Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2023-10-16 09:02:46
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10467.41 | 922.62 | 922.62 |
Net Site Energy | 10467.41 | 922.62 | 922.62 |
Total Source Energy | 28118.82 | 2478.46 | 2478.46 |
Net Source Energy | 28118.82 | 2478.46 | 2478.46 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 3.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3318.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 604.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 174.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 641.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 604.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 188.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 295.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 452.74 | 622.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 44.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 8051.92 | 2415.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 3.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 3318.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 604.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 174.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 952.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 22.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 604.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 188.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 295.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.75 | 622.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Other | 361.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 21.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 3.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3318.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 604.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 174.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 641.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 604.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 188.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 295.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 452.74 | 622.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 44.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 402.25 | 55.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 238.81 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 709.71 | 212.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 402.25 | 55.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 238.81 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 709.71 | 212.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 8051.918 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 8051.918 | 100.00 |
Total On-Site and Utility Electric Sources | 8051.918 | 100.00 |
Total Electricity End Uses | 8051.918 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 3133.21 | 98.03 |
Air to Air Heat Recovery for Heating | 62.83 | 1.97 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 3196.04 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 145.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8433.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYSLAUNDRY HPWH TANK | SWHSYS1 HPWH TANK |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| SWHSYS1 HPWH FAN | SWHSYSLAUNDRY HPWH FAN | FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02 |
RunPeriod | RUNPERIOD 1 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 6.6442 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 9.6995 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 9.6995 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 4.0903 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.7049 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 9.2569 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 9.0417 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 4.4132 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.4132 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.7327 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 4.4132 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8432 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8432 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.6442 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 4.0903 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.7049 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 9.2569 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 9.0417 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 4.4132 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.4132 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.7327 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 4.4132 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.8432 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.8432 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.6992 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 27-JUL-19:19 | 18-JAN-18:49 | - | - | - | - | - | - | - | - | - | - | 09-JAN-21:49 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 190132.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 50471.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 87982.85 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31577.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 29619.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 7310.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 38234.82 | 46939.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1682.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 458047.05 | 151187.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 190132.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 50471.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58308.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1274.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 29619.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 7310.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3810.24 | 46939.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 771.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 670.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 4.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 10508.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1914.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 552.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5473.02 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2031.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1914.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 596.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 935.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1433.82 | 675.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 140.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 25500.43 | 2618.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 926.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 168.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 52.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 82.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 126.38 | 59.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2247.67 | 230.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 926.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 168.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 52.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 82.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 126.38 | 59.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2247.67 | 230.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.28 | 0.660581 | 0.577000 | 1.32 | 1.00 | 0.500000 | 0.000577 | 0.000061 | 1.32 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.264793 | 0.193012 | 0.577000 | 0.152786 | 0.577000 | 0.500000 | 0.001974 | 0.000019 | 0.152786 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.220151 | 0.268832 | 0.577000 | 0.127027 | 0.716886 | 0.500000 | 0.001417 | 0.000010 | 0.127027 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.200186 | 0.625184 | 0.577000 | 0.115508 | 1.00 | 0.500000 | 0.000609 | 0.000012 | 0.115508 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.107210 | 0.673505 | 0.577000 | 0.061860 | 1.00 | 0.500000 | 0.000566 | 0.000007 | 0.061860 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.25 | 0.072583 | 0.577000 | 1.88 | 0.577000 | 0.500000 | 0.020830 | 0.000096 | 1.88 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.23 | 0.116751 | 0.577000 | 0.711238 | 0.577000 | 0.500000 | 0.003263 | 0.000063 | 0.711238 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.37 | 0.228366 | 0.577000 | 2.52 | 0.608975 | 0.500000 | 0.001668 | 0.000185 | 2.52 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.12 | 1.00 | 0.577000 | 0.647218 | 1.00 | 0.500000 | 0.000360 | 0.000075 | 0.647218 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.14 | 0.117982 | 0.577000 | 1.24 | 0.577000 | 0.500000 | 0.003229 | 0.000087 | 1.24 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.25 | 0.112460 | 0.577000 | 1.30 | 0.577000 | 0.500000 | 0.003388 | 0.000090 | 1.30 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.12 | 0.066744 | 0.577000 | 1.22 | 0.577000 | 0.500000 | 0.010267 | 0.000061 | 1.22 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.658158 | 0.477148 | 0.577000 | 0.379757 | 1.00 | 0.500000 | 0.000798 | 0.000050 | 0.379757 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 6945.93 | 0.000061 | 144.85 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 2179.89 | 0.000019 | 49.91 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1104.85 | 0.000010 | 23.85 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1395.54 | 0.000012 | 31.20 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 810.82 | 0.000007 | 18.33 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10961.00 | 0.000096 | 229.86 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 7225.47 | 0.000063 | 158.32 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 21101.17 | 0.000185 | 453.92 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 3152.81 | 0.000028 | 90.07 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 3153.08 | 0.000028 | 90.08 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 19391.91 | 0.000170 | 554.02 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 19397.21 | 0.000170 | 554.17 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 3151.82 | 0.000028 | 90.05 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 3152.10 | 0.000028 | 90.05 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 8585.00 | 0.000075 | 194.42 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 971.83 | 0.000009 | 27.76 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 972.08 | 0.000009 | 27.77 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 4702.70 | 0.000041 | 134.35 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 9921.83 | 0.000087 | 212.68 |
DINING_FLR_6 VAV BOX REHEAT COIL | 10316.85 | 0.000090 | 220.98 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7025.77 | 0.000061 | 147.18 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 5675.93 | 0.000050 | 130.94 |
VAV WITH REHEAT HEATING COIL | 58306.04 | 0.000510 | 1081.95 |
FLR_3_DOAS HEATING COIL | 5950.05 | 0.000052 | 110.41 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 0.904733 | 0.000028 | 0.000365 |
ROOM_2_FLR_3 FAN COIL | 0.914959 | 0.000028 | 0.000369 |
ROOM_3_MULT19_FLR_3 FAN COIL | 4.66 | 0.000170 | 0.001842 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.69 | 0.000170 | 0.002394 |
ROOM_5_FLR_3 FAN COIL | 0.808981 | 0.000028 | 0.000328 |
ROOM_6_FLR_3 FAN COIL | 0.816774 | 0.000028 | 0.000331 |
ROOM_1_FLR_6 FAN COIL | 0.238656 | 0.000009 | 0.000096 |
ROOM_2_FLR_6 FAN COIL | 0.240978 | 0.000009 | 0.000097 |
ROOM_3_MULT9_FLR_6 FAN COIL | 0.961841 | 0.000041 | 0.000398 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 0.904733 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 0.914959 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 4.66 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.69 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 0.808981 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.816774 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.238656 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.240978 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 0.961841 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008632 | 12.80 | 0.008500 | 0.000365 | 0.904733 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008630 | 12.80 | 0.008500 | 0.000369 | 0.914959 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008552 | 12.80 | 0.008500 | 0.001842 | 4.66 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008790 | 12.80 | 0.008500 | 0.002394 | 5.69 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008648 | 12.80 | 0.008500 | 0.000328 | 0.808981 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008647 | 12.80 | 0.008500 | 0.000331 | 0.816774 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008625 | 12.80 | 0.008500 | 0.000096 | 0.238656 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008624 | 12.80 | 0.008500 | 0.000097 | 0.240978 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008727 | 12.80 | 0.008500 | 0.000398 | 0.961841 | |
VAV WITH REHEAT COOLING COIL | 29.33 | 6.70 | 0.014058 | 11.08 | 0.008500 | 0.028349 | 20.10 | 793698.19 |
FLR_3_DOAS COOLING COIL | 33.20 | 6.70 | 0.017167 | 11.94 | 0.008500 | 0.003869 | 2.05 | 108329.82 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.66 | 11.66 | 20.21 | 11.66 | 20.10 | 20.10 | 0.300000 | 0.580240 | 20.10 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 20.10 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 20.10 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.028349 | 0.000017 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.000510 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.003869 | 0.000123 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000052 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Size Rated Evaporator Air Flow Rate [m3/s] | Design Size Rated Condenser Water Flow Rate [m3/s] | |
SWHSYSLAUNDRY HPWH DXCOIL | 4.90 | 0.004370 |
SWHSYS1 HPWH DXCOIL | 3.87 | 0.003451 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
SWHSYSLAUNDRY HPWH FAN | 4.90 | 700.51 |
SWHSYS1 HPWH FAN | 3.87 | 553.22 |
Condenser water flow rate [m3/s] | Evaporator air flow rate [m3/s] | |
SWHSYS1 HPWH | 0.003451 | 3.87 |
SWHSYSLAUNDRY HPWH | 0.004370 | 4.90 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.038440 | 7842.72 | |
HEATSYS1 PUMP | 0.001886 | 562.28 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.001886 | 0.226289 |
COOLSYS1 | 0.038440 | 4.61 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 215551.66 | 215551.66 | 0.001886 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.038440 | 5429.78 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.038440 | 1076229.64 | 1079019.20 | 123.01 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 HPWH TANK | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.49 | 8.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 6.644 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.024 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 4.090 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.780 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.705 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.235 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 9.257 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.637 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 9.042 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.112 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.733 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2943.236 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 13147.704 | 6.644 | 123.454 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13147.704 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 650.557 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 650.557 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 753.347 | 9.699 | 60.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 753.347 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 387.592 | 4.090 | 189.996 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 387.592 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 445.205 | 5.705 | 53.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 445.205 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1748.285 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1748.285 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 11828.200 | 9.042 | 28.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11828.200 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 108.229 | 4.413 | 72.152 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.229 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1718.521 | 4.413 | 82.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1718.521 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1212.035 | 11.733 | 54.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1212.035 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1818.789 | 4.413 | 82.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1818.789 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 1.287 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.608 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.684 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.608 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.684 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.4124 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.4124 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6100 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4545 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4264 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4545 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4264 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.165 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.165 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
21 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
22 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
23 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | 0.16691074E-14 | 0.45207920E-16 | -0.13282787E-09 | -0.59403108E-17 |
29 | 8 | 0.19494068E-07 | 0.16957001E-12 | 0.35230437E-03 | -0.22165426E-09 |
30 | 7 | -0.11479370E-01 | 0.90467759E-08 | -0.21987867E-01 | 0.13052461E-03 |
31 | 6 | 0.38463807 | 0.31869432E-05 | 0.45441076 | -0.45036152E-02 |
32 | 5 | -4.9884079 | 0.12028467E-03 | -4.3052891 | 0.60677235E-01 |
33 | 4 | 32.108494 | 0.99355415E-03 | 20.908458 | -0.41024850 |
34 | 3 | -109.32288 | 0.21841230E-02 | -54.572312 | 1.4876971 |
35 | 2 | 195.24423 | 0.12380226E-02 | 76.910992 | -2.8707534 |
36 | 1 | -170.46733 | 0.13310261E-03 | -54.975783 | 2.7333683 |
37 | 0 | 57.057407 | 0.76355891E-06 | 15.605832 | |
38 | 9 | 0.14115123E-14 | 0.53960859E-16 | -0.11739578E-09 | -0.22900007E-17 |
39 | 8 | 0.17311930E-07 | 0.20639465E-12 | 0.32798840E-03 | -0.19684260E-09 |
40 | 7 | -0.10748946E-01 | 0.11327704E-07 | -0.20934514E-01 | 0.12221941E-03 |
41 | 6 | 0.36478417 | 0.40360747E-05 | 0.43737925 | -0.42695883E-02 |
42 | 5 | -4.7945715 | 0.15382307E-03 | -4.1739388 | 0.58273831E-01 |
43 | 4 | 31.250576 | 0.12816568E-02 | 20.393829 | -0.39885853 |
44 | 3 | -107.49604 | 0.28390629E-02 | -53.554356 | 1.4613070 |
45 | 2 | 193.43186 | 0.16201491E-02 | 75.979619 | -2.8419759 |
46 | 1 | -169.79719 | 0.17527083E-03 | -54.709122 | 2.7216233 |
47 | 0 | 57.057407 | 0.10123612E-05 | 15.653272 | |
48 | 9 | 0.65135446E-15 | 0.56204292E-16 | -0.11372497E-09 | -0.53489081E-17 |
49 | 8 | 0.16791160E-07 | 0.21454591E-12 | 0.32203280E-03 | -0.19092129E-09 |
50 | 7 | -0.10569524E-01 | 0.11862766E-07 | -0.20675571E-01 | 0.12017931E-03 |
51 | 6 | 0.35990649 | 0.42391557E-05 | 0.43318136 | -0.42120931E-02 |
52 | 5 | -4.7469406 | 0.16196889E-03 | -4.1415055 | 0.57683257E-01 |
53 | 4 | 31.039704 | 0.13525358E-02 | 20.266625 | -0.39605902 |
54 | 3 | -107.04684 | 0.30019179E-02 | -53.302690 | 1.4548183 |
55 | 2 | 192.98603 | 0.17160237E-02 | 75.749609 | -2.8348971 |
56 | 1 | -169.63227 | 0.18593554E-03 | -54.643729 | 2.7187328 |
57 | 0 | 57.057407 | 0.10758168E-05 | 15.665287 | |
58 | 9 | 0.14115123E-14 | 0.53960859E-16 | -0.11739578E-09 | -0.22900007E-17 |
59 | 8 | 0.17311930E-07 | 0.20639465E-12 | 0.32798840E-03 | -0.19684260E-09 |
60 | 7 | -0.10748946E-01 | 0.11327704E-07 | -0.20934514E-01 | 0.12221941E-03 |
61 | 6 | 0.36478417 | 0.40360747E-05 | 0.43737925 | -0.42695883E-02 |
62 | 5 | -4.7945715 | 0.15382307E-03 | -4.1739388 | 0.58273831E-01 |
63 | 4 | 31.250576 | 0.12816568E-02 | 20.393829 | -0.39885853 |
64 | 3 | -107.49604 | 0.28390629E-02 | -53.554356 | 1.4613070 |
65 | 2 | 193.43186 | 0.16201491E-02 | 75.979619 | -2.8419759 |
66 | 1 | -169.79719 | 0.17527083E-03 | -54.709122 | 2.7216233 |
67 | 0 | 57.057407 | 0.10123612E-05 | 15.653272 | |
68 | 9 | 0.65135446E-15 | 0.56204292E-16 | -0.11372497E-09 | -0.53489081E-17 |
69 | 8 | 0.16791160E-07 | 0.21454591E-12 | 0.32203280E-03 | -0.19092129E-09 |
70 | 7 | -0.10569524E-01 | 0.11862766E-07 | -0.20675571E-01 | 0.12017931E-03 |
71 | 6 | 0.35990649 | 0.42391557E-05 | 0.43318136 | -0.42120931E-02 |
72 | 5 | -4.7469406 | 0.16196889E-03 | -4.1415055 | 0.57683257E-01 |
73 | 4 | 31.039704 | 0.13525358E-02 | 20.266625 | -0.39605902 |
74 | 3 | -107.04684 | 0.30019179E-02 | -53.302690 | 1.4548183 |
75 | 2 | 192.98603 | 0.17160237E-02 | 75.749609 | -2.8348971 |
76 | 1 | -169.63227 | 0.18593554E-03 | -54.643729 | 2.7187328 |
77 | 0 | 57.057407 | 0.10758168E-05 | 15.665287 | |
78 | 7 | -0.10696287E-14 | 0.39031946E-16 | -0.22096194E-13 | 0.53014468E-15 |
79 | 6 | 0.18597363E-10 | 0.52355087E-11 | 0.51921923E-09 | -0.18483703E-10 |
80 | 5 | -0.10208356E-06 | 0.25520809E-07 | -0.21786771E-05 | 0.17041956E-06 |
81 | 4 | 0.13587196E-03 | 0.96408156E-05 | 0.17589348E-02 | -0.28090751E-03 |
82 | 3 | -0.20124247E-01 | 0.34048350E-03 | -0.21477792 | 0.43172268E-01 |
83 | 2 | 0.28586126 | 0.14813331E-02 | 2.8938873 | -0.61762740 |
84 | 1 | -0.72340799 | 0.92453067E-03 | -7.1302655 | 1.5680075 |
85 | 0 | 0.46030979 | 0.18706506E-04 | 4.4521723 | |
86 | 7 | -0.22096194E-13 | 0.39031946E-16 | -0.10696287E-14 | 0.53014468E-15 |
87 | 6 | 0.51921923E-09 | 0.52355087E-11 | 0.18597363E-10 | -0.18483703E-10 |
88 | 5 | -0.21786771E-05 | 0.25520809E-07 | -0.10208356E-06 | 0.17041956E-06 |
89 | 4 | 0.17589348E-02 | 0.96408156E-05 | 0.13587196E-03 | -0.28090751E-03 |
90 | 3 | -0.21477792 | 0.34048350E-03 | -0.20124247E-01 | 0.43172268E-01 |
91 | 2 | 2.8938873 | 0.14813331E-02 | 0.28586126 | -0.61762740 |
92 | 1 | -7.1302655 | 0.92453067E-03 | -0.72340799 | 1.5680075 |
93 | 0 | 4.4521723 | 0.18706506E-04 | 0.46030979 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5095_SHGC_0.23 | 37 | 1 | VerySmooth | 2.897 | 2.897 | 1.000 | 0.231 | ||
2 | RESWINDOW_U_0.5095_SHGC_0.23 | 38 | 1 | VerySmooth | 2.897 | 2.897 | 1.000 | 0.231 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 1.83516E-002 | 0.14129 | 0.62979 | 0.62979 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10484 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 1.83516E-002 | 0.14129 | 0.62979 | 0.62979 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10484 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | "DX Coil Total Cooling Rate {W | HPWH Only}" | |
1 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | 1.1400 | 77692.7 | 48.891 | 1.7316 | 76621 | |
2 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | 2.8400 | 63045.8 | 4.646 | 9.4738 | 53264 |
Node Number | Height {m} | Volume {m3} | Maximum Capacity {W} | Off-Cycle UA {W/K} | On-Cycle UA {W/K} | Number Of Inlets | Number Of Outlets | |
1 | 1 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 0 | 1 |
2 | 2 | 0.2683 | 0.4733 | 16900.000 | 1.5573 | 1.5573 | 0 | 0 |
3 | 3 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
4 | 4 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
5 | 5 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 1 |
6 | 6 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 2 | 0 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 9.802E-003 | 1.461E-004 | 7.212E-005 | 0.133 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 3.784E-003 | 4.872E-005 | 1.327E-004 | 4.426E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 8.942E-003 | 5.445E-005 | 1.424E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 5.159E-003 | 5.445E-005 | 1.182E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 1.221E-002 | 1.565E-004 | 1.392E-004 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 2.167E-002 | 1.147E-004 | 6.318E-005 | 0.104 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 6.191E-002 | 4.733E-005 | 9.051E-005 | 4.300E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.587E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.588E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 6.879E-003 | 1.766E-005 | 1.424E-004 | 2.086E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 2.910E-003 | 1.186E-004 | 6.472E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1.243E-002 | 1.204E-004 | 6.523E-005 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1.217E-002 | 2.953E-005 | 2.446E-005 | 3.488E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 6.8639E-002 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.6868E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 7.4322E-002 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.7764E-002 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 5.5686E-002 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.9297E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.4391E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.0788E-003 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.6465E-002 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.3691E-002 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 8.2783E-002 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.4947E-002 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 6.1557E-002 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.4805E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 2.7408E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.1075E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.8227E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0220E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.4207E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 7.8005E-003 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.3286E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 5.2976E-003 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.4020E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 8.4927E-003 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.8227E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0220E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.4207E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 7.8005E-003 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.3286E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 5.2976E-003 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.4020E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 8.4927E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 31379.23433 | 31379.23433 | 2.28264 | 2.28264 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 29.14650 | 1.71595E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | 00:10:00 | 8.70000 | 6.99286E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 3639.64310 | 3639.64310 | 0.26479 | 0.26479 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.20000 | 1.71672E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 1374.20072 | 1374.20072 | 5.89721E-002 | 7.92179E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8.70000 | 6.99286E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3026.02857 | 3026.02857 | 0.22015 | 0.22015 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 31.25700 | 1.71635E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 435.00834 | 435.00834 | 1.86679E-002 | 9.17347E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8.70000 | 6.99286E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2752.20300 | 2752.20300 | 0.20019 | 0.20019 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 29.54850 | 1.71603E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 786.45354 | 786.45354 | 3.37497E-002 | 3.37497E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8.70000 | 6.99286E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1473.93398 | 1473.93398 | 0.10721 | 0.10721 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 31.70367 | 1.71644E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 484.61905 | 484.61905 | 2.07969E-002 | 5.77652E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8.70000 | 6.99286E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44692.19763 | 44692.19763 | 3.25110 | 3.25110 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 32.86500 | 1.71666E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1069.33564 | 1069.33564 | 4.58892E-002 | 4.58892E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8.70000 | 6.99286E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 16928.77389 | 16928.77389 | 1.23265 | 1.23265 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.20000 | 1.71672E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 3474.86574 | 3474.86574 | 0.14912 | 0.67639 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8.70000 | 6.99286E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 59982.71266 | 59982.71266 | 4.36510 | 4.36510 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.20000 | 1.71672E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 7819.58642 | 7819.58642 | 0.33557 | 1.89399 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8.70000 | 6.99286E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 9229.65740 | 9229.65740 | 0.90473 | 0.90473 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 3152.81040 | 3152.81040 | 0.13609 | 0.13609 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8.70000 | 6.99286E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 9333.98449 | 9333.98449 | 0.91496 | 0.91496 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.15033 | 1.71652E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 3153.08440 | 3153.08440 | 0.13611 | 0.13611 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8.70000 | 6.99286E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 47551.49224 | 47551.49224 | 4.66093 | 4.66093 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.20000 | 1.71672E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 18644.90492 | 18644.90492 | 0.80483 | 0.83707 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8.70000 | 6.99286E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 58002.89678 | 58002.89678 | 5.68580 | 5.68580 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 31.70367 | 1.71644E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 18662.05754 | 18662.05754 | 0.80557 | 0.83730 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8.70000 | 6.99286E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 8252.83791 | 8252.83791 | 0.80898 | 0.80898 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 30.65400 | 1.71624E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 3151.82830 | 3151.82830 | 0.13605 | 0.13605 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8.70000 | 6.99286E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 8332.33543 | 8332.33543 | 0.81677 | 0.81677 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 30.65400 | 1.71624E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 3152.10231 | 3152.10231 | 0.13606 | 0.13606 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8.70000 | 6.99286E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 15420.11250 | 15420.11250 | 1.12169 | 1.12169 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.03867 | 1.71650E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 5171.94749 | 5171.94749 | 0.22195 | 0.47476 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8.70000 | 6.99286E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2434.65374 | 2434.65374 | 0.23866 | 0.23866 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 971.82907 | 971.82907 | 4.19499E-002 | 4.19499E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8.70000 | 6.99286E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2458.34389 | 2458.34389 | 0.24098 | 0.24098 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 972.08187 | 972.08187 | 4.19608E-002 | 4.19608E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8.70000 | 6.99286E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 9812.03508 | 9812.03508 | 0.96184 | 0.96184 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.20000 | 1.71672E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 4702.70014 | 4702.70014 | 0.20300 | 0.20300 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8.70000 | 6.99286E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29410.86878 | 29410.86878 | 2.14205 | 2.14205 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.20000 | 1.71672E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 3403.99221 | 3403.99221 | 0.14608 | 1.18780 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8.70000 | 6.99286E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30855.24146 | 30855.24146 | 2.24722 | 2.24722 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.20000 | 1.71672E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 3479.03620 | 3479.03620 | 0.14930 | 1.18780 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 8.70000 | 6.99286E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 29085.53198 | 29085.53198 | 2.12131 | 2.12131 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 32.59700 | 1.71661E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 607.90510 | 607.90510 | 2.60851E-002 | 0.36735 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 8.70000 | 6.99286E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 9047.86559 | 9047.86559 | 0.65816 | 0.65816 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.20000 | 1.71672E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 3673.27501 | 3673.27501 | 0.15763 | 0.15763 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 8.70000 | 6.99286E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 401641.41 | 20.10138 | 20.10138 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 68729.47 | 7.10848 | 7.10848 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 50573.62 | 14.83053 | 2.05125 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 19832.79 | 2.50559 | 2.05125 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.28264 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.66058 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57700 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.31708 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.76765E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.07660E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.31708 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6945.92523 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.07660E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 144.84530 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.26479 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19301 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57700 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15279 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57700 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.97397E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.90706E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.15279 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2179.88552 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.90706E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 49.91154 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22015 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26883 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57700 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12703 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71689 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.41724E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.66572E-006 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12703 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1104.85138 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.66572E-006 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 23.84522 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.20019 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.62518 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57700 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11551 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.09421E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.22088E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11551 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1395.53524 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.22088E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 31.20269 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.10721 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.67351 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57700 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.18602E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.65697E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.09337E-006 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.18602E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 810.81592 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.09337E-006 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 18.33052 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.25110 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.25828E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57700 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.87588 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57700 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.08298E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.58916E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.87588 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10961.00180 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.58916E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 229.85935 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23265 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11675 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57700 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.71124 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57700 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.26336E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.32116E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71124 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7225.47092 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.32116E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 158.31918 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.36510 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22837 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57700 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.51866 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60897 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.66838E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.84602E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.51866 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21101.16792 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.84602E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 453.92340 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.90473 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.90473 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.75821E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.65404E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68345 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63178E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.65404E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.90473 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3152.80654 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.75821E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 90.07460 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.91496 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.91496 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.75845E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.69378E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68345 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63021E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.69378E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.91496 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3153.08054 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.75845E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 90.08243 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 4.66093 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 4.66093 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.69649E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.84195E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68403 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55193E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.84195E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 4.66093 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 19391.90943 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69649E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 554.01897 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.68580 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.68580 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.69695E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.39423E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68314 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.78954E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.39423E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.68580 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 19397.21211 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69695E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 554.17046 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.80898 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.80898 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.75735E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.28148E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68342 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.64783E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.28148E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.80898 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3151.82444 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.75735E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 90.04655 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.81677 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.81677 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.75759E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.31191E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68342 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.64651E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.31191E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.81677 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3152.09845 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.75759E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 90.05437 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.12169 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.00000 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57700 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.64722 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.60067E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.51053E-005 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.64722 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8584.99780 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.51053E-005 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 194.41730 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.23866 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.23866 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.50197E-006 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.62124E-005 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68346 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62502E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.62124E-005 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.23866 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 971.82792 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.50197E-006 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 27.76467 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.24098 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.24098 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.50419E-006 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.71135E-005 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68346 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62369E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.71135E-005 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.24098 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 972.08072 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.50419E-006 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 27.77189 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.96184 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.96184 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.11412E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.98455E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68316 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.72700E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.98455E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.96184 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4702.69568 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.11412E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 134.35369 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.14205 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11798 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57700 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.23597 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57700 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.22932E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.68005E-005 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.23597 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9921.82930 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.68005E-005 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 212.67550 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.24722 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11246 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57700 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.29664 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57700 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.38786E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.02563E-005 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.29664 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10316.85413 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.02563E-005 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 220.98338 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.12131 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.67436E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57700 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.22400 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57700 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.02673E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.14645E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.22400 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7025.77469 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.14645E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 147.18499 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65816 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.47715 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57700 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.37976 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.98494E-004 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.96555E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.37976 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5675.93188 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.96555E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 130.93961 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.66363 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.66363 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 20.21426 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.66363 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 20.10138 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 20.10138 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.58024 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 20.10138 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 20.10138 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 29.33241 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.08297 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.40578E-002 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 793698.18800 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.83491E-002 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 20.10138 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 58306.03887 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.10087E-004 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1081.94703 |
350 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 20.10138 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.83491E-002 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.67974E-005 |
353 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.10087E-004 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
356 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 33.20000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.94186 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.71672E-002 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 108329.82081 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.86929E-003 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 5950.04693 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.20536E-005 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 110.41113 |
368 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.86929E-003 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.23069E-004 |
371 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.20536E-005 |
372 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 4.90359 |
373 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 4.36989E-003 |
374 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.90359 |
375 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Electric Power Consumption [W] | 700.51236 |
376 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 3.87257 |
377 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 3.45109E-003 |
378 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.87257 |
379 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Electric Power Consumption [W] | 553.22422 |
380 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Condenser water flow rate [m3/s] | 3.45109E-003 |
381 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Evaporator air flow rate [m3/s] | 3.87257 |
382 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 3.84404E-002 |
383 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 7842.72053 |
384 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.88574E-003 |
385 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.22629 |
386 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.88574E-003 |
387 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 562.27928 |
388 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
389 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 215551.66335 |
390 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 215551.66000 |
391 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.88574E-003 |
392 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 3.84404E-002 |
393 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 4.61285 |
394 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 3.84404E-002 |
395 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 5429.77995 |
396 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 3.84404E-002 |
397 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1076229.64418 |
398 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1079019.20000 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 123.00819 |
400 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
401 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
402 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
403 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
404 | WaterHeater:Stratified | SWHSYS1 HPWH TANK | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
405 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Condenser water flow rate [m3/s] | 4.36989E-003 |
406 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Evaporator air flow rate [m3/s] | 4.90359 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 6981.80 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 2190.02 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1110.38 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 1402.18 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 814.63 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11017.31 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 7261.13 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 21207.02 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 3395.33 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 3395.63 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 20883.59 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 20889.30 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 3394.27 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 3394.57 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 8625.35 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1046.58 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1046.85 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 5064.43 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 9971.76 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 10368.81 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7061.90 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 5702.11 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 52199.94 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 5326.93 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 15100.16 | 12180.62 | 2919.54 | 0.81 | 1694.29 | 17.18 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 15266.62 | 12316.19 | 2950.43 | 0.81 | 1713.02 | 17.37 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 76692.24 | 62199.85 | 14492.39 | 0.81 | 8620.44 | 87.43 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 97491.26 | 77844.87 | 19646.39 | 0.80 | 10905.74 | 110.61 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 13540.13 | 10910.56 | 2629.57 | 0.81 | 1518.73 | 15.40 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 13667.39 | 11014.07 | 2653.32 | 0.81 | 1533.05 | 15.55 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 3978.47 | 3210.70 | 767.77 | 0.81 | 446.46 | 4.53 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4016.23 | 3241.47 | 774.77 | 0.81 | 450.71 | 4.57 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 16319.70 | 13082.66 | 3237.04 | 0.80 | 1827.64 | 18.54 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 625155.69 | 408172.25 | 216983.44 | 0.65 | 74936.20 | 760.04 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 67803.65 | 43510.62 | 24293.03 | 0.64 | 8145.92 | 82.62 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.608 | 1.296 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.608 | 1.296 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.608 | 1.296 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.608 | 1.296 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.684 | 1.345 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.684 | 1.345 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.684 | 1.345 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.684 | 1.345 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.684 | 1.345 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.6160100068E-002 | 1.9412448515E-002 | Pass | Pass | 8.5204468013E-003 | 1.8990645522E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.1685059852E-002 | 4.2938596323E-002 | Pass | Pass | 1.5537954785E-002 | 1.7810233953E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.2449053526E-002 | 2.5358724988E-002 | Pass | Pass | 9.0828826065E-003 | 1.8516281260E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.3229422156E-002 | 1.3549202131E-002 | Pass | Pass | 8.8971588240E-003 | 1.9875492351E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.0098809223E-002 | 8.8740535471E-003 | Pass | Pass | 8.7380643369E-003 | 1.9891707336E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.9076397449E-002 | 0.2139112353 | Pass | Pass | 1.8618042566E-002 | 4.7094646288E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.8890787700E-002 | 4.0310734728E-002 | Pass | Pass | 1.6289568769E-002 | 2.5762922860E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.1978450074E-002 | 3.5685784479E-002 | Pass | Pass | 1.1463889641E-002 | 2.1126389129E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2644836057E-002 | 0.3241178946 | Pass | Pass | 1.0410169381 | 11.0917334710 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 0.1102287086 | 0.2957334937 | Pass | Pass | 7.7483423680E-002 | 0.2094101334 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.1330830792E-005 | 1.1173798082E-004 | Pass | Pass | 3.1472511550E-002 | 4.0383625416E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 0.1162566274 | 0.2566015948 | Pass | Pass | 9.8410603402E-002 | 0.2523705818 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2634752059E-002 | 0.3339404178 | Pass | Pass | 0.1523688989 | 0.5606038336 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 0.1417330484 | 0.3826713306 | Pass | Pass | 9.3374384293E-002 | 0.2871286980 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.0447255347E-002 | 9.5045805546E-003 | Pass | Pass | 8.7052554367E-003 | 1.9448874873E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2649252380E-002 | 0.3228639227 | Pass | Pass | 0.4457759300 | 4.1174129218 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1031266981 | 0.2857887008 | Pass | Pass | 7.2607300414E-002 | 0.1853446585 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2688393280E-002 | 0.3140544520 | Pass | Pass | 0.1069395777 | 0.3605086651 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.8862737865E-002 | 4.9579058108E-002 | Pass | Pass | 1.3677565544E-002 | 3.6035770456E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.6306921247E-002 | 4.3990264422E-002 | Pass | Pass | 1.3772550474E-002 | 3.4777205329E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.9402653803E-002 | 5.3846769134E-002 | Pass | Pass | 1.9284998928E-002 | 3.7955331245E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.1201443350E-002 | 1.5540982827E-002 | Pass | Pass | 9.2562919502E-003 | 1.8176807480E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3200.24 | -24.5 | -1109.6 | -4911.5 | 14312.35 | 11467.06 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 65.00 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 38.00 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 391.00 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 225.00 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 5.00 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.897 | 0.231 | 0.231 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.897 | 0.231 | 0.231 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.897 | 0.231 | 0.231 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.897 | 0.231 | 0.231 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.897 | 0.231 | 0.231 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.897 | 0.231 | 0.231 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.897 | 0.231 | 0.231 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.897 | 0.231 | 0.231 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.897 | 0.231 | 0.231 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.897 | 0.231 | 0.231 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.897 | 0.231 | 0.231 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.897 | 0.231 | 0.231 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.897 | 0.231 | 0.231 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.897 | 0.231 | 0.231 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.897 | 0.231 | 0.231 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.897 | 0.231 | 0.231 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.897 | 0.231 | 0.231 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.897 | 0.231 | 0.231 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.897 | 0.231 | 0.231 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.897 | 0.231 | 0.231 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.897 | 0.231 | 0.231 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.897 | 0.231 | 0.231 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.897 | 0.231 | 0.231 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.897 | 0.231 | 0.231 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.897 | 0.231 | 0.231 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.897 | 0.231 | 0.231 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.897 | 0.231 | 0.231 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.897 | 0.231 | 0.231 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.897 | 0.231 | 0.231 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.897 | 0.231 | 0.231 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.897 | 0.231 | 0.231 | |||||||||||||||||
North Total or Average | 432.95 | 2.897 | 0.231 | 0.231 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.897 | 0.231 | 0.231 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.6442 | 1978.83 | 13147.70 | LightsWired | LTG_SCH_BASEMENT | 45.99 | 168.00 | 45.94 | 0.0000 | Y | 113.37 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 9.6995 | 67.07 | 650.56 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 6.26 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 9.6995 | 77.67 | 753.35 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.25 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 4.0903 | 94.76 | 387.59 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 1.87 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.7049 | 78.04 | 445.21 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.90 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 9.2569 | 188.86 | 1748.29 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.92 | 0.0000 | Y | 13.10 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 9.0417 | 1308.19 | 11828.20 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 55.48 | 0.0000 | Y | 123.18 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.4132 | 1863.81 | 8225.38 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 73.68 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.4132 | 1864.32 | 8227.62 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 73.70 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 4.4132 | 1557.62 | 6874.08 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 56.74 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.21 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.54 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.19 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.54 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.4132 | 220.77 | 974.32 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 8.73 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.52 | 0.0000 | Y | 28.54 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.52 | 0.0000 | Y | 28.54 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.7327 | 103.30 | 1212.04 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.34 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 4.4132 | 412.12 | 1818.79 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 15.01 |
Interior Lighting Total | 5.8432 | 11345.29 | 66293.22 | 390.09 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 11096.45 | AstronomicalClock | - | 83.82 | 83.82 | 174.60 | |
Exterior Lighting Total | 11096.45 | 174.60 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 215551.66 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1079019.20 | 2.96 | 1079208.86 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10230.52 | 15100.16 | 12180.62 | 2919.54 | 0.81 | - | 1694.29 | 17.18 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10341.78 | 15266.62 | 12316.19 | 2950.43 | 0.81 | - | 1713.02 | 17.37 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 51570.62 | 76692.24 | 62199.85 | 14492.39 | 0.81 | - | 8620.44 | 87.43 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 67033.28 | 97491.26 | 77844.87 | 19646.39 | 0.80 | - | 10905.74 | 110.61 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9187.45 | 13540.13 | 10910.56 | 2629.57 | 0.81 | - | 1518.73 | 15.40 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9272.64 | 13667.39 | 11014.07 | 2653.32 | 0.81 | - | 1533.05 | 15.55 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2693.74 | 3978.47 | 3210.70 | 767.77 | 0.81 | - | 446.46 | 4.53 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2718.97 | 4016.23 | 3241.47 | 774.77 | 0.81 | - | 450.71 | 4.57 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 11155.88 | 16319.70 | 13082.66 | 3237.04 | 0.80 | - | 1827.64 | 18.54 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 793698.19 | 625155.69 | 408172.25 | 216983.44 | 0.65 | - | 74936.20 | 760.04 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 108329.82 | 67803.65 | 43510.62 | 24293.03 | 0.64 | - | 8145.92 | 82.62 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 6945.93 | 6981.80 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2179.89 | 2190.02 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1104.85 | 1110.38 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1395.54 | 1402.18 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 810.82 | 814.63 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10961.00 | 11017.31 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 7225.47 | 7261.13 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 21101.17 | 21207.02 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3152.81 | 3395.33 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3153.08 | 3395.63 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 19391.91 | 20883.59 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 19397.21 | 20889.30 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3151.82 | 3394.27 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3152.10 | 3394.57 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 8585.00 | 8625.35 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 971.83 | 1046.58 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 972.08 | 1046.85 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 4702.70 | 5064.43 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 9921.83 | 9971.76 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10316.85 | 10368.81 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7025.77 | 7061.90 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 5675.93 | 5702.11 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 58306.04 | 52199.94 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 5950.05 | 5326.93 | - |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 75921.46 | 3.40 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 54370.95 | 3.40 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.90 | 636.60 | 703.64 | 1.00 | 1.22 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.91 | 643.80 | 703.64 | 1.00 | 1.22 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 4.66 | 3279.60 | 703.64 | 1.00 | 0.98 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.69 | 4000.74 | 703.64 | 1.00 | 0.96 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.81 | 569.23 | 703.64 | 1.00 | 1.25 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.82 | 574.71 | 703.64 | 1.00 | 1.25 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.24 | 167.93 | 703.64 | 1.00 | 1.89 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.24 | 169.56 | 703.64 | 1.00 | 1.88 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.96 | 676.79 | 703.64 | 1.00 | 1.21 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1314.72 | 20.10 | 42797.88 | 2129.10 | 1.00 | 1.12 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 4.90 | 700.51 | 142.86 | 0.00 | 2.78 | General | ||
SWHSYS1 HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 3.87 | 553.22 | 142.86 | 0.00 | 2.84 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.038440 | 7842.72 | 204022.71 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.001886 | 562.28 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.038440 | 5429.78 | 141251.80 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYSLAUNDRY HPWH | WaterHeater:HeatPump:PumpedCondenser | 1.14 | 77692.71 | 0.80 | 48.89 | 1.73 |
SWHSYS1 HPWH | WaterHeater:HeatPump:PumpedCondenser | 2.84 | 63045.86 | 0.80 | 4.65 | 9.47 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 31379.23 | 31379.23 | 15.86 | 2.283 | 2.283 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 24.00 | 24.00 | 0.00927 | 29.15 | 0.01716 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 3639.64 | 3639.64 | 54.27 | 0.265 | 0.265 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00924 | 33.20 | 0.01717 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3026.03 | 3026.03 | 38.96 | 0.220 | 0.220 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.00 | 24.00 | 0.00947 | 31.26 | 0.01716 | 0.092 | 0.00 |
MECH_FLR_1 | 2752.20 | 2752.20 | 16.76 | 0.200 | 0.200 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 24.00 | 24.00 | 0.00881 | 29.55 | 0.01716 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1473.93 | 1473.93 | 15.55 | 0.107 | 0.107 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 24.00 | 24.00 | 0.00891 | 31.70 | 0.01716 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44692.20 | 44692.20 | 572.69 | 3.251 | 3.251 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00855 | 32.87 | 0.01717 | 0.000 | 0.00 |
CAFE_FLR_1 | 16928.77 | 16928.77 | 89.64 | 1.233 | 1.233 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 23.99 | 0.01043 | 33.20 | 0.01717 | 0.676 | 0.00 |
LOBBY_FLR_1 | 59982.71 | 59982.71 | 45.85 | 4.365 | 4.365 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 23.99 | 0.01012 | 33.20 | 0.01717 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 9229.66 | 9229.66 | 236.52 | 0.905 | 0.905 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00863 | 32.26 | 0.01717 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 9333.98 | 9333.98 | 239.23 | 0.915 | 0.915 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00863 | 32.15 | 0.01717 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 47551.49 | 47551.49 | 1938.99 | 4.661 | 4.661 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 21.11 | 21.11 | 0.00855 | 33.20 | 0.01717 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 58002.90 | 58002.90 | 2364.52 | 5.686 | 5.686 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 21.11 | 21.11 | 0.00879 | 31.70 | 0.01716 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 8252.84 | 8252.84 | 211.49 | 0.809 | 0.809 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 21.11 | 21.11 | 0.00865 | 30.65 | 0.01716 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 8332.34 | 8332.34 | 213.55 | 0.817 | 0.817 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 21.11 | 21.11 | 0.00865 | 30.65 | 0.01716 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 15420.11 | 15420.11 | 39.60 | 1.122 | 1.122 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00978 | 32.04 | 0.01717 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2434.65 | 2434.65 | 62.39 | 0.239 | 0.239 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00863 | 32.26 | 0.01717 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2458.34 | 2458.34 | 63.01 | 0.241 | 0.241 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00862 | 32.26 | 0.01717 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 9812.04 | 9812.04 | 399.99 | 0.962 | 0.962 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 21.11 | 21.11 | 0.00873 | 33.20 | 0.01717 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29410.87 | 29410.87 | 88.68 | 2.142 | 2.142 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 23.98 | 0.01043 | 33.20 | 0.01717 | 1.188 | 0.00 |
DINING_FLR_6 | 30855.24 | 30855.24 | 93.03 | 2.247 | 2.247 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 23.99 | 0.01034 | 33.20 | 0.01717 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 29085.53 | 29085.53 | 281.55 | 2.121 | 2.121 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01018 | 32.60 | 0.01717 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9047.87 | 9047.87 | 21.95 | 0.658 | 0.658 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00909 | 33.20 | 0.01717 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | 00:10:00 | 21.00 | 22.74 | 0.00699 | 8.70 | 0.00699 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 1374.20 | 1374.20 | 20.49 | 0.059 | 0.079 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00796 | 8.70 | 0.00699 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 435.01 | 435.01 | 5.60 | 0.019 | 0.092 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00795 | 8.70 | 0.00699 | 0.092 | 0.00 |
MECH_FLR_1 | 786.45 | 786.45 | 4.79 | 0.034 | 0.034 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00794 | 8.70 | 0.00699 | 0.000 | 0.00 |
STORAGE_FLR_1 | 484.62 | 484.62 | 5.11 | 0.021 | 0.058 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00794 | 8.70 | 0.00699 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1069.34 | 1069.34 | 13.70 | 0.046 | 0.046 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00794 | 8.70 | 0.00699 | 0.000 | 0.00 |
CAFE_FLR_1 | 3474.87 | 3474.87 | 18.40 | 0.149 | 0.676 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00796 | 8.70 | 0.00699 | 0.676 | 0.00 |
LOBBY_FLR_1 | 7819.59 | 7819.59 | 5.98 | 0.336 | 1.894 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00795 | 8.70 | 0.00699 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 3152.81 | 3152.81 | 80.80 | 0.136 | 0.136 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00796 | 8.70 | 0.00699 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 3153.08 | 3153.08 | 80.81 | 0.136 | 0.136 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00796 | 8.70 | 0.00699 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 18644.90 | 18644.90 | 760.28 | 0.805 | 0.837 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00796 | 8.70 | 0.00699 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 18662.06 | 18662.06 | 760.77 | 0.806 | 0.837 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00796 | 8.70 | 0.00699 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 3151.83 | 3151.83 | 80.77 | 0.136 | 0.136 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00796 | 8.70 | 0.00699 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 3152.10 | 3152.10 | 80.79 | 0.136 | 0.136 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00796 | 8.70 | 0.00699 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 5171.95 | 5171.95 | 13.28 | 0.222 | 0.475 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00797 | 8.70 | 0.00699 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 971.83 | 971.83 | 24.90 | 0.042 | 0.042 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00797 | 8.70 | 0.00699 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 972.08 | 972.08 | 24.91 | 0.042 | 0.042 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00797 | 8.70 | 0.00699 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4702.70 | 4702.70 | 191.71 | 0.203 | 0.203 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00797 | 8.70 | 0.00699 | 0.099 | 0.00 |
BANQUET_FLR_6 | 3403.99 | 3403.99 | 10.26 | 0.146 | 1.188 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00798 | 8.70 | 0.00699 | 1.188 | 0.00 |
DINING_FLR_6 | 3479.04 | 3479.04 | 10.49 | 0.149 | 1.188 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 21.00 | 21.00 | 0.00798 | 8.70 | 0.00699 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 607.91 | 607.91 | 5.88 | 0.026 | 0.367 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00516 | 8.70 | 0.00699 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 3673.28 | 3673.28 | 8.91 | 0.158 | 0.158 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 21.00 | 21.00 | 0.00798 | 8.70 | 0.00699 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 20.10 | 20.10 | 7.11 | 7.11 | 20.1014 | 11.6636 | 20.1014 | 0.5802 | 0.3000 |
FLR_3_DOAS | 14.83 | 2.05 | 2.51 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 6945.925 | 6945.925 | 1.317082 | 0.00006077 | 144.845 | 1/21 00:10:00 | 1/21 00:10:00 | 6945.93 | 6945.93 | 1.317082 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 0.00 | 0.00 | 6984.96 | 6984.96 | ||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 2179.886 | 2179.886 | 0.152786 | 0.00001907 | 49.912 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2179.89 | 2179.89 | 0.152786 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00795872 | 51.3929 | 1374.20 | 0.00 | 2191.60 | 2191.60 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1104.851 | 1104.851 | 0.127027 | 0.00000967 | 23.845 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1104.85 | 1104.85 | 0.127027 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00795007 | 51.3377 | 435.01 | 0.00 | 1110.99 | 1110.99 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1395.535 | 1395.535 | 0.115508 | 0.00001221 | 31.203 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1395.54 | 1395.54 | 0.115508 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00793568 | 51.2460 | 786.45 | 0.00 | 1403.10 | 1403.10 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 810.816 | 810.816 | 0.061860 | 0.00000709 | 18.331 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 810.82 | 810.82 | 0.061860 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00793954 | 51.2706 | 484.62 | 0.00 | 815.19 | 815.19 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10961.002 | 10961.002 | 1.875884 | 0.00009589 | 229.859 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10961.00 | 10961.00 | 1.875884 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00793550 | 51.2449 | 1069.34 | 0.00 | 11022.48 | 11022.48 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 7225.471 | 7225.471 | 0.711238 | 0.00006321 | 158.319 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7225.47 | 7225.47 | 0.711238 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00796372 | 51.4248 | 3474.87 | 0.00 | 7265.45 | 7265.45 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 21101.168 | 21101.168 | 2.518660 | 0.00018460 | 453.923 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21101.17 | 21101.17 | 2.518660 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00795435 | 51.3650 | 7819.59 | 0.00 | 21218.53 | 21218.53 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 10230.522 | -999.000 | 0.904733 | 0.00036540 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 10230.52 | 9908.72 | 0.904733 | 21.68 | 15.66 | 0.00863178 | 12.80 | 12.09 | 0.00850000 | 32.26 | 0.01716543 | 25.09 | 0.0000 | 21.11 | 0.00863178 | 55.3032 | 9229.66 | 0.00 | 10251.98 | 9772.48 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 3152.807 | 3152.807 | 0.136094 | 0.00002758 | 90.075 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3152.81 | 3152.81 | 0.136094 | 21.11 | 14.84 | 0.00795848 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.11 | 0.00795848 | 51.0421 | 3152.81 | 0.00 | 3398.84 | 3398.84 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 10341.780 | -999.000 | 0.914959 | 0.00036938 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 10341.78 | 10020.22 | 0.914959 | 21.68 | 15.66 | 0.00863021 | 12.80 | 12.09 | 0.00850000 | 32.15 | 0.01716522 | 25.06 | 0.0000 | 21.11 | 0.00863021 | 55.2933 | 9333.98 | 0.00 | 10363.48 | 9882.24 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 3153.081 | 3153.081 | 0.136106 | 0.00002758 | 90.082 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3153.08 | 3153.08 | 0.136106 | 21.11 | 14.84 | 0.00795848 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.11 | 0.00795848 | 51.0422 | 3153.08 | 0.00 | 3399.13 | 3399.13 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 51570.623 | -999.000 | 4.660928 | 0.00184195 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | unknown | 7/21 14:50:00 | 51570.62 | 50918.95 | 4.660928 | 21.68 | 15.59 | 0.00855193 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 0.0000 | 21.11 | 0.00855193 | 54.7969 | 47551.49 | 0.00 | 51681.09 | 50163.47 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 19391.909 | 19391.909 | 0.837072 | 0.00016965 | 554.019 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 19391.91 | 19391.91 | 0.837072 | 21.11 | 14.85 | 0.00796262 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.11 | 0.00796262 | 51.0683 | 18644.90 | 0.00 | 20905.18 | 20905.18 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 67033.279 | -999.000 | 5.685803 | 0.00239423 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | unknown | 7/21 17:50:00 | 67033.28 | 62568.46 | 5.685803 | 21.68 | 15.80 | 0.00878954 | 12.80 | 12.09 | 0.00850000 | 31.70 | 0.01716436 | 24.94 | 0.0000 | 21.11 | 0.00878954 | 56.3004 | 58002.90 | 0.00 | 67168.48 | 61835.44 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 19397.212 | 19397.212 | 0.837300 | 0.00016970 | 554.170 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 19397.21 | 19397.21 | 0.837300 | 21.11 | 14.85 | 0.00796264 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.11 | 0.00796264 | 51.0684 | 18662.06 | 0.00 | 20910.89 | 20910.89 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 9187.451 | -999.000 | 0.808981 | 0.00032815 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | 7/21 10:00:00 | 9187.45 | 8864.49 | 0.808981 | 21.68 | 15.67 | 0.00864783 | 12.80 | 12.09 | 0.00850000 | 30.65 | 0.01716236 | 24.67 | 0.0000 | 21.11 | 0.00864783 | 55.4047 | 8252.84 | 0.00 | 9206.64 | 8744.50 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 3151.824 | 3151.824 | 0.136052 | 0.00002757 | 90.047 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3151.82 | 3151.82 | 0.136052 | 21.11 | 14.84 | 0.00795847 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.11 | 0.00795847 | 51.0420 | 3151.83 | 0.00 | 3397.78 | 3397.78 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 9272.645 | -999.000 | 0.816774 | 0.00033119 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | 7/21 10:00:00 | 9272.64 | 8949.51 | 0.816774 | 21.68 | 15.67 | 0.00864651 | 12.80 | 12.09 | 0.00850000 | 30.65 | 0.01716236 | 24.67 | 0.0000 | 21.11 | 0.00864651 | 55.3963 | 8332.34 | 0.00 | 9292.02 | 8828.21 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 3152.098 | 3152.098 | 0.136063 | 0.00002758 | 90.054 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3152.10 | 3152.10 | 0.136063 | 21.11 | 14.84 | 0.00795847 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.11 | 0.00795847 | 51.0421 | 3152.10 | 0.00 | 3398.07 | 3398.07 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 8584.998 | 8584.998 | 0.647218 | 0.00007511 | 194.417 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8585.00 | 8585.00 | 0.647218 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00796883 | 51.4573 | 5171.95 | 0.00 | 8631.29 | 8631.29 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2693.740 | -999.000 | 0.238656 | 0.00009621 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 2693.74 | 2613.22 | 0.238656 | 21.68 | 15.65 | 0.00862502 | 12.80 | 12.09 | 0.00850000 | 32.26 | 0.01716543 | 25.09 | 0.0000 | 21.11 | 0.00862502 | 55.2605 | 2434.65 | 0.00 | 2699.40 | 2577.06 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 971.828 | 971.828 | 0.041950 | 0.00000850 | 27.765 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 971.83 | 971.83 | 0.041950 | 21.11 | 14.85 | 0.00796605 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.11 | 0.00796605 | 51.0901 | 971.83 | 0.00 | 1047.67 | 1047.67 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2718.971 | -999.000 | 0.240978 | 0.00009711 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 2718.97 | 2638.54 | 0.240978 | 21.68 | 15.65 | 0.00862369 | 12.80 | 12.09 | 0.00850000 | 32.26 | 0.01716543 | 25.09 | 0.0000 | 21.11 | 0.00862369 | 55.2521 | 2458.34 | 0.00 | 2724.69 | 2601.97 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 972.081 | 972.081 | 0.041961 | 0.00000850 | 27.772 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 972.08 | 972.08 | 0.041961 | 21.11 | 14.85 | 0.00796606 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.11 | 0.00796606 | 51.0902 | 972.08 | 0.00 | 1047.94 | 1047.94 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 11155.878 | -999.000 | 0.961841 | 0.00039845 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | unknown | 7/21 14:40:00 | 11155.88 | 10564.83 | 0.961841 | 21.68 | 15.74 | 0.00872700 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 0.0000 | 21.11 | 0.00872700 | 55.9055 | 9812.04 | 0.00 | 11178.72 | 10432.73 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 4702.696 | 4702.696 | 0.202997 | 0.00004114 | 134.354 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4702.70 | 4702.70 | 0.202997 | 21.11 | 14.85 | 0.00796764 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.11 | 0.00796764 | 51.1001 | 4702.70 | 0.00 | 5069.67 | 5069.67 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 9921.829 | 9921.829 | 1.235965 | 0.00008680 | 212.675 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9921.83 | 9921.83 | 1.235965 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00797595 | 51.5028 | 3403.99 | 0.00 | 9977.07 | 9977.07 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10316.854 | 10316.854 | 1.296643 | 0.00009026 | 220.983 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 10316.85 | 10316.85 | 1.296643 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00797645 | 51.5059 | 3479.04 | 0.00 | 10374.31 | 10374.31 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7025.775 | 7025.775 | 1.223998 | 0.00006146 | 147.185 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 7025.77 | 7025.77 | 1.223998 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00515992 | 33.4736 | 607.91 | 0.00 | 7065.20 | 7065.20 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 5675.932 | 5675.932 | 0.379757 | 0.00004966 | 130.940 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 5675.93 | 5675.93 | 0.379757 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00798038 | 51.5310 | 3673.28 | 0.00 | 5706.34 | 5706.34 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 793698.188 | -999.000 | 20.101385 | 0.02834906 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 793698.19 | 444923.57 | 20.101385 | 29.33 | 22.31 | 0.01405785 | 11.08 | 11.08 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 58.0132 | 23.99 | 0.00976791 | 52.4386 | 276146.16 | 0.00 | 794730.38 | 445416.89 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 58306.039 | 58306.039 | 6.030415 | 0.00051009 | 1081.947 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 58306.04 | 58306.04 | 6.030415 | 8.70 | 8.70 | 0.00699286 | 16.70 | 13.18 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 193.3774 | 21.53 | 0.00765547 | 47.8877 | 31418.57 | 0.00 | 63205.49 | 63205.49 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 108329.821 | -999.000 | 2.051317 | 0.00386929 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 108329.82 | 53987.08 | 2.051317 | 33.20 | 25.32 | 0.01716721 | 11.94 | 11.73 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 99.9965 | 21.11 | 0.00868456 | 55.6363 | 150592.54 | 0.00 | 108457.34 | 54776.98 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 5950.047 | 5950.047 | 0.615395 | 0.00005205 | 110.411 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 5950.05 | 5950.05 | 0.615395 | 8.70 | 8.70 | 0.00699286 | 16.70 | 13.18 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 333.3216 | 21.11 | 0.00796263 | 51.0684 | 56563.40 | 0.00 | 6450.03 | 6450.03 |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 73461.225 | 54067.461 | 4.903586 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 75921.46 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 58043.819 | 42720.251 | 3.872570 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 54370.95 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 6945.925 | 6945.925 | 1.317082 | 0.00006077 | 144.845 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 3.1588 | 3.222395 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 6945.93 | 6945.93 | 1.0000 | 1.58410618 | 1.317082 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.06075979 | 60.00 | 32.22 | 27.78 | 0.000 | 6945.93 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 0.00 | 0.00 | 6984.96 | 6984.96 | 1.58410618 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2179.886 | 2179.886 | 0.152786 | 0.00001907 | 49.912 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 0.9914 | 1.011305 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2179.89 | 2179.89 | 1.0000 | 0.18376149 | 0.152786 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.01906864 | 60.00 | 32.22 | 27.78 | 0.000 | 2179.89 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00795872 | 21.00 | 0.00795872 | 51.3929 | 1374.20 | 0.00 | 2191.60 | 2191.60 | 0.18376149 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.30 | 17.46 | 0.00800000 | 48861.0 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1104.851 | 1104.851 | 0.127027 | 0.00000967 | 23.845 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 0.5025 | 0.512569 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1104.85 | 1104.85 | 1.0000 | 0.15278039 | 0.127027 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.00966474 | 60.00 | 32.22 | 27.78 | 0.000 | 1104.85 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00795007 | 21.00 | 0.00795007 | 51.3377 | 435.01 | 0.00 | 1110.99 | 1110.99 | 0.15278039 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.73 | 15.86 | 0.00800000 | 44206.5 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1395.535 | 1395.535 | 0.115508 | 0.00001221 | 31.203 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 0.6347 | 0.647425 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1395.54 | 1395.54 | 1.0000 | 0.13892538 | 0.115508 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.01220751 | 60.00 | 32.22 | 27.78 | 0.000 | 1395.54 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00793568 | 21.00 | 0.00793568 | 51.2460 | 786.45 | 0.00 | 1403.10 | 1403.10 | 0.13892538 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.50 | 16.84 | 0.00800000 | 47034.4 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 810.816 | 810.816 | 0.061860 | 0.00000709 | 18.331 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 0.3687 | 0.376159 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 810.82 | 810.82 | 1.0000 | 0.07440169 | 0.061860 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.00709265 | 60.00 | 32.22 | 27.78 | 0.000 | 810.82 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00793954 | 21.00 | 0.00793954 | 51.2706 | 484.62 | 0.00 | 815.19 | 815.19 | 0.07440169 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.34 | 17.14 | 0.00800000 | 47891.4 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10961.002 | 10961.002 | 1.875884 | 0.00009589 | 229.859 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 4.9848 | 5.085093 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 10961.00 | 10961.00 | 1.0000 | 2.25619848 | 1.875884 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.09588184 | 60.00 | 32.22 | 27.78 | 0.000 | 10961.00 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00793550 | 21.00 | 0.00793550 | 51.2449 | 1069.34 | 0.00 | 11022.48 | 11022.48 | 2.25619848 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.39 | 15.00 | 0.00800000 | 41820.2 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7225.471 | 7225.471 | 0.711238 | 0.00006321 | 158.319 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 3.2860 | 3.352083 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7225.47 | 7225.47 | 1.0000 | 0.85543343 | 0.711238 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.06320512 | 60.00 | 32.22 | 27.78 | 0.000 | 7225.47 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00796372 | 21.00 | 0.00796372 | 51.4248 | 3474.87 | 0.00 | 7265.45 | 7265.45 | 0.85543343 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.93 | 16.29 | 0.00800000 | 45428.0 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21101.168 | 21101.168 | 2.518660 | 0.00018460 | 453.923 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 9.5963 | 9.789378 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 21101.17 | 21101.17 | 1.0000 | 3.02929078 | 2.518660 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.18458339 | 60.00 | 32.22 | 27.78 | 0.000 | 21101.17 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00795435 | 21.00 | 0.00795435 | 51.3650 | 7819.59 | 0.00 | 21218.53 | 21218.53 | 3.02929078 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.47 | 15.76 | 0.00800000 | 43939.2 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10230.522 | -999.000 | 0.904733 | 0.00036540 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8860 | 1004.8586 | 1.2027 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.904733 | 1.08815714 | 4197.9300 | 999.8980 | 38.43650793 | 13.37 | 6.70 | 6.67 | 1076229.64 | 0.9506 | 0.950571 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 10230.52 | 9908.72 | 1.0000 | 1.08815714 | 0.904733 | 21.68 | 15.66 | 0.00863178 | 43723.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.36536644 | 6.70 | 13.37 | 6.67 | 0.000 | 10230.52 | 32.26 | 0.01716543 | 25.09 | 0.00000000 | 0.0000 | 21.11 | 0.00863178 | 21.11 | 0.00863178 | 55.3032 | 9229.66 | 0.00 | 10251.98 | 9772.48 | 1.08815714 | 21.68 | 15.67 | 0.00863178 | 43723.9 | 12.89 | 12.09 | 0.00845726 | 34302.5 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3152.807 | 3152.807 | 0.136094 | 0.00002758 | 90.075 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.904733 | 1.08815714 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 1.4338 | 1.462669 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3152.81 | 3152.81 | 1.0000 | 0.16368554 | 0.136094 | 21.11 | 14.84 | 0.00795848 | 41429.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.02757931 | 60.00 | 32.22 | 27.78 | 0.000 | 3152.81 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.11 | 0.00795848 | 21.11 | 0.00795848 | 51.0421 | 3152.81 | 0.00 | 3398.84 | 3398.84 | 0.16368554 | 16.60 | 13.11 | 0.00795848 | 36829.6 | 36.96 | 20.24 | 0.00795848 | 57594.0 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10341.780 | -999.000 | 0.914959 | 0.00036938 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8831 | 1004.8586 | 1.2027 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.914959 | 1.10045687 | 4197.9300 | 999.8980 | 38.43650793 | 13.37 | 6.70 | 6.67 | 1076229.64 | 0.9609 | 0.960909 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 10341.78 | 10020.22 | 1.0000 | 1.10045687 | 0.914959 | 21.68 | 15.66 | 0.00863021 | 43719.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.36933984 | 6.70 | 13.37 | 6.67 | 0.000 | 10341.78 | 32.15 | 0.01716522 | 25.06 | 0.00000000 | 0.0000 | 21.11 | 0.00863021 | 21.11 | 0.00863021 | 55.2933 | 9333.98 | 0.00 | 10363.48 | 9882.24 | 1.10045687 | 21.68 | 15.67 | 0.00863021 | 43719.9 | 12.89 | 12.09 | 0.00845701 | 34302.5 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3153.081 | 3153.081 | 0.136106 | 0.00002758 | 90.082 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.914959 | 1.10045687 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 1.4339 | 1.462796 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3153.08 | 3153.08 | 1.0000 | 0.16369976 | 0.136106 | 21.11 | 14.84 | 0.00795848 | 41429.2 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.02758171 | 60.00 | 32.22 | 27.78 | 0.000 | 3153.08 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.11 | 0.00795848 | 21.11 | 0.00795848 | 51.0422 | 3153.08 | 0.00 | 3399.13 | 3399.13 | 0.16369976 | 16.60 | 13.11 | 0.00795848 | 36829.6 | 36.96 | 20.24 | 0.00795848 | 57594.1 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 51570.623 | -999.000 | 4.660928 | 0.00184195 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7376 | 1004.8586 | 1.2027 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 4.660928 | 5.60587955 | 4197.9300 | 999.8980 | 38.43650793 | 13.37 | 6.70 | 6.67 | 1076229.64 | 4.7918 | 4.791697 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | unknown | unknown | unknown | 7/21 14:50:00 | Sensible | 51570.62 | 50918.95 | 1.0000 | 5.60587955 | 4.660928 | 21.68 | 15.59 | 0.00855193 | 43521.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 1.84176085 | 6.70 | 13.37 | 6.67 | 0.000 | 51570.62 | 33.20 | 0.01716721 | 25.32 | 0.00000000 | 0.0000 | 21.11 | 0.00855193 | 21.11 | 0.00855193 | 54.7969 | 47551.49 | 0.00 | 51681.09 | 50163.47 | 5.60587955 | 21.68 | 15.60 | 0.00855193 | 43521.6 | 12.92 | 12.09 | 0.00844472 | 34302.5 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19391.909 | 19391.909 | 0.837072 | 0.00016965 | 554.019 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 4.660928 | 5.60587955 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 8.8189 | 8.996409 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 19391.91 | 19391.91 | 1.0000 | 1.00677850 | 0.837072 | 21.11 | 14.85 | 0.00796262 | 41439.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.16963158 | 60.00 | 32.22 | 27.78 | 0.000 | 19391.91 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.11 | 0.00796262 | 21.11 | 0.00796262 | 51.0683 | 18644.90 | 0.00 | 20905.18 | 20905.18 | 1.00677850 | 16.60 | 13.11 | 0.00796262 | 36840.1 | 36.96 | 20.24 | 0.00796262 | 57604.5 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 67033.279 | -999.000 | 5.685803 | 0.00239423 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1793 | 1004.8586 | 1.2027 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.685803 | 6.83853630 | 4197.9300 | 999.8980 | 38.43650793 | 13.37 | 6.70 | 6.67 | 1076229.64 | 6.2285 | 6.228413 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | unknown | unknown | unknown | 7/21 17:50:00 | Sensible | 67033.28 | 62568.46 | 1.0000 | 6.83853630 | 5.685803 | 21.68 | 15.80 | 0.00878954 | 44124.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 2.39398444 | 6.70 | 13.37 | 6.67 | 0.000 | 67033.28 | 31.70 | 0.01716436 | 24.94 | 0.00000000 | 0.0000 | 21.11 | 0.00878954 | 21.11 | 0.00878954 | 56.3004 | 58002.90 | 0.00 | 67168.48 | 61835.44 | 6.83853630 | 21.68 | 15.81 | 0.00878954 | 44124.5 | 12.83 | 12.09 | 0.00848066 | 34302.4 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19397.212 | 19397.212 | 0.837300 | 0.00016970 | 554.170 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.685803 | 6.83853630 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 8.8213 | 8.998869 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 19397.21 | 19397.21 | 1.0000 | 1.00705380 | 0.837300 | 21.11 | 14.85 | 0.00796264 | 41439.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.16967796 | 60.00 | 32.22 | 27.78 | 0.000 | 19397.21 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.11 | 0.00796264 | 21.11 | 0.00796264 | 51.0684 | 18662.06 | 0.00 | 20910.89 | 20910.89 | 1.00705380 | 16.60 | 13.11 | 0.00796264 | 36840.1 | 36.96 | 20.24 | 0.00796264 | 57604.6 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9187.451 | -999.000 | 0.808981 | 0.00032815 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9159 | 1004.8586 | 1.2027 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.808981 | 0.97299331 | 4197.9300 | 999.8980 | 38.43650793 | 13.37 | 6.70 | 6.67 | 1076229.64 | 0.8537 | 0.853654 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | unknown | unknown | 7/21 10:00:00 | Sensible | 9187.45 | 8864.49 | 1.0000 | 0.97299331 | 0.808981 | 21.68 | 15.67 | 0.00864783 | 43764.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.32811487 | 6.70 | 13.37 | 6.67 | 0.000 | 9187.45 | 30.65 | 0.01716236 | 24.67 | 0.00000000 | 0.0000 | 21.11 | 0.00864783 | 21.11 | 0.00864783 | 55.4047 | 8252.84 | 0.00 | 9206.64 | 8744.50 | 0.97299331 | 21.68 | 15.68 | 0.00864783 | 43764.7 | 12.88 | 12.09 | 0.00845972 | 34302.5 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3151.824 | 3151.824 | 0.136052 | 0.00002757 | 90.047 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.808981 | 0.97299331 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 1.4334 | 1.462213 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3151.82 | 3151.82 | 1.0000 | 0.16363455 | 0.136052 | 21.11 | 14.84 | 0.00795847 | 41429.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.02757072 | 60.00 | 32.22 | 27.78 | 0.000 | 3151.82 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.11 | 0.00795847 | 21.11 | 0.00795847 | 51.0420 | 3151.83 | 0.00 | 3397.78 | 3397.78 | 0.16363455 | 16.60 | 13.11 | 0.00795847 | 36829.6 | 36.96 | 20.24 | 0.00795847 | 57594.0 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9272.645 | -999.000 | 0.816774 | 0.00033119 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9134 | 1004.8586 | 1.2027 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.816774 | 0.98236562 | 4197.9300 | 999.8980 | 38.43650793 | 13.37 | 6.70 | 6.67 | 1076229.64 | 0.8616 | 0.861570 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | unknown | unknown | 7/21 10:00:00 | Sensible | 9272.64 | 8949.51 | 1.0000 | 0.98236562 | 0.816774 | 21.68 | 15.67 | 0.00864651 | 43761.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.33115742 | 6.70 | 13.37 | 6.67 | 0.000 | 9272.64 | 30.65 | 0.01716236 | 24.67 | 0.00000000 | 0.0000 | 21.11 | 0.00864651 | 21.11 | 0.00864651 | 55.3963 | 8332.34 | 0.00 | 9292.02 | 8828.21 | 0.98236562 | 21.68 | 15.68 | 0.00864651 | 43761.3 | 12.88 | 12.09 | 0.00845952 | 34302.5 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3152.098 | 3152.098 | 0.136063 | 0.00002758 | 90.054 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.816774 | 0.98236562 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 1.4335 | 1.462340 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3152.10 | 3152.10 | 1.0000 | 0.16364877 | 0.136063 | 21.11 | 14.84 | 0.00795847 | 41429.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.02757312 | 60.00 | 32.22 | 27.78 | 0.000 | 3152.10 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.11 | 0.00795847 | 21.11 | 0.00795847 | 51.0421 | 3152.10 | 0.00 | 3398.07 | 3398.07 | 0.16364877 | 16.60 | 13.11 | 0.00795847 | 36829.6 | 36.96 | 20.24 | 0.00795847 | 57594.0 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8584.998 | 8584.998 | 0.647218 | 0.00007511 | 194.417 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 3.9042 | 3.982803 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8585.00 | 8585.00 | 1.0000 | 0.77843429 | 0.647218 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.07509764 | 60.00 | 32.22 | 27.78 | 0.000 | 8585.00 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00796883 | 21.00 | 0.00796883 | 51.4573 | 5171.95 | 0.00 | 8631.29 | 8631.29 | 0.77843429 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.47 | 17.18 | 0.00800000 | 48022.8 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2693.740 | -999.000 | 0.238656 | 0.00009621 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8735 | 1004.8586 | 1.2027 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.238656 | 0.28704031 | 4197.9300 | 999.8980 | 38.43650793 | 13.37 | 6.70 | 6.67 | 1076229.64 | 0.2503 | 0.250289 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 2693.74 | 2613.22 | 1.0000 | 0.28704031 | 0.238656 | 21.68 | 15.65 | 0.00862502 | 43706.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.09620254 | 6.70 | 13.37 | 6.67 | 0.000 | 2693.74 | 32.26 | 0.01716543 | 25.09 | 0.00000000 | 0.0000 | 21.11 | 0.00862502 | 21.11 | 0.00862502 | 55.2605 | 2434.65 | 0.00 | 2699.40 | 2577.06 | 0.28704031 | 21.68 | 15.66 | 0.00862502 | 43706.7 | 12.89 | 12.09 | 0.00845621 | 34302.5 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 971.828 | 971.828 | 0.041950 | 0.00000850 | 27.765 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.238656 | 0.28704031 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 0.4420 | 0.450856 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 971.83 | 971.83 | 1.0000 | 0.05045478 | 0.041950 | 21.11 | 14.85 | 0.00796605 | 41448.4 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.00850111 | 60.00 | 32.22 | 27.78 | 0.000 | 971.83 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.11 | 0.00796605 | 21.11 | 0.00796605 | 51.0901 | 971.83 | 0.00 | 1047.67 | 1047.67 | 0.05045478 | 16.60 | 13.12 | 0.00796605 | 36848.8 | 36.96 | 20.24 | 0.00796605 | 57613.2 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2718.971 | -999.000 | 0.240978 | 0.00009711 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8710 | 1004.8586 | 1.2027 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.240978 | 0.28983336 | 4197.9300 | 999.8980 | 38.43650793 | 13.37 | 6.70 | 6.67 | 1076229.64 | 0.2526 | 0.252634 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 2718.97 | 2638.54 | 1.0000 | 0.28983336 | 0.240978 | 21.68 | 15.65 | 0.00862369 | 43703.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.09710364 | 6.70 | 13.37 | 6.67 | 0.000 | 2718.97 | 32.26 | 0.01716543 | 25.09 | 0.00000000 | 0.0000 | 21.11 | 0.00862369 | 21.11 | 0.00862369 | 55.2521 | 2458.34 | 0.00 | 2724.69 | 2601.97 | 0.28983336 | 21.68 | 15.66 | 0.00862369 | 43703.3 | 12.89 | 12.09 | 0.00845601 | 34302.5 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 972.081 | 972.081 | 0.041961 | 0.00000850 | 27.772 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.240978 | 0.28983336 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 0.4421 | 0.450973 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 972.08 | 972.08 | 1.0000 | 0.05046791 | 0.041961 | 21.11 | 14.85 | 0.00796606 | 41448.4 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.00850332 | 60.00 | 32.22 | 27.78 | 0.000 | 972.08 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.11 | 0.00796606 | 21.11 | 0.00796606 | 51.0902 | 972.08 | 0.00 | 1047.94 | 1047.94 | 0.05046791 | 16.60 | 13.12 | 0.00796606 | 36848.8 | 36.96 | 20.24 | 0.00796606 | 57613.2 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11155.878 | -999.000 | 0.961841 | 0.00039845 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0631 | 1004.8586 | 1.2027 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.961841 | 1.15684421 | 4197.9300 | 999.8980 | 38.43650793 | 13.37 | 6.70 | 6.67 | 1076229.64 | 1.0366 | 1.036551 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | unknown | unknown | unknown | 7/21 14:40:00 | Sensible | 11155.88 | 10564.83 | 1.0000 | 1.15684421 | 0.961841 | 21.68 | 15.74 | 0.00872700 | 43965.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.39841403 | 6.70 | 13.37 | 6.67 | 0.000 | 11155.88 | 33.20 | 0.01716721 | 25.32 | 0.00000000 | 0.0000 | 21.11 | 0.00872700 | 21.11 | 0.00872700 | 55.9055 | 9812.04 | 0.00 | 11178.72 | 10432.73 | 1.15684421 | 21.68 | 15.75 | 0.00872700 | 43965.6 | 12.85 | 12.09 | 0.00847159 | 34302.5 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4702.696 | 4702.696 | 0.202997 | 0.00004114 | 134.354 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.961841 | 1.15684421 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 2.1387 | 2.181702 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 4702.70 | 4702.70 | 1.0000 | 0.24415183 | 0.202997 | 21.11 | 14.85 | 0.00796764 | 41452.4 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.04113704 | 60.00 | 32.22 | 27.78 | 0.000 | 4702.70 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.11 | 0.00796764 | 21.11 | 0.00796764 | 51.1001 | 4702.70 | 0.00 | 5069.67 | 5069.67 | 0.24415183 | 16.60 | 13.12 | 0.00796764 | 36852.8 | 36.96 | 20.24 | 0.00796764 | 57617.2 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9921.829 | 9921.829 | 1.235965 | 0.00008680 | 212.675 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 4.5122 | 4.602994 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9921.83 | 9921.83 | 1.0000 | 1.48654366 | 1.235965 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.08679164 | 60.00 | 32.22 | 27.78 | 0.000 | 9921.83 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00797595 | 21.00 | 0.00797595 | 51.5028 | 3403.99 | 0.00 | 9977.07 | 9977.07 | 1.48654366 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.18 | 15.66 | 0.00800000 | 43646.3 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10316.854 | 10316.854 | 1.296643 | 0.00009026 | 220.983 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 4.6918 | 4.786256 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | Sensible | 10316.85 | 10316.85 | 1.0000 | 1.55952353 | 1.296643 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.09024713 | 60.00 | 32.22 | 27.78 | 0.000 | 10316.85 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00797645 | 21.00 | 0.00797645 | 51.5059 | 3479.04 | 0.00 | 10374.31 | 10374.31 | 1.55952353 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.12 | 15.64 | 0.00800000 | 43587.0 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7025.775 | 7025.775 | 1.223998 | 0.00006146 | 147.185 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 3.1951 | 3.259439 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 7025.77 | 7025.77 | 1.0000 | 1.47215022 | 1.223998 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.06145827 | 60.00 | 32.22 | 27.78 | 0.000 | 7025.77 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 18.73 | 0.00515992 | 21.00 | 0.00515992 | 33.4736 | 607.91 | 0.00 | 7065.20 | 7065.20 | 1.47215022 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.31 | 14.97 | 0.00800000 | 41734.0 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5675.932 | 5675.932 | 0.379757 | 0.00004966 | 130.940 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 2.5813 | 2.633212 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | Sensible | 5675.93 | 5675.93 | 1.0000 | 0.45674873 | 0.379757 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.04965046 | 60.00 | 32.22 | 27.78 | 0.000 | 5675.93 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00798038 | 21.00 | 0.00798038 | 51.5310 | 3673.28 | 0.00 | 5706.34 | 5706.34 | 0.45674873 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.85 | 17.65 | 0.00800000 | 49428.1 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 793698.188 | -999.000 | 20.101385 | 0.02834906 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1030.9728 | 1004.8586 | 1.2027 | VAV WITH REHEAT FAN | Fan:VariableVolume | 20.101385 | 24.17671811 | 4197.9300 | 999.8980 | 38.43650793 | 13.37 | 6.70 | 6.67 | 1076229.64 | 73.7480 | 73.748033 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 793698.19 | 444923.57 | 1.0000 | 24.17671811 | 20.101385 | 29.33 | 22.31 | 0.01405785 | 65398.8 | 11.08 | 11.08 | 0.00850000 | 32569.7 | 28.34616837 | 6.70 | 13.37 | 6.67 | 42797.883 | 750900.31 | 33.20 | 0.01716721 | 25.32 | 11.66146000 | 58.0132 | 23.99 | 0.00976164 | 23.99 | 0.00976791 | 52.4386 | 276146.16 | 0.00 | 794730.38 | 445416.89 | 24.17671811 | 29.33 | 22.32 | 0.01405785 | 65398.8 | 11.46 | 11.37 | 0.00832949 | 32527.0 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 58306.039 | 58306.039 | 6.030415 | 0.00051009 | 1081.947 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | VAV WITH REHEAT FAN | Fan:VariableVolume | 20.101385 | 24.17671811 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 26.5160 | 27.049682 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | Sensible | 58306.04 | 58306.04 | 1.0000 | 7.25301543 | 6.030415 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 0.51003463 | 60.00 | 32.22 | 27.78 | 0.000 | 58306.04 | 8.70 | 0.00699286 | 8.70 | 11.66146000 | 193.3774 | 18.35 | 0.00770957 | 21.53 | 0.00765547 | 47.8877 | 31418.57 | 0.00 | 63205.49 | 63205.49 | 7.25301543 | 2.80 | 2.80 | 0.00699286 | 20338.7 | 11.36 | 9.92 | 0.00699286 | 29053.0 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 108329.821 | -999.000 | 2.051317 | 0.00386929 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1036.7530 | 1004.8586 | 1.2027 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.46711237 | 4197.9300 | 999.8980 | 38.43650793 | 13.37 | 6.70 | 6.67 | 1076229.64 | 10.0657 | 10.065679 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | Sensible | 108329.82 | 53987.08 | 1.0000 | 2.46719911 | 2.051317 | 33.20 | 25.32 | 0.01716721 | 77354.4 | 11.94 | 11.73 | 0.00850000 | 33446.3 | 3.86889549 | 6.70 | 13.37 | 6.67 | 2195.006 | 106134.81 | 33.20 | 0.01716721 | 25.32 | 2.05124512 | 99.9965 | 21.11 | 0.00868128 | 21.11 | 0.00868456 | 55.6363 | 150592.54 | 0.00 | 108457.34 | 54776.98 | 2.46719911 | 33.20 | 25.34 | 0.01716721 | 77354.4 | 11.78 | 11.72 | 0.00854298 | 33394.7 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 5950.047 | 5950.047 | 0.615395 | 0.00005205 | 110.411 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.46711237 | 4197.9300 | 999.8980 | 1.88554762 | 54.44 | 82.22 | 27.78 | 219889.73 | 2.7059 | 2.760381 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 5950.05 | 5950.05 | 1.0000 | 0.74015973 | 0.615395 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 0.05204830 | 60.00 | 32.22 | 27.78 | 0.000 | 5950.05 | 8.70 | 0.00699286 | 8.70 | 2.05124512 | 333.3216 | 21.11 | 0.00796225 | 21.11 | 0.00796263 | 51.0684 | 56563.40 | 0.00 | 6450.03 | 6450.03 | 0.74015973 | 2.80 | 2.80 | 0.00699286 | 20338.7 | 11.36 | 9.92 | 0.00699286 | 29053.0 | |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 73461.225 | 54067.461 | 4.903586 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 1.2027 | SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 4.903586 | 5.89773440 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 75921.46 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 75921.46 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 58043.819 | 42720.251 | 3.872570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 1.2027 | SWHSYS1 HPWH FAN | Fan:SystemModel | 3.872570 | 4.65769018 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 54370.95 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54370.95 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2170.00 | 4508.33 | 0.00 |
RETAIL_1_FLR_1 | 5680.67 | 1979.83 | 0.00 |
RETAIL_2_FLR_1 | 4333.83 | 2182.33 | 0.00 |
MECH_FLR_1 | 1784.67 | 4346.33 | 0.00 |
STORAGE_FLR_1 | 1028.67 | 4985.67 | 0.00 |
LAUNDRY_FLR_1 | 8191.33 | 3450.33 | 3350.50 |
CAFE_FLR_1 | 7718.50 | 3457.00 | 3002.83 |
LOBBY_FLR_1 | 6298.33 | 3190.33 | 2441.33 |
ROOM_1_FLR_3 | 16.00 | 7734.17 | 12.67 |
ROOM_2_FLR_3 | 370.50 | 7653.83 | 256.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 252.33 | 8731.33 | 250.50 |
ROOM_5_FLR_3 | 10.00 | 7492.83 | 9.83 |
ROOM_6_FLR_3 | 404.50 | 7478.83 | 263.17 |
CORRIDOR_FLR_3 | 1870.00 | 5424.00 | 1174.17 |
ROOM_1_FLR_6 | 101.17 | 7507.17 | 57.17 |
ROOM_2_FLR_6 | 547.50 | 7458.00 | 424.00 |
ROOM_3_MULT9_FLR_6 | 166.33 | 7728.00 | 43.17 |
BANQUET_FLR_6 | 8117.67 | 2671.33 | 2451.83 |
DINING_FLR_6 | 8365.00 | 2322.50 | 2238.00 |
KITCHEN_FLR_6 | 8712.50 | 6788.33 | 6784.33 |
CORRIDOR_FLR_6 | 3452.00 | 3581.17 | 0.00 |
Facility | 8732.83 | 8760.00 | 8433.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 19.67 | 0.00 | 19.67 |
ROOM_2_FLR_3 | 0.00 | 15.17 | 0.00 | 15.17 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 69.00 | 0.00 | 69.00 |
ROOM_5_FLR_3 | 0.00 | 12.33 | 0.00 | 12.33 |
ROOM_6_FLR_3 | 0.00 | 38.00 | 0.00 | 38.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 24.83 | 0.00 | 24.83 |
ROOM_2_FLR_6 | 0.00 | 21.50 | 0.00 | 21.50 |
ROOM_3_MULT9_FLR_6 | 0.00 | 80.17 | 0.00 | 80.17 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 145.00 | 0.00 | 145.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.927 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.060 | 0.033 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.437 | 0.011 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.605 | 0.012 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.556 | 0.012 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 22.484 | 0.035 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 3.524 | 0.026 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.772 | 0.011 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.042 | 0.000 | 0.065 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.042 | 0.000 | 0.067 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.403 | 0.019 | 0.000 | 0.105 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.042 | 0.000 | 0.065 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.042 | 0.000 | 0.067 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.461 | 0.005 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.355 | 0.042 | 0.000 | 0.079 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.042 | 0.000 | 0.081 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.403 | 0.034 | 0.000 | 0.125 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.895 | 0.012 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 5.200 | 0.012 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 19.915 | 0.035 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.035 | 0.009 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.610 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.686 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.315 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.559 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.469 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 16.308 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 2.867 | 0.000 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.539 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.000 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.329 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.124 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.362 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 11.864 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.825 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.80 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.58 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.14 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.39 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 38385177.58 | 0.00 | 38385177.58 | 0.00 | 38385177.58 | 26946214.98 | 2.00 | 2.33 | 8755.67 | 0.00 |
RETAIL_1_FLR_1 | 4693043.32 | 0.00 | 4693043.32 | 74829.37 | 4767872.69 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3790949.01 | 0.00 | 3790949.01 | 28884.23 | 3819833.24 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 3378303.17 | 0.00 | 3378303.17 | 68265.16 | 3446568.33 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1791742.00 | 0.00 | 1791742.00 | 39385.24 | 1831127.24 | 1821682.01 | 4288.48 | 2244.03 | 2227.50 | 0.00 |
LAUNDRY_FLR_1 | 59791822.46 | 0.00 | 59791822.46 | 93212.59 | 59885035.06 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 22557641.98 | 0.00 | 22557641.98 | 165414.56 | 22723056.54 | 21330615.53 | 2774.58 | 2123.68 | 3861.74 | 0.00 |
LOBBY_FLR_1 | 78621052.60 | 0.00 | 78621052.60 | 472627.18 | 79093679.78 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 66809.15 | 1526965.87 | 43432.96 | 1570398.82 | 1946875.62 | 2190.00 | 5694.33 | 875.67 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 68724.89 | 1528710.52 | 43429.64 | 1572140.17 | 1946647.51 | 2190.00 | 5695.67 | 874.33 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 0.00 | 1099911.97 | 12118.28 | 1112030.25 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.00 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 67928.83 | 19871758.13 | 12121.60 | 19883879.72 | 26405105.73 | 2190.00 | 5773.81 | 796.19 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 66890.25 | 1527046.96 | 43432.96 | 1570479.92 | 1946875.62 | 2190.00 | 5694.33 | 875.67 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 68742.96 | 1528728.59 | 43429.64 | 1572158.24 | 1946647.51 | 2190.00 | 5694.61 | 875.39 | 0.00 |
CORRIDOR_FLR_3 | 18738384.20 | 0.00 | 18738384.20 | 52519.18 | 18790903.38 | 14972100.18 | 19.33 | 12.83 | 8727.83 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 80896.97 | 445936.15 | 43441.64 | 489377.79 | 486718.90 | 2019.32 | 5688.84 | 1051.85 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 82576.42 | 447572.82 | 43438.32 | 491011.15 | 486661.88 | 2023.79 | 5690.08 | 1046.13 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 81057.71 | 2426248.03 | 22226.26 | 2448474.29 | 3126920.42 | 2190.00 | 5683.83 | 886.17 | 0.00 |
BANQUET_FLR_6 | 42299643.11 | 0.00 | 42299643.11 | 106073.56 | 42405716.67 | 37458366.31 | 2323.34 | 1114.62 | 5322.05 | 0.00 |
DINING_FLR_6 | 44936367.06 | 0.00 | 44936367.06 | 106073.56 | 45042440.62 | 37458366.31 | 0.00 | 0.00 | 8760.00 | 0.00 |
KITCHEN_FLR_6 | 53634743.08 | 0.00 | 53634743.08 | 94960.43 | 53729703.50 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 11158118.01 | 0.00 | 11158118.01 | 92941.97 | 11251059.97 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 7140253.04 | 0.21E+10 | 4376792.35 | 0.21E+10 | 0.43E+10 | 8760.00 | 8139.64 | 8760.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.2172 | 0.0000 | 1.2172 | 0.0000 | 1.2172 | 0.8545 | 2.00 | 2.33 | 8755.67 |
RETAIL_1_FLR_1 | 0.1488 | 0.0000 | 0.1488 | 0.0024 | 0.1512 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1202 | 0.0000 | 0.1202 | 0.0009 | 0.1211 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.1071 | 0.0000 | 0.1071 | 0.0022 | 0.1093 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0568 | 0.0000 | 0.0568 | 0.0012 | 0.0581 | 0.0578 | 4288.48 | 2244.03 | 2227.50 |
LAUNDRY_FLR_1 | 1.8960 | 0.0000 | 1.8960 | 0.0030 | 1.8989 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7153 | 0.0000 | 0.7153 | 0.0052 | 0.7205 | 0.6764 | 2774.58 | 2123.68 | 3861.74 |
LOBBY_FLR_1 | 2.4931 | 0.0000 | 2.4931 | 0.0150 | 2.5080 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0021 | 0.0484 | 0.0014 | 0.0498 | 0.0617 | 2190.00 | 5694.33 | 875.67 |
ROOM_2_FLR_3 | 0.0463 | 0.0022 | 0.0485 | 0.0014 | 0.0499 | 0.0617 | 2190.00 | 5695.67 | 874.33 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0022 | 0.6301 | 0.0004 | 0.6305 | 0.8373 | 2190.00 | 5773.81 | 796.19 |
ROOM_5_FLR_3 | 0.0463 | 0.0021 | 0.0484 | 0.0014 | 0.0498 | 0.0617 | 2190.00 | 5694.33 | 875.67 |
ROOM_6_FLR_3 | 0.0463 | 0.0022 | 0.0485 | 0.0014 | 0.0499 | 0.0617 | 2190.00 | 5694.61 | 875.39 |
CORRIDOR_FLR_3 | 0.5942 | 0.0000 | 0.5942 | 0.0017 | 0.5959 | 0.4748 | 19.33 | 12.83 | 8727.83 |
ROOM_1_FLR_6 | 0.0116 | 0.0026 | 0.0141 | 0.0014 | 0.0155 | 0.0154 | 2019.32 | 5688.84 | 1051.85 |
ROOM_2_FLR_6 | 0.0116 | 0.0026 | 0.0142 | 0.0014 | 0.0156 | 0.0154 | 2023.79 | 5690.08 | 1046.13 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0026 | 0.0769 | 0.0007 | 0.0776 | 0.0992 | 2190.00 | 5683.83 | 886.17 |
BANQUET_FLR_6 | 1.3413 | 0.0000 | 1.3413 | 0.0034 | 1.3447 | 1.1878 | 2323.34 | 1114.62 | 5322.05 |
DINING_FLR_6 | 1.4249 | 0.0000 | 1.4249 | 0.0034 | 1.4283 | 1.1878 | 0.00 | 0.00 | 8760.00 |
KITCHEN_FLR_6 | 1.7007 | 0.0000 | 1.7007 | 0.0030 | 1.7038 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3538 | 0.0000 | 0.3538 | 0.0029 | 0.3568 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 63.1114 | 0.2264 | 63.3378 | 0.1096 | 63.4474 | 73.9670 | 8760.00 | 8139.64 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.56E+09 | 0.00 | 0.56E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 43135961.56 | 583627.18 | 43719588.74 | 64690340.46 | 8750.44 | 9.39 | 0.17 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 17.6042 | 0.0000 | 17.6042 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.3678 | 0.0185 | 1.3863 | 2.0513 | 8750.44 | 9.39 | 0.17 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 17.6042 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.7278 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1363 |
Defaulted Fields | 1208 |
Fields with Defaults | 4115 |
Autosized Fields | 353 |
Autosizable Fields | 407 |
Autocalculated Fields | 289 |
Autocalculatable Fields | 549 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 8051.92 | 76750.16 | 04-FEB-04:00 | 458047.05 | 27-JUL-19:20 |
Electricity:Building | 2339.60 | 31015.39 | 02-JAN-02:10 | 138695.41 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 256.48 | 3058.02 | 02-JAN-02:10 | 18903.76 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2332.51 | 30874.25 | 02-JAN-02:10 | 138454.08 | 02-JAN-20:10 |
InteriorLights:Electricity | 604.37 | 5592.07 | 02-JAN-02:10 | 50471.22 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 113.37 | 1030.12 | 02-JAN-02:10 | 9271.23 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 604.37 | 5592.07 | 02-JAN-02:10 | 50471.22 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 604.37 | 5592.07 | 02-JAN-02:10 | 50471.22 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 113.37 | 1030.12 | 02-JAN-02:10 | 9271.23 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 604.37 | 5592.07 | 02-JAN-02:10 | 50471.22 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 16.45 | 201.26 | 02-JAN-02:10 | 1197.92 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 19.05 | 233.06 | 02-JAN-02:10 | 1387.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.46 | 67.94 | 02-JAN-02:10 | 394.77 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.87 | 16.96 | 02-JAN-02:10 | 152.61 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.87 | 16.96 | 02-JAN-02:10 | 152.61 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.84 | 1007.22 | 02-JAN-02:10 | 4973.49 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 27.44 | 378.04 | 02-JAN-02:10 | 2538.73 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 13.10 | 76.92 | 01-JAN-13:10 | 1573.46 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 13.10 | 76.92 | 01-JAN-13:10 | 1573.46 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 272.18 | 3294.23 | 02-JAN-02:10 | 20674.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 123.19 | 1182.82 | 02-JAN-02:10 | 10645.38 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 123.19 | 1182.82 | 02-JAN-02:10 | 10645.38 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 18.46 | 262.96 | 01-JAN-02:10 | 1214.21 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 18.46 | 262.93 | 01-JAN-02:10 | 1214.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 302.44 | 4545.27 | 01-JAN-02:10 | 20822.55 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 73.68 | 623.81 | 01-JAN-02:10 | 5671.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 73.68 | 623.81 | 01-JAN-02:10 | 5671.40 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 302.52 | 4546.52 | 01-JAN-02:10 | 20828.25 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 73.70 | 623.98 | 01-JAN-02:10 | 5672.95 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 73.70 | 623.98 | 01-JAN-02:10 | 5672.95 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 18.46 | 262.96 | 01-JAN-02:10 | 1214.21 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 18.46 | 262.93 | 01-JAN-02:10 | 1214.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.62 | 65.74 | 01-JAN-02:10 | 303.55 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.74 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.74 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.62 | 65.73 | 01-JAN-02:10 | 303.52 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.73 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.73 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 35.82 | 538.40 | 01-JAN-02:10 | 2466.50 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 8.73 | 73.89 | 01-JAN-02:10 | 671.80 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 8.73 | 73.89 | 01-JAN-02:10 | 671.80 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 204.40 | 2556.31 | 02-JAN-02:10 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.54 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.54 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 204.40 | 2556.31 | 02-JAN-02:10 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.54 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.54 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 444.45 | 5944.83 | 02-JAN-02:10 | 18636.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 44.40 | 741.51 | 16-MAR-22:30 | 2791.20 | 17-DEC-11:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 3996.41 | 2332.00 | 04-FEB-04:00 | 250125.08 | 27-JUL-18:20 |
LowTempRefrigeration:Refrigeration:Electricity | 15.84 | 0.00 | 01-JAN-11:10 | 1308.81 | 23-JUL-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 21.48 | 619.24 | 25-JAN-04:10 | 717.37 | 28-AUG-13:10 |
WaterSystems:Electricity | 452.74 | 1086.62 | 13-MAY-00:20 | 43579.35 | 03-JAN-21:50 |
Electricity:HVAC | 922.27 | 21783.11 | 17-DEC-06:00 | 49615.05 | 21-SEP-21:10 |
Fans:Electricity | 604.49 | 12580.47 | 05-FEB-04:00 | 38839.06 | 21-SEP-21:10 |
General:Fans:Electricity | 604.49 | 12580.47 | 05-FEB-04:00 | 38839.06 | 21-SEP-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ExteriorEquipment:Electricity | 641.49 | 9451.24 | 02-JAN-02:20 | 39155.93 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 22.46 | 386.43 | 03-JAN-04:10 | 1283.34 | 28-MAR-20:10 |
ElectricityPurchased:Facility | 8051.92 | 76750.16 | 04-FEB-04:00 | 458047.05 | 27-JUL-19:20 |
ElectricityPurchased:Plant | 8051.92 | 76750.16 | 04-FEB-04:00 | 458047.05 | 27-JUL-19:20 |
Cogeneration:ElectricityPurchased | 8051.92 | 76750.16 | 04-FEB-04:00 | 458047.05 | 27-JUL-19:20 |
General:Cogeneration:ElectricityPurchased | 8051.92 | 76750.16 | 04-FEB-04:00 | 458047.05 | 27-JUL-19:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 8051.92 | 76750.16 | 04-FEB-04:00 | 458047.05 | 27-JUL-19:20 |
ElectricityNet:Plant | 8051.92 | 76750.16 | 04-FEB-04:00 | 458047.05 | 27-JUL-19:20 |
Cogeneration:ElectricityNet | 8051.92 | 76750.16 | 04-FEB-04:00 | 458047.05 | 27-JUL-19:20 |
General:Cogeneration:ElectricityNet | 8051.92 | 76750.16 | 04-FEB-04:00 | 458047.05 | 27-JUL-19:20 |
ExteriorLights:Electricity | 174.60 | 0.00 | 01-JAN-07:20 | 11096.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 174.60 | 0.00 | 01-JAN-07:20 | 11096.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 295.32 | 8417.13 | 01-JAN-02:10 | 9938.94 | 28-FEB-10:00 |
General:HeatRecovery:Electricity | 295.32 | 8417.13 | 01-JAN-02:10 | 9938.94 | 28-FEB-10:00 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.58 | 07-OCT-00:20 | 4738.73 | 13-FEB-19:10 |
Water Heater Parasitic:WaterSystems:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 3318.04 | 0.00 | 04-FEB-04:00 | 203625.45 | 27-JUL-18:10 |
General:Cooling:Electricity | 3318.04 | 0.00 | 04-FEB-04:00 | 203625.45 | 27-JUL-18:10 |
Pumps:Electricity | 188.33 | 48.25 | 16-MAR-08:00 | 7643.99 | 25-SEP-20:00 |
General:Pumps:Electricity | 188.33 | 48.25 | 16-MAR-08:00 | 7643.99 | 25-SEP-20:00 |
WIRED_LTG_ELECTRICITY | 21.27 | 0.00 | 01-JAN-00:10 | 1776.59 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2415.49 | 29270.80 | 02-JAN-02:10 | 151187.46 | 18-JAN-18:50 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 626.65 | 15908.90 | 01-JAN-11:10 | 53104.38 | 15-JAN-23:00 |
WaterSystems:NaturalGas | 622.93 | 15908.90 | 01-JAN-11:10 | 46939.24 | 18-JAN-19:40 |
Water Heater:WaterSystems:NaturalGas | 622.93 | 15908.90 | 01-JAN-11:10 | 46939.24 | 18-JAN-19:40 |
Heating:NaturalGas | 3.73 | 0.00 | 01-JAN-00:10 | 19263.55 | 04-FEB-06:00 |
Boiler:Heating:NaturalGas | 3.73 | 0.00 | 01-JAN-00:10 | 19263.55 | 04-FEB-06:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 10659.68 | 0.00 | 04-FEB-04:00 | 691002.03 | 25-SEP-22:00 |
PlantLoopCoolingDemand:HVAC | 10659.68 | 0.00 | 04-FEB-04:00 | 691002.03 | 25-SEP-22:00 |
CoolingCoils:PlantLoopCoolingDemand | 10659.68 | 0.00 | 04-FEB-04:00 | 691002.03 | 25-SEP-22:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 09-JAN-21:50 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 09-JAN-21:50 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 09-JAN-21:50 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 09-JAN-21:50 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 09-JAN-21:50 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 09-JAN-21:50 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 23-FEB-08:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 23-FEB-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 46929.05 | 152700.48 | 20-MAR-10:20 | 2919558.89 | 27-JUL-18:20 |
EnergyTransfer:Building | 6260.80 | 112092.32 | 05-FEB-04:00 | 328457.16 | 27-JUL-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 736.66 | 11557.09 | 04-FEB-04:00 | 34559.52 | 23-JUL-10:50 |
Refrigeration:EnergyTransfer | 189.24 | 4129.71 | 16-MAR-22:10 | 10381.03 | 22-DEC-07:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 94.62 | 2064.86 | 16-MAR-22:10 | 5190.52 | 22-DEC-07:30 |
General:Refrigeration:EnergyTransfer | 94.62 | 2064.86 | 16-MAR-22:10 | 5190.52 | 22-DEC-07:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 94.62 | 2064.86 | 16-MAR-22:10 | 5190.52 | 22-DEC-07:30 |
EnergyTransfer:Plant | 25609.37 | 17575.16 | 04-FEB-04:00 | 1601557.07 | 25-SEP-22:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.76 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 72.86 | 1879.28 | 25-JAN-04:10 | 2564.21 | 28-AUG-13:10 |
EnergyTransfer:HVAC | 15058.89 | 4001.57 | 20-MAR-10:20 | 1051879.27 | 27-JUL-18:20 |
CoolingCoils:EnergyTransfer | 11860.39 | 0.00 | 04-FEB-04:00 | 796244.46 | 25-SEP-20:50 |
EnergyTransfer:Zone:BASEMENT | 426.03 | 10771.54 | 24-APR-13:50 | 18807.73 | 18-OCT-21:00 |
Heating:EnergyTransfer | 0.39 | 0.00 | 01-JAN-00:10 | 6347.46 | 04-FEB-07:00 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 0.39 | 0.00 | 01-JAN-00:10 | 6347.46 | 04-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 6165.78 | 105139.03 | 04-FEB-06:00 | 324846.98 | 27-JUL-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 426.03 | 10771.54 | 24-APR-13:50 | 18807.73 | 18-OCT-21:00 |
General:Cooling:EnergyTransfer | 6165.78 | 105139.03 | 04-FEB-06:00 | 324846.98 | 27-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 426.03 | 10771.54 | 24-APR-13:50 | 18807.73 | 18-OCT-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 52.93 | 380.66 | 04-FEB-07:10 | 3636.76 | 09-DEC-12:30 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 52.93 | 380.66 | 04-FEB-07:10 | 3636.76 | 09-DEC-12:30 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 52.93 | 380.66 | 04-FEB-07:10 | 3636.76 | 09-DEC-12:30 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 43.09 | 981.25 | 20-MAR-12:20 | 2121.35 | 17-AUG-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 43.09 | 981.25 | 20-MAR-12:20 | 2121.35 | 17-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 43.09 | 981.25 | 20-MAR-12:20 | 2121.35 | 17-AUG-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 37.38 | 860.15 | 05-FEB-15:10 | 1957.38 | 28-JUL-21:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 37.38 | 860.15 | 05-FEB-15:10 | 1957.38 | 28-JUL-21:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 37.38 | 860.15 | 05-FEB-15:10 | 1957.38 | 28-JUL-21:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 19.56 | 456.11 | 05-FEB-06:00 | 861.13 | 28-JUL-21:00 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 19.56 | 456.11 | 05-FEB-06:00 | 861.13 | 28-JUL-21:00 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 19.56 | 456.11 | 05-FEB-06:00 | 861.13 | 28-JUL-21:00 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 627.49 | 10426.84 | 04-FEB-06:00 | 38778.76 | 28-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 627.49 | 10426.84 | 04-FEB-06:00 | 38778.76 | 28-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 627.49 | 10426.84 | 04-FEB-06:00 | 38778.76 | 28-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 262.15 | 4998.55 | 16-MAR-08:40 | 12604.28 | 09-DEC-12:30 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 262.15 | 4998.55 | 16-MAR-08:40 | 12604.28 | 09-DEC-12:30 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 262.15 | 4998.55 | 16-MAR-08:40 | 12604.28 | 09-DEC-12:30 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 909.29 | 20477.73 | 20-MAR-10:10 | 42543.92 | 22-SEP-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 909.29 | 20477.73 | 20-MAR-10:10 | 42543.92 | 22-SEP-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 909.29 | 20477.73 | 20-MAR-10:10 | 42543.92 | 22-SEP-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 99.14 | 0.00 | 01-JAN-08:10 | 10163.86 | 30-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.04 | 0.00 | 01-JAN-00:10 | 949.48 | 04-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.04 | 0.00 | 01-JAN-00:10 | 949.48 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 99.10 | 0.00 | 01-JAN-08:10 | 10163.86 | 30-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 99.10 | 0.00 | 01-JAN-08:10 | 10163.86 | 30-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 85.10 | 0.00 | 01-JAN-08:10 | 9764.66 | 28-JUL-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 0.07 | 0.00 | 01-JAN-00:10 | 1119.41 | 04-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 0.07 | 0.00 | 01-JAN-00:10 | 1119.41 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 85.04 | 0.00 | 01-JAN-08:10 | 9764.66 | 28-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 85.04 | 0.00 | 01-JAN-08:10 | 9764.66 | 28-JUL-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 512.83 | 0.00 | 08-JAN-04:00 | 44844.93 | 03-DEC-14:00 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 512.83 | 0.00 | 08-JAN-04:00 | 44844.93 | 03-DEC-14:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 512.83 | 0.00 | 08-JAN-04:00 | 44844.93 | 03-DEC-14:00 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 701.66 | 0.00 | 01-JAN-08:10 | 67770.70 | 29-JUL-15:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.06 | 0.00 | 01-JAN-00:10 | 4135.39 | 25-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.06 | 0.00 | 01-JAN-00:10 | 4135.39 | 25-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 701.60 | 0.00 | 01-JAN-08:10 | 67770.70 | 29-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 701.60 | 0.00 | 01-JAN-08:10 | 67770.70 | 29-JUL-15:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 100.30 | 0.00 | 01-JAN-18:10 | 8635.01 | 23-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.02 | 0.00 | 01-JAN-00:10 | 1012.05 | 04-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.02 | 0.00 | 01-JAN-00:10 | 1012.05 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 100.27 | 0.00 | 01-JAN-18:10 | 8635.01 | 23-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 100.27 | 0.00 | 01-JAN-18:10 | 8635.01 | 23-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 86.03 | 0.00 | 01-JAN-08:10 | 8891.85 | 04-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 0.07 | 0.00 | 01-JAN-00:10 | 1204.59 | 04-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 0.07 | 0.00 | 01-JAN-00:10 | 1204.59 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 85.96 | 0.00 | 01-JAN-08:10 | 8891.85 | 04-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 85.96 | 0.00 | 01-JAN-08:10 | 8891.85 | 04-JUL-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 208.31 | 4912.62 | 04-FEB-07:40 | 8856.44 | 22-SEP-21:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 208.31 | 4912.62 | 04-FEB-07:40 | 8856.44 | 22-SEP-21:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 208.31 | 4912.62 | 04-FEB-07:40 | 8856.44 | 22-SEP-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 24.67 | 0.00 | 01-JAN-08:10 | 2710.92 | 30-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.04 | 0.00 | 01-JAN-00:10 | 479.28 | 04-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.04 | 0.00 | 01-JAN-00:10 | 479.28 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 24.63 | 0.00 | 01-JAN-08:10 | 2710.92 | 30-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 24.63 | 0.00 | 01-JAN-08:10 | 2710.92 | 30-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 21.39 | 0.00 | 01-JAN-08:10 | 2671.03 | 29-JUL-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.08 | 0.00 | 01-JAN-00:10 | 534.77 | 04-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.08 | 0.00 | 01-JAN-00:10 | 534.77 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 21.31 | 0.00 | 01-JAN-08:10 | 2671.03 | 29-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 21.31 | 0.00 | 01-JAN-08:10 | 2671.03 | 29-JUL-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 146.22 | 0.00 | 01-JAN-08:10 | 11964.29 | 07-NOV-16:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 1047.89 | 04-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 1047.89 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 146.20 | 0.00 | 01-JAN-08:10 | 11964.29 | 07-NOV-16:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 146.20 | 0.00 | 01-JAN-08:10 | 11964.29 | 07-NOV-16:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 501.71 | 10354.96 | 16-MAR-09:30 | 23309.45 | 28-JUL-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 501.71 | 10354.96 | 16-MAR-09:30 | 23309.45 | 28-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 501.71 | 10354.96 | 16-MAR-09:30 | 23309.45 | 28-JUL-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 535.69 | 11312.93 | 16-MAR-09:30 | 24510.08 | 28-JUL-21:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 535.69 | 11312.93 | 16-MAR-09:30 | 24510.08 | 28-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 535.69 | 11312.93 | 16-MAR-09:30 | 24510.08 | 28-JUL-21:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 642.04 | 9426.84 | 04-FEB-04:00 | 29489.70 | 23-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 642.04 | 9426.84 | 04-FEB-04:00 | 29489.70 | 23-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 123.17 | 1611.16 | 04-FEB-07:10 | 6669.71 | 28-JUL-15:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 123.17 | 1611.16 | 04-FEB-07:10 | 6669.71 | 28-JUL-15:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 123.17 | 1611.16 | 04-FEB-07:10 | 6669.71 | 28-JUL-15:40 |
PlantLoopHeatingDemand:Facility | 2105.12 | 6825.77 | 20-JUL-01:20 | 201400.66 | 30-NOV-21:30 |
PlantLoopHeatingDemand:Plant | 2102.67 | 6825.77 | 20-JUL-01:20 | 201400.66 | 30-NOV-21:30 |
WaterSystems:PlantLoopHeatingDemand | 2102.67 | 6825.77 | 20-JUL-01:20 | 201400.66 | 30-NOV-21:30 |
General:WaterSystems:PlantLoopHeatingDemand | 553.00 | 6822.15 | 19-JUL-01:20 | 40139.70 | 19-JAN-07:10 |
HeatingCoils:EnergyTransfer | 2.45 | 0.00 | 01-JAN-00:10 | 11880.07 | 04-FEB-06:00 |
PlantLoopHeatingDemand:HVAC | 2.45 | 0.00 | 01-JAN-00:10 | 11880.07 | 04-FEB-06:00 |
HeatingCoils:PlantLoopHeatingDemand | 2.45 | 0.00 | 01-JAN-00:10 | 11880.07 | 04-FEB-06:00 |
HeatRecoveryForHeating:EnergyTransfer | 62.83 | 0.00 | 01-JAN-00:10 | 200342.52 | 04-FEB-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 3133.21 | 0.00 | 01-JAN-00:10 | 279926.56 | 27-JUL-18:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 1549.67 | 0.00 | 01-JAN-00:10 | 171111.43 | 31-OCT-20:30 |
WaterSystems:EnergyTransfer | 553.00 | 6822.15 | 19-JUL-01:20 | 40139.70 | 19-JAN-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 553.00 | 6822.15 | 19-JUL-01:20 | 40139.70 | 19-JAN-07:10 |
Boilers:EnergyTransfer | 2.42 | 0.00 | 01-JAN-00:10 | 11572.65 | 04-FEB-06:00 |
Chillers:EnergyTransfer | 10820.65 | 0.00 | 04-FEB-04:00 | 700869.67 | 25-SEP-22:00 |
HeatRejection:EnergyTransfer | 14138.68 | 0.00 | 04-FEB-04:00 | 875796.76 | 25-SEP-22:00 |
General:HeatRejection:EnergyTransfer | 14138.68 | 0.00 | 04-FEB-04:00 | 875796.76 | 25-SEP-22:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -426.028 | 0.000 | 0.000 | 139.042 | 113.371 | 143.105 | 0.000 | 0.000 | 0.000 | 30.511 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.000 | -52.933 | 0.000 | 0.000 | 14.170 | 6.265 | 10.186 | 19.174 | 0.000 | 0.202 | 5.770 | 0.000 | -2.726 | 0.000 | -0.107 | -0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -43.088 | 0.000 | 0.000 | 16.134 | 7.255 | 11.795 | 0.000 | 0.000 | 0.082 | 7.871 | 0.000 | 0.000 | 0.000 | -0.048 | 0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -37.382 | 0.000 | 0.000 | 3.475 | 8.366 | 12.471 | 0.000 | 0.000 | 0.196 | 12.972 | 0.000 | 0.000 | 0.000 | -0.098 | 0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.000 | -19.562 | 0.000 | 0.000 | 2.691 | 1.866 | 3.598 | 0.000 | 0.000 | 0.116 | 11.346 | 0.000 | 0.000 | 0.000 | -0.055 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -627.493 | 0.000 | 0.000 | 11.402 | 4.900 | 658.131 | 0.000 | 0.000 | 0.335 | 0.000 | 0.000 | 0.000 | 0.000 | -0.138 | -47.138 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -262.152 | 0.000 | 0.000 | 181.199 | 13.100 | 14.341 | 53.639 | 0.000 | 0.451 | 8.343 | 0.000 | -8.628 | 0.000 | -0.293 | -0.000 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -909.300 | 0.000 | 0.000 | 538.229 | 123.187 | 148.998 | 72.096 | 0.000 | 1.321 | 37.386 | 0.000 | -11.072 | 0.000 | -0.845 | -0.003 |
ROOM_1_FLR_3 | 0.110 | -84.624 | 0.000 | -14.549 | 0.000 | 0.000 | 9.626 | 6.171 | 12.292 | 45.538 | 0.000 | 1.056 | 28.987 | 0.000 | -4.079 | 0.000 | -0.528 | 0.000 |
ROOM_2_FLR_3 | 0.199 | -70.049 | 0.000 | -15.117 | 0.000 | 0.000 | 9.491 | 6.170 | 12.291 | 37.851 | 0.000 | 0.785 | 23.755 | 0.000 | -4.501 | 0.000 | -0.874 | -0.000 |
ROOM_3_MULT19_FLR_3 | 0.000 | -494.424 | 0.000 | -18.397 | 0.000 | 0.000 | 0.000 | 73.685 | 228.754 | 202.074 | 0.000 | 0.816 | 73.152 | 0.000 | -62.246 | 0.000 | -3.413 | -0.000 |
ROOM_4_MULT19_FLR_3 | 0.236 | -498.073 | 0.000 | -203.674 | 0.000 | 0.000 | 180.945 | 73.705 | 228.817 | 144.726 | 0.000 | 5.230 | 102.273 | 0.000 | -22.382 | 0.000 | -11.802 | -0.012 |
ROOM_5_FLR_3 | 0.100 | -85.793 | 0.000 | -14.553 | 0.000 | 0.000 | 9.623 | 6.171 | 12.292 | 46.613 | 0.000 | 1.053 | 28.936 | 0.000 | -3.904 | 0.000 | -0.538 | 0.000 |
ROOM_6_FLR_3 | 0.196 | -70.956 | 0.000 | -15.132 | 0.000 | 0.000 | 9.490 | 6.170 | 12.291 | 38.731 | 0.000 | 0.784 | 23.472 | 0.000 | -4.187 | 0.000 | -0.859 | -0.001 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.000 | -208.307 | 0.000 | 0.000 | 109.664 | 56.739 | 0.000 | 42.037 | 0.000 | 0.591 | 6.217 | 0.000 | -6.628 | 0.000 | -0.312 | -0.000 |
ROOM_1_FLR_6 | 0.107 | -21.050 | 0.000 | -3.638 | 0.000 | 0.000 | 2.407 | 1.543 | 3.073 | 11.316 | 0.000 | 0.277 | 7.091 | 0.000 | -0.981 | 0.000 | -0.144 | -0.000 |
ROOM_2_FLR_6 | 0.170 | -17.633 | 0.000 | -3.769 | 0.000 | 0.000 | 2.376 | 1.543 | 3.073 | 9.420 | 0.000 | 0.200 | 5.938 | 0.000 | -1.083 | 0.000 | -0.234 | -0.000 |
ROOM_3_MULT9_FLR_6 | 0.069 | -122.840 | 0.000 | -23.410 | 0.000 | 0.000 | 21.650 | 8.728 | 27.097 | 55.083 | 0.000 | 1.653 | 37.570 | 0.000 | -4.463 | 0.000 | -1.137 | -0.000 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -501.716 | 0.000 | 0.000 | 315.403 | 28.541 | 175.857 | 13.134 | 0.000 | 0.266 | 0.000 | 0.000 | -4.559 | 0.000 | -0.201 | -26.726 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -535.694 | 0.000 | 0.000 | 314.871 | 28.541 | 175.857 | 12.773 | 0.000 | 0.262 | 8.432 | 0.000 | -4.837 | 0.000 | -0.204 | -0.001 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -642.032 | 0.000 | 0.000 | 28.312 | 13.339 | 540.650 | 21.309 | 0.000 | 0.232 | 42.093 | 0.000 | -3.727 | 0.000 | -0.177 | 0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.000 | -123.170 | 0.000 | 0.000 | 29.233 | 15.012 | 0.000 | 19.085 | 0.000 | 0.250 | 62.724 | 0.000 | -3.009 | 0.000 | -0.126 | 0.000 |
Total Facility | 1.186 | -1465.443 | 0.000 | -4701.097 | 0.000 | 0.000 | 1949.434 | 604.366 | 2434.967 | 844.599 | 0.000 | 16.158 | 564.837 | 0.000 | -153.013 | 0.000 | -22.132 | -73.883 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 18-OCT-21:00 | 0.00 | 0.00 | 0.00 | -18808.59 | 0.00 | 0.00 | 5924.41 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4482.48 |
RETAIL_1_FLR_1 | 09-DEC-12:30 | 0.00 | 0.00 | 0.00 | -3636.14 | 0.00 | 0.00 | 225.91 | 142.31 | 252.59 | 4258.32 | 0.00 | 9.32 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1252.31 |
RETAIL_2_FLR_1 | 17-AUG-21:00 | 0.00 | 0.00 | 0.00 | -2121.45 | 0.00 | 0.00 | 697.61 | 527.34 | 752.15 | 0.00 | 0.00 | 4.28 | 140.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 28-JUL-21:00 | 0.00 | 0.00 | 0.00 | -1957.44 | 0.00 | 0.00 | 147.52 | 608.16 | 795.27 | 0.00 | 0.00 | 14.17 | 392.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 28-JUL-21:00 | 0.00 | 0.00 | 0.00 | -861.17 | 0.00 | 0.00 | 113.48 | 135.66 | 229.41 | 0.00 | 0.00 | 8.18 | 374.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 28-JUL-20:00 | 0.00 | 0.00 | 0.00 | -38779.17 | 0.00 | 0.00 | 408.87 | 400.68 | 44299.38 | 0.00 | 0.00 | 15.46 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6345.23 |
CAFE_FLR_1 | 09-DEC-12:30 | 0.00 | 0.00 | 0.00 | -12602.18 | 0.00 | 0.00 | 2968.86 | 96.16 | 355.63 | 11946.53 | 0.00 | 20.62 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2785.62 |
LOBBY_FLR_1 | 18-SEP-21:10 | 0.00 | 0.00 | 0.00 | -42551.36 | 0.00 | 0.00 | 26439.84 | 7096.92 | 7389.94 | 552.76 | 0.00 | 78.93 | 992.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 10-OCT-15:02 | 0.00 | -10150.82 | 0.00 | -751.22 | 0.00 | 0.00 | 235.28 | 132.99 | 273.93 | 5179.60 | 0.00 | 31.20 | 5049.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 13-JUN-18:11 | 0.00 | -10798.18 | 0.00 | -895.54 | 0.00 | 0.00 | 296.59 | 422.67 | 516.20 | 2804.63 | 0.00 | 5.02 | 7648.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 03-DEC-14:00 | 0.00 | -44843.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1871.60 | 5686.12 | 45546.22 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -83.60 | -8177.01 |
ROOM_4_MULT19_FLR_3 | 27-JUL-18:02 | 0.00 | -66907.08 | 0.00 | -10385.07 | 0.00 | 0.00 | 6374.46 | 5048.96 | 9610.21 | 9888.14 | 0.00 | 312.35 | 46058.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 30-AUG-08:62 | 0.00 | -9183.94 | 0.00 | -757.09 | 0.00 | 0.00 | 87.14 | 208.98 | 453.05 | 6345.94 | 0.00 | 41.42 | 2804.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 21-APR-08:31 | 0.00 | -10093.69 | 0.00 | -951.55 | 0.00 | 0.00 | 72.50 | 208.96 | 452.99 | 5973.54 | 0.00 | 0.00 | 4338.37 | 0.00 | -0.00 | 0.00 | -1.12 | 0.00 |
CORRIDOR_FLR_3 | 22-SEP-21:10 | 0.00 | 0.00 | 0.00 | -8857.05 | 0.00 | 0.00 | 5246.14 | 3093.34 | 0.00 | 581.35 | 0.00 | 34.80 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -98.58 |
ROOM_1_FLR_6 | 07-NOV-16:02 | 0.00 | -2677.94 | 0.00 | -190.92 | 0.00 | 0.00 | 58.82 | 33.25 | 68.48 | 1579.10 | 0.00 | 8.78 | 1120.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 13-JUN-18:11 | 0.00 | -2833.13 | 0.00 | -224.20 | 0.00 | 0.00 | 73.89 | 105.67 | 129.05 | 692.70 | 0.00 | 1.13 | 2054.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10-SEP-15:02 | 0.00 | -11283.99 | 0.00 | -1239.11 | 0.00 | 0.00 | 294.09 | 221.70 | 673.54 | 4531.59 | 0.00 | 61.56 | 6740.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 28-JUL-21:10 | 0.00 | 0.00 | 0.00 | -23314.13 | 0.00 | 0.00 | 15644.24 | 1842.08 | 6747.90 | 185.91 | 0.00 | 21.29 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1127.30 |
DINING_FLR_6 | 28-JUL-21:10 | 0.00 | 0.00 | 0.00 | -24515.20 | 0.00 | 0.00 | 15644.17 | 1842.08 | 6747.90 | 170.68 | 0.00 | 21.29 | 89.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 23-JUL-10:50 | 0.00 | 0.00 | 0.00 | -29491.09 | 0.00 | 0.00 | 461.42 | 363.61 | 23951.61 | 2648.50 | 0.00 | 31.13 | 2034.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 28-JUL-15:40 | 0.00 | 0.00 | 0.00 | -6669.14 | 0.00 | 0.00 | 771.15 | 341.02 | 0.00 | 1460.14 | 0.00 | 38.20 | 4058.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 27-JUL-18:02 | 0.00 | -146015.20 | 0.00 | -199816.10 | 0.00 | 0.00 | 74700.86 | 41298.45 | 121562.63 | 35008.76 | 0.00 | 1299.47 | 71961.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 20-APR-08:05 | 3453.98 | 630.78 | 0.00 | -630.78 | 0.00 | 0.00 | 87.14 | 208.98 | 453.05 | 1081.82 | 0.00 | 16.02 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5300.99 |
ROOM_2_FLR_3 | 28-DEC-16:04 | 4028.46 | 590.72 | 0.00 | -590.72 | 0.00 | 0.00 | 241.24 | 132.97 | 273.90 | 504.87 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -178.98 | -5002.47 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 25-JAN-16:04 | 28945.38 | 6875.14 | 0.00 | -6875.14 | 0.00 | 0.00 | 4790.21 | 1588.43 | 5099.29 | 46.58 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4536.69 | -35933.20 |
ROOM_5_FLR_3 | 16-MAR-18:05 | 3233.78 | 523.27 | 0.00 | -523.27 | 0.00 | 0.00 | 341.39 | 422.72 | 516.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -593.66 | 0.00 | -223.79 | -3696.71 |
ROOM_6_FLR_3 | 03-FEB-16:04 | 4108.13 | 458.21 | 0.00 | -458.21 | 0.00 | 0.00 | 246.75 | 132.97 | 273.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -162.35 | 0.00 | -742.43 | -3856.97 |
CORRIDOR_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 16-MAR-08:62 | 1494.97 | 102.05 | 0.00 | -102.05 | 0.00 | 0.00 | 25.55 | 52.25 | 113.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -143.97 | 0.00 | -22.26 | -1519.80 |
ROOM_2_FLR_6 | 16-MAR-08:62 | 1507.47 | 98.15 | 0.00 | -98.15 | 0.00 | 0.00 | 25.78 | 52.24 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -250.65 | 0.00 | -21.88 | -1426.21 |
ROOM_3_MULT9_FLR_6 | 21-MAR-08:03 | 3578.91 | 683.57 | 0.00 | -683.57 | 0.00 | 0.00 | 215.46 | 295.59 | 998.70 | 388.07 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -71.43 | -5405.30 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 25-JAN-16:04 | -116973.39 | 127450.12 | 0.00 | -127450.12 | 0.00 | 0.00 | 55738.64 | 12800.20 | 76844.13 | 39097.45 | 0.00 | 0.00 | 0.00 | 0.00 | -317.23 | 0.00 | -7290.17 | -59899.63 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 20.2143 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 20.1014 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6636 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6636 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2826 | 2.2826 | 1.3171 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2648 | 0.2648 | 0.1528 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2202 | 0.2202 | 0.1270 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2002 | 0.2002 | 0.1155 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1072 | 0.1072 | 0.0619 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2511 | 3.2511 | 1.8759 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2326 | 1.2326 | 0.7112 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.3651 | 4.3651 | 2.5187 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1217 | 1.1217 | 0.6472 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1421 | 2.1421 | 1.2360 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2472 | 2.2472 | 1.2966 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1213 | 2.1213 | 1.2240 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6582 | 0.6582 | 0.3798 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 20.2143 | 20.1014 | 20.2143 | 11.6636 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3171 | 1.3171 | 1.3171 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1528 | 0.1528 | 0.1528 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1270 | 0.1270 | 0.1270 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1155 | 0.1155 | 0.1155 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0619 | 0.0619 | 0.0619 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8759 | 1.8759 | 1.8759 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7112 | 0.7112 | 0.7112 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5187 | 2.5187 | 2.5187 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6472 | 0.6472 | 0.6472 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2360 | 1.2360 | 1.2360 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2966 | 1.2966 | 1.2966 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2240 | 1.2240 | 1.2240 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3798 | 0.3798 | 0.3798 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6636 | 11.6636 | 11.6636 | 11.6636 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 145.00 |
Number of hours not met | 145.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 3.73 | 19263.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3318.04 | 203625.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 604.37 | 50471.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 174.60 | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 952.41 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 22.46 | 1283.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 604.49 | 38839.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 188.33 | 7643.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 295.32 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4738.73 | 622.93 | 46939.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Other | 0.00 | 38840.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.84 | 1308.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 21.48 | 717.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1772.54 | 8051.92 |
Natural Gas | 1788.84 | 2415.49 |
Additional | 0.00 | 0.00 |
Total | 3561.38 | 10467.41 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 53.27 |
Space Heating | 0.00 |
Space Cooling | 292.46 |
Fans (All) | 53.28 |
Service Water Heating | 39.91 |
Receptacle Equipment | 152.32 |
Miscellaneous (All) | 709.71 |
Subtotal | 709.71 |
Natural Gas [MJ/m2] | |
Space Heating | 0.33 |
Service Water Heating | 54.91 |
Miscellaneous (All) | 212.91 |
Subtotal | 212.91 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.77 |
Space Heating | 0.04 |
Space Cooling | 31.70 |
Fans (All) | 5.78 |
Service Water Heating | 10.28 |
Receptacle Equipment | 33.60 |
Miscellaneous | 12.84 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2398. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 2482. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7134.83 | 1625.17 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7134.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1625.17 | 0.00 | 0.00 | 0.00 |
Average | 8686.05 | 73.95 | 0.00 | 0.00 | 0.00 |
Sum | 191093.00 | 1627.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4153.83 | 0.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.17 | 0.00 | 0.00 | 0.00 |
Average | 288887.04 | 0.01 | 0.00 | 0.00 | 0.00 |
Sum | 6355514.83 | 0.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8417.50 | 342.50 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 5604.00 | 3156.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 6018.17 | 2741.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8756.33 | 3.67 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8560.50 | 199.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 5907.00 | 2853.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8599.17 | 160.83 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8757.33 | 2.67 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8495.17 | 264.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8152.83 | 607.17 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8747.33 | 12.67 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8487.33 | 272.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8743.33 | 16.67 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 5798.50 | 2961.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 6017.33 | 2742.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8140.00 | 620.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 5604.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 3156.00 | 0.00 | 0.00 | 0.00 |
Average | 7989.17 | 770.83 | 0.00 | 0.00 | 0.00 |
Sum | 175761.83 | 16958.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 55453.50 | 3702.50 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 341094.00 | 369323.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1165044.67 | 950384.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4085.67 | 68.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4092.17 | 61.83 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4091.50 | 62.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 89928.33 | 10429.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4049.83 | 104.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 646305.67 | 599409.33 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 684499.33 | 561215.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 102861.33 | 5407.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1165044.67 | 950384.33 | 0.00 | 0.00 | 0.00 |
Average | 175243.00 | 113644.05 | 0.00 | 0.00 | 0.00 |
Sum | 3855346.00 | 2500169.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.364989E+11 | 16771.27 | 13-JAN-22:00 | 24.40 | 20.99 | 0.799741E+10 | 4837.20 | 25-JAN-23:10 | 12.20 | 8.81 |
February | 0.316704E+11 | 15794.61 | 11-FEB-11:35 | 27.60 | 23.74 | 0.702501E+10 | 4837.08 | 01-FEB-23:10 | 27.60 | 23.74 |
March | 0.332086E+11 | 15229.44 | 04-MAR-11:35 | 27.03 | 22.82 | 0.746347E+10 | 4714.40 | 01-MAR-23:10 | 27.03 | 22.82 |
April | 0.318628E+11 | 15381.30 | 16-APR-10:33 | 28.67 | 21.62 | 0.706780E+10 | 4510.08 | 06-APR-22:10 | 28.67 | 21.62 |
May | 0.339436E+11 | 15558.10 | 14-MAY-10:33 | 29.23 | 23.78 | 0.742429E+10 | 4608.86 | 26-MAY-22:10 | 25.28 | 23.53 |
June | 0.335672E+11 | 15925.56 | 11-JUN-10:33 | 30.93 | 23.60 | 0.726896E+10 | 4624.78 | 21-JUN-22:10 | 25.00 | 23.59 |
July | 0.362758E+11 | 16552.45 | 16-JUL-10:33 | 30.20 | 24.06 | 0.770633E+10 | 4784.59 | 14-JUL-22:10 | 30.20 | 24.06 |
August | 0.375538E+11 | 17007.23 | 20-AUG-10:33 | 31.13 | 25.97 | 0.799668E+10 | 4837.03 | 30-AUG-21:30 | 27.25 | 23.62 |
September | 0.374610E+11 | 18312.18 | 22-SEP-21:00 | 28.30 | 25.04 | 0.782010E+10 | 4837.09 | 05-SEP-22:10 | 28.30 | 25.04 |
October | 0.389688E+11 | 18807.73 | 18-OCT-21:00 | 25.60 | 19.05 | 0.811185E+10 | 4837.08 | 27-OCT-22:10 | 23.80 | 21.85 |
November | 0.373142E+11 | 18761.68 | 22-NOV-22:00 | 26.70 | 23.11 | 0.785141E+10 | 4837.10 | 15-NOV-00:10 | 26.70 | 23.11 |
December | 0.377013E+11 | 18510.36 | 01-DEC-22:00 | 21.70 | 19.15 | 0.808611E+10 | 4837.12 | 20-DEC-22:19 | 10.40 | 8.14 |
Annual Sum or Average | 0.426027E+12 | 0.918194E+11 | ||||||||
Minimum of Months | 0.316704E+11 | 15229.44 | 21.70 | 19.05 | 0.702501E+10 | 4510.08 | 10.40 | 8.14 | ||
Maximum of Months | 0.389688E+11 | 18807.73 | 31.13 | 25.97 | 0.811185E+10 | 4837.20 | 30.20 | 25.04 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.412065E+10 | 3296.19 | 02-JAN-14:30 | 28.90 | 24.11 | 0.744123E+09 | 491.84 | 02-JAN-23:10 | 20.50 | 19.70 |
February | 0.377231E+10 | 3226.23 | 11-FEB-14:10 | 29.22 | 24.12 | 0.684036E+09 | 491.84 | 09-FEB-23:10 | 29.22 | 24.12 |
March | 0.407159E+10 | 2533.30 | 04-MAR-11:35 | 27.03 | 22.82 | 0.766817E+09 | 491.84 | 31-MAR-22:10 | 23.05 | 18.37 |
April | 0.411934E+10 | 2353.65 | 13-APR-13:20 | 29.23 | 23.89 | 0.757718E+09 | 491.84 | 10-APR-22:10 | 29.23 | 23.89 |
May | 0.434506E+10 | 2177.21 | 22-MAY-18:05 | 30.40 | 23.74 | 0.799909E+09 | 491.82 | 04-MAY-21:30 | 30.40 | 23.74 |
June | 0.437387E+10 | 2324.95 | 29-JUN-18:03 | 30.00 | 24.76 | 0.788933E+09 | 491.83 | 09-JUN-23:19 | 30.00 | 24.76 |
July | 0.473825E+10 | 2539.98 | 29-JUL-17:02 | 34.22 | 24.14 | 0.819523E+09 | 491.83 | 27-JUL-23:19 | 34.22 | 24.14 |
August | 0.467725E+10 | 2551.46 | 20-AUG-12:00 | 32.20 | 26.10 | 0.817143E+09 | 491.83 | 02-AUG-23:19 | 32.20 | 26.10 |
September | 0.486165E+10 | 3253.83 | 30-SEP-13:10 | 30.68 | 24.82 | 0.794888E+09 | 491.84 | 25-SEP-22:10 | 30.68 | 24.82 |
October | 0.505476E+10 | 3434.03 | 25-OCT-12:30 | 30.00 | 22.10 | 0.815048E+09 | 491.83 | 18-OCT-23:19 | 30.00 | 22.10 |
November | 0.451385E+10 | 3501.61 | 07-NOV-13:20 | 27.97 | 21.09 | 0.762217E+09 | 491.84 | 21-NOV-22:40 | 24.40 | 22.66 |
December | 0.428419E+10 | 3636.76 | 09-DEC-12:30 | 27.20 | 22.50 | 0.754304E+09 | 491.84 | 04-DEC-23:10 | 27.20 | 22.50 |
Annual Sum or Average | 0.529328E+11 | 0.930466E+10 | ||||||||
Minimum of Months | 0.377231E+10 | 2177.21 | 27.03 | 21.09 | 0.684036E+09 | 491.82 | 20.50 | 18.37 | ||
Maximum of Months | 0.505476E+10 | 3636.76 | 34.22 | 26.10 | 0.819523E+09 | 491.84 | 34.22 | 26.10 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.333444E+10 | 1776.24 | 03-JAN-22:00 | 22.20 | 20.64 | 0.910571E+09 | 569.55 | 02-JAN-23:10 | 22.20 | 20.64 |
February | 0.307785E+10 | 1764.50 | 22-FEB-22:00 | 19.40 | 14.76 | 0.829415E+09 | 569.55 | 22-FEB-23:10 | 18.30 | 15.01 |
March | 0.345689E+10 | 1885.13 | 28-MAR-20:52 | 24.40 | 21.00 | 0.927056E+09 | 569.55 | 29-MAR-22:10 | 23.80 | 20.49 |
April | 0.350307E+10 | 2021.60 | 13-APR-21:00 | 25.60 | 22.81 | 0.907076E+09 | 569.56 | 20-APR-22:10 | 22.20 | 16.88 |
May | 0.372810E+10 | 2025.45 | 17-MAY-21:00 | 26.10 | 22.56 | 0.945231E+09 | 569.55 | 24-MAY-21:10 | 24.40 | 22.88 |
June | 0.369803E+10 | 2083.48 | 09-JUN-21:00 | 29.40 | 24.96 | 0.922083E+09 | 569.55 | 21-JUN-21:10 | 24.50 | 22.87 |
July | 0.393879E+10 | 2121.23 | 28-JUL-21:00 | 29.40 | 24.13 | 0.953979E+09 | 569.55 | 14-JUL-22:10 | 29.40 | 24.13 |
August | 0.385468E+10 | 2121.35 | 17-AUG-21:00 | 27.80 | 24.58 | 0.954092E+09 | 569.54 | 02-AUG-23:19 | 27.80 | 24.58 |
September | 0.378456E+10 | 2101.06 | 01-SEP-21:00 | 28.90 | 24.03 | 0.924486E+09 | 569.55 | 05-SEP-22:10 | 23.90 | 22.74 |
October | 0.380716E+10 | 2075.50 | 06-OCT-21:00 | 26.70 | 23.40 | 0.951471E+09 | 569.55 | 27-OCT-22:10 | 23.80 | 21.85 |
November | 0.348717E+10 | 1939.73 | 07-NOV-22:00 | 24.40 | 22.09 | 0.905897E+09 | 569.55 | 21-NOV-22:40 | 24.40 | 22.66 |
December | 0.341721E+10 | 1896.08 | 08-DEC-22:00 | 23.90 | 22.40 | 0.917878E+09 | 569.55 | 08-DEC-23:10 | 24.50 | 22.98 |
Annual Sum or Average | 0.430879E+11 | 0.110492E+11 | ||||||||
Minimum of Months | 0.307785E+10 | 1764.50 | 19.40 | 14.76 | 0.829415E+09 | 569.54 | 18.30 | 15.01 | ||
Maximum of Months | 0.393879E+10 | 2121.35 | 29.40 | 24.96 | 0.954092E+09 | 569.56 | 29.40 | 24.58 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.279025E+10 | 1358.71 | 01-JAN-11:33 | 26.30 | 21.34 | 0.180282E+09 | 116.28 | 03-JAN-22:19 | 22.03 | 20.47 |
February | 0.258249E+10 | 1375.83 | 11-FEB-11:35 | 27.60 | 23.74 | 0.165249E+09 | 117.43 | 17-FEB-22:19 | 23.90 | 20.81 |
March | 0.289621E+10 | 1378.02 | 05-MAR-11:33 | 27.77 | 23.38 | 0.184748E+09 | 117.52 | 30-MAR-22:10 | 23.80 | 20.03 |
April | 0.298007E+10 | 1472.70 | 16-APR-10:33 | 28.67 | 21.62 | 0.184510E+09 | 120.45 | 14-APR-21:30 | 28.67 | 21.62 |
May | 0.327380E+10 | 1666.34 | 23-MAY-21:00 | 26.10 | 23.27 | 0.197530E+09 | 120.45 | 18-MAY-21:30 | 26.10 | 23.27 |
June | 0.336041E+10 | 1906.86 | 29-JUN-20:00 | 28.90 | 25.14 | 0.195613E+09 | 120.45 | 12-JUN-21:30 | 28.90 | 25.14 |
July | 0.359108E+10 | 1957.38 | 28-JUL-21:00 | 29.40 | 24.13 | 0.202670E+09 | 120.45 | 24-JUL-21:30 | 29.40 | 24.13 |
August | 0.341524E+10 | 1892.90 | 21-AUG-20:00 | 28.30 | 24.58 | 0.200975E+09 | 120.45 | 23-AUG-21:30 | 26.70 | 22.51 |
September | 0.335256E+10 | 1891.77 | 22-SEP-20:00 | 28.30 | 25.04 | 0.195116E+09 | 120.45 | 14-SEP-21:30 | 28.30 | 25.04 |
October | 0.327388E+10 | 1590.88 | 03-OCT-21:00 | 27.80 | 25.31 | 0.197911E+09 | 120.45 | 25-OCT-21:30 | 26.40 | 21.40 |
November | 0.298422E+10 | 1431.50 | 23-NOV-11:33 | 27.03 | 23.96 | 0.185436E+09 | 120.45 | 10-NOV-22:30 | 27.03 | 23.96 |
December | 0.288155E+10 | 1452.38 | 09-DEC-12:30 | 27.20 | 22.50 | 0.183830E+09 | 119.58 | 01-DEC-22:19 | 27.20 | 22.50 |
Annual Sum or Average | 0.373818E+11 | 0.227387E+10 | ||||||||
Minimum of Months | 0.258249E+10 | 1358.71 | 26.10 | 21.34 | 0.165249E+09 | 116.28 | 22.03 | 20.03 | ||
Maximum of Months | 0.359108E+10 | 1957.38 | 29.40 | 25.31 | 0.202670E+09 | 120.45 | 29.40 | 25.14 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147298E+10 | 728.99 | 01-JAN-11:33 | 26.30 | 21.34 | 0.136961E+09 | 87.02 | 03-JAN-23:10 | 21.52 | 20.04 |
February | 0.136349E+10 | 739.17 | 11-FEB-11:35 | 27.60 | 23.74 | 0.125509E+09 | 87.91 | 17-FEB-23:10 | 23.90 | 20.81 |
March | 0.152869E+10 | 738.84 | 05-MAR-11:33 | 27.77 | 23.38 | 0.140313E+09 | 87.95 | 30-MAR-22:10 | 23.80 | 20.03 |
April | 0.157361E+10 | 785.39 | 16-APR-10:33 | 28.67 | 21.62 | 0.140082E+09 | 90.45 | 14-APR-22:10 | 28.67 | 21.62 |
May | 0.171804E+10 | 802.60 | 31-MAY-10:35 | 32.23 | 24.19 | 0.150144E+09 | 92.46 | 23-MAY-21:49 | 32.23 | 24.19 |
June | 0.173580E+10 | 831.01 | 11-JUN-10:33 | 30.93 | 23.60 | 0.149341E+09 | 92.66 | 28-JUN-21:19 | 28.90 | 24.83 |
July | 0.183907E+10 | 861.13 | 28-JUL-21:00 | 29.40 | 24.13 | 0.155163E+09 | 92.66 | 06-JUL-21:30 | 29.40 | 24.13 |
August | 0.177512E+10 | 833.35 | 20-AUG-10:33 | 31.13 | 25.97 | 0.153447E+09 | 92.66 | 16-AUG-21:30 | 31.13 | 25.97 |
September | 0.173495E+10 | 834.04 | 24-SEP-10:33 | 30.53 | 25.04 | 0.148987E+09 | 92.66 | 11-SEP-21:30 | 30.53 | 25.04 |
October | 0.172481E+10 | 809.19 | 07-OCT-10:35 | 31.13 | 24.14 | 0.150512E+09 | 92.19 | 03-OCT-22:10 | 31.13 | 24.14 |
November | 0.157556E+10 | 764.63 | 23-NOV-11:33 | 27.03 | 23.96 | 0.140790E+09 | 90.69 | 03-NOV-22:10 | 27.03 | 23.96 |
December | 0.152034E+10 | 781.05 | 09-DEC-12:30 | 27.20 | 22.50 | 0.139568E+09 | 89.16 | 08-DEC-23:10 | 27.20 | 22.50 |
Annual Sum or Average | 0.195624E+11 | 0.173082E+10 | ||||||||
Minimum of Months | 0.136349E+10 | 728.99 | 26.30 | 21.34 | 0.125509E+09 | 87.02 | 21.52 | 20.03 | ||
Maximum of Months | 0.183907E+10 | 861.13 | 32.23 | 25.97 | 0.155163E+09 | 92.66 | 32.23 | 25.97 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.518619E+11 | 37890.25 | 03-JAN-21:00 | 22.80 | 20.45 | 0.575869E+09 | 381.75 | 30-JAN-22:10 | 15.00 | 13.89 |
February | 0.471562E+11 | 37890.62 | 17-FEB-21:00 | 23.90 | 20.81 | 0.520628E+09 | 381.75 | 24-FEB-22:10 | 16.02 | 11.81 |
March | 0.526412E+11 | 38140.49 | 27-MAR-20:00 | 24.40 | 20.99 | 0.578409E+09 | 381.73 | 21-MAR-21:10 | 24.40 | 20.99 |
April | 0.515085E+11 | 38439.63 | 14-APR-20:00 | 26.10 | 23.27 | 0.559015E+09 | 381.69 | 11-APR-21:10 | 26.10 | 23.27 |
May | 0.538420E+11 | 38540.41 | 31-MAY-20:00 | 27.80 | 24.12 | 0.579012E+09 | 381.69 | 19-MAY-21:10 | 27.80 | 24.12 |
June | 0.526244E+11 | 38666.66 | 09-JUN-20:00 | 29.40 | 24.96 | 0.561781E+09 | 381.68 | 13-JUN-21:10 | 26.10 | 22.31 |
July | 0.544587E+11 | 38778.76 | 28-JUL-20:00 | 28.30 | 23.96 | 0.579051E+09 | 381.69 | 14-JUL-21:10 | 28.30 | 23.96 |
August | 0.540977E+11 | 38635.35 | 31-AUG-20:00 | 27.80 | 24.58 | 0.579793E+09 | 381.73 | 11-AUG-21:10 | 27.80 | 24.58 |
September | 0.524575E+11 | 38586.88 | 08-SEP-20:00 | 30.60 | 24.86 | 0.560587E+09 | 381.74 | 12-SEP-21:10 | 26.60 | 23.14 |
October | 0.536571E+11 | 38464.01 | 06-OCT-20:00 | 26.70 | 23.40 | 0.578182E+09 | 381.74 | 20-OCT-21:10 | 25.92 | 21.15 |
November | 0.512531E+11 | 38165.14 | 03-NOV-20:00 | 26.10 | 24.52 | 0.558835E+09 | 381.74 | 03-NOV-21:10 | 26.70 | 24.27 |
December | 0.519270E+11 | 37993.47 | 08-DEC-21:00 | 24.40 | 22.09 | 0.575493E+09 | 381.74 | 08-DEC-22:10 | 23.98 | 22.48 |
Annual Sum or Average | 0.627485E+12 | 0.680666E+10 | ||||||||
Minimum of Months | 0.471562E+11 | 37890.25 | 22.80 | 20.45 | 0.520628E+09 | 381.68 | 15.00 | 11.81 | ||
Maximum of Months | 0.544587E+11 | 38778.76 | 30.60 | 24.96 | 0.579793E+09 | 381.75 | 28.30 | 24.58 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.211008E+11 | 12313.55 | 01-JAN-10:30 | 25.85 | 21.37 | 0.107086E+11 | 6462.62 | 02-JAN-23:10 | 20.50 | 19.70 |
February | 0.191931E+11 | 11543.96 | 11-FEB-14:00 | 29.40 | 24.15 | 0.971137E+10 | 6462.68 | 16-FEB-23:10 | 23.22 | 20.64 |
March | 0.208784E+11 | 10733.30 | 27-MAR-21:10 | 24.90 | 21.81 | 0.107699E+11 | 6462.69 | 28-MAR-21:10 | 24.32 | 20.85 |
April | 0.206513E+11 | 10911.47 | 14-APR-21:10 | 25.50 | 22.67 | 0.104097E+11 | 6462.76 | 20-APR-22:10 | 22.20 | 16.88 |
May | 0.218517E+11 | 11091.75 | 22-MAY-21:10 | 27.70 | 22.63 | 0.107758E+11 | 6462.68 | 24-MAY-21:10 | 24.40 | 22.88 |
June | 0.218612E+11 | 11246.43 | 02-JUN-21:10 | 28.90 | 24.83 | 0.104762E+11 | 6462.73 | 21-JUN-21:10 | 24.50 | 22.87 |
July | 0.229927E+11 | 11503.99 | 28-JUL-21:10 | 29.32 | 24.20 | 0.108348E+11 | 6462.68 | 14-JUL-22:10 | 29.32 | 24.20 |
August | 0.229300E+11 | 11519.60 | 31-AUG-21:10 | 27.77 | 24.60 | 0.108725E+11 | 6462.05 | 02-AUG-23:19 | 27.77 | 24.60 |
September | 0.231212E+11 | 12082.35 | 08-SEP-21:10 | 29.90 | 24.64 | 0.105591E+11 | 6462.67 | 05-SEP-22:10 | 29.90 | 24.64 |
October | 0.240070E+11 | 12296.96 | 25-OCT-15:03 | 29.22 | 22.14 | 0.109185E+11 | 6462.61 | 27-OCT-22:10 | 23.80 | 21.85 |
November | 0.220810E+11 | 11921.27 | 19-NOV-11:00 | 26.70 | 21.75 | 0.104859E+11 | 6462.63 | 21-NOV-22:40 | 24.40 | 22.66 |
December | 0.214802E+11 | 12604.28 | 09-DEC-12:30 | 27.20 | 22.50 | 0.107471E+11 | 6462.62 | 05-DEC-23:10 | 27.20 | 22.50 |
Annual Sum or Average | 0.262149E+12 | 0.127269E+12 | ||||||||
Minimum of Months | 0.191931E+11 | 10733.30 | 24.90 | 21.37 | 0.971137E+10 | 6462.05 | 20.50 | 16.88 | ||
Maximum of Months | 0.240070E+11 | 12604.28 | 29.90 | 24.83 | 0.109185E+11 | 6462.76 | 29.90 | 24.64 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.715197E+11 | 38797.09 | 13-JAN-22:10 | 24.32 | 21.03 | 0.317938E+11 | 19186.04 | 02-JAN-23:10 | 24.32 | 21.03 |
February | 0.655521E+11 | 37947.69 | 17-FEB-22:10 | 23.90 | 20.81 | 0.287861E+11 | 19186.11 | 22-FEB-23:10 | 18.30 | 15.01 |
March | 0.727536E+11 | 37822.73 | 27-MAR-21:10 | 24.90 | 21.81 | 0.319303E+11 | 19186.12 | 28-MAR-21:10 | 24.32 | 20.85 |
April | 0.726788E+11 | 39240.36 | 14-APR-21:10 | 25.50 | 22.67 | 0.309198E+11 | 19186.32 | 20-APR-22:10 | 22.20 | 16.88 |
May | 0.778607E+11 | 39959.13 | 22-MAY-21:10 | 27.70 | 22.63 | 0.320603E+11 | 19186.12 | 24-MAY-21:10 | 24.40 | 22.88 |
June | 0.778538E+11 | 41157.29 | 29-JUN-21:10 | 28.90 | 24.82 | 0.311594E+11 | 19186.18 | 21-JUN-21:10 | 28.90 | 24.82 |
July | 0.818178E+11 | 41724.68 | 28-JUL-21:10 | 29.32 | 24.20 | 0.321408E+11 | 19186.11 | 14-JUL-22:10 | 29.32 | 24.20 |
August | 0.807674E+11 | 41659.22 | 21-AUG-21:10 | 28.22 | 25.01 | 0.322541E+11 | 19185.34 | 02-AUG-23:19 | 28.22 | 25.01 |
September | 0.797098E+11 | 42543.92 | 22-SEP-21:10 | 28.30 | 25.17 | 0.312312E+11 | 19186.10 | 05-SEP-22:10 | 28.30 | 25.17 |
October | 0.809410E+11 | 41481.29 | 06-OCT-21:10 | 26.70 | 23.48 | 0.322621E+11 | 19186.02 | 27-OCT-22:10 | 23.80 | 21.85 |
November | 0.747210E+11 | 40643.29 | 03-NOV-21:10 | 26.70 | 24.27 | 0.310690E+11 | 19186.08 | 21-NOV-22:40 | 24.40 | 22.66 |
December | 0.731147E+11 | 39913.75 | 08-DEC-22:05 | 23.98 | 22.48 | 0.318905E+11 | 19186.03 | 08-DEC-23:10 | 24.50 | 22.98 |
Annual Sum or Average | 0.909290E+12 | 0.377498E+12 | ||||||||
Minimum of Months | 0.655521E+11 | 37822.73 | 23.90 | 20.81 | 0.287861E+11 | 19185.34 | 18.30 | 15.01 | ||
Maximum of Months | 0.818178E+11 | 42543.92 | 29.32 | 25.17 | 0.322621E+11 | 19186.32 | 29.32 | 25.17 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130279E+10 | 2639.28 | 23-JAN-16:02 | 26.70 | 20.30 | 98659408.10 | 56.69 | 12-JAN-22:40 | 26.70 | 20.30 |
February | 0.141512E+10 | 2613.96 | 14-FEB-16:02 | 24.32 | 19.24 | 89225884.02 | 56.69 | 09-FEB-22:00 | 24.32 | 19.24 |
March | 0.176258E+10 | 2683.29 | 27-MAR-18:02 | 25.60 | 21.37 | 98945496.34 | 56.69 | 02-MAR-22:30 | 25.60 | 21.37 |
April | 0.210628E+10 | 2709.74 | 22-APR-15:02 | 26.60 | 21.27 | 95856720.84 | 56.70 | 10-APR-21:10 | 26.60 | 21.27 |
May | 0.235596E+10 | 2714.58 | 15-MAY-18:02 | 27.70 | 22.47 | 99156130.94 | 56.70 | 30-MAY-02:20 | 25.60 | 24.31 |
June | 0.238470E+10 | 2719.96 | 08-JUN-18:02 | 29.90 | 25.47 | 96000810.48 | 56.70 | 08-JUN-21:10 | 28.90 | 25.14 |
July | 0.266645E+10 | 2698.13 | 11-JUL-18:02 | 29.90 | 24.79 | 99117139.73 | 56.70 | 28-JUL-21:40 | 29.07 | 24.38 |
August | 0.253501E+10 | 2714.05 | 03-AUG-18:02 | 28.80 | 24.86 | 99212417.03 | 56.70 | 31-AUG-21:10 | 27.77 | 24.60 |
September | 0.249292E+10 | 2709.44 | 11-SEP-18:02 | 27.12 | 24.06 | 95930824.39 | 56.70 | 01-SEP-21:19 | 27.12 | 24.06 |
October | 0.242082E+10 | 2725.40 | 10-OCT-15:02 | 27.38 | 24.35 | 99128546.44 | 56.70 | 06-OCT-21:10 | 27.38 | 24.35 |
November | 0.186184E+10 | 2680.51 | 18-NOV-16:02 | 27.12 | 21.96 | 95833965.32 | 56.69 | 29-NOV-22:00 | 26.10 | 24.12 |
December | 0.147173E+10 | 2688.26 | 07-DEC-16:02 | 26.52 | 23.06 | 98653131.20 | 56.69 | 04-DEC-23:49 | 26.52 | 23.06 |
Annual Sum or Average | 0.247762E+11 | 0.116572E+10 | ||||||||
Minimum of Months | 0.130279E+10 | 2613.96 | 24.32 | 19.24 | 89225884.02 | 56.69 | 24.32 | 19.24 | ||
Maximum of Months | 0.266645E+10 | 2725.40 | 29.90 | 25.47 | 99212417.03 | 56.70 | 29.07 | 25.14 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.733700E+09 | 2699.38 | 03-JAN-16:02 | 26.42 | 20.44 | 0.102784E+09 | 74.99 | 03-JAN-22:10 | 22.12 | 20.55 |
February | 0.908216E+09 | 2718.05 | 17-FEB-16:02 | 26.42 | 21.60 | 94635600.78 | 76.06 | 16-FEB-22:10 | 26.42 | 21.60 |
March | 0.128174E+10 | 2755.85 | 13-MAR-15:02 | 28.98 | 23.21 | 0.105524E+09 | 79.13 | 30-MAR-21:10 | 23.90 | 19.88 |
April | 0.177719E+10 | 2735.88 | 22-APR-15:02 | 26.60 | 21.27 | 0.101689E+09 | 80.83 | 10-APR-21:10 | 26.60 | 21.27 |
May | 0.230904E+10 | 2878.81 | 10-MAY-16:31 | 25.53 | 22.56 | 0.100491E+09 | 76.45 | 25-MAY-21:10 | 23.90 | 22.59 |
June | 0.240416E+10 | 2923.60 | 13-JUN-18:11 | 25.37 | 22.49 | 96561702.01 | 70.13 | 21-JUN-20:00 | 24.40 | 22.75 |
July | 0.265988E+10 | 2726.51 | 15-JUL-18:02 | 28.80 | 24.34 | 0.100048E+09 | 80.23 | 14-JUL-21:10 | 28.80 | 24.34 |
August | 0.246961E+10 | 2738.52 | 03-AUG-18:02 | 28.80 | 24.86 | 99553757.33 | 58.53 | 06-AUG-21:00 | 24.40 | 23.27 |
September | 0.229920E+10 | 2739.49 | 07-SEP-15:02 | 27.20 | 24.67 | 96826078.29 | 78.23 | 05-SEP-21:10 | 27.20 | 24.67 |
October | 0.207108E+10 | 2730.11 | 03-OCT-18:02 | 29.22 | 24.97 | 0.100080E+09 | 72.41 | 27-OCT-21:19 | 23.90 | 21.88 |
November | 0.142030E+10 | 2728.74 | 22-NOV-16:02 | 27.70 | 23.78 | 98454881.30 | 75.47 | 21-NOV-22:10 | 27.70 | 23.78 |
December | 0.925277E+09 | 2661.44 | 01-DEC-16:02 | 26.42 | 19.90 | 0.102835E+09 | 75.38 | 01-DEC-22:10 | 21.70 | 19.20 |
Annual Sum or Average | 0.212594E+11 | 0.119948E+10 | ||||||||
Minimum of Months | 0.733700E+09 | 2661.44 | 25.37 | 19.90 | 94635600.78 | 58.53 | 21.70 | 19.20 | ||
Maximum of Months | 0.265988E+10 | 2923.60 | 29.22 | 24.97 | 0.105524E+09 | 80.83 | 28.80 | 24.67 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.531173E+09 | 579.16 | 02-JAN-14:30 | 28.90 | 24.11 | 0.00 | 0.00 | 01-JAN-00:10 | 28.90 | 24.11 |
February | 0.467724E+09 | 509.26 | 11-FEB-14:30 | 28.85 | 24.07 | 0.00 | 0.00 | 01-FEB-00:10 | 28.85 | 24.07 |
March | 0.463739E+09 | 416.75 | 02-MAR-14:30 | 25.00 | 17.17 | 0.00 | 0.00 | 01-MAR-00:10 | 25.00 | 17.17 |
April | 0.469215E+09 | 337.38 | 15-APR-14:30 | 30.85 | 22.80 | 0.00 | 0.00 | 01-APR-00:10 | 30.85 | 22.80 |
May | 0.506107E+09 | 313.65 | 22-MAY-17:12 | 31.33 | 23.80 | 0.00 | 0.00 | 01-MAY-00:10 | 31.33 | 23.80 |
June | 0.537725E+09 | 323.32 | 03-JUN-20:50 | 29.40 | 24.56 | 0.00 | 0.00 | 01-JUN-00:10 | 29.40 | 24.56 |
July | 0.597893E+09 | 360.14 | 29-JUL-19:10 | 31.55 | 24.08 | 0.00 | 0.00 | 01-JUL-00:10 | 31.55 | 24.08 |
August | 0.592517E+09 | 359.34 | 20-AUG-14:00 | 32.20 | 24.99 | 0.00 | 0.00 | 01-AUG-00:10 | 32.20 | 24.99 |
September | 0.672125E+09 | 486.82 | 30-SEP-13:40 | 30.93 | 24.69 | 0.00 | 0.00 | 01-SEP-00:10 | 30.93 | 24.69 |
October | 0.728491E+09 | 547.19 | 25-OCT-14:00 | 30.60 | 22.69 | 0.00 | 0.00 | 01-OCT-00:10 | 30.60 | 22.69 |
November | 0.627717E+09 | 582.76 | 07-NOV-13:40 | 28.13 | 20.93 | 0.00 | 0.00 | 01-NOV-00:10 | 28.13 | 20.93 |
December | 0.553282E+09 | 590.06 | 03-DEC-14:00 | 24.40 | 18.35 | 0.00 | 0.00 | 01-DEC-00:10 | 24.40 | 18.35 |
Annual Sum or Average | 0.674771E+10 | 0.00 | ||||||||
Minimum of Months | 0.463739E+09 | 313.65 | 24.40 | 17.17 | 0.00 | 0.00 | 24.40 | 17.17 | ||
Maximum of Months | 0.728491E+09 | 590.06 | 32.20 | 24.99 | 0.00 | 0.00 | 32.20 | 24.99 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.466253E+09 | 962.55 | 06-JAN-19:02 | 24.40 | 21.75 | 0.102016E+09 | 73.80 | 03-JAN-22:10 | 24.40 | 21.75 |
February | 0.486399E+09 | 985.07 | 22-FEB-16:02 | 27.43 | 14.84 | 93714152.30 | 75.43 | 10-FEB-22:10 | 27.43 | 14.84 |
March | 0.614028E+09 | 988.16 | 13-MAR-18:02 | 27.93 | 22.26 | 0.103577E+09 | 75.12 | 31-MAR-21:10 | 23.27 | 18.08 |
April | 0.738779E+09 | 1011.40 | 16-APR-18:02 | 30.63 | 21.39 | 0.100180E+09 | 76.52 | 25-APR-21:10 | 22.88 | 20.54 |
May | 0.940536E+09 | 1012.73 | 22-MAY-18:02 | 30.40 | 23.74 | 0.100172E+09 | 76.56 | 25-MAY-21:10 | 23.90 | 22.59 |
June | 0.994906E+09 | 1012.36 | 09-JUN-18:02 | 30.00 | 25.09 | 96335914.03 | 67.96 | 21-JUN-20:00 | 24.40 | 22.75 |
July | 0.104912E+10 | 1016.98 | 27-JUL-18:02 | 31.83 | 25.86 | 99770487.73 | 79.45 | 14-JUL-21:10 | 31.83 | 25.86 |
August | 0.978219E+09 | 1004.71 | 24-AUG-08:61 | 26.97 | 23.36 | 99311233.76 | 56.69 | 07-AUG-21:40 | 26.97 | 23.36 |
September | 0.925667E+09 | 1009.75 | 14-SEP-08:61 | 26.88 | 24.32 | 96525597.01 | 77.14 | 05-SEP-21:10 | 26.88 | 24.32 |
October | 0.850629E+09 | 1003.42 | 05-OCT-08:61 | 26.28 | 23.68 | 99666245.42 | 71.40 | 27-OCT-21:10 | 23.90 | 21.88 |
November | 0.673353E+09 | 1002.17 | 21-NOV-09:01 | 26.70 | 21.80 | 97940135.80 | 73.34 | 21-NOV-22:10 | 24.40 | 22.53 |
December | 0.513731E+09 | 988.03 | 09-DEC-09:02 | 26.20 | 22.58 | 0.102166E+09 | 73.66 | 01-DEC-22:10 | 26.20 | 22.58 |
Annual Sum or Average | 0.923162E+10 | 0.119138E+10 | ||||||||
Minimum of Months | 0.466253E+09 | 962.55 | 24.40 | 14.84 | 93714152.30 | 56.69 | 22.88 | 14.84 | ||
Maximum of Months | 0.104912E+10 | 1016.98 | 31.83 | 25.86 | 0.103577E+09 | 79.45 | 31.83 | 25.86 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135440E+10 | 2379.15 | 23-JAN-16:02 | 26.70 | 20.30 | 98813711.99 | 56.69 | 03-JAN-23:40 | 26.70 | 20.30 |
February | 0.141734E+10 | 2426.63 | 19-FEB-16:02 | 27.12 | 21.84 | 89372624.98 | 56.69 | 07-FEB-22:49 | 27.12 | 21.84 |
March | 0.173536E+10 | 2446.43 | 09-MAR-16:02 | 27.12 | 22.68 | 99110387.56 | 56.69 | 31-MAR-00:10 | 23.30 | 19.23 |
April | 0.209118E+10 | 2464.03 | 13-APR-08:61 | 27.20 | 23.27 | 95930128.96 | 56.70 | 10-APR-21:10 | 27.20 | 23.27 |
May | 0.236430E+10 | 2481.36 | 31-MAY-08:62 | 28.07 | 24.52 | 99192494.96 | 56.70 | 31-MAY-21:10 | 27.17 | 24.28 |
June | 0.251712E+10 | 2471.52 | 09-JUN-18:02 | 30.00 | 25.09 | 96029841.76 | 56.70 | 02-JUN-21:30 | 30.00 | 25.09 |
July | 0.274828E+10 | 2476.67 | 16-JUL-08:62 | 28.98 | 23.72 | 99137825.26 | 56.70 | 25-JUL-21:00 | 28.30 | 25.04 |
August | 0.254046E+10 | 2485.18 | 30-AUG-08:62 | 28.98 | 23.94 | 99228001.68 | 56.70 | 21-AUG-21:30 | 28.98 | 23.94 |
September | 0.258485E+10 | 2479.33 | 21-SEP-08:62 | 28.07 | 24.95 | 95954728.96 | 56.70 | 01-SEP-21:40 | 28.07 | 24.95 |
October | 0.245597E+10 | 2480.73 | 06-OCT-08:62 | 26.88 | 23.89 | 99155711.23 | 56.70 | 06-OCT-21:19 | 26.70 | 23.55 |
November | 0.187648E+10 | 2475.49 | 21-NOV-09:01 | 26.70 | 21.80 | 95902721.43 | 56.69 | 24-NOV-01:10 | 25.22 | 23.80 |
December | 0.138245E+10 | 2447.95 | 25-DEC-16:02 | 25.92 | 23.57 | 98696895.54 | 56.69 | 09-DEC-01:19 | 25.92 | 23.57 |
Annual Sum or Average | 0.250682E+11 | 0.116653E+10 | ||||||||
Minimum of Months | 0.135440E+10 | 2379.15 | 25.92 | 20.30 | 89372624.98 | 56.69 | 23.30 | 19.23 | ||
Maximum of Months | 0.274828E+10 | 2485.18 | 30.00 | 25.09 | 99228001.68 | 56.70 | 30.00 | 25.09 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.777798E+09 | 2400.19 | 01-JAN-09:51 | 25.00 | 21.12 | 0.102921E+09 | 74.60 | 03-JAN-22:10 | 22.12 | 20.55 |
February | 0.895959E+09 | 2678.75 | 28-FEB-09:51 | 24.40 | 16.28 | 94702988.84 | 75.18 | 17-FEB-22:10 | 24.40 | 16.28 |
March | 0.126274E+10 | 2596.76 | 02-MAR-09:51 | 23.90 | 16.69 | 0.105085E+09 | 77.25 | 31-MAR-21:10 | 23.27 | 18.08 |
April | 0.174834E+10 | 2761.46 | 21-APR-08:31 | 25.20 | 18.41 | 0.101708E+09 | 78.14 | 10-APR-21:10 | 25.20 | 18.41 |
May | 0.230915E+10 | 2600.00 | 02-MAY-08:11 | 26.47 | 22.35 | 0.100657E+09 | 76.00 | 25-MAY-21:10 | 23.90 | 22.59 |
June | 0.253329E+10 | 2654.34 | 13-JUN-18:11 | 25.37 | 22.49 | 96637036.82 | 70.88 | 21-JUN-20:00 | 24.40 | 22.75 |
July | 0.273910E+10 | 2497.71 | 23-JUL-08:62 | 29.60 | 24.60 | 0.100130E+09 | 81.99 | 14-JUL-21:10 | 29.60 | 24.60 |
August | 0.247490E+10 | 2501.38 | 08-AUG-08:62 | 29.68 | 24.64 | 99567649.01 | 58.38 | 06-AUG-21:00 | 29.68 | 24.64 |
September | 0.238665E+10 | 2545.58 | 17-SEP-07:51 | 26.70 | 23.84 | 96937549.90 | 78.38 | 05-SEP-21:10 | 26.70 | 23.84 |
October | 0.209490E+10 | 2616.31 | 17-OCT-08:61 | 25.78 | 18.68 | 0.100263E+09 | 73.58 | 27-OCT-21:19 | 23.90 | 21.88 |
November | 0.141329E+10 | 2487.03 | 07-NOV-09:51 | 25.60 | 21.07 | 98766283.38 | 75.40 | 21-NOV-22:10 | 24.40 | 22.53 |
December | 0.854544E+09 | 2451.72 | 09-DEC-09:02 | 26.20 | 22.58 | 0.102345E+09 | 72.95 | 07-DEC-22:10 | 26.20 | 22.58 |
Annual Sum or Average | 0.214907E+11 | 0.119972E+10 | ||||||||
Minimum of Months | 0.777798E+09 | 2400.19 | 23.90 | 16.28 | 94702988.84 | 58.38 | 22.12 | 16.28 | ||
Maximum of Months | 0.273910E+10 | 2761.46 | 29.68 | 24.64 | 0.105085E+09 | 81.99 | 29.68 | 24.64 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.399127E+10 | 1966.71 | 01-JAN-11:33 | 26.30 | 21.34 | 0.144145E+10 | 916.98 | 03-JAN-22:49 | 21.78 | 20.23 |
February | 0.366491E+10 | 1944.55 | 11-FEB-11:35 | 27.60 | 23.74 | 0.131347E+10 | 906.98 | 17-FEB-23:10 | 23.90 | 20.81 |
March | 0.414535E+10 | 1976.04 | 04-MAR-11:35 | 27.03 | 22.82 | 0.147919E+10 | 920.58 | 31-MAR-22:10 | 23.05 | 18.37 |
April | 0.425918E+10 | 2102.28 | 16-APR-10:33 | 28.67 | 21.62 | 0.147630E+10 | 937.73 | 14-APR-21:49 | 28.67 | 21.62 |
May | 0.451976E+10 | 2102.88 | 20-MAY-10:35 | 29.23 | 21.81 | 0.154807E+10 | 943.03 | 19-MAY-21:49 | 29.23 | 21.81 |
June | 0.452302E+10 | 2158.74 | 11-JUN-10:33 | 30.93 | 23.60 | 0.153185E+10 | 951.84 | 29-JUN-23:19 | 28.90 | 24.51 |
July | 0.477580E+10 | 2186.57 | 29-JUL-18:00 | 33.30 | 24.11 | 0.159230E+10 | 951.85 | 14-JUL-22:10 | 33.30 | 24.11 |
August | 0.467958E+10 | 2175.47 | 20-AUG-10:33 | 31.13 | 25.97 | 0.158555E+10 | 951.84 | 02-AUG-23:19 | 31.13 | 25.97 |
September | 0.458648E+10 | 2214.11 | 22-SEP-21:10 | 28.30 | 25.17 | 0.153883E+10 | 951.84 | 18-SEP-23:19 | 28.30 | 25.17 |
October | 0.463651E+10 | 2163.57 | 07-OCT-10:35 | 31.13 | 24.14 | 0.157767E+10 | 951.83 | 25-OCT-21:30 | 26.40 | 21.40 |
November | 0.422586E+10 | 2045.95 | 10-NOV-11:33 | 27.20 | 24.31 | 0.147204E+10 | 945.25 | 10-NOV-23:10 | 22.52 | 20.48 |
December | 0.406896E+10 | 2128.44 | 09-DEC-12:30 | 27.20 | 22.50 | 0.145651E+10 | 930.28 | 08-DEC-23:10 | 27.20 | 22.50 |
Annual Sum or Average | 0.520767E+11 | 0.180132E+11 | ||||||||
Minimum of Months | 0.366491E+10 | 1944.55 | 26.30 | 21.34 | 0.131347E+10 | 906.98 | 21.78 | 18.37 | ||
Maximum of Months | 0.477580E+10 | 2214.11 | 33.30 | 25.97 | 0.159230E+10 | 951.85 | 33.30 | 25.97 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116855E+10 | 2754.50 | 06-JAN-16:02 | 25.92 | 22.27 | 98504465.59 | 56.69 | 13-JAN-22:19 | 24.23 | 21.06 |
February | 0.134326E+10 | 2764.43 | 11-FEB-16:02 | 27.70 | 24.11 | 89115284.87 | 56.69 | 22-FEB-22:30 | 18.85 | 14.85 |
March | 0.171046E+10 | 2821.80 | 13-MAR-18:02 | 27.93 | 22.26 | 98854112.49 | 56.70 | 30-MAR-22:00 | 23.30 | 19.57 |
April | 0.211582E+10 | 2791.09 | 22-APR-15:02 | 26.60 | 21.27 | 95823423.19 | 56.70 | 13-APR-01:10 | 26.60 | 21.27 |
May | 0.240910E+10 | 2822.42 | 31-MAY-18:02 | 28.30 | 23.96 | 99147499.29 | 56.70 | 05-MAY-21:10 | 28.30 | 23.96 |
June | 0.244903E+10 | 2827.33 | 08-JUN-18:02 | 29.90 | 25.47 | 95993842.79 | 56.70 | 09-JUN-21:10 | 29.32 | 24.94 |
July | 0.275276E+10 | 2833.28 | 11-JUL-18:02 | 29.90 | 24.79 | 99112249.67 | 56.70 | 27-JUL-21:10 | 29.22 | 25.45 |
August | 0.259341E+10 | 2835.88 | 14-AUG-18:02 | 29.22 | 23.90 | 99201146.84 | 56.70 | 20-AUG-04:30 | 27.80 | 24.87 |
September | 0.252904E+10 | 2868.73 | 30-SEP-15:02 | 31.10 | 24.59 | 95918232.78 | 56.70 | 01-SEP-21:10 | 31.10 | 24.59 |
October | 0.240534E+10 | 2849.16 | 10-OCT-15:02 | 27.38 | 24.35 | 99105112.56 | 56.70 | 06-OCT-21:40 | 27.38 | 24.35 |
November | 0.179051E+10 | 2868.82 | 07-NOV-16:02 | 28.22 | 22.20 | 95756250.25 | 56.70 | 03-NOV-22:00 | 28.22 | 22.20 |
December | 0.135827E+10 | 2773.57 | 07-DEC-16:02 | 26.52 | 23.06 | 98499673.02 | 56.70 | 04-DEC-22:30 | 26.52 | 23.06 |
Annual Sum or Average | 0.246256E+11 | 0.116503E+10 | ||||||||
Minimum of Months | 0.116855E+10 | 2754.50 | 25.92 | 21.27 | 89115284.87 | 56.69 | 18.85 | 14.85 | ||
Maximum of Months | 0.275276E+10 | 2868.82 | 31.10 | 25.47 | 99201146.84 | 56.70 | 31.10 | 25.45 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.627681E+09 | 2799.46 | 02-JAN-16:02 | 25.50 | 20.58 | 0.102058E+09 | 74.50 | 03-JAN-22:10 | 22.12 | 20.55 |
February | 0.863711E+09 | 2802.41 | 10-FEB-16:02 | 26.02 | 22.24 | 94231241.29 | 76.26 | 10-FEB-22:10 | 23.90 | 22.01 |
March | 0.126166E+10 | 2831.04 | 13-MAR-18:02 | 27.93 | 22.26 | 0.105317E+09 | 79.06 | 30-MAR-21:10 | 23.90 | 19.88 |
April | 0.182088E+10 | 2813.16 | 22-APR-15:02 | 26.60 | 21.27 | 0.101557E+09 | 81.12 | 10-APR-21:10 | 26.60 | 21.27 |
May | 0.237389E+10 | 2980.30 | 10-MAY-16:31 | 25.53 | 22.56 | 0.100418E+09 | 76.36 | 25-MAY-21:10 | 23.90 | 22.59 |
June | 0.247325E+10 | 3057.52 | 13-JUN-18:11 | 25.37 | 22.49 | 96550606.69 | 70.23 | 21-JUN-20:00 | 24.40 | 22.75 |
July | 0.275329E+10 | 2906.74 | 07-JUL-18:02 | 30.32 | 24.24 | 0.100050E+09 | 81.06 | 14-JUL-21:10 | 23.22 | 22.08 |
August | 0.252987E+10 | 2862.08 | 14-AUG-18:02 | 29.22 | 23.90 | 99525792.57 | 58.42 | 06-AUG-21:00 | 29.22 | 23.90 |
September | 0.233779E+10 | 2866.66 | 12-SEP-18:02 | 27.20 | 22.88 | 96753111.64 | 78.28 | 05-SEP-21:10 | 27.20 | 22.88 |
October | 0.205670E+10 | 2848.23 | 03-OCT-18:02 | 29.22 | 24.97 | 99916274.56 | 71.47 | 27-OCT-21:19 | 23.90 | 21.88 |
November | 0.136459E+10 | 2854.73 | 30-NOV-16:02 | 27.80 | 24.87 | 98009448.94 | 74.95 | 21-NOV-22:10 | 27.80 | 24.87 |
December | 0.847307E+09 | 2790.38 | 07-DEC-16:02 | 26.52 | 23.06 | 0.102032E+09 | 75.09 | 01-DEC-22:10 | 26.52 | 23.06 |
Annual Sum or Average | 0.213106E+11 | 0.119642E+10 | ||||||||
Minimum of Months | 0.627681E+09 | 2790.38 | 25.37 | 20.58 | 94231241.29 | 58.42 | 22.12 | 19.88 | ||
Maximum of Months | 0.275329E+10 | 3057.52 | 30.32 | 24.97 | 0.105317E+09 | 81.12 | 29.22 | 24.87 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117917E+10 | 1369.53 | 03-JAN-16:02 | 26.42 | 20.44 | 98932769.55 | 56.70 | 27-JAN-22:19 | 19.40 | 15.40 |
February | 0.109325E+10 | 1377.65 | 11-FEB-16:02 | 27.70 | 24.11 | 89372379.84 | 56.70 | 22-FEB-22:49 | 18.48 | 14.89 |
March | 0.114859E+10 | 1354.89 | 01-MAR-16:02 | 24.90 | 15.69 | 98991361.94 | 56.70 | 27-MAR-21:30 | 24.70 | 21.76 |
April | 0.120515E+10 | 1368.42 | 17-APR-18:02 | 30.03 | 18.67 | 95836636.69 | 56.70 | 14-APR-21:00 | 30.03 | 18.67 |
May | 0.132056E+10 | 1367.18 | 29-MAY-18:02 | 30.82 | 24.67 | 99141062.41 | 56.70 | 31-MAY-21:30 | 27.10 | 24.22 |
June | 0.137774E+10 | 1360.15 | 04-JUN-15:02 | 26.83 | 24.20 | 95990541.50 | 56.70 | 14-JUN-21:00 | 28.30 | 23.17 |
July | 0.150689E+10 | 1372.90 | 27-JUL-18:02 | 31.83 | 25.86 | 99109318.88 | 56.70 | 24-JUL-21:49 | 31.83 | 25.86 |
August | 0.148417E+10 | 1373.31 | 30-AUG-15:02 | 29.90 | 23.96 | 99216422.36 | 56.70 | 14-AUG-22:10 | 29.90 | 23.96 |
September | 0.159587E+10 | 1391.43 | 10-SEP-15:02 | 31.10 | 25.25 | 95981820.19 | 56.70 | 06-SEP-21:00 | 31.10 | 25.25 |
October | 0.167382E+10 | 1389.14 | 20-OCT-15:02 | 27.20 | 21.57 | 99250668.67 | 56.70 | 23-OCT-22:40 | 25.37 | 22.35 |
November | 0.142520E+10 | 1388.30 | 03-NOV-15:02 | 28.30 | 24.32 | 95950969.40 | 56.70 | 03-NOV-22:40 | 26.70 | 23.98 |
December | 0.123437E+10 | 1370.46 | 08-DEC-16:02 | 26.93 | 23.20 | 98886256.54 | 56.69 | 01-DEC-22:10 | 26.93 | 23.20 |
Annual Sum or Average | 0.162448E+11 | 0.116666E+10 | ||||||||
Minimum of Months | 0.109325E+10 | 1354.89 | 24.90 | 15.69 | 89372379.84 | 56.69 | 18.48 | 14.89 | ||
Maximum of Months | 0.167382E+10 | 1391.43 | 31.83 | 25.86 | 99250668.67 | 56.70 | 31.83 | 25.86 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.382906E+11 | 20983.12 | 13-JAN-23:00 | 23.90 | 21.21 | 0.190471E+11 | 11348.85 | 02-JAN-23:10 | 23.90 | 21.21 |
February | 0.355981E+11 | 21375.99 | 17-FEB-22:53 | 23.90 | 20.81 | 0.172609E+11 | 11348.99 | 16-FEB-23:10 | 23.90 | 20.81 |
March | 0.403959E+11 | 21651.01 | 27-MAR-22:00 | 24.40 | 21.69 | 0.192194E+11 | 11349.03 | 28-MAR-21:10 | 24.32 | 20.85 |
April | 0.411588E+11 | 22320.01 | 14-APR-21:10 | 25.50 | 22.67 | 0.186280E+11 | 11349.13 | 20-APR-22:10 | 22.20 | 16.88 |
May | 0.444116E+11 | 22999.80 | 22-MAY-22:00 | 27.20 | 22.18 | 0.192934E+11 | 11349.02 | 24-MAY-21:10 | 24.40 | 22.88 |
June | 0.442677E+11 | 23267.56 | 09-JUN-21:20 | 29.23 | 24.92 | 0.187219E+11 | 11349.13 | 21-JUN-21:10 | 24.50 | 22.87 |
July | 0.461280E+11 | 23309.45 | 28-JUL-21:10 | 29.32 | 24.20 | 0.192808E+11 | 11348.99 | 14-JUL-22:10 | 29.32 | 24.20 |
August | 0.452220E+11 | 23138.27 | 02-AUG-21:20 | 29.23 | 24.60 | 0.193425E+11 | 11347.82 | 02-AUG-23:19 | 28.90 | 24.51 |
September | 0.435954E+11 | 23213.15 | 08-SEP-22:00 | 29.40 | 24.47 | 0.186634E+11 | 11348.98 | 05-SEP-22:10 | 29.40 | 24.47 |
October | 0.435680E+11 | 22539.67 | 03-OCT-22:00 | 27.80 | 25.31 | 0.192369E+11 | 11348.84 | 27-OCT-22:10 | 23.80 | 21.85 |
November | 0.400146E+11 | 22180.58 | 03-NOV-22:00 | 26.70 | 24.27 | 0.185400E+11 | 11348.87 | 21-NOV-22:40 | 24.40 | 22.66 |
December | 0.390593E+11 | 21441.31 | 08-DEC-22:53 | 24.40 | 22.88 | 0.190705E+11 | 11348.84 | 05-DEC-23:10 | 24.40 | 22.88 |
Annual Sum or Average | 0.501710E+12 | 0.226305E+12 | ||||||||
Minimum of Months | 0.355981E+11 | 20983.12 | 23.90 | 20.81 | 0.172609E+11 | 11347.82 | 22.20 | 16.88 | ||
Maximum of Months | 0.461280E+11 | 23309.45 | 29.40 | 25.31 | 0.193425E+11 | 11349.13 | 29.40 | 24.51 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.414399E+11 | 22427.19 | 13-JAN-23:00 | 23.90 | 21.21 | 0.191451E+11 | 11348.85 | 02-JAN-23:10 | 23.90 | 21.21 |
February | 0.384115E+11 | 22737.67 | 17-FEB-22:53 | 23.90 | 20.81 | 0.173407E+11 | 11349.00 | 16-FEB-23:10 | 23.90 | 20.81 |
March | 0.435064E+11 | 22970.82 | 27-MAR-21:20 | 24.80 | 21.78 | 0.192884E+11 | 11349.03 | 28-MAR-21:10 | 24.32 | 20.85 |
April | 0.439869E+11 | 23552.63 | 14-APR-21:10 | 25.50 | 22.67 | 0.186645E+11 | 11354.56 | 17-APR-21:30 | 23.05 | 17.57 |
May | 0.472404E+11 | 24215.49 | 22-MAY-21:10 | 27.70 | 22.63 | 0.193172E+11 | 11349.95 | 02-MAY-21:30 | 27.70 | 22.63 |
June | 0.469055E+11 | 24463.81 | 28-JUN-21:20 | 28.90 | 24.83 | 0.187378E+11 | 11353.57 | 28-JUN-21:19 | 28.90 | 24.83 |
July | 0.488390E+11 | 24510.08 | 28-JUL-21:10 | 29.32 | 24.20 | 0.192928E+11 | 11349.00 | 14-JUL-22:10 | 29.32 | 24.20 |
August | 0.479402E+11 | 24330.47 | 02-AUG-21:10 | 29.32 | 24.62 | 0.193613E+11 | 11352.13 | 29-AUG-21:30 | 27.20 | 23.42 |
September | 0.461968E+11 | 24426.87 | 08-SEP-21:10 | 29.90 | 24.64 | 0.186812E+11 | 11351.39 | 26-SEP-21:30 | 27.20 | 22.81 |
October | 0.462618E+11 | 23749.97 | 03-OCT-21:10 | 27.80 | 25.31 | 0.192638E+11 | 11359.39 | 06-OCT-21:30 | 26.70 | 23.62 |
November | 0.428107E+11 | 23407.16 | 03-NOV-22:00 | 26.70 | 24.27 | 0.185879E+11 | 11350.91 | 03-NOV-21:30 | 26.70 | 24.27 |
December | 0.421487E+11 | 22713.07 | 08-DEC-22:53 | 24.40 | 22.88 | 0.191561E+11 | 11348.85 | 05-DEC-23:10 | 24.40 | 22.88 |
Annual Sum or Average | 0.535688E+12 | 0.226837E+12 | ||||||||
Minimum of Months | 0.384115E+11 | 22427.19 | 23.90 | 20.81 | 0.173407E+11 | 11348.85 | 23.05 | 17.57 | ||
Maximum of Months | 0.488390E+11 | 24510.08 | 29.90 | 25.31 | 0.193613E+11 | 11359.39 | 29.32 | 24.83 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.519477E+11 | 27916.10 | 01-JAN-11:45 | 26.20 | 21.28 | 0.188189E+11 | 11319.58 | 28-JAN-18:19 | 22.93 | 20.00 |
February | 0.474964E+11 | 28099.85 | 11-FEB-11:40 | 27.60 | 23.74 | 0.170023E+11 | 11319.63 | 25-FEB-18:19 | 22.43 | 15.34 |
March | 0.532221E+11 | 28308.15 | 27-MAR-10:35 | 26.13 | 21.70 | 0.188351E+11 | 11319.66 | 25-MAR-17:19 | 26.13 | 21.70 |
April | 0.528760E+11 | 29094.35 | 15-APR-10:50 | 29.63 | 22.91 | 0.182320E+11 | 11319.68 | 08-APR-17:19 | 29.63 | 22.91 |
May | 0.555673E+11 | 29043.27 | 06-MAY-10:50 | 29.13 | 21.57 | 0.188475E+11 | 11319.68 | 13-MAY-17:19 | 28.53 | 23.26 |
June | 0.545238E+11 | 29344.65 | 11-JUN-10:37 | 30.93 | 23.60 | 0.182486E+11 | 11319.68 | 10-JUN-17:19 | 30.93 | 23.60 |
July | 0.567130E+11 | 29489.70 | 23-JUL-10:50 | 32.75 | 24.78 | 0.188504E+11 | 11319.68 | 15-JUL-17:19 | 32.75 | 24.78 |
August | 0.559865E+11 | 29299.43 | 19-AUG-10:40 | 31.50 | 24.70 | 0.188554E+11 | 11319.68 | 26-AUG-17:19 | 30.40 | 25.15 |
September | 0.543504E+11 | 29270.85 | 24-SEP-10:33 | 30.53 | 25.04 | 0.182430E+11 | 11319.68 | 16-SEP-17:19 | 30.53 | 25.04 |
October | 0.552282E+11 | 29181.69 | 07-OCT-10:50 | 31.42 | 24.17 | 0.188442E+11 | 11319.65 | 21-OCT-17:19 | 26.67 | 19.93 |
November | 0.519646E+11 | 28060.39 | 03-NOV-10:50 | 28.22 | 23.99 | 0.182244E+11 | 11319.58 | 18-NOV-18:19 | 25.93 | 23.26 |
December | 0.521682E+11 | 28099.31 | 09-DEC-11:50 | 27.20 | 22.50 | 0.188218E+11 | 11319.63 | 02-DEC-18:19 | 27.20 | 22.50 |
Annual Sum or Average | 0.642044E+12 | 0.221824E+12 | ||||||||
Minimum of Months | 0.474964E+11 | 27916.10 | 26.13 | 21.28 | 0.170023E+11 | 11319.58 | 22.43 | 15.34 | ||
Maximum of Months | 0.567130E+11 | 29489.70 | 32.75 | 25.04 | 0.188554E+11 | 11319.68 | 32.75 | 25.15 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.889392E+10 | 4688.17 | 01-JAN-11:33 | 26.30 | 21.34 | 0.146004E+10 | 951.18 | 03-JAN-22:40 | 21.87 | 20.31 |
February | 0.831531E+10 | 4749.94 | 11-FEB-11:35 | 27.60 | 23.74 | 0.134888E+10 | 950.60 | 17-FEB-22:40 | 23.90 | 20.81 |
March | 0.945810E+10 | 4688.01 | 04-MAR-11:35 | 27.03 | 22.82 | 0.152617E+10 | 969.92 | 30-MAR-21:40 | 23.90 | 20.02 |
April | 0.997164E+10 | 5091.08 | 16-APR-15:13 | 31.33 | 21.09 | 0.154834E+10 | 1007.09 | 14-APR-21:40 | 31.33 | 21.09 |
May | 0.108551E+11 | 5324.93 | 18-MAY-15:03 | 30.92 | 22.77 | 0.165216E+10 | 1007.39 | 22-MAY-23:19 | 25.20 | 22.38 |
June | 0.111324E+11 | 5895.74 | 28-JUN-15:50 | 30.10 | 24.37 | 0.163771E+10 | 1007.39 | 09-JUN-23:19 | 30.10 | 24.37 |
July | 0.120056E+11 | 6669.71 | 28-JUL-15:40 | 35.00 | 24.98 | 0.169214E+10 | 1007.39 | 27-JUL-23:19 | 35.00 | 24.98 |
August | 0.114314E+11 | 5910.73 | 20-AUG-15:04 | 31.93 | 25.29 | 0.168506E+10 | 1007.39 | 02-AUG-23:19 | 31.93 | 25.29 |
September | 0.112511E+11 | 6571.57 | 09-SEP-13:00 | 31.70 | 25.11 | 0.162955E+10 | 1007.39 | 08-SEP-23:19 | 31.70 | 25.11 |
October | 0.109816E+11 | 6050.82 | 07-OCT-13:30 | 30.00 | 23.82 | 0.165656E+10 | 1007.39 | 06-OCT-23:19 | 30.00 | 23.82 |
November | 0.971343E+10 | 5050.76 | 10-NOV-13:40 | 28.33 | 24.04 | 0.152446E+10 | 997.97 | 03-NOV-22:10 | 28.33 | 24.04 |
December | 0.916008E+10 | 5105.71 | 09-DEC-12:30 | 27.20 | 22.50 | 0.148597E+10 | 973.41 | 08-DEC-22:00 | 27.20 | 22.50 |
Annual Sum or Average | 0.123170E+12 | 0.188470E+11 | ||||||||
Minimum of Months | 0.831531E+10 | 4688.01 | 26.30 | 21.09 | 0.134888E+10 | 950.60 | 21.87 | 20.02 | ||
Maximum of Months | 0.120056E+11 | 6669.71 | 35.00 | 25.29 | 0.169214E+10 | 1007.39 | 35.00 | 25.29 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1338372.06 | 851.02 | 11-JAN-19:05 | 21.52 |
February | 4599739.25 | 843.70 | 12-FEB-19:05 | 20.10 |
March | 758091.90 | 756.53 | 19-MAR-18:05 | 18.72 |
April | 462427.23 | 863.49 | 20-APR-08:05 | 23.48 |
May | 273607.94 | 575.50 | 08-MAY-08:05 | 25.18 |
June | 129069.03 | 498.31 | 19-JUN-08:05 | 26.60 |
July | 10119.82 | 101.20 | 03-JUL-08:05 | 26.88 |
August | 93162.22 | 373.59 | 13-AUG-08:05 | 27.07 |
September | 64482.32 | 287.93 | 15-SEP-08:05 | 25.37 |
October | 169482.91 | 598.99 | 18-OCT-08:05 | 26.20 |
November | 767893.18 | 757.95 | 30-NOV-09:05 | 26.20 |
December | 1129472.79 | 649.70 | 16-DEC-09:04 | 14.45 |
Annual Sum or Average | 9795920.64 | |||
Minimum of Months | 10119.82 | 101.20 | 14.45 | |
Maximum of Months | 4599739.25 | 863.49 | 27.07 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2633604.11 | 805.57 | 24-JAN-09:03 | 11.88 |
February | 7622880.06 | 765.75 | 23-FEB-09:53 | 22.80 |
March | 938222.56 | 729.07 | 17-MAR-08:03 | 14.78 |
April | 145321.23 | 324.14 | 25-APR-08:36 | 25.53 |
May | 193452.45 | 557.37 | 28-MAY-06:55 | 25.00 |
June | 65865.67 | 256.88 | 19-JUN-08:05 | 26.60 |
July | 42809.75 | 323.95 | 06-JUL-06:55 | 25.00 |
August | 143471.68 | 465.57 | 28-AUG-08:55 | 22.80 |
September | 208822.84 | 493.08 | 07-SEP-06:55 | 24.40 |
October | 503604.63 | 807.26 | 18-OCT-08:05 | 26.20 |
November | 1249560.12 | 912.82 | 12-NOV-16:04 | 20.00 |
December | 2876429.86 | 1007.27 | 28-DEC-16:04 | 19.90 |
Annual Sum or Average | 16624044.95 | |||
Minimum of Months | 42809.75 | 256.88 | 11.88 | |
Maximum of Months | 7622880.06 | 1007.27 | 26.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 216921.85 | 380.89 | 25-JAN-16:04 | 17.80 |
February | 115242.36 | 180.65 | 04-FEB-09:06 | 10.47 |
March | 116767.63 | 298.08 | 16-MAR-15:05 | 18.48 |
April | 7481.98 | 39.65 | 19-APR-08:55 | 21.70 |
May | 6054.85 | 44.53 | 28-MAY-06:57 | 25.00 |
June | 7898.82 | 82.03 | 25-JUN-06:56 | 25.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 4733.56 | 63.11 | 06-AUG-21:57 | 24.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 22212.05 | 118.06 | 15-OCT-06:56 | 24.40 |
November | 23305.62 | 102.67 | 13-NOV-16:07 | 24.32 |
December | 243503.00 | 283.77 | 27-DEC-09:05 | 11.47 |
Annual Sum or Average | 764121.71 | |||
Minimum of Months | 0.00 | 0.00 | 10.47 | |
Maximum of Months | 243503.00 | 380.89 | 27.05 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 565677.91 | 615.68 | 21-JAN-19:05 | 17.38 |
February | 4120411.02 | 692.64 | 05-FEB-19:05 | 18.90 |
March | 433108.95 | 808.45 | 16-MAR-18:05 | 18.22 |
April | 783.83 | 7.84 | 29-APR-08:07 | 23.40 |
May | 388.09 | 4.53 | 26-MAY-08:06 | 25.68 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 17391.30 | 123.49 | 12-AUG-08:07 | 22.70 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 36498.01 | 104.26 | 24-NOV-09:07 | 21.70 |
December | 873922.88 | 782.08 | 19-DEC-19:04 | 18.22 |
Annual Sum or Average | 6048181.98 | |||
Minimum of Months | 0.00 | 0.00 | 17.38 | |
Maximum of Months | 4120411.02 | 808.45 | 27.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3281729.79 | 916.76 | 24-JAN-16:05 | 16.70 |
February | 7323167.33 | 1027.21 | 03-FEB-16:04 | 16.42 |
March | 836275.24 | 479.19 | 21-MAR-21:55 | 18.30 |
April | 14227.71 | 118.73 | 19-APR-08:56 | 21.70 |
May | 31834.79 | 165.73 | 27-MAY-08:56 | 23.90 |
June | 14716.72 | 136.99 | 15-JUN-08:56 | 25.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 5324.81 | 62.12 | 03-AUG-08:56 | 24.40 |
September | 5931.52 | 79.09 | 27-SEP-18:56 | 24.40 |
October | 67157.69 | 226.81 | 10-OCT-06:56 | 24.40 |
November | 341973.76 | 406.95 | 16-NOV-22:55 | 23.90 |
December | 4826476.94 | 835.42 | 13-DEC-16:05 | 21.02 |
Annual Sum or Average | 16748816.29 | |||
Minimum of Months | 0.00 | 0.00 | 16.42 | |
Maximum of Months | 7323167.33 | 1027.21 | 26.83 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7159589.15 | 841.23 | 24-JAN-19:05 | 13.72 |
February | 14287773.00 | 916.85 | 04-FEB-09:02 | 10.47 |
March | 5834644.97 | 1495.03 | 16-MAR-08:62 | 8.68 |
April | 541537.85 | 718.13 | 20-APR-08:05 | 23.48 |
May | 531119.64 | 751.71 | 08-MAY-08:05 | 25.18 |
June | 428185.11 | 745.10 | 19-JUN-08:05 | 26.60 |
July | 119012.90 | 507.17 | 03-JUL-08:05 | 26.88 |
August | 405349.73 | 799.15 | 10-AUG-08:05 | 24.60 |
September | 306558.22 | 715.75 | 15-SEP-08:05 | 25.37 |
October | 531838.88 | 748.50 | 18-OCT-08:05 | 26.20 |
November | 3014322.55 | 1027.29 | 12-NOV-16:04 | 20.00 |
December | 10919687.80 | 899.48 | 28-DEC-09:03 | 19.90 |
Annual Sum or Average | 44079619.79 | |||
Minimum of Months | 119012.90 | 507.17 | 8.68 | |
Maximum of Months | 14287773.00 | 1495.03 | 26.88 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16970906.26 | 1485.81 | 25-JAN-09:02 | 11.57 |
February | 21669492.82 | 1488.95 | 04-FEB-09:02 | 10.47 |
March | 7338579.57 | 1507.53 | 16-MAR-08:62 | 8.68 |
April | 347328.22 | 634.26 | 20-APR-08:54 | 24.40 |
May | 281984.44 | 538.87 | 28-MAY-06:55 | 25.00 |
June | 310918.78 | 640.28 | 19-JUN-08:05 | 26.60 |
July | 94685.69 | 409.34 | 18-JUL-06:55 | 27.20 |
August | 408120.77 | 735.32 | 10-AUG-08:05 | 24.60 |
September | 445242.26 | 759.88 | 15-SEP-08:05 | 25.37 |
October | 971705.90 | 786.97 | 18-OCT-08:05 | 26.20 |
November | 4571897.19 | 1069.99 | 13-NOV-09:52 | 19.40 |
December | 24167507.91 | 1479.79 | 27-DEC-09:02 | 11.47 |
Annual Sum or Average | 77578369.80 | |||
Minimum of Months | 94685.69 | 409.34 | 8.68 | |
Maximum of Months | 24167507.91 | 1507.53 | 27.20 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 168664.62 | 329.54 | 14-JAN-16:06 | 18.80 |
February | 1024263.72 | 163.65 | 04-FEB-09:06 | 10.47 |
March | 269672.54 | 397.67 | 21-MAR-08:03 | 12.57 |
April | 81586.54 | 156.35 | 13-APR-08:06 | 27.20 |
May | 35572.35 | 145.50 | 26-MAY-08:06 | 25.68 |
June | 4170.14 | 48.65 | 22-JUN-08:06 | 24.90 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 28709.67 | 176.42 | 28-AUG-08:06 | 23.72 |
September | 58054.66 | 164.74 | 14-SEP-08:06 | 26.88 |
October | 45093.88 | 149.05 | 12-OCT-08:06 | 27.80 |
November | 22341.25 | 218.67 | 12-NOV-16:06 | 20.00 |
December | 208477.07 | 296.45 | 28-DEC-16:06 | 19.90 |
Annual Sum or Average | 1946606.43 | |||
Minimum of Months | 0.00 | 0.00 | 10.47 | |
Maximum of Months | 1024263.72 | 397.67 | 27.80 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.962539E+10 | 9271.23 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.869085E+10 | 9271.23 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.965507E+10 | 9271.23 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.929905E+10 | 9271.23 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.964208E+10 | 9271.23 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.934170E+10 | 9271.23 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.959943E+10 | 9271.23 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.965878E+10 | 9271.23 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.930276E+10 | 9271.23 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.962169E+10 | 9271.23 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.933428E+10 | 9271.23 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.959943E+10 | 9271.23 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.113371E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.869085E+10 | 9271.23 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.965878E+10 | 9271.23 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.531884E+09 | 512.31 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.480243E+09 | 512.31 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.533523E+09 | 512.31 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.513850E+09 | 512.31 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.532806E+09 | 512.31 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.516207E+09 | 512.31 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.530449E+09 | 512.31 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.533728E+09 | 512.31 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.514055E+09 | 512.31 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.531679E+09 | 512.31 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.515797E+09 | 512.31 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.530449E+09 | 512.31 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.626467E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.480243E+09 | 512.31 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.533728E+09 | 512.31 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.615923E+09 | 593.26 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.556123E+09 | 593.26 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.617822E+09 | 593.26 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.595041E+09 | 593.26 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.616991E+09 | 593.26 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.597770E+09 | 593.26 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.614262E+09 | 593.26 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.618059E+09 | 593.26 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.595278E+09 | 593.26 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.615686E+09 | 593.26 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.597295E+09 | 593.26 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.614262E+09 | 593.26 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.725451E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.556123E+09 | 593.26 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.618059E+09 | 593.26 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.158446E+09 | 152.61 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.143062E+09 | 152.61 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.158934E+09 | 152.61 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.153074E+09 | 152.61 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.158720E+09 | 152.61 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.153776E+09 | 152.61 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.158018E+09 | 152.61 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.158995E+09 | 152.61 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.153135E+09 | 152.61 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.158385E+09 | 152.61 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.153654E+09 | 152.61 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.158018E+09 | 152.61 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.186622E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.143062E+09 | 152.61 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.158995E+09 | 152.61 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.415991E+09 | 400.68 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.375602E+09 | 400.68 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.417273E+09 | 400.68 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.401887E+09 | 400.68 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.416712E+09 | 400.68 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.403730E+09 | 400.68 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.414869E+09 | 400.68 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.417433E+09 | 400.68 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.402047E+09 | 400.68 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.415830E+09 | 400.68 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.403409E+09 | 400.68 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.414869E+09 | 400.68 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.489965E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.375602E+09 | 400.68 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.417433E+09 | 400.68 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.119845E+10 | 1573.46 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.105631E+10 | 1573.46 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.111343E+10 | 1573.46 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.103916E+10 | 1573.46 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.104182E+10 | 1573.46 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.101118E+10 | 1573.46 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.100291E+10 | 1573.46 | 03-JUL-19:19 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.106100E+10 | 1573.46 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.107435E+10 | 1573.46 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.115798E+10 | 1573.46 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.113734E+10 | 1573.46 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.120647E+10 | 1573.46 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.131004E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.100291E+10 | 1573.46 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.120647E+10 | 1573.46 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105373E+11 | 10645.38 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.948960E+10 | 10645.38 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.104884E+11 | 10645.38 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.100674E+11 | 10645.38 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.104142E+11 | 10645.38 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.101005E+11 | 10645.38 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.103277E+11 | 10645.38 | 03-JUL-19:19 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.104388E+11 | 10645.38 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.101071E+11 | 10645.38 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.104973E+11 | 10645.38 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.101918E+11 | 10645.38 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.105263E+11 | 10645.38 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.123187E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.948960E+10 | 10645.38 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.105373E+11 | 10645.38 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82476868.03 | 74.62 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 74484663.28 | 74.62 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 81821381.83 | 74.62 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 79911301.67 | 74.62 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 82149124.93 | 74.62 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 79277307.08 | 74.62 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 82793865.32 | 74.62 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 81821381.83 | 74.62 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 79932793.28 | 74.62 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 82466122.22 | 74.62 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 79594304.38 | 74.62 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 82804611.13 | 74.62 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.969534E+09 | 0.300992E+10 | ||||
Minimum of Months | 74484663.28 | 74.62 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 82804611.13 | 74.62 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82499421.18 | 74.64 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 74505030.97 | 74.64 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 81843755.73 | 74.64 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 79933153.27 | 74.64 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 82171588.45 | 74.64 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 79298985.31 | 74.64 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 82816505.16 | 74.64 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 81843755.73 | 74.64 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 79954650.76 | 74.64 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 82488672.43 | 74.64 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 79616069.29 | 74.64 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 82827253.90 | 74.64 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.969799E+09 | 0.301074E+10 | ||||
Minimum of Months | 74505030.97 | 74.64 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 82827253.90 | 74.64 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.120431E+10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.108739E+10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.120803E+10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.116348E+10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.120640E+10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.116882E+10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.120107E+10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.120849E+10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.116395E+10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.120385E+10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.116789E+10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.120107E+10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.141847E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.108739E+10 | 1160.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120849E+10 | 1160.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82499421.18 | 74.64 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 74505030.97 | 74.64 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 81843755.73 | 74.64 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 79933153.27 | 74.64 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 82171588.45 | 74.64 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 79298985.31 | 74.64 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 82816505.16 | 74.64 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 81843755.73 | 74.64 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 79954650.76 | 74.64 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 82488672.43 | 74.64 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 79616069.29 | 74.64 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 82827253.90 | 74.64 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.969799E+09 | 0.301074E+10 | ||||
Minimum of Months | 74505030.97 | 74.64 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 82827253.90 | 74.64 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.254928E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.226088E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.244329E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.229329E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.232739E+10 | 2763.12 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.223813E+10 | 2763.12 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.228349E+10 | 2763.12 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.235988E+10 | 2763.12 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.233627E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.248195E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.243202E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.253532E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.285412E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.223813E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.254928E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.254928E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.226088E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.244329E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.229329E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.232739E+10 | 2763.12 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.223813E+10 | 2763.12 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.228349E+10 | 2763.12 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.235988E+10 | 2763.12 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.233627E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.248195E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.243202E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.253532E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.285412E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.223813E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.254928E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113250E+10 | 1090.83 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.102255E+10 | 1090.83 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.113599E+10 | 1090.83 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.109410E+10 | 1090.83 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.113446E+10 | 1090.83 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.109912E+10 | 1090.83 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.112945E+10 | 1090.83 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.113643E+10 | 1090.83 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.109454E+10 | 1090.83 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.113207E+10 | 1090.83 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.109825E+10 | 1090.83 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.112945E+10 | 1090.83 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.133389E+11 | 0.424019E+12 | ||||
Minimum of Months | 0.102255E+10 | 1090.83 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.113643E+10 | 1090.83 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.127458E+10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.115083E+10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.127851E+10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.123137E+10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.127679E+10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.123701E+10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.127114E+10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.127900E+10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.123186E+10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.127409E+10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.123603E+10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.127114E+10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.150123E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.115083E+10 | 1227.68 | 0.00 | 0.00 | |
Maximum of Months | 0.127900E+10 | 1227.68 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.962539E+10 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.869085E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.965507E+10 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.929905E+10 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.964208E+10 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.934170E+10 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.959943E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.965878E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.930276E+10 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.962169E+10 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.933428E+10 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.959943E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.113371E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.869085E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.965878E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.531884E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2126920.99 | 30599485.77 |
February | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3248047.47 | 19481679.95 |
March | 0.199990E+10 | 0.533523E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4232617.27 | 16635580.12 |
April | 0.192973E+10 | 0.513850E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10484184.37 | 4345320.38 |
May | 0.199475E+10 | 0.532806E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23164293.23 | 419030.08 |
June | 0.193394E+10 | 0.516207E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30308599.77 | 7685.68 |
July | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33777851.49 | 105791.60 |
August | 0.199896E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33287640.09 | 26475.58 |
September | 0.192879E+10 | 0.514055E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27742898.61 | 37773.13 |
October | 0.199148E+10 | 0.531679E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20770563.58 | 540102.75 |
November | 0.192552E+10 | 0.515797E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10307672.18 | 9475639.06 |
December | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3000720.59 | 25313842.26 |
Annual Sum or Average | 0.234744E+11 | 0.626467E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202452E+09 | 0.106988E+09 |
Minimum of Months | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2126920.99 | 7685.68 |
Maximum of Months | 0.199990E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33777851.49 | 30599485.77 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.615923E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1175959.88 | 13006195.62 |
February | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1788665.70 | 8636207.43 |
March | 0.231589E+10 | 0.617822E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2075531.41 | 7577177.82 |
April | 0.223463E+10 | 0.595041E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4381175.22 | 2518771.89 |
May | 0.230993E+10 | 0.616991E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8943177.40 | 351615.71 |
June | 0.223950E+10 | 0.597770E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11803890.99 | 9247.99 |
July | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13349488.73 | 97048.09 |
August | 0.231480E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13015416.81 | 40123.72 |
September | 0.223354E+10 | 0.595278E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11035619.74 | 72231.11 |
October | 0.230614E+10 | 0.615686E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8429880.05 | 398239.14 |
November | 0.222975E+10 | 0.597295E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4491303.39 | 4357059.68 |
December | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1537648.17 | 10948678.79 |
Annual Sum or Average | 0.271834E+11 | 0.725451E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82027757.51 | 48012596.98 |
Minimum of Months | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1175959.88 | 9247.99 |
Maximum of Months | 0.231589E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13349488.73 | 13006195.62 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3405169.15 | 27109298.58 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4968903.11 | 17703264.58 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5798336.09 | 15103200.06 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11052618.17 | 4478870.88 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21226646.78 | 658349.62 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27015028.89 | 22262.12 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30604910.12 | 224910.57 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30486755.66 | 102954.34 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25711792.60 | 125934.95 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20424943.93 | 665621.72 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11414030.55 | 9225334.62 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4173127.74 | 22937070.24 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196282E+09 | 98357072.28 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3405169.15 | 22262.12 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30604910.12 | 27109298.58 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.158446E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1999235.71 | 15225690.44 |
February | 0.339028E+09 | 0.143062E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2931030.95 | 9866886.18 |
March | 0.376747E+09 | 0.158934E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3490705.85 | 8390945.20 |
April | 0.363528E+09 | 0.153074E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6607140.20 | 2355112.42 |
May | 0.375778E+09 | 0.158720E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12642555.07 | 338461.52 |
June | 0.364321E+09 | 0.153776E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15868549.80 | 8047.25 |
July | 0.374985E+09 | 0.158018E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17817992.93 | 109518.73 |
August | 0.376571E+09 | 0.158995E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17864049.08 | 46952.88 |
September | 0.363352E+09 | 0.153135E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15089909.44 | 50305.94 |
October | 0.375161E+09 | 0.158385E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12150677.54 | 332745.64 |
November | 0.362735E+09 | 0.153654E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6815339.07 | 5088189.85 |
December | 0.374985E+09 | 0.158018E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2487759.08 | 12833062.89 |
Annual Sum or Average | 0.442217E+10 | 0.186622E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115765E+09 | 54645918.92 |
Minimum of Months | 0.339028E+09 | 0.143062E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1999235.71 | 8047.25 |
Maximum of Months | 0.376747E+09 | 0.158995E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17864049.08 | 15225690.44 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.415991E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 5363993.48 | 39038492.95 |
February | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 8310544.68 | 25644633.50 |
March | 0.155131E+10 | 0.417273E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 9831863.11 | 21965235.84 |
April | 0.149688E+10 | 0.401887E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 18510652.39 | 5498015.76 |
May | 0.154732E+10 | 0.416712E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 36186543.12 | 472026.71 |
June | 0.150015E+10 | 0.403730E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 46448448.03 | 24088.72 |
July | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 52335723.88 | 130612.78 |
August | 0.155059E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 50940870.18 | 96325.83 |
September | 0.149615E+10 | 0.402047E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 44665104.07 | 131190.95 |
October | 0.154478E+10 | 0.415830E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 35581191.30 | 477303.09 |
November | 0.149361E+10 | 0.403409E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 19261601.45 | 11631114.80 |
December | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 7698558.79 | 32505609.77 |
Annual Sum or Average | 0.182090E+11 | 0.489965E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.335135E+09 | 0.137615E+09 |
Minimum of Months | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 5363993.48 | 24088.72 |
Maximum of Months | 0.155131E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 52335723.88 | 39038492.95 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.119845E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4612328.01 | 80140368.72 |
February | 0.236489E+11 | 0.105631E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7184495.00 | 52567121.47 |
March | 0.262800E+11 | 0.111343E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9693372.15 | 45673413.46 |
April | 0.253579E+11 | 0.103916E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23861082.23 | 15017641.13 |
May | 0.262123E+11 | 0.104182E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51290218.70 | 2285791.50 |
June | 0.254132E+11 | 0.101118E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68079189.69 | 81371.14 |
July | 0.261570E+11 | 0.100291E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76546671.10 | 556481.31 |
August | 0.262677E+11 | 0.106100E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73904366.64 | 195284.40 |
September | 0.253456E+11 | 0.107435E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61429880.27 | 471490.14 |
October | 0.261693E+11 | 0.115798E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45147131.16 | 2371800.47 |
November | 0.253025E+11 | 0.113734E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22261425.79 | 26238684.38 |
December | 0.261570E+11 | 0.120647E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6631802.52 | 67232872.50 |
Annual Sum or Average | 0.308468E+12 | 0.131004E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450642E+09 | 0.292832E+09 |
Minimum of Months | 0.236489E+11 | 0.100291E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4612328.01 | 81371.14 |
Maximum of Months | 0.262800E+11 | 0.120647E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76546671.10 | 80140368.72 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.105373E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16536849.16 | 0.228524E+09 |
February | 0.702046E+11 | 0.948960E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25977139.60 | 0.151699E+09 |
March | 0.780153E+11 | 0.104884E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31888706.37 | 0.132346E+09 |
April | 0.752779E+11 | 0.100674E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71069369.95 | 45229540.92 |
May | 0.778146E+11 | 0.104142E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145353E+09 | 7005176.60 |
June | 0.754422E+11 | 0.101005E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192691E+09 | 261785.60 |
July | 0.776503E+11 | 0.103277E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219468E+09 | 1709114.07 |
August | 0.779788E+11 | 0.104388E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212161E+09 | 806968.76 |
September | 0.752414E+11 | 0.101071E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179534E+09 | 1468799.56 |
October | 0.776868E+11 | 0.104973E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134651E+09 | 7158972.03 |
November | 0.751137E+11 | 0.101918E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69367364.28 | 76622082.95 |
December | 0.776503E+11 | 0.105263E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22515172.97 | 0.192447E+09 |
Annual Sum or Average | 0.915726E+12 | 0.123187E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132121E+10 | 0.845277E+09 |
Minimum of Months | 0.702046E+11 | 0.948960E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16536849.16 | 261785.60 |
Maximum of Months | 0.780153E+11 | 0.105373E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219468E+09 | 0.228524E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2943910.53 | 13908747.39 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4513735.68 | 8423152.66 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6426254.50 | 7502410.35 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11227209.61 | 980176.33 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20987318.10 | 44908.22 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25787891.08 | 2451.02 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28570082.28 | 5808.61 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27935940.39 | 25288.89 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24883568.99 | 0.00 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20611829.70 | 16118.75 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11329224.18 | 3452275.35 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4394241.78 | 11334940.00 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189611E+09 | 45696277.58 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2943910.53 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28570082.28 | 13908747.39 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2471900.96 | 14949816.74 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3679923.78 | 9602348.20 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5192913.90 | 8769280.04 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9918045.48 | 1982830.81 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20478753.50 | 123791.26 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25556557.43 | 14713.24 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28300285.57 | 110344.57 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27786656.95 | 41333.70 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24561307.08 | 27768.16 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20214562.84 | 80179.13 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10899183.70 | 4097386.85 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3811666.99 | 12292754.48 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182872E+09 | 52092547.17 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2471900.96 | 14713.24 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28300285.57 | 14949816.74 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 82476868.03 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18080.90 | 9550189.90 |
February | 0.00 | 74484663.28 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32407.39 | 6922039.43 |
March | 0.00 | 81821381.83 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47161.88 | 6751449.72 |
April | 0.00 | 79911301.67 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 333677.03 | 3585165.16 |
May | 0.00 | 82149124.93 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1066308.64 | 1469353.89 |
June | 0.00 | 79277307.08 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1747085.72 | 576865.69 |
July | 0.00 | 82793865.32 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2374411.33 | 620083.94 |
August | 0.00 | 81821381.83 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2121687.71 | 550912.67 |
September | 0.00 | 79932793.28 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1844677.83 | 915679.52 |
October | 0.00 | 82466122.22 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 944723.95 | 1428955.11 |
November | 0.00 | 79594304.38 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 178067.52 | 4103667.32 |
December | 0.00 | 82804611.13 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28330.87 | 8428072.58 |
Annual Sum or Average | 0.00 | 0.969534E+09 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10736620.77 | 44902434.93 |
Minimum of Months | 0.00 | 74484663.28 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18080.90 | 550912.67 |
Maximum of Months | 0.00 | 82804611.13 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2374411.33 | 9550189.90 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 82499421.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 727488.34 | 4084769.98 |
February | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1079284.53 | 2611367.97 |
March | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1506956.93 | 2272394.22 |
April | 0.293479E+09 | 79933153.27 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2832811.00 | 440386.09 |
May | 0.303504E+09 | 82171588.45 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5760842.52 | 26379.71 |
June | 0.293842E+09 | 79298985.31 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7167512.01 | 1097.69 |
July | 0.303141E+09 | 82816505.16 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7930007.91 | 19327.55 |
August | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7798179.54 | 8338.82 |
September | 0.293479E+09 | 79954650.76 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6898863.71 | 2934.56 |
October | 0.303322E+09 | 82488672.43 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5708139.91 | 15221.88 |
November | 0.293661E+09 | 79616069.29 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3098788.87 | 1115114.65 |
December | 0.303141E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1107473.17 | 3372480.67 |
Annual Sum or Average | 0.357224E+10 | 0.969799E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51616348.45 | 13969813.77 |
Minimum of Months | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 727488.34 | 1097.69 |
Maximum of Months | 0.303685E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7930007.91 | 4084769.98 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2927976.45 | 14025176.99 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4503508.35 | 8526826.12 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6405477.01 | 7644746.95 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11193664.49 | 1009230.61 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20946123.68 | 46470.08 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25740418.42 | 2449.94 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28532022.82 | 6000.86 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27908526.78 | 25563.32 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24847995.80 | 0.00 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20581868.24 | 18156.25 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11309472.56 | 3493067.95 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4387665.54 | 11381510.02 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189285E+09 | 46179199.07 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2927976.45 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28532022.82 | 14025176.99 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2392071.69 | 15163604.64 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3613203.32 | 9807280.98 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5140658.79 | 8865554.28 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9829373.17 | 2136973.83 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20403957.78 | 180182.29 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25496898.49 | 27091.81 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28252677.81 | 125369.45 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27757142.26 | 41364.25 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24495856.78 | 52356.18 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20114183.36 | 129839.57 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10800198.43 | 4293375.22 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3783055.38 | 12164128.41 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182079E+09 | 52987120.90 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2392071.69 | 27091.81 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28252677.81 | 15163604.64 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.120431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2247344.16 | 21525489.45 |
February | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3414319.58 | 13860234.04 |
March | 0.387034E+10 | 0.120803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3956215.57 | 12211044.35 |
April | 0.373454E+10 | 0.116348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7817229.74 | 3796469.58 |
May | 0.386038E+10 | 0.120640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16478691.32 | 503790.18 |
June | 0.374269E+10 | 0.116882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21059501.13 | 13537.92 |
July | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23646310.51 | 163391.92 |
August | 0.386853E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23279746.56 | 76435.95 |
September | 0.373273E+10 | 0.116395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19605780.66 | 88702.61 |
October | 0.385404E+10 | 0.120385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14944192.87 | 616033.64 |
November | 0.372639E+10 | 0.116789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8371798.90 | 7323903.34 |
December | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2963507.00 | 17911279.43 |
Annual Sum or Average | 0.454292E+11 | 0.141847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147785E+09 | 78090312.40 |
Minimum of Months | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2247344.16 | 13537.92 |
Maximum of Months | 0.387034E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23646310.51 | 21525489.45 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2861474.43 | 14001625.08 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4393338.91 | 8479310.80 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6258809.83 | 7539737.00 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11001590.83 | 1000596.91 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20724082.55 | 48758.82 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25530797.47 | 2940.81 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28301524.36 | 6525.88 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27674932.99 | 25896.66 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24631912.95 | 0.00 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20358639.61 | 16277.93 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11144975.23 | 3479477.42 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4287337.00 | 11395684.06 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187169E+09 | 45996831.37 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2861474.43 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28301524.36 | 14001625.08 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2433842.42 | 14800019.64 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3602655.39 | 9544953.78 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5072566.72 | 8778773.73 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9746027.14 | 1983469.66 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20238827.78 | 120149.75 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25306840.25 | 19424.62 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28046933.06 | 125485.49 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27531883.88 | 40653.32 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24335348.32 | 25718.31 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20009499.86 | 58100.26 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10758711.51 | 3988473.28 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3751520.91 | 12079509.61 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180835E+09 | 51564731.46 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2433842.42 | 19424.62 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28046933.06 | 14800019.64 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 82499421.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1433331.94 | 7300266.89 |
February | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2219276.92 | 4417717.56 |
March | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3183919.70 | 3919569.77 |
April | 0.293479E+09 | 79933153.27 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5624176.84 | 512523.34 |
May | 0.303504E+09 | 82171588.45 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10607473.06 | 24801.28 |
June | 0.293842E+09 | 79298985.31 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13062616.93 | 1504.07 |
July | 0.303141E+09 | 82816505.16 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14480832.32 | 3192.49 |
August | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14153197.97 | 13166.90 |
September | 0.293479E+09 | 79954650.76 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12574503.63 | 0.00 |
October | 0.303322E+09 | 82488672.43 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10362912.18 | 9468.56 |
November | 0.293661E+09 | 79616069.29 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5658930.71 | 1821189.66 |
December | 0.303141E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2161593.37 | 5958276.29 |
Annual Sum or Average | 0.357224E+10 | 0.969799E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95522765.59 | 23981676.82 |
Minimum of Months | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1433331.94 | 0.00 |
Maximum of Months | 0.303685E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14480832.32 | 7300266.89 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.254928E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3151026.08 | 53540438.73 |
February | 0.415303E+11 | 0.226088E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4825736.96 | 35986276.91 |
March | 0.461508E+11 | 0.244329E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5264456.48 | 31956036.15 |
April | 0.445315E+11 | 0.229329E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12618079.94 | 11386122.56 |
May | 0.460320E+11 | 0.232739E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28239394.77 | 1885680.77 |
June | 0.446286E+11 | 0.223813E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38967773.06 | 132177.16 |
July | 0.459349E+11 | 0.228349E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45201212.43 | 510778.67 |
August | 0.461292E+11 | 0.235988E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43711600.36 | 312604.57 |
September | 0.445099E+11 | 0.233627E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37263578.28 | 449601.63 |
October | 0.459565E+11 | 0.248195E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27786610.69 | 1840053.46 |
November | 0.444343E+11 | 0.243202E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14086993.12 | 18159483.98 |
December | 0.459349E+11 | 0.253532E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4433279.11 | 45180518.00 |
Annual Sum or Average | 0.541708E+12 | 0.285412E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265550E+09 | 0.201340E+09 |
Minimum of Months | 0.415303E+11 | 0.223813E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3151026.08 | 132177.16 |
Maximum of Months | 0.461508E+11 | 0.254928E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45201212.43 | 53540438.73 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.254928E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2834336.76 | 54364011.20 |
February | 0.415303E+11 | 0.226088E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4383413.52 | 36470867.66 |
March | 0.461508E+11 | 0.244329E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4864304.38 | 32440111.36 |
April | 0.445315E+11 | 0.229329E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12190397.81 | 11470695.71 |
May | 0.460320E+11 | 0.232739E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27890723.47 | 1899721.20 |
June | 0.446286E+11 | 0.223813E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38716427.71 | 133400.25 |
July | 0.459349E+11 | 0.228349E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45013797.15 | 515373.32 |
August | 0.461292E+11 | 0.235988E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43445366.10 | 338177.92 |
September | 0.445099E+11 | 0.233627E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36993588.98 | 451034.42 |
October | 0.459565E+11 | 0.248195E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27405319.31 | 1845956.89 |
November | 0.444343E+11 | 0.243202E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13661749.50 | 18353807.26 |
December | 0.459349E+11 | 0.253532E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4118749.56 | 45878402.12 |
Annual Sum or Average | 0.541708E+12 | 0.285412E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261518E+09 | 0.204162E+09 |
Minimum of Months | 0.415303E+11 | 0.223813E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2834336.76 | 133400.25 |
Maximum of Months | 0.461508E+11 | 0.254928E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45013797.15 | 54364011.20 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113250E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 2053537.47 | 48070645.68 |
February | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 3188749.46 | 31555530.27 |
March | 0.410691E+10 | 0.113599E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3788971.32 | 28228183.56 |
April | 0.396281E+10 | 0.109410E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 10394091.55 | 9204976.63 |
May | 0.409635E+10 | 0.113446E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 25146430.13 | 1315079.90 |
June | 0.397146E+10 | 0.109912E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 35056147.67 | 100694.80 |
July | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 40713564.57 | 348523.03 |
August | 0.410499E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 39339810.80 | 328953.74 |
September | 0.396089E+10 | 0.109454E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 33369383.75 | 279920.49 |
October | 0.408962E+10 | 0.113207E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 24444671.89 | 1275095.75 |
November | 0.395417E+10 | 0.109825E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 11715929.89 | 15642046.37 |
December | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3149736.19 | 40438136.87 |
Annual Sum or Average | 0.482060E+11 | 0.133389E+11 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.232361E+09 | 0.176788E+09 |
Minimum of Months | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 2053537.47 | 100694.80 |
Maximum of Months | 0.410691E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 40713564.57 | 48070645.68 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.127458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3962872.81 | 34953447.78 |
February | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5752261.13 | 22611426.26 |
March | 0.409620E+10 | 0.127851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6647560.21 | 19743606.49 |
April | 0.395248E+10 | 0.123137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12888633.78 | 5996194.76 |
May | 0.408566E+10 | 0.127679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27101885.89 | 803080.10 |
June | 0.396110E+10 | 0.123701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35209856.11 | 31274.63 |
July | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40281447.30 | 274922.72 |
August | 0.409429E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39706166.66 | 120357.13 |
September | 0.395056E+10 | 0.123186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33570433.98 | 93157.33 |
October | 0.407896E+10 | 0.127409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25876526.84 | 795612.66 |
November | 0.394385E+10 | 0.123603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14430869.31 | 11533060.46 |
December | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5012767.51 | 28997887.85 |
Annual Sum or Average | 0.480803E+11 | 0.150123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250441E+09 | 0.125954E+09 |
Minimum of Months | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3962872.81 | 31274.63 |
Maximum of Months | 0.409620E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40281447.30 | 34953447.78 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 9271.23 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 9271.23 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 9271.23 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 9271.23 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 9271.23 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 9271.23 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 9271.23 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 9271.23 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 9271.23 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 9271.23 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 9271.23 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 9271.23 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 512.31 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.24 | 02-JAN-14:00 | 37.10 | 25-JAN-05:20 |
February | 1169.53 | 01-FEB-00:10 | 512.31 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 11-FEB-14:00 | 50.74 | 04-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 512.31 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.53 | 13-MAR-16:00 | 44.86 | 16-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 512.31 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.36 | 17-APR-15:00 | 24.02 | 02-APR-05:20 |
May | 1169.53 | 01-MAY-00:10 | 512.31 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.48 | 22-MAY-13:00 | 6.50 | 07-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 512.31 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.53 | 11-JUN-13:00 | 2.08 | 05-JUN-22:00 |
July | 1169.53 | 01-JUL-00:10 | 512.31 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.70 | 29-JUL-16:00 | 3.56 | 14-JUL-21:51 |
August | 1169.53 | 01-AUG-00:10 | 512.31 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.24 | 23-AUG-13:00 | 1.90 | 12-AUG-07:00 |
September | 1169.53 | 01-SEP-00:10 | 512.31 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.46 | 13-SEP-13:00 | 3.56 | 02-SEP-22:00 |
October | 1169.53 | 01-OCT-23:10 | 512.31 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.46 | 09-OCT-10:55 | 6.82 | 26-OCT-14:00 |
November | 1169.53 | 01-NOV-00:10 | 512.31 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.28 | 17-NOV-15:00 | 36.79 | 27-NOV-03:00 |
December | 1169.53 | 01-DEC-00:10 | 512.31 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.11 | 10-DEC-14:00 | 42.56 | 15-DEC-05:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 14.11 | 1.90 | |||||
Maximum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 32.70 | 50.74 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 593.26 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.79 | 02-JAN-14:30 | 16.44 | 25-JAN-05:30 |
February | 1354.32 | 01-FEB-00:10 | 593.26 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 | 11-FEB-14:00 | 21.52 | 04-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 593.26 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.03 | 13-MAR-16:00 | 19.77 | 16-MAR-05:00 |
April | 1354.32 | 01-APR-00:10 | 593.26 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.98 | 17-APR-15:00 | 10.76 | 02-APR-05:30 |
May | 1354.32 | 01-MAY-00:10 | 593.26 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.48 | 22-MAY-13:00 | 3.58 | 07-MAY-05:50 |
June | 1354.32 | 01-JUN-00:10 | 593.26 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.95 | 11-JUN-13:00 | 0.80 | 05-JUN-22:00 |
July | 1354.32 | 01-JUL-00:10 | 593.26 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.35 | 29-JUL-16:00 | 1.38 | 14-JUL-21:52 |
August | 1354.32 | 01-AUG-00:10 | 593.26 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.70 | 23-AUG-13:00 | 1.53 | 12-AUG-07:00 |
September | 1354.32 | 01-SEP-00:10 | 593.26 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.94 | 13-SEP-13:00 | 1.93 | 05-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 593.26 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.90 | 14-OCT-13:00 | 2.88 | 28-OCT-03:00 |
November | 1354.32 | 01-NOV-00:10 | 593.26 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.47 | 17-NOV-15:00 | 15.94 | 27-NOV-03:00 |
December | 1354.32 | 01-DEC-00:10 | 593.26 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.36 | 10-DEC-14:40 | 18.58 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 6.36 | 0.80 | |||||
Maximum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 13.35 | 21.52 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.47 | 02-JAN-14:30 | 36.14 | 25-JAN-07:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.25 | 11-FEB-14:00 | 49.06 | 04-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.84 | 13-MAR-16:00 | 44.51 | 16-MAR-06:40 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.57 | 17-APR-15:00 | 23.94 | 02-APR-05:40 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.59 | 22-MAY-13:00 | 7.75 | 07-MAY-05:50 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.37 | 11-JUN-13:00 | 2.02 | 05-JUN-15:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.59 | 29-JUL-16:00 | 3.26 | 14-JUL-21:52 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 | 23-AUG-13:00 | 3.66 | 12-AUG-07:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.79 | 08-SEP-16:00 | 4.14 | 05-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.32 | 14-OCT-13:00 | 5.94 | 28-OCT-03:00 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.26 | 17-NOV-15:00 | 35.93 | 27-NOV-07:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.12 | 10-DEC-14:40 | 41.70 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 15.12 | 2.02 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 30.59 | 49.06 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 152.61 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.42 | 02-JAN-14:30 | 20.55 | 25-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 152.61 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.86 | 11-FEB-14:00 | 27.98 | 04-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 152.61 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.21 | 13-MAR-16:00 | 25.26 | 16-MAR-05:40 |
April | 220.32 | 01-APR-00:10 | 152.61 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.54 | 17-APR-15:00 | 13.53 | 02-APR-05:20 |
May | 220.32 | 01-MAY-00:10 | 152.61 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.46 | 22-MAY-13:00 | 4.23 | 07-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 152.61 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.89 | 11-JUN-13:00 | 1.04 | 05-JUN-15:00 |
July | 220.32 | 01-JUL-00:10 | 152.61 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.54 | 29-JUL-16:00 | 1.88 | 14-JUL-21:52 |
August | 220.32 | 01-AUG-00:10 | 152.61 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.36 | 23-AUG-13:00 | 1.94 | 12-AUG-07:00 |
September | 220.32 | 01-SEP-00:10 | 152.61 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.10 | 08-SEP-16:00 | 2.13 | 05-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 152.61 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.36 | 14-OCT-13:00 | 3.33 | 28-OCT-03:00 |
November | 220.32 | 01-NOV-00:10 | 152.61 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.49 | 17-NOV-15:00 | 20.53 | 27-NOV-03:00 |
December | 220.32 | 01-DEC-00:10 | 152.61 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 10-DEC-14:40 | 23.72 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 1.04 | |||||
Maximum of Months | 220.32 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 17.54 | 27.98 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 400.68 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 27.51 | 02-JAN-14:30 | 56.11 | 25-JAN-07:10 |
February | 907.20 | 01-FEB-00:10 | 400.68 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 28.69 | 11-FEB-14:00 | 69.15 | 04-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 400.68 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 28.37 | 13-MAR-16:00 | 67.59 | 16-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 400.68 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 37.40 | 15-APR-17:00 | 34.56 | 02-APR-06:10 |
May | 907.20 | 01-MAY-00:10 | 400.68 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 43.89 | 22-MAY-13:00 | 12.43 | 01-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 400.68 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 38.05 | 11-JUN-13:00 | 2.59 | 15-JUN-08:00 |
July | 907.20 | 01-JUL-00:10 | 400.68 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 50.46 | 29-JUL-16:00 | 4.49 | 14-JUL-19:20 |
August | 907.20 | 01-AUG-00:10 | 400.68 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 42.27 | 06-AUG-13:00 | 6.67 | 12-AUG-08:57 |
September | 907.20 | 01-SEP-00:10 | 400.68 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 38.48 | 08-SEP-16:00 | 6.59 | 05-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 400.68 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 37.03 | 07-OCT-10:50 | 8.46 | 31-OCT-06:00 |
November | 907.20 | 01-NOV-00:10 | 400.68 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 27.55 | 10-NOV-14:00 | 53.26 | 27-NOV-07:00 |
December | 907.20 | 01-DEC-00:10 | 400.68 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 27.74 | 10-DEC-14:40 | 62.76 | 15-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 27.51 | 2.59 | ||||||
Maximum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 50.46 | 69.15 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1573.46 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.47 | 02-JAN-14:00 | 97.92 | 25-JAN-05:20 |
February | 15368.40 | 01-FEB-00:10 | 1573.46 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.66 | 11-FEB-14:00 | 122.05 | 04-FEB-06:00 |
March | 15368.40 | 01-MAR-00:10 | 1573.46 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.34 | 13-MAR-16:00 | 115.10 | 16-MAR-05:00 |
April | 15368.40 | 01-APR-00:10 | 1573.46 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.17 | 17-APR-15:00 | 60.79 | 02-APR-05:20 |
May | 15368.40 | 01-MAY-00:10 | 1573.46 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.33 | 22-MAY-13:00 | 22.39 | 01-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 1573.46 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.84 | 11-JUN-13:00 | 4.57 | 14-JUN-05:55 |
July | 15368.40 | 01-JUL-00:10 | 1573.46 | 03-JUL-19:19 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.30 | 29-JUL-16:00 | 7.89 | 14-JUL-21:55 |
August | 15368.40 | 01-AUG-00:10 | 1573.46 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.36 | 08-AUG-10:55 | 7.86 | 14-AUG-03:00 |
September | 15368.40 | 01-SEP-00:10 | 1573.46 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.51 | 14-SEP-10:55 | 11.75 | 05-SEP-06:00 |
October | 15368.40 | 01-OCT-23:10 | 1573.46 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.87 | 09-OCT-10:55 | 19.00 | 28-OCT-03:10 |
November | 15368.40 | 01-NOV-00:10 | 1573.46 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.21 | 17-NOV-15:00 | 94.61 | 27-NOV-03:00 |
December | 15368.40 | 01-DEC-00:10 | 1573.46 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.21 | 10-DEC-14:00 | 109.53 | 15-DEC-05:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 31.21 | 4.57 | |||||
Maximum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 74.30 | 122.05 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 10645.38 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.76 | 02-JAN-14:30 | 282.71 | 25-JAN-05:40 |
February | 45622.98 | 01-FEB-00:10 | 10645.38 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.54 | 11-FEB-14:00 | 364.06 | 04-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 10645.38 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.61 | 13-MAR-16:00 | 335.46 | 16-MAR-05:00 |
April | 45622.98 | 01-APR-00:10 | 10645.38 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.82 | 17-APR-15:00 | 180.54 | 02-APR-05:40 |
May | 45622.98 | 01-MAY-00:10 | 10645.38 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.56 | 22-MAY-13:00 | 64.01 | 01-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 10645.38 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.40 | 11-JUN-13:00 | 13.10 | 05-JUN-22:00 |
July | 45622.98 | 01-JUL-00:10 | 10645.38 | 03-JUL-19:19 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.90 | 29-JUL-16:00 | 22.55 | 14-JUL-21:52 |
August | 45622.98 | 01-AUG-00:10 | 10645.38 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.84 | 23-AUG-13:00 | 28.22 | 12-AUG-07:00 |
September | 45622.98 | 01-SEP-00:10 | 10645.38 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.42 | 13-SEP-13:00 | 33.60 | 05-SEP-06:00 |
October | 45622.98 | 01-OCT-23:10 | 10645.38 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.36 | 09-OCT-10:55 | 54.32 | 28-OCT-03:10 |
November | 45622.98 | 01-NOV-00:10 | 10645.38 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.54 | 17-NOV-15:00 | 272.35 | 27-NOV-05:40 |
December | 45622.98 | 01-DEC-00:10 | 10645.38 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.21 | 10-DEC-14:40 | 317.37 | 15-DEC-05:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 10645.38 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 99.21 | 13.10 | |||||
Maximum of Months | 45622.98 | 10645.38 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 220.90 | 364.06 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.43 | 01-JAN-11:00 | 21.26 | 25-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.05 | 11-FEB-16:10 | 29.73 | 04-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.76 | 13-MAR-16:00 | 26.32 | 16-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.13 | 17-APR-15:10 | 11.93 | 02-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.01 | 29-MAY-16:00 | 2.89 | 10-MAY-15:00 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 | 10-JUN-16:00 | 0.99 | 05-JUN-15:00 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.63 | 29-JUL-16:00 | 1.00 | 14-JUL-17:50 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.34 | 21-AUG-16:00 | 2.04 | 28-AUG-12:00 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.34 | 20-SEP-16:00 | 0.00 | 01-SEP-00:05 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.48 | 14-OCT-16:00 | 2.89 | 26-OCT-14:00 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.38 | 17-NOV-16:10 | 20.05 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 10-DEC-16:10 | 24.30 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 9.43 | 0.00 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 23.63 | 29.73 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.43 | 01-JAN-11:00 | 21.25 | 25-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.09 | 11-FEB-16:10 | 29.73 | 04-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.76 | 13-MAR-16:00 | 26.31 | 16-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.13 | 17-APR-15:10 | 11.93 | 02-APR-05:40 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 29-MAY-16:00 | 3.40 | 07-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 | 10-JUN-16:00 | 1.98 | 21-JUN-17:50 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.63 | 29-JUL-16:00 | 4.74 | 02-JUL-18:00 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.34 | 21-AUG-16:00 | 2.82 | 12-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.34 | 20-SEP-16:00 | 2.37 | 04-SEP-21:50 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.47 | 14-OCT-16:00 | 4.19 | 01-OCT-08:00 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.38 | 17-NOV-16:08 | 20.04 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 10-DEC-16:10 | 24.29 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 9.43 | 1.98 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 23.63 | 29.73 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 74.62 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 | 02-JAN-14:00 | 8.73 | 25-JAN-07:00 |
February | 0.00 | 01-FEB-00:10 | 74.62 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 | 11-FEB-14:00 | 10.52 | 04-FEB-07:00 |
March | 0.00 | 01-MAR-00:10 | 74.62 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 13-MAR-16:00 | 10.17 | 16-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 74.62 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.53 | 17-APR-15:00 | 6.06 | 02-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 74.62 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 | 22-MAY-13:00 | 2.95 | 01-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 74.62 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 | 11-JUN-13:00 | 1.87 | 05-JUN-15:00 |
July | 0.00 | 01-JUL-00:10 | 74.62 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 29-JUL-16:00 | 1.88 | 14-JUL-21:55 |
August | 0.00 | 01-AUG-00:10 | 74.62 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 | 23-AUG-13:00 | 2.17 | 28-AUG-12:00 |
September | 0.00 | 01-SEP-00:10 | 74.62 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.54 | 13-SEP-13:00 | 2.16 | 05-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 74.62 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.54 | 09-OCT-10:55 | 2.69 | 28-OCT-04:00 |
November | 0.00 | 01-NOV-00:10 | 74.62 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 | 17-NOV-15:00 | 8.38 | 27-NOV-07:00 |
December | 0.00 | 01-DEC-00:10 | 74.62 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 | 10-DEC-14:00 | 9.60 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 74.62 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 | 1.87 | |||||
Maximum of Months | 0.00 | 74.62 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 10.52 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 74.64 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.90 | 02-JAN-14:00 | 5.93 | 25-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 74.64 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.10 | 11-FEB-16:10 | 8.30 | 04-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 74.64 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.84 | 13-MAR-16:00 | 7.37 | 16-MAR-07:10 |
April | 180.00 | 01-APR-00:10 | 74.64 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 | 17-APR-15:10 | 3.33 | 02-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 74.64 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 29-MAY-16:00 | 0.99 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 74.64 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 | 10-JUN-16:00 | 0.28 | 05-JUN-15:00 |
July | 180.00 | 01-JUL-00:10 | 74.64 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.60 | 29-JUL-16:00 | 0.95 | 14-JUL-18:00 |
August | 180.00 | 01-AUG-00:10 | 74.64 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.12 | 21-AUG-16:00 | 0.67 | 12-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 74.64 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.12 | 20-SEP-16:00 | 0.40 | 04-SEP-21:50 |
October | 180.00 | 01-OCT-00:10 | 74.64 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.88 | 14-OCT-16:00 | 0.87 | 01-OCT-08:00 |
November | 180.00 | 01-NOV-00:10 | 74.64 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.74 | 17-NOV-16:10 | 5.59 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 74.64 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.26 | 10-DEC-16:10 | 6.78 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2.90 | 0.28 | |||||
Maximum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6.60 | 8.30 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.43 | 01-JAN-11:00 | 22.35 | 25-JAN-08:50 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.09 | 11-FEB-16:10 | 29.73 | 04-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.76 | 13-MAR-16:00 | 27.10 | 16-MAR-07:30 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.13 | 17-APR-15:10 | 11.93 | 02-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 29-MAY-16:00 | 2.89 | 10-MAY-15:00 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 | 10-JUN-16:00 | 0.99 | 05-JUN-15:00 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.63 | 29-JUL-16:00 | 1.00 | 14-JUL-17:50 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.35 | 21-AUG-16:00 | 2.03 | 28-AUG-12:00 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.34 | 20-SEP-16:00 | 0.00 | 01-SEP-00:05 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.48 | 14-OCT-16:00 | 2.89 | 26-OCT-14:00 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.38 | 17-NOV-16:10 | 20.05 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 10-DEC-16:10 | 24.30 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 9.43 | 0.00 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 23.63 | 29.73 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.43 | 01-JAN-11:00 | 21.25 | 25-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.09 | 11-FEB-16:10 | 29.73 | 04-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.76 | 13-MAR-16:00 | 26.76 | 16-MAR-07:30 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.13 | 17-APR-15:10 | 12.00 | 18-APR-08:00 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 29-MAY-16:00 | 4.01 | 01-MAY-07:10 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 | 10-JUN-16:00 | 2.67 | 13-JUN-07:10 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.63 | 29-JUL-16:00 | 5.15 | 14-JUL-18:00 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.34 | 21-AUG-16:00 | 2.81 | 12-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.34 | 20-SEP-16:00 | 3.16 | 26-SEP-07:50 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.47 | 14-OCT-16:00 | 4.49 | 28-OCT-08:00 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.38 | 17-NOV-16:10 | 20.04 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 10-DEC-16:10 | 24.29 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 9.43 | 2.67 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 23.63 | 29.73 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.44 | 02-JAN-14:00 | 28.19 | 25-JAN-05:05 |
February | 2263.36 | 01-FEB-00:10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.68 | 11-FEB-14:00 | 37.73 | 04-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.54 | 13-MAR-16:00 | 34.96 | 16-MAR-05:00 |
April | 2263.36 | 01-APR-00:10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.27 | 17-APR-15:00 | 18.69 | 02-APR-05:03 |
May | 2263.36 | 01-MAY-00:10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.63 | 22-MAY-13:00 | 5.75 | 07-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.18 | 11-JUN-13:00 | 1.54 | 05-JUN-15:00 |
July | 2263.36 | 01-JUL-00:10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 29-JUL-16:00 | 2.60 | 14-JUL-21:52 |
August | 2263.36 | 01-AUG-00:10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.14 | 23-AUG-13:00 | 2.67 | 12-AUG-07:00 |
September | 2263.36 | 01-SEP-00:10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 | 08-SEP-16:00 | 2.87 | 05-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.11 | 09-OCT-10:55 | 5.16 | 28-OCT-03:00 |
November | 2263.36 | 01-NOV-00:10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 | 17-NOV-15:00 | 28.28 | 27-NOV-03:00 |
December | 2263.36 | 01-DEC-00:10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.72 | 10-DEC-14:00 | 32.77 | 15-DEC-05:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.72 | 1.54 | ||||
Maximum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 37.73 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 01-JAN-11:00 | 21.37 | 25-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.99 | 11-FEB-16:10 | 29.84 | 04-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 13-MAR-16:00 | 26.43 | 16-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.04 | 17-APR-15:10 | 12.03 | 02-APR-05:50 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.91 | 29-MAY-16:00 | 2.99 | 10-MAY-15:00 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.48 | 10-JUN-16:00 | 1.10 | 05-JUN-15:00 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.54 | 29-JUL-16:00 | 1.10 | 14-JUL-17:50 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.25 | 21-AUG-16:00 | 2.14 | 28-AUG-12:00 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.24 | 20-SEP-16:00 | 0.00 | 01-SEP-00:05 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.38 | 14-OCT-16:00 | 2.99 | 26-OCT-14:00 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.29 | 17-NOV-16:10 | 20.16 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.57 | 10-DEC-16:10 | 24.41 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 0.00 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 23.54 | 29.84 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 01-JAN-11:00 | 21.37 | 25-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.99 | 11-FEB-16:10 | 29.84 | 04-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 13-MAR-16:00 | 26.43 | 16-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.04 | 17-APR-15:10 | 12.03 | 02-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.91 | 29-MAY-16:00 | 3.00 | 07-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.48 | 10-JUN-16:00 | 2.38 | 21-JUN-17:50 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.54 | 29-JUL-16:00 | 5.07 | 02-JUL-18:00 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.25 | 21-AUG-16:00 | 2.53 | 12-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.24 | 20-SEP-16:00 | 2.53 | 04-SEP-21:50 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.38 | 14-OCT-16:00 | 3.93 | 01-OCT-08:00 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.29 | 17-NOV-16:10 | 20.15 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.57 | 10-DEC-16:10 | 24.41 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 2.38 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 23.54 | 29.84 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 74.64 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.77 | 01-JAN-11:00 | 11.03 | 25-JAN-08:20 |
February | 180.00 | 01-FEB-00:10 | 74.64 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.21 | 11-FEB-11:00 | 15.27 | 04-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 74.64 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 | 13-MAR-16:00 | 13.52 | 16-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 74.64 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.12 | 17-APR-15:10 | 6.16 | 02-APR-05:30 |
May | 180.00 | 01-MAY-00:10 | 74.64 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.19 | 29-MAY-16:00 | 1.53 | 10-MAY-15:00 |
June | 180.00 | 01-JUN-00:10 | 74.64 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.95 | 10-JUN-15:50 | 0.56 | 05-JUN-15:00 |
July | 180.00 | 01-JUL-00:10 | 74.64 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.04 | 29-JUL-16:00 | 0.56 | 14-JUL-18:00 |
August | 180.00 | 01-AUG-00:10 | 74.64 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.34 | 21-AUG-16:00 | 1.09 | 28-AUG-12:00 |
September | 180.00 | 01-SEP-00:10 | 74.64 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.30 | 08-SEP-16:00 | 0.00 | 01-SEP-00:05 |
October | 180.00 | 01-OCT-00:10 | 74.64 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.84 | 14-OCT-16:00 | 1.53 | 26-OCT-14:00 |
November | 180.00 | 01-NOV-00:10 | 74.64 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.40 | 17-NOV-16:10 | 10.31 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 74.64 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.48 | 10-DEC-16:10 | 12.49 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4.77 | 0.00 | |||||
Maximum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 12.04 | 15.27 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.07 | 02-JAN-14:30 | 64.91 | 25-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 11-FEB-14:00 | 85.49 | 04-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.61 | 13-MAR-16:00 | 77.29 | 16-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.71 | 17-APR-15:00 | 41.83 | 02-APR-05:10 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.06 | 22-MAY-13:00 | 14.80 | 01-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.20 | 11-JUN-13:00 | 5.39 | 05-JUN-15:00 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.95 | 29-JUL-16:00 | 5.49 | 14-JUL-21:55 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.23 | 23-AUG-13:00 | 8.00 | 12-AUG-07:00 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.08 | 13-SEP-13:00 | 7.96 | 05-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.47 | 09-OCT-10:55 | 12.61 | 28-OCT-03:10 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.80 | 17-NOV-15:00 | 61.87 | 27-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.54 | 10-DEC-14:40 | 72.42 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 21.61 | 5.39 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 45.95 | 85.49 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 | 02-JAN-14:30 | 64.91 | 25-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.55 | 11-FEB-14:00 | 85.84 | 04-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.61 | 13-MAR-16:00 | 77.29 | 16-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.71 | 17-APR-15:00 | 41.83 | 02-APR-05:10 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.53 | 22-MAY-13:00 | 14.80 | 01-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.94 | 11-JUN-13:00 | 5.46 | 05-JUN-15:00 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.95 | 29-JUL-16:00 | 5.49 | 14-JUL-21:52 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.79 | 23-AUG-13:00 | 8.00 | 12-AUG-07:00 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.60 | 13-SEP-13:00 | 7.96 | 05-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.08 | 09-OCT-10:55 | 12.61 | 28-OCT-03:10 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.17 | 17-NOV-15:00 | 61.88 | 27-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.06 | 10-DEC-14:40 | 72.42 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 21.61 | 5.46 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 45.95 | 85.84 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1090.83 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 17.73 | 02-JAN-14:00 | 58.09 | 25-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 1090.83 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 19.56 | 11-FEB-14:00 | 76.81 | 04-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1090.83 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 19.39 | 13-MAR-16:00 | 69.23 | 16-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1090.83 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 29.31 | 17-APR-15:00 | 37.43 | 02-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1090.83 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 37.08 | 22-MAY-13:00 | 13.24 | 01-MAY-05:10 |
June | 2401.70 | 01-JUN-00:10 | 1090.83 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 29.53 | 11-JUN-13:00 | 4.86 | 05-JUN-15:00 |
July | 2401.70 | 01-JUL-00:10 | 1090.83 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 41.18 | 29-JUL-16:00 | 4.94 | 14-JUL-22:40 |
August | 2401.70 | 01-AUG-00:10 | 1090.83 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 35.50 | 23-AUG-13:00 | 7.17 | 12-AUG-08:58 |
September | 2401.70 | 01-SEP-00:10 | 1090.83 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 29.45 | 20-SEP-16:00 | 7.11 | 05-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1090.83 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 29.45 | 09-OCT-10:55 | 9.05 | 20-OCT-05:05 |
November | 2401.70 | 01-NOV-00:10 | 1090.83 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 21.59 | 17-NOV-15:00 | 55.37 | 27-NOV-07:00 |
December | 2401.70 | 01-DEC-00:10 | 1090.83 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 17.58 | 10-DEC-14:00 | 64.81 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 17.58 | 4.86 | ||||||
Maximum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 41.18 | 76.81 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.74 | 02-JAN-14:00 | 46.14 | 25-JAN-05:00 |
February | 2395.44 | 01-FEB-00:10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.05 | 11-FEB-14:00 | 63.42 | 04-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.28 | 13-MAR-16:00 | 57.72 | 16-MAR-05:00 |
April | 2395.44 | 01-APR-00:10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.65 | 17-APR-15:00 | 31.30 | 02-APR-05:00 |
May | 2395.44 | 01-MAY-00:10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.25 | 22-MAY-13:00 | 9.56 | 07-MAY-05:03 |
June | 2395.44 | 01-JUN-00:10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.86 | 11-JUN-13:00 | 3.96 | 05-JUN-15:00 |
July | 2395.44 | 01-JUL-00:10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.25 | 29-JUL-16:00 | 4.44 | 14-JUL-21:51 |
August | 2395.44 | 01-AUG-00:10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.71 | 23-AUG-13:00 | 4.66 | 12-AUG-07:00 |
September | 2395.44 | 01-SEP-00:10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.78 | 13-SEP-13:00 | 4.76 | 02-SEP-22:00 |
October | 2395.44 | 01-OCT-23:10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 09-OCT-10:55 | 7.70 | 26-OCT-14:00 |
November | 2395.44 | 01-NOV-00:10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.76 | 17-NOV-15:00 | 46.75 | 27-NOV-03:00 |
December | 2395.44 | 01-DEC-00:10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.80 | 10-DEC-14:30 | 53.89 | 15-DEC-05:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.80 | 3.96 | ||||
Maximum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.25 | 63.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16771.27 | 13-JAN-22:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15794.61 | 11-FEB-11:35 | 7667.93 | 5150.74 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15229.44 | 04-MAR-11:35 | 7667.93 | 5150.74 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15381.30 | 16-APR-10:33 | 11501.89 | 9271.10 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15558.10 | 14-MAY-10:33 | 11501.89 | 9271.10 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15925.56 | 11-JUN-10:33 | 11501.89 | 9271.10 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16552.45 | 16-JUL-10:33 | 11501.89 | 9271.10 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17007.23 | 20-AUG-10:33 | 11501.89 | 9271.10 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18312.18 | 22-SEP-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18807.73 | 18-OCT-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18761.68 | 22-NOV-22:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18510.36 | 01-DEC-22:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 15229.44 | 7667.93 | 5150.74 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18807.73 | 11501.89 | 9271.10 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3296.19 | 02-JAN-14:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 14.23 | 0.00 |
February | 3226.23 | 11-FEB-14:10 | 389.84 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 15.15 | 0.00 |
March | 2533.30 | 04-MAR-11:35 | 779.69 | 284.62 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 8.87 | 0.00 |
April | 2353.65 | 13-APR-13:20 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 15.20 | 0.00 |
May | 2177.21 | 22-MAY-18:05 | 5457.82 | 2732.34 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 18.37 | 0.00 |
June | 2324.95 | 29-JUN-18:03 | 5457.82 | 2732.34 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 17.30 | 0.00 |
July | 2539.98 | 29-JUL-17:02 | 6237.50 | 2732.34 | 4041.45 | 0.00 | 0.00 | 0.00 | 0.00 | 28.93 | 0.00 |
August | 2551.46 | 20-AUG-12:00 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 23.53 | 0.00 |
September | 3253.83 | 30-SEP-13:10 | 389.84 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 19.23 | 0.00 |
October | 3434.03 | 25-OCT-12:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 17.26 | 0.00 |
November | 3501.61 | 07-NOV-13:20 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 11.47 | 0.00 |
December | 3636.76 | 09-DEC-12:30 | 389.84 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 9.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2177.21 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 8.87 | 0.00 | |
Maximum of Months | 3636.76 | 6237.50 | 2732.34 | 4041.45 | 0.00 | 0.00 | 0.00 | 0.00 | 28.93 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1776.24 | 03-JAN-22:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.07 |
February | 1764.50 | 22-FEB-22:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 |
March | 1885.13 | 28-MAR-20:52 | 9630.72 | 4218.74 | 6017.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 | 0.00 |
April | 2021.60 | 13-APR-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.81 | 0.00 |
May | 2025.45 | 17-MAY-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.37 | 0.00 |
June | 2083.48 | 09-JUN-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.03 | 0.00 |
July | 2121.23 | 28-JUL-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 0.00 |
August | 2121.35 | 17-AUG-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 4.28 | 0.00 |
September | 2101.06 | 01-SEP-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.48 | 0.00 |
October | 2075.50 | 06-OCT-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 | 0.00 |
November | 1939.73 | 07-NOV-22:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 | 0.00 |
December | 1896.08 | 08-DEC-22:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1764.50 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2121.35 | 9630.72 | 4218.74 | 6017.16 | 0.00 | 0.00 | 0.00 | 0.00 | 6.03 | 5.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1358.71 | 01-JAN-11:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 9.21 | 0.00 |
February | 1375.83 | 11-FEB-11:35 | 190.94 | 380.10 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 12.55 | 0.00 |
March | 1378.02 | 05-MAR-11:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 | 0.00 |
April | 1472.70 | 16-APR-10:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 14.41 | 0.00 |
May | 1666.34 | 23-MAY-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 0.00 |
June | 1906.86 | 29-JUN-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 12.95 | 0.00 |
July | 1957.38 | 28-JUL-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 0.00 |
August | 1892.90 | 21-AUG-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 11.36 | 0.00 |
September | 1891.77 | 22-SEP-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 11.41 | 0.00 |
October | 1590.88 | 03-OCT-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 10.04 | 0.00 |
November | 1431.50 | 23-NOV-11:33 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 9.62 | 0.00 |
December | 1452.38 | 09-DEC-12:30 | 95.47 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 11.06 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1358.71 | 95.47 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 0.00 | |
Maximum of Months | 1957.38 | 286.42 | 684.18 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 14.41 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 728.99 | 01-JAN-11:33 | 220.32 | 152.61 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 | 0.00 |
February | 739.17 | 11-FEB-11:35 | 146.88 | 84.79 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 7.19 | 0.00 |
March | 738.84 | 05-MAR-11:33 | 220.32 | 152.61 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 7.29 | 0.00 |
April | 785.39 | 16-APR-10:33 | 220.32 | 152.61 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 8.38 | 0.00 |
May | 802.60 | 31-MAY-10:35 | 97.92 | 84.79 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 0.00 |
June | 831.01 | 11-JUN-10:33 | 220.32 | 152.61 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 10.96 | 0.00 |
July | 861.13 | 28-JUL-21:00 | 195.84 | 135.66 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 8.18 | 0.00 |
August | 833.35 | 20-AUG-10:33 | 220.32 | 152.61 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 11.12 | 0.00 |
September | 834.04 | 24-SEP-10:33 | 220.32 | 152.61 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 10.31 | 0.00 |
October | 809.19 | 07-OCT-10:35 | 146.88 | 84.79 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 11.66 | 0.00 |
November | 764.63 | 23-NOV-11:33 | 220.32 | 152.61 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 5.60 | 0.00 |
December | 781.05 | 09-DEC-12:30 | 73.44 | 42.39 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 6.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 728.99 | 73.44 | 42.39 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 | 0.00 | |
Maximum of Months | 861.13 | 220.32 | 152.61 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37890.25 | 03-JAN-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 4.45 |
February | 37890.62 | 17-FEB-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
March | 38140.49 | 27-MAR-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 1.46 | 0.00 |
April | 38439.63 | 14-APR-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 7.63 | 0.00 |
May | 38540.41 | 31-MAY-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 13.77 | 0.00 |
June | 38666.66 | 09-JUN-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 19.47 | 0.00 |
July | 38778.76 | 28-JUL-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 15.46 | 0.00 |
August | 38635.35 | 31-AUG-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 13.80 | 0.00 |
September | 38586.88 | 08-SEP-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 23.64 | 0.00 |
October | 38464.01 | 06-OCT-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 9.78 | 0.00 |
November | 38165.14 | 03-NOV-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 7.63 | 0.00 |
December | 37993.47 | 08-DEC-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 1.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37890.25 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38778.76 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 23.64 | 4.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12313.55 | 01-JAN-10:30 | 8538.00 | 115.39 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 12.02 | 0.00 |
February | 11543.96 | 11-FEB-14:00 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 34.66 | 0.00 |
March | 10733.30 | 27-MAR-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.87 | 0.00 |
April | 10911.47 | 14-APR-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.71 | 0.00 |
May | 11091.75 | 22-MAY-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.74 | 0.00 |
June | 11246.43 | 02-JUN-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.46 | 0.00 |
July | 11503.99 | 28-JUL-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 33.85 | 0.00 |
August | 11519.60 | 31-AUG-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 24.30 | 0.00 |
September | 12082.35 | 08-SEP-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 37.64 | 0.00 |
October | 12296.96 | 25-OCT-15:03 | 51228.00 | 576.93 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 33.21 | 0.00 |
November | 11921.27 | 19-NOV-11:00 | 8538.00 | 115.39 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 17.49 | 0.00 |
December | 12604.28 | 09-DEC-12:30 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 20.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10733.30 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5.87 | 0.00 | |
Maximum of Months | 12604.28 | 51228.00 | 1048.97 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 37.64 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 38797.09 | 13-JAN-22:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 0.00 |
February | 37947.69 | 17-FEB-22:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
March | 37822.73 | 27-MAR-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 16.74 | 0.00 |
April | 39240.36 | 14-APR-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 27.71 | 0.00 |
May | 39959.13 | 22-MAY-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 67.80 | 0.00 |
June | 41157.29 | 29-JUN-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 89.69 | 0.00 |
July | 41724.68 | 28-JUL-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 96.68 | 0.00 |
August | 41659.22 | 21-AUG-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 77.28 | 0.00 |
September | 42543.92 | 22-SEP-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 79.09 | 0.00 |
October | 41481.29 | 06-OCT-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 49.70 | 0.00 |
November | 40643.29 | 03-NOV-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 49.66 | 0.00 |
December | 39913.75 | 08-DEC-22:05 | 182491.92 | 28387.68 | 29559.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 37822.73 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42543.92 | 182491.92 | 28387.68 | 29559.77 | 0.00 | 0.00 | 0.00 | 0.00 | 96.68 | 1.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2639.28 | 23-JAN-16:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 6.71 | 0.00 |
February | 2613.96 | 14-FEB-16:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 | 0.00 |
March | 2683.29 | 27-MAR-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 4.93 | 0.00 |
April | 2709.74 | 22-APR-15:02 | 324.00 | 235.11 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 6.58 | 0.00 |
May | 2714.58 | 15-MAY-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 8.37 | 0.00 |
June | 2719.96 | 08-JUN-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 11.96 | 0.00 |
July | 2698.13 | 11-JUL-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 12.07 | 0.00 |
August | 2714.05 | 03-AUG-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 10.27 | 0.00 |
September | 2709.44 | 11-SEP-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 7.43 | 0.00 |
October | 2725.40 | 10-OCT-15:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.80 | 0.00 |
November | 2680.51 | 18-NOV-16:02 | 324.00 | 235.11 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 7.49 | 0.00 |
December | 2688.26 | 07-DEC-16:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2613.96 | 324.00 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 | 0.00 | |
Maximum of Months | 2725.40 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 12.07 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2699.38 | 03-JAN-16:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 0.00 |
February | 2718.05 | 17-FEB-16:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 6.41 | 0.00 |
March | 2755.85 | 13-MAR-15:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 10.47 | 0.00 |
April | 2735.88 | 22-APR-15:02 | 324.00 | 235.08 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6.59 | 0.00 |
May | 2878.81 | 10-MAY-16:31 | 972.00 | 332.43 | 1343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 | 0.00 |
June | 2923.60 | 13-JUN-18:11 | 1386.00 | 1056.67 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 0.00 |
July | 2726.51 | 15-JUL-18:02 | 702.00 | 712.36 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 | 0.00 |
August | 2738.52 | 03-AUG-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 10.28 | 0.00 |
September | 2739.49 | 07-SEP-15:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 7.63 | 0.00 |
October | 2730.11 | 03-OCT-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 10.96 | 0.00 |
November | 2728.74 | 22-NOV-16:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 0.00 |
December | 2661.44 | 01-DEC-16:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 6.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2661.44 | 324.00 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 0.00 | |
Maximum of Months | 2923.60 | 1386.00 | 1056.67 | 1343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 10.96 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 579.16 | 02-JAN-14:30 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 | 0.00 |
February | 509.26 | 11-FEB-14:30 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 | 0.00 |
March | 416.75 | 02-MAR-14:30 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 |
April | 337.38 | 15-APR-14:30 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 1.92 | 0.00 |
May | 313.65 | 22-MAY-17:12 | 0.00 | 199.99 | 526.30 | 0.00 | 0.00 | 0.00 | 0.00 | 2.14 | 0.00 |
June | 323.32 | 03-JUN-20:50 | 0.00 | 74.62 | 180.59 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 | 0.00 |
July | 360.14 | 29-JUL-19:10 | 0.00 | 74.62 | 170.27 | 0.00 | 0.00 | 0.00 | 0.00 | 2.24 | 0.00 |
August | 359.34 | 20-AUG-14:00 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 | 0.00 |
September | 486.82 | 30-SEP-13:40 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 1.97 | 0.00 |
October | 547.19 | 25-OCT-14:00 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1.81 | 0.00 |
November | 582.76 | 07-NOV-13:40 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 0.00 |
December | 590.06 | 03-DEC-14:00 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 313.65 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 590.06 | 0.00 | 199.99 | 526.30 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 | 1.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 962.55 | 06-JAN-19:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 | 0.00 |
February | 985.07 | 22-FEB-16:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2.14 | 0.00 |
March | 988.16 | 13-MAR-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 2.35 | 0.00 |
April | 1011.40 | 16-APR-18:02 | 702.00 | 447.86 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 3.59 | 0.00 |
May | 1012.73 | 22-MAY-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 3.47 | 0.00 |
June | 1012.36 | 09-JUN-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 3.30 | 0.00 |
July | 1016.98 | 27-JUL-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 4.11 | 0.00 |
August | 1004.71 | 24-AUG-08:61 | 252.00 | 229.90 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 1.92 | 0.00 |
September | 1009.75 | 14-SEP-08:61 | 252.00 | 229.90 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 1.88 | 0.00 |
October | 1003.42 | 05-OCT-08:61 | 252.00 | 229.90 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 | 0.00 |
November | 1002.17 | 21-NOV-09:01 | 252.00 | 229.90 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 | 0.00 |
December | 988.03 | 09-DEC-09:02 | 324.00 | 250.80 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 1.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 962.55 | 252.00 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 | 0.00 | |
Maximum of Months | 1016.98 | 831.60 | 447.86 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 4.11 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2379.15 | 23-JAN-16:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 6.76 | 0.00 |
February | 2426.63 | 19-FEB-16:02 | 324.00 | 235.11 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 7.40 | 0.00 |
March | 2446.43 | 09-MAR-16:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.38 | 0.00 |
April | 2464.03 | 13-APR-08:61 | 252.00 | 365.72 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 7.42 | 0.00 |
May | 2481.36 | 31-MAY-08:62 | 216.00 | 313.47 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 0.00 |
June | 2471.52 | 09-JUN-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 12.11 | 0.00 |
July | 2476.67 | 16-JUL-08:62 | 324.00 | 398.97 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 10.36 | 0.00 |
August | 2485.18 | 30-AUG-08:62 | 216.00 | 313.47 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 10.35 | 0.00 |
September | 2479.33 | 21-SEP-08:62 | 216.00 | 313.47 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 | 0.00 |
October | 2480.73 | 06-OCT-08:62 | 216.00 | 313.47 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 6.80 | 0.00 |
November | 2475.49 | 21-NOV-09:01 | 252.00 | 365.72 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 0.00 |
December | 2447.95 | 25-DEC-16:02 | 324.00 | 235.11 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2379.15 | 216.00 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 | 0.00 | |
Maximum of Months | 2485.18 | 831.60 | 634.08 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 12.11 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2400.19 | 01-JAN-09:51 | 486.00 | 598.38 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 | 0.00 |
February | 2678.75 | 28-FEB-09:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 |
March | 2596.76 | 02-MAR-09:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 |
April | 2761.46 | 21-APR-08:31 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
May | 2600.00 | 02-MAY-08:11 | 324.00 | 470.16 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 1.66 | 0.00 |
June | 2654.34 | 13-JUN-18:11 | 1386.00 | 1056.67 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1.28 | 0.00 |
July | 2497.71 | 23-JUL-08:62 | 324.00 | 398.92 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 11.26 | 0.00 |
August | 2501.38 | 08-AUG-08:62 | 216.00 | 313.44 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 11.52 | 0.00 |
September | 2545.58 | 17-SEP-07:51 | 667.80 | 465.41 | 1659.22 | 0.00 | 0.00 | 0.00 | 0.00 | 3.06 | 0.00 |
October | 2616.31 | 17-OCT-08:61 | 324.00 | 470.16 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 | 0.00 |
November | 2487.03 | 07-NOV-09:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 | 0.00 |
December | 2451.72 | 09-DEC-09:02 | 324.00 | 398.92 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 5.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2400.19 | 216.00 | 313.44 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2761.46 | 1386.00 | 1056.67 | 1659.22 | 0.00 | 0.00 | 0.00 | 0.00 | 11.52 | 1.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1966.71 | 01-JAN-11:33 | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.38 | 0.00 |
February | 1944.55 | 11-FEB-11:35 | 1508.90 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.41 | 0.00 |
March | 1976.04 | 04-MAR-11:35 | 1508.90 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.93 | 0.00 |
April | 2102.28 | 16-APR-10:33 | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.63 | 0.00 |
May | 2102.88 | 20-MAY-10:35 | 1508.90 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.68 | 0.00 |
June | 2158.74 | 11-JUN-10:33 | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.72 | 0.00 |
July | 2186.57 | 29-JUL-18:00 | 1508.90 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.62 | 0.00 |
August | 2175.47 | 20-AUG-10:33 | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.82 | 0.00 |
September | 2214.11 | 22-SEP-21:10 | 2263.36 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.70 | 0.00 |
October | 2163.57 | 07-OCT-10:35 | 1508.90 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.01 | 0.00 |
November | 2045.95 | 10-NOV-11:33 | 1508.90 | 966.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.37 | 0.00 |
December | 2128.44 | 09-DEC-12:30 | 754.45 | 322.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1944.55 | 754.45 | 322.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.38 | 0.00 | |
Maximum of Months | 2214.11 | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.62 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2754.50 | 06-JAN-16:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 5.53 | 0.00 |
February | 2764.43 | 11-FEB-16:02 | 324.00 | 235.11 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 | 0.00 |
March | 2821.80 | 13-MAR-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 8.71 | 0.00 |
April | 2791.09 | 22-APR-15:02 | 324.00 | 235.11 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 6.47 | 0.00 |
May | 2822.42 | 31-MAY-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 9.34 | 0.00 |
June | 2827.33 | 08-JUN-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 11.86 | 0.00 |
July | 2833.28 | 11-JUL-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 0.00 |
August | 2835.88 | 14-AUG-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 | 0.00 |
September | 2868.73 | 30-SEP-15:02 | 324.00 | 235.11 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 | 0.00 |
October | 2849.16 | 10-OCT-15:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.75 | 0.00 |
November | 2868.82 | 07-NOV-16:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 8.78 | 0.00 |
December | 2773.57 | 07-DEC-16:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 6.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2754.50 | 324.00 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 5.53 | 0.00 | |
Maximum of Months | 2868.82 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2799.46 | 02-JAN-16:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 4.73 | 0.00 |
February | 2802.41 | 10-FEB-16:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 5.52 | 0.00 |
March | 2831.04 | 13-MAR-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 8.74 | 0.00 |
April | 2813.16 | 22-APR-15:02 | 324.00 | 235.08 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6.48 | 0.00 |
May | 2980.30 | 10-MAY-16:31 | 972.00 | 332.43 | 1343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 | 0.00 |
June | 3057.52 | 13-JUN-18:11 | 1386.00 | 1056.67 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 | 0.00 |
July | 2906.74 | 07-JUL-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 12.42 | 0.00 |
August | 2862.08 | 14-AUG-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 10.92 | 0.00 |
September | 2866.66 | 12-SEP-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 7.58 | 0.00 |
October | 2848.23 | 03-OCT-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 10.88 | 0.00 |
November | 2854.73 | 30-NOV-16:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 8.57 | 0.00 |
December | 2790.38 | 07-DEC-16:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 6.51 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2790.38 | 324.00 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 | 0.00 | |
Maximum of Months | 3057.52 | 1386.00 | 1056.67 | 1343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 12.42 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1369.53 | 03-JAN-16:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2.88 | 0.00 |
February | 1377.65 | 11-FEB-16:02 | 324.00 | 147.80 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 | 0.00 |
March | 1354.89 | 01-MAR-16:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 | 0.00 |
April | 1368.42 | 17-APR-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 6.07 | 0.00 |
May | 1367.18 | 29-MAY-18:02 | 702.00 | 447.86 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 6.73 | 0.00 |
June | 1360.15 | 04-JUN-15:02 | 324.00 | 147.80 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 3.42 | 0.00 |
July | 1372.90 | 27-JUL-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 7.53 | 0.00 |
August | 1373.31 | 30-AUG-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 5.89 | 0.00 |
September | 1391.43 | 10-SEP-15:02 | 324.00 | 147.80 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 6.84 | 0.00 |
October | 1389.14 | 20-OCT-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 3.55 | 0.00 |
November | 1388.30 | 03-NOV-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 4.51 | 0.00 |
December | 1370.46 | 08-DEC-16:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1354.89 | 324.00 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 | 0.00 | |
Maximum of Months | 1391.43 | 831.60 | 447.86 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 7.53 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20983.12 | 13-JAN-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 |
February | 21375.99 | 17-FEB-22:53 | 188921.38 | 12894.57 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 |
March | 21651.01 | 27-MAR-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 | 0.00 |
April | 22320.01 | 14-APR-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 5.81 | 0.00 |
May | 22999.80 | 22-MAY-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 12.77 | 0.00 |
June | 23267.56 | 09-JUN-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 21.09 | 0.00 |
July | 23309.45 | 28-JUL-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 0.00 |
August | 23138.27 | 02-AUG-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 21.08 | 0.00 |
September | 23213.15 | 08-SEP-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 21.72 | 0.00 |
October | 22539.67 | 03-OCT-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 15.20 | 0.00 |
November | 22180.58 | 03-NOV-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 10.74 | 0.00 |
December | 21441.31 | 08-DEC-22:53 | 188921.38 | 12894.57 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20983.12 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23309.45 | 188921.38 | 12894.57 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 21.72 | 0.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22427.19 | 13-JAN-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 |
February | 22737.67 | 17-FEB-22:53 | 188921.38 | 12894.57 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 |
March | 22970.82 | 27-MAR-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 2.92 | 0.00 |
April | 23552.63 | 14-APR-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 5.81 | 0.00 |
May | 24215.49 | 22-MAY-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 14.81 | 0.00 |
June | 24463.81 | 28-JUN-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 19.75 | 0.00 |
July | 24510.08 | 28-JUL-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 0.00 |
August | 24330.47 | 02-AUG-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 21.42 | 0.00 |
September | 24426.87 | 08-SEP-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 23.72 | 0.00 |
October | 23749.97 | 03-OCT-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 15.20 | 0.00 |
November | 23407.16 | 03-NOV-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 10.74 | 0.00 |
December | 22713.07 | 08-DEC-22:53 | 188921.38 | 12894.57 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22427.19 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24510.08 | 188921.38 | 12894.57 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 23.72 | 0.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27916.10 | 01-JAN-11:45 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 7.84 | 0.00 |
February | 28099.85 | 11-FEB-11:40 | 1601.14 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 13.03 | 0.00 |
March | 28308.15 | 27-MAR-10:35 | 1067.42 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 7.61 | 0.00 |
April | 29094.35 | 15-APR-10:50 | 800.57 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 20.30 | 0.00 |
May | 29043.27 | 06-MAY-10:50 | 800.57 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 18.48 | 0.00 |
June | 29344.65 | 11-JUN-10:37 | 2401.70 | 1090.83 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 24.92 | 0.00 |
July | 29489.70 | 23-JUL-10:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 31.13 | 0.00 |
August | 29299.43 | 19-AUG-10:40 | 1601.14 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 26.99 | 0.00 |
September | 29270.85 | 24-SEP-10:33 | 2401.70 | 1090.83 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 23.61 | 0.00 |
October | 29181.69 | 07-OCT-10:50 | 800.57 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 26.74 | 0.00 |
November | 28060.39 | 03-NOV-10:50 | 1067.42 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 15.16 | 0.00 |
December | 28099.31 | 09-DEC-11:50 | 800.57 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 11.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 27916.10 | 800.57 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 7.61 | 0.00 | |
Maximum of Months | 29489.70 | 2401.70 | 1090.83 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 31.13 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4688.17 | 01-JAN-11:33 | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.45 | 0.00 |
February | 4749.94 | 11-FEB-11:35 | 1596.96 | 682.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.95 | 0.00 |
March | 4688.01 | 04-MAR-11:35 | 1596.96 | 682.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.37 | 0.00 |
April | 5091.08 | 16-APR-15:13 | 2395.44 | 818.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 0.00 |
May | 5324.93 | 18-MAY-15:03 | 7984.80 | 2046.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.38 | 0.00 |
June | 5895.74 | 28-JUN-15:50 | 1330.80 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.51 | 0.00 |
July | 6669.71 | 28-JUL-15:40 | 1330.80 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.20 | 0.00 |
August | 5910.73 | 20-AUG-15:04 | 3992.40 | 1364.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.89 | 0.00 |
September | 6571.57 | 09-SEP-13:00 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.03 | 0.00 |
October | 6050.82 | 07-OCT-13:30 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.12 | 0.00 |
November | 5050.76 | 10-NOV-13:40 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.25 | 0.00 |
December | 5105.71 | 09-DEC-12:30 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 4688.01 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.45 | 0.00 | |
Maximum of Months | 6669.71 | 7984.80 | 2046.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.20 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.555843E+12 | 392277.07 | 06-JAN-20:49 | 0.218942E+12 | 151187.46 | 18-JAN-18:49 |
February | 0.530122E+12 | 386249.43 | 17-FEB-21:30 | 0.196023E+12 | 149245.87 | 01-FEB-18:00 |
March | 0.606259E+12 | 403819.49 | 13-MAR-19:19 | 0.213138E+12 | 145679.81 | 01-MAR-18:00 |
April | 0.635897E+12 | 416834.52 | 14-APR-19:10 | 0.199836E+12 | 138173.91 | 01-APR-17:19 |
May | 0.720363E+12 | 430452.39 | 22-MAY-19:10 | 0.199658E+12 | 129301.86 | 01-MAY-17:30 |
June | 0.738119E+12 | 450992.29 | 29-JUN-19:19 | 0.188869E+12 | 122115.25 | 01-JUN-17:30 |
July | 0.775982E+12 | 458047.05 | 27-JUL-19:19 | 0.194504E+12 | 120157.22 | 01-JUL-17:10 |
August | 0.772727E+12 | 447640.15 | 02-AUG-19:10 | 0.194827E+12 | 121127.78 | 31-AUG-17:19 |
September | 0.743191E+12 | 455872.74 | 08-SEP-19:00 | 0.190438E+12 | 125172.79 | 30-SEP-17:49 |
October | 0.734821E+12 | 445099.60 | 03-OCT-19:49 | 0.201445E+12 | 131816.94 | 31-OCT-17:00 |
November | 0.648297E+12 | 427878.38 | 03-NOV-19:49 | 0.201904E+12 | 139701.48 | 30-NOV-18:49 |
December | 0.590297E+12 | 411588.79 | 06-DEC-21:00 | 0.215907E+12 | 148455.16 | 30-DEC-18:49 |
Annual Sum or Average | 0.805192E+13 | 0.241549E+13 | ||||
Minimum of Months | 0.530122E+12 | 386249.43 | 0.188869E+12 | 120157.22 | ||
Maximum of Months | 0.775982E+12 | 458047.05 | 0.218942E+12 | 151187.46 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.517594E+11 | 0.166580E+11 | 0.146779E+12 | 0.544822E+11 | 0.465590E+11 | 0.151977E+11 | 0.00 | 0.157212E+12 | 0.00 | 0.00 | 0.238592E+11 | 0.395779E+11 | 0.00 |
February | 0.466048E+11 | 0.143743E+11 | 0.132565E+12 | 0.492097E+11 | 0.428529E+11 | 0.138225E+11 | 0.00 | 0.169987E+12 | 0.00 | 0.00 | 0.217619E+11 | 0.355477E+11 | 0.00 |
March | 0.513486E+11 | 0.150068E+11 | 0.146789E+12 | 0.544839E+11 | 0.481107E+11 | 0.154566E+11 | 0.00 | 0.207496E+12 | 0.00 | 0.00 | 0.246629E+11 | 0.391382E+11 | 0.00 |
April | 0.494779E+11 | 0.136353E+11 | 0.142011E+12 | 0.527242E+11 | 0.484476E+11 | 0.151722E+11 | 0.00 | 0.249144E+12 | 0.00 | 0.00 | 0.242387E+11 | 0.373975E+11 | 0.00 |
May | 0.510072E+11 | 0.132891E+11 | 0.146789E+12 | 0.544827E+11 | 0.524990E+11 | 0.161517E+11 | 0.00 | 0.318600E+12 | 0.00 | 0.00 | 0.256768E+11 | 0.380877E+11 | 0.00 |
June | 0.493379E+11 | 0.124968E+11 | 0.142058E+12 | 0.527260E+11 | 0.526119E+11 | 0.160166E+11 | 0.00 | 0.347746E+12 | 0.00 | 0.00 | 0.249197E+11 | 0.365435E+11 | 0.00 |
July | 0.508308E+11 | 0.130295E+11 | 0.146742E+12 | 0.544808E+11 | 0.550541E+11 | 0.166807E+11 | 0.00 | 0.371942E+12 | 0.00 | 0.00 | 0.257285E+11 | 0.377290E+11 | 0.00 |
August | 0.510872E+11 | 0.137352E+11 | 0.146800E+12 | 0.544838E+11 | 0.543054E+11 | 0.166223E+11 | 0.00 | 0.368474E+12 | 0.00 | 0.00 | 0.257431E+11 | 0.376957E+11 | 0.00 |
September | 0.496503E+11 | 0.141480E+11 | 0.142022E+12 | 0.527244E+11 | 0.533868E+11 | 0.161004E+11 | 0.00 | 0.350041E+12 | 0.00 | 0.00 | 0.249151E+11 | 0.365438E+11 | 0.00 |
October | 0.515348E+11 | 0.155395E+11 | 0.146768E+12 | 0.544820E+11 | 0.538976E+11 | 0.162995E+11 | 0.00 | 0.328882E+12 | 0.00 | 0.00 | 0.257084E+11 | 0.379301E+11 | 0.00 |
November | 0.499884E+11 | 0.158590E+11 | 0.142074E+12 | 0.527251E+11 | 0.492552E+11 | 0.153772E+11 | 0.00 | 0.258030E+12 | 0.00 | 0.00 | 0.240640E+11 | 0.372784E+11 | 0.00 |
December | 0.517387E+11 | 0.168311E+11 | 0.146742E+12 | 0.544813E+11 | 0.475128E+11 | 0.154303E+11 | 0.00 | 0.190482E+12 | 0.00 | 0.00 | 0.240459E+11 | 0.392672E+11 | 0.00 |
Annual Sum or Average | 0.604366E+12 | 0.174603E+12 | 0.172814E+13 | 0.641486E+12 | 0.604493E+12 | 0.188328E+12 | 0.00 | 0.331804E+13 | 0.00 | 0.00 | 0.295324E+12 | 0.452737E+12 | 0.00 |
Minimum of Months | 0.466048E+11 | 0.124968E+11 | 0.132565E+12 | 0.492097E+11 | 0.428529E+11 | 0.138225E+11 | 0.00 | 0.157212E+12 | 0.00 | 0.00 | 0.217619E+11 | 0.355477E+11 | 0.00 |
Maximum of Months | 0.517594E+11 | 0.168311E+11 | 0.146800E+12 | 0.544839E+11 | 0.550541E+11 | 0.166807E+11 | 0.00 | 0.371942E+12 | 0.00 | 0.00 | 0.257431E+11 | 0.395779E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.722479E+09 | 0.00 | 0.663009E+11 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.775560E+09 | 0.00 | 0.580439E+11 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.434163E+09 | 0.00 | 0.606805E+11 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.152380E+09 | 0.00 | 0.527277E+11 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.117083E+09 | 0.00 | 0.475627E+11 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 70502746.82 | 0.00 | 0.416842E+11 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 72926761.59 | 0.00 | 0.426104E+11 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 99188072.87 | 0.00 | 0.426895E+11 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 85181899.67 | 0.00 | 0.433824E+11 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.127935E+09 | 0.00 | 0.494143E+11 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.272028E+09 | 0.00 | 0.545412E+11 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.796502E+09 | 0.00 | 0.632905E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.372593E+10 | 0.00 | 0.622928E+12 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 70502746.82 | 0.00 | 0.416842E+11 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.796502E+09 | 0.00 | 0.663009E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 50471.22 | 02-JAN-20:10 | 11096.45 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 39155.93 | 02-JAN-07:19 | 34338.83 | 13-JAN-22:10 | 6735.96 | 06-JAN-22:00 | 0.00 | 01-JAN-00:10 |
February | 50471.22 | 01-FEB-20:10 | 11096.45 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 39155.93 | 24-FEB-07:19 | 33183.05 | 17-FEB-22:00 | 6643.24 | 10-FEB-22:00 | 0.00 | 01-FEB-00:10 |
March | 50471.22 | 01-MAR-20:10 | 11096.45 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 39155.93 | 13-MAR-06:19 | 33925.07 | 30-MAR-21:00 | 6713.53 | 09-MAR-22:00 | 0.00 | 01-MAR-00:10 |
April | 50471.22 | 03-APR-19:10 | 11096.45 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 39155.93 | 03-APR-06:19 | 34187.24 | 14-APR-21:19 | 6679.31 | 13-APR-18:10 | 0.00 | 01-APR-00:10 |
May | 50471.22 | 01-MAY-19:10 | 11096.45 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 39155.30 | 25-MAY-06:19 | 34870.99 | 24-MAY-21:10 | 6881.35 | 22-MAY-18:10 | 0.00 | 01-MAY-00:10 |
June | 50471.22 | 01-JUN-19:10 | 11096.45 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 39155.45 | 15-JUN-06:19 | 35902.61 | 29-JUN-21:10 | 7209.74 | 08-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 50471.22 | 03-JUL-19:19 | 11096.45 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 39155.26 | 13-JUL-06:19 | 36364.71 | 27-JUL-21:10 | 7416.69 | 27-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 50471.22 | 01-AUG-19:10 | 11096.45 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 39155.88 | 25-AUG-06:19 | 37122.76 | 21-AUG-21:10 | 7166.97 | 21-AUG-18:19 | 0.00 | 01-AUG-00:10 |
September | 50471.22 | 01-SEP-19:10 | 11096.45 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 39155.93 | 15-SEP-06:19 | 38839.06 | 21-SEP-21:10 | 7643.99 | 25-SEP-19:00 | 0.00 | 01-SEP-00:10 |
October | 50471.22 | 02-OCT-19:10 | 11096.45 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 39155.93 | 02-OCT-06:19 | 38580.07 | 06-OCT-21:19 | 7098.71 | 01-OCT-19:00 | 0.00 | 01-OCT-00:10 |
November | 50471.22 | 01-NOV-19:10 | 11096.45 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 39155.93 | 01-NOV-06:19 | 37340.54 | 21-NOV-22:40 | 7137.92 | 21-NOV-19:00 | 0.00 | 01-NOV-00:10 |
December | 50471.22 | 01-DEC-20:10 | 11096.45 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 39155.93 | 27-DEC-07:19 | 34948.35 | 08-DEC-22:00 | 7294.89 | 08-DEC-21:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 50471.22 | 11096.45 | 88863.15 | 39155.26 | 33183.05 | 6643.24 | 0.00 | |||||||
Maximum of Months | 50471.22 | 11096.45 | 88863.15 | 39155.93 | 38839.06 | 7643.99 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 146828.31 | 06-JAN-22:00 | 0.00 | 0.00 | 9938.94 | 01-JAN-09:30 | 43579.35 | 03-JAN-21:49 | 0.00 |
February | 155254.97 | 10-FEB-22:00 | 0.00 | 0.00 | 9938.94 | 01-FEB-09:20 | 43390.88 | 28-FEB-21:30 | 0.00 |
March | 152961.86 | 09-MAR-22:00 | 0.00 | 0.00 | 9938.94 | 01-MAR-02:49 | 43214.80 | 23-MAR-20:49 | 0.00 |
April | 167576.16 | 14-APR-15:20 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 42801.68 | 27-APR-20:30 | 0.00 |
May | 177054.40 | 29-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAY-00:10 | 42201.17 | 25-MAY-20:30 | 0.00 |
June | 187561.67 | 08-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-00:10 | 42335.34 | 05-JUN-17:30 | 0.00 |
July | 203625.45 | 27-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUL-00:10 | 41815.41 | 13-JUL-20:30 | 0.00 |
August | 191614.61 | 21-AUG-15:00 | 0.00 | 0.00 | 9938.94 | 01-AUG-00:10 | 41810.79 | 01-AUG-20:30 | 0.00 |
September | 196174.12 | 18-SEP-18:19 | 0.00 | 0.00 | 9938.94 | 01-SEP-00:10 | 41806.46 | 07-SEP-20:49 | 0.00 |
October | 179197.29 | 03-OCT-15:20 | 0.00 | 0.00 | 9938.94 | 01-OCT-00:10 | 42031.64 | 03-OCT-20:49 | 0.00 |
November | 163488.75 | 03-NOV-20:00 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 42587.64 | 02-NOV-20:30 | 0.00 |
December | 164196.97 | 06-DEC-21:00 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 43252.73 | 12-DEC-21:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 146828.31 | 0.00 | 0.00 | 9938.94 | 41806.46 | 0.00 | |||
Maximum of Months | 203625.45 | 0.00 | 0.00 | 9938.94 | 43579.35 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 392277.07 | 06-JAN-20:49 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 26858.74 | 6345.42 | 0.00 | 126867.60 | 0.00 |
February | 386249.43 | 17-FEB-21:30 | 44879.15 | 88373.09 | 11096.45 | 24006.45 | 28423.76 | 6264.77 | 0.00 | 128838.02 | 0.00 |
March | 403819.49 | 13-MAR-19:19 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 26780.95 | 6497.75 | 0.00 | 138769.62 | 0.00 |
April | 416834.52 | 14-APR-19:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 28780.17 | 6610.74 | 0.00 | 149578.36 | 0.00 |
May | 430452.39 | 22-MAY-19:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 27596.94 | 6779.25 | 0.00 | 164310.30 | 0.00 |
June | 450992.29 | 29-JUN-19:19 | 50471.22 | 87982.85 | 11096.45 | 31576.97 | 29799.82 | 7057.18 | 0.00 | 183111.00 | 0.00 |
July | 458047.05 | 27-JUL-19:19 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 29619.70 | 7310.36 | 0.00 | 190132.17 | 0.00 |
August | 447640.15 | 02-AUG-19:10 | 50471.22 | 87982.85 | 11096.45 | 31571.78 | 28211.50 | 7129.88 | 0.00 | 180721.33 | 0.00 |
September | 455872.74 | 08-SEP-19:00 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 32064.17 | 7004.47 | 0.00 | 186478.71 | 0.00 |
October | 445099.60 | 03-OCT-19:49 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 31466.22 | 7031.93 | 0.00 | 175891.24 | 0.00 |
November | 427878.38 | 03-NOV-19:49 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 30472.20 | 6913.44 | 0.00 | 159517.11 | 0.00 |
December | 411588.79 | 06-DEC-21:00 | 44879.15 | 88373.09 | 11096.45 | 24006.45 | 33432.44 | 7238.49 | 0.00 | 164196.97 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 386249.43 | 44879.15 | 87982.85 | 11096.45 | 24006.45 | 26780.95 | 6264.77 | 0.00 | 126867.60 | 0.00 | |
Maximum of Months | 458047.05 | 50471.22 | 88373.09 | 11096.45 | 31577.78 | 33432.44 | 7310.36 | 0.00 | 190132.17 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 6281.20 | 25-JAN-04:00 | 0.00 | 46939.24 | 18-JAN-19:40 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 19263.55 | 04-FEB-05:00 | 0.00 | 44997.59 | 01-FEB-17:40 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 9719.09 | 15-MAR-08:20 | 0.00 | 41431.94 | 01-MAR-22:30 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 4908.43 | 19-APR-08:00 | 0.00 | 33926.02 | 01-APR-16:40 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 6528.53 | 28-MAY-06:00 | 0.00 | 25235.61 | 01-MAY-21:49 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 5627.37 | 25-JUN-06:00 | 0.00 | 17866.94 | 01-JUN-19:40 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 1724.00 | 30-JUL-16:00 | 0.00 | 15908.90 | 01-JUL-00:10 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 4391.15 | 06-AUG-21:00 | 0.00 | 16879.47 | 31-AUG-20:10 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 5116.25 | 07-SEP-06:00 | 0.00 | 20924.47 | 30-SEP-16:49 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 7694.75 | 15-OCT-06:00 | 0.00 | 27568.73 | 31-OCT-21:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 7956.80 | 12-NOV-09:20 | 0.00 | 35453.32 | 30-NOV-17:19 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 7911.14 | 12-DEC-09:09 | 0.00 | 44393.81 | 31-DEC-23:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 1724.00 | 0.00 | 15908.90 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 19263.55 | 0.00 | 46939.24 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.82 | 1.33 | 21.82 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.69 | 0.83 | 21.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.76 | 1.83 | 21.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.71 | 2.00 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.72 | 1.33 | 21.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.77 | 2.50 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.79 | 2.17 | 21.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.80 | 2.50 | 21.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.80 | 3.17 | 21.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.74 | 0.83 | 21.74 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.78 | 1.17 | 21.78 |
Annual Sum or Average | 0.00 | 0.00 | 19.67 | 21.77 | 19.67 | 21.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.82 | 3.17 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.71 | 0.67 | 21.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.73 | 3.17 | 21.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.75 | 2.33 | 21.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.77 | 2.00 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.77 | 2.83 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.76 | 1.33 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.73 | 1.50 | 21.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.76 | 0.83 | 21.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.79 | 0.33 | 21.79 |
Annual Sum or Average | 0.00 | 0.00 | 15.17 | 21.75 | 15.17 | 21.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.79 | 3.17 | 21.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.72 | 1.83 | 21.72 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.82 | 3.50 | 21.82 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 21.78 | 6.17 | 21.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 21.78 | 8.33 | 21.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 21.76 | 8.33 | 21.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 21.75 | 9.33 | 21.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 21.75 | 11.00 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 21.71 | 6.83 | 21.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 21.73 | 6.17 | 21.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.76 | 3.00 | 21.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.75 | 1.83 | 21.75 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.80 | 2.67 | 21.80 |
Annual Sum or Average | 0.00 | 0.00 | 69.00 | 21.76 | 69.00 | 21.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.71 | 1.83 | 21.71 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 21.82 | 11.00 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.71 | 1.17 | 21.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.72 | 0.83 | 21.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.74 | 2.67 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.74 | 1.50 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.75 | 2.67 | 21.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.72 | 2.33 | 21.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.70 | 0.50 | 21.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.33 | 21.73 | 12.33 | 21.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.75 | 2.67 | 21.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.97 | 1.67 | 21.97 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.93 | 3.00 | 21.93 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 22.02 | 4.17 | 22.02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 22.10 | 8.83 | 22.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 22.09 | 2.83 | 22.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.80 | 2.50 | 21.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.77 | 3.83 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.71 | 1.17 | 21.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.93 | 1.83 | 21.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 22.25 | 3.00 | 22.25 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 22.01 | 3.00 | 22.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.89 | 2.17 | 21.89 |
Annual Sum or Average | 0.00 | 0.00 | 38.00 | 21.99 | 38.00 | 21.99 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.71 | 1.17 | 21.71 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 22.25 | 8.83 | 22.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.80 | 1.67 | 21.80 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.71 | 1.17 | 21.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.81 | 2.33 | 21.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.78 | 2.83 | 21.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.80 | 1.67 | 21.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.83 | 3.50 | 21.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.80 | 3.00 | 21.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.81 | 3.17 | 21.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.80 | 3.50 | 21.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.77 | 0.67 | 21.77 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.76 | 1.17 | 21.76 |
Annual Sum or Average | 0.00 | 0.00 | 24.83 | 21.80 | 24.83 | 21.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.83 | 3.50 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.72 | 0.83 | 21.72 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.75 | 3.67 | 21.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.79 | 3.50 | 21.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.79 | 2.67 | 21.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.81 | 4.17 | 21.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.76 | 2.83 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.75 | 2.33 | 21.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.70 | 1.00 | 21.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.74 | 0.33 | 21.74 |
Annual Sum or Average | 0.00 | 0.00 | 21.50 | 21.77 | 21.50 | 21.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.81 | 4.17 | 21.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 21.93 | 7.67 | 21.93 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 21.87 | 6.50 | 21.87 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.85 | 4.50 | 21.85 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.89 | 3.17 | 21.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.73 | 3.33 | 21.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.76 | 3.00 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 21.81 | 5.83 | 21.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 21.83 | 5.67 | 21.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 21.87 | 10.17 | 21.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 21.95 | 13.33 | 21.95 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 21.90 | 8.00 | 21.90 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 21.91 | 9.00 | 21.91 |
Annual Sum or Average | 0.00 | 0.00 | 80.17 | 21.88 | 80.17 | 21.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.73 | 3.00 | 21.73 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 21.95 | 13.33 | 21.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 264.83 | 23.41 | 213.67 | 23.59 | 0.00 | 23.59 |
February | 456.33 | 23.18 | 11.50 | 23.20 | 0.00 | 23.20 |
March | 738.00 | 22.82 | 0.00 | 22.82 | 0.00 | 22.82 |
April | 720.00 | 22.63 | 0.00 | 22.63 | 0.00 | 22.63 |
May | 743.83 | 22.79 | 0.00 | 22.79 | 0.00 | 22.79 |
June | 718.33 | 22.89 | 0.00 | 22.89 | 0.00 | 22.89 |
July | 444.33 | 23.01 | 0.67 | 23.01 | 0.00 | 23.01 |
August | 228.67 | 23.20 | 319.17 | 23.54 | 0.00 | 23.54 |
September | 43.67 | 23.27 | 420.50 | 23.83 | 0.00 | 23.83 |
October | 9.33 | 23.29 | 460.50 | 23.91 | 0.00 | 23.91 |
November | 42.67 | 23.61 | 402.17 | 23.89 | 0.00 | 23.89 |
December | 98.33 | 23.50 | 341.83 | 23.79 | 0.00 | 23.79 |
Annual Sum or Average | 4508.33 | 22.93 | 2170.00 | 23.24 | 0.00 | 23.24 |
Minimum of Months | 9.33 | 22.63 | 0.00 | 22.63 | 0.00 | 22.63 |
Maximum of Months | 743.83 | 23.61 | 460.50 | 23.91 | 0.00 | 23.91 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 416.50 | 22.32 | 226.83 | 22.86 | 0.00 | 22.86 |
February | 319.17 | 22.40 | 242.00 | 23.01 | 0.00 | 23.01 |
March | 322.67 | 22.40 | 293.67 | 23.04 | 0.00 | 23.04 |
April | 239.33 | 22.67 | 343.17 | 23.31 | 0.00 | 23.31 |
May | 81.17 | 22.75 | 526.17 | 23.57 | 0.00 | 23.57 |
June | 9.67 | 22.87 | 635.00 | 23.72 | 0.00 | 23.72 |
July | 0.00 | 0.00 | 703.50 | 23.82 | 0.00 | 23.82 |
August | 45.17 | 22.70 | 631.83 | 23.74 | 0.00 | 23.74 |
September | 7.00 | 22.88 | 661.17 | 23.85 | 0.00 | 23.85 |
October | 17.00 | 22.78 | 648.83 | 23.81 | 0.00 | 23.81 |
November | 168.50 | 22.49 | 462.67 | 23.47 | 0.00 | 23.47 |
December | 353.67 | 22.26 | 305.83 | 22.99 | 0.00 | 22.99 |
Annual Sum or Average | 1979.83 | 22.43 | 5680.67 | 23.44 | 0.00 | 23.44 |
Minimum of Months | 0.00 | 0.00 | 226.83 | 22.86 | 0.00 | 22.86 |
Maximum of Months | 416.50 | 22.88 | 703.50 | 23.85 | 0.00 | 23.85 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 436.67 | 22.89 | 151.67 | 23.12 | 0.00 | 23.12 |
February | 337.00 | 22.89 | 178.00 | 23.20 | 0.00 | 23.20 |
March | 333.00 | 22.85 | 253.83 | 23.26 | 0.00 | 23.26 |
April | 202.83 | 22.87 | 343.17 | 23.48 | 0.00 | 23.48 |
May | 141.33 | 22.91 | 431.50 | 23.63 | 0.00 | 23.63 |
June | 86.50 | 22.97 | 449.00 | 23.75 | 0.00 | 23.75 |
July | 23.67 | 22.98 | 490.83 | 23.88 | 0.00 | 23.88 |
August | 72.33 | 22.94 | 479.50 | 23.76 | 0.00 | 23.76 |
September | 20.17 | 22.97 | 500.00 | 23.86 | 0.00 | 23.86 |
October | 34.17 | 22.97 | 487.17 | 23.82 | 0.00 | 23.82 |
November | 155.00 | 22.93 | 353.17 | 23.56 | 0.00 | 23.56 |
December | 339.67 | 22.85 | 216.00 | 23.23 | 0.00 | 23.23 |
Annual Sum or Average | 2182.33 | 22.89 | 4333.83 | 23.54 | 0.00 | 23.54 |
Minimum of Months | 20.17 | 22.85 | 151.67 | 23.12 | 0.00 | 23.12 |
Maximum of Months | 436.67 | 22.98 | 500.00 | 23.88 | 0.00 | 23.88 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 737.50 | 22.59 | 0.00 | 22.59 | 0.00 | 22.59 |
February | 654.00 | 22.71 | 0.00 | 22.71 | 0.00 | 22.71 |
March | 705.50 | 22.74 | 0.00 | 22.74 | 0.00 | 22.74 |
April | 590.83 | 23.04 | 5.67 | 23.05 | 0.00 | 23.05 |
May | 218.00 | 23.18 | 126.50 | 23.45 | 0.00 | 23.45 |
June | 16.00 | 23.31 | 381.33 | 23.88 | 0.00 | 23.88 |
July | 0.00 | 0.00 | 468.00 | 23.94 | 0.00 | 23.94 |
August | 95.83 | 23.23 | 295.50 | 23.76 | 0.00 | 23.76 |
September | 22.33 | 23.31 | 372.33 | 23.88 | 0.00 | 23.88 |
October | 185.33 | 23.26 | 119.50 | 23.51 | 0.00 | 23.51 |
November | 458.67 | 23.02 | 15.50 | 23.05 | 0.00 | 23.05 |
December | 662.33 | 22.70 | 0.33 | 22.70 | 0.00 | 22.70 |
Annual Sum or Average | 4346.33 | 22.83 | 1784.67 | 23.15 | 0.00 | 23.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.59 | 0.00 | 22.59 |
Maximum of Months | 737.50 | 23.31 | 468.00 | 23.94 | 0.00 | 23.94 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.49 | 0.00 | 22.49 | 0.00 | 22.49 |
February | 672.00 | 22.63 | 0.00 | 22.63 | 0.00 | 22.63 |
March | 744.00 | 22.67 | 0.00 | 22.67 | 0.00 | 22.67 |
April | 675.00 | 22.99 | 0.00 | 22.99 | 0.00 | 22.99 |
May | 357.83 | 23.21 | 12.83 | 23.24 | 0.00 | 23.24 |
June | 34.67 | 23.32 | 213.83 | 23.80 | 0.00 | 23.80 |
July | 0.00 | 0.00 | 381.50 | 23.89 | 0.00 | 23.89 |
August | 134.67 | 23.25 | 192.50 | 23.62 | 0.00 | 23.62 |
September | 39.67 | 23.33 | 214.50 | 23.79 | 0.00 | 23.79 |
October | 271.17 | 23.27 | 13.50 | 23.30 | 0.00 | 23.30 |
November | 589.00 | 23.02 | 0.00 | 23.02 | 0.00 | 23.02 |
December | 723.67 | 22.66 | 0.00 | 22.66 | 0.00 | 22.66 |
Annual Sum or Average | 4985.67 | 22.82 | 1028.67 | 23.00 | 0.00 | 23.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.49 | 0.00 | 22.49 |
Maximum of Months | 744.00 | 23.33 | 381.50 | 23.89 | 0.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 283.83 | 23.65 | 644.17 | 23.17 | 254.33 | 23.34 |
February | 257.00 | 23.73 | 588.00 | 23.18 | 237.00 | 23.35 |
March | 287.00 | 23.75 | 658.33 | 23.17 | 266.17 | 23.34 |
April | 279.67 | 23.92 | 675.50 | 23.15 | 276.83 | 23.33 |
May | 297.83 | 23.94 | 715.00 | 23.13 | 297.83 | 23.32 |
June | 291.17 | 23.94 | 706.50 | 23.11 | 291.17 | 23.29 |
July | 300.83 | 23.94 | 734.50 | 23.09 | 300.83 | 23.28 |
August | 298.50 | 23.94 | 723.33 | 23.11 | 298.50 | 23.30 |
September | 290.67 | 23.94 | 705.00 | 23.11 | 290.67 | 23.30 |
October | 296.67 | 23.94 | 711.33 | 23.13 | 296.67 | 23.32 |
November | 281.17 | 23.87 | 664.33 | 23.17 | 273.83 | 23.34 |
December | 286.00 | 23.75 | 665.33 | 23.15 | 266.67 | 23.32 |
Annual Sum or Average | 3450.33 | 23.86 | 8191.33 | 23.14 | 3350.50 | 23.32 |
Minimum of Months | 257.00 | 23.65 | 588.00 | 23.09 | 237.00 | 23.28 |
Maximum of Months | 300.83 | 23.94 | 734.50 | 23.18 | 300.83 | 23.35 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 292.17 | 23.50 | 534.83 | 23.71 | 192.33 | 23.74 |
February | 245.50 | 23.59 | 528.50 | 23.74 | 172.17 | 23.77 |
March | 302.17 | 23.53 | 559.67 | 23.68 | 208.33 | 23.73 |
April | 298.17 | 23.75 | 600.17 | 23.73 | 260.50 | 23.78 |
May | 308.33 | 23.92 | 677.67 | 23.73 | 299.67 | 23.78 |
June | 273.50 | 23.96 | 680.50 | 23.74 | 271.33 | 23.79 |
July | 280.67 | 23.98 | 732.67 | 23.78 | 280.67 | 23.82 |
August | 297.83 | 23.89 | 706.83 | 23.78 | 283.17 | 23.82 |
September | 266.67 | 23.98 | 717.67 | 23.86 | 266.67 | 23.89 |
October | 293.67 | 23.94 | 732.50 | 23.89 | 288.33 | 23.91 |
November | 286.17 | 23.80 | 651.83 | 23.84 | 246.00 | 23.86 |
December | 312.17 | 23.55 | 595.67 | 23.74 | 233.67 | 23.77 |
Annual Sum or Average | 3457.00 | 23.78 | 7718.50 | 23.77 | 3002.83 | 23.81 |
Minimum of Months | 245.50 | 23.50 | 528.50 | 23.68 | 172.17 | 23.73 |
Maximum of Months | 312.17 | 23.98 | 732.67 | 23.89 | 299.67 | 23.91 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 323.33 | 23.47 | 396.67 | 23.66 | 158.50 | 23.71 |
February | 247.83 | 23.53 | 377.67 | 23.71 | 137.67 | 23.76 |
March | 316.50 | 23.44 | 410.17 | 23.67 | 170.17 | 23.72 |
April | 302.83 | 23.61 | 459.83 | 23.76 | 212.67 | 23.81 |
May | 286.00 | 23.81 | 508.33 | 23.85 | 246.17 | 23.88 |
June | 237.00 | 23.92 | 533.50 | 23.86 | 222.00 | 23.89 |
July | 224.17 | 23.99 | 604.83 | 23.86 | 222.67 | 23.89 |
August | 239.83 | 23.94 | 596.50 | 23.85 | 229.00 | 23.88 |
September | 214.83 | 23.99 | 653.83 | 23.84 | 214.33 | 23.87 |
October | 237.83 | 23.98 | 692.67 | 23.84 | 234.67 | 23.87 |
November | 250.00 | 23.80 | 574.33 | 23.80 | 201.00 | 23.84 |
December | 310.17 | 23.54 | 490.00 | 23.71 | 192.50 | 23.75 |
Annual Sum or Average | 3190.33 | 23.73 | 6298.33 | 23.79 | 2441.33 | 23.83 |
Minimum of Months | 214.83 | 23.44 | 377.67 | 23.66 | 137.67 | 23.71 |
Maximum of Months | 323.33 | 23.99 | 692.67 | 23.86 | 246.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 706.33 | 21.59 | 1.83 | 21.59 | 1.83 | 21.60 |
February | 625.17 | 21.57 | 2.83 | 21.58 | 2.83 | 21.59 |
March | 684.50 | 21.56 | 3.50 | 21.56 | 3.50 | 21.57 |
April | 641.67 | 21.54 | 0.17 | 21.54 | 0.17 | 21.54 |
May | 654.83 | 21.52 | 0.17 | 21.52 | 0.17 | 21.52 |
June | 619.83 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
July | 616.67 | 21.42 | 0.17 | 21.42 | 0.00 | 21.42 |
August | 626.83 | 21.45 | 0.50 | 21.45 | 0.50 | 21.45 |
September | 595.83 | 21.41 | 1.33 | 21.42 | 0.00 | 21.42 |
October | 633.67 | 21.47 | 1.00 | 21.47 | 0.33 | 21.47 |
November | 641.83 | 21.53 | 2.00 | 21.53 | 0.83 | 21.53 |
December | 687.00 | 21.54 | 2.50 | 21.55 | 2.50 | 21.55 |
Annual Sum or Average | 7734.17 | 21.51 | 16.00 | 21.51 | 12.67 | 21.51 |
Minimum of Months | 595.83 | 21.41 | 0.00 | 21.42 | 0.00 | 21.42 |
Maximum of Months | 706.33 | 21.59 | 3.50 | 21.59 | 3.50 | 21.60 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 717.67 | 21.95 | 29.50 | 21.99 | 28.50 | 22.04 |
February | 613.50 | 22.04 | 50.33 | 22.15 | 42.50 | 22.23 |
March | 632.83 | 21.97 | 70.67 | 22.17 | 38.00 | 22.25 |
April | 574.00 | 21.86 | 71.83 | 22.13 | 25.83 | 22.20 |
May | 643.50 | 21.63 | 17.33 | 21.70 | 14.33 | 21.75 |
June | 610.33 | 21.51 | 9.33 | 21.55 | 4.33 | 21.57 |
July | 608.00 | 21.49 | 13.00 | 21.55 | 9.17 | 21.60 |
August | 632.17 | 21.50 | 7.00 | 21.53 | 4.50 | 21.54 |
September | 608.33 | 21.54 | 11.67 | 21.58 | 7.67 | 21.61 |
October | 662.67 | 21.66 | 12.67 | 21.70 | 11.17 | 21.73 |
November | 665.83 | 21.85 | 30.00 | 21.92 | 29.00 | 21.98 |
December | 685.00 | 21.88 | 47.17 | 21.97 | 41.50 | 22.03 |
Annual Sum or Average | 7653.83 | 21.74 | 370.50 | 21.84 | 256.50 | 21.89 |
Minimum of Months | 574.00 | 21.49 | 7.00 | 21.53 | 4.33 | 21.54 |
Maximum of Months | 717.67 | 22.04 | 71.83 | 22.17 | 42.50 | 22.25 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.91 | 26.00 | 21.95 | 26.00 | 21.98 |
February | 667.67 | 22.06 | 44.17 | 22.14 | 44.17 | 22.21 |
March | 736.50 | 22.04 | 39.83 | 22.11 | 39.83 | 22.17 |
April | 709.33 | 22.08 | 22.17 | 22.13 | 22.00 | 22.18 |
May | 743.67 | 21.83 | 15.50 | 21.86 | 15.50 | 21.90 |
June | 718.83 | 21.76 | 6.17 | 21.78 | 5.50 | 21.79 |
July | 743.17 | 21.79 | 9.83 | 21.82 | 9.67 | 21.85 |
August | 744.00 | 21.74 | 4.83 | 21.75 | 4.83 | 21.76 |
September | 716.50 | 21.77 | 7.50 | 21.79 | 6.67 | 21.81 |
October | 743.83 | 21.79 | 11.00 | 21.81 | 11.00 | 21.83 |
November | 720.00 | 21.89 | 25.67 | 21.94 | 25.67 | 21.98 |
December | 743.83 | 21.93 | 39.67 | 21.99 | 39.67 | 22.05 |
Annual Sum or Average | 8731.33 | 21.88 | 252.33 | 21.92 | 250.50 | 21.96 |
Minimum of Months | 667.67 | 21.74 | 4.83 | 21.75 | 4.83 | 21.76 |
Maximum of Months | 744.00 | 22.08 | 44.17 | 22.14 | 44.17 | 22.21 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 714.33 | 21.64 | 1.33 | 21.64 | 1.33 | 21.64 |
February | 626.17 | 21.60 | 1.83 | 21.61 | 1.83 | 21.61 |
March | 677.83 | 21.58 | 2.83 | 21.58 | 2.67 | 21.59 |
April | 609.33 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
May | 615.17 | 21.42 | 0.33 | 21.42 | 0.33 | 21.42 |
June | 570.00 | 21.34 | 0.00 | 21.34 | 0.00 | 21.34 |
July | 571.17 | 21.28 | 0.00 | 21.28 | 0.00 | 21.28 |
August | 598.33 | 21.37 | 0.50 | 21.37 | 0.50 | 21.37 |
September | 566.67 | 21.33 | 0.00 | 21.33 | 0.00 | 21.33 |
October | 606.33 | 21.39 | 0.33 | 21.39 | 0.33 | 21.39 |
November | 638.83 | 21.53 | 0.50 | 21.53 | 0.50 | 21.54 |
December | 698.67 | 21.58 | 2.33 | 21.59 | 2.33 | 21.59 |
Annual Sum or Average | 7492.83 | 21.47 | 10.00 | 21.47 | 9.83 | 21.47 |
Minimum of Months | 566.67 | 21.28 | 0.00 | 21.28 | 0.00 | 21.28 |
Maximum of Months | 714.33 | 21.64 | 2.83 | 21.64 | 2.67 | 21.64 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 721.00 | 22.01 | 34.83 | 22.09 | 29.17 | 22.15 |
February | 640.17 | 22.15 | 55.00 | 22.28 | 42.67 | 22.36 |
March | 655.00 | 22.07 | 61.17 | 22.25 | 38.33 | 22.35 |
April | 539.67 | 21.83 | 74.67 | 22.16 | 26.67 | 22.27 |
May | 597.67 | 21.53 | 25.33 | 21.64 | 15.67 | 21.71 |
June | 554.83 | 21.35 | 11.00 | 21.41 | 4.17 | 21.43 |
July | 560.50 | 21.34 | 15.17 | 21.43 | 9.17 | 21.49 |
August | 597.17 | 21.40 | 7.00 | 21.43 | 4.67 | 21.44 |
September | 566.67 | 21.43 | 15.17 | 21.50 | 7.67 | 21.54 |
October | 630.83 | 21.60 | 18.67 | 21.69 | 11.67 | 21.74 |
November | 689.67 | 21.96 | 37.67 | 22.08 | 30.67 | 22.16 |
December | 725.67 | 21.94 | 48.83 | 22.03 | 42.67 | 22.10 |
Annual Sum or Average | 7478.83 | 21.74 | 404.50 | 21.86 | 263.17 | 21.93 |
Minimum of Months | 539.67 | 21.34 | 7.00 | 21.41 | 4.17 | 21.43 |
Maximum of Months | 725.67 | 22.15 | 74.67 | 22.28 | 42.67 | 22.36 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 740.50 | 22.74 | 43.50 | 22.76 | 43.50 | 22.78 |
February | 672.00 | 22.82 | 44.00 | 22.83 | 44.00 | 22.83 |
March | 735.67 | 22.93 | 64.83 | 22.95 | 64.83 | 22.97 |
April | 628.17 | 23.24 | 95.33 | 23.26 | 95.33 | 23.27 |
May | 493.00 | 23.35 | 145.00 | 23.39 | 126.50 | 23.41 |
June | 219.17 | 23.60 | 216.83 | 23.69 | 130.33 | 23.70 |
July | 130.83 | 23.81 | 320.50 | 23.85 | 125.67 | 23.84 |
August | 256.50 | 23.56 | 256.00 | 23.69 | 136.67 | 23.70 |
September | 158.33 | 23.70 | 286.83 | 23.81 | 124.00 | 23.80 |
October | 169.67 | 23.62 | 236.17 | 23.71 | 130.67 | 23.70 |
November | 538.83 | 23.20 | 106.00 | 23.24 | 97.67 | 23.26 |
December | 681.33 | 22.78 | 55.00 | 22.81 | 55.00 | 22.83 |
Annual Sum or Average | 5424.00 | 23.09 | 1870.00 | 23.24 | 1174.17 | 23.29 |
Minimum of Months | 130.83 | 22.74 | 43.50 | 22.76 | 43.50 | 22.78 |
Maximum of Months | 740.50 | 23.81 | 320.50 | 23.85 | 136.67 | 23.84 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 696.67 | 21.54 | 8.67 | 21.55 | 8.67 | 21.56 |
February | 615.17 | 21.52 | 14.33 | 21.54 | 13.17 | 21.55 |
March | 667.67 | 21.49 | 10.00 | 21.51 | 10.00 | 21.53 |
April | 618.67 | 21.47 | 5.50 | 21.48 | 2.67 | 21.49 |
May | 621.33 | 21.43 | 1.83 | 21.43 | 0.50 | 21.43 |
June | 591.33 | 21.40 | 2.50 | 21.41 | 0.00 | 21.41 |
July | 591.83 | 21.34 | 6.00 | 21.36 | 0.00 | 21.36 |
August | 606.17 | 21.39 | 7.00 | 21.41 | 1.00 | 21.41 |
September | 579.00 | 21.36 | 8.50 | 21.39 | 0.17 | 21.39 |
October | 613.17 | 21.40 | 11.17 | 21.44 | 2.67 | 21.44 |
November | 629.67 | 21.48 | 7.67 | 21.50 | 3.00 | 21.50 |
December | 676.50 | 21.49 | 18.00 | 21.51 | 15.33 | 21.52 |
Annual Sum or Average | 7507.17 | 21.45 | 101.17 | 21.46 | 57.17 | 21.47 |
Minimum of Months | 579.00 | 21.34 | 1.83 | 21.36 | 0.00 | 21.36 |
Maximum of Months | 696.67 | 21.54 | 18.00 | 21.55 | 15.33 | 21.56 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 713.17 | 21.85 | 56.33 | 21.92 | 55.83 | 21.97 |
February | 606.50 | 21.96 | 80.33 | 22.10 | 73.17 | 22.19 |
March | 621.17 | 21.90 | 92.83 | 22.15 | 57.17 | 22.25 |
April | 561.00 | 21.81 | 87.33 | 22.12 | 42.17 | 22.23 |
May | 613.17 | 21.55 | 24.00 | 21.63 | 19.83 | 21.70 |
June | 583.83 | 21.43 | 13.33 | 21.49 | 6.33 | 21.51 |
July | 585.33 | 21.42 | 20.33 | 21.51 | 10.00 | 21.56 |
August | 608.67 | 21.43 | 12.17 | 21.47 | 7.00 | 21.49 |
September | 586.50 | 21.47 | 16.67 | 21.53 | 13.50 | 21.57 |
October | 646.33 | 21.60 | 21.50 | 21.65 | 21.50 | 21.70 |
November | 653.00 | 21.76 | 44.00 | 21.85 | 44.00 | 21.92 |
December | 679.33 | 21.77 | 78.67 | 21.87 | 73.50 | 21.95 |
Annual Sum or Average | 7458.00 | 21.67 | 547.50 | 21.79 | 424.00 | 21.86 |
Minimum of Months | 561.00 | 21.42 | 12.17 | 21.47 | 6.33 | 21.49 |
Maximum of Months | 713.17 | 21.96 | 92.83 | 22.15 | 73.50 | 22.25 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 655.17 | 21.51 | 24.50 | 21.57 | 5.17 | 21.57 |
February | 598.17 | 21.53 | 12.67 | 21.56 | 8.17 | 21.58 |
March | 681.17 | 21.57 | 12.83 | 21.58 | 12.83 | 21.60 |
April | 661.17 | 21.59 | 2.83 | 21.60 | 2.83 | 21.60 |
May | 688.67 | 21.61 | 1.33 | 21.61 | 1.33 | 21.62 |
June | 661.33 | 21.60 | 0.00 | 21.60 | 0.00 | 21.60 |
July | 648.33 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
August | 654.83 | 21.53 | 1.17 | 21.53 | 1.17 | 21.54 |
September | 600.50 | 21.44 | 6.67 | 21.46 | 0.00 | 21.46 |
October | 622.83 | 21.46 | 38.83 | 21.57 | 2.83 | 21.58 |
November | 611.50 | 21.47 | 31.50 | 21.56 | 2.33 | 21.56 |
December | 644.33 | 21.47 | 34.00 | 21.56 | 6.50 | 21.58 |
Annual Sum or Average | 7728.00 | 21.53 | 166.33 | 21.56 | 43.17 | 21.57 |
Minimum of Months | 598.17 | 21.44 | 0.00 | 21.46 | 0.00 | 21.46 |
Maximum of Months | 688.67 | 21.61 | 38.83 | 21.61 | 12.83 | 21.62 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 238.00 | 23.68 | 545.17 | 23.78 | 169.00 | 23.82 |
February | 186.67 | 23.79 | 536.83 | 23.81 | 144.67 | 23.84 |
March | 217.83 | 23.77 | 637.17 | 23.83 | 174.17 | 23.86 |
April | 207.33 | 24.00 | 708.67 | 23.90 | 207.33 | 23.92 |
May | 232.67 | 24.00 | 744.00 | 23.93 | 232.67 | 23.94 |
June | 214.00 | 24.00 | 720.00 | 23.95 | 214.00 | 23.96 |
July | 219.00 | 24.00 | 744.00 | 23.96 | 219.00 | 23.97 |
August | 223.83 | 24.00 | 743.83 | 23.94 | 223.83 | 23.95 |
September | 217.83 | 24.00 | 720.00 | 23.94 | 217.83 | 23.95 |
October | 235.00 | 24.00 | 744.00 | 23.91 | 235.00 | 23.92 |
November | 219.33 | 23.94 | 664.00 | 23.87 | 208.17 | 23.90 |
December | 259.83 | 23.75 | 610.00 | 23.82 | 206.17 | 23.85 |
Annual Sum or Average | 2671.33 | 23.91 | 8117.67 | 23.89 | 2451.83 | 23.91 |
Minimum of Months | 186.67 | 23.68 | 536.83 | 23.78 | 144.67 | 23.82 |
Maximum of Months | 259.83 | 24.00 | 744.00 | 23.96 | 235.00 | 23.97 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 174.00 | 23.85 | 627.67 | 23.86 | 148.50 | 23.88 |
February | 142.83 | 23.91 | 588.50 | 23.88 | 129.17 | 23.89 |
March | 176.50 | 23.84 | 669.50 | 23.88 | 149.33 | 23.89 |
April | 186.50 | 24.00 | 715.50 | 23.93 | 186.50 | 23.94 |
May | 216.83 | 24.00 | 744.00 | 23.96 | 216.83 | 23.96 |
June | 200.00 | 24.00 | 720.00 | 23.97 | 200.00 | 23.97 |
July | 206.00 | 24.00 | 744.00 | 23.98 | 206.00 | 23.98 |
August | 208.83 | 24.00 | 744.00 | 23.96 | 208.83 | 23.97 |
September | 204.67 | 24.00 | 720.00 | 23.96 | 204.67 | 23.97 |
October | 219.67 | 24.00 | 744.00 | 23.93 | 219.67 | 23.94 |
November | 186.83 | 24.00 | 685.00 | 23.91 | 186.83 | 23.92 |
December | 199.83 | 23.90 | 662.83 | 23.87 | 181.67 | 23.89 |
Annual Sum or Average | 2322.50 | 23.96 | 8365.00 | 23.93 | 2238.00 | 23.94 |
Minimum of Months | 142.83 | 23.84 | 588.50 | 23.86 | 129.17 | 23.88 |
Maximum of Months | 219.67 | 24.00 | 744.00 | 23.98 | 219.67 | 23.98 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 549.67 | 23.99 | 730.67 | 23.88 | 548.50 | 23.91 |
February | 501.67 | 23.98 | 658.33 | 23.89 | 499.00 | 23.92 |
March | 560.67 | 23.99 | 736.50 | 23.90 | 560.50 | 23.93 |
April | 557.00 | 23.99 | 720.00 | 23.92 | 557.00 | 23.94 |
May | 586.33 | 23.99 | 744.00 | 23.93 | 586.33 | 23.95 |
June | 576.50 | 23.99 | 720.00 | 23.95 | 576.50 | 23.96 |
July | 596.33 | 23.99 | 744.00 | 23.95 | 596.33 | 23.96 |
August | 592.00 | 23.99 | 744.00 | 23.94 | 592.00 | 23.96 |
September | 574.33 | 23.99 | 720.00 | 23.95 | 574.33 | 23.96 |
October | 585.17 | 23.99 | 744.00 | 23.93 | 585.17 | 23.95 |
November | 550.83 | 23.99 | 713.33 | 23.91 | 550.83 | 23.94 |
December | 557.83 | 23.99 | 737.67 | 23.89 | 557.83 | 23.92 |
Annual Sum or Average | 6788.33 | 23.99 | 8712.50 | 23.92 | 6784.33 | 23.94 |
Minimum of Months | 501.67 | 23.98 | 658.33 | 23.88 | 499.00 | 23.91 |
Maximum of Months | 596.33 | 23.99 | 744.00 | 23.95 | 596.33 | 23.96 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 720.00 | 22.34 | 2.33 | 22.34 | 0.00 | 22.34 |
February | 635.50 | 22.53 | 3.50 | 22.54 | 0.00 | 22.54 |
March | 633.00 | 22.61 | 10.33 | 22.63 | 0.00 | 22.63 |
April | 395.00 | 22.99 | 120.50 | 23.19 | 0.00 | 23.19 |
May | 91.50 | 23.07 | 356.67 | 23.67 | 0.00 | 23.67 |
June | 0.00 | 0.00 | 612.83 | 23.87 | 0.00 | 23.87 |
July | 0.00 | 0.00 | 691.33 | 23.89 | 0.00 | 23.89 |
August | 38.83 | 23.11 | 572.50 | 23.83 | 0.00 | 23.83 |
September | 14.00 | 23.16 | 563.00 | 23.88 | 0.00 | 23.88 |
October | 49.17 | 23.13 | 388.83 | 23.76 | 0.00 | 23.76 |
November | 377.67 | 22.75 | 108.17 | 22.98 | 0.00 | 22.98 |
December | 626.50 | 22.36 | 22.00 | 22.41 | 0.00 | 22.41 |
Annual Sum or Average | 3581.17 | 22.58 | 3452.00 | 23.21 | 0.00 | 23.21 |
Minimum of Months | 0.00 | 0.00 | 2.33 | 22.34 | 0.00 | 22.34 |
Maximum of Months | 720.00 | 23.16 | 691.33 | 23.89 | 0.00 | 23.89 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.60624 | 52.94782 | 0.34493 | 7.64000 |
February | 672.00000 | 23.29329 | 54.38376 | 0.27161 | 6.69676 |
March | 744.00000 | 22.82286 | 56.77847 | 0.16307 | 5.73527 |
April | 720.00000 | 22.62996 | 61.34749 | 0.14141 | 5.54553 |
May | 744.00000 | 22.79225 | 61.77707 | -0.8360 | 19.91853 |
June | 720.00000 | 22.89221 | 61.22578 | -0.8015 | 18.71443 |
July | 744.00000 | 23.20028 | 60.00698 | -0.6951 | 15.34506 |
August | 744.00000 | 23.54948 | 59.18348 | -0.5735 | 12.05974 |
September | 720.00000 | 23.70109 | 58.42468 | -0.5195 | 10.81576 |
October | 744.00000 | 23.75576 | 58.39033 | 0.42672 | 8.87193 |
November | 720.00000 | 23.77181 | 56.63012 | 0.41753 | 8.73172 |
December | 744.00000 | 23.73096 | 55.25769 | 0.39544 | 8.37121 |
Annual Sum or Average | 8760.00000 | 23.31303 | 58.04434 | -0.1076 | 10.73404 |
Minimum of Months | 672.00000 | 22.62996 | 52.94782 | -0.8360 | 5.54553 |
Maximum of Months | 744.00000 | 23.77181 | 61.77707 | 0.42672 | 19.91853 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.91594 | 54.37892 | 0.26125 | 7.79126 |
February | 672.00000 | 23.05621 | 54.47677 | 0.30137 | 8.13493 |
March | 744.00000 | 23.06830 | 55.44917 | 0.30871 | 8.20603 |
April | 720.00000 | 23.28219 | 58.84054 | 0.39243 | 8.74122 |
May | 744.00000 | 23.48546 | 59.33669 | -0.4614 | 9.92667 |
June | 720.00000 | 23.65443 | 58.68851 | -0.3948 | 8.52438 |
July | 744.00000 | 23.78044 | 58.03436 | -0.3417 | 7.67064 |
August | 744.00000 | 23.68837 | 58.66329 | -0.3745 | 8.39916 |
September | 720.00000 | 23.79741 | 57.91857 | -0.3200 | 7.55293 |
October | 744.00000 | 23.73757 | 58.20310 | 0.53884 | 11.34595 |
November | 720.00000 | 23.43363 | 57.29495 | 0.43783 | 9.96871 |
December | 744.00000 | 23.01948 | 57.02866 | 0.31202 | 8.40575 |
Annual Sum or Average | 8760.00000 | 23.41141 | 57.37410 | 0.05326 | 8.72741 |
Minimum of Months | 672.00000 | 22.91594 | 54.37892 | -0.4614 | 7.55293 |
Maximum of Months | 744.00000 | 23.79741 | 59.33669 | 0.53884 | 11.34595 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.17910 | 54.99062 | 0.28124 | 7.06134 |
February | 672.00000 | 23.25500 | 55.27748 | 0.30554 | 7.38846 |
March | 744.00000 | 23.29250 | 56.12800 | 0.32304 | 7.70909 |
April | 720.00000 | 23.44904 | 59.50594 | 0.39054 | 8.47630 |
May | 744.00000 | 23.54433 | 60.16420 | -0.5064 | 10.77439 |
June | 720.00000 | 23.61829 | 59.74515 | -0.4777 | 10.12231 |
July | 744.00000 | 23.69236 | 59.23025 | -0.4480 | 9.47912 |
August | 744.00000 | 23.64004 | 59.75626 | -0.4681 | 9.92121 |
September | 720.00000 | 23.70197 | 59.27224 | -0.4445 | 9.41052 |
October | 744.00000 | 23.66055 | 59.61099 | 0.45480 | 9.46960 |
November | 720.00000 | 23.49034 | 58.42942 | 0.39495 | 8.57016 |
December | 744.00000 | 23.26907 | 57.57317 | 0.32456 | 7.59171 |
Annual Sum or Average | 8760.00000 | 23.48369 | 58.32167 | 0.00891 | 8.83960 |
Minimum of Months | 672.00000 | 23.17910 | 54.99062 | -0.5064 | 7.06134 |
Maximum of Months | 744.00000 | 23.70197 | 60.16420 | 0.45480 | 10.77439 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.72730 | 51.88016 | 0.77540 | 20.47333 |
February | 672.00000 | 22.72403 | 52.42997 | 0.78635 | 20.85328 |
March | 744.00000 | 22.72503 | 53.47040 | 0.80176 | 21.39195 |
April | 720.00000 | 22.71330 | 57.48048 | 0.83920 | 22.50510 |
May | 744.00000 | 22.72517 | 58.41026 | 0.13178 | 11.12093 |
June | 720.00000 | 22.72931 | 58.18166 | 0.14882 | 11.21954 |
July | 744.00000 | 22.72025 | 58.00796 | 0.15094 | 11.15817 |
August | 744.00000 | 22.71574 | 58.36301 | 0.13502 | 11.19419 |
September | 720.00000 | 22.72698 | 58.08558 | 0.14543 | 11.15597 |
October | 744.00000 | 22.71620 | 58.33121 | 0.85580 | 23.04347 |
November | 720.00000 | 22.73323 | 56.46885 | 0.83083 | 22.23732 |
December | 744.00000 | 22.70853 | 54.90189 | 0.79252 | 20.95892 |
Annual Sum or Average | 8760.00000 | 22.72203 | 56.35301 | 0.53119 | 17.25205 |
Minimum of Months | 672.00000 | 22.70853 | 51.88016 | 0.13178 | 11.12093 |
Maximum of Months | 744.00000 | 22.73323 | 58.41026 | 0.85580 | 23.04347 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.61909 | 58.12542 | 0.50180 | 10.87657 |
February | 672.00000 | 23.64377 | 58.53102 | 0.51554 | 11.11080 |
March | 744.00000 | 23.54754 | 59.76890 | 0.49551 | 10.80800 |
April | 720.00000 | 23.55803 | 63.43819 | 0.53129 | 11.25408 |
May | 744.00000 | 23.55608 | 64.24029 | -0.3442 | 7.85392 |
June | 720.00000 | 23.59150 | 63.76975 | -0.3171 | 7.45850 |
July | 744.00000 | 23.68755 | 63.25167 | -0.2764 | 6.82832 |
August | 744.00000 | 23.67575 | 63.56293 | -0.2817 | 7.04382 |
September | 720.00000 | 23.81306 | 62.68201 | -0.2163 | 6.25104 |
October | 744.00000 | 23.84876 | 62.70492 | 0.64520 | 13.90947 |
November | 720.00000 | 23.77214 | 61.50510 | 0.59625 | 12.88494 |
December | 744.00000 | 23.64891 | 60.75254 | 0.53445 | 11.56211 |
Annual Sum or Average | 8760.00000 | 23.66346 | 61.87761 | 0.19664 | 9.81345 |
Minimum of Months | 672.00000 | 23.54754 | 58.12542 | -0.3442 | 6.25104 |
Maximum of Months | 744.00000 | 23.84876 | 64.24029 | 0.64520 | 13.90947 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.54156 | 57.03515 | 0.41198 | 8.91556 |
February | 672.00000 | 23.55368 | 57.47094 | 0.42157 | 9.08071 |
March | 744.00000 | 23.49830 | 58.56423 | 0.41560 | 9.09143 |
April | 720.00000 | 23.54432 | 62.12170 | 0.45789 | 9.68684 |
May | 744.00000 | 23.58913 | 62.73740 | -0.4309 | 9.32106 |
June | 720.00000 | 23.62988 | 62.27378 | -0.4085 | 8.88110 |
July | 744.00000 | 23.67359 | 61.88033 | -0.3894 | 8.49067 |
August | 744.00000 | 23.65924 | 62.27881 | -0.3971 | 8.64104 |
September | 720.00000 | 23.72988 | 61.71176 | -0.3675 | 8.08015 |
October | 744.00000 | 23.74041 | 61.90679 | 0.52602 | 10.91458 |
November | 720.00000 | 23.68481 | 60.58264 | 0.49117 | 10.28680 |
December | 744.00000 | 23.58286 | 59.61115 | 0.44506 | 9.46254 |
Annual Sum or Average | 8760.00000 | 23.61920 | 60.69675 | 0.09592 | 9.23904 |
Minimum of Months | 672.00000 | 23.49830 | 57.03515 | -0.4309 | 8.08015 |
Maximum of Months | 744.00000 | 23.74041 | 62.73740 | 0.52602 | 10.91458 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.67557 | 56.27830 | -0.0891 | 5.99887 |
February | 672.00000 | 21.69436 | 55.55013 | -0.0695 | 5.99668 |
March | 744.00000 | 21.69783 | 54.82272 | -0.0571 | 5.93354 |
April | 720.00000 | 21.73351 | 54.73836 | -0.0185 | 5.86517 |
May | 744.00000 | 21.74064 | 53.48334 | -1.0854 | 31.22890 |
June | 720.00000 | 21.74238 | 52.85521 | -1.0765 | 30.80000 |
July | 744.00000 | 21.74727 | 52.44364 | -1.0577 | 30.02879 |
August | 744.00000 | 21.74497 | 52.81764 | -1.0696 | 30.55222 |
September | 720.00000 | 21.74522 | 52.73913 | -1.0640 | 30.36096 |
October | 744.00000 | 21.74391 | 53.03267 | -0.0055 | 5.83170 |
November | 720.00000 | 21.72318 | 54.29145 | -0.0398 | 5.89823 |
December | 744.00000 | 21.67867 | 57.49210 | -0.0683 | 5.93188 |
Annual Sum or Average | 8760.00000 | 21.72237 | 54.20715 | -0.4776 | 16.26389 |
Minimum of Months | 672.00000 | 21.67557 | 52.44364 | -1.0854 | 5.83170 |
Maximum of Months | 744.00000 | 21.74727 | 57.49210 | -0.0055 | 31.22890 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.00275 | 58.59601 | -0.0431 | 6.07537 |
February | 672.00000 | 22.17647 | 57.31891 | 0.01463 | 6.30494 |
March | 744.00000 | 22.23926 | 55.63382 | 0.04398 | 6.40844 |
April | 720.00000 | 22.25181 | 55.32084 | 0.08656 | 6.43422 |
May | 744.00000 | 21.86872 | 53.72373 | -1.0458 | 29.69620 |
June | 720.00000 | 21.79695 | 52.81314 | -1.0564 | 30.04102 |
July | 744.00000 | 21.82835 | 52.53968 | -1.0305 | 29.07160 |
August | 744.00000 | 21.78052 | 52.99062 | -1.0632 | 30.29043 |
September | 720.00000 | 21.82386 | 53.21371 | -1.0549 | 30.00865 |
October | 744.00000 | 21.84421 | 54.18148 | 0.00045 | 5.86221 |
November | 720.00000 | 21.96359 | 56.17617 | -0.0050 | 5.95786 |
December | 744.00000 | 22.01203 | 59.77978 | -0.0177 | 6.07048 |
Annual Sum or Average | 8760.00000 | 21.96405 | 55.18204 | -0.4337 | 16.07536 |
Minimum of Months | 672.00000 | 21.78052 | 52.53968 | -1.0632 | 5.86221 |
Maximum of Months | 744.00000 | 22.25181 | 59.77978 | 0.08656 | 30.29043 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.90525 | 56.29556 | -0.1022 | 6.01031 |
February | 672.00000 | 22.07193 | 56.29648 | -0.0513 | 6.03854 |
March | 744.00000 | 22.05859 | 55.80506 | -0.0484 | 6.00356 |
April | 720.00000 | 22.10872 | 56.48128 | -0.0144 | 5.92786 |
May | 744.00000 | 21.82671 | 54.87541 | -1.1754 | 35.15424 |
June | 720.00000 | 21.76635 | 54.06769 | -1.1851 | 35.53011 |
July | 744.00000 | 21.79469 | 54.07001 | -1.1717 | 35.00655 |
August | 744.00000 | 21.74421 | 54.22020 | -1.2008 | 36.21068 |
September | 720.00000 | 21.78425 | 54.31359 | -1.1890 | 35.73081 |
October | 744.00000 | 21.78629 | 55.45957 | -0.0878 | 5.79642 |
November | 720.00000 | 21.89448 | 56.30923 | -0.0757 | 5.81408 |
December | 744.00000 | 21.93222 | 58.42509 | -0.0761 | 5.87503 |
Annual Sum or Average | 8760.00000 | 21.88799 | 55.54831 | -0.5345 | 18.33130 |
Minimum of Months | 672.00000 | 21.74421 | 54.06769 | -1.2008 | 5.79642 |
Maximum of Months | 744.00000 | 22.10872 | 58.42509 | -0.0144 | 36.21068 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.70374 | 55.79916 | -0.0800 | 6.01216 |
February | 672.00000 | 21.72122 | 55.30717 | -0.0627 | 5.99219 |
March | 744.00000 | 21.73238 | 54.61334 | -0.0498 | 5.94855 |
April | 720.00000 | 21.74753 | 54.41204 | -0.0165 | 5.90507 |
May | 744.00000 | 21.75004 | 53.41678 | -1.0804 | 31.06682 |
June | 720.00000 | 21.75320 | 52.71580 | -1.0592 | 30.12170 |
July | 744.00000 | 21.75572 | 52.36761 | -1.0463 | 29.61414 |
August | 744.00000 | 21.75109 | 52.81378 | -1.0661 | 30.45733 |
September | 720.00000 | 21.75332 | 52.52796 | -1.0523 | 29.90499 |
October | 744.00000 | 21.75095 | 52.99437 | -0.0010 | 5.85923 |
November | 720.00000 | 21.73665 | 54.31104 | -0.0347 | 5.89564 |
December | 744.00000 | 21.68994 | 57.66483 | -0.0712 | 5.92035 |
Annual Sum or Average | 8760.00000 | 21.73716 | 54.07499 | -0.4709 | 16.12011 |
Minimum of Months | 672.00000 | 21.68994 | 52.36761 | -1.0804 | 5.85923 |
Maximum of Months | 744.00000 | 21.75572 | 57.66483 | -0.0010 | 31.06682 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.06597 | 57.60612 | -0.0293 | 6.17714 |
February | 672.00000 | 22.24116 | 56.80957 | 0.02806 | 6.38854 |
March | 744.00000 | 22.27072 | 55.35783 | 0.04979 | 6.44662 |
April | 720.00000 | 22.30644 | 54.97588 | 0.09684 | 6.73048 |
May | 744.00000 | 21.89745 | 53.66271 | -1.0353 | 29.49584 |
June | 720.00000 | 21.81331 | 52.70755 | -1.0375 | 29.35364 |
July | 744.00000 | 21.84211 | 52.44488 | -1.0178 | 28.66739 |
August | 744.00000 | 21.78706 | 53.06037 | -1.0591 | 30.17511 |
September | 720.00000 | 21.84432 | 52.99844 | -1.0395 | 29.48228 |
October | 744.00000 | 21.87717 | 54.03540 | 0.00999 | 6.00366 |
November | 720.00000 | 22.02968 | 55.82891 | 0.00940 | 6.15481 |
December | 744.00000 | 21.99054 | 59.87753 | -0.0291 | 6.04904 |
Annual Sum or Average | 8760.00000 | 21.99514 | 54.94077 | -0.4240 | 15.98349 |
Minimum of Months | 672.00000 | 21.78706 | 52.44488 | -1.0591 | 6.00366 |
Maximum of Months | 744.00000 | 22.30644 | 59.87753 | 0.09684 | 30.17511 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.65350 | 58.22844 | -0.0985 | 6.14884 |
February | 672.00000 | 21.67710 | 57.03814 | -0.0748 | 6.13557 |
March | 744.00000 | 21.68288 | 56.08246 | -0.0598 | 6.05593 |
April | 720.00000 | 21.73005 | 55.62967 | -0.0139 | 5.95057 |
May | 744.00000 | 21.74095 | 54.01748 | -1.0758 | 30.96446 |
June | 720.00000 | 21.74290 | 53.24230 | -1.0657 | 30.48178 |
July | 744.00000 | 21.74862 | 52.77013 | -1.0450 | 29.68771 |
August | 744.00000 | 21.74460 | 53.28455 | -1.0601 | 30.29846 |
September | 720.00000 | 21.74444 | 53.26588 | -1.0564 | 30.20882 |
October | 744.00000 | 21.74129 | 53.81528 | -0.0027 | 5.91486 |
November | 720.00000 | 21.71188 | 55.52497 | -0.0427 | 5.99066 |
December | 744.00000 | 21.65525 | 59.36176 | -0.0764 | 6.05677 |
Annual Sum or Average | 8760.00000 | 21.71457 | 55.18169 | -0.4751 | 16.21833 |
Minimum of Months | 672.00000 | 21.65350 | 52.77013 | -1.0758 | 5.91486 |
Maximum of Months | 744.00000 | 21.74862 | 59.36176 | -0.0027 | 30.96446 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.91900 | 60.67641 | -0.0656 | 6.25225 |
February | 672.00000 | 22.12193 | 58.72527 | 0.00263 | 6.47943 |
March | 744.00000 | 22.20809 | 56.74502 | 0.04000 | 6.58297 |
April | 720.00000 | 22.23184 | 56.01888 | 0.08977 | 6.53873 |
May | 744.00000 | 21.86230 | 54.18257 | -1.0375 | 29.48506 |
June | 720.00000 | 21.79675 | 53.17752 | -1.0454 | 29.72578 |
July | 744.00000 | 21.82952 | 52.80477 | -1.0174 | 28.74062 |
August | 744.00000 | 21.77851 | 53.45958 | -1.0538 | 30.03212 |
September | 720.00000 | 21.81680 | 53.74382 | -1.0489 | 29.88263 |
October | 744.00000 | 21.82621 | 55.14094 | 0.00082 | 5.90217 |
November | 720.00000 | 21.91215 | 57.57861 | -0.0154 | 6.01547 |
December | 744.00000 | 21.91985 | 61.75640 | -0.0404 | 6.25187 |
Annual Sum or Average | 8760.00000 | 21.93366 | 56.15783 | -0.4354 | 16.04647 |
Minimum of Months | 672.00000 | 21.77851 | 52.80477 | -1.0538 | 5.90217 |
Maximum of Months | 744.00000 | 22.23184 | 61.75640 | 0.08977 | 30.03212 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.72347 | 55.54531 | -0.0602 | 6.15606 |
February | 672.00000 | 21.72710 | 55.71569 | -0.0557 | 6.10727 |
March | 744.00000 | 21.71632 | 55.38639 | -0.0673 | 6.02957 |
April | 720.00000 | 21.73235 | 55.80233 | -0.0502 | 5.92209 |
May | 744.00000 | 21.73901 | 54.61506 | -1.1373 | 33.53490 |
June | 720.00000 | 21.74281 | 53.92804 | -1.1226 | 32.84901 |
July | 744.00000 | 21.74821 | 53.69025 | -1.1092 | 32.32153 |
August | 744.00000 | 21.74728 | 53.82800 | -1.1133 | 32.51338 |
September | 720.00000 | 21.75703 | 53.91462 | -1.0831 | 31.34354 |
October | 744.00000 | 21.76486 | 54.11041 | -0.0022 | 5.98791 |
November | 720.00000 | 21.74879 | 54.75518 | -0.0251 | 6.04760 |
December | 744.00000 | 21.72212 | 57.03347 | -0.0453 | 6.08290 |
Annual Sum or Average | 8760.00000 | 21.73914 | 54.85622 | -0.4920 | 17.14324 |
Minimum of Months | 672.00000 | 21.71632 | 53.69025 | -1.1373 | 5.92209 |
Maximum of Months | 744.00000 | 21.76486 | 57.03347 | -0.0022 | 33.53490 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.68726 | 57.41481 | 0.49329 | 10.51925 |
February | 672.00000 | 23.73952 | 57.63424 | 0.52145 | 11.05527 |
March | 744.00000 | 23.76383 | 58.35369 | 0.54388 | 11.60583 |
April | 720.00000 | 23.86549 | 61.49777 | 0.61552 | 13.07459 |
May | 744.00000 | 23.91245 | 61.96634 | -0.1922 | 5.85265 |
June | 720.00000 | 23.93572 | 61.54475 | -0.1673 | 5.64407 |
July | 744.00000 | 23.95211 | 61.29544 | -0.1564 | 5.55089 |
August | 744.00000 | 23.92362 | 61.76823 | -0.1782 | 5.74064 |
September | 720.00000 | 23.92356 | 61.57412 | -0.1802 | 5.77109 |
October | 744.00000 | 23.88003 | 62.05663 | 0.63587 | 13.55925 |
November | 720.00000 | 23.80837 | 60.90165 | 0.58431 | 12.37603 |
December | 744.00000 | 23.71078 | 59.99325 | 0.52596 | 11.16248 |
Annual Sum or Average | 8760.00000 | 23.84228 | 60.51399 | 0.25208 | 9.31299 |
Minimum of Months | 672.00000 | 23.68726 | 57.41481 | -0.1922 | 5.55089 |
Maximum of Months | 744.00000 | 23.95211 | 62.05663 | 0.63587 | 13.55925 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.78799 | 56.54179 | 0.54788 | 11.62322 |
February | 672.00000 | 23.83050 | 56.81357 | 0.57303 | 12.16782 |
March | 744.00000 | 23.84209 | 57.57946 | 0.59200 | 12.67506 |
April | 720.00000 | 23.91299 | 60.85208 | 0.65382 | 14.07389 |
May | 744.00000 | 23.94532 | 61.41040 | -0.1439 | 5.48362 |
June | 720.00000 | 23.95939 | 61.05252 | -0.1240 | 5.36119 |
July | 744.00000 | 23.96960 | 60.82840 | -0.1154 | 5.30815 |
August | 744.00000 | 23.95010 | 61.26020 | -0.1338 | 5.42651 |
September | 720.00000 | 23.94908 | 61.07076 | -0.1365 | 5.45953 |
October | 744.00000 | 23.91521 | 61.50198 | 0.66874 | 14.44670 |
November | 720.00000 | 23.86567 | 60.21876 | 0.62497 | 13.36752 |
December | 744.00000 | 23.80018 | 59.15433 | 0.57704 | 12.26434 |
Annual Sum or Average | 8760.00000 | 23.89423 | 59.87172 | 0.29688 | 9.78800 |
Minimum of Months | 672.00000 | 23.78799 | 56.54179 | -0.1439 | 5.30815 |
Maximum of Months | 744.00000 | 23.96960 | 61.50198 | 0.66874 | 14.44670 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.77971 | 55.53760 | 1.18841 | 36.59764 |
February | 672.00000 | 23.79471 | 55.96564 | 1.20882 | 37.53846 |
March | 744.00000 | 23.81909 | 56.82011 | 1.23424 | 38.60049 |
April | 720.00000 | 23.85818 | 60.25196 | 1.29601 | 41.35006 |
May | 744.00000 | 23.88949 | 60.91943 | 0.77710 | 21.44415 |
June | 720.00000 | 23.91655 | 60.60572 | 0.80760 | 22.18052 |
July | 744.00000 | 23.91693 | 60.42609 | 0.81915 | 22.69392 |
August | 744.00000 | 23.90819 | 60.76487 | 0.79518 | 21.84174 |
September | 720.00000 | 23.91062 | 60.53375 | 0.80031 | 22.02433 |
October | 744.00000 | 23.88732 | 60.85045 | 1.32064 | 42.37238 |
November | 720.00000 | 23.83956 | 59.44065 | 1.26759 | 40.04334 |
December | 744.00000 | 23.79334 | 58.18413 | 1.21409 | 37.65137 |
Annual Sum or Average | 8760.00000 | 23.85977 | 59.20708 | 1.05974 | 31.98980 |
Minimum of Months | 672.00000 | 23.77971 | 55.53760 | 0.77710 | 21.44415 |
Maximum of Months | 744.00000 | 23.91693 | 60.91943 | 1.32064 | 42.37238 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.49322 | 53.93553 | 0.06168 | 5.46746 |
February | 672.00000 | 22.62536 | 54.04127 | 0.09713 | 5.60099 |
March | 744.00000 | 22.67482 | 54.96483 | 0.11641 | 5.74630 |
April | 720.00000 | 23.02501 | 57.97524 | 0.22588 | 6.17461 |
May | 744.00000 | 23.40284 | 57.96523 | -0.6393 | 13.70653 |
June | 720.00000 | 23.67520 | 57.05712 | -0.5462 | 11.31607 |
July | 744.00000 | 23.78216 | 56.52999 | -0.5098 | 10.48349 |
August | 744.00000 | 23.61085 | 57.42095 | -0.5672 | 11.86842 |
September | 720.00000 | 23.68027 | 56.91189 | -0.5438 | 11.28981 |
October | 744.00000 | 23.45106 | 57.69913 | 0.33706 | 7.39911 |
November | 720.00000 | 23.10863 | 56.82396 | 0.24124 | 6.44858 |
December | 744.00000 | 22.68168 | 56.41880 | 0.12647 | 5.70755 |
Annual Sum or Average | 8760.00000 | 23.18679 | 56.49088 | -0.1350 | 8.45327 |
Minimum of Months | 672.00000 | 22.49322 | 53.93553 | -0.6393 | 5.46746 |
Maximum of Months | 744.00000 | 23.78216 | 57.97524 | 0.33706 | 13.70653 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.74242 | 57.78183 | 0.11903 | 5.65270 |
February | 672.00000 | 22.81934 | 58.09232 | 0.14082 | 5.73902 |
March | 744.00000 | 22.93925 | 58.77700 | 0.17688 | 5.99884 |
April | 720.00000 | 23.28995 | 61.71022 | 0.28609 | 6.79447 |
May | 744.00000 | 23.43903 | 62.33984 | -0.6439 | 13.79707 |
June | 720.00000 | 23.65223 | 61.57581 | -0.5718 | 11.90582 |
July | 744.00000 | 23.76365 | 61.02159 | -0.5349 | 11.02839 |
August | 744.00000 | 23.66976 | 61.63251 | -0.5653 | 11.78706 |
September | 720.00000 | 23.73965 | 61.13194 | -0.5420 | 11.23893 |
October | 744.00000 | 23.66972 | 61.47038 | 0.38498 | 8.11127 |
November | 720.00000 | 23.29962 | 60.74445 | 0.28316 | 6.85016 |
December | 744.00000 | 22.84392 | 60.48557 | 0.16235 | 5.91996 |
Annual Sum or Average | 8760.00000 | 23.32462 | 60.57597 | -0.1105 | 8.75487 |
Minimum of Months | 672.00000 | 22.74242 | 57.78183 | -0.6439 | 5.65270 |
Maximum of Months | 744.00000 | 23.76365 | 62.33984 | 0.38498 | 13.79707 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.37274 | 55.36367 | 0.05851 | 5.73154 |
February | 672.00000 | 22.58265 | 55.27987 | 0.11435 | 5.92037 |
March | 744.00000 | 22.73092 | 55.83933 | 0.15860 | 6.21809 |
April | 720.00000 | 23.25642 | 58.27487 | 0.31355 | 7.26978 |
May | 744.00000 | 23.58398 | 58.26345 | -0.5316 | 11.13126 |
June | 720.00000 | 23.81401 | 57.34076 | -0.4488 | 9.29464 |
July | 744.00000 | 23.86558 | 56.94264 | -0.4271 | 8.88392 |
August | 744.00000 | 23.76398 | 57.63596 | -0.4657 | 9.69517 |
September | 720.00000 | 23.79476 | 57.26926 | -0.4540 | 9.47043 |
October | 744.00000 | 23.64010 | 57.95101 | 0.41606 | 8.68334 |
November | 720.00000 | 23.13399 | 57.68746 | 0.27706 | 7.07041 |
December | 744.00000 | 22.54089 | 57.92351 | 0.11931 | 6.00751 |
Annual Sum or Average | 8760.00000 | 23.25954 | 57.15757 | -0.0740 | 7.96111 |
Minimum of Months | 672.00000 | 22.37274 | 55.27987 | -0.5316 | 5.73154 |
Maximum of Months | 744.00000 | 23.86558 | 58.27487 | 0.41606 | 11.13126 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.59918 | 53.13252 | 0.08728 | 5.56052 |
February | 672.00000 | 22.73292 | 53.23535 | 0.12337 | 5.74401 |
March | 744.00000 | 22.78592 | 54.13794 | 0.14351 | 5.90812 |
April | 720.00000 | 23.13878 | 57.10277 | 0.25422 | 6.48161 |
May | 744.00000 | 23.50872 | 57.08599 | -0.5992 | 12.70156 |
June | 720.00000 | 23.74724 | 56.25628 | -0.5151 | 10.63822 |
July | 744.00000 | 23.82595 | 55.81591 | -0.4865 | 10.01245 |
August | 744.00000 | 23.68056 | 56.62730 | -0.5378 | 11.19902 |
September | 720.00000 | 23.75001 | 56.12265 | -0.5137 | 10.63653 |
October | 744.00000 | 23.55239 | 56.83601 | 0.36297 | 7.80069 |
November | 720.00000 | 23.22355 | 55.94678 | 0.26965 | 6.76939 |
December | 744.00000 | 22.79512 | 55.57207 | 0.15407 | 5.88314 |
Annual Sum or Average | 8760.00000 | 23.28080 | 55.66818 | -0.1064 | 8.29489 |
Minimum of Months | 672.00000 | 22.59918 | 53.13252 | -0.5992 | 5.56052 |
Maximum of Months | 744.00000 | 23.82595 | 57.10277 | 0.36297 | 12.70156 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.157212E+12 | 146828.31 | 06-JAN-23:00 | 744.00 | 0.493620E+12 | 0.00 | 0.650833E+12 | 3.08 | 4.05 | 02-JAN-22:53 | 0.00 | 0.00 |
February | 0.169987E+12 | 161608.82 | 10-FEB-22:53 | 671.19 | 0.530777E+12 | 0.00 | 0.700764E+12 | 3.07 | 3.95 | 10-FEB-22:53 | 0.00 | 0.00 |
March | 0.207496E+12 | 159353.27 | 09-MAR-22:52 | 743.56 | 0.667336E+12 | 0.00 | 0.874832E+12 | 3.14 | 4.02 | 26-MAR-21:51 | 0.00 | 0.00 |
April | 0.249144E+12 | 170852.55 | 14-APR-15:03 | 720.00 | 0.790922E+12 | 0.00 | 0.104007E+13 | 3.13 | 3.98 | 26-APR-21:53 | 0.00 | 0.00 |
May | 0.318600E+12 | 183871.08 | 29-MAY-18:03 | 744.00 | 0.104150E+13 | 0.00 | 0.136010E+13 | 3.26 | 3.98 | 10-MAY-15:02 | 0.00 | 0.00 |
June | 0.347746E+12 | 194570.96 | 08-JUN-18:03 | 720.00 | 0.114264E+13 | 0.00 | 0.149039E+13 | 3.28 | 3.89 | 05-JUN-22:00 | 0.00 | 0.00 |
July | 0.371942E+12 | 210261.99 | 27-JUL-18:03 | 744.00 | 0.121709E+13 | 0.00 | 0.158904E+13 | 3.28 | 4.09 | 14-JUL-21:54 | 0.00 | 0.00 |
August | 0.368474E+12 | 191614.61 | 21-AUG-16:00 | 744.00 | 0.120897E+13 | 0.00 | 0.157745E+13 | 3.28 | 4.01 | 12-AUG-08:53 | 0.00 | 0.00 |
September | 0.350041E+12 | 202816.62 | 18-SEP-18:03 | 720.00 | 0.115869E+13 | 0.00 | 0.150873E+13 | 3.31 | 4.05 | 04-SEP-21:52 | 0.00 | 0.00 |
October | 0.328882E+12 | 183827.71 | 03-OCT-15:03 | 744.00 | 0.109133E+13 | 0.00 | 0.142021E+13 | 3.31 | 3.95 | 27-OCT-21:53 | 0.00 | 0.00 |
November | 0.258030E+12 | 171089.60 | 29-NOV-19:03 | 720.00 | 0.854579E+12 | 0.00 | 0.111261E+13 | 3.25 | 4.02 | 24-NOV-22:53 | 0.00 | 0.00 |
December | 0.190482E+12 | 169760.48 | 25-DEC-22:53 | 744.00 | 0.623180E+12 | 0.00 | 0.813662E+12 | 3.17 | 4.08 | 24-DEC-22:53 | 0.00 | 0.00 |
Annual Sum or Average | 0.331804E+13 | 8758.75 | 0.108206E+14 | 0.00 | 0.141387E+14 | 3.21 | 0.00 | 0.00 | ||||
Minimum of Months | 0.157212E+12 | 146828.31 | 671.19 | 0.493620E+12 | 0.00 | 0.650833E+12 | 3.07 | 3.89 | 0.00 | 0.00 | ||
Maximum of Months | 0.371942E+12 | 210261.99 | 744.00 | 0.121709E+13 | 0.00 | 0.158904E+13 | 3.31 | 4.09 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.448190E+09 | 0.00 | 159.83 | 19570.50 | 16-JAN-09:56 | 0.00 | 48.48 | 54.46 | 0.00 | 0.00 | 0.00 | 0.09 | 16-JAN-09:56 |
February | 0.485301E+09 | 0.00 | 114.53 | 22139.92 | 22-FEB-09:53 | 0.00 | 40.87 | 46.57 | 0.00 | 0.00 | 0.00 | 0.10 | 22-FEB-09:53 |
March | 0.282141E+09 | 0.00 | 111.45 | 20620.23 | 02-MAR-09:54 | 0.00 | 39.96 | 45.22 | 0.00 | 0.00 | 0.00 | 0.10 | 02-MAR-09:54 |
April | 0.112206E+09 | 0.00 | 63.83 | 19459.18 | 19-APR-08:55 | 0.00 | 31.41 | 35.66 | 0.00 | 0.00 | 0.00 | 0.09 | 19-APR-08:55 |
May | 86107978.58 | 0.00 | 54.06 | 18349.62 | 28-MAY-06:57 | 0.00 | 30.83 | 34.36 | 0.00 | 0.00 | 0.00 | 0.09 | 28-MAY-06:57 |
June | 52290453.16 | 0.00 | 36.30 | 23846.58 | 25-JUN-06:56 | 0.00 | 29.91 | 32.40 | 0.00 | 0.00 | 0.00 | 0.11 | 25-JUN-06:56 |
July | 55282774.80 | 0.00 | 35.59 | 4321.85 | 06-JUL-06:55 | 0.00 | 26.20 | 28.74 | 0.00 | 0.00 | 0.00 | 0.02 | 06-JUL-06:55 |
August | 72835788.71 | 0.00 | 43.32 | 22854.41 | 06-AUG-21:57 | 0.00 | 27.29 | 30.33 | 0.00 | 0.00 | 0.00 | 0.11 | 06-AUG-21:57 |
September | 59620043.25 | 0.00 | 38.83 | 15373.52 | 27-SEP-08:28 | 0.00 | 27.96 | 30.74 | 0.00 | 0.00 | 0.00 | 0.07 | 27-SEP-08:28 |
October | 93611837.44 | 0.00 | 57.52 | 28047.45 | 15-OCT-06:56 | 0.00 | 31.88 | 35.56 | 0.00 | 0.00 | 0.00 | 0.13 | 15-OCT-06:56 |
November | 0.178406E+09 | 0.00 | 79.77 | 21403.15 | 09-NOV-09:17 | 0.00 | 40.32 | 44.41 | 0.00 | 0.00 | 0.00 | 0.10 | 09-NOV-09:17 |
December | 0.497374E+09 | 0.00 | 156.78 | 22899.65 | 12-DEC-16:07 | 0.00 | 45.22 | 51.40 | 0.00 | 0.00 | 0.00 | 0.11 | 12-DEC-16:07 |
Annual Sum or Average | 0.242337E+10 | 0.00 | 951.81 | 0.00 | 35.01 | 39.13 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 52290453.16 | 0.00 | 35.59 | 4321.85 | 0.00 | 26.20 | 28.74 | 0.00 | 0.00 | 0.00 | 0.02 | ||
Maximum of Months | 0.497374E+09 | 0.00 | 159.83 | 28047.45 | 0.00 | 48.48 | 54.46 | 0.00 | 0.00 | 0.00 | 0.13 |
Report: DXReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.418924E+11 | 0.00 | 350.62 | 0.328789E+11 | 0.901350E+10 | 0.00 | 1.00 | 01-JAN-07:05 | 0.00 | 01-JAN-00:10 | 58091.10 | 18-JAN-07:05 | 45861.54 | 11-JAN-09:15 | 13037.12 | 14-JAN-19:06 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.376097E+11 | 0.00 | 314.27 | 0.302531E+11 | 0.735660E+10 | 0.00 | 1.00 | 01-FEB-06:08 | 0.00 | 01-FEB-00:03 | 59216.56 | 01-FEB-06:08 | 47861.12 | 06-FEB-09:15 | 11837.19 | 21-FEB-18:05 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 0.404297E+11 | 0.00 | 350.07 | 0.300455E+11 | 0.103842E+11 | 0.00 | 1.00 | 01-MAR-06:08 | 0.00 | 01-MAR-00:03 | 60292.02 | 01-MAR-07:30 | 44962.12 | 02-MAR-10:05 | 15962.83 | 14-MAR-05:40 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 0.375466E+11 | 0.00 | 331.51 | 0.272709E+11 | 0.102757E+11 | 0.00 | 1.00 | 01-APR-05:08 | 0.00 | 01-APR-00:20 | 62541.59 | 01-APR-17:06 | 45503.40 | 06-APR-10:06 | 17574.93 | 01-APR-05:08 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.371035E+11 | 0.00 | 342.87 | 0.222447E+11 | 0.148588E+11 | 0.00 | 1.00 | 01-MAY-05:15 | 0.00 | 01-MAY-00:05 | 65270.26 | 01-MAY-05:15 | 39359.52 | 04-MAY-10:07 | 26452.92 | 06-MAY-17:07 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.345934E+11 | 0.00 | 330.89 | 0.182164E+11 | 0.163770E+11 | 0.00 | 1.00 | 01-JUN-05:08 | 0.00 | 01-JUN-00:05 | 66681.58 | 01-JUN-07:03 | 35238.49 | 17-JUN-10:05 | 31756.42 | 01-JUN-15:08 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.350748E+11 | 0.00 | 341.30 | 0.188589E+11 | 0.162160E+11 | 0.00 | 1.00 | 01-JUL-05:08 | 0.00 | 01-JUL-00:20 | 66623.57 | 01-JUL-05:08 | 36081.00 | 05-JUL-10:06 | 31244.96 | 28-JUL-15:08 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.355570E+11 | 0.00 | 339.55 | 0.186578E+11 | 0.168993E+11 | 0.00 | 1.00 | 01-AUG-07:04 | 0.00 | 01-AUG-00:05 | 66916.04 | 31-AUG-05:08 | 35245.70 | 31-AUG-09:05 | 31961.49 | 29-AUG-17:15 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.357631E+11 | 0.00 | 330.64 | 0.187601E+11 | 0.170030E+11 | 0.00 | 1.00 | 01-SEP-05:08 | 0.00 | 01-SEP-00:05 | 67009.49 | 30-SEP-05:08 | 35339.42 | 23-SEP-08:03 | 32091.58 | 28-SEP-15:08 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.388550E+11 | 0.00 | 340.07 | 0.220808E+11 | 0.167742E+11 | 0.00 | 1.00 | 01-OCT-06:37 | 0.00 | 01-OCT-00:10 | 66174.36 | 31-OCT-05:30 | 37753.92 | 30-OCT-09:05 | 28775.17 | 31-OCT-17:15 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.391882E+11 | 0.00 | 336.66 | 0.246543E+11 | 0.145340E+11 | 0.00 | 1.00 | 01-NOV-05:08 | 0.00 | 01-NOV-00:05 | 63356.17 | 30-NOV-06:08 | 40065.36 | 28-NOV-08:15 | 23975.05 | 25-NOV-16:07 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.415412E+11 | 0.00 | 349.03 | 0.282775E+11 | 0.132637E+11 | 0.00 | 1.00 | 01-DEC-06:08 | 0.00 | 01-DEC-00:03 | 59770.14 | 31-DEC-06:07 | 40939.76 | 27-DEC-06:08 | 19531.69 | 25-DEC-16:07 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.455155E+12 | 0.00 | 4057.49 | 0.292199E+12 | 0.162956E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.345934E+11 | 0.00 | 314.27 | 0.182164E+11 | 0.735660E+10 | 0.00 | 1.00 | 0.00 | 58091.10 | 35238.49 | 11837.19 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.418924E+11 | 0.00 | 350.62 | 0.328789E+11 | 0.170030E+11 | 0.00 | 1.00 | 0.00 | 67009.49 | 47861.12 | 32091.58 | 0.00 | 0.00 |
Report: DXReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.581299E+11 | 0.00 | 349.23 | 0.456330E+11 | 0.124969E+11 | 0.00 | 1.00 | 01-JAN-17:10 | 0.00 | 01-JAN-00:10 | 73521.09 | 18-JAN-23:20 | 58059.41 | 24-JAN-20:20 | 16505.56 | 14-JAN-19:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.534455E+11 | 0.00 | 314.73 | 0.429976E+11 | 0.104480E+11 | 0.00 | 1.00 | 01-FEB-17:10 | 0.00 | 01-FEB-00:07 | 74946.18 | 01-FEB-17:10 | 60573.06 | 11-FEB-19:15 | 14965.35 | 21-FEB-17:10 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 0.600883E+11 | 0.00 | 347.01 | 0.446671E+11 | 0.154212E+11 | 0.00 | 1.00 | 01-MAR-17:10 | 0.00 | 01-MAR-00:07 | 76307.98 | 01-MAR-17:10 | 56920.36 | 02-MAR-22:00 | 20243.19 | 14-MAR-16:10 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 0.602515E+11 | 0.00 | 335.06 | 0.437671E+11 | 0.164845E+11 | 0.00 | 1.00 | 01-APR-16:05 | 0.00 | 01-APR-00:20 | 79156.46 | 01-APR-20:40 | 57597.05 | 07-APR-19:00 | 22173.19 | 01-APR-16:05 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.649529E+11 | 0.00 | 347.39 | 0.389379E+11 | 0.260150E+11 | 0.00 | 1.00 | 01-MAY-16:10 | 0.00 | 01-MAY-00:05 | 82611.60 | 01-MAY-19:30 | 49849.42 | 03-MAY-22:00 | 33470.17 | 06-MAY-16:20 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.643011E+11 | 0.00 | 327.39 | 0.338576E+11 | 0.304435E+11 | 0.00 | 1.00 | 01-JUN-16:10 | 0.00 | 01-JUN-00:05 | 84398.66 | 01-JUN-16:40 | 44541.65 | 15-JUN-23:00 | 40238.07 | 01-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.665251E+11 | 0.00 | 338.43 | 0.357643E+11 | 0.307608E+11 | 0.00 | 1.00 | 01-JUL-16:10 | 0.00 | 01-JUL-00:10 | 84325.21 | 01-JUL-16:10 | 45679.57 | 04-JUL-21:00 | 39537.36 | 28-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.666775E+11 | 0.00 | 338.79 | 0.349827E+11 | 0.316948E+11 | 0.00 | 1.00 | 01-AUG-16:10 | 0.00 | 01-AUG-00:05 | 84695.55 | 31-AUG-16:10 | 44619.50 | 31-AUG-22:00 | 40444.69 | 29-AUG-17:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.645630E+11 | 0.00 | 326.83 | 0.338596E+11 | 0.307034E+11 | 0.00 | 1.00 | 01-SEP-16:10 | 0.00 | 01-SEP-00:05 | 84813.88 | 30-SEP-18:00 | 44659.28 | 23-SEP-21:00 | 40609.57 | 28-SEP-16:10 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.658294E+11 | 0.00 | 351.06 | 0.374037E+11 | 0.284257E+11 | 0.00 | 1.00 | 01-OCT-16:10 | 0.00 | 01-OCT-00:10 | 83756.41 | 31-OCT-16:20 | 47785.75 | 29-OCT-23:00 | 36410.65 | 31-OCT-17:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.610903E+11 | 0.00 | 336.50 | 0.384362E+11 | 0.226541E+11 | 0.00 | 1.00 | 01-NOV-16:10 | 0.00 | 01-NOV-00:05 | 80187.92 | 30-NOV-17:10 | 50791.31 | 28-NOV-22:20 | 30321.47 | 25-NOV-17:05 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.596971E+11 | 0.00 | 349.87 | 0.406477E+11 | 0.190494E+11 | 0.00 | 1.00 | 01-DEC-17:10 | 0.00 | 01-DEC-00:07 | 75647.15 | 31-DEC-18:25 | 51847.67 | 30-DEC-17:20 | 24708.23 | 25-DEC-17:10 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.745552E+12 | 0.00 | 4062.30 | 0.470954E+12 | 0.274597E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.534455E+11 | 0.00 | 314.73 | 0.338576E+11 | 0.104480E+11 | 0.00 | 1.00 | 0.00 | 73521.09 | 44541.65 | 14965.35 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.666775E+11 | 0.00 | 351.06 | 0.456330E+11 | 0.316948E+11 | 0.00 | 1.00 | 0.00 | 84813.88 | 60573.06 | 40609.57 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.353754E+12 | 0.00 | 711.93 | 0.229125E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 473989.75 | 06-JAN-23:00 | 210159.68 | 13-JAN-22:00 | 0.00 | 0.00 | 0.00 |
February | 0.389474E+12 | 0.00 | 647.94 | 0.258860E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 460870.60 | 10-FEB-21:40 | 202971.60 | 17-FEB-22:00 | 0.00 | 0.00 | 0.00 |
March | 0.500675E+12 | 0.00 | 719.54 | 0.313695E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 481065.78 | 09-MAR-21:10 | 213865.13 | 13-MAR-18:10 | 0.00 | 0.00 | 0.00 |
April | 0.596922E+12 | 0.00 | 720.00 | 0.383159E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 410568.17 | 12-APR-22:00 | 230889.06 | 17-APR-18:10 | 0.00 | 0.00 | 0.00 |
May | 0.806314E+12 | 0.00 | 744.00 | 0.459113E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 493133.81 | 24-MAY-18:50 | 241350.72 | 22-MAY-20:10 | 0.00 | 0.00 | 0.00 |
June | 0.892463E+12 | 0.00 | 720.00 | 0.474746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 484509.27 | 05-JUN-21:00 | 251623.72 | 07-JUN-21:00 | 0.00 | 0.00 | 0.00 |
July | 0.949067E+12 | 0.00 | 744.00 | 0.502938E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 486029.55 | 27-JUL-19:20 | 258862.56 | 28-JUL-18:10 | 0.00 | 0.00 | 0.00 |
August | 0.950082E+12 | 0.00 | 744.00 | 0.496105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 515843.28 | 06-AUG-21:00 | 252724.41 | 02-AUG-21:00 | 0.00 | 0.00 | 0.00 |
September | 0.901923E+12 | 0.00 | 720.00 | 0.477934E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 591225.09 | 25-SEP-21:00 | 268395.98 | 08-SEP-20:10 | 0.00 | 0.00 | 0.00 |
October | 0.842285E+12 | 0.00 | 744.00 | 0.466845E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 509794.34 | 01-OCT-20:00 | 246817.77 | 03-OCT-21:00 | 0.00 | 0.00 | 0.00 |
November | 0.654036E+12 | 0.00 | 712.25 | 0.366809E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 521365.77 | 21-NOV-21:20 | 236553.03 | 03-NOV-21:00 | 0.00 | 0.00 | 0.00 |
December | 0.465812E+12 | 0.00 | 709.11 | 0.268251E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 515038.08 | 25-DEC-22:00 | 214924.40 | 08-DEC-21:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.830281E+13 | 0.00 | 8636.77 | 0.469758E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.353754E+12 | 0.00 | 647.94 | 0.229125E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 410568.17 | 202971.60 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.950082E+12 | 0.00 | 744.00 | 0.502938E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 591225.09 | 268395.98 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.302241E+11 | 0.00 | 484.17 | 0.179787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43680.71 | 07-JAN-09:02 | 18854.10 | 07-JAN-13:20 | 0.00 | 0.00 | 0.00 |
February | 0.328775E+11 | 0.00 | 473.67 | 0.206174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41144.18 | 11-FEB-19:02 | 19317.40 | 11-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.396807E+11 | 0.00 | 526.50 | 0.252752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44822.51 | 14-MAR-08:62 | 19293.91 | 13-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.465830E+11 | 0.00 | 568.83 | 0.302868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42394.34 | 16-APR-08:62 | 20305.36 | 17-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.562843E+11 | 0.00 | 589.00 | 0.335876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48516.27 | 28-MAY-18:05 | 21306.15 | 22-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.604233E+11 | 0.00 | 570.00 | 0.336285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43517.00 | 18-JUN-20:50 | 20521.46 | 11-JUN-13:00 | 0.00 | 0.00 | 0.00 |
July | 0.630075E+11 | 0.00 | 589.00 | 0.349588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46717.94 | 02-JUL-17:00 | 21651.94 | 28-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.637900E+11 | 0.00 | 589.00 | 0.349145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45950.57 | 12-AUG-08:07 | 21198.59 | 23-AUG-13:00 | 0.00 | 0.00 | 0.00 |
September | 0.600955E+11 | 0.00 | 570.00 | 0.334625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44272.90 | 04-SEP-21:51 | 20501.64 | 08-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.578633E+11 | 0.00 | 589.00 | 0.335546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45192.41 | 01-OCT-08:20 | 20366.76 | 03-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.488820E+11 | 0.00 | 546.00 | 0.279205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47072.13 | 08-NOV-09:03 | 19298.68 | 17-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.380129E+11 | 0.00 | 510.50 | 0.213610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49467.94 | 23-DEC-19:03 | 19076.60 | 10-DEC-13:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.597724E+12 | 0.00 | 6605.67 | 0.347546E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.302241E+11 | 0.00 | 473.67 | 0.179787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41144.18 | 18854.10 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.637900E+11 | 0.00 | 589.00 | 0.349588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49467.94 | 21651.94 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.517064E+10 | 0.00 | 646.00 | 0.281574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15446.47 | 07-JAN-09:02 | 11169.34 | 23-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.581146E+10 | 0.00 | 590.95 | 0.337414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14995.44 | 02-FEB-09:02 | 11199.20 | 17-FEB-19:02 | 0.00 | 0.00 | 0.00 |
March | 0.731782E+10 | 0.00 | 665.04 | 0.442821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15324.33 | 19-MAR-08:62 | 11367.59 | 27-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.882649E+10 | 0.00 | 682.25 | 0.560871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14153.47 | 29-APR-08:62 | 11435.11 | 22-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.995639E+10 | 0.00 | 712.04 | 0.648341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14100.64 | 24-MAY-18:02 | 11455.09 | 31-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.101219E+11 | 0.00 | 690.62 | 0.669793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13244.39 | 13-JUN-08:61 | 11484.41 | 04-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.113328E+11 | 0.00 | 716.98 | 0.778782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12769.95 | 14-JUL-18:02 | 11417.70 | 11-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.107602E+11 | 0.00 | 713.00 | 0.725385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14850.67 | 12-AUG-08:62 | 11494.68 | 03-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.105904E+11 | 0.00 | 692.83 | 0.713963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13348.27 | 05-SEP-08:62 | 11463.17 | 11-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.102334E+11 | 0.00 | 714.22 | 0.676276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14346.51 | 31-OCT-08:62 | 11521.63 | 02-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.775763E+10 | 0.00 | 666.08 | 0.469822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14465.53 | 24-NOV-09:02 | 11373.33 | 18-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.600109E+10 | 0.00 | 642.82 | 0.341092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15520.52 | 23-DEC-09:02 | 11412.32 | 07-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103880E+12 | 0.00 | 8132.82 | 0.664614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.517064E+10 | 0.00 | 590.95 | 0.281574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12769.95 | 11169.34 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.113328E+11 | 0.00 | 716.98 | 0.778782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15520.52 | 11521.63 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.235847E+10 | 0.00 | 386.77 | 0.106241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16094.01 | 07-JAN-09:52 | 11462.47 | 03-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.323888E+10 | 0.00 | 379.10 | 0.171332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15655.36 | 18-FEB-09:51 | 11594.48 | 17-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.488580E+10 | 0.00 | 460.10 | 0.283521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16928.15 | 14-MAR-08:21 | 11651.01 | 13-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.716208E+10 | 0.00 | 526.68 | 0.457811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16075.01 | 22-APR-08:21 | 11563.44 | 22-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.967099E+10 | 0.00 | 672.14 | 0.634840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15833.50 | 24-MAY-20:51 | 11923.12 | 10-MAY-16:31 | 0.00 | 0.00 | 0.00 |
June | 0.101809E+11 | 0.00 | 677.15 | 0.679492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16085.39 | 18-JUN-21:51 | 12095.14 | 13-JUN-18:11 | 0.00 | 0.00 | 0.00 |
July | 0.112547E+11 | 0.00 | 697.47 | 0.777868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15490.66 | 02-JUL-21:51 | 12526.84 | 05-JUL-17:52 | 0.00 | 0.00 | 0.00 |
August | 0.104612E+11 | 0.00 | 699.75 | 0.698623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15590.36 | 12-AUG-08:52 | 12552.24 | 23-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.970626E+10 | 0.00 | 663.17 | 0.635346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16031.91 | 16-SEP-07:52 | 11811.90 | 17-SEP-07:51 | 0.00 | 0.00 | 0.00 |
October | 0.865531E+10 | 0.00 | 664.23 | 0.539941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15888.55 | 21-OCT-08:61 | 11628.52 | 03-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.565120E+10 | 0.00 | 540.04 | 0.315553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15864.89 | 22-NOV-08:51 | 11610.96 | 22-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.328035E+10 | 0.00 | 399.15 | 0.170475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16099.44 | 10-DEC-09:01 | 11422.21 | 09-DEC-19:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.865062E+11 | 0.00 | 6765.74 | 0.547104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.235847E+10 | 0.00 | 379.10 | 0.106241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15490.66 | 11422.21 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.112547E+11 | 0.00 | 699.75 | 0.777868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16928.15 | 12552.24 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.419547E+11 | 0.00 | 704.18 | 0.279730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47193.07 | 02-JAN-14:30 | 40506.32 | 02-JAN-14:30 | 0.00 | 0.00 | 0.00 |
February | 0.369577E+11 | 0.00 | 643.43 | 0.235214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40416.41 | 11-FEB-14:30 | 31975.80 | 11-FEB-14:30 | 0.00 | 0.00 | 0.00 |
March | 0.367904E+11 | 0.00 | 702.21 | 0.217518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34507.77 | 04-MAR-11:35 | 31266.90 | 02-MAR-13:40 | 0.00 | 0.00 | 0.00 |
April | 0.374885E+11 | 0.00 | 712.35 | 0.208121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28772.82 | 15-APR-15:02 | 22119.38 | 15-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.409827E+11 | 0.00 | 740.11 | 0.220929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27903.47 | 14-MAY-08:00 | 20063.14 | 22-MAY-17:20 | 0.00 | 0.00 | 0.00 |
June | 0.438517E+11 | 0.00 | 719.33 | 0.247817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27662.03 | 03-JUN-08:00 | 21122.23 | 03-JUN-20:40 | 0.00 | 0.00 | 0.00 |
July | 0.487700E+11 | 0.00 | 744.00 | 0.293595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30279.52 | 29-JUL-16:10 | 25887.07 | 29-JUL-17:20 | 0.00 | 0.00 | 0.00 |
August | 0.483575E+11 | 0.00 | 741.92 | 0.292270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30580.53 | 20-AUG-08:00 | 25710.76 | 20-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.546629E+11 | 0.00 | 720.00 | 0.370691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38684.32 | 30-SEP-13:40 | 31348.21 | 19-SEP-14:00 | 0.00 | 0.00 | 0.00 |
October | 0.589190E+11 | 0.00 | 744.00 | 0.404459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43410.19 | 25-OCT-14:00 | 36831.55 | 25-OCT-12:40 | 0.00 | 0.00 | 0.00 |
November | 0.503939E+11 | 0.00 | 706.99 | 0.340112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47107.58 | 07-NOV-13:30 | 40985.58 | 07-NOV-13:40 | 0.00 | 0.00 | 0.00 |
December | 0.440074E+11 | 0.00 | 710.74 | 0.290583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47990.86 | 03-DEC-13:40 | 42574.65 | 03-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.543136E+12 | 0.00 | 8589.25 | 0.340104E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.367904E+11 | 0.00 | 643.43 | 0.208121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27662.03 | 20063.14 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.589190E+11 | 0.00 | 744.00 | 0.404459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47990.86 | 42574.65 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.261361E+11 | 0.00 | 377.71 | 0.153833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102028.12 | 07-JAN-09:52 | 70079.51 | 06-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.287639E+11 | 0.00 | 352.49 | 0.179596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98815.58 | 17-FEB-09:21 | 72258.95 | 22-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.386105E+11 | 0.00 | 425.85 | 0.244078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108661.24 | 14-MAR-08:21 | 72055.26 | 13-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.496003E+11 | 0.00 | 475.94 | 0.326347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100364.35 | 22-APR-08:21 | 73856.28 | 16-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.674707E+11 | 0.00 | 622.63 | 0.461713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 101583.08 | 25-MAY-21:51 | 73661.72 | 22-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.726291E+11 | 0.00 | 630.74 | 0.512669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102359.93 | 18-JUN-21:51 | 73635.12 | 01-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.764791E+11 | 0.00 | 659.49 | 0.544531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96076.66 | 02-JUL-21:51 | 74264.17 | 05-JUL-17:52 | 0.00 | 0.00 | 0.00 |
August | 0.710390E+11 | 0.00 | 648.14 | 0.490307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98514.79 | 12-AUG-08:52 | 73379.84 | 05-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.669566E+11 | 0.00 | 612.68 | 0.461701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102387.77 | 16-SEP-07:52 | 73633.08 | 14-SEP-08:61 | 0.00 | 0.00 | 0.00 |
October | 0.599565E+11 | 0.00 | 604.89 | 0.385517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98196.55 | 31-OCT-08:31 | 73246.47 | 05-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.445742E+11 | 0.00 | 493.03 | 0.276967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100465.52 | 22-NOV-08:51 | 73079.21 | 21-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 0.302148E+11 | 0.00 | 394.63 | 0.178288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 101922.39 | 10-DEC-09:01 | 72262.46 | 09-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.632431E+12 | 0.00 | 6298.20 | 0.421555E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.261361E+11 | 0.00 | 352.49 | 0.153833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96076.66 | 70079.51 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.764791E+11 | 0.00 | 659.49 | 0.544531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108661.24 | 74264.17 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.544126E+10 | 0.00 | 655.04 | 0.309928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13524.38 | 07-JAN-09:02 | 10018.55 | 23-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.584844E+10 | 0.00 | 608.53 | 0.342412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13188.42 | 18-FEB-09:02 | 10176.80 | 19-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.722284E+10 | 0.00 | 690.85 | 0.434218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13722.31 | 19-MAR-08:62 | 10240.18 | 09-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.878044E+10 | 0.00 | 696.63 | 0.560834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12583.16 | 29-APR-08:62 | 10208.22 | 13-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.999034E+10 | 0.00 | 722.82 | 0.660374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12879.17 | 24-MAY-18:02 | 10307.87 | 30-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.106890E+11 | 0.00 | 702.26 | 0.739434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10951.63 | 05-JUN-08:62 | 10299.89 | 09-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.116867E+11 | 0.00 | 726.75 | 0.836412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11275.16 | 02-JUL-18:02 | 10292.32 | 03-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.107819E+11 | 0.00 | 720.77 | 0.746938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13288.97 | 12-AUG-08:62 | 10297.02 | 30-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.109893E+11 | 0.00 | 701.40 | 0.778475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11771.58 | 05-SEP-08:62 | 10297.02 | 01-SEP-08:62 | 0.00 | 0.00 | 0.00 |
October | 0.103902E+11 | 0.00 | 722.37 | 0.708136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12806.75 | 31-OCT-08:62 | 10299.07 | 15-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.783136E+10 | 0.00 | 679.84 | 0.485920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12960.09 | 24-NOV-09:02 | 10221.34 | 05-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 0.562259E+10 | 0.00 | 641.84 | 0.315710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13901.71 | 23-DEC-09:02 | 10276.65 | 25-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105274E+12 | 0.00 | 8269.12 | 0.691879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.544126E+10 | 0.00 | 608.53 | 0.309928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10951.63 | 10018.55 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.116867E+11 | 0.00 | 726.75 | 0.836412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13901.71 | 10307.87 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.261697E+10 | 0.00 | 393.55 | 0.131920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14563.11 | 07-JAN-09:52 | 10051.68 | 03-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.322529E+10 | 0.00 | 394.37 | 0.171911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14465.26 | 17-FEB-09:21 | 10914.88 | 28-FEB-09:51 | 0.00 | 0.00 | 0.00 |
March | 0.483215E+10 | 0.00 | 485.44 | 0.279512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15221.63 | 04-MAR-08:51 | 10591.34 | 02-MAR-09:51 | 0.00 | 0.00 | 0.00 |
April | 0.706980E+10 | 0.00 | 534.48 | 0.449327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14957.45 | 22-APR-08:21 | 11216.35 | 21-APR-08:31 | 0.00 | 0.00 | 0.00 |
May | 0.968242E+10 | 0.00 | 681.60 | 0.644365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14719.74 | 07-MAY-08:11 | 10734.62 | 06-MAY-07:31 | 0.00 | 0.00 | 0.00 |
June | 0.107341E+11 | 0.00 | 687.61 | 0.749409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14628.12 | 13-JUN-07:51 | 11111.33 | 22-JUN-07:52 | 0.00 | 0.00 | 0.00 |
July | 0.115986E+11 | 0.00 | 706.57 | 0.835038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13997.47 | 02-JUL-21:51 | 10922.10 | 05-JUL-17:52 | 0.00 | 0.00 | 0.00 |
August | 0.104779E+11 | 0.00 | 707.75 | 0.714710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14349.53 | 29-AUG-07:52 | 11032.21 | 23-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.100986E+11 | 0.00 | 671.56 | 0.689164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14570.84 | 16-SEP-07:52 | 11548.33 | 17-SEP-07:51 | 0.00 | 0.00 | 0.00 |
October | 0.878510E+10 | 0.00 | 671.15 | 0.556471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14750.05 | 21-OCT-08:61 | 10714.72 | 17-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.564963E+10 | 0.00 | 547.98 | 0.327485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15072.62 | 22-NOV-08:51 | 10421.69 | 05-NOV-18:02 | 0.00 | 0.00 | 0.00 |
December | 0.299804E+10 | 0.00 | 390.77 | 0.156669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14789.73 | 07-DEC-08:52 | 10285.64 | 06-DEC-08:52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.877686E+11 | 0.00 | 6872.82 | 0.570598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.261697E+10 | 0.00 | 390.77 | 0.131920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13997.47 | 10051.68 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.115986E+11 | 0.00 | 707.75 | 0.835038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15221.63 | 11548.33 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.115915E+10 | 0.00 | 584.21 | 0.611865E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4307.53 | 07-JAN-09:02 | 2963.08 | 06-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.138587E+10 | 0.00 | 568.81 | 0.781230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4151.66 | 02-FEB-09:02 | 2945.61 | 17-FEB-19:02 | 0.00 | 0.00 | 0.00 |
March | 0.179359E+10 | 0.00 | 640.69 | 0.105744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4210.28 | 19-MAR-08:62 | 3007.44 | 13-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.222745E+10 | 0.00 | 679.63 | 0.139196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3939.15 | 29-APR-08:62 | 2979.51 | 06-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.256110E+10 | 0.00 | 710.93 | 0.164927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3869.10 | 24-MAY-18:02 | 3002.43 | 31-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.261355E+10 | 0.00 | 690.48 | 0.170647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3679.27 | 13-JUN-08:61 | 3006.62 | 04-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.293952E+10 | 0.00 | 718.04 | 0.200185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3423.88 | 04-JUL-08:62 | 3013.80 | 11-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.276621E+10 | 0.00 | 712.37 | 0.184095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4156.95 | 12-AUG-08:62 | 3024.61 | 08-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.269863E+10 | 0.00 | 691.59 | 0.179232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3744.29 | 05-SEP-08:62 | 3024.23 | 06-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.255258E+10 | 0.00 | 710.84 | 0.164708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4020.96 | 31-OCT-08:62 | 3033.40 | 12-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.187186E+10 | 0.00 | 647.62 | 0.110280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4023.98 | 24-NOV-09:02 | 3005.93 | 18-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.139087E+10 | 0.00 | 593.02 | 0.771162E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4352.38 | 23-DEC-09:02 | 2977.89 | 10-DEC-19:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259604E+11 | 0.00 | 7948.23 | 0.163544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.115915E+10 | 0.00 | 568.81 | 0.611865E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3423.88 | 2945.61 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.293952E+10 | 0.00 | 718.04 | 0.200185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4352.38 | 3033.40 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.492648E+09 | 0.00 | 314.27 | 0.215364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4394.07 | 07-JAN-09:52 | 2994.14 | 02-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.769752E+09 | 0.00 | 347.59 | 0.400385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4288.40 | 17-FEB-09:21 | 2996.54 | 17-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.121435E+10 | 0.00 | 439.24 | 0.692216E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4661.37 | 14-MAR-08:21 | 3025.88 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.184511E+10 | 0.00 | 527.74 | 0.116608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4370.24 | 22-APR-08:21 | 3002.11 | 06-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.250088E+10 | 0.00 | 672.28 | 0.163253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4361.17 | 24-MAY-20:51 | 3102.64 | 10-MAY-16:31 | 0.00 | 0.00 | 0.00 |
June | 0.263364E+10 | 0.00 | 677.36 | 0.173671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4416.07 | 18-JUN-21:51 | 3183.85 | 13-JUN-18:11 | 0.00 | 0.00 | 0.00 |
July | 0.292773E+10 | 0.00 | 698.66 | 0.201030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4228.33 | 02-JUL-21:51 | 3250.77 | 05-JUL-17:52 | 0.00 | 0.00 | 0.00 |
August | 0.269262E+10 | 0.00 | 699.16 | 0.177518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4274.82 | 12-AUG-08:52 | 3305.58 | 23-AUG-17:52 | 0.00 | 0.00 | 0.00 |
September | 0.248038E+10 | 0.00 | 662.30 | 0.159978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4432.40 | 16-SEP-07:52 | 3066.67 | 12-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.215596E+10 | 0.00 | 662.76 | 0.130230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4312.44 | 21-OCT-08:61 | 3049.29 | 03-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.136004E+10 | 0.00 | 521.89 | 0.728700E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4348.32 | 10-NOV-08:51 | 3050.49 | 01-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 0.753992E+09 | 0.00 | 345.69 | 0.383436E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4422.11 | 10-DEC-09:01 | 3000.93 | 09-DEC-19:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218271E+11 | 0.00 | 6568.93 | 0.136430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.492648E+09 | 0.00 | 314.27 | 0.215364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4228.33 | 2994.14 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.292773E+10 | 0.00 | 699.16 | 0.201030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4661.37 | 3305.58 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.108852E+11 | 0.00 | 684.32 | 0.749679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17292.40 | 07-JAN-09:02 | 12310.83 | 29-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.102759E+11 | 0.00 | 614.80 | 0.685644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16889.90 | 02-FEB-09:02 | 12198.02 | 11-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.108139E+11 | 0.00 | 676.92 | 0.706754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17502.38 | 06-MAR-09:02 | 12121.90 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.112801E+11 | 0.00 | 675.97 | 0.735365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15989.98 | 29-APR-18:02 | 12391.58 | 17-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.123659E+11 | 0.00 | 706.01 | 0.815197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16713.69 | 24-MAY-18:02 | 12394.49 | 29-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.129082E+11 | 0.00 | 686.47 | 0.884784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14786.90 | 13-JUN-08:61 | 12354.45 | 04-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.141380E+11 | 0.00 | 712.48 | 0.995033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14899.76 | 02-JUL-18:02 | 12379.91 | 27-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.139081E+11 | 0.00 | 709.17 | 0.976287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17351.93 | 12-AUG-08:62 | 12287.28 | 30-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.150429E+11 | 0.00 | 692.61 | 0.109117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15148.18 | 05-SEP-08:62 | 12384.37 | 10-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.157867E+11 | 0.00 | 718.28 | 0.115900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16474.18 | 31-OCT-08:62 | 12398.05 | 28-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.133658E+11 | 0.00 | 682.88 | 0.943643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16769.46 | 24-NOV-09:02 | 12388.09 | 03-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 0.115983E+11 | 0.00 | 684.15 | 0.788447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17525.26 | 23-DEC-09:02 | 12223.63 | 01-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152369E+12 | 0.00 | 8244.07 | 0.105310E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.102759E+11 | 0.00 | 614.80 | 0.685644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14786.90 | 12121.90 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.157867E+11 | 0.00 | 718.28 | 0.115900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17525.26 | 12398.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 486.34 | 316.24 | 170.10 | 794.27 | 211.10 | 0.00 | 0.00 | 0.00 |
February | 429.33 | 244.18 | 185.15 | 739.20 | 175.83 | 0.00 | 0.00 | 0.00 |
March | 331.80 | 137.18 | 194.62 | 582.41 | 141.31 | 0.00 | 0.00 | 0.00 |
April | 237.90 | 48.73 | 189.17 | 469.88 | 86.80 | 0.00 | 0.00 | 0.00 |
May | 185.75 | 5.90 | 179.85 | 408.53 | 31.07 | 0.00 | 0.00 | 0.00 |
June | 175.21 | 0.36 | 174.85 | 416.56 | 9.88 | 0.00 | 0.00 | 0.00 |
July | 187.48 | 1.57 | 185.91 | 458.11 | 18.89 | 0.00 | 0.00 | 0.00 |
August | 210.77 | 15.76 | 195.00 | 494.00 | 8.81 | 0.00 | 0.00 | 0.00 |
September | 273.32 | 67.52 | 205.79 | 626.87 | 27.07 | 0.00 | 0.00 | 0.00 |
October | 379.32 | 180.36 | 198.96 | 759.58 | 47.04 | 0.00 | 0.00 | 0.00 |
November | 429.72 | 241.17 | 188.55 | 771.02 | 101.28 | 0.00 | 0.00 | 0.00 |
December | 468.89 | 296.06 | 172.83 | 783.42 | 183.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 315.80 | 129.08 | 186.71 | 607.99 | 86.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.21 | 0.36 | 170.10 | 408.53 | 8.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 486.34 | 316.24 | 205.79 | 794.27 | 211.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1369.50 | 890.50 | 479.00 | 2203.30 | 665.16 | 0.00 | 0.00 | 0.00 |
February | 1208.97 | 687.59 | 521.38 | 2050.32 | 555.13 | 0.00 | 0.00 | 0.00 |
March | 934.32 | 386.29 | 548.03 | 1617.82 | 448.87 | 0.00 | 0.00 | 0.00 |
April | 669.92 | 137.23 | 532.69 | 1312.82 | 274.35 | 0.00 | 0.00 | 0.00 |
May | 523.06 | 16.60 | 506.46 | 1151.37 | 102.43 | 0.00 | 0.00 | 0.00 |
June | 493.39 | 1.03 | 492.36 | 1183.19 | 34.89 | 0.00 | 0.00 | 0.00 |
July | 527.93 | 4.43 | 523.50 | 1303.14 | 56.28 | 0.00 | 0.00 | 0.00 |
August | 593.50 | 44.38 | 549.12 | 1393.64 | 32.18 | 0.00 | 0.00 | 0.00 |
September | 769.64 | 190.14 | 579.50 | 1764.08 | 83.85 | 0.00 | 0.00 | 0.00 |
October | 1068.14 | 507.89 | 560.25 | 2126.91 | 146.02 | 0.00 | 0.00 | 0.00 |
November | 1210.05 | 679.12 | 530.93 | 2147.61 | 318.85 | 0.00 | 0.00 | 0.00 |
December | 1320.36 | 833.69 | 486.67 | 2177.45 | 579.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 889.27 | 363.49 | 525.77 | 1700.88 | 273.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 493.39 | 1.03 | 479.00 | 1151.37 | 32.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1369.50 | 890.50 | 579.50 | 2203.30 | 665.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1779.06 | 1156.81 | 622.25 | 2946.24 | 866.87 | 0.00 | 0.00 | 0.00 |
February | 1570.52 | 893.22 | 677.31 | 2748.18 | 718.33 | 0.00 | 0.00 | 0.00 |
March | 1213.73 | 501.81 | 711.92 | 2173.52 | 580.22 | 0.00 | 0.00 | 0.00 |
April | 870.27 | 178.27 | 692.00 | 1768.59 | 351.50 | 0.00 | 0.00 | 0.00 |
May | 679.49 | 21.57 | 657.92 | 1550.03 | 129.11 | 0.00 | 0.00 | 0.00 |
June | 640.94 | 1.33 | 639.60 | 1595.20 | 43.91 | 0.00 | 0.00 | 0.00 |
July | 685.82 | 5.76 | 680.06 | 1762.65 | 70.56 | 0.00 | 0.00 | 0.00 |
August | 770.99 | 57.66 | 713.34 | 1884.25 | 39.11 | 0.00 | 0.00 | 0.00 |
September | 999.80 | 247.00 | 752.80 | 2387.29 | 104.55 | 0.00 | 0.00 | 0.00 |
October | 1387.58 | 659.78 | 727.80 | 2860.54 | 173.45 | 0.00 | 0.00 | 0.00 |
November | 1571.93 | 882.22 | 689.71 | 2878.81 | 404.56 | 0.00 | 0.00 | 0.00 |
December | 1715.22 | 1083.01 | 632.21 | 2906.63 | 750.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1155.21 | 472.20 | 683.01 | 2286.15 | 351.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 640.94 | 1.33 | 622.25 | 1550.03 | 39.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1779.06 | 1156.81 | 752.80 | 2946.24 | 866.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.16 | 62.53 | 33.63 | 162.16 | 34.18 | 0.00 | 0.00 | 0.00 |
February | 84.89 | 48.28 | 36.61 | 151.34 | 26.60 | 0.00 | 0.00 | 0.00 |
March | 65.60 | 27.12 | 38.48 | 119.55 | 19.51 | 0.00 | 0.00 | 0.00 |
April | 47.04 | 9.64 | 37.40 | 99.01 | 8.46 | 0.00 | 0.00 | 0.00 |
May | 36.73 | 1.17 | 35.56 | 94.72 | 1.34 | 0.00 | 0.00 | 0.00 |
June | 34.64 | 0.07 | 34.57 | 101.02 | 0.10 | 0.00 | 0.00 | 0.00 |
July | 37.07 | 0.31 | 36.76 | 108.36 | 0.49 | 0.00 | 0.00 | 0.00 |
August | 41.67 | 3.12 | 38.56 | 116.94 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 54.04 | 13.35 | 40.69 | 140.93 | 0.76 | 0.00 | 0.00 | 0.00 |
October | 75.00 | 35.66 | 39.34 | 164.11 | 2.05 | 0.00 | 0.00 | 0.00 |
November | 84.96 | 47.68 | 37.28 | 162.66 | 12.41 | 0.00 | 0.00 | 0.00 |
December | 92.71 | 58.54 | 34.17 | 159.67 | 27.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.44 | 25.52 | 36.92 | 131.61 | 11.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.64 | 0.07 | 33.63 | 94.72 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.16 | 62.53 | 40.69 | 164.11 | 34.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.72 | 35.77 | 46.95 | 130.19 | 68.59 | 0.00 | 0.00 | 0.00 |
February | 103.82 | 47.29 | 56.54 | 179.43 | 53.06 | 0.00 | 0.00 | 0.00 |
March | 128.61 | 58.79 | 69.82 | 222.01 | 38.31 | 0.00 | 0.00 | 0.00 |
April | 141.16 | 65.27 | 75.89 | 269.90 | 15.60 | 0.00 | 0.00 | 0.00 |
May | 129.10 | 49.84 | 79.26 | 285.52 | 2.49 | 0.00 | 0.00 | 0.00 |
June | 109.31 | 30.67 | 78.64 | 272.68 | 0.20 | 0.00 | 0.00 | 0.00 |
July | 121.97 | 37.69 | 84.28 | 301.90 | 0.93 | 0.00 | 0.00 | 0.00 |
August | 121.69 | 39.55 | 82.13 | 294.20 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 103.84 | 30.60 | 73.24 | 258.16 | 1.49 | 0.00 | 0.00 | 0.00 |
October | 103.49 | 40.42 | 63.07 | 230.02 | 3.91 | 0.00 | 0.00 | 0.00 |
November | 85.13 | 31.18 | 53.95 | 169.95 | 24.86 | 0.00 | 0.00 | 0.00 |
December | 85.35 | 38.15 | 47.21 | 142.68 | 54.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.73 | 42.09 | 67.64 | 229.99 | 21.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.72 | 30.60 | 46.95 | 130.19 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 141.16 | 65.27 | 84.28 | 301.90 | 68.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.42 | 0.00 | 20.42 | 27.03 | 38.52 | 0.00 | 0.00 | 0.00 |
February | 24.17 | 0.00 | 24.17 | 38.88 | 30.59 | 0.00 | 0.00 | 0.00 |
March | 28.84 | 0.00 | 28.84 | 45.53 | 23.29 | 0.00 | 0.00 | 0.00 |
April | 32.40 | 0.18 | 32.21 | 63.76 | 10.35 | 0.00 | 0.00 | 0.00 |
May | 36.79 | 1.51 | 35.28 | 93.33 | 1.44 | 0.00 | 0.00 | 0.00 |
June | 39.43 | 2.84 | 36.59 | 111.52 | 0.18 | 0.00 | 0.00 | 0.00 |
July | 39.94 | 1.99 | 37.95 | 114.34 | 0.68 | 0.00 | 0.00 | 0.00 |
August | 35.37 | 0.37 | 35.00 | 102.26 | 0.09 | 0.00 | 0.00 | 0.00 |
September | 31.32 | 0.01 | 31.32 | 93.00 | 1.05 | 0.00 | 0.00 | 0.00 |
October | 26.23 | 0.00 | 26.23 | 69.75 | 2.21 | 0.00 | 0.00 | 0.00 |
November | 22.81 | 0.00 | 22.81 | 49.20 | 14.03 | 0.00 | 0.00 | 0.00 |
December | 20.20 | 0.00 | 20.20 | 30.31 | 30.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.85 | 0.58 | 29.28 | 70.06 | 12.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.20 | 0.00 | 20.20 | 27.03 | 0.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 39.94 | 2.84 | 37.95 | 114.34 | 38.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.72 | 35.77 | 46.95 | 132.58 | 70.19 | 0.00 | 0.00 | 0.00 |
February | 103.82 | 47.29 | 56.54 | 180.22 | 56.39 | 0.00 | 0.00 | 0.00 |
March | 128.61 | 58.79 | 69.82 | 220.87 | 42.33 | 0.00 | 0.00 | 0.00 |
April | 141.16 | 65.27 | 75.89 | 267.43 | 19.31 | 0.00 | 0.00 | 0.00 |
May | 129.10 | 49.84 | 79.26 | 283.97 | 2.82 | 0.00 | 0.00 | 0.00 |
June | 109.31 | 30.67 | 78.64 | 271.61 | 0.32 | 0.00 | 0.00 | 0.00 |
July | 121.97 | 37.69 | 84.28 | 300.87 | 1.25 | 0.00 | 0.00 | 0.00 |
August | 121.69 | 39.55 | 82.13 | 294.21 | 0.13 | 0.00 | 0.00 | 0.00 |
September | 103.84 | 30.60 | 73.24 | 259.23 | 1.92 | 0.00 | 0.00 | 0.00 |
October | 103.49 | 40.42 | 63.07 | 232.04 | 4.06 | 0.00 | 0.00 | 0.00 |
November | 85.13 | 31.18 | 53.95 | 171.85 | 26.06 | 0.00 | 0.00 | 0.00 |
December | 85.35 | 38.15 | 47.21 | 144.72 | 55.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.73 | 42.09 | 67.64 | 230.24 | 23.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.72 | 30.60 | 46.95 | 132.58 | 0.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 141.16 | 65.27 | 84.28 | 300.87 | 70.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.91 | 50.01 | 26.90 | 113.88 | 53.21 | 0.00 | 0.00 | 0.00 |
February | 67.90 | 38.61 | 29.28 | 104.21 | 45.75 | 0.00 | 0.00 | 0.00 |
March | 52.47 | 21.69 | 30.78 | 78.97 | 38.81 | 0.00 | 0.00 | 0.00 |
April | 37.62 | 7.71 | 29.92 | 62.62 | 27.04 | 0.00 | 0.00 | 0.00 |
May | 29.38 | 0.93 | 28.44 | 52.86 | 14.68 | 0.00 | 0.00 | 0.00 |
June | 27.71 | 0.06 | 27.65 | 52.65 | 7.69 | 0.00 | 0.00 | 0.00 |
July | 29.65 | 0.25 | 29.40 | 61.71 | 9.97 | 0.00 | 0.00 | 0.00 |
August | 33.33 | 2.49 | 30.84 | 65.61 | 8.50 | 0.00 | 0.00 | 0.00 |
September | 43.22 | 10.68 | 32.54 | 87.15 | 11.16 | 0.00 | 0.00 | 0.00 |
October | 59.99 | 28.52 | 31.46 | 109.86 | 17.76 | 0.00 | 0.00 | 0.00 |
November | 67.96 | 38.14 | 29.82 | 110.74 | 29.95 | 0.00 | 0.00 | 0.00 |
December | 74.15 | 46.82 | 27.33 | 112.65 | 48.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.94 | 20.41 | 29.53 | 84.31 | 25.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.71 | 0.06 | 26.90 | 52.65 | 7.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 76.91 | 50.01 | 32.54 | 113.88 | 53.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.34 | 0.00 | 16.34 | 22.97 | 29.89 | 0.00 | 0.00 | 0.00 |
February | 19.34 | 0.00 | 19.34 | 33.21 | 23.20 | 0.00 | 0.00 | 0.00 |
March | 23.07 | 0.00 | 23.07 | 39.53 | 16.59 | 0.00 | 0.00 | 0.00 |
April | 25.92 | 0.15 | 25.77 | 55.34 | 6.36 | 0.00 | 0.00 | 0.00 |
May | 29.43 | 1.21 | 28.23 | 80.53 | 0.84 | 0.00 | 0.00 | 0.00 |
June | 31.55 | 2.27 | 29.28 | 95.21 | 0.04 | 0.00 | 0.00 | 0.00 |
July | 31.96 | 1.59 | 30.37 | 97.79 | 0.31 | 0.00 | 0.00 | 0.00 |
August | 28.30 | 0.30 | 28.00 | 88.29 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 25.06 | 0.01 | 25.06 | 80.22 | 0.43 | 0.00 | 0.00 | 0.00 |
October | 20.98 | 0.00 | 20.98 | 61.16 | 1.12 | 0.00 | 0.00 | 0.00 |
November | 18.25 | 0.00 | 18.25 | 42.81 | 10.38 | 0.00 | 0.00 | 0.00 |
December | 16.16 | 0.00 | 16.16 | 25.97 | 23.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.89 | 0.46 | 23.42 | 60.38 | 9.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.16 | 0.00 | 16.16 | 22.97 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 31.96 | 2.27 | 30.37 | 97.79 | 29.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.82 | 44.00 | 47.82 | 143.04 | 65.05 | 0.00 | 0.00 | 0.00 |
February | 106.50 | 49.48 | 57.02 | 179.57 | 48.71 | 0.00 | 0.00 | 0.00 |
March | 129.73 | 61.33 | 68.39 | 218.03 | 33.86 | 0.00 | 0.00 | 0.00 |
April | 140.96 | 62.93 | 78.03 | 269.73 | 14.52 | 0.00 | 0.00 | 0.00 |
May | 133.36 | 53.32 | 80.05 | 294.05 | 2.27 | 0.00 | 0.00 | 0.00 |
June | 131.07 | 50.30 | 80.77 | 312.69 | 0.21 | 0.00 | 0.00 | 0.00 |
July | 134.86 | 48.66 | 86.19 | 326.46 | 0.87 | 0.00 | 0.00 | 0.00 |
August | 123.26 | 41.27 | 81.99 | 298.51 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 118.75 | 42.88 | 75.87 | 286.41 | 1.42 | 0.00 | 0.00 | 0.00 |
October | 109.18 | 46.86 | 62.32 | 241.56 | 3.70 | 0.00 | 0.00 | 0.00 |
November | 88.90 | 35.40 | 53.50 | 174.85 | 22.84 | 0.00 | 0.00 | 0.00 |
December | 71.90 | 25.48 | 46.43 | 117.23 | 52.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.04 | 46.79 | 68.25 | 238.75 | 20.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.90 | 25.48 | 46.43 | 117.23 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.96 | 62.93 | 86.19 | 326.46 | 65.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.16 | 62.53 | 33.63 | 161.32 | 34.01 | 0.00 | 0.00 | 0.00 |
February | 84.89 | 48.28 | 36.61 | 150.62 | 26.28 | 0.00 | 0.00 | 0.00 |
March | 65.60 | 27.12 | 38.48 | 118.75 | 19.08 | 0.00 | 0.00 | 0.00 |
April | 47.04 | 9.64 | 37.40 | 98.46 | 8.07 | 0.00 | 0.00 | 0.00 |
May | 36.73 | 1.17 | 35.56 | 94.49 | 1.29 | 0.00 | 0.00 | 0.00 |
June | 34.64 | 0.07 | 34.57 | 100.19 | 0.12 | 0.00 | 0.00 | 0.00 |
July | 37.07 | 0.31 | 36.76 | 107.84 | 0.49 | 0.00 | 0.00 | 0.00 |
August | 41.67 | 3.12 | 38.56 | 116.82 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 54.04 | 13.35 | 40.69 | 140.35 | 0.78 | 0.00 | 0.00 | 0.00 |
October | 75.00 | 35.66 | 39.34 | 163.79 | 1.98 | 0.00 | 0.00 | 0.00 |
November | 84.96 | 47.68 | 37.28 | 162.26 | 12.26 | 0.00 | 0.00 | 0.00 |
December | 92.71 | 58.54 | 34.17 | 159.65 | 27.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.44 | 25.52 | 36.92 | 131.12 | 10.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.64 | 0.07 | 33.63 | 94.49 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.16 | 62.53 | 40.69 | 163.79 | 34.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.42 | 0.00 | 20.42 | 25.83 | 38.27 | 0.00 | 0.00 | 0.00 |
February | 24.17 | 0.00 | 24.17 | 37.76 | 30.19 | 0.00 | 0.00 | 0.00 |
March | 28.84 | 0.00 | 28.84 | 44.54 | 22.60 | 0.00 | 0.00 | 0.00 |
April | 32.40 | 0.18 | 32.21 | 62.76 | 9.78 | 0.00 | 0.00 | 0.00 |
May | 36.79 | 1.51 | 35.28 | 92.95 | 1.39 | 0.00 | 0.00 | 0.00 |
June | 39.43 | 2.84 | 36.59 | 110.64 | 0.19 | 0.00 | 0.00 | 0.00 |
July | 39.94 | 1.99 | 37.95 | 113.80 | 0.69 | 0.00 | 0.00 | 0.00 |
August | 35.37 | 0.37 | 35.00 | 102.14 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 31.32 | 0.01 | 31.32 | 92.32 | 1.08 | 0.00 | 0.00 | 0.00 |
October | 26.23 | 0.00 | 26.23 | 69.22 | 2.15 | 0.00 | 0.00 | 0.00 |
November | 22.81 | 0.00 | 22.81 | 48.38 | 13.88 | 0.00 | 0.00 | 0.00 |
December | 20.20 | 0.00 | 20.20 | 30.05 | 29.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.85 | 0.58 | 29.28 | 69.36 | 12.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.20 | 0.00 | 20.20 | 25.83 | 0.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 39.94 | 2.84 | 37.95 | 113.80 | 38.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.82 | 44.00 | 47.82 | 144.63 | 66.36 | 0.00 | 0.00 | 0.00 |
February | 106.50 | 49.48 | 57.02 | 179.24 | 51.67 | 0.00 | 0.00 | 0.00 |
March | 129.73 | 61.33 | 68.39 | 216.30 | 37.25 | 0.00 | 0.00 | 0.00 |
April | 140.96 | 62.93 | 78.03 | 266.08 | 17.93 | 0.00 | 0.00 | 0.00 |
May | 133.36 | 53.32 | 80.05 | 292.06 | 2.54 | 0.00 | 0.00 | 0.00 |
June | 131.07 | 50.30 | 80.77 | 311.52 | 0.33 | 0.00 | 0.00 | 0.00 |
July | 134.86 | 48.66 | 86.19 | 325.40 | 1.25 | 0.00 | 0.00 | 0.00 |
August | 123.26 | 41.27 | 81.99 | 298.55 | 0.14 | 0.00 | 0.00 | 0.00 |
September | 118.75 | 42.88 | 75.87 | 287.24 | 1.84 | 0.00 | 0.00 | 0.00 |
October | 109.18 | 46.86 | 62.32 | 243.03 | 3.78 | 0.00 | 0.00 | 0.00 |
November | 88.90 | 35.40 | 53.50 | 175.61 | 23.84 | 0.00 | 0.00 | 0.00 |
December | 71.90 | 25.48 | 46.43 | 118.95 | 53.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 115.04 | 46.79 | 68.25 | 238.46 | 21.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.90 | 25.48 | 46.43 | 118.95 | 0.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.96 | 62.93 | 86.19 | 325.40 | 66.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.86 | 0.00 | 25.86 | 32.69 | 56.02 | 0.00 | 0.00 | 0.00 |
February | 30.61 | 0.00 | 30.61 | 48.87 | 43.82 | 0.00 | 0.00 | 0.00 |
March | 36.52 | 0.00 | 36.52 | 58.27 | 33.85 | 0.00 | 0.00 | 0.00 |
April | 41.03 | 0.23 | 40.79 | 80.65 | 17.52 | 0.00 | 0.00 | 0.00 |
May | 46.59 | 1.91 | 44.68 | 111.77 | 4.29 | 0.00 | 0.00 | 0.00 |
June | 49.94 | 3.59 | 46.35 | 130.33 | 1.29 | 0.00 | 0.00 | 0.00 |
July | 50.58 | 2.52 | 48.07 | 134.84 | 2.73 | 0.00 | 0.00 | 0.00 |
August | 44.80 | 0.47 | 44.33 | 118.04 | 1.18 | 0.00 | 0.00 | 0.00 |
September | 39.67 | 0.01 | 39.66 | 107.99 | 4.82 | 0.00 | 0.00 | 0.00 |
October | 33.22 | 0.00 | 33.22 | 79.57 | 7.89 | 0.00 | 0.00 | 0.00 |
November | 28.88 | 0.00 | 28.88 | 56.87 | 23.85 | 0.00 | 0.00 | 0.00 |
December | 25.58 | 0.00 | 25.58 | 36.78 | 45.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.81 | 0.73 | 37.08 | 83.22 | 20.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.58 | 0.00 | 25.58 | 32.69 | 1.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.58 | 3.59 | 48.07 | 134.84 | 56.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.53 | 0.00 | 9.53 | 12.05 | 20.65 | 0.00 | 0.00 | 0.00 |
February | 11.29 | 0.00 | 11.29 | 18.02 | 16.16 | 0.00 | 0.00 | 0.00 |
March | 13.46 | 0.00 | 13.46 | 21.48 | 12.48 | 0.00 | 0.00 | 0.00 |
April | 15.12 | 0.09 | 15.04 | 29.73 | 6.46 | 0.00 | 0.00 | 0.00 |
May | 17.17 | 0.70 | 16.47 | 41.20 | 1.58 | 0.00 | 0.00 | 0.00 |
June | 18.41 | 1.32 | 17.08 | 48.04 | 0.47 | 0.00 | 0.00 | 0.00 |
July | 18.65 | 0.93 | 17.72 | 49.71 | 1.01 | 0.00 | 0.00 | 0.00 |
August | 16.51 | 0.17 | 16.34 | 43.51 | 0.44 | 0.00 | 0.00 | 0.00 |
September | 14.62 | 0.00 | 14.62 | 39.81 | 1.78 | 0.00 | 0.00 | 0.00 |
October | 12.24 | 0.00 | 12.24 | 29.33 | 2.91 | 0.00 | 0.00 | 0.00 |
November | 10.65 | 0.00 | 10.65 | 20.97 | 8.79 | 0.00 | 0.00 | 0.00 |
December | 9.43 | 0.00 | 9.43 | 13.56 | 16.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 13.94 | 0.27 | 13.67 | 30.68 | 7.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.43 | 0.00 | 9.43 | 12.05 | 0.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 18.65 | 1.32 | 17.72 | 49.71 | 20.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.87 | 29.17 | 15.69 | 75.45 | 18.81 | 0.00 | 0.00 | 0.00 |
February | 39.61 | 22.53 | 17.08 | 70.41 | 14.98 | 0.00 | 0.00 | 0.00 |
March | 30.61 | 12.66 | 17.95 | 55.60 | 11.71 | 0.00 | 0.00 | 0.00 |
April | 21.95 | 4.50 | 17.45 | 45.54 | 6.57 | 0.00 | 0.00 | 0.00 |
May | 17.14 | 0.54 | 16.59 | 41.42 | 1.61 | 0.00 | 0.00 | 0.00 |
June | 16.16 | 0.03 | 16.13 | 42.89 | 0.48 | 0.00 | 0.00 | 0.00 |
July | 17.30 | 0.15 | 17.15 | 46.65 | 1.01 | 0.00 | 0.00 | 0.00 |
August | 19.44 | 1.45 | 17.99 | 50.30 | 0.43 | 0.00 | 0.00 | 0.00 |
September | 25.21 | 6.23 | 18.99 | 62.30 | 1.75 | 0.00 | 0.00 | 0.00 |
October | 34.99 | 16.64 | 18.35 | 73.63 | 2.84 | 0.00 | 0.00 | 0.00 |
November | 39.64 | 22.25 | 17.39 | 74.09 | 8.17 | 0.00 | 0.00 | 0.00 |
December | 43.26 | 27.31 | 15.94 | 74.26 | 15.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.13 | 11.91 | 17.23 | 59.32 | 6.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.16 | 0.03 | 15.69 | 41.42 | 0.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 44.87 | 29.17 | 18.99 | 75.45 | 18.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.78 | 79.18 | 42.59 | 204.78 | 51.06 | 0.00 | 0.00 | 0.00 |
February | 107.50 | 61.14 | 46.36 | 191.11 | 40.65 | 0.00 | 0.00 | 0.00 |
March | 83.08 | 34.35 | 48.73 | 150.91 | 31.77 | 0.00 | 0.00 | 0.00 |
April | 59.57 | 12.20 | 47.37 | 123.59 | 17.83 | 0.00 | 0.00 | 0.00 |
May | 46.51 | 1.48 | 45.04 | 112.42 | 4.38 | 0.00 | 0.00 | 0.00 |
June | 43.87 | 0.09 | 43.78 | 116.41 | 1.30 | 0.00 | 0.00 | 0.00 |
July | 46.95 | 0.39 | 46.55 | 126.62 | 2.74 | 0.00 | 0.00 | 0.00 |
August | 52.78 | 3.95 | 48.83 | 136.52 | 1.16 | 0.00 | 0.00 | 0.00 |
September | 68.44 | 16.91 | 51.53 | 169.10 | 4.75 | 0.00 | 0.00 | 0.00 |
October | 94.98 | 45.16 | 49.82 | 199.86 | 7.71 | 0.00 | 0.00 | 0.00 |
November | 107.60 | 60.39 | 47.21 | 201.10 | 22.17 | 0.00 | 0.00 | 0.00 |
December | 117.41 | 74.13 | 43.28 | 201.56 | 43.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.08 | 32.32 | 46.75 | 161.01 | 18.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.87 | 0.09 | 42.59 | 112.42 | 1.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.78 | 79.18 | 51.53 | 204.78 | 51.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.16 | 62.53 | 33.63 | 160.90 | 33.28 | 0.00 | 0.00 | 0.00 |
February | 84.89 | 48.28 | 36.61 | 149.89 | 25.87 | 0.00 | 0.00 | 0.00 |
March | 65.60 | 27.12 | 38.48 | 118.19 | 18.80 | 0.00 | 0.00 | 0.00 |
April | 47.04 | 9.64 | 37.40 | 97.95 | 7.93 | 0.00 | 0.00 | 0.00 |
May | 36.73 | 1.17 | 35.56 | 94.54 | 1.19 | 0.00 | 0.00 | 0.00 |
June | 34.64 | 0.07 | 34.57 | 100.97 | 0.07 | 0.00 | 0.00 | 0.00 |
July | 37.07 | 0.31 | 36.76 | 108.11 | 0.41 | 0.00 | 0.00 | 0.00 |
August | 41.67 | 3.12 | 38.56 | 116.78 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 54.04 | 13.35 | 40.69 | 140.33 | 0.58 | 0.00 | 0.00 | 0.00 |
October | 75.00 | 35.66 | 39.34 | 163.38 | 1.76 | 0.00 | 0.00 | 0.00 |
November | 84.96 | 47.68 | 37.28 | 161.63 | 11.78 | 0.00 | 0.00 | 0.00 |
December | 92.71 | 58.54 | 34.17 | 158.31 | 27.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.44 | 25.52 | 36.92 | 130.82 | 10.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.64 | 0.07 | 33.63 | 94.54 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.16 | 62.53 | 40.69 | 163.38 | 33.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.72 | 35.77 | 46.95 | 128.99 | 66.69 | 0.00 | 0.00 | 0.00 |
February | 103.82 | 47.29 | 56.54 | 177.78 | 51.60 | 0.00 | 0.00 | 0.00 |
March | 128.61 | 58.79 | 69.82 | 219.64 | 37.02 | 0.00 | 0.00 | 0.00 |
April | 141.16 | 65.27 | 75.89 | 267.36 | 14.63 | 0.00 | 0.00 | 0.00 |
May | 129.10 | 49.84 | 79.26 | 283.84 | 2.21 | 0.00 | 0.00 | 0.00 |
June | 109.31 | 30.67 | 78.64 | 271.51 | 0.14 | 0.00 | 0.00 | 0.00 |
July | 121.97 | 37.69 | 84.28 | 300.46 | 0.76 | 0.00 | 0.00 | 0.00 |
August | 121.69 | 39.55 | 82.13 | 293.01 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 103.84 | 30.60 | 73.24 | 257.11 | 1.12 | 0.00 | 0.00 | 0.00 |
October | 103.49 | 40.42 | 63.07 | 229.44 | 3.30 | 0.00 | 0.00 | 0.00 |
November | 85.13 | 31.18 | 53.95 | 169.13 | 23.56 | 0.00 | 0.00 | 0.00 |
December | 85.35 | 38.15 | 47.21 | 141.37 | 52.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.73 | 42.09 | 67.64 | 228.58 | 21.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.72 | 30.60 | 46.95 | 128.99 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 141.16 | 65.27 | 84.28 | 300.46 | 66.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.42 | 0.00 | 20.42 | 27.18 | 37.28 | 0.00 | 0.00 | 0.00 |
February | 24.17 | 0.00 | 24.17 | 38.79 | 29.82 | 0.00 | 0.00 | 0.00 |
March | 28.84 | 0.00 | 28.84 | 45.07 | 22.77 | 0.00 | 0.00 | 0.00 |
April | 32.40 | 0.18 | 32.21 | 63.13 | 9.98 | 0.00 | 0.00 | 0.00 |
May | 36.79 | 1.51 | 35.28 | 92.97 | 1.31 | 0.00 | 0.00 | 0.00 |
June | 39.43 | 2.84 | 36.59 | 111.20 | 0.15 | 0.00 | 0.00 | 0.00 |
July | 39.94 | 1.99 | 37.95 | 113.97 | 0.62 | 0.00 | 0.00 | 0.00 |
August | 35.37 | 0.37 | 35.00 | 102.19 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 31.32 | 0.01 | 31.32 | 93.02 | 0.86 | 0.00 | 0.00 | 0.00 |
October | 26.23 | 0.00 | 26.23 | 70.14 | 1.83 | 0.00 | 0.00 | 0.00 |
November | 22.81 | 0.00 | 22.81 | 49.50 | 13.22 | 0.00 | 0.00 | 0.00 |
December | 20.20 | 0.00 | 20.20 | 30.43 | 29.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.85 | 0.58 | 29.28 | 69.95 | 12.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.20 | 0.00 | 20.20 | 27.18 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 39.94 | 2.84 | 37.95 | 113.97 | 37.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.72 | 35.77 | 46.95 | 132.02 | 67.86 | 0.00 | 0.00 | 0.00 |
February | 103.82 | 47.29 | 56.54 | 178.90 | 54.98 | 0.00 | 0.00 | 0.00 |
March | 128.61 | 58.79 | 69.82 | 218.51 | 41.37 | 0.00 | 0.00 | 0.00 |
April | 141.16 | 65.27 | 75.89 | 264.81 | 18.61 | 0.00 | 0.00 | 0.00 |
May | 129.10 | 49.84 | 79.26 | 282.22 | 2.54 | 0.00 | 0.00 | 0.00 |
June | 109.31 | 30.67 | 78.64 | 270.38 | 0.26 | 0.00 | 0.00 | 0.00 |
July | 121.97 | 37.69 | 84.28 | 299.38 | 1.14 | 0.00 | 0.00 | 0.00 |
August | 121.69 | 39.55 | 82.13 | 293.02 | 0.10 | 0.00 | 0.00 | 0.00 |
September | 103.84 | 30.60 | 73.24 | 258.26 | 1.56 | 0.00 | 0.00 | 0.00 |
October | 103.49 | 40.42 | 63.07 | 231.67 | 3.36 | 0.00 | 0.00 | 0.00 |
November | 85.13 | 31.18 | 53.95 | 171.46 | 24.56 | 0.00 | 0.00 | 0.00 |
December | 85.35 | 38.15 | 47.21 | 144.04 | 53.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.73 | 42.09 | 67.64 | 229.00 | 22.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.72 | 30.60 | 46.95 | 132.02 | 0.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 141.16 | 65.27 | 84.28 | 299.38 | 67.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.03 | 91.70 | 49.33 | 233.03 | 50.60 | 0.00 | 0.00 | 0.00 |
February | 124.49 | 70.80 | 53.69 | 218.50 | 38.51 | 0.00 | 0.00 | 0.00 |
March | 96.21 | 39.78 | 56.43 | 174.11 | 26.83 | 0.00 | 0.00 | 0.00 |
April | 68.99 | 14.13 | 54.85 | 147.38 | 10.07 | 0.00 | 0.00 | 0.00 |
May | 53.86 | 1.71 | 52.15 | 144.77 | 1.49 | 0.00 | 0.00 | 0.00 |
June | 50.81 | 0.11 | 50.70 | 153.99 | 0.07 | 0.00 | 0.00 | 0.00 |
July | 54.36 | 0.46 | 53.91 | 164.96 | 0.43 | 0.00 | 0.00 | 0.00 |
August | 61.12 | 4.57 | 56.55 | 176.97 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 79.25 | 19.58 | 59.67 | 209.35 | 0.63 | 0.00 | 0.00 | 0.00 |
October | 109.99 | 52.30 | 57.69 | 241.05 | 2.39 | 0.00 | 0.00 | 0.00 |
November | 124.61 | 69.93 | 54.67 | 236.20 | 17.61 | 0.00 | 0.00 | 0.00 |
December | 135.96 | 85.85 | 50.12 | 230.02 | 41.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.57 | 37.43 | 54.14 | 194.08 | 15.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.81 | 0.11 | 49.33 | 144.77 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 141.03 | 91.70 | 59.67 | 241.05 | 50.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.95 | 0.00 | 142.95 | 153.48 | 371.70 | 0.00 | 0.00 | 0.00 |
February | 169.20 | 0.00 | 169.20 | 231.40 | 305.65 | 0.00 | 0.00 | 0.00 |
March | 201.84 | 0.00 | 201.84 | 278.28 | 243.63 | 0.00 | 0.00 | 0.00 |
April | 226.76 | 1.29 | 225.47 | 398.36 | 135.84 | 0.00 | 0.00 | 0.00 |
May | 257.51 | 10.55 | 246.96 | 558.62 | 47.73 | 0.00 | 0.00 | 0.00 |
June | 276.00 | 19.85 | 256.15 | 661.23 | 15.98 | 0.00 | 0.00 | 0.00 |
July | 279.58 | 13.92 | 265.67 | 697.78 | 25.57 | 0.00 | 0.00 | 0.00 |
August | 247.60 | 2.60 | 245.00 | 597.78 | 16.20 | 0.00 | 0.00 | 0.00 |
September | 219.25 | 0.05 | 219.20 | 554.57 | 38.87 | 0.00 | 0.00 | 0.00 |
October | 183.59 | 0.00 | 183.59 | 405.30 | 63.10 | 0.00 | 0.00 | 0.00 |
November | 159.63 | 0.00 | 159.63 | 276.68 | 165.18 | 0.00 | 0.00 | 0.00 |
December | 141.39 | 0.00 | 141.39 | 173.71 | 313.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 208.97 | 4.04 | 204.93 | 416.49 | 144.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.39 | 0.00 | 141.39 | 153.48 | 15.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 279.58 | 19.85 | 265.67 | 697.78 | 371.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.95 | 0.00 | 142.95 | 144.22 | 389.40 | 0.00 | 0.00 | 0.00 |
February | 169.20 | 0.00 | 169.20 | 220.12 | 321.07 | 0.00 | 0.00 | 0.00 |
March | 201.84 | 0.00 | 201.84 | 266.43 | 257.01 | 0.00 | 0.00 | 0.00 |
April | 226.76 | 1.29 | 225.47 | 386.86 | 144.82 | 0.00 | 0.00 | 0.00 |
May | 257.51 | 10.55 | 246.96 | 546.72 | 53.66 | 0.00 | 0.00 | 0.00 |
June | 276.00 | 19.85 | 256.15 | 647.95 | 18.44 | 0.00 | 0.00 | 0.00 |
July | 279.58 | 13.92 | 265.67 | 686.26 | 28.78 | 0.00 | 0.00 | 0.00 |
August | 247.60 | 2.60 | 245.00 | 584.15 | 18.88 | 0.00 | 0.00 | 0.00 |
September | 219.25 | 0.05 | 219.20 | 542.29 | 42.36 | 0.00 | 0.00 | 0.00 |
October | 183.59 | 0.00 | 183.59 | 394.12 | 69.36 | 0.00 | 0.00 | 0.00 |
November | 159.63 | 0.00 | 159.63 | 265.81 | 175.58 | 0.00 | 0.00 | 0.00 |
December | 141.39 | 0.00 | 141.39 | 164.53 | 330.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 208.97 | 4.04 | 204.93 | 405.01 | 153.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.39 | 0.00 | 141.39 | 144.22 | 18.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 279.58 | 19.85 | 265.67 | 686.26 | 389.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.42 | 0.00 | 20.42 | 27.37 | 51.52 | 0.00 | 0.00 | 0.00 |
February | 24.17 | 0.00 | 24.17 | 38.68 | 44.13 | 0.00 | 0.00 | 0.00 |
March | 28.84 | 0.00 | 28.84 | 46.51 | 36.05 | 0.00 | 0.00 | 0.00 |
April | 32.40 | 0.18 | 32.21 | 66.97 | 21.06 | 0.00 | 0.00 | 0.00 |
May | 36.79 | 1.51 | 35.28 | 92.93 | 9.52 | 0.00 | 0.00 | 0.00 |
June | 39.43 | 2.84 | 36.59 | 108.50 | 3.92 | 0.00 | 0.00 | 0.00 |
July | 39.94 | 1.99 | 37.95 | 116.12 | 5.72 | 0.00 | 0.00 | 0.00 |
August | 35.37 | 0.37 | 35.00 | 98.06 | 4.01 | 0.00 | 0.00 | 0.00 |
September | 31.32 | 0.01 | 31.32 | 92.35 | 6.32 | 0.00 | 0.00 | 0.00 |
October | 26.23 | 0.00 | 26.23 | 69.35 | 10.59 | 0.00 | 0.00 | 0.00 |
November | 22.81 | 0.00 | 22.81 | 48.87 | 24.43 | 0.00 | 0.00 | 0.00 |
December | 20.20 | 0.00 | 20.20 | 31.10 | 43.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.85 | 0.58 | 29.28 | 69.89 | 21.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.20 | 0.00 | 20.20 | 27.37 | 3.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 39.94 | 2.84 | 37.95 | 116.12 | 51.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.62 | 87.99 | 95.62 | 294.81 | 180.96 | 0.00 | 0.00 | 0.00 |
February | 212.98 | 98.94 | 114.04 | 359.66 | 154.61 | 0.00 | 0.00 | 0.00 |
March | 259.43 | 122.66 | 136.78 | 437.20 | 124.75 | 0.00 | 0.00 | 0.00 |
April | 281.90 | 125.85 | 156.05 | 545.12 | 79.43 | 0.00 | 0.00 | 0.00 |
May | 266.71 | 106.63 | 160.08 | 576.30 | 36.26 | 0.00 | 0.00 | 0.00 |
June | 262.13 | 100.60 | 161.52 | 610.16 | 14.87 | 0.00 | 0.00 | 0.00 |
July | 269.70 | 97.32 | 172.37 | 655.60 | 21.59 | 0.00 | 0.00 | 0.00 |
August | 246.51 | 82.53 | 163.98 | 576.29 | 15.22 | 0.00 | 0.00 | 0.00 |
September | 237.49 | 85.76 | 151.73 | 571.46 | 23.81 | 0.00 | 0.00 | 0.00 |
October | 218.34 | 93.71 | 124.64 | 484.16 | 39.77 | 0.00 | 0.00 | 0.00 |
November | 177.79 | 70.80 | 106.99 | 351.69 | 86.47 | 0.00 | 0.00 | 0.00 |
December | 143.79 | 50.95 | 92.85 | 240.32 | 155.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 230.07 | 93.58 | 136.49 | 475.69 | 77.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 143.79 | 50.95 | 92.85 | 240.32 | 14.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 281.90 | 125.85 | 172.37 | 655.60 | 180.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.16 | 62.53 | 33.63 | 164.47 | 47.59 | 0.00 | 0.00 | 0.00 |
February | 84.89 | 48.28 | 36.61 | 152.06 | 41.00 | 0.00 | 0.00 | 0.00 |
March | 65.60 | 27.12 | 38.48 | 120.07 | 34.12 | 0.00 | 0.00 | 0.00 |
April | 47.04 | 9.64 | 37.40 | 101.09 | 21.10 | 0.00 | 0.00 | 0.00 |
May | 36.73 | 1.17 | 35.56 | 92.08 | 9.64 | 0.00 | 0.00 | 0.00 |
June | 34.64 | 0.07 | 34.57 | 97.19 | 3.91 | 0.00 | 0.00 | 0.00 |
July | 37.07 | 0.31 | 36.76 | 109.16 | 5.75 | 0.00 | 0.00 | 0.00 |
August | 41.67 | 3.12 | 38.56 | 112.02 | 4.03 | 0.00 | 0.00 | 0.00 |
September | 54.04 | 13.35 | 40.69 | 140.91 | 6.31 | 0.00 | 0.00 | 0.00 |
October | 75.00 | 35.66 | 39.34 | 164.86 | 10.48 | 0.00 | 0.00 | 0.00 |
November | 84.96 | 47.68 | 37.28 | 163.96 | 22.99 | 0.00 | 0.00 | 0.00 |
December | 92.71 | 58.54 | 34.17 | 162.26 | 40.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.44 | 25.52 | 36.92 | 131.57 | 20.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.64 | 0.07 | 33.63 | 92.08 | 3.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.16 | 62.53 | 40.69 | 164.86 | 47.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.86 | 0.00 | 25.86 | 31.17 | 54.99 | 0.00 | 0.00 | 0.00 |
February | 30.61 | 0.00 | 30.61 | 46.42 | 43.94 | 0.00 | 0.00 | 0.00 |
March | 36.52 | 0.00 | 36.52 | 55.33 | 34.11 | 0.00 | 0.00 | 0.00 |
April | 41.03 | 0.23 | 40.79 | 76.19 | 18.97 | 0.00 | 0.00 | 0.00 |
May | 46.59 | 1.91 | 44.68 | 104.63 | 5.75 | 0.00 | 0.00 | 0.00 |
June | 49.94 | 3.59 | 46.35 | 122.03 | 1.99 | 0.00 | 0.00 | 0.00 |
July | 50.58 | 2.52 | 48.07 | 127.61 | 3.68 | 0.00 | 0.00 | 0.00 |
August | 44.80 | 0.47 | 44.33 | 110.83 | 1.86 | 0.00 | 0.00 | 0.00 |
September | 39.67 | 0.01 | 39.66 | 101.66 | 5.75 | 0.00 | 0.00 | 0.00 |
October | 33.22 | 0.00 | 33.22 | 74.85 | 8.85 | 0.00 | 0.00 | 0.00 |
November | 28.88 | 0.00 | 28.88 | 53.45 | 23.94 | 0.00 | 0.00 | 0.00 |
December | 25.58 | 0.00 | 25.58 | 34.77 | 45.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.81 | 0.73 | 37.08 | 78.40 | 20.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.58 | 0.00 | 25.58 | 31.17 | 1.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.58 | 3.59 | 48.07 | 127.61 | 54.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.14 | 0.00 | 23.14 | 27.88 | 49.20 | 0.00 | 0.00 | 0.00 |
February | 27.39 | 0.00 | 27.39 | 41.53 | 39.32 | 0.00 | 0.00 | 0.00 |
March | 32.67 | 0.00 | 32.67 | 49.50 | 30.52 | 0.00 | 0.00 | 0.00 |
April | 36.71 | 0.21 | 36.50 | 68.17 | 16.97 | 0.00 | 0.00 | 0.00 |
May | 41.68 | 1.71 | 39.98 | 93.61 | 5.14 | 0.00 | 0.00 | 0.00 |
June | 44.68 | 3.21 | 41.47 | 109.18 | 1.78 | 0.00 | 0.00 | 0.00 |
July | 45.26 | 2.25 | 43.01 | 114.18 | 3.29 | 0.00 | 0.00 | 0.00 |
August | 40.08 | 0.42 | 39.66 | 99.16 | 1.67 | 0.00 | 0.00 | 0.00 |
September | 35.49 | 0.01 | 35.48 | 90.96 | 5.14 | 0.00 | 0.00 | 0.00 |
October | 29.72 | 0.00 | 29.72 | 66.97 | 7.91 | 0.00 | 0.00 | 0.00 |
November | 25.84 | 0.00 | 25.84 | 47.82 | 21.42 | 0.00 | 0.00 | 0.00 |
December | 22.89 | 0.00 | 22.89 | 31.11 | 40.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.83 | 0.65 | 33.17 | 70.14 | 18.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.89 | 0.00 | 22.89 | 27.88 | 1.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.26 | 3.21 | 43.01 | 114.18 | 49.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 358.99 | 233.43 | 125.56 | 595.15 | 147.99 | 0.00 | 0.00 | 0.00 |
February | 316.91 | 180.24 | 136.67 | 551.80 | 120.65 | 0.00 | 0.00 | 0.00 |
March | 244.91 | 101.26 | 143.66 | 432.91 | 94.84 | 0.00 | 0.00 | 0.00 |
April | 175.61 | 35.97 | 139.64 | 349.43 | 57.18 | 0.00 | 0.00 | 0.00 |
May | 137.11 | 4.35 | 132.76 | 309.93 | 17.09 | 0.00 | 0.00 | 0.00 |
June | 129.33 | 0.27 | 129.06 | 319.25 | 6.13 | 0.00 | 0.00 | 0.00 |
July | 138.39 | 1.16 | 137.23 | 351.94 | 11.01 | 0.00 | 0.00 | 0.00 |
August | 155.58 | 11.63 | 143.94 | 380.47 | 5.54 | 0.00 | 0.00 | 0.00 |
September | 201.75 | 49.84 | 151.91 | 477.75 | 16.94 | 0.00 | 0.00 | 0.00 |
October | 279.99 | 133.13 | 146.86 | 571.83 | 25.92 | 0.00 | 0.00 | 0.00 |
November | 317.19 | 178.02 | 139.17 | 578.85 | 66.04 | 0.00 | 0.00 | 0.00 |
December | 346.10 | 218.53 | 127.57 | 583.85 | 126.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 233.10 | 95.28 | 137.82 | 458.13 | 57.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 129.33 | 0.27 | 125.56 | 309.93 | 5.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 358.99 | 233.43 | 151.91 | 595.15 | 147.99 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130262E+10 | 0.847008E+09 | 0.455609E+09 | 0.212736E+10 | 0.565407E+09 |
February | 0.103864E+10 | 0.590715E+09 | 0.447926E+09 | 0.178826E+10 | 0.425360E+09 |
March | 0.888686E+09 | 0.367421E+09 | 0.521265E+09 | 0.155992E+10 | 0.378496E+09 |
April | 0.616648E+09 | 0.126319E+09 | 0.490329E+09 | 0.121792E+10 | 0.224973E+09 |
May | 0.497514E+09 | 15792888.41 | 0.481721E+09 | 0.109420E+10 | 83206765.77 |
June | 0.454150E+09 | 945370.99 | 0.453204E+09 | 0.107974E+10 | 25607716.12 |
July | 0.502150E+09 | 4216541.70 | 0.497933E+09 | 0.122700E+10 | 50587131.50 |
August | 0.564515E+09 | 42215893.17 | 0.522299E+09 | 0.132313E+10 | 23590505.63 |
September | 0.708434E+09 | 0.175017E+09 | 0.533417E+09 | 0.162485E+10 | 70169590.95 |
October | 0.101597E+10 | 0.483084E+09 | 0.532887E+09 | 0.203446E+10 | 0.125992E+09 |
November | 0.111383E+10 | 0.625115E+09 | 0.488710E+09 | 0.199849E+10 | 0.262526E+09 |
December | 0.125587E+10 | 0.792971E+09 | 0.462900E+09 | 0.209832E+10 | 0.490467E+09 |
Annual Sum or Average | 0.995902E+10 | 0.407082E+10 | 0.588820E+10 | 0.191736E+11 | 0.272638E+10 |
Minimum of Months | 0.454150E+09 | 945370.99 | 0.447926E+09 | 0.107974E+10 | 23590505.63 |
Maximum of Months | 0.130262E+10 | 0.847008E+09 | 0.533417E+09 | 0.212736E+10 | 0.565407E+09 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.366808E+10 | 0.238512E+10 | 0.128296E+10 | 0.590132E+10 | 0.178157E+10 |
February | 0.292475E+10 | 0.166341E+10 | 0.126133E+10 | 0.496015E+10 | 0.134297E+10 |
March | 0.250248E+10 | 0.103463E+10 | 0.146785E+10 | 0.433317E+10 | 0.120224E+10 |
April | 0.173644E+10 | 0.355706E+09 | 0.138073E+10 | 0.340284E+10 | 0.711119E+09 |
May | 0.140097E+10 | 44471732.47 | 0.135649E+10 | 0.308384E+10 | 0.274356E+09 |
June | 0.127886E+10 | 2662102.37 | 0.127619E+10 | 0.306682E+10 | 90444362.75 |
July | 0.141402E+10 | 11873503.41 | 0.140215E+10 | 0.349033E+10 | 0.150754E+09 |
August | 0.158964E+10 | 0.118877E+09 | 0.147076E+10 | 0.373272E+10 | 86203588.86 |
September | 0.199490E+10 | 0.492837E+09 | 0.150207E+10 | 0.457250E+10 | 0.217329E+09 |
October | 0.286091E+10 | 0.136033E+10 | 0.150057E+10 | 0.569672E+10 | 0.391092E+09 |
November | 0.313646E+10 | 0.176028E+10 | 0.137618E+10 | 0.556660E+10 | 0.826466E+09 |
December | 0.353645E+10 | 0.223295E+10 | 0.130350E+10 | 0.583209E+10 | 0.155336E+10 |
Annual Sum or Average | 0.280439E+11 | 0.114632E+11 | 0.165808E+11 | 0.536391E+11 | 0.862790E+10 |
Minimum of Months | 0.127886E+10 | 2662102.37 | 0.126133E+10 | 0.306682E+10 | 86203588.86 |
Maximum of Months | 0.366808E+10 | 0.238512E+10 | 0.150207E+10 | 0.590132E+10 | 0.178157E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.476505E+10 | 0.309840E+10 | 0.166664E+10 | 0.789120E+10 | 0.232183E+10 |
February | 0.379941E+10 | 0.216087E+10 | 0.163854E+10 | 0.664841E+10 | 0.173777E+10 |
March | 0.325087E+10 | 0.134405E+10 | 0.190682E+10 | 0.582157E+10 | 0.155405E+10 |
April | 0.225574E+10 | 0.462083E+09 | 0.179365E+10 | 0.458418E+10 | 0.911091E+09 |
May | 0.181994E+10 | 57771311.39 | 0.176216E+10 | 0.415159E+10 | 0.345804E+09 |
June | 0.166131E+10 | 3458222.48 | 0.165785E+10 | 0.413476E+10 | 0.113816E+09 |
July | 0.183689E+10 | 15424356.66 | 0.182147E+10 | 0.472109E+10 | 0.188977E+09 |
August | 0.206503E+10 | 0.154428E+09 | 0.191060E+10 | 0.504677E+10 | 0.104747E+09 |
September | 0.259149E+10 | 0.640223E+09 | 0.195127E+10 | 0.618786E+10 | 0.270990E+09 |
October | 0.371648E+10 | 0.176715E+10 | 0.194933E+10 | 0.766166E+10 | 0.464567E+09 |
November | 0.407444E+10 | 0.228671E+10 | 0.178773E+10 | 0.746188E+10 | 0.104863E+10 |
December | 0.459405E+10 | 0.290074E+10 | 0.169332E+10 | 0.778513E+10 | 0.200957E+10 |
Annual Sum or Average | 0.364307E+11 | 0.148913E+11 | 0.215394E+11 | 0.720961E+11 | 0.110718E+11 |
Minimum of Months | 0.166131E+10 | 3458222.48 | 0.163854E+10 | 0.413476E+10 | 0.104747E+09 |
Maximum of Months | 0.476505E+10 | 0.309840E+10 | 0.195127E+10 | 0.789120E+10 | 0.232183E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257550E+09 | 0.167468E+09 | 90082335.07 | 0.434331E+09 | 91549462.69 |
February | 0.205358E+09 | 0.116795E+09 | 88563446.37 | 0.366115E+09 | 64349651.37 |
March | 0.175710E+09 | 72645397.10 | 0.103064E+09 | 0.320200E+09 | 52254857.45 |
April | 0.121923E+09 | 24975453.13 | 96947571.18 | 0.256634E+09 | 21935440.87 |
May | 98368166.03 | 3122525.28 | 95245640.75 | 0.253711E+09 | 3583536.00 |
June | 89794232.35 | 186916.08 | 89607316.27 | 0.261837E+09 | 268506.02 |
July | 99284742.67 | 833682.71 | 98451059.96 | 0.290227E+09 | 1316897.30 |
August | 0.111615E+09 | 8346807.13 | 0.103268E+09 | 0.313201E+09 | 110367.74 |
September | 0.140070E+09 | 34603902.39 | 0.105467E+09 | 0.365281E+09 | 1980656.97 |
October | 0.200876E+09 | 95513992.58 | 0.105362E+09 | 0.439544E+09 | 5496718.56 |
November | 0.220223E+09 | 0.123596E+09 | 96627063.75 | 0.421614E+09 | 32163523.01 |
December | 0.248308E+09 | 0.156784E+09 | 91523891.56 | 0.427669E+09 | 74479136.53 |
Annual Sum or Average | 0.196908E+10 | 0.804871E+09 | 0.116421E+10 | 0.415036E+10 | 0.349489E+09 |
Minimum of Months | 89794232.35 | 186916.08 | 88563446.37 | 0.253711E+09 | 110367.74 |
Maximum of Months | 0.257550E+09 | 0.167468E+09 | 0.105467E+09 | 0.439544E+09 | 91549462.69 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221564E+09 | 95806949.54 | 0.125757E+09 | 0.348710E+09 | 0.183716E+09 |
February | 0.251167E+09 | 0.114393E+09 | 0.136774E+09 | 0.434076E+09 | 0.128365E+09 |
March | 0.344456E+09 | 0.157460E+09 | 0.186996E+09 | 0.594642E+09 | 0.102616E+09 |
April | 0.365885E+09 | 0.169185E+09 | 0.196700E+09 | 0.699571E+09 | 40443578.85 |
May | 0.345789E+09 | 0.133502E+09 | 0.212287E+09 | 0.764747E+09 | 6673618.51 |
June | 0.283325E+09 | 79500419.30 | 0.203825E+09 | 0.706794E+09 | 517826.84 |
July | 0.326686E+09 | 0.100960E+09 | 0.225726E+09 | 0.808618E+09 | 2482156.23 |
August | 0.325925E+09 | 0.105939E+09 | 0.219986E+09 | 0.787974E+09 | 178282.80 |
September | 0.269154E+09 | 79319231.83 | 0.189834E+09 | 0.669153E+09 | 3864284.91 |
October | 0.277185E+09 | 0.108264E+09 | 0.168920E+09 | 0.616076E+09 | 10480860.32 |
November | 0.220665E+09 | 80823817.61 | 0.139841E+09 | 0.440501E+09 | 64445411.09 |
December | 0.228615E+09 | 0.102173E+09 | 0.126442E+09 | 0.382142E+09 | 0.145413E+09 |
Annual Sum or Average | 0.346042E+10 | 0.132733E+10 | 0.213309E+10 | 0.725300E+10 | 0.689197E+09 |
Minimum of Months | 0.220665E+09 | 79319231.83 | 0.125757E+09 | 0.348710E+09 | 178282.80 |
Maximum of Months | 0.365885E+09 | 0.169185E+09 | 0.225726E+09 | 0.808618E+09 | 0.183716E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54698183.53 | 0.00 | 54698183.53 | 72388660.77 | 0.103165E+09 |
February | 58478498.71 | 0.00 | 58478498.71 | 94064790.27 | 73999139.13 |
March | 77233473.39 | 1362.94 | 77232110.44 | 0.121960E+09 | 62387111.67 |
April | 83970605.55 | 479410.66 | 83491194.89 | 0.165278E+09 | 26824303.19 |
May | 98532712.50 | 4036540.06 | 94496172.44 | 0.249981E+09 | 3854995.35 |
June | 0.102205E+09 | 7350764.32 | 94853740.60 | 0.289060E+09 | 461764.55 |
July | 0.106981E+09 | 5324768.18 | 0.101656E+09 | 0.306245E+09 | 1815315.24 |
August | 94741363.18 | 993169.98 | 93748193.20 | 0.273900E+09 | 233554.00 |
September | 81187455.09 | 18756.62 | 81168698.47 | 0.241069E+09 | 2728947.08 |
October | 70248201.14 | 0.00 | 70248201.14 | 0.186827E+09 | 5907595.74 |
November | 59110813.52 | 0.00 | 59110813.52 | 0.127536E+09 | 36359669.63 |
December | 54103315.64 | 0.00 | 54103315.64 | 81172356.83 | 82127647.69 |
Annual Sum or Average | 0.941490E+09 | 18204772.77 | 0.923285E+09 | 0.220948E+10 | 0.399865E+09 |
Minimum of Months | 54103315.64 | 0.00 | 54103315.64 | 72388660.77 | 233554.00 |
Maximum of Months | 0.106981E+09 | 7350764.32 | 0.101656E+09 | 0.306245E+09 | 0.103165E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221564E+09 | 95806949.54 | 0.125757E+09 | 0.355097E+09 | 0.187987E+09 |
February | 0.251167E+09 | 0.114393E+09 | 0.136774E+09 | 0.435983E+09 | 0.136412E+09 |
March | 0.344456E+09 | 0.157460E+09 | 0.186996E+09 | 0.591590E+09 | 0.113390E+09 |
April | 0.365885E+09 | 0.169185E+09 | 0.196700E+09 | 0.693188E+09 | 50044975.09 |
May | 0.345789E+09 | 0.133502E+09 | 0.212287E+09 | 0.760575E+09 | 7555440.53 |
June | 0.283325E+09 | 79500419.30 | 0.203825E+09 | 0.704016E+09 | 826093.65 |
July | 0.326686E+09 | 0.100960E+09 | 0.225726E+09 | 0.805854E+09 | 3353041.36 |
August | 0.325925E+09 | 0.105939E+09 | 0.219986E+09 | 0.788011E+09 | 342641.06 |
September | 0.269154E+09 | 79319231.83 | 0.189834E+09 | 0.671925E+09 | 4976381.14 |
October | 0.277185E+09 | 0.108264E+09 | 0.168920E+09 | 0.621508E+09 | 10861416.18 |
November | 0.220665E+09 | 80823817.61 | 0.139841E+09 | 0.445445E+09 | 67544068.98 |
December | 0.228615E+09 | 0.102173E+09 | 0.126442E+09 | 0.387622E+09 | 0.149709E+09 |
Annual Sum or Average | 0.346042E+10 | 0.132733E+10 | 0.213309E+10 | 0.726081E+10 | 0.733001E+09 |
Minimum of Months | 0.220665E+09 | 79319231.83 | 0.125757E+09 | 0.355097E+09 | 342641.06 |
Maximum of Months | 0.365885E+09 | 0.169185E+09 | 0.225726E+09 | 0.805854E+09 | 0.187987E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.205999E+09 | 0.133948E+09 | 72051538.95 | 0.305023E+09 | 0.142506E+09 |
February | 0.164254E+09 | 93417022.33 | 70836669.59 | 0.252097E+09 | 0.110673E+09 |
March | 0.140540E+09 | 58104762.21 | 82434892.27 | 0.211517E+09 | 0.103962E+09 |
April | 97519025.54 | 19976389.74 | 77542635.80 | 0.162301E+09 | 70095355.80 |
May | 78678885.71 | 2497523.53 | 76181362.18 | 0.141570E+09 | 39318519.23 |
June | 71821102.60 | 149503.13 | 71671599.46 | 0.136464E+09 | 19932642.37 |
July | 79412001.23 | 666813.56 | 78745187.67 | 0.165274E+09 | 26705850.62 |
August | 89274487.04 | 6676118.00 | 82598369.03 | 0.175723E+09 | 22754557.10 |
September | 0.112034E+09 | 27677617.58 | 84356449.57 | 0.225887E+09 | 28930512.07 |
October | 0.160669E+09 | 76396000.95 | 84272641.20 | 0.294246E+09 | 47576495.75 |
November | 0.176143E+09 | 98857127.90 | 77286280.84 | 0.287030E+09 | 77635849.50 |
December | 0.198607E+09 | 0.125402E+09 | 73204554.83 | 0.301735E+09 | 0.128940E+09 |
Annual Sum or Average | 0.157495E+10 | 0.643769E+09 | 0.931182E+09 | 0.265887E+10 | 0.819030E+09 |
Minimum of Months | 71821102.60 | 149503.13 | 70836669.59 | 0.136464E+09 | 19932642.37 |
Maximum of Months | 0.205999E+09 | 0.133948E+09 | 84356449.57 | 0.305023E+09 | 0.142506E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 43764347.27 | 0.00 | 43764347.27 | 61527045.79 | 80065465.54 |
February | 46789000.29 | 0.00 | 46789000.29 | 80341692.94 | 56126762.96 |
March | 61794968.90 | 1090.50 | 61793878.40 | 0.105865E+09 | 44432859.33 |
April | 67185389.07 | 383579.37 | 66801809.70 | 0.143450E+09 | 16475092.07 |
May | 78836618.86 | 3229660.10 | 75606958.76 | 0.215681E+09 | 2241291.37 |
June | 81774442.16 | 5881390.96 | 75893051.20 | 0.246774E+09 | 114076.63 |
July | 85596033.41 | 4260379.21 | 81335654.20 | 0.261909E+09 | 841306.81 |
August | 75803137.35 | 794641.31 | 75008496.04 | 0.236483E+09 | 34797.67 |
September | 64958573.56 | 15007.28 | 64943566.27 | 0.207923E+09 | 1103306.15 |
October | 56206010.35 | 0.00 | 56206010.35 | 0.163806E+09 | 2991329.75 |
November | 47294919.20 | 0.00 | 47294919.20 | 0.110967E+09 | 26915217.24 |
December | 43288389.88 | 0.00 | 43288389.88 | 69566384.65 | 63160663.40 |
Annual Sum or Average | 0.753292E+09 | 14565748.73 | 0.738726E+09 | 0.190429E+10 | 0.294502E+09 |
Minimum of Months | 43288389.88 | 0.00 | 43288389.88 | 61527045.79 | 34797.67 |
Maximum of Months | 85596033.41 | 5881390.96 | 81335654.20 | 0.261909E+09 | 80065465.54 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.245920E+09 | 0.117851E+09 | 0.128069E+09 | 0.383131E+09 | 0.174232E+09 |
February | 0.257639E+09 | 0.119692E+09 | 0.137947E+09 | 0.434421E+09 | 0.117847E+09 |
March | 0.347459E+09 | 0.164276E+09 | 0.183183E+09 | 0.583983E+09 | 90700154.60 |
April | 0.365369E+09 | 0.163107E+09 | 0.202261E+09 | 0.699135E+09 | 37644836.94 |
May | 0.357204E+09 | 0.142810E+09 | 0.214394E+09 | 0.787595E+09 | 6085110.44 |
June | 0.339741E+09 | 0.130390E+09 | 0.209351E+09 | 0.810505E+09 | 556030.96 |
July | 0.361204E+09 | 0.130344E+09 | 0.230860E+09 | 0.874403E+09 | 2337407.84 |
August | 0.330152E+09 | 0.110538E+09 | 0.219614E+09 | 0.799535E+09 | 167656.56 |
September | 0.307809E+09 | 0.111147E+09 | 0.196662E+09 | 0.742378E+09 | 3679376.88 |
October | 0.292427E+09 | 0.125499E+09 | 0.166928E+09 | 0.646981E+09 | 9905316.49 |
November | 0.230434E+09 | 91766114.67 | 0.138668E+09 | 0.453219E+09 | 59194100.69 |
December | 0.192583E+09 | 68233865.73 | 0.124349E+09 | 0.313986E+09 | 0.140280E+09 |
Annual Sum or Average | 0.362794E+10 | 0.147565E+10 | 0.215229E+10 | 0.752927E+10 | 0.642628E+09 |
Minimum of Months | 0.192583E+09 | 68233865.73 | 0.124349E+09 | 0.313986E+09 | 167656.56 |
Maximum of Months | 0.365369E+09 | 0.164276E+09 | 0.230860E+09 | 0.874403E+09 | 0.174232E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257550E+09 | 0.167468E+09 | 90082335.07 | 0.432074E+09 | 91100735.34 |
February | 0.205358E+09 | 0.116795E+09 | 88563446.37 | 0.364382E+09 | 63577872.34 |
March | 0.175710E+09 | 72645397.10 | 0.103064E+09 | 0.318064E+09 | 51107133.23 |
April | 0.121923E+09 | 24975453.13 | 96947571.18 | 0.255207E+09 | 20916104.49 |
May | 98368166.03 | 3122525.28 | 95245640.75 | 0.253086E+09 | 3458286.26 |
June | 89794232.35 | 186916.08 | 89607316.27 | 0.259687E+09 | 303845.89 |
July | 99284742.67 | 833682.71 | 98451059.96 | 0.288842E+09 | 1299761.16 |
August | 0.111615E+09 | 8346807.13 | 0.103268E+09 | 0.312902E+09 | 88924.38 |
September | 0.140070E+09 | 34603902.39 | 0.105467E+09 | 0.363798E+09 | 2011712.12 |
October | 0.200876E+09 | 95513992.58 | 0.105362E+09 | 0.438683E+09 | 5315349.04 |
November | 0.220223E+09 | 0.123596E+09 | 96627063.75 | 0.420587E+09 | 31784530.30 |
December | 0.248308E+09 | 0.156784E+09 | 91523891.56 | 0.427602E+09 | 73275298.33 |
Annual Sum or Average | 0.196908E+10 | 0.804871E+09 | 0.116421E+10 | 0.413491E+10 | 0.344240E+09 |
Minimum of Months | 89794232.35 | 186916.08 | 88563446.37 | 0.253086E+09 | 88924.38 |
Maximum of Months | 0.257550E+09 | 0.167468E+09 | 0.105467E+09 | 0.438683E+09 | 91100735.34 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54698183.53 | 0.00 | 54698183.53 | 69176971.23 | 0.102502E+09 |
February | 58478498.71 | 0.00 | 58478498.71 | 91348043.12 | 73029951.88 |
March | 77233473.39 | 1362.94 | 77232110.44 | 0.119301E+09 | 60524134.10 |
April | 83970605.55 | 479410.66 | 83491194.89 | 0.162674E+09 | 25356784.71 |
May | 98532712.50 | 4036540.06 | 94496172.44 | 0.248950E+09 | 3719680.44 |
June | 0.102205E+09 | 7350764.32 | 94853740.60 | 0.286789E+09 | 496017.00 |
July | 0.106981E+09 | 5324768.18 | 0.101656E+09 | 0.304801E+09 | 1857644.17 |
August | 94741363.18 | 993169.98 | 93748193.20 | 0.273576E+09 | 209248.64 |
September | 81187455.09 | 18756.62 | 81168698.47 | 0.239305E+09 | 2791358.38 |
October | 70248201.14 | 0.00 | 70248201.14 | 0.185405E+09 | 5764249.19 |
November | 59110813.52 | 0.00 | 59110813.52 | 0.125403E+09 | 35970378.28 |
December | 54103315.64 | 0.00 | 54103315.64 | 80484626.70 | 79705986.33 |
Annual Sum or Average | 0.941490E+09 | 18204772.77 | 0.923285E+09 | 0.218721E+10 | 0.391927E+09 |
Minimum of Months | 54103315.64 | 0.00 | 54103315.64 | 69176971.23 | 209248.64 |
Maximum of Months | 0.106981E+09 | 7350764.32 | 0.101656E+09 | 0.304801E+09 | 0.102502E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.245920E+09 | 0.117851E+09 | 0.128069E+09 | 0.387365E+09 | 0.177736E+09 |
February | 0.257639E+09 | 0.119692E+09 | 0.137947E+09 | 0.433609E+09 | 0.125008E+09 |
March | 0.347459E+09 | 0.164276E+09 | 0.183183E+09 | 0.579331E+09 | 99765389.86 |
April | 0.365369E+09 | 0.163107E+09 | 0.202261E+09 | 0.689687E+09 | 46469094.93 |
May | 0.357204E+09 | 0.142810E+09 | 0.214394E+09 | 0.782255E+09 | 6810095.50 |
June | 0.339741E+09 | 0.130390E+09 | 0.209351E+09 | 0.807462E+09 | 857619.03 |
July | 0.361204E+09 | 0.130344E+09 | 0.230860E+09 | 0.871555E+09 | 3349690.67 |
August | 0.330152E+09 | 0.110538E+09 | 0.219614E+09 | 0.799630E+09 | 387305.55 |
September | 0.307809E+09 | 0.111147E+09 | 0.196662E+09 | 0.744520E+09 | 4761178.48 |
October | 0.292427E+09 | 0.125499E+09 | 0.166928E+09 | 0.650936E+09 | 10115173.22 |
November | 0.230434E+09 | 91766114.67 | 0.138668E+09 | 0.455188E+09 | 61785098.74 |
December | 0.192583E+09 | 68233865.73 | 0.124349E+09 | 0.318582E+09 | 0.142335E+09 |
Annual Sum or Average | 0.362794E+10 | 0.147565E+10 | 0.215229E+10 | 0.752012E+10 | 0.679380E+09 |
Minimum of Months | 0.192583E+09 | 68233865.73 | 0.124349E+09 | 0.318582E+09 | 387305.55 |
Maximum of Months | 0.365369E+09 | 0.164276E+09 | 0.230860E+09 | 0.871555E+09 | 0.177736E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69271798.18 | 0.00 | 69271798.18 | 87558694.26 | 0.150034E+09 |
February | 74059328.83 | 0.00 | 74059328.83 | 0.118233E+09 | 0.106017E+09 |
March | 97811320.88 | 1726.08 | 97809594.80 | 0.156083E+09 | 90652415.24 |
April | 0.106343E+09 | 607143.35 | 0.105736E+09 | 0.209041E+09 | 45409706.97 |
May | 0.124785E+09 | 5112023.30 | 0.119673E+09 | 0.299375E+09 | 11485532.68 |
June | 0.129436E+09 | 9309279.20 | 0.120126E+09 | 0.337808E+09 | 3339732.20 |
July | 0.135485E+09 | 6743482.93 | 0.128741E+09 | 0.361149E+09 | 7306680.70 |
August | 0.119984E+09 | 1257787.12 | 0.118726E+09 | 0.316145E+09 | 3167490.21 |
September | 0.102819E+09 | 23754.07 | 0.102795E+09 | 0.279904E+09 | 12501475.54 |
October | 88964914.33 | 0.00 | 88964914.33 | 0.213114E+09 | 21133625.04 |
November | 74860115.64 | 0.00 | 74860115.64 | 0.147411E+09 | 61828143.43 |
December | 68518435.53 | 0.00 | 68518435.53 | 98520938.71 | 0.122965E+09 |
Annual Sum or Average | 0.119234E+10 | 23055196.05 | 0.116928E+10 | 0.262434E+10 | 0.635840E+09 |
Minimum of Months | 68518435.53 | 0.00 | 68518435.53 | 87558694.26 | 3167490.21 |
Maximum of Months | 0.135485E+09 | 9309279.20 | 0.128741E+09 | 0.361149E+09 | 0.150034E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 25536453.13 | 0.00 | 25536453.13 | 32277760.22 | 55308760.98 |
February | 27301335.16 | 0.00 | 27301335.16 | 43585682.78 | 39082279.74 |
March | 36057302.93 | 636.31 | 36056666.62 | 57538758.96 | 33418233.88 |
April | 39202607.73 | 223818.18 | 38978789.56 | 77061296.74 | 16739898.26 |
May | 46001088.74 | 1884503.46 | 44116585.28 | 0.110362E+09 | 4234042.92 |
June | 47715305.71 | 3431785.78 | 44283519.93 | 0.124530E+09 | 1231163.58 |
July | 49945200.41 | 2485927.03 | 47459273.38 | 0.133135E+09 | 2693545.05 |
August | 44231055.29 | 463672.41 | 43767382.88 | 0.116544E+09 | 1167668.05 |
September | 37903263.10 | 8756.73 | 37894506.36 | 0.103184E+09 | 4608561.53 |
October | 32796151.17 | 0.00 | 32796151.17 | 78562521.86 | 7790970.85 |
November | 27596538.34 | 0.00 | 27596538.34 | 54341676.87 | 22792413.77 |
December | 25258732.46 | 0.00 | 25258732.46 | 36318897.44 | 45329810.38 |
Annual Sum or Average | 0.439545E+09 | 8499099.90 | 0.431046E+09 | 0.967442E+09 | 0.234397E+09 |
Minimum of Months | 25258732.46 | 0.00 | 25258732.46 | 32277760.22 | 1167668.05 |
Maximum of Months | 49945200.41 | 3431785.78 | 47459273.38 | 0.133135E+09 | 55308760.98 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120172E+09 | 78139865.69 | 42032054.54 | 0.202079E+09 | 50385370.02 |
February | 95819190.52 | 54495843.32 | 41323347.19 | 0.170335E+09 | 36234044.29 |
March | 81985346.99 | 33896049.55 | 48089297.44 | 0.148917E+09 | 31350907.70 |
April | 56888791.83 | 11653445.79 | 45235346.04 | 0.118029E+09 | 17026558.31 |
May | 45898189.87 | 1456957.71 | 44441232.16 | 0.110935E+09 | 4318010.30 |
June | 41897626.97 | 87214.29 | 41810412.68 | 0.111169E+09 | 1240674.55 |
July | 46325860.84 | 388992.99 | 45936867.85 | 0.124952E+09 | 2704819.81 |
August | 52079249.98 | 3894586.57 | 48184663.41 | 0.134720E+09 | 1145224.65 |
September | 65356300.36 | 16146041.41 | 49210258.95 | 0.161482E+09 | 4537403.53 |
October | 93727812.46 | 44566444.04 | 49161368.42 | 0.197224E+09 | 7608031.63 |
November | 0.102755E+09 | 57669388.50 | 45085798.57 | 0.192047E+09 | 21168414.12 |
December | 0.115859E+09 | 73154797.97 | 42704678.99 | 0.198896E+09 | 42479366.81 |
Annual Sum or Average | 0.918765E+09 | 0.375550E+09 | 0.543215E+09 | 0.187078E+10 | 0.220199E+09 |
Minimum of Months | 41897626.97 | 87214.29 | 41323347.19 | 0.110935E+09 | 1145224.65 |
Maximum of Months | 0.120172E+09 | 78139865.69 | 49210258.95 | 0.202079E+09 | 50385370.02 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.326171E+09 | 0.212088E+09 | 0.114084E+09 | 0.548483E+09 | 0.136756E+09 |
February | 0.260073E+09 | 0.147913E+09 | 0.112160E+09 | 0.462323E+09 | 98346607.71 |
March | 0.222525E+09 | 92000811.75 | 0.130524E+09 | 0.404191E+09 | 85092776.18 |
April | 0.154408E+09 | 31629835.53 | 0.122778E+09 | 0.320356E+09 | 46213561.96 |
May | 0.124577E+09 | 3954481.25 | 0.120623E+09 | 0.301100E+09 | 11719963.20 |
June | 0.113719E+09 | 236717.42 | 0.113482E+09 | 0.301736E+09 | 3367444.49 |
July | 0.125738E+09 | 1055806.55 | 0.124682E+09 | 0.339145E+09 | 7341434.23 |
August | 0.141354E+09 | 10570704.58 | 0.130783E+09 | 0.365657E+09 | 3108373.95 |
September | 0.177390E+09 | 43823658.99 | 0.133567E+09 | 0.438296E+09 | 12315441.29 |
October | 0.254396E+09 | 0.120962E+09 | 0.133434E+09 | 0.535306E+09 | 20649754.03 |
November | 0.278899E+09 | 0.156527E+09 | 0.122372E+09 | 0.521254E+09 | 57455405.82 |
December | 0.314466E+09 | 0.198557E+09 | 0.115909E+09 | 0.539845E+09 | 0.115298E+09 |
Annual Sum or Average | 0.249372E+10 | 0.101932E+10 | 0.147440E+10 | 0.507769E+10 | 0.597665E+09 |
Minimum of Months | 0.113719E+09 | 236717.42 | 0.112160E+09 | 0.301100E+09 | 3108373.95 |
Maximum of Months | 0.326171E+09 | 0.212088E+09 | 0.133567E+09 | 0.548483E+09 | 0.136756E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257550E+09 | 0.167468E+09 | 90082335.07 | 0.430945E+09 | 89138412.51 |
February | 0.205358E+09 | 0.116795E+09 | 88563446.37 | 0.362618E+09 | 62590946.26 |
March | 0.175710E+09 | 72645397.10 | 0.103064E+09 | 0.316551E+09 | 50344968.42 |
April | 0.121923E+09 | 24975453.13 | 96947571.18 | 0.253874E+09 | 20542503.26 |
May | 98368166.03 | 3122525.28 | 95245640.75 | 0.253218E+09 | 3190345.61 |
June | 89794232.35 | 186916.08 | 89607316.27 | 0.261702E+09 | 189085.68 |
July | 99284742.67 | 833682.71 | 98451059.96 | 0.289558E+09 | 1095559.34 |
August | 0.111615E+09 | 8346807.13 | 0.103268E+09 | 0.312773E+09 | 86785.98 |
September | 0.140070E+09 | 34603902.39 | 0.105467E+09 | 0.363735E+09 | 1516024.10 |
October | 0.200876E+09 | 95513992.58 | 0.105362E+09 | 0.437609E+09 | 4706129.01 |
November | 0.220223E+09 | 0.123596E+09 | 96627063.75 | 0.418950E+09 | 30532822.99 |
December | 0.248308E+09 | 0.156784E+09 | 91523891.56 | 0.424018E+09 | 72307549.34 |
Annual Sum or Average | 0.196908E+10 | 0.804871E+09 | 0.116421E+10 | 0.412555E+10 | 0.336241E+09 |
Minimum of Months | 89794232.35 | 186916.08 | 88563446.37 | 0.253218E+09 | 86785.98 |
Maximum of Months | 0.257550E+09 | 0.167468E+09 | 0.105467E+09 | 0.437609E+09 | 89138412.51 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221564E+09 | 95806949.54 | 0.125757E+09 | 0.345486E+09 | 0.178611E+09 |
February | 0.251167E+09 | 0.114393E+09 | 0.136774E+09 | 0.430090E+09 | 0.124842E+09 |
March | 0.344456E+09 | 0.157460E+09 | 0.186996E+09 | 0.588276E+09 | 99161676.21 |
April | 0.365885E+09 | 0.169185E+09 | 0.196700E+09 | 0.692987E+09 | 37930736.02 |
May | 0.345789E+09 | 0.133502E+09 | 0.212287E+09 | 0.760248E+09 | 5928516.27 |
June | 0.283325E+09 | 79500419.30 | 0.203825E+09 | 0.703742E+09 | 355749.32 |
July | 0.326686E+09 | 0.100960E+09 | 0.225726E+09 | 0.804753E+09 | 2041597.07 |
August | 0.325925E+09 | 0.105939E+09 | 0.219986E+09 | 0.784807E+09 | 124632.72 |
September | 0.269154E+09 | 79319231.83 | 0.189834E+09 | 0.666417E+09 | 2891993.47 |
October | 0.277185E+09 | 0.108264E+09 | 0.168920E+09 | 0.614532E+09 | 8845026.48 |
November | 0.220665E+09 | 80823817.61 | 0.139841E+09 | 0.438396E+09 | 61060287.62 |
December | 0.228615E+09 | 0.102173E+09 | 0.126442E+09 | 0.378645E+09 | 0.141207E+09 |
Annual Sum or Average | 0.346042E+10 | 0.132733E+10 | 0.213309E+10 | 0.720838E+10 | 0.663000E+09 |
Minimum of Months | 0.220665E+09 | 79319231.83 | 0.125757E+09 | 0.345486E+09 | 124632.72 |
Maximum of Months | 0.365885E+09 | 0.169185E+09 | 0.225726E+09 | 0.804753E+09 | 0.178611E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54698183.53 | 0.00 | 54698183.53 | 72809364.40 | 99856052.06 |
February | 58478498.71 | 0.00 | 58478498.71 | 93850826.27 | 72134811.07 |
March | 77233473.39 | 1362.94 | 77232110.44 | 0.120703E+09 | 60981729.30 |
April | 83970605.55 | 479410.66 | 83491194.89 | 0.163636E+09 | 25877668.85 |
May | 98532712.50 | 4036540.06 | 94496172.44 | 0.249006E+09 | 3508242.84 |
June | 0.102205E+09 | 7350764.32 | 94853740.60 | 0.288228E+09 | 383344.39 |
July | 0.106981E+09 | 5324768.18 | 0.101656E+09 | 0.305265E+09 | 1663150.59 |
August | 94741363.18 | 993169.98 | 93748193.20 | 0.273693E+09 | 199436.04 |
September | 81187455.09 | 18756.62 | 81168698.47 | 0.241115E+09 | 2230168.93 |
October | 70248201.14 | 0.00 | 70248201.14 | 0.187864E+09 | 4891092.88 |
November | 59110813.52 | 0.00 | 59110813.52 | 0.128307E+09 | 34259609.62 |
December | 54103315.64 | 0.00 | 54103315.64 | 81510501.68 | 79105069.00 |
Annual Sum or Average | 0.941490E+09 | 18204772.77 | 0.923285E+09 | 0.220599E+10 | 0.385090E+09 |
Minimum of Months | 54103315.64 | 0.00 | 54103315.64 | 72809364.40 | 199436.04 |
Maximum of Months | 0.106981E+09 | 7350764.32 | 0.101656E+09 | 0.305265E+09 | 99856052.06 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221564E+09 | 95806949.54 | 0.125757E+09 | 0.353603E+09 | 0.181753E+09 |
February | 0.251167E+09 | 0.114393E+09 | 0.136774E+09 | 0.432789E+09 | 0.133005E+09 |
March | 0.344456E+09 | 0.157460E+09 | 0.186996E+09 | 0.585246E+09 | 0.110798E+09 |
April | 0.365885E+09 | 0.169185E+09 | 0.196700E+09 | 0.686395E+09 | 48229712.94 |
May | 0.345789E+09 | 0.133502E+09 | 0.212287E+09 | 0.755911E+09 | 6795418.39 |
June | 0.283325E+09 | 79500419.30 | 0.203825E+09 | 0.700816E+09 | 683362.66 |
July | 0.326686E+09 | 0.100960E+09 | 0.225726E+09 | 0.801857E+09 | 3043117.68 |
August | 0.325925E+09 | 0.105939E+09 | 0.219986E+09 | 0.784835E+09 | 275744.10 |
September | 0.269154E+09 | 79319231.83 | 0.189834E+09 | 0.669422E+09 | 4041488.24 |
October | 0.277185E+09 | 0.108264E+09 | 0.168920E+09 | 0.620504E+09 | 9006677.69 |
November | 0.220665E+09 | 80823817.61 | 0.139841E+09 | 0.444430E+09 | 63657744.87 |
December | 0.228615E+09 | 0.102173E+09 | 0.126442E+09 | 0.385809E+09 | 0.144094E+09 |
Annual Sum or Average | 0.346042E+10 | 0.132733E+10 | 0.213309E+10 | 0.722162E+10 | 0.705382E+09 |
Minimum of Months | 0.220665E+09 | 79319231.83 | 0.125757E+09 | 0.353603E+09 | 275744.10 |
Maximum of Months | 0.365885E+09 | 0.169185E+09 | 0.225726E+09 | 0.801857E+09 | 0.181753E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.377722E+09 | 0.245608E+09 | 0.132114E+09 | 0.624155E+09 | 0.135532E+09 |
February | 0.301177E+09 | 0.171290E+09 | 0.129887E+09 | 0.528596E+09 | 93162556.88 |
March | 0.257695E+09 | 0.106541E+09 | 0.151153E+09 | 0.466343E+09 | 71855066.51 |
April | 0.178812E+09 | 36628898.92 | 0.142183E+09 | 0.382003E+09 | 26089937.85 |
May | 0.144266E+09 | 4579482.99 | 0.139687E+09 | 0.387756E+09 | 3999836.76 |
June | 0.131692E+09 | 274130.37 | 0.131418E+09 | 0.399135E+09 | 175501.64 |
July | 0.145611E+09 | 1222675.71 | 0.144388E+09 | 0.441824E+09 | 1164607.08 |
August | 0.163695E+09 | 12241393.70 | 0.151453E+09 | 0.473985E+09 | 46581.27 |
September | 0.205427E+09 | 50749943.80 | 0.154677E+09 | 0.542639E+09 | 1644825.04 |
October | 0.294604E+09 | 0.140080E+09 | 0.154523E+09 | 0.645641E+09 | 6404345.59 |
November | 0.322978E+09 | 0.181265E+09 | 0.141713E+09 | 0.612230E+09 | 45642822.40 |
December | 0.364167E+09 | 0.229939E+09 | 0.134229E+09 | 0.616075E+09 | 0.110158E+09 |
Annual Sum or Average | 0.288785E+10 | 0.118042E+10 | 0.170742E+10 | 0.612038E+10 | 0.495876E+09 |
Minimum of Months | 0.131692E+09 | 274130.37 | 0.129887E+09 | 0.382003E+09 | 46581.27 |
Maximum of Months | 0.377722E+09 | 0.245608E+09 | 0.154677E+09 | 0.645641E+09 | 0.135532E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.382873E+09 | 0.00 | 0.382873E+09 | 0.411086E+09 | 0.995556E+09 |
February | 0.409334E+09 | 0.00 | 0.409334E+09 | 0.559795E+09 | 0.739434E+09 |
March | 0.540614E+09 | 9540.24 | 0.540604E+09 | 0.745333E+09 | 0.652542E+09 |
April | 0.587772E+09 | 3355747.53 | 0.584416E+09 | 0.103256E+10 | 0.352099E+09 |
May | 0.689703E+09 | 28254710.30 | 0.661448E+09 | 0.149620E+10 | 0.127847E+09 |
June | 0.715404E+09 | 51453401.44 | 0.663951E+09 | 0.171391E+10 | 41411858.37 |
July | 0.748838E+09 | 37271965.62 | 0.711566E+09 | 0.186892E+10 | 68486076.01 |
August | 0.663164E+09 | 6951926.59 | 0.656212E+09 | 0.160111E+10 | 43394934.91 |
September | 0.568291E+09 | 131291.34 | 0.568159E+09 | 0.143745E+10 | 0.100740E+09 |
October | 0.491719E+09 | 0.00 | 0.491719E+09 | 0.108555E+10 | 0.168999E+09 |
November | 0.413760E+09 | 0.00 | 0.413760E+09 | 0.717151E+09 | 0.428138E+09 |
December | 0.378709E+09 | 0.00 | 0.378709E+09 | 0.465267E+09 | 0.840030E+09 |
Annual Sum or Average | 0.659018E+10 | 0.127429E+09 | 0.646275E+10 | 0.131343E+11 | 0.455868E+10 |
Minimum of Months | 0.378709E+09 | 0.00 | 0.378709E+09 | 0.411086E+09 | 41411858.37 |
Maximum of Months | 0.748838E+09 | 51453401.44 | 0.711566E+09 | 0.186892E+10 | 0.995556E+09 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.382873E+09 | 0.00 | 0.382873E+09 | 0.386285E+09 | 0.104296E+10 |
February | 0.409334E+09 | 0.00 | 0.409334E+09 | 0.532522E+09 | 0.776728E+09 |
March | 0.540614E+09 | 9540.24 | 0.540604E+09 | 0.713616E+09 | 0.688369E+09 |
April | 0.587772E+09 | 3355747.53 | 0.584416E+09 | 0.100274E+10 | 0.375370E+09 |
May | 0.689703E+09 | 28254710.30 | 0.661448E+09 | 0.146433E+10 | 0.143721E+09 |
June | 0.715404E+09 | 51453401.44 | 0.663951E+09 | 0.167949E+10 | 47797530.17 |
July | 0.748838E+09 | 37271965.62 | 0.711566E+09 | 0.183808E+10 | 77075224.78 |
August | 0.663164E+09 | 6951926.59 | 0.656212E+09 | 0.156460E+10 | 50573767.72 |
September | 0.568291E+09 | 131291.34 | 0.568159E+09 | 0.140561E+10 | 0.109788E+09 |
October | 0.491719E+09 | 0.00 | 0.491719E+09 | 0.105560E+10 | 0.185777E+09 |
November | 0.413760E+09 | 0.00 | 0.413760E+09 | 0.688971E+09 | 0.455095E+09 |
December | 0.378709E+09 | 0.00 | 0.378709E+09 | 0.440681E+09 | 0.884181E+09 |
Annual Sum or Average | 0.659018E+10 | 0.127429E+09 | 0.646275E+10 | 0.127725E+11 | 0.483744E+10 |
Minimum of Months | 0.378709E+09 | 0.00 | 0.378709E+09 | 0.386285E+09 | 47797530.17 |
Maximum of Months | 0.748838E+09 | 51453401.44 | 0.711566E+09 | 0.183808E+10 | 0.104296E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54698183.53 | 0.00 | 54698183.53 | 73315347.89 | 0.137984E+09 |
February | 58478498.71 | 0.00 | 58478498.71 | 93573972.70 | 0.106756E+09 |
March | 77233473.39 | 1362.94 | 77232110.44 | 0.124585E+09 | 96552093.46 |
April | 83970605.55 | 479410.66 | 83491194.89 | 0.173585E+09 | 54579105.80 |
May | 98532712.50 | 4036540.06 | 94496172.44 | 0.248911E+09 | 25498824.88 |
June | 0.102205E+09 | 7350764.32 | 94853740.60 | 0.281245E+09 | 10166548.69 |
July | 0.106981E+09 | 5324768.18 | 0.101656E+09 | 0.311020E+09 | 15322169.37 |
August | 94741363.18 | 993169.98 | 93748193.20 | 0.262655E+09 | 10729226.36 |
September | 81187455.09 | 18756.62 | 81168698.47 | 0.239378E+09 | 16372089.61 |
October | 70248201.14 | 0.00 | 70248201.14 | 0.185740E+09 | 28373951.72 |
November | 59110813.52 | 0.00 | 59110813.52 | 0.126665E+09 | 63321646.11 |
December | 54103315.64 | 0.00 | 54103315.64 | 83293178.22 | 0.115985E+09 |
Annual Sum or Average | 0.941490E+09 | 18204772.77 | 0.923285E+09 | 0.220397E+10 | 0.681641E+09 |
Minimum of Months | 54103315.64 | 0.00 | 54103315.64 | 73315347.89 | 10166548.69 |
Maximum of Months | 0.106981E+09 | 7350764.32 | 0.101656E+09 | 0.311020E+09 | 0.137984E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.491805E+09 | 0.235685E+09 | 0.256120E+09 | 0.789618E+09 | 0.484673E+09 |
February | 0.515241E+09 | 0.239367E+09 | 0.275874E+09 | 0.870095E+09 | 0.374041E+09 |
March | 0.694868E+09 | 0.328529E+09 | 0.366339E+09 | 0.117099E+10 | 0.334127E+09 |
April | 0.730685E+09 | 0.326192E+09 | 0.404494E+09 | 0.141296E+10 | 0.205894E+09 |
May | 0.714357E+09 | 0.285600E+09 | 0.428757E+09 | 0.154356E+10 | 97124913.88 |
June | 0.679434E+09 | 0.260761E+09 | 0.418673E+09 | 0.158154E+10 | 38535188.54 |
July | 0.722357E+09 | 0.260669E+09 | 0.461688E+09 | 0.175597E+10 | 57824645.91 |
August | 0.660257E+09 | 0.221061E+09 | 0.439197E+09 | 0.154353E+10 | 40768145.69 |
September | 0.615575E+09 | 0.222279E+09 | 0.393296E+09 | 0.148122E+10 | 61723288.93 |
October | 0.584813E+09 | 0.250981E+09 | 0.333833E+09 | 0.129676E+10 | 0.106527E+09 |
November | 0.460835E+09 | 0.183519E+09 | 0.277316E+09 | 0.911581E+09 | 0.224133E+09 |
December | 0.385138E+09 | 0.136458E+09 | 0.248680E+09 | 0.643671E+09 | 0.417225E+09 |
Annual Sum or Average | 0.725536E+10 | 0.295110E+10 | 0.430427E+10 | 0.150015E+11 | 0.244260E+10 |
Minimum of Months | 0.385138E+09 | 0.136458E+09 | 0.248680E+09 | 0.643671E+09 | 38535188.54 |
Maximum of Months | 0.730685E+09 | 0.328529E+09 | 0.461688E+09 | 0.175597E+10 | 0.484673E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257550E+09 | 0.167468E+09 | 90082335.07 | 0.440512E+09 | 0.127468E+09 |
February | 0.205358E+09 | 0.116795E+09 | 88563446.37 | 0.367868E+09 | 99184857.56 |
March | 0.175710E+09 | 72645397.10 | 0.103064E+09 | 0.321597E+09 | 91374976.25 |
April | 0.121923E+09 | 24975453.13 | 96947571.18 | 0.262030E+09 | 54682951.67 |
May | 98368166.03 | 3122525.28 | 95245640.75 | 0.246623E+09 | 25819854.20 |
June | 89794232.35 | 186916.08 | 89607316.27 | 0.251907E+09 | 10144396.27 |
July | 99284742.67 | 833682.71 | 98451059.96 | 0.292368E+09 | 15387938.89 |
August | 0.111615E+09 | 8346807.13 | 0.103268E+09 | 0.300027E+09 | 10800977.92 |
September | 0.140070E+09 | 34603902.39 | 0.105467E+09 | 0.365240E+09 | 16358623.47 |
October | 0.200876E+09 | 95513992.58 | 0.105362E+09 | 0.441574E+09 | 28058054.86 |
November | 0.220223E+09 | 0.123596E+09 | 96627063.75 | 0.424980E+09 | 59580558.79 |
December | 0.248308E+09 | 0.156784E+09 | 91523891.56 | 0.434605E+09 | 0.109183E+09 |
Annual Sum or Average | 0.196908E+10 | 0.804871E+09 | 0.116421E+10 | 0.414933E+10 | 0.648044E+09 |
Minimum of Months | 89794232.35 | 186916.08 | 88563446.37 | 0.246623E+09 | 10144396.27 |
Maximum of Months | 0.257550E+09 | 0.167468E+09 | 0.105467E+09 | 0.441574E+09 | 0.127468E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69271798.18 | 0.00 | 69271798.18 | 83475741.54 | 0.147295E+09 |
February | 74059328.83 | 0.00 | 74059328.83 | 0.112291E+09 | 0.106305E+09 |
March | 97811320.88 | 1726.08 | 97809594.80 | 0.148189E+09 | 91367537.90 |
April | 0.106343E+09 | 607143.35 | 0.105736E+09 | 0.197493E+09 | 49161881.40 |
May | 0.124785E+09 | 5112023.30 | 0.119673E+09 | 0.280235E+09 | 15394077.89 |
June | 0.129436E+09 | 9309279.20 | 0.120126E+09 | 0.316304E+09 | 5152759.40 |
July | 0.135485E+09 | 6743482.93 | 0.128741E+09 | 0.341797E+09 | 9852071.20 |
August | 0.119984E+09 | 1257787.12 | 0.118726E+09 | 0.296853E+09 | 4989922.09 |
September | 0.102819E+09 | 23754.07 | 0.102795E+09 | 0.263504E+09 | 14900189.38 |
October | 88964914.33 | 0.00 | 88964914.33 | 0.200482E+09 | 23692042.34 |
November | 74860115.64 | 0.00 | 74860115.64 | 0.138533E+09 | 62053424.89 |
December | 68518435.53 | 0.00 | 68518435.53 | 93132498.88 | 0.122244E+09 |
Annual Sum or Average | 0.119234E+10 | 23055196.05 | 0.116928E+10 | 0.247229E+10 | 0.652408E+09 |
Minimum of Months | 68518435.53 | 0.00 | 68518435.53 | 83475741.54 | 4989922.09 |
Maximum of Months | 0.135485E+09 | 9309279.20 | 0.128741E+09 | 0.341797E+09 | 0.147295E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61977740.30 | 0.00 | 61977740.30 | 74686062.13 | 0.131783E+09 |
February | 66261162.11 | 0.00 | 66261162.11 | 0.100467E+09 | 95111719.73 |
March | 87512159.40 | 1544.33 | 87510615.07 | 0.132585E+09 | 81746882.35 |
April | 95145908.84 | 543213.46 | 94602695.38 | 0.176698E+09 | 43985321.56 |
May | 0.111646E+09 | 4573746.61 | 0.107072E+09 | 0.250727E+09 | 13773139.81 |
June | 0.115806E+09 | 8329047.37 | 0.107477E+09 | 0.282999E+09 | 4610193.36 |
July | 0.121219E+09 | 6033419.73 | 0.115185E+09 | 0.305807E+09 | 8814685.44 |
August | 0.107350E+09 | 1125346.90 | 0.106225E+09 | 0.265595E+09 | 4464502.20 |
September | 91992360.30 | 21252.86 | 91971107.44 | 0.235758E+09 | 13331255.90 |
October | 79597245.94 | 0.00 | 79597245.94 | 0.179372E+09 | 21197791.09 |
November | 66977629.11 | 0.00 | 66977629.11 | 0.123946E+09 | 55519361.62 |
December | 61303703.89 | 0.00 | 61303703.89 | 83325996.86 | 0.109371E+09 |
Annual Sum or Average | 0.106679E+10 | 20627571.26 | 0.104616E+10 | 0.221197E+10 | 0.583709E+09 |
Minimum of Months | 61303703.89 | 0.00 | 61303703.89 | 74686062.13 | 4464502.20 |
Maximum of Months | 0.121219E+09 | 8329047.37 | 0.115185E+09 | 0.305807E+09 | 0.131783E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.961512E+09 | 0.625208E+09 | 0.336304E+09 | 0.159405E+10 | 0.396370E+09 |
February | 0.766662E+09 | 0.436029E+09 | 0.330634E+09 | 0.133490E+10 | 0.291879E+09 |
March | 0.655976E+09 | 0.271207E+09 | 0.384769E+09 | 0.115950E+10 | 0.254024E+09 |
April | 0.455175E+09 | 93240808.86 | 0.361934E+09 | 0.905710E+09 | 0.148208E+09 |
May | 0.367238E+09 | 11657317.33 | 0.355580E+09 | 0.830113E+09 | 45784097.47 |
June | 0.335229E+09 | 697813.43 | 0.334531E+09 | 0.827499E+09 | 15890276.72 |
July | 0.370660E+09 | 3112385.99 | 0.367547E+09 | 0.942643E+09 | 29480987.95 |
August | 0.416693E+09 | 31161118.24 | 0.385532E+09 | 0.101904E+10 | 14833110.84 |
September | 0.522925E+09 | 0.129187E+09 | 0.393738E+09 | 0.123834E+10 | 43918917.36 |
October | 0.749929E+09 | 0.356582E+09 | 0.393347E+09 | 0.153159E+10 | 69423142.78 |
November | 0.822158E+09 | 0.461421E+09 | 0.360738E+09 | 0.150037E+10 | 0.171168E+09 |
December | 0.927007E+09 | 0.585322E+09 | 0.341686E+09 | 0.156377E+10 | 0.338182E+09 |
Annual Sum or Average | 0.735116E+10 | 0.300482E+10 | 0.434634E+10 | 0.144475E+11 | 0.181916E+10 |
Minimum of Months | 0.335229E+09 | 697813.43 | 0.330634E+09 | 0.827499E+09 | 14833110.84 |
Maximum of Months | 0.961512E+09 | 0.625208E+09 | 0.393738E+09 | 0.159405E+10 | 0.396370E+09 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 794.27 | 211.10 | 486.34 | 316.24 | 170.10 | 0.00 | 0.00 |
February | 739.20 | 175.83 | 429.33 | 244.18 | 185.15 | 0.00 | 0.00 |
March | 582.41 | 141.31 | 331.80 | 137.18 | 194.62 | 0.00 | 0.00 |
April | 469.88 | 86.80 | 237.90 | 48.73 | 189.17 | 0.00 | 0.00 |
May | 408.53 | 31.07 | 185.75 | 5.90 | 179.85 | 0.00 | 0.00 |
June | 416.56 | 9.88 | 175.21 | 0.36 | 174.85 | 0.00 | 0.00 |
July | 458.11 | 18.89 | 187.48 | 1.57 | 185.91 | 0.00 | 0.00 |
August | 494.00 | 8.81 | 210.77 | 15.76 | 195.00 | 0.00 | 0.00 |
September | 626.87 | 27.07 | 273.32 | 67.52 | 205.79 | 0.00 | 0.00 |
October | 759.58 | 47.04 | 379.32 | 180.36 | 198.96 | 0.00 | 0.00 |
November | 771.02 | 101.28 | 429.72 | 241.17 | 188.55 | 0.00 | 0.00 |
December | 783.42 | 183.12 | 468.89 | 296.06 | 172.83 | 0.00 | 0.00 |
Annual Sum or Average | 607.99 | 86.45 | 315.80 | 129.08 | 186.71 | 0.00 | 0.00 |
Minimum of Months | 408.53 | 8.81 | 175.21 | 0.36 | 170.10 | 0.00 | 0.00 |
Maximum of Months | 794.27 | 211.10 | 486.34 | 316.24 | 205.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2203.30 | 665.16 | 1369.50 | 890.50 | 479.00 | 0.00 | 0.00 |
February | 2050.32 | 555.13 | 1208.97 | 687.59 | 521.38 | 0.00 | 0.00 |
March | 1617.82 | 448.87 | 934.32 | 386.29 | 548.03 | 0.00 | 0.00 |
April | 1312.82 | 274.35 | 669.92 | 137.23 | 532.69 | 0.00 | 0.00 |
May | 1151.37 | 102.43 | 523.06 | 16.60 | 506.46 | 0.00 | 0.00 |
June | 1183.19 | 34.89 | 493.39 | 1.03 | 492.36 | 0.00 | 0.00 |
July | 1303.14 | 56.28 | 527.93 | 4.43 | 523.50 | 0.00 | 0.00 |
August | 1393.64 | 32.18 | 593.50 | 44.38 | 549.12 | 0.00 | 0.00 |
September | 1764.08 | 83.85 | 769.64 | 190.14 | 579.50 | 0.00 | 0.00 |
October | 2126.91 | 146.02 | 1068.14 | 507.89 | 560.25 | 0.00 | 0.00 |
November | 2147.61 | 318.85 | 1210.05 | 679.12 | 530.93 | 0.00 | 0.00 |
December | 2177.45 | 579.96 | 1320.36 | 833.69 | 486.67 | 0.00 | 0.00 |
Annual Sum or Average | 1700.88 | 273.59 | 889.27 | 363.49 | 525.77 | 0.00 | 0.00 |
Minimum of Months | 1151.37 | 32.18 | 493.39 | 1.03 | 479.00 | 0.00 | 0.00 |
Maximum of Months | 2203.30 | 665.16 | 1369.50 | 890.50 | 579.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2946.24 | 866.87 | 1779.06 | 1156.81 | 622.25 | 0.00 | 0.00 |
February | 2748.18 | 718.33 | 1570.52 | 893.22 | 677.31 | 0.00 | 0.00 |
March | 2173.52 | 580.22 | 1213.73 | 501.81 | 711.92 | 0.00 | 0.00 |
April | 1768.59 | 351.50 | 870.27 | 178.27 | 692.00 | 0.00 | 0.00 |
May | 1550.03 | 129.11 | 679.49 | 21.57 | 657.92 | 0.00 | 0.00 |
June | 1595.20 | 43.91 | 640.94 | 1.33 | 639.60 | 0.00 | 0.00 |
July | 1762.65 | 70.56 | 685.82 | 5.76 | 680.06 | 0.00 | 0.00 |
August | 1884.25 | 39.11 | 770.99 | 57.66 | 713.34 | 0.00 | 0.00 |
September | 2387.29 | 104.55 | 999.80 | 247.00 | 752.80 | 0.00 | 0.00 |
October | 2860.54 | 173.45 | 1387.58 | 659.78 | 727.80 | 0.00 | 0.00 |
November | 2878.81 | 404.56 | 1571.93 | 882.22 | 689.71 | 0.00 | 0.00 |
December | 2906.63 | 750.29 | 1715.22 | 1083.01 | 632.21 | 0.00 | 0.00 |
Annual Sum or Average | 2286.15 | 351.09 | 1155.21 | 472.20 | 683.01 | 0.00 | 0.00 |
Minimum of Months | 1550.03 | 39.11 | 640.94 | 1.33 | 622.25 | 0.00 | 0.00 |
Maximum of Months | 2946.24 | 866.87 | 1779.06 | 1156.81 | 752.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 289.61 | 100.03 | 178.88 | 98.30 | 80.59 | 0.00 | 0.00 |
February | 329.45 | 78.35 | 188.71 | 95.56 | 93.15 | 0.00 | 0.00 |
March | 340.53 | 56.79 | 194.21 | 85.91 | 108.30 | 0.00 | 0.00 |
April | 368.80 | 23.96 | 188.20 | 74.91 | 113.29 | 0.00 | 0.00 |
May | 380.25 | 3.83 | 165.83 | 51.01 | 114.82 | 0.00 | 0.00 |
June | 373.70 | 0.30 | 143.95 | 30.74 | 113.21 | 0.00 | 0.00 |
July | 410.26 | 1.42 | 159.04 | 38.01 | 121.03 | 0.00 | 0.00 |
August | 411.13 | 0.11 | 163.36 | 42.67 | 120.69 | 0.00 | 0.00 |
September | 399.08 | 2.25 | 157.88 | 43.95 | 113.93 | 0.00 | 0.00 |
October | 394.10 | 5.94 | 178.49 | 76.08 | 102.41 | 0.00 | 0.00 |
November | 331.84 | 36.51 | 170.10 | 78.87 | 91.23 | 0.00 | 0.00 |
December | 301.09 | 80.84 | 178.06 | 96.68 | 81.38 | 0.00 | 0.00 |
Annual Sum or Average | 361.00 | 32.33 | 172.17 | 67.61 | 104.56 | 0.00 | 0.00 |
Minimum of Months | 289.61 | 0.11 | 143.95 | 30.74 | 80.59 | 0.00 | 0.00 |
Maximum of Months | 411.13 | 100.03 | 194.21 | 98.30 | 121.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 158.72 | 107.82 | 103.14 | 35.77 | 67.37 | 0.00 | 0.00 |
February | 218.75 | 86.63 | 127.99 | 47.29 | 80.71 | 0.00 | 0.00 |
March | 265.79 | 65.01 | 157.44 | 58.79 | 98.65 | 0.00 | 0.00 |
April | 331.05 | 29.50 | 173.56 | 65.46 | 108.10 | 0.00 | 0.00 |
May | 377.22 | 4.18 | 165.89 | 51.35 | 114.54 | 0.00 | 0.00 |
June | 383.13 | 0.50 | 148.74 | 33.51 | 115.23 | 0.00 | 0.00 |
July | 415.19 | 1.91 | 161.91 | 39.68 | 122.23 | 0.00 | 0.00 |
August | 396.46 | 0.21 | 157.06 | 39.92 | 117.13 | 0.00 | 0.00 |
September | 352.23 | 2.97 | 135.16 | 30.61 | 104.55 | 0.00 | 0.00 |
October | 301.80 | 6.26 | 129.72 | 40.42 | 89.30 | 0.00 | 0.00 |
November | 220.99 | 40.02 | 107.94 | 31.18 | 76.76 | 0.00 | 0.00 |
December | 174.37 | 85.90 | 105.55 | 38.15 | 67.41 | 0.00 | 0.00 |
Annual Sum or Average | 300.06 | 35.69 | 139.58 | 42.67 | 96.92 | 0.00 | 0.00 |
Minimum of Months | 158.72 | 0.21 | 103.14 | 30.61 | 67.37 | 0.00 | 0.00 |
Maximum of Months | 415.19 | 107.82 | 173.56 | 65.46 | 122.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 113.88 | 53.21 | 76.91 | 50.01 | 26.90 | 0.00 | 0.00 |
February | 104.21 | 45.75 | 67.90 | 38.61 | 29.28 | 0.00 | 0.00 |
March | 78.97 | 38.81 | 52.47 | 21.69 | 30.78 | 0.00 | 0.00 |
April | 62.62 | 27.04 | 37.62 | 7.71 | 29.92 | 0.00 | 0.00 |
May | 52.86 | 14.68 | 29.38 | 0.93 | 28.44 | 0.00 | 0.00 |
June | 52.65 | 7.69 | 27.71 | 0.06 | 27.65 | 0.00 | 0.00 |
July | 61.71 | 9.97 | 29.65 | 0.25 | 29.40 | 0.00 | 0.00 |
August | 65.61 | 8.50 | 33.33 | 2.49 | 30.84 | 0.00 | 0.00 |
September | 87.15 | 11.16 | 43.22 | 10.68 | 32.54 | 0.00 | 0.00 |
October | 109.86 | 17.76 | 59.99 | 28.52 | 31.46 | 0.00 | 0.00 |
November | 110.74 | 29.95 | 67.96 | 38.14 | 29.82 | 0.00 | 0.00 |
December | 112.65 | 48.14 | 74.15 | 46.82 | 27.33 | 0.00 | 0.00 |
Annual Sum or Average | 84.31 | 25.97 | 49.94 | 20.41 | 29.53 | 0.00 | 0.00 |
Minimum of Months | 52.65 | 7.69 | 27.71 | 0.06 | 26.90 | 0.00 | 0.00 |
Maximum of Months | 113.88 | 53.21 | 76.91 | 50.01 | 32.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 22.97 | 29.89 | 16.34 | 0.00 | 16.34 | 0.00 | 0.00 |
February | 33.21 | 23.20 | 19.34 | 0.00 | 19.34 | 0.00 | 0.00 |
March | 39.53 | 16.59 | 23.07 | 0.00 | 23.07 | 0.00 | 0.00 |
April | 55.34 | 6.36 | 25.92 | 0.15 | 25.77 | 0.00 | 0.00 |
May | 80.53 | 0.84 | 29.43 | 1.21 | 28.23 | 0.00 | 0.00 |
June | 95.21 | 0.04 | 31.55 | 2.27 | 29.28 | 0.00 | 0.00 |
July | 97.79 | 0.31 | 31.96 | 1.59 | 30.37 | 0.00 | 0.00 |
August | 88.29 | 0.01 | 28.30 | 0.30 | 28.00 | 0.00 | 0.00 |
September | 80.22 | 0.43 | 25.06 | 0.01 | 25.06 | 0.00 | 0.00 |
October | 61.16 | 1.12 | 20.98 | 0.00 | 20.98 | 0.00 | 0.00 |
November | 42.81 | 10.38 | 18.25 | 0.00 | 18.25 | 0.00 | 0.00 |
December | 25.97 | 23.58 | 16.16 | 0.00 | 16.16 | 0.00 | 0.00 |
Annual Sum or Average | 60.38 | 9.34 | 23.89 | 0.46 | 23.42 | 0.00 | 0.00 |
Minimum of Months | 22.97 | 0.01 | 16.16 | 0.00 | 16.16 | 0.00 | 0.00 |
Maximum of Months | 97.79 | 29.89 | 31.96 | 2.27 | 30.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 303.17 | 97.87 | 187.97 | 106.53 | 81.45 | 0.00 | 0.00 |
February | 329.59 | 74.39 | 191.38 | 97.75 | 93.63 | 0.00 | 0.00 |
March | 335.68 | 51.84 | 195.33 | 88.46 | 106.87 | 0.00 | 0.00 |
April | 368.02 | 22.42 | 188.00 | 72.56 | 115.44 | 0.00 | 0.00 |
May | 388.50 | 3.52 | 170.09 | 54.49 | 115.61 | 0.00 | 0.00 |
June | 412.88 | 0.33 | 165.72 | 50.38 | 115.34 | 0.00 | 0.00 |
July | 434.30 | 1.35 | 171.93 | 48.98 | 122.95 | 0.00 | 0.00 |
August | 415.34 | 0.10 | 164.94 | 44.39 | 120.55 | 0.00 | 0.00 |
September | 426.76 | 2.19 | 172.79 | 56.23 | 116.56 | 0.00 | 0.00 |
October | 405.34 | 5.68 | 184.18 | 82.52 | 101.66 | 0.00 | 0.00 |
November | 337.00 | 34.98 | 173.86 | 83.09 | 90.78 | 0.00 | 0.00 |
December | 276.01 | 78.87 | 164.61 | 84.01 | 80.60 | 0.00 | 0.00 |
Annual Sum or Average | 369.52 | 30.95 | 177.48 | 72.31 | 105.17 | 0.00 | 0.00 |
Minimum of Months | 276.01 | 0.10 | 164.61 | 44.39 | 80.60 | 0.00 | 0.00 |
Maximum of Months | 434.30 | 97.87 | 195.33 | 106.53 | 122.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 167.84 | 102.02 | 112.24 | 44.00 | 68.24 | 0.00 | 0.00 |
February | 214.79 | 79.65 | 130.67 | 49.48 | 81.19 | 0.00 | 0.00 |
March | 258.43 | 57.43 | 158.56 | 61.33 | 97.23 | 0.00 | 0.00 |
April | 328.69 | 27.56 | 173.36 | 63.11 | 110.24 | 0.00 | 0.00 |
May | 385.00 | 3.93 | 170.15 | 54.83 | 115.33 | 0.00 | 0.00 |
June | 422.16 | 0.52 | 170.50 | 53.14 | 117.36 | 0.00 | 0.00 |
July | 439.20 | 1.94 | 174.80 | 50.65 | 124.15 | 0.00 | 0.00 |
August | 400.69 | 0.22 | 158.64 | 41.64 | 117.00 | 0.00 | 0.00 |
September | 379.53 | 2.89 | 150.08 | 42.89 | 107.19 | 0.00 | 0.00 |
October | 312.18 | 5.85 | 135.41 | 46.86 | 88.55 | 0.00 | 0.00 |
November | 223.04 | 36.76 | 111.71 | 35.40 | 76.30 | 0.00 | 0.00 |
December | 148.03 | 81.94 | 92.10 | 25.48 | 66.63 | 0.00 | 0.00 |
Annual Sum or Average | 307.04 | 33.19 | 144.90 | 47.37 | 97.53 | 0.00 | 0.00 |
Minimum of Months | 148.03 | 0.22 | 92.10 | 25.48 | 66.63 | 0.00 | 0.00 |
Maximum of Months | 439.20 | 102.02 | 174.80 | 63.11 | 124.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 320.45 | 142.02 | 202.04 | 108.36 | 93.68 | 0.00 | 0.00 |
February | 326.47 | 113.68 | 189.01 | 83.67 | 105.34 | 0.00 | 0.00 |
March | 285.09 | 88.62 | 163.67 | 47.01 | 116.67 | 0.00 | 0.00 |
April | 279.40 | 48.27 | 137.67 | 17.02 | 120.65 | 0.00 | 0.00 |
May | 306.68 | 11.73 | 127.41 | 4.63 | 122.78 | 0.00 | 0.00 |
June | 337.61 | 3.48 | 128.38 | 5.04 | 123.34 | 0.00 | 0.00 |
July | 357.76 | 7.43 | 133.47 | 3.99 | 129.49 | 0.00 | 0.00 |
August | 348.36 | 3.20 | 133.53 | 6.04 | 127.49 | 0.00 | 0.00 |
September | 379.18 | 13.09 | 147.94 | 23.15 | 124.79 | 0.00 | 0.00 |
October | 382.27 | 21.22 | 175.44 | 61.80 | 113.63 | 0.00 | 0.00 |
November | 351.78 | 61.73 | 186.77 | 82.64 | 104.13 | 0.00 | 0.00 |
December | 323.69 | 119.27 | 195.68 | 101.45 | 94.23 | 0.00 | 0.00 |
Annual Sum or Average | 333.24 | 52.54 | 159.96 | 45.23 | 114.72 | 0.00 | 0.00 |
Minimum of Months | 279.40 | 3.20 | 127.41 | 3.99 | 93.68 | 0.00 | 0.00 |
Maximum of Months | 382.27 | 142.02 | 202.04 | 108.36 | 129.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 287.31 | 97.39 | 178.88 | 98.30 | 80.59 | 0.00 | 0.00 |
February | 326.44 | 76.25 | 188.71 | 95.56 | 93.15 | 0.00 | 0.00 |
March | 336.81 | 54.81 | 194.21 | 85.91 | 108.30 | 0.00 | 0.00 |
April | 365.19 | 22.44 | 188.20 | 74.91 | 113.29 | 0.00 | 0.00 |
May | 378.38 | 3.40 | 165.83 | 51.01 | 114.82 | 0.00 | 0.00 |
June | 372.47 | 0.21 | 143.95 | 30.74 | 113.21 | 0.00 | 0.00 |
July | 408.57 | 1.17 | 159.04 | 38.01 | 121.03 | 0.00 | 0.00 |
August | 409.79 | 0.08 | 163.36 | 42.67 | 120.69 | 0.00 | 0.00 |
September | 397.43 | 1.70 | 157.88 | 43.95 | 113.93 | 0.00 | 0.00 |
October | 392.81 | 5.04 | 178.49 | 76.08 | 102.41 | 0.00 | 0.00 |
November | 330.06 | 34.64 | 170.10 | 78.87 | 91.23 | 0.00 | 0.00 |
December | 298.51 | 78.55 | 178.06 | 96.68 | 81.38 | 0.00 | 0.00 |
Annual Sum or Average | 358.83 | 31.12 | 172.17 | 67.61 | 104.56 | 0.00 | 0.00 |
Minimum of Months | 287.31 | 0.08 | 143.95 | 30.74 | 80.59 | 0.00 | 0.00 |
Maximum of Months | 409.79 | 97.39 | 194.21 | 98.30 | 121.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 158.33 | 104.26 | 103.14 | 35.77 | 67.37 | 0.00 | 0.00 |
February | 217.35 | 84.45 | 127.99 | 47.29 | 80.71 | 0.00 | 0.00 |
March | 262.92 | 63.48 | 157.44 | 58.79 | 98.65 | 0.00 | 0.00 |
April | 327.77 | 28.42 | 173.56 | 65.46 | 108.10 | 0.00 | 0.00 |
May | 375.13 | 3.78 | 165.89 | 51.35 | 114.54 | 0.00 | 0.00 |
June | 381.58 | 0.41 | 148.74 | 33.51 | 115.23 | 0.00 | 0.00 |
July | 413.34 | 1.74 | 161.91 | 39.68 | 122.23 | 0.00 | 0.00 |
August | 395.20 | 0.17 | 157.06 | 39.92 | 117.13 | 0.00 | 0.00 |
September | 351.29 | 2.42 | 135.16 | 30.61 | 104.55 | 0.00 | 0.00 |
October | 301.81 | 5.19 | 129.72 | 40.42 | 89.30 | 0.00 | 0.00 |
November | 220.89 | 37.71 | 107.94 | 31.18 | 76.76 | 0.00 | 0.00 |
December | 173.83 | 82.68 | 105.55 | 38.15 | 67.41 | 0.00 | 0.00 |
Annual Sum or Average | 298.71 | 34.34 | 139.58 | 42.67 | 96.92 | 0.00 | 0.00 |
Minimum of Months | 158.33 | 0.17 | 103.14 | 30.61 | 67.37 | 0.00 | 0.00 |
Maximum of Months | 413.34 | 104.26 | 173.56 | 65.46 | 122.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 233.03 | 50.60 | 141.03 | 91.70 | 49.33 | 0.00 | 0.00 |
February | 218.50 | 38.51 | 124.49 | 70.80 | 53.69 | 0.00 | 0.00 |
March | 174.11 | 26.83 | 96.21 | 39.78 | 56.43 | 0.00 | 0.00 |
April | 147.38 | 10.07 | 68.99 | 14.13 | 54.85 | 0.00 | 0.00 |
May | 144.77 | 1.49 | 53.86 | 1.71 | 52.15 | 0.00 | 0.00 |
June | 153.99 | 0.07 | 50.81 | 0.11 | 50.70 | 0.00 | 0.00 |
July | 164.96 | 0.43 | 54.36 | 0.46 | 53.91 | 0.00 | 0.00 |
August | 176.97 | 0.02 | 61.12 | 4.57 | 56.55 | 0.00 | 0.00 |
September | 209.35 | 0.63 | 79.25 | 19.58 | 59.67 | 0.00 | 0.00 |
October | 241.05 | 2.39 | 109.99 | 52.30 | 57.69 | 0.00 | 0.00 |
November | 236.20 | 17.61 | 124.61 | 69.93 | 54.67 | 0.00 | 0.00 |
December | 230.02 | 41.13 | 135.96 | 85.85 | 50.12 | 0.00 | 0.00 |
Annual Sum or Average | 194.08 | 15.72 | 91.57 | 37.43 | 54.14 | 0.00 | 0.00 |
Minimum of Months | 144.77 | 0.02 | 50.81 | 0.11 | 49.33 | 0.00 | 0.00 |
Maximum of Months | 241.05 | 50.60 | 141.03 | 91.70 | 59.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 153.48 | 371.70 | 142.95 | 0.00 | 142.95 | 0.00 | 0.00 |
February | 231.40 | 305.65 | 169.20 | 0.00 | 169.20 | 0.00 | 0.00 |
March | 278.28 | 243.63 | 201.84 | 0.00 | 201.84 | 0.00 | 0.00 |
April | 398.36 | 135.84 | 226.76 | 1.29 | 225.47 | 0.00 | 0.00 |
May | 558.62 | 47.73 | 257.51 | 10.55 | 246.96 | 0.00 | 0.00 |
June | 661.23 | 15.98 | 276.00 | 19.85 | 256.15 | 0.00 | 0.00 |
July | 697.78 | 25.57 | 279.58 | 13.92 | 265.67 | 0.00 | 0.00 |
August | 597.78 | 16.20 | 247.60 | 2.60 | 245.00 | 0.00 | 0.00 |
September | 554.57 | 38.87 | 219.25 | 0.05 | 219.20 | 0.00 | 0.00 |
October | 405.30 | 63.10 | 183.59 | 0.00 | 183.59 | 0.00 | 0.00 |
November | 276.68 | 165.18 | 159.63 | 0.00 | 159.63 | 0.00 | 0.00 |
December | 173.71 | 313.63 | 141.39 | 0.00 | 141.39 | 0.00 | 0.00 |
Annual Sum or Average | 416.49 | 144.55 | 208.97 | 4.04 | 204.93 | 0.00 | 0.00 |
Minimum of Months | 153.48 | 15.98 | 141.39 | 0.00 | 141.39 | 0.00 | 0.00 |
Maximum of Months | 697.78 | 371.70 | 279.58 | 19.85 | 265.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 144.22 | 389.40 | 142.95 | 0.00 | 142.95 | 0.00 | 0.00 |
February | 220.12 | 321.07 | 169.20 | 0.00 | 169.20 | 0.00 | 0.00 |
March | 266.43 | 257.01 | 201.84 | 0.00 | 201.84 | 0.00 | 0.00 |
April | 386.86 | 144.82 | 226.76 | 1.29 | 225.47 | 0.00 | 0.00 |
May | 546.72 | 53.66 | 257.51 | 10.55 | 246.96 | 0.00 | 0.00 |
June | 647.95 | 18.44 | 276.00 | 19.85 | 256.15 | 0.00 | 0.00 |
July | 686.26 | 28.78 | 279.58 | 13.92 | 265.67 | 0.00 | 0.00 |
August | 584.15 | 18.88 | 247.60 | 2.60 | 245.00 | 0.00 | 0.00 |
September | 542.29 | 42.36 | 219.25 | 0.05 | 219.20 | 0.00 | 0.00 |
October | 394.12 | 69.36 | 183.59 | 0.00 | 183.59 | 0.00 | 0.00 |
November | 265.81 | 175.58 | 159.63 | 0.00 | 159.63 | 0.00 | 0.00 |
December | 164.53 | 330.12 | 141.39 | 0.00 | 141.39 | 0.00 | 0.00 |
Annual Sum or Average | 405.01 | 153.39 | 208.97 | 4.04 | 204.93 | 0.00 | 0.00 |
Minimum of Months | 144.22 | 18.44 | 141.39 | 0.00 | 141.39 | 0.00 | 0.00 |
Maximum of Months | 686.26 | 389.40 | 279.58 | 19.85 | 265.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 481.62 | 275.03 | 300.20 | 150.52 | 149.68 | 0.00 | 0.00 |
February | 546.85 | 236.18 | 322.04 | 147.22 | 174.82 | 0.00 | 0.00 |
March | 599.63 | 190.76 | 353.87 | 149.78 | 204.09 | 0.00 | 0.00 |
April | 712.80 | 121.20 | 361.33 | 135.67 | 225.67 | 0.00 | 0.00 |
May | 761.22 | 55.33 | 340.22 | 109.30 | 230.92 | 0.00 | 0.00 |
June | 815.85 | 22.70 | 336.20 | 103.51 | 232.69 | 0.00 | 0.00 |
July | 880.87 | 33.04 | 346.71 | 99.62 | 247.09 | 0.00 | 0.00 |
August | 786.36 | 23.25 | 323.56 | 86.02 | 237.53 | 0.00 | 0.00 |
September | 804.71 | 36.43 | 322.85 | 99.11 | 223.74 | 0.00 | 0.00 |
October | 718.32 | 60.79 | 319.57 | 129.37 | 190.20 | 0.00 | 0.00 |
November | 563.26 | 132.63 | 285.56 | 118.49 | 167.07 | 0.00 | 0.00 |
December | 430.78 | 236.95 | 256.70 | 109.48 | 147.22 | 0.00 | 0.00 |
Annual Sum or Average | 675.71 | 118.17 | 322.36 | 119.68 | 202.68 | 0.00 | 0.00 |
Minimum of Months | 430.78 | 22.70 | 256.70 | 86.02 | 147.22 | 0.00 | 0.00 |
Maximum of Months | 880.87 | 275.03 | 361.33 | 150.52 | 247.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 647.56 | 245.55 | 407.99 | 233.43 | 174.56 | 0.00 | 0.00 |
February | 636.86 | 201.02 | 374.91 | 180.24 | 194.67 | 0.00 | 0.00 |
March | 536.02 | 157.76 | 314.11 | 101.26 | 212.85 | 0.00 | 0.00 |
April | 493.58 | 92.91 | 253.34 | 36.42 | 216.93 | 0.00 | 0.00 |
May | 507.88 | 27.70 | 225.38 | 7.97 | 217.42 | 0.00 | 0.00 |
June | 550.24 | 9.67 | 223.95 | 7.07 | 216.87 | 0.00 | 0.00 |
July | 593.61 | 17.85 | 234.23 | 5.93 | 228.30 | 0.00 | 0.00 |
August | 590.46 | 9.06 | 240.45 | 12.52 | 227.93 | 0.00 | 0.00 |
September | 670.35 | 27.82 | 276.90 | 49.86 | 227.05 | 0.00 | 0.00 |
October | 713.45 | 42.48 | 342.93 | 133.13 | 209.79 | 0.00 | 0.00 |
November | 678.27 | 109.56 | 371.91 | 178.02 | 193.89 | 0.00 | 0.00 |
December | 646.09 | 209.10 | 394.57 | 218.53 | 176.04 | 0.00 | 0.00 |
Annual Sum or Average | 605.18 | 95.40 | 304.74 | 96.67 | 208.07 | 0.00 | 0.00 |
Minimum of Months | 493.58 | 9.06 | 223.95 | 5.93 | 174.56 | 0.00 | 0.00 |
Maximum of Months | 713.45 | 245.55 | 407.99 | 233.43 | 228.30 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.212736E+10 | 0.565407E+09 | 0.130262E+10 | 0.847008E+09 | 0.455609E+09 | 0.00 | 0.00 |
February | 0.178826E+10 | 0.425360E+09 | 0.103864E+10 | 0.590715E+09 | 0.447926E+09 | 0.00 | 0.00 |
March | 0.155992E+10 | 0.378496E+09 | 0.888686E+09 | 0.367421E+09 | 0.521265E+09 | 0.00 | 0.00 |
April | 0.121792E+10 | 0.224973E+09 | 0.616648E+09 | 0.126319E+09 | 0.490329E+09 | 0.00 | 0.00 |
May | 0.109420E+10 | 83206765.77 | 0.497514E+09 | 15792888.41 | 0.481721E+09 | 0.00 | 0.00 |
June | 0.107974E+10 | 25607716.12 | 0.454150E+09 | 945370.99 | 0.453204E+09 | 0.00 | 0.00 |
July | 0.122700E+10 | 50587131.50 | 0.502150E+09 | 4216541.70 | 0.497933E+09 | 0.00 | 0.00 |
August | 0.132313E+10 | 23590505.63 | 0.564515E+09 | 42215893.17 | 0.522299E+09 | 0.00 | 0.00 |
September | 0.162485E+10 | 70169590.95 | 0.708434E+09 | 0.175017E+09 | 0.533417E+09 | 0.00 | 0.00 |
October | 0.203446E+10 | 0.125992E+09 | 0.101597E+10 | 0.483084E+09 | 0.532887E+09 | 0.00 | 0.00 |
November | 0.199849E+10 | 0.262526E+09 | 0.111383E+10 | 0.625115E+09 | 0.488710E+09 | 0.00 | 0.00 |
December | 0.209832E+10 | 0.490467E+09 | 0.125587E+10 | 0.792971E+09 | 0.462900E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.191736E+11 | 0.272638E+10 | 0.995902E+10 | 0.407082E+10 | 0.588820E+10 | 0.00 | 0.00 |
Minimum of Months | 0.107974E+10 | 23590505.63 | 0.454150E+09 | 945370.99 | 0.447926E+09 | 0.00 | 0.00 |
Maximum of Months | 0.212736E+10 | 0.565407E+09 | 0.130262E+10 | 0.847008E+09 | 0.533417E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.590132E+10 | 0.178157E+10 | 0.366808E+10 | 0.238512E+10 | 0.128296E+10 | 0.00 | 0.00 |
February | 0.496015E+10 | 0.134297E+10 | 0.292475E+10 | 0.166341E+10 | 0.126133E+10 | 0.00 | 0.00 |
March | 0.433317E+10 | 0.120224E+10 | 0.250248E+10 | 0.103463E+10 | 0.146785E+10 | 0.00 | 0.00 |
April | 0.340284E+10 | 0.711119E+09 | 0.173644E+10 | 0.355706E+09 | 0.138073E+10 | 0.00 | 0.00 |
May | 0.308384E+10 | 0.274356E+09 | 0.140097E+10 | 44471732.47 | 0.135649E+10 | 0.00 | 0.00 |
June | 0.306682E+10 | 90444362.75 | 0.127886E+10 | 2662102.37 | 0.127619E+10 | 0.00 | 0.00 |
July | 0.349033E+10 | 0.150754E+09 | 0.141402E+10 | 11873503.41 | 0.140215E+10 | 0.00 | 0.00 |
August | 0.373272E+10 | 86203588.86 | 0.158964E+10 | 0.118877E+09 | 0.147076E+10 | 0.00 | 0.00 |
September | 0.457250E+10 | 0.217329E+09 | 0.199490E+10 | 0.492837E+09 | 0.150207E+10 | 0.00 | 0.00 |
October | 0.569672E+10 | 0.391092E+09 | 0.286091E+10 | 0.136033E+10 | 0.150057E+10 | 0.00 | 0.00 |
November | 0.556660E+10 | 0.826466E+09 | 0.313646E+10 | 0.176028E+10 | 0.137618E+10 | 0.00 | 0.00 |
December | 0.583209E+10 | 0.155336E+10 | 0.353645E+10 | 0.223295E+10 | 0.130350E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.536391E+11 | 0.862790E+10 | 0.280439E+11 | 0.114632E+11 | 0.165808E+11 | 0.00 | 0.00 |
Minimum of Months | 0.306682E+10 | 86203588.86 | 0.127886E+10 | 2662102.37 | 0.126133E+10 | 0.00 | 0.00 |
Maximum of Months | 0.590132E+10 | 0.178157E+10 | 0.366808E+10 | 0.238512E+10 | 0.150207E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.789120E+10 | 0.232183E+10 | 0.476505E+10 | 0.309840E+10 | 0.166664E+10 | 0.00 | 0.00 |
February | 0.664841E+10 | 0.173777E+10 | 0.379941E+10 | 0.216087E+10 | 0.163854E+10 | 0.00 | 0.00 |
March | 0.582157E+10 | 0.155405E+10 | 0.325087E+10 | 0.134405E+10 | 0.190682E+10 | 0.00 | 0.00 |
April | 0.458418E+10 | 0.911091E+09 | 0.225574E+10 | 0.462083E+09 | 0.179365E+10 | 0.00 | 0.00 |
May | 0.415159E+10 | 0.345804E+09 | 0.181994E+10 | 57771311.39 | 0.176216E+10 | 0.00 | 0.00 |
June | 0.413476E+10 | 0.113816E+09 | 0.166131E+10 | 3458222.48 | 0.165785E+10 | 0.00 | 0.00 |
July | 0.472109E+10 | 0.188977E+09 | 0.183689E+10 | 15424356.66 | 0.182147E+10 | 0.00 | 0.00 |
August | 0.504677E+10 | 0.104747E+09 | 0.206503E+10 | 0.154428E+09 | 0.191060E+10 | 0.00 | 0.00 |
September | 0.618786E+10 | 0.270990E+09 | 0.259149E+10 | 0.640223E+09 | 0.195127E+10 | 0.00 | 0.00 |
October | 0.766166E+10 | 0.464567E+09 | 0.371648E+10 | 0.176715E+10 | 0.194933E+10 | 0.00 | 0.00 |
November | 0.746188E+10 | 0.104863E+10 | 0.407444E+10 | 0.228671E+10 | 0.178773E+10 | 0.00 | 0.00 |
December | 0.778513E+10 | 0.200957E+10 | 0.459405E+10 | 0.290074E+10 | 0.169332E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.720961E+11 | 0.110718E+11 | 0.364307E+11 | 0.148913E+11 | 0.215394E+11 | 0.00 | 0.00 |
Minimum of Months | 0.413476E+10 | 0.104747E+09 | 0.166131E+10 | 3458222.48 | 0.163854E+10 | 0.00 | 0.00 |
Maximum of Months | 0.789120E+10 | 0.232183E+10 | 0.476505E+10 | 0.309840E+10 | 0.195127E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.775696E+09 | 0.267921E+09 | 0.479115E+09 | 0.263275E+09 | 0.215840E+09 | 0.00 | 0.00 |
February | 0.797012E+09 | 0.189537E+09 | 0.456525E+09 | 0.231188E+09 | 0.225337E+09 | 0.00 | 0.00 |
March | 0.912084E+09 | 0.152113E+09 | 0.520166E+09 | 0.230106E+09 | 0.290060E+09 | 0.00 | 0.00 |
April | 0.955938E+09 | 62112422.10 | 0.487808E+09 | 0.194160E+09 | 0.293648E+09 | 0.00 | 0.00 |
May | 0.101846E+10 | 10256577.92 | 0.444157E+09 | 0.136624E+09 | 0.307533E+09 | 0.00 | 0.00 |
June | 0.968631E+09 | 786107.45 | 0.373119E+09 | 79687335.38 | 0.293432E+09 | 0.00 | 0.00 |
July | 0.109884E+10 | 3798207.26 | 0.425971E+09 | 0.101793E+09 | 0.324177E+09 | 0.00 | 0.00 |
August | 0.110117E+10 | 283142.09 | 0.437540E+09 | 0.114285E+09 | 0.323255E+09 | 0.00 | 0.00 |
September | 0.103442E+10 | 5834704.94 | 0.409224E+09 | 0.113923E+09 | 0.295301E+09 | 0.00 | 0.00 |
October | 0.105556E+10 | 15912934.39 | 0.478060E+09 | 0.203778E+09 | 0.274282E+09 | 0.00 | 0.00 |
November | 0.860131E+09 | 94623824.19 | 0.440888E+09 | 0.204420E+09 | 0.236468E+09 | 0.00 | 0.00 |
December | 0.806448E+09 | 0.216530E+09 | 0.476923E+09 | 0.258957E+09 | 0.217966E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.113844E+11 | 0.101971E+10 | 0.542950E+10 | 0.213220E+10 | 0.329730E+10 | 0.00 | 0.00 |
Minimum of Months | 0.775696E+09 | 283142.09 | 0.373119E+09 | 79687335.38 | 0.215840E+09 | 0.00 | 0.00 |
Maximum of Months | 0.110117E+10 | 0.267921E+09 | 0.520166E+09 | 0.263275E+09 | 0.324177E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.425125E+09 | 0.288791E+09 | 0.276263E+09 | 95806949.54 | 0.180456E+09 | 0.00 | 0.00 |
February | 0.529204E+09 | 0.209568E+09 | 0.309645E+09 | 0.114393E+09 | 0.195252E+09 | 0.00 | 0.00 |
March | 0.711896E+09 | 0.174123E+09 | 0.421690E+09 | 0.157462E+09 | 0.264228E+09 | 0.00 | 0.00 |
April | 0.858069E+09 | 76471910.27 | 0.449856E+09 | 0.169664E+09 | 0.280192E+09 | 0.00 | 0.00 |
May | 0.101034E+10 | 11194371.85 | 0.444322E+09 | 0.137538E+09 | 0.306783E+09 | 0.00 | 0.00 |
June | 0.993076E+09 | 1286954.15 | 0.385530E+09 | 86851183.61 | 0.298679E+09 | 0.00 | 0.00 |
July | 0.111204E+10 | 5111984.82 | 0.433667E+09 | 0.106284E+09 | 0.327382E+09 | 0.00 | 0.00 |
August | 0.106188E+10 | 549751.82 | 0.420666E+09 | 0.106932E+09 | 0.313734E+09 | 0.00 | 0.00 |
September | 0.912989E+09 | 7699759.91 | 0.350341E+09 | 79337988.45 | 0.271003E+09 | 0.00 | 0.00 |
October | 0.808331E+09 | 16765020.74 | 0.347433E+09 | 0.108264E+09 | 0.239169E+09 | 0.00 | 0.00 |
November | 0.572803E+09 | 0.103725E+09 | 0.279776E+09 | 80823817.61 | 0.198952E+09 | 0.00 | 0.00 |
December | 0.467043E+09 | 0.230085E+09 | 0.282718E+09 | 0.102173E+09 | 0.180545E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.946280E+10 | 0.112537E+10 | 0.440191E+10 | 0.134553E+10 | 0.305637E+10 | 0.00 | 0.00 |
Minimum of Months | 0.425125E+09 | 549751.82 | 0.276263E+09 | 79337988.45 | 0.180456E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111204E+10 | 0.288791E+09 | 0.449856E+09 | 0.169664E+09 | 0.327382E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.305023E+09 | 0.142506E+09 | 0.205999E+09 | 0.133948E+09 | 72051538.95 | 0.00 | 0.00 |
February | 0.252097E+09 | 0.110673E+09 | 0.164254E+09 | 93417022.33 | 70836669.59 | 0.00 | 0.00 |
March | 0.211517E+09 | 0.103962E+09 | 0.140540E+09 | 58104762.21 | 82434892.27 | 0.00 | 0.00 |
April | 0.162301E+09 | 70095355.80 | 97519025.54 | 19976389.74 | 77542635.80 | 0.00 | 0.00 |
May | 0.141570E+09 | 39318519.23 | 78678885.71 | 2497523.53 | 76181362.18 | 0.00 | 0.00 |
June | 0.136464E+09 | 19932642.37 | 71821102.60 | 149503.13 | 71671599.46 | 0.00 | 0.00 |
July | 0.165274E+09 | 26705850.62 | 79412001.23 | 666813.56 | 78745187.67 | 0.00 | 0.00 |
August | 0.175723E+09 | 22754557.10 | 89274487.04 | 6676118.00 | 82598369.03 | 0.00 | 0.00 |
September | 0.225887E+09 | 28930512.07 | 0.112034E+09 | 27677617.58 | 84356449.57 | 0.00 | 0.00 |
October | 0.294246E+09 | 47576495.75 | 0.160669E+09 | 76396000.95 | 84272641.20 | 0.00 | 0.00 |
November | 0.287030E+09 | 77635849.50 | 0.176143E+09 | 98857127.90 | 77286280.84 | 0.00 | 0.00 |
December | 0.301735E+09 | 0.128940E+09 | 0.198607E+09 | 0.125402E+09 | 73204554.83 | 0.00 | 0.00 |
Annual Sum or Average | 0.265887E+10 | 0.819030E+09 | 0.157495E+10 | 0.643769E+09 | 0.931182E+09 | 0.00 | 0.00 |
Minimum of Months | 0.136464E+09 | 19932642.37 | 71821102.60 | 149503.13 | 70836669.59 | 0.00 | 0.00 |
Maximum of Months | 0.305023E+09 | 0.142506E+09 | 0.205999E+09 | 0.133948E+09 | 84356449.57 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 61527045.79 | 80065465.54 | 43764347.27 | 0.00 | 43764347.27 | 0.00 | 0.00 |
February | 80341692.94 | 56126762.96 | 46789000.29 | 0.00 | 46789000.29 | 0.00 | 0.00 |
March | 0.105865E+09 | 44432859.33 | 61794968.90 | 1090.50 | 61793878.40 | 0.00 | 0.00 |
April | 0.143450E+09 | 16475092.07 | 67185389.07 | 383579.37 | 66801809.70 | 0.00 | 0.00 |
May | 0.215681E+09 | 2241291.37 | 78836618.86 | 3229660.10 | 75606958.76 | 0.00 | 0.00 |
June | 0.246774E+09 | 114076.63 | 81774442.16 | 5881390.96 | 75893051.20 | 0.00 | 0.00 |
July | 0.261909E+09 | 841306.81 | 85596033.41 | 4260379.21 | 81335654.20 | 0.00 | 0.00 |
August | 0.236483E+09 | 34797.67 | 75803137.35 | 794641.31 | 75008496.04 | 0.00 | 0.00 |
September | 0.207923E+09 | 1103306.15 | 64958573.56 | 15007.28 | 64943566.27 | 0.00 | 0.00 |
October | 0.163806E+09 | 2991329.75 | 56206010.35 | 0.00 | 56206010.35 | 0.00 | 0.00 |
November | 0.110967E+09 | 26915217.24 | 47294919.20 | 0.00 | 47294919.20 | 0.00 | 0.00 |
December | 69566384.65 | 63160663.40 | 43288389.88 | 0.00 | 43288389.88 | 0.00 | 0.00 |
Annual Sum or Average | 0.190429E+10 | 0.294502E+09 | 0.753292E+09 | 14565748.73 | 0.738726E+09 | 0.00 | 0.00 |
Minimum of Months | 61527045.79 | 34797.67 | 43288389.88 | 0.00 | 43288389.88 | 0.00 | 0.00 |
Maximum of Months | 0.261909E+09 | 80065465.54 | 85596033.41 | 5881390.96 | 81335654.20 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.812012E+09 | 0.262140E+09 | 0.503470E+09 | 0.285319E+09 | 0.218151E+09 | 0.00 | 0.00 |
February | 0.797338E+09 | 0.179959E+09 | 0.462997E+09 | 0.236486E+09 | 0.226510E+09 | 0.00 | 0.00 |
March | 0.899077E+09 | 0.138837E+09 | 0.523168E+09 | 0.236921E+09 | 0.286247E+09 | 0.00 | 0.00 |
April | 0.953904E+09 | 58123287.46 | 0.487292E+09 | 0.188083E+09 | 0.299209E+09 | 0.00 | 0.00 |
May | 0.104055E+10 | 9414918.47 | 0.455572E+09 | 0.145933E+09 | 0.309639E+09 | 0.00 | 0.00 |
June | 0.107019E+10 | 858891.46 | 0.429535E+09 | 0.130577E+09 | 0.298959E+09 | 0.00 | 0.00 |
July | 0.116324E+10 | 3627255.87 | 0.460489E+09 | 0.131177E+09 | 0.329312E+09 | 0.00 | 0.00 |
August | 0.111244E+10 | 256267.89 | 0.441767E+09 | 0.118885E+09 | 0.322882E+09 | 0.00 | 0.00 |
September | 0.110616E+10 | 5679114.60 | 0.447880E+09 | 0.145751E+09 | 0.302129E+09 | 0.00 | 0.00 |
October | 0.108566E+10 | 15213741.65 | 0.493303E+09 | 0.221013E+09 | 0.272290E+09 | 0.00 | 0.00 |
November | 0.873502E+09 | 90674749.97 | 0.450657E+09 | 0.215362E+09 | 0.235295E+09 | 0.00 | 0.00 |
December | 0.739271E+09 | 0.211238E+09 | 0.440891E+09 | 0.225018E+09 | 0.215873E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.116533E+11 | 0.976021E+09 | 0.559702E+10 | 0.228053E+10 | 0.331649E+10 | 0.00 | 0.00 |
Minimum of Months | 0.739271E+09 | 256267.89 | 0.429535E+09 | 0.118885E+09 | 0.215873E+09 | 0.00 | 0.00 |
Maximum of Months | 0.116324E+10 | 0.262140E+09 | 0.523168E+09 | 0.285319E+09 | 0.329312E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.449554E+09 | 0.273250E+09 | 0.300618E+09 | 0.117851E+09 | 0.182767E+09 | 0.00 | 0.00 |
February | 0.519619E+09 | 0.192699E+09 | 0.316117E+09 | 0.119692E+09 | 0.196425E+09 | 0.00 | 0.00 |
March | 0.692175E+09 | 0.153833E+09 | 0.424692E+09 | 0.164277E+09 | 0.260415E+09 | 0.00 | 0.00 |
April | 0.851964E+09 | 71428933.37 | 0.449339E+09 | 0.163587E+09 | 0.285752E+09 | 0.00 | 0.00 |
May | 0.103119E+10 | 10517272.02 | 0.455736E+09 | 0.146847E+09 | 0.308890E+09 | 0.00 | 0.00 |
June | 0.109425E+10 | 1353016.57 | 0.441945E+09 | 0.137740E+09 | 0.304205E+09 | 0.00 | 0.00 |
July | 0.117635E+10 | 5204392.33 | 0.468185E+09 | 0.135668E+09 | 0.332517E+09 | 0.00 | 0.00 |
August | 0.107320E+10 | 592029.68 | 0.424893E+09 | 0.111531E+09 | 0.313362E+09 | 0.00 | 0.00 |
September | 0.983753E+09 | 7479980.66 | 0.388997E+09 | 0.111166E+09 | 0.277831E+09 | 0.00 | 0.00 |
October | 0.836134E+09 | 15672530.28 | 0.362676E+09 | 0.125499E+09 | 0.237176E+09 | 0.00 | 0.00 |
November | 0.578126E+09 | 95290339.48 | 0.289545E+09 | 91766114.67 | 0.197779E+09 | 0.00 | 0.00 |
December | 0.396496E+09 | 0.219470E+09 | 0.246686E+09 | 68233865.73 | 0.178452E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.968282E+10 | 0.104679E+10 | 0.456943E+10 | 0.149386E+10 | 0.307557E+10 | 0.00 | 0.00 |
Minimum of Months | 0.396496E+09 | 592029.68 | 0.246686E+09 | 68233865.73 | 0.178452E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117635E+10 | 0.273250E+09 | 0.468185E+09 | 0.164277E+09 | 0.332517E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.858298E+09 | 0.380384E+09 | 0.541151E+09 | 0.290227E+09 | 0.250924E+09 | 0.00 | 0.00 |
February | 0.789806E+09 | 0.275010E+09 | 0.457253E+09 | 0.202409E+09 | 0.254844E+09 | 0.00 | 0.00 |
March | 0.763573E+09 | 0.237357E+09 | 0.438379E+09 | 0.125899E+09 | 0.312480E+09 | 0.00 | 0.00 |
April | 0.724204E+09 | 0.125105E+09 | 0.356843E+09 | 44114242.85 | 0.312728E+09 | 0.00 | 0.00 |
May | 0.821420E+09 | 31405006.70 | 0.341262E+09 | 12407965.71 | 0.328854E+09 | 0.00 | 0.00 |
June | 0.875079E+09 | 9013672.99 | 0.332767E+09 | 13064996.69 | 0.319702E+09 | 0.00 | 0.00 |
July | 0.958235E+09 | 19901360.16 | 0.357493E+09 | 10674209.51 | 0.346819E+09 | 0.00 | 0.00 |
August | 0.933058E+09 | 8580801.07 | 0.357648E+09 | 16186750.68 | 0.341461E+09 | 0.00 | 0.00 |
September | 0.982840E+09 | 33936391.51 | 0.383469E+09 | 60002211.20 | 0.323467E+09 | 0.00 | 0.00 |
October | 0.102387E+10 | 56844686.07 | 0.469885E+09 | 0.165529E+09 | 0.304356E+09 | 0.00 | 0.00 |
November | 0.911811E+09 | 0.160002E+09 | 0.484110E+09 | 0.214196E+09 | 0.269915E+09 | 0.00 | 0.00 |
December | 0.866968E+09 | 0.319458E+09 | 0.524103E+09 | 0.271712E+09 | 0.252391E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105092E+11 | 0.165700E+10 | 0.504436E+10 | 0.142642E+10 | 0.361794E+10 | 0.00 | 0.00 |
Minimum of Months | 0.724204E+09 | 8580801.07 | 0.332767E+09 | 10674209.51 | 0.250924E+09 | 0.00 | 0.00 |
Maximum of Months | 0.102387E+10 | 0.380384E+09 | 0.541151E+09 | 0.290227E+09 | 0.346819E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.769528E+09 | 0.260846E+09 | 0.479115E+09 | 0.263275E+09 | 0.215840E+09 | 0.00 | 0.00 |
February | 0.789735E+09 | 0.184461E+09 | 0.456525E+09 | 0.231188E+09 | 0.225337E+09 | 0.00 | 0.00 |
March | 0.902121E+09 | 0.146801E+09 | 0.520166E+09 | 0.230106E+09 | 0.290060E+09 | 0.00 | 0.00 |
April | 0.946564E+09 | 58176560.32 | 0.487808E+09 | 0.194160E+09 | 0.293648E+09 | 0.00 | 0.00 |
May | 0.101346E+10 | 9117619.48 | 0.444157E+09 | 0.136624E+09 | 0.307533E+09 | 0.00 | 0.00 |
June | 0.965443E+09 | 544513.75 | 0.373119E+09 | 79687335.38 | 0.293432E+09 | 0.00 | 0.00 |
July | 0.109431E+10 | 3136900.26 | 0.425971E+09 | 0.101793E+09 | 0.324177E+09 | 0.00 | 0.00 |
August | 0.109757E+10 | 205983.85 | 0.437540E+09 | 0.114285E+09 | 0.323255E+09 | 0.00 | 0.00 |
September | 0.103015E+10 | 4401451.91 | 0.409224E+09 | 0.113923E+09 | 0.295301E+09 | 0.00 | 0.00 |
October | 0.105209E+10 | 13501837.04 | 0.478060E+09 | 0.203778E+09 | 0.274282E+09 | 0.00 | 0.00 |
November | 0.855528E+09 | 89775390.12 | 0.440888E+09 | 0.204420E+09 | 0.236468E+09 | 0.00 | 0.00 |
December | 0.799533E+09 | 0.210385E+09 | 0.476923E+09 | 0.258957E+09 | 0.217966E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.113160E+11 | 0.981354E+09 | 0.542950E+10 | 0.213220E+10 | 0.329730E+10 | 0.00 | 0.00 |
Minimum of Months | 0.769528E+09 | 205983.85 | 0.373119E+09 | 79687335.38 | 0.215840E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109757E+10 | 0.260846E+09 | 0.520166E+09 | 0.263275E+09 | 0.324177E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.424065E+09 | 0.279262E+09 | 0.276263E+09 | 95806949.54 | 0.180456E+09 | 0.00 | 0.00 |
February | 0.525809E+09 | 0.204309E+09 | 0.309645E+09 | 0.114393E+09 | 0.195252E+09 | 0.00 | 0.00 |
March | 0.704198E+09 | 0.170029E+09 | 0.421690E+09 | 0.157462E+09 | 0.264228E+09 | 0.00 | 0.00 |
April | 0.849583E+09 | 73659596.47 | 0.449856E+09 | 0.169664E+09 | 0.280192E+09 | 0.00 | 0.00 |
May | 0.100474E+10 | 10127548.93 | 0.444322E+09 | 0.137538E+09 | 0.306783E+09 | 0.00 | 0.00 |
June | 0.989043E+09 | 1066006.99 | 0.385530E+09 | 86851183.61 | 0.298679E+09 | 0.00 | 0.00 |
July | 0.110708E+10 | 4668057.15 | 0.433667E+09 | 0.106284E+09 | 0.327382E+09 | 0.00 | 0.00 |
August | 0.105850E+10 | 450805.96 | 0.420666E+09 | 0.106932E+09 | 0.313734E+09 | 0.00 | 0.00 |
September | 0.910534E+09 | 6268625.97 | 0.350341E+09 | 79337988.45 | 0.271003E+09 | 0.00 | 0.00 |
October | 0.808364E+09 | 13893040.12 | 0.347433E+09 | 0.108264E+09 | 0.239169E+09 | 0.00 | 0.00 |
November | 0.572558E+09 | 97738770.82 | 0.279776E+09 | 80823817.61 | 0.198952E+09 | 0.00 | 0.00 |
December | 0.465576E+09 | 0.221455E+09 | 0.282718E+09 | 0.102173E+09 | 0.180545E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.942006E+10 | 0.108293E+10 | 0.440191E+10 | 0.134553E+10 | 0.305637E+10 | 0.00 | 0.00 |
Minimum of Months | 0.424065E+09 | 450805.96 | 0.276263E+09 | 79337988.45 | 0.180456E+09 | 0.00 | 0.00 |
Maximum of Months | 0.110708E+10 | 0.279262E+09 | 0.449856E+09 | 0.169664E+09 | 0.327382E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.624155E+09 | 0.135532E+09 | 0.377722E+09 | 0.245608E+09 | 0.132114E+09 | 0.00 | 0.00 |
February | 0.528596E+09 | 93162556.88 | 0.301177E+09 | 0.171290E+09 | 0.129887E+09 | 0.00 | 0.00 |
March | 0.466343E+09 | 71855066.51 | 0.257695E+09 | 0.106541E+09 | 0.151153E+09 | 0.00 | 0.00 |
April | 0.382003E+09 | 26089937.85 | 0.178812E+09 | 36628898.92 | 0.142183E+09 | 0.00 | 0.00 |
May | 0.387756E+09 | 3999836.76 | 0.144266E+09 | 4579482.99 | 0.139687E+09 | 0.00 | 0.00 |
June | 0.399135E+09 | 175501.64 | 0.131692E+09 | 274130.37 | 0.131418E+09 | 0.00 | 0.00 |
July | 0.441824E+09 | 1164607.08 | 0.145611E+09 | 1222675.71 | 0.144388E+09 | 0.00 | 0.00 |
August | 0.473985E+09 | 46581.27 | 0.163695E+09 | 12241393.70 | 0.151453E+09 | 0.00 | 0.00 |
September | 0.542639E+09 | 1644825.04 | 0.205427E+09 | 50749943.80 | 0.154677E+09 | 0.00 | 0.00 |
October | 0.645641E+09 | 6404345.59 | 0.294604E+09 | 0.140080E+09 | 0.154523E+09 | 0.00 | 0.00 |
November | 0.612230E+09 | 45642822.40 | 0.322978E+09 | 0.181265E+09 | 0.141713E+09 | 0.00 | 0.00 |
December | 0.616075E+09 | 0.110158E+09 | 0.364167E+09 | 0.229939E+09 | 0.134229E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.612038E+10 | 0.495876E+09 | 0.288785E+10 | 0.118042E+10 | 0.170742E+10 | 0.00 | 0.00 |
Minimum of Months | 0.382003E+09 | 46581.27 | 0.131692E+09 | 274130.37 | 0.129887E+09 | 0.00 | 0.00 |
Maximum of Months | 0.645641E+09 | 0.135532E+09 | 0.377722E+09 | 0.245608E+09 | 0.154677E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.411086E+09 | 0.995556E+09 | 0.382873E+09 | 0.00 | 0.382873E+09 | 0.00 | 0.00 |
February | 0.559795E+09 | 0.739434E+09 | 0.409334E+09 | 0.00 | 0.409334E+09 | 0.00 | 0.00 |
March | 0.745333E+09 | 0.652542E+09 | 0.540614E+09 | 9540.24 | 0.540604E+09 | 0.00 | 0.00 |
April | 0.103256E+10 | 0.352099E+09 | 0.587772E+09 | 3355747.53 | 0.584416E+09 | 0.00 | 0.00 |
May | 0.149620E+10 | 0.127847E+09 | 0.689703E+09 | 28254710.30 | 0.661448E+09 | 0.00 | 0.00 |
June | 0.171391E+10 | 41411858.37 | 0.715404E+09 | 51453401.44 | 0.663951E+09 | 0.00 | 0.00 |
July | 0.186892E+10 | 68486076.01 | 0.748838E+09 | 37271965.62 | 0.711566E+09 | 0.00 | 0.00 |
August | 0.160111E+10 | 43394934.91 | 0.663164E+09 | 6951926.59 | 0.656212E+09 | 0.00 | 0.00 |
September | 0.143745E+10 | 0.100740E+09 | 0.568291E+09 | 131291.34 | 0.568159E+09 | 0.00 | 0.00 |
October | 0.108555E+10 | 0.168999E+09 | 0.491719E+09 | 0.00 | 0.491719E+09 | 0.00 | 0.00 |
November | 0.717151E+09 | 0.428138E+09 | 0.413760E+09 | 0.00 | 0.413760E+09 | 0.00 | 0.00 |
December | 0.465267E+09 | 0.840030E+09 | 0.378709E+09 | 0.00 | 0.378709E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.131343E+11 | 0.455868E+10 | 0.659018E+10 | 0.127429E+09 | 0.646275E+10 | 0.00 | 0.00 |
Minimum of Months | 0.411086E+09 | 41411858.37 | 0.378709E+09 | 0.00 | 0.378709E+09 | 0.00 | 0.00 |
Maximum of Months | 0.186892E+10 | 0.995556E+09 | 0.748838E+09 | 51453401.44 | 0.711566E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.386285E+09 | 0.104296E+10 | 0.382873E+09 | 0.00 | 0.382873E+09 | 0.00 | 0.00 |
February | 0.532522E+09 | 0.776728E+09 | 0.409334E+09 | 0.00 | 0.409334E+09 | 0.00 | 0.00 |
March | 0.713616E+09 | 0.688369E+09 | 0.540614E+09 | 9540.24 | 0.540604E+09 | 0.00 | 0.00 |
April | 0.100274E+10 | 0.375370E+09 | 0.587772E+09 | 3355747.53 | 0.584416E+09 | 0.00 | 0.00 |
May | 0.146433E+10 | 0.143721E+09 | 0.689703E+09 | 28254710.30 | 0.661448E+09 | 0.00 | 0.00 |
June | 0.167949E+10 | 47797530.17 | 0.715404E+09 | 51453401.44 | 0.663951E+09 | 0.00 | 0.00 |
July | 0.183808E+10 | 77075224.78 | 0.748838E+09 | 37271965.62 | 0.711566E+09 | 0.00 | 0.00 |
August | 0.156460E+10 | 50573767.72 | 0.663164E+09 | 6951926.59 | 0.656212E+09 | 0.00 | 0.00 |
September | 0.140561E+10 | 0.109788E+09 | 0.568291E+09 | 131291.34 | 0.568159E+09 | 0.00 | 0.00 |
October | 0.105560E+10 | 0.185777E+09 | 0.491719E+09 | 0.00 | 0.491719E+09 | 0.00 | 0.00 |
November | 0.688971E+09 | 0.455095E+09 | 0.413760E+09 | 0.00 | 0.413760E+09 | 0.00 | 0.00 |
December | 0.440681E+09 | 0.884181E+09 | 0.378709E+09 | 0.00 | 0.378709E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127725E+11 | 0.483744E+10 | 0.659018E+10 | 0.127429E+09 | 0.646275E+10 | 0.00 | 0.00 |
Minimum of Months | 0.386285E+09 | 47797530.17 | 0.378709E+09 | 0.00 | 0.378709E+09 | 0.00 | 0.00 |
Maximum of Months | 0.183808E+10 | 0.104296E+10 | 0.748838E+09 | 51453401.44 | 0.711566E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.128997E+10 | 0.736648E+09 | 0.804053E+09 | 0.403152E+09 | 0.400901E+09 | 0.00 | 0.00 |
February | 0.132293E+10 | 0.571378E+09 | 0.779077E+09 | 0.356161E+09 | 0.422916E+09 | 0.00 | 0.00 |
March | 0.160604E+10 | 0.510923E+09 | 0.947811E+09 | 0.401176E+09 | 0.546635E+09 | 0.00 | 0.00 |
April | 0.184757E+10 | 0.314154E+09 | 0.936579E+09 | 0.351647E+09 | 0.584932E+09 | 0.00 | 0.00 |
May | 0.203885E+10 | 0.148191E+09 | 0.911258E+09 | 0.292759E+09 | 0.618499E+09 | 0.00 | 0.00 |
June | 0.211467E+10 | 58825839.66 | 0.871432E+09 | 0.268298E+09 | 0.603134E+09 | 0.00 | 0.00 |
July | 0.235933E+10 | 88506060.18 | 0.928622E+09 | 0.266827E+09 | 0.661795E+09 | 0.00 | 0.00 |
August | 0.210619E+10 | 62271486.25 | 0.866614E+09 | 0.230401E+09 | 0.636213E+09 | 0.00 | 0.00 |
September | 0.208581E+10 | 94424981.62 | 0.836833E+09 | 0.256901E+09 | 0.579931E+09 | 0.00 | 0.00 |
October | 0.192394E+10 | 0.162824E+09 | 0.855937E+09 | 0.346495E+09 | 0.509443E+09 | 0.00 | 0.00 |
November | 0.145997E+10 | 0.343778E+09 | 0.740169E+09 | 0.307115E+09 | 0.433054E+09 | 0.00 | 0.00 |
December | 0.115381E+10 | 0.634639E+09 | 0.687549E+09 | 0.293242E+09 | 0.394307E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.213091E+11 | 0.372656E+10 | 0.101659E+11 | 0.377417E+10 | 0.639176E+10 | 0.00 | 0.00 |
Minimum of Months | 0.115381E+10 | 58825839.66 | 0.687549E+09 | 0.230401E+09 | 0.394307E+09 | 0.00 | 0.00 |
Maximum of Months | 0.235933E+10 | 0.736648E+09 | 0.947811E+09 | 0.403152E+09 | 0.661795E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.173443E+10 | 0.657669E+09 | 0.109276E+10 | 0.625208E+09 | 0.467554E+09 | 0.00 | 0.00 |
February | 0.154069E+10 | 0.486320E+09 | 0.906983E+09 | 0.436029E+09 | 0.470954E+09 | 0.00 | 0.00 |
March | 0.143567E+10 | 0.422540E+09 | 0.841299E+09 | 0.271210E+09 | 0.570089E+09 | 0.00 | 0.00 |
April | 0.127937E+10 | 0.240822E+09 | 0.656664E+09 | 94391165.67 | 0.562273E+09 | 0.00 | 0.00 |
May | 0.136032E+10 | 74193017.40 | 0.603669E+09 | 21343087.24 | 0.582326E+09 | 0.00 | 0.00 |
June | 0.142622E+10 | 25071867.09 | 0.580471E+09 | 18336140.00 | 0.562135E+09 | 0.00 | 0.00 |
July | 0.158992E+10 | 47819130.71 | 0.627363E+09 | 15889288.65 | 0.611473E+09 | 0.00 | 0.00 |
August | 0.158148E+10 | 24275885.46 | 0.644027E+09 | 33544252.27 | 0.610483E+09 | 0.00 | 0.00 |
September | 0.173756E+10 | 72104472.12 | 0.717736E+09 | 0.129232E+09 | 0.588504E+09 | 0.00 | 0.00 |
October | 0.191091E+10 | 0.113777E+09 | 0.918491E+09 | 0.356582E+09 | 0.561909E+09 | 0.00 | 0.00 |
November | 0.175809E+10 | 0.283979E+09 | 0.963996E+09 | 0.461421E+09 | 0.502575E+09 | 0.00 | 0.00 |
December | 0.173048E+10 | 0.560042E+09 | 0.105683E+10 | 0.585322E+09 | 0.471508E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.190851E+11 | 0.300861E+10 | 0.961029E+10 | 0.304851E+10 | 0.656178E+10 | 0.00 | 0.00 |
Minimum of Months | 0.127937E+10 | 24275885.46 | 0.580471E+09 | 15889288.65 | 0.467554E+09 | 0.00 | 0.00 |
Maximum of Months | 0.191091E+10 | 0.657669E+09 | 0.109276E+10 | 0.625208E+09 | 0.611473E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770479E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161998422.5 | 81.21 | 0.00 | 0.00 |
February | 0.696226E+10 | -0.681597E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146283812.6 | 81.21 | 0.00 | 0.00 |
March | 0.770335E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161889138.0 | 81.21 | 0.00 | 0.00 |
April | 0.746514E+10 | -0.730858E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156561804.3 | 81.21 | 0.00 | 0.00 |
May | 0.770447E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161694646.4 | 81.21 | 0.00 | 0.00 |
June | 0.745693E+10 | -0.730052E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156406856.1 | 81.21 | 0.00 | 0.00 |
July | 0.771246E+10 | -0.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161619747.6 | 81.21 | 0.00 | 0.00 |
August | 0.770444E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161643043.5 | 81.21 | 0.00 | 0.00 |
September | 0.746635E+10 | -0.730992E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156422437.9 | 81.21 | 0.00 | 0.00 |
October | 0.770313E+10 | -0.754143E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161700036.1 | 81.21 | 0.00 | 0.00 |
November | 0.744904E+10 | -0.729242E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156612203.9 | 81.21 | 0.00 | 0.00 |
December | 0.771282E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161960838.4 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907452E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190479E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696226E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161998422.5 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771282E+10 | -0.681597E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146283812.6 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYSLAUNDRY HPWH TANK
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.188898E+11 | -0.943518E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -739161996.5 | 81.68 | 0.00 | 0.00 |
February | 0.155579E+11 | -0.847101E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -657535155.1 | 81.68 | 0.00 | 0.00 |
March | 0.143609E+11 | -0.920250E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -722995934.1 | 81.68 | 0.00 | 0.00 |
April | 0.904932E+10 | -0.865701E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -680460058.6 | 81.68 | 0.00 | 0.00 |
May | 0.377379E+10 | -0.868177E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -685772223.1 | 81.68 | 0.00 | 0.00 |
June | 0.162255E+09 | -0.821612E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -654260815.7 | 81.70 | 0.00 | 0.00 |
July | -230649119.7 | -0.846850E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -673723592.5 | 81.81 | 0.00 | 0.00 |
August | -131639575.9 | -0.848558E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -674122801.7 | 81.74 | 0.00 | 0.00 |
September | 0.148612E+10 | -0.835613E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -655298603.0 | 81.69 | 0.00 | 0.00 |
October | 0.526103E+10 | -0.888927E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -685801786.3 | 81.68 | 0.00 | 0.00 |
November | 0.104906E+11 | -0.885792E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -684085211.7 | 81.68 | 0.00 | 0.00 |
December | 0.164303E+11 | -0.935320E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -732957125.6 | 81.68 | 0.00 | 0.00 |
Annual Sum or Average | 0.950997E+11 | -0.105074E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.824618E+10 | 81.70 | 0.00 | 0.00 |
Minimum of Months | -230649119.7 | -0.943518E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -739161996.5 | 81.68 | 0.00 | 0.00 |
Maximum of Months | 0.188898E+11 | -0.821612E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -654260815.7 | 81.81 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 HPWH TANK
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | -0.202327E+10 | -0.514916E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.110885E+10 | 59.44 | 0.00 | 0.00 |
February | -0.180999E+10 | -0.460766E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -977386671.8 | 59.44 | 0.00 | 0.00 |
March | -0.186497E+10 | -0.495250E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.107075E+10 | 59.46 | 0.00 | 0.00 |
April | -0.173447E+10 | -0.457479E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -990496284.5 | 59.48 | 0.00 | 0.00 |
May | -0.161742E+10 | -0.449760E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -982557177.2 | 59.50 | 0.00 | 0.00 |
June | -0.146872E+10 | -0.418348E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -928442618.0 | 59.52 | 0.00 | 0.00 |
July | -0.148797E+10 | -0.424475E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -950691132.6 | 59.53 | 0.00 | 0.00 |
August | -0.150360E+10 | -0.429818E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -953440577.4 | 59.52 | 0.00 | 0.00 |
September | -0.155527E+10 | -0.430984E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -930806499.3 | 59.50 | 0.00 | 0.00 |
October | -0.176987E+10 | -0.467527E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -981851071.6 | 59.48 | 0.00 | 0.00 |
November | -0.179765E+10 | -0.474668E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -998895436.4 | 59.47 | 0.00 | 0.00 |
December | -0.200074E+10 | -0.507798E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.109420E+10 | 59.45 | 0.00 | 0.00 |
Annual Sum or Average | -0.206339E+11 | -0.553179E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.119684E+11 | 59.48 | 0.00 | 0.00 |
Minimum of Months | -0.202327E+10 | -0.514916E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.110885E+10 | 59.44 | 0.00 | 0.00 |
Maximum of Months | -0.146872E+10 | -0.418348E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -928442618.0 | 59.53 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.87 | 0.86 | 01-JAN-07:40 | 4962.50 | 35.22 | 267.17 | 292.67 | 600.38 | 25.05 | 186.83 | 262.33 |
February | 304.33 | 0.87 | 0.86 | 01-FEB-07:00 | 1503.80 | 24.47 | 113.67 | 279.67 | 435.77 | 20.99 | 125.67 | 229.50 |
March | 362.67 | 0.87 | 0.86 | 01-MAR-09:09 | 923.43 | 19.00 | 0.00 | 325.17 | 361.58 | 20.77 | 137.83 | 249.33 |
April | 357.50 | 0.87 | 0.86 | 01-APR-08:39 | 749.31 | 18.84 | 0.00 | 326.33 | 303.36 | 20.56 | 102.33 | 226.50 |
May | 389.00 | 0.88 | 0.86 | 01-MAY-07:49 | 651.52 | 18.07 | 0.00 | 341.67 | 261.16 | 19.81 | 56.00 | 203.17 |
June | 388.17 | 0.88 | 0.86 | 01-JUN-07:00 | 613.21 | 17.36 | 0.00 | 317.33 | 242.97 | 19.13 | 38.67 | 181.33 |
July | 403.83 | 0.88 | 0.86 | 01-JUL-07:30 | 689.75 | 18.16 | 0.00 | 350.50 | 276.47 | 19.92 | 78.00 | 240.00 |
August | 348.33 | 0.87 | 0.86 | 01-AUG-07:00 | 818.86 | 18.55 | 0.00 | 340.83 | 322.55 | 20.27 | 129.33 | 253.83 |
September | 349.67 | 0.87 | 0.86 | 01-SEP-07:40 | 1003.11 | 18.70 | 0.00 | 315.17 | 383.32 | 20.44 | 166.50 | 244.00 |
October | 323.50 | 0.87 | 0.86 | 02-OCT-11:39 | 1289.24 | 20.92 | 40.33 | 315.67 | 463.54 | 21.34 | 191.00 | 262.33 |
November | 314.83 | 0.87 | 0.86 | 01-NOV-07:10 | 2983.85 | 30.70 | 237.17 | 291.67 | 525.70 | 23.54 | 201.83 | 258.50 |
December | 282.67 | 0.87 | 0.86 | 01-DEC-08:39 | 5098.42 | 35.99 | 278.67 | 279.83 | 620.60 | 24.63 | 185.67 | 252.33 |
Annual Sum or Average | 4111.50 | 0.87 | 1626.73 | 22.35 | 937.00 | 3776.50 | 386.56 | 21.19 | 1599.67 | 2863.17 | ||
Minimum of Months | 282.67 | 0.87 | 0.86 | 613.21 | 17.36 | 0.00 | 279.67 | 242.97 | 19.13 | 38.67 | 181.33 | |
Maximum of Months | 403.83 | 0.88 | 0.86 | 5098.42 | 35.99 | 278.67 | 350.50 | 620.60 | 25.05 | 201.83 | 262.33 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.25 | 0.22 | 01-JAN-07:40 | 5252.16 | 35.26 | 267.50 | 297.83 | 888.21 | 25.00 | 187.17 | 285.00 |
February | 304.33 | 0.25 | 0.22 | 01-FEB-07:49 | 1735.71 | 24.66 | 114.83 | 286.67 | 667.00 | 21.32 | 145.50 | 263.67 |
March | 362.67 | 0.26 | 0.22 | 01-MAR-07:49 | 1101.27 | 19.68 | 2.67 | 339.67 | 538.33 | 21.24 | 185.50 | 301.50 |
April | 357.50 | 0.26 | 0.22 | 01-APR-07:19 | 884.01 | 19.67 | 0.17 | 339.67 | 437.62 | 21.16 | 192.83 | 304.50 |
May | 389.00 | 0.27 | 0.22 | 01-MAY-06:00 | 757.09 | 19.04 | 0.00 | 361.50 | 366.33 | 20.53 | 157.00 | 311.33 |
June | 388.17 | 0.30 | 0.22 | 01-JUN-06:00 | 710.69 | 18.38 | 0.00 | 338.83 | 340.07 | 19.90 | 129.83 | 285.67 |
July | 403.83 | 0.27 | 0.22 | 01-JUL-06:00 | 797.79 | 19.14 | 0.00 | 368.33 | 384.10 | 20.65 | 203.33 | 316.67 |
August | 348.33 | 0.27 | 0.22 | 01-AUG-07:10 | 945.04 | 19.44 | 0.00 | 354.83 | 448.25 | 20.94 | 208.67 | 313.33 |
September | 349.67 | 0.26 | 0.22 | 01-SEP-06:00 | 1159.39 | 19.52 | 10.00 | 326.17 | 538.97 | 21.04 | 211.00 | 290.83 |
October | 323.50 | 0.26 | 0.22 | 02-OCT-07:30 | 1505.81 | 21.42 | 42.33 | 322.67 | 679.21 | 21.73 | 215.67 | 299.33 |
November | 314.83 | 0.25 | 0.22 | 01-NOV-06:00 | 3224.64 | 30.78 | 238.33 | 300.00 | 765.12 | 23.76 | 220.00 | 280.17 |
December | 282.67 | 0.24 | 0.22 | 01-DEC-08:39 | 5390.00 | 36.05 | 278.67 | 287.33 | 909.78 | 24.69 | 190.00 | 268.83 |
Annual Sum or Average | 4111.50 | 0.26 | 1800.83 | 22.98 | 954.50 | 3923.50 | 559.79 | 21.68 | 2246.50 | 3520.83 | ||
Minimum of Months | 282.67 | 0.24 | 0.22 | 710.69 | 18.38 | 0.00 | 286.67 | 340.07 | 19.90 | 129.83 | 263.67 | |
Maximum of Months | 403.83 | 0.30 | 0.22 | 5390.00 | 36.05 | 278.67 | 368.33 | 909.78 | 25.00 | 220.00 | 316.67 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.68 | 0.60 | 01-JAN-10:30 | 299.83 | 13.92 | 0.00 | 236.83 | 149.58 | 17.38 | 0.00 | 46.50 |
February | 304.33 | 0.66 | 0.60 | 01-FEB-09:39 | 349.68 | 14.88 | 0.00 | 245.83 | 167.36 | 18.20 | 0.00 | 81.83 |
March | 362.67 | 0.64 | 0.60 | 01-MAR-13:20 | 423.49 | 15.87 | 0.00 | 312.17 | 197.55 | 19.10 | 0.00 | 174.33 |
April | 357.50 | 0.63 | 0.60 | 01-APR-07:30 | 514.70 | 16.76 | 0.00 | 338.67 | 236.63 | 19.94 | 3.33 | 234.17 |
May | 389.00 | 0.62 | 0.60 | 01-MAY-06:49 | 631.84 | 17.39 | 12.17 | 370.50 | 272.03 | 20.53 | 49.00 | 303.83 |
June | 388.17 | 0.63 | 0.60 | 01-JUN-06:10 | 690.49 | 19.17 | 58.83 | 361.67 | 291.80 | 21.21 | 80.33 | 295.00 |
July | 403.83 | 0.62 | 0.60 | 01-JUL-06:30 | 719.52 | 17.18 | 1.33 | 378.00 | 306.40 | 21.09 | 85.00 | 326.00 |
August | 348.33 | 0.63 | 0.60 | 01-AUG-07:10 | 638.75 | 16.93 | 0.00 | 355.50 | 281.04 | 20.10 | 19.67 | 300.67 |
September | 349.67 | 0.63 | 0.60 | 01-SEP-07:10 | 530.97 | 16.21 | 0.00 | 319.17 | 235.73 | 19.37 | 0.17 | 233.17 |
October | 323.50 | 0.65 | 0.60 | 02-OCT-11:39 | 405.91 | 15.53 | 0.00 | 298.83 | 194.80 | 18.80 | 0.00 | 165.83 |
November | 314.83 | 0.66 | 0.60 | 01-NOV-08:20 | 362.21 | 14.85 | 0.00 | 256.00 | 169.61 | 18.17 | 0.00 | 92.50 |
December | 282.67 | 0.66 | 0.60 | 01-DEC-09:20 | 338.00 | 14.61 | 0.00 | 248.00 | 163.60 | 18.02 | 0.00 | 51.83 |
Annual Sum or Average | 4111.50 | 0.64 | 506.75 | 16.25 | 72.33 | 3721.17 | 227.63 | 19.45 | 237.50 | 2305.67 | ||
Minimum of Months | 282.67 | 0.62 | 0.60 | 299.83 | 13.92 | 0.00 | 236.83 | 149.58 | 17.38 | 0.00 | 46.50 | |
Maximum of Months | 403.83 | 0.68 | 0.60 | 719.52 | 19.17 | 58.83 | 378.00 | 306.40 | 21.21 | 85.00 | 326.00 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.68 | 0.60 | 01-JAN-10:30 | 299.83 | 13.92 | 0.00 | 236.83 | 149.58 | 17.38 | 0.00 | 46.50 |
February | 304.33 | 0.66 | 0.60 | 01-FEB-09:39 | 349.68 | 14.88 | 0.00 | 245.83 | 167.36 | 18.20 | 0.00 | 81.83 |
March | 362.67 | 0.64 | 0.60 | 01-MAR-13:20 | 423.49 | 15.87 | 0.00 | 312.17 | 197.55 | 19.10 | 0.00 | 174.33 |
April | 357.50 | 0.63 | 0.60 | 01-APR-07:30 | 514.70 | 16.76 | 0.00 | 338.67 | 236.63 | 19.94 | 3.33 | 234.17 |
May | 389.00 | 0.62 | 0.60 | 01-MAY-06:49 | 631.84 | 17.39 | 12.17 | 370.50 | 272.03 | 20.53 | 49.00 | 303.83 |
June | 388.17 | 0.63 | 0.60 | 01-JUN-06:10 | 690.49 | 19.17 | 58.83 | 361.67 | 291.80 | 21.21 | 80.33 | 295.00 |
July | 403.83 | 0.62 | 0.60 | 01-JUL-06:30 | 719.52 | 17.18 | 1.33 | 378.00 | 306.40 | 21.09 | 85.17 | 326.00 |
August | 348.33 | 0.63 | 0.60 | 01-AUG-07:10 | 638.75 | 16.93 | 0.00 | 355.50 | 281.04 | 20.10 | 19.67 | 300.67 |
September | 349.67 | 0.63 | 0.60 | 01-SEP-07:10 | 530.97 | 16.21 | 0.00 | 319.17 | 235.73 | 19.37 | 0.17 | 233.17 |
October | 323.50 | 0.65 | 0.60 | 02-OCT-11:39 | 405.91 | 15.53 | 0.00 | 298.83 | 194.80 | 18.80 | 0.00 | 165.83 |
November | 314.83 | 0.66 | 0.60 | 01-NOV-08:20 | 362.21 | 14.85 | 0.00 | 256.00 | 169.61 | 18.17 | 0.00 | 92.50 |
December | 282.67 | 0.66 | 0.60 | 01-DEC-09:20 | 338.00 | 14.61 | 0.00 | 248.00 | 163.60 | 18.02 | 0.00 | 51.83 |
Annual Sum or Average | 4111.50 | 0.64 | 506.75 | 16.25 | 72.33 | 3721.17 | 227.63 | 19.45 | 237.67 | 2305.67 | ||
Minimum of Months | 282.67 | 0.62 | 0.60 | 299.83 | 13.92 | 0.00 | 236.83 | 149.58 | 17.38 | 0.00 | 46.50 | |
Maximum of Months | 403.83 | 0.68 | 0.60 | 719.52 | 19.17 | 58.83 | 378.00 | 306.40 | 21.21 | 85.17 | 326.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 18027780.84 | 3880.53 | 09-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16960957.91 | 3432.56 | 03-FEB-19:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14038831.87 | 2681.16 | 15-MAR-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6195802.23 | 4170.85 | 26-NOV-23:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23295581.39 | 4666.75 | 20-DEC-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78518954.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23295581.39 | 4666.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 788541.51 | 184.83 | 26-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10491126.61 | 624.95 | 04-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6952382.67 | 346.31 | 21-MAR-07:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 681763.48 | 108.89 | 13-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 423494.66 | 136.08 | 16-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19337308.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10491126.61 | 624.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.186265E+09 | 1653.41 | 23-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150015E+09 | 1909.78 | 04-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147798E+09 | 1494.69 | 20-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101136E+09 | 1303.82 | 15-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 76945624.86 | 1413.84 | 29-MAY-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 47304379.85 | 1415.73 | 25-JUN-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 57095247.66 | 1375.20 | 04-JUL-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 66021199.33 | 1389.13 | 26-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 52425477.01 | 1215.30 | 16-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 79410911.82 | 1261.30 | 07-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105002E+09 | 1574.32 | 13-NOV-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.198065E+09 | 1731.74 | 16-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 47304379.85 | 1215.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.198065E+09 | 1909.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1082758.37 | 481.95 | 26-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9746149.26 | 887.66 | 04-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 10828907.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9746149.26 | 887.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2273.22 | 0.18 | 04-JAN-09:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3608.50 | 0.18 | 09-FEB-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3873.19 | 0.18 | 05-MAR-02:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2931.56 | 0.18 | 16-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2796.75 | 0.18 | 16-MAY-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3617.96 | 0.18 | 06-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2965.03 | 0.18 | 20-JUL-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3038.12 | 0.18 | 11-AUG-21:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3008.06 | 0.18 | 16-SEP-22:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3191.21 | 0.18 | 14-OCT-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3522.96 | 4.58 | 14-NOV-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3789.39 | 0.18 | 16-DEC-19:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38615.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2273.22 | 0.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3873.19 | 4.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 15500318.77 | 3784.62 | 11-JAN-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 38380592.21 | 3740.79 | 12-FEB-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10105752.16 | 3357.89 | 19-MAR-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2768775.84 | 3839.09 | 20-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1862718.55 | 2720.56 | 08-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 930981.61 | 2426.97 | 19-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 101252.30 | 919.88 | 03-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 889623.31 | 1944.30 | 13-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 623721.93 | 1623.45 | 15-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1048285.56 | 2818.47 | 18-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6728934.76 | 3427.62 | 30-NOV-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19756668.74 | 2855.78 | 19-DEC-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98697625.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 101252.30 | 919.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38380592.21 | 3839.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 38063239.91 | 3440.99 | 24-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 58356574.43 | 3482.35 | 23-FEB-09:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14515485.84 | 3145.95 | 17-MAR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1468729.62 | 1795.36 | 25-APR-08:36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1339438.10 | 2667.61 | 28-MAY-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 611505.43 | 1506.60 | 19-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 257026.76 | 1778.39 | 06-JUL-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1038725.77 | 2323.74 | 28-AUG-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1373212.87 | 2425.36 | 07-SEP-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3042044.87 | 3622.65 | 18-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10076911.68 | 3979.59 | 12-NOV-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 48465561.21 | 4178.08 | 28-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178608E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 257026.76 | 1506.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 58356574.43 | 4178.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 53178108.12 | 31562.14 | 25-JAN-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 42967095.65 | 18376.61 | 04-FEB-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 30732596.06 | 27322.13 | 16-MAR-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5495779.71 | 10791.87 | 19-APR-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3761451.03 | 11129.39 | 28-MAY-06:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1942835.63 | 13869.04 | 25-JUN-06:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1254106.83 | 12527.75 | 06-AUG-21:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1728568.10 | 7230.21 | 27-SEP-08:28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6514424.55 | 16408.13 | 15-OCT-06:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15991211.76 | 15348.45 | 13-NOV-16:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 51778724.39 | 24891.55 | 27-DEC-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 53178108.12 | 31562.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 17079933.20 | 2795.33 | 21-JAN-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 35955319.13 | 3136.60 | 05-FEB-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8681789.75 | 3554.55 | 16-MAR-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 113076.16 | 606.62 | 29-APR-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 50762.97 | 592.23 | 26-MAY-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 172936.78 | 1044.72 | 12-AUG-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 97150.38 | 574.46 | 31-OCT-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2883546.40 | 973.42 | 24-NOV-09:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24664568.11 | 3446.11 | 19-DEC-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89699082.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35955319.13 | 3554.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 45369189.35 | 3928.45 | 24-JAN-16:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 53590950.42 | 4182.55 | 03-FEB-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11343187.49 | 2298.30 | 21-MAR-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 252304.48 | 1020.97 | 19-APR-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 328588.70 | 1200.80 | 27-MAY-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 158512.75 | 1088.61 | 15-JUN-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 141779.93 | 807.40 | 03-AUG-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 67051.27 | 870.76 | 27-SEP-18:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 564183.53 | 1432.15 | 10-OCT-06:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5289498.22 | 2111.03 | 16-NOV-22:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 60615889.62 | 3756.03 | 13-DEC-16:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177721E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 60615889.62 | 4182.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 22482730.20 | 892.33 | 24-JAN-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23553666.55 | 1004.15 | 04-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14128260.14 | 1579.29 | 16-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 789633.36 | 824.23 | 20-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 838887.72 | 854.29 | 08-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 588975.47 | 848.26 | 19-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 207886.24 | 618.17 | 03-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 598353.01 | 900.30 | 10-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 437799.32 | 819.71 | 15-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 811396.35 | 852.58 | 18-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7559038.85 | 1114.66 | 12-NOV-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 25411230.59 | 991.16 | 28-DEC-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97407857.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 207886.24 | 618.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25411230.59 | 1579.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 42463331.20 | 1568.94 | 25-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 34267310.66 | 1590.74 | 04-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16839773.55 | 1587.09 | 16-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 568663.37 | 747.76 | 20-APR-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 479481.16 | 655.14 | 28-MAY-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 445741.54 | 747.00 | 19-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 137500.38 | 531.36 | 18-JUL-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 594152.63 | 838.37 | 10-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 654189.01 | 862.65 | 15-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1342001.50 | 889.45 | 18-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10397538.63 | 1186.19 | 13-NOV-09:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 47415881.04 | 1566.49 | 27-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155606E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 137500.38 | 531.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 47415881.04 | 1590.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 5689172.42 | 3664.55 | 14-JAN-16:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 27473320.99 | 2278.02 | 12-FEB-16:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12413649.14 | 4065.69 | 21-MAR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2808602.23 | 2283.28 | 13-APR-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1775003.06 | 2190.65 | 26-MAY-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1074760.65 | 1343.23 | 22-JUN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 757925.26 | 694.36 | 04-JUL-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1399710.43 | 2458.18 | 28-AUG-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1424529.34 | 2355.86 | 14-SEP-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1168460.27 | 2219.98 | 12-OCT-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2631760.64 | 2773.63 | 12-NOV-16:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4241730.69 | 3441.97 | 28-DEC-16:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62858625.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 757925.26 | 694.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27473320.99 | 4065.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.418924E+11 | 0.328789E+11 | 58091.10 | 18-JAN-07:05 | 45525.04 | 0.00 |
February | 0.00 | 0.00 | 0.376097E+11 | 0.302531E+11 | 59216.56 | 01-FEB-06:08 | 47713.78 | 0.00 |
March | 0.00 | 0.00 | 0.404297E+11 | 0.300455E+11 | 60292.02 | 01-MAR-07:30 | 44841.71 | 0.00 |
April | 0.00 | 0.00 | 0.375466E+11 | 0.272709E+11 | 62541.59 | 01-APR-17:06 | 45020.04 | 0.00 |
May | 0.00 | 0.00 | 0.371035E+11 | 0.222447E+11 | 65270.26 | 01-MAY-05:15 | 39116.53 | 0.00 |
June | 0.00 | 0.00 | 0.345934E+11 | 0.182164E+11 | 66681.58 | 01-JUN-07:03 | 34998.23 | 0.00 |
July | 0.00 | 0.00 | 0.350748E+11 | 0.188589E+11 | 66623.57 | 01-JUL-05:08 | 35840.74 | 0.00 |
August | 0.00 | 0.00 | 0.355570E+11 | 0.186578E+11 | 66916.04 | 31-AUG-05:08 | 35183.16 | 0.00 |
September | 0.00 | 0.00 | 0.357631E+11 | 0.187601E+11 | 67009.49 | 30-SEP-05:08 | 35074.56 | 0.00 |
October | 0.00 | 0.00 | 0.388550E+11 | 0.220808E+11 | 66174.36 | 31-OCT-05:30 | 37610.73 | 0.00 |
November | 0.00 | 0.00 | 0.391882E+11 | 0.246543E+11 | 63356.17 | 30-NOV-06:08 | 39778.28 | 0.00 |
December | 0.00 | 0.00 | 0.415412E+11 | 0.282775E+11 | 59770.14 | 31-DEC-06:07 | 40552.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.455155E+12 | 0.292199E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.345934E+11 | 0.182164E+11 | 58091.10 | 34998.23 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.418924E+11 | 0.328789E+11 | 67009.49 | 47713.78 | 0.00 |
Report: CoilReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.581299E+11 | 0.456330E+11 | 73521.09 | 18-JAN-23:20 | 57602.25 | 0.00 |
February | 0.00 | 0.00 | 0.534455E+11 | 0.429976E+11 | 74946.18 | 01-FEB-17:10 | 60283.54 | 0.00 |
March | 0.00 | 0.00 | 0.600883E+11 | 0.446671E+11 | 76307.98 | 01-MAR-17:10 | 56682.86 | 0.00 |
April | 0.00 | 0.00 | 0.602515E+11 | 0.437671E+11 | 79156.46 | 01-APR-20:40 | 57163.03 | 0.00 |
May | 0.00 | 0.00 | 0.649529E+11 | 0.389379E+11 | 82611.60 | 01-MAY-19:30 | 49457.93 | 0.00 |
June | 0.00 | 0.00 | 0.643011E+11 | 0.338576E+11 | 84398.66 | 01-JUN-16:40 | 44200.31 | 0.00 |
July | 0.00 | 0.00 | 0.665251E+11 | 0.357643E+11 | 84325.21 | 01-JUL-16:10 | 45214.99 | 0.00 |
August | 0.00 | 0.00 | 0.666775E+11 | 0.349827E+11 | 84695.55 | 31-AUG-16:10 | 44474.25 | 0.00 |
September | 0.00 | 0.00 | 0.645630E+11 | 0.338596E+11 | 84813.88 | 30-SEP-18:00 | 44402.66 | 0.00 |
October | 0.00 | 0.00 | 0.658294E+11 | 0.374037E+11 | 83756.41 | 31-OCT-16:20 | 47396.89 | 0.00 |
November | 0.00 | 0.00 | 0.610903E+11 | 0.384362E+11 | 80187.92 | 30-NOV-17:10 | 50286.12 | 0.00 |
December | 0.00 | 0.00 | 0.596971E+11 | 0.406477E+11 | 75647.15 | 31-DEC-18:25 | 51339.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.745552E+12 | 0.470954E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.534455E+11 | 0.338576E+11 | 73521.09 | 44200.31 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.666775E+11 | 0.456330E+11 | 84813.88 | 60283.54 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.353754E+12 | 0.229125E+12 | 473989.75 | 06-JAN-23:00 | 195736.55 | 0.82 |
February | 0.00 | 0.00 | 0.389474E+12 | 0.258860E+12 | 460870.60 | 10-FEB-21:40 | 199330.59 | 0.84 |
March | 0.00 | 0.00 | 0.500675E+12 | 0.313695E+12 | 481065.78 | 09-MAR-21:10 | 200168.71 | 0.86 |
April | 0.00 | 0.00 | 0.596922E+12 | 0.383159E+12 | 410568.17 | 12-APR-22:00 | 213019.77 | 1.00 |
May | 0.00 | 0.00 | 0.806314E+12 | 0.459113E+12 | 493133.81 | 24-MAY-18:50 | 192749.27 | 1.00 |
June | 0.00 | 0.00 | 0.892463E+12 | 0.474746E+12 | 484509.27 | 05-JUN-21:00 | 240085.65 | 1.00 |
July | 0.00 | 0.00 | 0.949067E+12 | 0.502938E+12 | 486029.55 | 27-JUL-19:20 | 251813.12 | 1.00 |
August | 0.00 | 0.00 | 0.950082E+12 | 0.496105E+12 | 515843.28 | 06-AUG-21:00 | 192828.23 | 1.00 |
September | 0.00 | 0.00 | 0.901923E+12 | 0.477934E+12 | 591225.09 | 25-SEP-21:00 | 213187.03 | 1.00 |
October | 0.00 | 0.00 | 0.842285E+12 | 0.466845E+12 | 509794.34 | 01-OCT-20:00 | 186927.58 | 1.00 |
November | 0.00 | 0.00 | 0.654036E+12 | 0.366809E+12 | 521365.77 | 21-NOV-21:20 | 207246.89 | 0.94 |
December | 0.00 | 0.00 | 0.465812E+12 | 0.268251E+12 | 515038.08 | 25-DEC-22:00 | 179064.71 | 0.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.830281E+13 | 0.469758E+13 | 0.95 | |||
Minimum of Months | 0.00 | 0.00 | 0.353754E+12 | 0.229125E+12 | 410568.17 | 179064.71 | 0.82 | |
Maximum of Months | 0.00 | 0.00 | 0.950082E+12 | 0.502938E+12 | 591225.09 | 251813.12 | 1.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.302241E+11 | 0.179787E+11 | 43680.71 | 07-JAN-09:02 | 18209.91 | 0.60 |
February | 0.00 | 0.00 | 0.328775E+11 | 0.206174E+11 | 41144.18 | 11-FEB-19:02 | 17304.67 | 0.66 |
March | 0.00 | 0.00 | 0.396807E+11 | 0.252752E+11 | 44822.51 | 14-MAR-08:62 | 18156.44 | 0.66 |
April | 0.00 | 0.00 | 0.465830E+11 | 0.302868E+11 | 42394.34 | 16-APR-08:62 | 18337.37 | 0.79 |
May | 0.00 | 0.00 | 0.562843E+11 | 0.335876E+11 | 48516.27 | 28-MAY-18:05 | 17368.44 | 0.79 |
June | 0.00 | 0.00 | 0.604233E+11 | 0.336285E+11 | 43517.00 | 18-JUN-20:50 | 17585.39 | 0.79 |
July | 0.00 | 0.00 | 0.630075E+11 | 0.349588E+11 | 46717.94 | 02-JUL-17:00 | 16452.97 | 0.79 |
August | 0.00 | 0.00 | 0.637900E+11 | 0.349145E+11 | 45950.57 | 12-AUG-08:07 | 16296.74 | 0.79 |
September | 0.00 | 0.00 | 0.600955E+11 | 0.334625E+11 | 44272.90 | 04-SEP-21:51 | 16433.31 | 0.79 |
October | 0.00 | 0.00 | 0.578633E+11 | 0.335546E+11 | 45192.41 | 01-OCT-08:20 | 16390.70 | 0.79 |
November | 0.00 | 0.00 | 0.488820E+11 | 0.279205E+11 | 47072.13 | 08-NOV-09:03 | 17156.18 | 0.73 |
December | 0.00 | 0.00 | 0.380129E+11 | 0.213610E+11 | 49467.94 | 23-DEC-19:03 | 17101.15 | 0.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.597724E+12 | 0.347546E+12 | 0.74 | |||
Minimum of Months | 0.00 | 0.00 | 0.302241E+11 | 0.179787E+11 | 41144.18 | 16296.74 | 0.60 | |
Maximum of Months | 0.00 | 0.00 | 0.637900E+11 | 0.349588E+11 | 49467.94 | 18337.37 | 0.79 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.517064E+10 | 0.281574E+10 | 15446.47 | 07-JAN-09:02 | 8669.42 | 0.83 |
February | 0.00 | 0.00 | 0.581146E+10 | 0.337414E+10 | 14995.44 | 02-FEB-09:02 | 8947.31 | 0.86 |
March | 0.00 | 0.00 | 0.731782E+10 | 0.442821E+10 | 15324.33 | 19-MAR-08:62 | 8256.84 | 0.86 |
April | 0.00 | 0.00 | 0.882649E+10 | 0.560871E+10 | 14153.47 | 29-APR-08:62 | 9378.28 | 0.95 |
May | 0.00 | 0.00 | 0.995639E+10 | 0.648341E+10 | 14100.64 | 24-MAY-18:02 | 9353.59 | 0.96 |
June | 0.00 | 0.00 | 0.101219E+11 | 0.669793E+10 | 13244.39 | 13-JUN-08:61 | 10249.23 | 0.96 |
July | 0.00 | 0.00 | 0.113328E+11 | 0.778782E+10 | 12769.95 | 14-JUL-18:02 | 10103.07 | 0.96 |
August | 0.00 | 0.00 | 0.107602E+11 | 0.725385E+10 | 14850.67 | 12-AUG-08:62 | 8838.27 | 0.96 |
September | 0.00 | 0.00 | 0.105904E+11 | 0.713963E+10 | 13348.27 | 05-SEP-08:62 | 9965.75 | 0.96 |
October | 0.00 | 0.00 | 0.102334E+11 | 0.676276E+10 | 14346.51 | 31-OCT-08:62 | 9396.47 | 0.96 |
November | 0.00 | 0.00 | 0.775763E+10 | 0.469822E+10 | 14465.53 | 24-NOV-09:02 | 8904.17 | 0.92 |
December | 0.00 | 0.00 | 0.600109E+10 | 0.341092E+10 | 15520.52 | 23-DEC-09:02 | 8599.68 | 0.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.103880E+12 | 0.664614E+11 | 0.92 | |||
Minimum of Months | 0.00 | 0.00 | 0.517064E+10 | 0.281574E+10 | 12769.95 | 8256.84 | 0.83 | |
Maximum of Months | 0.00 | 0.00 | 0.113328E+11 | 0.778782E+10 | 15520.52 | 10249.23 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.235847E+10 | 0.106241E+10 | 16094.01 | 07-JAN-09:52 | 8615.76 | 0.50 |
February | 0.00 | 0.00 | 0.323888E+10 | 0.171332E+10 | 15655.36 | 18-FEB-09:51 | 9260.79 | 0.55 |
March | 0.00 | 0.00 | 0.488580E+10 | 0.283521E+10 | 16928.15 | 14-MAR-08:21 | 8449.41 | 0.60 |
April | 0.00 | 0.00 | 0.716208E+10 | 0.457811E+10 | 16075.01 | 22-APR-08:21 | 9676.84 | 0.73 |
May | 0.00 | 0.00 | 0.967099E+10 | 0.634840E+10 | 15833.50 | 24-MAY-20:51 | 9754.13 | 0.90 |
June | 0.00 | 0.00 | 0.101809E+11 | 0.679492E+10 | 16085.39 | 18-JUN-21:51 | 9239.23 | 0.94 |
July | 0.00 | 0.00 | 0.112547E+11 | 0.777868E+10 | 15490.66 | 02-JUL-21:51 | 10215.72 | 0.94 |
August | 0.00 | 0.00 | 0.104612E+11 | 0.698623E+10 | 15590.36 | 12-AUG-08:52 | 8595.04 | 0.94 |
September | 0.00 | 0.00 | 0.970626E+10 | 0.635346E+10 | 16031.91 | 16-SEP-07:52 | 9779.28 | 0.92 |
October | 0.00 | 0.00 | 0.865531E+10 | 0.539941E+10 | 15888.55 | 21-OCT-08:61 | 10434.28 | 0.89 |
November | 0.00 | 0.00 | 0.565120E+10 | 0.315553E+10 | 15864.89 | 22-NOV-08:51 | 9662.86 | 0.75 |
December | 0.00 | 0.00 | 0.328035E+10 | 0.170475E+10 | 16099.44 | 10-DEC-09:01 | 10047.49 | 0.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.865062E+11 | 0.547104E+11 | 0.77 | |||
Minimum of Months | 0.00 | 0.00 | 0.235847E+10 | 0.106241E+10 | 15490.66 | 8449.41 | 0.50 | |
Maximum of Months | 0.00 | 0.00 | 0.112547E+11 | 0.777868E+10 | 16928.15 | 10434.28 | 0.94 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.419547E+11 | 0.279730E+11 | 47193.07 | 02-JAN-14:30 | 40506.32 | 0.91 |
February | 0.00 | 0.00 | 0.369577E+11 | 0.235214E+11 | 40416.41 | 11-FEB-14:30 | 31975.80 | 0.96 |
March | 0.00 | 0.00 | 0.367904E+11 | 0.217518E+11 | 34507.77 | 04-MAR-11:35 | 29575.76 | 0.91 |
April | 0.00 | 0.00 | 0.374885E+11 | 0.208121E+11 | 28772.82 | 15-APR-15:02 | 22119.38 | 0.99 |
May | 0.00 | 0.00 | 0.409827E+11 | 0.220929E+11 | 27903.47 | 14-MAY-08:00 | 18709.91 | 0.99 |
June | 0.00 | 0.00 | 0.438517E+11 | 0.247817E+11 | 27662.03 | 03-JUN-08:00 | 18589.09 | 1.00 |
July | 0.00 | 0.00 | 0.487700E+11 | 0.293595E+11 | 30279.52 | 29-JUL-16:10 | 24837.91 | 1.00 |
August | 0.00 | 0.00 | 0.483575E+11 | 0.292270E+11 | 30580.53 | 20-AUG-08:00 | 23165.15 | 1.00 |
September | 0.00 | 0.00 | 0.546629E+11 | 0.370691E+11 | 38684.32 | 30-SEP-13:40 | 30095.97 | 1.00 |
October | 0.00 | 0.00 | 0.589190E+11 | 0.404459E+11 | 43410.19 | 25-OCT-14:00 | 36578.42 | 1.00 |
November | 0.00 | 0.00 | 0.503939E+11 | 0.340112E+11 | 47107.58 | 07-NOV-13:30 | 40919.93 | 0.98 |
December | 0.00 | 0.00 | 0.440074E+11 | 0.290583E+11 | 47990.86 | 03-DEC-13:40 | 42488.46 | 0.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.543136E+12 | 0.340104E+12 | 0.97 | |||
Minimum of Months | 0.00 | 0.00 | 0.367904E+11 | 0.208121E+11 | 27662.03 | 18589.09 | 0.91 | |
Maximum of Months | 0.00 | 0.00 | 0.589190E+11 | 0.404459E+11 | 47990.86 | 42488.46 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.261361E+11 | 0.153833E+11 | 102028.12 | 07-JAN-09:52 | 54680.24 | 0.46 |
February | 0.00 | 0.00 | 0.287639E+11 | 0.179596E+11 | 98815.58 | 17-FEB-09:21 | 58207.22 | 0.49 |
March | 0.00 | 0.00 | 0.386105E+11 | 0.244078E+11 | 108661.24 | 14-MAR-08:21 | 50041.18 | 0.55 |
April | 0.00 | 0.00 | 0.496003E+11 | 0.326347E+11 | 100364.35 | 22-APR-08:21 | 59802.34 | 0.66 |
May | 0.00 | 0.00 | 0.674707E+11 | 0.461713E+11 | 101583.08 | 25-MAY-21:51 | 57913.94 | 0.84 |
June | 0.00 | 0.00 | 0.726291E+11 | 0.512669E+11 | 102359.93 | 18-JUN-21:51 | 57049.15 | 0.88 |
July | 0.00 | 0.00 | 0.764791E+11 | 0.544531E+11 | 96076.66 | 02-JUL-21:51 | 64022.93 | 0.89 |
August | 0.00 | 0.00 | 0.710390E+11 | 0.490307E+11 | 98514.79 | 12-AUG-08:52 | 53739.59 | 0.87 |
September | 0.00 | 0.00 | 0.669566E+11 | 0.461701E+11 | 102387.77 | 16-SEP-07:52 | 59571.52 | 0.85 |
October | 0.00 | 0.00 | 0.599565E+11 | 0.385517E+11 | 98196.55 | 31-OCT-08:31 | 55014.94 | 0.81 |
November | 0.00 | 0.00 | 0.445742E+11 | 0.276967E+11 | 100465.52 | 22-NOV-08:51 | 59488.79 | 0.68 |
December | 0.00 | 0.00 | 0.302148E+11 | 0.178288E+11 | 101922.39 | 10-DEC-09:01 | 61318.07 | 0.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.632431E+12 | 0.421555E+12 | 0.71 | |||
Minimum of Months | 0.00 | 0.00 | 0.261361E+11 | 0.153833E+11 | 96076.66 | 50041.18 | 0.46 | |
Maximum of Months | 0.00 | 0.00 | 0.764791E+11 | 0.544531E+11 | 108661.24 | 64022.93 | 0.89 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.544126E+10 | 0.309928E+10 | 13524.38 | 07-JAN-09:02 | 7970.08 | 0.84 |
February | 0.00 | 0.00 | 0.584844E+10 | 0.342412E+10 | 13188.42 | 18-FEB-09:02 | 8187.73 | 0.89 |
March | 0.00 | 0.00 | 0.722284E+10 | 0.434218E+10 | 13722.31 | 19-MAR-08:62 | 7411.99 | 0.90 |
April | 0.00 | 0.00 | 0.878044E+10 | 0.560834E+10 | 12583.16 | 29-APR-08:62 | 8467.11 | 0.97 |
May | 0.00 | 0.00 | 0.999034E+10 | 0.660374E+10 | 12879.17 | 24-MAY-18:02 | 8239.08 | 0.97 |
June | 0.00 | 0.00 | 0.106890E+11 | 0.739434E+10 | 10951.63 | 05-JUN-08:62 | 9862.99 | 0.98 |
July | 0.00 | 0.00 | 0.116867E+11 | 0.836412E+10 | 11275.16 | 02-JUL-18:02 | 9121.68 | 0.98 |
August | 0.00 | 0.00 | 0.107819E+11 | 0.746938E+10 | 13288.97 | 12-AUG-08:62 | 7936.69 | 0.97 |
September | 0.00 | 0.00 | 0.109893E+11 | 0.778475E+10 | 11771.58 | 05-SEP-08:62 | 9043.26 | 0.97 |
October | 0.00 | 0.00 | 0.103902E+11 | 0.708136E+10 | 12806.75 | 31-OCT-08:62 | 8453.48 | 0.97 |
November | 0.00 | 0.00 | 0.783136E+10 | 0.485920E+10 | 12960.09 | 24-NOV-09:02 | 7985.56 | 0.94 |
December | 0.00 | 0.00 | 0.562259E+10 | 0.315710E+10 | 13901.71 | 23-DEC-09:02 | 7716.59 | 0.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.105274E+12 | 0.691879E+11 | 0.94 | |||
Minimum of Months | 0.00 | 0.00 | 0.544126E+10 | 0.309928E+10 | 10951.63 | 7411.99 | 0.84 | |
Maximum of Months | 0.00 | 0.00 | 0.116867E+11 | 0.836412E+10 | 13901.71 | 9862.99 | 0.98 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.261697E+10 | 0.131920E+10 | 14563.11 | 07-JAN-09:52 | 7902.12 | 0.51 |
February | 0.00 | 0.00 | 0.322529E+10 | 0.171911E+10 | 14465.26 | 17-FEB-09:21 | 9128.08 | 0.57 |
March | 0.00 | 0.00 | 0.483215E+10 | 0.279512E+10 | 15221.63 | 04-MAR-08:51 | 9733.40 | 0.64 |
April | 0.00 | 0.00 | 0.706980E+10 | 0.449327E+10 | 14957.45 | 22-APR-08:21 | 9661.52 | 0.74 |
May | 0.00 | 0.00 | 0.968242E+10 | 0.644365E+10 | 14719.74 | 07-MAY-08:11 | 10171.63 | 0.92 |
June | 0.00 | 0.00 | 0.107341E+11 | 0.749409E+10 | 14628.12 | 13-JUN-07:51 | 10227.78 | 0.96 |
July | 0.00 | 0.00 | 0.115986E+11 | 0.835038E+10 | 13997.47 | 02-JUL-21:51 | 9251.49 | 0.95 |
August | 0.00 | 0.00 | 0.104779E+11 | 0.714710E+10 | 14349.53 | 29-AUG-07:52 | 9382.16 | 0.95 |
September | 0.00 | 0.00 | 0.100986E+11 | 0.689164E+10 | 14570.84 | 16-SEP-07:52 | 9133.12 | 0.93 |
October | 0.00 | 0.00 | 0.878510E+10 | 0.556471E+10 | 14750.05 | 21-OCT-08:61 | 10094.75 | 0.90 |
November | 0.00 | 0.00 | 0.564963E+10 | 0.327485E+10 | 15072.62 | 22-NOV-08:51 | 9986.94 | 0.76 |
December | 0.00 | 0.00 | 0.299804E+10 | 0.156669E+10 | 14789.73 | 07-DEC-08:52 | 9667.23 | 0.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.877686E+11 | 0.570598E+11 | 0.78 | |||
Minimum of Months | 0.00 | 0.00 | 0.261697E+10 | 0.131920E+10 | 13997.47 | 7902.12 | 0.51 | |
Maximum of Months | 0.00 | 0.00 | 0.115986E+11 | 0.835038E+10 | 15221.63 | 10227.78 | 0.96 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.115915E+10 | 0.611865E+09 | 4307.53 | 07-JAN-09:02 | 2135.69 | 0.76 |
February | 0.00 | 0.00 | 0.138587E+10 | 0.781230E+09 | 4151.66 | 02-FEB-09:02 | 2233.68 | 0.84 |
March | 0.00 | 0.00 | 0.179359E+10 | 0.105744E+10 | 4210.28 | 19-MAR-08:62 | 2029.49 | 0.83 |
April | 0.00 | 0.00 | 0.222745E+10 | 0.139196E+10 | 3939.15 | 29-APR-08:62 | 2344.12 | 0.94 |
May | 0.00 | 0.00 | 0.256110E+10 | 0.164927E+10 | 3869.10 | 24-MAY-18:02 | 2371.85 | 0.96 |
June | 0.00 | 0.00 | 0.261355E+10 | 0.170647E+10 | 3679.27 | 13-JUN-08:61 | 2588.92 | 0.96 |
July | 0.00 | 0.00 | 0.293952E+10 | 0.200185E+10 | 3423.88 | 04-JUL-08:62 | 2791.45 | 0.97 |
August | 0.00 | 0.00 | 0.276621E+10 | 0.184095E+10 | 4156.95 | 12-AUG-08:62 | 2178.11 | 0.96 |
September | 0.00 | 0.00 | 0.269863E+10 | 0.179232E+10 | 3744.29 | 05-SEP-08:62 | 2490.95 | 0.96 |
October | 0.00 | 0.00 | 0.255258E+10 | 0.164708E+10 | 4020.96 | 31-OCT-08:62 | 2328.46 | 0.96 |
November | 0.00 | 0.00 | 0.187186E+10 | 0.110280E+10 | 4023.98 | 24-NOV-09:02 | 2160.77 | 0.90 |
December | 0.00 | 0.00 | 0.139087E+10 | 0.771162E+09 | 4352.38 | 23-DEC-09:02 | 2100.97 | 0.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.259604E+11 | 0.163544E+11 | 0.90 | |||
Minimum of Months | 0.00 | 0.00 | 0.115915E+10 | 0.611865E+09 | 3423.88 | 2029.49 | 0.76 | |
Maximum of Months | 0.00 | 0.00 | 0.293952E+10 | 0.200185E+10 | 4352.38 | 2791.45 | 0.97 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.492648E+09 | 0.215364E+09 | 4394.07 | 07-JAN-09:52 | 2135.54 | 0.41 |
February | 0.00 | 0.00 | 0.769752E+09 | 0.400385E+09 | 4288.40 | 17-FEB-09:21 | 2352.05 | 0.51 |
March | 0.00 | 0.00 | 0.121435E+10 | 0.692216E+09 | 4661.37 | 14-MAR-08:21 | 2058.18 | 0.58 |
April | 0.00 | 0.00 | 0.184511E+10 | 0.116608E+10 | 4370.24 | 22-APR-08:21 | 2433.26 | 0.73 |
May | 0.00 | 0.00 | 0.250088E+10 | 0.163253E+10 | 4361.17 | 24-MAY-20:51 | 2457.13 | 0.90 |
June | 0.00 | 0.00 | 0.263364E+10 | 0.173671E+10 | 4416.07 | 18-JUN-21:51 | 2326.86 | 0.94 |
July | 0.00 | 0.00 | 0.292773E+10 | 0.201030E+10 | 4228.33 | 02-JUL-21:51 | 2634.61 | 0.94 |
August | 0.00 | 0.00 | 0.269262E+10 | 0.177518E+10 | 4274.82 | 12-AUG-08:52 | 2111.77 | 0.94 |
September | 0.00 | 0.00 | 0.248038E+10 | 0.159978E+10 | 4432.40 | 16-SEP-07:52 | 2379.39 | 0.92 |
October | 0.00 | 0.00 | 0.215596E+10 | 0.130230E+10 | 4312.44 | 21-OCT-08:61 | 2579.82 | 0.89 |
November | 0.00 | 0.00 | 0.136004E+10 | 0.728700E+09 | 4348.32 | 10-NOV-08:51 | 2464.40 | 0.72 |
December | 0.00 | 0.00 | 0.753992E+09 | 0.383436E+09 | 4422.11 | 10-DEC-09:01 | 2448.86 | 0.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.218271E+11 | 0.136430E+11 | 0.75 | |||
Minimum of Months | 0.00 | 0.00 | 0.492648E+09 | 0.215364E+09 | 4228.33 | 2058.18 | 0.41 | |
Maximum of Months | 0.00 | 0.00 | 0.292773E+10 | 0.201030E+10 | 4661.37 | 2634.61 | 0.94 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.108852E+11 | 0.749679E+10 | 17292.40 | 07-JAN-09:02 | 8974.61 | 0.87 |
February | 0.00 | 0.00 | 0.102759E+11 | 0.685644E+10 | 16889.90 | 02-FEB-09:02 | 9220.71 | 0.89 |
March | 0.00 | 0.00 | 0.108139E+11 | 0.706754E+10 | 17502.38 | 06-MAR-09:02 | 8828.93 | 0.88 |
April | 0.00 | 0.00 | 0.112801E+11 | 0.735365E+10 | 15989.98 | 29-APR-18:02 | 9473.45 | 0.94 |
May | 0.00 | 0.00 | 0.123659E+11 | 0.815197E+10 | 16713.69 | 24-MAY-18:02 | 9180.71 | 0.95 |
June | 0.00 | 0.00 | 0.129082E+11 | 0.884784E+10 | 14786.90 | 13-JUN-08:61 | 10738.50 | 0.95 |
July | 0.00 | 0.00 | 0.141380E+11 | 0.995033E+10 | 14899.76 | 02-JUL-18:02 | 10185.65 | 0.96 |
August | 0.00 | 0.00 | 0.139081E+11 | 0.976287E+10 | 17351.93 | 12-AUG-08:62 | 8727.04 | 0.95 |
September | 0.00 | 0.00 | 0.150429E+11 | 0.109117E+11 | 15148.18 | 05-SEP-08:62 | 10290.07 | 0.96 |
October | 0.00 | 0.00 | 0.157867E+11 | 0.115900E+11 | 16474.18 | 31-OCT-08:62 | 9529.94 | 0.97 |
November | 0.00 | 0.00 | 0.133658E+11 | 0.943643E+10 | 16769.46 | 24-NOV-09:02 | 8825.92 | 0.95 |
December | 0.00 | 0.00 | 0.115983E+11 | 0.788447E+10 | 17525.26 | 23-DEC-09:02 | 8806.41 | 0.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.152369E+12 | 0.105310E+12 | 0.93 | |||
Minimum of Months | 0.00 | 0.00 | 0.102759E+11 | 0.685644E+10 | 14786.90 | 8727.04 | 0.87 | |
Maximum of Months | 0.00 | 0.00 | 0.157867E+11 | 0.115900E+11 | 17525.26 | 10738.50 | 0.97 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 167.34 | 19570.50 | 16-JAN-09:56 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 200.60 | 22139.92 | 22-FEB-09:53 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 105.34 | 20620.23 | 02-MAR-09:54 |
April | 0.00 | 0.00 | 01-APR-00:10 | 43.29 | 19459.18 | 19-APR-08:55 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 32.15 | 18349.62 | 28-MAY-06:57 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 20.17 | 23846.58 | 25-JUN-06:56 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.64 | 4321.85 | 06-JUL-06:55 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 27.19 | 22854.41 | 06-AUG-21:57 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.00 | 15373.52 | 27-SEP-08:28 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 34.95 | 28047.45 | 15-OCT-06:56 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 68.83 | 21403.15 | 09-NOV-09:17 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 185.70 | 22899.65 | 12-DEC-16:07 |
Annual Sum or Average | 0.00 | 76.85 | ||||
Minimum of Months | 0.00 | 0.00 | 20.17 | 4321.85 | ||
Maximum of Months | 0.00 | 0.00 | 200.60 | 28047.45 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 184296.75 | 568128.49 | 06-JAN-23:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 219401.87 | 638895.33 | 10-FEB-22:53 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 249154.72 | 640145.30 | 09-MAR-22:52 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 305139.77 | 570989.01 | 13-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 388853.20 | 661297.42 | 25-MAY-21:53 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 440834.25 | 656994.08 | 08-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 454411.07 | 675652.61 | 27-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 451378.34 | 643893.90 | 21-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 447023.60 | 735986.64 | 25-SEP-21:53 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 407457.03 | 637411.86 | 27-OCT-21:53 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 329698.70 | 628491.68 | 16-NOV-22:52 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 232668.80 | 689770.87 | 25-DEC-22:53 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 343120.44 | 0.00 | ||||
Minimum of Months | 184296.75 | 568128.49 | 0.00 | 0.00 | ||
Maximum of Months | 454411.07 | 735986.64 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 19242.43 | 40173.68 | 18-JAN-07:40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 19063.24 | 40067.15 | 01-FEB-07:40 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 18507.31 | 39272.11 | 01-MAR-07:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 17665.60 | 37571.87 | 03-APR-06:20 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16807.95 | 35871.14 | 01-MAY-06:20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 16155.52 | 34191.91 | 01-JUN-06:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15863.60 | 33164.13 | 03-JUL-06:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16063.10 | 33934.85 | 31-AUG-06:50 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16642.94 | 35399.42 | 29-SEP-06:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17470.44 | 37334.83 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 18328.22 | 38959.82 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 18976.18 | 39960.74 | 29-DEC-07:40 |
Annual Sum or Average | 0.00 | 17557.26 | ||||
Minimum of Months | 0.00 | 0.00 | 15863.60 | 33164.13 | ||
Maximum of Months | 0.00 | 0.00 | 19242.43 | 40173.68 |
Report: FanReportMonthly
For: SWHSYS1 HPWH FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.435840E+09 | 0.05 | 553.22 | 01-JAN-07:05 | 0.10 |
February | 0.385350E+09 | 0.05 | 553.22 | 01-FEB-06:08 | 0.10 |
March | 0.410374E+09 | 0.05 | 553.22 | 01-MAR-06:08 | 0.10 |
April | 0.370170E+09 | 0.05 | 553.22 | 01-APR-05:08 | 0.10 |
May | 0.355151E+09 | 0.05 | 553.22 | 01-MAY-05:15 | 0.10 |
June | 0.325814E+09 | 0.05 | 553.22 | 01-JUN-05:08 | 0.10 |
July | 0.330819E+09 | 0.05 | 553.22 | 01-JUL-05:08 | 0.10 |
August | 0.333815E+09 | 0.05 | 553.22 | 01-AUG-07:04 | 0.10 |
September | 0.334581E+09 | 0.05 | 553.22 | 01-SEP-05:08 | 0.10 |
October | 0.364985E+09 | 0.05 | 553.22 | 01-OCT-06:37 | 0.10 |
November | 0.381110E+09 | 0.05 | 553.22 | 01-NOV-05:08 | 0.10 |
December | 0.422808E+09 | 0.05 | 553.22 | 01-DEC-06:08 | 0.10 |
Annual Sum or Average | 0.445082E+10 | 0.05 | |||
Minimum of Months | 0.325814E+09 | 0.05 | 553.22 | 0.10 | |
Maximum of Months | 0.435840E+09 | 0.05 | 553.22 | 0.10 |
Report: FanReportMonthly
For: SWHSYSLAUNDRY HPWH FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.555613E+09 | 0.05 | 700.51 | 01-JAN-17:10 | 0.10 |
February | 0.501870E+09 | 0.05 | 700.51 | 01-FEB-17:10 | 0.10 |
March | 0.555349E+09 | 0.05 | 700.51 | 01-MAR-17:10 | 0.10 |
April | 0.537301E+09 | 0.05 | 700.51 | 01-APR-16:05 | 0.10 |
May | 0.554945E+09 | 0.05 | 700.51 | 01-MAY-16:10 | 0.10 |
June | 0.536780E+09 | 0.05 | 700.51 | 01-JUN-16:10 | 0.10 |
July | 0.554504E+09 | 0.05 | 700.51 | 01-JUL-16:10 | 0.10 |
August | 0.554459E+09 | 0.05 | 700.51 | 01-AUG-16:10 | 0.10 |
September | 0.537086E+09 | 0.05 | 700.51 | 01-SEP-16:10 | 0.10 |
October | 0.554919E+09 | 0.05 | 700.51 | 01-OCT-16:10 | 0.10 |
November | 0.537384E+09 | 0.05 | 700.51 | 01-NOV-16:10 | 0.10 |
December | 0.555711E+09 | 0.05 | 700.51 | 01-DEC-17:10 | 0.10 |
Annual Sum or Average | 0.653592E+10 | 0.05 | |||
Minimum of Months | 0.501870E+09 | 0.05 | 700.51 | 0.10 | |
Maximum of Months | 0.555711E+09 | 0.05 | 700.51 | 0.10 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.69 | 1299.30 | 01-JAN-09:58 | 0.87 |
February | 0.244774E+10 | 0.69 | 1299.30 | 01-FEB-10:00 | 0.87 |
March | 0.271000E+10 | 0.69 | 1299.30 | 01-MAR-00:03 | 0.87 |
April | 0.262258E+10 | 0.69 | 1299.30 | 01-APR-00:10 | 0.87 |
May | 0.271000E+10 | 0.69 | 1299.30 | 01-MAY-09:05 | 0.87 |
June | 0.262258E+10 | 0.69 | 1299.30 | 01-JUN-00:05 | 0.87 |
July | 0.271000E+10 | 0.69 | 1299.30 | 01-JUL-00:20 | 0.87 |
August | 0.271000E+10 | 0.69 | 1299.30 | 01-AUG-00:05 | 0.87 |
September | 0.262258E+10 | 0.69 | 1299.30 | 01-SEP-00:30 | 0.87 |
October | 0.271000E+10 | 0.69 | 1299.30 | 01-OCT-01:20 | 0.87 |
November | 0.262258E+10 | 0.69 | 1299.30 | 01-NOV-08:58 | 0.87 |
December | 0.271000E+10 | 0.69 | 1299.30 | 01-DEC-01:20 | 0.87 |
Annual Sum or Average | 0.319080E+11 | 0.69 | |||
Minimum of Months | 0.244774E+10 | 0.69 | 1299.30 | 0.87 | |
Maximum of Months | 0.271000E+10 | 0.69 | 1299.30 | 0.87 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.370818E+11 | 0.86 | 28026.00 | 13-JAN-22:10 | 1.32 |
February | 0.339154E+11 | 0.87 | 26672.57 | 17-FEB-22:10 | 1.28 |
March | 0.379582E+11 | 0.87 | 26625.81 | 27-MAR-21:20 | 1.28 |
April | 0.375707E+11 | 0.89 | 27470.29 | 14-APR-21:20 | 1.31 |
May | 0.401587E+11 | 0.90 | 27295.77 | 22-MAY-21:10 | 1.30 |
June | 0.399731E+11 | 0.92 | 28593.61 | 29-JUN-21:10 | 1.34 |
July | 0.415724E+11 | 0.92 | 28960.92 | 27-JUL-21:10 | 1.35 |
August | 0.414158E+11 | 0.92 | 29499.87 | 21-AUG-21:10 | 1.37 |
September | 0.405875E+11 | 0.92 | 31161.27 | 21-SEP-21:10 | 1.41 |
October | 0.411623E+11 | 0.91 | 31703.22 | 25-OCT-21:20 | 1.43 |
November | 0.383366E+11 | 0.89 | 30153.96 | 03-NOV-21:20 | 1.39 |
December | 0.377040E+11 | 0.87 | 28577.58 | 08-DEC-22:17 | 1.34 |
Annual Sum or Average | 0.467437E+12 | 0.90 | |||
Minimum of Months | 0.339154E+11 | 0.86 | 26625.81 | 1.28 | |
Maximum of Months | 0.415724E+11 | 0.92 | 31703.22 | 1.43 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.26 | 76.61 | 01-JAN-00:10 | 0.26 |
February | 0.185347E+09 | 0.26 | 76.61 | 01-FEB-00:03 | 0.26 |
March | 0.205205E+09 | 0.26 | 76.61 | 01-MAR-00:03 | 0.26 |
April | 0.198586E+09 | 0.26 | 76.61 | 01-APR-00:10 | 0.26 |
May | 0.205205E+09 | 0.26 | 76.61 | 01-MAY-00:05 | 0.26 |
June | 0.198586E+09 | 0.26 | 76.61 | 01-JUN-00:05 | 0.26 |
July | 0.205205E+09 | 0.26 | 76.61 | 01-JUL-00:10 | 0.26 |
August | 0.205205E+09 | 0.26 | 76.61 | 01-AUG-00:05 | 0.26 |
September | 0.198586E+09 | 0.26 | 76.61 | 01-SEP-00:05 | 0.26 |
October | 0.205205E+09 | 0.26 | 76.61 | 01-OCT-00:10 | 0.26 |
November | 0.198586E+09 | 0.26 | 76.61 | 01-NOV-00:05 | 0.26 |
December | 0.205205E+09 | 0.26 | 76.61 | 01-DEC-00:03 | 0.26 |
Annual Sum or Average | 0.241613E+10 | 0.26 | |||
Minimum of Months | 0.185347E+09 | 0.26 | 76.61 | 0.26 | |
Maximum of Months | 0.205205E+09 | 0.26 | 76.61 | 0.26 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:05 | 0.26 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.26 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.26 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.26 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.26 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.26 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.26 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:10 | 0.26 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:10 | 0.26 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:05 | 0.26 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.26 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:10 | 0.26 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.26 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.26 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.259743E+09 | 0.51 | 636.60 | 01-JAN-09:02 | 0.57 |
February | 0.285723E+09 | 0.52 | 636.60 | 01-FEB-09:02 | 0.57 |
March | 0.355780E+09 | 0.52 | 636.60 | 01-MAR-09:02 | 0.57 |
April | 0.426696E+09 | 0.54 | 636.60 | 01-APR-08:62 | 0.57 |
May | 0.468716E+09 | 0.55 | 636.60 | 01-MAY-08:62 | 0.57 |
June | 0.470602E+09 | 0.55 | 636.60 | 01-JUN-08:62 | 0.57 |
July | 0.535557E+09 | 0.55 | 636.60 | 01-JUL-08:62 | 0.57 |
August | 0.503646E+09 | 0.55 | 636.60 | 01-AUG-08:62 | 0.57 |
September | 0.497992E+09 | 0.55 | 636.60 | 01-SEP-08:62 | 0.57 |
October | 0.478610E+09 | 0.55 | 636.60 | 01-OCT-08:62 | 0.57 |
November | 0.360615E+09 | 0.53 | 636.60 | 01-NOV-08:62 | 0.57 |
December | 0.291053E+09 | 0.51 | 636.60 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.493473E+10 | 0.54 | |||
Minimum of Months | 0.259743E+09 | 0.51 | 636.60 | 0.57 | |
Maximum of Months | 0.535557E+09 | 0.55 | 636.60 | 0.57 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.124009E+09 | 0.33 | 643.80 | 01-JAN-09:51 | 0.57 |
February | 0.164953E+09 | 0.34 | 643.80 | 01-FEB-09:52 | 0.57 |
March | 0.235337E+09 | 0.37 | 643.80 | 01-MAR-09:51 | 0.57 |
April | 0.343557E+09 | 0.42 | 643.80 | 01-APR-08:51 | 0.57 |
May | 0.457053E+09 | 0.52 | 643.80 | 01-MAY-08:31 | 0.57 |
June | 0.474551E+09 | 0.54 | 643.80 | 01-JUN-08:62 | 0.57 |
July | 0.533619E+09 | 0.54 | 643.80 | 01-JUL-08:62 | 0.57 |
August | 0.487441E+09 | 0.54 | 643.80 | 01-AUG-08:62 | 0.57 |
September | 0.452233E+09 | 0.53 | 643.80 | 01-SEP-08:62 | 0.57 |
October | 0.396379E+09 | 0.51 | 643.80 | 01-OCT-08:51 | 0.57 |
November | 0.259470E+09 | 0.43 | 643.80 | 01-NOV-08:51 | 0.57 |
December | 0.162673E+09 | 0.34 | 643.80 | 01-DEC-09:21 | 0.57 |
Annual Sum or Average | 0.409127E+10 | 0.45 | |||
Minimum of Months | 0.124009E+09 | 0.33 | 643.80 | 0.57 | |
Maximum of Months | 0.533619E+09 | 0.54 | 643.80 | 0.57 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.170097E+10 | 0.54 | 1936.28 | 26-JAN-14:25 | 0.57 |
February | 0.146070E+10 | 0.55 | 1743.82 | 22-FEB-14:30 | 0.57 |
March | 0.140578E+10 | 0.54 | 1611.34 | 02-MAR-14:30 | 0.57 |
April | 0.140229E+10 | 0.57 | 920.97 | 15-APR-15:02 | 0.57 |
May | 0.149050E+10 | 0.57 | 878.56 | 22-MAY-17:20 | 0.57 |
June | 0.155498E+10 | 0.57 | 897.69 | 03-JUN-20:30 | 0.57 |
July | 0.171144E+10 | 0.57 | 988.13 | 29-JUL-17:20 | 0.57 |
August | 0.169552E+10 | 0.57 | 983.49 | 20-AUG-14:00 | 0.57 |
September | 0.192781E+10 | 0.57 | 1687.37 | 30-SEP-13:10 | 0.57 |
October | 0.217288E+10 | 0.57 | 1838.34 | 25-OCT-12:40 | 0.57 |
November | 0.189312E+10 | 0.56 | 1919.82 | 07-NOV-13:40 | 0.57 |
December | 0.173445E+10 | 0.55 | 1969.17 | 03-DEC-13:50 | 0.57 |
Annual Sum or Average | 0.201504E+11 | 0.56 | |||
Minimum of Months | 0.140229E+10 | 0.54 | 878.56 | 0.57 | |
Maximum of Months | 0.217288E+10 | 0.57 | 1969.17 | 0.57 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.126691E+10 | 0.29 | 4000.74 | 01-JAN-09:51 | 0.57 |
February | 0.138727E+10 | 0.30 | 4000.74 | 01-FEB-09:52 | 0.57 |
March | 0.186323E+10 | 0.33 | 4000.74 | 01-MAR-09:51 | 0.57 |
April | 0.236751E+10 | 0.38 | 4000.74 | 01-APR-08:51 | 0.57 |
May | 0.319489E+10 | 0.48 | 4000.74 | 01-MAY-08:31 | 0.57 |
June | 0.346348E+10 | 0.50 | 4000.74 | 01-JUN-08:62 | 0.57 |
July | 0.367726E+10 | 0.51 | 4000.74 | 01-JUL-08:62 | 0.57 |
August | 0.332633E+10 | 0.50 | 4000.74 | 01-AUG-08:62 | 0.57 |
September | 0.312860E+10 | 0.49 | 4000.74 | 01-SEP-08:62 | 0.57 |
October | 0.280007E+10 | 0.47 | 4000.74 | 01-OCT-08:51 | 0.57 |
November | 0.209665E+10 | 0.39 | 4000.74 | 01-NOV-08:51 | 0.57 |
December | 0.145265E+10 | 0.31 | 4000.74 | 01-DEC-09:21 | 0.57 |
Annual Sum or Average | 0.300248E+11 | 0.41 | |||
Minimum of Months | 0.126691E+10 | 0.29 | 4000.74 | 0.57 | |
Maximum of Months | 0.367726E+10 | 0.51 | 4000.74 | 0.57 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.274184E+09 | 0.52 | 569.23 | 01-JAN-09:02 | 0.57 |
February | 0.286786E+09 | 0.53 | 569.23 | 01-FEB-09:02 | 0.57 |
March | 0.350099E+09 | 0.54 | 569.23 | 01-MAR-09:02 | 0.57 |
April | 0.419740E+09 | 0.55 | 569.23 | 01-APR-08:62 | 0.57 |
May | 0.471014E+09 | 0.56 | 569.23 | 01-MAY-08:62 | 0.57 |
June | 0.506461E+09 | 0.56 | 569.23 | 01-JUN-08:62 | 0.57 |
July | 0.556238E+09 | 0.56 | 569.23 | 01-JUL-08:62 | 0.57 |
August | 0.505418E+09 | 0.56 | 569.23 | 01-AUG-08:62 | 0.57 |
September | 0.521295E+09 | 0.56 | 569.23 | 01-SEP-08:62 | 0.57 |
October | 0.489567E+09 | 0.56 | 569.23 | 01-OCT-08:62 | 0.57 |
November | 0.370358E+09 | 0.54 | 569.23 | 01-NOV-08:62 | 0.57 |
December | 0.273889E+09 | 0.51 | 569.23 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.502505E+10 | 0.55 | |||
Minimum of Months | 0.273889E+09 | 0.51 | 569.23 | 0.57 | |
Maximum of Months | 0.556238E+09 | 0.56 | 569.23 | 0.57 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134337E+09 | 0.33 | 574.71 | 01-JAN-09:51 | 0.57 |
February | 0.160972E+09 | 0.35 | 574.71 | 01-FEB-09:52 | 0.57 |
March | 0.233183E+09 | 0.38 | 574.71 | 01-MAR-09:51 | 0.57 |
April | 0.337463E+09 | 0.43 | 574.71 | 01-APR-08:51 | 0.57 |
May | 0.458321E+09 | 0.53 | 574.71 | 01-MAY-08:31 | 0.57 |
June | 0.510074E+09 | 0.55 | 574.71 | 01-JUN-08:62 | 0.57 |
July | 0.553623E+09 | 0.54 | 574.71 | 01-JUL-08:62 | 0.57 |
August | 0.490979E+09 | 0.55 | 574.71 | 01-AUG-08:62 | 0.57 |
September | 0.475285E+09 | 0.53 | 574.71 | 01-SEP-08:62 | 0.57 |
October | 0.408879E+09 | 0.52 | 574.71 | 01-OCT-08:51 | 0.57 |
November | 0.260686E+09 | 0.44 | 574.71 | 01-NOV-08:51 | 0.57 |
December | 0.148390E+09 | 0.33 | 574.71 | 01-DEC-09:21 | 0.57 |
Annual Sum or Average | 0.417219E+10 | 0.46 | |||
Minimum of Months | 0.134337E+09 | 0.33 | 574.71 | 0.57 | |
Maximum of Months | 0.553623E+09 | 0.55 | 574.71 | 0.57 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 60102034.90 | 0.50 | 167.93 | 01-JAN-09:02 | 0.57 |
February | 69162627.26 | 0.52 | 167.93 | 01-FEB-09:02 | 0.57 |
March | 88219477.18 | 0.52 | 167.93 | 01-MAR-09:02 | 0.57 |
April | 0.108408E+09 | 0.54 | 167.93 | 01-APR-08:62 | 0.57 |
May | 0.120965E+09 | 0.55 | 167.93 | 01-MAY-08:62 | 0.57 |
June | 0.121693E+09 | 0.55 | 167.93 | 01-JUN-08:62 | 0.57 |
July | 0.139545E+09 | 0.55 | 167.93 | 01-JUL-08:62 | 0.57 |
August | 0.129691E+09 | 0.55 | 167.93 | 01-AUG-08:62 | 0.57 |
September | 0.126744E+09 | 0.55 | 167.93 | 01-SEP-08:62 | 0.57 |
October | 0.119249E+09 | 0.55 | 167.93 | 01-OCT-08:62 | 0.57 |
November | 87155392.43 | 0.53 | 167.93 | 01-NOV-08:62 | 0.57 |
December | 69060872.58 | 0.51 | 167.93 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.124000E+10 | 0.53 | |||
Minimum of Months | 60102034.90 | 0.50 | 167.93 | 0.57 | |
Maximum of Months | 0.139545E+09 | 0.55 | 167.93 | 0.57 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 28681081.24 | 0.32 | 169.56 | 01-JAN-09:51 | 0.57 |
February | 40451347.08 | 0.34 | 169.56 | 01-FEB-16:02 | 0.57 |
March | 59599872.81 | 0.37 | 169.56 | 01-MAR-09:51 | 0.57 |
April | 89249350.36 | 0.42 | 169.56 | 01-APR-08:51 | 0.57 |
May | 0.118357E+09 | 0.52 | 169.56 | 01-MAY-08:31 | 0.57 |
June | 0.122972E+09 | 0.54 | 169.56 | 01-JUN-08:62 | 0.57 |
July | 0.139370E+09 | 0.54 | 169.56 | 01-JUL-08:62 | 0.57 |
August | 0.125885E+09 | 0.54 | 169.56 | 01-AUG-08:62 | 0.57 |
September | 0.115517E+09 | 0.53 | 169.56 | 01-SEP-08:62 | 0.57 |
October | 99109012.98 | 0.51 | 169.56 | 01-OCT-08:51 | 0.57 |
November | 63334713.43 | 0.43 | 169.56 | 01-NOV-08:51 | 0.57 |
December | 39904210.98 | 0.34 | 169.56 | 01-DEC-09:21 | 0.57 |
Annual Sum or Average | 0.104243E+10 | 0.45 | |||
Minimum of Months | 28681081.24 | 0.32 | 169.56 | 0.57 | |
Maximum of Months | 0.139370E+09 | 0.54 | 169.56 | 0.57 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.558840E+09 | 0.53 | 676.79 | 01-JAN-09:02 | 0.57 |
February | 0.510893E+09 | 0.54 | 676.79 | 01-FEB-09:02 | 0.57 |
March | 0.517523E+09 | 0.53 | 676.79 | 01-MAR-09:02 | 0.57 |
April | 0.528099E+09 | 0.54 | 676.79 | 01-APR-08:62 | 0.57 |
May | 0.572407E+09 | 0.54 | 676.79 | 01-MAY-08:62 | 0.57 |
June | 0.604881E+09 | 0.55 | 676.79 | 01-JUN-08:62 | 0.57 |
July | 0.671620E+09 | 0.55 | 676.79 | 01-JUL-08:62 | 0.57 |
August | 0.658343E+09 | 0.55 | 676.79 | 01-AUG-08:62 | 0.57 |
September | 0.735686E+09 | 0.55 | 676.79 | 01-SEP-08:62 | 0.57 |
October | 0.772663E+09 | 0.55 | 676.79 | 01-OCT-08:62 | 0.57 |
November | 0.662249E+09 | 0.55 | 676.79 | 01-NOV-08:62 | 0.57 |
December | 0.580152E+09 | 0.53 | 676.79 | 01-DEC-09:02 | 0.57 |
Annual Sum or Average | 0.737336E+10 | 0.54 | |||
Minimum of Months | 0.510893E+09 | 0.53 | 676.79 | 0.57 | |
Maximum of Months | 0.772663E+09 | 0.55 | 676.79 | 0.57 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 4222894.74 | 3838611.32 | 176.33 | 25-JAN-16:04 | 160.28 | 160.28 | 60.67 | 0.21 |
February | 4452011.01 | 4046878.00 | 161.38 | 04-FEB-09:06 | 146.69 | 146.69 | 55.08 | 0.19 |
March | 2324709.13 | 2113160.60 | 136.59 | 16-MAR-15:05 | 124.16 | 124.16 | 63.10 | 0.16 |
April | 540526.98 | 491339.02 | 85.05 | 19-APR-08:55 | 77.31 | 77.31 | 29.94 | 0.09 |
May | 410677.67 | 373306.00 | 86.76 | 28-MAY-06:57 | 78.86 | 78.86 | 33.70 | 0.10 |
June | 243937.89 | 221739.54 | 106.14 | 25-JUN-06:56 | 96.48 | 96.48 | 31.79 | 0.12 |
July | 241524.21 | 219545.50 | 19.06 | 06-JUL-06:55 | 17.33 | 17.33 | 27.48 | 0.02 |
August | 322443.66 | 293101.29 | 92.96 | 06-AUG-21:57 | 84.50 | 84.50 | 26.70 | 0.10 |
September | 267038.05 | 242737.59 | 66.86 | 27-SEP-08:28 | 60.78 | 60.78 | 28.86 | 0.07 |
October | 451433.58 | 410353.12 | 126.41 | 15-OCT-06:56 | 114.91 | 114.91 | 33.32 | 0.15 |
November | 1288148.22 | 1170926.73 | 106.57 | 13-NOV-16:07 | 96.88 | 96.88 | 62.54 | 0.12 |
December | 4705721.02 | 4277500.41 | 167.44 | 15-DEC-16:04 | 152.20 | 152.20 | 62.15 | 0.20 |
Annual Sum or Average | 19471066.14 | 17699199.12 | ||||||
Minimum of Months | 241524.21 | 219545.50 | 19.06 | 17.33 | 17.33 | 26.70 | 0.02 | |
Maximum of Months | 4705721.02 | 4277500.41 | 176.33 | 160.28 | 160.28 | 63.10 | 0.21 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.522074E+09 | 0.474565E+09 | 1258.28 | 06-JAN-23:00 | 1143.77 | 1143.77 | 7.15 | 18.09 |
February | 0.582140E+09 | 0.529166E+09 | 1247.86 | 10-FEB-22:53 | 1134.31 | 1134.31 | 7.15 | 18.02 |
March | 0.791511E+09 | 0.719483E+09 | 1330.67 | 09-MAR-22:52 | 1209.58 | 1209.58 | 7.24 | 18.53 |
April | 0.973479E+09 | 0.884893E+09 | 1310.04 | 13-APR-18:03 | 1190.83 | 1190.83 | 6.75 | 18.41 |
May | 0.147988E+10 | 0.134521E+10 | 1496.37 | 31-MAY-18:03 | 1360.20 | 1360.20 | 6.73 | 19.49 |
June | 0.181823E+10 | 0.165277E+10 | 1827.36 | 08-JUN-18:03 | 1661.07 | 1661.07 | 6.73 | 21.21 |
July | 0.200898E+10 | 0.182616E+10 | 2031.98 | 27-JUL-18:03 | 1847.07 | 1847.07 | 6.73 | 22.18 |
August | 0.195059E+10 | 0.177308E+10 | 1764.57 | 21-AUG-18:03 | 1604.00 | 1604.00 | 6.73 | 20.90 |
September | 0.190198E+10 | 0.172890E+10 | 2166.30 | 25-SEP-20:00 | 1969.17 | 1969.17 | 7.15 | 22.79 |
October | 0.162759E+10 | 0.147948E+10 | 1621.02 | 01-OCT-20:00 | 1473.51 | 1473.51 | 7.15 | 20.16 |
November | 0.117775E+10 | 0.107058E+10 | 1660.23 | 21-NOV-20:00 | 1509.15 | 1509.15 | 7.14 | 20.37 |
December | 0.754115E+09 | 0.685491E+09 | 1817.20 | 08-DEC-22:00 | 1651.83 | 1651.83 | 7.15 | 21.16 |
Annual Sum or Average | 0.155883E+11 | 0.141698E+11 | ||||||
Minimum of Months | 0.522074E+09 | 0.474565E+09 | 1247.86 | 1134.31 | 1134.31 | 6.73 | 18.02 | |
Maximum of Months | 0.200898E+10 | 0.182616E+10 | 2166.30 | 1969.17 | 1969.17 | 7.24 | 22.79 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.145431E+11 | 0.132197E+11 | 5429.78 | 01-JAN-00:10 | 4935.67 | 4935.67 | 9.40 | 38.44 |
February | 0.131200E+11 | 0.119261E+11 | 5429.78 | 01-FEB-00:03 | 4935.67 | 4935.67 | 8.61 | 38.44 |
March | 0.145344E+11 | 0.132118E+11 | 5429.78 | 01-MAR-00:03 | 4935.67 | 4935.67 | 8.87 | 38.44 |
April | 0.140740E+11 | 0.127933E+11 | 5429.78 | 01-APR-00:10 | 4935.67 | 4935.67 | 8.97 | 38.44 |
May | 0.145431E+11 | 0.132197E+11 | 5429.78 | 01-MAY-00:05 | 4935.67 | 4935.67 | 9.37 | 38.44 |
June | 0.140740E+11 | 0.127933E+11 | 5429.78 | 01-JUN-00:05 | 4935.67 | 4935.67 | 9.35 | 38.44 |
July | 0.145431E+11 | 0.132197E+11 | 5429.78 | 01-JUL-00:10 | 4935.67 | 4935.67 | 9.28 | 38.44 |
August | 0.145431E+11 | 0.132197E+11 | 5429.78 | 01-AUG-00:05 | 4935.67 | 4935.67 | 9.71 | 38.44 |
September | 0.140740E+11 | 0.127933E+11 | 5429.78 | 01-SEP-00:05 | 4935.67 | 4935.67 | 9.32 | 38.44 |
October | 0.145431E+11 | 0.132197E+11 | 5429.78 | 01-OCT-00:10 | 4935.67 | 4935.67 | 9.22 | 38.44 |
November | 0.140740E+11 | 0.127933E+11 | 5429.78 | 01-NOV-00:05 | 4935.67 | 4935.67 | 9.66 | 38.44 |
December | 0.145431E+11 | 0.132197E+11 | 5429.78 | 01-DEC-00:03 | 4935.67 | 4935.67 | 9.21 | 38.44 |
Annual Sum or Average | 0.171209E+12 | 0.155629E+12 | ||||||
Minimum of Months | 0.131200E+11 | 0.119261E+11 | 5429.78 | 4935.67 | 4935.67 | 8.61 | 38.44 | |
Maximum of Months | 0.145431E+11 | 0.132197E+11 | 5429.78 | 4935.67 | 4935.67 | 9.71 | 38.44 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 52.04 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 52.44 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 52.59 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 54.85 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 54.95 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 55.18 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 55.46 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 55.34 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 55.21 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 54.58 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 54.73 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 52.64 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 52.04 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 55.46 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 46.33 | 46.33 | 167.34 | 19570.50 | 16-JAN-09:56 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 62.84 | 79.40 | 200.60 | 22139.92 | 22-FEB-09:53 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 40.78 | 40.78 | 105.34 | 20620.23 | 02-MAR-09:54 |
April | 0.00 | 0.00 | 01-APR-00:10 | 36.32 | 36.32 | 43.29 | 19459.18 | 19-APR-08:55 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 31.74 | 31.74 | 32.15 | 18349.62 | 28-MAY-06:57 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 30.69 | 30.69 | 20.17 | 23846.58 | 25-JUN-06:56 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 30.05 | 30.05 | 20.64 | 4321.85 | 06-JUL-06:55 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 24.18 | 24.18 | 27.19 | 22854.41 | 06-AUG-21:57 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.06 | 27.06 | 23.00 | 15373.52 | 27-SEP-08:28 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 30.03 | 30.03 | 34.95 | 28047.45 | 15-OCT-06:56 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 30.99 | 30.99 | 68.83 | 21403.15 | 09-NOV-09:17 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 45.56 | 45.56 | 185.70 | 22899.65 | 12-DEC-16:07 |
Annual Sum or Average | 0.00 | 76.85 | ||||||
Minimum of Months | 0.00 | 0.00 | 24.18 | 24.18 | 20.17 | 4321.85 | ||
Maximum of Months | 0.00 | 0.00 | 62.84 | 79.40 | 200.60 | 28047.45 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 184296.75 | 568128.49 | 06-JAN-23:00 | 10.65 | 7.12 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 219401.87 | 638895.33 | 10-FEB-22:53 | 11.09 | 7.12 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 249154.72 | 640145.30 | 09-MAR-22:52 | 11.19 | 7.21 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 305139.77 | 570989.01 | 13-APR-18:03 | 10.27 | 6.73 | 0.00 | 0.00 | 01-APR-00:10 |
May | 388853.20 | 661297.42 | 25-MAY-21:53 | 11.23 | 7.12 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 440834.25 | 656994.08 | 08-JUN-18:03 | 10.78 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 454411.07 | 675652.61 | 27-JUL-18:03 | 10.90 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 451378.34 | 643893.90 | 21-AUG-18:03 | 10.70 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 447023.60 | 735986.64 | 25-SEP-21:53 | 11.69 | 7.12 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 407457.03 | 637411.86 | 27-OCT-21:53 | 11.08 | 7.12 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 329698.70 | 628491.68 | 16-NOV-22:52 | 11.02 | 7.12 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 232668.80 | 689770.87 | 25-DEC-22:53 | 11.50 | 7.21 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 343120.44 | 0.00 | ||||||
Minimum of Months | 184296.75 | 568128.49 | 10.27 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 454411.07 | 735986.64 | 11.69 | 7.21 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 52.04 | 59.99 | 19242.43 | 40173.68 | 18-JAN-07:40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 52.44 | 59.97 | 19063.24 | 40067.15 | 01-FEB-07:40 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 52.59 | 59.97 | 18507.31 | 39272.11 | 01-MAR-07:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 54.85 | 59.97 | 17665.60 | 37571.87 | 03-APR-06:20 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 54.95 | 60.00 | 16807.95 | 35871.14 | 01-MAY-06:20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 55.18 | 59.97 | 16155.52 | 34191.91 | 01-JUN-06:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 55.46 | 59.97 | 15863.60 | 33164.13 | 03-JUL-06:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 55.34 | 60.00 | 16063.10 | 33934.85 | 31-AUG-06:50 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 55.21 | 59.97 | 16642.94 | 35399.42 | 29-SEP-06:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 54.58 | 59.99 | 17470.44 | 37334.83 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 54.73 | 59.97 | 18328.22 | 38959.82 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 52.64 | 59.97 | 18976.18 | 39960.74 | 29-DEC-07:40 |
Annual Sum or Average | 0.00 | 17557.26 | ||||||
Minimum of Months | 0.00 | 0.00 | 52.04 | 59.97 | 15863.60 | 33164.13 | ||
Maximum of Months | 0.00 | 0.00 | 55.46 | 60.00 | 19242.43 | 40173.68 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.206164E+09 | 0.00 | 0.353754E+12 | 0.370818E+11 | 0.00 | 0.00 |
February | 0.187213E+09 | 0.00 | 0.389474E+12 | 0.339154E+11 | 0.00 | 0.00 |
March | 0.168789E+09 | 0.00 | 0.500675E+12 | 0.379582E+11 | 0.00 | 0.00 |
April | 0.101136E+09 | 0.00 | 0.596922E+12 | 0.375707E+11 | 0.00 | 0.00 |
May | 76945624.86 | 0.00 | 0.806314E+12 | 0.401587E+11 | 0.00 | 0.00 |
June | 47304379.85 | 0.00 | 0.892463E+12 | 0.399731E+11 | 0.00 | 0.00 |
July | 57095247.66 | 0.00 | 0.949067E+12 | 0.415724E+11 | 0.00 | 0.00 |
August | 66021199.33 | 0.00 | 0.950082E+12 | 0.414158E+11 | 0.00 | 0.00 |
September | 52425477.01 | 0.00 | 0.901923E+12 | 0.405875E+11 | 0.00 | 0.00 |
October | 79410911.82 | 0.00 | 0.842285E+12 | 0.411623E+11 | 0.00 | 0.00 |
November | 0.111880E+09 | 0.00 | 0.654036E+12 | 0.383366E+11 | 0.00 | 0.00 |
December | 0.221784E+09 | 0.00 | 0.465812E+12 | 0.377040E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.137617E+10 | 0.00 | 0.830281E+13 | 0.467437E+12 | 0.00 | 0.00 |
Minimum of Months | 47304379.85 | 0.00 | 0.353754E+12 | 0.339154E+11 | 0.00 | 0.00 |
Maximum of Months | 0.221784E+09 | 0.00 | 0.950082E+12 | 0.415724E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 2273.22 | 0.00 | 0.302241E+11 | 0.271000E+10 | 0.00 | 0.00 |
February | 3608.50 | 0.00 | 0.328775E+11 | 0.244774E+10 | 0.00 | 0.00 |
March | 3873.19 | 0.00 | 0.396807E+11 | 0.271000E+10 | 0.00 | 0.00 |
April | 2931.56 | 0.00 | 0.465830E+11 | 0.262258E+10 | 0.00 | 0.00 |
May | 2796.75 | 0.00 | 0.562843E+11 | 0.271000E+10 | 0.00 | 0.00 |
June | 3617.96 | 0.00 | 0.604233E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 2965.03 | 0.00 | 0.630075E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 3038.12 | 0.00 | 0.637900E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 3008.06 | 0.00 | 0.600955E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 3191.21 | 0.00 | 0.578633E+11 | 0.271000E+10 | 0.00 | 0.00 |
November | 3522.96 | 0.00 | 0.488820E+11 | 0.262258E+10 | 0.00 | 0.00 |
December | 3789.39 | 0.00 | 0.380129E+11 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 38615.94 | 0.00 | 0.597724E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 2273.22 | 0.00 | 0.302241E+11 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 3873.19 | 0.00 | 0.637900E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.370818E+11 | 0.353754E+12 | 0.206164E+09 | 0.107786E+11 | 0.328821E+11 | 0.00 | 0.00 | 0.00 |
February | 0.339154E+11 | 0.389474E+12 | 0.187213E+09 | 0.144058E+11 | 0.355698E+11 | 0.00 | 0.00 | 0.00 |
March | 0.379582E+11 | 0.500675E+12 | 0.168789E+09 | 0.111317E+11 | 0.647083E+11 | 0.00 | 0.00 | 0.00 |
April | 0.375707E+11 | 0.596922E+12 | 0.101136E+09 | 0.544406E+09 | 0.104959E+12 | 0.00 | 0.00 | 0.00 |
May | 0.401587E+11 | 0.806314E+12 | 76945624.86 | 0.207949E+09 | 0.284216E+12 | 0.00 | 0.00 | 0.00 |
June | 0.399731E+11 | 0.892463E+12 | 47304379.85 | 0.00 | 0.421997E+12 | 0.00 | 0.00 | 0.00 |
July | 0.415724E+11 | 0.949067E+12 | 57095247.66 | 0.00 | 0.439153E+12 | 0.00 | 0.00 | 0.00 |
August | 0.414158E+11 | 0.950082E+12 | 66021199.33 | 0.00 | 0.453251E+12 | 0.00 | 0.00 | 0.00 |
September | 0.405875E+11 | 0.901923E+12 | 52425477.01 | 0.00 | 0.394197E+12 | 0.00 | 0.00 | 0.00 |
October | 0.411623E+11 | 0.842285E+12 | 79410911.82 | 0.308939E+09 | 0.302134E+12 | 0.00 | 0.00 | 0.00 |
November | 0.383366E+11 | 0.654036E+12 | 0.111880E+09 | 0.387958E+10 | 0.167903E+12 | 0.00 | 0.00 | 0.00 |
December | 0.377040E+11 | 0.465812E+12 | 0.221784E+09 | 0.151230E+11 | 0.587290E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.467437E+12 | 0.830281E+13 | 0.137617E+10 | 0.563800E+11 | 0.275970E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.339154E+11 | 0.353754E+12 | 47304379.85 | 0.00 | 0.328821E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.415724E+11 | 0.950082E+12 | 0.221784E+09 | 0.151230E+11 | 0.453251E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.302241E+11 | 2273.22 | 0.138207E+10 | 0.518832E+10 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.328775E+11 | 3608.50 | 0.158574E+10 | 0.634901E+10 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.396807E+11 | 3873.19 | 0.117440E+10 | 0.135291E+11 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.465830E+11 | 2931.56 | 68817558.98 | 0.188840E+11 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.562843E+11 | 2796.75 | 0.00 | 0.399806E+11 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.604233E+11 | 3617.96 | 0.00 | 0.518505E+11 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.630075E+11 | 2965.03 | 0.00 | 0.542382E+11 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.637900E+11 | 3038.12 | 0.00 | 0.557331E+11 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.600955E+11 | 3008.06 | 0.00 | 0.503598E+11 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.578633E+11 | 3191.21 | 0.00 | 0.424582E+11 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.488820E+11 | 3522.96 | 0.412237E+09 | 0.245814E+11 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.380129E+11 | 3789.39 | 0.182632E+10 | 0.103620E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.597724E+12 | 38615.94 | 0.644957E+10 | 0.373514E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.302241E+11 | 2273.22 | 0.00 | 0.518832E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.637900E+11 | 3873.19 | 0.182632E+10 | 0.557331E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.370818E+11 | 0.206164E+09 | 0.353754E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.339154E+11 | 0.187213E+09 | 0.389474E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.379582E+11 | 0.168789E+09 | 0.500675E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.375707E+11 | 0.101136E+09 | 0.596922E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.401587E+11 | 76945624.86 | 0.806314E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.399731E+11 | 47304379.85 | 0.892463E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.415724E+11 | 57095247.66 | 0.949067E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.414158E+11 | 66021199.33 | 0.950082E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.405875E+11 | 52425477.01 | 0.901923E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.411623E+11 | 79410911.82 | 0.842285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.383366E+11 | 0.111880E+09 | 0.654036E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.377040E+11 | 0.221784E+09 | 0.465812E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.467437E+12 | 0.137617E+10 | 0.830281E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.339154E+11 | 47304379.85 | 0.353754E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.415724E+11 | 0.221784E+09 | 0.950082E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 2273.22 | 0.302241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 3608.50 | 0.328775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 3873.19 | 0.396807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 2931.56 | 0.465830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 2796.75 | 0.562843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 3617.96 | 0.604233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 2965.03 | 0.630075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 3038.12 | 0.637900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 3008.06 | 0.600955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 3191.21 | 0.578633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 3522.96 | 0.488820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 3789.39 | 0.380129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 38615.94 | 0.597724E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 2273.22 | 0.302241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 3873.19 | 0.637900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.597317E+10 | 0.247570E+10 | 0.00 | 15525273.19 | 0.336542E+10 | 0.00 | 0.155823E+11 | 0.00 | 0.94 |
February | 0.106164E+11 | 0.114452E+10 | 0.00 | 2242278.09 | 0.541979E+10 | 0.00 | 0.313736E+10 | 0.00 | 0.93 |
March | 0.123202E+11 | 71445479.08 | 0.00 | 111163.50 | 0.112781E+11 | 0.00 | 0.190481E+09 | 0.00 | 0.93 |
April | 0.377514E+10 | 0.00 | 0.00 | 0.00 | 0.129510E+11 | 0.00 | 0.00 | 0.00 | 0.92 |
May | 33180887.88 | 0.00 | 0.00 | 0.00 | 0.268384E+11 | 0.00 | 0.00 | 0.00 | 0.92 |
June | 0.00 | 0.258844E+09 | 0.00 | 0.00 | 0.351553E+11 | 0.00 | 0.00 | 0.00 | 0.91 |
July | 0.00 | 0.477251E+10 | 0.00 | 0.00 | 0.338512E+11 | 0.00 | 0.00 | 0.00 | 0.91 |
August | 0.00 | 0.180494E+11 | 0.00 | 0.00 | 0.211685E+11 | 0.00 | 0.00 | 0.00 | 0.92 |
September | 0.00 | 0.205483E+11 | 0.00 | 0.00 | 0.153228E+11 | 0.00 | 0.00 | 0.00 | 0.92 |
October | 440161.71 | 0.187520E+11 | 0.00 | 1577421.31 | 0.108150E+11 | 0.00 | 56485896.50 | 0.00 | 0.94 |
November | 0.655262E+09 | 0.133146E+11 | 0.00 | 10759617.79 | 0.667796E+10 | 0.00 | 0.530563E+10 | 0.00 | 0.95 |
December | 0.286440E+10 | 0.704065E+10 | 0.00 | 21171648.95 | 0.449976E+10 | 0.00 | 0.138193E+11 | 0.00 | 0.95 |
Annual Sum or Average | 0.362382E+11 | 0.864280E+11 | 0.00 | 51387402.82 | 0.187343E+12 | 0.00 | 0.380915E+11 | 0.00 | 0.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.336542E+10 | 0.00 | 0.00 | 0.00 | 0.91 |
Maximum of Months | 0.123202E+11 | 0.205483E+11 | 0.00 | 21171648.95 | 0.351553E+11 | 0.00 | 0.155823E+11 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.199451E+10 | 0.484893E+09 | 0.00 | 1711142.55 | 0.252602E+09 | 0.00 | 0.533998E+09 | 0.00 | 2.08 |
February | 0.127032E+10 | 0.491142E+09 | 0.00 | 1653666.45 | 0.319232E+09 | 0.00 | 0.336877E+09 | 0.00 | 2.06 |
March | 0.122480E+10 | 0.852560E+09 | 0.00 | 826506.59 | 0.500847E+09 | 0.00 | 0.229630E+09 | 0.00 | 2.00 |
April | 0.328469E+09 | 0.107340E+10 | 0.00 | 291636.85 | 0.492106E+09 | 0.00 | 0.109382E+09 | 0.00 | 1.99 |
May | 1944602.04 | 0.239909E+10 | 0.00 | 15050.77 | 0.759041E+09 | 0.00 | 1889438.49 | 0.00 | 1.96 |
June | 0.00 | 0.373729E+10 | 0.00 | 0.00 | 0.476042E+09 | 0.00 | 0.00 | 0.00 | 1.97 |
July | 0.00 | 0.445372E+10 | 0.00 | 0.00 | 0.267317E+09 | 0.00 | 0.00 | 0.00 | 2.00 |
August | 0.00 | 0.428746E+10 | 0.00 | 0.00 | 0.538147E+09 | 0.00 | 0.00 | 0.00 | 2.03 |
September | 0.00 | 0.435930E+10 | 0.00 | 0.00 | 0.297133E+09 | 0.00 | 0.00 | 0.00 | 2.14 |
October | 1217027.76 | 0.348519E+10 | 0.00 | 100251.45 | 0.374087E+09 | 0.00 | 5442538.84 | 0.00 | 2.20 |
November | 0.531736E+09 | 0.225230E+10 | 0.00 | 650622.50 | 0.299454E+09 | 0.00 | 0.162702E+09 | 0.00 | 2.15 |
December | 0.145989E+10 | 0.112500E+10 | 0.00 | 1238103.27 | 0.338640E+09 | 0.00 | 0.459615E+09 | 0.00 | 2.11 |
Annual Sum or Average | 0.681288E+10 | 0.290013E+11 | 0.00 | 6486980.43 | 0.491465E+10 | 0.00 | 0.183954E+10 | 0.00 | 2.06 |
Minimum of Months | 0.00 | 0.484893E+09 | 0.00 | 0.00 | 0.252602E+09 | 0.00 | 0.00 | 0.00 | 1.96 |
Maximum of Months | 0.199451E+10 | 0.445372E+10 | 0.00 | 1711142.55 | 0.759041E+09 | 0.00 | 0.533998E+09 | 0.00 | 2.20 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.136379E+10 | 0.218167E+09 | 0.00 | 751751.29 | 0.349598E+09 | 0.00 | 0.700576E+09 | 0.00 | 1.41 |
February | 0.654169E+09 | 0.276336E+09 | 0.00 | 907675.55 | 0.364807E+09 | 0.00 | 0.686369E+09 | 0.00 | 1.42 |
March | 0.697183E+09 | 0.592767E+09 | 0.00 | 799279.26 | 0.523062E+09 | 0.00 | 0.518108E+09 | 0.00 | 1.42 |
April | 68811194.47 | 0.681970E+09 | 0.00 | 849799.06 | 0.604671E+09 | 0.00 | 0.300560E+09 | 0.00 | 1.44 |
May | 9930.23 | 0.155506E+10 | 0.00 | 66178.97 | 0.112228E+10 | 0.00 | 3156815.90 | 0.00 | 1.44 |
June | 0.00 | 0.227020E+10 | 0.00 | 0.00 | 0.129098E+10 | 0.00 | 0.00 | 0.00 | 1.44 |
July | 0.00 | 0.288896E+10 | 0.00 | 0.00 | 0.102815E+10 | 0.00 | 0.00 | 0.00 | 1.45 |
August | 0.00 | 0.272181E+10 | 0.00 | 0.00 | 0.123502E+10 | 0.00 | 0.00 | 0.00 | 1.46 |
September | 0.00 | 0.282935E+10 | 0.00 | 0.00 | 0.776930E+09 | 0.00 | 0.00 | 0.00 | 1.46 |
October | 69549.20 | 0.207054E+10 | 0.00 | 152889.01 | 0.837014E+09 | 0.00 | 5469959.91 | 0.00 | 1.45 |
November | 0.309163E+09 | 0.123840E+10 | 0.00 | 329069.45 | 0.701519E+09 | 0.00 | 0.254209E+09 | 0.00 | 1.43 |
December | 0.965629E+09 | 0.658251E+09 | 0.00 | 720937.51 | 0.462263E+09 | 0.00 | 0.608473E+09 | 0.00 | 1.42 |
Annual Sum or Average | 0.405882E+10 | 0.180018E+11 | 0.00 | 4577580.09 | 0.929629E+10 | 0.00 | 0.307692E+10 | 0.00 | 1.44 |
Minimum of Months | 0.00 | 0.218167E+09 | 0.00 | 0.00 | 0.349598E+09 | 0.00 | 0.00 | 0.00 | 1.41 |
Maximum of Months | 0.136379E+10 | 0.288896E+10 | 0.00 | 907675.55 | 0.129098E+10 | 0.00 | 0.700576E+09 | 0.00 | 1.46 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.187421E+10 | 0.00 | 0.00 | 0.00 | 0.509399E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
February | 0.120639E+10 | 6651127.04 | 0.00 | 0.00 | 0.568979E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
March | 0.109615E+10 | 17840097.53 | 0.00 | 1542.23 | 0.977507E+09 | 0.00 | 1034514.42 | 0.00 | 0.60 |
April | 0.325622E+09 | 92032431.18 | 0.00 | 24344.87 | 0.104398E+10 | 0.00 | 5431874.24 | 0.00 | 0.60 |
May | 2451340.61 | 0.650833E+09 | 0.00 | 3562.06 | 0.172212E+10 | 0.00 | 455045.97 | 0.00 | 0.60 |
June | 0.00 | 0.183128E+10 | 0.00 | 0.00 | 0.136892E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.259156E+10 | 0.00 | 0.00 | 0.942018E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
August | 0.00 | 0.175174E+10 | 0.00 | 0.00 | 0.175667E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
September | 0.00 | 0.188837E+10 | 0.00 | 0.00 | 0.130395E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
October | 4721878.58 | 0.721666E+09 | 0.00 | 15318.42 | 0.183142E+10 | 0.00 | 326462.76 | 0.00 | 0.60 |
November | 0.510327E+09 | 0.270375E+09 | 0.00 | 368.43 | 0.143558E+10 | 0.00 | 1100780.32 | 0.00 | 0.60 |
December | 0.141279E+10 | 57598078.72 | 0.00 | 5705.29 | 0.938849E+09 | 0.00 | 10556407.64 | 0.00 | 0.60 |
Annual Sum or Average | 0.643267E+10 | 0.987994E+10 | 0.00 | 50841.31 | 0.143994E+11 | 0.00 | 18905085.34 | 0.00 | 0.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.509399E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
Maximum of Months | 0.187421E+10 | 0.259156E+10 | 0.00 | 24344.87 | 0.183142E+10 | 0.00 | 10556407.64 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100374E+10 | 0.00 | 0.00 | 0.00 | 0.272810E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
February | 0.646085E+09 | 0.00 | 0.00 | 0.00 | 0.308280E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
March | 0.587601E+09 | 0.00 | 0.00 | 0.00 | 0.533060E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
April | 0.177309E+09 | 3645731.42 | 0.00 | 0.00 | 0.604632E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
May | 1558427.11 | 0.135564E+09 | 0.00 | 0.00 | 0.112497E+10 | 0.00 | 0.00 | 0.00 | 0.56 |
June | 0.00 | 0.679198E+09 | 0.00 | 0.00 | 0.988821E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
July | 0.00 | 0.113275E+10 | 0.00 | 0.00 | 0.695347E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.659610E+09 | 0.00 | 0.00 | 0.118204E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
September | 0.00 | 0.734533E+09 | 0.00 | 0.00 | 0.932195E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 2627496.29 | 0.149914E+09 | 0.00 | 360.69 | 0.121088E+10 | 0.00 | 82170.11 | 0.00 | 0.55 |
November | 0.273896E+09 | 11546606.76 | 0.00 | 0.00 | 0.901860E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
December | 0.762277E+09 | 0.00 | 0.00 | 0.00 | 0.533649E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
Annual Sum or Average | 0.345509E+10 | 0.350676E+10 | 0.00 | 360.69 | 0.928854E+10 | 0.00 | 82170.11 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.272810E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.100374E+10 | 0.113275E+10 | 0.00 | 360.69 | 0.121088E+10 | 0.00 | 82170.11 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.163076E+09 | 0.924566E+10 | 0.00 | 66784780.23 | 29317107.48 | 0.00 | 0.335234E+11 | 0.00 | 22.80 |
February | 92584449.64 | 0.104433E+11 | 0.00 | 53657288.73 | 32797757.60 | 0.00 | 0.215042E+11 | 0.00 | 22.78 |
March | 80033461.11 | 0.180252E+11 | 0.00 | 47548997.15 | 43490256.50 | 0.00 | 0.196210E+11 | 0.00 | 22.78 |
April | 23383000.38 | 0.202622E+11 | 0.00 | 23352065.93 | 0.105305E+09 | 0.00 | 0.579809E+10 | 0.00 | 22.60 |
May | 0.00 | 0.419934E+11 | 0.00 | 898394.14 | 0.190127E+09 | 0.00 | 46488236.09 | 0.00 | 22.49 |
June | 0.00 | 0.557211E+11 | 0.00 | 0.00 | 0.166120E+09 | 0.00 | 0.00 | 0.00 | 22.31 |
July | 0.00 | 0.599757E+11 | 0.00 | 0.00 | 0.297855E+09 | 0.00 | 0.00 | 0.00 | 21.96 |
August | 0.00 | 0.611307E+11 | 0.00 | 0.00 | 0.269212E+09 | 0.00 | 0.00 | 0.00 | 22.29 |
September | 0.00 | 0.555791E+11 | 0.00 | 0.00 | 0.204830E+09 | 0.00 | 0.00 | 0.00 | 22.18 |
October | 0.00 | 0.452287E+11 | 0.00 | 2278602.06 | 0.211333E+09 | 0.00 | 83688752.59 | 0.00 | 22.36 |
November | 27791505.62 | 0.310390E+11 | 0.00 | 23722030.96 | 77237656.46 | 0.00 | 0.903085E+10 | 0.00 | 22.58 |
December | 0.104932E+09 | 0.180018E+11 | 0.00 | 52914587.21 | 82297337.59 | 0.00 | 0.257719E+11 | 0.00 | 22.71 |
Annual Sum or Average | 0.491800E+09 | 0.426646E+12 | 0.00 | 0.271157E+09 | 0.170992E+10 | 0.00 | 0.115380E+12 | 0.00 | 22.48 |
Minimum of Months | 0.00 | 0.924566E+10 | 0.00 | 0.00 | 29317107.48 | 0.00 | 0.00 | 0.00 | 21.96 |
Maximum of Months | 0.163076E+09 | 0.611307E+11 | 0.00 | 66784780.23 | 0.297855E+09 | 0.00 | 0.335234E+11 | 0.00 | 22.80 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130446E+10 | 0.314843E+10 | 0.00 | 22399846.62 | 0.293522E+09 | 0.00 | 0.106846E+11 | 0.00 | 3.48 |
February | 0.765949E+09 | 0.342258E+10 | 0.00 | 18910087.92 | 0.373311E+09 | 0.00 | 0.699687E+10 | 0.00 | 3.48 |
March | 0.139657E+10 | 0.589058E+10 | 0.00 | 13412411.77 | 0.670709E+09 | 0.00 | 0.556244E+10 | 0.00 | 3.43 |
April | 0.229644E+09 | 0.646778E+10 | 0.00 | 7696028.93 | 0.950943E+09 | 0.00 | 0.193136E+10 | 0.00 | 3.44 |
May | 0.00 | 0.137491E+11 | 0.00 | 684567.67 | 0.172194E+10 | 0.00 | 20832099.07 | 0.00 | 3.47 |
June | 0.00 | 0.189815E+11 | 0.00 | 0.00 | 0.184009E+10 | 0.00 | 0.00 | 0.00 | 3.52 |
July | 0.00 | 0.211761E+11 | 0.00 | 0.00 | 0.146392E+10 | 0.00 | 0.00 | 0.00 | 3.49 |
August | 0.00 | 0.212414E+11 | 0.00 | 0.00 | 0.188396E+10 | 0.00 | 0.00 | 0.00 | 3.55 |
September | 0.00 | 0.207701E+11 | 0.00 | 0.00 | 0.756762E+09 | 0.00 | 0.00 | 0.00 | 3.63 |
October | 382488.00 | 0.171363E+11 | 0.00 | 1067380.21 | 0.637139E+09 | 0.00 | 35546008.42 | 0.00 | 3.68 |
November | 0.354129E+09 | 0.113551E+11 | 0.00 | 8085598.44 | 0.498590E+09 | 0.00 | 0.292863E+10 | 0.00 | 3.61 |
December | 0.109374E+10 | 0.659847E+10 | 0.00 | 16828589.03 | 0.274465E+09 | 0.00 | 0.800106E+10 | 0.00 | 3.51 |
Annual Sum or Average | 0.514487E+10 | 0.149937E+12 | 0.00 | 89084510.60 | 0.113653E+11 | 0.00 | 0.361613E+11 | 0.00 | 3.52 |
Minimum of Months | 0.00 | 0.314843E+10 | 0.00 | 0.00 | 0.274465E+09 | 0.00 | 0.00 | 0.00 | 3.43 |
Maximum of Months | 0.139657E+10 | 0.212414E+11 | 0.00 | 22399846.62 | 0.188396E+10 | 0.00 | 0.106846E+11 | 0.00 | 3.68 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101355E+11 | 0.817686E+10 | 0.00 | 50970304.95 | 0.349782E+10 | 0.00 | 0.317949E+11 | 0.00 | 1.72 |
February | 0.515601E+10 | 0.886977E+10 | 0.00 | 44710746.76 | 0.427371E+10 | 0.00 | 0.221802E+11 | 0.00 | 1.73 |
March | 0.708480E+10 | 0.160387E+11 | 0.00 | 35408855.61 | 0.696976E+10 | 0.00 | 0.175411E+11 | 0.00 | 1.73 |
April | 0.842564E+09 | 0.168578E+11 | 0.00 | 27637308.86 | 0.932308E+10 | 0.00 | 0.679388E+10 | 0.00 | 1.75 |
May | 0.00 | 0.373718E+11 | 0.00 | 2359367.14 | 0.176753E+11 | 0.00 | 71051171.63 | 0.00 | 1.78 |
June | 0.00 | 0.546466E+11 | 0.00 | 0.00 | 0.193360E+11 | 0.00 | 0.00 | 0.00 | 1.80 |
July | 0.00 | 0.642783E+11 | 0.00 | 0.00 | 0.163650E+11 | 0.00 | 0.00 | 0.00 | 1.79 |
August | 0.00 | 0.640703E+11 | 0.00 | 0.00 | 0.176703E+11 | 0.00 | 0.00 | 0.00 | 1.81 |
September | 0.00 | 0.661880E+11 | 0.00 | 0.00 | 0.867715E+10 | 0.00 | 0.00 | 0.00 | 1.82 |
October | 1138531.36 | 0.528881E+11 | 0.00 | 3698259.93 | 0.780410E+10 | 0.00 | 0.123540E+09 | 0.00 | 1.81 |
November | 0.163077E+10 | 0.348804E+11 | 0.00 | 21529297.83 | 0.563394E+10 | 0.00 | 0.985858E+10 | 0.00 | 1.78 |
December | 0.728656E+10 | 0.189826E+11 | 0.00 | 44170939.61 | 0.431779E+10 | 0.00 | 0.249189E+11 | 0.00 | 1.74 |
Annual Sum or Average | 0.321373E+11 | 0.443249E+12 | 0.00 | 0.230485E+09 | 0.121544E+12 | 0.00 | 0.113282E+12 | 0.00 | 1.77 |
Minimum of Months | 0.00 | 0.817686E+10 | 0.00 | 0.00 | 0.349782E+10 | 0.00 | 0.00 | 0.00 | 1.72 |
Maximum of Months | 0.101355E+11 | 0.661880E+11 | 0.00 | 50970304.95 | 0.193360E+11 | 0.00 | 0.317949E+11 | 0.00 | 1.82 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4499185.55 | 0.333836E+09 | 183733.63 | 6118836.42 | 2169724.12 | 1603130.54 | 0.560418E+09 | 4039.38 | 0.35 |
February | 4955955.92 | 0.318927E+09 | 52667.39 | 5390532.07 | 2538119.37 | 33684790.33 | 0.320203E+09 | 1660.02 | 0.35 |
March | 13133331.56 | 0.483830E+09 | 184586.72 | 4674280.71 | 77510.88 | 1315610.45 | 0.317320E+09 | 7070.71 | 0.35 |
April | 0.00 | 0.656070E+09 | 201553.04 | 1764529.49 | 0.00 | 121760.28 | 54927114.61 | 7905.86 | 0.35 |
May | 0.00 | 0.121719E+10 | 602265.19 | 0.00 | 0.00 | 0.00 | 0.00 | 10110.44 | 0.36 |
June | 0.00 | 0.154888E+10 | 400245.10 | 0.00 | 0.00 | 0.00 | 0.00 | 4794.01 | 0.35 |
July | 0.00 | 0.162462E+10 | 84173.81 | 0.00 | 0.00 | 0.00 | 0.00 | 348.68 | 0.35 |
August | 0.00 | 0.166792E+10 | 408184.88 | 0.00 | 0.00 | 0.00 | 0.00 | 3331.34 | 0.35 |
September | 0.00 | 0.150901E+10 | 288348.29 | 0.00 | 0.00 | 0.00 | 0.00 | 2325.22 | 0.36 |
October | 0.00 | 0.129287E+10 | 385090.68 | 0.00 | 0.00 | 0.00 | 0.00 | 7584.72 | 0.36 |
November | 638778.62 | 0.934665E+09 | 459165.10 | 2025146.56 | 0.00 | 507511.87 | 0.146550E+09 | 11555.33 | 0.35 |
December | 1411815.08 | 0.508249E+09 | 146068.97 | 4582587.76 | 1419646.71 | 1924288.92 | 0.396639E+09 | 4297.07 | 0.35 |
Annual Sum or Average | 24639066.74 | 0.120961E+11 | 3396082.80 | 24555913.01 | 6205001.09 | 39157092.40 | 0.179606E+10 | 65022.76 | 0.35 |
Minimum of Months | 0.00 | 0.318927E+09 | 52667.39 | 0.00 | 0.00 | 0.00 | 0.00 | 348.68 | 0.35 |
Maximum of Months | 13133331.56 | 0.166792E+10 | 602265.19 | 6118836.42 | 2538119.37 | 33684790.33 | 0.560418E+09 | 11555.33 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.149742E+09 | 0.252949E+09 | 416895.52 | 2542279.22 | 82762563.26 | 24157409.28 | 0.396131E+09 | 26225.75 | 0.36 |
February | 84182861.62 | 0.242000E+09 | 338724.13 | 2845475.82 | 79119661.41 | 51996060.53 | 0.225167E+09 | 22715.50 | 0.35 |
March | 86018881.57 | 0.386354E+09 | 188879.74 | 2268222.84 | 97491654.41 | 7566340.76 | 0.240551E+09 | 8210.42 | 0.35 |
April | 20280128.94 | 0.552599E+09 | 299959.84 | 996741.55 | 0.103297E+09 | 26450.95 | 35503426.43 | 5721.33 | 0.36 |
May | 0.00 | 0.116052E+10 | 457944.80 | 0.00 | 56668442.25 | 0.00 | 0.00 | 8953.45 | 0.36 |
June | 0.00 | 0.152685E+10 | 424862.81 | 0.00 | 21823695.57 | 0.00 | 0.00 | 2410.73 | 0.35 |
July | 0.00 | 0.158807E+10 | 94408.98 | 0.00 | 36341259.80 | 0.00 | 0.00 | 2208.46 | 0.35 |
August | 0.00 | 0.164688E+10 | 403676.09 | 0.00 | 20845654.41 | 0.00 | 0.00 | 5471.38 | 0.35 |
September | 0.00 | 0.146411E+10 | 687377.59 | 0.00 | 44322117.90 | 0.00 | 0.00 | 8297.32 | 0.36 |
October | 0.00 | 0.123194E+10 | 1056667.89 | 0.00 | 60086818.02 | 0.00 | 0.00 | 22254.99 | 0.36 |
November | 38378731.44 | 0.836556E+09 | 1016203.69 | 992593.26 | 97421715.66 | 831781.30 | 0.109501E+09 | 32180.20 | 0.36 |
December | 0.113016E+09 | 0.397095E+09 | 638811.05 | 1861686.25 | 0.112006E+09 | 33124264.23 | 0.256508E+09 | 19664.07 | 0.36 |
Annual Sum or Average | 0.491619E+09 | 0.112859E+11 | 6024412.14 | 11506998.94 | 0.812187E+09 | 0.117702E+09 | 0.126336E+10 | 164313.60 | 0.36 |
Minimum of Months | 0.00 | 0.242000E+09 | 94408.98 | 0.00 | 20845654.41 | 0.00 | 0.00 | 2208.46 | 0.35 |
Maximum of Months | 0.149742E+09 | 0.164688E+10 | 1056667.89 | 2845475.82 | 0.112006E+09 | 51996060.53 | 0.396131E+09 | 32180.20 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 33119772.83 | 0.478461E+09 | 0.00 | 2167599.22 | 194096.69 | 0.00 | 0.430990E+09 | 0.00 | 0.02 |
February | 0.00 | 0.504820E+09 | 0.00 | 1512092.43 | 0.00 | 0.00 | 0.219672E+09 | 0.00 | 0.02 |
March | 0.00 | 0.559904E+09 | 0.00 | 1006639.06 | 0.00 | 0.00 | 0.318452E+09 | 0.00 | 0.02 |
April | 0.00 | 0.685878E+09 | 0.00 | 170608.82 | 0.00 | 0.00 | 47735114.92 | 0.00 | 0.02 |
May | 0.00 | 0.104045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.116471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
July | 0.00 | 0.123932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
August | 0.00 | 0.131705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
September | 0.00 | 0.121543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
October | 0.00 | 0.106754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
November | 25588723.24 | 0.701439E+09 | 0.00 | 506554.65 | 0.00 | 0.00 | 69194106.06 | 0.00 | 0.02 |
December | 22475039.00 | 0.713733E+09 | 0.00 | 1360797.00 | 0.00 | 0.00 | 0.284706E+09 | 0.00 | 0.02 |
Annual Sum or Average | 81183535.07 | 0.106887E+11 | 0.00 | 6724291.18 | 194096.69 | 0.00 | 0.137075E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.478461E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 33119772.83 | 0.131705E+10 | 0.00 | 2167599.22 | 194096.69 | 0.00 | 0.430990E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.203600E+10 | 0.326133E+10 | 1793313.41 | 42075767.15 | 0.129659E+10 | 19952235.58 | 0.566857E+10 | 23212.94 | 0.40 |
February | 0.117148E+10 | 0.316208E+10 | 719094.08 | 35568281.07 | 0.119790E+10 | 14746882.09 | 0.371824E+10 | 9339.21 | 0.40 |
March | 0.118064E+10 | 0.508106E+10 | 158425.15 | 30111127.46 | 0.148451E+10 | 16848193.49 | 0.333552E+10 | 16231.60 | 0.40 |
April | 0.288983E+09 | 0.735655E+10 | 331159.91 | 10734745.58 | 0.154411E+10 | 262352.24 | 0.470570E+09 | 4250.39 | 0.40 |
May | 0.00 | 0.156393E+11 | 1227910.48 | 0.00 | 0.876253E+09 | 0.00 | 0.00 | 5036.61 | 0.40 |
June | 0.00 | 0.206991E+11 | 1701550.73 | 0.00 | 0.311836E+09 | 0.00 | 0.00 | 6902.31 | 0.40 |
July | 0.00 | 0.215190E+11 | 0.00 | 0.00 | 0.516553E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.221779E+11 | 617707.25 | 0.00 | 0.448685E+09 | 0.00 | 0.00 | 4787.52 | 0.40 |
September | 0.00 | 0.198243E+11 | 0.00 | 0.00 | 0.646111E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
October | 0.00 | 0.163079E+11 | 2308074.64 | 0.00 | 0.123007E+10 | 0.00 | 0.00 | 16978.19 | 0.40 |
November | 0.554524E+09 | 0.108793E+11 | 1224552.54 | 15559493.44 | 0.180250E+10 | 890097.41 | 0.145967E+10 | 17853.87 | 0.40 |
December | 0.154887E+10 | 0.513080E+10 | 1392664.66 | 30699072.70 | 0.178236E+10 | 14047068.22 | 0.389333E+10 | 38056.91 | 0.40 |
Annual Sum or Average | 0.678050E+10 | 0.151039E+12 | 11474452.85 | 0.164748E+09 | 0.131375E+11 | 66746829.03 | 0.185459E+11 | 142649.57 | 0.40 |
Minimum of Months | 0.00 | 0.316208E+10 | 0.00 | 0.00 | 0.311836E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.203600E+10 | 0.221779E+11 | 2308074.64 | 42075767.15 | 0.180250E+10 | 19952235.58 | 0.566857E+10 | 38056.91 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2734944.21 | 0.334047E+09 | 84379.71 | 6525456.85 | 2060573.17 | 4793799.51 | 0.558585E+09 | 1922.84 | 0.35 |
February | 3993989.21 | 0.319125E+09 | 69406.64 | 5814118.98 | 2322814.33 | 32626681.70 | 0.321799E+09 | 2148.85 | 0.35 |
March | 1547091.61 | 0.484023E+09 | 74658.82 | 4817059.32 | 0.00 | 5703818.58 | 0.324376E+09 | 1088.45 | 0.35 |
April | 0.00 | 0.656267E+09 | 12294.85 | 1838319.35 | 0.00 | 0.00 | 54975085.03 | 31.55 | 0.35 |
May | 0.00 | 0.121775E+10 | 52024.76 | 0.00 | 0.00 | 0.00 | 0.00 | 16.57 | 0.36 |
June | 0.00 | 0.154928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
July | 0.00 | 0.162470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
August | 0.00 | 0.166825E+10 | 78311.35 | 0.00 | 0.00 | 0.00 | 0.00 | 726.18 | 0.35 |
September | 0.00 | 0.150930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
October | 0.00 | 0.129326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
November | 555948.61 | 0.934805E+09 | 104724.71 | 2253518.77 | 225580.72 | 119822.10 | 0.146793E+09 | 420.01 | 0.35 |
December | 1740409.93 | 0.508374E+09 | 25517.30 | 4586531.41 | 1419646.71 | 7020950.32 | 0.391210E+09 | 338.75 | 0.35 |
Annual Sum or Average | 10572383.57 | 0.120992E+11 | 501318.15 | 25835004.69 | 6028614.93 | 50265072.20 | 0.179774E+10 | 6693.20 | 0.35 |
Minimum of Months | 0.00 | 0.319125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 3993989.21 | 0.166825E+10 | 104724.71 | 6525456.85 | 2322814.33 | 32626681.70 | 0.558585E+09 | 2148.85 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.148027E+09 | 0.254058E+09 | 190450.43 | 3093430.25 | 81899111.38 | 32751822.83 | 0.388700E+09 | 7229.02 | 0.36 |
February | 83786018.90 | 0.242326E+09 | 176754.53 | 3103687.51 | 78972836.15 | 46646971.38 | 0.230655E+09 | 5550.67 | 0.35 |
March | 84257398.05 | 0.386589E+09 | 42860.65 | 2580859.25 | 97409718.92 | 10881275.91 | 0.238685E+09 | 472.68 | 0.35 |
April | 20280128.94 | 0.554618E+09 | 35844.87 | 1110441.90 | 0.101548E+09 | 5952.91 | 35410224.12 | 243.43 | 0.36 |
May | 0.00 | 0.116152E+10 | 141774.03 | 0.00 | 55996678.20 | 0.00 | 0.00 | 1333.92 | 0.36 |
June | 0.00 | 0.152716E+10 | 120497.42 | 0.00 | 21823695.57 | 0.00 | 0.00 | 664.37 | 0.35 |
July | 0.00 | 0.158817E+10 | 0.00 | 0.00 | 36341259.80 | 0.00 | 0.00 | 0.00 | 0.35 |
August | 0.00 | 0.164723E+10 | 56031.63 | 0.00 | 20845654.41 | 0.00 | 0.00 | 242.18 | 0.35 |
September | 0.00 | 0.146493E+10 | 58088.76 | 0.00 | 44135451.37 | 0.00 | 0.00 | 307.74 | 0.36 |
October | 0.00 | 0.123296E+10 | 160185.12 | 0.00 | 59990103.89 | 0.00 | 0.00 | 2708.15 | 0.36 |
November | 38378731.44 | 0.837345E+09 | 361846.89 | 1254801.24 | 97311081.24 | 367066.33 | 0.109704E+09 | 8335.02 | 0.36 |
December | 0.112984E+09 | 0.395788E+09 | 418691.64 | 1865032.88 | 0.113542E+09 | 47934758.04 | 0.241727E+09 | 10743.97 | 0.36 |
Annual Sum or Average | 0.487713E+09 | 0.112927E+11 | 1763025.98 | 13008253.03 | 0.809815E+09 | 0.138588E+09 | 0.124488E+10 | 37831.16 | 0.36 |
Minimum of Months | 0.00 | 0.242326E+09 | 0.00 | 0.00 | 20845654.41 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.148027E+09 | 0.164723E+10 | 418691.64 | 3103687.51 | 0.113542E+09 | 47934758.04 | 0.388700E+09 | 10743.97 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105017E+11 | 0.00 | 0.00 | 0.00 | 0.285429E+10 | 0.00 | 0.00 | 0.00 | 0.46 |
February | 0.675972E+10 | 0.00 | 0.00 | 0.00 | 0.322540E+10 | 0.00 | 0.00 | 0.00 | 0.46 |
March | 0.614783E+10 | 0.00 | 0.00 | 0.00 | 0.557718E+10 | 0.00 | 0.00 | 0.00 | 0.46 |
April | 0.183867E+10 | 0.103594E+09 | 0.00 | 9221.64 | 0.626057E+10 | 0.00 | 16432318.73 | 0.00 | 0.46 |
May | 16305182.83 | 0.836925E+09 | 0.00 | 0.00 | 0.123515E+11 | 0.00 | 0.00 | 0.00 | 0.46 |
June | 0.00 | 0.455535E+10 | 0.00 | 0.00 | 0.128535E+11 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.870407E+10 | 0.00 | 0.00 | 0.103197E+11 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.655666E+10 | 0.00 | 0.00 | 0.127047E+11 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.806774E+10 | 0.00 | 0.00 | 0.941093E+10 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 25381467.17 | 0.384319E+10 | 0.00 | 74427.06 | 0.103975E+11 | 0.00 | 2898006.22 | 0.00 | 0.46 |
November | 0.286566E+10 | 0.429968E+09 | 0.00 | 0.00 | 0.912663E+10 | 0.00 | 0.00 | 0.00 | 0.46 |
December | 0.797539E+10 | 2887639.50 | 0.00 | 0.00 | 0.558046E+10 | 0.00 | 0.00 | 0.00 | 0.46 |
Annual Sum or Average | 0.361306E+11 | 0.331004E+11 | 0.00 | 83648.70 | 0.100662E+12 | 0.00 | 19330324.95 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.285429E+10 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.105017E+11 | 0.870407E+10 | 0.00 | 74427.06 | 0.128535E+11 | 0.00 | 16432318.73 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1229944.86 | 83474269.04 | 55396.34 | 1266556.11 | 515143.29 | 17637786.38 | 0.123026E+09 | 3626.97 | 0.35 |
February | 1238988.98 | 79728986.59 | 9317.88 | 1168383.50 | 640472.17 | 14628669.69 | 74022478.34 | 1038.23 | 0.35 |
March | 3309822.70 | 0.120964E+09 | 51146.67 | 1041756.09 | 6753.42 | 12474527.63 | 67284806.28 | 3302.81 | 0.35 |
April | 0.00 | 0.164007E+09 | 59218.45 | 406459.14 | 0.00 | 14741.19 | 13782150.76 | 3836.61 | 0.35 |
May | 0.00 | 0.304241E+09 | 204304.96 | 0.00 | 0.00 | 0.00 | 0.00 | 5055.27 | 0.36 |
June | 0.00 | 0.387128E+09 | 188350.97 | 0.00 | 0.00 | 0.00 | 0.00 | 4123.84 | 0.35 |
July | 0.00 | 0.406087E+09 | 87291.14 | 0.00 | 0.00 | 0.00 | 0.00 | 1119.73 | 0.35 |
August | 0.00 | 0.416779E+09 | 204990.66 | 0.00 | 94230.97 | 0.00 | 0.00 | 3891.33 | 0.35 |
September | 0.00 | 0.377173E+09 | 149307.59 | 0.00 | 0.00 | 0.00 | 0.00 | 2929.30 | 0.36 |
October | 0.00 | 0.323008E+09 | 301222.17 | 0.00 | 0.00 | 0.00 | 0.00 | 5807.01 | 0.36 |
November | 159694.65 | 0.233535E+09 | 176823.37 | 423655.38 | 67603.64 | 6258826.23 | 30588275.19 | 4147.57 | 0.35 |
December | 491952.51 | 0.127053E+09 | 35920.99 | 913514.27 | 364684.03 | 20265400.91 | 79468585.50 | 1670.52 | 0.35 |
Annual Sum or Average | 6430403.71 | 0.302318E+10 | 1523291.21 | 5220324.49 | 1688887.53 | 71279952.03 | 0.388172E+09 | 40549.18 | 0.35 |
Minimum of Months | 0.00 | 79728986.59 | 9317.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1038.23 | 0.35 |
Maximum of Months | 3309822.70 | 0.416779E+09 | 301222.17 | 1266556.11 | 640472.17 | 20265400.91 | 0.123026E+09 | 5807.01 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 37625840.12 | 63221017.52 | 126587.33 | 427607.78 | 20684502.82 | 35048983.15 | 70040583.16 | 6480.48 | 0.36 |
February | 21105021.92 | 60498407.39 | 86662.80 | 582302.11 | 19779915.35 | 18820715.33 | 50539812.31 | 5411.66 | 0.35 |
March | 21531401.57 | 96564272.13 | 70034.40 | 459795.78 | 24372913.60 | 13854859.29 | 48255001.24 | 3407.61 | 0.35 |
April | 5070032.23 | 0.138141E+09 | 81222.98 | 227723.60 | 25824308.23 | 7045.88 | 8896885.24 | 3848.66 | 0.36 |
May | 0.00 | 0.290112E+09 | 132198.50 | 0.00 | 14167110.56 | 0.00 | 0.00 | 2951.05 | 0.36 |
June | 0.00 | 0.381674E+09 | 142402.57 | 0.00 | 5455923.89 | 0.00 | 0.00 | 3083.27 | 0.35 |
July | 0.00 | 0.396984E+09 | 57485.94 | 0.00 | 9085314.95 | 0.00 | 0.00 | 1206.28 | 0.35 |
August | 0.00 | 0.411482E+09 | 242199.32 | 0.00 | 5305633.54 | 0.00 | 0.00 | 3948.26 | 0.35 |
September | 0.00 | 0.365971E+09 | 225482.58 | 0.00 | 11080529.48 | 0.00 | 0.00 | 4459.45 | 0.36 |
October | 0.00 | 0.307827E+09 | 418653.31 | 0.00 | 15021704.51 | 0.00 | 0.00 | 10237.90 | 0.36 |
November | 9710865.24 | 0.208853E+09 | 394343.99 | 175456.69 | 24496435.57 | 8158754.84 | 19380989.16 | 12683.25 | 0.36 |
December | 28126893.57 | 99190840.28 | 214677.05 | 312620.94 | 28027745.35 | 31268614.30 | 41419474.42 | 6653.64 | 0.36 |
Annual Sum or Average | 0.123170E+09 | 0.282052E+10 | 2191950.77 | 2185506.89 | 0.203302E+09 | 0.107159E+09 | 0.238533E+09 | 64371.52 | 0.36 |
Minimum of Months | 0.00 | 60498407.39 | 57485.94 | 0.00 | 5305633.54 | 0.00 | 0.00 | 1206.28 | 0.35 |
Maximum of Months | 37625840.12 | 0.411482E+09 | 418653.31 | 582302.11 | 28027745.35 | 35048983.15 | 70040583.16 | 12683.25 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2870518.66 | 0.537908E+09 | 110876.12 | 12937877.34 | 1945187.19 | 580991.67 | 0.903339E+09 | 4291.48 | 0.40 |
February | 0.00 | 0.513285E+09 | 83096.22 | 9642997.03 | 3029533.78 | 21551862.81 | 0.553810E+09 | 1833.34 | 0.40 |
March | 2484818.39 | 0.777350E+09 | 168811.14 | 7071424.20 | 0.00 | 2663995.39 | 0.528149E+09 | 3349.75 | 0.40 |
April | 0.00 | 0.105357E+10 | 492905.79 | 2205389.47 | 0.00 | 191308.96 | 88852579.30 | 5723.27 | 0.40 |
May | 0.00 | 0.195554E+10 | 394489.96 | 0.00 | 0.00 | 0.00 | 0.00 | 3329.20 | 0.40 |
June | 0.00 | 0.248824E+10 | 93872.16 | 0.00 | 0.00 | 0.00 | 0.00 | 406.22 | 0.40 |
July | 0.00 | 0.260947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.267131E+10 | 265597.65 | 0.00 | 7961700.15 | 0.00 | 0.00 | 2980.33 | 0.40 |
September | 0.00 | 0.242348E+10 | 641679.10 | 0.00 | 0.00 | 0.00 | 0.00 | 5736.63 | 0.40 |
October | 0.00 | 0.207664E+10 | 493957.02 | 0.00 | 0.00 | 0.00 | 0.00 | 4703.34 | 0.40 |
November | 892921.49 | 0.150158E+10 | 0.00 | 3859820.58 | 362310.23 | 204156.16 | 0.235515E+09 | 0.00 | 0.40 |
December | 1485132.91 | 0.816957E+09 | 51053.41 | 9534626.57 | 1823065.68 | 857929.23 | 0.637892E+09 | 1015.88 | 0.40 |
Annual Sum or Average | 7733391.45 | 0.194253E+11 | 2796338.58 | 45252135.20 | 15121797.02 | 26050244.22 | 0.294756E+10 | 33369.44 | 0.40 |
Minimum of Months | 0.00 | 0.513285E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 2870518.66 | 0.267131E+10 | 641679.10 | 12937877.34 | 7961700.15 | 21551862.81 | 0.903339E+09 | 5736.63 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.715373E+09 | 0.595153E+10 | 0.00 | 45084108.97 | 0.126271E+09 | 0.00 | 0.216119E+11 | 0.00 | 4.64 |
February | 0.297423E+09 | 0.677653E+10 | 0.00 | 39127865.25 | 0.141006E+09 | 0.00 | 0.144288E+11 | 0.00 | 4.72 |
March | 0.484018E+09 | 0.122780E+11 | 0.00 | 34025078.68 | 0.132055E+09 | 0.00 | 0.129565E+11 | 0.00 | 4.79 |
April | 23458752.10 | 0.140062E+11 | 0.00 | 21451932.56 | 90877309.55 | 0.00 | 0.433714E+10 | 0.00 | 4.90 |
May | 0.00 | 0.299396E+11 | 0.00 | 1419925.04 | 37240023.16 | 0.00 | 42710861.07 | 0.00 | 5.04 |
June | 0.00 | 0.404203E+11 | 0.00 | 0.00 | 3804813.93 | 0.00 | 0.00 | 0.00 | 5.10 |
July | 0.00 | 0.438113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.04 |
August | 0.00 | 0.441136E+11 | 0.00 | 0.00 | 20246337.95 | 0.00 | 0.00 | 0.00 | 5.05 |
September | 0.00 | 0.398613E+11 | 0.00 | 0.00 | 38760070.14 | 0.00 | 0.00 | 0.00 | 5.01 |
October | 0.00 | 0.319751E+11 | 0.00 | 2275087.42 | 0.100258E+09 | 0.00 | 68569855.78 | 0.00 | 4.94 |
November | 67687426.07 | 0.210715E+11 | 0.00 | 17400524.11 | 0.148363E+09 | 0.00 | 0.613771E+10 | 0.00 | 4.82 |
December | 0.578424E+09 | 0.121978E+11 | 0.00 | 36507541.01 | 85634166.25 | 0.00 | 0.165223E+11 | 0.00 | 4.68 |
Annual Sum or Average | 0.216638E+10 | 0.302403E+12 | 0.00 | 0.197292E+09 | 0.924517E+09 | 0.00 | 0.761057E+11 | 0.00 | 4.89 |
Minimum of Months | 0.00 | 0.595153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.64 |
Maximum of Months | 0.715373E+09 | 0.441136E+11 | 0.00 | 45084108.97 | 0.148363E+09 | 0.00 | 0.216119E+11 | 0.00 | 5.10 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.376526E+09 | 0.645366E+10 | 0.00 | 54144949.96 | 31135960.08 | 0.00 | 0.236436E+11 | 0.00 | 4.96 |
February | 0.147150E+09 | 0.736080E+10 | 0.00 | 46167681.77 | 23057159.12 | 0.00 | 0.156530E+11 | 0.00 | 5.04 |
March | 0.304672E+09 | 0.132304E+11 | 0.00 | 40224943.17 | 20424441.12 | 0.00 | 0.141177E+11 | 0.00 | 5.12 |
April | 13512968.71 | 0.149792E+11 | 0.00 | 23413427.50 | 10407662.61 | 0.00 | 0.462143E+10 | 0.00 | 5.22 |
May | 0.00 | 0.318085E+11 | 0.00 | 1499949.59 | 2090871.57 | 0.00 | 45090156.12 | 0.00 | 5.34 |
June | 0.00 | 0.427844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 |
July | 0.00 | 0.463750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 |
August | 0.00 | 0.467180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.34 |
September | 0.00 | 0.422171E+11 | 0.00 | 0.00 | 1205939.02 | 0.00 | 0.00 | 0.00 | 5.29 |
October | 0.00 | 0.339426E+11 | 0.00 | 2442906.61 | 12853004.80 | 0.00 | 72101998.80 | 0.00 | 5.22 |
November | 40568809.09 | 0.225225E+11 | 0.00 | 20324035.65 | 32642912.43 | 0.00 | 0.660965E+10 | 0.00 | 5.13 |
December | 0.316921E+09 | 0.130948E+11 | 0.00 | 43265423.99 | 20131709.93 | 0.00 | 0.180418E+11 | 0.00 | 5.01 |
Annual Sum or Average | 0.119935E+10 | 0.321487E+12 | 0.00 | 0.231483E+09 | 0.153950E+09 | 0.00 | 0.828044E+11 | 0.00 | 5.20 |
Minimum of Months | 0.00 | 0.645366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.96 |
Maximum of Months | 0.376526E+09 | 0.467180E+11 | 0.00 | 54144949.96 | 32642912.43 | 0.00 | 0.236436E+11 | 0.00 | 5.39 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.870830E+10 | 0.00 | 81426842.99 | 0.00 | 0.00 | 0.274007E+11 | 0.00 | 19.84 |
February | 0.00 | 0.972539E+10 | 0.00 | 65318768.32 | 0.00 | 0.00 | 0.170998E+11 | 0.00 | 19.92 |
March | 0.00 | 0.162954E+11 | 0.00 | 57734306.87 | 0.00 | 0.00 | 0.159221E+11 | 0.00 | 19.98 |
April | 0.00 | 0.190657E+11 | 0.00 | 25526906.47 | 0.00 | 0.00 | 0.452430E+10 | 0.00 | 20.05 |
May | 0.00 | 0.393470E+11 | 0.00 | 1023988.69 | 0.00 | 0.00 | 32791462.28 | 0.00 | 20.07 |
June | 0.00 | 0.520538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.01 |
July | 0.00 | 0.568676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.80 |
August | 0.00 | 0.573769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.94 |
September | 0.00 | 0.519409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.88 |
October | 0.00 | 0.420745E+11 | 0.00 | 2433379.17 | 0.00 | 0.00 | 67127157.48 | 0.00 | 19.88 |
November | 0.00 | 0.284934E+11 | 0.00 | 29566612.15 | 0.00 | 0.00 | 0.735093E+10 | 0.00 | 19.87 |
December | 0.00 | 0.162796E+11 | 0.00 | 62837949.90 | 0.00 | 0.00 | 0.208238E+11 | 0.00 | 19.75 |
Annual Sum or Average | 0.00 | 0.398228E+12 | 0.00 | 0.325869E+09 | 0.00 | 0.00 | 0.932215E+11 | 0.00 | 19.91 |
Minimum of Months | 0.00 | 0.870830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.75 |
Maximum of Months | 0.00 | 0.573769E+11 | 0.00 | 81426842.99 | 0.00 | 0.00 | 0.274007E+11 | 0.00 | 20.07 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.616190E+10 | 85665692.19 | 0.00 | 0.00 | 0.158910E+10 | 0.00 | 0.00 | 0.00 | 1.03 |
February | 0.396532E+10 | 0.110711E+09 | 0.00 | 3327.29 | 0.178180E+10 | 0.00 | 969402.46 | 0.00 | 1.03 |
March | 0.360586E+10 | 0.186258E+09 | 0.00 | 9223.97 | 0.308617E+10 | 0.00 | 1389414.26 | 0.00 | 1.03 |
April | 0.104542E+10 | 0.141074E+10 | 0.00 | 67842.77 | 0.234371E+10 | 0.00 | 43007429.06 | 0.00 | 1.03 |
May | 7821971.24 | 0.481619E+10 | 0.00 | 5355.14 | 0.298755E+10 | 0.00 | 1739790.22 | 0.00 | 1.03 |
June | 0.00 | 0.925819E+10 | 0.00 | 0.00 | 0.131418E+10 | 0.00 | 0.00 | 0.00 | 1.04 |
July | 0.00 | 0.110084E+11 | 0.00 | 0.00 | 0.916774E+09 | 0.00 | 0.00 | 0.00 | 1.07 |
August | 0.00 | 0.956169E+10 | 0.00 | 0.00 | 0.214354E+10 | 0.00 | 0.00 | 0.00 | 1.05 |
September | 0.00 | 0.898142E+10 | 0.00 | 0.00 | 0.174538E+10 | 0.00 | 0.00 | 0.00 | 1.05 |
October | 14385131.01 | 0.565100E+10 | 0.00 | 49915.35 | 0.283763E+10 | 0.00 | 2201692.67 | 0.00 | 1.03 |
November | 0.168017E+10 | 0.213832E+10 | 0.00 | 761.14 | 0.347569E+10 | 0.00 | 1263567.30 | 0.00 | 1.02 |
December | 0.467639E+10 | 0.501143E+09 | 0.00 | 14633.80 | 0.277490E+10 | 0.00 | 3174634.45 | 0.00 | 1.03 |
Annual Sum or Average | 0.211573E+11 | 0.537098E+11 | 0.00 | 151059.45 | 0.269964E+11 | 0.00 | 53745930.42 | 0.00 | 1.04 |
Minimum of Months | 0.00 | 85665692.19 | 0.00 | 0.00 | 0.916774E+09 | 0.00 | 0.00 | 0.00 | 1.02 |
Maximum of Months | 0.616190E+10 | 0.110084E+11 | 0.00 | 67842.77 | 0.347569E+10 | 0.00 | 43007429.06 | 0.00 | 1.07 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.195133E+12 | 0.543145E+09 | 0.281221E+11 | 0.116793E+12 | 0.665432E+12 |
February | 0.225122E+12 | -98879836.8 | 0.862764E+10 | 0.392893E+11 | 0.714464E+12 |
March | 0.313601E+12 | -660896716.9 | -0.928254E+10 | -0.567922E+11 | 0.890241E+12 |
April | 0.336752E+12 | -0.139031E+10 | -0.458984E+11 | -0.211756E+12 | 0.105525E+13 |
May | 0.332676E+12 | -0.286046E+10 | -0.129038E+12 | -0.571351E+12 | 0.137471E+13 |
June | 0.292200E+12 | -0.368215E+10 | -0.178640E+12 | -0.798755E+12 | 0.150421E+13 |
July | 0.306365E+12 | -0.393259E+10 | -0.196835E+12 | -0.846485E+12 | 0.160316E+13 |
August | 0.335644E+12 | -0.397742E+10 | -0.196382E+12 | -0.866954E+12 | 0.159158E+13 |
September | 0.251019E+12 | -0.362442E+10 | -0.176811E+12 | -0.772015E+12 | 0.152259E+13 |
October | 0.240141E+12 | -0.300849E+10 | -0.137990E+12 | -0.614253E+12 | 0.143497E+13 |
November | 0.178654E+12 | -0.164305E+10 | -0.741835E+11 | -0.318730E+12 | 0.112699E+13 |
December | 0.192935E+12 | -177209445.7 | -0.126003E+10 | -0.104270E+11 | 0.828524E+12 |
Annual Sum or Average | 0.320024E+13 | -0.245127E+11 | -0.110957E+13 | -0.491143E+13 | 0.143121E+14 |
Minimum of Months | 0.178654E+12 | -0.397742E+10 | -0.196835E+12 | -0.866954E+12 | 0.665432E+12 |
Maximum of Months | 0.336752E+12 | 0.543145E+09 | 0.281221E+11 | 0.116793E+12 | 0.160316E+13 |