.51 | 1092.53 | 0.00 | 0.00 |
November | 1750.25 | 1853.47 | 1829.85 | 1035.33 | 794.51 | 0.00 | 0.00 |
December | 1297.29 | 2686.40 | 1704.44 | 883.46 | 820.98 | 0.00 | 0.00 |
Annual Sum or Average | 2424.80 | 1500.50 | 2217.52 | 975.70 | 1241.82 | 0.00 | 0.00 |
Minimum of Months | 1297.29 | 374.39 | 1704.44 | 416.95 | 794.51 | 0.00 | 0.00 |
Maximum of Months | 3395.04 | 2738.23 | 2836.44 | 1593.56 | 1574.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 91.18 | 418.35 | 185.40 | 82.07 | 103.33 | 0.00 | 0.00 |
February | 137.73 | 406.06 | 246.93 | 91.31 | 155.62 | 0.00 | 0.00 |
March | 293.50 | 278.30 | 344.57 | 168.27 | 176.30 | 0.00 | 0.00 |
April | 350.95 | 205.00 | 359.96 | 146.08 | 213.89 | 0.00 | 0.00 |
May | 438.71 | 123.95 | 387.18 | 157.54 | 229.64 | 0.00 | 0.00 |
June | 561.15 | 69.88 | 439.45 | 178.46 | 260.99 | 0.00 | 0.00 |
July | 566.51 | 39.64 | 406.00 | 155.75 | 250.25 | 0.00 | 0.00 |
August | 531.82 | 56.73 | 390.63 | 152.53 | 238.10 | 0.00 | 0.00 |
September | 435.55 | 106.05 | 354.18 | 160.52 | 193.66 | 0.00 | 0.00 |
October | 272.41 | 191.69 | 275.15 | 127.45 | 147.69 | 0.00 | 0.00 |
November | 138.62 | 263.12 | 179.78 | 79.16 | 100.62 | 0.00 | 0.00 |
December | 77.25 | 409.28 | 162.10 | 62.83 | 99.28 | 0.00 | 0.00 |
Annual Sum or Average | 325.64 | 213.01 | 311.23 | 130.36 | 180.86 | 0.00 | 0.00 |
Minimum of Months | 77.25 | 39.64 | 162.10 | 62.83 | 99.28 | 0.00 | 0.00 |
Maximum of Months | 566.51 | 418.35 | 439.45 | 178.46 | 260.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 16.35 | 452.99 | 100.82 | 17.73 | 83.08 | 0.00 | 0.00 |
February | 48.52 | 427.47 | 161.15 | 31.64 | 129.51 | 0.00 | 0.00 |
March | 164.89 | 288.71 | 238.54 | 82.14 | 156.41 | 0.00 | 0.00 |
April | 256.40 | 203.66 | 293.54 | 95.86 | 197.68 | 0.00 | 0.00 |
May | 366.97 | 122.73 | 345.31 | 127.49 | 217.83 | 0.00 | 0.00 |
June | 508.86 | 73.15 | 416.20 | 163.24 | 252.96 | 0.00 | 0.00 |
July | 506.66 | 42.77 | 375.19 | 135.29 | 239.90 | 0.00 | 0.00 |
August | 441.08 | 60.88 | 336.10 | 114.99 | 221.11 | 0.00 | 0.00 |
September | 300.57 | 110.57 | 262.26 | 90.96 | 171.30 | 0.00 | 0.00 |
October | 145.53 | 195.62 | 175.71 | 48.62 | 127.09 | 0.00 | 0.00 |
November | 54.02 | 270.11 | 106.71 | 23.20 | 83.51 | 0.00 | 0.00 |
December | 15.67 | 434.55 | 93.93 | 15.08 | 78.85 | 0.00 | 0.00 |
Annual Sum or Average | 236.51 | 222.57 | 242.49 | 79.08 | 163.40 | 0.00 | 0.00 |
Minimum of Months | 15.67 | 42.77 | 93.93 | 15.08 | 78.85 | 0.00 | 0.00 |
Maximum of Months | 508.86 | 452.99 | 416.20 | 163.24 | 252.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 73.80 | 100.94 | 88.12 | 51.46 | 36.66 | 0.00 | 0.00 |
February | 82.81 | 98.10 | 99.79 | 47.73 | 52.07 | 0.00 | 0.00 |
March | 112.39 | 96.46 | 122.62 | 68.89 | 53.73 | 0.00 | 0.00 |
April | 94.93 | 80.91 | 101.42 | 40.43 | 60.98 | 0.00 | 0.00 |
May | 91.25 | 55.41 | 89.43 | 26.36 | 63.07 | 0.00 | 0.00 |
June | 98.43 | 35.39 | 86.08 | 18.03 | 68.06 | 0.00 | 0.00 |
July | 112.83 | 24.50 | 87.50 | 20.73 | 66.77 | 0.00 | 0.00 |
August | 125.08 | 31.73 | 97.98 | 31.09 | 66.89 | 0.00 | 0.00 |
September | 135.87 | 49.78 | 114.68 | 55.66 | 59.03 | 0.00 | 0.00 |
October | 110.86 | 77.21 | 110.28 | 63.05 | 47.23 | 0.00 | 0.00 |
November | 69.56 | 94.47 | 79.11 | 44.76 | 34.35 | 0.00 | 0.00 |
December | 58.41 | 100.23 | 73.69 | 38.19 | 35.49 | 0.00 | 0.00 |
Annual Sum or Average | 97.28 | 70.26 | 95.87 | 42.18 | 53.69 | 0.00 | 0.00 |
Minimum of Months | 58.41 | 24.50 | 73.69 | 18.03 | 34.35 | 0.00 | 0.00 |
Maximum of Months | 135.87 | 100.94 | 122.62 | 68.89 | 68.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 138.72 | 20.47 | 0.00 | 20.47 | 0.00 | 0.00 |
February | 1.04 | 131.01 | 31.19 | 0.00 | 31.19 | 0.00 | 0.00 |
March | 12.25 | 89.06 | 37.83 | 0.00 | 37.83 | 0.00 | 0.00 |
April | 27.29 | 59.50 | 48.30 | 0.27 | 48.03 | 0.00 | 0.00 |
May | 49.32 | 32.98 | 55.96 | 2.32 | 53.64 | 0.00 | 0.00 |
June | 80.51 | 18.33 | 67.50 | 5.85 | 61.66 | 0.00 | 0.00 |
July | 88.08 | 10.38 | 62.87 | 4.37 | 58.51 | 0.00 | 0.00 |
August | 71.96 | 15.31 | 54.38 | 1.07 | 53.31 | 0.00 | 0.00 |
September | 42.19 | 30.17 | 41.18 | 0.02 | 41.16 | 0.00 | 0.00 |
October | 16.40 | 57.85 | 30.76 | 0.00 | 30.76 | 0.00 | 0.00 |
November | 4.18 | 81.70 | 20.67 | 0.00 | 20.67 | 0.00 | 0.00 |
December | 0.17 | 132.78 | 19.16 | 0.00 | 19.16 | 0.00 | 0.00 |
Annual Sum or Average | 32.98 | 66.16 | 40.90 | 1.16 | 39.73 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 10.38 | 19.16 | 0.00 | 19.16 | 0.00 | 0.00 |
Maximum of Months | 88.08 | 138.72 | 67.50 | 5.85 | 61.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 108.10 | 415.57 | 197.53 | 92.48 | 105.05 | 0.00 | 0.00 |
February | 147.06 | 401.68 | 253.74 | 98.74 | 155.00 | 0.00 | 0.00 |
March | 284.78 | 275.60 | 338.37 | 163.96 | 174.42 | 0.00 | 0.00 |
April | 358.45 | 199.32 | 370.40 | 158.16 | 212.25 | 0.00 | 0.00 |
May | 431.85 | 118.51 | 384.75 | 153.72 | 231.03 | 0.00 | 0.00 |
June | 521.86 | 64.95 | 412.19 | 157.01 | 255.18 | 0.00 | 0.00 |
July | 558.58 | 36.11 | 401.89 | 154.53 | 247.36 | 0.00 | 0.00 |
August | 523.57 | 53.39 | 386.68 | 149.53 | 237.15 | 0.00 | 0.00 |
September | 445.44 | 102.19 | 363.46 | 167.21 | 196.25 | 0.00 | 0.00 |
October | 285.72 | 189.44 | 287.14 | 140.49 | 146.65 | 0.00 | 0.00 |
November | 143.37 | 261.42 | 183.52 | 83.05 | 100.46 | 0.00 | 0.00 |
December | 74.71 | 406.30 | 160.29 | 61.87 | 98.42 | 0.00 | 0.00 |
Annual Sum or Average | 324.60 | 209.39 | 311.91 | 131.89 | 180.02 | 0.00 | 0.00 |
Minimum of Months | 74.71 | 36.11 | 160.29 | 61.87 | 98.42 | 0.00 | 0.00 |
Maximum of Months | 558.58 | 415.57 | 412.19 | 167.21 | 255.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 23.51 | 439.97 | 112.94 | 28.13 | 84.81 | 0.00 | 0.00 |
February | 51.37 | 416.22 | 167.96 | 39.07 | 128.89 | 0.00 | 0.00 |
March | 153.03 | 282.72 | 232.34 | 77.83 | 154.52 | 0.00 | 0.00 |
April | 262.55 | 197.13 | 303.98 | 107.94 | 196.03 | 0.00 | 0.00 |
May | 362.77 | 117.55 | 342.88 | 123.66 | 219.22 | 0.00 | 0.00 |
June | 474.98 | 68.45 | 388.93 | 141.78 | 247.15 | 0.00 | 0.00 |
July | 499.58 | 40.54 | 371.08 | 134.07 | 237.00 | 0.00 | 0.00 |
August | 433.42 | 57.77 | 332.15 | 112.00 | 220.16 | 0.00 | 0.00 |
September | 311.22 | 104.97 | 271.54 | 97.65 | 173.89 | 0.00 | 0.00 |
October | 155.53 | 189.94 | 187.70 | 61.66 | 126.04 | 0.00 | 0.00 |
November | 56.06 | 265.64 | 110.45 | 27.09 | 83.35 | 0.00 | 0.00 |
December | 11.96 | 430.49 | 92.11 | 14.12 | 77.99 | 0.00 | 0.00 |
Annual Sum or Average | 234.02 | 216.63 | 243.17 | 80.61 | 162.56 | 0.00 | 0.00 |
Minimum of Months | 11.96 | 40.54 | 92.11 | 14.12 | 77.99 | 0.00 | 0.00 |
Maximum of Months | 499.58 | 439.97 | 388.93 | 141.78 | 247.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 122.22 | 538.07 | 235.28 | 111.51 | 123.77 | 0.00 | 0.00 |
February | 148.90 | 523.21 | 283.79 | 103.41 | 180.38 | 0.00 | 0.00 |
March | 276.10 | 358.61 | 347.64 | 149.27 | 198.37 | 0.00 | 0.00 |
April | 290.73 | 263.42 | 324.39 | 88.20 | 236.19 | 0.00 | 0.00 |
May | 331.72 | 156.86 | 315.01 | 62.16 | 252.85 | 0.00 | 0.00 |
June | 410.00 | 93.47 | 332.76 | 51.73 | 281.03 | 0.00 | 0.00 |
July | 453.81 | 59.65 | 325.79 | 54.37 | 271.42 | 0.00 | 0.00 |
August | 445.31 | 84.89 | 330.09 | 69.68 | 260.41 | 0.00 | 0.00 |
September | 408.12 | 147.17 | 337.70 | 120.64 | 217.05 | 0.00 | 0.00 |
October | 297.95 | 244.46 | 305.59 | 136.62 | 168.97 | 0.00 | 0.00 |
November | 166.36 | 335.26 | 216.18 | 96.98 | 119.20 | 0.00 | 0.00 |
December | 97.18 | 525.95 | 201.16 | 82.75 | 118.41 | 0.00 | 0.00 |
Annual Sum or Average | 288.16 | 276.31 | 296.31 | 93.92 | 202.40 | 0.00 | 0.00 |
Minimum of Months | 97.18 | 59.65 | 201.16 | 51.73 | 118.41 | 0.00 | 0.00 |
Maximum of Months | 453.81 | 538.07 | 347.64 | 149.27 | 281.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 91.30 | 417.91 | 185.40 | 82.07 | 103.33 | 0.00 | 0.00 |
February | 137.11 | 406.13 | 246.93 | 91.31 | 155.62 | 0.00 | 0.00 |
March | 292.26 | 277.33 | 344.57 | 168.27 | 176.30 | 0.00 | 0.00 |
April | 348.25 | 204.23 | 359.96 | 146.08 | 213.89 | 0.00 | 0.00 |
May | 434.87 | 123.04 | 387.18 | 157.54 | 229.64 | 0.00 | 0.00 |
June | 556.61 | 68.94 | 439.45 | 178.46 | 260.99 | 0.00 | 0.00 |
July | 562.66 | 38.63 | 406.00 | 155.75 | 250.25 | 0.00 | 0.00 |
August | 528.53 | 55.51 | 390.63 | 152.53 | 238.10 | 0.00 | 0.00 |
September | 432.98 | 104.37 | 354.18 | 160.52 | 193.66 | 0.00 | 0.00 |
October | 271.41 | 190.04 | 275.15 | 127.45 | 147.69 | 0.00 | 0.00 |
November | 138.84 | 260.85 | 179.78 | 79.16 | 100.62 | 0.00 | 0.00 |
December | 77.11 | 408.83 | 162.10 | 62.83 | 99.28 | 0.00 | 0.00 |
Annual Sum or Average | 323.68 | 211.98 | 311.23 | 130.36 | 180.86 | 0.00 | 0.00 |
Minimum of Months | 77.11 | 38.63 | 162.10 | 62.83 | 99.28 | 0.00 | 0.00 |
Maximum of Months | 562.66 | 417.91 | 439.45 | 178.46 | 260.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 16.40 | 452.82 | 100.82 | 17.73 | 83.08 | 0.00 | 0.00 |
February | 48.37 | 427.64 | 161.15 | 31.64 | 129.51 | 0.00 | 0.00 |
March | 164.66 | 287.69 | 238.54 | 82.14 | 156.41 | 0.00 | 0.00 |
April | 254.63 | 202.67 | 293.54 | 95.86 | 197.68 | 0.00 | 0.00 |
May | 363.03 | 122.63 | 345.31 | 127.49 | 217.83 | 0.00 | 0.00 |
June | 503.42 | 74.23 | 416.20 | 163.24 | 252.96 | 0.00 | 0.00 |
July | 502.69 | 42.99 | 375.19 | 135.29 | 239.90 | 0.00 | 0.00 |
August | 438.00 | 60.85 | 336.10 | 114.99 | 221.11 | 0.00 | 0.00 |
September | 298.31 | 109.86 | 262.26 | 90.96 | 171.30 | 0.00 | 0.00 |
October | 145.66 | 193.51 | 175.71 | 48.62 | 127.09 | 0.00 | 0.00 |
November | 54.88 | 267.23 | 106.71 | 23.20 | 83.51 | 0.00 | 0.00 |
December | 15.76 | 434.02 | 93.93 | 15.08 | 78.85 | 0.00 | 0.00 |
Annual Sum or Average | 234.86 | 221.98 | 242.49 | 79.08 | 163.40 | 0.00 | 0.00 |
Minimum of Months | 15.76 | 42.99 | 93.93 | 15.08 | 78.85 | 0.00 | 0.00 |
Maximum of Months | 503.42 | 452.82 | 416.20 | 163.24 | 252.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 125.47 | 214.46 | 161.58 | 94.36 | 67.21 | 0.00 | 0.00 |
February | 139.00 | 210.46 | 182.98 | 87.51 | 95.47 | 0.00 | 0.00 |
March | 215.85 | 147.62 | 224.84 | 126.32 | 98.52 | 0.00 | 0.00 |
April | 189.85 | 110.34 | 185.96 | 74.14 | 111.82 | 0.00 | 0.00 |
May | 187.83 | 64.58 | 163.98 | 48.34 | 115.64 | 0.00 | 0.00 |
June | 205.83 | 34.48 | 157.84 | 33.05 | 124.79 | 0.00 | 0.00 |
July | 234.61 | 18.56 | 160.44 | 38.01 | 122.43 | 0.00 | 0.00 |
August | 253.06 | 27.58 | 179.65 | 57.01 | 122.64 | 0.00 | 0.00 |
September | 267.94 | 54.29 | 210.29 | 102.05 | 108.23 | 0.00 | 0.00 |
October | 218.97 | 100.02 | 202.22 | 115.61 | 86.60 | 0.00 | 0.00 |
November | 135.93 | 137.09 | 145.05 | 82.07 | 62.98 | 0.00 | 0.00 |
December | 98.98 | 209.12 | 135.11 | 70.03 | 65.08 | 0.00 | 0.00 |
Annual Sum or Average | 189.74 | 110.19 | 175.78 | 77.34 | 98.44 | 0.00 | 0.00 |
Minimum of Months | 98.98 | 18.56 | 135.11 | 33.05 | 62.98 | 0.00 | 0.00 |
Maximum of Months | 267.94 | 214.46 | 224.84 | 126.32 | 124.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1353.59 | 179.10 | 0.00 | 179.10 | 0.00 | 0.00 |
February | 3.59 | 1279.92 | 272.88 | 0.00 | 272.88 | 0.00 | 0.00 |
March | 84.63 | 893.84 | 330.96 | 0.00 | 330.96 | 0.00 | 0.00 |
April | 197.58 | 615.54 | 422.60 | 2.38 | 420.21 | 0.00 | 0.00 |
May | 375.30 | 355.19 | 489.58 | 20.34 | 469.24 | 0.00 | 0.00 |
June | 644.47 | 205.48 | 590.57 | 51.17 | 539.40 | 0.00 | 0.00 |
July | 708.87 | 129.04 | 550.04 | 38.19 | 511.84 | 0.00 | 0.00 |
August | 575.65 | 182.43 | 475.75 | 9.36 | 466.39 | 0.00 | 0.00 |
September | 326.68 | 332.85 | 360.26 | 0.20 | 360.06 | 0.00 | 0.00 |
October | 112.58 | 606.49 | 269.10 | 0.00 | 269.10 | 0.00 | 0.00 |
November | 23.77 | 840.52 | 180.83 | 0.00 | 180.83 | 0.00 | 0.00 |
December | 0.67 | 1301.60 | 167.63 | 0.00 | 167.63 | 0.00 | 0.00 |
Annual Sum or Average | 256.07 | 671.66 | 357.79 | 10.18 | 347.61 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 129.04 | 167.63 | 0.00 | 167.63 | 0.00 | 0.00 |
Maximum of Months | 708.87 | 1353.59 | 590.57 | 51.17 | 539.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1390.45 | 179.10 | 0.00 | 179.10 | 0.00 | 0.00 |
February | 2.52 | 1316.19 | 272.88 | 0.00 | 272.88 | 0.00 | 0.00 |
March | 78.57 | 919.84 | 330.96 | 0.00 | 330.96 | 0.00 | 0.00 |
April | 186.50 | 633.25 | 422.60 | 2.38 | 420.21 | 0.00 | 0.00 |
May | 362.62 | 365.25 | 489.58 | 20.34 | 469.24 | 0.00 | 0.00 |
June | 633.60 | 211.51 | 590.57 | 51.17 | 539.40 | 0.00 | 0.00 |
July | 699.89 | 133.72 | 550.04 | 38.19 | 511.84 | 0.00 | 0.00 |
August | 566.98 | 188.61 | 475.75 | 9.36 | 466.39 | 0.00 | 0.00 |
September | 317.50 | 343.28 | 360.26 | 0.20 | 360.06 | 0.00 | 0.00 |
October | 104.22 | 626.26 | 269.10 | 0.00 | 269.10 | 0.00 | 0.00 |
November | 20.98 | 869.28 | 180.83 | 0.00 | 180.83 | 0.00 | 0.00 |
December | 0.50 | 1337.79 | 167.63 | 0.00 | 167.63 | 0.00 | 0.00 |
Annual Sum or Average | 249.38 | 691.48 | 357.79 | 10.18 | 347.61 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 133.72 | 167.63 | 0.00 | 167.63 | 0.00 | 0.00 |
Maximum of Months | 699.89 | 1390.45 | 590.57 | 51.17 | 539.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 127.28 | 869.35 | 310.46 | 120.61 | 189.85 | 0.00 | 0.00 |
February | 201.92 | 840.26 | 421.68 | 137.80 | 283.88 | 0.00 | 0.00 |
March | 473.02 | 573.16 | 570.69 | 241.77 | 328.92 | 0.00 | 0.00 |
April | 689.37 | 422.24 | 674.35 | 266.09 | 408.26 | 0.00 | 0.00 |
May | 897.02 | 260.68 | 727.59 | 277.36 | 450.23 | 0.00 | 0.00 |
June | 1131.05 | 157.55 | 801.08 | 298.78 | 502.31 | 0.00 | 0.00 |
July | 1207.54 | 99.28 | 772.93 | 288.59 | 484.34 | 0.00 | 0.00 |
August | 1097.63 | 131.80 | 718.80 | 261.51 | 457.28 | 0.00 | 0.00 |
September | 867.01 | 221.06 | 634.97 | 264.85 | 370.12 | 0.00 | 0.00 |
October | 498.00 | 394.50 | 474.82 | 202.14 | 272.68 | 0.00 | 0.00 |
November | 219.35 | 544.75 | 293.95 | 110.14 | 183.81 | 0.00 | 0.00 |
December | 82.15 | 858.26 | 252.39 | 75.99 | 176.40 | 0.00 | 0.00 |
Annual Sum or Average | 626.63 | 445.74 | 555.06 | 212.50 | 342.56 | 0.00 | 0.00 |
Minimum of Months | 82.15 | 99.28 | 252.39 | 75.99 | 176.40 | 0.00 | 0.00 |
Maximum of Months | 1207.54 | 869.35 | 801.08 | 298.78 | 502.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 276.78 | 958.12 | 472.70 | 240.21 | 232.49 | 0.00 | 0.00 |
February | 323.64 | 932.63 | 559.33 | 222.77 | 336.56 | 0.00 | 0.00 |
March | 569.63 | 642.58 | 685.80 | 321.56 | 364.25 | 0.00 | 0.00 |
April | 564.68 | 476.34 | 618.24 | 189.55 | 428.69 | 0.00 | 0.00 |
May | 614.63 | 286.07 | 585.26 | 130.03 | 455.23 | 0.00 | 0.00 |
June | 732.60 | 171.28 | 604.25 | 101.67 | 502.57 | 0.00 | 0.00 |
July | 814.69 | 111.82 | 596.96 | 109.84 | 487.11 | 0.00 | 0.00 |
August | 826.63 | 156.10 | 620.40 | 148.32 | 472.08 | 0.00 | 0.00 |
September | 797.67 | 262.30 | 658.79 | 259.85 | 398.94 | 0.00 | 0.00 |
October | 603.64 | 440.12 | 607.01 | 294.30 | 312.70 | 0.00 | 0.00 |
November | 348.26 | 604.38 | 431.22 | 208.91 | 222.31 | 0.00 | 0.00 |
December | 218.45 | 938.87 | 401.39 | 178.27 | 223.12 | 0.00 | 0.00 |
Annual Sum or Average | 558.95 | 496.13 | 570.11 | 200.37 | 369.74 | 0.00 | 0.00 |
Minimum of Months | 218.45 | 111.82 | 401.39 | 101.67 | 222.31 | 0.00 | 0.00 |
Maximum of Months | 826.63 | 958.12 | 685.80 | 321.56 | 502.57 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.120541E+10 | 0.186750E+10 | 0.149244E+10 | 0.871616E+09 | 0.620826E+09 | 0.00 | 0.00 |
February | 0.121822E+10 | 0.164211E+10 | 0.152659E+10 | 0.730113E+09 | 0.796480E+09 | 0.00 | 0.00 |
March | 0.206088E+10 | 0.129571E+10 | 0.207681E+10 | 0.116679E+10 | 0.910020E+09 | 0.00 | 0.00 |
April | 0.174650E+10 | 0.944171E+09 | 0.166226E+10 | 0.662735E+09 | 0.999522E+09 | 0.00 | 0.00 |
May | 0.176989E+10 | 0.595631E+09 | 0.151468E+10 | 0.446521E+09 | 0.106816E+10 | 0.00 | 0.00 |
June | 0.183253E+10 | 0.351565E+09 | 0.141093E+10 | 0.295438E+09 | 0.111549E+10 | 0.00 | 0.00 |
July | 0.211315E+10 | 0.232570E+09 | 0.148192E+10 | 0.351066E+09 | 0.113085E+10 | 0.00 | 0.00 |
August | 0.229976E+10 | 0.320185E+09 | 0.165938E+10 | 0.526561E+09 | 0.113282E+10 | 0.00 | 0.00 |
September | 0.239636E+10 | 0.518969E+09 | 0.187970E+10 | 0.912236E+09 | 0.967463E+09 | 0.00 | 0.00 |
October | 0.206327E+10 | 0.900541E+09 | 0.186785E+10 | 0.106791E+10 | 0.799941E+09 | 0.00 | 0.00 |
November | 0.124958E+10 | 0.116740E+10 | 0.129658E+10 | 0.733608E+09 | 0.562970E+09 | 0.00 | 0.00 |
December | 0.955685E+09 | 0.182022E+10 | 0.124798E+10 | 0.646864E+09 | 0.601115E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.209112E+11 | 0.116566E+11 | 0.191171E+11 | 0.841146E+10 | 0.107057E+11 | 0.00 | 0.00 |
Minimum of Months | 0.955685E+09 | 0.232570E+09 | 0.124798E+10 | 0.295438E+09 | 0.562970E+09 | 0.00 | 0.00 |
Maximum of Months | 0.239636E+10 | 0.186750E+10 | 0.207681E+10 | 0.116679E+10 | 0.113282E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.334722E+10 | 0.535661E+10 | 0.420262E+10 | 0.245441E+10 | 0.174821E+10 | 0.00 | 0.00 |
February | 0.337974E+10 | 0.470607E+10 | 0.429879E+10 | 0.205595E+10 | 0.224284E+10 | 0.00 | 0.00 |
March | 0.572195E+10 | 0.381366E+10 | 0.584817E+10 | 0.328562E+10 | 0.256256E+10 | 0.00 | 0.00 |
April | 0.483679E+10 | 0.283624E+10 | 0.468081E+10 | 0.186622E+10 | 0.281459E+10 | 0.00 | 0.00 |
May | 0.488047E+10 | 0.186169E+10 | 0.426524E+10 | 0.125737E+10 | 0.300787E+10 | 0.00 | 0.00 |
June | 0.507342E+10 | 0.111311E+10 | 0.397308E+10 | 0.831935E+09 | 0.314115E+10 | 0.00 | 0.00 |
July | 0.588342E+10 | 0.741060E+09 | 0.417299E+10 | 0.988579E+09 | 0.318441E+10 | 0.00 | 0.00 |
August | 0.641045E+10 | 0.101229E+10 | 0.467271E+10 | 0.148276E+10 | 0.318995E+10 | 0.00 | 0.00 |
September | 0.666520E+10 | 0.163580E+10 | 0.529311E+10 | 0.256880E+10 | 0.272431E+10 | 0.00 | 0.00 |
October | 0.572840E+10 | 0.273610E+10 | 0.525974E+10 | 0.300716E+10 | 0.225258E+10 | 0.00 | 0.00 |
November | 0.345787E+10 | 0.346924E+10 | 0.365108E+10 | 0.206579E+10 | 0.158529E+10 | 0.00 | 0.00 |
December | 0.265036E+10 | 0.523441E+10 | 0.351423E+10 | 0.182153E+10 | 0.169270E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.580353E+11 | 0.345163E+11 | 0.538326E+11 | 0.236861E+11 | 0.301464E+11 | 0.00 | 0.00 |
Minimum of Months | 0.265036E+10 | 0.741060E+09 | 0.351423E+10 | 0.831935E+09 | 0.158529E+10 | 0.00 | 0.00 |
Maximum of Months | 0.666520E+10 | 0.535661E+10 | 0.584817E+10 | 0.328562E+10 | 0.318995E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.439090E+10 | 0.733408E+10 | 0.545944E+10 | 0.318842E+10 | 0.227102E+10 | 0.00 | 0.00 |
February | 0.443644E+10 | 0.643283E+10 | 0.558437E+10 | 0.267080E+10 | 0.291357E+10 | 0.00 | 0.00 |
March | 0.755246E+10 | 0.519556E+10 | 0.759711E+10 | 0.426820E+10 | 0.332891E+10 | 0.00 | 0.00 |
April | 0.637198E+10 | 0.389384E+10 | 0.608063E+10 | 0.242432E+10 | 0.365631E+10 | 0.00 | 0.00 |
May | 0.642597E+10 | 0.257441E+10 | 0.554079E+10 | 0.163340E+10 | 0.390739E+10 | 0.00 | 0.00 |
June | 0.668877E+10 | 0.152773E+10 | 0.516126E+10 | 0.108073E+10 | 0.408053E+10 | 0.00 | 0.00 |
July | 0.778285E+10 | 0.100277E+10 | 0.542095E+10 | 0.128422E+10 | 0.413673E+10 | 0.00 | 0.00 |
August | 0.847839E+10 | 0.136273E+10 | 0.607012E+10 | 0.192619E+10 | 0.414393E+10 | 0.00 | 0.00 |
September | 0.879994E+10 | 0.222725E+10 | 0.687605E+10 | 0.333701E+10 | 0.353904E+10 | 0.00 | 0.00 |
October | 0.752937E+10 | 0.376907E+10 | 0.683270E+10 | 0.390647E+10 | 0.292623E+10 | 0.00 | 0.00 |
November | 0.453666E+10 | 0.480419E+10 | 0.474296E+10 | 0.268358E+10 | 0.205938E+10 | 0.00 | 0.00 |
December | 0.347467E+10 | 0.719524E+10 | 0.456518E+10 | 0.236627E+10 | 0.219891E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.764684E+11 | 0.473197E+11 | 0.699316E+11 | 0.307696E+11 | 0.391619E+11 | 0.00 | 0.00 |
Minimum of Months | 0.347467E+10 | 0.100277E+10 | 0.456518E+10 | 0.108073E+10 | 0.205938E+10 | 0.00 | 0.00 |
Maximum of Months | 0.879994E+10 | 0.733408E+10 | 0.759711E+10 | 0.426820E+10 | 0.414393E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.244228E+09 | 0.112051E+10 | 0.496582E+09 | 0.219829E+09 | 0.276753E+09 | 0.00 | 0.00 |
February | 0.333208E+09 | 0.982332E+09 | 0.597378E+09 | 0.220903E+09 | 0.376475E+09 | 0.00 | 0.00 |
March | 0.786101E+09 | 0.745403E+09 | 0.922898E+09 | 0.450693E+09 | 0.472205E+09 | 0.00 | 0.00 |
April | 0.909666E+09 | 0.531362E+09 | 0.933028E+09 | 0.378627E+09 | 0.554401E+09 | 0.00 | 0.00 |
May | 0.117505E+10 | 0.332000E+09 | 0.103703E+10 | 0.421961E+09 | 0.615067E+09 | 0.00 | 0.00 |
June | 0.145450E+10 | 0.181136E+09 | 0.113907E+10 | 0.462572E+09 | 0.676493E+09 | 0.00 | 0.00 |
July | 0.151733E+10 | 0.106162E+09 | 0.108744E+10 | 0.417167E+09 | 0.670276E+09 | 0.00 | 0.00 |
August | 0.142442E+10 | 0.151944E+09 | 0.104626E+10 | 0.408530E+09 | 0.637726E+09 | 0.00 | 0.00 |
September | 0.112894E+10 | 0.274880E+09 | 0.918033E+09 | 0.416060E+09 | 0.501973E+09 | 0.00 | 0.00 |
October | 0.729611E+09 | 0.513413E+09 | 0.736956E+09 | 0.341373E+09 | 0.395583E+09 | 0.00 | 0.00 |
November | 0.359314E+09 | 0.682019E+09 | 0.465984E+09 | 0.205175E+09 | 0.260809E+09 | 0.00 | 0.00 |
December | 0.206916E+09 | 0.109622E+10 | 0.434182E+09 | 0.168279E+09 | 0.265903E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102693E+11 | 0.671738E+10 | 0.981483E+10 | 0.411117E+10 | 0.570366E+10 | 0.00 | 0.00 |
Minimum of Months | 0.206916E+09 | 0.106162E+09 | 0.434182E+09 | 0.168279E+09 | 0.260809E+09 | 0.00 | 0.00 |
Maximum of Months | 0.151733E+10 | 0.112051E+10 | 0.113907E+10 | 0.462572E+09 | 0.676493E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 43788280.28 | 0.121328E+10 | 0.270031E+09 | 47495878.30 | 0.222535E+09 | 0.00 | 0.00 |
February | 0.117370E+09 | 0.103413E+10 | 0.389854E+09 | 76547281.39 | 0.313306E+09 | 0.00 | 0.00 |
March | 0.441648E+09 | 0.773282E+09 | 0.638916E+09 | 0.219999E+09 | 0.418917E+09 | 0.00 | 0.00 |
April | 0.664582E+09 | 0.527897E+09 | 0.760857E+09 | 0.248475E+09 | 0.512382E+09 | 0.00 | 0.00 |
May | 0.982900E+09 | 0.328716E+09 | 0.924883E+09 | 0.341459E+09 | 0.583424E+09 | 0.00 | 0.00 |
June | 0.131897E+10 | 0.189599E+09 | 0.107878E+10 | 0.423106E+09 | 0.655679E+09 | 0.00 | 0.00 |
July | 0.135703E+10 | 0.114564E+09 | 0.100491E+10 | 0.362370E+09 | 0.642537E+09 | 0.00 | 0.00 |
August | 0.118139E+10 | 0.163049E+09 | 0.900208E+09 | 0.308000E+09 | 0.592208E+09 | 0.00 | 0.00 |
September | 0.779073E+09 | 0.286605E+09 | 0.679788E+09 | 0.235770E+09 | 0.444017E+09 | 0.00 | 0.00 |
October | 0.389776E+09 | 0.523944E+09 | 0.470617E+09 | 0.130229E+09 | 0.340388E+09 | 0.00 | 0.00 |
November | 0.140026E+09 | 0.700127E+09 | 0.276588E+09 | 60128040.21 | 0.216460E+09 | 0.00 | 0.00 |
December | 41967052.12 | 0.116391E+10 | 0.251577E+09 | 40382403.54 | 0.211194E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.745852E+10 | 0.701911E+10 | 0.764701E+10 | 0.249396E+10 | 0.515305E+10 | 0.00 | 0.00 |
Minimum of Months | 41967052.12 | 0.114564E+09 | 0.251577E+09 | 40382403.54 | 0.211194E+09 | 0.00 | 0.00 |
Maximum of Months | 0.135703E+10 | 0.121328E+10 | 0.107878E+10 | 0.423106E+09 | 0.655679E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.197661E+09 | 0.270362E+09 | 0.236019E+09 | 0.137839E+09 | 98179314.65 | 0.00 | 0.00 |
February | 0.200333E+09 | 0.237335E+09 | 0.241420E+09 | 0.115462E+09 | 0.125958E+09 | 0.00 | 0.00 |
March | 0.301020E+09 | 0.258352E+09 | 0.328433E+09 | 0.184520E+09 | 0.143914E+09 | 0.00 | 0.00 |
April | 0.246054E+09 | 0.209730E+09 | 0.262875E+09 | 0.104806E+09 | 0.158068E+09 | 0.00 | 0.00 |
May | 0.244413E+09 | 0.148399E+09 | 0.239537E+09 | 70613797.98 | 0.168923E+09 | 0.00 | 0.00 |
June | 0.255134E+09 | 91738107.33 | 0.223129E+09 | 46721309.88 | 0.176408E+09 | 0.00 | 0.00 |
July | 0.302214E+09 | 65608682.13 | 0.234356E+09 | 55518414.20 | 0.178838E+09 | 0.00 | 0.00 |
August | 0.335027E+09 | 84974419.12 | 0.262420E+09 | 83271556.86 | 0.179149E+09 | 0.00 | 0.00 |
September | 0.352175E+09 | 0.129032E+09 | 0.297261E+09 | 0.144263E+09 | 0.152998E+09 | 0.00 | 0.00 |
October | 0.296929E+09 | 0.206795E+09 | 0.295387E+09 | 0.168881E+09 | 0.126505E+09 | 0.00 | 0.00 |
November | 0.180304E+09 | 0.244860E+09 | 0.205044E+09 | 0.116014E+09 | 89029868.95 | 0.00 | 0.00 |
December | 0.156439E+09 | 0.268461E+09 | 0.197359E+09 | 0.102297E+09 | 95062038.89 | 0.00 | 0.00 |
Annual Sum or Average | 0.306770E+10 | 0.221565E+10 | 0.302324E+10 | 0.133021E+10 | 0.169303E+10 | 0.00 | 0.00 |
Minimum of Months | 0.156439E+09 | 65608682.13 | 0.197359E+09 | 46721309.88 | 89029868.95 | 0.00 | 0.00 |
Maximum of Months | 0.352175E+09 | 0.270362E+09 | 0.328433E+09 | 0.184520E+09 | 0.179149E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 13109.76 | 0.371535E+09 | 54831599.44 | 0.00 | 54831599.44 | 0.00 | 0.00 |
February | 2511383.78 | 0.316929E+09 | 75458009.98 | 0.00 | 75458009.98 | 0.00 | 0.00 |
March | 32816300.04 | 0.238525E+09 | 0.101326E+09 | 1459.70 | 0.101325E+09 | 0.00 | 0.00 |
April | 70724945.71 | 0.154236E+09 | 0.125206E+09 | 705821.57 | 0.124501E+09 | 0.00 | 0.00 |
May | 0.132097E+09 | 88325059.15 | 0.149888E+09 | 6227089.73 | 0.143661E+09 | 0.00 | 0.00 |
June | 0.208690E+09 | 47509688.56 | 0.174972E+09 | 15159636.67 | 0.159813E+09 | 0.00 | 0.00 |
July | 0.235917E+09 | 27790560.62 | 0.168396E+09 | 11693265.88 | 0.156703E+09 | 0.00 | 0.00 |
August | 0.192736E+09 | 41004934.97 | 0.145653E+09 | 2864391.37 | 0.142789E+09 | 0.00 | 0.00 |
September | 0.109360E+09 | 78189872.55 | 0.106739E+09 | 60414.17 | 0.106678E+09 | 0.00 | 0.00 |
October | 43912810.04 | 0.154959E+09 | 82385417.85 | 0.00 | 82385417.85 | 0.00 | 0.00 |
November | 10838290.13 | 0.211756E+09 | 53575070.74 | 0.00 | 53575070.74 | 0.00 | 0.00 |
December | 445513.05 | 0.355636E+09 | 51320709.15 | 0.00 | 51320709.15 | 0.00 | 0.00 |
Annual Sum or Average | 0.104006E+10 | 0.208640E+10 | 0.128975E+10 | 36712079.10 | 0.125304E+10 | 0.00 | 0.00 |
Minimum of Months | 13109.76 | 27790560.62 | 51320709.15 | 0.00 | 51320709.15 | 0.00 | 0.00 |
Maximum of Months | 0.235917E+09 | 0.371535E+09 | 0.174972E+09 | 15159636.67 | 0.159813E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.289534E+09 | 0.111306E+10 | 0.529059E+09 | 0.247689E+09 | 0.281370E+09 | 0.00 | 0.00 |
February | 0.355765E+09 | 0.971739E+09 | 0.613844E+09 | 0.238869E+09 | 0.374976E+09 | 0.00 | 0.00 |
March | 0.762744E+09 | 0.738166E+09 | 0.906294E+09 | 0.439141E+09 | 0.467153E+09 | 0.00 | 0.00 |
April | 0.929115E+09 | 0.516646E+09 | 0.960085E+09 | 0.409945E+09 | 0.550140E+09 | 0.00 | 0.00 |
May | 0.115667E+10 | 0.317421E+09 | 0.103051E+10 | 0.411715E+09 | 0.618794E+09 | 0.00 | 0.00 |
June | 0.135266E+10 | 0.168339E+09 | 0.106840E+10 | 0.406971E+09 | 0.661427E+09 | 0.00 | 0.00 |
July | 0.149610E+10 | 96724709.57 | 0.107643E+10 | 0.413896E+09 | 0.662531E+09 | 0.00 | 0.00 |
August | 0.140234E+10 | 0.143003E+09 | 0.103569E+10 | 0.400506E+09 | 0.635183E+09 | 0.00 | 0.00 |
September | 0.115457E+10 | 0.264889E+09 | 0.942085E+09 | 0.433411E+09 | 0.508674E+09 | 0.00 | 0.00 |
October | 0.765273E+09 | 0.507398E+09 | 0.769075E+09 | 0.376289E+09 | 0.392786E+09 | 0.00 | 0.00 |
November | 0.371608E+09 | 0.677599E+09 | 0.475675E+09 | 0.215274E+09 | 0.260401E+09 | 0.00 | 0.00 |
December | 0.200109E+09 | 0.108823E+10 | 0.429316E+09 | 0.165717E+09 | 0.263599E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102365E+11 | 0.660322E+10 | 0.983646E+10 | 0.415942E+10 | 0.567703E+10 | 0.00 | 0.00 |
Minimum of Months | 0.200109E+09 | 96724709.57 | 0.429316E+09 | 0.165717E+09 | 0.260401E+09 | 0.00 | 0.00 |
Maximum of Months | 0.149610E+10 | 0.111306E+10 | 0.107643E+10 | 0.439141E+09 | 0.662531E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 62961328.36 | 0.117841E+10 | 0.302508E+09 | 75355657.08 | 0.227152E+09 | 0.00 | 0.00 |
February | 0.124272E+09 | 0.100693E+10 | 0.406320E+09 | 94512709.61 | 0.311807E+09 | 0.00 | 0.00 |
March | 0.409867E+09 | 0.757226E+09 | 0.622312E+09 | 0.208448E+09 | 0.413864E+09 | 0.00 | 0.00 |
April | 0.680540E+09 | 0.510969E+09 | 0.787914E+09 | 0.279793E+09 | 0.508121E+09 | 0.00 | 0.00 |
May | 0.971643E+09 | 0.314836E+09 | 0.918365E+09 | 0.331213E+09 | 0.587152E+09 | 0.00 | 0.00 |
June | 0.123116E+10 | 0.177417E+09 | 0.100812E+10 | 0.367505E+09 | 0.640612E+09 | 0.00 | 0.00 |
July | 0.133807E+10 | 0.108572E+09 | 0.993891E+09 | 0.359099E+09 | 0.634792E+09 | 0.00 | 0.00 |
August | 0.116087E+10 | 0.154742E+09 | 0.889641E+09 | 0.299976E+09 | 0.589665E+09 | 0.00 | 0.00 |
September | 0.806684E+09 | 0.272092E+09 | 0.703840E+09 | 0.253121E+09 | 0.450719E+09 | 0.00 | 0.00 |
October | 0.416576E+09 | 0.508733E+09 | 0.502736E+09 | 0.165145E+09 | 0.337591E+09 | 0.00 | 0.00 |
November | 0.145307E+09 | 0.688531E+09 | 0.286279E+09 | 70227577.39 | 0.216051E+09 | 0.00 | 0.00 |
December | 32043730.46 | 0.115304E+10 | 0.246711E+09 | 37820722.34 | 0.208890E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.737999E+10 | 0.683149E+10 | 0.766863E+10 | 0.254222E+10 | 0.512642E+10 | 0.00 | 0.00 |
Minimum of Months | 32043730.46 | 0.108572E+09 | 0.246711E+09 | 37820722.34 | 0.208890E+09 | 0.00 | 0.00 |
Maximum of Months | 0.133807E+10 | 0.117841E+10 | 0.100812E+10 | 0.367505E+09 | 0.640612E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.327345E+09 | 0.144117E+10 | 0.630170E+09 | 0.298660E+09 | 0.331511E+09 | 0.00 | 0.00 |
February | 0.360213E+09 | 0.126575E+10 | 0.686557E+09 | 0.250173E+09 | 0.436383E+09 | 0.00 | 0.00 |
March | 0.739517E+09 | 0.960493E+09 | 0.931130E+09 | 0.399806E+09 | 0.531325E+09 | 0.00 | 0.00 |
April | 0.753564E+09 | 0.682786E+09 | 0.840815E+09 | 0.228616E+09 | 0.612200E+09 | 0.00 | 0.00 |
May | 0.888488E+09 | 0.420122E+09 | 0.843718E+09 | 0.166490E+09 | 0.677228E+09 | 0.00 | 0.00 |
June | 0.106271E+10 | 0.242270E+09 | 0.862508E+09 | 0.134073E+09 | 0.728435E+09 | 0.00 | 0.00 |
July | 0.121548E+10 | 0.159773E+09 | 0.872587E+09 | 0.145624E+09 | 0.726962E+09 | 0.00 | 0.00 |
August | 0.119271E+10 | 0.227361E+09 | 0.884124E+09 | 0.186632E+09 | 0.697493E+09 | 0.00 | 0.00 |
September | 0.105786E+10 | 0.381476E+09 | 0.875314E+09 | 0.312709E+09 | 0.562605E+09 | 0.00 | 0.00 |
October | 0.798027E+09 | 0.654751E+09 | 0.818495E+09 | 0.365919E+09 | 0.452576E+09 | 0.00 | 0.00 |
November | 0.431207E+09 | 0.869006E+09 | 0.560335E+09 | 0.251371E+09 | 0.308965E+09 | 0.00 | 0.00 |
December | 0.260284E+09 | 0.140872E+10 | 0.538799E+09 | 0.221648E+09 | 0.317151E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.908740E+10 | 0.871367E+10 | 0.934455E+10 | 0.296172E+10 | 0.638283E+10 | 0.00 | 0.00 |
Minimum of Months | 0.260284E+09 | 0.159773E+09 | 0.538799E+09 | 0.134073E+09 | 0.308965E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121548E+10 | 0.144117E+10 | 0.931130E+09 | 0.399806E+09 | 0.728435E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.244541E+09 | 0.111932E+10 | 0.496582E+09 | 0.219829E+09 | 0.276753E+09 | 0.00 | 0.00 |
February | 0.331703E+09 | 0.982512E+09 | 0.597378E+09 | 0.220903E+09 | 0.376475E+09 | 0.00 | 0.00 |
March | 0.782798E+09 | 0.742804E+09 | 0.922898E+09 | 0.450693E+09 | 0.472205E+09 | 0.00 | 0.00 |
April | 0.902657E+09 | 0.529372E+09 | 0.933028E+09 | 0.378627E+09 | 0.554401E+09 | 0.00 | 0.00 |
May | 0.116476E+10 | 0.329559E+09 | 0.103703E+10 | 0.421961E+09 | 0.615067E+09 | 0.00 | 0.00 |
June | 0.144272E+10 | 0.178694E+09 | 0.113907E+10 | 0.462572E+09 | 0.676493E+09 | 0.00 | 0.00 |
July | 0.150702E+10 | 0.103461E+09 | 0.108744E+10 | 0.417167E+09 | 0.670276E+09 | 0.00 | 0.00 |
August | 0.141562E+10 | 0.148673E+09 | 0.104626E+10 | 0.408530E+09 | 0.637726E+09 | 0.00 | 0.00 |
September | 0.112229E+10 | 0.270539E+09 | 0.918033E+09 | 0.416060E+09 | 0.501973E+09 | 0.00 | 0.00 |
October | 0.726936E+09 | 0.509013E+09 | 0.736956E+09 | 0.341373E+09 | 0.395583E+09 | 0.00 | 0.00 |
November | 0.359886E+09 | 0.676136E+09 | 0.465984E+09 | 0.205175E+09 | 0.260809E+09 | 0.00 | 0.00 |
December | 0.206525E+09 | 0.109501E+10 | 0.434182E+09 | 0.168279E+09 | 0.265903E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102075E+11 | 0.668509E+10 | 0.981483E+10 | 0.411117E+10 | 0.570366E+10 | 0.00 | 0.00 |
Minimum of Months | 0.206525E+09 | 0.103461E+09 | 0.434182E+09 | 0.168279E+09 | 0.260809E+09 | 0.00 | 0.00 |
Maximum of Months | 0.150702E+10 | 0.111932E+10 | 0.113907E+10 | 0.462572E+09 | 0.676493E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 43925392.31 | 0.121284E+10 | 0.270031E+09 | 47495878.30 | 0.222535E+09 | 0.00 | 0.00 |
February | 0.117007E+09 | 0.103454E+10 | 0.389854E+09 | 76547281.39 | 0.313306E+09 | 0.00 | 0.00 |
March | 0.441026E+09 | 0.770556E+09 | 0.638916E+09 | 0.219999E+09 | 0.418917E+09 | 0.00 | 0.00 |
April | 0.659990E+09 | 0.525320E+09 | 0.760857E+09 | 0.248475E+09 | 0.512382E+09 | 0.00 | 0.00 |
May | 0.972336E+09 | 0.328444E+09 | 0.924883E+09 | 0.341459E+09 | 0.583424E+09 | 0.00 | 0.00 |
June | 0.130485E+10 | 0.192402E+09 | 0.107878E+10 | 0.423106E+09 | 0.655679E+09 | 0.00 | 0.00 |
July | 0.134640E+10 | 0.115144E+09 | 0.100491E+10 | 0.362370E+09 | 0.642537E+09 | 0.00 | 0.00 |
August | 0.117315E+10 | 0.162992E+09 | 0.900208E+09 | 0.308000E+09 | 0.592208E+09 | 0.00 | 0.00 |
September | 0.773217E+09 | 0.284747E+09 | 0.679788E+09 | 0.235770E+09 | 0.444017E+09 | 0.00 | 0.00 |
October | 0.390145E+09 | 0.518295E+09 | 0.470617E+09 | 0.130229E+09 | 0.340388E+09 | 0.00 | 0.00 |
November | 0.142258E+09 | 0.692670E+09 | 0.276588E+09 | 60128040.21 | 0.216460E+09 | 0.00 | 0.00 |
December | 42210971.51 | 0.116248E+10 | 0.251577E+09 | 40382403.54 | 0.211194E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.740651E+10 | 0.700044E+10 | 0.764701E+10 | 0.249396E+10 | 0.515305E+10 | 0.00 | 0.00 |
Minimum of Months | 42210971.51 | 0.115144E+09 | 0.251577E+09 | 40382403.54 | 0.211194E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134640E+10 | 0.121284E+10 | 0.107878E+10 | 0.423106E+09 | 0.655679E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.336071E+09 | 0.574408E+09 | 0.432766E+09 | 0.252744E+09 | 0.180023E+09 | 0.00 | 0.00 |
February | 0.336270E+09 | 0.509140E+09 | 0.442669E+09 | 0.211712E+09 | 0.230958E+09 | 0.00 | 0.00 |
March | 0.578140E+09 | 0.395386E+09 | 0.602218E+09 | 0.338337E+09 | 0.263882E+09 | 0.00 | 0.00 |
April | 0.492096E+09 | 0.286010E+09 | 0.482009E+09 | 0.192174E+09 | 0.289835E+09 | 0.00 | 0.00 |
May | 0.503091E+09 | 0.172961E+09 | 0.439217E+09 | 0.129478E+09 | 0.309739E+09 | 0.00 | 0.00 |
June | 0.533509E+09 | 89377058.46 | 0.409132E+09 | 85668639.80 | 0.323464E+09 | 0.00 | 0.00 |
July | 0.628374E+09 | 49710948.80 | 0.429718E+09 | 0.101799E+09 | 0.327918E+09 | 0.00 | 0.00 |
August | 0.677799E+09 | 73871085.00 | 0.481176E+09 | 0.152688E+09 | 0.328488E+09 | 0.00 | 0.00 |
September | 0.694491E+09 | 0.140711E+09 | 0.545061E+09 | 0.264522E+09 | 0.280539E+09 | 0.00 | 0.00 |
October | 0.586492E+09 | 0.267900E+09 | 0.541624E+09 | 0.309663E+09 | 0.231961E+09 | 0.00 | 0.00 |
November | 0.352322E+09 | 0.355327E+09 | 0.375971E+09 | 0.212725E+09 | 0.163246E+09 | 0.00 | 0.00 |
December | 0.265103E+09 | 0.560106E+09 | 0.361879E+09 | 0.187572E+09 | 0.174307E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.598376E+10 | 0.347491E+10 | 0.554344E+10 | 0.243908E+10 | 0.310436E+10 | 0.00 | 0.00 |
Minimum of Months | 0.265103E+09 | 49710948.80 | 0.361879E+09 | 85668639.80 | 0.163246E+09 | 0.00 | 0.00 |
Maximum of Months | 0.694491E+09 | 0.574408E+09 | 0.602218E+09 | 0.338337E+09 | 0.328488E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.362547E+10 | 0.479695E+09 | 0.00 | 0.479695E+09 | 0.00 | 0.00 |
February | 8677293.46 | 0.309638E+10 | 0.660145E+09 | 0.00 | 0.660145E+09 | 0.00 | 0.00 |
March | 0.226665E+09 | 0.239406E+10 | 0.886455E+09 | 12770.23 | 0.886442E+09 | 0.00 | 0.00 |
April | 0.512133E+09 | 0.159549E+10 | 0.109537E+10 | 6174886.32 | 0.108919E+10 | 0.00 | 0.00 |
May | 0.100519E+10 | 0.951351E+09 | 0.131130E+10 | 54477750.25 | 0.125682E+10 | 0.00 | 0.00 |
June | 0.167046E+10 | 0.532608E+09 | 0.153075E+10 | 0.132624E+09 | 0.139812E+10 | 0.00 | 0.00 |
July | 0.189863E+10 | 0.345609E+09 | 0.147322E+10 | 0.102299E+09 | 0.137092E+10 | 0.00 | 0.00 |
August | 0.154182E+10 | 0.488620E+09 | 0.127425E+10 | 25059153.55 | 0.124919E+10 | 0.00 | 0.00 |
September | 0.846761E+09 | 0.862740E+09 | 0.933804E+09 | 528533.88 | 0.933276E+09 | 0.00 | 0.00 |
October | 0.301529E+09 | 0.162441E+10 | 0.720750E+09 | 0.00 | 0.720750E+09 | 0.00 | 0.00 |
November | 61612828.13 | 0.217863E+10 | 0.468702E+09 | 0.00 | 0.468702E+09 | 0.00 | 0.00 |
December | 1791039.99 | 0.348621E+10 | 0.448980E+09 | 0.00 | 0.448980E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.807528E+10 | 0.211816E+11 | 0.112834E+11 | 0.321176E+09 | 0.109622E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.345609E+09 | 0.448980E+09 | 0.00 | 0.448980E+09 | 0.00 | 0.00 |
Maximum of Months | 0.189863E+10 | 0.362547E+10 | 0.153075E+10 | 0.132624E+09 | 0.139812E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.372419E+10 | 0.479695E+09 | 0.00 | 0.479695E+09 | 0.00 | 0.00 |
February | 6097551.12 | 0.318412E+10 | 0.660145E+09 | 0.00 | 0.660145E+09 | 0.00 | 0.00 |
March | 0.210437E+09 | 0.246369E+10 | 0.886455E+09 | 12770.23 | 0.886442E+09 | 0.00 | 0.00 |
April | 0.483416E+09 | 0.164138E+10 | 0.109537E+10 | 6174886.32 | 0.108919E+10 | 0.00 | 0.00 |
May | 0.971229E+09 | 0.978289E+09 | 0.131130E+10 | 54477750.25 | 0.125682E+10 | 0.00 | 0.00 |
June | 0.164229E+10 | 0.548234E+09 | 0.153075E+10 | 0.132624E+09 | 0.139812E+10 | 0.00 | 0.00 |
July | 0.187460E+10 | 0.358154E+09 | 0.147322E+10 | 0.102299E+09 | 0.137092E+10 | 0.00 | 0.00 |
August | 0.151859E+10 | 0.505168E+09 | 0.127425E+10 | 25059153.55 | 0.124919E+10 | 0.00 | 0.00 |
September | 0.822954E+09 | 0.889773E+09 | 0.933804E+09 | 528533.88 | 0.933276E+09 | 0.00 | 0.00 |
October | 0.279148E+09 | 0.167737E+10 | 0.720750E+09 | 0.00 | 0.720750E+09 | 0.00 | 0.00 |
November | 54372302.76 | 0.225317E+10 | 0.468702E+09 | 0.00 | 0.468702E+09 | 0.00 | 0.00 |
December | 1343089.03 | 0.358312E+10 | 0.448980E+09 | 0.00 | 0.448980E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.786447E+10 | 0.218067E+11 | 0.112834E+11 | 0.321176E+09 | 0.109622E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.358154E+09 | 0.448980E+09 | 0.00 | 0.448980E+09 | 0.00 | 0.00 |
Maximum of Months | 0.187460E+10 | 0.372419E+10 | 0.153075E+10 | 0.132624E+09 | 0.139812E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.340913E+09 | 0.232848E+10 | 0.831534E+09 | 0.323034E+09 | 0.508500E+09 | 0.00 | 0.00 |
February | 0.488489E+09 | 0.203275E+10 | 0.102012E+10 | 0.333368E+09 | 0.686752E+09 | 0.00 | 0.00 |
March | 0.126695E+10 | 0.153516E+10 | 0.152854E+10 | 0.647559E+09 | 0.880977E+09 | 0.00 | 0.00 |
April | 0.178683E+10 | 0.109444E+10 | 0.174791E+10 | 0.689699E+09 | 0.105821E+10 | 0.00 | 0.00 |
May | 0.240258E+10 | 0.698218E+09 | 0.194877E+10 | 0.742882E+09 | 0.120589E+10 | 0.00 | 0.00 |
June | 0.293169E+10 | 0.408363E+09 | 0.207640E+10 | 0.774426E+09 | 0.130198E+10 | 0.00 | 0.00 |
July | 0.323427E+10 | 0.265912E+09 | 0.207021E+10 | 0.772947E+09 | 0.129726E+10 | 0.00 | 0.00 |
August | 0.293989E+10 | 0.353017E+09 | 0.192523E+10 | 0.700440E+09 | 0.122479E+10 | 0.00 | 0.00 |
September | 0.224730E+10 | 0.572983E+09 | 0.164584E+10 | 0.686496E+09 | 0.959347E+09 | 0.00 | 0.00 |
October | 0.133383E+10 | 0.105663E+10 | 0.127175E+10 | 0.541411E+09 | 0.730344E+09 | 0.00 | 0.00 |
November | 0.568557E+09 | 0.141199E+10 | 0.761923E+09 | 0.285492E+09 | 0.476431E+09 | 0.00 | 0.00 |
December | 0.220020E+09 | 0.229877E+10 | 0.676000E+09 | 0.203532E+09 | 0.472468E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.197613E+11 | 0.140567E+11 | 0.175042E+11 | 0.670129E+10 | 0.108029E+11 | 0.00 | 0.00 |
Minimum of Months | 0.220020E+09 | 0.265912E+09 | 0.676000E+09 | 0.203532E+09 | 0.472468E+09 | 0.00 | 0.00 |
Maximum of Months | 0.323427E+10 | 0.232848E+10 | 0.207640E+10 | 0.774426E+09 | 0.130198E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.741324E+09 | 0.256624E+10 | 0.126607E+10 | 0.643372E+09 | 0.622697E+09 | 0.00 | 0.00 |
February | 0.782946E+09 | 0.225622E+10 | 0.135314E+10 | 0.538923E+09 | 0.814214E+09 | 0.00 | 0.00 |
March | 0.152569E+10 | 0.172109E+10 | 0.183686E+10 | 0.861259E+09 | 0.975599E+09 | 0.00 | 0.00 |
April | 0.146365E+10 | 0.123467E+10 | 0.160248E+10 | 0.491306E+09 | 0.111117E+10 | 0.00 | 0.00 |
May | 0.164621E+10 | 0.766202E+09 | 0.156757E+10 | 0.348269E+09 | 0.121930E+10 | 0.00 | 0.00 |
June | 0.189890E+10 | 0.443949E+09 | 0.156621E+10 | 0.263538E+09 | 0.130267E+10 | 0.00 | 0.00 |
July | 0.218206E+10 | 0.299510E+09 | 0.159889E+10 | 0.294203E+09 | 0.130469E+10 | 0.00 | 0.00 |
August | 0.221404E+10 | 0.418095E+09 | 0.166167E+10 | 0.397265E+09 | 0.126441E+10 | 0.00 | 0.00 |
September | 0.206757E+10 | 0.679872E+09 | 0.170759E+10 | 0.673537E+09 | 0.103405E+10 | 0.00 | 0.00 |
October | 0.161680E+10 | 0.117881E+10 | 0.162581E+10 | 0.788262E+09 | 0.837544E+09 | 0.00 | 0.00 |
November | 0.902686E+09 | 0.156656E+10 | 0.111773E+10 | 0.541503E+09 | 0.576223E+09 | 0.00 | 0.00 |
December | 0.585100E+09 | 0.251467E+10 | 0.107509E+10 | 0.477475E+09 | 0.597618E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.176270E+11 | 0.156459E+11 | 0.179791E+11 | 0.631891E+10 | 0.116602E+11 | 0.00 | 0.00 |
Minimum of Months | 0.585100E+09 | 0.299510E+09 | 0.107509E+10 | 0.263538E+09 | 0.576223E+09 | 0.00 | 0.00 |
Maximum of Months | 0.221404E+10 | 0.256624E+10 | 0.183686E+10 | 0.861259E+09 | 0.130469E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770544E+10 | -0.754277E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162661294.6 | 81.21 | 0.00 | 0.00 |
February | 0.696291E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146951374.9 | 81.21 | 0.00 | 0.00 |
March | 0.770386E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162396354.5 | 81.21 | 0.00 | 0.00 |
April | 0.746558E+10 | -0.730861E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156970754.0 | 81.21 | 0.00 | 0.00 |
May | 0.770478E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161977378.7 | 81.21 | 0.00 | 0.00 |
June | 0.745710E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156565482.1 | 81.21 | 0.00 | 0.00 |
July | 0.771253E+10 | -0.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161681165.2 | 81.21 | 0.00 | 0.00 |
August | 0.770452E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161719892.6 | 81.21 | 0.00 | 0.00 |
September | 0.746659E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156652441.7 | 81.21 | 0.00 | 0.00 |
October | 0.770358E+10 | -0.754145E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162133681.3 | 81.21 | 0.00 | 0.00 |
November | 0.744952E+10 | -0.729244E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157077638.4 | 81.21 | 0.00 | 0.00 |
December | 0.771348E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162623123.9 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907499E+11 | -0.888405E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190941E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696291E+10 | -0.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162661294.6 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771348E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146951374.9 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.127584E+12 | -0.125825E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175911E+10 | 81.37 | 0.00 | 0.00 |
February | 0.116183E+12 | -0.114588E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.159529E+10 | 81.33 | 0.00 | 0.00 |
March | 0.127682E+12 | -0.125896E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.178592E+10 | 81.38 | 0.00 | 0.00 |
April | 0.119679E+12 | -0.117948E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.173116E+10 | 81.28 | 0.00 | 0.00 |
May | 0.118752E+12 | -0.116961E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.179094E+10 | 81.27 | 0.00 | 0.00 |
June | 0.110158E+12 | -0.108441E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.171746E+10 | 81.25 | 0.00 | 0.00 |
July | 0.110197E+12 | -0.108435E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176212E+10 | 81.25 | 0.00 | 0.00 |
August | 0.108797E+12 | -0.107053E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.174440E+10 | 81.25 | 0.00 | 0.00 |
September | 0.106500E+12 | -0.104822E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167770E+10 | 81.25 | 0.00 | 0.00 |
October | 0.113595E+12 | -0.111865E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.172982E+10 | 81.25 | 0.00 | 0.00 |
November | 0.114647E+12 | -0.112972E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.167518E+10 | 81.26 | 0.00 | 0.00 |
December | 0.123417E+12 | -0.121678E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.173850E+10 | 81.28 | 0.00 | 0.00 |
Annual Sum or Average | 0.139719E+13 | -0.137648E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.207076E+11 | 81.29 | 0.00 | 0.00 |
Minimum of Months | 0.106500E+12 | -0.125896E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.179094E+10 | 81.25 | 0.00 | 0.00 |
Maximum of Months | 0.127682E+12 | -0.104822E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.159529E+10 | 81.38 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.769909E+11 | -0.754878E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150307E+10 | 58.98 | 0.00 | 0.00 |
February | 0.705552E+11 | -0.691872E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.136796E+10 | 58.98 | 0.00 | 0.00 |
March | 0.771457E+11 | -0.756057E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.154002E+10 | 58.98 | 0.00 | 0.00 |
April | 0.717242E+11 | -0.702262E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.149803E+10 | 58.98 | 0.00 | 0.00 |
May | 0.699605E+11 | -0.684090E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.155147E+10 | 58.98 | 0.00 | 0.00 |
June | 0.636293E+11 | -0.621490E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.148028E+10 | 58.98 | 0.00 | 0.00 |
July | 0.625549E+11 | -0.610428E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151204E+10 | 58.98 | 0.00 | 0.00 |
August | 0.614013E+11 | -0.599135E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.148779E+10 | 58.98 | 0.00 | 0.00 |
September | 0.604287E+11 | -0.590035E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.142517E+10 | 58.98 | 0.00 | 0.00 |
October | 0.654626E+11 | -0.639953E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146739E+10 | 58.98 | 0.00 | 0.00 |
November | 0.674007E+11 | -0.659793E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.142143E+10 | 58.98 | 0.00 | 0.00 |
December | 0.738473E+11 | -0.723688E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.147845E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.821101E+12 | -0.803368E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.177331E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.604287E+11 | -0.756057E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.155147E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.771457E+11 | -0.590035E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.136796E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.87 | 0.86 | 01-JAN-09:30 | 3452.88 | 32.64 | 237.00 | 250.17 | 2289.58 | 32.22 | 237.83 | 212.67 |
February | 262.50 | 0.87 | 0.86 | 01-FEB-09:00 | 4383.70 | 32.69 | 248.00 | 257.33 | 885.23 | 25.38 | 219.33 | 228.33 |
March | 339.33 | 0.87 | 0.86 | 01-MAR-07:49 | 4407.76 | 26.84 | 183.67 | 326.00 | 620.85 | 21.77 | 219.00 | 275.50 |
April | 371.17 | 0.87 | 0.86 | 01-APR-07:10 | 1340.59 | 19.65 | 52.50 | 345.83 | 521.10 | 21.37 | 223.33 | 286.00 |
May | 332.17 | 0.87 | 0.86 | 01-MAY-06:00 | 1181.25 | 19.95 | 44.67 | 384.00 | 482.96 | 21.70 | 235.67 | 300.50 |
June | 430.67 | 0.87 | 0.86 | 01-JUN-06:30 | 1087.17 | 19.61 | 36.33 | 392.50 | 439.57 | 21.35 | 273.00 | 316.33 |
July | 439.00 | 0.87 | 0.86 | 01-JUL-06:49 | 1144.54 | 19.53 | 54.83 | 398.83 | 456.11 | 21.27 | 270.67 | 319.67 |
August | 406.00 | 0.87 | 0.86 | 01-AUG-06:40 | 1378.02 | 19.94 | 73.67 | 376.83 | 536.80 | 21.66 | 275.83 | 310.67 |
September | 289.17 | 0.87 | 0.86 | 01-SEP-07:40 | 1732.84 | 21.18 | 103.00 | 323.83 | 672.58 | 22.39 | 229.17 | 271.17 |
October | 314.33 | 0.87 | 0.86 | 01-OCT-07:49 | 5200.06 | 32.23 | 279.33 | 300.50 | 704.95 | 22.60 | 201.83 | 265.83 |
November | 258.33 | 0.87 | 0.86 | 01-NOV-07:40 | 3287.66 | 32.53 | 241.50 | 242.33 | 1313.46 | 28.85 | 210.00 | 206.00 |
December | 230.67 | 0.87 | 0.86 | 01-DEC-08:09 | 2885.43 | 31.40 | 211.67 | 239.17 | 2131.77 | 32.42 | 218.83 | 195.00 |
Annual Sum or Average | 3928.50 | 0.87 | 2443.19 | 24.68 | 1766.17 | 3837.33 | 823.65 | 23.74 | 2814.50 | 3187.67 | ||
Minimum of Months | 230.67 | 0.87 | 0.86 | 1087.17 | 19.53 | 36.33 | 239.17 | 439.57 | 21.27 | 201.83 | 195.00 | |
Maximum of Months | 439.00 | 0.87 | 0.86 | 5200.06 | 32.69 | 279.33 | 398.83 | 2289.58 | 32.42 | 275.83 | 319.67 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.24 | 0.22 | 01-JAN-08:00 | 3740.08 | 32.78 | 238.17 | 261.50 | 2575.35 | 32.34 | 241.17 | 233.17 |
February | 262.50 | 0.24 | 0.22 | 01-FEB-09:30 | 4692.06 | 32.80 | 249.00 | 264.50 | 1190.93 | 25.51 | 228.00 | 244.67 |
March | 339.33 | 0.24 | 0.22 | 01-MAR-07:30 | 4737.56 | 27.11 | 200.00 | 336.50 | 949.60 | 21.93 | 214.67 | 305.17 |
April | 371.17 | 0.25 | 0.22 | 01-APR-06:49 | 1593.01 | 20.17 | 89.00 | 360.00 | 772.66 | 21.71 | 238.00 | 325.50 |
May | 332.17 | 0.26 | 0.22 | 01-MAY-06:19 | 1420.89 | 20.45 | 92.00 | 401.50 | 721.92 | 22.02 | 249.67 | 354.33 |
June | 430.67 | 0.26 | 0.22 | 01-JUN-06:10 | 1284.92 | 20.25 | 106.17 | 409.00 | 636.67 | 21.80 | 303.67 | 368.50 |
July | 439.00 | 0.26 | 0.22 | 01-JUL-05:00 | 1348.62 | 20.16 | 119.50 | 413.83 | 659.50 | 21.71 | 296.83 | 370.67 |
August | 406.00 | 0.25 | 0.22 | 01-AUG-06:10 | 1618.17 | 20.48 | 127.33 | 390.83 | 776.06 | 22.02 | 294.17 | 352.50 |
September | 289.17 | 0.25 | 0.22 | 01-SEP-07:40 | 2073.95 | 21.40 | 109.33 | 336.17 | 1012.57 | 22.50 | 243.00 | 304.33 |
October | 314.33 | 0.24 | 0.22 | 01-OCT-07:19 | 5514.67 | 32.42 | 280.83 | 309.50 | 1019.52 | 22.81 | 205.33 | 286.17 |
November | 258.33 | 0.25 | 0.22 | 01-NOV-07:40 | 3540.81 | 32.64 | 242.50 | 253.67 | 1567.84 | 28.99 | 220.83 | 227.50 |
December | 230.67 | 0.24 | 0.22 | 01-DEC-07:00 | 3143.07 | 31.55 | 214.50 | 250.00 | 2388.16 | 32.54 | 221.00 | 219.83 |
Annual Sum or Average | 3928.50 | 0.25 | 2706.41 | 25.06 | 2068.33 | 3987.00 | 1086.05 | 24.00 | 2956.33 | 3592.33 | ||
Minimum of Months | 230.67 | 0.24 | 0.22 | 1284.92 | 20.16 | 89.00 | 250.00 | 636.67 | 21.71 | 205.33 | 219.83 | |
Maximum of Months | 439.00 | 0.26 | 0.22 | 5514.67 | 32.80 | 280.83 | 413.83 | 2575.35 | 32.54 | 303.67 | 370.67 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.65 | 0.60 | 01-JAN-10:00 | 419.22 | 14.90 | 0.00 | 232.50 | 183.23 | 18.18 | 0.00 | 99.67 |
February | 262.50 | 0.63 | 0.60 | 01-FEB-12:39 | 552.10 | 15.98 | 0.00 | 249.00 | 237.54 | 19.15 | 0.00 | 177.17 |
March | 339.33 | 0.62 | 0.60 | 01-MAR-08:39 | 561.31 | 16.53 | 0.00 | 324.00 | 253.35 | 19.76 | 0.00 | 244.00 |
April | 371.17 | 0.62 | 0.60 | 01-APR-06:00 | 654.40 | 17.17 | 0.00 | 357.83 | 291.11 | 20.33 | 38.83 | 302.00 |
May | 332.17 | 0.61 | 0.60 | 01-MAY-06:10 | 752.64 | 18.39 | 8.67 | 407.33 | 353.12 | 22.16 | 161.00 | 358.50 |
June | 430.67 | 0.61 | 0.60 | 01-JUN-06:10 | 884.31 | 20.75 | 71.50 | 419.83 | 403.74 | 22.61 | 236.33 | 390.33 |
July | 439.00 | 0.61 | 0.60 | 01-JUL-05:19 | 843.18 | 20.29 | 66.83 | 424.17 | 382.50 | 22.39 | 224.50 | 389.67 |
August | 406.00 | 0.61 | 0.60 | 01-AUG-05:00 | 741.70 | 17.98 | 5.33 | 394.67 | 341.67 | 21.16 | 132.67 | 354.50 |
September | 289.17 | 0.62 | 0.60 | 01-SEP-07:40 | 592.39 | 17.34 | 0.00 | 328.33 | 287.55 | 20.56 | 28.83 | 262.33 |
October | 314.33 | 0.63 | 0.60 | 01-OCT-07:49 | 502.68 | 15.87 | 0.00 | 290.00 | 224.32 | 19.12 | 0.00 | 190.50 |
November | 258.33 | 0.65 | 0.60 | 01-NOV-08:30 | 410.21 | 14.59 | 0.00 | 227.83 | 177.71 | 17.80 | 0.00 | 95.17 |
December | 230.67 | 0.65 | 0.60 | 01-DEC-12:09 | 428.88 | 14.88 | 0.00 | 221.50 | 182.88 | 18.11 | 0.00 | 91.67 |
Annual Sum or Average | 3928.50 | 0.63 | 641.87 | 17.42 | 152.33 | 3877.00 | 290.87 | 20.41 | 822.17 | 2955.50 | ||
Minimum of Months | 230.67 | 0.61 | 0.60 | 410.21 | 14.59 | 0.00 | 221.50 | 177.71 | 17.80 | 0.00 | 91.67 | |
Maximum of Months | 439.00 | 0.65 | 0.60 | 884.31 | 20.75 | 71.50 | 424.17 | 403.74 | 22.61 | 236.33 | 390.33 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.65 | 0.60 | 01-JAN-10:00 | 419.22 | 14.90 | 0.00 | 232.50 | 183.23 | 18.18 | 0.00 | 99.67 |
February | 262.50 | 0.63 | 0.60 | 01-FEB-12:39 | 552.10 | 15.98 | 0.00 | 249.00 | 237.54 | 19.15 | 0.00 | 177.17 |
March | 339.33 | 0.62 | 0.60 | 01-MAR-08:39 | 561.31 | 16.53 | 0.00 | 324.00 | 253.35 | 19.76 | 0.00 | 244.00 |
April | 371.17 | 0.62 | 0.60 | 01-APR-06:00 | 654.40 | 17.17 | 0.00 | 357.83 | 291.11 | 20.33 | 38.83 | 302.00 |
May | 332.17 | 0.61 | 0.60 | 01-MAY-06:10 | 752.64 | 18.39 | 8.67 | 407.33 | 353.12 | 22.16 | 161.00 | 358.50 |
June | 430.67 | 0.61 | 0.60 | 01-JUN-06:10 | 884.31 | 20.75 | 71.50 | 419.83 | 403.74 | 22.61 | 236.33 | 390.33 |
July | 439.00 | 0.61 | 0.60 | 01-JUL-05:19 | 843.18 | 20.29 | 66.83 | 424.17 | 382.50 | 22.39 | 224.50 | 389.67 |
August | 406.00 | 0.61 | 0.60 | 01-AUG-05:00 | 741.70 | 17.98 | 5.33 | 394.67 | 341.67 | 21.16 | 132.67 | 354.50 |
September | 289.17 | 0.62 | 0.60 | 01-SEP-07:40 | 592.39 | 17.34 | 0.00 | 328.33 | 287.55 | 20.56 | 28.83 | 262.33 |
October | 314.33 | 0.63 | 0.60 | 01-OCT-07:49 | 502.68 | 15.87 | 0.00 | 290.00 | 224.32 | 19.12 | 0.00 | 190.50 |
November | 258.33 | 0.65 | 0.60 | 01-NOV-08:30 | 410.21 | 14.59 | 0.00 | 227.83 | 177.71 | 17.80 | 0.00 | 95.17 |
December | 230.67 | 0.65 | 0.60 | 01-DEC-12:09 | 428.88 | 14.88 | 0.00 | 221.50 | 182.88 | 18.11 | 0.00 | 91.67 |
Annual Sum or Average | 3928.50 | 0.63 | 641.87 | 17.42 | 152.33 | 3877.00 | 290.87 | 20.41 | 822.17 | 2955.50 | ||
Minimum of Months | 230.67 | 0.61 | 0.60 | 410.21 | 14.59 | 0.00 | 221.50 | 177.71 | 17.80 | 0.00 | 91.67 | |
Maximum of Months | 439.00 | 0.65 | 0.60 | 884.31 | 20.75 | 71.50 | 424.17 | 403.74 | 22.61 | 236.33 | 390.33 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.981298E+11 | 106901.82 | 06-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.984265E+11 | 125984.96 | 07-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.601739E+11 | 106126.85 | 11-MAR-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.432507E+11 | 106727.20 | 02-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.537130E+11 | 107317.49 | 06-MAY-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.176319E+11 | 102132.10 | 14-JUN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.292307E+10 | 46414.93 | 13-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.630472E+10 | 58163.26 | 01-AUG-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.321126E+11 | 107797.79 | 30-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.634117E+11 | 113025.25 | 17-OCT-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.368933E+11 | 109981.56 | 03-NOV-17:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.819040E+11 | 123414.12 | 11-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.594875E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.292307E+10 | 46414.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.984265E+11 | 125984.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.367669E+10 | 2498.15 | 24-JAN-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.324970E+10 | 2844.92 | 07-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173576E+10 | 2067.56 | 05-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106844E+10 | 1605.92 | 17-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.337427E+09 | 933.20 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31223425.85 | 478.29 | 14-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5559843.96 | 344.77 | 31-AUG-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102148E+09 | 919.74 | 30-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.883407E+09 | 1446.85 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183039E+10 | 1781.09 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.370999E+10 | 2514.91 | 11-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.370999E+10 | 2844.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.220945E+09 | 543.31 | 29-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.204282E+09 | 644.32 | 06-FEB-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7408000.86 | 244.25 | 20-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 345911.52 | 200.83 | 17-APR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7961291.81 | 211.66 | 23-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203944E+09 | 530.25 | 11-DEC-10:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.644886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.220945E+09 | 644.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.142054E+10 | 1034.75 | 31-JAN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135943E+10 | 1263.28 | 07-FEB-11:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.601023E+09 | 896.29 | 07-MAR-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 89225728.64 | 654.51 | 17-APR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2880108.58 | 185.96 | 18-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164044E+09 | 597.37 | 24-NOV-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.124714E+10 | 1096.92 | 11-DEC-10:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.488428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.142054E+10 | 1263.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.117078E+10 | 748.11 | 31-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110141E+10 | 871.45 | 07-FEB-11:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.539578E+09 | 600.04 | 07-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115821E+09 | 434.55 | 17-APR-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16151230.91 | 191.30 | 17-OCT-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.224246E+09 | 398.16 | 24-NOV-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105901E+10 | 787.81 | 11-DEC-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.422700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.117078E+10 | 871.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.451612E+09 | 2539.38 | 30-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.430185E+09 | 2783.11 | 07-FEB-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.303367E+09 | 2289.09 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177141E+09 | 1925.75 | 17-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82623286.07 | 1118.33 | 13-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19516350.59 | 702.29 | 14-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6856327.88 | 423.70 | 10-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7037053.05 | 527.07 | 10-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 39846323.43 | 1123.51 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135247E+09 | 1648.79 | 30-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.226316E+09 | 1924.52 | 24-NOV-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.444543E+09 | 2702.57 | 11-DEC-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6856327.88 | 423.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.451612E+09 | 2783.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.283335E+10 | 5284.24 | 26-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235346E+10 | 6667.39 | 06-FEB-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.629620E+09 | 4007.69 | 20-MAR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.309838E+09 | 2814.94 | 14-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 47502975.74 | 2010.05 | 12-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 504884.27 | 764.57 | 31-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20344202.34 | 1940.30 | 29-SEP-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.178058E+09 | 2301.17 | 08-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106491E+10 | 4038.31 | 30-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.311013E+10 | 5667.72 | 11-DEC-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.311013E+10 | 6667.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.134777E+10 | 8352.30 | 29-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116911E+10 | 10201.02 | 06-FEB-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14021558.78 | 2155.08 | 20-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28056029.23 | 2426.82 | 30-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133878E+10 | 8100.75 | 12-DEC-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.389775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.134777E+10 | 10201.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116684E+11 | 7984.14 | 25-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102194E+11 | 9547.74 | 06-FEB-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.394096E+10 | 5688.74 | 07-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.958964E+09 | 4027.08 | 17-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.615280E+09 | 3811.04 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.410907E+10 | 5642.84 | 30-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115221E+11 | 8744.27 | 11-DEC-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.430341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116684E+11 | 9547.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.726571E+10 | 4921.51 | 10-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.651644E+10 | 5867.23 | 07-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.312723E+10 | 4426.80 | 07-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.887695E+09 | 2945.85 | 17-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5168797.46 | 684.09 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1222914.30 | 333.89 | 30-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.717168E+09 | 2573.01 | 17-OCT-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252261E+10 | 3149.10 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.698318E+10 | 5517.65 | 11-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.280264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.726571E+10 | 5867.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 420872.95 | 304.43 | 07-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26929.50 | 44.88 | 11-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 447802.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 420872.95 | 304.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.394734E+10 | 7525.02 | 31-JAN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.417264E+10 | 8672.33 | 06-FEB-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160914E+10 | 5493.29 | 07-MAR-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 80161231.19 | 1650.66 | 17-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5475.31 | 0.26 | 14-MAY-08:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8843.04 | 0.26 | 25-JUN-23:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10073.91 | 0.26 | 05-JUL-21:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9794.25 | 0.26 | 01-AUG-01:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10244.08 | 0.26 | 26-SEP-15:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15789393.00 | 961.66 | 17-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 63273508.13 | 1436.98 | 24-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.327380E+10 | 7909.92 | 11-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5475.31 | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.417264E+10 | 8672.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.650495E+10 | 10939.39 | 12-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.566020E+10 | 10939.39 | 12-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.258655E+10 | 10911.45 | 06-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103089E+10 | 10711.18 | 16-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 97125579.55 | 5357.80 | 17-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7779091.48 | 4288.66 | 22-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4593643.13 | 4378.88 | 25-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7290715.00 | 4070.84 | 18-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 49449972.21 | 4667.48 | 06-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100692E+10 | 10611.10 | 17-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262087E+10 | 10766.61 | 24-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.633559E+10 | 10939.65 | 09-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4593643.13 | 4070.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.650495E+10 | 10939.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.742250E+10 | 10856.79 | 12-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.642316E+10 | 10856.84 | 12-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.334681E+10 | 10856.16 | 05-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126083E+10 | 10639.17 | 16-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109833E+09 | 5373.92 | 25-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4929041.37 | 3403.60 | 15-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1843583.05 | 2772.85 | 07-JUL-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3762957.61 | 3208.74 | 24-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 55429443.31 | 5199.07 | 06-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134777E+10 | 10652.32 | 17-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316259E+10 | 10704.76 | 24-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.704643E+10 | 10857.05 | 09-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.301859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1843583.05 | 2772.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.742250E+10 | 10857.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.185708E+10 | 14563.84 | 04-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.212621E+10 | 18828.84 | 07-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.503878E+09 | 7628.93 | 10-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.448717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.212621E+10 | 18828.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.265374E+11 | 60768.47 | 31-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236373E+11 | 60768.06 | 06-FEB-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.118831E+11 | 60374.69 | 06-MAR-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152246E+10 | 28028.30 | 22-APR-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 65242314.34 | 48676.08 | 29-MAY-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15990693.65 | 39609.04 | 09-JUN-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3441825.55 | 8102.12 | 18-JUL-21:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8689029.79 | 13420.17 | 22-AUG-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37548566.46 | 15990.86 | 18-SEP-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128601E+10 | 37639.86 | 10-OCT-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.562754E+10 | 57629.65 | 29-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.241306E+11 | 60770.31 | 28-DEC-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.947553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3441825.55 | 8102.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.265374E+11 | 60770.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.631281E+10 | 10677.35 | 03-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.552239E+10 | 10678.01 | 12-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.262765E+10 | 10623.78 | 04-MAR-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102176E+10 | 10381.39 | 16-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122447E+09 | 5032.72 | 02-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6840190.12 | 3025.95 | 03-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 40444.00 | 207.04 | 29-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2095737.87 | 3403.07 | 30-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 48697341.94 | 3195.40 | 14-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.982441E+09 | 10188.77 | 24-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.261891E+10 | 10472.23 | 23-NOV-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.632913E+10 | 10678.28 | 09-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.255952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 40444.00 | 207.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.632913E+10 | 10678.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.720216E+10 | 10596.19 | 03-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.626041E+10 | 10596.91 | 12-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.341519E+10 | 10594.96 | 06-MAR-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123591E+10 | 10311.32 | 16-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139825E+09 | 5336.73 | 02-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4893500.92 | 3340.81 | 13-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 529241.14 | 1964.84 | 04-JUL-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1175311.27 | 2404.02 | 24-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 56467904.21 | 3646.83 | 28-SEP-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127739E+10 | 10134.42 | 24-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.312118E+10 | 10399.54 | 24-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.704021E+10 | 10597.13 | 09-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.297553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 529241.14 | 1964.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.720216E+10 | 10597.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.228634E+10 | 3270.94 | 12-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.199555E+10 | 3270.92 | 03-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.993937E+09 | 3270.62 | 05-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.447292E+09 | 3236.28 | 16-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 76094253.70 | 1364.34 | 17-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6235866.67 | 1015.30 | 21-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1371672.07 | 864.78 | 25-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2896612.98 | 1067.51 | 10-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31833142.02 | 1138.58 | 06-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.446337E+09 | 3211.92 | 17-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100039E+10 | 3225.30 | 24-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.221970E+10 | 3270.94 | 07-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.950799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1371672.07 | 864.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.228634E+10 | 3270.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.255922E+10 | 3240.53 | 12-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.222400E+10 | 3240.53 | 03-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123667E+10 | 3240.20 | 05-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.525809E+09 | 3206.25 | 16-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 79632539.82 | 1320.29 | 17-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2989572.44 | 830.78 | 14-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 466074.61 | 895.60 | 06-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1333709.83 | 1064.44 | 31-AUG-18:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34245192.03 | 1311.90 | 06-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.567999E+09 | 3190.37 | 17-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117542E+10 | 3195.36 | 24-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243030E+10 | 3240.54 | 09-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 466074.61 | 830.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.255922E+10 | 3240.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.735604E+10 | 15566.86 | 03-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.664076E+10 | 15568.12 | 12-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261814E+10 | 15303.74 | 20-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120108E+10 | 15106.09 | 16-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165707E+09 | 7428.84 | 28-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19799079.30 | 4804.54 | 14-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4485503.97 | 4800.78 | 06-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5332663.23 | 3771.38 | 21-AUG-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 44388081.41 | 4399.63 | 26-SEP-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.863797E+09 | 13801.54 | 24-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.261740E+10 | 15151.73 | 24-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.754867E+10 | 15568.60 | 09-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.290856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4485503.97 | 3771.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.754867E+10 | 15568.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.143017E+11 | 0.140469E+11 | 199834.33 | 14-MAR-10:45 | 137297.12 | 0.06 |
April | 0.00 | 0.00 | 0.824425E+10 | 0.824425E+10 | 102314.88 | 08-APR-13:00 | 102314.88 | 0.02 |
May | 0.00 | 0.00 | 0.675017E+11 | 0.662702E+11 | 181804.83 | 10-MAY-15:30 | 158447.69 | 0.22 |
June | 0.00 | 0.00 | 0.275839E+12 | 0.202072E+12 | 507585.37 | 27-JUN-20:08 | 201471.50 | 0.66 |
July | 0.00 | 0.00 | 0.513129E+12 | 0.323198E+12 | 507216.55 | 21-JUL-20:04 | 200390.93 | 0.94 |
August | 0.00 | 0.00 | 0.375044E+12 | 0.271710E+12 | 441919.64 | 14-AUG-22:00 | 200150.89 | 0.89 |
September | 0.00 | 0.00 | 0.181601E+12 | 0.134371E+12 | 414252.61 | 15-SEP-20:10 | 169015.22 | 0.55 |
October | 0.00 | 0.00 | 0.223274E+11 | 0.223274E+11 | 129462.64 | 11-OCT-15:15 | 129462.64 | 0.13 |
November | 0.00 | 0.00 | 0.709649E+10 | 0.709649E+10 | 76601.74 | 05-NOV-10:50 | 76601.74 | 0.05 |
December | 0.00 | 0.00 | 5785851.23 | 5785851.23 | 3359.53 | 01-DEC-11:00 | 3359.53 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.146509E+13 | 0.104934E+13 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.513129E+12 | 0.323198E+12 | 507585.37 | 201471.50 | 0.94 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.106379E+10 | 0.101811E+10 | 21341.77 | 14-MAR-12:20 | 16151.24 | 0.05 |
April | 0.00 | 0.00 | 0.441673E+09 | 0.441673E+09 | 13334.55 | 08-APR-13:00 | 13334.55 | 0.02 |
May | 0.00 | 0.00 | 0.486239E+10 | 0.463851E+10 | 21425.28 | 10-MAY-15:02 | 17574.64 | 0.15 |
June | 0.00 | 0.00 | 0.222930E+11 | 0.153159E+11 | 42332.09 | 18-JUN-08:62 | 18551.83 | 0.51 |
July | 0.00 | 0.00 | 0.404864E+11 | 0.246713E+11 | 41906.99 | 17-JUL-18:10 | 17675.00 | 0.74 |
August | 0.00 | 0.00 | 0.296902E+11 | 0.202919E+11 | 40422.42 | 14-AUG-08:62 | 17900.73 | 0.68 |
September | 0.00 | 0.00 | 0.147656E+11 | 0.100051E+11 | 37046.77 | 15-SEP-20:00 | 15150.12 | 0.42 |
October | 0.00 | 0.00 | 0.151434E+10 | 0.151412E+10 | 14829.46 | 11-OCT-15:01 | 14829.46 | 0.09 |
November | 0.00 | 0.00 | 0.566793E+09 | 0.566793E+09 | 8665.51 | 05-NOV-13:00 | 8665.51 | 0.03 |
December | 0.00 | 0.00 | 850142.93 | 850142.93 | 572.22 | 01-DEC-11:00 | 572.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.115685E+12 | 0.784642E+11 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.404864E+11 | 0.246713E+11 | 42332.09 | 18551.83 | 0.74 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 12305601.01 | 8831516.85 | 10637.86 | 12-JAN-16:01 | 10637.86 | 0.00 |
February | 0.00 | 0.00 | 36346354.07 | 31004518.04 | 12899.15 | 28-FEB-16:02 | 12899.15 | 0.00 |
March | 0.00 | 0.00 | 0.677186E+09 | 0.472503E+09 | 14447.41 | 14-MAR-15:01 | 12896.67 | 0.10 |
April | 0.00 | 0.00 | 0.148888E+10 | 0.108532E+10 | 12939.13 | 30-APR-15:02 | 12094.87 | 0.25 |
May | 0.00 | 0.00 | 0.388982E+10 | 0.269559E+10 | 14675.62 | 17-MAY-15:01 | 11308.98 | 0.59 |
June | 0.00 | 0.00 | 0.791596E+10 | 0.513636E+10 | 16920.32 | 18-JUN-08:62 | 11448.27 | 0.88 |
July | 0.00 | 0.00 | 0.100816E+11 | 0.628696E+10 | 16761.69 | 17-JUL-08:62 | 11451.65 | 0.95 |
August | 0.00 | 0.00 | 0.898332E+10 | 0.562766E+10 | 17130.14 | 14-AUG-08:62 | 11313.59 | 0.93 |
September | 0.00 | 0.00 | 0.528751E+10 | 0.301814E+10 | 16662.65 | 13-SEP-18:02 | 11084.25 | 0.86 |
October | 0.00 | 0.00 | 0.121414E+10 | 0.649176E+09 | 14798.28 | 01-OCT-08:62 | 9898.67 | 0.32 |
November | 0.00 | 0.00 | 0.109491E+09 | 57916374.71 | 13671.51 | 04-NOV-15:01 | 11240.80 | 0.05 |
December | 0.00 | 0.00 | 9396450.74 | 6752028.67 | 12104.49 | 04-DEC-16:01 | 12104.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.397060E+11 | 0.250762E+11 | 0.41 | |||
Minimum of Months | 0.00 | 0.00 | 9396450.74 | 6752028.67 | 10637.86 | 9898.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.100816E+11 | 0.628696E+10 | 17130.14 | 12899.15 | 0.95 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4637043.45 | 3283151.11 | 4325.25 | 11-JAN-16:04 | 3048.55 | 0.00 |
February | 0.00 | 0.00 | 8346076.31 | 6761623.44 | 8270.46 | 18-FEB-16:01 | 7707.50 | 0.00 |
March | 0.00 | 0.00 | 0.287524E+09 | 0.177041E+09 | 15810.81 | 14-MAR-15:01 | 11365.00 | 0.06 |
April | 0.00 | 0.00 | 0.866674E+09 | 0.621482E+09 | 13969.82 | 19-APR-18:11 | 13969.82 | 0.17 |
May | 0.00 | 0.00 | 0.245279E+10 | 0.152293E+10 | 14220.94 | 17-MAY-18:01 | 10695.99 | 0.46 |
June | 0.00 | 0.00 | 0.569824E+10 | 0.357266E+10 | 19450.11 | 18-JUN-08:21 | 10888.50 | 0.66 |
July | 0.00 | 0.00 | 0.788983E+10 | 0.504733E+10 | 19549.39 | 16-JUL-08:21 | 10833.24 | 0.71 |
August | 0.00 | 0.00 | 0.649722E+10 | 0.401305E+10 | 19076.50 | 14-AUG-08:21 | 10589.89 | 0.68 |
September | 0.00 | 0.00 | 0.274220E+10 | 0.130062E+10 | 16520.74 | 17-SEP-08:51 | 10675.68 | 0.59 |
October | 0.00 | 0.00 | 0.376079E+09 | 0.168932E+09 | 14153.44 | 01-OCT-08:62 | 9364.47 | 0.15 |
November | 0.00 | 0.00 | 27241933.52 | 16610333.60 | 12310.07 | 05-NOV-15:01 | 10747.15 | 0.01 |
December | 0.00 | 0.00 | 5357442.05 | 3561567.33 | 4575.53 | 14-DEC-19:04 | 3171.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.268561E+11 | 0.164543E+11 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 4637043.45 | 3283151.11 | 4325.25 | 3048.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.788983E+10 | 0.504733E+10 | 19549.39 | 13969.82 | 0.71 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.313904E+10 | 0.172434E+10 | 42925.00 | 15-MAR-13:30 | 36080.47 | 0.09 |
April | 0.00 | 0.00 | 0.956244E+10 | 0.789545E+10 | 32891.14 | 22-APR-13:00 | 32891.14 | 0.13 |
May | 0.00 | 0.00 | 0.216262E+11 | 0.126887E+11 | 32089.61 | 14-MAY-13:30 | 22292.58 | 0.57 |
June | 0.00 | 0.00 | 0.342163E+11 | 0.164965E+11 | 36010.64 | 27-JUN-13:00 | 26977.09 | 0.95 |
July | 0.00 | 0.00 | 0.467895E+11 | 0.245637E+11 | 41387.52 | 30-JUL-12:30 | 34192.53 | 1.00 |
August | 0.00 | 0.00 | 0.467812E+11 | 0.264978E+11 | 44809.75 | 18-AUG-12:40 | 42388.33 | 0.99 |
September | 0.00 | 0.00 | 0.379898E+11 | 0.222123E+11 | 55589.01 | 21-SEP-13:00 | 46143.87 | 0.92 |
October | 0.00 | 0.00 | 0.172974E+11 | 0.112612E+11 | 56601.38 | 11-OCT-12:30 | 48813.07 | 0.43 |
November | 0.00 | 0.00 | 0.302593E+10 | 0.222391E+10 | 32081.69 | 03-NOV-12:30 | 32081.69 | 0.07 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.220428E+12 | 0.125564E+12 | 0.43 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.467895E+11 | 0.264978E+11 | 56601.38 | 48813.07 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.102399E+09 | 82046476.21 | 44527.93 | 15-JAN-09:01 | 44527.93 | 0.01 |
February | 0.00 | 0.00 | 83889361.17 | 82058330.44 | 52690.24 | 19-FEB-09:01 | 52690.24 | 0.00 |
March | 0.00 | 0.00 | 0.498884E+10 | 0.295238E+10 | 76044.78 | 14-MAR-15:01 | 61823.90 | 0.17 |
April | 0.00 | 0.00 | 0.989810E+10 | 0.704165E+10 | 64407.01 | 07-APR-15:02 | 64407.01 | 0.32 |
May | 0.00 | 0.00 | 0.242260E+11 | 0.177871E+11 | 74959.32 | 10-MAY-15:02 | 65232.02 | 0.47 |
June | 0.00 | 0.00 | 0.399824E+11 | 0.286595E+11 | 100116.72 | 18-JUN-08:21 | 54737.00 | 0.57 |
July | 0.00 | 0.00 | 0.532835E+11 | 0.371007E+11 | 100598.94 | 16-JUL-08:21 | 53370.73 | 0.65 |
August | 0.00 | 0.00 | 0.451365E+11 | 0.311498E+11 | 98818.58 | 14-AUG-08:21 | 50897.10 | 0.62 |
September | 0.00 | 0.00 | 0.268847E+11 | 0.169283E+11 | 85410.73 | 15-SEP-21:51 | 58252.45 | 0.56 |
October | 0.00 | 0.00 | 0.102962E+11 | 0.562704E+10 | 68454.50 | 01-OCT-08:62 | 56831.83 | 0.43 |
November | 0.00 | 0.00 | 0.263219E+10 | 0.163888E+10 | 61863.43 | 04-NOV-15:01 | 57594.54 | 0.14 |
December | 0.00 | 0.00 | 0.156690E+09 | 0.103718E+09 | 57576.25 | 03-DEC-09:01 | 57576.25 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.217671E+12 | 0.149153E+12 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 83889361.17 | 82046476.21 | 44527.93 | 44527.93 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.532835E+11 | 0.371007E+11 | 100598.94 | 65232.02 | 0.65 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 7395147.93 | 5604546.70 | 6517.84 | 15-JAN-16:01 | 6022.95 | 0.00 |
February | 0.00 | 0.00 | 35137383.88 | 33920973.15 | 10930.63 | 28-FEB-09:01 | 10930.63 | 0.00 |
March | 0.00 | 0.00 | 0.612417E+09 | 0.411493E+09 | 12778.62 | 14-MAR-08:62 | 9465.88 | 0.09 |
April | 0.00 | 0.00 | 0.159462E+10 | 0.113697E+10 | 11937.13 | 30-APR-15:02 | 10841.81 | 0.29 |
May | 0.00 | 0.00 | 0.385876E+10 | 0.255746E+10 | 13271.27 | 17-MAY-15:01 | 10313.51 | 0.62 |
June | 0.00 | 0.00 | 0.746437E+10 | 0.468117E+10 | 14935.45 | 08-JUN-08:62 | 9166.59 | 0.90 |
July | 0.00 | 0.00 | 0.100994E+11 | 0.634183E+10 | 15177.35 | 05-JUL-18:02 | 10047.92 | 0.97 |
August | 0.00 | 0.00 | 0.890887E+10 | 0.559974E+10 | 15417.28 | 14-AUG-08:62 | 10372.45 | 0.96 |
September | 0.00 | 0.00 | 0.544417E+10 | 0.315351E+10 | 15139.56 | 17-SEP-08:61 | 10072.17 | 0.87 |
October | 0.00 | 0.00 | 0.131857E+10 | 0.701358E+09 | 13601.36 | 01-OCT-08:62 | 9319.70 | 0.36 |
November | 0.00 | 0.00 | 0.169614E+09 | 89852205.64 | 12261.76 | 04-NOV-15:01 | 9952.99 | 0.06 |
December | 0.00 | 0.00 | 17302079.07 | 10535534.55 | 4670.71 | 14-DEC-19:04 | 3416.84 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.395306E+11 | 0.247234E+11 | 0.43 | |||
Minimum of Months | 0.00 | 0.00 | 7395147.93 | 5604546.70 | 4670.71 | 3416.84 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.100994E+11 | 0.634183E+10 | 15417.28 | 10930.63 | 0.97 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3960360.98 | 2897021.51 | 3744.70 | 11-JAN-19:04 | 2202.81 | 0.00 |
February | 0.00 | 0.00 | 6835412.89 | 6197474.39 | 5755.90 | 28-FEB-09:01 | 5755.90 | 0.00 |
March | 0.00 | 0.00 | 0.260352E+09 | 0.142278E+09 | 13694.60 | 14-MAR-15:01 | 10769.73 | 0.07 |
April | 0.00 | 0.00 | 0.925866E+09 | 0.649107E+09 | 11366.43 | 09-APR-08:62 | 10643.46 | 0.20 |
May | 0.00 | 0.00 | 0.267046E+10 | 0.168784E+10 | 13234.17 | 17-MAY-18:01 | 9576.98 | 0.52 |
June | 0.00 | 0.00 | 0.558560E+10 | 0.350357E+10 | 18104.73 | 18-JUN-08:21 | 11046.86 | 0.69 |
July | 0.00 | 0.00 | 0.784411E+10 | 0.499412E+10 | 18378.83 | 17-JUL-08:32 | 13109.34 | 0.72 |
August | 0.00 | 0.00 | 0.644212E+10 | 0.394286E+10 | 17445.40 | 14-AUG-08:21 | 9716.59 | 0.70 |
September | 0.00 | 0.00 | 0.312506E+10 | 0.161463E+10 | 16048.71 | 16-SEP-08:51 | 11905.93 | 0.64 |
October | 0.00 | 0.00 | 0.461815E+09 | 0.221599E+09 | 13109.88 | 01-OCT-08:62 | 8840.55 | 0.18 |
November | 0.00 | 0.00 | 37757523.29 | 17798934.77 | 11300.78 | 05-NOV-15:01 | 9936.17 | 0.02 |
December | 0.00 | 0.00 | 4732136.64 | 3255615.74 | 4371.07 | 14-DEC-09:04 | 3058.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.273687E+11 | 0.167861E+11 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 3960360.98 | 2897021.51 | 3744.70 | 2202.81 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.784411E+10 | 0.499412E+10 | 18378.83 | 13109.34 | 0.72 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3839323.17 | 2755924.31 | 2822.60 | 15-JAN-16:01 | 2822.60 | 0.00 |
February | 0.00 | 0.00 | 9324433.07 | 7959376.74 | 3378.01 | 28-FEB-16:02 | 3378.01 | 0.00 |
March | 0.00 | 0.00 | 0.157525E+09 | 0.109562E+09 | 3763.58 | 16-MAR-15:01 | 3130.82 | 0.09 |
April | 0.00 | 0.00 | 0.376432E+09 | 0.279167E+09 | 3421.97 | 30-APR-15:02 | 3148.49 | 0.21 |
May | 0.00 | 0.00 | 0.964846E+09 | 0.694230E+09 | 3864.03 | 17-MAY-15:01 | 2948.91 | 0.51 |
June | 0.00 | 0.00 | 0.199143E+10 | 0.130778E+10 | 4620.01 | 18-JUN-08:62 | 2881.27 | 0.85 |
July | 0.00 | 0.00 | 0.256002E+10 | 0.159832E+10 | 4659.05 | 29-JUL-08:61 | 2666.76 | 0.94 |
August | 0.00 | 0.00 | 0.223089E+10 | 0.140181E+10 | 4777.81 | 14-AUG-08:62 | 2781.50 | 0.92 |
September | 0.00 | 0.00 | 0.124228E+10 | 0.731010E+09 | 4565.24 | 17-SEP-08:61 | 2777.98 | 0.77 |
October | 0.00 | 0.00 | 0.273061E+09 | 0.155196E+09 | 3902.36 | 01-OCT-15:02 | 2717.73 | 0.24 |
November | 0.00 | 0.00 | 21905522.36 | 13040226.91 | 3625.82 | 04-NOV-15:01 | 2835.97 | 0.03 |
December | 0.00 | 0.00 | 3291549.84 | 2272543.68 | 2644.89 | 04-DEC-16:01 | 2644.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.983485E+10 | 0.630310E+10 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 3291549.84 | 2272543.68 | 2644.89 | 2644.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.256002E+10 | 0.159832E+10 | 4777.81 | 3378.01 | 0.94 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1606283.93 | 1104128.10 | 1275.40 | 11-JAN-19:04 | 811.37 | 0.00 |
February | 0.00 | 0.00 | 1760115.63 | 1352961.52 | 1011.15 | 20-FEB-09:04 | 698.62 | 0.00 |
March | 0.00 | 0.00 | 60457793.26 | 34955285.47 | 4123.25 | 14-MAR-15:01 | 2970.78 | 0.05 |
April | 0.00 | 0.00 | 0.217260E+09 | 0.155609E+09 | 3758.44 | 19-APR-18:11 | 3758.44 | 0.14 |
May | 0.00 | 0.00 | 0.605478E+09 | 0.388264E+09 | 3785.68 | 31-MAY-21:51 | 3549.94 | 0.41 |
June | 0.00 | 0.00 | 0.148586E+10 | 0.942565E+09 | 5266.96 | 18-JUN-08:21 | 2746.33 | 0.66 |
July | 0.00 | 0.00 | 0.206314E+10 | 0.132762E+10 | 5311.27 | 16-JUL-08:21 | 2682.24 | 0.71 |
August | 0.00 | 0.00 | 0.165095E+10 | 0.102646E+10 | 5213.21 | 14-AUG-08:21 | 2581.34 | 0.68 |
September | 0.00 | 0.00 | 0.618144E+09 | 0.298509E+09 | 4436.33 | 17-SEP-08:51 | 2686.44 | 0.53 |
October | 0.00 | 0.00 | 70744180.66 | 33638612.46 | 3783.79 | 01-OCT-15:02 | 2495.21 | 0.10 |
November | 0.00 | 0.00 | 6542346.30 | 3999915.85 | 2885.40 | 05-NOV-15:01 | 2246.50 | 0.01 |
December | 0.00 | 0.00 | 2090086.07 | 1272825.76 | 1384.39 | 01-DEC-16:04 | 865.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.678403E+10 | 0.421535E+10 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 1606283.93 | 1104128.10 | 1011.15 | 698.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.206314E+10 | 0.132762E+10 | 5311.27 | 3758.44 | 0.71 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.297006E+09 | 0.262158E+09 | 15769.69 | 06-JAN-16:01 | 15769.69 | 0.01 |
February | 0.00 | 0.00 | 0.295655E+09 | 0.270962E+09 | 15775.67 | 22-FEB-16:02 | 15775.67 | 0.01 |
March | 0.00 | 0.00 | 0.219535E+10 | 0.176479E+10 | 17145.28 | 16-MAR-15:01 | 14869.09 | 0.14 |
April | 0.00 | 0.00 | 0.281490E+10 | 0.202845E+10 | 16009.36 | 30-APR-15:02 | 14683.17 | 0.35 |
May | 0.00 | 0.00 | 0.499251E+10 | 0.333147E+10 | 18010.51 | 17-MAY-15:01 | 13804.76 | 0.58 |
June | 0.00 | 0.00 | 0.879294E+10 | 0.517846E+10 | 21439.57 | 27-JUN-08:62 | 13726.96 | 0.84 |
July | 0.00 | 0.00 | 0.126314E+11 | 0.763114E+10 | 21982.80 | 28-JUL-18:02 | 12721.38 | 0.94 |
August | 0.00 | 0.00 | 0.120267E+11 | 0.752373E+10 | 22708.64 | 14-AUG-08:62 | 12787.94 | 0.93 |
September | 0.00 | 0.00 | 0.896432E+10 | 0.572928E+10 | 21205.12 | 17-SEP-08:61 | 13079.68 | 0.87 |
October | 0.00 | 0.00 | 0.404991E+10 | 0.270387E+10 | 17730.72 | 01-OCT-08:62 | 13089.29 | 0.51 |
November | 0.00 | 0.00 | 0.133296E+10 | 0.876350E+09 | 17370.73 | 04-NOV-15:01 | 14537.77 | 0.22 |
December | 0.00 | 0.00 | 0.325667E+09 | 0.259513E+09 | 15765.29 | 11-DEC-16:01 | 15765.29 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.587193E+11 | 0.375602E+11 | 0.46 | |||
Minimum of Months | 0.00 | 0.00 | 0.295655E+09 | 0.259513E+09 | 15765.29 | 12721.38 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.126314E+11 | 0.763114E+10 | 22708.64 | 15775.67 | 0.94 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 74004.67 | 245028.14 | 31-JAN-16:03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 77653.74 | 281202.49 | 06-FEB-09:03 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 37479.20 | 211126.24 | 06-MAR-19:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 21073.46 | 139169.16 | 25-APR-15:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 20362.39 | 118121.91 | 18-MAY-08:04 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 6792.09 | 120739.62 | 13-JUN-08:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1094.15 | 46659.94 | 13-JUL-04:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 2343.52 | 57701.00 | 01-AUG-06:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12484.66 | 108067.91 | 30-SEP-06:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27291.46 | 161591.63 | 19-OCT-08:62 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 26369.03 | 184018.07 | 24-NOV-09:01 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 65937.46 | 263474.56 | 11-DEC-09:03 |
Annual Sum or Average | 0.00 | 30848.71 | ||||
Minimum of Months | 0.00 | 0.00 | 1094.15 | 46659.94 | ||
Maximum of Months | 0.00 | 0.00 | 77653.74 | 281202.49 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 418.27 | 29638.47 | 15-JAN-09:01 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 460.89 | 41301.64 | 28-FEB-16:05 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 12167.50 | 334477.95 | 15-MAR-15:03 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 16963.36 | 217146.35 | 08-APR-15:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 55484.48 | 361557.02 | 10-MAY-15:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 162879.24 | 587884.53 | 27-JUN-20:10 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 268185.39 | 629198.02 | 21-JUL-20:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 207134.04 | 547315.45 | 14-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 115517.22 | 526646.55 | 15-SEP-21:53 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 25327.24 | 313099.72 | 11-OCT-15:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 7483.39 | 173351.32 | 04-NOV-15:01 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 482.16 | 32860.96 | 01-DEC-19:02 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 73269.51 | 0.00 | ||||
Minimum of Months | 418.27 | 29638.47 | 0.00 | 0.00 | ||
Maximum of Months | 268185.39 | 629198.02 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 29745.91 | 61103.44 | 31-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 30160.36 | 61321.07 | 14-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 29790.00 | 61134.73 | 01-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 28657.45 | 59243.43 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 27108.19 | 56536.57 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25547.47 | 53072.43 | 01-JUN-06:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 24364.01 | 49948.14 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23943.19 | 48358.78 | 31-AUG-06:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24337.11 | 49915.90 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25464.47 | 52964.24 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27021.96 | 56320.13 | 30-NOV-07:10 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 28583.86 | 59185.53 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 27042.19 | ||||
Minimum of Months | 0.00 | 0.00 | 23943.19 | 48358.78 | ||
Maximum of Months | 0.00 | 0.00 | 30160.36 | 61321.07 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.71 | 1299.30 | 01-JAN-00:30 | 0.90 |
February | 0.244774E+10 | 0.71 | 1299.30 | 01-FEB-00:10 | 0.90 |
March | 0.271000E+10 | 0.71 | 1299.30 | 01-MAR-00:07 | 0.90 |
April | 0.262258E+10 | 0.71 | 1299.30 | 01-APR-00:10 | 0.90 |
May | 0.271000E+10 | 0.71 | 1299.30 | 01-MAY-00:10 | 0.90 |
June | 0.262258E+10 | 0.71 | 1299.30 | 01-JUN-00:05 | 0.89 |
July | 0.271000E+10 | 0.71 | 1299.30 | 01-JUL-02:70 | 0.89 |
August | 0.271000E+10 | 0.71 | 1299.30 | 25-AUG-15:10 | 0.89 |
September | 0.262258E+10 | 0.71 | 1299.30 | 01-SEP-00:10 | 0.89 |
October | 0.271000E+10 | 0.71 | 1299.30 | 01-OCT-00:20 | 0.89 |
November | 0.262258E+10 | 0.71 | 1299.30 | 19-NOV-19:01 | 0.90 |
December | 0.271000E+10 | 0.71 | 1299.30 | 01-DEC-00:07 | 0.90 |
Annual Sum or Average | 0.319080E+11 | 0.71 | |||
Minimum of Months | 0.244774E+10 | 0.71 | 1299.30 | 0.89 | |
Maximum of Months | 0.271000E+10 | 0.71 | 1299.30 | 0.90 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.332765E+11 | 0.84 | 17839.90 | 17-JAN-19:40 | 1.02 |
February | 0.300809E+11 | 0.84 | 18053.39 | 22-FEB-21:10 | 1.03 |
March | 0.346699E+11 | 0.85 | 24476.51 | 15-MAR-21:10 | 1.23 |
April | 0.343583E+11 | 0.86 | 21255.66 | 07-APR-21:10 | 1.14 |
May | 0.369396E+11 | 0.88 | 24622.64 | 23-MAY-21:10 | 1.24 |
June | 0.376059E+11 | 0.90 | 27176.09 | 29-JUN-21:10 | 1.31 |
July | 0.400735E+11 | 0.91 | 28201.28 | 21-JUL-21:10 | 1.34 |
August | 0.399292E+11 | 0.91 | 28692.29 | 11-AUG-21:10 | 1.36 |
September | 0.370435E+11 | 0.89 | 29516.92 | 21-SEP-21:10 | 1.38 |
October | 0.364379E+11 | 0.87 | 26340.22 | 11-OCT-21:10 | 1.30 |
November | 0.340714E+11 | 0.86 | 20404.88 | 16-NOV-22:10 | 1.11 |
December | 0.334715E+11 | 0.84 | 19121.85 | 01-DEC-19:20 | 1.07 |
Annual Sum or Average | 0.427958E+12 | 0.87 | |||
Minimum of Months | 0.300809E+11 | 0.84 | 17839.90 | 1.02 | |
Maximum of Months | 0.400735E+11 | 0.91 | 29516.92 | 1.38 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:05 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:03 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:03 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.27 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:05 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:05 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:05 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:05 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:05 | 0.27 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:03 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:03 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:05 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.305819E+09 | 0.49 | 770.91 | 01-JAN-09:01 | 0.59 |
February | 0.267189E+09 | 0.48 | 770.91 | 01-FEB-09:01 | 0.59 |
March | 0.188756E+09 | 0.44 | 770.91 | 01-MAR-09:01 | 0.59 |
April | 0.175893E+09 | 0.46 | 770.91 | 02-APR-15:02 | 0.59 |
May | 0.259748E+09 | 0.50 | 770.91 | 01-MAY-15:02 | 0.59 |
June | 0.428542E+09 | 0.54 | 770.91 | 01-JUN-08:62 | 0.58 |
July | 0.501413E+09 | 0.56 | 770.91 | 01-JUL-08:62 | 0.58 |
August | 0.462631E+09 | 0.55 | 770.91 | 01-AUG-08:62 | 0.59 |
September | 0.301383E+09 | 0.53 | 770.91 | 01-SEP-08:62 | 0.58 |
October | 0.150774E+09 | 0.45 | 770.91 | 01-OCT-08:62 | 0.58 |
November | 0.165160E+09 | 0.42 | 770.91 | 01-NOV-15:02 | 0.59 |
December | 0.301318E+09 | 0.49 | 770.91 | 01-DEC-16:01 | 0.59 |
Annual Sum or Average | 0.350863E+10 | 0.49 | |||
Minimum of Months | 0.150774E+09 | 0.42 | 770.91 | 0.58 | |
Maximum of Months | 0.501413E+09 | 0.56 | 770.91 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.333834E+09 | 0.53 | 744.25 | 01-JAN-09:01 | 0.59 |
February | 0.289162E+09 | 0.51 | 744.25 | 01-FEB-09:01 | 0.59 |
March | 0.192837E+09 | 0.42 | 744.25 | 01-MAR-09:01 | 0.59 |
April | 0.144011E+09 | 0.42 | 744.25 | 02-APR-15:02 | 0.59 |
May | 0.166678E+09 | 0.40 | 744.25 | 01-MAY-15:02 | 0.59 |
June | 0.300817E+09 | 0.39 | 744.25 | 01-JUN-08:51 | 0.58 |
July | 0.390840E+09 | 0.42 | 744.25 | 01-JUL-08:51 | 0.58 |
August | 0.330379E+09 | 0.40 | 744.25 | 01-AUG-08:51 | 0.59 |
September | 0.157046E+09 | 0.37 | 744.25 | 01-SEP-08:62 | 0.58 |
October | 0.117067E+09 | 0.39 | 744.25 | 01-OCT-08:62 | 0.58 |
November | 0.178925E+09 | 0.41 | 744.25 | 02-NOV-08:62 | 0.59 |
December | 0.321068E+09 | 0.52 | 744.25 | 01-DEC-09:02 | 0.59 |
Annual Sum or Average | 0.292266E+10 | 0.43 | |||
Minimum of Months | 0.117067E+09 | 0.37 | 744.25 | 0.58 | |
Maximum of Months | 0.390840E+09 | 0.53 | 744.25 | 0.59 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.129408E+09 | 0.09 | 695.88 | 04-JAN-05:00 | 0.59 |
February | 0.133591E+09 | 0.08 | 819.10 | 07-FEB-05:00 | 0.59 |
March | 0.154917E+09 | 0.08 | 1376.68 | 15-MAR-13:30 | 0.59 |
April | 0.488592E+09 | 0.22 | 1258.50 | 22-APR-13:00 | 0.59 |
May | 0.104861E+10 | 0.44 | 1167.36 | 06-MAY-13:00 | 0.59 |
June | 0.145748E+10 | 0.56 | 1202.05 | 12-JUN-13:10 | 0.59 |
July | 0.182974E+10 | 0.59 | 1350.41 | 21-JUL-13:30 | 0.59 |
August | 0.186640E+10 | 0.58 | 2180.67 | 19-AUG-13:30 | 0.59 |
September | 0.162798E+10 | 0.54 | 2461.54 | 21-SEP-12:50 | 0.59 |
October | 0.839505E+09 | 0.32 | 2555.81 | 11-OCT-12:30 | 0.59 |
November | 0.161056E+09 | 0.08 | 1315.46 | 01-NOV-11:40 | 0.59 |
December | 39302677.74 | 0.03 | 466.25 | 10-DEC-06:00 | 0.59 |
Annual Sum or Average | 0.977658E+10 | 0.30 | |||
Minimum of Months | 39302677.74 | 0.03 | 466.25 | 0.59 | |
Maximum of Months | 0.186640E+10 | 0.59 | 2555.81 | 0.59 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.121258E+10 | 0.42 | 3787.56 | 01-JAN-16:01 | 0.59 |
February | 0.108120E+10 | 0.42 | 3787.56 | 01-FEB-09:01 | 0.59 |
March | 0.907200E+09 | 0.41 | 3787.56 | 01-MAR-09:01 | 0.59 |
April | 0.778087E+09 | 0.40 | 3787.56 | 01-APR-08:62 | 0.59 |
May | 0.143370E+10 | 0.36 | 3787.56 | 01-MAY-08:62 | 0.59 |
June | 0.215346E+10 | 0.35 | 3787.56 | 01-JUN-08:51 | 0.59 |
July | 0.271400E+10 | 0.38 | 3787.56 | 01-JUL-08:51 | 0.59 |
August | 0.229027E+10 | 0.36 | 3787.56 | 01-AUG-08:51 | 0.59 |
September | 0.141290E+10 | 0.33 | 3787.56 | 01-SEP-08:62 | 0.59 |
October | 0.749094E+09 | 0.38 | 3787.56 | 01-OCT-08:62 | 0.58 |
November | 0.580019E+09 | 0.41 | 3787.56 | 01-NOV-08:62 | 0.59 |
December | 0.113336E+10 | 0.42 | 3787.56 | 01-DEC-19:02 | 0.59 |
Annual Sum or Average | 0.164459E+11 | 0.39 | |||
Minimum of Months | 0.580019E+09 | 0.33 | 3787.56 | 0.58 | |
Maximum of Months | 0.271400E+10 | 0.42 | 3787.56 | 0.59 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.279003E+09 | 0.48 | 699.57 | 01-JAN-09:01 | 0.59 |
February | 0.244419E+09 | 0.47 | 699.57 | 01-FEB-09:01 | 0.59 |
March | 0.175157E+09 | 0.43 | 699.57 | 01-MAR-09:01 | 0.59 |
April | 0.173548E+09 | 0.47 | 699.57 | 01-APR-08:62 | 0.59 |
May | 0.246917E+09 | 0.52 | 699.57 | 01-MAY-08:62 | 0.59 |
June | 0.390996E+09 | 0.56 | 699.57 | 01-JUN-08:62 | 0.58 |
July | 0.493615E+09 | 0.57 | 699.57 | 01-JUL-08:62 | 0.59 |
August | 0.444249E+09 | 0.56 | 699.57 | 01-AUG-08:62 | 0.59 |
September | 0.295621E+09 | 0.54 | 699.57 | 01-SEP-08:62 | 0.58 |
October | 0.148706E+09 | 0.46 | 699.57 | 01-OCT-08:62 | 0.58 |
November | 0.157512E+09 | 0.42 | 699.57 | 01-NOV-15:02 | 0.59 |
December | 0.282712E+09 | 0.49 | 699.57 | 01-DEC-16:01 | 0.59 |
Annual Sum or Average | 0.333246E+10 | 0.50 | |||
Minimum of Months | 0.148706E+09 | 0.42 | 699.57 | 0.58 | |
Maximum of Months | 0.493615E+09 | 0.57 | 699.57 | 0.59 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.306693E+09 | 0.52 | 676.90 | 01-JAN-09:01 | 0.59 |
February | 0.265234E+09 | 0.50 | 676.90 | 01-FEB-09:01 | 0.59 |
March | 0.181769E+09 | 0.42 | 676.90 | 01-MAR-09:01 | 0.59 |
April | 0.141571E+09 | 0.43 | 676.90 | 01-APR-08:62 | 0.59 |
May | 0.180438E+09 | 0.43 | 676.90 | 01-MAY-08:62 | 0.59 |
June | 0.297292E+09 | 0.41 | 676.90 | 01-JUN-08:51 | 0.58 |
July | 0.383843E+09 | 0.42 | 676.90 | 01-JUL-08:51 | 0.58 |
August | 0.320759E+09 | 0.41 | 676.90 | 01-AUG-08:51 | 0.59 |
September | 0.179064E+09 | 0.40 | 676.90 | 01-SEP-08:62 | 0.58 |
October | 0.111280E+09 | 0.39 | 676.90 | 01-OCT-08:62 | 0.58 |
November | 0.166407E+09 | 0.42 | 676.90 | 02-NOV-08:62 | 0.59 |
December | 0.301757E+09 | 0.52 | 676.90 | 01-DEC-16:01 | 0.59 |
Annual Sum or Average | 0.283611E+10 | 0.44 | |||
Minimum of Months | 0.111280E+09 | 0.39 | 676.90 | 0.58 | |
Maximum of Months | 0.383843E+09 | 0.52 | 676.90 | 0.59 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 93933941.95 | 0.53 | 201.98 | 01-JAN-09:01 | 0.59 |
February | 82193194.32 | 0.52 | 201.98 | 01-FEB-09:01 | 0.59 |
March | 57144643.84 | 0.44 | 201.98 | 01-MAR-09:01 | 0.59 |
April | 51782278.95 | 0.46 | 201.98 | 02-APR-15:02 | 0.59 |
May | 68056407.85 | 0.50 | 201.98 | 01-MAY-15:02 | 0.59 |
June | 0.109649E+09 | 0.54 | 201.98 | 01-JUN-08:62 | 0.58 |
July | 0.129056E+09 | 0.55 | 201.98 | 01-JUL-08:62 | 0.58 |
August | 0.116520E+09 | 0.55 | 201.98 | 01-AUG-08:62 | 0.59 |
September | 72862891.51 | 0.52 | 201.98 | 01-SEP-15:01 | 0.59 |
October | 43867210.40 | 0.45 | 201.98 | 01-OCT-15:02 | 0.58 |
November | 52207594.25 | 0.44 | 201.98 | 02-NOV-08:62 | 0.59 |
December | 92341592.50 | 0.53 | 201.98 | 01-DEC-09:02 | 0.59 |
Annual Sum or Average | 0.969615E+09 | 0.50 | |||
Minimum of Months | 43867210.40 | 0.44 | 201.98 | 0.58 | |
Maximum of Months | 0.129056E+09 | 0.55 | 201.98 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.100754E+09 | 0.56 | 194.45 | 01-JAN-09:01 | 0.59 |
February | 87690498.75 | 0.55 | 194.45 | 01-FEB-09:01 | 0.59 |
March | 59285752.69 | 0.46 | 194.45 | 01-MAR-09:01 | 0.59 |
April | 43869425.02 | 0.42 | 194.45 | 01-APR-08:62 | 0.59 |
May | 44097545.24 | 0.40 | 194.45 | 01-MAY-15:02 | 0.59 |
June | 79212200.47 | 0.40 | 194.45 | 01-JUN-08:51 | 0.58 |
July | 0.103508E+09 | 0.42 | 194.45 | 01-JUL-08:51 | 0.58 |
August | 84884666.03 | 0.40 | 194.45 | 01-AUG-08:51 | 0.58 |
September | 36924112.54 | 0.37 | 194.45 | 01-SEP-15:01 | 0.59 |
October | 36412924.45 | 0.39 | 194.45 | 01-OCT-15:02 | 0.58 |
November | 56543692.25 | 0.45 | 194.45 | 01-NOV-08:62 | 0.59 |
December | 97001313.22 | 0.55 | 194.45 | 01-DEC-09:02 | 0.59 |
Annual Sum or Average | 0.830184E+09 | 0.45 | |||
Minimum of Months | 36412924.45 | 0.37 | 194.45 | 0.58 | |
Maximum of Months | 0.103508E+09 | 0.56 | 194.45 | 0.59 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.333554E+09 | 0.46 | 935.74 | 01-JAN-09:01 | 0.59 |
February | 0.298745E+09 | 0.45 | 935.74 | 01-FEB-09:01 | 0.59 |
March | 0.267651E+09 | 0.47 | 935.74 | 01-MAR-16:02 | 0.59 |
April | 0.255795E+09 | 0.48 | 935.74 | 01-APR-15:02 | 0.59 |
May | 0.309863E+09 | 0.51 | 935.74 | 01-MAY-15:02 | 0.59 |
June | 0.444054E+09 | 0.54 | 935.74 | 01-JUN-08:62 | 0.59 |
July | 0.594027E+09 | 0.55 | 935.74 | 01-JUL-08:62 | 0.58 |
August | 0.589750E+09 | 0.55 | 935.74 | 01-AUG-08:62 | 0.59 |
September | 0.480909E+09 | 0.53 | 935.74 | 01-SEP-08:62 | 0.58 |
October | 0.302930E+09 | 0.48 | 935.74 | 01-OCT-08:62 | 0.58 |
November | 0.228661E+09 | 0.46 | 935.74 | 01-NOV-15:02 | 0.59 |
December | 0.343674E+09 | 0.47 | 935.74 | 01-DEC-16:01 | 0.59 |
Annual Sum or Average | 0.444961E+10 | 0.50 | |||
Minimum of Months | 0.228661E+09 | 0.45 | 935.74 | 0.58 | |
Maximum of Months | 0.594027E+09 | 0.55 | 935.74 | 0.59 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.109113E+10 | 0.991837E+09 | 819.34 | 31-JAN-16:01 | 744.78 | 744.78 | 37.43 | 1.30 |
February | 0.100135E+10 | 0.910228E+09 | 909.76 | 06-FEB-09:02 | 826.97 | 826.97 | 41.27 | 1.60 |
March | 0.606969E+09 | 0.551735E+09 | 700.32 | 06-MAR-19:01 | 636.59 | 636.59 | 31.93 | 1.00 |
April | 0.326259E+09 | 0.296569E+09 | 577.36 | 26-APR-08:05 | 524.82 | 524.82 | 51.99 | 0.76 |
May | 0.240134E+09 | 0.218282E+09 | 484.84 | 11-MAY-15:08 | 440.72 | 440.72 | 34.14 | 0.61 |
June | 73928122.84 | 67200663.66 | 484.38 | 13-JUN-08:05 | 440.30 | 440.30 | 32.02 | 0.61 |
July | 12170257.99 | 11062764.52 | 191.26 | 13-JUL-05:00 | 173.86 | 173.86 | 27.02 | 0.21 |
August | 26210145.56 | 23825022.32 | 239.92 | 01-AUG-06:00 | 218.09 | 218.09 | 28.12 | 0.27 |
September | 0.139131E+09 | 0.126470E+09 | 513.11 | 30-SEP-06:05 | 466.41 | 466.41 | 57.20 | 0.65 |
October | 0.392468E+09 | 0.356754E+09 | 612.68 | 19-OCT-08:62 | 556.93 | 556.93 | 33.03 | 0.83 |
November | 0.479200E+09 | 0.435593E+09 | 637.43 | 13-NOV-09:02 | 579.42 | 579.42 | 37.59 | 0.87 |
December | 0.100192E+10 | 0.910747E+09 | 855.06 | 11-DEC-09:03 | 777.25 | 777.25 | 37.43 | 1.41 |
Annual Sum or Average | 0.539087E+10 | 0.490030E+10 | ||||||
Minimum of Months | 12170257.99 | 11062764.52 | 191.26 | 173.86 | 173.86 | 27.02 | 0.21 | |
Maximum of Months | 0.109113E+10 | 0.991837E+09 | 909.76 | 826.97 | 826.97 | 57.20 | 1.60 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 260960.60 | 237213.18 | 33.85 | 12-JAN-09:04 | 30.77 | 30.77 | 8.40 | 2.76 |
February | 292663.86 | 266031.45 | 35.99 | 18-FEB-16:03 | 32.72 | 32.72 | 8.40 | 2.86 |
March | 29135203.52 | 26483900.00 | 554.52 | 15-MAR-15:03 | 504.06 | 504.06 | 6.91 | 11.37 |
April | 38000473.89 | 34542430.76 | 460.99 | 08-APR-15:03 | 419.04 | 419.04 | 7.86 | 10.46 |
May | 0.147726E+09 | 0.134283E+09 | 655.67 | 31-MAY-15:03 | 596.01 | 596.01 | 7.47 | 12.26 |
June | 0.564613E+09 | 0.513233E+09 | 1696.49 | 17-JUN-19:00 | 1542.11 | 1542.11 | 7.22 | 18.49 |
July | 0.111024E+10 | 0.100921E+10 | 2257.34 | 21-JUL-20:00 | 2051.92 | 2051.92 | 7.23 | 20.83 |
August | 0.828393E+09 | 0.753009E+09 | 1470.67 | 14-AUG-18:03 | 1336.84 | 1336.84 | 6.84 | 17.41 |
September | 0.366088E+09 | 0.332774E+09 | 1213.07 | 15-SEP-20:00 | 1102.68 | 1102.68 | 7.41 | 16.04 |
October | 64104738.70 | 58271207.48 | 662.71 | 11-OCT-15:03 | 602.40 | 602.40 | 7.42 | 12.32 |
November | 11128000.65 | 10115352.59 | 203.53 | 04-NOV-15:01 | 185.01 | 185.01 | 7.99 | 7.12 |
December | 324799.43 | 295242.68 | 31.81 | 17-DEC-09:01 | 28.92 | 28.92 | 8.40 | 2.66 |
Annual Sum or Average | 0.316031E+10 | 0.287272E+10 | ||||||
Minimum of Months | 260960.60 | 237213.18 | 31.81 | 28.92 | 28.92 | 6.84 | 2.66 | |
Maximum of Months | 0.111024E+10 | 0.100921E+10 | 2257.34 | 2051.92 | 2051.92 | 8.40 | 20.83 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.752710E+09 | 0.684213E+09 | 4521.94 | 01-JAN-09:01 | 4110.45 | 4110.45 | 8.58 | 32.01 |
February | 0.701127E+09 | 0.637325E+09 | 4521.94 | 01-FEB-09:03 | 4110.45 | 4110.45 | 8.44 | 32.01 |
March | 0.530666E+10 | 0.482375E+10 | 4521.94 | 01-MAR-08:00 | 4110.45 | 4110.45 | 8.40 | 32.01 |
April | 0.826382E+10 | 0.751181E+10 | 4521.94 | 01-APR-07:00 | 4110.45 | 4110.45 | 8.40 | 32.01 |
May | 0.119514E+11 | 0.108638E+11 | 4521.94 | 01-MAY-00:05 | 4110.45 | 4110.45 | 8.45 | 32.01 |
June | 0.117209E+11 | 0.106543E+11 | 4521.94 | 01-JUN-00:05 | 4110.45 | 4110.45 | 8.81 | 32.01 |
July | 0.121116E+11 | 0.110094E+11 | 4521.94 | 01-JUL-00:10 | 4110.45 | 4110.45 | 8.86 | 32.01 |
August | 0.121116E+11 | 0.110094E+11 | 4521.94 | 01-AUG-00:05 | 4110.45 | 4110.45 | 9.21 | 32.01 |
September | 0.116273E+11 | 0.105692E+11 | 4521.94 | 01-SEP-00:05 | 4110.45 | 4110.45 | 8.55 | 32.01 |
October | 0.944766E+10 | 0.858793E+10 | 4521.94 | 01-OCT-00:10 | 4110.45 | 4110.45 | 8.48 | 32.01 |
November | 0.479745E+10 | 0.436088E+10 | 4521.94 | 01-NOV-00:05 | 4110.45 | 4110.45 | 8.42 | 32.01 |
December | 0.839886E+09 | 0.763457E+09 | 4521.94 | 01-DEC-06:30 | 4110.45 | 4110.45 | 8.40 | 32.01 |
Annual Sum or Average | 0.896320E+11 | 0.814755E+11 | ||||||
Minimum of Months | 0.701127E+09 | 0.637325E+09 | 4521.94 | 4110.45 | 4110.45 | 8.40 | 32.01 | |
Maximum of Months | 0.121116E+11 | 0.110094E+11 | 4521.94 | 4110.45 | 4110.45 | 9.21 | 32.01 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 47.38 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 47.83 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 47.82 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 51.03 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 50.92 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 52.04 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 52.48 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 52.70 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 52.62 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 51.56 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 51.28 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 48.80 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 47.38 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 52.70 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 53.17 | 81.25 | 74004.67 | 245028.14 | 31-JAN-16:03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 51.09 | 81.64 | 77653.74 | 281202.49 | 06-FEB-09:03 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 49.23 | 81.91 | 37479.20 | 211126.24 | 06-MAR-19:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 65.84 | 80.39 | 21073.46 | 139169.16 | 25-APR-15:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 51.17 | 79.96 | 20362.39 | 118121.91 | 18-MAY-08:04 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.30 | 28.30 | 6792.09 | 120739.62 | 13-JUN-08:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.10 | 32.10 | 1094.15 | 46659.94 | 13-JUL-04:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 40.03 | 40.03 | 2343.52 | 57701.00 | 01-AUG-06:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.30 | 79.40 | 12484.66 | 108067.91 | 30-SEP-06:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 29.07 | 79.40 | 27291.46 | 161591.63 | 19-OCT-08:62 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 59.17 | 79.98 | 26369.03 | 184018.07 | 24-NOV-09:01 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 61.18 | 80.25 | 65937.46 | 263474.56 | 11-DEC-09:03 |
Annual Sum or Average | 0.00 | 30848.71 | ||||||
Minimum of Months | 0.00 | 0.00 | 23.30 | 28.30 | 1094.15 | 46659.94 | ||
Maximum of Months | 0.00 | 0.00 | 65.84 | 81.91 | 77653.74 | 281202.49 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 418.27 | 29638.47 | 15-JAN-09:01 | 8.59 | 8.37 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 460.89 | 41301.64 | 28-FEB-16:05 | 8.68 | 8.37 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 12167.50 | 334477.95 | 15-MAR-15:03 | 9.37 | 6.88 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 16963.36 | 217146.35 | 08-APR-15:03 | 9.46 | 7.84 | 0.00 | 0.00 | 01-APR-00:10 |
May | 55484.48 | 361557.02 | 10-MAY-15:03 | 9.53 | 6.83 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 162879.24 | 587884.53 | 27-JUN-20:10 | 11.55 | 7.16 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 268185.39 | 629198.02 | 21-JUL-20:00 | 11.90 | 7.21 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 207134.04 | 547315.45 | 14-AUG-18:03 | 10.90 | 6.82 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 115517.22 | 526646.55 | 15-SEP-21:53 | 11.47 | 7.54 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 25327.24 | 313099.72 | 11-OCT-15:03 | 9.72 | 7.39 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 7483.39 | 173351.32 | 04-NOV-15:01 | 9.26 | 7.96 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 482.16 | 32860.96 | 01-DEC-19:02 | 8.61 | 8.37 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 73269.51 | 0.00 | ||||||
Minimum of Months | 418.27 | 29638.47 | 8.59 | 6.82 | 0.00 | 0.00 | ||
Maximum of Months | 268185.39 | 629198.02 | 11.90 | 8.37 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 47.38 | 59.68 | 29745.91 | 61103.44 | 31-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 47.83 | 58.91 | 30160.36 | 61321.07 | 14-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 47.82 | 58.88 | 29790.00 | 61134.73 | 01-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 51.03 | 58.78 | 28657.45 | 59243.43 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 50.92 | 58.32 | 27108.19 | 56536.57 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 52.04 | 59.71 | 25547.47 | 53072.43 | 01-JUN-06:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 52.48 | 59.22 | 24364.01 | 49948.14 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 52.70 | 59.70 | 23943.19 | 48358.78 | 31-AUG-06:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 52.62 | 59.08 | 24337.11 | 49915.90 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 51.56 | 58.84 | 25464.47 | 52964.24 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 51.28 | 58.17 | 27021.96 | 56320.13 | 30-NOV-07:10 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 48.80 | 59.36 | 28583.86 | 59185.53 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 27042.19 | ||||||
Minimum of Months | 0.00 | 0.00 | 47.38 | 58.17 | 23943.19 | 48358.78 | ||
Maximum of Months | 0.00 | 0.00 | 52.70 | 59.71 | 30160.36 | 61321.07 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.128186E+12 | 0.00 | 0.00 | 0.332765E+11 | 0.00 | 0.00 |
February | 0.125030E+12 | 0.00 | 0.00 | 0.300809E+11 | 0.00 | 0.00 |
March | 0.710729E+11 | 0.00 | 0.143017E+11 | 0.346699E+11 | 0.00 | 0.00 |
April | 0.468582E+11 | 0.00 | 0.824425E+10 | 0.343583E+11 | 0.00 | 0.00 |
May | 0.541858E+11 | 0.00 | 0.675017E+11 | 0.369396E+11 | 0.00 | 0.00 |
June | 0.176826E+11 | 0.00 | 0.275839E+12 | 0.376059E+11 | 0.00 | 0.00 |
July | 0.292993E+10 | 0.00 | 0.513129E+12 | 0.400735E+11 | 0.00 | 0.00 |
August | 0.631782E+10 | 0.00 | 0.375044E+12 | 0.399292E+11 | 0.00 | 0.00 |
September | 0.322761E+11 | 0.00 | 0.181601E+12 | 0.370435E+11 | 0.00 | 0.00 |
October | 0.659599E+11 | 0.00 | 0.223274E+11 | 0.364379E+11 | 0.00 | 0.00 |
November | 0.470709E+11 | 0.00 | 0.709649E+10 | 0.340714E+11 | 0.00 | 0.00 |
December | 0.111523E+12 | 0.00 | 5785851.23 | 0.334715E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.709093E+12 | 0.00 | 0.146509E+13 | 0.427958E+12 | 0.00 | 0.00 |
Minimum of Months | 0.292993E+10 | 0.00 | 0.00 | 0.300809E+11 | 0.00 | 0.00 |
Maximum of Months | 0.128186E+12 | 0.00 | 0.513129E+12 | 0.400735E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.394734E+10 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
February | 0.417264E+10 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
March | 0.160914E+10 | 0.00 | 0.106379E+10 | 0.271000E+10 | 0.00 | 0.00 |
April | 80161231.19 | 0.00 | 0.441673E+09 | 0.262258E+10 | 0.00 | 0.00 |
May | 5475.31 | 0.00 | 0.486239E+10 | 0.271000E+10 | 0.00 | 0.00 |
June | 8843.04 | 0.00 | 0.222930E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 10073.91 | 0.00 | 0.404864E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 9794.25 | 0.00 | 0.296902E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 10244.08 | 0.00 | 0.147656E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 15789393.00 | 0.00 | 0.151434E+10 | 0.271000E+10 | 0.00 | 0.00 |
November | 63273508.13 | 0.00 | 0.566793E+09 | 0.262258E+10 | 0.00 | 0.00 |
December | 0.327380E+10 | 0.00 | 850142.93 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.131622E+11 | 0.00 | 0.115685E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 5475.31 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.417264E+10 | 0.00 | 0.404864E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.332765E+11 | 0.00 | 0.128186E+12 | 0.736107E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.300809E+11 | 0.00 | 0.125030E+12 | 0.684655E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.346699E+11 | 0.143017E+11 | 0.710729E+11 | 0.522577E+12 | 92002047.01 | 0.00 | 0.00 | 0.00 |
April | 0.343583E+11 | 0.824425E+10 | 0.468582E+11 | 0.304265E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.369396E+11 | 0.675017E+11 | 0.541858E+11 | 0.497129E+11 | 0.214811E+09 | 0.00 | 0.00 | 0.00 |
June | 0.376059E+11 | 0.275839E+12 | 0.176826E+11 | 0.127663E+11 | 0.225143E+11 | 0.00 | 0.00 | 0.00 |
July | 0.400735E+11 | 0.513129E+12 | 0.292993E+10 | 0.115703E+10 | 0.704241E+11 | 0.00 | 0.00 | 0.00 |
August | 0.399292E+11 | 0.375044E+12 | 0.631782E+10 | 0.369130E+10 | 0.336028E+11 | 0.00 | 0.00 | 0.00 |
September | 0.370435E+11 | 0.181601E+12 | 0.322761E+11 | 0.131660E+11 | 0.442886E+10 | 0.00 | 0.00 | 0.00 |
October | 0.364379E+11 | 0.223274E+11 | 0.659599E+11 | 0.194362E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.340714E+11 | 0.709649E+10 | 0.470709E+11 | 0.382352E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.334715E+11 | 5785851.23 | 0.111523E+12 | 0.702795E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.427958E+12 | 0.146509E+13 | 0.709093E+12 | 0.360761E+13 | 0.131277E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.300809E+11 | 0.00 | 0.292993E+10 | 0.115703E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.400735E+11 | 0.513129E+12 | 0.128186E+12 | 0.736107E+12 | 0.704241E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.00 | 0.394734E+10 | 0.671875E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.00 | 0.417264E+10 | 0.623303E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.106379E+10 | 0.160914E+10 | 0.489643E+11 | 35933466.39 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.441673E+09 | 80161231.19 | 0.320722E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.486239E+10 | 5475.31 | 0.113485E+11 | 85003606.67 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.222930E+11 | 8843.04 | 0.320191E+10 | 0.314603E+10 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.404864E+11 | 10073.91 | 0.320675E+09 | 0.101479E+11 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.296902E+11 | 9794.25 | 0.798251E+09 | 0.507646E+10 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.147656E+11 | 10244.08 | 0.507684E+10 | 0.979459E+09 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.151434E+10 | 15789393.00 | 0.244709E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.566793E+09 | 63273508.13 | 0.373304E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 850142.93 | 0.327380E+10 | 0.634027E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.115685E+12 | 0.131622E+11 | 0.356504E+12 | 0.194707E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.00 | 5475.31 | 0.320675E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.404864E+11 | 0.417264E+10 | 0.671875E+11 | 0.101479E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.332765E+11 | 0.128186E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.300809E+11 | 0.125030E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.346699E+11 | 0.710729E+11 | 0.143017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.343583E+11 | 0.468582E+11 | 0.824425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.369396E+11 | 0.541858E+11 | 0.675017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.376059E+11 | 0.176826E+11 | 0.275839E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.400735E+11 | 0.292993E+10 | 0.513129E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.399292E+11 | 0.631782E+10 | 0.375044E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.370435E+11 | 0.322761E+11 | 0.181601E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.364379E+11 | 0.659599E+11 | 0.223274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.340714E+11 | 0.470709E+11 | 0.709649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.334715E+11 | 0.111523E+12 | 5785851.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.427958E+12 | 0.709093E+12 | 0.146509E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.300809E+11 | 0.292993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.400735E+11 | 0.128186E+12 | 0.513129E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.394734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.417264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.160914E+10 | 0.106379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 80161231.19 | 0.441673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 5475.31 | 0.486239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 8843.04 | 0.222930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 10073.91 | 0.404864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 9794.25 | 0.296902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 10244.08 | 0.147656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 15789393.00 | 0.151434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 63273508.13 | 0.566793E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.327380E+10 | 850142.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.131622E+11 | 0.115685E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 5475.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.417264E+10 | 0.404864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.450146E+11 | 0.00 | 0.00 | 529283.10 | 0.00 | 0.00 | 0.355911E+10 | 0.00 | 0.90 |
February | 0.446252E+11 | 0.00 | 0.00 | 2597.84 | 0.00 | 0.00 | 50470877.27 | 0.00 | 0.90 |
March | 0.449645E+11 | 0.00 | 0.00 | 0.00 | 3504716.00 | 0.00 | 0.00 | 0.00 | 0.89 |
April | 0.434864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.90 |
May | 0.419605E+11 | 0.00 | 0.00 | 0.00 | 2855375.66 | 0.00 | 0.00 | 0.00 | 0.90 |
June | 0.238459E+11 | 0.00 | 0.00 | 0.00 | 0.280209E+10 | 0.00 | 0.00 | 0.00 | 0.90 |
July | 0.108486E+11 | 27366451.58 | 0.00 | 0.00 | 0.911263E+10 | 0.00 | 0.00 | 0.00 | 0.91 |
August | 0.116489E+11 | 0.957661E+09 | 0.00 | 6176025.72 | 0.308486E+10 | 0.00 | 0.644771E+10 | 0.00 | 0.91 |
September | 0.683054E+10 | 0.704514E+09 | 0.00 | 29961148.42 | 0.823716E+09 | 0.00 | 0.261612E+11 | 0.00 | 0.93 |
October | 0.356901E+10 | 0.00 | 0.00 | 49405860.32 | 0.00 | 0.00 | 0.463471E+11 | 0.00 | 0.96 |
November | 0.717133E+10 | 0.00 | 0.00 | 40788469.50 | 0.00 | 0.00 | 0.379775E+11 | 0.00 | 0.95 |
December | 0.218791E+11 | 0.00 | 0.00 | 15765601.31 | 0.00 | 0.00 | 0.261648E+11 | 0.00 | 0.91 |
Annual Sum or Average | 0.305845E+12 | 0.168954E+10 | 0.00 | 0.142629E+09 | 0.158297E+11 | 0.00 | 0.146708E+12 | 0.00 | 0.91 |
Minimum of Months | 0.356901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.89 |
Maximum of Months | 0.450146E+11 | 0.957661E+09 | 0.00 | 49405860.32 | 0.911263E+10 | 0.00 | 0.463471E+11 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.296042E+10 | 0.00 | 0.00 | 32445.37 | 0.00 | 0.523296E+10 | 64330554.79 | 0.00 | 2.75 |
February | 0.294408E+10 | 0.00 | 0.00 | 45990.75 | 0.00 | 0.457507E+10 | 75790057.27 | 0.00 | 2.75 |
March | 0.625098E+10 | 195646.05 | 0.00 | 320270.04 | 400795.88 | 0.106562E+10 | 0.330547E+09 | 0.00 | 2.75 |
April | 0.690145E+10 | 0.00 | 0.00 | 270607.53 | 0.00 | 0.165621E+09 | 0.327506E+09 | 0.00 | 2.77 |
May | 0.686084E+10 | 436152.96 | 0.00 | 224443.73 | 49268.33 | 0.00 | 0.272325E+09 | 0.00 | 2.77 |
June | 0.386248E+10 | 0.187562E+09 | 0.00 | 262013.89 | 0.291507E+09 | 0.00 | 0.191179E+09 | 0.00 | 2.78 |
July | 0.173279E+10 | 0.828251E+09 | 0.00 | 365581.00 | 0.749923E+09 | 0.00 | 0.111177E+09 | 0.00 | 2.82 |
August | 0.269835E+10 | 0.373041E+09 | 0.00 | 1450887.73 | 0.334539E+09 | 0.00 | 0.381824E+09 | 0.00 | 2.85 |
September | 0.484635E+10 | 64414459.24 | 0.00 | 1930699.06 | 0.189880E+09 | 0.00 | 0.665766E+09 | 0.00 | 2.85 |
October | 0.741657E+10 | 0.00 | 0.00 | 1022769.25 | 0.00 | 25733101.32 | 0.562306E+09 | 0.00 | 2.81 |
November | 0.647541E+10 | 0.00 | 0.00 | 150333.94 | 0.00 | 0.584113E+09 | 0.229498E+09 | 0.00 | 2.77 |
December | 0.268214E+10 | 0.00 | 0.00 | 48227.89 | 0.00 | 0.531622E+10 | 65130026.54 | 0.00 | 2.76 |
Annual Sum or Average | 0.556319E+11 | 0.145390E+10 | 0.00 | 6124270.21 | 0.156630E+10 | 0.169653E+11 | 0.327738E+10 | 0.00 | 2.79 |
Minimum of Months | 0.173279E+10 | 0.00 | 0.00 | 32445.37 | 0.00 | 0.00 | 64330554.79 | 0.00 | 2.75 |
Maximum of Months | 0.741657E+10 | 0.828251E+09 | 0.00 | 1930699.06 | 0.749923E+09 | 0.531622E+10 | 0.665766E+09 | 0.00 | 2.85 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.490244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 |
February | 0.450897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 |
March | 0.445009E+10 | 0.00 | 0.00 | 51261.79 | 353719.33 | 0.00 | 88050378.85 | 0.00 | 1.41 |
April | 0.416855E+10 | 0.00 | 0.00 | 56456.37 | 0.00 | 0.00 | 0.220326E+09 | 0.00 | 1.43 |
May | 0.350719E+10 | 0.00 | 0.00 | 399564.93 | 288183.57 | 0.00 | 0.728095E+09 | 0.00 | 1.43 |
June | 0.122260E+10 | 0.111071E+09 | 0.00 | 1702236.07 | 0.179556E+09 | 0.00 | 0.120400E+10 | 0.00 | 1.45 |
July | 0.219529E+09 | 0.558039E+09 | 0.00 | 1794145.66 | 0.405356E+09 | 0.00 | 0.896550E+09 | 0.00 | 1.49 |
August | 0.474922E+09 | 0.214207E+09 | 0.00 | 2511186.17 | 0.207345E+09 | 0.00 | 0.140041E+10 | 0.00 | 1.48 |
September | 0.194049E+10 | 52865246.64 | 0.00 | 1242649.60 | 97885562.12 | 0.00 | 0.132365E+10 | 0.00 | 1.44 |
October | 0.426395E+10 | 0.00 | 0.00 | 215539.89 | 0.00 | 0.00 | 0.446242E+09 | 0.00 | 1.42 |
November | 0.429621E+10 | 0.00 | 0.00 | 3972.48 | 0.00 | 0.00 | 28704309.17 | 0.00 | 1.42 |
December | 0.478714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 |
Annual Sum or Average | 0.387421E+11 | 0.936182E+09 | 0.00 | 7977012.95 | 0.890784E+09 | 0.00 | 0.633603E+10 | 0.00 | 1.44 |
Minimum of Months | 0.219529E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 |
Maximum of Months | 0.490244E+10 | 0.558039E+09 | 0.00 | 2511186.17 | 0.405356E+09 | 0.00 | 0.140041E+10 | 0.00 | 1.49 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.234585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162889E+10 | 0.00 | 0.00 | 0.54 |
February | 0.201419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164154E+10 | 0.00 | 0.00 | 0.54 |
March | 0.333359E+10 | 0.00 | 0.00 | 0.00 | 286784.01 | 0.345769E+09 | 0.00 | 0.00 | 0.54 |
April | 0.355840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
May | 0.343354E+10 | 0.00 | 0.00 | 0.00 | 233649.77 | 0.00 | 0.00 | 0.00 | 0.55 |
June | 0.191676E+10 | 24856210.51 | 0.00 | 70475.32 | 0.205145E+09 | 0.00 | 34452511.16 | 0.00 | 0.55 |
July | 0.801621E+09 | 0.292468E+09 | 0.00 | 194409.24 | 0.476608E+09 | 0.00 | 86285519.51 | 0.00 | 0.56 |
August | 0.127394E+10 | 72991014.60 | 0.00 | 401414.55 | 0.259782E+09 | 0.00 | 0.208861E+09 | 0.00 | 0.55 |
September | 0.261152E+10 | 8949884.23 | 0.00 | 3678.25 | 0.111796E+09 | 0.00 | 13314119.67 | 0.00 | 0.55 |
October | 0.381733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
November | 0.350650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
December | 0.254825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133301E+10 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.311615E+11 | 0.399265E+09 | 0.00 | 669977.36 | 0.105385E+10 | 0.494920E+10 | 0.342913E+09 | 0.00 | 0.55 |
Minimum of Months | 0.801621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.381733E+10 | 0.292468E+09 | 0.00 | 401414.55 | 0.476608E+09 | 0.164154E+10 | 0.208861E+09 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.510259E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162729E+10 | 0.00 | 0.00 | 0.50 |
February | 0.404403E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156159E+10 | 0.00 | 0.00 | 0.50 |
March | 0.149119E+10 | 0.00 | 0.00 | 0.00 | 154227.98 | 0.487509E+09 | 0.00 | 0.00 | 0.50 |
April | 0.190724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6411295.85 | 0.00 | 0.00 | 0.51 |
May | 0.184651E+10 | 0.00 | 0.00 | 0.00 | 125653.21 | 0.00 | 0.00 | 0.00 | 0.51 |
June | 0.104936E+10 | 0.00 | 0.00 | 0.00 | 0.123308E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
July | 0.477184E+09 | 78831802.80 | 0.00 | 477.52 | 0.324924E+09 | 0.00 | 218972.80 | 0.00 | 0.51 |
August | 0.785162E+09 | 9805872.11 | 0.00 | 7952.70 | 0.168009E+09 | 0.00 | 10155514.18 | 0.00 | 0.51 |
September | 0.141160E+10 | 0.00 | 0.00 | 0.00 | 64935266.34 | 0.00 | 0.00 | 0.00 | 0.51 |
October | 0.205290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
November | 0.185485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30895212.39 | 0.00 | 0.00 | 0.51 |
December | 0.753327E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133395E+10 | 0.00 | 0.00 | 0.51 |
Annual Sum or Average | 0.145440E+11 | 88637674.91 | 0.00 | 8430.22 | 0.681456E+09 | 0.504765E+10 | 10374486.98 | 0.00 | 0.51 |
Minimum of Months | 0.404403E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.205290E+10 | 78831802.80 | 0.00 | 7952.70 | 0.324924E+09 | 0.162729E+10 | 10155514.18 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.856023E+09 | 0.00 | 0.00 | 91361577.85 | 0.00 | 0.00 | 0.837349E+11 | 0.00 | 24.21 |
February | 0.802224E+09 | 0.00 | 0.00 | 81751162.96 | 0.00 | 0.00 | 0.769480E+11 | 0.00 | 24.24 |
March | 0.360694E+09 | 5375721.10 | 0.00 | 91869705.64 | 0.00 | 0.00 | 0.783484E+11 | 0.00 | 24.30 |
April | 0.220318E+09 | 0.00 | 0.00 | 91080209.21 | 0.00 | 0.00 | 0.758859E+11 | 0.00 | 24.50 |
May | 0.279266E+09 | 4379728.12 | 0.00 | 0.107217E+09 | 0.00 | 0.00 | 0.735103E+11 | 0.00 | 24.52 |
June | 0.142145E+09 | 0.493913E+10 | 0.00 | 94020845.44 | 18485764.41 | 0.00 | 0.408731E+11 | 0.00 | 24.54 |
July | 34215417.56 | 0.160895E+11 | 0.00 | 61980367.34 | 39716425.41 | 0.00 | 0.181034E+11 | 0.00 | 24.53 |
August | 86266047.29 | 0.716572E+10 | 0.00 | 88861265.58 | 32857081.44 | 0.00 | 0.308807E+11 | 0.00 | 24.57 |
September | 0.234522E+09 | 0.266485E+10 | 0.00 | 94065502.01 | 2839052.87 | 0.00 | 0.555572E+11 | 0.00 | 24.53 |
October | 0.246562E+09 | 0.00 | 0.00 | 93869292.25 | 0.00 | 0.00 | 0.813231E+11 | 0.00 | 24.46 |
November | 0.353933E+09 | 0.00 | 0.00 | 88562865.30 | 0.00 | 0.00 | 0.745346E+11 | 0.00 | 24.50 |
December | 0.818243E+09 | 0.00 | 0.00 | 90510812.13 | 0.00 | 0.00 | 0.816691E+11 | 0.00 | 24.32 |
Annual Sum or Average | 0.443441E+10 | 0.308690E+11 | 0.00 | 0.107515E+10 | 93898324.12 | 0.00 | 0.771369E+12 | 0.00 | 24.44 |
Minimum of Months | 34215417.56 | 0.00 | 0.00 | 61980367.34 | 0.00 | 0.00 | 0.181034E+11 | 0.00 | 24.21 |
Maximum of Months | 0.856023E+09 | 0.160895E+11 | 0.00 | 0.107217E+09 | 39716425.41 | 0.00 | 0.837349E+11 | 0.00 | 24.57 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.333180E+11 | 0.00 | 0.00 | 451593.01 | 0.00 | 0.00 | 0.176324E+10 | 0.00 | 4.16 |
February | 0.302798E+11 | 0.00 | 0.00 | 619175.80 | 0.00 | 0.309167E+09 | 0.167625E+10 | 0.00 | 4.16 |
March | 0.219606E+11 | 1914059.19 | 0.00 | 5690941.43 | 618333.87 | 0.00 | 0.105323E+11 | 0.00 | 4.16 |
April | 0.165853E+11 | 0.00 | 0.00 | 6946986.40 | 0.00 | 0.00 | 0.148282E+11 | 0.00 | 4.21 |
May | 0.113443E+11 | 2062221.84 | 0.00 | 11380472.10 | 0.00 | 0.00 | 0.189526E+11 | 0.00 | 4.21 |
June | 0.458142E+10 | 0.158444E+10 | 0.00 | 16816136.88 | 0.450483E+09 | 0.00 | 0.126561E+11 | 0.00 | 4.23 |
July | 0.117034E+10 | 0.552374E+10 | 0.00 | 14646039.10 | 0.121981E+10 | 0.00 | 0.669979E+10 | 0.00 | 4.30 |
August | 0.251253E+10 | 0.251343E+10 | 0.00 | 23737423.39 | 0.479771E+09 | 0.00 | 0.106716E+11 | 0.00 | 4.31 |
September | 0.564613E+10 | 0.775474E+09 | 0.00 | 22823479.14 | 0.302499E+09 | 0.00 | 0.177613E+11 | 0.00 | 4.30 |
October | 0.165819E+11 | 0.00 | 0.00 | 12979998.25 | 0.00 | 0.00 | 0.173845E+11 | 0.00 | 4.24 |
November | 0.204465E+11 | 0.00 | 0.00 | 3945267.66 | 0.00 | 0.00 | 0.105238E+11 | 0.00 | 4.19 |
December | 0.321592E+11 | 0.00 | 0.00 | 679968.32 | 0.00 | 63055985.78 | 0.203838E+10 | 0.00 | 4.18 |
Annual Sum or Average | 0.196586E+12 | 0.104011E+11 | 0.00 | 0.120717E+09 | 0.245318E+10 | 0.372223E+09 | 0.125488E+12 | 0.00 | 4.22 |
Minimum of Months | 0.117034E+10 | 0.00 | 0.00 | 451593.01 | 0.00 | 0.00 | 0.167625E+10 | 0.00 | 4.16 |
Maximum of Months | 0.333180E+11 | 0.552374E+10 | 0.00 | 23737423.39 | 0.121981E+10 | 0.309167E+09 | 0.189526E+11 | 0.00 | 4.31 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105967E+12 | 0.00 | 0.00 | 143808.07 | 0.00 | 0.00 | 0.133240E+10 | 0.00 | 1.84 |
February | 0.970939E+11 | 0.00 | 0.00 | 254559.50 | 0.00 | 0.00 | 0.159318E+10 | 0.00 | 1.84 |
March | 0.789737E+11 | 0.00 | 0.00 | 10044520.54 | 7741823.47 | 0.00 | 0.204444E+11 | 0.00 | 1.84 |
April | 0.617891E+11 | 0.00 | 0.00 | 16899098.95 | 0.00 | 0.00 | 0.343074E+11 | 0.00 | 1.86 |
May | 0.398266E+11 | 0.00 | 0.00 | 42039063.37 | 6307448.12 | 0.00 | 0.533282E+11 | 0.00 | 1.87 |
June | 0.144999E+11 | 0.365808E+10 | 0.00 | 70795890.97 | 0.273306E+10 | 0.00 | 0.397609E+11 | 0.00 | 1.93 |
July | 0.287611E+10 | 0.158609E+11 | 0.00 | 59236521.67 | 0.559678E+10 | 0.00 | 0.224565E+11 | 0.00 | 1.99 |
August | 0.609497E+10 | 0.687183E+10 | 0.00 | 81727184.73 | 0.255338E+10 | 0.00 | 0.365204E+11 | 0.00 | 1.98 |
September | 0.182058E+11 | 0.201496E+10 | 0.00 | 67094618.33 | 0.137003E+10 | 0.00 | 0.546893E+11 | 0.00 | 1.92 |
October | 0.558591E+11 | 0.00 | 0.00 | 31808038.57 | 0.00 | 0.00 | 0.476999E+11 | 0.00 | 1.86 |
November | 0.700977E+11 | 0.00 | 0.00 | 9654072.10 | 0.00 | 0.00 | 0.245617E+11 | 0.00 | 1.86 |
December | 0.102926E+12 | 0.00 | 0.00 | 286018.09 | 0.00 | 0.00 | 0.184898E+10 | 0.00 | 1.85 |
Annual Sum or Average | 0.654210E+12 | 0.284058E+11 | 0.00 | 0.389983E+09 | 0.122673E+11 | 0.00 | 0.338543E+12 | 0.00 | 1.89 |
Minimum of Months | 0.287611E+10 | 0.00 | 0.00 | 143808.07 | 0.00 | 0.00 | 0.133240E+10 | 0.00 | 1.84 |
Maximum of Months | 0.105967E+12 | 0.158609E+11 | 0.00 | 81727184.73 | 0.559678E+10 | 0.00 | 0.546893E+11 | 0.00 | 1.99 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 44676965.48 | 0.00 | 0.00 | 144805.34 | 0.00 | 0.165825E+10 | 7038870.36 | 0.00 | 0.35 |
February | 51768368.79 | 0.00 | 0.00 | 249458.44 | 0.00 | 0.149854E+10 | 19785878.01 | 0.00 | 0.35 |
March | 77564888.94 | 389930.10 | 0.00 | 2390904.15 | 0.00 | 0.118053E+10 | 0.297412E+09 | 0.00 | 0.35 |
April | 66220221.28 | 0.00 | 0.00 | 5323272.66 | 0.00 | 0.689518E+09 | 0.726034E+09 | 0.00 | 0.36 |
May | 30412739.83 | 2299708.17 | 0.00 | 12934663.98 | 0.00 | 65464156.66 | 0.121074E+10 | 0.00 | 0.36 |
June | 2730706.89 | 0.176363E+09 | 63532.71 | 12865593.35 | 62474.60 | 1523559.37 | 0.629576E+09 | 4931.83 | 0.36 |
July | 0.00 | 0.522047E+09 | 159525.30 | 5676504.14 | 0.00 | 322001.93 | 0.189043E+09 | 6860.21 | 0.36 |
August | 2256393.79 | 0.276740E+09 | 137005.08 | 10366457.77 | 0.00 | 961883.21 | 0.393914E+09 | 4879.53 | 0.35 |
September | 9597880.90 | 0.102639E+09 | 91747.25 | 11692136.42 | 0.00 | 45572586.29 | 0.818075E+09 | 7546.78 | 0.36 |
October | 69919219.62 | 0.00 | 0.00 | 4277457.94 | 0.00 | 0.675635E+09 | 0.704554E+09 | 0.00 | 0.35 |
November | 77559212.53 | 0.00 | 0.00 | 850215.00 | 0.00 | 0.118196E+10 | 0.207255E+09 | 0.00 | 0.36 |
December | 39394815.58 | 0.00 | 0.00 | 118425.89 | 0.00 | 0.162897E+10 | 6032322.02 | 0.00 | 0.36 |
Annual Sum or Average | 0.472101E+09 | 0.108048E+10 | 451810.34 | 66889895.09 | 62474.60 | 0.862724E+10 | 0.520946E+10 | 24218.36 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 118425.89 | 0.00 | 322001.93 | 6032322.02 | 0.00 | 0.35 |
Maximum of Months | 77564888.94 | 0.522047E+09 | 159525.30 | 12934663.98 | 62474.60 | 0.165825E+10 | 0.121074E+10 | 7546.78 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 9576480.96 | 0.00 | 0.00 | 60035.74 | 0.00 | 0.169800E+10 | 2275896.22 | 0.00 | 0.35 |
February | 18845986.69 | 0.00 | 0.00 | 85764.85 | 0.00 | 0.154181E+10 | 9416492.03 | 0.00 | 0.35 |
March | 85672657.54 | 149251.74 | 0.00 | 1234698.68 | 240632.68 | 0.124425E+10 | 0.226558E+09 | 0.00 | 0.35 |
April | 0.120140E+09 | 0.00 | 0.00 | 3855374.54 | 0.00 | 0.808267E+09 | 0.554659E+09 | 0.00 | 0.36 |
May | 0.207749E+09 | 1921642.69 | 0.00 | 10043894.42 | 377796.04 | 89564550.16 | 0.101203E+10 | 0.00 | 0.36 |
June | 0.152797E+09 | 0.145434E+09 | 61567.58 | 9671992.47 | 30974973.85 | 1332273.05 | 0.482819E+09 | 2807.36 | 0.36 |
July | 52655683.49 | 0.430647E+09 | 176711.18 | 4183149.87 | 91320717.19 | 118495.44 | 0.138062E+09 | 7850.48 | 0.36 |
August | 0.111928E+09 | 0.233783E+09 | 119167.79 | 7316390.02 | 42937051.95 | 427331.83 | 0.287779E+09 | 10805.23 | 0.36 |
September | 0.164557E+09 | 75772612.82 | 128083.39 | 7143449.44 | 26819647.89 | 50893703.14 | 0.662240E+09 | 6296.03 | 0.36 |
October | 0.146486E+09 | 0.00 | 0.00 | 2052671.06 | 0.00 | 0.833255E+09 | 0.472421E+09 | 0.00 | 0.35 |
November | 88973593.23 | 0.00 | 0.00 | 316071.09 | 0.00 | 0.131044E+10 | 67718121.50 | 0.00 | 0.36 |
December | 22197204.50 | 0.00 | 0.00 | 67198.37 | 0.00 | 0.164973E+10 | 2329633.36 | 0.00 | 0.36 |
Annual Sum or Average | 0.118158E+10 | 0.887707E+09 | 485529.94 | 46030690.56 | 0.192671E+09 | 0.922808E+10 | 0.391831E+10 | 27759.10 | 0.36 |
Minimum of Months | 9576480.96 | 0.00 | 0.00 | 60035.74 | 0.00 | 118495.44 | 2275896.22 | 0.00 | 0.35 |
Maximum of Months | 0.207749E+09 | 0.430647E+09 | 176711.18 | 10043894.42 | 91320717.19 | 0.169800E+10 | 0.101203E+10 | 10805.23 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.819305E+09 | 0.00 | 0.00 | 0.00 | 2576742.07 | 66472265.12 | 0.00 | 0.00 | 0.02 |
February | 0.802600E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
March | 0.105785E+10 | 644475.45 | 0.00 | 509999.59 | 0.00 | 0.00 | 0.322728E+09 | 0.00 | 0.02 |
April | 0.628747E+09 | 0.00 | 0.00 | 1873354.88 | 0.00 | 0.00 | 0.958153E+09 | 0.00 | 0.02 |
May | 0.142850E+09 | 33167544.68 | 0.00 | 2616111.20 | 0.00 | 0.00 | 0.128096E+10 | 0.00 | 0.02 |
June | 0.00 | 0.313894E+09 | 0.00 | 2011562.40 | 0.00 | 0.00 | 0.590836E+09 | 0.00 | 0.02 |
July | 0.00 | 0.635853E+09 | 0.00 | 564209.99 | 0.00 | 0.00 | 69366531.95 | 0.00 | 0.02 |
August | 0.00 | 0.360761E+09 | 0.00 | 2330345.99 | 0.00 | 0.00 | 0.221219E+09 | 0.00 | 0.02 |
September | 57220008.97 | 0.167656E+09 | 0.00 | 3573510.06 | 0.00 | 0.00 | 0.692414E+09 | 0.00 | 0.02 |
October | 0.569761E+09 | 0.00 | 0.00 | 2780435.17 | 0.00 | 0.00 | 0.100774E+10 | 0.00 | 0.02 |
November | 0.110661E+10 | 0.00 | 0.00 | 427794.28 | 0.00 | 0.00 | 0.279694E+09 | 0.00 | 0.02 |
December | 0.879920E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.606487E+10 | 0.151198E+10 | 0.00 | 16687323.57 | 2576742.07 | 66472265.12 | 0.542311E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.110661E+10 | 0.635853E+09 | 0.00 | 3573510.06 | 2576742.07 | 66472265.12 | 0.128096E+10 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112697E+10 | 0.00 | 0.00 | 2162731.13 | 0.00 | 0.202291E+11 | 0.183573E+10 | 0.00 | 0.40 |
February | 0.105664E+10 | 0.00 | 0.00 | 1750304.03 | 0.00 | 0.187425E+11 | 0.149737E+10 | 0.00 | 0.40 |
March | 0.125705E+10 | 2024510.28 | 0.00 | 24618873.04 | 3264037.96 | 0.102305E+11 | 0.961722E+10 | 0.00 | 0.40 |
April | 0.162962E+10 | 0.00 | 0.00 | 56747587.69 | 0.00 | 0.764106E+09 | 0.177187E+11 | 0.00 | 0.40 |
May | 0.300409E+10 | 21313790.43 | 0.00 | 0.123046E+09 | 9876716.48 | 29736168.52 | 0.147399E+11 | 0.00 | 0.40 |
June | 0.237749E+10 | 0.194750E+10 | 415472.43 | 0.113149E+09 | 0.445830E+09 | 3314414.38 | 0.627706E+10 | 10876.60 | 0.40 |
July | 0.750631E+09 | 0.580485E+10 | 197259.85 | 51923854.72 | 0.127764E+10 | 0.00 | 0.184276E+10 | 200.80 | 0.41 |
August | 0.159759E+10 | 0.314197E+10 | 203539.27 | 85457082.69 | 0.613125E+09 | 1718177.48 | 0.384207E+10 | 3576.79 | 0.40 |
September | 0.245401E+10 | 0.948186E+09 | 0.00 | 96281454.90 | 0.445239E+09 | 13435862.99 | 0.943851E+10 | 0.00 | 0.40 |
October | 0.198535E+10 | 0.00 | 0.00 | 53026910.32 | 0.00 | 0.825014E+09 | 0.168622E+11 | 0.00 | 0.40 |
November | 0.126147E+10 | 0.00 | 0.00 | 19852384.47 | 0.00 | 0.468962E+10 | 0.139341E+11 | 0.00 | 0.40 |
December | 0.112660E+10 | 0.00 | 0.00 | 3046808.32 | 0.00 | 0.183761E+11 | 0.320537E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.196275E+11 | 0.118658E+11 | 816271.55 | 0.631062E+09 | 0.279498E+10 | 0.739052E+11 | 0.100811E+12 | 14654.19 | 0.40 |
Minimum of Months | 0.750631E+09 | 0.00 | 0.00 | 1750304.03 | 0.00 | 0.00 | 0.149737E+10 | 0.00 | 0.40 |
Maximum of Months | 0.300409E+10 | 0.580485E+10 | 415472.43 | 0.123046E+09 | 0.127764E+10 | 0.202291E+11 | 0.177187E+11 | 10876.60 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 50870968.40 | 0.00 | 0.00 | 97505.07 | 0.00 | 0.163635E+10 | 22789842.60 | 0.00 | 0.35 |
February | 56084053.12 | 0.00 | 0.00 | 214363.95 | 0.00 | 0.147883E+10 | 35216924.14 | 0.00 | 0.35 |
March | 75970264.37 | 389930.10 | 0.00 | 2074430.03 | 0.00 | 0.116471E+10 | 0.315140E+09 | 0.00 | 0.35 |
April | 48918530.85 | 0.00 | 0.00 | 5498837.48 | 0.00 | 0.668895E+09 | 0.763782E+09 | 0.00 | 0.36 |
May | 17363968.92 | 2299708.17 | 0.00 | 12161705.94 | 0.00 | 0.109787E+09 | 0.118023E+10 | 0.00 | 0.36 |
June | 0.00 | 0.176071E+09 | 849.58 | 12046512.81 | 421112.64 | 835640.81 | 0.633814E+09 | 1233.28 | 0.36 |
July | 0.00 | 0.522214E+09 | 0.00 | 6866608.16 | 0.00 | 0.00 | 0.188175E+09 | 0.00 | 0.36 |
August | 1097692.75 | 0.276813E+09 | 67187.75 | 11125128.90 | 0.00 | 343414.52 | 0.394933E+09 | 1704.81 | 0.35 |
September | 7680108.23 | 0.102725E+09 | 12084.08 | 11441560.62 | 0.00 | 44935500.72 | 0.820880E+09 | 1603.21 | 0.36 |
October | 62847278.77 | 0.00 | 0.00 | 4541231.10 | 0.00 | 0.665771E+09 | 0.721226E+09 | 0.00 | 0.35 |
November | 78213543.33 | 0.00 | 0.00 | 973201.11 | 0.00 | 0.116271E+10 | 0.225729E+09 | 0.00 | 0.36 |
December | 36394466.15 | 0.00 | 0.00 | 119990.48 | 0.00 | 0.161949E+10 | 18513887.18 | 0.00 | 0.36 |
Annual Sum or Average | 0.435441E+09 | 0.108051E+10 | 80121.41 | 67161075.66 | 421112.64 | 0.855265E+10 | 0.532043E+10 | 4541.30 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 97505.07 | 0.00 | 0.00 | 18513887.18 | 0.00 | 0.35 |
Maximum of Months | 78213543.33 | 0.522214E+09 | 67187.75 | 12161705.94 | 421112.64 | 0.163635E+10 | 0.118023E+10 | 1704.81 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 11548506.90 | 0.00 | 0.00 | 52222.78 | 0.00 | 0.169616E+10 | 2147406.63 | 0.00 | 0.35 |
February | 26475091.17 | 0.00 | 0.00 | 78121.36 | 0.00 | 0.153427E+10 | 9335792.56 | 0.00 | 0.35 |
March | 87452710.68 | 162249.61 | 0.00 | 1041263.37 | 227634.81 | 0.125322E+10 | 0.215999E+09 | 0.00 | 0.35 |
April | 0.105416E+09 | 0.00 | 0.00 | 3891492.33 | 0.00 | 0.783614E+09 | 0.594000E+09 | 0.00 | 0.36 |
May | 0.178485E+09 | 2033813.12 | 0.00 | 9675838.49 | 265625.61 | 0.129480E+09 | 0.100175E+10 | 0.00 | 0.36 |
June | 0.146911E+09 | 0.145910E+09 | 17437.99 | 9535411.11 | 30542422.71 | 771863.08 | 0.489402E+09 | 2968.48 | 0.36 |
July | 51203501.62 | 0.432343E+09 | 9817.16 | 4742403.15 | 89798251.65 | 50761.43 | 0.139022E+09 | 1446.88 | 0.36 |
August | 0.108684E+09 | 0.234646E+09 | 28014.90 | 7742827.73 | 42174531.17 | 269551.06 | 0.290755E+09 | 1043.76 | 0.36 |
September | 0.151501E+09 | 76251057.94 | 103595.85 | 7677105.01 | 26369551.53 | 50977788.70 | 0.674678E+09 | 2434.83 | 0.36 |
October | 0.145202E+09 | 0.00 | 0.00 | 2219592.92 | 0.00 | 0.803758E+09 | 0.503036E+09 | 0.00 | 0.35 |
November | 88383055.52 | 0.00 | 0.00 | 334221.57 | 0.00 | 0.127866E+10 | 0.100073E+09 | 0.00 | 0.36 |
December | 17612949.09 | 0.00 | 0.00 | 57697.67 | 0.00 | 0.165333E+10 | 3319409.92 | 0.00 | 0.36 |
Annual Sum or Average | 0.111887E+10 | 0.891347E+09 | 158865.90 | 47048197.49 | 0.189378E+09 | 0.918456E+10 | 0.402352E+10 | 7893.95 | 0.36 |
Minimum of Months | 11548506.90 | 0.00 | 0.00 | 52222.78 | 0.00 | 50761.43 | 2147406.63 | 0.00 | 0.35 |
Maximum of Months | 0.178485E+09 | 0.432343E+09 | 103595.85 | 9675838.49 | 89798251.65 | 0.169616E+10 | 0.100175E+10 | 2968.48 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.141216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138757E+11 | 0.00 | 0.00 | 0.52 |
February | 0.135237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122265E+11 | 0.00 | 0.00 | 0.52 |
March | 0.252202E+11 | 0.00 | 0.00 | 0.00 | 2020053.13 | 0.696528E+09 | 0.00 | 0.00 | 0.52 |
April | 0.250647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
May | 0.241852E+11 | 0.00 | 0.00 | 0.00 | 1645785.43 | 0.00 | 0.00 | 0.00 | 0.53 |
June | 0.137146E+11 | 2542997.75 | 0.00 | 3271.88 | 0.161253E+10 | 0.00 | 29748374.37 | 0.00 | 0.53 |
July | 0.623494E+10 | 0.102839E+10 | 0.00 | 31206.87 | 0.424058E+10 | 0.00 | 17974988.52 | 0.00 | 0.53 |
August | 0.993119E+10 | 0.149609E+09 | 0.00 | 230342.92 | 0.217939E+10 | 0.00 | 0.485622E+09 | 0.00 | 0.53 |
September | 0.184889E+11 | 0.00 | 0.00 | 0.00 | 0.850512E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 0.268886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
November | 0.238858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.813326E+09 | 0.00 | 0.00 | 0.53 |
December | 0.137178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136210E+11 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.214977E+12 | 0.118054E+10 | 0.00 | 264821.67 | 0.888667E+10 | 0.412330E+11 | 0.533346E+09 | 0.00 | 0.53 |
Minimum of Months | 0.623494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.268886E+11 | 0.102839E+10 | 0.00 | 230342.92 | 0.424058E+10 | 0.138757E+11 | 0.485622E+09 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4969874.23 | 0.00 | 0.00 | 45427.30 | 0.00 | 0.420901E+09 | 1611651.59 | 0.00 | 0.35 |
February | 5921913.06 | 0.00 | 0.00 | 72060.97 | 0.00 | 0.382309E+09 | 4283103.05 | 0.00 | 0.35 |
March | 18367061.74 | 97482.53 | 0.00 | 532599.00 | 0.00 | 0.315074E+09 | 55499853.05 | 0.00 | 0.35 |
April | 15506005.05 | 0.00 | 0.00 | 1285971.46 | 0.00 | 0.218462E+09 | 0.136520E+09 | 0.00 | 0.36 |
May | 6772829.96 | 574927.04 | 0.00 | 3120624.20 | 0.00 | 64323212.14 | 0.255670E+09 | 0.00 | 0.36 |
June | 1233130.26 | 44091170.32 | 14631.35 | 3112351.61 | 15618.65 | 3770393.68 | 0.153558E+09 | 2028.63 | 0.36 |
July | 0.00 | 0.130504E+09 | 45762.93 | 1323266.59 | 0.00 | 83029.55 | 47354192.84 | 3880.75 | 0.36 |
August | 564098.45 | 69181338.55 | 37924.83 | 2431644.94 | 0.00 | 260154.51 | 98618861.82 | 1295.43 | 0.35 |
September | 2409299.11 | 25659108.53 | 23823.30 | 2714716.76 | 0.00 | 18664338.50 | 0.197446E+09 | 1737.55 | 0.36 |
October | 17549675.60 | 0.00 | 0.00 | 936523.78 | 0.00 | 0.215849E+09 | 0.129261E+09 | 0.00 | 0.35 |
November | 17545047.53 | 0.00 | 0.00 | 178720.62 | 0.00 | 0.323542E+09 | 25639877.13 | 0.00 | 0.36 |
December | 5492764.90 | 0.00 | 0.00 | 39114.16 | 0.00 | 0.411826E+09 | 1270828.43 | 0.00 | 0.36 |
Annual Sum or Average | 96331699.90 | 0.270108E+09 | 122142.41 | 15793021.39 | 15618.65 | 0.237506E+10 | 0.110673E+10 | 8942.36 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 39114.16 | 0.00 | 83029.55 | 1270828.43 | 0.00 | 0.35 |
Maximum of Months | 18367061.74 | 0.130504E+09 | 45762.93 | 3120624.20 | 15618.65 | 0.420901E+09 | 0.255670E+09 | 3880.75 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 524825.92 | 0.00 | 0.00 | 20377.54 | 0.00 | 0.426352E+09 | 580611.63 | 0.00 | 0.35 |
February | 869136.90 | 0.00 | 0.00 | 23007.99 | 0.00 | 0.389844E+09 | 1803680.75 | 0.00 | 0.35 |
March | 15086639.74 | 37312.93 | 0.00 | 246549.43 | 60158.17 | 0.335082E+09 | 39012758.90 | 0.00 | 0.35 |
April | 29921462.18 | 0.00 | 0.00 | 920968.45 | 0.00 | 0.242509E+09 | 98378798.09 | 0.00 | 0.36 |
May | 49859689.91 | 508453.28 | 0.00 | 2484492.68 | 66406.40 | 67695601.86 | 0.209808E+09 | 0.00 | 0.36 |
June | 37632958.42 | 36358442.05 | 15465.16 | 2487269.19 | 7743743.46 | 2278206.39 | 0.119257E+09 | 628.58 | 0.36 |
July | 12998000.68 | 0.107660E+09 | 46650.80 | 1034249.65 | 22830179.30 | 24514.07 | 34698011.58 | 1651.37 | 0.36 |
August | 27765022.47 | 58442261.73 | 33072.15 | 1767891.52 | 10734262.99 | 113891.66 | 72216017.96 | 2851.74 | 0.36 |
September | 40180028.45 | 18991442.06 | 20069.50 | 1623649.29 | 6669319.12 | 20416993.82 | 0.158988E+09 | 829.36 | 0.36 |
October | 36591123.19 | 0.00 | 0.00 | 398880.55 | 0.00 | 0.255645E+09 | 70918658.58 | 0.00 | 0.35 |
November | 17856886.24 | 0.00 | 0.00 | 70191.10 | 0.00 | 0.343252E+09 | 5683756.68 | 0.00 | 0.36 |
December | 1743854.42 | 0.00 | 0.00 | 25410.33 | 0.00 | 0.416097E+09 | 713874.76 | 0.00 | 0.36 |
Annual Sum or Average | 0.271030E+09 | 0.221998E+09 | 115257.60 | 11102937.71 | 48104069.44 | 0.249931E+10 | 0.812059E+09 | 5961.04 | 0.36 |
Minimum of Months | 524825.92 | 0.00 | 0.00 | 20377.54 | 0.00 | 24514.07 | 580611.63 | 0.00 | 0.35 |
Maximum of Months | 49859689.91 | 0.107660E+09 | 46650.80 | 2487269.19 | 22830179.30 | 0.426352E+09 | 0.209808E+09 | 2851.74 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 83862635.85 | 0.00 | 0.00 | 995402.05 | 0.00 | 0.250181E+10 | 0.159985E+09 | 0.00 | 0.40 |
February | 0.100785E+09 | 0.00 | 0.00 | 1037397.44 | 0.00 | 0.224753E+10 | 0.172816E+09 | 0.00 | 0.40 |
March | 62369732.79 | 626275.45 | 0.00 | 5649882.86 | 0.00 | 0.151607E+10 | 0.918080E+09 | 0.00 | 0.40 |
April | 59563482.39 | 0.00 | 0.00 | 8795268.52 | 0.00 | 0.871379E+09 | 0.144872E+10 | 0.00 | 0.40 |
May | 21282519.90 | 3693612.66 | 0.00 | 15950724.10 | 0.00 | 0.124083E+09 | 0.195804E+10 | 0.00 | 0.40 |
June | 2636604.19 | 0.282674E+09 | 21828.75 | 13592088.83 | 773600.55 | 7844167.48 | 0.101460E+10 | 1503.20 | 0.40 |
July | 0.00 | 0.838513E+09 | 217756.59 | 6709793.10 | 0.00 | 465122.23 | 0.306086E+09 | 8035.68 | 0.40 |
August | 3624044.46 | 0.444703E+09 | 3615.10 | 13554133.46 | 0.00 | 1296302.15 | 0.636019E+09 | 216.67 | 0.40 |
September | 7147595.22 | 0.165011E+09 | 0.00 | 18069414.60 | 0.00 | 30905049.71 | 0.136520E+10 | 0.00 | 0.40 |
October | 73702038.65 | 0.00 | 0.00 | 11018518.37 | 0.00 | 0.688275E+09 | 0.156293E+10 | 0.00 | 0.40 |
November | 84092266.13 | 0.00 | 0.00 | 4190744.63 | 0.00 | 0.141944E+10 | 0.849454E+09 | 0.00 | 0.40 |
December | 83633693.21 | 0.00 | 0.00 | 986566.04 | 0.00 | 0.247027E+10 | 0.134589E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.582699E+09 | 0.173522E+10 | 243200.44 | 0.100550E+09 | 773600.55 | 0.118794E+11 | 0.105265E+11 | 9755.55 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 986566.04 | 0.00 | 465122.23 | 0.134589E+09 | 0.00 | 0.40 |
Maximum of Months | 0.100785E+09 | 0.838513E+09 | 217756.59 | 18069414.60 | 773600.55 | 0.250181E+10 | 0.195804E+10 | 8035.68 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.150858E+11 | 0.00 | 0.00 | 30066107.37 | 0.00 | 0.00 | 0.341949E+11 | 0.00 | 4.35 |
February | 0.145051E+11 | 0.00 | 0.00 | 26800661.97 | 0.00 | 0.00 | 0.307803E+11 | 0.00 | 4.35 |
March | 0.752764E+10 | 1139796.54 | 0.00 | 43880364.63 | 2342516.55 | 0.00 | 0.401539E+11 | 0.00 | 4.53 |
April | 0.198720E+10 | 0.00 | 0.00 | 56019797.46 | 0.00 | 0.00 | 0.457689E+11 | 0.00 | 4.73 |
May | 0.600618E+09 | 2850652.57 | 0.00 | 81408348.28 | 0.00 | 0.00 | 0.490368E+11 | 0.00 | 5.02 |
June | 0.111195E+09 | 0.330395E+10 | 0.00 | 81107759.57 | 1075191.26 | 0.00 | 0.300611E+11 | 0.00 | 5.33 |
July | 11679908.84 | 0.112341E+11 | 0.00 | 55906321.20 | 549724.36 | 0.00 | 0.145227E+11 | 0.00 | 5.51 |
August | 42658258.64 | 0.484781E+10 | 0.00 | 76216944.44 | 3545932.82 | 0.00 | 0.235549E+11 | 0.00 | 5.41 |
September | 0.307037E+09 | 0.170132E+10 | 0.00 | 72523273.67 | 5561051.78 | 0.00 | 0.382327E+11 | 0.00 | 5.10 |
October | 0.197416E+10 | 0.00 | 0.00 | 57692303.33 | 0.00 | 0.00 | 0.498434E+11 | 0.00 | 4.75 |
November | 0.480194E+10 | 0.00 | 0.00 | 44347074.74 | 0.00 | 0.00 | 0.410419E+11 | 0.00 | 4.61 |
December | 0.139771E+11 | 0.00 | 0.00 | 32003549.98 | 0.00 | 0.00 | 0.343355E+11 | 0.00 | 4.39 |
Annual Sum or Average | 0.609322E+11 | 0.210911E+11 | 0.00 | 0.657973E+09 | 13074416.76 | 0.00 | 0.431527E+12 | 0.00 | 4.84 |
Minimum of Months | 11679908.84 | 0.00 | 0.00 | 26800661.97 | 0.00 | 0.00 | 0.145227E+11 | 0.00 | 4.35 |
Maximum of Months | 0.150858E+11 | 0.112341E+11 | 0.00 | 81408348.28 | 5561051.78 | 0.00 | 0.498434E+11 | 0.00 | 5.51 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.104391E+11 | 0.00 | 0.00 | 41656327.63 | 0.00 | 0.00 | 0.424309E+11 | 0.00 | 4.67 |
February | 0.820985E+10 | 0.00 | 0.00 | 37535088.61 | 0.00 | 0.00 | 0.403376E+11 | 0.00 | 4.67 |
March | 0.321356E+10 | 3523326.38 | 0.00 | 57750910.46 | 133493.55 | 0.00 | 0.484817E+11 | 0.00 | 4.91 |
April | 0.634133E+09 | 0.00 | 0.00 | 71697632.46 | 0.00 | 0.00 | 0.514507E+11 | 0.00 | 5.16 |
May | 44253689.71 | 3124006.70 | 0.00 | 96675852.04 | 0.00 | 0.00 | 0.539008E+11 | 0.00 | 5.45 |
June | 15490295.64 | 0.355505E+10 | 0.00 | 90838582.26 | 0.00 | 0.00 | 0.323770E+11 | 0.00 | 5.73 |
July | 0.00 | 0.119939E+11 | 0.00 | 61645188.12 | 0.00 | 0.00 | 0.154448E+11 | 0.00 | 5.88 |
August | 215798.05 | 0.519674E+10 | 0.00 | 84837980.70 | 0.00 | 0.00 | 0.251379E+11 | 0.00 | 5.77 |
September | 27590296.37 | 0.184061E+10 | 0.00 | 84098861.47 | 187578.16 | 0.00 | 0.415898E+11 | 0.00 | 5.50 |
October | 0.706569E+09 | 0.00 | 0.00 | 72757955.81 | 0.00 | 0.00 | 0.557122E+11 | 0.00 | 5.17 |
November | 0.143656E+10 | 0.00 | 0.00 | 58860345.09 | 0.00 | 0.00 | 0.485135E+11 | 0.00 | 5.01 |
December | 0.844285E+10 | 0.00 | 0.00 | 44229051.11 | 0.00 | 0.00 | 0.435109E+11 | 0.00 | 4.73 |
Annual Sum or Average | 0.331701E+11 | 0.225930E+11 | 0.00 | 0.802584E+09 | 321071.71 | 0.00 | 0.498888E+12 | 0.00 | 5.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 37535088.61 | 0.00 | 0.00 | 0.154448E+11 | 0.00 | 4.67 |
Maximum of Months | 0.104391E+11 | 0.119939E+11 | 0.00 | 96675852.04 | 187578.16 | 0.00 | 0.557122E+11 | 0.00 | 5.88 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 55630936.34 | 0.00 | 0.00 | 0.102912E+09 | 0.00 | 0.00 | 0.699766E+11 | 0.00 | 19.93 |
February | 65609169.81 | 0.00 | 0.00 | 92604553.66 | 0.00 | 0.00 | 0.645966E+11 | 0.00 | 20.04 |
March | 20141845.35 | 6559202.41 | 0.00 | 0.106867E+09 | 0.00 | 0.00 | 0.671318E+11 | 0.00 | 20.86 |
April | 0.00 | 0.00 | 0.00 | 0.110150E+09 | 0.00 | 0.00 | 0.669272E+11 | 0.00 | 21.61 |
May | 0.00 | 5282843.28 | 0.00 | 0.135022E+09 | 0.00 | 0.00 | 0.640765E+11 | 0.00 | 22.09 |
June | 0.00 | 0.501357E+10 | 0.00 | 0.114214E+09 | 0.00 | 0.00 | 0.350524E+11 | 0.00 | 22.47 |
July | 0.00 | 0.159477E+11 | 0.00 | 73696711.51 | 0.00 | 0.00 | 0.147283E+11 | 0.00 | 22.69 |
August | 0.00 | 0.713501E+10 | 0.00 | 0.107217E+09 | 0.00 | 0.00 | 0.256723E+11 | 0.00 | 22.49 |
September | 0.00 | 0.264993E+10 | 0.00 | 0.115672E+09 | 0.00 | 0.00 | 0.477530E+11 | 0.00 | 22.16 |
October | 0.00 | 0.00 | 0.00 | 0.111124E+09 | 0.00 | 0.00 | 0.710157E+11 | 0.00 | 21.46 |
November | 0.00 | 0.00 | 0.00 | 0.101559E+09 | 0.00 | 0.00 | 0.640129E+11 | 0.00 | 20.96 |
December | 68511071.22 | 0.00 | 0.00 | 0.102070E+09 | 0.00 | 0.00 | 0.681546E+11 | 0.00 | 20.05 |
Annual Sum or Average | 0.209893E+09 | 0.307580E+11 | 0.00 | 0.127311E+10 | 0.00 | 0.00 | 0.659098E+12 | 0.00 | 21.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 73696711.51 | 0.00 | 0.00 | 0.147283E+11 | 0.00 | 19.93 |
Maximum of Months | 68511071.22 | 0.159477E+11 | 0.00 | 0.135022E+09 | 0.00 | 0.00 | 0.710157E+11 | 0.00 | 22.69 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.590714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.972797E+10 | 0.00 | 0.00 | 1.10 |
February | 0.543294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894730E+10 | 0.00 | 0.00 | 1.10 |
March | 0.122286E+11 | 0.00 | 0.00 | 0.00 | 1128100.17 | 0.224457E+10 | 0.00 | 0.00 | 1.10 |
April | 0.139272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70171271.15 | 0.00 | 0.00 | 1.11 |
May | 0.135063E+11 | 0.00 | 0.00 | 0.00 | 919090.10 | 0.00 | 0.00 | 0.00 | 1.11 |
June | 0.751718E+10 | 0.326330E+09 | 0.00 | 350910.15 | 0.576415E+09 | 0.00 | 0.158013E+09 | 0.00 | 1.12 |
July | 0.317155E+10 | 0.201740E+10 | 0.00 | 907617.15 | 0.993251E+09 | 0.00 | 0.319528E+09 | 0.00 | 1.14 |
August | 0.507912E+10 | 0.645007E+09 | 0.00 | 2423417.16 | 0.665579E+09 | 0.00 | 0.740646E+09 | 0.00 | 1.13 |
September | 0.103029E+11 | 26233078.52 | 0.00 | 112054.67 | 0.448736E+09 | 0.00 | 22154521.62 | 0.00 | 1.11 |
October | 0.150001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15802782.69 | 0.00 | 0.00 | 1.11 |
November | 0.135365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256787E+09 | 0.00 | 0.00 | 1.11 |
December | 0.652108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.874632E+10 | 0.00 | 0.00 | 1.11 |
Annual Sum or Average | 0.112131E+12 | 0.301497E+10 | 0.00 | 3793999.15 | 0.268603E+10 | 0.300089E+11 | 0.124034E+10 | 0.00 | 1.11 |
Minimum of Months | 0.317155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 |
Maximum of Months | 0.150001E+11 | 0.201740E+10 | 0.00 | 2423417.16 | 0.993251E+09 | 0.972797E+10 | 0.740646E+09 | 0.00 | 1.14 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:01:52
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.156492E+12 | 0.609504E+10 | 0.291964E+12 | 0.124144E+13 | 0.862450E+11 |
February | 0.252686E+12 | 0.566765E+10 | 0.269411E+12 | 0.114998E+13 | 0.810361E+11 |
March | 0.379770E+12 | 0.485860E+10 | 0.229228E+12 | 0.100215E+13 | 0.100000E+12 |
April | 0.458608E+12 | 0.371654E+10 | 0.173340E+12 | 0.778077E+12 | 0.939017E+11 |
May | 0.574483E+12 | 0.280957E+10 | 0.112334E+12 | 0.512998E+12 | 0.231691E+12 |
June | 0.639868E+12 | 0.112024E+10 | 0.440014E+11 | 0.218255E+12 | 0.568114E+12 |
July | 0.579397E+12 | -656170751.3 | -0.162883E+11 | -0.651571E+11 | 0.936802E+12 |
August | 0.486754E+12 | 0.433635E+09 | 0.219761E+11 | 0.115559E+12 | 0.734623E+12 |
September | 0.360598E+12 | 0.172931E+10 | 0.724400E+11 | 0.340861E+12 | 0.415310E+12 |
October | 0.239301E+12 | 0.340322E+10 | 0.156956E+12 | 0.703459E+12 | 0.134713E+12 |
November | 0.125550E+12 | 0.396166E+10 | 0.193326E+12 | 0.841780E+12 | 0.710151E+11 |
December | 0.141290E+12 | 0.580326E+10 | 0.282491E+12 | 0.119623E+13 | 0.816727E+11 |
Annual Sum or Average | 0.439480E+13 | 0.389426E+11 | 0.183118E+13 | 0.803563E+13 | 0.353512E+13 |
Minimum of Months | 0.125550E+12 | -656170751.3 | -0.162883E+11 | -0.651571E+11 | 0.710151E+11 |
Maximum of Months | 0.639868E+12 | 0.609504E+10 | 0.291964E+12 | 0.124144E+13 | 0.936802E+12 |