Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2023-10-16 09:02:48
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10949.69 | 965.13 | 965.13 |
Net Site Energy | 10949.69 | 965.13 | 965.13 |
Total Source Energy | 29703.96 | 2618.18 | 2618.18 |
Net Source Energy | 29703.96 | 2618.18 | 2618.18 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3794.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 604.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 174.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 641.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 645.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 189.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 294.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 444.97 | 597.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 44.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 8561.93 | 2387.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 3794.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 604.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 174.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 952.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 22.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 645.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 189.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 294.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.74 | 597.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Other | 354.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 21.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3794.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 604.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 174.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 641.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 645.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 189.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 294.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 444.97 | 597.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 44.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 447.31 | 52.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 238.72 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 754.67 | 210.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 447.31 | 52.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 238.72 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 754.67 | 210.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 8561.930 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 8561.930 | 100.00 |
Total On-Site and Utility Electric Sources | 8561.930 | 100.00 |
Total Electricity End Uses | 8561.930 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 3413.10 | 98.72 |
Air to Air Heat Recovery for Heating | 44.25 | 1.28 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 3457.34 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 46.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8359.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYSLAUNDRY HPWH TANK | SWHSYS1 HPWH TANK |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| SWHSYS1 HPWH FAN | SWHSYSLAUNDRY HPWH FAN | FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 6.6442 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 9.6995 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 9.6995 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 4.0903 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.7049 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 9.2569 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 9.0417 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 4.4132 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.4132 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.7327 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 4.4132 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8432 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8432 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.6442 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 4.0903 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.7049 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 9.2569 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 9.0417 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 4.4132 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.4132 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.7327 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 4.4132 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.8432 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.8432 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.6992 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-AUG-19:40 | 12-JAN-18:40 | - | - | - | - | - | - | - | - | - | - | 23-FEB-21:19 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 279993.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 50471.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 87982.85 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31577.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38282.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 8353.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 35909.97 | 49006.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1681.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 555288.18 | 153255.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 279993.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 50471.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58308.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1274.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 38282.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 8353.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4038.26 | 49006.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 771.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12018.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1913.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 553.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5473.02 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2031.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2043.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 600.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 931.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1409.21 | 647.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 140.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 27115.63 | 2588.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1059.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 180.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 52.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 82.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 124.21 | 57.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2390.03 | 228.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1059.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 180.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 52.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 82.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 124.21 | 57.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2390.03 | 228.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.52 | 0.598216 | 0.525000 | 1.32 | 1.00 | 0.500000 | 0.000637 | 0.000061 | 1.32 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.360082 | 0.141935 | 0.525000 | 0.189043 | 0.525000 | 0.500000 | 0.002684 | 0.000017 | 0.189043 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.238091 | 0.248576 | 0.525000 | 0.124998 | 0.662869 | 0.500000 | 0.001533 | 0.000008 | 0.124998 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.233919 | 0.535029 | 0.525000 | 0.122807 | 1.00 | 0.500000 | 0.000712 | 0.000010 | 0.122807 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.127224 | 0.567554 | 0.525000 | 0.066793 | 1.00 | 0.500000 | 0.000671 | 0.000006 | 0.066793 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.29 | 0.071688 | 0.525000 | 1.73 | 0.525000 | 0.500000 | 0.021090 | 0.000086 | 1.73 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.49 | 0.096763 | 0.525000 | 0.780813 | 0.525000 | 0.500000 | 0.003937 | 0.000058 | 0.780813 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.84 | 0.205927 | 0.525000 | 2.54 | 0.549140 | 0.500000 | 0.001850 | 0.000163 | 2.54 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.39 | 0.854289 | 0.525000 | 0.729409 | 1.00 | 0.500000 | 0.000446 | 0.000067 | 0.729409 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.29 | 0.110586 | 0.525000 | 1.20 | 0.525000 | 0.500000 | 0.003445 | 0.000078 | 1.20 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.39 | 0.105692 | 0.525000 | 1.26 | 0.525000 | 0.500000 | 0.003605 | 0.000081 | 1.26 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.22 | 0.063840 | 0.525000 | 1.16 | 0.525000 | 0.500000 | 0.010734 | 0.000054 | 1.16 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.823440 | 0.381374 | 0.525000 | 0.432306 | 1.00 | 0.500000 | 0.000999 | 0.000044 | 0.432306 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 6983.78 | 0.000061 | 145.63 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 1979.19 | 0.000017 | 43.50 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 947.00 | 0.000008 | 20.21 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1146.03 | 0.000010 | 24.89 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 661.80 | 0.000006 | 14.46 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 9865.94 | 0.000086 | 206.61 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 6616.13 | 0.000058 | 142.45 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 18619.51 | 0.000163 | 396.27 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 2251.34 | 0.000020 | 64.32 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 2249.38 | 0.000020 | 64.26 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 19405.67 | 0.000170 | 554.38 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 19410.98 | 0.000170 | 554.53 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 2254.96 | 0.000020 | 64.42 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 2252.99 | 0.000020 | 64.36 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 7602.98 | 0.000067 | 167.02 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 708.94 | 0.000006 | 20.25 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 708.63 | 0.000006 | 20.24 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 3454.35 | 0.000030 | 98.68 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 8926.15 | 0.000078 | 190.19 |
DINING_FLR_6 VAV BOX REHEAT COIL | 9207.09 | 0.000081 | 195.96 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6144.83 | 0.000054 | 128.14 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 5086.26 | 0.000044 | 113.33 |
VAV WITH REHEAT HEATING COIL | 32082.98 | 0.000281 | 614.41 |
FLR_3_DOAS HEATING COIL | 2977.14 | 0.000026 | 57.01 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.08 | 0.000020 | 0.000430 |
ROOM_2_FLR_3 FAN COIL | 1.06 | 0.000020 | 0.000422 |
ROOM_3_MULT19_FLR_3 FAN COIL | 6.47 | 0.000170 | 0.002529 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.83 | 0.000170 | 0.002823 |
ROOM_5_FLR_3 FAN COIL | 0.968796 | 0.000020 | 0.000387 |
ROOM_6_FLR_3 FAN COIL | 0.950413 | 0.000020 | 0.000380 |
ROOM_1_FLR_6 FAN COIL | 0.291853 | 0.000006 | 0.000116 |
ROOM_2_FLR_6 FAN COIL | 0.286397 | 0.000006 | 0.000114 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.38 | 0.000030 | 0.000559 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.08 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.06 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.47 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.83 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 0.968796 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.950413 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.291853 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.286397 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.38 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008579 | 12.80 | 0.008500 | 0.000430 | 1.08 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008581 | 12.80 | 0.008500 | 0.000422 | 1.06 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008510 | 12.80 | 0.008500 | 0.002529 | 6.47 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008715 | 12.80 | 0.008500 | 0.002823 | 6.83 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008588 | 12.80 | 0.008500 | 0.000387 | 0.968796 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008590 | 12.80 | 0.008500 | 0.000380 | 0.950413 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008573 | 12.80 | 0.008500 | 0.000116 | 0.291853 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008574 | 12.80 | 0.008500 | 0.000114 | 0.286397 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008630 | 12.80 | 0.008500 | 0.000559 | 1.38 | |
VAV WITH REHEAT COOLING COIL | 33.91 | 6.70 | 0.010239 | 10.98 | 0.008500 | 0.026478 | 22.11 | 741326.08 |
FLR_3_DOAS COOLING COIL | 42.80 | 6.70 | 0.010782 | 11.93 | 0.008500 | 0.003297 | 2.05 | 92321.21 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.66 | 11.66 | 22.21 | 11.66 | 22.11 | 22.11 | 0.300000 | 0.527392 | 22.11 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 22.11 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 22.11 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.026478 | 0.000018 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.000281 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.003297 | 0.000144 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000026 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Size Rated Evaporator Air Flow Rate [m3/s] | Design Size Rated Condenser Water Flow Rate [m3/s] | |
SWHSYSLAUNDRY HPWH DXCOIL | 4.90 | 0.004370 |
SWHSYS1 HPWH DXCOIL | 3.87 | 0.003451 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
SWHSYSLAUNDRY HPWH FAN | 4.90 | 700.51 |
SWHSYS1 HPWH FAN | 3.87 | 553.22 |
Condenser water flow rate [m3/s] | Evaporator air flow rate [m3/s] | |
SWHSYS1 HPWH | 0.003451 | 3.87 |
SWHSYSLAUNDRY HPWH | 0.004370 | 4.90 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.037536 | 7658.13 | |
HEATSYS1 PUMP | 0.001501 | 447.48 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.001501 | 0.180089 |
COOLSYS1 | 0.037536 | 4.50 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 171544.07 | 171544.07 | 0.001501 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.037536 | 5301.98 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.037536 | 1050898.32 | 1051512.08 | 119.87 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 HPWH TANK | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 6.644 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.024 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 4.090 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.780 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.705 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.235 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 9.257 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.637 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 9.042 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.112 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.733 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2943.236 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 13147.704 | 6.644 | 123.454 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13147.704 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 650.557 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 650.557 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 753.347 | 9.699 | 60.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 753.347 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 387.592 | 4.090 | 189.996 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 387.592 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 445.205 | 5.705 | 53.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 445.205 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1748.285 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1748.285 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 11828.200 | 9.042 | 28.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11828.200 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 108.229 | 4.413 | 72.152 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.229 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1718.521 | 4.413 | 82.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1718.521 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1212.035 | 11.733 | 54.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1212.035 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1818.789 | 4.413 | 82.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1818.789 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 1.287 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.608 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.684 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.608 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.684 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.4124 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.4124 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6100 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4545 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4264 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4545 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4264 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.165 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.165 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
21 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
22 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
23 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | 0.16691074E-14 | 0.45207920E-16 | -0.13282787E-09 | -0.59403108E-17 |
29 | 8 | 0.19494068E-07 | 0.16957001E-12 | 0.35230437E-03 | -0.22165426E-09 |
30 | 7 | -0.11479370E-01 | 0.90467759E-08 | -0.21987867E-01 | 0.13052461E-03 |
31 | 6 | 0.38463807 | 0.31869432E-05 | 0.45441076 | -0.45036152E-02 |
32 | 5 | -4.9884079 | 0.12028467E-03 | -4.3052891 | 0.60677235E-01 |
33 | 4 | 32.108494 | 0.99355415E-03 | 20.908458 | -0.41024850 |
34 | 3 | -109.32288 | 0.21841230E-02 | -54.572312 | 1.4876971 |
35 | 2 | 195.24423 | 0.12380226E-02 | 76.910992 | -2.8707534 |
36 | 1 | -170.46733 | 0.13310261E-03 | -54.975783 | 2.7333683 |
37 | 0 | 57.057407 | 0.76355891E-06 | 15.605832 | |
38 | 9 | 0.14115123E-14 | 0.53960859E-16 | -0.11739578E-09 | -0.22900007E-17 |
39 | 8 | 0.17311930E-07 | 0.20639465E-12 | 0.32798840E-03 | -0.19684260E-09 |
40 | 7 | -0.10748946E-01 | 0.11327704E-07 | -0.20934514E-01 | 0.12221941E-03 |
41 | 6 | 0.36478417 | 0.40360747E-05 | 0.43737925 | -0.42695883E-02 |
42 | 5 | -4.7945715 | 0.15382307E-03 | -4.1739388 | 0.58273831E-01 |
43 | 4 | 31.250576 | 0.12816568E-02 | 20.393829 | -0.39885853 |
44 | 3 | -107.49604 | 0.28390629E-02 | -53.554356 | 1.4613070 |
45 | 2 | 193.43186 | 0.16201491E-02 | 75.979619 | -2.8419759 |
46 | 1 | -169.79719 | 0.17527083E-03 | -54.709122 | 2.7216233 |
47 | 0 | 57.057407 | 0.10123612E-05 | 15.653272 | |
48 | 9 | 0.65135446E-15 | 0.56204292E-16 | -0.11372497E-09 | -0.53489081E-17 |
49 | 8 | 0.16791160E-07 | 0.21454591E-12 | 0.32203280E-03 | -0.19092129E-09 |
50 | 7 | -0.10569524E-01 | 0.11862766E-07 | -0.20675571E-01 | 0.12017931E-03 |
51 | 6 | 0.35990649 | 0.42391557E-05 | 0.43318136 | -0.42120931E-02 |
52 | 5 | -4.7469406 | 0.16196889E-03 | -4.1415055 | 0.57683257E-01 |
53 | 4 | 31.039704 | 0.13525358E-02 | 20.266625 | -0.39605902 |
54 | 3 | -107.04684 | 0.30019179E-02 | -53.302690 | 1.4548183 |
55 | 2 | 192.98603 | 0.17160237E-02 | 75.749609 | -2.8348971 |
56 | 1 | -169.63227 | 0.18593554E-03 | -54.643729 | 2.7187328 |
57 | 0 | 57.057407 | 0.10758168E-05 | 15.665287 | |
58 | 9 | 0.14115123E-14 | 0.53960859E-16 | -0.11739578E-09 | -0.22900007E-17 |
59 | 8 | 0.17311930E-07 | 0.20639465E-12 | 0.32798840E-03 | -0.19684260E-09 |
60 | 7 | -0.10748946E-01 | 0.11327704E-07 | -0.20934514E-01 | 0.12221941E-03 |
61 | 6 | 0.36478417 | 0.40360747E-05 | 0.43737925 | -0.42695883E-02 |
62 | 5 | -4.7945715 | 0.15382307E-03 | -4.1739388 | 0.58273831E-01 |
63 | 4 | 31.250576 | 0.12816568E-02 | 20.393829 | -0.39885853 |
64 | 3 | -107.49604 | 0.28390629E-02 | -53.554356 | 1.4613070 |
65 | 2 | 193.43186 | 0.16201491E-02 | 75.979619 | -2.8419759 |
66 | 1 | -169.79719 | 0.17527083E-03 | -54.709122 | 2.7216233 |
67 | 0 | 57.057407 | 0.10123612E-05 | 15.653272 | |
68 | 9 | 0.65135446E-15 | 0.56204292E-16 | -0.11372497E-09 | -0.53489081E-17 |
69 | 8 | 0.16791160E-07 | 0.21454591E-12 | 0.32203280E-03 | -0.19092129E-09 |
70 | 7 | -0.10569524E-01 | 0.11862766E-07 | -0.20675571E-01 | 0.12017931E-03 |
71 | 6 | 0.35990649 | 0.42391557E-05 | 0.43318136 | -0.42120931E-02 |
72 | 5 | -4.7469406 | 0.16196889E-03 | -4.1415055 | 0.57683257E-01 |
73 | 4 | 31.039704 | 0.13525358E-02 | 20.266625 | -0.39605902 |
74 | 3 | -107.04684 | 0.30019179E-02 | -53.302690 | 1.4548183 |
75 | 2 | 192.98603 | 0.17160237E-02 | 75.749609 | -2.8348971 |
76 | 1 | -169.63227 | 0.18593554E-03 | -54.643729 | 2.7187328 |
77 | 0 | 57.057407 | 0.10758168E-05 | 15.665287 | |
78 | 7 | -0.10696287E-14 | 0.39031946E-16 | -0.22096194E-13 | 0.53014468E-15 |
79 | 6 | 0.18597363E-10 | 0.52355087E-11 | 0.51921923E-09 | -0.18483703E-10 |
80 | 5 | -0.10208356E-06 | 0.25520809E-07 | -0.21786771E-05 | 0.17041956E-06 |
81 | 4 | 0.13587196E-03 | 0.96408156E-05 | 0.17589348E-02 | -0.28090751E-03 |
82 | 3 | -0.20124247E-01 | 0.34048350E-03 | -0.21477792 | 0.43172268E-01 |
83 | 2 | 0.28586126 | 0.14813331E-02 | 2.8938873 | -0.61762740 |
84 | 1 | -0.72340799 | 0.92453067E-03 | -7.1302655 | 1.5680075 |
85 | 0 | 0.46030979 | 0.18706506E-04 | 4.4521723 | |
86 | 7 | -0.22096194E-13 | 0.39031946E-16 | -0.10696287E-14 | 0.53014468E-15 |
87 | 6 | 0.51921923E-09 | 0.52355087E-11 | 0.18597363E-10 | -0.18483703E-10 |
88 | 5 | -0.21786771E-05 | 0.25520809E-07 | -0.10208356E-06 | 0.17041956E-06 |
89 | 4 | 0.17589348E-02 | 0.96408156E-05 | 0.13587196E-03 | -0.28090751E-03 |
90 | 3 | -0.21477792 | 0.34048350E-03 | -0.20124247E-01 | 0.43172268E-01 |
91 | 2 | 2.8938873 | 0.14813331E-02 | 0.28586126 | -0.61762740 |
92 | 1 | -7.1302655 | 0.92453067E-03 | -0.72340799 | 1.5680075 |
93 | 0 | 4.4521723 | 0.18706506E-04 | 0.46030979 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5095_SHGC_0.23 | 37 | 1 | VerySmooth | 2.897 | 2.897 | 1.000 | 0.231 | ||
2 | RESWINDOW_U_0.5095_SHGC_0.23 | 38 | 1 | VerySmooth | 2.897 | 2.897 | 1.000 | 0.231 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 1.83516E-002 | 0.14129 | 0.62979 | 0.62979 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10484 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 1.83516E-002 | 0.14129 | 0.62979 | 0.62979 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10484 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | "DX Coil Total Cooling Rate {W | HPWH Only}" | |
1 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | 1.1400 | 77713.0 | 48.891 | 1.7319 | 76621 | |
2 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | 2.8400 | 63057.6 | 4.646 | 9.4742 | 53264 |
Node Number | Height {m} | Volume {m3} | Maximum Capacity {W} | Off-Cycle UA {W/K} | On-Cycle UA {W/K} | Number Of Inlets | Number Of Outlets | |
1 | 1 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 0 | 1 |
2 | 2 | 0.2683 | 0.4733 | 18438.260 | 1.5573 | 1.5573 | 0 | 0 |
3 | 3 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
4 | 4 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
5 | 5 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 1 |
6 | 6 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 2 | 0 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 9.802E-003 | 1.461E-004 | 7.212E-005 | 0.133 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 3.784E-003 | 4.872E-005 | 1.327E-004 | 4.426E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 8.942E-003 | 5.445E-005 | 1.424E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 5.159E-003 | 5.445E-005 | 1.182E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 1.221E-002 | 1.565E-004 | 1.392E-004 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 2.167E-002 | 1.147E-004 | 6.318E-005 | 0.104 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 6.191E-002 | 4.733E-005 | 9.051E-005 | 4.300E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.587E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.588E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 6.879E-003 | 1.766E-005 | 1.424E-004 | 2.086E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 2.910E-003 | 1.186E-004 | 6.472E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1.243E-002 | 1.204E-004 | 6.523E-005 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1.217E-002 | 2.953E-005 | 2.446E-005 | 3.488E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 6.7472E-002 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.6429E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 7.2834E-002 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.7218E-002 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 5.5179E-002 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.9089E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.4391E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.0788E-003 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.5228E-002 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.3192E-002 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 8.1205E-002 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.4327E-002 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 6.1025E-002 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.4571E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 2.7408E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.1075E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.8159E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0168E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.4163E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 7.7663E-003 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.3193E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 5.2587E-003 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.4020E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 8.4927E-003 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.8159E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0168E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.4163E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 7.7663E-003 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.3193E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 5.2587E-003 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.4020E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 8.4927E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 34675.30920 | 34675.30920 | 2.52061 | 2.52061 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 20:40:00 | 37.36800 | 1.07725E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | 00:10:00 | 12.70000 | 9.15345E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 4953.06179 | 4953.06179 | 0.36008 | 0.36008 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 981.38593 | 981.38593 | 4.20853E-002 | 7.92179E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | 12.70000 | 9.15345E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3274.98234 | 3274.98234 | 0.23809 | 0.23809 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 40.95700 | 1.07786E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 287.21999 | 287.21999 | 1.23170E-002 | 9.17347E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | 12.70000 | 9.15345E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3218.28066 | 3218.28066 | 0.23392 | 0.23392 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:20:00 | 38.66133 | 1.07747E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 497.78292 | 497.78292 | 2.13466E-002 | 2.13466E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | 12.70000 | 9.15345E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1750.34882 | 1750.34882 | 0.12722 | 0.12722 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 309.23778 | 309.23778 | 1.32612E-002 | 5.77652E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | 12.70000 | 9.15345E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 45282.90496 | 45282.90496 | 3.29167 | 3.29167 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 41.28033 | 1.07792E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 743.93367 | 743.93367 | 3.19025E-002 | 3.19025E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | 12.70000 | 9.15345E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 20441.09416 | 20441.09416 | 1.48726 | 1.48726 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 2494.92607 | 2494.92607 | 0.10699 | 0.67639 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | 12.70000 | 9.15345E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 66566.79937 | 66566.79937 | 4.84072 | 4.84072 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 42.80000 | 1.07818E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 5205.51092 | 5205.51092 | 0.22323 | 1.89399 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | 12.70000 | 9.15345E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11020.31821 | 11020.31821 | 1.07947 | 1.07947 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 42.08867 | 1.07806E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 2251.34037 | 2251.34037 | 9.71127E-002 | 9.71127E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 12.70000 | 9.15345E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10810.40712 | 10810.40712 | 1.05891 | 1.05891 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 2249.37597 | 2249.37597 | 9.70280E-002 | 9.70280E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 12.70000 | 9.15345E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 66063.16699 | 66063.16699 | 6.47074 | 6.47074 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 42.80000 | 1.07818E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 13425.98961 | 13425.98961 | 0.57914 | 0.83707 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 12.70000 | 9.15345E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 69742.29552 | 69742.29552 | 6.83163 | 6.83163 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 42.50900 | 1.07813E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 13402.06831 | 13402.06831 | 0.57810 | 0.83730 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 12.70000 | 9.15345E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 9890.44893 | 9890.44893 | 0.96880 | 0.96880 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 40.08400 | 1.07771E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 2254.95633 | 2254.95633 | 9.72687E-002 | 9.72687E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 12.70000 | 9.15345E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9702.77952 | 9702.77952 | 0.95041 | 0.95041 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 39.84150 | 1.07767E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 2252.98930 | 2252.98930 | 9.71839E-002 | 9.71839E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 12.70000 | 9.15345E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 19113.30184 | 19113.30184 | 1.38935 | 1.38935 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 42.60600 | 1.07815E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 3753.20818 | 3753.20818 | 0.16095 | 0.47476 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12.70000 | 9.15345E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2979.53332 | 2979.53332 | 0.29185 | 0.29185 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 42.08867 | 1.07806E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 708.94180 | 708.94180 | 3.05806E-002 | 3.05806E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 12.70000 | 9.15345E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2923.83754 | 2923.83754 | 0.28640 | 0.28640 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 42.08867 | 1.07806E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 708.63033 | 708.63033 | 3.05671E-002 | 3.05671E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 12.70000 | 9.15345E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 14130.12741 | 14130.12741 | 1.38412 | 1.38412 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 42.80000 | 1.07818E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 3454.35174 | 3454.35174 | 0.14901 | 0.14901 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 12.70000 | 9.15345E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 31400.94246 | 31400.94246 | 2.28531 | 2.28531 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 42.80000 | 1.07818E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 2593.85270 | 2593.85270 | 0.11123 | 1.18780 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 20:20:00 | 12.70000 | 9.15345E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 32855.25507 | 32855.25507 | 2.39112 | 2.39112 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 42.80000 | 1.07818E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 2581.62423 | 2581.62423 | 0.11071 | 1.18780 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | 12.70000 | 9.15345E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30431.32360 | 30431.32360 | 2.21781 | 2.21781 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 41.92700 | 1.07803E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.36735 | 00:10:00 | 12.70000 | 9.15345E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 | |
43 | CORRIDOR_FLR_6 | Cooling | 11328.18977 | 11328.18977 | 0.82344 | 0.82344 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 42.80000 | 1.07818E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 2804.64846 | 2804.64846 | 0.12027 | 0.12562 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 12.70000 | 9.15345E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 564456.75 | 22.10590 | 22.10590 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 34106.90 | 7.05013 | 7.05013 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 74425.91 | 19.06562 | 2.05125 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 9923.45 | 2.27312 | 2.05125 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.52061 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.59822 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52500 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.32332 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.36893E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.10972E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.32332 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6983.78206 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.10972E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 145.63474 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.36008 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14194 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52500 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18904 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52500 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.68432E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.73148E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.18904 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1979.18913 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.73148E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 43.49985 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.23809 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24858 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52500 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12500 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66287 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.53273E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.28474E-006 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12500 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 946.99694 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.28474E-006 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 20.20519 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.23392 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.53503 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52500 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12281 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.12111E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00260E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12281 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1146.03088 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00260E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 24.89430 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.12722 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.56755 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52500 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.67926E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.71302E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.78974E-006 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.67926E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 661.80316 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.78974E-006 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 14.46200 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.29167 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.16881E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52500 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.72813 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52500 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.10898E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.63116E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.72813 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9865.94464 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.63116E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 206.61300 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.48726 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.67634E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52500 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78081 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52500 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.93744E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.78808E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.78081 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6616.12892 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.78808E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 142.45473 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.84072 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20593 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52500 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.54138 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54914 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.85017E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.62892E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.54138 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18619.50990 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.62892E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 396.26839 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.07947 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.07947 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.96957E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.30056E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68328 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57901E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.30056E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.07947 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2251.34251 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.96957E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 64.31614 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.05891 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.05891 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.96785E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.22056E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68328 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58067E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.22056E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.05891 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2249.37811 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.96785E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 64.26001 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.47074 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.47074 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.69769E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.52902E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68375 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50966E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.52902E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.47074 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 19405.67168 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69769E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 554.38139 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.83163 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.83163 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.69816E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.82273E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68291 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.71454E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.82273E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.83163 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 19410.97812 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69816E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 554.53295 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.96880 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.96880 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.97274E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.86941E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68326 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58825E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.86941E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.96880 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2254.95848 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.97274E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 64.41944 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.95041 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.95041 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.97102E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.79777E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68326 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58996E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.79777E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.95041 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2252.99144 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.97102E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 64.36324 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.38935 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.85429 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52500 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.72941 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.45985E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.65142E-005 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.72941 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7602.98493 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.65142E-005 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 167.02263 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.29185 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.29185 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.20214E-006 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.16086E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68329 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57313E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.16086E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.29185 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 708.94245 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.20214E-006 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 20.25315 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.28640 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.28640 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.19941E-006 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.13957E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68329 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57444E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.13957E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.28640 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 708.63097 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.19941E-006 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 20.24425 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.38412 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.38412 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.02202E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.59081E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68303 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62974E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.59081E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.38412 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3454.35426 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.02202E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 98.68454 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.28531 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11059 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52500 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.19979 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52500 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.44529E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.80899E-005 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.19979 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8926.15077 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.80899E-005 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 190.18705 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.39112 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10569 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52500 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.25534 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52500 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.60480E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.05476E-005 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.25534 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9207.08639 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.05476E-005 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 195.96458 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.21781 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.38396E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52500 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.16435 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52500 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07343E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.37577E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.16435 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6144.83195 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.37577E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 128.13988 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82344 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38137 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52500 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.43231 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.99018E-004 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.44968E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.43231 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5086.26010 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.44968E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 113.32954 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.65847 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.65847 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.20661 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.65847 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.10590 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 22.10590 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.52739 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 22.10590 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.10590 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 33.91238 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.98179 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.02390E-002 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 741326.08000 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.64784E-002 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 22.10590 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 32082.98180 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.80676E-004 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 614.40849 |
350 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 22.10590 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.64784E-002 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.79841E-005 |
353 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.80676E-004 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
356 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 42.80000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.93254 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.07818E-002 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 92321.21181 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.29750E-003 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 2977.14093 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.60453E-005 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 57.01405 |
368 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.29750E-003 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.44410E-004 |
371 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.60453E-005 |
372 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 4.90359 |
373 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 4.36989E-003 |
374 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.90359 |
375 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Electric Power Consumption [W] | 700.51236 |
376 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 3.87257 |
377 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 3.45109E-003 |
378 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.87257 |
379 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Electric Power Consumption [W] | 553.22422 |
380 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Condenser water flow rate [m3/s] | 3.45109E-003 |
381 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Evaporator air flow rate [m3/s] | 3.87257 |
382 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 3.75357E-002 |
383 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 7658.12560 |
384 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.50074E-003 |
385 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.18009 |
386 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.50074E-003 |
387 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 447.48287 |
388 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
389 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 171544.07052 |
390 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 171544.07000 |
391 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.50074E-003 |
392 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75357E-002 |
393 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 4.50428 |
394 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 3.75357E-002 |
395 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 5301.97865 |
396 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 3.75357E-002 |
397 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1050898.31512 |
398 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1051512.08000 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 119.87238 |
400 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
401 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
402 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
403 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
404 | WaterHeater:Stratified | SWHSYS1 HPWH TANK | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
405 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Condenser water flow rate [m3/s] | 4.36989E-003 |
406 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Evaporator air flow rate [m3/s] | 4.90359 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 7019.85 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 1988.78 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 951.78 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 1151.73 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 665.08 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 9916.69 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 6649.29 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 18713.83 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 2424.44 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 2422.32 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 20897.71 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 20903.42 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 2428.33 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 2426.21 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 7639.86 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 763.45 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 763.12 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 3719.96 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 8971.32 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 9253.72 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6176.57 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 5110.57 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 30384.80 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 2819.56 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 17846.74 | 14459.98 | 3386.76 | 0.81 | 2002.62 | 20.31 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 17512.02 | 14187.18 | 3324.85 | 0.81 | 1964.98 | 19.93 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 105641.37 | 86005.25 | 19636.12 | 0.81 | 11873.42 | 120.43 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 115657.39 | 92871.55 | 22785.83 | 0.80 | 12941.98 | 131.26 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 16043.53 | 12990.79 | 3052.73 | 0.81 | 1799.90 | 18.26 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 15743.93 | 12746.72 | 2997.21 | 0.81 | 1766.23 | 17.91 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4820.07 | 3906.94 | 913.13 | 0.81 | 540.94 | 5.49 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4731.09 | 3834.47 | 896.62 | 0.81 | 530.94 | 5.39 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 23090.56 | 18644.83 | 4445.73 | 0.81 | 2588.19 | 26.25 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 640749.70 | 427028.98 | 213720.73 | 0.67 | 72742.75 | 737.80 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 62973.74 | 41190.39 | 21783.35 | 0.65 | 6855.01 | 69.53 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.608 | 1.296 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.608 | 1.296 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.608 | 1.296 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.608 | 1.296 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.684 | 1.345 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.684 | 1.345 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.684 | 1.345 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.684 | 1.345 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.684 | 1.345 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.1650963668E-002 | 1.9662584212E-002 | Pass | Pass | 7.0499353580E-003 | 1.8374350055E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.2523655238E-002 | 4.0792960013E-002 | Pass | Pass | 1.4117131245E-002 | 1.9615861914E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.4337059522E-002 | 2.9067637217E-002 | Pass | Pass | 5.6774997857E-003 | 1.5382471762E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.2933718799E-002 | 1.4508138735E-002 | Pass | Pass | 5.2997469001E-003 | 1.6952859266E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.8114815308E-003 | 9.2249363207E-003 | Pass | Pass | 5.0566951484E-003 | 1.7069296608E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.7619502564E-002 | 0.1999016718 | Pass | Pass | 1.8538251387E-002 | 4.9862730747E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.0241573323E-002 | 6.6812526030E-002 | Pass | Pass | 8.0818842852E-003 | 1.5298645814E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.3514393894E-002 | 4.2596252171E-002 | Pass | Pass | 6.3374448428E-003 | 1.4495507251E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.3107671650E-002 | 0.2428367069 | Pass | Pass | 0.2653508685 | 2.1393498130 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.6089270837E-002 | 0.2090489306 | Pass | Pass | 2.9800473057 | 34.1588430081 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.6202787875E-003 | 1.6554246062E-002 | Pass | Pass | 8.7270773003E-002 | 0.1906562468 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2118654578E-002 | 0.2253833441 | Pass | Pass | 0.8561080115 | 9.1827028714 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.5453591200E-002 | 0.2379129635 | Pass | Pass | 0.2914356762 | 1.9606845708 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.1009411368E-002 | 0.1805313684 | Pass | Pass | 1.4586061255 | 15.0848428932 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.9498372061E-003 | 1.0082457226E-002 | Pass | Pass | 5.4407846951E-003 | 1.7913364528E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.5309815660E-002 | 0.2250338114 | Pass | Pass | 0.3375314894 | 1.5571618968 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.6609055277E-002 | 0.1925805602 | Pass | Pass | 0.8885832911 | 8.3940099676 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.8868871957E-002 | 0.2713657194 | Pass | Pass | 0.1230853198 | 0.6284657004 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.8378724898E-002 | 6.3733652833E-002 | Pass | Pass | 1.2257754421E-002 | 3.7141415658E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.8794036424E-002 | 4.5119358821E-002 | Pass | Pass | 1.2796776038E-002 | 3.6286106236E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.2817367820E-002 | 6.7524860304E-002 | Pass | Pass | 2.0151149561E-002 | 4.0027754093E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.3122172818E-002 | 1.4128758086E-002 | Pass | Pass | 1.0301834408E-002 | 1.8955580528E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2247.96 | -24.4 | -1304.6 | -4811.4 | 15104.95 | 11212.45 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.897 | 0.231 | 0.231 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.897 | 0.231 | 0.231 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.897 | 0.231 | 0.231 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.897 | 0.231 | 0.231 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.897 | 0.231 | 0.231 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.897 | 0.231 | 0.231 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.897 | 0.231 | 0.231 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.897 | 0.231 | 0.231 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.897 | 0.231 | 0.231 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.897 | 0.231 | 0.231 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.897 | 0.231 | 0.231 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.897 | 0.231 | 0.231 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.897 | 0.231 | 0.231 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.897 | 0.231 | 0.231 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.897 | 0.231 | 0.231 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.897 | 0.231 | 0.231 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.897 | 0.231 | 0.231 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.897 | 0.231 | 0.231 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.897 | 0.231 | 0.231 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.897 | 0.231 | 0.231 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.897 | 0.231 | 0.231 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.897 | 0.231 | 0.231 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.897 | 0.231 | 0.231 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.897 | 0.231 | 0.231 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.897 | 0.231 | 0.231 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.897 | 0.231 | 0.231 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.897 | 0.231 | 0.231 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.897 | 0.231 | 0.231 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.897 | 0.231 | 0.231 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.897 | 0.231 | 0.231 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.897 | 0.231 | 0.231 | |||||||||||||||||
North Total or Average | 432.95 | 2.897 | 0.231 | 0.231 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.897 | 0.231 | 0.231 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.6442 | 1978.83 | 13147.70 | LightsWired | LTG_SCH_BASEMENT | 45.99 | 168.00 | 45.94 | 0.0000 | Y | 113.37 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 9.6995 | 67.07 | 650.56 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 6.26 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 9.6995 | 77.67 | 753.35 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.25 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 4.0903 | 94.76 | 387.59 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 1.87 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.7049 | 78.04 | 445.21 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.90 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 9.2569 | 188.86 | 1748.29 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.87 | 0.0000 | Y | 13.08 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 9.0417 | 1308.19 | 11828.20 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 55.44 | 0.0000 | Y | 123.09 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.4132 | 1863.81 | 8225.38 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 73.68 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.4132 | 1864.32 | 8227.62 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 73.70 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 4.4132 | 1557.62 | 6874.08 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 56.74 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.21 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.54 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.19 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.54 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.4132 | 220.77 | 974.32 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 8.73 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.36 | 0.0000 | Y | 28.45 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.36 | 0.0000 | Y | 28.45 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.7327 | 103.30 | 1212.04 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.34 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 4.4132 | 412.12 | 1818.79 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 15.01 |
Interior Lighting Total | 5.8432 | 11345.29 | 66293.22 | 389.79 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 11096.45 | AstronomicalClock | - | 83.85 | 83.85 | 174.66 | |
Exterior Lighting Total | 11096.45 | 174.66 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 171544.07 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1051512.08 | 2.96 | 1051696.91 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12040.64 | 17846.74 | 14459.98 | 3386.76 | 0.81 | - | 2002.62 | 20.31 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11816.67 | 17512.02 | 14187.18 | 3324.85 | 0.81 | - | 1964.98 | 19.93 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 70807.27 | 105641.37 | 86005.25 | 19636.12 | 0.81 | - | 11873.42 | 120.43 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 79030.28 | 115657.39 | 92871.55 | 22785.83 | 0.80 | - | 12941.98 | 131.26 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10833.52 | 16043.53 | 12990.79 | 3052.73 | 0.81 | - | 1799.90 | 18.26 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10632.93 | 15743.93 | 12746.72 | 2997.21 | 0.81 | - | 1766.23 | 17.91 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3250.15 | 4820.07 | 3906.94 | 913.13 | 0.81 | - | 540.94 | 5.49 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3190.54 | 4731.09 | 3834.47 | 896.62 | 0.81 | - | 530.94 | 5.39 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 15653.08 | 23090.56 | 18644.83 | 4445.73 | 0.81 | - | 2588.19 | 26.25 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 741326.08 | 640749.70 | 427028.98 | 213720.73 | 0.67 | - | 72742.75 | 737.80 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 92321.21 | 62973.74 | 41190.39 | 21783.35 | 0.65 | - | 6855.01 | 69.53 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 6983.78 | 7019.85 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1979.19 | 1988.78 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 947.00 | 951.78 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1146.03 | 1151.73 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 661.80 | 665.08 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9865.94 | 9916.69 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6616.13 | 6649.29 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 18619.51 | 18713.83 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 2251.34 | 2424.44 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 2249.38 | 2422.32 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 19405.67 | 20897.71 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 19410.98 | 20903.42 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 2254.96 | 2428.33 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 2252.99 | 2426.21 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 7602.98 | 7639.86 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 708.94 | 763.45 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 708.63 | 763.12 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 3454.35 | 3719.96 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8926.15 | 8971.32 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 9207.09 | 9253.72 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 6144.83 | 6176.57 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 5086.26 | 5110.57 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 32082.98 | 30384.80 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 2977.14 | 2819.56 | - |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 75921.46 | 3.40 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 54370.95 | 3.40 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.08 | 759.55 | 703.64 | 1.00 | 1.18 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.06 | 745.09 | 703.64 | 1.00 | 1.18 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.47 | 4553.05 | 703.64 | 1.00 | 0.95 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.83 | 4806.98 | 703.64 | 1.00 | 0.95 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.97 | 681.68 | 703.64 | 1.00 | 1.20 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.95 | 668.75 | 703.64 | 1.00 | 1.21 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.29 | 205.36 | 703.64 | 1.00 | 1.73 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.29 | 201.52 | 703.64 | 1.00 | 1.75 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.38 | 973.91 | 703.64 | 1.00 | 1.13 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 22.11 | 49531.33 | 2240.64 | 1.00 | 1.11 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 |
SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 4.90 | 700.51 | 142.86 | 0.00 | 2.78 | General | ||
SWHSYS1 HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 3.87 | 553.22 | 142.86 | 0.00 | 2.84 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.037536 | 7658.13 | 204022.71 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.001501 | 447.48 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.037536 | 5301.98 | 141251.80 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYSLAUNDRY HPWH | WaterHeater:HeatPump:PumpedCondenser | 1.14 | 77713.00 | 0.80 | 48.89 | 1.73 |
SWHSYS1 HPWH | WaterHeater:HeatPump:PumpedCondenser | 2.84 | 63057.66 | 0.80 | 4.65 | 9.47 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 34675.31 | 34675.31 | 17.52 | 2.521 | 2.521 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 20:40:00 | 24.00 | 24.00 | 0.00920 | 37.37 | 0.01077 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4953.06 | 4953.06 | 73.85 | 0.360 | 0.360 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00901 | 42.80 | 0.01078 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3274.98 | 3274.98 | 42.17 | 0.238 | 0.238 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 24.00 | 24.00 | 0.00937 | 40.96 | 0.01078 | 0.092 | 0.00 |
MECH_FLR_1 | 3218.28 | 3218.28 | 19.59 | 0.234 | 0.234 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 19:20:00 | 24.00 | 24.00 | 0.00871 | 38.66 | 0.01077 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1750.35 | 1750.35 | 18.47 | 0.127 | 0.127 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00878 | 41.96 | 0.01078 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 45282.90 | 45282.90 | 580.26 | 3.292 | 3.292 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00854 | 41.28 | 0.01078 | 0.000 | 0.00 |
CAFE_FLR_1 | 20441.09 | 20441.09 | 108.23 | 1.487 | 1.487 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 23.99 | 0.01008 | 42.80 | 0.01078 | 0.676 | 0.00 |
LOBBY_FLR_1 | 66566.80 | 66566.80 | 50.88 | 4.841 | 4.841 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 23.99 | 0.00994 | 42.80 | 0.01078 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 11020.32 | 11020.32 | 282.41 | 1.079 | 1.079 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 21.11 | 21.11 | 0.00858 | 42.09 | 0.01078 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10810.41 | 10810.41 | 277.07 | 1.059 | 1.059 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 21.11 | 21.11 | 0.00858 | 41.96 | 0.01078 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 66063.17 | 66063.17 | 2693.83 | 6.471 | 6.471 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 21.11 | 21.11 | 0.00851 | 42.80 | 0.01078 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 69742.30 | 69742.30 | 2843.08 | 6.832 | 6.832 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 21.11 | 21.11 | 0.00871 | 42.51 | 0.01078 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9890.45 | 9890.45 | 253.46 | 0.969 | 0.969 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 21.11 | 21.11 | 0.00859 | 40.08 | 0.01078 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9702.78 | 9702.78 | 248.68 | 0.950 | 0.950 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 21.11 | 21.11 | 0.00859 | 39.84 | 0.01078 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 19113.30 | 19113.30 | 49.08 | 1.389 | 1.389 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00950 | 42.61 | 0.01078 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2979.53 | 2979.53 | 76.36 | 0.292 | 0.292 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 21.11 | 21.11 | 0.00857 | 42.09 | 0.01078 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2923.84 | 2923.84 | 74.94 | 0.286 | 0.286 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 21.11 | 21.11 | 0.00857 | 42.09 | 0.01078 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 14130.13 | 14130.13 | 576.02 | 1.384 | 1.384 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 21.11 | 21.11 | 0.00863 | 42.80 | 0.01078 | 0.099 | 0.00 |
BANQUET_FLR_6 | 31400.94 | 31400.94 | 94.68 | 2.285 | 2.285 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 23.99 | 0.01030 | 42.80 | 0.01078 | 1.188 | 0.00 |
DINING_FLR_6 | 32855.26 | 32855.26 | 99.06 | 2.391 | 2.391 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 23.99 | 0.01022 | 42.80 | 0.01078 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30431.32 | 30431.32 | 294.58 | 2.218 | 2.218 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 24.00 | 23.97 | 0.01009 | 41.93 | 0.01078 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 11328.19 | 11328.19 | 27.49 | 0.823 | 0.823 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00895 | 42.80 | 0.01078 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | 00:10:00 | 21.00 | 23.71 | 0.00915 | 12.70 | 0.00915 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 981.39 | 981.39 | 14.63 | 0.042 | 0.079 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | 21.00 | 21.00 | 0.00806 | 12.70 | 0.00915 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 287.22 | 287.22 | 3.70 | 0.012 | 0.092 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | 21.00 | 21.00 | 0.00808 | 12.70 | 0.00915 | 0.092 | 0.00 |
MECH_FLR_1 | 497.78 | 497.78 | 3.03 | 0.021 | 0.021 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | 21.00 | 21.00 | 0.00811 | 12.70 | 0.00915 | 0.000 | 0.00 |
STORAGE_FLR_1 | 309.24 | 309.24 | 3.26 | 0.013 | 0.058 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | 21.00 | 21.00 | 0.00810 | 12.70 | 0.00915 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 743.93 | 743.93 | 9.53 | 0.032 | 0.032 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | 21.00 | 21.00 | 0.00810 | 12.70 | 0.00915 | 0.000 | 0.00 |
CAFE_FLR_1 | 2494.93 | 2494.93 | 13.21 | 0.107 | 0.676 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | 21.00 | 21.00 | 0.00806 | 12.70 | 0.00915 | 0.676 | 0.00 |
LOBBY_FLR_1 | 5205.51 | 5205.51 | 3.98 | 0.223 | 1.894 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | 21.00 | 21.00 | 0.00808 | 12.70 | 0.00915 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 2251.34 | 2251.34 | 57.69 | 0.097 | 0.097 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.11 | 21.11 | 0.00806 | 12.70 | 0.00915 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 2249.38 | 2249.38 | 57.65 | 0.097 | 0.097 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.11 | 21.11 | 0.00806 | 12.70 | 0.00915 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 13425.99 | 13425.99 | 547.47 | 0.579 | 0.837 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.11 | 21.11 | 0.00806 | 12.70 | 0.00915 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 13402.07 | 13402.07 | 546.34 | 0.578 | 0.837 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.11 | 21.11 | 0.00806 | 12.70 | 0.00915 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 2254.96 | 2254.96 | 57.79 | 0.097 | 0.097 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.11 | 21.11 | 0.00806 | 12.70 | 0.00915 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 2252.99 | 2252.99 | 57.74 | 0.097 | 0.097 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.11 | 21.11 | 0.00806 | 12.70 | 0.00915 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 3753.21 | 3753.21 | 9.64 | 0.161 | 0.475 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00805 | 12.70 | 0.00915 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 708.94 | 708.94 | 18.17 | 0.031 | 0.031 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.11 | 21.11 | 0.00805 | 12.70 | 0.00915 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 708.63 | 708.63 | 18.16 | 0.031 | 0.031 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.11 | 21.11 | 0.00805 | 12.70 | 0.00915 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3454.35 | 3454.35 | 140.82 | 0.149 | 0.149 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.11 | 21.11 | 0.00805 | 12.70 | 0.00915 | 0.099 | 0.00 |
BANQUET_FLR_6 | 2593.85 | 2593.85 | 7.82 | 0.111 | 1.188 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 20:20:00 | 21.00 | 21.00 | 0.00804 | 12.70 | 0.00915 | 1.188 | 0.00 |
DINING_FLR_6 | 2581.62 | 2581.62 | 7.78 | 0.111 | 1.188 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | 21.00 | 21.00 | 0.00804 | 12.70 | 0.00915 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.367 | 00:10:00 | 21.00 | 22.08 | 0.00428 | 12.70 | 0.00915 | 0.367 | 0.00 | |
CORRIDOR_FLR_6 | 2804.65 | 2804.65 | 6.81 | 0.120 | 0.126 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 21.00 | 21.00 | 0.00803 | 12.70 | 0.00915 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 22.11 | 22.11 | 7.05 | 7.05 | 22.1059 | 11.6585 | 22.1059 | 0.5274 | 0.3000 |
FLR_3_DOAS | 19.07 | 2.05 | 2.27 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 6983.782 | 6983.782 | 1.323319 | 0.00006110 | 145.635 | 1/21 00:10:00 | 1/21 00:10:00 | 6983.78 | 6983.78 | 1.323319 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 7023.03 | 7023.03 | ||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 1979.189 | 1979.189 | 0.189043 | 0.00001731 | 43.500 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | 1979.19 | 1979.19 | 0.189043 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00806411 | 52.1015 | 981.39 | 0.00 | 1989.99 | 1989.99 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 946.997 | 946.997 | 0.124998 | 0.00000828 | 20.205 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | 947.00 | 947.00 | 0.124998 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00808307 | 52.2226 | 287.22 | 0.00 | 952.28 | 952.28 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1146.031 | 1146.031 | 0.122807 | 0.00001003 | 24.894 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | 1146.03 | 1146.03 | 0.122807 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00811043 | 52.3971 | 497.78 | 0.00 | 1152.39 | 1152.39 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 661.803 | 661.803 | 0.066793 | 0.00000579 | 14.462 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | 661.80 | 661.80 | 0.066793 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00810325 | 52.3513 | 309.24 | 0.00 | 665.47 | 665.47 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 9865.945 | 9865.945 | 1.728128 | 0.00008631 | 206.613 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | 9865.94 | 9865.94 | 1.728128 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00810171 | 52.3413 | 743.93 | 0.00 | 9921.31 | 9921.31 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 6616.129 | 6616.129 | 0.780813 | 0.00005788 | 142.455 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | 6616.13 | 6616.13 | 0.780813 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00805615 | 52.0508 | 2494.93 | 0.00 | 6652.92 | 6652.92 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 18619.510 | 18619.510 | 2.541379 | 0.00016289 | 396.268 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | 18619.51 | 18619.51 | 2.541379 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00807554 | 52.1745 | 5205.51 | 0.00 | 18723.42 | 18723.42 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12040.639 | -999.000 | 1.079469 | 0.00043006 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | unknown | 8/21 16:10:00 | 12040.64 | 11810.41 | 1.079469 | 21.68 | 15.62 | 0.00857901 | 12.80 | 12.09 | 0.00850000 | 42.09 | 0.01078059 | 23.67 | 0.0000 | 21.11 | 0.00857901 | 55.0083 | 11020.32 | 0.00 | 12058.49 | 11632.63 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 2251.343 | 2251.343 | 0.097113 | 0.00001970 | 64.316 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 2251.34 | 2251.34 | 0.097113 | 21.11 | 14.95 | 0.00806448 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.11 | 0.00806448 | 51.7498 | 2251.34 | 0.00 | 2427.03 | 2427.03 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 11816.673 | -999.000 | 1.058907 | 0.00042206 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | 8/21 16:20:00 | 11816.67 | 11586.07 | 1.058907 | 21.68 | 15.62 | 0.00858067 | 12.80 | 12.09 | 0.00850000 | 41.96 | 0.01078037 | 23.63 | 0.0000 | 21.11 | 0.00858067 | 55.0188 | 10810.41 | 0.00 | 11834.18 | 11411.94 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 2249.378 | 2249.378 | 0.097028 | 0.00001968 | 64.260 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 2249.38 | 2249.38 | 0.097028 | 21.11 | 14.95 | 0.00806453 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.11 | 0.00806453 | 51.7501 | 2249.38 | 0.00 | 2424.91 | 2424.91 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 70807.273 | -999.000 | 6.470743 | 0.00252902 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | unknown | 8/21 14:20:00 | 70807.27 | 70638.97 | 6.470743 | 21.68 | 15.56 | 0.00850966 | 12.80 | 12.09 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 0.0000 | 21.11 | 0.00850966 | 54.5682 | 66063.17 | 0.00 | 70914.76 | 69505.51 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 19405.672 | 19405.672 | 0.837072 | 0.00016977 | 554.381 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 19405.67 | 19405.67 | 0.837072 | 21.11 | 14.94 | 0.00805768 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.11 | 0.00805768 | 51.7068 | 13425.99 | 0.00 | 20920.03 | 20920.03 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 79030.282 | -999.000 | 6.831626 | 0.00282273 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | unknown | 8/21 15:30:00 | 79030.28 | 75057.35 | 6.831626 | 21.68 | 15.74 | 0.00871454 | 12.80 | 12.09 | 0.00850000 | 42.51 | 0.01078131 | 23.78 | 0.0000 | 21.11 | 0.00871454 | 55.8660 | 69742.30 | 0.00 | 79142.54 | 74066.51 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 19410.978 | 19410.978 | 0.837300 | 0.00016982 | 554.533 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 19410.98 | 19410.98 | 0.837300 | 21.11 | 14.94 | 0.00805779 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.11 | 0.00805779 | 51.7075 | 13402.07 | 0.00 | 20925.75 | 20925.75 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 10833.516 | -999.000 | 0.968796 | 0.00038694 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | unknown | 8/21 10:40:00 | 10833.52 | 10602.68 | 0.968796 | 21.68 | 15.63 | 0.00858825 | 12.80 | 12.09 | 0.00850000 | 40.08 | 0.01077714 | 23.12 | 0.0000 | 21.11 | 0.00858825 | 55.0667 | 9890.45 | 0.00 | 10849.53 | 10444.45 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 2254.958 | 2254.958 | 0.097269 | 0.00001973 | 64.419 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 2254.96 | 2254.96 | 0.097269 | 21.11 | 14.95 | 0.00806438 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.11 | 0.00806438 | 51.7492 | 2254.96 | 0.00 | 2430.93 | 2430.93 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10632.932 | -999.000 | 0.950413 | 0.00037978 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | unknown | 8/21 10:30:00 | 10632.93 | 10402.06 | 0.950413 | 21.68 | 15.63 | 0.00858996 | 12.80 | 12.09 | 0.00850000 | 39.84 | 0.01077673 | 23.05 | 0.0000 | 21.11 | 0.00858996 | 55.0775 | 9702.78 | 0.00 | 10648.64 | 10247.08 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 2252.991 | 2252.991 | 0.097184 | 0.00001971 | 64.363 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 2252.99 | 2252.99 | 0.097184 | 21.11 | 14.95 | 0.00806443 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.11 | 0.00806443 | 51.7495 | 2252.99 | 0.00 | 2428.81 | 2428.81 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 7602.985 | 7602.985 | 0.729409 | 0.00006651 | 167.023 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7602.98 | 7602.98 | 0.729409 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00804787 | 51.9981 | 3753.21 | 0.00 | 7644.48 | 7644.48 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3250.147 | -999.000 | 0.291853 | 0.00011609 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | unknown | 8/21 16:10:00 | 3250.15 | 3192.55 | 0.291853 | 21.68 | 15.61 | 0.00857313 | 12.80 | 12.09 | 0.00850000 | 42.09 | 0.01078059 | 23.67 | 0.0000 | 21.11 | 0.00857313 | 54.9711 | 2979.53 | 0.00 | 3254.98 | 3144.22 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 708.942 | 708.942 | 0.030581 | 0.00000620 | 20.253 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 708.94 | 708.94 | 0.030581 | 21.11 | 14.93 | 0.00805180 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.11 | 0.00805180 | 51.6695 | 708.94 | 0.00 | 764.27 | 764.27 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3190.539 | -999.000 | 0.286397 | 0.00011396 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | unknown | 8/21 16:10:00 | 3190.54 | 3133.00 | 0.286397 | 21.68 | 15.61 | 0.00857444 | 12.80 | 12.09 | 0.00850000 | 42.09 | 0.01078059 | 23.67 | 0.0000 | 21.11 | 0.00857444 | 54.9793 | 2923.84 | 0.00 | 3195.28 | 3085.64 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 708.631 | 708.631 | 0.030567 | 0.00000620 | 20.244 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 708.63 | 708.63 | 0.030567 | 21.11 | 14.93 | 0.00805182 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.11 | 0.00805182 | 51.6696 | 708.63 | 0.00 | 763.93 | 763.93 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 15653.079 | -999.000 | 1.384115 | 0.00055908 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | unknown | 8/21 14:20:00 | 15653.08 | 15167.56 | 1.384115 | 21.68 | 15.66 | 0.00862974 | 12.80 | 12.09 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 0.0000 | 21.11 | 0.00862974 | 55.3298 | 14130.13 | 0.00 | 15675.91 | 14949.97 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 3454.354 | 3454.354 | 0.149005 | 0.00003022 | 98.685 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 3454.35 | 3454.35 | 0.149005 | 21.11 | 14.93 | 0.00804907 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.11 | 0.00804907 | 51.6522 | 3454.35 | 0.00 | 3723.92 | 3723.92 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 8926.151 | 8926.151 | 1.199787 | 0.00007809 | 190.187 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 20:20:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 20:20:00 | 8926.15 | 8926.15 | 1.199787 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00803530 | 51.9179 | 2593.85 | 0.00 | 8975.95 | 8975.95 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 9207.086 | 9207.086 | 1.255337 | 0.00008055 | 195.965 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | 9207.09 | 9207.09 | 1.255337 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00803556 | 51.9196 | 2581.62 | 0.00 | 9258.47 | 9258.47 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 6144.832 | 6144.832 | 1.164351 | 0.00005376 | 128.140 | 1/21 00:10:00 | 1/21 00:10:00 | 6144.83 | 6144.83 | 1.164351 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 6179.37 | 6179.37 | ||
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 5086.260 | 5086.260 | 0.432306 | 0.00004450 | 113.330 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 5086.26 | 5086.26 | 0.432306 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00802883 | 51.8767 | 2804.65 | 0.00 | 5113.86 | 5113.86 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 741326.080 | -999.000 | 22.105898 | 0.02647845 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 741326.08 | 619988.11 | 22.105898 | 33.91 | 20.98 | 0.01023895 | 10.98 | 10.98 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 52.7527 | 23.99 | 0.00961384 | 51.6595 | 303909.58 | 0.00 | 742267.38 | 605764.03 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 32082.982 | 32082.982 | 6.631769 | 0.00028068 | 614.408 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | 32082.98 | 32082.98 | 6.631769 | 12.70 | 12.70 | 0.00915345 | 16.70 | 13.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 175.8424 | 22.04 | 0.00731202 | 44.3791 | 22208.08 | 0.00 | 36793.34 | 36793.34 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 92321.212 | -999.000 | 2.051317 | 0.00329750 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 92321.21 | 77917.60 | 2.051317 | 42.80 | 23.86 | 0.01078182 | 11.93 | 11.73 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 99.9965 | 21.11 | 0.00861493 | 55.2352 | 194419.14 | 0.00 | 92413.81 | 77447.65 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 2977.141 | 2977.141 | 0.615395 | 0.00002605 | 57.014 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 2977.14 | 2977.14 | 0.615395 | 12.70 | 12.70 | 0.00915345 | 16.70 | 13.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 333.3216 | 21.11 | 0.00805772 | 51.7071 | 40708.64 | 0.00 | 3414.24 | 3414.24 |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 71441.156 | 52580.691 | 4.903586 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 75921.46 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 56448.486 | 41546.086 | 3.872570 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 54370.95 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 6983.782 | 6983.782 | 1.323319 | 0.00006110 | 145.635 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 3.9908 | 4.071130 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 6983.78 | 6983.78 | 1.0000 | 1.59273991 | 1.323319 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.06109094 | 60.00 | 32.22 | 27.78 | 0.000 | 6983.78 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 7023.03 | 7023.03 | 1.59273991 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1979.189 | 1979.189 | 0.189043 | 0.00001731 | 43.500 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 1.1310 | 1.153750 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | Sensible | 1979.19 | 1979.19 | 1.0000 | 0.22753116 | 0.189043 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01731304 | 60.00 | 32.22 | 27.78 | 0.000 | 1979.19 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00806411 | 21.00 | 0.00806411 | 52.1015 | 981.39 | 0.00 | 1989.99 | 1989.99 | 0.22753116 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.18 | 16.38 | 0.00800000 | 45680.7 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 946.997 | 946.997 | 0.124998 | 0.00000828 | 20.205 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 0.5412 | 0.552043 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | Sensible | 947.00 | 947.00 | 1.0000 | 0.15044675 | 0.124998 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.00828390 | 60.00 | 32.22 | 27.78 | 0.000 | 947.00 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00808307 | 21.00 | 0.00808307 | 52.2226 | 287.22 | 0.00 | 952.28 | 952.28 | 0.15044675 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.81 | 15.52 | 0.00800000 | 43264.4 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1146.031 | 1146.031 | 0.122807 | 0.00001003 | 24.894 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 0.6549 | 0.668068 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | Sensible | 1146.03 | 1146.03 | 1.0000 | 0.14781033 | 0.122807 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01002496 | 60.00 | 32.22 | 27.78 | 0.000 | 1146.03 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00811043 | 21.00 | 0.00811043 | 52.3971 | 497.78 | 0.00 | 1152.39 | 1152.39 | 0.14781033 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.25 | 16.04 | 0.00800000 | 44731.1 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 661.803 | 661.803 | 0.066793 | 0.00000579 | 14.462 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 0.3782 | 0.385792 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | Sensible | 661.80 | 661.80 | 1.0000 | 0.08039129 | 0.066793 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.00578915 | 60.00 | 32.22 | 27.78 | 0.000 | 661.80 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00810325 | 21.00 | 0.00810325 | 52.3513 | 309.24 | 0.00 | 665.47 | 665.47 | 0.08039129 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.72 | 16.21 | 0.00800000 | 45212.6 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9865.945 | 9865.945 | 1.728128 | 0.00008631 | 206.613 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 5.6378 | 5.751259 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | Sensible | 9865.94 | 9865.94 | 1.0000 | 2.07996647 | 1.728128 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.08630278 | 60.00 | 32.22 | 27.78 | 0.000 | 9865.94 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00810171 | 21.00 | 0.00810171 | 52.3413 | 743.93 | 0.00 | 9921.31 | 9921.31 | 2.07996647 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.28 | 14.96 | 0.00800000 | 41704.7 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6616.129 | 6616.129 | 0.780813 | 0.00005788 | 142.455 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 3.7807 | 3.856810 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | Sensible | 6616.13 | 6616.13 | 1.0000 | 0.93978316 | 0.780813 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.05787488 | 60.00 | 32.22 | 27.78 | 0.000 | 6616.13 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00805615 | 21.00 | 0.00805615 | 52.0508 | 2494.93 | 0.00 | 6652.92 | 6652.92 | 0.93978316 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.54 | 15.79 | 0.00800000 | 44013.9 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18619.510 | 18619.510 | 2.541379 | 0.00016289 | 396.268 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 10.6399 | 10.854068 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | Sensible | 18619.51 | 18619.51 | 1.0000 | 3.05879120 | 2.541379 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.16287498 | 60.00 | 32.22 | 27.78 | 0.000 | 18619.51 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00807554 | 21.00 | 0.00807554 | 52.1745 | 5205.51 | 0.00 | 18723.42 | 18723.42 | 3.05879120 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.60 | 15.45 | 0.00800000 | 43055.9 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12040.639 | -999.000 | 1.079469 | 0.00043006 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7880 | 1004.8586 | 1.2036 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.079469 | 1.29924313 | 4197.9300 | 999.8980 | 37.53182385 | 13.37 | 6.70 | 6.67 | 1050898.32 | 1.1457 | 1.145726 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | unknown | unknown | unknown | 8/21 16:10:00 | Sensible | 12040.64 | 11810.41 | 1.0000 | 1.29924313 | 1.079469 | 21.68 | 15.62 | 0.00857901 | 43589.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.43001182 | 6.70 | 13.37 | 6.67 | 0.000 | 12040.64 | 42.09 | 0.01078059 | 23.67 | 0.00000000 | 0.0000 | 21.11 | 0.00857901 | 21.11 | 0.00857901 | 55.0083 | 11020.32 | 0.00 | 12058.49 | 11632.63 | 1.29924313 | 21.68 | 15.62 | 0.00857901 | 43589.6 | 12.91 | 12.10 | 0.00844920 | 34308.5 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2251.343 | 2251.343 | 0.097113 | 0.00001970 | 64.316 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.079469 | 1.29924313 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 1.2865 | 1.312399 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 2251.34 | 2251.34 | 1.0000 | 0.11688439 | 0.097113 | 21.11 | 14.95 | 0.00806448 | 41698.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01969372 | 60.00 | 32.22 | 27.78 | 0.000 | 2251.34 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.11 | 0.00806448 | 21.11 | 0.00806448 | 51.7498 | 2251.34 | 0.00 | 2427.03 | 2427.03 | 0.11688439 | 16.60 | 13.21 | 0.00806448 | 37098.0 | 36.96 | 20.31 | 0.00806448 | 57862.4 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11816.673 | -999.000 | 1.058907 | 0.00042206 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7910 | 1004.8586 | 1.2036 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.058907 | 1.27449569 | 4197.9300 | 999.8980 | 37.53182385 | 13.37 | 6.70 | 6.67 | 1050898.32 | 1.1244 | 1.124414 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | unknown | unknown | 8/21 16:20:00 | Sensible | 11816.67 | 11586.07 | 1.0000 | 1.27449569 | 1.058907 | 21.68 | 15.62 | 0.00858067 | 43593.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.42201324 | 6.70 | 13.37 | 6.67 | 0.000 | 11816.67 | 41.96 | 0.01078037 | 23.63 | 0.00000000 | 0.0000 | 21.11 | 0.00858067 | 21.11 | 0.00858067 | 55.0188 | 10810.41 | 0.00 | 11834.18 | 11411.94 | 1.27449569 | 21.68 | 15.63 | 0.00858067 | 43593.8 | 12.91 | 12.10 | 0.00844946 | 34308.5 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2249.378 | 2249.378 | 0.097028 | 0.00001968 | 64.260 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.058907 | 1.27449569 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 1.2854 | 1.311254 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 2249.38 | 2249.38 | 1.0000 | 0.11678240 | 0.097028 | 21.11 | 14.95 | 0.00806453 | 41698.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01967653 | 60.00 | 32.22 | 27.78 | 0.000 | 2249.38 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.11 | 0.00806453 | 21.11 | 0.00806453 | 51.7501 | 2249.38 | 0.00 | 2424.91 | 2424.91 | 0.11678240 | 16.60 | 13.21 | 0.00806453 | 37098.1 | 36.96 | 20.31 | 0.00806453 | 57862.5 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 70807.273 | -999.000 | 6.470743 | 0.00252902 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6590 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.470743 | 7.78815409 | 4197.9300 | 999.8980 | 37.53182385 | 13.37 | 6.70 | 6.67 | 1050898.32 | 6.7378 | 6.737660 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | unknown | unknown | unknown | 8/21 14:20:00 | Sensible | 70807.27 | 70638.97 | 1.0000 | 7.78815409 | 6.470743 | 21.68 | 15.56 | 0.00850966 | 43413.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 2.52876652 | 6.70 | 13.37 | 6.67 | 0.000 | 70807.27 | 42.80 | 0.01078182 | 23.86 | 0.00000000 | 0.0000 | 21.11 | 0.00850966 | 21.11 | 0.00850966 | 54.5682 | 66063.17 | 0.00 | 70914.76 | 69505.51 | 7.78815409 | 21.68 | 15.56 | 0.00850966 | 43413.9 | 12.94 | 12.10 | 0.00843799 | 34308.4 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19405.672 | 19405.672 | 0.837072 | 0.00016977 | 554.381 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.470743 | 7.78815409 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 11.0892 | 11.312354 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 19405.67 | 19405.67 | 1.0000 | 1.00749507 | 0.837072 | 21.11 | 14.94 | 0.00805768 | 41681.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.16975196 | 60.00 | 32.22 | 27.78 | 0.000 | 19405.67 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.11 | 0.00805768 | 21.11 | 0.00805768 | 51.7068 | 13425.99 | 0.00 | 20920.03 | 20920.03 | 1.00749507 | 16.60 | 13.21 | 0.00805768 | 37080.8 | 36.96 | 20.31 | 0.00805768 | 57845.2 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 79030.282 | -999.000 | 6.831626 | 0.00282273 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0399 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.831626 | 8.22251037 | 4197.9300 | 999.8980 | 37.53182385 | 13.37 | 6.70 | 6.67 | 1050898.32 | 7.5203 | 7.520119 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | unknown | unknown | unknown | 8/21 15:30:00 | Sensible | 79030.28 | 75057.35 | 1.0000 | 8.22251037 | 6.831626 | 21.68 | 15.74 | 0.00871454 | 43933.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 2.82243789 | 6.70 | 13.37 | 6.67 | 0.000 | 79030.28 | 42.51 | 0.01078131 | 23.78 | 0.00000000 | 0.0000 | 21.11 | 0.00871454 | 21.11 | 0.00871454 | 55.8660 | 69742.30 | 0.00 | 79142.54 | 74066.51 | 8.22251037 | 21.68 | 15.74 | 0.00871454 | 43933.6 | 12.86 | 12.10 | 0.00847004 | 34308.5 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19410.978 | 19410.978 | 0.837300 | 0.00016982 | 554.533 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.831626 | 8.22251037 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 11.0922 | 11.315447 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 19410.98 | 19410.98 | 1.0000 | 1.00777057 | 0.837300 | 21.11 | 14.94 | 0.00805779 | 41681.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.16979838 | 60.00 | 32.22 | 27.78 | 0.000 | 19410.98 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.11 | 0.00805779 | 21.11 | 0.00805779 | 51.7075 | 13402.07 | 0.00 | 20925.75 | 20925.75 | 1.00777057 | 16.60 | 13.21 | 0.00805779 | 37081.1 | 36.96 | 20.31 | 0.00805779 | 57845.4 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10833.516 | -999.000 | 0.968796 | 0.00038694 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8051 | 1004.8586 | 1.2036 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.968796 | 1.16603776 | 4197.9300 | 999.8980 | 37.53182385 | 13.37 | 6.70 | 6.67 | 1050898.32 | 1.0309 | 1.030862 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | unknown | unknown | unknown | 8/21 10:40:00 | Sensible | 10833.52 | 10602.68 | 1.0000 | 1.16603776 | 0.968796 | 21.68 | 15.63 | 0.00858825 | 43613.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.38690139 | 6.70 | 13.37 | 6.67 | 0.000 | 10833.52 | 40.08 | 0.01077714 | 23.12 | 0.00000000 | 0.0000 | 21.11 | 0.00858825 | 21.11 | 0.00858825 | 55.0667 | 9890.45 | 0.00 | 10849.53 | 10444.45 | 1.16603776 | 21.68 | 15.63 | 0.00858825 | 43613.1 | 12.91 | 12.10 | 0.00845066 | 34308.5 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2254.958 | 2254.958 | 0.097269 | 0.00001973 | 64.419 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.968796 | 1.16603776 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 1.2886 | 1.314507 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 2254.96 | 2254.96 | 1.0000 | 0.11707212 | 0.097269 | 21.11 | 14.95 | 0.00806438 | 41698.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01972535 | 60.00 | 32.22 | 27.78 | 0.000 | 2254.96 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.11 | 0.00806438 | 21.11 | 0.00806438 | 51.7492 | 2254.96 | 0.00 | 2430.93 | 2430.93 | 0.11707212 | 16.60 | 13.21 | 0.00806438 | 37097.7 | 36.96 | 20.31 | 0.00806438 | 57862.1 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10632.932 | -999.000 | 0.950413 | 0.00037978 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8083 | 1004.8586 | 1.2036 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.950413 | 1.14391256 | 4197.9300 | 999.8980 | 37.53182385 | 13.37 | 6.70 | 6.67 | 1050898.32 | 1.0118 | 1.011776 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | unknown | unknown | unknown | 8/21 10:30:00 | Sensible | 10632.93 | 10402.06 | 1.0000 | 1.14391256 | 0.950413 | 21.68 | 15.63 | 0.00858996 | 43617.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.37973787 | 6.70 | 13.37 | 6.67 | 0.000 | 10632.93 | 39.84 | 0.01077673 | 23.05 | 0.00000000 | 0.0000 | 21.11 | 0.00858996 | 21.11 | 0.00858996 | 55.0775 | 9702.78 | 0.00 | 10648.64 | 10247.08 | 1.14391256 | 21.68 | 15.63 | 0.00858996 | 43617.4 | 12.91 | 12.10 | 0.00845093 | 34308.5 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2252.991 | 2252.991 | 0.097184 | 0.00001971 | 64.363 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.950413 | 1.14391256 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 1.2874 | 1.313360 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 2252.99 | 2252.99 | 1.0000 | 0.11696999 | 0.097184 | 21.11 | 14.95 | 0.00806443 | 41698.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01970814 | 60.00 | 32.22 | 27.78 | 0.000 | 2252.99 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.11 | 0.00806443 | 21.11 | 0.00806443 | 51.7495 | 2252.99 | 0.00 | 2428.81 | 2428.81 | 0.11696999 | 16.60 | 13.21 | 0.00806443 | 37097.9 | 36.96 | 20.31 | 0.00806443 | 57862.2 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7602.985 | 7602.985 | 0.729409 | 0.00006651 | 167.023 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 4.3447 | 4.432088 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7602.98 | 7602.98 | 1.0000 | 0.87791246 | 0.729409 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.06650744 | 60.00 | 32.22 | 27.78 | 0.000 | 7602.98 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00804787 | 21.00 | 0.00804787 | 51.9981 | 3753.21 | 0.00 | 7644.48 | 7644.48 | 0.87791246 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.14 | 16.36 | 0.00800000 | 45642.3 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3250.147 | -999.000 | 0.291853 | 0.00011609 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7770 | 1004.8586 | 1.2036 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.291853 | 0.35127256 | 4197.9300 | 999.8980 | 37.53182385 | 13.37 | 6.70 | 6.67 | 1050898.32 | 0.3093 | 0.309267 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | unknown | unknown | unknown | 8/21 16:10:00 | Sensible | 3250.15 | 3192.55 | 1.0000 | 0.35127256 | 0.291853 | 21.68 | 15.61 | 0.00857313 | 43574.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.11607371 | 6.70 | 13.37 | 6.67 | 0.000 | 3250.15 | 42.09 | 0.01078059 | 23.67 | 0.00000000 | 0.0000 | 21.11 | 0.00857313 | 21.11 | 0.00857313 | 54.9711 | 2979.53 | 0.00 | 3254.98 | 3144.22 | 0.35127256 | 21.68 | 15.62 | 0.00857313 | 43574.7 | 12.91 | 12.10 | 0.00844826 | 34308.5 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 708.942 | 708.942 | 0.030581 | 0.00000620 | 20.253 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.291853 | 0.35127256 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 0.4051 | 0.413271 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 708.94 | 708.94 | 1.0000 | 0.03680662 | 0.030581 | 21.11 | 14.93 | 0.00805180 | 41666.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.00620151 | 60.00 | 32.22 | 27.78 | 0.000 | 708.94 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.11 | 0.00805180 | 21.11 | 0.00805180 | 51.6695 | 708.94 | 0.00 | 764.27 | 764.27 | 0.03680662 | 16.60 | 13.20 | 0.00805180 | 37065.9 | 36.96 | 20.30 | 0.00805180 | 57830.3 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3190.539 | -999.000 | 0.286397 | 0.00011396 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7795 | 1004.8586 | 1.2036 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.286397 | 0.34470640 | 4197.9300 | 999.8980 | 37.53182385 | 13.37 | 6.70 | 6.67 | 1050898.32 | 0.3036 | 0.303595 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | unknown | unknown | unknown | 8/21 16:10:00 | Sensible | 3190.54 | 3133.00 | 1.0000 | 0.34470640 | 0.286397 | 21.68 | 15.61 | 0.00857444 | 43578.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.11394492 | 6.70 | 13.37 | 6.67 | 0.000 | 3190.54 | 42.09 | 0.01078059 | 23.67 | 0.00000000 | 0.0000 | 21.11 | 0.00857444 | 21.11 | 0.00857444 | 54.9793 | 2923.84 | 0.00 | 3195.28 | 3085.64 | 0.34470640 | 21.68 | 15.62 | 0.00857444 | 43578.0 | 12.91 | 12.10 | 0.00844847 | 34308.5 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 708.631 | 708.631 | 0.030567 | 0.00000620 | 20.244 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.286397 | 0.34470640 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 0.4049 | 0.413090 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 708.63 | 708.63 | 1.0000 | 0.03679045 | 0.030567 | 21.11 | 14.93 | 0.00805182 | 41666.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.00619878 | 60.00 | 32.22 | 27.78 | 0.000 | 708.63 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.11 | 0.00805182 | 21.11 | 0.00805182 | 51.6696 | 708.63 | 0.00 | 763.93 | 763.93 | 0.03679045 | 16.60 | 13.20 | 0.00805182 | 37065.9 | 36.96 | 20.30 | 0.00805182 | 57830.3 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15653.079 | -999.000 | 1.384115 | 0.00055908 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8823 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.384115 | 1.66591413 | 4197.9300 | 999.8980 | 37.53182385 | 13.37 | 6.70 | 6.67 | 1050898.32 | 1.4895 | 1.489467 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | unknown | unknown | unknown | 8/21 14:20:00 | Sensible | 15653.08 | 15167.56 | 1.0000 | 1.66591413 | 1.384115 | 21.68 | 15.66 | 0.00862974 | 43718.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.55902425 | 6.70 | 13.37 | 6.67 | 0.000 | 15653.08 | 42.80 | 0.01078182 | 23.86 | 0.00000000 | 0.0000 | 21.11 | 0.00862974 | 21.11 | 0.00862974 | 55.3298 | 14130.13 | 0.00 | 15675.91 | 14949.97 | 1.66591413 | 21.68 | 15.67 | 0.00862974 | 43718.3 | 12.89 | 12.10 | 0.00845716 | 34308.5 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3454.354 | 3454.354 | 0.149005 | 0.00003022 | 98.685 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.384115 | 1.66591413 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 1.9740 | 2.013683 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 3454.35 | 3454.35 | 1.0000 | 0.17934181 | 0.149005 | 21.11 | 14.93 | 0.00804907 | 41659.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.03021712 | 60.00 | 32.22 | 27.78 | 0.000 | 3454.35 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.11 | 0.00804907 | 21.11 | 0.00804907 | 51.6522 | 3454.35 | 0.00 | 3723.92 | 3723.92 | 0.17934181 | 16.60 | 13.20 | 0.00804907 | 37059.0 | 36.96 | 20.30 | 0.00804907 | 57823.4 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8926.151 | 8926.151 | 1.199787 | 0.00007809 | 190.187 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 5.1008 | 5.203416 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 20:20:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 20:20:00 | Sensible | 8926.15 | 8926.15 | 1.0000 | 1.44405813 | 1.199787 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.07808189 | 60.00 | 32.22 | 27.78 | 0.000 | 8926.15 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00803530 | 21.00 | 0.00803530 | 51.9179 | 2593.85 | 0.00 | 8975.95 | 8975.95 | 1.44405813 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.70 | 15.48 | 0.00800000 | 43150.5 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9207.086 | 9207.086 | 1.255337 | 0.00008055 | 195.965 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 5.2613 | 5.367184 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | Sensible | 9207.09 | 9207.09 | 1.0000 | 1.51091726 | 1.255337 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.08053939 | 60.00 | 32.22 | 27.78 | 0.000 | 9207.09 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00803556 | 21.00 | 0.00803556 | 51.9196 | 2581.62 | 0.00 | 9258.47 | 9258.47 | 1.51091726 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.61 | 15.45 | 0.00800000 | 43062.4 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6144.832 | 6144.832 | 1.164351 | 0.00005376 | 128.140 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 3.5114 | 3.582072 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 6144.83 | 6144.83 | 1.0000 | 1.40140672 | 1.164351 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.05375219 | 60.00 | 32.22 | 27.78 | 0.000 | 6144.83 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 6179.37 | 6179.37 | 1.40140672 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |||
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5086.260 | 5086.260 | 0.432306 | 0.00004450 | 113.330 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 2.9065 | 2.964987 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | Sensible | 5086.26 | 5086.26 | 1.0000 | 0.52032159 | 0.432306 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.04449228 | 60.00 | 32.22 | 27.78 | 0.000 | 5086.26 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00802883 | 21.00 | 0.00802883 | 51.8767 | 2804.65 | 0.00 | 5113.86 | 5113.86 | 0.52032159 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.24 | 16.75 | 0.00800000 | 46763.0 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 741326.080 | -999.000 | 22.105898 | 0.02647845 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8737 | 1004.8586 | 1.2036 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.105898 | 26.60654787 | 4197.9300 | 999.8980 | 37.53182385 | 13.37 | 6.70 | 6.67 | 1050898.32 | 70.5421 | 70.542132 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | Sensible | 741326.08 | 619988.11 | 1.0000 | 26.60654787 | 22.105898 | 33.91 | 20.98 | 0.01023895 | 60329.0 | 10.98 | 10.98 | 0.00850000 | 32466.5 | 26.47574884 | 6.70 | 13.37 | 6.67 | 49531.328 | 691794.75 | 42.80 | 0.01078182 | 23.86 | 11.66146000 | 52.7527 | 23.99 | 0.00963283 | 23.99 | 0.00961384 | 51.6595 | 303909.58 | 0.00 | 742267.38 | 605764.03 | 26.60654787 | 33.91 | 20.99 | 0.01023895 | 60329.0 | 11.68 | 11.33 | 0.00820520 | 32431.1 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 32082.982 | 32082.982 | 6.631769 | 0.00028068 | 614.408 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.105898 | 26.60654787 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 18.3335 | 18.702472 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | Sensible | 32082.98 | 32082.98 | 1.0000 | 7.98196436 | 6.631769 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 0.28064729 | 60.00 | 32.22 | 27.78 | 0.000 | 32082.98 | 12.70 | 0.00915345 | 12.70 | 11.66146000 | 175.8424 | 17.36 | 0.00799123 | 22.04 | 0.00731202 | 44.3791 | 22208.08 | 0.00 | 36793.34 | 36793.34 | 7.98196436 | 2.80 | 2.80 | 0.00915345 | 25753.4 | 7.31 | 7.31 | 0.00915345 | 30363.0 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 92321.212 | -999.000 | 2.051317 | 0.00329750 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8829 | 1004.8586 | 1.2036 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.46886833 | 4197.9300 | 999.8980 | 37.53182385 | 13.37 | 6.70 | 6.67 | 1050898.32 | 8.7850 | 8.784980 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | Sensible | 92321.21 | 77917.60 | 1.0000 | 2.46895513 | 2.051317 | 42.80 | 23.86 | 0.01078182 | 70829.7 | 11.93 | 11.73 | 0.00850000 | 33436.8 | 3.29716340 | 6.70 | 13.37 | 6.67 | 2195.006 | 90126.21 | 42.80 | 0.01078182 | 23.86 | 2.05124512 | 99.9965 | 21.11 | 0.00860979 | 21.11 | 0.00861493 | 55.2352 | 194419.14 | 0.00 | 92413.81 | 77447.65 | 2.46895513 | 42.80 | 23.87 | 0.01078182 | 70829.7 | 12.19 | 11.73 | 0.00837980 | 33399.3 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 2977.141 | 2977.141 | 0.615395 | 0.00002605 | 57.014 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.46886833 | 4197.9300 | 999.8980 | 1.50058927 | 54.44 | 82.22 | 27.78 | 174996.46 | 1.7013 | 1.735496 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 2977.14 | 2977.14 | 1.0000 | 0.74068654 | 0.615395 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 0.02604267 | 60.00 | 32.22 | 27.78 | 0.000 | 2977.14 | 12.70 | 0.00915345 | 12.70 | 2.05124512 | 333.3216 | 21.11 | 0.00805816 | 21.11 | 0.00805772 | 51.7071 | 40708.64 | 0.00 | 3414.24 | 3414.24 | 0.74068654 | 2.80 | 2.80 | 0.00915345 | 25753.4 | 7.31 | 7.31 | 0.00915345 | 30363.0 | |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 71441.156 | 52580.691 | 4.903586 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 1.2036 | SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 4.903586 | 5.90193210 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 75921.46 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 75921.46 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 56448.486 | 41546.086 | 3.872570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 1.2036 | SWHSYS1 HPWH FAN | Fan:SystemModel | 3.872570 | 4.66100528 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 54370.95 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54370.95 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 4059.67 | 3098.17 | 0.00 |
RETAIL_1_FLR_1 | 5250.17 | 2694.17 | 0.00 |
RETAIL_2_FLR_1 | 5672.83 | 1788.50 | 1.67 |
MECH_FLR_1 | 4068.17 | 3535.17 | 0.00 |
STORAGE_FLR_1 | 3793.17 | 3931.50 | 0.00 |
LAUNDRY_FLR_1 | 8559.67 | 3880.50 | 3837.33 |
CAFE_FLR_1 | 7622.67 | 3095.83 | 2561.83 |
LOBBY_FLR_1 | 7141.67 | 2465.50 | 1926.67 |
ROOM_1_FLR_3 | 135.50 | 7380.33 | 0.83 |
ROOM_2_FLR_3 | 159.50 | 7472.00 | 37.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 28.17 | 8757.33 | 28.17 |
ROOM_5_FLR_3 | 66.83 | 7325.50 | 0.17 |
ROOM_6_FLR_3 | 163.83 | 7339.17 | 39.17 |
CORRIDOR_FLR_3 | 3453.00 | 4388.00 | 260.50 |
ROOM_1_FLR_6 | 495.33 | 7165.17 | 13.67 |
ROOM_2_FLR_6 | 524.00 | 7261.83 | 104.67 |
ROOM_3_MULT9_FLR_6 | 83.33 | 7271.33 | 4.33 |
BANQUET_FLR_6 | 8444.67 | 2195.00 | 2153.33 |
DINING_FLR_6 | 8680.50 | 1963.50 | 1963.50 |
KITCHEN_FLR_6 | 8758.83 | 7211.17 | 7211.17 |
CORRIDOR_FLR_6 | 4214.50 | 3733.83 | 0.00 |
Facility | 8760.00 | 8760.00 | 8359.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 19.83 | 0.00 | 19.83 |
ROOM_2_FLR_3 | 0.00 | 19.83 | 0.00 | 19.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 27.00 | 0.00 | 27.00 |
ROOM_5_FLR_3 | 0.00 | 18.00 | 0.00 | 18.00 |
ROOM_6_FLR_3 | 0.00 | 25.83 | 0.00 | 25.83 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 22.83 | 0.00 | 22.83 |
ROOM_2_FLR_6 | 0.00 | 22.00 | 0.00 | 22.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 16.67 | 0.00 | 16.67 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 46.17 | 0.00 | 46.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 0.872 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.235 | 0.032 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.303 | 0.011 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.600 | 0.012 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.555 | 0.012 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 19.056 | 0.035 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.55 | 142.30 | 748.35 | 3.364 | 0.026 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.05 | 422.44 | 5183.56 | 1.624 | 0.011 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.358 | 0.042 | 0.000 | 0.047 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.358 | 0.042 | 0.000 | 0.050 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.407 | 0.019 | 0.000 | 0.079 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.358 | 0.042 | 0.000 | 0.047 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.358 | 0.042 | 0.000 | 0.050 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.470 | 0.005 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.358 | 0.042 | 0.000 | 0.055 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.358 | 0.042 | 0.000 | 0.057 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.407 | 0.034 | 0.000 | 0.088 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.409 | 0.012 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.699 | 0.012 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 18.211 | 0.035 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.087 | 0.009 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 0.519 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.530 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 0.968 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.496 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.442 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 10.442 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.55 | 142.30 | 748.35 | 2.675 | 0.000 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.05 | 422.44 | 5183.56 | 1.184 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.000 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.322 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 3.579 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 3.759 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 7.885 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.735 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.78 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.55 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.05 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.96 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.96 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.11 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 35765082.27 | 0.00 | 35765082.27 | 0.00 | 35765082.27 | 26946214.98 | 650.39 | 86.70 | 8022.91 | 0.00 |
RETAIL_1_FLR_1 | 5049162.94 | 0.00 | 5049162.94 | 73411.88 | 5122574.82 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3402267.58 | 0.00 | 3402267.58 | 28337.08 | 3430604.66 | 2892943.94 | 124.29 | 72.93 | 8562.78 | 0.00 |
MECH_FLR_1 | 3320233.70 | 0.00 | 3320233.70 | 66972.02 | 3387205.72 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1771648.47 | 0.00 | 1771648.47 | 38639.16 | 1810287.64 | 1821682.01 | 5718.72 | 262.42 | 2778.86 | 0.00 |
LAUNDRY_FLR_1 | 50149867.53 | 0.00 | 50149867.53 | 91446.87 | 50241314.39 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 21337777.22 | 0.00 | 21337777.22 | 162281.11 | 21500058.32 | 21330615.53 | 4715.47 | 416.54 | 3627.99 | 0.00 |
LOBBY_FLR_1 | 71324144.72 | 0.00 | 71324144.72 | 463674.19 | 71787818.91 | 59728886.00 | 148.51 | 70.15 | 8541.34 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 48238.71 | 1508395.43 | 42610.14 | 1551005.57 | 1946875.62 | 2190.00 | 5847.33 | 722.67 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 50834.44 | 1510820.08 | 42606.89 | 1553426.97 | 1946647.51 | 2190.00 | 5847.33 | 722.67 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 0.00 | 1099911.97 | 11888.71 | 1111800.68 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.00 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 50562.44 | 19854391.74 | 11891.96 | 19866283.70 | 26405105.73 | 2190.00 | 5927.61 | 642.39 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 48393.99 | 1508550.71 | 42610.14 | 1551160.85 | 1946875.62 | 2190.00 | 5847.33 | 722.67 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 50888.26 | 1510873.90 | 42606.89 | 1553480.79 | 1946647.51 | 2190.00 | 5847.50 | 722.50 | 0.00 |
CORRIDOR_FLR_3 | 18956449.14 | 0.00 | 18956449.14 | 51524.23 | 19007973.38 | 14972100.18 | 202.61 | 120.58 | 8436.81 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 56667.49 | 421706.67 | 42618.57 | 464325.24 | 486718.90 | 2046.95 | 5853.19 | 859.86 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 58423.91 | 423420.32 | 42615.32 | 466035.64 | 486661.88 | 2054.59 | 5851.91 | 853.50 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 56892.28 | 2402082.60 | 21805.15 | 2423887.75 | 3126920.42 | 2190.00 | 5847.17 | 722.83 | 0.00 |
BANQUET_FLR_6 | 37727880.34 | 0.00 | 37727880.34 | 104063.84 | 37831944.18 | 37458366.31 | 4183.98 | 1670.58 | 2905.44 | 0.00 |
DINING_FLR_6 | 40220859.09 | 0.00 | 40220859.09 | 104063.84 | 40324922.93 | 37458366.31 | 1254.65 | 690.84 | 6814.51 | 0.00 |
KITCHEN_FLR_6 | 48587128.74 | 0.00 | 48587128.74 | 93161.26 | 48680290.00 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 11605515.48 | 0.00 | 11605515.48 | 91181.04 | 11696696.53 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.20E+10 | 5263289.16 | 0.20E+10 | 4293876.34 | 0.20E+10 | 0.43E+10 | 8760.00 | 7395.04 | 8760.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.1341 | 0.0000 | 1.1341 | 0.0000 | 1.1341 | 0.8545 | 650.39 | 86.70 | 8022.91 |
RETAIL_1_FLR_1 | 0.1601 | 0.0000 | 0.1601 | 0.0023 | 0.1624 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1079 | 0.0000 | 0.1079 | 0.0009 | 0.1088 | 0.0917 | 124.29 | 72.93 | 8562.78 |
MECH_FLR_1 | 0.1053 | 0.0000 | 0.1053 | 0.0021 | 0.1074 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0562 | 0.0000 | 0.0562 | 0.0012 | 0.0574 | 0.0578 | 5718.72 | 262.42 | 2778.86 |
LAUNDRY_FLR_1 | 1.5902 | 0.0000 | 1.5902 | 0.0029 | 1.5931 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.6766 | 0.0000 | 0.6766 | 0.0051 | 0.6818 | 0.6764 | 4715.47 | 416.54 | 3627.99 |
LOBBY_FLR_1 | 2.2617 | 0.0000 | 2.2617 | 0.0147 | 2.2764 | 1.8940 | 148.51 | 70.15 | 8541.34 |
ROOM_1_FLR_3 | 0.0463 | 0.0015 | 0.0478 | 0.0014 | 0.0492 | 0.0617 | 2190.00 | 5847.33 | 722.67 |
ROOM_2_FLR_3 | 0.0463 | 0.0016 | 0.0479 | 0.0014 | 0.0493 | 0.0617 | 2190.00 | 5847.33 | 722.67 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0016 | 0.6296 | 0.0004 | 0.6300 | 0.8373 | 2190.00 | 5927.61 | 642.39 |
ROOM_5_FLR_3 | 0.0463 | 0.0015 | 0.0478 | 0.0014 | 0.0492 | 0.0617 | 2190.00 | 5847.33 | 722.67 |
ROOM_6_FLR_3 | 0.0463 | 0.0016 | 0.0479 | 0.0014 | 0.0493 | 0.0617 | 2190.00 | 5847.50 | 722.50 |
CORRIDOR_FLR_3 | 0.6011 | 0.0000 | 0.6011 | 0.0016 | 0.6027 | 0.4748 | 202.61 | 120.58 | 8436.81 |
ROOM_1_FLR_6 | 0.0116 | 0.0018 | 0.0134 | 0.0014 | 0.0147 | 0.0154 | 2046.95 | 5853.19 | 859.86 |
ROOM_2_FLR_6 | 0.0116 | 0.0019 | 0.0134 | 0.0014 | 0.0148 | 0.0154 | 2054.59 | 5851.91 | 853.50 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0018 | 0.0762 | 0.0007 | 0.0769 | 0.0992 | 2190.00 | 5847.17 | 722.83 |
BANQUET_FLR_6 | 1.1963 | 0.0000 | 1.1963 | 0.0033 | 1.1996 | 1.1878 | 4183.98 | 1670.58 | 2905.44 |
DINING_FLR_6 | 1.2754 | 0.0000 | 1.2754 | 0.0033 | 1.2787 | 1.1878 | 1254.65 | 690.84 | 6814.51 |
KITCHEN_FLR_6 | 1.5407 | 0.0000 | 1.5407 | 0.0030 | 1.5436 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3680 | 0.0000 | 0.3680 | 0.0029 | 0.3709 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 62.0363 | 0.1669 | 62.2032 | 0.1075 | 62.3107 | 73.9670 | 8760.00 | 7395.04 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.51E+09 | 0.00 | 0.51E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 43197387.25 | 420901.53 | 43618288.78 | 64690340.46 | 8756.00 | 3.64 | 0.36 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 16.0417 | 0.0000 | 16.0417 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.3698 | 0.0133 | 1.3831 | 2.0513 | 8756.00 | 3.64 | 0.36 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 16.0417 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.7302 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1363 |
Defaulted Fields | 1208 |
Fields with Defaults | 4115 |
Autosized Fields | 353 |
Autosizable Fields | 407 |
Autocalculated Fields | 289 |
Autocalculatable Fields | 549 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 8561.93 | 86562.71 | 20-JAN-03:50 | 555288.18 | 16-AUG-19:40 |
Electricity:Building | 2339.31 | 31015.39 | 02-JAN-02:10 | 138695.41 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 256.48 | 3058.02 | 02-JAN-02:10 | 18903.76 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2332.22 | 30874.25 | 02-JAN-02:10 | 138454.08 | 02-JAN-20:10 |
InteriorLights:Electricity | 604.08 | 5592.07 | 02-JAN-02:10 | 50471.22 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 113.37 | 1030.12 | 02-JAN-02:10 | 9271.23 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 604.08 | 5592.07 | 02-JAN-02:10 | 50471.22 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 604.08 | 5592.07 | 02-JAN-02:10 | 50471.22 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 113.37 | 1030.12 | 02-JAN-02:10 | 9271.23 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 604.08 | 5592.07 | 02-JAN-02:10 | 50471.22 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 16.45 | 201.26 | 02-JAN-02:10 | 1197.92 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 19.05 | 233.06 | 02-JAN-02:10 | 1387.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.46 | 67.94 | 02-JAN-02:10 | 394.77 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.87 | 16.96 | 02-JAN-02:10 | 152.61 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.87 | 16.96 | 02-JAN-02:10 | 152.61 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.84 | 1007.22 | 02-JAN-02:10 | 4973.49 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 27.43 | 378.04 | 02-JAN-02:10 | 2538.73 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 13.08 | 76.92 | 01-JAN-13:10 | 1573.46 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 13.08 | 76.92 | 01-JAN-13:10 | 1573.46 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 272.09 | 3294.23 | 02-JAN-02:10 | 20674.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 123.10 | 1182.82 | 02-JAN-02:10 | 10645.38 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 123.10 | 1182.82 | 02-JAN-02:10 | 10645.38 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 18.46 | 262.96 | 01-JAN-02:10 | 1214.21 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 18.46 | 262.93 | 01-JAN-02:10 | 1214.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 302.44 | 4545.27 | 01-JAN-02:10 | 20822.55 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 73.68 | 623.81 | 01-JAN-02:10 | 5671.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 73.68 | 623.81 | 01-JAN-02:10 | 5671.40 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 302.52 | 4546.52 | 01-JAN-02:10 | 20828.25 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 73.70 | 623.98 | 01-JAN-02:10 | 5672.95 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 73.70 | 623.98 | 01-JAN-02:10 | 5672.95 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 18.46 | 262.96 | 01-JAN-02:10 | 1214.21 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 18.46 | 262.93 | 01-JAN-02:10 | 1214.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.62 | 65.74 | 01-JAN-02:10 | 303.55 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.74 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.74 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.62 | 65.73 | 01-JAN-02:10 | 303.52 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.73 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.73 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 35.82 | 538.40 | 01-JAN-02:10 | 2466.50 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 8.73 | 73.89 | 01-JAN-02:10 | 671.80 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 8.73 | 73.89 | 01-JAN-02:10 | 671.80 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 204.31 | 2556.31 | 02-JAN-02:10 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.45 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.45 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 204.31 | 2556.31 | 02-JAN-02:10 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.45 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.45 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 444.45 | 5944.83 | 02-JAN-02:10 | 18636.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 44.44 | 751.55 | 22-MAR-22:30 | 2791.07 | 20-FEB-11:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 4466.89 | 11566.56 | 01-JAN-03:50 | 348591.18 | 10-AUG-18:20 |
LowTempRefrigeration:Refrigeration:Electricity | 15.86 | 0.00 | 01-JAN-11:10 | 1307.00 | 30-JUL-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 21.48 | 631.01 | 01-JAN-04:10 | 717.12 | 15-DEC-14:10 |
WaterSystems:Electricity | 444.97 | 1086.56 | 19-SEP-00:50 | 43956.31 | 31-JAN-21:50 |
Electricity:HVAC | 962.05 | 21068.40 | 01-JAN-02:30 | 57483.88 | 16-AUG-21:10 |
Fans:Electricity | 645.34 | 12220.30 | 01-JAN-03:50 | 46707.89 | 16-AUG-21:10 |
General:Fans:Electricity | 645.34 | 12220.30 | 01-JAN-03:50 | 46707.89 | 16-AUG-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ExteriorEquipment:Electricity | 641.49 | 9451.24 | 02-JAN-02:20 | 39155.93 | 09-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 22.46 | 386.43 | 03-JAN-04:10 | 1283.34 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 8561.93 | 86562.71 | 20-JAN-03:50 | 555288.18 | 16-AUG-19:40 |
ElectricityPurchased:Plant | 8561.93 | 86562.71 | 20-JAN-03:50 | 555288.18 | 16-AUG-19:40 |
Cogeneration:ElectricityPurchased | 8561.93 | 86562.71 | 20-JAN-03:50 | 555288.18 | 16-AUG-19:40 |
General:Cogeneration:ElectricityPurchased | 8561.93 | 86562.71 | 20-JAN-03:50 | 555288.18 | 16-AUG-19:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 8561.93 | 86562.71 | 20-JAN-03:50 | 555288.18 | 16-AUG-19:40 |
ElectricityNet:Plant | 8561.93 | 86562.71 | 20-JAN-03:50 | 555288.18 | 16-AUG-19:40 |
Cogeneration:ElectricityNet | 8561.93 | 86562.71 | 20-JAN-03:50 | 555288.18 | 16-AUG-19:40 |
General:Cogeneration:ElectricityNet | 8561.93 | 86562.71 | 20-JAN-03:50 | 555288.18 | 16-AUG-19:40 |
ExteriorLights:Electricity | 174.66 | 0.00 | 01-JAN-07:10 | 11096.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 174.66 | 0.00 | 01-JAN-07:10 | 11096.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 294.25 | 8417.13 | 01-JAN-02:10 | 9938.94 | 02-APR-08:40 |
General:HeatRecovery:Electricity | 294.25 | 8417.13 | 01-JAN-02:10 | 9938.94 | 02-APR-08:40 |
Water Heater:WaterSystems:Electricity | 90.74 | 1086.56 | 19-SEP-00:50 | 4738.77 | 13-JUL-18:10 |
Water Heater Parasitic:WaterSystems:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 3794.93 | 3132.02 | 19-JAN-08:20 | 308464.81 | 10-AUG-18:10 |
General:Cooling:Electricity | 3794.93 | 3132.02 | 19-JAN-08:20 | 308464.81 | 10-AUG-18:10 |
Pumps:Electricity | 189.65 | 5352.83 | 19-JAN-08:20 | 9147.60 | 19-JUL-18:10 |
General:Pumps:Electricity | 189.65 | 5352.83 | 19-JAN-08:20 | 9147.60 | 19-JUL-18:10 |
WIRED_LTG_ELECTRICITY | 21.26 | 0.00 | 01-JAN-00:10 | 1776.59 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2387.76 | 29270.80 | 04-JAN-02:10 | 153255.15 | 12-JAN-18:40 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 598.92 | 15908.90 | 27-MAR-10:10 | 53890.54 | 17-JAN-23:00 |
WaterSystems:NaturalGas | 597.02 | 15908.90 | 01-JAN-16:10 | 49007.37 | 12-JAN-22:50 |
Water Heater:WaterSystems:NaturalGas | 597.02 | 15908.90 | 01-JAN-16:10 | 49007.37 | 12-JAN-22:50 |
Heating:NaturalGas | 1.90 | 0.00 | 01-JAN-09:50 | 24078.49 | 21-JAN-07:10 |
Boiler:Heating:NaturalGas | 1.90 | 0.00 | 01-JAN-09:50 | 24078.49 | 21-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 10982.32 | 4729.07 | 20-JAN-08:20 | 807430.98 | 19-JUL-18:10 |
PlantLoopCoolingDemand:HVAC | 10982.32 | 4729.07 | 20-JAN-08:20 | 807430.98 | 19-JUL-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 10982.32 | 4729.07 | 20-JAN-08:20 | 807430.98 | 19-JUL-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 23-FEB-21:20 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 23-FEB-21:20 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 23-FEB-21:20 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 23-FEB-21:20 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 23-FEB-21:20 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 23-FEB-21:20 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 31-JAN-07:30 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 31-JAN-07:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 49120.65 | 185999.29 | 01-JAN-02:30 | 3549841.67 | 11-AUG-18:20 |
EnergyTransfer:Building | 6887.25 | 118946.92 | 01-JAN-06:00 | 395975.70 | 16-AUG-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 751.19 | 12066.69 | 01-JAN-04:00 | 35743.55 | 30-JUL-10:40 |
Refrigeration:EnergyTransfer | 189.29 | 4264.29 | 20-JAN-23:10 | 10377.93 | 15-DEC-07:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 94.65 | 2132.15 | 20-JAN-23:10 | 5188.97 | 15-DEC-07:30 |
General:Refrigeration:EnergyTransfer | 94.65 | 2132.15 | 20-JAN-23:10 | 5188.97 | 15-DEC-07:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 94.65 | 2132.15 | 20-JAN-23:10 | 5188.97 | 15-DEC-07:30 |
EnergyTransfer:Plant | 26674.29 | 39417.88 | 01-JAN-04:00 | 1937727.67 | 11-AUG-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.76 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 72.89 | 1961.45 | 01-JAN-04:10 | 2562.52 | 15-DEC-14:10 |
EnergyTransfer:HVAC | 15559.11 | 8956.91 | 04-JAN-08:50 | 1273203.14 | 30-AUG-20:00 |
CoolingCoils:EnergyTransfer | 12100.55 | 5105.54 | 20-JAN-08:30 | 913297.61 | 30-AUG-20:40 |
EnergyTransfer:Zone:BASEMENT | 464.09 | 10824.18 | 24-APR-14:00 | 24129.61 | 03-NOV-21:00 |
Heating:EnergyTransfer | 0.55 | 0.00 | 01-JAN-00:10 | 5805.09 | 09-JAN-09:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 0.55 | 0.00 | 01-JAN-00:10 | 5805.09 | 09-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 6792.05 | 115678.59 | 01-JAN-06:00 | 392372.30 | 16-AUG-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 464.09 | 10824.18 | 24-APR-14:00 | 24129.61 | 03-NOV-21:00 |
General:Cooling:EnergyTransfer | 6792.05 | 115678.59 | 01-JAN-06:00 | 392372.30 | 16-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 464.09 | 10824.18 | 24-APR-14:00 | 24129.61 | 03-NOV-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 63.17 | 841.93 | 01-JAN-06:00 | 3407.23 | 26-SEP-13:00 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 63.17 | 841.93 | 01-JAN-06:00 | 3407.23 | 26-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 63.17 | 841.93 | 01-JAN-06:00 | 3407.23 | 26-SEP-13:00 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 45.22 | 1010.11 | 01-JAN-16:00 | 2473.64 | 21-JUL-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 45.22 | 1010.11 | 01-JAN-16:00 | 2473.64 | 21-JUL-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 45.22 | 1010.11 | 01-JAN-16:00 | 2473.64 | 21-JUL-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 43.27 | 940.21 | 01-JAN-16:00 | 2639.24 | 21-JUL-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 43.27 | 940.21 | 01-JAN-16:00 | 2639.24 | 21-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 43.27 | 940.21 | 01-JAN-16:00 | 2639.24 | 21-JUL-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 22.76 | 508.87 | 01-JAN-06:00 | 1279.12 | 21-JUL-21:00 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 22.76 | 508.87 | 01-JAN-06:00 | 1279.12 | 21-JUL-21:00 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 22.76 | 508.87 | 01-JAN-06:00 | 1279.12 | 21-JUL-21:00 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 632.74 | 10981.91 | 02-JAN-05:00 | 39659.89 | 21-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 632.74 | 10981.91 | 02-JAN-05:00 | 39659.89 | 21-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 632.74 | 10981.91 | 02-JAN-05:00 | 39659.89 | 21-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 283.55 | 5608.08 | 09-JAN-09:30 | 14066.03 | 21-JUL-21:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 283.55 | 5608.08 | 09-JAN-09:30 | 14066.03 | 21-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 283.55 | 5608.08 | 09-JAN-09:30 | 14066.03 | 21-JUL-21:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 960.40 | 21059.75 | 20-FEB-16:00 | 48751.80 | 21-JUL-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 960.40 | 21059.75 | 20-FEB-16:00 | 48751.80 | 21-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 960.40 | 21059.75 | 20-FEB-16:00 | 48751.80 | 21-JUL-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 119.43 | 0.00 | 01-JAN-08:10 | 11429.37 | 06-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.06 | 0.00 | 01-JAN-00:10 | 619.47 | 19-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.06 | 0.00 | 01-JAN-00:10 | 619.47 | 19-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 119.37 | 0.00 | 01-JAN-08:10 | 11429.37 | 06-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 119.37 | 0.00 | 01-JAN-08:10 | 11429.37 | 06-AUG-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 108.09 | 0.00 | 01-JAN-08:10 | 11245.60 | 21-JUL-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 0.05 | 0.00 | 01-JAN-00:10 | 594.80 | 19-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 0.05 | 0.00 | 01-JAN-00:10 | 594.80 | 19-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 108.04 | 0.00 | 01-JAN-08:10 | 11245.60 | 21-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 108.04 | 0.00 | 01-JAN-08:10 | 11245.60 | 21-JUL-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 627.85 | 0.00 | 01-JAN-01:50 | 40618.16 | 09-OCT-13:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 627.85 | 0.00 | 01-JAN-01:50 | 40618.16 | 09-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 627.85 | 0.00 | 01-JAN-01:50 | 40618.16 | 09-OCT-13:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 840.08 | 0.00 | 01-JAN-08:10 | 79398.80 | 21-JUL-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.31 | 0.00 | 01-JAN-00:10 | 3850.48 | 31-JAN-07:30 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.31 | 0.00 | 01-JAN-00:10 | 3850.48 | 31-JAN-07:30 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 839.77 | 0.00 | 01-JAN-08:10 | 79398.80 | 21-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 839.77 | 0.00 | 01-JAN-08:10 | 79398.80 | 21-JUL-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 119.58 | 0.00 | 01-JAN-08:10 | 10497.16 | 21-JUL-15:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.02 | 0.00 | 01-JAN-00:10 | 555.44 | 20-FEB-19:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.02 | 0.00 | 01-JAN-00:10 | 555.44 | 20-FEB-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 119.56 | 0.00 | 01-JAN-08:10 | 10497.16 | 21-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 119.56 | 0.00 | 01-JAN-08:10 | 10497.16 | 21-JUL-15:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 108.12 | 0.00 | 01-JAN-08:10 | 10485.10 | 21-JUL-15:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 0.04 | 0.00 | 01-JAN-00:10 | 577.64 | 13-FEB-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 0.04 | 0.00 | 01-JAN-00:10 | 577.64 | 13-FEB-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 108.09 | 0.00 | 01-JAN-06:00 | 10485.10 | 21-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 108.09 | 0.00 | 01-JAN-06:00 | 10485.10 | 21-JUL-15:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 240.46 | 5256.87 | 02-JAN-07:40 | 12672.30 | 21-JUL-18:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 240.46 | 5256.87 | 02-JAN-07:40 | 12672.30 | 21-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 240.46 | 5256.87 | 02-JAN-07:40 | 12672.30 | 21-JUL-18:20 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 30.60 | 0.00 | 01-JAN-08:10 | 3163.42 | 06-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 156.26 | 20-FEB-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 156.26 | 20-FEB-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 30.59 | 0.00 | 01-JAN-04:10 | 3163.42 | 06-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 30.59 | 0.00 | 01-JAN-04:10 | 3163.42 | 06-AUG-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 27.86 | 0.00 | 01-JAN-08:10 | 3139.63 | 21-JUL-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 156.24 | 16-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 156.24 | 16-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 27.85 | 0.00 | 01-JAN-02:50 | 3139.63 | 21-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 27.85 | 0.00 | 01-JAN-02:50 | 3139.63 | 21-JUL-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 174.20 | 0.00 | 01-JAN-08:10 | 15370.79 | 26-SEP-15:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.03 | 0.00 | 01-JAN-00:10 | 653.24 | 20-FEB-19:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.03 | 0.00 | 01-JAN-00:10 | 653.24 | 20-FEB-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 174.17 | 0.00 | 01-JAN-08:10 | 15370.79 | 26-SEP-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 174.17 | 0.00 | 01-JAN-08:10 | 15370.79 | 26-SEP-15:20 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 521.57 | 10712.08 | 02-JAN-09:30 | 25618.70 | 21-JUL-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 521.57 | 10712.08 | 02-JAN-09:30 | 25618.70 | 21-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 521.57 | 10712.08 | 02-JAN-09:30 | 25618.70 | 21-JUL-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 557.20 | 11707.66 | 19-JAN-10:20 | 26804.53 | 21-JUL-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 557.20 | 11707.66 | 19-JAN-10:20 | 26804.53 | 21-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 557.20 | 11707.66 | 19-JAN-10:20 | 26804.53 | 21-JUL-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 656.54 | 9850.21 | 01-JAN-04:00 | 30660.25 | 30-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 656.54 | 9850.21 | 01-JAN-04:00 | 30660.25 | 30-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 145.79 | 2114.33 | 02-JAN-07:10 | 8199.62 | 21-JUL-12:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 145.79 | 2114.33 | 02-JAN-07:10 | 8199.62 | 21-JUL-12:20 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 145.79 | 2114.33 | 02-JAN-07:10 | 8199.62 | 21-JUL-12:20 |
PlantLoopHeatingDemand:Facility | 1955.19 | 5317.87 | 14-JUL-01:20 | 199347.63 | 30-NOV-21:50 |
PlantLoopHeatingDemand:Plant | 1953.97 | 5317.87 | 14-JUL-01:20 | 199347.63 | 30-NOV-21:50 |
WaterSystems:PlantLoopHeatingDemand | 1953.97 | 5317.87 | 14-JUL-01:20 | 199347.63 | 30-NOV-21:50 |
General:WaterSystems:PlantLoopHeatingDemand | 496.96 | 5314.34 | 14-JUL-02:00 | 40005.14 | 12-JAN-07:10 |
HeatingCoils:EnergyTransfer | 1.22 | 0.00 | 01-JAN-09:50 | 22792.48 | 21-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 1.22 | 0.00 | 01-JAN-09:50 | 22792.48 | 21-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 1.22 | 0.00 | 01-JAN-09:50 | 22792.48 | 21-JAN-07:10 |
HeatRecoveryForHeating:EnergyTransfer | 44.25 | 0.00 | 01-JAN-00:10 | 116121.32 | 25-APR-05:00 |
HeatRecoveryForCooling:EnergyTransfer | 3413.10 | 0.00 | 01-JAN-00:10 | 417376.69 | 20-JUL-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 1457.01 | 0.00 | 01-JAN-00:10 | 168810.51 | 30-NOV-21:50 |
WaterSystems:EnergyTransfer | 496.96 | 5314.34 | 14-JUL-02:00 | 40005.14 | 12-JAN-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 496.96 | 5314.34 | 14-JUL-02:00 | 40005.14 | 12-JAN-07:10 |
Boilers:EnergyTransfer | 1.21 | 0.00 | 01-JAN-09:50 | 14465.23 | 21-JAN-07:10 |
Chillers:EnergyTransfer | 11143.27 | 9933.70 | 20-JAN-08:20 | 814717.13 | 19-JUL-18:10 |
HeatRejection:EnergyTransfer | 14938.20 | 13074.55 | 20-JAN-08:20 | 1106168.69 | 11-AUG-18:10 |
General:HeatRejection:EnergyTransfer | 14938.20 | 13074.55 | 20-JAN-08:20 | 1106168.69 | 11-AUG-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -464.089 | 0.000 | 0.000 | 137.289 | 113.371 | 143.105 | 0.000 | 0.000 | 0.000 | 70.325 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.000 | -63.173 | 0.000 | 0.000 | 14.349 | 6.265 | 10.186 | 22.229 | 0.000 | 0.471 | 11.927 | 0.000 | -2.184 | 0.000 | -0.070 | -0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -45.220 | 0.000 | 0.000 | 16.030 | 7.255 | 11.795 | 0.000 | 0.000 | 0.180 | 10.001 | 0.000 | 0.000 | 0.000 | -0.040 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -43.271 | 0.000 | 0.000 | 3.441 | 8.366 | 12.471 | 0.000 | 0.000 | 0.427 | 18.648 | 0.000 | 0.000 | 0.000 | -0.082 | 0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.000 | -22.758 | 0.000 | 0.000 | 2.660 | 1.866 | 3.598 | 0.000 | 0.000 | 0.248 | 14.431 | 0.000 | 0.000 | 0.000 | -0.045 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -632.749 | 0.000 | 0.000 | 11.179 | 4.900 | 658.131 | 0.000 | 0.000 | 0.630 | 0.000 | 0.000 | 0.000 | 0.000 | -0.121 | -41.971 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -283.557 | 0.000 | 0.000 | 181.445 | 13.085 | 14.341 | 62.004 | 0.000 | 1.026 | 19.255 | 0.000 | -7.366 | 0.000 | -0.233 | -0.001 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -960.413 | 0.000 | 0.000 | 535.710 | 123.096 | 148.998 | 83.025 | 0.000 | 2.935 | 77.142 | 0.000 | -9.779 | 0.000 | -0.713 | -0.001 |
ROOM_1_FLR_3 | 0.087 | -104.789 | 0.000 | -14.609 | 0.000 | 0.000 | 9.625 | 6.171 | 12.292 | 54.835 | 0.000 | 1.480 | 39.244 | 0.000 | -3.845 | 0.000 | -0.490 | -0.000 |
ROOM_2_FLR_3 | 0.087 | -93.058 | 0.000 | -15.013 | 0.000 | 0.000 | 9.534 | 6.170 | 12.291 | 48.542 | 0.000 | 1.379 | 34.973 | 0.000 | -4.160 | 0.000 | -0.744 | -0.001 |
ROOM_3_MULT19_FLR_3 | 0.000 | -609.337 | 0.000 | -18.514 | 0.000 | 0.000 | 0.000 | 73.685 | 228.754 | 237.718 | 0.000 | 3.710 | 137.012 | 0.000 | -50.318 | 0.000 | -2.709 | -0.002 |
ROOM_4_MULT19_FLR_3 | 0.759 | -636.968 | 0.000 | -203.225 | 0.000 | 0.000 | 181.319 | 73.705 | 228.817 | 211.156 | 0.000 | 7.751 | 169.448 | 0.000 | -21.239 | 0.000 | -11.523 | -0.006 |
ROOM_5_FLR_3 | 0.044 | -104.963 | 0.000 | -14.611 | 0.000 | 0.000 | 9.623 | 6.171 | 12.292 | 54.613 | 0.000 | 1.479 | 39.536 | 0.000 | -3.679 | 0.000 | -0.505 | -0.001 |
ROOM_6_FLR_3 | 0.069 | -93.095 | 0.000 | -15.025 | 0.000 | 0.000 | 9.533 | 6.170 | 12.291 | 48.166 | 0.000 | 1.380 | 35.122 | 0.000 | -3.867 | 0.000 | -0.743 | -0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.000 | -240.459 | 0.000 | 0.000 | 109.724 | 56.739 | 0.000 | 54.308 | 0.000 | 1.321 | 24.302 | 0.000 | -5.699 | 0.000 | -0.234 | -0.000 |
ROOM_1_FLR_6 | 0.046 | -26.959 | 0.000 | -3.653 | 0.000 | 0.000 | 2.407 | 1.543 | 3.073 | 13.682 | 0.000 | 0.371 | 10.550 | 0.000 | -0.926 | 0.000 | -0.133 | -0.000 |
ROOM_2_FLR_6 | 0.048 | -24.130 | 0.000 | -3.746 | 0.000 | 0.000 | 2.386 | 1.543 | 3.073 | 12.131 | 0.000 | 0.343 | 9.554 | 0.000 | -1.003 | 0.000 | -0.197 | -0.000 |
ROOM_3_MULT9_FLR_6 | 0.056 | -150.719 | 0.000 | -23.468 | 0.000 | 0.000 | 21.652 | 8.728 | 27.097 | 65.127 | 0.000 | 1.842 | 54.997 | 0.000 | -4.220 | 0.000 | -1.092 | -0.001 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -521.575 | 0.000 | 0.000 | 314.579 | 28.449 | 175.857 | 20.430 | 0.000 | 0.633 | 0.000 | 0.000 | -3.928 | 0.000 | -0.173 | -14.273 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -557.202 | 0.000 | 0.000 | 314.249 | 28.449 | 175.857 | 20.048 | 0.000 | 0.631 | 22.284 | 0.000 | -4.141 | 0.000 | -0.175 | -0.000 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -656.532 | 0.000 | 0.000 | 28.129 | 13.339 | 540.650 | 25.853 | 0.000 | 0.565 | 51.228 | 0.000 | -3.079 | 0.000 | -0.152 | -0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.000 | -145.794 | 0.000 | 0.000 | 29.302 | 15.012 | 0.000 | 24.384 | 0.000 | 0.579 | 79.133 | 0.000 | -2.524 | 0.000 | -0.092 | 0.000 |
Total Facility | 1.196 | -1844.020 | 0.000 | -4948.658 | 0.000 | 0.000 | 1944.164 | 604.076 | 2434.967 | 1058.252 | 0.000 | 29.380 | 929.110 | 0.000 | -131.955 | 0.000 | -20.268 | -56.258 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 03-NOV-21:00 | 0.00 | 0.00 | 0.00 | -24130.00 | 0.00 | 0.00 | 5924.42 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 838.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 26-SEP-13:00 | 0.00 | 0.00 | 0.00 | -3408.16 | 0.00 | 0.00 | 150.59 | 142.31 | 252.59 | 3006.51 | 0.00 | 47.42 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -191.26 |
RETAIL_2_FLR_1 | 21-JUL-21:00 | 0.00 | 0.00 | 0.00 | -2473.69 | 0.00 | 0.00 | 697.61 | 527.34 | 752.15 | 0.00 | 0.00 | 16.85 | 479.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 21-JUL-20:00 | 0.00 | 0.00 | 0.00 | -2639.26 | 0.00 | 0.00 | 129.08 | 684.18 | 839.45 | 0.00 | 0.00 | 42.12 | 944.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 21-JUL-21:00 | 0.00 | 0.00 | 0.00 | -1279.16 | 0.00 | 0.00 | 113.48 | 135.66 | 229.41 | 0.00 | 0.00 | 22.97 | 777.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 21-JUL-20:00 | 0.00 | 0.00 | 0.00 | -39659.76 | 0.00 | 0.00 | 408.87 | 400.68 | 44299.38 | 0.00 | 0.00 | 57.52 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5506.69 |
CAFE_FLR_1 | 21-JUL-21:10 | 0.00 | 0.00 | 0.00 | -14068.21 | 0.00 | 0.00 | 8907.74 | 1048.97 | 711.25 | 1787.10 | 0.00 | 94.39 | 1518.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 21-JUL-21:10 | 0.00 | 0.00 | 0.00 | -48757.50 | 0.00 | 0.00 | 26439.78 | 7096.92 | 7389.94 | 2416.30 | 0.00 | 269.65 | 5144.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 16-AUG-18:02 | 0.00 | -11787.32 | 0.00 | -756.82 | 0.00 | 0.00 | 335.49 | 422.72 | 516.26 | 3547.16 | 0.00 | 115.08 | 7607.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 22-JUN-08:51 | 0.00 | -12465.56 | 0.00 | -850.74 | 0.00 | 0.00 | 79.52 | 208.96 | 452.99 | 2684.26 | 0.00 | 64.56 | 9826.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 09-OCT-13:30 | 0.00 | -40616.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1871.60 | 5686.12 | 33977.37 | 0.00 | 363.86 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1282.40 |
ROOM_4_MULT19_FLR_3 | 21-OCT-08:41 | 0.00 | -79991.62 | 0.00 | -10567.93 | 0.00 | 0.00 | 2467.36 | 3176.85 | 12159.85 | 8558.92 | 0.00 | 180.10 | 64016.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 10-AUG-15:02 | 0.00 | -10851.77 | 0.00 | -754.80 | 0.00 | 0.00 | 235.28 | 132.99 | 273.93 | 3987.90 | 0.00 | 121.77 | 6854.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 22-JUN-08:51 | 0.00 | -12043.76 | 0.00 | -943.04 | 0.00 | 0.00 | 72.51 | 208.96 | 452.99 | 5455.08 | 0.00 | 56.72 | 6740.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 21-JUL-18:17 | 0.00 | 0.00 | 0.00 | -12672.64 | 0.00 | 0.00 | 4080.26 | 4124.45 | 0.00 | 2959.64 | 0.00 | 134.15 | 1374.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 21-JUL-18:02 | 0.00 | -3245.60 | 0.00 | -188.20 | 0.00 | 0.00 | 83.87 | 105.68 | 129.07 | 742.96 | 0.00 | 29.91 | 2342.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 22-JUN-08:51 | 0.00 | -3297.17 | 0.00 | -212.68 | 0.00 | 0.00 | 19.84 | 52.24 | 113.25 | 671.26 | 0.00 | 16.06 | 2637.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 18-SEP-15:02 | 0.00 | -15781.46 | 0.00 | -1216.20 | 0.00 | 0.00 | 529.37 | 188.10 | 603.86 | 4616.50 | 0.00 | 90.82 | 10969.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 21-JUL-21:20 | 0.00 | 0.00 | 0.00 | -25623.53 | 0.00 | 0.00 | 15636.36 | 1842.08 | 6747.90 | 950.74 | 0.00 | 58.78 | 387.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 21-JUL-21:20 | 0.00 | 0.00 | 0.00 | -26809.65 | 0.00 | 0.00 | 15635.16 | 1842.08 | 6747.90 | 936.73 | 0.00 | 58.77 | 1588.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 30-JUL-10:50 | 0.00 | 0.00 | 0.00 | -30662.13 | 0.00 | 0.00 | 463.43 | 363.61 | 23951.61 | 3293.36 | 0.00 | 69.90 | 2520.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 21-JUL-12:20 | 0.00 | 0.00 | 0.00 | -8204.12 | 0.00 | 0.00 | 308.44 | 341.02 | 0.00 | 2378.82 | 0.00 | 68.99 | 5106.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-AUG-18:02 | 0.00 | -181296.64 | 0.00 | -230014.90 | 0.00 | 0.00 | 73720.46 | 42059.90 | 121562.63 | 56883.04 | 0.00 | 2694.65 | 114390.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 14-JAN-19:04 | 4208.16 | 592.08 | 0.00 | -592.08 | 0.00 | 0.00 | 283.24 | 474.96 | 516.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -631.87 | 0.00 | -88.97 | -4761.78 |
ROOM_2_FLR_3 | 19-JAN-16:04 | 4163.35 | 610.66 | 0.00 | -610.66 | 0.00 | 0.00 | 235.28 | 132.97 | 273.90 | 2035.78 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -60.31 | -6780.98 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 11-FEB-16:06 | 26204.96 | 8561.25 | 0.00 | -8561.25 | 0.00 | 0.00 | 2483.56 | 1872.11 | 5687.67 | 3165.34 | 0.00 | 193.67 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -39607.32 |
ROOM_5_FLR_3 | 25-FEB-19:04 | 3335.93 | 607.15 | 0.00 | -607.15 | 0.00 | 0.00 | 283.23 | 474.96 | 516.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -557.47 | 0.00 | -84.91 | -3968.00 |
ROOM_6_FLR_3 | 13-FEB-16:05 | 3465.53 | 632.05 | 0.00 | -632.05 | 0.00 | 0.00 | 235.28 | 132.97 | 273.90 | 636.40 | 0.00 | 90.59 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4834.68 |
CORRIDOR_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 20-FEB-16:04 | 1093.54 | 129.06 | 0.00 | -129.06 | 0.00 | 0.00 | 32.68 | 39.19 | 76.39 | 94.09 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -111.43 | -1224.44 |
ROOM_2_FLR_6 | 16-DEC-16:04 | 1093.44 | 158.15 | 0.00 | -158.15 | 0.00 | 0.00 | 32.68 | 39.18 | 76.38 | 266.36 | 0.00 | 7.21 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1515.24 |
ROOM_3_MULT9_FLR_6 | 27-DEC-09:05 | 3794.96 | 1013.39 | 0.00 | -1013.39 | 0.00 | 0.00 | 196.93 | 295.59 | 998.70 | 2581.36 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -0.30 | -7867.24 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-FEB-16:06 | -132780.90 | 135265.50 | 0.00 | -135265.50 | 0.00 | 0.00 | 32217.34 | 13390.11 | 78232.63 | 37198.25 | 0.00 | 251.39 | 0.00 | 0.00 | 0.00 | 0.00 | -320.26 | -28188.56 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 22.2066 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.1059 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6585 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6585 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5206 | 2.5206 | 1.3233 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3601 | 0.3601 | 0.1890 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2381 | 0.2381 | 0.1250 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2339 | 0.2339 | 0.1228 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1272 | 0.1272 | 0.0668 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2917 | 3.2917 | 1.7281 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4873 | 1.4873 | 0.7808 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.8407 | 4.8407 | 2.5414 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3893 | 1.3893 | 0.7294 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2853 | 2.2853 | 1.1998 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3911 | 2.3911 | 1.2553 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2178 | 2.2178 | 1.1644 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8234 | 0.8234 | 0.4323 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 22.2066 | 22.1059 | 22.2066 | 11.6585 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3233 | 1.3233 | 1.3233 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1890 | 0.1890 | 0.1890 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1250 | 0.1250 | 0.1250 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1228 | 0.1228 | 0.1228 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0668 | 0.0668 | 0.0668 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7281 | 1.7281 | 1.7281 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7808 | 0.7808 | 0.7808 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5414 | 2.5414 | 2.5414 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7294 | 0.7294 | 0.7294 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1998 | 1.1998 | 1.1998 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2553 | 1.2553 | 1.2553 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1644 | 1.1644 | 1.1644 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4323 | 0.4323 | 0.4323 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6585 | 11.6585 | 11.6585 | 11.6585 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 46.17 |
Number of hours not met | 46.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1.90 | 24078.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3794.93 | 308464.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 604.08 | 50471.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 174.66 | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 952.41 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 22.46 | 1283.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 645.34 | 46707.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 189.65 | 9147.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 294.25 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.74 | 4738.77 | 597.02 | 49007.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Other | 0.00 | 39217.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.86 | 1307.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 21.48 | 717.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1772.58 | 8561.93 |
Natural Gas | 1788.84 | 2387.76 |
Additional | 0.00 | 0.00 |
Total | 3561.42 | 10949.69 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 53.24 |
Space Heating | 0.00 |
Space Cooling | 334.49 |
Fans (All) | 56.88 |
Service Water Heating | 39.22 |
Receptacle Equipment | 152.32 |
Miscellaneous (All) | 754.67 |
Subtotal | 754.67 |
Natural Gas [MJ/m2] | |
Space Heating | 0.17 |
Service Water Heating | 52.62 |
Miscellaneous (All) | 210.46 |
Subtotal | 210.46 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.52 |
Space Heating | 0.02 |
Space Cooling | 34.66 |
Fans (All) | 5.89 |
Service Water Heating | 9.52 |
Receptacle Equipment | 32.12 |
Miscellaneous | 12.28 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2398. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 2482. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 6991.67 | 1768.33 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 6991.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1768.33 | 0.00 | 0.00 | 0.00 |
Average | 8679.62 | 80.38 | 0.00 | 0.00 | 0.00 |
Sum | 190951.67 | 1768.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8726.33 | 33.67 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 6194.17 | 2565.83 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 6597.17 | 2162.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8736.83 | 23.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 5855.67 | 2904.33 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8748.83 | 11.17 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8707.50 | 52.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8503.33 | 256.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8723.00 | 37.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 6336.83 | 2423.17 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 6552.17 | 2207.83 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8438.67 | 321.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 5855.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2904.33 | 0.00 | 0.00 | 0.00 |
Average | 8168.98 | 591.02 | 0.00 | 0.00 | 0.00 |
Sum | 179717.67 | 13002.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 58788.67 | 367.33 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 402463.33 | 307953.67 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1346399.83 | 769029.17 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4152.17 | 1.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4152.83 | 1.17 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4153.17 | 0.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 95937.33 | 4420.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4148.17 | 5.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 743104.83 | 502610.17 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 782568.67 | 463146.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 105765.83 | 2503.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1346399.83 | 769029.17 | 0.00 | 0.00 | 0.00 |
Average | 195703.40 | 93183.64 | 0.00 | 0.00 | 0.00 |
Sum | 4305474.83 | 2050040.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:48
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.388509E+11 | 19899.88 | 13-JAN-22:00 | 19.80 | 16.14 | 0.816998E+10 | 4837.08 | 04-JAN-23:10 | 19.80 | 16.14 |
February | 0.325379E+11 | 18417.36 | 01-FEB-22:00 | 19.70 | 17.64 | 0.721074E+10 | 4837.12 | 13-FEB-23:10 | 20.00 | 16.11 |
March | 0.336213E+11 | 15532.92 | 01-MAR-19:10 | 28.92 | 20.98 | 0.759338E+10 | 4805.46 | 01-MAR-23:10 | 26.00 | 20.01 |
April | 0.317573E+11 | 15004.67 | 02-APR-10:33 | 33.47 | 18.23 | 0.710964E+10 | 4534.09 | 04-APR-22:10 | 22.42 | 18.15 |
May | 0.342953E+11 | 15724.07 | 31-MAY-18:10 | 40.35 | 22.36 | 0.747184E+10 | 4619.85 | 26-MAY-22:10 | 40.35 | 22.36 |
June | 0.347199E+11 | 16211.93 | 11-JUN-10:33 | 38.67 | 26.57 | 0.746477E+10 | 4754.83 | 30-JUN-22:10 | 31.88 | 26.12 |
July | 0.382366E+11 | 17326.84 | 20-JUL-21:00 | 39.10 | 19.02 | 0.798994E+10 | 4837.01 | 31-JUL-21:19 | 36.10 | 26.51 |
August | 0.429367E+11 | 21593.74 | 24-AUG-21:00 | 33.00 | 29.08 | 0.821477E+10 | 4837.04 | 09-AUG-23:19 | 33.00 | 29.08 |
September | 0.431056E+11 | 22712.77 | 28-SEP-21:00 | 30.80 | 28.00 | 0.794893E+10 | 4837.05 | 20-SEP-21:30 | 30.80 | 28.00 |
October | 0.465772E+11 | 24056.99 | 20-OCT-21:00 | 28.00 | 20.00 | 0.822613E+10 | 4837.08 | 19-OCT-21:19 | 28.00 | 20.00 |
November | 0.449034E+11 | 24129.61 | 03-NOV-21:00 | 28.00 | 21.23 | 0.795910E+10 | 4837.07 | 29-NOV-23:10 | 22.83 | 20.84 |
December | 0.425450E+11 | 22928.40 | 01-DEC-22:00 | 21.80 | 17.40 | 0.821310E+10 | 4837.09 | 29-DEC-23:10 | 18.67 | 13.55 |
Annual Sum or Average | 0.464087E+12 | 0.935723E+11 | ||||||||
Minimum of Months | 0.317573E+11 | 15004.67 | 19.70 | 16.14 | 0.710964E+10 | 4534.09 | 18.67 | 13.55 | ||
Maximum of Months | 0.465772E+11 | 24129.61 | 40.35 | 29.08 | 0.822613E+10 | 4837.12 | 40.35 | 29.08 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.413241E+10 | 2209.35 | 29-JAN-11:33 | 26.67 | 18.74 | 0.684236E+09 | 436.66 | 24-JAN-22:30 | 26.67 | 18.74 |
February | 0.392844E+10 | 2583.62 | 05-FEB-13:00 | 31.10 | 19.64 | 0.635573E+09 | 472.95 | 07-FEB-22:30 | 24.20 | 19.96 |
March | 0.454510E+10 | 2512.31 | 27-MAR-14:10 | 35.00 | 19.31 | 0.728541E+09 | 491.81 | 27-MAR-21:19 | 28.63 | 15.92 |
April | 0.471294E+10 | 2588.65 | 28-APR-18:07 | 34.08 | 21.01 | 0.732116E+09 | 491.83 | 27-APR-21:19 | 34.08 | 21.01 |
May | 0.556409E+10 | 3055.78 | 31-MAY-19:10 | 41.85 | 20.81 | 0.809020E+09 | 491.83 | 31-MAY-21:19 | 35.53 | 22.46 |
June | 0.565640E+10 | 3086.40 | 09-JUN-18:03 | 39.75 | 25.47 | 0.798396E+09 | 491.83 | 14-JUN-21:19 | 32.60 | 22.89 |
July | 0.636907E+10 | 3383.67 | 21-JUL-18:03 | 41.83 | 23.77 | 0.832308E+09 | 491.87 | 20-JUL-23:30 | 41.83 | 23.77 |
August | 0.667267E+10 | 3370.92 | 16-AUG-18:13 | 40.93 | 26.86 | 0.838185E+09 | 491.83 | 15-AUG-23:19 | 40.93 | 26.86 |
September | 0.611484E+10 | 3407.23 | 26-SEP-13:00 | 41.20 | 22.43 | 0.799265E+09 | 491.83 | 02-SEP-01:19 | 41.20 | 22.43 |
October | 0.596521E+10 | 3400.48 | 09-OCT-12:00 | 38.00 | 19.81 | 0.810694E+09 | 491.83 | 19-OCT-21:19 | 28.70 | 19.77 |
November | 0.508696E+10 | 3076.50 | 05-NOV-12:00 | 34.00 | 17.15 | 0.746917E+09 | 491.83 | 03-NOV-21:19 | 34.00 | 17.15 |
December | 0.442452E+10 | 2786.90 | 03-DEC-13:00 | 29.80 | 17.63 | 0.709733E+09 | 465.75 | 05-DEC-22:30 | 23.00 | 20.57 |
Annual Sum or Average | 0.631726E+11 | 0.912498E+10 | ||||||||
Minimum of Months | 0.392844E+10 | 2209.35 | 26.67 | 17.15 | 0.635573E+09 | 436.66 | 23.00 | 15.92 | ||
Maximum of Months | 0.667267E+10 | 3407.23 | 41.85 | 26.86 | 0.838185E+09 | 491.87 | 41.83 | 26.86 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.316302E+10 | 1475.97 | 31-JAN-22:00 | 19.00 | 15.30 | 0.902631E+09 | 569.55 | 26-JAN-23:10 | 19.00 | 15.30 |
February | 0.295165E+10 | 1790.71 | 07-FEB-22:00 | 24.40 | 19.99 | 0.827489E+09 | 569.55 | 27-FEB-23:10 | 20.00 | 16.18 |
March | 0.340513E+10 | 2009.84 | 27-MAR-21:00 | 29.00 | 16.17 | 0.933140E+09 | 569.55 | 09-MAR-23:10 | 29.00 | 16.17 |
April | 0.349583E+10 | 2126.71 | 28-APR-21:00 | 31.00 | 17.98 | 0.914900E+09 | 569.55 | 04-APR-22:10 | 31.00 | 17.98 |
May | 0.406434E+10 | 2315.60 | 31-MAY-21:00 | 36.20 | 22.07 | 0.962981E+09 | 569.54 | 06-MAY-01:19 | 36.20 | 22.07 |
June | 0.412138E+10 | 2356.28 | 09-JUN-21:00 | 36.00 | 26.28 | 0.936387E+09 | 569.54 | 17-JUN-01:19 | 29.13 | 22.28 |
July | 0.444095E+10 | 2473.64 | 21-JUL-21:00 | 40.00 | 20.24 | 0.965897E+09 | 569.56 | 20-JUL-23:30 | 40.00 | 20.24 |
August | 0.453906E+10 | 2473.01 | 16-AUG-20:50 | 36.33 | 28.50 | 0.971080E+09 | 569.54 | 19-AUG-01:19 | 34.00 | 26.77 |
September | 0.415556E+10 | 2371.58 | 05-SEP-20:10 | 34.42 | 28.06 | 0.935531E+09 | 569.54 | 16-SEP-01:19 | 28.57 | 22.94 |
October | 0.403331E+10 | 2244.71 | 05-OCT-21:00 | 32.00 | 24.80 | 0.963317E+09 | 569.54 | 14-OCT-01:19 | 27.33 | 20.37 |
November | 0.355110E+10 | 2063.05 | 01-NOV-21:00 | 30.00 | 23.64 | 0.920253E+09 | 569.55 | 30-NOV-23:10 | 21.63 | 16.49 |
December | 0.329836E+10 | 1735.82 | 06-DEC-21:55 | 22.30 | 18.79 | 0.919976E+09 | 569.55 | 29-DEC-23:10 | 18.67 | 13.55 |
Annual Sum or Average | 0.452197E+11 | 0.111536E+11 | ||||||||
Minimum of Months | 0.295165E+10 | 1475.97 | 19.00 | 15.30 | 0.827489E+09 | 569.54 | 18.67 | 13.55 | ||
Maximum of Months | 0.453906E+10 | 2473.64 | 40.00 | 28.50 | 0.971080E+09 | 569.56 | 40.00 | 26.77 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.285367E+10 | 1305.84 | 29-JAN-11:33 | 26.67 | 18.74 | 0.178058E+09 | 112.93 | 30-JAN-22:10 | 19.67 | 16.72 |
February | 0.268230E+10 | 1390.68 | 08-FEB-19:10 | 24.33 | 20.46 | 0.164898E+09 | 117.87 | 07-FEB-22:19 | 24.33 | 20.46 |
March | 0.310145E+10 | 1496.95 | 27-MAR-18:10 | 32.92 | 18.22 | 0.187981E+09 | 120.45 | 28-MAR-21:19 | 25.00 | 21.54 |
April | 0.322616E+10 | 1905.54 | 28-APR-20:00 | 33.00 | 18.35 | 0.188371E+09 | 120.45 | 25-APR-21:19 | 33.00 | 18.35 |
May | 0.391634E+10 | 2324.32 | 31-MAY-20:00 | 40.60 | 20.99 | 0.203817E+09 | 120.45 | 04-MAY-21:30 | 40.60 | 20.99 |
June | 0.413779E+10 | 2434.03 | 09-JUN-20:00 | 37.00 | 25.93 | 0.198932E+09 | 120.45 | 15-JUN-21:19 | 33.07 | 24.57 |
July | 0.461232E+10 | 2639.24 | 21-JUL-20:00 | 41.00 | 20.45 | 0.204964E+09 | 120.46 | 20-JUL-23:30 | 41.00 | 20.45 |
August | 0.469819E+10 | 2592.44 | 16-AUG-20:00 | 38.00 | 28.83 | 0.205847E+09 | 120.45 | 10-AUG-21:19 | 38.00 | 28.83 |
September | 0.405604E+10 | 2415.25 | 05-SEP-20:00 | 34.50 | 28.10 | 0.198303E+09 | 120.45 | 20-SEP-21:30 | 31.80 | 26.09 |
October | 0.375064E+10 | 2144.84 | 05-OCT-20:00 | 33.00 | 25.07 | 0.202900E+09 | 120.46 | 19-OCT-21:19 | 28.70 | 19.77 |
November | 0.322626E+10 | 1713.23 | 02-NOV-21:00 | 29.00 | 24.60 | 0.189337E+09 | 120.45 | 03-NOV-21:19 | 27.67 | 21.12 |
December | 0.301017E+10 | 1372.23 | 03-DEC-11:33 | 27.33 | 18.33 | 0.184241E+09 | 116.90 | 01-DEC-22:19 | 27.33 | 18.33 |
Annual Sum or Average | 0.432713E+11 | 0.230765E+10 | ||||||||
Minimum of Months | 0.268230E+10 | 1305.84 | 24.33 | 18.22 | 0.164898E+09 | 112.93 | 19.67 | 16.72 | ||
Maximum of Months | 0.469819E+10 | 2639.24 | 41.00 | 28.83 | 0.205847E+09 | 120.46 | 41.00 | 28.83 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152469E+10 | 709.86 | 29-JAN-11:33 | 26.67 | 18.74 | 0.134974E+09 | 84.15 | 30-JAN-23:10 | 20.00 | 16.82 |
February | 0.143402E+10 | 743.04 | 08-FEB-11:33 | 27.33 | 19.29 | 0.124994E+09 | 88.03 | 07-FEB-23:10 | 27.33 | 19.29 |
March | 0.165795E+10 | 798.91 | 27-MAR-18:10 | 32.92 | 18.22 | 0.142444E+09 | 90.51 | 27-MAR-22:10 | 27.92 | 15.44 |
April | 0.171772E+10 | 859.04 | 29-APR-10:33 | 35.90 | 19.60 | 0.142892E+09 | 92.66 | 28-APR-22:49 | 35.90 | 19.60 |
May | 0.202509E+10 | 1109.50 | 31-MAY-20:10 | 39.87 | 21.29 | 0.156267E+09 | 92.66 | 04-MAY-21:30 | 39.87 | 21.29 |
June | 0.213609E+10 | 1148.39 | 09-JUN-20:50 | 36.17 | 26.23 | 0.153051E+09 | 92.66 | 15-JUN-21:19 | 33.07 | 24.57 |
July | 0.241945E+10 | 1279.12 | 21-JUL-21:00 | 40.00 | 20.24 | 0.157682E+09 | 92.66 | 20-JUL-23:30 | 40.00 | 20.24 |
August | 0.246704E+10 | 1249.16 | 16-AUG-20:00 | 38.00 | 28.83 | 0.158356E+09 | 92.66 | 10-AUG-21:19 | 38.00 | 28.83 |
September | 0.209767E+10 | 1129.83 | 05-SEP-20:00 | 34.50 | 28.10 | 0.152480E+09 | 92.66 | 20-SEP-21:30 | 31.80 | 26.09 |
October | 0.195004E+10 | 983.92 | 05-OCT-20:40 | 32.33 | 24.90 | 0.155312E+09 | 92.66 | 19-OCT-21:19 | 28.70 | 19.77 |
November | 0.171984E+10 | 813.92 | 05-NOV-10:33 | 31.33 | 19.23 | 0.143633E+09 | 92.65 | 01-NOV-22:10 | 31.33 | 19.23 |
December | 0.160848E+10 | 744.52 | 03-DEC-11:33 | 27.33 | 18.33 | 0.139607E+09 | 87.09 | 01-DEC-22:49 | 27.33 | 18.33 |
Annual Sum or Average | 0.227581E+11 | 0.176169E+10 | ||||||||
Minimum of Months | 0.143402E+10 | 709.86 | 26.67 | 18.22 | 0.124994E+09 | 84.15 | 20.00 | 15.44 | ||
Maximum of Months | 0.246704E+10 | 1279.12 | 40.00 | 28.83 | 0.158356E+09 | 92.66 | 40.00 | 28.83 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.514085E+11 | 37761.11 | 24-JAN-21:00 | 21.00 | 17.21 | 0.591278E+09 | 381.69 | 04-JAN-22:10 | 21.00 | 17.21 |
February | 0.468134E+11 | 38143.19 | 07-FEB-21:00 | 25.00 | 20.23 | 0.535120E+09 | 381.69 | 08-FEB-22:10 | 23.58 | 21.11 |
March | 0.525633E+11 | 38690.32 | 27-MAR-20:00 | 31.00 | 16.56 | 0.595068E+09 | 381.68 | 28-MAR-21:19 | 25.00 | 21.54 |
April | 0.516315E+11 | 39022.82 | 28-APR-20:00 | 33.00 | 18.35 | 0.576718E+09 | 381.73 | 28-APR-21:10 | 30.82 | 17.97 |
May | 0.548126E+11 | 39290.03 | 31-MAY-20:00 | 40.60 | 20.99 | 0.599236E+09 | 381.73 | 12-MAY-21:10 | 40.60 | 20.99 |
June | 0.534772E+11 | 39358.28 | 01-JUN-20:00 | 34.00 | 25.28 | 0.581434E+09 | 381.73 | 16-JUN-21:10 | 31.92 | 24.81 |
July | 0.555044E+11 | 39659.89 | 21-JUL-20:00 | 41.00 | 20.45 | 0.600475E+09 | 381.76 | 25-JUL-21:10 | 34.78 | 29.42 |
August | 0.558698E+11 | 39590.73 | 16-AUG-20:00 | 38.00 | 28.83 | 0.602438E+09 | 381.78 | 25-AUG-21:10 | 33.83 | 29.33 |
September | 0.531984E+11 | 39297.15 | 05-SEP-20:00 | 34.50 | 28.10 | 0.580278E+09 | 381.78 | 15-SEP-21:10 | 32.63 | 24.56 |
October | 0.542275E+11 | 39001.83 | 05-OCT-20:00 | 33.00 | 25.07 | 0.598317E+09 | 381.77 | 03-OCT-21:10 | 33.00 | 25.07 |
November | 0.514570E+11 | 38577.61 | 01-NOV-20:00 | 30.00 | 22.92 | 0.576738E+09 | 381.73 | 03-NOV-21:10 | 27.83 | 21.18 |
December | 0.517785E+11 | 38050.45 | 01-DEC-21:00 | 22.00 | 18.12 | 0.592520E+09 | 381.70 | 01-DEC-22:10 | 21.67 | 17.26 |
Annual Sum or Average | 0.632742E+12 | 0.702962E+10 | ||||||||
Minimum of Months | 0.468134E+11 | 37761.11 | 21.00 | 16.56 | 0.535120E+09 | 381.68 | 21.00 | 17.21 | ||
Maximum of Months | 0.558698E+11 | 39659.89 | 41.00 | 28.83 | 0.602438E+09 | 381.78 | 40.60 | 29.42 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203690E+11 | 9477.64 | 29-JAN-11:33 | 26.67 | 18.74 | 0.104274E+11 | 6462.55 | 26-JAN-23:10 | 26.67 | 18.74 |
February | 0.189602E+11 | 10744.87 | 05-FEB-11:00 | 29.00 | 18.72 | 0.951077E+10 | 6462.64 | 13-FEB-23:10 | 20.00 | 16.11 |
March | 0.215054E+11 | 11490.71 | 27-MAR-21:10 | 28.82 | 16.04 | 0.106516E+11 | 6462.68 | 09-MAR-23:10 | 28.82 | 16.04 |
April | 0.217635E+11 | 11940.10 | 28-APR-21:10 | 30.82 | 17.97 | 0.103797E+11 | 6462.61 | 04-APR-22:10 | 30.82 | 17.97 |
May | 0.247641E+11 | 12935.58 | 31-MAY-21:10 | 35.87 | 22.27 | 0.108824E+11 | 6462.00 | 13-MAY-01:19 | 35.87 | 22.27 |
June | 0.247717E+11 | 13091.64 | 09-JUN-21:10 | 35.72 | 26.19 | 0.105820E+11 | 6461.99 | 10-JUN-01:19 | 32.40 | 24.94 |
July | 0.270217E+11 | 14066.03 | 21-JUL-21:10 | 39.63 | 20.08 | 0.109423E+11 | 6461.99 | 22-JUL-01:19 | 34.40 | 24.82 |
August | 0.278807E+11 | 13893.42 | 16-AUG-21:10 | 35.72 | 28.34 | 0.110073E+11 | 6461.99 | 19-AUG-01:19 | 34.00 | 26.77 |
September | 0.261130E+11 | 13238.73 | 06-SEP-21:10 | 33.97 | 28.38 | 0.106112E+11 | 6461.99 | 02-SEP-01:19 | 33.97 | 28.38 |
October | 0.260896E+11 | 12756.50 | 05-OCT-21:10 | 31.97 | 24.90 | 0.109423E+11 | 6462.00 | 14-OCT-01:19 | 27.33 | 20.37 |
November | 0.230899E+11 | 12060.91 | 01-NOV-21:10 | 30.00 | 23.75 | 0.105040E+11 | 6462.53 | 21-NOV-23:10 | 20.83 | 15.96 |
December | 0.212252E+11 | 10830.32 | 03-DEC-13:00 | 29.80 | 17.63 | 0.105824E+11 | 6462.61 | 12-DEC-23:10 | 19.00 | 14.29 |
Annual Sum or Average | 0.283554E+12 | 0.127023E+12 | ||||||||
Minimum of Months | 0.189602E+11 | 9477.64 | 26.67 | 16.04 | 0.951077E+10 | 6461.99 | 19.00 | 14.29 | ||
Maximum of Months | 0.278807E+11 | 14066.03 | 39.63 | 28.38 | 0.110073E+11 | 6462.68 | 35.87 | 28.38 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.696184E+11 | 35335.55 | 24-JAN-22:10 | 20.25 | 16.41 | 0.316820E+11 | 19185.97 | 26-JAN-23:10 | 19.83 | 15.00 |
February | 0.647257E+11 | 39010.56 | 07-FEB-22:10 | 24.33 | 19.98 | 0.287924E+11 | 19186.20 | 13-FEB-23:10 | 20.00 | 16.11 |
March | 0.739320E+11 | 41010.58 | 27-MAR-21:10 | 28.82 | 16.04 | 0.321030E+11 | 19186.19 | 09-MAR-23:10 | 28.82 | 16.04 |
April | 0.750091E+11 | 42622.25 | 28-APR-21:10 | 30.82 | 17.97 | 0.311179E+11 | 19186.02 | 04-APR-22:10 | 30.82 | 17.97 |
May | 0.850128E+11 | 45510.33 | 31-MAY-21:10 | 35.87 | 22.27 | 0.324005E+11 | 19185.20 | 13-MAY-01:19 | 35.87 | 22.27 |
June | 0.851853E+11 | 46308.39 | 09-JUN-21:10 | 35.72 | 26.19 | 0.314889E+11 | 19185.19 | 17-JUN-01:19 | 29.13 | 22.28 |
July | 0.913451E+11 | 48751.80 | 21-JUL-21:10 | 39.63 | 20.08 | 0.324901E+11 | 19185.34 | 20-JUL-23:30 | 39.63 | 20.08 |
August | 0.930748E+11 | 48473.40 | 16-AUG-21:10 | 35.72 | 28.34 | 0.326765E+11 | 19185.20 | 19-AUG-01:19 | 34.00 | 26.77 |
September | 0.866500E+11 | 46704.21 | 06-SEP-21:10 | 33.97 | 28.38 | 0.315186E+11 | 19185.20 | 16-SEP-01:19 | 28.57 | 22.94 |
October | 0.860262E+11 | 45255.14 | 05-OCT-21:10 | 31.97 | 24.90 | 0.325114E+11 | 19185.21 | 14-OCT-01:19 | 27.33 | 20.37 |
November | 0.773056E+11 | 42827.36 | 01-NOV-21:10 | 30.00 | 23.75 | 0.312879E+11 | 19185.92 | 30-NOV-23:10 | 21.63 | 16.49 |
December | 0.725188E+11 | 38211.46 | 05-DEC-22:05 | 23.00 | 20.35 | 0.319473E+11 | 19186.02 | 14-DEC-23:10 | 22.00 | 18.20 |
Annual Sum or Average | 0.960404E+12 | 0.380017E+12 | ||||||||
Minimum of Months | 0.647257E+11 | 35335.55 | 20.25 | 16.04 | 0.287924E+11 | 19185.19 | 19.83 | 15.00 | ||
Maximum of Months | 0.930748E+11 | 48751.80 | 39.63 | 28.38 | 0.326765E+11 | 19186.20 | 39.63 | 26.77 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106076E+10 | 3091.53 | 22-JAN-16:01 | 25.67 | 16.85 | 98577487.47 | 56.69 | 27-JAN-22:49 | 18.10 | 15.06 |
February | 0.123230E+10 | 3059.66 | 03-FEB-16:02 | 25.25 | 17.88 | 89183123.47 | 56.70 | 07-FEB-22:10 | 24.33 | 19.98 |
March | 0.177544E+10 | 3122.38 | 25-MAR-18:02 | 27.38 | 20.47 | 98969878.22 | 56.70 | 29-MAR-21:40 | 24.00 | 20.62 |
April | 0.220803E+10 | 3134.00 | 18-APR-18:02 | 27.85 | 21.12 | 95869620.41 | 56.70 | 21-APR-21:00 | 24.90 | 21.73 |
May | 0.310968E+10 | 3116.78 | 28-MAY-08:62 | 32.92 | 25.09 | 99200689.33 | 56.70 | 31-MAY-22:19 | 33.83 | 23.07 |
June | 0.328270E+10 | 3105.15 | 19-JUN-08:62 | 30.50 | 25.55 | 96038065.57 | 56.70 | 13-JUN-21:10 | 30.50 | 25.55 |
July | 0.367676E+10 | 3114.57 | 28-JUL-08:62 | 32.40 | 28.80 | 99143849.69 | 56.70 | 22-JUL-00:20 | 32.40 | 28.80 |
August | 0.379499E+10 | 3135.97 | 16-AUG-18:02 | 40.97 | 26.89 | 99251324.37 | 56.70 | 30-AUG-21:40 | 32.87 | 30.22 |
September | 0.327779E+10 | 3120.73 | 15-SEP-08:62 | 31.23 | 25.35 | 95961077.92 | 56.70 | 12-SEP-21:49 | 31.23 | 25.35 |
October | 0.292258E+10 | 3134.22 | 24-OCT-18:02 | 30.50 | 23.92 | 99150760.06 | 56.70 | 18-OCT-21:10 | 30.50 | 23.92 |
November | 0.213246E+10 | 3105.08 | 15-NOV-19:02 | 27.92 | 20.61 | 95926185.99 | 56.70 | 02-NOV-23:00 | 27.92 | 20.61 |
December | 0.136959E+10 | 3094.02 | 05-DEC-16:02 | 26.25 | 23.06 | 98735345.55 | 56.69 | 08-DEC-01:30 | 18.35 | 15.25 |
Annual Sum or Average | 0.298431E+11 | 0.116601E+10 | ||||||||
Minimum of Months | 0.106076E+10 | 3059.66 | 25.25 | 16.85 | 89183123.47 | 56.69 | 18.10 | 15.06 | ||
Maximum of Months | 0.379499E+10 | 3135.97 | 40.97 | 28.80 | 99251324.37 | 56.70 | 33.83 | 30.22 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.590697E+09 | 2897.03 | 29-JAN-16:02 | 25.83 | 20.06 | 0.103171E+09 | 69.03 | 23-JAN-22:10 | 25.83 | 20.06 |
February | 0.807308E+09 | 3094.53 | 04-FEB-16:01 | 28.50 | 17.14 | 94030491.59 | 73.66 | 08-FEB-22:10 | 23.58 | 21.11 |
March | 0.142868E+10 | 3086.05 | 24-MAR-15:02 | 26.83 | 20.18 | 0.103505E+09 | 76.06 | 30-MAR-21:10 | 23.00 | 20.23 |
April | 0.204884E+10 | 3273.80 | 24-APR-08:11 | 28.00 | 17.01 | 97326437.19 | 75.55 | 04-APR-21:10 | 28.00 | 17.01 |
May | 0.309468E+10 | 3074.58 | 31-MAY-18:02 | 40.35 | 22.36 | 99476201.62 | 56.70 | 31-MAY-22:40 | 33.47 | 23.08 |
June | 0.332436E+10 | 3329.16 | 22-JUN-08:51 | 34.00 | 22.19 | 96056398.52 | 56.70 | 27-JUN-21:49 | 32.42 | 28.81 |
July | 0.369201E+10 | 3067.55 | 27-JUL-08:62 | 32.33 | 28.90 | 99144818.17 | 56.70 | 22-JUL-00:00 | 32.33 | 28.90 |
August | 0.373511E+10 | 3148.55 | 05-AUG-18:02 | 39.92 | 26.01 | 99251781.07 | 56.70 | 03-AUG-00:10 | 39.92 | 26.01 |
September | 0.309576E+10 | 3074.56 | 15-SEP-08:62 | 31.23 | 25.35 | 96060915.87 | 56.70 | 01-SEP-21:30 | 31.23 | 25.35 |
October | 0.259410E+10 | 3134.71 | 21-OCT-08:41 | 28.17 | 14.74 | 99577980.02 | 56.70 | 05-OCT-21:00 | 28.17 | 14.74 |
November | 0.171256E+10 | 3089.13 | 25-NOV-16:01 | 26.25 | 18.81 | 97675308.30 | 71.90 | 22-NOV-22:10 | 26.25 | 18.81 |
December | 0.886043E+09 | 3053.89 | 01-DEC-16:01 | 26.75 | 18.64 | 0.103535E+09 | 72.77 | 01-DEC-22:10 | 21.67 | 17.26 |
Annual Sum or Average | 0.270101E+11 | 0.118881E+10 | ||||||||
Minimum of Months | 0.590697E+09 | 2897.03 | 25.83 | 14.74 | 94030491.59 | 56.70 | 21.67 | 14.74 | ||
Maximum of Months | 0.373511E+10 | 3329.16 | 40.35 | 28.90 | 0.103535E+09 | 76.06 | 39.92 | 28.90 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.422495E+09 | 396.12 | 28-JAN-13:50 | 27.88 | 13.04 | 0.00 | 0.00 | 01-JAN-00:10 | 27.88 | 13.04 |
February | 0.417527E+09 | 459.05 | 05-FEB-13:40 | 31.43 | 19.44 | 0.00 | 0.00 | 01-FEB-00:10 | 31.43 | 19.44 |
March | 0.500586E+09 | 412.44 | 27-MAR-13:40 | 35.33 | 19.53 | 0.00 | 0.00 | 01-MAR-00:10 | 35.33 | 19.53 |
April | 0.556425E+09 | 382.54 | 28-APR-17:20 | 34.10 | 20.70 | 0.00 | 0.00 | 01-APR-00:10 | 34.10 | 20.70 |
May | 0.739111E+09 | 441.29 | 31-MAY-19:10 | 41.85 | 20.81 | 0.00 | 0.00 | 01-MAY-00:10 | 41.85 | 20.81 |
June | 0.766530E+09 | 449.09 | 09-JUN-17:20 | 40.67 | 25.01 | 0.00 | 0.00 | 01-JUN-00:10 | 40.67 | 25.01 |
July | 0.898895E+09 | 496.90 | 21-JUL-20:20 | 40.67 | 20.38 | 0.00 | 0.00 | 01-JUL-00:10 | 40.67 | 20.38 |
August | 0.963261E+09 | 500.78 | 16-AUG-17:13 | 41.00 | 26.91 | 0.00 | 0.00 | 01-AUG-00:10 | 41.00 | 26.91 |
September | 0.892722E+09 | 523.95 | 26-SEP-13:20 | 40.47 | 22.95 | 0.00 | 0.00 | 01-SEP-00:10 | 40.47 | 22.95 |
October | 0.882854E+09 | 534.45 | 09-OCT-13:30 | 37.30 | 20.15 | 0.00 | 0.00 | 01-OCT-00:10 | 37.30 | 20.15 |
November | 0.712009E+09 | 511.65 | 05-NOV-13:30 | 33.20 | 21.19 | 0.00 | 0.00 | 01-NOV-00:10 | 33.20 | 21.19 |
December | 0.508835E+09 | 468.47 | 03-DEC-13:00 | 29.80 | 17.63 | 0.00 | 0.00 | 01-DEC-00:10 | 29.80 | 17.63 |
Annual Sum or Average | 0.826125E+10 | 0.00 | ||||||||
Minimum of Months | 0.417527E+09 | 382.54 | 27.88 | 13.04 | 0.00 | 0.00 | 27.88 | 13.04 | ||
Maximum of Months | 0.963261E+09 | 534.45 | 41.85 | 26.91 | 0.00 | 0.00 | 41.85 | 26.91 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.454122E+09 | 1116.41 | 28-JAN-16:02 | 24.42 | 17.40 | 0.103353E+09 | 72.10 | 30-JAN-22:49 | 19.93 | 16.80 |
February | 0.492972E+09 | 1168.46 | 04-FEB-16:01 | 28.50 | 17.14 | 93636916.32 | 73.46 | 09-FEB-22:10 | 21.75 | 16.24 |
March | 0.697794E+09 | 1164.07 | 26-MAR-18:02 | 30.67 | 18.80 | 0.102882E+09 | 73.87 | 09-MAR-22:10 | 30.67 | 18.80 |
April | 0.865089E+09 | 1178.18 | 02-APR-08:31 | 28.40 | 16.26 | 96939579.68 | 73.04 | 04-APR-21:10 | 22.95 | 18.43 |
May | 0.116651E+10 | 1176.28 | 15-MAY-15:02 | 31.97 | 24.10 | 99326380.36 | 56.70 | 05-MAY-21:40 | 31.97 | 24.10 |
June | 0.122959E+10 | 1176.44 | 09-JUN-18:02 | 39.75 | 25.47 | 95984624.39 | 56.70 | 01-JUN-22:30 | 39.75 | 25.47 |
July | 0.134878E+10 | 1172.06 | 05-JUL-15:02 | 34.93 | 28.80 | 99096590.12 | 56.70 | 23-JUL-23:10 | 35.83 | 25.69 |
August | 0.134164E+10 | 1173.45 | 10-AUG-18:02 | 41.02 | 28.50 | 99197801.51 | 56.70 | 10-AUG-21:10 | 34.93 | 27.53 |
September | 0.113973E+10 | 1177.47 | 28-SEP-15:02 | 33.95 | 28.46 | 95937978.60 | 56.70 | 11-SEP-21:00 | 33.95 | 28.46 |
October | 0.100731E+10 | 1191.58 | 21-OCT-08:41 | 28.17 | 14.74 | 99328452.07 | 56.70 | 05-OCT-21:40 | 28.17 | 14.74 |
November | 0.761123E+09 | 1160.35 | 10-NOV-19:02 | 27.83 | 20.10 | 97240973.72 | 71.09 | 22-NOV-22:10 | 22.25 | 16.62 |
December | 0.544948E+09 | 1152.00 | 05-DEC-19:01 | 25.08 | 21.83 | 0.103536E+09 | 73.30 | 26-DEC-22:10 | 23.33 | 19.65 |
Annual Sum or Average | 0.110496E+11 | 0.118646E+10 | ||||||||
Minimum of Months | 0.454122E+09 | 1116.41 | 24.42 | 14.74 | 93636916.32 | 56.70 | 19.93 | 14.74 | ||
Maximum of Months | 0.134878E+10 | 1191.58 | 41.02 | 28.80 | 0.103536E+09 | 73.87 | 39.75 | 28.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106372E+10 | 2772.93 | 28-JAN-16:02 | 24.42 | 17.40 | 98730966.91 | 56.69 | 27-JAN-22:00 | 24.42 | 17.40 |
February | 0.121984E+10 | 2847.11 | 23-FEB-16:01 | 26.25 | 17.96 | 89275079.97 | 56.70 | 07-FEB-22:19 | 26.25 | 17.96 |
March | 0.171919E+10 | 2835.25 | 17-MAR-15:02 | 25.83 | 18.62 | 99038664.49 | 56.70 | 20-MAR-21:10 | 22.83 | 17.34 |
April | 0.223807E+10 | 2839.08 | 30-APR-18:02 | 29.95 | 25.20 | 95915499.46 | 56.70 | 28-APR-21:10 | 29.95 | 25.20 |
May | 0.316101E+10 | 2870.26 | 23-MAY-08:62 | 30.67 | 22.98 | 99212117.15 | 56.70 | 09-MAY-21:40 | 30.67 | 22.98 |
June | 0.328131E+10 | 2855.26 | 07-JUN-18:02 | 31.78 | 26.76 | 96038434.10 | 56.70 | 23-JUN-21:40 | 31.47 | 28.41 |
July | 0.369047E+10 | 2884.14 | 30-JUL-15:02 | 40.45 | 27.73 | 99142794.83 | 56.70 | 22-JUL-02:20 | 40.45 | 27.73 |
August | 0.380435E+10 | 2901.58 | 10-AUG-15:02 | 42.02 | 29.59 | 99250648.51 | 56.70 | 02-AUG-02:20 | 42.02 | 29.59 |
September | 0.328252E+10 | 2863.31 | 28-SEP-08:62 | 28.40 | 26.24 | 95966443.20 | 56.70 | 06-SEP-22:00 | 28.40 | 26.24 |
October | 0.294499E+10 | 2871.61 | 01-OCT-08:62 | 27.90 | 26.14 | 99170030.15 | 56.70 | 05-OCT-21:40 | 31.87 | 25.19 |
November | 0.213608E+10 | 2874.67 | 06-NOV-09:01 | 27.40 | 21.69 | 95969450.20 | 56.70 | 24-NOV-22:30 | 25.85 | 21.74 |
December | 0.134758E+10 | 2824.93 | 01-DEC-16:01 | 26.75 | 18.64 | 98842051.22 | 56.69 | 01-DEC-22:10 | 21.67 | 17.26 |
Annual Sum or Average | 0.298891E+11 | 0.116655E+10 | ||||||||
Minimum of Months | 0.106372E+10 | 2772.93 | 24.42 | 17.40 | 89275079.97 | 56.69 | 21.67 | 17.26 | ||
Maximum of Months | 0.380435E+10 | 2901.58 | 42.02 | 29.59 | 99250648.51 | 56.70 | 42.02 | 29.59 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.601445E+09 | 2642.25 | 24-JAN-09:51 | 21.90 | 15.35 | 0.103040E+09 | 68.98 | 24-JAN-22:19 | 20.20 | 16.37 |
February | 0.800311E+09 | 2923.91 | 05-FEB-09:51 | 27.30 | 18.55 | 93857582.36 | 73.48 | 08-FEB-22:10 | 23.58 | 21.11 |
March | 0.137700E+10 | 2858.76 | 26-MAR-08:51 | 26.00 | 16.43 | 0.103267E+09 | 74.94 | 30-MAR-21:10 | 23.00 | 20.23 |
April | 0.206482E+10 | 3204.61 | 24-APR-08:11 | 28.00 | 17.01 | 97559582.47 | 74.49 | 04-APR-21:10 | 28.00 | 17.01 |
May | 0.314322E+10 | 2987.04 | 03-MAY-08:21 | 26.50 | 18.68 | 99525908.16 | 56.70 | 18-MAY-21:00 | 30.90 | 23.86 |
June | 0.332225E+10 | 3246.79 | 22-JUN-08:51 | 34.00 | 22.19 | 96061995.50 | 56.70 | 13-JUN-22:10 | 34.00 | 22.19 |
July | 0.370565E+10 | 2842.65 | 30-JUL-15:02 | 40.45 | 27.73 | 99144520.57 | 56.70 | 24-JUL-00:49 | 40.45 | 27.73 |
August | 0.374447E+10 | 2851.45 | 16-AUG-15:02 | 40.08 | 29.46 | 99250921.77 | 56.70 | 17-AUG-01:10 | 33.42 | 27.61 |
September | 0.309977E+10 | 2830.95 | 22-SEP-18:02 | 31.90 | 26.82 | 96070001.61 | 56.70 | 06-SEP-22:49 | 31.90 | 26.82 |
October | 0.261235E+10 | 3101.61 | 21-OCT-08:41 | 28.17 | 14.74 | 99674112.24 | 56.70 | 04-OCT-21:10 | 28.17 | 14.74 |
November | 0.169038E+10 | 2962.87 | 18-NOV-09:51 | 27.10 | 16.51 | 98083678.09 | 71.41 | 30-NOV-22:10 | 22.20 | 17.52 |
December | 0.860503E+09 | 2771.79 | 10-DEC-19:01 | 25.73 | 19.87 | 0.103504E+09 | 72.36 | 01-DEC-22:10 | 25.73 | 19.87 |
Annual Sum or Average | 0.270222E+11 | 0.118904E+10 | ||||||||
Minimum of Months | 0.601445E+09 | 2642.25 | 21.90 | 14.74 | 93857582.36 | 56.70 | 20.20 | 14.74 | ||
Maximum of Months | 0.374447E+10 | 3246.79 | 40.45 | 29.46 | 0.103504E+09 | 74.94 | 40.45 | 27.73 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.405210E+10 | 1895.89 | 29-JAN-11:33 | 26.67 | 18.74 | 0.135978E+10 | 838.30 | 31-JAN-22:49 | 18.00 | 14.99 |
February | 0.386239E+10 | 1992.95 | 05-FEB-11:33 | 30.33 | 18.87 | 0.127040E+10 | 882.70 | 08-FEB-23:10 | 23.83 | 21.01 |
March | 0.448682E+10 | 2172.86 | 27-MAR-18:10 | 32.92 | 18.22 | 0.145255E+10 | 910.96 | 27-MAR-21:49 | 28.08 | 15.55 |
April | 0.464780E+10 | 2318.43 | 29-APR-10:33 | 35.90 | 19.60 | 0.145656E+10 | 947.81 | 28-APR-21:49 | 35.90 | 19.60 |
May | 0.537546E+10 | 2788.13 | 31-MAY-18:17 | 40.70 | 22.08 | 0.159860E+10 | 951.84 | 31-MAY-23:19 | 32.97 | 23.19 |
June | 0.550663E+10 | 2861.96 | 09-JUN-18:13 | 39.50 | 25.61 | 0.156819E+10 | 951.84 | 15-JUN-21:19 | 33.07 | 24.57 |
July | 0.607942E+10 | 3168.14 | 21-JUL-18:13 | 41.67 | 23.66 | 0.161799E+10 | 951.85 | 20-JUL-23:30 | 41.67 | 23.66 |
August | 0.624981E+10 | 3167.09 | 16-AUG-18:13 | 40.93 | 26.86 | 0.162549E+10 | 951.84 | 15-AUG-23:19 | 40.93 | 26.86 |
September | 0.554170E+10 | 2847.54 | 05-SEP-18:15 | 35.63 | 27.42 | 0.156400E+10 | 951.84 | 16-SEP-01:19 | 28.57 | 22.94 |
October | 0.529735E+10 | 2524.82 | 05-OCT-21:10 | 31.97 | 24.90 | 0.159600E+10 | 951.85 | 19-OCT-21:19 | 28.70 | 19.77 |
November | 0.469306E+10 | 2229.71 | 05-NOV-10:33 | 31.33 | 19.23 | 0.147234E+10 | 943.90 | 01-NOV-22:10 | 31.33 | 19.23 |
December | 0.432192E+10 | 2026.31 | 03-DEC-11:33 | 27.33 | 18.33 | 0.141635E+10 | 881.86 | 01-DEC-22:49 | 27.33 | 18.33 |
Annual Sum or Average | 0.601145E+11 | 0.179982E+11 | ||||||||
Minimum of Months | 0.386239E+10 | 1895.89 | 26.67 | 18.22 | 0.127040E+10 | 838.30 | 18.00 | 14.99 | ||
Maximum of Months | 0.624981E+10 | 3168.14 | 41.67 | 27.42 | 0.162549E+10 | 951.85 | 41.67 | 26.86 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.969593E+09 | 3282.00 | 22-JAN-16:01 | 25.67 | 16.85 | 98448068.13 | 56.69 | 08-JAN-05:00 | 25.67 | 16.85 |
February | 0.117443E+10 | 3263.56 | 07-FEB-19:02 | 26.67 | 20.05 | 89091668.56 | 56.69 | 24-FEB-00:10 | 20.08 | 18.14 |
March | 0.176349E+10 | 3318.86 | 25-MAR-18:02 | 27.38 | 20.47 | 98893972.69 | 56.70 | 29-MAR-21:10 | 24.00 | 20.62 |
April | 0.225829E+10 | 3352.65 | 03-APR-18:02 | 26.78 | 19.11 | 95828157.07 | 56.70 | 19-APR-21:10 | 25.97 | 21.79 |
May | 0.324828E+10 | 3340.29 | 22-MAY-08:62 | 36.25 | 22.78 | 99193142.30 | 56.70 | 31-MAY-21:00 | 34.20 | 23.06 |
June | 0.345158E+10 | 3315.29 | 02-JUN-08:62 | 33.67 | 17.87 | 96037366.22 | 56.70 | 21-JUN-21:10 | 32.82 | 27.13 |
July | 0.391441E+10 | 3433.76 | 21-JUL-18:02 | 41.83 | 23.77 | 99145172.33 | 56.70 | 12-JUL-21:10 | 41.83 | 23.77 |
August | 0.403063E+10 | 3411.11 | 05-AUG-18:02 | 39.92 | 26.01 | 99252075.29 | 56.70 | 06-AUG-00:20 | 36.53 | 25.64 |
September | 0.341482E+10 | 3344.02 | 04-SEP-08:62 | 33.72 | 21.14 | 95955617.29 | 56.70 | 06-SEP-21:40 | 33.87 | 27.73 |
October | 0.297407E+10 | 3354.41 | 24-OCT-18:02 | 30.50 | 23.92 | 99133285.54 | 56.70 | 12-OCT-23:49 | 30.50 | 23.92 |
November | 0.210042E+10 | 3319.42 | 08-NOV-19:02 | 28.67 | 22.03 | 95888939.85 | 56.70 | 10-NOV-22:10 | 25.08 | 19.47 |
December | 0.128511E+10 | 3329.21 | 11-DEC-16:02 | 27.17 | 18.34 | 98632428.64 | 56.69 | 20-DEC-22:19 | 19.00 | 15.25 |
Annual Sum or Average | 0.305851E+11 | 0.116550E+10 | ||||||||
Minimum of Months | 0.969593E+09 | 3263.56 | 25.67 | 16.85 | 89091668.56 | 56.69 | 19.00 | 15.25 | ||
Maximum of Months | 0.403063E+10 | 3433.76 | 41.83 | 26.01 | 99252075.29 | 56.70 | 41.83 | 27.73 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.510622E+09 | 3147.61 | 29-JAN-16:02 | 25.83 | 20.06 | 0.102809E+09 | 68.85 | 24-JAN-22:30 | 25.83 | 20.06 |
February | 0.767734E+09 | 3290.53 | 23-FEB-16:01 | 26.25 | 17.96 | 93783223.08 | 73.31 | 08-FEB-22:10 | 26.25 | 17.96 |
March | 0.144054E+10 | 3298.02 | 31-MAR-15:02 | 26.90 | 21.51 | 0.103280E+09 | 75.66 | 30-MAR-21:10 | 26.90 | 21.51 |
April | 0.211669E+10 | 3397.70 | 24-APR-08:11 | 28.00 | 17.01 | 97055314.32 | 75.08 | 04-APR-21:10 | 28.00 | 17.01 |
May | 0.323678E+10 | 3306.93 | 31-MAY-18:02 | 40.35 | 22.36 | 99437289.93 | 56.70 | 10-MAY-21:10 | 40.35 | 22.36 |
June | 0.349465E+10 | 3510.05 | 22-JUN-08:51 | 34.00 | 22.19 | 96057199.37 | 56.70 | 02-JUN-21:10 | 34.00 | 22.19 |
July | 0.392993E+10 | 3370.25 | 21-JUL-18:02 | 41.83 | 23.77 | 99147004.24 | 56.70 | 21-JUL-23:00 | 35.00 | 27.35 |
August | 0.396848E+10 | 3356.02 | 16-AUG-18:02 | 40.97 | 26.89 | 99252603.68 | 56.70 | 28-AUG-21:00 | 35.60 | 26.82 |
September | 0.322843E+10 | 3294.46 | 04-SEP-08:62 | 33.72 | 21.14 | 96043104.71 | 56.70 | 07-SEP-21:10 | 33.92 | 27.71 |
October | 0.264061E+10 | 3284.18 | 20-OCT-18:02 | 30.87 | 21.41 | 99484483.15 | 56.70 | 10-OCT-00:10 | 30.87 | 21.41 |
November | 0.169055E+10 | 3268.99 | 25-NOV-16:01 | 26.25 | 18.81 | 97308586.62 | 71.05 | 30-NOV-22:10 | 22.20 | 17.52 |
December | 0.821894E+09 | 3302.99 | 01-DEC-16:01 | 26.75 | 18.64 | 0.103048E+09 | 72.18 | 26-DEC-22:10 | 23.33 | 19.65 |
Annual Sum or Average | 0.278469E+11 | 0.118671E+10 | ||||||||
Minimum of Months | 0.510622E+09 | 3147.61 | 25.83 | 17.01 | 93783223.08 | 56.70 | 22.20 | 17.01 | ||
Maximum of Months | 0.396848E+10 | 3510.05 | 41.83 | 26.89 | 0.103280E+09 | 75.66 | 40.35 | 27.71 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.973297E+09 | 1780.11 | 23-JAN-16:02 | 24.50 | 16.94 | 98798933.66 | 56.69 | 14-JAN-01:30 | 24.50 | 16.94 |
February | 0.978530E+09 | 1805.60 | 05-FEB-19:02 | 27.83 | 20.31 | 89250197.35 | 56.69 | 23-FEB-22:49 | 21.87 | 16.99 |
March | 0.120560E+10 | 1811.75 | 22-MAR-18:02 | 28.50 | 16.26 | 98962047.91 | 56.70 | 23-MAR-22:30 | 23.50 | 20.70 |
April | 0.135884E+10 | 1846.82 | 30-APR-18:02 | 29.95 | 25.20 | 95847709.93 | 56.70 | 28-APR-21:10 | 29.95 | 25.20 |
May | 0.178991E+10 | 1840.38 | 16-MAY-18:02 | 33.02 | 22.56 | 99186327.62 | 56.70 | 04-MAY-21:10 | 33.02 | 22.56 |
June | 0.185674E+10 | 1833.20 | 14-JUN-18:02 | 33.93 | 24.95 | 96028841.02 | 56.70 | 29-JUN-21:10 | 30.95 | 23.07 |
July | 0.214630E+10 | 1850.94 | 30-JUL-15:02 | 40.45 | 27.73 | 99141518.18 | 56.70 | 12-JUL-21:49 | 40.45 | 27.73 |
August | 0.225638E+10 | 1863.73 | 10-AUG-15:02 | 42.02 | 29.59 | 99250851.97 | 56.70 | 25-AUG-21:49 | 33.17 | 29.41 |
September | 0.205401E+10 | 1888.60 | 18-SEP-15:02 | 34.95 | 25.62 | 95957616.63 | 56.70 | 14-SEP-21:49 | 34.95 | 25.62 |
October | 0.198786E+10 | 1885.59 | 06-OCT-15:02 | 34.97 | 26.28 | 99155305.19 | 56.70 | 05-OCT-22:10 | 34.97 | 26.28 |
November | 0.158911E+10 | 1852.67 | 05-NOV-15:02 | 31.90 | 20.93 | 95959761.46 | 56.70 | 01-NOV-21:10 | 31.90 | 20.93 |
December | 0.115515E+10 | 1809.78 | 11-DEC-19:01 | 25.42 | 18.78 | 98871109.49 | 56.69 | 06-DEC-22:00 | 25.42 | 18.78 |
Annual Sum or Average | 0.193517E+11 | 0.116641E+10 | ||||||||
Minimum of Months | 0.973297E+09 | 1780.11 | 24.50 | 16.26 | 89250197.35 | 56.69 | 21.87 | 16.94 | ||
Maximum of Months | 0.225638E+10 | 1888.60 | 42.02 | 29.59 | 99250851.97 | 56.70 | 40.45 | 29.41 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.374986E+11 | 20272.59 | 23-JAN-22:53 | 21.00 | 16.55 | 0.191228E+11 | 11348.69 | 26-JAN-23:10 | 19.83 | 15.00 |
February | 0.352007E+11 | 21516.19 | 07-FEB-23:00 | 24.00 | 19.92 | 0.173490E+11 | 11348.86 | 09-FEB-23:10 | 21.83 | 16.38 |
March | 0.409005E+11 | 22602.07 | 27-MAR-21:10 | 28.82 | 16.04 | 0.193250E+11 | 11348.95 | 09-MAR-23:10 | 28.82 | 16.04 |
April | 0.420582E+11 | 23601.08 | 28-APR-21:10 | 30.82 | 17.97 | 0.186927E+11 | 11348.84 | 04-APR-22:10 | 30.82 | 17.97 |
May | 0.474143E+11 | 24777.52 | 31-MAY-21:10 | 35.87 | 22.27 | 0.193465E+11 | 11347.47 | 13-MAY-01:19 | 35.87 | 22.27 |
June | 0.472282E+11 | 24930.82 | 09-JUN-21:20 | 35.43 | 26.11 | 0.187592E+11 | 11349.50 | 09-JUN-21:19 | 35.43 | 26.11 |
July | 0.500124E+11 | 25618.70 | 21-JUL-21:20 | 39.27 | 19.92 | 0.193092E+11 | 11369.17 | 20-JUL-21:19 | 39.27 | 19.92 |
August | 0.500619E+11 | 25364.14 | 16-AUG-21:20 | 35.43 | 28.26 | 0.193905E+11 | 11370.26 | 16-AUG-21:19 | 35.43 | 28.26 |
September | 0.462609E+11 | 24443.16 | 06-SEP-22:00 | 33.80 | 27.30 | 0.187074E+11 | 11350.37 | 06-SEP-22:30 | 33.40 | 27.13 |
October | 0.454173E+11 | 23691.38 | 05-OCT-21:10 | 31.97 | 24.90 | 0.193049E+11 | 11347.47 | 14-OCT-01:19 | 27.33 | 20.37 |
November | 0.407173E+11 | 22803.00 | 01-NOV-22:00 | 30.00 | 24.33 | 0.186380E+11 | 11348.66 | 21-NOV-23:10 | 20.83 | 15.96 |
December | 0.387997E+11 | 21170.92 | 11-DEC-23:00 | 24.00 | 21.17 | 0.191832E+11 | 11348.84 | 12-DEC-23:10 | 19.00 | 14.29 |
Annual Sum or Average | 0.521570E+12 | 0.227128E+12 | ||||||||
Minimum of Months | 0.352007E+11 | 20272.59 | 21.00 | 16.04 | 0.173490E+11 | 11347.47 | 19.00 | 14.29 | ||
Maximum of Months | 0.500619E+11 | 25618.70 | 39.27 | 28.26 | 0.193905E+11 | 11370.26 | 39.27 | 28.26 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.410572E+11 | 21910.50 | 23-JAN-22:53 | 21.00 | 16.55 | 0.192220E+11 | 11348.70 | 26-JAN-23:10 | 19.83 | 15.00 |
February | 0.382963E+11 | 22951.41 | 07-FEB-22:10 | 24.33 | 19.98 | 0.174098E+11 | 11348.86 | 09-FEB-23:10 | 21.83 | 16.38 |
March | 0.442208E+11 | 23941.39 | 27-MAR-21:10 | 28.82 | 16.04 | 0.193692E+11 | 11348.96 | 09-MAR-23:10 | 28.82 | 16.04 |
April | 0.450736E+11 | 24808.89 | 28-APR-21:10 | 30.82 | 17.97 | 0.187094E+11 | 11348.84 | 04-APR-22:10 | 30.82 | 17.97 |
May | 0.502161E+11 | 25949.32 | 31-MAY-21:20 | 35.53 | 22.46 | 0.193495E+11 | 11351.57 | 31-MAY-21:19 | 35.53 | 22.46 |
June | 0.498935E+11 | 26123.49 | 09-JUN-21:20 | 35.43 | 26.11 | 0.187601E+11 | 11353.89 | 09-JUN-21:19 | 35.43 | 26.11 |
July | 0.527443E+11 | 26804.53 | 21-JUL-21:20 | 39.27 | 19.92 | 0.193099E+11 | 11372.25 | 20-JUL-21:19 | 39.27 | 19.92 |
August | 0.527843E+11 | 26545.42 | 16-AUG-21:20 | 35.43 | 28.26 | 0.193912E+11 | 11372.72 | 16-AUG-21:19 | 35.43 | 28.26 |
September | 0.488887E+11 | 25613.24 | 06-SEP-21:10 | 33.97 | 28.38 | 0.187097E+11 | 11351.45 | 05-SEP-22:30 | 33.97 | 28.38 |
October | 0.481779E+11 | 24869.20 | 05-OCT-21:10 | 31.97 | 24.90 | 0.193139E+11 | 11347.48 | 14-OCT-01:19 | 27.33 | 20.37 |
November | 0.436462E+11 | 24015.47 | 01-NOV-22:00 | 30.00 | 24.33 | 0.186631E+11 | 11348.67 | 21-NOV-23:10 | 20.83 | 15.96 |
December | 0.421969E+11 | 22679.28 | 11-DEC-23:00 | 24.00 | 21.17 | 0.192514E+11 | 11348.84 | 12-DEC-23:10 | 19.00 | 14.29 |
Annual Sum or Average | 0.557196E+12 | 0.227459E+12 | ||||||||
Minimum of Months | 0.382963E+11 | 21910.50 | 21.00 | 16.04 | 0.174098E+11 | 11347.48 | 19.00 | 14.29 | ||
Maximum of Months | 0.527843E+11 | 26804.53 | 39.27 | 28.38 | 0.193912E+11 | 11372.72 | 39.27 | 28.38 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.515324E+11 | 27391.49 | 29-JAN-11:50 | 26.83 | 18.70 | 0.188289E+11 | 11319.62 | 21-JAN-18:19 | 26.83 | 18.70 |
February | 0.473275E+11 | 27956.50 | 05-FEB-11:45 | 30.67 | 18.90 | 0.170132E+11 | 11319.61 | 04-FEB-18:19 | 30.67 | 18.90 |
March | 0.535534E+11 | 28647.69 | 26-MAR-10:45 | 32.33 | 16.61 | 0.188505E+11 | 11319.64 | 18-MAR-17:19 | 32.33 | 16.61 |
April | 0.535216E+11 | 29528.17 | 29-APR-10:50 | 35.95 | 19.83 | 0.182465E+11 | 11319.68 | 29-APR-17:19 | 33.33 | 22.70 |
May | 0.577260E+11 | 29888.35 | 29-MAY-10:33 | 37.30 | 22.20 | 0.188665E+11 | 11319.68 | 06-MAY-17:19 | 37.30 | 22.20 |
June | 0.565261E+11 | 30085.98 | 10-JUN-10:33 | 38.30 | 26.21 | 0.182636E+11 | 11319.77 | 17-JUN-17:19 | 36.67 | 22.74 |
July | 0.591590E+11 | 30663.06 | 30-JUL-10:37 | 44.13 | 22.13 | 0.188675E+11 | 11319.69 | 01-JUL-17:19 | 44.13 | 22.13 |
August | 0.593574E+11 | 30590.01 | 05-AUG-10:33 | 42.43 | 25.20 | 0.188751E+11 | 11319.68 | 26-AUG-17:19 | 35.80 | 28.04 |
September | 0.561575E+11 | 30010.90 | 04-SEP-10:50 | 38.00 | 23.07 | 0.182587E+11 | 11319.69 | 16-SEP-17:19 | 33.00 | 25.65 |
October | 0.565885E+11 | 29503.76 | 09-OCT-10:50 | 35.55 | 20.67 | 0.188611E+11 | 11319.66 | 28-OCT-17:19 | 30.73 | 21.17 |
November | 0.527599E+11 | 28585.88 | 05-NOV-10:45 | 31.82 | 18.97 | 0.182398E+11 | 11319.66 | 04-NOV-17:19 | 31.82 | 18.97 |
December | 0.523351E+11 | 27695.48 | 03-DEC-11:45 | 27.67 | 18.43 | 0.188353E+11 | 11319.70 | 09-DEC-18:19 | 25.80 | 19.58 |
Annual Sum or Average | 0.656544E+12 | 0.222007E+12 | ||||||||
Minimum of Months | 0.473275E+11 | 27391.49 | 26.83 | 16.61 | 0.170132E+11 | 11319.61 | 25.80 | 16.61 | ||
Maximum of Months | 0.593574E+11 | 30663.06 | 44.13 | 26.21 | 0.188751E+11 | 11319.77 | 44.13 | 28.04 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.911975E+10 | 4523.16 | 29-JAN-11:33 | 26.67 | 18.74 | 0.138207E+10 | 865.65 | 30-JAN-00:20 | 22.00 | 19.30 |
February | 0.881145E+10 | 4798.22 | 08-FEB-11:33 | 27.33 | 19.29 | 0.130019E+10 | 933.00 | 07-FEB-22:40 | 27.33 | 19.29 |
March | 0.104126E+11 | 5307.30 | 27-MAR-18:10 | 32.92 | 18.22 | 0.150509E+10 | 978.53 | 27-MAR-21:40 | 28.27 | 15.67 |
April | 0.110696E+11 | 6136.18 | 28-APR-12:20 | 40.23 | 20.93 | 0.153362E+10 | 1007.39 | 28-APR-21:40 | 30.27 | 17.92 |
May | 0.134819E+11 | 7091.76 | 31-MAY-18:40 | 41.40 | 21.47 | 0.168965E+10 | 1007.40 | 31-MAY-21:19 | 35.53 | 22.46 |
June | 0.139504E+11 | 7382.16 | 01-JUN-15:02 | 39.88 | 22.68 | 0.165615E+10 | 1007.40 | 01-JUN-21:19 | 31.77 | 25.51 |
July | 0.157184E+11 | 8199.62 | 21-JUL-12:20 | 44.77 | 24.20 | 0.171246E+10 | 1007.44 | 20-JUL-23:30 | 44.77 | 24.20 |
August | 0.159252E+11 | 8124.40 | 16-AUG-14:10 | 43.33 | 26.52 | 0.172041E+10 | 1007.40 | 10-AUG-21:19 | 43.33 | 26.52 |
September | 0.138542E+11 | 7572.32 | 05-SEP-13:00 | 40.90 | 23.53 | 0.164917E+10 | 1007.39 | 20-SEP-21:30 | 31.80 | 26.09 |
October | 0.128295E+11 | 6734.27 | 04-OCT-12:40 | 37.07 | 20.65 | 0.167134E+10 | 1007.39 | 11-OCT-21:19 | 29.73 | 21.47 |
November | 0.108575E+11 | 5292.49 | 01-NOV-18:05 | 30.93 | 24.44 | 0.151901E+10 | 999.76 | 01-NOV-21:40 | 30.00 | 24.10 |
December | 0.976251E+10 | 4769.06 | 03-DEC-11:33 | 27.33 | 18.33 | 0.143954E+10 | 906.16 | 05-DEC-22:40 | 23.00 | 20.68 |
Annual Sum or Average | 0.145793E+12 | 0.187787E+11 | ||||||||
Minimum of Months | 0.881145E+10 | 4523.16 | 26.67 | 18.22 | 0.130019E+10 | 865.65 | 22.00 | 15.67 | ||
Maximum of Months | 0.159252E+11 | 8199.62 | 44.77 | 26.52 | 0.172041E+10 | 1007.44 | 44.77 | 26.52 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3591339.88 | 1052.01 | 14-JAN-19:04 | 20.00 |
February | 2819521.69 | 1041.55 | 13-FEB-19:04 | 19.92 |
March | 1961144.34 | 1031.43 | 14-MAR-08:04 | 23.17 |
April | 1518083.06 | 1036.99 | 07-APR-08:04 | 24.50 |
May | 244876.13 | 419.76 | 02-MAY-08:04 | 26.50 |
June | 82778.32 | 229.94 | 08-JUN-08:05 | 25.67 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 171264.47 | 302.96 | 25-SEP-08:05 | 25.67 |
October | 349439.92 | 368.21 | 30-OCT-08:04 | 25.50 |
November | 931169.31 | 827.39 | 21-NOV-09:04 | 23.35 |
December | 3201715.53 | 1041.06 | 19-DEC-19:04 | 20.83 |
Annual Sum or Average | 14871332.63 | |||
Minimum of Months | 0.00 | 0.00 | 19.92 | |
Maximum of Months | 3591339.88 | 1052.01 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3559994.38 | 1040.90 | 19-JAN-16:04 | 20.50 |
February | 2051399.44 | 923.48 | 23-FEB-19:04 | 24.50 |
March | 1347885.44 | 878.78 | 11-MAR-09:54 | 22.00 |
April | 563013.89 | 1027.72 | 17-APR-08:04 | 26.50 |
May | 126562.16 | 275.40 | 03-MAY-08:25 | 26.50 |
June | 62526.19 | 313.34 | 22-JUN-08:55 | 34.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 222233.42 | 276.58 | 24-SEP-08:05 | 27.75 |
October | 683447.61 | 892.85 | 30-OCT-08:24 | 26.50 |
November | 1715866.50 | 960.77 | 25-NOV-09:04 | 26.02 |
December | 3108434.99 | 1025.66 | 09-DEC-19:04 | 25.33 |
Annual Sum or Average | 13441364.03 | |||
Minimum of Months | 0.00 | 0.00 | 20.50 | |
Maximum of Months | 3559994.38 | 1040.90 | 34.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 707033.52 | 277.43 | 16-JAN-09:55 | 21.00 |
February | 428193.98 | 344.82 | 11-FEB-16:06 | 21.25 |
March | 569313.57 | 282.00 | 05-MAR-16:06 | 19.50 |
April | 308948.85 | 189.22 | 01-APR-08:55 | 24.00 |
May | 140996.81 | 170.28 | 16-MAY-08:07 | 28.50 |
June | 155544.27 | 100.07 | 29-JUN-08:07 | 35.00 |
July | 167629.34 | 99.45 | 08-JUL-08:07 | 32.17 |
August | 206203.11 | 109.18 | 18-AUG-08:07 | 34.33 |
September | 125718.11 | 73.37 | 08-SEP-08:07 | 31.33 |
October | 256569.14 | 248.31 | 30-OCT-08:26 | 26.50 |
November | 480495.39 | 256.99 | 13-NOV-09:26 | 26.75 |
December | 560195.62 | 274.38 | 30-DEC-09:55 | 22.50 |
Annual Sum or Average | 4106841.72 | |||
Minimum of Months | 125718.11 | 73.37 | 19.50 | |
Maximum of Months | 707033.52 | 344.82 | 35.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1830471.50 | 680.88 | 23-JAN-09:05 | 21.17 |
February | 1329405.02 | 833.96 | 25-FEB-19:04 | 20.33 |
March | 1199780.63 | 712.66 | 04-MAR-19:05 | 22.42 |
April | 191159.16 | 818.46 | 14-APR-08:05 | 22.33 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 71841.94 | 280.81 | 21-NOV-19:05 | 24.27 |
December | 1502876.95 | 813.69 | 11-DEC-09:05 | 23.18 |
Annual Sum or Average | 6125535.21 | |||
Minimum of Months | 0.00 | 0.00 | 20.33 | |
Maximum of Months | 1830471.50 | 833.96 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3172522.11 | 855.01 | 27-JAN-16:05 | 21.42 |
February | 1514038.35 | 866.45 | 13-FEB-16:05 | 22.00 |
March | 905753.31 | 619.22 | 01-MAR-07:45 | 24.83 |
April | 85658.28 | 342.22 | 05-APR-08:55 | 21.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 10435.01 | 121.74 | 30-SEP-06:56 | 25.60 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 660419.28 | 591.19 | 23-NOV-19:05 | 25.75 |
December | 2439163.93 | 860.27 | 18-DEC-16:05 | 23.00 |
Annual Sum or Average | 8787990.27 | |||
Minimum of Months | 0.00 | 0.00 | 21.00 | |
Maximum of Months | 3172522.11 | 866.45 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4823720.50 | 1074.37 | 14-JAN-19:04 | 20.00 |
February | 2662188.16 | 1093.82 | 20-FEB-16:04 | 17.83 |
March | 2287948.83 | 966.97 | 06-MAR-19:04 | 21.17 |
April | 1644310.51 | 1016.88 | 10-APR-08:04 | 25.25 |
May | 271887.00 | 815.81 | 03-MAY-08:04 | 25.50 |
June | 62100.26 | 219.86 | 08-JUN-08:05 | 25.67 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 184402.64 | 373.35 | 25-SEP-08:05 | 25.67 |
October | 1145530.39 | 931.15 | 30-OCT-08:04 | 25.50 |
November | 1713306.33 | 1026.22 | 21-NOV-09:04 | 23.35 |
December | 3961438.01 | 1027.44 | 29-DEC-19:04 | 21.00 |
Annual Sum or Average | 18756832.64 | |||
Minimum of Months | 0.00 | 0.00 | 17.83 | |
Maximum of Months | 4823720.50 | 1093.82 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6256000.73 | 1077.70 | 02-JAN-16:04 | 21.17 |
February | 2120275.38 | 892.82 | 05-FEB-09:53 | 27.30 |
March | 1539898.84 | 856.66 | 28-MAR-08:04 | 26.03 |
April | 652619.05 | 961.24 | 17-APR-08:04 | 26.50 |
May | 116088.82 | 153.05 | 07-MAY-08:05 | 28.83 |
June | 42590.65 | 206.86 | 08-JUN-08:05 | 25.67 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 318105.76 | 675.48 | 30-SEP-06:54 | 25.60 |
October | 1283929.19 | 968.88 | 25-OCT-08:04 | 26.33 |
November | 1870113.70 | 1007.77 | 20-NOV-09:04 | 27.02 |
December | 3340320.52 | 1093.68 | 16-DEC-16:04 | 21.42 |
Annual Sum or Average | 17539942.64 | |||
Minimum of Months | 0.00 | 0.00 | 21.17 | |
Maximum of Months | 6256000.73 | 1093.68 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 664340.49 | 367.87 | 25-JAN-19:05 | 20.00 |
February | 622151.28 | 418.26 | 12-FEB-19:05 | 19.25 |
March | 530818.94 | 355.36 | 17-MAR-08:04 | 19.00 |
April | 360405.98 | 332.58 | 04-APR-08:05 | 22.33 |
May | 439799.73 | 409.70 | 02-MAY-08:04 | 26.50 |
June | 181314.98 | 362.64 | 08-JUN-08:05 | 25.67 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 89694.68 | 224.66 | 25-SEP-08:05 | 25.67 |
October | 54626.68 | 175.34 | 11-OCT-08:05 | 27.50 |
November | 25547.99 | 255.48 | 22-NOV-09:05 | 20.48 |
December | 479538.33 | 421.66 | 27-DEC-09:05 | 21.18 |
Annual Sum or Average | 3448239.07 | |||
Minimum of Months | 0.00 | 0.00 | 19.00 | |
Maximum of Months | 664340.49 | 421.66 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.962539E+10 | 9271.23 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.869085E+10 | 9271.23 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.965507E+10 | 9271.23 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.929905E+10 | 9271.23 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.964208E+10 | 9271.23 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.934170E+10 | 9271.23 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.959943E+10 | 9271.23 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.965878E+10 | 9271.23 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.930276E+10 | 9271.23 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.962169E+10 | 9271.23 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.933428E+10 | 9271.23 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.959943E+10 | 9271.23 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.113371E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.869085E+10 | 9271.23 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.965878E+10 | 9271.23 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.531884E+09 | 512.31 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.480243E+09 | 512.31 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.533523E+09 | 512.31 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.513850E+09 | 512.31 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.532806E+09 | 512.31 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.516207E+09 | 512.31 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.530449E+09 | 512.31 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.533728E+09 | 512.31 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.514055E+09 | 512.31 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.531679E+09 | 512.31 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.515797E+09 | 512.31 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.530449E+09 | 512.31 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.626467E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.480243E+09 | 512.31 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.533728E+09 | 512.31 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.615923E+09 | 593.26 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.556123E+09 | 593.26 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.617822E+09 | 593.26 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.595041E+09 | 593.26 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.616991E+09 | 593.26 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.597770E+09 | 593.26 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.614262E+09 | 593.26 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.618059E+09 | 593.26 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.595278E+09 | 593.26 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.615686E+09 | 593.26 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.597295E+09 | 593.26 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.614262E+09 | 593.26 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.725451E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.556123E+09 | 593.26 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.618059E+09 | 593.26 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.158446E+09 | 152.61 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.143062E+09 | 152.61 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.158934E+09 | 152.61 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.153074E+09 | 152.61 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.158720E+09 | 152.61 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.153776E+09 | 152.61 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.158018E+09 | 152.61 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.158995E+09 | 152.61 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.153135E+09 | 152.61 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.158385E+09 | 152.61 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.153654E+09 | 152.61 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.158018E+09 | 152.61 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.186622E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.143062E+09 | 152.61 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.158995E+09 | 152.61 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.415991E+09 | 400.68 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.375602E+09 | 400.68 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.417273E+09 | 400.68 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.401887E+09 | 400.68 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.416712E+09 | 400.68 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.403730E+09 | 400.68 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.414869E+09 | 400.68 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.417433E+09 | 400.68 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.402047E+09 | 400.68 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.415830E+09 | 400.68 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.403409E+09 | 400.68 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.414869E+09 | 400.68 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.489965E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.375602E+09 | 400.68 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.417433E+09 | 400.68 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.119349E+10 | 1573.46 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.105850E+10 | 1573.46 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.113458E+10 | 1573.46 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.104387E+10 | 1573.46 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.104260E+10 | 1573.46 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.976463E+09 | 1573.46 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.103261E+10 | 1573.46 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.106219E+10 | 1573.46 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.106604E+10 | 1573.46 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.115880E+10 | 1573.46 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.112755E+10 | 1573.46 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.118824E+10 | 1573.46 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.130849E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.976463E+09 | 1573.46 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.119349E+10 | 1573.46 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105297E+11 | 10645.38 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.949292E+10 | 10645.38 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.105094E+11 | 10645.38 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.100700E+11 | 10645.38 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.104002E+11 | 10645.38 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.100434E+11 | 10645.38 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.103511E+11 | 10645.38 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.104341E+11 | 10645.38 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.100941E+11 | 10645.38 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.104939E+11 | 10645.38 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.101760E+11 | 10645.38 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.105009E+11 | 10645.38 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.123096E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.949292E+10 | 10645.38 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.105297E+11 | 10645.38 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82476868.03 | 74.62 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 74484663.28 | 74.62 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 81821381.83 | 74.62 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 79911301.67 | 74.62 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 82149124.93 | 74.62 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 79277307.08 | 74.62 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 82793865.32 | 74.62 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 81821381.83 | 74.62 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 79932793.28 | 74.62 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 82466122.22 | 74.62 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 79594304.38 | 74.62 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 82804611.13 | 74.62 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.969534E+09 | 0.300992E+10 | ||||
Minimum of Months | 74484663.28 | 74.62 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 82804611.13 | 74.62 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82499421.18 | 74.64 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 74505030.97 | 74.64 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 81843755.73 | 74.64 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 79933153.27 | 74.64 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 82171588.45 | 74.64 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 79298985.31 | 74.64 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 82816505.16 | 74.64 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 81843755.73 | 74.64 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 79954650.76 | 74.64 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 82488672.43 | 74.64 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 79616069.29 | 74.64 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 82827253.90 | 74.64 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.969799E+09 | 0.301074E+10 | ||||
Minimum of Months | 74505030.97 | 74.64 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 82827253.90 | 74.64 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.120431E+10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.108739E+10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.120803E+10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.116348E+10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.120640E+10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.116882E+10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.120107E+10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.120849E+10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.116395E+10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.120385E+10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.116789E+10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.120107E+10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.141847E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.108739E+10 | 1160.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120849E+10 | 1160.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82499421.18 | 74.64 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 74505030.97 | 74.64 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 81843755.73 | 74.64 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 79933153.27 | 74.64 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 82171588.45 | 74.64 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 79298985.31 | 74.64 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 82816505.16 | 74.64 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 81843755.73 | 74.64 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 79954650.76 | 74.64 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 82488672.43 | 74.64 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 79616069.29 | 74.64 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 82827253.90 | 74.64 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.969799E+09 | 0.301074E+10 | ||||
Minimum of Months | 74505030.97 | 74.64 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 82827253.90 | 74.64 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.252113E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.224559E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.244599E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.229598E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.232385E+10 | 2763.12 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.221570E+10 | 2763.12 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.231595E+10 | 2763.12 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.235863E+10 | 2763.12 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.232533E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.247170E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.241331E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.251598E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.284492E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.221570E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.252113E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.252113E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.224559E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.244599E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.229598E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.232385E+10 | 2763.12 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.221570E+10 | 2763.12 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.231595E+10 | 2763.12 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.235863E+10 | 2763.12 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.232533E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.247170E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.241331E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.251598E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.284492E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.221570E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.252113E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113250E+10 | 1090.83 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.102255E+10 | 1090.83 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.113599E+10 | 1090.83 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.109410E+10 | 1090.83 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.113446E+10 | 1090.83 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.109912E+10 | 1090.83 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.112945E+10 | 1090.83 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.113643E+10 | 1090.83 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.109454E+10 | 1090.83 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.113207E+10 | 1090.83 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.109825E+10 | 1090.83 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.112945E+10 | 1090.83 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.133389E+11 | 0.424019E+12 | ||||
Minimum of Months | 0.102255E+10 | 1090.83 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.113643E+10 | 1090.83 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.127458E+10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.115083E+10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.127851E+10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.123137E+10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.127679E+10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.123701E+10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.127114E+10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.127900E+10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.123186E+10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.127409E+10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.123603E+10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.127114E+10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.150123E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.115083E+10 | 1227.68 | 0.00 | 0.00 | |
Maximum of Months | 0.127900E+10 | 1227.68 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.962539E+10 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.869085E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.965507E+10 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.929905E+10 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.964208E+10 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.934170E+10 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.959943E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.965878E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.930276E+10 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.962169E+10 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.933428E+10 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.959943E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.113371E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.869085E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.965878E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.531884E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1134535.29 | 24310634.18 |
February | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077896.27 | 15799015.05 |
March | 0.199990E+10 | 0.533523E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12890529.40 | 9029016.11 |
April | 0.192973E+10 | 0.513850E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28338162.02 | 2284129.69 |
May | 0.199475E+10 | 0.532806E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58584366.55 | 85556.10 |
June | 0.193394E+10 | 0.516207E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66312303.03 | 6644.64 |
July | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82821669.88 | 0.00 |
August | 0.199896E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84498883.05 | 0.00 |
September | 0.192879E+10 | 0.514055E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63045772.30 | 285.26 |
October | 0.199148E+10 | 0.531679E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44707627.95 | 83892.39 |
November | 0.192552E+10 | 0.515797E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20133284.80 | 3388506.52 |
December | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4636462.17 | 15461746.18 |
Annual Sum or Average | 0.234744E+11 | 0.626467E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471181E+09 | 70449426.13 |
Minimum of Months | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1134535.29 | 0.00 |
Maximum of Months | 0.199990E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84498883.05 | 24310634.18 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.615923E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 560828.04 | 12605753.61 |
February | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1678750.97 | 8718720.52 |
March | 0.231589E+10 | 0.617822E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4692732.53 | 5672090.92 |
April | 0.223463E+10 | 0.595041E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10201839.87 | 1939245.82 |
May | 0.230993E+10 | 0.616991E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22131202.46 | 111302.76 |
June | 0.223950E+10 | 0.597770E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25413300.33 | 4389.02 |
July | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32040814.74 | 0.00 |
August | 0.231480E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32705558.08 | 0.00 |
September | 0.223354E+10 | 0.595278E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24195999.87 | 8639.19 |
October | 0.230614E+10 | 0.615686E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16888013.14 | 144230.94 |
November | 0.222975E+10 | 0.597295E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7679795.78 | 2439479.54 |
December | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1862892.88 | 8670144.06 |
Annual Sum or Average | 0.271834E+11 | 0.725451E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180052E+09 | 40313996.37 |
Minimum of Months | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 560828.04 | 0.00 |
Maximum of Months | 0.231589E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32705558.08 | 12605753.61 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1784628.81 | 25796026.85 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4537440.17 | 17773476.67 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12077890.43 | 11424024.75 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24779022.58 | 3806146.00 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51822115.17 | 222280.31 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59379150.59 | 10450.72 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75195257.36 | 0.00 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76898897.27 | 0.00 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56787579.72 | 18424.62 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39924632.97 | 279009.69 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18952772.27 | 4864751.40 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5120440.19 | 17736896.95 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427260E+09 | 81931487.95 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1784628.81 | 0.00 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76898897.27 | 25796026.85 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.158446E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1045255.27 | 14367940.34 |
February | 0.339028E+09 | 0.143062E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2673887.06 | 9832482.36 |
March | 0.376747E+09 | 0.158934E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7152448.34 | 6234040.63 |
April | 0.363528E+09 | 0.153074E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14614902.15 | 2029091.27 |
May | 0.375778E+09 | 0.158720E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29999270.66 | 113284.14 |
June | 0.364321E+09 | 0.153776E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34237157.06 | 6013.34 |
July | 0.374985E+09 | 0.158018E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43372884.64 | 0.00 |
August | 0.376571E+09 | 0.158995E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44357673.77 | 0.00 |
September | 0.363352E+09 | 0.153135E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32762656.42 | 8288.25 |
October | 0.375161E+09 | 0.158385E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23204399.22 | 138833.98 |
November | 0.362735E+09 | 0.153654E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11235197.06 | 2613368.79 |
December | 0.374985E+09 | 0.158018E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3054799.08 | 9782043.47 |
Annual Sum or Average | 0.442217E+10 | 0.186622E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247711E+09 | 45125386.57 |
Minimum of Months | 0.339028E+09 | 0.143062E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1045255.27 | 0.00 |
Maximum of Months | 0.376747E+09 | 0.158995E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44357673.77 | 14367940.34 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.415991E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 1749028.99 | 40398352.69 |
February | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 5695142.81 | 26976263.48 |
March | 0.155131E+10 | 0.417273E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 16305019.70 | 16505291.06 |
April | 0.149688E+10 | 0.401887E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 35547919.47 | 4483761.71 |
May | 0.154732E+10 | 0.416712E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 77863497.73 | 261759.38 |
June | 0.150015E+10 | 0.403730E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 88709392.04 | 14231.27 |
July | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.110562E+09 | 0.00 |
August | 0.155059E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.112929E+09 | 0.00 |
September | 0.149615E+10 | 0.402047E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 85113730.37 | 15922.72 |
October | 0.154478E+10 | 0.415830E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 61174644.46 | 251027.89 |
November | 0.149361E+10 | 0.403409E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 27749244.93 | 5529117.64 |
December | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 6511342.26 | 26338069.62 |
Annual Sum or Average | 0.182090E+11 | 0.489965E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.629910E+09 | 0.120774E+09 |
Minimum of Months | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 1749028.99 | 0.00 |
Maximum of Months | 0.155131E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.112929E+09 | 40398352.69 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.119349E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1966938.25 | 74256171.38 |
February | 0.236489E+11 | 0.105850E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8067448.49 | 50527106.69 |
March | 0.262800E+11 | 0.113458E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25697519.12 | 31786083.35 |
April | 0.253579E+11 | 0.104387E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58738003.43 | 10758815.41 |
May | 0.262123E+11 | 0.104260E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128012E+09 | 535545.40 |
June | 0.254132E+11 | 0.976463E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146988E+09 | 14475.14 |
July | 0.261570E+11 | 0.103261E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184126E+09 | 0.00 |
August | 0.262677E+11 | 0.106219E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187625E+09 | 0.00 |
September | 0.253456E+11 | 0.106604E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138508E+09 | 44199.75 |
October | 0.261693E+11 | 0.115880E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95924882.81 | 718363.69 |
November | 0.253025E+11 | 0.112755E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41842927.85 | 13828387.80 |
December | 0.261570E+11 | 0.118824E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8660645.60 | 50429758.81 |
Annual Sum or Average | 0.308468E+12 | 0.130849E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102616E+10 | 0.232899E+09 |
Minimum of Months | 0.236489E+11 | 0.976463E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1966938.25 | 0.00 |
Maximum of Months | 0.262800E+11 | 0.119349E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187625E+09 | 74256171.38 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.105297E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6850116.75 | 0.224169E+09 |
February | 0.702046E+11 | 0.949292E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24907256.06 | 0.154624E+09 |
March | 0.780153E+11 | 0.105094E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73611495.72 | 99729567.47 |
April | 0.752779E+11 | 0.100700E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165294E+09 | 34323539.66 |
May | 0.778146E+11 | 0.104002E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363658E+09 | 1836442.95 |
June | 0.754422E+11 | 0.100434E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417779E+09 | 69029.34 |
July | 0.776503E+11 | 0.103511E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526027E+09 | 0.00 |
August | 0.779788E+11 | 0.104341E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536497E+09 | 0.00 |
September | 0.752414E+11 | 0.100941E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395947E+09 | 139252.59 |
October | 0.776868E+11 | 0.104939E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274761E+09 | 2416442.93 |
November | 0.751137E+11 | 0.101760E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122480E+09 | 42185141.85 |
December | 0.776503E+11 | 0.105009E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26813813.80 | 0.153660E+09 |
Annual Sum or Average | 0.915726E+12 | 0.123096E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293463E+10 | 0.713152E+09 |
Minimum of Months | 0.702046E+11 | 0.949292E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6850116.75 | 0.00 |
Maximum of Months | 0.780153E+11 | 0.105297E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536497E+09 | 0.224169E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1089900.73 | 12775429.33 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3642098.07 | 7934809.03 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10146306.31 | 4181421.08 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21079300.54 | 818576.86 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42091034.99 | 14993.73 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46990016.06 | 3890.49 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57365078.42 | 0.00 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58467621.70 | 0.00 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45389559.40 | 0.00 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34441475.60 | 7607.62 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17278900.65 | 946374.47 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4407119.54 | 7385018.77 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342388E+09 | 34068121.37 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1089900.73 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58467621.70 | 12775429.33 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 839839.54 | 14222232.26 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3238005.09 | 9469331.25 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9556519.05 | 5401454.34 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20646887.92 | 1222236.07 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41981370.65 | 71414.33 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46964044.31 | 6788.78 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57357003.82 | 0.00 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58462468.88 | 0.00 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45345863.51 | 225.55 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34265317.91 | 50758.42 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16799330.47 | 1342802.71 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3815219.62 | 8670913.81 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339272E+09 | 40458157.52 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 839839.54 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58462468.88 | 14222232.26 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 82476868.03 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4872.16 | 9760380.85 |
February | 0.00 | 74484663.28 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 185389.67 | 7185135.78 |
March | 0.00 | 81821381.83 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 680437.81 | 5328779.24 |
April | 0.00 | 79911301.67 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1989035.15 | 2348641.09 |
May | 0.00 | 82149124.93 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5995283.60 | 328743.07 |
June | 0.00 | 79277307.08 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7361239.55 | 46744.80 |
July | 0.00 | 82793865.32 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10068296.46 | 0.00 |
August | 0.00 | 81821381.83 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10366757.51 | 0.00 |
September | 0.00 | 79932793.28 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6887939.36 | 74080.08 |
October | 0.00 | 82466122.22 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4011651.66 | 551402.17 |
November | 0.00 | 79594304.38 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1192633.86 | 2698701.67 |
December | 0.00 | 82804611.13 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68226.02 | 7322237.10 |
Annual Sum or Average | 0.00 | 0.969534E+09 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48811762.81 | 35644845.85 |
Minimum of Months | 0.00 | 74484663.28 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4872.16 | 0.00 |
Maximum of Months | 0.00 | 82804611.13 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10366757.51 | 9760380.85 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 82499421.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 267234.05 | 3989417.58 |
February | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 938269.80 | 2605477.27 |
March | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2712580.11 | 1462845.23 |
April | 0.293479E+09 | 79933153.27 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5807558.06 | 315846.77 |
May | 0.303504E+09 | 82171588.45 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11746657.55 | 14560.73 |
June | 0.293842E+09 | 79298985.31 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13131379.96 | 1332.25 |
July | 0.303141E+09 | 82816505.16 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16028590.19 | 0.00 |
August | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16339093.98 | 0.00 |
September | 0.293479E+09 | 79954650.76 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12686034.25 | 0.00 |
October | 0.303322E+09 | 82488672.43 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9608292.86 | 9262.24 |
November | 0.293661E+09 | 79616069.29 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4746153.65 | 355108.37 |
December | 0.303141E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1117301.07 | 2445143.78 |
Annual Sum or Average | 0.357224E+10 | 0.969799E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95129145.54 | 11198994.22 |
Minimum of Months | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 267234.05 | 0.00 |
Maximum of Months | 0.303685E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16339093.98 | 3989417.58 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1078538.86 | 12886918.17 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3628572.02 | 8000401.25 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10130235.14 | 4222219.43 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21053629.54 | 836105.87 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42066966.45 | 15684.25 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46975939.75 | 3891.61 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57353380.19 | 0.00 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58455763.85 | 0.00 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45374824.16 | 0.00 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34418717.16 | 8760.22 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17257068.82 | 963181.89 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4389725.49 | 7449491.27 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342183E+09 | 34386653.96 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1078538.86 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58455763.85 | 12886918.17 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 809136.10 | 14308742.17 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3202166.31 | 9512637.84 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9529957.94 | 5402693.57 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20546185.57 | 1312450.79 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41948932.61 | 91600.91 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46945277.84 | 8596.58 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57343949.87 | 0.00 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58450795.53 | 0.00 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45328311.06 | 607.69 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34209269.34 | 71891.09 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16677735.64 | 1521531.62 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3781633.59 | 8774506.35 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338773E+09 | 41005258.61 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 809136.10 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58450795.53 | 14308742.17 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.120431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1501208.58 | 18423842.51 |
February | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3626622.63 | 12853176.70 |
March | 0.387034E+10 | 0.120803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9583016.34 | 8176939.27 |
April | 0.373454E+10 | 0.116348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19622443.36 | 2653476.37 |
May | 0.386038E+10 | 0.120640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40088358.88 | 152793.15 |
June | 0.374269E+10 | 0.116882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45682119.86 | 7344.10 |
July | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57743839.79 | 0.00 |
August | 0.386853E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59020381.88 | 0.00 |
September | 0.373273E+10 | 0.116395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43611253.23 | 11238.57 |
October | 0.385404E+10 | 0.120385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30703830.80 | 192893.10 |
November | 0.372639E+10 | 0.116789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14832462.38 | 3481825.07 |
December | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4148469.38 | 12659989.09 |
Annual Sum or Average | 0.454292E+11 | 0.141847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330164E+09 | 58613517.93 |
Minimum of Months | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1501208.58 | 0.00 |
Maximum of Months | 0.387034E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59020381.88 | 18423842.51 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1039166.35 | 12920331.39 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3557133.91 | 8042222.22 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9979444.35 | 4238728.78 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20858530.65 | 833747.11 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41837347.95 | 15540.17 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46746397.13 | 4071.19 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57117459.60 | 0.00 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58221301.51 | 0.00 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45147993.78 | 0.00 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34190670.20 | 7532.93 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17066461.83 | 972296.86 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4290195.63 | 7478152.19 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340052E+09 | 34512622.85 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1039166.35 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58221301.51 | 12920331.39 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 796409.46 | 14268090.52 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3174001.67 | 9511411.84 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9418982.78 | 5387340.18 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20458686.68 | 1147805.19 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41734107.97 | 61700.01 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46721151.62 | 6839.40 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57109222.98 | 0.00 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58215479.41 | 0.00 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45107843.08 | 0.00 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34037314.99 | 36242.84 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16637524.69 | 1250764.87 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3731250.09 | 8608978.47 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337142E+09 | 40279173.32 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 796409.46 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58215479.41 | 14268090.52 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 82499421.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 520485.98 | 6727462.94 |
February | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1808131.31 | 4164732.38 |
March | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5096819.49 | 2186116.59 |
April | 0.293479E+09 | 79933153.27 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10672500.69 | 430998.59 |
May | 0.303504E+09 | 82171588.45 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21414444.02 | 7854.45 |
June | 0.293842E+09 | 79298985.31 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23927902.27 | 2082.56 |
July | 0.303141E+09 | 82816505.16 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29229206.80 | 0.00 |
August | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29790900.86 | 0.00 |
September | 0.293479E+09 | 79954650.76 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23098737.41 | 0.00 |
October | 0.303322E+09 | 82488672.43 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17481106.64 | 4517.93 |
November | 0.293661E+09 | 79616069.29 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8708805.05 | 509558.90 |
December | 0.303141E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2169659.87 | 3890791.89 |
Annual Sum or Average | 0.357224E+10 | 0.969799E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173919E+09 | 17924116.24 |
Minimum of Months | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 520485.98 | 0.00 |
Maximum of Months | 0.303685E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29790900.86 | 6727462.94 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.252113E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 992566.73 | 54133697.64 |
February | 0.415303E+11 | 0.224559E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4625488.43 | 37681747.81 |
March | 0.461508E+11 | 0.244599E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13875994.05 | 24306562.62 |
April | 0.445315E+11 | 0.229598E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33486063.04 | 8354442.41 |
May | 0.460320E+11 | 0.232385E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78344083.77 | 469097.54 |
June | 0.446286E+11 | 0.221570E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91010170.93 | 18930.81 |
July | 0.459349E+11 | 0.231595E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115766E+09 | 0.00 |
August | 0.461292E+11 | 0.235863E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118432E+09 | 0.00 |
September | 0.445099E+11 | 0.232533E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86928808.66 | 37893.89 |
October | 0.459565E+11 | 0.247170E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59681784.43 | 624122.00 |
November | 0.444343E+11 | 0.241331E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25560842.71 | 10009932.49 |
December | 0.459349E+11 | 0.251598E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4749713.64 | 36928752.01 |
Annual Sum or Average | 0.541708E+12 | 0.284492E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633454E+09 | 0.172565E+09 |
Minimum of Months | 0.415303E+11 | 0.221570E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 992566.73 | 0.00 |
Maximum of Months | 0.461508E+11 | 0.252113E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118432E+09 | 54133697.64 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.252113E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 783512.71 | 55186570.27 |
February | 0.415303E+11 | 0.224559E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4350769.85 | 38252116.34 |
March | 0.461508E+11 | 0.244599E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13476890.00 | 24565119.66 |
April | 0.445315E+11 | 0.229598E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33236580.59 | 8379730.13 |
May | 0.460320E+11 | 0.232385E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78297030.91 | 469896.21 |
June | 0.446286E+11 | 0.221570E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90995926.96 | 18931.78 |
July | 0.459349E+11 | 0.231595E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115757E+09 | 0.00 |
August | 0.461292E+11 | 0.235863E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118421E+09 | 0.00 |
September | 0.445099E+11 | 0.232533E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86892116.98 | 37896.81 |
October | 0.459565E+11 | 0.247170E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59531017.10 | 624158.82 |
November | 0.444343E+11 | 0.241331E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25177058.75 | 10021470.77 |
December | 0.459349E+11 | 0.251598E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4328504.25 | 37431906.45 |
Annual Sum or Average | 0.541708E+12 | 0.284492E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631247E+09 | 0.174988E+09 |
Minimum of Months | 0.415303E+11 | 0.221570E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 783512.71 | 0.00 |
Maximum of Months | 0.461508E+11 | 0.252113E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118421E+09 | 55186570.27 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113250E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 564356.94 | 48722369.08 |
February | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 3709022.53 | 33399461.04 |
March | 0.410691E+10 | 0.113599E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 11918555.56 | 21193175.77 |
April | 0.396281E+10 | 0.109410E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 29763389.39 | 6964189.93 |
May | 0.409635E+10 | 0.113446E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 70306695.09 | 404482.31 |
June | 0.397146E+10 | 0.109912E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 81582177.44 | 16867.11 |
July | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.103685E+09 | 0.00 |
August | 0.410499E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.106055E+09 | 0.00 |
September | 0.396089E+10 | 0.109454E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 77921894.76 | 33805.46 |
October | 0.408962E+10 | 0.113207E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 53524044.46 | 500460.44 |
November | 0.395417E+10 | 0.109825E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 22444717.82 | 8264408.09 |
December | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3588730.94 | 32588107.68 |
Annual Sum or Average | 0.482060E+11 | 0.133389E+11 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.565064E+09 | 0.152087E+09 |
Minimum of Months | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 564356.94 | 0.00 |
Maximum of Months | 0.410691E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.106055E+09 | 48722369.08 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.127458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2486813.57 | 29773151.11 |
February | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6091481.63 | 20584289.55 |
March | 0.409620E+10 | 0.127851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16306176.04 | 12894940.56 |
April | 0.395248E+10 | 0.123137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33454281.05 | 4035348.30 |
May | 0.408566E+10 | 0.127679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69985168.77 | 209221.34 |
June | 0.396110E+10 | 0.123701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80241739.38 | 12685.50 |
July | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101508E+09 | 0.00 |
August | 0.409429E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103806E+09 | 0.00 |
September | 0.395056E+10 | 0.123186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76792898.53 | 8830.78 |
October | 0.407896E+10 | 0.127409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54305872.99 | 210515.93 |
November | 0.394385E+10 | 0.123603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26255039.65 | 4911336.70 |
December | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7402201.85 | 19740408.57 |
Annual Sum or Average | 0.480803E+11 | 0.150123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578636E+09 | 92380728.33 |
Minimum of Months | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2486813.57 | 0.00 |
Maximum of Months | 0.409620E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103806E+09 | 29773151.11 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 9271.23 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 9271.23 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 9271.23 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 9271.23 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 9271.23 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 9271.23 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 9271.23 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 9271.23 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 9271.23 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 9271.23 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 9271.23 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 9271.23 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 512.31 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.80 | 23-JAN-14:00 | 27.66 | 09-JAN-08:00 |
February | 1169.53 | 01-FEB-00:10 | 512.31 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 06-FEB-15:00 | 25.11 | 01-FEB-05:20 |
March | 1169.53 | 01-MAR-00:10 | 512.31 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.33 | 27-MAR-10:55 | 21.65 | 08-MAR-06:00 |
April | 1169.53 | 01-APR-00:10 | 512.31 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.49 | 28-APR-12:00 | 14.36 | 05-APR-05:00 |
May | 1169.53 | 01-MAY-00:10 | 512.31 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.43 | 31-MAY-19:00 | 6.49 | 01-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 512.31 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.60 | 12-JUN-12:00 | 6.73 | 22-JUN-07:53 |
July | 1169.53 | 01-JUL-00:10 | 512.31 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.88 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 1169.53 | 01-AUG-00:10 | 512.31 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.19 | 16-AUG-12:00 | 0.00 | 01-AUG-00:05 |
September | 1169.53 | 01-SEP-00:10 | 512.31 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.42 | 26-SEP-13:00 | 0.17 | 25-SEP-05:00 |
October | 1169.53 | 01-OCT-23:10 | 512.31 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.05 | 04-OCT-12:00 | 6.38 | 29-OCT-07:00 |
November | 1169.53 | 01-NOV-00:10 | 512.31 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.41 | 05-NOV-12:00 | 15.21 | 22-NOV-07:00 |
December | 1169.53 | 01-DEC-00:10 | 512.31 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.07 | 10-DEC-11:55 | 24.77 | 30-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 12.80 | 0.00 | |||||
Maximum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 59.19 | 27.66 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 593.26 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.88 | 23-JAN-14:00 | 13.20 | 19-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 593.26 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.20 | 06-FEB-15:00 | 12.16 | 01-FEB-05:40 |
March | 1354.32 | 01-MAR-00:10 | 593.26 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.21 | 27-MAR-10:55 | 10.80 | 08-MAR-06:00 |
April | 1354.32 | 01-APR-00:10 | 593.26 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.89 | 28-APR-12:00 | 7.66 | 05-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 593.26 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.08 | 31-MAY-19:00 | 4.11 | 01-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 593.26 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.46 | 12-JUN-12:00 | 3.38 | 22-JUN-07:53 |
July | 1354.32 | 01-JUL-00:10 | 593.26 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 1354.32 | 01-AUG-00:10 | 593.26 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.20 | 16-AUG-12:00 | 0.00 | 01-AUG-00:05 |
September | 1354.32 | 01-SEP-00:10 | 593.26 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.71 | 26-SEP-13:00 | 1.13 | 25-SEP-05:23 |
October | 1354.32 | 01-OCT-23:10 | 593.26 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.63 | 04-OCT-12:00 | 3.90 | 29-OCT-07:00 |
November | 1354.32 | 01-NOV-00:10 | 593.26 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.49 | 05-NOV-12:00 | 7.91 | 22-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 593.26 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.80 | 10-DEC-11:55 | 12.01 | 30-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 5.88 | 0.00 | |||||
Maximum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 23.20 | 13.20 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.92 | 28-JAN-14:00 | 29.46 | 19-JAN-07:40 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.81 | 06-FEB-15:00 | 26.95 | 01-FEB-06:10 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.28 | 27-MAR-10:55 | 23.48 | 08-MAR-06:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.48 | 28-APR-12:00 | 16.87 | 05-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.10 | 31-MAY-19:00 | 9.05 | 01-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.32 | 12-JUN-12:00 | 7.99 | 22-JUN-07:53 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.72 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 | 16-AUG-12:00 | 0.00 | 01-AUG-00:05 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.76 | 26-SEP-13:00 | 2.65 | 25-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.32 | 04-OCT-12:00 | 8.56 | 29-OCT-07:00 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.36 | 05-NOV-12:00 | 17.54 | 22-NOV-07:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 | 10-DEC-11:55 | 26.52 | 31-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 14.92 | 0.00 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 | 29.46 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 152.61 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.53 | 28-JAN-14:00 | 16.64 | 19-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 152.61 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 06-FEB-15:00 | 15.31 | 01-FEB-05:30 |
March | 220.32 | 01-MAR-00:10 | 152.61 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.04 | 27-MAR-10:55 | 13.37 | 08-MAR-06:00 |
April | 220.32 | 01-APR-00:10 | 152.61 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.73 | 28-APR-12:00 | 9.39 | 05-APR-05:50 |
May | 220.32 | 01-MAY-00:10 | 152.61 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.02 | 31-MAY-19:00 | 4.93 | 01-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 152.61 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.19 | 12-JUN-12:00 | 4.61 | 22-JUN-07:53 |
July | 220.32 | 01-JUL-00:10 | 152.61 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.99 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 220.32 | 01-AUG-00:10 | 152.61 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.15 | 16-AUG-12:00 | 0.00 | 01-AUG-00:05 |
September | 220.32 | 01-SEP-00:10 | 152.61 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.13 | 26-SEP-13:00 | 1.27 | 25-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 152.61 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.86 | 04-OCT-12:00 | 4.63 | 29-OCT-07:00 |
November | 220.32 | 01-NOV-00:10 | 152.61 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.77 | 05-NOV-12:00 | 9.79 | 22-NOV-07:00 |
December | 220.32 | 01-DEC-00:10 | 152.61 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.86 | 10-DEC-11:55 | 15.09 | 30-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 8.53 | 0.00 | |||||
Maximum of Months | 220.32 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 31.15 | 16.64 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 400.68 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 18.59 | 28-JAN-14:00 | 45.94 | 09-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 400.68 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 34.30 | 05-FEB-16:20 | 41.84 | 14-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 400.68 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 55.14 | 27-MAR-10:55 | 37.33 | 08-MAR-06:10 |
April | 907.20 | 01-APR-00:10 | 400.68 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 67.24 | 28-APR-12:00 | 26.18 | 05-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 400.68 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 63.65 | 09-MAY-12:00 | 13.25 | 01-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 400.68 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 69.85 | 12-JUN-12:00 | 10.91 | 22-JUN-07:53 |
July | 907.20 | 01-JUL-00:10 | 400.68 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 78.98 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 907.20 | 01-AUG-00:10 | 400.68 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 79.27 | 16-AUG-12:00 | 0.00 | 01-AUG-00:05 |
September | 907.20 | 01-SEP-00:10 | 400.68 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 65.41 | 04-SEP-15:50 | 3.66 | 25-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 400.68 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 54.10 | 04-OCT-12:00 | 12.58 | 29-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 400.68 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 40.44 | 05-NOV-12:10 | 26.71 | 22-NOV-07:00 |
December | 907.20 | 01-DEC-00:10 | 400.68 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 26.04 | 10-DEC-11:50 | 40.89 | 18-DEC-06:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 18.59 | 0.00 | ||||||
Maximum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 79.27 | 45.94 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1573.46 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.58 | 23-JAN-14:00 | 77.30 | 20-JAN-05:30 |
February | 15368.40 | 01-FEB-00:10 | 1573.46 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.44 | 06-FEB-15:00 | 71.51 | 01-FEB-05:20 |
March | 15368.40 | 01-MAR-00:10 | 1573.46 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.34 | 27-MAR-10:55 | 64.03 | 08-MAR-06:00 |
April | 15368.40 | 01-APR-00:10 | 1573.46 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.75 | 28-APR-12:00 | 45.31 | 05-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 1573.46 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.29 | 31-MAY-19:00 | 22.04 | 01-MAY-06:00 |
June | 15368.40 | 01-JUN-00:10 | 1573.46 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.90 | 12-JUN-12:00 | 14.96 | 22-JUN-07:53 |
July | 15368.40 | 01-JUL-00:10 | 1573.46 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.85 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 15368.40 | 01-AUG-00:10 | 1573.46 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.85 | 16-AUG-12:00 | 0.00 | 01-AUG-00:05 |
September | 15368.40 | 01-SEP-00:10 | 1573.46 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.82 | 26-SEP-13:00 | 6.48 | 25-SEP-05:23 |
October | 15368.40 | 01-OCT-23:10 | 1573.46 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.33 | 04-OCT-12:00 | 21.67 | 29-OCT-07:00 |
November | 15368.40 | 01-NOV-00:10 | 1573.46 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.82 | 05-NOV-12:00 | 46.25 | 22-NOV-05:20 |
December | 15368.40 | 01-DEC-00:10 | 1573.46 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.66 | 10-DEC-11:55 | 71.13 | 30-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 28.58 | 0.00 | |||||
Maximum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 130.85 | 77.30 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 10645.38 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.11 | 23-JAN-14:00 | 229.68 | 20-JAN-06:00 |
February | 45622.98 | 01-FEB-00:10 | 10645.38 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.56 | 06-FEB-15:00 | 212.66 | 01-FEB-06:00 |
March | 45622.98 | 01-MAR-00:10 | 10645.38 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.63 | 27-MAR-10:55 | 190.54 | 08-MAR-06:00 |
April | 45622.98 | 01-APR-00:10 | 10645.38 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 326.20 | 28-APR-12:00 | 132.64 | 05-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 10645.38 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 312.24 | 31-MAY-19:00 | 67.19 | 01-MAY-06:00 |
June | 45622.98 | 01-JUN-00:10 | 10645.38 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 337.03 | 12-JUN-12:00 | 54.42 | 22-JUN-07:53 |
July | 45622.98 | 01-JUL-00:10 | 10645.38 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.87 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 45622.98 | 01-AUG-00:10 | 10645.38 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 380.60 | 16-AUG-12:00 | 0.00 | 01-AUG-00:05 |
September | 45622.98 | 01-SEP-00:10 | 10645.38 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.95 | 26-SEP-13:00 | 18.54 | 25-SEP-05:23 |
October | 45622.98 | 01-OCT-23:10 | 10645.38 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.97 | 04-OCT-12:00 | 63.86 | 29-OCT-07:00 |
November | 45622.98 | 01-NOV-00:10 | 10645.38 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.00 | 05-NOV-12:00 | 135.49 | 22-NOV-07:00 |
December | 45622.98 | 01-DEC-00:10 | 10645.38 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.99 | 10-DEC-11:55 | 210.81 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 10645.38 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 90.11 | 0.00 | |||||
Maximum of Months | 45622.98 | 10645.38 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 380.60 | 229.68 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 | 29-JAN-11:00 | 16.83 | 09-JAN-08:20 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.68 | 05-FEB-16:10 | 14.51 | 01-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.64 | 27-MAR-11:00 | 12.74 | 19-MAR-07:20 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.72 | 28-APR-12:00 | 8.15 | 01-APR-07:20 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.20 | 31-MAY-19:00 | 3.39 | 01-MAY-07:20 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.68 | 09-JUN-15:10 | 4.03 | 22-JUN-08:00 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.14 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 | 16-AUG-12:00 | 0.00 | 01-AUG-00:05 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.47 | 04-SEP-15:10 | 0.00 | 01-SEP-00:05 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.63 | 09-OCT-15:10 | 2.83 | 29-OCT-07:20 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.61 | 06-NOV-11:00 | 7.46 | 22-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.15 | 10-DEC-11:00 | 14.52 | 18-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 | 0.00 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 | 16.83 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 | 29-JAN-11:00 | 16.70 | 09-JAN-08:20 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.68 | 05-FEB-16:10 | 14.51 | 01-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.64 | 27-MAR-11:00 | 12.79 | 19-MAR-07:20 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.72 | 28-APR-12:00 | 8.95 | 05-APR-07:00 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.20 | 31-MAY-19:00 | 4.78 | 01-MAY-07:20 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.65 | 09-JUN-15:10 | 6.12 | 22-JUN-08:00 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.14 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 | 16-AUG-12:00 | 0.00 | 01-AUG-00:05 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.47 | 04-SEP-15:10 | 0.29 | 25-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.64 | 09-OCT-15:10 | 3.98 | 29-OCT-07:10 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.61 | 06-NOV-11:00 | 8.67 | 22-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.15 | 10-DEC-11:00 | 14.52 | 18-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 | 0.00 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 | 16.70 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 74.62 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 | 23-JAN-14:00 | 7.32 | 09-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 74.62 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 06-FEB-15:00 | 6.80 | 01-FEB-06:00 |
March | 0.00 | 01-MAR-00:10 | 74.62 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.09 | 27-MAR-11:00 | 6.25 | 08-MAR-06:00 |
April | 0.00 | 01-APR-00:10 | 74.62 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.81 | 28-APR-12:00 | 4.72 | 01-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 74.62 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.81 | 31-MAY-19:00 | 3.02 | 01-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 74.62 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.16 | 12-JUN-12:00 | 2.70 | 22-JUN-07:57 |
July | 0.00 | 01-JUL-00:10 | 74.62 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.36 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 01-AUG-00:10 | 74.62 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.40 | 16-AUG-12:00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 01-SEP-00:10 | 74.62 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.47 | 26-SEP-13:00 | 1.76 | 25-SEP-05:00 |
October | 0.00 | 01-OCT-00:10 | 74.62 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.10 | 04-OCT-12:00 | 2.94 | 29-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 74.62 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.35 | 05-NOV-12:00 | 4.80 | 22-NOV-07:00 |
December | 0.00 | 01-DEC-00:10 | 74.62 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 | 10-DEC-12:00 | 6.80 | 31-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 74.62 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 | 0.00 | |||||
Maximum of Months | 0.00 | 74.62 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 8.40 | 7.32 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 74.64 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.54 | 28-JAN-14:00 | 5.00 | 09-JAN-08:30 |
February | 180.00 | 01-FEB-00:10 | 74.64 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.93 | 05-FEB-16:08 | 4.06 | 12-FEB-08:20 |
March | 180.00 | 01-MAR-00:10 | 74.64 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.60 | 27-MAR-10:55 | 3.75 | 19-MAR-07:20 |
April | 180.00 | 01-APR-00:10 | 74.64 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.30 | 28-APR-12:00 | 2.48 | 05-APR-07:00 |
May | 180.00 | 01-MAY-00:10 | 74.64 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.27 | 31-MAY-19:00 | 1.12 | 01-MAY-07:10 |
June | 180.00 | 01-JUN-00:10 | 74.64 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.13 | 09-JUN-15:10 | 1.30 | 22-JUN-08:00 |
July | 180.00 | 01-JUL-00:10 | 74.64 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.81 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 74.64 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.86 | 16-AUG-12:00 | 0.00 | 01-AUG-00:05 |
September | 180.00 | 01-SEP-00:10 | 74.64 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.79 | 04-SEP-15:10 | 0.00 | 01-SEP-00:05 |
October | 180.00 | 01-OCT-00:10 | 74.64 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.16 | 09-OCT-15:10 | 1.03 | 29-OCT-07:10 |
November | 180.00 | 01-NOV-00:10 | 74.64 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.47 | 06-NOV-11:00 | 2.40 | 22-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 74.64 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 10-DEC-11:00 | 4.05 | 18-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2.54 | 0.00 | |||||
Maximum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 9.86 | 5.00 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 | 29-JAN-11:00 | 17.81 | 19-JAN-08:30 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.68 | 05-FEB-16:10 | 14.51 | 01-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.64 | 27-MAR-10:55 | 13.15 | 19-MAR-07:20 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.72 | 28-APR-12:00 | 8.33 | 01-APR-07:20 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.20 | 31-MAY-19:00 | 3.50 | 01-MAY-07:17 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.67 | 09-JUN-15:10 | 4.03 | 22-JUN-08:00 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.14 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 | 16-AUG-12:00 | 0.00 | 01-AUG-00:05 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 | 04-SEP-15:10 | 0.00 | 01-SEP-00:05 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.64 | 09-OCT-15:10 | 3.29 | 29-OCT-07:10 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.61 | 06-NOV-11:00 | 7.80 | 22-NOV-08:20 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.15 | 10-DEC-11:00 | 14.52 | 18-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 | 0.00 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 | 17.81 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 | 29-JAN-11:00 | 17.47 | 19-JAN-08:30 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.68 | 05-FEB-16:10 | 14.51 | 01-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.64 | 27-MAR-11:00 | 13.20 | 19-MAR-07:20 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.72 | 28-APR-12:00 | 8.99 | 05-APR-07:00 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.20 | 31-MAY-19:00 | 5.72 | 01-MAY-07:20 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.54 | 09-JUN-15:10 | 7.34 | 22-JUN-08:00 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.14 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 | 16-AUG-12:00 | 0.00 | 01-AUG-00:05 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.44 | 04-SEP-15:10 | 0.56 | 25-SEP-07:30 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.64 | 09-OCT-15:10 | 4.71 | 29-OCT-07:10 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.61 | 06-NOV-11:00 | 8.89 | 22-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.15 | 10-DEC-11:00 | 14.52 | 18-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 | 0.00 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 | 17.47 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.61 | 23-JAN-14:00 | 21.77 | 20-JAN-05:20 |
February | 2263.36 | 01-FEB-00:10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.14 | 06-FEB-15:00 | 20.26 | 01-FEB-05:20 |
March | 2263.36 | 01-MAR-00:10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.42 | 27-MAR-10:55 | 18.01 | 08-MAR-06:00 |
April | 2263.36 | 01-APR-00:10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 | 28-APR-12:00 | 12.70 | 05-APR-05:00 |
May | 2263.36 | 01-MAY-00:10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.61 | 31-MAY-19:00 | 6.51 | 01-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 12-JUN-12:00 | 5.87 | 22-JUN-07:53 |
July | 2263.36 | 01-JUL-00:10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.25 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 2263.36 | 01-AUG-00:10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.46 | 16-AUG-12:00 | 0.00 | 01-AUG-00:05 |
September | 2263.36 | 01-SEP-00:10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.33 | 26-SEP-13:00 | 1.79 | 25-SEP-05:00 |
October | 2263.36 | 01-OCT-23:10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 | 04-OCT-12:00 | 6.10 | 29-OCT-07:00 |
November | 2263.36 | 01-NOV-00:10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.73 | 05-NOV-12:00 | 13.01 | 22-NOV-07:00 |
December | 2263.36 | 01-DEC-00:10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.73 | 10-DEC-11:55 | 20.16 | 30-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.61 | 0.00 | ||||
Maximum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.46 | 21.77 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.10 | 29-JAN-11:00 | 16.44 | 09-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 | 05-FEB-16:10 | 14.62 | 01-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.55 | 27-MAR-10:55 | 12.71 | 08-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.63 | 28-APR-12:00 | 7.67 | 01-APR-07:20 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.12 | 31-MAY-19:00 | 3.12 | 01-MAY-07:20 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.55 | 09-JUN-15:10 | 4.13 | 22-JUN-07:57 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.06 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.24 | 16-AUG-12:00 | 0.00 | 01-AUG-00:05 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.39 | 04-SEP-15:10 | 0.00 | 01-SEP-00:05 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.53 | 09-OCT-15:10 | 2.73 | 29-OCT-07:20 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.52 | 06-NOV-11:00 | 7.57 | 22-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.06 | 10-DEC-11:00 | 14.63 | 18-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 8.10 | 0.00 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 35.24 | 16.44 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.10 | 29-JAN-11:00 | 16.44 | 09-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 | 05-FEB-16:08 | 14.61 | 01-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.55 | 27-MAR-10:55 | 12.71 | 08-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.63 | 28-APR-12:00 | 8.35 | 05-APR-07:00 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.11 | 31-MAY-19:00 | 4.43 | 01-MAY-07:20 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.46 | 09-JUN-15:10 | 6.08 | 22-JUN-08:00 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.06 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.24 | 16-AUG-12:00 | 0.00 | 01-AUG-00:05 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.38 | 04-SEP-15:10 | 0.00 | 01-SEP-00:05 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.54 | 09-OCT-15:10 | 3.51 | 29-OCT-07:10 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.52 | 06-NOV-11:00 | 8.04 | 22-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.05 | 10-DEC-11:00 | 14.63 | 18-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 8.10 | 0.00 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 35.24 | 16.44 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 74.64 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.14 | 29-JAN-11:00 | 8.99 | 19-JAN-08:20 |
February | 180.00 | 01-FEB-00:10 | 74.64 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 05-FEB-16:10 | 7.48 | 01-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 74.64 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.05 | 27-MAR-11:00 | 6.67 | 19-MAR-07:20 |
April | 180.00 | 01-APR-00:10 | 74.64 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.16 | 28-APR-12:00 | 4.11 | 01-APR-07:20 |
May | 180.00 | 01-MAY-00:10 | 74.64 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.94 | 31-MAY-19:00 | 1.56 | 01-MAY-07:20 |
June | 180.00 | 01-JUN-00:10 | 74.64 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.69 | 09-JUN-15:10 | 2.11 | 22-JUN-08:00 |
July | 180.00 | 01-JUL-00:10 | 74.64 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.94 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 74.64 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.03 | 16-AUG-12:00 | 0.00 | 01-AUG-00:05 |
September | 180.00 | 01-SEP-00:10 | 74.64 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.07 | 04-SEP-15:10 | 0.00 | 01-SEP-00:05 |
October | 180.00 | 01-OCT-00:10 | 74.64 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.07 | 09-OCT-15:10 | 1.54 | 29-OCT-07:10 |
November | 180.00 | 01-NOV-00:10 | 74.64 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 | 06-NOV-11:00 | 3.87 | 22-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 74.64 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.68 | 10-DEC-11:00 | 7.48 | 18-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4.14 | 0.00 | |||||
Maximum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 18.03 | 8.99 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.04 | 23-JAN-14:00 | 52.68 | 20-JAN-06:10 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.35 | 06-FEB-15:00 | 48.21 | 01-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 | 27-MAR-10:55 | 43.44 | 08-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.76 | 28-APR-12:00 | 30.23 | 01-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.69 | 31-MAY-19:00 | 15.50 | 01-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.76 | 12-JUN-12:00 | 12.84 | 22-JUN-07:53 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.08 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.52 | 16-AUG-12:00 | 0.00 | 01-AUG-00:05 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.82 | 26-SEP-13:00 | 4.58 | 25-SEP-05:23 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.96 | 04-OCT-12:00 | 14.75 | 29-OCT-07:00 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.87 | 05-NOV-12:00 | 30.83 | 22-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.28 | 10-DEC-11:55 | 48.26 | 18-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 18.04 | 0.00 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 83.52 | 52.68 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.85 | 23-JAN-14:00 | 52.68 | 20-JAN-06:10 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.86 | 06-FEB-15:00 | 48.21 | 01-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.14 | 27-MAR-10:55 | 43.44 | 08-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.76 | 28-APR-12:00 | 30.23 | 01-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.69 | 31-MAY-19:00 | 15.50 | 01-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.76 | 12-JUN-12:00 | 12.84 | 22-JUN-07:53 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.08 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.52 | 16-AUG-12:00 | 0.00 | 01-AUG-00:05 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.82 | 26-SEP-13:00 | 4.58 | 25-SEP-05:23 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.96 | 04-OCT-12:00 | 14.75 | 29-OCT-07:00 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.87 | 05-NOV-12:00 | 30.84 | 22-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.51 | 10-DEC-11:55 | 48.26 | 18-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 16.85 | 0.00 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 83.52 | 52.68 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1090.83 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 14.33 | 23-JAN-14:00 | 47.16 | 09-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 1090.83 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 30.34 | 06-FEB-15:00 | 43.10 | 01-FEB-06:10 |
March | 2401.70 | 01-MAR-00:10 | 1090.83 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 49.17 | 27-MAR-10:55 | 38.83 | 07-MAR-06:00 |
April | 2401.70 | 01-APR-00:10 | 1090.83 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 62.50 | 28-APR-12:00 | 27.05 | 01-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1090.83 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 62.42 | 31-MAY-19:00 | 13.86 | 01-MAY-06:00 |
June | 2401.70 | 01-JUN-00:10 | 1090.83 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 65.17 | 12-JUN-12:00 | 11.47 | 22-JUN-07:57 |
July | 2401.70 | 01-JUL-00:10 | 1090.83 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 74.42 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 2401.70 | 01-AUG-00:10 | 1090.83 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 74.81 | 16-AUG-12:00 | 0.00 | 01-AUG-00:05 |
September | 2401.70 | 01-SEP-00:10 | 1090.83 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 59.85 | 26-SEP-13:00 | 4.10 | 25-SEP-05:07 |
October | 2401.70 | 01-OCT-23:10 | 1090.83 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 49.25 | 04-OCT-12:00 | 13.18 | 29-OCT-07:00 |
November | 2401.70 | 01-NOV-00:10 | 1090.83 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 35.74 | 05-NOV-12:00 | 27.59 | 22-NOV-07:00 |
December | 2401.70 | 01-DEC-00:10 | 1090.83 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 21.56 | 10-DEC-11:55 | 43.09 | 31-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 14.33 | 0.00 | ||||||
Maximum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 74.81 | 47.16 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.28 | 23-JAN-14:00 | 35.97 | 19-JAN-07:00 |
February | 2395.44 | 01-FEB-00:10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.01 | 06-FEB-15:00 | 33.24 | 01-FEB-05:03 |
March | 2395.44 | 01-MAR-00:10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.99 | 27-MAR-10:55 | 29.02 | 08-MAR-06:00 |
April | 2395.44 | 01-APR-00:10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.12 | 28-APR-12:00 | 20.54 | 05-APR-05:00 |
May | 2395.44 | 01-MAY-00:10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.05 | 31-MAY-19:00 | 10.45 | 01-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.74 | 12-JUN-12:00 | 10.25 | 22-JUN-07:53 |
July | 2395.44 | 01-JUL-00:10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.79 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 2395.44 | 01-AUG-00:10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.17 | 16-AUG-12:00 | 0.00 | 01-AUG-00:05 |
September | 2395.44 | 01-SEP-00:10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.54 | 26-SEP-13:00 | 1.99 | 25-SEP-05:00 |
October | 2395.44 | 01-OCT-23:10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.15 | 04-OCT-12:00 | 9.24 | 29-OCT-07:00 |
November | 2395.44 | 01-NOV-00:10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.74 | 05-NOV-12:00 | 20.50 | 22-NOV-07:00 |
December | 2395.44 | 01-DEC-00:10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.69 | 10-DEC-11:55 | 32.57 | 18-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.28 | 0.00 | ||||
Maximum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.17 | 35.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19899.88 | 13-JAN-22:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18417.36 | 01-FEB-22:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15532.92 | 01-MAR-19:10 | 53675.50 | 49446.67 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15004.67 | 02-APR-10:33 | 11501.89 | 9271.10 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15724.07 | 31-MAY-18:10 | 53675.50 | 49446.67 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16211.93 | 11-JUN-10:33 | 11501.89 | 9271.10 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17326.84 | 20-JUL-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 21593.74 | 24-AUG-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 22712.77 | 28-SEP-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24056.99 | 20-OCT-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 24129.61 | 03-NOV-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22928.40 | 01-DEC-22:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 15004.67 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24129.61 | 53675.50 | 49446.67 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2209.35 | 29-JAN-11:33 | 1169.53 | 512.31 | 866.03 | 0.00 | 0.00 | 0.00 | 0.00 | 9.32 | 0.00 |
February | 2583.62 | 05-FEB-13:00 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 20.34 | 0.00 |
March | 2512.31 | 27-MAR-14:10 | 389.84 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 30.95 | 0.00 |
April | 2588.65 | 28-APR-18:07 | 5457.82 | 2732.34 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 28.45 | 0.00 |
May | 3055.78 | 31-MAY-19:10 | 909.64 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 48.80 | 0.00 |
June | 3086.40 | 09-JUN-18:03 | 5457.82 | 2732.34 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 43.20 | 0.00 |
July | 3383.67 | 21-JUL-18:03 | 5457.82 | 2732.34 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 48.32 | 0.00 |
August | 3370.92 | 16-AUG-18:13 | 2728.91 | 1366.17 | 1948.56 | 0.00 | 0.00 | 0.00 | 0.00 | 46.26 | 0.00 |
September | 3407.23 | 26-SEP-13:00 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 47.42 | 0.00 |
October | 3400.48 | 09-OCT-12:00 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 39.01 | 0.00 |
November | 3076.50 | 05-NOV-12:00 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 28.41 | 0.00 |
December | 2786.90 | 03-DEC-13:00 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 16.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2209.35 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 9.32 | 0.00 | |
Maximum of Months | 3407.23 | 5457.82 | 2732.34 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 48.80 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1475.97 | 31-JAN-22:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.79 |
February | 1790.71 | 07-FEB-22:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 | 0.00 |
March | 2009.84 | 27-MAR-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.54 | 0.00 |
April | 2126.71 | 28-APR-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 7.70 | 0.00 |
May | 2315.60 | 31-MAY-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 13.13 | 0.00 |
June | 2356.28 | 09-JUN-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 12.88 | 0.00 |
July | 2473.64 | 21-JUL-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 16.85 | 0.00 |
August | 2473.01 | 16-AUG-20:50 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 13.23 | 0.00 |
September | 2371.58 | 05-SEP-20:10 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 11.29 | 0.00 |
October | 2244.71 | 05-OCT-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 8.79 | 0.00 |
November | 2063.05 | 01-NOV-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.66 | 0.00 |
December | 1735.82 | 06-DEC-21:55 | 2407.68 | 1054.69 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1475.97 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2473.64 | 2407.68 | 1054.69 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 16.85 | 5.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1305.84 | 29-JAN-11:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 10.76 | 0.00 |
February | 1390.68 | 08-FEB-19:10 | 1336.61 | 3648.94 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 0.00 |
March | 1496.95 | 27-MAR-18:10 | 1336.61 | 3648.94 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 24.32 | 0.00 |
April | 1905.54 | 28-APR-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 23.23 | 0.00 |
May | 2324.32 | 31-MAY-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 41.61 | 0.00 |
June | 2434.03 | 09-JUN-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 32.87 | 0.00 |
July | 2639.24 | 21-JUL-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 42.12 | 0.00 |
August | 2592.44 | 16-AUG-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 35.28 | 0.00 |
September | 2415.25 | 05-SEP-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 26.90 | 0.00 |
October | 2144.84 | 05-OCT-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 23.30 | 0.00 |
November | 1713.23 | 02-NOV-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 13.19 | 0.00 |
December | 1372.23 | 03-DEC-11:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1305.84 | 222.77 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 0.00 | |
Maximum of Months | 2639.24 | 1336.61 | 3648.94 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 42.12 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 709.86 | 29-JAN-11:33 | 220.32 | 152.61 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 6.22 | 0.00 |
February | 743.04 | 08-FEB-11:33 | 146.88 | 127.18 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 6.64 | 0.00 |
March | 798.91 | 27-MAR-18:10 | 1028.16 | 813.94 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 14.31 | 0.00 |
April | 859.04 | 29-APR-10:33 | 220.32 | 127.18 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 18.09 | 0.00 |
May | 1109.50 | 31-MAY-20:10 | 195.84 | 135.66 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 0.00 |
June | 1148.39 | 09-JUN-20:50 | 195.84 | 135.66 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 17.80 | 0.00 |
July | 1279.12 | 21-JUL-21:00 | 195.84 | 135.66 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 22.97 | 0.00 |
August | 1249.16 | 16-AUG-20:00 | 171.36 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 20.36 | 0.00 |
September | 1129.83 | 05-SEP-20:00 | 171.36 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 15.52 | 0.00 |
October | 983.92 | 05-OCT-20:40 | 195.84 | 135.66 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 0.00 |
November | 813.92 | 05-NOV-10:33 | 220.32 | 152.61 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 11.93 | 0.00 |
December | 744.52 | 03-DEC-11:33 | 220.32 | 152.61 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 6.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 709.86 | 146.88 | 127.18 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 6.22 | 0.00 | |
Maximum of Months | 1279.12 | 1028.16 | 813.94 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37761.11 | 24-JAN-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 11.09 |
February | 38143.19 | 07-FEB-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 3.64 | 0.00 |
March | 38690.32 | 27-MAR-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 24.85 | 0.00 |
April | 39022.82 | 28-APR-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 31.71 | 0.00 |
May | 39290.03 | 31-MAY-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 56.81 | 0.00 |
June | 39358.28 | 01-JUN-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 34.89 | 0.00 |
July | 39659.89 | 21-JUL-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 57.52 | 0.00 |
August | 39590.73 | 16-AUG-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 48.18 | 0.00 |
September | 39297.15 | 05-SEP-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 36.73 | 0.00 |
October | 39001.83 | 05-OCT-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 31.82 | 0.00 |
November | 38577.61 | 01-NOV-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 21.49 | 0.00 |
December | 38050.45 | 01-DEC-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 7.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37761.11 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39659.89 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 57.52 | 11.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9477.64 | 29-JAN-11:33 | 15368.40 | 346.16 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 18.32 | 0.00 |
February | 10744.87 | 05-FEB-11:00 | 8538.00 | 115.39 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 32.02 | 0.00 |
March | 11490.71 | 27-MAR-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 30.58 | 0.00 |
April | 11940.10 | 28-APR-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 43.00 | 0.00 |
May | 12935.58 | 31-MAY-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 73.25 | 0.00 |
June | 13091.64 | 09-JUN-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 72.12 | 0.00 |
July | 14066.03 | 21-JUL-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 94.39 | 0.00 |
August | 13893.42 | 16-AUG-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 72.17 | 0.00 |
September | 13238.73 | 06-SEP-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 62.00 | 0.00 |
October | 12756.50 | 05-OCT-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 | 0.00 |
November | 12060.91 | 01-NOV-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 38.18 | 0.00 |
December | 10830.32 | 03-DEC-13:00 | 5122.80 | 115.39 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 36.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9477.64 | 5122.80 | 115.39 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 18.32 | 0.00 | |
Maximum of Months | 14066.03 | 15368.40 | 1048.97 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 94.39 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35335.55 | 24-JAN-22:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.43 |
February | 39010.56 | 07-FEB-22:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 6.15 | 0.00 |
March | 41010.58 | 27-MAR-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 87.32 | 0.00 |
April | 42622.25 | 28-APR-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 122.82 | 0.00 |
May | 45510.33 | 31-MAY-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 209.26 | 0.00 |
June | 46308.39 | 09-JUN-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 206.03 | 0.00 |
July | 48751.80 | 21-JUL-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 269.65 | 0.00 |
August | 48473.40 | 16-AUG-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 206.18 | 0.00 |
September | 46704.21 | 06-SEP-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 177.12 | 0.00 |
October | 45255.14 | 05-OCT-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 143.31 | 0.00 |
November | 42827.36 | 01-NOV-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 109.05 | 0.00 |
December | 38211.46 | 05-DEC-22:05 | 91245.96 | 14193.84 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 35335.55 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48751.80 | 91245.96 | 14193.84 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 269.65 | 70.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3091.53 | 22-JAN-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 0.00 |
February | 3059.66 | 03-FEB-16:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 4.60 | 0.00 |
March | 3122.38 | 25-MAR-18:02 | 702.00 | 712.44 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 0.00 |
April | 3134.00 | 18-APR-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 8.89 | 0.00 |
May | 3116.78 | 28-MAY-08:62 | 324.00 | 398.97 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 17.08 | 0.00 |
June | 3105.15 | 19-JUN-08:62 | 216.00 | 313.47 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 13.19 | 0.00 |
July | 3114.57 | 28-JUL-08:62 | 216.00 | 313.47 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 16.18 | 0.00 |
August | 3135.97 | 16-AUG-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 28.77 | 0.00 |
September | 3120.73 | 15-SEP-08:62 | 216.00 | 313.47 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 14.44 | 0.00 |
October | 3134.22 | 24-OCT-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 0.00 |
November | 3105.08 | 15-NOV-19:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 9.15 | 0.00 |
December | 3094.02 | 05-DEC-16:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 6.25 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3059.66 | 216.00 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 4.60 | 0.00 | |
Maximum of Months | 3135.97 | 831.60 | 712.44 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 28.77 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2897.03 | 29-JAN-16:02 | 324.00 | 235.08 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 | 0.00 |
February | 3094.53 | 04-FEB-16:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 9.87 | 0.00 |
March | 3086.05 | 24-MAR-15:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 7.16 | 0.00 |
April | 3273.80 | 24-APR-08:11 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 7.22 | 0.00 |
May | 3074.58 | 31-MAY-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 27.95 | 0.00 |
June | 3329.16 | 22-JUN-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 16.14 | 0.00 |
July | 3067.55 | 27-JUL-08:62 | 216.00 | 313.44 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 16.04 | 0.00 |
August | 3148.55 | 05-AUG-18:02 | 702.00 | 712.36 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 27.22 | 0.00 |
September | 3074.56 | 15-SEP-08:62 | 216.00 | 313.44 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 14.44 | 0.00 |
October | 3134.71 | 21-OCT-08:41 | 540.00 | 664.87 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 7.93 | 0.00 |
November | 3089.13 | 25-NOV-16:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 6.13 | 0.00 |
December | 3053.89 | 01-DEC-16:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 6.98 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2897.03 | 216.00 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 | 0.00 | |
Maximum of Months | 3329.16 | 831.60 | 712.36 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 27.95 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 396.12 | 28-JAN-13:50 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 | 0.00 |
February | 459.05 | 05-FEB-13:40 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 2.19 | 0.00 |
March | 412.44 | 27-MAR-13:40 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 3.92 | 0.00 |
April | 382.54 | 28-APR-17:20 | 0.00 | 150.00 | 394.73 | 0.00 | 0.00 | 0.00 | 0.00 | 3.38 | 0.00 |
May | 441.29 | 31-MAY-19:10 | 0.00 | 74.62 | 170.27 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 |
June | 449.09 | 09-JUN-17:20 | 0.00 | 150.00 | 394.73 | 0.00 | 0.00 | 0.00 | 0.00 | 6.18 | 0.00 |
July | 496.90 | 21-JUL-20:20 | 0.00 | 66.42 | 180.59 | 0.00 | 0.00 | 0.00 | 0.00 | 6.15 | 0.00 |
August | 500.78 | 16-AUG-17:13 | 0.00 | 150.00 | 394.73 | 0.00 | 0.00 | 0.00 | 0.00 | 6.32 | 0.00 |
September | 523.95 | 26-SEP-13:20 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 | 0.00 |
October | 534.45 | 09-OCT-13:30 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 4.79 | 0.00 |
November | 511.65 | 05-NOV-13:30 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 | 0.00 |
December | 468.47 | 03-DEC-13:00 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 1.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 382.54 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 | 0.00 | |
Maximum of Months | 534.45 | 0.00 | 150.00 | 394.73 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1116.41 | 28-JAN-16:02 | 324.00 | 147.80 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 | 0.00 |
February | 1168.46 | 04-FEB-16:01 | 378.00 | 172.43 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 2.64 | 0.00 |
March | 1164.07 | 26-MAR-18:02 | 702.00 | 447.86 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 | 0.00 |
April | 1178.18 | 02-APR-08:31 | 540.00 | 418.01 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 | 0.00 |
May | 1176.28 | 15-MAY-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 | 0.00 |
June | 1176.44 | 09-JUN-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 | 0.00 |
July | 1172.06 | 05-JUL-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 | 0.00 |
August | 1173.45 | 10-AUG-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 8.02 | 0.00 |
September | 1177.47 | 28-SEP-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 5.07 | 0.00 |
October | 1191.58 | 21-OCT-08:41 | 540.00 | 418.01 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2.37 | 0.00 |
November | 1160.35 | 10-NOV-19:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 2.36 | 0.00 |
December | 1152.00 | 05-DEC-19:01 | 970.20 | 465.04 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1116.41 | 324.00 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 | 0.00 | |
Maximum of Months | 1191.58 | 970.20 | 465.04 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 8.02 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2772.93 | 28-JAN-16:02 | 324.00 | 235.11 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 3.18 | 0.00 |
February | 2847.11 | 23-FEB-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 6.05 | 0.00 |
March | 2835.25 | 17-MAR-15:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 5.48 | 0.00 |
April | 2839.08 | 30-APR-18:02 | 702.00 | 712.44 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 12.11 | 0.00 |
May | 2870.26 | 23-MAY-08:62 | 216.00 | 313.47 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 13.29 | 0.00 |
June | 2855.26 | 07-JUN-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 14.91 | 0.00 |
July | 2884.14 | 30-JUL-15:02 | 324.00 | 235.11 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 27.86 | 0.00 |
August | 2901.58 | 10-AUG-15:02 | 486.00 | 166.24 | 342.42 | 0.00 | 0.00 | 0.00 | 0.00 | 30.44 | 0.00 |
September | 2863.31 | 28-SEP-08:62 | 216.00 | 313.47 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.63 | 0.00 |
October | 2871.61 | 01-OCT-08:62 | 324.00 | 398.97 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 8.81 | 0.00 |
November | 2874.67 | 06-NOV-09:01 | 360.00 | 522.46 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 7.58 | 0.00 |
December | 2824.93 | 01-DEC-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 6.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2772.93 | 216.00 | 166.24 | 342.42 | 0.00 | 0.00 | 0.00 | 0.00 | 3.18 | 0.00 | |
Maximum of Months | 2901.58 | 831.60 | 712.44 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 30.44 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2642.25 | 24-JAN-09:51 | 252.00 | 365.68 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 |
February | 2923.91 | 05-FEB-09:51 | 486.00 | 598.38 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 5.65 | 0.00 |
March | 2858.76 | 26-MAR-08:51 | 486.00 | 598.38 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 | 0.00 |
April | 3204.61 | 24-APR-08:11 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 0.00 |
May | 2987.04 | 03-MAY-08:21 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 2.74 | 0.00 |
June | 3246.79 | 22-JUN-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 14.18 | 0.00 |
July | 2842.65 | 30-JUL-15:02 | 324.00 | 235.08 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 27.84 | 0.00 |
August | 2851.45 | 16-AUG-15:02 | 486.00 | 166.22 | 342.38 | 0.00 | 0.00 | 0.00 | 0.00 | 27.54 | 0.00 |
September | 2830.95 | 22-SEP-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 15.24 | 0.00 |
October | 3101.61 | 21-OCT-08:41 | 540.00 | 664.87 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 5.97 | 0.00 |
November | 2962.87 | 18-NOV-09:51 | 486.00 | 598.38 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 0.00 |
December | 2771.79 | 10-DEC-19:01 | 819.00 | 831.08 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2642.25 | 252.00 | 166.22 | 342.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3246.79 | 831.60 | 831.08 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 27.84 | 1.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1895.89 | 29-JAN-11:33 | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.60 | 0.00 |
February | 1992.95 | 05-FEB-11:33 | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.47 | 0.00 |
March | 2172.86 | 27-MAR-18:10 | 10562.33 | 6186.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.09 | 0.00 |
April | 2318.43 | 29-APR-10:33 | 2263.36 | 966.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.29 | 0.00 |
May | 2788.13 | 31-MAY-18:17 | 5281.16 | 3093.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.11 | 0.00 |
June | 2861.96 | 09-JUN-18:13 | 5281.16 | 3093.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.78 | 0.00 |
July | 3168.14 | 21-JUL-18:13 | 5281.16 | 3093.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.54 | 0.00 |
August | 3167.09 | 16-AUG-18:13 | 5281.16 | 3093.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.39 | 0.00 |
September | 2847.54 | 05-SEP-18:15 | 3520.78 | 2062.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.73 | 0.00 |
October | 2524.82 | 05-OCT-21:10 | 2263.36 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 | 0.00 |
November | 2229.71 | 05-NOV-10:33 | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.78 | 0.00 |
December | 2026.31 | 03-DEC-11:33 | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1895.89 | 2263.36 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.60 | 0.00 | |
Maximum of Months | 3168.14 | 10562.33 | 6186.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.54 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3282.00 | 22-JAN-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 5.08 | 0.00 |
February | 3263.56 | 07-FEB-19:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 7.08 | 0.00 |
March | 3318.86 | 25-MAR-18:02 | 702.00 | 712.44 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 | 0.00 |
April | 3352.65 | 03-APR-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 7.13 | 0.00 |
May | 3340.29 | 22-MAY-08:62 | 216.00 | 313.47 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 22.31 | 0.00 |
June | 3315.29 | 02-JUN-08:62 | 216.00 | 313.47 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 18.16 | 0.00 |
July | 3433.76 | 21-JUL-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 29.91 | 0.00 |
August | 3411.11 | 05-AUG-18:02 | 702.00 | 712.44 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 0.00 |
September | 3344.02 | 04-SEP-08:62 | 324.00 | 398.97 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 18.28 | 0.00 |
October | 3354.41 | 24-OCT-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 13.24 | 0.00 |
November | 3319.42 | 08-NOV-19:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 10.36 | 0.00 |
December | 3329.21 | 11-DEC-16:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3263.56 | 216.00 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 5.08 | 0.00 | |
Maximum of Months | 3433.76 | 831.60 | 712.44 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 29.91 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3147.61 | 29-JAN-16:02 | 324.00 | 235.08 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 5.52 | 0.00 |
February | 3290.53 | 23-FEB-16:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 6.08 | 0.00 |
March | 3298.02 | 31-MAR-15:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 7.23 | 0.00 |
April | 3397.70 | 24-APR-08:11 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 7.47 | 0.00 |
May | 3306.93 | 31-MAY-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 27.89 | 0.00 |
June | 3510.05 | 22-JUN-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 16.06 | 0.00 |
July | 3370.25 | 21-JUL-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 29.86 | 0.00 |
August | 3356.02 | 16-AUG-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 28.69 | 0.00 |
September | 3294.46 | 04-SEP-08:62 | 324.00 | 398.92 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 18.26 | 0.00 |
October | 3284.18 | 20-OCT-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 13.82 | 0.00 |
November | 3268.99 | 25-NOV-16:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 6.07 | 0.00 |
December | 3302.99 | 01-DEC-16:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 6.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3147.61 | 324.00 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 5.52 | 0.00 | |
Maximum of Months | 3510.05 | 831.60 | 634.00 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 29.86 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1780.11 | 23-JAN-16:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 | 0.00 |
February | 1805.60 | 05-FEB-19:02 | 702.00 | 447.86 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 4.44 | 0.00 |
March | 1811.75 | 22-MAR-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 4.99 | 0.00 |
April | 1846.82 | 30-APR-18:02 | 702.00 | 447.86 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 6.18 | 0.00 |
May | 1840.38 | 16-MAY-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 8.70 | 0.00 |
June | 1833.20 | 14-JUN-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 0.00 |
July | 1850.94 | 30-JUL-15:02 | 324.00 | 147.80 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 14.24 | 0.00 |
August | 1863.73 | 10-AUG-15:02 | 486.00 | 104.50 | 335.48 | 0.00 | 0.00 | 0.00 | 0.00 | 15.54 | 0.00 |
September | 1888.60 | 18-SEP-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 10.09 | 0.00 |
October | 1885.59 | 06-OCT-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 10.10 | 0.00 |
November | 1852.67 | 05-NOV-15:02 | 324.00 | 147.80 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 7.65 | 0.00 |
December | 1809.78 | 11-DEC-19:01 | 970.20 | 465.04 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1780.11 | 324.00 | 104.50 | 335.48 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 | 0.00 | |
Maximum of Months | 1888.60 | 970.20 | 465.04 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 15.54 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20272.59 | 23-JAN-22:53 | 161932.61 | 11052.49 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.03 |
February | 21516.19 | 07-FEB-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
March | 22602.07 | 27-MAR-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 | 0.00 |
April | 23601.08 | 28-APR-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 27.16 | 0.00 |
May | 24777.52 | 31-MAY-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 46.57 | 0.00 |
June | 24930.82 | 09-JUN-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 44.78 | 0.00 |
July | 25618.70 | 21-JUL-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 58.78 | 0.00 |
August | 25364.14 | 16-AUG-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 44.78 | 0.00 |
September | 24443.16 | 06-SEP-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 38.70 | 0.00 |
October | 23691.38 | 05-OCT-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 31.76 | 0.00 |
November | 22803.00 | 01-NOV-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 24.10 | 0.00 |
December | 21170.92 | 11-DEC-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20272.59 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25618.70 | 161932.61 | 11052.49 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 58.78 | 13.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21910.50 | 23-JAN-22:53 | 161932.61 | 11052.49 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.03 |
February | 22951.41 | 07-FEB-22:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 | 0.00 |
March | 23941.39 | 27-MAR-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 | 0.00 |
April | 24808.89 | 28-APR-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 27.16 | 0.00 |
May | 25949.32 | 31-MAY-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 45.30 | 0.00 |
June | 26123.49 | 09-JUN-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 44.77 | 0.00 |
July | 26804.53 | 21-JUL-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 58.77 | 0.00 |
August | 26545.42 | 16-AUG-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 44.77 | 0.00 |
September | 25613.24 | 06-SEP-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 39.36 | 0.00 |
October | 24869.20 | 05-OCT-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 31.76 | 0.00 |
November | 24015.47 | 01-NOV-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 24.10 | 0.00 |
December | 22679.28 | 11-DEC-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 21910.50 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26804.53 | 161932.61 | 11052.49 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 58.77 | 13.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27391.49 | 29-JAN-11:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 10.10 | 0.00 |
February | 27956.50 | 05-FEB-11:45 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 23.99 | 0.00 |
March | 28647.69 | 26-MAR-10:45 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 29.70 | 0.00 |
April | 29528.17 | 29-APR-10:50 | 800.57 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 42.18 | 0.00 |
May | 29888.35 | 29-MAY-10:33 | 2401.70 | 1090.83 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 46.49 | 0.00 |
June | 30085.98 | 10-JUN-10:33 | 2401.70 | 909.03 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 49.83 | 0.00 |
July | 30663.06 | 30-JUL-10:37 | 2401.70 | 1090.83 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 68.56 | 0.00 |
August | 30590.01 | 05-AUG-10:33 | 2401.70 | 909.03 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 63.42 | 0.00 |
September | 30010.90 | 04-SEP-10:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 49.05 | 0.00 |
October | 29503.76 | 09-OCT-10:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 40.87 | 0.00 |
November | 28585.88 | 05-NOV-10:45 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 28.10 | 0.00 |
December | 27695.48 | 03-DEC-11:45 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 13.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 27391.49 | 800.57 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 10.10 | 0.00 | |
Maximum of Months | 30663.06 | 2401.70 | 1090.83 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 68.56 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4523.16 | 29-JAN-11:33 | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 | 0.00 |
February | 4798.22 | 08-FEB-11:33 | 1596.96 | 1023.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.38 | 0.00 |
March | 5307.30 | 27-MAR-18:10 | 11178.72 | 6547.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.53 | 0.00 |
April | 6136.18 | 28-APR-12:20 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.42 | 0.00 |
May | 7091.76 | 31-MAY-18:40 | 1863.12 | 1091.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.84 | 0.00 |
June | 7382.16 | 01-JUN-15:02 | 6654.00 | 1705.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.78 | 0.00 |
July | 8199.62 | 21-JUL-12:20 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.99 | 0.00 |
August | 8124.40 | 16-AUG-14:10 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.78 | 0.00 |
September | 7572.32 | 05-SEP-13:00 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.31 | 0.00 |
October | 6734.27 | 04-OCT-12:40 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.03 | 0.00 |
November | 5292.49 | 01-NOV-18:05 | 11178.72 | 6547.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.57 | 0.00 |
December | 4769.06 | 03-DEC-11:33 | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4523.16 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 | 0.00 | |
Maximum of Months | 8199.62 | 11178.72 | 6547.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.99 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.523062E+12 | 356341.17 | 29-JAN-20:00 | 0.220318E+12 | 153255.15 | 12-JAN-18:40 |
February | 0.504252E+12 | 387065.15 | 07-FEB-20:10 | 0.194702E+12 | 149221.86 | 01-FEB-18:40 |
March | 0.599081E+12 | 403886.92 | 28-MAR-19:10 | 0.209399E+12 | 142613.55 | 01-MAR-18:40 |
April | 0.649421E+12 | 428339.39 | 27-APR-19:10 | 0.192489E+12 | 130317.68 | 01-APR-17:40 |
May | 0.770422E+12 | 484793.95 | 30-MAY-19:40 | 0.194646E+12 | 120157.22 | 01-MAY-17:10 |
June | 0.817526E+12 | 510479.20 | 09-JUN-19:19 | 0.188406E+12 | 120157.22 | 01-JUN-17:10 |
July | 0.915724E+12 | 529360.52 | 18-JUL-20:00 | 0.194478E+12 | 120157.22 | 01-JUL-17:10 |
August | 0.938828E+12 | 555288.18 | 16-AUG-19:40 | 0.194704E+12 | 120157.22 | 01-AUG-17:10 |
September | 0.839042E+12 | 518799.52 | 08-SEP-19:10 | 0.188265E+12 | 120157.22 | 01-SEP-17:10 |
October | 0.774207E+12 | 495438.50 | 06-OCT-19:10 | 0.195663E+12 | 125171.51 | 31-OCT-17:40 |
November | 0.653445E+12 | 447525.32 | 01-NOV-19:10 | 0.199240E+12 | 138194.37 | 30-NOV-18:10 |
December | 0.576917E+12 | 399500.79 | 05-DEC-20:10 | 0.215450E+12 | 149088.92 | 30-DEC-18:00 |
Annual Sum or Average | 0.856193E+13 | 0.238776E+13 | ||||
Minimum of Months | 0.504252E+12 | 356341.17 | 0.188265E+12 | 120157.22 | ||
Maximum of Months | 0.938828E+12 | 555288.18 | 0.220318E+12 | 153255.15 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.516905E+11 | 0.165448E+11 | 0.146779E+12 | 0.544821E+11 | 0.445055E+11 | 0.146801E+11 | 0.00 | 0.127299E+12 | 0.00 | 0.00 | 0.234091E+11 | 0.399131E+11 | 0.00 |
February | 0.465797E+11 | 0.143544E+11 | 0.132565E+12 | 0.492097E+11 | 0.411835E+11 | 0.134146E+11 | 0.00 | 0.146553E+12 | 0.00 | 0.00 | 0.212805E+11 | 0.357087E+11 | 0.00 |
March | 0.513962E+11 | 0.150335E+11 | 0.146789E+12 | 0.544840E+11 | 0.478710E+11 | 0.150847E+11 | 0.00 | 0.201099E+12 | 0.00 | 0.00 | 0.242140E+11 | 0.393412E+11 | 0.00 |
April | 0.494906E+11 | 0.136353E+11 | 0.142011E+12 | 0.527242E+11 | 0.493503E+11 | 0.149993E+11 | 0.00 | 0.261597E+12 | 0.00 | 0.00 | 0.244767E+11 | 0.374894E+11 | 0.00 |
May | 0.509869E+11 | 0.133557E+11 | 0.146789E+12 | 0.544827E+11 | 0.573156E+11 | 0.162277E+11 | 0.00 | 0.364224E+12 | 0.00 | 0.00 | 0.257434E+11 | 0.375168E+11 | 0.00 |
June | 0.492012E+11 | 0.125834E+11 | 0.142058E+12 | 0.527259E+11 | 0.582495E+11 | 0.164319E+11 | 0.00 | 0.422874E+12 | 0.00 | 0.00 | 0.249395E+11 | 0.348000E+11 | 0.00 |
July | 0.509489E+11 | 0.131293E+11 | 0.146742E+12 | 0.544808E+11 | 0.636028E+11 | 0.176406E+11 | 0.00 | 0.504561E+12 | 0.00 | 0.00 | 0.257713E+11 | 0.350807E+11 | 0.00 |
August | 0.510812E+11 | 0.137618E+11 | 0.146800E+12 | 0.544838E+11 | 0.660925E+11 | 0.179267E+11 | 0.00 | 0.523935E+12 | 0.00 | 0.00 | 0.257713E+11 | 0.351931E+11 | 0.00 |
September | 0.496070E+11 | 0.141480E+11 | 0.142022E+12 | 0.527244E+11 | 0.600478E+11 | 0.168311E+11 | 0.00 | 0.439785E+12 | 0.00 | 0.00 | 0.249400E+11 | 0.352740E+11 | 0.00 |
October | 0.515117E+11 | 0.155262E+11 | 0.146768E+12 | 0.544820E+11 | 0.586276E+11 | 0.164216E+11 | 0.00 | 0.363423E+12 | 0.00 | 0.00 | 0.257521E+11 | 0.379143E+11 | 0.00 |
November | 0.499253E+11 | 0.158058E+11 | 0.142074E+12 | 0.527251E+11 | 0.514985E+11 | 0.150467E+11 | 0.00 | 0.261077E+12 | 0.00 | 0.00 | 0.243106E+11 | 0.373292E+11 | 0.00 |
December | 0.516563E+11 | 0.167778E+11 | 0.146742E+12 | 0.544813E+11 | 0.469943E+11 | 0.149409E+11 | 0.00 | 0.178502E+12 | 0.00 | 0.00 | 0.236454E+11 | 0.394064E+11 | 0.00 |
Annual Sum or Average | 0.604076E+12 | 0.174656E+12 | 0.172814E+13 | 0.641486E+12 | 0.645339E+12 | 0.189646E+12 | 0.00 | 0.379493E+13 | 0.00 | 0.00 | 0.294254E+12 | 0.444967E+12 | 0.00 |
Minimum of Months | 0.465797E+11 | 0.125834E+11 | 0.132565E+12 | 0.492097E+11 | 0.411835E+11 | 0.134146E+11 | 0.00 | 0.127299E+12 | 0.00 | 0.00 | 0.212805E+11 | 0.348000E+11 | 0.00 |
Maximum of Months | 0.516905E+11 | 0.167778E+11 | 0.146800E+12 | 0.544840E+11 | 0.660925E+11 | 0.179267E+11 | 0.00 | 0.523935E+12 | 0.00 | 0.00 | 0.257713E+11 | 0.399131E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.542035E+09 | 0.00 | 0.678572E+11 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.225456E+09 | 0.00 | 0.572728E+11 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.203953E+09 | 0.00 | 0.571716E+11 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.102992E+09 | 0.00 | 0.454299E+11 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 56903136.87 | 0.00 | 0.426104E+11 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 56456642.34 | 0.00 | 0.412359E+11 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 47509025.74 | 0.00 | 0.426104E+11 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 55212341.20 | 0.00 | 0.426104E+11 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 58305862.56 | 0.00 | 0.412359E+11 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 92939369.14 | 0.00 | 0.436668E+11 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.164599E+09 | 0.00 | 0.519845E+11 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.291855E+09 | 0.00 | 0.633373E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.189822E+10 | 0.00 | 0.597023E+12 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 47509025.74 | 0.00 | 0.412359E+11 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.542035E+09 | 0.00 | 0.678572E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 50471.22 | 02-JAN-20:10 | 11096.45 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 39155.93 | 09-JAN-07:19 | 30186.28 | 23-JAN-22:00 | 5974.28 | 29-JAN-22:00 | 0.00 | 01-JAN-00:10 |
February | 50471.22 | 01-FEB-20:10 | 11096.45 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 39155.88 | 09-FEB-07:19 | 32981.25 | 07-FEB-22:10 | 6356.21 | 06-FEB-19:10 | 0.00 | 01-FEB-00:10 |
March | 50471.22 | 01-MAR-20:10 | 11096.45 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 39155.93 | 13-MAR-06:19 | 35848.97 | 27-MAR-21:10 | 6463.27 | 28-MAR-19:19 | 0.00 | 01-MAR-00:10 |
April | 50471.22 | 03-APR-19:10 | 11096.45 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 39155.93 | 03-APR-06:19 | 37466.03 | 28-APR-21:10 | 6940.44 | 30-APR-18:10 | 0.00 | 01-APR-00:10 |
May | 50471.22 | 01-MAY-19:10 | 11096.45 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 39154.78 | 01-MAY-06:19 | 41012.19 | 31-MAY-21:10 | 7782.81 | 30-MAY-18:10 | 0.00 | 01-MAY-00:10 |
June | 50471.22 | 01-JUN-19:10 | 11096.45 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 39155.41 | 08-JUN-06:19 | 41712.49 | 09-JUN-21:10 | 8496.82 | 26-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 50471.22 | 03-JUL-19:10 | 11096.45 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 39155.62 | 20-JUL-06:19 | 44272.98 | 21-JUL-21:10 | 9147.60 | 19-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 50471.22 | 01-AUG-19:10 | 11096.45 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 39155.86 | 30-AUG-06:19 | 46707.89 | 16-AUG-21:10 | 9101.84 | 30-AUG-18:10 | 0.00 | 01-AUG-00:10 |
September | 50471.22 | 01-SEP-19:10 | 11096.45 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 39155.93 | 21-SEP-06:19 | 45549.79 | 06-SEP-21:10 | 8683.38 | 08-SEP-18:10 | 0.00 | 01-SEP-00:10 |
October | 50471.22 | 02-OCT-19:10 | 11096.45 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 39155.93 | 02-OCT-06:19 | 44822.45 | 05-OCT-21:10 | 8022.96 | 07-OCT-18:10 | 0.00 | 01-OCT-00:10 |
November | 50471.22 | 01-NOV-19:10 | 11096.45 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 39155.93 | 01-NOV-06:19 | 41351.00 | 01-NOV-21:10 | 7105.22 | 01-NOV-18:19 | 0.00 | 01-NOV-00:10 |
December | 50471.22 | 01-DEC-20:10 | 11096.45 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 39155.88 | 21-DEC-07:19 | 33561.55 | 01-DEC-22:00 | 6602.17 | 04-DEC-21:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 50471.22 | 11096.45 | 88863.15 | 39154.78 | 30186.28 | 5974.28 | 0.00 | |||||||
Maximum of Months | 50471.22 | 11096.45 | 88863.15 | 39155.93 | 46707.89 | 9147.60 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 110318.68 | 29-JAN-16:10 | 0.00 | 0.00 | 9938.94 | 01-JAN-02:39 | 43956.31 | 31-JAN-21:49 | 0.00 |
February | 138188.77 | 07-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-03:49 | 43667.30 | 28-FEB-21:49 | 0.00 |
March | 147949.65 | 27-MAR-15:20 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:20 | 43578.49 | 30-MAR-20:30 | 0.00 |
April | 178118.33 | 30-APR-15:20 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 43000.30 | 25-APR-20:30 | 0.00 |
May | 240766.61 | 30-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAY-00:10 | 42153.23 | 02-MAY-20:30 | 0.00 |
June | 251029.78 | 09-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-00:10 | 39987.91 | 05-JUN-20:00 | 0.00 |
July | 281042.99 | 19-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUL-00:10 | 38832.18 | 31-JUL-20:00 | 0.00 |
August | 308464.81 | 10-AUG-18:10 | 0.00 | 0.00 | 9938.94 | 01-AUG-00:10 | 39092.00 | 28-AUG-20:00 | 0.00 |
September | 261716.67 | 08-SEP-18:10 | 0.00 | 0.00 | 9938.94 | 01-SEP-00:10 | 41186.04 | 28-SEP-17:40 | 0.00 |
October | 231780.80 | 06-OCT-18:10 | 0.00 | 0.00 | 9938.94 | 01-OCT-00:10 | 42114.81 | 03-OCT-20:30 | 0.00 |
November | 189048.60 | 01-NOV-15:20 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 42715.18 | 06-NOV-21:30 | 0.00 |
December | 133953.80 | 04-DEC-21:10 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:10 | 43500.22 | 01-DEC-21:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 110318.68 | 0.00 | 0.00 | 9938.94 | 38832.18 | 0.00 | |||
Maximum of Months | 308464.81 | 0.00 | 0.00 | 9938.94 | 43956.31 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 356341.17 | 29-JAN-20:00 | 46435.92 | 86521.75 | 11096.45 | 31540.10 | 23619.21 | 5815.44 | 0.00 | 101652.48 | 0.00 |
February | 387065.15 | 07-FEB-20:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 28376.27 | 6098.70 | 0.00 | 120369.13 | 0.00 |
March | 403886.92 | 28-MAR-19:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 28803.38 | 6430.01 | 0.00 | 136292.66 | 0.00 |
April | 428339.39 | 27-APR-19:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 29395.04 | 6492.82 | 0.00 | 159967.78 | 0.00 |
May | 484793.95 | 30-MAY-19:40 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 33934.12 | 7125.10 | 0.00 | 213326.51 | 0.00 |
June | 510479.20 | 09-JUN-19:19 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 37250.82 | 7248.53 | 0.00 | 236664.87 | 0.00 |
July | 529360.52 | 18-JUL-20:00 | 44879.15 | 88373.09 | 11096.45 | 24006.45 | 39576.37 | 8605.06 | 0.00 | 263244.79 | 0.00 |
August | 555288.18 | 16-AUG-19:40 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 38282.66 | 8353.03 | 0.00 | 279993.47 | 0.00 |
September | 518799.52 | 08-SEP-19:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 36396.47 | 8320.93 | 0.00 | 244621.25 | 0.00 |
October | 495438.50 | 06-OCT-19:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 35875.76 | 7832.40 | 0.00 | 220647.25 | 0.00 |
November | 447525.32 | 01-NOV-19:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 31784.59 | 6951.23 | 0.00 | 176507.98 | 0.00 |
December | 399500.79 | 05-DEC-20:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 28702.87 | 6514.64 | 0.00 | 132098.36 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 356341.17 | 44879.15 | 86521.75 | 11096.45 | 24006.45 | 23619.21 | 5815.44 | 0.00 | 101652.48 | 0.00 | |
Maximum of Months | 555288.18 | 50471.22 | 88373.09 | 11096.45 | 31577.78 | 39576.37 | 8605.06 | 0.00 | 279993.47 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 24078.49 | 21-JAN-07:10 | 0.00 | 49007.37 | 12-JAN-22:49 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 5629.57 | 24-FEB-22:00 | 0.00 | 44973.54 | 01-FEB-18:40 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 5464.69 | 05-MAR-16:10 | 0.00 | 38365.49 | 01-MAR-19:40 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 5441.92 | 05-APR-18:10 | 0.00 | 26155.49 | 01-APR-22:19 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 5526.33 | 16-MAY-08:09 | 0.00 | 15908.90 | 01-MAY-00:10 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 4603.87 | 08-JUN-08:09 | 0.00 | 15908.90 | 01-JUN-00:10 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 3404.37 | 21-JUL-08:09 | 0.00 | 15908.90 | 01-JUL-00:10 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 3563.60 | 18-AUG-08:09 | 0.00 | 15908.90 | 01-AUG-00:10 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 4302.40 | 26-SEP-08:09 | 0.00 | 15908.90 | 01-SEP-00:10 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 4257.81 | 11-OCT-08:09 | 0.00 | 20923.21 | 31-OCT-18:00 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 5380.80 | 23-NOV-19:10 | 0.00 | 33946.26 | 30-NOV-22:19 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 20671.21 | 30-DEC-07:10 | 0.00 | 44871.38 | 31-DEC-22:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 3404.37 | 0.00 | 15908.90 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 24078.49 | 0.00 | 49007.37 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.74 | 1.83 | 21.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.75 | 3.00 | 21.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.76 | 4.50 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 21.76 | 5.00 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.74 | 4.00 | 21.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.72 | 1.50 | 21.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 19.83 | 21.75 | 19.83 | 21.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 21.76 | 5.00 | 21.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.75 | 2.50 | 21.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.77 | 3.83 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.77 | 5.17 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 21.77 | 5.00 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.75 | 2.17 | 21.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.77 | 0.33 | 21.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.69 | 0.67 | 21.69 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 19.83 | 21.76 | 19.83 | 21.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.77 | 5.17 | 21.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.69 | 0.50 | 21.69 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.74 | 0.67 | 21.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.71 | 0.67 | 21.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.72 | 2.67 | 21.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.71 | 5.17 | 21.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 21.72 | 7.67 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 21.73 | 6.50 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.70 | 1.33 | 21.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.96 | 0.33 | 21.96 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.76 | 1.17 | 21.76 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
Annual Sum or Average | 0.00 | 0.00 | 27.00 | 21.72 | 27.00 | 21.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 21.96 | 7.67 | 21.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.72 | 1.83 | 21.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.74 | 2.50 | 21.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.74 | 4.50 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.75 | 4.83 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.73 | 3.33 | 21.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.70 | 1.00 | 21.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 18.00 | 21.74 | 18.00 | 21.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.75 | 4.83 | 21.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.75 | 0.17 | 21.75 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.74 | 0.67 | 21.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.89 | 2.83 | 21.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.83 | 2.67 | 21.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.80 | 3.33 | 21.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.76 | 5.17 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 21.74 | 5.33 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.74 | 1.50 | 21.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 22.01 | 1.17 | 22.01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 22.00 | 3.00 | 22.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 25.83 | 21.82 | 25.83 | 21.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 22.01 | 5.33 | 22.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.75 | 2.83 | 21.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.76 | 3.67 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.74 | 4.83 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.73 | 4.83 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.72 | 4.17 | 21.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.72 | 2.33 | 21.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 22.83 | 21.74 | 22.83 | 21.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.76 | 4.83 | 21.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.74 | 3.83 | 21.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.77 | 4.33 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.76 | 5.17 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.74 | 5.17 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.73 | 3.00 | 21.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 22.00 | 21.75 | 22.00 | 21.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.77 | 5.17 | 21.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.69 | 0.83 | 21.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.70 | 1.00 | 21.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.73 | 3.00 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 21.75 | 4.67 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.74 | 2.50 | 21.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.73 | 3.67 | 21.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.73 | 0.83 | 21.73 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.67 | 21.74 | 16.67 | 21.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 21.75 | 4.67 | 21.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 77.00 | 23.65 | 304.67 | 23.90 | 0.00 | 23.90 |
February | 214.33 | 23.30 | 173.83 | 23.55 | 0.00 | 23.55 |
March | 700.33 | 22.97 | 5.50 | 22.97 | 0.00 | 22.97 |
April | 720.00 | 22.69 | 0.00 | 22.69 | 0.00 | 22.69 |
May | 743.17 | 22.86 | 0.00 | 22.86 | 0.00 | 22.86 |
June | 457.50 | 23.00 | 0.17 | 23.00 | 0.00 | 23.00 |
July | 184.00 | 23.22 | 358.17 | 23.62 | 0.00 | 23.62 |
August | 1.83 | 23.29 | 559.00 | 23.96 | 0.00 | 23.96 |
September | 0.00 | 0.00 | 670.50 | 23.94 | 0.00 | 23.94 |
October | 0.00 | 0.00 | 697.17 | 23.98 | 0.00 | 23.98 |
November | 0.00 | 0.00 | 700.83 | 23.99 | 0.00 | 23.99 |
December | 0.00 | 0.00 | 589.83 | 23.96 | 0.00 | 23.96 |
Annual Sum or Average | 3098.17 | 22.94 | 4059.67 | 23.51 | 0.00 | 23.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.69 | 0.00 | 22.69 |
Maximum of Months | 743.17 | 23.65 | 700.83 | 23.99 | 0.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 635.83 | 21.89 | 54.83 | 22.01 | 0.00 | 22.01 |
February | 501.50 | 21.99 | 88.67 | 22.23 | 0.00 | 22.23 |
March | 484.00 | 22.15 | 140.17 | 22.47 | 0.00 | 22.47 |
April | 303.50 | 22.37 | 261.50 | 22.93 | 0.00 | 22.93 |
May | 32.67 | 22.66 | 628.67 | 23.70 | 0.00 | 23.70 |
June | 0.00 | 0.00 | 714.50 | 23.81 | 0.00 | 23.81 |
July | 0.00 | 0.00 | 744.00 | 23.94 | 0.00 | 23.94 |
August | 0.00 | 0.00 | 744.00 | 23.97 | 0.00 | 23.97 |
September | 0.00 | 0.00 | 704.33 | 23.88 | 0.00 | 23.88 |
October | 22.67 | 22.73 | 644.67 | 23.77 | 0.00 | 23.77 |
November | 190.50 | 22.46 | 398.17 | 23.34 | 0.00 | 23.34 |
December | 523.50 | 22.05 | 126.67 | 22.36 | 0.00 | 22.36 |
Annual Sum or Average | 2694.17 | 22.10 | 5250.17 | 23.24 | 0.00 | 23.24 |
Minimum of Months | 0.00 | 0.00 | 54.83 | 22.01 | 0.00 | 22.01 |
Maximum of Months | 635.83 | 22.73 | 744.00 | 23.97 | 0.00 | 23.97 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 537.67 | 22.86 | 89.33 | 23.00 | 0.00 | 23.00 |
February | 377.50 | 22.91 | 154.50 | 23.18 | 0.00 | 23.18 |
March | 322.67 | 22.96 | 238.00 | 23.35 | 0.00 | 23.35 |
April | 159.50 | 23.03 | 376.83 | 23.62 | 0.00 | 23.62 |
May | 14.83 | 23.20 | 603.00 | 23.89 | 0.00 | 23.89 |
June | 1.67 | 24.00 | 664.17 | 23.90 | 1.67 | 23.90 |
July | 0.00 | 0.00 | 739.67 | 23.92 | 0.00 | 23.92 |
August | 0.00 | 0.00 | 743.83 | 23.94 | 0.00 | 23.94 |
September | 0.00 | 0.00 | 708.50 | 23.91 | 0.00 | 23.91 |
October | 5.83 | 23.52 | 650.17 | 23.90 | 0.00 | 23.90 |
November | 26.83 | 23.14 | 506.50 | 23.81 | 0.00 | 23.81 |
December | 342.00 | 22.93 | 198.33 | 23.25 | 0.00 | 23.25 |
Annual Sum or Average | 1788.50 | 22.93 | 5672.83 | 23.66 | 1.67 | 23.66 |
Minimum of Months | 0.00 | 0.00 | 89.33 | 23.00 | 0.00 | 23.00 |
Maximum of Months | 537.67 | 24.00 | 743.83 | 23.94 | 1.67 | 23.94 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.47 | 0.00 | 22.47 | 0.00 | 22.47 |
February | 653.83 | 22.69 | 0.00 | 22.69 | 0.00 | 22.69 |
March | 665.00 | 22.89 | 5.50 | 22.89 | 0.00 | 22.89 |
April | 436.33 | 23.15 | 63.17 | 23.25 | 0.00 | 23.25 |
May | 17.33 | 23.42 | 533.50 | 23.94 | 0.00 | 23.94 |
June | 0.00 | 0.00 | 689.17 | 23.98 | 0.00 | 23.98 |
July | 0.00 | 0.00 | 741.50 | 23.99 | 0.00 | 23.99 |
August | 0.00 | 0.00 | 744.00 | 24.00 | 0.00 | 24.00 |
September | 0.00 | 0.00 | 694.00 | 23.97 | 0.00 | 23.97 |
October | 19.17 | 23.57 | 510.17 | 23.92 | 0.00 | 23.92 |
November | 279.67 | 23.17 | 87.17 | 23.35 | 0.00 | 23.35 |
December | 719.83 | 22.79 | 0.00 | 22.79 | 0.00 | 22.79 |
Annual Sum or Average | 3535.17 | 22.81 | 4068.17 | 23.43 | 0.00 | 23.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.47 | 0.00 | 22.47 |
Maximum of Months | 744.00 | 23.57 | 744.00 | 24.00 | 0.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.35 | 0.00 | 22.35 | 0.00 | 22.35 |
February | 671.17 | 22.59 | 0.00 | 22.59 | 0.00 | 22.59 |
March | 726.67 | 22.82 | 0.00 | 22.82 | 0.00 | 22.82 |
April | 572.83 | 23.13 | 25.17 | 23.16 | 0.00 | 23.16 |
May | 23.17 | 23.38 | 475.33 | 23.92 | 0.00 | 23.92 |
June | 0.00 | 0.00 | 690.67 | 23.98 | 0.00 | 23.98 |
July | 0.00 | 0.00 | 740.17 | 24.00 | 0.00 | 24.00 |
August | 0.00 | 0.00 | 744.00 | 24.00 | 0.00 | 24.00 |
September | 0.00 | 0.00 | 700.50 | 23.97 | 0.00 | 23.97 |
October | 23.17 | 23.57 | 405.17 | 23.89 | 0.00 | 23.89 |
November | 426.50 | 23.17 | 12.17 | 23.19 | 0.00 | 23.19 |
December | 744.00 | 22.69 | 0.00 | 22.69 | 0.00 | 22.69 |
Annual Sum or Average | 3931.50 | 22.76 | 3793.17 | 23.35 | 0.00 | 23.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.35 | 0.00 | 22.35 |
Maximum of Months | 744.00 | 23.57 | 744.00 | 24.00 | 0.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 301.33 | 23.78 | 678.17 | 23.40 | 279.50 | 23.53 |
February | 275.00 | 23.88 | 633.33 | 23.40 | 265.50 | 23.53 |
March | 304.00 | 23.92 | 704.67 | 23.40 | 297.50 | 23.53 |
April | 303.83 | 23.97 | 712.00 | 23.37 | 303.83 | 23.51 |
May | 338.33 | 23.94 | 744.00 | 23.38 | 338.33 | 23.51 |
June | 342.00 | 23.92 | 720.00 | 23.38 | 342.00 | 23.52 |
July | 364.33 | 23.91 | 744.00 | 23.40 | 364.33 | 23.52 |
August | 361.50 | 23.92 | 744.00 | 23.40 | 361.50 | 23.52 |
September | 338.83 | 23.93 | 720.00 | 23.39 | 338.83 | 23.52 |
October | 335.00 | 23.95 | 742.50 | 23.39 | 335.00 | 23.52 |
November | 313.17 | 23.97 | 715.00 | 23.39 | 313.17 | 23.53 |
December | 303.17 | 23.93 | 702.00 | 23.42 | 297.83 | 23.55 |
Annual Sum or Average | 3880.50 | 23.92 | 8559.67 | 23.39 | 3837.33 | 23.52 |
Minimum of Months | 275.00 | 23.78 | 633.33 | 23.37 | 265.50 | 23.51 |
Maximum of Months | 364.33 | 23.97 | 744.00 | 23.42 | 364.33 | 23.55 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 308.00 | 23.07 | 379.50 | 23.39 | 108.17 | 23.45 |
February | 282.50 | 23.31 | 453.83 | 23.52 | 173.17 | 23.58 |
March | 255.33 | 23.30 | 517.50 | 23.56 | 149.00 | 23.62 |
April | 280.00 | 23.72 | 600.67 | 23.70 | 241.67 | 23.74 |
May | 247.33 | 23.98 | 729.83 | 23.81 | 247.33 | 23.84 |
June | 258.50 | 23.98 | 719.83 | 23.83 | 258.50 | 23.86 |
July | 245.67 | 23.99 | 744.00 | 23.91 | 245.67 | 23.92 |
August | 229.83 | 23.99 | 744.00 | 23.94 | 229.83 | 23.95 |
September | 233.33 | 23.99 | 720.00 | 23.93 | 233.33 | 23.94 |
October | 240.67 | 23.98 | 742.33 | 23.92 | 240.67 | 23.93 |
November | 236.83 | 23.95 | 709.83 | 23.86 | 236.83 | 23.87 |
December | 277.83 | 23.43 | 561.33 | 23.59 | 197.67 | 23.63 |
Annual Sum or Average | 3095.83 | 23.70 | 7622.67 | 23.77 | 2561.83 | 23.80 |
Minimum of Months | 229.83 | 23.07 | 379.50 | 23.39 | 108.17 | 23.45 |
Maximum of Months | 308.00 | 23.99 | 744.00 | 23.94 | 258.50 | 23.95 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 265.67 | 23.20 | 308.67 | 23.59 | 66.50 | 23.63 |
February | 242.17 | 23.49 | 382.67 | 23.72 | 134.17 | 23.76 |
March | 231.83 | 23.47 | 440.83 | 23.74 | 119.00 | 23.78 |
April | 234.67 | 23.81 | 515.50 | 23.83 | 194.00 | 23.86 |
May | 183.50 | 23.99 | 675.17 | 23.87 | 181.33 | 23.89 |
June | 205.67 | 24.00 | 698.50 | 23.88 | 205.67 | 23.90 |
July | 183.50 | 24.00 | 744.00 | 23.90 | 183.50 | 23.92 |
August | 162.50 | 24.00 | 744.00 | 23.92 | 162.50 | 23.94 |
September | 163.17 | 24.00 | 720.00 | 23.92 | 163.17 | 23.93 |
October | 172.83 | 24.00 | 731.83 | 23.91 | 172.83 | 23.92 |
November | 182.83 | 23.99 | 690.17 | 23.86 | 182.83 | 23.88 |
December | 237.17 | 23.62 | 490.33 | 23.76 | 161.17 | 23.79 |
Annual Sum or Average | 2465.50 | 23.76 | 7141.67 | 23.84 | 1926.67 | 23.86 |
Minimum of Months | 162.50 | 23.20 | 308.67 | 23.59 | 66.50 | 23.63 |
Maximum of Months | 265.67 | 24.00 | 744.00 | 23.92 | 205.67 | 23.94 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 733.17 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
February | 625.83 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
March | 678.50 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
April | 623.67 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
May | 592.17 | 21.35 | 3.00 | 21.36 | 0.17 | 21.36 |
June | 558.33 | 21.30 | 11.00 | 21.34 | 0.00 | 21.34 |
July | 558.67 | 21.24 | 39.00 | 21.38 | 0.00 | 21.38 |
August | 553.67 | 21.23 | 60.17 | 21.44 | 0.00 | 21.44 |
September | 554.67 | 21.29 | 21.67 | 21.36 | 0.00 | 21.36 |
October | 589.33 | 21.33 | 0.00 | 21.33 | 0.00 | 21.33 |
November | 612.83 | 21.46 | 0.17 | 21.46 | 0.17 | 21.46 |
December | 699.50 | 21.58 | 0.50 | 21.59 | 0.50 | 21.59 |
Annual Sum or Average | 7380.33 | 21.43 | 135.50 | 21.46 | 0.83 | 21.47 |
Minimum of Months | 553.67 | 21.23 | 0.00 | 21.33 | 0.00 | 21.33 |
Maximum of Months | 733.17 | 21.64 | 60.17 | 21.64 | 0.50 | 21.64 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 741.67 | 22.03 | 0.83 | 22.03 | 0.83 | 22.03 |
February | 648.67 | 22.10 | 4.17 | 22.11 | 3.33 | 22.12 |
March | 674.67 | 21.95 | 11.33 | 21.98 | 7.50 | 22.00 |
April | 617.17 | 21.67 | 8.50 | 21.70 | 7.00 | 21.73 |
May | 587.83 | 21.37 | 6.50 | 21.40 | 2.00 | 21.41 |
June | 551.33 | 21.28 | 15.33 | 21.34 | 0.00 | 21.34 |
July | 554.17 | 21.23 | 40.83 | 21.37 | 0.00 | 21.37 |
August | 554.67 | 21.23 | 44.83 | 21.39 | 0.00 | 21.39 |
September | 564.17 | 21.33 | 5.17 | 21.35 | 0.00 | 21.35 |
October | 615.50 | 21.47 | 3.50 | 21.48 | 2.00 | 21.49 |
November | 631.67 | 21.72 | 10.17 | 21.76 | 6.50 | 21.78 |
December | 730.50 | 22.07 | 8.33 | 22.08 | 8.33 | 22.09 |
Annual Sum or Average | 7472.00 | 21.65 | 159.50 | 21.69 | 37.50 | 21.70 |
Minimum of Months | 551.33 | 21.23 | 0.83 | 21.34 | 0.00 | 21.34 |
Maximum of Months | 741.67 | 22.10 | 44.83 | 22.11 | 8.33 | 22.12 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.02 | 0.00 | 22.02 | 0.00 | 22.02 |
February | 672.00 | 22.09 | 2.17 | 22.09 | 2.17 | 22.10 |
March | 742.00 | 22.03 | 6.00 | 22.04 | 6.00 | 22.05 |
April | 720.00 | 21.87 | 5.33 | 21.88 | 5.33 | 21.89 |
May | 743.83 | 21.76 | 1.83 | 21.76 | 1.83 | 21.77 |
June | 720.00 | 21.74 | 0.00 | 21.74 | 0.00 | 21.74 |
July | 744.00 | 21.74 | 0.00 | 21.74 | 0.00 | 21.74 |
August | 744.00 | 21.74 | 0.00 | 21.74 | 0.00 | 21.74 |
September | 720.00 | 21.74 | 0.00 | 21.74 | 0.00 | 21.74 |
October | 743.67 | 21.75 | 2.50 | 21.76 | 2.50 | 21.77 |
November | 719.83 | 21.87 | 4.00 | 21.88 | 4.00 | 21.88 |
December | 744.00 | 22.07 | 6.33 | 22.08 | 6.33 | 22.09 |
Annual Sum or Average | 8757.33 | 21.87 | 28.17 | 21.87 | 28.17 | 21.88 |
Minimum of Months | 672.00 | 21.74 | 0.00 | 21.74 | 0.00 | 21.74 |
Maximum of Months | 744.00 | 22.09 | 6.33 | 22.09 | 6.33 | 22.10 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
February | 657.83 | 21.67 | 0.00 | 21.67 | 0.00 | 21.67 |
March | 698.50 | 21.62 | 0.00 | 21.62 | 0.00 | 21.62 |
April | 597.00 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
May | 558.00 | 21.23 | 0.00 | 21.23 | 0.00 | 21.23 |
June | 533.83 | 21.21 | 0.00 | 21.21 | 0.00 | 21.21 |
July | 547.33 | 21.20 | 21.83 | 21.28 | 0.00 | 21.28 |
August | 544.67 | 21.19 | 41.00 | 21.34 | 0.00 | 21.34 |
September | 538.50 | 21.23 | 3.83 | 21.24 | 0.00 | 21.24 |
October | 571.83 | 21.28 | 0.00 | 21.28 | 0.00 | 21.28 |
November | 603.33 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
December | 730.67 | 21.68 | 0.17 | 21.68 | 0.17 | 21.68 |
Annual Sum or Average | 7325.50 | 21.43 | 66.83 | 21.44 | 0.17 | 21.44 |
Minimum of Months | 533.83 | 21.19 | 0.00 | 21.21 | 0.00 | 21.21 |
Maximum of Months | 744.00 | 21.69 | 41.00 | 21.69 | 0.17 | 21.69 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 742.17 | 22.05 | 2.00 | 22.06 | 0.67 | 22.06 |
February | 662.50 | 22.15 | 4.67 | 22.16 | 3.17 | 22.16 |
March | 701.67 | 22.02 | 10.00 | 22.05 | 7.33 | 22.06 |
April | 570.67 | 21.55 | 26.33 | 21.69 | 7.00 | 21.72 |
May | 549.83 | 21.25 | 6.00 | 21.29 | 2.17 | 21.30 |
June | 530.33 | 21.20 | 1.33 | 21.21 | 0.00 | 21.21 |
July | 545.67 | 21.19 | 23.50 | 21.28 | 0.00 | 21.28 |
August | 544.83 | 21.19 | 35.50 | 21.32 | 0.00 | 21.32 |
September | 539.33 | 21.24 | 0.83 | 21.25 | 0.00 | 21.25 |
October | 579.33 | 21.36 | 9.00 | 21.41 | 2.17 | 21.42 |
November | 638.83 | 21.77 | 32.00 | 21.91 | 7.83 | 21.94 |
December | 734.00 | 22.10 | 12.67 | 22.12 | 8.83 | 22.13 |
Annual Sum or Average | 7339.17 | 21.64 | 163.83 | 21.69 | 39.17 | 21.70 |
Minimum of Months | 530.33 | 21.19 | 0.83 | 21.21 | 0.00 | 21.21 |
Maximum of Months | 742.17 | 22.15 | 35.50 | 22.16 | 8.83 | 22.16 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.16 | 0.00 | 22.16 | 0.00 | 22.16 |
February | 672.00 | 22.48 | 0.00 | 22.48 | 0.00 | 22.48 |
March | 744.00 | 22.76 | 0.83 | 22.76 | 0.83 | 22.76 |
April | 638.00 | 23.09 | 6.50 | 23.10 | 0.50 | 23.10 |
May | 90.33 | 23.58 | 342.33 | 23.84 | 30.17 | 23.84 |
June | 90.83 | 23.96 | 616.67 | 23.95 | 90.83 | 23.95 |
July | 50.50 | 23.99 | 727.67 | 23.98 | 50.50 | 23.98 |
August | 28.50 | 24.00 | 742.67 | 23.98 | 28.50 | 23.98 |
September | 30.50 | 23.94 | 650.67 | 23.95 | 30.50 | 23.95 |
October | 49.83 | 23.72 | 349.33 | 23.88 | 21.67 | 23.88 |
November | 505.50 | 23.19 | 16.33 | 23.20 | 7.00 | 23.21 |
December | 744.00 | 22.56 | 0.00 | 22.56 | 0.00 | 22.56 |
Annual Sum or Average | 4388.00 | 22.76 | 3453.00 | 23.29 | 260.50 | 23.31 |
Minimum of Months | 28.50 | 22.16 | 0.00 | 22.16 | 0.00 | 22.16 |
Maximum of Months | 744.00 | 24.00 | 742.67 | 23.98 | 90.83 | 23.98 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 705.33 | 21.55 | 1.33 | 21.55 | 1.33 | 21.56 |
February | 605.83 | 21.49 | 2.33 | 21.49 | 2.33 | 21.50 |
March | 652.17 | 21.47 | 1.50 | 21.47 | 0.67 | 21.47 |
April | 592.83 | 21.39 | 4.00 | 21.40 | 0.67 | 21.40 |
May | 575.50 | 21.29 | 41.00 | 21.43 | 0.67 | 21.43 |
June | 542.83 | 21.25 | 77.00 | 21.51 | 0.00 | 21.51 |
July | 548.33 | 21.22 | 111.67 | 21.57 | 0.00 | 21.57 |
August | 546.67 | 21.21 | 125.83 | 21.61 | 0.00 | 21.61 |
September | 546.67 | 21.27 | 84.00 | 21.54 | 0.00 | 21.54 |
October | 580.83 | 21.30 | 38.83 | 21.43 | 0.17 | 21.43 |
November | 598.50 | 21.41 | 2.17 | 21.41 | 2.17 | 21.42 |
December | 669.67 | 21.49 | 5.67 | 21.50 | 5.67 | 21.50 |
Annual Sum or Average | 7165.17 | 21.37 | 495.33 | 21.50 | 13.67 | 21.50 |
Minimum of Months | 542.83 | 21.21 | 1.33 | 21.40 | 0.00 | 21.40 |
Maximum of Months | 705.33 | 21.55 | 125.83 | 21.61 | 5.67 | 21.61 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 737.00 | 21.98 | 5.67 | 21.98 | 5.67 | 21.99 |
February | 613.00 | 21.98 | 21.17 | 22.02 | 16.83 | 22.04 |
March | 636.50 | 21.82 | 20.17 | 21.88 | 12.50 | 21.90 |
April | 593.33 | 21.58 | 18.67 | 21.64 | 16.00 | 21.68 |
May | 571.00 | 21.32 | 41.83 | 21.46 | 3.17 | 21.47 |
June | 538.50 | 21.24 | 83.33 | 21.53 | 0.00 | 21.53 |
July | 546.67 | 21.21 | 112.00 | 21.57 | 0.00 | 21.57 |
August | 546.83 | 21.21 | 112.67 | 21.58 | 0.00 | 21.58 |
September | 553.17 | 21.30 | 54.67 | 21.48 | 0.67 | 21.48 |
October | 595.50 | 21.40 | 7.50 | 21.42 | 3.67 | 21.43 |
November | 620.00 | 21.65 | 18.50 | 21.70 | 18.33 | 21.75 |
December | 710.33 | 21.98 | 27.83 | 22.00 | 27.83 | 22.02 |
Annual Sum or Average | 7261.83 | 21.58 | 524.00 | 21.70 | 104.67 | 21.72 |
Minimum of Months | 538.50 | 21.21 | 5.67 | 21.42 | 0.00 | 21.43 |
Maximum of Months | 737.00 | 21.98 | 112.67 | 22.02 | 27.83 | 22.04 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 672.83 | 21.53 | 0.00 | 21.53 | 0.00 | 21.53 |
February | 590.50 | 21.48 | 0.00 | 21.48 | 0.00 | 21.48 |
March | 659.00 | 21.50 | 0.67 | 21.50 | 0.67 | 21.50 |
April | 626.50 | 21.49 | 0.67 | 21.49 | 0.67 | 21.50 |
May | 612.67 | 21.41 | 0.67 | 21.41 | 0.67 | 21.41 |
June | 577.50 | 21.36 | 0.00 | 21.36 | 0.00 | 21.36 |
July | 578.83 | 21.31 | 1.67 | 21.31 | 0.00 | 21.31 |
August | 574.17 | 21.29 | 13.67 | 21.34 | 0.00 | 21.34 |
September | 559.33 | 21.30 | 33.33 | 21.41 | 0.00 | 21.41 |
October | 586.67 | 21.33 | 28.67 | 21.42 | 0.00 | 21.42 |
November | 586.83 | 21.39 | 3.33 | 21.40 | 1.67 | 21.40 |
December | 646.50 | 21.47 | 0.67 | 21.47 | 0.67 | 21.47 |
Annual Sum or Average | 7271.33 | 21.41 | 83.33 | 21.43 | 4.33 | 21.43 |
Minimum of Months | 559.33 | 21.29 | 0.00 | 21.31 | 0.00 | 21.31 |
Maximum of Months | 672.83 | 21.53 | 33.33 | 21.53 | 1.67 | 21.53 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 116.50 | 23.69 | 579.83 | 23.85 | 79.67 | 23.86 |
February | 149.00 | 23.98 | 623.17 | 23.90 | 147.33 | 23.91 |
March | 124.17 | 24.00 | 707.17 | 23.92 | 124.17 | 23.93 |
April | 195.17 | 24.00 | 717.83 | 23.96 | 195.17 | 23.97 |
May | 201.50 | 24.00 | 744.00 | 23.99 | 201.50 | 23.99 |
June | 212.83 | 24.00 | 720.00 | 23.99 | 212.83 | 23.99 |
July | 208.17 | 24.00 | 744.00 | 23.99 | 208.17 | 23.99 |
August | 201.00 | 24.00 | 744.00 | 23.99 | 201.00 | 23.99 |
September | 196.33 | 24.00 | 720.00 | 23.99 | 196.33 | 23.99 |
October | 204.50 | 24.00 | 744.00 | 23.98 | 204.50 | 23.98 |
November | 200.00 | 24.00 | 720.00 | 23.95 | 200.00 | 23.96 |
December | 185.83 | 23.98 | 680.67 | 23.90 | 182.67 | 23.91 |
Annual Sum or Average | 2195.00 | 23.98 | 8444.67 | 23.96 | 2153.33 | 23.96 |
Minimum of Months | 116.50 | 23.69 | 579.83 | 23.85 | 79.67 | 23.86 |
Maximum of Months | 212.83 | 24.00 | 744.00 | 23.99 | 212.83 | 23.99 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 62.00 | 24.00 | 680.50 | 23.91 | 62.00 | 23.92 |
February | 125.67 | 24.00 | 666.00 | 23.93 | 125.67 | 23.94 |
March | 106.50 | 24.00 | 738.67 | 23.96 | 106.50 | 23.96 |
April | 176.83 | 24.00 | 720.00 | 23.98 | 176.83 | 23.98 |
May | 189.33 | 24.00 | 744.00 | 23.99 | 189.33 | 23.99 |
June | 203.33 | 24.00 | 720.00 | 23.99 | 203.33 | 23.99 |
July | 197.17 | 24.00 | 744.00 | 24.00 | 197.17 | 24.00 |
August | 188.83 | 24.00 | 744.00 | 23.99 | 188.83 | 23.99 |
September | 188.00 | 24.00 | 720.00 | 23.99 | 188.00 | 23.99 |
October | 191.33 | 24.00 | 744.00 | 23.99 | 191.33 | 23.99 |
November | 184.17 | 24.00 | 720.00 | 23.98 | 184.17 | 23.98 |
December | 150.33 | 24.00 | 739.33 | 23.93 | 150.33 | 23.94 |
Annual Sum or Average | 1963.50 | 24.00 | 8680.50 | 23.97 | 1963.50 | 23.98 |
Minimum of Months | 62.00 | 24.00 | 666.00 | 23.91 | 62.00 | 23.92 |
Maximum of Months | 203.33 | 24.00 | 744.00 | 24.00 | 203.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 541.00 | 23.99 | 742.83 | 23.89 | 541.00 | 23.92 |
February | 500.33 | 23.99 | 672.00 | 23.91 | 500.33 | 23.93 |
March | 565.00 | 23.99 | 744.00 | 23.93 | 565.00 | 23.95 |
April | 570.50 | 23.99 | 720.00 | 23.95 | 570.50 | 23.96 |
May | 625.50 | 23.99 | 744.00 | 23.98 | 625.50 | 23.98 |
June | 634.17 | 23.99 | 720.00 | 23.99 | 634.17 | 23.99 |
July | 704.33 | 23.99 | 744.00 | 23.99 | 704.33 | 23.99 |
August | 712.67 | 23.99 | 744.00 | 23.99 | 712.67 | 23.99 |
September | 627.33 | 23.99 | 720.00 | 23.99 | 627.33 | 23.99 |
October | 609.33 | 23.99 | 744.00 | 23.97 | 609.33 | 23.98 |
November | 564.00 | 23.99 | 720.00 | 23.94 | 564.00 | 23.96 |
December | 557.00 | 23.99 | 744.00 | 23.91 | 557.00 | 23.94 |
Annual Sum or Average | 7211.17 | 23.99 | 8758.83 | 23.96 | 7211.17 | 23.97 |
Minimum of Months | 500.33 | 23.99 | 672.00 | 23.89 | 500.33 | 23.92 |
Maximum of Months | 712.67 | 23.99 | 744.00 | 23.99 | 712.67 | 23.99 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.83 | 0.00 | 21.83 | 0.00 | 21.83 |
February | 664.33 | 22.21 | 0.00 | 22.21 | 0.00 | 22.21 |
March | 681.67 | 22.53 | 7.83 | 22.54 | 0.00 | 22.54 |
April | 412.00 | 22.89 | 80.33 | 23.04 | 0.00 | 23.04 |
May | 16.33 | 23.09 | 609.17 | 23.89 | 0.00 | 23.89 |
June | 0.00 | 0.00 | 716.67 | 23.94 | 0.00 | 23.94 |
July | 0.00 | 0.00 | 744.00 | 23.99 | 0.00 | 23.99 |
August | 0.00 | 0.00 | 744.00 | 23.99 | 0.00 | 23.99 |
September | 0.00 | 0.00 | 693.83 | 23.94 | 0.00 | 23.94 |
October | 41.17 | 23.11 | 527.00 | 23.81 | 0.00 | 23.81 |
November | 431.50 | 22.85 | 91.67 | 23.01 | 0.00 | 23.01 |
December | 742.83 | 22.23 | 0.00 | 22.23 | 0.00 | 22.23 |
Annual Sum or Average | 3733.83 | 22.36 | 4214.50 | 23.20 | 0.00 | 23.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.83 | 0.00 | 21.83 |
Maximum of Months | 744.00 | 23.11 | 744.00 | 23.99 | 0.00 | 23.99 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.86364 | 50.77766 | 0.40107 | 8.45380 |
February | 672.00000 | 23.57787 | 55.64715 | 0.35482 | 7.73705 |
March | 744.00000 | 23.00440 | 55.73836 | 0.20368 | 6.01442 |
April | 720.00000 | 22.69422 | 59.08323 | 0.14320 | 5.59744 |
May | 744.00000 | 22.85824 | 59.45760 | -0.8261 | 19.59573 |
June | 720.00000 | 23.16895 | 59.32402 | -0.7121 | 15.86400 |
July | 744.00000 | 23.58815 | 57.93028 | -0.5652 | 11.86545 |
August | 744.00000 | 23.87863 | 56.71861 | -0.4555 | 9.40801 |
September | 720.00000 | 23.92824 | 56.68333 | -0.4316 | 8.95193 |
October | 744.00000 | 23.97320 | 55.83218 | 0.48330 | 9.90972 |
November | 720.00000 | 23.98658 | 56.78798 | 0.49262 | 10.08627 |
December | 744.00000 | 23.94957 | 54.71250 | 0.45931 | 9.45008 |
Annual Sum or Average | 8760.00000 | 23.54003 | 56.54975 | -0.0400 | 10.26641 |
Minimum of Months | 672.00000 | 22.69422 | 50.77766 | -0.8261 | 5.59744 |
Maximum of Months | 744.00000 | 23.98658 | 59.45760 | 0.49262 | 19.59573 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.08822 | 54.90777 | 0.05856 | 6.01156 |
February | 672.00000 | 22.33384 | 58.47837 | 0.15249 | 6.43913 |
March | 744.00000 | 22.57127 | 55.95920 | 0.20623 | 6.74433 |
April | 720.00000 | 22.95529 | 57.25359 | 0.32541 | 7.76349 |
May | 744.00000 | 23.62783 | 55.99889 | -0.3606 | 8.23729 |
June | 720.00000 | 23.80668 | 56.40538 | -0.2783 | 6.85902 |
July | 744.00000 | 23.94258 | 55.88038 | -0.2038 | 5.97970 |
August | 744.00000 | 23.96915 | 55.77249 | -0.1791 | 5.77213 |
September | 720.00000 | 23.85646 | 56.50212 | -0.2335 | 6.50923 |
October | 744.00000 | 23.69603 | 56.42336 | 0.55423 | 11.75880 |
November | 720.00000 | 23.28101 | 58.76561 | 0.43399 | 9.60921 |
December | 744.00000 | 22.44904 | 58.83479 | 0.18699 | 6.71651 |
Annual Sum or Average | 8760.00000 | 23.21917 | 56.74597 | 0.05433 | 7.37083 |
Minimum of Months | 672.00000 | 22.08822 | 54.90777 | -0.3606 | 5.77213 |
Maximum of Months | 744.00000 | 23.96915 | 58.83479 | 0.55423 | 11.75880 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.08083 | 54.05875 | 0.24240 | 6.57637 |
February | 672.00000 | 23.23025 | 57.62950 | 0.30839 | 7.28087 |
March | 744.00000 | 23.37635 | 55.47502 | 0.33707 | 7.68656 |
April | 720.00000 | 23.56419 | 57.15158 | 0.40370 | 8.67075 |
May | 744.00000 | 23.81238 | 56.93452 | -0.4151 | 8.80436 |
June | 720.00000 | 23.86878 | 57.51152 | -0.3805 | 8.14784 |
July | 744.00000 | 23.91612 | 57.24072 | -0.3554 | 7.70366 |
August | 744.00000 | 23.93723 | 57.14336 | -0.3435 | 7.51233 |
September | 720.00000 | 23.90545 | 57.70371 | -0.3625 | 7.83703 |
October | 744.00000 | 23.85233 | 57.48472 | 0.49824 | 10.27983 |
November | 720.00000 | 23.69093 | 59.26938 | 0.45433 | 9.42544 |
December | 744.00000 | 23.29553 | 58.14829 | 0.32988 | 7.53185 |
Annual Sum or Average | 8760.00000 | 23.62937 | 57.13359 | 0.05805 | 8.12394 |
Minimum of Months | 672.00000 | 23.08083 | 54.05875 | -0.4151 | 6.57637 |
Maximum of Months | 744.00000 | 23.93723 | 59.26938 | 0.49824 | 10.27983 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.06073 | 49.56799 | 0.83414 | 22.05382 |
February | 672.00000 | 23.07087 | 53.59138 | 0.87309 | 23.32930 |
March | 744.00000 | 23.07464 | 51.88998 | 0.87856 | 23.54400 |
April | 720.00000 | 23.09590 | 54.16225 | 0.91845 | 24.89164 |
May | 744.00000 | 23.12437 | 54.94840 | 0.28202 | 11.11485 |
June | 720.00000 | 23.13026 | 55.83763 | 0.30371 | 11.33293 |
July | 744.00000 | 23.14505 | 55.78935 | 0.32006 | 11.37198 |
August | 744.00000 | 23.14334 | 55.81811 | 0.32746 | 11.52907 |
September | 720.00000 | 23.13540 | 56.13155 | 0.30166 | 11.22343 |
October | 744.00000 | 23.13517 | 55.54408 | 0.95824 | 26.27500 |
November | 720.00000 | 23.13021 | 56.68627 | 0.93885 | 25.54853 |
December | 744.00000 | 23.08133 | 54.26653 | 0.87990 | 23.49118 |
Annual Sum or Average | 8760.00000 | 23.11080 | 54.51410 | 0.64991 | 18.77779 |
Minimum of Months | 672.00000 | 23.06073 | 49.56799 | 0.28202 | 11.11485 |
Maximum of Months | 744.00000 | 23.14505 | 56.68627 | 0.95824 | 26.27500 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.26936 | 57.46043 | 0.39579 | 8.75614 |
February | 672.00000 | 23.36737 | 61.07970 | 0.45641 | 9.79270 |
March | 744.00000 | 23.40590 | 59.19062 | 0.46389 | 9.94883 |
April | 720.00000 | 23.52580 | 60.94205 | 0.52419 | 11.08311 |
May | 744.00000 | 23.73181 | 60.66348 | -0.2403 | 6.46524 |
June | 720.00000 | 23.77846 | 61.20164 | -0.2011 | 6.03063 |
July | 744.00000 | 23.87819 | 60.59064 | -0.1380 | 5.50452 |
August | 744.00000 | 23.91803 | 60.34720 | -0.1090 | 5.34412 |
September | 720.00000 | 23.91011 | 60.89589 | -0.1270 | 5.52447 |
October | 744.00000 | 23.89436 | 60.61027 | 0.67472 | 14.68014 |
November | 720.00000 | 23.81201 | 62.39329 | 0.62927 | 13.49045 |
December | 744.00000 | 23.45536 | 61.49930 | 0.48590 | 10.35581 |
Annual Sum or Average | 8760.00000 | 23.66362 | 60.56010 | 0.23305 | 8.90618 |
Minimum of Months | 672.00000 | 23.26936 | 57.46043 | -0.2403 | 5.34412 |
Maximum of Months | 744.00000 | 23.91803 | 62.39329 | 0.67472 | 14.68014 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.47915 | 55.95733 | 0.38300 | 8.40434 |
February | 672.00000 | 23.54880 | 59.56411 | 0.43169 | 9.16016 |
March | 744.00000 | 23.57858 | 57.65506 | 0.43356 | 9.20806 |
April | 720.00000 | 23.65229 | 59.48578 | 0.47528 | 9.99153 |
May | 744.00000 | 23.78059 | 59.48317 | -0.3555 | 7.86681 |
June | 720.00000 | 23.82599 | 60.04405 | -0.3235 | 7.34904 |
July | 744.00000 | 23.87874 | 59.70388 | -0.2934 | 6.89542 |
August | 744.00000 | 23.90858 | 59.56776 | -0.2776 | 6.67609 |
September | 720.00000 | 23.90481 | 60.06312 | -0.2879 | 6.81166 |
October | 744.00000 | 23.88625 | 59.75124 | 0.56344 | 11.71191 |
November | 720.00000 | 23.80460 | 61.40613 | 0.53567 | 11.08812 |
December | 744.00000 | 23.60185 | 60.04837 | 0.45139 | 9.48549 |
Annual Sum or Average | 8760.00000 | 23.73842 | 59.38339 | 0.14281 | 8.71613 |
Minimum of Months | 672.00000 | 23.47915 | 55.95733 | -0.3555 | 6.67609 |
Maximum of Months | 744.00000 | 23.90858 | 61.40613 | 0.56344 | 11.71191 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.66474 | 57.49853 | -0.1039 | 5.99733 |
February | 672.00000 | 21.68661 | 57.76718 | -0.0710 | 5.88177 |
March | 744.00000 | 21.70865 | 54.60123 | -0.0527 | 5.86204 |
April | 720.00000 | 21.73387 | 52.79043 | -0.0215 | 5.86661 |
May | 744.00000 | 21.75099 | 50.27962 | -1.0282 | 28.82798 |
June | 720.00000 | 21.75538 | 50.56430 | -0.9988 | 27.58544 |
July | 744.00000 | 21.75852 | 50.83664 | -0.9708 | 26.43280 |
August | 744.00000 | 21.75922 | 51.04380 | -0.9587 | 25.97779 |
September | 720.00000 | 21.75414 | 50.61340 | -0.9977 | 27.64020 |
October | 744.00000 | 21.74780 | 50.99848 | 0.01743 | 5.85428 |
November | 720.00000 | 21.73486 | 53.36295 | -0.0208 | 5.85478 |
December | 744.00000 | 21.68945 | 57.78060 | -0.0694 | 5.87460 |
Annual Sum or Average | 8760.00000 | 21.72886 | 53.15512 | -0.4419 | 14.85680 |
Minimum of Months | 672.00000 | 21.66474 | 50.27962 | -1.0282 | 5.85428 |
Maximum of Months | 744.00000 | 21.75922 | 57.78060 | 0.01743 | 28.82798 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.03114 | 58.65928 | -0.0485 | 5.87015 |
February | 672.00000 | 22.15150 | 58.84971 | 0.01122 | 5.91968 |
March | 744.00000 | 22.10333 | 54.72769 | 0.01705 | 5.94240 |
April | 720.00000 | 21.92270 | 53.15145 | 0.01318 | 5.94327 |
May | 744.00000 | 21.78685 | 50.38562 | -1.0174 | 28.40076 |
June | 720.00000 | 21.76130 | 50.64492 | -0.9924 | 27.33609 |
July | 744.00000 | 21.75937 | 51.02417 | -0.9680 | 26.31687 |
August | 744.00000 | 21.75938 | 51.20130 | -0.9631 | 26.12004 |
September | 720.00000 | 21.76329 | 50.85911 | -1.0107 | 28.09849 |
October | 744.00000 | 21.79505 | 51.77640 | 0.01089 | 5.83087 |
November | 720.00000 | 21.93138 | 54.88743 | 0.00263 | 5.88532 |
December | 744.00000 | 22.09580 | 59.30843 | -0.0018 | 5.82956 |
Annual Sum or Average | 8760.00000 | 21.90373 | 53.76342 | -0.4148 | 14.84185 |
Minimum of Months | 672.00000 | 21.75937 | 50.38562 | -1.0174 | 5.82956 |
Maximum of Months | 744.00000 | 22.15150 | 59.30843 | 0.01705 | 28.40076 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.02006 | 54.82954 | -0.0834 | 5.73801 |
February | 672.00000 | 22.08871 | 56.25186 | -0.0443 | 5.71249 |
March | 744.00000 | 22.03221 | 53.54643 | -0.0563 | 5.75403 |
April | 720.00000 | 21.86525 | 53.60888 | -0.0748 | 5.82511 |
May | 744.00000 | 21.75884 | 51.63443 | -1.1791 | 35.22408 |
June | 720.00000 | 21.74101 | 52.31780 | -1.1638 | 34.51666 |
July | 744.00000 | 21.74300 | 52.78459 | -1.1483 | 33.80374 |
August | 744.00000 | 21.74143 | 52.89518 | -1.1495 | 33.84755 |
September | 720.00000 | 21.73837 | 52.31002 | -1.1786 | 35.20803 |
October | 744.00000 | 21.75557 | 52.88439 | -0.0903 | 5.77890 |
November | 720.00000 | 21.86856 | 55.19197 | -0.0773 | 5.76082 |
December | 744.00000 | 22.07356 | 56.59507 | -0.0479 | 5.69425 |
Annual Sum or Average | 8760.00000 | 21.86779 | 53.72102 | -0.5273 | 17.80911 |
Minimum of Months | 672.00000 | 21.73837 | 51.63443 | -1.1791 | 5.69425 |
Maximum of Months | 744.00000 | 22.08871 | 56.59507 | -0.0443 | 35.22408 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.69100 | 56.78315 | -0.1004 | 5.97315 |
February | 672.00000 | 21.70546 | 57.16348 | -0.0700 | 5.86108 |
March | 744.00000 | 21.72102 | 54.03944 | -0.0562 | 5.86316 |
April | 720.00000 | 21.74372 | 52.48854 | -0.0178 | 5.89454 |
May | 744.00000 | 21.75655 | 50.39853 | -1.0196 | 28.50803 |
June | 720.00000 | 21.75868 | 50.63969 | -0.9961 | 27.50491 |
July | 744.00000 | 21.76121 | 51.13725 | -0.9660 | 26.27173 |
August | 744.00000 | 21.76194 | 51.50859 | -0.9534 | 25.79988 |
September | 720.00000 | 21.75756 | 50.73938 | -0.9944 | 27.51873 |
October | 744.00000 | 21.75309 | 51.27523 | 0.02262 | 5.87113 |
November | 720.00000 | 21.74357 | 53.29733 | -0.0182 | 5.85679 |
December | 744.00000 | 21.70705 | 57.25065 | -0.0692 | 5.85715 |
Annual Sum or Average | 8760.00000 | 21.73854 | 53.04028 | -0.4388 | 14.78310 |
Minimum of Months | 672.00000 | 21.69100 | 50.39853 | -1.0196 | 5.85679 |
Maximum of Months | 744.00000 | 21.76194 | 57.25065 | 0.02262 | 28.50803 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.05605 | 57.95364 | -0.0458 | 5.80560 |
February | 672.00000 | 22.17023 | 58.31186 | 0.01234 | 5.85763 |
March | 744.00000 | 22.10929 | 54.41061 | 0.01340 | 5.92402 |
April | 720.00000 | 21.96617 | 52.90403 | 0.02438 | 6.12855 |
May | 744.00000 | 21.79855 | 50.44418 | -1.0074 | 28.08178 |
June | 720.00000 | 21.76612 | 50.71623 | -0.9894 | 27.25231 |
July | 744.00000 | 21.76238 | 51.29996 | -0.9633 | 26.15601 |
August | 744.00000 | 21.76206 | 51.67228 | -0.9577 | 25.93745 |
September | 720.00000 | 21.76745 | 51.05222 | -1.0066 | 27.95309 |
October | 744.00000 | 21.81207 | 52.01481 | 0.01832 | 5.89386 |
November | 720.00000 | 21.99915 | 54.52863 | 0.01604 | 6.09639 |
December | 744.00000 | 22.12524 | 58.85885 | 0.00104 | 5.81118 |
Annual Sum or Average | 8760.00000 | 21.92309 | 53.65767 | -0.4096 | 14.79132 |
Minimum of Months | 672.00000 | 21.76206 | 50.44418 | -1.0074 | 5.80560 |
Maximum of Months | 744.00000 | 22.17023 | 58.85885 | 0.02438 | 28.08178 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.64696 | 59.02259 | -0.1103 | 6.14595 |
February | 672.00000 | 21.67319 | 59.38931 | -0.0722 | 5.98393 |
March | 744.00000 | 21.69881 | 55.73924 | -0.0507 | 5.96443 |
April | 720.00000 | 21.72954 | 53.61161 | -0.0141 | 5.96548 |
May | 744.00000 | 21.75093 | 50.53051 | -1.0114 | 28.35114 |
June | 720.00000 | 21.75584 | 50.58974 | -0.9794 | 27.01201 |
July | 744.00000 | 21.75881 | 50.83487 | -0.9451 | 25.64664 |
August | 744.00000 | 21.75916 | 51.01661 | -0.9338 | 25.24122 |
September | 720.00000 | 21.75346 | 50.84157 | -0.9811 | 27.19140 |
October | 744.00000 | 21.74596 | 51.50846 | 0.02400 | 5.96622 |
November | 720.00000 | 21.73038 | 54.53281 | -0.0184 | 5.93600 |
December | 744.00000 | 21.67545 | 59.42896 | -0.0726 | 5.97039 |
Annual Sum or Average | 8760.00000 | 21.72341 | 53.89231 | -0.4326 | 14.66456 |
Minimum of Months | 672.00000 | 21.64696 | 50.53051 | -1.0114 | 5.93600 |
Maximum of Months | 744.00000 | 21.75916 | 59.42896 | 0.02400 | 28.35114 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.99060 | 60.19453 | -0.0590 | 6.05387 |
February | 672.00000 | 22.11756 | 60.33677 | 0.00717 | 6.05065 |
March | 744.00000 | 22.07168 | 55.72752 | 0.01570 | 6.05807 |
April | 720.00000 | 21.89079 | 53.91638 | 0.01519 | 6.00740 |
May | 744.00000 | 21.78312 | 50.62566 | -1.0015 | 27.95003 |
June | 720.00000 | 21.76156 | 50.72742 | -0.9726 | 26.75843 |
July | 744.00000 | 21.75971 | 51.01069 | -0.9423 | 25.53930 |
August | 744.00000 | 21.75948 | 51.07809 | -0.9388 | 25.39483 |
September | 720.00000 | 21.76176 | 51.00019 | -0.9951 | 27.65425 |
October | 744.00000 | 21.78507 | 52.36913 | 0.01592 | 5.90957 |
November | 720.00000 | 21.88906 | 56.13772 | -0.0026 | 5.91289 |
December | 744.00000 | 22.04134 | 61.01210 | -0.0123 | 5.92878 |
Annual Sum or Average | 8760.00000 | 21.88303 | 54.48063 | -0.4083 | 14.65007 |
Minimum of Months | 672.00000 | 21.75948 | 50.62566 | -1.0015 | 5.90957 |
Maximum of Months | 744.00000 | 22.11756 | 61.01210 | 0.01592 | 27.95003 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.70066 | 55.50120 | -0.0881 | 6.08905 |
February | 672.00000 | 21.70208 | 56.59315 | -0.0680 | 5.98980 |
March | 744.00000 | 21.71007 | 54.30647 | -0.0660 | 5.97241 |
April | 720.00000 | 21.73120 | 53.28249 | -0.0460 | 5.94102 |
May | 744.00000 | 21.74687 | 51.13284 | -1.0833 | 31.22554 |
June | 720.00000 | 21.75079 | 51.26657 | -1.0618 | 30.25912 |
July | 744.00000 | 21.75612 | 51.13623 | -1.0288 | 28.85013 |
August | 744.00000 | 21.75787 | 51.25192 | -1.0126 | 28.23672 |
September | 720.00000 | 21.75369 | 51.37034 | -1.0308 | 29.18284 |
October | 744.00000 | 21.75146 | 51.60299 | 0.01179 | 5.98402 |
November | 720.00000 | 21.74592 | 53.33434 | -0.0149 | 5.96802 |
December | 744.00000 | 21.71344 | 56.04138 | -0.0603 | 5.97747 |
Annual Sum or Average | 8760.00000 | 21.73517 | 53.04763 | -0.4648 | 15.86477 |
Minimum of Months | 672.00000 | 21.70066 | 51.13284 | -1.0833 | 5.94102 |
Maximum of Months | 744.00000 | 21.75787 | 56.59315 | 0.01179 | 31.22554 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.76222 | 56.11762 | 0.49447 | 10.35734 |
February | 672.00000 | 23.83468 | 59.50680 | 0.55388 | 11.57927 |
March | 744.00000 | 23.88856 | 57.40344 | 0.57486 | 12.06214 |
April | 720.00000 | 23.95299 | 59.07055 | 0.63120 | 13.46035 |
May | 744.00000 | 23.98912 | 59.25954 | -0.1399 | 5.44358 |
June | 720.00000 | 23.99308 | 59.88829 | -0.1145 | 5.29316 |
July | 744.00000 | 23.99442 | 59.73331 | -0.0968 | 5.20936 |
August | 744.00000 | 23.99378 | 59.77959 | -0.0973 | 5.21120 |
September | 720.00000 | 23.99009 | 60.35394 | -0.1249 | 5.36421 |
October | 744.00000 | 23.97405 | 60.18467 | 0.66683 | 14.37928 |
November | 720.00000 | 23.93333 | 61.83270 | 0.63116 | 13.40623 |
December | 744.00000 | 23.82951 | 60.22454 | 0.55544 | 11.61727 |
Annual Sum or Average | 8760.00000 | 23.92832 | 59.43654 | 0.29283 | 9.43185 |
Minimum of Months | 672.00000 | 23.76222 | 56.11762 | -0.1399 | 5.20936 |
Maximum of Months | 744.00000 | 23.99442 | 61.83270 | 0.66683 | 14.37928 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.87389 | 55.12659 | 0.55604 | 11.63894 |
February | 672.00000 | 23.91808 | 58.61734 | 0.60671 | 12.82027 |
March | 744.00000 | 23.94792 | 56.65412 | 0.62040 | 13.17332 |
April | 720.00000 | 23.97889 | 58.48951 | 0.66584 | 14.39720 |
May | 744.00000 | 23.99357 | 58.85267 | -0.1023 | 5.25278 |
June | 720.00000 | 23.99447 | 59.51729 | -0.0790 | 5.15200 |
July | 744.00000 | 23.99529 | 59.38097 | -0.0619 | 5.09700 |
August | 744.00000 | 23.99485 | 59.42671 | -0.0625 | 5.09761 |
September | 720.00000 | 23.99363 | 59.96454 | -0.0890 | 5.20367 |
October | 744.00000 | 23.98790 | 59.72313 | 0.69496 | 15.18544 |
November | 720.00000 | 23.97043 | 61.19513 | 0.66817 | 14.40871 |
December | 744.00000 | 23.91192 | 59.33348 | 0.60781 | 12.84808 |
Annual Sum or Average | 8760.00000 | 23.96355 | 58.84851 | 0.33369 | 10.00247 |
Minimum of Months | 672.00000 | 23.87389 | 55.12659 | -0.1023 | 5.09700 |
Maximum of Months | 744.00000 | 23.99529 | 61.19513 | 0.69496 | 15.18544 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.82290 | 54.18917 | 1.18178 | 36.13290 |
February | 672.00000 | 23.84789 | 57.79014 | 1.23025 | 38.24142 |
March | 744.00000 | 23.88396 | 56.02984 | 1.25244 | 39.19327 |
April | 720.00000 | 23.92265 | 57.96415 | 1.31111 | 41.87788 |
May | 744.00000 | 23.97024 | 58.45662 | 0.85309 | 23.48576 |
June | 720.00000 | 23.98164 | 59.17331 | 0.88211 | 24.39048 |
July | 744.00000 | 23.98943 | 59.10503 | 0.90884 | 25.28362 |
August | 744.00000 | 23.99057 | 59.12757 | 0.91320 | 25.42844 |
September | 720.00000 | 23.97951 | 59.52106 | 0.87307 | 24.09012 |
October | 744.00000 | 23.95888 | 59.16782 | 1.35592 | 43.95398 |
November | 720.00000 | 23.90802 | 60.49725 | 1.30873 | 41.77705 |
December | 744.00000 | 23.85112 | 58.43550 | 1.23388 | 38.37712 |
Annual Sum or Average | 8760.00000 | 23.92596 | 58.28125 | 1.10787 | 33.48585 |
Minimum of Months | 672.00000 | 23.82290 | 54.18917 | 0.85309 | 23.48576 |
Maximum of Months | 744.00000 | 23.99057 | 60.49725 | 1.35592 | 43.95398 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.34778 | 52.84175 | 0.02044 | 5.18203 |
February | 672.00000 | 22.58710 | 56.35065 | 0.10508 | 5.36750 |
March | 744.00000 | 22.83319 | 53.85497 | 0.15370 | 5.66326 |
April | 720.00000 | 23.23361 | 55.13019 | 0.26553 | 6.59638 |
May | 744.00000 | 23.84930 | 54.16395 | -0.4935 | 10.17999 |
June | 720.00000 | 23.97866 | 54.79861 | -0.4346 | 8.95417 |
July | 744.00000 | 23.99755 | 54.71143 | -0.4175 | 8.63722 |
August | 744.00000 | 23.99842 | 54.74619 | -0.4142 | 8.57915 |
September | 720.00000 | 23.96506 | 55.25104 | -0.4364 | 9.01017 |
October | 744.00000 | 23.79611 | 55.07004 | 0.41520 | 8.64415 |
November | 720.00000 | 23.32291 | 57.41546 | 0.30501 | 7.00624 |
December | 744.00000 | 22.68781 | 56.79739 | 0.13424 | 5.51906 |
Annual Sum or Average | 8760.00000 | 23.38702 | 55.07790 | -0.0677 | 7.45712 |
Minimum of Months | 672.00000 | 22.34778 | 52.84175 | -0.4935 | 5.18203 |
Maximum of Months | 744.00000 | 23.99842 | 57.41546 | 0.41520 | 10.17999 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.15570 | 57.40454 | -0.0303 | 5.19003 |
February | 672.00000 | 22.48138 | 60.70200 | 0.07466 | 5.21926 |
March | 744.00000 | 22.75782 | 58.12854 | 0.13045 | 5.50068 |
April | 720.00000 | 23.15596 | 59.41956 | 0.24141 | 6.32298 |
May | 744.00000 | 23.79108 | 58.32145 | -0.5344 | 11.05948 |
June | 720.00000 | 23.93045 | 58.65907 | -0.4786 | 9.80644 |
July | 744.00000 | 23.97262 | 58.27084 | -0.4607 | 9.43968 |
August | 744.00000 | 23.98046 | 58.17494 | -0.4562 | 9.34924 |
September | 720.00000 | 23.93759 | 58.94265 | -0.4723 | 9.69943 |
October | 744.00000 | 23.79947 | 58.97125 | 0.40833 | 8.51476 |
November | 720.00000 | 23.30840 | 61.49888 | 0.29579 | 6.89914 |
December | 744.00000 | 22.56345 | 61.19966 | 0.09928 | 5.35747 |
Annual Sum or Average | 8760.00000 | 23.32353 | 59.12293 | -0.0999 | 7.71159 |
Minimum of Months | 672.00000 | 22.15570 | 57.40454 | -0.5344 | 5.19003 |
Maximum of Months | 744.00000 | 23.98046 | 61.49888 | 0.40833 | 11.05948 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.83205 | 55.41832 | -0.0752 | 5.42859 |
February | 672.00000 | 22.22017 | 58.54007 | 0.04781 | 5.33649 |
March | 744.00000 | 22.60777 | 55.54091 | 0.13323 | 5.72576 |
April | 720.00000 | 23.16592 | 56.27251 | 0.28724 | 6.94934 |
May | 744.00000 | 23.82862 | 55.00058 | -0.4355 | 9.11535 |
June | 720.00000 | 23.93847 | 55.47586 | -0.3821 | 8.08918 |
July | 744.00000 | 23.98673 | 55.16900 | -0.3515 | 7.59167 |
August | 744.00000 | 23.99012 | 55.17850 | -0.3482 | 7.54110 |
September | 720.00000 | 23.92014 | 55.87445 | -0.3865 | 8.21148 |
October | 744.00000 | 23.73165 | 56.00059 | 0.44242 | 9.18279 |
November | 720.00000 | 23.11866 | 59.00184 | 0.29186 | 6.98708 |
December | 744.00000 | 22.23144 | 59.23524 | 0.05495 | 5.35624 |
Annual Sum or Average | 8760.00000 | 23.21896 | 56.37178 | -0.0611 | 7.13622 |
Minimum of Months | 672.00000 | 21.83205 | 55.00058 | -0.4355 | 5.33649 |
Maximum of Months | 744.00000 | 23.99012 | 59.23524 | 0.44242 | 9.18279 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.47311 | 52.04093 | 0.05053 | 5.25900 |
February | 672.00000 | 22.71285 | 55.51778 | 0.13559 | 5.55278 |
March | 744.00000 | 22.96351 | 53.02021 | 0.18566 | 5.93204 |
April | 720.00000 | 23.35557 | 54.29521 | 0.29645 | 6.99361 |
May | 744.00000 | 23.87757 | 53.59917 | -0.4738 | 9.78375 |
June | 720.00000 | 23.97292 | 54.33612 | -0.4240 | 8.77139 |
July | 744.00000 | 23.99482 | 54.28768 | -0.4060 | 8.44289 |
August | 744.00000 | 23.99617 | 54.31913 | -0.4025 | 8.38191 |
September | 720.00000 | 23.96523 | 54.74652 | -0.4247 | 8.80646 |
October | 744.00000 | 23.84287 | 54.43393 | 0.43141 | 8.93874 |
November | 720.00000 | 23.44613 | 56.56392 | 0.33595 | 7.44085 |
December | 744.00000 | 22.81907 | 55.94115 | 0.16612 | 5.74511 |
Annual Sum or Average | 8760.00000 | 23.45517 | 54.41002 | -0.0455 | 7.51461 |
Minimum of Months | 672.00000 | 22.47311 | 52.04093 | -0.4738 | 5.25900 |
Maximum of Months | 744.00000 | 23.99617 | 56.56392 | 0.43141 | 9.78375 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.127299E+12 | 122036.41 | 29-JAN-16:03 | 744.00 | 0.362488E+12 | 0.00 | 0.489787E+12 | 2.90 | 3.85 | 30-JAN-16:03 | 0.00 | 0.00 |
February | 0.146553E+12 | 149798.26 | 07-FEB-16:03 | 672.00 | 0.429677E+12 | 0.00 | 0.576230E+12 | 2.92 | 3.87 | 09-FEB-16:03 | 0.00 | 0.00 |
March | 0.201099E+12 | 155690.55 | 01-MAR-16:03 | 744.00 | 0.585668E+12 | 0.00 | 0.786767E+12 | 2.89 | 3.96 | 02-MAR-22:53 | 0.00 | 0.00 |
April | 0.261597E+12 | 187952.01 | 30-APR-18:03 | 720.00 | 0.781598E+12 | 0.00 | 0.104320E+13 | 2.97 | 3.81 | 30-APR-06:20 | 0.00 | 0.00 |
May | 0.364224E+12 | 256248.65 | 30-MAY-18:03 | 744.00 | 0.105391E+13 | 0.00 | 0.141813E+13 | 2.89 | 3.89 | 01-MAY-08:61 | 0.00 | 0.00 |
June | 0.422874E+12 | 263147.26 | 26-JUN-18:03 | 720.00 | 0.123417E+13 | 0.00 | 0.165704E+13 | 2.93 | 3.74 | 08-JUN-08:62 | 0.00 | 0.00 |
July | 0.504561E+12 | 294578.96 | 17-JUL-18:02 | 744.00 | 0.142690E+13 | 0.00 | 0.193146E+13 | 2.83 | 3.37 | 06-JUL-06:10 | 0.00 | 0.00 |
August | 0.523935E+12 | 316091.45 | 10-AUG-18:03 | 744.00 | 0.148228E+13 | 0.00 | 0.200622E+13 | 2.84 | 3.41 | 27-AUG-06:10 | 0.00 | 0.00 |
September | 0.439785E+12 | 278169.67 | 08-SEP-18:02 | 720.00 | 0.131767E+13 | 0.00 | 0.175746E+13 | 3.01 | 3.81 | 25-SEP-05:07 | 0.00 | 0.00 |
October | 0.363423E+12 | 249799.87 | 06-OCT-18:03 | 744.00 | 0.112354E+13 | 0.00 | 0.148696E+13 | 3.08 | 3.76 | 31-OCT-06:00 | 0.00 | 0.00 |
November | 0.261077E+12 | 201334.66 | 01-NOV-18:03 | 720.00 | 0.809284E+12 | 0.00 | 0.107036E+13 | 3.07 | 3.98 | 29-NOV-22:53 | 0.00 | 0.00 |
December | 0.178502E+12 | 145724.26 | 05-DEC-16:02 | 744.00 | 0.536084E+12 | 0.00 | 0.714586E+12 | 2.97 | 3.97 | 05-DEC-22:52 | 0.00 | 0.00 |
Annual Sum or Average | 0.379493E+13 | 8760.00 | 0.111433E+14 | 0.00 | 0.149382E+14 | 2.94 | 0.00 | 0.00 | ||||
Minimum of Months | 0.127299E+12 | 122036.41 | 672.00 | 0.362488E+12 | 0.00 | 0.489787E+12 | 2.83 | 3.37 | 0.00 | 0.00 | ||
Maximum of Months | 0.523935E+12 | 316091.45 | 744.00 | 0.148228E+13 | 0.00 | 0.200622E+13 | 3.08 | 3.98 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.337718E+09 | 0.00 | 112.17 | 24199.24 | 07-JAN-09:55 | 0.00 | 49.36 | 53.60 | 0.00 | 0.00 | 0.00 | 0.14 | 07-JAN-09:55 |
February | 0.142069E+09 | 0.00 | 38.58 | 20221.80 | 11-FEB-16:06 | 0.00 | 50.13 | 51.78 | 0.00 | 0.00 | 0.00 | 0.12 | 11-FEB-16:06 |
March | 0.132362E+09 | 0.00 | 12.49 | 21591.12 | 18-MAR-08:56 | 0.00 | 48.83 | 49.34 | 0.00 | 0.00 | 0.00 | 0.13 | 18-MAR-08:56 |
April | 67258026.00 | 0.00 | 2.70 | 18528.21 | 10-APR-08:36 | 0.00 | 48.23 | 48.34 | 0.00 | 0.00 | 0.00 | 0.11 | 10-APR-08:36 |
May | 36452212.48 | 0.00 | 1.45 | 17219.57 | 16-MAY-08:07 | 0.00 | 49.86 | 49.92 | 0.00 | 0.00 | 0.00 | 0.10 | 16-MAY-08:07 |
June | 36170917.69 | 0.00 | 1.28 | 13686.72 | 09-JUN-08:07 | 0.00 | 50.86 | 50.91 | 0.00 | 0.00 | 0.00 | 0.08 | 09-JUN-08:07 |
July | 31102387.31 | 0.00 | 0.83 | 13748.69 | 21-JUL-08:07 | 0.00 | 50.29 | 50.32 | 0.00 | 0.00 | 0.00 | 0.08 | 21-JUL-08:07 |
August | 36562162.05 | 0.00 | 0.94 | 14552.16 | 18-AUG-08:07 | 0.00 | 49.54 | 49.58 | 0.00 | 0.00 | 0.00 | 0.08 | 18-AUG-08:07 |
September | 36862436.97 | 0.00 | 1.55 | 12357.82 | 01-SEP-08:07 | 0.00 | 51.11 | 51.17 | 0.00 | 0.00 | 0.00 | 0.07 | 01-SEP-08:07 |
October | 59663720.05 | 0.00 | 2.17 | 20839.97 | 30-OCT-08:26 | 0.00 | 50.58 | 50.67 | 0.00 | 0.00 | 0.00 | 0.12 | 30-OCT-08:26 |
November | 0.106772E+09 | 0.00 | 4.27 | 20721.86 | 13-NOV-09:26 | 0.00 | 49.31 | 49.49 | 0.00 | 0.00 | 0.00 | 0.12 | 13-NOV-09:26 |
December | 0.184839E+09 | 0.00 | 36.04 | 20686.30 | 05-DEC-16:07 | 0.00 | 48.95 | 50.32 | 0.00 | 0.00 | 0.00 | 0.12 | 05-DEC-16:07 |
Annual Sum or Average | 0.120783E+10 | 0.00 | 214.48 | 0.00 | 49.75 | 50.45 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 31102387.31 | 0.00 | 0.83 | 12357.82 | 0.00 | 48.23 | 48.34 | 0.00 | 0.00 | 0.00 | 0.07 | ||
Maximum of Months | 0.337718E+09 | 0.00 | 112.17 | 24199.24 | 0.00 | 51.11 | 53.60 | 0.00 | 0.00 | 0.00 | 0.14 |
Report: DXReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.413355E+11 | 0.00 | 352.75 | 0.382589E+11 | 0.307660E+10 | 0.00 | 1.00 | 01-JAN-07:05 | 0.00 | 01-JAN-00:10 | 56487.74 | 12-JAN-05:10 | 52484.37 | 06-JAN-08:13 | 4472.79 | 28-JAN-16:07 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.364697E+11 | 0.00 | 317.18 | 0.310804E+11 | 0.538930E+10 | 0.00 | 1.00 | 01-FEB-05:10 | 0.00 | 01-FEB-00:03 | 58495.93 | 01-FEB-05:10 | 50023.57 | 01-FEB-09:56 | 8898.82 | 04-FEB-16:07 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 0.375345E+11 | 0.00 | 349.11 | 0.356380E+11 | 0.189643E+10 | 0.00 | 1.00 | 01-MAR-05:10 | 0.00 | 01-MAR-00:03 | 59406.77 | 01-MAR-05:10 | 56307.62 | 08-MAR-09:55 | 3527.61 | 31-MAR-23:10 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 0.327150E+11 | 0.00 | 330.33 | 0.295473E+11 | 0.316776E+10 | 0.00 | 1.00 | 01-APR-05:08 | 0.00 | 01-APR-00:20 | 61908.46 | 01-APR-05:08 | 55813.46 | 05-APR-10:08 | 6500.68 | 03-APR-05:07 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.301532E+11 | 0.00 | 334.27 | 0.271508E+11 | 0.300242E+10 | 0.00 | 1.00 | 01-MAY-05:17 | 0.00 | 01-MAY-00:05 | 64818.48 | 01-MAY-07:05 | 58143.68 | 04-MAY-08:05 | 6940.76 | 01-MAY-17:15 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.266426E+11 | 0.00 | 323.01 | 0.191807E+11 | 0.746187E+10 | 0.00 | 1.00 | 01-JUN-07:15 | 0.00 | 01-JUN-00:05 | 66561.26 | 01-JUN-17:17 | 47764.98 | 01-JUN-07:15 | 18805.71 | 01-JUN-17:17 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.267736E+11 | 0.00 | 332.41 | 0.181615E+11 | 0.861207E+10 | 0.00 | 1.00 | 01-JUL-07:15 | 0.00 | 01-JUL-00:10 | 68027.07 | 31-JUL-07:15 | 46113.02 | 31-JUL-10:20 | 21922.65 | 31-JUL-17:17 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.281763E+11 | 0.00 | 334.31 | 0.181293E+11 | 0.100470E+11 | 0.00 | 1.00 | 01-AUG-07:15 | 0.00 | 01-AUG-00:05 | 69379.32 | 31-AUG-07:15 | 44474.99 | 31-AUG-08:05 | 25316.30 | 24-AUG-10:20 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.302204E+11 | 0.00 | 322.84 | 0.187503E+11 | 0.114701E+11 | 0.00 | 1.00 | 01-SEP-07:15 | 0.00 | 01-SEP-00:05 | 68617.89 | 30-SEP-15:08 | 42453.23 | 30-SEP-10:06 | 26423.44 | 27-SEP-17:08 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.351294E+11 | 0.00 | 340.55 | 0.254193E+11 | 0.971003E+10 | 0.00 | 1.00 | 01-OCT-05:10 | 0.00 | 01-OCT-00:20 | 66346.68 | 31-OCT-10:07 | 47998.79 | 30-OCT-08:33 | 18711.91 | 31-OCT-15:08 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.375103E+11 | 0.00 | 333.43 | 0.301905E+11 | 0.731985E+10 | 0.00 | 1.00 | 01-NOV-05:07 | 0.00 | 01-NOV-00:05 | 63248.79 | 30-NOV-05:10 | 50872.55 | 21-NOV-07:15 | 12704.05 | 29-NOV-05:10 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.409190E+11 | 0.00 | 350.39 | 0.335440E+11 | 0.737501E+10 | 0.00 | 1.00 | 01-DEC-05:10 | 0.00 | 01-DEC-00:05 | 59156.25 | 31-DEC-06:07 | 48609.87 | 18-DEC-09:56 | 10847.63 | 23-DEC-16:07 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.403579E+12 | 0.00 | 4020.60 | 0.325051E+12 | 0.785284E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.266426E+11 | 0.00 | 317.18 | 0.181293E+11 | 0.189643E+10 | 0.00 | 1.00 | 0.00 | 56487.74 | 42453.23 | 3527.61 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.413355E+11 | 0.00 | 352.75 | 0.382589E+11 | 0.114701E+11 | 0.00 | 1.00 | 0.00 | 69379.32 | 58143.68 | 26423.44 | 0.00 | 0.00 |
Report: DXReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.565157E+11 | 0.00 | 350.63 | 0.523171E+11 | 0.419858E+10 | 0.00 | 1.00 | 01-JAN-17:10 | 0.00 | 01-JAN-00:10 | 71490.86 | 12-JAN-18:03 | 66444.14 | 06-JAN-21:20 | 5641.07 | 28-JAN-17:05 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.526808E+11 | 0.00 | 315.60 | 0.448918E+11 | 0.778901E+10 | 0.00 | 1.00 | 01-FEB-17:10 | 0.00 | 01-FEB-00:07 | 74033.71 | 01-FEB-17:10 | 63155.18 | 01-FEB-17:10 | 11233.10 | 05-FEB-17:10 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 0.590145E+11 | 0.00 | 349.24 | 0.560488E+11 | 0.296571E+10 | 0.00 | 1.00 | 01-MAR-17:10 | 0.00 | 01-MAR-00:07 | 75187.05 | 01-MAR-17:10 | 71199.06 | 03-MAR-22:00 | 4271.21 | 02-MAR-18:00 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 0.594145E+11 | 0.00 | 328.43 | 0.536628E+11 | 0.575167E+10 | 0.00 | 1.00 | 01-APR-16:10 | 0.00 | 01-APR-00:10 | 78354.77 | 01-APR-17:01 | 70520.14 | 06-APR-22:00 | 8190.20 | 02-APR-16:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.622830E+11 | 0.00 | 335.29 | 0.561081E+11 | 0.617495E+10 | 0.00 | 1.00 | 01-MAY-16:10 | 0.00 | 01-MAY-00:05 | 82039.55 | 01-MAY-16:10 | 73417.19 | 04-MAY-16:10 | 8762.49 | 01-MAY-16:10 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.576637E+11 | 0.00 | 324.33 | 0.415261E+11 | 0.161376E+11 | 0.00 | 0.94 | 01-JUN-16:10 | 0.00 | 01-JUN-00:05 | 77821.86 | 01-JUN-16:10 | 55845.80 | 01-JUN-16:10 | 21976.06 | 01-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.589753E+11 | 0.00 | 337.38 | 0.400152E+11 | 0.189602E+11 | 0.00 | 0.91 | 31-JUL-16:10 | 0.00 | 01-JUL-00:10 | 75619.99 | 31-JUL-16:10 | 51264.70 | 31-JUL-16:10 | 24355.29 | 31-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.606482E+11 | 0.00 | 336.56 | 0.390462E+11 | 0.216020E+11 | 0.00 | 0.93 | 31-AUG-16:10 | 0.00 | 01-AUG-00:05 | 79350.30 | 31-AUG-16:10 | 50866.85 | 31-AUG-16:10 | 28483.45 | 31-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.618818E+11 | 0.00 | 323.10 | 0.384058E+11 | 0.234759E+11 | 0.00 | 0.98 | 30-SEP-16:10 | 0.00 | 01-SEP-00:05 | 84657.87 | 30-SEP-16:10 | 52234.99 | 30-SEP-16:10 | 32514.31 | 28-SEP-16:10 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.656926E+11 | 0.00 | 338.88 | 0.475213E+11 | 0.181714E+11 | 0.00 | 1.00 | 01-OCT-16:10 | 0.00 | 01-OCT-00:10 | 83974.60 | 31-OCT-21:50 | 60701.65 | 29-OCT-21:00 | 23667.70 | 31-OCT-16:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.608435E+11 | 0.00 | 342.76 | 0.489703E+11 | 0.118732E+11 | 0.00 | 1.00 | 01-NOV-16:10 | 0.00 | 01-NOV-00:05 | 80051.95 | 30-NOV-17:10 | 64343.04 | 30-NOV-22:00 | 16007.59 | 29-NOV-17:10 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.590315E+11 | 0.00 | 349.97 | 0.483931E+11 | 0.106384E+11 | 0.00 | 1.00 | 01-DEC-17:10 | 0.00 | 01-DEC-00:10 | 74869.82 | 31-DEC-17:10 | 61471.05 | 17-DEC-19:00 | 13681.94 | 25-DEC-17:10 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.714645E+12 | 0.00 | 4032.17 | 0.566907E+12 | 0.147739E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.526808E+11 | 0.00 | 315.60 | 0.384058E+11 | 0.296571E+10 | 0.00 | 0.91 | 0.00 | 71490.86 | 50866.85 | 4271.21 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.656926E+11 | 0.00 | 350.63 | 0.561081E+11 | 0.234759E+11 | 0.00 | 1.00 | 0.00 | 84657.87 | 73417.19 | 32514.31 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.251376E+12 | 0.00 | 713.81 | 0.226718E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 284816.54 | 30-JAN-14:00 | 182409.67 | 29-JAN-20:20 | 0.00 | 0.00 | 0.00 |
February | 0.304506E+12 | 0.00 | 666.51 | 0.251057E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 404985.13 | 08-FEB-22:00 | 212967.18 | 07-FEB-21:10 | 0.00 | 0.00 | 0.00 |
March | 0.417461E+12 | 0.00 | 743.92 | 0.352850E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 372329.78 | 31-MAR-10:00 | 256224.96 | 27-MAR-18:20 | 0.00 | 0.00 | 0.00 |
April | 0.571125E+12 | 0.00 | 720.00 | 0.429955E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 432455.52 | 29-APR-20:40 | 270048.37 | 28-APR-20:10 | 0.00 | 0.00 | 0.00 |
May | 0.768577E+12 | 0.00 | 744.00 | 0.552066E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 525775.78 | 30-MAY-18:03 | 321526.05 | 31-MAY-19:10 | 0.00 | 0.00 | 0.00 |
June | 0.923734E+12 | 0.00 | 720.00 | 0.567204E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 572666.30 | 26-JUN-18:03 | 308360.40 | 09-JUN-18:20 | 0.00 | 0.00 | 0.00 |
July | 0.107359E+13 | 0.00 | 744.00 | 0.626528E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 619917.24 | 17-JUL-18:02 | 334133.63 | 21-JUL-20:10 | 0.00 | 0.00 | 0.00 |
August | 0.111880E+13 | 0.00 | 744.00 | 0.640539E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 627514.42 | 30-AUG-20:00 | 335182.89 | 10-AUG-19:20 | 0.00 | 0.00 | 0.00 |
September | 0.998701E+12 | 0.00 | 720.00 | 0.573362E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 628428.91 | 08-SEP-18:02 | 306540.26 | 12-SEP-20:10 | 0.00 | 0.00 | 0.00 |
October | 0.839104E+12 | 0.00 | 744.00 | 0.539529E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 568950.28 | 07-OCT-10:33 | 291854.17 | 05-OCT-20:10 | 0.00 | 0.00 | 0.00 |
November | 0.594053E+12 | 0.00 | 720.00 | 0.427381E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 467118.71 | 02-NOV-21:00 | 271148.54 | 01-NOV-21:00 | 0.00 | 0.00 | 0.00 |
December | 0.389347E+12 | 0.00 | 739.89 | 0.297549E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 406159.18 | 04-DEC-21:10 | 217597.49 | 05-DEC-21:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.825038E+13 | 0.00 | 8720.13 | 0.548474E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.251376E+12 | 0.00 | 666.51 | 0.226718E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 284816.54 | 182409.67 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.111880E+13 | 0.00 | 744.00 | 0.640539E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 628428.91 | 335182.89 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.213661E+11 | 0.00 | 504.17 | 0.172777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33449.09 | 30-JAN-16:02 | 18442.68 | 23-JAN-13:20 | 0.00 | 0.00 | 0.00 |
February | 0.262802E+11 | 0.00 | 499.50 | 0.194353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33877.18 | 03-FEB-20:00 | 20187.63 | 05-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.338636E+11 | 0.00 | 584.67 | 0.271891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36588.83 | 29-MAR-08:30 | 22018.23 | 27-MAR-12:20 | 0.00 | 0.00 | 0.00 |
April | 0.427194E+11 | 0.00 | 570.00 | 0.315056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44892.92 | 30-APR-06:00 | 23281.86 | 28-APR-12:20 | 0.00 | 0.00 | 0.00 |
May | 0.520701E+11 | 0.00 | 589.00 | 0.370545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45639.31 | 29-MAY-13:00 | 23569.67 | 09-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.627577E+11 | 0.00 | 570.00 | 0.374132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44834.69 | 10-JUN-13:00 | 24390.08 | 12-JUN-12:20 | 0.00 | 0.00 | 0.00 |
July | 0.738308E+11 | 0.00 | 589.00 | 0.406451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50369.90 | 20-JUL-12:40 | 25152.62 | 21-JUL-12:20 | 0.00 | 0.00 | 0.00 |
August | 0.760364E+11 | 0.00 | 589.00 | 0.409026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50525.09 | 08-AUG-13:00 | 25501.33 | 16-AUG-12:20 | 0.00 | 0.00 | 0.00 |
September | 0.674343E+11 | 0.00 | 570.00 | 0.371940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48016.18 | 08-SEP-18:02 | 23783.43 | 04-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.564372E+11 | 0.00 | 589.00 | 0.358560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45894.31 | 07-OCT-10:00 | 22431.78 | 09-OCT-12:05 | 0.00 | 0.00 | 0.00 |
November | 0.439885E+11 | 0.00 | 570.00 | 0.307438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40213.62 | 08-NOV-07:40 | 20917.98 | 05-NOV-12:05 | 0.00 | 0.00 | 0.00 |
December | 0.326690E+11 | 0.00 | 576.33 | 0.227521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37227.53 | 06-DEC-09:50 | 19414.12 | 10-DEC-13:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.589453E+12 | 0.00 | 6800.67 | 0.377969E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.213661E+11 | 0.00 | 499.50 | 0.172777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33449.09 | 18442.68 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.760364E+11 | 0.00 | 589.00 | 0.409026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50525.09 | 25501.33 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.384496E+10 | 0.00 | 640.95 | 0.166235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16080.84 | 29-JAN-09:01 | 13388.79 | 22-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.479935E+10 | 0.00 | 605.03 | 0.229528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16017.48 | 07-FEB-09:01 | 13447.80 | 07-FEB-19:02 | 0.00 | 0.00 | 0.00 |
March | 0.701597E+10 | 0.00 | 690.44 | 0.386290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15497.25 | 29-MAR-08:61 | 13663.25 | 25-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.902376E+10 | 0.00 | 683.46 | 0.551629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16198.12 | 18-APR-08:61 | 13688.92 | 03-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.129922E+11 | 0.00 | 722.79 | 0.920308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16410.15 | 01-MAY-08:61 | 13693.14 | 15-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.139118E+11 | 0.00 | 704.52 | 0.101433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14050.51 | 08-JUN-08:62 | 13642.20 | 19-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.156451E+11 | 0.00 | 731.77 | 0.115907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13788.93 | 01-JUL-08:62 | 13641.67 | 28-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.161882E+11 | 0.00 | 732.10 | 0.120471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13903.51 | 27-AUG-08:62 | 13648.21 | 08-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.139505E+11 | 0.00 | 703.00 | 0.101247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14485.94 | 25-SEP-08:62 | 13691.64 | 15-SEP-08:62 | 0.00 | 0.00 | 0.00 |
October | 0.122855E+11 | 0.00 | 721.57 | 0.841023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15795.12 | 31-OCT-08:61 | 13651.22 | 24-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.882137E+10 | 0.00 | 684.66 | 0.522067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16807.36 | 02-NOV-08:62 | 13638.96 | 15-NOV-19:02 | 0.00 | 0.00 | 0.00 |
December | 0.534389E+10 | 0.00 | 668.15 | 0.249714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16002.61 | 06-DEC-09:02 | 13477.47 | 05-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123823E+12 | 0.00 | 8288.44 | 0.825739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.384496E+10 | 0.00 | 605.03 | 0.166235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13788.93 | 13388.79 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.161882E+11 | 0.00 | 732.10 | 0.120471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16807.36 | 13693.14 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.150303E+10 | 0.00 | 368.17 | 0.543469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15684.60 | 29-JAN-09:51 | 12672.19 | 29-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.265593E+10 | 0.00 | 394.68 | 0.115541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16503.60 | 07-FEB-09:41 | 13391.95 | 04-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.533770E+10 | 0.00 | 524.99 | 0.294257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16318.20 | 29-MAR-08:51 | 13414.52 | 25-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.825154E+10 | 0.00 | 608.21 | 0.513699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18142.78 | 30-APR-08:51 | 14099.57 | 27-APR-07:51 | 0.00 | 0.00 | 0.00 |
May | 0.129131E+11 | 0.00 | 712.73 | 0.922380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17674.36 | 02-MAY-08:61 | 13666.16 | 15-MAY-07:41 | 0.00 | 0.00 | 0.00 |
June | 0.140857E+11 | 0.00 | 704.78 | 0.103452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14781.24 | 22-JUN-08:51 | 14106.10 | 22-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.157042E+11 | 0.00 | 732.15 | 0.116573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13523.64 | 14-JUL-08:62 | 13386.38 | 27-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.159275E+11 | 0.00 | 732.05 | 0.118285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13647.14 | 27-AUG-08:62 | 13366.14 | 09-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.131660E+11 | 0.00 | 697.72 | 0.940189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15787.21 | 25-SEP-08:62 | 13465.80 | 15-SEP-08:62 | 0.00 | 0.00 | 0.00 |
October | 0.108407E+11 | 0.00 | 694.66 | 0.706742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18036.40 | 31-OCT-07:52 | 13348.01 | 29-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.686696E+10 | 0.00 | 584.83 | 0.384443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18359.34 | 01-NOV-08:11 | 13346.18 | 15-NOV-19:02 | 0.00 | 0.00 | 0.00 |
December | 0.293565E+10 | 0.00 | 433.52 | 0.125565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15918.61 | 10-DEC-09:51 | 13200.28 | 01-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110188E+12 | 0.00 | 7188.49 | 0.744025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.150303E+10 | 0.00 | 368.17 | 0.543469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13523.64 | 12672.19 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.159275E+11 | 0.00 | 732.15 | 0.118285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18359.34 | 14106.10 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.327117E+11 | 0.00 | 706.47 | 0.148631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32735.41 | 28-JAN-13:30 | 23295.53 | 28-JAN-13:50 | 0.00 | 0.00 | 0.00 |
February | 0.326891E+11 | 0.00 | 653.54 | 0.152348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37853.71 | 05-FEB-13:30 | 30628.10 | 05-FEB-13:40 | 0.00 | 0.00 | 0.00 |
March | 0.390946E+11 | 0.00 | 738.08 | 0.181462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33336.89 | 27-MAR-13:30 | 25073.77 | 27-MAR-13:40 | 0.00 | 0.00 | 0.00 |
April | 0.439312E+11 | 0.00 | 720.00 | 0.212511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31459.68 | 28-APR-16:20 | 21881.51 | 28-APR-17:20 | 0.00 | 0.00 | 0.00 |
May | 0.588423E+11 | 0.00 | 744.00 | 0.329527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36355.14 | 31-MAY-19:10 | 28463.06 | 31-MAY-19:10 | 0.00 | 0.00 | 0.00 |
June | 0.617502E+11 | 0.00 | 720.00 | 0.356216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37240.31 | 09-JUN-17:20 | 29433.83 | 09-JUN-17:20 | 0.00 | 0.00 | 0.00 |
July | 0.727637E+11 | 0.00 | 744.00 | 0.461667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40667.58 | 21-JUL-16:20 | 35372.69 | 21-JUL-20:20 | 0.00 | 0.00 | 0.00 |
August | 0.780584E+11 | 0.00 | 744.00 | 0.523717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41520.29 | 16-AUG-16:20 | 36041.50 | 16-AUG-17:20 | 0.00 | 0.00 | 0.00 |
September | 0.722464E+11 | 0.00 | 720.00 | 0.476574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42443.64 | 26-SEP-13:00 | 39179.57 | 26-SEP-13:20 | 0.00 | 0.00 | 0.00 |
October | 0.707819E+11 | 0.00 | 744.00 | 0.465098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43393.47 | 09-OCT-12:40 | 40649.25 | 09-OCT-13:30 | 0.00 | 0.00 | 0.00 |
November | 0.567382E+11 | 0.00 | 720.00 | 0.338519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41380.66 | 05-NOV-12:40 | 37383.33 | 05-NOV-13:30 | 0.00 | 0.00 | 0.00 |
December | 0.400896E+11 | 0.00 | 732.46 | 0.197230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39495.33 | 03-DEC-12:40 | 31858.09 | 03-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.659697E+12 | 0.00 | 8686.55 | 0.384350E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.326891E+11 | 0.00 | 653.54 | 0.148631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31459.68 | 21881.51 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.780584E+11 | 0.00 | 744.00 | 0.523717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43393.47 | 40649.25 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.234788E+11 | 0.00 | 345.00 | 0.130304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100333.59 | 29-JAN-09:51 | 84522.18 | 28-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.288790E+11 | 0.00 | 355.87 | 0.166938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109061.17 | 08-FEB-22:51 | 87834.05 | 04-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.439297E+11 | 0.00 | 475.42 | 0.277701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103692.08 | 02-MAR-22:51 | 87890.58 | 26-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.592645E+11 | 0.00 | 565.63 | 0.382432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 113527.75 | 30-APR-08:51 | 88257.25 | 30-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.850537E+11 | 0.00 | 686.75 | 0.606451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110914.38 | 01-MAY-08:51 | 88259.03 | 15-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.915218E+11 | 0.00 | 680.14 | 0.662526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93303.13 | 22-JUN-08:51 | 87846.24 | 05-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.100907E+12 | 0.00 | 707.66 | 0.730685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90340.81 | 26-JUL-08:62 | 87570.34 | 05-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.100634E+12 | 0.00 | 706.58 | 0.724906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90611.02 | 08-AUG-08:62 | 87775.39 | 26-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.846855E+11 | 0.00 | 672.49 | 0.597033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103776.18 | 25-SEP-08:62 | 88341.31 | 28-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.724426E+11 | 0.00 | 650.68 | 0.477438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114822.63 | 31-OCT-08:61 | 88099.26 | 03-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.515056E+11 | 0.00 | 535.12 | 0.314800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118182.64 | 01-NOV-08:11 | 87548.45 | 10-NOV-19:02 | 0.00 | 0.00 | 0.00 |
December | 0.320081E+11 | 0.00 | 392.38 | 0.186459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104293.73 | 26-DEC-22:52 | 86278.79 | 05-DEC-19:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.774310E+12 | 0.00 | 6773.74 | 0.525767E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.234788E+11 | 0.00 | 345.00 | 0.130304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90340.81 | 84522.18 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.100907E+12 | 0.00 | 707.66 | 0.730685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118182.64 | 88341.31 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.389126E+10 | 0.00 | 645.58 | 0.177746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13983.04 | 29-JAN-09:01 | 12034.57 | 28-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.477430E+10 | 0.00 | 613.62 | 0.238716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14159.58 | 07-FEB-09:01 | 12207.79 | 07-FEB-19:02 | 0.00 | 0.00 | 0.00 |
March | 0.680122E+10 | 0.00 | 695.63 | 0.388003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13953.59 | 02-MAR-19:02 | 12238.49 | 17-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.917639E+10 | 0.00 | 694.60 | 0.580344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14502.27 | 18-APR-08:61 | 12171.87 | 30-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.132135E+11 | 0.00 | 729.80 | 0.966861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14100.86 | 01-MAY-08:61 | 12306.10 | 23-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.139093E+11 | 0.00 | 707.51 | 0.104583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12450.34 | 08-JUN-08:62 | 12202.74 | 07-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.156977E+11 | 0.00 | 732.67 | 0.120046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12590.73 | 20-JUL-08:62 | 12206.91 | 16-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.162139E+11 | 0.00 | 733.26 | 0.124095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12399.43 | 08-AUG-08:62 | 12245.69 | 22-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.139837E+11 | 0.00 | 706.49 | 0.105046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12520.63 | 25-SEP-08:62 | 12271.90 | 28-SEP-08:62 | 0.00 | 0.00 | 0.00 |
October | 0.123845E+11 | 0.00 | 727.21 | 0.862246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13725.75 | 31-OCT-08:61 | 12298.40 | 01-OCT-08:62 | 0.00 | 0.00 | 0.00 |
November | 0.885986E+10 | 0.00 | 694.31 | 0.539333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14521.46 | 02-NOV-08:62 | 12254.04 | 08-NOV-19:02 | 0.00 | 0.00 | 0.00 |
December | 0.528515E+10 | 0.00 | 676.52 | 0.259328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14156.86 | 06-DEC-09:02 | 12115.08 | 09-DEC-19:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124191E+12 | 0.00 | 8357.20 | 0.855028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.389126E+10 | 0.00 | 613.62 | 0.177746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12399.43 | 12034.57 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.162139E+11 | 0.00 | 733.26 | 0.124095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14521.46 | 12306.10 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.158908E+10 | 0.00 | 370.12 | 0.642092E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14728.46 | 29-JAN-09:51 | 11509.59 | 17-JAN-09:52 | 0.00 | 0.00 | 0.00 |
February | 0.264891E+10 | 0.00 | 404.43 | 0.123190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15080.14 | 07-FEB-09:41 | 12281.33 | 05-FEB-09:51 | 0.00 | 0.00 | 0.00 |
March | 0.512949E+10 | 0.00 | 532.37 | 0.289226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15110.09 | 29-MAR-08:51 | 12012.92 | 21-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.834403E+10 | 0.00 | 614.25 | 0.533707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16852.53 | 30-APR-08:51 | 13351.43 | 24-APR-08:11 | 0.00 | 0.00 | 0.00 |
May | 0.131278E+11 | 0.00 | 717.86 | 0.971979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16529.28 | 01-MAY-08:51 | 12880.89 | 15-MAY-07:41 | 0.00 | 0.00 | 0.00 |
June | 0.140791E+11 | 0.00 | 706.86 | 0.107131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14168.43 | 22-JUN-08:51 | 13478.12 | 22-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.157547E+11 | 0.00 | 733.00 | 0.120985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12379.61 | 20-JUL-08:62 | 12016.99 | 12-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.159514E+11 | 0.00 | 733.05 | 0.121514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12175.71 | 08-AUG-08:62 | 12018.90 | 22-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.131895E+11 | 0.00 | 702.03 | 0.966170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14985.05 | 25-SEP-07:32 | 12085.28 | 22-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.109264E+11 | 0.00 | 701.73 | 0.719922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16673.24 | 31-OCT-07:52 | 12913.81 | 21-OCT-08:41 | 0.00 | 0.00 | 0.00 |
November | 0.680907E+10 | 0.00 | 590.40 | 0.395889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16926.55 | 01-NOV-08:11 | 12434.65 | 18-NOV-09:51 | 0.00 | 0.00 | 0.00 |
December | 0.284284E+10 | 0.00 | 440.44 | 0.127406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14694.41 | 10-DEC-09:51 | 11928.95 | 10-DEC-19:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110392E+12 | 0.00 | 7246.54 | 0.768800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.158908E+10 | 0.00 | 370.12 | 0.642092E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12175.71 | 11509.59 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.159514E+11 | 0.00 | 733.05 | 0.121514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16926.55 | 13478.12 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.875148E+09 | 0.00 | 576.09 | 0.375535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4479.40 | 29-JAN-09:01 | 3607.26 | 29-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.113675E+10 | 0.00 | 581.77 | 0.536063E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4538.92 | 07-FEB-09:01 | 3632.92 | 07-FEB-19:02 | 0.00 | 0.00 | 0.00 |
March | 0.173889E+10 | 0.00 | 684.61 | 0.943207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4401.53 | 29-MAR-08:61 | 3664.17 | 25-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.231133E+10 | 0.00 | 682.22 | 0.139065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4588.41 | 18-APR-08:61 | 3700.53 | 03-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.340967E+10 | 0.00 | 723.26 | 0.239311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4714.15 | 01-MAY-08:61 | 3690.97 | 22-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.367529E+10 | 0.00 | 704.04 | 0.265900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3949.48 | 08-JUN-08:62 | 3675.77 | 02-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.418723E+10 | 0.00 | 732.01 | 0.308303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3838.91 | 01-JUL-08:62 | 3686.44 | 13-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.432156E+10 | 0.00 | 731.95 | 0.320276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3875.25 | 27-AUG-08:62 | 3687.60 | 11-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.365027E+10 | 0.00 | 702.50 | 0.260889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4123.94 | 25-SEP-08:62 | 3692.63 | 04-SEP-08:62 | 0.00 | 0.00 | 0.00 |
October | 0.313702E+10 | 0.00 | 719.95 | 0.210616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4572.33 | 31-OCT-08:61 | 3697.39 | 31-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.216916E+10 | 0.00 | 682.34 | 0.123071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4841.95 | 02-NOV-08:62 | 3679.55 | 08-NOV-19:02 | 0.00 | 0.00 | 0.00 |
December | 0.124040E+10 | 0.00 | 645.13 | 0.561886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4518.27 | 06-DEC-09:02 | 3690.94 | 11-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318527E+11 | 0.00 | 8165.87 | 0.210910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.875148E+09 | 0.00 | 576.09 | 0.375535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3838.91 | 3607.26 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.432156E+10 | 0.00 | 732.01 | 0.320276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4841.95 | 3700.53 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.304161E+09 | 0.00 | 299.29 | 0.109792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4353.31 | 29-JAN-09:51 | 3471.43 | 29-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.620931E+09 | 0.00 | 379.42 | 0.267181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4631.59 | 08-FEB-22:51 | 3589.19 | 23-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.134597E+10 | 0.00 | 528.44 | 0.727062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4527.70 | 29-MAR-08:51 | 3610.43 | 31-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.213819E+10 | 0.00 | 609.43 | 0.131249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5044.27 | 30-APR-08:51 | 3877.55 | 27-APR-07:51 | 0.00 | 0.00 | 0.00 |
May | 0.339416E+10 | 0.00 | 713.09 | 0.240184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4901.43 | 02-MAY-08:61 | 3637.17 | 20-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.372061E+10 | 0.00 | 703.92 | 0.270232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4110.86 | 22-JUN-08:51 | 3753.55 | 22-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.420218E+10 | 0.00 | 732.24 | 0.310351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3745.94 | 01-JUL-08:62 | 3615.59 | 24-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.425415E+10 | 0.00 | 731.87 | 0.315706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3805.62 | 27-AUG-08:62 | 3609.66 | 11-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.344940E+10 | 0.00 | 697.62 | 0.243394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4448.82 | 25-SEP-08:62 | 3630.30 | 04-SEP-08:62 | 0.00 | 0.00 | 0.00 |
October | 0.276888E+10 | 0.00 | 694.20 | 0.175687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5023.22 | 28-OCT-08:11 | 3609.75 | 20-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.169172E+10 | 0.00 | 585.00 | 0.904531E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5217.27 | 01-NOV-08:11 | 3608.90 | 08-NOV-19:02 | 0.00 | 0.00 | 0.00 |
December | 0.661206E+09 | 0.00 | 415.95 | 0.272581E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4437.12 | 10-DEC-09:51 | 3601.94 | 01-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.285515E+11 | 0.00 | 7090.45 | 0.191492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.304161E+09 | 0.00 | 299.29 | 0.109792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3745.94 | 3471.43 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.425415E+10 | 0.00 | 732.24 | 0.315706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5217.27 | 3877.55 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.845277E+10 | 0.00 | 685.13 | 0.461134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20867.98 | 29-JAN-09:01 | 17195.73 | 23-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.879182E+10 | 0.00 | 619.73 | 0.491594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21325.98 | 07-FEB-09:01 | 17343.45 | 05-FEB-19:02 | 0.00 | 0.00 | 0.00 |
March | 0.106718E+11 | 0.00 | 692.08 | 0.629098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21186.72 | 02-MAR-19:02 | 17415.87 | 22-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.123164E+11 | 0.00 | 681.26 | 0.755594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22355.25 | 18-APR-08:61 | 17738.19 | 30-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.165984E+11 | 0.00 | 719.25 | 0.113733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23229.17 | 01-MAY-08:61 | 17638.00 | 16-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.174717E+11 | 0.00 | 699.33 | 0.122793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18204.21 | 07-JUN-08:62 | 17501.73 | 14-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.203284E+11 | 0.00 | 727.59 | 0.150190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18073.95 | 14-JUL-08:62 | 17609.23 | 28-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.214442E+11 | 0.00 | 728.96 | 0.161056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18114.05 | 18-AUG-08:62 | 17592.08 | 08-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.194737E+11 | 0.00 | 701.48 | 0.141936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19140.26 | 25-SEP-08:62 | 17703.16 | 18-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.186584E+11 | 0.00 | 723.64 | 0.132461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20984.34 | 31-OCT-08:61 | 17650.00 | 06-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.148023E+11 | 0.00 | 695.66 | 0.972081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23036.19 | 02-NOV-08:62 | 17509.18 | 03-NOV-18:02 | 0.00 | 0.00 | 0.00 |
December | 0.104731E+11 | 0.00 | 690.98 | 0.605061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21398.13 | 06-DEC-09:02 | 17384.72 | 10-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179483E+12 | 0.00 | 8365.09 | 0.121363E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.845277E+10 | 0.00 | 619.73 | 0.461134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18073.95 | 17195.73 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.214442E+11 | 0.00 | 728.96 | 0.161056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23229.17 | 17738.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 396.09 | 187.06 | 209.03 | 642.12 | 197.83 | 0.00 | 0.00 | 0.00 |
February | 370.28 | 151.44 | 218.83 | 632.99 | 163.66 | 0.00 | 0.00 | 0.00 |
March | 301.55 | 79.58 | 221.97 | 575.35 | 122.22 | 0.00 | 0.00 | 0.00 |
April | 240.82 | 26.60 | 214.22 | 546.25 | 68.64 | 0.00 | 0.00 | 0.00 |
May | 203.74 | 3.84 | 199.90 | 613.28 | 11.85 | 0.00 | 0.00 | 0.00 |
June | 191.09 | 0.24 | 190.85 | 645.56 | 1.17 | 0.00 | 0.00 | 0.00 |
July | 190.82 | 1.26 | 189.56 | 763.19 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 220.75 | 14.68 | 206.06 | 840.95 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 292.60 | 67.28 | 225.32 | 842.67 | 3.71 | 0.00 | 0.00 | 0.00 |
October | 383.26 | 152.76 | 230.50 | 868.72 | 22.45 | 0.00 | 0.00 | 0.00 |
November | 424.17 | 205.50 | 218.67 | 812.83 | 84.40 | 0.00 | 0.00 | 0.00 |
December | 392.53 | 194.25 | 198.28 | 668.70 | 160.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 300.22 | 90.04 | 210.17 | 704.89 | 69.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 190.82 | 0.24 | 189.56 | 546.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 424.17 | 205.50 | 230.50 | 868.72 | 197.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1115.37 | 526.74 | 588.62 | 1755.53 | 659.44 | 0.00 | 0.00 | 0.00 |
February | 1042.67 | 426.45 | 616.22 | 1737.58 | 552.47 | 0.00 | 0.00 | 0.00 |
March | 849.15 | 224.09 | 625.05 | 1584.85 | 414.81 | 0.00 | 0.00 | 0.00 |
April | 678.13 | 74.90 | 603.23 | 1513.09 | 238.83 | 0.00 | 0.00 | 0.00 |
May | 573.73 | 10.83 | 562.91 | 1726.03 | 43.23 | 0.00 | 0.00 | 0.00 |
June | 538.09 | 0.67 | 537.42 | 1825.82 | 4.80 | 0.00 | 0.00 | 0.00 |
July | 537.34 | 3.56 | 533.78 | 2159.72 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 621.61 | 41.35 | 580.26 | 2376.65 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 823.96 | 189.47 | 634.49 | 2368.09 | 13.72 | 0.00 | 0.00 | 0.00 |
October | 1079.23 | 430.15 | 649.08 | 2431.25 | 77.53 | 0.00 | 0.00 | 0.00 |
November | 1194.44 | 578.68 | 615.75 | 2258.00 | 278.60 | 0.00 | 0.00 | 0.00 |
December | 1105.33 | 546.99 | 558.34 | 1838.18 | 537.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 845.39 | 253.55 | 591.84 | 1966.14 | 233.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 537.34 | 0.67 | 533.78 | 1513.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1194.44 | 578.68 | 649.08 | 2431.25 | 659.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1448.92 | 684.27 | 764.66 | 2327.16 | 887.65 | 0.00 | 0.00 | 0.00 |
February | 1354.49 | 553.99 | 800.51 | 2308.39 | 740.80 | 0.00 | 0.00 | 0.00 |
March | 1103.09 | 291.11 | 811.98 | 2107.74 | 555.29 | 0.00 | 0.00 | 0.00 |
April | 880.93 | 97.30 | 783.63 | 2019.32 | 315.21 | 0.00 | 0.00 | 0.00 |
May | 745.31 | 14.06 | 731.25 | 2321.23 | 55.15 | 0.00 | 0.00 | 0.00 |
June | 699.01 | 0.86 | 698.14 | 2457.03 | 5.72 | 0.00 | 0.00 | 0.00 |
July | 698.03 | 4.62 | 693.42 | 2913.52 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 807.50 | 53.71 | 753.79 | 3204.73 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1070.37 | 246.13 | 824.24 | 3186.48 | 16.46 | 0.00 | 0.00 | 0.00 |
October | 1401.98 | 558.79 | 843.19 | 3260.34 | 94.97 | 0.00 | 0.00 | 0.00 |
November | 1551.64 | 751.74 | 799.90 | 3018.96 | 357.56 | 0.00 | 0.00 | 0.00 |
December | 1435.88 | 710.57 | 725.31 | 2440.93 | 716.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1098.21 | 329.38 | 768.83 | 2632.69 | 310.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 698.03 | 0.86 | 693.42 | 2019.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1551.64 | 751.74 | 843.19 | 3260.34 | 887.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.31 | 36.98 | 41.33 | 129.08 | 35.01 | 0.00 | 0.00 | 0.00 |
February | 73.21 | 29.94 | 43.27 | 128.09 | 27.21 | 0.00 | 0.00 | 0.00 |
March | 59.62 | 15.73 | 43.89 | 118.34 | 18.60 | 0.00 | 0.00 | 0.00 |
April | 47.61 | 5.26 | 42.36 | 116.65 | 8.01 | 0.00 | 0.00 | 0.00 |
May | 40.28 | 0.76 | 39.52 | 141.81 | 0.56 | 0.00 | 0.00 | 0.00 |
June | 37.78 | 0.05 | 37.73 | 153.28 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 37.73 | 0.25 | 37.48 | 178.89 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 43.65 | 2.90 | 40.74 | 194.69 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 57.85 | 13.30 | 44.55 | 191.75 | 0.12 | 0.00 | 0.00 | 0.00 |
October | 75.78 | 30.20 | 45.57 | 191.18 | 1.01 | 0.00 | 0.00 | 0.00 |
November | 83.87 | 40.63 | 43.23 | 171.35 | 9.58 | 0.00 | 0.00 | 0.00 |
December | 77.61 | 38.41 | 39.20 | 136.06 | 25.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 59.36 | 17.80 | 41.56 | 154.44 | 10.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.73 | 0.05 | 37.48 | 116.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.87 | 40.63 | 45.57 | 194.69 | 35.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.12 | 23.05 | 57.08 | 122.38 | 70.37 | 0.00 | 0.00 | 0.00 |
February | 91.44 | 26.16 | 65.28 | 153.26 | 53.11 | 0.00 | 0.00 | 0.00 |
March | 108.02 | 31.98 | 76.04 | 205.57 | 35.08 | 0.00 | 0.00 | 0.00 |
April | 118.11 | 33.18 | 84.93 | 263.91 | 14.74 | 0.00 | 0.00 | 0.00 |
May | 128.49 | 38.46 | 90.04 | 363.46 | 0.99 | 0.00 | 0.00 | 0.00 |
June | 132.74 | 41.82 | 90.92 | 403.40 | 0.02 | 0.00 | 0.00 | 0.00 |
July | 121.75 | 34.77 | 86.98 | 431.11 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 124.91 | 37.91 | 87.00 | 439.84 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 119.03 | 37.44 | 81.58 | 367.53 | 0.20 | 0.00 | 0.00 | 0.00 |
October | 105.87 | 34.32 | 71.55 | 282.07 | 1.90 | 0.00 | 0.00 | 0.00 |
November | 91.03 | 29.87 | 61.16 | 196.83 | 18.77 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 22.85 | 53.05 | 129.55 | 51.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.18 | 32.67 | 75.51 | 280.64 | 20.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 22.85 | 53.05 | 122.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.74 | 41.82 | 90.92 | 439.84 | 70.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.12 | 0.00 | 24.12 | 32.01 | 39.51 | 0.00 | 0.00 | 0.00 |
February | 27.65 | 0.00 | 27.65 | 43.01 | 30.70 | 0.00 | 0.00 | 0.00 |
March | 31.76 | 0.00 | 31.76 | 61.70 | 20.61 | 0.00 | 0.00 | 0.00 |
April | 35.90 | 0.14 | 35.76 | 90.33 | 8.07 | 0.00 | 0.00 | 0.00 |
May | 40.36 | 1.24 | 39.12 | 142.07 | 0.51 | 0.00 | 0.00 | 0.00 |
June | 43.14 | 2.42 | 40.73 | 165.36 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 39.64 | 1.19 | 38.45 | 183.68 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 36.93 | 0.37 | 36.56 | 180.03 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33.56 | 0.01 | 33.55 | 141.25 | 0.14 | 0.00 | 0.00 | 0.00 |
October | 29.74 | 0.00 | 29.74 | 101.86 | 1.09 | 0.00 | 0.00 | 0.00 |
November | 25.53 | 0.00 | 25.53 | 62.58 | 10.19 | 0.00 | 0.00 | 0.00 |
December | 22.51 | 0.00 | 22.51 | 36.18 | 29.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.59 | 0.45 | 32.14 | 103.71 | 11.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.51 | 0.00 | 22.51 | 32.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.14 | 2.42 | 40.73 | 183.68 | 39.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.12 | 23.05 | 57.08 | 123.95 | 72.93 | 0.00 | 0.00 | 0.00 |
February | 91.44 | 26.16 | 65.28 | 153.35 | 56.50 | 0.00 | 0.00 | 0.00 |
March | 108.02 | 31.98 | 76.04 | 205.28 | 38.18 | 0.00 | 0.00 | 0.00 |
April | 118.11 | 33.18 | 84.93 | 263.00 | 15.31 | 0.00 | 0.00 | 0.00 |
May | 128.49 | 38.46 | 90.04 | 363.10 | 1.06 | 0.00 | 0.00 | 0.00 |
June | 132.74 | 41.82 | 90.92 | 402.92 | 0.02 | 0.00 | 0.00 | 0.00 |
July | 121.75 | 34.77 | 86.98 | 430.97 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 124.91 | 37.91 | 87.00 | 440.37 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 119.03 | 37.44 | 81.58 | 369.14 | 0.24 | 0.00 | 0.00 | 0.00 |
October | 105.87 | 34.32 | 71.55 | 284.50 | 1.96 | 0.00 | 0.00 | 0.00 |
November | 91.03 | 29.87 | 61.16 | 198.26 | 18.90 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 22.85 | 53.05 | 130.75 | 54.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.18 | 32.67 | 75.51 | 281.21 | 21.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 22.85 | 53.05 | 123.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.74 | 41.82 | 90.92 | 440.37 | 72.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.64 | 29.58 | 33.06 | 87.35 | 53.45 | 0.00 | 0.00 | 0.00 |
February | 58.56 | 23.95 | 34.61 | 87.00 | 46.68 | 0.00 | 0.00 | 0.00 |
March | 47.69 | 12.59 | 35.10 | 78.41 | 36.73 | 0.00 | 0.00 | 0.00 |
April | 38.08 | 4.21 | 33.88 | 74.40 | 23.66 | 0.00 | 0.00 | 0.00 |
May | 32.22 | 0.61 | 31.61 | 85.00 | 6.59 | 0.00 | 0.00 | 0.00 |
June | 30.22 | 0.04 | 30.18 | 89.77 | 1.93 | 0.00 | 0.00 | 0.00 |
July | 30.18 | 0.20 | 29.98 | 108.38 | 0.09 | 0.00 | 0.00 | 0.00 |
August | 34.91 | 2.32 | 32.59 | 120.85 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 46.27 | 10.64 | 35.63 | 120.57 | 2.77 | 0.00 | 0.00 | 0.00 |
October | 60.61 | 24.16 | 36.45 | 126.42 | 10.44 | 0.00 | 0.00 | 0.00 |
November | 67.08 | 32.50 | 34.58 | 117.87 | 26.05 | 0.00 | 0.00 | 0.00 |
December | 62.08 | 30.72 | 31.36 | 93.19 | 45.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.48 | 14.24 | 33.24 | 99.18 | 20.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.18 | 0.04 | 29.98 | 74.40 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.08 | 32.50 | 36.45 | 126.42 | 53.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.30 | 0.00 | 19.30 | 26.48 | 31.65 | 0.00 | 0.00 | 0.00 |
February | 22.12 | 0.00 | 22.12 | 36.09 | 23.89 | 0.00 | 0.00 | 0.00 |
March | 25.41 | 0.00 | 25.41 | 52.19 | 15.33 | 0.00 | 0.00 | 0.00 |
April | 28.72 | 0.11 | 28.61 | 76.80 | 5.42 | 0.00 | 0.00 | 0.00 |
May | 32.29 | 0.99 | 31.30 | 120.89 | 0.23 | 0.00 | 0.00 | 0.00 |
June | 34.52 | 1.94 | 32.58 | 140.30 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31.72 | 0.95 | 30.77 | 155.33 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29.55 | 0.30 | 29.25 | 152.65 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26.85 | 0.01 | 26.85 | 120.75 | 0.06 | 0.00 | 0.00 | 0.00 |
October | 23.80 | 0.00 | 23.80 | 87.85 | 0.54 | 0.00 | 0.00 | 0.00 |
November | 20.43 | 0.00 | 20.43 | 53.79 | 6.98 | 0.00 | 0.00 | 0.00 |
December | 18.01 | 0.00 | 18.01 | 30.32 | 22.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.08 | 0.36 | 25.72 | 88.10 | 8.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.01 | 0.00 | 18.01 | 26.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.52 | 1.94 | 32.58 | 155.33 | 31.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.32 | 24.53 | 56.79 | 120.50 | 65.29 | 0.00 | 0.00 | 0.00 |
February | 88.80 | 24.07 | 64.73 | 146.28 | 49.60 | 0.00 | 0.00 | 0.00 |
March | 98.17 | 24.22 | 73.96 | 187.14 | 32.52 | 0.00 | 0.00 | 0.00 |
April | 119.51 | 34.78 | 84.73 | 268.71 | 13.82 | 0.00 | 0.00 | 0.00 |
May | 133.35 | 42.46 | 90.88 | 374.13 | 0.90 | 0.00 | 0.00 | 0.00 |
June | 130.62 | 39.93 | 90.69 | 401.31 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 121.93 | 35.13 | 86.80 | 433.80 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 124.89 | 38.34 | 86.55 | 441.14 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 117.34 | 36.25 | 81.10 | 365.96 | 0.22 | 0.00 | 0.00 | 0.00 |
October | 106.45 | 34.73 | 71.73 | 284.98 | 1.86 | 0.00 | 0.00 | 0.00 |
November | 89.18 | 28.16 | 61.01 | 193.88 | 17.69 | 0.00 | 0.00 | 0.00 |
December | 72.30 | 19.88 | 52.42 | 120.62 | 48.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.06 | 31.91 | 75.15 | 278.97 | 19.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.30 | 19.88 | 52.42 | 120.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.35 | 42.46 | 90.88 | 441.14 | 65.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.31 | 36.98 | 41.33 | 128.52 | 34.80 | 0.00 | 0.00 | 0.00 |
February | 73.21 | 29.94 | 43.27 | 127.69 | 26.97 | 0.00 | 0.00 | 0.00 |
March | 59.62 | 15.73 | 43.89 | 118.21 | 18.31 | 0.00 | 0.00 | 0.00 |
April | 47.61 | 5.26 | 42.36 | 116.25 | 7.90 | 0.00 | 0.00 | 0.00 |
May | 40.28 | 0.76 | 39.52 | 141.47 | 0.55 | 0.00 | 0.00 | 0.00 |
June | 37.78 | 0.05 | 37.73 | 153.22 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 37.73 | 0.25 | 37.48 | 178.78 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 43.65 | 2.90 | 40.74 | 194.59 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 57.85 | 13.30 | 44.55 | 191.68 | 0.11 | 0.00 | 0.00 | 0.00 |
October | 75.78 | 30.20 | 45.57 | 191.00 | 0.99 | 0.00 | 0.00 | 0.00 |
November | 83.87 | 40.63 | 43.23 | 171.12 | 9.44 | 0.00 | 0.00 | 0.00 |
December | 77.61 | 38.41 | 39.20 | 135.74 | 25.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 59.36 | 17.80 | 41.56 | 154.19 | 10.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.73 | 0.05 | 37.48 | 116.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.87 | 40.63 | 45.57 | 194.59 | 34.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.12 | 0.00 | 24.12 | 31.29 | 39.06 | 0.00 | 0.00 | 0.00 |
February | 27.65 | 0.00 | 27.65 | 42.39 | 30.21 | 0.00 | 0.00 | 0.00 |
March | 31.76 | 0.00 | 31.76 | 61.46 | 20.12 | 0.00 | 0.00 | 0.00 |
April | 35.90 | 0.14 | 35.76 | 89.68 | 7.97 | 0.00 | 0.00 | 0.00 |
May | 40.36 | 1.24 | 39.12 | 141.69 | 0.49 | 0.00 | 0.00 | 0.00 |
June | 43.14 | 2.42 | 40.73 | 165.30 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 39.64 | 1.19 | 38.45 | 183.58 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 36.93 | 0.37 | 36.56 | 179.94 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33.56 | 0.01 | 33.55 | 141.17 | 0.13 | 0.00 | 0.00 | 0.00 |
October | 29.74 | 0.00 | 29.74 | 101.58 | 1.07 | 0.00 | 0.00 | 0.00 |
November | 25.53 | 0.00 | 25.53 | 61.92 | 10.09 | 0.00 | 0.00 | 0.00 |
December | 22.51 | 0.00 | 22.51 | 35.62 | 28.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.59 | 0.45 | 32.14 | 103.34 | 11.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.51 | 0.00 | 22.51 | 31.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.14 | 2.42 | 40.73 | 183.58 | 39.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 81.32 | 24.53 | 56.79 | 122.01 | 67.58 | 0.00 | 0.00 | 0.00 |
February | 88.80 | 24.07 | 64.73 | 146.17 | 52.70 | 0.00 | 0.00 | 0.00 |
March | 98.17 | 24.22 | 73.96 | 186.41 | 35.08 | 0.00 | 0.00 | 0.00 |
April | 119.51 | 34.78 | 84.73 | 266.85 | 14.09 | 0.00 | 0.00 | 0.00 |
May | 133.35 | 42.46 | 90.88 | 373.59 | 0.91 | 0.00 | 0.00 | 0.00 |
June | 130.62 | 39.93 | 90.69 | 400.82 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 121.93 | 35.13 | 86.80 | 433.66 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 124.89 | 38.34 | 86.55 | 441.67 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 117.34 | 36.25 | 81.10 | 367.52 | 0.23 | 0.00 | 0.00 | 0.00 |
October | 106.45 | 34.73 | 71.73 | 287.09 | 1.84 | 0.00 | 0.00 | 0.00 |
November | 89.18 | 28.16 | 61.01 | 193.95 | 17.58 | 0.00 | 0.00 | 0.00 |
December | 72.30 | 19.88 | 52.42 | 121.26 | 50.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.06 | 31.91 | 75.15 | 279.19 | 19.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.30 | 19.88 | 52.42 | 121.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.35 | 42.46 | 90.88 | 441.67 | 67.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.54 | 0.00 | 30.54 | 41.92 | 52.89 | 0.00 | 0.00 | 0.00 |
February | 35.01 | 0.00 | 35.01 | 56.08 | 42.19 | 0.00 | 0.00 | 0.00 |
March | 40.22 | 0.00 | 40.22 | 79.47 | 29.53 | 0.00 | 0.00 | 0.00 |
April | 45.47 | 0.18 | 45.28 | 113.42 | 14.87 | 0.00 | 0.00 | 0.00 |
May | 51.11 | 1.57 | 49.54 | 170.01 | 2.03 | 0.00 | 0.00 | 0.00 |
June | 54.64 | 3.06 | 51.58 | 197.02 | 0.11 | 0.00 | 0.00 | 0.00 |
July | 50.21 | 1.51 | 48.70 | 220.10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 46.77 | 0.47 | 46.30 | 215.45 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 42.51 | 0.01 | 42.49 | 165.54 | 0.60 | 0.00 | 0.00 | 0.00 |
October | 37.67 | 0.00 | 37.67 | 117.76 | 4.08 | 0.00 | 0.00 | 0.00 |
November | 32.34 | 0.00 | 32.34 | 75.65 | 19.36 | 0.00 | 0.00 | 0.00 |
December | 28.51 | 0.00 | 28.51 | 46.12 | 41.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.27 | 0.57 | 40.70 | 125.30 | 17.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.51 | 0.00 | 28.51 | 41.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.64 | 3.06 | 51.58 | 220.10 | 52.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.26 | 0.00 | 11.26 | 15.45 | 19.50 | 0.00 | 0.00 | 0.00 |
February | 12.91 | 0.00 | 12.91 | 20.67 | 15.55 | 0.00 | 0.00 | 0.00 |
March | 14.83 | 0.00 | 14.83 | 29.30 | 10.89 | 0.00 | 0.00 | 0.00 |
April | 16.76 | 0.07 | 16.69 | 41.81 | 5.48 | 0.00 | 0.00 | 0.00 |
May | 18.84 | 0.58 | 18.26 | 62.67 | 0.75 | 0.00 | 0.00 | 0.00 |
June | 20.14 | 1.13 | 19.01 | 72.63 | 0.04 | 0.00 | 0.00 | 0.00 |
July | 18.51 | 0.56 | 17.95 | 81.14 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17.24 | 0.17 | 17.07 | 79.42 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15.67 | 0.00 | 15.67 | 61.02 | 0.22 | 0.00 | 0.00 | 0.00 |
October | 13.89 | 0.00 | 13.89 | 43.41 | 1.50 | 0.00 | 0.00 | 0.00 |
November | 11.92 | 0.00 | 11.92 | 27.89 | 7.14 | 0.00 | 0.00 | 0.00 |
December | 10.51 | 0.00 | 10.51 | 17.00 | 15.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.22 | 0.21 | 15.01 | 46.19 | 6.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.51 | 0.00 | 10.51 | 15.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.14 | 1.13 | 19.01 | 81.14 | 19.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.54 | 17.26 | 19.28 | 61.08 | 17.96 | 0.00 | 0.00 | 0.00 |
February | 34.16 | 13.97 | 20.19 | 60.32 | 14.76 | 0.00 | 0.00 | 0.00 |
March | 27.82 | 7.34 | 20.48 | 55.56 | 10.74 | 0.00 | 0.00 | 0.00 |
April | 22.22 | 2.45 | 19.76 | 53.81 | 5.61 | 0.00 | 0.00 | 0.00 |
May | 18.80 | 0.35 | 18.44 | 62.48 | 0.83 | 0.00 | 0.00 | 0.00 |
June | 17.63 | 0.02 | 17.61 | 66.87 | 0.04 | 0.00 | 0.00 | 0.00 |
July | 17.60 | 0.12 | 17.49 | 78.83 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20.36 | 1.35 | 19.01 | 86.31 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26.99 | 6.21 | 20.79 | 84.84 | 0.21 | 0.00 | 0.00 | 0.00 |
October | 35.36 | 14.09 | 21.26 | 85.48 | 1.44 | 0.00 | 0.00 | 0.00 |
November | 39.13 | 18.96 | 20.17 | 78.69 | 6.70 | 0.00 | 0.00 | 0.00 |
December | 36.21 | 17.92 | 18.29 | 63.73 | 14.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 27.70 | 8.31 | 19.39 | 69.90 | 6.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.60 | 0.02 | 17.49 | 53.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 39.13 | 18.96 | 21.26 | 86.31 | 17.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.18 | 46.84 | 52.34 | 165.77 | 48.73 | 0.00 | 0.00 | 0.00 |
February | 92.72 | 37.92 | 54.80 | 163.71 | 40.05 | 0.00 | 0.00 | 0.00 |
March | 75.51 | 19.93 | 55.58 | 150.79 | 29.14 | 0.00 | 0.00 | 0.00 |
April | 60.30 | 6.66 | 53.64 | 146.05 | 15.24 | 0.00 | 0.00 | 0.00 |
May | 51.02 | 0.96 | 50.05 | 169.58 | 2.26 | 0.00 | 0.00 | 0.00 |
June | 47.85 | 0.06 | 47.79 | 181.49 | 0.12 | 0.00 | 0.00 | 0.00 |
July | 47.78 | 0.32 | 47.47 | 213.97 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 55.27 | 3.68 | 51.60 | 234.27 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 73.27 | 16.85 | 56.42 | 230.27 | 0.58 | 0.00 | 0.00 | 0.00 |
October | 95.97 | 38.25 | 57.72 | 232.01 | 3.91 | 0.00 | 0.00 | 0.00 |
November | 106.21 | 51.46 | 54.75 | 213.57 | 18.19 | 0.00 | 0.00 | 0.00 |
December | 98.29 | 48.64 | 49.65 | 172.98 | 38.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.17 | 22.55 | 52.63 | 189.72 | 16.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.78 | 0.06 | 47.47 | 146.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.21 | 51.46 | 57.72 | 234.27 | 48.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.31 | 36.98 | 41.33 | 127.93 | 34.25 | 0.00 | 0.00 | 0.00 |
February | 73.21 | 29.94 | 43.27 | 126.85 | 26.49 | 0.00 | 0.00 | 0.00 |
March | 59.62 | 15.73 | 43.89 | 117.35 | 17.92 | 0.00 | 0.00 | 0.00 |
April | 47.61 | 5.26 | 42.36 | 116.08 | 7.47 | 0.00 | 0.00 | 0.00 |
May | 40.28 | 0.76 | 39.52 | 142.16 | 0.47 | 0.00 | 0.00 | 0.00 |
June | 37.78 | 0.05 | 37.73 | 154.17 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 37.73 | 0.25 | 37.48 | 179.47 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 43.65 | 2.90 | 40.74 | 195.20 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 57.85 | 13.30 | 44.55 | 192.01 | 0.10 | 0.00 | 0.00 | 0.00 |
October | 75.78 | 30.20 | 45.57 | 191.08 | 0.85 | 0.00 | 0.00 | 0.00 |
November | 83.87 | 40.63 | 43.23 | 170.53 | 8.89 | 0.00 | 0.00 | 0.00 |
December | 77.61 | 38.41 | 39.20 | 135.04 | 25.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 59.36 | 17.80 | 41.56 | 154.17 | 10.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.73 | 0.05 | 37.48 | 116.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.87 | 40.63 | 45.57 | 195.20 | 34.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.12 | 23.05 | 57.08 | 120.74 | 68.65 | 0.00 | 0.00 | 0.00 |
February | 91.44 | 26.16 | 65.28 | 151.46 | 51.58 | 0.00 | 0.00 | 0.00 |
March | 108.02 | 31.98 | 76.04 | 203.57 | 33.72 | 0.00 | 0.00 | 0.00 |
April | 118.11 | 33.18 | 84.93 | 262.33 | 13.75 | 0.00 | 0.00 | 0.00 |
May | 128.49 | 38.46 | 90.04 | 363.14 | 0.82 | 0.00 | 0.00 | 0.00 |
June | 132.74 | 41.82 | 90.92 | 403.83 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 121.75 | 34.77 | 86.98 | 431.27 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 124.91 | 37.91 | 87.00 | 439.91 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 119.03 | 37.44 | 81.58 | 367.98 | 0.17 | 0.00 | 0.00 | 0.00 |
October | 105.87 | 34.32 | 71.55 | 282.53 | 1.59 | 0.00 | 0.00 | 0.00 |
November | 91.03 | 29.87 | 61.16 | 196.46 | 17.42 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 22.85 | 53.05 | 128.30 | 49.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.18 | 32.67 | 75.51 | 280.03 | 19.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 22.85 | 53.05 | 120.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.74 | 41.82 | 90.92 | 439.91 | 68.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.12 | 0.00 | 24.12 | 31.82 | 38.63 | 0.00 | 0.00 | 0.00 |
February | 27.65 | 0.00 | 27.65 | 42.71 | 30.04 | 0.00 | 0.00 | 0.00 |
March | 31.76 | 0.00 | 31.76 | 61.36 | 19.99 | 0.00 | 0.00 | 0.00 |
April | 35.90 | 0.14 | 35.76 | 90.24 | 7.50 | 0.00 | 0.00 | 0.00 |
May | 40.36 | 1.24 | 39.12 | 142.48 | 0.42 | 0.00 | 0.00 | 0.00 |
June | 43.14 | 2.42 | 40.73 | 165.97 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 39.64 | 1.19 | 38.45 | 184.39 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 36.93 | 0.37 | 36.56 | 180.82 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33.56 | 0.01 | 33.55 | 142.23 | 0.11 | 0.00 | 0.00 | 0.00 |
October | 29.74 | 0.00 | 29.74 | 102.85 | 0.90 | 0.00 | 0.00 | 0.00 |
November | 25.53 | 0.00 | 25.53 | 63.14 | 9.37 | 0.00 | 0.00 | 0.00 |
December | 22.51 | 0.00 | 22.51 | 36.19 | 28.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.59 | 0.45 | 32.14 | 104.06 | 11.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.51 | 0.00 | 22.51 | 31.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.14 | 2.42 | 40.73 | 184.39 | 38.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.12 | 23.05 | 57.08 | 122.60 | 71.28 | 0.00 | 0.00 | 0.00 |
February | 91.44 | 26.16 | 65.28 | 151.68 | 55.22 | 0.00 | 0.00 | 0.00 |
March | 108.02 | 31.98 | 76.04 | 203.40 | 37.00 | 0.00 | 0.00 | 0.00 |
April | 118.11 | 33.18 | 84.93 | 261.54 | 14.18 | 0.00 | 0.00 | 0.00 |
May | 128.49 | 38.46 | 90.04 | 362.78 | 0.88 | 0.00 | 0.00 | 0.00 |
June | 132.74 | 41.82 | 90.92 | 403.34 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 121.75 | 34.77 | 86.98 | 431.12 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 124.91 | 37.91 | 87.00 | 440.45 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 119.03 | 37.44 | 81.58 | 369.64 | 0.19 | 0.00 | 0.00 | 0.00 |
October | 105.87 | 34.32 | 71.55 | 285.12 | 1.61 | 0.00 | 0.00 | 0.00 |
November | 91.03 | 29.87 | 61.16 | 198.30 | 17.38 | 0.00 | 0.00 | 0.00 |
December | 75.91 | 22.85 | 53.05 | 129.86 | 52.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.18 | 32.67 | 75.51 | 280.73 | 20.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.91 | 22.85 | 53.05 | 122.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.74 | 41.82 | 90.92 | 440.45 | 71.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.86 | 54.24 | 60.61 | 185.31 | 51.75 | 0.00 | 0.00 | 0.00 |
February | 107.37 | 43.91 | 63.46 | 185.09 | 39.38 | 0.00 | 0.00 | 0.00 |
March | 87.44 | 23.08 | 64.37 | 173.27 | 25.77 | 0.00 | 0.00 | 0.00 |
April | 69.83 | 7.71 | 62.12 | 173.90 | 10.23 | 0.00 | 0.00 | 0.00 |
May | 59.08 | 1.11 | 57.97 | 215.53 | 0.52 | 0.00 | 0.00 | 0.00 |
June | 55.41 | 0.07 | 55.34 | 234.36 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 55.33 | 0.37 | 54.97 | 271.51 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 64.01 | 4.26 | 59.75 | 294.28 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 84.85 | 19.51 | 65.34 | 287.32 | 0.11 | 0.00 | 0.00 | 0.00 |
October | 111.13 | 44.30 | 66.84 | 283.05 | 1.11 | 0.00 | 0.00 | 0.00 |
November | 123.00 | 59.59 | 63.41 | 250.14 | 12.96 | 0.00 | 0.00 | 0.00 |
December | 113.82 | 56.33 | 57.50 | 196.40 | 37.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.05 | 26.11 | 60.94 | 229.46 | 14.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 55.33 | 0.07 | 54.97 | 173.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.00 | 59.59 | 66.84 | 294.28 | 51.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 168.82 | 0.00 | 168.82 | 185.88 | 376.57 | 0.00 | 0.00 | 0.00 |
February | 193.52 | 0.00 | 193.52 | 260.24 | 305.38 | 0.00 | 0.00 | 0.00 |
March | 222.31 | 0.00 | 222.31 | 382.60 | 216.58 | 0.00 | 0.00 | 0.00 |
April | 251.29 | 1.00 | 250.29 | 568.38 | 116.23 | 0.00 | 0.00 | 0.00 |
May | 282.49 | 8.66 | 273.83 | 892.38 | 17.77 | 0.00 | 0.00 | 0.00 |
June | 302.00 | 16.93 | 285.07 | 1043.66 | 1.45 | 0.00 | 0.00 | 0.00 |
July | 277.50 | 8.35 | 269.15 | 1174.47 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 258.52 | 2.60 | 255.92 | 1151.24 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 234.94 | 0.07 | 234.87 | 877.36 | 5.09 | 0.00 | 0.00 | 0.00 |
October | 208.19 | 0.00 | 208.19 | 616.73 | 32.61 | 0.00 | 0.00 | 0.00 |
November | 178.72 | 0.00 | 178.72 | 379.30 | 137.88 | 0.00 | 0.00 | 0.00 |
December | 157.57 | 0.00 | 157.57 | 213.15 | 294.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 228.12 | 3.15 | 224.98 | 647.83 | 124.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 157.57 | 0.00 | 157.57 | 185.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 302.00 | 16.93 | 285.07 | 1174.47 | 376.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 168.82 | 0.00 | 168.82 | 173.87 | 394.83 | 0.00 | 0.00 | 0.00 |
February | 193.52 | 0.00 | 193.52 | 248.31 | 320.50 | 0.00 | 0.00 | 0.00 |
March | 222.31 | 0.00 | 222.31 | 370.48 | 228.02 | 0.00 | 0.00 | 0.00 |
April | 251.29 | 1.00 | 250.29 | 556.97 | 123.46 | 0.00 | 0.00 | 0.00 |
May | 282.49 | 8.66 | 273.83 | 880.19 | 19.56 | 0.00 | 0.00 | 0.00 |
June | 302.00 | 16.93 | 285.07 | 1030.60 | 1.77 | 0.00 | 0.00 | 0.00 |
July | 277.50 | 8.35 | 269.15 | 1161.51 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 258.52 | 2.60 | 255.92 | 1138.30 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 234.94 | 0.07 | 234.87 | 864.52 | 5.75 | 0.00 | 0.00 | 0.00 |
October | 208.19 | 0.00 | 208.19 | 604.92 | 35.83 | 0.00 | 0.00 | 0.00 |
November | 178.72 | 0.00 | 178.72 | 368.38 | 146.37 | 0.00 | 0.00 | 0.00 |
December | 157.57 | 0.00 | 157.57 | 202.10 | 310.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 228.12 | 3.15 | 224.98 | 635.72 | 131.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 157.57 | 0.00 | 157.57 | 173.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 302.00 | 16.93 | 285.07 | 1161.51 | 394.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.12 | 0.00 | 24.12 | 32.85 | 51.40 | 0.00 | 0.00 | 0.00 |
February | 27.65 | 0.00 | 27.65 | 44.96 | 42.80 | 0.00 | 0.00 | 0.00 |
March | 31.76 | 0.00 | 31.76 | 64.63 | 30.68 | 0.00 | 0.00 | 0.00 |
April | 35.90 | 0.14 | 35.76 | 94.34 | 18.02 | 0.00 | 0.00 | 0.00 |
May | 40.36 | 1.24 | 39.12 | 141.95 | 4.00 | 0.00 | 0.00 | 0.00 |
June | 43.14 | 2.42 | 40.73 | 161.66 | 0.53 | 0.00 | 0.00 | 0.00 |
July | 39.64 | 1.19 | 38.45 | 180.17 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 36.93 | 0.37 | 36.56 | 176.38 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33.56 | 0.01 | 33.55 | 137.72 | 1.06 | 0.00 | 0.00 | 0.00 |
October | 29.74 | 0.00 | 29.74 | 102.16 | 6.21 | 0.00 | 0.00 | 0.00 |
November | 25.53 | 0.00 | 25.53 | 66.96 | 20.43 | 0.00 | 0.00 | 0.00 |
December | 22.51 | 0.00 | 22.51 | 38.58 | 39.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.59 | 0.45 | 32.14 | 103.88 | 17.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.51 | 0.00 | 22.51 | 32.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.14 | 2.42 | 40.73 | 180.17 | 51.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 162.63 | 49.05 | 113.58 | 251.32 | 180.39 | 0.00 | 0.00 | 0.00 |
February | 177.59 | 48.13 | 129.46 | 302.95 | 151.80 | 0.00 | 0.00 | 0.00 |
March | 196.33 | 48.43 | 147.90 | 386.77 | 110.24 | 0.00 | 0.00 | 0.00 |
April | 239.01 | 69.55 | 169.46 | 553.52 | 66.40 | 0.00 | 0.00 | 0.00 |
May | 266.67 | 84.92 | 181.75 | 748.84 | 15.10 | 0.00 | 0.00 | 0.00 |
June | 261.22 | 79.86 | 181.37 | 788.06 | 1.96 | 0.00 | 0.00 | 0.00 |
July | 243.85 | 70.26 | 173.58 | 853.96 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 249.77 | 76.68 | 173.08 | 869.66 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 234.67 | 72.49 | 162.18 | 722.44 | 4.01 | 0.00 | 0.00 | 0.00 |
October | 212.89 | 69.45 | 143.44 | 577.52 | 23.31 | 0.00 | 0.00 | 0.00 |
November | 178.34 | 56.32 | 122.02 | 408.45 | 73.79 | 0.00 | 0.00 | 0.00 |
December | 144.59 | 39.76 | 104.83 | 255.59 | 142.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 214.11 | 63.81 | 150.30 | 561.40 | 63.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 144.59 | 39.76 | 104.83 | 251.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 266.67 | 84.92 | 181.75 | 869.66 | 180.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.31 | 36.98 | 41.33 | 131.77 | 48.03 | 0.00 | 0.00 | 0.00 |
February | 73.21 | 29.94 | 43.27 | 130.89 | 41.02 | 0.00 | 0.00 | 0.00 |
March | 59.62 | 15.73 | 43.89 | 121.77 | 30.24 | 0.00 | 0.00 | 0.00 |
April | 47.61 | 5.26 | 42.36 | 120.69 | 18.17 | 0.00 | 0.00 | 0.00 |
May | 40.28 | 0.76 | 39.52 | 141.89 | 4.10 | 0.00 | 0.00 | 0.00 |
June | 37.78 | 0.05 | 37.73 | 149.47 | 0.53 | 0.00 | 0.00 | 0.00 |
July | 37.73 | 0.25 | 37.48 | 175.65 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 43.65 | 2.90 | 40.74 | 191.61 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 57.85 | 13.30 | 44.55 | 189.45 | 1.05 | 0.00 | 0.00 | 0.00 |
October | 75.78 | 30.20 | 45.57 | 193.35 | 6.17 | 0.00 | 0.00 | 0.00 |
November | 83.87 | 40.63 | 43.23 | 176.86 | 19.62 | 0.00 | 0.00 | 0.00 |
December | 77.61 | 38.41 | 39.20 | 140.05 | 37.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 59.36 | 17.80 | 41.56 | 155.45 | 17.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.73 | 0.05 | 37.48 | 120.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.87 | 40.63 | 45.57 | 193.35 | 48.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.54 | 0.00 | 30.54 | 40.29 | 52.05 | 0.00 | 0.00 | 0.00 |
February | 35.01 | 0.00 | 35.01 | 53.81 | 41.94 | 0.00 | 0.00 | 0.00 |
March | 40.22 | 0.00 | 40.22 | 76.16 | 29.86 | 0.00 | 0.00 | 0.00 |
April | 45.47 | 0.18 | 45.28 | 108.45 | 15.86 | 0.00 | 0.00 | 0.00 |
May | 51.11 | 1.57 | 49.54 | 163.78 | 2.37 | 0.00 | 0.00 | 0.00 |
June | 54.64 | 3.06 | 51.58 | 190.93 | 0.16 | 0.00 | 0.00 | 0.00 |
July | 50.21 | 1.51 | 48.70 | 213.85 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 46.77 | 0.47 | 46.30 | 209.37 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 42.51 | 0.01 | 42.49 | 160.17 | 0.68 | 0.00 | 0.00 | 0.00 |
October | 37.67 | 0.00 | 37.67 | 113.43 | 4.36 | 0.00 | 0.00 | 0.00 |
November | 32.34 | 0.00 | 32.34 | 72.98 | 19.35 | 0.00 | 0.00 | 0.00 |
December | 28.51 | 0.00 | 28.51 | 44.55 | 40.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.27 | 0.57 | 40.70 | 121.06 | 17.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.51 | 0.00 | 28.51 | 40.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.64 | 3.06 | 51.58 | 213.85 | 52.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.33 | 0.00 | 27.33 | 36.05 | 46.57 | 0.00 | 0.00 | 0.00 |
February | 31.33 | 0.00 | 31.33 | 48.14 | 37.53 | 0.00 | 0.00 | 0.00 |
March | 35.99 | 0.00 | 35.99 | 68.14 | 26.71 | 0.00 | 0.00 | 0.00 |
April | 40.68 | 0.16 | 40.52 | 97.03 | 14.19 | 0.00 | 0.00 | 0.00 |
May | 45.73 | 1.40 | 44.33 | 146.54 | 2.12 | 0.00 | 0.00 | 0.00 |
June | 48.89 | 2.74 | 46.15 | 170.83 | 0.14 | 0.00 | 0.00 | 0.00 |
July | 44.92 | 1.35 | 43.57 | 191.33 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 41.85 | 0.42 | 41.43 | 187.32 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38.03 | 0.01 | 38.02 | 143.30 | 0.61 | 0.00 | 0.00 | 0.00 |
October | 33.70 | 0.00 | 33.70 | 101.48 | 3.90 | 0.00 | 0.00 | 0.00 |
November | 28.93 | 0.00 | 28.93 | 65.29 | 17.31 | 0.00 | 0.00 | 0.00 |
December | 25.51 | 0.00 | 25.51 | 39.86 | 36.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.93 | 0.51 | 36.42 | 108.31 | 15.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.51 | 0.00 | 25.51 | 36.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.89 | 2.74 | 46.15 | 191.33 | 46.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 292.37 | 138.07 | 154.30 | 480.85 | 142.28 | 0.00 | 0.00 | 0.00 |
February | 273.32 | 111.79 | 161.53 | 472.65 | 118.09 | 0.00 | 0.00 | 0.00 |
March | 222.59 | 58.74 | 163.85 | 432.46 | 87.34 | 0.00 | 0.00 | 0.00 |
April | 177.76 | 19.63 | 158.13 | 414.40 | 48.06 | 0.00 | 0.00 | 0.00 |
May | 150.39 | 2.84 | 147.56 | 481.17 | 7.68 | 0.00 | 0.00 | 0.00 |
June | 141.05 | 0.17 | 140.88 | 517.72 | 0.47 | 0.00 | 0.00 | 0.00 |
July | 140.85 | 0.93 | 139.92 | 611.78 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 162.94 | 10.84 | 152.10 | 671.67 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 215.98 | 49.66 | 166.32 | 660.51 | 1.95 | 0.00 | 0.00 | 0.00 |
October | 282.90 | 112.76 | 170.14 | 667.61 | 12.38 | 0.00 | 0.00 | 0.00 |
November | 313.10 | 151.69 | 161.41 | 617.67 | 53.98 | 0.00 | 0.00 | 0.00 |
December | 289.74 | 143.38 | 146.36 | 502.42 | 112.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 221.60 | 66.46 | 155.14 | 544.74 | 48.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 140.85 | 0.17 | 139.92 | 414.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 313.10 | 151.69 | 170.14 | 671.67 | 142.28 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106089E+10 | 0.501015E+09 | 0.559875E+09 | 0.171986E+10 | 0.529870E+09 |
February | 0.895772E+09 | 0.366370E+09 | 0.529403E+09 | 0.153133E+10 | 0.395918E+09 |
March | 0.807673E+09 | 0.213150E+09 | 0.594524E+09 | 0.154103E+10 | 0.327342E+09 |
April | 0.624204E+09 | 68941985.48 | 0.555262E+09 | 0.141588E+10 | 0.177909E+09 |
May | 0.545709E+09 | 10297057.61 | 0.535412E+09 | 0.164261E+10 | 31750396.03 |
June | 0.495298E+09 | 612545.60 | 0.494685E+09 | 0.167329E+10 | 3032078.23 |
July | 0.511095E+09 | 3381839.23 | 0.507713E+09 | 0.204413E+10 | 0.00 |
August | 0.591245E+09 | 39328632.82 | 0.551917E+09 | 0.225241E+10 | 0.00 |
September | 0.758432E+09 | 0.174399E+09 | 0.584033E+09 | 0.218420E+10 | 9628725.11 |
October | 0.102652E+10 | 0.409144E+09 | 0.617377E+09 | 0.232679E+10 | 60137580.46 |
November | 0.109945E+10 | 0.532665E+09 | 0.566787E+09 | 0.210687E+10 | 0.218771E+09 |
December | 0.105134E+10 | 0.520273E+09 | 0.531067E+09 | 0.179105E+10 | 0.429254E+09 |
Annual Sum or Average | 0.946763E+10 | 0.283958E+10 | 0.662805E+10 | 0.222294E+11 | 0.218361E+10 |
Minimum of Months | 0.495298E+09 | 612545.60 | 0.494685E+09 | 0.141588E+10 | 0.00 |
Maximum of Months | 0.109945E+10 | 0.532665E+09 | 0.617377E+09 | 0.232679E+10 | 0.529870E+09 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.298740E+10 | 0.141082E+10 | 0.157657E+10 | 0.470200E+10 | 0.176625E+10 |
February | 0.252244E+10 | 0.103167E+10 | 0.149076E+10 | 0.420356E+10 | 0.133652E+10 |
March | 0.227435E+10 | 0.600216E+09 | 0.167414E+10 | 0.424485E+10 | 0.111103E+10 |
April | 0.175772E+10 | 0.194136E+09 | 0.156358E+10 | 0.392193E+10 | 0.619054E+09 |
May | 0.153668E+10 | 28995835.30 | 0.150769E+10 | 0.462300E+10 | 0.115796E+09 |
June | 0.139473E+10 | 1724888.02 | 0.139300E+10 | 0.473254E+10 | 12435306.80 |
July | 0.143921E+10 | 9523036.29 | 0.142969E+10 | 0.578459E+10 | 0.00 |
August | 0.166491E+10 | 0.110747E+09 | 0.155416E+10 | 0.636561E+10 | 0.00 |
September | 0.213569E+10 | 0.491095E+09 | 0.164460E+10 | 0.613810E+10 | 35569440.83 |
October | 0.289061E+10 | 0.115212E+10 | 0.173849E+10 | 0.651186E+10 | 0.207670E+09 |
November | 0.309598E+10 | 0.149995E+10 | 0.159603E+10 | 0.585273E+10 | 0.722143E+09 |
December | 0.296051E+10 | 0.146506E+10 | 0.149545E+10 | 0.492339E+10 | 0.143926E+10 |
Annual Sum or Average | 0.266602E+11 | 0.799606E+10 | 0.186642E+11 | 0.620042E+11 | 0.736573E+10 |
Minimum of Months | 0.139473E+10 | 1724888.02 | 0.139300E+10 | 0.392193E+10 | 0.00 |
Maximum of Months | 0.309598E+10 | 0.149995E+10 | 0.173849E+10 | 0.651186E+10 | 0.176625E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.388080E+10 | 0.183274E+10 | 0.204806E+10 | 0.623306E+10 | 0.237748E+10 |
February | 0.327679E+10 | 0.134020E+10 | 0.193659E+10 | 0.558446E+10 | 0.179215E+10 |
March | 0.295452E+10 | 0.779714E+09 | 0.217480E+10 | 0.564538E+10 | 0.148729E+10 |
April | 0.228337E+10 | 0.252194E+09 | 0.203118E+10 | 0.523408E+10 | 0.817017E+09 |
May | 0.199624E+10 | 37667240.23 | 0.195857E+10 | 0.621719E+10 | 0.147703E+09 |
June | 0.181183E+10 | 2240727.70 | 0.180959E+10 | 0.636861E+10 | 14816050.70 |
July | 0.186962E+10 | 12370966.10 | 0.185724E+10 | 0.780357E+10 | 0.00 |
August | 0.216281E+10 | 0.143866E+09 | 0.201894E+10 | 0.858354E+10 | 0.00 |
September | 0.277439E+10 | 0.637960E+09 | 0.213643E+10 | 0.825936E+10 | 42652682.86 |
October | 0.375507E+10 | 0.149667E+10 | 0.225840E+10 | 0.873248E+10 | 0.254369E+09 |
November | 0.402186E+10 | 0.194852E+10 | 0.207334E+10 | 0.782514E+10 | 0.926790E+09 |
December | 0.384587E+10 | 0.190319E+10 | 0.194267E+10 | 0.653780E+10 | 0.191855E+10 |
Annual Sum or Average | 0.346332E+11 | 0.103873E+11 | 0.242458E+11 | 0.830247E+11 | 0.977883E+10 |
Minimum of Months | 0.181183E+10 | 2240727.70 | 0.180959E+10 | 0.523408E+10 | 0.00 |
Maximum of Months | 0.402186E+10 | 0.194852E+10 | 0.225840E+10 | 0.873248E+10 | 0.237748E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209757E+09 | 99059251.48 | 0.110698E+09 | 0.345736E+09 | 93767638.50 |
February | 0.177110E+09 | 72437614.58 | 0.104673E+09 | 0.309880E+09 | 65830941.34 |
March | 0.159692E+09 | 42143365.56 | 0.117548E+09 | 0.316970E+09 | 49823966.43 |
April | 0.123417E+09 | 13631014.60 | 0.109786E+09 | 0.302362E+09 | 20762964.85 |
May | 0.107897E+09 | 2035905.14 | 0.105861E+09 | 0.379831E+09 | 1511280.33 |
June | 97930013.93 | 121110.79 | 97808903.15 | 0.397298E+09 | 22185.64 |
July | 0.101053E+09 | 668647.70 | 0.100385E+09 | 0.479145E+09 | 0.00 |
August | 0.116900E+09 | 7775946.17 | 0.109125E+09 | 0.521458E+09 | 0.00 |
September | 0.149956E+09 | 34481594.92 | 0.115474E+09 | 0.497012E+09 | 298080.02 |
October | 0.202962E+09 | 80894729.87 | 0.122067E+09 | 0.512069E+09 | 2714766.89 |
November | 0.217381E+09 | 0.105317E+09 | 0.112064E+09 | 0.444133E+09 | 24822175.49 |
December | 0.207869E+09 | 0.102867E+09 | 0.105002E+09 | 0.364421E+09 | 69469051.08 |
Annual Sum or Average | 0.187192E+10 | 0.561433E+09 | 0.131049E+10 | 0.487031E+10 | 0.329023E+09 |
Minimum of Months | 97930013.93 | 121110.79 | 97808903.15 | 0.302362E+09 | 0.00 |
Maximum of Months | 0.217381E+09 | 0.105317E+09 | 0.122067E+09 | 0.521458E+09 | 93767638.50 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214599E+09 | 61728185.06 | 0.152871E+09 | 0.327781E+09 | 0.188487E+09 |
February | 0.221221E+09 | 63288497.46 | 0.157932E+09 | 0.370775E+09 | 0.128488E+09 |
March | 0.289318E+09 | 85658341.72 | 0.203660E+09 | 0.550586E+09 | 93953198.91 |
April | 0.306149E+09 | 86007599.93 | 0.220141E+09 | 0.684067E+09 | 38207828.31 |
May | 0.344157E+09 | 0.103003E+09 | 0.241154E+09 | 0.973494E+09 | 2644057.76 |
June | 0.344056E+09 | 0.108404E+09 | 0.235652E+09 | 0.104560E+10 | 42066.10 |
July | 0.326083E+09 | 93121778.29 | 0.232961E+09 | 0.115470E+10 | 0.00 |
August | 0.334560E+09 | 0.101529E+09 | 0.233031E+09 | 0.117806E+10 | 0.00 |
September | 0.308518E+09 | 97057138.34 | 0.211461E+09 | 0.952640E+09 | 529406.06 |
October | 0.283567E+09 | 91929001.41 | 0.191638E+09 | 0.755503E+09 | 5079860.32 |
November | 0.235943E+09 | 77413695.10 | 0.158529E+09 | 0.510196E+09 | 48643364.50 |
December | 0.203311E+09 | 61210839.51 | 0.142101E+09 | 0.346980E+09 | 0.138016E+09 |
Annual Sum or Average | 0.341148E+10 | 0.103035E+10 | 0.238113E+10 | 0.885038E+10 | 0.644091E+09 |
Minimum of Months | 0.203311E+09 | 61210839.51 | 0.142101E+09 | 0.327781E+09 | 0.00 |
Maximum of Months | 0.344157E+09 | 0.108404E+09 | 0.241154E+09 | 0.117806E+10 | 0.188487E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 64598396.86 | 0.00 | 64598396.86 | 85727513.33 | 0.105829E+09 |
February | 66882322.40 | 0.00 | 66882322.40 | 0.104056E+09 | 74275404.68 |
March | 85067066.34 | 1019.81 | 85066046.53 | 0.165270E+09 | 55197043.64 |
April | 93053529.14 | 370879.84 | 92682649.30 | 0.234131E+09 | 20922011.63 |
May | 0.108093E+09 | 3314474.28 | 0.104779E+09 | 0.380527E+09 | 1363702.56 |
June | 0.111830E+09 | 6269529.39 | 0.105560E+09 | 0.428615E+09 | 24358.44 |
July | 0.106183E+09 | 3193498.36 | 0.102990E+09 | 0.491966E+09 | 0.00 |
August | 98920446.75 | 994666.35 | 97925780.39 | 0.482197E+09 | 0.00 |
September | 86998567.13 | 26467.21 | 86972099.92 | 0.366122E+09 | 351728.82 |
October | 79660604.55 | 0.00 | 79660604.55 | 0.272820E+09 | 2932021.94 |
November | 66180877.97 | 0.00 | 66180877.97 | 0.162196E+09 | 26411906.58 |
December | 60294245.24 | 0.00 | 60294245.24 | 96891504.14 | 78453230.64 |
Annual Sum or Average | 0.102776E+10 | 14170535.24 | 0.101359E+10 | 0.327052E+10 | 0.365760E+09 |
Minimum of Months | 60294245.24 | 0.00 | 60294245.24 | 85727513.33 | 0.00 |
Maximum of Months | 0.111830E+09 | 6269529.39 | 0.105560E+09 | 0.491966E+09 | 0.105829E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214599E+09 | 61728185.06 | 0.152871E+09 | 0.331991E+09 | 0.195331E+09 |
February | 0.221221E+09 | 63288497.46 | 0.157932E+09 | 0.370975E+09 | 0.136673E+09 |
March | 0.289318E+09 | 85658341.72 | 0.203660E+09 | 0.549828E+09 | 0.102266E+09 |
April | 0.306149E+09 | 86007599.93 | 0.220141E+09 | 0.681701E+09 | 39676709.09 |
May | 0.344157E+09 | 0.103003E+09 | 0.241154E+09 | 0.972533E+09 | 2842976.70 |
June | 0.344056E+09 | 0.108404E+09 | 0.235652E+09 | 0.104436E+10 | 42850.75 |
July | 0.326083E+09 | 93121778.29 | 0.232961E+09 | 0.115432E+10 | 0.00 |
August | 0.334560E+09 | 0.101529E+09 | 0.233031E+09 | 0.117948E+10 | 0.00 |
September | 0.308518E+09 | 97057138.34 | 0.211461E+09 | 0.956808E+09 | 614458.60 |
October | 0.283567E+09 | 91929001.41 | 0.191638E+09 | 0.762013E+09 | 5243551.03 |
November | 0.235943E+09 | 77413695.10 | 0.158529E+09 | 0.513894E+09 | 48992472.44 |
December | 0.203311E+09 | 61210839.51 | 0.142101E+09 | 0.350188E+09 | 0.145531E+09 |
Annual Sum or Average | 0.341148E+10 | 0.103035E+10 | 0.238113E+10 | 0.886809E+10 | 0.677214E+09 |
Minimum of Months | 0.203311E+09 | 61210839.51 | 0.142101E+09 | 0.331991E+09 | 0.00 |
Maximum of Months | 0.344157E+09 | 0.108404E+09 | 0.241154E+09 | 0.117948E+10 | 0.195331E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.167772E+09 | 79231644.14 | 88540435.51 | 0.233963E+09 | 0.143149E+09 |
February | 0.141660E+09 | 57938569.24 | 83721463.90 | 0.210481E+09 | 0.112937E+09 |
March | 0.127728E+09 | 33707988.83 | 94020020.17 | 0.210008E+09 | 98375234.82 |
April | 98713829.41 | 10902643.44 | 87811185.97 | 0.192850E+09 | 61323165.71 |
May | 86300615.81 | 1628400.27 | 84672215.54 | 0.227669E+09 | 17651746.77 |
June | 78328433.73 | 96869.36 | 78231564.37 | 0.232689E+09 | 5011759.11 |
July | 80826650.48 | 534811.80 | 80291838.68 | 0.290291E+09 | 251510.50 |
August | 93501784.60 | 6219520.04 | 87282264.56 | 0.323697E+09 | 104780.22 |
September | 0.119941E+09 | 27579791.06 | 92361105.18 | 0.312515E+09 | 7177562.47 |
October | 0.162337E+09 | 64702916.23 | 97634093.70 | 0.338610E+09 | 27964156.41 |
November | 0.173870E+09 | 84236921.85 | 89633479.97 | 0.305511E+09 | 67528741.18 |
December | 0.166262E+09 | 82277240.17 | 83984635.32 | 0.249588E+09 | 0.120604E+09 |
Annual Sum or Average | 0.149724E+10 | 0.449057E+09 | 0.104818E+10 | 0.312787E+10 | 0.662078E+09 |
Minimum of Months | 78328433.73 | 96869.36 | 78231564.37 | 0.192850E+09 | 104780.22 |
Maximum of Months | 0.173870E+09 | 84236921.85 | 97634093.70 | 0.338610E+09 | 0.143149E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51685567.80 | 0.00 | 51685567.80 | 70911354.21 | 84777543.15 |
February | 53512950.43 | 0.00 | 53512950.43 | 87315563.09 | 57797889.96 |
March | 68062673.97 | 815.95 | 68061858.01 | 0.139785E+09 | 41068162.38 |
April | 74452691.13 | 296743.20 | 74155947.93 | 0.199070E+09 | 14054183.68 |
May | 86486126.04 | 2651930.91 | 83834195.14 | 0.323791E+09 | 605504.30 |
June | 89475839.67 | 5016288.36 | 84459551.31 | 0.363665E+09 | 529.18 |
July | 84957971.33 | 2555137.34 | 82402833.99 | 0.416037E+09 | 0.00 |
August | 79146847.37 | 795838.56 | 78351008.81 | 0.408863E+09 | 0.00 |
September | 69608079.43 | 21176.58 | 69586902.85 | 0.312995E+09 | 145856.44 |
October | 63736931.21 | 0.00 | 63736931.21 | 0.235297E+09 | 1450441.30 |
November | 52951720.50 | 0.00 | 52951720.50 | 0.139429E+09 | 18101119.74 |
December | 48241790.07 | 0.00 | 48241790.07 | 81216971.41 | 61455664.20 |
Annual Sum or Average | 0.822319E+09 | 11337930.90 | 0.810981E+09 | 0.277837E+10 | 0.279457E+09 |
Minimum of Months | 48241790.07 | 0.00 | 48241790.07 | 70911354.21 | 0.00 |
Maximum of Months | 89475839.67 | 5016288.36 | 84459551.31 | 0.416037E+09 | 84777543.15 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217811E+09 | 65694227.05 | 0.152117E+09 | 0.322747E+09 | 0.174867E+09 |
February | 0.214825E+09 | 58222494.92 | 0.156603E+09 | 0.353870E+09 | 0.119986E+09 |
March | 0.262946E+09 | 64860068.80 | 0.198086E+09 | 0.501228E+09 | 87088800.82 |
April | 0.309775E+09 | 90143128.72 | 0.219632E+09 | 0.696497E+09 | 35824713.85 |
May | 0.357154E+09 | 0.113738E+09 | 0.243416E+09 | 0.100208E+10 | 2404567.40 |
June | 0.338571E+09 | 0.103501E+09 | 0.235070E+09 | 0.104020E+10 | 35950.83 |
July | 0.326583E+09 | 94102098.75 | 0.232481E+09 | 0.116188E+10 | 0.00 |
August | 0.334513E+09 | 0.102703E+09 | 0.231810E+09 | 0.118156E+10 | 0.00 |
September | 0.304158E+09 | 93958399.31 | 0.210199E+09 | 0.948570E+09 | 559979.09 |
October | 0.285129E+09 | 93013451.27 | 0.192115E+09 | 0.763277E+09 | 4989154.95 |
November | 0.231144E+09 | 73001029.63 | 0.158143E+09 | 0.502539E+09 | 45850777.00 |
December | 0.193650E+09 | 53245381.57 | 0.140404E+09 | 0.323065E+09 | 0.129227E+09 |
Annual Sum or Average | 0.337626E+10 | 0.100618E+10 | 0.237008E+10 | 0.879751E+10 | 0.600834E+09 |
Minimum of Months | 0.193650E+09 | 53245381.57 | 0.140404E+09 | 0.322747E+09 | 0.00 |
Maximum of Months | 0.357154E+09 | 0.113738E+09 | 0.243416E+09 | 0.118156E+10 | 0.174867E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209757E+09 | 99059251.48 | 0.110698E+09 | 0.344228E+09 | 93217596.21 |
February | 0.177110E+09 | 72437614.58 | 0.104673E+09 | 0.308911E+09 | 65252193.05 |
March | 0.159692E+09 | 42143365.56 | 0.117548E+09 | 0.316606E+09 | 49049474.81 |
April | 0.123417E+09 | 13631014.60 | 0.109786E+09 | 0.301316E+09 | 20489430.14 |
May | 0.107897E+09 | 2035905.14 | 0.105861E+09 | 0.378919E+09 | 1459938.94 |
June | 97930013.93 | 121110.79 | 97808903.15 | 0.397145E+09 | 20389.31 |
July | 0.101053E+09 | 668647.70 | 0.100385E+09 | 0.478854E+09 | 0.00 |
August | 0.116900E+09 | 7775946.17 | 0.109125E+09 | 0.521184E+09 | 0.00 |
September | 0.149956E+09 | 34481594.92 | 0.115474E+09 | 0.496836E+09 | 290046.56 |
October | 0.202962E+09 | 80894729.87 | 0.122067E+09 | 0.511572E+09 | 2643646.79 |
November | 0.217381E+09 | 0.105317E+09 | 0.112064E+09 | 0.443532E+09 | 24472252.07 |
December | 0.207869E+09 | 0.102867E+09 | 0.105002E+09 | 0.363570E+09 | 68854087.98 |
Annual Sum or Average | 0.187192E+10 | 0.561433E+09 | 0.131049E+10 | 0.486267E+10 | 0.325749E+09 |
Minimum of Months | 97930013.93 | 121110.79 | 97808903.15 | 0.301316E+09 | 0.00 |
Maximum of Months | 0.217381E+09 | 0.105317E+09 | 0.122067E+09 | 0.521184E+09 | 93217596.21 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 64598396.86 | 0.00 | 64598396.86 | 83798506.35 | 0.104624E+09 |
February | 66882322.40 | 0.00 | 66882322.40 | 0.102557E+09 | 73090546.34 |
March | 85067066.34 | 1019.81 | 85066046.53 | 0.164608E+09 | 53898188.73 |
April | 93053529.14 | 370879.84 | 92682649.30 | 0.232439E+09 | 20657947.41 |
May | 0.108093E+09 | 3314474.28 | 0.104779E+09 | 0.379495E+09 | 1315851.52 |
June | 0.111830E+09 | 6269529.39 | 0.105560E+09 | 0.428454E+09 | 22573.96 |
July | 0.106183E+09 | 3193498.36 | 0.102990E+09 | 0.491700E+09 | 0.00 |
August | 98920446.75 | 994666.35 | 97925780.39 | 0.481958E+09 | 0.00 |
September | 86998567.13 | 26467.21 | 86972099.92 | 0.365919E+09 | 343099.34 |
October | 79660604.55 | 0.00 | 79660604.55 | 0.272060E+09 | 2875887.09 |
November | 66180877.97 | 0.00 | 66180877.97 | 0.160489E+09 | 26143061.08 |
December | 60294245.24 | 0.00 | 60294245.24 | 95394444.45 | 77337612.90 |
Annual Sum or Average | 0.102776E+10 | 14170535.24 | 0.101359E+10 | 0.325887E+10 | 0.360309E+09 |
Minimum of Months | 60294245.24 | 0.00 | 60294245.24 | 83798506.35 | 0.00 |
Maximum of Months | 0.111830E+09 | 6269529.39 | 0.105560E+09 | 0.491700E+09 | 0.104624E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217811E+09 | 65694227.05 | 0.152117E+09 | 0.326786E+09 | 0.180993E+09 |
February | 0.214825E+09 | 58222494.92 | 0.156603E+09 | 0.353618E+09 | 0.127481E+09 |
March | 0.262946E+09 | 64860068.80 | 0.198086E+09 | 0.499282E+09 | 93963850.78 |
April | 0.309775E+09 | 90143128.72 | 0.219632E+09 | 0.691672E+09 | 36522788.32 |
May | 0.357154E+09 | 0.113738E+09 | 0.243416E+09 | 0.100061E+10 | 2448395.72 |
June | 0.338571E+09 | 0.103501E+09 | 0.235070E+09 | 0.103892E+10 | 36644.65 |
July | 0.326583E+09 | 94102098.75 | 0.232481E+09 | 0.116150E+10 | 0.00 |
August | 0.334513E+09 | 0.102703E+09 | 0.231810E+09 | 0.118297E+10 | 0.00 |
September | 0.304158E+09 | 93958399.31 | 0.210199E+09 | 0.952620E+09 | 604846.11 |
October | 0.285129E+09 | 93013451.27 | 0.192115E+09 | 0.768930E+09 | 4936474.25 |
November | 0.231144E+09 | 73001029.63 | 0.158143E+09 | 0.502728E+09 | 45557150.72 |
December | 0.193650E+09 | 53245381.57 | 0.140404E+09 | 0.324775E+09 | 0.135655E+09 |
Annual Sum or Average | 0.337626E+10 | 0.100618E+10 | 0.237008E+10 | 0.880442E+10 | 0.628199E+09 |
Minimum of Months | 0.193650E+09 | 53245381.57 | 0.140404E+09 | 0.324775E+09 | 0.00 |
Maximum of Months | 0.357154E+09 | 0.113738E+09 | 0.243416E+09 | 0.118297E+10 | 0.180993E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 81809793.70 | 0.00 | 81809793.70 | 0.112279E+09 | 0.141660E+09 |
February | 84702241.28 | 0.00 | 84702241.28 | 0.135662E+09 | 0.102066E+09 |
March | 0.107732E+09 | 1291.52 | 0.107731E+09 | 0.212860E+09 | 79094072.54 |
April | 0.117846E+09 | 469695.92 | 0.117377E+09 | 0.293988E+09 | 38534855.39 |
May | 0.136893E+09 | 4197572.54 | 0.132696E+09 | 0.455364E+09 | 5447019.41 |
June | 0.141626E+09 | 7939963.38 | 0.133686E+09 | 0.510683E+09 | 293236.78 |
July | 0.134475E+09 | 4044364.17 | 0.130430E+09 | 0.589504E+09 | 0.00 |
August | 0.125277E+09 | 1259682.17 | 0.124017E+09 | 0.577070E+09 | 0.00 |
September | 0.110178E+09 | 33519.06 | 0.110145E+09 | 0.429070E+09 | 1543589.64 |
October | 0.100885E+09 | 0.00 | 0.100885E+09 | 0.315416E+09 | 10914670.30 |
November | 83813906.17 | 0.00 | 83813906.17 | 0.196079E+09 | 50185012.21 |
December | 76358857.24 | 0.00 | 76358857.24 | 0.123529E+09 | 0.110845E+09 |
Annual Sum or Average | 0.130160E+10 | 17946088.77 | 0.128365E+10 | 0.395150E+10 | 0.540584E+09 |
Minimum of Months | 76358857.24 | 0.00 | 76358857.24 | 0.112279E+09 | 0.00 |
Maximum of Months | 0.141626E+09 | 7939963.38 | 0.133686E+09 | 0.589504E+09 | 0.141660E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 30158477.43 | 0.00 | 30158477.43 | 41390566.59 | 52221665.38 |
February | 31224753.38 | 0.00 | 31224753.38 | 50010760.22 | 37625864.19 |
March | 39714502.60 | 476.11 | 39714026.50 | 78469010.23 | 29157350.17 |
April | 43443071.27 | 173149.36 | 43269921.90 | 0.108376E+09 | 14205543.30 |
May | 50464568.58 | 1547399.05 | 48917169.53 | 0.167866E+09 | 2007996.90 |
June | 52209063.51 | 2926999.27 | 49282064.24 | 0.188259E+09 | 108099.22 |
July | 49572891.82 | 1490920.10 | 48081971.72 | 0.217316E+09 | 0.00 |
August | 46182106.77 | 464371.01 | 45717735.76 | 0.212732E+09 | 0.00 |
September | 40616245.15 | 12356.51 | 40603888.64 | 0.158173E+09 | 569031.06 |
October | 37190436.00 | 0.00 | 37190436.00 | 0.116275E+09 | 4023600.80 |
November | 30897276.27 | 0.00 | 30897276.27 | 72282827.59 | 18500273.50 |
December | 28149036.55 | 0.00 | 28149036.55 | 45538041.43 | 40862145.69 |
Annual Sum or Average | 0.479822E+09 | 6615671.41 | 0.473207E+09 | 0.145669E+10 | 0.199282E+09 |
Minimum of Months | 28149036.55 | 0.00 | 28149036.55 | 41390566.59 | 0.00 |
Maximum of Months | 52209063.51 | 2926999.27 | 49282064.24 | 0.217316E+09 | 52221665.38 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 97871680.54 | 46220647.56 | 51651032.98 | 0.163587E+09 | 48090753.89 |
February | 82638932.16 | 33799099.06 | 48839833.10 | 0.145914E+09 | 35699591.38 |
March | 74511533.26 | 19663924.54 | 54847608.72 | 0.148803E+09 | 28755646.87 |
April | 57585793.76 | 6360176.48 | 51225617.27 | 0.139471E+09 | 14549715.49 |
May | 50344409.62 | 949945.13 | 49394464.49 | 0.167345E+09 | 2231226.97 |
June | 45693749.87 | 56509.80 | 45637240.07 | 0.173315E+09 | 112782.17 |
July | 47151111.98 | 311988.32 | 46839123.66 | 0.211147E+09 | 0.00 |
August | 54545290.32 | 3628225.15 | 50917065.17 | 0.231178E+09 | 0.00 |
September | 69968835.72 | 16088973.24 | 53879862.48 | 0.219902E+09 | 555045.32 |
October | 94701073.08 | 37745154.98 | 56955918.10 | 0.228953E+09 | 3861726.25 |
November | 0.101429E+09 | 49140531.14 | 52288672.44 | 0.203955E+09 | 17370751.28 |
December | 96990686.40 | 47997329.37 | 48993357.03 | 0.170703E+09 | 38136883.35 |
Annual Sum or Average | 0.873432E+09 | 0.261963E+09 | 0.611470E+09 | 0.220427E+10 | 0.189364E+09 |
Minimum of Months | 45693749.87 | 56509.80 | 45637240.07 | 0.139471E+09 | 0.00 |
Maximum of Months | 0.101429E+09 | 49140531.14 | 56955918.10 | 0.231178E+09 | 48090753.89 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265644E+09 | 0.125452E+09 | 0.140191E+09 | 0.444008E+09 | 0.130528E+09 |
February | 0.224299E+09 | 91737668.31 | 0.132561E+09 | 0.396042E+09 | 96895993.20 |
March | 0.202240E+09 | 53371913.38 | 0.148868E+09 | 0.403883E+09 | 78048707.45 |
April | 0.156300E+09 | 17262819.92 | 0.139037E+09 | 0.378554E+09 | 39490903.91 |
May | 0.136645E+09 | 2578345.40 | 0.134067E+09 | 0.454209E+09 | 6056006.38 |
June | 0.124022E+09 | 153379.17 | 0.123869E+09 | 0.470414E+09 | 306113.89 |
July | 0.127978E+09 | 846800.12 | 0.127131E+09 | 0.573097E+09 | 0.00 |
August | 0.148047E+09 | 9847745.19 | 0.138199E+09 | 0.627464E+09 | 0.00 |
September | 0.189910E+09 | 43668764.30 | 0.146241E+09 | 0.596859E+09 | 1506506.53 |
October | 0.257038E+09 | 0.102448E+09 | 0.154590E+09 | 0.621425E+09 | 10481514.95 |
November | 0.275300E+09 | 0.133377E+09 | 0.141922E+09 | 0.553577E+09 | 47147772.09 |
December | 0.263253E+09 | 0.130275E+09 | 0.132978E+09 | 0.463322E+09 | 0.103511E+09 |
Annual Sum or Average | 0.237067E+10 | 0.711020E+09 | 0.165965E+10 | 0.598285E+10 | 0.513973E+09 |
Minimum of Months | 0.124022E+09 | 153379.17 | 0.123869E+09 | 0.378554E+09 | 0.00 |
Maximum of Months | 0.275300E+09 | 0.133377E+09 | 0.154590E+09 | 0.627464E+09 | 0.130528E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209757E+09 | 99059251.48 | 0.110698E+09 | 0.342660E+09 | 91744830.00 |
February | 0.177110E+09 | 72437614.58 | 0.104673E+09 | 0.306866E+09 | 64080605.58 |
March | 0.159692E+09 | 42143365.56 | 0.117548E+09 | 0.314305E+09 | 47986192.51 |
April | 0.123417E+09 | 13631014.60 | 0.109786E+09 | 0.300876E+09 | 19349533.29 |
May | 0.107897E+09 | 2035905.14 | 0.105861E+09 | 0.380749E+09 | 1246413.53 |
June | 97930013.93 | 121110.79 | 97808903.15 | 0.399617E+09 | 10628.02 |
July | 0.101053E+09 | 668647.70 | 0.100385E+09 | 0.480679E+09 | 0.00 |
August | 0.116900E+09 | 7775946.17 | 0.109125E+09 | 0.522825E+09 | 0.00 |
September | 0.149956E+09 | 34481594.92 | 0.115474E+09 | 0.497689E+09 | 248216.43 |
October | 0.202962E+09 | 80894729.87 | 0.122067E+09 | 0.511793E+09 | 2265555.22 |
November | 0.217381E+09 | 0.105317E+09 | 0.112064E+09 | 0.442024E+09 | 23045583.32 |
December | 0.207869E+09 | 0.102867E+09 | 0.105002E+09 | 0.361685E+09 | 67332284.81 |
Annual Sum or Average | 0.187192E+10 | 0.561433E+09 | 0.131049E+10 | 0.486177E+10 | 0.317310E+09 |
Minimum of Months | 97930013.93 | 121110.79 | 97808903.15 | 0.300876E+09 | 0.00 |
Maximum of Months | 0.217381E+09 | 0.105317E+09 | 0.122067E+09 | 0.522825E+09 | 91744830.00 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214599E+09 | 61728185.06 | 0.152871E+09 | 0.323388E+09 | 0.183878E+09 |
February | 0.221221E+09 | 63288497.46 | 0.157932E+09 | 0.366419E+09 | 0.124784E+09 |
March | 0.289318E+09 | 85658341.72 | 0.203660E+09 | 0.545238E+09 | 90310159.06 |
April | 0.306149E+09 | 86007599.93 | 0.220141E+09 | 0.679969E+09 | 35647200.69 |
May | 0.344157E+09 | 0.103003E+09 | 0.241154E+09 | 0.972623E+09 | 2194110.37 |
June | 0.344056E+09 | 0.108404E+09 | 0.235652E+09 | 0.104673E+10 | 24985.47 |
July | 0.326083E+09 | 93121778.29 | 0.232961E+09 | 0.115511E+10 | 0.00 |
August | 0.334560E+09 | 0.101529E+09 | 0.233031E+09 | 0.117825E+10 | 0.00 |
September | 0.308518E+09 | 97057138.34 | 0.211461E+09 | 0.953795E+09 | 438617.60 |
October | 0.283567E+09 | 91929001.41 | 0.191638E+09 | 0.756716E+09 | 4258222.84 |
November | 0.235943E+09 | 77413695.10 | 0.158529E+09 | 0.509236E+09 | 45164015.20 |
December | 0.203311E+09 | 61210839.51 | 0.142101E+09 | 0.343628E+09 | 0.133421E+09 |
Annual Sum or Average | 0.341148E+10 | 0.103035E+10 | 0.238113E+10 | 0.883110E+10 | 0.620120E+09 |
Minimum of Months | 0.203311E+09 | 61210839.51 | 0.142101E+09 | 0.323388E+09 | 0.00 |
Maximum of Months | 0.344157E+09 | 0.108404E+09 | 0.241154E+09 | 0.117825E+10 | 0.183878E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 64598396.86 | 0.00 | 64598396.86 | 85228454.50 | 0.103470E+09 |
February | 66882322.40 | 0.00 | 66882322.40 | 0.103335E+09 | 72669702.90 |
March | 85067066.34 | 1019.81 | 85066046.53 | 0.164348E+09 | 53528970.98 |
April | 93053529.14 | 370879.84 | 92682649.30 | 0.233891E+09 | 19435096.92 |
May | 0.108093E+09 | 3314474.28 | 0.104779E+09 | 0.381626E+09 | 1128947.26 |
June | 0.111830E+09 | 6269529.39 | 0.105560E+09 | 0.430193E+09 | 15013.21 |
July | 0.106183E+09 | 3193498.36 | 0.102990E+09 | 0.493857E+09 | 0.00 |
August | 98920446.75 | 994666.35 | 97925780.39 | 0.484307E+09 | 0.00 |
September | 86998567.13 | 26467.21 | 86972099.92 | 0.368667E+09 | 287154.93 |
October | 79660604.55 | 0.00 | 79660604.55 | 0.275466E+09 | 2410892.01 |
November | 66180877.97 | 0.00 | 66180877.97 | 0.163659E+09 | 24294461.60 |
December | 60294245.24 | 0.00 | 60294245.24 | 96918141.20 | 75912798.60 |
Annual Sum or Average | 0.102776E+10 | 14170535.24 | 0.101359E+10 | 0.328150E+10 | 0.353153E+09 |
Minimum of Months | 60294245.24 | 0.00 | 60294245.24 | 85228454.50 | 0.00 |
Maximum of Months | 0.111830E+09 | 6269529.39 | 0.105560E+09 | 0.493857E+09 | 0.103470E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214599E+09 | 61728185.06 | 0.152871E+09 | 0.328383E+09 | 0.190914E+09 |
February | 0.221221E+09 | 63288497.46 | 0.157932E+09 | 0.366935E+09 | 0.133578E+09 |
March | 0.289318E+09 | 85658341.72 | 0.203660E+09 | 0.544780E+09 | 99099762.36 |
April | 0.306149E+09 | 86007599.93 | 0.220141E+09 | 0.677907E+09 | 36742615.07 |
May | 0.344157E+09 | 0.103003E+09 | 0.241154E+09 | 0.971675E+09 | 2346300.92 |
June | 0.344056E+09 | 0.108404E+09 | 0.235652E+09 | 0.104545E+10 | 25607.43 |
July | 0.326083E+09 | 93121778.29 | 0.232961E+09 | 0.115472E+10 | 0.00 |
August | 0.334560E+09 | 0.101529E+09 | 0.233031E+09 | 0.117971E+10 | 0.00 |
September | 0.308518E+09 | 97057138.34 | 0.211461E+09 | 0.958105E+09 | 499467.47 |
October | 0.283567E+09 | 91929001.41 | 0.191638E+09 | 0.763675E+09 | 4325298.97 |
November | 0.235943E+09 | 77413695.10 | 0.158529E+09 | 0.513991E+09 | 45040595.64 |
December | 0.203311E+09 | 61210839.51 | 0.142101E+09 | 0.347820E+09 | 0.140759E+09 |
Annual Sum or Average | 0.341148E+10 | 0.103035E+10 | 0.238113E+10 | 0.885314E+10 | 0.653330E+09 |
Minimum of Months | 0.203311E+09 | 61210839.51 | 0.142101E+09 | 0.328383E+09 | 0.00 |
Maximum of Months | 0.344157E+09 | 0.108404E+09 | 0.241154E+09 | 0.117971E+10 | 0.190914E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.307628E+09 | 0.145280E+09 | 0.162349E+09 | 0.496338E+09 | 0.138605E+09 |
February | 0.259749E+09 | 0.106237E+09 | 0.153512E+09 | 0.447772E+09 | 95265561.57 |
March | 0.234203E+09 | 61807290.10 | 0.172396E+09 | 0.464078E+09 | 69013702.86 |
April | 0.181003E+09 | 19991191.08 | 0.161011E+09 | 0.450761E+09 | 26508822.84 |
May | 0.158242E+09 | 2985850.27 | 0.155256E+09 | 0.577281E+09 | 1386966.53 |
June | 0.143624E+09 | 177620.59 | 0.143446E+09 | 0.607450E+09 | 1330.71 |
July | 0.148205E+09 | 980636.02 | 0.147224E+09 | 0.727218E+09 | 0.00 |
August | 0.171446E+09 | 11404171.32 | 0.160042E+09 | 0.788187E+09 | 0.00 |
September | 0.219925E+09 | 50570568.16 | 0.169354E+09 | 0.744743E+09 | 296130.06 |
October | 0.297663E+09 | 0.118640E+09 | 0.179023E+09 | 0.758110E+09 | 2982977.33 |
November | 0.318810E+09 | 0.154458E+09 | 0.164353E+09 | 0.648363E+09 | 33589813.38 |
December | 0.304859E+09 | 0.150864E+09 | 0.153995E+09 | 0.526041E+09 | 0.101270E+09 |
Annual Sum or Average | 0.274536E+10 | 0.823396E+09 | 0.192196E+10 | 0.723634E+10 | 0.468920E+09 |
Minimum of Months | 0.143624E+09 | 177620.59 | 0.143446E+09 | 0.447772E+09 | 0.00 |
Maximum of Months | 0.318810E+09 | 0.154458E+09 | 0.179023E+09 | 0.788187E+09 | 0.138605E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.452172E+09 | 0.00 | 0.452172E+09 | 0.497865E+09 | 0.100860E+10 |
February | 0.468159E+09 | 0.00 | 0.468159E+09 | 0.629581E+09 | 0.738772E+09 |
March | 0.595447E+09 | 7138.38 | 0.595440E+09 | 0.102475E+10 | 0.580088E+09 |
April | 0.651350E+09 | 2596060.55 | 0.648754E+09 | 0.147325E+10 | 0.301258E+09 |
May | 0.756625E+09 | 23200441.26 | 0.733424E+09 | 0.239015E+10 | 47592131.40 |
June | 0.782780E+09 | 43885043.59 | 0.738895E+09 | 0.270517E+10 | 3766748.17 |
July | 0.743256E+09 | 22353641.88 | 0.720902E+09 | 0.314570E+10 | 0.00 |
August | 0.692417E+09 | 6962400.77 | 0.685455E+09 | 0.308349E+10 | 0.00 |
September | 0.608967E+09 | 185263.48 | 0.608782E+09 | 0.227412E+10 | 13199451.23 |
October | 0.557603E+09 | 0.00 | 0.557603E+09 | 0.165185E+10 | 87344853.61 |
November | 0.463249E+09 | 0.00 | 0.463249E+09 | 0.983145E+09 | 0.357379E+09 |
December | 0.422044E+09 | 0.00 | 0.422044E+09 | 0.570891E+09 | 0.789572E+09 |
Annual Sum or Average | 0.719407E+10 | 99189989.90 | 0.709488E+10 | 0.204300E+11 | 0.392757E+10 |
Minimum of Months | 0.422044E+09 | 0.00 | 0.422044E+09 | 0.497865E+09 | 0.00 |
Maximum of Months | 0.782780E+09 | 43885043.59 | 0.738895E+09 | 0.314570E+10 | 0.100860E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.452172E+09 | 0.00 | 0.452172E+09 | 0.465696E+09 | 0.105751E+10 |
February | 0.468159E+09 | 0.00 | 0.468159E+09 | 0.600711E+09 | 0.775348E+09 |
March | 0.595447E+09 | 7138.38 | 0.595440E+09 | 0.992306E+09 | 0.610737E+09 |
April | 0.651350E+09 | 2596060.55 | 0.648754E+09 | 0.144366E+10 | 0.320002E+09 |
May | 0.756625E+09 | 23200441.26 | 0.733424E+09 | 0.235751E+10 | 52398658.36 |
June | 0.782780E+09 | 43885043.59 | 0.738895E+09 | 0.267132E+10 | 4581670.08 |
July | 0.743256E+09 | 22353641.88 | 0.720902E+09 | 0.311098E+10 | 0.00 |
August | 0.692417E+09 | 6962400.77 | 0.685455E+09 | 0.304882E+10 | 0.00 |
September | 0.608967E+09 | 185263.48 | 0.608782E+09 | 0.224085E+10 | 14916881.62 |
October | 0.557603E+09 | 0.00 | 0.557603E+09 | 0.162021E+10 | 95960518.94 |
November | 0.463249E+09 | 0.00 | 0.463249E+09 | 0.954843E+09 | 0.379385E+09 |
December | 0.422044E+09 | 0.00 | 0.422044E+09 | 0.541310E+09 | 0.830562E+09 |
Annual Sum or Average | 0.719407E+10 | 99189989.90 | 0.709488E+10 | 0.200482E+11 | 0.414140E+10 |
Minimum of Months | 0.422044E+09 | 0.00 | 0.422044E+09 | 0.465696E+09 | 0.00 |
Maximum of Months | 0.782780E+09 | 43885043.59 | 0.738895E+09 | 0.311098E+10 | 0.105751E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 64598396.86 | 0.00 | 64598396.86 | 87975519.82 | 0.137673E+09 |
February | 66882322.40 | 0.00 | 66882322.40 | 0.108772E+09 | 0.103535E+09 |
March | 85067066.34 | 1019.81 | 85066046.53 | 0.173108E+09 | 82166033.52 |
April | 93053529.14 | 370879.84 | 92682649.30 | 0.244534E+09 | 46695021.54 |
May | 0.108093E+09 | 3314474.28 | 0.104779E+09 | 0.380191E+09 | 10722962.69 |
June | 0.111830E+09 | 6269529.39 | 0.105560E+09 | 0.419021E+09 | 1362282.77 |
July | 0.106183E+09 | 3193498.36 | 0.102990E+09 | 0.482568E+09 | 0.00 |
August | 98920446.75 | 994666.35 | 97925780.39 | 0.472404E+09 | 0.00 |
September | 86998567.13 | 26467.21 | 86972099.92 | 0.356978E+09 | 2736917.15 |
October | 79660604.55 | 0.00 | 79660604.55 | 0.273639E+09 | 16631476.28 |
November | 66180877.97 | 0.00 | 66180877.97 | 0.173555E+09 | 52947063.77 |
December | 60294245.24 | 0.00 | 60294245.24 | 0.103346E+09 | 0.106750E+09 |
Annual Sum or Average | 0.102776E+10 | 14170535.24 | 0.101359E+10 | 0.327609E+10 | 0.561220E+09 |
Minimum of Months | 60294245.24 | 0.00 | 60294245.24 | 87975519.82 | 0.00 |
Maximum of Months | 0.111830E+09 | 6269529.39 | 0.105560E+09 | 0.482568E+09 | 0.137673E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.435591E+09 | 0.131379E+09 | 0.304212E+09 | 0.673142E+09 | 0.483144E+09 |
February | 0.429620E+09 | 0.116437E+09 | 0.313183E+09 | 0.732905E+09 | 0.367229E+09 |
March | 0.525856E+09 | 0.129711E+09 | 0.396145E+09 | 0.103593E+10 | 0.295269E+09 |
April | 0.619506E+09 | 0.180273E+09 | 0.439233E+09 | 0.143472E+10 | 0.172105E+09 |
May | 0.714257E+09 | 0.227460E+09 | 0.486797E+09 | 0.200570E+10 | 40445729.58 |
June | 0.677093E+09 | 0.206987E+09 | 0.470106E+09 | 0.204265E+10 | 5092093.60 |
July | 0.653120E+09 | 0.188191E+09 | 0.464929E+09 | 0.228726E+10 | 0.00 |
August | 0.668979E+09 | 0.205391E+09 | 0.463588E+09 | 0.232931E+10 | 0.00 |
September | 0.608272E+09 | 0.187903E+09 | 0.420369E+09 | 0.187257E+10 | 10382468.97 |
October | 0.570217E+09 | 0.186014E+09 | 0.384203E+09 | 0.154684E+10 | 62427962.42 |
November | 0.462255E+09 | 0.145992E+09 | 0.316264E+09 | 0.105871E+10 | 0.191258E+09 |
December | 0.387272E+09 | 0.106483E+09 | 0.280789E+09 | 0.684582E+09 | 0.380751E+09 |
Annual Sum or Average | 0.675204E+10 | 0.201222E+10 | 0.473982E+10 | 0.177043E+11 | 0.200811E+10 |
Minimum of Months | 0.387272E+09 | 0.106483E+09 | 0.280789E+09 | 0.673142E+09 | 0.00 |
Maximum of Months | 0.714257E+09 | 0.227460E+09 | 0.486797E+09 | 0.232931E+10 | 0.483144E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209757E+09 | 99059251.48 | 0.110698E+09 | 0.352942E+09 | 0.128634E+09 |
February | 0.177110E+09 | 72437614.58 | 0.104673E+09 | 0.316653E+09 | 99239518.51 |
March | 0.159692E+09 | 42143365.56 | 0.117548E+09 | 0.326137E+09 | 80999238.93 |
April | 0.123417E+09 | 13631014.60 | 0.109786E+09 | 0.312816E+09 | 47091996.49 |
May | 0.107897E+09 | 2035905.14 | 0.105861E+09 | 0.380044E+09 | 10981327.00 |
June | 97930013.93 | 121110.79 | 97808903.15 | 0.387431E+09 | 1380292.60 |
July | 0.101053E+09 | 668647.70 | 0.100385E+09 | 0.470452E+09 | 0.00 |
August | 0.116900E+09 | 7775946.17 | 0.109125E+09 | 0.513213E+09 | 0.00 |
September | 0.149956E+09 | 34481594.92 | 0.115474E+09 | 0.491059E+09 | 2732610.09 |
October | 0.202962E+09 | 80894729.87 | 0.122067E+09 | 0.517870E+09 | 16513574.31 |
November | 0.217381E+09 | 0.105317E+09 | 0.112064E+09 | 0.458430E+09 | 50866355.08 |
December | 0.207869E+09 | 0.102867E+09 | 0.105002E+09 | 0.375101E+09 | 0.101439E+09 |
Annual Sum or Average | 0.187192E+10 | 0.561433E+09 | 0.131049E+10 | 0.490215E+10 | 0.539877E+09 |
Minimum of Months | 97930013.93 | 121110.79 | 97808903.15 | 0.312816E+09 | 0.00 |
Maximum of Months | 0.217381E+09 | 0.105317E+09 | 0.122067E+09 | 0.517870E+09 | 0.128634E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 81809793.70 | 0.00 | 81809793.70 | 0.107926E+09 | 0.139414E+09 |
February | 84702241.28 | 0.00 | 84702241.28 | 0.130167E+09 | 0.101473E+09 |
March | 0.107732E+09 | 1291.52 | 0.107731E+09 | 0.203989E+09 | 79968566.03 |
April | 0.117846E+09 | 469695.92 | 0.117377E+09 | 0.281106E+09 | 41096256.36 |
May | 0.136893E+09 | 4197572.54 | 0.132696E+09 | 0.438674E+09 | 6339629.58 |
June | 0.141626E+09 | 7939963.38 | 0.133686E+09 | 0.494897E+09 | 409914.07 |
July | 0.134475E+09 | 4044364.17 | 0.130430E+09 | 0.572782E+09 | 0.00 |
August | 0.125277E+09 | 1259682.17 | 0.124017E+09 | 0.560771E+09 | 0.00 |
September | 0.110178E+09 | 33519.06 | 0.110145E+09 | 0.415153E+09 | 1759318.18 |
October | 0.100885E+09 | 0.00 | 0.100885E+09 | 0.303801E+09 | 11672074.89 |
November | 83813906.17 | 0.00 | 83813906.17 | 0.189151E+09 | 50146112.28 |
December | 76358857.24 | 0.00 | 76358857.24 | 0.119336E+09 | 0.108702E+09 |
Annual Sum or Average | 0.130160E+10 | 17946088.77 | 0.128365E+10 | 0.381775E+10 | 0.540981E+09 |
Minimum of Months | 76358857.24 | 0.00 | 76358857.24 | 0.107926E+09 | 0.00 |
Maximum of Months | 0.141626E+09 | 7939963.38 | 0.133686E+09 | 0.572782E+09 | 0.139414E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73195532.40 | 0.00 | 73195532.40 | 96561759.89 | 0.124731E+09 |
February | 75783416.21 | 0.00 | 75783416.21 | 0.116461E+09 | 90788722.36 |
March | 96388293.09 | 1155.53 | 96387137.56 | 0.182510E+09 | 71548179.03 |
April | 0.105438E+09 | 420238.72 | 0.105017E+09 | 0.251507E+09 | 36768976.28 |
May | 0.122479E+09 | 3755584.06 | 0.118723E+09 | 0.392483E+09 | 5672090.60 |
June | 0.126713E+09 | 7103915.32 | 0.119609E+09 | 0.442786E+09 | 366751.67 |
July | 0.120315E+09 | 3618507.95 | 0.116696E+09 | 0.512470E+09 | 0.00 |
August | 0.112085E+09 | 1127042.41 | 0.110958E+09 | 0.501724E+09 | 0.00 |
September | 98576849.40 | 29989.63 | 98546859.77 | 0.371439E+09 | 1574068.64 |
October | 90262307.49 | 0.00 | 90262307.49 | 0.271812E+09 | 10443636.52 |
November | 74988619.42 | 0.00 | 74988619.42 | 0.169234E+09 | 44866174.80 |
December | 68318558.89 | 0.00 | 68318558.89 | 0.106770E+09 | 97248584.86 |
Annual Sum or Average | 0.116454E+10 | 16056433.62 | 0.114849E+10 | 0.341576E+10 | 0.484009E+09 |
Minimum of Months | 68318558.89 | 0.00 | 68318558.89 | 96561759.89 | 0.00 |
Maximum of Months | 0.126713E+09 | 7103915.32 | 0.119609E+09 | 0.512470E+09 | 0.124731E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.783085E+09 | 0.369818E+09 | 0.413267E+09 | 0.128790E+10 | 0.381096E+09 |
February | 0.661205E+09 | 0.270431E+09 | 0.390774E+09 | 0.114345E+10 | 0.285676E+09 |
March | 0.596177E+09 | 0.157334E+09 | 0.438843E+09 | 0.115830E+10 | 0.233930E+09 |
April | 0.460752E+09 | 50888639.33 | 0.409863E+09 | 0.107411E+10 | 0.124573E+09 |
May | 0.402812E+09 | 7600640.56 | 0.395212E+09 | 0.128876E+10 | 20581676.60 |
June | 0.365602E+09 | 452142.65 | 0.365150E+09 | 0.134192E+10 | 1222934.66 |
July | 0.377262E+09 | 2496261.10 | 0.374766E+09 | 0.163858E+10 | 0.00 |
August | 0.436424E+09 | 29029924.17 | 0.407394E+09 | 0.179899E+10 | 0.00 |
September | 0.559830E+09 | 0.128730E+09 | 0.431100E+09 | 0.171205E+10 | 5067329.16 |
October | 0.757716E+09 | 0.302004E+09 | 0.455712E+09 | 0.178813E+10 | 33168029.26 |
November | 0.811549E+09 | 0.393180E+09 | 0.418369E+09 | 0.160099E+10 | 0.139904E+09 |
December | 0.776036E+09 | 0.384033E+09 | 0.392003E+09 | 0.134567E+10 | 0.301486E+09 |
Annual Sum or Average | 0.698845E+10 | 0.209600E+10 | 0.489245E+10 | 0.171789E+11 | 0.152671E+10 |
Minimum of Months | 0.365602E+09 | 452142.65 | 0.365150E+09 | 0.107411E+10 | 0.00 |
Maximum of Months | 0.811549E+09 | 0.393180E+09 | 0.455712E+09 | 0.179899E+10 | 0.381096E+09 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 642.12 | 197.83 | 396.09 | 187.06 | 209.03 | 0.00 | 0.00 |
February | 632.99 | 163.66 | 370.28 | 151.44 | 218.83 | 0.00 | 0.00 |
March | 575.35 | 122.22 | 301.55 | 79.58 | 221.97 | 0.00 | 0.00 |
April | 546.25 | 68.64 | 240.82 | 26.60 | 214.22 | 0.00 | 0.00 |
May | 613.28 | 11.85 | 203.74 | 3.84 | 199.90 | 0.00 | 0.00 |
June | 645.56 | 1.17 | 191.09 | 0.24 | 190.85 | 0.00 | 0.00 |
July | 763.19 | 0.00 | 190.82 | 1.26 | 189.56 | 0.00 | 0.00 |
August | 840.95 | 0.00 | 220.75 | 14.68 | 206.06 | 0.00 | 0.00 |
September | 842.67 | 3.71 | 292.60 | 67.28 | 225.32 | 0.00 | 0.00 |
October | 868.72 | 22.45 | 383.26 | 152.76 | 230.50 | 0.00 | 0.00 |
November | 812.83 | 84.40 | 424.17 | 205.50 | 218.67 | 0.00 | 0.00 |
December | 668.70 | 160.27 | 392.53 | 194.25 | 198.28 | 0.00 | 0.00 |
Annual Sum or Average | 704.89 | 69.24 | 300.22 | 90.04 | 210.17 | 0.00 | 0.00 |
Minimum of Months | 546.25 | 0.00 | 190.82 | 0.24 | 189.56 | 0.00 | 0.00 |
Maximum of Months | 868.72 | 197.83 | 424.17 | 205.50 | 230.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1755.53 | 659.44 | 1115.37 | 526.74 | 588.62 | 0.00 | 0.00 |
February | 1737.58 | 552.47 | 1042.67 | 426.45 | 616.22 | 0.00 | 0.00 |
March | 1584.85 | 414.81 | 849.15 | 224.09 | 625.05 | 0.00 | 0.00 |
April | 1513.09 | 238.83 | 678.13 | 74.90 | 603.23 | 0.00 | 0.00 |
May | 1726.03 | 43.23 | 573.73 | 10.83 | 562.91 | 0.00 | 0.00 |
June | 1825.82 | 4.80 | 538.09 | 0.67 | 537.42 | 0.00 | 0.00 |
July | 2159.72 | 0.00 | 537.34 | 3.56 | 533.78 | 0.00 | 0.00 |
August | 2376.65 | 0.00 | 621.61 | 41.35 | 580.26 | 0.00 | 0.00 |
September | 2368.09 | 13.72 | 823.96 | 189.47 | 634.49 | 0.00 | 0.00 |
October | 2431.25 | 77.53 | 1079.23 | 430.15 | 649.08 | 0.00 | 0.00 |
November | 2258.00 | 278.60 | 1194.44 | 578.68 | 615.75 | 0.00 | 0.00 |
December | 1838.18 | 537.36 | 1105.33 | 546.99 | 558.34 | 0.00 | 0.00 |
Annual Sum or Average | 1966.14 | 233.57 | 845.39 | 253.55 | 591.84 | 0.00 | 0.00 |
Minimum of Months | 1513.09 | 0.00 | 537.34 | 0.67 | 533.78 | 0.00 | 0.00 |
Maximum of Months | 2431.25 | 659.44 | 1194.44 | 578.68 | 649.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2327.16 | 887.65 | 1448.92 | 684.27 | 764.66 | 0.00 | 0.00 |
February | 2308.39 | 740.80 | 1354.49 | 553.99 | 800.51 | 0.00 | 0.00 |
March | 2107.74 | 555.29 | 1103.09 | 291.11 | 811.98 | 0.00 | 0.00 |
April | 2019.32 | 315.21 | 880.93 | 97.30 | 783.63 | 0.00 | 0.00 |
May | 2321.23 | 55.15 | 745.31 | 14.06 | 731.25 | 0.00 | 0.00 |
June | 2457.03 | 5.72 | 699.01 | 0.86 | 698.14 | 0.00 | 0.00 |
July | 2913.52 | 0.00 | 698.03 | 4.62 | 693.42 | 0.00 | 0.00 |
August | 3204.73 | 0.00 | 807.50 | 53.71 | 753.79 | 0.00 | 0.00 |
September | 3186.48 | 16.46 | 1070.37 | 246.13 | 824.24 | 0.00 | 0.00 |
October | 3260.34 | 94.97 | 1401.98 | 558.79 | 843.19 | 0.00 | 0.00 |
November | 3018.96 | 357.56 | 1551.64 | 751.74 | 799.90 | 0.00 | 0.00 |
December | 2440.93 | 716.30 | 1435.88 | 710.57 | 725.31 | 0.00 | 0.00 |
Annual Sum or Average | 2632.69 | 310.08 | 1098.21 | 329.38 | 768.83 | 0.00 | 0.00 |
Minimum of Months | 2019.32 | 0.00 | 698.03 | 0.86 | 693.42 | 0.00 | 0.00 |
Maximum of Months | 3260.34 | 887.65 | 1551.64 | 751.74 | 843.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 249.51 | 103.43 | 158.44 | 60.03 | 98.41 | 0.00 | 0.00 |
February | 280.81 | 79.78 | 164.65 | 56.10 | 108.55 | 0.00 | 0.00 |
March | 323.83 | 53.60 | 167.64 | 47.72 | 119.93 | 0.00 | 0.00 |
April | 380.56 | 22.75 | 165.73 | 38.44 | 127.29 | 0.00 | 0.00 |
May | 505.27 | 1.55 | 168.78 | 39.22 | 129.56 | 0.00 | 0.00 |
June | 556.67 | 0.02 | 170.52 | 41.87 | 128.65 | 0.00 | 0.00 |
July | 610.01 | 0.00 | 159.47 | 35.02 | 124.46 | 0.00 | 0.00 |
August | 634.53 | 0.00 | 168.56 | 40.81 | 127.75 | 0.00 | 0.00 |
September | 559.28 | 0.32 | 176.88 | 50.75 | 126.13 | 0.00 | 0.00 |
October | 473.21 | 2.87 | 181.65 | 64.52 | 117.12 | 0.00 | 0.00 |
November | 367.61 | 27.77 | 174.89 | 70.50 | 104.40 | 0.00 | 0.00 |
December | 264.27 | 76.13 | 153.52 | 61.26 | 92.26 | 0.00 | 0.00 |
Annual Sum or Average | 434.70 | 30.48 | 167.54 | 50.48 | 117.06 | 0.00 | 0.00 |
Minimum of Months | 249.51 | 0.00 | 153.52 | 35.02 | 92.26 | 0.00 | 0.00 |
Maximum of Months | 634.53 | 103.43 | 181.65 | 70.50 | 129.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 155.49 | 111.98 | 104.24 | 23.05 | 81.19 | 0.00 | 0.00 |
February | 195.94 | 86.78 | 119.09 | 26.16 | 92.93 | 0.00 | 0.00 |
March | 266.89 | 58.69 | 139.78 | 31.98 | 107.80 | 0.00 | 0.00 |
April | 353.29 | 23.34 | 154.01 | 33.33 | 120.69 | 0.00 | 0.00 |
May | 505.14 | 1.54 | 168.85 | 39.69 | 129.16 | 0.00 | 0.00 |
June | 568.28 | 0.03 | 175.88 | 44.24 | 131.64 | 0.00 | 0.00 |
July | 614.65 | 0.00 | 161.39 | 35.96 | 125.43 | 0.00 | 0.00 |
August | 620.40 | 0.00 | 161.84 | 38.28 | 123.57 | 0.00 | 0.00 |
September | 510.39 | 0.37 | 152.59 | 37.46 | 115.14 | 0.00 | 0.00 |
October | 386.36 | 3.05 | 135.61 | 34.32 | 101.29 | 0.00 | 0.00 |
November | 260.84 | 29.09 | 116.56 | 29.87 | 86.69 | 0.00 | 0.00 |
December | 166.79 | 83.50 | 98.42 | 22.85 | 75.57 | 0.00 | 0.00 |
Annual Sum or Average | 384.82 | 32.98 | 140.77 | 33.12 | 107.65 | 0.00 | 0.00 |
Minimum of Months | 155.49 | 0.00 | 98.42 | 22.85 | 75.57 | 0.00 | 0.00 |
Maximum of Months | 620.40 | 111.98 | 175.88 | 44.24 | 131.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 87.35 | 53.45 | 62.64 | 29.58 | 33.06 | 0.00 | 0.00 |
February | 87.00 | 46.68 | 58.56 | 23.95 | 34.61 | 0.00 | 0.00 |
March | 78.41 | 36.73 | 47.69 | 12.59 | 35.10 | 0.00 | 0.00 |
April | 74.40 | 23.66 | 38.08 | 4.21 | 33.88 | 0.00 | 0.00 |
May | 85.00 | 6.59 | 32.22 | 0.61 | 31.61 | 0.00 | 0.00 |
June | 89.77 | 1.93 | 30.22 | 0.04 | 30.18 | 0.00 | 0.00 |
July | 108.38 | 0.09 | 30.18 | 0.20 | 29.98 | 0.00 | 0.00 |
August | 120.85 | 0.04 | 34.91 | 2.32 | 32.59 | 0.00 | 0.00 |
September | 120.57 | 2.77 | 46.27 | 10.64 | 35.63 | 0.00 | 0.00 |
October | 126.42 | 10.44 | 60.61 | 24.16 | 36.45 | 0.00 | 0.00 |
November | 117.87 | 26.05 | 67.08 | 32.50 | 34.58 | 0.00 | 0.00 |
December | 93.19 | 45.03 | 62.08 | 30.72 | 31.36 | 0.00 | 0.00 |
Annual Sum or Average | 99.18 | 20.99 | 47.48 | 14.24 | 33.24 | 0.00 | 0.00 |
Minimum of Months | 74.40 | 0.04 | 30.18 | 0.04 | 29.98 | 0.00 | 0.00 |
Maximum of Months | 126.42 | 53.45 | 67.08 | 32.50 | 36.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 26.48 | 31.65 | 19.30 | 0.00 | 19.30 | 0.00 | 0.00 |
February | 36.09 | 23.89 | 22.12 | 0.00 | 22.12 | 0.00 | 0.00 |
March | 52.19 | 15.33 | 25.41 | 0.00 | 25.41 | 0.00 | 0.00 |
April | 76.80 | 5.42 | 28.72 | 0.11 | 28.61 | 0.00 | 0.00 |
May | 120.89 | 0.23 | 32.29 | 0.99 | 31.30 | 0.00 | 0.00 |
June | 140.30 | 0.00 | 34.52 | 1.94 | 32.58 | 0.00 | 0.00 |
July | 155.33 | 0.00 | 31.72 | 0.95 | 30.77 | 0.00 | 0.00 |
August | 152.65 | 0.00 | 29.55 | 0.30 | 29.25 | 0.00 | 0.00 |
September | 120.75 | 0.06 | 26.85 | 0.01 | 26.85 | 0.00 | 0.00 |
October | 87.85 | 0.54 | 23.80 | 0.00 | 23.80 | 0.00 | 0.00 |
November | 53.79 | 6.98 | 20.43 | 0.00 | 20.43 | 0.00 | 0.00 |
December | 30.32 | 22.94 | 18.01 | 0.00 | 18.01 | 0.00 | 0.00 |
Annual Sum or Average | 88.10 | 8.86 | 26.08 | 0.36 | 25.72 | 0.00 | 0.00 |
Minimum of Months | 26.48 | 0.00 | 18.01 | 0.00 | 18.01 | 0.00 | 0.00 |
Maximum of Months | 155.33 | 31.65 | 34.52 | 1.94 | 32.58 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 248.40 | 99.47 | 159.64 | 61.51 | 98.12 | 0.00 | 0.00 |
February | 273.29 | 75.89 | 162.01 | 54.01 | 108.00 | 0.00 | 0.00 |
March | 304.62 | 50.10 | 157.80 | 39.95 | 117.84 | 0.00 | 0.00 |
April | 384.58 | 21.35 | 167.13 | 40.04 | 127.09 | 0.00 | 0.00 |
May | 515.55 | 1.39 | 173.63 | 43.23 | 130.41 | 0.00 | 0.00 |
June | 554.53 | 0.02 | 168.40 | 39.98 | 128.43 | 0.00 | 0.00 |
July | 612.58 | 0.00 | 159.66 | 35.38 | 124.28 | 0.00 | 0.00 |
August | 635.73 | 0.00 | 168.54 | 41.25 | 127.29 | 0.00 | 0.00 |
September | 557.64 | 0.33 | 175.20 | 49.55 | 125.65 | 0.00 | 0.00 |
October | 475.97 | 2.85 | 182.23 | 64.93 | 117.30 | 0.00 | 0.00 |
November | 364.98 | 27.11 | 173.04 | 68.80 | 104.25 | 0.00 | 0.00 |
December | 256.17 | 73.77 | 149.91 | 58.29 | 91.62 | 0.00 | 0.00 |
Annual Sum or Average | 432.94 | 29.16 | 166.42 | 49.71 | 116.71 | 0.00 | 0.00 |
Minimum of Months | 248.40 | 0.00 | 149.91 | 35.38 | 91.62 | 0.00 | 0.00 |
Maximum of Months | 635.73 | 99.47 | 182.23 | 68.80 | 130.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 150.67 | 104.01 | 105.44 | 24.53 | 80.91 | 0.00 | 0.00 |
February | 186.83 | 81.17 | 116.45 | 24.07 | 92.38 | 0.00 | 0.00 |
March | 246.80 | 54.14 | 129.93 | 24.22 | 105.72 | 0.00 | 0.00 |
April | 356.20 | 21.74 | 155.41 | 34.92 | 120.49 | 0.00 | 0.00 |
May | 515.26 | 1.40 | 173.70 | 43.70 | 130.00 | 0.00 | 0.00 |
June | 566.12 | 0.02 | 173.77 | 42.35 | 131.42 | 0.00 | 0.00 |
July | 617.24 | 0.00 | 161.58 | 36.33 | 125.25 | 0.00 | 0.00 |
August | 621.61 | 0.00 | 161.83 | 38.72 | 123.11 | 0.00 | 0.00 |
September | 508.69 | 0.36 | 150.91 | 36.26 | 114.65 | 0.00 | 0.00 |
October | 388.56 | 2.81 | 136.20 | 34.73 | 101.47 | 0.00 | 0.00 |
November | 255.09 | 26.88 | 114.71 | 28.16 | 86.54 | 0.00 | 0.00 |
December | 155.17 | 77.82 | 94.81 | 19.88 | 74.93 | 0.00 | 0.00 |
Annual Sum or Average | 381.83 | 30.65 | 139.65 | 32.36 | 107.30 | 0.00 | 0.00 |
Minimum of Months | 150.67 | 0.00 | 94.81 | 19.88 | 74.93 | 0.00 | 0.00 |
Maximum of Months | 621.61 | 104.01 | 173.77 | 43.70 | 131.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 281.36 | 136.21 | 177.53 | 64.10 | 113.43 | 0.00 | 0.00 |
February | 299.92 | 111.70 | 174.80 | 51.89 | 122.90 | 0.00 | 0.00 |
March | 315.03 | 80.21 | 158.38 | 27.27 | 131.11 | 0.00 | 0.00 |
April | 355.04 | 41.15 | 144.74 | 9.36 | 135.38 | 0.00 | 0.00 |
May | 464.66 | 5.79 | 139.77 | 3.46 | 136.30 | 0.00 | 0.00 |
June | 518.00 | 0.31 | 140.26 | 4.27 | 135.99 | 0.00 | 0.00 |
July | 594.03 | 0.00 | 134.10 | 2.50 | 131.60 | 0.00 | 0.00 |
August | 615.46 | 0.00 | 139.65 | 5.68 | 133.98 | 0.00 | 0.00 |
September | 541.67 | 1.61 | 158.44 | 23.07 | 135.37 | 0.00 | 0.00 |
October | 478.53 | 10.79 | 182.88 | 52.34 | 130.53 | 0.00 | 0.00 |
November | 394.85 | 50.45 | 189.60 | 70.42 | 119.18 | 0.00 | 0.00 |
December | 297.90 | 107.59 | 173.52 | 66.56 | 106.96 | 0.00 | 0.00 |
Annual Sum or Average | 430.52 | 45.18 | 159.36 | 31.63 | 127.73 | 0.00 | 0.00 |
Minimum of Months | 281.36 | 0.00 | 134.10 | 2.50 | 106.96 | 0.00 | 0.00 |
Maximum of Months | 615.46 | 136.21 | 189.60 | 70.42 | 136.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 246.83 | 101.06 | 158.44 | 60.03 | 98.41 | 0.00 | 0.00 |
February | 277.79 | 77.55 | 164.65 | 56.10 | 108.55 | 0.00 | 0.00 |
March | 320.84 | 51.56 | 167.64 | 47.72 | 119.93 | 0.00 | 0.00 |
April | 378.41 | 21.22 | 165.73 | 38.44 | 127.29 | 0.00 | 0.00 |
May | 505.29 | 1.28 | 168.78 | 39.22 | 129.56 | 0.00 | 0.00 |
June | 558.00 | 0.01 | 170.52 | 41.87 | 128.65 | 0.00 | 0.00 |
July | 610.73 | 0.00 | 159.47 | 35.02 | 124.46 | 0.00 | 0.00 |
August | 635.11 | 0.00 | 168.56 | 40.81 | 127.75 | 0.00 | 0.00 |
September | 559.99 | 0.26 | 176.88 | 50.75 | 126.13 | 0.00 | 0.00 |
October | 473.57 | 2.40 | 181.65 | 64.52 | 117.12 | 0.00 | 0.00 |
November | 366.47 | 25.79 | 174.89 | 70.50 | 104.40 | 0.00 | 0.00 |
December | 262.07 | 73.69 | 153.52 | 61.26 | 92.26 | 0.00 | 0.00 |
Annual Sum or Average | 433.84 | 29.37 | 167.54 | 50.48 | 117.06 | 0.00 | 0.00 |
Minimum of Months | 246.83 | 0.00 | 153.52 | 35.02 | 92.26 | 0.00 | 0.00 |
Maximum of Months | 635.11 | 101.06 | 181.65 | 70.50 | 129.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 153.94 | 109.43 | 104.24 | 23.05 | 81.19 | 0.00 | 0.00 |
February | 193.94 | 84.81 | 119.09 | 26.16 | 92.93 | 0.00 | 0.00 |
March | 264.65 | 56.88 | 139.78 | 31.98 | 107.80 | 0.00 | 0.00 |
April | 351.73 | 21.63 | 154.01 | 33.33 | 120.69 | 0.00 | 0.00 |
May | 505.23 | 1.27 | 168.85 | 39.69 | 129.16 | 0.00 | 0.00 |
June | 569.31 | 0.02 | 175.88 | 44.24 | 131.64 | 0.00 | 0.00 |
July | 615.51 | 0.00 | 161.39 | 35.96 | 125.43 | 0.00 | 0.00 |
August | 621.27 | 0.00 | 161.84 | 38.28 | 123.57 | 0.00 | 0.00 |
September | 511.87 | 0.30 | 152.59 | 37.46 | 115.14 | 0.00 | 0.00 |
October | 387.97 | 2.51 | 135.61 | 34.32 | 101.29 | 0.00 | 0.00 |
November | 261.44 | 26.75 | 116.56 | 29.87 | 86.69 | 0.00 | 0.00 |
December | 165.91 | 80.76 | 98.42 | 22.85 | 75.57 | 0.00 | 0.00 |
Annual Sum or Average | 384.68 | 31.81 | 140.77 | 33.12 | 107.65 | 0.00 | 0.00 |
Minimum of Months | 153.94 | 0.00 | 98.42 | 22.85 | 75.57 | 0.00 | 0.00 |
Maximum of Months | 621.27 | 109.43 | 175.88 | 44.24 | 131.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 185.31 | 51.75 | 114.86 | 54.24 | 60.61 | 0.00 | 0.00 |
February | 185.09 | 39.38 | 107.37 | 43.91 | 63.46 | 0.00 | 0.00 |
March | 173.27 | 25.77 | 87.44 | 23.08 | 64.37 | 0.00 | 0.00 |
April | 173.90 | 10.23 | 69.83 | 7.71 | 62.12 | 0.00 | 0.00 |
May | 215.53 | 0.52 | 59.08 | 1.11 | 57.97 | 0.00 | 0.00 |
June | 234.36 | 0.00 | 55.41 | 0.07 | 55.34 | 0.00 | 0.00 |
July | 271.51 | 0.00 | 55.33 | 0.37 | 54.97 | 0.00 | 0.00 |
August | 294.28 | 0.00 | 64.01 | 4.26 | 59.75 | 0.00 | 0.00 |
September | 287.32 | 0.11 | 84.85 | 19.51 | 65.34 | 0.00 | 0.00 |
October | 283.05 | 1.11 | 111.13 | 44.30 | 66.84 | 0.00 | 0.00 |
November | 250.14 | 12.96 | 123.00 | 59.59 | 63.41 | 0.00 | 0.00 |
December | 196.40 | 37.81 | 113.82 | 56.33 | 57.50 | 0.00 | 0.00 |
Annual Sum or Average | 229.46 | 14.87 | 87.05 | 26.11 | 60.94 | 0.00 | 0.00 |
Minimum of Months | 173.27 | 0.00 | 55.33 | 0.07 | 54.97 | 0.00 | 0.00 |
Maximum of Months | 294.28 | 51.75 | 123.00 | 59.59 | 66.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 185.88 | 376.57 | 168.82 | 0.00 | 168.82 | 0.00 | 0.00 |
February | 260.24 | 305.38 | 193.52 | 0.00 | 193.52 | 0.00 | 0.00 |
March | 382.60 | 216.58 | 222.31 | 0.00 | 222.31 | 0.00 | 0.00 |
April | 568.38 | 116.23 | 251.29 | 1.00 | 250.29 | 0.00 | 0.00 |
May | 892.38 | 17.77 | 282.49 | 8.66 | 273.83 | 0.00 | 0.00 |
June | 1043.66 | 1.45 | 302.00 | 16.93 | 285.07 | 0.00 | 0.00 |
July | 1174.47 | 0.00 | 277.50 | 8.35 | 269.15 | 0.00 | 0.00 |
August | 1151.24 | 0.00 | 258.52 | 2.60 | 255.92 | 0.00 | 0.00 |
September | 877.36 | 5.09 | 234.94 | 0.07 | 234.87 | 0.00 | 0.00 |
October | 616.73 | 32.61 | 208.19 | 0.00 | 208.19 | 0.00 | 0.00 |
November | 379.30 | 137.88 | 178.72 | 0.00 | 178.72 | 0.00 | 0.00 |
December | 213.15 | 294.79 | 157.57 | 0.00 | 157.57 | 0.00 | 0.00 |
Annual Sum or Average | 647.83 | 124.54 | 228.12 | 3.15 | 224.98 | 0.00 | 0.00 |
Minimum of Months | 185.88 | 0.00 | 157.57 | 0.00 | 157.57 | 0.00 | 0.00 |
Maximum of Months | 1174.47 | 376.57 | 302.00 | 16.93 | 285.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 173.87 | 394.83 | 168.82 | 0.00 | 168.82 | 0.00 | 0.00 |
February | 248.31 | 320.50 | 193.52 | 0.00 | 193.52 | 0.00 | 0.00 |
March | 370.48 | 228.02 | 222.31 | 0.00 | 222.31 | 0.00 | 0.00 |
April | 556.97 | 123.46 | 251.29 | 1.00 | 250.29 | 0.00 | 0.00 |
May | 880.19 | 19.56 | 282.49 | 8.66 | 273.83 | 0.00 | 0.00 |
June | 1030.60 | 1.77 | 302.00 | 16.93 | 285.07 | 0.00 | 0.00 |
July | 1161.51 | 0.00 | 277.50 | 8.35 | 269.15 | 0.00 | 0.00 |
August | 1138.30 | 0.00 | 258.52 | 2.60 | 255.92 | 0.00 | 0.00 |
September | 864.52 | 5.75 | 234.94 | 0.07 | 234.87 | 0.00 | 0.00 |
October | 604.92 | 35.83 | 208.19 | 0.00 | 208.19 | 0.00 | 0.00 |
November | 368.38 | 146.37 | 178.72 | 0.00 | 178.72 | 0.00 | 0.00 |
December | 202.10 | 310.10 | 157.57 | 0.00 | 157.57 | 0.00 | 0.00 |
Annual Sum or Average | 635.72 | 131.32 | 228.12 | 3.15 | 224.98 | 0.00 | 0.00 |
Minimum of Months | 173.87 | 0.00 | 157.57 | 0.00 | 157.57 | 0.00 | 0.00 |
Maximum of Months | 1161.51 | 394.83 | 302.00 | 16.93 | 285.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 412.32 | 276.19 | 265.06 | 86.04 | 179.03 | 0.00 | 0.00 |
February | 476.26 | 233.07 | 278.44 | 78.07 | 200.37 | 0.00 | 0.00 |
March | 571.54 | 169.53 | 287.71 | 64.16 | 223.55 | 0.00 | 0.00 |
April | 767.90 | 101.94 | 322.52 | 74.95 | 247.57 | 0.00 | 0.00 |
May | 1032.59 | 23.11 | 347.31 | 86.92 | 260.39 | 0.00 | 0.00 |
June | 1099.19 | 3.02 | 342.15 | 82.32 | 259.83 | 0.00 | 0.00 |
July | 1209.78 | 0.00 | 321.22 | 71.70 | 249.52 | 0.00 | 0.00 |
August | 1237.65 | 0.00 | 330.35 | 79.96 | 250.39 | 0.00 | 0.00 |
September | 1049.62 | 6.12 | 326.09 | 85.81 | 240.28 | 0.00 | 0.00 |
October | 872.98 | 35.63 | 318.41 | 99.65 | 218.76 | 0.00 | 0.00 |
November | 651.45 | 113.01 | 287.74 | 96.96 | 190.78 | 0.00 | 0.00 |
December | 432.26 | 217.92 | 244.71 | 78.16 | 166.55 | 0.00 | 0.00 |
Annual Sum or Average | 819.79 | 97.65 | 306.05 | 82.06 | 223.99 | 0.00 | 0.00 |
Minimum of Months | 412.32 | 0.00 | 244.71 | 64.16 | 166.55 | 0.00 | 0.00 |
Maximum of Months | 1237.65 | 276.19 | 347.31 | 99.65 | 260.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 552.79 | 236.50 | 350.24 | 138.07 | 212.17 | 0.00 | 0.00 |
February | 573.27 | 196.23 | 339.65 | 111.79 | 227.87 | 0.00 | 0.00 |
March | 576.63 | 143.78 | 298.80 | 58.74 | 240.05 | 0.00 | 0.00 |
April | 619.80 | 78.02 | 263.90 | 19.98 | 243.93 | 0.00 | 0.00 |
May | 791.31 | 12.00 | 247.23 | 5.81 | 241.42 | 0.00 | 0.00 |
June | 879.46 | 0.76 | 244.58 | 5.98 | 238.60 | 0.00 | 0.00 |
July | 1016.96 | 0.00 | 235.98 | 3.79 | 232.19 | 0.00 | 0.00 |
August | 1068.36 | 0.00 | 251.56 | 11.73 | 239.83 | 0.00 | 0.00 |
September | 963.98 | 3.24 | 296.52 | 49.69 | 246.83 | 0.00 | 0.00 |
October | 882.30 | 20.42 | 354.27 | 112.76 | 241.51 | 0.00 | 0.00 |
November | 754.50 | 89.20 | 374.36 | 151.69 | 222.67 | 0.00 | 0.00 |
December | 583.93 | 186.55 | 343.75 | 143.38 | 200.37 | 0.00 | 0.00 |
Annual Sum or Average | 773.22 | 80.02 | 299.80 | 67.54 | 232.26 | 0.00 | 0.00 |
Minimum of Months | 552.79 | 0.00 | 235.98 | 3.79 | 200.37 | 0.00 | 0.00 |
Maximum of Months | 1068.36 | 236.50 | 374.36 | 151.69 | 246.83 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.171986E+10 | 0.529870E+09 | 0.106089E+10 | 0.501015E+09 | 0.559875E+09 | 0.00 | 0.00 |
February | 0.153133E+10 | 0.395918E+09 | 0.895772E+09 | 0.366370E+09 | 0.529403E+09 | 0.00 | 0.00 |
March | 0.154103E+10 | 0.327342E+09 | 0.807673E+09 | 0.213150E+09 | 0.594524E+09 | 0.00 | 0.00 |
April | 0.141588E+10 | 0.177909E+09 | 0.624204E+09 | 68941985.48 | 0.555262E+09 | 0.00 | 0.00 |
May | 0.164261E+10 | 31750396.03 | 0.545709E+09 | 10297057.61 | 0.535412E+09 | 0.00 | 0.00 |
June | 0.167329E+10 | 3032078.23 | 0.495298E+09 | 612545.60 | 0.494685E+09 | 0.00 | 0.00 |
July | 0.204413E+10 | 0.00 | 0.511095E+09 | 3381839.23 | 0.507713E+09 | 0.00 | 0.00 |
August | 0.225241E+10 | 0.00 | 0.591245E+09 | 39328632.82 | 0.551917E+09 | 0.00 | 0.00 |
September | 0.218420E+10 | 9628725.11 | 0.758432E+09 | 0.174399E+09 | 0.584033E+09 | 0.00 | 0.00 |
October | 0.232679E+10 | 60137580.46 | 0.102652E+10 | 0.409144E+09 | 0.617377E+09 | 0.00 | 0.00 |
November | 0.210687E+10 | 0.218771E+09 | 0.109945E+10 | 0.532665E+09 | 0.566787E+09 | 0.00 | 0.00 |
December | 0.179105E+10 | 0.429254E+09 | 0.105134E+10 | 0.520273E+09 | 0.531067E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.222294E+11 | 0.218361E+10 | 0.946763E+10 | 0.283958E+10 | 0.662805E+10 | 0.00 | 0.00 |
Minimum of Months | 0.141588E+10 | 0.00 | 0.495298E+09 | 612545.60 | 0.494685E+09 | 0.00 | 0.00 |
Maximum of Months | 0.232679E+10 | 0.529870E+09 | 0.109945E+10 | 0.532665E+09 | 0.617377E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.470200E+10 | 0.176625E+10 | 0.298740E+10 | 0.141082E+10 | 0.157657E+10 | 0.00 | 0.00 |
February | 0.420356E+10 | 0.133652E+10 | 0.252244E+10 | 0.103167E+10 | 0.149076E+10 | 0.00 | 0.00 |
March | 0.424485E+10 | 0.111103E+10 | 0.227435E+10 | 0.600216E+09 | 0.167414E+10 | 0.00 | 0.00 |
April | 0.392193E+10 | 0.619054E+09 | 0.175772E+10 | 0.194136E+09 | 0.156358E+10 | 0.00 | 0.00 |
May | 0.462300E+10 | 0.115796E+09 | 0.153668E+10 | 28995835.30 | 0.150769E+10 | 0.00 | 0.00 |
June | 0.473254E+10 | 12435306.80 | 0.139473E+10 | 1724888.02 | 0.139300E+10 | 0.00 | 0.00 |
July | 0.578459E+10 | 0.00 | 0.143921E+10 | 9523036.29 | 0.142969E+10 | 0.00 | 0.00 |
August | 0.636561E+10 | 0.00 | 0.166491E+10 | 0.110747E+09 | 0.155416E+10 | 0.00 | 0.00 |
September | 0.613810E+10 | 35569440.83 | 0.213569E+10 | 0.491095E+09 | 0.164460E+10 | 0.00 | 0.00 |
October | 0.651186E+10 | 0.207670E+09 | 0.289061E+10 | 0.115212E+10 | 0.173849E+10 | 0.00 | 0.00 |
November | 0.585273E+10 | 0.722143E+09 | 0.309598E+10 | 0.149995E+10 | 0.159603E+10 | 0.00 | 0.00 |
December | 0.492339E+10 | 0.143926E+10 | 0.296051E+10 | 0.146506E+10 | 0.149545E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.620042E+11 | 0.736573E+10 | 0.266602E+11 | 0.799606E+10 | 0.186642E+11 | 0.00 | 0.00 |
Minimum of Months | 0.392193E+10 | 0.00 | 0.139473E+10 | 1724888.02 | 0.139300E+10 | 0.00 | 0.00 |
Maximum of Months | 0.651186E+10 | 0.176625E+10 | 0.309598E+10 | 0.149995E+10 | 0.173849E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.623306E+10 | 0.237748E+10 | 0.388080E+10 | 0.183274E+10 | 0.204806E+10 | 0.00 | 0.00 |
February | 0.558446E+10 | 0.179215E+10 | 0.327679E+10 | 0.134020E+10 | 0.193659E+10 | 0.00 | 0.00 |
March | 0.564538E+10 | 0.148729E+10 | 0.295452E+10 | 0.779714E+09 | 0.217480E+10 | 0.00 | 0.00 |
April | 0.523408E+10 | 0.817017E+09 | 0.228337E+10 | 0.252194E+09 | 0.203118E+10 | 0.00 | 0.00 |
May | 0.621719E+10 | 0.147703E+09 | 0.199624E+10 | 37667240.23 | 0.195857E+10 | 0.00 | 0.00 |
June | 0.636861E+10 | 14816050.70 | 0.181183E+10 | 2240727.70 | 0.180959E+10 | 0.00 | 0.00 |
July | 0.780357E+10 | 0.00 | 0.186962E+10 | 12370966.10 | 0.185724E+10 | 0.00 | 0.00 |
August | 0.858354E+10 | 0.00 | 0.216281E+10 | 0.143866E+09 | 0.201894E+10 | 0.00 | 0.00 |
September | 0.825936E+10 | 42652682.86 | 0.277439E+10 | 0.637960E+09 | 0.213643E+10 | 0.00 | 0.00 |
October | 0.873248E+10 | 0.254369E+09 | 0.375507E+10 | 0.149667E+10 | 0.225840E+10 | 0.00 | 0.00 |
November | 0.782514E+10 | 0.926790E+09 | 0.402186E+10 | 0.194852E+10 | 0.207334E+10 | 0.00 | 0.00 |
December | 0.653780E+10 | 0.191855E+10 | 0.384587E+10 | 0.190319E+10 | 0.194267E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.830247E+11 | 0.977883E+10 | 0.346332E+11 | 0.103873E+11 | 0.242458E+11 | 0.00 | 0.00 |
Minimum of Months | 0.523408E+10 | 0.00 | 0.181183E+10 | 2240727.70 | 0.180959E+10 | 0.00 | 0.00 |
Maximum of Months | 0.873248E+10 | 0.237748E+10 | 0.402186E+10 | 0.194852E+10 | 0.225840E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.668300E+09 | 0.277037E+09 | 0.424356E+09 | 0.160787E+09 | 0.263569E+09 | 0.00 | 0.00 |
February | 0.679330E+09 | 0.192994E+09 | 0.398331E+09 | 0.135726E+09 | 0.262605E+09 | 0.00 | 0.00 |
March | 0.867345E+09 | 0.143567E+09 | 0.449010E+09 | 0.127802E+09 | 0.321208E+09 | 0.00 | 0.00 |
April | 0.986420E+09 | 58961120.46 | 0.429565E+09 | 99638614.52 | 0.329927E+09 | 0.00 | 0.00 |
May | 0.135332E+10 | 4153660.82 | 0.452054E+09 | 0.105038E+09 | 0.347016E+09 | 0.00 | 0.00 |
June | 0.144290E+10 | 64251.75 | 0.441986E+09 | 0.108525E+09 | 0.333461E+09 | 0.00 | 0.00 |
July | 0.163384E+10 | 0.00 | 0.427136E+09 | 93790425.99 | 0.333345E+09 | 0.00 | 0.00 |
August | 0.169952E+10 | 0.00 | 0.451461E+09 | 0.109305E+09 | 0.342155E+09 | 0.00 | 0.00 |
September | 0.144965E+10 | 826445.02 | 0.458474E+09 | 0.131539E+09 | 0.326936E+09 | 0.00 | 0.00 |
October | 0.126745E+10 | 7674827.94 | 0.486529E+09 | 0.172824E+09 | 0.313705E+09 | 0.00 | 0.00 |
November | 0.952848E+09 | 71984395.39 | 0.453324E+09 | 0.182731E+09 | 0.270593E+09 | 0.00 | 0.00 |
December | 0.707818E+09 | 0.203903E+09 | 0.411180E+09 | 0.164078E+09 | 0.247102E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.137087E+11 | 0.961165E+09 | 0.528341E+10 | 0.159178E+10 | 0.369162E+10 | 0.00 | 0.00 |
Minimum of Months | 0.668300E+09 | 0.00 | 0.398331E+09 | 93790425.99 | 0.247102E+09 | 0.00 | 0.00 |
Maximum of Months | 0.169952E+10 | 0.277037E+09 | 0.486529E+09 | 0.182731E+09 | 0.347016E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.416476E+09 | 0.299917E+09 | 0.279198E+09 | 61728185.06 | 0.217469E+09 | 0.00 | 0.00 |
February | 0.474017E+09 | 0.209933E+09 | 0.288103E+09 | 63288497.46 | 0.224814E+09 | 0.00 | 0.00 |
March | 0.714830E+09 | 0.157194E+09 | 0.374385E+09 | 85659361.53 | 0.288726E+09 | 0.00 | 0.00 |
April | 0.915738E+09 | 60504205.39 | 0.399202E+09 | 86378479.77 | 0.312824E+09 | 0.00 | 0.00 |
May | 0.135297E+10 | 4112191.28 | 0.452250E+09 | 0.106317E+09 | 0.345933E+09 | 0.00 | 0.00 |
June | 0.147298E+10 | 67209.18 | 0.455886E+09 | 0.114674E+09 | 0.341212E+09 | 0.00 | 0.00 |
July | 0.164628E+10 | 0.00 | 0.432266E+09 | 96315276.65 | 0.335951E+09 | 0.00 | 0.00 |
August | 0.166168E+10 | 0.00 | 0.433481E+09 | 0.102524E+09 | 0.330957E+09 | 0.00 | 0.00 |
September | 0.132293E+10 | 965740.29 | 0.395517E+09 | 97083605.56 | 0.298433E+09 | 0.00 | 0.00 |
October | 0.103483E+10 | 8173408.07 | 0.363228E+09 | 91929001.41 | 0.271299E+09 | 0.00 | 0.00 |
November | 0.676088E+09 | 75403190.98 | 0.302124E+09 | 77413695.10 | 0.224710E+09 | 0.00 | 0.00 |
December | 0.446729E+09 | 0.223634E+09 | 0.263606E+09 | 61210839.51 | 0.202395E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.121355E+11 | 0.103990E+10 | 0.443925E+10 | 0.104452E+10 | 0.339472E+10 | 0.00 | 0.00 |
Minimum of Months | 0.416476E+09 | 0.00 | 0.263606E+09 | 61210839.51 | 0.202395E+09 | 0.00 | 0.00 |
Maximum of Months | 0.166168E+10 | 0.299917E+09 | 0.455886E+09 | 0.114674E+09 | 0.345933E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.233963E+09 | 0.143149E+09 | 0.167772E+09 | 79231644.14 | 88540435.51 | 0.00 | 0.00 |
February | 0.210481E+09 | 0.112937E+09 | 0.141660E+09 | 57938569.24 | 83721463.90 | 0.00 | 0.00 |
March | 0.210008E+09 | 98375234.82 | 0.127728E+09 | 33707988.83 | 94020020.17 | 0.00 | 0.00 |
April | 0.192850E+09 | 61323165.71 | 98713829.41 | 10902643.44 | 87811185.97 | 0.00 | 0.00 |
May | 0.227669E+09 | 17651746.77 | 86300615.81 | 1628400.27 | 84672215.54 | 0.00 | 0.00 |
June | 0.232689E+09 | 5011759.11 | 78328433.73 | 96869.36 | 78231564.37 | 0.00 | 0.00 |
July | 0.290291E+09 | 251510.50 | 80826650.48 | 534811.80 | 80291838.68 | 0.00 | 0.00 |
August | 0.323697E+09 | 104780.22 | 93501784.60 | 6219520.04 | 87282264.56 | 0.00 | 0.00 |
September | 0.312515E+09 | 7177562.47 | 0.119941E+09 | 27579791.06 | 92361105.18 | 0.00 | 0.00 |
October | 0.338610E+09 | 27964156.41 | 0.162337E+09 | 64702916.23 | 97634093.70 | 0.00 | 0.00 |
November | 0.305511E+09 | 67528741.18 | 0.173870E+09 | 84236921.85 | 89633479.97 | 0.00 | 0.00 |
December | 0.249588E+09 | 0.120604E+09 | 0.166262E+09 | 82277240.17 | 83984635.32 | 0.00 | 0.00 |
Annual Sum or Average | 0.312787E+10 | 0.662078E+09 | 0.149724E+10 | 0.449057E+09 | 0.104818E+10 | 0.00 | 0.00 |
Minimum of Months | 0.192850E+09 | 104780.22 | 78328433.73 | 96869.36 | 78231564.37 | 0.00 | 0.00 |
Maximum of Months | 0.338610E+09 | 0.143149E+09 | 0.173870E+09 | 84236921.85 | 97634093.70 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 70911354.21 | 84777543.15 | 51685567.80 | 0.00 | 51685567.80 | 0.00 | 0.00 |
February | 87315563.09 | 57797889.96 | 53512950.43 | 0.00 | 53512950.43 | 0.00 | 0.00 |
March | 0.139785E+09 | 41068162.38 | 68062673.97 | 815.95 | 68061858.01 | 0.00 | 0.00 |
April | 0.199070E+09 | 14054183.68 | 74452691.13 | 296743.20 | 74155947.93 | 0.00 | 0.00 |
May | 0.323791E+09 | 605504.30 | 86486126.04 | 2651930.91 | 83834195.14 | 0.00 | 0.00 |
June | 0.363665E+09 | 529.18 | 89475839.67 | 5016288.36 | 84459551.31 | 0.00 | 0.00 |
July | 0.416037E+09 | 0.00 | 84957971.33 | 2555137.34 | 82402833.99 | 0.00 | 0.00 |
August | 0.408863E+09 | 0.00 | 79146847.37 | 795838.56 | 78351008.81 | 0.00 | 0.00 |
September | 0.312995E+09 | 145856.44 | 69608079.43 | 21176.58 | 69586902.85 | 0.00 | 0.00 |
October | 0.235297E+09 | 1450441.30 | 63736931.21 | 0.00 | 63736931.21 | 0.00 | 0.00 |
November | 0.139429E+09 | 18101119.74 | 52951720.50 | 0.00 | 52951720.50 | 0.00 | 0.00 |
December | 81216971.41 | 61455664.20 | 48241790.07 | 0.00 | 48241790.07 | 0.00 | 0.00 |
Annual Sum or Average | 0.277837E+10 | 0.279457E+09 | 0.822319E+09 | 11337930.90 | 0.810981E+09 | 0.00 | 0.00 |
Minimum of Months | 70911354.21 | 0.00 | 48241790.07 | 0.00 | 48241790.07 | 0.00 | 0.00 |
Maximum of Months | 0.416037E+09 | 84777543.15 | 89475839.67 | 5016288.36 | 84459551.31 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.665314E+09 | 0.266423E+09 | 0.427568E+09 | 0.164753E+09 | 0.262814E+09 | 0.00 | 0.00 |
February | 0.661136E+09 | 0.183593E+09 | 0.391935E+09 | 0.130660E+09 | 0.261275E+09 | 0.00 | 0.00 |
March | 0.815884E+09 | 0.134188E+09 | 0.422638E+09 | 0.107003E+09 | 0.315635E+09 | 0.00 | 0.00 |
April | 0.996842E+09 | 55343115.98 | 0.433192E+09 | 0.103774E+09 | 0.329418E+09 | 0.00 | 0.00 |
May | 0.138084E+10 | 3710014.75 | 0.465051E+09 | 0.115774E+09 | 0.349277E+09 | 0.00 | 0.00 |
June | 0.143735E+10 | 56240.00 | 0.436501E+09 | 0.103622E+09 | 0.332879E+09 | 0.00 | 0.00 |
July | 0.164073E+10 | 0.00 | 0.427637E+09 | 94770746.45 | 0.332866E+09 | 0.00 | 0.00 |
August | 0.170274E+10 | 0.00 | 0.451414E+09 | 0.110479E+09 | 0.340935E+09 | 0.00 | 0.00 |
September | 0.144540E+10 | 847875.40 | 0.454114E+09 | 0.128440E+09 | 0.325674E+09 | 0.00 | 0.00 |
October | 0.127484E+10 | 7620166.11 | 0.488090E+09 | 0.173908E+09 | 0.314182E+09 | 0.00 | 0.00 |
November | 0.946025E+09 | 70277578.20 | 0.448525E+09 | 0.178318E+09 | 0.270207E+09 | 0.00 | 0.00 |
December | 0.686133E+09 | 0.197579E+09 | 0.401518E+09 | 0.156112E+09 | 0.245406E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136532E+11 | 0.919638E+09 | 0.524818E+10 | 0.156762E+10 | 0.368057E+10 | 0.00 | 0.00 |
Minimum of Months | 0.661136E+09 | 0.00 | 0.391935E+09 | 94770746.45 | 0.245406E+09 | 0.00 | 0.00 |
Maximum of Months | 0.170274E+10 | 0.266423E+09 | 0.488090E+09 | 0.178318E+09 | 0.349277E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.403553E+09 | 0.278585E+09 | 0.282409E+09 | 65694227.05 | 0.216715E+09 | 0.00 | 0.00 |
February | 0.451972E+09 | 0.196369E+09 | 0.281707E+09 | 58222494.92 | 0.223485E+09 | 0.00 | 0.00 |
March | 0.661027E+09 | 0.144999E+09 | 0.348014E+09 | 64861088.60 | 0.283152E+09 | 0.00 | 0.00 |
April | 0.923269E+09 | 56339257.05 | 0.402829E+09 | 90514008.56 | 0.312315E+09 | 0.00 | 0.00 |
May | 0.138008E+10 | 3736683.01 | 0.465247E+09 | 0.117053E+09 | 0.348195E+09 | 0.00 | 0.00 |
June | 0.146737E+10 | 59199.79 | 0.450401E+09 | 0.109770E+09 | 0.340630E+09 | 0.00 | 0.00 |
July | 0.165320E+10 | 0.00 | 0.432767E+09 | 97295597.11 | 0.335471E+09 | 0.00 | 0.00 |
August | 0.166493E+10 | 0.00 | 0.433434E+09 | 0.103697E+09 | 0.329736E+09 | 0.00 | 0.00 |
September | 0.131851E+10 | 923928.91 | 0.391156E+09 | 93984866.52 | 0.297171E+09 | 0.00 | 0.00 |
October | 0.104071E+10 | 7530206.38 | 0.364789E+09 | 93013451.27 | 0.271776E+09 | 0.00 | 0.00 |
November | 0.661186E+09 | 69669538.51 | 0.297325E+09 | 73001029.63 | 0.224324E+09 | 0.00 | 0.00 |
December | 0.415610E+09 | 0.208433E+09 | 0.253944E+09 | 53245381.57 | 0.200699E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.120414E+11 | 0.966645E+09 | 0.440402E+10 | 0.102035E+10 | 0.338367E+10 | 0.00 | 0.00 |
Minimum of Months | 0.403553E+09 | 0.00 | 0.253944E+09 | 53245381.57 | 0.200699E+09 | 0.00 | 0.00 |
Maximum of Months | 0.166493E+10 | 0.278585E+09 | 0.465247E+09 | 0.117053E+09 | 0.348195E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.753588E+09 | 0.364824E+09 | 0.475484E+09 | 0.171673E+09 | 0.303811E+09 | 0.00 | 0.00 |
February | 0.725571E+09 | 0.270230E+09 | 0.422865E+09 | 0.125537E+09 | 0.297328E+09 | 0.00 | 0.00 |
March | 0.843782E+09 | 0.214823E+09 | 0.424198E+09 | 73037605.55 | 0.351160E+09 | 0.00 | 0.00 |
April | 0.920259E+09 | 0.106651E+09 | 0.375175E+09 | 24265841.68 | 0.350909E+09 | 0.00 | 0.00 |
May | 0.124455E+10 | 15503153.09 | 0.374347E+09 | 9273262.13 | 0.365074E+09 | 0.00 | 0.00 |
June | 0.134265E+10 | 803268.42 | 0.363551E+09 | 11076851.63 | 0.352474E+09 | 0.00 | 0.00 |
July | 0.159106E+10 | 0.00 | 0.359176E+09 | 6694072.71 | 0.352482E+09 | 0.00 | 0.00 |
August | 0.164844E+10 | 0.00 | 0.374051E+09 | 15200023.52 | 0.358851E+09 | 0.00 | 0.00 |
September | 0.140400E+10 | 4169206.94 | 0.410673E+09 | 59803613.10 | 0.350869E+09 | 0.00 | 0.00 |
October | 0.128170E+10 | 28908097.90 | 0.489815E+09 | 0.140193E+09 | 0.349621E+09 | 0.00 | 0.00 |
November | 0.102345E+10 | 0.130760E+09 | 0.491440E+09 | 0.182518E+09 | 0.308922E+09 | 0.00 | 0.00 |
December | 0.797906E+09 | 0.288169E+09 | 0.464751E+09 | 0.178272E+09 | 0.286479E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135770E+11 | 0.142484E+10 | 0.502553E+10 | 0.997544E+09 | 0.402798E+10 | 0.00 | 0.00 |
Minimum of Months | 0.725571E+09 | 0.00 | 0.359176E+09 | 6694072.71 | 0.286479E+09 | 0.00 | 0.00 |
Maximum of Months | 0.164844E+10 | 0.364824E+09 | 0.491440E+09 | 0.182518E+09 | 0.365074E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.661097E+09 | 0.270673E+09 | 0.424356E+09 | 0.160787E+09 | 0.263569E+09 | 0.00 | 0.00 |
February | 0.672039E+09 | 0.187618E+09 | 0.398331E+09 | 0.135726E+09 | 0.262605E+09 | 0.00 | 0.00 |
March | 0.859350E+09 | 0.138102E+09 | 0.449010E+09 | 0.127802E+09 | 0.321208E+09 | 0.00 | 0.00 |
April | 0.980840E+09 | 54991865.69 | 0.429565E+09 | 99638614.52 | 0.329927E+09 | 0.00 | 0.00 |
May | 0.135337E+10 | 3438669.79 | 0.452054E+09 | 0.105038E+09 | 0.347016E+09 | 0.00 | 0.00 |
June | 0.144635E+10 | 35415.20 | 0.441986E+09 | 0.108525E+09 | 0.333461E+09 | 0.00 | 0.00 |
July | 0.163579E+10 | 0.00 | 0.427136E+09 | 93790425.99 | 0.333345E+09 | 0.00 | 0.00 |
August | 0.170107E+10 | 0.00 | 0.451461E+09 | 0.109305E+09 | 0.342155E+09 | 0.00 | 0.00 |
September | 0.145148E+10 | 686542.71 | 0.458474E+09 | 0.131539E+09 | 0.326936E+09 | 0.00 | 0.00 |
October | 0.126841E+10 | 6428295.11 | 0.486529E+09 | 0.172824E+09 | 0.313705E+09 | 0.00 | 0.00 |
November | 0.949885E+09 | 66835149.76 | 0.453324E+09 | 0.182731E+09 | 0.270593E+09 | 0.00 | 0.00 |
December | 0.701935E+09 | 0.197375E+09 | 0.411180E+09 | 0.164078E+09 | 0.247102E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136816E+11 | 0.926184E+09 | 0.528341E+10 | 0.159178E+10 | 0.369162E+10 | 0.00 | 0.00 |
Minimum of Months | 0.661097E+09 | 0.00 | 0.398331E+09 | 93790425.99 | 0.247102E+09 | 0.00 | 0.00 |
Maximum of Months | 0.170107E+10 | 0.270673E+09 | 0.486529E+09 | 0.182731E+09 | 0.347016E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.412313E+09 | 0.293086E+09 | 0.279198E+09 | 61728185.06 | 0.217469E+09 | 0.00 | 0.00 |
February | 0.469183E+09 | 0.205160E+09 | 0.288103E+09 | 63288497.46 | 0.224814E+09 | 0.00 | 0.00 |
March | 0.708833E+09 | 0.152334E+09 | 0.374385E+09 | 85659361.53 | 0.288726E+09 | 0.00 | 0.00 |
April | 0.911694E+09 | 56074367.82 | 0.399202E+09 | 86378479.77 | 0.312824E+09 | 0.00 | 0.00 |
May | 0.135322E+10 | 3392070.97 | 0.452250E+09 | 0.106317E+09 | 0.345933E+09 | 0.00 | 0.00 |
June | 0.147564E+10 | 40620.63 | 0.455886E+09 | 0.114674E+09 | 0.341212E+09 | 0.00 | 0.00 |
July | 0.164857E+10 | 0.00 | 0.432266E+09 | 96315276.65 | 0.335951E+09 | 0.00 | 0.00 |
August | 0.166401E+10 | 0.00 | 0.433481E+09 | 0.102524E+09 | 0.330957E+09 | 0.00 | 0.00 |
September | 0.132677E+10 | 786548.90 | 0.395517E+09 | 97083605.56 | 0.298433E+09 | 0.00 | 0.00 |
October | 0.103914E+10 | 6730730.57 | 0.363228E+09 | 91929001.41 | 0.271299E+09 | 0.00 | 0.00 |
November | 0.677647E+09 | 69332299.54 | 0.302124E+09 | 77413695.10 | 0.224710E+09 | 0.00 | 0.00 |
December | 0.444369E+09 | 0.216303E+09 | 0.263606E+09 | 61210839.51 | 0.202395E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.121314E+11 | 0.100324E+10 | 0.443925E+10 | 0.104452E+10 | 0.339472E+10 | 0.00 | 0.00 |
Minimum of Months | 0.412313E+09 | 0.00 | 0.263606E+09 | 61210839.51 | 0.202395E+09 | 0.00 | 0.00 |
Maximum of Months | 0.166401E+10 | 0.293086E+09 | 0.455886E+09 | 0.114674E+09 | 0.345933E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.496338E+09 | 0.138605E+09 | 0.307628E+09 | 0.145280E+09 | 0.162349E+09 | 0.00 | 0.00 |
February | 0.447772E+09 | 95265561.57 | 0.259749E+09 | 0.106237E+09 | 0.153512E+09 | 0.00 | 0.00 |
March | 0.464078E+09 | 69013702.86 | 0.234203E+09 | 61807290.10 | 0.172396E+09 | 0.00 | 0.00 |
April | 0.450761E+09 | 26508822.84 | 0.181003E+09 | 19991191.08 | 0.161011E+09 | 0.00 | 0.00 |
May | 0.577281E+09 | 1386966.53 | 0.158242E+09 | 2985850.27 | 0.155256E+09 | 0.00 | 0.00 |
June | 0.607450E+09 | 1330.71 | 0.143624E+09 | 177620.59 | 0.143446E+09 | 0.00 | 0.00 |
July | 0.727218E+09 | 0.00 | 0.148205E+09 | 980636.02 | 0.147224E+09 | 0.00 | 0.00 |
August | 0.788187E+09 | 0.00 | 0.171446E+09 | 11404171.32 | 0.160042E+09 | 0.00 | 0.00 |
September | 0.744743E+09 | 296130.06 | 0.219925E+09 | 50570568.16 | 0.169354E+09 | 0.00 | 0.00 |
October | 0.758110E+09 | 2982977.33 | 0.297663E+09 | 0.118640E+09 | 0.179023E+09 | 0.00 | 0.00 |
November | 0.648363E+09 | 33589813.38 | 0.318810E+09 | 0.154458E+09 | 0.164353E+09 | 0.00 | 0.00 |
December | 0.526041E+09 | 0.101270E+09 | 0.304859E+09 | 0.150864E+09 | 0.153995E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.723634E+10 | 0.468920E+09 | 0.274536E+10 | 0.823396E+09 | 0.192196E+10 | 0.00 | 0.00 |
Minimum of Months | 0.447772E+09 | 0.00 | 0.143624E+09 | 177620.59 | 0.143446E+09 | 0.00 | 0.00 |
Maximum of Months | 0.788187E+09 | 0.138605E+09 | 0.318810E+09 | 0.154458E+09 | 0.179023E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.497865E+09 | 0.100860E+10 | 0.452172E+09 | 0.00 | 0.452172E+09 | 0.00 | 0.00 |
February | 0.629581E+09 | 0.738772E+09 | 0.468159E+09 | 0.00 | 0.468159E+09 | 0.00 | 0.00 |
March | 0.102475E+10 | 0.580088E+09 | 0.595447E+09 | 7138.38 | 0.595440E+09 | 0.00 | 0.00 |
April | 0.147325E+10 | 0.301258E+09 | 0.651350E+09 | 2596060.55 | 0.648754E+09 | 0.00 | 0.00 |
May | 0.239015E+10 | 47592131.40 | 0.756625E+09 | 23200441.26 | 0.733424E+09 | 0.00 | 0.00 |
June | 0.270517E+10 | 3766748.17 | 0.782780E+09 | 43885043.59 | 0.738895E+09 | 0.00 | 0.00 |
July | 0.314570E+10 | 0.00 | 0.743256E+09 | 22353641.88 | 0.720902E+09 | 0.00 | 0.00 |
August | 0.308349E+10 | 0.00 | 0.692417E+09 | 6962400.77 | 0.685455E+09 | 0.00 | 0.00 |
September | 0.227412E+10 | 13199451.23 | 0.608967E+09 | 185263.48 | 0.608782E+09 | 0.00 | 0.00 |
October | 0.165185E+10 | 87344853.61 | 0.557603E+09 | 0.00 | 0.557603E+09 | 0.00 | 0.00 |
November | 0.983145E+09 | 0.357379E+09 | 0.463249E+09 | 0.00 | 0.463249E+09 | 0.00 | 0.00 |
December | 0.570891E+09 | 0.789572E+09 | 0.422044E+09 | 0.00 | 0.422044E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.204300E+11 | 0.392757E+10 | 0.719407E+10 | 99189989.90 | 0.709488E+10 | 0.00 | 0.00 |
Minimum of Months | 0.497865E+09 | 0.00 | 0.422044E+09 | 0.00 | 0.422044E+09 | 0.00 | 0.00 |
Maximum of Months | 0.314570E+10 | 0.100860E+10 | 0.782780E+09 | 43885043.59 | 0.738895E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.465696E+09 | 0.105751E+10 | 0.452172E+09 | 0.00 | 0.452172E+09 | 0.00 | 0.00 |
February | 0.600711E+09 | 0.775348E+09 | 0.468159E+09 | 0.00 | 0.468159E+09 | 0.00 | 0.00 |
March | 0.992306E+09 | 0.610737E+09 | 0.595447E+09 | 7138.38 | 0.595440E+09 | 0.00 | 0.00 |
April | 0.144366E+10 | 0.320002E+09 | 0.651350E+09 | 2596060.55 | 0.648754E+09 | 0.00 | 0.00 |
May | 0.235751E+10 | 52398658.36 | 0.756625E+09 | 23200441.26 | 0.733424E+09 | 0.00 | 0.00 |
June | 0.267132E+10 | 4581670.08 | 0.782780E+09 | 43885043.59 | 0.738895E+09 | 0.00 | 0.00 |
July | 0.311098E+10 | 0.00 | 0.743256E+09 | 22353641.88 | 0.720902E+09 | 0.00 | 0.00 |
August | 0.304882E+10 | 0.00 | 0.692417E+09 | 6962400.77 | 0.685455E+09 | 0.00 | 0.00 |
September | 0.224085E+10 | 14916881.62 | 0.608967E+09 | 185263.48 | 0.608782E+09 | 0.00 | 0.00 |
October | 0.162021E+10 | 95960518.94 | 0.557603E+09 | 0.00 | 0.557603E+09 | 0.00 | 0.00 |
November | 0.954843E+09 | 0.379385E+09 | 0.463249E+09 | 0.00 | 0.463249E+09 | 0.00 | 0.00 |
December | 0.541310E+09 | 0.830562E+09 | 0.422044E+09 | 0.00 | 0.422044E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.200482E+11 | 0.414140E+10 | 0.719407E+10 | 99189989.90 | 0.709488E+10 | 0.00 | 0.00 |
Minimum of Months | 0.465696E+09 | 0.00 | 0.422044E+09 | 0.00 | 0.422044E+09 | 0.00 | 0.00 |
Maximum of Months | 0.311098E+10 | 0.105751E+10 | 0.782780E+09 | 43885043.59 | 0.738895E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.110437E+10 | 0.739758E+09 | 0.709946E+09 | 0.230438E+09 | 0.479508E+09 | 0.00 | 0.00 |
February | 0.115216E+10 | 0.563834E+09 | 0.673612E+09 | 0.188874E+09 | 0.484738E+09 | 0.00 | 0.00 |
March | 0.153082E+10 | 0.454074E+09 | 0.770614E+09 | 0.171855E+09 | 0.598759E+09 | 0.00 | 0.00 |
April | 0.199039E+10 | 0.264217E+09 | 0.835977E+09 | 0.194275E+09 | 0.641701E+09 | 0.00 | 0.00 |
May | 0.276568E+10 | 61894691.58 | 0.930248E+09 | 0.232811E+09 | 0.697437E+09 | 0.00 | 0.00 |
June | 0.284909E+10 | 7820774.60 | 0.886853E+09 | 0.213377E+09 | 0.673476E+09 | 0.00 | 0.00 |
July | 0.324028E+10 | 0.00 | 0.860357E+09 | 0.192053E+09 | 0.668304E+09 | 0.00 | 0.00 |
August | 0.331492E+10 | 0.00 | 0.884800E+09 | 0.214161E+09 | 0.670638E+09 | 0.00 | 0.00 |
September | 0.272060E+10 | 15850967.72 | 0.845227E+09 | 0.222412E+09 | 0.622815E+09 | 0.00 | 0.00 |
October | 0.233820E+10 | 95422515.30 | 0.852839E+09 | 0.266908E+09 | 0.585931E+09 | 0.00 | 0.00 |
November | 0.168856E+10 | 0.292930E+09 | 0.745817E+09 | 0.251309E+09 | 0.494509E+09 | 0.00 | 0.00 |
December | 0.115776E+10 | 0.583667E+09 | 0.655435E+09 | 0.209350E+09 | 0.446085E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.258528E+11 | 0.307947E+10 | 0.965172E+10 | 0.258782E+10 | 0.706390E+10 | 0.00 | 0.00 |
Minimum of Months | 0.110437E+10 | 0.00 | 0.655435E+09 | 0.171855E+09 | 0.446085E+09 | 0.00 | 0.00 |
Maximum of Months | 0.331492E+10 | 0.739758E+09 | 0.930248E+09 | 0.266908E+09 | 0.697437E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.148059E+10 | 0.633439E+09 | 0.938090E+09 | 0.369818E+09 | 0.568272E+09 | 0.00 | 0.00 |
February | 0.138685E+10 | 0.474717E+09 | 0.821691E+09 | 0.270431E+09 | 0.551260E+09 | 0.00 | 0.00 |
March | 0.154445E+10 | 0.385103E+09 | 0.800297E+09 | 0.157336E+09 | 0.642961E+09 | 0.00 | 0.00 |
April | 0.160651E+10 | 0.202222E+09 | 0.684036E+09 | 51778573.96 | 0.632257E+09 | 0.00 | 0.00 |
May | 0.211946E+10 | 32134967.74 | 0.662185E+09 | 15553797.16 | 0.646631E+09 | 0.00 | 0.00 |
June | 0.227956E+10 | 1962525.36 | 0.633941E+09 | 15496021.36 | 0.618444E+09 | 0.00 | 0.00 |
July | 0.272384E+10 | 0.00 | 0.632052E+09 | 10159133.23 | 0.621893E+09 | 0.00 | 0.00 |
August | 0.286149E+10 | 0.00 | 0.673786E+09 | 31416648.76 | 0.642370E+09 | 0.00 | 0.00 |
September | 0.249863E+10 | 8393013.52 | 0.768585E+09 | 0.128794E+09 | 0.639792E+09 | 0.00 | 0.00 |
October | 0.236315E+10 | 54695535.49 | 0.948864E+09 | 0.302004E+09 | 0.646860E+09 | 0.00 | 0.00 |
November | 0.195566E+10 | 0.231198E+09 | 0.970351E+09 | 0.393180E+09 | 0.577171E+09 | 0.00 | 0.00 |
December | 0.156401E+10 | 0.499668E+09 | 0.920713E+09 | 0.384033E+09 | 0.536680E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.243842E+11 | 0.252353E+10 | 0.945459E+10 | 0.213000E+10 | 0.732459E+10 | 0.00 | 0.00 |
Minimum of Months | 0.138685E+10 | 0.00 | 0.632052E+09 | 10159133.23 | 0.536680E+09 | 0.00 | 0.00 |
Maximum of Months | 0.286149E+10 | 0.633439E+09 | 0.970351E+09 | 0.393180E+09 | 0.646860E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770467E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161876867.1 | 81.21 | 0.00 | 0.00 |
February | 0.696211E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146148833.3 | 81.21 | 0.00 | 0.00 |
March | 0.770316E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161708301.1 | 81.21 | 0.00 | 0.00 |
April | 0.746497E+10 | -0.730858E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156389145.2 | 81.21 | 0.00 | 0.00 |
May | 0.770426E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161471736.9 | 81.21 | 0.00 | 0.00 |
June | 0.745676E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156232669.8 | 81.21 | 0.00 | 0.00 |
July | 0.771227E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161418358.9 | 81.21 | 0.00 | 0.00 |
August | 0.770422E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161415168.2 | 81.21 | 0.00 | 0.00 |
September | 0.746617E+10 | -0.730993E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156238388.6 | 81.21 | 0.00 | 0.00 |
October | 0.770294E+10 | -0.754143E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161502599.3 | 81.21 | 0.00 | 0.00 |
November | 0.744886E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156428052.8 | 81.21 | 0.00 | 0.00 |
December | 0.771264E+10 | -0.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161798837.5 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907430E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190263E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696211E+10 | -0.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161876867.1 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771264E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146148833.3 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYSLAUNDRY HPWH TANK
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.201491E+11 | -0.940652E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -740405116.0 | 81.68 | 0.00 | 0.00 |
February | 0.149156E+11 | -0.834761E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -658658474.4 | 81.68 | 0.00 | 0.00 |
March | 0.114285E+11 | -0.885189E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -710575063.8 | 81.68 | 0.00 | 0.00 |
April | 0.304722E+10 | -0.805667E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -662391084.0 | 81.68 | 0.00 | 0.00 |
May | -16649.2 | -0.809910E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -653513805.0 | 82.19 | 0.00 | 0.00 |
June | -21597.1 | -0.747965E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -620416629.0 | 82.19 | 0.00 | 0.00 |
July | -9489.6 | -0.761019E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -624972909.5 | 82.19 | 0.00 | 0.00 |
August | -109.6 | -0.777798E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -623758822.5 | 82.19 | 0.00 | 0.00 |
September | 2155.26 | -0.791828E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -624075985.1 | 82.19 | 0.00 | 0.00 |
October | 0.518405E+09 | -0.846429E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -663134230.1 | 81.76 | 0.00 | 0.00 |
November | 0.832303E+10 | -0.864709E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -669674800.6 | 81.68 | 0.00 | 0.00 |
December | 0.164294E+11 | -0.929664E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -726745653.5 | 81.68 | 0.00 | 0.00 |
Annual Sum or Average | 0.748112E+11 | -0.999559E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.797832E+10 | 81.90 | 0.00 | 0.00 |
Minimum of Months | -21597.1 | -0.940652E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -740405116.0 | 81.68 | 0.00 | 0.00 |
Maximum of Months | 0.201491E+11 | -0.747965E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -620416629.0 | 82.19 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 HPWH TANK
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | -0.195618E+10 | -0.512443E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.111191E+10 | 59.44 | 0.00 | 0.00 |
February | -0.167162E+10 | -0.450105E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -980554303.3 | 59.46 | 0.00 | 0.00 |
March | -0.168081E+10 | -0.464925E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.104191E+10 | 59.49 | 0.00 | 0.00 |
April | -0.133431E+10 | -0.405316E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -948948440.6 | 59.53 | 0.00 | 0.00 |
May | -0.101727E+10 | -0.373964E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -892194011.4 | 59.56 | 0.00 | 0.00 |
June | -711357334.0 | -0.331056E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -835486619.0 | 59.59 | 0.00 | 0.00 |
July | -664149762.1 | -0.331519E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -824985223.3 | 59.60 | 0.00 | 0.00 |
August | -767435910.8 | -0.346355E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -821512167.1 | 59.59 | 0.00 | 0.00 |
September | -0.103592E+10 | -0.368793E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -843019308.3 | 59.55 | 0.00 | 0.00 |
October | -0.147601E+10 | -0.426923E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -926746120.9 | 59.52 | 0.00 | 0.00 |
November | -0.172441E+10 | -0.456421E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -964626921.1 | 59.48 | 0.00 | 0.00 |
December | -0.190070E+10 | -0.502913E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.107947E+10 | 59.45 | 0.00 | 0.00 |
Annual Sum or Average | -0.159402E+11 | -0.497073E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.112714E+11 | 59.52 | 0.00 | 0.00 |
Minimum of Months | -0.195618E+10 | -0.512443E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.111191E+10 | 59.44 | 0.00 | 0.00 |
Maximum of Months | -664149762.1 | -0.331056E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -821512167.1 | 59.60 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.87 | 0.86 | 01-JAN-07:00 | 3308.13 | 33.59 | 298.33 | 294.83 | 583.15 | 24.88 | 268.83 | 278.00 |
February | 308.33 | 0.87 | 0.86 | 01-FEB-07:49 | 1583.05 | 24.53 | 120.33 | 275.50 | 494.09 | 21.22 | 184.50 | 231.33 |
March | 357.50 | 0.87 | 0.86 | 01-MAR-08:39 | 1101.75 | 18.70 | 0.00 | 316.83 | 412.12 | 20.45 | 184.17 | 258.83 |
April | 375.00 | 0.88 | 0.86 | 01-APR-07:49 | 872.28 | 18.17 | 0.00 | 325.00 | 332.14 | 19.87 | 110.50 | 260.00 |
May | 405.33 | 0.88 | 0.86 | 01-MAY-07:30 | 726.07 | 18.04 | 0.00 | 350.50 | 286.60 | 19.77 | 38.50 | 271.50 |
June | 403.50 | 0.88 | 0.86 | 01-JUN-07:40 | 689.18 | 17.95 | 0.00 | 344.50 | 277.44 | 19.71 | 39.50 | 267.17 |
July | 405.00 | 0.88 | 0.86 | 01-JUL-07:40 | 728.54 | 17.80 | 0.00 | 345.83 | 289.71 | 19.56 | 76.67 | 270.33 |
August | 395.83 | 0.88 | 0.86 | 01-AUG-07:40 | 865.49 | 18.30 | 0.00 | 344.50 | 336.67 | 20.02 | 182.50 | 278.17 |
September | 358.83 | 0.87 | 0.86 | 01-SEP-07:40 | 1090.66 | 19.04 | 0.00 | 319.83 | 416.22 | 20.77 | 234.17 | 267.33 |
October | 351.17 | 0.87 | 0.86 | 01-OCT-07:40 | 1371.45 | 20.80 | 39.33 | 318.33 | 501.37 | 21.48 | 248.33 | 276.67 |
November | 318.83 | 0.87 | 0.86 | 01-NOV-07:10 | 2772.90 | 31.37 | 242.83 | 299.50 | 581.50 | 24.55 | 281.33 | 278.67 |
December | 319.00 | 0.87 | 0.86 | 01-DEC-07:30 | 3500.18 | 34.59 | 308.17 | 290.83 | 584.31 | 24.72 | 244.17 | 267.83 |
Annual Sum or Average | 4323.33 | 0.87 | 1472.91 | 22.24 | 1009.00 | 3826.00 | 413.96 | 21.26 | 2093.17 | 3205.83 | ||
Minimum of Months | 308.33 | 0.87 | 0.86 | 689.18 | 17.80 | 0.00 | 275.50 | 277.44 | 19.56 | 38.50 | 231.33 | |
Maximum of Months | 405.33 | 0.88 | 0.86 | 3500.18 | 34.59 | 308.17 | 350.50 | 584.31 | 24.88 | 281.33 | 278.67 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.26 | 0.22 | 01-JAN-07:00 | 3531.15 | 33.67 | 298.50 | 300.50 | 804.48 | 25.11 | 293.83 | 289.00 |
February | 308.33 | 0.27 | 0.22 | 01-FEB-07:49 | 1789.22 | 24.83 | 120.83 | 284.83 | 699.55 | 21.68 | 209.33 | 257.67 |
March | 357.50 | 0.27 | 0.22 | 01-MAR-08:09 | 1270.27 | 19.50 | 0.00 | 329.67 | 579.71 | 21.03 | 223.33 | 293.50 |
April | 375.00 | 0.28 | 0.22 | 01-APR-07:30 | 1003.20 | 19.07 | 0.00 | 337.83 | 462.54 | 20.55 | 216.67 | 302.17 |
May | 405.33 | 0.28 | 0.22 | 01-MAY-06:00 | 838.38 | 19.00 | 0.00 | 364.67 | 398.49 | 20.49 | 233.50 | 324.33 |
June | 403.50 | 0.28 | 0.22 | 01-JUN-06:49 | 797.40 | 18.93 | 0.00 | 359.83 | 385.27 | 20.45 | 243.33 | 318.17 |
July | 405.00 | 0.29 | 0.22 | 01-JUL-06:00 | 840.63 | 18.80 | 0.00 | 358.17 | 401.38 | 20.33 | 241.67 | 322.00 |
August | 395.83 | 0.28 | 0.22 | 01-AUG-06:00 | 994.08 | 19.20 | 0.00 | 354.83 | 464.76 | 20.70 | 260.17 | 321.50 |
September | 358.83 | 0.27 | 0.22 | 01-SEP-07:10 | 1256.13 | 19.80 | 0.00 | 331.67 | 581.05 | 21.32 | 256.00 | 300.17 |
October | 351.17 | 0.27 | 0.22 | 01-OCT-07:10 | 1582.07 | 21.34 | 39.33 | 324.33 | 710.93 | 21.90 | 267.67 | 304.00 |
November | 318.83 | 0.24 | 0.22 | 01-NOV-06:00 | 3010.82 | 31.45 | 243.17 | 305.00 | 817.90 | 24.77 | 306.50 | 293.83 |
December | 319.00 | 0.25 | 0.22 | 01-DEC-07:19 | 3723.97 | 34.66 | 308.50 | 298.33 | 806.36 | 24.96 | 280.83 | 282.67 |
Annual Sum or Average | 4323.33 | 0.27 | 1637.48 | 22.89 | 1010.33 | 3949.67 | 577.68 | 21.80 | 3032.83 | 3609.00 | ||
Minimum of Months | 308.33 | 0.24 | 0.22 | 797.40 | 18.80 | 0.00 | 284.83 | 385.27 | 20.33 | 209.33 | 257.67 | |
Maximum of Months | 405.33 | 0.29 | 0.22 | 3723.97 | 34.66 | 308.50 | 364.67 | 817.90 | 25.11 | 306.50 | 324.33 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.66 | 0.60 | 01-JAN-10:20 | 381.46 | 14.57 | 0.00 | 272.00 | 170.59 | 17.78 | 0.00 | 117.67 |
February | 308.33 | 0.65 | 0.60 | 01-FEB-09:09 | 432.25 | 15.18 | 0.00 | 263.17 | 191.82 | 18.34 | 0.00 | 176.00 |
March | 357.50 | 0.64 | 0.60 | 01-MAR-08:50 | 511.14 | 15.92 | 0.00 | 318.00 | 222.17 | 19.06 | 0.00 | 247.00 |
April | 375.00 | 0.63 | 0.60 | 01-APR-07:40 | 596.33 | 16.34 | 0.00 | 336.00 | 255.39 | 19.45 | 0.00 | 285.83 |
May | 405.33 | 0.62 | 0.60 | 01-MAY-06:49 | 703.29 | 17.71 | 20.83 | 375.17 | 299.69 | 20.82 | 42.17 | 336.17 |
June | 403.50 | 0.62 | 0.60 | 01-JUN-06:19 | 785.93 | 20.11 | 74.67 | 370.00 | 331.05 | 21.63 | 109.33 | 341.50 |
July | 405.00 | 0.63 | 0.60 | 01-JUL-06:49 | 758.30 | 17.23 | 12.50 | 365.00 | 319.58 | 20.82 | 76.83 | 329.67 |
August | 395.83 | 0.63 | 0.60 | 01-AUG-06:00 | 680.94 | 16.75 | 0.00 | 356.17 | 294.10 | 19.93 | 15.67 | 316.50 |
September | 358.83 | 0.63 | 0.60 | 01-SEP-07:19 | 581.85 | 16.54 | 0.00 | 324.50 | 258.21 | 19.70 | 0.00 | 274.00 |
October | 351.17 | 0.64 | 0.60 | 01-OCT-07:40 | 473.32 | 15.77 | 0.00 | 308.50 | 215.61 | 18.96 | 0.00 | 239.17 |
November | 318.83 | 0.64 | 0.60 | 01-NOV-08:09 | 410.10 | 15.46 | 0.00 | 273.67 | 188.32 | 18.72 | 0.00 | 165.33 |
December | 319.00 | 0.66 | 0.60 | 01-DEC-09:09 | 369.53 | 14.60 | 0.00 | 262.83 | 166.16 | 17.84 | 0.00 | 94.33 |
Annual Sum or Average | 4323.33 | 0.64 | 570.41 | 16.47 | 108.00 | 3825.00 | 247.98 | 19.53 | 244.00 | 2923.17 | ||
Minimum of Months | 308.33 | 0.62 | 0.60 | 369.53 | 14.57 | 0.00 | 262.83 | 166.16 | 17.78 | 0.00 | 94.33 | |
Maximum of Months | 405.33 | 0.66 | 0.60 | 785.93 | 20.11 | 74.67 | 375.17 | 331.05 | 21.63 | 109.33 | 341.50 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.66 | 0.60 | 01-JAN-10:20 | 381.46 | 14.57 | 0.00 | 272.00 | 170.59 | 17.78 | 0.00 | 117.67 |
February | 308.33 | 0.65 | 0.60 | 01-FEB-09:09 | 432.25 | 15.18 | 0.00 | 263.17 | 191.82 | 18.34 | 0.00 | 176.00 |
March | 357.50 | 0.64 | 0.60 | 01-MAR-08:50 | 511.14 | 15.92 | 0.00 | 318.00 | 222.17 | 19.06 | 0.00 | 247.00 |
April | 375.00 | 0.63 | 0.60 | 01-APR-07:40 | 596.33 | 16.34 | 0.00 | 336.00 | 255.39 | 19.45 | 0.00 | 285.83 |
May | 405.33 | 0.62 | 0.60 | 01-MAY-06:49 | 703.29 | 17.71 | 20.83 | 375.17 | 299.69 | 20.82 | 42.17 | 336.17 |
June | 403.50 | 0.62 | 0.60 | 01-JUN-06:19 | 785.93 | 20.11 | 74.67 | 370.00 | 331.05 | 21.63 | 109.33 | 341.50 |
July | 405.00 | 0.63 | 0.60 | 01-JUL-06:49 | 758.30 | 17.23 | 12.50 | 365.00 | 319.58 | 20.82 | 76.83 | 329.67 |
August | 395.83 | 0.63 | 0.60 | 01-AUG-06:00 | 680.94 | 16.75 | 0.00 | 356.17 | 294.10 | 19.93 | 15.67 | 316.50 |
September | 358.83 | 0.63 | 0.60 | 01-SEP-07:19 | 581.85 | 16.54 | 0.00 | 324.50 | 258.21 | 19.70 | 0.00 | 274.00 |
October | 351.17 | 0.64 | 0.60 | 01-OCT-07:40 | 473.32 | 15.77 | 0.00 | 308.50 | 215.61 | 18.96 | 0.00 | 239.17 |
November | 318.83 | 0.64 | 0.60 | 01-NOV-08:09 | 410.10 | 15.46 | 0.00 | 273.67 | 188.32 | 18.72 | 0.00 | 165.33 |
December | 319.00 | 0.66 | 0.60 | 01-DEC-09:09 | 369.53 | 14.60 | 0.00 | 262.83 | 166.16 | 17.84 | 0.00 | 94.33 |
Annual Sum or Average | 4323.33 | 0.64 | 570.41 | 16.47 | 108.00 | 3825.00 | 247.98 | 19.53 | 244.00 | 2923.17 | ||
Minimum of Months | 308.33 | 0.62 | 0.60 | 369.53 | 14.57 | 0.00 | 262.83 | 166.16 | 17.78 | 0.00 | 94.33 | |
Maximum of Months | 405.33 | 0.66 | 0.60 | 785.93 | 20.11 | 74.67 | 375.17 | 331.05 | 21.63 | 109.33 | 341.50 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 56192800.21 | 22271.60 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1609142.91 | 2660.26 | 12-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2030.26 | 6.77 | 07-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17689586.13 | 22262.63 | 30-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75493559.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 56192800.21 | 22271.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 23262917.06 | 406.36 | 01-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8071088.94 | 344.57 | 21-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 467468.76 | 126.74 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2353160.98 | 182.18 | 16-DEC-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 34154635.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23262917.06 | 406.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 5091428.26 | 465.53 | 02-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2603335.07 | 424.76 | 21-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 497764.71 | 259.03 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2267761.12 | 383.73 | 16-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 10460289.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5091428.26 | 465.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 16997908.64 | 759.73 | 02-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 16997908.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16997908.64 | 759.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 66222.95 | 67.69 | 06-JAN-23:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4623.58 | 0.30 | 13-FEB-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7506.99 | 0.30 | 25-MAR-01:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5365.52 | 0.30 | 19-APR-18:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3547.20 | 0.30 | 27-MAY-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2569.45 | 0.30 | 25-JUN-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4158.71 | 0.30 | 21-JUL-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3604.71 | 0.30 | 02-AUG-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2246.62 | 0.30 | 14-SEP-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6106.18 | 0.30 | 13-OCT-04:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6914.22 | 0.30 | 12-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8288.12 | 0.30 | 21-DEC-22:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121154.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2246.62 | 0.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 66222.95 | 67.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 19076119.02 | 3841.83 | 21-JAN-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12959199.96 | 3841.52 | 13-FEB-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9287203.26 | 3841.46 | 14-MAR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6859126.96 | 3842.35 | 06-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1893515.23 | 2113.58 | 02-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 855924.46 | 1382.14 | 08-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1376127.94 | 1651.50 | 25-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2542495.23 | 1866.85 | 30-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5399492.41 | 3326.74 | 21-NOV-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15465023.17 | 3841.61 | 19-DEC-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75714227.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19076119.02 | 3842.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 24819556.27 | 3832.74 | 21-JAN-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10473014.16 | 3477.50 | 23-FEB-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7103983.84 | 3593.86 | 11-MAR-09:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3153584.14 | 3832.11 | 17-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1073788.55 | 1579.80 | 03-MAY-08:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 432499.86 | 1711.60 | 22-JUN-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1526983.51 | 1556.28 | 24-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3761575.63 | 3641.50 | 30-OCT-08:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8733247.45 | 3677.22 | 13-NOV-09:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16010045.31 | 3832.38 | 09-DEC-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 77088278.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24819556.27 | 3832.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105150E+09 | 26544.87 | 16-JAN-09:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 72581625.70 | 29689.76 | 11-FEB-16:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 89956898.54 | 25932.10 | 05-MAR-16:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 48802240.68 | 21440.90 | 01-APR-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 27181085.45 | 20087.65 | 16-MAY-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32109804.30 | 14999.25 | 29-JUN-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31597955.63 | 14924.20 | 08-JUL-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 36961374.30 | 15654.36 | 18-AUG-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30928414.26 | 13072.50 | 08-SEP-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 50773652.65 | 25818.48 | 30-OCT-08:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 85220015.21 | 26463.13 | 13-NOV-09:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 88243562.52 | 26302.21 | 30-DEC-09:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.699507E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 27181085.45 | 13072.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105150E+09 | 29689.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 15087862.98 | 3091.41 | 23-JAN-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7114224.59 | 3360.44 | 25-FEB-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6594523.31 | 3201.18 | 04-MAR-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 987461.34 | 3399.60 | 14-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 578477.29 | 1573.51 | 21-NOV-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8681156.08 | 3372.09 | 11-DEC-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39043705.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15087862.98 | 3399.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 29731288.08 | 3512.65 | 27-JAN-16:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8537543.39 | 3572.58 | 13-FEB-16:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5496911.21 | 2870.45 | 01-MAR-07:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 684359.24 | 1815.17 | 05-APR-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 86529.14 | 1009.51 | 30-SEP-06:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8099.01 | 134.98 | 20-OCT-08:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3523442.26 | 2754.52 | 23-NOV-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13261714.17 | 3552.04 | 18-DEC-16:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 61329886.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29731288.08 | 3572.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 17034830.04 | 1069.47 | 14-JAN-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5732962.77 | 1053.82 | 20-FEB-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3348299.16 | 986.77 | 08-MAR-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1936824.66 | 1021.36 | 10-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 529401.77 | 897.07 | 03-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 207834.39 | 338.63 | 08-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3146.76 | 19.56 | 06-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5905.64 | 23.83 | 15-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 419697.88 | 481.74 | 25-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1450981.06 | 1006.02 | 30-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2173546.52 | 1030.44 | 21-NOV-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7453066.51 | 1033.41 | 29-DEC-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40296497.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3146.76 | 19.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17034830.04 | 1069.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 22400892.78 | 1079.07 | 02-JAN-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4756609.12 | 969.19 | 05-FEB-09:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2088136.83 | 938.74 | 28-MAR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 910063.44 | 998.84 | 03-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 345083.15 | 276.67 | 07-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 158870.88 | 326.73 | 08-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 476.88 | 2.68 | 06-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14170.38 | 40.82 | 21-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 567963.64 | 760.63 | 30-SEP-06:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1529610.41 | 981.69 | 25-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2455571.65 | 1018.10 | 20-NOV-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6247500.08 | 1094.73 | 16-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41474949.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 476.88 | 2.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22400892.78 | 1094.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 8510848.91 | 3935.20 | 25-JAN-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7971017.00 | 4321.17 | 12-FEB-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8605575.93 | 3775.16 | 17-MAR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4675544.92 | 3692.69 | 04-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5488818.53 | 4368.74 | 02-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2812725.42 | 3941.42 | 08-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9240.85 | 92.41 | 06-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 40131.81 | 401.32 | 15-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1747398.47 | 2747.76 | 25-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1404650.32 | 2344.26 | 11-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 362895.40 | 2982.86 | 22-NOV-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8514821.94 | 4447.76 | 27-DEC-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50143669.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9240.85 | 92.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8605575.93 | 4447.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.413355E+11 | 0.382589E+11 | 56487.74 | 12-JAN-05:10 | 52433.41 | 0.00 |
February | 0.00 | 0.00 | 0.364697E+11 | 0.310804E+11 | 58495.93 | 01-FEB-05:10 | 49894.07 | 0.00 |
March | 0.00 | 0.00 | 0.375345E+11 | 0.356380E+11 | 59406.77 | 01-MAR-05:10 | 56130.01 | 0.00 |
April | 0.00 | 0.00 | 0.327150E+11 | 0.295473E+11 | 61908.46 | 01-APR-05:08 | 55732.41 | 0.00 |
May | 0.00 | 0.00 | 0.301532E+11 | 0.271508E+11 | 64818.48 | 01-MAY-07:05 | 57990.53 | 0.00 |
June | 0.00 | 0.00 | 0.266426E+11 | 0.191807E+11 | 66561.26 | 01-JUN-17:17 | 47755.54 | 0.00 |
July | 0.00 | 0.00 | 0.267736E+11 | 0.181615E+11 | 68027.07 | 31-JUL-07:15 | 46106.14 | 0.00 |
August | 0.00 | 0.00 | 0.281763E+11 | 0.181293E+11 | 69379.32 | 31-AUG-07:15 | 44471.05 | 0.00 |
September | 0.00 | 0.00 | 0.302204E+11 | 0.187503E+11 | 68617.89 | 30-SEP-15:08 | 42327.59 | 0.00 |
October | 0.00 | 0.00 | 0.351294E+11 | 0.254193E+11 | 66346.68 | 31-OCT-10:07 | 47852.91 | 0.00 |
November | 0.00 | 0.00 | 0.375103E+11 | 0.301905E+11 | 63248.79 | 30-NOV-05:10 | 50721.57 | 0.00 |
December | 0.00 | 0.00 | 0.409190E+11 | 0.335440E+11 | 59156.25 | 31-DEC-06:07 | 48445.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.403579E+12 | 0.325051E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.266426E+11 | 0.181293E+11 | 56487.74 | 42327.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.413355E+11 | 0.382589E+11 | 69379.32 | 57990.53 | 0.00 |
Report: CoilReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.565157E+11 | 0.523171E+11 | 71490.86 | 12-JAN-18:03 | 66335.30 | 0.00 |
February | 0.00 | 0.00 | 0.526808E+11 | 0.448918E+11 | 74033.71 | 01-FEB-17:10 | 63155.18 | 0.00 |
March | 0.00 | 0.00 | 0.590145E+11 | 0.560488E+11 | 75187.05 | 01-MAR-17:10 | 70949.10 | 0.00 |
April | 0.00 | 0.00 | 0.594145E+11 | 0.536628E+11 | 78354.77 | 01-APR-17:01 | 70324.60 | 0.00 |
May | 0.00 | 0.00 | 0.622830E+11 | 0.561081E+11 | 82039.55 | 01-MAY-16:10 | 73277.06 | 0.00 |
June | 0.00 | 0.00 | 0.576637E+11 | 0.415261E+11 | 77821.86 | 01-JUN-16:10 | 55845.80 | 0.00 |
July | 0.00 | 0.00 | 0.589753E+11 | 0.400152E+11 | 75619.99 | 31-JUL-16:10 | 51264.70 | 0.00 |
August | 0.00 | 0.00 | 0.606482E+11 | 0.390462E+11 | 79350.30 | 31-AUG-16:10 | 50866.85 | 0.00 |
September | 0.00 | 0.00 | 0.618818E+11 | 0.384058E+11 | 84657.87 | 30-SEP-16:10 | 52234.99 | 0.00 |
October | 0.00 | 0.00 | 0.656926E+11 | 0.475213E+11 | 83974.60 | 31-OCT-21:50 | 60367.09 | 0.00 |
November | 0.00 | 0.00 | 0.608435E+11 | 0.489703E+11 | 80051.95 | 30-NOV-17:10 | 64160.37 | 0.00 |
December | 0.00 | 0.00 | 0.590315E+11 | 0.483931E+11 | 74869.82 | 31-DEC-17:10 | 61320.79 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.714645E+12 | 0.566907E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.526808E+11 | 0.384058E+11 | 71490.86 | 50866.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.656926E+11 | 0.561081E+11 | 84657.87 | 73277.06 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.251376E+12 | 0.226718E+12 | 284816.54 | 30-JAN-14:00 | 128204.40 | 0.86 |
February | 0.00 | 0.00 | 0.304506E+12 | 0.251057E+12 | 404985.13 | 08-FEB-22:00 | 201131.42 | 0.98 |
March | 0.00 | 0.00 | 0.417461E+12 | 0.352850E+12 | 372329.78 | 31-MAR-10:00 | 132951.76 | 0.97 |
April | 0.00 | 0.00 | 0.571125E+12 | 0.429955E+12 | 432455.52 | 29-APR-20:40 | 226901.90 | 0.96 |
May | 0.00 | 0.00 | 0.768577E+12 | 0.552066E+12 | 525775.78 | 30-MAY-18:03 | 281677.76 | 1.00 |
June | 0.00 | 0.00 | 0.923734E+12 | 0.567204E+12 | 572666.30 | 26-JUN-18:03 | 278919.28 | 1.00 |
July | 0.00 | 0.00 | 0.107359E+13 | 0.626528E+12 | 619917.24 | 17-JUL-18:02 | 294397.78 | 1.00 |
August | 0.00 | 0.00 | 0.111880E+13 | 0.640539E+12 | 627514.42 | 30-AUG-20:00 | 291245.46 | 1.00 |
September | 0.00 | 0.00 | 0.998701E+12 | 0.573362E+12 | 628428.91 | 08-SEP-18:02 | 282313.46 | 1.00 |
October | 0.00 | 0.00 | 0.839104E+12 | 0.539529E+12 | 568950.28 | 07-OCT-10:33 | 229535.93 | 0.99 |
November | 0.00 | 0.00 | 0.594053E+12 | 0.427381E+12 | 467118.71 | 02-NOV-21:00 | 264323.54 | 1.00 |
December | 0.00 | 0.00 | 0.389347E+12 | 0.297549E+12 | 406159.18 | 04-DEC-21:10 | 210779.19 | 0.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.825038E+13 | 0.548474E+13 | 0.98 | |||
Minimum of Months | 0.00 | 0.00 | 0.251376E+12 | 0.226718E+12 | 284816.54 | 128204.40 | 0.86 | |
Maximum of Months | 0.00 | 0.00 | 0.111880E+13 | 0.640539E+12 | 628428.91 | 294397.78 | 1.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.213661E+11 | 0.172777E+11 | 33449.09 | 30-JAN-16:02 | 15535.23 | 0.61 |
February | 0.00 | 0.00 | 0.262802E+11 | 0.194353E+11 | 33877.18 | 03-FEB-20:00 | 15165.12 | 0.73 |
March | 0.00 | 0.00 | 0.338636E+11 | 0.271891E+11 | 36588.83 | 29-MAR-08:30 | 15933.36 | 0.77 |
April | 0.00 | 0.00 | 0.427194E+11 | 0.315056E+11 | 44892.92 | 30-APR-06:00 | 15248.56 | 0.78 |
May | 0.00 | 0.00 | 0.520701E+11 | 0.370545E+11 | 45639.31 | 29-MAY-13:00 | 21331.40 | 0.79 |
June | 0.00 | 0.00 | 0.627577E+11 | 0.374132E+11 | 44834.69 | 10-JUN-13:00 | 22462.07 | 0.79 |
July | 0.00 | 0.00 | 0.738308E+11 | 0.406451E+11 | 50369.90 | 20-JUL-12:40 | 23419.27 | 0.79 |
August | 0.00 | 0.00 | 0.760364E+11 | 0.409026E+11 | 50525.09 | 08-AUG-13:00 | 22528.40 | 0.79 |
September | 0.00 | 0.00 | 0.674343E+11 | 0.371940E+11 | 48016.18 | 08-SEP-18:02 | 21571.70 | 0.79 |
October | 0.00 | 0.00 | 0.564372E+11 | 0.358560E+11 | 45894.31 | 07-OCT-10:00 | 17842.44 | 0.79 |
November | 0.00 | 0.00 | 0.439885E+11 | 0.307438E+11 | 40213.62 | 08-NOV-07:40 | 15812.40 | 0.79 |
December | 0.00 | 0.00 | 0.326690E+11 | 0.227521E+11 | 37227.53 | 06-DEC-09:50 | 15315.18 | 0.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.589453E+12 | 0.377969E+12 | 0.77 | |||
Minimum of Months | 0.00 | 0.00 | 0.213661E+11 | 0.172777E+11 | 33449.09 | 15165.12 | 0.61 | |
Maximum of Months | 0.00 | 0.00 | 0.760364E+11 | 0.409026E+11 | 50525.09 | 23419.27 | 0.79 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.384496E+10 | 0.166235E+10 | 16080.84 | 29-JAN-09:01 | 11383.15 | 0.86 |
February | 0.00 | 0.00 | 0.479935E+10 | 0.229528E+10 | 16017.48 | 07-FEB-09:01 | 11659.73 | 0.90 |
March | 0.00 | 0.00 | 0.701597E+10 | 0.386290E+10 | 15497.25 | 29-MAR-08:61 | 11327.04 | 0.93 |
April | 0.00 | 0.00 | 0.902376E+10 | 0.551629E+10 | 16198.12 | 18-APR-08:61 | 11295.96 | 0.95 |
May | 0.00 | 0.00 | 0.129922E+11 | 0.920308E+10 | 16410.15 | 01-MAY-08:61 | 10961.00 | 0.97 |
June | 0.00 | 0.00 | 0.139118E+11 | 0.101433E+11 | 14050.51 | 08-JUN-08:62 | 12986.80 | 0.98 |
July | 0.00 | 0.00 | 0.156451E+11 | 0.115907E+11 | 13788.93 | 01-JUL-08:62 | 13404.18 | 0.98 |
August | 0.00 | 0.00 | 0.161882E+11 | 0.120471E+11 | 13903.51 | 27-AUG-08:62 | 13338.49 | 0.98 |
September | 0.00 | 0.00 | 0.139505E+11 | 0.101247E+11 | 14485.94 | 25-SEP-08:62 | 12677.99 | 0.98 |
October | 0.00 | 0.00 | 0.122855E+11 | 0.841023E+10 | 15795.12 | 31-OCT-08:61 | 11966.16 | 0.97 |
November | 0.00 | 0.00 | 0.882137E+10 | 0.522067E+10 | 16807.36 | 02-NOV-08:62 | 11174.87 | 0.95 |
December | 0.00 | 0.00 | 0.534389E+10 | 0.249714E+10 | 16002.61 | 06-DEC-09:02 | 11055.68 | 0.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.123823E+12 | 0.825739E+11 | 0.95 | |||
Minimum of Months | 0.00 | 0.00 | 0.384496E+10 | 0.166235E+10 | 13788.93 | 10961.00 | 0.86 | |
Maximum of Months | 0.00 | 0.00 | 0.161882E+11 | 0.120471E+11 | 16807.36 | 13404.18 | 0.98 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.150303E+10 | 0.543469E+09 | 15684.60 | 29-JAN-09:51 | 11044.29 | 0.49 |
February | 0.00 | 0.00 | 0.265593E+10 | 0.115541E+10 | 16503.60 | 07-FEB-09:41 | 10979.95 | 0.59 |
March | 0.00 | 0.00 | 0.533770E+10 | 0.294257E+10 | 16318.20 | 29-MAR-08:51 | 10803.83 | 0.71 |
April | 0.00 | 0.00 | 0.825154E+10 | 0.513699E+10 | 18142.78 | 30-APR-08:51 | 11177.73 | 0.84 |
May | 0.00 | 0.00 | 0.129131E+11 | 0.922380E+10 | 17674.36 | 02-MAY-08:61 | 12246.62 | 0.96 |
June | 0.00 | 0.00 | 0.140857E+11 | 0.103452E+11 | 14781.24 | 22-JUN-08:51 | 14106.10 | 0.98 |
July | 0.00 | 0.00 | 0.157042E+11 | 0.116573E+11 | 13523.64 | 14-JUL-08:62 | 13153.41 | 0.98 |
August | 0.00 | 0.00 | 0.159275E+11 | 0.118285E+11 | 13647.14 | 27-AUG-08:62 | 13084.09 | 0.98 |
September | 0.00 | 0.00 | 0.131660E+11 | 0.940189E+10 | 15787.21 | 25-SEP-08:62 | 11509.35 | 0.97 |
October | 0.00 | 0.00 | 0.108407E+11 | 0.706742E+10 | 18036.40 | 31-OCT-07:52 | 11206.85 | 0.93 |
November | 0.00 | 0.00 | 0.686696E+10 | 0.384443E+10 | 18359.34 | 01-NOV-08:11 | 11000.23 | 0.81 |
December | 0.00 | 0.00 | 0.293565E+10 | 0.125565E+10 | 15918.61 | 10-DEC-09:51 | 11585.63 | 0.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.110188E+12 | 0.744025E+11 | 0.82 | |||
Minimum of Months | 0.00 | 0.00 | 0.150303E+10 | 0.543469E+09 | 13523.64 | 10803.83 | 0.49 | |
Maximum of Months | 0.00 | 0.00 | 0.159275E+11 | 0.118285E+11 | 18359.34 | 14106.10 | 0.98 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.327117E+11 | 0.148631E+11 | 32735.41 | 28-JAN-13:30 | 23230.18 | 0.95 |
February | 0.00 | 0.00 | 0.326891E+11 | 0.152348E+11 | 37853.71 | 05-FEB-13:30 | 30621.60 | 0.97 |
March | 0.00 | 0.00 | 0.390946E+11 | 0.181462E+11 | 33336.89 | 27-MAR-13:30 | 25030.15 | 0.99 |
April | 0.00 | 0.00 | 0.439312E+11 | 0.212511E+11 | 31459.68 | 28-APR-16:20 | 21465.20 | 1.00 |
May | 0.00 | 0.00 | 0.588423E+11 | 0.329527E+11 | 36355.14 | 31-MAY-19:10 | 28463.06 | 1.00 |
June | 0.00 | 0.00 | 0.617502E+11 | 0.356216E+11 | 37240.31 | 09-JUN-17:20 | 29433.83 | 1.00 |
July | 0.00 | 0.00 | 0.727637E+11 | 0.461667E+11 | 40667.58 | 21-JUL-16:20 | 33926.50 | 1.00 |
August | 0.00 | 0.00 | 0.780584E+11 | 0.523717E+11 | 41520.29 | 16-AUG-16:20 | 35062.38 | 1.00 |
September | 0.00 | 0.00 | 0.722464E+11 | 0.476574E+11 | 42443.64 | 26-SEP-13:00 | 39101.85 | 1.00 |
October | 0.00 | 0.00 | 0.707819E+11 | 0.465098E+11 | 43393.47 | 09-OCT-12:40 | 39816.07 | 1.00 |
November | 0.00 | 0.00 | 0.567382E+11 | 0.338519E+11 | 41380.66 | 05-NOV-12:40 | 36585.38 | 1.00 |
December | 0.00 | 0.00 | 0.400896E+11 | 0.197230E+11 | 39495.33 | 03-DEC-12:40 | 31368.67 | 0.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.659697E+12 | 0.384350E+12 | 0.99 | |||
Minimum of Months | 0.00 | 0.00 | 0.326891E+11 | 0.148631E+11 | 31459.68 | 21465.20 | 0.95 | |
Maximum of Months | 0.00 | 0.00 | 0.780584E+11 | 0.523717E+11 | 43393.47 | 39816.07 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.234788E+11 | 0.130304E+11 | 100333.59 | 29-JAN-09:51 | 74685.38 | 0.46 |
February | 0.00 | 0.00 | 0.288790E+11 | 0.166938E+11 | 109061.17 | 08-FEB-22:51 | 72015.78 | 0.53 |
March | 0.00 | 0.00 | 0.439297E+11 | 0.277701E+11 | 103692.08 | 02-MAR-22:51 | 73541.71 | 0.64 |
April | 0.00 | 0.00 | 0.592645E+11 | 0.382432E+11 | 113527.75 | 30-APR-08:51 | 71163.35 | 0.79 |
May | 0.00 | 0.00 | 0.850537E+11 | 0.606451E+11 | 110914.38 | 01-MAY-08:51 | 69146.34 | 0.92 |
June | 0.00 | 0.00 | 0.915218E+11 | 0.662526E+11 | 93303.13 | 22-JUN-08:51 | 84398.50 | 0.94 |
July | 0.00 | 0.00 | 0.100907E+12 | 0.730685E+11 | 90340.81 | 26-JUL-08:62 | 85403.00 | 0.95 |
August | 0.00 | 0.00 | 0.100634E+12 | 0.724906E+11 | 90611.02 | 08-AUG-08:62 | 85253.33 | 0.95 |
September | 0.00 | 0.00 | 0.846855E+11 | 0.597033E+11 | 103776.18 | 25-SEP-08:62 | 75711.31 | 0.93 |
October | 0.00 | 0.00 | 0.724426E+11 | 0.477438E+11 | 114822.63 | 31-OCT-08:61 | 69137.58 | 0.87 |
November | 0.00 | 0.00 | 0.515056E+11 | 0.314800E+11 | 118182.64 | 01-NOV-08:11 | 69196.74 | 0.74 |
December | 0.00 | 0.00 | 0.320081E+11 | 0.186459E+11 | 104293.73 | 26-DEC-22:52 | 73829.45 | 0.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.774310E+12 | 0.525767E+12 | 0.77 | |||
Minimum of Months | 0.00 | 0.00 | 0.234788E+11 | 0.130304E+11 | 90340.81 | 69137.58 | 0.46 | |
Maximum of Months | 0.00 | 0.00 | 0.100907E+12 | 0.730685E+11 | 118182.64 | 85403.00 | 0.95 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.389126E+10 | 0.177746E+10 | 13983.04 | 29-JAN-09:01 | 10509.75 | 0.87 |
February | 0.00 | 0.00 | 0.477430E+10 | 0.238716E+10 | 14159.58 | 07-FEB-09:01 | 10618.89 | 0.91 |
March | 0.00 | 0.00 | 0.680122E+10 | 0.388003E+10 | 13953.59 | 02-MAR-19:02 | 10072.11 | 0.93 |
April | 0.00 | 0.00 | 0.917639E+10 | 0.580344E+10 | 14502.27 | 18-APR-08:61 | 10185.02 | 0.96 |
May | 0.00 | 0.00 | 0.132135E+11 | 0.966861E+10 | 14100.86 | 01-MAY-08:61 | 10240.04 | 0.98 |
June | 0.00 | 0.00 | 0.139093E+11 | 0.104583E+11 | 12450.34 | 08-JUN-08:62 | 11769.84 | 0.98 |
July | 0.00 | 0.00 | 0.156977E+11 | 0.120046E+11 | 12590.73 | 20-JUL-08:62 | 11927.15 | 0.98 |
August | 0.00 | 0.00 | 0.162139E+11 | 0.124095E+11 | 12399.43 | 08-AUG-08:62 | 12036.96 | 0.99 |
September | 0.00 | 0.00 | 0.139837E+11 | 0.105046E+11 | 12520.63 | 25-SEP-08:62 | 11677.80 | 0.98 |
October | 0.00 | 0.00 | 0.123845E+11 | 0.862246E+10 | 13725.75 | 31-OCT-08:61 | 11031.13 | 0.98 |
November | 0.00 | 0.00 | 0.885986E+10 | 0.539333E+10 | 14521.46 | 02-NOV-08:62 | 10396.06 | 0.96 |
December | 0.00 | 0.00 | 0.528515E+10 | 0.259328E+10 | 14156.86 | 06-DEC-09:02 | 10122.03 | 0.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.124191E+12 | 0.855028E+11 | 0.95 | |||
Minimum of Months | 0.00 | 0.00 | 0.389126E+10 | 0.177746E+10 | 12399.43 | 10072.11 | 0.87 | |
Maximum of Months | 0.00 | 0.00 | 0.162139E+11 | 0.124095E+11 | 14521.46 | 12036.96 | 0.99 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.158908E+10 | 0.642092E+09 | 14728.46 | 29-JAN-09:51 | 10805.51 | 0.50 |
February | 0.00 | 0.00 | 0.264891E+10 | 0.123190E+10 | 15080.14 | 07-FEB-09:41 | 10222.99 | 0.60 |
March | 0.00 | 0.00 | 0.512949E+10 | 0.289226E+10 | 15110.09 | 29-MAR-08:51 | 10371.97 | 0.72 |
April | 0.00 | 0.00 | 0.834403E+10 | 0.533707E+10 | 16852.53 | 30-APR-08:51 | 10732.67 | 0.85 |
May | 0.00 | 0.00 | 0.131278E+11 | 0.971979E+10 | 16529.28 | 01-MAY-08:51 | 10934.89 | 0.96 |
June | 0.00 | 0.00 | 0.140791E+11 | 0.107131E+11 | 14168.43 | 22-JUN-08:51 | 13478.12 | 0.98 |
July | 0.00 | 0.00 | 0.157547E+11 | 0.120985E+11 | 12379.61 | 20-JUL-08:62 | 11689.15 | 0.99 |
August | 0.00 | 0.00 | 0.159514E+11 | 0.121514E+11 | 12175.71 | 08-AUG-08:62 | 11806.12 | 0.99 |
September | 0.00 | 0.00 | 0.131895E+11 | 0.966170E+10 | 14985.05 | 25-SEP-07:32 | 11504.43 | 0.98 |
October | 0.00 | 0.00 | 0.109264E+11 | 0.719922E+10 | 16673.24 | 31-OCT-07:52 | 10737.89 | 0.94 |
November | 0.00 | 0.00 | 0.680907E+10 | 0.395889E+10 | 16926.55 | 01-NOV-08:11 | 10483.66 | 0.82 |
December | 0.00 | 0.00 | 0.284284E+10 | 0.127406E+10 | 14694.41 | 10-DEC-09:51 | 10945.67 | 0.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.110392E+12 | 0.768800E+11 | 0.83 | |||
Minimum of Months | 0.00 | 0.00 | 0.158908E+10 | 0.642092E+09 | 12175.71 | 10222.99 | 0.50 | |
Maximum of Months | 0.00 | 0.00 | 0.159514E+11 | 0.121514E+11 | 16926.55 | 13478.12 | 0.99 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.875148E+09 | 0.375535E+09 | 4479.40 | 29-JAN-09:01 | 2992.87 | 0.77 |
February | 0.00 | 0.00 | 0.113675E+10 | 0.536063E+09 | 4538.92 | 07-FEB-09:01 | 3021.31 | 0.87 |
March | 0.00 | 0.00 | 0.173889E+10 | 0.943207E+09 | 4401.53 | 29-MAR-08:61 | 2881.89 | 0.92 |
April | 0.00 | 0.00 | 0.231133E+10 | 0.139065E+10 | 4588.41 | 18-APR-08:61 | 2921.78 | 0.95 |
May | 0.00 | 0.00 | 0.340967E+10 | 0.239311E+10 | 4714.15 | 01-MAY-08:61 | 2788.04 | 0.97 |
June | 0.00 | 0.00 | 0.367529E+10 | 0.265900E+10 | 3949.48 | 08-JUN-08:62 | 3419.73 | 0.98 |
July | 0.00 | 0.00 | 0.418723E+10 | 0.308303E+10 | 3838.91 | 01-JUL-08:62 | 3556.29 | 0.98 |
August | 0.00 | 0.00 | 0.432156E+10 | 0.320276E+10 | 3875.25 | 27-AUG-08:62 | 3535.22 | 0.98 |
September | 0.00 | 0.00 | 0.365027E+10 | 0.260889E+10 | 4123.94 | 25-SEP-08:62 | 3301.50 | 0.98 |
October | 0.00 | 0.00 | 0.313702E+10 | 0.210616E+10 | 4572.33 | 31-OCT-08:61 | 3047.70 | 0.97 |
November | 0.00 | 0.00 | 0.216916E+10 | 0.123071E+10 | 4841.95 | 02-NOV-08:62 | 2832.17 | 0.95 |
December | 0.00 | 0.00 | 0.124040E+10 | 0.561886E+09 | 4518.27 | 06-DEC-09:02 | 2767.06 | 0.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.318527E+11 | 0.210910E+11 | 0.93 | |||
Minimum of Months | 0.00 | 0.00 | 0.875148E+09 | 0.375535E+09 | 3838.91 | 2767.06 | 0.77 | |
Maximum of Months | 0.00 | 0.00 | 0.432156E+10 | 0.320276E+10 | 4841.95 | 3556.29 | 0.98 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.304161E+09 | 0.109792E+09 | 4353.31 | 29-JAN-09:51 | 2893.84 | 0.40 |
February | 0.00 | 0.00 | 0.620931E+09 | 0.267181E+09 | 4631.59 | 08-FEB-22:51 | 2906.77 | 0.56 |
March | 0.00 | 0.00 | 0.134597E+10 | 0.727062E+09 | 4527.70 | 29-MAR-08:51 | 2794.04 | 0.71 |
April | 0.00 | 0.00 | 0.213819E+10 | 0.131249E+10 | 5044.27 | 30-APR-08:51 | 2910.35 | 0.85 |
May | 0.00 | 0.00 | 0.339416E+10 | 0.240184E+10 | 4901.43 | 02-MAY-08:61 | 3165.61 | 0.96 |
June | 0.00 | 0.00 | 0.372061E+10 | 0.270232E+10 | 4110.86 | 22-JUN-08:51 | 3753.55 | 0.98 |
July | 0.00 | 0.00 | 0.420218E+10 | 0.310351E+10 | 3745.94 | 01-JUL-08:62 | 3502.94 | 0.98 |
August | 0.00 | 0.00 | 0.425415E+10 | 0.315706E+10 | 3805.62 | 27-AUG-08:62 | 3468.50 | 0.98 |
September | 0.00 | 0.00 | 0.344940E+10 | 0.243394E+10 | 4448.82 | 25-SEP-08:62 | 2999.15 | 0.97 |
October | 0.00 | 0.00 | 0.276888E+10 | 0.175687E+10 | 5023.22 | 28-OCT-08:11 | 3030.03 | 0.93 |
November | 0.00 | 0.00 | 0.169172E+10 | 0.904531E+09 | 5217.27 | 01-NOV-08:11 | 2735.65 | 0.81 |
December | 0.00 | 0.00 | 0.661206E+09 | 0.272581E+09 | 4437.12 | 10-DEC-09:51 | 3018.25 | 0.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.285515E+11 | 0.191492E+11 | 0.81 | |||
Minimum of Months | 0.00 | 0.00 | 0.304161E+09 | 0.109792E+09 | 3745.94 | 2735.65 | 0.40 | |
Maximum of Months | 0.00 | 0.00 | 0.425415E+10 | 0.315706E+10 | 5217.27 | 3753.55 | 0.98 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.845277E+10 | 0.461134E+10 | 20867.98 | 29-JAN-09:01 | 14649.02 | 0.92 |
February | 0.00 | 0.00 | 0.879182E+10 | 0.491594E+10 | 21325.98 | 07-FEB-09:01 | 14682.34 | 0.92 |
March | 0.00 | 0.00 | 0.106718E+11 | 0.629098E+10 | 21186.72 | 02-MAR-19:02 | 13805.79 | 0.93 |
April | 0.00 | 0.00 | 0.123164E+11 | 0.755594E+10 | 22355.25 | 18-APR-08:61 | 13732.15 | 0.95 |
May | 0.00 | 0.00 | 0.165984E+11 | 0.113733E+11 | 23229.17 | 01-MAY-08:61 | 12927.98 | 0.97 |
June | 0.00 | 0.00 | 0.174717E+11 | 0.122793E+11 | 18204.21 | 07-JUN-08:62 | 17067.73 | 0.97 |
July | 0.00 | 0.00 | 0.203284E+11 | 0.150190E+11 | 18073.95 | 14-JUL-08:62 | 17140.14 | 0.98 |
August | 0.00 | 0.00 | 0.214442E+11 | 0.161056E+11 | 18114.05 | 18-AUG-08:62 | 17120.61 | 0.98 |
September | 0.00 | 0.00 | 0.194737E+11 | 0.141936E+11 | 19140.26 | 25-SEP-08:62 | 16113.95 | 0.97 |
October | 0.00 | 0.00 | 0.186584E+11 | 0.132461E+11 | 20984.34 | 31-OCT-08:61 | 15108.83 | 0.97 |
November | 0.00 | 0.00 | 0.148023E+11 | 0.972081E+10 | 23036.19 | 02-NOV-08:62 | 13635.44 | 0.97 |
December | 0.00 | 0.00 | 0.104731E+11 | 0.605061E+10 | 21398.13 | 06-DEC-09:02 | 13921.57 | 0.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.179483E+12 | 0.121363E+12 | 0.95 | |||
Minimum of Months | 0.00 | 0.00 | 0.845277E+10 | 0.461134E+10 | 18073.95 | 12927.98 | 0.92 | |
Maximum of Months | 0.00 | 0.00 | 0.214442E+11 | 0.161056E+11 | 23229.17 | 17140.14 | 0.98 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 126.09 | 24199.24 | 07-JAN-09:55 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 58.73 | 20221.80 | 11-FEB-16:06 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 49.42 | 21591.12 | 18-MAR-08:56 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25.95 | 18528.21 | 10-APR-08:36 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 13.61 | 17219.57 | 16-MAY-08:07 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.95 | 13686.72 | 09-JUN-08:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.61 | 13748.69 | 21-JUL-08:07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 13.65 | 14552.16 | 18-AUG-08:07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14.22 | 12357.82 | 01-SEP-08:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.28 | 20839.97 | 30-OCT-08:26 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 41.19 | 20721.86 | 13-NOV-09:26 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 69.01 | 20686.30 | 05-DEC-16:07 |
Annual Sum or Average | 0.00 | 38.30 | ||||
Minimum of Months | 0.00 | 0.00 | 11.61 | 12357.82 | ||
Maximum of Months | 0.00 | 0.00 | 126.09 | 24199.24 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 135337.65 | 456473.52 | 30-JAN-16:03 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 177611.10 | 533537.90 | 08-FEB-22:53 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 218663.33 | 550579.26 | 28-MAR-18:03 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 301542.58 | 632831.08 | 30-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 393484.47 | 757004.99 | 30-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 476144.91 | 810594.74 | 26-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 532743.41 | 855881.71 | 17-JUL-18:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 553420.18 | 854115.90 | 21-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 508362.19 | 857949.95 | 08-SEP-18:02 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 419482.14 | 791240.02 | 06-OCT-18:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 312223.75 | 663826.37 | 01-NOV-18:03 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 200150.86 | 559727.98 | 05-DEC-22:52 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 353350.84 | 0.00 | ||||
Minimum of Months | 135337.65 | 456473.52 | 0.00 | 0.00 | ||
Maximum of Months | 553420.18 | 857949.95 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 19150.86 | 40038.54 | 12-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 18623.27 | 39619.63 | 01-FEB-07:30 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17375.44 | 37730.63 | 01-MAR-07:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15654.15 | 34144.21 | 03-APR-06:30 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 13979.96 | 30749.60 | 01-MAY-06:30 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12791.38 | 27578.82 | 01-JUN-06:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 12395.58 | 26062.00 | 31-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 12949.15 | 28079.37 | 31-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 14244.72 | 31192.95 | 29-SEP-06:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 15954.48 | 35071.41 | 31-OCT-06:50 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17624.03 | 38142.56 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 18793.91 | 39825.81 | 29-DEC-07:30 |
Annual Sum or Average | 0.00 | 15779.34 | ||||
Minimum of Months | 0.00 | 0.00 | 12395.58 | 26062.00 | ||
Maximum of Months | 0.00 | 0.00 | 19150.86 | 40038.54 |
Report: FanReportMonthly
For: SWHSYS1 HPWH FAN
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.441993E+09 | 0.05 | 553.22 | 01-JAN-07:05 | 0.10 |
February | 0.380809E+09 | 0.05 | 553.22 | 01-FEB-05:10 | 0.10 |
March | 0.391399E+09 | 0.05 | 553.22 | 01-MAR-05:10 | 0.10 |
April | 0.333216E+09 | 0.05 | 553.22 | 01-APR-05:08 | 0.10 |
May | 0.299267E+09 | 0.05 | 553.22 | 01-MAY-05:17 | 0.10 |
June | 0.260439E+09 | 0.05 | 553.22 | 01-JUN-07:15 | 0.10 |
July | 0.256368E+09 | 0.05 | 553.22 | 01-JUL-07:15 | 0.10 |
August | 0.265137E+09 | 0.05 | 553.22 | 01-AUG-07:15 | 0.10 |
September | 0.284036E+09 | 0.05 | 553.22 | 01-SEP-07:15 | 0.10 |
October | 0.335337E+09 | 0.05 | 553.22 | 01-OCT-05:10 | 0.10 |
November | 0.367986E+09 | 0.05 | 553.22 | 01-NOV-05:07 | 0.10 |
December | 0.421999E+09 | 0.05 | 553.22 | 01-DEC-05:10 | 0.10 |
Annual Sum or Average | 0.403799E+10 | 0.05 | |||
Minimum of Months | 0.256368E+09 | 0.05 | 553.22 | 0.10 | |
Maximum of Months | 0.441993E+09 | 0.05 | 553.22 | 0.10 |
Report: FanReportMonthly
For: SWHSYSLAUNDRY HPWH FAN
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.555722E+09 | 0.05 | 700.51 | 01-JAN-17:10 | 0.10 |
February | 0.502117E+09 | 0.05 | 700.51 | 01-FEB-17:10 | 0.10 |
March | 0.556239E+09 | 0.05 | 700.51 | 01-MAR-17:10 | 0.10 |
April | 0.538243E+09 | 0.05 | 700.51 | 01-APR-16:10 | 0.10 |
May | 0.541291E+09 | 0.05 | 700.51 | 01-MAY-16:10 | 0.10 |
June | 0.494872E+09 | 0.05 | 659.67 | 01-JUN-16:10 | 0.10 |
July | 0.497089E+09 | 0.05 | 634.54 | 31-JUL-16:10 | 0.10 |
August | 0.502473E+09 | 0.05 | 648.62 | 31-AUG-16:10 | 0.10 |
September | 0.511815E+09 | 0.05 | 687.16 | 30-SEP-16:10 | 0.10 |
October | 0.555425E+09 | 0.05 | 700.51 | 01-OCT-16:10 | 0.10 |
November | 0.538205E+09 | 0.05 | 700.51 | 01-NOV-16:10 | 0.10 |
December | 0.556047E+09 | 0.05 | 700.51 | 01-DEC-17:10 | 0.10 |
Annual Sum or Average | 0.634954E+10 | 0.05 | |||
Minimum of Months | 0.494872E+09 | 0.05 | 634.54 | 0.10 | |
Maximum of Months | 0.556239E+09 | 0.05 | 700.51 | 0.10 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.69 | 1299.30 | 01-JAN-09:02 | 0.88 |
February | 0.244774E+10 | 0.69 | 1299.30 | 01-FEB-09:52 | 0.87 |
March | 0.271000E+10 | 0.69 | 1299.30 | 01-MAR-07:42 | 0.87 |
April | 0.262258E+10 | 0.69 | 1299.30 | 01-APR-08:51 | 0.87 |
May | 0.271000E+10 | 0.69 | 1299.30 | 01-MAY-08:51 | 0.87 |
June | 0.262258E+10 | 0.69 | 1299.30 | 01-JUN-08:62 | 0.87 |
July | 0.271000E+10 | 0.69 | 1299.30 | 01-JUL-08:62 | 0.87 |
August | 0.271000E+10 | 0.69 | 1299.30 | 01-AUG-08:62 | 0.87 |
September | 0.262258E+10 | 0.69 | 1299.30 | 01-SEP-08:62 | 0.87 |
October | 0.271000E+10 | 0.69 | 1299.30 | 01-OCT-08:62 | 0.87 |
November | 0.262258E+10 | 0.69 | 1299.30 | 01-NOV-08:11 | 0.87 |
December | 0.271000E+10 | 0.69 | 1299.30 | 01-DEC-09:41 | 0.87 |
Annual Sum or Average | 0.319080E+11 | 0.69 | |||
Minimum of Months | 0.244774E+10 | 0.69 | 1299.30 | 0.87 | |
Maximum of Months | 0.271000E+10 | 0.69 | 1299.30 | 0.88 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.357098E+11 | 0.82 | 24393.30 | 24-JAN-22:10 | 1.17 |
February | 0.325850E+11 | 0.82 | 26590.03 | 07-FEB-22:10 | 1.23 |
March | 0.371966E+11 | 0.84 | 28303.20 | 27-MAR-21:10 | 1.28 |
April | 0.374207E+11 | 0.85 | 29742.66 | 28-APR-21:20 | 1.32 |
May | 0.424032E+11 | 0.90 | 32393.49 | 31-MAY-21:10 | 1.39 |
June | 0.428953E+11 | 0.92 | 32943.51 | 09-JUN-21:10 | 1.41 |
July | 0.465205E+11 | 0.95 | 34952.15 | 21-JUL-21:10 | 1.46 |
August | 0.486931E+11 | 0.97 | 37507.74 | 16-AUG-21:10 | 1.53 |
September | 0.448180E+11 | 0.94 | 37041.95 | 06-SEP-21:10 | 1.51 |
October | 0.443015E+11 | 0.92 | 36730.13 | 05-OCT-21:20 | 1.50 |
November | 0.397540E+11 | 0.88 | 33755.05 | 02-NOV-21:10 | 1.43 |
December | 0.373578E+11 | 0.84 | 27920.00 | 01-DEC-22:10 | 1.27 |
Annual Sum or Average | 0.489655E+12 | 0.89 | |||
Minimum of Months | 0.325850E+11 | 0.82 | 24393.30 | 1.17 | |
Maximum of Months | 0.486931E+11 | 0.97 | 37507.74 | 1.53 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.26 | 76.61 | 01-JAN-00:10 | 0.26 |
February | 0.185347E+09 | 0.26 | 76.61 | 01-FEB-00:03 | 0.26 |
March | 0.205205E+09 | 0.26 | 76.61 | 01-MAR-00:03 | 0.26 |
April | 0.198586E+09 | 0.26 | 76.61 | 01-APR-00:10 | 0.26 |
May | 0.205205E+09 | 0.26 | 76.61 | 01-MAY-00:05 | 0.26 |
June | 0.198586E+09 | 0.26 | 76.61 | 01-JUN-00:05 | 0.26 |
July | 0.205205E+09 | 0.26 | 76.61 | 01-JUL-00:10 | 0.26 |
August | 0.205205E+09 | 0.26 | 76.61 | 01-AUG-00:05 | 0.26 |
September | 0.198586E+09 | 0.26 | 76.61 | 01-SEP-00:05 | 0.26 |
October | 0.205205E+09 | 0.26 | 76.61 | 01-OCT-00:10 | 0.26 |
November | 0.198586E+09 | 0.26 | 76.61 | 01-NOV-00:05 | 0.26 |
December | 0.205205E+09 | 0.26 | 76.61 | 01-DEC-00:05 | 0.26 |
Annual Sum or Average | 0.241613E+10 | 0.26 | |||
Minimum of Months | 0.185347E+09 | 0.26 | 76.61 | 0.26 | |
Maximum of Months | 0.205205E+09 | 0.26 | 76.61 | 0.26 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:05 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.26 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.26 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.26 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.26 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:10 | 0.26 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.26 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:10 | 0.26 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:10 | 0.26 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:10 | 0.26 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.26 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.26 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.26 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.212700E+09 | 0.50 | 759.55 | 01-JAN-09:02 | 0.57 |
February | 0.244388E+09 | 0.52 | 759.55 | 01-FEB-16:02 | 0.57 |
March | 0.352343E+09 | 0.53 | 759.55 | 01-MAR-09:01 | 0.57 |
April | 0.435319E+09 | 0.54 | 759.55 | 01-APR-08:62 | 0.57 |
May | 0.628954E+09 | 0.56 | 759.55 | 01-MAY-08:61 | 0.57 |
June | 0.674866E+09 | 0.56 | 759.55 | 01-JUN-08:62 | 0.57 |
July | 0.779623E+09 | 0.56 | 759.55 | 01-JUL-08:62 | 0.57 |
August | 0.814687E+09 | 0.56 | 759.55 | 01-AUG-08:62 | 0.57 |
September | 0.674190E+09 | 0.56 | 759.55 | 01-SEP-08:62 | 0.57 |
October | 0.578572E+09 | 0.56 | 759.55 | 01-OCT-08:62 | 0.57 |
November | 0.410640E+09 | 0.55 | 759.55 | 01-NOV-08:61 | 0.57 |
December | 0.270333E+09 | 0.52 | 759.55 | 01-DEC-09:01 | 0.57 |
Annual Sum or Average | 0.607662E+10 | 0.54 | |||
Minimum of Months | 0.212700E+09 | 0.50 | 759.55 | 0.57 | |
Maximum of Months | 0.814687E+09 | 0.56 | 759.55 | 0.57 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 93054236.22 | 0.30 | 745.09 | 01-JAN-16:01 | 0.57 |
February | 0.138165E+09 | 0.34 | 745.09 | 01-FEB-16:02 | 0.57 |
March | 0.265377E+09 | 0.40 | 745.09 | 01-MAR-07:42 | 0.57 |
April | 0.396667E+09 | 0.48 | 745.09 | 01-APR-08:51 | 0.57 |
May | 0.628917E+09 | 0.55 | 745.09 | 01-MAY-08:51 | 0.57 |
June | 0.694176E+09 | 0.56 | 745.09 | 01-JUN-08:62 | 0.57 |
July | 0.790541E+09 | 0.56 | 745.09 | 01-JUL-08:62 | 0.57 |
August | 0.803349E+09 | 0.56 | 745.09 | 01-AUG-08:62 | 0.57 |
September | 0.630357E+09 | 0.56 | 745.09 | 01-SEP-08:62 | 0.57 |
October | 0.508041E+09 | 0.54 | 745.09 | 01-OCT-08:62 | 0.57 |
November | 0.320628E+09 | 0.47 | 745.09 | 01-NOV-08:11 | 0.57 |
December | 0.152115E+09 | 0.34 | 745.09 | 01-DEC-09:41 | 0.57 |
Annual Sum or Average | 0.542139E+10 | 0.47 | |||
Minimum of Months | 93054236.22 | 0.30 | 745.09 | 0.57 | |
Maximum of Months | 0.803349E+09 | 0.56 | 745.09 | 0.57 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140837E+10 | 0.54 | 1121.33 | 28-JAN-13:40 | 0.57 |
February | 0.135628E+10 | 0.56 | 1272.84 | 05-FEB-13:30 | 0.57 |
March | 0.160509E+10 | 0.57 | 1159.03 | 27-MAR-13:40 | 0.57 |
April | 0.172628E+10 | 0.57 | 1089.98 | 28-APR-17:20 | 0.57 |
May | 0.217809E+10 | 0.57 | 1230.02 | 31-MAY-19:10 | 0.57 |
June | 0.222447E+10 | 0.57 | 1249.96 | 09-JUN-17:20 | 0.57 |
July | 0.256109E+10 | 0.57 | 1358.48 | 21-JUL-20:20 | 0.57 |
August | 0.271651E+10 | 0.57 | 1373.31 | 16-AUG-17:20 | 0.57 |
September | 0.253460E+10 | 0.57 | 1427.31 | 26-SEP-13:10 | 0.57 |
October | 0.253150E+10 | 0.57 | 1451.77 | 09-OCT-13:30 | 0.57 |
November | 0.211947E+10 | 0.57 | 1394.46 | 05-NOV-13:30 | 0.57 |
December | 0.162958E+10 | 0.56 | 1297.18 | 03-DEC-13:00 | 0.57 |
Annual Sum or Average | 0.245913E+11 | 0.57 | |||
Minimum of Months | 0.135628E+10 | 0.54 | 1089.98 | 0.57 | |
Maximum of Months | 0.271651E+10 | 0.57 | 1451.77 | 0.57 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.120335E+10 | 0.27 | 4806.98 | 01-JAN-09:02 | 0.57 |
February | 0.140228E+10 | 0.30 | 4806.98 | 01-FEB-09:52 | 0.57 |
March | 0.216629E+10 | 0.37 | 4806.98 | 01-MAR-07:42 | 0.57 |
April | 0.291143E+10 | 0.45 | 4806.98 | 01-APR-08:51 | 0.57 |
May | 0.414837E+10 | 0.53 | 4806.98 | 01-MAY-08:51 | 0.57 |
June | 0.450371E+10 | 0.54 | 4806.98 | 01-JUN-08:62 | 0.57 |
July | 0.512645E+10 | 0.55 | 4806.98 | 01-JUL-08:62 | 0.57 |
August | 0.509481E+10 | 0.54 | 4806.98 | 01-AUG-08:62 | 0.57 |
September | 0.405030E+10 | 0.54 | 4806.98 | 01-SEP-08:62 | 0.57 |
October | 0.343925E+10 | 0.50 | 4806.98 | 01-OCT-08:62 | 0.57 |
November | 0.242685E+10 | 0.43 | 4806.98 | 01-NOV-08:11 | 0.57 |
December | 0.152294E+10 | 0.30 | 4806.98 | 01-DEC-09:41 | 0.57 |
Annual Sum or Average | 0.379961E+11 | 0.44 | |||
Minimum of Months | 0.120335E+10 | 0.27 | 4806.98 | 0.57 | |
Maximum of Months | 0.512645E+10 | 0.55 | 4806.98 | 0.57 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.209239E+09 | 0.51 | 681.68 | 01-JAN-09:02 | 0.57 |
February | 0.237351E+09 | 0.52 | 681.68 | 01-FEB-09:02 | 0.57 |
March | 0.331790E+09 | 0.54 | 681.68 | 01-MAR-09:01 | 0.57 |
April | 0.440117E+09 | 0.55 | 681.68 | 01-APR-08:62 | 0.57 |
May | 0.643694E+09 | 0.56 | 681.68 | 01-MAY-08:61 | 0.57 |
June | 0.673744E+09 | 0.56 | 681.68 | 01-JUN-08:62 | 0.57 |
July | 0.787129E+09 | 0.56 | 681.68 | 01-JUL-08:62 | 0.57 |
August | 0.824631E+09 | 0.56 | 681.68 | 01-AUG-08:62 | 0.57 |
September | 0.674824E+09 | 0.56 | 681.68 | 01-SEP-08:62 | 0.57 |
October | 0.592960E+09 | 0.56 | 681.68 | 01-OCT-08:62 | 0.57 |
November | 0.415642E+09 | 0.55 | 681.68 | 01-NOV-08:61 | 0.57 |
December | 0.260591E+09 | 0.52 | 681.68 | 01-DEC-09:01 | 0.57 |
Annual Sum or Average | 0.609171E+10 | 0.55 | |||
Minimum of Months | 0.209239E+09 | 0.51 | 681.68 | 0.57 | |
Maximum of Months | 0.824631E+09 | 0.56 | 681.68 | 0.57 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 94898410.67 | 0.31 | 668.75 | 01-JAN-09:02 | 0.57 |
February | 0.135447E+09 | 0.35 | 668.75 | 01-FEB-09:52 | 0.57 |
March | 0.250358E+09 | 0.41 | 668.75 | 01-MAR-07:42 | 0.57 |
April | 0.400321E+09 | 0.49 | 668.75 | 01-APR-08:51 | 0.57 |
May | 0.641655E+09 | 0.55 | 668.75 | 01-MAY-08:51 | 0.57 |
June | 0.689193E+09 | 0.56 | 668.75 | 01-JUN-08:62 | 0.57 |
July | 0.798617E+09 | 0.56 | 668.75 | 01-JUL-08:62 | 0.57 |
August | 0.814613E+09 | 0.56 | 668.75 | 01-AUG-08:62 | 0.57 |
September | 0.634186E+09 | 0.56 | 668.75 | 01-SEP-08:62 | 0.57 |
October | 0.521776E+09 | 0.54 | 668.75 | 01-OCT-08:62 | 0.57 |
November | 0.316425E+09 | 0.47 | 668.75 | 01-NOV-08:11 | 0.57 |
December | 0.145002E+09 | 0.34 | 668.75 | 01-DEC-09:41 | 0.57 |
Annual Sum or Average | 0.544249E+10 | 0.48 | |||
Minimum of Months | 94898410.67 | 0.31 | 668.75 | 0.57 | |
Maximum of Months | 0.814613E+09 | 0.56 | 668.75 | 0.57 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 50142775.38 | 0.50 | 205.36 | 01-JAN-16:01 | 0.57 |
February | 58629548.74 | 0.51 | 205.36 | 01-FEB-16:02 | 0.57 |
March | 88144446.48 | 0.53 | 205.36 | 01-MAR-09:01 | 0.57 |
April | 0.112223E+09 | 0.54 | 205.36 | 01-APR-08:62 | 0.57 |
May | 0.165287E+09 | 0.56 | 205.36 | 01-MAY-08:61 | 0.57 |
June | 0.178591E+09 | 0.56 | 205.36 | 01-JUN-08:62 | 0.57 |
July | 0.208463E+09 | 0.56 | 205.36 | 01-JUL-08:62 | 0.57 |
August | 0.216214E+09 | 0.56 | 205.36 | 01-AUG-08:62 | 0.57 |
September | 0.176408E+09 | 0.56 | 205.36 | 01-SEP-08:62 | 0.57 |
October | 0.147566E+09 | 0.56 | 205.36 | 01-OCT-08:62 | 0.57 |
November | 0.102058E+09 | 0.54 | 205.36 | 01-NOV-08:61 | 0.57 |
December | 63810976.59 | 0.51 | 205.36 | 01-DEC-09:01 | 0.57 |
Annual Sum or Average | 0.156754E+10 | 0.54 | |||
Minimum of Months | 50142775.38 | 0.50 | 205.36 | 0.57 | |
Maximum of Months | 0.216214E+09 | 0.56 | 205.36 | 0.57 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 21247284.58 | 0.30 | 201.52 | 01-JAN-16:01 | 0.57 |
February | 32805597.77 | 0.34 | 201.52 | 01-FEB-16:02 | 0.57 |
March | 67653368.41 | 0.41 | 201.52 | 01-MAR-07:42 | 0.57 |
April | 0.103310E+09 | 0.49 | 201.52 | 01-APR-08:51 | 0.57 |
May | 0.165312E+09 | 0.55 | 201.52 | 01-MAY-08:51 | 0.57 |
June | 0.183551E+09 | 0.56 | 201.52 | 01-JUN-08:62 | 0.57 |
July | 0.210868E+09 | 0.56 | 201.52 | 01-JUL-08:62 | 0.57 |
August | 0.212869E+09 | 0.56 | 201.52 | 01-AUG-08:62 | 0.57 |
September | 0.164900E+09 | 0.56 | 201.52 | 01-SEP-08:62 | 0.57 |
October | 0.129807E+09 | 0.54 | 201.52 | 01-OCT-08:62 | 0.57 |
November | 79755977.59 | 0.47 | 201.52 | 01-NOV-08:11 | 0.57 |
December | 35016278.98 | 0.34 | 201.52 | 01-DEC-09:41 | 0.57 |
Annual Sum or Average | 0.140710E+10 | 0.47 | |||
Minimum of Months | 21247284.58 | 0.30 | 201.52 | 0.57 | |
Maximum of Months | 0.212869E+09 | 0.56 | 201.52 | 0.57 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.426953E+09 | 0.53 | 973.91 | 01-JAN-09:02 | 0.57 |
February | 0.426828E+09 | 0.53 | 973.91 | 01-FEB-09:02 | 0.57 |
March | 0.521624E+09 | 0.53 | 973.91 | 01-MAR-09:01 | 0.57 |
April | 0.586024E+09 | 0.54 | 973.91 | 01-APR-08:62 | 0.57 |
May | 0.793496E+09 | 0.55 | 973.91 | 01-MAY-08:61 | 0.57 |
June | 0.830094E+09 | 0.56 | 973.91 | 01-JUN-08:62 | 0.57 |
July | 0.988026E+09 | 0.56 | 973.91 | 01-JUL-08:62 | 0.57 |
August | 0.105608E+10 | 0.56 | 973.91 | 01-AUG-08:62 | 0.57 |
September | 0.947763E+09 | 0.56 | 973.91 | 01-SEP-08:62 | 0.57 |
October | 0.907817E+09 | 0.56 | 973.91 | 01-OCT-08:62 | 0.57 |
November | 0.700353E+09 | 0.55 | 973.91 | 01-NOV-08:61 | 0.57 |
December | 0.501103E+09 | 0.53 | 973.91 | 01-DEC-09:01 | 0.57 |
Annual Sum or Average | 0.868616E+10 | 0.55 | |||
Minimum of Months | 0.426828E+09 | 0.53 | 973.91 | 0.57 | |
Maximum of Months | 0.105608E+10 | 0.56 | 973.91 | 0.57 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 2674137.82 | 2430791.28 | 148.90 | 07-JAN-09:55 | 135.35 | 135.35 | 47.72 | 0.18 |
February | 1075970.94 | 978057.59 | 138.23 | 16-FEB-09:54 | 125.65 | 125.65 | 54.78 | 0.17 |
March | 928615.60 | 844111.58 | 138.49 | 18-MAR-08:56 | 125.88 | 125.88 | 48.52 | 0.17 |
April | 461135.90 | 419172.54 | 121.94 | 01-APR-08:55 | 110.84 | 110.84 | 49.18 | 0.14 |
May | 266126.65 | 241909.12 | 117.33 | 16-MAY-08:07 | 106.65 | 106.65 | 49.42 | 0.14 |
June | 272873.23 | 248041.77 | 98.74 | 29-JUN-08:07 | 89.75 | 89.75 | 50.87 | 0.11 |
July | 226784.23 | 206146.87 | 98.45 | 08-JUL-08:07 | 89.49 | 89.49 | 50.57 | 0.11 |
August | 259422.27 | 235814.84 | 101.21 | 18-AUG-08:07 | 92.00 | 92.00 | 49.38 | 0.12 |
September | 282391.89 | 256694.22 | 91.00 | 08-SEP-08:07 | 82.72 | 82.72 | 50.67 | 0.10 |
October | 444306.74 | 403874.82 | 136.00 | 30-OCT-08:26 | 123.63 | 123.63 | 48.93 | 0.16 |
November | 757073.00 | 688179.36 | 138.01 | 13-NOV-09:26 | 125.45 | 125.45 | 49.62 | 0.17 |
December | 1383820.68 | 1257893.00 | 139.52 | 30-DEC-09:55 | 126.83 | 126.83 | 55.05 | 0.17 |
Annual Sum or Average | 9032658.95 | 8210686.98 | ||||||
Minimum of Months | 226784.23 | 206146.87 | 91.00 | 82.72 | 82.72 | 47.72 | 0.10 | |
Maximum of Months | 2674137.82 | 2430791.28 | 148.90 | 135.35 | 135.35 | 55.05 | 0.18 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.348318E+09 | 0.316621E+09 | 729.63 | 29-JAN-22:53 | 663.24 | 663.24 | 7.43 | 14.05 |
February | 0.471099E+09 | 0.428229E+09 | 1182.05 | 06-FEB-19:02 | 1074.48 | 1074.48 | 7.12 | 17.37 |
March | 0.754605E+09 | 0.685936E+09 | 1197.06 | 28-MAR-18:03 | 1088.13 | 1088.13 | 6.84 | 17.46 |
April | 0.113190E+10 | 0.102890E+10 | 1715.95 | 30-APR-18:03 | 1559.80 | 1559.80 | 6.73 | 20.38 |
May | 0.189826E+10 | 0.172552E+10 | 2645.83 | 30-MAY-18:03 | 2405.06 | 2405.06 | 6.73 | 24.42 |
June | 0.256471E+10 | 0.233132E+10 | 3403.20 | 26-JUN-18:03 | 3093.51 | 3093.51 | 6.73 | 27.08 |
July | 0.331127E+10 | 0.300994E+10 | 4135.41 | 17-JUL-18:02 | 3759.09 | 3759.09 | 6.73 | 29.31 |
August | 0.359735E+10 | 0.326999E+10 | 4001.03 | 30-AUG-18:02 | 3636.93 | 3636.93 | 6.73 | 28.92 |
September | 0.296396E+10 | 0.269424E+10 | 3791.65 | 08-SEP-18:02 | 3446.61 | 3446.61 | 6.73 | 28.29 |
October | 0.209201E+10 | 0.190163E+10 | 2917.03 | 06-OCT-18:03 | 2651.58 | 2651.58 | 6.73 | 25.42 |
November | 0.117905E+10 | 0.107176E+10 | 1939.40 | 01-NOV-18:03 | 1762.92 | 1762.92 | 6.73 | 21.46 |
December | 0.610425E+09 | 0.554876E+09 | 1252.29 | 04-DEC-21:10 | 1138.33 | 1138.33 | 7.16 | 17.81 |
Annual Sum or Average | 0.209230E+11 | 0.190190E+11 | ||||||
Minimum of Months | 0.348318E+09 | 0.316621E+09 | 729.63 | 663.24 | 663.24 | 6.73 | 14.05 | |
Maximum of Months | 0.359735E+10 | 0.326999E+10 | 4135.41 | 3759.09 | 3759.09 | 7.43 | 29.31 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.142008E+11 | 0.129085E+11 | 5301.98 | 01-JAN-00:10 | 4819.50 | 4819.50 | 8.63 | 37.53 |
February | 0.128265E+11 | 0.116593E+11 | 5301.98 | 01-FEB-00:03 | 4819.50 | 4819.50 | 8.92 | 37.53 |
March | 0.142008E+11 | 0.129085E+11 | 5301.98 | 01-MAR-00:03 | 4819.50 | 4819.50 | 9.08 | 37.53 |
April | 0.137427E+11 | 0.124921E+11 | 5301.98 | 01-APR-00:10 | 4819.50 | 4819.50 | 9.43 | 37.53 |
May | 0.142008E+11 | 0.129085E+11 | 5301.98 | 01-MAY-00:05 | 4819.50 | 4819.50 | 9.23 | 37.53 |
June | 0.137427E+11 | 0.124921E+11 | 5301.98 | 01-JUN-00:05 | 4819.50 | 4819.50 | 9.30 | 37.53 |
July | 0.142008E+11 | 0.129085E+11 | 5301.98 | 01-JUL-00:10 | 4819.50 | 4819.50 | 9.84 | 37.53 |
August | 0.142008E+11 | 0.129085E+11 | 5301.98 | 01-AUG-00:05 | 4819.50 | 4819.50 | 10.10 | 37.53 |
September | 0.137427E+11 | 0.124921E+11 | 5301.98 | 01-SEP-00:05 | 4819.50 | 4819.50 | 9.62 | 37.53 |
October | 0.142008E+11 | 0.129085E+11 | 5301.98 | 01-OCT-00:10 | 4819.50 | 4819.50 | 9.71 | 37.53 |
November | 0.137427E+11 | 0.124921E+11 | 5301.98 | 01-NOV-00:05 | 4819.50 | 4819.50 | 8.93 | 37.53 |
December | 0.142008E+11 | 0.129085E+11 | 5301.98 | 01-DEC-00:05 | 4819.50 | 4819.50 | 8.79 | 37.53 |
Annual Sum or Average | 0.167203E+12 | 0.151988E+12 | ||||||
Minimum of Months | 0.128265E+11 | 0.116593E+11 | 5301.98 | 4819.50 | 4819.50 | 8.63 | 37.53 | |
Maximum of Months | 0.142008E+11 | 0.129085E+11 | 5301.98 | 4819.50 | 4819.50 | 10.10 | 37.53 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 52.06 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 52.52 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 52.87 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 55.30 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 55.66 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 56.12 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 56.47 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 56.33 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 56.04 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 55.19 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 55.05 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:05 | 14.37 | 14.37 | 52.94 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 52.06 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 56.47 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 50.33 | 79.40 | 126.09 | 24199.24 | 07-JAN-09:55 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 45.52 | 45.52 | 58.73 | 20221.80 | 11-FEB-16:06 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 48.85 | 48.85 | 49.42 | 21591.12 | 18-MAR-08:56 |
April | 0.00 | 0.00 | 01-APR-00:10 | 49.77 | 49.77 | 25.95 | 18528.21 | 10-APR-08:36 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 49.69 | 49.69 | 13.61 | 17219.57 | 16-MAY-08:07 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 50.59 | 50.59 | 13.95 | 13686.72 | 09-JUN-08:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 50.58 | 50.58 | 11.61 | 13748.69 | 21-JUL-08:07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 50.14 | 50.14 | 13.65 | 14552.16 | 18-AUG-08:07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 49.97 | 49.97 | 14.22 | 12357.82 | 01-SEP-08:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 51.62 | 51.62 | 22.28 | 20839.97 | 30-OCT-08:26 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 48.59 | 48.59 | 41.19 | 20721.86 | 13-NOV-09:26 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 47.23 | 47.23 | 69.01 | 20686.30 | 05-DEC-16:07 |
Annual Sum or Average | 0.00 | 38.30 | ||||||
Minimum of Months | 0.00 | 0.00 | 45.52 | 45.52 | 11.61 | 12357.82 | ||
Maximum of Months | 0.00 | 0.00 | 51.62 | 79.40 | 126.09 | 24199.24 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 135337.65 | 456473.52 | 30-JAN-16:03 | 10.27 | 7.37 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 177611.10 | 533537.90 | 08-FEB-22:53 | 10.50 | 7.11 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 218663.33 | 550579.26 | 28-MAR-18:03 | 10.31 | 6.81 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 301542.58 | 632831.08 | 30-APR-18:03 | 10.72 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 393484.47 | 757004.99 | 30-MAY-18:03 | 11.51 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 476144.91 | 810594.74 | 26-JUN-18:03 | 11.86 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 532743.41 | 855881.71 | 17-JUL-18:02 | 12.14 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 553420.18 | 854115.90 | 21-AUG-18:03 | 12.13 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 508362.19 | 857949.95 | 08-SEP-18:02 | 12.16 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 419482.14 | 791240.02 | 06-OCT-18:03 | 11.73 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 312223.75 | 663826.37 | 01-NOV-18:03 | 10.92 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 200150.86 | 559727.98 | 05-DEC-22:52 | 10.82 | 7.26 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 353350.84 | 0.00 | ||||||
Minimum of Months | 135337.65 | 456473.52 | 10.27 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 553420.18 | 857949.95 | 12.16 | 7.37 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 52.06 | 59.99 | 19150.86 | 40038.54 | 12-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 52.52 | 59.97 | 18623.27 | 39619.63 | 01-FEB-07:30 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 52.87 | 59.97 | 17375.44 | 37730.63 | 01-MAR-07:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 55.30 | 59.97 | 15654.15 | 34144.21 | 03-APR-06:30 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 55.66 | 59.98 | 13979.96 | 30749.60 | 01-MAY-06:30 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 56.12 | 60.00 | 12791.38 | 27578.82 | 01-JUN-06:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.47 | 59.99 | 12395.58 | 26062.00 | 31-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 56.33 | 60.00 | 12949.15 | 28079.37 | 31-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 56.04 | 60.00 | 14244.72 | 31192.95 | 29-SEP-06:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 55.19 | 59.97 | 15954.48 | 35071.41 | 31-OCT-06:50 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 55.05 | 59.97 | 17624.03 | 38142.56 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 52.94 | 59.97 | 18793.91 | 39825.81 | 29-DEC-07:30 |
Annual Sum or Average | 0.00 | 15779.34 | ||||||
Minimum of Months | 0.00 | 0.00 | 52.06 | 59.97 | 12395.58 | 26062.00 | ||
Maximum of Months | 0.00 | 0.00 | 56.47 | 60.00 | 19150.86 | 40038.54 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.101545E+09 | 0.00 | 0.251376E+12 | 0.357098E+11 | 0.00 | 0.00 |
February | 12283566.92 | 0.00 | 0.304506E+12 | 0.325850E+11 | 0.00 | 0.00 |
March | 967263.72 | 0.00 | 0.417461E+12 | 0.371966E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.571125E+12 | 0.374207E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.768577E+12 | 0.424032E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.923734E+12 | 0.428953E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.107359E+13 | 0.465205E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.111880E+13 | 0.486931E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.998701E+12 | 0.448180E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.839104E+12 | 0.443015E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.594053E+12 | 0.397540E+11 | 0.00 | 0.00 |
December | 22310508.23 | 0.00 | 0.389347E+12 | 0.373578E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.137106E+09 | 0.00 | 0.825038E+13 | 0.489655E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.251376E+12 | 0.325850E+11 | 0.00 | 0.00 |
Maximum of Months | 0.101545E+09 | 0.00 | 0.111880E+13 | 0.486931E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 66222.95 | 0.00 | 0.213661E+11 | 0.271000E+10 | 0.00 | 0.00 |
February | 4623.58 | 0.00 | 0.262802E+11 | 0.244774E+10 | 0.00 | 0.00 |
March | 7506.99 | 0.00 | 0.338636E+11 | 0.271000E+10 | 0.00 | 0.00 |
April | 5365.52 | 0.00 | 0.427194E+11 | 0.262258E+10 | 0.00 | 0.00 |
May | 3547.20 | 0.00 | 0.520701E+11 | 0.271000E+10 | 0.00 | 0.00 |
June | 2569.45 | 0.00 | 0.627577E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 4158.71 | 0.00 | 0.738308E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 3604.71 | 0.00 | 0.760364E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 2246.62 | 0.00 | 0.674343E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 6106.18 | 0.00 | 0.564372E+11 | 0.271000E+10 | 0.00 | 0.00 |
November | 6914.22 | 0.00 | 0.439885E+11 | 0.262258E+10 | 0.00 | 0.00 |
December | 8288.12 | 0.00 | 0.326690E+11 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 121154.24 | 0.00 | 0.589453E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 2246.62 | 0.00 | 0.213661E+11 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 66222.95 | 0.00 | 0.760364E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.357098E+11 | 0.251376E+12 | 0.101545E+09 | 0.583726E+10 | 0.319177E+10 | 0.00 | 0.00 | 0.00 |
February | 0.325850E+11 | 0.304506E+12 | 12283566.92 | 0.234068E+10 | 0.131419E+11 | 0.00 | 0.00 | 0.00 |
March | 0.371966E+11 | 0.417461E+12 | 967263.72 | 0.113449E+11 | 0.365702E+11 | 0.00 | 0.00 | 0.00 |
April | 0.374207E+11 | 0.571125E+12 | 0.00 | 0.923939E+10 | 0.112698E+12 | 0.00 | 0.00 | 0.00 |
May | 0.424032E+11 | 0.768577E+12 | 0.00 | 0.547359E+10 | 0.273851E+12 | 0.00 | 0.00 | 0.00 |
June | 0.428953E+11 | 0.923734E+12 | 0.00 | 0.372842E+09 | 0.432918E+12 | 0.00 | 0.00 | 0.00 |
July | 0.465205E+11 | 0.107359E+13 | 0.00 | 0.943695E+09 | 0.557649E+12 | 0.00 | 0.00 | 0.00 |
August | 0.486931E+11 | 0.111880E+13 | 0.00 | 0.00 | 0.587395E+12 | 0.00 | 0.00 | 0.00 |
September | 0.448180E+11 | 0.998701E+12 | 0.00 | 81539613.16 | 0.492297E+12 | 0.00 | 0.00 | 0.00 |
October | 0.443015E+11 | 0.839104E+12 | 0.00 | 0.148840E+10 | 0.325924E+12 | 0.00 | 0.00 | 0.00 |
November | 0.397540E+11 | 0.594053E+12 | 0.00 | 0.195709E+10 | 0.110163E+12 | 0.00 | 0.00 | 0.00 |
December | 0.373578E+11 | 0.389347E+12 | 22310508.23 | 0.302385E+10 | 0.237267E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.489655E+12 | 0.825038E+13 | 0.137106E+09 | 0.421032E+11 | 0.296952E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.325850E+11 | 0.251376E+12 | 0.00 | 0.00 | 0.319177E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.486931E+11 | 0.111880E+13 | 0.101545E+09 | 0.113449E+11 | 0.587395E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.213661E+11 | 66222.95 | 0.933638E+09 | 0.873848E+09 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.262802E+11 | 4623.58 | 0.257076E+09 | 0.333905E+10 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.338636E+11 | 7506.99 | 0.441315E+09 | 0.747884E+10 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.427194E+11 | 5365.52 | 0.255557E+09 | 0.204948E+11 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.520701E+11 | 3547.20 | 216694.00 | 0.436413E+11 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.627577E+11 | 2569.45 | 0.00 | 0.629618E+11 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.738308E+11 | 4158.71 | 0.00 | 0.792754E+11 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.760364E+11 | 3604.71 | 0.00 | 0.829088E+11 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.674343E+11 | 2246.62 | 0.00 | 0.690087E+11 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.564372E+11 | 6106.18 | 27533733.00 | 0.476621E+11 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.439885E+11 | 6914.22 | 19386933.97 | 0.207726E+11 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.326690E+11 | 8288.12 | 0.209495E+09 | 0.515530E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.589453E+12 | 121154.24 | 0.214422E+10 | 0.443573E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.213661E+11 | 2246.62 | 0.00 | 0.873848E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.760364E+11 | 66222.95 | 0.933638E+09 | 0.829088E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.357098E+11 | 0.101545E+09 | 0.251376E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.325850E+11 | 12283566.92 | 0.304506E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.371966E+11 | 967263.72 | 0.417461E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.374207E+11 | 0.00 | 0.571125E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.424032E+11 | 0.00 | 0.768577E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.428953E+11 | 0.00 | 0.923734E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.465205E+11 | 0.00 | 0.107359E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.486931E+11 | 0.00 | 0.111880E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.448180E+11 | 0.00 | 0.998701E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.443015E+11 | 0.00 | 0.839104E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.397540E+11 | 0.00 | 0.594053E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.373578E+11 | 22310508.23 | 0.389347E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.489655E+12 | 0.137106E+09 | 0.825038E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.325850E+11 | 0.00 | 0.251376E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.486931E+11 | 0.101545E+09 | 0.111880E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 66222.95 | 0.213661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 4623.58 | 0.262802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 7506.99 | 0.338636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 5365.52 | 0.427194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 3547.20 | 0.520701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 2569.45 | 0.627577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 4158.71 | 0.738308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 3604.71 | 0.760364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 2246.62 | 0.674343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 6106.18 | 0.564372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 6914.22 | 0.439885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 8288.12 | 0.326690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 121154.24 | 0.589453E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 2246.62 | 0.213661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 66222.95 | 0.760364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.855507E+09 | 0.491452E+09 | 0.00 | 56544059.86 | 0.102065E+09 | 0.00 | 0.260390E+11 | 0.00 | 0.95 |
February | 0.489762E+10 | 0.643654E+09 | 0.00 | 14768865.62 | 0.937379E+09 | 0.00 | 0.122202E+11 | 0.00 | 0.90 |
March | 0.126510E+11 | 0.298326E+09 | 0.00 | 268260.43 | 0.308703E+10 | 0.00 | 0.577694E+09 | 0.00 | 0.88 |
April | 0.415122E+10 | 0.00 | 0.00 | 0.00 | 0.958006E+10 | 0.00 | 0.00 | 0.00 | 0.85 |
May | 0.816676E+09 | 70302730.76 | 0.00 | 0.00 | 0.196677E+11 | 0.00 | 0.00 | 0.00 | 0.79 |
June | 82207282.13 | 0.441630E+10 | 0.00 | 0.00 | 0.289361E+11 | 0.00 | 0.00 | 0.00 | 0.75 |
July | 39753119.45 | 0.214796E+11 | 0.00 | 199302.09 | 0.220548E+11 | 0.00 | 0.100171E+09 | 0.00 | 0.72 |
August | 0.00 | 0.459989E+11 | 0.00 | 0.00 | 0.321065E+10 | 0.00 | 0.00 | 0.00 | 0.75 |
September | 0.00 | 0.423643E+11 | 0.00 | 643909.90 | 0.112391E+10 | 0.00 | 20879741.76 | 0.00 | 0.85 |
October | 0.00 | 0.293598E+11 | 0.00 | 7712049.77 | 42042898.28 | 0.00 | 0.738833E+09 | 0.00 | 0.97 |
November | 0.00 | 0.116085E+11 | 0.00 | 35561407.14 | 1395511.43 | 0.00 | 0.507605E+10 | 0.00 | 1.04 |
December | 32588113.55 | 0.363972E+10 | 0.00 | 66547826.80 | 55976311.30 | 0.00 | 0.183931E+11 | 0.00 | 1.01 |
Annual Sum or Average | 0.235266E+11 | 0.160371E+12 | 0.00 | 0.182246E+09 | 0.887991E+11 | 0.00 | 0.631660E+11 | 0.00 | 0.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1395511.43 | 0.00 | 0.00 | 0.00 | 0.72 |
Maximum of Months | 0.126510E+11 | 0.459989E+11 | 0.00 | 66547826.80 | 0.289361E+11 | 0.00 | 0.260390E+11 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.356917E+10 | 27520457.29 | 0.00 | 257943.46 | 55948516.48 | 0.00 | 92759993.36 | 0.00 | 2.35 |
February | 0.235245E+10 | 0.122267E+09 | 0.00 | 276415.05 | 0.104661E+09 | 0.00 | 85540538.85 | 0.00 | 2.32 |
March | 0.176447E+10 | 0.302639E+09 | 0.00 | 334644.16 | 0.185285E+09 | 0.00 | 0.125106E+09 | 0.00 | 2.27 |
April | 0.525864E+09 | 0.932489E+09 | 0.00 | 260274.63 | 0.444401E+09 | 0.00 | 67046422.72 | 0.00 | 2.22 |
May | 43907291.84 | 0.273220E+10 | 0.00 | 280929.72 | 0.194537E+09 | 0.00 | 72491659.68 | 0.00 | 2.13 |
June | 1367036.70 | 0.493272E+10 | 0.00 | 70517.57 | 0.124749E+09 | 0.00 | 10306182.60 | 0.00 | 2.06 |
July | 225775.22 | 0.695757E+10 | 0.00 | 118406.88 | 27438989.67 | 0.00 | 19701757.85 | 0.00 | 2.07 |
August | 0.00 | 0.768415E+10 | 0.00 | 0.00 | 19527024.45 | 0.00 | 0.00 | 0.00 | 2.12 |
September | 797889.94 | 0.623682E+10 | 0.00 | 8908.66 | 0.120549E+09 | 0.00 | 1798486.77 | 0.00 | 2.23 |
October | 48240042.32 | 0.370744E+10 | 0.00 | 288420.46 | 0.245838E+09 | 0.00 | 38492996.83 | 0.00 | 2.37 |
November | 0.496645E+09 | 0.122859E+10 | 0.00 | 626299.52 | 0.279717E+09 | 0.00 | 77992510.72 | 0.00 | 2.36 |
December | 0.217825E+10 | 0.268770E+09 | 0.00 | 570292.23 | 0.211302E+09 | 0.00 | 99011371.07 | 0.00 | 2.33 |
Annual Sum or Average | 0.109814E+11 | 0.351332E+11 | 0.00 | 3093052.34 | 0.201395E+10 | 0.00 | 0.690248E+09 | 0.00 | 2.23 |
Minimum of Months | 0.00 | 27520457.29 | 0.00 | 0.00 | 19527024.45 | 0.00 | 0.00 | 0.00 | 2.06 |
Maximum of Months | 0.356917E+10 | 0.768415E+10 | 0.00 | 626299.52 | 0.444401E+09 | 0.00 | 0.125106E+09 | 0.00 | 2.37 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.170366E+10 | 5567724.27 | 0.00 | 954737.60 | 49660552.14 | 0.00 | 0.719333E+09 | 0.00 | 1.35 |
February | 0.968470E+09 | 78003344.69 | 0.00 | 1017977.72 | 74800218.00 | 0.00 | 0.647545E+09 | 0.00 | 1.33 |
March | 0.517990E+09 | 0.161339E+09 | 0.00 | 1579592.32 | 0.171682E+09 | 0.00 | 0.740173E+09 | 0.00 | 1.32 |
April | 60865337.18 | 0.554798E+09 | 0.00 | 1144105.92 | 0.391036E+09 | 0.00 | 0.335193E+09 | 0.00 | 1.31 |
May | 823507.51 | 0.190420E+10 | 0.00 | 914316.26 | 0.176652E+09 | 0.00 | 80638367.90 | 0.00 | 1.30 |
June | 0.00 | 0.347010E+10 | 0.00 | 195493.60 | 0.131921E+09 | 0.00 | 8471495.43 | 0.00 | 1.27 |
July | 0.00 | 0.467603E+10 | 0.00 | 164978.53 | 94019312.32 | 0.00 | 15515028.75 | 0.00 | 1.23 |
August | 0.00 | 0.501372E+10 | 0.00 | 0.00 | 68442444.42 | 0.00 | 0.00 | 0.00 | 1.23 |
September | 0.00 | 0.409890E+10 | 0.00 | 45825.73 | 0.102370E+09 | 0.00 | 1788480.57 | 0.00 | 1.28 |
October | 2171456.52 | 0.246541E+10 | 0.00 | 395948.87 | 0.138542E+09 | 0.00 | 56386131.77 | 0.00 | 1.34 |
November | 32558895.51 | 0.778389E+09 | 0.00 | 1415179.65 | 0.206346E+09 | 0.00 | 0.351943E+09 | 0.00 | 1.34 |
December | 0.768473E+09 | 0.115872E+09 | 0.00 | 1178859.54 | 0.203902E+09 | 0.00 | 0.743382E+09 | 0.00 | 1.34 |
Annual Sum or Average | 0.405501E+10 | 0.233223E+11 | 0.00 | 9007015.75 | 0.180938E+10 | 0.00 | 0.370037E+10 | 0.00 | 1.30 |
Minimum of Months | 0.00 | 5567724.27 | 0.00 | 0.00 | 49660552.14 | 0.00 | 0.00 | 0.00 | 1.23 |
Maximum of Months | 0.170366E+10 | 0.501372E+10 | 0.00 | 1579592.32 | 0.391036E+09 | 0.00 | 0.743382E+09 | 0.00 | 1.35 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.237902E+10 | 0.00 | 0.00 | 0.00 | 54212923.07 | 0.00 | 0.00 | 0.00 | 0.62 |
February | 0.158393E+10 | 13013745.40 | 0.00 | 0.00 | 0.132118E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
March | 0.121953E+10 | 41955608.23 | 0.00 | 33696.90 | 0.272413E+09 | 0.00 | 8171346.98 | 0.00 | 0.60 |
April | 0.335568E+09 | 0.225241E+09 | 0.00 | 191350.46 | 0.671695E+09 | 0.00 | 49901344.63 | 0.00 | 0.59 |
May | 7709910.30 | 0.176329E+10 | 0.00 | 649051.58 | 0.244622E+09 | 0.00 | 69508315.30 | 0.00 | 0.59 |
June | 0.00 | 0.355621E+10 | 0.00 | 206551.17 | 38423049.96 | 0.00 | 8468491.36 | 0.00 | 0.60 |
July | 0.00 | 0.494721E+10 | 0.00 | 168780.29 | 1290898.31 | 0.00 | 15668577.78 | 0.00 | 0.60 |
August | 0.00 | 0.526799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.404669E+10 | 0.00 | 50247.24 | 63514636.13 | 0.00 | 1720571.66 | 0.00 | 0.59 |
October | 16449333.32 | 0.200045E+10 | 0.00 | 161545.40 | 0.447884E+09 | 0.00 | 39536589.81 | 0.00 | 0.59 |
November | 0.338287E+09 | 0.255467E+09 | 0.00 | 97277.42 | 0.664937E+09 | 0.00 | 34224317.65 | 0.00 | 0.60 |
December | 0.147526E+10 | 720799.50 | 0.00 | 1674.09 | 0.307313E+09 | 0.00 | 4124284.56 | 0.00 | 0.61 |
Annual Sum or Average | 0.735576E+10 | 0.221182E+11 | 0.00 | 1560174.54 | 0.289842E+10 | 0.00 | 0.231324E+09 | 0.00 | 0.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.237902E+10 | 0.526799E+10 | 0.00 | 649051.58 | 0.671695E+09 | 0.00 | 69508315.30 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.129390E+10 | 0.00 | 0.00 | 0.00 | 29485402.40 | 0.00 | 0.00 | 0.00 | 0.59 |
February | 0.861471E+09 | 0.00 | 0.00 | 0.00 | 78934720.93 | 0.00 | 0.00 | 0.00 | 0.58 |
March | 0.666669E+09 | 2305479.66 | 0.00 | 1448.07 | 0.168566E+09 | 0.00 | 1042871.89 | 0.00 | 0.57 |
April | 0.198827E+09 | 52587701.25 | 0.00 | 43592.01 | 0.431132E+09 | 0.00 | 10707608.28 | 0.00 | 0.55 |
May | 9033033.87 | 0.867710E+09 | 0.00 | 212123.94 | 0.170970E+09 | 0.00 | 32274991.61 | 0.00 | 0.53 |
June | 0.00 | 0.184109E+10 | 0.00 | 104379.16 | 19329954.70 | 0.00 | 4295554.84 | 0.00 | 0.54 |
July | 0.00 | 0.260286E+10 | 0.00 | 86333.07 | 0.00 | 0.00 | 7961632.65 | 0.00 | 0.55 |
August | 0.00 | 0.277343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
September | 102222.75 | 0.208273E+10 | 0.00 | 9421.55 | 44193028.34 | 0.00 | 808854.96 | 0.00 | 0.53 |
October | 18611367.42 | 0.925516E+09 | 0.00 | 37831.43 | 0.351832E+09 | 0.00 | 11853172.26 | 0.00 | 0.54 |
November | 0.201849E+09 | 59504751.12 | 0.00 | 1708.56 | 0.436345E+09 | 0.00 | 804524.16 | 0.00 | 0.56 |
December | 0.804613E+09 | 0.00 | 0.00 | 0.00 | 0.167534E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
Annual Sum or Average | 0.405508E+10 | 0.112077E+11 | 0.00 | 496837.78 | 0.189832E+10 | 0.00 | 69749210.66 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.129390E+10 | 0.277343E+10 | 0.00 | 212123.94 | 0.436345E+09 | 0.00 | 32274991.61 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.142981E+09 | 0.815392E+09 | 0.00 | 0.100605E+09 | 118596.52 | 0.00 | 0.378376E+11 | 0.00 | 21.13 |
February | 94703446.92 | 0.253163E+10 | 0.00 | 80867630.00 | 0.00 | 0.00 | 0.249509E+11 | 0.00 | 20.84 |
March | 60817658.94 | 0.530375E+10 | 0.00 | 75801608.12 | 730652.85 | 0.00 | 0.193856E+11 | 0.00 | 20.53 |
April | 5353968.23 | 0.148313E+11 | 0.00 | 31035701.25 | 0.00 | 0.00 | 0.573712E+10 | 0.00 | 19.96 |
May | 85580.15 | 0.303021E+11 | 0.00 | 13139862.18 | 6427971.58 | 0.00 | 0.115431E+10 | 0.00 | 18.51 |
June | 0.00 | 0.510273E+11 | 0.00 | 2329372.24 | 9387569.32 | 0.00 | 0.110952E+09 | 0.00 | 17.51 |
July | 0.00 | 0.653354E+11 | 0.00 | 1674147.98 | 13727936.90 | 0.00 | 0.193728E+09 | 0.00 | 16.49 |
August | 0.00 | 0.691799E+11 | 0.00 | 0.00 | 8644042.52 | 0.00 | 0.00 | 0.00 | 16.23 |
September | 0.00 | 0.590172E+11 | 0.00 | 813781.46 | 12051953.56 | 0.00 | 27376103.88 | 0.00 | 17.48 |
October | 1487224.78 | 0.379425E+11 | 0.00 | 7286355.75 | 5259253.25 | 0.00 | 0.827124E+09 | 0.00 | 19.07 |
November | 2277214.72 | 0.151922E+11 | 0.00 | 33251255.55 | 1126608.16 | 0.00 | 0.563066E+10 | 0.00 | 20.23 |
December | 88039531.53 | 0.525063E+10 | 0.00 | 77584750.89 | 0.00 | 0.00 | 0.231897E+11 | 0.00 | 20.83 |
Annual Sum or Average | 0.395746E+09 | 0.356729E+12 | 0.00 | 0.424389E+09 | 57474584.66 | 0.00 | 0.119045E+12 | 0.00 | 19.06 |
Minimum of Months | 0.00 | 0.815392E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 |
Maximum of Months | 0.142981E+09 | 0.691799E+11 | 0.00 | 0.100605E+09 | 13727936.90 | 0.00 | 0.378376E+11 | 0.00 | 21.13 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.286235E+10 | 0.195802E+09 | 0.00 | 20605240.42 | 0.151000E+09 | 0.00 | 0.123155E+11 | 0.00 | 3.48 |
February | 0.181170E+10 | 0.823572E+09 | 0.00 | 17698832.54 | 0.142647E+09 | 0.00 | 0.830344E+10 | 0.00 | 3.46 |
March | 0.135299E+10 | 0.174342E+10 | 0.00 | 17948219.38 | 0.323505E+09 | 0.00 | 0.657458E+10 | 0.00 | 3.42 |
April | 0.268965E+09 | 0.521973E+10 | 0.00 | 9286948.11 | 0.602534E+09 | 0.00 | 0.226373E+10 | 0.00 | 3.38 |
May | 19706729.25 | 0.122004E+11 | 0.00 | 4784412.76 | 0.467751E+09 | 0.00 | 0.502326E+09 | 0.00 | 3.30 |
June | 1333436.97 | 0.210815E+11 | 0.00 | 880088.19 | 0.677540E+09 | 0.00 | 51290080.40 | 0.00 | 3.19 |
July | 584986.37 | 0.286850E+11 | 0.00 | 899723.33 | 0.385343E+09 | 0.00 | 93925910.26 | 0.00 | 3.11 |
August | 0.00 | 0.309868E+11 | 0.00 | 0.00 | 0.255486E+09 | 0.00 | 0.00 | 0.00 | 3.12 |
September | 1194995.25 | 0.260198E+11 | 0.00 | 162036.96 | 0.253248E+09 | 0.00 | 9790999.88 | 0.00 | 3.33 |
October | 16992945.16 | 0.163602E+11 | 0.00 | 2968330.19 | 0.266626E+09 | 0.00 | 0.367790E+09 | 0.00 | 3.57 |
November | 58963088.69 | 0.606154E+10 | 0.00 | 13954922.91 | 0.241912E+09 | 0.00 | 0.238768E+10 | 0.00 | 3.55 |
December | 0.121904E+10 | 0.181662E+10 | 0.00 | 20005326.91 | 0.191825E+09 | 0.00 | 0.827544E+10 | 0.00 | 3.47 |
Annual Sum or Average | 0.761382E+10 | 0.151194E+12 | 0.00 | 0.109194E+09 | 0.395942E+10 | 0.00 | 0.411455E+11 | 0.00 | 3.36 |
Minimum of Months | 0.00 | 0.195802E+09 | 0.00 | 0.00 | 0.142647E+09 | 0.00 | 0.00 | 0.00 | 3.11 |
Maximum of Months | 0.286235E+10 | 0.309868E+11 | 0.00 | 20605240.42 | 0.677540E+09 | 0.00 | 0.123155E+11 | 0.00 | 3.57 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.102129E+11 | 0.294723E+09 | 0.00 | 69032896.23 | 0.841509E+09 | 0.00 | 0.402566E+11 | 0.00 | 1.66 |
February | 0.579616E+10 | 0.240640E+10 | 0.00 | 60775127.04 | 0.844532E+09 | 0.00 | 0.279069E+11 | 0.00 | 1.66 |
March | 0.337835E+10 | 0.483256E+10 | 0.00 | 65811150.12 | 0.214977E+10 | 0.00 | 0.232614E+11 | 0.00 | 1.66 |
April | 0.499058E+09 | 0.150585E+11 | 0.00 | 36973372.89 | 0.467250E+10 | 0.00 | 0.808779E+10 | 0.00 | 1.65 |
May | 19474997.46 | 0.402570E+11 | 0.00 | 20125078.84 | 0.283675E+10 | 0.00 | 0.177385E+10 | 0.00 | 1.62 |
June | 82677.83 | 0.711108E+11 | 0.00 | 3923222.27 | 0.299767E+10 | 0.00 | 0.181570E+09 | 0.00 | 1.57 |
July | 0.00 | 0.953964E+11 | 0.00 | 3498401.05 | 0.244559E+10 | 0.00 | 0.332490E+09 | 0.00 | 1.51 |
August | 0.00 | 0.101681E+12 | 0.00 | 0.00 | 0.205324E+10 | 0.00 | 0.00 | 0.00 | 1.50 |
September | 197297.18 | 0.849006E+11 | 0.00 | 870948.86 | 0.186071E+10 | 0.00 | 37158357.77 | 0.00 | 1.59 |
October | 7992771.00 | 0.528090E+11 | 0.00 | 11087669.58 | 0.187070E+10 | 0.00 | 0.130020E+10 | 0.00 | 1.69 |
November | 0.113304E+09 | 0.190036E+11 | 0.00 | 49774162.51 | 0.177330E+10 | 0.00 | 0.828180E+10 | 0.00 | 1.71 |
December | 0.412860E+10 | 0.493025E+10 | 0.00 | 67724521.98 | 0.178916E+10 | 0.00 | 0.277605E+11 | 0.00 | 1.67 |
Annual Sum or Average | 0.241561E+11 | 0.492681E+12 | 0.00 | 0.389597E+09 | 0.261354E+11 | 0.00 | 0.139180E+12 | 0.00 | 1.62 |
Minimum of Months | 0.00 | 0.294723E+09 | 0.00 | 0.00 | 0.841509E+09 | 0.00 | 0.00 | 0.00 | 1.50 |
Maximum of Months | 0.102129E+11 | 0.101681E+12 | 0.00 | 69032896.23 | 0.467250E+10 | 0.00 | 0.402566E+11 | 0.00 | 1.71 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1839578.54 | 55949053.74 | 87320.75 | 8128833.23 | 119493.31 | 2690771.90 | 0.691028E+09 | 10520.17 | 0.35 |
February | 705802.65 | 0.152701E+09 | 253568.14 | 6328401.42 | 0.00 | 1290067.76 | 0.365162E+09 | 19065.18 | 0.36 |
March | 0.00 | 0.262368E+09 | 98045.48 | 5975985.05 | 0.00 | 862975.04 | 0.249463E+09 | 16127.81 | 0.36 |
April | 0.00 | 0.605984E+09 | 245029.79 | 2154381.61 | 0.00 | 158498.71 | 35542464.69 | 36274.56 | 0.36 |
May | 0.00 | 0.112983E+10 | 351237.94 | 103956.38 | 0.00 | 2412.08 | 313567.98 | 9480.91 | 0.36 |
June | 0.00 | 0.174332E+10 | 566216.92 | 0.00 | 0.00 | 0.00 | 0.00 | 3064.71 | 0.36 |
July | 0.00 | 0.221758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.232797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
September | 0.00 | 0.197117E+10 | 883951.88 | 0.00 | 0.00 | 0.00 | 0.00 | 6373.11 | 0.36 |
October | 0.00 | 0.133729E+10 | 959566.29 | 491111.38 | 0.00 | 28870.88 | 3481049.68 | 12213.34 | 0.36 |
November | 0.00 | 0.668314E+09 | 693439.12 | 1085431.91 | 0.00 | 40275.73 | 27017736.68 | 31854.59 | 0.36 |
December | 989684.45 | 0.261014E+09 | 555390.47 | 5555790.77 | 0.00 | 949718.33 | 0.331822E+09 | 44714.53 | 0.36 |
Annual Sum or Average | 3535065.64 | 0.127335E+11 | 4693766.79 | 29823891.73 | 119493.31 | 6023590.44 | 0.170383E+10 | 189688.91 | 0.36 |
Minimum of Months | 0.00 | 55949053.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 1839578.54 | 0.232797E+10 | 959566.29 | 8128833.23 | 119493.31 | 2690771.90 | 0.691028E+09 | 44714.53 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.188552E+09 | 35098398.83 | 139304.70 | 3996554.06 | 20898487.91 | 4057847.96 | 0.506999E+09 | 23615.83 | 0.36 |
February | 0.112531E+09 | 0.121819E+09 | 359880.06 | 3288075.79 | 30741910.60 | 829516.39 | 0.256793E+09 | 35584.81 | 0.36 |
March | 0.101396E+09 | 0.231839E+09 | 242701.87 | 3639530.87 | 30348551.58 | 347557.81 | 0.150889E+09 | 20958.18 | 0.36 |
April | 23864504.17 | 0.570894E+09 | 271419.53 | 1210850.48 | 35006394.37 | 23087.92 | 12752467.14 | 21888.58 | 0.36 |
May | 7351.65 | 0.111653E+10 | 150259.73 | 98470.45 | 13373194.55 | 2411.79 | 311653.34 | 4630.77 | 0.36 |
June | 0.00 | 0.174197E+10 | 236577.75 | 0.00 | 1476317.95 | 0.00 | 0.00 | 2870.04 | 0.36 |
July | 0.00 | 0.221732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.232770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
September | 0.00 | 0.196522E+10 | 800134.90 | 0.00 | 5800265.19 | 0.00 | 0.00 | 8414.83 | 0.36 |
October | 1599702.26 | 0.132250E+10 | 1655064.67 | 274546.73 | 13926738.09 | 8888.98 | 2117425.19 | 27210.56 | 0.36 |
November | 14150908.59 | 0.604165E+09 | 1072426.28 | 586598.05 | 63655518.15 | 19541.81 | 13383098.45 | 68761.54 | 0.36 |
December | 0.115009E+09 | 0.203853E+09 | 894127.91 | 2780010.01 | 56761139.13 | 1040978.66 | 0.220447E+09 | 75785.60 | 0.36 |
Annual Sum or Average | 0.557111E+09 | 0.124589E+11 | 5821897.39 | 15874636.44 | 0.271989E+09 | 6329831.33 | 0.116369E+10 | 289720.73 | 0.36 |
Minimum of Months | 0.00 | 35098398.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.188552E+09 | 0.232770E+10 | 1655064.67 | 3996554.06 | 63655518.15 | 4057847.96 | 0.506999E+09 | 75785.60 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.121511E+09 | 0.00 | 2459875.72 | 0.00 | 0.00 | 0.464364E+09 | 0.00 | 0.02 |
February | 10749309.13 | 0.169109E+09 | 0.00 | 1437899.63 | 0.00 | 0.00 | 0.208320E+09 | 0.00 | 0.02 |
March | 0.00 | 0.196668E+09 | 0.00 | 1717703.58 | 0.00 | 0.00 | 0.161537E+09 | 0.00 | 0.02 |
April | 0.00 | 0.444678E+09 | 0.00 | 423510.53 | 0.00 | 0.00 | 7595092.91 | 0.00 | 0.02 |
May | 0.00 | 0.758798E+09 | 0.00 | 150988.03 | 0.00 | 0.00 | 3365237.38 | 0.00 | 0.02 |
June | 0.00 | 0.116677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
July | 0.00 | 0.159257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
August | 0.00 | 0.178656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
September | 0.00 | 0.143194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
October | 0.00 | 0.820545E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.554616E+09 | 0.00 | 192098.97 | 0.00 | 0.00 | 7323682.20 | 0.00 | 0.02 |
December | 10292712.85 | 0.398868E+09 | 0.00 | 1537666.04 | 0.00 | 0.00 | 0.174587E+09 | 0.00 | 0.02 |
Annual Sum or Average | 21042021.99 | 0.944262E+10 | 0.00 | 7919742.51 | 0.00 | 0.00 | 0.102709E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.121511E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 10749309.13 | 0.178656E+10 | 0.00 | 2459875.72 | 0.00 | 0.00 | 0.464364E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.258674E+10 | 0.429327E+09 | 2742050.91 | 72458448.79 | 0.329562E+09 | 20199996.37 | 0.686458E+10 | 142556.29 | 0.40 |
February | 0.156743E+10 | 0.160617E+10 | 5380505.94 | 50609533.62 | 0.463052E+09 | 5209231.09 | 0.344227E+10 | 148184.07 | 0.40 |
March | 0.141521E+10 | 0.305454E+10 | 9686336.12 | 45828553.91 | 0.495489E+09 | 3318081.54 | 0.201181E+10 | 278010.76 | 0.41 |
April | 0.325150E+09 | 0.770560E+10 | 11682186.57 | 12188111.71 | 0.505156E+09 | 202149.95 | 0.175885E+09 | 219650.30 | 0.41 |
May | 99720.66 | 0.151356E+11 | 11485429.70 | 960841.98 | 0.181399E+09 | 16017.94 | 4618937.77 | 101886.25 | 0.41 |
June | 0.00 | 0.236063E+11 | 25639126.46 | 0.00 | 20025367.34 | 0.00 | 0.00 | 115053.64 | 0.41 |
July | 0.00 | 0.300432E+11 | 33225776.71 | 0.00 | 0.00 | 0.00 | 0.00 | 123966.73 | 0.41 |
August | 0.00 | 0.315329E+11 | 40776297.88 | 0.00 | 0.00 | 0.00 | 0.00 | 152748.24 | 0.41 |
September | 0.00 | 0.266375E+11 | 30439700.36 | 0.00 | 78677117.76 | 0.00 | 0.00 | 92221.19 | 0.41 |
October | 21699001.46 | 0.179311E+11 | 30335243.75 | 2846713.49 | 0.188908E+09 | 0.00 | 29719524.39 | 196278.74 | 0.41 |
November | 0.192438E+09 | 0.801004E+10 | 23288506.32 | 6794541.48 | 0.104038E+10 | 281415.66 | 0.182190E+09 | 351649.40 | 0.40 |
December | 0.157680E+10 | 0.261309E+10 | 9372590.48 | 44800473.63 | 0.925485E+09 | 4885560.16 | 0.297561E+10 | 280649.39 | 0.40 |
Annual Sum or Average | 0.768557E+10 | 0.168305E+12 | 0.234054E+09 | 0.236487E+09 | 0.422813E+10 | 34112452.71 | 0.156867E+11 | 2202855.00 | 0.41 |
Minimum of Months | 0.00 | 0.429327E+09 | 2742050.91 | 0.00 | 0.00 | 0.00 | 0.00 | 92221.19 | 0.40 |
Maximum of Months | 0.258674E+10 | 0.315329E+11 | 40776297.88 | 72458448.79 | 0.104038E+10 | 20199996.37 | 0.686458E+10 | 351649.40 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 793399.29 | 55831490.30 | 102366.85 | 8597798.26 | 226509.32 | 2059726.75 | 0.692237E+09 | 6021.51 | 0.35 |
February | 762671.67 | 0.152845E+09 | 126146.08 | 6532016.61 | 0.00 | 1021514.48 | 0.365170E+09 | 2549.10 | 0.36 |
March | 0.00 | 0.262389E+09 | 87311.54 | 6131160.33 | 0.00 | 777551.86 | 0.249393E+09 | 5209.78 | 0.36 |
April | 0.00 | 0.606210E+09 | 52322.09 | 2365675.45 | 0.00 | 82237.44 | 35407432.12 | 2341.88 | 0.36 |
May | 0.00 | 0.113019E+10 | 0.00 | 113520.60 | 0.00 | 0.00 | 306415.83 | 0.00 | 0.36 |
June | 0.00 | 0.174389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
July | 0.00 | 0.221758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.232797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
September | 0.00 | 0.197206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
October | 0.00 | 0.133826E+10 | 0.00 | 595870.10 | 0.00 | 0.00 | 3405161.84 | 0.00 | 0.36 |
November | 0.00 | 0.668870E+09 | 167337.15 | 1178253.17 | 0.00 | 0.00 | 26965191.15 | 2608.38 | 0.36 |
December | 249817.70 | 0.261411E+09 | 192791.93 | 5761297.29 | 0.00 | 988953.05 | 0.332317E+09 | 10495.30 | 0.36 |
Annual Sum or Average | 1805888.65 | 0.127375E+11 | 728275.63 | 31275591.81 | 226509.32 | 4929983.59 | 0.170520E+10 | 29225.96 | 0.36 |
Minimum of Months | 0.00 | 55831490.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 793399.29 | 0.232797E+10 | 192791.93 | 8597798.26 | 226509.32 | 2059726.75 | 0.692237E+09 | 10495.30 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.186597E+09 | 35259364.26 | 136998.85 | 4309382.16 | 20736277.60 | 3802308.74 | 0.508897E+09 | 27166.54 | 0.36 |
February | 0.112167E+09 | 0.121645E+09 | 393283.28 | 3390463.44 | 30898599.91 | 765299.95 | 0.257119E+09 | 18586.09 | 0.36 |
March | 0.101396E+09 | 0.231854E+09 | 198783.45 | 3635448.73 | 30384746.42 | 298500.95 | 0.150942E+09 | 13737.51 | 0.36 |
April | 23864504.17 | 0.571095E+09 | 89657.89 | 1301941.25 | 35006394.37 | 4236.67 | 12680227.62 | 3037.91 | 0.36 |
May | 7351.65 | 0.111669E+10 | 0.00 | 107341.60 | 13373194.55 | 0.00 | 305193.98 | 0.00 | 0.36 |
June | 0.00 | 0.174249E+10 | 0.00 | 0.00 | 1193128.66 | 0.00 | 0.00 | 0.00 | 0.36 |
July | 0.00 | 0.221732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.232770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
September | 0.00 | 0.196600E+10 | 36991.32 | 0.00 | 5800265.19 | 0.00 | 0.00 | 476.39 | 0.36 |
October | 1599702.26 | 0.132418E+10 | 0.00 | 356990.63 | 13926738.09 | 0.00 | 2043870.27 | 0.00 | 0.36 |
November | 14150908.59 | 0.604870E+09 | 414823.51 | 597663.71 | 63655518.15 | 18036.60 | 13373538.00 | 20632.60 | 0.36 |
December | 0.115191E+09 | 0.202316E+09 | 693947.47 | 2802751.09 | 58528010.86 | 958808.51 | 0.220325E+09 | 45288.07 | 0.36 |
Annual Sum or Average | 0.554973E+09 | 0.124614E+11 | 1964485.77 | 16501982.61 | 0.273503E+09 | 5847191.42 | 0.116569E+10 | 128925.12 | 0.36 |
Minimum of Months | 0.00 | 35259364.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.186597E+09 | 0.232770E+10 | 693947.47 | 4309382.16 | 63655518.15 | 3802308.74 | 0.508897E+09 | 45288.07 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.141301E+11 | 0.00 | 0.00 | 0.00 | 0.321995E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
February | 0.940769E+10 | 0.00 | 0.00 | 0.00 | 0.862006E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
March | 0.729176E+10 | 0.00 | 0.00 | 0.00 | 0.186600E+10 | 0.00 | 0.00 | 0.00 | 0.49 |
April | 0.225072E+10 | 0.270909E+09 | 0.00 | 174264.06 | 0.500959E+10 | 0.00 | 37242085.08 | 0.00 | 0.48 |
May | 0.243672E+09 | 0.776696E+10 | 0.00 | 1110809.12 | 0.328636E+10 | 0.00 | 0.206161E+09 | 0.00 | 0.45 |
June | 3854778.96 | 0.175201E+11 | 0.00 | 518450.22 | 0.176897E+10 | 0.00 | 41732011.67 | 0.00 | 0.44 |
July | 871137.29 | 0.254456E+11 | 0.00 | 693741.69 | 0.787476E+09 | 0.00 | 77677255.01 | 0.00 | 0.44 |
August | 0.00 | 0.275655E+11 | 0.00 | 0.00 | 0.621172E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 5455945.48 | 0.208059E+11 | 0.00 | 37118.96 | 0.169991E+10 | 0.00 | 4559239.87 | 0.00 | 0.45 |
October | 0.200480E+09 | 0.936874E+10 | 0.00 | 372929.51 | 0.446823E+10 | 0.00 | 0.132248E+09 | 0.00 | 0.46 |
November | 0.221302E+10 | 0.480721E+09 | 0.00 | 64.17 | 0.493419E+10 | 0.00 | 77569.25 | 0.00 | 0.48 |
December | 0.878677E+10 | 0.00 | 0.00 | 0.00 | 0.182955E+10 | 0.00 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.445344E+11 | 0.109224E+12 | 0.00 | 2907377.73 | 0.274554E+11 | 0.00 | 0.499697E+09 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.321995E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.141301E+11 | 0.275655E+11 | 0.00 | 1110809.12 | 0.500959E+10 | 0.00 | 0.206161E+09 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 219162.47 | 13971155.42 | 26337.98 | 1753733.27 | 41564.89 | 9116561.31 | 0.164832E+09 | 2538.70 | 0.35 |
February | 190667.92 | 38182157.15 | 55834.83 | 1381629.68 | 0.00 | 457698.95 | 91341551.97 | 5463.33 | 0.36 |
March | 0.00 | 65596045.87 | 20850.73 | 1339350.43 | 0.00 | 744435.89 | 61991608.81 | 3602.35 | 0.36 |
April | 0.00 | 0.151485E+09 | 71734.06 | 489092.47 | 0.00 | 43420.74 | 8931323.05 | 9811.02 | 0.36 |
May | 0.00 | 0.282421E+09 | 124026.21 | 24927.33 | 0.00 | 603.02 | 79453.76 | 2719.46 | 0.36 |
June | 0.00 | 0.435848E+09 | 124013.60 | 0.00 | 0.00 | 0.00 | 0.00 | 566.83 | 0.36 |
July | 0.00 | 0.554394E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.581992E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
September | 0.00 | 0.492794E+09 | 220842.72 | 0.00 | 0.00 | 0.00 | 0.00 | 1738.53 | 0.36 |
October | 0.00 | 0.334120E+09 | 435564.16 | 115367.02 | 0.00 | 7217.72 | 877673.24 | 10082.70 | 0.36 |
November | 0.00 | 0.167072E+09 | 173895.58 | 234377.20 | 0.00 | 13779.23 | 6787704.65 | 14437.73 | 0.36 |
December | 247421.11 | 65263838.55 | 125168.96 | 1196076.91 | 0.00 | 569513.05 | 82816308.27 | 14580.01 | 0.36 |
Annual Sum or Average | 657251.50 | 0.318314E+10 | 1378268.83 | 6534554.31 | 41564.89 | 10953229.90 | 0.417658E+09 | 65540.66 | 0.36 |
Minimum of Months | 0.00 | 13971155.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 247421.11 | 0.581992E+09 | 435564.16 | 1753733.27 | 41564.89 | 9116561.31 | 0.164832E+09 | 14580.01 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 46895485.70 | 8909971.00 | 43179.89 | 781497.12 | 5081520.36 | 17194937.85 | 0.111029E+09 | 5280.56 | 0.36 |
February | 28075560.34 | 30637829.28 | 107600.61 | 686385.82 | 7482627.09 | 200701.39 | 64397961.12 | 10917.56 | 0.36 |
March | 25330821.46 | 57968095.89 | 51342.86 | 819065.35 | 7587137.89 | 83779.90 | 37834221.04 | 6233.91 | 0.36 |
April | 5966126.04 | 0.142714E+09 | 77362.97 | 281960.46 | 8751598.59 | 5701.53 | 3208939.39 | 5931.24 | 0.36 |
May | 1837.91 | 0.279074E+09 | 96436.83 | 23636.75 | 3343298.64 | 602.95 | 78894.20 | 918.58 | 0.36 |
June | 0.00 | 0.435493E+09 | 59438.91 | 0.00 | 369079.49 | 0.00 | 0.00 | 423.04 | 0.36 |
July | 0.00 | 0.554329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.581924E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
September | 0.00 | 0.491216E+09 | 289151.18 | 0.00 | 1450066.30 | 0.00 | 0.00 | 3129.41 | 0.36 |
October | 399925.56 | 0.330608E+09 | 423899.60 | 67548.90 | 3481684.52 | 4726.11 | 527940.21 | 12819.73 | 0.36 |
November | 3537727.15 | 0.150977E+09 | 329919.14 | 128779.24 | 15913879.54 | 6773.75 | 3361756.60 | 19674.99 | 0.36 |
December | 28592606.76 | 50990908.31 | 247354.93 | 559375.40 | 14135724.64 | 257276.39 | 55410121.79 | 21936.64 | 0.36 |
Annual Sum or Average | 0.138800E+09 | 0.311484E+10 | 1725686.91 | 3348249.04 | 67596617.06 | 17754499.87 | 0.275849E+09 | 87265.66 | 0.36 |
Minimum of Months | 0.00 | 8909971.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 46895485.70 | 0.581924E+09 | 423899.60 | 819065.35 | 15913879.54 | 17194937.85 | 0.111029E+09 | 21936.64 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 90158904.19 | 48283.70 | 15703529.89 | 0.00 | 2277372.13 | 0.111223E+10 | 2902.34 | 0.40 |
February | 1133605.39 | 0.245695E+09 | 0.00 | 10707203.11 | 0.00 | 1580152.42 | 0.586444E+09 | 0.00 | 0.40 |
March | 0.00 | 0.421488E+09 | 81048.88 | 9061581.85 | 0.00 | 1074454.86 | 0.401516E+09 | 8831.27 | 0.41 |
April | 0.00 | 0.973488E+09 | 233649.13 | 2981955.62 | 0.00 | 195909.01 | 57622450.52 | 13801.16 | 0.41 |
May | 0.00 | 0.181428E+10 | 914742.02 | 145766.06 | 0.00 | 3874.09 | 524829.12 | 37313.91 | 0.41 |
June | 0.00 | 0.279916E+10 | 1723055.32 | 0.00 | 0.00 | 0.00 | 0.00 | 15430.83 | 0.41 |
July | 0.00 | 0.356170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
August | 0.00 | 0.373900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.316657E+10 | 799473.93 | 0.00 | 0.00 | 0.00 | 0.00 | 7489.14 | 0.41 |
October | 0.00 | 0.214876E+10 | 645181.09 | 786008.97 | 0.00 | 6451.62 | 5633686.17 | 3916.38 | 0.41 |
November | 0.00 | 0.107456E+10 | 0.00 | 1781049.78 | 0.00 | 41652.95 | 43379111.78 | 0.00 | 0.40 |
December | 401237.79 | 0.420134E+09 | 48282.76 | 10093197.85 | 0.00 | 1837034.46 | 0.532654E+09 | 2707.33 | 0.40 |
Annual Sum or Average | 1534843.19 | 0.204550E+11 | 4493716.84 | 51260293.13 | 0.00 | 7016901.55 | 0.274000E+10 | 92392.35 | 0.41 |
Minimum of Months | 0.00 | 90158904.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 1133605.39 | 0.373900E+10 | 1723055.32 | 15703529.89 | 0.00 | 2277372.13 | 0.111223E+10 | 37313.91 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.369526E+09 | 0.541422E+09 | 0.00 | 69074252.90 | 10342013.21 | 0.00 | 0.264350E+11 | 0.00 | 4.40 |
February | 0.127505E+09 | 0.166780E+10 | 0.00 | 59941598.59 | 7581051.21 | 0.00 | 0.180466E+11 | 0.00 | 4.44 |
March | 57783316.06 | 0.363288E+10 | 0.00 | 60463071.75 | 14684307.27 | 0.00 | 0.146195E+11 | 0.00 | 4.51 |
April | 2761708.54 | 0.105288E+11 | 0.00 | 29738699.68 | 2838210.75 | 0.00 | 0.481003E+10 | 0.00 | 4.58 |
May | 0.00 | 0.235048E+11 | 0.00 | 13392536.43 | 0.00 | 0.00 | 0.100243E+10 | 0.00 | 4.53 |
June | 0.00 | 0.403478E+11 | 0.00 | 2415002.05 | 0.00 | 0.00 | 0.102239E+09 | 0.00 | 4.38 |
July | 0.00 | 0.530475E+11 | 0.00 | 1913281.60 | 0.00 | 0.00 | 0.179765E+09 | 0.00 | 4.20 |
August | 0.00 | 0.555165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.10 |
September | 0.00 | 0.459255E+11 | 0.00 | 601440.39 | 0.00 | 0.00 | 19841809.97 | 0.00 | 4.31 |
October | 0.00 | 0.284943E+11 | 0.00 | 7082608.36 | 382768.95 | 0.00 | 0.704481E+09 | 0.00 | 4.52 |
November | 3313070.22 | 0.105980E+11 | 0.00 | 31099375.74 | 19364430.02 | 0.00 | 0.450601E+10 | 0.00 | 4.52 |
December | 0.112438E+09 | 0.334351E+10 | 0.00 | 59090161.48 | 31623938.87 | 0.00 | 0.169707E+11 | 0.00 | 4.43 |
Annual Sum or Average | 0.673328E+09 | 0.277149E+12 | 0.00 | 0.334812E+09 | 86816720.29 | 0.00 | 0.873966E+11 | 0.00 | 4.41 |
Minimum of Months | 0.00 | 0.541422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.10 |
Maximum of Months | 0.369526E+09 | 0.555165E+11 | 0.00 | 69074252.90 | 31623938.87 | 0.00 | 0.264350E+11 | 0.00 | 4.58 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112582E+09 | 0.588196E+09 | 0.00 | 83095516.54 | 0.00 | 0.00 | 0.289583E+11 | 0.00 | 4.75 |
February | 25674597.55 | 0.180322E+10 | 0.00 | 70158988.14 | 72615.06 | 0.00 | 0.196187E+11 | 0.00 | 4.79 |
March | 5792128.73 | 0.391312E+10 | 0.00 | 68728692.76 | 0.00 | 0.00 | 0.157859E+11 | 0.00 | 4.84 |
April | 0.00 | 0.112924E+11 | 0.00 | 32572354.72 | 0.00 | 0.00 | 0.512073E+10 | 0.00 | 4.89 |
May | 0.00 | 0.249330E+11 | 0.00 | 14181795.26 | 0.00 | 0.00 | 0.105501E+10 | 0.00 | 4.80 |
June | 0.00 | 0.427122E+11 | 0.00 | 2544670.54 | 0.00 | 0.00 | 0.107312E+09 | 0.00 | 4.62 |
July | 0.00 | 0.560534E+11 | 0.00 | 2003538.21 | 0.00 | 0.00 | 0.187778E+09 | 0.00 | 4.43 |
August | 0.00 | 0.586681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 |
September | 0.00 | 0.486115E+11 | 0.00 | 644287.88 | 0.00 | 0.00 | 21044100.15 | 0.00 | 4.55 |
October | 0.00 | 0.302166E+11 | 0.00 | 7625543.71 | 0.00 | 0.00 | 0.745533E+09 | 0.00 | 4.79 |
November | 0.00 | 0.113343E+11 | 0.00 | 33745045.68 | 0.00 | 0.00 | 0.481995E+10 | 0.00 | 4.83 |
December | 22479900.04 | 0.363215E+10 | 0.00 | 68934241.52 | 0.00 | 0.00 | 0.184342E+11 | 0.00 | 4.77 |
Annual Sum or Average | 0.166529E+09 | 0.293758E+12 | 0.00 | 0.384235E+09 | 72615.06 | 0.00 | 0.948543E+11 | 0.00 | 4.70 |
Minimum of Months | 0.00 | 0.588196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 |
Maximum of Months | 0.112582E+09 | 0.586681E+11 | 0.00 | 83095516.54 | 72615.06 | 0.00 | 0.289583E+11 | 0.00 | 4.89 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.937569E+09 | 0.00 | 0.114736E+09 | 0.00 | 0.00 | 0.315489E+11 | 0.00 | 19.56 |
February | 0.00 | 0.245258E+10 | 0.00 | 92197482.14 | 0.00 | 0.00 | 0.208428E+11 | 0.00 | 19.44 |
March | 0.00 | 0.535369E+10 | 0.00 | 84626776.77 | 0.00 | 0.00 | 0.159654E+11 | 0.00 | 19.22 |
April | 0.00 | 0.149265E+11 | 0.00 | 35286375.48 | 0.00 | 0.00 | 0.472765E+10 | 0.00 | 18.92 |
May | 0.00 | 0.302443E+11 | 0.00 | 14818268.57 | 0.00 | 0.00 | 0.992825E+09 | 0.00 | 17.90 |
June | 0.00 | 0.509790E+11 | 0.00 | 2816323.86 | 0.00 | 0.00 | 0.106503E+09 | 0.00 | 17.13 |
July | 0.00 | 0.660355E+11 | 0.00 | 1795563.51 | 0.00 | 0.00 | 0.154908E+09 | 0.00 | 16.33 |
August | 0.00 | 0.700295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.09 |
September | 0.00 | 0.586426E+11 | 0.00 | 884110.14 | 0.00 | 0.00 | 27766875.76 | 0.00 | 17.12 |
October | 0.00 | 0.374031E+11 | 0.00 | 8960884.79 | 0.00 | 0.00 | 0.752211E+09 | 0.00 | 18.33 |
November | 0.00 | 0.152389E+11 | 0.00 | 35629095.37 | 0.00 | 0.00 | 0.450696E+10 | 0.00 | 19.15 |
December | 0.00 | 0.533418E+10 | 0.00 | 88976264.24 | 0.00 | 0.00 | 0.191404E+11 | 0.00 | 19.45 |
Annual Sum or Average | 0.00 | 0.357577E+12 | 0.00 | 0.480727E+09 | 0.00 | 0.00 | 0.987663E+11 | 0.00 | 18.21 |
Minimum of Months | 0.00 | 0.937569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.09 |
Maximum of Months | 0.00 | 0.700295E+11 | 0.00 | 0.114736E+09 | 0.00 | 0.00 | 0.315489E+11 | 0.00 | 19.56 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.837462E+10 | 0.00 | 0.00 | 0.00 | 0.190840E+09 | 0.00 | 0.00 | 0.00 | 1.13 |
February | 0.557575E+10 | 2049822.64 | 0.00 | 0.00 | 0.508844E+09 | 0.00 | 0.00 | 0.00 | 1.12 |
March | 0.430868E+10 | 0.142392E+09 | 0.00 | 46243.74 | 0.963547E+09 | 0.00 | 12956670.34 | 0.00 | 1.10 |
April | 0.128248E+10 | 0.112994E+10 | 0.00 | 319265.58 | 0.202471E+10 | 0.00 | 73608315.33 | 0.00 | 1.07 |
May | 0.125219E+09 | 0.661821E+10 | 0.00 | 716786.54 | 0.401621E+09 | 0.00 | 0.141072E+09 | 0.00 | 1.07 |
June | 3158885.51 | 0.122149E+11 | 0.00 | 198450.62 | 0.195207E+09 | 0.00 | 23500699.71 | 0.00 | 1.06 |
July | 516306.08 | 0.172269E+11 | 0.00 | 315114.79 | 37374185.99 | 0.00 | 45136201.75 | 0.00 | 1.08 |
August | 0.00 | 0.183261E+11 | 0.00 | 0.00 | 39327259.33 | 0.00 | 0.00 | 0.00 | 1.07 |
September | 3670996.93 | 0.139291E+11 | 0.00 | 5975.21 | 0.392165E+09 | 0.00 | 2280832.60 | 0.00 | 1.06 |
October | 0.160219E+09 | 0.712287E+10 | 0.00 | 191735.79 | 0.136289E+10 | 0.00 | 37011423.16 | 0.00 | 1.07 |
November | 0.130653E+10 | 0.130198E+10 | 0.00 | 57299.78 | 0.191297E+10 | 0.00 | 5068502.66 | 0.00 | 1.08 |
December | 0.520775E+10 | 0.00 | 0.00 | 0.00 | 0.108434E+10 | 0.00 | 0.00 | 0.00 | 1.12 |
Annual Sum or Average | 0.263486E+11 | 0.780144E+11 | 0.00 | 1850872.04 | 0.911383E+10 | 0.00 | 0.340635E+09 | 0.00 | 1.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 37374185.99 | 0.00 | 0.00 | 0.00 | 1.06 |
Maximum of Months | 0.837462E+10 | 0.183261E+11 | 0.00 | 716786.54 | 0.202471E+10 | 0.00 | 0.141072E+09 | 0.00 | 1.13 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:02:48
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.135306E+12 | 0.145308E+10 | 0.580843E+11 | 0.239681E+12 | 0.504062E+12 |
February | 0.159815E+12 | 0.772525E+09 | 0.332196E+11 | 0.127820E+12 | 0.589352E+12 |
March | 0.208086E+12 | 0.406975E+09 | 0.155407E+11 | 0.575881E+11 | 0.801224E+12 |
April | 0.229777E+12 | -900379579.9 | -0.470815E+11 | -0.174390E+12 | 0.105715E+13 |
May | 0.245368E+12 | -0.249970E+10 | -0.127424E+12 | -0.488185E+12 | 0.143204E+13 |
June | 0.242374E+12 | -0.414171E+10 | -0.219318E+12 | -0.804167E+12 | 0.167036E+13 |
July | 0.234946E+12 | -0.547046E+10 | -0.288134E+12 | -0.103979E+13 | 0.194500E+13 |
August | 0.229534E+12 | -0.582080E+10 | -0.310996E+12 | -0.109970E+13 | 0.201990E+13 |
September | 0.188612E+12 | -0.472923E+10 | -0.249235E+12 | -0.925146E+12 | 0.177081E+13 |
October | 0.146472E+12 | -0.298187E+10 | -0.145212E+12 | -0.604567E+12 | 0.150109E+13 |
November | 0.112192E+12 | -0.103343E+10 | -0.459287E+11 | -0.191107E+12 | 0.108469E+13 |
December | 0.115480E+12 | 0.533493E+09 | 0.218697E+11 | 0.904024E+11 | 0.729237E+12 |
Annual Sum or Average | 0.224796E+13 | -0.244115E+11 | -0.130461E+13 | -0.481157E+13 | 0.151049E+14 |
Minimum of Months | 0.112192E+12 | -0.582080E+10 | -0.310996E+12 | -0.109970E+13 | 0.504062E+12 |
Maximum of Months | 0.245368E+12 | 0.145308E+10 | 0.580843E+11 | 0.239681E+12 | 0.201990E+13 |