Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:01
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2023-10-16 09:02:03
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 9516.53 | 838.81 | 838.81 |
Net Site Energy | 9516.53 | 838.81 | 838.81 |
Total Source Energy | 23122.86 | 2038.10 | 2038.10 |
Net Source Energy | 23122.86 | 2038.10 | 2038.10 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 620.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1595.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 604.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 174.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 641.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 566.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 149.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 166.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 477.19 | 958.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 44.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 6148.32 | 3368.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 620.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1595.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 604.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 174.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 952.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 22.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 566.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 149.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 166.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.75 | 958.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Other | 386.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 21.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 620.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1595.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 604.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 174.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 641.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 566.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 149.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 166.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 477.19 | 958.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 44.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 245.88 | 139.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 227.42 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 541.93 | 296.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 245.88 | 139.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 227.42 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 541.93 | 296.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 6148.319 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 6148.319 | 100.00 |
Total On-Site and Utility Electric Sources | 6148.319 | 100.00 |
Total Electricity End Uses | 6148.319 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 870.02 | 38.97 |
Air to Air Heat Recovery for Heating | 1362.74 | 61.03 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2232.76 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 109.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7940.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYSLAUNDRY HPWH TANK | SWHSYS1 HPWH TANK |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| SWHSYS1 HPWH FAN | SWHSYSLAUNDRY HPWH FAN | FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:01 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 6.6442 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 9.6995 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 9.6995 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 4.0903 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.7049 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 9.2569 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 9.0417 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 4.4132 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.4132 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.7327 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 4.4132 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8432 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8432 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.6442 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 4.0903 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.7049 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 9.2569 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 9.0417 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 4.4132 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.4132 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.7327 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 4.4132 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.8432 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.8432 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.6992 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-AUG-19:49 | 07-JAN-19:10 | - | - | - | - | - | - | - | - | - | - | 03-MAR-21:49 |
Heating | 0.00 | 165135.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 176239.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 50471.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 87982.85 | 83438.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31577.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 31462.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6520.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 38061.04 | 107716.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1682.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 445032.98 | 356289.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 165135.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 176239.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 50471.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58308.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 33453.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1274.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 31462.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 6520.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3838.37 | 107716.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 771.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 669.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 672.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5054.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1913.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 552.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5473.02 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2031.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1795.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 473.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 527.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1511.27 | 1039.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 139.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 19471.73 | 3651.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 59.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 445.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 158.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 41.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 46.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 133.21 | 91.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1716.28 | 321.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 59.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 445.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 158.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 41.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 46.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 133.21 | 91.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1716.28 | 321.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.11 | 0.714280 | 0.557000 | 1.18 | 1.00 | 0.500000 | 0.000533 | 0.000074 | 1.18 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.302842 | 0.168762 | 0.557000 | 0.168683 | 0.557000 | 0.500000 | 0.002258 | 0.000030 | 0.168683 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.227057 | 0.260656 | 0.557000 | 0.126471 | 0.695081 | 0.500000 | 0.001462 | 0.000013 | 0.126471 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.199495 | 0.627351 | 0.557000 | 0.111119 | 1.00 | 0.500000 | 0.000607 | 0.000019 | 0.111119 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.107460 | 0.671941 | 0.557000 | 0.059855 | 1.00 | 0.500000 | 0.000567 | 0.000012 | 0.059855 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.38 | 0.069795 | 0.557000 | 1.88 | 0.557000 | 0.500000 | 0.021662 | 0.000102 | 1.88 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.37 | 0.105373 | 0.557000 | 0.760720 | 0.557000 | 0.500000 | 0.003616 | 0.000091 | 0.760720 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.62 | 0.215556 | 0.557000 | 2.58 | 0.574816 | 0.500000 | 0.001768 | 0.000251 | 2.58 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.19 | 1.00 | 0.557000 | 0.660451 | 1.00 | 0.500000 | 0.000381 | 0.000111 | 0.660451 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.20 | 0.114702 | 0.557000 | 1.23 | 0.557000 | 0.500000 | 0.003322 | 0.000107 | 1.23 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.31 | 0.109265 | 0.557000 | 1.29 | 0.557000 | 0.500000 | 0.003487 | 0.000111 | 1.29 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.23 | 0.063583 | 0.557000 | 1.24 | 0.557000 | 0.500000 | 0.010778 | 0.000078 | 1.24 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.679763 | 0.461983 | 0.557000 | 0.378628 | 1.00 | 0.500000 | 0.000825 | 0.000073 | 0.378628 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 8490.27 | 0.000074 | 180.98 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3453.19 | 0.000030 | 85.68 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1516.57 | 0.000013 | 34.03 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2195.77 | 0.000019 | 54.00 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1329.79 | 0.000012 | 33.74 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11668.37 | 0.000102 | 246.10 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 10415.93 | 0.000091 | 238.27 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 28743.27 | 0.000251 | 639.10 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 5708.36 | 0.000050 | 163.09 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 5718.89 | 0.000050 | 163.40 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 32986.56 | 0.000289 | 942.46 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 33198.52 | 0.000290 | 948.51 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 5686.64 | 0.000050 | 162.47 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 5697.18 | 0.000050 | 162.78 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12745.09 | 0.000111 | 311.62 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1781.74 | 0.000016 | 50.91 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1785.96 | 0.000016 | 51.03 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8550.56 | 0.000075 | 244.30 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 12287.01 | 0.000107 | 269.80 |
DINING_FLR_6 VAV BOX REHEAT COIL | 12738.96 | 0.000111 | 279.37 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8874.41 | 0.000078 | 189.04 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8294.73 | 0.000073 | 209.63 |
VAV WITH REHEAT HEATING COIL | 167523.09 | 0.001466 | 2827.46 |
FLR_3_DOAS HEATING COIL | 16512.40 | 0.000144 | 278.70 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 0.944257 | 0.000050 | 0.000367 |
ROOM_2_FLR_3 FAN COIL | 0.932739 | 0.000050 | 0.000363 |
ROOM_3_MULT19_FLR_3 FAN COIL | 5.30 | 0.000289 | 0.002017 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.66 | 0.000290 | 0.002305 |
ROOM_5_FLR_3 FAN COIL | 0.849306 | 0.000050 | 0.000331 |
ROOM_6_FLR_3 FAN COIL | 0.841845 | 0.000050 | 0.000329 |
ROOM_1_FLR_6 FAN COIL | 0.249876 | 0.000016 | 0.000097 |
ROOM_2_FLR_6 FAN COIL | 0.246408 | 0.000016 | 0.000096 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.11 | 0.000075 | 0.000439 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 0.944257 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 0.932739 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.30 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.66 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 0.849306 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.841845 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.249876 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.246408 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.11 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008614 | 12.80 | 0.008500 | 0.000367 | 0.944257 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008616 | 12.80 | 0.008500 | 0.000363 | 0.932739 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008531 | 12.80 | 0.008500 | 0.002017 | 5.30 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008786 | 12.80 | 0.008500 | 0.002305 | 5.66 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008627 | 12.80 | 0.008500 | 0.000331 | 0.849306 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008628 | 12.80 | 0.008500 | 0.000329 | 0.841845 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008608 | 12.80 | 0.008500 | 0.000097 | 0.249876 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008609 | 12.80 | 0.008500 | 0.000096 | 0.246408 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008688 | 12.80 | 0.008500 | 0.000439 | 1.11 | |
VAV WITH REHEAT COOLING COIL | 29.82 | 6.70 | 0.012399 | 10.92 | 0.008500 | 0.025249 | 20.81 | 706915.30 |
FLR_3_DOAS COOLING COIL | 34.40 | 6.70 | 0.014473 | 11.91 | 0.008500 | 0.003256 | 2.05 | 91161.11 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.66 | 11.66 | 20.93 | 11.66 | 20.81 | 20.81 | 0.300000 | 0.560115 | 20.81 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 20.81 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 20.81 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.025249 | 0.000019 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001466 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.003256 | 0.000146 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000144 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Size Rated Evaporator Air Flow Rate [m3/s] | Design Size Rated Condenser Water Flow Rate [m3/s] | |
SWHSYSLAUNDRY HPWH DXCOIL | 4.90 | 0.004370 |
SWHSYS1 HPWH DXCOIL | 3.87 | 0.003451 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
SWHSYSLAUNDRY HPWH FAN | 4.90 | 700.51 |
SWHSYS1 HPWH FAN | 3.87 | 553.22 |
Condenser water flow rate [m3/s] | Evaporator air flow rate [m3/s] | |
SWHSYS1 HPWH | 0.003451 | 3.87 |
SWHSYSLAUNDRY HPWH | 0.004370 | 4.90 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.034849 | 7109.91 | |
HEATSYS1 PUMP | 0.003569 | 1064.04 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003569 | 0.428222 |
COOLSYS1 | 0.034849 | 4.18 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 407903.26 | 407903.26 | 0.003569 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.034849 | 4922.43 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.034849 | 975668.04 | 976253.81 | 111.29 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 HPWH TANK | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 6.644 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.024 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 4.090 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.780 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.705 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.235 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 9.257 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.637 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 9.042 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.112 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.733 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2943.236 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 13147.704 | 6.644 | 123.454 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13147.704 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 650.557 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 650.557 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 753.347 | 9.699 | 60.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 753.347 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 387.592 | 4.090 | 189.996 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 387.592 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 445.205 | 5.705 | 53.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 445.205 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1748.285 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1748.285 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 11828.200 | 9.042 | 28.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11828.200 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 108.229 | 4.413 | 72.152 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.229 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1718.521 | 4.413 | 82.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1718.521 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1212.035 | 11.733 | 54.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1212.035 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1818.789 | 4.413 | 82.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1818.789 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 1.067 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.370 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.442 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.217 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.286 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7702 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5624 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5260 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6546 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6103 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | -0.55514967E-15 | 0.35055860E-16 | -0.14326465E-09 | 0.28783368E-17 |
29 | 8 | 0.20966873E-07 | 0.14258959E-12 | 0.36819155E-03 | -0.23840058E-09 |
30 | 7 | -0.11954852E-01 | 0.74774803E-08 | -0.22672946E-01 | 0.13593102E-03 |
31 | 6 | 0.39755982 | 0.26159305E-05 | 0.46545104 | -0.46559307E-02 |
32 | 5 | -5.1145337 | 0.98147117E-04 | -4.3902405 | 0.62241115E-01 |
33 | 4 | 32.666535 | 0.80637729E-03 | 21.240866 | -0.41765750 |
34 | 3 | -110.51061 | 0.17642800E-02 | -55.229641 | 1.5048560 |
35 | 2 | 196.42192 | 0.99585215E-03 | 77.513220 | -2.8894543 |
36 | 1 | -170.90254 | 0.10665179E-03 | -55.149704 | 2.7409959 |
37 | 0 | 57.057407 | 0.60929387E-06 | 15.576129 | |
38 | 9 | 0.10314710E-14 | 0.47183642E-16 | -0.12881513E-09 | -0.40099708E-17 |
39 | 8 | 0.18927665E-07 | 0.17950474E-12 | 0.34608657E-03 | -0.21521408E-09 |
40 | 7 | -0.11292911E-01 | 0.96443222E-08 | -0.21719088E-01 | 0.12840450E-03 |
41 | 6 | 0.37957032 | 0.34070209E-05 | 0.45007157 | -0.44438791E-02 |
42 | 5 | -4.9389364 | 0.12890179E-03 | -4.2718596 | 0.60063826E-01 |
43 | 4 | 31.889569 | 0.10670331E-02 | 20.777560 | -0.40734193 |
44 | 3 | -108.85680 | 0.23501275E-02 | -54.313423 | 1.4809641 |
45 | 2 | 194.78196 | 0.13343675E-02 | 76.673975 | -2.8634131 |
46 | 1 | -170.29645 | 0.14368413E-03 | -54.907648 | 2.7303734 |
47 | 0 | 57.057407 | 0.82565881E-06 | 15.617726 | |
48 | 9 | 0.86975537E-15 | 0.52023775E-16 | -0.12536948E-09 | -0.54620444E-17 |
49 | 8 | 0.18440443E-07 | 0.18784465E-12 | 0.34068694E-03 | -0.20967419E-09 |
50 | 7 | -0.11130813E-01 | 0.10155400E-07 | -0.21485363E-01 | 0.12656138E-03 |
51 | 6 | 0.37516444 | 0.35965268E-05 | 0.44629465 | -0.43919449E-02 |
52 | 5 | -4.8959230 | 0.13636263E-03 | -4.2427425 | 0.59530495E-01 |
53 | 4 | 31.699203 | 0.11309484E-02 | 20.663505 | -0.40481456 |
54 | 3 | -108.45147 | 0.24950915E-02 | -54.087828 | 1.4751087 |
55 | 2 | 194.37988 | 0.14187814E-02 | 76.467519 | -2.8570287 |
56 | 1 | -170.14779 | 0.15298304E-03 | -54.848449 | 2.7277680 |
57 | 0 | 57.057407 | 0.88039223E-06 | 15.628184 | |
58 | 9 | 0.12430042E-14 | 0.43603463E-16 | -0.13615479E-09 | -0.52742981E-17 |
59 | 8 | 0.19963588E-07 | 0.16114398E-12 | 0.35741204E-03 | -0.22699287E-09 |
60 | 7 | -0.11632381E-01 | 0.85488282E-08 | -0.22208377E-01 | 0.13226440E-03 |
61 | 6 | 0.38879653 | 0.30047059E-05 | 0.45796739 | -0.45526330E-02 |
62 | 5 | -5.0290001 | 0.11318598E-03 | -4.3326723 | 0.61180550E-01 |
63 | 4 | 32.288109 | 0.93328928E-03 | 21.015642 | -0.41263319 |
64 | 3 | -109.70522 | 0.20484795E-02 | -54.784283 | 1.4932205 |
65 | 2 | 195.62339 | 0.11595496E-02 | 77.105128 | -2.8767741 |
66 | 1 | -170.60747 | 0.12450863E-03 | -55.031726 | 2.7358244 |
67 | 0 | 57.057407 | 0.71328115E-06 | 15.596176 | |
68 | 9 | 0.10418955E-14 | 0.45554749E-16 | -0.13285794E-09 | -0.34221686E-17 |
69 | 8 | 0.19498290E-07 | 0.16949498E-12 | 0.35235048E-03 | -0.22170227E-09 |
70 | 7 | -0.11480752E-01 | 0.90423087E-08 | -0.21989859E-01 | 0.13054032E-03 |
71 | 6 | 0.38467563 | 0.31853038E-05 | 0.45444290 | -0.45040579E-02 |
72 | 5 | -4.9887746 | 0.12022067E-03 | -4.3055366 | 0.60681782E-01 |
73 | 4 | 32.110117 | 0.99300969E-03 | 20.909427 | -0.41027004 |
74 | 3 | -109.32633 | 0.21828955E-02 | -54.574228 | 1.4877470 |
75 | 2 | 195.24766 | 0.12373115E-02 | 76.912747 | -2.8708078 |
76 | 1 | -170.46860 | 0.13302463E-03 | -54.976289 | 2.7333905 |
77 | 0 | 57.057407 | 0.76310210E-06 | 15.605744 | |
78 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
79 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
80 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
81 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
82 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
83 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
84 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
85 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
86 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
87 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
88 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
89 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
90 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
91 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
92 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
93 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.4295_SHGC_0.25 | 37 | 1 | VerySmooth | 2.441 | 2.441 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.4295_SHGC_0.25 | 38 | 1 | VerySmooth | 2.441 | 2.441 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.91738E-002 | 0.16139 | 0.61970 | 0.61970 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12244 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.91738E-002 | 0.16139 | 0.61970 | 0.61970 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12244 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | "DX Coil Total Cooling Rate {W | HPWH Only}" | |
1 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | 1.1400 | 76665.7 | 48.891 | 1.7148 | 76621 | |
2 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | 2.8400 | 62446.2 | 4.639 | 9.4532 | 53264 |
Node Number | Height {m} | Volume {m3} | Maximum Capacity {W} | Off-Cycle UA {W/K} | On-Cycle UA {W/K} | Number Of Inlets | Number Of Outlets | |
1 | 1 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 0 | 1 |
2 | 2 | 0.2683 | 0.4733 | 41512.160 | 1.5573 | 1.5573 | 0 | 0 |
3 | 3 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
4 | 4 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
5 | 5 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 1 |
6 | 6 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 2 | 0 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 9.802E-003 | 1.461E-004 | 7.212E-005 | 0.133 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 3.784E-003 | 4.872E-005 | 1.327E-004 | 4.426E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 8.942E-003 | 5.445E-005 | 1.424E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 5.159E-003 | 5.445E-005 | 1.182E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 1.221E-002 | 1.565E-004 | 1.392E-004 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 2.167E-002 | 1.147E-004 | 6.318E-005 | 0.104 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 6.191E-002 | 4.733E-005 | 9.051E-005 | 4.300E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.587E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.588E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 6.879E-003 | 1.766E-005 | 1.424E-004 | 2.086E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 2.910E-003 | 1.186E-004 | 6.472E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1.243E-002 | 1.204E-004 | 6.523E-005 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1.217E-002 | 2.953E-005 | 2.446E-005 | 3.488E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 8.9580E-002 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.6657E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1002 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.9606E-002 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 6.5426E-002 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.3594E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.6511E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.7811E-003 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 9.8153E-002 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.5023E-002 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1094 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.8621E-002 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.1825E-002 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.9872E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 2.9789E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.2036E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.1008E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.1943E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.6249E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.0557E-003 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.5728E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.2866E-003 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.6108E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.2309E-003 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.1008E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.1943E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.6249E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.0557E-003 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.5728E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.2866E-003 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.6108E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.2309E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 28012.36012 | 28012.36012 | 2.11103 | 2.11103 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 28.79500 | 1.44630E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 2504.51507 | 2504.51507 | 0.11134 | 0.85446 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -6.30000 | 2.29779E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4018.12069 | 4018.12069 | 0.30284 | 0.30284 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 34.40000 | 1.44733E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2594.74972 | 2594.74972 | 0.11535 | 0.11535 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3012.58196 | 3012.58196 | 0.22706 | 0.22706 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 31.40750 | 1.44678E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 872.94310 | 872.94310 | 3.88086E-002 | 9.17347E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2647.46897 | 2647.46897 | 0.19949 | 0.19949 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:40:00 | 29.08000 | 1.44636E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1630.31909 | 1630.31909 | 7.24794E-002 | 7.24794E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1426.07042 | 1426.07042 | 0.10746 | 0.10746 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 31.64500 | 1.44682E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1025.19922 | 1025.19922 | 4.55775E-002 | 5.77652E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44863.51246 | 44863.51246 | 3.38094 | 3.38094 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 33.70333 | 1.44720E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2086.02509 | 2086.02509 | 9.27377E-002 | 9.27377E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 18105.29642 | 18105.29642 | 1.36574 | 1.36574 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 34.40000 | 1.44733E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 6544.43286 | 6544.43286 | 0.29095 | 0.67639 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 61340.25317 | 61340.25317 | 4.62450 | 4.62450 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 15634.25429 | 15634.25429 | 0.69506 | 1.89399 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 9298.46714 | 9298.46714 | 0.94426 | 0.94426 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5708.37511 | 5708.37511 | 0.25527 | 0.25527 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 9185.04742 | 9185.04742 | 0.93274 | 0.93274 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.75333 | 1.44703E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5718.90749 | 5718.90749 | 0.25574 | 0.25574 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 52233.77649 | 52233.77649 | 5.30403 | 5.30403 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 32986.60584 | 32986.60584 | 1.47511 | 1.47511 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 55757.51147 | 55757.51147 | 5.66229 | 5.66229 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 33.92500 | 1.44724E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 33198.56881 | 33198.56881 | 1.48459 | 1.48459 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 8363.44344 | 8363.44344 | 0.84931 | 0.84931 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 31.50250 | 1.44680E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5686.66134 | 5686.66134 | 0.25430 | 0.25430 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 8289.97037 | 8289.97037 | 0.84185 | 0.84185 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 31.26500 | 1.44675E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5697.20048 | 5697.20048 | 0.25477 | 0.25477 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 15734.37060 | 15734.37060 | 1.18573 | 1.18573 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 34.21000 | 1.44729E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 9383.65493 | 9383.65493 | 0.41717 | 0.47476 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -6.30000 | 2.29779E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2460.62711 | 2460.62711 | 0.24988 | 0.24988 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1781.75665 | 1781.75665 | 7.96766E-002 | 7.96766E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2426.47196 | 2426.47196 | 0.24641 | 0.24641 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1785.96976 | 1785.96976 | 7.98650E-002 | 7.98650E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 10906.84848 | 10906.84848 | 1.10761 | 1.10761 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 8550.60847 | 8550.60847 | 0.38237 | 0.38237 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -6.30000 | 2.29779E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29200.57492 | 29200.57492 | 2.20330 | 2.20330 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 6040.71545 | 6040.71545 | 0.26855 | 1.18780 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30654.21433 | 30654.21433 | 2.31294 | 2.31294 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 6181.80425 | 6181.80425 | 0.27483 | 1.18780 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 29470.50116 | 29470.50116 | 2.22677 | 2.22677 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 33.54500 | 1.44717E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2570.91741 | 2570.91741 | 0.11429 | 0.36735 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -6.30000 | 2.29779E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 9020.39880 | 9020.39880 | 0.67976 | 0.67976 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 34.40000 | 1.44733E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 6367.55518 | 6367.55518 | 0.28308 | 0.28308 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -6.30000 | 2.29779E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 413283.61 | 20.81120 | 20.81120 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 197369.61 | 7.35570 | 7.35570 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 51689.19 | 15.52095 | 2.05125 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 55039.41 | 4.52166 | 2.05125 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.11103 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.71428 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55700 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.17585 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.33404E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.42766E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.17585 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8490.26750 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.42766E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 180.98348 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.30284 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16876 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55700 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16868 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55700 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.25761E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.02100E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.16868 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3453.18591 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.02100E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 85.68232 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22706 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26066 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55700 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12647 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69508 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.46170E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.32676E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12647 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1516.56535 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.32676E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 34.03311 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.19949 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.62735 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55700 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11112 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.07315E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.92096E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11112 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2195.77094 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.92096E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 53.99822 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.10746 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.67194 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55700 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.98550E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.67014E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.16336E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.98550E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1329.79327 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.16336E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 33.74207 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.38094 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.97953E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55700 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.88318 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55700 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.16617E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.02080E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.88318 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11668.37020 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.02080E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 246.09620 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.36574 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10537 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55700 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76072 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55700 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.61572E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.11231E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.76072 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10415.92973 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.11231E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 238.26960 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.62450 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21556 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55700 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.57585 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57482 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.76752E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.51459E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.57585 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 28743.27074 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.51459E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 639.10249 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.94426 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.94426 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.99392E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.67191E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70415 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.61408E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.67191E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.94426 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5708.35830 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.99392E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 163.09430 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.93274 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.93274 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.00313E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.62869E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70415 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.61568E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.62869E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.93274 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5718.89066 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.00313E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 163.39520 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.30403 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.30403 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.88581E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.01651E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70471 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.53146E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.01651E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.30403 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 32986.55678 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.88581E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 942.45939 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.66229 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.66229 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.90435E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.30451E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70377 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.78622E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.30451E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.66229 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 33198.51949 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.90435E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 948.51496 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.84931 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.84931 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.97492E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.31439E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70413 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62717E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.31439E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.84931 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5686.64459 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.97492E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 162.47396 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.84185 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.84185 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.98414E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.28630E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70413 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62834E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.28630E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.84185 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5697.18370 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.98414E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 162.77505 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.18573 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.00000 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55700 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.66045 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.80622E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.11500E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.66045 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12745.08730 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.11500E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 311.62472 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.24988 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.24988 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.55875E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.70060E-005 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70416 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60790E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.70060E-005 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.24988 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1781.74286 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55875E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 50.90572 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.24641 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.24641 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.56243E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.56965E-005 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70416 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60932E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.56965E-005 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.24641 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1785.95595 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.56243E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 51.02608 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.10761 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.10761 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.48040E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.39309E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.70387 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.68782E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.39309E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.10761 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8550.55546 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.48040E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 244.29521 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.20330 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11470 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55700 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.22724 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55700 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.32164E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.07492E-004 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.22724 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12287.00942 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.07492E-004 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 269.79714 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.31294 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10926 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55700 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28831 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55700 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.48694E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.11446E-004 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28831 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12738.95953 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.11446E-004 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 279.37436 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.22677 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.35827E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55700 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.24031 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55700 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07777E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.76372E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.24031 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8874.41402 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.76372E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 189.04249 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67976 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.46198 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55700 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.37863 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.24706E-004 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.25659E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.37863 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8294.73155 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.25659E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 209.62656 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.65666 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.65666 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 20.92757 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.65666 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 20.81120 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 20.81120 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.56011 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 20.81120 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 20.81120 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 29.82247 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.92241 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.23992E-002 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 706915.30453 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.52494E-002 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 20.81120 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 167523.09017 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.46557E-003 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2827.45534 |
350 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 20.81120 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.52494E-002 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.88595E-005 |
353 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.46557E-003 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
356 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 34.40000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.90668 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.44733E-002 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 91161.10877 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.25606E-003 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 16512.40431 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.44458E-004 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 278.69642 |
368 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.25606E-003 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.46247E-004 |
371 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.44458E-004 |
372 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 4.90359 |
373 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 4.36989E-003 |
374 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.90359 |
375 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Electric Power Consumption [W] | 700.51236 |
376 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 3.87257 |
377 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 3.45109E-003 |
378 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.87257 |
379 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Electric Power Consumption [W] | 553.22422 |
380 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Condenser water flow rate [m3/s] | 3.45109E-003 |
381 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Evaporator air flow rate [m3/s] | 3.87257 |
382 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 3.48486E-002 |
383 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 7109.90617 |
384 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.56852E-003 |
385 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.42822 |
386 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.56852E-003 |
387 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1064.03980 |
388 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
389 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 407903.25772 |
390 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 407903.26000 |
391 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.56852E-003 |
392 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 3.48486E-002 |
393 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 4.18183 |
394 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 3.48486E-002 |
395 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 4922.42784 |
396 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 3.48486E-002 |
397 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 975668.04145 |
398 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 976253.81000 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 111.29293 |
400 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
401 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
402 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
403 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
404 | WaterHeater:Stratified | SWHSYS1 HPWH TANK | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
405 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Condenser water flow rate [m3/s] | 4.36989E-003 |
406 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Evaporator air flow rate [m3/s] | 4.90359 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 8533.40 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3467.98 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1523.81 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2205.26 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1335.37 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11728.20 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 10464.81 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 28881.90 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 6148.09 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 6159.43 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 35527.58 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 35755.86 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 6124.70 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 6136.05 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12800.47 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1918.98 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1923.52 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 9209.16 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 12347.01 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 12802.15 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8919.52 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8329.66 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 124590.16 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 12280.59 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 15788.18 | 12569.32 | 3218.85 | 0.80 | 1880.73 | 19.08 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 15599.97 | 12418.04 | 3181.93 | 0.80 | 1858.20 | 18.85 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 87389.28 | 70002.15 | 17387.13 | 0.80 | 10444.65 | 105.94 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 97519.95 | 76700.46 | 20819.49 | 0.79 | 11554.53 | 117.19 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 14233.18 | 11320.53 | 2912.64 | 0.80 | 1694.64 | 17.19 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 14111.02 | 11222.42 | 2888.60 | 0.80 | 1680.02 | 17.04 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4173.44 | 3324.07 | 849.36 | 0.80 | 497.27 | 5.04 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4116.54 | 3278.41 | 838.12 | 0.80 | 490.46 | 4.97 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 18757.43 | 14854.19 | 3903.24 | 0.79 | 2228.31 | 22.60 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 622114.62 | 401334.41 | 220780.22 | 0.65 | 75606.01 | 766.84 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 64688.92 | 41041.02 | 23647.90 | 0.63 | 7608.06 | 77.17 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.067 | 0.920 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.370 | 1.137 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.370 | 1.137 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.370 | 1.137 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.370 | 1.137 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.442 | 1.186 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4295_SHGC_0.25 | N/A | 2.441 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.7242281357E-002 | 2.1164875559E-002 | Pass | Pass | 5.2639144779E-003 | 1.6632159992E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.2678614250E-003 | 9.6632115790E-004 | Pass | Pass | 0.1653860225 | 0.6231692881 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.2878578325E-002 | 3.0053234312E-002 | Pass | Pass | 9.8712347015E-003 | 2.2876709612E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.8399190840E-003 | 1.0703260619E-002 | Pass | Pass | 1.7741604865E-002 | 4.0330560871E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.4818102052E-004 | 2.6066883339E-004 | Pass | Pass | 2.3934208610E-002 | 4.0478440565E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.0413001289E-002 | 0.2262625185 | Pass | Pass | 1.9029894659E-002 | 4.9073374113E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.7436275839E-002 | 6.4506812016E-002 | Pass | Pass | 1.6928105669E-002 | 4.4823702204E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.5570333845E-002 | 4.5859817867E-002 | Pass | Pass | 7.8832648558E-003 | 1.8382315950E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.3758031611E-002 | 0.1361746776 | Pass | Pass | 0.1258547461 | 0.4966120120 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.5536923787E-002 | 0.1430885318 | Pass | Pass | 0.1188781765 | 0.4562838398 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.4473184127E-002 | 4.5796294177E-002 | Pass | Pass | 7.2594688971E-003 | 7.5234409570E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.5140624800E-002 | 0.1321216811 | Pass | Pass | 0.4697419487 | 3.7971927724 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.2154810956E-002 | 0.1312888180 | Pass | Pass | 0.1310693755 | 0.5168821376 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.3914653504E-002 | 0.1380519099 | Pass | Pass | 0.1230798239 | 0.4721303283 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.9292551159E-004 | 2.8065698418E-004 | Pass | Pass | 4.3645879177E-002 | 0.1006606240 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.5056335350E-002 | 0.2092182164 | Pass | Pass | 8.9858499724E-002 | 0.3195971770 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.7136127067E-002 | 0.2171975808 | Pass | Pass | 8.7510674472E-002 | 0.3107455755 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.5722491180E-002 | 7.5972336817E-002 | Pass | Pass | 0.1148917877 | 0.3245377430 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.7866815155E-002 | 7.3410180474E-002 | Pass | Pass | 1.1045749102E-002 | 3.1313067368E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.6935146657E-002 | 6.1195298445E-002 | Pass | Pass | 1.2129469440E-002 | 3.6199926018E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.7479840137E-002 | 8.7406631590E-002 | Pass | Pass | 2.0192501691E-002 | 3.8560069218E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.1468217345E-004 | 4.5227529115E-004 | Pass | Pass | 2.3342657073E-002 | 3.0831085340E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3027.34 | 13.41 | 578.13 | 2637.95 | 7116.32 | 13373.14 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.920 | 1.067 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.441 | 0.251 | 0.251 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.441 | 0.251 | 0.251 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.441 | 0.251 | 0.251 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.441 | 0.251 | 0.251 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.441 | 0.251 | 0.251 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.441 | 0.251 | 0.251 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.441 | 0.251 | 0.251 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.441 | 0.251 | 0.251 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.441 | 0.251 | 0.251 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.441 | 0.251 | 0.251 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.441 | 0.251 | 0.251 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.441 | 0.251 | 0.251 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.441 | 0.251 | 0.251 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.441 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.441 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.441 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.441 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.441 | 0.251 | 0.251 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.441 | 0.251 | 0.251 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.441 | 0.251 | 0.251 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.441 | 0.251 | 0.251 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4295_SHGC_0.25 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.441 | 0.251 | 0.251 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.441 | 0.251 | 0.251 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.441 | 0.251 | 0.251 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.441 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.441 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.441 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.441 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.441 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.4295_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.441 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.441 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 432.95 | 2.441 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.441 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.6442 | 1978.83 | 13147.70 | LightsWired | LTG_SCH_BASEMENT | 45.99 | 168.00 | 45.94 | 0.0000 | Y | 113.37 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 9.6995 | 67.07 | 650.56 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 6.26 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 9.6995 | 77.67 | 753.35 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.25 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 4.0903 | 94.76 | 387.59 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 1.87 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.7049 | 78.04 | 445.21 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.90 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 9.2569 | 188.86 | 1748.29 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.55 | 0.0000 | Y | 12.98 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 9.0417 | 1308.19 | 11828.20 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 55.43 | 0.0000 | Y | 123.08 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.4132 | 1863.81 | 8225.38 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 73.68 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.4132 | 1864.32 | 8227.62 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 73.70 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 4.4132 | 1557.62 | 6874.08 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 56.74 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.21 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.54 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.19 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.54 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.4132 | 220.77 | 974.32 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 8.73 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.52 | 0.0000 | Y | 28.54 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.52 | 0.0000 | Y | 28.54 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.7327 | 103.30 | 1212.04 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.34 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 4.4132 | 412.12 | 1818.79 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 15.01 |
Interior Lighting Total | 5.8432 | 11345.29 | 66293.22 | 389.85 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 11096.45 | AstronomicalClock | - | 83.77 | 83.77 | 174.49 | |
Exterior Lighting Total | 11096.45 | 174.49 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 407903.26 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 976253.81 | 2.96 | 976425.41 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10280.58 | 15788.18 | 12569.32 | 3218.85 | 0.80 | - | 1880.73 | 19.08 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10159.57 | 15599.97 | 12418.04 | 3181.93 | 0.80 | - | 1858.20 | 18.85 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 56458.06 | 87389.28 | 70002.15 | 17387.13 | 0.80 | - | 10444.65 | 105.94 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 64521.25 | 97519.95 | 76700.46 | 20819.49 | 0.79 | - | 11554.53 | 117.19 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9279.57 | 14233.18 | 11320.53 | 2912.64 | 0.80 | - | 1694.64 | 17.19 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9200.95 | 14111.02 | 11222.42 | 2888.60 | 0.80 | - | 1680.02 | 17.04 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2715.96 | 4173.44 | 3324.07 | 849.36 | 0.80 | - | 497.27 | 5.04 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2679.30 | 4116.54 | 3278.41 | 838.12 | 0.80 | - | 490.46 | 4.97 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 12299.72 | 18757.43 | 14854.19 | 3903.24 | 0.79 | - | 2228.31 | 22.60 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 706915.30 | 622114.62 | 401334.41 | 220780.22 | 0.65 | - | 75606.01 | 766.84 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 91161.11 | 64688.92 | 41041.02 | 23647.90 | 0.63 | - | 7608.06 | 77.17 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 8490.27 | 8533.40 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3453.19 | 3467.98 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1516.57 | 1523.81 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2195.77 | 2205.26 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1329.79 | 1335.37 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11668.37 | 11728.20 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10415.93 | 10464.81 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 28743.27 | 28881.90 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5708.36 | 6148.09 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5718.89 | 6159.43 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 32986.56 | 35527.58 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 33198.52 | 35755.86 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5686.64 | 6124.70 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5697.18 | 6136.05 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 12745.09 | 12800.47 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1781.74 | 1918.98 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1785.96 | 1923.52 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 8550.56 | 9209.16 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12287.01 | 12347.01 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12738.96 | 12802.15 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8874.41 | 8919.52 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8294.73 | 8329.66 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 167523.09 | 124590.16 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 16512.40 | 12280.59 | - |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 75921.46 | 3.40 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 54370.95 | 3.40 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.94 | 664.41 | 703.64 | 1.00 | 1.21 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.93 | 656.31 | 703.64 | 1.00 | 1.21 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.30 | 3732.11 | 703.64 | 1.00 | 0.97 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.66 | 3984.20 | 703.64 | 1.00 | 0.96 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.85 | 597.60 | 703.64 | 1.00 | 1.24 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.84 | 592.35 | 703.64 | 1.00 | 1.24 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.25 | 175.82 | 703.64 | 1.00 | 1.85 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.25 | 173.38 | 703.64 | 1.00 | 1.86 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.11 | 779.36 | 703.64 | 1.00 | 1.17 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 20.81 | 46630.39 | 2240.64 | 1.00 | 1.11 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 4.90 | 700.51 | 142.86 | 0.00 | 2.77 | General | ||
SWHSYS1 HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 3.87 | 553.22 | 142.86 | 0.00 | 2.84 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.034849 | 7109.91 | 204022.71 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003569 | 1064.04 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.034849 | 4922.43 | 141251.80 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYSLAUNDRY HPWH | WaterHeater:HeatPump:PumpedCondenser | 1.14 | 76665.80 | 0.80 | 48.89 | 1.71 |
SWHSYS1 HPWH | WaterHeater:HeatPump:PumpedCondenser | 2.84 | 62446.28 | 0.80 | 4.64 | 9.45 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 28012.36 | 28012.36 | 14.16 | 2.111 | 2.111 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 24.00 | 24.00 | 0.00936 | 28.79 | 0.01446 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4018.12 | 4018.12 | 59.91 | 0.303 | 0.303 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00915 | 34.40 | 0.01447 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3012.58 | 3012.58 | 38.79 | 0.227 | 0.227 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 24.00 | 24.00 | 0.00946 | 31.41 | 0.01447 | 0.092 | 0.00 |
MECH_FLR_1 | 2647.47 | 2647.47 | 16.12 | 0.199 | 0.199 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:40:00 | 24.00 | 24.00 | 0.00879 | 29.08 | 0.01446 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1426.07 | 1426.07 | 15.05 | 0.107 | 0.107 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.00 | 24.00 | 0.00889 | 31.64 | 0.01447 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44863.51 | 44863.51 | 574.88 | 3.381 | 3.381 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 24.00 | 24.00 | 0.00855 | 33.70 | 0.01447 | 0.000 | 0.00 |
CAFE_FLR_1 | 18105.30 | 18105.30 | 95.87 | 1.366 | 1.366 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 23.99 | 0.01029 | 34.40 | 0.01447 | 0.676 | 0.00 |
LOBBY_FLR_1 | 61340.25 | 61340.25 | 46.89 | 4.624 | 4.624 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 23.99 | 0.01007 | 34.40 | 0.01447 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 9298.47 | 9298.47 | 238.29 | 0.944 | 0.944 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00861 | 32.91 | 0.01447 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 9185.05 | 9185.05 | 235.41 | 0.933 | 0.933 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00862 | 32.75 | 0.01447 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 52233.78 | 52233.78 | 2129.92 | 5.304 | 5.304 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00853 | 34.40 | 0.01447 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 55757.51 | 55757.51 | 2272.98 | 5.662 | 5.662 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 21.11 | 21.11 | 0.00879 | 33.92 | 0.01447 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 8363.44 | 8363.44 | 214.33 | 0.849 | 0.849 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 21.11 | 21.11 | 0.00863 | 31.50 | 0.01447 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 8289.97 | 8289.97 | 212.47 | 0.842 | 0.842 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 21.11 | 21.11 | 0.00863 | 31.26 | 0.01447 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 15734.37 | 15734.37 | 40.41 | 1.186 | 1.186 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00974 | 34.21 | 0.01447 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2460.63 | 2460.63 | 63.06 | 0.250 | 0.250 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00861 | 32.91 | 0.01447 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2426.47 | 2426.47 | 62.19 | 0.246 | 0.246 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00861 | 32.91 | 0.01447 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10906.85 | 10906.85 | 444.62 | 1.108 | 1.108 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00869 | 34.40 | 0.01447 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29200.57 | 29200.57 | 88.04 | 2.203 | 2.203 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.98 | 0.01044 | 34.30 | 0.01447 | 1.188 | 0.00 |
DINING_FLR_6 | 30654.21 | 30654.21 | 92.43 | 2.313 | 2.313 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.98 | 0.01035 | 34.30 | 0.01447 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 29470.50 | 29470.50 | 285.28 | 2.227 | 2.227 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01015 | 33.55 | 0.01447 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9020.40 | 9020.40 | 21.89 | 0.680 | 0.680 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00908 | 34.40 | 0.01447 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 2504.52 | 2504.52 | 1.27 | 0.111 | 0.854 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2594.75 | 2594.75 | 38.69 | 0.115 | 0.115 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00787 | -6.30 | 0.00230 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 872.94 | 872.94 | 11.24 | 0.039 | 0.092 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00785 | -6.30 | 0.00230 | 0.092 | 0.00 |
MECH_FLR_1 | 1630.32 | 1630.32 | 9.93 | 0.072 | 0.072 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00781 | -6.30 | 0.00230 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1025.20 | 1025.20 | 10.82 | 0.046 | 0.058 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00783 | -6.30 | 0.00230 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2086.03 | 2086.03 | 26.73 | 0.093 | 0.093 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00780 | -6.30 | 0.00230 | 0.000 | 0.00 |
CAFE_FLR_1 | 6544.43 | 6544.43 | 34.65 | 0.291 | 0.676 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00789 | -6.30 | 0.00230 | 0.676 | 0.00 |
LOBBY_FLR_1 | 15634.25 | 15634.25 | 11.95 | 0.695 | 1.894 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00786 | -6.30 | 0.00230 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5708.38 | 5708.38 | 146.29 | 0.255 | 0.255 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.11 | 21.11 | 0.00786 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5718.91 | 5718.91 | 146.57 | 0.256 | 0.256 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.11 | 21.11 | 0.00786 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 32986.61 | 32986.61 | 1345.08 | 1.475 | 1.475 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.11 | 21.11 | 0.00788 | -6.30 | 0.00230 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 33198.57 | 33198.57 | 1353.36 | 1.485 | 1.485 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.11 | 21.11 | 0.00788 | -6.30 | 0.00230 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5686.66 | 5686.66 | 145.73 | 0.254 | 0.254 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.11 | 21.11 | 0.00786 | -6.30 | 0.00230 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5697.20 | 5697.20 | 146.02 | 0.255 | 0.255 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.11 | 21.11 | 0.00786 | -6.30 | 0.00230 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 9383.65 | 9383.65 | 24.10 | 0.417 | 0.475 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00790 | -6.30 | 0.00230 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1781.76 | 1781.76 | 45.66 | 0.080 | 0.080 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00789 | -6.30 | 0.00230 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1785.97 | 1785.97 | 45.77 | 0.080 | 0.080 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00789 | -6.30 | 0.00230 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8550.61 | 8550.61 | 348.57 | 0.382 | 0.382 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00790 | -6.30 | 0.00230 | 0.099 | 0.00 |
BANQUET_FLR_6 | 6040.72 | 6040.72 | 18.21 | 0.269 | 1.188 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00792 | -6.30 | 0.00230 | 1.188 | 0.00 |
DINING_FLR_6 | 6181.80 | 6181.80 | 18.64 | 0.275 | 1.188 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00792 | -6.30 | 0.00230 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 2570.92 | 2570.92 | 24.89 | 0.114 | 0.367 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00732 | -6.30 | 0.00230 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 6367.56 | 6367.56 | 15.45 | 0.283 | 0.283 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00793 | -6.30 | 0.00230 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 20.81 | 20.81 | 7.36 | 7.36 | 20.8112 | 11.6567 | 20.8112 | 0.5601 | 0.3000 |
FLR_3_DOAS | 15.52 | 2.05 | 4.52 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 8490.268 | 8490.268 | 1.175845 | 0.00007428 | 180.983 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8490.27 | 8490.27 | 1.175845 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00799922 | 49.8576 | 2504.52 | 0.00 | 8537.63 | 8537.63 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3453.186 | 3453.186 | 0.168683 | 0.00003021 | 85.682 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 3453.19 | 3453.19 | 0.168683 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00787050 | 49.0663 | 2594.75 | 0.00 | 3471.03 | 3471.03 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1516.565 | 1516.565 | 0.126471 | 0.00001327 | 34.033 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 1516.57 | 1516.57 | 0.126471 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00785191 | 48.9512 | 872.94 | 0.00 | 1524.77 | 1524.77 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2195.771 | 2195.771 | 0.111119 | 0.00001921 | 53.998 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 2195.77 | 2195.77 | 0.111119 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00781388 | 48.7171 | 1630.32 | 0.00 | 2207.15 | 2207.15 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1329.793 | 1329.793 | 0.059855 | 0.00001163 | 33.742 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 1329.79 | 1329.79 | 0.059855 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00782878 | 48.8088 | 1025.20 | 0.00 | 1336.62 | 1336.62 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11668.370 | 11668.370 | 1.883183 | 0.00010208 | 246.096 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 11668.37 | 11668.37 | 1.883183 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00780182 | 48.6434 | 2086.03 | 0.00 | 11733.69 | 11733.69 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 10415.930 | 10415.930 | 0.760720 | 0.00009112 | 238.270 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 10415.93 | 10415.93 | 0.760720 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00788618 | 49.1626 | 6544.43 | 0.00 | 10471.90 | 10471.90 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 28743.271 | 28743.271 | 2.575845 | 0.00025146 | 639.102 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 28743.27 | 28743.27 | 2.575845 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00786440 | 49.0281 | 15634.25 | 0.00 | 28899.37 | 28899.37 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 10280.576 | -999.000 | 0.944257 | 0.00036719 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 10280.58 | 10013.66 | 0.944257 | 21.70 | 15.30 | 0.00861408 | 12.80 | 11.77 | 0.00850000 | 32.91 | 0.01447054 | 23.14 | 0.0000 | 21.11 | 0.00861408 | 53.2748 | 9298.47 | 0.00 | 10643.62 | 10167.89 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5708.358 | 5708.358 | 0.255266 | 0.00004994 | 163.094 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 5708.36 | 5708.36 | 0.255266 | 21.11 | 14.41 | 0.00786428 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00786428 | 48.6949 | 5708.38 | 0.00 | 6153.78 | 6153.78 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 10159.566 | -999.000 | 0.932739 | 0.00036287 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 10159.57 | 9892.20 | 0.932739 | 21.70 | 15.30 | 0.00861568 | 12.80 | 11.77 | 0.00850000 | 32.75 | 0.01447025 | 23.10 | 0.0000 | 21.11 | 0.00861568 | 53.2845 | 9185.05 | 0.00 | 10518.27 | 10044.47 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5718.891 | 5718.891 | 0.255737 | 0.00005003 | 163.395 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 5718.89 | 5718.89 | 0.255737 | 21.11 | 14.41 | 0.00786453 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00786453 | 48.6964 | 5718.91 | 0.00 | 6165.13 | 6165.13 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 56458.057 | -999.000 | 5.304026 | 0.00201651 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 56458.06 | 56046.05 | 5.304026 | 21.70 | 15.23 | 0.00853146 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 0.0000 | 21.11 | 0.00853146 | 52.7692 | 52233.78 | 0.00 | 58473.47 | 56936.82 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 32986.557 | 32986.557 | 1.475107 | 0.00028858 | 942.459 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 32986.56 | 32986.56 | 1.475107 | 21.11 | 14.42 | 0.00787525 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00787525 | 48.7614 | 32986.61 | 0.00 | 35560.61 | 35560.61 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 64521.251 | -999.000 | 5.662293 | 0.00230451 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | unknown | 7/21 15:50:00 | 64521.25 | 60476.72 | 5.662293 | 21.70 | 15.45 | 0.00878622 | 12.80 | 11.77 | 0.00850000 | 33.92 | 0.01447239 | 23.42 | 0.0000 | 21.11 | 0.00878622 | 54.3252 | 55757.51 | 0.00 | 66773.16 | 61371.24 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 33198.519 | 33198.519 | 1.484585 | 0.00029044 | 948.515 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 33198.52 | 33198.52 | 1.484585 | 21.11 | 14.42 | 0.00787600 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00787600 | 48.7659 | 33198.57 | 0.00 | 35789.11 | 35789.11 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 9279.572 | -999.000 | 0.849306 | 0.00033144 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | 7/21 10:30:00 | 9279.57 | 9011.80 | 0.849306 | 21.70 | 15.31 | 0.00862717 | 12.80 | 11.77 | 0.00850000 | 31.50 | 0.01446797 | 22.76 | 0.0000 | 21.11 | 0.00862717 | 53.3546 | 8363.44 | 0.00 | 9606.71 | 9149.93 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5686.645 | 5686.645 | 0.254295 | 0.00004975 | 162.474 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 5686.64 | 5686.64 | 0.254295 | 21.11 | 14.41 | 0.00786378 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00786378 | 48.6918 | 5686.66 | 0.00 | 6130.37 | 6130.37 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 9200.948 | -999.000 | 0.841845 | 0.00032863 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | 7/21 10:20:00 | 9200.95 | 8933.08 | 0.841845 | 21.70 | 15.31 | 0.00862834 | 12.80 | 11.77 | 0.00850000 | 31.26 | 0.01446754 | 22.70 | 0.0000 | 21.11 | 0.00862834 | 53.3618 | 8289.97 | 0.00 | 9525.27 | 9069.94 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5697.184 | 5697.184 | 0.254766 | 0.00004984 | 162.775 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 5697.18 | 5697.18 | 0.254766 | 21.11 | 14.41 | 0.00786403 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00786403 | 48.6934 | 5697.20 | 0.00 | 6141.73 | 6141.73 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 12745.087 | 12745.087 | 0.660451 | 0.00011150 | 311.625 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12745.09 | 12745.09 | 0.660451 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00789895 | 49.2406 | 9383.65 | 0.00 | 12811.27 | 12811.27 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2715.961 | -999.000 | 0.249876 | 0.00009701 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 2715.96 | 2649.18 | 0.249876 | 21.70 | 15.29 | 0.00860790 | 12.80 | 11.77 | 0.00850000 | 32.91 | 0.01447054 | 23.14 | 0.0000 | 21.11 | 0.00860790 | 53.2370 | 2460.63 | 0.00 | 2811.95 | 2690.07 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1781.743 | 1781.743 | 0.079677 | 0.00001559 | 50.906 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1781.74 | 1781.74 | 0.079677 | 21.11 | 14.44 | 0.00789076 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00789076 | 48.8563 | 1781.76 | 0.00 | 1920.78 | 1920.78 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2679.297 | -999.000 | 0.246408 | 0.00009570 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 2679.30 | 2612.57 | 0.246408 | 21.70 | 15.29 | 0.00860932 | 12.80 | 11.77 | 0.00850000 | 32.91 | 0.01447054 | 23.14 | 0.0000 | 21.11 | 0.00860932 | 53.2457 | 2426.47 | 0.00 | 2773.97 | 2652.88 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1785.956 | 1785.956 | 0.079865 | 0.00001562 | 51.026 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1785.96 | 1785.96 | 0.079865 | 21.11 | 14.44 | 0.00789102 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00789102 | 48.8579 | 1785.97 | 0.00 | 1925.32 | 1925.32 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 12299.716 | -999.000 | 1.107614 | 0.00043931 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 12299.72 | 11782.64 | 1.107614 | 21.70 | 15.36 | 0.00868782 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 0.0000 | 21.11 | 0.00868782 | 53.7252 | 10906.85 | 0.00 | 12729.96 | 11959.26 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 8550.555 | 8550.555 | 0.382367 | 0.00007480 | 244.295 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8550.56 | 8550.56 | 0.382367 | 21.11 | 14.44 | 0.00789510 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.11 | 0.00789510 | 48.8827 | 8550.61 | 0.00 | 9217.78 | 9217.78 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12287.009 | 12287.009 | 1.227236 | 0.00010749 | 269.797 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 12287.01 | 12287.01 | 1.227236 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00792044 | 49.3731 | 6040.72 | 0.00 | 12354.08 | 12354.08 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12738.960 | 12738.960 | 1.288308 | 0.00011145 | 279.374 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 12738.96 | 12738.96 | 1.288308 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00792223 | 49.3841 | 6181.80 | 0.00 | 12809.44 | 12809.44 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 8874.414 | 8874.414 | 1.240313 | 0.00007764 | 189.042 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 8874.41 | 8874.41 | 1.240313 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00731827 | 45.6677 | 2570.92 | 0.00 | 8923.93 | 8923.93 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 8294.732 | 8294.732 | 0.378628 | 0.00007257 | 209.627 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 8294.73 | 8294.73 | 0.378628 | 16.70 | 12.85 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00793371 | 49.4547 | 6367.56 | 0.00 | 8337.35 | 8337.35 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 706915.305 | -999.000 | 20.811203 | 0.02524938 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 706915.30 | 465020.58 | 20.811203 | 29.82 | 20.89 | 0.01239925 | 10.92 | 10.92 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 56.0345 | 23.99 | 0.00975509 | 50.5528 | 275965.34 | 0.00 | 720864.92 | 462334.32 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 167523.090 | 167523.090 | 6.243361 | 0.00146557 | 2827.455 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 167523.09 | 167523.09 | 6.243361 | -6.30 | -6.30 | 0.00229779 | 16.70 | 12.85 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 186.7818 | 21.00 | 0.00788106 | 49.1188 | 63052.40 | 0.00 | 150655.17 | 150655.17 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 91161.109 | -999.000 | 2.051317 | 0.00325606 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 91161.11 | 55491.40 | 2.051317 | 34.40 | 23.54 | 0.01447326 | 11.91 | 11.41 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 99.9965 | 21.11 | 0.00866371 | 53.5771 | 152255.57 | 0.00 | 92644.03 | 56011.80 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 16512.404 | 16512.404 | 0.615395 | 0.00014446 | 278.696 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 16512.40 | 16512.40 | 0.615395 | -6.30 | -6.30 | 0.00229779 | 16.70 | 12.85 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 333.3216 | 21.11 | 0.00787572 | 48.7643 | 101114.54 | 0.00 | 14849.77 | 14849.77 |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 50306.711 | 37025.739 | 4.903586 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 75921.46 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 39757.721 | 29261.683 | 3.872570 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 54370.95 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 8490.268 | 8490.268 | 1.175845 | 0.00007428 | 180.983 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 2.0404 | 2.081441 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8490.27 | 8490.27 | 1.0000 | 1.36512860 | 1.175845 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.07426899 | 60.00 | 32.22 | 27.78 | 0.000 | 8490.27 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00799922 | 21.00 | 0.00799922 | 49.8576 | 2504.52 | 0.00 | 8537.63 | 8537.63 | 1.36512860 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.73 | 15.49 | 0.00800000 | 43188.8 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3453.186 | 3453.186 | 0.168683 | 0.00003021 | 85.682 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 0.8299 | 0.846570 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 3453.19 | 3453.19 | 1.0000 | 0.19583729 | 0.168683 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.03020690 | 60.00 | 32.22 | 27.78 | 0.000 | 3453.19 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00787050 | 21.00 | 0.00787050 | 49.0663 | 2594.75 | 0.00 | 3471.03 | 3471.03 | 0.19583729 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 33.98 | 19.34 | 0.00800000 | 54658.8 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1516.565 | 1516.565 | 0.126471 | 0.00001327 | 34.033 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 0.3645 | 0.371795 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 1516.57 | 1516.57 | 1.0000 | 0.14682966 | 0.126471 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01326622 | 60.00 | 32.22 | 27.78 | 0.000 | 1516.57 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00785191 | 21.00 | 0.00785191 | 48.9512 | 872.94 | 0.00 | 1524.77 | 1524.77 | 0.14682966 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.78 | 16.94 | 0.00800000 | 47319.4 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2195.771 | 2195.771 | 0.111119 | 0.00001921 | 53.998 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 0.5277 | 0.538307 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 2195.77 | 2195.77 | 1.0000 | 0.12900608 | 0.111119 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01920760 | 60.00 | 32.22 | 27.78 | 0.000 | 2195.77 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00781388 | 21.00 | 0.00781388 | 48.7171 | 1630.32 | 0.00 | 2207.15 | 2207.15 | 0.12900608 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 33.38 | 19.14 | 0.00800000 | 54043.6 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1329.793 | 1329.793 | 0.059855 | 0.00001163 | 33.742 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 0.3196 | 0.326007 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 1329.79 | 1329.79 | 1.0000 | 0.06949026 | 0.059855 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01163242 | 60.00 | 32.22 | 27.78 | 0.000 | 1329.79 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00782878 | 21.00 | 0.00782878 | 48.8088 | 1025.20 | 0.00 | 1336.62 | 1336.62 | 0.06949026 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.46 | 19.80 | 0.00800000 | 56169.4 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11668.370 | 11668.370 | 1.883183 | 0.00010208 | 246.096 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 2.8041 | 2.860573 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 11668.37 | 11668.37 | 1.0000 | 2.18633146 | 1.883183 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.10206958 | 60.00 | 32.22 | 27.78 | 0.000 | 11668.37 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00780182 | 21.00 | 0.00780182 | 48.6434 | 2086.03 | 0.00 | 11733.69 | 11733.69 | 2.18633146 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.86 | 15.17 | 0.00800000 | 42301.6 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10415.930 | 10415.930 | 0.760720 | 0.00009112 | 238.270 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 2.5032 | 2.553529 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 10415.93 | 10415.93 | 1.0000 | 0.88317773 | 0.760720 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.09111380 | 60.00 | 32.22 | 27.78 | 0.000 | 10415.93 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00788618 | 21.00 | 0.00788618 | 49.1626 | 6544.43 | 0.00 | 10471.90 | 10471.90 | 0.88317773 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.23 | 17.44 | 0.00800000 | 48791.8 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 28743.271 | 28743.271 | 2.575845 | 0.00025146 | 639.102 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 6.9076 | 7.046590 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 28743.27 | 28743.27 | 1.0000 | 2.99049594 | 2.575845 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.25143302 | 60.00 | 32.22 | 27.78 | 0.000 | 28743.27 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00786440 | 21.00 | 0.00786440 | 49.0281 | 15634.25 | 0.00 | 28899.37 | 28899.37 | 2.99049594 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.08 | 16.69 | 0.00800000 | 46598.5 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10280.576 | -999.000 | 0.944257 | 0.00036719 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8532 | 1004.8586 | 1.1610 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.944257 | 1.09626025 | 4197.9300 | 999.8980 | 34.84504689 | 13.37 | 6.70 | 6.67 | 975668.04 | 1.0537 | 1.053676 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 10280.58 | 10013.66 | 1.0000 | 1.09626025 | 0.944257 | 21.70 | 15.30 | 0.00861408 | 43700.1 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.36715403 | 6.70 | 13.37 | 6.67 | 0.000 | 10280.58 | 32.91 | 0.01447054 | 23.14 | 0.00000000 | 0.0000 | 21.11 | 0.00861408 | 21.11 | 0.00861408 | 53.2748 | 9298.47 | 0.00 | 10643.62 | 10167.89 | 1.09626025 | 21.70 | 15.66 | 0.00861408 | 43700.1 | 12.62 | 11.97 | 0.00844218 | 33991.0 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5708.358 | 5708.358 | 0.255266 | 0.00004994 | 163.094 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.944257 | 1.09626025 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 1.3718 | 1.399439 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 5708.36 | 5708.36 | 1.0000 | 0.29635806 | 0.255266 | 21.11 | 14.41 | 0.00786428 | 41189.5 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.04993411 | 60.00 | 32.22 | 27.78 | 0.000 | 5708.36 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00786428 | 21.11 | 0.00786428 | 48.6949 | 5708.38 | 0.00 | 6153.78 | 6153.78 | 0.29635806 | 16.60 | 13.02 | 0.00786428 | 36591.1 | 36.97 | 20.17 | 0.00786428 | 57355.8 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10159.566 | -999.000 | 0.932739 | 0.00036287 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8561 | 1004.8586 | 1.1610 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.932739 | 1.08288846 | 4197.9300 | 999.8980 | 34.84504689 | 13.37 | 6.70 | 6.67 | 975668.04 | 1.0413 | 1.041274 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | Sensible | 10159.57 | 9892.20 | 1.0000 | 1.08288846 | 0.932739 | 21.70 | 15.30 | 0.00861568 | 43704.1 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.36283235 | 6.70 | 13.37 | 6.67 | 0.000 | 10159.57 | 32.75 | 0.01447025 | 23.10 | 0.00000000 | 0.0000 | 21.11 | 0.00861568 | 21.11 | 0.00861568 | 53.2845 | 9185.05 | 0.00 | 10518.27 | 10044.47 | 1.08288846 | 21.70 | 15.66 | 0.00861568 | 43704.1 | 12.62 | 11.97 | 0.00844236 | 33991.0 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5718.891 | 5718.891 | 0.255737 | 0.00005003 | 163.395 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.932739 | 1.08288846 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 1.3744 | 1.402021 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 5718.89 | 5718.89 | 1.0000 | 0.29690486 | 0.255737 | 21.11 | 14.41 | 0.00786453 | 41190.2 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.05002625 | 60.00 | 32.22 | 27.78 | 0.000 | 5718.89 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00786453 | 21.11 | 0.00786453 | 48.6964 | 5718.91 | 0.00 | 6165.13 | 6165.13 | 0.29690486 | 16.60 | 13.02 | 0.00786453 | 36591.8 | 36.97 | 20.17 | 0.00786453 | 57356.4 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 56458.057 | -999.000 | 5.304026 | 0.00201651 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6996 | 1004.8586 | 1.1610 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.304026 | 6.15784982 | 4197.9300 | 999.8980 | 34.84504689 | 13.37 | 6.70 | 6.67 | 975668.04 | 5.7866 | 5.786497 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 56458.06 | 56046.05 | 1.0000 | 6.15784982 | 5.304026 | 21.70 | 15.23 | 0.00853146 | 43490.7 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 2.01630763 | 6.70 | 13.37 | 6.67 | 0.000 | 56458.06 | 34.40 | 0.01447326 | 23.54 | 0.00000000 | 0.0000 | 21.11 | 0.00853146 | 21.11 | 0.00853146 | 52.7692 | 52233.78 | 0.00 | 58473.47 | 56936.82 | 6.15784982 | 21.70 | 15.59 | 0.00853146 | 43490.7 | 12.65 | 11.97 | 0.00843261 | 33994.9 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 32986.557 | 32986.557 | 1.475107 | 0.00028858 | 942.459 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.304026 | 6.15784982 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 7.9273 | 8.086858 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 32986.56 | 32986.56 | 1.0000 | 1.71256418 | 1.475107 | 21.11 | 14.42 | 0.00787525 | 41217.6 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.28855135 | 60.00 | 32.22 | 27.78 | 0.000 | 32986.56 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00787525 | 21.11 | 0.00787525 | 48.7614 | 32986.61 | 0.00 | 35560.61 | 35560.61 | 1.71256418 | 16.60 | 13.03 | 0.00787525 | 36618.9 | 36.97 | 20.17 | 0.00787525 | 57383.4 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 64521.251 | -999.000 | 5.662293 | 0.00230451 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1731 | 1004.8586 | 1.1610 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.662293 | 6.57378927 | 4197.9300 | 999.8980 | 34.84504689 | 13.37 | 6.70 | 6.67 | 975668.04 | 6.6130 | 6.612910 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | unknown | unknown | unknown | 7/21 15:50:00 | Sensible | 64521.25 | 60476.72 | 1.0000 | 6.57378927 | 5.662293 | 21.70 | 15.45 | 0.00878622 | 44137.1 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 2.30427148 | 6.70 | 13.37 | 6.67 | 0.000 | 64521.25 | 33.92 | 0.01447239 | 23.42 | 0.00000000 | 0.0000 | 21.11 | 0.00878622 | 21.11 | 0.00878622 | 54.3252 | 55757.51 | 0.00 | 66773.16 | 61371.24 | 6.57378927 | 21.70 | 15.81 | 0.00878622 | 44137.1 | 12.56 | 11.96 | 0.00846069 | 33979.6 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 33198.519 | 33198.519 | 1.484585 | 0.00029044 | 948.515 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.662293 | 6.57378927 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 7.9783 | 8.138822 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 33198.52 | 33198.52 | 1.0000 | 1.72356866 | 1.484585 | 21.11 | 14.42 | 0.00787600 | 41219.5 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.29040550 | 60.00 | 32.22 | 27.78 | 0.000 | 33198.52 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00787600 | 21.11 | 0.00787600 | 48.7659 | 33198.57 | 0.00 | 35789.11 | 35789.11 | 1.72356866 | 16.60 | 13.03 | 0.00787600 | 36620.8 | 36.97 | 20.18 | 0.00787600 | 57385.3 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9279.572 | -999.000 | 0.849306 | 0.00033144 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8775 | 1004.8586 | 1.1610 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.849306 | 0.98602483 | 4197.9300 | 999.8980 | 34.84504689 | 13.37 | 6.70 | 6.67 | 975668.04 | 0.9511 | 0.951082 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | unknown | unknown | 7/21 10:30:00 | Sensible | 9279.57 | 9011.80 | 1.0000 | 0.98602483 | 0.849306 | 21.70 | 15.31 | 0.00862717 | 43733.3 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.33140481 | 6.70 | 13.37 | 6.67 | 0.000 | 9279.57 | 31.50 | 0.01446797 | 22.76 | 0.00000000 | 0.0000 | 21.11 | 0.00862717 | 21.11 | 0.00862717 | 53.3546 | 8363.44 | 0.00 | 9606.71 | 9149.93 | 0.98602483 | 21.70 | 15.67 | 0.00862717 | 43733.3 | 12.61 | 11.97 | 0.00844366 | 33990.4 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5686.645 | 5686.645 | 0.254295 | 0.00004975 | 162.474 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.849306 | 0.98602483 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 1.3666 | 1.394116 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 5686.64 | 5686.64 | 1.0000 | 0.29523075 | 0.254295 | 21.11 | 14.41 | 0.00786378 | 41188.3 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.04974417 | 60.00 | 32.22 | 27.78 | 0.000 | 5686.64 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00786378 | 21.11 | 0.00786378 | 48.6918 | 5686.66 | 0.00 | 6130.37 | 6130.37 | 0.29523075 | 16.60 | 13.02 | 0.00786378 | 36589.8 | 36.97 | 20.17 | 0.00786378 | 57354.5 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9200.948 | -999.000 | 0.841845 | 0.00032863 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8796 | 1004.8586 | 1.1610 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.841845 | 0.97736266 | 4197.9300 | 999.8980 | 34.84504689 | 13.37 | 6.70 | 6.67 | 975668.04 | 0.9430 | 0.943023 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | unknown | unknown | 7/21 10:20:00 | Sensible | 9200.95 | 8933.08 | 1.0000 | 0.97736266 | 0.841845 | 21.70 | 15.31 | 0.00862834 | 43736.3 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.32859690 | 6.70 | 13.37 | 6.67 | 0.000 | 9200.95 | 31.26 | 0.01446754 | 22.70 | 0.00000000 | 0.0000 | 21.11 | 0.00862834 | 21.11 | 0.00862834 | 53.3618 | 8289.97 | 0.00 | 9525.27 | 9069.94 | 0.97736266 | 21.70 | 15.68 | 0.00862834 | 43736.3 | 12.61 | 11.97 | 0.00844379 | 33990.4 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5697.184 | 5697.184 | 0.254766 | 0.00004984 | 162.775 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.841845 | 0.97736266 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 1.3691 | 1.396700 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 5697.18 | 5697.18 | 1.0000 | 0.29577791 | 0.254766 | 21.11 | 14.41 | 0.00786403 | 41188.9 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.04983636 | 60.00 | 32.22 | 27.78 | 0.000 | 5697.18 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00786403 | 21.11 | 0.00786403 | 48.6934 | 5697.20 | 0.00 | 6141.73 | 6141.73 | 0.29577791 | 16.60 | 13.02 | 0.00786403 | 36590.5 | 36.97 | 20.17 | 0.00786403 | 57355.2 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12745.087 | 12745.087 | 0.660451 | 0.00011150 | 311.625 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 3.0629 | 3.124537 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 12745.09 | 12745.09 | 1.0000 | 0.76676771 | 0.660451 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.11148821 | 60.00 | 32.22 | 27.78 | 0.000 | 12745.09 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00789895 | 21.00 | 0.00789895 | 49.2406 | 9383.65 | 0.00 | 12811.27 | 12811.27 | 0.76676771 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.99 | 19.02 | 0.00800000 | 53642.9 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2715.961 | -999.000 | 0.249876 | 0.00009701 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8417 | 1004.8586 | 1.1610 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.249876 | 0.29010004 | 4197.9300 | 999.8980 | 34.84504689 | 13.37 | 6.70 | 6.67 | 975668.04 | 0.2784 | 0.278364 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 2715.96 | 2649.18 | 1.0000 | 0.29010004 | 0.249876 | 21.70 | 15.29 | 0.00860790 | 43684.3 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.09699614 | 6.70 | 13.37 | 6.67 | 0.000 | 2715.96 | 32.91 | 0.01447054 | 23.14 | 0.00000000 | 0.0000 | 21.11 | 0.00860790 | 21.11 | 0.00860790 | 53.2370 | 2460.63 | 0.00 | 2811.95 | 2690.07 | 0.29010004 | 21.70 | 15.66 | 0.00860790 | 43684.3 | 12.62 | 11.97 | 0.00844147 | 33991.3 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1781.743 | 1781.743 | 0.079677 | 0.00001559 | 50.906 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.249876 | 0.29010004 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 0.4282 | 0.436805 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 1781.74 | 1781.74 | 1.0000 | 0.09250266 | 0.079677 | 21.11 | 14.44 | 0.00789076 | 41257.0 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01558587 | 60.00 | 32.22 | 27.78 | 0.000 | 1781.74 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00789076 | 21.11 | 0.00789076 | 48.8563 | 1781.76 | 0.00 | 1920.78 | 1920.78 | 0.09250266 | 16.60 | 13.04 | 0.00789076 | 36658.1 | 36.97 | 20.19 | 0.00789076 | 57422.7 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2679.297 | -999.000 | 0.246408 | 0.00009570 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8443 | 1004.8586 | 1.1610 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.246408 | 0.28607336 | 4197.9300 | 999.8980 | 34.84504689 | 13.37 | 6.70 | 6.67 | 975668.04 | 0.2746 | 0.274606 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 2679.30 | 2612.57 | 1.0000 | 0.28607336 | 0.246408 | 21.70 | 15.29 | 0.00860932 | 43688.0 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.09568674 | 6.70 | 13.37 | 6.67 | 0.000 | 2679.30 | 32.91 | 0.01447054 | 23.14 | 0.00000000 | 0.0000 | 21.11 | 0.00860932 | 21.11 | 0.00860932 | 53.2457 | 2426.47 | 0.00 | 2773.97 | 2652.88 | 0.28607336 | 21.70 | 15.66 | 0.00860932 | 43688.0 | 12.62 | 11.97 | 0.00844164 | 33991.2 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1785.956 | 1785.956 | 0.079865 | 0.00001562 | 51.026 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.246408 | 0.28607336 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 0.4292 | 0.437838 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 1785.96 | 1785.96 | 1.0000 | 0.09272139 | 0.079865 | 21.11 | 14.44 | 0.00789102 | 41257.6 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.01562273 | 60.00 | 32.22 | 27.78 | 0.000 | 1785.96 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00789102 | 21.11 | 0.00789102 | 48.8579 | 1785.97 | 0.00 | 1925.32 | 1925.32 | 0.09272139 | 16.60 | 13.04 | 0.00789102 | 36658.8 | 36.97 | 20.19 | 0.00789102 | 57423.4 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12299.716 | -999.000 | 1.107614 | 0.00043931 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9902 | 1004.8586 | 1.1610 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.107614 | 1.28591389 | 4197.9300 | 999.8980 | 34.84504689 | 13.37 | 6.70 | 6.67 | 975668.04 | 1.2606 | 1.260622 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 12299.72 | 11782.64 | 1.0000 | 1.28591389 | 1.107614 | 21.70 | 15.36 | 0.00868782 | 43887.2 | 12.80 | 11.77 | 0.00850000 | 34322.2 | 0.43926433 | 6.70 | 13.37 | 6.67 | 0.000 | 12299.72 | 34.40 | 0.01447326 | 23.54 | 0.00000000 | 0.0000 | 21.11 | 0.00868782 | 21.11 | 0.00868782 | 53.7252 | 10906.85 | 0.00 | 12729.96 | 11959.26 | 1.28591389 | 21.70 | 15.73 | 0.00868782 | 43887.2 | 12.59 | 11.97 | 0.00845040 | 33987.6 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8550.555 | 8550.555 | 0.382367 | 0.00007480 | 244.295 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.107614 | 1.28591389 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 2.0549 | 2.096221 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 8550.56 | 8550.56 | 1.0000 | 0.44391967 | 0.382367 | 21.11 | 14.44 | 0.00789510 | 41268.0 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.07479636 | 60.00 | 32.22 | 27.78 | 0.000 | 8550.56 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00789510 | 21.11 | 0.00789510 | 48.8827 | 8550.61 | 0.00 | 9217.78 | 9217.78 | 0.44391967 | 16.60 | 13.05 | 0.00789510 | 36669.1 | 36.97 | 20.19 | 0.00789510 | 57433.7 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12287.009 | 12287.009 | 1.227236 | 0.00010749 | 269.797 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 2.9528 | 3.012236 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 12287.01 | 12287.01 | 1.0000 | 1.42479214 | 1.227236 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.10748115 | 60.00 | 32.22 | 27.78 | 0.000 | 12287.01 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00792044 | 21.00 | 0.00792044 | 49.3731 | 6040.72 | 0.00 | 12354.08 | 12354.08 | 1.42479214 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.10 | 16.35 | 0.00800000 | 45605.5 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12738.960 | 12738.960 | 1.288308 | 0.00011145 | 279.374 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 3.0614 | 3.123035 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 12738.96 | 12738.96 | 1.0000 | 1.49569525 | 1.288308 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.11143461 | 60.00 | 32.22 | 27.78 | 0.000 | 12738.96 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00792223 | 21.00 | 0.00792223 | 49.3841 | 6181.80 | 0.00 | 12809.44 | 12809.44 | 1.49569525 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.00 | 16.31 | 0.00800000 | 45498.9 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8874.414 | 8874.414 | 1.240313 | 0.00007764 | 189.042 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 2.1327 | 2.175617 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 8874.41 | 8874.41 | 1.0000 | 1.43997468 | 1.240313 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.07762933 | 60.00 | 32.22 | 27.78 | 0.000 | 8874.41 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.61 | 0.00731827 | 21.00 | 0.00731827 | 45.6677 | 2570.92 | 0.00 | 8923.93 | 8923.93 | 1.43997468 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.68 | 15.47 | 0.00800000 | 43132.0 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8294.732 | 8294.732 | 0.378628 | 0.00007257 | 209.627 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 1.9934 | 2.033505 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 8294.73 | 8294.73 | 1.0000 | 0.43957836 | 0.378628 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 40.00 | 20.76 | 0.00800000 | 60796.0 | 0.07255853 | 60.00 | 32.22 | 27.78 | 0.000 | 8294.73 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00793371 | 21.00 | 0.00793371 | 49.4547 | 6367.56 | 0.00 | 8337.35 | 8337.35 | 0.43957836 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.20 | 19.72 | 0.00800000 | 55901.4 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 706915.305 | -999.000 | 20.811203 | 0.02524938 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.8896 | 1004.8586 | 1.1610 | VAV WITH REHEAT FAN | Fan:VariableVolume | 20.811203 | 24.16131879 | 4197.9300 | 999.8980 | 34.84504689 | 13.37 | 6.70 | 6.67 | 975668.04 | 72.4545 | 72.454490 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 706915.30 | 465020.58 | 1.0000 | 24.16131879 | 20.811203 | 29.82 | 20.89 | 0.01239925 | 61664.0 | 10.92 | 10.92 | 0.00850000 | 32405.8 | 25.24680105 | 6.70 | 13.37 | 6.67 | 46630.386 | 660284.92 | 34.40 | 0.01447326 | 23.54 | 11.66146000 | 56.0345 | 23.99 | 0.00975589 | 23.99 | 0.00975509 | 50.5528 | 275965.34 | 0.00 | 720864.92 | 462334.32 | 24.16131879 | 29.82 | 21.32 | 0.01239925 | 61664.0 | 11.21 | 11.08 | 0.00815613 | 31828.5 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 167523.090 | 167523.090 | 6.243361 | 0.00146557 | 2827.455 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | VAV WITH REHEAT FAN | Fan:VariableVolume | 20.811203 | 24.16131879 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 40.2591 | 41.069319 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 167523.09 | 167523.09 | 1.0000 | 7.24839564 | 6.243361 | -6.30 | -6.30 | 0.00229779 | -610.8 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 1.46541557 | 60.00 | 32.22 | 27.78 | 0.000 | 167523.09 | -6.30 | 0.00229779 | -6.30 | 11.66146000 | 186.7818 | 20.98 | 0.00787744 | 21.00 | 0.00788106 | 49.1188 | 63052.40 | 0.00 | 150655.17 | 150655.17 | 7.24839564 | 2.80 | -0.72 | 0.00229779 | 8572.2 | 23.40 | 10.14 | 0.00229779 | 29356.8 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 91161.109 | -999.000 | 2.051317 | 0.00325606 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1031.7451 | 1004.8586 | 1.1610 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.38144746 | 4197.9300 | 999.8980 | 34.84504689 | 13.37 | 6.70 | 6.67 | 975668.04 | 9.3435 | 9.343455 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 91161.11 | 55491.40 | 1.0000 | 2.38153119 | 2.051317 | 34.40 | 23.54 | 0.01447326 | 71688.8 | 11.91 | 11.41 | 0.00850000 | 33410.4 | 3.25573143 | 6.70 | 13.37 | 6.67 | 2195.006 | 88966.10 | 34.40 | 0.01447326 | 23.54 | 2.05124512 | 99.9965 | 21.11 | 0.00866026 | 21.11 | 0.00866371 | 53.5771 | 152255.57 | 0.00 | 92644.03 | 56011.80 | 2.38153119 | 34.40 | 23.99 | 0.01447326 | 71688.8 | 11.60 | 11.47 | 0.00837545 | 32787.8 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 16512.404 | 16512.404 | 0.615395 | 0.00014446 | 278.696 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.38144746 | 4197.9300 | 999.8980 | 3.56815162 | 54.44 | 82.22 | 27.78 | 416112.47 | 3.9683 | 4.048118 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 16512.40 | 16512.40 | 1.0000 | 0.71445936 | 0.615395 | -6.30 | -6.30 | 0.00229779 | -610.8 | 16.70 | 12.85 | 0.00800000 | 37036.7 | 0.14444298 | 60.00 | 32.22 | 27.78 | 0.000 | 16512.40 | -6.30 | 0.00229779 | -6.30 | 2.05124512 | 333.3216 | 21.11 | 0.00787522 | 21.11 | 0.00787572 | 48.7643 | 101114.54 | 0.00 | 14849.77 | 14849.77 | 0.71445936 | 2.80 | -0.72 | 0.00229779 | 8572.2 | 23.40 | 10.14 | 0.00229779 | 29356.8 | |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 50306.711 | 37025.739 | 4.903586 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 1.1610 | SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 4.903586 | 5.69294889 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 75921.46 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 75921.46 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 39757.721 | 29261.683 | 3.872570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 1.1610 | SWHSYS1 HPWH FAN | Fan:SystemModel | 3.872570 | 4.49596240 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 54370.95 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54370.95 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 20.81 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 892.00 | 6820.33 | 216.00 |
RETAIL_1_FLR_1 | 2615.33 | 5817.83 | 553.83 |
RETAIL_2_FLR_1 | 2239.00 | 6195.17 | 752.50 |
MECH_FLR_1 | 1579.50 | 6650.33 | 562.33 |
STORAGE_FLR_1 | 1208.00 | 6947.00 | 639.17 |
LAUNDRY_FLR_1 | 7087.50 | 3456.33 | 2790.50 |
CAFE_FLR_1 | 4133.17 | 5566.33 | 1847.50 |
LOBBY_FLR_1 | 3318.50 | 5718.17 | 1520.67 |
ROOM_1_FLR_3 | 896.50 | 8202.17 | 884.17 |
ROOM_2_FLR_3 | 1786.83 | 8041.50 | 1678.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 962.33 | 8744.50 | 961.33 |
ROOM_5_FLR_3 | 853.83 | 8056.33 | 851.83 |
ROOM_6_FLR_3 | 1754.33 | 8003.00 | 1650.50 |
CORRIDOR_FLR_3 | 1768.33 | 7601.83 | 1505.50 |
ROOM_1_FLR_6 | 1657.17 | 8054.67 | 1607.17 |
ROOM_2_FLR_6 | 2546.67 | 7918.33 | 2404.50 |
ROOM_3_MULT9_FLR_6 | 572.33 | 8158.83 | 547.50 |
BANQUET_FLR_6 | 5152.00 | 3851.17 | 1639.83 |
DINING_FLR_6 | 5753.17 | 2964.17 | 1474.67 |
KITCHEN_FLR_6 | 8197.17 | 6552.33 | 6314.33 |
CORRIDOR_FLR_6 | 2201.50 | 6290.50 | 542.00 |
Facility | 8670.00 | 8760.00 | 7940.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.33 | 0.00 | 0.33 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 6.83 | 0.00 | 6.83 |
ROOM_2_FLR_3 | 0.00 | 14.00 | 0.00 | 14.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 47.33 | 0.00 | 47.33 |
ROOM_5_FLR_3 | 0.00 | 5.00 | 0.00 | 5.00 |
ROOM_6_FLR_3 | 0.00 | 41.67 | 0.00 | 41.67 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 11.50 | 0.00 | 11.50 |
ROOM_2_FLR_6 | 0.00 | 15.83 | 0.00 | 15.83 |
ROOM_3_MULT9_FLR_6 | 0.00 | 23.33 | 0.00 | 23.33 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 17.50 | 0.00 | 17.50 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 109.00 | 0.00 | 109.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 0.880 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.276 | 0.034 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.484 | 0.011 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.607 | 0.013 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.564 | 0.013 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 24.190 | 0.036 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 3.734 | 0.027 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 1.838 | 0.011 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.044 | 0.000 | 0.068 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.044 | 0.000 | 0.069 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.403 | 0.019 | 0.000 | 0.109 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.044 | 0.000 | 0.068 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.044 | 0.000 | 0.069 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.492 | 0.005 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.355 | 0.044 | 0.000 | 0.081 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.044 | 0.000 | 0.081 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.403 | 0.036 | 0.000 | 0.130 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.971 | 0.013 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 5.330 | 0.013 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 21.225 | 0.036 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.074 | 0.009 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 0.561 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.771 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.378 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.572 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.467 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 16.845 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 3.054 | 0.000 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 1.645 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.000 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.360 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.156 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.373 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 12.589 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.857 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.79 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.56 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.09 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.25 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 36587493.46 | 0.00 | 36587493.46 | 0.00 | 36587493.46 | 26946214.98 | 15.67 | 3.83 | 8740.50 | 0.00 |
RETAIL_1_FLR_1 | 5218996.84 | 0.00 | 5218996.84 | 77555.21 | 5296552.05 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3932376.70 | 0.00 | 3932376.70 | 29936.41 | 3962313.11 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 3411942.37 | 0.00 | 3411942.37 | 70751.89 | 3482694.26 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1826992.86 | 0.00 | 1826992.86 | 40819.94 | 1867812.80 | 1821682.01 | 3267.94 | 2099.49 | 3392.58 | 0.00 |
LAUNDRY_FLR_1 | 64466553.41 | 0.00 | 64466553.41 | 96608.09 | 64563161.51 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 24007022.30 | 0.00 | 24007022.30 | 171440.19 | 24178462.49 | 21330615.53 | 7.83 | 1.83 | 8750.33 | 0.00 |
LOBBY_FLR_1 | 81851990.95 | 0.00 | 81851990.95 | 489843.78 | 82341834.73 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 69954.62 | 1530111.34 | 45015.29 | 1575126.63 | 1946875.62 | 2190.00 | 5688.17 | 881.83 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 70916.23 | 1530901.87 | 45011.86 | 1575913.73 | 1946647.51 | 2190.00 | 5696.22 | 873.78 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 3225.67 | 1103137.64 | 12559.77 | 1115697.41 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 396.00 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 69808.60 | 19873637.89 | 12563.21 | 19886201.10 | 26405105.73 | 2190.00 | 5735.66 | 834.34 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 69977.96 | 1530134.68 | 45015.29 | 1575149.97 | 1946875.62 | 2190.00 | 5688.17 | 881.83 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 70315.10 | 1530300.73 | 45011.86 | 1575312.59 | 1946647.51 | 2190.00 | 5688.25 | 881.75 | 0.00 |
CORRIDOR_FLR_3 | 20154874.93 | 0.00 | 20154874.93 | 54432.55 | 20209307.48 | 14972100.18 | 1.00 | 2.00 | 8757.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 83649.95 | 448689.13 | 45024.55 | 493713.68 | 486718.90 | 1994.58 | 5687.87 | 1077.55 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 82639.43 | 447635.83 | 45021.12 | 492656.95 | 486661.88 | 1996.00 | 5702.95 | 1061.05 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 83756.38 | 2428946.69 | 23036.14 | 2451982.83 | 3126920.42 | 2190.00 | 5684.17 | 885.83 | 0.00 |
BANQUET_FLR_6 | 43065993.75 | 0.00 | 43065993.75 | 109938.64 | 43175932.39 | 37458366.31 | 997.04 | 1275.74 | 6487.22 | 0.00 |
DINING_FLR_6 | 46170745.17 | 0.00 | 46170745.17 | 109938.64 | 46280683.81 | 37458366.31 | 0.00 | 2.83 | 8757.17 | 0.00 |
KITCHEN_FLR_6 | 57302577.38 | 0.00 | 57302577.38 | 98420.57 | 57400997.95 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 11647533.67 | 0.00 | 11647533.67 | 96328.56 | 11743862.23 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 7595356.68 | 0.21E+10 | 4536246.56 | 0.21E+10 | 0.43E+10 | 8760.00 | 6739.80 | 8760.00 | 396.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.1602 | 0.0000 | 1.1602 | 0.0000 | 1.1602 | 0.8545 | 15.67 | 3.83 | 8740.50 |
RETAIL_1_FLR_1 | 0.1655 | 0.0000 | 0.1655 | 0.0025 | 0.1680 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1247 | 0.0000 | 0.1247 | 0.0009 | 0.1256 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.1082 | 0.0000 | 0.1082 | 0.0022 | 0.1104 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0579 | 0.0000 | 0.0579 | 0.0013 | 0.0592 | 0.0578 | 3267.94 | 2099.49 | 3392.58 |
LAUNDRY_FLR_1 | 2.0442 | 0.0000 | 2.0442 | 0.0031 | 2.0473 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7613 | 0.0000 | 0.7613 | 0.0054 | 0.7667 | 0.6764 | 7.83 | 1.83 | 8750.33 |
LOBBY_FLR_1 | 2.5955 | 0.0000 | 2.5955 | 0.0155 | 2.6110 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0022 | 0.0485 | 0.0014 | 0.0499 | 0.0617 | 2190.00 | 5688.17 | 881.83 |
ROOM_2_FLR_3 | 0.0463 | 0.0022 | 0.0485 | 0.0014 | 0.0500 | 0.0617 | 2190.00 | 5696.22 | 873.78 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0022 | 0.6302 | 0.0004 | 0.6306 | 0.8373 | 2190.00 | 5735.66 | 834.34 |
ROOM_5_FLR_3 | 0.0463 | 0.0022 | 0.0485 | 0.0014 | 0.0499 | 0.0617 | 2190.00 | 5688.17 | 881.83 |
ROOM_6_FLR_3 | 0.0463 | 0.0022 | 0.0485 | 0.0014 | 0.0500 | 0.0617 | 2190.00 | 5688.25 | 881.75 |
CORRIDOR_FLR_3 | 0.6391 | 0.0000 | 0.6391 | 0.0017 | 0.6408 | 0.4748 | 1.00 | 2.00 | 8757.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0027 | 0.0142 | 0.0014 | 0.0157 | 0.0154 | 1994.58 | 5687.87 | 1077.55 |
ROOM_2_FLR_6 | 0.0116 | 0.0026 | 0.0142 | 0.0014 | 0.0156 | 0.0154 | 1996.00 | 5702.95 | 1061.05 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0027 | 0.0770 | 0.0007 | 0.0778 | 0.0992 | 2190.00 | 5684.17 | 885.83 |
BANQUET_FLR_6 | 1.3656 | 0.0000 | 1.3656 | 0.0035 | 1.3691 | 1.1878 | 997.04 | 1275.74 | 6487.22 |
DINING_FLR_6 | 1.4641 | 0.0000 | 1.4641 | 0.0035 | 1.4676 | 1.1878 | 0.00 | 2.83 | 8757.17 |
KITCHEN_FLR_6 | 1.8171 | 0.0000 | 1.8171 | 0.0031 | 1.8202 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3693 | 0.0000 | 0.3693 | 0.0031 | 0.3724 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 63.7493 | 0.2331 | 63.9824 | 0.1136 | 64.0960 | 73.9670 | 8760.00 | 6739.80 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.54E+09 | 0.00 | 0.54E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 40192371.46 | 604243.93 | 40796615.39 | 64690340.46 | 8759.50 | 0.17 | 0.33 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 17.0810 | 0.0000 | 17.0810 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.2745 | 0.0192 | 1.2937 | 2.0513 | 8759.50 | 0.17 | 0.33 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 3965.81 | 0.00 | 0.00 | 0.00 | 4794.19 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 17.3619 | 0.0000 | 0.0000 | 0.0000 | 16.8522 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.6099 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1363 |
Defaulted Fields | 1208 |
Fields with Defaults | 4115 |
Autosized Fields | 353 |
Autosizable Fields | 407 |
Autocalculated Fields | 289 |
Autocalculatable Fields | 549 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 6148.32 | 68811.96 | 01-NOV-01:50 | 445032.98 | 02-AUG-19:50 |
Electricity:Building | 2339.36 | 31015.39 | 02-JAN-02:10 | 138695.41 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 256.48 | 3058.02 | 02-JAN-02:10 | 18903.76 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2332.27 | 30874.25 | 02-JAN-02:10 | 138454.08 | 02-JAN-20:10 |
InteriorLights:Electricity | 604.13 | 5592.07 | 02-JAN-02:10 | 50471.22 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 113.37 | 1030.12 | 02-JAN-02:10 | 9271.23 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 604.13 | 5592.07 | 02-JAN-02:10 | 50471.22 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 604.13 | 5592.07 | 02-JAN-02:10 | 50471.22 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 113.37 | 1030.12 | 02-JAN-02:10 | 9271.23 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 604.13 | 5592.07 | 02-JAN-02:10 | 50471.22 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 16.45 | 201.26 | 02-JAN-02:10 | 1197.92 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 19.05 | 233.06 | 02-JAN-02:10 | 1387.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.46 | 67.94 | 02-JAN-02:10 | 394.77 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.87 | 16.96 | 02-JAN-02:10 | 152.61 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.87 | 16.96 | 02-JAN-02:10 | 152.61 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.84 | 1007.22 | 02-JAN-02:10 | 4973.49 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 27.32 | 378.04 | 02-JAN-02:10 | 2538.73 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 12.98 | 76.92 | 01-JAN-13:10 | 1573.46 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 12.98 | 76.92 | 01-JAN-13:10 | 1573.46 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 272.08 | 3294.23 | 02-JAN-02:10 | 20674.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 123.08 | 1182.82 | 02-JAN-02:10 | 10645.38 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 123.08 | 1182.82 | 02-JAN-02:10 | 10645.38 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 18.46 | 262.96 | 01-JAN-02:10 | 1214.21 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 18.46 | 262.93 | 01-JAN-02:10 | 1214.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 302.44 | 4545.27 | 01-JAN-02:10 | 20822.55 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 73.68 | 623.81 | 01-JAN-02:10 | 5671.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 73.68 | 623.81 | 01-JAN-02:10 | 5671.40 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 302.52 | 4546.52 | 01-JAN-02:10 | 20828.25 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 73.70 | 623.98 | 01-JAN-02:10 | 5672.95 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 73.70 | 623.98 | 01-JAN-02:10 | 5672.95 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 18.46 | 262.96 | 01-JAN-02:10 | 1214.21 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 18.46 | 262.93 | 01-JAN-02:10 | 1214.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.62 | 65.74 | 01-JAN-02:10 | 303.55 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.74 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.74 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.62 | 65.73 | 01-JAN-02:10 | 303.52 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.73 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.73 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 35.82 | 538.40 | 01-JAN-02:10 | 2466.50 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 8.73 | 73.89 | 01-JAN-02:10 | 671.80 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 8.73 | 73.89 | 01-JAN-02:10 | 671.80 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 204.39 | 2556.31 | 02-JAN-02:10 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.54 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.54 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 204.39 | 2556.31 | 02-JAN-02:10 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.54 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.54 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 444.45 | 5944.83 | 02-JAN-02:10 | 18636.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 44.02 | 732.86 | 17-MAR-22:30 | 2790.53 | 01-OCT-10:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 2259.64 | 2178.20 | 24-FEB-01:20 | 235833.20 | 06-JUL-18:20 |
LowTempRefrigeration:Refrigeration:Electricity | 15.76 | 0.00 | 01-JAN-11:10 | 1316.50 | 02-JUN-10:40 |
MedTempRefrigeration:Refrigeration:Electricity | 21.17 | 600.38 | 12-FEB-04:10 | 717.46 | 13-APR-13:10 |
WaterSystems:Electricity | 477.19 | 1086.62 | 31-MAY-01:00 | 43981.56 | 04-OCT-21:00 |
Electricity:HVAC | 755.80 | 13268.43 | 29-OCT-03:30 | 50666.64 | 18-AUG-21:10 |
Fans:Electricity | 566.84 | 12381.95 | 04-FEB-08:10 | 39890.65 | 18-AUG-21:10 |
General:Fans:Electricity | 566.84 | 12381.95 | 04-FEB-08:10 | 39890.65 | 18-AUG-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ExteriorEquipment:Electricity | 641.49 | 9451.24 | 02-JAN-02:20 | 39155.93 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 22.46 | 386.43 | 03-JAN-04:10 | 1283.34 | 13-OCT-20:10 |
ElectricityPurchased:Facility | 6148.32 | 68811.96 | 01-NOV-01:50 | 445032.98 | 02-AUG-19:50 |
ElectricityPurchased:Plant | 6148.32 | 68811.96 | 01-NOV-01:50 | 445032.98 | 02-AUG-19:50 |
Cogeneration:ElectricityPurchased | 6148.32 | 68811.96 | 01-NOV-01:50 | 445032.98 | 02-AUG-19:50 |
General:Cogeneration:ElectricityPurchased | 6148.32 | 68811.96 | 01-NOV-01:50 | 445032.98 | 02-AUG-19:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 6148.32 | 68811.96 | 01-NOV-01:50 | 445032.98 | 02-AUG-19:50 |
ElectricityNet:Plant | 6148.32 | 68811.96 | 01-NOV-01:50 | 445032.98 | 02-AUG-19:50 |
Cogeneration:ElectricityNet | 6148.32 | 68811.96 | 01-NOV-01:50 | 445032.98 | 02-AUG-19:50 |
General:Cogeneration:ElectricityNet | 6148.32 | 68811.96 | 01-NOV-01:50 | 445032.98 | 02-AUG-19:50 |
ExteriorLights:Electricity | 174.49 | 0.00 | 01-JAN-07:50 | 11096.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 174.49 | 0.00 | 01-JAN-07:50 | 11096.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 166.50 | 0.00 | 01-JAN-08:10 | 9938.94 | 06-MAY-09:00 |
General:HeatRecovery:Electricity | 166.50 | 0.00 | 01-JAN-08:10 | 9938.94 | 06-MAY-09:00 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.57 | 14-JUN-00:30 | 4738.74 | 13-OCT-18:10 |
Water Heater Parasitic:WaterSystems:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1595.86 | 0.00 | 01-JAN-00:30 | 190317.43 | 08-JUL-15:20 |
General:Cooling:Electricity | 1595.86 | 0.00 | 01-JAN-00:30 | 190317.43 | 08-JUL-15:20 |
Pumps:Electricity | 149.65 | 48.85 | 14-DEC-08:50 | 7783.96 | 23-AUG-20:00 |
General:Pumps:Electricity | 149.65 | 48.85 | 14-DEC-08:50 | 7783.96 | 23-AUG-20:00 |
WIRED_LTG_ELECTRICITY | 21.27 | 0.00 | 01-JAN-00:10 | 1776.59 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 3368.21 | 29270.80 | 09-MAR-02:10 | 356289.96 | 07-JAN-19:10 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 1579.37 | 15908.90 | 03-JUN-10:10 | 274746.43 | 11-FEB-24:00 |
WaterSystems:NaturalGas | 958.81 | 15908.90 | 02-JAN-09:10 | 109467.80 | 31-JAN-23:50 |
Water Heater:WaterSystems:NaturalGas | 958.81 | 15908.90 | 02-JAN-09:10 | 109467.80 | 31-JAN-23:50 |
Heating:NaturalGas | 620.56 | 0.00 | 19-JAN-20:10 | 211479.66 | 12-FEB-07:10 |
Boiler:Heating:NaturalGas | 620.56 | 0.00 | 19-JAN-20:10 | 211479.66 | 12-FEB-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 5040.40 | 0.00 | 01-JAN-00:30 | 749896.09 | 23-AUG-22:00 |
PlantLoopCoolingDemand:HVAC | 5040.40 | 0.00 | 01-JAN-00:30 | 749896.09 | 23-AUG-22:00 |
CoolingCoils:PlantLoopCoolingDemand | 5040.40 | 0.00 | 01-JAN-00:30 | 749896.09 | 23-AUG-22:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-MAR-21:50 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-MAR-21:50 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-MAR-21:50 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-MAR-21:50 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-MAR-21:50 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-MAR-21:50 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 03-APR-06:40 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 03-APR-06:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 27169.77 | 121422.34 | 23-MAR-13:20 | 2842729.69 | 23-AUG-22:00 |
EnergyTransfer:Building | 5103.57 | 78069.97 | 08-JAN-15:00 | 332334.40 | 07-JUL-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 702.60 | 9889.40 | 12-FEB-04:00 | 34903.83 | 08-JUL-10:50 |
Refrigeration:EnergyTransfer | 184.75 | 3989.40 | 12-FEB-04:00 | 10374.64 | 04-APR-06:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.38 | 1994.70 | 12-FEB-04:00 | 5187.32 | 04-APR-06:30 |
General:Refrigeration:EnergyTransfer | 92.38 | 1994.70 | 12-FEB-04:00 | 5187.32 | 04-APR-06:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.38 | 1994.70 | 12-FEB-04:00 | 5187.32 | 04-APR-06:30 |
EnergyTransfer:Plant | 13150.31 | 16815.43 | 08-NOV-02:20 | 1726165.84 | 23-AUG-22:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.65 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 70.73 | 1747.66 | 12-FEB-04:10 | 2564.87 | 13-APR-13:10 |
EnergyTransfer:HVAC | 8915.89 | 159.13 | 22-FEB-16:00 | 974825.72 | 08-AUG-20:10 |
CoolingCoils:EnergyTransfer | 6243.26 | 0.00 | 01-JAN-02:50 | 835190.84 | 23-AUG-20:50 |
EnergyTransfer:Zone:BASEMENT | 325.04 | 2565.18 | 09-APR-15:00 | 19010.81 | 08-NOV-22:00 |
Heating:EnergyTransfer | 70.16 | 0.00 | 01-JAN-08:10 | 71676.59 | 07-JAN-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 70.16 | 0.00 | 01-JAN-08:10 | 71676.59 | 07-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4941.04 | 66593.75 | 08-JAN-15:00 | 329637.51 | 07-JUL-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 325.04 | 2565.18 | 09-APR-15:00 | 19010.81 | 08-NOV-22:00 |
General:Cooling:EnergyTransfer | 4941.04 | 66593.75 | 08-JAN-15:00 | 329637.51 | 07-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 325.04 | 2565.18 | 09-APR-15:00 | 19010.81 | 08-NOV-22:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 41.28 | 0.00 | 25-DEC-15:00 | 3114.62 | 10-OCT-13:30 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.40 | 0.00 | 01-JAN-00:10 | 1289.67 | 12-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.40 | 0.00 | 01-JAN-00:10 | 1289.67 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 40.88 | 0.00 | 01-JAN-17:50 | 3114.62 | 10-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 40.88 | 0.00 | 01-JAN-17:50 | 3114.62 | 10-OCT-13:30 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 36.76 | 231.40 | 08-JAN-15:50 | 2164.96 | 18-AUG-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 36.76 | 231.40 | 08-JAN-15:50 | 2164.96 | 18-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 36.76 | 231.40 | 08-JAN-15:50 | 2164.96 | 18-AUG-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 27.99 | 0.01 | 12-JAN-04:40 | 1869.46 | 07-JUL-21:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.09 | 0.00 | 01-JAN-00:10 | 387.51 | 08-JAN-13:50 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.09 | 0.00 | 01-JAN-00:10 | 387.51 | 08-JAN-13:50 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 27.90 | 0.00 | 06-JAN-03:00 | 1869.46 | 07-JUL-21:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 27.90 | 0.00 | 06-JAN-03:00 | 1869.46 | 07-JUL-21:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 14.39 | 0.05 | 23-JAN-04:40 | 824.53 | 07-JUL-21:00 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.16 | 0.00 | 01-JAN-00:10 | 311.33 | 08-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.16 | 0.00 | 01-JAN-00:10 | 311.33 | 08-JAN-05:30 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 14.23 | 0.00 | 03-JAN-10:20 | 824.53 | 07-JUL-21:00 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 14.23 | 0.00 | 03-JAN-10:20 | 824.53 | 07-JUL-21:00 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 607.91 | 9234.49 | 09-JAN-05:00 | 39122.13 | 07-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 607.91 | 9234.49 | 09-JAN-05:00 | 39122.13 | 07-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 607.91 | 9234.49 | 09-JAN-05:00 | 39122.13 | 07-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 229.58 | 166.81 | 09-JAN-09:20 | 12096.51 | 18-AUG-21:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 229.58 | 166.81 | 09-JAN-09:20 | 12096.51 | 18-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 229.58 | 166.81 | 09-JAN-09:20 | 12096.51 | 18-AUG-21:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 803.16 | 8609.28 | 08-JAN-16:00 | 42629.02 | 18-AUG-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 803.16 | 8609.28 | 08-JAN-16:00 | 42629.02 | 18-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 803.16 | 8609.28 | 08-JAN-16:00 | 42629.02 | 18-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 64.74 | 0.00 | 01-JAN-08:10 | 10053.83 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 7.58 | 0.00 | 01-JAN-08:10 | 5551.12 | 07-JAN-19:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 7.58 | 0.00 | 01-JAN-08:10 | 5551.12 | 07-JAN-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 57.16 | 0.00 | 01-JAN-00:10 | 10053.83 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 57.16 | 0.00 | 01-JAN-00:10 | 10053.83 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 56.51 | 0.00 | 01-JAN-08:10 | 10202.47 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 10.56 | 0.00 | 01-JAN-08:10 | 6069.72 | 12-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 10.56 | 0.00 | 01-JAN-08:10 | 6069.72 | 12-FEB-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 45.94 | 0.00 | 01-JAN-00:10 | 10202.47 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 45.94 | 0.00 | 01-JAN-00:10 | 10202.47 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 309.45 | 0.00 | 01-JAN-00:10 | 40260.51 | 10-OCT-13:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 309.45 | 0.00 | 01-JAN-00:10 | 40260.51 | 10-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 309.45 | 0.00 | 01-JAN-00:10 | 40260.51 | 10-OCT-13:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 445.90 | 0.00 | 01-JAN-08:10 | 67522.91 | 16-JUL-15:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 17.63 | 0.00 | 01-JAN-00:10 | 31897.74 | 07-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 17.63 | 0.00 | 01-JAN-00:10 | 31897.74 | 07-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 428.27 | 0.00 | 01-JAN-08:10 | 67522.91 | 16-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 428.27 | 0.00 | 01-JAN-08:10 | 67522.91 | 16-JUL-15:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 64.96 | 0.00 | 01-JAN-08:10 | 8972.57 | 07-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 7.54 | 0.00 | 01-JAN-08:10 | 5646.30 | 07-JAN-19:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 7.54 | 0.00 | 01-JAN-08:10 | 5646.30 | 07-JAN-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 57.42 | 0.00 | 01-JAN-00:10 | 8972.57 | 07-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 57.42 | 0.00 | 01-JAN-00:10 | 8972.57 | 07-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 56.86 | 0.00 | 01-JAN-08:10 | 9388.56 | 04-JUN-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 10.51 | 0.00 | 01-JAN-08:10 | 5879.38 | 07-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 10.51 | 0.00 | 01-JAN-08:10 | 5879.38 | 07-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 46.35 | 0.00 | 01-JAN-00:10 | 9388.56 | 04-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 46.35 | 0.00 | 01-JAN-00:10 | 9388.56 | 04-JUN-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 163.62 | 0.02 | 09-JAN-05:10 | 9020.54 | 18-AUG-18:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.65 | 0.00 | 01-JAN-00:10 | 3284.42 | 09-JAN-09:20 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.65 | 0.00 | 01-JAN-00:10 | 3284.42 | 09-JAN-09:20 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 162.97 | 0.00 | 02-JAN-09:10 | 9020.54 | 18-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 162.97 | 0.00 | 02-JAN-09:10 | 9020.54 | 18-AUG-18:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 17.35 | 0.00 | 01-JAN-08:10 | 2694.58 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 3.36 | 0.00 | 01-JAN-08:10 | 1825.96 | 07-JAN-19:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 3.36 | 0.00 | 01-JAN-08:10 | 1825.96 | 07-JAN-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.99 | 0.00 | 01-JAN-00:10 | 2694.58 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.99 | 0.00 | 01-JAN-00:10 | 2694.58 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 15.87 | 0.00 | 01-JAN-08:10 | 2726.28 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 4.40 | 0.00 | 01-JAN-08:10 | 2013.34 | 12-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 4.40 | 0.00 | 01-JAN-08:10 | 2013.34 | 12-FEB-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 11.46 | 0.00 | 01-JAN-00:10 | 2726.28 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 11.46 | 0.00 | 01-JAN-00:10 | 2726.28 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 94.05 | 0.00 | 01-JAN-08:10 | 13089.21 | 10-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 6.37 | 0.00 | 01-JAN-08:10 | 7800.70 | 07-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 6.37 | 0.00 | 01-JAN-08:10 | 7800.70 | 07-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 87.68 | 0.00 | 01-JAN-00:10 | 13089.21 | 10-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 87.68 | 0.00 | 01-JAN-00:10 | 13089.21 | 10-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 447.84 | 8354.07 | 03-FEB-12:00 | 23542.57 | 07-JUL-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 447.84 | 8354.07 | 03-FEB-12:00 | 23542.57 | 07-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 447.84 | 8354.07 | 03-FEB-12:00 | 23542.57 | 07-JUL-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 485.79 | 9374.32 | 03-FEB-12:00 | 24768.72 | 07-JUL-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 485.79 | 9374.32 | 03-FEB-12:00 | 24768.72 | 07-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 485.79 | 9374.32 | 03-FEB-12:00 | 24768.72 | 07-JUL-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 610.22 | 7894.70 | 12-FEB-04:00 | 29841.18 | 08-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 610.22 | 7894.70 | 12-FEB-04:00 | 29841.18 | 08-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 91.92 | 0.31 | 01-DEC-09:00 | 6500.84 | 08-JUL-16:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.90 | 0.00 | 01-JAN-00:10 | 2692.66 | 12-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.90 | 0.00 | 01-JAN-00:10 | 2692.66 | 12-FEB-06:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 91.02 | 0.00 | 03-JAN-09:10 | 6500.84 | 08-JUL-16:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 91.02 | 0.00 | 03-JAN-09:10 | 6500.84 | 08-JUL-16:10 |
PlantLoopHeatingDemand:Facility | 2706.00 | 7887.60 | 03-AUG-01:20 | 290900.49 | 11-FEB-23:00 |
PlantLoopHeatingDemand:Plant | 2266.13 | 7887.60 | 03-AUG-01:20 | 212771.42 | 01-MAY-20:20 |
WaterSystems:PlantLoopHeatingDemand | 2266.13 | 7887.60 | 03-AUG-01:20 | 212771.42 | 01-MAY-20:20 |
General:WaterSystems:PlantLoopHeatingDemand | 688.47 | 7883.76 | 03-AUG-00:10 | 52947.37 | 01-FEB-07:50 |
HeatingCoils:EnergyTransfer | 439.87 | 0.00 | 19-JAN-20:10 | 174239.44 | 12-FEB-07:10 |
PlantLoopHeatingDemand:HVAC | 439.87 | 0.00 | 19-JAN-20:10 | 174239.44 | 12-FEB-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 439.87 | 0.00 | 19-JAN-20:10 | 174239.44 | 12-FEB-07:10 |
HeatRecoveryForHeating:EnergyTransfer | 1362.74 | 0.00 | 01-JAN-08:10 | 435332.30 | 12-FEB-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 870.02 | 0.00 | 01-JAN-00:10 | 254398.99 | 08-AUG-19:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 1577.66 | 0.00 | 01-JAN-00:10 | 176044.25 | 01-MAY-20:50 |
WaterSystems:EnergyTransfer | 688.47 | 7883.76 | 03-AUG-00:10 | 52947.37 | 01-FEB-07:50 |
WaterUse:WaterSystems:EnergyTransfer | 688.47 | 7883.76 | 03-AUG-00:10 | 52947.37 | 01-FEB-07:50 |
Boilers:EnergyTransfer | 435.65 | 0.00 | 19-JAN-20:10 | 170530.97 | 12-FEB-07:10 |
Chillers:EnergyTransfer | 5168.97 | 0.00 | 01-JAN-00:30 | 757057.12 | 23-AUG-22:00 |
HeatRejection:EnergyTransfer | 6764.84 | 0.00 | 01-JAN-00:30 | 942643.49 | 23-AUG-22:00 |
General:HeatRejection:EnergyTransfer | 6764.84 | 0.00 | 01-JAN-00:30 | 942643.49 | 23-AUG-22:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -325.038 | 0.000 | 0.000 | 145.083 | 113.371 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -76.521 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.404 | -40.880 | 0.000 | 0.000 | 15.113 | 6.265 | 10.186 | 18.771 | 0.000 | 0.089 | 0.000 | 0.000 | -8.173 | 0.000 | -0.635 | -1.138 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -36.760 | 0.000 | 0.000 | 16.742 | 7.255 | 11.795 | 0.000 | 0.000 | 0.036 | 1.199 | 0.000 | 0.000 | 0.000 | -0.266 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.089 | -27.904 | 0.000 | 0.000 | 3.662 | 8.366 | 12.471 | 0.000 | 0.000 | 0.085 | 3.819 | 0.000 | 0.000 | 0.000 | -0.590 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.160 | -14.226 | 0.000 | 0.000 | 2.838 | 1.866 | 3.598 | 0.000 | 0.000 | 0.050 | 6.050 | 0.000 | 0.000 | 0.000 | -0.335 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -607.915 | 0.000 | 0.000 | 11.373 | 4.900 | 658.131 | 0.000 | 0.000 | 0.135 | 0.000 | 0.000 | 0.000 | 0.000 | -0.873 | -65.750 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -229.581 | 0.000 | 0.000 | 187.395 | 12.978 | 14.341 | 52.060 | 0.000 | 0.199 | 0.000 | 0.000 | -25.115 | 0.000 | -1.560 | -10.718 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -803.170 | 0.000 | 0.000 | 550.741 | 123.083 | 148.998 | 69.077 | 0.000 | 0.578 | 0.000 | 0.000 | -33.760 | 0.000 | -4.552 | -50.997 |
ROOM_1_FLR_3 | 10.159 | -47.799 | 0.000 | -11.934 | 0.000 | 0.000 | 9.689 | 6.171 | 12.292 | 39.155 | 0.000 | 0.434 | 1.690 | 0.000 | -17.761 | 0.000 | -2.095 | -0.002 |
ROOM_2_FLR_3 | 13.515 | -36.472 | 0.000 | -12.419 | 0.000 | 0.000 | 9.578 | 6.170 | 12.291 | 30.034 | 0.000 | 0.310 | 0.000 | 0.000 | -18.848 | 0.000 | -2.476 | -1.683 |
ROOM_3_MULT19_FLR_3 | 0.000 | -293.454 | 0.000 | -15.993 | 0.000 | 0.000 | 0.000 | 73.685 | 228.754 | 200.360 | 0.000 | 0.445 | 0.002 | 0.000 | -140.801 | 0.000 | -13.149 | -39.846 |
ROOM_4_MULT19_FLR_3 | 37.788 | -281.335 | 0.000 | -167.075 | 0.000 | 0.000 | 182.314 | 73.705 | 228.817 | 90.819 | 0.000 | 2.223 | 0.000 | 0.000 | -105.203 | 0.000 | -24.804 | -37.247 |
ROOM_5_FLR_3 | 10.088 | -48.019 | 0.000 | -11.944 | 0.000 | 0.000 | 9.682 | 6.171 | 12.292 | 39.030 | 0.000 | 0.433 | 1.528 | 0.000 | -17.162 | 0.000 | -2.100 | -0.000 |
ROOM_6_FLR_3 | 13.449 | -36.874 | 0.000 | -12.414 | 0.000 | 0.000 | 9.584 | 6.170 | 12.291 | 29.415 | 0.000 | 0.313 | 0.001 | 0.000 | -17.741 | 0.000 | -2.407 | -1.785 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.650 | -162.968 | 0.000 | 0.000 | 116.100 | 56.739 | 0.000 | 35.063 | 0.000 | 0.257 | 0.000 | 0.000 | -23.537 | 0.000 | -1.810 | -20.493 |
ROOM_1_FLR_6 | 4.142 | -11.796 | 0.000 | -2.980 | 0.000 | 0.000 | 2.426 | 1.543 | 3.073 | 9.733 | 0.000 | 0.113 | 0.000 | 0.000 | -4.379 | 0.000 | -0.551 | -1.324 |
ROOM_2_FLR_6 | 5.253 | -9.221 | 0.000 | -3.094 | 0.000 | 0.000 | 2.399 | 1.543 | 3.073 | 7.475 | 0.000 | 0.079 | 0.000 | 0.000 | -4.649 | 0.000 | -0.645 | -2.211 |
ROOM_3_MULT9_FLR_6 | 9.379 | -71.432 | 0.000 | -19.255 | 0.000 | 0.000 | 21.749 | 8.728 | 27.097 | 49.735 | 0.000 | 0.693 | 0.001 | 0.000 | -20.347 | 0.000 | -3.482 | -2.865 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -447.845 | 0.000 | 0.000 | 317.710 | 28.537 | 175.857 | 8.942 | 0.000 | 0.112 | 0.000 | 0.000 | -15.204 | 0.000 | -1.077 | -67.032 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -485.795 | 0.000 | 0.000 | 316.312 | 28.537 | 175.857 | 8.690 | 0.000 | 0.110 | 0.000 | 0.000 | -15.752 | 0.000 | -1.090 | -26.868 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -610.208 | 0.000 | 0.000 | 28.516 | 13.339 | 540.650 | 18.765 | 0.000 | 0.097 | 20.157 | 0.000 | -10.339 | 0.000 | -0.976 | -0.001 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.896 | -91.022 | 0.000 | 0.000 | 30.855 | 15.012 | 0.000 | 16.652 | 0.000 | 0.106 | 38.886 | 0.000 | -10.591 | 0.000 | -0.795 | -0.000 |
Total Facility | 103.773 | -836.403 | 2.198 | -4140.421 | 0.000 | 0.000 | 1989.862 | 604.131 | 2434.967 | 723.775 | 0.000 | 6.897 | 73.335 | 0.000 | -489.363 | 0.000 | -66.269 | -406.480 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 08-NOV-22:00 | 0.00 | 0.00 | 0.00 | -19011.68 | 0.00 | 0.00 | 5924.42 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4279.40 |
RETAIL_1_FLR_1 | 10-OCT-13:30 | 0.00 | 0.00 | 0.00 | -3114.72 | 0.00 | 0.00 | 150.60 | 142.31 | 252.59 | 4113.68 | 0.00 | 13.52 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1557.97 |
RETAIL_2_FLR_1 | 18-AUG-21:00 | 0.00 | 0.00 | 0.00 | -2165.01 | 0.00 | 0.00 | 697.61 | 527.34 | 752.15 | 0.00 | 0.00 | 7.57 | 180.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 07-JUL-21:00 | 0.00 | 0.00 | 0.00 | -1869.53 | 0.00 | 0.00 | 147.52 | 608.16 | 795.27 | 0.00 | 0.00 | 16.67 | 301.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 07-JUL-21:00 | 0.00 | 0.00 | 0.00 | -824.56 | 0.00 | 0.00 | 113.48 | 135.66 | 229.41 | 0.00 | 0.00 | 9.62 | 336.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 07-JUL-20:00 | 0.00 | 0.00 | 0.00 | -39123.43 | 0.00 | 0.00 | 408.86 | 400.68 | 44299.38 | 0.00 | 0.00 | 24.45 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6009.94 |
CAFE_FLR_1 | 18-AUG-21:10 | 0.00 | 0.00 | 0.00 | -12098.91 | 0.00 | 0.00 | 8907.85 | 1048.97 | 711.25 | 419.53 | 0.00 | 41.71 | 969.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 18-AUG-21:10 | 0.00 | 0.00 | 0.00 | -42635.38 | 0.00 | 0.00 | 26439.93 | 7096.92 | 7389.94 | 595.45 | 0.00 | 119.15 | 993.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 12-JUL-18:02 | 0.00 | -10597.49 | 0.00 | -731.37 | 0.00 | 0.00 | 335.50 | 422.72 | 516.26 | 5235.14 | 0.00 | 59.05 | 4760.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 18-SEP-16:01 | 0.00 | -11395.13 | 0.00 | -854.51 | 0.00 | 0.00 | 207.30 | 132.97 | 537.27 | 5015.25 | 0.00 | 5.86 | 6350.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 10-OCT-13:30 | 0.00 | -40262.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1587.99 | 5097.90 | 48178.47 | 0.00 | 73.35 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -14675.59 |
ROOM_4_MULT19_FLR_3 | 11-JUN-08:51 | 0.00 | -66593.18 | 0.00 | -9990.80 | 0.00 | 0.00 | 2494.96 | 3176.85 | 12159.85 | 6266.71 | 0.00 | 12.17 | 52473.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 14-JUL-08:62 | 0.00 | -9520.73 | 0.00 | -724.25 | 0.00 | 0.00 | 87.14 | 208.98 | 453.05 | 5058.14 | 0.00 | 31.12 | 4406.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 06-JUN-08:51 | 0.00 | -10328.51 | 0.00 | -928.46 | 0.00 | 0.00 | 71.66 | 208.96 | 452.99 | 6443.44 | 0.00 | 4.02 | 4075.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 18-AUG-18:20 | 0.00 | 0.00 | 0.00 | -9026.22 | 0.00 | 0.00 | 4080.27 | 4124.45 | 0.00 | 1813.93 | 0.00 | 73.06 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1065.49 |
ROOM_1_FLR_6 | 07-JUL-18:02 | 0.00 | -2826.91 | 0.00 | -183.05 | 0.00 | 0.00 | 83.87 | 105.68 | 129.07 | 1060.60 | 0.00 | 17.33 | 1613.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 18-SEP-16:01 | 0.00 | -3032.23 | 0.00 | -216.52 | 0.00 | 0.00 | 50.99 | 33.24 | 134.32 | 1237.60 | 0.00 | 1.10 | 1791.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11-SEP-15:02 | 0.00 | -12748.26 | 0.00 | -1189.14 | 0.00 | 0.00 | 529.36 | 188.10 | 603.86 | 5988.01 | 0.00 | 48.13 | 6579.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 07-JUL-21:20 | 0.00 | 0.00 | 0.00 | -23547.21 | 0.00 | 0.00 | 15636.02 | 1842.08 | 6747.90 | 266.58 | 0.00 | 23.98 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -969.34 |
DINING_FLR_6 | 07-JUL-21:20 | 0.00 | 0.00 | 0.00 | -24773.68 | 0.00 | 0.00 | 15629.87 | 1842.08 | 6747.90 | 253.08 | 0.00 | 23.97 | 276.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 16-APR-17:02 | 0.00 | 0.00 | 0.00 | -31038.78 | 0.00 | 0.00 | 564.46 | 606.02 | 26450.81 | 807.47 | 0.00 | 6.71 | 2603.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 08-JUL-16:10 | 0.00 | 0.00 | 0.00 | -6500.21 | 0.00 | 0.00 | 771.15 | 341.02 | 0.00 | 1532.31 | 0.00 | 41.26 | 3814.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-AUG-18:02 | 0.00 | -150106.28 | 0.00 | -196601.02 | 0.00 | 0.00 | 74786.33 | 40733.17 | 121562.63 | 42375.01 | 0.00 | 1416.37 | 65833.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 12-FEB-06:00 | 0.00 | 0.00 | 1289.67 | 0.00 | 0.00 | 0.00 | 626.42 | 113.85 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1596.00 | 0.00 | -108.99 | -541.47 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 08-JAN-13:50 | 0.00 | 0.00 | 387.50 | 0.00 | 0.00 | 0.00 | 43.84 | 152.04 | 265.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -61.23 | -787.25 |
STORAGE_FLR_1 | 08-JAN-05:30 | 0.00 | 0.00 | 311.34 | 0.00 | 0.00 | 0.00 | 118.04 | 33.91 | 76.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -43.57 | -496.19 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 07-JAN-19:01 | 8890.78 | 288.28 | 0.00 | -288.28 | 0.00 | 0.00 | 353.87 | 474.96 | 516.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2774.65 | 0.00 | -184.02 | -7277.20 |
ROOM_2_FLR_3 | 03-FEB-09:01 | 8923.28 | 287.31 | 0.00 | -287.31 | 0.00 | 0.00 | 108.88 | 208.96 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2481.68 | 0.00 | -195.17 | -7017.26 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 07-JAN-16:01 | 50379.73 | 4227.71 | 0.00 | -4227.71 | 0.00 | 0.00 | 3032.25 | 1872.11 | 5687.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11135.87 | 0.00 | -925.18 | -48910.72 |
ROOM_5_FLR_3 | 07-JAN-19:01 | 8678.75 | 286.58 | 0.00 | -286.58 | 0.00 | 0.00 | 353.87 | 474.96 | 516.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2816.41 | 0.00 | -183.85 | -7023.58 |
ROOM_6_FLR_3 | 07-JAN-19:01 | 8686.05 | 285.68 | 0.00 | -285.68 | 0.00 | 0.00 | 353.87 | 474.90 | 516.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2832.97 | 0.00 | -183.75 | -7014.31 |
CORRIDOR_FLR_3 | 09-JAN-09:03 | 0.00 | 0.00 | 3380.88 | 0.00 | 0.00 | 0.00 | 1385.69 | 2062.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2337.54 | 0.00 | -213.61 | -4277.65 |
ROOM_1_FLR_6 | 07-JAN-19:01 | 2678.09 | 72.70 | 0.00 | -72.70 | 0.00 | 0.00 | 88.47 | 118.74 | 129.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -691.06 | 0.00 | -46.19 | -2277.11 |
ROOM_2_FLR_6 | 03-FEB-09:01 | 2688.42 | 72.37 | 0.00 | -72.37 | 0.00 | 0.00 | 27.22 | 52.24 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -620.81 | 0.00 | -48.96 | -2211.35 |
ROOM_3_MULT9_FLR_6 | 07-JAN-19:01 | 12492.84 | 466.21 | 0.00 | -466.21 | 0.00 | 0.00 | 796.21 | 671.80 | 1138.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3255.35 | 0.00 | -212.61 | -11630.94 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 12-FEB-06:00 | 0.00 | 0.00 | 2692.67 | 0.00 | 0.00 | 0.00 | 1283.28 | 272.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2135.28 | 0.00 | -135.77 | -1977.72 |
Total Facility | 07-JAN-16:01 | 29350.50 | 79785.35 | 5734.38 | -79785.35 | 0.00 | 0.00 | 36399.52 | 13516.26 | 78232.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -41913.13 | 0.00 | -4448.31 | -116871.85 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 20.9276 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 20.8112 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6567 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6567 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1110 | 2.1110 | 1.1758 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3028 | 0.3028 | 0.1687 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2271 | 0.2271 | 0.1265 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1995 | 0.1995 | 0.1111 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1075 | 0.1075 | 0.0599 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3809 | 3.3809 | 1.8832 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3657 | 1.3657 | 0.7607 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.6245 | 4.6245 | 2.5758 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1857 | 1.1857 | 0.6605 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2033 | 2.2033 | 1.2272 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3129 | 2.3129 | 1.2883 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2268 | 2.2268 | 1.2403 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6798 | 0.6798 | 0.3786 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 20.9276 | 20.8112 | 20.9276 | 11.6567 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1758 | 1.1758 | 1.1758 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1687 | 0.1687 | 0.1687 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1265 | 0.1265 | 0.1265 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1111 | 0.1111 | 0.1111 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0599 | 0.0599 | 0.0599 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8832 | 1.8832 | 1.8832 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7607 | 0.7607 | 0.7607 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5758 | 2.5758 | 2.5758 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6605 | 0.6605 | 0.6605 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2272 | 1.2272 | 1.2272 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2883 | 1.2883 | 1.2883 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2403 | 1.2403 | 1.2403 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3786 | 0.3786 | 0.3786 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6567 | 11.6567 | 11.6567 | 11.6567 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 109.00 |
Number of hours not met | 109.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 620.56 | 211479.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1595.86 | 190317.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 604.13 | 50471.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 174.49 | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 952.41 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 22.46 | 1283.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 566.84 | 39890.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 149.65 | 7783.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 166.50 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4738.74 | 958.81 | 109467.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Other | 0.00 | 39242.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.76 | 1316.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 21.17 | 717.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1772.16 | 6148.32 |
Natural Gas | 1788.84 | 3368.21 |
Additional | 0.00 | 0.00 |
Total | 3561.00 | 9516.53 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 53.25 |
Space Heating | 0.00 |
Space Cooling | 140.66 |
Fans (All) | 49.96 |
Service Water Heating | 42.06 |
Receptacle Equipment | 152.32 |
Miscellaneous (All) | 541.93 |
Subtotal | 541.93 |
Natural Gas [MJ/m2] | |
Space Heating | 54.70 |
Service Water Heating | 84.51 |
Miscellaneous (All) | 296.88 |
Subtotal | 296.88 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.35 |
Space Heating | 6.52 |
Space Cooling | 16.77 |
Fans (All) | 5.96 |
Service Water Heating | 15.09 |
Receptacle Equipment | 36.96 |
Miscellaneous | 12.36 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2398. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 2482. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7634.33 | 1125.67 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8751.33 | 8.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8758.17 | 1.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7634.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1125.67 | 0.00 | 0.00 | 0.00 |
Average | 8708.33 | 51.67 | 0.00 | 0.00 | 0.00 |
Sum | 191583.33 | 1136.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8656.17 | 103.83 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 7361.00 | 1399.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 7553.00 | 1207.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8575.00 | 185.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 6825.17 | 1934.83 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8625.00 | 135.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8528.00 | 232.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8584.33 | 175.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8544.67 | 215.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8748.00 | 12.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 7424.50 | 1335.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 7570.83 | 1189.17 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8552.50 | 207.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 6825.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1934.83 | 0.00 | 0.00 | 0.00 |
Average | 8380.76 | 379.24 | 0.00 | 0.00 | 0.00 |
Sum | 184376.67 | 8343.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 58027.83 | 1128.17 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 542747.17 | 167669.83 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1691864.50 | 423564.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4116.33 | 37.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4120.67 | 33.33 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4115.83 | 38.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 97313.00 | 3045.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4106.33 | 47.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 973225.50 | 272489.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1000404.17 | 245310.83 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 106655.17 | 1613.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1691864.50 | 423564.50 | 0.00 | 0.00 | 0.00 |
Average | 238206.20 | 50680.84 | 0.00 | 0.00 | 0.00 |
Sum | 5240536.50 | 1114978.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:03
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258726E+11 | 11579.91 | 31-JAN-21:00 | 17.20 | 12.43 | 0.718967E+10 | 4490.24 | 27-JAN-22:10 | 17.20 | 12.43 |
February | 0.215749E+11 | 11126.63 | 01-FEB-21:00 | 9.40 | 8.81 | 0.612017E+10 | 4404.21 | 01-FEB-22:10 | 8.72 | 8.24 |
March | 0.213845E+11 | 10728.22 | 30-MAR-18:08 | 26.02 | 17.62 | 0.640594E+10 | 4115.62 | 01-MAR-22:10 | 26.02 | 17.62 |
April | 0.173137E+11 | 12141.68 | 17-APR-18:07 | 26.42 | 16.07 | 0.600285E+10 | 3824.90 | 14-APR-22:10 | 26.42 | 16.07 |
May | 0.215951E+11 | 12255.25 | 16-MAY-18:02 | 28.22 | 17.07 | 0.635257E+10 | 3943.30 | 10-MAY-22:10 | 28.22 | 17.07 |
June | 0.254480E+11 | 12522.41 | 25-JUN-10:33 | 29.80 | 23.29 | 0.666317E+10 | 4288.31 | 30-JUN-22:10 | 22.58 | 21.11 |
July | 0.287110E+11 | 13397.06 | 20-JUL-18:10 | 32.12 | 22.73 | 0.726714E+10 | 4565.65 | 28-JUL-22:10 | 17.70 | 17.38 |
August | 0.310933E+11 | 14319.12 | 27-AUG-10:33 | 29.47 | 22.52 | 0.776827E+10 | 4827.30 | 31-AUG-22:10 | 21.58 | 19.54 |
September | 0.327134E+11 | 17710.78 | 28-SEP-21:00 | 15.60 | 13.52 | 0.787310E+10 | 4837.09 | 14-SEP-22:10 | 15.60 | 13.52 |
October | 0.348148E+11 | 18757.47 | 13-OCT-21:00 | 13.30 | 9.72 | 0.818898E+10 | 4837.18 | 27-OCT-23:49 | 12.85 | 12.31 |
November | 0.337412E+11 | 19010.81 | 08-NOV-22:00 | 13.90 | 7.06 | 0.792872E+10 | 4837.16 | 01-NOV-01:10 | 13.90 | 7.06 |
December | 0.307742E+11 | 17097.63 | 01-DEC-22:00 | 3.90 | 0.00 | 0.801735E+10 | 4837.08 | 15-DEC-22:19 | 5.40 | 3.89 |
Annual Sum or Average | 0.325037E+12 | 0.857779E+11 | ||||||||
Minimum of Months | 0.173137E+11 | 10728.22 | 3.90 | 0.00 | 0.600285E+10 | 3824.90 | 5.40 | 3.89 | ||
Maximum of Months | 0.348148E+11 | 19010.81 | 32.12 | 23.29 | 0.818898E+10 | 4837.18 | 28.22 | 21.11 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148473E+10 | 1988.08 | 29-JAN-13:00 | 13.90 | 6.14 | 0.628563E+09 | 399.23 | 31-JAN-22:30 | 13.75 | 10.50 |
February | 0.186170E+10 | 2377.87 | 21-FEB-14:25 | 22.25 | 10.82 | 0.580669E+09 | 450.66 | 28-FEB-22:30 | 18.10 | 10.49 |
March | 0.322443E+10 | 2361.41 | 30-MAR-15:23 | 27.80 | 17.27 | 0.678904E+09 | 484.46 | 30-MAR-21:19 | 23.53 | 16.75 |
April | 0.348625E+10 | 2663.87 | 13-APR-15:30 | 26.95 | 15.18 | 0.674828E+09 | 480.40 | 17-APR-21:40 | 20.00 | 13.94 |
May | 0.396494E+10 | 2169.83 | 16-MAY-18:02 | 28.22 | 17.07 | 0.727279E+09 | 490.00 | 19-MAY-21:30 | 23.05 | 15.97 |
June | 0.427584E+10 | 2258.18 | 13-JUN-18:08 | 31.93 | 21.91 | 0.753826E+09 | 491.84 | 05-JUN-21:19 | 31.93 | 21.91 |
July | 0.466028E+10 | 2582.39 | 07-JUL-18:20 | 33.70 | 23.11 | 0.790332E+09 | 491.84 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.494793E+10 | 2901.81 | 19-AUG-13:40 | 33.70 | 23.70 | 0.810633E+09 | 491.84 | 07-AUG-22:10 | 33.70 | 23.70 |
September | 0.423125E+10 | 2945.08 | 24-SEP-12:40 | 28.70 | 19.86 | 0.734667E+09 | 491.84 | 11-SEP-22:10 | 28.70 | 19.86 |
October | 0.368758E+10 | 3114.62 | 10-OCT-13:30 | 28.85 | 20.88 | 0.704579E+09 | 491.84 | 10-OCT-22:10 | 21.02 | 18.59 |
November | 0.297472E+10 | 2508.85 | 08-NOV-13:40 | 20.20 | 9.59 | 0.638568E+09 | 441.41 | 08-NOV-22:30 | 13.05 | 6.76 |
December | 0.207984E+10 | 2319.80 | 10-DEC-13:00 | 15.60 | 7.72 | 0.638934E+09 | 439.14 | 12-DEC-22:30 | 18.30 | 14.75 |
Annual Sum or Average | 0.408795E+11 | 0.836178E+10 | ||||||||
Minimum of Months | 0.148473E+10 | 1988.08 | 13.90 | 6.14 | 0.580669E+09 | 399.23 | 13.05 | 6.76 | ||
Maximum of Months | 0.494793E+10 | 3114.62 | 33.70 | 23.70 | 0.810633E+09 | 491.84 | 33.70 | 23.70 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235525E+10 | 1246.82 | 31-JAN-21:00 | 17.20 | 12.43 | 0.781087E+09 | 534.15 | 31-JAN-23:10 | 12.22 | 9.67 |
February | 0.230333E+10 | 1379.44 | 28-FEB-21:00 | 20.60 | 11.78 | 0.731321E+09 | 569.55 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.292637E+10 | 1672.37 | 30-MAR-21:00 | 23.90 | 16.89 | 0.873006E+09 | 569.55 | 13-MAR-22:10 | 23.90 | 16.89 |
April | 0.301010E+10 | 1727.34 | 14-APR-21:00 | 20.00 | 13.56 | 0.867218E+09 | 569.55 | 24-APR-21:19 | 13.13 | 10.01 |
May | 0.330258E+10 | 1854.99 | 19-MAY-21:00 | 23.90 | 16.26 | 0.919418E+09 | 569.55 | 10-MAY-21:40 | 23.90 | 16.26 |
June | 0.348938E+10 | 1966.91 | 27-JUN-21:00 | 27.20 | 20.99 | 0.917128E+09 | 569.55 | 08-JUN-22:10 | 27.20 | 20.99 |
July | 0.372913E+10 | 2126.61 | 07-JUL-21:00 | 30.60 | 22.80 | 0.948125E+09 | 569.55 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.382053E+10 | 2164.96 | 18-AUG-21:00 | 31.10 | 22.83 | 0.959738E+09 | 569.55 | 31-AUG-22:10 | 21.58 | 19.54 |
September | 0.335608E+10 | 2035.60 | 08-SEP-21:00 | 25.60 | 21.61 | 0.905940E+09 | 569.55 | 14-SEP-22:10 | 18.62 | 13.88 |
October | 0.310270E+10 | 1814.26 | 11-OCT-21:00 | 16.10 | 9.61 | 0.895505E+09 | 569.55 | 10-OCT-22:10 | 16.10 | 9.61 |
November | 0.276189E+10 | 1365.60 | 06-NOV-21:00 | 12.20 | 6.19 | 0.829610E+09 | 568.19 | 06-NOV-22:40 | 10.77 | 5.58 |
December | 0.260239E+10 | 1334.23 | 12-DEC-21:00 | 18.30 | 14.62 | 0.813310E+09 | 560.41 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.367597E+11 | 0.104414E+11 | ||||||||
Minimum of Months | 0.230333E+10 | 1246.82 | 12.20 | 6.19 | 0.731321E+09 | 534.15 | 10.77 | 5.58 | ||
Maximum of Months | 0.382053E+10 | 2164.96 | 31.10 | 22.83 | 0.959738E+09 | 569.55 | 27.20 | 21.29 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.925327E+09 | 941.99 | 20-JAN-21:00 | 12.80 | 8.84 | 0.152743E+09 | 99.01 | 20-JAN-22:10 | 11.52 | 8.16 |
February | 0.127439E+10 | 1048.01 | 28-FEB-21:00 | 20.60 | 11.78 | 0.141534E+09 | 105.78 | 28-FEB-22:19 | 18.37 | 10.65 |
March | 0.221259E+10 | 1274.91 | 30-MAR-15:05 | 27.80 | 17.14 | 0.166164E+09 | 112.17 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.239881E+10 | 1378.69 | 17-APR-18:07 | 26.42 | 16.07 | 0.169868E+09 | 114.83 | 19-APR-21:19 | 18.53 | 16.00 |
May | 0.273244E+10 | 1373.75 | 16-MAY-18:02 | 28.22 | 17.07 | 0.185686E+09 | 119.21 | 31-MAY-22:10 | 21.73 | 18.83 |
June | 0.295832E+10 | 1611.22 | 28-JUN-21:00 | 26.10 | 21.77 | 0.191682E+09 | 120.45 | 22-JUN-21:30 | 26.10 | 21.77 |
July | 0.321240E+10 | 1869.46 | 07-JUL-21:00 | 30.60 | 22.80 | 0.200209E+09 | 120.45 | 13-JUL-21:19 | 23.30 | 21.29 |
August | 0.323678E+10 | 1821.83 | 18-AUG-21:00 | 31.10 | 22.83 | 0.202250E+09 | 120.45 | 02-AUG-21:19 | 31.10 | 22.83 |
September | 0.278284E+10 | 1515.63 | 07-SEP-21:00 | 25.60 | 21.61 | 0.186227E+09 | 120.45 | 11-SEP-21:19 | 22.97 | 20.08 |
October | 0.247576E+10 | 1218.50 | 11-OCT-18:10 | 21.73 | 13.14 | 0.175791E+09 | 115.72 | 19-OCT-21:19 | 17.03 | 15.75 |
November | 0.208083E+10 | 1076.35 | 05-NOV-10:33 | 18.33 | 17.01 | 0.159015E+09 | 107.82 | 06-NOV-22:10 | 11.02 | 5.78 |
December | 0.161341E+10 | 1030.26 | 13-DEC-19:10 | 16.10 | 16.05 | 0.155264E+09 | 105.11 | 13-DEC-22:10 | 13.22 | 12.84 |
Annual Sum or Average | 0.279039E+11 | 0.208643E+10 | ||||||||
Minimum of Months | 0.925327E+09 | 941.99 | 12.80 | 8.84 | 0.141534E+09 | 99.01 | 11.02 | 5.78 | ||
Maximum of Months | 0.323678E+10 | 1869.46 | 31.10 | 22.83 | 0.202250E+09 | 120.45 | 31.10 | 22.83 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.333506E+09 | 483.07 | 31-JAN-21:00 | 17.20 | 12.43 | 0.117048E+09 | 73.76 | 31-JAN-23:10 | 12.22 | 9.67 |
February | 0.585750E+09 | 545.00 | 28-FEB-19:00 | 21.70 | 12.09 | 0.107830E+09 | 79.14 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.114994E+10 | 688.45 | 30-MAR-15:05 | 27.80 | 17.14 | 0.125756E+09 | 84.01 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.126411E+10 | 730.77 | 17-APR-18:07 | 26.42 | 16.07 | 0.128411E+09 | 85.36 | 19-APR-21:49 | 17.98 | 15.78 |
May | 0.144522E+10 | 732.29 | 16-MAY-18:02 | 28.22 | 17.07 | 0.140521E+09 | 88.77 | 31-MAY-22:10 | 21.73 | 18.83 |
June | 0.154879E+10 | 757.08 | 25-JUN-10:33 | 29.80 | 23.29 | 0.145491E+09 | 92.64 | 28-JUN-22:10 | 26.10 | 21.34 |
July | 0.166367E+10 | 824.53 | 07-JUL-21:00 | 30.60 | 22.80 | 0.152611E+09 | 92.66 | 13-JUL-21:19 | 23.30 | 21.29 |
August | 0.167198E+10 | 805.85 | 18-AUG-21:00 | 31.10 | 22.83 | 0.154312E+09 | 92.66 | 02-AUG-21:19 | 31.10 | 22.83 |
September | 0.146802E+10 | 739.89 | 09-SEP-10:33 | 30.03 | 23.84 | 0.140944E+09 | 91.95 | 07-SEP-22:10 | 30.03 | 23.84 |
October | 0.130273E+10 | 644.56 | 11-OCT-10:33 | 24.67 | 19.78 | 0.132812E+09 | 86.08 | 18-OCT-22:10 | 22.80 | 22.03 |
November | 0.106916E+10 | 572.22 | 05-NOV-10:33 | 18.33 | 17.01 | 0.120229E+09 | 79.97 | 03-NOV-22:10 | 18.33 | 17.01 |
December | 0.723409E+09 | 536.55 | 13-DEC-11:33 | 19.80 | 17.47 | 0.118242E+09 | 78.15 | 13-DEC-23:10 | 12.62 | 12.25 |
Annual Sum or Average | 0.142263E+11 | 0.158421E+10 | ||||||||
Minimum of Months | 0.333506E+09 | 483.07 | 17.20 | 12.09 | 0.107830E+09 | 73.76 | 12.22 | 9.67 | ||
Maximum of Months | 0.167198E+10 | 824.53 | 31.10 | 23.84 | 0.154312E+09 | 92.66 | 31.10 | 23.84 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.481934E+11 | 37171.46 | 31-JAN-21:00 | 17.20 | 12.43 | 0.571661E+09 | 381.63 | 24-JAN-22:10 | 17.20 | 12.43 |
February | 0.444235E+11 | 37719.65 | 28-FEB-21:00 | 20.60 | 11.78 | 0.519309E+09 | 381.68 | 28-FEB-22:10 | 18.63 | 10.80 |
March | 0.509805E+11 | 38143.31 | 30-MAR-20:00 | 24.40 | 16.98 | 0.581083E+09 | 381.70 | 27-MAR-21:10 | 24.40 | 16.98 |
April | 0.501499E+11 | 38371.62 | 14-APR-20:00 | 21.10 | 13.71 | 0.563276E+09 | 381.72 | 14-APR-21:10 | 19.53 | 13.39 |
May | 0.529316E+11 | 38864.92 | 16-MAY-19:25 | 26.10 | 16.87 | 0.583095E+09 | 381.85 | 19-MAY-21:10 | 23.62 | 16.17 |
June | 0.522073E+11 | 38922.18 | 13-JUN-20:00 | 29.40 | 21.98 | 0.566523E+09 | 381.72 | 27-JUN-21:10 | 27.02 | 21.02 |
July | 0.540814E+11 | 39122.13 | 07-JUL-20:00 | 31.10 | 23.22 | 0.584593E+09 | 381.74 | 18-JUL-21:10 | 22.80 | 21.57 |
August | 0.543872E+11 | 39000.93 | 02-AUG-20:00 | 30.60 | 23.37 | 0.586344E+09 | 381.73 | 15-AUG-21:10 | 26.52 | 23.10 |
September | 0.512815E+11 | 38789.67 | 07-SEP-20:00 | 27.20 | 22.45 | 0.564535E+09 | 382.52 | 15-SEP-21:10 | 24.82 | 18.06 |
October | 0.514651E+11 | 38184.77 | 10-OCT-20:00 | 22.20 | 19.19 | 0.580741E+09 | 381.76 | 26-OCT-21:10 | 10.82 | 8.42 |
November | 0.487731E+11 | 37593.72 | 03-NOV-20:00 | 18.90 | 16.38 | 0.560055E+09 | 381.78 | 10-NOV-22:10 | 12.62 | 10.31 |
December | 0.490352E+11 | 37438.28 | 12-DEC-21:00 | 18.30 | 14.62 | 0.574906E+09 | 381.78 | 11-DEC-22:10 | 18.30 | 14.62 |
Annual Sum or Average | 0.607910E+12 | 0.683612E+10 | ||||||||
Minimum of Months | 0.444235E+11 | 37171.46 | 17.20 | 11.78 | 0.519309E+09 | 381.63 | 10.82 | 8.42 | ||
Maximum of Months | 0.543872E+11 | 39122.13 | 31.10 | 23.37 | 0.586344E+09 | 382.52 | 27.02 | 23.10 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149407E+11 | 9657.58 | 29-JAN-13:00 | 13.90 | 6.14 | 0.928776E+10 | 6457.57 | 31-JAN-22:40 | 13.37 | 10.31 |
February | 0.147133E+11 | 9799.70 | 26-FEB-13:00 | 23.90 | 12.59 | 0.868743E+10 | 6462.49 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.185692E+11 | 10857.25 | 30-MAR-15:23 | 27.80 | 17.27 | 0.102743E+11 | 6462.55 | 13-MAR-22:10 | 27.80 | 17.27 |
April | 0.186437E+11 | 11192.20 | 15-APR-11:47 | 26.52 | 14.84 | 0.100275E+11 | 6462.71 | 24-APR-21:19 | 13.13 | 10.01 |
May | 0.202246E+11 | 10295.60 | 18-MAY-21:05 | 22.62 | 16.71 | 0.105502E+11 | 6462.67 | 10-MAY-21:40 | 22.62 | 16.71 |
June | 0.211067E+11 | 11133.02 | 13-JUN-21:10 | 28.12 | 21.63 | 0.103924E+11 | 6462.71 | 07-JUN-22:10 | 28.12 | 21.63 |
July | 0.225582E+11 | 11716.35 | 07-JUL-21:10 | 30.40 | 22.79 | 0.107507E+11 | 6462.70 | 18-JUL-22:10 | 22.80 | 21.57 |
August | 0.235308E+11 | 12096.51 | 18-AUG-21:10 | 30.82 | 22.88 | 0.108918E+11 | 6462.66 | 31-AUG-22:10 | 21.58 | 19.54 |
September | 0.210063E+11 | 11766.67 | 25-SEP-15:03 | 29.40 | 19.56 | 0.103557E+11 | 6462.66 | 11-SEP-22:10 | 29.40 | 19.56 |
October | 0.199238E+11 | 11906.08 | 10-OCT-15:03 | 29.08 | 20.63 | 0.104410E+11 | 6462.60 | 11-OCT-22:10 | 14.40 | 8.97 |
November | 0.178079E+11 | 10737.53 | 11-NOV-13:00 | 21.10 | 11.68 | 0.978232E+10 | 6462.39 | 02-NOV-22:10 | 21.10 | 11.68 |
December | 0.165532E+11 | 10462.05 | 10-DEC-13:00 | 15.60 | 7.72 | 0.963231E+10 | 6462.24 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.229578E+12 | 0.121074E+12 | ||||||||
Minimum of Months | 0.147133E+11 | 9657.58 | 13.90 | 6.14 | 0.868743E+10 | 6457.57 | 13.13 | 8.97 | ||
Maximum of Months | 0.235308E+11 | 12096.51 | 30.82 | 22.88 | 0.108918E+11 | 6462.71 | 29.40 | 21.63 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.547522E+11 | 27739.32 | 31-JAN-22:20 | 14.13 | 10.68 | 0.284276E+11 | 19185.06 | 31-JAN-22:49 | 12.98 | 10.12 |
February | 0.524634E+11 | 33082.42 | 28-FEB-22:10 | 18.63 | 10.80 | 0.264424E+11 | 19185.81 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.641464E+11 | 36553.98 | 30-MAR-21:05 | 23.72 | 16.82 | 0.309464E+11 | 19185.99 | 13-MAR-22:10 | 23.72 | 16.82 |
April | 0.649704E+11 | 35940.79 | 17-APR-21:10 | 20.00 | 14.08 | 0.302935E+11 | 19186.13 | 24-APR-21:19 | 13.13 | 10.01 |
May | 0.711306E+11 | 37525.81 | 19-MAY-21:05 | 23.62 | 16.17 | 0.317315E+11 | 19186.09 | 10-MAY-21:40 | 23.62 | 16.17 |
June | 0.744904E+11 | 39889.77 | 13-JUN-21:10 | 28.12 | 21.63 | 0.310784E+11 | 19186.16 | 08-JUN-22:10 | 28.12 | 21.63 |
July | 0.791071E+11 | 41834.18 | 07-JUL-21:10 | 30.40 | 22.79 | 0.320708E+11 | 19186.14 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.811543E+11 | 42629.02 | 18-AUG-21:10 | 30.82 | 22.88 | 0.323361E+11 | 19186.08 | 31-AUG-22:10 | 21.58 | 19.54 |
September | 0.726165E+11 | 40947.53 | 07-SEP-21:10 | 25.40 | 21.43 | 0.310016E+11 | 19186.10 | 14-SEP-22:10 | 18.62 | 13.88 |
October | 0.682068E+11 | 38153.96 | 10-OCT-21:10 | 21.10 | 18.77 | 0.314308E+11 | 19186.00 | 11-OCT-22:10 | 14.40 | 8.97 |
November | 0.613612E+11 | 32610.65 | 06-NOV-22:10 | 11.02 | 5.78 | 0.297226E+11 | 19185.73 | 03-NOV-22:10 | 11.02 | 5.78 |
December | 0.587628E+11 | 32190.78 | 12-DEC-22:10 | 18.30 | 14.66 | 0.295032E+11 | 19185.54 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.803162E+12 | 0.364985E+12 | ||||||||
Minimum of Months | 0.524634E+11 | 27739.32 | 11.02 | 5.78 | 0.264424E+11 | 19185.06 | 11.02 | 5.78 | ||
Maximum of Months | 0.811543E+11 | 42629.02 | 30.82 | 22.88 | 0.323361E+11 | 19186.16 | 28.12 | 21.63 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 64571205.87 | 2576.92 | 29-JAN-16:01 | 16.52 | 6.64 | 94567382.62 | 56.69 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 0.222558E+09 | 2820.17 | 27-FEB-16:01 | 22.70 | 11.34 | 86285596.02 | 57.29 | 16-FEB-22:49 | 22.70 | 11.34 |
March | 0.735167E+09 | 2725.19 | 10-MAR-16:01 | 20.10 | 8.83 | 97846323.64 | 60.69 | 23-MAR-21:30 | 15.00 | 10.40 |
April | 0.119811E+10 | 2770.17 | 09-APR-18:01 | 20.45 | 11.08 | 95252747.04 | 56.69 | 19-APR-21:30 | 18.35 | 15.93 |
May | 0.166804E+10 | 2789.28 | 30-MAY-18:02 | 27.43 | 22.23 | 98855364.22 | 56.69 | 03-MAY-21:49 | 27.43 | 22.23 |
June | 0.217109E+10 | 2778.47 | 16-JUN-18:02 | 27.85 | 20.92 | 95921387.25 | 56.70 | 29-JUN-00:49 | 24.60 | 20.61 |
July | 0.242066E+10 | 2832.18 | 12-JUL-18:02 | 32.02 | 22.51 | 99043523.17 | 56.70 | 07-JUL-21:49 | 32.02 | 22.51 |
August | 0.254068E+10 | 2827.12 | 18-AUG-18:02 | 33.72 | 23.57 | 99192811.46 | 56.70 | 18-AUG-21:00 | 29.40 | 23.06 |
September | 0.176114E+10 | 2778.83 | 10-SEP-15:02 | 27.38 | 22.13 | 95624412.75 | 56.70 | 07-SEP-00:40 | 27.38 | 22.13 |
October | 0.987104E+09 | 2721.33 | 02-OCT-15:02 | 26.70 | 20.27 | 97963440.79 | 56.69 | 10-OCT-21:00 | 21.10 | 18.56 |
November | 0.398327E+09 | 2694.19 | 14-NOV-16:01 | 19.13 | 9.12 | 94013382.73 | 56.69 | 05-NOV-23:10 | 19.13 | 9.12 |
December | 0.122663E+09 | 2539.84 | 11-DEC-16:01 | 21.02 | 15.88 | 95467196.21 | 56.69 | 13-DEC-00:10 | 17.62 | 14.70 |
Annual Sum or Average | 0.142901E+11 | 0.115003E+10 | ||||||||
Minimum of Months | 64571205.87 | 2539.84 | 16.52 | 6.64 | 86285596.02 | 56.69 | 14.52 | 9.12 | ||
Maximum of Months | 0.254068E+10 | 2832.18 | 33.72 | 23.57 | 99192811.46 | 60.69 | 32.02 | 23.06 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18222516.39 | 2340.34 | 29-JAN-16:01 | 16.52 | 6.64 | 93353478.23 | 57.47 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 85066769.16 | 2757.27 | 27-FEB-16:01 | 22.70 | 11.34 | 86086812.44 | 67.03 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.404684E+09 | 2720.18 | 11-MAR-16:01 | 26.02 | 16.23 | 99759584.84 | 72.38 | 29-MAR-21:10 | 22.62 | 17.00 |
April | 0.863670E+09 | 2788.72 | 11-APR-15:01 | 27.70 | 16.39 | 0.100069E+09 | 75.69 | 14-APR-21:40 | 18.13 | 12.83 |
May | 0.138595E+10 | 2777.38 | 09-MAY-20:41 | 13.68 | 6.54 | 0.105063E+09 | 76.53 | 09-MAY-18:10 | 13.68 | 6.54 |
June | 0.201732E+10 | 2826.89 | 05-JUN-18:02 | 30.82 | 19.88 | 99758344.88 | 83.02 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.225424E+10 | 2830.22 | 21-JUL-18:02 | 33.03 | 22.93 | 0.102667E+09 | 80.91 | 18-JUL-21:10 | 33.03 | 22.93 |
August | 0.230470E+10 | 2788.69 | 18-AUG-18:02 | 33.72 | 23.57 | 0.101731E+09 | 76.42 | 07-AUG-21:00 | 33.72 | 23.57 |
September | 0.139753E+10 | 3062.43 | 18-SEP-16:01 | 25.40 | 17.60 | 0.100111E+09 | 76.15 | 11-SEP-21:00 | 25.40 | 17.60 |
October | 0.557107E+09 | 2806.89 | 07-OCT-16:21 | 23.85 | 13.02 | 0.101026E+09 | 72.98 | 10-OCT-21:10 | 21.10 | 18.77 |
November | 0.157532E+09 | 2628.39 | 14-NOV-16:01 | 19.13 | 9.12 | 93872339.75 | 63.07 | 02-NOV-21:40 | 19.13 | 9.12 |
December | 39402188.78 | 2385.07 | 11-DEC-16:01 | 21.02 | 15.88 | 94234635.77 | 60.83 | 12-DEC-22:30 | 18.30 | 14.75 |
Annual Sum or Average | 0.114854E+11 | 0.117773E+10 | ||||||||
Minimum of Months | 18222516.39 | 2340.34 | 13.68 | 6.54 | 86086812.44 | 57.47 | 13.68 | 6.54 | ||
Maximum of Months | 0.230470E+10 | 3062.43 | 33.72 | 23.57 | 0.105063E+09 | 83.02 | 33.72 | 23.57 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38836553.40 | 362.69 | 29-JAN-13:30 | 14.45 | 6.22 | 0.00 | 0.00 | 01-JAN-00:10 | 14.45 | 6.22 |
February | 0.100869E+09 | 423.88 | 26-FEB-14:50 | 24.90 | 12.71 | 0.00 | 0.00 | 01-FEB-00:10 | 24.90 | 12.71 |
March | 0.267136E+09 | 389.39 | 30-MAR-13:40 | 27.43 | 17.97 | 0.00 | 0.00 | 01-MAR-00:10 | 27.43 | 17.97 |
April | 0.306211E+09 | 372.41 | 15-APR-14:00 | 27.80 | 15.01 | 0.00 | 0.00 | 01-APR-00:10 | 27.80 | 15.01 |
May | 0.382327E+09 | 303.58 | 06-MAY-13:40 | 28.30 | 19.41 | 0.00 | 0.00 | 01-MAY-00:10 | 28.30 | 19.41 |
June | 0.485374E+09 | 328.76 | 24-JUN-17:20 | 32.60 | 22.26 | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 22.26 |
July | 0.562410E+09 | 370.19 | 08-JUL-17:30 | 34.40 | 23.36 | 0.00 | 0.00 | 01-JUL-00:10 | 34.40 | 23.36 |
August | 0.646263E+09 | 431.49 | 19-AUG-13:50 | 33.80 | 23.78 | 0.00 | 0.00 | 01-AUG-00:10 | 33.80 | 23.78 |
September | 0.505399E+09 | 496.62 | 24-SEP-12:50 | 28.80 | 19.88 | 0.00 | 0.00 | 01-SEP-00:10 | 28.80 | 19.88 |
October | 0.389730E+09 | 529.74 | 10-OCT-13:30 | 28.85 | 20.88 | 0.00 | 0.00 | 01-OCT-00:10 | 28.85 | 20.88 |
November | 0.256871E+09 | 476.21 | 15-NOV-14:00 | 21.10 | 11.33 | 0.00 | 0.00 | 01-NOV-00:10 | 21.10 | 11.33 |
December | 0.130308E+09 | 465.23 | 10-DEC-14:25 | 17.50 | 8.24 | 0.00 | 0.00 | 01-DEC-00:10 | 17.50 | 8.24 |
Annual Sum or Average | 0.407173E+10 | 0.00 | ||||||||
Minimum of Months | 38836553.40 | 303.58 | 14.45 | 6.22 | 0.00 | 0.00 | 14.45 | 6.22 | ||
Maximum of Months | 0.646263E+09 | 529.74 | 34.40 | 23.78 | 0.00 | 0.00 | 34.40 | 23.78 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 57780662.64 | 823.19 | 31-JAN-16:01 | 19.90 | 13.55 | 95030370.53 | 64.41 | 31-JAN-22:19 | 14.13 | 10.68 |
February | 0.133955E+09 | 956.50 | 27-FEB-16:01 | 22.70 | 11.34 | 87002957.75 | 69.09 | 28-FEB-22:00 | 17.30 | 10.02 |
March | 0.320709E+09 | 974.76 | 29-MAR-18:02 | 25.50 | 17.73 | 98670778.46 | 70.57 | 28-MAR-21:10 | 25.50 | 17.73 |
April | 0.466457E+09 | 990.28 | 11-APR-15:01 | 27.70 | 16.39 | 98371016.86 | 73.53 | 24-APR-21:10 | 13.22 | 9.86 |
May | 0.649010E+09 | 997.31 | 30-MAY-18:02 | 27.43 | 22.23 | 0.103309E+09 | 74.09 | 31-MAY-21:10 | 22.13 | 18.80 |
June | 0.833153E+09 | 1007.68 | 11-JUN-08:51 | 23.30 | 14.13 | 98669164.65 | 78.29 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.905815E+09 | 997.47 | 26-JUL-18:02 | 30.13 | 24.13 | 0.101888E+09 | 77.08 | 25-JUL-21:10 | 30.13 | 24.13 |
August | 0.899191E+09 | 1002.59 | 19-AUG-15:02 | 33.22 | 24.02 | 0.101039E+09 | 75.32 | 31-AUG-21:30 | 21.65 | 19.90 |
September | 0.641342E+09 | 984.82 | 06-SEP-18:02 | 29.13 | 22.99 | 99221935.93 | 75.62 | 01-SEP-21:10 | 29.13 | 22.99 |
October | 0.390345E+09 | 983.44 | 17-OCT-18:01 | 24.32 | 20.52 | 0.100009E+09 | 72.80 | 18-OCT-21:10 | 23.22 | 22.46 |
November | 0.230624E+09 | 892.40 | 08-NOV-16:02 | 21.60 | 10.05 | 94411263.64 | 68.62 | 03-NOV-21:49 | 21.60 | 10.05 |
December | 0.106780E+09 | 831.98 | 11-DEC-16:01 | 21.02 | 15.88 | 95746936.82 | 65.48 | 12-DEC-22:49 | 18.30 | 14.83 |
Annual Sum or Average | 0.563516E+10 | 0.117337E+10 | ||||||||
Minimum of Months | 57780662.64 | 823.19 | 19.90 | 10.05 | 87002957.75 | 64.41 | 13.22 | 9.86 | ||
Maximum of Months | 0.905815E+09 | 1007.68 | 33.22 | 24.13 | 0.103309E+09 | 78.29 | 30.13 | 24.13 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 54236828.61 | 2332.73 | 29-JAN-16:01 | 16.52 | 6.64 | 94698175.85 | 56.69 | 31-JAN-22:49 | 12.98 | 10.12 |
February | 0.236498E+09 | 2550.51 | 27-FEB-16:01 | 22.70 | 11.34 | 86473256.33 | 56.83 | 16-FEB-22:49 | 22.70 | 11.34 |
March | 0.671498E+09 | 2536.47 | 11-MAR-16:01 | 26.02 | 16.23 | 98015006.60 | 57.65 | 23-MAR-21:30 | 15.00 | 10.40 |
April | 0.116629E+10 | 2497.70 | 17-APR-18:02 | 26.42 | 16.07 | 95494319.66 | 56.69 | 19-APR-21:00 | 17.80 | 15.70 |
May | 0.170889E+10 | 2544.37 | 17-MAY-18:02 | 28.03 | 17.41 | 99037230.78 | 56.69 | 30-MAY-21:10 | 23.62 | 21.16 |
June | 0.222323E+10 | 2551.52 | 22-JUN-18:02 | 30.40 | 22.95 | 96015146.43 | 56.70 | 13-JUN-21:10 | 30.40 | 22.95 |
July | 0.250283E+10 | 2561.18 | 14-JUL-08:62 | 27.48 | 22.50 | 99088020.34 | 56.70 | 10-JUL-21:10 | 27.48 | 22.50 |
August | 0.255896E+10 | 2551.22 | 04-AUG-18:02 | 28.80 | 23.56 | 99224415.17 | 56.70 | 17-AUG-21:19 | 28.53 | 23.54 |
September | 0.177145E+10 | 2540.08 | 06-SEP-18:02 | 29.13 | 22.99 | 95706689.78 | 56.69 | 12-SEP-23:49 | 21.38 | 18.58 |
October | 0.967635E+09 | 2478.55 | 02-OCT-15:02 | 26.70 | 20.27 | 98111454.83 | 56.69 | 02-OCT-21:30 | 19.20 | 17.02 |
November | 0.376176E+09 | 2426.98 | 14-NOV-16:01 | 19.13 | 9.12 | 94229308.34 | 56.69 | 02-NOV-21:19 | 19.13 | 9.12 |
December | 0.116799E+09 | 2256.42 | 11-DEC-16:01 | 21.02 | 15.88 | 95632122.21 | 56.69 | 11-DEC-22:40 | 15.60 | 13.95 |
Annual Sum or Average | 0.143545E+11 | 0.115173E+10 | ||||||||
Minimum of Months | 54236828.61 | 2256.42 | 16.52 | 6.64 | 86473256.33 | 56.69 | 12.98 | 9.12 | ||
Maximum of Months | 0.255896E+10 | 2561.18 | 30.40 | 23.56 | 99224415.17 | 57.65 | 30.40 | 23.54 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18756391.14 | 2022.72 | 31-JAN-16:01 | 19.90 | 13.55 | 93419615.16 | 58.07 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 0.108007E+09 | 2502.61 | 27-FEB-16:01 | 22.70 | 11.34 | 86044679.89 | 66.26 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.383176E+09 | 2445.53 | 30-MAR-18:02 | 26.02 | 17.62 | 98977948.29 | 68.90 | 29-MAR-21:10 | 26.02 | 17.62 |
April | 0.858161E+09 | 2613.99 | 16-APR-08:51 | 21.10 | 14.17 | 99363789.46 | 73.01 | 17-APR-21:00 | 20.00 | 13.85 |
May | 0.142269E+10 | 2797.95 | 18-MAY-08:51 | 24.40 | 17.97 | 0.104812E+09 | 76.87 | 31-MAY-21:10 | 22.13 | 18.80 |
June | 0.203836E+10 | 2814.46 | 06-JUN-08:51 | 26.10 | 19.70 | 0.100102E+09 | 79.53 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.229918E+10 | 2689.95 | 17-JUL-08:51 | 26.10 | 21.47 | 0.103272E+09 | 81.40 | 25-JUL-21:10 | 22.80 | 21.95 |
August | 0.230456E+10 | 2717.47 | 26-AUG-08:51 | 24.40 | 19.19 | 0.102017E+09 | 78.07 | 07-AUG-21:00 | 24.40 | 19.19 |
September | 0.139497E+10 | 2699.70 | 15-SEP-08:51 | 21.70 | 14.94 | 0.100174E+09 | 75.33 | 01-SEP-21:10 | 21.70 | 14.94 |
October | 0.564540E+09 | 2467.57 | 10-OCT-18:02 | 25.63 | 20.24 | 0.100376E+09 | 72.13 | 17-OCT-21:10 | 23.22 | 20.61 |
November | 0.158650E+09 | 2253.97 | 06-NOV-16:01 | 20.32 | 10.34 | 93490289.73 | 63.47 | 03-NOV-21:40 | 20.32 | 10.34 |
December | 36817778.24 | 1963.17 | 11-DEC-16:01 | 21.02 | 15.88 | 94233197.72 | 60.29 | 12-DEC-22:30 | 18.30 | 14.75 |
Annual Sum or Average | 0.115879E+11 | 0.117628E+10 | ||||||||
Minimum of Months | 18756391.14 | 1963.17 | 19.90 | 10.34 | 86044679.89 | 58.07 | 14.52 | 10.34 | ||
Maximum of Months | 0.230456E+10 | 2814.46 | 26.10 | 21.47 | 0.104812E+09 | 81.40 | 26.02 | 21.95 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143945E+10 | 1326.44 | 29-JAN-11:33 | 12.43 | 5.39 | 0.120188E+10 | 744.37 | 31-JAN-22:49 | 12.98 | 10.12 |
February | 0.186321E+10 | 1557.51 | 27-FEB-19:10 | 19.82 | 10.52 | 0.111141E+10 | 819.29 | 28-FEB-22:49 | 17.57 | 10.18 |
March | 0.334896E+10 | 1916.94 | 30-MAR-15:05 | 27.80 | 17.14 | 0.132092E+10 | 849.73 | 30-MAR-22:10 | 22.62 | 16.35 |
April | 0.362667E+10 | 2094.19 | 17-APR-18:07 | 26.42 | 16.07 | 0.135449E+10 | 889.78 | 19-APR-21:49 | 17.98 | 15.78 |
May | 0.406541E+10 | 2054.86 | 16-MAY-18:02 | 28.22 | 17.07 | 0.146348E+10 | 907.78 | 19-MAY-22:10 | 21.93 | 15.69 |
June | 0.429887E+10 | 2084.41 | 25-JUN-10:33 | 29.80 | 23.29 | 0.149997E+10 | 949.31 | 29-JUN-21:49 | 25.18 | 21.75 |
July | 0.461407E+10 | 2156.26 | 08-JUL-17:50 | 34.40 | 23.36 | 0.157643E+10 | 951.85 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.463813E+10 | 2256.50 | 18-AUG-18:20 | 33.53 | 23.50 | 0.159181E+10 | 951.84 | 16-AUG-23:19 | 33.53 | 23.50 |
September | 0.411178E+10 | 2058.62 | 09-SEP-10:33 | 30.03 | 23.84 | 0.146352E+10 | 940.26 | 08-SEP-21:49 | 30.03 | 23.84 |
October | 0.363069E+10 | 1829.59 | 11-OCT-18:10 | 21.73 | 13.14 | 0.137922E+10 | 887.88 | 11-OCT-21:40 | 14.97 | 9.20 |
November | 0.296506E+10 | 1538.83 | 11-NOV-11:33 | 18.50 | 11.57 | 0.122773E+10 | 802.66 | 08-NOV-22:49 | 18.50 | 11.57 |
December | 0.213953E+10 | 1425.51 | 13-DEC-19:10 | 16.10 | 16.05 | 0.121325E+10 | 778.41 | 12-DEC-23:10 | 16.10 | 16.05 |
Annual Sum or Average | 0.407418E+11 | 0.164041E+11 | ||||||||
Minimum of Months | 0.143945E+10 | 1326.44 | 12.43 | 5.39 | 0.111141E+10 | 744.37 | 12.98 | 9.20 | ||
Maximum of Months | 0.463813E+10 | 2256.50 | 34.40 | 23.84 | 0.159181E+10 | 951.85 | 33.53 | 23.84 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 46622847.74 | 2700.71 | 29-JAN-16:01 | 16.52 | 6.64 | 93868396.77 | 56.69 | 31-JAN-22:10 | 14.52 | 10.85 |
February | 0.189938E+09 | 2970.50 | 27-FEB-16:01 | 22.70 | 11.34 | 85711510.62 | 56.69 | 28-FEB-03:30 | 11.95 | 6.66 |
March | 0.655108E+09 | 2868.12 | 10-MAR-16:01 | 20.10 | 8.83 | 97476284.69 | 58.99 | 23-MAR-21:30 | 15.00 | 10.40 |
April | 0.114309E+10 | 2920.95 | 09-APR-18:01 | 20.45 | 11.08 | 95056771.88 | 56.69 | 05-APR-02:00 | 20.45 | 11.08 |
May | 0.166892E+10 | 2916.94 | 10-MAY-18:01 | 20.92 | 10.48 | 98764289.39 | 56.70 | 12-MAY-04:10 | 12.12 | 9.75 |
June | 0.220991E+10 | 2992.53 | 05-JUN-18:02 | 30.82 | 19.88 | 95880884.80 | 56.70 | 27-JUN-21:10 | 27.02 | 21.02 |
July | 0.247770E+10 | 3009.89 | 07-JUL-18:02 | 33.80 | 23.16 | 99007537.26 | 56.70 | 06-JUL-21:10 | 33.80 | 23.16 |
August | 0.259913E+10 | 3007.03 | 18-AUG-18:02 | 33.72 | 23.57 | 99172342.26 | 56.70 | 18-AUG-21:40 | 29.97 | 23.01 |
September | 0.170902E+10 | 2907.89 | 03-SEP-15:02 | 29.50 | 22.84 | 95507583.53 | 56.70 | 05-SEP-22:00 | 26.10 | 21.15 |
October | 0.877917E+09 | 2801.43 | 02-OCT-18:02 | 24.22 | 19.50 | 97640215.16 | 56.69 | 13-OCT-01:10 | 8.80 | 6.36 |
November | 0.322250E+09 | 2831.10 | 14-NOV-16:01 | 19.13 | 9.12 | 93578801.60 | 56.69 | 01-NOV-21:19 | 19.13 | 9.12 |
December | 93495337.20 | 2652.65 | 11-DEC-16:01 | 21.02 | 15.88 | 94776425.00 | 56.69 | 12-DEC-23:10 | 18.22 | 14.85 |
Annual Sum or Average | 0.139931E+11 | 0.114644E+10 | ||||||||
Minimum of Months | 46622847.74 | 2652.65 | 16.52 | 6.64 | 85711510.62 | 56.69 | 8.80 | 6.36 | ||
Maximum of Months | 0.259913E+10 | 3009.89 | 33.80 | 23.57 | 99172342.26 | 58.99 | 33.80 | 23.16 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12688930.64 | 2033.48 | 29-JAN-16:01 | 16.52 | 6.64 | 92809146.30 | 56.69 | 08-JAN-02:20 | 16.52 | 6.64 |
February | 64456403.19 | 2894.96 | 27-FEB-16:01 | 22.70 | 11.34 | 85601014.41 | 66.63 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.342076E+09 | 2898.22 | 30-MAR-15:02 | 27.80 | 17.14 | 99242151.91 | 72.52 | 29-MAR-21:10 | 27.80 | 17.14 |
April | 0.820684E+09 | 2922.45 | 09-APR-20:11 | 13.70 | 8.28 | 0.100066E+09 | 77.06 | 14-APR-21:40 | 18.13 | 12.83 |
May | 0.142165E+10 | 2982.44 | 09-MAY-20:41 | 13.68 | 6.54 | 0.105040E+09 | 79.04 | 09-MAY-18:10 | 13.68 | 6.54 |
June | 0.209056E+10 | 2953.70 | 05-JUN-18:02 | 30.82 | 19.88 | 99529331.50 | 84.46 | 26-JUN-21:10 | 23.22 | 21.66 |
July | 0.234651E+10 | 2975.77 | 12-JUL-18:02 | 32.02 | 22.51 | 0.102341E+09 | 80.92 | 18-JUL-21:19 | 22.80 | 21.57 |
August | 0.238423E+10 | 2977.28 | 18-AUG-18:02 | 33.72 | 23.57 | 0.101478E+09 | 76.09 | 07-AUG-21:00 | 33.72 | 23.57 |
September | 0.137405E+10 | 3248.75 | 18-SEP-16:01 | 25.40 | 17.60 | 99666907.34 | 75.64 | 11-SEP-21:00 | 25.40 | 17.60 |
October | 0.468189E+09 | 2961.26 | 07-OCT-16:21 | 23.85 | 13.02 | 0.100428E+09 | 72.68 | 10-OCT-21:19 | 21.10 | 18.73 |
November | 0.113395E+09 | 2748.99 | 14-NOV-16:01 | 19.13 | 9.12 | 93186727.05 | 62.12 | 02-NOV-21:40 | 19.13 | 9.12 |
December | 26375411.92 | 2428.20 | 11-DEC-16:01 | 21.02 | 15.88 | 93499377.71 | 59.24 | 12-DEC-22:30 | 18.30 | 14.75 |
Annual Sum or Average | 0.114649E+11 | 0.117289E+10 | ||||||||
Minimum of Months | 12688930.64 | 2033.48 | 13.68 | 6.54 | 85601014.41 | 56.69 | 13.68 | 6.54 | ||
Maximum of Months | 0.238423E+10 | 3248.75 | 33.72 | 23.57 | 0.105040E+09 | 84.46 | 33.72 | 23.57 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189372E+09 | 1419.51 | 29-JAN-16:01 | 16.52 | 6.64 | 96284258.66 | 58.08 | 19-JAN-22:49 | 16.52 | 6.64 |
February | 0.293032E+09 | 1492.34 | 28-FEB-19:01 | 21.52 | 12.04 | 87498912.13 | 61.79 | 16-FEB-22:49 | 21.52 | 12.04 |
March | 0.609152E+09 | 1506.23 | 30-MAR-18:02 | 26.02 | 17.62 | 98137499.28 | 63.37 | 23-MAR-21:30 | 26.02 | 17.62 |
April | 0.744463E+09 | 1505.21 | 17-APR-18:02 | 26.42 | 16.07 | 95241124.98 | 56.69 | 20-APR-21:49 | 18.90 | 15.37 |
May | 0.946484E+09 | 1510.99 | 16-MAY-18:02 | 28.22 | 17.07 | 98774168.31 | 56.69 | 19-MAY-21:10 | 23.62 | 16.17 |
June | 0.119644E+10 | 1519.68 | 20-JUN-18:02 | 30.32 | 22.34 | 95873020.47 | 56.70 | 12-JUN-21:10 | 30.32 | 22.34 |
July | 0.136522E+10 | 1518.49 | 11-JUL-18:02 | 27.85 | 21.78 | 99000156.12 | 56.70 | 11-JUL-21:10 | 26.52 | 20.92 |
August | 0.152009E+10 | 1544.38 | 19-AUG-15:02 | 33.22 | 24.02 | 99182410.73 | 56.70 | 01-AUG-21:00 | 33.22 | 24.02 |
September | 0.115298E+10 | 1548.56 | 11-SEP-15:02 | 29.50 | 23.02 | 95609693.32 | 56.70 | 07-SEP-21:40 | 29.50 | 23.02 |
October | 0.848027E+09 | 1533.18 | 08-OCT-15:02 | 27.20 | 18.90 | 98247609.39 | 56.69 | 02-OCT-22:49 | 27.20 | 18.90 |
November | 0.559239E+09 | 1482.56 | 14-NOV-16:01 | 19.13 | 9.12 | 94914609.39 | 56.69 | 08-NOV-22:19 | 19.13 | 9.12 |
December | 0.318075E+09 | 1401.29 | 19-DEC-16:02 | 14.32 | 5.15 | 96937077.67 | 56.69 | 12-DEC-22:30 | 14.32 | 5.15 |
Annual Sum or Average | 0.974258E+10 | 0.115570E+10 | ||||||||
Minimum of Months | 0.189372E+09 | 1401.29 | 14.32 | 5.15 | 87498912.13 | 56.69 | 14.32 | 5.15 | ||
Maximum of Months | 0.152009E+10 | 1548.56 | 33.22 | 24.02 | 99182410.73 | 63.37 | 33.22 | 24.02 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.305294E+11 | 18423.54 | 19-JAN-22:57 | 18.30 | 16.51 | 0.183670E+11 | 11348.14 | 25-JAN-00:20 | 7.43 | 5.00 |
February | 0.292740E+11 | 19645.38 | 28-FEB-22:53 | 17.30 | 10.02 | 0.168302E+11 | 11348.56 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.358817E+11 | 21161.67 | 30-MAR-21:53 | 22.80 | 16.45 | 0.190682E+11 | 11348.66 | 13-MAR-22:10 | 22.80 | 16.45 |
April | 0.371170E+11 | 21227.26 | 18-APR-21:53 | 19.40 | 14.44 | 0.185489E+11 | 11348.99 | 24-APR-21:19 | 13.13 | 10.01 |
May | 0.411275E+11 | 21982.83 | 19-MAY-21:05 | 23.62 | 16.17 | 0.192622E+11 | 11348.96 | 16-MAY-22:10 | 23.62 | 16.17 |
June | 0.424984E+11 | 23021.64 | 13-JUN-22:00 | 27.20 | 20.99 | 0.187202E+11 | 11355.60 | 14-JUN-21:19 | 26.33 | 20.79 |
July | 0.446397E+11 | 23542.57 | 07-JUL-21:20 | 30.20 | 22.78 | 0.192751E+11 | 11357.48 | 17-JUL-21:19 | 25.93 | 20.55 |
August | 0.448012E+11 | 23270.99 | 18-AUG-21:20 | 30.53 | 22.93 | 0.193551E+11 | 11358.73 | 10-AUG-21:19 | 30.53 | 22.93 |
September | 0.399218E+11 | 22295.08 | 07-SEP-21:10 | 25.40 | 21.43 | 0.186219E+11 | 11348.95 | 11-SEP-22:10 | 23.22 | 19.91 |
October | 0.369483E+11 | 21111.19 | 18-OCT-21:53 | 22.80 | 21.95 | 0.190629E+11 | 11348.80 | 11-OCT-22:10 | 22.80 | 21.95 |
November | 0.331405E+11 | 19505.48 | 03-NOV-21:54 | 17.80 | 16.05 | 0.182454E+11 | 11348.33 | 02-NOV-22:10 | 17.80 | 16.05 |
December | 0.319611E+11 | 19114.49 | 12-DEC-22:55 | 18.30 | 14.87 | 0.186406E+11 | 11348.15 | 15-DEC-00:20 | 7.77 | 4.55 |
Annual Sum or Average | 0.447840E+12 | 0.223998E+12 | ||||||||
Minimum of Months | 0.292740E+11 | 18423.54 | 17.30 | 10.02 | 0.168302E+11 | 11348.14 | 7.43 | 4.55 | ||
Maximum of Months | 0.448012E+11 | 23542.57 | 30.53 | 22.93 | 0.193551E+11 | 11358.73 | 30.53 | 22.93 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.338042E+11 | 20450.62 | 19-JAN-22:57 | 18.30 | 16.51 | 0.186797E+11 | 11348.20 | 25-JAN-00:20 | 7.43 | 5.00 |
February | 0.323782E+11 | 21408.94 | 28-FEB-22:10 | 18.63 | 10.80 | 0.170474E+11 | 11348.57 | 28-FEB-23:10 | 17.02 | 9.75 |
March | 0.394175E+11 | 22684.08 | 30-MAR-21:05 | 23.72 | 16.82 | 0.192085E+11 | 11348.67 | 13-MAR-22:10 | 23.72 | 16.82 |
April | 0.404001E+11 | 22601.51 | 18-APR-21:10 | 19.90 | 15.31 | 0.186255E+11 | 11348.99 | 24-APR-21:19 | 13.13 | 10.01 |
May | 0.443353E+11 | 23307.98 | 30-MAY-21:05 | 23.62 | 21.16 | 0.193033E+11 | 11348.96 | 16-MAY-22:10 | 23.62 | 21.16 |
June | 0.453000E+11 | 24278.27 | 13-JUN-21:20 | 27.93 | 21.51 | 0.187386E+11 | 11367.70 | 14-JUN-21:19 | 26.33 | 20.79 |
July | 0.474661E+11 | 24768.72 | 07-JUL-21:20 | 30.20 | 22.78 | 0.192911E+11 | 11366.31 | 17-JUL-21:19 | 25.93 | 20.55 |
August | 0.475523E+11 | 24488.75 | 18-AUG-21:20 | 30.53 | 22.93 | 0.193705E+11 | 11367.25 | 10-AUG-21:19 | 30.53 | 22.93 |
September | 0.428464E+11 | 23543.29 | 07-SEP-21:10 | 25.40 | 21.43 | 0.186601E+11 | 11348.95 | 11-SEP-22:10 | 23.22 | 19.91 |
October | 0.403314E+11 | 22628.61 | 18-OCT-21:53 | 22.80 | 21.95 | 0.191696E+11 | 11348.81 | 11-OCT-22:10 | 22.80 | 21.95 |
November | 0.365454E+11 | 21303.33 | 03-NOV-21:54 | 17.80 | 16.05 | 0.184203E+11 | 11348.35 | 02-NOV-22:10 | 17.80 | 16.05 |
December | 0.354133E+11 | 20957.14 | 12-DEC-22:55 | 18.30 | 14.87 | 0.188806E+11 | 11348.21 | 15-DEC-00:20 | 7.77 | 4.55 |
Annual Sum or Average | 0.485790E+12 | 0.225395E+12 | ||||||||
Minimum of Months | 0.323782E+11 | 20450.62 | 17.80 | 10.80 | 0.170474E+11 | 11348.20 | 7.43 | 4.55 | ||
Maximum of Months | 0.475523E+11 | 24768.72 | 30.53 | 22.93 | 0.193705E+11 | 11367.70 | 30.53 | 22.93 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.459043E+11 | 25683.27 | 29-JAN-11:50 | 12.62 | 5.48 | 0.187750E+11 | 11319.65 | 07-JAN-18:19 | 12.62 | 5.48 |
February | 0.429854E+11 | 26873.39 | 26-FEB-11:45 | 22.43 | 11.86 | 0.169711E+11 | 11319.65 | 04-FEB-18:19 | 22.43 | 11.86 |
March | 0.504549E+11 | 28815.21 | 30-MAR-15:05 | 27.80 | 17.14 | 0.188189E+11 | 11319.57 | 18-MAR-17:19 | 27.80 | 17.14 |
April | 0.507113E+11 | 31027.31 | 16-APR-17:02 | 26.52 | 15.66 | 0.182212E+11 | 11343.08 | 15-APR-17:10 | 26.52 | 15.66 |
May | 0.542996E+11 | 30104.03 | 16-MAY-18:02 | 28.22 | 17.07 | 0.188403E+11 | 11319.67 | 06-MAY-17:19 | 28.22 | 17.07 |
June | 0.541468E+11 | 29481.00 | 11-JUN-10:40 | 26.13 | 15.22 | 0.182459E+11 | 11323.20 | 10-JUN-17:10 | 26.13 | 15.22 |
July | 0.564488E+11 | 29841.18 | 08-JUL-10:50 | 33.53 | 24.57 | 0.188511E+11 | 11319.67 | 15-JUL-17:19 | 33.30 | 24.04 |
August | 0.565233E+11 | 29710.83 | 27-AUG-10:33 | 29.47 | 22.52 | 0.188602E+11 | 11319.67 | 12-AUG-17:19 | 29.47 | 22.52 |
September | 0.525529E+11 | 29222.65 | 09-SEP-10:45 | 30.32 | 23.97 | 0.182347E+11 | 11319.68 | 23-SEP-17:19 | 27.23 | 18.81 |
October | 0.513498E+11 | 27950.88 | 09-OCT-10:33 | 23.67 | 17.95 | 0.188199E+11 | 11319.62 | 14-OCT-17:19 | 21.67 | 13.44 |
November | 0.476053E+11 | 26522.92 | 11-NOV-11:45 | 18.95 | 11.69 | 0.181946E+11 | 11319.56 | 25-NOV-18:19 | 13.53 | 7.66 |
December | 0.472412E+11 | 26098.86 | 12-DEC-11:45 | 20.22 | 16.28 | 0.187869E+11 | 11319.66 | 23-DEC-18:19 | 11.83 | 10.77 |
Annual Sum or Average | 0.610224E+12 | 0.221620E+12 | ||||||||
Minimum of Months | 0.429854E+11 | 25683.27 | 12.62 | 5.48 | 0.169711E+11 | 11319.56 | 11.83 | 5.48 | ||
Maximum of Months | 0.565233E+11 | 31027.31 | 33.53 | 24.57 | 0.188602E+11 | 11343.08 | 33.30 | 24.04 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.253695E+10 | 3068.01 | 29-JAN-11:33 | 12.43 | 5.39 | 0.127158E+10 | 792.43 | 31-JAN-22:40 | 13.37 | 10.31 |
February | 0.386363E+10 | 3592.42 | 27-FEB-18:12 | 21.13 | 11.05 | 0.116999E+10 | 863.37 | 28-FEB-22:40 | 17.83 | 10.34 |
March | 0.722289E+10 | 4719.91 | 30-MAR-15:05 | 27.80 | 17.14 | 0.136843E+10 | 929.86 | 30-MAR-21:00 | 22.80 | 16.45 |
April | 0.810226E+10 | 5012.01 | 17-APR-18:07 | 26.42 | 16.07 | 0.140874E+10 | 956.25 | 17-APR-21:40 | 20.00 | 13.94 |
May | 0.937639E+10 | 4927.33 | 16-MAY-18:02 | 28.22 | 17.07 | 0.154859E+10 | 988.55 | 19-MAY-21:30 | 23.05 | 15.97 |
June | 0.101123E+11 | 5325.57 | 24-JUN-17:13 | 32.60 | 22.26 | 0.160049E+10 | 1007.39 | 22-JUN-21:19 | 32.60 | 22.26 |
July | 0.110998E+11 | 6500.84 | 08-JUL-16:10 | 36.32 | 23.83 | 0.166691E+10 | 1007.40 | 13-JUL-22:10 | 23.48 | 21.29 |
August | 0.112162E+11 | 6391.47 | 18-AUG-15:03 | 34.50 | 23.13 | 0.169025E+10 | 1007.40 | 07-AUG-22:10 | 34.50 | 23.13 |
September | 0.932454E+10 | 5207.09 | 07-SEP-15:30 | 31.70 | 23.32 | 0.152787E+10 | 1007.39 | 07-SEP-21:40 | 24.80 | 20.88 |
October | 0.791850E+10 | 4315.07 | 10-OCT-17:12 | 27.97 | 20.36 | 0.141665E+10 | 937.00 | 10-OCT-21:40 | 21.10 | 18.64 |
November | 0.615125E+10 | 3605.37 | 05-NOV-17:12 | 21.10 | 17.61 | 0.127630E+10 | 841.95 | 05-NOV-23:19 | 14.43 | 14.43 |
December | 0.409641E+10 | 3339.96 | 13-DEC-11:33 | 19.80 | 17.47 | 0.127929E+10 | 832.45 | 12-DEC-23:10 | 19.80 | 17.47 |
Annual Sum or Average | 0.910212E+11 | 0.172251E+11 | ||||||||
Minimum of Months | 0.253695E+10 | 3068.01 | 12.43 | 5.39 | 0.116999E+10 | 792.43 | 13.37 | 10.31 | ||
Maximum of Months | 0.112162E+11 | 6500.84 | 36.32 | 23.83 | 0.169025E+10 | 1007.40 | 34.50 | 23.13 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.253328E+09 | 1081.23 | 08-JAN-05:30 | -5.3 |
February | 0.117367E+09 | 1289.67 | 12-FEB-06:00 | -12.2 |
March | 3876.87 | 18.19 | 23-MAR-08:03 | 6.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 5475319.14 | 399.12 | 21-NOV-07:05 | -2.8 |
December | 27584377.96 | 561.36 | 01-DEC-07:15 | -3.7 |
Annual Sum or Average | 0.403759E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.253328E+09 | 1289.67 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 53573587.30 | 387.51 | 08-JAN-13:50 | -0.7 |
February | 35517501.87 | 324.60 | 12-FEB-13:20 | -0.5 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 89091089.16 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 53573587.30 | 387.51 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 99526844.46 | 311.33 | 08-JAN-05:30 | -5.3 |
February | 58871232.82 | 299.20 | 12-FEB-09:03 | -10.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.70 |
December | 1117536.58 | 50.95 | 18-DEC-09:03 | -1.7 |
Annual Sum or Average | 0.159516E+09 | |||
Minimum of Months | 0.00 | 0.00 | -10.2 | |
Maximum of Months | 99526844.46 | 311.33 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.781279E+09 | 2222.74 | 07-JAN-19:01 | -5.6 |
February | 0.440010E+09 | 2210.36 | 03-FEB-09:01 | -6.8 |
March | 49266199.40 | 2043.22 | 23-MAR-08:62 | 6.97 |
April | 12196549.59 | 2052.74 | 06-APR-08:62 | 5.37 |
May | 1282995.85 | 848.19 | 19-MAY-08:05 | 21.23 |
June | 593205.71 | 741.72 | 04-JUN-08:05 | 22.57 |
July | 204573.12 | 451.01 | 03-JUL-08:05 | 24.60 |
August | 258999.38 | 782.59 | 25-AUG-08:05 | 22.15 |
September | 1601686.23 | 741.35 | 21-SEP-18:05 | 19.90 |
October | 32961708.15 | 2073.33 | 26-OCT-08:61 | 5.05 |
November | 0.128251E+09 | 2132.06 | 22-NOV-09:01 | 1.05 |
December | 0.448202E+09 | 2159.68 | 18-DEC-09:01 | -1.7 |
Annual Sum or Average | 0.189611E+10 | |||
Minimum of Months | 204573.12 | 451.01 | -6.8 | |
Maximum of Months | 0.781279E+09 | 2222.74 | 24.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103773E+10 | 2223.71 | 07-JAN-19:01 | -5.6 |
February | 0.591984E+09 | 2230.88 | 03-FEB-09:01 | -6.8 |
March | 71923091.48 | 2053.91 | 19-MAR-08:62 | 4.27 |
April | 16111607.05 | 2058.76 | 06-APR-08:62 | 5.37 |
May | 585353.66 | 479.35 | 12-MAY-08:05 | 15.28 |
June | 67466.53 | 260.73 | 09-JUN-08:54 | 22.80 |
July | 94900.30 | 220.77 | 07-JUL-06:56 | 25.00 |
August | 41398.64 | 216.11 | 10-AUG-08:05 | 27.48 |
September | 716859.39 | 813.59 | 20-SEP-08:53 | 20.00 |
October | 43887009.20 | 2098.90 | 26-OCT-08:61 | 5.05 |
November | 0.218894E+09 | 2169.10 | 21-NOV-09:01 | -0.1 |
December | 0.658812E+09 | 2189.64 | 18-DEC-09:01 | -1.7 |
Annual Sum or Average | 0.264085E+10 | |||
Minimum of Months | 41398.64 | 216.11 | -6.8 | |
Maximum of Months | 0.103773E+10 | 2230.88 | 27.48 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120868E+09 | 662.90 | 07-JAN-16:01 | -4.1 |
February | 65996166.94 | 653.93 | 03-FEB-09:01 | -6.8 |
March | 1070115.75 | 502.84 | 19-MAR-15:03 | 16.20 |
April | 258925.87 | 316.22 | 06-APR-08:03 | 5.37 |
May | 43748.39 | 124.15 | 15-MAY-08:55 | 20.60 |
June | 7925.05 | 63.99 | 05-JUN-21:56 | 22.20 |
July | 2931.93 | 34.21 | 28-JUL-15:07 | 19.40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 64437.75 | 198.76 | 30-SEP-15:07 | 17.88 |
October | 532438.24 | 254.05 | 27-OCT-08:05 | 10.47 |
November | 7035720.79 | 628.16 | 22-NOV-09:01 | 1.05 |
December | 36085271.35 | 638.02 | 18-DEC-09:01 | -1.7 |
Annual Sum or Average | 0.231966E+09 | |||
Minimum of Months | 0.00 | 0.00 | -6.8 | |
Maximum of Months | 0.120868E+09 | 662.90 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.785524E+09 | 2169.73 | 07-JAN-19:01 | -5.6 |
February | 0.430151E+09 | 2152.66 | 11-FEB-19:01 | -6.2 |
March | 55588641.13 | 1994.68 | 23-MAR-08:62 | 6.97 |
April | 12601527.40 | 588.99 | 06-APR-15:05 | 15.60 |
May | 219745.34 | 517.24 | 26-MAY-08:05 | 20.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 97257.35 | 399.91 | 28-JUL-08:06 | 19.40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 437745.79 | 681.42 | 30-SEP-15:05 | 17.88 |
October | 33698918.00 | 1981.61 | 31-OCT-08:62 | 7.80 |
November | 0.127230E+09 | 2033.42 | 30-NOV-16:01 | 7.20 |
December | 0.439671E+09 | 2064.72 | 21-DEC-09:01 | 2.30 |
Annual Sum or Average | 0.188522E+10 | |||
Minimum of Months | 0.00 | 0.00 | -6.2 | |
Maximum of Months | 0.785524E+09 | 2169.73 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105082E+10 | 2171.55 | 07-JAN-19:01 | -5.6 |
February | 0.578183E+09 | 2157.04 | 11-FEB-19:01 | -6.2 |
March | 78519035.03 | 1996.16 | 23-MAR-08:62 | 6.97 |
April | 16239658.60 | 626.21 | 26-APR-15:06 | 15.68 |
May | 183839.65 | 405.93 | 12-MAY-21:55 | 17.80 |
June | 35662.55 | 186.28 | 18-JUN-21:56 | 22.80 |
July | 40207.97 | 250.11 | 29-JUL-08:56 | 17.80 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 411816.11 | 735.72 | 30-SEP-15:05 | 17.88 |
October | 45590858.62 | 1981.90 | 31-OCT-08:62 | 7.80 |
November | 0.212038E+09 | 2039.57 | 22-NOV-09:01 | 1.05 |
December | 0.645349E+09 | 2099.88 | 17-DEC-19:01 | -0.2 |
Annual Sum or Average | 0.262741E+10 | |||
Minimum of Months | 0.00 | 0.00 | -6.2 | |
Maximum of Months | 0.105082E+10 | 2171.55 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122018E+09 | 845.25 | 09-JAN-09:03 | -3.2 |
February | 38733003.30 | 566.81 | 12-FEB-08:03 | -11.9 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.70 |
December | 1706557.29 | 137.67 | 18-DEC-07:40 | -5.4 |
Annual Sum or Average | 0.162458E+09 | |||
Minimum of Months | 0.00 | 0.00 | -11.9 | |
Maximum of Months | 0.122018E+09 | 845.25 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125188E+10 | 2678.14 | 07-JAN-19:01 | -5.6 |
February | 0.737153E+09 | 2665.39 | 03-FEB-09:01 | -6.8 |
March | 0.141652E+09 | 2486.89 | 19-MAR-08:62 | 4.27 |
April | 40839751.85 | 2499.73 | 06-APR-08:62 | 5.37 |
May | 1419749.56 | 746.82 | 20-MAY-08:05 | 21.15 |
June | 897341.07 | 725.85 | 04-JUN-08:05 | 22.57 |
July | 495041.13 | 705.07 | 03-JUL-08:05 | 24.60 |
August | 590309.13 | 667.69 | 26-AUG-08:05 | 23.07 |
September | 2330885.38 | 692.22 | 21-SEP-18:05 | 19.90 |
October | 95545055.03 | 2527.78 | 26-OCT-08:61 | 5.05 |
November | 0.290751E+09 | 2589.03 | 21-NOV-09:01 | -0.1 |
December | 0.794993E+09 | 2611.53 | 18-DEC-09:01 | -1.7 |
Annual Sum or Average | 0.335855E+10 | |||
Minimum of Months | 495041.13 | 667.69 | -6.8 | |
Maximum of Months | 0.125188E+10 | 2678.14 | 24.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158180E+10 | 2678.05 | 07-JAN-19:01 | -5.6 |
February | 0.939458E+09 | 2688.49 | 03-FEB-09:01 | -6.8 |
March | 0.187863E+09 | 2508.38 | 19-MAR-08:62 | 4.27 |
April | 46267188.04 | 2505.79 | 06-APR-08:62 | 5.37 |
May | 935022.40 | 790.96 | 13-MAY-08:53 | 20.00 |
June | 334399.20 | 879.95 | 07-JUN-08:53 | 18.90 |
July | 82121.20 | 391.95 | 02-JUL-21:55 | 22.80 |
August | 125638.94 | 577.24 | 10-AUG-08:05 | 27.48 |
September | 992377.61 | 633.71 | 21-SEP-08:53 | 20.60 |
October | 0.125293E+09 | 2554.24 | 26-OCT-08:61 | 5.05 |
November | 0.445013E+09 | 2608.07 | 21-NOV-09:01 | -0.1 |
December | 0.107429E+10 | 2637.32 | 18-DEC-09:01 | -1.7 |
Annual Sum or Average | 0.440246E+10 | |||
Minimum of Months | 82121.20 | 391.95 | -6.8 | |
Maximum of Months | 0.158180E+10 | 2688.49 | 27.48 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.313498E+09 | 1388.13 | 07-JAN-19:01 | -5.6 |
February | 0.167799E+09 | 1358.80 | 12-FEB-09:02 | -10.2 |
March | 21662517.09 | 1275.04 | 23-MAR-08:62 | 6.97 |
April | 9287242.36 | 1284.98 | 06-APR-08:62 | 5.37 |
May | 409765.07 | 450.59 | 10-MAY-08:03 | 11.57 |
June | 80011.56 | 279.95 | 08-JUN-08:03 | 17.57 |
July | 59984.53 | 145.79 | 28-JUL-08:06 | 19.40 |
August | 51976.60 | 133.72 | 14-AUG-08:06 | 24.68 |
September | 483973.49 | 473.97 | 30-SEP-15:05 | 17.88 |
October | 12791947.10 | 1263.07 | 31-OCT-08:62 | 7.80 |
November | 36520648.51 | 1295.19 | 30-NOV-16:01 | 7.20 |
December | 0.145309E+09 | 1318.83 | 01-DEC-09:01 | -0.2 |
Annual Sum or Average | 0.707954E+09 | |||
Minimum of Months | 51976.60 | 133.72 | -10.2 | |
Maximum of Months | 0.313498E+09 | 1388.13 | 24.68 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.546819E+09 | 2217.25 | 08-JAN-05:30 | -5.3 |
February | 0.277013E+09 | 2692.66 | 12-FEB-06:00 | -12.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 10158013.37 | 815.88 | 22-NOV-07:05 | -3.2 |
December | 61923457.36 | 1338.18 | 18-DEC-07:40 | -5.4 |
Annual Sum or Average | 0.895913E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.546819E+09 | 2692.66 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.962539E+10 | 9271.23 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.869085E+10 | 9271.23 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.965507E+10 | 9271.23 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.929905E+10 | 9271.23 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.964208E+10 | 9271.23 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.934170E+10 | 9271.23 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.959943E+10 | 9271.23 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.965878E+10 | 9271.23 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.930276E+10 | 9271.23 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.962169E+10 | 9271.23 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.933428E+10 | 9271.23 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.959943E+10 | 9271.23 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.113371E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.869085E+10 | 9271.23 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.965878E+10 | 9271.23 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.531884E+09 | 512.31 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.480243E+09 | 512.31 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.533523E+09 | 512.31 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.513850E+09 | 512.31 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.532806E+09 | 512.31 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.516207E+09 | 512.31 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.530449E+09 | 512.31 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.533728E+09 | 512.31 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.514055E+09 | 512.31 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.531679E+09 | 512.31 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.515797E+09 | 512.31 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.530449E+09 | 512.31 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.626467E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.480243E+09 | 512.31 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.533728E+09 | 512.31 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.615923E+09 | 593.26 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.556123E+09 | 593.26 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.617822E+09 | 593.26 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.595041E+09 | 593.26 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.616991E+09 | 593.26 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.597770E+09 | 593.26 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.614262E+09 | 593.26 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.618059E+09 | 593.26 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.595278E+09 | 593.26 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.615686E+09 | 593.26 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.597295E+09 | 593.26 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.614262E+09 | 593.26 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.725451E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.556123E+09 | 593.26 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.618059E+09 | 593.26 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.158446E+09 | 152.61 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.143062E+09 | 152.61 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.158934E+09 | 152.61 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.153074E+09 | 152.61 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.158720E+09 | 152.61 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.153776E+09 | 152.61 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.158018E+09 | 152.61 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.158995E+09 | 152.61 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.153135E+09 | 152.61 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.158385E+09 | 152.61 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.153654E+09 | 152.61 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.158018E+09 | 152.61 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.186622E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.143062E+09 | 152.61 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.158995E+09 | 152.61 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.415991E+09 | 400.68 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.375602E+09 | 400.68 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.417273E+09 | 400.68 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.401887E+09 | 400.68 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.416712E+09 | 400.68 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.403730E+09 | 400.68 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.414869E+09 | 400.68 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.417433E+09 | 400.68 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.402047E+09 | 400.68 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.415830E+09 | 400.68 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.403409E+09 | 400.68 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.414869E+09 | 400.68 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.489965E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.375602E+09 | 400.68 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.417433E+09 | 400.68 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123299E+10 | 1573.46 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.110504E+10 | 1573.46 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.112566E+10 | 1573.46 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.100652E+10 | 1573.46 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.973309E+09 | 1573.46 | 01-MAY-19:19 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.909057E+09 | 1573.46 | 01-JUN-19:40 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.954334E+09 | 1573.46 | 03-JUL-19:49 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.100656E+10 | 1573.46 | 01-AUG-19:40 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.106983E+10 | 1573.46 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.118831E+10 | 1573.46 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.117666E+10 | 1573.46 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.122996E+10 | 1573.46 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.129782E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.909057E+09 | 1573.46 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.123299E+10 | 1573.46 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105828E+11 | 10645.38 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.955319E+10 | 10645.38 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.105031E+11 | 10645.38 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.100418E+11 | 10645.38 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.103333E+11 | 10645.38 | 01-MAY-19:19 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.997461E+10 | 10645.38 | 01-JUN-19:40 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.102711E+11 | 10645.38 | 03-JUL-19:49 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.103770E+11 | 10645.38 | 01-AUG-19:40 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.101073E+11 | 10645.38 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.105441E+11 | 10645.38 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.102397E+11 | 10645.38 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.105550E+11 | 10645.38 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.123083E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.955319E+10 | 10645.38 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.105828E+11 | 10645.38 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82476868.03 | 74.62 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 74484663.28 | 74.62 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 81821381.83 | 74.62 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 79911301.67 | 74.62 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 82149124.93 | 74.62 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 79277307.08 | 74.62 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 82793865.32 | 74.62 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 81821381.83 | 74.62 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 79932793.28 | 74.62 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 82466122.22 | 74.62 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 79594304.38 | 74.62 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 82804611.13 | 74.62 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.969534E+09 | 0.300992E+10 | ||||
Minimum of Months | 74484663.28 | 74.62 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 82804611.13 | 74.62 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82499421.18 | 74.64 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 74505030.97 | 74.64 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 81843755.73 | 74.64 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 79933153.27 | 74.64 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 82171588.45 | 74.64 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 79298985.31 | 74.64 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 82816505.16 | 74.64 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 81843755.73 | 74.64 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 79954650.76 | 74.64 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 82488672.43 | 74.64 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 79616069.29 | 74.64 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 82827253.90 | 74.64 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.969799E+09 | 0.301074E+10 | ||||
Minimum of Months | 74505030.97 | 74.64 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 82827253.90 | 74.64 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.120431E+10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.108739E+10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.120803E+10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.116348E+10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.120640E+10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.116882E+10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.120107E+10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.120849E+10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.116395E+10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.120385E+10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.116789E+10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.120107E+10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.141847E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.108739E+10 | 1160.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120849E+10 | 1160.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82499421.18 | 74.64 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 74505030.97 | 74.64 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 81843755.73 | 74.64 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 79933153.27 | 74.64 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 82171588.45 | 74.64 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 79298985.31 | 74.64 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 82816505.16 | 74.64 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 81843755.73 | 74.64 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 79954650.76 | 74.64 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 82488672.43 | 74.64 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 79616069.29 | 74.64 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 82827253.90 | 74.64 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.969799E+09 | 0.301074E+10 | ||||
Minimum of Months | 74505030.97 | 74.64 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 82827253.90 | 74.64 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.258523E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.232321E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.246098E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.227590E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.225924E+10 | 2763.12 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.214624E+10 | 2763.12 | 01-JUN-19:40 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.223394E+10 | 2763.12 | 03-JUL-19:49 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.230655E+10 | 2763.12 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.234223E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.254433E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.248051E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.257826E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.285366E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.214624E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.258523E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.258523E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.232321E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.246098E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.227590E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.225924E+10 | 2763.12 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.214624E+10 | 2763.12 | 01-JUN-19:40 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.223394E+10 | 2763.12 | 03-JUL-19:49 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.230655E+10 | 2763.12 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.234223E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.254433E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.248051E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.257826E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.285366E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.214624E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.258523E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113250E+10 | 1090.83 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.102255E+10 | 1090.83 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.113599E+10 | 1090.83 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.109410E+10 | 1090.83 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.113446E+10 | 1090.83 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.109912E+10 | 1090.83 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.112945E+10 | 1090.83 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.113643E+10 | 1090.83 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.109454E+10 | 1090.83 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.113207E+10 | 1090.83 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.109825E+10 | 1090.83 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.112945E+10 | 1090.83 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.133389E+11 | 0.424019E+12 | ||||
Minimum of Months | 0.102255E+10 | 1090.83 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.113643E+10 | 1090.83 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.127458E+10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.115083E+10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.127851E+10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.123137E+10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.127679E+10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.123701E+10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.127114E+10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.127900E+10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.123186E+10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.127409E+10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.123603E+10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.127114E+10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.150123E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.115083E+10 | 1227.68 | 0.00 | 0.00 | |
Maximum of Months | 0.127900E+10 | 1227.68 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.962539E+10 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.869085E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.965507E+10 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.929905E+10 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.964208E+10 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.934170E+10 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.959943E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.965878E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.930276E+10 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.962169E+10 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.933428E+10 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.959943E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.113371E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.869085E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.965878E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.531884E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142625E+09 |
February | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52730.82 | 0.100022E+09 |
March | 0.199990E+10 | 0.533523E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 681333.76 | 65484272.32 |
April | 0.192973E+10 | 0.513850E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3058234.42 | 40957706.51 |
May | 0.199475E+10 | 0.532806E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7934918.41 | 21314791.40 |
June | 0.193394E+10 | 0.516207E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19448099.79 | 8089386.09 |
July | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24194804.42 | 4282622.31 |
August | 0.199896E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23355495.84 | 1474481.09 |
September | 0.192879E+10 | 0.514055E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8581873.34 | 12276958.27 |
October | 0.199148E+10 | 0.531679E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1503078.14 | 51303775.93 |
November | 0.192552E+10 | 0.515797E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 111045.74 | 76075387.94 |
December | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111585E+09 |
Annual Sum or Average | 0.234744E+11 | 0.626467E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88921614.69 | 0.635491E+09 |
Minimum of Months | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1474481.09 |
Maximum of Months | 0.199990E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24194804.42 | 0.142625E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.615923E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56311606.98 |
February | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73661.18 | 40121370.17 |
March | 0.231589E+10 | 0.617822E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 336210.90 | 27675077.35 |
April | 0.223463E+10 | 0.595041E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1420309.44 | 18457867.04 |
May | 0.230993E+10 | 0.616991E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3191866.26 | 10472844.68 |
June | 0.223950E+10 | 0.597770E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7638416.51 | 4318175.45 |
July | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9531319.41 | 2581813.83 |
August | 0.231480E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9205031.91 | 1091545.61 |
September | 0.223354E+10 | 0.595278E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3580010.46 | 6397370.98 |
October | 0.230614E+10 | 0.615686E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 747982.19 | 22018580.92 |
November | 0.222975E+10 | 0.597295E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53802.52 | 31787399.86 |
December | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2008.17 | 44922509.63 |
Annual Sum or Average | 0.271834E+11 | 0.725451E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35780618.95 | 0.266156E+09 |
Minimum of Months | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1091545.61 |
Maximum of Months | 0.231589E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9531319.41 | 56311606.98 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.68 | 0.128721E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 329809.97 | 90333393.54 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1148945.86 | 59183968.12 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4100089.89 | 39825772.10 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7914357.92 | 22579307.75 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17693278.34 | 9605677.31 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21884186.10 | 5907380.06 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21296844.03 | 2349309.87 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8698214.11 | 13944146.47 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2149893.50 | 47816443.34 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 219387.03 | 69217474.76 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31072.20 | 0.100034E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85466168.63 | 0.589518E+09 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89.68 | 2349309.87 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21884186.10 | 0.128721E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.158446E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.54 | 74149282.31 |
February | 0.339028E+09 | 0.143062E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 188053.50 | 51826708.35 |
March | 0.376747E+09 | 0.158934E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 682149.11 | 33590862.74 |
April | 0.363528E+09 | 0.153074E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2391514.24 | 22402557.79 |
May | 0.375778E+09 | 0.158720E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4647751.51 | 12534825.97 |
June | 0.364321E+09 | 0.153776E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10380779.39 | 5242503.74 |
July | 0.374985E+09 | 0.158018E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12750226.09 | 3184953.34 |
August | 0.376571E+09 | 0.158995E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12466787.79 | 1213532.43 |
September | 0.363352E+09 | 0.153135E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5172758.54 | 7614623.84 |
October | 0.375161E+09 | 0.158385E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1261280.13 | 26940686.30 |
November | 0.362735E+09 | 0.153654E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 127503.92 | 39351572.97 |
December | 0.374985E+09 | 0.158018E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17133.32 | 57402692.09 |
Annual Sum or Average | 0.442217E+10 | 0.186622E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50085980.09 | 0.335455E+09 |
Minimum of Months | 0.339028E+09 | 0.143062E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.54 | 1213532.43 |
Maximum of Months | 0.376747E+09 | 0.158995E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12750226.09 | 74149282.31 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.415991E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192305E+09 |
February | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 285486.52 | 0.136563E+09 |
March | 0.155131E+10 | 0.417273E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 1101764.74 | 90902139.38 |
April | 0.149688E+10 | 0.401887E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 4919366.32 | 58852971.46 |
May | 0.154732E+10 | 0.416712E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 11328641.68 | 31117210.50 |
June | 0.150015E+10 | 0.403730E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 27722532.67 | 10521045.50 |
July | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 35583166.31 | 5881176.48 |
August | 0.155059E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 36291481.65 | 1921000.04 |
September | 0.149615E+10 | 0.402047E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 14079416.22 | 17618637.54 |
October | 0.154478E+10 | 0.415830E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 3048452.56 | 70307607.99 |
November | 0.149361E+10 | 0.403409E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 221278.29 | 0.105188E+09 |
December | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 6040.71 | 0.152248E+09 |
Annual Sum or Average | 0.182090E+11 | 0.489965E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.134588E+09 | 0.873425E+09 |
Minimum of Months | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1921000.04 |
Maximum of Months | 0.155131E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 36291481.65 | 0.192305E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.123299E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330811E+09 |
February | 0.236489E+11 | 0.110504E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103252.77 | 0.236510E+09 |
March | 0.262800E+11 | 0.112566E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1235735.79 | 0.163587E+09 |
April | 0.253579E+11 | 0.100652E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6370812.36 | 0.106269E+09 |
May | 0.262123E+11 | 0.973309E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17343313.06 | 59742284.12 |
June | 0.254132E+11 | 0.909057E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44298154.40 | 24049627.55 |
July | 0.261570E+11 | 0.954334E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54929719.15 | 14188804.02 |
August | 0.262677E+11 | 0.100656E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52386093.15 | 5687002.25 |
September | 0.253456E+11 | 0.106983E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19016970.44 | 35973395.67 |
October | 0.261693E+11 | 0.118831E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3146740.65 | 0.129622E+09 |
November | 0.253025E+11 | 0.117666E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 134765.46 | 0.188352E+09 |
December | 0.261570E+11 | 0.122996E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264932E+09 |
Annual Sum or Average | 0.308468E+12 | 0.129782E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198966E+09 | 0.155972E+10 |
Minimum of Months | 0.236489E+11 | 0.909057E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5687002.25 |
Maximum of Months | 0.262800E+11 | 0.123299E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54929719.15 | 0.330811E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.105828E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.955762E+09 |
February | 0.702046E+11 | 0.955319E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 834733.48 | 0.684827E+09 |
March | 0.780153E+11 | 0.105031E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4502549.36 | 0.475112E+09 |
April | 0.752779E+11 | 0.100418E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21223526.95 | 0.315834E+09 |
May | 0.778146E+11 | 0.103333E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50320346.62 | 0.179915E+09 |
June | 0.754422E+11 | 0.997461E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125113E+09 | 72637073.62 |
July | 0.776503E+11 | 0.102711E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156655E+09 | 44000653.59 |
August | 0.779788E+11 | 0.103770E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151220E+09 | 17887052.83 |
September | 0.752414E+11 | 0.101073E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56678463.10 | 0.109874E+09 |
October | 0.776868E+11 | 0.105441E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10627468.32 | 0.378441E+09 |
November | 0.751137E+11 | 0.102397E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 545081.10 | 0.547837E+09 |
December | 0.776503E+11 | 0.105550E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 444.11 | 0.769392E+09 |
Annual Sum or Average | 0.915726E+12 | 0.123083E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577720E+09 | 0.455152E+10 |
Minimum of Months | 0.702046E+11 | 0.955319E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17887052.83 |
Maximum of Months | 0.780153E+11 | 0.105828E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156655E+09 | 0.955762E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81586500.72 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 113579.72 | 56945310.24 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 722185.67 | 36749077.72 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2455912.49 | 22432607.70 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5833090.47 | 10151769.97 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15216512.61 | 2647579.77 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19626134.07 | 1082517.70 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20818527.01 | 149562.38 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8184117.39 | 5067950.98 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1534168.23 | 27230308.39 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 99135.74 | 42940936.26 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4557.13 | 63606662.94 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74607920.52 | 0.350591E+09 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149562.38 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20818527.01 | 81586500.72 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80372025.72 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90551.02 | 56342064.96 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 599205.58 | 37037752.35 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2242004.52 | 23835914.10 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5455001.56 | 12102804.57 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14558124.76 | 3661478.88 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18904102.79 | 2028809.33 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20007236.70 | 573403.93 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7570602.25 | 6244369.44 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1311870.46 | 27883983.51 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66345.28 | 42328372.50 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4594.77 | 62333210.48 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70809639.70 | 0.354744E+09 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573403.93 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20007236.70 | 80372025.72 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 82476868.03 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25363321.63 |
February | 0.00 | 74484663.28 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20035681.44 |
March | 0.00 | 81821381.83 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5292.19 | 16374295.59 |
April | 0.00 | 79911301.67 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47763.28 | 11698608.28 |
May | 0.00 | 82149124.93 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 267085.27 | 7661340.90 |
June | 0.00 | 79277307.08 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1385850.09 | 3748125.44 |
July | 0.00 | 82793865.32 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1964806.43 | 2842720.02 |
August | 0.00 | 81821381.83 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1770566.19 | 2025362.28 |
September | 0.00 | 79932793.28 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 388893.06 | 5458335.55 |
October | 0.00 | 82466122.22 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29067.32 | 13525119.87 |
November | 0.00 | 79594304.38 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18209041.96 |
December | 0.00 | 82804611.13 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23439965.01 |
Annual Sum or Average | 0.00 | 0.969534E+09 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5859323.84 | 0.150382E+09 |
Minimum of Months | 0.00 | 74484663.28 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2025362.28 |
Maximum of Months | 0.00 | 82804611.13 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1964806.43 | 25363321.63 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 82499421.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22827737.03 |
February | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35311.04 | 15973869.33 |
March | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 183908.73 | 10251439.49 |
April | 0.293479E+09 | 79933153.27 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 671824.08 | 6513915.25 |
May | 0.303504E+09 | 82171588.45 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1561436.48 | 3220121.98 |
June | 0.293842E+09 | 79298985.31 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4101226.68 | 927546.56 |
July | 0.303141E+09 | 82816505.16 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5315579.42 | 499539.47 |
August | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5641871.77 | 113004.55 |
September | 0.293479E+09 | 79954650.76 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2163876.92 | 1678712.90 |
October | 0.303322E+09 | 82488672.43 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 403968.34 | 7725687.27 |
November | 0.293661E+09 | 79616069.29 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22771.96 | 11930807.55 |
December | 0.303141E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3012.08 | 17747710.27 |
Annual Sum or Average | 0.357224E+10 | 0.969799E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20104787.50 | 99410091.65 |
Minimum of Months | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113004.55 |
Maximum of Months | 0.303685E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5641871.77 | 22827737.03 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81763206.41 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 114035.30 | 57176664.15 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 728169.59 | 37041432.26 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2457081.56 | 22689464.79 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5811541.73 | 10274018.15 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15189588.74 | 2699296.71 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19594080.91 | 1100770.81 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20790002.52 | 156976.62 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8174511.24 | 5120599.02 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1533992.23 | 27394123.43 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 100176.86 | 43141737.81 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4530.32 | 63787827.72 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74497710.99 | 0.352346E+09 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156976.62 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20790002.52 | 81763206.41 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80481610.96 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84261.21 | 56472974.76 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 620228.30 | 37038409.92 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2226155.29 | 23864457.62 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5412982.99 | 12259752.25 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14453851.75 | 3958586.04 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18788225.26 | 2331319.06 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19936387.64 | 735116.68 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7522095.91 | 6415614.00 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1316731.97 | 27870515.20 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90719.67 | 42248536.93 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9335.65 | 62415001.90 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70460975.62 | 0.356092E+09 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 735116.68 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19936387.64 | 80481610.96 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.120431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99102867.16 |
February | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192769.06 | 69442154.94 |
March | 0.387034E+10 | 0.120803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 806882.91 | 46090492.94 |
April | 0.373454E+10 | 0.116348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2735974.24 | 31027609.60 |
May | 0.386038E+10 | 0.120640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5798602.78 | 17293999.71 |
June | 0.374269E+10 | 0.116882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13572238.89 | 7140747.35 |
July | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16670428.29 | 4452364.49 |
August | 0.386853E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16280962.16 | 1732164.52 |
September | 0.373273E+10 | 0.116395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6489621.84 | 10535960.36 |
October | 0.385404E+10 | 0.120385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1499826.93 | 36568322.06 |
November | 0.372639E+10 | 0.116789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183841.49 | 52432819.48 |
December | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20984.58 | 76731660.72 |
Annual Sum or Average | 0.454292E+11 | 0.141847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64252133.15 | 0.452551E+09 |
Minimum of Months | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1732164.52 |
Maximum of Months | 0.387034E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16670428.29 | 99102867.16 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81261525.05 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 108675.38 | 56717682.67 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 703399.66 | 36693953.22 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2396482.49 | 22484460.55 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5724045.75 | 10253900.93 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15032546.62 | 2696958.03 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19407552.37 | 1106293.36 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20571355.82 | 152558.43 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8033068.36 | 5093330.35 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1494436.00 | 27197748.76 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92581.42 | 42841883.03 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4158.67 | 63280546.76 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73568302.56 | 0.349781E+09 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152558.43 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20571355.82 | 81261525.05 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80230699.97 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90589.22 | 56224804.85 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 582863.92 | 36893221.35 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2184414.49 | 23933990.00 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5360187.53 | 12190630.73 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14402398.13 | 3626766.88 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18722088.68 | 1946987.91 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19807784.82 | 508550.92 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7450301.80 | 6130215.02 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1281850.59 | 27703180.57 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68125.98 | 42085354.85 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5708.09 | 62005835.73 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69956313.25 | 0.353480E+09 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508550.92 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19807784.82 | 80230699.97 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 82499421.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42711462.25 |
February | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52630.97 | 29825598.45 |
March | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 357753.68 | 19104339.00 |
April | 0.293479E+09 | 79933153.27 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1223196.93 | 11607677.80 |
May | 0.303504E+09 | 82171588.45 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2932977.10 | 5251716.34 |
June | 0.293842E+09 | 79298985.31 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7700681.13 | 1379918.28 |
July | 0.303141E+09 | 82816505.16 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9936634.24 | 566846.32 |
August | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10523154.12 | 78881.04 |
September | 0.293479E+09 | 79954650.76 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4099192.24 | 2635428.57 |
October | 0.303322E+09 | 82488672.43 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 752612.01 | 14178213.55 |
November | 0.293661E+09 | 79616069.29 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45720.54 | 22490361.01 |
December | 0.303141E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2067.25 | 33354793.68 |
Annual Sum or Average | 0.357224E+10 | 0.969799E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37626620.20 | 0.183185E+09 |
Minimum of Months | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78881.04 |
Maximum of Months | 0.303685E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10523154.12 | 42711462.25 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.258523E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225356E+09 |
February | 0.415303E+11 | 0.232321E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 115347.85 | 0.162346E+09 |
March | 0.461508E+11 | 0.246098E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 613755.98 | 0.112926E+09 |
April | 0.445315E+11 | 0.227590E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3178034.82 | 75624115.86 |
May | 0.460320E+11 | 0.225924E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8403637.93 | 43373030.42 |
June | 0.446286E+11 | 0.214624E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24456404.77 | 17330147.95 |
July | 0.459349E+11 | 0.223394E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31756475.19 | 10853968.45 |
August | 0.461292E+11 | 0.230655E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30864265.02 | 4562353.10 |
September | 0.445099E+11 | 0.234223E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10731394.88 | 26503494.61 |
October | 0.459565E+11 | 0.254433E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1814978.91 | 88983837.73 |
November | 0.444343E+11 | 0.248051E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45022.15 | 0.128264E+09 |
December | 0.459349E+11 | 0.257826E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181175E+09 |
Annual Sum or Average | 0.541708E+12 | 0.285366E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111979E+09 | 0.107730E+10 |
Minimum of Months | 0.415303E+11 | 0.214624E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4562353.10 |
Maximum of Months | 0.461508E+11 | 0.258523E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31756475.19 | 0.225356E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.258523E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228172E+09 |
February | 0.415303E+11 | 0.232321E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80769.22 | 0.164414E+09 |
March | 0.461508E+11 | 0.246098E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 559946.33 | 0.114474E+09 |
April | 0.445315E+11 | 0.227590E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2975184.25 | 76394247.62 |
May | 0.460320E+11 | 0.225924E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8137658.82 | 43708385.95 |
June | 0.446286E+11 | 0.214624E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24217119.26 | 17383369.39 |
July | 0.459349E+11 | 0.223394E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31563031.84 | 10909169.91 |
August | 0.461292E+11 | 0.230655E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30641513.91 | 4587525.55 |
September | 0.445099E+11 | 0.234223E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10432205.02 | 26739398.19 |
October | 0.459565E+11 | 0.254433E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1654176.34 | 90087135.05 |
November | 0.444343E+11 | 0.248051E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22919.28 | 0.130079E+09 |
December | 0.459349E+11 | 0.257826E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183524E+09 |
Annual Sum or Average | 0.541708E+12 | 0.285366E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110285E+09 | 0.109047E+10 |
Minimum of Months | 0.415303E+11 | 0.214624E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4587525.55 |
Maximum of Months | 0.461508E+11 | 0.258523E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31563031.84 | 0.228172E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113250E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206432E+09 |
February | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 34961.46 | 0.148234E+09 |
March | 0.410691E+10 | 0.113599E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 447530.59 | 0.102364E+09 |
April | 0.396281E+10 | 0.109410E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 2284109.37 | 67621145.75 |
May | 0.409635E+10 | 0.113446E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 6982831.98 | 38196197.03 |
June | 0.397146E+10 | 0.109912E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 21431977.65 | 14799893.78 |
July | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 28152323.96 | 9195446.03 |
August | 0.410499E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 27395779.12 | 3731191.17 |
September | 0.396089E+10 | 0.109454E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 9010403.92 | 23188281.95 |
October | 0.408962E+10 | 0.113207E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 1307690.63 | 80290924.90 |
November | 0.395417E+10 | 0.109825E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 3126.38 | 0.116580E+09 |
December | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165318E+09 |
Annual Sum or Average | 0.482060E+11 | 0.133389E+11 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 97050735.08 | 0.975952E+09 |
Minimum of Months | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3731191.17 |
Maximum of Months | 0.410691E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 28152323.96 | 0.206432E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.127458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176013E+09 |
February | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264230.44 | 0.123123E+09 |
March | 0.409620E+10 | 0.127851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1201576.71 | 80335639.22 |
April | 0.395248E+10 | 0.123137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4089815.93 | 53524356.87 |
May | 0.408566E+10 | 0.127679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8868051.36 | 30236489.37 |
June | 0.396110E+10 | 0.123701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22203579.09 | 12563766.55 |
July | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28230499.98 | 7471514.71 |
August | 0.409429E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27392227.41 | 2897102.18 |
September | 0.395056E+10 | 0.123186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10682347.52 | 17466230.76 |
October | 0.407896E+10 | 0.127409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2405516.60 | 62629616.07 |
November | 0.394385E+10 | 0.123603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230806.07 | 92107330.52 |
December | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18848.05 | 0.136229E+09 |
Annual Sum or Average | 0.480803E+11 | 0.150123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105587E+09 | 0.794597E+09 |
Minimum of Months | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2897102.18 |
Maximum of Months | 0.409620E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28230499.98 | 0.176013E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 9271.23 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 9271.23 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 9271.23 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 9271.23 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 9271.23 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 9271.23 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 9271.23 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 9271.23 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 9271.23 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 9271.23 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 9271.23 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 9271.23 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 512.31 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 88.71 | 27-JAN-08:00 |
February | 1169.53 | 01-FEB-00:10 | 512.31 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.52 | 28-FEB-14:40 | 111.31 | 12-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 512.31 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.75 | 30-MAR-15:17 | 61.55 | 19-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 512.31 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.95 | 17-APR-15:55 | 64.97 | 06-APR-05:00 |
May | 1169.53 | 01-MAY-00:10 | 512.31 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.08 | 19-MAY-17:00 | 39.60 | 11-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 512.31 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 | 06-JUN-15:00 | 31.32 | 10-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 512.31 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.54 | 08-JUL-15:00 | 15.17 | 28-JUL-23:00 |
August | 1169.53 | 01-AUG-00:10 | 512.31 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.20 | 02-AUG-16:00 | 12.86 | 25-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 512.31 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.20 | 07-SEP-16:00 | 28.86 | 14-SEP-05:00 |
October | 1169.53 | 01-OCT-23:10 | 512.31 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 | 10-OCT-16:00 | 57.72 | 26-OCT-07:00 |
November | 1169.53 | 01-NOV-00:10 | 512.31 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.24 | 19-NOV-15:40 | 75.86 | 22-NOV-06:40 |
December | 1169.53 | 01-DEC-00:10 | 512.31 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 84.58 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.86 | |||||
Maximum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 34.54 | 111.31 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 593.26 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 34.98 | 27-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 593.26 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.85 | 26-FEB-15:00 | 42.96 | 12-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 593.26 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 | 30-MAR-14:00 | 25.28 | 19-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 593.26 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.62 | 12-APR-14:00 | 26.86 | 06-APR-05:00 |
May | 1354.32 | 01-MAY-00:10 | 593.26 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.26 | 30-MAY-14:00 | 17.77 | 11-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 593.26 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 | 06-JUN-15:00 | 14.14 | 10-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 593.26 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.97 | 08-JUL-16:00 | 7.43 | 28-JUL-23:00 |
August | 1354.32 | 01-AUG-00:10 | 593.26 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.39 | 01-AUG-15:00 | 6.33 | 25-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 593.26 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.76 | 07-SEP-15:00 | 13.04 | 14-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 593.26 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.19 | 10-OCT-16:00 | 24.05 | 26-OCT-05:00 |
November | 1354.32 | 01-NOV-00:10 | 593.26 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.59 | 19-NOV-15:00 | 30.42 | 22-NOV-06:00 |
December | 1354.32 | 01-DEC-00:10 | 593.26 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 12-DEC-14:00 | 33.22 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | |||||
Maximum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 13.97 | 42.96 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 | 31-JAN-15:00 | 80.93 | 27-JAN-08:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.35 | 26-FEB-15:00 | 101.55 | 12-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.89 | 30-MAR-14:00 | 56.19 | 19-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.57 | 12-APR-14:00 | 60.98 | 06-APR-05:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.53 | 19-MAY-16:50 | 40.07 | 11-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.48 | 06-JUN-15:00 | 32.22 | 10-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.23 | 08-JUL-16:00 | 16.77 | 28-JUL-23:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.23 | 01-AUG-16:40 | 14.39 | 25-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.88 | 07-SEP-16:00 | 29.85 | 29-SEP-04:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.01 | 10-OCT-16:00 | 54.17 | 26-OCT-06:50 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.64 | 19-NOV-15:00 | 69.20 | 22-NOV-07:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.39 | 12-DEC-14:00 | 77.16 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 | 14.39 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 32.23 | 101.55 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 152.61 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 | 31-JAN-15:00 | 46.69 | 27-JAN-08:00 |
February | 220.32 | 01-FEB-00:10 | 152.61 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 | 26-FEB-15:00 | 58.59 | 12-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 152.61 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 | 30-MAR-14:00 | 32.40 | 19-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 152.61 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.07 | 12-APR-14:00 | 34.80 | 06-APR-05:00 |
May | 220.32 | 01-MAY-00:10 | 152.61 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.26 | 19-MAY-16:40 | 22.72 | 11-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 152.61 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.86 | 06-JUN-15:00 | 18.34 | 10-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 152.61 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.49 | 08-JUL-16:00 | 9.29 | 28-JUL-23:00 |
August | 220.32 | 01-AUG-00:10 | 152.61 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.78 | 01-AUG-16:50 | 7.97 | 25-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 152.61 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.01 | 07-SEP-16:00 | 17.00 | 29-SEP-04:00 |
October | 220.32 | 01-OCT-23:10 | 152.61 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.87 | 10-OCT-16:00 | 30.74 | 26-OCT-05:40 |
November | 220.32 | 01-NOV-00:10 | 152.61 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.39 | 19-NOV-15:00 | 39.92 | 22-NOV-06:40 |
December | 220.32 | 01-DEC-00:10 | 152.61 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 | 12-DEC-14:00 | 44.51 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 | 7.97 | |||||
Maximum of Months | 220.32 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 18.49 | 58.59 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 400.68 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 122.45 | 27-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 400.68 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 10.20 | 26-FEB-14:50 | 147.82 | 12-FEB-07:10 |
March | 907.20 | 01-MAR-00:10 | 400.68 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 20.60 | 30-MAR-15:50 | 88.19 | 19-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 400.68 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 24.35 | 17-APR-16:25 | 89.37 | 06-APR-05:10 |
May | 907.20 | 01-MAY-00:10 | 400.68 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 31.59 | 19-MAY-17:00 | 60.45 | 11-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 400.68 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 42.11 | 06-JUN-17:00 | 45.07 | 08-JUN-06:00 |
July | 907.20 | 01-JUL-00:10 | 400.68 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 51.51 | 08-JUL-16:00 | 24.26 | 28-JUL-23:00 |
August | 907.20 | 01-AUG-00:10 | 400.68 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 46.58 | 01-AUG-17:00 | 20.45 | 25-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 400.68 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 34.39 | 07-SEP-16:00 | 43.22 | 14-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 400.68 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 28.57 | 10-OCT-16:00 | 83.36 | 26-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 400.68 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 11.17 | 05-NOV-16:00 | 105.59 | 22-NOV-07:10 |
December | 907.20 | 01-DEC-00:10 | 400.68 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 1.23 | 12-DEC-14:00 | 117.22 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 20.45 | ||||||
Maximum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 51.51 | 147.82 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1573.46 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 202.66 | 14-JAN-06:00 |
February | 15368.40 | 01-FEB-00:10 | 1573.46 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.45 | 28-FEB-14:40 | 246.08 | 12-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 1573.46 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.95 | 30-MAR-15:17 | 142.94 | 19-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 1573.46 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.53 | 12-APR-14:00 | 154.98 | 06-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 1573.46 | 01-MAY-19:19 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.50 | 30-MAY-14:00 | 99.66 | 11-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 1573.46 | 01-JUN-19:40 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.45 | 06-JUN-15:00 | 82.82 | 10-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1573.46 | 03-JUL-19:49 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.71 | 08-JUL-16:00 | 43.89 | 28-JUL-23:10 |
August | 15368.40 | 01-AUG-00:10 | 1573.46 | 01-AUG-19:40 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.34 | 01-AUG-17:00 | 35.39 | 25-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 1573.46 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.88 | 07-SEP-16:00 | 76.73 | 29-SEP-04:00 |
October | 15368.40 | 01-OCT-23:10 | 1573.46 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.78 | 10-OCT-16:00 | 140.41 | 26-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1573.46 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.48 | 19-NOV-15:40 | 176.75 | 22-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 1573.46 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 190.29 | 18-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.39 | |||||
Maximum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 78.71 | 246.08 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 10645.38 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 590.50 | 14-JAN-06:00 |
February | 45622.98 | 01-FEB-00:10 | 10645.38 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.53 | 28-FEB-14:20 | 715.88 | 12-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 10645.38 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.49 | 30-MAR-14:00 | 424.52 | 19-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 10645.38 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.12 | 12-APR-14:00 | 455.53 | 06-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 10645.38 | 01-MAY-19:19 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.79 | 30-MAY-14:00 | 298.72 | 11-MAY-06:00 |
June | 45622.98 | 01-JUN-00:10 | 10645.38 | 01-JUN-19:40 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.42 | 06-JUN-15:00 | 241.56 | 10-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 10645.38 | 03-JUL-19:49 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.58 | 08-JUL-16:00 | 125.42 | 28-JUL-23:07 |
August | 45622.98 | 01-AUG-00:10 | 10645.38 | 01-AUG-19:40 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.69 | 01-AUG-15:00 | 103.77 | 25-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 10645.38 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.21 | 07-SEP-15:00 | 226.44 | 29-SEP-04:00 |
October | 45622.98 | 01-OCT-23:10 | 10645.38 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.21 | 10-OCT-16:00 | 410.31 | 26-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 10645.38 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.15 | 19-NOV-15:00 | 517.19 | 22-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 10645.38 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 | 12-DEC-15:00 | 555.19 | 18-DEC-05:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 10645.38 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.77 | |||||
Maximum of Months | 45622.98 | 10645.38 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 231.58 | 715.88 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 51.77 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.20 | 26-FEB-16:10 | 64.90 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.76 | 30-MAR-16:00 | 36.00 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.54 | 17-APR-15:10 | 37.98 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 | 19-MAY-16:00 | 23.25 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.69 | 06-JUN-15:10 | 17.31 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.51 | 08-JUL-15:50 | 8.50 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.06 | 02-AUG-16:00 | 5.02 | 25-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.85 | 07-SEP-16:00 | 16.23 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.23 | 10-OCT-16:00 | 33.77 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.32 | 05-NOV-16:00 | 44.30 | 22-NOV-06:06 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 | 12-DEC-16:09 | 49.37 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.02 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 24.51 | 64.90 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 51.77 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.19 | 26-FEB-16:07 | 64.90 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.76 | 30-MAR-16:00 | 36.00 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.54 | 17-APR-15:10 | 37.98 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 | 19-MAY-16:00 | 23.25 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.69 | 06-JUN-15:10 | 17.31 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.51 | 08-JUL-15:50 | 9.15 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.06 | 02-AUG-16:00 | 7.02 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.85 | 07-SEP-16:00 | 16.23 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.23 | 10-OCT-16:00 | 33.77 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.32 | 05-NOV-16:00 | 44.30 | 22-NOV-06:06 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 | 12-DEC-16:09 | 49.37 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.02 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 24.51 | 64.90 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 74.62 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 16.13 | 27-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 74.62 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 17.42 | 12-FEB-07:10 |
March | 0.00 | 01-MAR-00:10 | 74.62 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 | 30-MAR-14:00 | 12.36 | 19-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 74.62 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 12-APR-14:00 | 12.60 | 06-APR-05:10 |
May | 0.00 | 01-MAY-00:10 | 74.62 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.75 | 19-MAY-14:00 | 9.16 | 11-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 74.62 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.37 | 06-JUN-15:00 | 7.49 | 10-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 74.62 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.40 | 08-JUL-15:00 | 4.50 | 28-JUL-23:40 |
August | 0.00 | 01-AUG-00:10 | 74.62 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 | 02-AUG-16:00 | 3.93 | 25-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 74.62 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.22 | 07-SEP-16:00 | 6.94 | 29-SEP-04:00 |
October | 0.00 | 01-OCT-00:10 | 74.62 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.48 | 10-OCT-16:00 | 11.92 | 26-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 74.62 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 14.26 | 22-NOV-08:00 |
December | 0.00 | 01-DEC-00:10 | 74.62 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 15.83 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 74.62 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.93 | |||||
Maximum of Months | 0.00 | 74.62 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 4.40 | 17.42 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 74.64 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 14.45 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 74.64 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.45 | 26-FEB-16:10 | 18.11 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 74.64 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 30-MAR-16:00 | 10.05 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 74.64 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 17-APR-15:08 | 10.60 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 74.64 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 | 19-MAY-16:00 | 6.49 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 74.64 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.77 | 06-JUN-15:10 | 4.83 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 74.64 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.85 | 08-JUL-15:10 | 2.73 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 74.64 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 | 02-AUG-16:00 | 1.81 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 74.64 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.70 | 07-SEP-16:00 | 4.53 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 74.64 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 | 10-OCT-16:00 | 9.43 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 74.64 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 | 05-NOV-16:00 | 12.36 | 22-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 74.64 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 | 12-DEC-14:00 | 13.78 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.81 | |||||
Maximum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6.85 | 18.11 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 51.77 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.20 | 26-FEB-16:09 | 64.90 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.76 | 30-MAR-16:00 | 36.00 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.54 | 17-APR-15:10 | 37.98 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 | 19-MAY-16:00 | 23.25 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.69 | 06-JUN-15:10 | 17.31 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.52 | 08-JUL-15:50 | 8.46 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.06 | 02-AUG-16:00 | 5.55 | 25-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.86 | 07-SEP-16:00 | 16.23 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.23 | 10-OCT-16:00 | 33.77 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.32 | 05-NOV-16:00 | 44.30 | 22-NOV-06:06 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 | 12-DEC-16:07 | 49.37 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 24.52 | 64.90 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 51.77 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.19 | 26-FEB-16:07 | 64.89 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.76 | 30-MAR-16:00 | 36.00 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.54 | 17-APR-15:08 | 37.98 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 | 19-MAY-16:00 | 23.25 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.69 | 06-JUN-15:10 | 17.31 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.51 | 08-JUL-15:50 | 8.99 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.06 | 02-AUG-16:00 | 6.86 | 27-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.85 | 07-SEP-16:00 | 16.23 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.23 | 10-OCT-16:00 | 33.77 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.32 | 05-NOV-16:00 | 44.30 | 22-NOV-06:06 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.01 | 12-DEC-14:00 | 49.37 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.86 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 24.51 | 64.89 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 62.36 | 27-JAN-08:00 |
February | 2263.36 | 01-FEB-00:10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.20 | 26-FEB-15:00 | 78.22 | 12-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.48 | 30-MAR-14:00 | 43.77 | 19-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.57 | 12-APR-14:00 | 47.21 | 06-APR-05:00 |
May | 2263.36 | 01-MAY-00:10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.61 | 30-MAY-14:00 | 31.05 | 11-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.75 | 06-JUN-15:00 | 25.01 | 10-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.47 | 08-JUL-16:00 | 12.78 | 28-JUL-23:00 |
August | 2263.36 | 01-AUG-00:10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.18 | 01-AUG-17:00 | 10.72 | 25-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.63 | 07-SEP-16:00 | 23.08 | 29-SEP-04:00 |
October | 2263.36 | 01-OCT-23:10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.64 | 10-OCT-16:00 | 41.54 | 26-OCT-05:00 |
November | 2263.36 | 01-NOV-00:10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 19-NOV-15:00 | 53.33 | 22-NOV-06:50 |
December | 2263.36 | 01-DEC-00:10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 | 12-DEC-15:00 | 59.46 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.72 | ||||
Maximum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.47 | 78.22 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 51.89 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.10 | 26-FEB-16:09 | 65.03 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 30-MAR-16:00 | 36.12 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.45 | 17-APR-15:10 | 38.10 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.13 | 19-MAY-16:00 | 23.36 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.60 | 06-JUN-15:10 | 17.42 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.42 | 08-JUL-16:00 | 7.87 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.97 | 02-AUG-16:00 | 4.88 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.76 | 07-SEP-16:00 | 16.34 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.14 | 10-OCT-16:00 | 33.88 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.22 | 05-NOV-16:00 | 44.42 | 22-NOV-06:06 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 12-DEC-16:09 | 49.49 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.88 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 24.42 | 65.03 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 51.89 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.10 | 26-FEB-16:07 | 65.02 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 30-MAR-16:00 | 36.12 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.45 | 17-APR-15:10 | 38.10 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.13 | 19-MAY-16:00 | 23.36 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.60 | 06-JUN-15:10 | 17.41 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.42 | 08-JUL-16:00 | 8.82 | 28-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.96 | 02-AUG-16:00 | 6.53 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.76 | 07-SEP-16:00 | 16.34 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.14 | 10-OCT-16:00 | 33.88 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 | 05-NOV-16:00 | 44.42 | 22-NOV-06:06 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 12-DEC-14:00 | 49.49 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 24.42 | 65.02 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 74.64 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 26.55 | 27-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 74.64 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 | 26-FEB-16:10 | 33.27 | 12-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 74.64 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.46 | 30-MAR-16:00 | 18.48 | 19-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 74.64 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.36 | 17-APR-15:50 | 19.49 | 06-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 74.64 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.74 | 19-MAY-16:00 | 11.95 | 11-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 74.64 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.54 | 06-JUN-15:10 | 8.91 | 10-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 74.64 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.49 | 08-JUL-16:00 | 4.21 | 29-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 74.64 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.24 | 02-AUG-16:00 | 2.50 | 25-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 74.64 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.57 | 07-SEP-16:00 | 8.36 | 29-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 74.64 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.22 | 10-OCT-16:00 | 17.34 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 74.64 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 05-NOV-16:00 | 22.73 | 22-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 74.64 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 | 12-DEC-16:09 | 25.32 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | |||||
Maximum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 12.49 | 33.27 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 137.54 | 14-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.98 | 28-FEB-14:00 | 167.84 | 12-FEB-07:10 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.77 | 30-MAR-14:00 | 100.84 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.38 | 12-APR-14:00 | 105.67 | 06-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.79 | 19-MAY-14:00 | 69.31 | 11-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:40 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.54 | 06-JUN-15:00 | 54.65 | 10-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:49 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.57 | 08-JUL-15:00 | 28.56 | 28-JUL-23:07 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.42 | 02-AUG-16:00 | 23.69 | 25-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 07-SEP-16:00 | 51.98 | 29-SEP-04:00 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.19 | 10-OCT-16:00 | 95.19 | 26-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.57 | 19-NOV-15:00 | 120.16 | 22-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 128.98 | 18-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.69 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 48.57 | 167.84 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 138.39 | 14-JAN-06:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.72 | 28-FEB-14:00 | 168.88 | 12-FEB-07:10 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.03 | 30-MAR-15:17 | 100.84 | 19-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.41 | 12-APR-14:00 | 105.67 | 06-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.60 | 19-MAY-14:00 | 69.31 | 11-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:40 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.54 | 06-JUN-15:00 | 54.65 | 10-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:49 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.57 | 08-JUL-15:00 | 28.56 | 28-JUL-23:07 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.42 | 02-AUG-16:00 | 23.70 | 25-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 07-SEP-16:00 | 51.99 | 29-SEP-04:00 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.19 | 10-OCT-16:00 | 95.21 | 26-OCT-05:10 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.12 | 19-NOV-15:00 | 120.92 | 22-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 129.82 | 18-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.70 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 48.57 | 168.88 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1090.83 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 125.13 | 27-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 1090.83 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 3.31 | 26-FEB-15:00 | 153.73 | 12-FEB-07:10 |
March | 2401.70 | 01-MAR-00:10 | 1090.83 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 12.99 | 30-MAR-14:00 | 90.25 | 19-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1090.83 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 17.19 | 12-APR-14:00 | 92.82 | 06-APR-05:20 |
May | 2401.70 | 01-MAY-00:10 | 1090.83 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 22.95 | 19-MAY-15:50 | 62.03 | 11-MAY-06:00 |
June | 2401.70 | 01-JUN-00:10 | 1090.83 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 35.43 | 06-JUN-15:00 | 48.22 | 10-JUN-05:10 |
July | 2401.70 | 01-JUL-00:10 | 1090.83 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 43.51 | 08-JUL-15:00 | 25.57 | 28-JUL-23:10 |
August | 2401.70 | 01-AUG-00:10 | 1090.83 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 38.02 | 02-AUG-16:00 | 21.20 | 25-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1090.83 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 26.60 | 07-SEP-15:50 | 46.03 | 29-SEP-04:10 |
October | 2401.70 | 01-OCT-23:10 | 1090.83 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 20.80 | 10-OCT-16:00 | 85.28 | 26-OCT-07:00 |
November | 2401.70 | 01-NOV-00:10 | 1090.83 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 1.11 | 05-NOV-16:00 | 108.50 | 22-NOV-07:00 |
December | 2401.70 | 01-DEC-00:10 | 1090.83 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 119.80 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 21.20 | ||||||
Maximum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 43.51 | 153.73 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 110.59 | 27-JAN-08:00 |
February | 2395.44 | 01-FEB-00:10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.39 | 28-FEB-14:00 | 138.68 | 12-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.78 | 30-MAR-14:00 | 76.85 | 19-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.44 | 12-APR-14:00 | 81.09 | 06-APR-05:00 |
May | 2395.44 | 01-MAY-00:10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.26 | 19-MAY-17:00 | 52.33 | 11-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.64 | 06-JUN-15:00 | 42.29 | 10-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.55 | 08-JUL-15:00 | 21.42 | 28-JUL-23:00 |
August | 2395.44 | 01-AUG-00:10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.16 | 02-AUG-16:00 | 18.17 | 25-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.98 | 07-SEP-16:00 | 38.51 | 29-SEP-04:00 |
October | 2395.44 | 01-OCT-23:10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.29 | 10-OCT-16:00 | 72.07 | 26-OCT-07:00 |
November | 2395.44 | 01-NOV-00:10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.46 | 19-NOV-15:00 | 94.61 | 22-NOV-06:40 |
December | 2395.44 | 01-DEC-00:10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.71 | 12-DEC-15:00 | 105.46 | 18-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | ||||
Maximum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.55 | 138.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11579.91 | 31-JAN-21:00 | 8945.92 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11126.63 | 01-FEB-21:00 | 8945.92 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10728.22 | 30-MAR-18:08 | 53675.50 | 49446.67 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12141.68 | 17-APR-18:07 | 53675.50 | 49446.67 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12255.25 | 16-MAY-18:02 | 53675.50 | 49446.67 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12522.41 | 25-JUN-10:33 | 11501.89 | 9271.10 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13397.06 | 20-JUL-18:10 | 53675.50 | 49446.67 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14319.12 | 27-AUG-10:33 | 11501.89 | 9271.10 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17710.78 | 28-SEP-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18757.47 | 13-OCT-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19010.81 | 08-NOV-22:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17097.63 | 01-DEC-22:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 10728.22 | 8945.92 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19010.81 | 53675.50 | 49446.67 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1988.08 | 29-JAN-13:00 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.16 |
February | 2377.87 | 21-FEB-14:25 | 519.79 | 284.62 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.98 |
March | 2361.41 | 30-MAR-15:23 | 1949.22 | 426.93 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 10.73 | 0.00 |
April | 2663.87 | 13-APR-15:30 | 1299.48 | 284.62 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 | 0.00 |
May | 2169.83 | 16-MAY-18:02 | 5457.82 | 2732.34 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 13.91 | 0.00 |
June | 2258.18 | 13-JUN-18:08 | 5457.82 | 2732.34 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 21.86 | 0.00 |
July | 2582.39 | 07-JUL-18:20 | 2728.91 | 1366.17 | 1948.56 | 0.00 | 0.00 | 0.00 | 0.00 | 26.58 | 0.00 |
August | 2901.81 | 19-AUG-13:40 | 389.84 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 26.57 | 0.00 |
September | 2945.08 | 24-SEP-12:40 | 259.90 | 113.85 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 13.14 | 0.00 |
October | 3114.62 | 10-OCT-13:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 13.52 | 0.00 |
November | 2508.85 | 08-NOV-13:40 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.95 |
December | 2319.80 | 10-DEC-13:00 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1988.08 | 259.90 | 113.85 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3114.62 | 5457.82 | 2732.34 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 26.58 | 30.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1246.82 | 31-JAN-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.58 |
February | 1379.44 | 28-FEB-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 |
March | 1672.37 | 30-MAR-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 |
April | 1727.34 | 14-APR-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.44 |
May | 1854.99 | 19-MAY-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 |
June | 1966.91 | 27-JUN-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 0.00 |
July | 2126.61 | 07-JUL-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 7.05 | 0.00 |
August | 2164.96 | 18-AUG-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 7.57 | 0.00 |
September | 2035.60 | 08-SEP-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 | 0.00 |
October | 1814.26 | 11-OCT-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 |
November | 1365.60 | 06-NOV-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.11 |
December | 1334.23 | 12-DEC-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1246.82 | 1053.36 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2164.96 | 1203.84 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 7.57 | 13.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 941.99 | 20-JAN-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.32 |
February | 1048.01 | 28-FEB-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 |
March | 1274.91 | 30-MAR-15:05 | 954.72 | 1140.29 | 1855.62 | 0.00 | 0.00 | 0.00 | 0.00 | 13.69 | 0.00 |
April | 1378.69 | 17-APR-18:07 | 1336.61 | 3648.94 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 9.20 | 0.00 |
May | 1373.75 | 16-MAY-18:02 | 1336.61 | 3648.94 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 | 0.00 |
June | 1611.22 | 28-JUN-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 | 0.00 |
July | 1869.46 | 07-JUL-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 0.00 |
August | 1821.83 | 18-AUG-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 17.90 | 0.00 |
September | 1515.63 | 07-SEP-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 4.10 | 0.00 |
October | 1218.50 | 11-OCT-18:10 | 1336.61 | 3648.94 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.30 |
November | 1076.35 | 05-NOV-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.22 |
December | 1030.26 | 13-DEC-19:10 | 668.30 | 1824.47 | 2385.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 941.99 | 222.77 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1869.46 | 1336.61 | 3648.94 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 17.90 | 24.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 483.07 | 31-JAN-21:00 | 171.36 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 |
February | 545.00 | 28-FEB-19:00 | 122.40 | 101.74 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
March | 688.45 | 30-MAR-15:05 | 734.40 | 254.37 | 535.30 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 | 0.00 |
April | 730.77 | 17-APR-18:07 | 1028.16 | 813.94 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 5.56 | 0.00 |
May | 732.29 | 16-MAY-18:02 | 1028.16 | 813.94 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 8.11 | 0.00 |
June | 757.08 | 25-JUN-10:33 | 220.32 | 152.61 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 9.22 | 0.00 |
July | 824.53 | 07-JUL-21:00 | 195.84 | 135.66 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 9.62 | 0.00 |
August | 805.85 | 18-AUG-21:00 | 195.84 | 135.66 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 0.00 |
September | 739.89 | 09-SEP-10:33 | 220.32 | 127.18 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 9.78 | 0.00 |
October | 644.56 | 11-OCT-10:33 | 146.88 | 127.18 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 3.14 | 0.00 |
November | 572.22 | 05-NOV-10:33 | 220.32 | 152.61 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.73 |
December | 536.55 | 13-DEC-11:33 | 146.88 | 127.18 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 483.07 | 122.40 | 101.74 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 824.53 | 1028.16 | 813.94 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 6.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37171.46 | 31-JAN-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 24.81 |
February | 37719.65 | 28-FEB-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 12.13 |
March | 38143.31 | 30-MAR-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 1.40 | 0.00 |
April | 38371.62 | 14-APR-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 10.35 |
May | 38864.92 | 16-MAY-19:25 | 1411.20 | 801.37 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 5.89 | 0.00 |
June | 38922.18 | 13-JUN-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 18.73 | 0.00 |
July | 39122.13 | 07-JUL-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 24.45 | 0.00 |
August | 39000.93 | 02-AUG-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 22.90 | 0.00 |
September | 38789.67 | 07-SEP-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 11.15 | 0.00 |
October | 38184.77 | 10-OCT-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 6.39 |
November | 37593.72 | 03-NOV-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 18.42 |
December | 37438.28 | 12-DEC-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37171.46 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39122.13 | 1411.20 | 801.37 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 24.45 | 24.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9657.58 | 29-JAN-13:00 | 5122.80 | 115.39 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.66 |
February | 9799.70 | 26-FEB-13:00 | 5122.80 | 115.39 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
March | 10857.25 | 30-MAR-15:23 | 25614.00 | 288.47 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 23.90 | 0.00 |
April | 11192.20 | 15-APR-11:47 | 15368.40 | 288.47 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 17.52 | 0.00 |
May | 10295.60 | 18-MAY-21:05 | 30736.80 | 2097.94 | 1422.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.74 |
June | 11133.02 | 13-JUN-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 25.47 | 0.00 |
July | 11716.35 | 07-JUL-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 39.22 | 0.00 |
August | 12096.51 | 18-AUG-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 41.71 | 0.00 |
September | 11766.67 | 25-SEP-15:03 | 51228.00 | 576.93 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 33.21 | 0.00 |
October | 11906.08 | 10-OCT-15:03 | 51228.00 | 576.93 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 31.24 | 0.00 |
November | 10737.53 | 11-NOV-13:00 | 5122.80 | 115.39 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.38 |
December | 10462.05 | 10-DEC-13:00 | 5122.80 | 115.39 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9657.58 | 5122.80 | 115.39 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12096.51 | 51228.00 | 2097.94 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 41.71 | 66.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27739.32 | 31-JAN-22:20 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.38 |
February | 33082.42 | 28-FEB-22:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.52 |
March | 36553.98 | 30-MAR-21:05 | 182491.92 | 28387.68 | 29559.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.10 |
April | 35940.79 | 17-APR-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.70 |
May | 37525.81 | 19-MAY-21:05 | 182491.92 | 28387.68 | 29559.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.92 |
June | 39889.77 | 13-JUN-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 72.73 | 0.00 |
July | 41834.18 | 07-JUL-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 112.02 | 0.00 |
August | 42629.02 | 18-AUG-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 119.15 | 0.00 |
September | 40947.53 | 07-SEP-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 24.87 | 0.00 |
October | 38153.96 | 10-OCT-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.42 |
November | 32610.65 | 06-NOV-22:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.18 |
December | 32190.78 | 12-DEC-22:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 27739.32 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42629.02 | 182491.92 | 28387.68 | 29559.77 | 0.00 | 0.00 | 0.00 | 0.00 | 119.15 | 242.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2576.92 | 29-JAN-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 |
February | 2820.17 | 27-FEB-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 |
March | 2725.19 | 10-MAR-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.34 |
April | 2770.17 | 09-APR-18:01 | 819.00 | 831.18 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.89 |
May | 2789.28 | 30-MAY-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 7.82 | 0.00 |
June | 2778.47 | 16-JUN-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 8.51 | 0.00 |
July | 2832.18 | 12-JUL-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 14.76 | 0.00 |
August | 2827.12 | 18-AUG-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 17.26 | 0.00 |
September | 2778.83 | 10-SEP-15:02 | 324.00 | 235.11 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 0.00 |
October | 2721.33 | 02-OCT-15:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 6.47 | 0.00 |
November | 2694.19 | 14-NOV-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.93 |
December | 2539.84 | 11-DEC-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2539.84 | 324.00 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2832.18 | 831.60 | 831.18 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 17.26 | 10.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2340.34 | 29-JAN-16:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.64 |
February | 2757.27 | 27-FEB-16:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 | 0.00 |
March | 2720.18 | 11-MAR-16:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 0.00 |
April | 2788.72 | 11-APR-15:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 8.16 | 0.00 |
May | 2777.38 | 09-MAY-20:41 | 1602.00 | 1056.67 | 1843.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.22 |
June | 2826.89 | 05-JUN-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 12.77 | 0.00 |
July | 2830.22 | 21-JUL-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 16.22 | 0.00 |
August | 2788.69 | 18-AUG-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 17.26 | 0.00 |
September | 3062.43 | 18-SEP-16:01 | 972.00 | 332.43 | 1343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 | 0.00 |
October | 2806.89 | 07-OCT-16:21 | 858.60 | 352.62 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
November | 2628.39 | 14-NOV-16:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.73 |
December | 2385.07 | 11-DEC-16:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2340.34 | 378.00 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3062.43 | 1602.00 | 1056.67 | 1843.57 | 0.00 | 0.00 | 0.00 | 0.00 | 17.26 | 17.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 362.69 | 29-JAN-13:30 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.91 |
February | 423.88 | 26-FEB-14:50 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 |
March | 389.39 | 30-MAR-13:40 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 0.00 |
April | 372.41 | 15-APR-14:00 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 | 0.00 |
May | 303.58 | 06-MAY-13:40 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 | 0.00 |
June | 328.76 | 24-JUN-17:20 | 0.00 | 190.29 | 394.73 | 0.00 | 0.00 | 0.00 | 0.00 | 2.63 | 0.00 |
July | 370.19 | 08-JUL-17:30 | 0.00 | 126.86 | 263.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.41 | 0.00 |
August | 431.49 | 19-AUG-13:50 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 3.14 | 0.00 |
September | 496.62 | 24-SEP-12:50 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 | 0.00 |
October | 529.74 | 10-OCT-13:30 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 | 0.00 |
November | 476.21 | 15-NOV-14:00 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.59 |
December | 465.23 | 10-DEC-14:25 | 0.00 | 49.25 | 149.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 303.58 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 529.74 | 0.00 | 190.29 | 394.73 | 0.00 | 0.00 | 0.00 | 0.00 | 3.41 | 5.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 823.19 | 31-JAN-16:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 |
February | 956.50 | 27-FEB-16:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 0.00 |
March | 974.76 | 29-MAR-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 | 0.00 |
April | 990.28 | 11-APR-15:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 2.20 | 0.00 |
May | 997.31 | 30-MAY-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 2.06 | 0.00 |
June | 1007.68 | 11-JUN-08:51 | 486.00 | 376.21 | 1439.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 | 0.00 |
July | 997.47 | 26-JUL-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 | 0.00 |
August | 1002.59 | 19-AUG-15:02 | 324.00 | 147.80 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 4.57 | 0.00 |
September | 984.82 | 06-SEP-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 2.81 | 0.00 |
October | 983.44 | 17-OCT-18:01 | 970.20 | 465.04 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 | 0.00 |
November | 892.40 | 08-NOV-16:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 831.98 | 11-DEC-16:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 823.19 | 324.00 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1007.68 | 970.20 | 465.04 | 1439.98 | 0.00 | 0.00 | 0.00 | 0.00 | 4.57 | 0.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2332.73 | 29-JAN-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.41 |
February | 2550.51 | 27-FEB-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
March | 2536.47 | 11-MAR-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 | 0.00 |
April | 2497.70 | 17-APR-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 | 0.00 |
May | 2544.37 | 17-MAY-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 8.75 | 0.00 |
June | 2551.52 | 22-JUN-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 | 0.00 |
July | 2561.18 | 14-JUL-08:62 | 216.00 | 313.47 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 7.78 | 0.00 |
August | 2551.22 | 04-AUG-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 9.87 | 0.00 |
September | 2540.08 | 06-SEP-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 10.37 | 0.00 |
October | 2478.55 | 02-OCT-15:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 6.48 | 0.00 |
November | 2426.98 | 14-NOV-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 |
December | 2256.42 | 11-DEC-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2256.42 | 216.00 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2561.18 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 | 10.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2022.72 | 31-JAN-16:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.46 |
February | 2502.61 | 27-FEB-16:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 | 0.00 |
March | 2445.53 | 30-MAR-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 | 0.00 |
April | 2613.99 | 16-APR-08:51 | 486.00 | 598.38 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.99 |
May | 2797.95 | 18-MAY-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 |
June | 2814.46 | 06-JUN-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 | 0.00 |
July | 2689.95 | 17-JUL-08:51 | 324.00 | 470.16 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 | 0.00 |
August | 2717.47 | 26-AUG-08:51 | 540.00 | 664.87 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.82 |
September | 2699.70 | 15-SEP-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.68 |
October | 2467.57 | 10-OCT-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 0.00 |
November | 2253.97 | 06-NOV-16:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.42 |
December | 1963.17 | 11-DEC-16:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1963.17 | 324.00 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2814.46 | 831.60 | 664.87 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 | 5.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1326.44 | 29-JAN-11:33 | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.18 |
February | 1557.51 | 27-FEB-19:10 | 12322.72 | 7217.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.57 |
March | 1916.94 | 30-MAR-15:05 | 7544.52 | 1933.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.24 | 0.00 |
April | 2094.19 | 17-APR-18:07 | 10562.33 | 6186.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.56 | 0.00 |
May | 2054.86 | 16-MAY-18:02 | 10562.33 | 6186.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.40 | 0.00 |
June | 2084.41 | 25-JUN-10:33 | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.28 | 0.00 |
July | 2156.26 | 08-JUL-17:50 | 1508.90 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.05 | 0.00 |
August | 2256.50 | 18-AUG-18:20 | 3520.78 | 2062.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.27 | 0.00 |
September | 2058.62 | 09-SEP-10:33 | 2263.36 | 966.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.81 | 0.00 |
October | 1829.59 | 11-OCT-18:10 | 10562.33 | 6186.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.78 |
November | 1538.83 | 11-NOV-11:33 | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.80 |
December | 1425.51 | 13-DEC-19:10 | 5281.16 | 3093.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1326.44 | 1508.90 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2256.50 | 12322.72 | 7217.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.05 | 18.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2700.71 | 29-JAN-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.44 |
February | 2970.50 | 27-FEB-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
March | 2868.12 | 10-MAR-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.42 |
April | 2920.95 | 09-APR-18:01 | 819.00 | 831.18 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 |
May | 2916.94 | 10-MAY-18:01 | 970.20 | 739.76 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.09 |
June | 2992.53 | 05-JUN-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 12.72 | 0.00 |
July | 3009.89 | 07-JUL-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 0.00 |
August | 3007.03 | 18-AUG-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 0.00 |
September | 2907.89 | 03-SEP-15:02 | 324.00 | 235.11 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 | 0.00 |
October | 2801.43 | 02-OCT-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 2.63 | 0.00 |
November | 2831.10 | 14-NOV-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.99 |
December | 2652.65 | 11-DEC-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2652.65 | 324.00 | 232.73 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3009.89 | 970.20 | 831.18 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 10.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2033.48 | 29-JAN-16:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.14 |
February | 2894.96 | 27-FEB-16:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 | 0.00 |
March | 2898.22 | 30-MAR-15:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 | 0.00 |
April | 2922.45 | 09-APR-20:11 | 1247.40 | 1068.54 | 1659.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.63 |
May | 2982.44 | 09-MAY-20:41 | 1602.00 | 1056.67 | 1843.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.82 |
June | 2953.70 | 05-JUN-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 12.66 | 0.00 |
July | 2975.77 | 12-JUL-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 14.63 | 0.00 |
August | 2977.28 | 18-AUG-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 17.18 | 0.00 |
September | 3248.75 | 18-SEP-16:01 | 972.00 | 332.43 | 1343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 | 0.00 |
October | 2961.26 | 07-OCT-16:21 | 858.60 | 352.62 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
November | 2748.99 | 14-NOV-16:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.74 |
December | 2428.20 | 11-DEC-16:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2033.48 | 378.00 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3248.75 | 1602.00 | 1068.54 | 1843.57 | 0.00 | 0.00 | 0.00 | 0.00 | 17.18 | 17.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1419.51 | 29-JAN-16:01 | 378.00 | 172.43 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 |
February | 1492.34 | 28-FEB-19:01 | 970.20 | 465.04 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 |
March | 1506.23 | 30-MAR-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 2.70 | 0.00 |
April | 1505.21 | 17-APR-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 | 0.00 |
May | 1510.99 | 16-MAY-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 4.55 | 0.00 |
June | 1519.68 | 20-JUN-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 6.20 | 0.00 |
July | 1518.49 | 11-JUL-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 4.22 | 0.00 |
August | 1544.38 | 19-AUG-15:02 | 324.00 | 147.80 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 8.32 | 0.00 |
September | 1548.56 | 11-SEP-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 | 0.00 |
October | 1533.18 | 08-OCT-15:02 | 324.00 | 147.80 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 3.47 | 0.00 |
November | 1482.56 | 14-NOV-16:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.27 |
December | 1401.29 | 19-DEC-16:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1401.29 | 324.00 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1548.56 | 970.20 | 465.04 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 8.32 | 7.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18423.54 | 19-JAN-22:57 | 80966.30 | 5526.25 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.58 |
February | 19645.38 | 28-FEB-22:53 | 161932.61 | 11052.49 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.87 |
March | 21161.67 | 30-MAR-21:53 | 161932.61 | 11052.49 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.24 |
April | 21227.26 | 18-APR-21:53 | 188921.38 | 12894.57 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.26 |
May | 21982.83 | 19-MAY-21:05 | 107955.07 | 7368.33 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.96 |
June | 23021.64 | 13-JUN-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 12.34 | 0.00 |
July | 23542.57 | 07-JUL-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 23.98 | 0.00 |
August | 23270.99 | 18-AUG-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 25.27 | 0.00 |
September | 22295.08 | 07-SEP-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 5.19 | 0.00 |
October | 21111.19 | 18-OCT-21:53 | 161932.61 | 11052.49 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 |
November | 19505.48 | 03-NOV-21:54 | 134943.84 | 9210.41 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.02 |
December | 19114.49 | 12-DEC-22:55 | 107955.07 | 7368.33 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18423.54 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23542.57 | 188921.38 | 12894.57 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 25.27 | 27.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20450.62 | 19-JAN-22:57 | 80966.30 | 5526.25 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.58 |
February | 21408.94 | 28-FEB-22:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.29 |
March | 22684.08 | 30-MAR-21:05 | 107955.07 | 7368.33 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.55 |
April | 22601.51 | 18-APR-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 |
May | 23307.98 | 30-MAY-21:05 | 107955.07 | 7368.33 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.96 |
June | 24278.27 | 13-JUN-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 15.21 | 0.00 |
July | 24768.72 | 07-JUL-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 23.97 | 0.00 |
August | 24488.75 | 18-AUG-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 25.26 | 0.00 |
September | 23543.29 | 07-SEP-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 5.19 | 0.00 |
October | 22628.61 | 18-OCT-21:53 | 161932.61 | 11052.49 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 |
November | 21303.33 | 03-NOV-21:54 | 134943.84 | 9210.41 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.02 |
December | 20957.14 | 12-DEC-22:55 | 107955.07 | 7368.33 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20450.62 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24768.72 | 161932.61 | 11052.49 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 25.26 | 26.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25683.27 | 29-JAN-11:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 43.72 |
February | 26873.39 | 26-FEB-11:45 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 6.02 |
March | 28815.21 | 30-MAR-15:05 | 8005.68 | 1818.05 | 87627.33 | 134956.99 | 0.00 | 0.00 | 0.00 | 12.69 | 0.00 |
April | 31027.31 | 16-APR-17:02 | 6404.54 | 3636.11 | 87627.33 | 134956.99 | 0.00 | 0.00 | 0.00 | 6.71 | 0.00 |
May | 30104.03 | 16-MAY-18:02 | 11207.95 | 5817.77 | 87627.33 | 89971.33 | 0.00 | 0.00 | 0.00 | 14.17 | 0.00 |
June | 29481.00 | 11-JUN-10:40 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 6.75 | 0.00 |
July | 29841.18 | 08-JUL-10:50 | 800.57 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 32.73 | 0.00 |
August | 29710.83 | 27-AUG-10:33 | 2401.70 | 1090.83 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 18.98 | 0.00 |
September | 29222.65 | 09-SEP-10:45 | 1601.14 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 21.93 | 0.00 |
October | 27950.88 | 09-OCT-10:33 | 2401.70 | 1090.83 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 |
November | 26522.92 | 11-NOV-11:45 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 18.88 |
December | 26098.86 | 12-DEC-11:45 | 1067.42 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 14.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 25683.27 | 800.57 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31027.31 | 11207.95 | 5817.77 | 87627.33 | 134956.99 | 0.00 | 0.00 | 0.00 | 32.73 | 43.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3068.01 | 29-JAN-11:33 | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.66 |
February | 3592.42 | 27-FEB-18:12 | 5323.20 | 3273.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.03 |
March | 4719.91 | 30-MAR-15:05 | 7984.80 | 2046.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.37 | 0.00 |
April | 5012.01 | 17-APR-18:07 | 11178.72 | 6547.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.74 | 0.00 |
May | 4927.33 | 16-MAY-18:02 | 11178.72 | 6547.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.49 | 0.00 |
June | 5325.57 | 24-JUN-17:13 | 4790.88 | 2455.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.11 | 0.00 |
July | 6500.84 | 08-JUL-16:10 | 1330.80 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.26 | 0.00 |
August | 6391.47 | 18-AUG-15:03 | 7984.80 | 2046.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.32 | 0.00 |
September | 5207.09 | 07-SEP-15:30 | 1330.80 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.98 | 0.00 |
October | 4315.07 | 10-OCT-17:12 | 5323.20 | 3273.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 0.00 |
November | 3605.37 | 05-NOV-17:12 | 4258.56 | 2728.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.59 |
December | 3339.96 | 13-DEC-11:33 | 1596.96 | 1023.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3068.01 | 1330.80 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6500.84 | 11178.72 | 6547.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.26 | 32.66 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.395221E+12 | 297524.26 | 19-JAN-20:10 | 0.405685E+12 | 356289.96 | 07-JAN-19:10 |
February | 0.364129E+12 | 312398.87 | 28-FEB-20:49 | 0.337210E+12 | 335148.80 | 14-FEB-20:00 |
March | 0.429077E+12 | 356741.03 | 30-MAR-19:10 | 0.324725E+12 | 282445.80 | 18-MAR-19:00 |
April | 0.461435E+12 | 362992.60 | 04-APR-19:00 | 0.263514E+12 | 273626.51 | 05-APR-18:00 |
May | 0.549632E+12 | 397155.35 | 30-MAY-19:40 | 0.234063E+12 | 187640.91 | 11-MAY-06:10 |
June | 0.632590E+12 | 421271.67 | 13-JUN-19:49 | 0.207635E+12 | 154023.13 | 10-JUN-17:30 |
July | 0.710749E+12 | 438478.03 | 07-JUL-19:00 | 0.206039E+12 | 136924.52 | 01-JUL-17:10 |
August | 0.731474E+12 | 445032.98 | 02-AUG-19:49 | 0.205156E+12 | 135561.01 | 31-AUG-17:49 |
September | 0.590487E+12 | 422610.12 | 07-SEP-19:19 | 0.208710E+12 | 148509.03 | 30-SEP-17:30 |
October | 0.474953E+12 | 414814.74 | 18-OCT-19:49 | 0.297527E+12 | 263648.23 | 25-OCT-18:49 |
November | 0.410174E+12 | 341501.16 | 27-NOV-20:10 | 0.306594E+12 | 310727.19 | 22-NOV-18:00 |
December | 0.398397E+12 | 296903.78 | 12-DEC-20:19 | 0.371348E+12 | 339218.40 | 30-DEC-19:10 |
Annual Sum or Average | 0.614832E+13 | 0.336821E+13 | ||||
Minimum of Months | 0.364129E+12 | 296903.78 | 0.205156E+12 | 135561.01 | ||
Maximum of Months | 0.731474E+12 | 445032.98 | 0.405685E+12 | 356289.96 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.519113E+11 | 0.172705E+11 | 0.146779E+12 | 0.544823E+11 | 0.420336E+11 | 0.759887E+10 | 0.00 | 0.677762E+10 | 0.00 | 0.00 | 0.202339E+11 | 0.444433E+11 | 0.00 |
February | 0.468418E+11 | 0.147405E+11 | 0.132565E+12 | 0.492099E+11 | 0.386601E+11 | 0.847256E+10 | 0.00 | 0.188373E+11 | 0.00 | 0.00 | 0.126024E+11 | 0.388609E+11 | 0.00 |
March | 0.514110E+11 | 0.150734E+11 | 0.146789E+12 | 0.544840E+11 | 0.447681E+11 | 0.130237E+11 | 0.00 | 0.527011E+11 | 0.00 | 0.00 | 0.591836E+10 | 0.411902E+11 | 0.00 |
April | 0.493848E+11 | 0.133424E+11 | 0.142011E+12 | 0.527241E+11 | 0.453955E+11 | 0.131849E+11 | 0.00 | 0.971725E+11 | 0.00 | 0.00 | 0.575798E+10 | 0.388455E+11 | 0.00 |
May | 0.507215E+11 | 0.127032E+11 | 0.146789E+12 | 0.544825E+11 | 0.496712E+11 | 0.139365E+11 | 0.00 | 0.169021E+12 | 0.00 | 0.00 | 0.937325E+10 | 0.391665E+11 | 0.00 |
June | 0.489261E+11 | 0.118177E+11 | 0.142058E+12 | 0.527257E+11 | 0.521000E+11 | 0.140691E+11 | 0.00 | 0.251457E+12 | 0.00 | 0.00 | 0.185634E+11 | 0.372201E+11 | 0.00 |
July | 0.506265E+11 | 0.123903E+11 | 0.146742E+12 | 0.544806E+11 | 0.551062E+11 | 0.149560E+11 | 0.00 | 0.310718E+12 | 0.00 | 0.00 | 0.239229E+11 | 0.380437E+11 | 0.00 |
August | 0.508643E+11 | 0.132958E+11 | 0.146800E+12 | 0.544837E+11 | 0.562552E+11 | 0.151768E+11 | 0.00 | 0.327933E+12 | 0.00 | 0.00 | 0.249863E+11 | 0.378981E+11 | 0.00 |
September | 0.496579E+11 | 0.140481E+11 | 0.142022E+12 | 0.527244E+11 | 0.499552E+11 | 0.138298E+11 | 0.00 | 0.212480E+12 | 0.00 | 0.00 | 0.145517E+11 | 0.375628E+11 | 0.00 |
October | 0.517367E+11 | 0.158058E+11 | 0.146768E+12 | 0.544821E+11 | 0.471624E+11 | 0.132504E+11 | 0.00 | 0.948781E+11 | 0.00 | 0.00 | 0.675491E+10 | 0.403689E+11 | 0.00 |
November | 0.501725E+11 | 0.164250E+11 | 0.142074E+12 | 0.527253E+11 | 0.432305E+11 | 0.122220E+11 | 0.00 | 0.406270E+11 | 0.00 | 0.00 | 0.868133E+10 | 0.404257E+11 | 0.00 |
December | 0.518768E+11 | 0.175768E+11 | 0.146742E+12 | 0.544814E+11 | 0.425063E+11 | 0.993353E+10 | 0.00 | 0.132582E+11 | 0.00 | 0.00 | 0.151518E+11 | 0.431686E+11 | 0.00 |
Annual Sum or Average | 0.604131E+12 | 0.174489E+12 | 0.172814E+13 | 0.641486E+12 | 0.566844E+12 | 0.149654E+12 | 0.00 | 0.159586E+13 | 0.00 | 0.00 | 0.166498E+12 | 0.477194E+12 | 0.00 |
Minimum of Months | 0.468418E+11 | 0.118177E+11 | 0.132565E+12 | 0.492099E+11 | 0.386601E+11 | 0.759887E+10 | 0.00 | 0.677762E+10 | 0.00 | 0.00 | 0.575798E+10 | 0.372201E+11 | 0.00 |
Maximum of Months | 0.519113E+11 | 0.175768E+11 | 0.146800E+12 | 0.544840E+11 | 0.562552E+11 | 0.151768E+11 | 0.00 | 0.327933E+12 | 0.00 | 0.00 | 0.249863E+11 | 0.444433E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.139223E+12 | 0.00 | 0.114544E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.101906E+12 | 0.00 | 0.981003E+11 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.764288E+11 | 0.00 | 0.962726E+11 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.348100E+11 | 0.00 | 0.817486E+11 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.104365E+11 | 0.00 | 0.716484E+11 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.172759E+10 | 0.00 | 0.587938E+11 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 52020249.74 | 0.00 | 0.541664E+11 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 28395539.33 | 0.00 | 0.530892E+11 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.183299E+10 | 0.00 | 0.599065E+11 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.685583E+11 | 0.00 | 0.770657E+11 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.708180E+11 | 0.00 | 0.886851E+11 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.114735E+12 | 0.00 | 0.104793E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.620557E+12 | 0.00 | 0.958814E+12 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 28395539.33 | 0.00 | 0.530892E+11 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.139223E+12 | 0.00 | 0.114544E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 50471.22 | 02-JAN-20:10 | 11096.45 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 39155.93 | 02-JAN-07:19 | 24796.64 | 31-JAN-22:40 | 5475.52 | 12-JAN-17:00 | 0.00 | 01-JAN-00:10 |
February | 50471.22 | 01-FEB-20:10 | 11096.45 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 39155.93 | 01-FEB-07:19 | 29584.74 | 28-FEB-22:00 | 5450.58 | 11-FEB-09:39 | 0.00 | 01-FEB-00:10 |
March | 50471.22 | 01-MAR-20:10 | 11096.45 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 39155.93 | 01-MAR-07:19 | 33295.53 | 30-MAR-21:00 | 5633.74 | 30-MAR-15:09 | 0.00 | 01-MAR-00:10 |
April | 50471.22 | 03-APR-19:10 | 11096.45 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 39155.93 | 03-APR-06:19 | 33168.51 | 17-APR-21:00 | 5959.23 | 15-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 50471.22 | 01-MAY-19:19 | 11096.45 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 39155.56 | 08-MAY-06:19 | 34819.57 | 31-MAY-21:00 | 6133.31 | 30-MAY-21:00 | 0.00 | 01-MAY-00:10 |
June | 50471.22 | 01-JUN-19:40 | 11096.45 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 39155.37 | 23-JUN-06:19 | 36768.66 | 26-JUN-21:00 | 6663.02 | 30-JUN-19:49 | 0.00 | 01-JUN-00:10 |
July | 50471.22 | 03-JUL-19:49 | 11096.45 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 39155.49 | 28-JUL-06:19 | 38323.94 | 07-JUL-21:10 | 6875.90 | 18-JUL-18:00 | 0.00 | 01-JUL-00:10 |
August | 50471.22 | 01-AUG-19:40 | 11096.45 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 39155.93 | 25-AUG-06:19 | 39890.65 | 18-AUG-21:10 | 7783.96 | 23-AUG-19:00 | 0.00 | 01-AUG-00:10 |
September | 50471.22 | 01-SEP-19:10 | 11096.45 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 39155.93 | 01-SEP-06:19 | 38684.39 | 08-SEP-21:19 | 6342.57 | 07-SEP-18:19 | 0.00 | 01-SEP-00:10 |
October | 50471.22 | 02-OCT-19:10 | 11096.45 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 39155.93 | 02-OCT-06:19 | 36163.43 | 10-OCT-21:00 | 6524.31 | 18-OCT-20:00 | 0.00 | 01-OCT-00:10 |
November | 50471.22 | 01-NOV-19:10 | 11096.45 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 39155.93 | 01-NOV-06:19 | 31074.04 | 02-NOV-21:00 | 5465.13 | 21-NOV-16:40 | 0.00 | 01-NOV-00:10 |
December | 50471.22 | 01-DEC-20:10 | 11096.45 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 39155.93 | 01-DEC-07:19 | 29427.94 | 12-DEC-22:00 | 5491.66 | 18-DEC-17:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 50471.22 | 11096.45 | 88863.15 | 39155.37 | 24796.64 | 5450.58 | 0.00 | |||||||
Maximum of Months | 50471.22 | 11096.45 | 88863.15 | 39155.93 | 39890.65 | 7783.96 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 53035.07 | 19-JAN-22:00 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 40650.64 | 03-JAN-19:49 | 0.00 |
February | 86660.22 | 26-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:00 | 40595.29 | 23-FEB-19:10 | 0.00 |
March | 113235.65 | 30-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 03-MAR-01:19 | 41584.30 | 30-MAR-18:40 | 0.00 |
April | 113405.01 | 12-APR-15:20 | 0.00 | 0.00 | 9938.94 | 02-APR-15:20 | 42387.90 | 27-APR-17:00 | 0.00 |
May | 141045.60 | 30-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAY-15:00 | 43048.66 | 25-MAY-20:30 | 0.00 |
June | 170307.75 | 28-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-08:30 | 42442.14 | 28-JUN-20:00 | 0.00 |
July | 190317.43 | 08-JUL-15:20 | 0.00 | 0.00 | 9938.94 | 01-JUL-00:10 | 41988.70 | 25-JUL-20:30 | 0.00 |
August | 190253.28 | 18-AUG-18:19 | 0.00 | 0.00 | 9938.94 | 01-AUG-00:10 | 41837.71 | 08-AUG-20:30 | 0.00 |
September | 166880.93 | 07-SEP-15:20 | 0.00 | 0.00 | 9938.94 | 01-SEP-09:20 | 42726.77 | 14-SEP-20:30 | 0.00 |
October | 153620.34 | 18-OCT-20:00 | 0.00 | 0.00 | 9938.94 | 01-OCT-15:20 | 43981.56 | 04-OCT-20:00 | 0.00 |
November | 95143.96 | 05-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 05-NOV-15:30 | 42895.78 | 02-NOV-18:19 | 0.00 |
December | 73119.80 | 12-DEC-16:10 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 41859.15 | 01-DEC-19:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 53035.07 | 0.00 | 0.00 | 9938.94 | 40595.29 | 0.00 | |||
Maximum of Months | 190317.43 | 0.00 | 0.00 | 9938.94 | 43981.56 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 297524.26 | 19-JAN-20:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 21252.93 | 5052.14 | 0.00 | 48720.16 | 0.00 |
February | 312398.87 | 28-FEB-20:49 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 23707.67 | 5091.75 | 0.00 | 61415.94 | 0.00 |
March | 356741.03 | 30-MAR-19:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 26714.63 | 5491.78 | 0.00 | 99475.55 | 0.00 |
April | 362992.60 | 04-APR-19:00 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 26545.18 | 5509.50 | 0.00 | 99477.00 | 0.00 |
May | 397155.35 | 30-MAY-19:40 | 50471.22 | 87982.85 | 11096.45 | 31577.31 | 29461.47 | 5993.68 | 0.00 | 129977.39 | 0.00 |
June | 421271.67 | 13-JUN-19:49 | 50471.22 | 87982.85 | 11096.45 | 31577.45 | 31941.40 | 6051.53 | 0.00 | 152463.60 | 0.00 |
July | 438478.03 | 07-JUL-19:00 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 33743.71 | 6268.01 | 0.00 | 167909.06 | 0.00 |
August | 445032.98 | 02-AUG-19:49 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 31462.77 | 6520.32 | 0.00 | 176239.15 | 0.00 |
September | 422610.12 | 07-SEP-19:19 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 30981.30 | 6290.92 | 0.00 | 153533.19 | 0.00 |
October | 414814.74 | 18-OCT-19:49 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 26395.19 | 6467.28 | 0.00 | 149143.75 | 0.00 |
November | 341501.16 | 27-NOV-20:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 23511.81 | 5298.55 | 0.00 | 80301.70 | 0.00 |
December | 296903.78 | 12-DEC-20:19 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 23075.28 | 5084.63 | 0.00 | 45552.07 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 296903.78 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 21252.93 | 5052.14 | 0.00 | 45552.07 | 0.00 | |
Maximum of Months | 445032.98 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 33743.71 | 6520.32 | 0.00 | 176239.15 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 189100.34 | 07-JAN-16:10 | 0.00 | 109467.80 | 31-JAN-23:49 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 211479.66 | 12-FEB-07:10 | 0.00 | 101456.64 | 01-FEB-17:00 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 153191.01 | 16-MAR-07:00 | 0.00 | 88128.41 | 01-MAR-18:10 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 126346.28 | 10-APR-04:49 | 0.00 | 74250.26 | 01-APR-21:40 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 120624.25 | 10-MAY-04:00 | 0.00 | 58358.87 | 01-MAY-19:49 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 57626.83 | 10-JUN-04:00 | 0.00 | 43104.76 | 01-JUN-21:49 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 5841.09 | 28-JUL-15:09 | 0.00 | 32676.65 | 01-JUL-20:49 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 2423.62 | 04-AUG-08:09 | 0.00 | 31312.88 | 31-AUG-21:30 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 60933.75 | 29-SEP-03:00 | 0.00 | 44739.74 | 30-SEP-20:00 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 172347.85 | 31-OCT-08:09 | 0.00 | 64862.27 | 31-OCT-18:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 147740.91 | 24-NOV-07:40 | 0.00 | 83053.96 | 30-NOV-22:30 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 167845.08 | 23-DEC-09:09 | 0.00 | 98954.59 | 31-DEC-17:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 2423.62 | 0.00 | 31312.88 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 211479.66 | 0.00 | 109467.80 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.75 | 0.33 | 24.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 24.75 | 0.33 | 24.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.75 | 0.33 | 24.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.75 | 2.33 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.76 | 2.50 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.74 | 1.00 | 21.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.83 | 21.74 | 6.83 | 21.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.76 | 2.50 | 21.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.73 | 3.67 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 21.78 | 6.50 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.75 | 2.83 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.81 | 0.50 | 21.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.86 | 0.17 | 21.86 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 14.00 | 21.76 | 14.00 | 21.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 21.86 | 6.50 | 21.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.73 | 0.33 | 21.73 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.81 | 2.00 | 21.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.80 | 5.17 | 21.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 21.76 | 11.33 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 21.81 | 13.67 | 21.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 21.76 | 9.50 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.76 | 4.17 | 21.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.79 | 1.00 | 21.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 47.33 | 21.78 | 47.33 | 21.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 21.81 | 13.67 | 21.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.76 | 0.17 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.72 | 2.33 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.74 | 2.00 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.00 | 21.73 | 5.00 | 21.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.76 | 2.33 | 21.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 22.12 | 1.00 | 22.12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 22.11 | 5.00 | 22.11 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 22.18 | 9.83 | 22.18 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 22.16 | 13.17 | 22.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 22.11 | 7.67 | 22.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 22.16 | 4.33 | 22.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.72 | 0.67 | 21.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 41.67 | 22.14 | 41.67 | 22.14 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 22.18 | 13.17 | 22.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.70 | 0.83 | 21.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.73 | 1.50 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.78 | 3.67 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.80 | 3.67 | 21.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.79 | 1.17 | 21.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.72 | 0.33 | 21.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.50 | 21.77 | 11.50 | 21.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.80 | 3.67 | 21.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.75 | 4.17 | 21.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 21.81 | 6.17 | 21.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.76 | 4.17 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.85 | 0.50 | 21.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.83 | 0.17 | 21.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 15.83 | 21.78 | 15.83 | 21.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 21.85 | 6.17 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 22.00 | 0.50 | 22.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.86 | 1.50 | 21.86 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.84 | 1.67 | 21.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.81 | 1.67 | 21.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.69 | 0.50 | 21.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.78 | 2.83 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.84 | 4.33 | 21.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.85 | 3.33 | 21.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.88 | 3.67 | 21.88 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.87 | 2.00 | 21.87 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.90 | 1.17 | 21.90 |
Annual Sum or Average | 0.00 | 0.00 | 23.33 | 21.84 | 23.33 | 21.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 22.00 | 4.33 | 22.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.64 | 0.67 | 24.64 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 24.85 | 12.17 | 24.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.73 | 3.83 | 24.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.68 | 0.67 | 24.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.62 | 0.17 | 24.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 17.50 | 24.81 | 17.50 | 24.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 24.85 | 12.17 | 24.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.49 | 0.67 | 22.49 | 0.67 | 22.49 |
February | 672.00 | 21.89 | 0.00 | 21.89 | 0.00 | 21.89 |
March | 744.00 | 21.33 | 14.33 | 21.32 | 14.33 | 21.32 |
April | 720.00 | 21.11 | 3.17 | 21.11 | 3.17 | 21.11 |
May | 744.00 | 21.28 | 0.00 | 21.28 | 0.00 | 21.28 |
June | 720.00 | 22.01 | 0.00 | 22.01 | 0.00 | 22.01 |
July | 744.00 | 22.59 | 15.33 | 22.60 | 15.33 | 22.60 |
August | 480.00 | 23.06 | 79.17 | 23.12 | 68.17 | 23.15 |
September | 110.00 | 23.75 | 418.50 | 23.89 | 80.17 | 23.89 |
October | 147.33 | 23.78 | 218.33 | 23.88 | 29.33 | 23.89 |
November | 344.33 | 23.87 | 122.50 | 23.89 | 4.83 | 23.89 |
December | 650.67 | 23.61 | 20.00 | 23.62 | 0.00 | 23.62 |
Annual Sum or Average | 6820.33 | 22.25 | 892.00 | 22.43 | 216.00 | 22.46 |
Minimum of Months | 110.00 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 744.00 | 23.87 | 418.50 | 23.89 | 80.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 738.50 | 21.22 | 267.33 | 21.16 | 267.33 | 21.13 |
February | 641.50 | 21.32 | 168.50 | 21.26 | 168.50 | 21.21 |
March | 672.67 | 21.71 | 35.83 | 21.78 | 7.17 | 21.78 |
April | 602.67 | 21.85 | 43.83 | 21.99 | 1.00 | 21.98 |
May | 528.17 | 22.18 | 115.67 | 22.42 | 0.00 | 22.42 |
June | 231.67 | 22.53 | 355.17 | 23.21 | 0.00 | 23.21 |
July | 128.33 | 22.43 | 481.00 | 23.45 | 0.00 | 23.45 |
August | 26.00 | 22.76 | 605.83 | 23.71 | 0.00 | 23.71 |
September | 321.00 | 22.24 | 278.83 | 22.94 | 0.00 | 22.94 |
October | 558.50 | 21.85 | 124.17 | 22.21 | 0.00 | 22.21 |
November | 654.00 | 21.53 | 42.00 | 21.59 | 19.17 | 21.57 |
December | 714.83 | 21.33 | 97.17 | 21.31 | 90.67 | 21.28 |
Annual Sum or Average | 5817.83 | 21.69 | 2615.33 | 22.14 | 553.83 | 22.07 |
Minimum of Months | 26.00 | 21.22 | 35.83 | 21.16 | 0.00 | 21.13 |
Maximum of Months | 738.50 | 22.76 | 605.83 | 23.71 | 267.33 | 23.71 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.63 | 8.83 | 21.63 | 8.83 | 21.63 |
February | 668.50 | 21.95 | 16.33 | 21.92 | 16.33 | 21.90 |
March | 685.83 | 22.56 | 19.67 | 22.59 | 0.00 | 22.59 |
April | 567.67 | 22.74 | 61.33 | 22.84 | 18.00 | 22.85 |
May | 481.50 | 22.95 | 267.67 | 23.22 | 109.50 | 23.25 |
June | 302.00 | 23.37 | 371.67 | 23.65 | 123.83 | 23.69 |
July | 223.33 | 23.50 | 475.67 | 23.76 | 135.67 | 23.78 |
August | 175.33 | 23.85 | 537.17 | 23.88 | 152.67 | 23.90 |
September | 325.33 | 23.22 | 370.00 | 23.53 | 131.33 | 23.57 |
October | 590.83 | 22.78 | 92.33 | 22.90 | 42.83 | 22.94 |
November | 697.17 | 22.51 | 17.33 | 22.53 | 12.83 | 22.54 |
December | 733.67 | 21.99 | 1.00 | 21.99 | 0.67 | 21.99 |
Annual Sum or Average | 6195.17 | 22.52 | 2239.00 | 22.86 | 752.50 | 22.93 |
Minimum of Months | 175.33 | 21.63 | 1.00 | 21.63 | 0.00 | 21.63 |
Maximum of Months | 744.00 | 23.85 | 537.17 | 23.88 | 152.67 | 23.90 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.05 | 275.17 | 21.04 | 275.17 | 21.03 |
February | 672.00 | 21.25 | 172.50 | 21.20 | 172.50 | 21.17 |
March | 744.00 | 21.73 | 11.67 | 21.72 | 11.67 | 21.71 |
April | 720.00 | 22.29 | 0.00 | 22.29 | 0.00 | 22.29 |
May | 701.33 | 22.81 | 0.17 | 22.81 | 0.00 | 22.81 |
June | 257.33 | 23.18 | 191.00 | 23.48 | 0.00 | 23.48 |
July | 100.50 | 23.14 | 359.50 | 23.74 | 0.00 | 23.74 |
August | 32.83 | 23.31 | 425.33 | 23.86 | 0.00 | 23.86 |
September | 474.00 | 23.05 | 41.17 | 23.12 | 0.00 | 23.12 |
October | 740.33 | 22.32 | 0.00 | 22.32 | 0.00 | 22.32 |
November | 720.00 | 21.69 | 6.00 | 21.68 | 6.00 | 21.67 |
December | 744.00 | 21.18 | 97.00 | 21.16 | 97.00 | 21.14 |
Annual Sum or Average | 6650.33 | 21.96 | 1579.50 | 22.13 | 562.33 | 22.06 |
Minimum of Months | 32.83 | 21.05 | 0.00 | 21.04 | 0.00 | 21.03 |
Maximum of Months | 744.00 | 23.31 | 425.33 | 23.86 | 275.17 | 23.86 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.02 | 307.50 | 21.01 | 307.50 | 21.01 |
February | 672.00 | 21.18 | 189.50 | 21.14 | 189.50 | 21.11 |
March | 744.00 | 21.59 | 16.00 | 21.58 | 16.00 | 21.57 |
April | 720.00 | 22.14 | 0.00 | 22.14 | 0.00 | 22.14 |
May | 740.83 | 22.71 | 0.00 | 22.71 | 0.00 | 22.71 |
June | 330.50 | 23.14 | 49.00 | 23.23 | 0.00 | 23.23 |
July | 146.00 | 23.14 | 238.17 | 23.60 | 0.00 | 23.60 |
August | 52.67 | 23.31 | 279.00 | 23.76 | 0.00 | 23.76 |
September | 589.00 | 23.00 | 2.67 | 23.00 | 0.00 | 23.00 |
October | 744.00 | 22.16 | 0.00 | 22.16 | 0.00 | 22.16 |
November | 720.00 | 21.54 | 8.83 | 21.54 | 8.83 | 21.53 |
December | 744.00 | 21.10 | 117.33 | 21.09 | 117.33 | 21.08 |
Annual Sum or Average | 6947.00 | 21.91 | 1208.00 | 21.97 | 639.17 | 21.90 |
Minimum of Months | 52.67 | 21.02 | 0.00 | 21.01 | 0.00 | 21.01 |
Maximum of Months | 744.00 | 23.31 | 307.50 | 23.76 | 307.50 | 23.76 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 304.67 | 22.54 | 396.67 | 23.09 | 139.67 | 23.24 |
February | 254.50 | 22.72 | 390.17 | 23.16 | 137.33 | 23.31 |
March | 280.83 | 23.14 | 539.33 | 23.22 | 197.83 | 23.37 |
April | 278.83 | 23.53 | 607.67 | 23.24 | 235.67 | 23.40 |
May | 300.33 | 23.86 | 690.33 | 23.23 | 288.67 | 23.40 |
June | 299.33 | 23.90 | 697.33 | 23.19 | 293.50 | 23.37 |
July | 311.50 | 23.94 | 737.83 | 23.18 | 311.50 | 23.36 |
August | 314.17 | 23.95 | 741.17 | 23.18 | 314.17 | 23.35 |
September | 295.67 | 23.92 | 686.83 | 23.23 | 291.83 | 23.40 |
October | 293.17 | 23.52 | 647.50 | 23.20 | 247.33 | 23.36 |
November | 256.33 | 23.14 | 506.83 | 23.24 | 180.83 | 23.38 |
December | 267.00 | 22.78 | 445.83 | 23.18 | 152.17 | 23.32 |
Annual Sum or Average | 3456.33 | 23.43 | 7087.50 | 23.20 | 2790.50 | 23.36 |
Minimum of Months | 254.50 | 22.54 | 390.17 | 23.09 | 137.33 | 23.24 |
Maximum of Months | 314.17 | 23.95 | 741.17 | 23.24 | 314.17 | 23.40 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 709.50 | 22.02 | 60.33 | 21.97 | 58.17 | 21.93 |
February | 583.67 | 22.19 | 58.50 | 22.25 | 34.67 | 22.25 |
March | 512.50 | 22.67 | 146.67 | 22.92 | 38.67 | 22.97 |
April | 429.83 | 22.76 | 282.17 | 23.15 | 98.83 | 23.22 |
May | 420.17 | 23.21 | 470.83 | 23.43 | 240.33 | 23.51 |
June | 306.33 | 23.67 | 564.33 | 23.66 | 250.33 | 23.72 |
July | 348.17 | 23.79 | 672.00 | 23.71 | 326.67 | 23.76 |
August | 322.83 | 23.92 | 714.17 | 23.80 | 320.00 | 23.83 |
September | 361.00 | 23.48 | 589.17 | 23.64 | 282.67 | 23.69 |
October | 368.33 | 22.77 | 375.17 | 23.28 | 116.00 | 23.34 |
November | 544.50 | 22.67 | 148.50 | 22.91 | 63.33 | 22.97 |
December | 659.50 | 22.28 | 51.33 | 22.39 | 17.83 | 22.43 |
Annual Sum or Average | 5566.33 | 22.80 | 4133.17 | 23.17 | 1847.50 | 23.26 |
Minimum of Months | 306.33 | 22.02 | 51.33 | 21.97 | 17.83 | 21.93 |
Maximum of Months | 709.50 | 23.92 | 714.17 | 23.80 | 326.67 | 23.83 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 737.17 | 22.28 | 6.17 | 22.29 | 6.17 | 22.30 |
February | 642.50 | 22.52 | 19.83 | 22.55 | 18.33 | 22.57 |
March | 588.67 | 22.93 | 92.83 | 23.06 | 25.67 | 23.09 |
April | 465.83 | 23.02 | 199.00 | 23.28 | 85.83 | 23.35 |
May | 414.50 | 23.33 | 375.67 | 23.59 | 207.50 | 23.66 |
June | 281.67 | 23.68 | 478.83 | 23.76 | 207.67 | 23.81 |
July | 311.17 | 23.88 | 599.33 | 23.83 | 289.50 | 23.86 |
August | 284.50 | 23.98 | 661.50 | 23.85 | 283.50 | 23.88 |
September | 305.67 | 23.72 | 532.83 | 23.78 | 248.17 | 23.82 |
October | 386.83 | 23.10 | 246.00 | 23.37 | 98.00 | 23.44 |
November | 595.00 | 22.98 | 75.67 | 23.08 | 44.67 | 23.12 |
December | 704.67 | 22.63 | 30.83 | 22.68 | 5.67 | 22.69 |
Annual Sum or Average | 5718.17 | 23.00 | 3318.50 | 23.30 | 1520.67 | 23.39 |
Minimum of Months | 281.67 | 22.28 | 6.17 | 22.29 | 5.67 | 22.30 |
Maximum of Months | 737.17 | 23.98 | 661.50 | 23.85 | 289.50 | 23.88 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.94 | 372.67 | 20.87 | 372.67 | 20.83 |
February | 670.83 | 21.11 | 227.00 | 21.00 | 227.00 | 20.93 |
March | 732.67 | 21.47 | 14.33 | 21.45 | 14.33 | 21.44 |
April | 692.00 | 21.56 | 3.50 | 21.56 | 3.50 | 21.56 |
May | 684.17 | 21.55 | 1.33 | 21.55 | 1.33 | 21.55 |
June | 620.50 | 21.48 | 3.17 | 21.48 | 2.00 | 21.49 |
July | 626.50 | 21.44 | 12.33 | 21.47 | 6.17 | 21.48 |
August | 614.00 | 21.41 | 7.50 | 21.43 | 3.17 | 21.44 |
September | 643.83 | 21.50 | 4.67 | 21.52 | 4.00 | 21.52 |
October | 714.17 | 21.47 | 30.00 | 21.47 | 30.00 | 21.46 |
November | 715.50 | 21.40 | 39.17 | 21.38 | 39.17 | 21.36 |
December | 744.00 | 21.13 | 180.83 | 21.06 | 180.83 | 21.01 |
Annual Sum or Average | 8202.17 | 21.37 | 896.50 | 21.31 | 884.17 | 21.27 |
Minimum of Months | 614.00 | 20.94 | 1.33 | 20.87 | 1.33 | 20.83 |
Maximum of Months | 744.00 | 21.56 | 372.67 | 21.56 | 372.67 | 21.56 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.69 | 535.17 | 20.63 | 535.17 | 20.60 |
February | 672.00 | 20.98 | 298.67 | 20.83 | 298.67 | 20.75 |
March | 733.50 | 21.56 | 33.33 | 21.52 | 32.33 | 21.49 |
April | 663.17 | 21.82 | 29.17 | 21.91 | 14.83 | 21.92 |
May | 624.50 | 21.90 | 77.50 | 22.12 | 43.50 | 22.19 |
June | 586.83 | 21.80 | 65.00 | 22.03 | 46.17 | 22.16 |
July | 604.50 | 21.81 | 96.50 | 22.09 | 80.83 | 22.27 |
August | 606.83 | 21.71 | 67.33 | 21.93 | 57.33 | 22.08 |
September | 633.17 | 21.91 | 56.83 | 22.06 | 49.33 | 22.17 |
October | 709.00 | 21.63 | 57.00 | 21.67 | 49.83 | 21.67 |
November | 720.00 | 21.28 | 90.83 | 21.22 | 90.83 | 21.18 |
December | 744.00 | 20.86 | 379.50 | 20.77 | 379.50 | 20.73 |
Annual Sum or Average | 8041.50 | 21.47 | 1786.83 | 21.45 | 1678.33 | 21.40 |
Minimum of Months | 586.83 | 20.69 | 29.17 | 20.63 | 14.83 | 20.60 |
Maximum of Months | 744.00 | 21.91 | 535.17 | 22.12 | 535.17 | 22.27 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.98 | 309.50 | 20.92 | 309.50 | 20.88 |
February | 672.00 | 21.18 | 191.33 | 21.09 | 191.33 | 21.04 |
March | 744.00 | 21.51 | 10.17 | 21.50 | 10.17 | 21.49 |
April | 718.67 | 21.84 | 6.83 | 21.85 | 6.83 | 21.87 |
May | 738.00 | 22.04 | 28.50 | 22.09 | 28.50 | 22.13 |
June | 717.50 | 22.00 | 47.50 | 22.10 | 47.00 | 22.18 |
July | 741.00 | 22.02 | 82.17 | 22.16 | 81.83 | 22.27 |
August | 743.00 | 21.93 | 61.00 | 22.04 | 61.00 | 22.13 |
September | 718.33 | 22.01 | 43.00 | 22.09 | 42.83 | 22.16 |
October | 744.00 | 21.67 | 28.67 | 21.70 | 28.67 | 21.73 |
November | 720.00 | 21.37 | 16.67 | 21.36 | 16.67 | 21.35 |
December | 744.00 | 21.12 | 137.00 | 21.08 | 137.00 | 21.05 |
Annual Sum or Average | 8744.50 | 21.64 | 962.33 | 21.63 | 961.33 | 21.63 |
Minimum of Months | 672.00 | 20.98 | 6.83 | 20.92 | 6.83 | 20.88 |
Maximum of Months | 744.00 | 22.04 | 309.50 | 22.16 | 309.50 | 22.27 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.98 | 369.17 | 20.91 | 369.17 | 20.87 |
February | 672.00 | 21.16 | 213.00 | 21.06 | 213.00 | 20.99 |
March | 740.67 | 21.55 | 16.67 | 21.53 | 16.67 | 21.51 |
April | 686.00 | 21.60 | 3.33 | 21.60 | 3.33 | 21.61 |
May | 667.17 | 21.54 | 0.83 | 21.54 | 0.83 | 21.54 |
June | 580.00 | 21.37 | 0.83 | 21.37 | 0.50 | 21.37 |
July | 579.33 | 21.30 | 6.17 | 21.31 | 4.83 | 21.33 |
August | 582.00 | 21.31 | 2.50 | 21.32 | 2.17 | 21.33 |
September | 621.67 | 21.46 | 4.00 | 21.46 | 4.00 | 21.47 |
October | 719.50 | 21.52 | 29.00 | 21.52 | 29.00 | 21.51 |
November | 720.00 | 21.46 | 33.50 | 21.43 | 33.50 | 21.41 |
December | 744.00 | 21.17 | 174.83 | 21.10 | 174.83 | 21.06 |
Annual Sum or Average | 8056.33 | 21.37 | 853.83 | 21.32 | 851.83 | 21.27 |
Minimum of Months | 579.33 | 20.98 | 0.83 | 20.91 | 0.50 | 20.87 |
Maximum of Months | 744.00 | 21.60 | 369.17 | 21.60 | 369.17 | 21.61 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.71 | 529.33 | 20.65 | 529.33 | 20.62 |
February | 672.00 | 21.01 | 298.17 | 20.87 | 298.17 | 20.79 |
March | 744.00 | 21.58 | 32.00 | 21.55 | 32.00 | 21.52 |
April | 705.17 | 21.97 | 17.00 | 22.00 | 12.50 | 22.02 |
May | 617.33 | 21.96 | 73.83 | 22.18 | 43.00 | 22.26 |
June | 539.83 | 21.76 | 73.17 | 22.12 | 48.50 | 22.31 |
July | 563.17 | 21.82 | 101.00 | 22.21 | 81.33 | 22.45 |
August | 572.83 | 21.68 | 68.50 | 21.96 | 58.17 | 22.15 |
September | 638.67 | 21.99 | 62.67 | 22.17 | 49.67 | 22.29 |
October | 742.00 | 21.73 | 51.00 | 21.74 | 50.17 | 21.75 |
November | 720.00 | 21.26 | 79.67 | 21.21 | 79.67 | 21.18 |
December | 744.00 | 20.87 | 368.00 | 20.80 | 368.00 | 20.77 |
Annual Sum or Average | 8003.00 | 21.50 | 1754.33 | 21.50 | 1650.50 | 21.47 |
Minimum of Months | 539.83 | 20.71 | 17.00 | 20.65 | 12.50 | 20.62 |
Maximum of Months | 744.00 | 21.99 | 529.33 | 22.21 | 529.33 | 22.45 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.02 | 188.50 | 21.01 | 188.50 | 21.01 |
February | 672.00 | 21.21 | 144.83 | 21.17 | 144.83 | 21.15 |
March | 744.00 | 21.80 | 1.00 | 21.80 | 1.00 | 21.80 |
April | 720.00 | 22.40 | 30.00 | 22.41 | 30.00 | 22.42 |
May | 744.00 | 22.85 | 129.83 | 22.86 | 129.83 | 22.86 |
June | 509.50 | 23.34 | 195.17 | 23.41 | 176.17 | 23.43 |
July | 333.83 | 23.55 | 363.33 | 23.66 | 245.50 | 23.66 |
August | 285.67 | 23.69 | 380.00 | 23.75 | 255.83 | 23.75 |
September | 640.83 | 23.15 | 189.17 | 23.19 | 187.33 | 23.21 |
October | 744.00 | 22.27 | 54.83 | 22.30 | 54.83 | 22.32 |
November | 720.00 | 21.49 | 14.50 | 21.49 | 14.50 | 21.49 |
December | 744.00 | 21.09 | 77.17 | 21.08 | 77.17 | 21.08 |
Annual Sum or Average | 7601.83 | 22.14 | 1768.33 | 22.29 | 1505.50 | 22.35 |
Minimum of Months | 285.67 | 21.02 | 1.00 | 21.01 | 1.00 | 21.01 |
Maximum of Months | 744.00 | 23.69 | 380.00 | 23.75 | 255.83 | 23.75 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.81 | 543.83 | 20.75 | 543.83 | 20.73 |
February | 670.00 | 20.99 | 339.33 | 20.87 | 339.33 | 20.82 |
March | 729.00 | 21.39 | 49.67 | 21.35 | 49.67 | 21.31 |
April | 672.50 | 21.47 | 31.00 | 21.48 | 31.00 | 21.49 |
May | 655.50 | 21.46 | 18.33 | 21.47 | 17.50 | 21.47 |
June | 597.33 | 21.40 | 14.50 | 21.44 | 9.33 | 21.46 |
July | 606.17 | 21.38 | 40.33 | 21.47 | 20.50 | 21.50 |
August | 595.33 | 21.35 | 31.67 | 21.44 | 12.17 | 21.47 |
September | 623.33 | 21.43 | 26.83 | 21.46 | 22.17 | 21.48 |
October | 704.50 | 21.38 | 66.50 | 21.36 | 66.50 | 21.33 |
November | 713.33 | 21.31 | 118.83 | 21.26 | 118.83 | 21.23 |
December | 743.67 | 21.00 | 376.33 | 20.91 | 376.33 | 20.87 |
Annual Sum or Average | 8054.67 | 21.27 | 1657.17 | 21.21 | 1607.17 | 21.15 |
Minimum of Months | 595.33 | 20.81 | 14.50 | 20.75 | 9.33 | 20.73 |
Maximum of Months | 744.00 | 21.47 | 543.83 | 21.48 | 543.83 | 21.50 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.59 | 623.83 | 20.55 | 623.83 | 20.54 |
February | 670.50 | 20.88 | 391.67 | 20.75 | 391.67 | 20.69 |
March | 731.00 | 21.46 | 86.50 | 21.39 | 85.33 | 21.33 |
April | 636.33 | 21.71 | 71.33 | 21.83 | 48.83 | 21.83 |
May | 595.67 | 21.79 | 106.50 | 22.07 | 63.50 | 22.14 |
June | 569.50 | 21.72 | 78.50 | 21.98 | 57.33 | 22.11 |
July | 593.17 | 21.76 | 123.67 | 22.06 | 99.00 | 22.24 |
August | 594.00 | 21.66 | 88.67 | 21.89 | 75.33 | 22.05 |
September | 616.67 | 21.81 | 86.00 | 21.98 | 78.00 | 22.08 |
October | 704.00 | 21.52 | 112.83 | 21.52 | 104.50 | 21.50 |
November | 719.50 | 21.16 | 232.00 | 21.08 | 232.00 | 21.03 |
December | 744.00 | 20.72 | 545.17 | 20.66 | 545.17 | 20.64 |
Annual Sum or Average | 7918.33 | 21.37 | 2546.67 | 21.34 | 2404.50 | 21.29 |
Minimum of Months | 569.50 | 20.59 | 71.33 | 20.55 | 48.83 | 20.54 |
Maximum of Months | 744.00 | 21.81 | 623.83 | 22.07 | 623.83 | 22.24 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.83 | 21.28 | 223.00 | 21.15 | 223.00 | 21.07 |
February | 660.50 | 21.33 | 134.67 | 21.24 | 134.67 | 21.17 |
March | 716.50 | 21.50 | 12.83 | 21.49 | 12.83 | 21.47 |
April | 683.50 | 21.55 | 4.00 | 21.55 | 4.00 | 21.55 |
May | 696.83 | 21.57 | 4.50 | 21.57 | 4.50 | 21.58 |
June | 649.67 | 21.55 | 10.67 | 21.57 | 10.67 | 21.59 |
July | 650.50 | 21.50 | 20.33 | 21.53 | 20.33 | 21.56 |
August | 630.67 | 21.46 | 22.17 | 21.50 | 16.17 | 21.53 |
September | 638.17 | 21.49 | 18.50 | 21.53 | 9.33 | 21.55 |
October | 675.17 | 21.43 | 34.00 | 21.45 | 24.33 | 21.45 |
November | 680.17 | 21.48 | 17.83 | 21.46 | 17.83 | 21.45 |
December | 733.33 | 21.38 | 69.83 | 21.32 | 69.83 | 21.27 |
Annual Sum or Average | 8158.83 | 21.46 | 572.33 | 21.43 | 547.50 | 21.41 |
Minimum of Months | 630.67 | 21.28 | 4.00 | 21.15 | 4.00 | 21.07 |
Maximum of Months | 743.83 | 21.57 | 223.00 | 21.57 | 223.00 | 21.59 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 611.50 | 22.96 | 40.33 | 23.02 | 12.83 | 23.04 |
February | 428.67 | 22.99 | 90.83 | 23.16 | 30.33 | 23.20 |
March | 283.00 | 23.19 | 239.17 | 23.51 | 34.67 | 23.54 |
April | 168.83 | 23.54 | 479.00 | 23.80 | 91.50 | 23.83 |
May | 227.50 | 23.96 | 682.17 | 23.91 | 219.33 | 23.93 |
June | 210.83 | 24.00 | 705.33 | 23.95 | 210.83 | 23.96 |
July | 290.17 | 24.00 | 744.00 | 23.96 | 290.17 | 23.97 |
August | 291.50 | 24.00 | 744.00 | 23.96 | 291.50 | 23.96 |
September | 269.17 | 23.99 | 700.00 | 23.92 | 269.00 | 23.93 |
October | 226.50 | 23.43 | 475.17 | 23.74 | 112.33 | 23.77 |
November | 361.67 | 23.18 | 170.83 | 23.41 | 58.67 | 23.46 |
December | 481.83 | 23.01 | 81.17 | 23.14 | 18.67 | 23.17 |
Annual Sum or Average | 3851.17 | 23.41 | 5152.00 | 23.70 | 1639.83 | 23.74 |
Minimum of Months | 168.83 | 22.96 | 40.33 | 23.02 | 12.83 | 23.04 |
Maximum of Months | 611.50 | 24.00 | 744.00 | 23.96 | 291.50 | 23.97 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 473.33 | 23.07 | 88.83 | 23.21 | 8.83 | 23.22 |
February | 321.83 | 23.13 | 160.00 | 23.40 | 27.17 | 23.43 |
March | 158.83 | 23.26 | 322.33 | 23.70 | 23.83 | 23.71 |
April | 117.50 | 23.71 | 569.17 | 23.89 | 80.33 | 23.90 |
May | 200.33 | 23.98 | 711.17 | 23.94 | 197.50 | 23.95 |
June | 196.17 | 24.00 | 715.17 | 23.97 | 196.17 | 23.97 |
July | 268.50 | 24.00 | 744.00 | 23.97 | 268.50 | 23.98 |
August | 269.50 | 24.00 | 744.00 | 23.97 | 269.50 | 23.98 |
September | 243.83 | 24.00 | 717.83 | 23.94 | 243.83 | 23.95 |
October | 155.33 | 23.64 | 578.00 | 23.85 | 102.33 | 23.87 |
November | 219.17 | 23.28 | 256.00 | 23.61 | 47.50 | 23.65 |
December | 339.83 | 23.10 | 146.67 | 23.35 | 9.17 | 23.36 |
Annual Sum or Average | 2964.17 | 23.53 | 5753.17 | 23.80 | 1474.67 | 23.83 |
Minimum of Months | 117.50 | 23.07 | 88.83 | 23.21 | 8.83 | 23.22 |
Maximum of Months | 473.33 | 24.00 | 744.00 | 23.97 | 269.50 | 23.98 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 544.00 | 23.63 | 598.17 | 23.79 | 447.67 | 23.84 |
February | 481.50 | 23.77 | 571.17 | 23.83 | 428.67 | 23.88 |
March | 522.83 | 23.96 | 670.50 | 23.91 | 513.83 | 23.94 |
April | 524.67 | 24.02 | 697.83 | 23.93 | 521.50 | 23.96 |
May | 568.67 | 24.00 | 738.50 | 23.93 | 568.67 | 23.95 |
June | 565.33 | 24.00 | 720.00 | 23.95 | 565.33 | 23.96 |
July | 599.00 | 23.99 | 744.00 | 23.95 | 599.00 | 23.96 |
August | 599.83 | 23.99 | 744.00 | 23.96 | 599.83 | 23.97 |
September | 558.00 | 23.99 | 720.00 | 23.93 | 558.00 | 23.95 |
October | 541.00 | 23.99 | 730.17 | 23.88 | 539.67 | 23.91 |
November | 512.50 | 23.92 | 640.00 | 23.89 | 492.67 | 23.92 |
December | 535.00 | 23.79 | 622.83 | 23.84 | 479.50 | 23.89 |
Annual Sum or Average | 6552.33 | 23.92 | 8197.17 | 23.90 | 6314.33 | 23.93 |
Minimum of Months | 481.50 | 23.63 | 571.17 | 23.79 | 428.67 | 23.84 |
Maximum of Months | 599.83 | 24.02 | 744.00 | 23.96 | 599.83 | 23.97 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.02 | 263.67 | 21.01 | 263.67 | 21.01 |
February | 672.00 | 21.19 | 182.33 | 21.15 | 182.33 | 21.12 |
March | 744.00 | 21.65 | 0.00 | 21.65 | 0.00 | 21.65 |
April | 704.33 | 22.25 | 0.00 | 22.25 | 0.00 | 22.25 |
May | 559.83 | 22.71 | 35.00 | 22.77 | 0.00 | 22.77 |
June | 150.50 | 23.03 | 386.83 | 23.61 | 0.00 | 23.61 |
July | 73.33 | 22.88 | 523.33 | 23.75 | 0.00 | 23.75 |
August | 3.50 | 23.14 | 610.83 | 23.87 | 0.00 | 23.87 |
September | 439.83 | 22.82 | 102.67 | 23.01 | 0.00 | 23.01 |
October | 735.17 | 22.01 | 0.83 | 22.01 | 0.00 | 22.01 |
November | 720.00 | 21.37 | 2.67 | 21.37 | 2.67 | 21.37 |
December | 744.00 | 21.08 | 93.33 | 21.07 | 93.33 | 21.06 |
Annual Sum or Average | 6290.50 | 21.76 | 2201.50 | 22.12 | 542.00 | 22.05 |
Minimum of Months | 3.50 | 21.02 | 0.00 | 21.01 | 0.00 | 21.01 |
Maximum of Months | 744.00 | 23.14 | 610.83 | 23.87 | 263.67 | 23.87 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.49144 | 30.69060 | -0.1094 | 5.43340 |
February | 672.00000 | 21.89196 | 33.52441 | -0.2430 | 6.48703 |
March | 744.00000 | 21.32864 | 40.38911 | -0.3457 | 7.74831 |
April | 720.00000 | 21.10791 | 51.44912 | -0.3471 | 7.69956 |
May | 744.00000 | 21.27958 | 61.94205 | -1.4160 | 46.41769 |
June | 720.00000 | 22.01215 | 60.77835 | -1.1492 | 33.01832 |
July | 744.00000 | 22.59074 | 62.44542 | -0.9258 | 23.31864 |
August | 744.00000 | 23.23368 | 60.29483 | -0.7034 | 15.64636 |
September | 720.00000 | 23.78751 | 57.29661 | -0.5163 | 10.73018 |
October | 744.00000 | 23.88654 | 46.80297 | 0.36849 | 7.95222 |
November | 720.00000 | 23.90854 | 36.10266 | 0.30029 | 7.06402 |
December | 744.00000 | 23.63470 | 32.34251 | 0.19558 | 5.99254 |
Annual Sum or Average | 8760.00000 | 22.60072 | 47.91676 | -0.4088 | 14.86242 |
Minimum of Months | 672.00000 | 21.10791 | 30.69060 | -1.4160 | 5.43340 |
Maximum of Months | 744.00000 | 23.90854 | 62.44542 | 0.36849 | 46.41769 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.23640 | 31.25635 | -0.4467 | 10.02597 |
February | 672.00000 | 21.43964 | 33.02497 | -0.3498 | 8.90698 |
March | 744.00000 | 21.89155 | 37.86246 | -0.1388 | 6.99083 |
April | 720.00000 | 22.13274 | 47.45463 | -0.0012 | 6.43302 |
May | 744.00000 | 22.50975 | 56.66644 | -0.8459 | 21.58388 |
June | 720.00000 | 23.17711 | 55.82364 | -0.5883 | 13.52206 |
July | 744.00000 | 23.36990 | 58.85104 | -0.4862 | 10.94917 |
August | 744.00000 | 23.60454 | 58.03648 | -0.3921 | 8.78969 |
September | 720.00000 | 22.97183 | 58.90659 | -0.6454 | 15.78834 |
October | 744.00000 | 22.30320 | 49.91335 | 0.05761 | 7.01314 |
November | 720.00000 | 21.73783 | 39.45171 | -0.1775 | 7.19376 |
December | 744.00000 | 21.42437 | 34.76353 | -0.3376 | 8.63668 |
Annual Sum or Average | 8760.00000 | 22.32171 | 46.90859 | -0.3629 | 10.49639 |
Minimum of Months | 672.00000 | 21.23640 | 31.25635 | -0.8459 | 6.43302 |
Maximum of Months | 744.00000 | 23.60454 | 58.90659 | 0.05761 | 21.58388 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.63410 | 32.21384 | -0.2933 | 7.27591 |
February | 672.00000 | 21.95662 | 33.66441 | -0.1961 | 6.65173 |
March | 744.00000 | 22.64569 | 38.12206 | 0.01935 | 5.73317 |
April | 720.00000 | 22.94705 | 47.08911 | 0.15951 | 6.18312 |
May | 744.00000 | 23.21260 | 56.19954 | -0.6752 | 15.31525 |
June | 720.00000 | 23.54364 | 56.23217 | -0.5403 | 11.67641 |
July | 744.00000 | 23.61359 | 59.35059 | -0.4874 | 10.37967 |
August | 744.00000 | 23.71301 | 58.95367 | -0.4496 | 9.49855 |
September | 720.00000 | 23.45033 | 58.83770 | -0.5626 | 12.19433 |
October | 744.00000 | 22.96905 | 49.78492 | 0.18303 | 6.33195 |
November | 720.00000 | 22.54222 | 39.39873 | -0.0020 | 5.59748 |
December | 744.00000 | 22.01262 | 35.27950 | -0.1703 | 6.21897 |
Annual Sum or Average | 8760.00000 | 22.85782 | 47.16812 | -0.2519 | 8.60040 |
Minimum of Months | 672.00000 | 21.63410 | 32.21384 | -0.6752 | 5.59748 |
Maximum of Months | 744.00000 | 23.71301 | 59.35059 | 0.18303 | 15.31525 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.66879 | 26.24414 | 0.50767 | 13.49362 |
February | 672.00000 | 22.72423 | 27.96031 | 0.55671 | 14.65939 |
March | 744.00000 | 22.80472 | 33.31084 | 0.65316 | 17.03951 |
April | 720.00000 | 22.83633 | 42.95218 | 0.74414 | 19.55675 |
May | 744.00000 | 22.82715 | 52.91779 | 0.10231 | 10.98927 |
June | 720.00000 | 22.83592 | 54.04593 | 0.14537 | 11.14153 |
July | 744.00000 | 22.84230 | 57.49308 | 0.17803 | 11.13263 |
August | 744.00000 | 22.84227 | 57.46741 | 0.18378 | 11.28364 |
September | 720.00000 | 22.84573 | 56.35493 | 0.13561 | 10.96111 |
October | 744.00000 | 22.82392 | 45.68674 | 0.75045 | 19.65453 |
November | 720.00000 | 22.80863 | 34.44033 | 0.64756 | 16.74861 |
December | 744.00000 | 22.73603 | 29.62419 | 0.56782 | 14.77226 |
Annual Sum or Average | 8760.00000 | 22.79994 | 43.29249 | 0.43016 | 14.27954 |
Minimum of Months | 672.00000 | 22.66879 | 26.24414 | 0.10231 | 10.96111 |
Maximum of Months | 744.00000 | 22.84573 | 57.49308 | 0.75045 | 19.65453 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.09637 | 35.80535 | -0.1511 | 6.70019 |
February | 672.00000 | 22.40006 | 37.26457 | -0.0377 | 6.61625 |
March | 744.00000 | 22.98186 | 41.78753 | 0.18602 | 6.96891 |
April | 720.00000 | 23.09020 | 50.94520 | 0.28804 | 7.74737 |
May | 744.00000 | 23.25538 | 60.12444 | -0.5222 | 11.73950 |
June | 720.00000 | 23.46860 | 60.27069 | -0.4051 | 9.17564 |
July | 744.00000 | 23.55892 | 63.25721 | -0.3341 | 7.88278 |
August | 744.00000 | 23.70141 | 62.55108 | -0.2666 | 6.91108 |
September | 720.00000 | 23.50313 | 62.46440 | -0.3835 | 9.19190 |
October | 744.00000 | 23.24306 | 53.14900 | 0.35024 | 8.82943 |
November | 720.00000 | 22.92933 | 42.91216 | 0.17409 | 6.86133 |
December | 744.00000 | 22.44592 | 38.89971 | -0.0118 | 6.33081 |
Annual Sum or Average | 8760.00000 | 23.05948 | 50.86023 | -0.0934 | 7.91996 |
Minimum of Months | 672.00000 | 22.09637 | 35.80535 | -0.5222 | 6.33081 |
Maximum of Months | 744.00000 | 23.70141 | 63.25721 | 0.35024 | 11.73950 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.29762 | 34.39714 | -0.1076 | 5.93897 |
February | 672.00000 | 22.57931 | 35.83347 | -0.0166 | 5.97450 |
March | 744.00000 | 23.11178 | 40.41710 | 0.16748 | 6.31649 |
April | 720.00000 | 23.27755 | 49.34851 | 0.27835 | 7.26176 |
May | 744.00000 | 23.42661 | 58.42849 | -0.5477 | 12.03128 |
June | 720.00000 | 23.58273 | 58.70711 | -0.4646 | 10.06289 |
July | 744.00000 | 23.63485 | 61.79677 | -0.4154 | 8.99199 |
August | 744.00000 | 23.70106 | 61.41080 | -0.3863 | 8.39310 |
September | 720.00000 | 23.60150 | 60.98652 | -0.4502 | 9.70342 |
October | 744.00000 | 23.36784 | 51.72007 | 0.32077 | 7.68770 |
November | 720.00000 | 23.11994 | 41.44317 | 0.17348 | 6.27607 |
December | 744.00000 | 22.68561 | 37.36210 | 0.02145 | 5.70690 |
Annual Sum or Average | 8760.00000 | 23.20180 | 49.39563 | -0.1198 | 7.87252 |
Minimum of Months | 672.00000 | 22.29762 | 34.39714 | -0.5477 | 5.70690 |
Maximum of Months | 744.00000 | 23.70106 | 61.79677 | 0.32077 | 12.03128 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.94215 | 45.66014 | -0.5220 | 11.29387 |
February | 672.00000 | 21.11115 | 46.14165 | -0.4348 | 9.89750 |
March | 744.00000 | 21.49589 | 46.94897 | -0.2457 | 7.15616 |
April | 720.00000 | 21.62417 | 53.15496 | -0.1309 | 6.30008 |
May | 744.00000 | 21.69301 | 55.58249 | -1.1613 | 34.67396 |
June | 720.00000 | 21.73181 | 53.14443 | -1.1019 | 32.02046 |
July | 744.00000 | 21.73708 | 54.34167 | -1.0755 | 30.84931 |
August | 744.00000 | 21.74397 | 53.35610 | -1.0662 | 30.47101 |
September | 720.00000 | 21.69763 | 56.31395 | -1.1391 | 33.69632 |
October | 744.00000 | 21.54591 | 56.95922 | -0.1525 | 6.35558 |
November | 720.00000 | 21.41074 | 49.98658 | -0.2892 | 7.60033 |
December | 744.00000 | 21.12987 | 48.18339 | -0.4306 | 9.47287 |
Annual Sum or Average | 8760.00000 | 21.49032 | 51.67659 | -0.6473 | 18.36740 |
Minimum of Months | 672.00000 | 20.94215 | 45.66014 | -1.1613 | 6.30008 |
Maximum of Months | 744.00000 | 21.74397 | 56.95922 | -0.1309 | 34.67396 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.68550 | 46.31264 | -0.6078 | 13.33330 |
February | 672.00000 | 20.97647 | 46.49026 | -0.4949 | 11.22607 |
March | 744.00000 | 21.59013 | 47.15401 | -0.2535 | 7.40768 |
April | 720.00000 | 21.99777 | 52.99585 | -0.0680 | 6.51058 |
May | 744.00000 | 22.21506 | 55.80865 | -1.0134 | 28.82908 |
June | 720.00000 | 22.12111 | 53.58368 | -0.9859 | 27.65184 |
July | 744.00000 | 22.11156 | 55.25953 | -0.9621 | 26.63550 |
August | 744.00000 | 22.02226 | 54.38510 | -0.9919 | 27.67879 |
September | 720.00000 | 22.11406 | 57.43723 | -1.0325 | 29.37684 |
October | 744.00000 | 21.74378 | 57.81272 | -0.1368 | 6.57312 |
November | 720.00000 | 21.28098 | 50.77933 | -0.3514 | 8.39437 |
December | 744.00000 | 20.85650 | 49.04793 | -0.5210 | 11.22044 |
Annual Sum or Average | 8760.00000 | 21.64583 | 52.28715 | -0.6194 | 17.10782 |
Minimum of Months | 672.00000 | 20.68550 | 46.31264 | -1.0325 | 6.51058 |
Maximum of Months | 744.00000 | 22.21506 | 57.81272 | -0.0680 | 29.37684 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.98443 | 41.65026 | -0.5024 | 10.61627 |
February | 672.00000 | 21.17530 | 41.84532 | -0.4315 | 9.40187 |
March | 744.00000 | 21.50566 | 43.73582 | -0.2970 | 7.35963 |
April | 720.00000 | 21.84365 | 50.56789 | -0.1516 | 6.29411 |
May | 744.00000 | 22.05624 | 55.48242 | -1.1407 | 33.54194 |
June | 720.00000 | 22.01019 | 54.82073 | -1.1261 | 33.05284 |
July | 744.00000 | 22.02582 | 57.05448 | -1.0991 | 31.95796 |
August | 744.00000 | 21.93715 | 56.35262 | -1.1364 | 33.49043 |
September | 720.00000 | 22.01723 | 57.38241 | -1.1425 | 33.65507 |
October | 744.00000 | 21.66514 | 54.66474 | -0.1839 | 6.25823 |
November | 720.00000 | 21.36912 | 46.27714 | -0.3329 | 7.77779 |
December | 744.00000 | 21.12332 | 44.38651 | -0.4345 | 9.25440 |
Annual Sum or Average | 8760.00000 | 21.64478 | 50.40067 | -0.6665 | 18.61231 |
Minimum of Months | 672.00000 | 20.98443 | 41.65026 | -1.1425 | 6.25823 |
Maximum of Months | 744.00000 | 22.05624 | 57.38241 | -0.1516 | 33.65507 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.97884 | 45.54986 | -0.5145 | 11.12441 |
February | 672.00000 | 21.16499 | 45.97167 | -0.4196 | 9.65961 |
March | 744.00000 | 21.55737 | 46.62668 | -0.2369 | 7.13878 |
April | 720.00000 | 21.68191 | 52.64435 | -0.1203 | 6.30631 |
May | 744.00000 | 21.72497 | 54.92992 | -1.1469 | 34.11636 |
June | 720.00000 | 21.75009 | 52.80557 | -1.0895 | 31.57666 |
July | 744.00000 | 21.74843 | 53.83121 | -1.0646 | 30.48161 |
August | 744.00000 | 21.75210 | 53.06466 | -1.0619 | 30.36749 |
September | 720.00000 | 21.71202 | 55.89551 | -1.1337 | 33.52471 |
October | 744.00000 | 21.58166 | 56.46982 | -0.1467 | 6.37510 |
November | 720.00000 | 21.45515 | 49.76853 | -0.2812 | 7.48563 |
December | 744.00000 | 21.16808 | 48.04723 | -0.4214 | 9.27845 |
Annual Sum or Average | 8760.00000 | 21.52452 | 51.32802 | -0.6380 | 18.17155 |
Minimum of Months | 672.00000 | 20.97884 | 45.54986 | -1.1469 | 6.30631 |
Maximum of Months | 744.00000 | 21.75210 | 56.46982 | -0.1203 | 34.11636 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.70813 | 46.25612 | -0.6031 | 13.18763 |
February | 672.00000 | 21.00822 | 46.40103 | -0.4836 | 10.93242 |
March | 744.00000 | 21.58332 | 47.04323 | -0.2585 | 7.28125 |
April | 720.00000 | 22.00665 | 52.63596 | -0.0672 | 6.32019 |
May | 744.00000 | 22.25910 | 55.20151 | -0.9957 | 28.28840 |
June | 720.00000 | 22.21465 | 53.10618 | -0.9525 | 27.08731 |
July | 744.00000 | 22.20598 | 54.51573 | -0.9278 | 26.24830 |
August | 744.00000 | 22.07491 | 54.05590 | -0.9745 | 27.52674 |
September | 720.00000 | 22.16514 | 56.84086 | -1.0173 | 29.07449 |
October | 744.00000 | 21.73860 | 57.14574 | -0.1412 | 6.43600 |
November | 720.00000 | 21.25526 | 50.74138 | -0.3577 | 8.30170 |
December | 744.00000 | 20.87183 | 48.96686 | -0.5162 | 11.04104 |
Annual Sum or Average | 8760.00000 | 21.67720 | 51.93890 | -0.6091 | 16.84906 |
Minimum of Months | 672.00000 | 20.70813 | 46.25612 | -1.0173 | 6.32019 |
Maximum of Months | 744.00000 | 22.25910 | 57.14574 | -0.0672 | 29.07449 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.80961 | 46.98954 | -0.5868 | 12.88526 |
February | 672.00000 | 20.99639 | 47.47870 | -0.4874 | 11.14843 |
March | 744.00000 | 21.42740 | 48.09559 | -0.2756 | 7.67262 |
April | 720.00000 | 21.58956 | 54.55298 | -0.1422 | 6.55547 |
May | 744.00000 | 21.68092 | 56.82081 | -1.1600 | 34.81563 |
June | 720.00000 | 21.72788 | 53.88543 | -1.0949 | 31.91331 |
July | 744.00000 | 21.73375 | 55.29793 | -1.0651 | 30.59704 |
August | 744.00000 | 21.74266 | 54.10407 | -1.0560 | 30.22159 |
September | 720.00000 | 21.67980 | 57.96256 | -1.1445 | 34.10725 |
October | 744.00000 | 21.48743 | 58.93083 | -0.1753 | 6.68145 |
November | 720.00000 | 21.32864 | 51.49260 | -0.3274 | 8.27783 |
December | 744.00000 | 20.99748 | 49.82147 | -0.4876 | 10.70516 |
Annual Sum or Average | 8760.00000 | 21.43543 | 52.98104 | -0.6683 | 18.84579 |
Minimum of Months | 672.00000 | 20.80961 | 46.98954 | -1.1600 | 6.55547 |
Maximum of Months | 744.00000 | 21.74266 | 58.93083 | -0.1422 | 34.81563 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.59109 | 47.62308 | -0.6666 | 15.00338 |
February | 672.00000 | 20.88543 | 47.82897 | -0.5442 | 12.50073 |
March | 744.00000 | 21.50133 | 48.32913 | -0.2883 | 8.04002 |
April | 720.00000 | 21.97343 | 54.19015 | -0.0758 | 6.86051 |
May | 744.00000 | 22.19678 | 56.71618 | -1.0107 | 29.09712 |
June | 720.00000 | 22.09106 | 54.17001 | -0.9845 | 27.74025 |
July | 744.00000 | 22.07631 | 56.06967 | -0.9591 | 26.59701 |
August | 744.00000 | 21.99485 | 55.06687 | -0.9881 | 27.60270 |
September | 720.00000 | 22.05687 | 58.97580 | -1.0475 | 30.18832 |
October | 744.00000 | 21.65021 | 59.88615 | -0.1672 | 7.01257 |
November | 720.00000 | 21.16382 | 52.42194 | -0.3992 | 9.32204 |
December | 744.00000 | 20.72261 | 50.74145 | -0.5803 | 12.72903 |
Annual Sum or Average | 8760.00000 | 21.57829 | 53.53248 | -0.6436 | 17.75861 |
Minimum of Months | 672.00000 | 20.59109 | 47.62308 | -1.0475 | 6.86051 |
Maximum of Months | 744.00000 | 22.19678 | 59.88615 | -0.0758 | 30.18832 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.27902 | 45.33893 | -0.4066 | 9.71602 |
February | 672.00000 | 21.36867 | 45.63349 | -0.3482 | 8.73995 |
March | 744.00000 | 21.56855 | 46.23149 | -0.2287 | 7.18736 |
April | 720.00000 | 21.63682 | 53.02722 | -0.1510 | 6.52464 |
May | 744.00000 | 21.68132 | 56.57568 | -1.2062 | 36.84013 |
June | 720.00000 | 21.72345 | 54.49310 | -1.1571 | 34.54407 |
July | 744.00000 | 21.73091 | 55.77058 | -1.1262 | 33.11017 |
August | 744.00000 | 21.74385 | 54.51315 | -1.1056 | 32.28353 |
September | 720.00000 | 21.69805 | 56.73379 | -1.1609 | 34.84767 |
October | 744.00000 | 21.60507 | 55.84773 | -0.1343 | 6.43600 |
November | 720.00000 | 21.58031 | 48.80999 | -0.2206 | 7.16461 |
December | 744.00000 | 21.40745 | 47.45926 | -0.3257 | 8.30357 |
Annual Sum or Average | 8760.00000 | 21.58626 | 51.73562 | -0.6328 | 18.86939 |
Minimum of Months | 672.00000 | 21.27902 | 45.33893 | -1.2062 | 6.43600 |
Maximum of Months | 744.00000 | 21.74385 | 56.73379 | -0.1343 | 36.84013 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.12848 | 34.86758 | 0.09922 | 6.22160 |
February | 672.00000 | 23.31887 | 36.04635 | 0.18049 | 6.77504 |
March | 744.00000 | 23.60825 | 40.39808 | 0.32715 | 7.84851 |
April | 720.00000 | 23.76901 | 48.83405 | 0.45545 | 9.79949 |
May | 744.00000 | 23.86829 | 57.48080 | -0.2903 | 7.05476 |
June | 720.00000 | 23.93188 | 57.98849 | -0.2209 | 6.20416 |
July | 744.00000 | 23.94360 | 61.15178 | -0.1827 | 5.76974 |
August | 744.00000 | 23.93964 | 61.08870 | -0.1831 | 5.76710 |
September | 720.00000 | 23.86697 | 60.71994 | -0.2656 | 6.69920 |
October | 744.00000 | 23.68224 | 51.79062 | 0.43725 | 9.46715 |
November | 720.00000 | 23.51236 | 41.80932 | 0.29233 | 7.50140 |
December | 744.00000 | 23.32538 | 37.78307 | 0.18767 | 6.60801 |
Annual Sum or Average | 8760.00000 | 23.65947 | 49.23625 | 0.06888 | 7.14156 |
Minimum of Months | 672.00000 | 23.12848 | 34.86758 | -0.2903 | 5.76710 |
Maximum of Months | 744.00000 | 23.94360 | 61.15178 | 0.45545 | 9.79949 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.37085 | 33.88432 | 0.19654 | 6.62481 |
February | 672.00000 | 23.52210 | 35.06532 | 0.26762 | 7.37778 |
March | 744.00000 | 23.75179 | 39.45894 | 0.39750 | 8.76923 |
April | 720.00000 | 23.86041 | 47.99816 | 0.51049 | 10.81677 |
May | 744.00000 | 23.92377 | 56.77069 | -0.2276 | 6.30023 |
June | 720.00000 | 23.96024 | 57.45263 | -0.1730 | 5.77426 |
July | 744.00000 | 23.96679 | 60.64284 | -0.1377 | 5.44462 |
August | 744.00000 | 23.96291 | 60.59609 | -0.1392 | 5.44941 |
September | 720.00000 | 23.91830 | 60.04456 | -0.2070 | 6.05063 |
October | 744.00000 | 23.79665 | 50.85744 | 0.49835 | 10.54906 |
November | 720.00000 | 23.68220 | 40.79839 | 0.37019 | 8.42190 |
December | 744.00000 | 23.53131 | 36.74188 | 0.27583 | 7.27079 |
Annual Sum or Average | 8760.00000 | 23.77173 | 48.43331 | 0.13505 | 7.40038 |
Minimum of Months | 672.00000 | 23.37085 | 33.88432 | -0.2276 | 5.44462 |
Maximum of Months | 744.00000 | 23.96679 | 60.64284 | 0.51049 | 10.81677 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.58241 | 32.66759 | 0.85828 | 23.87469 |
February | 672.00000 | 23.64076 | 34.04721 | 0.91927 | 26.02679 |
March | 744.00000 | 23.74871 | 38.61838 | 1.03912 | 30.36187 |
April | 720.00000 | 23.82400 | 47.30860 | 1.15562 | 35.30881 |
May | 744.00000 | 23.86157 | 56.17264 | 0.69884 | 19.97968 |
June | 720.00000 | 23.90677 | 57.02243 | 0.76940 | 21.58508 |
July | 744.00000 | 23.91924 | 60.14260 | 0.81073 | 22.56138 |
August | 744.00000 | 23.92812 | 60.05626 | 0.81405 | 22.52479 |
September | 720.00000 | 23.87494 | 59.30669 | 0.72446 | 20.14282 |
October | 744.00000 | 23.78076 | 49.88638 | 1.13956 | 34.43590 |
November | 720.00000 | 23.70275 | 39.78875 | 1.00830 | 29.15357 |
December | 744.00000 | 23.63674 | 35.58421 | 0.92079 | 25.88314 |
Annual Sum or Average | 8760.00000 | 23.78460 | 47.62489 | 0.90465 | 25.98006 |
Minimum of Months | 672.00000 | 23.58241 | 32.66759 | 0.69884 | 19.97968 |
Maximum of Months | 744.00000 | 23.92812 | 60.14260 | 1.15562 | 35.30881 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.02086 | 30.10189 | -0.5021 | 10.45434 |
February | 672.00000 | 21.17562 | 31.94555 | -0.4376 | 9.36378 |
March | 744.00000 | 21.59386 | 36.96569 | -0.2783 | 7.21144 |
April | 720.00000 | 22.13972 | 45.80461 | -0.0850 | 5.77932 |
May | 744.00000 | 22.71128 | 54.62747 | -0.9164 | 23.14377 |
June | 720.00000 | 23.38833 | 53.87095 | -0.6779 | 15.03806 |
July | 744.00000 | 23.59364 | 56.87059 | -0.5831 | 12.31659 |
August | 744.00000 | 23.66678 | 56.67250 | -0.5582 | 11.60704 |
September | 720.00000 | 23.09206 | 57.13291 | -0.7630 | 17.55449 |
October | 744.00000 | 22.16369 | 48.88493 | -0.0596 | 5.59160 |
November | 720.00000 | 21.54173 | 38.24112 | -0.2854 | 7.20532 |
December | 744.00000 | 21.10243 | 33.81634 | -0.4351 | 9.28554 |
Annual Sum or Average | 8760.00000 | 22.27179 | 45.48516 | -0.4655 | 11.22581 |
Minimum of Months | 672.00000 | 21.02086 | 30.10189 | -0.9164 | 5.59160 |
Maximum of Months | 744.00000 | 23.66678 | 57.13291 | -0.0596 | 23.14377 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.01728 | 34.41646 | -0.4862 | 10.07052 |
February | 672.00000 | 21.21058 | 36.24342 | -0.4189 | 8.96670 |
March | 744.00000 | 21.80422 | 40.99782 | -0.2264 | 6.51800 |
April | 720.00000 | 22.40096 | 49.61036 | -0.0223 | 5.52791 |
May | 744.00000 | 22.85014 | 58.65256 | -0.8813 | 21.68142 |
June | 720.00000 | 23.42782 | 58.20726 | -0.6762 | 14.88646 |
July | 744.00000 | 23.65232 | 61.01962 | -0.5763 | 12.10892 |
August | 744.00000 | 23.71107 | 60.84784 | -0.5567 | 11.54965 |
September | 720.00000 | 23.20238 | 61.17977 | -0.7374 | 16.69396 |
October | 744.00000 | 22.27252 | 52.99761 | -0.0337 | 5.57291 |
November | 720.00000 | 21.48858 | 42.75152 | -0.2968 | 7.18532 |
December | 744.00000 | 21.09288 | 38.15133 | -0.4332 | 9.16757 |
Annual Sum or Average | 8760.00000 | 22.35042 | 49.66264 | -0.4458 | 10.84004 |
Minimum of Months | 672.00000 | 21.01728 | 34.41646 | -0.8813 | 5.52791 |
Maximum of Months | 744.00000 | 23.71107 | 61.17977 | -0.0223 | 21.68142 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.02000 | 31.30653 | -0.4954 | 10.31833 |
February | 672.00000 | 21.18603 | 33.12311 | -0.4227 | 9.14418 |
March | 744.00000 | 21.64644 | 38.02709 | -0.2446 | 6.97608 |
April | 720.00000 | 22.27988 | 46.65422 | -0.0248 | 5.93027 |
May | 744.00000 | 22.90283 | 55.14571 | -0.8101 | 19.60116 |
June | 720.00000 | 23.56331 | 54.32240 | -0.5707 | 12.41774 |
July | 744.00000 | 23.68750 | 57.38304 | -0.4988 | 10.52139 |
August | 744.00000 | 23.78701 | 57.05518 | -0.4648 | 9.64489 |
September | 720.00000 | 23.10559 | 58.12355 | -0.7165 | 16.43749 |
October | 744.00000 | 22.02816 | 50.31741 | -0.0692 | 5.88124 |
November | 720.00000 | 21.37002 | 39.80301 | -0.3116 | 7.54881 |
December | 744.00000 | 21.07955 | 35.03379 | -0.4359 | 9.28039 |
Annual Sum or Average | 8760.00000 | 22.31087 | 46.42979 | -0.4223 | 10.31505 |
Minimum of Months | 672.00000 | 21.02000 | 31.30653 | -0.8101 | 5.88124 |
Maximum of Months | 744.00000 | 23.78701 | 58.12355 | -0.0248 | 19.60116 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.04834 | 29.59518 | -0.4898 | 10.22291 |
February | 672.00000 | 21.25220 | 31.32658 | -0.4166 | 9.05789 |
March | 744.00000 | 21.73185 | 36.22565 | -0.2466 | 6.88986 |
April | 720.00000 | 22.28994 | 44.95745 | -0.0500 | 5.69532 |
May | 744.00000 | 22.85242 | 53.71051 | -0.8675 | 21.36838 |
June | 720.00000 | 23.50987 | 52.98747 | -0.6332 | 13.82403 |
July | 744.00000 | 23.67998 | 56.04362 | -0.5484 | 11.49222 |
August | 744.00000 | 23.74722 | 55.85023 | -0.5254 | 10.87803 |
September | 720.00000 | 23.24188 | 56.13964 | -0.7106 | 15.95774 |
October | 744.00000 | 22.32496 | 47.96904 | -0.0224 | 5.52411 |
November | 720.00000 | 21.68584 | 37.48311 | -0.2521 | 6.86542 |
December | 744.00000 | 21.17587 | 33.21697 | -0.4152 | 8.97296 |
Annual Sum or Average | 8760.00000 | 22.38430 | 44.69896 | -0.4318 | 10.57452 |
Minimum of Months | 672.00000 | 21.04834 | 29.59518 | -0.8675 | 5.52411 |
Maximum of Months | 744.00000 | 23.74722 | 56.13964 | -0.0224 | 21.36838 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.677762E+10 | 65590.11 | 31-JAN-16:01 | 386.50 | 0.206156E+11 | 0.00 | 0.273932E+11 | 1.64 | 3.19 | 21-JAN-09:30 | 0.00 | 0.00 |
February | 0.188373E+11 | 97273.98 | 26-FEB-16:01 | 446.11 | 0.546512E+11 | 0.00 | 0.734884E+11 | 2.06 | 3.41 | 27-FEB-16:03 | 0.00 | 0.00 |
March | 0.527011E+11 | 126558.27 | 30-MAR-15:05 | 705.63 | 0.154313E+12 | 0.00 | 0.207014E+12 | 2.90 | 3.56 | 28-MAR-18:03 | 0.00 | 0.00 |
April | 0.971725E+11 | 124766.19 | 17-APR-15:05 | 712.88 | 0.285366E+12 | 0.00 | 0.382539E+12 | 2.98 | 3.77 | 22-APR-15:03 | 0.00 | 0.00 |
May | 0.169021E+12 | 150041.24 | 30-MAY-18:03 | 744.00 | 0.519657E+12 | 0.00 | 0.688678E+12 | 3.04 | 4.13 | 30-MAY-21:51 | 0.00 | 0.00 |
June | 0.251457E+12 | 176692.06 | 28-JUN-18:03 | 720.00 | 0.817235E+12 | 0.00 | 0.106869E+13 | 3.22 | 4.25 | 22-JUN-21:52 | 0.00 | 0.00 |
July | 0.310718E+12 | 194092.19 | 06-JUL-18:03 | 744.00 | 0.103980E+13 | 0.00 | 0.135052E+13 | 3.36 | 4.23 | 27-JUL-21:53 | 0.00 | 0.00 |
August | 0.327933E+12 | 196796.57 | 18-AUG-18:05 | 744.00 | 0.111504E+13 | 0.00 | 0.144297E+13 | 3.41 | 4.20 | 07-AUG-21:52 | 0.00 | 0.00 |
September | 0.212480E+12 | 169944.91 | 07-SEP-18:03 | 720.00 | 0.701424E+12 | 0.00 | 0.913904E+12 | 3.23 | 4.16 | 27-SEP-21:53 | 0.00 | 0.00 |
October | 0.948781E+11 | 160515.70 | 18-OCT-21:53 | 709.91 | 0.300868E+12 | 0.00 | 0.395746E+12 | 2.98 | 4.15 | 18-OCT-21:53 | 0.00 | 0.00 |
November | 0.406270E+11 | 103908.63 | 05-NOV-15:03 | 662.71 | 0.120176E+12 | 0.00 | 0.160803E+12 | 2.84 | 3.74 | 27-NOV-22:53 | 0.00 | 0.00 |
December | 0.132582E+11 | 84824.38 | 12-DEC-16:03 | 524.37 | 0.398273E+11 | 0.00 | 0.530855E+11 | 2.22 | 3.47 | 13-DEC-16:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.159586E+13 | 7820.11 | 0.516897E+13 | 0.00 | 0.676484E+13 | 2.83 | 0.00 | 0.00 | ||||
Minimum of Months | 0.677762E+10 | 65590.11 | 386.50 | 0.206156E+11 | 0.00 | 0.273932E+11 | 1.64 | 3.19 | 0.00 | 0.00 | ||
Maximum of Months | 0.327933E+12 | 196796.57 | 744.00 | 0.111504E+13 | 0.00 | 0.144297E+13 | 3.41 | 4.25 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.989639E+11 | 0.00 | 731.29 | 177504.44 | 27-JAN-09:01 | 0.00 | 48.67 | 79.88 | 0.27 | 0.00 | 0.09 | 0.44 | 27-JAN-09:01 |
February | 0.722760E+11 | 0.00 | 582.24 | 211233.18 | 12-FEB-09:02 | 0.00 | 45.08 | 74.69 | 0.21 | 0.00 | 0.07 | 0.52 | 12-FEB-09:02 |
March | 0.531451E+11 | 0.00 | 559.01 | 136598.77 | 16-MAR-08:07 | 0.00 | 36.52 | 68.37 | 0.11 | 0.00 | 0.05 | 0.33 | 16-MAR-08:07 |
April | 0.245178E+11 | 0.00 | 524.04 | 109062.15 | 26-APR-08:05 | 0.00 | 35.70 | 67.77 | 0.05 | 0.00 | 0.02 | 0.27 | 26-APR-08:05 |
May | 0.771040E+10 | 0.00 | 319.61 | 87377.97 | 11-MAY-06:10 | 0.00 | 29.34 | 50.82 | 0.01 | 0.00 | 0.01 | 0.21 | 11-MAY-06:10 |
June | 0.134394E+10 | 0.00 | 38.03 | 46101.46 | 10-JUN-05:00 | 0.00 | 31.69 | 34.39 | 0.00 | 0.00 | 0.00 | 0.11 | 10-JUN-05:00 |
July | 35082190.34 | 0.00 | 16.61 | 17965.08 | 28-JUL-15:07 | 0.00 | 40.34 | 41.19 | 0.00 | 0.00 | 0.00 | 0.04 | 28-JUL-15:07 |
August | 18761857.58 | 0.00 | 9.67 | 7989.35 | 10-AUG-08:05 | 0.00 | 46.56 | 46.99 | 0.00 | 0.00 | 0.00 | 0.02 | 10-AUG-08:05 |
September | 0.122223E+10 | 0.00 | 68.28 | 38016.61 | 29-SEP-08:04 | 0.00 | 44.56 | 48.00 | 0.00 | 0.00 | 0.00 | 0.09 | 29-SEP-08:04 |
October | 0.472377E+11 | 0.00 | 361.78 | 156188.43 | 31-OCT-08:62 | 0.00 | 36.55 | 57.50 | 0.09 | 0.00 | 0.04 | 0.38 | 31-OCT-08:62 |
November | 0.493266E+11 | 0.00 | 520.69 | 155016.44 | 21-NOV-16:02 | 0.00 | 45.39 | 70.14 | 0.12 | 0.00 | 0.05 | 0.38 | 21-NOV-16:02 |
December | 0.798560E+11 | 0.00 | 707.66 | 173371.93 | 22-DEC-16:01 | 0.00 | 47.59 | 78.49 | 0.22 | 0.00 | 0.07 | 0.43 | 22-DEC-16:01 |
Annual Sum or Average | 0.435654E+12 | 0.00 | 4438.89 | 0.00 | 40.64 | 59.78 | 0.09 | 0.00 | 0.03 | ||||
Minimum of Months | 18761857.58 | 0.00 | 9.67 | 7989.35 | 0.00 | 29.34 | 34.39 | 0.00 | 0.00 | 0.00 | 0.02 | ||
Maximum of Months | 0.989639E+11 | 0.00 | 731.29 | 211233.18 | 0.00 | 48.67 | 79.88 | 0.27 | 0.00 | 0.09 | 0.52 |
Report: DXReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.507526E+11 | 0.00 | 439.95 | 0.507526E+11 | 0.00 | 0.00 | 1.00 | 01-JAN-06:20 | 0.00 | 01-JAN-00:05 | 39958.33 | 31-JAN-11:13 | 39958.33 | 31-JAN-18:30 | 0.00 | 29-JAN-02:07 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 0.475583E+11 | 0.00 | 382.57 | 0.475583E+11 | 0.00 | 0.00 | 1.00 | 01-FEB-00:20 | 0.00 | 01-FEB-00:03 | 44871.57 | 01-FEB-09:01 | 44871.57 | 01-FEB-10:05 | 0.00 | 03-FEB-10:05 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 0.530043E+11 | 0.00 | 397.69 | 0.530019E+11 | 2457513.42 | 0.00 | 1.00 | 01-MAR-00:07 | 0.00 | 01-MAR-00:03 | 56659.15 | 31-MAR-23:07 | 53351.89 | 31-MAR-23:07 | 3307.26 | 31-MAR-23:07 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 0.487337E+11 | 0.00 | 363.82 | 0.461104E+11 | 0.262334E+10 | 0.00 | 1.00 | 01-APR-05:08 | 0.00 | 01-APR-00:20 | 56628.47 | 01-APR-05:08 | 53344.62 | 01-APR-10:15 | 8593.79 | 30-APR-23:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.469020E+11 | 0.00 | 355.72 | 0.377156E+11 | 0.918644E+10 | 0.00 | 1.00 | 01-MAY-05:15 | 0.00 | 01-MAY-00:05 | 60883.65 | 01-MAY-07:35 | 48754.55 | 01-MAY-08:55 | 12146.94 | 01-MAY-17:05 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.420110E+11 | 0.00 | 341.82 | 0.316224E+11 | 0.103887E+11 | 0.00 | 1.00 | 01-JUN-05:15 | 0.00 | 01-JUN-00:05 | 64073.14 | 01-JUN-17:15 | 48025.28 | 04-JUN-08:53 | 16071.16 | 01-JUN-17:15 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.413087E+11 | 0.00 | 349.19 | 0.256379E+11 | 0.156708E+11 | 0.00 | 1.00 | 01-JUL-05:17 | 0.00 | 01-JUL-00:10 | 65841.04 | 01-JUL-07:50 | 40794.10 | 04-JUL-07:55 | 25055.35 | 01-JUL-05:17 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.413047E+11 | 0.00 | 345.72 | 0.244046E+11 | 0.169001E+11 | 0.00 | 1.00 | 01-AUG-04:10 | 0.00 | 01-AUG-00:05 | 66454.33 | 31-AUG-06:40 | 39223.64 | 31-AUG-22:05 | 27275.09 | 30-AUG-17:06 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.413064E+11 | 0.00 | 339.23 | 0.282986E+11 | 0.130078E+11 | 0.00 | 1.00 | 01-SEP-05:08 | 0.00 | 01-SEP-00:05 | 62398.09 | 30-SEP-05:08 | 42669.75 | 30-SEP-21:55 | 19766.58 | 29-SEP-05:08 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.451568E+11 | 0.00 | 365.39 | 0.375258E+11 | 0.763099E+10 | 0.00 | 1.00 | 01-OCT-05:07 | 0.00 | 01-OCT-00:20 | 55435.94 | 31-OCT-05:15 | 45867.28 | 31-OCT-10:37 | 9581.55 | 31-OCT-15:07 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.465175E+11 | 0.00 | 378.60 | 0.465175E+11 | 0.00 | 0.00 | 1.00 | 01-NOV-05:15 | 0.00 | 01-NOV-00:05 | 49811.89 | 30-NOV-06:15 | 49811.89 | 30-NOV-06:15 | 0.00 | 05-NOV-06:20 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.501688E+11 | 0.00 | 419.72 | 0.501688E+11 | -0.0 | 0.00 | 1.00 | 01-DEC-00:07 | 0.00 | 01-DEC-00:03 | 44629.08 | 31-DEC-00:20 | 44629.08 | 31-DEC-00:20 | 0.00 | 23-DEC-09:30 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.554725E+12 | 0.00 | 4479.42 | 0.479314E+12 | 0.754106E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.413047E+11 | 0.00 | 339.23 | 0.244046E+11 | -0.0 | 0.00 | 1.00 | 0.00 | 39958.33 | 39223.64 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.530043E+11 | 0.00 | 439.95 | 0.530019E+11 | 0.169001E+11 | 0.00 | 1.00 | 0.00 | 66454.33 | 53351.89 | 27275.09 | 0.00 | 0.00 |
Report: DXReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.400531E+11 | 0.00 | 385.19 | 0.400531E+11 | 0.00 | 0.00 | 1.00 | 01-JAN-17:10 | 0.00 | 01-JAN-00:05 | 50560.72 | 31-JAN-17:10 | 50560.72 | 31-JAN-17:10 | 0.00 | 17-JAN-19:15 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 0.406085E+11 | 0.00 | 344.68 | 0.406085E+11 | 0.00 | 0.00 | 1.00 | 01-FEB-17:10 | 0.00 | 01-FEB-00:07 | 56782.05 | 01-FEB-17:30 | 56782.05 | 01-FEB-20:00 | 0.00 | 17-FEB-21:50 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 0.519623E+11 | 0.00 | 353.29 | 0.519619E+11 | 469036.65 | 0.00 | 1.00 | 01-MAR-17:10 | 0.00 | 01-MAR-00:07 | 65997.07 | 01-MAR-17:10 | 65997.07 | 01-MAR-20:00 | 2205.48 | 31-MAR-23:03 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 0.544136E+11 | 0.00 | 335.57 | 0.515071E+11 | 0.290659E+10 | 0.00 | 1.00 | 01-APR-16:05 | 0.00 | 01-APR-00:20 | 71669.06 | 01-APR-16:40 | 67529.02 | 01-APR-21:00 | 8142.33 | 30-APR-23:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.603341E+11 | 0.00 | 346.52 | 0.485310E+11 | 0.118031E+11 | 0.00 | 1.00 | 01-MAY-16:10 | 0.00 | 01-MAY-00:05 | 77057.12 | 01-MAY-16:20 | 61710.79 | 01-MAY-21:51 | 15357.61 | 01-MAY-17:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.615212E+11 | 0.00 | 336.46 | 0.463240E+11 | 0.151972E+11 | 0.00 | 1.00 | 01-JUN-16:10 | 0.00 | 01-JUN-00:05 | 81095.77 | 01-JUN-16:10 | 60803.65 | 03-JUN-23:00 | 20325.18 | 01-JUN-17:00 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.656138E+11 | 0.00 | 352.75 | 0.407272E+11 | 0.248865E+11 | 0.00 | 1.00 | 01-JUL-16:10 | 0.00 | 01-JUL-00:20 | 83334.34 | 01-JUL-16:10 | 51643.82 | 01-JUL-21:00 | 31700.58 | 01-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.662316E+11 | 0.00 | 336.71 | 0.391312E+11 | 0.271004E+11 | 0.00 | 1.00 | 01-AUG-16:10 | 0.00 | 01-AUG-00:05 | 84110.92 | 31-AUG-18:50 | 49656.04 | 31-AUG-21:51 | 34511.02 | 30-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.599852E+11 | 0.00 | 335.67 | 0.410983E+11 | 0.188869E+11 | 0.00 | 1.00 | 01-SEP-16:10 | 0.00 | 01-SEP-00:05 | 78974.76 | 30-SEP-19:10 | 54018.16 | 30-SEP-20:00 | 25000.56 | 28-SEP-16:10 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.549887E+11 | 0.00 | 349.27 | 0.457042E+11 | 0.928456E+10 | 0.00 | 1.00 | 01-OCT-16:10 | 0.00 | 01-OCT-00:20 | 70159.03 | 31-OCT-19:30 | 58053.30 | 31-OCT-20:00 | 12110.62 | 31-OCT-16:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.479014E+11 | 0.00 | 367.77 | 0.479014E+11 | 0.00 | 0.00 | 1.00 | 01-NOV-16:10 | 0.00 | 01-NOV-00:05 | 63037.66 | 30-NOV-17:30 | 63037.66 | 30-NOV-17:20 | 0.00 | 12-NOV-19:40 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.445208E+11 | 0.00 | 382.06 | 0.445208E+11 | -0.0 | 0.00 | 1.00 | 01-DEC-17:10 | 0.00 | 01-DEC-00:07 | 56475.00 | 31-DEC-18:35 | 56475.00 | 31-DEC-19:00 | 0.00 | 13-DEC-22:20 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.648134E+12 | 0.00 | 4225.93 | 0.538069E+12 | 0.110066E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.400531E+11 | 0.00 | 335.57 | 0.391312E+11 | -0.0 | 0.00 | 1.00 | 0.00 | 50560.72 | 49656.04 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.662316E+11 | 0.00 | 385.19 | 0.519619E+11 | 0.271004E+11 | 0.00 | 1.00 | 0.00 | 84110.92 | 67529.02 | 34511.02 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.857199E+10 | 0.00 | 224.09 | 0.717297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 127525.87 | 19-JAN-21:00 | 92846.65 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.295379E+11 | 0.00 | 247.32 | 0.291262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152266.98 | 26-FEB-14:40 | 152266.98 | 26-FEB-14:40 | 0.00 | 0.00 | 0.00 |
March | 0.884677E+11 | 0.00 | 403.73 | 0.856890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 236236.18 | 30-MAR-18:05 | 225650.25 | 30-MAR-15:23 | 0.00 | 0.00 | 0.00 |
April | 0.185861E+12 | 0.00 | 519.58 | 0.161258E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 262498.41 | 04-APR-10:33 | 245765.26 | 13-APR-15:30 | 0.00 | 0.00 | 0.00 |
May | 0.367444E+12 | 0.00 | 686.62 | 0.266205E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 430502.17 | 30-MAY-21:05 | 271224.58 | 16-MAY-18:25 | 0.00 | 0.00 | 0.00 |
June | 0.612444E+12 | 0.00 | 702.00 | 0.383362E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 485831.73 | 26-JUN-21:00 | 262288.11 | 10-JUN-17:10 | 0.00 | 0.00 | 0.00 |
July | 0.801700E+12 | 0.00 | 744.00 | 0.436782E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 509105.97 | 18-JUL-20:10 | 271413.89 | 07-JUL-18:40 | 0.00 | 0.00 | 0.00 |
August | 0.866298E+12 | 0.00 | 744.00 | 0.463821E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 618006.24 | 23-AUG-21:00 | 274928.01 | 18-AUG-18:20 | 0.00 | 0.00 | 0.00 |
September | 0.526500E+12 | 0.00 | 697.17 | 0.320418E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 476816.56 | 27-SEP-21:00 | 242226.33 | 08-SEP-20:10 | 0.00 | 0.00 | 0.00 |
October | 0.202313E+12 | 0.00 | 434.95 | 0.133923E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 541472.50 | 18-OCT-21:00 | 203951.35 | 10-OCT-18:20 | 0.00 | 0.00 | 0.00 |
November | 0.674967E+11 | 0.00 | 368.04 | 0.550056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 240259.75 | 27-NOV-19:05 | 144628.00 | 05-NOV-16:00 | 0.00 | 0.00 | 0.00 |
December | 0.148349E+11 | 0.00 | 278.62 | 0.126143E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 172471.86 | 13-DEC-11:40 | 121529.46 | 12-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.377147E+13 | 0.00 | 6050.11 | 0.235538E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.857199E+10 | 0.00 | 224.09 | 0.717297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 127525.87 | 92846.65 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.866298E+12 | 0.00 | 744.00 | 0.463821E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 618006.24 | 274928.01 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.699421E+09 | 0.00 | 30.83 | 0.528690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13434.67 | 19-JAN-16:03 | 12205.19 | 31-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.198040E+10 | 0.00 | 88.33 | 0.195579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16293.42 | 28-FEB-16:02 | 16293.42 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.717311E+10 | 0.00 | 245.17 | 0.651348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23092.79 | 28-MAR-15:02 | 18081.15 | 30-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.143549E+11 | 0.00 | 373.17 | 0.115018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29172.24 | 30-APR-15:02 | 18447.06 | 17-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.302587E+11 | 0.00 | 535.17 | 0.200722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38844.87 | 30-MAY-21:51 | 19091.08 | 19-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.447665E+11 | 0.00 | 553.17 | 0.279822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45304.17 | 29-JUN-08:03 | 20561.12 | 06-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.559576E+11 | 0.00 | 589.00 | 0.315227E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49357.42 | 26-JUL-08:05 | 21493.36 | 08-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.571073E+11 | 0.00 | 589.00 | 0.326820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47904.80 | 24-AUG-08:62 | 20880.02 | 01-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.400859E+11 | 0.00 | 550.67 | 0.244157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45917.73 | 17-SEP-08:03 | 19662.46 | 07-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.162102E+11 | 0.00 | 307.17 | 0.100590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44452.02 | 18-OCT-21:50 | 18630.43 | 10-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.575607E+10 | 0.00 | 170.67 | 0.417254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27234.27 | 19-NOV-24:00 | 16763.84 | 05-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 0.119221E+10 | 0.00 | 51.50 | 0.941584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20043.31 | 12-DEC-13:30 | 14743.43 | 12-DEC-16:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.275542E+12 | 0.00 | 4083.83 | 0.172348E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.699421E+09 | 0.00 | 30.83 | 0.528690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13434.67 | 12205.19 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.571073E+11 | 0.00 | 589.00 | 0.326820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49357.42 | 21493.36 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.155002E+09 | 0.00 | 41.02 | 0.131177E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12383.13 | 20-JAN-16:01 | 11280.16 | 29-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.677357E+09 | 0.00 | 132.02 | 0.585935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13395.33 | 19-FEB-16:02 | 11933.42 | 27-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.254767E+10 | 0.00 | 412.90 | 0.180057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14006.76 | 28-MAR-15:02 | 11641.70 | 10-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.458235E+10 | 0.00 | 569.58 | 0.282774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14292.85 | 02-APR-15:02 | 11763.01 | 18-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.687033E+10 | 0.00 | 675.78 | 0.407194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13635.22 | 27-MAY-08:62 | 11948.49 | 30-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.912175E+10 | 0.00 | 680.57 | 0.587705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15050.30 | 29-JUN-08:62 | 11910.83 | 16-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.104157E+11 | 0.00 | 705.28 | 0.679872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15451.66 | 30-JUL-08:62 | 11941.70 | 11-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.109427E+11 | 0.00 | 712.91 | 0.723444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15575.39 | 29-AUG-08:62 | 11870.36 | 22-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.735741E+10 | 0.00 | 654.77 | 0.437086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15243.04 | 17-SEP-08:62 | 11891.82 | 10-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.374635E+10 | 0.00 | 497.80 | 0.217304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14763.55 | 18-OCT-08:62 | 11572.21 | 02-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.126656E+10 | 0.00 | 281.64 | 0.796489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14082.44 | 04-NOV-15:01 | 11564.95 | 14-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.345911E+09 | 0.00 | 92.27 | 0.234687E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13242.67 | 12-DEC-16:01 | 11173.73 | 08-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.580291E+11 | 0.00 | 5456.54 | 0.369027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.155002E+09 | 0.00 | 41.02 | 0.131177E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12383.13 | 11173.73 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.109427E+11 | 0.00 | 712.91 | 0.723444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15575.39 | 11948.49 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 13849955.74 | 0.00 | 4.80 | 10440865.82 | 0.00 | 0.00 | 0.00 | 0.00 | 11916.23 | 20-JAN-16:01 | 10382.64 | 29-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.140547E+09 | 0.00 | 50.69 | 0.108872E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13082.99 | 19-FEB-16:02 | 11790.09 | 27-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.111893E+10 | 0.00 | 231.41 | 0.686237E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13994.94 | 28-MAR-15:02 | 11597.56 | 11-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.299366E+10 | 0.00 | 412.92 | 0.171075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14349.21 | 02-APR-15:02 | 11823.42 | 26-APR-18:41 | 0.00 | 0.00 | 0.00 |
May | 0.541752E+10 | 0.00 | 498.57 | 0.325603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15186.19 | 07-MAY-17:41 | 11821.58 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.828116E+10 | 0.00 | 564.25 | 0.552498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16422.20 | 26-JUN-08:21 | 11801.14 | 05-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.945354E+10 | 0.00 | 590.15 | 0.639259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16853.32 | 23-JUL-08:51 | 11783.72 | 21-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.972865E+10 | 0.00 | 620.15 | 0.648570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17476.28 | 20-AUG-07:52 | 12727.77 | 08-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.553932E+10 | 0.00 | 496.90 | 0.323601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15750.26 | 06-SEP-08:31 | 12772.20 | 18-SEP-16:01 | 0.00 | 0.00 | 0.00 |
October | 0.176718E+10 | 0.00 | 304.45 | 0.860343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15169.61 | 18-OCT-21:52 | 11769.31 | 07-OCT-16:21 | 0.00 | 0.00 | 0.00 |
November | 0.279000E+09 | 0.00 | 105.98 | 0.156516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13973.94 | 02-NOV-15:02 | 11426.15 | 14-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 50672702.02 | 0.00 | 18.81 | 32163516.48 | 0.00 | 0.00 | 0.00 | 0.00 | 13555.90 | 12-DEC-16:01 | 10322.22 | 11-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.447840E+11 | 0.00 | 3899.09 | 0.284606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 13849955.74 | 0.00 | 4.80 | 10440865.82 | 0.00 | 0.00 | 0.00 | 0.00 | 11916.23 | 10322.22 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.972865E+10 | 0.00 | 620.15 | 0.648570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17476.28 | 12772.20 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.217526E+10 | 0.00 | 64.41 | 0.197410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28651.92 | 29-JAN-13:30 | 28651.92 | 29-JAN-13:30 | 0.00 | 0.00 | 0.00 |
February | 0.697272E+10 | 0.00 | 160.99 | 0.636384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33375.78 | 26-FEB-14:50 | 33375.78 | 26-FEB-14:50 | 0.00 | 0.00 | 0.00 |
March | 0.200250E+11 | 0.00 | 517.79 | 0.146214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33652.49 | 30-MAR-13:30 | 29576.48 | 13-MAR-16:03 | 0.00 | 0.00 | 0.00 |
April | 0.233495E+11 | 0.00 | 595.57 | 0.121436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30862.78 | 15-APR-13:15 | 24695.71 | 15-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.300126E+11 | 0.00 | 712.10 | 0.138004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25695.75 | 06-MAY-13:30 | 16958.65 | 06-MAY-13:30 | 0.00 | 0.00 | 0.00 |
June | 0.387349E+11 | 0.00 | 712.16 | 0.198877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27676.58 | 13-JUN-17:20 | 19638.22 | 24-JUN-17:20 | 0.00 | 0.00 | 0.00 |
July | 0.454230E+11 | 0.00 | 741.92 | 0.248347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30966.85 | 08-JUL-17:25 | 24486.48 | 08-JUL-17:25 | 0.00 | 0.00 | 0.00 |
August | 0.523336E+11 | 0.00 | 744.00 | 0.314386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35731.21 | 27-AUG-13:20 | 32561.10 | 19-AUG-13:50 | 0.00 | 0.00 | 0.00 |
September | 0.403340E+11 | 0.00 | 700.73 | 0.232649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39576.70 | 24-SEP-12:50 | 35583.31 | 23-SEP-13:20 | 0.00 | 0.00 | 0.00 |
October | 0.302338E+11 | 0.00 | 589.58 | 0.185150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42160.25 | 10-OCT-13:30 | 35147.96 | 08-OCT-15:30 | 0.00 | 0.00 | 0.00 |
November | 0.192837E+11 | 0.00 | 478.61 | 0.149707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38035.94 | 12-NOV-14:00 | 37922.96 | 15-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.922842E+10 | 0.00 | 233.83 | 0.772665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37095.28 | 10-DEC-14:25 | 37095.28 | 10-DEC-14:25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318107E+12 | 0.00 | 6251.69 | 0.189542E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.217526E+10 | 0.00 | 64.41 | 0.197410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25695.75 | 16958.65 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.523336E+11 | 0.00 | 744.00 | 0.314386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42160.25 | 37922.96 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.126183E+10 | 0.00 | 69.47 | 0.684812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75370.65 | 19-JAN-22:53 | 61609.61 | 30-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.482668E+10 | 0.00 | 169.10 | 0.337910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75805.83 | 19-FEB-16:02 | 70401.47 | 27-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.145641E+11 | 0.00 | 361.16 | 0.102708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80571.58 | 29-MAR-15:02 | 71476.70 | 29-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.270417E+11 | 0.00 | 402.54 | 0.180293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82278.08 | 02-APR-15:02 | 72440.93 | 11-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.430462E+11 | 0.00 | 449.88 | 0.286588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93064.34 | 07-MAY-17:41 | 73069.12 | 18-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.584359E+11 | 0.00 | 525.02 | 0.410190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99712.25 | 26-JUN-08:21 | 73158.27 | 09-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.654818E+11 | 0.00 | 556.06 | 0.452647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102640.48 | 23-JUL-08:51 | 73115.28 | 13-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.651870E+11 | 0.00 | 571.04 | 0.444466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109954.93 | 20-AUG-07:52 | 74419.25 | 08-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.427459E+11 | 0.00 | 448.43 | 0.269132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97044.36 | 17-SEP-08:52 | 72092.62 | 06-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.208560E+11 | 0.00 | 395.17 | 0.119016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97038.44 | 18-OCT-21:52 | 71734.22 | 10-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.910564E+10 | 0.00 | 291.86 | 0.596681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81442.72 | 05-NOV-15:02 | 66497.90 | 08-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.281571E+10 | 0.00 | 141.38 | 0.155771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76328.11 | 13-DEC-21:02 | 61448.47 | 29-DEC-19:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.355369E+12 | 0.00 | 4381.11 | 0.238092E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.126183E+10 | 0.00 | 69.47 | 0.684812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75370.65 | 61448.47 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.654818E+11 | 0.00 | 571.04 | 0.452647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109954.93 | 74419.25 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.103507E+09 | 0.00 | 42.14 | 82269224.97 | 0.00 | 0.00 | 0.00 | 0.00 | 10853.86 | 20-JAN-16:01 | 10162.48 | 29-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.737733E+09 | 0.00 | 151.13 | 0.633294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11856.61 | 19-FEB-16:02 | 10751.38 | 27-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.228550E+10 | 0.00 | 435.27 | 0.153599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12438.79 | 28-MAR-15:02 | 10706.43 | 11-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.445586E+10 | 0.00 | 595.69 | 0.269164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12853.09 | 02-APR-15:02 | 10613.87 | 28-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.707831E+10 | 0.00 | 698.02 | 0.424057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12315.88 | 27-MAY-08:62 | 10776.16 | 17-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.937150E+10 | 0.00 | 699.39 | 0.610686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13442.85 | 23-JUN-08:62 | 10752.75 | 22-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.107969E+11 | 0.00 | 718.32 | 0.728041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13871.36 | 30-JUL-08:62 | 10764.83 | 14-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.110378E+11 | 0.00 | 723.75 | 0.750338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13399.47 | 24-AUG-08:62 | 10746.34 | 04-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.742301E+10 | 0.00 | 664.71 | 0.448807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13719.52 | 17-SEP-08:62 | 10735.87 | 25-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.369540E+10 | 0.00 | 511.38 | 0.209555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13336.16 | 18-OCT-08:62 | 10464.22 | 02-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.116152E+10 | 0.00 | 292.69 | 0.717190E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12578.89 | 04-NOV-15:01 | 10419.06 | 14-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.303536E+09 | 0.00 | 93.88 | 0.180671E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12096.33 | 12-DEC-16:01 | 9868.18 | 09-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.584506E+11 | 0.00 | 5626.37 | 0.375559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.103507E+09 | 0.00 | 42.14 | 82269224.97 | 0.00 | 0.00 | 0.00 | 0.00 | 10853.86 | 9868.18 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.110378E+11 | 0.00 | 723.75 | 0.750338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13871.36 | 10776.16 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 13643619.05 | 0.00 | 4.15 | 10352114.83 | 0.00 | 0.00 | 0.00 | 0.00 | 9790.28 | 31-JAN-16:01 | 8737.29 | 31-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.228611E+09 | 0.00 | 60.42 | 0.177973E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11162.76 | 19-FEB-16:02 | 10658.11 | 27-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.103572E+10 | 0.00 | 236.60 | 0.615407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12487.10 | 28-MAR-15:02 | 10455.69 | 30-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.299023E+10 | 0.00 | 439.34 | 0.170361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13007.44 | 02-APR-15:02 | 10768.53 | 16-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.561019E+10 | 0.00 | 522.48 | 0.338387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14390.94 | 30-MAY-08:51 | 11422.34 | 18-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.841181E+10 | 0.00 | 577.70 | 0.567039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15510.79 | 13-JUN-08:62 | 11486.65 | 06-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.970290E+10 | 0.00 | 600.56 | 0.678113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15452.91 | 23-JUL-08:51 | 10987.12 | 17-JUL-08:51 | 0.00 | 0.00 | 0.00 |
August | 0.977794E+10 | 0.00 | 629.18 | 0.661427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16002.50 | 29-AUG-08:31 | 11608.55 | 08-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.556764E+10 | 0.00 | 509.11 | 0.325910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15191.36 | 06-SEP-08:31 | 11091.04 | 15-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.185970E+10 | 0.00 | 328.39 | 0.960731E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13729.53 | 18-OCT-21:52 | 10553.85 | 10-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.284456E+09 | 0.00 | 96.01 | 0.148983E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13166.93 | 05-NOV-15:02 | 9668.24 | 06-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 38043722.80 | 0.00 | 17.75 | 19202239.07 | 0.00 | 0.00 | 0.00 | 0.00 | 12106.20 | 12-DEC-16:01 | 8436.61 | 11-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.455209E+11 | 0.00 | 4021.71 | 0.293450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 13643619.05 | 0.00 | 4.15 | 10352114.83 | 0.00 | 0.00 | 0.00 | 0.00 | 9790.28 | 8436.61 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.977794E+10 | 0.00 | 629.18 | 0.678113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16002.50 | 11608.55 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 26374935.01 | 0.00 | 24.54 | 23065194.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3339.19 | 20-JAN-16:01 | 2983.03 | 29-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.147891E+09 | 0.00 | 100.22 | 0.128879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3655.60 | 19-FEB-16:02 | 3155.72 | 27-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.584434E+09 | 0.00 | 328.18 | 0.416664E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3741.87 | 28-MAR-15:02 | 3078.58 | 10-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.109916E+10 | 0.00 | 513.02 | 0.690854E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3858.13 | 02-APR-15:02 | 3101.03 | 09-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.171619E+10 | 0.00 | 662.56 | 0.102075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3754.45 | 28-MAY-08:62 | 3127.51 | 30-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.232962E+10 | 0.00 | 679.17 | 0.148625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4206.48 | 23-JUN-08:62 | 3156.63 | 14-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.267556E+10 | 0.00 | 702.70 | 0.173431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4380.23 | 30-JUL-08:62 | 3161.73 | 07-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.281174E+10 | 0.00 | 710.74 | 0.183865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4346.69 | 29-AUG-08:62 | 3150.77 | 18-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.178277E+10 | 0.00 | 631.54 | 0.104579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4307.17 | 17-SEP-08:62 | 3121.43 | 03-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.845851E+09 | 0.00 | 421.96 | 0.497816E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4073.41 | 18-OCT-08:62 | 3045.76 | 02-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.266752E+09 | 0.00 | 206.11 | 0.171713E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3829.69 | 04-NOV-15:01 | 3058.31 | 14-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 67757783.89 | 0.00 | 66.10 | 46231016.23 | 0.00 | 0.00 | 0.00 | 0.00 | 3546.17 | 12-DEC-16:01 | 2954.92 | 08-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143541E+11 | 0.00 | 5046.85 | 0.910096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 26374935.01 | 0.00 | 24.54 | 23065194.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3339.19 | 2954.92 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.281174E+10 | 0.00 | 710.74 | 0.183865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4380.23 | 3161.73 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2969508.59 | 0.00 | 1.39 | 1989732.10 | 0.00 | 0.00 | 0.00 | 0.00 | 3200.70 | 20-JAN-16:01 | 2271.63 | 20-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 25867166.64 | 0.00 | 26.34 | 20162782.76 | 0.00 | 0.00 | 0.00 | 0.00 | 3561.18 | 19-FEB-16:02 | 3112.50 | 27-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.242735E+09 | 0.00 | 173.35 | 0.147791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3748.54 | 28-MAR-15:02 | 3096.96 | 30-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.712696E+09 | 0.00 | 376.49 | 0.412873E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3886.32 | 02-APR-15:02 | 3146.24 | 09-APR-20:11 | 0.00 | 0.00 | 0.00 |
May | 0.139305E+10 | 0.00 | 501.18 | 0.841778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4071.59 | 07-MAY-17:41 | 3187.08 | 09-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.215551E+10 | 0.00 | 566.54 | 0.143539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4546.95 | 26-JUN-08:21 | 3093.86 | 14-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.247145E+10 | 0.00 | 591.04 | 0.166810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4568.48 | 23-JUL-08:51 | 3117.62 | 12-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.253030E+10 | 0.00 | 620.61 | 0.168162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4879.24 | 20-AUG-07:52 | 3341.88 | 08-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.135811E+10 | 0.00 | 486.14 | 0.780508E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4331.46 | 17-SEP-08:52 | 3408.14 | 18-SEP-16:01 | 0.00 | 0.00 | 0.00 |
October | 0.371389E+09 | 0.00 | 232.96 | 0.184388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4200.65 | 18-OCT-21:52 | 3129.86 | 15-OCT-16:21 | 0.00 | 0.00 | 0.00 |
November | 45810995.39 | 0.00 | 53.00 | 26033955.87 | 0.00 | 0.00 | 0.00 | 0.00 | 3794.46 | 02-NOV-15:02 | 3016.38 | 14-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 6754610.99 | 0.00 | 7.59 | 4248327.20 | 0.00 | 0.00 | 0.00 | 0.00 | 3663.57 | 12-DEC-16:01 | 2653.51 | 11-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113167E+11 | 0.00 | 3636.63 | 0.720488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2969508.59 | 0.00 | 1.39 | 1989732.10 | 0.00 | 0.00 | 0.00 | 0.00 | 3200.70 | 2271.63 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.253030E+10 | 0.00 | 620.61 | 0.168162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4879.24 | 3408.14 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.136147E+10 | 0.00 | 176.72 | 0.119940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14797.86 | 20-JAN-16:01 | 13351.47 | 29-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.217834E+10 | 0.00 | 237.34 | 0.193564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16058.82 | 19-FEB-16:02 | 13974.22 | 28-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.482034E+10 | 0.00 | 496.60 | 0.363706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15733.25 | 28-MAR-15:02 | 14040.33 | 30-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.628960E+10 | 0.00 | 570.04 | 0.398048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17011.97 | 21-APR-18:02 | 14028.43 | 17-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.857336E+10 | 0.00 | 666.47 | 0.490360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16862.47 | 25-MAY-18:02 | 14107.39 | 16-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.111723E+11 | 0.00 | 673.72 | 0.692682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19538.58 | 29-JUN-08:62 | 14137.00 | 20-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.131823E+11 | 0.00 | 698.87 | 0.844523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19838.13 | 29-JUL-18:02 | 14138.34 | 11-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.146938E+11 | 0.00 | 709.47 | 0.989168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19972.57 | 29-AUG-08:62 | 14147.65 | 30-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.108017E+11 | 0.00 | 651.27 | 0.678857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19183.11 | 17-SEP-08:62 | 14150.26 | 07-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.738505E+10 | 0.00 | 571.92 | 0.496268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18224.33 | 18-OCT-08:62 | 14051.91 | 10-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.451502E+10 | 0.00 | 456.54 | 0.339428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16470.16 | 04-NOV-15:01 | 13688.30 | 14-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.248334E+10 | 0.00 | 276.15 | 0.205036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15098.36 | 13-DEC-16:01 | 13272.10 | 05-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.874567E+11 | 0.00 | 6185.11 | 0.581158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.136147E+10 | 0.00 | 176.72 | 0.119940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14797.86 | 13272.10 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.146938E+11 | 0.00 | 709.47 | 0.989168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19972.57 | 14150.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 527.26 | 366.27 | 160.99 | 608.49 | 560.17 | 0.00 | 0.00 | 0.00 |
February | 491.15 | 327.66 | 163.48 | 616.45 | 466.18 | 0.00 | 0.00 | 0.00 |
March | 449.12 | 235.68 | 213.44 | 627.37 | 300.67 | 0.00 | 0.00 | 0.00 |
April | 338.00 | 112.77 | 225.23 | 531.44 | 237.82 | 0.00 | 0.00 | 0.00 |
May | 271.69 | 33.25 | 238.45 | 459.22 | 146.89 | 0.00 | 0.00 | 0.00 |
June | 249.47 | 13.93 | 235.54 | 488.45 | 88.53 | 0.00 | 0.00 | 0.00 |
July | 250.25 | 16.88 | 233.37 | 512.72 | 56.13 | 0.00 | 0.00 | 0.00 |
August | 301.54 | 56.67 | 244.87 | 616.91 | 46.10 | 0.00 | 0.00 | 0.00 |
September | 340.43 | 132.46 | 207.97 | 599.99 | 118.89 | 0.00 | 0.00 | 0.00 |
October | 478.03 | 308.97 | 169.06 | 723.40 | 270.72 | 0.00 | 0.00 | 0.00 |
November | 522.27 | 348.52 | 173.76 | 711.63 | 364.65 | 0.00 | 0.00 | 0.00 |
December | 523.54 | 368.30 | 155.25 | 646.94 | 466.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 394.80 | 192.80 | 202.00 | 595.21 | 259.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 249.47 | 13.93 | 155.25 | 459.22 | 46.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 527.26 | 368.30 | 244.87 | 723.40 | 560.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1484.72 | 1031.40 | 453.32 | 1679.18 | 1670.78 | 0.00 | 0.00 | 0.00 |
February | 1383.03 | 922.68 | 460.35 | 1701.80 | 1413.78 | 0.00 | 0.00 | 0.00 |
March | 1264.70 | 663.66 | 601.04 | 1728.51 | 942.10 | 0.00 | 0.00 | 0.00 |
April | 951.78 | 317.55 | 634.23 | 1462.99 | 744.83 | 0.00 | 0.00 | 0.00 |
May | 765.07 | 93.63 | 671.45 | 1266.17 | 468.06 | 0.00 | 0.00 | 0.00 |
June | 702.49 | 39.22 | 663.27 | 1368.68 | 271.28 | 0.00 | 0.00 | 0.00 |
July | 704.68 | 47.53 | 657.15 | 1441.94 | 173.30 | 0.00 | 0.00 | 0.00 |
August | 849.11 | 159.58 | 689.52 | 1736.70 | 137.67 | 0.00 | 0.00 | 0.00 |
September | 958.64 | 373.00 | 585.64 | 1671.02 | 375.20 | 0.00 | 0.00 | 0.00 |
October | 1346.11 | 870.05 | 476.06 | 2006.28 | 846.06 | 0.00 | 0.00 | 0.00 |
November | 1470.69 | 981.40 | 489.29 | 1962.46 | 1134.54 | 0.00 | 0.00 | 0.00 |
December | 1474.27 | 1037.10 | 437.17 | 1784.68 | 1417.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1111.73 | 542.91 | 568.82 | 1650.83 | 796.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 702.49 | 39.22 | 437.17 | 1266.17 | 137.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1484.72 | 1037.10 | 689.52 | 2006.28 | 1670.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1928.74 | 1339.84 | 588.89 | 2219.87 | 2260.83 | 0.00 | 0.00 | 0.00 |
February | 1796.64 | 1198.62 | 598.02 | 2254.57 | 1909.28 | 0.00 | 0.00 | 0.00 |
March | 1642.92 | 862.13 | 780.79 | 2293.86 | 1260.90 | 0.00 | 0.00 | 0.00 |
April | 1236.41 | 412.51 | 823.90 | 1939.62 | 1002.05 | 0.00 | 0.00 | 0.00 |
May | 993.87 | 121.63 | 872.25 | 1678.85 | 627.54 | 0.00 | 0.00 | 0.00 |
June | 912.57 | 50.95 | 861.62 | 1819.95 | 359.72 | 0.00 | 0.00 | 0.00 |
July | 915.42 | 61.75 | 853.67 | 1922.66 | 227.99 | 0.00 | 0.00 | 0.00 |
August | 1103.04 | 207.31 | 895.73 | 2322.10 | 175.63 | 0.00 | 0.00 | 0.00 |
September | 1245.33 | 484.54 | 760.78 | 2218.91 | 497.79 | 0.00 | 0.00 | 0.00 |
October | 1748.68 | 1130.24 | 618.43 | 2661.28 | 1133.61 | 0.00 | 0.00 | 0.00 |
November | 1910.51 | 1274.89 | 635.62 | 2595.60 | 1524.28 | 0.00 | 0.00 | 0.00 |
December | 1915.16 | 1347.25 | 567.91 | 2358.06 | 1918.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1444.20 | 705.27 | 738.93 | 2190.43 | 1070.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 912.57 | 50.95 | 567.91 | 1678.85 | 175.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1928.74 | 1347.25 | 895.73 | 2661.28 | 2260.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.25 | 72.42 | 31.83 | 121.01 | 112.76 | 0.00 | 0.00 | 0.00 |
February | 97.11 | 64.78 | 32.32 | 122.52 | 92.84 | 0.00 | 0.00 | 0.00 |
March | 88.80 | 46.60 | 42.20 | 124.27 | 57.63 | 0.00 | 0.00 | 0.00 |
April | 66.83 | 22.30 | 44.53 | 105.55 | 44.51 | 0.00 | 0.00 | 0.00 |
May | 53.72 | 6.57 | 47.15 | 92.65 | 24.63 | 0.00 | 0.00 | 0.00 |
June | 49.32 | 2.75 | 46.57 | 103.23 | 11.51 | 0.00 | 0.00 | 0.00 |
July | 49.48 | 3.34 | 46.14 | 110.14 | 5.53 | 0.00 | 0.00 | 0.00 |
August | 59.62 | 11.20 | 48.41 | 132.25 | 2.80 | 0.00 | 0.00 | 0.00 |
September | 67.31 | 26.19 | 41.12 | 123.33 | 17.01 | 0.00 | 0.00 | 0.00 |
October | 94.52 | 61.09 | 33.43 | 145.37 | 49.49 | 0.00 | 0.00 | 0.00 |
November | 103.26 | 68.91 | 34.36 | 142.20 | 70.40 | 0.00 | 0.00 | 0.00 |
December | 103.51 | 72.82 | 30.70 | 129.09 | 92.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.06 | 38.12 | 39.94 | 120.98 | 48.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.32 | 2.75 | 30.70 | 92.65 | 2.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.25 | 72.82 | 48.41 | 145.37 | 112.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.12 | 38.65 | 44.47 | 65.38 | 237.58 | 0.00 | 0.00 | 0.00 |
February | 95.23 | 44.63 | 50.60 | 98.29 | 192.42 | 0.00 | 0.00 | 0.00 |
March | 139.71 | 67.38 | 72.33 | 179.51 | 111.49 | 0.00 | 0.00 | 0.00 |
April | 157.43 | 72.01 | 85.43 | 235.75 | 81.93 | 0.00 | 0.00 | 0.00 |
May | 158.41 | 60.12 | 98.28 | 264.11 | 45.60 | 0.00 | 0.00 | 0.00 |
June | 166.42 | 64.08 | 102.34 | 316.13 | 21.34 | 0.00 | 0.00 | 0.00 |
July | 156.65 | 57.94 | 98.71 | 312.49 | 10.22 | 0.00 | 0.00 | 0.00 |
August | 153.87 | 57.55 | 96.32 | 309.00 | 5.21 | 0.00 | 0.00 | 0.00 |
September | 125.70 | 52.55 | 73.15 | 218.16 | 31.86 | 0.00 | 0.00 | 0.00 |
October | 111.85 | 58.15 | 53.69 | 159.24 | 97.40 | 0.00 | 0.00 | 0.00 |
November | 88.83 | 39.72 | 49.11 | 103.07 | 144.81 | 0.00 | 0.00 | 0.00 |
December | 73.57 | 32.23 | 41.35 | 63.61 | 194.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.06 | 53.79 | 72.27 | 194.24 | 97.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.57 | 32.23 | 41.35 | 63.61 | 5.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 166.42 | 72.01 | 102.34 | 316.13 | 237.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.63 | 0.00 | 19.63 | 3.12 | 133.92 | 0.00 | 0.00 | 0.00 |
February | 21.76 | 0.00 | 21.76 | 10.50 | 107.15 | 0.17 | 0.00 | 0.00 |
March | 30.56 | 0.00 | 30.56 | 23.98 | 61.75 | 0.00 | 0.00 | 0.00 |
April | 37.06 | 0.22 | 36.84 | 45.38 | 45.59 | 0.00 | 0.00 | 0.00 |
May | 44.21 | 1.39 | 42.83 | 68.86 | 25.11 | 0.00 | 0.00 | 0.00 |
June | 48.63 | 3.19 | 45.44 | 98.25 | 11.56 | 0.00 | 0.00 | 0.00 |
July | 46.05 | 2.36 | 43.69 | 100.20 | 6.06 | 0.00 | 0.00 | 0.00 |
August | 40.90 | 0.48 | 40.42 | 92.34 | 3.13 | 0.00 | 0.00 | 0.00 |
September | 30.88 | 0.01 | 30.86 | 53.35 | 18.57 | 0.00 | 0.00 | 0.00 |
October | 23.46 | 0.00 | 23.46 | 24.40 | 53.57 | 0.00 | 0.00 | 0.00 |
November | 21.00 | 0.00 | 21.00 | 13.46 | 78.13 | 0.00 | 0.00 | 0.00 |
December | 18.15 | 0.00 | 18.15 | 4.11 | 106.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.91 | 0.64 | 31.27 | 45.03 | 53.99 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 18.15 | 0.00 | 18.15 | 3.12 | 3.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.63 | 3.19 | 45.44 | 100.20 | 133.92 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.12 | 38.65 | 44.47 | 69.05 | 233.31 | 0.00 | 0.00 | 0.00 |
February | 95.23 | 44.63 | 50.60 | 101.60 | 189.54 | 0.17 | 0.00 | 0.00 |
March | 139.71 | 67.38 | 72.33 | 181.64 | 111.21 | 0.00 | 0.00 | 0.00 |
April | 157.43 | 72.01 | 85.43 | 235.41 | 84.54 | 0.00 | 0.00 | 0.00 |
May | 158.41 | 60.12 | 98.28 | 261.60 | 49.19 | 0.00 | 0.00 | 0.00 |
June | 166.42 | 64.08 | 102.34 | 313.17 | 23.11 | 0.00 | 0.00 | 0.00 |
July | 156.65 | 57.94 | 98.71 | 309.62 | 11.65 | 0.00 | 0.00 | 0.00 |
August | 153.87 | 57.55 | 96.32 | 307.56 | 5.91 | 0.00 | 0.00 | 0.00 |
September | 125.70 | 52.55 | 73.15 | 217.56 | 34.36 | 0.00 | 0.00 | 0.00 |
October | 111.85 | 58.15 | 53.69 | 161.26 | 98.00 | 0.00 | 0.00 | 0.00 |
November | 88.83 | 39.72 | 49.11 | 107.16 | 142.16 | 0.00 | 0.00 | 0.00 |
December | 73.57 | 32.23 | 41.35 | 67.82 | 190.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.06 | 53.79 | 72.27 | 194.96 | 97.31 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 73.57 | 32.23 | 41.35 | 67.82 | 5.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 166.42 | 72.01 | 102.34 | 313.17 | 233.31 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.38 | 57.92 | 25.46 | 89.91 | 103.32 | 0.00 | 0.00 | 0.00 |
February | 77.67 | 51.82 | 25.85 | 88.66 | 96.00 | 0.00 | 0.00 | 0.00 |
March | 71.03 | 37.27 | 33.75 | 86.34 | 71.19 | 0.00 | 0.00 | 0.00 |
April | 53.45 | 17.83 | 35.62 | 71.54 | 57.89 | 0.00 | 0.00 | 0.00 |
May | 42.97 | 5.26 | 37.71 | 60.27 | 38.88 | 0.00 | 0.00 | 0.00 |
June | 39.45 | 2.20 | 37.25 | 66.42 | 24.48 | 0.00 | 0.00 | 0.00 |
July | 39.57 | 2.67 | 36.91 | 70.82 | 18.00 | 0.00 | 0.00 | 0.00 |
August | 47.69 | 8.96 | 38.72 | 88.14 | 15.61 | 0.00 | 0.00 | 0.00 |
September | 53.84 | 20.95 | 32.89 | 84.90 | 32.98 | 0.00 | 0.00 | 0.00 |
October | 75.60 | 48.86 | 26.74 | 103.94 | 64.83 | 0.00 | 0.00 | 0.00 |
November | 82.59 | 55.11 | 27.48 | 100.67 | 83.90 | 0.00 | 0.00 | 0.00 |
December | 82.79 | 58.24 | 24.55 | 91.69 | 100.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.43 | 30.49 | 31.95 | 83.60 | 58.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.45 | 2.20 | 24.55 | 60.27 | 15.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.38 | 58.24 | 38.72 | 103.94 | 103.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.71 | 0.00 | 15.71 | 2.20 | 112.59 | 0.00 | 0.00 | 0.00 |
February | 17.41 | 0.00 | 17.41 | 8.27 | 89.46 | 0.00 | 0.00 | 0.00 |
March | 24.45 | 0.00 | 24.45 | 20.12 | 49.29 | 0.00 | 0.00 | 0.00 |
April | 29.65 | 0.17 | 29.48 | 38.39 | 35.40 | 0.00 | 0.00 | 0.00 |
May | 35.37 | 1.11 | 34.27 | 58.03 | 18.81 | 0.00 | 0.00 | 0.00 |
June | 38.91 | 2.55 | 36.35 | 82.67 | 7.95 | 0.00 | 0.00 | 0.00 |
July | 36.85 | 1.89 | 34.96 | 84.60 | 3.87 | 0.00 | 0.00 | 0.00 |
August | 32.73 | 0.38 | 32.34 | 78.83 | 1.66 | 0.00 | 0.00 | 0.00 |
September | 24.70 | 0.01 | 24.69 | 45.45 | 13.65 | 0.00 | 0.00 | 0.00 |
October | 18.77 | 0.00 | 18.77 | 20.62 | 42.68 | 0.00 | 0.00 | 0.00 |
November | 16.80 | 0.00 | 16.80 | 10.69 | 64.42 | 0.00 | 0.00 | 0.00 |
December | 14.52 | 0.00 | 14.52 | 2.78 | 89.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.53 | 0.51 | 25.02 | 37.89 | 43.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.52 | 0.00 | 14.52 | 2.20 | 1.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.91 | 2.55 | 36.35 | 84.60 | 112.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.12 | 36.93 | 44.18 | 55.84 | 230.84 | 0.00 | 0.00 | 0.00 |
February | 101.81 | 54.80 | 47.00 | 98.89 | 182.01 | 0.00 | 0.00 | 0.00 |
March | 128.09 | 58.43 | 69.66 | 151.98 | 103.54 | 0.00 | 0.00 | 0.00 |
April | 154.84 | 70.67 | 84.16 | 225.23 | 75.57 | 0.00 | 0.00 | 0.00 |
May | 169.62 | 71.73 | 97.89 | 278.64 | 42.10 | 0.00 | 0.00 | 0.00 |
June | 175.44 | 73.48 | 101.96 | 329.72 | 19.44 | 0.00 | 0.00 | 0.00 |
July | 171.00 | 71.74 | 99.26 | 335.70 | 9.83 | 0.00 | 0.00 | 0.00 |
August | 156.73 | 62.17 | 94.56 | 314.35 | 4.90 | 0.00 | 0.00 | 0.00 |
September | 128.45 | 56.76 | 71.69 | 221.82 | 30.32 | 0.00 | 0.00 | 0.00 |
October | 109.86 | 57.18 | 52.68 | 149.07 | 90.95 | 0.00 | 0.00 | 0.00 |
November | 87.50 | 39.47 | 48.03 | 89.91 | 133.75 | 0.00 | 0.00 | 0.00 |
December | 75.93 | 34.56 | 41.37 | 56.47 | 183.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.49 | 57.32 | 71.17 | 192.80 | 91.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.93 | 34.56 | 41.37 | 55.84 | 4.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 175.44 | 73.48 | 101.96 | 335.70 | 230.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.25 | 72.42 | 31.83 | 120.41 | 112.48 | 0.00 | 0.00 | 0.00 |
February | 97.11 | 64.78 | 32.32 | 121.56 | 92.64 | 0.00 | 0.00 | 0.00 |
March | 88.80 | 46.60 | 42.20 | 123.46 | 57.10 | 0.00 | 0.00 | 0.00 |
April | 66.83 | 22.30 | 44.53 | 104.70 | 44.18 | 0.00 | 0.00 | 0.00 |
May | 53.72 | 6.57 | 47.15 | 91.81 | 24.45 | 0.00 | 0.00 | 0.00 |
June | 49.32 | 2.75 | 46.57 | 102.51 | 11.34 | 0.00 | 0.00 | 0.00 |
July | 49.48 | 3.34 | 46.14 | 109.51 | 5.44 | 0.00 | 0.00 | 0.00 |
August | 59.62 | 11.20 | 48.41 | 131.96 | 2.70 | 0.00 | 0.00 | 0.00 |
September | 67.31 | 26.19 | 41.12 | 122.89 | 16.81 | 0.00 | 0.00 | 0.00 |
October | 94.52 | 61.09 | 33.43 | 144.68 | 49.12 | 0.00 | 0.00 | 0.00 |
November | 103.26 | 68.91 | 34.36 | 141.58 | 70.09 | 0.00 | 0.00 | 0.00 |
December | 103.51 | 72.82 | 30.70 | 128.47 | 92.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.06 | 38.12 | 39.94 | 120.31 | 47.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.32 | 2.75 | 30.70 | 91.81 | 2.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.25 | 72.82 | 48.41 | 144.68 | 112.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.63 | 0.00 | 19.63 | 2.97 | 133.99 | 0.00 | 0.00 | 0.00 |
February | 21.76 | 0.00 | 21.76 | 10.07 | 107.30 | 0.33 | 0.00 | 0.00 |
March | 30.56 | 0.00 | 30.56 | 23.54 | 61.01 | 0.00 | 0.00 | 0.00 |
April | 37.06 | 0.22 | 36.84 | 44.58 | 44.93 | 0.00 | 0.00 | 0.00 |
May | 44.21 | 1.39 | 42.83 | 67.75 | 24.70 | 0.00 | 0.00 | 0.00 |
June | 48.63 | 3.19 | 45.44 | 96.95 | 11.33 | 0.00 | 0.00 | 0.00 |
July | 46.05 | 2.36 | 43.69 | 99.01 | 6.02 | 0.00 | 0.00 | 0.00 |
August | 40.90 | 0.48 | 40.42 | 91.73 | 3.01 | 0.00 | 0.00 | 0.00 |
September | 30.88 | 0.01 | 30.86 | 52.58 | 18.32 | 0.00 | 0.00 | 0.00 |
October | 23.46 | 0.00 | 23.46 | 23.75 | 52.95 | 0.00 | 0.00 | 0.00 |
November | 21.00 | 0.00 | 21.00 | 13.19 | 77.62 | 0.00 | 0.00 | 0.00 |
December | 18.15 | 0.00 | 18.15 | 3.92 | 106.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.91 | 0.64 | 31.27 | 44.37 | 53.72 | 0.33 | 0.00 | 0.00 |
Minimum of Months | 18.15 | 0.00 | 18.15 | 2.97 | 3.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.63 | 3.19 | 45.44 | 99.01 | 133.99 | 0.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.12 | 36.93 | 44.18 | 57.87 | 224.76 | 0.00 | 0.00 | 0.00 |
February | 101.81 | 54.80 | 47.00 | 101.81 | 178.35 | 0.17 | 0.00 | 0.00 |
March | 128.09 | 58.43 | 69.66 | 154.73 | 102.61 | 0.00 | 0.00 | 0.00 |
April | 154.84 | 70.67 | 84.16 | 225.34 | 77.76 | 0.00 | 0.00 | 0.00 |
May | 169.62 | 71.73 | 97.89 | 275.62 | 45.28 | 0.00 | 0.00 | 0.00 |
June | 175.44 | 73.48 | 101.96 | 325.32 | 20.98 | 0.00 | 0.00 | 0.00 |
July | 171.00 | 71.74 | 99.26 | 331.35 | 11.19 | 0.00 | 0.00 | 0.00 |
August | 156.73 | 62.17 | 94.56 | 312.02 | 5.47 | 0.00 | 0.00 | 0.00 |
September | 128.45 | 56.76 | 71.69 | 220.33 | 32.53 | 0.00 | 0.00 | 0.00 |
October | 109.86 | 57.18 | 52.68 | 151.28 | 90.94 | 0.00 | 0.00 | 0.00 |
November | 87.50 | 39.47 | 48.03 | 94.17 | 130.19 | 0.00 | 0.00 | 0.00 |
December | 75.93 | 34.56 | 41.37 | 59.49 | 177.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.49 | 57.32 | 71.17 | 192.93 | 91.04 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 75.93 | 34.56 | 41.37 | 57.87 | 5.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 175.44 | 73.48 | 101.96 | 331.35 | 224.76 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.87 | 0.00 | 24.87 | 3.46 | 182.91 | 0.00 | 0.00 | 0.00 |
February | 27.56 | 0.00 | 27.56 | 12.82 | 145.21 | 0.00 | 0.00 | 0.00 |
March | 38.70 | 0.00 | 38.70 | 31.05 | 82.71 | 0.00 | 0.00 | 0.00 |
April | 46.93 | 0.27 | 46.65 | 59.08 | 61.60 | 0.00 | 0.00 | 0.00 |
May | 55.99 | 1.76 | 54.24 | 89.15 | 35.46 | 0.00 | 0.00 | 0.00 |
June | 61.58 | 4.04 | 57.54 | 123.34 | 19.46 | 0.00 | 0.00 | 0.00 |
July | 58.32 | 2.99 | 55.33 | 123.59 | 12.38 | 0.00 | 0.00 | 0.00 |
August | 51.80 | 0.61 | 51.19 | 112.48 | 8.83 | 0.00 | 0.00 | 0.00 |
September | 39.10 | 0.02 | 39.09 | 66.52 | 29.39 | 0.00 | 0.00 | 0.00 |
October | 29.71 | 0.00 | 29.71 | 30.48 | 74.29 | 0.00 | 0.00 | 0.00 |
November | 26.59 | 0.00 | 26.59 | 16.41 | 105.84 | 0.00 | 0.00 | 0.00 |
December | 22.99 | 0.00 | 22.99 | 4.15 | 145.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.42 | 0.81 | 39.60 | 56.29 | 74.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.99 | 0.00 | 22.99 | 3.46 | 8.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.58 | 4.04 | 57.54 | 123.59 | 182.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.17 | 0.00 | 9.17 | 1.28 | 67.43 | 0.00 | 0.00 | 0.00 |
February | 10.16 | 0.00 | 10.16 | 4.73 | 53.53 | 0.00 | 0.00 | 0.00 |
March | 14.27 | 0.00 | 14.27 | 11.44 | 30.49 | 0.00 | 0.00 | 0.00 |
April | 17.30 | 0.10 | 17.20 | 21.78 | 22.71 | 0.00 | 0.00 | 0.00 |
May | 20.64 | 0.65 | 19.99 | 32.86 | 13.07 | 0.00 | 0.00 | 0.00 |
June | 22.70 | 1.49 | 21.21 | 45.47 | 7.17 | 0.00 | 0.00 | 0.00 |
July | 21.50 | 1.10 | 20.40 | 45.56 | 4.57 | 0.00 | 0.00 | 0.00 |
August | 19.10 | 0.22 | 18.87 | 41.46 | 3.26 | 0.00 | 0.00 | 0.00 |
September | 14.41 | 0.01 | 14.41 | 24.52 | 10.83 | 0.00 | 0.00 | 0.00 |
October | 10.95 | 0.00 | 10.95 | 11.24 | 27.39 | 0.00 | 0.00 | 0.00 |
November | 9.80 | 0.00 | 9.80 | 6.05 | 39.02 | 0.00 | 0.00 | 0.00 |
December | 8.47 | 0.00 | 8.47 | 1.53 | 53.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14.90 | 0.30 | 14.60 | 20.75 | 27.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.47 | 0.00 | 8.47 | 1.28 | 3.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.70 | 1.49 | 21.21 | 45.56 | 67.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 48.64 | 33.79 | 14.85 | 56.09 | 55.19 | 0.00 | 0.00 | 0.00 |
February | 45.31 | 30.23 | 15.08 | 57.20 | 45.44 | 0.00 | 0.00 | 0.00 |
March | 41.43 | 21.74 | 19.69 | 58.76 | 28.51 | 0.00 | 0.00 | 0.00 |
April | 31.18 | 10.40 | 20.78 | 49.81 | 22.92 | 0.00 | 0.00 | 0.00 |
May | 25.07 | 3.07 | 22.00 | 43.43 | 13.86 | 0.00 | 0.00 | 0.00 |
June | 23.01 | 1.28 | 21.73 | 47.14 | 7.73 | 0.00 | 0.00 | 0.00 |
July | 23.09 | 1.56 | 21.53 | 49.52 | 4.78 | 0.00 | 0.00 | 0.00 |
August | 27.82 | 5.23 | 22.59 | 59.67 | 3.32 | 0.00 | 0.00 | 0.00 |
September | 31.41 | 12.22 | 19.19 | 56.93 | 10.74 | 0.00 | 0.00 | 0.00 |
October | 44.10 | 28.50 | 15.60 | 68.09 | 25.55 | 0.00 | 0.00 | 0.00 |
November | 48.18 | 32.15 | 16.03 | 66.97 | 34.44 | 0.00 | 0.00 | 0.00 |
December | 48.30 | 33.98 | 14.32 | 60.19 | 44.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.42 | 17.79 | 18.64 | 56.15 | 24.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.01 | 1.28 | 14.32 | 43.43 | 3.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.64 | 33.98 | 22.59 | 68.09 | 55.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.02 | 91.71 | 40.31 | 152.25 | 149.79 | 0.00 | 0.00 | 0.00 |
February | 122.98 | 82.05 | 40.94 | 155.26 | 123.32 | 0.00 | 0.00 | 0.00 |
March | 112.46 | 59.01 | 53.45 | 159.49 | 77.37 | 0.00 | 0.00 | 0.00 |
April | 84.63 | 28.24 | 56.40 | 135.19 | 62.20 | 0.00 | 0.00 | 0.00 |
May | 68.03 | 8.33 | 59.71 | 117.88 | 37.61 | 0.00 | 0.00 | 0.00 |
June | 62.47 | 3.49 | 58.98 | 127.95 | 20.98 | 0.00 | 0.00 | 0.00 |
July | 62.66 | 4.23 | 58.43 | 134.42 | 12.97 | 0.00 | 0.00 | 0.00 |
August | 75.50 | 14.19 | 61.31 | 161.96 | 9.01 | 0.00 | 0.00 | 0.00 |
September | 85.24 | 33.17 | 52.08 | 154.52 | 29.16 | 0.00 | 0.00 | 0.00 |
October | 119.70 | 77.37 | 42.33 | 184.80 | 69.35 | 0.00 | 0.00 | 0.00 |
November | 130.78 | 87.27 | 43.51 | 181.76 | 93.47 | 0.00 | 0.00 | 0.00 |
December | 131.09 | 92.22 | 38.87 | 163.38 | 122.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.86 | 48.28 | 50.58 | 152.41 | 66.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.47 | 3.49 | 38.87 | 117.88 | 9.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.02 | 92.22 | 61.31 | 184.80 | 149.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.25 | 72.42 | 31.83 | 120.74 | 112.01 | 0.00 | 0.00 | 0.00 |
February | 97.11 | 64.78 | 32.32 | 122.03 | 92.05 | 0.67 | 0.00 | 0.00 |
March | 88.80 | 46.60 | 42.20 | 123.37 | 56.85 | 0.00 | 0.00 | 0.00 |
April | 66.83 | 22.30 | 44.53 | 104.62 | 43.92 | 0.00 | 0.00 | 0.00 |
May | 53.72 | 6.57 | 47.15 | 91.67 | 24.19 | 0.00 | 0.00 | 0.00 |
June | 49.32 | 2.75 | 46.57 | 102.61 | 11.04 | 0.00 | 0.00 | 0.00 |
July | 49.48 | 3.34 | 46.14 | 109.54 | 5.14 | 0.00 | 0.00 | 0.00 |
August | 59.62 | 11.20 | 48.41 | 131.58 | 2.49 | 0.00 | 0.00 | 0.00 |
September | 67.31 | 26.19 | 41.12 | 122.62 | 16.37 | 0.00 | 0.00 | 0.00 |
October | 94.52 | 61.09 | 33.43 | 144.57 | 48.58 | 0.83 | 0.00 | 0.00 |
November | 103.26 | 68.91 | 34.36 | 141.68 | 69.45 | 0.00 | 0.00 | 0.00 |
December | 103.51 | 72.82 | 30.70 | 128.76 | 91.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.06 | 38.12 | 39.94 | 120.33 | 47.57 | 1.50 | 0.00 | 0.00 |
Minimum of Months | 49.32 | 2.75 | 30.70 | 91.67 | 2.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.25 | 72.82 | 48.41 | 144.57 | 112.01 | 0.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.12 | 38.65 | 44.47 | 65.42 | 236.00 | 0.00 | 0.00 | 0.00 |
February | 95.23 | 44.63 | 50.60 | 97.90 | 190.58 | 2.17 | 0.00 | 0.00 |
March | 139.71 | 67.38 | 72.33 | 178.00 | 109.81 | 0.00 | 0.00 | 0.00 |
April | 157.43 | 72.01 | 85.43 | 233.70 | 80.78 | 0.00 | 0.00 | 0.00 |
May | 158.41 | 60.12 | 98.28 | 261.68 | 44.73 | 0.00 | 0.00 | 0.00 |
June | 166.42 | 64.08 | 102.34 | 313.88 | 20.39 | 0.00 | 0.00 | 0.00 |
July | 156.65 | 57.94 | 98.71 | 310.67 | 9.48 | 0.00 | 0.00 | 0.00 |
August | 153.87 | 57.55 | 96.32 | 307.28 | 4.62 | 0.00 | 0.00 | 0.00 |
September | 125.70 | 52.55 | 73.15 | 216.89 | 30.58 | 0.00 | 0.00 | 0.00 |
October | 111.85 | 58.15 | 53.69 | 158.23 | 95.44 | 1.00 | 0.00 | 0.00 |
November | 88.83 | 39.72 | 49.11 | 102.62 | 142.78 | 0.00 | 0.00 | 0.00 |
December | 73.57 | 32.23 | 41.35 | 63.71 | 192.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.06 | 53.79 | 72.27 | 193.01 | 96.00 | 3.17 | 0.00 | 0.00 |
Minimum of Months | 73.57 | 32.23 | 41.35 | 63.71 | 4.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 166.42 | 72.01 | 102.34 | 313.88 | 236.00 | 2.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.63 | 0.00 | 19.63 | 3.26 | 133.05 | 0.00 | 0.00 | 0.00 |
February | 21.76 | 0.00 | 21.76 | 10.72 | 106.21 | 3.83 | 0.00 | 0.00 |
March | 30.56 | 0.00 | 30.56 | 24.07 | 60.88 | 0.00 | 0.00 | 0.00 |
April | 37.06 | 0.22 | 36.84 | 44.99 | 45.28 | 0.00 | 0.00 | 0.00 |
May | 44.21 | 1.39 | 42.83 | 68.08 | 24.97 | 0.00 | 0.00 | 0.00 |
June | 48.63 | 3.19 | 45.44 | 97.75 | 11.20 | 0.00 | 0.00 | 0.00 |
July | 46.05 | 2.36 | 43.69 | 99.75 | 5.74 | 0.00 | 0.00 | 0.00 |
August | 40.90 | 0.48 | 40.42 | 92.02 | 2.79 | 0.00 | 0.00 | 0.00 |
September | 30.88 | 0.01 | 30.86 | 53.22 | 17.87 | 0.00 | 0.00 | 0.00 |
October | 23.46 | 0.00 | 23.46 | 24.65 | 52.47 | 1.33 | 0.00 | 0.00 |
November | 21.00 | 0.00 | 21.00 | 13.85 | 76.80 | 0.00 | 0.00 | 0.00 |
December | 18.15 | 0.00 | 18.15 | 4.46 | 105.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.91 | 0.64 | 31.27 | 44.93 | 53.28 | 5.17 | 0.00 | 0.00 |
Minimum of Months | 18.15 | 0.00 | 18.15 | 3.26 | 2.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.63 | 3.19 | 45.44 | 99.75 | 133.05 | 3.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.12 | 38.65 | 44.47 | 69.17 | 231.99 | 0.00 | 0.00 | 0.00 |
February | 95.23 | 44.63 | 50.60 | 101.37 | 187.86 | 2.83 | 0.00 | 0.00 |
March | 139.71 | 67.38 | 72.33 | 180.49 | 109.48 | 0.00 | 0.00 | 0.00 |
April | 157.43 | 72.01 | 85.43 | 233.31 | 83.87 | 0.00 | 0.00 | 0.00 |
May | 158.41 | 60.12 | 98.28 | 259.02 | 48.71 | 0.00 | 0.00 | 0.00 |
June | 166.42 | 64.08 | 102.34 | 310.97 | 22.25 | 0.00 | 0.00 | 0.00 |
July | 156.65 | 57.94 | 98.71 | 307.87 | 10.89 | 0.00 | 0.00 | 0.00 |
August | 153.87 | 57.55 | 96.32 | 305.93 | 5.25 | 0.00 | 0.00 | 0.00 |
September | 125.70 | 52.55 | 73.15 | 216.42 | 33.01 | 0.00 | 0.00 | 0.00 |
October | 111.85 | 58.15 | 53.69 | 160.67 | 95.89 | 1.33 | 0.00 | 0.00 |
November | 88.83 | 39.72 | 49.11 | 107.31 | 139.77 | 0.00 | 0.00 | 0.00 |
December | 73.57 | 32.23 | 41.35 | 68.34 | 188.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.06 | 53.79 | 72.27 | 193.90 | 95.97 | 4.17 | 0.00 | 0.00 |
Minimum of Months | 73.57 | 32.23 | 41.35 | 68.34 | 5.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 166.42 | 72.01 | 102.34 | 310.97 | 231.99 | 2.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.89 | 106.21 | 46.68 | 169.47 | 171.67 | 0.00 | 0.00 | 0.00 |
February | 142.42 | 95.01 | 47.41 | 173.08 | 140.98 | 0.00 | 0.00 | 0.00 |
March | 130.23 | 68.34 | 61.89 | 178.31 | 85.12 | 0.00 | 0.00 | 0.00 |
April | 98.01 | 32.70 | 65.31 | 153.62 | 63.84 | 0.00 | 0.00 | 0.00 |
May | 78.78 | 9.64 | 69.14 | 136.76 | 34.16 | 0.00 | 0.00 | 0.00 |
June | 72.34 | 4.04 | 68.30 | 154.45 | 14.88 | 0.00 | 0.00 | 0.00 |
July | 72.57 | 4.89 | 67.67 | 164.94 | 6.64 | 0.00 | 0.00 | 0.00 |
August | 87.44 | 16.43 | 71.00 | 196.93 | 3.06 | 0.00 | 0.00 | 0.00 |
September | 98.72 | 38.41 | 60.31 | 180.82 | 23.50 | 0.00 | 0.00 | 0.00 |
October | 138.62 | 89.59 | 49.02 | 209.58 | 73.23 | 0.00 | 0.00 | 0.00 |
November | 151.44 | 101.06 | 50.39 | 202.65 | 106.51 | 0.00 | 0.00 | 0.00 |
December | 151.81 | 106.80 | 45.02 | 181.65 | 140.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 114.48 | 55.91 | 58.58 | 175.23 | 71.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.34 | 4.04 | 45.02 | 136.76 | 3.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.89 | 106.80 | 71.00 | 209.58 | 171.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.44 | 0.00 | 137.44 | 12.63 | 1142.42 | 0.00 | 0.00 | 0.00 |
February | 152.33 | 0.00 | 152.33 | 54.22 | 927.13 | 0.00 | 0.00 | 0.00 |
March | 213.92 | 0.00 | 213.92 | 134.98 | 544.12 | 0.00 | 0.00 | 0.00 |
April | 259.38 | 1.51 | 257.87 | 284.05 | 396.24 | 0.00 | 0.00 | 0.00 |
May | 309.48 | 9.71 | 299.77 | 445.68 | 233.12 | 0.00 | 0.00 | 0.00 |
June | 340.37 | 22.32 | 318.05 | 644.10 | 126.86 | 0.00 | 0.00 | 0.00 |
July | 322.35 | 16.52 | 305.83 | 654.23 | 82.11 | 0.00 | 0.00 | 0.00 |
August | 286.31 | 3.36 | 282.94 | 596.44 | 61.49 | 0.00 | 0.00 | 0.00 |
September | 216.12 | 0.08 | 216.03 | 339.47 | 190.53 | 0.00 | 0.00 | 0.00 |
October | 164.21 | 0.00 | 164.21 | 143.09 | 480.58 | 0.00 | 0.00 | 0.00 |
November | 146.96 | 0.00 | 146.96 | 65.16 | 688.96 | 0.00 | 0.00 | 0.00 |
December | 127.05 | 0.00 | 127.05 | 12.85 | 937.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 223.38 | 4.48 | 218.90 | 283.56 | 482.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.05 | 0.00 | 127.05 | 12.63 | 61.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 340.37 | 22.32 | 318.05 | 654.23 | 1142.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.44 | 0.00 | 137.44 | 10.87 | 1179.63 | 0.00 | 0.00 | 0.00 |
February | 152.33 | 0.00 | 152.33 | 49.59 | 958.55 | 0.00 | 0.00 | 0.00 |
March | 213.92 | 0.00 | 213.92 | 124.83 | 563.99 | 0.00 | 0.00 | 0.00 |
April | 259.38 | 1.51 | 257.87 | 272.60 | 408.85 | 0.00 | 0.00 | 0.00 |
May | 309.48 | 9.71 | 299.77 | 434.43 | 241.42 | 0.00 | 0.00 | 0.00 |
June | 340.37 | 22.32 | 318.05 | 634.05 | 132.20 | 0.00 | 0.00 | 0.00 |
July | 322.35 | 16.52 | 305.83 | 644.53 | 86.70 | 0.00 | 0.00 | 0.00 |
August | 286.31 | 3.36 | 282.94 | 587.04 | 65.96 | 0.00 | 0.00 | 0.00 |
September | 216.12 | 0.08 | 216.03 | 330.00 | 199.39 | 0.00 | 0.00 | 0.00 |
October | 164.21 | 0.00 | 164.21 | 134.87 | 498.71 | 0.00 | 0.00 | 0.00 |
November | 146.96 | 0.00 | 146.96 | 57.65 | 713.73 | 0.00 | 0.00 | 0.00 |
December | 127.05 | 0.00 | 127.05 | 10.51 | 971.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 223.38 | 4.48 | 218.90 | 275.55 | 499.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.05 | 0.00 | 127.05 | 10.51 | 65.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 340.37 | 22.32 | 318.05 | 644.53 | 1179.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.63 | 0.00 | 19.63 | 3.00 | 150.86 | 0.00 | 0.00 | 0.00 |
February | 21.76 | 0.00 | 21.76 | 11.13 | 122.09 | 0.00 | 0.00 | 0.00 |
March | 30.56 | 0.00 | 30.56 | 28.42 | 70.97 | 0.00 | 0.00 | 0.00 |
April | 37.06 | 0.22 | 36.84 | 55.30 | 52.13 | 0.00 | 0.00 | 0.00 |
May | 44.21 | 1.39 | 42.83 | 83.55 | 31.83 | 0.00 | 0.00 | 0.00 |
June | 48.63 | 3.19 | 45.44 | 114.89 | 18.70 | 0.00 | 0.00 | 0.00 |
July | 46.05 | 2.36 | 43.69 | 117.72 | 12.32 | 0.00 | 0.00 | 0.00 |
August | 40.90 | 0.48 | 40.42 | 109.23 | 9.40 | 0.00 | 0.00 | 0.00 |
September | 30.88 | 0.01 | 30.86 | 66.80 | 24.08 | 0.00 | 0.00 | 0.00 |
October | 23.46 | 0.00 | 23.46 | 30.52 | 61.19 | 0.00 | 0.00 | 0.00 |
November | 21.00 | 0.00 | 21.00 | 15.77 | 88.64 | 0.00 | 0.00 | 0.00 |
December | 18.15 | 0.00 | 18.15 | 3.76 | 121.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.91 | 0.64 | 31.27 | 53.58 | 63.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.15 | 0.00 | 18.15 | 3.00 | 9.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.63 | 3.19 | 45.44 | 117.72 | 150.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 162.23 | 73.86 | 88.36 | 114.72 | 509.06 | 0.00 | 0.00 | 0.00 |
February | 203.60 | 109.60 | 94.00 | 208.07 | 411.01 | 0.00 | 0.00 | 0.00 |
March | 256.16 | 116.85 | 139.31 | 331.42 | 244.01 | 0.00 | 0.00 | 0.00 |
April | 309.65 | 141.33 | 168.31 | 494.29 | 184.56 | 0.00 | 0.00 | 0.00 |
May | 339.21 | 143.45 | 195.76 | 611.02 | 117.89 | 0.00 | 0.00 | 0.00 |
June | 350.85 | 146.95 | 203.90 | 719.61 | 69.74 | 0.00 | 0.00 | 0.00 |
July | 341.97 | 143.47 | 198.50 | 731.85 | 46.38 | 0.00 | 0.00 | 0.00 |
August | 313.43 | 124.33 | 189.10 | 688.31 | 35.37 | 0.00 | 0.00 | 0.00 |
September | 256.88 | 113.51 | 143.37 | 496.45 | 88.63 | 0.00 | 0.00 | 0.00 |
October | 219.71 | 114.36 | 105.35 | 332.24 | 214.73 | 0.00 | 0.00 | 0.00 |
November | 174.98 | 78.93 | 96.05 | 199.99 | 299.77 | 0.00 | 0.00 | 0.00 |
December | 151.85 | 69.12 | 82.73 | 117.87 | 407.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 256.97 | 114.63 | 142.34 | 421.61 | 218.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 151.85 | 69.12 | 82.73 | 114.72 | 35.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 350.85 | 146.95 | 203.90 | 731.85 | 509.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.25 | 72.42 | 31.83 | 122.30 | 124.47 | 0.00 | 0.00 | 0.00 |
February | 97.11 | 64.78 | 32.32 | 125.01 | 104.49 | 0.00 | 0.00 | 0.00 |
March | 88.80 | 46.60 | 42.20 | 131.33 | 66.89 | 0.00 | 0.00 | 0.00 |
April | 66.83 | 22.30 | 44.53 | 115.83 | 52.50 | 0.00 | 0.00 | 0.00 |
May | 53.72 | 6.57 | 47.15 | 106.08 | 32.86 | 0.00 | 0.00 | 0.00 |
June | 49.32 | 2.75 | 46.57 | 118.38 | 19.40 | 0.00 | 0.00 | 0.00 |
July | 49.48 | 3.34 | 46.14 | 125.80 | 12.45 | 0.00 | 0.00 | 0.00 |
August | 59.62 | 11.20 | 48.41 | 148.22 | 9.41 | 0.00 | 0.00 | 0.00 |
September | 67.31 | 26.19 | 41.12 | 137.23 | 23.82 | 0.00 | 0.00 | 0.00 |
October | 94.52 | 61.09 | 33.43 | 154.54 | 57.70 | 0.00 | 0.00 | 0.00 |
November | 103.26 | 68.91 | 34.36 | 148.62 | 78.94 | 0.00 | 0.00 | 0.00 |
December | 103.51 | 72.82 | 30.70 | 131.44 | 103.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.06 | 38.12 | 39.94 | 130.45 | 56.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.32 | 2.75 | 30.70 | 106.08 | 9.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.25 | 72.82 | 48.41 | 154.54 | 124.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.87 | 0.00 | 24.87 | 3.10 | 187.06 | 0.00 | 0.00 | 0.00 |
February | 27.56 | 0.00 | 27.56 | 11.80 | 148.48 | 0.00 | 0.00 | 0.00 |
March | 38.70 | 0.00 | 38.70 | 28.92 | 83.53 | 0.00 | 0.00 | 0.00 |
April | 46.93 | 0.27 | 46.65 | 56.27 | 62.33 | 0.00 | 0.00 | 0.00 |
May | 55.99 | 1.76 | 54.24 | 84.83 | 37.15 | 0.00 | 0.00 | 0.00 |
June | 61.58 | 4.04 | 57.54 | 118.10 | 21.27 | 0.00 | 0.00 | 0.00 |
July | 58.32 | 2.99 | 55.33 | 118.83 | 13.67 | 0.00 | 0.00 | 0.00 |
August | 51.80 | 0.61 | 51.19 | 107.57 | 10.44 | 0.00 | 0.00 | 0.00 |
September | 39.10 | 0.02 | 39.09 | 63.63 | 30.32 | 0.00 | 0.00 | 0.00 |
October | 29.71 | 0.00 | 29.71 | 28.90 | 74.51 | 0.00 | 0.00 | 0.00 |
November | 26.59 | 0.00 | 26.59 | 14.97 | 107.43 | 0.00 | 0.00 | 0.00 |
December | 22.99 | 0.00 | 22.99 | 3.50 | 148.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.42 | 0.81 | 39.60 | 53.60 | 76.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.99 | 0.00 | 22.99 | 3.10 | 10.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.58 | 4.04 | 57.54 | 118.83 | 187.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.25 | 0.00 | 22.25 | 2.77 | 167.36 | 0.00 | 0.00 | 0.00 |
February | 24.66 | 0.00 | 24.66 | 10.56 | 132.84 | 0.00 | 0.00 | 0.00 |
March | 34.63 | 0.00 | 34.63 | 25.88 | 74.74 | 0.00 | 0.00 | 0.00 |
April | 41.99 | 0.25 | 41.74 | 50.34 | 55.77 | 0.00 | 0.00 | 0.00 |
May | 50.10 | 1.57 | 48.53 | 75.89 | 33.23 | 0.00 | 0.00 | 0.00 |
June | 55.10 | 3.61 | 51.48 | 105.67 | 19.03 | 0.00 | 0.00 | 0.00 |
July | 52.18 | 2.67 | 49.51 | 106.32 | 12.23 | 0.00 | 0.00 | 0.00 |
August | 46.35 | 0.54 | 45.80 | 96.24 | 9.34 | 0.00 | 0.00 | 0.00 |
September | 34.98 | 0.01 | 34.97 | 56.93 | 27.12 | 0.00 | 0.00 | 0.00 |
October | 26.58 | 0.00 | 26.58 | 25.85 | 66.67 | 0.00 | 0.00 | 0.00 |
November | 23.79 | 0.00 | 23.79 | 13.40 | 96.12 | 0.00 | 0.00 | 0.00 |
December | 20.57 | 0.00 | 20.57 | 3.13 | 133.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.16 | 0.73 | 35.43 | 47.96 | 68.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.57 | 0.00 | 20.57 | 2.77 | 9.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 55.10 | 3.61 | 51.48 | 106.32 | 167.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 389.19 | 270.36 | 118.83 | 440.21 | 449.45 | 0.00 | 0.00 | 0.00 |
February | 362.53 | 241.86 | 120.67 | 448.72 | 371.27 | 0.00 | 0.00 | 0.00 |
March | 331.52 | 173.96 | 157.55 | 460.00 | 230.47 | 0.00 | 0.00 | 0.00 |
April | 249.49 | 83.24 | 166.25 | 388.06 | 186.00 | 0.00 | 0.00 | 0.00 |
May | 200.55 | 24.54 | 176.01 | 334.11 | 116.36 | 0.00 | 0.00 | 0.00 |
June | 184.14 | 10.28 | 173.86 | 361.70 | 67.65 | 0.00 | 0.00 | 0.00 |
July | 184.72 | 12.46 | 172.26 | 381.95 | 42.33 | 0.00 | 0.00 | 0.00 |
August | 222.58 | 41.83 | 180.75 | 461.87 | 31.57 | 0.00 | 0.00 | 0.00 |
September | 251.29 | 97.77 | 153.51 | 445.12 | 89.00 | 0.00 | 0.00 | 0.00 |
October | 352.86 | 228.06 | 124.79 | 536.58 | 205.32 | 0.00 | 0.00 | 0.00 |
November | 385.51 | 257.25 | 128.26 | 526.98 | 279.10 | 0.00 | 0.00 | 0.00 |
December | 386.45 | 271.85 | 114.60 | 472.32 | 367.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 291.42 | 142.31 | 149.11 | 438.13 | 202.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 184.14 | 10.28 | 114.60 | 334.11 | 31.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 389.19 | 271.85 | 180.75 | 536.58 | 449.45 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141220E+10 | 0.981020E+09 | 0.431183E+09 | 0.162977E+10 | 0.150036E+10 |
February | 0.118818E+10 | 0.792686E+09 | 0.395494E+09 | 0.149132E+10 | 0.112779E+10 |
March | 0.120293E+10 | 0.631243E+09 | 0.571687E+09 | 0.168036E+10 | 0.805313E+09 |
April | 0.876087E+09 | 0.292293E+09 | 0.583795E+09 | 0.137750E+10 | 0.616431E+09 |
May | 0.727706E+09 | 89053889.35 | 0.638652E+09 | 0.122999E+10 | 0.393442E+09 |
June | 0.646621E+09 | 36100811.87 | 0.610520E+09 | 0.126605E+10 | 0.229470E+09 |
July | 0.670261E+09 | 45210453.17 | 0.625050E+09 | 0.137328E+10 | 0.150329E+09 |
August | 0.807634E+09 | 0.151787E+09 | 0.655847E+09 | 0.165234E+10 | 0.123464E+09 |
September | 0.882405E+09 | 0.343335E+09 | 0.539070E+09 | 0.155517E+10 | 0.308166E+09 |
October | 0.128037E+10 | 0.827554E+09 | 0.452812E+09 | 0.193755E+10 | 0.725098E+09 |
November | 0.135373E+10 | 0.903351E+09 | 0.450383E+09 | 0.184455E+10 | 0.945180E+09 |
December | 0.140226E+10 | 0.986443E+09 | 0.415820E+09 | 0.173276E+10 | 0.124815E+10 |
Annual Sum or Average | 0.124504E+11 | 0.608008E+10 | 0.637031E+10 | 0.187706E+11 | 0.817320E+10 |
Minimum of Months | 0.646621E+09 | 36100811.87 | 0.395494E+09 | 0.122999E+10 | 0.123464E+09 |
Maximum of Months | 0.141220E+10 | 0.986443E+09 | 0.655847E+09 | 0.193755E+10 | 0.150036E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.397667E+10 | 0.276249E+10 | 0.121418E+10 | 0.449750E+10 | 0.447503E+10 |
February | 0.334584E+10 | 0.223215E+10 | 0.111368E+10 | 0.411700E+10 | 0.342021E+10 |
March | 0.338737E+10 | 0.177754E+10 | 0.160983E+10 | 0.462965E+10 | 0.252332E+10 |
April | 0.246700E+10 | 0.823077E+09 | 0.164393E+10 | 0.379207E+10 | 0.193060E+10 |
May | 0.204917E+10 | 0.250770E+09 | 0.179840E+10 | 0.339131E+10 | 0.125364E+10 |
June | 0.182084E+10 | 0.101658E+09 | 0.171918E+10 | 0.354762E+10 | 0.703165E+09 |
July | 0.188741E+10 | 0.127310E+09 | 0.176010E+10 | 0.386208E+10 | 0.464170E+09 |
August | 0.227424E+10 | 0.427422E+09 | 0.184682E+10 | 0.465157E+10 | 0.368730E+09 |
September | 0.248479E+10 | 0.966809E+09 | 0.151798E+10 | 0.433127E+10 | 0.972522E+09 |
October | 0.360543E+10 | 0.233034E+10 | 0.127509E+10 | 0.537362E+10 | 0.226609E+10 |
November | 0.381203E+10 | 0.254378E+10 | 0.126825E+10 | 0.508669E+10 | 0.294073E+10 |
December | 0.394868E+10 | 0.277776E+10 | 0.117092E+10 | 0.478009E+10 | 0.379672E+10 |
Annual Sum or Average | 0.350595E+11 | 0.171211E+11 | 0.179384E+11 | 0.520605E+11 | 0.251149E+11 |
Minimum of Months | 0.182084E+10 | 0.101658E+09 | 0.111368E+10 | 0.339131E+10 | 0.368730E+09 |
Maximum of Months | 0.397667E+10 | 0.277776E+10 | 0.184682E+10 | 0.537362E+10 | 0.447503E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.516592E+10 | 0.358863E+10 | 0.157729E+10 | 0.594571E+10 | 0.605540E+10 |
February | 0.434643E+10 | 0.289969E+10 | 0.144674E+10 | 0.545427E+10 | 0.461894E+10 |
March | 0.440039E+10 | 0.230912E+10 | 0.209126E+10 | 0.614388E+10 | 0.337718E+10 |
April | 0.320478E+10 | 0.106922E+10 | 0.213555E+10 | 0.502749E+10 | 0.259731E+10 |
May | 0.266199E+10 | 0.325764E+09 | 0.233623E+10 | 0.449662E+10 | 0.168080E+10 |
June | 0.236538E+10 | 0.132059E+09 | 0.223332E+10 | 0.471730E+10 | 0.932391E+09 |
July | 0.245185E+10 | 0.165382E+09 | 0.228647E+10 | 0.514965E+10 | 0.610638E+09 |
August | 0.295437E+10 | 0.555246E+09 | 0.239913E+10 | 0.621952E+10 | 0.470401E+09 |
September | 0.322789E+10 | 0.125594E+10 | 0.197195E+10 | 0.575140E+10 | 0.129026E+10 |
October | 0.468365E+10 | 0.302724E+10 | 0.165641E+10 | 0.712797E+10 | 0.303627E+10 |
November | 0.495204E+10 | 0.330451E+10 | 0.164753E+10 | 0.672778E+10 | 0.395094E+10 |
December | 0.512956E+10 | 0.360846E+10 | 0.152109E+10 | 0.631584E+10 | 0.513958E+10 |
Annual Sum or Average | 0.455443E+11 | 0.222413E+11 | 0.233030E+11 | 0.690774E+11 | 0.337601E+11 |
Minimum of Months | 0.236538E+10 | 0.132059E+09 | 0.144674E+10 | 0.449662E+10 | 0.470401E+09 |
Maximum of Months | 0.516592E+10 | 0.360846E+10 | 0.239913E+10 | 0.712797E+10 | 0.605540E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279218E+09 | 0.193965E+09 | 85252967.91 | 0.324110E+09 | 0.302029E+09 |
February | 0.234924E+09 | 0.156728E+09 | 78196598.94 | 0.296398E+09 | 0.224605E+09 |
March | 0.237841E+09 | 0.124808E+09 | 0.113033E+09 | 0.332847E+09 | 0.154352E+09 |
April | 0.173219E+09 | 57791307.85 | 0.115427E+09 | 0.273587E+09 | 0.115367E+09 |
May | 0.143881E+09 | 17607483.41 | 0.126274E+09 | 0.248166E+09 | 65981819.25 |
June | 0.127849E+09 | 7137750.53 | 0.120712E+09 | 0.267571E+09 | 29831497.76 |
July | 0.132523E+09 | 8938883.07 | 0.123585E+09 | 0.294999E+09 | 14802470.18 |
August | 0.159684E+09 | 30010917.68 | 0.129673E+09 | 0.354231E+09 | 7504514.97 |
September | 0.174468E+09 | 67883271.16 | 0.106584E+09 | 0.319683E+09 | 44098009.54 |
October | 0.253151E+09 | 0.163622E+09 | 89529587.28 | 0.389354E+09 | 0.132554E+09 |
November | 0.267657E+09 | 0.178608E+09 | 89049108.36 | 0.368585E+09 | 0.182476E+09 |
December | 0.277252E+09 | 0.195037E+09 | 82215273.99 | 0.345746E+09 | 0.247287E+09 |
Annual Sum or Average | 0.246167E+10 | 0.120214E+10 | 0.125953E+10 | 0.381528E+10 | 0.152089E+10 |
Minimum of Months | 0.127849E+09 | 7137750.53 | 78196598.94 | 0.248166E+09 | 7504514.97 |
Maximum of Months | 0.279218E+09 | 0.195037E+09 | 0.129673E+09 | 0.389354E+09 | 0.302029E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222627E+09 | 0.103516E+09 | 0.119111E+09 | 0.175122E+09 | 0.636324E+09 |
February | 0.230374E+09 | 0.107973E+09 | 0.122401E+09 | 0.237787E+09 | 0.465501E+09 |
March | 0.374198E+09 | 0.180474E+09 | 0.193725E+09 | 0.480806E+09 | 0.298615E+09 |
April | 0.408065E+09 | 0.186640E+09 | 0.221425E+09 | 0.611059E+09 | 0.212360E+09 |
May | 0.424277E+09 | 0.161030E+09 | 0.263246E+09 | 0.707390E+09 | 0.122138E+09 |
June | 0.431370E+09 | 0.166096E+09 | 0.265273E+09 | 0.819399E+09 | 55312649.69 |
July | 0.419570E+09 | 0.155192E+09 | 0.264378E+09 | 0.836965E+09 | 27375015.87 |
August | 0.412124E+09 | 0.154141E+09 | 0.257983E+09 | 0.827615E+09 | 13953033.71 |
September | 0.325820E+09 | 0.136209E+09 | 0.189611E+09 | 0.565473E+09 | 82588084.90 |
October | 0.299566E+09 | 0.155754E+09 | 0.143812E+09 | 0.426501E+09 | 0.260887E+09 |
November | 0.230249E+09 | 0.102964E+09 | 0.127285E+09 | 0.267153E+09 | 0.375352E+09 |
December | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.170381E+09 | 0.521096E+09 |
Annual Sum or Average | 0.397530E+10 | 0.169631E+10 | 0.227899E+10 | 0.612565E+10 | 0.307150E+10 |
Minimum of Months | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.170381E+09 | 13953033.71 |
Maximum of Months | 0.431370E+09 | 0.186640E+09 | 0.265273E+09 | 0.836965E+09 | 0.636324E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52588594.07 | 0.00 | 52588594.07 | 8352702.70 | 0.358685E+09 |
February | 52648446.06 | 0.00 | 52648446.06 | 25409120.88 | 0.259227E+09 |
March | 81855013.60 | 1648.52 | 81853365.08 | 64240050.18 | 0.165401E+09 |
April | 96048332.89 | 560963.03 | 95487369.87 | 0.117620E+09 | 0.118165E+09 |
May | 0.118419E+09 | 3714011.78 | 0.114705E+09 | 0.184437E+09 | 67257544.55 |
June | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.254661E+09 | 29974321.82 |
July | 0.123345E+09 | 6320378.90 | 0.117025E+09 | 0.268380E+09 | 16222763.41 |
August | 0.109554E+09 | 1287040.28 | 0.108267E+09 | 0.247329E+09 | 8371209.24 |
September | 80028430.11 | 31459.51 | 79996970.60 | 0.138279E+09 | 48132723.78 |
October | 62833545.17 | 0.00 | 62833545.17 | 65360725.98 | 0.143475E+09 |
November | 54419711.70 | 0.00 | 54419711.70 | 34876499.95 | 0.202508E+09 |
December | 48614241.33 | 0.00 | 48614241.33 | 11009365.71 | 0.285277E+09 |
Annual Sum or Average | 0.100639E+10 | 20181056.73 | 0.986211E+09 | 0.141995E+10 | 0.170270E+10 |
Minimum of Months | 48614241.33 | 0.00 | 48614241.33 | 8352702.70 | 8371209.24 |
Maximum of Months | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.268380E+09 | 0.358685E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222627E+09 | 0.103516E+09 | 0.119111E+09 | 0.184949E+09 | 0.624902E+09 |
February | 0.230374E+09 | 0.107973E+09 | 0.122401E+09 | 0.245799E+09 | 0.458525E+09 |
March | 0.374198E+09 | 0.180474E+09 | 0.193725E+09 | 0.486501E+09 | 0.297856E+09 |
April | 0.408065E+09 | 0.186640E+09 | 0.221425E+09 | 0.610190E+09 | 0.219123E+09 |
May | 0.424277E+09 | 0.161030E+09 | 0.263246E+09 | 0.700671E+09 | 0.131744E+09 |
June | 0.431370E+09 | 0.166096E+09 | 0.265273E+09 | 0.811737E+09 | 59906523.12 |
July | 0.419570E+09 | 0.155192E+09 | 0.264378E+09 | 0.829297E+09 | 31192531.75 |
August | 0.412124E+09 | 0.154141E+09 | 0.257983E+09 | 0.823763E+09 | 15818149.77 |
September | 0.325820E+09 | 0.136209E+09 | 0.189611E+09 | 0.563923E+09 | 89062202.84 |
October | 0.299566E+09 | 0.155754E+09 | 0.143812E+09 | 0.431914E+09 | 0.262489E+09 |
November | 0.230249E+09 | 0.102964E+09 | 0.127285E+09 | 0.277770E+09 | 0.368477E+09 |
December | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.181642E+09 | 0.509768E+09 |
Annual Sum or Average | 0.397530E+10 | 0.169631E+10 | 0.227899E+10 | 0.614816E+10 | 0.306886E+10 |
Minimum of Months | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.181642E+09 | 15818149.77 |
Maximum of Months | 0.431370E+09 | 0.186640E+09 | 0.265273E+09 | 0.829297E+09 | 0.624902E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223330E+09 | 0.155141E+09 | 68188813.41 | 0.240815E+09 | 0.276745E+09 |
February | 0.187902E+09 | 0.125357E+09 | 62544840.67 | 0.214479E+09 | 0.232251E+09 |
March | 0.190235E+09 | 99826196.68 | 90408627.06 | 0.231241E+09 | 0.190662E+09 |
April | 0.138547E+09 | 46223853.60 | 92323562.43 | 0.185444E+09 | 0.150049E+09 |
May | 0.115082E+09 | 14083185.96 | 0.100999E+09 | 0.161437E+09 | 0.104146E+09 |
June | 0.102259E+09 | 5709065.05 | 96550134.41 | 0.172154E+09 | 63450135.28 |
July | 0.105998E+09 | 7149684.58 | 98847981.78 | 0.189687E+09 | 48206738.18 |
August | 0.127722E+09 | 24003960.40 | 0.103718E+09 | 0.236078E+09 | 41812497.21 |
September | 0.139546E+09 | 54295818.95 | 85250458.26 | 0.220060E+09 | 85475515.84 |
October | 0.202481E+09 | 0.130871E+09 | 71609428.64 | 0.278393E+09 | 0.173639E+09 |
November | 0.214083E+09 | 0.142858E+09 | 71225121.93 | 0.260931E+09 | 0.217475E+09 |
December | 0.221757E+09 | 0.155998E+09 | 65759141.47 | 0.245593E+09 | 0.268731E+09 |
Annual Sum or Average | 0.196894E+10 | 0.961517E+09 | 0.100743E+10 | 0.263631E+10 | 0.185264E+10 |
Minimum of Months | 0.102259E+09 | 5709065.05 | 62544840.67 | 0.161437E+09 | 41812497.21 |
Maximum of Months | 0.223330E+09 | 0.155998E+09 | 0.103718E+09 | 0.278393E+09 | 0.276745E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42076451.99 | 0.00 | 42076451.99 | 5897974.58 | 0.301561E+09 |
February | 42124339.93 | 0.00 | 42124339.93 | 20016960.96 | 0.216430E+09 |
March | 65492691.15 | 1318.99 | 65491372.16 | 53897000.52 | 0.132021E+09 |
April | 76848851.72 | 448829.91 | 76400021.81 | 99517047.38 | 91763245.30 |
May | 94747450.04 | 2971603.27 | 91775846.77 | 0.155421E+09 | 50377894.65 |
June | 0.100844E+09 | 6613320.29 | 94230889.24 | 0.214282E+09 | 20594242.88 |
July | 98689421.90 | 5056973.36 | 93632448.53 | 0.226604E+09 | 10359055.44 |
August | 87654522.95 | 1029768.70 | 86624754.24 | 0.211134E+09 | 4453437.61 |
September | 64031230.67 | 25170.94 | 64006059.72 | 0.117809E+09 | 35371851.01 |
October | 50273499.29 | 0.00 | 50273499.29 | 55226828.84 | 0.114302E+09 |
November | 43541540.27 | 0.00 | 43541540.27 | 27718443.46 | 0.166988E+09 |
December | 38896548.34 | 0.00 | 38896548.34 | 7458715.25 | 0.240031E+09 |
Annual Sum or Average | 0.805221E+09 | 16146985.47 | 0.789074E+09 | 0.119498E+10 | 0.138425E+10 |
Minimum of Months | 38896548.34 | 0.00 | 38896548.34 | 5897974.58 | 4453437.61 |
Maximum of Months | 0.100844E+09 | 6613320.29 | 94230889.24 | 0.226604E+09 | 0.301561E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217269E+09 | 98926312.94 | 0.118343E+09 | 0.149562E+09 | 0.618286E+09 |
February | 0.246295E+09 | 0.132584E+09 | 0.113711E+09 | 0.239243E+09 | 0.440316E+09 |
March | 0.343073E+09 | 0.156492E+09 | 0.186581E+09 | 0.407058E+09 | 0.277313E+09 |
April | 0.401332E+09 | 0.183183E+09 | 0.218149E+09 | 0.583795E+09 | 0.195876E+09 |
May | 0.454306E+09 | 0.192122E+09 | 0.262184E+09 | 0.746321E+09 | 0.112758E+09 |
June | 0.454739E+09 | 0.190467E+09 | 0.264272E+09 | 0.854632E+09 | 50393000.41 |
July | 0.458002E+09 | 0.192153E+09 | 0.265848E+09 | 0.899127E+09 | 26340722.09 |
August | 0.419782E+09 | 0.166515E+09 | 0.253266E+09 | 0.841960E+09 | 13115156.12 |
September | 0.332940E+09 | 0.147113E+09 | 0.185827E+09 | 0.574963E+09 | 78590581.46 |
October | 0.294256E+09 | 0.153163E+09 | 0.141093E+09 | 0.399260E+09 | 0.243594E+09 |
November | 0.226791E+09 | 0.102303E+09 | 0.124488E+09 | 0.233038E+09 | 0.346691E+09 |
December | 0.203367E+09 | 92572432.32 | 0.110794E+09 | 0.151260E+09 | 0.490859E+09 |
Annual Sum or Average | 0.405215E+10 | 0.180759E+10 | 0.224456E+10 | 0.608022E+10 | 0.289413E+10 |
Minimum of Months | 0.203367E+09 | 92572432.32 | 0.110794E+09 | 0.149562E+09 | 13115156.12 |
Maximum of Months | 0.458002E+09 | 0.192153E+09 | 0.265848E+09 | 0.899127E+09 | 0.618286E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279218E+09 | 0.193965E+09 | 85252967.91 | 0.322511E+09 | 0.301278E+09 |
February | 0.234924E+09 | 0.156728E+09 | 78196598.94 | 0.294068E+09 | 0.224107E+09 |
March | 0.237841E+09 | 0.124808E+09 | 0.113033E+09 | 0.330680E+09 | 0.152943E+09 |
April | 0.173219E+09 | 57791307.85 | 0.115427E+09 | 0.271392E+09 | 0.114512E+09 |
May | 0.143881E+09 | 17607483.41 | 0.126274E+09 | 0.245914E+09 | 65478631.63 |
June | 0.127849E+09 | 7137750.53 | 0.120712E+09 | 0.265708E+09 | 29384228.64 |
July | 0.132523E+09 | 8938883.07 | 0.123585E+09 | 0.293316E+09 | 14574408.55 |
August | 0.159684E+09 | 30010917.68 | 0.129673E+09 | 0.353452E+09 | 7221880.16 |
September | 0.174468E+09 | 67883271.16 | 0.106584E+09 | 0.318531E+09 | 43580974.72 |
October | 0.253151E+09 | 0.163622E+09 | 89529587.28 | 0.387513E+09 | 0.131573E+09 |
November | 0.267657E+09 | 0.178608E+09 | 89049108.36 | 0.366970E+09 | 0.181666E+09 |
December | 0.277252E+09 | 0.195037E+09 | 82215273.99 | 0.344106E+09 | 0.246786E+09 |
Annual Sum or Average | 0.246167E+10 | 0.120214E+10 | 0.125953E+10 | 0.379416E+10 | 0.151310E+10 |
Minimum of Months | 0.127849E+09 | 7137750.53 | 78196598.94 | 0.245914E+09 | 7221880.16 |
Maximum of Months | 0.279218E+09 | 0.195037E+09 | 0.129673E+09 | 0.387513E+09 | 0.301278E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52588594.07 | 0.00 | 52588594.07 | 7942268.80 | 0.358883E+09 |
February | 52648446.06 | 0.00 | 52648446.06 | 24356004.13 | 0.259591E+09 |
March | 81855013.60 | 1648.52 | 81853365.08 | 63042805.12 | 0.163408E+09 |
April | 96048332.89 | 560963.03 | 95487369.87 | 0.115552E+09 | 0.116470E+09 |
May | 0.118419E+09 | 3714011.78 | 0.114705E+09 | 0.181472E+09 | 66156251.41 |
June | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.251289E+09 | 29363718.63 |
July | 0.123345E+09 | 6320378.90 | 0.117025E+09 | 0.265197E+09 | 16127181.88 |
August | 0.109554E+09 | 1287040.28 | 0.108267E+09 | 0.245685E+09 | 8055642.12 |
September | 80028430.11 | 31459.51 | 79996970.60 | 0.136291E+09 | 47486189.54 |
October | 62833545.17 | 0.00 | 62833545.17 | 63611914.05 | 0.141825E+09 |
November | 54419711.70 | 0.00 | 54419711.70 | 34198895.54 | 0.201194E+09 |
December | 48614241.33 | 0.00 | 48614241.33 | 10501746.12 | 0.285454E+09 |
Annual Sum or Average | 0.100639E+10 | 20181056.73 | 0.986211E+09 | 0.139914E+10 | 0.169401E+10 |
Minimum of Months | 48614241.33 | 0.00 | 48614241.33 | 7942268.80 | 8055642.12 |
Maximum of Months | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.265197E+09 | 0.358883E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217269E+09 | 98926312.94 | 0.118343E+09 | 0.155005E+09 | 0.602009E+09 |
February | 0.246295E+09 | 0.132584E+09 | 0.113711E+09 | 0.246293E+09 | 0.431465E+09 |
March | 0.343073E+09 | 0.156492E+09 | 0.186581E+09 | 0.414423E+09 | 0.274829E+09 |
April | 0.401332E+09 | 0.183183E+09 | 0.218149E+09 | 0.584080E+09 | 0.201551E+09 |
May | 0.454306E+09 | 0.192122E+09 | 0.262184E+09 | 0.738214E+09 | 0.121282E+09 |
June | 0.454739E+09 | 0.190467E+09 | 0.264272E+09 | 0.843222E+09 | 54370614.66 |
July | 0.458002E+09 | 0.192153E+09 | 0.265848E+09 | 0.887491E+09 | 29969891.91 |
August | 0.419782E+09 | 0.166515E+09 | 0.253266E+09 | 0.835722E+09 | 14653927.79 |
September | 0.332940E+09 | 0.147113E+09 | 0.185827E+09 | 0.571093E+09 | 84311437.78 |
October | 0.294256E+09 | 0.153163E+09 | 0.141093E+09 | 0.405195E+09 | 0.243573E+09 |
November | 0.226791E+09 | 0.102303E+09 | 0.124488E+09 | 0.244078E+09 | 0.337445E+09 |
December | 0.203367E+09 | 92572432.32 | 0.110794E+09 | 0.159334E+09 | 0.475483E+09 |
Annual Sum or Average | 0.405215E+10 | 0.180759E+10 | 0.224456E+10 | 0.608415E+10 | 0.287094E+10 |
Minimum of Months | 0.203367E+09 | 92572432.32 | 0.110794E+09 | 0.155005E+09 | 14653927.79 |
Maximum of Months | 0.458002E+09 | 0.192153E+09 | 0.265848E+09 | 0.887491E+09 | 0.602009E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66600136.23 | 0.00 | 66600136.23 | 9277484.95 | 0.489908E+09 |
February | 66675935.00 | 0.00 | 66675935.00 | 31020250.65 | 0.351297E+09 |
March | 0.103664E+09 | 2087.74 | 0.103662E+09 | 83152796.51 | 0.221537E+09 |
April | 0.121639E+09 | 710424.28 | 0.120929E+09 | 0.153148E+09 | 0.159668E+09 |
May | 0.149970E+09 | 4703561.58 | 0.145266E+09 | 0.238773E+09 | 94980715.43 |
June | 0.159620E+09 | 10467803.52 | 0.149152E+09 | 0.319692E+09 | 50434632.34 |
July | 0.156209E+09 | 8004361.08 | 0.148205E+09 | 0.331031E+09 | 33169037.74 |
August | 0.138743E+09 | 1629955.30 | 0.137113E+09 | 0.301265E+09 | 23661357.11 |
September | 0.101351E+09 | 39841.48 | 0.101311E+09 | 0.172427E+09 | 76178894.22 |
October | 79574720.39 | 0.00 | 79574720.39 | 81646269.99 | 0.198973E+09 |
November | 68919131.17 | 0.00 | 68919131.17 | 42530603.48 | 0.274341E+09 |
December | 61566869.25 | 0.00 | 61566869.25 | 11108714.89 | 0.389097E+09 |
Annual Sum or Average | 0.127453E+10 | 25558034.99 | 0.124897E+10 | 0.177507E+10 | 0.236324E+10 |
Minimum of Months | 61566869.25 | 0.00 | 61566869.25 | 9277484.95 | 23661357.11 |
Maximum of Months | 0.159620E+09 | 10467803.52 | 0.149152E+09 | 0.331031E+09 | 0.489908E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 24551567.91 | 0.00 | 24551567.91 | 3420065.10 | 0.180600E+09 |
February | 24579510.47 | 0.00 | 24579510.47 | 11435348.84 | 0.129503E+09 |
March | 38214920.19 | 769.63 | 38214150.56 | 30653563.88 | 81667714.13 |
April | 44841228.59 | 261891.81 | 44579336.78 | 56456730.10 | 58860274.86 |
May | 55285042.92 | 1733927.56 | 53551115.36 | 88021620.77 | 35013824.55 |
June | 58842496.02 | 3858865.82 | 54983630.20 | 0.117852E+09 | 18592293.81 |
July | 57585179.58 | 2950738.93 | 54634440.65 | 0.122032E+09 | 12227480.73 |
August | 51146327.01 | 600869.02 | 50545457.99 | 0.111059E+09 | 8722555.97 |
September | 37362159.44 | 14687.22 | 37347472.22 | 63563579.62 | 28082694.73 |
October | 29334536.86 | 0.00 | 29334536.86 | 30098195.83 | 73349572.15 |
November | 25406445.47 | 0.00 | 25406445.47 | 15678541.50 | 0.101133E+09 |
December | 22696097.29 | 0.00 | 22696097.29 | 4095132.29 | 0.143437E+09 |
Annual Sum or Average | 0.469846E+09 | 9421749.97 | 0.460424E+09 | 0.654365E+09 | 0.871190E+09 |
Minimum of Months | 22696097.29 | 0.00 | 22696097.29 | 3420065.10 | 8722555.97 |
Maximum of Months | 58842496.02 | 3858865.82 | 54983630.20 | 0.122032E+09 | 0.180600E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130282E+09 | 90503082.87 | 39778691.28 | 0.150237E+09 | 0.147815E+09 |
February | 0.109615E+09 | 73128454.63 | 36486217.96 | 0.138383E+09 | 0.109918E+09 |
March | 0.110976E+09 | 58234705.39 | 52740862.99 | 0.157384E+09 | 76349021.03 |
April | 80823152.87 | 26965191.36 | 53857961.51 | 0.129102E+09 | 59401110.41 |
May | 67134435.80 | 8215580.81 | 58918854.99 | 0.116329E+09 | 37113109.19 |
June | 59654024.21 | 3330445.64 | 56323578.57 | 0.122187E+09 | 20036222.73 |
July | 61834899.83 | 4170846.82 | 57664053.01 | 0.132647E+09 | 12794914.98 |
August | 74508055.00 | 14002973.25 | 60505081.75 | 0.159822E+09 | 8894146.21 |
September | 81405849.48 | 31674060.78 | 49731788.71 | 0.147563E+09 | 27842852.67 |
October | 0.118119E+09 | 76345167.07 | 41774144.65 | 0.182360E+09 | 68431689.99 |
November | 0.124888E+09 | 83337782.51 | 41549955.12 | 0.173580E+09 | 89257590.22 |
December | 0.129365E+09 | 91003310.47 | 38361315.54 | 0.161221E+09 | 0.120458E+09 |
Annual Sum or Average | 0.114860E+10 | 0.560912E+09 | 0.587693E+09 | 0.177081E+10 | 0.778312E+09 |
Minimum of Months | 59654024.21 | 3330445.64 | 36486217.96 | 0.116329E+09 | 8894146.21 |
Maximum of Months | 0.130282E+09 | 91003310.47 | 60505081.75 | 0.182360E+09 | 0.147815E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353611E+09 | 0.245644E+09 | 0.107968E+09 | 0.407774E+09 | 0.401200E+09 |
February | 0.297517E+09 | 0.198486E+09 | 99031058.63 | 0.375600E+09 | 0.298340E+09 |
March | 0.301210E+09 | 0.158061E+09 | 0.143149E+09 | 0.427172E+09 | 0.207227E+09 |
April | 0.219371E+09 | 73189044.97 | 0.146182E+09 | 0.350410E+09 | 0.161227E+09 |
May | 0.182217E+09 | 22298766.77 | 0.159918E+09 | 0.315742E+09 | 0.100733E+09 |
June | 0.161913E+09 | 9039510.68 | 0.152874E+09 | 0.331640E+09 | 54382406.81 |
July | 0.167833E+09 | 11320531.40 | 0.156512E+09 | 0.360031E+09 | 34728016.40 |
August | 0.202230E+09 | 38006933.66 | 0.164223E+09 | 0.433788E+09 | 24140529.61 |
September | 0.220952E+09 | 85969879.73 | 0.134982E+09 | 0.400517E+09 | 75571197.27 |
October | 0.320600E+09 | 0.207216E+09 | 0.113384E+09 | 0.494962E+09 | 0.185738E+09 |
November | 0.338971E+09 | 0.226196E+09 | 0.112775E+09 | 0.471132E+09 | 0.242263E+09 |
December | 0.351122E+09 | 0.247002E+09 | 0.104120E+09 | 0.437586E+09 | 0.326948E+09 |
Annual Sum or Average | 0.311755E+10 | 0.152243E+10 | 0.159512E+10 | 0.480635E+10 | 0.211250E+10 |
Minimum of Months | 0.161913E+09 | 9039510.68 | 99031058.63 | 0.315742E+09 | 24140529.61 |
Maximum of Months | 0.353611E+09 | 0.247002E+09 | 0.164223E+09 | 0.494962E+09 | 0.401200E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279218E+09 | 0.193965E+09 | 85252967.91 | 0.323393E+09 | 0.300004E+09 |
February | 0.234924E+09 | 0.156728E+09 | 78196598.94 | 0.295205E+09 | 0.222687E+09 |
March | 0.237841E+09 | 0.124808E+09 | 0.113033E+09 | 0.330438E+09 | 0.152260E+09 |
April | 0.173219E+09 | 57791307.85 | 0.115427E+09 | 0.271186E+09 | 0.113839E+09 |
May | 0.143881E+09 | 17607483.41 | 0.126274E+09 | 0.245540E+09 | 64786177.05 |
June | 0.127849E+09 | 7137750.53 | 0.120712E+09 | 0.265956E+09 | 28621085.39 |
July | 0.132523E+09 | 8938883.07 | 0.123585E+09 | 0.293399E+09 | 13758666.46 |
August | 0.159684E+09 | 30010917.68 | 0.129673E+09 | 0.352414E+09 | 6660334.25 |
September | 0.174468E+09 | 67883271.16 | 0.106584E+09 | 0.317838E+09 | 42439148.67 |
October | 0.253151E+09 | 0.163622E+09 | 89529587.28 | 0.387228E+09 | 0.130114E+09 |
November | 0.267657E+09 | 0.178608E+09 | 89049108.36 | 0.367239E+09 | 0.180027E+09 |
December | 0.277252E+09 | 0.195037E+09 | 82215273.99 | 0.344857E+09 | 0.244830E+09 |
Annual Sum or Average | 0.246167E+10 | 0.120214E+10 | 0.125953E+10 | 0.379469E+10 | 0.150003E+10 |
Minimum of Months | 0.127849E+09 | 7137750.53 | 78196598.94 | 0.245540E+09 | 6660334.25 |
Maximum of Months | 0.279218E+09 | 0.195037E+09 | 0.129673E+09 | 0.387228E+09 | 0.300004E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222627E+09 | 0.103516E+09 | 0.119111E+09 | 0.175234E+09 | 0.632098E+09 |
February | 0.230374E+09 | 0.107973E+09 | 0.122401E+09 | 0.236843E+09 | 0.461042E+09 |
March | 0.374198E+09 | 0.180474E+09 | 0.193725E+09 | 0.476744E+09 | 0.294118E+09 |
April | 0.408065E+09 | 0.186640E+09 | 0.221425E+09 | 0.605762E+09 | 0.209372E+09 |
May | 0.424277E+09 | 0.161030E+09 | 0.263246E+09 | 0.700870E+09 | 0.119802E+09 |
June | 0.431370E+09 | 0.166096E+09 | 0.265273E+09 | 0.813575E+09 | 52863337.56 |
July | 0.419570E+09 | 0.155192E+09 | 0.264378E+09 | 0.832112E+09 | 25378055.98 |
August | 0.412124E+09 | 0.154141E+09 | 0.257983E+09 | 0.823030E+09 | 12381405.47 |
September | 0.325820E+09 | 0.136209E+09 | 0.189611E+09 | 0.562166E+09 | 79273634.87 |
October | 0.299566E+09 | 0.155754E+09 | 0.143812E+09 | 0.423800E+09 | 0.255640E+09 |
November | 0.230249E+09 | 0.102964E+09 | 0.127285E+09 | 0.266001E+09 | 0.370092E+09 |
December | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.170630E+09 | 0.515446E+09 |
Annual Sum or Average | 0.397530E+10 | 0.169631E+10 | 0.227899E+10 | 0.608677E+10 | 0.302751E+10 |
Minimum of Months | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.170630E+09 | 12381405.47 |
Maximum of Months | 0.431370E+09 | 0.186640E+09 | 0.265273E+09 | 0.832112E+09 | 0.632098E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52588594.07 | 0.00 | 52588594.07 | 8720222.16 | 0.356369E+09 |
February | 52648446.06 | 0.00 | 52648446.06 | 25935801.88 | 0.256946E+09 |
March | 81855013.60 | 1648.52 | 81853365.08 | 64476692.96 | 0.163066E+09 |
April | 96048332.89 | 560963.03 | 95487369.87 | 0.116622E+09 | 0.117377E+09 |
May | 0.118419E+09 | 3714011.78 | 0.114705E+09 | 0.182354E+09 | 66867368.49 |
June | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.253378E+09 | 29042978.04 |
July | 0.123345E+09 | 6320378.90 | 0.117025E+09 | 0.267157E+09 | 15361712.21 |
August | 0.109554E+09 | 1287040.28 | 0.108267E+09 | 0.246474E+09 | 7474062.28 |
September | 80028430.11 | 31459.51 | 79996970.60 | 0.137958E+09 | 46310603.28 |
October | 62833545.17 | 0.00 | 62833545.17 | 66020621.85 | 0.140526E+09 |
November | 54419711.70 | 0.00 | 54419711.70 | 35907729.09 | 0.199066E+09 |
December | 48614241.33 | 0.00 | 48614241.33 | 11940251.66 | 0.281676E+09 |
Annual Sum or Average | 0.100639E+10 | 20181056.73 | 0.986211E+09 | 0.141694E+10 | 0.168008E+10 |
Minimum of Months | 48614241.33 | 0.00 | 48614241.33 | 8720222.16 | 7474062.28 |
Maximum of Months | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.267157E+09 | 0.356369E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222627E+09 | 0.103516E+09 | 0.119111E+09 | 0.185266E+09 | 0.621351E+09 |
February | 0.230374E+09 | 0.107973E+09 | 0.122401E+09 | 0.245238E+09 | 0.454460E+09 |
March | 0.374198E+09 | 0.180474E+09 | 0.193725E+09 | 0.483423E+09 | 0.293239E+09 |
April | 0.408065E+09 | 0.186640E+09 | 0.221425E+09 | 0.604739E+09 | 0.217385E+09 |
May | 0.424277E+09 | 0.161030E+09 | 0.263246E+09 | 0.693760E+09 | 0.130457E+09 |
June | 0.431370E+09 | 0.166096E+09 | 0.265273E+09 | 0.806024E+09 | 57680393.04 |
July | 0.419570E+09 | 0.155192E+09 | 0.264378E+09 | 0.824593E+09 | 29158552.12 |
August | 0.412124E+09 | 0.154141E+09 | 0.257983E+09 | 0.819411E+09 | 14057765.25 |
September | 0.325820E+09 | 0.136209E+09 | 0.189611E+09 | 0.560965E+09 | 85573283.55 |
October | 0.299566E+09 | 0.155754E+09 | 0.143812E+09 | 0.430334E+09 | 0.256844E+09 |
November | 0.230249E+09 | 0.102964E+09 | 0.127285E+09 | 0.278155E+09 | 0.362280E+09 |
December | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.183036E+09 | 0.504110E+09 |
Annual Sum or Average | 0.397530E+10 | 0.169631E+10 | 0.227899E+10 | 0.611494E+10 | 0.302660E+10 |
Minimum of Months | 0.197060E+09 | 86321527.55 | 0.110739E+09 | 0.183036E+09 | 14057765.25 |
Maximum of Months | 0.431370E+09 | 0.186640E+09 | 0.265273E+09 | 0.824593E+09 | 0.621351E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.409499E+09 | 0.284468E+09 | 0.125032E+09 | 0.453901E+09 | 0.459813E+09 |
February | 0.344539E+09 | 0.229856E+09 | 0.114683E+09 | 0.418719E+09 | 0.341064E+09 |
March | 0.348816E+09 | 0.183042E+09 | 0.165774E+09 | 0.477595E+09 | 0.227994E+09 |
April | 0.254042E+09 | 84756499.22 | 0.169285E+09 | 0.398181E+09 | 0.165481E+09 |
May | 0.211016E+09 | 25823064.22 | 0.185193E+09 | 0.366300E+09 | 91498801.03 |
June | 0.187503E+09 | 10468196.17 | 0.177035E+09 | 0.400324E+09 | 38563009.36 |
July | 0.194358E+09 | 13109729.90 | 0.181249E+09 | 0.441773E+09 | 17793178.38 |
August | 0.234192E+09 | 44013890.93 | 0.190178E+09 | 0.527455E+09 | 8189186.36 |
September | 0.255873E+09 | 99557331.94 | 0.156316E+09 | 0.468676E+09 | 60923613.00 |
October | 0.371270E+09 | 0.239967E+09 | 0.131304E+09 | 0.561350E+09 | 0.196146E+09 |
November | 0.392545E+09 | 0.261946E+09 | 0.130599E+09 | 0.525281E+09 | 0.276070E+09 |
December | 0.406617E+09 | 0.286040E+09 | 0.120577E+09 | 0.486541E+09 | 0.377206E+09 |
Annual Sum or Average | 0.361027E+10 | 0.176305E+10 | 0.184722E+10 | 0.552610E+10 | 0.226074E+10 |
Minimum of Months | 0.187503E+09 | 10468196.17 | 0.114683E+09 | 0.366300E+09 | 8189186.36 |
Maximum of Months | 0.409499E+09 | 0.286040E+09 | 0.190178E+09 | 0.561350E+09 | 0.459813E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.368106E+09 | 0.00 | 0.368106E+09 | 33835386.11 | 0.305986E+10 |
February | 0.368525E+09 | 0.00 | 0.368525E+09 | 0.131164E+09 | 0.224291E+10 |
March | 0.572963E+09 | 11539.19 | 0.572952E+09 | 0.361528E+09 | 0.145738E+10 |
April | 0.672313E+09 | 3926592.47 | 0.668386E+09 | 0.736251E+09 | 0.102705E+10 |
May | 0.828899E+09 | 25997097.83 | 0.802902E+09 | 0.119372E+10 | 0.624382E+09 |
June | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.166951E+10 | 0.328833E+09 |
July | 0.863385E+09 | 44240976.70 | 0.819144E+09 | 0.175229E+10 | 0.219916E+09 |
August | 0.766846E+09 | 9008940.72 | 0.757837E+09 | 0.159752E+10 | 0.164683E+09 |
September | 0.560178E+09 | 220208.23 | 0.559958E+09 | 0.879910E+09 | 0.493859E+09 |
October | 0.439818E+09 | 0.00 | 0.439818E+09 | 0.383247E+09 | 0.128718E+10 |
November | 0.380924E+09 | 0.00 | 0.380924E+09 | 0.168898E+09 | 0.178577E+10 |
December | 0.340287E+09 | 0.00 | 0.340287E+09 | 34424927.98 | 0.251219E+10 |
Annual Sum or Average | 0.704448E+10 | 0.141262E+09 | 0.690322E+10 | 0.894230E+10 | 0.152040E+11 |
Minimum of Months | 0.340287E+09 | 0.00 | 0.340287E+09 | 33835386.11 | 0.164683E+09 |
Maximum of Months | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.175229E+10 | 0.305986E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.368106E+09 | 0.00 | 0.368106E+09 | 29124510.44 | 0.315953E+10 |
February | 0.368525E+09 | 0.00 | 0.368525E+09 | 0.119971E+09 | 0.231891E+10 |
March | 0.572963E+09 | 11539.19 | 0.572952E+09 | 0.334336E+09 | 0.151059E+10 |
April | 0.672313E+09 | 3926592.47 | 0.668386E+09 | 0.706574E+09 | 0.105973E+10 |
May | 0.828899E+09 | 25997097.83 | 0.802902E+09 | 0.116357E+10 | 0.646616E+09 |
June | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.164346E+10 | 0.342654E+09 |
July | 0.863385E+09 | 44240976.70 | 0.819144E+09 | 0.172631E+10 | 0.232223E+09 |
August | 0.766846E+09 | 9008940.72 | 0.757837E+09 | 0.157231E+10 | 0.176666E+09 |
September | 0.560178E+09 | 220208.23 | 0.559958E+09 | 0.855358E+09 | 0.516828E+09 |
October | 0.439818E+09 | 0.00 | 0.439818E+09 | 0.361236E+09 | 0.133574E+10 |
November | 0.380924E+09 | 0.00 | 0.380924E+09 | 0.149432E+09 | 0.185000E+10 |
December | 0.340287E+09 | 0.00 | 0.340287E+09 | 28142983.05 | 0.260288E+10 |
Annual Sum or Average | 0.704448E+10 | 0.141262E+09 | 0.690322E+10 | 0.868982E+10 | 0.157524E+11 |
Minimum of Months | 0.340287E+09 | 0.00 | 0.340287E+09 | 28142983.05 | 0.176666E+09 |
Maximum of Months | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.172631E+10 | 0.315953E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52588594.07 | 0.00 | 52588594.07 | 8043385.29 | 0.404056E+09 |
February | 52648446.06 | 0.00 | 52648446.06 | 26935764.78 | 0.295352E+09 |
March | 81855013.60 | 1648.52 | 81853365.08 | 76123623.68 | 0.190079E+09 |
April | 96048332.89 | 560963.03 | 95487369.87 | 0.143329E+09 | 0.135125E+09 |
May | 0.118419E+09 | 3714011.78 | 0.114705E+09 | 0.223774E+09 | 85257368.07 |
June | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.297806E+09 | 48470509.72 |
July | 0.123345E+09 | 6320378.90 | 0.117025E+09 | 0.315292E+09 | 33004630.81 |
August | 0.109554E+09 | 1287040.28 | 0.108267E+09 | 0.292562E+09 | 25170127.77 |
September | 80028430.11 | 31459.51 | 79996970.60 | 0.173141E+09 | 62420652.47 |
October | 62833545.17 | 0.00 | 62833545.17 | 81753065.09 | 0.163898E+09 |
November | 54419711.70 | 0.00 | 54419711.70 | 40876480.93 | 0.229745E+09 |
December | 48614241.33 | 0.00 | 48614241.33 | 10079969.31 | 0.325903E+09 |
Annual Sum or Average | 0.100639E+10 | 20181056.73 | 0.986211E+09 | 0.168972E+10 | 0.199848E+10 |
Minimum of Months | 48614241.33 | 0.00 | 48614241.33 | 8043385.29 | 25170127.77 |
Maximum of Months | 0.126039E+09 | 8265554.72 | 0.117773E+09 | 0.315292E+09 | 0.404056E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.434507E+09 | 0.197839E+09 | 0.236668E+09 | 0.307276E+09 | 0.136346E+10 |
February | 0.492555E+09 | 0.265149E+09 | 0.227406E+09 | 0.503366E+09 | 0.994309E+09 |
March | 0.686097E+09 | 0.312962E+09 | 0.373136E+09 | 0.887668E+09 | 0.653548E+09 |
April | 0.802608E+09 | 0.366340E+09 | 0.436268E+09 | 0.128121E+10 | 0.478379E+09 |
May | 0.908547E+09 | 0.384217E+09 | 0.524331E+09 | 0.163654E+10 | 0.315767E+09 |
June | 0.909412E+09 | 0.380907E+09 | 0.528506E+09 | 0.186524E+10 | 0.180774E+09 |
July | 0.915938E+09 | 0.384279E+09 | 0.531659E+09 | 0.196018E+10 | 0.124215E+09 |
August | 0.839504E+09 | 0.333007E+09 | 0.506497E+09 | 0.184357E+10 | 94739580.28 |
September | 0.665833E+09 | 0.294206E+09 | 0.371628E+09 | 0.128679E+10 | 0.229740E+09 |
October | 0.588469E+09 | 0.306304E+09 | 0.282165E+09 | 0.889868E+09 | 0.575144E+09 |
November | 0.453550E+09 | 0.204592E+09 | 0.248958E+09 | 0.518373E+09 | 0.776994E+09 |
December | 0.406705E+09 | 0.185132E+09 | 0.221573E+09 | 0.315711E+09 | 0.109269E+10 |
Annual Sum or Average | 0.810373E+10 | 0.361493E+10 | 0.448879E+10 | 0.132958E+11 | 0.687976E+10 |
Minimum of Months | 0.406705E+09 | 0.185132E+09 | 0.221573E+09 | 0.307276E+09 | 94739580.28 |
Maximum of Months | 0.915938E+09 | 0.384279E+09 | 0.531659E+09 | 0.196018E+10 | 0.136346E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279218E+09 | 0.193965E+09 | 85252967.91 | 0.327578E+09 | 0.333389E+09 |
February | 0.234924E+09 | 0.156728E+09 | 78196598.94 | 0.302415E+09 | 0.252774E+09 |
March | 0.237841E+09 | 0.124808E+09 | 0.113033E+09 | 0.351762E+09 | 0.179161E+09 |
April | 0.173219E+09 | 57791307.85 | 0.115427E+09 | 0.300243E+09 | 0.136086E+09 |
May | 0.143881E+09 | 17607483.41 | 0.126274E+09 | 0.284126E+09 | 88025533.36 |
June | 0.127849E+09 | 7137750.53 | 0.120712E+09 | 0.306840E+09 | 50291039.92 |
July | 0.132523E+09 | 8938883.07 | 0.123585E+09 | 0.336930E+09 | 33358474.68 |
August | 0.159684E+09 | 30010917.68 | 0.129673E+09 | 0.396992E+09 | 25193509.96 |
September | 0.174468E+09 | 67883271.16 | 0.106584E+09 | 0.355710E+09 | 61745125.73 |
October | 0.253151E+09 | 0.163622E+09 | 89529587.28 | 0.413923E+09 | 0.154542E+09 |
November | 0.267657E+09 | 0.178608E+09 | 89049108.36 | 0.385230E+09 | 0.204623E+09 |
December | 0.277252E+09 | 0.195037E+09 | 82215273.99 | 0.352042E+09 | 0.276303E+09 |
Annual Sum or Average | 0.246167E+10 | 0.120214E+10 | 0.125953E+10 | 0.411379E+10 | 0.179549E+10 |
Minimum of Months | 0.127849E+09 | 7137750.53 | 78196598.94 | 0.284126E+09 | 25193509.96 |
Maximum of Months | 0.279218E+09 | 0.195037E+09 | 0.129673E+09 | 0.413923E+09 | 0.333389E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66600136.23 | 0.00 | 66600136.23 | 8300009.17 | 0.501011E+09 |
February | 66675935.00 | 0.00 | 66675935.00 | 28545799.34 | 0.359198E+09 |
March | 0.103664E+09 | 2087.74 | 0.103662E+09 | 77466134.06 | 0.223737E+09 |
April | 0.121639E+09 | 710424.28 | 0.120929E+09 | 0.145839E+09 | 0.161554E+09 |
May | 0.149970E+09 | 4703561.58 | 0.145266E+09 | 0.227199E+09 | 99492005.92 |
June | 0.159620E+09 | 10467803.52 | 0.149152E+09 | 0.306127E+09 | 55129850.58 |
July | 0.156209E+09 | 8004361.08 | 0.148205E+09 | 0.318266E+09 | 36624157.77 |
August | 0.138743E+09 | 1629955.30 | 0.137113E+09 | 0.288108E+09 | 27951862.65 |
September | 0.101351E+09 | 39841.48 | 0.101311E+09 | 0.164941E+09 | 78577913.14 |
October | 79574720.39 | 0.00 | 79574720.39 | 77396191.18 | 0.199573E+09 |
November | 68919131.17 | 0.00 | 68919131.17 | 38813418.38 | 0.278460E+09 |
December | 61566869.25 | 0.00 | 61566869.25 | 9363470.68 | 0.398669E+09 |
Annual Sum or Average | 0.127453E+10 | 25558034.99 | 0.124897E+10 | 0.169037E+10 | 0.241998E+10 |
Minimum of Months | 61566869.25 | 0.00 | 61566869.25 | 8300009.17 | 27951862.65 |
Maximum of Months | 0.159620E+09 | 10467803.52 | 0.149152E+09 | 0.318266E+09 | 0.501011E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 59587394.23 | 0.00 | 59587394.23 | 7426049.65 | 0.448247E+09 |
February | 59655211.68 | 0.00 | 59655211.68 | 25540034.83 | 0.321376E+09 |
March | 92748761.43 | 1867.91 | 92746893.52 | 69309243.66 | 0.200178E+09 |
April | 0.108831E+09 | 635619.29 | 0.108195E+09 | 0.130483E+09 | 0.144543E+09 |
May | 0.134178E+09 | 4208294.36 | 0.129970E+09 | 0.203276E+09 | 89015874.67 |
June | 0.142813E+09 | 9365583.47 | 0.133447E+09 | 0.273893E+09 | 49324886.20 |
July | 0.139761E+09 | 7161532.19 | 0.132599E+09 | 0.284754E+09 | 32767772.72 |
August | 0.124134E+09 | 1458327.18 | 0.122675E+09 | 0.257771E+09 | 25008637.42 |
September | 90679085.44 | 35646.33 | 90643439.12 | 0.147573E+09 | 70303956.62 |
October | 71195803.84 | 0.00 | 71195803.84 | 69246665.50 | 0.178559E+09 |
November | 61662207.79 | 0.00 | 61662207.79 | 34726512.49 | 0.249138E+09 |
December | 55084111.20 | 0.00 | 55084111.20 | 8377532.69 | 0.356676E+09 |
Annual Sum or Average | 0.114033E+10 | 22866870.75 | 0.111746E+10 | 0.151238E+10 | 0.216514E+10 |
Minimum of Months | 55084111.20 | 0.00 | 55084111.20 | 7426049.65 | 25008637.42 |
Maximum of Months | 0.142813E+09 | 9365583.47 | 0.133447E+09 | 0.284754E+09 | 0.448247E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104240E+10 | 0.724128E+09 | 0.318275E+09 | 0.117905E+10 | 0.120380E+10 |
February | 0.877042E+09 | 0.585111E+09 | 0.291931E+09 | 0.108554E+10 | 0.898172E+09 |
March | 0.887931E+09 | 0.465944E+09 | 0.421987E+09 | 0.123207E+10 | 0.617289E+09 |
April | 0.646677E+09 | 0.215752E+09 | 0.430925E+09 | 0.100585E+10 | 0.482115E+09 |
May | 0.537152E+09 | 65733982.34 | 0.471418E+09 | 0.894878E+09 | 0.311655E+09 |
June | 0.477300E+09 | 26647349.68 | 0.450653E+09 | 0.937537E+09 | 0.175361E+09 |
July | 0.494749E+09 | 33371514.17 | 0.461378E+09 | 0.102303E+10 | 0.113381E+09 |
August | 0.596149E+09 | 0.112040E+09 | 0.484109E+09 | 0.123708E+10 | 84566054.00 |
September | 0.651339E+09 | 0.253428E+09 | 0.397911E+09 | 0.115374E+10 | 0.230688E+09 |
October | 0.945089E+09 | 0.610848E+09 | 0.334241E+09 | 0.143718E+10 | 0.549918E+09 |
November | 0.999244E+09 | 0.666797E+09 | 0.332447E+09 | 0.136593E+10 | 0.723423E+09 |
December | 0.103506E+10 | 0.728130E+09 | 0.306934E+09 | 0.126505E+10 | 0.983119E+09 |
Annual Sum or Average | 0.919014E+10 | 0.448793E+10 | 0.470221E+10 | 0.138169E+11 | 0.637348E+10 |
Minimum of Months | 0.477300E+09 | 26647349.68 | 0.291931E+09 | 0.894878E+09 | 84566054.00 |
Maximum of Months | 0.104240E+10 | 0.728130E+09 | 0.484109E+09 | 0.143718E+10 | 0.120380E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 608.49 | 560.17 | 527.26 | 366.27 | 160.99 | 0.00 | 0.00 |
February | 616.45 | 466.18 | 491.15 | 327.66 | 163.48 | 0.00 | 0.00 |
March | 627.37 | 300.67 | 449.12 | 235.68 | 213.44 | 0.00 | 0.00 |
April | 531.44 | 237.82 | 338.00 | 112.77 | 225.23 | 0.00 | 0.00 |
May | 459.22 | 146.89 | 271.69 | 33.25 | 238.45 | 0.00 | 0.00 |
June | 488.45 | 88.53 | 249.47 | 13.93 | 235.54 | 0.00 | 0.00 |
July | 512.72 | 56.13 | 250.25 | 16.88 | 233.37 | 0.00 | 0.00 |
August | 616.91 | 46.10 | 301.54 | 56.67 | 244.87 | 0.00 | 0.00 |
September | 599.99 | 118.89 | 340.43 | 132.46 | 207.97 | 0.00 | 0.00 |
October | 723.40 | 270.72 | 478.03 | 308.97 | 169.06 | 0.00 | 0.00 |
November | 711.63 | 364.65 | 522.27 | 348.52 | 173.76 | 0.00 | 0.00 |
December | 646.94 | 466.01 | 523.54 | 368.30 | 155.25 | 0.00 | 0.00 |
Annual Sum or Average | 595.21 | 259.17 | 394.80 | 192.80 | 202.00 | 0.00 | 0.00 |
Minimum of Months | 459.22 | 46.10 | 249.47 | 13.93 | 155.25 | 0.00 | 0.00 |
Maximum of Months | 723.40 | 560.17 | 527.26 | 368.30 | 244.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1679.18 | 1670.78 | 1484.72 | 1031.40 | 453.32 | 0.00 | 0.00 |
February | 1701.80 | 1413.78 | 1383.03 | 922.68 | 460.35 | 0.00 | 0.00 |
March | 1728.51 | 942.10 | 1264.70 | 663.66 | 601.04 | 0.00 | 0.00 |
April | 1462.99 | 744.83 | 951.78 | 317.55 | 634.23 | 0.00 | 0.00 |
May | 1266.17 | 468.06 | 765.07 | 93.63 | 671.45 | 0.00 | 0.00 |
June | 1368.68 | 271.28 | 702.49 | 39.22 | 663.27 | 0.00 | 0.00 |
July | 1441.94 | 173.30 | 704.68 | 47.53 | 657.15 | 0.00 | 0.00 |
August | 1736.70 | 137.67 | 849.11 | 159.58 | 689.52 | 0.00 | 0.00 |
September | 1671.02 | 375.20 | 958.64 | 373.00 | 585.64 | 0.00 | 0.00 |
October | 2006.28 | 846.06 | 1346.11 | 870.05 | 476.06 | 0.00 | 0.00 |
November | 1962.46 | 1134.54 | 1470.69 | 981.40 | 489.29 | 0.00 | 0.00 |
December | 1784.68 | 1417.53 | 1474.27 | 1037.10 | 437.17 | 0.00 | 0.00 |
Annual Sum or Average | 1650.83 | 796.39 | 1111.73 | 542.91 | 568.82 | 0.00 | 0.00 |
Minimum of Months | 1266.17 | 137.67 | 702.49 | 39.22 | 437.17 | 0.00 | 0.00 |
Maximum of Months | 2006.28 | 1670.78 | 1484.72 | 1037.10 | 689.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2219.87 | 2260.83 | 1928.74 | 1339.84 | 588.89 | 0.00 | 0.00 |
February | 2254.57 | 1909.28 | 1796.64 | 1198.62 | 598.02 | 0.00 | 0.00 |
March | 2293.86 | 1260.90 | 1642.92 | 862.13 | 780.79 | 0.00 | 0.00 |
April | 1939.62 | 1002.05 | 1236.41 | 412.51 | 823.90 | 0.00 | 0.00 |
May | 1678.85 | 627.54 | 993.87 | 121.63 | 872.25 | 0.00 | 0.00 |
June | 1819.95 | 359.72 | 912.57 | 50.95 | 861.62 | 0.00 | 0.00 |
July | 1922.66 | 227.99 | 915.42 | 61.75 | 853.67 | 0.00 | 0.00 |
August | 2322.10 | 175.63 | 1103.04 | 207.31 | 895.73 | 0.00 | 0.00 |
September | 2218.91 | 497.79 | 1245.33 | 484.54 | 760.78 | 0.00 | 0.00 |
October | 2661.28 | 1133.61 | 1748.68 | 1130.24 | 618.43 | 0.00 | 0.00 |
November | 2595.60 | 1524.28 | 1910.51 | 1274.89 | 635.62 | 0.00 | 0.00 |
December | 2358.06 | 1918.90 | 1915.16 | 1347.25 | 567.91 | 0.00 | 0.00 |
Annual Sum or Average | 2190.43 | 1070.53 | 1444.20 | 705.27 | 738.93 | 0.00 | 0.00 |
Minimum of Months | 1678.85 | 175.63 | 912.57 | 50.95 | 567.91 | 0.00 | 0.00 |
Maximum of Months | 2661.28 | 2260.83 | 1928.74 | 1347.25 | 895.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 169.50 | 333.45 | 187.37 | 111.07 | 76.30 | 0.00 | 0.00 |
February | 208.12 | 272.57 | 192.34 | 109.42 | 82.92 | 0.00 | 0.00 |
March | 300.49 | 165.83 | 228.51 | 113.98 | 114.53 | 0.00 | 0.00 |
April | 340.15 | 125.29 | 224.26 | 94.30 | 129.96 | 0.00 | 0.00 |
May | 356.60 | 70.07 | 212.13 | 66.70 | 145.43 | 0.00 | 0.00 |
June | 419.33 | 32.82 | 215.75 | 66.83 | 148.91 | 0.00 | 0.00 |
July | 422.62 | 15.74 | 206.13 | 61.28 | 144.85 | 0.00 | 0.00 |
August | 441.25 | 8.01 | 213.49 | 68.75 | 144.73 | 0.00 | 0.00 |
September | 341.38 | 48.76 | 193.01 | 78.74 | 114.27 | 0.00 | 0.00 |
October | 301.99 | 144.27 | 206.36 | 119.24 | 87.12 | 0.00 | 0.00 |
November | 237.89 | 207.83 | 192.09 | 108.63 | 83.46 | 0.00 | 0.00 |
December | 178.73 | 272.91 | 177.09 | 105.05 | 72.04 | 0.00 | 0.00 |
Annual Sum or Average | 310.40 | 140.80 | 204.11 | 91.91 | 112.21 | 0.00 | 0.00 |
Minimum of Months | 169.50 | 8.01 | 177.09 | 61.28 | 72.04 | 0.00 | 0.00 |
Maximum of Months | 441.25 | 333.45 | 228.51 | 119.24 | 148.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 64.98 | 360.03 | 102.75 | 38.65 | 64.11 | 0.00 | 0.00 |
February | 107.08 | 291.66 | 116.99 | 44.63 | 72.36 | 0.00 | 0.00 |
March | 203.84 | 171.18 | 170.27 | 67.38 | 102.89 | 0.00 | 0.00 |
April | 279.92 | 129.26 | 194.49 | 72.22 | 122.27 | 0.00 | 0.00 |
May | 329.87 | 73.71 | 202.62 | 61.51 | 141.11 | 0.00 | 0.00 |
June | 410.69 | 33.95 | 215.05 | 67.27 | 147.78 | 0.00 | 0.00 |
July | 409.50 | 17.38 | 202.70 | 60.30 | 142.40 | 0.00 | 0.00 |
August | 399.83 | 8.96 | 194.77 | 58.03 | 136.74 | 0.00 | 0.00 |
September | 270.81 | 52.83 | 156.58 | 52.56 | 104.02 | 0.00 | 0.00 |
October | 184.61 | 150.52 | 135.30 | 58.15 | 77.15 | 0.00 | 0.00 |
November | 119.05 | 218.71 | 109.83 | 39.72 | 70.10 | 0.00 | 0.00 |
December | 68.36 | 293.27 | 91.72 | 32.23 | 59.50 | 0.00 | 0.00 |
Annual Sum or Average | 238.09 | 149.41 | 157.97 | 54.43 | 103.54 | 0.00 | 0.00 |
Minimum of Months | 64.98 | 8.96 | 91.72 | 32.23 | 59.50 | 0.00 | 0.00 |
Maximum of Months | 410.69 | 360.03 | 215.05 | 72.22 | 147.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 89.91 | 103.32 | 83.38 | 57.92 | 25.46 | 0.00 | 0.00 |
February | 88.66 | 96.00 | 77.67 | 51.82 | 25.85 | 0.00 | 0.00 |
March | 86.34 | 71.19 | 71.03 | 37.27 | 33.75 | 0.00 | 0.00 |
April | 71.54 | 57.89 | 53.45 | 17.83 | 35.62 | 0.00 | 0.00 |
May | 60.27 | 38.88 | 42.97 | 5.26 | 37.71 | 0.00 | 0.00 |
June | 66.42 | 24.48 | 39.45 | 2.20 | 37.25 | 0.00 | 0.00 |
July | 70.82 | 18.00 | 39.57 | 2.67 | 36.91 | 0.00 | 0.00 |
August | 88.14 | 15.61 | 47.69 | 8.96 | 38.72 | 0.00 | 0.00 |
September | 84.90 | 32.98 | 53.84 | 20.95 | 32.89 | 0.00 | 0.00 |
October | 103.94 | 64.83 | 75.60 | 48.86 | 26.74 | 0.00 | 0.00 |
November | 100.67 | 83.90 | 82.59 | 55.11 | 27.48 | 0.00 | 0.00 |
December | 91.69 | 100.33 | 82.79 | 58.24 | 24.55 | 0.00 | 0.00 |
Annual Sum or Average | 83.60 | 58.75 | 62.43 | 30.49 | 31.95 | 0.00 | 0.00 |
Minimum of Months | 60.27 | 15.61 | 39.45 | 2.20 | 24.55 | 0.00 | 0.00 |
Maximum of Months | 103.94 | 103.32 | 83.38 | 58.24 | 38.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.20 | 112.59 | 15.71 | 0.00 | 15.71 | 0.00 | 0.00 |
February | 8.27 | 89.46 | 17.41 | 0.00 | 17.41 | 0.00 | 0.00 |
March | 20.12 | 49.29 | 24.45 | 0.00 | 24.45 | 0.00 | 0.00 |
April | 38.39 | 35.40 | 29.65 | 0.17 | 29.48 | 0.00 | 0.00 |
May | 58.03 | 18.81 | 35.37 | 1.11 | 34.27 | 0.00 | 0.00 |
June | 82.67 | 7.95 | 38.91 | 2.55 | 36.35 | 0.00 | 0.00 |
July | 84.60 | 3.87 | 36.85 | 1.89 | 34.96 | 0.00 | 0.00 |
August | 78.83 | 1.66 | 32.73 | 0.38 | 32.34 | 0.00 | 0.00 |
September | 45.45 | 13.65 | 24.70 | 0.01 | 24.69 | 0.00 | 0.00 |
October | 20.62 | 42.68 | 18.77 | 0.00 | 18.77 | 0.00 | 0.00 |
November | 10.69 | 64.42 | 16.80 | 0.00 | 16.80 | 0.00 | 0.00 |
December | 2.78 | 89.62 | 14.52 | 0.00 | 14.52 | 0.00 | 0.00 |
Annual Sum or Average | 37.89 | 43.89 | 25.53 | 0.51 | 25.02 | 0.00 | 0.00 |
Minimum of Months | 2.20 | 1.66 | 14.52 | 0.00 | 14.52 | 0.00 | 0.00 |
Maximum of Months | 84.60 | 112.59 | 38.91 | 2.55 | 36.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 161.58 | 328.66 | 185.37 | 109.35 | 76.01 | 0.00 | 0.00 |
February | 212.29 | 266.49 | 198.92 | 119.59 | 79.33 | 0.00 | 0.00 |
March | 272.66 | 157.86 | 216.89 | 105.03 | 111.86 | 0.00 | 0.00 |
April | 326.71 | 116.53 | 221.66 | 92.97 | 128.69 | 0.00 | 0.00 |
May | 368.86 | 64.95 | 223.34 | 78.30 | 145.03 | 0.00 | 0.00 |
June | 431.42 | 29.97 | 224.76 | 76.24 | 148.53 | 0.00 | 0.00 |
July | 445.06 | 15.13 | 220.48 | 75.08 | 145.40 | 0.00 | 0.00 |
August | 446.26 | 7.54 | 216.35 | 73.37 | 142.97 | 0.00 | 0.00 |
September | 344.20 | 46.62 | 195.76 | 82.95 | 112.81 | 0.00 | 0.00 |
October | 292.14 | 138.47 | 204.38 | 118.27 | 86.10 | 0.00 | 0.00 |
November | 228.65 | 201.00 | 190.76 | 108.38 | 82.38 | 0.00 | 0.00 |
December | 176.69 | 267.14 | 179.44 | 107.38 | 72.06 | 0.00 | 0.00 |
Annual Sum or Average | 309.41 | 136.05 | 206.55 | 95.44 | 111.11 | 0.00 | 0.00 |
Minimum of Months | 161.58 | 7.54 | 179.44 | 73.37 | 72.06 | 0.00 | 0.00 |
Maximum of Months | 446.26 | 328.66 | 224.76 | 119.59 | 148.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 50.48 | 348.40 | 100.75 | 36.93 | 63.82 | 0.00 | 0.00 |
February | 101.76 | 275.54 | 123.57 | 54.80 | 68.77 | 0.00 | 0.00 |
March | 173.06 | 158.42 | 158.65 | 58.43 | 100.22 | 0.00 | 0.00 |
April | 266.77 | 119.54 | 191.89 | 70.89 | 121.00 | 0.00 | 0.00 |
May | 342.79 | 69.40 | 213.83 | 73.12 | 140.71 | 0.00 | 0.00 |
June | 422.15 | 32.19 | 224.07 | 76.67 | 147.39 | 0.00 | 0.00 |
July | 430.35 | 17.20 | 217.05 | 74.10 | 142.95 | 0.00 | 0.00 |
August | 403.73 | 8.46 | 197.63 | 62.65 | 134.98 | 0.00 | 0.00 |
September | 272.18 | 50.11 | 159.32 | 56.77 | 102.56 | 0.00 | 0.00 |
October | 171.15 | 140.01 | 133.32 | 57.18 | 76.14 | 0.00 | 0.00 |
November | 101.03 | 201.48 | 108.49 | 39.47 | 69.02 | 0.00 | 0.00 |
December | 54.20 | 274.89 | 94.08 | 34.56 | 59.52 | 0.00 | 0.00 |
Annual Sum or Average | 233.18 | 140.64 | 160.41 | 57.96 | 102.45 | 0.00 | 0.00 |
Minimum of Months | 50.48 | 8.46 | 94.08 | 34.56 | 59.52 | 0.00 | 0.00 |
Maximum of Months | 430.35 | 348.40 | 224.07 | 76.67 | 147.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 182.47 | 424.71 | 214.70 | 125.50 | 89.19 | 0.00 | 0.00 |
February | 210.27 | 347.76 | 206.01 | 112.27 | 93.74 | 0.00 | 0.00 |
March | 257.28 | 215.62 | 206.86 | 80.76 | 126.11 | 0.00 | 0.00 |
April | 265.47 | 169.04 | 180.04 | 39.01 | 141.03 | 0.00 | 0.00 |
May | 282.54 | 99.21 | 169.73 | 13.80 | 155.93 | 0.00 | 0.00 |
June | 342.84 | 54.29 | 169.76 | 10.30 | 159.46 | 0.00 | 0.00 |
July | 352.59 | 34.18 | 165.57 | 9.87 | 155.70 | 0.00 | 0.00 |
August | 375.43 | 24.29 | 174.22 | 20.25 | 153.97 | 0.00 | 0.00 |
September | 302.41 | 80.03 | 170.17 | 45.41 | 124.76 | 0.00 | 0.00 |
October | 290.98 | 192.94 | 204.46 | 105.87 | 98.59 | 0.00 | 0.00 |
November | 260.93 | 262.50 | 215.35 | 119.42 | 95.93 | 0.00 | 0.00 |
December | 207.67 | 344.29 | 210.85 | 126.20 | 84.66 | 0.00 | 0.00 |
Annual Sum or Average | 277.96 | 186.59 | 190.59 | 67.17 | 123.42 | 0.00 | 0.00 |
Minimum of Months | 182.47 | 24.29 | 165.57 | 9.87 | 84.66 | 0.00 | 0.00 |
Maximum of Months | 375.43 | 424.71 | 215.35 | 126.20 | 159.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 169.60 | 331.45 | 187.37 | 111.07 | 76.30 | 0.00 | 0.00 |
February | 207.52 | 270.21 | 192.34 | 109.42 | 82.92 | 0.00 | 0.00 |
March | 298.18 | 163.47 | 228.51 | 113.98 | 114.53 | 0.00 | 0.00 |
April | 337.17 | 123.53 | 224.26 | 94.30 | 129.96 | 0.00 | 0.00 |
May | 353.17 | 68.74 | 212.13 | 66.70 | 145.43 | 0.00 | 0.00 |
June | 416.46 | 31.41 | 215.75 | 66.83 | 148.91 | 0.00 | 0.00 |
July | 420.21 | 14.60 | 206.13 | 61.28 | 144.85 | 0.00 | 0.00 |
August | 438.86 | 7.11 | 213.49 | 68.75 | 144.73 | 0.00 | 0.00 |
September | 339.40 | 46.85 | 193.01 | 78.74 | 114.27 | 0.00 | 0.00 |
October | 300.29 | 141.51 | 206.36 | 119.24 | 87.12 | 0.00 | 0.00 |
November | 237.19 | 205.13 | 192.09 | 108.63 | 83.46 | 0.00 | 0.00 |
December | 178.87 | 270.26 | 177.09 | 105.05 | 72.04 | 0.00 | 0.00 |
Annual Sum or Average | 308.63 | 138.86 | 204.11 | 91.91 | 112.21 | 0.00 | 0.00 |
Minimum of Months | 169.60 | 7.11 | 177.09 | 61.28 | 72.04 | 0.00 | 0.00 |
Maximum of Months | 438.86 | 331.45 | 228.51 | 119.24 | 148.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 65.52 | 358.13 | 102.75 | 38.65 | 64.11 | 0.00 | 0.00 |
February | 107.19 | 289.17 | 116.99 | 44.63 | 72.36 | 0.00 | 0.00 |
March | 202.79 | 168.60 | 170.27 | 67.38 | 102.89 | 0.00 | 0.00 |
April | 277.39 | 128.24 | 194.49 | 72.22 | 122.27 | 0.00 | 0.00 |
May | 326.53 | 73.10 | 202.62 | 61.51 | 141.11 | 0.00 | 0.00 |
June | 408.05 | 32.79 | 215.05 | 67.27 | 147.78 | 0.00 | 0.00 |
July | 407.35 | 16.36 | 202.70 | 60.30 | 142.40 | 0.00 | 0.00 |
August | 397.90 | 7.99 | 194.77 | 58.03 | 136.74 | 0.00 | 0.00 |
September | 269.54 | 50.78 | 156.58 | 52.56 | 104.02 | 0.00 | 0.00 |
October | 184.27 | 147.32 | 135.30 | 58.15 | 77.15 | 0.00 | 0.00 |
November | 119.69 | 215.09 | 109.83 | 39.72 | 70.10 | 0.00 | 0.00 |
December | 69.47 | 290.06 | 91.72 | 32.23 | 59.50 | 0.00 | 0.00 |
Annual Sum or Average | 237.02 | 147.43 | 157.97 | 54.43 | 103.54 | 0.00 | 0.00 |
Minimum of Months | 65.52 | 7.99 | 91.72 | 32.23 | 59.50 | 0.00 | 0.00 |
Maximum of Months | 408.05 | 358.13 | 215.05 | 72.22 | 147.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 169.47 | 171.67 | 152.89 | 106.21 | 46.68 | 0.00 | 0.00 |
February | 173.08 | 140.98 | 142.42 | 95.01 | 47.41 | 0.00 | 0.00 |
March | 178.31 | 85.12 | 130.23 | 68.34 | 61.89 | 0.00 | 0.00 |
April | 153.62 | 63.84 | 98.01 | 32.70 | 65.31 | 0.00 | 0.00 |
May | 136.76 | 34.16 | 78.78 | 9.64 | 69.14 | 0.00 | 0.00 |
June | 154.45 | 14.88 | 72.34 | 4.04 | 68.30 | 0.00 | 0.00 |
July | 164.94 | 6.64 | 72.57 | 4.89 | 67.67 | 0.00 | 0.00 |
August | 196.93 | 3.06 | 87.44 | 16.43 | 71.00 | 0.00 | 0.00 |
September | 180.82 | 23.50 | 98.72 | 38.41 | 60.31 | 0.00 | 0.00 |
October | 209.58 | 73.23 | 138.62 | 89.59 | 49.02 | 0.00 | 0.00 |
November | 202.65 | 106.51 | 151.44 | 101.06 | 50.39 | 0.00 | 0.00 |
December | 181.65 | 140.83 | 151.81 | 106.80 | 45.02 | 0.00 | 0.00 |
Annual Sum or Average | 175.23 | 71.69 | 114.48 | 55.91 | 58.58 | 0.00 | 0.00 |
Minimum of Months | 136.76 | 3.06 | 72.34 | 4.04 | 45.02 | 0.00 | 0.00 |
Maximum of Months | 209.58 | 171.67 | 152.89 | 106.80 | 71.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 12.63 | 1142.42 | 137.44 | 0.00 | 137.44 | 0.00 | 0.00 |
February | 54.22 | 927.13 | 152.33 | 0.00 | 152.33 | 0.00 | 0.00 |
March | 134.98 | 544.12 | 213.92 | 0.00 | 213.92 | 0.00 | 0.00 |
April | 284.05 | 396.24 | 259.38 | 1.51 | 257.87 | 0.00 | 0.00 |
May | 445.68 | 233.12 | 309.48 | 9.71 | 299.77 | 0.00 | 0.00 |
June | 644.10 | 126.86 | 340.37 | 22.32 | 318.05 | 0.00 | 0.00 |
July | 654.23 | 82.11 | 322.35 | 16.52 | 305.83 | 0.00 | 0.00 |
August | 596.44 | 61.49 | 286.31 | 3.36 | 282.94 | 0.00 | 0.00 |
September | 339.47 | 190.53 | 216.12 | 0.08 | 216.03 | 0.00 | 0.00 |
October | 143.09 | 480.58 | 164.21 | 0.00 | 164.21 | 0.00 | 0.00 |
November | 65.16 | 688.96 | 146.96 | 0.00 | 146.96 | 0.00 | 0.00 |
December | 12.85 | 937.94 | 127.05 | 0.00 | 127.05 | 0.00 | 0.00 |
Annual Sum or Average | 283.56 | 482.12 | 223.38 | 4.48 | 218.90 | 0.00 | 0.00 |
Minimum of Months | 12.63 | 61.49 | 127.05 | 0.00 | 127.05 | 0.00 | 0.00 |
Maximum of Months | 654.23 | 1142.42 | 340.37 | 22.32 | 318.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10.87 | 1179.63 | 137.44 | 0.00 | 137.44 | 0.00 | 0.00 |
February | 49.59 | 958.55 | 152.33 | 0.00 | 152.33 | 0.00 | 0.00 |
March | 124.83 | 563.99 | 213.92 | 0.00 | 213.92 | 0.00 | 0.00 |
April | 272.60 | 408.85 | 259.38 | 1.51 | 257.87 | 0.00 | 0.00 |
May | 434.43 | 241.42 | 309.48 | 9.71 | 299.77 | 0.00 | 0.00 |
June | 634.05 | 132.20 | 340.37 | 22.32 | 318.05 | 0.00 | 0.00 |
July | 644.53 | 86.70 | 322.35 | 16.52 | 305.83 | 0.00 | 0.00 |
August | 587.04 | 65.96 | 286.31 | 3.36 | 282.94 | 0.00 | 0.00 |
September | 330.00 | 199.39 | 216.12 | 0.08 | 216.03 | 0.00 | 0.00 |
October | 134.87 | 498.71 | 164.21 | 0.00 | 164.21 | 0.00 | 0.00 |
November | 57.65 | 713.73 | 146.96 | 0.00 | 146.96 | 0.00 | 0.00 |
December | 10.51 | 971.80 | 127.05 | 0.00 | 127.05 | 0.00 | 0.00 |
Annual Sum or Average | 275.55 | 499.50 | 223.38 | 4.48 | 218.90 | 0.00 | 0.00 |
Minimum of Months | 10.51 | 65.96 | 127.05 | 0.00 | 127.05 | 0.00 | 0.00 |
Maximum of Months | 644.53 | 1179.63 | 340.37 | 22.32 | 318.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 196.96 | 741.32 | 286.11 | 146.28 | 139.83 | 0.00 | 0.00 |
February | 316.66 | 610.03 | 322.47 | 174.39 | 148.09 | 0.00 | 0.00 |
March | 483.56 | 374.26 | 375.52 | 163.44 | 212.08 | 0.00 | 0.00 |
April | 660.05 | 283.82 | 413.53 | 163.85 | 249.68 | 0.00 | 0.00 |
May | 798.96 | 180.90 | 437.14 | 151.41 | 285.73 | 0.00 | 0.00 |
June | 952.07 | 107.03 | 448.80 | 152.90 | 295.91 | 0.00 | 0.00 |
July | 975.23 | 71.02 | 437.50 | 149.17 | 288.33 | 0.00 | 0.00 |
August | 945.73 | 54.14 | 413.96 | 136.02 | 277.94 | 0.00 | 0.00 |
September | 699.80 | 135.85 | 355.07 | 139.71 | 215.36 | 0.00 | 0.00 |
October | 512.40 | 328.72 | 337.68 | 175.45 | 162.23 | 0.00 | 0.00 |
November | 353.89 | 456.85 | 299.24 | 147.84 | 151.40 | 0.00 | 0.00 |
December | 227.31 | 607.04 | 273.51 | 141.94 | 131.57 | 0.00 | 0.00 |
Annual Sum or Average | 595.03 | 327.86 | 366.94 | 153.39 | 213.55 | 0.00 | 0.00 |
Minimum of Months | 196.96 | 54.14 | 273.51 | 136.02 | 131.57 | 0.00 | 0.00 |
Maximum of Months | 975.23 | 741.32 | 448.80 | 175.45 | 295.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 399.96 | 757.74 | 436.30 | 270.36 | 165.94 | 0.00 | 0.00 |
February | 441.18 | 622.69 | 414.75 | 241.86 | 172.89 | 0.00 | 0.00 |
March | 509.52 | 383.46 | 404.85 | 173.96 | 230.88 | 0.00 | 0.00 |
April | 494.02 | 303.45 | 338.41 | 83.76 | 254.65 | 0.00 | 0.00 |
May | 493.34 | 185.25 | 306.64 | 27.87 | 278.77 | 0.00 | 0.00 |
June | 583.51 | 105.99 | 300.82 | 17.93 | 282.89 | 0.00 | 0.00 |
July | 606.09 | 67.24 | 295.22 | 18.12 | 277.10 | 0.00 | 0.00 |
August | 665.38 | 51.04 | 320.72 | 42.98 | 277.74 | 0.00 | 0.00 |
September | 565.56 | 146.31 | 325.37 | 97.80 | 227.57 | 0.00 | 0.00 |
October | 585.91 | 341.07 | 409.15 | 228.06 | 181.08 | 0.00 | 0.00 |
November | 539.70 | 466.99 | 435.89 | 257.25 | 178.64 | 0.00 | 0.00 |
December | 446.11 | 616.24 | 430.00 | 271.85 | 158.15 | 0.00 | 0.00 |
Annual Sum or Average | 528.03 | 335.84 | 367.99 | 143.85 | 224.15 | 0.00 | 0.00 |
Minimum of Months | 399.96 | 51.04 | 295.22 | 17.93 | 158.15 | 0.00 | 0.00 |
Maximum of Months | 665.38 | 757.74 | 436.30 | 271.85 | 282.89 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.162977E+10 | 0.150036E+10 | 0.141220E+10 | 0.981020E+09 | 0.431183E+09 | 0.00 | 0.00 |
February | 0.149132E+10 | 0.112779E+10 | 0.118818E+10 | 0.792686E+09 | 0.395494E+09 | 0.00 | 0.00 |
March | 0.168036E+10 | 0.805313E+09 | 0.120293E+10 | 0.631243E+09 | 0.571687E+09 | 0.00 | 0.00 |
April | 0.137750E+10 | 0.616431E+09 | 0.876087E+09 | 0.292293E+09 | 0.583795E+09 | 0.00 | 0.00 |
May | 0.122999E+10 | 0.393442E+09 | 0.727706E+09 | 89053889.35 | 0.638652E+09 | 0.00 | 0.00 |
June | 0.126605E+10 | 0.229470E+09 | 0.646621E+09 | 36100811.87 | 0.610520E+09 | 0.00 | 0.00 |
July | 0.137328E+10 | 0.150329E+09 | 0.670261E+09 | 45210453.17 | 0.625050E+09 | 0.00 | 0.00 |
August | 0.165234E+10 | 0.123464E+09 | 0.807634E+09 | 0.151787E+09 | 0.655847E+09 | 0.00 | 0.00 |
September | 0.155517E+10 | 0.308166E+09 | 0.882405E+09 | 0.343335E+09 | 0.539070E+09 | 0.00 | 0.00 |
October | 0.193755E+10 | 0.725098E+09 | 0.128037E+10 | 0.827554E+09 | 0.452812E+09 | 0.00 | 0.00 |
November | 0.184455E+10 | 0.945180E+09 | 0.135373E+10 | 0.903351E+09 | 0.450383E+09 | 0.00 | 0.00 |
December | 0.173276E+10 | 0.124815E+10 | 0.140226E+10 | 0.986443E+09 | 0.415820E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.187706E+11 | 0.817320E+10 | 0.124504E+11 | 0.608008E+10 | 0.637031E+10 | 0.00 | 0.00 |
Minimum of Months | 0.122999E+10 | 0.123464E+09 | 0.646621E+09 | 36100811.87 | 0.395494E+09 | 0.00 | 0.00 |
Maximum of Months | 0.193755E+10 | 0.150036E+10 | 0.141220E+10 | 0.986443E+09 | 0.655847E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.449750E+10 | 0.447503E+10 | 0.397667E+10 | 0.276249E+10 | 0.121418E+10 | 0.00 | 0.00 |
February | 0.411700E+10 | 0.342021E+10 | 0.334584E+10 | 0.223215E+10 | 0.111368E+10 | 0.00 | 0.00 |
March | 0.462965E+10 | 0.252332E+10 | 0.338737E+10 | 0.177754E+10 | 0.160983E+10 | 0.00 | 0.00 |
April | 0.379207E+10 | 0.193060E+10 | 0.246700E+10 | 0.823077E+09 | 0.164393E+10 | 0.00 | 0.00 |
May | 0.339131E+10 | 0.125364E+10 | 0.204917E+10 | 0.250770E+09 | 0.179840E+10 | 0.00 | 0.00 |
June | 0.354762E+10 | 0.703165E+09 | 0.182084E+10 | 0.101658E+09 | 0.171918E+10 | 0.00 | 0.00 |
July | 0.386208E+10 | 0.464170E+09 | 0.188741E+10 | 0.127310E+09 | 0.176010E+10 | 0.00 | 0.00 |
August | 0.465157E+10 | 0.368730E+09 | 0.227424E+10 | 0.427422E+09 | 0.184682E+10 | 0.00 | 0.00 |
September | 0.433127E+10 | 0.972522E+09 | 0.248479E+10 | 0.966809E+09 | 0.151798E+10 | 0.00 | 0.00 |
October | 0.537362E+10 | 0.226609E+10 | 0.360543E+10 | 0.233034E+10 | 0.127509E+10 | 0.00 | 0.00 |
November | 0.508669E+10 | 0.294073E+10 | 0.381203E+10 | 0.254378E+10 | 0.126825E+10 | 0.00 | 0.00 |
December | 0.478009E+10 | 0.379672E+10 | 0.394868E+10 | 0.277776E+10 | 0.117092E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.520605E+11 | 0.251149E+11 | 0.350595E+11 | 0.171211E+11 | 0.179384E+11 | 0.00 | 0.00 |
Minimum of Months | 0.339131E+10 | 0.368730E+09 | 0.182084E+10 | 0.101658E+09 | 0.111368E+10 | 0.00 | 0.00 |
Maximum of Months | 0.537362E+10 | 0.447503E+10 | 0.397667E+10 | 0.277776E+10 | 0.184682E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.594571E+10 | 0.605540E+10 | 0.516592E+10 | 0.358863E+10 | 0.157729E+10 | 0.00 | 0.00 |
February | 0.545427E+10 | 0.461894E+10 | 0.434643E+10 | 0.289969E+10 | 0.144674E+10 | 0.00 | 0.00 |
March | 0.614388E+10 | 0.337718E+10 | 0.440039E+10 | 0.230912E+10 | 0.209126E+10 | 0.00 | 0.00 |
April | 0.502749E+10 | 0.259731E+10 | 0.320478E+10 | 0.106922E+10 | 0.213555E+10 | 0.00 | 0.00 |
May | 0.449662E+10 | 0.168080E+10 | 0.266199E+10 | 0.325764E+09 | 0.233623E+10 | 0.00 | 0.00 |
June | 0.471730E+10 | 0.932391E+09 | 0.236538E+10 | 0.132059E+09 | 0.223332E+10 | 0.00 | 0.00 |
July | 0.514965E+10 | 0.610638E+09 | 0.245185E+10 | 0.165382E+09 | 0.228647E+10 | 0.00 | 0.00 |
August | 0.621952E+10 | 0.470401E+09 | 0.295437E+10 | 0.555246E+09 | 0.239913E+10 | 0.00 | 0.00 |
September | 0.575140E+10 | 0.129026E+10 | 0.322789E+10 | 0.125594E+10 | 0.197195E+10 | 0.00 | 0.00 |
October | 0.712797E+10 | 0.303627E+10 | 0.468365E+10 | 0.302724E+10 | 0.165641E+10 | 0.00 | 0.00 |
November | 0.672778E+10 | 0.395094E+10 | 0.495204E+10 | 0.330451E+10 | 0.164753E+10 | 0.00 | 0.00 |
December | 0.631584E+10 | 0.513958E+10 | 0.512956E+10 | 0.360846E+10 | 0.152109E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.690774E+11 | 0.337601E+11 | 0.455443E+11 | 0.222413E+11 | 0.233030E+11 | 0.00 | 0.00 |
Minimum of Months | 0.449662E+10 | 0.470401E+09 | 0.236538E+10 | 0.132059E+09 | 0.144674E+10 | 0.00 | 0.00 |
Maximum of Months | 0.712797E+10 | 0.605540E+10 | 0.516592E+10 | 0.360846E+10 | 0.239913E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.453998E+09 | 0.893120E+09 | 0.501844E+09 | 0.297480E+09 | 0.204364E+09 | 0.00 | 0.00 |
February | 0.503491E+09 | 0.659412E+09 | 0.465298E+09 | 0.264700E+09 | 0.200598E+09 | 0.00 | 0.00 |
March | 0.804842E+09 | 0.444157E+09 | 0.612039E+09 | 0.305281E+09 | 0.306758E+09 | 0.00 | 0.00 |
April | 0.881670E+09 | 0.324752E+09 | 0.581284E+09 | 0.244432E+09 | 0.336852E+09 | 0.00 | 0.00 |
May | 0.955107E+09 | 0.187671E+09 | 0.568158E+09 | 0.178638E+09 | 0.389520E+09 | 0.00 | 0.00 |
June | 0.108690E+10 | 85076414.27 | 0.559219E+09 | 0.173234E+09 | 0.385985E+09 | 0.00 | 0.00 |
July | 0.113194E+10 | 42148386.43 | 0.552093E+09 | 0.164131E+09 | 0.387962E+09 | 0.00 | 0.00 |
August | 0.118184E+10 | 21455551.29 | 0.571808E+09 | 0.184152E+09 | 0.387656E+09 | 0.00 | 0.00 |
September | 0.884859E+09 | 0.126390E+09 | 0.500287E+09 | 0.204092E+09 | 0.296195E+09 | 0.00 | 0.00 |
October | 0.808838E+09 | 0.386423E+09 | 0.552717E+09 | 0.319376E+09 | 0.233342E+09 | 0.00 | 0.00 |
November | 0.616604E+09 | 0.538694E+09 | 0.497906E+09 | 0.281572E+09 | 0.216334E+09 | 0.00 | 0.00 |
December | 0.478710E+09 | 0.730965E+09 | 0.474312E+09 | 0.281358E+09 | 0.192954E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.978880E+10 | 0.444026E+10 | 0.643697E+10 | 0.289845E+10 | 0.353852E+10 | 0.00 | 0.00 |
Minimum of Months | 0.453998E+09 | 21455551.29 | 0.465298E+09 | 0.164131E+09 | 0.192954E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118184E+10 | 0.893120E+09 | 0.612039E+09 | 0.319376E+09 | 0.389520E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.174032E+09 | 0.964318E+09 | 0.275215E+09 | 0.103516E+09 | 0.171700E+09 | 0.00 | 0.00 |
February | 0.259048E+09 | 0.705591E+09 | 0.283022E+09 | 0.107973E+09 | 0.175050E+09 | 0.00 | 0.00 |
March | 0.545976E+09 | 0.458492E+09 | 0.456053E+09 | 0.180475E+09 | 0.275578E+09 | 0.00 | 0.00 |
April | 0.725559E+09 | 0.335037E+09 | 0.504114E+09 | 0.187201E+09 | 0.316912E+09 | 0.00 | 0.00 |
May | 0.883533E+09 | 0.197427E+09 | 0.542695E+09 | 0.164744E+09 | 0.377951E+09 | 0.00 | 0.00 |
June | 0.106451E+10 | 87995474.72 | 0.557408E+09 | 0.174362E+09 | 0.383046E+09 | 0.00 | 0.00 |
July | 0.109681E+10 | 46553307.07 | 0.542915E+09 | 0.161512E+09 | 0.381403E+09 | 0.00 | 0.00 |
August | 0.107090E+10 | 24000100.12 | 0.521677E+09 | 0.155428E+09 | 0.366249E+09 | 0.00 | 0.00 |
September | 0.701948E+09 | 0.136941E+09 | 0.405848E+09 | 0.136240E+09 | 0.269608E+09 | 0.00 | 0.00 |
October | 0.494463E+09 | 0.403152E+09 | 0.362400E+09 | 0.155754E+09 | 0.206646E+09 | 0.00 | 0.00 |
November | 0.308567E+09 | 0.566905E+09 | 0.284668E+09 | 0.102964E+09 | 0.181704E+09 | 0.00 | 0.00 |
December | 0.183092E+09 | 0.785486E+09 | 0.245674E+09 | 86321527.55 | 0.159353E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.750845E+10 | 0.471190E+10 | 0.498169E+10 | 0.171649E+10 | 0.326520E+10 | 0.00 | 0.00 |
Minimum of Months | 0.174032E+09 | 24000100.12 | 0.245674E+09 | 86321527.55 | 0.159353E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109681E+10 | 0.964318E+09 | 0.557408E+09 | 0.187201E+09 | 0.383046E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.240815E+09 | 0.276745E+09 | 0.223330E+09 | 0.155141E+09 | 68188813.41 | 0.00 | 0.00 |
February | 0.214479E+09 | 0.232251E+09 | 0.187902E+09 | 0.125357E+09 | 62544840.67 | 0.00 | 0.00 |
March | 0.231241E+09 | 0.190662E+09 | 0.190235E+09 | 99826196.68 | 90408627.06 | 0.00 | 0.00 |
April | 0.185444E+09 | 0.150049E+09 | 0.138547E+09 | 46223853.60 | 92323562.43 | 0.00 | 0.00 |
May | 0.161437E+09 | 0.104146E+09 | 0.115082E+09 | 14083185.96 | 0.100999E+09 | 0.00 | 0.00 |
June | 0.172154E+09 | 63450135.28 | 0.102259E+09 | 5709065.05 | 96550134.41 | 0.00 | 0.00 |
July | 0.189687E+09 | 48206738.18 | 0.105998E+09 | 7149684.58 | 98847981.78 | 0.00 | 0.00 |
August | 0.236078E+09 | 41812497.21 | 0.127722E+09 | 24003960.40 | 0.103718E+09 | 0.00 | 0.00 |
September | 0.220060E+09 | 85475515.84 | 0.139546E+09 | 54295818.95 | 85250458.26 | 0.00 | 0.00 |
October | 0.278393E+09 | 0.173639E+09 | 0.202481E+09 | 0.130871E+09 | 71609428.64 | 0.00 | 0.00 |
November | 0.260931E+09 | 0.217475E+09 | 0.214083E+09 | 0.142858E+09 | 71225121.93 | 0.00 | 0.00 |
December | 0.245593E+09 | 0.268731E+09 | 0.221757E+09 | 0.155998E+09 | 65759141.47 | 0.00 | 0.00 |
Annual Sum or Average | 0.263631E+10 | 0.185264E+10 | 0.196894E+10 | 0.961517E+09 | 0.100743E+10 | 0.00 | 0.00 |
Minimum of Months | 0.161437E+09 | 41812497.21 | 0.102259E+09 | 5709065.05 | 62544840.67 | 0.00 | 0.00 |
Maximum of Months | 0.278393E+09 | 0.276745E+09 | 0.223330E+09 | 0.155998E+09 | 0.103718E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 5897974.58 | 0.301561E+09 | 42076451.99 | 0.00 | 42076451.99 | 0.00 | 0.00 |
February | 20016960.96 | 0.216430E+09 | 42124339.93 | 0.00 | 42124339.93 | 0.00 | 0.00 |
March | 53897000.52 | 0.132021E+09 | 65492691.15 | 1318.99 | 65491372.16 | 0.00 | 0.00 |
April | 99517047.38 | 91763245.30 | 76848851.72 | 448829.91 | 76400021.81 | 0.00 | 0.00 |
May | 0.155421E+09 | 50377894.65 | 94747450.04 | 2971603.27 | 91775846.77 | 0.00 | 0.00 |
June | 0.214282E+09 | 20594242.88 | 0.100844E+09 | 6613320.29 | 94230889.24 | 0.00 | 0.00 |
July | 0.226604E+09 | 10359055.44 | 98689421.90 | 5056973.36 | 93632448.53 | 0.00 | 0.00 |
August | 0.211134E+09 | 4453437.61 | 87654522.95 | 1029768.70 | 86624754.24 | 0.00 | 0.00 |
September | 0.117809E+09 | 35371851.01 | 64031230.67 | 25170.94 | 64006059.72 | 0.00 | 0.00 |
October | 55226828.84 | 0.114302E+09 | 50273499.29 | 0.00 | 50273499.29 | 0.00 | 0.00 |
November | 27718443.46 | 0.166988E+09 | 43541540.27 | 0.00 | 43541540.27 | 0.00 | 0.00 |
December | 7458715.25 | 0.240031E+09 | 38896548.34 | 0.00 | 38896548.34 | 0.00 | 0.00 |
Annual Sum or Average | 0.119498E+10 | 0.138425E+10 | 0.805221E+09 | 16146985.47 | 0.789074E+09 | 0.00 | 0.00 |
Minimum of Months | 5897974.58 | 4453437.61 | 38896548.34 | 0.00 | 38896548.34 | 0.00 | 0.00 |
Maximum of Months | 0.226604E+09 | 0.301561E+09 | 0.100844E+09 | 6613320.29 | 94230889.24 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.432788E+09 | 0.880278E+09 | 0.496486E+09 | 0.292891E+09 | 0.203596E+09 | 0.00 | 0.00 |
February | 0.513574E+09 | 0.644685E+09 | 0.481219E+09 | 0.289311E+09 | 0.191908E+09 | 0.00 | 0.00 |
March | 0.730286E+09 | 0.422803E+09 | 0.580914E+09 | 0.281299E+09 | 0.299614E+09 | 0.00 | 0.00 |
April | 0.846833E+09 | 0.302034E+09 | 0.574551E+09 | 0.240974E+09 | 0.333577E+09 | 0.00 | 0.00 |
May | 0.987963E+09 | 0.173965E+09 | 0.598187E+09 | 0.209729E+09 | 0.388458E+09 | 0.00 | 0.00 |
June | 0.111823E+10 | 77671686.06 | 0.582588E+09 | 0.197605E+09 | 0.384983E+09 | 0.00 | 0.00 |
July | 0.119206E+10 | 40530656.79 | 0.590525E+09 | 0.201092E+09 | 0.389433E+09 | 0.00 | 0.00 |
August | 0.119527E+10 | 20198471.64 | 0.579466E+09 | 0.196526E+09 | 0.382940E+09 | 0.00 | 0.00 |
September | 0.892173E+09 | 0.120850E+09 | 0.507408E+09 | 0.214997E+09 | 0.292411E+09 | 0.00 | 0.00 |
October | 0.782479E+09 | 0.370872E+09 | 0.547407E+09 | 0.316785E+09 | 0.230622E+09 | 0.00 | 0.00 |
November | 0.592652E+09 | 0.521001E+09 | 0.494448E+09 | 0.280911E+09 | 0.213537E+09 | 0.00 | 0.00 |
December | 0.473238E+09 | 0.715517E+09 | 0.480619E+09 | 0.287609E+09 | 0.193010E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.975755E+10 | 0.429041E+10 | 0.651382E+10 | 0.300973E+10 | 0.350409E+10 | 0.00 | 0.00 |
Minimum of Months | 0.432788E+09 | 20198471.64 | 0.480619E+09 | 0.196526E+09 | 0.191908E+09 | 0.00 | 0.00 |
Maximum of Months | 0.119527E+10 | 0.880278E+09 | 0.598187E+09 | 0.316785E+09 | 0.389433E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.135213E+09 | 0.933158E+09 | 0.269858E+09 | 98926312.94 | 0.170931E+09 | 0.00 | 0.00 |
February | 0.246189E+09 | 0.666597E+09 | 0.298943E+09 | 0.132584E+09 | 0.166359E+09 | 0.00 | 0.00 |
March | 0.463534E+09 | 0.424305E+09 | 0.424928E+09 | 0.156494E+09 | 0.268435E+09 | 0.00 | 0.00 |
April | 0.691468E+09 | 0.309858E+09 | 0.497381E+09 | 0.183744E+09 | 0.313637E+09 | 0.00 | 0.00 |
May | 0.918121E+09 | 0.185874E+09 | 0.572725E+09 | 0.195836E+09 | 0.376889E+09 | 0.00 | 0.00 |
June | 0.109423E+10 | 83449228.29 | 0.580777E+09 | 0.198732E+09 | 0.382045E+09 | 0.00 | 0.00 |
July | 0.115266E+10 | 46064822.16 | 0.581347E+09 | 0.198474E+09 | 0.382873E+09 | 0.00 | 0.00 |
August | 0.108135E+10 | 22657161.57 | 0.529335E+09 | 0.167803E+09 | 0.361533E+09 | 0.00 | 0.00 |
September | 0.705481E+09 | 0.129895E+09 | 0.412969E+09 | 0.147145E+09 | 0.265824E+09 | 0.00 | 0.00 |
October | 0.458407E+09 | 0.374999E+09 | 0.357089E+09 | 0.153163E+09 | 0.203926E+09 | 0.00 | 0.00 |
November | 0.261880E+09 | 0.522241E+09 | 0.281211E+09 | 0.102303E+09 | 0.178908E+09 | 0.00 | 0.00 |
December | 0.145176E+09 | 0.736277E+09 | 0.251981E+09 | 92572432.32 | 0.159409E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.735371E+10 | 0.443537E+10 | 0.505854E+10 | 0.182778E+10 | 0.323077E+10 | 0.00 | 0.00 |
Minimum of Months | 0.135213E+09 | 22657161.57 | 0.251981E+09 | 92572432.32 | 0.159409E+09 | 0.00 | 0.00 |
Maximum of Months | 0.115266E+10 | 0.933158E+09 | 0.581347E+09 | 0.198732E+09 | 0.382873E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.488722E+09 | 0.113754E+10 | 0.575045E+09 | 0.336147E+09 | 0.238898E+09 | 0.00 | 0.00 |
February | 0.508682E+09 | 0.841301E+09 | 0.498387E+09 | 0.271614E+09 | 0.226773E+09 | 0.00 | 0.00 |
March | 0.689102E+09 | 0.577521E+09 | 0.554065E+09 | 0.216298E+09 | 0.337767E+09 | 0.00 | 0.00 |
April | 0.688105E+09 | 0.438144E+09 | 0.466674E+09 | 0.101127E+09 | 0.365548E+09 | 0.00 | 0.00 |
May | 0.756753E+09 | 0.265728E+09 | 0.454606E+09 | 36951836.71 | 0.417654E+09 | 0.00 | 0.00 |
June | 0.888649E+09 | 0.140724E+09 | 0.440030E+09 | 26696625.66 | 0.413333E+09 | 0.00 | 0.00 |
July | 0.944365E+09 | 91543487.49 | 0.443462E+09 | 26446478.24 | 0.417015E+09 | 0.00 | 0.00 |
August | 0.100556E+10 | 65046912.23 | 0.466627E+09 | 54240731.23 | 0.412387E+09 | 0.00 | 0.00 |
September | 0.783835E+09 | 0.207440E+09 | 0.441071E+09 | 0.117698E+09 | 0.323373E+09 | 0.00 | 0.00 |
October | 0.779356E+09 | 0.516781E+09 | 0.547629E+09 | 0.283562E+09 | 0.264067E+09 | 0.00 | 0.00 |
November | 0.676330E+09 | 0.680404E+09 | 0.558184E+09 | 0.309534E+09 | 0.248651E+09 | 0.00 | 0.00 |
December | 0.556230E+09 | 0.922159E+09 | 0.564750E+09 | 0.338005E+09 | 0.226745E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.876569E+10 | 0.588433E+10 | 0.601053E+10 | 0.211832E+10 | 0.389221E+10 | 0.00 | 0.00 |
Minimum of Months | 0.488722E+09 | 65046912.23 | 0.440030E+09 | 26446478.24 | 0.226745E+09 | 0.00 | 0.00 |
Maximum of Months | 0.100556E+10 | 0.113754E+10 | 0.575045E+09 | 0.338005E+09 | 0.417654E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.454269E+09 | 0.887745E+09 | 0.501844E+09 | 0.297480E+09 | 0.204364E+09 | 0.00 | 0.00 |
February | 0.502023E+09 | 0.653704E+09 | 0.465298E+09 | 0.264700E+09 | 0.200598E+09 | 0.00 | 0.00 |
March | 0.798640E+09 | 0.437836E+09 | 0.612039E+09 | 0.305281E+09 | 0.306758E+09 | 0.00 | 0.00 |
April | 0.873934E+09 | 0.320198E+09 | 0.581284E+09 | 0.244432E+09 | 0.336852E+09 | 0.00 | 0.00 |
May | 0.945941E+09 | 0.184118E+09 | 0.568158E+09 | 0.178638E+09 | 0.389520E+09 | 0.00 | 0.00 |
June | 0.107946E+10 | 81412902.71 | 0.559219E+09 | 0.173234E+09 | 0.385985E+09 | 0.00 | 0.00 |
July | 0.112548E+10 | 39106360.29 | 0.552093E+09 | 0.164131E+09 | 0.387962E+09 | 0.00 | 0.00 |
August | 0.117544E+10 | 19040548.86 | 0.571808E+09 | 0.184152E+09 | 0.387656E+09 | 0.00 | 0.00 |
September | 0.879731E+09 | 0.121439E+09 | 0.500287E+09 | 0.204092E+09 | 0.296195E+09 | 0.00 | 0.00 |
October | 0.804289E+09 | 0.379016E+09 | 0.552717E+09 | 0.319376E+09 | 0.233342E+09 | 0.00 | 0.00 |
November | 0.614805E+09 | 0.531684E+09 | 0.497906E+09 | 0.281572E+09 | 0.216334E+09 | 0.00 | 0.00 |
December | 0.479086E+09 | 0.723875E+09 | 0.474312E+09 | 0.281358E+09 | 0.192954E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.973310E+10 | 0.437917E+10 | 0.643697E+10 | 0.289845E+10 | 0.353852E+10 | 0.00 | 0.00 |
Minimum of Months | 0.454269E+09 | 19040548.86 | 0.465298E+09 | 0.164131E+09 | 0.192954E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117544E+10 | 0.887745E+09 | 0.612039E+09 | 0.319376E+09 | 0.389520E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.175479E+09 | 0.959213E+09 | 0.275215E+09 | 0.103516E+09 | 0.171700E+09 | 0.00 | 0.00 |
February | 0.259321E+09 | 0.699554E+09 | 0.283022E+09 | 0.107973E+09 | 0.175050E+09 | 0.00 | 0.00 |
March | 0.543160E+09 | 0.451565E+09 | 0.456053E+09 | 0.180475E+09 | 0.275578E+09 | 0.00 | 0.00 |
April | 0.718997E+09 | 0.332397E+09 | 0.504114E+09 | 0.187201E+09 | 0.316912E+09 | 0.00 | 0.00 |
May | 0.874574E+09 | 0.195784E+09 | 0.542695E+09 | 0.164744E+09 | 0.377951E+09 | 0.00 | 0.00 |
June | 0.105767E+10 | 84995781.51 | 0.557408E+09 | 0.174362E+09 | 0.383046E+09 | 0.00 | 0.00 |
July | 0.109104E+10 | 43806624.33 | 0.542915E+09 | 0.161512E+09 | 0.381403E+09 | 0.00 | 0.00 |
August | 0.106575E+10 | 21391650.93 | 0.521677E+09 | 0.155428E+09 | 0.366249E+09 | 0.00 | 0.00 |
September | 0.698649E+09 | 0.131610E+09 | 0.405848E+09 | 0.136240E+09 | 0.269608E+09 | 0.00 | 0.00 |
October | 0.493555E+09 | 0.394571E+09 | 0.362400E+09 | 0.155754E+09 | 0.206646E+09 | 0.00 | 0.00 |
November | 0.310235E+09 | 0.557519E+09 | 0.284668E+09 | 0.102964E+09 | 0.181704E+09 | 0.00 | 0.00 |
December | 0.186081E+09 | 0.776890E+09 | 0.245674E+09 | 86321527.55 | 0.159353E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.747451E+10 | 0.464930E+10 | 0.498169E+10 | 0.171649E+10 | 0.326520E+10 | 0.00 | 0.00 |
Minimum of Months | 0.175479E+09 | 21391650.93 | 0.245674E+09 | 86321527.55 | 0.159353E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109104E+10 | 0.959213E+09 | 0.557408E+09 | 0.187201E+09 | 0.383046E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.453901E+09 | 0.459813E+09 | 0.409499E+09 | 0.284468E+09 | 0.125032E+09 | 0.00 | 0.00 |
February | 0.418719E+09 | 0.341064E+09 | 0.344539E+09 | 0.229856E+09 | 0.114683E+09 | 0.00 | 0.00 |
March | 0.477595E+09 | 0.227994E+09 | 0.348816E+09 | 0.183042E+09 | 0.165774E+09 | 0.00 | 0.00 |
April | 0.398181E+09 | 0.165481E+09 | 0.254042E+09 | 84756499.22 | 0.169285E+09 | 0.00 | 0.00 |
May | 0.366300E+09 | 91498801.03 | 0.211016E+09 | 25823064.22 | 0.185193E+09 | 0.00 | 0.00 |
June | 0.400324E+09 | 38563009.36 | 0.187503E+09 | 10468196.17 | 0.177035E+09 | 0.00 | 0.00 |
July | 0.441773E+09 | 17793178.38 | 0.194358E+09 | 13109729.90 | 0.181249E+09 | 0.00 | 0.00 |
August | 0.527455E+09 | 8189186.36 | 0.234192E+09 | 44013890.93 | 0.190178E+09 | 0.00 | 0.00 |
September | 0.468676E+09 | 60923613.00 | 0.255873E+09 | 99557331.94 | 0.156316E+09 | 0.00 | 0.00 |
October | 0.561350E+09 | 0.196146E+09 | 0.371270E+09 | 0.239967E+09 | 0.131304E+09 | 0.00 | 0.00 |
November | 0.525281E+09 | 0.276070E+09 | 0.392545E+09 | 0.261946E+09 | 0.130599E+09 | 0.00 | 0.00 |
December | 0.486541E+09 | 0.377206E+09 | 0.406617E+09 | 0.286040E+09 | 0.120577E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.552610E+10 | 0.226074E+10 | 0.361027E+10 | 0.176305E+10 | 0.184722E+10 | 0.00 | 0.00 |
Minimum of Months | 0.366300E+09 | 8189186.36 | 0.187503E+09 | 10468196.17 | 0.114683E+09 | 0.00 | 0.00 |
Maximum of Months | 0.561350E+09 | 0.459813E+09 | 0.409499E+09 | 0.286040E+09 | 0.190178E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 33835386.11 | 0.305986E+10 | 0.368106E+09 | 0.00 | 0.368106E+09 | 0.00 | 0.00 |
February | 0.131164E+09 | 0.224291E+10 | 0.368525E+09 | 0.00 | 0.368525E+09 | 0.00 | 0.00 |
March | 0.361528E+09 | 0.145738E+10 | 0.572963E+09 | 11539.19 | 0.572952E+09 | 0.00 | 0.00 |
April | 0.736251E+09 | 0.102705E+10 | 0.672313E+09 | 3926592.47 | 0.668386E+09 | 0.00 | 0.00 |
May | 0.119372E+10 | 0.624382E+09 | 0.828899E+09 | 25997097.83 | 0.802902E+09 | 0.00 | 0.00 |
June | 0.166951E+10 | 0.328833E+09 | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.00 | 0.00 |
July | 0.175229E+10 | 0.219916E+09 | 0.863385E+09 | 44240976.70 | 0.819144E+09 | 0.00 | 0.00 |
August | 0.159752E+10 | 0.164683E+09 | 0.766846E+09 | 9008940.72 | 0.757837E+09 | 0.00 | 0.00 |
September | 0.879910E+09 | 0.493859E+09 | 0.560178E+09 | 220208.23 | 0.559958E+09 | 0.00 | 0.00 |
October | 0.383247E+09 | 0.128718E+10 | 0.439818E+09 | 0.00 | 0.439818E+09 | 0.00 | 0.00 |
November | 0.168898E+09 | 0.178577E+10 | 0.380924E+09 | 0.00 | 0.380924E+09 | 0.00 | 0.00 |
December | 34424927.98 | 0.251219E+10 | 0.340287E+09 | 0.00 | 0.340287E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.894230E+10 | 0.152040E+11 | 0.704448E+10 | 0.141262E+09 | 0.690322E+10 | 0.00 | 0.00 |
Minimum of Months | 33835386.11 | 0.164683E+09 | 0.340287E+09 | 0.00 | 0.340287E+09 | 0.00 | 0.00 |
Maximum of Months | 0.175229E+10 | 0.305986E+10 | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 29124510.44 | 0.315953E+10 | 0.368106E+09 | 0.00 | 0.368106E+09 | 0.00 | 0.00 |
February | 0.119971E+09 | 0.231891E+10 | 0.368525E+09 | 0.00 | 0.368525E+09 | 0.00 | 0.00 |
March | 0.334336E+09 | 0.151059E+10 | 0.572963E+09 | 11539.19 | 0.572952E+09 | 0.00 | 0.00 |
April | 0.706574E+09 | 0.105973E+10 | 0.672313E+09 | 3926592.47 | 0.668386E+09 | 0.00 | 0.00 |
May | 0.116357E+10 | 0.646616E+09 | 0.828899E+09 | 25997097.83 | 0.802902E+09 | 0.00 | 0.00 |
June | 0.164346E+10 | 0.342654E+09 | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.00 | 0.00 |
July | 0.172631E+10 | 0.232223E+09 | 0.863385E+09 | 44240976.70 | 0.819144E+09 | 0.00 | 0.00 |
August | 0.157231E+10 | 0.176666E+09 | 0.766846E+09 | 9008940.72 | 0.757837E+09 | 0.00 | 0.00 |
September | 0.855358E+09 | 0.516828E+09 | 0.560178E+09 | 220208.23 | 0.559958E+09 | 0.00 | 0.00 |
October | 0.361236E+09 | 0.133574E+10 | 0.439818E+09 | 0.00 | 0.439818E+09 | 0.00 | 0.00 |
November | 0.149432E+09 | 0.185000E+10 | 0.380924E+09 | 0.00 | 0.380924E+09 | 0.00 | 0.00 |
December | 28142983.05 | 0.260288E+10 | 0.340287E+09 | 0.00 | 0.340287E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.868982E+10 | 0.157524E+11 | 0.704448E+10 | 0.141262E+09 | 0.690322E+10 | 0.00 | 0.00 |
Minimum of Months | 28142983.05 | 0.176666E+09 | 0.340287E+09 | 0.00 | 0.340287E+09 | 0.00 | 0.00 |
Maximum of Months | 0.172631E+10 | 0.315953E+10 | 0.882236E+09 | 57856691.74 | 0.824380E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.527528E+09 | 0.198554E+10 | 0.766313E+09 | 0.391803E+09 | 0.374510E+09 | 0.00 | 0.00 |
February | 0.766060E+09 | 0.147578E+10 | 0.780127E+09 | 0.421877E+09 | 0.358251E+09 | 0.00 | 0.00 |
March | 0.129518E+10 | 0.100241E+10 | 0.100579E+10 | 0.437771E+09 | 0.568023E+09 | 0.00 | 0.00 |
April | 0.171086E+10 | 0.735668E+09 | 0.107188E+10 | 0.424692E+09 | 0.647183E+09 | 0.00 | 0.00 |
May | 0.213993E+10 | 0.484532E+09 | 0.117085E+10 | 0.405538E+09 | 0.765309E+09 | 0.00 | 0.00 |
June | 0.246776E+10 | 0.277415E+09 | 0.116330E+10 | 0.396310E+09 | 0.766990E+09 | 0.00 | 0.00 |
July | 0.261206E+10 | 0.190229E+09 | 0.117181E+10 | 0.399539E+09 | 0.772269E+09 | 0.00 | 0.00 |
August | 0.253305E+10 | 0.145020E+09 | 0.110874E+10 | 0.364305E+09 | 0.744437E+09 | 0.00 | 0.00 |
September | 0.181387E+10 | 0.352134E+09 | 0.920329E+09 | 0.362120E+09 | 0.558209E+09 | 0.00 | 0.00 |
October | 0.137241E+10 | 0.880452E+09 | 0.904454E+09 | 0.469926E+09 | 0.434528E+09 | 0.00 | 0.00 |
November | 0.917284E+09 | 0.118417E+10 | 0.775627E+09 | 0.383200E+09 | 0.392427E+09 | 0.00 | 0.00 |
December | 0.608832E+09 | 0.162589E+10 | 0.732571E+09 | 0.380168E+09 | 0.352403E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.187648E+11 | 0.103392E+11 | 0.115718E+11 | 0.483725E+10 | 0.673454E+10 | 0.00 | 0.00 |
Minimum of Months | 0.527528E+09 | 0.145020E+09 | 0.732571E+09 | 0.362120E+09 | 0.352403E+09 | 0.00 | 0.00 |
Maximum of Months | 0.261206E+10 | 0.198554E+10 | 0.117181E+10 | 0.469926E+09 | 0.772269E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.107126E+10 | 0.202954E+10 | 0.116859E+10 | 0.724128E+09 | 0.444462E+09 | 0.00 | 0.00 |
February | 0.106729E+10 | 0.150642E+10 | 0.100337E+10 | 0.585111E+09 | 0.418262E+09 | 0.00 | 0.00 |
March | 0.136470E+10 | 0.102706E+10 | 0.108434E+10 | 0.465948E+09 | 0.618396E+09 | 0.00 | 0.00 |
April | 0.128050E+10 | 0.786536E+09 | 0.877147E+09 | 0.217098E+09 | 0.660049E+09 | 0.00 | 0.00 |
May | 0.132136E+10 | 0.496166E+09 | 0.821300E+09 | 74645838.28 | 0.746654E+09 | 0.00 | 0.00 |
June | 0.151247E+10 | 0.274728E+09 | 0.779732E+09 | 46480736.68 | 0.733252E+09 | 0.00 | 0.00 |
July | 0.162336E+10 | 0.180084E+09 | 0.790720E+09 | 48537407.44 | 0.742182E+09 | 0.00 | 0.00 |
August | 0.178215E+10 | 0.136718E+09 | 0.859026E+09 | 0.115128E+09 | 0.743898E+09 | 0.00 | 0.00 |
September | 0.146592E+10 | 0.379238E+09 | 0.843369E+09 | 0.253504E+09 | 0.589865E+09 | 0.00 | 0.00 |
October | 0.156929E+10 | 0.913525E+09 | 0.109586E+10 | 0.610848E+09 | 0.485011E+09 | 0.00 | 0.00 |
November | 0.139889E+10 | 0.121044E+10 | 0.112983E+10 | 0.666797E+09 | 0.463028E+09 | 0.00 | 0.00 |
December | 0.119485E+10 | 0.165053E+10 | 0.115171E+10 | 0.728130E+09 | 0.423585E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.166521E+11 | 0.105910E+11 | 0.116050E+11 | 0.453636E+10 | 0.706864E+10 | 0.00 | 0.00 |
Minimum of Months | 0.106729E+10 | 0.136718E+09 | 0.779732E+09 | 46480736.68 | 0.418262E+09 | 0.00 | 0.00 |
Maximum of Months | 0.178215E+10 | 0.202954E+10 | 0.116859E+10 | 0.728130E+09 | 0.746654E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770533E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162552534.7 | 81.21 | 0.00 | 0.00 |
February | 0.696265E+10 | -0.681598E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146673384.9 | 81.21 | 0.00 | 0.00 |
March | 0.770356E+10 | -0.754148E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162084065.8 | 81.21 | 0.00 | 0.00 |
April | 0.746524E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156650445.3 | 81.21 | 0.00 | 0.00 |
May | 0.770456E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161768294.3 | 81.21 | 0.00 | 0.00 |
June | 0.745696E+10 | -0.730052E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156431134.0 | 81.21 | 0.00 | 0.00 |
July | 0.771245E+10 | -0.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161611555.9 | 81.21 | 0.00 | 0.00 |
August | 0.770439E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161586453.2 | 81.21 | 0.00 | 0.00 |
September | 0.746644E+10 | -0.730993E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156515141.8 | 81.21 | 0.00 | 0.00 |
October | 0.770343E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161995067.5 | 81.21 | 0.00 | 0.00 |
November | 0.744942E+10 | -0.729244E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156981926.5 | 81.21 | 0.00 | 0.00 |
December | 0.771325E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162399733.8 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907477E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190725E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696265E+10 | -0.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162552534.7 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771325E+10 | -0.681598E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146673384.9 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYSLAUNDRY HPWH TANK
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.577442E+11 | -0.112936E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -858436240.6 | 81.67 | 0.00 | 0.00 |
February | 0.478051E+11 | -0.102144E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -747308355.4 | 81.67 | 0.00 | 0.00 |
March | 0.430310E+11 | -0.110520E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -782585925.3 | 81.67 | 0.00 | 0.00 |
April | 0.324237E+11 | -0.102355E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -732092716.6 | 81.67 | 0.00 | 0.00 |
May | 0.231704E+11 | -0.100122E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -727935299.0 | 81.68 | 0.00 | 0.00 |
June | 0.139456E+11 | -0.920407E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -675643382.9 | 81.68 | 0.00 | 0.00 |
July | 0.904259E+10 | -0.920906E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -688256456.5 | 81.68 | 0.00 | 0.00 |
August | 0.821797E+10 | -0.918779E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -684486843.1 | 81.67 | 0.00 | 0.00 |
September | 0.148096E+11 | -0.914774E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -692551517.5 | 81.68 | 0.00 | 0.00 |
October | 0.275565E+11 | -0.993307E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -765280514.6 | 81.67 | 0.00 | 0.00 |
November | 0.380551E+11 | -0.101594E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -771828279.1 | 81.68 | 0.00 | 0.00 |
December | 0.498646E+11 | -0.109948E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -829859307.2 | 81.67 | 0.00 | 0.00 |
Annual Sum or Average | 0.365666E+12 | -0.120644E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.895626E+10 | 81.68 | 0.00 | 0.00 |
Minimum of Months | 0.821797E+10 | -0.112936E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -858436240.6 | 81.67 | 0.00 | 0.00 |
Maximum of Months | 0.577442E+11 | -0.914774E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -675643382.9 | 81.68 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 HPWH TANK
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | -0.176471E+10 | -0.674729E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.139105E+10 | 59.29 | 0.00 | 0.00 |
February | -0.187760E+10 | -0.610950E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.118873E+10 | 59.28 | 0.00 | 0.00 |
March | -0.255797E+10 | -0.654956E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.120914E+10 | 59.31 | 0.00 | 0.00 |
April | -0.244623E+10 | -0.593873E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.111067E+10 | 59.35 | 0.00 | 0.00 |
May | -0.247398E+10 | -0.565055E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.108021E+10 | 59.39 | 0.00 | 0.00 |
June | -0.201823E+10 | -0.505075E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -977567067.7 | 59.43 | 0.00 | 0.00 |
July | -0.192504E+10 | -0.495281E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -987035484.9 | 59.46 | 0.00 | 0.00 |
August | -0.195245E+10 | -0.493936E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -978170205.4 | 59.46 | 0.00 | 0.00 |
September | -0.197189E+10 | -0.499975E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.101835E+10 | 59.44 | 0.00 | 0.00 |
October | -0.228719E+10 | -0.557887E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.117081E+10 | 59.41 | 0.00 | 0.00 |
November | -0.220479E+10 | -0.586982E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.120641E+10 | 59.36 | 0.00 | 0.00 |
December | -0.201672E+10 | -0.649227E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.132324E+10 | 59.32 | 0.00 | 0.00 |
Annual Sum or Average | -0.254968E+11 | -0.688793E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.136414E+11 | 59.37 | 0.00 | 0.00 |
Minimum of Months | -0.255797E+10 | -0.674729E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.139105E+10 | 59.28 | 0.00 | 0.00 |
Maximum of Months | -0.176471E+10 | -0.493936E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -977567067.7 | 59.46 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.87 | 0.86 | 01-JAN-09:20 | 4810.38 | 33.78 | 269.00 | 273.50 | 741.71 | 25.18 | 151.33 | 241.67 |
February | 263.00 | 0.87 | 0.86 | 01-FEB-13:39 | 4266.88 | 30.58 | 190.67 | 246.83 | 522.58 | 21.54 | 97.50 | 198.00 |
March | 351.67 | 0.87 | 0.86 | 01-MAR-08:00 | 1056.89 | 19.19 | 10.83 | 318.00 | 406.47 | 20.61 | 139.17 | 246.00 |
April | 369.33 | 0.87 | 0.86 | 01-APR-09:00 | 845.23 | 18.68 | 0.00 | 322.50 | 334.92 | 20.43 | 116.33 | 236.00 |
May | 407.00 | 0.87 | 0.86 | 01-MAY-07:00 | 800.66 | 18.64 | 0.00 | 357.17 | 317.53 | 20.38 | 152.83 | 259.83 |
June | 411.67 | 0.88 | 0.86 | 01-JUN-07:30 | 739.11 | 18.40 | 0.00 | 356.83 | 297.30 | 20.16 | 141.67 | 241.50 |
July | 411.00 | 0.88 | 0.86 | 01-JUL-08:39 | 782.10 | 18.50 | 0.00 | 361.50 | 311.90 | 20.24 | 172.50 | 260.67 |
August | 390.50 | 0.87 | 0.86 | 01-AUG-07:00 | 968.53 | 19.17 | 0.00 | 350.17 | 378.70 | 20.89 | 213.33 | 279.33 |
September | 298.50 | 0.87 | 0.86 | 01-SEP-07:00 | 1018.70 | 19.11 | 0.00 | 308.17 | 402.18 | 20.85 | 149.67 | 223.17 |
October | 293.50 | 0.87 | 0.86 | 01-OCT-10:39 | 2457.31 | 24.40 | 105.00 | 289.50 | 415.76 | 20.68 | 95.83 | 209.50 |
November | 299.00 | 0.87 | 0.86 | 01-NOV-08:39 | 4784.52 | 34.53 | 285.17 | 273.17 | 601.17 | 24.85 | 156.33 | 239.83 |
December | 285.17 | 0.87 | 0.86 | 01-DEC-07:00 | 4501.80 | 34.28 | 269.67 | 268.00 | 831.29 | 26.35 | 158.83 | 232.67 |
Annual Sum or Average | 4071.00 | 0.87 | 2032.35 | 23.27 | 1130.33 | 3725.33 | 443.69 | 21.64 | 1745.33 | 2868.17 | ||
Minimum of Months | 263.00 | 0.87 | 0.86 | 739.11 | 18.40 | 0.00 | 246.83 | 297.30 | 20.16 | 95.83 | 198.00 | |
Maximum of Months | 411.67 | 0.88 | 0.86 | 4810.38 | 34.53 | 285.17 | 361.50 | 831.29 | 26.35 | 213.33 | 279.33 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.24 | 0.22 | 01-JAN-08:00 | 5101.01 | 33.90 | 271.67 | 281.50 | 1031.72 | 25.14 | 165.83 | 262.17 |
February | 263.00 | 0.26 | 0.22 | 01-FEB-10:20 | 4543.25 | 30.69 | 191.83 | 258.33 | 798.39 | 21.67 | 101.83 | 222.00 |
March | 351.67 | 0.26 | 0.22 | 01-MAR-08:39 | 1281.88 | 19.69 | 18.33 | 331.83 | 630.73 | 20.95 | 161.17 | 296.83 |
April | 369.33 | 0.27 | 0.22 | 01-APR-08:09 | 1011.06 | 19.41 | 0.83 | 340.83 | 500.21 | 20.93 | 167.50 | 297.50 |
May | 407.00 | 0.26 | 0.22 | 01-MAY-07:19 | 934.53 | 19.51 | 1.33 | 379.50 | 450.90 | 21.02 | 223.00 | 327.33 |
June | 411.67 | 0.27 | 0.22 | 01-JUN-06:49 | 861.61 | 19.31 | 0.33 | 378.67 | 419.36 | 20.84 | 209.83 | 330.00 |
July | 411.00 | 0.27 | 0.22 | 01-JUL-06:00 | 908.39 | 19.40 | 0.33 | 382.33 | 437.70 | 20.90 | 234.00 | 330.33 |
August | 390.50 | 0.26 | 0.22 | 01-AUG-07:10 | 1124.13 | 19.95 | 16.00 | 365.17 | 533.70 | 21.45 | 255.33 | 326.17 |
September | 298.50 | 0.27 | 0.22 | 01-SEP-07:19 | 1211.51 | 19.74 | 9.00 | 322.17 | 594.37 | 21.28 | 175.17 | 285.00 |
October | 293.50 | 0.26 | 0.22 | 01-OCT-08:09 | 2727.60 | 24.56 | 108.50 | 304.00 | 683.42 | 20.80 | 103.00 | 261.83 |
November | 299.00 | 0.26 | 0.22 | 01-NOV-08:09 | 5063.09 | 34.62 | 286.17 | 281.33 | 877.87 | 24.86 | 167.67 | 264.00 |
December | 285.17 | 0.24 | 0.22 | 01-DEC-07:49 | 4797.33 | 34.39 | 271.00 | 278.00 | 1124.77 | 26.31 | 167.50 | 256.67 |
Annual Sum or Average | 4071.00 | 0.26 | 2233.66 | 23.81 | 1175.33 | 3903.67 | 644.09 | 22.01 | 2131.83 | 3459.83 | ||
Minimum of Months | 263.00 | 0.24 | 0.22 | 861.61 | 19.31 | 0.33 | 258.33 | 419.36 | 20.80 | 101.83 | 222.00 | |
Maximum of Months | 411.67 | 0.27 | 0.22 | 5101.01 | 34.62 | 286.17 | 382.33 | 1124.77 | 26.31 | 255.33 | 330.33 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.69 | 0.60 | 01-JAN-11:09 | 301.69 | 13.68 | 0.00 | 195.50 | 139.89 | 17.11 | 0.00 | 33.83 |
February | 263.00 | 0.69 | 0.60 | 01-FEB-13:50 | 311.13 | 13.86 | 0.00 | 183.17 | 147.54 | 17.25 | 0.00 | 59.67 |
March | 351.67 | 0.65 | 0.60 | 01-MAR-09:20 | 402.95 | 15.41 | 0.00 | 306.33 | 188.03 | 18.66 | 0.00 | 149.33 |
April | 369.33 | 0.63 | 0.60 | 01-APR-10:20 | 489.90 | 16.33 | 0.00 | 336.83 | 223.06 | 19.53 | 0.17 | 205.00 |
May | 407.00 | 0.62 | 0.60 | 01-MAY-07:40 | 623.77 | 17.85 | 17.83 | 388.00 | 284.43 | 21.38 | 69.33 | 334.50 |
June | 411.67 | 0.61 | 0.60 | 01-JUN-06:40 | 693.74 | 19.46 | 55.17 | 391.33 | 318.45 | 22.88 | 153.00 | 353.83 |
July | 411.00 | 0.62 | 0.60 | 01-JUL-06:10 | 704.97 | 18.37 | 27.33 | 393.00 | 308.00 | 22.24 | 140.67 | 345.00 |
August | 390.50 | 0.62 | 0.60 | 01-AUG-06:49 | 619.03 | 17.23 | 0.00 | 368.00 | 280.36 | 20.41 | 32.33 | 314.17 |
September | 298.50 | 0.64 | 0.60 | 01-SEP-07:40 | 453.58 | 16.15 | 0.00 | 311.83 | 213.19 | 19.34 | 0.00 | 171.00 |
October | 293.50 | 0.68 | 0.60 | 01-OCT-10:50 | 316.48 | 14.32 | 0.00 | 213.33 | 155.11 | 17.73 | 0.00 | 74.50 |
November | 299.00 | 0.68 | 0.60 | 01-NOV-10:09 | 312.14 | 13.94 | 0.00 | 231.17 | 147.05 | 17.32 | 0.00 | 26.00 |
December | 285.17 | 0.69 | 0.60 | 01-DEC-11:09 | 292.19 | 13.72 | 0.00 | 194.17 | 137.44 | 17.19 | 0.00 | 7.67 |
Annual Sum or Average | 4071.00 | 0.65 | 483.43 | 16.15 | 100.33 | 3512.67 | 221.87 | 19.55 | 395.50 | 2074.50 | ||
Minimum of Months | 263.00 | 0.61 | 0.60 | 292.19 | 13.68 | 0.00 | 183.17 | 137.44 | 17.11 | 0.00 | 7.67 | |
Maximum of Months | 411.67 | 0.69 | 0.60 | 704.97 | 19.46 | 55.17 | 393.00 | 318.45 | 22.88 | 153.00 | 353.83 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.69 | 0.60 | 01-JAN-11:09 | 301.69 | 13.68 | 0.00 | 195.50 | 139.89 | 17.11 | 0.00 | 33.83 |
February | 263.00 | 0.69 | 0.60 | 01-FEB-13:50 | 311.13 | 13.86 | 0.00 | 183.17 | 147.54 | 17.25 | 0.00 | 59.67 |
March | 351.67 | 0.65 | 0.60 | 01-MAR-09:20 | 402.95 | 15.41 | 0.00 | 306.33 | 188.03 | 18.66 | 0.00 | 149.33 |
April | 369.33 | 0.63 | 0.60 | 01-APR-10:20 | 489.90 | 16.33 | 0.00 | 336.83 | 223.06 | 19.53 | 0.17 | 205.00 |
May | 407.00 | 0.62 | 0.60 | 01-MAY-07:40 | 623.77 | 17.85 | 17.83 | 388.00 | 284.43 | 21.38 | 69.33 | 334.50 |
June | 411.67 | 0.61 | 0.60 | 01-JUN-06:40 | 693.74 | 19.46 | 55.17 | 391.33 | 318.45 | 22.88 | 153.00 | 353.83 |
July | 411.00 | 0.62 | 0.60 | 01-JUL-06:10 | 704.97 | 18.37 | 27.33 | 393.00 | 308.00 | 22.24 | 140.67 | 345.00 |
August | 390.50 | 0.62 | 0.60 | 01-AUG-06:49 | 619.03 | 17.23 | 0.00 | 368.00 | 280.36 | 20.41 | 32.33 | 314.17 |
September | 298.50 | 0.64 | 0.60 | 01-SEP-07:40 | 453.58 | 16.15 | 0.00 | 311.83 | 213.19 | 19.34 | 0.00 | 171.00 |
October | 293.50 | 0.68 | 0.60 | 01-OCT-10:50 | 316.48 | 14.32 | 0.00 | 213.33 | 155.11 | 17.73 | 0.00 | 74.50 |
November | 299.00 | 0.68 | 0.60 | 01-NOV-10:09 | 312.14 | 13.94 | 0.00 | 231.17 | 147.05 | 17.32 | 0.00 | 26.00 |
December | 285.17 | 0.69 | 0.60 | 01-DEC-11:09 | 292.19 | 13.72 | 0.00 | 194.17 | 137.44 | 17.19 | 0.00 | 7.67 |
Annual Sum or Average | 4071.00 | 0.65 | 483.43 | 16.15 | 100.33 | 3512.67 | 221.87 | 19.55 | 395.50 | 2074.50 | ||
Minimum of Months | 263.00 | 0.61 | 0.60 | 292.19 | 13.68 | 0.00 | 183.17 | 137.44 | 17.11 | 0.00 | 7.67 | |
Maximum of Months | 411.67 | 0.69 | 0.60 | 704.97 | 19.46 | 55.17 | 393.00 | 318.45 | 22.88 | 153.00 | 353.83 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.435470E+11 | 102674.99 | 21-JAN-18:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.406312E+11 | 102723.98 | 12-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.484610E+11 | 101213.58 | 18-MAR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.197696E+11 | 98628.68 | 09-APR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.625135E+10 | 88685.51 | 11-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.131181E+10 | 45547.65 | 10-JUN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 344731.49 | 470.36 | 25-AUG-21:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111719E+10 | 36053.81 | 29-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.450265E+11 | 105975.43 | 06-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.402920E+11 | 103083.20 | 26-NOV-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.496469E+11 | 105378.89 | 27-DEC-23:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296055E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.496469E+11 | 105975.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.875817E+09 | 3913.57 | 27-MAR-10:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.382168E+10 | 7228.45 | 17-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145314E+10 | 5744.61 | 01-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9042206.92 | 3131.30 | 01-JUN-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.615967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.382168E+10 | 7228.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.180974E+10 | 2151.91 | 08-JAN-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114060E+10 | 2356.96 | 12-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.281383E+09 | 1139.72 | 22-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 99797245.82 | 988.18 | 06-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2088462.82 | 226.55 | 11-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5130886.80 | 324.04 | 30-SEP-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186529E+09 | 1081.47 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.355948E+09 | 1471.02 | 21-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111988E+10 | 1632.48 | 01-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.500109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.180974E+10 | 2356.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 85459211.84 | 571.12 | 08-JAN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 41121304.84 | 411.69 | 13-FEB-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 129358.66 | 151.80 | 23-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5103534.28 | 183.41 | 25-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131813E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 85459211.84 | 571.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106471E+10 | 1092.38 | 08-JAN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.595256E+09 | 1078.25 | 13-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 31029180.25 | 494.80 | 23-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 322899.76 | 216.16 | 07-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 51774454.08 | 551.04 | 22-NOV-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.381249E+09 | 741.21 | 18-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106471E+10 | 1092.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.803884E+09 | 691.30 | 08-JAN-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.448041E+09 | 677.31 | 12-FEB-09:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 32665178.00 | 313.37 | 23-MAR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 821010.57 | 161.63 | 07-APR-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 452228.29 | 91.70 | 31-OCT-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 53345709.22 | 352.09 | 22-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.338308E+09 | 452.28 | 18-DEC-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.803884E+09 | 691.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.437574E+09 | 2735.85 | 09-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.304448E+09 | 2678.48 | 13-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167177E+09 | 1788.43 | 23-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 91589555.50 | 1457.96 | 06-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43993026.74 | 904.08 | 14-MAY-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13294180.29 | 812.71 | 25-JUN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20172841.69 | 861.91 | 16-JUL-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9464710.77 | 666.67 | 06-AUG-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32960853.09 | 973.78 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121797E+09 | 1537.62 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.199110E+09 | 2001.46 | 22-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.336545E+09 | 2351.13 | 18-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9464710.77 | 666.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.437574E+09 | 2735.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.890575E+09 | 4688.07 | 09-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.477325E+09 | 3663.62 | 07-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 68983225.61 | 2639.58 | 22-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9993749.63 | 1755.31 | 06-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 429674.65 | 507.36 | 29-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 70959811.10 | 2534.24 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 54519851.94 | 2347.00 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.294658E+09 | 2910.82 | 25-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.890575E+09 | 4688.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.423973E+09 | 7747.08 | 08-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 99114704.33 | 4235.14 | 07-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1691047.63 | 1017.12 | 25-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.524779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.423973E+09 | 7747.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.618242E+10 | 7559.04 | 09-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.353489E+10 | 6438.03 | 12-FEB-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109671E+09 | 3239.94 | 23-MAR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104557E+09 | 3011.27 | 31-OCT-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.432704E+09 | 3969.64 | 22-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.314249E+10 | 4745.36 | 26-DEC-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.618242E+10 | 7559.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.457489E+10 | 4620.04 | 08-JAN-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.259266E+10 | 5086.99 | 12-FEB-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.323324E+09 | 2184.36 | 19-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 65212591.77 | 1643.66 | 07-APR-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164669E+09 | 1918.09 | 26-OCT-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.762303E+09 | 3221.59 | 22-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.264826E+10 | 3732.85 | 18-DEC-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.457489E+10 | 5086.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.684360E+09 | 4032.61 | 07-JAN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.588801E+09 | 5204.97 | 12-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4112.02 | 0.21 | 05-MAR-00:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5360.70 | 0.21 | 14-APR-12:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7323.34 | 0.21 | 31-MAY-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9489.30 | 0.21 | 16-JUN-19:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4939.57 | 0.21 | 13-JUL-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5280.15 | 0.21 | 03-AUG-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6927.54 | 0.21 | 01-SEP-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5815.40 | 0.21 | 03-OCT-15:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 36855599.33 | 1149.31 | 22-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123974E+09 | 2128.72 | 18-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4112.02 | 0.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.684360E+09 | 5204.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.364604E+10 | 9146.50 | 07-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.214335E+10 | 9176.53 | 03-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.367967E+09 | 8703.52 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 95090648.67 | 8758.07 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6580716.33 | 3803.94 | 19-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3356360.34 | 3392.22 | 04-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1522574.37 | 2259.46 | 03-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1535890.09 | 3548.67 | 25-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9787434.80 | 3344.66 | 21-SEP-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.254930E+09 | 8746.17 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.793593E+09 | 8936.51 | 21-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229904E+10 | 9029.05 | 18-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.962279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1522574.37 | 2259.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.364604E+10 | 9176.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.468266E+10 | 9136.37 | 07-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.278053E+10 | 9166.40 | 03-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.509335E+09 | 8752.35 | 19-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112148E+09 | 8768.35 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3698149.90 | 2350.82 | 18-MAY-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 837364.72 | 1554.97 | 09-JUN-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 743029.05 | 1400.73 | 07-JUL-06:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 429880.84 | 1361.36 | 10-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4514754.78 | 3655.51 | 20-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.326550E+09 | 8807.39 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124785E+10 | 9019.32 | 21-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.317669E+10 | 9058.87 | 18-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 429880.84 | 1361.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.468266E+10 | 9166.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.161105E+11 | 52803.33 | 07-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.887750E+10 | 52711.49 | 03-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.590538E+09 | 41443.80 | 19-MAR-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150595E+09 | 28420.31 | 06-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11302028.49 | 16598.03 | 15-MAY-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4564457.78 | 12433.21 | 05-JUN-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1734806.97 | 9515.56 | 28-JUL-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 694524.90 | 2762.23 | 15-AUG-08:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18341281.83 | 20881.76 | 30-SEP-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.241141E+09 | 23785.77 | 27-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197746E+10 | 51242.84 | 22-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.770492E+10 | 51781.94 | 18-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.356893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 694524.90 | 2762.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161105E+11 | 52803.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.367118E+10 | 8912.49 | 07-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.210921E+10 | 8925.87 | 11-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.399737E+09 | 8477.40 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 94955748.07 | 2608.33 | 06-APR-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1474537.76 | 2502.30 | 26-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 675171.73 | 2042.63 | 28-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4859.80 | 44.15 | 31-AUG-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4176685.86 | 3082.65 | 30-SEP-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.263515E+09 | 8422.48 | 31-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.784844E+09 | 8511.76 | 30-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.226083E+10 | 8633.81 | 21-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.959060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.367118E+10 | 8925.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.474747E+10 | 8907.47 | 07-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.272297E+10 | 8920.88 | 11-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.537569E+09 | 8496.28 | 22-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113818E+09 | 2793.29 | 26-APR-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1265532.13 | 2007.81 | 12-MAY-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 368411.16 | 1271.56 | 18-JUN-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 351524.04 | 1409.23 | 29-JUL-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19239.19 | 256.52 | 31-AUG-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2944058.34 | 3293.64 | 30-SEP-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.347646E+09 | 8420.83 | 31-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121866E+10 | 8593.89 | 22-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.313466E+10 | 8743.20 | 17-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 19239.19 | 256.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.474747E+10 | 8920.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.137490E+10 | 2752.21 | 07-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.835668E+09 | 2761.34 | 03-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.210821E+09 | 2659.65 | 19-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 64372140.33 | 2670.53 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3384201.88 | 854.13 | 20-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1181750.39 | 834.90 | 04-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 770541.57 | 813.87 | 03-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 823544.20 | 777.65 | 26-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6956063.35 | 792.68 | 21-SEP-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148076E+09 | 2667.61 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.383488E+09 | 2717.22 | 21-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.922685E+09 | 2729.01 | 18-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.395313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 770541.57 | 777.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.137490E+10 | 2761.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.170483E+10 | 2748.01 | 07-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104348E+10 | 2757.12 | 03-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.265267E+09 | 2671.83 | 19-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 67864217.04 | 2672.42 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1332596.90 | 893.92 | 13-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 509439.42 | 969.99 | 07-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 216048.34 | 514.81 | 02-JUL-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 222805.09 | 691.20 | 10-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3423024.81 | 745.25 | 21-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183650E+09 | 2682.61 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.551156E+09 | 2713.10 | 21-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120472E+10 | 2724.85 | 18-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.502667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 216048.34 | 514.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.170483E+10 | 2757.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.355807E+10 | 12954.99 | 07-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202646E+10 | 12932.55 | 12-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.403550E+09 | 12270.77 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169401E+09 | 12388.01 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8051717.10 | 4519.16 | 10-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1802200.68 | 3141.32 | 08-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2254634.04 | 2090.32 | 28-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1974009.65 | 2070.04 | 14-AUG-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13320954.65 | 4865.17 | 30-SEP-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.240471E+09 | 12168.42 | 31-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.580590E+09 | 12309.19 | 30-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192026E+10 | 12557.34 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.892620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1802200.68 | 2070.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.355807E+10 | 12954.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.507526E+11 | 0.507526E+11 | 39958.33 | 31-JAN-11:13 | 39958.33 | 0.00 |
February | 0.00 | 0.00 | 0.475583E+11 | 0.475583E+11 | 44871.57 | 01-FEB-09:01 | 44871.57 | 0.00 |
March | 0.00 | 0.00 | 0.530043E+11 | 0.530019E+11 | 56659.15 | 31-MAR-23:07 | 53351.89 | 0.00 |
April | 0.00 | 0.00 | 0.487337E+11 | 0.461104E+11 | 56628.47 | 01-APR-05:08 | 53341.90 | 0.00 |
May | 0.00 | 0.00 | 0.469020E+11 | 0.377156E+11 | 60883.65 | 01-MAY-07:35 | 48748.61 | 0.00 |
June | 0.00 | 0.00 | 0.420110E+11 | 0.316224E+11 | 64073.14 | 01-JUN-17:15 | 48001.98 | 0.00 |
July | 0.00 | 0.00 | 0.413087E+11 | 0.256379E+11 | 65841.04 | 01-JUL-07:50 | 40792.32 | 0.00 |
August | 0.00 | 0.00 | 0.413047E+11 | 0.244046E+11 | 66454.33 | 31-AUG-06:40 | 39189.69 | 0.00 |
September | 0.00 | 0.00 | 0.413064E+11 | 0.282986E+11 | 62398.09 | 30-SEP-05:08 | 42637.06 | 0.00 |
October | 0.00 | 0.00 | 0.451568E+11 | 0.375258E+11 | 55435.94 | 31-OCT-05:15 | 45862.13 | 0.00 |
November | 0.00 | 0.00 | 0.465175E+11 | 0.465175E+11 | 49811.89 | 30-NOV-06:15 | 49811.89 | 0.00 |
December | 0.00 | 0.00 | 0.501688E+11 | 0.501688E+11 | 44629.08 | 31-DEC-00:20 | 44629.08 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.554725E+12 | 0.479314E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.413047E+11 | 0.244046E+11 | 39958.33 | 39189.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.530043E+11 | 0.530019E+11 | 66454.33 | 53351.89 | 0.00 |
Report: CoilReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.400531E+11 | 0.400531E+11 | 50560.72 | 31-JAN-17:10 | 50560.72 | 0.00 |
February | 0.00 | 0.00 | 0.406085E+11 | 0.406085E+11 | 56782.05 | 01-FEB-17:30 | 56782.05 | 0.00 |
March | 0.00 | 0.00 | 0.519623E+11 | 0.519619E+11 | 65997.07 | 01-MAR-17:10 | 65997.07 | 0.00 |
April | 0.00 | 0.00 | 0.544136E+11 | 0.515071E+11 | 71669.06 | 01-APR-16:40 | 67528.11 | 0.00 |
May | 0.00 | 0.00 | 0.603341E+11 | 0.485310E+11 | 77057.12 | 01-MAY-16:20 | 61703.27 | 0.00 |
June | 0.00 | 0.00 | 0.615212E+11 | 0.463240E+11 | 81095.77 | 01-JUN-16:10 | 60776.25 | 0.00 |
July | 0.00 | 0.00 | 0.656138E+11 | 0.407272E+11 | 83334.34 | 01-JUL-16:10 | 51633.76 | 0.00 |
August | 0.00 | 0.00 | 0.662316E+11 | 0.391312E+11 | 84110.92 | 31-AUG-18:50 | 49632.79 | 0.00 |
September | 0.00 | 0.00 | 0.599852E+11 | 0.410983E+11 | 78974.76 | 30-SEP-19:10 | 54003.59 | 0.00 |
October | 0.00 | 0.00 | 0.549887E+11 | 0.457042E+11 | 70159.03 | 31-OCT-19:30 | 58050.86 | 0.00 |
November | 0.00 | 0.00 | 0.479014E+11 | 0.479014E+11 | 63037.66 | 30-NOV-17:30 | 63037.66 | 0.00 |
December | 0.00 | 0.00 | 0.445208E+11 | 0.445208E+11 | 56475.00 | 31-DEC-18:35 | 56475.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.648134E+12 | 0.538069E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.400531E+11 | 0.391312E+11 | 50560.72 | 49632.79 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.662316E+11 | 0.519619E+11 | 84110.92 | 67528.11 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.857199E+10 | 0.717297E+10 | 127525.87 | 19-JAN-21:00 | 70168.20 | 0.05 |
February | 0.00 | 0.00 | 0.295379E+11 | 0.291262E+11 | 152266.98 | 26-FEB-14:40 | 152266.98 | 0.08 |
March | 0.00 | 0.00 | 0.884677E+11 | 0.856890E+11 | 236236.18 | 30-MAR-18:05 | 223199.00 | 0.25 |
April | 0.00 | 0.00 | 0.185861E+12 | 0.161258E+12 | 262498.41 | 04-APR-10:33 | 135865.50 | 0.54 |
May | 0.00 | 0.00 | 0.367444E+12 | 0.266205E+12 | 430502.17 | 30-MAY-21:05 | 195263.36 | 0.87 |
June | 0.00 | 0.00 | 0.612444E+12 | 0.383362E+12 | 485831.73 | 26-JUN-21:00 | 197163.61 | 0.89 |
July | 0.00 | 0.00 | 0.801700E+12 | 0.436782E+12 | 509105.97 | 18-JUL-20:10 | 191171.46 | 1.00 |
August | 0.00 | 0.00 | 0.866298E+12 | 0.463821E+12 | 618006.24 | 23-AUG-21:00 | 210282.99 | 1.00 |
September | 0.00 | 0.00 | 0.526500E+12 | 0.320418E+12 | 476816.56 | 27-SEP-21:00 | 186667.51 | 0.97 |
October | 0.00 | 0.00 | 0.202313E+12 | 0.133923E+12 | 541472.50 | 18-OCT-21:00 | 195887.28 | 0.43 |
November | 0.00 | 0.00 | 0.674967E+11 | 0.550056E+11 | 240259.75 | 27-NOV-19:05 | 135100.27 | 0.20 |
December | 0.00 | 0.00 | 0.148349E+11 | 0.126143E+11 | 172471.86 | 13-DEC-11:40 | 96220.76 | 0.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.377147E+13 | 0.235538E+13 | 0.53 | |||
Minimum of Months | 0.00 | 0.00 | 0.857199E+10 | 0.717297E+10 | 127525.87 | 70168.20 | 0.05 | |
Maximum of Months | 0.00 | 0.00 | 0.866298E+12 | 0.463821E+12 | 618006.24 | 223199.00 | 1.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.699421E+09 | 0.528690E+09 | 13434.67 | 19-JAN-16:03 | 8414.80 | 0.03 |
February | 0.00 | 0.00 | 0.198040E+10 | 0.195579E+10 | 16293.42 | 28-FEB-16:02 | 16293.42 | 0.04 |
March | 0.00 | 0.00 | 0.717311E+10 | 0.651348E+10 | 23092.79 | 28-MAR-15:02 | 16545.02 | 0.20 |
April | 0.00 | 0.00 | 0.143549E+11 | 0.115018E+11 | 29172.24 | 30-APR-15:02 | 15804.85 | 0.43 |
May | 0.00 | 0.00 | 0.302587E+11 | 0.200722E+11 | 38844.87 | 30-MAY-21:51 | 15016.75 | 0.69 |
June | 0.00 | 0.00 | 0.447665E+11 | 0.279822E+11 | 45304.17 | 29-JUN-08:03 | 17336.39 | 0.72 |
July | 0.00 | 0.00 | 0.559576E+11 | 0.315227E+11 | 49357.42 | 26-JUL-08:05 | 16840.22 | 0.79 |
August | 0.00 | 0.00 | 0.571073E+11 | 0.326820E+11 | 47904.80 | 24-AUG-08:62 | 17407.01 | 0.79 |
September | 0.00 | 0.00 | 0.400859E+11 | 0.244157E+11 | 45917.73 | 17-SEP-08:03 | 17077.78 | 0.76 |
October | 0.00 | 0.00 | 0.162102E+11 | 0.100590E+11 | 44452.02 | 18-OCT-21:50 | 16050.92 | 0.33 |
November | 0.00 | 0.00 | 0.575607E+10 | 0.417254E+10 | 27234.27 | 19-NOV-24:00 | 13347.30 | 0.16 |
December | 0.00 | 0.00 | 0.119221E+10 | 0.941584E+09 | 20043.31 | 12-DEC-13:30 | 14470.08 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.275542E+12 | 0.172348E+12 | 0.42 | |||
Minimum of Months | 0.00 | 0.00 | 0.699421E+09 | 0.528690E+09 | 13434.67 | 8414.80 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.571073E+11 | 0.326820E+11 | 49357.42 | 17407.01 | 0.79 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.155002E+09 | 0.131177E+09 | 12383.13 | 20-JAN-16:01 | 9613.80 | 0.03 |
February | 0.00 | 0.00 | 0.677357E+09 | 0.585935E+09 | 13395.33 | 19-FEB-16:02 | 8961.27 | 0.06 |
March | 0.00 | 0.00 | 0.254767E+10 | 0.180057E+10 | 14006.76 | 28-MAR-15:02 | 10077.57 | 0.34 |
April | 0.00 | 0.00 | 0.458235E+10 | 0.282774E+10 | 14292.85 | 02-APR-15:02 | 10074.35 | 0.72 |
May | 0.00 | 0.00 | 0.687033E+10 | 0.407194E+10 | 13635.22 | 27-MAY-08:62 | 8984.60 | 0.87 |
June | 0.00 | 0.00 | 0.912175E+10 | 0.587705E+10 | 15050.30 | 29-JUN-08:62 | 9472.18 | 0.95 |
July | 0.00 | 0.00 | 0.104157E+11 | 0.679872E+10 | 15451.66 | 30-JUL-08:62 | 9031.96 | 0.95 |
August | 0.00 | 0.00 | 0.109427E+11 | 0.723444E+10 | 15575.39 | 29-AUG-08:62 | 9323.86 | 0.96 |
September | 0.00 | 0.00 | 0.735741E+10 | 0.437086E+10 | 15243.04 | 17-SEP-08:62 | 9338.91 | 0.91 |
October | 0.00 | 0.00 | 0.374635E+10 | 0.217304E+10 | 14763.55 | 18-OCT-08:62 | 8462.21 | 0.64 |
November | 0.00 | 0.00 | 0.126656E+10 | 0.796489E+09 | 14082.44 | 04-NOV-15:01 | 8963.22 | 0.28 |
December | 0.00 | 0.00 | 0.345911E+09 | 0.234687E+09 | 13242.67 | 12-DEC-16:01 | 10340.47 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.580291E+11 | 0.369027E+11 | 0.57 | |||
Minimum of Months | 0.00 | 0.00 | 0.155002E+09 | 0.131177E+09 | 12383.13 | 8462.21 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.109427E+11 | 0.723444E+10 | 15575.39 | 10340.47 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 13849955.74 | 10440865.82 | 11916.23 | 20-JAN-16:01 | 9007.99 | 0.00 |
February | 0.00 | 0.00 | 0.140547E+09 | 0.108872E+09 | 13082.99 | 19-FEB-16:02 | 8633.19 | 0.03 |
March | 0.00 | 0.00 | 0.111893E+10 | 0.686237E+09 | 13994.94 | 28-MAR-15:02 | 9863.77 | 0.21 |
April | 0.00 | 0.00 | 0.299366E+10 | 0.171075E+10 | 14349.21 | 02-APR-15:02 | 9816.98 | 0.52 |
May | 0.00 | 0.00 | 0.541752E+10 | 0.325603E+10 | 15186.19 | 07-MAY-17:41 | 11252.21 | 0.64 |
June | 0.00 | 0.00 | 0.828116E+10 | 0.552498E+10 | 16422.20 | 26-JUN-08:21 | 9915.35 | 0.78 |
July | 0.00 | 0.00 | 0.945354E+10 | 0.639259E+10 | 16853.32 | 23-JUL-08:51 | 9580.78 | 0.79 |
August | 0.00 | 0.00 | 0.972865E+10 | 0.648570E+10 | 17476.28 | 20-AUG-07:52 | 9625.00 | 0.83 |
September | 0.00 | 0.00 | 0.553932E+10 | 0.323601E+10 | 15750.26 | 06-SEP-08:31 | 9486.80 | 0.69 |
October | 0.00 | 0.00 | 0.176718E+10 | 0.860343E+09 | 15169.61 | 18-OCT-21:52 | 8947.30 | 0.39 |
November | 0.00 | 0.00 | 0.279000E+09 | 0.156516E+09 | 13973.94 | 02-NOV-15:02 | 9785.54 | 0.10 |
December | 0.00 | 0.00 | 50672702.02 | 32163516.48 | 13555.90 | 12-DEC-16:01 | 9225.53 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.447840E+11 | 0.284606E+11 | 0.42 | |||
Minimum of Months | 0.00 | 0.00 | 13849955.74 | 10440865.82 | 11916.23 | 8633.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.972865E+10 | 0.648570E+10 | 17476.28 | 11252.21 | 0.83 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.217526E+10 | 0.197410E+10 | 28651.92 | 29-JAN-13:30 | 28651.92 | 0.01 |
February | 0.00 | 0.00 | 0.697272E+10 | 0.636384E+10 | 33375.78 | 26-FEB-14:50 | 33375.78 | 0.05 |
March | 0.00 | 0.00 | 0.200250E+11 | 0.146214E+11 | 33652.49 | 30-MAR-13:30 | 26902.94 | 0.38 |
April | 0.00 | 0.00 | 0.233495E+11 | 0.121436E+11 | 30862.78 | 15-APR-13:15 | 24198.20 | 0.77 |
May | 0.00 | 0.00 | 0.300126E+11 | 0.138004E+11 | 25695.75 | 06-MAY-13:30 | 16958.65 | 0.96 |
June | 0.00 | 0.00 | 0.387349E+11 | 0.198877E+11 | 27676.58 | 13-JUN-17:20 | 19574.70 | 0.99 |
July | 0.00 | 0.00 | 0.454230E+11 | 0.248347E+11 | 30966.85 | 08-JUL-17:25 | 24486.48 | 1.00 |
August | 0.00 | 0.00 | 0.523336E+11 | 0.314386E+11 | 35731.21 | 27-AUG-13:20 | 32163.58 | 1.00 |
September | 0.00 | 0.00 | 0.403340E+11 | 0.232649E+11 | 39576.70 | 24-SEP-12:50 | 29462.23 | 0.97 |
October | 0.00 | 0.00 | 0.302338E+11 | 0.185150E+11 | 42160.25 | 10-OCT-13:30 | 32517.22 | 0.79 |
November | 0.00 | 0.00 | 0.192837E+11 | 0.149707E+11 | 38035.94 | 12-NOV-14:00 | 31477.41 | 0.33 |
December | 0.00 | 0.00 | 0.922842E+10 | 0.772665E+10 | 37095.28 | 10-DEC-14:25 | 37095.28 | 0.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.318107E+12 | 0.189542E+12 | 0.62 | |||
Minimum of Months | 0.00 | 0.00 | 0.217526E+10 | 0.197410E+10 | 25695.75 | 16958.65 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.523336E+11 | 0.314386E+11 | 42160.25 | 37095.28 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.126183E+10 | 0.684812E+09 | 75370.65 | 19-JAN-22:53 | 53677.62 | 0.07 |
February | 0.00 | 0.00 | 0.482668E+10 | 0.337910E+10 | 75805.83 | 19-FEB-16:02 | 59044.89 | 0.13 |
March | 0.00 | 0.00 | 0.145641E+11 | 0.102708E+11 | 80571.58 | 29-MAR-15:02 | 67234.53 | 0.27 |
April | 0.00 | 0.00 | 0.270417E+11 | 0.180293E+11 | 82278.08 | 02-APR-15:02 | 64994.47 | 0.48 |
May | 0.00 | 0.00 | 0.430462E+11 | 0.286588E+11 | 93064.34 | 07-MAY-17:41 | 66016.73 | 0.57 |
June | 0.00 | 0.00 | 0.584359E+11 | 0.410190E+11 | 99712.25 | 26-JUN-08:21 | 57506.47 | 0.73 |
July | 0.00 | 0.00 | 0.654818E+11 | 0.452647E+11 | 102640.48 | 23-JUL-08:51 | 58000.06 | 0.75 |
August | 0.00 | 0.00 | 0.651870E+11 | 0.444466E+11 | 109954.93 | 20-AUG-07:52 | 55184.34 | 0.77 |
September | 0.00 | 0.00 | 0.427459E+11 | 0.269132E+11 | 97044.36 | 17-SEP-08:52 | 55463.64 | 0.62 |
October | 0.00 | 0.00 | 0.208560E+11 | 0.119016E+11 | 97038.44 | 18-OCT-21:52 | 55333.69 | 0.50 |
November | 0.00 | 0.00 | 0.910564E+10 | 0.596681E+10 | 81442.72 | 05-NOV-15:02 | 65038.46 | 0.22 |
December | 0.00 | 0.00 | 0.281571E+10 | 0.155771E+10 | 76328.11 | 13-DEC-21:02 | 55252.36 | 0.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.355369E+12 | 0.238092E+12 | 0.44 | |||
Minimum of Months | 0.00 | 0.00 | 0.126183E+10 | 0.684812E+09 | 75370.65 | 53677.62 | 0.07 | |
Maximum of Months | 0.00 | 0.00 | 0.654818E+11 | 0.452647E+11 | 109954.93 | 67234.53 | 0.77 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.103507E+09 | 82269224.97 | 10853.86 | 20-JAN-16:01 | 8155.82 | 0.02 |
February | 0.00 | 0.00 | 0.737733E+09 | 0.633294E+09 | 11856.61 | 19-FEB-16:02 | 7732.22 | 0.08 |
March | 0.00 | 0.00 | 0.228550E+10 | 0.153599E+10 | 12438.79 | 28-MAR-15:02 | 9189.24 | 0.38 |
April | 0.00 | 0.00 | 0.445586E+10 | 0.269164E+10 | 12853.09 | 02-APR-15:02 | 9093.84 | 0.75 |
May | 0.00 | 0.00 | 0.707831E+10 | 0.424057E+10 | 12315.88 | 27-MAY-08:62 | 8188.58 | 0.90 |
June | 0.00 | 0.00 | 0.937150E+10 | 0.610686E+10 | 13442.85 | 23-JUN-08:62 | 8688.67 | 0.97 |
July | 0.00 | 0.00 | 0.107969E+11 | 0.728041E+10 | 13871.36 | 30-JUL-08:62 | 8174.19 | 0.97 |
August | 0.00 | 0.00 | 0.110378E+11 | 0.750338E+10 | 13399.47 | 24-AUG-08:62 | 8690.05 | 0.97 |
September | 0.00 | 0.00 | 0.742301E+10 | 0.448807E+10 | 13719.52 | 17-SEP-08:62 | 8427.40 | 0.92 |
October | 0.00 | 0.00 | 0.369540E+10 | 0.209555E+10 | 13336.16 | 18-OCT-08:62 | 7746.89 | 0.66 |
November | 0.00 | 0.00 | 0.116152E+10 | 0.717190E+09 | 12578.89 | 04-NOV-15:01 | 8044.03 | 0.30 |
December | 0.00 | 0.00 | 0.303536E+09 | 0.180671E+09 | 12096.33 | 12-DEC-16:01 | 9221.10 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.584506E+11 | 0.375559E+11 | 0.59 | |||
Minimum of Months | 0.00 | 0.00 | 0.103507E+09 | 82269224.97 | 10853.86 | 7732.22 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.110378E+11 | 0.750338E+10 | 13871.36 | 9221.10 | 0.97 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 13643619.05 | 10352114.83 | 9790.28 | 31-JAN-16:01 | 8737.29 | 0.00 |
February | 0.00 | 0.00 | 0.228611E+09 | 0.177973E+09 | 11162.76 | 19-FEB-16:02 | 6973.34 | 0.04 |
March | 0.00 | 0.00 | 0.103572E+10 | 0.615407E+09 | 12487.10 | 28-MAR-15:02 | 9017.67 | 0.23 |
April | 0.00 | 0.00 | 0.299023E+10 | 0.170361E+10 | 13007.44 | 02-APR-15:02 | 8856.53 | 0.56 |
May | 0.00 | 0.00 | 0.561019E+10 | 0.338387E+10 | 14390.94 | 30-MAY-08:51 | 10953.66 | 0.67 |
June | 0.00 | 0.00 | 0.841181E+10 | 0.567039E+10 | 15510.79 | 13-JUN-08:62 | 11350.46 | 0.80 |
July | 0.00 | 0.00 | 0.970290E+10 | 0.678113E+10 | 15452.91 | 23-JUL-08:51 | 10297.53 | 0.81 |
August | 0.00 | 0.00 | 0.977794E+10 | 0.661427E+10 | 16002.50 | 29-AUG-08:31 | 9496.55 | 0.85 |
September | 0.00 | 0.00 | 0.556764E+10 | 0.325910E+10 | 15191.36 | 06-SEP-08:31 | 10044.82 | 0.71 |
October | 0.00 | 0.00 | 0.185970E+10 | 0.960731E+09 | 13729.53 | 18-OCT-21:52 | 8104.23 | 0.43 |
November | 0.00 | 0.00 | 0.284456E+09 | 0.148983E+09 | 13166.93 | 05-NOV-15:02 | 8697.11 | 0.10 |
December | 0.00 | 0.00 | 38043722.80 | 19202239.07 | 12106.20 | 12-DEC-16:01 | 8159.93 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.455209E+11 | 0.293450E+11 | 0.44 | |||
Minimum of Months | 0.00 | 0.00 | 13643619.05 | 10352114.83 | 9790.28 | 6973.34 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.977794E+10 | 0.678113E+10 | 16002.50 | 11350.46 | 0.85 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 26374935.01 | 23065194.98 | 3339.19 | 20-JAN-16:01 | 2448.36 | 0.01 |
February | 0.00 | 0.00 | 0.147891E+09 | 0.128879E+09 | 3655.60 | 19-FEB-16:02 | 2267.72 | 0.05 |
March | 0.00 | 0.00 | 0.584434E+09 | 0.416664E+09 | 3741.87 | 28-MAR-15:02 | 2641.51 | 0.29 |
April | 0.00 | 0.00 | 0.109916E+10 | 0.690854E+09 | 3858.13 | 02-APR-15:02 | 2615.85 | 0.66 |
May | 0.00 | 0.00 | 0.171619E+10 | 0.102075E+10 | 3754.45 | 28-MAY-08:62 | 2406.39 | 0.86 |
June | 0.00 | 0.00 | 0.232962E+10 | 0.148625E+10 | 4206.48 | 23-JUN-08:62 | 2386.79 | 0.94 |
July | 0.00 | 0.00 | 0.267556E+10 | 0.173431E+10 | 4380.23 | 30-JUL-08:62 | 2176.25 | 0.94 |
August | 0.00 | 0.00 | 0.281174E+10 | 0.183865E+10 | 4346.69 | 29-AUG-08:62 | 2321.63 | 0.96 |
September | 0.00 | 0.00 | 0.178277E+10 | 0.104579E+10 | 4307.17 | 17-SEP-08:62 | 2296.24 | 0.88 |
October | 0.00 | 0.00 | 0.845851E+09 | 0.497816E+09 | 4073.41 | 18-OCT-08:62 | 2038.15 | 0.54 |
November | 0.00 | 0.00 | 0.266752E+09 | 0.171713E+09 | 3829.69 | 04-NOV-15:01 | 2285.85 | 0.20 |
December | 0.00 | 0.00 | 67757783.89 | 46231016.23 | 3546.17 | 12-DEC-16:01 | 2707.85 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.143541E+11 | 0.910096E+10 | 0.53 | |||
Minimum of Months | 0.00 | 0.00 | 26374935.01 | 23065194.98 | 3339.19 | 2038.15 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.281174E+10 | 0.183865E+10 | 4380.23 | 2707.85 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2969508.59 | 1989732.10 | 3200.70 | 20-JAN-16:01 | 2271.63 | 0.00 |
February | 0.00 | 0.00 | 25867166.64 | 20162782.76 | 3561.18 | 19-FEB-16:02 | 2169.51 | 0.02 |
March | 0.00 | 0.00 | 0.242735E+09 | 0.147791E+09 | 3748.54 | 28-MAR-15:02 | 2570.55 | 0.17 |
April | 0.00 | 0.00 | 0.712696E+09 | 0.412873E+09 | 3886.32 | 02-APR-15:02 | 2530.87 | 0.49 |
May | 0.00 | 0.00 | 0.139305E+10 | 0.841778E+09 | 4071.59 | 07-MAY-17:41 | 2993.32 | 0.65 |
June | 0.00 | 0.00 | 0.215551E+10 | 0.143539E+10 | 4546.95 | 26-JUN-08:21 | 2455.05 | 0.79 |
July | 0.00 | 0.00 | 0.247145E+10 | 0.166810E+10 | 4568.48 | 23-JUL-08:51 | 2418.61 | 0.79 |
August | 0.00 | 0.00 | 0.253030E+10 | 0.168162E+10 | 4879.24 | 20-AUG-07:52 | 2307.09 | 0.83 |
September | 0.00 | 0.00 | 0.135811E+10 | 0.780508E+09 | 4331.46 | 17-SEP-08:52 | 2196.22 | 0.68 |
October | 0.00 | 0.00 | 0.371389E+09 | 0.184388E+09 | 4200.65 | 18-OCT-21:52 | 2229.80 | 0.30 |
November | 0.00 | 0.00 | 45810995.39 | 26033955.87 | 3794.46 | 02-NOV-15:02 | 2518.78 | 0.05 |
December | 0.00 | 0.00 | 6754610.99 | 4248327.20 | 3663.57 | 12-DEC-16:01 | 2363.57 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.113167E+11 | 0.720488E+10 | 0.40 | |||
Minimum of Months | 0.00 | 0.00 | 2969508.59 | 1989732.10 | 3200.70 | 2169.51 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.253030E+10 | 0.168162E+10 | 4879.24 | 2993.32 | 0.83 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.136147E+10 | 0.119940E+10 | 14797.86 | 20-JAN-16:01 | 11790.38 | 0.09 |
February | 0.00 | 0.00 | 0.217834E+10 | 0.193564E+10 | 16058.82 | 19-FEB-16:02 | 11054.92 | 0.14 |
March | 0.00 | 0.00 | 0.482034E+10 | 0.363706E+10 | 15733.25 | 28-MAR-15:02 | 12443.62 | 0.41 |
April | 0.00 | 0.00 | 0.628960E+10 | 0.398048E+10 | 17011.97 | 21-APR-18:02 | 11387.32 | 0.72 |
May | 0.00 | 0.00 | 0.857336E+10 | 0.490360E+10 | 16862.47 | 25-MAY-18:02 | 11348.38 | 0.86 |
June | 0.00 | 0.00 | 0.111723E+11 | 0.692682E+10 | 19538.58 | 29-JUN-08:62 | 10198.81 | 0.94 |
July | 0.00 | 0.00 | 0.131823E+11 | 0.844523E+10 | 19838.13 | 29-JUL-18:02 | 9757.26 | 0.94 |
August | 0.00 | 0.00 | 0.146938E+11 | 0.989168E+10 | 19972.57 | 29-AUG-08:62 | 10134.53 | 0.95 |
September | 0.00 | 0.00 | 0.108017E+11 | 0.678857E+10 | 19183.11 | 17-SEP-08:62 | 10401.15 | 0.90 |
October | 0.00 | 0.00 | 0.738505E+10 | 0.496268E+10 | 18224.33 | 18-OCT-08:62 | 9420.55 | 0.73 |
November | 0.00 | 0.00 | 0.451502E+10 | 0.339428E+10 | 16470.16 | 04-NOV-15:01 | 11082.66 | 0.42 |
December | 0.00 | 0.00 | 0.248334E+10 | 0.205036E+10 | 15098.36 | 13-DEC-16:01 | 11624.91 | 0.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.874567E+11 | 0.581158E+11 | 0.61 | |||
Minimum of Months | 0.00 | 0.00 | 0.136147E+10 | 0.119940E+10 | 14797.86 | 9420.55 | 0.09 | |
Maximum of Months | 0.00 | 0.00 | 0.146938E+11 | 0.989168E+10 | 19972.57 | 12443.62 | 0.95 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 36948.89 | 177504.44 | 27-JAN-09:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 29876.00 | 211233.18 | 12-FEB-09:02 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 19842.12 | 136598.77 | 16-MAR-08:07 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9459.03 | 109062.15 | 26-APR-08:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 2878.74 | 87377.97 | 11-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 518.50 | 46101.46 | 10-JUN-05:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 13.10 | 17965.08 | 28-JUL-15:07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 7.01 | 7989.35 | 10-AUG-08:05 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 471.54 | 38016.61 | 29-SEP-08:04 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17636.52 | 156188.43 | 31-OCT-08:62 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 19030.32 | 155016.44 | 21-NOV-16:02 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 29814.83 | 173371.93 | 22-DEC-16:01 |
Annual Sum or Average | 0.00 | 13814.48 | ||||
Minimum of Months | 0.00 | 0.00 | 7.01 | 7989.35 | ||
Maximum of Months | 0.00 | 0.00 | 36948.89 | 211233.18 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7696.98 | 197036.53 | 19-JAN-22:53 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 22590.60 | 329348.41 | 26-FEB-16:01 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 57613.92 | 423237.49 | 30-MAR-15:05 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 110095.09 | 404525.18 | 17-APR-18:02 | 0.00 | 0.00 | 01-APR-00:10 |
May | 194017.69 | 576380.17 | 30-MAY-21:51 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 315291.33 | 657488.10 | 26-JUN-21:52 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 388217.07 | 685663.54 | 25-JUL-21:52 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 416308.56 | 792715.11 | 23-AUG-21:52 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 270611.00 | 612984.70 | 09-SEP-21:52 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 112331.07 | 666459.76 | 18-OCT-21:53 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 46364.32 | 367954.76 | 05-NOV-15:03 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 14869.81 | 286409.81 | 12-DEC-16:03 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 163907.11 | 0.00 | ||||
Minimum of Months | 7696.98 | 197036.53 | 0.00 | 0.00 | ||
Maximum of Months | 416308.56 | 792715.11 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25252.60 | 53156.35 | 31-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 25300.06 | 53145.83 | 02-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 24480.28 | 52260.20 | 01-MAR-07:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22931.21 | 49302.06 | 03-APR-06:30 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 21112.13 | 45893.51 | 01-MAY-06:30 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 19499.93 | 42080.02 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18505.61 | 39169.03 | 03-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18455.18 | 39020.29 | 31-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 19304.91 | 41495.88 | 29-SEP-06:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 20847.77 | 45341.64 | 31-OCT-06:30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 22671.83 | 49103.64 | 30-NOV-07:40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24279.42 | 51852.05 | 28-DEC-08:00 |
Annual Sum or Average | 0.00 | 21867.29 | ||||
Minimum of Months | 0.00 | 0.00 | 18455.18 | 39020.29 | ||
Maximum of Months | 0.00 | 0.00 | 25300.06 | 53156.35 |
Report: FanReportMonthly
For: SWHSYS1 HPWH FAN
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.731723E+09 | 0.06 | 553.22 | 01-JAN-06:20 | 0.10 |
February | 0.614772E+09 | 0.06 | 553.22 | 01-FEB-00:20 | 0.10 |
March | 0.598209E+09 | 0.06 | 553.22 | 01-MAR-00:07 | 0.10 |
April | 0.513329E+09 | 0.06 | 553.22 | 01-APR-05:08 | 0.10 |
May | 0.465137E+09 | 0.05 | 553.22 | 01-MAY-05:15 | 0.10 |
June | 0.402325E+09 | 0.06 | 553.22 | 01-JUN-05:15 | 0.10 |
July | 0.387080E+09 | 0.05 | 553.22 | 01-JUL-05:17 | 0.10 |
August | 0.383288E+09 | 0.05 | 553.22 | 01-AUG-04:10 | 0.10 |
September | 0.405710E+09 | 0.05 | 553.22 | 01-SEP-05:08 | 0.10 |
October | 0.490370E+09 | 0.06 | 553.22 | 01-OCT-05:07 | 0.10 |
November | 0.554236E+09 | 0.06 | 553.22 | 01-NOV-05:15 | 0.10 |
December | 0.657969E+09 | 0.06 | 553.22 | 01-DEC-00:07 | 0.10 |
Annual Sum or Average | 0.620415E+10 | 0.06 | |||
Minimum of Months | 0.383288E+09 | 0.05 | 553.22 | 0.10 | |
Maximum of Months | 0.731723E+09 | 0.06 | 553.22 | 0.10 |
Report: FanReportMonthly
For: SWHSYSLAUNDRY HPWH FAN
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.558198E+09 | 0.06 | 700.51 | 01-JAN-17:10 | 0.10 |
February | 0.503531E+09 | 0.06 | 700.51 | 01-FEB-17:10 | 0.10 |
March | 0.556538E+09 | 0.06 | 700.51 | 01-MAR-17:10 | 0.10 |
April | 0.538102E+09 | 0.05 | 700.51 | 01-APR-16:05 | 0.10 |
May | 0.555517E+09 | 0.05 | 700.51 | 01-MAY-16:10 | 0.10 |
June | 0.537067E+09 | 0.05 | 700.51 | 01-JUN-16:10 | 0.10 |
July | 0.555263E+09 | 0.05 | 700.51 | 01-JUL-16:10 | 0.10 |
August | 0.554861E+09 | 0.05 | 700.51 | 01-AUG-16:10 | 0.10 |
September | 0.537576E+09 | 0.05 | 700.51 | 01-SEP-16:10 | 0.10 |
October | 0.556122E+09 | 0.05 | 700.51 | 01-OCT-16:10 | 0.10 |
November | 0.538869E+09 | 0.06 | 700.51 | 01-NOV-16:10 | 0.10 |
December | 0.557820E+09 | 0.06 | 700.51 | 01-DEC-17:10 | 0.10 |
Annual Sum or Average | 0.654946E+10 | 0.06 | |||
Minimum of Months | 0.503531E+09 | 0.05 | 700.51 | 0.10 | |
Maximum of Months | 0.558198E+09 | 0.06 | 700.51 | 0.10 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.72 | 1299.30 | 01-JAN-00:05 | 0.91 |
February | 0.244774E+10 | 0.72 | 1299.30 | 01-FEB-00:03 | 0.91 |
March | 0.271000E+10 | 0.72 | 1299.30 | 01-MAR-00:03 | 0.91 |
April | 0.262258E+10 | 0.72 | 1299.30 | 01-APR-00:10 | 0.91 |
May | 0.271000E+10 | 0.71 | 1299.30 | 01-MAY-00:05 | 0.90 |
June | 0.262258E+10 | 0.71 | 1299.30 | 01-JUN-00:05 | 0.90 |
July | 0.271000E+10 | 0.71 | 1299.30 | 01-JUL-00:10 | 0.90 |
August | 0.271000E+10 | 0.71 | 1299.30 | 01-AUG-00:05 | 0.90 |
September | 0.262258E+10 | 0.71 | 1299.30 | 01-SEP-00:05 | 0.90 |
October | 0.271000E+10 | 0.72 | 1299.30 | 01-OCT-00:10 | 0.90 |
November | 0.262258E+10 | 0.72 | 1299.30 | 01-NOV-00:05 | 0.91 |
December | 0.271000E+10 | 0.72 | 1299.30 | 01-DEC-00:03 | 0.91 |
Annual Sum or Average | 0.319080E+11 | 0.72 | |||
Minimum of Months | 0.244774E+10 | 0.71 | 1299.30 | 0.90 | |
Maximum of Months | 0.271000E+10 | 0.72 | 1299.30 | 0.91 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.343645E+11 | 0.87 | 20201.75 | 31-JAN-22:10 | 1.13 |
February | 0.318052E+11 | 0.88 | 25073.02 | 28-FEB-22:10 | 1.29 |
March | 0.368018E+11 | 0.90 | 27162.93 | 30-MAR-21:05 | 1.34 |
April | 0.366421E+11 | 0.91 | 27401.34 | 18-APR-21:10 | 1.35 |
May | 0.393873E+11 | 0.93 | 27715.76 | 19-MAY-21:15 | 1.36 |
June | 0.403510E+11 | 0.96 | 29194.84 | 29-JUN-21:10 | 1.40 |
July | 0.424233E+11 | 0.96 | 30765.94 | 07-JUL-21:10 | 1.45 |
August | 0.433518E+11 | 0.98 | 31941.22 | 18-AUG-21:10 | 1.48 |
September | 0.395759E+11 | 0.94 | 31802.99 | 08-SEP-21:20 | 1.48 |
October | 0.384619E+11 | 0.92 | 31432.31 | 10-OCT-21:10 | 1.47 |
November | 0.357887E+11 | 0.90 | 25779.07 | 02-NOV-21:10 | 1.30 |
December | 0.350973E+11 | 0.88 | 24228.87 | 12-DEC-22:10 | 1.25 |
Annual Sum or Average | 0.454051E+12 | 0.92 | |||
Minimum of Months | 0.318052E+11 | 0.87 | 20201.75 | 1.13 | |
Maximum of Months | 0.433518E+11 | 0.98 | 31941.22 | 1.48 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.28 | 76.61 | 01-JAN-00:05 | 0.28 |
February | 0.185347E+09 | 0.28 | 76.61 | 01-FEB-00:03 | 0.28 |
March | 0.205205E+09 | 0.28 | 76.61 | 01-MAR-00:03 | 0.28 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.28 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:05 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:05 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:05 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:05 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.28 | 76.61 | 01-NOV-00:05 | 0.28 |
December | 0.205205E+09 | 0.28 | 76.61 | 01-DEC-00:03 | 0.28 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.28 | 76.61 | 0.28 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:03 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.28 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:05 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.28 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.28 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.199793E+09 | 0.44 | 664.41 | 01-JAN-16:02 | 0.59 |
February | 0.161340E+09 | 0.43 | 664.41 | 01-FEB-09:01 | 0.59 |
March | 0.180076E+09 | 0.47 | 664.41 | 02-MAR-16:01 | 0.59 |
April | 0.256550E+09 | 0.51 | 664.41 | 01-APR-08:62 | 0.59 |
May | 0.344205E+09 | 0.54 | 664.41 | 01-MAY-15:02 | 0.59 |
June | 0.443482E+09 | 0.56 | 664.41 | 01-JUN-08:62 | 0.59 |
July | 0.499716E+09 | 0.56 | 664.41 | 01-JUL-08:62 | 0.59 |
August | 0.520948E+09 | 0.57 | 664.41 | 01-AUG-08:61 | 0.59 |
September | 0.355733E+09 | 0.54 | 664.41 | 01-SEP-08:62 | 0.59 |
October | 0.224529E+09 | 0.50 | 664.41 | 01-OCT-08:62 | 0.59 |
November | 0.133162E+09 | 0.46 | 664.41 | 01-NOV-15:01 | 0.59 |
December | 0.157609E+09 | 0.43 | 664.41 | 01-DEC-09:01 | 0.59 |
Annual Sum or Average | 0.347714E+10 | 0.50 | |||
Minimum of Months | 0.133162E+09 | 0.43 | 664.41 | 0.59 | |
Maximum of Months | 0.520948E+09 | 0.57 | 664.41 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.230149E+09 | 0.46 | 656.31 | 01-JAN-16:02 | 0.59 |
February | 0.153946E+09 | 0.41 | 656.31 | 01-FEB-09:01 | 0.59 |
March | 0.105641E+09 | 0.36 | 656.31 | 02-MAR-16:01 | 0.59 |
April | 0.172059E+09 | 0.38 | 656.31 | 01-APR-08:62 | 0.59 |
May | 0.269796E+09 | 0.40 | 656.31 | 01-MAY-08:53 | 0.59 |
June | 0.408267E+09 | 0.47 | 656.31 | 01-JUN-08:51 | 0.59 |
July | 0.461007E+09 | 0.47 | 656.31 | 01-JUL-08:31 | 0.59 |
August | 0.465803E+09 | 0.49 | 656.31 | 01-AUG-07:51 | 0.59 |
September | 0.265424E+09 | 0.41 | 656.31 | 01-SEP-08:51 | 0.59 |
October | 0.121167E+09 | 0.36 | 656.31 | 01-OCT-15:02 | 0.59 |
November | 99098277.19 | 0.37 | 656.31 | 01-NOV-15:01 | 0.59 |
December | 0.175829E+09 | 0.41 | 656.31 | 01-DEC-09:01 | 0.59 |
Annual Sum or Average | 0.292819E+10 | 0.42 | |||
Minimum of Months | 99098277.19 | 0.36 | 656.31 | 0.59 | |
Maximum of Months | 0.465803E+09 | 0.49 | 656.31 | 0.59 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.106327E+09 | 0.05 | 1087.43 | 29-JAN-13:30 | 0.60 |
February | 0.310908E+09 | 0.14 | 1162.00 | 26-FEB-14:25 | 0.60 |
March | 0.905117E+09 | 0.41 | 1167.91 | 11-MAR-12:40 | 0.60 |
April | 0.101551E+10 | 0.49 | 1036.84 | 15-APR-13:50 | 0.59 |
May | 0.123055E+10 | 0.57 | 872.52 | 06-MAY-13:30 | 0.59 |
June | 0.148320E+10 | 0.59 | 933.15 | 24-JUN-17:20 | 0.59 |
July | 0.167995E+10 | 0.59 | 1033.95 | 08-JUL-17:25 | 0.59 |
August | 0.188677E+10 | 0.59 | 1180.39 | 19-AUG-13:50 | 0.59 |
September | 0.154085E+10 | 0.58 | 1834.88 | 24-SEP-12:40 | 0.59 |
October | 0.127571E+10 | 0.47 | 1905.22 | 12-OCT-15:03 | 0.60 |
November | 0.900162E+09 | 0.40 | 2038.46 | 12-NOV-14:00 | 0.59 |
December | 0.422371E+09 | 0.19 | 1741.43 | 10-DEC-14:05 | 0.60 |
Annual Sum or Average | 0.127574E+11 | 0.42 | |||
Minimum of Months | 0.106327E+09 | 0.05 | 872.52 | 0.59 | |
Maximum of Months | 0.188677E+10 | 0.59 | 2038.46 | 0.60 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.978617E+09 | 0.41 | 3984.20 | 01-JAN-09:02 | 0.59 |
February | 0.797109E+09 | 0.38 | 3984.20 | 02-FEB-16:02 | 0.60 |
March | 0.903451E+09 | 0.34 | 3984.20 | 01-MAR-09:02 | 0.59 |
April | 0.144775E+10 | 0.35 | 3984.20 | 01-APR-08:62 | 0.59 |
May | 0.213402E+10 | 0.36 | 3984.20 | 01-MAY-08:53 | 0.59 |
June | 0.291064E+10 | 0.43 | 3984.20 | 01-JUN-08:51 | 0.59 |
July | 0.318160E+10 | 0.44 | 3984.20 | 01-JUL-08:31 | 0.59 |
August | 0.308785E+10 | 0.46 | 3984.20 | 01-AUG-07:51 | 0.59 |
September | 0.203674E+10 | 0.37 | 3984.20 | 01-SEP-08:51 | 0.59 |
October | 0.111648E+10 | 0.33 | 3984.20 | 01-OCT-08:53 | 0.59 |
November | 0.690697E+09 | 0.36 | 3984.20 | 01-NOV-15:01 | 0.59 |
December | 0.700071E+09 | 0.40 | 3984.20 | 01-DEC-16:02 | 0.60 |
Annual Sum or Average | 0.199850E+11 | 0.39 | |||
Minimum of Months | 0.690697E+09 | 0.33 | 3984.20 | 0.59 | |
Maximum of Months | 0.318160E+10 | 0.46 | 3984.20 | 0.60 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.183402E+09 | 0.44 | 597.60 | 01-JAN-16:02 | 0.59 |
February | 0.154269E+09 | 0.45 | 597.60 | 01-FEB-09:01 | 0.59 |
March | 0.162805E+09 | 0.49 | 597.60 | 02-MAR-16:01 | 0.59 |
April | 0.244960E+09 | 0.53 | 597.60 | 01-APR-08:62 | 0.59 |
May | 0.350906E+09 | 0.56 | 597.60 | 01-MAY-15:02 | 0.59 |
June | 0.455916E+09 | 0.58 | 597.60 | 01-JUN-08:62 | 0.59 |
July | 0.515191E+09 | 0.57 | 597.60 | 01-JUL-08:62 | 0.59 |
August | 0.520108E+09 | 0.58 | 597.60 | 01-AUG-08:61 | 0.59 |
September | 0.355859E+09 | 0.55 | 597.60 | 01-SEP-08:62 | 0.59 |
October | 0.216225E+09 | 0.51 | 597.60 | 01-OCT-08:62 | 0.59 |
November | 0.122341E+09 | 0.46 | 597.60 | 01-NOV-15:01 | 0.59 |
December | 0.142957E+09 | 0.43 | 597.60 | 01-DEC-09:01 | 0.59 |
Annual Sum or Average | 0.342494E+10 | 0.51 | |||
Minimum of Months | 0.122341E+09 | 0.43 | 597.60 | 0.59 | |
Maximum of Months | 0.520108E+09 | 0.58 | 597.60 | 0.59 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.216124E+09 | 0.45 | 592.35 | 01-JAN-16:02 | 0.59 |
February | 0.145834E+09 | 0.41 | 592.35 | 01-FEB-09:01 | 0.59 |
March | 98247609.99 | 0.36 | 592.35 | 02-MAR-16:01 | 0.59 |
April | 0.169964E+09 | 0.41 | 592.35 | 01-APR-08:62 | 0.59 |
May | 0.279421E+09 | 0.42 | 592.35 | 01-MAY-08:53 | 0.59 |
June | 0.411439E+09 | 0.48 | 592.35 | 01-JUN-08:51 | 0.59 |
July | 0.465299E+09 | 0.48 | 592.35 | 01-JUL-08:31 | 0.59 |
August | 0.464970E+09 | 0.50 | 592.35 | 01-AUG-07:51 | 0.59 |
September | 0.264860E+09 | 0.42 | 592.35 | 01-SEP-08:51 | 0.59 |
October | 0.122668E+09 | 0.38 | 592.35 | 01-OCT-15:02 | 0.59 |
November | 91679519.13 | 0.36 | 592.35 | 01-NOV-15:01 | 0.59 |
December | 0.160956E+09 | 0.40 | 592.35 | 01-DEC-09:01 | 0.59 |
Annual Sum or Average | 0.289146E+10 | 0.42 | |||
Minimum of Months | 91679519.13 | 0.36 | 592.35 | 0.59 | |
Maximum of Months | 0.465299E+09 | 0.50 | 592.35 | 0.59 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 62625063.78 | 0.45 | 175.82 | 01-JAN-16:02 | 0.59 |
February | 48684447.40 | 0.45 | 175.82 | 01-FEB-09:01 | 0.59 |
March | 47786922.06 | 0.46 | 175.82 | 02-MAR-16:01 | 0.59 |
April | 64340512.79 | 0.51 | 175.82 | 01-APR-15:01 | 0.59 |
May | 87303108.73 | 0.54 | 175.82 | 01-MAY-15:02 | 0.59 |
June | 0.114559E+09 | 0.56 | 175.82 | 01-JUN-08:62 | 0.59 |
July | 0.129730E+09 | 0.56 | 175.82 | 01-JUL-08:62 | 0.59 |
August | 0.134928E+09 | 0.57 | 175.82 | 01-AUG-08:61 | 0.59 |
September | 87426487.07 | 0.54 | 175.82 | 01-SEP-08:62 | 0.59 |
October | 55847263.24 | 0.49 | 175.82 | 01-OCT-15:02 | 0.59 |
November | 38132601.23 | 0.46 | 175.82 | 01-NOV-15:01 | 0.59 |
December | 49857648.09 | 0.44 | 175.82 | 01-DEC-09:01 | 0.59 |
Annual Sum or Average | 0.921221E+09 | 0.50 | |||
Minimum of Months | 38132601.23 | 0.44 | 175.82 | 0.59 | |
Maximum of Months | 0.134928E+09 | 0.57 | 175.82 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 72633353.53 | 0.49 | 173.38 | 01-JAN-16:02 | 0.59 |
February | 48793300.65 | 0.44 | 173.38 | 01-FEB-09:01 | 0.59 |
March | 30322567.95 | 0.36 | 173.38 | 03-MAR-09:02 | 0.59 |
April | 43041885.83 | 0.38 | 173.38 | 01-APR-15:01 | 0.59 |
May | 70253002.03 | 0.40 | 173.38 | 01-MAY-08:53 | 0.59 |
June | 0.107458E+09 | 0.47 | 173.38 | 01-JUN-08:51 | 0.59 |
July | 0.121839E+09 | 0.47 | 173.38 | 01-JUL-08:31 | 0.59 |
August | 0.121974E+09 | 0.50 | 173.38 | 01-AUG-07:51 | 0.59 |
September | 66185575.74 | 0.41 | 173.38 | 01-SEP-08:51 | 0.59 |
October | 31340826.62 | 0.36 | 173.38 | 01-OCT-15:02 | 0.59 |
November | 32395231.74 | 0.37 | 173.38 | 01-NOV-15:01 | 0.59 |
December | 56320631.95 | 0.44 | 173.38 | 01-DEC-09:01 | 0.59 |
Annual Sum or Average | 0.802557E+09 | 0.42 | |||
Minimum of Months | 30322567.95 | 0.36 | 173.38 | 0.59 | |
Maximum of Months | 0.121974E+09 | 0.50 | 173.38 | 0.59 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.251468E+09 | 0.47 | 779.36 | 02-JAN-09:01 | 0.59 |
February | 0.232330E+09 | 0.47 | 779.36 | 01-FEB-09:01 | 0.60 |
March | 0.300060E+09 | 0.50 | 779.36 | 01-MAR-19:02 | 0.59 |
April | 0.341373E+09 | 0.52 | 779.36 | 01-APR-08:62 | 0.59 |
May | 0.418789E+09 | 0.54 | 779.36 | 01-MAY-15:02 | 0.59 |
June | 0.528214E+09 | 0.56 | 779.36 | 01-JUN-08:62 | 0.59 |
July | 0.608173E+09 | 0.56 | 779.36 | 01-JUL-08:62 | 0.59 |
August | 0.683814E+09 | 0.57 | 779.36 | 01-AUG-08:61 | 0.59 |
September | 0.516469E+09 | 0.54 | 779.36 | 01-SEP-08:62 | 0.59 |
October | 0.412030E+09 | 0.52 | 779.36 | 01-OCT-08:62 | 0.59 |
November | 0.294545E+09 | 0.50 | 779.36 | 01-NOV-15:01 | 0.59 |
December | 0.249184E+09 | 0.48 | 779.36 | 01-DEC-09:01 | 0.59 |
Annual Sum or Average | 0.483645E+10 | 0.52 | |||
Minimum of Months | 0.232330E+09 | 0.47 | 779.36 | 0.59 | |
Maximum of Months | 0.683814E+09 | 0.57 | 779.36 | 0.60 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.612453E+09 | 0.556720E+09 | 612.91 | 07-JAN-16:03 | 557.13 | 557.13 | 36.94 | 0.94 |
February | 0.420374E+09 | 0.382120E+09 | 664.27 | 12-FEB-09:02 | 603.82 | 603.82 | 35.92 | 1.09 |
March | 0.255903E+09 | 0.232616E+09 | 536.75 | 16-MAR-08:07 | 487.91 | 487.91 | 36.90 | 0.76 |
April | 0.116682E+09 | 0.106064E+09 | 527.18 | 07-APR-08:04 | 479.20 | 479.20 | 46.91 | 0.74 |
May | 33036380.24 | 30030069.64 | 365.82 | 11-MAY-06:10 | 332.53 | 332.53 | 33.76 | 0.45 |
June | 5624430.77 | 5112607.57 | 188.31 | 10-JUN-05:00 | 171.17 | 171.17 | 27.24 | 0.21 |
July | 212764.79 | 193403.20 | 113.69 | 28-JUL-15:07 | 103.35 | 103.35 | 44.27 | 0.12 |
August | 133102.11 | 120989.82 | 55.10 | 15-AUG-08:38 | 50.09 | 50.09 | 46.39 | 0.06 |
September | 5864747.77 | 5331055.72 | 182.99 | 30-SEP-15:07 | 166.33 | 166.33 | 58.26 | 0.20 |
October | 0.214710E+09 | 0.195171E+09 | 559.81 | 31-OCT-08:62 | 508.87 | 508.87 | 33.87 | 0.81 |
November | 0.272872E+09 | 0.248041E+09 | 541.27 | 21-NOV-16:02 | 492.01 | 492.01 | 31.62 | 0.77 |
December | 0.491636E+09 | 0.446897E+09 | 580.26 | 22-DEC-16:01 | 527.46 | 527.46 | 31.31 | 0.86 |
Annual Sum or Average | 0.242950E+10 | 0.220842E+10 | ||||||
Minimum of Months | 133102.11 | 120989.82 | 55.10 | 50.09 | 50.09 | 27.24 | 0.06 | |
Maximum of Months | 0.612453E+09 | 0.556720E+09 | 664.27 | 603.82 | 603.82 | 58.26 | 1.09 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 9061198.98 | 8236629.87 | 267.84 | 31-JAN-16:01 | 243.47 | 243.47 | 7.74 | 8.49 |
February | 30873580.07 | 28064084.28 | 342.58 | 26-FEB-16:01 | 311.40 | 311.40 | 7.08 | 9.54 |
March | 0.135235E+09 | 0.122928E+09 | 789.07 | 30-MAR-15:05 | 717.27 | 717.27 | 6.73 | 13.96 |
April | 0.311234E+09 | 0.282911E+09 | 1052.23 | 17-APR-18:02 | 956.48 | 956.48 | 6.75 | 15.83 |
May | 0.590874E+09 | 0.537104E+09 | 1325.22 | 30-MAY-21:53 | 1204.62 | 1204.62 | 7.40 | 17.49 |
June | 0.118038E+10 | 0.107297E+10 | 1692.68 | 30-JUN-19:50 | 1538.65 | 1538.65 | 7.18 | 19.41 |
July | 0.164324E+10 | 0.149371E+10 | 1905.57 | 18-JUL-19:00 | 1732.16 | 1732.16 | 7.21 | 20.40 |
August | 0.186414E+10 | 0.169451E+10 | 2813.62 | 23-AUG-20:00 | 2557.58 | 2557.58 | 7.15 | 23.98 |
September | 0.940814E+09 | 0.855200E+09 | 1451.33 | 07-SEP-18:03 | 1319.26 | 1319.26 | 6.73 | 18.18 |
October | 0.327245E+09 | 0.297465E+09 | 1595.05 | 18-OCT-21:52 | 1449.90 | 1449.90 | 7.31 | 18.93 |
November | 81219887.52 | 73828877.75 | 473.03 | 05-NOV-15:13 | 429.98 | 429.98 | 7.13 | 11.08 |
December | 21355227.15 | 19411901.48 | 336.58 | 11-DEC-16:01 | 305.95 | 305.95 | 7.58 | 9.46 |
Annual Sum or Average | 0.713568E+10 | 0.648633E+10 | ||||||
Minimum of Months | 9061198.98 | 8236629.87 | 267.84 | 243.47 | 243.47 | 6.73 | 8.49 | |
Maximum of Months | 0.186414E+10 | 0.169451E+10 | 2813.62 | 2557.58 | 2557.58 | 7.74 | 23.98 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.684904E+10 | 0.622578E+10 | 4922.43 | 01-JAN-00:05 | 4474.49 | 4474.49 | 8.40 | 34.85 |
February | 0.790541E+10 | 0.718602E+10 | 4922.43 | 01-FEB-00:03 | 4474.49 | 4474.49 | 8.45 | 34.85 |
March | 0.125042E+11 | 0.113664E+11 | 4922.43 | 01-MAR-00:03 | 4474.49 | 4474.49 | 8.72 | 34.85 |
April | 0.126328E+11 | 0.114832E+11 | 4922.43 | 01-APR-00:10 | 4474.49 | 4474.49 | 8.51 | 34.85 |
May | 0.131842E+11 | 0.119845E+11 | 4922.43 | 01-MAY-00:05 | 4474.49 | 4474.49 | 9.15 | 34.85 |
June | 0.127589E+11 | 0.115979E+11 | 4922.43 | 01-JUN-00:05 | 4474.49 | 4474.49 | 9.41 | 34.85 |
July | 0.131842E+11 | 0.119845E+11 | 4922.43 | 01-JUL-00:10 | 4474.49 | 4474.49 | 10.25 | 34.85 |
August | 0.131842E+11 | 0.119845E+11 | 4922.43 | 01-AUG-00:05 | 4474.49 | 4474.49 | 9.39 | 34.85 |
September | 0.127589E+11 | 0.115979E+11 | 4922.43 | 01-SEP-00:05 | 4474.49 | 4474.49 | 9.23 | 34.85 |
October | 0.125802E+11 | 0.114354E+11 | 4922.43 | 01-OCT-00:10 | 4474.49 | 4474.49 | 8.70 | 34.85 |
November | 0.117437E+11 | 0.106751E+11 | 4922.43 | 01-NOV-00:05 | 4474.49 | 4474.49 | 8.41 | 34.85 |
December | 0.929222E+10 | 0.844663E+10 | 4922.43 | 01-DEC-00:03 | 4474.49 | 4474.49 | 8.40 | 34.85 |
Annual Sum or Average | 0.138578E+12 | 0.125968E+12 | ||||||
Minimum of Months | 0.684904E+10 | 0.622578E+10 | 4922.43 | 4474.49 | 4474.49 | 8.40 | 34.85 | |
Maximum of Months | 0.131842E+11 | 0.119845E+11 | 4922.43 | 4474.49 | 4474.49 | 10.25 | 34.85 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 49.33 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 50.00 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 50.15 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 53.24 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 53.54 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 54.08 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 54.64 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 54.62 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 54.50 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 53.62 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 53.61 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 50.74 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 49.33 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.64 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 60.97 | 80.12 | 36948.89 | 177504.44 | 27-JAN-09:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 34.47 | 79.41 | 29876.00 | 211233.18 | 12-FEB-09:02 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 36.94 | 36.94 | 19842.12 | 136598.77 | 16-MAR-08:07 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25.70 | 79.40 | 9459.03 | 109062.15 | 26-APR-08:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 39.02 | 39.02 | 2878.74 | 87377.97 | 11-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 27.39 | 27.39 | 518.50 | 46101.46 | 10-JUN-05:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 37.18 | 37.18 | 13.10 | 17965.08 | 28-JUL-15:07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 44.96 | 44.96 | 7.01 | 7989.35 | 10-AUG-08:05 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 48.80 | 48.80 | 471.54 | 38016.61 | 29-SEP-08:04 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 64.59 | 79.40 | 17636.52 | 156188.43 | 31-OCT-08:62 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 35.94 | 79.45 | 19030.32 | 155016.44 | 21-NOV-16:02 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 61.03 | 80.78 | 29814.83 | 173371.93 | 22-DEC-16:01 |
Annual Sum or Average | 0.00 | 13814.48 | ||||||
Minimum of Months | 0.00 | 0.00 | 25.70 | 27.39 | 7.01 | 7989.35 | ||
Maximum of Months | 0.00 | 0.00 | 64.59 | 80.78 | 36948.89 | 211233.18 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7696.98 | 197036.53 | 19-JAN-22:53 | 9.31 | 7.96 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 22590.60 | 329348.41 | 26-FEB-16:01 | 9.31 | 7.06 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 57613.92 | 423237.49 | 30-MAR-15:05 | 9.60 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 110095.09 | 404525.18 | 17-APR-18:02 | 9.51 | 6.74 | 0.00 | 0.00 | 01-APR-00:10 |
May | 194017.69 | 576380.17 | 30-MAY-21:51 | 11.33 | 7.38 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 315291.33 | 657488.10 | 26-JUN-21:52 | 11.79 | 7.29 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 388217.07 | 685663.54 | 25-JUL-21:52 | 11.98 | 7.29 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 416308.56 | 792715.11 | 23-AUG-21:52 | 12.55 | 7.12 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 270611.00 | 612984.70 | 09-SEP-21:52 | 11.49 | 7.29 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 112331.07 | 666459.76 | 18-OCT-21:53 | 11.85 | 7.29 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 46364.32 | 367954.76 | 05-NOV-15:03 | 9.63 | 7.11 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 14869.81 | 286409.81 | 12-DEC-16:03 | 9.35 | 7.39 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 163907.11 | 0.00 | ||||||
Minimum of Months | 7696.98 | 197036.53 | 9.31 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 416308.56 | 792715.11 | 12.55 | 7.96 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 49.33 | 59.99 | 25252.60 | 53156.35 | 31-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 50.00 | 60.00 | 25300.06 | 53145.83 | 02-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 50.15 | 59.97 | 24480.28 | 52260.20 | 01-MAR-07:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 53.24 | 59.97 | 22931.21 | 49302.06 | 03-APR-06:30 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 53.54 | 59.99 | 21112.13 | 45893.51 | 01-MAY-06:30 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 54.08 | 60.00 | 19499.93 | 42080.02 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 54.64 | 59.99 | 18505.61 | 39169.03 | 03-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 54.62 | 59.97 | 18455.18 | 39020.29 | 31-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 54.50 | 59.97 | 19304.91 | 41495.88 | 29-SEP-06:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.62 | 59.97 | 20847.77 | 45341.64 | 31-OCT-06:30 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 53.61 | 59.99 | 22671.83 | 49103.64 | 30-NOV-07:40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 50.74 | 59.97 | 24279.42 | 51852.05 | 28-DEC-08:00 |
Annual Sum or Average | 0.00 | 21867.29 | ||||||
Minimum of Months | 0.00 | 0.00 | 49.33 | 59.97 | 18455.18 | 39020.29 | ||
Maximum of Months | 0.00 | 0.00 | 54.64 | 60.00 | 25300.06 | 53156.35 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.598202E+11 | 0.00 | 0.857199E+10 | 0.343645E+11 | 0.00 | 0.00 |
February | 0.498647E+11 | 0.00 | 0.295379E+11 | 0.318052E+11 | 0.00 | 0.00 |
March | 0.503511E+11 | 0.00 | 0.884677E+11 | 0.368018E+11 | 0.00 | 0.00 |
April | 0.238590E+11 | 0.00 | 0.185861E+12 | 0.366421E+11 | 0.00 | 0.00 |
May | 0.775057E+10 | 0.00 | 0.367444E+12 | 0.393873E+11 | 0.00 | 0.00 |
June | 0.133415E+10 | 0.00 | 0.612444E+12 | 0.403510E+11 | 0.00 | 0.00 |
July | 20172841.69 | 0.00 | 0.801700E+12 | 0.424233E+11 | 0.00 | 0.00 |
August | 9809442.26 | 0.00 | 0.866298E+12 | 0.433518E+11 | 0.00 | 0.00 |
September | 0.115571E+10 | 0.00 | 0.526500E+12 | 0.395759E+11 | 0.00 | 0.00 |
October | 0.456755E+11 | 0.00 | 0.202313E+12 | 0.384619E+11 | 0.00 | 0.00 |
November | 0.422017E+11 | 0.00 | 0.674967E+11 | 0.357887E+11 | 0.00 | 0.00 |
December | 0.579151E+11 | 0.00 | 0.148349E+11 | 0.350973E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.339958E+12 | 0.00 | 0.377147E+13 | 0.454051E+12 | 0.00 | 0.00 |
Minimum of Months | 9809442.26 | 0.00 | 0.857199E+10 | 0.318052E+11 | 0.00 | 0.00 |
Maximum of Months | 0.598202E+11 | 0.00 | 0.866298E+12 | 0.433518E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.684360E+09 | 0.00 | 0.699421E+09 | 0.271000E+10 | 0.00 | 0.00 |
February | 0.588801E+09 | 0.00 | 0.198040E+10 | 0.244774E+10 | 0.00 | 0.00 |
March | 4112.02 | 0.00 | 0.717311E+10 | 0.271000E+10 | 0.00 | 0.00 |
April | 5360.70 | 0.00 | 0.143549E+11 | 0.262258E+10 | 0.00 | 0.00 |
May | 7323.34 | 0.00 | 0.302587E+11 | 0.271000E+10 | 0.00 | 0.00 |
June | 9489.30 | 0.00 | 0.447665E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 4939.57 | 0.00 | 0.559576E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 5280.15 | 0.00 | 0.571073E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 6927.54 | 0.00 | 0.400859E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 5815.40 | 0.00 | 0.162102E+11 | 0.271000E+10 | 0.00 | 0.00 |
November | 36855599.33 | 0.00 | 0.575607E+10 | 0.262258E+10 | 0.00 | 0.00 |
December | 0.123974E+09 | 0.00 | 0.119221E+10 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.143404E+10 | 0.00 | 0.275542E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 4112.02 | 0.00 | 0.699421E+09 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.684360E+09 | 0.00 | 0.571073E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.343645E+11 | 0.857199E+10 | 0.598202E+11 | 0.447180E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.318052E+11 | 0.295379E+11 | 0.498647E+11 | 0.255943E+12 | 39309941.81 | 0.00 | 0.00 | 0.00 |
March | 0.368018E+11 | 0.884677E+11 | 0.503511E+11 | 0.637422E+11 | 0.559966E+09 | 0.00 | 0.00 | 0.00 |
April | 0.366421E+11 | 0.185861E+12 | 0.238590E+11 | 0.297245E+11 | 0.515246E+10 | 0.00 | 0.00 | 0.00 |
May | 0.393873E+11 | 0.367444E+12 | 0.775057E+10 | 0.323650E+09 | 0.327923E+11 | 0.00 | 0.00 | 0.00 |
June | 0.403510E+11 | 0.612444E+12 | 0.133415E+10 | 0.00 | 0.134846E+12 | 0.00 | 0.00 | 0.00 |
July | 0.424233E+11 | 0.801700E+12 | 20172841.69 | 0.00 | 0.217187E+12 | 0.00 | 0.00 | 0.00 |
August | 0.433518E+11 | 0.866298E+12 | 9809442.26 | 0.00 | 0.275515E+12 | 0.00 | 0.00 | 0.00 |
September | 0.395759E+11 | 0.526500E+12 | 0.115571E+10 | 0.00 | 0.811204E+11 | 0.00 | 0.00 | 0.00 |
October | 0.384619E+11 | 0.202313E+12 | 0.456755E+11 | 0.151155E+11 | 0.139499E+11 | 0.00 | 0.00 | 0.00 |
November | 0.357887E+11 | 0.674967E+11 | 0.422017E+11 | 0.124815E+12 | 0.244839E+09 | 0.00 | 0.00 | 0.00 |
December | 0.350973E+11 | 0.148349E+11 | 0.579151E+11 | 0.274482E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.454051E+12 | 0.377147E+13 | 0.339958E+12 | 0.121133E+13 | 0.761407E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.318052E+11 | 0.857199E+10 | 9809442.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.433518E+11 | 0.866298E+12 | 0.598202E+11 | 0.447180E+12 | 0.275515E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.699421E+09 | 0.684360E+09 | 0.450711E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.198040E+10 | 0.588801E+09 | 0.281723E+11 | 353025.45 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.717311E+10 | 4112.02 | 0.126479E+11 | 0.360284E+09 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.143549E+11 | 5360.70 | 0.592296E+10 | 0.750848E+09 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.302587E+11 | 7323.34 | 0.106669E+10 | 0.462044E+10 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.447665E+11 | 9489.30 | 0.338365E+09 | 0.181770E+11 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.559576E+11 | 4939.57 | 0.00 | 0.298043E+11 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.571073E+11 | 5280.15 | 42440.84 | 0.387275E+11 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.400859E+11 | 6927.54 | 0.208820E+09 | 0.137667E+11 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.162102E+11 | 5815.40 | 0.781860E+10 | 0.230411E+10 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.575607E+10 | 36855599.33 | 0.178779E+11 | 0.104588E+09 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.119221E+10 | 0.123974E+09 | 0.322885E+11 | 810185.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.275542E+12 | 0.143404E+10 | 0.151413E+12 | 0.108617E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.699421E+09 | 4112.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.571073E+11 | 0.684360E+09 | 0.450711E+11 | 0.387275E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.343645E+11 | 0.598202E+11 | 0.857199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.318052E+11 | 0.498647E+11 | 0.295379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.368018E+11 | 0.503511E+11 | 0.884677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.366421E+11 | 0.238590E+11 | 0.185861E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393873E+11 | 0.775057E+10 | 0.367444E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.403510E+11 | 0.133415E+10 | 0.612444E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.424233E+11 | 20172841.69 | 0.801700E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.433518E+11 | 9809442.26 | 0.866298E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.395759E+11 | 0.115571E+10 | 0.526500E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.384619E+11 | 0.456755E+11 | 0.202313E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.357887E+11 | 0.422017E+11 | 0.674967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.350973E+11 | 0.579151E+11 | 0.148349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.454051E+12 | 0.339958E+12 | 0.377147E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.318052E+11 | 9809442.26 | 0.857199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.433518E+11 | 0.598202E+11 | 0.866298E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.684360E+09 | 0.699421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.588801E+09 | 0.198040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 4112.02 | 0.717311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 5360.70 | 0.143549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 7323.34 | 0.302587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 9489.30 | 0.447665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 4939.57 | 0.559576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 5280.15 | 0.571073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 6927.54 | 0.400859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 5815.40 | 0.162102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 36855599.33 | 0.575607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.123974E+09 | 0.119221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.143404E+10 | 0.275542E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 4112.02 | 0.699421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.684360E+09 | 0.571073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.429592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 |
February | 0.375757E+11 | 0.00 | 0.00 | 0.00 | 3192647.39 | 0.00 | 0.00 | 0.00 | 0.86 |
March | 0.385480E+11 | 0.00 | 0.00 | 0.00 | 35972626.00 | 0.00 | 0.00 | 0.00 | 0.87 |
April | 0.272326E+11 | 0.00 | 0.00 | 0.00 | 0.536006E+09 | 0.00 | 0.00 | 0.00 | 0.87 |
May | 0.154570E+11 | 0.00 | 0.00 | 0.00 | 0.321903E+10 | 0.00 | 0.00 | 0.00 | 0.87 |
June | 0.527639E+10 | 0.00 | 0.00 | 0.00 | 0.140712E+11 | 0.00 | 0.00 | 0.00 | 0.86 |
July | 0.622473E+09 | 0.00 | 0.00 | 0.00 | 0.235665E+11 | 0.00 | 0.00 | 0.00 | 0.84 |
August | 0.227522E+09 | 0.384102E+10 | 0.00 | 89170.92 | 0.238506E+11 | 0.00 | 49639795.56 | 0.00 | 0.84 |
September | 0.448909E+09 | 0.690548E+10 | 0.00 | 20088145.42 | 0.443783E+10 | 0.00 | 0.930410E+10 | 0.00 | 0.90 |
October | 0.110676E+10 | 0.253894E+10 | 0.00 | 48816372.71 | 0.465769E+09 | 0.00 | 0.351245E+11 | 0.00 | 0.94 |
November | 0.127025E+10 | 41147320.10 | 0.00 | 55578962.97 | 12490339.92 | 0.00 | 0.419321E+11 | 0.00 | 0.96 |
December | 0.179040E+11 | 0.00 | 0.00 | 18013961.73 | 0.00 | 0.00 | 0.271783E+11 | 0.00 | 0.88 |
Annual Sum or Average | 0.188629E+12 | 0.133266E+11 | 0.00 | 0.142587E+09 | 0.701986E+11 | 0.00 | 0.113589E+12 | 0.00 | 0.88 |
Minimum of Months | 0.227522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 |
Maximum of Months | 0.429592E+11 | 0.690548E+10 | 0.00 | 55578962.97 | 0.238506E+11 | 0.00 | 0.419321E+11 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.429186E+10 | 0.00 | 0.00 | 92593.82 | 0.00 | 0.171031E+10 | 0.162286E+09 | 0.00 | 2.23 |
February | 0.435907E+10 | 529918.57 | 0.00 | 360089.08 | 0.00 | 0.903625E+09 | 0.129378E+09 | 0.00 | 2.25 |
March | 0.524870E+10 | 3742432.16 | 0.00 | 493564.31 | 1876209.64 | 778378.89 | 0.281518E+09 | 0.00 | 2.27 |
April | 0.370194E+10 | 15889124.49 | 0.00 | 321320.96 | 62150402.25 | 0.00 | 0.204585E+09 | 0.00 | 2.29 |
May | 0.209218E+10 | 0.200213E+09 | 0.00 | 230659.31 | 0.261673E+09 | 0.00 | 0.125005E+09 | 0.00 | 2.28 |
June | 0.652396E+09 | 0.142142E+10 | 0.00 | 172899.69 | 0.609808E+09 | 0.00 | 0.104368E+09 | 0.00 | 2.25 |
July | 76678811.42 | 0.247059E+10 | 0.00 | 27379.26 | 0.100455E+10 | 0.00 | 12591882.42 | 0.00 | 2.25 |
August | 26787789.35 | 0.351495E+10 | 0.00 | 34613.10 | 0.700960E+09 | 0.00 | 12962527.23 | 0.00 | 2.33 |
September | 0.111373E+10 | 0.927062E+09 | 0.00 | 734129.30 | 0.720596E+09 | 0.00 | 0.211328E+09 | 0.00 | 2.33 |
October | 0.417558E+10 | 0.159613E+09 | 0.00 | 1347945.67 | 0.255645E+09 | 0.00 | 0.588196E+09 | 0.00 | 2.32 |
November | 0.512601E+10 | 1562122.19 | 0.00 | 899473.73 | 6000822.56 | 92125873.98 | 0.390311E+09 | 0.00 | 2.28 |
December | 0.565681E+10 | 0.00 | 0.00 | 373032.90 | 0.00 | 0.401849E+09 | 0.316407E+09 | 0.00 | 2.24 |
Annual Sum or Average | 0.365217E+11 | 0.871558E+10 | 0.00 | 5087701.13 | 0.362326E+10 | 0.310869E+10 | 0.253894E+10 | 0.00 | 2.28 |
Minimum of Months | 26787789.35 | 0.00 | 0.00 | 27379.26 | 0.00 | 0.00 | 12591882.42 | 0.00 | 2.23 |
Maximum of Months | 0.565681E+10 | 0.351495E+10 | 0.00 | 1347945.67 | 0.100455E+10 | 0.171031E+10 | 0.588196E+09 | 0.00 | 2.33 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.461459E+10 | 0.00 | 0.00 | 368.43 | 0.00 | 0.00 | 5990811.17 | 0.00 | 1.45 |
February | 0.388034E+10 | 0.00 | 0.00 | 97258.15 | 343392.80 | 0.00 | 0.161241E+09 | 0.00 | 1.45 |
March | 0.349779E+10 | 128054.97 | 0.00 | 468496.46 | 3741066.57 | 0.00 | 0.650116E+09 | 0.00 | 1.47 |
April | 0.193378E+10 | 1399995.80 | 0.00 | 1053040.60 | 56251390.69 | 0.00 | 0.101112E+10 | 0.00 | 1.49 |
May | 0.718764E+09 | 73838573.54 | 0.00 | 1639797.30 | 0.275854E+09 | 0.00 | 0.958102E+09 | 0.00 | 1.50 |
June | 0.104307E+09 | 0.889996E+09 | 0.00 | 1044173.29 | 0.692433E+09 | 0.00 | 0.475425E+09 | 0.00 | 1.52 |
July | 10865409.98 | 0.174779E+10 | 0.00 | 227136.83 | 0.922335E+09 | 0.00 | 56667961.23 | 0.00 | 1.51 |
August | 1169720.81 | 0.250670E+10 | 0.00 | 149930.39 | 0.685909E+09 | 0.00 | 29265184.03 | 0.00 | 1.53 |
September | 0.352777E+09 | 0.673780E+09 | 0.00 | 1157748.19 | 0.549247E+09 | 0.00 | 0.659106E+09 | 0.00 | 1.51 |
October | 0.243945E+10 | 0.117895E+09 | 0.00 | 949631.21 | 0.182097E+09 | 0.00 | 0.112995E+10 | 0.00 | 1.47 |
November | 0.371737E+10 | 0.00 | 0.00 | 196059.45 | 5666001.31 | 0.00 | 0.459442E+09 | 0.00 | 1.46 |
December | 0.467466E+10 | 0.00 | 0.00 | 34001.18 | 0.00 | 0.00 | 96806038.40 | 0.00 | 1.45 |
Annual Sum or Average | 0.259459E+11 | 0.601153E+10 | 0.00 | 7017641.49 | 0.337388E+10 | 0.00 | 0.569323E+10 | 0.00 | 1.48 |
Minimum of Months | 1169720.81 | 0.00 | 0.00 | 368.43 | 0.00 | 0.00 | 5990811.17 | 0.00 | 1.45 |
Maximum of Months | 0.467466E+10 | 0.250670E+10 | 0.00 | 1639797.30 | 0.922335E+09 | 0.00 | 0.112995E+10 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.345781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601884E+09 | 0.00 | 0.00 | 0.60 |
February | 0.311935E+10 | 0.00 | 0.00 | 0.00 | 301708.53 | 0.431591E+09 | 0.00 | 0.00 | 0.60 |
March | 0.364282E+10 | 0.00 | 0.00 | 0.00 | 3399450.90 | 0.00 | 0.00 | 0.00 | 0.61 |
April | 0.257351E+10 | 0.00 | 0.00 | 0.00 | 50653114.96 | 0.00 | 0.00 | 0.00 | 0.61 |
May | 0.145399E+10 | 8933763.83 | 0.00 | 9034.77 | 0.295268E+09 | 0.00 | 6698357.31 | 0.00 | 0.61 |
June | 0.457877E+09 | 0.468149E+09 | 0.00 | 97138.58 | 0.886614E+09 | 0.00 | 40730955.15 | 0.00 | 0.61 |
July | 50340471.59 | 0.111635E+10 | 0.00 | 37695.01 | 0.118256E+10 | 0.00 | 8446150.66 | 0.00 | 0.61 |
August | 18240366.25 | 0.158045E+10 | 0.00 | 24542.81 | 0.113179E+10 | 0.00 | 7951924.54 | 0.00 | 0.61 |
September | 0.852207E+09 | 0.162840E+09 | 0.00 | 15481.78 | 0.879736E+09 | 0.00 | 20206834.19 | 0.00 | 0.61 |
October | 0.312207E+10 | 0.00 | 0.00 | 0.00 | 0.260409E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
November | 0.366996E+10 | 0.00 | 0.00 | 0.00 | 4978208.39 | 0.00 | 0.00 | 0.00 | 0.60 |
December | 0.419229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 0.266105E+11 | 0.333672E+10 | 0.00 | 183892.95 | 0.469571E+10 | 0.103348E+10 | 84034221.85 | 0.00 | 0.61 |
Minimum of Months | 18240366.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
Maximum of Months | 0.419229E+10 | 0.158045E+10 | 0.00 | 97138.58 | 0.118256E+10 | 0.601884E+09 | 40730955.15 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.143511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751678E+09 | 0.00 | 0.00 | 0.56 |
February | 0.148809E+10 | 0.00 | 0.00 | 0.00 | 162517.96 | 0.424657E+09 | 0.00 | 0.00 | 0.56 |
March | 0.196224E+10 | 0.00 | 0.00 | 0.00 | 1831144.18 | 0.00 | 0.00 | 0.00 | 0.57 |
April | 0.138624E+10 | 0.00 | 0.00 | 0.00 | 27284746.61 | 0.00 | 0.00 | 0.00 | 0.57 |
May | 0.786820E+09 | 0.00 | 0.00 | 0.00 | 0.163861E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.268181E+09 | 0.117089E+09 | 0.00 | 655.98 | 0.599190E+09 | 0.00 | 406418.57 | 0.00 | 0.56 |
July | 30838058.38 | 0.406890E+09 | 0.00 | 672.24 | 0.799070E+09 | 0.00 | 847506.10 | 0.00 | 0.56 |
August | 13016315.22 | 0.559816E+09 | 0.00 | 3723.09 | 0.855320E+09 | 0.00 | 1093103.75 | 0.00 | 0.55 |
September | 0.469942E+09 | 20809086.01 | 0.00 | 0.00 | 0.538601E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 0.168173E+10 | 0.00 | 0.00 | 0.00 | 0.140272E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
November | 0.197686E+10 | 0.00 | 0.00 | 0.00 | 2681555.80 | 0.00 | 0.00 | 0.00 | 0.56 |
December | 0.220526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52953760.67 | 0.00 | 0.00 | 0.56 |
Annual Sum or Average | 0.137043E+11 | 0.110460E+10 | 0.00 | 5051.30 | 0.312827E+10 | 0.122929E+10 | 2347028.41 | 0.00 | 0.56 |
Minimum of Months | 13016315.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.220526E+10 | 0.559816E+09 | 0.00 | 3723.09 | 0.855320E+09 | 0.751678E+09 | 1093103.75 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.488616E+09 | 0.00 | 0.00 | 89641648.36 | 0.00 | 0.00 | 0.767288E+11 | 0.00 | 24.09 |
February | 0.316345E+09 | 5113207.26 | 0.00 | 83451933.56 | 0.00 | 0.00 | 0.675793E+11 | 0.00 | 24.22 |
March | 0.211732E+09 | 59020662.78 | 0.00 | 97207555.68 | 785840.87 | 0.00 | 0.691310E+11 | 0.00 | 24.53 |
April | 0.154037E+09 | 0.890695E+09 | 0.00 | 94792600.50 | 11090286.61 | 0.00 | 0.483954E+11 | 0.00 | 24.57 |
May | 93167972.42 | 0.569317E+10 | 0.00 | 74725609.17 | 31325648.49 | 0.00 | 0.268306E+11 | 0.00 | 24.61 |
June | 20360176.26 | 0.253338E+11 | 0.00 | 28886357.21 | 67467547.68 | 0.00 | 0.910197E+10 | 0.00 | 24.10 |
July | 0.00 | 0.421241E+11 | 0.00 | 4638626.96 | 89107155.62 | 0.00 | 0.102981E+10 | 0.00 | 23.44 |
August | 1504832.32 | 0.498608E+11 | 0.00 | 2612473.28 | 54612201.42 | 0.00 | 0.453084E+09 | 0.00 | 23.59 |
September | 67057779.06 | 0.197577E+11 | 0.00 | 43301041.32 | 57899884.19 | 0.00 | 0.164591E+11 | 0.00 | 24.30 |
October | 0.177922E+09 | 0.512985E+10 | 0.00 | 83906160.72 | 9256148.65 | 0.00 | 0.591398E+11 | 0.00 | 24.38 |
November | 0.198747E+09 | 88442665.14 | 0.00 | 90089894.79 | 1431494.33 | 0.00 | 0.701599E+11 | 0.00 | 24.35 |
December | 0.265215E+09 | 0.00 | 0.00 | 90136142.71 | 0.00 | 0.00 | 0.798804E+11 | 0.00 | 24.11 |
Annual Sum or Average | 0.199470E+10 | 0.148943E+12 | 0.00 | 0.783390E+09 | 0.322976E+09 | 0.00 | 0.524889E+12 | 0.00 | 24.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2612473.28 | 0.00 | 0.00 | 0.453084E+09 | 0.00 | 23.44 |
Maximum of Months | 0.488616E+09 | 0.498608E+11 | 0.00 | 97207555.68 | 89107155.62 | 0.00 | 0.798804E+11 | 0.00 | 24.61 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.182968E+11 | 0.00 | 0.00 | 4428112.87 | 0.00 | 0.00 | 0.952114E+10 | 0.00 | 3.59 |
February | 0.127400E+11 | 2312090.25 | 0.00 | 8602221.72 | 0.00 | 0.00 | 0.116447E+11 | 0.00 | 3.63 |
March | 0.802948E+10 | 19450794.31 | 0.00 | 17678260.57 | 5406924.87 | 0.00 | 0.170609E+11 | 0.00 | 3.68 |
April | 0.496517E+10 | 0.171654E+09 | 0.00 | 17048674.33 | 0.178346E+09 | 0.00 | 0.128935E+11 | 0.00 | 3.72 |
May | 0.173948E+10 | 0.153369E+10 | 0.00 | 18122883.20 | 0.581923E+09 | 0.00 | 0.850602E+10 | 0.00 | 3.75 |
June | 0.493514E+09 | 0.816430E+10 | 0.00 | 7683528.51 | 0.140820E+10 | 0.00 | 0.304717E+10 | 0.00 | 3.81 |
July | 15844894.82 | 0.141369E+11 | 0.00 | 1962121.96 | 0.203835E+10 | 0.00 | 0.407596E+09 | 0.00 | 3.79 |
August | 14227309.47 | 0.180481E+11 | 0.00 | 997936.06 | 0.156056E+10 | 0.00 | 0.184088E+09 | 0.00 | 3.90 |
September | 0.107395E+10 | 0.629081E+10 | 0.00 | 13146593.27 | 0.122124E+10 | 0.00 | 0.516865E+10 | 0.00 | 3.86 |
October | 0.582587E+10 | 0.145936E+10 | 0.00 | 21909319.66 | 0.444083E+09 | 0.00 | 0.159435E+11 | 0.00 | 3.77 |
November | 0.827394E+10 | 16330063.25 | 0.00 | 16629954.17 | 17800207.94 | 0.00 | 0.171051E+11 | 0.00 | 3.68 |
December | 0.148773E+11 | 0.00 | 0.00 | 9149702.85 | 0.00 | 0.00 | 0.139346E+11 | 0.00 | 3.61 |
Annual Sum or Average | 0.763456E+11 | 0.498429E+11 | 0.00 | 0.137359E+09 | 0.745591E+10 | 0.00 | 0.115417E+12 | 0.00 | 3.73 |
Minimum of Months | 14227309.47 | 0.00 | 0.00 | 997936.06 | 0.00 | 0.00 | 0.184088E+09 | 0.00 | 3.59 |
Maximum of Months | 0.182968E+11 | 0.180481E+11 | 0.00 | 21909319.66 | 0.203835E+10 | 0.00 | 0.171051E+11 | 0.00 | 3.90 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.800105E+11 | 0.00 | 0.00 | 5147289.21 | 0.00 | 0.00 | 0.141023E+11 | 0.00 | 1.76 |
February | 0.582987E+11 | 0.00 | 0.00 | 14932786.26 | 6993919.18 | 0.00 | 0.242238E+11 | 0.00 | 1.77 |
March | 0.378932E+11 | 20992846.01 | 0.00 | 44043393.14 | 57809980.62 | 0.00 | 0.472948E+11 | 0.00 | 1.80 |
April | 0.180849E+11 | 0.131297E+09 | 0.00 | 57729458.62 | 0.104314E+10 | 0.00 | 0.428651E+11 | 0.00 | 1.83 |
May | 0.512467E+10 | 0.248639E+10 | 0.00 | 69170346.82 | 0.474020E+10 | 0.00 | 0.301932E+11 | 0.00 | 1.87 |
June | 0.120434E+10 | 0.225849E+11 | 0.00 | 30892081.91 | 0.106536E+11 | 0.00 | 0.112293E+11 | 0.00 | 1.91 |
July | 30701763.02 | 0.419270E+11 | 0.00 | 7642688.55 | 0.140999E+11 | 0.00 | 0.146409E+10 | 0.00 | 1.90 |
August | 18028906.02 | 0.574186E+11 | 0.00 | 3886055.64 | 0.101878E+11 | 0.00 | 0.669472E+09 | 0.00 | 1.94 |
September | 0.317465E+10 | 0.182797E+11 | 0.00 | 42930237.69 | 0.736389E+10 | 0.00 | 0.185568E+11 | 0.00 | 1.91 |
October | 0.236880E+11 | 0.403684E+10 | 0.00 | 54106239.89 | 0.237626E+10 | 0.00 | 0.505299E+11 | 0.00 | 1.83 |
November | 0.382131E+11 | 7288026.82 | 0.00 | 36728398.32 | 0.108112E+09 | 0.00 | 0.474863E+11 | 0.00 | 1.79 |
December | 0.677353E+11 | 0.00 | 0.00 | 15380986.30 | 0.00 | 0.00 | 0.295742E+11 | 0.00 | 1.76 |
Annual Sum or Average | 0.333476E+12 | 0.146893E+12 | 0.00 | 0.382590E+09 | 0.506376E+11 | 0.00 | 0.318189E+12 | 0.00 | 1.84 |
Minimum of Months | 18028906.02 | 0.00 | 0.00 | 3886055.64 | 0.00 | 0.00 | 0.669472E+09 | 0.00 | 1.76 |
Maximum of Months | 0.800105E+11 | 0.574186E+11 | 0.00 | 69170346.82 | 0.140999E+11 | 0.00 | 0.505299E+11 | 0.00 | 1.94 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 75192790.11 | 0.00 | 0.00 | 971296.41 | 0.00 | 0.130157E+10 | 0.143260E+09 | 0.00 | 0.35 |
February | 81209781.43 | 0.00 | 0.00 | 2684258.87 | 0.00 | 0.884777E+09 | 0.346452E+09 | 0.00 | 0.35 |
March | 66458617.70 | 8769259.92 | 4577.80 | 6671764.37 | 173962.78 | 0.283118E+09 | 0.822892E+09 | 1350.47 | 0.35 |
April | 23215403.63 | 41675846.82 | 63755.00 | 9812888.45 | 2185629.77 | 75458332.08 | 0.742196E+09 | 7185.66 | 0.35 |
May | 1830105.97 | 0.244077E+09 | 14555.95 | 6500961.92 | 295900.36 | 938366.83 | 0.306482E+09 | 3764.06 | 0.36 |
June | 0.00 | 0.776306E+09 | 187010.05 | 3010552.34 | 0.00 | 264395.26 | 0.138259E+09 | 9900.48 | 0.36 |
July | 0.00 | 0.110874E+10 | 256060.86 | 234362.32 | 2522541.77 | 46072.50 | 3754174.40 | 4571.31 | 0.35 |
August | 0.00 | 0.121770E+10 | 145771.48 | 65993.43 | 0.00 | 10541.52 | 350952.81 | 6905.91 | 0.36 |
September | 1452532.23 | 0.582973E+09 | 579455.85 | 3388030.94 | 3940451.36 | 867495.37 | 0.181696E+09 | 25560.62 | 0.36 |
October | 28444003.02 | 0.152334E+09 | 144736.21 | 7106110.98 | 3303330.02 | 0.163196E+09 | 0.746049E+09 | 9702.48 | 0.36 |
November | 46829346.69 | 9243777.98 | 15712.89 | 4167756.99 | 1201933.04 | 0.485233E+09 | 0.701453E+09 | 6097.37 | 0.35 |
December | 80396277.95 | 381118.12 | 0.00 | 1618833.14 | 174110.23 | 0.112355E+10 | 0.276593E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.405029E+09 | 0.414220E+10 | 1411636.09 | 46232810.16 | 13797859.32 | 0.431902E+10 | 0.440944E+10 | 75038.36 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 65993.43 | 0.00 | 10541.52 | 350952.81 | 0.00 | 0.35 |
Maximum of Months | 81209781.43 | 0.121770E+10 | 579455.85 | 9812888.45 | 3940451.36 | 0.130157E+10 | 0.822892E+09 | 25560.62 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 70480840.16 | 0.00 | 0.00 | 183082.59 | 0.00 | 0.140502E+10 | 45132903.49 | 0.00 | 0.35 |
February | 0.116224E+09 | 0.00 | 0.00 | 976103.72 | 0.00 | 0.994573E+09 | 0.203194E+09 | 0.00 | 0.35 |
March | 0.225842E+09 | 7268914.29 | 10440.80 | 3254435.93 | 1662893.97 | 0.380948E+09 | 0.568958E+09 | 5853.38 | 0.35 |
April | 0.163037E+09 | 31971392.78 | 148242.99 | 7372077.77 | 11800024.33 | 79191131.69 | 0.600982E+09 | 7609.83 | 0.36 |
May | 98786178.85 | 0.205270E+09 | 159654.52 | 4354665.31 | 38921931.65 | 624664.76 | 0.211949E+09 | 10918.30 | 0.36 |
June | 28890170.46 | 0.655403E+09 | 95401.36 | 2630993.57 | 0.120911E+09 | 36783.94 | 0.109959E+09 | 2120.06 | 0.36 |
July | 3840703.44 | 0.949069E+09 | 193977.13 | 86598.90 | 0.162125E+09 | 2624.65 | 104209.52 | 3650.56 | 0.36 |
August | 427437.68 | 0.109426E+10 | 102478.61 | 0.00 | 0.123346E+09 | 0.00 | 0.00 | 2087.44 | 0.36 |
September | 60769474.19 | 0.464839E+09 | 218984.00 | 2333823.15 | 0.122383E+09 | 632953.02 | 0.123646E+09 | 8526.55 | 0.36 |
October | 0.163461E+09 | 0.118937E+09 | 308421.13 | 3335864.11 | 36512230.74 | 0.236509E+09 | 0.541378E+09 | 15554.81 | 0.36 |
November | 0.156999E+09 | 5134265.48 | 28657.36 | 1592671.04 | 5299858.48 | 0.714339E+09 | 0.364609E+09 | 3513.54 | 0.35 |
December | 0.110789E+09 | 373451.16 | 0.00 | 441955.83 | 181712.14 | 0.128124E+10 | 89513008.68 | 0.00 | 0.35 |
Annual Sum or Average | 0.119955E+10 | 0.353253E+10 | 1266257.90 | 26562271.90 | 0.623145E+09 | 0.509311E+10 | 0.285943E+10 | 59834.45 | 0.35 |
Minimum of Months | 427437.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.225842E+09 | 0.109426E+10 | 308421.13 | 7372077.77 | 0.162125E+09 | 0.140502E+10 | 0.600982E+09 | 15554.81 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100700E+10 | 0.00 | 0.00 | 357754.62 | 3066352.34 | 0.00 | 0.267695E+09 | 0.00 | 0.02 |
February | 0.757296E+09 | 0.00 | 0.00 | 1049477.18 | 0.00 | 0.00 | 0.406130E+09 | 0.00 | 0.02 |
March | 0.252281E+09 | 13272485.05 | 0.00 | 2401639.07 | 0.00 | 0.00 | 0.992674E+09 | 0.00 | 0.02 |
April | 92905587.22 | 88157814.80 | 0.00 | 2237654.60 | 0.00 | 0.00 | 0.494593E+09 | 0.00 | 0.02 |
May | 1912382.34 | 0.313440E+09 | 0.00 | 708145.83 | 0.00 | 0.00 | 0.163446E+09 | 0.00 | 0.02 |
June | 0.00 | 0.573448E+09 | 0.00 | 222665.39 | 0.00 | 0.00 | 66814161.99 | 0.00 | 0.02 |
July | 0.00 | 0.880184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
August | 0.00 | 0.966347E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
September | 32501854.92 | 0.653079E+09 | 0.00 | 748771.11 | 0.00 | 0.00 | 32971960.33 | 0.00 | 0.02 |
October | 0.186370E+09 | 0.236362E+09 | 0.00 | 2371894.87 | 0.00 | 0.00 | 0.597304E+09 | 0.00 | 0.02 |
November | 0.290108E+09 | 45923100.57 | 0.00 | 2534598.82 | 8419790.47 | 0.00 | 0.933924E+09 | 0.00 | 0.02 |
December | 0.653251E+09 | 0.00 | 0.00 | 1633660.95 | 0.00 | 0.00 | 0.880965E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.327362E+10 | 0.377021E+10 | 0.00 | 14266262.43 | 11486142.82 | 0.00 | 0.483652E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.100700E+10 | 0.966347E+09 | 0.00 | 2534598.82 | 8419790.47 | 0.00 | 0.992674E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.137371E+10 | 0.00 | 0.00 | 9485500.39 | 0.00 | 0.130805E+11 | 0.616520E+10 | 0.00 | 0.40 |
February | 0.181554E+10 | 0.00 | 0.00 | 25437379.99 | 0.00 | 0.718340E+10 | 0.881237E+10 | 0.00 | 0.40 |
March | 0.306398E+10 | 95199698.88 | 323566.80 | 56072805.75 | 25839353.71 | 0.238851E+09 | 0.126336E+11 | 13022.34 | 0.40 |
April | 0.222615E+10 | 0.399653E+09 | 447821.98 | 94181248.23 | 0.195740E+09 | 31671502.11 | 0.918563E+10 | 6364.33 | 0.40 |
May | 0.137089E+10 | 0.267072E+10 | 294727.43 | 53887906.48 | 0.643609E+09 | 1157418.71 | 0.285655E+10 | 7554.59 | 0.40 |
June | 0.419633E+09 | 0.887990E+10 | 146464.59 | 26788878.07 | 0.165150E+10 | 276989.45 | 0.147290E+10 | 4829.92 | 0.40 |
July | 52096838.16 | 0.128331E+11 | 586645.98 | 1692324.73 | 0.224172E+10 | 0.00 | 931478.78 | 2588.62 | 0.40 |
August | 5797935.68 | 0.148110E+11 | 0.00 | 0.00 | 0.170653E+10 | 0.00 | 0.00 | 0.00 | 0.40 |
September | 0.837771E+09 | 0.611234E+10 | 1969663.32 | 30708019.48 | 0.185406E+10 | 2030410.35 | 0.167122E+10 | 24661.48 | 0.41 |
October | 0.221726E+10 | 0.153123E+10 | 1844761.63 | 56268004.90 | 0.579870E+09 | 0.108090E+09 | 0.104325E+11 | 35461.07 | 0.40 |
November | 0.212959E+10 | 69821564.82 | 251060.40 | 41248063.34 | 71889400.90 | 0.160327E+10 | 0.130124E+11 | 6984.83 | 0.40 |
December | 0.152777E+10 | 5065640.95 | 0.00 | 18424033.31 | 2464816.11 | 0.685585E+10 | 0.117001E+11 | 0.00 | 0.40 |
Annual Sum or Average | 0.170402E+11 | 0.474080E+11 | 5864712.13 | 0.414194E+09 | 0.897323E+10 | 0.291051E+11 | 0.779433E+11 | 101467.18 | 0.40 |
Minimum of Months | 5797935.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.306398E+10 | 0.148110E+11 | 1969663.32 | 94181248.23 | 0.224172E+10 | 0.130805E+11 | 0.130124E+11 | 35461.07 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 75411477.35 | 0.00 | 0.00 | 675468.64 | 0.00 | 0.128843E+10 | 0.156477E+09 | 0.00 | 0.35 |
February | 72989245.47 | 0.00 | 0.00 | 2820058.28 | 0.00 | 0.877543E+09 | 0.361770E+09 | 0.00 | 0.35 |
March | 43623337.26 | 8883748.70 | 9730.27 | 6417908.07 | 53217.99 | 0.292589E+09 | 0.836510E+09 | 2454.02 | 0.35 |
April | 13162397.56 | 41896579.13 | 16159.03 | 10039137.59 | 2019622.37 | 69689020.91 | 0.757792E+09 | 56.72 | 0.35 |
May | 0.00 | 0.244088E+09 | 6911.39 | 6988670.58 | 295900.36 | 331348.62 | 0.308432E+09 | 615.48 | 0.36 |
June | 0.00 | 0.776503E+09 | 0.00 | 3325561.27 | 0.00 | 0.00 | 0.138208E+09 | 0.00 | 0.36 |
July | 0.00 | 0.110862E+10 | 92472.45 | 231897.27 | 2811008.09 | 46072.50 | 3756639.45 | 212.39 | 0.35 |
August | 0.00 | 0.121786E+10 | 0.00 | 84468.81 | 0.00 | 0.00 | 343018.95 | 0.00 | 0.36 |
September | 1452532.23 | 0.584348E+09 | 85030.61 | 3675266.50 | 3083672.39 | 650955.57 | 0.181626E+09 | 1107.65 | 0.36 |
October | 22873666.60 | 0.152480E+09 | 6572.07 | 6932874.57 | 3303330.02 | 0.163529E+09 | 0.751460E+09 | 1821.83 | 0.36 |
November | 43356875.73 | 9406535.48 | 20011.31 | 4234192.37 | 1035968.51 | 0.482403E+09 | 0.707690E+09 | 5005.97 | 0.35 |
December | 78265821.96 | 381118.12 | 0.00 | 1463592.06 | 174110.23 | 0.109839E+10 | 0.304040E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.351135E+09 | 0.414446E+10 | 236887.12 | 46889096.01 | 12776829.96 | 0.427360E+10 | 0.450810E+10 | 11274.07 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 84468.81 | 0.00 | 0.00 | 343018.95 | 0.00 | 0.35 |
Maximum of Months | 78265821.96 | 0.121786E+10 | 92472.45 | 10039137.59 | 3303330.02 | 0.128843E+10 | 0.836510E+09 | 5005.97 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 75598364.56 | 0.00 | 0.00 | 149745.05 | 0.00 | 0.140524E+10 | 39823233.29 | 0.00 | 0.35 |
February | 0.122895E+09 | 0.00 | 0.00 | 1272509.46 | 0.00 | 0.971565E+09 | 0.219235E+09 | 0.00 | 0.35 |
March | 0.225017E+09 | 7241465.14 | 34974.04 | 3324530.29 | 1662893.97 | 0.374803E+09 | 0.575858E+09 | 8769.29 | 0.35 |
April | 0.154040E+09 | 32280152.20 | 36470.89 | 7827699.18 | 11609181.10 | 76621466.05 | 0.612093E+09 | 1465.73 | 0.36 |
May | 96719805.71 | 0.206027E+09 | 18022.57 | 4628026.56 | 38316258.27 | 223223.68 | 0.214144E+09 | 1772.22 | 0.36 |
June | 28817207.13 | 0.658419E+09 | 60881.37 | 2986010.54 | 0.117931E+09 | 25461.37 | 0.109689E+09 | 768.01 | 0.36 |
July | 3840703.44 | 0.953238E+09 | 38094.58 | 85480.48 | 0.158116E+09 | 2624.65 | 105327.94 | 314.85 | 0.36 |
August | 427437.68 | 0.109597E+10 | 0.00 | 0.00 | 0.121740E+09 | 0.00 | 0.00 | 0.00 | 0.36 |
September | 60718656.50 | 0.466687E+09 | 139078.75 | 2465642.99 | 0.120620E+09 | 542760.73 | 0.123655E+09 | 3310.45 | 0.36 |
October | 0.159286E+09 | 0.120715E+09 | 215269.88 | 3460916.16 | 34837396.87 | 0.254549E+09 | 0.527389E+09 | 5828.10 | 0.36 |
November | 0.156999E+09 | 5132289.10 | 32704.44 | 1520102.63 | 5299858.48 | 0.688290E+09 | 0.390730E+09 | 1442.83 | 0.35 |
December | 0.112631E+09 | 373451.16 | 0.00 | 330874.02 | 181712.14 | 0.127466E+10 | 94358390.86 | 0.00 | 0.35 |
Annual Sum or Average | 0.119699E+10 | 0.354609E+10 | 575496.52 | 28051537.37 | 0.610314E+09 | 0.504653E+10 | 0.290708E+10 | 23671.48 | 0.35 |
Minimum of Months | 427437.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.225017E+09 | 0.109597E+10 | 215269.88 | 7827699.18 | 0.158116E+09 | 0.140524E+10 | 0.612093E+09 | 8769.29 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.203521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377735E+10 | 0.00 | 0.00 | 0.49 |
February | 0.193284E+11 | 0.00 | 0.00 | 0.00 | 1793251.53 | 0.177722E+10 | 0.00 | 0.00 | 0.49 |
March | 0.216517E+11 | 0.00 | 0.00 | 0.00 | 20205164.80 | 0.00 | 0.00 | 0.00 | 0.50 |
April | 0.152960E+11 | 0.00 | 0.00 | 0.00 | 0.301065E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
May | 0.868191E+10 | 0.00 | 0.00 | 0.00 | 0.180807E+10 | 0.00 | 0.00 | 0.00 | 0.50 |
June | 0.296365E+10 | 0.111915E+10 | 0.00 | 0.00 | 0.678439E+10 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.327758E+09 | 0.489986E+10 | 0.00 | 41936.06 | 0.837762E+10 | 0.00 | 21831444.59 | 0.00 | 0.48 |
August | 0.127959E+09 | 0.684589E+10 | 0.00 | 67658.64 | 0.875531E+10 | 0.00 | 27699780.14 | 0.00 | 0.48 |
September | 0.518542E+10 | 0.170483E+09 | 0.00 | 0.00 | 0.600215E+10 | 0.00 | 0.00 | 0.00 | 0.50 |
October | 0.185565E+11 | 0.00 | 0.00 | 0.00 | 0.154778E+10 | 0.00 | 0.00 | 0.00 | 0.50 |
November | 0.218130E+11 | 0.00 | 0.00 | 0.00 | 29588755.28 | 0.00 | 0.00 | 0.00 | 0.49 |
December | 0.246242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293381E+09 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 0.158909E+12 | 0.130354E+11 | 0.00 | 109594.70 | 0.336280E+11 | 0.584795E+10 | 49531224.73 | 0.00 | 0.49 |
Minimum of Months | 0.127959E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.246242E+11 | 0.684589E+10 | 0.00 | 67658.64 | 0.875531E+10 | 0.377735E+10 | 27699780.14 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17577011.52 | 0.00 | 0.00 | 172819.18 | 0.00 | 0.337135E+09 | 25363187.41 | 0.00 | 0.35 |
February | 18605356.32 | 0.00 | 0.00 | 575768.11 | 0.00 | 0.246459E+09 | 63139994.37 | 0.00 | 0.35 |
March | 17127540.22 | 2222501.18 | 700.21 | 1449857.96 | 13304.50 | 0.125409E+09 | 0.150799E+09 | 781.86 | 0.35 |
April | 5676149.96 | 10361869.15 | 15219.63 | 2227478.54 | 603500.00 | 34809465.92 | 0.169957E+09 | 2515.54 | 0.35 |
May | 434451.20 | 61023057.53 | 4112.55 | 1465093.99 | 69405.96 | 484033.80 | 76554361.31 | 1250.71 | 0.36 |
June | 0.00 | 0.194037E+09 | 82546.99 | 691111.24 | 0.00 | 61537.06 | 34630823.84 | 5794.94 | 0.36 |
July | 0.00 | 0.276948E+09 | 143802.49 | 46762.55 | 785007.43 | 18567.12 | 943322.63 | 4278.57 | 0.35 |
August | 0.00 | 0.304320E+09 | 138528.13 | 14608.91 | 0.00 | 2635.38 | 89627.65 | 5320.62 | 0.36 |
September | 363133.06 | 0.145486E+09 | 175644.71 | 700555.38 | 1209574.25 | 2850327.80 | 42937052.83 | 8257.82 | 0.36 |
October | 8220732.37 | 38089891.93 | 62944.95 | 1506722.80 | 792118.70 | 89266680.64 | 0.137205E+09 | 3016.57 | 0.36 |
November | 12123463.74 | 2310944.49 | 4237.64 | 848520.42 | 300483.26 | 0.180792E+09 | 0.115656E+09 | 1214.92 | 0.35 |
December | 19227377.69 | 95279.53 | 0.00 | 320683.80 | 43527.56 | 0.307830E+09 | 43160714.49 | 0.00 | 0.35 |
Annual Sum or Average | 99355216.09 | 0.103489E+10 | 627737.30 | 10019982.86 | 3816921.65 | 0.132512E+10 | 0.860436E+09 | 32431.55 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 14608.91 | 0.00 | 2635.38 | 89627.65 | 0.00 | 0.35 |
Maximum of Months | 19227377.69 | 0.304320E+09 | 175644.71 | 2227478.54 | 1209574.25 | 0.337135E+09 | 0.169957E+09 | 8257.82 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 11984548.32 | 0.00 | 0.00 | 31381.88 | 0.00 | 0.363884E+09 | 4304179.73 | 0.00 | 0.35 |
February | 26751867.21 | 0.00 | 0.00 | 184955.01 | 0.00 | 0.275125E+09 | 26679743.93 | 0.00 | 0.35 |
March | 56460540.50 | 1815287.09 | 4164.43 | 636239.44 | 415723.49 | 0.149019E+09 | 88635148.18 | 1850.60 | 0.35 |
April | 40706598.82 | 8066828.89 | 36587.36 | 1661272.12 | 2876025.38 | 35752588.12 | 0.134525E+09 | 2375.84 | 0.36 |
May | 24645478.46 | 51310007.87 | 43786.83 | 1008314.73 | 9732775.05 | 172727.96 | 53102170.41 | 4098.50 | 0.36 |
June | 7222542.62 | 0.163833E+09 | 40939.47 | 614767.07 | 30227816.09 | 34815.14 | 27507201.61 | 1406.93 | 0.36 |
July | 960175.86 | 0.236707E+09 | 63014.17 | 17422.10 | 41076913.53 | 3951.39 | 26984.77 | 855.21 | 0.36 |
August | 106859.42 | 0.273525E+09 | 65216.89 | 0.00 | 30836582.80 | 0.00 | 0.00 | 1421.54 | 0.36 |
September | 15191939.46 | 0.116122E+09 | 138778.47 | 473176.54 | 30595788.24 | 1506508.14 | 29673955.63 | 5495.73 | 0.36 |
October | 40995895.69 | 29809763.69 | 92670.30 | 607954.95 | 9036858.02 | 0.103420E+09 | 91147409.63 | 4116.82 | 0.36 |
November | 38063026.19 | 1282543.74 | 7409.46 | 286918.01 | 1324964.62 | 0.226178E+09 | 44856312.28 | 1655.88 | 0.35 |
December | 21499836.89 | 93362.79 | 0.00 | 67521.20 | 45428.03 | 0.338283E+09 | 10644794.94 | 0.00 | 0.35 |
Annual Sum or Average | 0.284589E+09 | 0.882565E+09 | 492567.39 | 5589923.06 | 0.156169E+09 | 0.149338E+10 | 0.511103E+09 | 23277.06 | 0.36 |
Minimum of Months | 106859.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 56460540.50 | 0.273525E+09 | 138778.47 | 1661272.12 | 41076913.53 | 0.363884E+09 | 0.134525E+09 | 5495.73 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 69503784.07 | 0.00 | 0.00 | 4876101.92 | 0.00 | 0.158462E+10 | 0.783902E+09 | 0.00 | 0.40 |
February | 84954912.86 | 0.00 | 0.00 | 7242484.94 | 0.00 | 0.103837E+10 | 0.981677E+09 | 0.00 | 0.40 |
March | 46268000.89 | 14287956.66 | 0.00 | 11895342.34 | 85474.60 | 0.308082E+09 | 0.152760E+10 | 0.00 | 0.40 |
April | 23883396.33 | 67092047.16 | 0.00 | 13298594.69 | 3468789.44 | 0.136879E+09 | 0.119224E+10 | 0.00 | 0.40 |
May | 14478.15 | 0.391996E+09 | 21022.62 | 8010049.69 | 503355.80 | 1202490.37 | 0.497909E+09 | 1784.42 | 0.40 |
June | 0.00 | 0.124710E+10 | 59821.55 | 3387278.56 | 0.00 | 247444.89 | 0.223686E+09 | 526.69 | 0.40 |
July | 0.00 | 0.178033E+10 | 392077.79 | 291773.12 | 4514822.88 | 119284.29 | 6069018.58 | 2667.30 | 0.40 |
August | 0.00 | 0.195530E+10 | 720153.06 | 94866.15 | 0.00 | 0.00 | 591731.49 | 5132.54 | 0.40 |
September | 2332944.46 | 0.935829E+09 | 23840.62 | 4912732.68 | 7770896.87 | 3845283.51 | 0.289903E+09 | 2136.96 | 0.40 |
October | 19351597.14 | 0.245118E+09 | 11946.94 | 13594780.80 | 5088958.12 | 0.196017E+09 | 0.128849E+10 | 1534.70 | 0.40 |
November | 31611717.86 | 15270858.39 | 4344.95 | 11916614.06 | 1536110.45 | 0.401979E+09 | 0.154236E+10 | 805.93 | 0.40 |
December | 55018303.32 | 891764.65 | 0.00 | 7130071.29 | 0.00 | 0.120970E+10 | 0.110867E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.332939E+09 | 0.665322E+10 | 1233207.53 | 86650690.24 | 22968408.16 | 0.488107E+10 | 0.944310E+10 | 14588.53 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 94866.15 | 0.00 | 0.00 | 591731.49 | 0.00 | 0.40 |
Maximum of Months | 84954912.86 | 0.195530E+10 | 720153.06 | 13594780.80 | 7770896.87 | 0.158462E+10 | 0.154236E+10 | 5132.54 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117260E+11 | 0.00 | 0.00 | 33832302.52 | 0.00 | 0.00 | 0.345743E+11 | 0.00 | 4.43 |
February | 0.704603E+10 | 3332183.44 | 0.00 | 39675619.33 | 0.00 | 0.00 | 0.346831E+11 | 0.00 | 4.57 |
March | 0.195159E+10 | 38811975.21 | 0.00 | 60276187.86 | 362858.02 | 0.00 | 0.433031E+11 | 0.00 | 4.85 |
April | 0.650967E+09 | 0.572992E+09 | 0.00 | 66588314.69 | 6057835.50 | 0.00 | 0.330026E+11 | 0.00 | 5.05 |
May | 0.125560E+09 | 0.370560E+10 | 0.00 | 61330839.95 | 26008221.22 | 0.00 | 0.202664E+11 | 0.00 | 5.28 |
June | 24771557.11 | 0.178795E+11 | 0.00 | 24987385.94 | 13328520.92 | 0.00 | 0.716631E+10 | 0.00 | 5.41 |
July | 0.00 | 0.302402E+11 | 0.00 | 5108404.77 | 11588508.24 | 0.00 | 0.879443E+09 | 0.00 | 5.34 |
August | 0.00 | 0.363089E+11 | 0.00 | 2690930.56 | 13401624.28 | 0.00 | 0.385910E+09 | 0.00 | 5.37 |
September | 99071569.00 | 0.134617E+11 | 0.00 | 35663511.22 | 65131781.70 | 0.00 | 0.119281E+11 | 0.00 | 5.23 |
October | 0.151188E+10 | 0.334262E+10 | 0.00 | 55689588.25 | 54794631.00 | 0.00 | 0.376490E+11 | 0.00 | 4.89 |
November | 0.315374E+10 | 51691620.18 | 0.00 | 49839318.82 | 3860481.78 | 0.00 | 0.410776E+11 | 0.00 | 4.69 |
December | 0.850426E+10 | 0.00 | 0.00 | 40876267.19 | 0.00 | 0.00 | 0.400738E+11 | 0.00 | 4.50 |
Annual Sum or Average | 0.347938E+11 | 0.105605E+12 | 0.00 | 0.476559E+09 | 0.194534E+09 | 0.00 | 0.304990E+12 | 0.00 | 4.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2690930.56 | 0.00 | 0.00 | 0.385910E+09 | 0.00 | 4.43 |
Maximum of Months | 0.117260E+11 | 0.363089E+11 | 0.00 | 66588314.69 | 65131781.70 | 0.00 | 0.433031E+11 | 0.00 | 5.41 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.658593E+10 | 0.00 | 0.00 | 45614470.47 | 0.00 | 0.00 | 0.431311E+11 | 0.00 | 4.76 |
February | 0.359651E+10 | 3498005.64 | 0.00 | 51742430.43 | 0.00 | 0.00 | 0.415067E+11 | 0.00 | 4.93 |
March | 0.854402E+09 | 42690441.70 | 0.00 | 74853024.53 | 0.00 | 0.00 | 0.481729E+11 | 0.00 | 5.24 |
April | 0.325182E+09 | 0.622649E+09 | 0.00 | 77647245.14 | 0.00 | 0.00 | 0.359813E+11 | 0.00 | 5.45 |
May | 26111560.80 | 0.399918E+10 | 0.00 | 68384514.52 | 13510.71 | 0.00 | 0.218009E+11 | 0.00 | 5.67 |
June | 1806428.58 | 0.190281E+11 | 0.00 | 27338996.41 | 0.00 | 0.00 | 0.763979E+10 | 0.00 | 5.75 |
July | 0.00 | 0.321583E+11 | 0.00 | 5458594.36 | 0.00 | 0.00 | 0.930426E+09 | 0.00 | 5.66 |
August | 0.00 | 0.384906E+11 | 0.00 | 2927591.14 | 0.00 | 0.00 | 0.406673E+09 | 0.00 | 5.68 |
September | 36858605.56 | 0.144329E+11 | 0.00 | 39850782.01 | 3656687.41 | 0.00 | 0.128305E+11 | 0.00 | 5.59 |
October | 0.630586E+09 | 0.364051E+10 | 0.00 | 67213648.31 | 5004953.79 | 0.00 | 0.417128E+11 | 0.00 | 5.27 |
November | 0.122646E+10 | 58594999.51 | 0.00 | 63847084.43 | 420400.89 | 0.00 | 0.467351E+11 | 0.00 | 5.07 |
December | 0.305614E+10 | 0.00 | 0.00 | 54172988.70 | 0.00 | 0.00 | 0.494793E+11 | 0.00 | 4.86 |
Annual Sum or Average | 0.163400E+11 | 0.112477E+12 | 0.00 | 0.579051E+09 | 9095552.81 | 0.00 | 0.350328E+12 | 0.00 | 5.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2927591.14 | 0.00 | 0.00 | 0.406673E+09 | 0.00 | 4.76 |
Maximum of Months | 0.658593E+10 | 0.384906E+11 | 0.00 | 77647245.14 | 5004953.79 | 0.00 | 0.494793E+11 | 0.00 | 5.75 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 29386786.70 | 0.00 | 0.00 | 0.103455E+09 | 0.00 | 0.00 | 0.639701E+11 | 0.00 | 19.98 |
February | 44733025.47 | 6003624.92 | 0.00 | 97910416.41 | 0.00 | 0.00 | 0.559995E+11 | 0.00 | 20.50 |
March | 0.00 | 67921661.93 | 0.00 | 0.114109E+09 | 0.00 | 0.00 | 0.581796E+11 | 0.00 | 21.33 |
April | 0.00 | 0.100515E+10 | 0.00 | 0.106051E+09 | 0.00 | 0.00 | 0.396118E+11 | 0.00 | 21.74 |
May | 0.00 | 0.598097E+10 | 0.00 | 79400746.22 | 0.00 | 0.00 | 0.211979E+11 | 0.00 | 22.01 |
June | 0.00 | 0.246406E+11 | 0.00 | 30888619.80 | 0.00 | 0.00 | 0.718599E+10 | 0.00 | 21.81 |
July | 0.00 | 0.405528E+11 | 0.00 | 4805058.83 | 0.00 | 0.00 | 0.768608E+09 | 0.00 | 21.41 |
August | 0.00 | 0.468306E+11 | 0.00 | 3089934.99 | 0.00 | 0.00 | 0.373177E+09 | 0.00 | 21.46 |
September | 0.00 | 0.190714E+11 | 0.00 | 50410247.52 | 0.00 | 0.00 | 0.131797E+11 | 0.00 | 21.77 |
October | 0.00 | 0.474224E+10 | 0.00 | 98643847.67 | 0.00 | 0.00 | 0.489895E+11 | 0.00 | 21.36 |
November | 0.00 | 96929955.88 | 0.00 | 0.105004E+09 | 0.00 | 0.00 | 0.584334E+11 | 0.00 | 20.97 |
December | 8449729.21 | 0.00 | 0.00 | 0.104716E+09 | 0.00 | 0.00 | 0.673817E+11 | 0.00 | 20.34 |
Annual Sum or Average | 82569541.38 | 0.142995E+12 | 0.00 | 0.898483E+09 | 0.00 | 0.00 | 0.435271E+12 | 0.00 | 21.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3089934.99 | 0.00 | 0.00 | 0.373177E+09 | 0.00 | 19.98 |
Maximum of Months | 44733025.47 | 0.468306E+11 | 0.00 | 0.114109E+09 | 0.00 | 0.00 | 0.673817E+11 | 0.00 | 22.01 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.988782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394526E+10 | 0.00 | 0.00 | 1.06 |
February | 0.102331E+11 | 0.00 | 0.00 | 0.00 | 1028048.73 | 0.186648E+10 | 0.00 | 0.00 | 1.06 |
March | 0.124126E+11 | 0.00 | 0.00 | 0.00 | 11583368.85 | 0.00 | 0.00 | 0.00 | 1.07 |
April | 0.876790E+10 | 6809917.38 | 0.00 | 7560.59 | 0.165787E+09 | 0.00 | 1115304.54 | 0.00 | 1.08 |
May | 0.490891E+10 | 0.276402E+09 | 0.00 | 81600.79 | 0.760158E+09 | 0.00 | 68235787.64 | 0.00 | 1.08 |
June | 0.157242E+10 | 0.340566E+10 | 0.00 | 266356.07 | 0.120296E+10 | 0.00 | 0.126337E+09 | 0.00 | 1.08 |
July | 0.169130E+09 | 0.588357E+10 | 0.00 | 88318.70 | 0.212241E+10 | 0.00 | 31220871.46 | 0.00 | 1.09 |
August | 69326536.58 | 0.757634E+10 | 0.00 | 67698.36 | 0.181083E+10 | 0.00 | 19882512.10 | 0.00 | 1.09 |
September | 0.296154E+10 | 0.114171E+10 | 0.00 | 34821.84 | 0.241253E+10 | 0.00 | 11161857.28 | 0.00 | 1.07 |
October | 0.106355E+11 | 10786121.39 | 0.00 | 1321.99 | 0.876538E+09 | 0.00 | 2723701.22 | 0.00 | 1.07 |
November | 0.122869E+11 | 0.00 | 0.00 | 0.00 | 16962864.18 | 0.218235E+09 | 0.00 | 0.00 | 1.07 |
December | 0.135196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765320E+09 | 0.00 | 0.00 | 1.06 |
Annual Sum or Average | 0.874248E+11 | 0.183013E+11 | 0.00 | 547678.34 | 0.938080E+10 | 0.679530E+10 | 0.260677E+09 | 0.00 | 1.07 |
Minimum of Months | 69326536.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 |
Maximum of Months | 0.135196E+11 | 0.757634E+10 | 0.00 | 266356.07 | 0.241253E+10 | 0.394526E+10 | 0.126337E+09 | 0.00 | 1.09 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:02:03
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.182557E+12 | 0.457710E+10 | 0.213173E+12 | 0.904371E+12 | 0.804661E+11 |
February | 0.189297E+12 | 0.348448E+10 | 0.153511E+12 | 0.661630E+12 | 0.114757E+12 |
March | 0.278625E+12 | 0.284156E+10 | 0.110887E+12 | 0.483362E+12 | 0.243514E+12 |
April | 0.313891E+12 | 0.172315E+10 | 0.672418E+11 | 0.318103E+12 | 0.406994E+12 |
May | 0.344859E+12 | 0.473670E+09 | 0.156230E+11 | 0.949620E+11 | 0.706882E+12 |
June | 0.351063E+12 | -0.136794E+10 | -0.627481E+11 | -0.245617E+12 | 0.108431E+13 |
July | 0.326309E+12 | -0.267723E+10 | -0.116725E+12 | -0.491224E+12 | 0.136581E+13 |
August | 0.301056E+12 | -0.314911E+10 | -0.136059E+12 | -0.607751E+12 | 0.145813E+13 |
September | 0.226481E+12 | -703273129.8 | -0.308360E+11 | -0.114529E+12 | 0.929193E+12 |
October | 0.216816E+12 | 0.171071E+10 | 0.713027E+11 | 0.330926E+12 | 0.430946E+12 |
November | 0.151225E+12 | 0.278372E+10 | 0.120766E+12 | 0.550226E+12 | 0.194718E+12 |
December | 0.145157E+12 | 0.371748E+10 | 0.171991E+12 | 0.753389E+12 | 0.100593E+12 |
Annual Sum or Average | 0.302734E+13 | 0.134143E+11 | 0.578128E+12 | 0.263785E+13 | 0.711631E+13 |
Minimum of Months | 0.145157E+12 | -0.314911E+10 | -0.136059E+12 | -0.607751E+12 | 0.804661E+11 |
Maximum of Months | 0.351063E+12 | 0.457710E+10 | 0.213173E+12 | 0.904371E+12 | 0.145813E+13 |