Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2023-10-16 09:02:47
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10251.70 | 903.61 | 903.61 |
Net Site Energy | 10251.70 | 903.61 | 903.61 |
Total Source Energy | 27277.82 | 2404.33 | 2404.33 |
Net Source Energy | 27277.82 | 2404.33 | 2404.33 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3017.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 604.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 174.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 641.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 631.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 168.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 454.86 | 682.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 44.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 7760.43 | 2491.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 3017.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 604.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 174.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 952.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 22.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 631.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 168.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.75 | 682.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Other | 364.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 21.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3017.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 604.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 174.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 641.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 631.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 168.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 295.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 454.86 | 682.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 44.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 376.57 | 61.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 238.77 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 684.02 | 219.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 376.57 | 61.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 238.77 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 684.02 | 219.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 7760.430 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 7760.430 | 100.00 |
Total On-Site and Utility Electric Sources | 7760.430 | 100.00 |
Total Electricity End Uses | 7760.430 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 2745.64 | 91.12 |
Air to Air Heat Recovery for Heating | 267.69 | 8.88 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 3013.33 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 67.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7967.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYSLAUNDRY HPWH TANK | SWHSYS1 HPWH TANK |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| SWHSYS1 HPWH FAN | SWHSYSLAUNDRY HPWH FAN | FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 6.6442 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 9.6995 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 9.6995 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 4.0903 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.7049 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 9.2569 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 9.0417 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 4.4132 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.4132 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.7327 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 4.4132 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8432 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8432 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.6442 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 4.0903 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.7049 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 9.2569 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 9.0417 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 4.4132 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.4132 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.7327 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 4.4132 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.8432 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.8432 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.6992 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 09-JUN-19:19 | 02-JAN-19:19 | - | - | - | - | - | - | - | - | - | - | 12-JAN-21:19 |
Heating | 0.00 | 19142.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 253441.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 50471.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 87982.85 | 87619.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31577.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 39567.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 7157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 37492.60 | 68843.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1342.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 530068.81 | 175605.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 19142.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 253441.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 50471.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58308.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1273.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 39567.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 7157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3979.85 | 68843.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 431.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 669.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 22.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 9557.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1915.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 552.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5473.02 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2031.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1998.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 533.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 934.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1440.55 | 739.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 140.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 24577.28 | 2700.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 842.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 46.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 82.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 126.97 | 65.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2166.30 | 238.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 842.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 46.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 82.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 126.97 | 65.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2166.30 | 238.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.30 | 0.656547 | 0.526000 | 1.21 | 1.00 | 0.500000 | 0.000580 | 0.000054 | 1.21 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.339822 | 0.150397 | 0.526000 | 0.178746 | 0.526000 | 0.500000 | 0.002533 | 0.000023 | 0.178746 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.241220 | 0.245352 | 0.526000 | 0.126882 | 0.654271 | 0.500000 | 0.001553 | 0.000010 | 0.126882 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.240776 | 0.519790 | 0.526000 | 0.126648 | 1.00 | 0.500000 | 0.000733 | 0.000014 | 0.126648 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.131671 | 0.548387 | 0.526000 | 0.069259 | 1.00 | 0.500000 | 0.000695 | 0.000008 | 0.069259 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.37 | 0.070015 | 0.526000 | 1.77 | 0.526000 | 0.500000 | 0.021594 | 0.000091 | 1.77 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.44 | 0.100008 | 0.526000 | 0.756922 | 0.526000 | 0.500000 | 0.003810 | 0.000071 | 0.756922 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.85 | 0.205342 | 0.526000 | 2.55 | 0.547579 | 0.500000 | 0.001855 | 0.000199 | 2.55 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.38 | 0.861472 | 0.526000 | 0.724704 | 1.00 | 0.500000 | 0.000442 | 0.000084 | 0.724704 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.35 | 0.107623 | 0.526000 | 1.24 | 0.526000 | 0.500000 | 0.003540 | 0.000093 | 1.24 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.46 | 0.102839 | 0.526000 | 1.29 | 0.526000 | 0.500000 | 0.003705 | 0.000097 | 1.29 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.26 | 0.062568 | 0.526000 | 1.19 | 0.526000 | 0.500000 | 0.010952 | 0.000064 | 1.19 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.829062 | 0.378788 | 0.526000 | 0.436087 | 1.00 | 0.500000 | 0.001006 | 0.000061 | 0.436087 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 6217.53 | 0.000054 | 129.66 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 2588.57 | 0.000023 | 59.65 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1185.68 | 0.000010 | 25.82 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1626.84 | 0.000014 | 36.80 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 954.11 | 0.000008 | 21.81 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10420.70 | 0.000091 | 218.92 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 8118.88 | 0.000071 | 179.44 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 22781.93 | 0.000199 | 493.94 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 3640.94 | 0.000032 | 104.02 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 3640.71 | 0.000032 | 104.02 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 21400.81 | 0.000187 | 611.42 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 21406.87 | 0.000187 | 611.59 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 3644.49 | 0.000032 | 104.12 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 3644.26 | 0.000032 | 104.12 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 9649.41 | 0.000084 | 219.43 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1157.31 | 0.000010 | 33.06 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1157.23 | 0.000010 | 33.06 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 5624.20 | 0.000049 | 160.68 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 10668.87 | 0.000093 | 230.62 |
DINING_FLR_6 VAV BOX REHEAT COIL | 11055.92 | 0.000097 | 238.77 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7306.59 | 0.000064 | 153.90 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 6967.37 | 0.000061 | 163.33 |
VAV WITH REHEAT HEATING COIL | 81282.44 | 0.000711 | 1482.02 |
FLR_3_DOAS HEATING COIL | 7548.86 | 0.000066 | 137.64 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.03 | 0.000032 | 0.000399 |
ROOM_2_FLR_3 FAN COIL | 1.03 | 0.000032 | 0.000401 |
ROOM_3_MULT19_FLR_3 FAN COIL | 6.05 | 0.000187 | 0.002304 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.99 | 0.000187 | 0.002818 |
ROOM_5_FLR_3 FAN COIL | 0.924960 | 0.000032 | 0.000361 |
ROOM_6_FLR_3 FAN COIL | 0.926617 | 0.000032 | 0.000361 |
ROOM_1_FLR_6 FAN COIL | 0.279123 | 0.000010 | 0.000108 |
ROOM_2_FLR_6 FAN COIL | 0.280030 | 0.000010 | 0.000109 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.30 | 0.000049 | 0.000512 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.03 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.03 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.05 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.99 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 0.924960 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.926617 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.279123 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.280030 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.30 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008577 | 12.80 | 0.008500 | 0.000399 | 1.03 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008577 | 12.80 | 0.008500 | 0.000401 | 1.03 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008503 | 12.80 | 0.008500 | 0.002304 | 6.05 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008708 | 12.80 | 0.008500 | 0.002818 | 6.99 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008585 | 12.80 | 0.008500 | 0.000361 | 0.924960 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008585 | 12.80 | 0.008500 | 0.000361 | 0.926617 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008571 | 12.80 | 0.008500 | 0.000108 | 0.279123 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008571 | 12.80 | 0.008500 | 0.000109 | 0.280030 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.70 | 6.70 | 0.008634 | 12.80 | 0.008500 | 0.000512 | 1.30 | |
VAV WITH REHEAT COOLING COIL | 33.50 | 6.70 | 0.009395 | 10.93 | 0.008500 | 0.023451 | 22.09 | 656561.51 |
FLR_3_DOAS COOLING COIL | 42.00 | 6.70 | 0.009158 | 11.91 | 0.008500 | 0.002787 | 2.05 | 78036.98 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.67 | 11.67 | 22.19 | 11.67 | 22.09 | 22.09 | 0.300000 | 0.528424 | 22.09 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 22.09 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 22.09 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.023451 | 0.000020 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.000711 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002787 | 0.000171 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000066 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Size Rated Evaporator Air Flow Rate [m3/s] | Design Size Rated Condenser Water Flow Rate [m3/s] | |
SWHSYSLAUNDRY HPWH DXCOIL | 4.90 | 0.004370 |
SWHSYS1 HPWH DXCOIL | 3.87 | 0.003451 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
SWHSYSLAUNDRY HPWH FAN | 4.90 | 700.51 |
SWHSYS1 HPWH FAN | 3.87 | 553.22 |
Condenser water flow rate [m3/s] | Evaporator air flow rate [m3/s] | |
SWHSYS1 HPWH | 0.003451 | 3.87 |
SWHSYSLAUNDRY HPWH | 0.004370 | 4.90 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.033612 | 6857.53 | |
HEATSYS1 PUMP | 0.002219 | 661.77 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.002219 | 0.266327 |
COOLSYS1 | 0.033612 | 4.03 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 253690.50 | 253690.50 | 0.002219 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.033612 | 4747.70 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.033612 | 941035.14 | 941649.76 | 107.35 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 HPWH TANK | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 6.644 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.024 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 4.090 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.780 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.705 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.235 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 9.257 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.637 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 9.042 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.112 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.733 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2943.236 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 13147.704 | 6.644 | 123.454 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13147.704 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 650.557 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 650.557 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 753.347 | 9.699 | 60.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 753.347 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 387.592 | 4.090 | 189.996 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 387.592 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 445.205 | 5.705 | 53.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 445.205 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1748.285 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1748.285 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 11828.200 | 9.042 | 28.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11828.200 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 108.229 | 4.413 | 72.152 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.229 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1718.521 | 4.413 | 82.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1718.521 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1212.035 | 11.733 | 54.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1212.035 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1818.789 | 4.413 | 82.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1818.789 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 1.287 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.608 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.684 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.608 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.684 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.4124 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.4124 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6100 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4545 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4264 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4545 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4264 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.165 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.165 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
21 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
22 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
23 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | 0.16691074E-14 | 0.45207920E-16 | -0.13282787E-09 | -0.59403108E-17 |
29 | 8 | 0.19494068E-07 | 0.16957001E-12 | 0.35230437E-03 | -0.22165426E-09 |
30 | 7 | -0.11479370E-01 | 0.90467759E-08 | -0.21987867E-01 | 0.13052461E-03 |
31 | 6 | 0.38463807 | 0.31869432E-05 | 0.45441076 | -0.45036152E-02 |
32 | 5 | -4.9884079 | 0.12028467E-03 | -4.3052891 | 0.60677235E-01 |
33 | 4 | 32.108494 | 0.99355415E-03 | 20.908458 | -0.41024850 |
34 | 3 | -109.32288 | 0.21841230E-02 | -54.572312 | 1.4876971 |
35 | 2 | 195.24423 | 0.12380226E-02 | 76.910992 | -2.8707534 |
36 | 1 | -170.46733 | 0.13310261E-03 | -54.975783 | 2.7333683 |
37 | 0 | 57.057407 | 0.76355891E-06 | 15.605832 | |
38 | 9 | 0.14115123E-14 | 0.53960859E-16 | -0.11739578E-09 | -0.22900007E-17 |
39 | 8 | 0.17311930E-07 | 0.20639465E-12 | 0.32798840E-03 | -0.19684260E-09 |
40 | 7 | -0.10748946E-01 | 0.11327704E-07 | -0.20934514E-01 | 0.12221941E-03 |
41 | 6 | 0.36478417 | 0.40360747E-05 | 0.43737925 | -0.42695883E-02 |
42 | 5 | -4.7945715 | 0.15382307E-03 | -4.1739388 | 0.58273831E-01 |
43 | 4 | 31.250576 | 0.12816568E-02 | 20.393829 | -0.39885853 |
44 | 3 | -107.49604 | 0.28390629E-02 | -53.554356 | 1.4613070 |
45 | 2 | 193.43186 | 0.16201491E-02 | 75.979619 | -2.8419759 |
46 | 1 | -169.79719 | 0.17527083E-03 | -54.709122 | 2.7216233 |
47 | 0 | 57.057407 | 0.10123612E-05 | 15.653272 | |
48 | 9 | 0.65135446E-15 | 0.56204292E-16 | -0.11372497E-09 | -0.53489081E-17 |
49 | 8 | 0.16791160E-07 | 0.21454591E-12 | 0.32203280E-03 | -0.19092129E-09 |
50 | 7 | -0.10569524E-01 | 0.11862766E-07 | -0.20675571E-01 | 0.12017931E-03 |
51 | 6 | 0.35990649 | 0.42391557E-05 | 0.43318136 | -0.42120931E-02 |
52 | 5 | -4.7469406 | 0.16196889E-03 | -4.1415055 | 0.57683257E-01 |
53 | 4 | 31.039704 | 0.13525358E-02 | 20.266625 | -0.39605902 |
54 | 3 | -107.04684 | 0.30019179E-02 | -53.302690 | 1.4548183 |
55 | 2 | 192.98603 | 0.17160237E-02 | 75.749609 | -2.8348971 |
56 | 1 | -169.63227 | 0.18593554E-03 | -54.643729 | 2.7187328 |
57 | 0 | 57.057407 | 0.10758168E-05 | 15.665287 | |
58 | 9 | 0.14115123E-14 | 0.53960859E-16 | -0.11739578E-09 | -0.22900007E-17 |
59 | 8 | 0.17311930E-07 | 0.20639465E-12 | 0.32798840E-03 | -0.19684260E-09 |
60 | 7 | -0.10748946E-01 | 0.11327704E-07 | -0.20934514E-01 | 0.12221941E-03 |
61 | 6 | 0.36478417 | 0.40360747E-05 | 0.43737925 | -0.42695883E-02 |
62 | 5 | -4.7945715 | 0.15382307E-03 | -4.1739388 | 0.58273831E-01 |
63 | 4 | 31.250576 | 0.12816568E-02 | 20.393829 | -0.39885853 |
64 | 3 | -107.49604 | 0.28390629E-02 | -53.554356 | 1.4613070 |
65 | 2 | 193.43186 | 0.16201491E-02 | 75.979619 | -2.8419759 |
66 | 1 | -169.79719 | 0.17527083E-03 | -54.709122 | 2.7216233 |
67 | 0 | 57.057407 | 0.10123612E-05 | 15.653272 | |
68 | 9 | 0.65135446E-15 | 0.56204292E-16 | -0.11372497E-09 | -0.53489081E-17 |
69 | 8 | 0.16791160E-07 | 0.21454591E-12 | 0.32203280E-03 | -0.19092129E-09 |
70 | 7 | -0.10569524E-01 | 0.11862766E-07 | -0.20675571E-01 | 0.12017931E-03 |
71 | 6 | 0.35990649 | 0.42391557E-05 | 0.43318136 | -0.42120931E-02 |
72 | 5 | -4.7469406 | 0.16196889E-03 | -4.1415055 | 0.57683257E-01 |
73 | 4 | 31.039704 | 0.13525358E-02 | 20.266625 | -0.39605902 |
74 | 3 | -107.04684 | 0.30019179E-02 | -53.302690 | 1.4548183 |
75 | 2 | 192.98603 | 0.17160237E-02 | 75.749609 | -2.8348971 |
76 | 1 | -169.63227 | 0.18593554E-03 | -54.643729 | 2.7187328 |
77 | 0 | 57.057407 | 0.10758168E-05 | 15.665287 | |
78 | 7 | -0.10696287E-14 | 0.39031946E-16 | -0.22096194E-13 | 0.53014468E-15 |
79 | 6 | 0.18597363E-10 | 0.52355087E-11 | 0.51921923E-09 | -0.18483703E-10 |
80 | 5 | -0.10208356E-06 | 0.25520809E-07 | -0.21786771E-05 | 0.17041956E-06 |
81 | 4 | 0.13587196E-03 | 0.96408156E-05 | 0.17589348E-02 | -0.28090751E-03 |
82 | 3 | -0.20124247E-01 | 0.34048350E-03 | -0.21477792 | 0.43172268E-01 |
83 | 2 | 0.28586126 | 0.14813331E-02 | 2.8938873 | -0.61762740 |
84 | 1 | -0.72340799 | 0.92453067E-03 | -7.1302655 | 1.5680075 |
85 | 0 | 0.46030979 | 0.18706506E-04 | 4.4521723 | |
86 | 7 | -0.22096194E-13 | 0.39031946E-16 | -0.10696287E-14 | 0.53014468E-15 |
87 | 6 | 0.51921923E-09 | 0.52355087E-11 | 0.18597363E-10 | -0.18483703E-10 |
88 | 5 | -0.21786771E-05 | 0.25520809E-07 | -0.10208356E-06 | 0.17041956E-06 |
89 | 4 | 0.17589348E-02 | 0.96408156E-05 | 0.13587196E-03 | -0.28090751E-03 |
90 | 3 | -0.21477792 | 0.34048350E-03 | -0.20124247E-01 | 0.43172268E-01 |
91 | 2 | 2.8938873 | 0.14813331E-02 | 0.28586126 | -0.61762740 |
92 | 1 | -7.1302655 | 0.92453067E-03 | -0.72340799 | 1.5680075 |
93 | 0 | 4.4521723 | 0.18706506E-04 | 0.46030979 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5095_SHGC_0.23 | 37 | 1 | VerySmooth | 2.897 | 2.897 | 1.000 | 0.231 | ||
2 | RESWINDOW_U_0.5095_SHGC_0.23 | 38 | 1 | VerySmooth | 2.897 | 2.897 | 1.000 | 0.231 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 1.83516E-002 | 0.14129 | 0.62979 | 0.62979 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10484 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 1.83516E-002 | 0.14129 | 0.62979 | 0.62979 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10484 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | "DX Coil Total Cooling Rate {W | HPWH Only}" | |
1 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | 1.1400 | 76996.7 | 48.891 | 1.7197 | 76621 | |
2 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | 2.8400 | 62640.0 | 4.641 | 9.4598 | 53264 |
Node Number | Height {m} | Volume {m3} | Maximum Capacity {W} | Off-Cycle UA {W/K} | On-Cycle UA {W/K} | Number Of Inlets | Number Of Outlets | |
1 | 1 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 0 | 1 |
2 | 2 | 0.2683 | 0.4733 | 26898.690 | 1.5573 | 1.5573 | 0 | 0 |
3 | 3 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
4 | 4 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
5 | 5 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 1 |
6 | 6 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 2 | 0 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 9.802E-003 | 1.461E-004 | 7.212E-005 | 0.133 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 3.784E-003 | 4.872E-005 | 1.327E-004 | 4.426E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 8.942E-003 | 5.445E-005 | 1.424E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 5.159E-003 | 5.445E-005 | 1.182E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 1.221E-002 | 1.565E-004 | 1.392E-004 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 2.167E-002 | 1.147E-004 | 6.318E-005 | 0.104 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 6.191E-002 | 4.733E-005 | 9.051E-005 | 4.300E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.587E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.588E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 6.879E-003 | 1.766E-005 | 1.424E-004 | 2.086E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 2.910E-003 | 1.186E-004 | 6.472E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1.243E-002 | 1.204E-004 | 6.523E-005 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1.217E-002 | 2.953E-005 | 2.446E-005 | 3.488E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 7.2951E-002 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.9052E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 7.9809E-002 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.0485E-002 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 5.7644E-002 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.0250E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.4391E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.0788E-003 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 8.1474E-002 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.6174E-002 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 8.9161E-002 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.8040E-002 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 6.3728E-002 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 2.5884E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 2.7408E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.1075E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.8518E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0446E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.4384E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 7.9481E-003 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.3586E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 5.4230E-003 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.4020E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 8.4927E-003 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.8518E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0446E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.4384E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 7.9481E-003 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.3586E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 5.4230E-003 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.4020E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 8.4927E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 30811.96670 | 30811.96670 | 2.29667 | 2.29667 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 21:10:00 | 36.13150 | 9.14812E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | 00:10:00 | 6.30000 | 6.07234E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 4558.61048 | 4558.61048 | 0.33982 | 0.33982 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 42.00000 | 9.15790E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 1668.71898 | 1668.71898 | 7.33773E-002 | 7.92179E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3235.83608 | 3235.83608 | 0.24122 | 0.24122 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:40:00 | 39.99533 | 9.15455E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 532.74728 | 532.74728 | 2.34261E-002 | 9.17347E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3230.59012 | 3230.59012 | 0.24078 | 0.24078 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:50:00 | 37.32783 | 9.15011E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 975.13032 | 975.13032 | 4.28787E-002 | 4.28787E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1766.66319 | 1766.66319 | 0.13167 | 0.13167 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:00:00 | 40.64200 | 9.15563E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 597.70927 | 597.70927 | 2.62827E-002 | 5.77652E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 45216.48407 | 45216.48407 | 3.37031 | 3.37031 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:50:00 | 39.83367 | 9.15428E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1298.40104 | 1298.40104 | 5.70935E-002 | 5.70935E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 19287.71104 | 19287.71104 | 1.43901 | 1.43901 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 42.00000 | 9.15790E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 4223.61861 | 4223.61861 | 0.18572 | 0.67639 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 65102.69112 | 65102.69112 | 4.85452 | 4.85452 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 41.90300 | 9.15774E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 9641.52094 | 9641.52094 | 0.42396 | 1.89399 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 10214.50804 | 10214.50804 | 1.02594 | 1.02594 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.15650E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 3640.94844 | 3640.94844 | 0.16104 | 0.16104 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10254.07444 | 10254.07444 | 1.02992 | 1.02992 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 41.03000 | 9.15628E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 3640.71381 | 3640.71381 | 0.16103 | 0.16103 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 60210.11072 | 60210.11072 | 6.04721 | 6.04721 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 41.80600 | 9.15758E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 21400.82920 | 21400.82920 | 0.94657 | 0.94657 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 69640.14016 | 69640.14016 | 6.99485 | 6.99485 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 41.03000 | 9.15628E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 21406.89729 | 21406.89729 | 0.94684 | 0.94684 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 9209.09380 | 9209.09380 | 0.92496 | 0.92496 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 39.52650 | 9.15377E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 3644.49775 | 3644.49775 | 0.16120 | 0.16120 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9225.58825 | 9225.58825 | 0.92662 | 0.92662 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 39.52650 | 9.15377E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 3644.26354 | 3644.26354 | 0.16119 | 0.16119 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 18484.47877 | 18484.47877 | 1.37776 | 1.37776 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.15650E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 5919.88816 | 5919.88816 | 0.26031 | 0.47476 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2779.00922 | 2779.00922 | 0.27912 | 0.27912 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.15650E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1157.31703 | 1157.31703 | 5.11888E-002 | 5.11888E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2788.04397 | 2788.04397 | 0.28003 | 0.28003 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.15650E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1157.23158 | 1157.23158 | 5.11850E-002 | 5.11850E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 12910.31533 | 12910.31533 | 1.29674 | 1.29674 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | 42.00000 | 9.15790E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 5624.20843 | 5624.20843 | 0.24876 | 0.24876 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 31465.75691 | 31465.75691 | 2.34822 | 2.34822 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | 42.00000 | 9.15790E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 4312.21487 | 4312.21487 | 0.18962 | 1.18780 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30000 | 6.07234E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 32930.03338 | 32930.03338 | 2.45746 | 2.45746 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | 42.00000 | 9.15790E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 4403.58804 | 4403.58804 | 0.19364 | 1.18780 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 6.30000 | 6.07234E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30279.77599 | 30279.77599 | 2.26288 | 2.26288 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | 41.12700 | 9.15644E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1203.40346 | 1203.40346 | 5.29105E-002 | 0.36735 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 6.30000 | 6.07234E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 11123.04019 | 11123.04019 | 0.82906 | 0.82906 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:40:00 | 42.00000 | 9.15790E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 4723.06450 | 4723.06450 | 0.20768 | 0.20768 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 6.30000 | 6.07234E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 539228.19 | 22.08760 | 22.08760 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 88060.86 | 7.17887 | 7.17887 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 70647.06 | 18.68961 | 2.05125 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 25161.97 | 2.88901 | 2.05125 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.29667 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.65655 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.20805 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.80309E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.43937E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20805 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6217.53343 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.43937E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 129.65594 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.33982 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15040 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17875 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52600 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.53329E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.26459E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17875 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2588.56609 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.26459E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 59.64512 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.24122 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24535 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12688 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65427 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.55287E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.03729E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12688 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1185.68277 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03729E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 25.82239 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.24078 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.51979 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12665 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.32988E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.42323E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12665 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1626.83932 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.42323E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 36.80073 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.13167 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.54839 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.92589E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.94765E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.34694E-006 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.92589E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 954.10597 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.34694E-006 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 21.80907 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.37031 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.00155E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.77278 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52600 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.15936E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.11648E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.77278 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10420.69504 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.11648E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 218.91874 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.43901 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10001 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.75692 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52600 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.80970E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.10275E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.75692 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8118.87759 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.10275E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 179.43656 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.85452 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20534 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.55348 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54758 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.85544E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.99306E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.55348 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22781.92932 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.99306E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 493.93764 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.02594 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.02594 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.18525E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.99023E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69786 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57695E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.99023E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.02594 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3640.94028 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.18525E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 104.02202 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.02992 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.02992 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.18505E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.00540E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69786 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57669E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.00540E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.02992 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3640.70566 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.18505E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 104.01531 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.04721 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.04721 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.87224E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.30443E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69832 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50299E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.30443E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.04721 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 21400.80612 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.87224E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 611.42100 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.99485 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.99485 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.87277E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.81830E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69747 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.70830E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.81830E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.99485 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 21406.87420 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.87277E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 611.59436 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.92496 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.92496 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.18836E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.60577E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69784 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58537E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.60577E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.92496 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3644.48959 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.18836E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 104.12342 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.92662 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.92662 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.18815E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.61211E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69785 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58526E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.61211E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.92662 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3644.25537 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.18815E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 104.11672 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.37776 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.86147 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.72470 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.42266E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.44173E-005 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.72470 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9649.41431 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.44173E-005 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 219.42738 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.27912 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.27912 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.01247E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.08377E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69787 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57079E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.08377E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.27912 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1157.31455 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.01247E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 33.06431 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.28003 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.28003 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.01239E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.08721E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69787 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57052E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.08721E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.28003 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1157.22909 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.01239E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 33.06187 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.29674 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.29674 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.92029E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.12261E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69759 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63435E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.12261E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.29674 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5624.19877 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.92029E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 160.68232 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.34822 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10762 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.23516 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52600 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.54013E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.33359E-005 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.23516 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10668.86926 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.33359E-005 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 230.62033 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.45746 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10284 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.29262 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52600 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.70482E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.67220E-005 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.29262 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11055.92231 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.67220E-005 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 238.77447 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.26288 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.25683E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.19027 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52600 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09525E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.39212E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.19027 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7306.58804 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.39212E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 153.90465 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82906 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37879 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52600 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.43609 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.00584E-003 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.09535E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.43609 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6967.36514 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.09535E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 163.32929 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.67161 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.67161 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.18938 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.67161 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.08760 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 22.08760 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.52842 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 22.08760 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.08760 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 33.49810 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.93275 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.39467E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 656561.51189 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.34509E-002 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 22.08760 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 81282.44393 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.11094E-004 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1482.02303 |
350 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 22.08760 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.34509E-002 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.03059E-005 |
353 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.11094E-004 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
356 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 42.00000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.90788 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.15790E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 78036.98448 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.78730E-003 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 7548.85526 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.60407E-005 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 137.63830 |
368 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.78730E-003 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.70843E-004 |
371 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.60407E-005 |
372 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 4.90359 |
373 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 4.36989E-003 |
374 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.90359 |
375 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Electric Power Consumption [W] | 700.51236 |
376 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 3.87257 |
377 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 3.45109E-003 |
378 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.87257 |
379 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Electric Power Consumption [W] | 553.22422 |
380 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Condenser water flow rate [m3/s] | 3.45109E-003 |
381 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Evaporator air flow rate [m3/s] | 3.87257 |
382 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 3.36116E-002 |
383 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 6857.52866 |
384 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.21940E-003 |
385 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.26633 |
386 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.21940E-003 |
387 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 661.76670 |
388 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
389 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 253690.50142 |
390 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 253690.50000 |
391 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.21940E-003 |
392 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 3.36116E-002 |
393 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 4.03339 |
394 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 3.36116E-002 |
395 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 4747.69838 |
396 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 3.36116E-002 |
397 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 941035.14181 |
398 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 941649.76000 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 107.34807 |
400 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
401 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
402 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
403 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
404 | WaterHeater:Stratified | SWHSYS1 HPWH TANK | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
405 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Condenser water flow rate [m3/s] | 4.36989E-003 |
406 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Evaporator air flow rate [m3/s] | 4.90359 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 6249.71 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 2600.60 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1191.59 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 1634.54 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 958.57 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10474.26 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 8158.19 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 22895.81 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 3921.25 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 3921.00 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 23048.37 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 23054.90 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 3925.07 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 3924.82 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 9694.84 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1246.41 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1246.32 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 6057.16 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 10722.34 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 11111.37 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7344.05 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 6999.24 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 70459.29 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 6543.69 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 17013.55 | 13643.23 | 3370.31 | 0.80 | 1987.62 | 20.16 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 17078.65 | 13695.70 | 3382.95 | 0.80 | 1995.24 | 20.24 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 98950.94 | 79782.24 | 19168.71 | 0.81 | 11590.20 | 117.55 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 118681.69 | 94295.92 | 24385.77 | 0.79 | 13807.26 | 140.04 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 15361.94 | 12311.31 | 3050.64 | 0.80 | 1794.16 | 18.20 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 15389.15 | 12333.21 | 3055.94 | 0.80 | 1797.34 | 18.23 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4623.69 | 3709.42 | 914.28 | 0.80 | 540.28 | 5.48 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4638.49 | 3721.37 | 917.13 | 0.80 | 542.01 | 5.50 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21723.18 | 17348.59 | 4374.59 | 0.80 | 2533.02 | 25.69 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 617300.78 | 409172.03 | 208128.75 | 0.66 | 70894.14 | 719.05 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 59755.63 | 38990.42 | 20765.21 | 0.65 | 6397.24 | 64.88 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.608 | 1.296 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.608 | 1.296 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.608 | 1.296 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.608 | 1.296 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.608 | 1.296 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.684 | 1.345 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.684 | 1.345 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.684 | 1.345 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.684 | 1.345 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.684 | 1.345 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5095_SHGC_0.23 | N/A | 2.897 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.5116831529E-002 | 2.0398431585E-002 | Pass | Pass | 4.6394025780E-003 | 1.2861396701E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.3755644913E-002 | 2.6951667160E-002 | Pass | Pass | 4.3172448885E-002 | 5.0566162210E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.4704065036E-002 | 2.8307176090E-002 | Pass | Pass | 5.8515907137E-003 | 1.5370858711E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.7632945973E-003 | 1.2835168654E-002 | Pass | Pass | 1.1790677646E-002 | 2.6986251480E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.1678520859E-003 | 4.8619180952E-003 | Pass | Pass | 1.4395682691E-002 | 2.1139255631E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.9931660929E-002 | 0.2024736772 | Pass | Pass | 1.9056881611E-002 | 5.0508744456E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.4532794466E-002 | 6.4872731150E-002 | Pass | Pass | 9.7348515363E-003 | 1.6067222188E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.5106266238E-002 | 4.1966610267E-002 | Pass | Pass | 6.6617802983E-003 | 1.4483338298E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.2876117018E-002 | 0.1203530417 | Pass | Pass | 1.2092657425 | 10.5158044040 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.2338353633E-002 | 8.8728437532E-002 | Pass | Pass | 0.2070182207 | 0.6659907727 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.5873248001E-002 | 4.3037203887E-002 | Pass | Pass | 0.2712470439 | 1.8783310590 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.1208971563E-002 | 0.1228604859 | Pass | Pass | 0.8406310482 | 8.1138014350 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.3091519470E-002 | 9.9825339963E-002 | Pass | Pass | 0.3407423121 | 1.9079823976 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.9218149960E-002 | 4.9640727100E-002 | Pass | Pass | 0.1572390121 | 0.5804847520 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.6234052839E-003 | 4.7602774142E-003 | Pass | Pass | 2.4016336782E-002 | 4.6067586944E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.8845725851E-002 | 0.1403381877 | Pass | Pass | 0.2233428015 | 1.1141206082 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.8504463175E-002 | 0.1467829906 | Pass | Pass | 0.1721519779 | 0.6676961388 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.3979613686E-002 | 0.2311011344 | Pass | Pass | 4.6274593759 | 52.5843527799 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.6425332204E-002 | 8.0801277898E-002 | Pass | Pass | 9.4893336669E-003 | 2.4199960506E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.7404230691E-002 | 6.7284484400E-002 | Pass | Pass | 1.0285612370E-002 | 2.9260453355E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.8477594396E-002 | 8.7628850437E-002 | Pass | Pass | 2.0838969914E-002 | 3.9568758811E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.0785546566E-003 | 4.2720879616E-003 | Pass | Pass | 5.3716334098E-002 | 5.8770644745E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2379.27 | -12.3 | -770.1 | -2707.2 | 12417.44 | 11307.13 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.897 | 0.231 | 0.231 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.897 | 0.231 | 0.231 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.897 | 0.231 | 0.231 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.897 | 0.231 | 0.231 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.897 | 0.231 | 0.231 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.897 | 0.231 | 0.231 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.897 | 0.231 | 0.231 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.897 | 0.231 | 0.231 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.897 | 0.231 | 0.231 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.897 | 0.231 | 0.231 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.897 | 0.231 | 0.231 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.897 | 0.231 | 0.231 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.897 | 0.231 | 0.231 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.897 | 0.231 | 0.231 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.897 | 0.231 | 0.231 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.897 | 0.231 | 0.231 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.897 | 0.231 | 0.231 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.897 | 0.231 | 0.231 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.897 | 0.231 | 0.231 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.897 | 0.231 | 0.231 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.897 | 0.231 | 0.231 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5095_SHGC_0.23 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.897 | 0.231 | 0.231 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.897 | 0.231 | 0.231 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.897 | 0.231 | 0.231 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.897 | 0.231 | 0.231 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.897 | 0.231 | 0.231 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.897 | 0.231 | 0.231 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.897 | 0.231 | 0.231 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.897 | 0.231 | 0.231 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.5095_SHGC_0.23 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.897 | 0.231 | 0.231 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.897 | 0.231 | 0.231 | |||||||||||||||||
North Total or Average | 432.95 | 2.897 | 0.231 | 0.231 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.897 | 0.231 | 0.231 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.6442 | 1978.83 | 13147.70 | LightsWired | LTG_SCH_BASEMENT | 45.99 | 168.00 | 45.94 | 0.0000 | Y | 113.37 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 9.6995 | 67.07 | 650.56 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 6.26 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 9.6995 | 77.67 | 753.35 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.25 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 4.0903 | 94.76 | 387.59 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 1.87 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.7049 | 78.04 | 445.21 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.90 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 9.2569 | 188.86 | 1748.29 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 40.28 | 0.0000 | Y | 13.22 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 9.0417 | 1308.19 | 11828.20 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 55.53 | 0.0000 | Y | 123.28 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.4132 | 1863.81 | 8225.38 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 73.68 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.4132 | 1864.32 | 8227.62 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 73.70 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 4.4132 | 1557.62 | 6874.08 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 56.74 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.21 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.54 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.19 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.54 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.4132 | 220.77 | 974.32 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 8.73 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.69 | 0.0000 | Y | 28.64 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.69 | 0.0000 | Y | 28.64 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.7327 | 103.30 | 1212.04 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.34 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 4.4132 | 412.12 | 1818.79 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 15.01 |
Interior Lighting Total | 5.8432 | 11345.29 | 66293.22 | 390.50 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 11096.45 | AstronomicalClock | - | 83.75 | 83.75 | 174.46 | |
Exterior Lighting Total | 11096.45 | 174.46 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 253690.50 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 941649.76 | 2.96 | 941815.28 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11171.80 | 17013.55 | 13643.23 | 3370.31 | 0.80 | - | 1987.62 | 20.16 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11214.27 | 17078.65 | 13695.70 | 3382.95 | 0.80 | - | 1995.24 | 20.24 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 64519.13 | 98950.94 | 79782.24 | 19168.71 | 0.81 | - | 11590.20 | 117.55 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 78906.27 | 118681.69 | 94295.92 | 24385.77 | 0.79 | - | 13807.26 | 140.04 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10095.38 | 15361.94 | 12311.31 | 3050.64 | 0.80 | - | 1794.16 | 18.20 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10113.15 | 15389.15 | 12333.21 | 3055.94 | 0.80 | - | 1797.34 | 18.23 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3034.33 | 4623.69 | 3709.42 | 914.28 | 0.80 | - | 540.28 | 5.48 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3043.96 | 4638.49 | 3721.37 | 917.13 | 0.80 | - | 542.01 | 5.50 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 14342.21 | 21723.18 | 17348.59 | 4374.59 | 0.80 | - | 2533.02 | 25.69 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 656561.51 | 617300.78 | 409172.03 | 208128.75 | 0.66 | - | 70894.14 | 719.05 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 78036.98 | 59755.63 | 38990.42 | 20765.21 | 0.65 | - | 6397.24 | 64.88 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 6217.53 | 6249.71 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2588.57 | 2600.60 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1185.68 | 1191.59 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1626.84 | 1634.54 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 954.11 | 958.57 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10420.70 | 10474.26 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 8118.88 | 8158.19 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 22781.93 | 22895.81 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3640.94 | 3921.25 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3640.71 | 3921.00 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 21400.81 | 23048.37 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 21406.87 | 23054.90 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3644.49 | 3925.07 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3644.26 | 3924.82 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 9649.41 | 9694.84 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1157.31 | 1246.41 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1157.23 | 1246.32 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 5624.20 | 6057.16 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10668.87 | 10722.34 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11055.92 | 11111.37 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7306.59 | 7344.05 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 6967.37 | 6999.24 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 81282.44 | 70459.29 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 7548.86 | 6543.69 | - |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 75921.46 | 3.40 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 54370.95 | 3.40 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.03 | 721.89 | 703.64 | 1.00 | 1.19 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.03 | 724.69 | 703.64 | 1.00 | 1.19 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.05 | 4255.03 | 703.64 | 1.00 | 0.96 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.99 | 4921.83 | 703.64 | 1.00 | 0.95 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.92 | 650.84 | 703.64 | 1.00 | 1.22 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.93 | 652.00 | 703.64 | 1.00 | 1.22 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.28 | 196.40 | 703.64 | 1.00 | 1.76 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.28 | 197.04 | 703.64 | 1.00 | 1.76 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.30 | 912.43 | 703.64 | 1.00 | 1.14 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 22.09 | 49490.32 | 2240.64 | 1.00 | 1.11 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 4.90 | 700.51 | 142.86 | 0.00 | 2.78 | General | ||
SWHSYS1 HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 3.87 | 553.22 | 142.86 | 0.00 | 2.84 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.033612 | 6857.53 | 204022.71 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.002219 | 661.77 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.033612 | 4747.70 | 141251.80 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYSLAUNDRY HPWH | WaterHeater:HeatPump:PumpedCondenser | 1.14 | 76996.79 | 0.80 | 48.89 | 1.72 |
SWHSYS1 HPWH | WaterHeater:HeatPump:PumpedCondenser | 2.84 | 62640.04 | 0.80 | 4.64 | 9.46 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 30811.97 | 30811.97 | 15.57 | 2.297 | 2.297 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 21:10:00 | 24.00 | 24.00 | 0.00928 | 36.13 | 0.00915 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4558.61 | 4558.61 | 67.97 | 0.340 | 0.340 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 24.00 | 24.00 | 0.00904 | 42.00 | 0.00916 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3235.84 | 3235.84 | 41.66 | 0.241 | 0.241 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:40:00 | 24.00 | 24.00 | 0.00938 | 40.00 | 0.00915 | 0.092 | 0.00 |
MECH_FLR_1 | 3230.59 | 3230.59 | 19.67 | 0.241 | 0.241 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:50:00 | 24.00 | 24.00 | 0.00869 | 37.33 | 0.00915 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1766.66 | 1766.66 | 18.64 | 0.132 | 0.132 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:00:00 | 24.00 | 24.00 | 0.00877 | 40.64 | 0.00916 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 45216.48 | 45216.48 | 579.41 | 3.370 | 3.370 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:50:00 | 24.00 | 24.00 | 0.00854 | 39.83 | 0.00915 | 0.000 | 0.00 |
CAFE_FLR_1 | 19287.71 | 19287.71 | 102.13 | 1.439 | 1.439 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 24.00 | 23.99 | 0.01016 | 42.00 | 0.00916 | 0.676 | 0.00 |
LOBBY_FLR_1 | 65102.69 | 65102.69 | 49.77 | 4.855 | 4.855 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 24.00 | 23.99 | 0.00997 | 41.90 | 0.00916 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 10214.51 | 10214.51 | 261.76 | 1.026 | 1.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 21.11 | 21.11 | 0.00858 | 41.16 | 0.00916 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10254.07 | 10254.07 | 262.81 | 1.030 | 1.030 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 21.11 | 21.11 | 0.00858 | 41.03 | 0.00916 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 60210.11 | 60210.11 | 2455.17 | 6.047 | 6.047 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 21.11 | 21.11 | 0.00850 | 41.81 | 0.00916 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 69640.14 | 69640.14 | 2838.91 | 6.995 | 6.995 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 21.11 | 21.11 | 0.00871 | 41.03 | 0.00916 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9209.09 | 9209.09 | 236.00 | 0.925 | 0.925 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 21.11 | 21.11 | 0.00859 | 39.53 | 0.00915 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9225.59 | 9225.59 | 236.45 | 0.927 | 0.927 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 21.11 | 21.11 | 0.00859 | 39.53 | 0.00915 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 18484.48 | 18484.48 | 47.47 | 1.378 | 1.378 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 24.00 | 24.00 | 0.00953 | 41.16 | 0.00916 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2779.01 | 2779.01 | 71.22 | 0.279 | 0.279 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 21.11 | 21.11 | 0.00857 | 41.16 | 0.00916 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2788.04 | 2788.04 | 71.46 | 0.280 | 0.280 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 21.11 | 21.11 | 0.00857 | 41.16 | 0.00916 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 12910.32 | 12910.32 | 526.30 | 1.297 | 1.297 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | 21.11 | 21.11 | 0.00863 | 42.00 | 0.00916 | 0.099 | 0.00 |
BANQUET_FLR_6 | 31465.76 | 31465.76 | 94.87 | 2.348 | 2.348 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | 24.00 | 23.99 | 0.01029 | 42.00 | 0.00916 | 1.188 | 0.00 |
DINING_FLR_6 | 32930.03 | 32930.03 | 99.29 | 2.457 | 2.457 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | 24.00 | 23.99 | 0.01021 | 42.00 | 0.00916 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30279.78 | 30279.78 | 293.11 | 2.263 | 2.263 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 12:30:00 | 24.00 | 23.97 | 0.01010 | 41.13 | 0.00916 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 11123.04 | 11123.04 | 26.99 | 0.829 | 0.829 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:40:00 | 24.00 | 24.00 | 0.00895 | 42.00 | 0.00916 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | 00:10:00 | 21.00 | 22.37 | 0.00607 | 6.30 | 0.00607 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 1668.72 | 1668.72 | 24.88 | 0.073 | 0.079 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00794 | 6.30 | 0.00607 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 532.75 | 532.75 | 6.86 | 0.023 | 0.092 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00792 | 6.30 | 0.00607 | 0.092 | 0.00 |
MECH_FLR_1 | 975.13 | 975.13 | 5.94 | 0.043 | 0.043 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00790 | 6.30 | 0.00607 | 0.000 | 0.00 |
STORAGE_FLR_1 | 597.71 | 597.71 | 6.31 | 0.026 | 0.058 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00791 | 6.30 | 0.00607 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1298.40 | 1298.40 | 16.64 | 0.057 | 0.057 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00790 | 6.30 | 0.00607 | 0.000 | 0.00 |
CAFE_FLR_1 | 4223.62 | 4223.62 | 22.36 | 0.186 | 0.676 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00794 | 6.30 | 0.00607 | 0.676 | 0.00 |
LOBBY_FLR_1 | 9641.52 | 9641.52 | 7.37 | 0.424 | 1.894 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00793 | 6.30 | 0.00607 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 3640.95 | 3640.95 | 93.30 | 0.161 | 0.161 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00793 | 6.30 | 0.00607 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 3640.71 | 3640.71 | 93.31 | 0.161 | 0.161 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00793 | 6.30 | 0.00607 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 21400.83 | 21400.83 | 872.65 | 0.947 | 0.947 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00794 | 6.30 | 0.00607 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 21406.90 | 21406.90 | 872.66 | 0.947 | 0.947 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00794 | 6.30 | 0.00607 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 3644.50 | 3644.50 | 93.40 | 0.161 | 0.161 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00793 | 6.30 | 0.00607 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 3644.26 | 3644.26 | 93.40 | 0.161 | 0.161 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00793 | 6.30 | 0.00607 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 5919.89 | 5919.89 | 15.20 | 0.260 | 0.475 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00795 | 6.30 | 0.00607 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1157.32 | 1157.32 | 29.66 | 0.051 | 0.051 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00795 | 6.30 | 0.00607 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1157.23 | 1157.23 | 29.66 | 0.051 | 0.051 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00795 | 6.30 | 0.00607 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 5624.21 | 5624.21 | 229.27 | 0.249 | 0.249 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00795 | 6.30 | 0.00607 | 0.099 | 0.00 |
BANQUET_FLR_6 | 4312.21 | 4312.21 | 13.00 | 0.190 | 1.188 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00796 | 6.30 | 0.00607 | 1.188 | 0.00 |
DINING_FLR_6 | 4403.59 | 4403.59 | 13.28 | 0.194 | 1.188 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 21.00 | 21.00 | 0.00796 | 6.30 | 0.00607 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 1203.40 | 1203.40 | 11.65 | 0.053 | 0.367 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00627 | 6.30 | 0.00607 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 4723.06 | 4723.06 | 11.46 | 0.208 | 0.208 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 21.00 | 21.00 | 0.00797 | 6.30 | 0.00607 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 22.09 | 22.09 | 7.18 | 7.18 | 22.0876 | 11.6716 | 22.0876 | 0.5284 | 0.3000 |
FLR_3_DOAS | 18.69 | 2.05 | 2.89 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 6217.533 | 6217.533 | 1.208046 | 0.00005439 | 129.656 | 1/21 00:10:00 | 1/21 00:10:00 | 6217.53 | 6217.53 | 1.208046 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 0.00 | 0.00 | 6252.48 | 6252.48 | ||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 2588.566 | 2588.566 | 0.178746 | 0.00002265 | 59.645 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2588.57 | 2588.57 | 0.178746 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00793536 | 50.0105 | 1668.72 | 0.00 | 2602.44 | 2602.44 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1185.683 | 1185.683 | 0.126882 | 0.00001037 | 25.822 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1185.68 | 1185.68 | 0.126882 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00792233 | 49.9293 | 532.75 | 0.00 | 1192.25 | 1192.25 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1626.839 | 1626.839 | 0.126648 | 0.00001423 | 36.801 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1626.84 | 1626.84 | 0.126648 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00790085 | 49.7956 | 975.13 | 0.00 | 1635.62 | 1635.62 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 954.106 | 954.106 | 0.069259 | 0.00000835 | 21.809 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 954.11 | 954.11 | 0.069259 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00790640 | 49.8302 | 597.71 | 0.00 | 959.23 | 959.23 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10420.695 | 10420.695 | 1.772782 | 0.00009116 | 218.919 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10420.70 | 10420.70 | 1.772782 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00789855 | 49.7814 | 1298.40 | 0.00 | 10479.11 | 10479.11 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 8118.878 | 8118.878 | 0.756922 | 0.00007103 | 179.437 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8118.88 | 8118.88 | 0.756922 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00794330 | 50.0599 | 4223.62 | 0.00 | 8163.08 | 8163.08 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 22781.929 | 22781.929 | 2.553477 | 0.00019931 | 493.938 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 22781.93 | 22781.93 | 2.553477 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00792951 | 49.9740 | 9641.52 | 0.00 | 22908.35 | 22908.35 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 11171.803 | -999.000 | 1.025943 | 0.00039902 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | unknown | 6/21 16:20:00 | 11171.80 | 10971.31 | 1.025943 | 21.70 | 15.37 | 0.00857695 | 12.80 | 11.87 | 0.00850000 | 41.16 | 0.00915650 | 22.03 | 0.0000 | 21.11 | 0.00857695 | 53.6331 | 10214.51 | 0.00 | 11445.55 | 11034.95 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 3640.940 | 3640.940 | 0.161041 | 0.00003185 | 104.022 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3640.94 | 3640.94 | 0.161041 | 21.11 | 14.58 | 0.00793175 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.11 | 0.00793175 | 49.6483 | 3640.95 | 0.00 | 3925.06 | 3925.06 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 11214.272 | -999.000 | 1.029917 | 0.00040054 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | unknown | 6/21 16:30:00 | 11214.27 | 11013.69 | 1.029917 | 21.70 | 15.37 | 0.00857669 | 12.80 | 11.87 | 0.00850000 | 41.03 | 0.00915628 | 21.99 | 0.0000 | 21.11 | 0.00857669 | 53.6314 | 10254.07 | 0.00 | 11489.07 | 11077.57 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 3640.706 | 3640.706 | 0.161031 | 0.00003185 | 104.015 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3640.71 | 3640.71 | 0.161031 | 21.11 | 14.58 | 0.00793175 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.11 | 0.00793175 | 49.6483 | 3640.71 | 0.00 | 3924.81 | 3924.81 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 64519.127 | -999.000 | 6.047207 | 0.00230443 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | unknown | 6/21 15:20:00 | 64519.13 | 64473.29 | 6.047207 | 21.70 | 15.31 | 0.00850299 | 12.80 | 11.87 | 0.00850000 | 41.81 | 0.00915758 | 22.21 | 0.0000 | 21.11 | 0.00850299 | 53.1756 | 60210.11 | 0.00 | 66116.06 | 64846.42 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 21400.806 | 21400.806 | 0.946574 | 0.00018722 | 611.421 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21400.81 | 21400.81 | 0.946574 | 21.11 | 14.59 | 0.00793823 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.11 | 0.00793823 | 49.6882 | 21400.83 | 0.00 | 23070.83 | 23070.83 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 78906.272 | -999.000 | 6.994851 | 0.00281830 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | unknown | 6/21 16:30:00 | 78906.27 | 75187.05 | 6.994851 | 21.70 | 15.49 | 0.00870830 | 12.80 | 11.87 | 0.00850000 | 41.03 | 0.00915628 | 21.99 | 0.0000 | 21.11 | 0.00870830 | 54.4439 | 69640.14 | 0.00 | 80806.31 | 75626.14 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 21406.874 | 21406.874 | 0.946842 | 0.00018728 | 611.594 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21406.87 | 21406.87 | 0.946842 | 21.11 | 14.59 | 0.00793823 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.11 | 0.00793823 | 49.6882 | 21406.90 | 0.00 | 23077.38 | 23077.38 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 10095.376 | -999.000 | 0.924960 | 0.00036058 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | unknown | 6/21 10:50:00 | 10095.38 | 9894.78 | 0.924960 | 21.70 | 15.38 | 0.00858537 | 12.80 | 11.87 | 0.00850000 | 39.53 | 0.00915377 | 21.56 | 0.0000 | 21.11 | 0.00858537 | 53.6850 | 9209.09 | 0.00 | 10342.47 | 9952.19 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 3644.490 | 3644.490 | 0.161198 | 0.00003188 | 104.123 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3644.49 | 3644.49 | 0.161198 | 21.11 | 14.58 | 0.00793181 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.11 | 0.00793181 | 49.6487 | 3644.50 | 0.00 | 3928.89 | 3928.89 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10113.149 | -999.000 | 0.926617 | 0.00036121 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | unknown | 6/21 10:50:00 | 10113.15 | 9912.46 | 0.926617 | 21.70 | 15.38 | 0.00858526 | 12.80 | 11.87 | 0.00850000 | 39.53 | 0.00915377 | 21.56 | 0.0000 | 21.11 | 0.00858526 | 53.6843 | 9225.59 | 0.00 | 10360.68 | 9969.97 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 3644.255 | 3644.255 | 0.161188 | 0.00003188 | 104.117 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3644.26 | 3644.26 | 0.161188 | 21.11 | 14.58 | 0.00793182 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.11 | 0.00793182 | 49.6487 | 3644.26 | 0.00 | 3928.64 | 3928.64 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 9649.414 | 9649.414 | 0.724704 | 0.00008442 | 219.427 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9649.41 | 9649.41 | 0.724704 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00794843 | 50.0917 | 5919.89 | 0.00 | 9701.37 | 9701.37 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3034.327 | -999.000 | 0.279123 | 0.00010838 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | unknown | 6/21 16:20:00 | 3034.33 | 2984.16 | 0.279123 | 21.70 | 15.37 | 0.00857079 | 12.80 | 11.87 | 0.00850000 | 41.16 | 0.00915650 | 22.03 | 0.0000 | 21.11 | 0.00857079 | 53.5950 | 2779.01 | 0.00 | 3108.74 | 3001.47 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1157.315 | 1157.315 | 0.051189 | 0.00001012 | 33.064 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1157.31 | 1157.31 | 0.051189 | 21.11 | 14.59 | 0.00794590 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.11 | 0.00794590 | 49.7358 | 1157.32 | 0.00 | 1247.63 | 1247.63 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3043.961 | -999.000 | 0.280030 | 0.00010872 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | unknown | 6/21 16:20:00 | 3043.96 | 2993.83 | 0.280030 | 21.70 | 15.37 | 0.00857052 | 12.80 | 11.87 | 0.00850000 | 41.16 | 0.00915650 | 22.03 | 0.0000 | 21.11 | 0.00857052 | 53.5933 | 2788.04 | 0.00 | 3118.61 | 3011.19 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1157.229 | 1157.229 | 0.051185 | 0.00001012 | 33.062 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1157.23 | 1157.23 | 0.051185 | 21.11 | 14.59 | 0.00794590 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.11 | 0.00794590 | 49.7358 | 1157.23 | 0.00 | 1247.53 | 1247.53 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 14342.213 | -999.000 | 1.296742 | 0.00051226 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | unknown | 6/21 14:50:00 | 14342.21 | 13898.77 | 1.296742 | 21.70 | 15.42 | 0.00863435 | 12.80 | 11.87 | 0.00850000 | 42.00 | 0.00915790 | 22.26 | 0.0000 | 21.11 | 0.00863435 | 53.9878 | 12910.32 | 0.00 | 14690.96 | 13979.60 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 5624.199 | 5624.199 | 0.248762 | 0.00004920 | 160.682 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 5624.20 | 5624.20 | 0.248762 | 21.11 | 14.60 | 0.00794866 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.11 | 0.00794866 | 49.7528 | 5624.21 | 0.00 | 6063.09 | 6063.09 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10668.869 | 10668.869 | 1.235164 | 0.00009334 | 230.620 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10668.87 | 10668.87 | 1.235164 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00796399 | 50.1886 | 4312.21 | 0.00 | 10728.12 | 10728.12 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11055.922 | 11055.922 | 1.292624 | 0.00009672 | 238.774 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 11055.92 | 11055.92 | 1.292624 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00796472 | 50.1932 | 4403.59 | 0.00 | 11117.34 | 11117.34 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7306.588 | 7306.588 | 1.190273 | 0.00006392 | 153.905 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 7306.59 | 7306.59 | 1.190273 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00626547 | 39.5973 | 1203.40 | 0.00 | 7347.51 | 7347.51 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 6967.365 | 6967.365 | 0.436087 | 0.00006095 | 163.329 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 6967.37 | 6967.37 | 0.436087 | 16.70 | 12.95 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00797109 | 50.2327 | 4723.06 | 0.00 | 7004.51 | 7004.51 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 656561.512 | -999.000 | 22.087598 | 0.02345086 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 656561.51 | 596428.59 | 22.087598 | 33.50 | 19.95 | 0.00939467 | 10.93 | 10.93 | 0.00850000 | 42.00 | 0.00915790 | 22.26 | 52.7964 | 23.99 | 0.00964107 | 50.5211 | 296131.36 | 0.00 | 666514.73 | 582307.48 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 81282.444 | 81282.444 | 6.626279 | 0.00071109 | 1482.023 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 81282.44 | 81282.44 | 6.626279 | 6.30 | 6.30 | 0.00607234 | 16.70 | 12.95 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 175.9881 | 21.35 | 0.00743310 | 45.8759 | 39183.12 | 0.00 | 85303.90 | 85303.90 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 78036.984 | -999.000 | 2.051317 | 0.00278730 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:00:00 | 78036.98 | 74039.07 | 2.051317 | 42.00 | 22.26 | 0.00915790 | 11.91 | 11.50 | 0.00850000 | 42.00 | 0.00915790 | 22.26 | 99.9965 | 21.11 | 0.00861343 | 53.8579 | 184815.87 | 0.00 | 79015.40 | 73461.98 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 7548.855 | 7548.855 | 0.615395 | 0.00006604 | 137.638 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7548.86 | 7548.86 | 0.615395 | 6.30 | 6.30 | 0.00607234 | 16.70 | 12.95 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 333.3216 | 21.11 | 0.00793828 | 49.6886 | 65316.91 | 0.00 | 7922.34 | 7922.34 |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 64488.768 | 47463.733 | 4.903586 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 75921.46 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 50957.891 | 37505.008 | 3.872570 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 54370.95 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 6217.533 | 6217.533 | 1.208046 | 0.00005439 | 129.656 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 2.4025 | 2.450834 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 6217.53 | 6217.53 | 1.0000 | 1.41798721 | 1.208046 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.05438815 | 60.00 | 32.22 | 27.78 | 0.000 | 6217.53 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 0.00 | 0.00 | 6252.48 | 6252.48 | 1.41798721 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2588.566 | 2588.566 | 0.178746 | 0.00002265 | 59.645 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 1.0002 | 1.020364 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2588.57 | 2588.57 | 1.0000 | 0.20981004 | 0.178746 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.02264360 | 60.00 | 32.22 | 27.78 | 0.000 | 2588.57 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00793536 | 21.00 | 0.00793536 | 50.0105 | 1668.72 | 0.00 | 2602.44 | 2602.44 | 0.20981004 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.76 | 17.62 | 0.00800000 | 49338.5 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1185.683 | 1185.683 | 0.126882 | 0.00001037 | 25.822 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 0.4582 | 0.467374 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1185.68 | 1185.68 | 1.0000 | 0.14893192 | 0.126882 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.01037181 | 60.00 | 32.22 | 27.78 | 0.000 | 1185.68 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00792233 | 21.00 | 0.00792233 | 49.9293 | 532.75 | 0.00 | 1192.25 | 1192.25 | 0.14893192 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.45 | 16.12 | 0.00800000 | 44940.1 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1626.839 | 1626.839 | 0.126648 | 0.00001423 | 36.801 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 0.6286 | 0.641269 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1626.84 | 1626.84 | 1.0000 | 0.14865807 | 0.126648 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.01423085 | 60.00 | 32.22 | 27.78 | 0.000 | 1626.84 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00790085 | 21.00 | 0.00790085 | 49.7956 | 975.13 | 0.00 | 1635.62 | 1635.62 | 0.14865807 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.39 | 17.15 | 0.00800000 | 47937.3 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 954.106 | 954.106 | 0.069259 | 0.00000835 | 21.809 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 0.3687 | 0.376091 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 954.11 | 954.11 | 1.0000 | 0.08129504 | 0.069259 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.00834608 | 60.00 | 32.22 | 27.78 | 0.000 | 954.11 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00790640 | 21.00 | 0.00790640 | 49.8302 | 597.71 | 0.00 | 959.23 | 959.23 | 0.08129504 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.17 | 17.42 | 0.00800000 | 48734.2 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10420.695 | 10420.695 | 1.772782 | 0.00009116 | 218.919 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 4.0266 | 4.107641 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 10420.70 | 10420.70 | 1.0000 | 2.08086629 | 1.772782 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.09115549 | 60.00 | 32.22 | 27.78 | 0.000 | 10420.70 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00789855 | 21.00 | 0.00789855 | 49.7814 | 1298.40 | 0.00 | 10479.11 | 10479.11 | 2.08086629 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.54 | 15.05 | 0.00800000 | 41970.7 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8118.878 | 8118.878 | 0.756922 | 0.00007103 | 179.437 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 3.1372 | 3.200308 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8118.88 | 8118.88 | 1.0000 | 0.88846357 | 0.756922 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.07102024 | 60.00 | 32.22 | 27.78 | 0.000 | 8118.88 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00794330 | 21.00 | 0.00794330 | 50.0599 | 4223.62 | 0.00 | 8163.08 | 8163.08 | 0.88846357 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.61 | 16.53 | 0.00800000 | 46122.6 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22781.929 | 22781.929 | 2.553477 | 0.00019931 | 493.938 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 8.8030 | 8.980206 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 22781.93 | 22781.93 | 1.0000 | 2.99723431 | 2.553477 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.19928592 | 60.00 | 32.22 | 27.78 | 0.000 | 22781.93 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00792951 | 21.00 | 0.00792951 | 49.9740 | 9641.52 | 0.00 | 22908.35 | 22908.35 | 2.99723431 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.10 | 15.99 | 0.00800000 | 44577.9 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11171.803 | -999.000 | 1.025943 | 0.00039902 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7841 | 1004.8586 | 1.1738 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.025943 | 1.20423681 | 4197.9300 | 999.8980 | 33.60816615 | 13.37 | 6.70 | 6.67 | 941035.14 | 1.1872 | 1.187160 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | unknown | unknown | unknown | 6/21 16:20:00 | Sensible | 11171.80 | 10971.31 | 1.0000 | 1.20423681 | 1.025943 | 21.70 | 15.37 | 0.00857695 | 43599.3 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.39898277 | 6.70 | 13.37 | 6.67 | 0.000 | 11171.80 | 41.16 | 0.00915650 | 22.03 | 0.00000000 | 0.0000 | 21.11 | 0.00857695 | 21.11 | 0.00857695 | 53.6331 | 10214.51 | 0.00 | 11445.55 | 11034.95 | 1.20423681 | 21.70 | 15.63 | 0.00857695 | 43599.3 | 12.72 | 12.01 | 0.00844190 | 34094.9 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3640.940 | 3640.940 | 0.161041 | 0.00003185 | 104.022 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.025943 | 1.20423681 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 1.4069 | 1.435190 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3640.94 | 3640.94 | 1.0000 | 0.18902784 | 0.161041 | 21.11 | 14.58 | 0.00793175 | 41361.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.03184928 | 60.00 | 32.22 | 27.78 | 0.000 | 3640.94 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00793175 | 21.11 | 0.00793175 | 49.6483 | 3640.95 | 0.00 | 3925.06 | 3925.06 | 0.18902784 | 16.60 | 13.08 | 0.00793175 | 36761.9 | 36.97 | 20.22 | 0.00793175 | 57526.4 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11214.272 | -999.000 | 1.029917 | 0.00040054 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7836 | 1004.8586 | 1.1738 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.029917 | 1.20890140 | 4197.9300 | 999.8980 | 33.60816615 | 13.37 | 6.70 | 6.67 | 941035.14 | 1.1917 | 1.191673 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | unknown | unknown | unknown | 6/21 16:30:00 | Sensible | 11214.27 | 11013.69 | 1.0000 | 1.20890140 | 1.029917 | 21.70 | 15.37 | 0.00857669 | 43598.6 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.40049946 | 6.70 | 13.37 | 6.67 | 0.000 | 11214.27 | 41.03 | 0.00915628 | 21.99 | 0.00000000 | 0.0000 | 21.11 | 0.00857669 | 21.11 | 0.00857669 | 53.6314 | 10254.07 | 0.00 | 11489.07 | 11077.57 | 1.20890140 | 21.70 | 15.63 | 0.00857669 | 43598.6 | 12.72 | 12.01 | 0.00844186 | 34094.9 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3640.706 | 3640.706 | 0.161031 | 0.00003185 | 104.015 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.029917 | 1.20890140 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 1.4068 | 1.435097 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3640.71 | 3640.71 | 1.0000 | 0.18901565 | 0.161031 | 21.11 | 14.58 | 0.00793175 | 41361.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.03184723 | 60.00 | 32.22 | 27.78 | 0.000 | 3640.71 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00793175 | 21.11 | 0.00793175 | 49.6483 | 3640.71 | 0.00 | 3924.81 | 3924.81 | 0.18901565 | 16.60 | 13.08 | 0.00793175 | 36761.9 | 36.97 | 20.22 | 0.00793175 | 57526.4 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 64519.127 | -999.000 | 6.047207 | 0.00230443 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6466 | 1004.8586 | 1.1738 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.047207 | 7.09812308 | 4197.9300 | 999.8980 | 33.60816615 | 13.37 | 6.70 | 6.67 | 941035.14 | 6.8562 | 6.856059 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | unknown | unknown | unknown | 6/21 15:20:00 | Sensible | 64519.13 | 64473.29 | 1.0000 | 7.09812308 | 6.047207 | 21.70 | 15.31 | 0.00850299 | 43411.8 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 2.30419563 | 6.70 | 13.37 | 6.67 | 0.000 | 64519.13 | 41.81 | 0.00915758 | 22.21 | 0.00000000 | 0.0000 | 21.11 | 0.00850299 | 21.11 | 0.00850299 | 53.1756 | 60210.11 | 0.00 | 66116.06 | 64846.42 | 7.09812308 | 21.70 | 15.56 | 0.00850299 | 43411.8 | 12.75 | 12.01 | 0.00843214 | 34097.2 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21400.806 | 21400.806 | 0.946574 | 0.00018722 | 611.421 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.047207 | 7.09812308 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 8.2694 | 8.435793 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 21400.81 | 21400.81 | 1.0000 | 1.11107439 | 0.946574 | 21.11 | 14.59 | 0.00793823 | 41377.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.18720449 | 60.00 | 32.22 | 27.78 | 0.000 | 21400.81 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00793823 | 21.11 | 0.00793823 | 49.6882 | 21400.83 | 0.00 | 23070.83 | 23070.83 | 1.11107439 | 16.60 | 13.09 | 0.00793823 | 36778.3 | 36.97 | 20.22 | 0.00793823 | 57542.8 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 78906.272 | -999.000 | 6.994851 | 0.00281830 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0283 | 1004.8586 | 1.1738 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.994851 | 8.21045393 | 4197.9300 | 999.8980 | 33.60816615 | 13.37 | 6.70 | 6.67 | 941035.14 | 8.3851 | 8.384894 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | unknown | unknown | unknown | 6/21 16:30:00 | Sensible | 78906.27 | 75187.05 | 1.0000 | 8.21045393 | 6.994851 | 21.70 | 15.49 | 0.00870830 | 43932.7 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 2.81800908 | 6.70 | 13.37 | 6.67 | 0.000 | 78906.27 | 41.03 | 0.00915628 | 21.99 | 0.00000000 | 0.0000 | 21.11 | 0.00870830 | 21.11 | 0.00870830 | 54.4439 | 69640.14 | 0.00 | 80806.31 | 75626.14 | 8.21045393 | 21.70 | 15.74 | 0.00870830 | 43932.7 | 12.68 | 12.01 | 0.00845838 | 34090.8 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21406.874 | 21406.874 | 0.946842 | 0.00018728 | 611.594 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.994851 | 8.21045393 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 8.2717 | 8.438185 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 21406.87 | 21406.87 | 1.0000 | 1.11138943 | 0.946842 | 21.11 | 14.59 | 0.00793823 | 41377.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.18725757 | 60.00 | 32.22 | 27.78 | 0.000 | 21406.87 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00793823 | 21.11 | 0.00793823 | 49.6882 | 21406.90 | 0.00 | 23077.38 | 23077.38 | 1.11138943 | 16.60 | 13.09 | 0.00793823 | 36778.3 | 36.97 | 20.22 | 0.00793823 | 57542.8 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10095.376 | -999.000 | 0.924960 | 0.00036058 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7998 | 1004.8586 | 1.1738 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.924960 | 1.08570448 | 4197.9300 | 999.8980 | 33.60816615 | 13.37 | 6.70 | 6.67 | 941035.14 | 1.0728 | 1.072775 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | unknown | unknown | unknown | 6/21 10:50:00 | Sensible | 10095.38 | 9894.78 | 1.0000 | 1.08570448 | 0.924960 | 21.70 | 15.38 | 0.00858537 | 43620.7 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.36053993 | 6.70 | 13.37 | 6.67 | 0.000 | 10095.38 | 39.53 | 0.00915377 | 21.56 | 0.00000000 | 0.0000 | 21.11 | 0.00858537 | 21.11 | 0.00858537 | 53.6850 | 9209.09 | 0.00 | 10342.47 | 9952.19 | 1.08570448 | 21.70 | 15.64 | 0.00858537 | 43620.7 | 12.72 | 12.01 | 0.00844298 | 34094.6 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3644.490 | 3644.490 | 0.161198 | 0.00003188 | 104.123 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.924960 | 1.08570448 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 1.4082 | 1.436589 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3644.49 | 3644.49 | 1.0000 | 0.18921211 | 0.161198 | 21.11 | 14.58 | 0.00793181 | 41361.4 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.03188033 | 60.00 | 32.22 | 27.78 | 0.000 | 3644.49 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00793181 | 21.11 | 0.00793181 | 49.6487 | 3644.50 | 0.00 | 3928.89 | 3928.89 | 0.18921211 | 16.60 | 13.08 | 0.00793181 | 36762.1 | 36.97 | 20.22 | 0.00793181 | 57526.6 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10113.149 | -999.000 | 0.926617 | 0.00036121 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7996 | 1004.8586 | 1.1738 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.926617 | 1.08764900 | 4197.9300 | 999.8980 | 33.60816615 | 13.37 | 6.70 | 6.67 | 941035.14 | 1.0747 | 1.074663 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | unknown | unknown | unknown | 6/21 10:50:00 | Sensible | 10113.15 | 9912.46 | 1.0000 | 1.08764900 | 0.926617 | 21.70 | 15.38 | 0.00858526 | 43620.4 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.36117464 | 6.70 | 13.37 | 6.67 | 0.000 | 10113.15 | 39.53 | 0.00915377 | 21.56 | 0.00000000 | 0.0000 | 21.11 | 0.00858526 | 21.11 | 0.00858526 | 53.6843 | 9225.59 | 0.00 | 10360.68 | 9969.97 | 1.08764900 | 21.70 | 15.63 | 0.00858526 | 43620.4 | 12.72 | 12.01 | 0.00844297 | 34094.6 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3644.255 | 3644.255 | 0.161188 | 0.00003188 | 104.117 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.926617 | 1.08764900 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 1.4082 | 1.436497 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3644.26 | 3644.26 | 1.0000 | 0.18919995 | 0.161188 | 21.11 | 14.58 | 0.00793182 | 41361.4 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.03187828 | 60.00 | 32.22 | 27.78 | 0.000 | 3644.26 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00793182 | 21.11 | 0.00793182 | 49.6487 | 3644.26 | 0.00 | 3928.64 | 3928.64 | 0.18919995 | 16.60 | 13.08 | 0.00793182 | 36762.1 | 36.97 | 20.22 | 0.00793182 | 57526.6 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9649.414 | 9649.414 | 0.724704 | 0.00008442 | 219.427 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 3.7286 | 3.803617 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9649.41 | 9649.41 | 1.0000 | 0.85064733 | 0.724704 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.08440867 | 60.00 | 32.22 | 27.78 | 0.000 | 9649.41 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00794843 | 21.00 | 0.00794843 | 50.0917 | 5919.89 | 0.00 | 9701.37 | 9701.37 | 0.85064733 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.78 | 17.29 | 0.00800000 | 48339.4 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3034.327 | -999.000 | 0.279123 | 0.00010838 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7727 | 1004.8586 | 1.1738 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.279123 | 0.32763034 | 4197.9300 | 999.8980 | 33.60816615 | 13.37 | 6.70 | 6.67 | 941035.14 | 0.3224 | 0.322440 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | unknown | unknown | unknown | 6/21 16:20:00 | Sensible | 3034.33 | 2984.16 | 1.0000 | 0.32763034 | 0.279123 | 21.70 | 15.37 | 0.00857079 | 43583.6 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.10836606 | 6.70 | 13.37 | 6.67 | 0.000 | 3034.33 | 41.16 | 0.00915650 | 22.03 | 0.00000000 | 0.0000 | 21.11 | 0.00857079 | 21.11 | 0.00857079 | 53.5950 | 2779.01 | 0.00 | 3108.74 | 3001.47 | 0.32763034 | 21.70 | 15.62 | 0.00857079 | 43583.6 | 12.72 | 12.01 | 0.00844110 | 34095.1 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1157.315 | 1157.315 | 0.051189 | 0.00001012 | 33.064 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.279123 | 0.32763034 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 0.4472 | 0.456192 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1157.31 | 1157.31 | 1.0000 | 0.06008466 | 0.051189 | 21.11 | 14.59 | 0.00794590 | 41397.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.01012366 | 60.00 | 32.22 | 27.78 | 0.000 | 1157.31 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00794590 | 21.11 | 0.00794590 | 49.7358 | 1157.32 | 0.00 | 1247.63 | 1247.63 | 0.06008466 | 16.60 | 13.10 | 0.00794590 | 36797.8 | 36.97 | 20.23 | 0.00794590 | 57562.2 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3043.961 | -999.000 | 0.280030 | 0.00010872 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7722 | 1004.8586 | 1.1738 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.280030 | 0.32869551 | 4197.9300 | 999.8980 | 33.60816615 | 13.37 | 6.70 | 6.67 | 941035.14 | 0.3235 | 0.323463 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | unknown | unknown | unknown | 6/21 16:20:00 | Sensible | 3043.96 | 2993.83 | 1.0000 | 0.32869551 | 0.280030 | 21.70 | 15.37 | 0.00857052 | 43582.9 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.10871013 | 6.70 | 13.37 | 6.67 | 0.000 | 3043.96 | 41.16 | 0.00915650 | 22.03 | 0.00000000 | 0.0000 | 21.11 | 0.00857052 | 21.11 | 0.00857052 | 53.5933 | 2788.04 | 0.00 | 3118.61 | 3011.19 | 0.32869551 | 21.70 | 15.62 | 0.00857052 | 43582.9 | 12.72 | 12.01 | 0.00844106 | 34095.1 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1157.229 | 1157.229 | 0.051185 | 0.00001012 | 33.062 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.280030 | 0.32869551 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 0.4472 | 0.456158 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1157.23 | 1157.23 | 1.0000 | 0.06008023 | 0.051185 | 21.11 | 14.59 | 0.00794590 | 41397.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.01012291 | 60.00 | 32.22 | 27.78 | 0.000 | 1157.23 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00794590 | 21.11 | 0.00794590 | 49.7358 | 1157.23 | 0.00 | 1247.53 | 1247.53 | 0.06008023 | 16.60 | 13.10 | 0.00794590 | 36797.8 | 36.97 | 20.23 | 0.00794590 | 57562.2 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14342.213 | -999.000 | 1.296742 | 0.00051226 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8908 | 1004.8586 | 1.1738 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.296742 | 1.52209695 | 4197.9300 | 999.8980 | 33.60816615 | 13.37 | 6.70 | 6.67 | 941035.14 | 1.5241 | 1.524061 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | unknown | unknown | unknown | 6/21 14:50:00 | Sensible | 14342.21 | 13898.77 | 1.0000 | 1.52209695 | 1.296742 | 21.70 | 15.42 | 0.00863435 | 43744.9 | 12.80 | 11.87 | 0.00850000 | 34322.2 | 0.51220879 | 6.70 | 13.37 | 6.67 | 0.000 | 14342.21 | 42.00 | 0.00915790 | 22.26 | 0.00000000 | 0.0000 | 21.11 | 0.00863435 | 21.11 | 0.00863435 | 53.9878 | 12910.32 | 0.00 | 14690.96 | 13979.60 | 1.52209695 | 21.70 | 15.68 | 0.00863435 | 43744.9 | 12.70 | 12.01 | 0.00844923 | 34093.1 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5624.199 | 5624.199 | 0.248762 | 0.00004920 | 160.682 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.296742 | 1.52209695 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 2.1732 | 2.216953 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 5624.20 | 5624.20 | 1.0000 | 0.29199348 | 0.248762 | 21.11 | 14.60 | 0.00794866 | 41404.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.04919793 | 60.00 | 32.22 | 27.78 | 0.000 | 5624.20 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.11 | 0.00794866 | 21.11 | 0.00794866 | 49.7528 | 5624.21 | 0.00 | 6063.09 | 6063.09 | 0.29199348 | 16.60 | 13.10 | 0.00794866 | 36804.8 | 36.96 | 20.23 | 0.00794866 | 57569.2 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10668.869 | 10668.869 | 1.235164 | 0.00009334 | 230.620 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 4.1225 | 4.205467 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 10668.87 | 10668.87 | 1.0000 | 1.44981740 | 1.235164 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.09332640 | 60.00 | 32.22 | 27.78 | 0.000 | 10668.87 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00796399 | 21.00 | 0.00796399 | 50.1886 | 4312.21 | 0.00 | 10728.12 | 10728.12 | 1.44981740 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.86 | 15.90 | 0.00800000 | 44334.4 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11055.922 | 11055.922 | 1.292624 | 0.00009672 | 238.774 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 4.2721 | 4.358036 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | Sensible | 11055.92 | 11055.92 | 1.0000 | 1.51726333 | 1.292624 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.09671216 | 60.00 | 32.22 | 27.78 | 0.000 | 11055.92 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00796472 | 21.00 | 0.00796472 | 50.1932 | 4403.59 | 0.00 | 11117.34 | 11117.34 | 1.51726333 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.79 | 15.88 | 0.00800000 | 44262.0 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7306.588 | 7306.588 | 1.190273 | 0.00006392 | 153.905 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 2.8233 | 2.880119 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 7306.59 | 7306.59 | 1.0000 | 1.39712528 | 1.190273 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.06391470 | 60.00 | 32.22 | 27.78 | 0.000 | 7306.59 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.13 | 0.00626547 | 21.00 | 0.00626547 | 39.5973 | 1203.40 | 0.00 | 7347.51 | 7347.51 | 1.39712528 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.76 | 15.13 | 0.00800000 | 42193.8 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6967.365 | 6967.365 | 0.436087 | 0.00006095 | 163.329 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 2.6922 | 2.746404 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | Sensible | 6967.37 | 6967.37 | 1.0000 | 0.51187202 | 0.436087 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.06094733 | 60.00 | 32.22 | 27.78 | 0.000 | 6967.37 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00797109 | 21.00 | 0.00797109 | 50.2327 | 4723.06 | 0.00 | 7004.51 | 7004.51 | 0.51187202 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.02 | 18.04 | 0.00800000 | 50618.8 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 656561.512 | -999.000 | 22.087598 | 0.02345086 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.3042 | 1004.8586 | 1.1738 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.087598 | 25.92610108 | 4197.9300 | 999.8980 | 33.60816615 | 13.37 | 6.70 | 6.67 | 941035.14 | 69.7701 | 69.770137 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | Sensible | 656561.51 | 596428.59 | 1.0000 | 25.92610108 | 22.087598 | 33.50 | 19.95 | 0.00939467 | 57740.7 | 10.93 | 10.93 | 0.00850000 | 32416.4 | 23.44846371 | 6.70 | 13.37 | 6.67 | 49490.324 | 607071.19 | 42.00 | 0.00915790 | 22.26 | 11.66146000 | 52.7964 | 23.99 | 0.00965948 | 23.99 | 0.00964107 | 50.5211 | 296131.36 | 0.00 | 666514.73 | 582307.48 | 25.92610108 | 33.50 | 20.24 | 0.00939467 | 57740.7 | 11.53 | 11.17 | 0.00810700 | 32032.5 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 81282.444 | 81282.444 | 6.626279 | 0.00071109 | 1482.023 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.087598 | 25.92610108 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 31.4079 | 32.040003 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 81282.44 | 81282.44 | 1.0000 | 7.77783032 | 6.626279 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 0.71102174 | 60.00 | 32.22 | 27.78 | 0.000 | 81282.44 | 6.30 | 0.00607234 | 6.30 | 11.66146000 | 175.9881 | 18.46 | 0.00764190 | 21.35 | 0.00743310 | 45.8759 | 39183.12 | 0.00 | 85303.90 | 85303.90 | 7.77783032 | 2.80 | 2.80 | 0.00607234 | 18031.7 | 13.59 | 9.91 | 0.00607234 | 28999.3 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 78036.984 | -999.000 | 2.051317 | 0.00278730 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.8641 | 1004.8586 | 1.1738 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.40772169 | 4197.9300 | 999.8980 | 33.60816615 | 13.37 | 6.70 | 6.67 | 941035.14 | 8.2927 | 8.292675 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:00:00 | Sensible | 78036.98 | 74039.07 | 1.0000 | 2.40780635 | 2.051317 | 42.00 | 22.26 | 0.00915790 | 65821.7 | 11.91 | 11.50 | 0.00850000 | 33411.7 | 2.78701594 | 6.70 | 13.37 | 6.67 | 2195.006 | 75841.98 | 42.00 | 0.00915790 | 22.26 | 2.05124512 | 99.9965 | 21.11 | 0.00860793 | 21.11 | 0.00861343 | 53.8579 | 184815.87 | 0.00 | 79015.40 | 73461.98 | 2.40780635 | 42.00 | 22.57 | 0.00915790 | 65821.7 | 12.14 | 11.57 | 0.00824393 | 33005.3 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 7548.855 | 7548.855 | 0.615395 | 0.00006604 | 137.638 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.40772169 | 4197.9300 | 999.8980 | 2.21916877 | 54.44 | 82.22 | 27.78 | 258796.12 | 2.9169 | 2.975616 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7548.86 | 7548.86 | 1.0000 | 0.72234190 | 0.615395 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 16.70 | 12.95 | 0.00800000 | 37036.7 | 0.06603394 | 60.00 | 32.22 | 27.78 | 0.000 | 7548.86 | 6.30 | 0.00607234 | 6.30 | 2.05124512 | 333.3216 | 21.11 | 0.00793796 | 21.11 | 0.00793828 | 49.6886 | 65316.91 | 0.00 | 7922.34 | 7922.34 | 0.72234190 | 2.80 | 2.80 | 0.00607234 | 18031.7 | 13.59 | 9.91 | 0.00607234 | 28999.3 | |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 64488.768 | 47463.733 | 4.903586 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 1.1738 | SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 4.903586 | 5.75575854 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 75921.46 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 75921.46 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 50957.891 | 37505.008 | 3.872570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 1.1738 | SWHSYS1 HPWH FAN | Fan:SystemModel | 3.872570 | 4.54556583 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 54370.95 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54370.95 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 3757.33 | 3479.67 | 49.33 |
RETAIL_1_FLR_1 | 5138.17 | 2874.00 | 0.00 |
RETAIL_2_FLR_1 | 4979.67 | 3181.67 | 626.17 |
MECH_FLR_1 | 3392.00 | 4243.17 | 0.00 |
STORAGE_FLR_1 | 3053.33 | 4549.83 | 0.00 |
LAUNDRY_FLR_1 | 8399.17 | 3773.83 | 3615.33 |
CAFE_FLR_1 | 7019.67 | 3554.67 | 2471.50 |
LOBBY_FLR_1 | 6372.33 | 3348.00 | 2028.17 |
ROOM_1_FLR_3 | 146.17 | 7503.00 | 2.33 |
ROOM_2_FLR_3 | 134.33 | 7650.17 | 17.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 9.33 | 8758.67 | 9.33 |
ROOM_5_FLR_3 | 106.67 | 7401.17 | 2.33 |
ROOM_6_FLR_3 | 162.33 | 7477.00 | 15.67 |
CORRIDOR_FLR_3 | 3132.33 | 5510.67 | 1269.17 |
ROOM_1_FLR_6 | 485.17 | 7297.33 | 25.17 |
ROOM_2_FLR_6 | 424.17 | 7467.67 | 78.00 |
ROOM_3_MULT9_FLR_6 | 226.00 | 7287.17 | 0.50 |
BANQUET_FLR_6 | 7410.00 | 2767.00 | 2164.00 |
DINING_FLR_6 | 7994.17 | 2137.17 | 1970.50 |
KITCHEN_FLR_6 | 8682.67 | 7022.17 | 7022.17 |
CORRIDOR_FLR_6 | 3850.50 | 4014.83 | 0.00 |
Facility | 8746.50 | 8760.00 | 7967.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 32.00 | 0.00 | 32.00 |
ROOM_2_FLR_3 | 0.00 | 23.50 | 0.00 | 23.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 10.17 | 0.00 | 10.17 |
ROOM_5_FLR_3 | 0.00 | 22.67 | 0.00 | 22.67 |
ROOM_6_FLR_3 | 0.00 | 26.33 | 0.00 | 26.33 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 41.00 | 0.00 | 41.00 |
ROOM_2_FLR_6 | 0.00 | 32.00 | 0.00 | 32.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 35.17 | 0.00 | 35.17 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 67.50 | 0.00 | 67.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 0.829 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.183 | 0.033 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.323 | 0.011 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.607 | 0.012 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.566 | 0.012 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 19.677 | 0.035 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.55 | 142.30 | 748.35 | 3.358 | 0.026 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.05 | 422.44 | 5183.56 | 1.629 | 0.011 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.359 | 0.042 | 0.000 | 0.033 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.359 | 0.042 | 0.000 | 0.036 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.407 | 0.019 | 0.000 | 0.056 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.359 | 0.042 | 0.000 | 0.033 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.359 | 0.042 | 0.000 | 0.036 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.466 | 0.005 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.359 | 0.042 | 0.000 | 0.035 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.359 | 0.042 | 0.000 | 0.038 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.407 | 0.034 | 0.000 | 0.056 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.422 | 0.012 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.717 | 0.012 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 18.533 | 0.035 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.093 | 0.009 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 0.509 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.399 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 0.969 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.483 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.438 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 10.520 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.55 | 142.30 | 748.35 | 2.648 | 0.000 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.05 | 422.44 | 5183.56 | 1.177 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.000 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.289 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 3.644 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 3.830 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 7.987 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.674 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.78 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.55 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.05 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.96 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.96 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.11 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 33956171.40 | 0.00 | 33956171.40 | 0.00 | 33956171.40 | 26946214.98 | 623.09 | 125.51 | 8011.39 | 0.00 |
RETAIL_1_FLR_1 | 4930901.48 | 0.00 | 4930901.48 | 74224.11 | 5005125.59 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3453400.97 | 0.00 | 3453400.97 | 28650.60 | 3482051.57 | 2892943.94 | 68.20 | 44.37 | 8647.42 | 0.00 |
MECH_FLR_1 | 3358240.51 | 0.00 | 3358240.51 | 67713.00 | 3425953.51 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1806526.67 | 0.00 | 1806526.67 | 39066.67 | 1845593.34 | 1821682.01 | 4541.45 | 616.69 | 3601.86 | 0.00 |
LAUNDRY_FLR_1 | 51765281.46 | 0.00 | 51765281.46 | 92458.64 | 51857740.10 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 21289309.54 | 0.00 | 21289309.54 | 164076.59 | 21453386.13 | 21330615.53 | 4526.58 | 402.41 | 3831.01 | 0.00 |
LOBBY_FLR_1 | 71519661.69 | 0.00 | 71519661.69 | 468804.30 | 71988465.99 | 59728886.00 | 102.59 | 143.02 | 8514.39 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 33522.84 | 1493679.55 | 43081.65 | 1536761.20 | 1946875.62 | 2190.00 | 5952.58 | 617.42 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 36852.49 | 1496838.13 | 43078.36 | 1539916.49 | 1946647.51 | 2190.00 | 5951.72 | 618.28 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 295.71 | 1100207.68 | 12020.26 | 1112227.94 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 368.83 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 35758.20 | 19839587.50 | 12023.55 | 19851611.05 | 26405105.73 | 2190.00 | 6083.22 | 486.78 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 33673.52 | 1493830.24 | 43081.65 | 1536911.88 | 1946875.62 | 2190.00 | 5952.58 | 617.42 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 36508.30 | 1496493.94 | 43078.36 | 1539572.30 | 1946647.51 | 2190.00 | 5951.61 | 618.39 | 0.00 |
CORRIDOR_FLR_3 | 18793169.14 | 0.00 | 18793169.14 | 52094.38 | 18845263.51 | 14972100.18 | 240.64 | 65.67 | 8453.69 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 35537.56 | 400576.74 | 43090.26 | 443667.00 | 486718.90 | 2126.34 | 5959.21 | 674.45 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 38365.08 | 403361.49 | 43086.97 | 446448.46 | 486661.88 | 2128.17 | 5960.16 | 671.67 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 35904.91 | 2381095.22 | 22046.48 | 2403141.70 | 3126920.42 | 2190.00 | 5953.64 | 616.36 | 0.00 |
BANQUET_FLR_6 | 37823597.37 | 0.00 | 37823597.37 | 105215.58 | 37928812.95 | 37458366.31 | 4885.97 | 836.64 | 3037.39 | 0.00 |
DINING_FLR_6 | 40349177.25 | 0.00 | 40349177.25 | 105215.58 | 40454392.83 | 37458366.31 | 577.15 | 715.11 | 7467.73 | 0.00 |
KITCHEN_FLR_6 | 49423292.72 | 0.00 | 49423292.72 | 94192.34 | 49517485.06 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 11676070.19 | 0.00 | 11676070.19 | 92190.20 | 11768260.40 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.20E+10 | 3699372.84 | 0.20E+10 | 4341390.40 | 0.20E+10 | 0.43E+10 | 8760.00 | 7165.65 | 8760.00 | 368.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.0767 | 0.0000 | 1.0767 | 0.0000 | 1.0767 | 0.8545 | 623.09 | 125.51 | 8011.39 |
RETAIL_1_FLR_1 | 0.1564 | 0.0000 | 0.1564 | 0.0024 | 0.1587 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1095 | 0.0000 | 0.1095 | 0.0009 | 0.1104 | 0.0917 | 68.20 | 44.37 | 8647.42 |
MECH_FLR_1 | 0.1065 | 0.0000 | 0.1065 | 0.0021 | 0.1086 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0573 | 0.0000 | 0.0573 | 0.0012 | 0.0585 | 0.0578 | 4541.45 | 616.69 | 3601.86 |
LAUNDRY_FLR_1 | 1.6415 | 0.0000 | 1.6415 | 0.0029 | 1.6444 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.6751 | 0.0000 | 0.6751 | 0.0052 | 0.6803 | 0.6764 | 4526.58 | 402.41 | 3831.01 |
LOBBY_FLR_1 | 2.2679 | 0.0000 | 2.2679 | 0.0149 | 2.2827 | 1.8940 | 102.59 | 143.02 | 8514.39 |
ROOM_1_FLR_3 | 0.0463 | 0.0011 | 0.0474 | 0.0014 | 0.0487 | 0.0617 | 2190.00 | 5952.58 | 617.42 |
ROOM_2_FLR_3 | 0.0463 | 0.0012 | 0.0475 | 0.0014 | 0.0488 | 0.0617 | 2190.00 | 5951.72 | 618.28 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0011 | 0.6291 | 0.0004 | 0.6295 | 0.8373 | 2190.00 | 6083.22 | 486.78 |
ROOM_5_FLR_3 | 0.0463 | 0.0011 | 0.0474 | 0.0014 | 0.0487 | 0.0617 | 2190.00 | 5952.58 | 617.42 |
ROOM_6_FLR_3 | 0.0463 | 0.0012 | 0.0475 | 0.0014 | 0.0488 | 0.0617 | 2190.00 | 5951.61 | 618.39 |
CORRIDOR_FLR_3 | 0.5959 | 0.0000 | 0.5959 | 0.0017 | 0.5976 | 0.4748 | 240.64 | 65.67 | 8453.69 |
ROOM_1_FLR_6 | 0.0116 | 0.0011 | 0.0127 | 0.0014 | 0.0141 | 0.0154 | 2126.34 | 5959.21 | 674.45 |
ROOM_2_FLR_6 | 0.0116 | 0.0012 | 0.0128 | 0.0014 | 0.0142 | 0.0154 | 2128.17 | 5960.16 | 671.67 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0011 | 0.0755 | 0.0007 | 0.0762 | 0.0992 | 2190.00 | 5953.64 | 616.36 |
BANQUET_FLR_6 | 1.1994 | 0.0000 | 1.1994 | 0.0033 | 1.2027 | 1.1878 | 4885.97 | 836.64 | 3037.39 |
DINING_FLR_6 | 1.2795 | 0.0000 | 1.2795 | 0.0033 | 1.2828 | 1.1878 | 577.15 | 715.11 | 7467.73 |
KITCHEN_FLR_6 | 1.5672 | 0.0000 | 1.5672 | 0.0030 | 1.5702 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3702 | 0.0000 | 0.3702 | 0.0029 | 0.3732 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 62.0501 | 0.1166 | 62.1667 | 0.1087 | 62.2754 | 73.9670 | 8760.00 | 7165.65 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.48E+09 | 0.00 | 0.48E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 41084139.42 | 286418.62 | 41370558.04 | 64690340.46 | 8760.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 15.2974 | 0.0000 | 15.2974 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.3028 | 0.0091 | 1.3119 | 2.0513 | 8760.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 15.2974 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.6456 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1363 |
Defaulted Fields | 1208 |
Fields with Defaults | 4115 |
Autosized Fields | 353 |
Autosizable Fields | 407 |
Autocalculated Fields | 289 |
Autocalculatable Fields | 549 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 7760.43 | 75912.06 | 30-JAN-02:50 | 530068.81 | 09-JUN-19:20 |
Electricity:Building | 2340.01 | 31015.39 | 02-JAN-02:10 | 138695.41 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 256.48 | 3058.02 | 02-JAN-02:10 | 18903.76 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2332.92 | 30874.25 | 02-JAN-02:10 | 138454.08 | 02-JAN-20:10 |
InteriorLights:Electricity | 604.78 | 5592.07 | 02-JAN-02:10 | 50471.22 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 113.37 | 1030.12 | 02-JAN-02:10 | 9271.23 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 604.78 | 5592.07 | 02-JAN-02:10 | 50471.22 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 604.78 | 5592.07 | 02-JAN-02:10 | 50471.22 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 113.37 | 1030.12 | 02-JAN-02:10 | 9271.23 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 604.78 | 5592.07 | 02-JAN-02:10 | 50471.22 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 16.45 | 201.26 | 02-JAN-02:10 | 1197.92 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 19.05 | 233.06 | 02-JAN-02:10 | 1387.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.46 | 67.94 | 02-JAN-02:10 | 394.77 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.87 | 16.96 | 02-JAN-02:10 | 152.61 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.87 | 16.96 | 02-JAN-02:10 | 152.61 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.84 | 1007.22 | 02-JAN-02:10 | 4973.49 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 27.56 | 378.04 | 02-JAN-02:10 | 2538.73 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 13.22 | 76.92 | 01-JAN-13:10 | 1573.46 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 13.22 | 76.92 | 01-JAN-13:10 | 1573.46 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 272.29 | 3294.23 | 02-JAN-02:10 | 20674.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 123.29 | 1182.82 | 02-JAN-02:10 | 10645.38 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 123.29 | 1182.82 | 02-JAN-02:10 | 10645.38 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 18.46 | 262.96 | 01-JAN-02:10 | 1214.21 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 18.46 | 262.93 | 01-JAN-02:10 | 1214.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 302.44 | 4545.27 | 01-JAN-02:10 | 20822.55 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 73.68 | 623.81 | 01-JAN-02:10 | 5671.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 73.68 | 623.81 | 01-JAN-02:10 | 5671.40 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 302.52 | 4546.52 | 01-JAN-02:10 | 20828.25 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 73.70 | 623.98 | 01-JAN-02:10 | 5672.95 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 73.70 | 623.98 | 01-JAN-02:10 | 5672.95 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 18.46 | 262.96 | 01-JAN-02:10 | 1214.21 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 18.46 | 262.93 | 01-JAN-02:10 | 1214.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.62 | 65.74 | 01-JAN-02:10 | 303.55 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.74 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.74 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.62 | 65.73 | 01-JAN-02:10 | 303.52 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.73 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.73 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 35.82 | 538.40 | 01-JAN-02:10 | 2466.50 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 8.73 | 73.89 | 01-JAN-02:10 | 671.80 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 8.73 | 73.89 | 01-JAN-02:10 | 671.80 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 204.49 | 2556.31 | 02-JAN-02:10 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.64 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.64 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 204.49 | 2556.31 | 02-JAN-02:10 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.64 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.64 | 307.01 | 02-JAN-02:10 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 444.45 | 5944.83 | 02-JAN-02:10 | 18636.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 44.32 | 746.67 | 20-DEC-23:30 | 2790.67 | 26-FEB-11:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 3678.30 | 2146.87 | 30-JAN-02:50 | 314956.00 | 10-JUN-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 15.84 | 0.00 | 01-JAN-11:10 | 1308.76 | 04-MAY-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 21.40 | 628.90 | 22-DEC-04:10 | 716.65 | 09-SEP-13:10 |
WaterSystems:Electricity | 454.86 | 1086.56 | 01-AUG-00:50 | 44136.33 | 05-DEC-18:40 |
Electricity:HVAC | 948.63 | 21157.03 | 15-JAN-06:00 | 58079.07 | 07-AUG-21:20 |
Fans:Electricity | 631.18 | 11947.31 | 22-JAN-01:30 | 47309.53 | 07-AUG-21:20 |
General:Fans:Electricity | 631.18 | 11947.31 | 22-JAN-01:30 | 47309.53 | 07-AUG-21:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ExteriorEquipment:Electricity | 641.49 | 9451.24 | 02-JAN-02:20 | 39155.93 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 22.46 | 386.43 | 03-JAN-04:10 | 1283.34 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 7760.43 | 75912.06 | 30-JAN-02:50 | 530068.81 | 09-JUN-19:20 |
ElectricityPurchased:Plant | 7760.43 | 75912.06 | 30-JAN-02:50 | 530068.81 | 09-JUN-19:20 |
Cogeneration:ElectricityPurchased | 7760.43 | 75912.06 | 30-JAN-02:50 | 530068.81 | 09-JUN-19:20 |
General:Cogeneration:ElectricityPurchased | 7760.43 | 75912.06 | 30-JAN-02:50 | 530068.81 | 09-JUN-19:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 7760.43 | 75912.06 | 30-JAN-02:50 | 530068.81 | 09-JUN-19:20 |
ElectricityNet:Plant | 7760.43 | 75912.06 | 30-JAN-02:50 | 530068.81 | 09-JUN-19:20 |
Cogeneration:ElectricityNet | 7760.43 | 75912.06 | 30-JAN-02:50 | 530068.81 | 09-JUN-19:20 |
General:Cogeneration:ElectricityNet | 7760.43 | 75912.06 | 30-JAN-02:50 | 530068.81 | 09-JUN-19:20 |
ExteriorLights:Electricity | 174.46 | 0.00 | 01-JAN-07:20 | 11096.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 174.46 | 0.00 | 01-JAN-07:20 | 11096.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 295.00 | 8417.13 | 01-JAN-11:10 | 9938.94 | 05-MAR-10:00 |
General:HeatRecovery:Electricity | 295.00 | 8417.13 | 01-JAN-11:10 | 9938.94 | 05-MAR-10:00 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.56 | 08-JUN-00:20 | 4738.76 | 20-JUL-18:10 |
Water Heater Parasitic:WaterSystems:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 3017.88 | 0.00 | 01-JAN-00:10 | 269604.35 | 10-JUN-18:10 |
General:Cooling:Electricity | 3017.88 | 0.00 | 01-JAN-00:10 | 269604.35 | 10-JUN-18:10 |
Pumps:Electricity | 168.32 | 52.20 | 10-FEB-09:00 | 8210.42 | 28-AUG-18:10 |
General:Pumps:Electricity | 168.32 | 52.20 | 10-FEB-09:00 | 8210.42 | 28-AUG-18:10 |
WIRED_LTG_ELECTRICITY | 21.29 | 0.00 | 01-JAN-00:10 | 1776.59 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2491.27 | 29270.80 | 09-FEB-02:10 | 175605.60 | 02-JAN-19:20 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 702.43 | 15908.90 | 07-MAR-11:10 | 87985.82 | 02-JAN-19:20 |
WaterSystems:NaturalGas | 682.08 | 15908.90 | 03-JAN-16:10 | 69344.90 | 17-JAN-24:00 |
Water Heater:WaterSystems:NaturalGas | 682.08 | 15908.90 | 03-JAN-16:10 | 69344.90 | 17-JAN-24:00 |
Heating:NaturalGas | 20.35 | 0.00 | 03-JAN-16:30 | 33021.87 | 02-JAN-09:10 |
Boiler:Heating:NaturalGas | 20.35 | 0.00 | 03-JAN-16:30 | 33021.87 | 02-JAN-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 9083.79 | 0.00 | 01-JAN-00:10 | 744821.33 | 28-AUG-18:10 |
PlantLoopCoolingDemand:HVAC | 9083.79 | 0.00 | 01-JAN-00:10 | 744821.33 | 28-AUG-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 9083.79 | 0.00 | 01-JAN-00:10 | 744821.33 | 28-AUG-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:20 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:20 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:20 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:20 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:20 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:20 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 41840.36 | 140085.79 | 10-FEB-11:20 | 3306823.89 | 01-JUL-18:10 |
EnergyTransfer:Building | 6458.29 | 100411.69 | 16-JAN-15:00 | 396780.80 | 12-JUN-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 739.15 | 11492.63 | 02-JAN-04:00 | 35740.00 | 04-MAY-10:50 |
Refrigeration:EnergyTransfer | 188.04 | 4205.56 | 19-FEB-23:10 | 10372.57 | 13-OCT-06:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 94.02 | 2102.78 | 19-FEB-23:10 | 5186.29 | 13-OCT-06:30 |
General:Refrigeration:EnergyTransfer | 94.02 | 2102.78 | 19-FEB-23:10 | 5186.29 | 13-OCT-06:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 94.02 | 2102.78 | 19-FEB-23:10 | 5186.29 | 13-OCT-06:30 |
EnergyTransfer:Plant | 22124.23 | 16370.95 | 25-JAN-03:20 | 1783591.60 | 01-JUL-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.72 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 72.30 | 1946.72 | 22-DEC-04:10 | 2559.25 | 09-SEP-13:10 |
EnergyTransfer:HVAC | 13257.84 | 2470.54 | 15-JAN-16:00 | 1213566.75 | 27-AUG-18:10 |
CoolingCoils:EnergyTransfer | 10232.05 | 0.00 | 01-JAN-00:10 | 859123.48 | 28-AUG-18:10 |
EnergyTransfer:Zone:BASEMENT | 425.21 | 9131.97 | 10-APR-14:10 | 23612.19 | 27-SEP-21:00 |
Heating:EnergyTransfer | 3.88 | 0.00 | 01-JAN-08:10 | 10158.22 | 02-JAN-09:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 3.88 | 0.00 | 01-JAN-08:10 | 10158.22 | 02-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 6360.38 | 91807.79 | 01-JAN-06:00 | 393184.90 | 12-JUN-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 425.21 | 9131.97 | 10-APR-14:10 | 23612.19 | 27-SEP-21:00 |
General:Cooling:EnergyTransfer | 6360.38 | 91807.79 | 01-JAN-06:00 | 393184.90 | 12-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 425.21 | 9131.97 | 10-APR-14:10 | 23612.19 | 27-SEP-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 58.76 | 117.11 | 02-JAN-07:10 | 3776.95 | 02-OCT-13:10 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 58.76 | 117.11 | 02-JAN-07:10 | 3776.95 | 02-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 58.76 | 117.11 | 02-JAN-07:10 | 3776.95 | 02-OCT-13:10 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 43.62 | 870.57 | 02-JAN-12:00 | 2555.54 | 12-JUN-20:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 43.62 | 870.57 | 02-JAN-12:00 | 2555.54 | 12-JUN-20:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 43.62 | 870.57 | 02-JAN-12:00 | 2555.54 | 12-JUN-20:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 40.24 | 553.29 | 02-JAN-11:20 | 2650.28 | 12-JUN-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 40.24 | 553.29 | 02-JAN-11:20 | 2650.28 | 12-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 40.24 | 553.29 | 02-JAN-11:20 | 2650.28 | 12-JUN-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 21.28 | 275.83 | 02-JAN-10:30 | 1268.62 | 12-JUN-20:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 21.28 | 275.83 | 02-JAN-10:30 | 1268.62 | 12-JUN-20:10 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 21.28 | 275.83 | 02-JAN-10:30 | 1268.62 | 12-JUN-20:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 626.08 | 10308.73 | 02-JAN-05:00 | 39726.95 | 12-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 626.08 | 10308.73 | 02-JAN-05:00 | 39726.95 | 12-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 626.08 | 10308.73 | 02-JAN-05:00 | 39726.95 | 12-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 272.98 | 3617.46 | 16-JAN-16:00 | 13702.77 | 12-JUN-21:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 272.98 | 3617.46 | 16-JAN-16:00 | 13702.77 | 12-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 272.98 | 3617.46 | 16-JAN-16:00 | 13702.77 | 12-JUN-21:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 922.39 | 18545.30 | 16-JAN-16:00 | 48358.93 | 12-JUN-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 922.39 | 18545.30 | 16-JAN-16:00 | 48358.93 | 12-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 922.39 | 18545.30 | 16-JAN-16:00 | 48358.93 | 12-JUN-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 105.26 | 0.00 | 01-JAN-08:10 | 11314.60 | 10-JUN-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.35 | 0.00 | 01-JAN-08:10 | 1310.41 | 02-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.35 | 0.00 | 01-JAN-08:10 | 1310.41 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 104.91 | 0.00 | 01-JAN-00:10 | 11314.60 | 10-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 104.91 | 0.00 | 01-JAN-00:10 | 11314.60 | 10-JUN-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 91.65 | 0.00 | 01-JAN-08:10 | 11257.90 | 07-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 0.85 | 0.00 | 01-JAN-08:10 | 2365.10 | 02-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 0.85 | 0.00 | 01-JAN-08:10 | 2365.10 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 90.80 | 0.00 | 01-JAN-00:10 | 11257.90 | 07-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 90.80 | 0.00 | 01-JAN-00:10 | 11257.90 | 07-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 594.03 | 0.00 | 01-JAN-00:10 | 45531.21 | 02-OCT-13:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 594.03 | 0.00 | 01-JAN-00:10 | 45531.21 | 02-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 594.03 | 0.00 | 01-JAN-00:10 | 45531.21 | 02-OCT-13:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 711.98 | 0.00 | 01-JAN-08:10 | 79885.38 | 12-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.44 | 0.00 | 01-JAN-00:10 | 5442.44 | 02-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.44 | 0.00 | 01-JAN-00:10 | 5442.44 | 02-FEB-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 711.54 | 0.00 | 01-JAN-08:10 | 79885.38 | 12-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 711.54 | 0.00 | 01-JAN-08:10 | 79885.38 | 12-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 105.03 | 0.00 | 01-JAN-08:10 | 10360.23 | 04-MAY-15:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.34 | 0.00 | 01-JAN-08:10 | 1206.05 | 01-JAN-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.34 | 0.00 | 01-JAN-08:10 | 1206.05 | 01-JAN-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 104.69 | 0.00 | 01-JAN-00:10 | 10360.23 | 04-MAY-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 104.69 | 0.00 | 01-JAN-00:10 | 10360.23 | 04-MAY-15:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 91.34 | 0.00 | 01-JAN-08:10 | 10238.60 | 04-MAY-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 0.85 | 0.00 | 01-JAN-08:10 | 1583.84 | 01-JAN-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 0.85 | 0.00 | 01-JAN-08:10 | 1583.84 | 01-JAN-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 90.49 | 0.00 | 01-JAN-00:10 | 10238.60 | 04-MAY-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 90.49 | 0.00 | 01-JAN-00:10 | 10238.60 | 04-MAY-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 223.01 | 1691.64 | 02-JAN-09:10 | 12889.74 | 12-JUN-18:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 223.01 | 1691.64 | 02-JAN-09:10 | 12889.74 | 12-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 223.01 | 1691.64 | 02-JAN-09:10 | 12889.74 | 12-JUN-18:20 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 27.13 | 0.00 | 01-JAN-08:10 | 3121.35 | 10-JUN-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.32 | 0.00 | 01-JAN-08:10 | 584.11 | 02-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.32 | 0.00 | 01-JAN-08:10 | 584.11 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 26.81 | 0.00 | 01-JAN-00:10 | 3121.35 | 10-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 26.81 | 0.00 | 01-JAN-00:10 | 3121.35 | 10-JUN-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 23.99 | 0.00 | 01-JAN-08:10 | 3112.40 | 10-JUN-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.61 | 0.00 | 01-JAN-08:10 | 825.39 | 02-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.61 | 0.00 | 01-JAN-08:10 | 825.39 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 23.37 | 0.00 | 01-JAN-00:10 | 3112.40 | 10-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 23.37 | 0.00 | 01-JAN-00:10 | 3112.40 | 10-JUN-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 162.99 | 0.00 | 01-JAN-08:10 | 14989.54 | 02-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.12 | 0.00 | 01-JAN-00:10 | 1307.81 | 11-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.12 | 0.00 | 01-JAN-00:10 | 1307.81 | 11-FEB-06:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 162.87 | 0.00 | 01-JAN-02:10 | 14989.54 | 02-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 162.87 | 0.00 | 01-JAN-02:10 | 14989.54 | 02-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 500.62 | 9767.80 | 02-JAN-09:30 | 25277.13 | 12-JUN-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 500.62 | 9767.80 | 02-JAN-09:30 | 25277.13 | 12-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 500.62 | 9767.80 | 02-JAN-09:30 | 25277.13 | 12-JUN-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 536.63 | 10849.16 | 02-JAN-09:30 | 26465.46 | 12-JUN-21:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 536.63 | 10849.16 | 02-JAN-09:30 | 26465.46 | 12-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 536.63 | 10849.16 | 02-JAN-09:30 | 26465.46 | 12-JUN-21:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 645.13 | 9264.01 | 01-JAN-04:00 | 30682.81 | 04-MAY-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 645.13 | 9264.01 | 01-JAN-04:00 | 30682.81 | 04-MAY-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 134.92 | 2.03 | 02-JAN-07:10 | 9313.51 | 08-JUN-15:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 134.92 | 2.03 | 02-JAN-07:10 | 9313.51 | 08-JUN-15:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 134.92 | 2.03 | 02-JAN-07:10 | 9313.51 | 08-JUN-15:30 |
PlantLoopHeatingDemand:Facility | 2057.62 | 5749.90 | 19-JUL-01:20 | 204870.74 | 01-MAR-22:00 |
PlantLoopHeatingDemand:Plant | 2045.15 | 5749.90 | 19-JUL-01:20 | 204870.74 | 01-MAR-22:00 |
WaterSystems:PlantLoopHeatingDemand | 2045.15 | 5749.90 | 19-JUL-01:20 | 204870.74 | 01-MAR-22:00 |
General:WaterSystems:PlantLoopHeatingDemand | 546.94 | 5745.13 | 19-JUL-02:00 | 44523.89 | 17-JAN-07:10 |
HeatingCoils:EnergyTransfer | 12.46 | 0.00 | 03-JAN-16:30 | 22125.54 | 01-JAN-00:10 |
PlantLoopHeatingDemand:HVAC | 12.46 | 0.00 | 03-JAN-16:30 | 22125.54 | 01-JAN-00:10 |
HeatingCoils:PlantLoopHeatingDemand | 12.46 | 0.00 | 03-JAN-16:30 | 22125.54 | 01-JAN-00:10 |
HeatRecoveryForHeating:EnergyTransfer | 267.69 | 0.00 | 01-JAN-12:40 | 202422.46 | 05-JAN-06:40 |
HeatRecoveryForCooling:EnergyTransfer | 2745.64 | 0.00 | 01-JAN-00:10 | 361667.87 | 27-AUG-18:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 1498.22 | 0.00 | 01-JAN-00:10 | 170932.19 | 01-MAR-22:00 |
WaterSystems:EnergyTransfer | 546.94 | 5745.13 | 19-JUL-02:00 | 44523.89 | 17-JAN-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 546.94 | 5745.13 | 19-JUL-02:00 | 44523.89 | 17-JAN-07:10 |
Boilers:EnergyTransfer | 12.30 | 0.00 | 03-JAN-16:30 | 22522.82 | 02-JAN-09:10 |
Chillers:EnergyTransfer | 9226.55 | 0.00 | 01-JAN-00:10 | 753668.29 | 28-AUG-18:10 |
HeatRejection:EnergyTransfer | 12244.43 | 0.00 | 01-JAN-00:10 | 1012887.24 | 01-JUL-18:10 |
General:HeatRejection:EnergyTransfer | 12244.43 | 0.00 | 01-JAN-00:10 | 1012887.24 | 01-JUL-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -425.215 | 0.000 | 0.000 | 137.735 | 113.371 | 143.105 | 0.000 | 0.000 | 0.000 | 31.004 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.000 | -58.762 | 0.000 | 0.000 | 14.419 | 6.265 | 10.186 | 23.242 | 0.000 | 0.354 | 8.868 | 0.000 | -4.349 | 0.000 | -0.222 | -0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -43.617 | 0.000 | 0.000 | 16.144 | 7.255 | 11.795 | 0.000 | 0.000 | 0.137 | 8.386 | 0.000 | 0.000 | 0.000 | -0.099 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -40.245 | 0.000 | 0.000 | 3.511 | 8.366 | 12.471 | 0.000 | 0.000 | 0.329 | 15.773 | 0.000 | 0.000 | 0.000 | -0.206 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.000 | -21.278 | 0.000 | 0.000 | 2.717 | 1.866 | 3.598 | 0.000 | 0.000 | 0.191 | 13.022 | 0.000 | 0.000 | 0.000 | -0.116 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -626.088 | 0.000 | 0.000 | 11.206 | 4.900 | 658.131 | 0.000 | 0.000 | 0.486 | 0.000 | 0.000 | 0.000 | 0.000 | -0.316 | -48.319 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -272.983 | 0.000 | 0.000 | 181.820 | 13.221 | 14.341 | 64.740 | 0.000 | 0.775 | 12.280 | 0.000 | -13.607 | 0.000 | -0.586 | -0.001 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -922.401 | 0.000 | 0.000 | 537.682 | 123.287 | 148.998 | 86.742 | 0.000 | 2.230 | 43.176 | 0.000 | -18.009 | 0.000 | -1.705 | -0.002 |
ROOM_1_FLR_3 | 0.924 | -92.056 | 0.000 | -13.429 | 0.000 | 0.000 | 9.634 | 6.171 | 12.292 | 51.661 | 0.000 | 1.105 | 33.498 | 0.000 | -8.892 | 0.000 | -0.909 | -0.000 |
ROOM_2_FLR_3 | 1.833 | -78.058 | 0.000 | -13.718 | 0.000 | 0.000 | 9.570 | 6.170 | 12.291 | 42.381 | 0.000 | 1.065 | 28.779 | 0.000 | -9.216 | 0.000 | -1.095 | -0.001 |
ROOM_3_MULT19_FLR_3 | 0.000 | -576.163 | 0.000 | -17.864 | 0.000 | 0.000 | 0.000 | 73.685 | 228.754 | 251.149 | 0.000 | 2.627 | 124.762 | 0.000 | -81.785 | 0.000 | -5.164 | -0.004 |
ROOM_4_MULT19_FLR_3 | 2.081 | -528.045 | 0.000 | -185.118 | 0.000 | 0.000 | 182.152 | 73.705 | 228.817 | 168.163 | 0.000 | 5.951 | 114.418 | 0.000 | -48.694 | 0.000 | -13.430 | -0.008 |
ROOM_5_FLR_3 | 0.909 | -91.824 | 0.000 | -13.428 | 0.000 | 0.000 | 9.630 | 6.171 | 12.292 | 51.424 | 0.000 | 1.105 | 33.187 | 0.000 | -8.543 | 0.000 | -0.923 | -0.001 |
ROOM_6_FLR_3 | 1.771 | -77.684 | 0.000 | -13.724 | 0.000 | 0.000 | 9.569 | 6.170 | 12.291 | 41.861 | 0.000 | 1.065 | 28.377 | 0.000 | -8.608 | 0.000 | -1.087 | -0.001 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.000 | -223.013 | 0.000 | 0.000 | 111.145 | 56.739 | 0.000 | 50.706 | 0.000 | 1.004 | 15.945 | 0.000 | -11.893 | 0.000 | -0.632 | -0.000 |
ROOM_1_FLR_6 | 0.570 | -23.708 | 0.000 | -3.358 | 0.000 | 0.000 | 2.409 | 1.543 | 3.073 | 12.847 | 0.000 | 0.275 | 8.756 | 0.000 | -2.176 | 0.000 | -0.231 | -0.000 |
ROOM_2_FLR_6 | 0.960 | -20.299 | 0.000 | -3.422 | 0.000 | 0.000 | 2.395 | 1.543 | 3.073 | 10.550 | 0.000 | 0.265 | 7.452 | 0.000 | -2.244 | 0.000 | -0.272 | -0.000 |
ROOM_3_MULT9_FLR_6 | 0.458 | -141.625 | 0.000 | -21.581 | 0.000 | 0.000 | 21.660 | 8.728 | 27.097 | 66.221 | 0.000 | 1.318 | 49.400 | 0.000 | -10.040 | 0.000 | -1.637 | -0.001 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -500.621 | 0.000 | 0.000 | 315.398 | 28.638 | 175.857 | 15.888 | 0.000 | 0.481 | 0.000 | 0.000 | -7.369 | 0.000 | -0.399 | -27.872 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -536.634 | 0.000 | 0.000 | 314.734 | 28.638 | 175.857 | 15.530 | 0.000 | 0.479 | 9.463 | 0.000 | -7.662 | 0.000 | -0.405 | -0.000 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -645.115 | 0.000 | 0.000 | 28.217 | 13.339 | 540.650 | 23.905 | 0.000 | 0.428 | 44.404 | 0.000 | -5.469 | 0.000 | -0.359 | -0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.000 | -134.919 | 0.000 | 0.000 | 29.786 | 15.012 | 0.000 | 23.332 | 0.000 | 0.438 | 71.775 | 0.000 | -5.161 | 0.000 | -0.262 | -0.001 |
Total Facility | 9.505 | -1629.461 | 0.000 | -4736.532 | 0.000 | 0.000 | 1951.532 | 604.780 | 2434.967 | 1000.343 | 0.000 | 22.107 | 702.726 | 0.000 | -253.719 | 0.000 | -30.055 | -76.212 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 27-SEP-21:00 | 0.00 | 0.00 | 0.00 | -23613.17 | 0.00 | 0.00 | 5924.41 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 322.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 02-OCT-13:10 | 0.00 | 0.00 | 0.00 | -3776.86 | 0.00 | 0.00 | 150.60 | 142.31 | 252.59 | 3625.40 | 0.00 | 33.52 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -427.56 |
RETAIL_2_FLR_1 | 12-JUN-20:10 | 0.00 | 0.00 | 0.00 | -2555.84 | 0.00 | 0.00 | 697.61 | 527.34 | 752.15 | 0.00 | 0.00 | 14.89 | 563.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 12-JUN-20:00 | 0.00 | 0.00 | 0.00 | -2650.36 | 0.00 | 0.00 | 129.08 | 684.18 | 839.45 | 0.00 | 0.00 | 35.80 | 961.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 12-JUN-20:10 | 0.00 | 0.00 | 0.00 | -1268.70 | 0.00 | 0.00 | 113.48 | 135.66 | 229.41 | 0.00 | 0.00 | 20.30 | 769.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 12-JUN-20:00 | 0.00 | 0.00 | 0.00 | -39727.82 | 0.00 | 0.00 | 408.86 | 400.68 | 44299.38 | 0.00 | 0.00 | 48.89 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5429.99 |
CAFE_FLR_1 | 12-JUN-21:10 | 0.00 | 0.00 | 0.00 | -13706.55 | 0.00 | 0.00 | 8907.83 | 1048.97 | 711.25 | 1346.34 | 0.00 | 76.97 | 1615.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 12-JUN-21:10 | 0.00 | 0.00 | 0.00 | -48369.07 | 0.00 | 0.00 | 26439.86 | 7096.92 | 7389.94 | 1828.71 | 0.00 | 219.89 | 5393.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 05-JUN-18:02 | 0.00 | -11503.23 | 0.00 | -739.98 | 0.00 | 0.00 | 335.47 | 422.72 | 516.26 | 3326.17 | 0.00 | 112.14 | 7530.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 04-JUL-18:02 | 0.00 | -11566.07 | 0.00 | -738.37 | 0.00 | 0.00 | 283.21 | 474.90 | 516.20 | 3758.70 | 0.00 | 107.32 | 7164.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 02-OCT-13:30 | 0.00 | -45532.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1587.99 | 5097.90 | 41387.53 | 0.00 | 323.34 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2864.61 |
ROOM_4_MULT19_FLR_3 | 05-AUG-15:02 | 0.00 | -80236.84 | 0.00 | -10047.57 | 0.00 | 0.00 | 2483.55 | 1872.11 | 5687.67 | 17299.52 | 0.00 | 442.12 | 62499.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 04-MAY-18:02 | 0.00 | -10399.62 | 0.00 | -742.43 | 0.00 | 0.00 | 335.50 | 422.72 | 516.26 | 1884.23 | 0.00 | 107.97 | 7875.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 06-APR-08:51 | 0.00 | -11517.34 | 0.00 | -914.06 | 0.00 | 0.00 | 73.05 | 208.96 | 452.99 | 5581.34 | 0.00 | 2.82 | 6112.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 12-JUN-18:13 | 0.00 | 0.00 | 0.00 | -12890.15 | 0.00 | 0.00 | 4080.27 | 4124.45 | 0.00 | 2875.30 | 0.00 | 132.69 | 1677.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 07-JUL-18:02 | 0.00 | -3114.31 | 0.00 | -183.60 | 0.00 | 0.00 | 83.87 | 105.68 | 129.07 | 630.03 | 0.00 | 23.81 | 2325.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 01-MAY-18:02 | 0.00 | -3127.98 | 0.00 | -184.34 | 0.00 | 0.00 | 83.87 | 105.67 | 129.05 | 694.01 | 0.00 | 26.83 | 2272.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 20-SEP-15:02 | 0.00 | -14748.61 | 0.00 | -1191.79 | 0.00 | 0.00 | 529.39 | 188.10 | 603.86 | 5159.99 | 0.00 | 77.45 | 9381.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 12-JUN-21:10 | 0.00 | 0.00 | 0.00 | -25285.04 | 0.00 | 0.00 | 15644.35 | 1842.08 | 6747.90 | 708.82 | 0.00 | 48.97 | 292.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 12-JUN-21:10 | 0.00 | 0.00 | 0.00 | -26474.03 | 0.00 | 0.00 | 15644.27 | 1842.08 | 6747.90 | 695.54 | 0.00 | 48.97 | 1495.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 04-MAY-10:50 | 0.00 | 0.00 | 0.00 | -30685.12 | 0.00 | 0.00 | 307.65 | 303.01 | 23951.61 | 3154.01 | 0.00 | 55.14 | 2913.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 08-JUN-15:25 | 0.00 | 0.00 | 0.00 | -9314.28 | 0.00 | 0.00 | 771.15 | 341.02 | 0.00 | 1909.15 | 0.00 | 66.76 | 6226.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-JUN-18:02 | 0.00 | -176635.57 | 0.00 | -230107.13 | 0.00 | 0.00 | 73909.71 | 41123.54 | 121562.63 | 58584.88 | 0.00 | 2799.64 | 108762.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 02-JAN-09:02 | 5664.71 | 409.56 | 0.00 | -409.56 | 0.00 | 0.00 | 101.52 | 208.98 | 453.05 | 260.59 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -88.38 | -6600.47 |
ROOM_2_FLR_3 | 03-JAN-09:02 | 5778.34 | 367.48 | 0.00 | -367.48 | 0.00 | 0.00 | 104.18 | 208.96 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -595.12 | 0.00 | -81.71 | -5867.65 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 28-JAN-16:04 | 33705.98 | 6880.65 | 0.00 | -6880.65 | 0.00 | 0.00 | 2630.72 | 1872.11 | 5687.67 | 945.23 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4258.27 | -40583.45 |
ROOM_5_FLR_3 | 29-DEC-16:04 | 4129.72 | 536.78 | 0.00 | -536.78 | 0.00 | 0.00 | 240.26 | 132.99 | 273.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -852.23 | 0.00 | -310.76 | -3613.91 |
ROOM_6_FLR_3 | 02-JAN-09:02 | 4721.86 | 413.73 | 0.00 | -413.73 | 0.00 | 0.00 | 100.84 | 208.96 | 452.99 | 1212.89 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -88.78 | -6608.76 |
CORRIDOR_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 02-JAN-09:02 | 1771.01 | 93.05 | 0.00 | -93.05 | 0.00 | 0.00 | 26.12 | 52.25 | 113.26 | 82.80 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -21.30 | -2024.13 |
ROOM_2_FLR_6 | 03-JAN-09:02 | 1803.99 | 82.44 | 0.00 | -82.44 | 0.00 | 0.00 | 26.76 | 52.24 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -133.30 | 0.00 | -19.63 | -1843.31 |
ROOM_3_MULT9_FLR_6 | 29-DEC-16:04 | 4386.78 | 862.67 | 0.00 | -862.67 | 0.00 | 0.00 | 529.39 | 188.10 | 603.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -949.27 | 0.00 | -864.46 | -3894.40 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-JAN-16:04 | -99175.51 | 123498.36 | 0.00 | -123498.36 | 0.00 | 0.00 | 33089.82 | 13473.85 | 78232.63 | 37124.53 | 0.00 | 0.00 | 0.00 | 0.00 | -93.16 | 0.00 | -6420.33 | -56231.83 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 22.1894 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.0876 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6716 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6716 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2967 | 2.2967 | 1.2080 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3398 | 0.3398 | 0.1787 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2412 | 0.2412 | 0.1269 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2408 | 0.2408 | 0.1266 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1317 | 0.1317 | 0.0693 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3703 | 3.3703 | 1.7728 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4390 | 1.4390 | 0.7569 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.8545 | 4.8545 | 2.5535 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3778 | 1.3778 | 0.7247 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3482 | 2.3482 | 1.2352 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4575 | 2.4575 | 1.2926 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2629 | 2.2629 | 1.1903 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8291 | 0.8291 | 0.4361 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 22.1894 | 22.0876 | 22.1894 | 11.6716 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2080 | 1.2080 | 1.2080 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1787 | 0.1787 | 0.1787 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1269 | 0.1269 | 0.1269 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1266 | 0.1266 | 0.1266 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0693 | 0.0693 | 0.0693 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7728 | 1.7728 | 1.7728 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7569 | 0.7569 | 0.7569 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5535 | 2.5535 | 2.5535 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7247 | 0.7247 | 0.7247 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2352 | 1.2352 | 1.2352 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2926 | 1.2926 | 1.2926 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1903 | 1.1903 | 1.1903 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4361 | 0.4361 | 0.4361 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6716 | 11.6716 | 11.6716 | 11.6716 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 67.50 |
Number of hours not met | 67.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 20.35 | 33021.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3017.88 | 269604.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 604.78 | 50471.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 174.46 | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 952.41 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 22.46 | 1283.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 631.18 | 47309.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 168.32 | 8210.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 295.00 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4738.76 | 682.08 | 69344.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Other | 0.00 | 39397.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.84 | 1308.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 21.40 | 716.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1772.46 | 7760.43 |
Natural Gas | 1788.84 | 2491.27 |
Additional | 0.00 | 0.00 |
Total | 3561.30 | 10251.70 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 53.31 |
Space Heating | 0.00 |
Space Cooling | 266.00 |
Fans (All) | 55.63 |
Service Water Heating | 40.09 |
Receptacle Equipment | 152.32 |
Miscellaneous (All) | 684.02 |
Subtotal | 684.02 |
Natural Gas [MJ/m2] | |
Space Heating | 1.79 |
Service Water Heating | 60.12 |
Miscellaneous (All) | 219.59 |
Subtotal | 219.59 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.90 |
Space Heating | 0.20 |
Space Cooling | 29.44 |
Fans (All) | 6.16 |
Service Water Heating | 11.09 |
Receptacle Equipment | 34.31 |
Miscellaneous | 12.91 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2398. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 2482. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7925.17 | 834.83 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7925.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 834.83 | 0.00 | 0.00 | 0.00 |
Average | 8722.05 | 37.95 | 0.00 | 0.00 | 0.00 |
Sum | 191885.17 | 834.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8706.67 | 53.33 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 6770.83 | 1989.17 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 7208.17 | 1551.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8749.50 | 10.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7242.67 | 1517.33 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8754.33 | 5.67 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8731.00 | 29.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8565.50 | 194.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8746.67 | 13.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 7002.83 | 1757.17 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 7159.50 | 1600.50 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8632.17 | 127.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 6770.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1989.17 | 0.00 | 0.00 | 0.00 |
Average | 8357.72 | 402.28 | 0.00 | 0.00 | 0.00 |
Sum | 183869.83 | 8850.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 58573.83 | 582.17 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 473665.67 | 236751.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1565173.67 | 550255.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4150.17 | 3.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4150.17 | 3.83 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4149.50 | 4.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 96952.33 | 3405.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4149.67 | 4.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 878655.50 | 367059.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 908553.00 | 337162.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 107302.50 | 966.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1565173.67 | 550255.33 | 0.00 | 0.00 | 0.00 |
Average | 220878.00 | 68009.05 | 0.00 | 0.00 | 0.00 |
Sum | 4859316.00 | 1496199.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:47
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.332555E+11 | 17415.49 | 13-JAN-22:00 | 17.60 | 13.76 | 0.810610E+10 | 4837.05 | 25-JAN-23:10 | 16.43 | 13.26 |
February | 0.275069E+11 | 15143.87 | 01-FEB-22:00 | 11.70 | 9.20 | 0.699115E+10 | 4836.99 | 02-FEB-22:30 | 11.55 | 10.15 |
March | 0.283737E+11 | 13047.48 | 12-MAR-10:33 | 27.43 | 17.74 | 0.725944E+10 | 4655.61 | 01-MAR-22:19 | 27.43 | 17.74 |
April | 0.274574E+11 | 13344.07 | 16-APR-10:33 | 36.27 | 21.85 | 0.684153E+10 | 4374.92 | 07-APR-22:10 | 36.27 | 21.85 |
May | 0.305803E+11 | 14125.74 | 18-MAY-18:10 | 39.45 | 24.21 | 0.739557E+10 | 4602.26 | 12-MAY-22:10 | 39.45 | 24.21 |
June | 0.325405E+11 | 15414.08 | 12-JUN-18:10 | 42.22 | 22.60 | 0.770600E+10 | 4837.02 | 28-JUN-21:30 | 31.80 | 26.58 |
July | 0.396246E+11 | 21033.20 | 18-JUL-21:00 | 27.20 | 26.40 | 0.819656E+10 | 4837.04 | 24-JUL-21:19 | 28.33 | 26.95 |
August | 0.440255E+11 | 23313.34 | 09-AUG-21:00 | 31.70 | 26.83 | 0.826351E+10 | 4837.06 | 23-AUG-21:19 | 27.03 | 25.92 |
September | 0.431360E+11 | 23612.19 | 27-SEP-21:00 | 27.70 | 23.37 | 0.797550E+10 | 4837.06 | 27-SEP-21:19 | 27.53 | 23.38 |
October | 0.425246E+11 | 22561.02 | 05-OCT-21:00 | 27.50 | 19.87 | 0.822898E+10 | 4837.09 | 24-OCT-21:19 | 21.43 | 16.47 |
November | 0.387781E+11 | 21839.98 | 01-NOV-21:00 | 19.30 | 15.01 | 0.795145E+10 | 4837.08 | 09-NOV-23:10 | 19.03 | 16.29 |
December | 0.374092E+11 | 20779.37 | 01-DEC-22:00 | 11.40 | 11.31 | 0.821018E+10 | 4837.07 | 14-DEC-22:40 | 14.40 | 12.54 |
Annual Sum or Average | 0.425212E+12 | 0.931260E+11 | ||||||||
Minimum of Months | 0.274574E+11 | 13047.48 | 11.40 | 9.20 | 0.684153E+10 | 4374.92 | 11.55 | 10.15 | ||
Maximum of Months | 0.440255E+11 | 23612.19 | 42.22 | 26.83 | 0.826351E+10 | 4837.09 | 39.45 | 26.95 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324845E+10 | 2049.79 | 12-JAN-13:50 | 23.12 | 13.90 | 0.659292E+09 | 432.88 | 13-JAN-22:30 | 17.55 | 13.65 |
February | 0.351698E+10 | 2653.64 | 20-FEB-13:00 | 25.90 | 13.36 | 0.626890E+09 | 470.06 | 22-FEB-22:30 | 19.25 | 14.18 |
March | 0.467544E+10 | 3071.60 | 13-MAR-13:20 | 32.07 | 18.93 | 0.756871E+09 | 491.84 | 13-MAR-22:10 | 21.72 | 17.00 |
April | 0.539264E+10 | 3370.99 | 15-APR-13:40 | 39.93 | 20.34 | 0.782066E+09 | 491.84 | 19-APR-21:19 | 31.50 | 18.57 |
May | 0.598097E+10 | 3419.60 | 04-MAY-15:04 | 42.23 | 22.18 | 0.826891E+09 | 491.83 | 08-MAY-21:30 | 33.55 | 19.72 |
June | 0.578121E+10 | 3471.50 | 12-JUN-18:04 | 42.22 | 22.60 | 0.799618E+09 | 491.83 | 12-JUN-21:19 | 36.80 | 22.54 |
July | 0.563347E+10 | 3195.59 | 07-JUL-18:03 | 38.10 | 25.41 | 0.822872E+09 | 491.83 | 01-JUL-01:19 | 38.10 | 25.41 |
August | 0.538868E+10 | 2991.61 | 07-AUG-18:03 | 35.77 | 27.05 | 0.820640E+09 | 491.82 | 07-AUG-21:30 | 33.05 | 27.34 |
September | 0.523687E+10 | 3466.35 | 26-SEP-13:30 | 35.30 | 22.98 | 0.776916E+09 | 491.83 | 27-SEP-21:19 | 27.53 | 23.38 |
October | 0.555450E+10 | 3776.95 | 02-OCT-13:10 | 36.23 | 21.17 | 0.793161E+09 | 491.84 | 24-OCT-22:10 | 21.02 | 16.79 |
November | 0.471271E+10 | 3372.31 | 04-NOV-13:20 | 30.17 | 17.23 | 0.718431E+09 | 481.88 | 08-NOV-22:30 | 19.75 | 17.48 |
December | 0.364006E+10 | 2682.51 | 02-DEC-13:30 | 23.70 | 13.05 | 0.671378E+09 | 447.13 | 28-DEC-22:30 | 17.65 | 13.86 |
Annual Sum or Average | 0.587620E+11 | 0.905503E+10 | ||||||||
Minimum of Months | 0.324845E+10 | 2049.79 | 23.12 | 13.05 | 0.626890E+09 | 432.88 | 17.55 | 13.65 | ||
Maximum of Months | 0.598097E+10 | 3776.95 | 42.23 | 27.05 | 0.826891E+09 | 491.84 | 38.10 | 27.34 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.291073E+10 | 1377.28 | 12-JAN-21:00 | 14.50 | 11.65 | 0.864022E+09 | 568.63 | 12-JAN-22:30 | 13.00 | 10.79 |
February | 0.281026E+10 | 1671.54 | 22-FEB-22:00 | 19.90 | 14.33 | 0.809933E+09 | 569.55 | 21-FEB-23:10 | 19.90 | 14.33 |
March | 0.346911E+10 | 2064.09 | 29-MAR-21:00 | 26.60 | 18.43 | 0.938640E+09 | 569.55 | 17-MAR-22:10 | 26.60 | 18.43 |
April | 0.386121E+10 | 2369.79 | 28-APR-21:00 | 33.70 | 19.17 | 0.928327E+09 | 569.54 | 30-APR-23:19 | 30.13 | 17.77 |
May | 0.428659E+10 | 2496.27 | 04-MAY-20:10 | 34.88 | 23.02 | 0.965197E+09 | 569.54 | 01-MAY-00:20 | 34.88 | 23.02 |
June | 0.417018E+10 | 2555.54 | 12-JUN-20:10 | 38.43 | 22.54 | 0.935418E+09 | 569.54 | 03-JUN-01:19 | 38.43 | 22.54 |
July | 0.415466E+10 | 2448.55 | 03-JUL-21:00 | 35.50 | 27.32 | 0.962779E+09 | 569.54 | 01-JUL-01:19 | 35.50 | 27.32 |
August | 0.405062E+10 | 2355.46 | 07-AUG-21:00 | 33.40 | 27.28 | 0.966073E+09 | 569.54 | 05-AUG-01:19 | 33.40 | 27.28 |
September | 0.380144E+10 | 2247.70 | 22-SEP-21:00 | 29.50 | 25.17 | 0.927572E+09 | 569.54 | 04-SEP-23:19 | 29.50 | 25.17 |
October | 0.379602E+10 | 2218.69 | 02-OCT-20:10 | 27.12 | 20.31 | 0.956497E+09 | 569.55 | 24-OCT-22:10 | 21.02 | 16.79 |
November | 0.329307E+10 | 1844.74 | 09-NOV-22:00 | 19.80 | 16.60 | 0.902552E+09 | 569.55 | 09-NOV-23:10 | 19.03 | 16.29 |
December | 0.301308E+10 | 1470.22 | 01-DEC-22:00 | 11.40 | 11.31 | 0.882750E+09 | 569.55 | 28-DEC-23:10 | 17.10 | 13.73 |
Annual Sum or Average | 0.436170E+11 | 0.110398E+11 | ||||||||
Minimum of Months | 0.281026E+10 | 1377.28 | 11.40 | 11.31 | 0.809933E+09 | 568.63 | 13.00 | 10.79 | ||
Maximum of Months | 0.428659E+10 | 2555.54 | 38.43 | 27.32 | 0.966073E+09 | 569.55 | 38.43 | 27.32 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.246469E+10 | 1170.65 | 26-JAN-21:00 | 14.80 | 11.71 | 0.162804E+09 | 104.57 | 26-JAN-22:10 | 14.45 | 11.64 |
February | 0.245274E+10 | 1289.76 | 23-FEB-19:10 | 21.65 | 14.67 | 0.154826E+09 | 111.41 | 24-FEB-22:19 | 19.30 | 16.56 |
March | 0.306823E+10 | 1482.47 | 29-MAR-18:08 | 30.77 | 18.53 | 0.184595E+09 | 118.53 | 29-MAR-21:30 | 26.00 | 18.21 |
April | 0.342886E+10 | 2106.01 | 28-APR-20:00 | 35.20 | 19.07 | 0.191309E+09 | 120.46 | 19-APR-21:10 | 35.20 | 19.07 |
May | 0.407498E+10 | 2449.26 | 04-MAY-20:00 | 35.20 | 23.02 | 0.203881E+09 | 120.45 | 05-MAY-23:00 | 33.90 | 18.52 |
June | 0.411330E+10 | 2650.28 | 12-JUN-20:00 | 38.70 | 22.52 | 0.197691E+09 | 120.45 | 07-JUN-21:30 | 38.70 | 22.52 |
July | 0.418932E+10 | 2563.40 | 07-JUL-20:00 | 35.70 | 25.97 | 0.203990E+09 | 120.45 | 10-JUL-21:30 | 27.40 | 23.56 |
August | 0.399233E+10 | 2377.45 | 08-AUG-20:00 | 33.20 | 27.10 | 0.204738E+09 | 120.45 | 07-AUG-21:30 | 33.20 | 27.10 |
September | 0.356306E+10 | 2123.87 | 01-SEP-20:00 | 31.50 | 26.31 | 0.194860E+09 | 120.45 | 27-SEP-21:19 | 27.53 | 23.38 |
October | 0.339602E+10 | 1799.17 | 02-OCT-20:00 | 27.40 | 20.32 | 0.195650E+09 | 120.45 | 02-OCT-21:19 | 25.47 | 20.14 |
November | 0.289464E+10 | 1383.60 | 01-NOV-18:08 | 24.40 | 15.69 | 0.175854E+09 | 115.08 | 10-NOV-22:19 | 18.77 | 15.74 |
December | 0.260641E+10 | 1222.84 | 01-DEC-21:00 | 12.30 | 11.75 | 0.167732E+09 | 107.82 | 01-DEC-22:10 | 11.27 | 11.19 |
Annual Sum or Average | 0.402446E+11 | 0.223793E+10 | ||||||||
Minimum of Months | 0.245274E+10 | 1170.65 | 12.30 | 11.71 | 0.154826E+09 | 104.57 | 11.27 | 11.19 | ||
Maximum of Months | 0.418932E+10 | 2650.28 | 38.70 | 27.10 | 0.204738E+09 | 120.46 | 38.70 | 27.10 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131189E+10 | 622.89 | 14-JAN-11:33 | 19.60 | 14.39 | 0.123278E+09 | 77.97 | 13-JAN-23:10 | 19.60 | 14.39 |
February | 0.131710E+10 | 699.10 | 23-FEB-11:33 | 24.77 | 14.09 | 0.117326E+09 | 83.10 | 24-FEB-23:10 | 19.05 | 16.42 |
March | 0.165114E+10 | 803.70 | 12-MAR-10:33 | 27.43 | 17.74 | 0.139953E+09 | 88.63 | 29-MAR-22:10 | 25.20 | 17.89 |
April | 0.182322E+10 | 951.33 | 28-APR-21:00 | 33.70 | 19.17 | 0.145595E+09 | 92.66 | 19-APR-21:19 | 33.70 | 19.17 |
May | 0.212257E+10 | 1145.53 | 04-MAY-20:00 | 35.20 | 23.02 | 0.156449E+09 | 92.66 | 05-MAY-23:00 | 33.90 | 18.52 |
June | 0.216305E+10 | 1268.62 | 12-JUN-20:10 | 38.43 | 22.54 | 0.151761E+09 | 92.66 | 07-JUN-21:30 | 38.43 | 22.54 |
July | 0.218572E+10 | 1210.83 | 07-JUL-20:10 | 35.53 | 25.98 | 0.156591E+09 | 92.66 | 06-JUL-21:30 | 35.53 | 25.98 |
August | 0.206407E+10 | 1104.46 | 08-AUG-20:10 | 33.08 | 27.12 | 0.157051E+09 | 92.66 | 07-AUG-21:30 | 33.08 | 27.12 |
September | 0.186819E+10 | 962.60 | 01-SEP-21:00 | 30.80 | 26.02 | 0.148807E+09 | 92.66 | 27-SEP-21:19 | 27.53 | 23.38 |
October | 0.181783E+10 | 870.48 | 01-OCT-10:33 | 31.23 | 19.64 | 0.148403E+09 | 92.66 | 02-OCT-21:40 | 25.23 | 20.09 |
November | 0.155654E+10 | 753.90 | 11-NOV-11:33 | 26.80 | 17.21 | 0.133235E+09 | 85.77 | 09-NOV-22:49 | 26.80 | 17.21 |
December | 0.139638E+10 | 651.09 | 03-DEC-11:33 | 22.07 | 14.16 | 0.126948E+09 | 79.99 | 01-DEC-22:40 | 22.07 | 14.16 |
Annual Sum or Average | 0.212777E+11 | 0.170540E+10 | ||||||||
Minimum of Months | 0.131189E+10 | 622.89 | 19.60 | 14.09 | 0.117326E+09 | 77.97 | 19.05 | 14.16 | ||
Maximum of Months | 0.218572E+10 | 1268.62 | 38.43 | 27.12 | 0.157051E+09 | 92.66 | 38.43 | 27.12 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.501289E+11 | 37470.78 | 26-JAN-21:00 | 14.80 | 11.71 | 0.586730E+09 | 381.70 | 23-JAN-22:10 | 14.80 | 11.71 |
February | 0.462064E+11 | 37999.47 | 22-FEB-21:00 | 21.10 | 14.62 | 0.532746E+09 | 381.70 | 21-FEB-22:10 | 21.10 | 14.62 |
March | 0.527709E+11 | 38697.86 | 28-MAR-20:00 | 28.80 | 18.84 | 0.594395E+09 | 381.72 | 03-MAR-22:10 | 28.80 | 18.84 |
April | 0.525914E+11 | 39330.45 | 28-APR-20:00 | 35.20 | 19.07 | 0.577666E+09 | 381.77 | 11-APR-21:10 | 35.20 | 19.07 |
May | 0.553061E+11 | 39708.50 | 04-MAY-20:00 | 35.20 | 23.02 | 0.599270E+09 | 381.74 | 02-MAY-21:10 | 35.20 | 23.02 |
June | 0.534116E+11 | 39726.95 | 12-JUN-20:00 | 38.70 | 22.52 | 0.580287E+09 | 381.76 | 23-JUN-21:10 | 34.93 | 26.84 |
July | 0.546752E+11 | 39625.91 | 07-JUL-20:00 | 35.70 | 25.97 | 0.598750E+09 | 381.80 | 21-JUL-21:10 | 32.72 | 26.02 |
August | 0.545659E+11 | 39233.13 | 07-AUG-20:00 | 34.20 | 27.22 | 0.599499E+09 | 381.81 | 08-AUG-21:10 | 32.47 | 27.18 |
September | 0.521578E+11 | 38944.47 | 22-SEP-20:00 | 30.40 | 25.15 | 0.577672E+09 | 381.81 | 01-SEP-21:10 | 30.40 | 25.15 |
October | 0.534472E+11 | 38827.59 | 02-OCT-20:00 | 27.40 | 20.32 | 0.595063E+09 | 381.77 | 03-OCT-21:10 | 27.92 | 22.53 |
November | 0.504045E+11 | 38137.72 | 09-NOV-21:00 | 20.50 | 16.99 | 0.572938E+09 | 381.76 | 02-NOV-21:10 | 20.50 | 16.99 |
December | 0.504157E+11 | 37512.46 | 28-DEC-21:00 | 19.00 | 14.10 | 0.587958E+09 | 381.72 | 28-DEC-22:10 | 17.95 | 13.92 |
Annual Sum or Average | 0.626082E+12 | 0.700297E+10 | ||||||||
Minimum of Months | 0.462064E+11 | 37470.78 | 14.80 | 11.71 | 0.532746E+09 | 381.70 | 14.80 | 11.71 | ||
Maximum of Months | 0.553061E+11 | 39726.95 | 38.70 | 27.22 | 0.599499E+09 | 381.81 | 35.20 | 27.18 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184314E+11 | 9369.13 | 08-JAN-13:00 | 20.10 | 12.07 | 0.101382E+11 | 6462.23 | 25-JAN-23:10 | 16.43 | 13.26 |
February | 0.180199E+11 | 10746.92 | 20-FEB-13:00 | 25.90 | 13.36 | 0.946938E+10 | 6462.53 | 27-FEB-23:10 | 15.28 | 12.98 |
March | 0.221382E+11 | 11741.16 | 13-MAR-15:03 | 32.83 | 18.67 | 0.108266E+11 | 6462.67 | 15-MAR-22:10 | 19.55 | 13.78 |
April | 0.238960E+11 | 13003.30 | 27-APR-21:10 | 34.92 | 17.25 | 0.105628E+11 | 6462.04 | 08-APR-01:19 | 34.92 | 17.25 |
May | 0.258496E+11 | 13473.03 | 05-MAY-21:10 | 36.73 | 18.90 | 0.109517E+11 | 6461.99 | 06-MAY-01:19 | 32.57 | 18.42 |
June | 0.250125E+11 | 13702.77 | 12-JUN-21:10 | 36.95 | 22.55 | 0.106076E+11 | 6461.97 | 10-JUN-01:19 | 36.95 | 22.55 |
July | 0.251648E+11 | 13270.75 | 07-JUL-21:10 | 34.58 | 25.98 | 0.109127E+11 | 6461.96 | 08-JUL-01:19 | 32.27 | 25.66 |
August | 0.245899E+11 | 12850.19 | 07-AUG-21:10 | 33.28 | 27.30 | 0.109423E+11 | 6461.94 | 05-AUG-01:19 | 33.28 | 27.30 |
September | 0.236747E+11 | 12440.67 | 26-SEP-15:03 | 36.05 | 22.65 | 0.105351E+11 | 6461.97 | 04-SEP-23:19 | 36.05 | 22.65 |
October | 0.249165E+11 | 13118.75 | 02-OCT-15:03 | 36.32 | 21.08 | 0.109104E+11 | 6462.67 | 24-OCT-22:10 | 21.02 | 16.79 |
November | 0.220231E+11 | 12444.80 | 04-NOV-13:10 | 30.13 | 17.24 | 0.104516E+11 | 6462.60 | 09-NOV-23:10 | 19.03 | 16.29 |
December | 0.192634E+11 | 11047.40 | 02-DEC-13:20 | 23.57 | 13.02 | 0.103405E+11 | 6462.41 | 28-DEC-23:10 | 17.10 | 13.73 |
Annual Sum or Average | 0.272980E+12 | 0.126649E+12 | ||||||||
Minimum of Months | 0.180199E+11 | 9369.13 | 20.10 | 12.07 | 0.946938E+10 | 6461.94 | 15.28 | 12.98 | ||
Maximum of Months | 0.258496E+11 | 13702.77 | 36.95 | 27.30 | 0.109517E+11 | 6462.67 | 36.95 | 27.30 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.635677E+11 | 32697.09 | 13-JAN-22:10 | 17.58 | 13.72 | 0.308081E+11 | 19185.53 | 25-JAN-23:10 | 16.43 | 13.26 |
February | 0.610552E+11 | 36499.34 | 22-FEB-22:10 | 19.68 | 14.28 | 0.284681E+11 | 19185.95 | 27-FEB-23:10 | 15.28 | 12.98 |
March | 0.741298E+11 | 40586.88 | 29-MAR-21:10 | 26.40 | 18.36 | 0.321996E+11 | 19186.15 | 17-MAR-22:10 | 26.40 | 18.36 |
April | 0.795090E+11 | 45007.68 | 27-APR-21:10 | 34.92 | 17.25 | 0.313208E+11 | 19185.34 | 08-APR-01:19 | 34.92 | 17.25 |
May | 0.872386E+11 | 46979.46 | 05-MAY-21:10 | 36.73 | 18.90 | 0.324798E+11 | 19185.20 | 06-MAY-01:19 | 32.57 | 18.42 |
June | 0.853324E+11 | 48358.93 | 12-JUN-21:10 | 36.95 | 22.55 | 0.315047E+11 | 19185.16 | 03-JUN-01:19 | 36.95 | 22.55 |
July | 0.869982E+11 | 47384.30 | 07-JUL-21:10 | 34.58 | 25.98 | 0.324304E+11 | 19185.15 | 08-JUL-01:19 | 32.27 | 25.66 |
August | 0.855369E+11 | 45944.18 | 08-AUG-21:10 | 32.47 | 27.18 | 0.325524E+11 | 19185.14 | 05-AUG-01:19 | 32.47 | 27.18 |
September | 0.805738E+11 | 44327.32 | 22-SEP-21:10 | 29.42 | 25.15 | 0.313856E+11 | 19185.23 | 04-SEP-23:19 | 29.42 | 25.15 |
October | 0.812252E+11 | 43653.00 | 03-OCT-21:10 | 27.92 | 22.53 | 0.324445E+11 | 19186.10 | 24-OCT-22:10 | 21.02 | 16.79 |
November | 0.715186E+11 | 38892.31 | 09-NOV-22:10 | 19.68 | 16.56 | 0.311484E+11 | 19186.01 | 09-NOV-23:10 | 19.03 | 16.29 |
December | 0.657058E+11 | 34215.78 | 28-DEC-22:10 | 17.95 | 13.92 | 0.313017E+11 | 19185.77 | 28-DEC-23:10 | 17.10 | 13.73 |
Annual Sum or Average | 0.922391E+12 | 0.378044E+12 | ||||||||
Minimum of Months | 0.610552E+11 | 32697.09 | 17.58 | 13.72 | 0.284681E+11 | 19185.14 | 15.28 | 12.98 | ||
Maximum of Months | 0.872386E+11 | 48358.93 | 36.95 | 27.18 | 0.325524E+11 | 19186.15 | 36.95 | 27.18 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.455843E+09 | 2866.14 | 12-JAN-16:01 | 23.13 | 14.50 | 97530284.00 | 56.69 | 13-JAN-22:10 | 17.58 | 13.72 |
February | 0.902429E+09 | 2982.88 | 24-FEB-16:01 | 26.18 | 17.45 | 88826848.85 | 56.69 | 22-FEB-22:19 | 26.18 | 17.45 |
March | 0.195290E+10 | 2943.28 | 04-MAR-16:01 | 26.57 | 15.69 | 98994493.92 | 56.70 | 29-MAR-02:20 | 22.07 | 18.67 |
April | 0.296026E+10 | 3032.95 | 28-APR-18:02 | 38.13 | 19.51 | 95973530.86 | 56.70 | 17-APR-21:40 | 38.13 | 19.51 |
May | 0.348703E+10 | 3059.12 | 01-MAY-18:02 | 40.17 | 22.26 | 99290202.01 | 56.70 | 05-MAY-00:00 | 30.10 | 21.23 |
June | 0.332020E+10 | 3060.74 | 05-JUN-18:02 | 40.98 | 23.28 | 96084438.56 | 56.70 | 12-JUN-02:39 | 33.43 | 23.90 |
July | 0.305915E+10 | 3016.97 | 02-JUL-18:02 | 39.48 | 26.63 | 99135475.20 | 56.70 | 08-JUL-00:30 | 32.60 | 25.54 |
August | 0.280659E+10 | 2981.47 | 15-AUG-18:02 | 32.63 | 27.21 | 99235252.59 | 56.70 | 03-AUG-21:10 | 32.63 | 27.21 |
September | 0.258438E+10 | 2973.79 | 03-SEP-15:02 | 28.28 | 25.37 | 95935677.39 | 56.70 | 27-SEP-21:10 | 27.62 | 23.38 |
October | 0.246971E+10 | 2979.26 | 06-OCT-18:02 | 28.05 | 20.86 | 99085974.50 | 56.70 | 02-OCT-21:10 | 28.05 | 20.86 |
November | 0.159086E+10 | 2914.28 | 04-NOV-18:02 | 25.43 | 17.21 | 95698145.04 | 56.70 | 10-NOV-22:40 | 18.53 | 15.73 |
December | 0.638781E+09 | 2822.51 | 28-DEC-16:02 | 23.63 | 15.15 | 98040903.14 | 56.69 | 28-DEC-23:40 | 16.80 | 13.63 |
Annual Sum or Average | 0.262281E+11 | 0.116383E+10 | ||||||||
Minimum of Months | 0.455843E+09 | 2822.51 | 23.13 | 14.50 | 88826848.85 | 56.69 | 16.80 | 13.63 | ||
Maximum of Months | 0.348703E+10 | 3060.74 | 40.98 | 27.21 | 99290202.01 | 56.70 | 38.13 | 27.21 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150483E+09 | 2820.14 | 08-JAN-16:01 | 21.92 | 14.14 | 97162500.16 | 62.52 | 13-JAN-22:40 | 17.53 | 13.62 |
February | 0.450490E+09 | 2966.61 | 21-FEB-16:02 | 25.98 | 15.67 | 91616382.68 | 71.27 | 22-FEB-22:19 | 19.47 | 14.23 |
March | 0.145911E+10 | 3023.96 | 22-MAR-15:01 | 26.48 | 16.54 | 0.103555E+09 | 75.96 | 13-MAR-21:00 | 26.48 | 16.54 |
April | 0.270223E+10 | 3058.06 | 30-APR-07:51 | 25.70 | 14.00 | 97200228.64 | 58.63 | 09-APR-21:10 | 25.70 | 14.00 |
May | 0.343573E+10 | 3070.20 | 01-MAY-18:02 | 40.17 | 22.26 | 99341980.60 | 56.70 | 31-MAY-00:49 | 33.40 | 21.46 |
June | 0.332457E+10 | 3069.08 | 05-JUN-18:02 | 40.98 | 23.28 | 96129481.49 | 56.70 | 08-JUN-02:39 | 32.63 | 23.68 |
July | 0.305645E+10 | 3076.06 | 04-JUL-18:02 | 40.17 | 24.19 | 99135667.75 | 56.70 | 04-JUL-00:20 | 40.17 | 24.19 |
August | 0.275916E+10 | 3000.21 | 15-AUG-18:02 | 32.63 | 27.21 | 99234343.61 | 56.70 | 07-AUG-22:19 | 32.63 | 27.21 |
September | 0.240031E+10 | 2963.03 | 29-SEP-18:02 | 30.22 | 22.95 | 96012551.44 | 56.70 | 07-SEP-21:10 | 30.22 | 22.95 |
October | 0.186992E+10 | 2994.19 | 08-OCT-21:51 | 22.50 | 18.53 | 0.102512E+09 | 76.34 | 11-OCT-21:10 | 22.40 | 20.30 |
November | 0.870032E+09 | 2989.90 | 05-NOV-15:01 | 28.82 | 17.45 | 99935924.38 | 73.03 | 09-NOV-22:19 | 19.57 | 16.52 |
December | 0.221201E+09 | 2807.28 | 02-DEC-16:01 | 22.50 | 13.59 | 97998073.01 | 64.78 | 28-DEC-22:30 | 17.65 | 13.86 |
Annual Sum or Average | 0.226997E+11 | 0.117983E+10 | ||||||||
Minimum of Months | 0.150483E+09 | 2807.28 | 21.92 | 13.59 | 91616382.68 | 56.70 | 17.53 | 13.62 | ||
Maximum of Months | 0.343573E+10 | 3076.06 | 40.98 | 27.21 | 0.103555E+09 | 76.34 | 40.17 | 27.21 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.310753E+09 | 426.64 | 08-JAN-14:20 | 22.50 | 13.35 | 0.00 | 0.00 | 01-JAN-00:10 | 22.50 | 13.35 |
February | 0.397760E+09 | 477.31 | 20-FEB-14:05 | 26.38 | 13.56 | 0.00 | 0.00 | 01-FEB-00:10 | 26.38 | 13.56 |
March | 0.606728E+09 | 499.06 | 13-MAR-13:40 | 32.23 | 18.89 | 0.00 | 0.00 | 01-MAR-00:10 | 32.23 | 18.89 |
April | 0.753076E+09 | 510.67 | 15-APR-14:00 | 40.20 | 20.61 | 0.00 | 0.00 | 01-APR-00:10 | 40.20 | 20.61 |
May | 0.823111E+09 | 507.26 | 04-MAY-17:13 | 41.63 | 22.16 | 0.00 | 0.00 | 01-MAY-00:10 | 41.63 | 22.16 |
June | 0.769342E+09 | 490.42 | 12-JUN-17:13 | 43.43 | 22.47 | 0.00 | 0.00 | 01-JUN-00:10 | 43.43 | 22.47 |
July | 0.763609E+09 | 461.69 | 04-JUL-20:10 | 39.85 | 24.37 | 0.00 | 0.00 | 01-JUL-00:10 | 39.85 | 24.37 |
August | 0.726256E+09 | 431.94 | 07-AUG-17:20 | 36.37 | 26.97 | 0.00 | 0.00 | 01-AUG-00:10 | 36.37 | 26.97 |
September | 0.715637E+09 | 536.57 | 26-SEP-13:40 | 35.43 | 22.96 | 0.00 | 0.00 | 01-SEP-00:10 | 35.43 | 22.96 |
October | 0.838943E+09 | 599.09 | 02-OCT-13:30 | 36.30 | 21.12 | 0.00 | 0.00 | 01-OCT-00:10 | 36.30 | 21.12 |
November | 0.699600E+09 | 578.07 | 04-NOV-13:30 | 30.20 | 17.21 | 0.00 | 0.00 | 01-NOV-00:10 | 30.20 | 17.21 |
December | 0.411399E+09 | 500.93 | 02-DEC-13:30 | 23.70 | 13.05 | 0.00 | 0.00 | 01-DEC-00:10 | 23.70 | 13.05 |
Annual Sum or Average | 0.781621E+10 | 0.00 | ||||||||
Minimum of Months | 0.310753E+09 | 426.64 | 22.50 | 13.05 | 0.00 | 0.00 | 22.50 | 13.05 | ||
Maximum of Months | 0.838943E+09 | 599.09 | 43.43 | 26.97 | 0.00 | 0.00 | 43.43 | 26.97 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248917E+09 | 1055.44 | 14-JAN-16:01 | 21.20 | 15.01 | 97359863.52 | 65.63 | 13-JAN-22:49 | 21.20 | 15.01 |
February | 0.346722E+09 | 1159.35 | 23-FEB-16:01 | 24.60 | 14.45 | 91213021.45 | 71.19 | 23-FEB-22:49 | 18.55 | 13.62 |
March | 0.650061E+09 | 1177.69 | 26-MAR-15:01 | 30.33 | 16.74 | 0.102575E+09 | 72.80 | 30-MAR-21:10 | 21.58 | 17.06 |
April | 0.956474E+09 | 1183.56 | 18-APR-15:02 | 37.58 | 23.23 | 96750878.78 | 56.70 | 18-APR-21:30 | 31.20 | 21.09 |
May | 0.120485E+10 | 1186.04 | 11-MAY-15:02 | 37.43 | 23.88 | 99172829.44 | 56.70 | 23-MAY-21:49 | 29.65 | 23.47 |
June | 0.119201E+10 | 1185.95 | 28-JUN-18:02 | 35.07 | 25.82 | 95986950.74 | 56.70 | 28-JUN-21:49 | 31.47 | 26.62 |
July | 0.119014E+10 | 1187.50 | 20-JUL-15:02 | 34.48 | 26.66 | 99042504.13 | 56.70 | 31-JUL-22:10 | 29.57 | 26.63 |
August | 0.110568E+10 | 1187.93 | 05-AUG-15:02 | 36.05 | 26.93 | 99116340.23 | 56.70 | 04-AUG-21:40 | 36.05 | 26.93 |
September | 0.954986E+09 | 1179.03 | 11-SEP-08:61 | 27.87 | 26.05 | 95831223.87 | 56.70 | 01-SEP-21:30 | 27.87 | 26.05 |
October | 0.765212E+09 | 1172.03 | 14-OCT-18:02 | 28.67 | 20.20 | 0.101627E+09 | 76.88 | 11-OCT-21:10 | 28.67 | 20.20 |
November | 0.460217E+09 | 1176.12 | 01-NOV-15:01 | 28.38 | 15.93 | 98872885.45 | 71.36 | 09-NOV-22:00 | 19.10 | 16.33 |
December | 0.287094E+09 | 1105.30 | 28-DEC-16:02 | 23.63 | 15.15 | 97948290.80 | 67.49 | 28-DEC-22:49 | 17.35 | 13.79 |
Annual Sum or Average | 0.936237E+10 | 0.117550E+10 | ||||||||
Minimum of Months | 0.248917E+09 | 1055.44 | 21.20 | 14.45 | 91213021.45 | 56.70 | 17.35 | 13.62 | ||
Maximum of Months | 0.120485E+10 | 1187.93 | 37.58 | 26.93 | 0.102575E+09 | 76.88 | 36.05 | 26.93 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.450158E+09 | 2605.51 | 12-JAN-16:01 | 23.13 | 14.50 | 97803717.69 | 56.69 | 25-JAN-22:19 | 16.70 | 13.27 |
February | 0.934733E+09 | 2704.50 | 24-FEB-16:01 | 26.18 | 17.45 | 89047592.68 | 56.69 | 24-FEB-22:10 | 19.35 | 16.58 |
March | 0.197278E+10 | 2709.69 | 22-MAR-15:01 | 26.48 | 16.54 | 99120826.09 | 56.70 | 29-MAR-21:19 | 26.20 | 18.28 |
April | 0.296628E+10 | 2726.38 | 27-APR-08:62 | 30.47 | 21.43 | 95963829.52 | 56.70 | 14-APR-22:30 | 30.47 | 21.43 |
May | 0.350892E+10 | 2785.48 | 04-MAY-18:02 | 40.25 | 22.32 | 99225158.37 | 56.70 | 02-MAY-00:00 | 40.25 | 22.32 |
June | 0.322783E+10 | 2762.44 | 12-JUN-18:02 | 42.22 | 22.60 | 96037185.86 | 56.70 | 08-JUN-03:39 | 42.22 | 22.60 |
July | 0.306456E+10 | 2749.01 | 07-JUL-15:02 | 40.35 | 24.63 | 99136093.62 | 56.70 | 04-JUL-00:49 | 40.35 | 24.63 |
August | 0.280189E+10 | 2732.95 | 22-AUG-15:02 | 29.43 | 26.68 | 99237924.15 | 56.70 | 04-AUG-21:40 | 29.43 | 26.68 |
September | 0.255396E+10 | 2734.19 | 17-SEP-08:62 | 28.18 | 25.20 | 95941960.55 | 56.70 | 29-SEP-21:10 | 27.58 | 23.06 |
October | 0.247877E+10 | 2736.09 | 04-OCT-08:61 | 27.45 | 21.90 | 99115654.59 | 56.70 | 05-OCT-21:10 | 27.28 | 19.87 |
November | 0.157847E+10 | 2641.82 | 15-NOV-16:02 | 26.08 | 17.94 | 95832082.71 | 56.69 | 07-NOV-22:49 | 26.08 | 17.94 |
December | 0.633443E+09 | 2602.79 | 03-DEC-16:01 | 21.53 | 14.07 | 98257650.96 | 56.69 | 27-DEC-22:19 | 14.07 | 12.80 |
Annual Sum or Average | 0.261718E+11 | 0.116472E+10 | ||||||||
Minimum of Months | 0.450158E+09 | 2602.79 | 21.53 | 14.07 | 89047592.68 | 56.69 | 14.07 | 12.80 | ||
Maximum of Months | 0.350892E+10 | 2785.48 | 42.22 | 26.68 | 99237924.15 | 56.70 | 42.22 | 26.68 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.168503E+09 | 2489.99 | 12-JAN-16:01 | 23.13 | 14.50 | 96818454.40 | 61.58 | 13-JAN-22:40 | 17.53 | 13.62 |
February | 0.485173E+09 | 2706.91 | 22-FEB-09:51 | 20.60 | 13.92 | 91654892.29 | 71.17 | 23-FEB-22:30 | 18.85 | 13.71 |
March | 0.145400E+10 | 2935.74 | 28-MAR-08:51 | 25.40 | 17.31 | 0.103817E+09 | 76.24 | 13-MAR-21:00 | 25.40 | 17.31 |
April | 0.269618E+10 | 3107.94 | 06-APR-08:51 | 25.60 | 16.75 | 97389997.99 | 57.90 | 09-APR-21:10 | 21.58 | 14.18 |
May | 0.345683E+10 | 2726.64 | 24-MAY-18:02 | 31.65 | 24.15 | 99288956.70 | 56.70 | 19-MAY-00:00 | 31.65 | 24.15 |
June | 0.323245E+10 | 2761.06 | 12-JUN-18:02 | 42.22 | 22.60 | 96079957.80 | 56.70 | 06-JUN-03:09 | 42.22 | 22.60 |
July | 0.306167E+10 | 2748.85 | 07-JUL-15:02 | 40.35 | 24.63 | 99136349.81 | 56.70 | 03-JUL-02:00 | 40.35 | 24.63 |
August | 0.275438E+10 | 2741.08 | 15-AUG-18:02 | 32.63 | 27.21 | 99237233.73 | 56.70 | 01-AUG-22:10 | 32.63 | 27.21 |
September | 0.237039E+10 | 2742.00 | 01-SEP-18:02 | 32.78 | 26.61 | 96021940.31 | 56.70 | 14-SEP-21:10 | 30.18 | 26.47 |
October | 0.186245E+10 | 2948.25 | 15-OCT-08:51 | 26.10 | 16.03 | 0.102676E+09 | 76.74 | 11-OCT-21:10 | 26.10 | 16.03 |
November | 0.841580E+09 | 2710.49 | 01-NOV-15:01 | 28.38 | 15.93 | 0.100039E+09 | 72.29 | 09-NOV-22:19 | 19.57 | 16.52 |
December | 0.238441E+09 | 2606.93 | 02-DEC-16:01 | 22.50 | 13.59 | 97814973.57 | 63.46 | 28-DEC-22:30 | 17.65 | 13.86 |
Annual Sum or Average | 0.226221E+11 | 0.117997E+10 | ||||||||
Minimum of Months | 0.168503E+09 | 2489.99 | 20.60 | 13.59 | 91654892.29 | 56.70 | 17.53 | 13.62 | ||
Maximum of Months | 0.345683E+10 | 3107.94 | 42.22 | 27.21 | 0.103817E+09 | 76.74 | 42.22 | 27.21 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.339415E+10 | 1606.80 | 14-JAN-11:33 | 19.60 | 14.39 | 0.125796E+10 | 790.27 | 13-JAN-23:10 | 19.60 | 14.39 |
February | 0.349607E+10 | 1876.03 | 23-FEB-11:33 | 24.77 | 14.09 | 0.121567E+10 | 859.97 | 23-FEB-22:49 | 18.55 | 13.62 |
March | 0.448199E+10 | 2162.29 | 12-MAR-10:33 | 27.43 | 17.74 | 0.147576E+10 | 924.70 | 13-MAR-22:10 | 21.72 | 17.00 |
April | 0.496529E+10 | 2724.70 | 28-APR-18:15 | 37.87 | 19.51 | 0.152883E+10 | 951.86 | 19-APR-21:19 | 37.87 | 19.51 |
May | 0.565185E+10 | 3134.92 | 05-MAY-18:17 | 40.70 | 19.92 | 0.161236E+10 | 951.85 | 01-MAY-00:20 | 40.70 | 19.92 |
June | 0.548135E+10 | 3222.54 | 12-JUN-18:13 | 41.93 | 22.55 | 0.155905E+10 | 951.84 | 03-JUN-01:19 | 41.93 | 22.55 |
July | 0.542322E+10 | 2956.50 | 07-JUL-18:15 | 37.90 | 25.47 | 0.160045E+10 | 951.84 | 05-JUL-23:19 | 37.90 | 25.47 |
August | 0.516187E+10 | 2690.41 | 09-AUG-18:05 | 33.95 | 27.13 | 0.159623E+10 | 951.84 | 05-AUG-01:19 | 33.95 | 27.13 |
September | 0.484687E+10 | 2422.87 | 26-SEP-18:10 | 32.77 | 22.38 | 0.151945E+10 | 951.84 | 23-SEP-01:19 | 32.77 | 22.38 |
October | 0.490587E+10 | 2320.18 | 01-OCT-10:33 | 31.23 | 19.64 | 0.155598E+10 | 951.84 | 02-OCT-23:19 | 24.13 | 19.90 |
November | 0.425411E+10 | 2050.44 | 11-NOV-11:33 | 26.80 | 17.21 | 0.141034E+10 | 903.73 | 01-NOV-21:49 | 26.80 | 17.21 |
December | 0.369023E+10 | 1782.08 | 03-DEC-11:33 | 22.07 | 14.16 | 0.131096E+10 | 833.82 | 01-DEC-22:40 | 22.07 | 14.16 |
Annual Sum or Average | 0.557529E+11 | 0.176430E+11 | ||||||||
Minimum of Months | 0.339415E+10 | 1606.80 | 19.60 | 14.09 | 0.121567E+10 | 790.27 | 18.55 | 13.62 | ||
Maximum of Months | 0.565185E+10 | 3222.54 | 41.93 | 27.13 | 0.161236E+10 | 951.86 | 41.93 | 27.13 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.395832E+09 | 3060.25 | 12-JAN-16:01 | 23.13 | 14.50 | 97261237.71 | 56.69 | 25-JAN-23:10 | 16.43 | 13.26 |
February | 0.833703E+09 | 3148.03 | 24-FEB-16:01 | 26.18 | 17.45 | 88685162.16 | 56.69 | 15-FEB-22:30 | 26.18 | 17.45 |
March | 0.194890E+10 | 3148.45 | 10-MAR-19:02 | 28.87 | 21.36 | 98914747.02 | 56.70 | 10-MAR-23:19 | 25.13 | 19.48 |
April | 0.308736E+10 | 3269.72 | 28-APR-18:02 | 38.13 | 19.51 | 95974858.30 | 56.70 | 19-APR-21:00 | 38.13 | 19.51 |
May | 0.371276E+10 | 3296.72 | 01-MAY-18:02 | 40.17 | 22.26 | 99329335.00 | 56.70 | 04-MAY-23:40 | 30.83 | 21.35 |
June | 0.356076E+10 | 3295.14 | 05-JUN-18:02 | 40.98 | 23.28 | 96120089.37 | 56.70 | 11-JUN-00:00 | 34.40 | 25.97 |
July | 0.322540E+10 | 3297.85 | 07-JUL-18:02 | 38.10 | 25.41 | 99136169.03 | 56.70 | 03-JUL-00:49 | 38.10 | 25.41 |
August | 0.292549E+10 | 3195.75 | 21-AUG-15:02 | 28.92 | 27.50 | 99231799.50 | 56.70 | 07-AUG-22:10 | 28.92 | 27.50 |
September | 0.265521E+10 | 3184.34 | 11-SEP-15:02 | 31.05 | 26.70 | 95923378.78 | 56.70 | 20-SEP-21:19 | 29.70 | 25.19 |
October | 0.246023E+10 | 3203.08 | 06-OCT-18:02 | 28.05 | 20.86 | 99020957.53 | 56.70 | 04-OCT-22:49 | 28.05 | 20.86 |
November | 0.147904E+10 | 3112.21 | 03-NOV-18:02 | 24.83 | 16.57 | 95576411.12 | 56.69 | 10-NOV-02:09 | 18.05 | 15.71 |
December | 0.528723E+09 | 3060.69 | 27-DEC-16:01 | 22.02 | 15.09 | 97802389.75 | 56.69 | 15-DEC-23:00 | 22.02 | 15.09 |
Annual Sum or Average | 0.268134E+11 | 0.116298E+10 | ||||||||
Minimum of Months | 0.395832E+09 | 3060.25 | 22.02 | 14.50 | 88685162.16 | 56.69 | 16.43 | 13.26 | ||
Maximum of Months | 0.371276E+10 | 3297.85 | 40.98 | 27.50 | 99329335.00 | 56.70 | 38.13 | 27.50 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108332E+09 | 3020.85 | 25-JAN-16:01 | 22.07 | 13.57 | 96763148.99 | 61.05 | 13-JAN-22:40 | 22.07 | 13.57 |
February | 0.388349E+09 | 3188.67 | 19-FEB-16:01 | 25.38 | 13.68 | 91385363.45 | 71.27 | 22-FEB-22:19 | 19.47 | 14.23 |
March | 0.147223E+10 | 3206.96 | 04-MAR-16:01 | 26.57 | 15.69 | 0.103215E+09 | 75.81 | 13-MAR-21:00 | 21.60 | 17.04 |
April | 0.283525E+10 | 3277.24 | 28-APR-18:02 | 38.13 | 19.51 | 97020542.64 | 57.98 | 09-APR-20:00 | 38.13 | 19.51 |
May | 0.366033E+10 | 3312.24 | 01-MAY-18:02 | 40.17 | 22.26 | 99371192.35 | 56.70 | 04-MAY-01:00 | 35.60 | 20.46 |
June | 0.356622E+10 | 3306.04 | 05-JUN-18:02 | 40.98 | 23.28 | 96157309.79 | 56.70 | 11-JUN-00:00 | 34.40 | 25.97 |
July | 0.322272E+10 | 3303.44 | 07-JUL-18:02 | 38.10 | 25.41 | 99136150.29 | 56.70 | 05-JUL-00:40 | 38.10 | 25.41 |
August | 0.287535E+10 | 3208.09 | 18-AUG-18:02 | 30.85 | 27.57 | 99230871.09 | 56.70 | 07-AUG-21:49 | 30.85 | 27.57 |
September | 0.246278E+10 | 3191.60 | 11-SEP-15:02 | 31.05 | 26.70 | 95988127.51 | 56.70 | 05-SEP-21:10 | 31.05 | 26.70 |
October | 0.187068E+10 | 3189.83 | 16-OCT-18:02 | 30.23 | 19.58 | 0.101969E+09 | 76.38 | 11-OCT-21:10 | 30.23 | 19.58 |
November | 0.761542E+09 | 3186.89 | 17-NOV-16:02 | 26.77 | 17.64 | 99243399.27 | 72.06 | 09-NOV-22:19 | 26.77 | 17.64 |
December | 0.150239E+09 | 3060.22 | 24-DEC-16:01 | 22.20 | 13.53 | 97506141.24 | 64.00 | 28-DEC-22:30 | 17.65 | 13.86 |
Annual Sum or Average | 0.233740E+11 | 0.117699E+10 | ||||||||
Minimum of Months | 0.108332E+09 | 3020.85 | 22.07 | 13.53 | 91385363.45 | 56.70 | 17.65 | 13.57 | ||
Maximum of Months | 0.366033E+10 | 3312.24 | 40.98 | 27.57 | 0.103215E+09 | 76.38 | 38.13 | 27.57 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.703907E+09 | 1618.49 | 14-JAN-16:01 | 21.20 | 15.01 | 98365660.72 | 56.69 | 25-JAN-22:19 | 16.70 | 13.27 |
February | 0.892985E+09 | 1638.98 | 25-FEB-16:01 | 21.12 | 17.96 | 89108899.51 | 56.69 | 15-FEB-22:40 | 21.12 | 17.96 |
March | 0.139620E+10 | 1739.42 | 29-MAR-15:02 | 33.07 | 18.99 | 99010061.05 | 56.70 | 28-MAR-21:19 | 33.07 | 18.99 |
April | 0.176717E+10 | 1752.23 | 01-APR-15:02 | 34.62 | 20.87 | 95927002.27 | 56.70 | 17-APR-21:40 | 29.40 | 20.35 |
May | 0.198302E+10 | 1736.10 | 07-MAY-15:02 | 42.38 | 21.50 | 99218232.43 | 56.70 | 11-MAY-21:40 | 30.60 | 23.12 |
June | 0.188703E+10 | 1743.20 | 11-JUN-15:02 | 43.23 | 23.42 | 96032305.96 | 56.70 | 19-JUN-21:30 | 32.65 | 23.90 |
July | 0.184846E+10 | 1725.75 | 08-JUL-08:62 | 33.90 | 28.37 | 99132976.60 | 56.70 | 20-JUL-21:40 | 30.97 | 26.17 |
August | 0.174562E+10 | 1719.98 | 10-AUG-15:02 | 26.35 | 25.52 | 99233904.69 | 56.70 | 03-AUG-21:40 | 26.35 | 25.52 |
September | 0.167815E+10 | 1771.12 | 20-SEP-15:02 | 33.48 | 24.59 | 95941755.23 | 56.70 | 26-SEP-21:00 | 26.70 | 22.62 |
October | 0.184290E+10 | 1749.23 | 28-OCT-15:01 | 29.18 | 18.46 | 99118219.93 | 56.70 | 05-OCT-21:49 | 29.18 | 18.46 |
November | 0.146974E+10 | 1763.76 | 09-NOV-16:01 | 28.22 | 17.54 | 95829792.89 | 56.69 | 01-NOV-23:00 | 28.22 | 17.54 |
December | 0.881581E+09 | 1618.87 | 26-DEC-16:01 | 21.58 | 14.41 | 98660436.48 | 56.69 | 01-DEC-22:30 | 21.58 | 14.41 |
Annual Sum or Average | 0.180968E+11 | 0.116558E+10 | ||||||||
Minimum of Months | 0.703907E+09 | 1618.49 | 21.12 | 14.41 | 89108899.51 | 56.69 | 16.70 | 13.27 | ||
Maximum of Months | 0.198302E+10 | 1771.12 | 43.23 | 28.37 | 99233904.69 | 56.70 | 33.07 | 26.17 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.339834E+11 | 18717.36 | 13-JAN-22:55 | 17.50 | 13.55 | 0.188647E+11 | 11347.96 | 25-JAN-23:10 | 16.43 | 13.26 |
February | 0.329615E+11 | 20183.57 | 22-FEB-22:10 | 19.68 | 14.28 | 0.172284E+11 | 11348.65 | 27-FEB-23:10 | 15.28 | 12.98 |
March | 0.408120E+11 | 22368.68 | 29-MAR-21:10 | 26.40 | 18.36 | 0.193128E+11 | 11348.96 | 15-MAR-22:10 | 26.40 | 18.36 |
April | 0.441541E+11 | 24347.51 | 27-APR-21:10 | 34.92 | 17.25 | 0.187002E+11 | 11350.34 | 27-APR-22:00 | 32.90 | 17.34 |
May | 0.486199E+11 | 24898.50 | 05-MAY-21:10 | 36.73 | 18.90 | 0.193456E+11 | 11358.57 | 04-MAY-22:00 | 36.73 | 18.90 |
June | 0.475205E+11 | 25277.13 | 12-JUN-21:10 | 36.95 | 22.55 | 0.187567E+11 | 11352.20 | 16-JUN-22:00 | 33.30 | 25.85 |
July | 0.479954E+11 | 24910.21 | 03-JUL-21:10 | 35.32 | 27.33 | 0.193034E+11 | 11352.87 | 06-JUL-22:30 | 34.05 | 25.47 |
August | 0.469456E+11 | 24205.19 | 07-AUG-21:10 | 33.28 | 27.30 | 0.193831E+11 | 11354.19 | 08-AUG-22:30 | 32.20 | 26.94 |
September | 0.436390E+11 | 23464.98 | 01-SEP-21:10 | 30.68 | 26.00 | 0.186891E+11 | 11347.71 | 04-SEP-23:19 | 26.83 | 25.26 |
October | 0.424971E+11 | 22497.25 | 04-OCT-21:10 | 24.95 | 18.88 | 0.192711E+11 | 11348.96 | 24-OCT-22:10 | 21.02 | 16.79 |
November | 0.368754E+11 | 20398.66 | 08-NOV-22:53 | 19.60 | 17.40 | 0.185271E+11 | 11348.81 | 08-NOV-23:10 | 19.53 | 17.36 |
December | 0.346113E+11 | 18963.62 | 28-DEC-22:54 | 17.20 | 13.76 | 0.189273E+11 | 11348.36 | 28-DEC-23:10 | 17.10 | 13.73 |
Annual Sum or Average | 0.500615E+12 | 0.226309E+12 | ||||||||
Minimum of Months | 0.329615E+11 | 18717.36 | 17.20 | 13.55 | 0.172284E+11 | 11347.71 | 15.28 | 12.98 | ||
Maximum of Months | 0.486199E+11 | 25277.13 | 36.95 | 27.33 | 0.193831E+11 | 11358.57 | 36.73 | 26.94 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.375355E+11 | 20561.82 | 13-JAN-22:55 | 17.50 | 13.55 | 0.190547E+11 | 11347.99 | 25-JAN-23:10 | 16.43 | 13.26 |
February | 0.361354E+11 | 21782.46 | 22-FEB-22:10 | 19.68 | 14.28 | 0.173410E+11 | 11348.66 | 27-FEB-23:10 | 15.28 | 12.98 |
March | 0.440329E+11 | 23658.36 | 29-MAR-21:10 | 26.40 | 18.36 | 0.193586E+11 | 11348.96 | 15-MAR-22:10 | 26.40 | 18.36 |
April | 0.469188E+11 | 25543.45 | 27-APR-21:10 | 34.92 | 17.25 | 0.187109E+11 | 11357.30 | 28-APR-21:30 | 33.05 | 19.24 |
May | 0.513798E+11 | 26081.86 | 05-MAY-21:10 | 36.73 | 18.90 | 0.193489E+11 | 11356.47 | 02-MAY-21:30 | 36.73 | 18.90 |
June | 0.501989E+11 | 26465.46 | 12-JUN-21:10 | 36.95 | 22.55 | 0.187590E+11 | 11352.27 | 28-JUN-21:30 | 31.80 | 26.58 |
July | 0.507507E+11 | 26089.05 | 03-JUL-21:10 | 35.32 | 27.33 | 0.193076E+11 | 11353.55 | 31-JUL-21:30 | 29.65 | 26.81 |
August | 0.497240E+11 | 25382.42 | 07-AUG-21:10 | 33.28 | 27.30 | 0.193887E+11 | 11355.79 | 07-AUG-22:30 | 32.35 | 27.42 |
September | 0.463984E+11 | 24647.92 | 01-SEP-21:10 | 30.68 | 26.00 | 0.187027E+11 | 11347.71 | 04-SEP-23:19 | 26.83 | 25.26 |
October | 0.454174E+11 | 23710.52 | 04-OCT-21:10 | 24.95 | 18.88 | 0.192945E+11 | 11348.97 | 24-OCT-22:10 | 21.02 | 16.79 |
November | 0.400128E+11 | 21825.85 | 08-NOV-22:53 | 19.60 | 17.40 | 0.186050E+11 | 11348.81 | 08-NOV-23:10 | 19.53 | 17.36 |
December | 0.381236E+11 | 20746.34 | 28-DEC-22:10 | 17.95 | 13.92 | 0.191019E+11 | 11348.38 | 28-DEC-23:10 | 17.10 | 13.73 |
Annual Sum or Average | 0.536628E+12 | 0.226974E+12 | ||||||||
Minimum of Months | 0.361354E+11 | 20561.82 | 17.50 | 13.55 | 0.173410E+11 | 11347.71 | 15.28 | 12.98 | ||
Maximum of Months | 0.513798E+11 | 26465.46 | 36.95 | 27.33 | 0.193887E+11 | 11357.30 | 36.73 | 27.42 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.493383E+11 | 26257.10 | 26-JAN-11:45 | 21.12 | 13.59 | 0.188085E+11 | 11319.63 | 07-JAN-18:19 | 21.12 | 13.59 |
February | 0.462349E+11 | 27484.90 | 20-FEB-11:45 | 24.15 | 13.15 | 0.170017E+11 | 11319.61 | 04-FEB-18:19 | 24.15 | 13.15 |
March | 0.540149E+11 | 29147.93 | 12-MAR-10:45 | 27.82 | 17.88 | 0.188494E+11 | 11319.66 | 11-MAR-18:19 | 27.82 | 17.88 |
April | 0.553049E+11 | 30522.29 | 16-APR-10:33 | 36.27 | 21.85 | 0.182533E+11 | 11319.68 | 01-APR-17:19 | 36.27 | 21.85 |
May | 0.587062E+11 | 30684.37 | 04-MAY-10:40 | 40.13 | 22.05 | 0.188687E+11 | 11319.67 | 13-MAY-17:19 | 33.17 | 22.98 |
June | 0.566372E+11 | 30585.39 | 11-JUN-10:37 | 38.13 | 25.22 | 0.182627E+11 | 11319.70 | 03-JUN-17:19 | 38.13 | 25.22 |
July | 0.576179E+11 | 30312.19 | 04-JUL-10:33 | 36.00 | 24.99 | 0.188649E+11 | 11319.67 | 29-JUL-17:19 | 33.57 | 26.66 |
August | 0.569903E+11 | 29519.46 | 06-AUG-10:50 | 33.30 | 25.72 | 0.188708E+11 | 11319.67 | 05-AUG-17:19 | 33.30 | 25.72 |
September | 0.543662E+11 | 29394.80 | 24-SEP-10:50 | 32.35 | 25.28 | 0.182535E+11 | 11319.68 | 16-SEP-17:19 | 32.35 | 25.28 |
October | 0.552138E+11 | 29562.68 | 01-OCT-10:33 | 31.23 | 19.64 | 0.188512E+11 | 11319.66 | 21-OCT-17:19 | 28.63 | 18.05 |
November | 0.508507E+11 | 28017.92 | 04-NOV-10:45 | 26.42 | 16.67 | 0.182223E+11 | 11319.67 | 04-NOV-17:19 | 27.33 | 17.60 |
December | 0.498525E+11 | 26866.49 | 03-DEC-11:50 | 22.38 | 14.19 | 0.188120E+11 | 11319.86 | 23-DEC-18:19 | 15.23 | 10.67 |
Annual Sum or Average | 0.645128E+12 | 0.221919E+12 | ||||||||
Minimum of Months | 0.462349E+11 | 26257.10 | 21.12 | 13.15 | 0.170017E+11 | 11319.61 | 15.23 | 10.67 | ||
Maximum of Months | 0.587062E+11 | 30684.37 | 40.13 | 25.72 | 0.188708E+11 | 11319.86 | 38.13 | 26.66 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.676980E+10 | 3816.78 | 26-JAN-11:33 | 20.83 | 13.52 | 0.129353E+10 | 807.29 | 13-JAN-22:40 | 20.83 | 13.52 |
February | 0.774703E+10 | 4546.42 | 23-FEB-11:33 | 24.77 | 14.09 | 0.123209E+10 | 886.19 | 22-FEB-22:40 | 24.77 | 14.09 |
March | 0.105395E+11 | 5803.62 | 13-MAR-15:03 | 32.83 | 18.67 | 0.152098E+10 | 989.39 | 29-MAR-21:40 | 25.80 | 18.13 |
April | 0.125450E+11 | 7919.40 | 29-APR-13:30 | 37.40 | 19.73 | 0.160397E+10 | 1007.42 | 19-APR-21:19 | 37.40 | 19.73 |
May | 0.148320E+11 | 9099.33 | 04-MAY-15:04 | 42.23 | 22.18 | 0.170143E+10 | 1007.40 | 01-MAY-21:30 | 42.23 | 22.18 |
June | 0.146028E+11 | 9314.64 | 08-JUN-15:25 | 44.55 | 22.34 | 0.164918E+10 | 1007.40 | 12-JUN-21:19 | 36.80 | 22.54 |
July | 0.140116E+11 | 8272.14 | 07-JUL-15:25 | 40.25 | 24.66 | 0.169646E+10 | 1007.39 | 06-JUL-21:19 | 40.25 | 24.66 |
August | 0.131241E+11 | 7471.50 | 08-AUG-15:03 | 36.88 | 26.52 | 0.169277E+10 | 1007.39 | 07-AUG-21:30 | 36.88 | 26.52 |
September | 0.119911E+11 | 7000.60 | 26-SEP-15:03 | 36.05 | 22.65 | 0.159876E+10 | 1007.39 | 25-SEP-21:19 | 36.05 | 22.65 |
October | 0.116317E+11 | 6980.88 | 02-OCT-14:10 | 36.40 | 21.05 | 0.159668E+10 | 1007.37 | 03-OCT-21:40 | 27.67 | 22.55 |
November | 0.951129E+10 | 4943.66 | 09-NOV-11:33 | 27.93 | 18.32 | 0.139976E+10 | 913.44 | 09-NOV-22:40 | 19.33 | 16.42 |
December | 0.761254E+10 | 4136.26 | 03-DEC-11:33 | 22.07 | 14.16 | 0.130903E+10 | 824.88 | 28-DEC-22:40 | 17.50 | 13.83 |
Annual Sum or Average | 0.134919E+12 | 0.182946E+11 | ||||||||
Minimum of Months | 0.676980E+10 | 3816.78 | 20.83 | 13.52 | 0.123209E+10 | 807.29 | 17.50 | 13.52 | ||
Maximum of Months | 0.148320E+11 | 9314.64 | 44.55 | 26.52 | 0.170143E+10 | 1007.42 | 42.23 | 26.52 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 51177373.55 | 1416.22 | 02-JAN-09:02 | 8.57 |
February | 10268087.23 | 794.26 | 14-FEB-19:04 | 20.98 |
March | 1449019.75 | 1028.32 | 14-MAR-08:04 | 21.43 |
April | 635890.65 | 1156.11 | 10-APR-08:04 | 21.57 |
May | 160384.05 | 314.78 | 24-MAY-08:05 | 25.67 |
June | 251913.09 | 372.04 | 18-JUN-08:05 | 26.23 |
July | 322212.76 | 417.70 | 28-JUL-08:04 | 27.58 |
August | 455332.27 | 487.39 | 23-AUG-08:04 | 27.25 |
September | 1114866.43 | 1066.16 | 07-SEP-08:04 | 24.37 |
October | 1237638.73 | 1063.87 | 24-OCT-08:04 | 21.12 |
November | 1827733.41 | 723.97 | 06-NOV-09:05 | 19.93 |
December | 18560198.33 | 1040.68 | 29-DEC-16:04 | 18.80 |
Annual Sum or Average | 87460650.26 | |||
Minimum of Months | 160384.05 | 314.78 | 8.57 | |
Maximum of Months | 51177373.55 | 1416.22 | 27.58 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133428E+09 | 1444.63 | 03-JAN-09:02 | 8.92 |
February | 19196938.86 | 888.87 | 02-FEB-09:02 | 10.37 |
March | 1122400.67 | 902.19 | 26-MAR-08:53 | 23.00 |
April | 307389.45 | 714.67 | 23-APR-08:44 | 25.78 |
May | 119733.97 | 310.49 | 24-MAY-08:05 | 25.67 |
June | 250793.17 | 495.34 | 18-JUN-06:55 | 24.80 |
July | 315403.71 | 444.73 | 28-JUL-08:04 | 27.58 |
August | 514154.83 | 528.91 | 23-AUG-08:04 | 27.25 |
September | 1338035.74 | 1069.48 | 07-SEP-08:04 | 24.37 |
October | 749294.74 | 741.46 | 15-OCT-08:54 | 26.10 |
November | 2275599.69 | 816.08 | 12-NOV-09:54 | 22.40 |
December | 53687820.95 | 1408.72 | 21-DEC-09:02 | 7.18 |
Annual Sum or Average | 0.213306E+09 | |||
Minimum of Months | 119733.97 | 310.49 | 7.18 | |
Maximum of Months | 0.133428E+09 | 1444.63 | 27.58 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1786165.23 | 443.56 | 28-JAN-16:04 | 18.07 |
February | 737930.88 | 388.28 | 02-FEB-16:04 | 22.17 |
March | 516795.40 | 316.12 | 25-MAR-15:06 | 25.75 |
April | 169921.84 | 124.95 | 12-APR-08:35 | 25.20 |
May | 78985.66 | 101.53 | 29-MAY-08:07 | 32.12 |
June | 73798.95 | 86.58 | 27-JUN-18:07 | 30.40 |
July | 86582.99 | 79.01 | 18-JUL-15:07 | 26.38 |
August | 82980.32 | 74.37 | 23-AUG-18:07 | 28.33 |
September | 235821.49 | 144.91 | 09-SEP-15:07 | 26.67 |
October | 408019.01 | 247.58 | 28-OCT-08:55 | 21.80 |
November | 682188.06 | 342.08 | 11-NOV-16:06 | 27.37 |
December | 891104.02 | 418.66 | 30-DEC-16:04 | 14.92 |
Annual Sum or Average | 5750293.85 | |||
Minimum of Months | 73798.95 | 74.37 | 14.92 | |
Maximum of Months | 1786165.23 | 443.56 | 32.12 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55410451.18 | 966.84 | 27-JAN-16:04 | 16.42 |
February | 9051631.05 | 654.17 | 03-FEB-19:05 | 17.42 |
March | 408686.29 | 649.53 | 22-MAR-08:05 | 19.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 29022.47 | 290.22 | 26-JUL-08:05 | 26.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 162304.34 | 453.23 | 07-SEP-08:04 | 24.37 |
October | 88227.15 | 561.13 | 12-OCT-08:05 | 22.63 |
November | 225279.75 | 335.22 | 02-NOV-08:05 | 18.43 |
December | 20182399.86 | 1032.52 | 29-DEC-16:04 | 18.80 |
Annual Sum or Average | 85558002.09 | |||
Minimum of Months | 0.00 | 0.00 | 16.42 | |
Maximum of Months | 55410451.18 | 1032.52 | 30.53 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130600E+09 | 1180.50 | 02-JAN-09:02 | 8.57 |
February | 19571113.60 | 822.77 | 12-FEB-16:04 | 20.43 |
March | 594582.35 | 534.83 | 03-MAR-22:55 | 18.10 |
April | 2069.45 | 27.59 | 09-APR-21:55 | 21.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 19977.23 | 199.08 | 18-JUN-06:55 | 24.80 |
July | 30162.30 | 301.62 | 26-JUL-08:05 | 26.73 |
August | 877.13 | 8.77 | 20-AUG-08:05 | 27.07 |
September | 183805.15 | 503.19 | 07-SEP-08:04 | 24.37 |
October | 212231.90 | 370.56 | 24-OCT-21:55 | 21.10 |
November | 1882203.76 | 824.23 | 28-NOV-16:05 | 22.55 |
December | 58995293.27 | 941.01 | 25-DEC-16:04 | 21.52 |
Annual Sum or Average | 0.212093E+09 | |||
Minimum of Months | 0.00 | 0.00 | 8.57 | |
Maximum of Months | 0.130600E+09 | 1180.50 | 30.53 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174995E+09 | 1771.07 | 02-JAN-09:02 | 8.57 |
February | 43327939.72 | 1144.37 | 10-FEB-09:02 | 13.18 |
March | 1872187.92 | 943.12 | 30-MAR-08:04 | 22.75 |
April | 967378.07 | 926.28 | 05-APR-08:04 | 22.92 |
May | 160933.65 | 455.40 | 13-MAY-08:05 | 24.87 |
June | 257612.74 | 568.69 | 25-JUN-08:04 | 27.88 |
July | 417383.48 | 830.77 | 28-JUL-08:04 | 27.58 |
August | 703603.06 | 866.87 | 23-AUG-08:04 | 27.25 |
September | 1303700.25 | 949.83 | 07-SEP-08:04 | 24.37 |
October | 1500201.98 | 883.90 | 16-OCT-08:04 | 24.53 |
November | 2690033.84 | 1001.02 | 28-NOV-19:04 | 19.52 |
December | 88670239.13 | 1611.72 | 21-DEC-09:02 | 7.18 |
Annual Sum or Average | 0.316866E+09 | |||
Minimum of Months | 160933.65 | 455.40 | 7.18 | |
Maximum of Months | 0.174995E+09 | 1771.07 | 27.88 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.323955E+09 | 1804.06 | 03-JAN-09:02 | 8.92 |
February | 70441393.35 | 1742.58 | 03-FEB-09:02 | 11.77 |
March | 1832118.45 | 963.82 | 27-MAR-08:53 | 22.90 |
April | 503763.88 | 788.98 | 02-APR-06:44 | 24.75 |
May | 109904.49 | 381.09 | 24-MAY-08:05 | 25.67 |
June | 247184.69 | 588.46 | 25-JUN-08:04 | 27.88 |
July | 401358.43 | 827.70 | 28-JUL-08:04 | 27.58 |
August | 715162.60 | 874.14 | 16-AUG-08:04 | 24.65 |
September | 1564558.84 | 943.65 | 07-SEP-08:04 | 24.37 |
October | 1166598.60 | 789.56 | 04-OCT-08:04 | 27.45 |
November | 6794676.81 | 825.68 | 01-NOV-08:53 | 21.10 |
December | 0.205155E+09 | 1764.29 | 21-DEC-09:02 | 7.18 |
Annual Sum or Average | 0.612887E+09 | |||
Minimum of Months | 109904.49 | 381.09 | 7.18 | |
Maximum of Months | 0.323955E+09 | 1804.06 | 27.88 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5834094.31 | 365.33 | 04-JAN-09:04 | 9.05 |
February | 3588003.22 | 405.44 | 12-FEB-19:05 | 17.02 |
March | 304185.16 | 258.36 | 18-MAR-08:05 | 18.55 |
April | 321615.93 | 385.86 | 03-APR-08:04 | 25.37 |
May | 164679.77 | 399.77 | 15-MAY-08:05 | 25.57 |
June | 204901.93 | 377.34 | 28-JUN-08:05 | 29.02 |
July | 200594.94 | 387.99 | 26-JUL-08:05 | 26.73 |
August | 199920.85 | 395.39 | 17-AUG-08:05 | 28.55 |
September | 176315.25 | 356.35 | 19-SEP-08:05 | 25.35 |
October | 144362.52 | 353.05 | 05-OCT-08:04 | 25.27 |
November | 199519.40 | 291.12 | 30-NOV-09:05 | 16.07 |
December | 2096914.17 | 487.48 | 29-DEC-16:04 | 18.80 |
Annual Sum or Average | 13435107.44 | |||
Minimum of Months | 144362.52 | 258.36 | 9.05 | |
Maximum of Months | 5834094.31 | 487.48 | 29.02 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.962539E+10 | 9271.23 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.869085E+10 | 9271.23 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.965507E+10 | 9271.23 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.929905E+10 | 9271.23 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.964208E+10 | 9271.23 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.934170E+10 | 9271.23 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.959943E+10 | 9271.23 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.965878E+10 | 9271.23 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.930276E+10 | 9271.23 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.962169E+10 | 9271.23 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.933428E+10 | 9271.23 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.959943E+10 | 9271.23 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.113371E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.869085E+10 | 9271.23 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.965878E+10 | 9271.23 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.531884E+09 | 512.31 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.480243E+09 | 512.31 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.533523E+09 | 512.31 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.513850E+09 | 512.31 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.532806E+09 | 512.31 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.516207E+09 | 512.31 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.530449E+09 | 512.31 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.533728E+09 | 512.31 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.514055E+09 | 512.31 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.531679E+09 | 512.31 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.515797E+09 | 512.31 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.530449E+09 | 512.31 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.626467E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.480243E+09 | 512.31 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.533728E+09 | 512.31 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.615923E+09 | 593.26 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.556123E+09 | 593.26 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.617822E+09 | 593.26 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.595041E+09 | 593.26 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.616991E+09 | 593.26 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.597770E+09 | 593.26 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.614262E+09 | 593.26 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.618059E+09 | 593.26 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.595278E+09 | 593.26 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.615686E+09 | 593.26 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.597295E+09 | 593.26 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.614262E+09 | 593.26 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.725451E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.556123E+09 | 593.26 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.618059E+09 | 593.26 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.158446E+09 | 152.61 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.143062E+09 | 152.61 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.158934E+09 | 152.61 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.153074E+09 | 152.61 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.158720E+09 | 152.61 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.153776E+09 | 152.61 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.158018E+09 | 152.61 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.158995E+09 | 152.61 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.153135E+09 | 152.61 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.158385E+09 | 152.61 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.153654E+09 | 152.61 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.158018E+09 | 152.61 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.186622E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.143062E+09 | 152.61 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.158995E+09 | 152.61 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.415991E+09 | 400.68 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.375602E+09 | 400.68 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.417273E+09 | 400.68 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.401887E+09 | 400.68 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.416712E+09 | 400.68 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.403730E+09 | 400.68 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.414869E+09 | 400.68 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.417433E+09 | 400.68 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.402047E+09 | 400.68 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.415830E+09 | 400.68 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.403409E+09 | 400.68 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.414869E+09 | 400.68 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.489965E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.375602E+09 | 400.68 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.417433E+09 | 400.68 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.120348E+10 | 1573.46 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.106385E+10 | 1573.46 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.112283E+10 | 1573.46 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.103316E+10 | 1573.46 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.103741E+10 | 1573.46 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.998684E+09 | 1573.46 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.105146E+10 | 1573.46 | 03-JUL-19:19 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.109695E+10 | 1573.46 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.109218E+10 | 1573.46 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.117689E+10 | 1573.46 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.114568E+10 | 1573.46 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.119827E+10 | 1573.46 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.132208E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.998684E+09 | 1573.46 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.120348E+10 | 1573.46 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105437E+11 | 10645.38 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.949817E+10 | 10645.38 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.104922E+11 | 10645.38 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.100558E+11 | 10645.38 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.103979E+11 | 10645.38 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.100746E+11 | 10645.38 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.103828E+11 | 10645.38 | 03-JUL-19:19 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.104866E+11 | 10645.38 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.101320E+11 | 10645.38 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.105154E+11 | 10645.38 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.101996E+11 | 10645.38 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.105084E+11 | 10645.38 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.123287E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.949817E+10 | 10645.38 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.105437E+11 | 10645.38 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82476868.03 | 74.62 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 74484663.28 | 74.62 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 81821381.83 | 74.62 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 79911301.67 | 74.62 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 82149124.93 | 74.62 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 79277307.08 | 74.62 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 82793865.32 | 74.62 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 81821381.83 | 74.62 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 79932793.28 | 74.62 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 82466122.22 | 74.62 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 79594304.38 | 74.62 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 82804611.13 | 74.62 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.969534E+09 | 0.300992E+10 | ||||
Minimum of Months | 74484663.28 | 74.62 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 82804611.13 | 74.62 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82499421.18 | 74.64 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 74505030.97 | 74.64 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 81843755.73 | 74.64 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 79933153.27 | 74.64 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 82171588.45 | 74.64 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 79298985.31 | 74.64 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 82816505.16 | 74.64 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 81843755.73 | 74.64 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 79954650.76 | 74.64 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 82488672.43 | 74.64 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 79616069.29 | 74.64 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 82827253.90 | 74.64 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.969799E+09 | 0.301074E+10 | ||||
Minimum of Months | 74505030.97 | 74.64 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 82827253.90 | 74.64 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.120431E+10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.108739E+10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.120803E+10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.116348E+10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.120640E+10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.116882E+10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.120107E+10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.120849E+10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.116395E+10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.120385E+10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.116789E+10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.120107E+10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.141847E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.108739E+10 | 1160.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120849E+10 | 1160.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82499421.18 | 74.64 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 74505030.97 | 74.64 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 81843755.73 | 74.64 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 79933153.27 | 74.64 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 82171588.45 | 74.64 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 79298985.31 | 74.64 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 82816505.16 | 74.64 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 81843755.73 | 74.64 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 79954650.76 | 74.64 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 82488672.43 | 74.64 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 79616069.29 | 74.64 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 82827253.90 | 74.64 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.969799E+09 | 0.301074E+10 | ||||
Minimum of Months | 74505030.97 | 74.64 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 82827253.90 | 74.64 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.253960E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.225652E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.243781E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.228574E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.232409E+10 | 2763.12 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.224840E+10 | 2763.12 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.233897E+10 | 2763.12 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.239918E+10 | 2763.12 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.235405E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.248783E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.243342E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.253194E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.286375E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.224840E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.253960E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.253960E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.225652E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.243781E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.228574E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.232409E+10 | 2763.12 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.224840E+10 | 2763.12 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.233897E+10 | 2763.12 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.239918E+10 | 2763.12 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.235405E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.248783E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.243342E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.253194E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.286375E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.224840E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.253960E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113250E+10 | 1090.83 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.102255E+10 | 1090.83 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.113599E+10 | 1090.83 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.109410E+10 | 1090.83 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.113446E+10 | 1090.83 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.109912E+10 | 1090.83 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.112945E+10 | 1090.83 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.113643E+10 | 1090.83 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.109454E+10 | 1090.83 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.113207E+10 | 1090.83 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.109825E+10 | 1090.83 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.112945E+10 | 1090.83 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.133389E+11 | 0.424019E+12 | ||||
Minimum of Months | 0.102255E+10 | 1090.83 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.113643E+10 | 1090.83 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.127458E+10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.115083E+10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.127851E+10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.123137E+10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.127679E+10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.123701E+10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.127114E+10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.127900E+10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.123186E+10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.127409E+10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.123603E+10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.127114E+10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.150123E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.115083E+10 | 1227.68 | 0.00 | 0.00 | |
Maximum of Months | 0.127900E+10 | 1227.68 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.962539E+10 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.869085E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.965507E+10 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.929905E+10 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.964208E+10 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.934170E+10 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.959943E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.965878E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.930276E+10 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.962169E+10 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.933428E+10 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.959943E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.113371E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.869085E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.965878E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.531884E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67349985.89 |
February | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 819715.16 | 38780560.43 |
March | 0.199990E+10 | 0.533523E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10681736.66 | 15967662.94 |
April | 0.192973E+10 | 0.513850E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40433737.73 | 1234295.53 |
May | 0.199475E+10 | 0.532806E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66462771.09 | 618.95 |
June | 0.193394E+10 | 0.516207E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68842275.25 | 0.00 |
July | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57629272.65 | 0.00 |
August | 0.199896E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46576437.65 | 2293.49 |
September | 0.192879E+10 | 0.514055E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37522373.00 | 1774.95 |
October | 0.199148E+10 | 0.531679E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19705472.41 | 8105896.05 |
November | 0.192552E+10 | 0.515797E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5117172.55 | 30803582.90 |
December | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30627.91 | 60055729.54 |
Annual Sum or Average | 0.234744E+11 | 0.626467E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353822E+09 | 0.222302E+09 |
Minimum of Months | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.199990E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68842275.25 | 67349985.89 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.615923E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13337.86 | 28645918.95 |
February | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 596780.00 | 17324881.82 |
March | 0.231589E+10 | 0.617822E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4609573.25 | 8055635.56 |
April | 0.223463E+10 | 0.595041E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15615775.38 | 886548.82 |
May | 0.230993E+10 | 0.616991E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25638978.31 | 20740.42 |
June | 0.223950E+10 | 0.597770E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26445144.55 | 4115.23 |
July | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22103840.14 | 3358.59 |
August | 0.231480E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17688321.84 | 2692.80 |
September | 0.223354E+10 | 0.595278E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13824381.28 | 7311.11 |
October | 0.230614E+10 | 0.615686E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7935971.59 | 4242882.72 |
November | 0.222975E+10 | 0.597295E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2495437.85 | 13906526.62 |
December | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 99174.66 | 25929112.18 |
Annual Sum or Average | 0.271834E+11 | 0.725451E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137067E+09 | 99029724.83 |
Minimum of Months | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13337.86 | 2692.80 |
Maximum of Months | 0.231589E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26445144.55 | 28645918.95 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 154352.68 | 60326351.44 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2243423.05 | 35820590.41 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12484123.61 | 15918969.78 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38050619.69 | 1627513.31 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60417408.65 | 28916.80 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62287948.84 | 6500.63 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51772870.46 | 4616.92 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41304050.94 | 6381.96 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32850455.15 | 12698.34 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19673288.74 | 8719690.56 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7226769.06 | 28824820.29 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 564353.33 | 54520439.01 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329030E+09 | 0.205817E+09 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 154352.68 | 4616.92 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62287948.84 | 60326351.44 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.158446E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85877.20 | 34270553.34 |
February | 0.339028E+09 | 0.143062E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1287814.24 | 20204012.99 |
March | 0.376747E+09 | 0.158934E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7312590.59 | 8801273.95 |
April | 0.363528E+09 | 0.153074E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22237369.76 | 857332.92 |
May | 0.375778E+09 | 0.158720E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34935737.94 | 14072.30 |
June | 0.364321E+09 | 0.153776E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36002540.66 | 2527.27 |
July | 0.374985E+09 | 0.158018E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29951640.95 | 2207.58 |
August | 0.376571E+09 | 0.158995E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23939083.40 | 3610.12 |
September | 0.363352E+09 | 0.153135E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19225387.30 | 5195.66 |
October | 0.375161E+09 | 0.158385E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11527126.37 | 4711830.25 |
November | 0.362735E+09 | 0.153654E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4180290.17 | 16147279.86 |
December | 0.374985E+09 | 0.158018E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 319044.55 | 30896354.82 |
Annual Sum or Average | 0.442217E+10 | 0.186622E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191005E+09 | 0.115916E+09 |
Minimum of Months | 0.339028E+09 | 0.143062E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85877.20 | 2207.58 |
Maximum of Months | 0.376747E+09 | 0.158995E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36002540.66 | 34270553.34 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.415991E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 32302.74 | 95933561.38 |
February | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 2080736.77 | 56268714.19 |
March | 0.155131E+10 | 0.417273E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 16058180.87 | 23413040.93 |
April | 0.149688E+10 | 0.401887E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 55668197.33 | 1999756.22 |
May | 0.154732E+10 | 0.416712E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 89600262.54 | 6297.01 |
June | 0.150015E+10 | 0.403730E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 92046723.40 | 27.74 |
July | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 77955833.57 | 0.00 |
August | 0.155059E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 63712007.92 | 0.00 |
September | 0.149615E+10 | 0.402047E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 50607039.05 | 10264.24 |
October | 0.154478E+10 | 0.415830E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 28789672.20 | 10542827.15 |
November | 0.149361E+10 | 0.403409E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 9232807.19 | 42342697.35 |
December | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 309973.98 | 85070087.93 |
Annual Sum or Average | 0.182090E+11 | 0.489965E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.486094E+09 | 0.315587E+09 |
Minimum of Months | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 32302.74 | 0.00 |
Maximum of Months | 0.155131E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 92046723.40 | 95933561.38 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.120348E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170782E+09 |
February | 0.236489E+11 | 0.106385E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1675206.95 | 0.103136E+09 |
March | 0.262800E+11 | 0.112283E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22978937.06 | 46314667.41 |
April | 0.253579E+11 | 0.103316E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88396778.66 | 4871461.47 |
May | 0.262123E+11 | 0.103741E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146933E+09 | 123512.86 |
June | 0.254132E+11 | 0.998684E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151850E+09 | 25863.13 |
July | 0.261570E+11 | 0.105146E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127180E+09 | 26191.12 |
August | 0.262677E+11 | 0.109695E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102046E+09 | 15252.24 |
September | 0.253456E+11 | 0.109218E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79249510.09 | 40264.23 |
October | 0.261693E+11 | 0.117689E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43223971.04 | 23790013.38 |
November | 0.253025E+11 | 0.114568E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11110840.77 | 81514516.87 |
December | 0.261570E+11 | 0.119827E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57160.10 | 0.155125E+09 |
Annual Sum or Average | 0.308468E+12 | 0.132208E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.774702E+09 | 0.585765E+09 |
Minimum of Months | 0.236489E+11 | 0.998684E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15252.24 |
Maximum of Months | 0.262800E+11 | 0.120348E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151850E+09 | 0.170782E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.105437E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56598.47 | 0.495790E+09 |
February | 0.702046E+11 | 0.949817E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7707419.51 | 0.300271E+09 |
March | 0.780153E+11 | 0.104922E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72158477.98 | 0.137766E+09 |
April | 0.752779E+11 | 0.100558E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255698E+09 | 15042072.92 |
May | 0.778146E+11 | 0.103979E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421074E+09 | 379289.27 |
June | 0.754422E+11 | 0.100746E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433709E+09 | 82542.38 |
July | 0.776503E+11 | 0.103828E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362362E+09 | 75153.33 |
August | 0.779788E+11 | 0.104866E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289801E+09 | 43904.09 |
September | 0.752414E+11 | 0.101320E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224047E+09 | 119358.79 |
October | 0.776868E+11 | 0.105154E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126249E+09 | 70754321.05 |
November | 0.751137E+11 | 0.101996E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36206268.75 | 0.236327E+09 |
December | 0.776503E+11 | 0.105084E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 787416.88 | 0.448732E+09 |
Annual Sum or Average | 0.915726E+12 | 0.123287E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222986E+10 | 0.170538E+10 |
Minimum of Months | 0.702046E+11 | 0.949817E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56598.47 | 43904.09 |
Maximum of Months | 0.780153E+11 | 0.105437E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433709E+09 | 0.495790E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15254.72 | 38034871.83 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1080604.67 | 20696691.08 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9174311.75 | 6780387.95 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30748490.26 | 313863.93 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47305836.09 | 0.00 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48231166.65 | 0.00 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42067752.90 | 0.00 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35448482.76 | 0.00 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29142327.44 | 0.00 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16555817.33 | 2276601.56 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4626526.81 | 14233340.62 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 86841.82 | 33252781.33 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264483E+09 | 0.115589E+09 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15254.72 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48231166.65 | 38034871.83 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18110.78 | 37320447.02 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 966852.87 | 21425376.79 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8809647.07 | 8118385.49 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30377927.93 | 543385.82 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47280791.22 | 2271.82 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48208000.56 | 0.00 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42064574.98 | 0.00 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35449017.04 | 0.00 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29117371.95 | 0.00 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15972725.39 | 3095831.79 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4550057.71 | 15622623.78 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 137017.70 | 32812859.73 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262952E+09 | 0.118941E+09 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18110.78 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48208000.56 | 37320447.02 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 82476868.03 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17070940.27 |
February | 0.00 | 74484663.28 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 933.75 | 11205781.37 |
March | 0.00 | 81821381.83 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 700029.86 | 6205740.70 |
April | 0.00 | 79911301.67 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3959246.60 | 1229555.03 |
May | 0.00 | 82149124.93 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7482232.61 | 123312.32 |
June | 0.00 | 79277307.08 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7901624.52 | 82027.29 |
July | 0.00 | 82793865.32 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5900084.62 | 31482.11 |
August | 0.00 | 81821381.83 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4080483.83 | 115996.37 |
September | 0.00 | 79932793.28 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2727544.49 | 373525.81 |
October | 0.00 | 82466122.22 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1617876.38 | 3720294.80 |
November | 0.00 | 79594304.38 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 198363.83 | 8938369.55 |
December | 0.00 | 82804611.13 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15720021.21 |
Annual Sum or Average | 0.00 | 0.969534E+09 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34568420.49 | 64817046.83 |
Minimum of Months | 0.00 | 74484663.28 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31482.11 |
Maximum of Months | 0.00 | 82804611.13 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7901624.52 | 17070940.27 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 82499421.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15394.95 | 10466769.74 |
February | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 326337.60 | 5967498.84 |
March | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2517833.77 | 2193241.82 |
April | 0.293479E+09 | 79933153.27 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8538487.41 | 131265.43 |
May | 0.303504E+09 | 82171588.45 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13235830.71 | 13.04 |
June | 0.293842E+09 | 79298985.31 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13489760.74 | 0.00 |
July | 0.303141E+09 | 82816505.16 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11766698.75 | 0.00 |
August | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9922990.79 | 0.00 |
September | 0.293479E+09 | 79954650.76 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8166913.56 | 0.00 |
October | 0.303322E+09 | 82488672.43 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4524486.63 | 808051.29 |
November | 0.293661E+09 | 79616069.29 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1361159.81 | 4289081.57 |
December | 0.303141E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67274.42 | 9155988.66 |
Annual Sum or Average | 0.357224E+10 | 0.969799E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73933169.14 | 33011910.37 |
Minimum of Months | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15394.95 | 0.00 |
Maximum of Months | 0.303685E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13489760.74 | 10466769.74 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15292.17 | 38280917.46 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1077282.91 | 20865234.22 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9166036.75 | 6868802.87 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30739071.55 | 320306.94 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47313825.79 | 0.00 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48242925.91 | 0.00 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42056400.52 | 0.00 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35437058.65 | 0.00 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29130007.33 | 0.00 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16542069.85 | 2292433.43 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4614950.18 | 14318450.73 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 86808.88 | 33426761.85 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264422E+09 | 0.116373E+09 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15292.17 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48242925.91 | 38280917.46 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27593.66 | 37273515.90 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 949571.21 | 21621077.27 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8760016.68 | 8429184.60 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30330066.73 | 650141.10 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47283200.00 | 3209.64 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48220122.81 | 0.00 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42052804.39 | 0.00 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35437192.44 | 0.00 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29100201.77 | 0.00 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15891178.90 | 3207516.90 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4495517.06 | 15837255.42 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 136824.22 | 32825630.02 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262684E+09 | 0.119848E+09 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27593.66 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48220122.81 | 37273515.90 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.120431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97422.88 | 45594738.50 |
February | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1480750.58 | 27349175.00 |
March | 0.387034E+10 | 0.120803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8903254.49 | 12563475.19 |
April | 0.373454E+10 | 0.116348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28442092.25 | 1372761.06 |
May | 0.386038E+10 | 0.120640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46217288.43 | 31582.91 |
June | 0.374269E+10 | 0.116882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47850987.20 | 5037.34 |
July | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40092825.51 | 4715.95 |
August | 0.386853E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32413925.95 | 4505.00 |
September | 0.373273E+10 | 0.116395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25780495.87 | 10710.57 |
October | 0.385404E+10 | 0.120385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14507430.11 | 6841445.33 |
November | 0.372639E+10 | 0.116789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4841879.25 | 22673474.67 |
December | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347038.99 | 41673333.26 |
Annual Sum or Average | 0.454292E+11 | 0.141847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250975E+09 | 0.158125E+09 |
Minimum of Months | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97422.88 | 4505.00 |
Maximum of Months | 0.387034E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47850987.20 | 45594738.50 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13797.49 | 38122062.01 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1043635.61 | 20809291.62 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9034356.60 | 6859282.19 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30512261.21 | 322471.47 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47041748.81 | 0.00 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47976430.99 | 0.00 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41820045.61 | 0.00 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35198412.17 | 0.00 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28903107.80 | 0.00 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16368727.76 | 2314042.38 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4540537.42 | 14336461.92 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79346.77 | 33369582.90 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262532E+09 | 0.116133E+09 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13797.49 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47976430.99 | 38122062.01 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16442.36 | 37324793.41 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 925118.72 | 21493212.74 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8686548.91 | 8067634.40 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30174271.83 | 500510.50 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47019371.65 | 1446.64 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47956475.74 | 0.00 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41816813.83 | 0.00 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35198691.35 | 0.00 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28880998.46 | 0.00 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15838593.57 | 2954061.67 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4477591.70 | 15488075.06 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 128943.01 | 32775521.93 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261120E+09 | 0.118605E+09 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16442.36 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47956475.74 | 37324793.41 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 82499421.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6557.86 | 19929814.85 |
February | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 527263.25 | 10803747.79 |
March | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4613026.92 | 3540144.84 |
April | 0.293479E+09 | 79933153.27 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15624490.15 | 165327.91 |
May | 0.303504E+09 | 82171588.45 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24100502.49 | 0.00 |
June | 0.293842E+09 | 79298985.31 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24572882.54 | 0.00 |
July | 0.303141E+09 | 82816505.16 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21398525.13 | 0.00 |
August | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18007879.63 | 0.00 |
September | 0.293479E+09 | 79954650.76 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14780830.25 | 0.00 |
October | 0.303322E+09 | 82488672.43 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8353039.66 | 1200635.15 |
November | 0.293661E+09 | 79616069.29 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2301409.85 | 7412521.56 |
December | 0.303141E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39112.40 | 17373377.63 |
Annual Sum or Average | 0.357224E+10 | 0.969799E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134326E+09 | 60425569.72 |
Minimum of Months | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6557.86 | 0.00 |
Maximum of Months | 0.303685E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24572882.54 | 19929814.85 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.253960E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7377.21 | 0.116458E+09 |
February | 0.415303E+11 | 0.225652E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1317008.67 | 70810986.35 |
March | 0.461508E+11 | 0.243781E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14168483.36 | 32579830.64 |
April | 0.445315E+11 | 0.228574E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54651369.03 | 3662421.78 |
May | 0.460320E+11 | 0.232409E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91802797.65 | 99532.33 |
June | 0.446286E+11 | 0.224840E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94789759.88 | 23466.30 |
July | 0.459349E+11 | 0.233897E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78775437.96 | 19911.04 |
August | 0.461292E+11 | 0.239918E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62376347.17 | 13357.20 |
September | 0.445099E+11 | 0.235405E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47800734.65 | 35027.81 |
October | 0.459565E+11 | 0.248783E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27133317.57 | 16585992.32 |
November | 0.444343E+11 | 0.243342E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7697931.12 | 54310576.24 |
December | 0.459349E+11 | 0.253194E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 143739.13 | 0.104383E+09 |
Annual Sum or Average | 0.541708E+12 | 0.286375E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480664E+09 | 0.398982E+09 |
Minimum of Months | 0.415303E+11 | 0.224840E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7377.21 | 13357.20 |
Maximum of Months | 0.461508E+11 | 0.253960E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94789759.88 | 0.116458E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.253960E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1043.46 | 0.118450E+09 |
February | 0.415303E+11 | 0.225652E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1110077.20 | 71902081.28 |
March | 0.461508E+11 | 0.243781E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13837284.88 | 32896593.03 |
April | 0.445315E+11 | 0.228574E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54486626.26 | 3668441.85 |
May | 0.460320E+11 | 0.232409E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91752083.96 | 99540.49 |
June | 0.446286E+11 | 0.224840E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94753601.01 | 23468.80 |
July | 0.459349E+11 | 0.233897E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78709200.82 | 19913.89 |
August | 0.461292E+11 | 0.239918E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62286732.87 | 13359.71 |
September | 0.445099E+11 | 0.235405E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47585693.16 | 35033.40 |
October | 0.459565E+11 | 0.248783E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26834171.06 | 16641822.39 |
November | 0.444343E+11 | 0.243342E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7232882.55 | 54795252.44 |
December | 0.459349E+11 | 0.253194E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83684.15 | 0.106163E+09 |
Annual Sum or Average | 0.541708E+12 | 0.286375E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478673E+09 | 0.404708E+09 |
Minimum of Months | 0.415303E+11 | 0.224840E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1043.46 | 13359.71 |
Maximum of Months | 0.461508E+11 | 0.253960E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94753601.01 | 0.118450E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113250E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106312E+09 |
February | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 834295.81 | 63828370.85 |
March | 0.410691E+10 | 0.113599E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 12177090.59 | 28698880.16 |
April | 0.396281E+10 | 0.109410E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 48827735.70 | 3056077.45 |
May | 0.409635E+10 | 0.113446E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 82248064.99 | 71814.17 |
June | 0.397146E+10 | 0.109912E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 84972434.77 | 17701.23 |
July | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 70577859.74 | 4547.37 |
August | 0.410499E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 55937300.62 | 10678.15 |
September | 0.396089E+10 | 0.109454E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 42845653.24 | 30856.68 |
October | 0.408962E+10 | 0.113207E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 23788680.59 | 14245850.38 |
November | 0.395417E+10 | 0.109825E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 6036347.10 | 47976285.28 |
December | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 20975.60 | 94851110.73 |
Annual Sum or Average | 0.482060E+11 | 0.133389E+11 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.428266E+09 | 0.359104E+09 |
Minimum of Months | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4547.37 |
Maximum of Months | 0.410691E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 84972434.77 | 0.106312E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.127458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108770.25 | 79337927.84 |
February | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2286769.36 | 45688444.44 |
March | 0.409620E+10 | 0.127851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14768299.68 | 19946469.20 |
April | 0.395248E+10 | 0.123137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49626101.29 | 1919133.88 |
May | 0.408566E+10 | 0.127679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81208255.89 | 32424.15 |
June | 0.396110E+10 | 0.123701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83905019.35 | 2544.46 |
July | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69977354.95 | 2222.96 |
August | 0.409429E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56205496.94 | 8467.91 |
September | 0.395056E+10 | 0.123186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45237372.33 | 3975.31 |
October | 0.407896E+10 | 0.127409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25376876.76 | 10030678.65 |
November | 0.394385E+10 | 0.123603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8457502.38 | 35576605.90 |
December | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505519.50 | 69726010.41 |
Annual Sum or Average | 0.480803E+11 | 0.150123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437663E+09 | 0.262275E+09 |
Minimum of Months | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108770.25 | 2222.96 |
Maximum of Months | 0.409620E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83905019.35 | 79337927.84 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 9271.23 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 9271.23 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 9271.23 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 9271.23 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 9271.23 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 9271.23 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 9271.23 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 9271.23 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 9271.23 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 9271.23 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 9271.23 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 9271.23 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 512.31 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 49.83 | 05-JAN-07:00 |
February | 1169.53 | 01-FEB-00:10 | 512.31 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.73 | 22-FEB-15:00 | 42.84 | 02-FEB-06:00 |
March | 1169.53 | 01-MAR-00:10 | 512.31 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.73 | 28-MAR-15:00 | 24.12 | 01-MAR-03:00 |
April | 1169.53 | 01-APR-00:10 | 512.31 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.71 | 15-APR-15:00 | 14.43 | 11-APR-05:00 |
May | 1169.53 | 01-MAY-00:10 | 512.31 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.06 | 03-MAY-15:00 | 0.17 | 13-MAY-05:00 |
June | 1169.53 | 01-JUN-00:10 | 512.31 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.12 | 08-JUN-16:00 | 0.00 | 01-JUN-00:05 |
July | 1169.53 | 01-JUL-00:10 | 512.31 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.71 | 07-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 1169.53 | 01-AUG-00:10 | 512.31 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.99 | 07-AUG-15:00 | 1.05 | 15-AUG-24:00 |
September | 1169.53 | 01-SEP-00:10 | 512.31 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.52 | 17-SEP-20:00 | 0.95 | 27-SEP-05:00 |
October | 1169.53 | 01-OCT-23:10 | 512.31 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.96 | 02-OCT-14:00 | 19.80 | 31-OCT-05:00 |
November | 1169.53 | 01-NOV-00:10 | 512.31 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 | 04-NOV-14:00 | 34.98 | 27-NOV-06:00 |
December | 1169.53 | 01-DEC-00:10 | 512.31 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.70 | 28-DEC-14:00 | 49.32 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Maximum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 54.12 | 49.83 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 593.26 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 | 12-JAN-15:00 | 21.16 | 05-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 593.26 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.40 | 22-FEB-15:00 | 18.54 | 02-FEB-06:00 |
March | 1354.32 | 01-MAR-00:10 | 593.26 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.86 | 28-MAR-15:00 | 11.34 | 01-MAR-04:00 |
April | 1354.32 | 01-APR-00:10 | 593.26 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.10 | 15-APR-15:00 | 7.26 | 11-APR-05:00 |
May | 1354.32 | 01-MAY-00:10 | 593.26 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 03-MAY-15:00 | 1.26 | 13-MAY-05:00 |
June | 1354.32 | 01-JUN-00:10 | 593.26 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 | 08-JUN-16:00 | 0.62 | 18-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 593.26 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.11 | 02-JUL-16:00 | 0.68 | 19-JUL-03:00 |
August | 1354.32 | 01-AUG-00:10 | 593.26 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.01 | 07-AUG-15:00 | 0.66 | 15-AUG-24:00 |
September | 1354.32 | 01-SEP-00:10 | 593.26 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.10 | 17-SEP-20:00 | 1.10 | 27-SEP-05:00 |
October | 1354.32 | 01-OCT-23:10 | 593.26 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.45 | 02-OCT-14:00 | 9.37 | 31-OCT-05:00 |
November | 1354.32 | 01-NOV-00:10 | 593.26 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.40 | 04-NOV-13:05 | 15.88 | 27-NOV-06:00 |
December | 1354.32 | 01-DEC-00:10 | 593.26 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.21 | 24-DEC-15:00 | 21.01 | 21-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 | 0.62 | |||||
Maximum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 21.16 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.05 | 12-JAN-15:00 | 46.37 | 05-JAN-07:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.43 | 22-FEB-15:00 | 40.72 | 02-FEB-06:10 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.94 | 28-MAR-15:00 | 24.09 | 01-MAR-04:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.96 | 15-APR-15:00 | 15.27 | 11-APR-05:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.53 | 03-MAY-15:00 | 1.97 | 13-MAY-05:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.37 | 08-JUN-16:00 | 1.19 | 18-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.88 | 07-JUL-15:00 | 1.06 | 19-JUL-03:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 07-AUG-15:00 | 1.56 | 15-AUG-24:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.32 | 17-SEP-20:00 | 2.20 | 27-SEP-05:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.11 | 02-OCT-14:00 | 19.98 | 31-OCT-05:10 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.30 | 04-NOV-14:00 | 34.65 | 27-NOV-06:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 | 24-DEC-15:00 | 46.29 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 5.05 | 1.06 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 49.53 | 46.37 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 152.61 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.87 | 12-JAN-15:00 | 26.44 | 05-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 152.61 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.09 | 22-FEB-15:00 | 23.25 | 02-FEB-06:00 |
March | 220.32 | 01-MAR-00:10 | 152.61 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 28-MAR-15:00 | 13.77 | 01-MAR-04:00 |
April | 220.32 | 01-APR-00:10 | 152.61 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.55 | 15-APR-15:00 | 8.59 | 11-APR-05:00 |
May | 220.32 | 01-MAY-00:10 | 152.61 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.46 | 03-MAY-15:00 | 1.07 | 13-MAY-05:00 |
June | 220.32 | 01-JUN-00:10 | 152.61 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.48 | 08-JUN-16:00 | 0.58 | 18-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 152.61 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.01 | 07-JUL-15:00 | 0.53 | 19-JUL-03:00 |
August | 220.32 | 01-AUG-00:10 | 152.61 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.94 | 07-AUG-15:00 | 0.90 | 15-AUG-24:00 |
September | 220.32 | 01-SEP-00:10 | 152.61 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.22 | 17-SEP-20:00 | 1.13 | 27-SEP-05:00 |
October | 220.32 | 01-OCT-23:10 | 152.61 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.45 | 02-OCT-14:00 | 11.33 | 31-OCT-05:00 |
November | 220.32 | 01-NOV-00:10 | 152.61 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.06 | 04-NOV-14:00 | 19.82 | 27-NOV-06:00 |
December | 220.32 | 01-DEC-00:10 | 152.61 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24-DEC-15:00 | 26.55 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 2.87 | 0.53 | |||||
Maximum of Months | 220.32 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 28.48 | 26.55 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 400.68 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 2.73 | 12-JAN-15:00 | 73.52 | 05-JAN-07:00 |
February | 907.20 | 01-FEB-00:10 | 400.68 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 14.56 | 22-FEB-14:00 | 64.35 | 02-FEB-06:50 |
March | 907.20 | 01-MAR-00:10 | 400.68 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 45.56 | 28-MAR-16:00 | 37.84 | 01-MAR-06:10 |
April | 907.20 | 01-APR-00:10 | 400.68 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 60.00 | 16-APR-15:30 | 23.15 | 11-APR-05:10 |
May | 907.20 | 01-MAY-00:10 | 400.68 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 73.13 | 03-MAY-16:00 | 1.46 | 13-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 400.68 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 73.89 | 08-JUN-16:00 | 0.14 | 18-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 400.68 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 63.08 | 02-JUL-16:40 | 0.00 | 01-JUL-00:10 |
August | 907.20 | 01-AUG-00:10 | 400.68 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 50.45 | 07-AUG-16:00 | 0.00 | 01-AUG-00:05 |
September | 907.20 | 01-SEP-00:10 | 400.68 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 46.19 | 26-SEP-15:30 | 2.98 | 27-SEP-05:10 |
October | 907.20 | 01-OCT-23:10 | 400.68 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 47.85 | 01-OCT-15:30 | 30.71 | 31-OCT-05:10 |
November | 907.20 | 01-NOV-00:10 | 400.68 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 26.10 | 04-NOV-15:20 | 53.58 | 27-NOV-06:10 |
December | 907.20 | 01-DEC-00:10 | 400.68 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 7.93 | 24-DEC-15:00 | 70.58 | 21-DEC-06:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 2.73 | 0.00 | ||||||
Maximum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 73.89 | 73.52 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1573.46 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 122.64 | 05-JAN-06:00 |
February | 15368.40 | 01-FEB-00:10 | 1573.46 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.31 | 22-FEB-15:00 | 108.53 | 02-FEB-06:00 |
March | 15368.40 | 01-MAR-00:10 | 1573.46 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.15 | 28-MAR-15:00 | 68.19 | 01-MAR-04:00 |
April | 15368.40 | 01-APR-00:10 | 1573.46 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.63 | 15-APR-15:00 | 42.64 | 11-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 1573.46 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.50 | 03-MAY-15:00 | 8.19 | 13-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 1573.46 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.64 | 08-JUN-16:00 | 3.88 | 18-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1573.46 | 03-JUL-19:19 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.63 | 07-JUL-15:00 | 4.99 | 19-JUL-03:00 |
August | 15368.40 | 01-AUG-00:10 | 1573.46 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.56 | 07-AUG-15:00 | 3.76 | 15-AUG-24:00 |
September | 15368.40 | 01-SEP-00:10 | 1573.46 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.75 | 17-SEP-20:00 | 6.28 | 27-SEP-05:00 |
October | 15368.40 | 01-OCT-23:10 | 1573.46 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.07 | 02-OCT-14:00 | 55.35 | 31-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1573.46 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.88 | 04-NOV-14:00 | 93.72 | 27-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 1573.46 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 | 28-DEC-14:00 | 122.77 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.76 | |||||
Maximum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 119.64 | 122.77 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 10645.38 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.45 | 12-JAN-15:00 | 358.03 | 05-JAN-06:03 |
February | 45622.98 | 01-FEB-00:10 | 10645.38 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.16 | 22-FEB-15:00 | 319.42 | 02-FEB-06:00 |
March | 45622.98 | 01-MAR-00:10 | 10645.38 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.40 | 28-MAR-15:00 | 197.92 | 01-MAR-04:00 |
April | 45622.98 | 01-APR-00:10 | 10645.38 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.66 | 15-APR-15:00 | 121.89 | 11-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 10645.38 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 344.25 | 03-MAY-15:00 | 23.46 | 13-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 10645.38 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.88 | 08-JUN-15:00 | 12.51 | 18-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 10645.38 | 03-JUL-19:19 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.41 | 02-JUL-16:00 | 14.31 | 19-JUL-03:00 |
August | 45622.98 | 01-AUG-00:10 | 10645.38 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.83 | 07-AUG-15:00 | 10.78 | 15-AUG-24:00 |
September | 45622.98 | 01-SEP-00:10 | 10645.38 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.69 | 17-SEP-20:00 | 17.98 | 27-SEP-05:00 |
October | 45622.98 | 01-OCT-23:10 | 10645.38 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.53 | 02-OCT-14:00 | 158.20 | 31-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 10645.38 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.05 | 04-NOV-15:00 | 273.80 | 27-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 10645.38 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 25-DEC-14:00 | 358.59 | 21-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 10645.38 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 10.45 | 10.78 | |||||
Maximum of Months | 45622.98 | 10645.38 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 344.25 | 358.59 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 | 12-JAN-16:07 | 29.20 | 05-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.55 | 22-FEB-16:10 | 25.13 | 02-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.80 | 28-MAR-15:40 | 13.50 | 01-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.15 | 15-APR-15:50 | 6.37 | 11-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.65 | 03-MAY-16:00 | 0.00 | 01-MAY-00:05 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.22 | 08-JUN-16:00 | 0.00 | 01-JUN-00:05 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 02-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.29 | 07-AUG-15:10 | 0.00 | 01-AUG-00:05 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 17-SEP-20:00 | 0.00 | 01-SEP-00:05 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.68 | 02-OCT-15:10 | 9.67 | 31-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.44 | 04-NOV-15:10 | 20.34 | 27-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.11 | 28-DEC-16:10 | 28.90 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 | 0.00 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 35.22 | 29.20 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 | 12-JAN-16:09 | 29.19 | 05-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.55 | 22-FEB-16:10 | 25.13 | 02-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.91 | 28-MAR-15:10 | 13.50 | 01-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.36 | 15-APR-15:10 | 7.53 | 11-APR-05:30 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.79 | 03-MAY-16:00 | 0.99 | 13-MAY-07:20 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.15 | 08-JUN-16:00 | 0.00 | 01-JUN-00:05 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 02-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.29 | 07-AUG-15:10 | 0.00 | 01-AUG-00:05 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | 17-SEP-20:00 | 0.00 | 01-SEP-00:05 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.08 | 02-OCT-15:10 | 10.25 | 31-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.44 | 04-NOV-15:07 | 20.34 | 27-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.10 | 28-DEC-16:08 | 28.90 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 | 0.00 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 35.15 | 29.19 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 74.62 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 10.87 | 05-JAN-07:00 |
February | 0.00 | 01-FEB-00:10 | 74.62 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 | 22-FEB-15:00 | 9.60 | 02-FEB-07:10 |
March | 0.00 | 01-MAR-00:10 | 74.62 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.94 | 28-MAR-15:00 | 6.43 | 01-MAR-04:00 |
April | 0.00 | 01-APR-00:10 | 74.62 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.90 | 15-APR-15:00 | 4.41 | 11-APR-05:00 |
May | 0.00 | 01-MAY-00:10 | 74.62 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.60 | 03-MAY-15:00 | 1.86 | 13-MAY-05:00 |
June | 0.00 | 01-JUN-00:10 | 74.62 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 | 08-JUN-16:00 | 1.56 | 18-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 74.62 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.91 | 07-JUL-15:00 | 1.61 | 19-JUL-03:00 |
August | 0.00 | 01-AUG-00:10 | 74.62 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.64 | 07-AUG-15:00 | 1.52 | 15-AUG-24:00 |
September | 0.00 | 01-SEP-00:10 | 74.62 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.73 | 17-SEP-20:00 | 1.71 | 27-SEP-05:00 |
October | 0.00 | 01-OCT-00:10 | 74.62 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.30 | 02-OCT-14:00 | 5.35 | 31-OCT-05:00 |
November | 0.00 | 01-NOV-00:10 | 74.62 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 | 04-NOV-14:00 | 8.38 | 27-NOV-06:00 |
December | 0.00 | 01-DEC-00:10 | 74.62 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 10.51 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 74.62 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 | |||||
Maximum of Months | 0.00 | 74.62 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 | 10.87 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 74.64 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 | 12-JAN-16:07 | 8.15 | 05-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 74.64 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 22-FEB-16:10 | 7.01 | 02-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 74.64 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.39 | 28-MAR-15:10 | 3.77 | 01-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 74.64 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.28 | 15-APR-15:10 | 1.96 | 11-APR-05:30 |
May | 180.00 | 01-MAY-00:10 | 74.64 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.96 | 03-MAY-15:10 | 0.04 | 13-MAY-07:20 |
June | 180.00 | 01-JUN-00:10 | 74.64 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.98 | 08-JUN-16:00 | 0.00 | 01-JUN-00:05 |
July | 180.00 | 01-JUL-00:10 | 74.64 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.29 | 07-JUL-15:10 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 74.64 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 | 07-AUG-15:10 | 0.00 | 01-AUG-00:05 |
September | 180.00 | 01-SEP-00:10 | 74.64 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.16 | 17-SEP-20:00 | 0.00 | 01-SEP-00:05 |
October | 180.00 | 01-OCT-00:10 | 74.64 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 | 02-OCT-15:08 | 2.82 | 31-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 74.64 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.03 | 04-NOV-15:09 | 5.68 | 27-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 74.64 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.37 | 24-DEC-14:00 | 8.07 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 | |||||
Maximum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 9.98 | 8.15 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 | 12-JAN-16:09 | 29.20 | 05-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.55 | 22-FEB-16:10 | 25.13 | 02-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.91 | 28-MAR-15:10 | 13.73 | 01-MAR-08:20 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.66 | 15-APR-15:10 | 6.37 | 11-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.47 | 03-MAY-15:50 | 0.00 | 01-MAY-00:05 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.75 | 08-JUN-16:00 | 0.00 | 01-JUN-00:05 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.68 | 07-JUL-15:10 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.29 | 07-AUG-15:10 | 0.00 | 01-AUG-00:05 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 17-SEP-20:00 | 0.00 | 01-SEP-00:05 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.91 | 02-OCT-15:10 | 9.67 | 31-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.44 | 04-NOV-15:10 | 20.34 | 27-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.11 | 28-DEC-16:08 | 28.90 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 | 0.00 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 35.75 | 29.20 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 | 12-JAN-16:07 | 29.19 | 05-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.55 | 22-FEB-16:08 | 25.13 | 02-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.91 | 28-MAR-15:10 | 13.50 | 01-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.54 | 15-APR-15:10 | 7.36 | 11-APR-05:30 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.52 | 03-MAY-15:40 | 1.24 | 13-MAY-08:00 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.74 | 08-JUN-16:00 | 0.00 | 01-JUN-00:05 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.68 | 07-JUL-15:10 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.30 | 07-AUG-15:10 | 0.00 | 01-AUG-00:05 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | 17-SEP-20:00 | 0.00 | 01-SEP-00:05 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.08 | 02-OCT-15:10 | 10.16 | 31-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.44 | 04-NOV-15:07 | 20.34 | 27-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 | 24-DEC-14:00 | 28.90 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 | 0.00 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 35.74 | 29.19 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 | 12-JAN-15:00 | 35.25 | 05-JAN-07:00 |
February | 2263.36 | 01-FEB-00:10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.74 | 22-FEB-15:00 | 31.11 | 02-FEB-06:00 |
March | 2263.36 | 01-MAR-00:10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.69 | 28-MAR-15:00 | 18.88 | 01-MAR-04:00 |
April | 2263.36 | 01-APR-00:10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 15-APR-15:00 | 12.36 | 11-APR-05:00 |
May | 2263.36 | 01-MAY-00:10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.86 | 03-MAY-15:00 | 2.09 | 13-MAY-05:00 |
June | 2263.36 | 01-JUN-00:10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.90 | 08-JUN-16:00 | 0.97 | 18-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.60 | 07-JUL-15:00 | 1.03 | 19-JUL-03:00 |
August | 2263.36 | 01-AUG-00:10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.18 | 07-AUG-15:00 | 1.17 | 15-AUG-24:00 |
September | 2263.36 | 01-SEP-00:10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.81 | 17-SEP-20:00 | 1.89 | 27-SEP-05:00 |
October | 2263.36 | 01-OCT-23:10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 02-OCT-14:00 | 15.91 | 31-OCT-05:00 |
November | 2263.36 | 01-NOV-00:10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 04-NOV-14:00 | 27.22 | 27-NOV-06:00 |
December | 2263.36 | 01-DEC-00:10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.54 | 25-DEC-14:00 | 35.84 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 | 0.97 | ||||
Maximum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.90 | 35.84 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.19 | 12-JAN-16:10 | 29.31 | 05-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.45 | 22-FEB-16:10 | 25.24 | 02-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 28-MAR-15:50 | 13.61 | 01-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.01 | 15-APR-15:50 | 6.48 | 11-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.31 | 01-MAY-16:00 | 0.00 | 01-MAY-00:05 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.74 | 07-JUN-16:00 | 0.00 | 01-JUN-00:05 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.58 | 02-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.21 | 07-AUG-15:10 | 0.00 | 01-AUG-00:05 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.58 | 17-SEP-20:00 | 0.00 | 01-SEP-00:05 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.57 | 02-OCT-15:10 | 9.78 | 31-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 | 04-NOV-15:10 | 20.45 | 27-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 | 28-DEC-16:10 | 29.02 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 3.19 | 0.00 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 34.74 | 29.31 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.19 | 12-JAN-16:07 | 29.31 | 05-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.45 | 22-FEB-16:10 | 25.24 | 02-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.81 | 28-MAR-15:10 | 13.61 | 01-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.13 | 15-APR-15:10 | 7.02 | 11-APR-05:30 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.47 | 01-MAY-16:00 | 0.71 | 13-MAY-07:20 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.77 | 08-JUN-16:00 | 0.00 | 01-JUN-00:05 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.58 | 02-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.21 | 07-AUG-15:10 | 0.00 | 01-AUG-00:05 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.57 | 17-SEP-20:00 | 0.00 | 01-SEP-00:05 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.97 | 02-OCT-15:10 | 9.78 | 31-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 | 04-NOV-15:07 | 20.45 | 27-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 | 28-DEC-16:08 | 29.01 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 3.19 | 0.00 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 34.77 | 29.31 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 74.64 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 | 12-JAN-16:10 | 15.00 | 05-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 74.64 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.32 | 22-FEB-16:10 | 12.92 | 02-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 74.64 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.62 | 28-MAR-15:40 | 6.96 | 01-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 74.64 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.95 | 15-APR-15:10 | 3.31 | 11-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 74.64 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.10 | 03-MAY-15:50 | 0.00 | 01-MAY-00:05 |
June | 180.00 | 01-JUN-00:10 | 74.64 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.25 | 08-JUN-16:00 | 0.00 | 01-JUN-00:05 |
July | 180.00 | 01-JUL-00:10 | 74.64 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.14 | 02-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 74.64 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.82 | 07-AUG-15:40 | 0.00 | 01-AUG-00:05 |
September | 180.00 | 01-SEP-00:10 | 74.64 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.09 | 17-SEP-20:00 | 0.00 | 01-SEP-00:05 |
October | 180.00 | 01-OCT-00:10 | 74.64 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.93 | 02-OCT-16:00 | 5.00 | 31-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 74.64 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.19 | 04-NOV-15:10 | 10.46 | 27-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 74.64 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 | 28-DEC-16:10 | 14.85 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 | 0.00 | |||||
Maximum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 18.25 | 15.00 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 | 12-JAN-15:00 | 83.81 | 05-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.46 | 22-FEB-15:00 | 74.06 | 02-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.59 | 28-MAR-15:00 | 45.33 | 01-MAR-04:00 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.58 | 15-APR-15:00 | 27.76 | 11-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.25 | 03-MAY-15:00 | 5.66 | 13-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.34 | 08-JUN-16:00 | 3.21 | 18-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.58 | 07-JUL-15:00 | 3.61 | 19-JUL-03:00 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.63 | 07-AUG-15:00 | 2.82 | 15-AUG-24:00 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.39 | 17-SEP-20:00 | 4.43 | 27-SEP-05:00 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.75 | 02-OCT-14:00 | 35.92 | 31-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.53 | 04-NOV-14:00 | 62.23 | 27-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.65 | 28-DEC-14:00 | 83.39 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 | 2.82 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 76.34 | 83.81 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 | 12-JAN-15:00 | 84.14 | 05-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.43 | 22-FEB-15:00 | 74.06 | 02-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.59 | 28-MAR-15:00 | 45.33 | 01-MAR-04:00 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.58 | 15-APR-15:00 | 27.76 | 11-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.25 | 03-MAY-15:00 | 5.66 | 13-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.34 | 08-JUN-16:00 | 3.21 | 18-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.58 | 07-JUL-15:00 | 3.61 | 19-JUL-03:00 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.63 | 07-AUG-15:00 | 2.82 | 15-AUG-24:00 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.39 | 17-SEP-20:00 | 4.43 | 27-SEP-05:00 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.75 | 02-OCT-14:00 | 35.92 | 31-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.53 | 04-NOV-14:00 | 62.23 | 27-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 | 28-DEC-14:00 | 83.45 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 | 2.82 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 76.34 | 84.14 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1090.83 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 75.30 | 05-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 1090.83 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 10.75 | 22-FEB-15:00 | 66.22 | 02-FEB-06:10 |
March | 2401.70 | 01-MAR-00:10 | 1090.83 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 39.95 | 28-MAR-15:00 | 39.19 | 01-MAR-06:10 |
April | 2401.70 | 01-APR-00:10 | 1090.83 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 55.16 | 15-APR-15:00 | 24.86 | 11-APR-05:00 |
May | 2401.70 | 01-MAY-00:10 | 1090.83 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 68.29 | 03-MAY-15:00 | 5.07 | 13-MAY-05:00 |
June | 2401.70 | 01-JUN-00:10 | 1090.83 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 68.38 | 08-JUN-16:00 | 2.86 | 18-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1090.83 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 55.16 | 07-JUL-15:00 | 1.40 | 19-JUL-03:10 |
August | 2401.70 | 01-AUG-00:10 | 1090.83 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 45.35 | 07-AUG-15:00 | 2.53 | 15-AUG-24:00 |
September | 2401.70 | 01-SEP-00:10 | 1090.83 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 46.03 | 17-SEP-20:00 | 3.97 | 27-SEP-05:00 |
October | 2401.70 | 01-OCT-23:10 | 1090.83 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 42.77 | 02-OCT-14:00 | 32.16 | 31-OCT-05:00 |
November | 2401.70 | 01-NOV-00:10 | 1090.83 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 21.99 | 04-NOV-14:00 | 55.51 | 27-NOV-06:10 |
December | 2401.70 | 01-DEC-00:10 | 1090.83 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 1.83 | 28-DEC-14:00 | 72.93 | 21-DEC-06:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 | ||||||
Maximum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 68.38 | 75.30 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 | 12-JAN-15:00 | 62.29 | 05-JAN-07:00 |
February | 2395.44 | 01-FEB-00:10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.61 | 22-FEB-15:00 | 53.60 | 02-FEB-06:00 |
March | 2395.44 | 01-MAR-00:10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.06 | 28-MAR-15:00 | 30.27 | 01-MAR-04:00 |
April | 2395.44 | 01-APR-00:10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.95 | 15-APR-15:00 | 19.14 | 11-APR-05:00 |
May | 2395.44 | 01-MAY-00:10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.81 | 03-MAY-15:00 | 2.49 | 13-MAY-05:00 |
June | 2395.44 | 01-JUN-00:10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.88 | 08-JUN-16:00 | 0.89 | 18-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.95 | 07-JUL-15:00 | 0.57 | 19-JUL-03:00 |
August | 2395.44 | 01-AUG-00:10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.35 | 07-AUG-15:00 | 2.17 | 15-AUG-24:00 |
September | 2395.44 | 01-SEP-00:10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.02 | 17-SEP-20:00 | 1.66 | 27-SEP-05:00 |
October | 2395.44 | 01-OCT-23:10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.83 | 02-OCT-14:00 | 25.03 | 31-OCT-05:00 |
November | 2395.44 | 01-NOV-00:10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.84 | 04-NOV-13:05 | 43.79 | 27-NOV-06:00 |
December | 2395.44 | 01-DEC-00:10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.37 | 24-DEC-15:00 | 61.66 | 23-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 | 0.57 | ||||
Maximum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.88 | 62.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17415.49 | 13-JAN-22:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15143.87 | 01-FEB-22:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13047.48 | 12-MAR-10:33 | 11501.89 | 9271.10 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13344.07 | 16-APR-10:33 | 11501.89 | 9271.10 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14125.74 | 18-MAY-18:10 | 53675.50 | 49446.67 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15414.08 | 12-JUN-18:10 | 44729.58 | 41205.56 | 45627.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21033.20 | 18-JUL-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23313.34 | 09-AUG-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23612.19 | 27-SEP-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22561.02 | 05-OCT-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21839.98 | 01-NOV-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20779.37 | 01-DEC-22:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13047.48 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23612.19 | 53675.50 | 49446.67 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2049.79 | 12-JAN-13:50 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.54 |
February | 2653.64 | 20-FEB-13:00 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 5.37 | 0.00 |
March | 3071.60 | 13-MAR-13:20 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 22.39 | 0.00 |
April | 3370.99 | 15-APR-13:40 | 389.84 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 42.83 | 0.00 |
May | 3419.60 | 04-MAY-15:04 | 3248.70 | 711.55 | 1262.95 | 0.00 | 0.00 | 0.00 | 0.00 | 48.55 | 0.00 |
June | 3471.50 | 12-JUN-18:04 | 4548.18 | 2276.95 | 3247.60 | 0.00 | 0.00 | 0.00 | 0.00 | 48.08 | 0.00 |
July | 3195.59 | 07-JUL-18:03 | 5457.82 | 2732.34 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 37.84 | 0.00 |
August | 2991.61 | 07-AUG-18:03 | 5457.82 | 2732.34 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 31.97 | 0.00 |
September | 3466.35 | 26-SEP-13:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 30.84 | 0.00 |
October | 3776.95 | 02-OCT-13:10 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 33.52 | 0.00 |
November | 3372.31 | 04-NOV-13:20 | 779.69 | 284.62 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 17.22 | 0.00 |
December | 2682.51 | 02-DEC-13:30 | 389.84 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2049.79 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3776.95 | 5457.82 | 2732.34 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 48.55 | 2.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1377.28 | 12-JAN-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.59 |
February | 1671.54 | 22-FEB-22:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.58 |
March | 2064.09 | 29-MAR-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 0.00 |
April | 2369.79 | 28-APR-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 10.22 | 0.00 |
May | 2496.27 | 04-MAY-20:10 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 11.45 | 0.00 |
June | 2555.54 | 12-JUN-20:10 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 14.89 | 0.00 |
July | 2448.55 | 03-JUL-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 12.04 | 0.00 |
August | 2355.46 | 07-AUG-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9.95 | 0.00 |
September | 2247.70 | 22-SEP-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.92 | 0.00 |
October | 2218.69 | 02-OCT-20:10 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.39 | 0.00 |
November | 1844.74 | 09-NOV-22:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.70 |
December | 1470.22 | 01-DEC-22:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1377.28 | 1053.36 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2555.54 | 1203.84 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 14.89 | 14.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1170.65 | 26-JAN-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.53 |
February | 1289.76 | 23-FEB-19:10 | 1336.61 | 3648.94 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.70 |
March | 1482.47 | 29-MAR-18:08 | 1336.61 | 3648.94 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 18.95 | 0.00 |
April | 2106.01 | 28-APR-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 27.71 | 0.00 |
May | 2449.26 | 04-MAY-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 27.83 | 0.00 |
June | 2650.28 | 12-JUN-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 35.80 | 0.00 |
July | 2563.40 | 07-JUL-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 28.91 | 0.00 |
August | 2377.45 | 08-AUG-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 23.02 | 0.00 |
September | 2123.87 | 01-SEP-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 18.91 | 0.00 |
October | 1799.17 | 02-OCT-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 8.74 | 0.00 |
November | 1383.60 | 01-NOV-18:08 | 1336.61 | 3648.94 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 3.47 | 0.00 |
December | 1222.84 | 01-DEC-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1170.65 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2650.28 | 1336.61 | 3648.94 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 35.80 | 28.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 622.89 | 14-JAN-11:33 | 220.32 | 127.18 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.44 |
February | 699.10 | 23-FEB-11:33 | 146.88 | 127.18 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 | 0.00 |
March | 803.70 | 12-MAR-10:33 | 220.32 | 152.61 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 0.00 |
April | 951.33 | 28-APR-21:00 | 195.84 | 135.66 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 13.93 | 0.00 |
May | 1145.53 | 04-MAY-20:00 | 171.36 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 16.06 | 0.00 |
June | 1268.62 | 12-JUN-20:10 | 195.84 | 135.66 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 20.30 | 0.00 |
July | 1210.83 | 07-JUL-20:10 | 195.84 | 135.66 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 16.45 | 0.00 |
August | 1104.46 | 08-AUG-20:10 | 195.84 | 135.66 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 13.12 | 0.00 |
September | 962.60 | 01-SEP-21:00 | 195.84 | 135.66 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 9.92 | 0.00 |
October | 870.48 | 01-OCT-10:33 | 220.32 | 152.61 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 11.23 | 0.00 |
November | 753.90 | 11-NOV-11:33 | 220.32 | 152.61 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 5.99 | 0.00 |
December | 651.09 | 03-DEC-11:33 | 220.32 | 152.61 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 622.89 | 146.88 | 127.18 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1268.62 | 220.32 | 152.61 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 20.30 | 3.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37470.78 | 26-JAN-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 33.78 |
February | 37999.47 | 22-FEB-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 10.42 |
March | 38697.86 | 28-MAR-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 16.71 | 0.00 |
April | 39330.45 | 28-APR-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 37.83 | 0.00 |
May | 39708.50 | 04-MAY-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 38.00 | 0.00 |
June | 39726.95 | 12-JUN-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 48.89 | 0.00 |
July | 39625.91 | 07-JUL-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 39.47 | 0.00 |
August | 39233.13 | 07-AUG-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 34.71 | 0.00 |
September | 38944.47 | 22-SEP-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 22.17 | 0.00 |
October | 38827.59 | 02-OCT-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 11.93 | 0.00 |
November | 38137.72 | 09-NOV-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 12.61 |
December | 37512.46 | 28-DEC-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 18.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37470.78 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39726.95 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 48.89 | 33.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9369.13 | 08-JAN-13:00 | 5122.80 | 115.39 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.12 |
February | 10746.92 | 20-FEB-13:00 | 5122.80 | 115.39 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 11.87 | 0.00 |
March | 11741.16 | 13-MAR-15:03 | 51228.00 | 576.93 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 53.96 | 0.00 |
April | 13003.30 | 27-APR-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 65.62 | 0.00 |
May | 13473.03 | 05-MAY-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 76.19 | 0.00 |
June | 13702.77 | 12-JUN-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 76.97 | 0.00 |
July | 13270.75 | 07-JUL-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 63.63 | 0.00 |
August | 12850.19 | 07-AUG-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 56.31 | 0.00 |
September | 12440.67 | 26-SEP-15:03 | 51228.00 | 576.93 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 72.47 | 0.00 |
October | 13118.75 | 02-OCT-15:03 | 51228.00 | 576.93 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 74.51 | 0.00 |
November | 12444.80 | 04-NOV-13:10 | 10245.60 | 192.31 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 37.87 | 0.00 |
December | 11047.40 | 02-DEC-13:20 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9369.13 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13702.77 | 51228.00 | 1048.97 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 76.97 | 25.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 32697.09 | 13-JAN-22:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.31 |
February | 36499.34 | 22-FEB-22:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.02 |
March | 40586.88 | 29-MAR-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 42.71 | 0.00 |
April | 45007.68 | 27-APR-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 187.46 | 0.00 |
May | 46979.46 | 05-MAY-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 217.66 | 0.00 |
June | 48358.93 | 12-JUN-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 219.89 | 0.00 |
July | 47384.30 | 07-JUL-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 181.77 | 0.00 |
August | 45944.18 | 08-AUG-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 147.09 | 0.00 |
September | 44327.32 | 22-SEP-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 95.49 | 0.00 |
October | 43653.00 | 03-OCT-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 69.53 | 0.00 |
November | 38892.31 | 09-NOV-22:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.00 |
December | 34215.78 | 28-DEC-22:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 32697.09 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48358.93 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 219.89 | 118.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2866.14 | 12-JAN-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | 0.00 |
February | 2982.88 | 24-FEB-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 | 0.00 |
March | 2943.28 | 04-MAR-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 6.47 | 0.00 |
April | 3032.95 | 28-APR-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 23.79 | 0.00 |
May | 3059.12 | 01-MAY-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 26.90 | 0.00 |
June | 3060.74 | 05-JUN-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 28.04 | 0.00 |
July | 3016.97 | 02-JUL-18:02 | 702.00 | 712.44 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 0.00 |
August | 2981.47 | 15-AUG-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 0.00 |
September | 2973.79 | 03-SEP-15:02 | 324.00 | 235.11 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 9.31 | 0.00 |
October | 2979.26 | 06-OCT-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 8.97 | 0.00 |
November | 2914.28 | 04-NOV-18:02 | 702.00 | 712.44 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 4.81 | 0.00 |
December | 2822.51 | 28-DEC-16:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2822.51 | 324.00 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | 0.00 | |
Maximum of Months | 3060.74 | 831.60 | 712.44 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 28.04 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2820.14 | 08-JAN-16:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 |
February | 2966.61 | 21-FEB-16:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 | 0.00 |
March | 3023.96 | 22-MAR-15:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 6.24 | 0.00 |
April | 3058.06 | 30-APR-07:51 | 667.80 | 465.41 | 1659.22 | 0.00 | 0.00 | 0.00 | 0.00 | 1.76 | 0.00 |
May | 3070.20 | 01-MAY-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 26.92 | 0.00 |
June | 3069.08 | 05-JUN-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 28.03 | 0.00 |
July | 3076.06 | 04-JUL-18:02 | 702.00 | 712.36 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 0.00 |
August | 3000.21 | 15-AUG-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 16.02 | 0.00 |
September | 2963.03 | 29-SEP-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 12.32 | 0.00 |
October | 2994.19 | 08-OCT-21:51 | 1108.80 | 807.35 | 737.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 |
November | 2989.90 | 05-NOV-15:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 0.00 |
December | 2807.28 | 02-DEC-16:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2807.28 | 378.00 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3076.06 | 1108.80 | 807.35 | 1659.22 | 0.00 | 0.00 | 0.00 | 0.00 | 28.03 | 1.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 426.64 | 08-JAN-14:20 | 0.00 | 49.25 | 149.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.97 |
February | 477.31 | 20-FEB-14:05 | 0.00 | 49.25 | 149.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
March | 499.06 | 13-MAR-13:40 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 2.48 | 0.00 |
April | 510.67 | 15-APR-14:00 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 5.87 | 0.00 |
May | 507.26 | 04-MAY-17:13 | 0.00 | 150.00 | 394.73 | 0.00 | 0.00 | 0.00 | 0.00 | 6.44 | 0.00 |
June | 490.42 | 12-JUN-17:13 | 0.00 | 150.00 | 394.73 | 0.00 | 0.00 | 0.00 | 0.00 | 7.12 | 0.00 |
July | 461.69 | 04-JUL-20:10 | 0.00 | 74.62 | 180.59 | 0.00 | 0.00 | 0.00 | 0.00 | 5.68 | 0.00 |
August | 431.94 | 07-AUG-17:20 | 0.00 | 150.00 | 394.73 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 | 0.00 |
September | 536.57 | 26-SEP-13:40 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 3.85 | 0.00 |
October | 599.09 | 02-OCT-13:30 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 | 0.00 |
November | 578.07 | 04-NOV-13:30 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 1.58 | 0.00 |
December | 500.93 | 02-DEC-13:30 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 426.64 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 599.09 | 0.00 | 150.00 | 394.73 | 0.00 | 0.00 | 0.00 | 0.00 | 7.12 | 1.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1055.44 | 14-JAN-16:01 | 378.00 | 172.43 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
February | 1159.35 | 23-FEB-16:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 | 0.00 |
March | 1177.69 | 26-MAR-15:01 | 378.00 | 172.43 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 3.40 | 0.00 |
April | 1183.56 | 18-APR-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 6.47 | 0.00 |
May | 1186.04 | 11-MAY-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 6.41 | 0.00 |
June | 1185.95 | 28-JUN-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 5.40 | 0.00 |
July | 1187.50 | 20-JUL-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 5.14 | 0.00 |
August | 1187.93 | 05-AUG-15:02 | 324.00 | 147.80 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 5.82 | 0.00 |
September | 1179.03 | 11-SEP-08:61 | 252.00 | 229.90 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 2.30 | 0.00 |
October | 1172.03 | 14-OCT-18:02 | 702.00 | 447.86 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 | 0.00 |
November | 1176.12 | 01-NOV-15:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 2.53 | 0.00 |
December | 1105.30 | 28-DEC-16:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1055.44 | 252.00 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1187.93 | 831.60 | 447.86 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 6.47 | 0.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2605.51 | 12-JAN-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 | 0.00 |
February | 2704.50 | 24-FEB-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 5.72 | 0.00 |
March | 2709.69 | 22-MAR-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 6.20 | 0.00 |
April | 2726.38 | 27-APR-08:62 | 216.00 | 313.47 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 12.53 | 0.00 |
May | 2785.48 | 04-MAY-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 26.99 | 0.00 |
June | 2762.44 | 12-JUN-18:02 | 693.00 | 528.40 | 645.33 | 0.00 | 0.00 | 0.00 | 0.00 | 29.75 | 0.00 |
July | 2749.01 | 07-JUL-15:02 | 486.00 | 166.24 | 342.42 | 0.00 | 0.00 | 0.00 | 0.00 | 27.11 | 0.00 |
August | 2732.95 | 22-AUG-15:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 10.98 | 0.00 |
September | 2734.19 | 17-SEP-08:62 | 324.00 | 398.97 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 8.97 | 0.00 |
October | 2736.09 | 04-OCT-08:61 | 252.00 | 365.72 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 7.71 | 0.00 |
November | 2641.82 | 15-NOV-16:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 0.00 |
December | 2602.79 | 03-DEC-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2602.79 | 216.00 | 166.24 | 342.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2785.48 | 831.60 | 634.08 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 29.75 | 1.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2489.99 | 12-JAN-16:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1.30 | 0.00 |
February | 2706.91 | 22-FEB-09:51 | 288.00 | 417.92 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.96 |
March | 2935.74 | 28-MAR-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.80 | 0.00 |
April | 3107.94 | 06-APR-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 | 0.00 |
May | 2726.64 | 24-MAY-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 14.34 | 0.00 |
June | 2761.06 | 12-JUN-18:02 | 693.00 | 528.34 | 645.25 | 0.00 | 0.00 | 0.00 | 0.00 | 29.73 | 0.00 |
July | 2748.85 | 07-JUL-15:02 | 486.00 | 166.22 | 342.38 | 0.00 | 0.00 | 0.00 | 0.00 | 27.11 | 0.00 |
August | 2741.08 | 15-AUG-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 15.88 | 0.00 |
September | 2742.00 | 01-SEP-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 16.15 | 0.00 |
October | 2948.25 | 15-OCT-08:51 | 540.00 | 664.87 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2.48 | 0.00 |
November | 2710.49 | 01-NOV-15:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 9.32 | 0.00 |
December | 2606.93 | 02-DEC-16:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2489.99 | 288.00 | 166.22 | 342.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3107.94 | 831.60 | 664.87 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 29.73 | 4.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1606.80 | 14-JAN-11:33 | 2263.36 | 966.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.45 |
February | 1876.03 | 23-FEB-11:33 | 1508.90 | 966.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 | 0.00 |
March | 2162.29 | 12-MAR-10:33 | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.29 | 0.00 |
April | 2724.70 | 28-APR-18:15 | 3520.78 | 2062.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.06 | 0.00 |
May | 3134.92 | 05-MAY-18:17 | 5281.16 | 3093.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.22 | 0.00 |
June | 3222.54 | 12-JUN-18:13 | 5281.16 | 3093.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 | 0.00 |
July | 2956.50 | 07-JUL-18:15 | 3520.78 | 2062.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.12 | 0.00 |
August | 2690.41 | 09-AUG-18:05 | 10562.33 | 6186.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.99 | 0.00 |
September | 2422.87 | 26-SEP-18:10 | 10562.33 | 6186.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.81 | 0.00 |
October | 2320.18 | 01-OCT-10:33 | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.53 | 0.00 |
November | 2050.44 | 11-NOV-11:33 | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.22 | 0.00 |
December | 1782.08 | 03-DEC-11:33 | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1606.80 | 1508.90 | 966.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3222.54 | 10562.33 | 6186.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 | 4.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3060.25 | 12-JAN-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 | 0.00 |
February | 3148.03 | 24-FEB-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 5.76 | 0.00 |
March | 3148.45 | 10-MAR-19:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 | 0.00 |
April | 3269.72 | 28-APR-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 23.71 | 0.00 |
May | 3296.72 | 01-MAY-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 26.80 | 0.00 |
June | 3295.14 | 05-JUN-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 27.94 | 0.00 |
July | 3297.85 | 07-JUL-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 23.81 | 0.00 |
August | 3195.75 | 21-AUG-15:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 10.24 | 0.00 |
September | 3184.34 | 11-SEP-15:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 13.53 | 0.00 |
October | 3203.08 | 06-OCT-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 8.97 | 0.00 |
November | 3112.21 | 03-NOV-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 3.86 | 0.00 |
December | 3060.69 | 27-DEC-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3060.25 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3297.85 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 27.94 | 1.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3020.85 | 25-JAN-16:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 |
February | 3188.67 | 19-FEB-16:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 4.51 | 0.00 |
March | 3206.96 | 04-MAR-16:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 6.49 | 0.00 |
April | 3277.24 | 28-APR-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 23.74 | 0.00 |
May | 3312.24 | 01-MAY-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 0.00 |
June | 3306.04 | 05-JUN-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 27.93 | 0.00 |
July | 3303.44 | 07-JUL-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 23.80 | 0.00 |
August | 3208.09 | 18-AUG-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 13.21 | 0.00 |
September | 3191.60 | 11-SEP-15:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 13.56 | 0.00 |
October | 3189.83 | 16-OCT-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 | 0.00 |
November | 3186.89 | 17-NOV-16:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 | 0.00 |
December | 3060.22 | 24-DEC-16:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3020.85 | 378.00 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3312.24 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 27.93 | 0.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1618.49 | 14-JAN-16:01 | 378.00 | 172.43 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 |
February | 1638.98 | 25-FEB-16:01 | 378.00 | 172.43 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 |
March | 1739.42 | 29-MAR-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 8.28 | 0.00 |
April | 1752.23 | 01-APR-15:02 | 324.00 | 147.80 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 9.52 | 0.00 |
May | 1736.10 | 07-MAY-15:02 | 324.00 | 147.80 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 15.29 | 0.00 |
June | 1743.20 | 11-JUN-15:02 | 270.00 | 123.17 | 374.19 | 0.00 | 0.00 | 0.00 | 0.00 | 15.93 | 0.00 |
July | 1725.75 | 08-JUL-08:62 | 324.00 | 250.80 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 9.08 | 0.00 |
August | 1719.98 | 10-AUG-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 | 0.00 |
September | 1771.12 | 20-SEP-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 8.61 | 0.00 |
October | 1749.23 | 28-OCT-15:01 | 378.00 | 172.43 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 5.14 | 0.00 |
November | 1763.76 | 09-NOV-16:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 4.37 | 0.00 |
December | 1618.87 | 26-DEC-16:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1618.49 | 270.00 | 123.17 | 374.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1771.12 | 680.40 | 250.80 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 15.93 | 1.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18717.36 | 13-JAN-22:55 | 107955.07 | 7368.33 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 |
February | 20183.57 | 22-FEB-22:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.14 |
March | 22368.68 | 29-MAR-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 9.19 | 0.00 |
April | 24347.51 | 27-APR-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 41.69 | 0.00 |
May | 24898.50 | 05-MAY-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 48.47 | 0.00 |
June | 25277.13 | 12-JUN-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 48.97 | 0.00 |
July | 24910.21 | 03-JUL-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 43.15 | 0.00 |
August | 24205.19 | 07-AUG-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 35.71 | 0.00 |
September | 23464.98 | 01-SEP-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 25.89 | 0.00 |
October | 22497.25 | 04-OCT-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 3.42 | 0.00 |
November | 20398.66 | 08-NOV-22:53 | 188921.38 | 12894.57 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.54 |
December | 18963.62 | 28-DEC-22:54 | 134943.84 | 9210.41 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18717.36 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25277.13 | 188921.38 | 12894.57 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 48.97 | 28.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20561.82 | 13-JAN-22:55 | 107955.07 | 7368.33 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 |
February | 21782.46 | 22-FEB-22:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.14 |
March | 23658.36 | 29-MAR-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 9.19 | 0.00 |
April | 25543.45 | 27-APR-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 41.69 | 0.00 |
May | 26081.86 | 05-MAY-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 48.47 | 0.00 |
June | 26465.46 | 12-JUN-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 48.97 | 0.00 |
July | 26089.05 | 03-JUL-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 43.15 | 0.00 |
August | 25382.42 | 07-AUG-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 35.71 | 0.00 |
September | 24647.92 | 01-SEP-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 25.89 | 0.00 |
October | 23710.52 | 04-OCT-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 3.41 | 0.00 |
November | 21825.85 | 08-NOV-22:53 | 188921.38 | 12894.57 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.54 |
December | 20746.34 | 28-DEC-22:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20561.82 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26465.46 | 188921.38 | 12894.57 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 48.97 | 27.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26257.10 | 26-JAN-11:45 | 1067.42 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 10.89 |
February | 27484.90 | 20-FEB-11:45 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.20 | 0.00 |
March | 29147.93 | 12-MAR-10:45 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 13.31 | 0.00 |
April | 30522.29 | 16-APR-10:33 | 2401.70 | 1090.83 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 42.06 | 0.00 |
May | 30684.37 | 04-MAY-10:40 | 1601.14 | 909.03 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 54.40 | 0.00 |
June | 30585.39 | 11-JUN-10:37 | 2401.70 | 1090.83 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 47.79 | 0.00 |
July | 30312.19 | 04-JUL-10:33 | 2401.70 | 1090.83 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 40.96 | 0.00 |
August | 29519.46 | 06-AUG-10:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 32.10 | 0.00 |
September | 29394.80 | 24-SEP-10:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 29.05 | 0.00 |
October | 29562.68 | 01-OCT-10:33 | 2401.70 | 1090.83 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 25.25 | 0.00 |
November | 28017.92 | 04-NOV-10:45 | 1601.14 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 8.35 | 0.00 |
December | 26866.49 | 03-DEC-11:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 6.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26257.10 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30684.37 | 2401.70 | 1090.83 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 54.40 | 10.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3816.78 | 26-JAN-11:33 | 1596.96 | 1023.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.19 |
February | 4546.42 | 23-FEB-11:33 | 1596.96 | 1023.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 0.00 |
March | 5803.62 | 13-MAR-15:03 | 7984.80 | 2046.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.96 | 0.00 |
April | 7919.40 | 29-APR-13:30 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.63 | 0.00 |
May | 9099.33 | 04-MAY-15:04 | 6654.00 | 1705.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.96 | 0.00 |
June | 9314.64 | 08-JUN-15:25 | 2661.60 | 682.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.76 | 0.00 |
July | 8272.14 | 07-JUL-15:25 | 2661.60 | 682.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.46 | 0.00 |
August | 7471.50 | 08-AUG-15:03 | 7984.80 | 2046.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.05 | 0.00 |
September | 7000.60 | 26-SEP-15:03 | 7984.80 | 2046.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.37 | 0.00 |
October | 6980.88 | 02-OCT-14:10 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.82 | 0.00 |
November | 4943.66 | 09-NOV-11:33 | 1596.96 | 1023.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.25 | 0.00 |
December | 4136.26 | 03-DEC-11:33 | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3816.78 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9314.64 | 7984.80 | 2046.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.76 | 3.19 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.436590E+12 | 304313.07 | 13-JAN-20:19 | 0.246748E+12 | 175605.60 | 02-JAN-19:19 |
February | 0.437547E+12 | 333912.82 | 22-FEB-20:19 | 0.209557E+12 | 167167.56 | 01-FEB-18:00 |
March | 0.571888E+12 | 398843.05 | 10-MAR-20:19 | 0.218554E+12 | 155170.14 | 01-MAR-18:19 |
April | 0.664209E+12 | 452071.09 | 26-APR-19:10 | 0.198631E+12 | 139366.99 | 01-APR-17:40 |
May | 0.784586E+12 | 494853.18 | 17-MAY-19:10 | 0.194867E+12 | 123105.18 | 01-MAY-17:30 |
June | 0.808977E+12 | 530068.81 | 09-JUN-19:19 | 0.188413E+12 | 120157.22 | 01-JUN-17:10 |
July | 0.848193E+12 | 520808.34 | 03-JUL-19:19 | 0.194502E+12 | 120157.22 | 01-JUL-17:10 |
August | 0.829776E+12 | 506808.89 | 07-AUG-19:10 | 0.194727E+12 | 120157.22 | 01-AUG-17:10 |
September | 0.755505E+12 | 505054.28 | 17-SEP-19:49 | 0.188340E+12 | 120157.22 | 01-SEP-17:10 |
October | 0.653078E+12 | 435062.85 | 03-OCT-19:10 | 0.205663E+12 | 139591.60 | 31-OCT-17:19 |
November | 0.518058E+12 | 354561.64 | 08-NOV-20:10 | 0.213365E+12 | 157555.89 | 30-NOV-18:00 |
December | 0.452024E+12 | 323103.57 | 28-DEC-20:19 | 0.237903E+12 | 171645.36 | 30-DEC-18:30 |
Annual Sum or Average | 0.776043E+13 | 0.249127E+13 | ||||
Minimum of Months | 0.436590E+12 | 304313.07 | 0.188340E+12 | 120157.22 | ||
Maximum of Months | 0.848193E+12 | 530068.81 | 0.246748E+12 | 175605.60 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.517514E+11 | 0.167645E+11 | 0.146779E+12 | 0.544822E+11 | 0.418160E+11 | 0.122332E+11 | 0.00 | 0.429743E+11 | 0.00 | 0.00 | 0.247278E+11 | 0.413272E+11 | 0.00 |
February | 0.466122E+11 | 0.145075E+11 | 0.132565E+12 | 0.492097E+11 | 0.396304E+11 | 0.118168E+11 | 0.00 | 0.814538E+11 | 0.00 | 0.00 | 0.218513E+11 | 0.365174E+11 | 0.00 |
March | 0.513508E+11 | 0.150335E+11 | 0.146789E+12 | 0.544839E+11 | 0.489953E+11 | 0.135749E+11 | 0.00 | 0.174499E+12 | 0.00 | 0.00 | 0.239780E+11 | 0.394194E+11 | 0.00 |
April | 0.494451E+11 | 0.135421E+11 | 0.142011E+12 | 0.527242E+11 | 0.542419E+11 | 0.138103E+11 | 0.00 | 0.272757E+12 | 0.00 | 0.00 | 0.247114E+11 | 0.373222E+11 | 0.00 |
May | 0.509798E+11 | 0.131093E+11 | 0.146789E+12 | 0.544827E+11 | 0.611593E+11 | 0.149700E+11 | 0.00 | 0.375761E+12 | 0.00 | 0.00 | 0.257713E+11 | 0.377824E+11 | 0.00 |
June | 0.493200E+11 | 0.122105E+11 | 0.142058E+12 | 0.527259E+11 | 0.600773E+11 | 0.150558E+11 | 0.00 | 0.413540E+12 | 0.00 | 0.00 | 0.249345E+11 | 0.353923E+11 | 0.00 |
July | 0.510454E+11 | 0.128763E+11 | 0.146742E+12 | 0.544809E+11 | 0.615370E+11 | 0.161017E+11 | 0.00 | 0.439903E+12 | 0.00 | 0.00 | 0.257658E+11 | 0.359738E+11 | 0.00 |
August | 0.512496E+11 | 0.135887E+11 | 0.146800E+12 | 0.544839E+11 | 0.607114E+11 | 0.161080E+11 | 0.00 | 0.420975E+12 | 0.00 | 0.00 | 0.257686E+11 | 0.363067E+11 | 0.00 |
September | 0.497285E+11 | 0.141147E+11 | 0.142022E+12 | 0.527244E+11 | 0.566442E+11 | 0.149280E+11 | 0.00 | 0.360483E+12 | 0.00 | 0.00 | 0.249400E+11 | 0.362577E+11 | 0.00 |
October | 0.515836E+11 | 0.156327E+11 | 0.146768E+12 | 0.544820E+11 | 0.553866E+11 | 0.140782E+11 | 0.00 | 0.247843E+12 | 0.00 | 0.00 | 0.247039E+11 | 0.388208E+11 | 0.00 |
November | 0.500073E+11 | 0.159989E+11 | 0.142074E+12 | 0.527252E+11 | 0.475642E+11 | 0.129207E+11 | 0.00 | 0.131408E+12 | 0.00 | 0.00 | 0.231203E+11 | 0.386075E+11 | 0.00 |
December | 0.517058E+11 | 0.170774E+11 | 0.146742E+12 | 0.544813E+11 | 0.434174E+11 | 0.127261E+11 | 0.00 | 0.562826E+11 | 0.00 | 0.00 | 0.247223E+11 | 0.411351E+11 | 0.00 |
Annual Sum or Average | 0.604780E+12 | 0.174456E+12 | 0.172814E+13 | 0.641487E+12 | 0.631181E+12 | 0.168324E+12 | 0.00 | 0.301788E+13 | 0.00 | 0.00 | 0.294995E+12 | 0.454863E+12 | 0.00 |
Minimum of Months | 0.466122E+11 | 0.122105E+11 | 0.132565E+12 | 0.492097E+11 | 0.396304E+11 | 0.118168E+11 | 0.00 | 0.429743E+11 | 0.00 | 0.00 | 0.218513E+11 | 0.353923E+11 | 0.00 |
Maximum of Months | 0.517514E+11 | 0.170774E+11 | 0.146800E+12 | 0.544839E+11 | 0.615370E+11 | 0.161080E+11 | 0.00 | 0.439903E+12 | 0.00 | 0.00 | 0.257713E+11 | 0.413272E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.109966E+11 | 0.00 | 0.838333E+11 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.244779E+10 | 0.00 | 0.699049E+11 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.181642E+09 | 0.00 | 0.663488E+11 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 89804197.01 | 0.00 | 0.515855E+11 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 59054582.72 | 0.00 | 0.428297E+11 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 62943918.44 | 0.00 | 0.412359E+11 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 71277906.15 | 0.00 | 0.426104E+11 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 77409732.68 | 0.00 | 0.426104E+11 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.133573E+09 | 0.00 | 0.412359E+11 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.156395E+09 | 0.00 | 0.536038E+11 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.364397E+09 | 0.00 | 0.659093E+11 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.570676E+10 | 0.00 | 0.803758E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.203476E+11 | 0.00 | 0.682084E+12 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 59054582.72 | 0.00 | 0.412359E+11 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.109966E+11 | 0.00 | 0.838333E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 50471.22 | 02-JAN-20:10 | 11096.45 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 39155.93 | 02-JAN-07:19 | 27979.40 | 13-JAN-22:00 | 5296.34 | 12-JAN-16:10 | 0.00 | 01-JAN-00:10 |
February | 50471.22 | 01-FEB-20:10 | 11096.45 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 39155.93 | 01-FEB-07:19 | 30713.21 | 22-FEB-22:00 | 5568.85 | 20-FEB-16:30 | 0.00 | 01-FEB-00:10 |
March | 50471.22 | 01-MAR-20:10 | 11096.45 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 39155.93 | 13-MAR-06:19 | 36087.03 | 29-MAR-21:10 | 5815.10 | 10-MAR-20:30 | 0.00 | 01-MAR-00:10 |
April | 50471.22 | 03-APR-19:10 | 11096.45 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 39155.93 | 03-APR-06:19 | 42718.79 | 28-APR-21:19 | 6624.80 | 27-APR-19:10 | 0.00 | 01-APR-00:10 |
May | 50471.22 | 01-MAY-19:10 | 11096.45 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 39155.53 | 24-MAY-06:19 | 44598.36 | 04-MAY-21:19 | 7304.48 | 17-MAY-18:10 | 0.00 | 01-MAY-00:10 |
June | 50471.22 | 01-JUN-19:10 | 11096.45 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 39155.54 | 27-JUN-06:19 | 45299.12 | 12-JUN-21:10 | 7977.65 | 22-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 50471.22 | 03-JUL-19:19 | 11096.45 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 39155.62 | 25-JUL-06:19 | 47105.83 | 07-JUL-21:19 | 8180.90 | 01-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 50471.22 | 01-AUG-19:10 | 11096.45 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 39155.90 | 30-AUG-06:19 | 47309.53 | 07-AUG-21:19 | 8210.42 | 28-AUG-18:10 | 0.00 | 01-AUG-00:10 |
September | 50471.22 | 01-SEP-19:10 | 11096.45 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 39155.93 | 18-SEP-06:19 | 45704.10 | 22-SEP-21:10 | 7928.11 | 14-SEP-18:19 | 0.00 | 01-SEP-00:10 |
October | 50471.22 | 02-OCT-19:10 | 11096.45 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 39155.93 | 02-OCT-06:19 | 44012.85 | 03-OCT-21:10 | 6484.04 | 12-OCT-19:00 | 0.00 | 01-OCT-00:10 |
November | 50471.22 | 01-NOV-19:10 | 11096.45 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 39155.93 | 01-NOV-06:19 | 34675.69 | 09-NOV-22:00 | 5579.56 | 01-NOV-15:39 | 0.00 | 01-NOV-00:10 |
December | 50471.22 | 01-DEC-20:10 | 11096.45 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 39155.93 | 15-DEC-07:19 | 30292.45 | 28-DEC-22:00 | 5400.81 | 01-DEC-16:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 50471.22 | 11096.45 | 88863.15 | 39155.53 | 27979.40 | 5296.34 | 0.00 | |||||||
Maximum of Months | 50471.22 | 11096.45 | 88863.15 | 39155.93 | 47309.53 | 8210.42 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 78240.41 | 12-JAN-16:10 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 43361.47 | 31-JAN-18:00 | 0.00 |
February | 97116.10 | 22-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:20 | 43985.20 | 28-FEB-21:00 | 0.00 |
March | 148277.56 | 28-MAR-15:20 | 0.00 | 0.00 | 9938.94 | 01-MAR-01:19 | 43504.98 | 30-MAR-20:30 | 0.00 |
April | 194174.05 | 26-APR-18:10 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 42715.44 | 28-APR-20:49 | 0.00 |
May | 245258.10 | 17-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAY-00:10 | 42003.86 | 26-MAY-20:49 | 0.00 |
June | 269604.35 | 10-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-00:10 | 41061.35 | 20-JUN-17:40 | 0.00 |
July | 263513.69 | 01-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUL-00:10 | 40357.81 | 18-JUL-17:40 | 0.00 |
August | 245153.65 | 28-AUG-18:10 | 0.00 | 0.00 | 9938.94 | 01-AUG-00:10 | 40938.49 | 22-AUG-17:40 | 0.00 |
September | 243219.26 | 17-SEP-19:00 | 0.00 | 0.00 | 9938.94 | 01-SEP-00:10 | 41703.56 | 19-SEP-20:30 | 0.00 |
October | 175926.23 | 03-OCT-15:20 | 0.00 | 0.00 | 9938.94 | 01-OCT-00:10 | 43074.63 | 03-OCT-20:30 | 0.00 |
November | 116421.20 | 04-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 01-NOV-09:09 | 44089.72 | 02-NOV-20:30 | 0.00 |
December | 82786.02 | 28-DEC-16:10 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 44136.33 | 05-DEC-18:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 78240.41 | 0.00 | 0.00 | 9938.94 | 40357.81 | 0.00 | |||
Maximum of Months | 269604.35 | 0.00 | 0.00 | 9938.94 | 44136.33 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 304313.07 | 13-JAN-20:19 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 22744.32 | 4934.39 | 0.00 | 45050.19 | 0.00 |
February | 333912.82 | 22-FEB-20:19 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 25107.60 | 5164.55 | 0.00 | 72283.42 | 0.00 |
March | 398843.05 | 10-MAR-20:19 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 30017.11 | 5796.89 | 0.00 | 131420.60 | 0.00 |
April | 452071.09 | 26-APR-19:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 31320.62 | 6342.15 | 0.00 | 182184.97 | 0.00 |
May | 494853.18 | 17-MAY-19:10 | 50471.22 | 87982.85 | 11096.45 | 31572.54 | 32728.93 | 7009.69 | 0.00 | 223552.04 | 0.00 |
June | 530068.81 | 09-JUN-19:19 | 50471.22 | 87982.85 | 11096.45 | 31577.31 | 39567.48 | 7157.67 | 0.00 | 253441.94 | 0.00 |
July | 520808.34 | 03-JUL-19:19 | 50471.22 | 87982.85 | 11096.45 | 31577.09 | 37010.24 | 7625.37 | 0.00 | 247078.05 | 0.00 |
August | 506808.89 | 07-AUG-19:10 | 50471.22 | 87982.85 | 11096.45 | 31572.20 | 35613.97 | 7751.11 | 0.00 | 233269.51 | 0.00 |
September | 505054.28 | 17-SEP-19:49 | 46435.92 | 86521.75 | 11096.45 | 31540.10 | 33078.21 | 7169.32 | 0.00 | 241046.69 | 0.00 |
October | 435062.85 | 03-OCT-19:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 35758.93 | 6251.23 | 0.00 | 161068.23 | 0.00 |
November | 354561.64 | 08-NOV-20:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 27298.91 | 5384.11 | 0.00 | 90235.70 | 0.00 |
December | 323103.57 | 28-DEC-20:19 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 24939.28 | 5051.67 | 0.00 | 61539.35 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 304313.07 | 46435.92 | 86521.75 | 11096.45 | 31540.10 | 22744.32 | 4934.39 | 0.00 | 45050.19 | 0.00 | |
Maximum of Months | 530068.81 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 39567.48 | 7751.11 | 0.00 | 253441.94 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 33021.87 | 02-JAN-09:09 | 0.00 | 69344.90 | 17-JAN-23:00 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 19799.42 | 11-FEB-06:10 | 0.00 | 62919.86 | 01-FEB-19:30 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 4792.05 | 17-MAR-08:00 | 0.00 | 50922.44 | 01-MAR-20:30 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 5175.13 | 13-APR-08:09 | 0.00 | 35129.38 | 01-APR-22:10 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 4306.16 | 24-MAY-08:09 | 0.00 | 18856.89 | 01-MAY-19:19 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 4443.24 | 24-JUN-18:10 | 0.00 | 15908.90 | 01-JUN-00:10 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 4916.54 | 26-JUL-08:09 | 0.00 | 15908.90 | 01-JUL-00:10 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 4327.50 | 20-AUG-08:09 | 0.00 | 15908.90 | 01-AUG-00:10 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 6268.17 | 07-SEP-08:09 | 0.00 | 15908.90 | 01-SEP-00:10 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 5032.21 | 30-OCT-08:00 | 0.00 | 35343.67 | 31-OCT-18:49 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 14951.69 | 26-NOV-00:10 | 0.00 | 53308.02 | 30-NOV-23:10 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 23750.64 | 23-DEC-05:00 | 0.00 | 67461.38 | 31-DEC-23:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 4306.16 | 0.00 | 15908.90 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 33021.87 | 0.00 | 69344.90 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.73 | 1.00 | 21.73 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 21.85 | 7.17 | 21.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 21.90 | 9.00 | 21.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 21.89 | 6.67 | 21.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.83 | 1.67 | 21.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.76 | 0.83 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.79 | 2.50 | 21.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.81 | 3.17 | 21.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 32.00 | 21.85 | 32.00 | 21.85 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 21.90 | 9.00 | 21.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.81 | 4.83 | 21.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 21.89 | 7.83 | 21.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 21.88 | 6.67 | 21.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.82 | 1.67 | 21.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.74 | 0.83 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.69 | 0.83 | 21.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.72 | 0.83 | 21.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 23.50 | 21.84 | 23.50 | 21.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 21.89 | 7.83 | 21.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.77 | 0.33 | 21.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.71 | 3.83 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.72 | 3.50 | 21.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.70 | 1.67 | 21.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.76 | 0.83 | 21.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.17 | 21.72 | 10.17 | 21.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.77 | 3.83 | 21.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.78 | 3.83 | 21.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 21.80 | 7.17 | 21.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.77 | 5.17 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.78 | 2.00 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.71 | 1.17 | 21.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.74 | 1.83 | 21.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.77 | 1.17 | 21.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 22.67 | 21.78 | 22.67 | 21.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 21.80 | 7.17 | 21.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.94 | 2.83 | 21.94 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.96 | 3.83 | 21.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 21.80 | 7.17 | 21.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 21.78 | 5.33 | 21.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.78 | 2.17 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.70 | 0.50 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.88 | 3.67 | 21.88 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.74 | 0.83 | 21.74 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 26.33 | 21.84 | 26.33 | 21.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 21.96 | 7.17 | 21.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.78 | 1.17 | 21.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 21.89 | 7.50 | 21.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 21.92 | 12.83 | 21.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 21.89 | 10.00 | 21.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.80 | 1.83 | 21.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.73 | 1.33 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.76 | 3.00 | 21.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.79 | 3.33 | 21.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 41.00 | 21.87 | 41.00 | 21.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 21.92 | 12.83 | 21.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.75 | 0.17 | 21.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 21.84 | 5.67 | 21.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 21.89 | 11.50 | 21.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 21.88 | 10.00 | 21.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.80 | 1.83 | 21.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.73 | 1.00 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.72 | 1.33 | 21.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.77 | 0.50 | 21.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 32.00 | 21.86 | 32.00 | 21.86 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 21.89 | 11.50 | 21.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.74 | 1.50 | 21.74 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.74 | 2.83 | 21.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.81 | 4.17 | 21.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.80 | 5.17 | 21.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.77 | 4.33 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.79 | 2.17 | 21.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.74 | 2.50 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.79 | 3.17 | 21.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 21.87 | 5.83 | 21.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.75 | 2.50 | 21.75 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.70 | 0.83 | 21.70 |
Annual Sum or Average | 0.00 | 0.00 | 35.17 | 21.79 | 35.17 | 21.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 21.87 | 5.83 | 21.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 273.50 | 23.57 | 56.33 | 23.63 | 0.00 | 23.63 |
February | 602.33 | 23.18 | 2.67 | 23.19 | 2.33 | 23.19 |
March | 744.00 | 22.54 | 0.00 | 22.54 | 0.00 | 22.54 |
April | 720.00 | 22.30 | 0.00 | 22.30 | 0.00 | 22.30 |
May | 744.00 | 22.74 | 5.17 | 22.75 | 5.17 | 22.75 |
June | 290.00 | 23.21 | 294.83 | 23.50 | 36.33 | 23.51 |
July | 7.00 | 23.71 | 691.83 | 23.94 | 5.50 | 23.94 |
August | 0.00 | 0.00 | 744.00 | 23.99 | 0.00 | 23.99 |
September | 0.00 | 0.00 | 720.00 | 24.00 | 0.00 | 24.00 |
October | 0.00 | 0.00 | 717.17 | 23.98 | 0.00 | 23.98 |
November | 0.00 | 0.00 | 421.33 | 23.99 | 0.00 | 23.99 |
December | 98.83 | 23.83 | 104.00 | 23.92 | 0.00 | 23.92 |
Annual Sum or Average | 3479.67 | 22.82 | 3757.33 | 23.41 | 49.33 | 23.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.30 | 0.00 | 22.30 |
Maximum of Months | 744.00 | 23.83 | 744.00 | 24.00 | 36.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 668.00 | 21.57 | 16.83 | 21.62 | 0.00 | 21.62 |
February | 520.17 | 21.86 | 83.33 | 22.13 | 0.00 | 22.13 |
March | 361.00 | 22.28 | 279.50 | 22.95 | 0.00 | 22.95 |
April | 84.67 | 22.58 | 556.00 | 23.68 | 0.00 | 23.68 |
May | 4.17 | 22.72 | 722.83 | 23.87 | 0.00 | 23.87 |
June | 10.17 | 22.60 | 668.17 | 23.87 | 0.00 | 23.87 |
July | 4.83 | 22.72 | 723.67 | 23.83 | 0.00 | 23.83 |
August | 0.00 | 0.00 | 698.50 | 23.79 | 0.00 | 23.79 |
September | 83.67 | 22.55 | 553.83 | 23.62 | 0.00 | 23.62 |
October | 143.17 | 22.54 | 513.00 | 23.55 | 0.00 | 23.55 |
November | 363.00 | 22.23 | 270.67 | 22.93 | 0.00 | 22.93 |
December | 631.17 | 21.71 | 51.83 | 21.88 | 0.00 | 21.88 |
Annual Sum or Average | 2874.00 | 21.94 | 5138.17 | 23.16 | 0.00 | 23.16 |
Minimum of Months | 0.00 | 0.00 | 16.83 | 21.62 | 0.00 | 21.62 |
Maximum of Months | 668.00 | 22.72 | 723.67 | 23.87 | 0.00 | 23.87 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 718.67 | 22.59 | 1.67 | 22.59 | 0.00 | 22.59 |
February | 525.00 | 22.80 | 54.00 | 22.90 | 6.83 | 22.91 |
March | 342.50 | 23.12 | 259.67 | 23.44 | 47.17 | 23.47 |
April | 88.83 | 23.47 | 498.67 | 23.85 | 37.00 | 23.86 |
May | 42.50 | 23.96 | 678.50 | 23.91 | 42.17 | 23.91 |
June | 65.00 | 23.96 | 662.50 | 23.91 | 65.00 | 23.92 |
July | 96.17 | 23.99 | 706.00 | 23.90 | 96.17 | 23.91 |
August | 109.67 | 23.99 | 703.50 | 23.89 | 109.67 | 23.90 |
September | 137.17 | 23.72 | 619.83 | 23.85 | 110.83 | 23.85 |
October | 108.67 | 23.79 | 565.67 | 23.86 | 93.67 | 23.86 |
November | 281.00 | 23.15 | 221.17 | 23.47 | 17.67 | 23.48 |
December | 666.50 | 22.76 | 8.50 | 22.78 | 0.00 | 22.78 |
Annual Sum or Average | 3181.67 | 23.02 | 4979.67 | 23.55 | 626.17 | 23.58 |
Minimum of Months | 42.50 | 22.59 | 1.67 | 22.59 | 0.00 | 22.59 |
Maximum of Months | 718.67 | 23.99 | 706.00 | 23.91 | 110.83 | 23.92 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
February | 672.00 | 22.08 | 0.00 | 22.08 | 0.00 | 22.08 |
March | 704.00 | 22.73 | 0.00 | 22.73 | 0.00 | 22.73 |
April | 295.50 | 23.19 | 170.17 | 23.46 | 0.00 | 23.46 |
May | 3.83 | 23.27 | 592.67 | 23.94 | 0.00 | 23.94 |
June | 0.50 | 23.26 | 611.00 | 23.95 | 0.00 | 23.95 |
July | 0.00 | 0.00 | 701.67 | 23.95 | 0.00 | 23.95 |
August | 0.00 | 0.00 | 706.00 | 23.93 | 0.00 | 23.93 |
September | 52.83 | 23.18 | 478.33 | 23.83 | 0.00 | 23.83 |
October | 310.17 | 23.14 | 132.17 | 23.36 | 0.00 | 23.36 |
November | 716.33 | 22.68 | 0.00 | 22.68 | 0.00 | 22.68 |
December | 744.00 | 21.88 | 0.00 | 21.88 | 0.00 | 21.88 |
Annual Sum or Average | 4243.17 | 22.34 | 3392.00 | 23.05 | 0.00 | 23.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.59 | 0.00 | 21.59 |
Maximum of Months | 744.00 | 23.27 | 706.00 | 23.95 | 0.00 | 23.95 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.47 | 0.00 | 21.47 | 0.00 | 21.47 |
February | 672.00 | 21.96 | 0.00 | 21.96 | 0.00 | 21.96 |
March | 741.33 | 22.65 | 0.00 | 22.65 | 0.00 | 22.65 |
April | 390.33 | 23.18 | 127.67 | 23.35 | 0.00 | 23.35 |
May | 3.83 | 23.28 | 546.00 | 23.94 | 0.00 | 23.94 |
June | 0.00 | 0.00 | 579.50 | 23.95 | 0.00 | 23.95 |
July | 0.00 | 0.00 | 673.83 | 23.94 | 0.00 | 23.94 |
August | 0.00 | 0.00 | 679.67 | 23.91 | 0.00 | 23.91 |
September | 94.33 | 23.16 | 403.50 | 23.73 | 0.00 | 23.73 |
October | 440.00 | 23.13 | 43.17 | 23.19 | 0.00 | 23.19 |
November | 720.00 | 22.56 | 0.00 | 22.56 | 0.00 | 22.56 |
December | 744.00 | 21.75 | 0.00 | 21.75 | 0.00 | 21.75 |
Annual Sum or Average | 4549.83 | 22.30 | 3053.33 | 22.95 | 0.00 | 22.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.47 | 0.00 | 21.47 |
Maximum of Months | 744.00 | 23.28 | 679.67 | 23.95 | 0.00 | 23.95 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 275.50 | 23.37 | 640.50 | 23.29 | 217.67 | 23.43 |
February | 266.83 | 23.67 | 604.00 | 23.37 | 237.50 | 23.50 |
March | 305.67 | 23.90 | 707.83 | 23.37 | 296.83 | 23.51 |
April | 319.17 | 23.95 | 713.83 | 23.36 | 319.17 | 23.50 |
May | 350.33 | 23.92 | 744.00 | 23.37 | 350.33 | 23.50 |
June | 337.67 | 23.92 | 720.00 | 23.36 | 337.67 | 23.50 |
July | 357.17 | 23.92 | 744.00 | 23.39 | 357.17 | 23.52 |
August | 347.00 | 23.93 | 744.00 | 23.38 | 347.00 | 23.51 |
September | 326.83 | 23.94 | 719.33 | 23.37 | 326.83 | 23.51 |
October | 319.83 | 23.96 | 741.33 | 23.35 | 319.83 | 23.49 |
November | 291.50 | 23.89 | 673.83 | 23.41 | 282.00 | 23.54 |
December | 276.33 | 23.43 | 646.50 | 23.32 | 223.33 | 23.45 |
Annual Sum or Average | 3773.83 | 23.83 | 8399.17 | 23.36 | 3615.33 | 23.50 |
Minimum of Months | 266.83 | 23.37 | 604.00 | 23.29 | 217.67 | 23.43 |
Maximum of Months | 357.17 | 23.96 | 744.00 | 23.41 | 357.17 | 23.54 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 450.67 | 22.61 | 159.33 | 22.92 | 19.17 | 22.93 |
February | 256.67 | 22.88 | 361.67 | 23.41 | 63.33 | 23.44 |
March | 239.83 | 23.52 | 605.50 | 23.75 | 170.33 | 23.78 |
April | 216.83 | 23.89 | 695.17 | 23.86 | 210.17 | 23.88 |
May | 291.00 | 23.97 | 743.33 | 23.89 | 291.00 | 23.91 |
June | 293.67 | 23.95 | 712.17 | 23.88 | 291.50 | 23.90 |
July | 330.17 | 23.95 | 739.33 | 23.87 | 327.50 | 23.89 |
August | 328.17 | 23.95 | 738.67 | 23.85 | 327.83 | 23.87 |
September | 331.00 | 23.91 | 691.33 | 23.85 | 325.83 | 23.87 |
October | 304.17 | 23.93 | 724.50 | 23.89 | 302.33 | 23.90 |
November | 178.83 | 23.69 | 609.00 | 23.84 | 137.17 | 23.86 |
December | 333.67 | 22.80 | 239.67 | 23.22 | 5.33 | 23.22 |
Annual Sum or Average | 3554.67 | 23.55 | 7019.67 | 23.74 | 2471.50 | 23.78 |
Minimum of Months | 178.83 | 22.61 | 159.33 | 22.92 | 5.33 | 22.93 |
Maximum of Months | 450.67 | 23.97 | 743.33 | 23.89 | 327.83 | 23.91 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 517.50 | 22.89 | 75.50 | 23.02 | 9.17 | 23.02 |
February | 295.67 | 23.04 | 222.17 | 23.41 | 31.00 | 23.44 |
March | 229.67 | 23.55 | 476.33 | 23.76 | 131.83 | 23.79 |
April | 189.50 | 23.93 | 606.33 | 23.87 | 179.83 | 23.89 |
May | 249.50 | 24.00 | 726.67 | 23.88 | 249.50 | 23.90 |
June | 249.50 | 24.00 | 709.83 | 23.89 | 249.50 | 23.91 |
July | 272.67 | 24.00 | 739.00 | 23.89 | 272.67 | 23.91 |
August | 273.83 | 24.00 | 738.83 | 23.88 | 273.83 | 23.90 |
September | 278.17 | 23.99 | 682.67 | 23.90 | 278.17 | 23.92 |
October | 260.00 | 23.99 | 733.50 | 23.89 | 260.00 | 23.91 |
November | 117.00 | 23.80 | 514.00 | 23.85 | 87.83 | 23.87 |
December | 415.00 | 23.02 | 147.50 | 23.27 | 4.83 | 23.27 |
Annual Sum or Average | 3348.00 | 23.58 | 6372.33 | 23.76 | 2028.17 | 23.80 |
Minimum of Months | 117.00 | 22.89 | 75.50 | 23.02 | 4.83 | 23.02 |
Maximum of Months | 517.50 | 24.00 | 739.00 | 23.90 | 278.17 | 23.92 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.50 | 2.33 | 21.50 | 2.33 | 21.50 |
February | 640.67 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
March | 659.00 | 21.50 | 0.17 | 21.50 | 0.00 | 21.50 |
April | 575.67 | 21.37 | 21.33 | 21.44 | 0.00 | 21.44 |
May | 568.00 | 21.30 | 45.50 | 21.45 | 0.00 | 21.45 |
June | 552.33 | 21.31 | 37.83 | 21.44 | 0.00 | 21.44 |
July | 586.17 | 21.33 | 16.33 | 21.38 | 0.00 | 21.38 |
August | 598.67 | 21.36 | 4.50 | 21.38 | 0.00 | 21.38 |
September | 593.17 | 21.41 | 10.33 | 21.44 | 0.00 | 21.44 |
October | 617.00 | 21.41 | 7.83 | 21.44 | 0.00 | 21.44 |
November | 630.00 | 21.47 | 0.00 | 21.47 | 0.00 | 21.47 |
December | 738.33 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
Annual Sum or Average | 7503.00 | 21.43 | 146.17 | 21.47 | 2.33 | 21.47 |
Minimum of Months | 552.33 | 21.30 | 0.00 | 21.38 | 0.00 | 21.38 |
Maximum of Months | 744.00 | 21.59 | 45.50 | 21.59 | 2.33 | 21.59 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.35 | 4.17 | 21.34 | 4.17 | 21.34 |
February | 668.33 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
March | 667.50 | 21.93 | 1.50 | 21.93 | 0.00 | 21.93 |
April | 580.33 | 21.53 | 14.17 | 21.58 | 0.00 | 21.58 |
May | 572.50 | 21.32 | 40.83 | 21.45 | 0.67 | 21.46 |
June | 551.50 | 21.31 | 38.00 | 21.44 | 0.00 | 21.44 |
July | 586.33 | 21.33 | 16.00 | 21.38 | 0.00 | 21.38 |
August | 603.00 | 21.38 | 3.17 | 21.39 | 0.00 | 21.39 |
September | 606.67 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
October | 643.00 | 21.83 | 16.33 | 21.88 | 12.33 | 21.92 |
November | 683.00 | 21.97 | 0.00 | 21.97 | 0.00 | 21.97 |
December | 744.00 | 21.49 | 0.17 | 21.49 | 0.17 | 21.49 |
Annual Sum or Average | 7650.17 | 21.57 | 134.33 | 21.60 | 17.33 | 21.60 |
Minimum of Months | 551.50 | 21.31 | 0.00 | 21.34 | 0.00 | 21.34 |
Maximum of Months | 744.00 | 21.97 | 40.83 | 21.97 | 12.33 | 21.97 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.37 | 0.00 | 21.37 | 0.00 | 21.37 |
February | 672.00 | 21.77 | 0.00 | 21.77 | 0.00 | 21.77 |
March | 744.00 | 21.99 | 0.00 | 21.99 | 0.00 | 21.99 |
April | 719.50 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
May | 743.50 | 21.74 | 0.17 | 21.74 | 0.17 | 21.74 |
June | 720.00 | 21.74 | 0.17 | 21.74 | 0.17 | 21.74 |
July | 744.00 | 21.73 | 0.00 | 21.73 | 0.00 | 21.73 |
August | 744.00 | 21.72 | 0.00 | 21.72 | 0.00 | 21.72 |
September | 720.00 | 21.72 | 0.00 | 21.72 | 0.00 | 21.72 |
October | 743.67 | 21.95 | 9.00 | 21.97 | 9.00 | 21.99 |
November | 720.00 | 21.90 | 0.00 | 21.90 | 0.00 | 21.90 |
December | 744.00 | 21.47 | 0.00 | 21.47 | 0.00 | 21.47 |
Annual Sum or Average | 8758.67 | 21.74 | 9.33 | 21.74 | 9.33 | 21.75 |
Minimum of Months | 672.00 | 21.37 | 0.00 | 21.37 | 0.00 | 21.37 |
Maximum of Months | 744.00 | 21.99 | 9.00 | 21.99 | 9.00 | 21.99 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.56 | 2.33 | 21.55 | 2.33 | 21.55 |
February | 659.50 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
March | 644.67 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
April | 543.33 | 21.25 | 11.17 | 21.29 | 0.00 | 21.29 |
May | 546.50 | 21.20 | 46.17 | 21.37 | 0.00 | 21.37 |
June | 544.33 | 21.26 | 33.33 | 21.38 | 0.00 | 21.38 |
July | 576.50 | 21.30 | 13.67 | 21.35 | 0.00 | 21.35 |
August | 583.67 | 21.32 | 0.00 | 21.32 | 0.00 | 21.32 |
September | 579.83 | 21.37 | 0.00 | 21.37 | 0.00 | 21.37 |
October | 593.67 | 21.34 | 0.00 | 21.34 | 0.00 | 21.34 |
November | 641.17 | 21.53 | 0.00 | 21.53 | 0.00 | 21.53 |
December | 744.00 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
Annual Sum or Average | 7401.17 | 21.42 | 106.67 | 21.45 | 2.33 | 21.45 |
Minimum of Months | 543.33 | 21.20 | 0.00 | 21.29 | 0.00 | 21.29 |
Maximum of Months | 744.00 | 21.64 | 46.17 | 21.64 | 2.33 | 21.64 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.33 | 2.50 | 21.33 | 2.50 | 21.33 |
February | 666.83 | 21.86 | 0.33 | 21.87 | 0.00 | 21.87 |
March | 654.67 | 21.96 | 21.50 | 22.04 | 0.00 | 22.04 |
April | 520.17 | 21.32 | 18.67 | 21.45 | 0.00 | 21.45 |
May | 546.67 | 21.21 | 32.00 | 21.33 | 0.67 | 21.34 |
June | 542.83 | 21.26 | 31.00 | 21.37 | 0.00 | 21.37 |
July | 576.33 | 21.30 | 13.00 | 21.34 | 0.00 | 21.34 |
August | 586.50 | 21.33 | 0.00 | 21.33 | 0.00 | 21.33 |
September | 585.00 | 21.39 | 0.33 | 21.39 | 0.00 | 21.39 |
October | 602.67 | 21.75 | 36.83 | 21.90 | 12.50 | 21.94 |
November | 707.33 | 22.07 | 6.17 | 22.09 | 0.00 | 22.09 |
December | 744.00 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
Annual Sum or Average | 7477.00 | 21.54 | 162.33 | 21.59 | 15.67 | 21.60 |
Minimum of Months | 520.17 | 21.21 | 0.00 | 21.33 | 0.00 | 21.33 |
Maximum of Months | 744.00 | 22.07 | 36.83 | 22.09 | 12.50 | 22.09 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.41 | 0.00 | 21.41 | 0.00 | 21.41 |
February | 672.00 | 22.05 | 6.17 | 22.05 | 6.17 | 22.06 |
March | 720.00 | 22.90 | 53.33 | 22.92 | 53.33 | 22.94 |
April | 332.17 | 23.51 | 231.50 | 23.64 | 94.17 | 23.65 |
May | 146.67 | 23.89 | 575.33 | 23.93 | 146.50 | 23.92 |
June | 164.33 | 23.83 | 560.50 | 23.90 | 159.33 | 23.89 |
July | 217.00 | 23.84 | 565.33 | 23.89 | 211.00 | 23.88 |
August | 262.17 | 23.72 | 470.67 | 23.80 | 224.50 | 23.80 |
September | 376.00 | 23.41 | 429.33 | 23.60 | 212.17 | 23.61 |
October | 412.33 | 23.39 | 226.67 | 23.49 | 148.50 | 23.50 |
November | 720.00 | 22.87 | 13.50 | 22.88 | 13.50 | 22.88 |
December | 744.00 | 21.81 | 0.00 | 21.81 | 0.00 | 21.81 |
Annual Sum or Average | 5510.67 | 22.68 | 3132.33 | 23.11 | 1269.17 | 23.18 |
Minimum of Months | 146.67 | 21.41 | 0.00 | 21.41 | 0.00 | 21.41 |
Maximum of Months | 744.00 | 23.89 | 575.33 | 23.93 | 224.50 | 23.92 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 740.17 | 21.45 | 22.00 | 21.44 | 22.00 | 21.43 |
February | 621.17 | 21.46 | 2.17 | 21.46 | 2.17 | 21.45 |
March | 632.50 | 21.42 | 12.83 | 21.45 | 0.17 | 21.46 |
April | 552.50 | 21.31 | 64.83 | 21.52 | 0.00 | 21.52 |
May | 543.17 | 21.26 | 97.67 | 21.57 | 0.00 | 21.57 |
June | 530.50 | 21.27 | 95.83 | 21.58 | 0.00 | 21.58 |
July | 575.00 | 21.30 | 58.50 | 21.49 | 0.00 | 21.49 |
August | 588.00 | 21.33 | 40.83 | 21.46 | 0.00 | 21.46 |
September | 578.33 | 21.36 | 44.17 | 21.50 | 0.00 | 21.50 |
October | 597.00 | 21.35 | 43.33 | 21.48 | 0.33 | 21.48 |
November | 615.33 | 21.41 | 2.50 | 21.42 | 0.00 | 21.42 |
December | 723.67 | 21.52 | 0.50 | 21.52 | 0.50 | 21.51 |
Annual Sum or Average | 7297.33 | 21.38 | 485.17 | 21.49 | 25.17 | 21.49 |
Minimum of Months | 530.50 | 21.26 | 0.50 | 21.42 | 0.00 | 21.42 |
Maximum of Months | 740.17 | 21.52 | 97.67 | 21.58 | 22.00 | 21.58 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.29 | 33.67 | 21.26 | 33.67 | 21.23 |
February | 657.50 | 21.76 | 4.17 | 21.76 | 4.17 | 21.76 |
March | 641.50 | 21.82 | 5.50 | 21.84 | 3.00 | 21.84 |
April | 555.67 | 21.45 | 47.67 | 21.60 | 0.67 | 21.61 |
May | 546.00 | 21.28 | 88.67 | 21.56 | 1.17 | 21.56 |
June | 530.00 | 21.27 | 96.17 | 21.58 | 1.67 | 21.59 |
July | 575.50 | 21.30 | 56.50 | 21.48 | 0.00 | 21.48 |
August | 590.50 | 21.34 | 28.50 | 21.43 | 0.00 | 21.43 |
September | 588.83 | 21.40 | 21.50 | 21.47 | 0.00 | 21.47 |
October | 626.17 | 21.74 | 33.17 | 21.82 | 25.00 | 21.88 |
November | 668.00 | 21.86 | 2.67 | 21.86 | 2.67 | 21.86 |
December | 744.00 | 21.42 | 6.00 | 21.41 | 6.00 | 21.40 |
Annual Sum or Average | 7467.67 | 21.50 | 424.17 | 21.58 | 78.00 | 21.59 |
Minimum of Months | 530.00 | 21.27 | 2.67 | 21.26 | 0.00 | 21.23 |
Maximum of Months | 744.00 | 21.86 | 96.17 | 21.86 | 33.67 | 21.88 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 671.67 | 21.46 | 0.50 | 21.46 | 0.50 | 21.46 |
February | 584.17 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
March | 626.67 | 21.42 | 13.17 | 21.46 | 0.00 | 21.46 |
April | 580.33 | 21.37 | 19.83 | 21.43 | 0.00 | 21.43 |
May | 596.50 | 21.37 | 16.50 | 21.42 | 0.00 | 21.42 |
June | 581.33 | 21.38 | 9.33 | 21.41 | 0.00 | 21.41 |
July | 610.67 | 21.41 | 0.33 | 21.41 | 0.00 | 21.41 |
August | 613.67 | 21.41 | 0.00 | 21.41 | 0.00 | 21.41 |
September | 599.50 | 21.43 | 31.67 | 21.53 | 0.00 | 21.53 |
October | 587.50 | 21.34 | 82.67 | 21.58 | 0.00 | 21.58 |
November | 579.17 | 21.34 | 52.00 | 21.51 | 0.00 | 21.51 |
December | 656.00 | 21.47 | 0.00 | 21.47 | 0.00 | 21.47 |
Annual Sum or Average | 7287.17 | 21.40 | 226.00 | 21.46 | 0.50 | 21.46 |
Minimum of Months | 579.17 | 21.34 | 0.00 | 21.41 | 0.00 | 21.41 |
Maximum of Months | 671.67 | 21.47 | 82.67 | 21.58 | 0.50 | 21.58 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 298.50 | 23.00 | 264.50 | 23.45 | 23.17 | 23.47 |
February | 126.00 | 23.31 | 429.00 | 23.79 | 43.83 | 23.81 |
March | 152.00 | 23.96 | 686.50 | 23.93 | 146.50 | 23.94 |
April | 188.50 | 24.00 | 717.00 | 23.97 | 188.50 | 23.98 |
May | 253.67 | 24.00 | 744.00 | 23.99 | 253.67 | 23.99 |
June | 252.50 | 24.00 | 720.00 | 23.99 | 252.50 | 23.99 |
July | 276.17 | 24.00 | 744.00 | 23.99 | 276.17 | 23.99 |
August | 280.67 | 24.00 | 744.00 | 23.99 | 280.67 | 23.99 |
September | 286.50 | 24.00 | 720.00 | 23.97 | 286.50 | 23.98 |
October | 289.17 | 23.99 | 744.00 | 23.94 | 289.17 | 23.96 |
November | 129.50 | 23.91 | 588.00 | 23.90 | 118.83 | 23.91 |
December | 233.83 | 23.05 | 309.00 | 23.56 | 4.50 | 23.57 |
Annual Sum or Average | 2767.00 | 23.77 | 7410.00 | 23.91 | 2164.00 | 23.92 |
Minimum of Months | 126.00 | 23.00 | 264.50 | 23.45 | 4.50 | 23.47 |
Maximum of Months | 298.50 | 24.00 | 744.00 | 23.99 | 289.17 | 23.99 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 115.67 | 23.14 | 442.00 | 23.78 | 12.33 | 23.78 |
February | 36.00 | 23.77 | 562.83 | 23.91 | 28.17 | 23.92 |
March | 128.17 | 24.00 | 725.83 | 23.95 | 128.17 | 23.96 |
April | 172.17 | 24.00 | 720.00 | 23.98 | 172.17 | 23.99 |
May | 239.83 | 24.00 | 744.00 | 23.99 | 239.83 | 23.99 |
June | 237.83 | 24.00 | 720.00 | 23.99 | 237.83 | 23.99 |
July | 258.17 | 24.00 | 744.00 | 23.99 | 258.17 | 23.99 |
August | 261.33 | 24.00 | 744.00 | 23.99 | 261.33 | 23.99 |
September | 265.67 | 24.00 | 720.00 | 23.99 | 265.67 | 23.99 |
October | 264.17 | 24.00 | 744.00 | 23.97 | 264.17 | 23.97 |
November | 98.50 | 23.99 | 675.33 | 23.93 | 98.50 | 23.94 |
December | 59.67 | 23.17 | 452.17 | 23.86 | 4.17 | 23.86 |
Annual Sum or Average | 2137.17 | 23.92 | 7994.17 | 23.96 | 1970.50 | 23.96 |
Minimum of Months | 36.00 | 23.14 | 442.00 | 23.78 | 4.17 | 23.78 |
Maximum of Months | 265.67 | 24.00 | 744.00 | 23.99 | 265.67 | 23.99 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 523.17 | 23.99 | 700.83 | 23.89 | 523.17 | 23.92 |
February | 482.83 | 23.99 | 665.83 | 23.88 | 482.83 | 23.91 |
March | 562.83 | 23.99 | 744.00 | 23.93 | 562.83 | 23.95 |
April | 588.83 | 23.99 | 720.00 | 23.97 | 588.83 | 23.98 |
May | 664.67 | 23.99 | 744.00 | 23.99 | 664.67 | 23.99 |
June | 654.67 | 23.99 | 720.00 | 23.98 | 654.67 | 23.99 |
July | 671.83 | 23.99 | 744.00 | 23.98 | 671.83 | 23.99 |
August | 641.50 | 23.99 | 744.00 | 23.98 | 641.50 | 23.98 |
September | 591.33 | 23.99 | 720.00 | 23.97 | 591.33 | 23.98 |
October | 587.33 | 23.99 | 744.00 | 23.95 | 587.33 | 23.96 |
November | 529.83 | 23.99 | 720.00 | 23.90 | 529.83 | 23.93 |
December | 523.33 | 23.99 | 716.00 | 23.88 | 523.33 | 23.91 |
Annual Sum or Average | 7022.17 | 23.99 | 8682.67 | 23.94 | 7022.17 | 23.96 |
Minimum of Months | 482.83 | 23.99 | 665.83 | 23.88 | 482.83 | 23.91 |
Maximum of Months | 671.83 | 23.99 | 744.00 | 23.99 | 671.83 | 23.99 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.22 | 0.00 | 21.22 | 0.00 | 21.22 |
February | 672.00 | 21.72 | 0.00 | 21.72 | 0.00 | 21.72 |
March | 579.17 | 22.49 | 58.67 | 22.62 | 0.00 | 22.62 |
April | 145.50 | 23.01 | 377.50 | 23.64 | 0.00 | 23.64 |
May | 0.00 | 0.00 | 708.00 | 23.92 | 0.00 | 23.92 |
June | 6.00 | 23.05 | 674.50 | 23.92 | 0.00 | 23.92 |
July | 0.00 | 0.00 | 711.33 | 23.90 | 0.00 | 23.90 |
August | 3.00 | 23.10 | 668.83 | 23.86 | 0.00 | 23.86 |
September | 119.00 | 22.96 | 439.67 | 23.66 | 0.00 | 23.66 |
October | 318.67 | 22.82 | 210.67 | 23.23 | 0.00 | 23.23 |
November | 683.50 | 22.28 | 1.33 | 22.29 | 0.00 | 22.29 |
December | 744.00 | 21.36 | 0.00 | 21.36 | 0.00 | 21.36 |
Annual Sum or Average | 4014.83 | 21.94 | 3850.50 | 22.90 | 0.00 | 22.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.22 | 0.00 | 21.22 |
Maximum of Months | 744.00 | 23.10 | 711.33 | 23.92 | 0.00 | 23.92 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.76499 | 43.37706 | 0.31029 | 7.11741 |
February | 672.00000 | 23.24068 | 48.91813 | 0.20831 | 6.05697 |
March | 744.00000 | 22.53791 | 55.48025 | 0.06760 | 5.25255 |
April | 720.00000 | 22.29883 | 58.33183 | 0.02439 | 5.19806 |
May | 744.00000 | 22.74468 | 60.28606 | -0.8771 | 21.48349 |
June | 720.00000 | 23.50362 | 58.59819 | -0.6087 | 13.00270 |
July | 744.00000 | 23.91785 | 57.32721 | -0.4492 | 9.26404 |
August | 744.00000 | 23.98953 | 57.00621 | -0.4117 | 8.54249 |
September | 720.00000 | 23.99514 | 57.08988 | -0.4059 | 8.46546 |
October | 744.00000 | 23.97992 | 56.26210 | 0.47798 | 9.79095 |
November | 720.00000 | 23.96582 | 49.96909 | 0.42451 | 8.82111 |
December | 744.00000 | 23.94101 | 42.20532 | 0.35737 | 7.73206 |
Annual Sum or Average | 8760.00000 | 23.49259 | 53.75246 | -0.0751 | 9.25723 |
Minimum of Months | 672.00000 | 22.29883 | 42.20532 | -0.8771 | 5.19806 |
Maximum of Months | 744.00000 | 23.99514 | 60.28606 | 0.47798 | 21.48349 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.78034 | 47.08002 | -0.1133 | 6.44904 |
February | 672.00000 | 22.25763 | 50.31940 | 0.05763 | 6.50152 |
March | 744.00000 | 22.98404 | 52.71254 | 0.29375 | 8.01787 |
April | 720.00000 | 23.62750 | 52.77187 | 0.49503 | 10.64665 |
May | 744.00000 | 23.85151 | 55.28295 | -0.2635 | 6.79121 |
June | 720.00000 | 23.81429 | 56.26410 | -0.2697 | 7.00521 |
July | 744.00000 | 23.80917 | 57.20698 | -0.2835 | 7.03745 |
August | 744.00000 | 23.74006 | 57.86831 | -0.3182 | 7.50970 |
September | 720.00000 | 23.53957 | 58.56997 | -0.3840 | 9.13721 |
October | 744.00000 | 23.48874 | 57.28434 | 0.48700 | 10.66372 |
November | 720.00000 | 22.96381 | 52.04764 | 0.28821 | 8.11008 |
December | 744.00000 | 22.00850 | 46.00400 | -0.0435 | 6.46070 |
Annual Sum or Average | 8760.00000 | 23.15918 | 53.63058 | -0.0054 | 7.86257 |
Minimum of Months | 672.00000 | 21.78034 | 46.00400 | -0.3840 | 6.44904 |
Maximum of Months | 744.00000 | 23.85151 | 58.56997 | 0.49503 | 10.66372 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.62497 | 46.62601 | 0.06684 | 5.44481 |
February | 672.00000 | 23.00092 | 49.98025 | 0.19280 | 6.17947 |
March | 744.00000 | 23.44530 | 53.14725 | 0.34198 | 7.79002 |
April | 720.00000 | 23.76313 | 53.92217 | 0.44749 | 9.39249 |
May | 744.00000 | 23.86068 | 56.59653 | -0.3884 | 8.29685 |
June | 720.00000 | 23.85908 | 57.38990 | -0.3826 | 8.21277 |
July | 744.00000 | 23.85746 | 58.20781 | -0.3850 | 8.22533 |
August | 744.00000 | 23.83908 | 58.67769 | -0.3942 | 8.37614 |
September | 720.00000 | 23.77399 | 59.09483 | -0.4201 | 8.95490 |
October | 744.00000 | 23.74656 | 58.06016 | 0.46562 | 9.65051 |
November | 720.00000 | 23.46346 | 52.40326 | 0.33923 | 7.67512 |
December | 744.00000 | 22.86132 | 45.65188 | 0.12514 | 5.67584 |
Annual Sum or Average | 8760.00000 | 23.50990 | 54.16367 | -0.0008 | 7.82830 |
Minimum of Months | 672.00000 | 22.62497 | 45.65188 | -0.4201 | 5.44481 |
Maximum of Months | 744.00000 | 23.86068 | 59.09483 | 0.46562 | 9.65051 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.97970 | 41.29020 | 0.72886 | 18.71805 |
February | 672.00000 | 23.02559 | 45.45126 | 0.79267 | 20.70624 |
March | 744.00000 | 23.05317 | 49.95708 | 0.86552 | 23.09177 |
April | 720.00000 | 23.08267 | 51.91873 | 0.92343 | 25.04654 |
May | 744.00000 | 23.10402 | 55.12611 | 0.29213 | 11.25168 |
June | 720.00000 | 23.09800 | 55.92601 | 0.29016 | 11.25483 |
July | 744.00000 | 23.13422 | 56.47830 | 0.29387 | 11.11568 |
August | 744.00000 | 23.12218 | 56.82708 | 0.28438 | 11.13233 |
September | 720.00000 | 23.10821 | 57.03648 | 0.26257 | 10.91241 |
October | 744.00000 | 23.07983 | 56.02060 | 0.92938 | 25.23900 |
November | 720.00000 | 23.06898 | 49.15716 | 0.84895 | 22.50775 |
December | 744.00000 | 23.00605 | 40.86709 | 0.74116 | 19.08240 |
Annual Sum or Average | 8760.00000 | 23.07207 | 51.36259 | 0.60313 | 17.47939 |
Minimum of Months | 672.00000 | 22.97970 | 40.86709 | 0.26257 | 10.91241 |
Maximum of Months | 744.00000 | 23.13422 | 57.03648 | 0.92938 | 25.23900 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.01671 | 50.09204 | 0.24213 | 6.93476 |
February | 672.00000 | 23.36688 | 53.28798 | 0.38246 | 8.73639 |
March | 744.00000 | 23.66057 | 56.42582 | 0.52026 | 11.16872 |
April | 720.00000 | 23.81749 | 57.28187 | 0.60985 | 13.04533 |
May | 744.00000 | 23.85618 | 60.00686 | -0.1762 | 5.87099 |
June | 720.00000 | 23.83479 | 60.82937 | -0.1782 | 5.94305 |
July | 744.00000 | 23.82238 | 61.65760 | -0.1900 | 6.02849 |
August | 744.00000 | 23.79451 | 62.21712 | -0.2103 | 6.18586 |
September | 720.00000 | 23.77005 | 62.51869 | -0.2213 | 6.59027 |
October | 744.00000 | 23.85136 | 61.17779 | 0.64536 | 14.01355 |
November | 720.00000 | 23.77155 | 55.42723 | 0.54719 | 11.70204 |
December | 744.00000 | 23.27291 | 49.02285 | 0.31647 | 7.71027 |
Annual Sum or Average | 8760.00000 | 23.65371 | 57.51337 | 0.18909 | 8.65296 |
Minimum of Months | 672.00000 | 23.01671 | 49.02285 | -0.2213 | 5.87099 |
Maximum of Months | 744.00000 | 23.85618 | 62.51869 | 0.64536 | 14.01355 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.16498 | 48.55474 | 0.23144 | 6.48438 |
February | 672.00000 | 23.42021 | 51.98363 | 0.33370 | 7.66527 |
March | 744.00000 | 23.63432 | 55.43431 | 0.43335 | 9.20070 |
April | 720.00000 | 23.77057 | 56.49222 | 0.49883 | 10.39549 |
May | 744.00000 | 23.82784 | 59.17009 | -0.3319 | 7.46436 |
June | 720.00000 | 23.83687 | 59.85538 | -0.3206 | 7.31286 |
July | 744.00000 | 23.84309 | 60.52689 | -0.3175 | 7.24900 |
August | 744.00000 | 23.83115 | 60.97459 | -0.3251 | 7.34771 |
September | 720.00000 | 23.82116 | 61.30098 | -0.3347 | 7.55618 |
October | 744.00000 | 23.84986 | 60.22650 | 0.54296 | 11.24171 |
November | 720.00000 | 23.74556 | 54.44364 | 0.45408 | 9.48124 |
December | 744.00000 | 23.36426 | 47.67452 | 0.28409 | 7.01098 |
Annual Sum or Average | 8760.00000 | 23.67663 | 56.40471 | 0.09400 | 8.19990 |
Minimum of Months | 672.00000 | 23.16498 | 47.67452 | -0.3347 | 6.48438 |
Maximum of Months | 744.00000 | 23.84986 | 61.30098 | 0.54296 | 11.24171 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.50212 | 56.37272 | -0.2166 | 6.64582 |
February | 672.00000 | 21.62170 | 56.62956 | -0.1290 | 6.15668 |
March | 744.00000 | 21.71268 | 53.19239 | -0.0479 | 5.90309 |
April | 720.00000 | 21.75497 | 50.03142 | 0.01903 | 5.92367 |
May | 744.00000 | 21.76676 | 50.41665 | -0.9886 | 27.25172 |
June | 720.00000 | 21.76265 | 51.37252 | -0.9901 | 27.26315 |
July | 744.00000 | 21.75202 | 51.54048 | -1.0245 | 28.62733 |
August | 744.00000 | 21.74835 | 51.60196 | -1.0486 | 29.65036 |
September | 720.00000 | 21.74620 | 52.01145 | -1.0604 | 30.25357 |
October | 744.00000 | 21.73967 | 52.51084 | -0.0077 | 5.87733 |
November | 720.00000 | 21.70433 | 54.41591 | -0.0648 | 5.96768 |
December | 744.00000 | 21.59891 | 54.97336 | -0.1768 | 6.42947 |
Annual Sum or Average | 8760.00000 | 21.70106 | 52.90254 | -0.4804 | 15.55224 |
Minimum of Months | 672.00000 | 21.50212 | 50.03142 | -1.0604 | 5.87733 |
Maximum of Months | 744.00000 | 21.76676 | 56.62956 | 0.01903 | 30.25357 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.34574 | 57.23135 | -0.2916 | 7.17264 |
February | 672.00000 | 21.82897 | 57.70880 | -0.1182 | 6.13753 |
March | 744.00000 | 22.09247 | 53.86777 | 0.00990 | 5.90500 |
April | 720.00000 | 21.89386 | 50.30393 | 0.03516 | 5.94074 |
May | 744.00000 | 21.77200 | 50.44784 | -0.9914 | 27.33754 |
June | 720.00000 | 21.76726 | 51.37881 | -0.9881 | 27.17392 |
July | 744.00000 | 21.75201 | 51.55692 | -1.0247 | 28.62878 |
August | 744.00000 | 21.74759 | 51.70495 | -1.0527 | 29.80609 |
September | 720.00000 | 21.75143 | 52.46884 | -1.0739 | 30.75652 |
October | 744.00000 | 22.05308 | 54.19447 | 0.03460 | 5.94750 |
November | 720.00000 | 22.03962 | 56.78628 | -0.0299 | 5.87570 |
December | 744.00000 | 21.49203 | 56.22134 | -0.2426 | 6.74912 |
Annual Sum or Average | 8760.00000 | 21.79364 | 53.63273 | -0.4804 | 15.67727 |
Minimum of Months | 672.00000 | 21.34574 | 50.30393 | -1.0739 | 5.87570 |
Maximum of Months | 744.00000 | 22.09247 | 57.70880 | 0.03516 | 30.75652 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.37484 | 53.22578 | -0.2875 | 6.88294 |
February | 672.00000 | 21.76617 | 54.29174 | -0.1614 | 5.98035 |
March | 744.00000 | 21.98622 | 52.96039 | -0.0787 | 5.72902 |
April | 720.00000 | 21.82595 | 51.44939 | -0.0865 | 5.82032 |
May | 744.00000 | 21.73818 | 51.45157 | -1.1813 | 35.30263 |
June | 720.00000 | 21.73709 | 52.26464 | -1.1728 | 34.90137 |
July | 744.00000 | 21.73017 | 52.48295 | -1.1793 | 35.21878 |
August | 744.00000 | 21.72361 | 52.64085 | -1.1943 | 35.91021 |
September | 720.00000 | 21.71729 | 53.16219 | -1.2125 | 36.75988 |
October | 744.00000 | 21.95405 | 55.11422 | -0.0592 | 5.73833 |
November | 720.00000 | 21.90432 | 54.86524 | -0.1104 | 5.73725 |
December | 744.00000 | 21.46539 | 52.55311 | -0.2614 | 6.61531 |
Annual Sum or Average | 8760.00000 | 21.74285 | 53.02934 | -0.5849 | 18.45843 |
Minimum of Months | 672.00000 | 21.37484 | 51.44939 | -1.2125 | 5.72902 |
Maximum of Months | 744.00000 | 21.98622 | 55.11422 | -0.0592 | 36.75988 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.55533 | 55.91987 | -0.2064 | 6.56731 |
February | 672.00000 | 21.66325 | 55.84630 | -0.1188 | 6.12341 |
March | 744.00000 | 21.73408 | 52.73088 | -0.0421 | 5.91949 |
April | 720.00000 | 21.75847 | 50.08563 | 0.02227 | 5.95708 |
May | 744.00000 | 21.76458 | 50.72408 | -0.9841 | 27.11947 |
June | 720.00000 | 21.75957 | 51.49690 | -0.9979 | 27.59351 |
July | 744.00000 | 21.75467 | 51.85097 | -1.0208 | 28.49191 |
August | 744.00000 | 21.75099 | 51.83789 | -1.0460 | 29.55733 |
September | 720.00000 | 21.74910 | 52.06371 | -1.0610 | 30.29386 |
October | 744.00000 | 21.74626 | 52.62321 | -0.0038 | 5.88568 |
November | 720.00000 | 21.72631 | 54.45242 | -0.0592 | 5.95361 |
December | 744.00000 | 21.63659 | 54.52831 | -0.1706 | 6.36094 |
Annual Sum or Average | 8760.00000 | 21.71669 | 52.83104 | -0.4764 | 15.54072 |
Minimum of Months | 672.00000 | 21.55533 | 50.08563 | -1.0610 | 5.88568 |
Maximum of Months | 744.00000 | 21.76458 | 55.91987 | 0.02227 | 30.29386 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.33218 | 57.16039 | -0.2929 | 7.07844 |
February | 672.00000 | 21.88059 | 56.80478 | -0.1065 | 6.04660 |
March | 744.00000 | 22.17261 | 53.16131 | 0.02685 | 6.09317 |
April | 720.00000 | 21.92985 | 50.29055 | 0.04487 | 6.13231 |
May | 744.00000 | 21.77139 | 50.61752 | -0.9873 | 27.21930 |
June | 720.00000 | 21.76409 | 51.50615 | -0.9959 | 27.50367 |
July | 744.00000 | 21.75476 | 51.85826 | -1.0210 | 28.49422 |
August | 744.00000 | 21.75032 | 51.92152 | -1.0502 | 29.71711 |
September | 720.00000 | 21.75550 | 52.56076 | -1.0739 | 30.77952 |
October | 744.00000 | 22.09651 | 53.91227 | 0.04421 | 6.11215 |
November | 720.00000 | 22.10123 | 56.10768 | -0.0202 | 5.87854 |
December | 744.00000 | 21.49407 | 56.08232 | -0.2420 | 6.63158 |
Annual Sum or Average | 8760.00000 | 21.81563 | 53.48112 | -0.4754 | 15.69822 |
Minimum of Months | 672.00000 | 21.33218 | 50.29055 | -1.0739 | 5.87854 |
Maximum of Months | 744.00000 | 22.17261 | 57.16039 | 0.04487 | 30.77952 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.46021 | 58.17571 | -0.2381 | 7.02452 |
February | 672.00000 | 21.59788 | 58.22844 | -0.1397 | 6.39743 |
March | 744.00000 | 21.70259 | 54.28775 | -0.0464 | 6.04971 |
April | 720.00000 | 21.75540 | 50.54088 | 0.03144 | 6.11796 |
May | 744.00000 | 21.77153 | 50.53971 | -0.9623 | 26.53805 |
June | 720.00000 | 21.76751 | 51.33816 | -0.9623 | 26.47836 |
July | 744.00000 | 21.75242 | 51.62939 | -1.0052 | 28.03400 |
August | 744.00000 | 21.74848 | 51.85467 | -1.0333 | 29.18687 |
September | 720.00000 | 21.74504 | 52.58040 | -1.0493 | 29.97629 |
October | 744.00000 | 21.73181 | 53.67053 | -0.0051 | 6.02365 |
November | 720.00000 | 21.68790 | 56.18907 | -0.0721 | 6.13921 |
December | 744.00000 | 21.56500 | 56.53418 | -0.1983 | 6.78236 |
Annual Sum or Average | 8760.00000 | 21.69071 | 53.77343 | -0.4757 | 15.45013 |
Minimum of Months | 672.00000 | 21.46021 | 50.53971 | -1.0493 | 6.02365 |
Maximum of Months | 744.00000 | 21.77153 | 58.22844 | 0.03144 | 29.97629 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.28574 | 59.18703 | -0.3201 | 7.65189 |
February | 672.00000 | 21.79558 | 59.30784 | -0.1321 | 6.41588 |
March | 744.00000 | 22.04989 | 54.89834 | 0.00514 | 6.02717 |
April | 720.00000 | 21.87476 | 50.68341 | 0.04280 | 6.07431 |
May | 744.00000 | 21.77598 | 50.54402 | -0.9655 | 26.62023 |
June | 720.00000 | 21.77135 | 51.35082 | -0.9604 | 26.39207 |
July | 744.00000 | 21.75243 | 51.62826 | -1.0055 | 28.03530 |
August | 744.00000 | 21.74779 | 51.93949 | -1.0377 | 29.34390 |
September | 720.00000 | 21.74962 | 52.94557 | -1.0642 | 30.50760 |
October | 744.00000 | 21.99340 | 55.48513 | 0.02651 | 5.99579 |
November | 720.00000 | 21.96586 | 58.82754 | -0.0503 | 6.02354 |
December | 744.00000 | 21.42455 | 57.97657 | -0.2755 | 7.25111 |
Annual Sum or Average | 8760.00000 | 21.76451 | 54.53771 | -0.4806 | 15.58427 |
Minimum of Months | 672.00000 | 21.28574 | 50.54402 | -1.0642 | 5.99579 |
Maximum of Months | 744.00000 | 22.04989 | 59.30784 | 0.04280 | 30.50760 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.64093 | 54.42997 | -0.1497 | 6.51208 |
February | 672.00000 | 21.67543 | 54.76813 | -0.1015 | 6.24166 |
March | 744.00000 | 21.71998 | 52.95391 | -0.0517 | 6.07014 |
April | 720.00000 | 21.74910 | 50.76399 | -0.0126 | 6.01341 |
May | 744.00000 | 21.75632 | 50.86817 | -1.0540 | 30.03604 |
June | 720.00000 | 21.75459 | 51.62684 | -1.0549 | 30.00345 |
July | 744.00000 | 21.75153 | 51.79705 | -1.0684 | 30.53053 |
August | 744.00000 | 21.74886 | 51.82731 | -1.0841 | 31.24775 |
September | 720.00000 | 21.74829 | 52.44328 | -1.0836 | 31.44141 |
October | 744.00000 | 21.74878 | 53.35864 | 0.00456 | 6.14877 |
November | 720.00000 | 21.73218 | 53.73987 | -0.0315 | 6.22872 |
December | 744.00000 | 21.69324 | 52.94349 | -0.1202 | 6.39750 |
Annual Sum or Average | 8760.00000 | 21.72681 | 52.61442 | -0.4864 | 16.46741 |
Minimum of Months | 672.00000 | 21.64093 | 50.76399 | -1.0841 | 6.01341 |
Maximum of Months | 744.00000 | 21.75632 | 54.76813 | 0.00456 | 31.44141 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.52193 | 48.94015 | 0.33781 | 7.77371 |
February | 672.00000 | 23.69986 | 52.22228 | 0.43863 | 9.31017 |
March | 744.00000 | 23.87262 | 55.42305 | 0.55614 | 11.66366 |
April | 720.00000 | 23.96475 | 56.43142 | 0.63931 | 13.67412 |
May | 744.00000 | 23.98771 | 59.05873 | -0.1238 | 5.35249 |
June | 720.00000 | 23.98928 | 59.70785 | -0.1124 | 5.30362 |
July | 744.00000 | 23.98580 | 60.41204 | -0.1235 | 5.35126 |
August | 744.00000 | 23.98288 | 60.85982 | -0.1377 | 5.42235 |
September | 720.00000 | 23.96209 | 61.33394 | -0.1677 | 5.65222 |
October | 744.00000 | 23.92513 | 60.84708 | 0.62664 | 13.30303 |
November | 720.00000 | 23.80293 | 55.33802 | 0.50655 | 10.57368 |
December | 744.00000 | 23.59084 | 48.34553 | 0.36002 | 8.04739 |
Annual Sum or Average | 8760.00000 | 23.85765 | 56.59463 | 0.23183 | 8.44144 |
Minimum of Months | 672.00000 | 23.52193 | 48.34553 | -0.1677 | 5.30362 |
Maximum of Months | 744.00000 | 23.98928 | 61.33394 | 0.63931 | 13.67412 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.70037 | 47.81006 | 0.41886 | 8.92686 |
February | 672.00000 | 23.82998 | 51.22367 | 0.50511 | 10.52613 |
March | 744.00000 | 23.93231 | 54.70675 | 0.60084 | 12.70268 |
April | 720.00000 | 23.98140 | 55.96444 | 0.66896 | 14.48494 |
May | 744.00000 | 23.99257 | 58.68107 | -0.0869 | 5.18937 |
June | 720.00000 | 23.99284 | 59.33791 | -0.0759 | 5.15933 |
July | 744.00000 | 23.99208 | 60.02317 | -0.0860 | 5.18269 |
August | 744.00000 | 23.99137 | 60.44609 | -0.0989 | 5.22621 |
September | 720.00000 | 23.98306 | 60.84225 | -0.1232 | 5.36446 |
October | 744.00000 | 23.95821 | 60.26284 | 0.66147 | 14.23260 |
November | 720.00000 | 23.89288 | 54.49786 | 0.55955 | 11.69695 |
December | 744.00000 | 23.75562 | 47.27397 | 0.43658 | 9.21329 |
Annual Sum or Average | 8760.00000 | 23.91710 | 55.94208 | 0.28013 | 8.97750 |
Minimum of Months | 672.00000 | 23.70037 | 47.27397 | -0.1232 | 5.15933 |
Maximum of Months | 744.00000 | 23.99284 | 60.84225 | 0.66896 | 14.48494 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.73325 | 46.47330 | 1.05988 | 31.04936 |
February | 672.00000 | 23.79185 | 50.21390 | 1.13931 | 34.32442 |
March | 744.00000 | 23.87886 | 54.04444 | 1.24718 | 39.02114 |
April | 720.00000 | 23.95194 | 55.51779 | 1.34078 | 43.29817 |
May | 744.00000 | 23.97929 | 58.33225 | 0.88498 | 24.63609 |
June | 720.00000 | 23.97651 | 59.04024 | 0.88361 | 24.59194 |
July | 744.00000 | 23.97854 | 59.65595 | 0.86466 | 23.69432 |
August | 744.00000 | 23.97272 | 60.00188 | 0.84439 | 23.01531 |
September | 720.00000 | 23.95664 | 60.26957 | 0.81593 | 22.22910 |
October | 744.00000 | 23.91631 | 59.55078 | 1.31806 | 42.25131 |
November | 720.00000 | 23.82978 | 53.60982 | 1.20031 | 36.96276 |
December | 744.00000 | 23.74808 | 46.10462 | 1.07221 | 31.56863 |
Annual Sum or Average | 8760.00000 | 23.89325 | 55.25526 | 1.05521 | 31.35853 |
Minimum of Months | 672.00000 | 23.73325 | 46.10462 | 0.81593 | 22.22910 |
Maximum of Months | 744.00000 | 23.97929 | 60.26957 | 1.34078 | 43.29817 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.46884 | 46.21464 | -0.2474 | 6.44967 |
February | 672.00000 | 21.95987 | 49.47000 | -0.1000 | 5.45604 |
March | 744.00000 | 22.65414 | 52.19447 | 0.09820 | 5.43435 |
April | 720.00000 | 23.42567 | 52.04253 | 0.29729 | 7.04008 |
May | 744.00000 | 23.86491 | 54.10321 | -0.4836 | 9.96512 |
June | 720.00000 | 23.87464 | 54.96996 | -0.4683 | 9.66786 |
July | 744.00000 | 23.90616 | 55.76977 | -0.4536 | 9.34736 |
August | 744.00000 | 23.88590 | 56.25916 | -0.4635 | 9.52879 |
September | 720.00000 | 23.67527 | 56.99696 | -0.5376 | 11.24322 |
October | 744.00000 | 23.30517 | 56.51317 | 0.29617 | 6.91925 |
November | 720.00000 | 22.55924 | 51.77662 | 0.06989 | 5.28473 |
December | 744.00000 | 21.75364 | 45.07893 | -0.1806 | 5.83477 |
Annual Sum or Average | 8760.00000 | 23.03266 | 52.62706 | -0.1820 | 7.69234 |
Minimum of Months | 672.00000 | 21.46884 | 45.07893 | -0.5376 | 5.28473 |
Maximum of Months | 744.00000 | 23.90616 | 56.99696 | 0.29729 | 11.24322 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.41068 | 50.38262 | -0.2667 | 6.58710 |
February | 672.00000 | 22.04802 | 53.27250 | -0.0851 | 5.43134 |
March | 744.00000 | 22.92309 | 55.57891 | 0.15567 | 5.74705 |
April | 720.00000 | 23.66670 | 55.53279 | 0.34810 | 7.65369 |
May | 744.00000 | 23.89621 | 57.82489 | -0.4969 | 10.20410 |
June | 720.00000 | 23.86396 | 58.71742 | -0.5021 | 10.33316 |
July | 744.00000 | 23.83464 | 59.67356 | -0.5091 | 10.49044 |
August | 744.00000 | 23.74928 | 60.46167 | -0.5378 | 11.13740 |
September | 720.00000 | 23.60559 | 61.04577 | -0.5855 | 12.48645 |
October | 744.00000 | 23.52915 | 59.94380 | 0.34198 | 7.50589 |
November | 720.00000 | 22.87265 | 55.03316 | 0.13850 | 5.58445 |
December | 744.00000 | 21.81034 | 48.98161 | -0.1723 | 5.78471 |
Annual Sum or Average | 8760.00000 | 23.10511 | 56.38291 | -0.1821 | 8.26019 |
Minimum of Months | 672.00000 | 21.41068 | 48.98161 | -0.5855 | 5.43134 |
Maximum of Months | 744.00000 | 23.89621 | 61.04577 | 0.34810 | 12.48645 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.22336 | 47.94462 | -0.2970 | 6.98008 |
February | 672.00000 | 21.72309 | 51.25109 | -0.1344 | 5.79057 |
March | 744.00000 | 22.73406 | 53.00769 | 0.14983 | 6.10519 |
April | 720.00000 | 23.63338 | 52.40672 | 0.39303 | 8.47851 |
May | 744.00000 | 23.89902 | 54.66847 | -0.3966 | 8.39029 |
June | 720.00000 | 23.89273 | 55.44301 | -0.3900 | 8.32088 |
July | 744.00000 | 23.88131 | 56.28349 | -0.4011 | 8.46797 |
August | 744.00000 | 23.81604 | 56.91527 | -0.4307 | 9.01336 |
September | 720.00000 | 23.58897 | 57.82774 | -0.5130 | 10.91470 |
October | 744.00000 | 23.28697 | 57.57115 | 0.32797 | 7.53557 |
November | 720.00000 | 22.34530 | 53.46932 | 0.04627 | 5.54381 |
December | 744.00000 | 21.35805 | 47.17028 | -0.2597 | 6.65269 |
Annual Sum or Average | 8760.00000 | 22.95403 | 53.67075 | -0.1595 | 7.69143 |
Minimum of Months | 672.00000 | 21.22336 | 47.17028 | -0.5130 | 5.54381 |
Maximum of Months | 744.00000 | 23.89902 | 57.82774 | 0.39303 | 10.91470 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.59488 | 45.48917 | -0.2185 | 6.21571 |
February | 672.00000 | 22.08122 | 48.72630 | -0.0715 | 5.39846 |
March | 744.00000 | 22.77528 | 51.43024 | 0.12774 | 5.61077 |
April | 720.00000 | 23.52076 | 51.35687 | 0.32296 | 7.38706 |
May | 744.00000 | 23.88518 | 53.61084 | -0.4662 | 9.62004 |
June | 720.00000 | 23.89208 | 54.48801 | -0.4522 | 9.35897 |
July | 744.00000 | 23.92697 | 55.23506 | -0.4361 | 9.01392 |
August | 744.00000 | 23.91341 | 55.66283 | -0.4439 | 9.15290 |
September | 720.00000 | 23.74684 | 56.28445 | -0.5065 | 10.54801 |
October | 744.00000 | 23.42783 | 55.69614 | 0.32721 | 7.34925 |
November | 720.00000 | 22.68283 | 50.99897 | 0.09970 | 5.43283 |
December | 744.00000 | 21.88486 | 44.34161 | -0.1504 | 5.66537 |
Annual Sum or Average | 8760.00000 | 23.11565 | 51.95515 | -0.1566 | 7.57378 |
Minimum of Months | 672.00000 | 21.59488 | 44.34161 | -0.5065 | 5.39846 |
Maximum of Months | 744.00000 | 23.92697 | 56.28445 | 0.32721 | 10.54801 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.429743E+11 | 90352.66 | 12-JAN-16:03 | 698.42 | 0.125563E+12 | 0.00 | 0.168537E+12 | 2.87 | 3.52 | 25-JAN-16:01 | 0.00 | 0.00 |
February | 0.814538E+11 | 107585.71 | 22-FEB-16:03 | 668.87 | 0.234120E+12 | 0.00 | 0.315574E+12 | 2.97 | 3.79 | 25-FEB-16:03 | 0.00 | 0.00 |
March | 0.174499E+12 | 156890.35 | 28-MAR-15:03 | 744.00 | 0.513645E+12 | 0.00 | 0.688144E+12 | 2.94 | 3.84 | 06-MAR-22:53 | 0.00 | 0.00 |
April | 0.272757E+12 | 205951.28 | 26-APR-18:05 | 720.00 | 0.784956E+12 | 0.00 | 0.105771E+13 | 2.89 | 3.76 | 22-APR-21:53 | 0.00 | 0.00 |
May | 0.375761E+12 | 255386.75 | 17-MAY-18:03 | 744.00 | 0.107406E+13 | 0.00 | 0.144982E+13 | 2.89 | 3.71 | 12-MAY-21:00 | 0.00 | 0.00 |
June | 0.413540E+12 | 277918.26 | 10-JUN-18:03 | 720.00 | 0.120098E+13 | 0.00 | 0.161452E+13 | 2.94 | 3.79 | 24-JUN-15:03 | 0.00 | 0.00 |
July | 0.439903E+12 | 273769.55 | 01-JUL-18:03 | 744.00 | 0.137783E+13 | 0.00 | 0.181773E+13 | 3.16 | 3.89 | 19-JUL-02:00 | 0.00 | 0.00 |
August | 0.420975E+12 | 266078.17 | 28-AUG-18:02 | 744.00 | 0.138044E+13 | 0.00 | 0.180141E+13 | 3.30 | 3.94 | 15-AUG-24:00 | 0.00 | 0.00 |
September | 0.360483E+12 | 247713.43 | 14-SEP-18:03 | 720.00 | 0.119794E+13 | 0.00 | 0.155842E+13 | 3.34 | 3.91 | 08-SEP-20:00 | 0.00 | 0.00 |
October | 0.247843E+12 | 182247.82 | 03-OCT-15:03 | 744.00 | 0.786562E+12 | 0.00 | 0.103441E+13 | 3.15 | 4.24 | 25-OCT-21:54 | 0.00 | 0.00 |
November | 0.131408E+12 | 128032.10 | 04-NOV-15:03 | 720.00 | 0.387755E+12 | 0.00 | 0.519163E+12 | 2.99 | 4.03 | 08-NOV-22:53 | 0.00 | 0.00 |
December | 0.562826E+11 | 97592.13 | 01-DEC-16:01 | 725.50 | 0.162703E+12 | 0.00 | 0.218986E+12 | 2.97 | 3.73 | 01-DEC-16:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.301788E+13 | 8692.79 | 0.922655E+13 | 0.00 | 0.122444E+14 | 3.03 | 0.00 | 0.00 | ||||
Minimum of Months | 0.429743E+11 | 90352.66 | 668.87 | 0.125563E+12 | 0.00 | 0.168537E+12 | 2.87 | 3.52 | 0.00 | 0.00 | ||
Maximum of Months | 0.439903E+12 | 277918.26 | 744.00 | 0.138044E+13 | 0.00 | 0.181773E+13 | 3.34 | 4.24 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.665746E+10 | 0.00 | 487.80 | 47473.67 | 02-JAN-09:03 | 0.00 | 57.46 | 72.38 | 0.03 | 0.00 | 0.01 | 0.19 | 02-JAN-09:03 |
February | 0.147646E+10 | 0.00 | 220.94 | 31891.98 | 02-FEB-09:05 | 0.00 | 56.36 | 63.57 | 0.01 | 0.00 | 0.00 | 0.13 | 02-FEB-09:05 |
March | 0.110568E+09 | 0.00 | 13.56 | 18714.46 | 16-MAR-08:54 | 0.00 | 53.56 | 53.98 | 0.00 | 0.00 | 0.00 | 0.07 | 16-MAR-08:54 |
April | 53987009.16 | 0.00 | 2.27 | 14123.89 | 12-APR-08:35 | 0.00 | 53.53 | 53.61 | 0.00 | 0.00 | 0.00 | 0.06 | 12-APR-08:35 |
May | 35477239.67 | 0.00 | 1.41 | 12190.60 | 29-MAY-08:07 | 0.00 | 54.83 | 54.87 | 0.00 | 0.00 | 0.00 | 0.05 | 29-MAY-08:07 |
June | 37813771.22 | 0.00 | 1.47 | 11188.98 | 27-JUN-18:07 | 0.00 | 54.57 | 54.62 | 0.00 | 0.00 | 0.00 | 0.04 | 27-JUN-18:07 |
July | 42820442.43 | 0.00 | 1.81 | 11296.22 | 26-JUL-08:05 | 0.00 | 55.14 | 55.19 | 0.00 | 0.00 | 0.00 | 0.04 | 26-JUL-08:05 |
August | 46504157.89 | 0.00 | 2.15 | 11100.08 | 23-AUG-18:07 | 0.00 | 55.58 | 55.65 | 0.00 | 0.00 | 0.00 | 0.04 | 23-AUG-18:07 |
September | 80406590.63 | 0.00 | 3.00 | 14732.08 | 09-SEP-15:07 | 0.00 | 54.40 | 54.50 | 0.00 | 0.00 | 0.00 | 0.06 | 09-SEP-15:07 |
October | 95311036.55 | 0.00 | 4.54 | 21462.73 | 30-OCT-08:54 | 0.00 | 53.05 | 53.22 | 0.00 | 0.00 | 0.00 | 0.08 | 30-OCT-08:54 |
November | 0.224190E+09 | 0.00 | 71.65 | 23401.07 | 14-NOV-09:54 | 0.00 | 52.93 | 55.41 | 0.00 | 0.00 | 0.00 | 0.09 | 14-NOV-09:54 |
December | 0.344025E+10 | 0.00 | 421.68 | 33477.96 | 21-DEC-09:04 | 0.00 | 58.68 | 70.48 | 0.01 | 0.00 | 0.01 | 0.13 | 21-DEC-09:04 |
Annual Sum or Average | 0.123012E+11 | 0.00 | 1232.26 | 0.00 | 55.01 | 58.12 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 35477239.67 | 0.00 | 1.41 | 11100.08 | 0.00 | 52.93 | 53.22 | 0.00 | 0.00 | 0.00 | 0.04 | ||
Maximum of Months | 0.665746E+10 | 0.00 | 487.80 | 47473.67 | 0.00 | 58.68 | 72.38 | 0.03 | 0.00 | 0.01 | 0.19 |
Report: DXReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.453160E+11 | 0.00 | 379.38 | 0.437082E+11 | 0.160778E+10 | 0.00 | 1.00 | 01-JAN-06:15 | 0.00 | 01-JAN-00:10 | 51043.46 | 17-JAN-07:15 | 49218.70 | 20-JAN-09:00 | 1827.30 | 18-JAN-06:05 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.407558E+11 | 0.00 | 332.36 | 0.387422E+11 | 0.201354E+10 | 0.00 | 1.00 | 01-FEB-06:15 | 0.00 | 01-FEB-00:03 | 54932.34 | 01-FEB-21:30 | 52107.84 | 01-FEB-11:05 | 2826.24 | 01-FEB-06:15 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 0.427438E+11 | 0.00 | 353.39 | 0.419346E+11 | 0.809173E+09 | 0.00 | 1.00 | 01-MAR-05:10 | 0.00 | 01-MAR-00:03 | 59577.77 | 01-MAR-05:10 | 58143.21 | 01-MAR-11:18 | 1434.71 | 01-MAR-17:55 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 0.373598E+11 | 0.00 | 336.90 | 0.373584E+11 | 1356199.39 | 0.00 | 1.00 | 01-APR-05:08 | 0.00 | 01-APR-00:20 | 63622.14 | 01-APR-05:08 | 63622.14 | 01-APR-05:08 | 764.14 | 30-APR-23:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.341945E+11 | 0.00 | 342.11 | 0.328169E+11 | 0.137767E+10 | 0.00 | 1.00 | 01-MAY-07:15 | 0.00 | 01-MAY-00:05 | 66769.86 | 01-MAY-07:15 | 63601.72 | 01-MAY-09:07 | 7128.06 | 31-MAY-23:10 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.296381E+11 | 0.00 | 323.32 | 0.229925E+11 | 0.664561E+10 | 0.00 | 1.00 | 01-JUN-07:05 | 0.00 | 01-JUN-00:05 | 67643.47 | 01-JUN-17:17 | 52254.69 | 01-JUN-10:18 | 15400.11 | 01-JUN-17:17 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.291927E+11 | 0.00 | 336.74 | 0.148491E+11 | 0.143436E+11 | 0.00 | 1.00 | 01-JUL-07:15 | 0.00 | 01-JUL-00:10 | 67767.70 | 01-JUL-07:15 | 34459.23 | 28-JUL-07:05 | 33388.90 | 01-JUL-17:08 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.303173E+11 | 0.00 | 332.89 | 0.129463E+11 | 0.173710E+11 | 0.00 | 1.00 | 01-AUG-07:15 | 0.00 | 01-AUG-00:05 | 68076.53 | 31-AUG-07:15 | 28977.79 | 26-AUG-10:06 | 39140.95 | 31-AUG-17:08 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.325601E+11 | 0.00 | 329.77 | 0.161551E+11 | 0.164050E+11 | 0.00 | 1.00 | 01-SEP-07:15 | 0.00 | 01-SEP-00:05 | 67626.37 | 30-SEP-07:23 | 33421.07 | 30-SEP-08:03 | 34242.48 | 30-SEP-17:08 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.375599E+11 | 0.00 | 345.05 | 0.317295E+11 | 0.583041E+10 | 0.00 | 1.00 | 01-OCT-05:23 | 0.00 | 01-OCT-00:20 | 62110.87 | 31-OCT-05:15 | 52127.75 | 31-OCT-10:07 | 9992.08 | 31-OCT-17:06 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.401866E+11 | 0.00 | 339.96 | 0.383187E+11 | 0.186786E+10 | 0.00 | 1.00 | 01-NOV-05:15 | 0.00 | 01-NOV-00:05 | 57033.31 | 30-NOV-06:15 | 54106.89 | 30-NOV-09:54 | 2928.82 | 30-NOV-21:55 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.440875E+11 | 0.00 | 375.31 | 0.435825E+11 | 0.504953E+09 | 0.00 | 1.00 | 01-DEC-06:15 | 0.00 | 01-DEC-00:03 | 51996.97 | 31-DEC-16:07 | 51264.05 | 31-DEC-16:07 | 919.85 | 22-DEC-11:05 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.443912E+12 | 0.00 | 4127.18 | 0.375134E+12 | 0.687780E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.291927E+11 | 0.00 | 323.32 | 0.129463E+11 | 1356199.39 | 0.00 | 1.00 | 0.00 | 51043.46 | 28977.79 | 764.14 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.453160E+11 | 0.00 | 379.38 | 0.437082E+11 | 0.173710E+11 | 0.00 | 1.00 | 0.00 | 68076.53 | 63622.14 | 39140.95 | 0.00 | 0.00 |
Report: DXReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.511225E+11 | 0.00 | 352.10 | 0.493240E+11 | 0.179856E+10 | 0.00 | 1.00 | 01-JAN-17:10 | 0.00 | 01-JAN-00:10 | 64597.12 | 17-JAN-17:10 | 62307.25 | 20-JAN-20:00 | 2293.01 | 18-JAN-17:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.495120E+11 | 0.00 | 315.92 | 0.470809E+11 | 0.243118E+10 | 0.00 | 1.00 | 01-FEB-17:10 | 0.00 | 01-FEB-00:07 | 69521.36 | 01-FEB-17:10 | 65965.59 | 01-FEB-22:00 | 3556.86 | 01-FEB-17:10 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 0.591596E+11 | 0.00 | 348.23 | 0.580622E+11 | 0.109742E+10 | 0.00 | 1.00 | 01-MAR-17:10 | 0.00 | 01-MAR-00:07 | 75403.57 | 01-MAR-17:10 | 73610.27 | 01-MAR-21:00 | 1793.42 | 01-MAR-17:10 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 0.609690E+11 | 0.00 | 327.35 | 0.609683E+11 | 676436.03 | 0.00 | 1.00 | 01-APR-16:10 | 0.00 | 01-APR-00:10 | 80524.70 | 01-APR-16:10 | 80524.70 | 01-APR-16:10 | 2193.72 | 30-APR-23:05 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.658649E+11 | 0.00 | 336.92 | 0.632495E+11 | 0.261537E+10 | 0.00 | 1.00 | 01-MAY-16:10 | 0.00 | 01-MAY-00:05 | 84510.45 | 01-MAY-16:10 | 80525.19 | 01-MAY-20:00 | 3985.44 | 01-MAY-17:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.611470E+11 | 0.00 | 324.77 | 0.474598E+11 | 0.136871E+11 | 0.00 | 0.98 | 01-JUN-16:10 | 0.00 | 01-JUN-00:05 | 83012.17 | 01-JUN-16:10 | 64135.49 | 01-JUN-16:10 | 18876.68 | 01-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.616396E+11 | 0.00 | 335.33 | 0.313578E+11 | 0.302818E+11 | 0.00 | 0.94 | 01-JUL-16:10 | 0.00 | 01-JUL-00:10 | 79277.88 | 01-JUL-16:10 | 40235.50 | 01-JUL-16:10 | 39042.39 | 01-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.628493E+11 | 0.00 | 336.80 | 0.268328E+11 | 0.360165E+11 | 0.00 | 0.97 | 31-AUG-16:10 | 0.00 | 01-AUG-00:05 | 82378.41 | 31-AUG-16:10 | 35031.29 | 31-AUG-16:10 | 47347.12 | 31-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.639769E+11 | 0.00 | 327.51 | 0.317289E+11 | 0.322481E+11 | 0.00 | 1.00 | 15-SEP-16:10 | 0.00 | 01-SEP-00:05 | 85595.00 | 30-SEP-19:00 | 42287.07 | 30-SEP-22:00 | 43332.48 | 30-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.614884E+11 | 0.00 | 352.24 | 0.519595E+11 | 0.952893E+10 | 0.00 | 1.00 | 01-OCT-16:10 | 0.00 | 01-OCT-00:10 | 78611.07 | 31-OCT-16:10 | 65986.60 | 31-OCT-18:00 | 12628.46 | 31-OCT-17:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.547697E+11 | 0.00 | 336.60 | 0.522443E+11 | 0.252539E+10 | 0.00 | 1.00 | 01-NOV-16:10 | 0.00 | 01-NOV-00:05 | 72181.68 | 30-NOV-23:50 | 68496.66 | 30-NOV-17:10 | 3687.03 | 30-NOV-24:00 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.518531E+11 | 0.00 | 352.22 | 0.512757E+11 | 0.577408E+09 | 0.00 | 1.00 | 01-DEC-17:10 | 0.00 | 01-DEC-00:07 | 65804.48 | 31-DEC-17:50 | 64897.44 | 31-DEC-17:10 | 1270.48 | 21-DEC-22:40 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.704352E+12 | 0.00 | 4045.98 | 0.571544E+12 | 0.132808E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.495120E+11 | 0.00 | 315.92 | 0.268328E+11 | 676436.03 | 0.00 | 0.94 | 0.00 | 64597.12 | 35031.29 | 1270.48 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.658649E+11 | 0.00 | 352.24 | 0.632495E+11 | 0.360165E+11 | 0.00 | 1.00 | 0.00 | 85595.00 | 80525.19 | 47347.12 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.688318E+11 | 0.00 | 560.13 | 0.688318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130618.92 | 12-JAN-16:20 | 130618.92 | 12-JAN-16:20 | 0.00 | 0.00 | 0.00 |
February | 0.147738E+12 | 0.00 | 606.27 | 0.144559E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 191089.47 | 25-FEB-18:17 | 175116.24 | 22-FEB-19:10 | 0.00 | 0.00 | 0.00 |
March | 0.344814E+12 | 0.00 | 743.83 | 0.324207E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 324255.14 | 10-MAR-20:30 | 250713.81 | 28-MAR-18:07 | 0.00 | 0.00 | 0.00 |
April | 0.541718E+12 | 0.00 | 720.00 | 0.483043E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 376062.18 | 26-APR-21:00 | 297315.68 | 28-APR-18:20 | 0.00 | 0.00 | 0.00 |
May | 0.773464E+12 | 0.00 | 744.00 | 0.576865E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 501926.15 | 22-MAY-21:00 | 315995.58 | 05-MAY-20:10 | 0.00 | 0.00 | 0.00 |
June | 0.898044E+12 | 0.00 | 720.00 | 0.571125E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 518410.97 | 29-JUN-21:00 | 326024.25 | 12-JUN-18:20 | 0.00 | 0.00 | 0.00 |
July | 0.106423E+13 | 0.00 | 744.00 | 0.564952E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 542469.12 | 13-JUL-18:02 | 313596.10 | 03-JUL-20:10 | 0.00 | 0.00 | 0.00 |
August | 0.108202E+13 | 0.00 | 744.00 | 0.543959E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 586608.26 | 28-AUG-18:02 | 300978.21 | 07-AUG-20:10 | 0.00 | 0.00 | 0.00 |
September | 0.931283E+12 | 0.00 | 720.00 | 0.501578E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 546618.32 | 14-SEP-18:03 | 297255.04 | 17-SEP-20:10 | 0.00 | 0.00 | 0.00 |
October | 0.557453E+12 | 0.00 | 744.00 | 0.424398E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 432702.71 | 12-OCT-20:00 | 267614.55 | 05-OCT-19:10 | 0.00 | 0.00 | 0.00 |
November | 0.244638E+12 | 0.00 | 704.01 | 0.235982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 278853.30 | 08-NOV-19:08 | 205904.38 | 03-NOV-18:07 | 0.00 | 0.00 | 0.00 |
December | 0.903586E+11 | 0.00 | 588.02 | 0.900716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 145916.58 | 03-DEC-13:00 | 145916.58 | 03-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.674460E+13 | 0.00 | 8338.27 | 0.452957E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.688318E+11 | 0.00 | 560.13 | 0.688318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130618.92 | 130618.92 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.108202E+13 | 0.00 | 744.00 | 0.576865E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 586608.26 | 326024.25 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.415393E+10 | 0.00 | 195.67 | 0.413816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15958.11 | 12-JAN-16:01 | 15958.11 | 12-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.991351E+10 | 0.00 | 316.33 | 0.929049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25529.81 | 25-FEB-17:00 | 17721.28 | 22-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.260363E+11 | 0.00 | 572.00 | 0.231951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26374.72 | 29-MAR-08:15 | 21059.34 | 28-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.369569E+11 | 0.00 | 570.00 | 0.330189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28762.85 | 25-APR-08:62 | 22748.48 | 15-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.495726E+11 | 0.00 | 589.00 | 0.374273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37779.09 | 22-MAY-23:00 | 24260.00 | 03-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.593590E+11 | 0.00 | 570.00 | 0.371422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44880.78 | 28-JUN-13:00 | 24326.77 | 08-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.722065E+11 | 0.00 | 589.00 | 0.372628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45460.97 | 18-JUL-15:00 | 23132.41 | 02-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.727658E+11 | 0.00 | 589.00 | 0.359183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45949.38 | 10-AUG-14:40 | 22123.43 | 07-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.630464E+11 | 0.00 | 570.00 | 0.335756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42526.37 | 12-SEP-15:02 | 21597.56 | 17-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.411362E+11 | 0.00 | 589.00 | 0.293743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40724.61 | 13-OCT-08:30 | 21397.49 | 02-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.156078E+11 | 0.00 | 461.17 | 0.141733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25915.92 | 08-NOV-19:40 | 19083.82 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.545463E+10 | 0.00 | 207.33 | 0.543023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16352.24 | 28-DEC-16:02 | 16352.24 | 28-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.456210E+12 | 0.00 | 5818.50 | 0.299947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.415393E+10 | 0.00 | 195.67 | 0.413816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15958.11 | 15958.11 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.727658E+11 | 0.00 | 589.00 | 0.374273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45949.38 | 24326.77 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.140800E+10 | 0.00 | 324.42 | 0.679201E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14348.18 | 18-JAN-16:01 | 12366.12 | 12-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.329445E+10 | 0.00 | 502.33 | 0.168209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13732.10 | 25-FEB-09:02 | 12857.25 | 24-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.779512E+10 | 0.00 | 692.87 | 0.482717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13739.02 | 10-MAR-09:01 | 12752.92 | 08-MAR-19:02 | 0.00 | 0.00 | 0.00 |
April | 0.121798E+11 | 0.00 | 696.19 | 0.895861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14216.07 | 23-APR-08:61 | 12918.67 | 19-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.146087E+11 | 0.00 | 728.40 | 0.109209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14027.69 | 13-MAY-08:62 | 12907.17 | 01-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.140376E+11 | 0.00 | 704.32 | 0.102193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14331.17 | 25-JUN-08:61 | 12905.82 | 08-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.130982E+11 | 0.00 | 724.59 | 0.909946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14041.67 | 18-JUL-15:02 | 12928.54 | 17-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.120518E+11 | 0.00 | 720.72 | 0.812054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14158.81 | 20-AUG-08:62 | 12938.71 | 02-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.109923E+11 | 0.00 | 693.72 | 0.734251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15189.28 | 09-SEP-15:02 | 12930.85 | 03-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.103007E+11 | 0.00 | 710.85 | 0.681957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14414.01 | 12-OCT-08:62 | 12932.12 | 06-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.636668E+10 | 0.00 | 664.34 | 0.361529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13713.11 | 18-NOV-09:02 | 12727.93 | 04-NOV-18:02 | 0.00 | 0.00 | 0.00 |
December | 0.205811E+10 | 0.00 | 452.37 | 0.946334E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13646.09 | 10-DEC-16:01 | 12274.84 | 28-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108191E+12 | 0.00 | 7615.12 | 0.732310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.140800E+10 | 0.00 | 324.42 | 0.679201E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13646.09 | 12274.84 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.146087E+11 | 0.00 | 728.40 | 0.109209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15189.28 | 12938.71 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.209065E+09 | 0.00 | 101.01 | 98846938.88 | 0.00 | 0.00 | 0.00 | 0.00 | 14143.77 | 14-JAN-16:01 | 12348.11 | 08-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.123338E+10 | 0.00 | 272.95 | 0.527474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14432.82 | 14-FEB-16:01 | 12914.64 | 21-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.552002E+10 | 0.00 | 518.05 | 0.324263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15263.17 | 10-MAR-09:51 | 12963.34 | 09-MAR-19:02 | 0.00 | 0.00 | 0.00 |
April | 0.110291E+11 | 0.00 | 644.48 | 0.800578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15876.11 | 22-APR-08:11 | 14140.25 | 30-APR-07:51 | 0.00 | 0.00 | 0.00 |
May | 0.143877E+11 | 0.00 | 725.76 | 0.106904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16672.32 | 13-MAY-08:11 | 12991.42 | 16-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.140545E+11 | 0.00 | 702.96 | 0.102329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15213.97 | 18-JUN-08:62 | 12945.35 | 24-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.130876E+11 | 0.00 | 724.63 | 0.907357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14102.68 | 18-JUL-15:02 | 12984.35 | 04-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.118491E+11 | 0.00 | 719.93 | 0.790073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14222.64 | 20-AUG-08:62 | 12991.52 | 02-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.101911E+11 | 0.00 | 687.57 | 0.650244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15283.98 | 09-SEP-15:02 | 12965.18 | 05-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.754276E+10 | 0.00 | 574.64 | 0.464104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16318.27 | 06-OCT-08:61 | 12979.36 | 04-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.299955E+10 | 0.00 | 445.03 | 0.138714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14624.95 | 09-NOV-09:51 | 12827.72 | 16-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.372839E+09 | 0.00 | 151.35 | 0.151573E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13904.05 | 16-DEC-16:01 | 12249.77 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.924768E+11 | 0.00 | 6268.37 | 0.624544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.209065E+09 | 0.00 | 101.01 | 98846938.88 | 0.00 | 0.00 | 0.00 | 0.00 | 13904.05 | 12249.77 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.143877E+11 | 0.00 | 725.76 | 0.106904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16672.32 | 14140.25 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.234026E+11 | 0.00 | 515.34 | 0.134423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34975.98 | 08-JAN-14:00 | 29248.78 | 08-JAN-14:05 | 0.00 | 0.00 | 0.00 |
February | 0.306450E+11 | 0.00 | 577.74 | 0.178018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38407.96 | 20-FEB-13:50 | 35046.64 | 20-FEB-14:10 | 0.00 | 0.00 | 0.00 |
March | 0.474737E+11 | 0.00 | 743.33 | 0.284167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40649.88 | 13-MAR-13:30 | 38091.99 | 13-MAR-13:40 | 0.00 | 0.00 | 0.00 |
April | 0.591496E+11 | 0.00 | 720.00 | 0.386152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40856.19 | 15-APR-13:50 | 39696.41 | 15-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.653980E+11 | 0.00 | 744.00 | 0.427967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40990.00 | 04-MAY-17:20 | 39252.48 | 04-MAY-17:20 | 0.00 | 0.00 | 0.00 |
June | 0.618619E+11 | 0.00 | 720.00 | 0.389999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39707.18 | 12-JUN-17:20 | 36843.47 | 12-JUN-17:20 | 0.00 | 0.00 | 0.00 |
July | 0.622669E+11 | 0.00 | 743.17 | 0.370623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38016.53 | 08-JUL-08:00 | 32904.87 | 04-JUL-20:10 | 0.00 | 0.00 | 0.00 |
August | 0.594712E+11 | 0.00 | 744.00 | 0.337568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36309.01 | 07-AUG-16:20 | 29165.24 | 07-AUG-17:20 | 0.00 | 0.00 | 0.00 |
September | 0.581675E+11 | 0.00 | 717.97 | 0.355103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44485.15 | 26-SEP-15:02 | 40394.60 | 25-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.667148E+11 | 0.00 | 744.00 | 0.452637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47725.48 | 02-OCT-13:30 | 40406.82 | 08-OCT-12:00 | 0.00 | 0.00 | 0.00 |
November | 0.550607E+11 | 0.00 | 719.67 | 0.369770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46082.25 | 04-NOV-13:30 | 40563.87 | 02-NOV-13:05 | 0.00 | 0.00 | 0.00 |
December | 0.315606E+11 | 0.00 | 607.21 | 0.187764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40572.24 | 02-DEC-13:30 | 39158.79 | 02-DEC-13:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.621173E+12 | 0.00 | 8296.43 | 0.387419E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.234026E+11 | 0.00 | 515.34 | 0.134423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34975.98 | 29165.24 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.667148E+11 | 0.00 | 744.00 | 0.452637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47725.48 | 40563.87 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.894943E+10 | 0.00 | 314.48 | 0.421679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88936.53 | 14-JAN-16:01 | 80267.40 | 26-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.171292E+11 | 0.00 | 341.33 | 0.893412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95726.92 | 24-FEB-22:52 | 87756.24 | 21-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.407619E+11 | 0.00 | 463.89 | 0.252586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97834.92 | 10-MAR-09:51 | 89329.63 | 14-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.666016E+11 | 0.00 | 600.52 | 0.452124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100208.73 | 22-APR-08:11 | 93221.38 | 30-APR-07:51 | 0.00 | 0.00 | 0.00 |
May | 0.887475E+11 | 0.00 | 692.95 | 0.636151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110815.97 | 13-MAY-08:11 | 89533.72 | 30-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.887361E+11 | 0.00 | 671.27 | 0.627708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102459.57 | 18-JUN-06:52 | 89596.72 | 28-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.893342E+11 | 0.00 | 691.93 | 0.621389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97527.61 | 18-JUL-15:02 | 89552.27 | 29-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.826867E+11 | 0.00 | 684.94 | 0.557897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97416.89 | 16-AUG-15:02 | 89606.14 | 05-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.698769E+11 | 0.00 | 635.17 | 0.445230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 101159.67 | 09-SEP-15:02 | 89606.11 | 10-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.517488E+11 | 0.00 | 518.24 | 0.314696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110566.40 | 11-OCT-21:51 | 89154.15 | 14-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.267623E+11 | 0.00 | 382.13 | 0.146192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98551.39 | 05-NOV-15:01 | 88923.11 | 01-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.111376E+11 | 0.00 | 379.79 | 0.525821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89082.75 | 29-DEC-22:53 | 84580.73 | 28-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.642472E+12 | 0.00 | 6376.64 | 0.423806E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.894943E+10 | 0.00 | 314.48 | 0.421679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88936.53 | 80267.40 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.893342E+11 | 0.00 | 692.95 | 0.636151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110815.97 | 93221.38 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.138503E+10 | 0.00 | 348.46 | 0.655288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12551.27 | 18-JAN-16:01 | 11166.26 | 12-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.347403E+10 | 0.00 | 518.55 | 0.187344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12753.38 | 26-FEB-16:01 | 11495.80 | 24-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.791238E+10 | 0.00 | 708.50 | 0.499131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12391.02 | 18-MAR-08:62 | 11610.74 | 14-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.122012E+11 | 0.00 | 705.94 | 0.914192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11924.27 | 23-APR-08:61 | 11606.90 | 27-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.146974E+11 | 0.00 | 732.74 | 0.112664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12481.40 | 13-MAY-08:62 | 11616.24 | 24-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.136421E+11 | 0.00 | 706.27 | 0.101247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12862.96 | 25-JUN-08:61 | 11665.46 | 25-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.131101E+11 | 0.00 | 726.58 | 0.933440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12612.02 | 18-JUL-15:02 | 11678.19 | 22-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.120297E+11 | 0.00 | 724.11 | 0.829579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12696.08 | 20-AUG-08:62 | 11678.83 | 18-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.108638E+11 | 0.00 | 698.03 | 0.742324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13634.81 | 09-SEP-15:02 | 11671.72 | 15-SEP-08:62 | 0.00 | 0.00 | 0.00 |
October | 0.103469E+11 | 0.00 | 719.41 | 0.692972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12947.28 | 12-OCT-08:62 | 11627.34 | 23-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.633260E+10 | 0.00 | 676.79 | 0.365065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12130.33 | 18-NOV-09:02 | 11340.03 | 15-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.206703E+10 | 0.00 | 452.58 | 0.101257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11999.86 | 10-DEC-16:01 | 11138.54 | 03-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108062E+12 | 0.00 | 7717.95 | 0.746995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.138503E+10 | 0.00 | 348.46 | 0.655288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11924.27 | 11138.54 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.146974E+11 | 0.00 | 732.74 | 0.112664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13634.81 | 11678.83 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.256652E+09 | 0.00 | 103.51 | 0.107538E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12501.42 | 14-JAN-16:01 | 10770.56 | 12-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.141526E+10 | 0.00 | 289.86 | 0.665601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12972.79 | 26-FEB-16:01 | 11554.78 | 20-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.552806E+10 | 0.00 | 538.28 | 0.328293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14724.33 | 10-MAR-09:51 | 12171.01 | 28-MAR-08:51 | 0.00 | 0.00 | 0.00 |
April | 0.110080E+11 | 0.00 | 652.39 | 0.806373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14878.53 | 23-APR-08:41 | 13179.95 | 30-APR-07:51 | 0.00 | 0.00 | 0.00 |
May | 0.144767E+11 | 0.00 | 730.06 | 0.110833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15204.18 | 13-MAY-08:11 | 11623.82 | 24-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.136605E+11 | 0.00 | 705.00 | 0.101484E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13449.74 | 18-JUN-06:52 | 11679.51 | 04-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.130978E+11 | 0.00 | 726.70 | 0.931639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12638.43 | 18-JUL-15:02 | 11685.26 | 28-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.118245E+11 | 0.00 | 723.61 | 0.806297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12725.55 | 20-AUG-08:62 | 11664.13 | 15-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.100658E+11 | 0.00 | 693.56 | 0.648251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13689.59 | 09-SEP-15:02 | 11673.26 | 01-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.754657E+10 | 0.00 | 583.34 | 0.466309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15117.48 | 01-OCT-08:21 | 12257.80 | 15-OCT-08:51 | 0.00 | 0.00 | 0.00 |
November | 0.291690E+10 | 0.00 | 452.72 | 0.142022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14022.08 | 09-NOV-09:51 | 11553.37 | 01-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.451778E+09 | 0.00 | 150.09 | 0.196122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12335.45 | 16-DEC-16:01 | 11269.76 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.922485E+11 | 0.00 | 6349.13 | 0.634928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.256652E+09 | 0.00 | 103.51 | 0.107538E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12335.45 | 10770.56 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.144767E+11 | 0.00 | 730.06 | 0.110833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15204.18 | 13179.95 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.320344E+09 | 0.00 | 257.70 | 0.162029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3999.31 | 18-JAN-16:01 | 3330.25 | 12-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.770531E+09 | 0.00 | 434.30 | 0.398877E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3915.42 | 26-FEB-09:02 | 3419.79 | 24-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.194047E+10 | 0.00 | 687.02 | 0.119178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3936.19 | 10-MAR-09:01 | 3467.79 | 07-MAR-19:02 | 0.00 | 0.00 | 0.00 |
April | 0.318920E+10 | 0.00 | 695.94 | 0.230875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4177.06 | 23-APR-08:61 | 3503.61 | 20-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.391102E+10 | 0.00 | 728.20 | 0.291076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4019.14 | 13-MAY-08:62 | 3516.86 | 22-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.378606E+10 | 0.00 | 704.47 | 0.277832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4146.75 | 25-JUN-08:61 | 3505.43 | 24-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.347035E+10 | 0.00 | 724.79 | 0.239054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3975.54 | 23-JUL-08:62 | 3517.18 | 07-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.315491E+10 | 0.00 | 721.18 | 0.208724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4053.81 | 20-AUG-08:62 | 3504.73 | 11-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.283511E+10 | 0.00 | 692.51 | 0.183700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4127.25 | 09-SEP-15:02 | 3507.93 | 05-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.256131E+10 | 0.00 | 705.76 | 0.164377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4137.66 | 12-OCT-08:62 | 3515.39 | 06-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.146410E+10 | 0.00 | 633.41 | 0.815281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3927.18 | 18-NOV-09:02 | 3447.37 | 03-NOV-18:02 | 0.00 | 0.00 | 0.00 |
December | 0.448662E+09 | 0.00 | 338.52 | 0.208528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3758.30 | 10-DEC-16:01 | 3352.41 | 25-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.278521E+11 | 0.00 | 7323.82 | 0.187329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.320344E+09 | 0.00 | 257.70 | 0.162029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3758.30 | 3330.25 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.391102E+10 | 0.00 | 728.20 | 0.291076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4177.06 | 3517.18 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 34074785.69 | 0.00 | 43.59 | 18648407.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3945.78 | 14-JAN-16:01 | 3343.72 | 25-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.264597E+09 | 0.00 | 206.96 | 0.118238E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3999.77 | 14-FEB-16:01 | 3472.02 | 19-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.139130E+10 | 0.00 | 517.51 | 0.811954E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4250.93 | 10-MAR-09:51 | 3525.44 | 10-MAR-19:02 | 0.00 | 0.00 | 0.00 |
April | 0.290855E+10 | 0.00 | 645.38 | 0.209051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4375.79 | 03-APR-08:61 | 3734.40 | 30-APR-07:51 | 0.00 | 0.00 | 0.00 |
May | 0.385503E+10 | 0.00 | 725.82 | 0.285154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4706.10 | 13-MAY-08:11 | 3523.07 | 09-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.379136E+10 | 0.00 | 703.15 | 0.278210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4361.08 | 18-JUN-08:62 | 3515.51 | 24-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.346748E+10 | 0.00 | 724.91 | 0.238533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3988.20 | 23-JUL-08:62 | 3528.81 | 01-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.310127E+10 | 0.00 | 720.26 | 0.202934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4069.87 | 20-AUG-08:62 | 3518.13 | 11-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.262586E+10 | 0.00 | 686.63 | 0.163699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4169.44 | 27-SEP-08:62 | 3527.91 | 10-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.188118E+10 | 0.00 | 574.93 | 0.112205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4649.83 | 06-OCT-08:61 | 3522.01 | 14-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.634446E+09 | 0.00 | 396.75 | 0.296483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4096.97 | 09-NOV-09:51 | 3517.52 | 17-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 59130111.79 | 0.00 | 82.65 | 26203457.81 | 0.00 | 0.00 | 0.00 | 0.00 | 3873.32 | 10-DEC-16:01 | 3390.56 | 24-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.240143E+11 | 0.00 | 6028.55 | 0.161694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 34074785.69 | 0.00 | 43.59 | 18648407.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3873.32 | 3343.72 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.385503E+10 | 0.00 | 725.82 | 0.285154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4706.10 | 3734.40 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.569563E+10 | 0.00 | 522.05 | 0.370669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18364.65 | 17-JAN-16:01 | 15691.75 | 11-JAN-19:01 | 0.00 | 0.00 | 0.00 |
February | 0.770991E+10 | 0.00 | 572.00 | 0.505863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17896.40 | 25-FEB-19:01 | 15524.77 | 25-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.125172E+11 | 0.00 | 700.26 | 0.835405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17480.15 | 18-MAR-18:01 | 16316.70 | 09-MAR-19:02 | 0.00 | 0.00 | 0.00 |
April | 0.161605E+11 | 0.00 | 694.63 | 0.117307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18137.48 | 23-APR-08:61 | 16310.75 | 23-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.184974E+11 | 0.00 | 724.22 | 0.136439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18302.47 | 13-MAY-08:62 | 16466.51 | 31-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.177513E+11 | 0.00 | 700.22 | 0.128137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18397.31 | 18-JUN-08:62 | 16470.59 | 04-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.175704E+11 | 0.00 | 722.12 | 0.123844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17957.90 | 18-JUL-15:02 | 16403.21 | 22-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.166179E+11 | 0.00 | 719.14 | 0.114881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17661.28 | 20-AUG-08:62 | 16448.05 | 03-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.158508E+11 | 0.00 | 693.68 | 0.108749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18942.43 | 09-SEP-15:02 | 16460.14 | 13-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.172560E+11 | 0.00 | 715.93 | 0.121877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18926.19 | 12-OCT-08:62 | 16387.30 | 13-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.135132E+11 | 0.00 | 684.75 | 0.938689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16947.82 | 18-NOV-09:02 | 16316.47 | 09-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.735324E+10 | 0.00 | 630.57 | 0.487386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16666.35 | 29-DEC-16:01 | 15399.19 | 26-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166494E+12 | 0.00 | 8079.58 | 0.116503E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.569563E+10 | 0.00 | 522.05 | 0.370669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16666.35 | 15399.19 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.184974E+11 | 0.00 | 724.22 | 0.136439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18942.43 | 16470.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 486.92 | 296.38 | 190.53 | 722.27 | 372.02 | 0.00 | 0.00 | 0.00 |
February | 461.95 | 256.60 | 205.36 | 746.95 | 287.73 | 0.00 | 0.00 | 0.00 |
March | 392.53 | 172.13 | 220.40 | 740.73 | 168.67 | 0.00 | 0.00 | 0.00 |
April | 279.85 | 80.71 | 199.14 | 706.99 | 51.44 | 0.00 | 0.00 | 0.00 |
May | 201.74 | 16.99 | 184.75 | 668.89 | 4.64 | 0.00 | 0.00 | 0.00 |
June | 182.47 | 3.17 | 179.30 | 658.57 | 3.65 | 0.00 | 0.00 | 0.00 |
July | 189.53 | 1.86 | 187.67 | 619.74 | 0.43 | 0.00 | 0.00 | 0.00 |
August | 199.84 | 8.76 | 191.08 | 576.40 | 1.21 | 0.00 | 0.00 | 0.00 |
September | 276.52 | 76.14 | 200.39 | 657.80 | 11.38 | 0.00 | 0.00 | 0.00 |
October | 468.15 | 262.57 | 205.58 | 931.86 | 131.47 | 0.00 | 0.00 | 0.00 |
November | 584.11 | 386.97 | 197.14 | 1015.40 | 266.30 | 0.00 | 0.00 | 0.00 |
December | 519.61 | 325.86 | 193.74 | 802.29 | 363.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 352.96 | 156.75 | 196.21 | 737.00 | 137.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 182.47 | 1.86 | 179.30 | 576.40 | 0.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 584.11 | 386.97 | 220.40 | 1015.40 | 372.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1371.13 | 834.60 | 536.53 | 1982.85 | 1166.13 | 0.00 | 0.00 | 0.00 |
February | 1300.83 | 722.56 | 578.27 | 2056.47 | 912.47 | 0.00 | 0.00 | 0.00 |
March | 1105.33 | 484.70 | 620.63 | 2055.22 | 531.31 | 0.00 | 0.00 | 0.00 |
April | 788.04 | 227.26 | 560.78 | 1982.76 | 158.34 | 0.00 | 0.00 | 0.00 |
May | 568.09 | 47.85 | 520.24 | 1888.36 | 15.20 | 0.00 | 0.00 | 0.00 |
June | 513.82 | 8.93 | 504.89 | 1857.59 | 13.83 | 0.00 | 0.00 | 0.00 |
July | 533.70 | 5.23 | 528.47 | 1743.52 | 1.82 | 0.00 | 0.00 | 0.00 |
August | 562.73 | 24.66 | 538.06 | 1618.09 | 6.00 | 0.00 | 0.00 | 0.00 |
September | 778.67 | 214.40 | 564.27 | 1826.08 | 39.94 | 0.00 | 0.00 | 0.00 |
October | 1318.29 | 739.38 | 578.90 | 2603.82 | 397.38 | 0.00 | 0.00 | 0.00 |
November | 1644.82 | 1089.67 | 555.15 | 2824.05 | 819.42 | 0.00 | 0.00 | 0.00 |
December | 1463.18 | 917.61 | 545.57 | 2205.37 | 1140.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 993.92 | 441.41 | 552.51 | 2052.91 | 431.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 513.82 | 5.23 | 504.89 | 1618.09 | 1.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1644.82 | 1089.67 | 620.63 | 2824.05 | 1166.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1781.18 | 1084.19 | 696.99 | 2638.30 | 1570.93 | 0.00 | 0.00 | 0.00 |
February | 1689.86 | 938.65 | 751.21 | 2744.94 | 1215.93 | 0.00 | 0.00 | 0.00 |
March | 1435.89 | 629.66 | 806.23 | 2754.26 | 693.73 | 0.00 | 0.00 | 0.00 |
April | 1023.70 | 295.22 | 728.48 | 2676.83 | 202.02 | 0.00 | 0.00 | 0.00 |
May | 737.99 | 62.16 | 675.82 | 2557.97 | 18.55 | 0.00 | 0.00 | 0.00 |
June | 667.49 | 11.61 | 655.88 | 2508.86 | 17.05 | 0.00 | 0.00 | 0.00 |
July | 693.30 | 6.79 | 686.52 | 2348.99 | 2.41 | 0.00 | 0.00 | 0.00 |
August | 731.01 | 32.04 | 698.98 | 2175.06 | 7.41 | 0.00 | 0.00 | 0.00 |
September | 1011.54 | 278.51 | 733.03 | 2444.54 | 48.03 | 0.00 | 0.00 | 0.00 |
October | 1712.53 | 960.50 | 752.03 | 3472.93 | 510.74 | 0.00 | 0.00 | 0.00 |
November | 2136.72 | 1415.55 | 721.17 | 3760.30 | 1071.59 | 0.00 | 0.00 | 0.00 |
December | 1900.75 | 1192.03 | 708.72 | 2935.73 | 1526.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1291.15 | 573.42 | 717.74 | 2750.56 | 571.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 667.49 | 6.79 | 655.88 | 2175.06 | 2.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2136.72 | 1415.55 | 806.23 | 3760.30 | 1570.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.27 | 58.60 | 37.67 | 146.06 | 71.35 | 0.00 | 0.00 | 0.00 |
February | 91.34 | 50.73 | 40.60 | 151.48 | 52.99 | 0.00 | 0.00 | 0.00 |
March | 77.61 | 34.03 | 43.58 | 152.67 | 26.52 | 0.00 | 0.00 | 0.00 |
April | 55.33 | 15.96 | 39.37 | 153.65 | 5.21 | 0.00 | 0.00 | 0.00 |
May | 39.89 | 3.36 | 36.53 | 154.61 | 0.05 | 0.00 | 0.00 | 0.00 |
June | 36.08 | 0.63 | 35.45 | 152.37 | 0.20 | 0.00 | 0.00 | 0.00 |
July | 37.47 | 0.37 | 37.11 | 145.59 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 39.51 | 1.73 | 37.78 | 134.88 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54.67 | 15.05 | 39.62 | 147.14 | 0.35 | 0.00 | 0.00 | 0.00 |
October | 92.56 | 51.91 | 40.65 | 193.87 | 17.61 | 0.00 | 0.00 | 0.00 |
November | 115.49 | 76.51 | 38.98 | 207.95 | 45.84 | 0.00 | 0.00 | 0.00 |
December | 102.74 | 64.43 | 38.31 | 162.97 | 69.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 69.79 | 30.99 | 38.79 | 158.59 | 23.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.08 | 0.37 | 35.45 | 134.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.49 | 76.51 | 43.58 | 207.95 | 71.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.60 | 32.14 | 50.46 | 105.36 | 145.61 | 0.00 | 0.00 | 0.00 |
February | 94.69 | 34.99 | 59.71 | 143.76 | 105.28 | 0.00 | 0.00 | 0.00 |
March | 122.73 | 49.19 | 73.54 | 229.77 | 50.61 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 69.63 | 79.05 | 355.03 | 9.71 | 0.00 | 0.00 | 0.00 |
May | 140.95 | 59.79 | 81.16 | 410.75 | 0.09 | 0.00 | 0.00 | 0.00 |
June | 132.61 | 51.65 | 80.96 | 411.06 | 0.35 | 0.00 | 0.00 | 0.00 |
July | 98.15 | 19.02 | 79.13 | 326.90 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 90.10 | 15.88 | 74.22 | 281.38 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 99.49 | 29.42 | 70.07 | 262.31 | 0.65 | 0.00 | 0.00 | 0.00 |
October | 103.47 | 41.31 | 62.16 | 223.74 | 33.67 | 0.00 | 0.00 | 0.00 |
November | 93.49 | 39.90 | 53.59 | 163.95 | 90.24 | 0.00 | 0.00 | 0.00 |
December | 79.77 | 30.33 | 49.44 | 106.50 | 138.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.21 | 39.38 | 67.82 | 252.09 | 47.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 79.77 | 15.88 | 49.44 | 105.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 148.68 | 69.63 | 81.16 | 411.06 | 145.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.11 | 0.00 | 21.11 | 16.44 | 77.53 | 0.00 | 0.00 | 0.00 |
February | 25.03 | 0.00 | 25.03 | 30.12 | 57.09 | 0.00 | 0.00 | 0.00 |
March | 30.17 | 0.00 | 30.17 | 56.05 | 28.62 | 0.00 | 0.00 | 0.00 |
April | 32.88 | 0.22 | 32.67 | 100.84 | 5.42 | 0.00 | 0.00 | 0.00 |
May | 36.33 | 1.07 | 35.26 | 145.09 | 0.05 | 0.00 | 0.00 | 0.00 |
June | 37.52 | 1.37 | 36.15 | 155.18 | 0.21 | 0.00 | 0.00 | 0.00 |
July | 37.12 | 0.67 | 36.45 | 145.06 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 34.07 | 0.15 | 33.91 | 123.14 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30.29 | 0.00 | 30.28 | 96.67 | 0.35 | 0.00 | 0.00 | 0.00 |
October | 26.23 | 0.00 | 26.23 | 62.72 | 18.72 | 0.00 | 0.00 | 0.00 |
November | 22.22 | 0.00 | 22.22 | 34.39 | 49.21 | 0.00 | 0.00 | 0.00 |
December | 20.59 | 0.00 | 20.59 | 18.41 | 73.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.49 | 0.29 | 29.19 | 82.27 | 25.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.59 | 0.00 | 20.59 | 16.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 37.52 | 1.37 | 36.45 | 155.18 | 77.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.60 | 32.14 | 50.46 | 110.65 | 142.29 | 0.00 | 0.00 | 0.00 |
February | 94.69 | 34.99 | 59.71 | 146.84 | 105.72 | 0.00 | 0.00 | 0.00 |
March | 122.73 | 49.19 | 73.54 | 230.91 | 53.10 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 69.63 | 79.05 | 355.69 | 10.12 | 0.00 | 0.00 | 0.00 |
May | 140.95 | 59.79 | 81.16 | 411.13 | 0.09 | 0.00 | 0.00 | 0.00 |
June | 132.61 | 51.65 | 80.96 | 410.96 | 0.37 | 0.00 | 0.00 | 0.00 |
July | 98.15 | 19.02 | 79.13 | 326.93 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 90.10 | 15.88 | 74.22 | 281.82 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 99.49 | 29.42 | 70.07 | 263.92 | 0.62 | 0.00 | 0.00 | 0.00 |
October | 103.47 | 41.31 | 62.16 | 225.43 | 34.75 | 0.00 | 0.00 | 0.00 |
November | 93.49 | 39.90 | 53.59 | 167.45 | 91.41 | 0.00 | 0.00 | 0.00 |
December | 79.77 | 30.33 | 49.44 | 111.89 | 135.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.21 | 39.38 | 67.82 | 254.01 | 47.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 79.77 | 15.88 | 49.44 | 110.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 148.68 | 69.63 | 81.16 | 411.13 | 142.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.00 | 46.87 | 30.13 | 101.74 | 85.70 | 0.00 | 0.00 | 0.00 |
February | 73.05 | 40.58 | 32.48 | 106.25 | 68.89 | 0.00 | 0.00 | 0.00 |
March | 62.08 | 27.22 | 34.85 | 106.64 | 42.88 | 0.00 | 0.00 | 0.00 |
April | 44.26 | 12.76 | 31.49 | 101.77 | 16.54 | 0.00 | 0.00 | 0.00 |
May | 31.90 | 2.69 | 29.22 | 93.98 | 3.76 | 0.00 | 0.00 | 0.00 |
June | 28.86 | 0.50 | 28.35 | 90.70 | 2.71 | 0.00 | 0.00 | 0.00 |
July | 29.97 | 0.29 | 29.68 | 82.82 | 1.13 | 0.00 | 0.00 | 0.00 |
August | 31.60 | 1.39 | 30.22 | 76.63 | 3.12 | 0.00 | 0.00 | 0.00 |
September | 43.73 | 12.04 | 31.69 | 91.48 | 9.46 | 0.00 | 0.00 | 0.00 |
October | 74.04 | 41.52 | 32.51 | 139.34 | 33.57 | 0.00 | 0.00 | 0.00 |
November | 92.37 | 61.20 | 31.18 | 151.89 | 60.69 | 0.00 | 0.00 | 0.00 |
December | 82.17 | 51.53 | 30.64 | 114.89 | 82.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.82 | 24.79 | 31.03 | 104.79 | 34.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.86 | 0.29 | 28.35 | 76.63 | 1.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.37 | 61.20 | 34.85 | 151.89 | 85.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.89 | 0.00 | 16.89 | 13.21 | 63.50 | 0.00 | 0.00 | 0.00 |
February | 20.03 | 0.00 | 20.03 | 25.20 | 45.65 | 0.00 | 0.00 | 0.00 |
March | 24.14 | 0.00 | 24.14 | 47.84 | 21.29 | 0.00 | 0.00 | 0.00 |
April | 26.31 | 0.17 | 26.14 | 87.22 | 3.32 | 0.00 | 0.00 | 0.00 |
May | 29.07 | 0.85 | 28.21 | 124.39 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30.02 | 1.10 | 28.92 | 132.10 | 0.05 | 0.00 | 0.00 | 0.00 |
July | 29.70 | 0.54 | 29.16 | 122.94 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 27.26 | 0.12 | 27.13 | 104.79 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 24.23 | 0.00 | 24.23 | 83.34 | 0.11 | 0.00 | 0.00 | 0.00 |
October | 20.99 | 0.00 | 20.99 | 53.79 | 13.13 | 0.00 | 0.00 | 0.00 |
November | 17.78 | 0.00 | 17.78 | 29.41 | 38.01 | 0.00 | 0.00 | 0.00 |
December | 16.48 | 0.00 | 16.48 | 15.04 | 59.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.59 | 0.23 | 23.36 | 70.16 | 20.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.48 | 0.00 | 16.48 | 13.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 30.02 | 1.10 | 29.16 | 132.10 | 63.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.32 | 33.80 | 50.53 | 96.37 | 134.28 | 0.00 | 0.00 | 0.00 |
February | 102.73 | 42.41 | 60.31 | 149.58 | 97.24 | 0.00 | 0.00 | 0.00 |
March | 125.37 | 51.83 | 73.54 | 232.42 | 47.13 | 0.00 | 0.00 | 0.00 |
April | 149.22 | 69.57 | 79.65 | 357.34 | 9.15 | 0.00 | 0.00 | 0.00 |
May | 146.62 | 65.07 | 81.55 | 421.27 | 0.06 | 0.00 | 0.00 | 0.00 |
June | 119.07 | 39.40 | 79.67 | 386.29 | 0.34 | 0.00 | 0.00 | 0.00 |
July | 99.94 | 20.89 | 79.05 | 329.58 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 90.32 | 15.72 | 74.61 | 281.22 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 96.33 | 26.76 | 69.57 | 256.65 | 0.60 | 0.00 | 0.00 | 0.00 |
October | 105.39 | 42.46 | 62.93 | 225.89 | 32.02 | 0.00 | 0.00 | 0.00 |
November | 93.33 | 39.90 | 53.43 | 156.88 | 84.17 | 0.00 | 0.00 | 0.00 |
December | 81.70 | 32.44 | 49.26 | 102.00 | 131.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.83 | 39.96 | 67.87 | 250.01 | 44.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 81.70 | 15.72 | 49.26 | 96.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.22 | 69.57 | 81.55 | 421.27 | 134.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.27 | 58.60 | 37.67 | 145.23 | 71.08 | 0.00 | 0.00 | 0.00 |
February | 91.34 | 50.73 | 40.60 | 150.54 | 52.82 | 0.00 | 0.00 | 0.00 |
March | 77.61 | 34.03 | 43.58 | 151.99 | 26.26 | 0.00 | 0.00 | 0.00 |
April | 55.33 | 15.96 | 39.37 | 153.40 | 5.08 | 0.00 | 0.00 | 0.00 |
May | 39.89 | 3.36 | 36.53 | 154.48 | 0.04 | 0.00 | 0.00 | 0.00 |
June | 36.08 | 0.63 | 35.45 | 152.80 | 0.19 | 0.00 | 0.00 | 0.00 |
July | 37.47 | 0.37 | 37.11 | 145.52 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 39.51 | 1.73 | 37.78 | 134.84 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54.67 | 15.05 | 39.62 | 147.20 | 0.33 | 0.00 | 0.00 | 0.00 |
October | 92.56 | 51.91 | 40.65 | 193.51 | 17.39 | 0.00 | 0.00 | 0.00 |
November | 115.49 | 76.51 | 38.98 | 207.45 | 45.54 | 0.00 | 0.00 | 0.00 |
December | 102.74 | 64.43 | 38.31 | 162.30 | 68.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 69.79 | 30.99 | 38.79 | 158.26 | 23.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.08 | 0.37 | 35.45 | 134.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.49 | 76.51 | 43.58 | 207.45 | 71.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.11 | 0.00 | 21.11 | 15.90 | 77.01 | 0.00 | 0.00 | 0.00 |
February | 25.03 | 0.00 | 25.03 | 29.08 | 56.89 | 0.00 | 0.00 | 0.00 |
March | 30.17 | 0.00 | 30.17 | 54.94 | 28.37 | 0.00 | 0.00 | 0.00 |
April | 32.88 | 0.22 | 32.67 | 100.32 | 5.29 | 0.00 | 0.00 | 0.00 |
May | 36.33 | 1.07 | 35.26 | 144.92 | 0.04 | 0.00 | 0.00 | 0.00 |
June | 37.52 | 1.37 | 36.15 | 155.60 | 0.19 | 0.00 | 0.00 | 0.00 |
July | 37.12 | 0.67 | 36.45 | 144.99 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 34.07 | 0.15 | 33.91 | 123.10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30.29 | 0.00 | 30.28 | 96.70 | 0.33 | 0.00 | 0.00 | 0.00 |
October | 26.23 | 0.00 | 26.23 | 62.08 | 18.51 | 0.00 | 0.00 | 0.00 |
November | 22.22 | 0.00 | 22.22 | 33.47 | 48.78 | 0.00 | 0.00 | 0.00 |
December | 20.59 | 0.00 | 20.59 | 17.74 | 73.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.49 | 0.29 | 29.19 | 81.84 | 25.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.59 | 0.00 | 20.59 | 15.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 37.52 | 1.37 | 36.45 | 155.60 | 77.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.32 | 33.80 | 50.53 | 102.21 | 130.54 | 0.00 | 0.00 | 0.00 |
February | 102.73 | 42.41 | 60.31 | 152.66 | 97.71 | 0.00 | 0.00 | 0.00 |
March | 125.37 | 51.83 | 73.54 | 232.12 | 49.27 | 0.00 | 0.00 | 0.00 |
April | 149.22 | 69.57 | 79.65 | 357.19 | 9.40 | 0.00 | 0.00 | 0.00 |
May | 146.62 | 65.07 | 81.55 | 421.62 | 0.06 | 0.00 | 0.00 | 0.00 |
June | 119.07 | 39.40 | 79.67 | 386.19 | 0.36 | 0.00 | 0.00 | 0.00 |
July | 99.94 | 20.89 | 79.05 | 329.61 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 90.32 | 15.72 | 74.61 | 281.65 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 96.33 | 26.76 | 69.57 | 258.24 | 0.56 | 0.00 | 0.00 | 0.00 |
October | 105.39 | 42.46 | 62.93 | 226.60 | 32.81 | 0.00 | 0.00 | 0.00 |
November | 93.33 | 39.90 | 53.43 | 159.54 | 85.11 | 0.00 | 0.00 | 0.00 |
December | 81.70 | 32.44 | 49.26 | 107.32 | 127.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.83 | 39.96 | 67.87 | 251.63 | 44.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 81.70 | 15.72 | 49.26 | 102.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 149.22 | 69.57 | 81.55 | 421.62 | 130.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.73 | 0.00 | 26.73 | 20.44 | 103.65 | 0.00 | 0.00 | 0.00 |
February | 31.70 | 0.00 | 31.70 | 38.77 | 76.60 | 0.00 | 0.00 | 0.00 |
March | 38.21 | 0.00 | 38.21 | 71.46 | 41.07 | 0.00 | 0.00 | 0.00 |
April | 41.64 | 0.27 | 41.37 | 122.82 | 10.98 | 0.00 | 0.00 | 0.00 |
May | 46.01 | 1.35 | 44.65 | 173.00 | 0.69 | 0.00 | 0.00 | 0.00 |
June | 47.52 | 1.74 | 45.78 | 185.64 | 0.75 | 0.00 | 0.00 | 0.00 |
July | 47.01 | 0.85 | 46.16 | 170.95 | 0.10 | 0.00 | 0.00 | 0.00 |
August | 43.14 | 0.20 | 42.95 | 143.42 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 38.36 | 0.00 | 38.35 | 111.89 | 1.77 | 0.00 | 0.00 | 0.00 |
October | 33.22 | 0.00 | 33.22 | 76.68 | 31.19 | 0.00 | 0.00 | 0.00 |
November | 28.14 | 0.00 | 28.14 | 42.42 | 69.51 | 0.00 | 0.00 | 0.00 |
December | 26.08 | 0.00 | 26.08 | 22.40 | 100.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.34 | 0.37 | 36.97 | 98.62 | 36.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.08 | 0.00 | 26.08 | 20.44 | 0.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.52 | 1.74 | 46.16 | 185.64 | 103.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.86 | 0.00 | 9.86 | 7.54 | 38.21 | 0.00 | 0.00 | 0.00 |
February | 11.69 | 0.00 | 11.69 | 14.29 | 28.24 | 0.00 | 0.00 | 0.00 |
March | 14.08 | 0.00 | 14.08 | 26.34 | 15.14 | 0.00 | 0.00 | 0.00 |
April | 15.35 | 0.10 | 15.25 | 45.28 | 4.05 | 0.00 | 0.00 | 0.00 |
May | 16.96 | 0.50 | 16.46 | 63.78 | 0.25 | 0.00 | 0.00 | 0.00 |
June | 17.52 | 0.64 | 16.88 | 68.44 | 0.28 | 0.00 | 0.00 | 0.00 |
July | 17.33 | 0.31 | 17.02 | 63.02 | 0.04 | 0.00 | 0.00 | 0.00 |
August | 15.90 | 0.07 | 15.83 | 52.87 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 14.14 | 0.00 | 14.14 | 41.25 | 0.65 | 0.00 | 0.00 | 0.00 |
October | 12.25 | 0.00 | 12.25 | 28.27 | 11.50 | 0.00 | 0.00 | 0.00 |
November | 10.37 | 0.00 | 10.37 | 15.64 | 25.62 | 0.00 | 0.00 | 0.00 |
December | 9.61 | 0.00 | 9.61 | 8.26 | 37.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 13.77 | 0.14 | 13.63 | 36.36 | 13.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.61 | 0.00 | 9.61 | 7.54 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 17.52 | 0.64 | 17.02 | 68.44 | 38.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.92 | 27.34 | 17.58 | 69.33 | 34.39 | 0.00 | 0.00 | 0.00 |
February | 42.62 | 23.67 | 18.95 | 71.62 | 26.43 | 0.00 | 0.00 | 0.00 |
March | 36.21 | 15.88 | 20.33 | 71.50 | 14.77 | 0.00 | 0.00 | 0.00 |
April | 25.82 | 7.45 | 18.37 | 69.94 | 4.08 | 0.00 | 0.00 | 0.00 |
May | 18.61 | 1.57 | 17.04 | 68.26 | 0.26 | 0.00 | 0.00 | 0.00 |
June | 16.83 | 0.29 | 16.54 | 67.07 | 0.28 | 0.00 | 0.00 | 0.00 |
July | 17.48 | 0.17 | 17.31 | 63.24 | 0.04 | 0.00 | 0.00 | 0.00 |
August | 18.44 | 0.81 | 17.63 | 58.40 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 25.51 | 7.02 | 18.49 | 65.05 | 0.64 | 0.00 | 0.00 | 0.00 |
October | 43.19 | 24.22 | 18.97 | 89.59 | 11.21 | 0.00 | 0.00 | 0.00 |
November | 53.89 | 35.70 | 18.19 | 97.20 | 24.21 | 0.00 | 0.00 | 0.00 |
December | 47.94 | 30.06 | 17.87 | 76.97 | 33.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.56 | 14.46 | 18.10 | 72.33 | 12.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.83 | 0.17 | 16.54 | 58.40 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.89 | 35.70 | 20.33 | 97.20 | 34.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.92 | 74.21 | 47.71 | 188.18 | 93.35 | 0.00 | 0.00 | 0.00 |
February | 115.67 | 64.25 | 51.42 | 194.39 | 71.73 | 0.00 | 0.00 | 0.00 |
March | 98.29 | 43.10 | 55.19 | 194.07 | 40.10 | 0.00 | 0.00 | 0.00 |
April | 70.07 | 20.21 | 49.87 | 189.82 | 11.07 | 0.00 | 0.00 | 0.00 |
May | 50.52 | 4.26 | 46.26 | 185.27 | 0.70 | 0.00 | 0.00 | 0.00 |
June | 45.69 | 0.79 | 44.90 | 182.05 | 0.76 | 0.00 | 0.00 | 0.00 |
July | 47.46 | 0.46 | 46.99 | 171.65 | 0.10 | 0.00 | 0.00 | 0.00 |
August | 50.04 | 2.19 | 47.85 | 158.52 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 69.24 | 19.06 | 50.18 | 176.57 | 1.73 | 0.00 | 0.00 | 0.00 |
October | 117.22 | 65.75 | 51.48 | 243.17 | 30.42 | 0.00 | 0.00 | 0.00 |
November | 146.26 | 96.90 | 49.36 | 263.82 | 65.72 | 0.00 | 0.00 | 0.00 |
December | 130.11 | 81.60 | 48.51 | 208.91 | 92.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.38 | 39.25 | 49.13 | 196.31 | 33.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 45.69 | 0.46 | 44.90 | 158.52 | 0.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 146.26 | 96.90 | 55.19 | 263.82 | 93.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.27 | 58.60 | 37.67 | 145.36 | 70.20 | 0.00 | 0.00 | 0.00 |
February | 91.34 | 50.73 | 40.60 | 150.33 | 52.11 | 0.00 | 0.00 | 0.00 |
March | 77.61 | 34.03 | 43.58 | 151.46 | 25.86 | 0.00 | 0.00 | 0.00 |
April | 55.33 | 15.96 | 39.37 | 152.62 | 4.91 | 0.00 | 0.00 | 0.00 |
May | 39.89 | 3.36 | 36.53 | 154.28 | 0.03 | 0.00 | 0.00 | 0.00 |
June | 36.08 | 0.63 | 35.45 | 151.63 | 0.21 | 0.00 | 0.00 | 0.00 |
July | 37.47 | 0.37 | 37.11 | 145.32 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 39.51 | 1.73 | 37.78 | 134.35 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54.67 | 15.05 | 39.62 | 146.35 | 0.30 | 0.00 | 0.00 | 0.00 |
October | 92.56 | 51.91 | 40.65 | 192.83 | 17.02 | 0.00 | 0.00 | 0.00 |
November | 115.49 | 76.51 | 38.98 | 207.05 | 44.91 | 0.00 | 0.00 | 0.00 |
December | 102.74 | 64.43 | 38.31 | 162.46 | 67.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 69.79 | 30.99 | 38.79 | 157.83 | 23.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.08 | 0.37 | 35.45 | 134.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.49 | 76.51 | 43.58 | 207.05 | 70.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.60 | 32.14 | 50.46 | 104.15 | 142.81 | 0.00 | 0.00 | 0.00 |
February | 94.69 | 34.99 | 59.71 | 142.05 | 103.25 | 0.00 | 0.00 | 0.00 |
March | 122.73 | 49.19 | 73.54 | 227.59 | 49.23 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 69.63 | 79.05 | 352.85 | 9.13 | 0.00 | 0.00 | 0.00 |
May | 140.95 | 59.79 | 81.16 | 409.44 | 0.06 | 0.00 | 0.00 | 0.00 |
June | 132.61 | 51.65 | 80.96 | 408.94 | 0.36 | 0.00 | 0.00 | 0.00 |
July | 98.15 | 19.02 | 79.13 | 325.71 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 90.10 | 15.88 | 74.22 | 280.21 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 99.49 | 29.42 | 70.07 | 261.00 | 0.55 | 0.00 | 0.00 | 0.00 |
October | 103.47 | 41.31 | 62.16 | 222.33 | 32.48 | 0.00 | 0.00 | 0.00 |
November | 93.49 | 39.90 | 53.59 | 162.82 | 88.20 | 0.00 | 0.00 | 0.00 |
December | 79.77 | 30.33 | 49.44 | 105.73 | 135.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.21 | 39.38 | 67.82 | 250.62 | 46.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 79.77 | 15.88 | 49.44 | 104.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 148.68 | 69.63 | 81.16 | 409.44 | 142.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.11 | 0.00 | 21.11 | 16.53 | 75.92 | 0.00 | 0.00 | 0.00 |
February | 25.03 | 0.00 | 25.03 | 29.91 | 56.04 | 0.00 | 0.00 | 0.00 |
March | 30.17 | 0.00 | 30.17 | 55.66 | 27.87 | 0.00 | 0.00 | 0.00 |
April | 32.88 | 0.22 | 32.67 | 100.51 | 5.06 | 0.00 | 0.00 | 0.00 |
May | 36.33 | 1.07 | 35.26 | 144.87 | 0.03 | 0.00 | 0.00 | 0.00 |
June | 37.52 | 1.37 | 36.15 | 154.40 | 0.21 | 0.00 | 0.00 | 0.00 |
July | 37.12 | 0.67 | 36.45 | 144.71 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 34.07 | 0.15 | 33.91 | 122.74 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30.29 | 0.00 | 30.28 | 96.39 | 0.29 | 0.00 | 0.00 | 0.00 |
October | 26.23 | 0.00 | 26.23 | 62.51 | 17.90 | 0.00 | 0.00 | 0.00 |
November | 22.22 | 0.00 | 22.22 | 34.45 | 47.85 | 0.00 | 0.00 | 0.00 |
December | 20.59 | 0.00 | 20.59 | 18.68 | 72.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.49 | 0.29 | 29.19 | 82.05 | 25.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.59 | 0.00 | 20.59 | 16.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 37.52 | 1.37 | 36.45 | 154.40 | 75.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.60 | 32.14 | 50.46 | 110.03 | 139.19 | 0.00 | 0.00 | 0.00 |
February | 94.69 | 34.99 | 59.71 | 145.45 | 103.67 | 0.00 | 0.00 | 0.00 |
March | 122.73 | 49.19 | 73.54 | 228.98 | 51.70 | 0.00 | 0.00 | 0.00 |
April | 148.68 | 69.63 | 79.05 | 353.64 | 9.42 | 0.00 | 0.00 | 0.00 |
May | 140.95 | 59.79 | 81.16 | 409.83 | 0.06 | 0.00 | 0.00 | 0.00 |
June | 132.61 | 51.65 | 80.96 | 408.83 | 0.37 | 0.00 | 0.00 | 0.00 |
July | 98.15 | 19.02 | 79.13 | 325.74 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 90.10 | 15.88 | 74.22 | 280.66 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 99.49 | 29.42 | 70.07 | 262.70 | 0.52 | 0.00 | 0.00 | 0.00 |
October | 103.47 | 41.31 | 62.16 | 224.41 | 33.18 | 0.00 | 0.00 | 0.00 |
November | 93.49 | 39.90 | 53.59 | 166.91 | 88.80 | 0.00 | 0.00 | 0.00 |
December | 79.77 | 30.33 | 49.44 | 111.90 | 131.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107.21 | 39.38 | 67.82 | 252.80 | 46.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 79.77 | 15.88 | 49.44 | 110.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 148.68 | 69.63 | 81.16 | 409.83 | 139.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.19 | 85.94 | 55.25 | 207.93 | 107.44 | 0.00 | 0.00 | 0.00 |
February | 133.95 | 74.41 | 59.55 | 217.54 | 78.59 | 0.00 | 0.00 | 0.00 |
March | 113.82 | 49.91 | 63.91 | 222.50 | 37.52 | 0.00 | 0.00 | 0.00 |
April | 81.15 | 23.40 | 57.75 | 229.22 | 6.46 | 0.00 | 0.00 | 0.00 |
May | 58.50 | 4.93 | 53.57 | 234.70 | 0.01 | 0.00 | 0.00 | 0.00 |
June | 52.91 | 0.92 | 51.99 | 230.72 | 0.20 | 0.00 | 0.00 | 0.00 |
July | 54.96 | 0.54 | 54.42 | 219.38 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 57.95 | 2.54 | 55.41 | 202.12 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 80.18 | 22.08 | 58.11 | 218.37 | 0.35 | 0.00 | 0.00 | 0.00 |
October | 135.75 | 76.14 | 59.61 | 282.81 | 24.75 | 0.00 | 0.00 | 0.00 |
November | 169.38 | 112.21 | 57.17 | 301.03 | 67.58 | 0.00 | 0.00 | 0.00 |
December | 150.67 | 94.49 | 56.18 | 233.42 | 103.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 102.35 | 45.45 | 56.89 | 233.32 | 35.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.91 | 0.54 | 51.99 | 202.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 169.38 | 112.21 | 63.91 | 301.03 | 107.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 147.76 | 0.00 | 147.76 | 78.63 | 677.79 | 0.00 | 0.00 | 0.00 |
February | 175.22 | 0.00 | 175.22 | 172.54 | 503.04 | 0.00 | 0.00 | 0.00 |
March | 211.18 | 0.01 | 211.17 | 351.63 | 270.15 | 0.00 | 0.00 | 0.00 |
April | 230.18 | 1.51 | 228.66 | 639.15 | 75.44 | 0.00 | 0.00 | 0.00 |
May | 254.28 | 7.47 | 246.81 | 911.55 | 6.80 | 0.00 | 0.00 | 0.00 |
June | 262.66 | 9.62 | 253.04 | 975.36 | 7.45 | 0.00 | 0.00 | 0.00 |
July | 259.84 | 4.71 | 255.13 | 891.76 | 0.89 | 0.00 | 0.00 | 0.00 |
August | 238.46 | 1.08 | 237.38 | 739.82 | 2.80 | 0.00 | 0.00 | 0.00 |
September | 212.00 | 0.02 | 211.98 | 563.99 | 18.14 | 0.00 | 0.00 | 0.00 |
October | 183.63 | 0.00 | 183.63 | 398.35 | 192.77 | 0.00 | 0.00 | 0.00 |
November | 155.54 | 0.00 | 155.54 | 209.56 | 421.82 | 0.00 | 0.00 | 0.00 |
December | 144.14 | 0.00 | 144.14 | 93.20 | 639.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 206.40 | 2.04 | 204.36 | 503.80 | 233.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 144.14 | 0.00 | 144.14 | 78.63 | 0.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 262.66 | 9.62 | 255.13 | 975.36 | 677.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 147.76 | 0.00 | 147.76 | 68.71 | 703.42 | 0.00 | 0.00 | 0.00 |
February | 175.22 | 0.00 | 175.22 | 160.89 | 522.22 | 0.00 | 0.00 | 0.00 |
March | 211.18 | 0.01 | 211.17 | 340.57 | 281.06 | 0.00 | 0.00 | 0.00 |
April | 230.18 | 1.51 | 228.66 | 628.26 | 79.77 | 0.00 | 0.00 | 0.00 |
May | 254.28 | 7.47 | 246.81 | 899.03 | 7.67 | 0.00 | 0.00 | 0.00 |
June | 262.66 | 9.62 | 253.04 | 962.87 | 8.17 | 0.00 | 0.00 | 0.00 |
July | 259.84 | 4.71 | 255.13 | 878.33 | 1.00 | 0.00 | 0.00 | 0.00 |
August | 238.46 | 1.08 | 237.38 | 726.88 | 3.55 | 0.00 | 0.00 | 0.00 |
September | 212.00 | 0.02 | 211.98 | 551.50 | 21.53 | 0.00 | 0.00 | 0.00 |
October | 183.63 | 0.00 | 183.63 | 389.48 | 200.94 | 0.00 | 0.00 | 0.00 |
November | 155.54 | 0.00 | 155.54 | 199.68 | 436.09 | 0.00 | 0.00 | 0.00 |
December | 144.14 | 0.00 | 144.14 | 83.23 | 663.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 206.40 | 2.04 | 204.36 | 492.46 | 242.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 144.14 | 0.00 | 144.14 | 68.71 | 1.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 262.66 | 9.62 | 255.13 | 962.87 | 703.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.11 | 0.00 | 21.11 | 15.04 | 91.07 | 0.00 | 0.00 | 0.00 |
February | 25.03 | 0.00 | 25.03 | 31.20 | 68.43 | 0.00 | 0.00 | 0.00 |
March | 30.17 | 0.00 | 30.17 | 62.27 | 37.73 | 0.00 | 0.00 | 0.00 |
April | 32.88 | 0.22 | 32.67 | 107.76 | 12.11 | 0.00 | 0.00 | 0.00 |
May | 36.33 | 1.07 | 35.26 | 145.57 | 1.97 | 0.00 | 0.00 | 0.00 |
June | 37.52 | 1.37 | 36.15 | 155.79 | 1.93 | 0.00 | 0.00 | 0.00 |
July | 37.12 | 0.67 | 36.45 | 142.93 | 0.38 | 0.00 | 0.00 | 0.00 |
August | 34.07 | 0.15 | 33.91 | 123.45 | 1.12 | 0.00 | 0.00 | 0.00 |
September | 30.29 | 0.00 | 30.28 | 97.59 | 4.80 | 0.00 | 0.00 | 0.00 |
October | 26.23 | 0.00 | 26.23 | 73.08 | 26.19 | 0.00 | 0.00 | 0.00 |
November | 22.22 | 0.00 | 22.22 | 40.28 | 55.38 | 0.00 | 0.00 | 0.00 |
December | 20.59 | 0.00 | 20.59 | 18.63 | 85.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.49 | 0.29 | 29.19 | 84.73 | 32.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.59 | 0.00 | 20.59 | 15.04 | 0.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 37.52 | 1.37 | 36.45 | 155.79 | 91.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 168.64 | 67.59 | 101.05 | 199.97 | 312.28 | 0.00 | 0.00 | 0.00 |
February | 205.44 | 84.82 | 120.62 | 313.90 | 239.25 | 0.00 | 0.00 | 0.00 |
March | 250.72 | 103.65 | 147.06 | 493.58 | 135.91 | 0.00 | 0.00 | 0.00 |
April | 298.42 | 139.14 | 159.28 | 740.63 | 45.08 | 0.00 | 0.00 | 0.00 |
May | 293.22 | 130.13 | 163.10 | 843.51 | 7.37 | 0.00 | 0.00 | 0.00 |
June | 238.12 | 78.80 | 159.32 | 770.34 | 7.34 | 0.00 | 0.00 | 0.00 |
July | 199.86 | 41.78 | 158.08 | 648.94 | 1.45 | 0.00 | 0.00 | 0.00 |
August | 180.63 | 31.43 | 149.21 | 562.92 | 4.21 | 0.00 | 0.00 | 0.00 |
September | 192.65 | 53.52 | 139.13 | 517.73 | 18.07 | 0.00 | 0.00 | 0.00 |
October | 210.76 | 84.92 | 125.85 | 493.70 | 96.49 | 0.00 | 0.00 | 0.00 |
November | 186.66 | 79.80 | 106.85 | 345.78 | 197.29 | 0.00 | 0.00 | 0.00 |
December | 163.38 | 64.87 | 98.51 | 217.84 | 301.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 215.65 | 79.91 | 135.74 | 513.15 | 113.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 163.38 | 31.43 | 98.51 | 199.97 | 1.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 298.42 | 139.14 | 163.10 | 843.51 | 312.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.27 | 58.60 | 37.67 | 148.69 | 83.06 | 0.00 | 0.00 | 0.00 |
February | 91.34 | 50.73 | 40.60 | 155.18 | 64.77 | 0.00 | 0.00 | 0.00 |
March | 77.61 | 34.03 | 43.58 | 159.91 | 37.23 | 0.00 | 0.00 | 0.00 |
April | 55.33 | 15.96 | 39.37 | 160.90 | 12.15 | 0.00 | 0.00 | 0.00 |
May | 39.89 | 3.36 | 36.53 | 155.46 | 1.98 | 0.00 | 0.00 | 0.00 |
June | 36.08 | 0.63 | 35.45 | 152.77 | 1.95 | 0.00 | 0.00 | 0.00 |
July | 37.47 | 0.37 | 37.11 | 143.30 | 0.38 | 0.00 | 0.00 | 0.00 |
August | 39.51 | 1.73 | 37.78 | 135.52 | 1.11 | 0.00 | 0.00 | 0.00 |
September | 54.67 | 15.05 | 39.62 | 148.73 | 4.79 | 0.00 | 0.00 | 0.00 |
October | 92.56 | 51.91 | 40.65 | 204.91 | 25.88 | 0.00 | 0.00 | 0.00 |
November | 115.49 | 76.51 | 38.98 | 216.51 | 53.15 | 0.00 | 0.00 | 0.00 |
December | 102.74 | 64.43 | 38.31 | 167.68 | 79.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 69.79 | 30.99 | 38.79 | 162.44 | 30.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.08 | 0.37 | 35.45 | 135.52 | 0.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.49 | 76.51 | 43.58 | 216.51 | 83.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.73 | 0.00 | 26.73 | 18.66 | 103.03 | 0.00 | 0.00 | 0.00 |
February | 31.70 | 0.00 | 31.70 | 36.85 | 75.20 | 0.00 | 0.00 | 0.00 |
March | 38.21 | 0.00 | 38.21 | 68.13 | 40.93 | 0.00 | 0.00 | 0.00 |
April | 41.64 | 0.27 | 41.37 | 117.42 | 11.62 | 0.00 | 0.00 | 0.00 |
May | 46.01 | 1.35 | 44.65 | 166.32 | 0.89 | 0.00 | 0.00 | 0.00 |
June | 47.52 | 1.74 | 45.78 | 177.90 | 0.91 | 0.00 | 0.00 | 0.00 |
July | 47.01 | 0.85 | 46.16 | 163.30 | 0.11 | 0.00 | 0.00 | 0.00 |
August | 43.14 | 0.20 | 42.95 | 135.80 | 0.25 | 0.00 | 0.00 | 0.00 |
September | 38.36 | 0.00 | 38.35 | 105.74 | 2.11 | 0.00 | 0.00 | 0.00 |
October | 33.22 | 0.00 | 33.22 | 73.64 | 31.07 | 0.00 | 0.00 | 0.00 |
November | 28.14 | 0.00 | 28.14 | 41.21 | 66.49 | 0.00 | 0.00 | 0.00 |
December | 26.08 | 0.00 | 26.08 | 21.44 | 97.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.34 | 0.37 | 36.97 | 94.15 | 35.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.08 | 0.00 | 26.08 | 18.66 | 0.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.52 | 1.74 | 46.16 | 177.90 | 103.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.92 | 0.00 | 23.92 | 16.69 | 92.18 | 0.00 | 0.00 | 0.00 |
February | 28.36 | 0.00 | 28.36 | 32.97 | 67.28 | 0.00 | 0.00 | 0.00 |
March | 34.18 | 0.00 | 34.18 | 60.95 | 36.62 | 0.00 | 0.00 | 0.00 |
April | 37.26 | 0.24 | 37.01 | 105.05 | 10.40 | 0.00 | 0.00 | 0.00 |
May | 41.16 | 1.21 | 39.95 | 148.81 | 0.80 | 0.00 | 0.00 | 0.00 |
June | 42.52 | 1.56 | 40.96 | 159.17 | 0.82 | 0.00 | 0.00 | 0.00 |
July | 42.06 | 0.76 | 41.30 | 146.11 | 0.09 | 0.00 | 0.00 | 0.00 |
August | 38.60 | 0.17 | 38.43 | 121.50 | 0.22 | 0.00 | 0.00 | 0.00 |
September | 34.32 | 0.00 | 34.31 | 94.60 | 1.89 | 0.00 | 0.00 | 0.00 |
October | 29.73 | 0.00 | 29.73 | 65.88 | 27.80 | 0.00 | 0.00 | 0.00 |
November | 25.18 | 0.00 | 25.18 | 36.87 | 59.49 | 0.00 | 0.00 | 0.00 |
December | 23.33 | 0.00 | 23.33 | 19.18 | 87.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.41 | 0.33 | 33.08 | 84.24 | 31.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.33 | 0.00 | 23.33 | 16.69 | 0.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.52 | 1.56 | 41.30 | 159.17 | 92.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 359.41 | 218.77 | 140.64 | 546.18 | 273.59 | 0.00 | 0.00 | 0.00 |
February | 340.99 | 189.40 | 151.58 | 564.41 | 208.22 | 0.00 | 0.00 | 0.00 |
March | 289.74 | 127.05 | 162.69 | 559.83 | 118.46 | 0.00 | 0.00 | 0.00 |
April | 206.57 | 59.57 | 147.00 | 541.49 | 34.66 | 0.00 | 0.00 | 0.00 |
May | 148.92 | 12.54 | 136.37 | 525.92 | 2.68 | 0.00 | 0.00 | 0.00 |
June | 134.69 | 2.34 | 132.35 | 513.80 | 2.76 | 0.00 | 0.00 | 0.00 |
July | 139.90 | 1.37 | 138.53 | 483.49 | 0.31 | 0.00 | 0.00 | 0.00 |
August | 147.51 | 6.46 | 141.04 | 444.22 | 0.74 | 0.00 | 0.00 | 0.00 |
September | 204.11 | 56.20 | 147.91 | 500.51 | 6.14 | 0.00 | 0.00 | 0.00 |
October | 345.56 | 193.81 | 151.75 | 705.82 | 89.70 | 0.00 | 0.00 | 0.00 |
November | 431.16 | 285.64 | 145.52 | 772.62 | 186.07 | 0.00 | 0.00 | 0.00 |
December | 383.54 | 240.53 | 143.01 | 611.41 | 263.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 260.54 | 115.71 | 144.83 | 563.94 | 98.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 134.69 | 1.37 | 132.35 | 444.22 | 0.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 431.16 | 285.64 | 162.69 | 772.62 | 273.59 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130416E+10 | 0.793836E+09 | 0.510329E+09 | 0.193452E+10 | 0.996421E+09 |
February | 0.111756E+10 | 0.620760E+09 | 0.496800E+09 | 0.180701E+10 | 0.696084E+09 |
March | 0.105134E+10 | 0.461029E+09 | 0.590316E+09 | 0.198398E+10 | 0.451765E+09 |
April | 0.725369E+09 | 0.209188E+09 | 0.516181E+09 | 0.183251E+10 | 0.133332E+09 |
May | 0.540347E+09 | 45516539.57 | 0.494830E+09 | 0.179155E+10 | 12436391.99 |
June | 0.472962E+09 | 8224351.46 | 0.464737E+09 | 0.170701E+10 | 9453310.47 |
July | 0.507632E+09 | 4971023.20 | 0.502661E+09 | 0.165991E+10 | 1161047.38 |
August | 0.535242E+09 | 23457320.20 | 0.511785E+09 | 0.154383E+10 | 3249713.17 |
September | 0.716747E+09 | 0.197346E+09 | 0.519402E+09 | 0.170501E+10 | 29488445.47 |
October | 0.125390E+10 | 0.703271E+09 | 0.550629E+09 | 0.249590E+10 | 0.352131E+09 |
November | 0.151402E+10 | 0.100302E+10 | 0.510999E+09 | 0.263193E+10 | 0.690248E+09 |
December | 0.139171E+10 | 0.872794E+09 | 0.518920E+09 | 0.214884E+10 | 0.973517E+09 |
Annual Sum or Average | 0.111310E+11 | 0.494341E+10 | 0.618759E+10 | 0.232420E+11 | 0.434929E+10 |
Minimum of Months | 0.472962E+09 | 4971023.20 | 0.464737E+09 | 0.154383E+10 | 1161047.38 |
Maximum of Months | 0.151402E+10 | 0.100302E+10 | 0.590316E+09 | 0.263193E+10 | 0.996421E+09 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.367244E+10 | 0.223539E+10 | 0.143705E+10 | 0.531087E+10 | 0.312335E+10 |
February | 0.314698E+10 | 0.174802E+10 | 0.139896E+10 | 0.497502E+10 | 0.220745E+10 |
March | 0.296052E+10 | 0.129823E+10 | 0.166229E+10 | 0.550470E+10 | 0.142306E+10 |
April | 0.204259E+10 | 0.589060E+09 | 0.145353E+10 | 0.513931E+10 | 0.410416E+09 |
May | 0.152158E+10 | 0.128172E+09 | 0.139341E+10 | 0.505779E+10 | 40702636.61 |
June | 0.133183E+10 | 23159231.46 | 0.130867E+10 | 0.481488E+10 | 35835303.12 |
July | 0.142946E+10 | 13998073.57 | 0.141546E+10 | 0.466985E+10 | 4887136.22 |
August | 0.150721E+10 | 66054267.05 | 0.144115E+10 | 0.433389E+10 | 16068165.26 |
September | 0.201831E+10 | 0.555713E+09 | 0.146260E+10 | 0.473321E+10 | 0.103515E+09 |
October | 0.353090E+10 | 0.198036E+10 | 0.155054E+10 | 0.697408E+10 | 0.106434E+10 |
November | 0.426338E+10 | 0.282444E+10 | 0.143894E+10 | 0.731994E+10 | 0.212394E+10 |
December | 0.391898E+10 | 0.245773E+10 | 0.146125E+10 | 0.590686E+10 | 0.305356E+10 |
Annual Sum or Average | 0.313442E+11 | 0.139203E+11 | 0.174238E+11 | 0.647404E+11 | 0.136071E+11 |
Minimum of Months | 0.133183E+10 | 13998073.57 | 0.130867E+10 | 0.433389E+10 | 4887136.22 |
Maximum of Months | 0.426338E+10 | 0.282444E+10 | 0.166229E+10 | 0.731994E+10 | 0.312335E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.477071E+10 | 0.290390E+10 | 0.186681E+10 | 0.706643E+10 | 0.420757E+10 |
February | 0.408810E+10 | 0.227078E+10 | 0.181732E+10 | 0.664055E+10 | 0.294157E+10 |
March | 0.384588E+10 | 0.168647E+10 | 0.215941E+10 | 0.737702E+10 | 0.185808E+10 |
April | 0.265344E+10 | 0.765222E+09 | 0.188822E+10 | 0.693835E+10 | 0.523638E+09 |
May | 0.197662E+10 | 0.166502E+09 | 0.181012E+10 | 0.685126E+10 | 49684248.75 |
June | 0.173012E+10 | 30085159.67 | 0.170004E+10 | 0.650296E+10 | 44192191.27 |
July | 0.185695E+10 | 18184294.20 | 0.183876E+10 | 0.629153E+10 | 6467088.74 |
August | 0.195795E+10 | 85808252.08 | 0.187214E+10 | 0.582569E+10 | 19852602.56 |
September | 0.262190E+10 | 0.721903E+09 | 0.190000E+10 | 0.633626E+10 | 0.124481E+09 |
October | 0.458684E+10 | 0.257261E+10 | 0.201423E+10 | 0.930189E+10 | 0.136797E+10 |
November | 0.553837E+10 | 0.366910E+10 | 0.186926E+10 | 0.974670E+10 | 0.277756E+10 |
December | 0.509097E+10 | 0.319273E+10 | 0.189824E+10 | 0.786307E+10 | 0.408770E+10 |
Annual Sum or Average | 0.407179E+11 | 0.180833E+11 | 0.226346E+11 | 0.867417E+11 | 0.180088E+11 |
Minimum of Months | 0.173012E+10 | 18184294.20 | 0.170004E+10 | 0.582569E+10 | 6467088.74 |
Maximum of Months | 0.553837E+10 | 0.366910E+10 | 0.215941E+10 | 0.974670E+10 | 0.420757E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257856E+09 | 0.156955E+09 | 0.100901E+09 | 0.391205E+09 | 0.191114E+09 |
February | 0.220962E+09 | 0.122735E+09 | 98226560.89 | 0.366461E+09 | 0.128193E+09 |
March | 0.207870E+09 | 91153340.39 | 0.116717E+09 | 0.408916E+09 | 71027833.53 |
April | 0.143419E+09 | 41360060.59 | 0.102059E+09 | 0.398273E+09 | 13515949.09 |
May | 0.106837E+09 | 8999401.61 | 97837742.79 | 0.414108E+09 | 128922.95 |
June | 93513864.01 | 1626095.54 | 91887768.48 | 0.394954E+09 | 523957.02 |
July | 0.100368E+09 | 982856.66 | 99385597.75 | 0.389941E+09 | 29652.93 |
August | 0.105827E+09 | 4637915.08 | 0.101189E+09 | 0.361257E+09 | 0.00 |
September | 0.141714E+09 | 39018665.27 | 0.102695E+09 | 0.381393E+09 | 913756.55 |
October | 0.247919E+09 | 0.139049E+09 | 0.108870E+09 | 0.519264E+09 | 47153961.01 |
November | 0.299348E+09 | 0.198314E+09 | 0.101034E+09 | 0.539018E+09 | 0.118829E+09 |
December | 0.275166E+09 | 0.172566E+09 | 0.102600E+09 | 0.436493E+09 | 0.185038E+09 |
Annual Sum or Average | 0.220080E+10 | 0.977398E+09 | 0.122340E+10 | 0.500128E+10 | 0.756469E+09 |
Minimum of Months | 93513864.01 | 982856.66 | 91887768.48 | 0.361257E+09 | 0.00 |
Maximum of Months | 0.299348E+09 | 0.198314E+09 | 0.116717E+09 | 0.539018E+09 | 0.191114E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221244E+09 | 86087524.92 | 0.135156E+09 | 0.282204E+09 | 0.389992E+09 |
February | 0.229086E+09 | 84636723.15 | 0.144449E+09 | 0.347781E+09 | 0.254693E+09 |
March | 0.328722E+09 | 0.131751E+09 | 0.196971E+09 | 0.615428E+09 | 0.135554E+09 |
April | 0.385378E+09 | 0.180472E+09 | 0.204906E+09 | 0.920242E+09 | 25169126.98 |
May | 0.377523E+09 | 0.160150E+09 | 0.217373E+09 | 0.110014E+10 | 231187.22 |
June | 0.343719E+09 | 0.133864E+09 | 0.209855E+09 | 0.106548E+10 | 916805.41 |
July | 0.262876E+09 | 50940232.63 | 0.211936E+09 | 0.875572E+09 | 48848.03 |
August | 0.241314E+09 | 42523490.64 | 0.198790E+09 | 0.753646E+09 | 0.00 |
September | 0.257885E+09 | 76260642.87 | 0.181624E+09 | 0.679905E+09 | 1692574.98 |
October | 0.277126E+09 | 0.110649E+09 | 0.166477E+09 | 0.599268E+09 | 90184049.73 |
November | 0.242324E+09 | 0.103431E+09 | 0.138892E+09 | 0.424952E+09 | 0.233913E+09 |
December | 0.213663E+09 | 81248581.68 | 0.132414E+09 | 0.285242E+09 | 0.369790E+09 |
Annual Sum or Average | 0.338086E+10 | 0.124201E+10 | 0.213884E+10 | 0.794986E+10 | 0.150219E+10 |
Minimum of Months | 0.213663E+09 | 42523490.64 | 0.132414E+09 | 0.282204E+09 | 0.00 |
Maximum of Months | 0.385378E+09 | 0.180472E+09 | 0.217373E+09 | 0.110014E+10 | 0.389992E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 56539365.29 | 0.00 | 56539365.29 | 44034255.86 | 0.207659E+09 |
February | 60557776.44 | 0.00 | 60557776.44 | 72862070.44 | 0.138106E+09 |
March | 80805919.73 | 2761.14 | 80803158.59 | 0.150120E+09 | 76648749.59 |
April | 85233890.90 | 560248.75 | 84673642.14 | 0.261385E+09 | 14038528.44 |
May | 97299063.90 | 2857973.11 | 94441090.78 | 0.388605E+09 | 143134.73 |
June | 97261652.82 | 3562361.46 | 93699291.36 | 0.402220E+09 | 535030.01 |
July | 99427608.29 | 1804127.96 | 97623480.33 | 0.388528E+09 | 29643.41 |
August | 91245924.45 | 413603.30 | 90832321.16 | 0.329826E+09 | 0.00 |
September | 78504458.66 | 9170.16 | 78495288.51 | 0.250556E+09 | 906148.79 |
October | 70266640.23 | 0.00 | 70266640.23 | 0.167991E+09 | 50149254.70 |
November | 57596651.05 | 0.00 | 57596651.05 | 89130635.06 | 0.127552E+09 |
December | 55155161.67 | 0.00 | 55155161.67 | 49316088.25 | 0.198120E+09 |
Annual Sum or Average | 0.929894E+09 | 9210245.88 | 0.920684E+09 | 0.259457E+10 | 0.813888E+09 |
Minimum of Months | 55155161.67 | 0.00 | 55155161.67 | 44034255.86 | 0.00 |
Maximum of Months | 99427608.29 | 3562361.46 | 97623480.33 | 0.402220E+09 | 0.207659E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221244E+09 | 86087524.92 | 0.135156E+09 | 0.296356E+09 | 0.381098E+09 |
February | 0.229086E+09 | 84636723.15 | 0.144449E+09 | 0.355243E+09 | 0.255766E+09 |
March | 0.328722E+09 | 0.131751E+09 | 0.196971E+09 | 0.618482E+09 | 0.142213E+09 |
April | 0.385378E+09 | 0.180472E+09 | 0.204906E+09 | 0.921937E+09 | 26222581.85 |
May | 0.377523E+09 | 0.160150E+09 | 0.217373E+09 | 0.110117E+10 | 237763.95 |
June | 0.343719E+09 | 0.133864E+09 | 0.209855E+09 | 0.106521E+10 | 970663.48 |
July | 0.262876E+09 | 50940232.63 | 0.211936E+09 | 0.875655E+09 | 48831.96 |
August | 0.241314E+09 | 42523490.64 | 0.198790E+09 | 0.754815E+09 | 0.00 |
September | 0.257885E+09 | 76260642.87 | 0.181624E+09 | 0.684079E+09 | 1619400.91 |
October | 0.277126E+09 | 0.110649E+09 | 0.166477E+09 | 0.603803E+09 | 93072243.86 |
November | 0.242324E+09 | 0.103431E+09 | 0.138892E+09 | 0.434027E+09 | 0.236931E+09 |
December | 0.213663E+09 | 81248581.68 | 0.132414E+09 | 0.299684E+09 | 0.361842E+09 |
Annual Sum or Average | 0.338086E+10 | 0.124201E+10 | 0.213884E+10 | 0.801046E+10 | 0.150002E+10 |
Minimum of Months | 0.213663E+09 | 42523490.64 | 0.132414E+09 | 0.296356E+09 | 0.00 |
Maximum of Months | 0.385378E+09 | 0.180472E+09 | 0.217373E+09 | 0.110117E+10 | 0.381098E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206244E+09 | 0.125539E+09 | 80705073.08 | 0.272493E+09 | 0.229539E+09 |
February | 0.176734E+09 | 98168448.57 | 78565624.13 | 0.257051E+09 | 0.166664E+09 |
March | 0.166263E+09 | 72908172.84 | 93354691.77 | 0.285632E+09 | 0.114841E+09 |
April | 0.114713E+09 | 33081469.46 | 81631059.55 | 0.263775E+09 | 42883768.68 |
May | 85452721.28 | 7198089.78 | 78254631.50 | 0.251708E+09 | 10072480.83 |
June | 74796216.26 | 1300617.77 | 73495598.49 | 0.235098E+09 | 7024261.70 |
July | 80278798.24 | 786128.99 | 79492669.25 | 0.221838E+09 | 3035916.48 |
August | 84645005.97 | 3709594.33 | 80935411.64 | 0.205252E+09 | 8353649.86 |
September | 0.113349E+09 | 31208725.64 | 82139971.61 | 0.237112E+09 | 24531862.76 |
October | 0.198295E+09 | 0.111217E+09 | 87078526.71 | 0.373209E+09 | 89915863.17 |
November | 0.239431E+09 | 0.158620E+09 | 80811117.20 | 0.393704E+09 | 0.157313E+09 |
December | 0.220089E+09 | 0.138026E+09 | 82063718.04 | 0.307713E+09 | 0.221946E+09 |
Annual Sum or Average | 0.176029E+10 | 0.781763E+09 | 0.978528E+09 | 0.330459E+10 | 0.107612E+10 |
Minimum of Months | 74796216.26 | 786128.99 | 73495598.49 | 0.205252E+09 | 3035916.48 |
Maximum of Months | 0.239431E+09 | 0.158620E+09 | 93354691.77 | 0.393704E+09 | 0.229539E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45237487.93 | 0.00 | 45237487.93 | 35370917.61 | 0.170089E+09 |
February | 48452642.97 | 0.00 | 48452642.97 | 60962708.80 | 0.110436E+09 |
March | 64653304.81 | 2209.21 | 64651095.60 | 0.128147E+09 | 57019284.60 |
April | 68196151.31 | 448258.41 | 67747892.89 | 0.226075E+09 | 8617792.48 |
May | 77849569.15 | 2286681.56 | 75562887.59 | 0.333171E+09 | 7042.27 |
June | 77819636.33 | 2850266.94 | 74969369.39 | 0.342394E+09 | 137519.58 |
July | 79552630.39 | 1443493.68 | 78109136.70 | 0.329290E+09 | 6108.55 |
August | 73006415.70 | 330926.50 | 72675489.20 | 0.280675E+09 | 0.00 |
September | 62811891.90 | 7337.10 | 62804554.80 | 0.216012E+09 | 291057.35 |
October | 56220763.58 | 0.00 | 56220763.58 | 0.144060E+09 | 35164155.97 |
November | 46083428.65 | 0.00 | 46083428.65 | 76234422.69 | 98512524.63 |
December | 44129978.24 | 0.00 | 44129978.24 | 40276799.67 | 0.160433E+09 |
Annual Sum or Average | 0.744014E+09 | 7369173.40 | 0.736645E+09 | 0.221267E+10 | 0.640714E+09 |
Minimum of Months | 44129978.24 | 0.00 | 44129978.24 | 35370917.61 | 0.00 |
Maximum of Months | 79552630.39 | 2850266.94 | 78109136.70 | 0.342394E+09 | 0.170089E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225854E+09 | 90517979.35 | 0.135336E+09 | 0.258122E+09 | 0.359650E+09 |
February | 0.248516E+09 | 0.102607E+09 | 0.145910E+09 | 0.361854E+09 | 0.235239E+09 |
March | 0.335784E+09 | 0.138821E+09 | 0.196962E+09 | 0.622514E+09 | 0.126245E+09 |
April | 0.386781E+09 | 0.180335E+09 | 0.206446E+09 | 0.926227E+09 | 23713669.72 |
May | 0.392711E+09 | 0.174277E+09 | 0.218435E+09 | 0.112833E+10 | 168376.05 |
June | 0.308626E+09 | 0.102130E+09 | 0.206496E+09 | 0.100127E+10 | 878795.38 |
July | 0.267668E+09 | 55953232.59 | 0.211715E+09 | 0.882754E+09 | 53800.99 |
August | 0.241923E+09 | 42092929.72 | 0.199830E+09 | 0.753211E+09 | 0.00 |
September | 0.249692E+09 | 69365482.92 | 0.180326E+09 | 0.665242E+09 | 1558494.09 |
October | 0.282275E+09 | 0.113730E+09 | 0.168545E+09 | 0.605035E+09 | 85762520.43 |
November | 0.241922E+09 | 0.103432E+09 | 0.138491E+09 | 0.406640E+09 | 0.218179E+09 |
December | 0.218812E+09 | 86880466.94 | 0.131932E+09 | 0.273197E+09 | 0.351359E+09 |
Annual Sum or Average | 0.340056E+10 | 0.126014E+10 | 0.214042E+10 | 0.788439E+10 | 0.140281E+10 |
Minimum of Months | 0.218812E+09 | 42092929.72 | 0.131932E+09 | 0.258122E+09 | 0.00 |
Maximum of Months | 0.392711E+09 | 0.180335E+09 | 0.218435E+09 | 0.112833E+10 | 0.359650E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257856E+09 | 0.156955E+09 | 0.100901E+09 | 0.388980E+09 | 0.190379E+09 |
February | 0.220962E+09 | 0.122735E+09 | 98226560.89 | 0.364184E+09 | 0.127787E+09 |
March | 0.207870E+09 | 91153340.39 | 0.116717E+09 | 0.407101E+09 | 70328653.10 |
April | 0.143419E+09 | 41360060.59 | 0.102059E+09 | 0.397624E+09 | 13177641.35 |
May | 0.106837E+09 | 8999401.61 | 97837742.79 | 0.413748E+09 | 102255.20 |
June | 93513864.01 | 1626095.54 | 91887768.48 | 0.396046E+09 | 481503.39 |
July | 0.100368E+09 | 982856.66 | 99385597.75 | 0.389751E+09 | 29166.83 |
August | 0.105827E+09 | 4637915.08 | 0.101189E+09 | 0.361154E+09 | 0.00 |
September | 0.141714E+09 | 39018665.27 | 0.102695E+09 | 0.381546E+09 | 852561.47 |
October | 0.247919E+09 | 0.139049E+09 | 0.108870E+09 | 0.518301E+09 | 46588154.97 |
November | 0.299348E+09 | 0.198314E+09 | 0.101034E+09 | 0.537700E+09 | 0.118049E+09 |
December | 0.275166E+09 | 0.172566E+09 | 0.102600E+09 | 0.434693E+09 | 0.184237E+09 |
Annual Sum or Average | 0.220080E+10 | 0.977398E+09 | 0.122340E+10 | 0.499083E+10 | 0.752010E+09 |
Minimum of Months | 93513864.01 | 982856.66 | 91887768.48 | 0.361154E+09 | 0.00 |
Maximum of Months | 0.299348E+09 | 0.198314E+09 | 0.116717E+09 | 0.537700E+09 | 0.190379E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 56539365.29 | 0.00 | 56539365.29 | 42580125.91 | 0.206270E+09 |
February | 60557776.44 | 0.00 | 60557776.44 | 70347894.46 | 0.137635E+09 |
March | 80805919.73 | 2761.14 | 80803158.59 | 0.147141E+09 | 75987952.37 |
April | 85233890.90 | 560248.75 | 84673642.14 | 0.260039E+09 | 13722141.13 |
May | 97299063.90 | 2857973.11 | 94441090.78 | 0.388158E+09 | 115395.63 |
June | 97261652.82 | 3562361.46 | 93699291.36 | 0.403307E+09 | 495296.42 |
July | 99427608.29 | 1804127.96 | 97623480.33 | 0.388330E+09 | 29157.95 |
August | 91245924.45 | 413603.30 | 90832321.16 | 0.329705E+09 | 0.00 |
September | 78504458.66 | 9170.16 | 78495288.51 | 0.250654E+09 | 843044.81 |
October | 70266640.23 | 0.00 | 70266640.23 | 0.166263E+09 | 49583059.06 |
November | 57596651.05 | 0.00 | 57596651.05 | 86766725.92 | 0.126449E+09 |
December | 55155161.67 | 0.00 | 55155161.67 | 47503963.25 | 0.196577E+09 |
Annual Sum or Average | 0.929894E+09 | 9210245.88 | 0.920684E+09 | 0.258080E+10 | 0.807707E+09 |
Minimum of Months | 55155161.67 | 0.00 | 55155161.67 | 42580125.91 | 0.00 |
Maximum of Months | 99427608.29 | 3562361.46 | 97623480.33 | 0.403307E+09 | 0.206270E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225854E+09 | 90517979.35 | 0.135336E+09 | 0.273752E+09 | 0.349647E+09 |
February | 0.248516E+09 | 0.102607E+09 | 0.145910E+09 | 0.369318E+09 | 0.236372E+09 |
March | 0.335784E+09 | 0.138821E+09 | 0.196962E+09 | 0.621709E+09 | 0.131974E+09 |
April | 0.386781E+09 | 0.180335E+09 | 0.206446E+09 | 0.925838E+09 | 24376110.78 |
May | 0.392711E+09 | 0.174277E+09 | 0.218435E+09 | 0.112927E+10 | 171512.14 |
June | 0.308626E+09 | 0.102130E+09 | 0.206496E+09 | 0.100101E+10 | 922576.13 |
July | 0.267668E+09 | 55953232.59 | 0.211715E+09 | 0.882838E+09 | 53785.03 |
August | 0.241923E+09 | 42092929.72 | 0.199830E+09 | 0.754379E+09 | 0.00 |
September | 0.249692E+09 | 69365482.92 | 0.180326E+09 | 0.669352E+09 | 1447155.71 |
October | 0.282275E+09 | 0.113730E+09 | 0.168545E+09 | 0.606930E+09 | 87888558.76 |
November | 0.241922E+09 | 0.103432E+09 | 0.138491E+09 | 0.413525E+09 | 0.220597E+09 |
December | 0.218812E+09 | 86880466.94 | 0.131932E+09 | 0.287452E+09 | 0.341820E+09 |
Annual Sum or Average | 0.340056E+10 | 0.126014E+10 | 0.214042E+10 | 0.793537E+10 | 0.139527E+10 |
Minimum of Months | 0.218812E+09 | 42092929.72 | 0.131932E+09 | 0.273752E+09 | 0.00 |
Maximum of Months | 0.392711E+09 | 0.180335E+09 | 0.218435E+09 | 0.112927E+10 | 0.349647E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 71603538.71 | 0.00 | 71603538.71 | 54752845.01 | 0.277618E+09 |
February | 76692602.88 | 0.00 | 76692602.88 | 93792999.17 | 0.185307E+09 |
March | 0.102336E+09 | 3496.82 | 0.102332E+09 | 0.191396E+09 | 0.110010E+09 |
April | 0.107943E+09 | 709519.70 | 0.107234E+09 | 0.318361E+09 | 28452838.31 |
May | 0.123223E+09 | 3619442.62 | 0.119604E+09 | 0.463376E+09 | 1844413.48 |
June | 0.123176E+09 | 4511506.01 | 0.118664E+09 | 0.481187E+09 | 1948322.89 |
July | 0.125919E+09 | 2284814.22 | 0.123634E+09 | 0.457874E+09 | 266279.34 |
August | 0.115557E+09 | 523802.48 | 0.115033E+09 | 0.384141E+09 | 224041.64 |
September | 99420943.54 | 11613.42 | 99409330.12 | 0.290013E+09 | 4594815.17 |
October | 88988266.27 | 0.00 | 88988266.27 | 0.205378E+09 | 83552044.27 |
November | 72942524.41 | 0.00 | 72942524.41 | 0.109945E+09 | 0.180170E+09 |
December | 69850532.15 | 0.00 | 69850532.15 | 59996824.17 | 0.269684E+09 |
Annual Sum or Average | 0.117765E+10 | 11664195.27 | 0.116599E+10 | 0.311021E+10 | 0.114367E+10 |
Minimum of Months | 69850532.15 | 0.00 | 69850532.15 | 54752845.01 | 224041.64 |
Maximum of Months | 0.125919E+09 | 4511506.01 | 0.123634E+09 | 0.481187E+09 | 0.277618E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 26396029.24 | 0.00 | 26396029.24 | 20184165.81 | 0.102341E+09 |
February | 28272069.01 | 0.00 | 28272069.01 | 34575983.16 | 68311742.03 |
March | 37725139.09 | 1289.07 | 37723850.02 | 70556665.17 | 40554397.54 |
April | 39792386.50 | 261558.34 | 39530828.16 | 0.117361E+09 | 10488894.34 |
May | 45425146.21 | 1334276.42 | 44090869.79 | 0.170819E+09 | 679927.18 |
June | 45407680.44 | 1663127.92 | 43744552.52 | 0.177385E+09 | 718232.49 |
July | 46418880.75 | 842277.13 | 45576603.62 | 0.168791E+09 | 98161.59 |
August | 42599170.99 | 193095.28 | 42406075.71 | 0.141610E+09 | 82591.03 |
September | 36650676.49 | 4281.19 | 36646395.30 | 0.106911E+09 | 1693839.13 |
October | 32804759.66 | 0.00 | 32804759.66 | 75710653.53 | 30800743.13 |
November | 26889634.81 | 0.00 | 26889634.81 | 40530369.83 | 66418094.11 |
December | 25749798.43 | 0.00 | 25749798.43 | 22117313.66 | 99416747.97 |
Annual Sum or Average | 0.434131E+09 | 4299905.35 | 0.429831E+09 | 0.114655E+10 | 0.421605E+09 |
Minimum of Months | 25749798.43 | 0.00 | 25749798.43 | 20184165.81 | 82591.03 |
Maximum of Months | 46418880.75 | 1663127.92 | 45576603.62 | 0.177385E+09 | 0.102341E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120315E+09 | 73234566.25 | 47080188.47 | 0.185697E+09 | 92122740.64 |
February | 0.103100E+09 | 57267639.87 | 45832117.49 | 0.173264E+09 | 63932374.20 |
March | 96991263.41 | 42531781.31 | 54459482.11 | 0.191506E+09 | 39573036.19 |
April | 66918810.43 | 19298437.60 | 47620372.82 | 0.181277E+09 | 10567900.03 |
May | 49849781.06 | 4199084.53 | 45650696.53 | 0.182824E+09 | 692112.42 |
June | 43633192.12 | 758729.62 | 42874462.49 | 0.173855E+09 | 725951.61 |
July | 46831516.37 | 458596.96 | 46372919.42 | 0.169387E+09 | 97655.59 |
August | 49378591.48 | 2164032.49 | 47214559.00 | 0.156426E+09 | 82957.44 |
September | 66123204.23 | 18205951.98 | 47917252.25 | 0.168616E+09 | 1655138.27 |
October | 0.115678E+09 | 64879587.76 | 50798212.47 | 0.239960E+09 | 30016061.00 |
November | 0.139675E+09 | 92532619.20 | 47142050.47 | 0.251941E+09 | 62756413.23 |
December | 0.128392E+09 | 80518807.91 | 47872768.89 | 0.206152E+09 | 90886633.48 |
Annual Sum or Average | 0.102688E+10 | 0.456050E+09 | 0.570835E+09 | 0.228091E+10 | 0.393109E+09 |
Minimum of Months | 43633192.12 | 458596.96 | 42874462.49 | 0.156426E+09 | 82957.44 |
Maximum of Months | 0.139675E+09 | 92532619.20 | 54459482.11 | 0.251941E+09 | 92122740.64 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.326559E+09 | 0.198774E+09 | 0.127785E+09 | 0.504021E+09 | 0.250040E+09 |
February | 0.279834E+09 | 0.155436E+09 | 0.124398E+09 | 0.470274E+09 | 0.173526E+09 |
March | 0.263254E+09 | 0.115440E+09 | 0.147814E+09 | 0.519787E+09 | 0.107409E+09 |
April | 0.181631E+09 | 52379907.07 | 0.129251E+09 | 0.492023E+09 | 28683442.28 |
May | 0.135303E+09 | 11397174.31 | 0.123905E+09 | 0.496222E+09 | 1878534.67 |
June | 0.118429E+09 | 2059347.40 | 0.116370E+09 | 0.471879E+09 | 1970381.15 |
July | 0.127110E+09 | 1244725.95 | 0.125866E+09 | 0.459750E+09 | 265057.25 |
August | 0.134024E+09 | 5873626.81 | 0.128150E+09 | 0.424573E+09 | 225163.46 |
September | 0.179472E+09 | 49414677.62 | 0.130057E+09 | 0.457658E+09 | 4492383.83 |
October | 0.313973E+09 | 0.176096E+09 | 0.137877E+09 | 0.651301E+09 | 81469729.21 |
November | 0.379106E+09 | 0.251152E+09 | 0.127953E+09 | 0.683821E+09 | 0.170334E+09 |
December | 0.348481E+09 | 0.218545E+09 | 0.129936E+09 | 0.559539E+09 | 0.246685E+09 |
Annual Sum or Average | 0.278718E+10 | 0.123781E+10 | 0.154936E+10 | 0.619085E+10 | 0.106698E+10 |
Minimum of Months | 0.118429E+09 | 1244725.95 | 0.116370E+09 | 0.424573E+09 | 225163.46 |
Maximum of Months | 0.379106E+09 | 0.251152E+09 | 0.147814E+09 | 0.683821E+09 | 0.250040E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257856E+09 | 0.156955E+09 | 0.100901E+09 | 0.389334E+09 | 0.188018E+09 |
February | 0.220962E+09 | 0.122735E+09 | 98226560.89 | 0.363674E+09 | 0.126056E+09 |
March | 0.207870E+09 | 91153340.39 | 0.116717E+09 | 0.405666E+09 | 69263392.29 |
April | 0.143419E+09 | 41360060.59 | 0.102059E+09 | 0.395600E+09 | 12736088.95 |
May | 0.106837E+09 | 8999401.61 | 97837742.79 | 0.413228E+09 | 77256.60 |
June | 93513864.01 | 1626095.54 | 91887768.48 | 0.393030E+09 | 537004.56 |
July | 0.100368E+09 | 982856.66 | 99385597.75 | 0.389235E+09 | 18439.32 |
August | 0.105827E+09 | 4637915.08 | 0.101189E+09 | 0.359834E+09 | 0.00 |
September | 0.141714E+09 | 39018665.27 | 0.102695E+09 | 0.379333E+09 | 783081.24 |
October | 0.247919E+09 | 0.139049E+09 | 0.108870E+09 | 0.516463E+09 | 45590533.26 |
November | 0.299348E+09 | 0.198314E+09 | 0.101034E+09 | 0.536676E+09 | 0.116405E+09 |
December | 0.275166E+09 | 0.172566E+09 | 0.102600E+09 | 0.435120E+09 | 0.181811E+09 |
Annual Sum or Average | 0.220080E+10 | 0.977398E+09 | 0.122340E+10 | 0.497719E+10 | 0.741297E+09 |
Minimum of Months | 93513864.01 | 982856.66 | 91887768.48 | 0.359834E+09 | 0.00 |
Maximum of Months | 0.299348E+09 | 0.198314E+09 | 0.116717E+09 | 0.536676E+09 | 0.188018E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221244E+09 | 86087524.92 | 0.135156E+09 | 0.278946E+09 | 0.382501E+09 |
February | 0.229086E+09 | 84636723.15 | 0.144449E+09 | 0.343656E+09 | 0.249791E+09 |
March | 0.328722E+09 | 0.131751E+09 | 0.196971E+09 | 0.609573E+09 | 0.131871E+09 |
April | 0.385378E+09 | 0.180472E+09 | 0.204906E+09 | 0.914586E+09 | 23662311.85 |
May | 0.377523E+09 | 0.160150E+09 | 0.217373E+09 | 0.109665E+10 | 150269.82 |
June | 0.343719E+09 | 0.133864E+09 | 0.209855E+09 | 0.105996E+10 | 930158.48 |
July | 0.262876E+09 | 50940232.63 | 0.211936E+09 | 0.872376E+09 | 31583.18 |
August | 0.241314E+09 | 42523490.64 | 0.198790E+09 | 0.750501E+09 | 0.00 |
September | 0.257885E+09 | 76260642.87 | 0.181624E+09 | 0.676508E+09 | 1434026.86 |
October | 0.277126E+09 | 0.110649E+09 | 0.166477E+09 | 0.595486E+09 | 86991095.21 |
November | 0.242324E+09 | 0.103431E+09 | 0.138892E+09 | 0.422019E+09 | 0.228607E+09 |
December | 0.213663E+09 | 81248581.68 | 0.132414E+09 | 0.283187E+09 | 0.362239E+09 |
Annual Sum or Average | 0.338086E+10 | 0.124201E+10 | 0.213884E+10 | 0.790345E+10 | 0.146821E+10 |
Minimum of Months | 0.213663E+09 | 42523490.64 | 0.132414E+09 | 0.278946E+09 | 0.00 |
Maximum of Months | 0.385378E+09 | 0.180472E+09 | 0.217373E+09 | 0.109665E+10 | 0.382501E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 56539365.29 | 0.00 | 56539365.29 | 44284382.01 | 0.203353E+09 |
February | 60557776.44 | 0.00 | 60557776.44 | 72365113.54 | 0.135577E+09 |
March | 80805919.73 | 2761.14 | 80803158.59 | 0.149084E+09 | 74648105.80 |
April | 85233890.90 | 560248.75 | 84673642.14 | 0.260516E+09 | 13121117.27 |
May | 97299063.90 | 2857973.11 | 94441090.78 | 0.388027E+09 | 92754.50 |
June | 97261652.82 | 3562361.46 | 93699291.36 | 0.400195E+09 | 538201.06 |
July | 99427608.29 | 1804127.96 | 97623480.33 | 0.387591E+09 | 18440.52 |
August | 91245924.45 | 413603.30 | 90832321.16 | 0.328739E+09 | 0.00 |
September | 78504458.66 | 9170.16 | 78495288.51 | 0.249836E+09 | 751347.54 |
October | 70266640.23 | 0.00 | 70266640.23 | 0.167433E+09 | 47941935.64 |
November | 57596651.05 | 0.00 | 57596651.05 | 89283063.48 | 0.124027E+09 |
December | 55155161.67 | 0.00 | 55155161.67 | 50038274.54 | 0.193411E+09 |
Annual Sum or Average | 0.929894E+09 | 9210245.88 | 0.920684E+09 | 0.258739E+10 | 0.793479E+09 |
Minimum of Months | 55155161.67 | 0.00 | 55155161.67 | 44284382.01 | 0.00 |
Maximum of Months | 99427608.29 | 3562361.46 | 97623480.33 | 0.400195E+09 | 0.203353E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221244E+09 | 86087524.92 | 0.135156E+09 | 0.294709E+09 | 0.372809E+09 |
February | 0.229086E+09 | 84636723.15 | 0.144449E+09 | 0.351882E+09 | 0.250788E+09 |
March | 0.328722E+09 | 0.131751E+09 | 0.196971E+09 | 0.613310E+09 | 0.138471E+09 |
April | 0.385378E+09 | 0.180472E+09 | 0.204906E+09 | 0.916638E+09 | 24415122.78 |
May | 0.377523E+09 | 0.160150E+09 | 0.217373E+09 | 0.109770E+10 | 148888.64 |
June | 0.343719E+09 | 0.133864E+09 | 0.209855E+09 | 0.105970E+10 | 971268.65 |
July | 0.262876E+09 | 50940232.63 | 0.211936E+09 | 0.872456E+09 | 31588.57 |
August | 0.241314E+09 | 42523490.64 | 0.198790E+09 | 0.751723E+09 | 0.00 |
September | 0.257885E+09 | 76260642.87 | 0.181624E+09 | 0.680911E+09 | 1338796.06 |
October | 0.277126E+09 | 0.110649E+09 | 0.166477E+09 | 0.601056E+09 | 88873370.06 |
November | 0.242324E+09 | 0.103431E+09 | 0.138892E+09 | 0.432621E+09 | 0.230158E+09 |
December | 0.213663E+09 | 81248581.68 | 0.132414E+09 | 0.299712E+09 | 0.352853E+09 |
Annual Sum or Average | 0.338086E+10 | 0.124201E+10 | 0.213884E+10 | 0.797242E+10 | 0.146086E+10 |
Minimum of Months | 0.213663E+09 | 42523490.64 | 0.132414E+09 | 0.294709E+09 | 0.00 |
Maximum of Months | 0.385378E+09 | 0.180472E+09 | 0.217373E+09 | 0.109770E+10 | 0.372809E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.378171E+09 | 0.230190E+09 | 0.147982E+09 | 0.556932E+09 | 0.287768E+09 |
February | 0.324061E+09 | 0.180003E+09 | 0.144059E+09 | 0.526265E+09 | 0.190127E+09 |
March | 0.304861E+09 | 0.133685E+09 | 0.171176E+09 | 0.595955E+09 | 0.100491E+09 |
April | 0.210338E+09 | 60658498.20 | 0.149679E+09 | 0.594141E+09 | 16739474.71 |
May | 0.156687E+09 | 13198486.14 | 0.143488E+09 | 0.628625E+09 | 24761.58 |
June | 0.137147E+09 | 2384825.16 | 0.134762E+09 | 0.598034E+09 | 506166.09 |
July | 0.147200E+09 | 1441453.62 | 0.145759E+09 | 0.587593E+09 | 17354.59 |
August | 0.155206E+09 | 6801947.57 | 0.148404E+09 | 0.541359E+09 | 0.00 |
September | 0.207837E+09 | 57224617.25 | 0.150613E+09 | 0.566026E+09 | 894836.98 |
October | 0.363596E+09 | 0.203928E+09 | 0.159668E+09 | 0.757485E+09 | 66299929.61 |
November | 0.439023E+09 | 0.290847E+09 | 0.148176E+09 | 0.780268E+09 | 0.175161E+09 |
December | 0.403558E+09 | 0.253085E+09 | 0.150473E+09 | 0.625202E+09 | 0.277546E+09 |
Annual Sum or Average | 0.322769E+10 | 0.143345E+10 | 0.179424E+10 | 0.735788E+10 | 0.111558E+10 |
Minimum of Months | 0.137147E+09 | 1441453.62 | 0.134762E+09 | 0.526265E+09 | 0.00 |
Maximum of Months | 0.439023E+09 | 0.290847E+09 | 0.171176E+09 | 0.780268E+09 | 0.287768E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.395761E+09 | 0.00 | 0.395761E+09 | 0.210605E+09 | 0.181539E+10 |
February | 0.423888E+09 | 0.00 | 0.423888E+09 | 0.417411E+09 | 0.121696E+10 |
March | 0.565620E+09 | 19327.28 | 0.565601E+09 | 0.941818E+09 | 0.723561E+09 |
April | 0.596615E+09 | 3921592.75 | 0.592693E+09 | 0.165669E+10 | 0.195535E+09 |
May | 0.681068E+09 | 20005054.12 | 0.661063E+09 | 0.244151E+10 | 18201137.84 |
June | 0.680806E+09 | 24935585.78 | 0.655870E+09 | 0.252814E+10 | 19319095.80 |
July | 0.695967E+09 | 12628417.41 | 0.683338E+09 | 0.238848E+10 | 2393014.86 |
August | 0.638697E+09 | 2895113.42 | 0.635802E+09 | 0.198154E+10 | 7504342.05 |
September | 0.549510E+09 | 64188.66 | 0.549446E+09 | 0.146185E+10 | 47029102.10 |
October | 0.491848E+09 | 0.00 | 0.491848E+09 | 0.106693E+10 | 0.516326E+09 |
November | 0.403161E+09 | 0.00 | 0.403161E+09 | 0.543167E+09 | 0.109337E+10 |
December | 0.386072E+09 | 0.00 | 0.386072E+09 | 0.249638E+09 | 0.171372E+10 |
Annual Sum or Average | 0.650901E+10 | 64469279.42 | 0.644454E+10 | 0.158878E+11 | 0.736930E+10 |
Minimum of Months | 0.386072E+09 | 0.00 | 0.386072E+09 | 0.210605E+09 | 2393014.86 |
Maximum of Months | 0.695967E+09 | 24935585.78 | 0.683338E+09 | 0.252814E+10 | 0.181539E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.395761E+09 | 0.00 | 0.395761E+09 | 0.184030E+09 | 0.188403E+10 |
February | 0.423888E+09 | 0.00 | 0.423888E+09 | 0.389219E+09 | 0.126334E+10 |
March | 0.565620E+09 | 19327.28 | 0.565601E+09 | 0.912186E+09 | 0.752799E+09 |
April | 0.596615E+09 | 3921592.75 | 0.592693E+09 | 0.162845E+10 | 0.206760E+09 |
May | 0.681068E+09 | 20005054.12 | 0.661063E+09 | 0.240797E+10 | 20533760.09 |
June | 0.680806E+09 | 24935585.78 | 0.655870E+09 | 0.249576E+10 | 21169498.30 |
July | 0.695967E+09 | 12628417.41 | 0.683338E+09 | 0.235253E+10 | 2673847.63 |
August | 0.638697E+09 | 2895113.42 | 0.635802E+09 | 0.194687E+10 | 9503968.17 |
September | 0.549510E+09 | 64188.66 | 0.549446E+09 | 0.142949E+10 | 55801565.65 |
October | 0.491848E+09 | 0.00 | 0.491848E+09 | 0.104319E+10 | 0.538186E+09 |
November | 0.403161E+09 | 0.00 | 0.403161E+09 | 0.517573E+09 | 0.113036E+10 |
December | 0.386072E+09 | 0.00 | 0.386072E+09 | 0.222912E+09 | 0.177645E+10 |
Annual Sum or Average | 0.650901E+10 | 64469279.42 | 0.644454E+10 | 0.155302E+11 | 0.766161E+10 |
Minimum of Months | 0.386072E+09 | 0.00 | 0.386072E+09 | 0.184030E+09 | 2673847.63 |
Maximum of Months | 0.695967E+09 | 24935585.78 | 0.683338E+09 | 0.249576E+10 | 0.188403E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 56539365.29 | 0.00 | 56539365.29 | 40289930.69 | 0.243911E+09 |
February | 60557776.44 | 0.00 | 60557776.44 | 75475035.65 | 0.165544E+09 |
March | 80805919.73 | 2761.14 | 80803158.59 | 0.166789E+09 | 0.101046E+09 |
April | 85233890.90 | 560248.75 | 84673642.14 | 0.279324E+09 | 31401463.69 |
May | 97299063.90 | 2857973.11 | 94441090.78 | 0.389889E+09 | 5279232.09 |
June | 97261652.82 | 3562361.46 | 93699291.36 | 0.403795E+09 | 5004739.41 |
July | 99427608.29 | 1804127.96 | 97623480.33 | 0.382825E+09 | 1021290.95 |
August | 91245924.45 | 413603.30 | 90832321.16 | 0.330652E+09 | 2991495.40 |
September | 78504458.66 | 9170.16 | 78495288.51 | 0.252961E+09 | 12439066.82 |
October | 70266640.23 | 0.00 | 70266640.23 | 0.195725E+09 | 70141284.48 |
November | 57596651.05 | 0.00 | 57596651.05 | 0.104410E+09 | 0.143537E+09 |
December | 55155161.67 | 0.00 | 55155161.67 | 49908388.03 | 0.229113E+09 |
Annual Sum or Average | 0.929894E+09 | 9210245.88 | 0.920684E+09 | 0.267204E+10 | 0.101143E+10 |
Minimum of Months | 55155161.67 | 0.00 | 55155161.67 | 40289930.69 | 1021290.95 |
Maximum of Months | 99427608.29 | 3562361.46 | 97623480.33 | 0.403795E+09 | 0.243911E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.451677E+09 | 0.181023E+09 | 0.270654E+09 | 0.535589E+09 | 0.836417E+09 |
February | 0.496998E+09 | 0.205199E+09 | 0.291799E+09 | 0.759392E+09 | 0.578801E+09 |
March | 0.671520E+09 | 0.277623E+09 | 0.393897E+09 | 0.132200E+10 | 0.364017E+09 |
April | 0.773506E+09 | 0.360643E+09 | 0.412863E+09 | 0.191971E+10 | 0.116838E+09 |
May | 0.785367E+09 | 0.348528E+09 | 0.436839E+09 | 0.225927E+10 | 19748255.18 |
June | 0.617209E+09 | 0.204246E+09 | 0.412963E+09 | 0.199671E+10 | 19016488.39 |
July | 0.535298E+09 | 0.111899E+09 | 0.423399E+09 | 0.173812E+10 | 3877734.91 |
August | 0.483812E+09 | 84179881.18 | 0.399632E+09 | 0.150773E+10 | 11284379.08 |
September | 0.499348E+09 | 0.138721E+09 | 0.360627E+09 | 0.134195E+10 | 46828240.15 |
October | 0.564510E+09 | 0.227445E+09 | 0.337066E+09 | 0.132233E+10 | 0.258446E+09 |
November | 0.483810E+09 | 0.206848E+09 | 0.276961E+09 | 0.896270E+09 | 0.511381E+09 |
December | 0.437593E+09 | 0.173749E+09 | 0.263844E+09 | 0.583475E+09 | 0.806366E+09 |
Annual Sum or Average | 0.680065E+10 | 0.252010E+10 | 0.428054E+10 | 0.161825E+11 | 0.357302E+10 |
Minimum of Months | 0.437593E+09 | 84179881.18 | 0.263844E+09 | 0.535589E+09 | 3877734.91 |
Maximum of Months | 0.785367E+09 | 0.360643E+09 | 0.436839E+09 | 0.225927E+10 | 0.836417E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257856E+09 | 0.156955E+09 | 0.100901E+09 | 0.398258E+09 | 0.222477E+09 |
February | 0.220962E+09 | 0.122735E+09 | 98226560.89 | 0.375403E+09 | 0.156691E+09 |
March | 0.207870E+09 | 91153340.39 | 0.116717E+09 | 0.428290E+09 | 99715880.84 |
April | 0.143419E+09 | 41360060.59 | 0.102059E+09 | 0.417053E+09 | 31504075.83 |
May | 0.106837E+09 | 8999401.61 | 97837742.79 | 0.416373E+09 | 5306777.80 |
June | 93513864.01 | 1626095.54 | 91887768.48 | 0.395985E+09 | 5064877.90 |
July | 0.100368E+09 | 982856.66 | 99385597.75 | 0.383811E+09 | 1017689.87 |
August | 0.105827E+09 | 4637915.08 | 0.101189E+09 | 0.362978E+09 | 2983621.23 |
September | 0.141714E+09 | 39018665.27 | 0.102695E+09 | 0.385507E+09 | 12415365.29 |
October | 0.247919E+09 | 0.139049E+09 | 0.108870E+09 | 0.548837E+09 | 69305947.54 |
November | 0.299348E+09 | 0.198314E+09 | 0.101034E+09 | 0.561198E+09 | 0.137763E+09 |
December | 0.275166E+09 | 0.172566E+09 | 0.102600E+09 | 0.449110E+09 | 0.212903E+09 |
Annual Sum or Average | 0.220080E+10 | 0.977398E+09 | 0.122340E+10 | 0.512280E+10 | 0.957148E+09 |
Minimum of Months | 93513864.01 | 982856.66 | 91887768.48 | 0.362978E+09 | 1017689.87 |
Maximum of Months | 0.299348E+09 | 0.198314E+09 | 0.116717E+09 | 0.561198E+09 | 0.222477E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 71603538.71 | 0.00 | 71603538.71 | 49967559.29 | 0.275964E+09 |
February | 76692602.88 | 0.00 | 76692602.88 | 89144245.64 | 0.181915E+09 |
March | 0.102336E+09 | 3496.82 | 0.102332E+09 | 0.182470E+09 | 0.109639E+09 |
April | 0.107943E+09 | 709519.70 | 0.107234E+09 | 0.304346E+09 | 30116387.78 |
May | 0.123223E+09 | 3619442.62 | 0.119604E+09 | 0.445475E+09 | 2391785.96 |
June | 0.123176E+09 | 4511506.01 | 0.118664E+09 | 0.461130E+09 | 2365289.56 |
July | 0.125919E+09 | 2284814.22 | 0.123634E+09 | 0.437390E+09 | 282314.95 |
August | 0.115557E+09 | 523802.48 | 0.115033E+09 | 0.363724E+09 | 666414.24 |
September | 99420943.54 | 11613.42 | 99409330.12 | 0.274070E+09 | 5465884.95 |
October | 88988266.27 | 0.00 | 88988266.27 | 0.197234E+09 | 83230327.89 |
November | 72942524.41 | 0.00 | 72942524.41 | 0.106808E+09 | 0.172333E+09 |
December | 69850532.15 | 0.00 | 69850532.15 | 57412293.99 | 0.261655E+09 |
Annual Sum or Average | 0.117765E+10 | 11664195.27 | 0.116599E+10 | 0.296917E+10 | 0.112602E+10 |
Minimum of Months | 69850532.15 | 0.00 | 69850532.15 | 49967559.29 | 282314.95 |
Maximum of Months | 0.125919E+09 | 4511506.01 | 0.123634E+09 | 0.461130E+09 | 0.275964E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 64063957.39 | 0.00 | 64063957.39 | 44706164.62 | 0.246892E+09 |
February | 68617162.38 | 0.00 | 68617162.38 | 79757694.34 | 0.162760E+09 |
March | 91560047.97 | 3128.61 | 91556919.35 | 0.163256E+09 | 98094371.60 |
April | 96577319.64 | 634809.96 | 95942509.68 | 0.272300E+09 | 26945246.26 |
May | 0.110248E+09 | 3238329.03 | 0.107010E+09 | 0.398568E+09 | 2139939.96 |
June | 0.110206E+09 | 4036461.52 | 0.106169E+09 | 0.412574E+09 | 2116233.53 |
July | 0.112660E+09 | 2044231.94 | 0.110616E+09 | 0.391334E+09 | 252588.26 |
August | 0.103389E+09 | 468648.06 | 0.102921E+09 | 0.325425E+09 | 596243.34 |
September | 88952294.89 | 10390.57 | 88941904.32 | 0.245212E+09 | 4890347.97 |
October | 79618139.01 | 0.00 | 79618139.01 | 0.176466E+09 | 74466508.38 |
November | 65261952.97 | 0.00 | 65261952.97 | 95561624.31 | 0.154187E+09 |
December | 62495535.78 | 0.00 | 62495535.78 | 51366996.97 | 0.234086E+09 |
Annual Sum or Average | 0.105365E+10 | 10435999.71 | 0.104321E+10 | 0.265653E+10 | 0.100743E+10 |
Minimum of Months | 62495535.78 | 0.00 | 62495535.78 | 44706164.62 | 252588.26 |
Maximum of Months | 0.112660E+09 | 4036461.52 | 0.110616E+09 | 0.412574E+09 | 0.246892E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.962655E+09 | 0.585960E+09 | 0.376695E+09 | 0.146288E+10 | 0.732783E+09 |
February | 0.824915E+09 | 0.458206E+09 | 0.366709E+09 | 0.136542E+10 | 0.503724E+09 |
March | 0.776040E+09 | 0.340303E+09 | 0.435738E+09 | 0.149945E+10 | 0.317276E+09 |
April | 0.535427E+09 | 0.154409E+09 | 0.381017E+09 | 0.140355E+10 | 89828332.23 |
May | 0.398855E+09 | 33597447.91 | 0.365257E+09 | 0.140863E+10 | 7190410.88 |
June | 0.349115E+09 | 6070699.19 | 0.343044E+09 | 0.133176E+10 | 7149851.52 |
July | 0.374705E+09 | 3669296.80 | 0.371036E+09 | 0.129498E+10 | 838613.70 |
August | 0.395085E+09 | 17314719.02 | 0.377770E+09 | 0.118980E+10 | 1970322.71 |
September | 0.529061E+09 | 0.145668E+09 | 0.383392E+09 | 0.129732E+10 | 15916953.74 |
October | 0.925554E+09 | 0.519110E+09 | 0.406443E+09 | 0.189048E+10 | 0.240240E+09 |
November | 0.111756E+10 | 0.740366E+09 | 0.377190E+09 | 0.200262E+10 | 0.482290E+09 |
December | 0.102728E+10 | 0.644242E+09 | 0.383037E+09 | 0.163761E+10 | 0.706644E+09 |
Annual Sum or Average | 0.821625E+10 | 0.364892E+10 | 0.456733E+10 | 0.177845E+11 | 0.310585E+10 |
Minimum of Months | 0.349115E+09 | 3669296.80 | 0.343044E+09 | 0.118980E+10 | 838613.70 |
Maximum of Months | 0.111756E+10 | 0.740366E+09 | 0.435738E+09 | 0.200262E+10 | 0.732783E+09 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 722.27 | 372.02 | 486.92 | 296.38 | 190.53 | 0.00 | 0.00 |
February | 746.95 | 287.73 | 461.95 | 256.60 | 205.36 | 0.00 | 0.00 |
March | 740.73 | 168.67 | 392.53 | 172.13 | 220.40 | 0.00 | 0.00 |
April | 706.99 | 51.44 | 279.85 | 80.71 | 199.14 | 0.00 | 0.00 |
May | 668.89 | 4.64 | 201.74 | 16.99 | 184.75 | 0.00 | 0.00 |
June | 658.57 | 3.65 | 182.47 | 3.17 | 179.30 | 0.00 | 0.00 |
July | 619.74 | 0.43 | 189.53 | 1.86 | 187.67 | 0.00 | 0.00 |
August | 576.40 | 1.21 | 199.84 | 8.76 | 191.08 | 0.00 | 0.00 |
September | 657.80 | 11.38 | 276.52 | 76.14 | 200.39 | 0.00 | 0.00 |
October | 931.86 | 131.47 | 468.15 | 262.57 | 205.58 | 0.00 | 0.00 |
November | 1015.40 | 266.30 | 584.11 | 386.97 | 197.14 | 0.00 | 0.00 |
December | 802.29 | 363.47 | 519.61 | 325.86 | 193.74 | 0.00 | 0.00 |
Annual Sum or Average | 737.00 | 137.92 | 352.96 | 156.75 | 196.21 | 0.00 | 0.00 |
Minimum of Months | 576.40 | 0.43 | 182.47 | 1.86 | 179.30 | 0.00 | 0.00 |
Maximum of Months | 1015.40 | 372.02 | 584.11 | 386.97 | 220.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1982.85 | 1166.13 | 1371.13 | 834.60 | 536.53 | 0.00 | 0.00 |
February | 2056.47 | 912.47 | 1300.83 | 722.56 | 578.27 | 0.00 | 0.00 |
March | 2055.22 | 531.31 | 1105.33 | 484.70 | 620.63 | 0.00 | 0.00 |
April | 1982.76 | 158.34 | 788.04 | 227.26 | 560.78 | 0.00 | 0.00 |
May | 1888.36 | 15.20 | 568.09 | 47.85 | 520.24 | 0.00 | 0.00 |
June | 1857.59 | 13.83 | 513.82 | 8.93 | 504.89 | 0.00 | 0.00 |
July | 1743.52 | 1.82 | 533.70 | 5.23 | 528.47 | 0.00 | 0.00 |
August | 1618.09 | 6.00 | 562.73 | 24.66 | 538.06 | 0.00 | 0.00 |
September | 1826.08 | 39.94 | 778.67 | 214.40 | 564.27 | 0.00 | 0.00 |
October | 2603.82 | 397.38 | 1318.29 | 739.38 | 578.90 | 0.00 | 0.00 |
November | 2824.05 | 819.42 | 1644.82 | 1089.67 | 555.15 | 0.00 | 0.00 |
December | 2205.37 | 1140.07 | 1463.18 | 917.61 | 545.57 | 0.00 | 0.00 |
Annual Sum or Average | 2052.91 | 431.48 | 993.92 | 441.41 | 552.51 | 0.00 | 0.00 |
Minimum of Months | 1618.09 | 1.82 | 513.82 | 5.23 | 504.89 | 0.00 | 0.00 |
Maximum of Months | 2824.05 | 1166.13 | 1644.82 | 1089.67 | 620.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2638.30 | 1570.93 | 1781.18 | 1084.19 | 696.99 | 0.00 | 0.00 |
February | 2744.94 | 1215.93 | 1689.86 | 938.65 | 751.21 | 0.00 | 0.00 |
March | 2754.26 | 693.73 | 1435.89 | 629.66 | 806.23 | 0.00 | 0.00 |
April | 2676.83 | 202.02 | 1023.70 | 295.22 | 728.48 | 0.00 | 0.00 |
May | 2557.97 | 18.55 | 737.99 | 62.16 | 675.82 | 0.00 | 0.00 |
June | 2508.86 | 17.05 | 667.49 | 11.61 | 655.88 | 0.00 | 0.00 |
July | 2348.99 | 2.41 | 693.30 | 6.79 | 686.52 | 0.00 | 0.00 |
August | 2175.06 | 7.41 | 731.01 | 32.04 | 698.98 | 0.00 | 0.00 |
September | 2444.54 | 48.03 | 1011.54 | 278.51 | 733.03 | 0.00 | 0.00 |
October | 3472.93 | 510.74 | 1712.53 | 960.50 | 752.03 | 0.00 | 0.00 |
November | 3760.30 | 1071.59 | 2136.72 | 1415.55 | 721.17 | 0.00 | 0.00 |
December | 2935.73 | 1526.17 | 1900.75 | 1192.03 | 708.72 | 0.00 | 0.00 |
Annual Sum or Average | 2750.56 | 571.05 | 1291.15 | 573.42 | 717.74 | 0.00 | 0.00 |
Minimum of Months | 2175.06 | 2.41 | 667.49 | 6.79 | 655.88 | 0.00 | 0.00 |
Maximum of Months | 3760.30 | 1570.93 | 2136.72 | 1415.55 | 806.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 246.36 | 211.90 | 178.88 | 90.74 | 88.13 | 0.00 | 0.00 |
February | 292.99 | 156.02 | 186.03 | 85.72 | 100.31 | 0.00 | 0.00 |
March | 382.18 | 76.86 | 200.34 | 83.22 | 117.12 | 0.00 | 0.00 |
April | 508.68 | 14.92 | 204.01 | 85.58 | 118.43 | 0.00 | 0.00 |
May | 565.36 | 0.13 | 180.84 | 63.15 | 117.69 | 0.00 | 0.00 |
June | 563.43 | 0.55 | 168.69 | 52.27 | 116.41 | 0.00 | 0.00 |
July | 472.49 | 0.03 | 135.62 | 19.39 | 116.23 | 0.00 | 0.00 |
August | 416.26 | 0.00 | 129.61 | 17.61 | 112.00 | 0.00 | 0.00 |
September | 409.45 | 1.01 | 154.17 | 44.48 | 109.69 | 0.00 | 0.00 |
October | 417.42 | 51.08 | 196.03 | 93.23 | 102.80 | 0.00 | 0.00 |
November | 370.39 | 134.58 | 208.98 | 116.41 | 92.56 | 0.00 | 0.00 |
December | 265.14 | 202.82 | 182.51 | 94.76 | 87.74 | 0.00 | 0.00 |
Annual Sum or Average | 409.54 | 70.49 | 176.99 | 70.38 | 106.62 | 0.00 | 0.00 |
Minimum of Months | 246.36 | 0.00 | 129.61 | 17.61 | 87.74 | 0.00 | 0.00 |
Maximum of Months | 565.36 | 211.90 | 208.98 | 116.41 | 118.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 125.75 | 218.48 | 103.71 | 32.14 | 71.57 | 0.00 | 0.00 |
February | 176.47 | 162.32 | 119.73 | 34.99 | 84.74 | 0.00 | 0.00 |
March | 286.89 | 81.64 | 152.90 | 49.19 | 103.71 | 0.00 | 0.00 |
April | 456.49 | 15.49 | 181.56 | 69.84 | 111.72 | 0.00 | 0.00 |
May | 556.22 | 0.14 | 177.28 | 60.86 | 116.42 | 0.00 | 0.00 |
June | 566.14 | 0.58 | 170.13 | 53.02 | 117.11 | 0.00 | 0.00 |
July | 471.99 | 0.03 | 135.27 | 19.69 | 115.58 | 0.00 | 0.00 |
August | 404.96 | 0.00 | 124.16 | 16.03 | 108.13 | 0.00 | 0.00 |
September | 360.58 | 0.97 | 129.78 | 29.43 | 100.35 | 0.00 | 0.00 |
October | 288.15 | 53.47 | 129.70 | 41.31 | 88.39 | 0.00 | 0.00 |
November | 201.64 | 140.42 | 115.71 | 39.90 | 75.81 | 0.00 | 0.00 |
December | 128.71 | 207.48 | 100.37 | 30.33 | 70.03 | 0.00 | 0.00 |
Annual Sum or Average | 335.97 | 73.06 | 136.69 | 39.68 | 97.02 | 0.00 | 0.00 |
Minimum of Months | 125.75 | 0.00 | 100.37 | 16.03 | 70.03 | 0.00 | 0.00 |
Maximum of Months | 566.14 | 218.48 | 181.56 | 69.84 | 117.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 101.74 | 85.70 | 77.00 | 46.87 | 30.13 | 0.00 | 0.00 |
February | 106.25 | 68.89 | 73.05 | 40.58 | 32.48 | 0.00 | 0.00 |
March | 106.64 | 42.88 | 62.08 | 27.22 | 34.85 | 0.00 | 0.00 |
April | 101.77 | 16.54 | 44.26 | 12.76 | 31.49 | 0.00 | 0.00 |
May | 93.98 | 3.76 | 31.90 | 2.69 | 29.22 | 0.00 | 0.00 |
June | 90.70 | 2.71 | 28.86 | 0.50 | 28.35 | 0.00 | 0.00 |
July | 82.82 | 1.13 | 29.97 | 0.29 | 29.68 | 0.00 | 0.00 |
August | 76.63 | 3.12 | 31.60 | 1.39 | 30.22 | 0.00 | 0.00 |
September | 91.48 | 9.46 | 43.73 | 12.04 | 31.69 | 0.00 | 0.00 |
October | 139.34 | 33.57 | 74.04 | 41.52 | 32.51 | 0.00 | 0.00 |
November | 151.89 | 60.69 | 92.37 | 61.20 | 31.18 | 0.00 | 0.00 |
December | 114.89 | 82.87 | 82.17 | 51.53 | 30.64 | 0.00 | 0.00 |
Annual Sum or Average | 104.79 | 34.12 | 55.82 | 24.79 | 31.03 | 0.00 | 0.00 |
Minimum of Months | 76.63 | 1.13 | 28.86 | 0.29 | 28.35 | 0.00 | 0.00 |
Maximum of Months | 151.89 | 85.70 | 92.37 | 61.20 | 34.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 13.21 | 63.50 | 16.89 | 0.00 | 16.89 | 0.00 | 0.00 |
February | 25.20 | 45.65 | 20.03 | 0.00 | 20.03 | 0.00 | 0.00 |
March | 47.84 | 21.29 | 24.14 | 0.00 | 24.14 | 0.00 | 0.00 |
April | 87.22 | 3.32 | 26.31 | 0.17 | 26.14 | 0.00 | 0.00 |
May | 124.39 | 0.00 | 29.07 | 0.85 | 28.21 | 0.00 | 0.00 |
June | 132.10 | 0.05 | 30.02 | 1.10 | 28.92 | 0.00 | 0.00 |
July | 122.94 | 0.00 | 29.70 | 0.54 | 29.16 | 0.00 | 0.00 |
August | 104.79 | 0.00 | 27.26 | 0.12 | 27.13 | 0.00 | 0.00 |
September | 83.34 | 0.11 | 24.23 | 0.00 | 24.23 | 0.00 | 0.00 |
October | 53.79 | 13.13 | 20.99 | 0.00 | 20.99 | 0.00 | 0.00 |
November | 29.41 | 38.01 | 17.78 | 0.00 | 17.78 | 0.00 | 0.00 |
December | 15.04 | 59.90 | 16.48 | 0.00 | 16.48 | 0.00 | 0.00 |
Annual Sum or Average | 70.16 | 20.32 | 23.59 | 0.23 | 23.36 | 0.00 | 0.00 |
Minimum of Months | 13.21 | 0.00 | 16.48 | 0.00 | 16.48 | 0.00 | 0.00 |
Maximum of Months | 132.10 | 63.50 | 30.02 | 1.10 | 29.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 239.57 | 203.32 | 180.60 | 92.40 | 88.20 | 0.00 | 0.00 |
February | 298.95 | 148.90 | 194.06 | 93.15 | 100.92 | 0.00 | 0.00 |
March | 383.37 | 72.35 | 202.98 | 85.86 | 117.11 | 0.00 | 0.00 |
April | 510.58 | 14.06 | 204.55 | 85.53 | 119.02 | 0.00 | 0.00 |
May | 575.74 | 0.10 | 186.51 | 68.43 | 118.08 | 0.00 | 0.00 |
June | 539.09 | 0.52 | 155.15 | 40.03 | 115.12 | 0.00 | 0.00 |
July | 475.10 | 0.03 | 137.41 | 21.26 | 116.15 | 0.00 | 0.00 |
August | 416.06 | 0.00 | 129.84 | 17.45 | 112.39 | 0.00 | 0.00 |
September | 403.85 | 0.93 | 151.01 | 41.81 | 109.19 | 0.00 | 0.00 |
October | 419.24 | 49.25 | 197.95 | 94.38 | 103.57 | 0.00 | 0.00 |
November | 363.79 | 129.18 | 208.82 | 116.41 | 92.41 | 0.00 | 0.00 |
December | 262.14 | 197.81 | 184.43 | 96.87 | 87.56 | 0.00 | 0.00 |
Annual Sum or Average | 407.66 | 67.72 | 177.62 | 70.95 | 106.67 | 0.00 | 0.00 |
Minimum of Months | 239.57 | 0.00 | 129.84 | 17.45 | 87.56 | 0.00 | 0.00 |
Maximum of Months | 575.74 | 203.32 | 208.82 | 116.41 | 119.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 111.61 | 201.06 | 105.43 | 33.80 | 71.64 | 0.00 | 0.00 |
February | 177.74 | 150.60 | 127.76 | 42.41 | 85.35 | 0.00 | 0.00 |
March | 285.29 | 75.87 | 155.54 | 51.83 | 103.71 | 0.00 | 0.00 |
April | 457.35 | 14.54 | 182.10 | 69.79 | 112.31 | 0.00 | 0.00 |
May | 566.54 | 0.11 | 182.95 | 66.13 | 116.81 | 0.00 | 0.00 |
June | 541.79 | 0.54 | 156.59 | 40.78 | 115.82 | 0.00 | 0.00 |
July | 474.60 | 0.03 | 137.06 | 21.56 | 115.49 | 0.00 | 0.00 |
August | 404.75 | 0.00 | 124.39 | 15.87 | 108.52 | 0.00 | 0.00 |
September | 354.93 | 0.87 | 126.62 | 26.76 | 99.85 | 0.00 | 0.00 |
October | 288.04 | 50.69 | 131.62 | 42.46 | 89.16 | 0.00 | 0.00 |
November | 190.79 | 131.66 | 115.56 | 39.90 | 75.65 | 0.00 | 0.00 |
December | 120.91 | 196.86 | 102.29 | 32.44 | 69.85 | 0.00 | 0.00 |
Annual Sum or Average | 331.85 | 68.24 | 137.32 | 40.25 | 97.07 | 0.00 | 0.00 |
Minimum of Months | 111.61 | 0.00 | 102.29 | 15.87 | 69.85 | 0.00 | 0.00 |
Maximum of Months | 566.54 | 201.06 | 182.95 | 69.79 | 116.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 278.24 | 262.36 | 203.43 | 101.56 | 101.88 | 0.00 | 0.00 |
February | 316.27 | 200.18 | 201.68 | 87.92 | 113.75 | 0.00 | 0.00 |
March | 363.04 | 110.76 | 186.79 | 58.98 | 127.81 | 0.00 | 0.00 |
April | 427.81 | 30.11 | 152.89 | 28.03 | 124.86 | 0.00 | 0.00 |
May | 490.30 | 1.90 | 132.09 | 7.67 | 124.42 | 0.00 | 0.00 |
June | 503.20 | 2.07 | 127.56 | 3.47 | 124.09 | 0.00 | 0.00 |
July | 468.86 | 0.27 | 129.29 | 1.80 | 127.48 | 0.00 | 0.00 |
August | 413.21 | 0.23 | 127.52 | 3.27 | 124.25 | 0.00 | 0.00 |
September | 394.75 | 4.80 | 147.25 | 26.09 | 121.15 | 0.00 | 0.00 |
October | 437.42 | 84.04 | 205.89 | 89.97 | 115.92 | 0.00 | 0.00 |
November | 416.90 | 182.89 | 238.66 | 132.59 | 106.07 | 0.00 | 0.00 |
December | 309.67 | 256.98 | 213.74 | 111.66 | 102.08 | 0.00 | 0.00 |
Annual Sum or Average | 401.97 | 94.28 | 172.05 | 54.22 | 117.83 | 0.00 | 0.00 |
Minimum of Months | 278.24 | 0.23 | 127.52 | 1.80 | 101.88 | 0.00 | 0.00 |
Maximum of Months | 503.20 | 262.36 | 238.66 | 132.59 | 127.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 244.69 | 208.19 | 178.88 | 90.74 | 88.13 | 0.00 | 0.00 |
February | 290.30 | 153.27 | 186.03 | 85.72 | 100.31 | 0.00 | 0.00 |
March | 378.80 | 74.85 | 200.34 | 83.22 | 117.12 | 0.00 | 0.00 |
April | 505.47 | 14.04 | 204.01 | 85.58 | 118.43 | 0.00 | 0.00 |
May | 563.72 | 0.08 | 180.84 | 63.15 | 117.69 | 0.00 | 0.00 |
June | 560.56 | 0.56 | 168.69 | 52.27 | 116.41 | 0.00 | 0.00 |
July | 471.03 | 0.02 | 135.62 | 19.39 | 116.23 | 0.00 | 0.00 |
August | 414.55 | 0.00 | 129.61 | 17.61 | 112.00 | 0.00 | 0.00 |
September | 407.35 | 0.85 | 154.17 | 44.48 | 109.69 | 0.00 | 0.00 |
October | 414.98 | 49.33 | 196.03 | 93.23 | 102.80 | 0.00 | 0.00 |
November | 368.48 | 131.72 | 208.98 | 116.41 | 92.56 | 0.00 | 0.00 |
December | 264.16 | 199.10 | 182.51 | 94.76 | 87.74 | 0.00 | 0.00 |
Annual Sum or Average | 407.38 | 69.00 | 176.99 | 70.38 | 106.62 | 0.00 | 0.00 |
Minimum of Months | 244.69 | 0.00 | 129.61 | 17.61 | 87.74 | 0.00 | 0.00 |
Maximum of Months | 563.72 | 208.19 | 208.98 | 116.41 | 118.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 125.20 | 213.75 | 103.71 | 32.14 | 71.57 | 0.00 | 0.00 |
February | 174.84 | 159.18 | 119.73 | 34.99 | 84.74 | 0.00 | 0.00 |
March | 284.58 | 79.50 | 152.90 | 49.19 | 103.71 | 0.00 | 0.00 |
April | 454.11 | 14.44 | 181.56 | 69.84 | 111.72 | 0.00 | 0.00 |
May | 554.71 | 0.09 | 177.28 | 60.86 | 116.42 | 0.00 | 0.00 |
June | 563.23 | 0.58 | 170.13 | 53.02 | 117.11 | 0.00 | 0.00 |
July | 470.45 | 0.02 | 135.27 | 19.69 | 115.58 | 0.00 | 0.00 |
August | 403.40 | 0.00 | 124.16 | 16.03 | 108.13 | 0.00 | 0.00 |
September | 359.08 | 0.81 | 129.78 | 29.43 | 100.35 | 0.00 | 0.00 |
October | 286.92 | 51.08 | 129.70 | 41.31 | 88.39 | 0.00 | 0.00 |
November | 201.14 | 136.44 | 115.71 | 39.90 | 75.81 | 0.00 | 0.00 |
December | 128.98 | 202.35 | 100.37 | 30.33 | 70.03 | 0.00 | 0.00 |
Annual Sum or Average | 334.53 | 71.17 | 136.69 | 39.68 | 97.02 | 0.00 | 0.00 |
Minimum of Months | 125.20 | 0.00 | 100.37 | 16.03 | 70.03 | 0.00 | 0.00 |
Maximum of Months | 563.23 | 213.75 | 181.56 | 69.84 | 117.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 207.93 | 107.44 | 141.19 | 85.94 | 55.25 | 0.00 | 0.00 |
February | 217.54 | 78.59 | 133.95 | 74.41 | 59.55 | 0.00 | 0.00 |
March | 222.50 | 37.52 | 113.82 | 49.91 | 63.91 | 0.00 | 0.00 |
April | 229.22 | 6.46 | 81.15 | 23.40 | 57.75 | 0.00 | 0.00 |
May | 234.70 | 0.01 | 58.50 | 4.93 | 53.57 | 0.00 | 0.00 |
June | 230.72 | 0.20 | 52.91 | 0.92 | 51.99 | 0.00 | 0.00 |
July | 219.38 | 0.01 | 54.96 | 0.54 | 54.42 | 0.00 | 0.00 |
August | 202.12 | 0.00 | 57.95 | 2.54 | 55.41 | 0.00 | 0.00 |
September | 218.37 | 0.35 | 80.18 | 22.08 | 58.11 | 0.00 | 0.00 |
October | 282.81 | 24.75 | 135.75 | 76.14 | 59.61 | 0.00 | 0.00 |
November | 301.03 | 67.58 | 169.38 | 112.21 | 57.17 | 0.00 | 0.00 |
December | 233.42 | 103.62 | 150.67 | 94.49 | 56.18 | 0.00 | 0.00 |
Annual Sum or Average | 233.32 | 35.37 | 102.35 | 45.45 | 56.89 | 0.00 | 0.00 |
Minimum of Months | 202.12 | 0.00 | 52.91 | 0.54 | 51.99 | 0.00 | 0.00 |
Maximum of Months | 301.03 | 107.44 | 169.38 | 112.21 | 63.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 78.63 | 677.79 | 147.76 | 0.00 | 147.76 | 0.00 | 0.00 |
February | 172.54 | 503.04 | 175.22 | 0.00 | 175.22 | 0.00 | 0.00 |
March | 351.63 | 270.15 | 211.18 | 0.01 | 211.17 | 0.00 | 0.00 |
April | 639.15 | 75.44 | 230.18 | 1.51 | 228.66 | 0.00 | 0.00 |
May | 911.55 | 6.80 | 254.28 | 7.47 | 246.81 | 0.00 | 0.00 |
June | 975.36 | 7.45 | 262.66 | 9.62 | 253.04 | 0.00 | 0.00 |
July | 891.76 | 0.89 | 259.84 | 4.71 | 255.13 | 0.00 | 0.00 |
August | 739.82 | 2.80 | 238.46 | 1.08 | 237.38 | 0.00 | 0.00 |
September | 563.99 | 18.14 | 212.00 | 0.02 | 211.98 | 0.00 | 0.00 |
October | 398.35 | 192.77 | 183.63 | 0.00 | 183.63 | 0.00 | 0.00 |
November | 209.56 | 421.82 | 155.54 | 0.00 | 155.54 | 0.00 | 0.00 |
December | 93.20 | 639.83 | 144.14 | 0.00 | 144.14 | 0.00 | 0.00 |
Annual Sum or Average | 503.80 | 233.68 | 206.40 | 2.04 | 204.36 | 0.00 | 0.00 |
Minimum of Months | 78.63 | 0.89 | 144.14 | 0.00 | 144.14 | 0.00 | 0.00 |
Maximum of Months | 975.36 | 677.79 | 262.66 | 9.62 | 255.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 68.71 | 703.42 | 147.76 | 0.00 | 147.76 | 0.00 | 0.00 |
February | 160.89 | 522.22 | 175.22 | 0.00 | 175.22 | 0.00 | 0.00 |
March | 340.57 | 281.06 | 211.18 | 0.01 | 211.17 | 0.00 | 0.00 |
April | 628.26 | 79.77 | 230.18 | 1.51 | 228.66 | 0.00 | 0.00 |
May | 899.03 | 7.67 | 254.28 | 7.47 | 246.81 | 0.00 | 0.00 |
June | 962.87 | 8.17 | 262.66 | 9.62 | 253.04 | 0.00 | 0.00 |
July | 878.33 | 1.00 | 259.84 | 4.71 | 255.13 | 0.00 | 0.00 |
August | 726.88 | 3.55 | 238.46 | 1.08 | 237.38 | 0.00 | 0.00 |
September | 551.50 | 21.53 | 212.00 | 0.02 | 211.98 | 0.00 | 0.00 |
October | 389.48 | 200.94 | 183.63 | 0.00 | 183.63 | 0.00 | 0.00 |
November | 199.68 | 436.09 | 155.54 | 0.00 | 155.54 | 0.00 | 0.00 |
December | 83.23 | 663.25 | 144.14 | 0.00 | 144.14 | 0.00 | 0.00 |
Annual Sum or Average | 492.46 | 242.95 | 206.40 | 2.04 | 204.36 | 0.00 | 0.00 |
Minimum of Months | 68.71 | 1.00 | 144.14 | 0.00 | 144.14 | 0.00 | 0.00 |
Maximum of Months | 962.87 | 703.42 | 262.66 | 9.62 | 255.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 354.03 | 476.74 | 286.02 | 126.19 | 159.83 | 0.00 | 0.00 |
February | 494.91 | 367.09 | 321.81 | 135.55 | 186.25 | 0.00 | 0.00 |
March | 713.28 | 208.39 | 358.50 | 137.69 | 220.81 | 0.00 | 0.00 |
April | 1009.08 | 69.13 | 386.64 | 155.31 | 231.33 | 0.00 | 0.00 |
May | 1144.53 | 11.32 | 369.44 | 134.55 | 234.89 | 0.00 | 0.00 |
June | 1078.87 | 11.20 | 311.72 | 80.80 | 230.92 | 0.00 | 0.00 |
July | 935.17 | 2.21 | 274.45 | 42.82 | 231.63 | 0.00 | 0.00 |
August | 821.89 | 6.44 | 254.21 | 33.32 | 220.90 | 0.00 | 0.00 |
September | 764.05 | 27.66 | 277.61 | 68.58 | 209.03 | 0.00 | 0.00 |
October | 771.20 | 148.07 | 329.56 | 136.83 | 192.73 | 0.00 | 0.00 |
November | 600.26 | 303.50 | 324.37 | 156.31 | 168.05 | 0.00 | 0.00 |
December | 397.15 | 459.08 | 286.71 | 129.30 | 157.41 | 0.00 | 0.00 |
Annual Sum or Average | 758.03 | 173.43 | 314.92 | 111.20 | 203.72 | 0.00 | 0.00 |
Minimum of Months | 354.03 | 2.21 | 254.21 | 33.32 | 157.41 | 0.00 | 0.00 |
Maximum of Months | 1144.53 | 476.74 | 386.64 | 156.31 | 234.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 570.15 | 457.43 | 410.07 | 218.77 | 191.29 | 0.00 | 0.00 |
February | 630.02 | 346.48 | 401.05 | 189.40 | 211.65 | 0.00 | 0.00 |
March | 688.44 | 195.54 | 362.13 | 127.06 | 235.08 | 0.00 | 0.00 |
April | 763.86 | 56.57 | 285.47 | 60.09 | 225.38 | 0.00 | 0.00 |
May | 841.04 | 4.37 | 236.08 | 15.10 | 220.98 | 0.00 | 0.00 |
June | 850.86 | 4.48 | 224.73 | 5.64 | 219.09 | 0.00 | 0.00 |
July | 792.90 | 0.51 | 228.97 | 2.99 | 225.99 | 0.00 | 0.00 |
August | 701.52 | 1.21 | 229.25 | 6.84 | 222.42 | 0.00 | 0.00 |
September | 700.85 | 10.13 | 276.79 | 56.21 | 220.58 | 0.00 | 0.00 |
October | 844.95 | 148.18 | 408.51 | 193.81 | 214.70 | 0.00 | 0.00 |
November | 847.78 | 309.13 | 484.48 | 285.64 | 198.84 | 0.00 | 0.00 |
December | 641.86 | 438.75 | 432.95 | 240.53 | 192.42 | 0.00 | 0.00 |
Annual Sum or Average | 739.86 | 163.66 | 331.29 | 116.41 | 214.88 | 0.00 | 0.00 |
Minimum of Months | 570.15 | 0.51 | 224.73 | 2.99 | 191.29 | 0.00 | 0.00 |
Maximum of Months | 850.86 | 457.43 | 484.48 | 285.64 | 235.08 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.193452E+10 | 0.996421E+09 | 0.130416E+10 | 0.793836E+09 | 0.510329E+09 | 0.00 | 0.00 |
February | 0.180701E+10 | 0.696084E+09 | 0.111756E+10 | 0.620760E+09 | 0.496800E+09 | 0.00 | 0.00 |
March | 0.198398E+10 | 0.451765E+09 | 0.105134E+10 | 0.461029E+09 | 0.590316E+09 | 0.00 | 0.00 |
April | 0.183251E+10 | 0.133332E+09 | 0.725369E+09 | 0.209188E+09 | 0.516181E+09 | 0.00 | 0.00 |
May | 0.179155E+10 | 12436391.99 | 0.540347E+09 | 45516539.57 | 0.494830E+09 | 0.00 | 0.00 |
June | 0.170701E+10 | 9453310.47 | 0.472962E+09 | 8224351.46 | 0.464737E+09 | 0.00 | 0.00 |
July | 0.165991E+10 | 1161047.38 | 0.507632E+09 | 4971023.20 | 0.502661E+09 | 0.00 | 0.00 |
August | 0.154383E+10 | 3249713.17 | 0.535242E+09 | 23457320.20 | 0.511785E+09 | 0.00 | 0.00 |
September | 0.170501E+10 | 29488445.47 | 0.716747E+09 | 0.197346E+09 | 0.519402E+09 | 0.00 | 0.00 |
October | 0.249590E+10 | 0.352131E+09 | 0.125390E+10 | 0.703271E+09 | 0.550629E+09 | 0.00 | 0.00 |
November | 0.263193E+10 | 0.690248E+09 | 0.151402E+10 | 0.100302E+10 | 0.510999E+09 | 0.00 | 0.00 |
December | 0.214884E+10 | 0.973517E+09 | 0.139171E+10 | 0.872794E+09 | 0.518920E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.232420E+11 | 0.434929E+10 | 0.111310E+11 | 0.494341E+10 | 0.618759E+10 | 0.00 | 0.00 |
Minimum of Months | 0.154383E+10 | 1161047.38 | 0.472962E+09 | 4971023.20 | 0.464737E+09 | 0.00 | 0.00 |
Maximum of Months | 0.263193E+10 | 0.996421E+09 | 0.151402E+10 | 0.100302E+10 | 0.590316E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.531087E+10 | 0.312335E+10 | 0.367244E+10 | 0.223539E+10 | 0.143705E+10 | 0.00 | 0.00 |
February | 0.497502E+10 | 0.220745E+10 | 0.314698E+10 | 0.174802E+10 | 0.139896E+10 | 0.00 | 0.00 |
March | 0.550470E+10 | 0.142306E+10 | 0.296052E+10 | 0.129823E+10 | 0.166229E+10 | 0.00 | 0.00 |
April | 0.513931E+10 | 0.410416E+09 | 0.204259E+10 | 0.589060E+09 | 0.145353E+10 | 0.00 | 0.00 |
May | 0.505779E+10 | 40702636.61 | 0.152158E+10 | 0.128172E+09 | 0.139341E+10 | 0.00 | 0.00 |
June | 0.481488E+10 | 35835303.12 | 0.133183E+10 | 23159231.46 | 0.130867E+10 | 0.00 | 0.00 |
July | 0.466985E+10 | 4887136.22 | 0.142946E+10 | 13998073.57 | 0.141546E+10 | 0.00 | 0.00 |
August | 0.433389E+10 | 16068165.26 | 0.150721E+10 | 66054267.05 | 0.144115E+10 | 0.00 | 0.00 |
September | 0.473321E+10 | 0.103515E+09 | 0.201831E+10 | 0.555713E+09 | 0.146260E+10 | 0.00 | 0.00 |
October | 0.697408E+10 | 0.106434E+10 | 0.353090E+10 | 0.198036E+10 | 0.155054E+10 | 0.00 | 0.00 |
November | 0.731994E+10 | 0.212394E+10 | 0.426338E+10 | 0.282444E+10 | 0.143894E+10 | 0.00 | 0.00 |
December | 0.590686E+10 | 0.305356E+10 | 0.391898E+10 | 0.245773E+10 | 0.146125E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.647404E+11 | 0.136071E+11 | 0.313442E+11 | 0.139203E+11 | 0.174238E+11 | 0.00 | 0.00 |
Minimum of Months | 0.433389E+10 | 4887136.22 | 0.133183E+10 | 13998073.57 | 0.130867E+10 | 0.00 | 0.00 |
Maximum of Months | 0.731994E+10 | 0.312335E+10 | 0.426338E+10 | 0.282444E+10 | 0.166229E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.706643E+10 | 0.420757E+10 | 0.477071E+10 | 0.290390E+10 | 0.186681E+10 | 0.00 | 0.00 |
February | 0.664055E+10 | 0.294157E+10 | 0.408810E+10 | 0.227078E+10 | 0.181732E+10 | 0.00 | 0.00 |
March | 0.737702E+10 | 0.185808E+10 | 0.384588E+10 | 0.168647E+10 | 0.215941E+10 | 0.00 | 0.00 |
April | 0.693835E+10 | 0.523638E+09 | 0.265344E+10 | 0.765222E+09 | 0.188822E+10 | 0.00 | 0.00 |
May | 0.685126E+10 | 49684248.75 | 0.197662E+10 | 0.166502E+09 | 0.181012E+10 | 0.00 | 0.00 |
June | 0.650296E+10 | 44192191.27 | 0.173012E+10 | 30085159.67 | 0.170004E+10 | 0.00 | 0.00 |
July | 0.629153E+10 | 6467088.74 | 0.185695E+10 | 18184294.20 | 0.183876E+10 | 0.00 | 0.00 |
August | 0.582569E+10 | 19852602.56 | 0.195795E+10 | 85808252.08 | 0.187214E+10 | 0.00 | 0.00 |
September | 0.633626E+10 | 0.124481E+09 | 0.262190E+10 | 0.721903E+09 | 0.190000E+10 | 0.00 | 0.00 |
October | 0.930189E+10 | 0.136797E+10 | 0.458684E+10 | 0.257261E+10 | 0.201423E+10 | 0.00 | 0.00 |
November | 0.974670E+10 | 0.277756E+10 | 0.553837E+10 | 0.366910E+10 | 0.186926E+10 | 0.00 | 0.00 |
December | 0.786307E+10 | 0.408770E+10 | 0.509097E+10 | 0.319273E+10 | 0.189824E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.867417E+11 | 0.180088E+11 | 0.407179E+11 | 0.180833E+11 | 0.226346E+11 | 0.00 | 0.00 |
Minimum of Months | 0.582569E+10 | 6467088.74 | 0.173012E+10 | 18184294.20 | 0.170004E+10 | 0.00 | 0.00 |
Maximum of Months | 0.974670E+10 | 0.420757E+10 | 0.553837E+10 | 0.366910E+10 | 0.215941E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.659855E+09 | 0.567553E+09 | 0.479100E+09 | 0.243043E+09 | 0.236058E+09 | 0.00 | 0.00 |
February | 0.708800E+09 | 0.377445E+09 | 0.450048E+09 | 0.207372E+09 | 0.242676E+09 | 0.00 | 0.00 |
March | 0.102364E+10 | 0.205873E+09 | 0.536592E+09 | 0.222904E+09 | 0.313688E+09 | 0.00 | 0.00 |
April | 0.131851E+10 | 38681552.69 | 0.528797E+09 | 0.221832E+09 | 0.306965E+09 | 0.00 | 0.00 |
May | 0.151425E+10 | 359718.21 | 0.484360E+09 | 0.169149E+09 | 0.315211E+09 | 0.00 | 0.00 |
June | 0.146041E+10 | 1423173.51 | 0.437233E+09 | 0.135490E+09 | 0.301743E+09 | 0.00 | 0.00 |
July | 0.126551E+10 | 78350.83 | 0.363245E+09 | 51923089.29 | 0.311322E+09 | 0.00 | 0.00 |
August | 0.111490E+10 | 0.00 | 0.347141E+09 | 47161405.72 | 0.299980E+09 | 0.00 | 0.00 |
September | 0.106130E+10 | 2605746.04 | 0.399599E+09 | 0.115279E+09 | 0.284319E+09 | 0.00 | 0.00 |
October | 0.111801E+10 | 0.136815E+09 | 0.525045E+09 | 0.249698E+09 | 0.275347E+09 | 0.00 | 0.00 |
November | 0.960048E+09 | 0.348820E+09 | 0.541672E+09 | 0.301746E+09 | 0.239926E+09 | 0.00 | 0.00 |
December | 0.710138E+09 | 0.543231E+09 | 0.488829E+09 | 0.253815E+09 | 0.235014E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.129154E+11 | 0.222289E+10 | 0.558166E+10 | 0.221941E+10 | 0.336225E+10 | 0.00 | 0.00 |
Minimum of Months | 0.659855E+09 | 0.00 | 0.347141E+09 | 47161405.72 | 0.235014E+09 | 0.00 | 0.00 |
Maximum of Months | 0.151425E+10 | 0.567553E+09 | 0.541672E+09 | 0.301746E+09 | 0.315211E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.336802E+09 | 0.585170E+09 | 0.277783E+09 | 86087524.92 | 0.191696E+09 | 0.00 | 0.00 |
February | 0.426924E+09 | 0.392691E+09 | 0.289644E+09 | 84636723.15 | 0.205007E+09 | 0.00 | 0.00 |
March | 0.768415E+09 | 0.218675E+09 | 0.409528E+09 | 0.131754E+09 | 0.277774E+09 | 0.00 | 0.00 |
April | 0.118322E+10 | 40159138.19 | 0.470612E+09 | 0.181032E+09 | 0.289580E+09 | 0.00 | 0.00 |
May | 0.148977E+10 | 379964.82 | 0.474822E+09 | 0.163008E+09 | 0.311814E+09 | 0.00 | 0.00 |
June | 0.146743E+10 | 1502989.54 | 0.440980E+09 | 0.137426E+09 | 0.303554E+09 | 0.00 | 0.00 |
July | 0.126418E+10 | 78325.94 | 0.362304E+09 | 52744360.58 | 0.309560E+09 | 0.00 | 0.00 |
August | 0.108464E+10 | 0.00 | 0.332560E+09 | 42937093.93 | 0.289623E+09 | 0.00 | 0.00 |
September | 0.934634E+09 | 2525012.38 | 0.336389E+09 | 76269813.02 | 0.260119E+09 | 0.00 | 0.00 |
October | 0.771791E+09 | 0.143218E+09 | 0.347393E+09 | 0.110649E+09 | 0.236744E+09 | 0.00 | 0.00 |
November | 0.522648E+09 | 0.363975E+09 | 0.299920E+09 | 0.103431E+09 | 0.196489E+09 | 0.00 | 0.00 |
December | 0.344742E+09 | 0.555705E+09 | 0.268818E+09 | 81248581.68 | 0.187569E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105952E+11 | 0.230408E+10 | 0.431075E+10 | 0.125122E+10 | 0.305953E+10 | 0.00 | 0.00 |
Minimum of Months | 0.336802E+09 | 0.00 | 0.268818E+09 | 42937093.93 | 0.187569E+09 | 0.00 | 0.00 |
Maximum of Months | 0.148977E+10 | 0.585170E+09 | 0.474822E+09 | 0.181032E+09 | 0.311814E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.272493E+09 | 0.229539E+09 | 0.206244E+09 | 0.125539E+09 | 80705073.08 | 0.00 | 0.00 |
February | 0.257051E+09 | 0.166664E+09 | 0.176734E+09 | 98168448.57 | 78565624.13 | 0.00 | 0.00 |
March | 0.285632E+09 | 0.114841E+09 | 0.166263E+09 | 72908172.84 | 93354691.77 | 0.00 | 0.00 |
April | 0.263775E+09 | 42883768.68 | 0.114713E+09 | 33081469.46 | 81631059.55 | 0.00 | 0.00 |
May | 0.251708E+09 | 10072480.83 | 85452721.28 | 7198089.78 | 78254631.50 | 0.00 | 0.00 |
June | 0.235098E+09 | 7024261.70 | 74796216.26 | 1300617.77 | 73495598.49 | 0.00 | 0.00 |
July | 0.221838E+09 | 3035916.48 | 80278798.24 | 786128.99 | 79492669.25 | 0.00 | 0.00 |
August | 0.205252E+09 | 8353649.86 | 84645005.97 | 3709594.33 | 80935411.64 | 0.00 | 0.00 |
September | 0.237112E+09 | 24531862.76 | 0.113349E+09 | 31208725.64 | 82139971.61 | 0.00 | 0.00 |
October | 0.373209E+09 | 89915863.17 | 0.198295E+09 | 0.111217E+09 | 87078526.71 | 0.00 | 0.00 |
November | 0.393704E+09 | 0.157313E+09 | 0.239431E+09 | 0.158620E+09 | 80811117.20 | 0.00 | 0.00 |
December | 0.307713E+09 | 0.221946E+09 | 0.220089E+09 | 0.138026E+09 | 82063718.04 | 0.00 | 0.00 |
Annual Sum or Average | 0.330459E+10 | 0.107612E+10 | 0.176029E+10 | 0.781763E+09 | 0.978528E+09 | 0.00 | 0.00 |
Minimum of Months | 0.205252E+09 | 3035916.48 | 74796216.26 | 786128.99 | 73495598.49 | 0.00 | 0.00 |
Maximum of Months | 0.393704E+09 | 0.229539E+09 | 0.239431E+09 | 0.158620E+09 | 93354691.77 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 35370917.61 | 0.170089E+09 | 45237487.93 | 0.00 | 45237487.93 | 0.00 | 0.00 |
February | 60962708.80 | 0.110436E+09 | 48452642.97 | 0.00 | 48452642.97 | 0.00 | 0.00 |
March | 0.128147E+09 | 57019284.60 | 64653304.81 | 2209.21 | 64651095.60 | 0.00 | 0.00 |
April | 0.226075E+09 | 8617792.48 | 68196151.31 | 448258.41 | 67747892.89 | 0.00 | 0.00 |
May | 0.333171E+09 | 7042.27 | 77849569.15 | 2286681.56 | 75562887.59 | 0.00 | 0.00 |
June | 0.342394E+09 | 137519.58 | 77819636.33 | 2850266.94 | 74969369.39 | 0.00 | 0.00 |
July | 0.329290E+09 | 6108.55 | 79552630.39 | 1443493.68 | 78109136.70 | 0.00 | 0.00 |
August | 0.280675E+09 | 0.00 | 73006415.70 | 330926.50 | 72675489.20 | 0.00 | 0.00 |
September | 0.216012E+09 | 291057.35 | 62811891.90 | 7337.10 | 62804554.80 | 0.00 | 0.00 |
October | 0.144060E+09 | 35164155.97 | 56220763.58 | 0.00 | 56220763.58 | 0.00 | 0.00 |
November | 76234422.69 | 98512524.63 | 46083428.65 | 0.00 | 46083428.65 | 0.00 | 0.00 |
December | 40276799.67 | 0.160433E+09 | 44129978.24 | 0.00 | 44129978.24 | 0.00 | 0.00 |
Annual Sum or Average | 0.221267E+10 | 0.640714E+09 | 0.744014E+09 | 7369173.40 | 0.736645E+09 | 0.00 | 0.00 |
Minimum of Months | 35370917.61 | 0.00 | 44129978.24 | 0.00 | 44129978.24 | 0.00 | 0.00 |
Maximum of Months | 0.342394E+09 | 0.170089E+09 | 79552630.39 | 2850266.94 | 78109136.70 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.641652E+09 | 0.544578E+09 | 0.483711E+09 | 0.247473E+09 | 0.236238E+09 | 0.00 | 0.00 |
February | 0.723223E+09 | 0.360212E+09 | 0.469478E+09 | 0.225342E+09 | 0.244136E+09 | 0.00 | 0.00 |
March | 0.102683E+10 | 0.193785E+09 | 0.543654E+09 | 0.229975E+09 | 0.313679E+09 | 0.00 | 0.00 |
April | 0.132341E+10 | 36455209.55 | 0.530200E+09 | 0.221695E+09 | 0.308505E+09 | 0.00 | 0.00 |
May | 0.154207E+10 | 268962.45 | 0.499549E+09 | 0.183276E+09 | 0.316273E+09 | 0.00 | 0.00 |
June | 0.139731E+10 | 1360298.78 | 0.402140E+09 | 0.103756E+09 | 0.298384E+09 | 0.00 | 0.00 |
July | 0.127251E+10 | 82967.83 | 0.368036E+09 | 56936089.25 | 0.311100E+09 | 0.00 | 0.00 |
August | 0.111436E+10 | 0.00 | 0.347750E+09 | 46730844.80 | 0.301020E+09 | 0.00 | 0.00 |
September | 0.104678E+10 | 2406358.93 | 0.391406E+09 | 0.108384E+09 | 0.283022E+09 | 0.00 | 0.00 |
October | 0.112290E+10 | 0.131919E+09 | 0.530194E+09 | 0.252779E+09 | 0.277415E+09 | 0.00 | 0.00 |
November | 0.942952E+09 | 0.334839E+09 | 0.541270E+09 | 0.301746E+09 | 0.239525E+09 | 0.00 | 0.00 |
December | 0.702107E+09 | 0.529812E+09 | 0.493978E+09 | 0.259447E+09 | 0.234532E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.128561E+11 | 0.213572E+10 | 0.560137E+10 | 0.223754E+10 | 0.336383E+10 | 0.00 | 0.00 |
Minimum of Months | 0.641652E+09 | 0.00 | 0.347750E+09 | 46730844.80 | 0.234532E+09 | 0.00 | 0.00 |
Maximum of Months | 0.154207E+10 | 0.544578E+09 | 0.543654E+09 | 0.301746E+09 | 0.316273E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.298943E+09 | 0.538528E+09 | 0.282394E+09 | 90517979.35 | 0.191876E+09 | 0.00 | 0.00 |
February | 0.429985E+09 | 0.364326E+09 | 0.309074E+09 | 0.102607E+09 | 0.206467E+09 | 0.00 | 0.00 |
March | 0.764110E+09 | 0.203221E+09 | 0.416590E+09 | 0.138824E+09 | 0.277766E+09 | 0.00 | 0.00 |
April | 0.118546E+10 | 37680280.97 | 0.472015E+09 | 0.180895E+09 | 0.291120E+09 | 0.00 | 0.00 |
May | 0.151742E+10 | 284611.11 | 0.490011E+09 | 0.177134E+09 | 0.312876E+09 | 0.00 | 0.00 |
June | 0.140431E+10 | 1410326.98 | 0.405888E+09 | 0.105693E+09 | 0.300195E+09 | 0.00 | 0.00 |
July | 0.127117E+10 | 82942.98 | 0.367095E+09 | 57757360.55 | 0.309338E+09 | 0.00 | 0.00 |
August | 0.108408E+10 | 0.00 | 0.333169E+09 | 42506533.02 | 0.290662E+09 | 0.00 | 0.00 |
September | 0.919974E+09 | 2258149.43 | 0.328196E+09 | 69374653.08 | 0.258821E+09 | 0.00 | 0.00 |
October | 0.771483E+09 | 0.135761E+09 | 0.352542E+09 | 0.113730E+09 | 0.238811E+09 | 0.00 | 0.00 |
November | 0.494517E+09 | 0.341271E+09 | 0.299519E+09 | 0.103432E+09 | 0.196087E+09 | 0.00 | 0.00 |
December | 0.323840E+09 | 0.527280E+09 | 0.273967E+09 | 86880466.94 | 0.187087E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104653E+11 | 0.215210E+10 | 0.433046E+10 | 0.126935E+10 | 0.306111E+10 | 0.00 | 0.00 |
Minimum of Months | 0.298943E+09 | 0.00 | 0.273967E+09 | 42506533.02 | 0.187087E+09 | 0.00 | 0.00 |
Maximum of Months | 0.151742E+10 | 0.538528E+09 | 0.490011E+09 | 0.180895E+09 | 0.312876E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.745236E+09 | 0.702702E+09 | 0.544873E+09 | 0.272008E+09 | 0.272865E+09 | 0.00 | 0.00 |
February | 0.765112E+09 | 0.484281E+09 | 0.487898E+09 | 0.212704E+09 | 0.275195E+09 | 0.00 | 0.00 |
March | 0.972369E+09 | 0.296670E+09 | 0.500306E+09 | 0.157977E+09 | 0.342330E+09 | 0.00 | 0.00 |
April | 0.110888E+10 | 78051915.70 | 0.396286E+09 | 72649422.71 | 0.323636E+09 | 0.00 | 0.00 |
May | 0.131323E+10 | 5083089.55 | 0.353801E+09 | 20549977.88 | 0.333251E+09 | 0.00 | 0.00 |
June | 0.130430E+10 | 5355746.65 | 0.330646E+09 | 8992710.96 | 0.321653E+09 | 0.00 | 0.00 |
July | 0.125580E+10 | 727153.77 | 0.346280E+09 | 4830414.26 | 0.341449E+09 | 0.00 | 0.00 |
August | 0.110675E+10 | 614073.59 | 0.341559E+09 | 8754557.06 | 0.332804E+09 | 0.00 | 0.00 |
September | 0.102319E+10 | 12431525.99 | 0.381667E+09 | 67636524.21 | 0.314030E+09 | 0.00 | 0.00 |
October | 0.117159E+10 | 0.225084E+09 | 0.551444E+09 | 0.240976E+09 | 0.310468E+09 | 0.00 | 0.00 |
November | 0.108061E+10 | 0.474049E+09 | 0.618612E+09 | 0.343685E+09 | 0.274927E+09 | 0.00 | 0.00 |
December | 0.829420E+09 | 0.688287E+09 | 0.572473E+09 | 0.299063E+09 | 0.273410E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.126765E+11 | 0.297334E+10 | 0.542584E+10 | 0.170983E+10 | 0.371602E+10 | 0.00 | 0.00 |
Minimum of Months | 0.745236E+09 | 614073.59 | 0.330646E+09 | 4830414.26 | 0.272865E+09 | 0.00 | 0.00 |
Maximum of Months | 0.131323E+10 | 0.702702E+09 | 0.618612E+09 | 0.343685E+09 | 0.342330E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.655380E+09 | 0.557620E+09 | 0.479100E+09 | 0.243043E+09 | 0.236058E+09 | 0.00 | 0.00 |
February | 0.702284E+09 | 0.370800E+09 | 0.450048E+09 | 0.207372E+09 | 0.242676E+09 | 0.00 | 0.00 |
March | 0.101458E+10 | 0.200474E+09 | 0.536592E+09 | 0.222904E+09 | 0.313688E+09 | 0.00 | 0.00 |
April | 0.131018E+10 | 36394807.68 | 0.528797E+09 | 0.221832E+09 | 0.306965E+09 | 0.00 | 0.00 |
May | 0.150987E+10 | 227013.89 | 0.484360E+09 | 0.169149E+09 | 0.315211E+09 | 0.00 | 0.00 |
June | 0.145297E+10 | 1444641.26 | 0.437233E+09 | 0.135490E+09 | 0.301743E+09 | 0.00 | 0.00 |
July | 0.126161E+10 | 50022.50 | 0.363245E+09 | 51923089.29 | 0.311322E+09 | 0.00 | 0.00 |
August | 0.111034E+10 | 0.00 | 0.347141E+09 | 47161405.72 | 0.299980E+09 | 0.00 | 0.00 |
September | 0.105584E+10 | 2215401.22 | 0.399599E+09 | 0.115279E+09 | 0.284319E+09 | 0.00 | 0.00 |
October | 0.111149E+10 | 0.132124E+09 | 0.525045E+09 | 0.249698E+09 | 0.275347E+09 | 0.00 | 0.00 |
November | 0.955108E+09 | 0.341426E+09 | 0.541672E+09 | 0.301746E+09 | 0.239926E+09 | 0.00 | 0.00 |
December | 0.707523E+09 | 0.533267E+09 | 0.488829E+09 | 0.253815E+09 | 0.235014E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.128472E+11 | 0.217604E+10 | 0.558166E+10 | 0.221941E+10 | 0.336225E+10 | 0.00 | 0.00 |
Minimum of Months | 0.655380E+09 | 0.00 | 0.347141E+09 | 47161405.72 | 0.235014E+09 | 0.00 | 0.00 |
Maximum of Months | 0.150987E+10 | 0.557620E+09 | 0.541672E+09 | 0.301746E+09 | 0.315211E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.335344E+09 | 0.572512E+09 | 0.277783E+09 | 86087524.92 | 0.191696E+09 | 0.00 | 0.00 |
February | 0.422976E+09 | 0.385093E+09 | 0.289644E+09 | 84636723.15 | 0.205007E+09 | 0.00 | 0.00 |
March | 0.762207E+09 | 0.212930E+09 | 0.409528E+09 | 0.131754E+09 | 0.277774E+09 | 0.00 | 0.00 |
April | 0.117706E+10 | 37440347.94 | 0.470612E+09 | 0.181032E+09 | 0.289580E+09 | 0.00 | 0.00 |
May | 0.148573E+10 | 241608.92 | 0.474822E+09 | 0.163008E+09 | 0.311814E+09 | 0.00 | 0.00 |
June | 0.145989E+10 | 1505127.84 | 0.440980E+09 | 0.137426E+09 | 0.303554E+09 | 0.00 | 0.00 |
July | 0.126005E+10 | 50029.09 | 0.362304E+09 | 52744360.58 | 0.309560E+09 | 0.00 | 0.00 |
August | 0.108046E+10 | 0.00 | 0.332560E+09 | 42937093.93 | 0.289623E+09 | 0.00 | 0.00 |
September | 0.930746E+09 | 2088644.29 | 0.336389E+09 | 76269813.02 | 0.260119E+09 | 0.00 | 0.00 |
October | 0.768484E+09 | 0.136811E+09 | 0.347393E+09 | 0.110649E+09 | 0.236744E+09 | 0.00 | 0.00 |
November | 0.521364E+09 | 0.353645E+09 | 0.299920E+09 | 0.103431E+09 | 0.196489E+09 | 0.00 | 0.00 |
December | 0.345463E+09 | 0.541976E+09 | 0.268818E+09 | 81248581.68 | 0.187569E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105498E+11 | 0.224429E+10 | 0.431075E+10 | 0.125122E+10 | 0.305953E+10 | 0.00 | 0.00 |
Minimum of Months | 0.335344E+09 | 0.00 | 0.268818E+09 | 42937093.93 | 0.187569E+09 | 0.00 | 0.00 |
Maximum of Months | 0.148573E+10 | 0.572512E+09 | 0.474822E+09 | 0.181032E+09 | 0.311814E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.556932E+09 | 0.287768E+09 | 0.378171E+09 | 0.230190E+09 | 0.147982E+09 | 0.00 | 0.00 |
February | 0.526265E+09 | 0.190127E+09 | 0.324061E+09 | 0.180003E+09 | 0.144059E+09 | 0.00 | 0.00 |
March | 0.595955E+09 | 0.100491E+09 | 0.304861E+09 | 0.133685E+09 | 0.171176E+09 | 0.00 | 0.00 |
April | 0.594141E+09 | 16739474.71 | 0.210338E+09 | 60658498.20 | 0.149679E+09 | 0.00 | 0.00 |
May | 0.628625E+09 | 24761.58 | 0.156687E+09 | 13198486.14 | 0.143488E+09 | 0.00 | 0.00 |
June | 0.598034E+09 | 506166.09 | 0.137147E+09 | 2384825.16 | 0.134762E+09 | 0.00 | 0.00 |
July | 0.587593E+09 | 17354.59 | 0.147200E+09 | 1441453.62 | 0.145759E+09 | 0.00 | 0.00 |
August | 0.541359E+09 | 0.00 | 0.155206E+09 | 6801947.57 | 0.148404E+09 | 0.00 | 0.00 |
September | 0.566026E+09 | 894836.98 | 0.207837E+09 | 57224617.25 | 0.150613E+09 | 0.00 | 0.00 |
October | 0.757485E+09 | 66299929.61 | 0.363596E+09 | 0.203928E+09 | 0.159668E+09 | 0.00 | 0.00 |
November | 0.780268E+09 | 0.175161E+09 | 0.439023E+09 | 0.290847E+09 | 0.148176E+09 | 0.00 | 0.00 |
December | 0.625202E+09 | 0.277546E+09 | 0.403558E+09 | 0.253085E+09 | 0.150473E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.735788E+10 | 0.111558E+10 | 0.322769E+10 | 0.143345E+10 | 0.179424E+10 | 0.00 | 0.00 |
Minimum of Months | 0.526265E+09 | 0.00 | 0.137147E+09 | 1441453.62 | 0.134762E+09 | 0.00 | 0.00 |
Maximum of Months | 0.780268E+09 | 0.287768E+09 | 0.439023E+09 | 0.290847E+09 | 0.171176E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.210605E+09 | 0.181539E+10 | 0.395761E+09 | 0.00 | 0.395761E+09 | 0.00 | 0.00 |
February | 0.417411E+09 | 0.121696E+10 | 0.423888E+09 | 0.00 | 0.423888E+09 | 0.00 | 0.00 |
March | 0.941818E+09 | 0.723561E+09 | 0.565620E+09 | 19327.28 | 0.565601E+09 | 0.00 | 0.00 |
April | 0.165669E+10 | 0.195535E+09 | 0.596615E+09 | 3921592.75 | 0.592693E+09 | 0.00 | 0.00 |
May | 0.244151E+10 | 18201137.84 | 0.681068E+09 | 20005054.12 | 0.661063E+09 | 0.00 | 0.00 |
June | 0.252814E+10 | 19319095.80 | 0.680806E+09 | 24935585.78 | 0.655870E+09 | 0.00 | 0.00 |
July | 0.238848E+10 | 2393014.86 | 0.695967E+09 | 12628417.41 | 0.683338E+09 | 0.00 | 0.00 |
August | 0.198154E+10 | 7504342.05 | 0.638697E+09 | 2895113.42 | 0.635802E+09 | 0.00 | 0.00 |
September | 0.146185E+10 | 47029102.10 | 0.549510E+09 | 64188.66 | 0.549446E+09 | 0.00 | 0.00 |
October | 0.106693E+10 | 0.516326E+09 | 0.491848E+09 | 0.00 | 0.491848E+09 | 0.00 | 0.00 |
November | 0.543167E+09 | 0.109337E+10 | 0.403161E+09 | 0.00 | 0.403161E+09 | 0.00 | 0.00 |
December | 0.249638E+09 | 0.171372E+10 | 0.386072E+09 | 0.00 | 0.386072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.158878E+11 | 0.736930E+10 | 0.650901E+10 | 64469279.42 | 0.644454E+10 | 0.00 | 0.00 |
Minimum of Months | 0.210605E+09 | 2393014.86 | 0.386072E+09 | 0.00 | 0.386072E+09 | 0.00 | 0.00 |
Maximum of Months | 0.252814E+10 | 0.181539E+10 | 0.695967E+09 | 24935585.78 | 0.683338E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.184030E+09 | 0.188403E+10 | 0.395761E+09 | 0.00 | 0.395761E+09 | 0.00 | 0.00 |
February | 0.389219E+09 | 0.126334E+10 | 0.423888E+09 | 0.00 | 0.423888E+09 | 0.00 | 0.00 |
March | 0.912186E+09 | 0.752799E+09 | 0.565620E+09 | 19327.28 | 0.565601E+09 | 0.00 | 0.00 |
April | 0.162845E+10 | 0.206760E+09 | 0.596615E+09 | 3921592.75 | 0.592693E+09 | 0.00 | 0.00 |
May | 0.240797E+10 | 20533760.09 | 0.681068E+09 | 20005054.12 | 0.661063E+09 | 0.00 | 0.00 |
June | 0.249576E+10 | 21169498.30 | 0.680806E+09 | 24935585.78 | 0.655870E+09 | 0.00 | 0.00 |
July | 0.235253E+10 | 2673847.63 | 0.695967E+09 | 12628417.41 | 0.683338E+09 | 0.00 | 0.00 |
August | 0.194687E+10 | 9503968.17 | 0.638697E+09 | 2895113.42 | 0.635802E+09 | 0.00 | 0.00 |
September | 0.142949E+10 | 55801565.65 | 0.549510E+09 | 64188.66 | 0.549446E+09 | 0.00 | 0.00 |
October | 0.104319E+10 | 0.538186E+09 | 0.491848E+09 | 0.00 | 0.491848E+09 | 0.00 | 0.00 |
November | 0.517573E+09 | 0.113036E+10 | 0.403161E+09 | 0.00 | 0.403161E+09 | 0.00 | 0.00 |
December | 0.222912E+09 | 0.177645E+10 | 0.386072E+09 | 0.00 | 0.386072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.155302E+11 | 0.766161E+10 | 0.650901E+10 | 64469279.42 | 0.644454E+10 | 0.00 | 0.00 |
Minimum of Months | 0.184030E+09 | 2673847.63 | 0.386072E+09 | 0.00 | 0.386072E+09 | 0.00 | 0.00 |
Maximum of Months | 0.249576E+10 | 0.188403E+10 | 0.695967E+09 | 24935585.78 | 0.683338E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.948224E+09 | 0.127689E+10 | 0.766073E+09 | 0.337978E+09 | 0.428094E+09 | 0.00 | 0.00 |
February | 0.119730E+10 | 0.888061E+09 | 0.778517E+09 | 0.327934E+09 | 0.450583E+09 | 0.00 | 0.00 |
March | 0.191046E+10 | 0.558159E+09 | 0.960196E+09 | 0.368779E+09 | 0.591416E+09 | 0.00 | 0.00 |
April | 0.261554E+10 | 0.179189E+09 | 0.100216E+10 | 0.402564E+09 | 0.599596E+09 | 0.00 | 0.00 |
May | 0.306551E+10 | 30313959.74 | 0.989503E+09 | 0.360386E+09 | 0.629118E+09 | 0.00 | 0.00 |
June | 0.279644E+10 | 29035809.08 | 0.807984E+09 | 0.209435E+09 | 0.598550E+09 | 0.00 | 0.00 |
July | 0.250475E+10 | 5916129.58 | 0.735094E+09 | 0.114686E+09 | 0.620408E+09 | 0.00 | 0.00 |
August | 0.220136E+10 | 17259486.61 | 0.680885E+09 | 89231399.56 | 0.591654E+09 | 0.00 | 0.00 |
September | 0.198042E+10 | 71682472.27 | 0.719566E+09 | 0.177749E+09 | 0.541817E+09 | 0.00 | 0.00 |
October | 0.206559E+10 | 0.396592E+09 | 0.882696E+09 | 0.366493E+09 | 0.516202E+09 | 0.00 | 0.00 |
November | 0.155587E+10 | 0.786672E+09 | 0.840755E+09 | 0.405163E+09 | 0.435592E+09 | 0.00 | 0.00 |
December | 0.106372E+10 | 0.122960E+10 | 0.767915E+09 | 0.346315E+09 | 0.421600E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239052E+11 | 0.546938E+10 | 0.993134E+10 | 0.350671E+10 | 0.642463E+10 | 0.00 | 0.00 |
Minimum of Months | 0.948224E+09 | 5916129.58 | 0.680885E+09 | 89231399.56 | 0.421600E+09 | 0.00 | 0.00 |
Maximum of Months | 0.306551E+10 | 0.127689E+10 | 0.100216E+10 | 0.405163E+09 | 0.629118E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.152709E+10 | 0.122518E+10 | 0.109832E+10 | 0.585960E+09 | 0.512363E+09 | 0.00 | 0.00 |
February | 0.152413E+10 | 0.838206E+09 | 0.970225E+09 | 0.458206E+09 | 0.512019E+09 | 0.00 | 0.00 |
March | 0.184391E+10 | 0.523747E+09 | 0.969936E+09 | 0.340309E+09 | 0.629627E+09 | 0.00 | 0.00 |
April | 0.197993E+10 | 0.146620E+09 | 0.739947E+09 | 0.155754E+09 | 0.584193E+09 | 0.00 | 0.00 |
May | 0.225265E+10 | 11691925.30 | 0.632326E+09 | 40455219.56 | 0.591871E+09 | 0.00 | 0.00 |
June | 0.220544E+10 | 11606225.87 | 0.582497E+09 | 14618666.73 | 0.567878E+09 | 0.00 | 0.00 |
July | 0.212371E+10 | 1373516.91 | 0.613284E+09 | 7998342.97 | 0.605286E+09 | 0.00 | 0.00 |
August | 0.187895E+10 | 3229636.96 | 0.614032E+09 | 18307169.56 | 0.595724E+09 | 0.00 | 0.00 |
September | 0.181660E+10 | 26267347.94 | 0.717434E+09 | 0.145690E+09 | 0.571744E+09 | 0.00 | 0.00 |
October | 0.226312E+10 | 0.396875E+09 | 0.109416E+10 | 0.519110E+09 | 0.575050E+09 | 0.00 | 0.00 |
November | 0.219744E+10 | 0.801255E+09 | 0.125576E+10 | 0.740366E+09 | 0.515394E+09 | 0.00 | 0.00 |
December | 0.171915E+10 | 0.117514E+10 | 0.115962E+10 | 0.644242E+09 | 0.515383E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.233321E+11 | 0.516119E+10 | 0.104475E+11 | 0.367102E+10 | 0.677653E+10 | 0.00 | 0.00 |
Minimum of Months | 0.152413E+10 | 1373516.91 | 0.582497E+09 | 7998342.97 | 0.512019E+09 | 0.00 | 0.00 |
Maximum of Months | 0.226312E+10 | 0.122518E+10 | 0.125576E+10 | 0.740366E+09 | 0.629627E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770492E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162128399.5 | 81.21 | 0.00 | 0.00 |
February | 0.696227E+10 | -0.681598E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146289906.8 | 81.21 | 0.00 | 0.00 |
March | 0.770318E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161722080.0 | 81.21 | 0.00 | 0.00 |
April | 0.746490E+10 | -0.730858E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156311118.5 | 81.21 | 0.00 | 0.00 |
May | 0.770424E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161446415.4 | 81.21 | 0.00 | 0.00 |
June | 0.745677E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156245909.8 | 81.21 | 0.00 | 0.00 |
July | 0.771229E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161449029.7 | 81.21 | 0.00 | 0.00 |
August | 0.770427E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161464724.0 | 81.21 | 0.00 | 0.00 |
September | 0.746623E+10 | -0.730993E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156299191.8 | 81.21 | 0.00 | 0.00 |
October | 0.770305E+10 | -0.754143E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161618891.9 | 81.21 | 0.00 | 0.00 |
November | 0.744906E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156636452.5 | 81.21 | 0.00 | 0.00 |
December | 0.771296E+10 | -0.755087E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162086431.5 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907441E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190370E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696227E+10 | -0.755087E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162128399.5 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771296E+10 | -0.681598E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146289906.8 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYSLAUNDRY HPWH TANK
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.330285E+11 | -0.100793E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -786353874.2 | 81.67 | 0.00 | 0.00 |
February | 0.251027E+11 | -0.897822E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -684449929.7 | 81.68 | 0.00 | 0.00 |
March | 0.188148E+11 | -0.952248E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -716731350.1 | 81.68 | 0.00 | 0.00 |
April | 0.799040E+10 | -0.863045E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -643096139.0 | 81.67 | 0.00 | 0.00 |
May | -73531269.6 | -0.843444E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -637740405.9 | 81.92 | 0.00 | 0.00 |
June | -292.6 | -0.785696E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -615651786.1 | 82.19 | 0.00 | 0.00 |
July | -8223.8 | -0.792427E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -651071935.7 | 82.19 | 0.00 | 0.00 |
August | -4194.7 | -0.806431E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -663492084.8 | 82.19 | 0.00 | 0.00 |
September | -70918884.4 | -0.817323E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -650669970.1 | 82.10 | 0.00 | 0.00 |
October | 0.851667E+10 | -0.880849E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -695781653.2 | 81.68 | 0.00 | 0.00 |
November | 0.196466E+11 | -0.912433E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -714113767.7 | 81.68 | 0.00 | 0.00 |
December | 0.302147E+11 | -0.989367E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -777658808.5 | 81.67 | 0.00 | 0.00 |
Annual Sum or Average | 0.143170E+12 | -0.105490E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.823681E+10 | 81.86 | 0.00 | 0.00 |
Minimum of Months | -73531269.6 | -0.100793E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -786353874.2 | 81.67 | 0.00 | 0.00 |
Maximum of Months | 0.330285E+11 | -0.785696E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -615651786.1 | 82.19 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 HPWH TANK
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | -0.216627E+10 | -0.570501E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.122131E+10 | 59.41 | 0.00 | 0.00 |
February | -0.201513E+10 | -0.504587E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.104120E+10 | 59.41 | 0.00 | 0.00 |
March | -0.207558E+10 | -0.522930E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.105466E+10 | 59.43 | 0.00 | 0.00 |
April | -0.170070E+10 | -0.455178E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -901034867.2 | 59.48 | 0.00 | 0.00 |
May | -0.139451E+10 | -0.416585E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -861217228.7 | 59.53 | 0.00 | 0.00 |
June | -980205757.5 | -0.363659E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -822902912.5 | 59.56 | 0.00 | 0.00 |
July | -881404414.6 | -0.358619E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -886848014.2 | 59.58 | 0.00 | 0.00 |
August | -980329337.1 | -0.371080E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -916204588.5 | 59.56 | 0.00 | 0.00 |
September | -0.131264E+10 | -0.395100E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -909054630.3 | 59.54 | 0.00 | 0.00 |
October | -0.168733E+10 | -0.460686E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.100631E+10 | 59.49 | 0.00 | 0.00 |
November | -0.192642E+10 | -0.497718E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.107015E+10 | 59.44 | 0.00 | 0.00 |
December | -0.212393E+10 | -0.554465E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.120088E+10 | 59.42 | 0.00 | 0.00 |
Annual Sum or Average | -0.192445E+11 | -0.547111E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.118918E+11 | 59.49 | 0.00 | 0.00 |
Minimum of Months | -0.216627E+10 | -0.570501E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.122131E+10 | 59.41 | 0.00 | 0.00 |
Maximum of Months | -881404414.6 | -0.358619E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -822902912.5 | 59.58 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.87 | 0.86 | 01-JAN-07:00 | 4659.63 | 35.31 | 301.00 | 287.50 | 631.88 | 25.25 | 272.17 | 265.00 |
February | 303.83 | 0.87 | 0.86 | 01-FEB-07:00 | 2315.06 | 27.07 | 158.83 | 273.33 | 513.98 | 21.98 | 204.00 | 232.00 |
March | 364.50 | 0.87 | 0.86 | 01-MAR-07:00 | 1075.29 | 19.49 | 7.00 | 325.83 | 421.51 | 21.03 | 222.83 | 271.00 |
April | 379.83 | 0.88 | 0.86 | 01-APR-07:40 | 727.28 | 18.49 | 0.00 | 330.00 | 304.55 | 20.23 | 129.83 | 259.00 |
May | 406.00 | 0.88 | 0.86 | 01-MAY-07:30 | 615.39 | 17.88 | 0.00 | 348.00 | 257.99 | 19.65 | 66.33 | 227.17 |
June | 386.67 | 0.88 | 0.86 | 01-JUN-08:20 | 619.78 | 17.43 | 0.00 | 332.33 | 253.66 | 19.18 | 48.67 | 198.00 |
July | 379.83 | 0.88 | 0.86 | 01-JUL-07:40 | 728.49 | 17.42 | 0.00 | 331.33 | 271.38 | 19.13 | 31.83 | 236.17 |
August | 372.50 | 0.88 | 0.86 | 01-AUG-07:40 | 834.29 | 17.34 | 0.00 | 321.17 | 302.58 | 19.02 | 66.83 | 226.17 |
September | 344.33 | 0.88 | 0.86 | 01-SEP-07:49 | 1020.34 | 18.26 | 0.00 | 302.17 | 383.04 | 19.99 | 153.00 | 229.83 |
October | 347.33 | 0.87 | 0.86 | 01-OCT-07:30 | 1415.45 | 21.65 | 76.83 | 308.17 | 466.06 | 20.69 | 205.83 | 270.50 |
November | 317.83 | 0.87 | 0.86 | 01-NOV-07:30 | 5413.43 | 34.95 | 288.33 | 287.67 | 598.46 | 24.38 | 257.17 | 267.17 |
December | 315.50 | 0.87 | 0.86 | 01-DEC-07:30 | 4794.60 | 36.46 | 309.00 | 286.67 | 742.52 | 26.79 | 287.33 | 276.33 |
Annual Sum or Average | 4237.50 | 0.87 | 1890.92 | 22.92 | 1141.00 | 3734.17 | 416.31 | 21.26 | 1945.83 | 2958.33 | ||
Minimum of Months | 303.83 | 0.87 | 0.86 | 615.39 | 17.34 | 0.00 | 273.33 | 253.66 | 19.02 | 31.83 | 198.00 | |
Maximum of Months | 406.00 | 0.88 | 0.86 | 5413.43 | 36.46 | 309.00 | 348.00 | 742.52 | 26.79 | 287.33 | 276.33 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.26 | 0.22 | 01-JAN-07:49 | 4931.26 | 35.38 | 301.33 | 295.17 | 900.55 | 25.33 | 249.00 | 278.50 |
February | 303.83 | 0.26 | 0.22 | 01-FEB-07:49 | 2565.02 | 27.20 | 159.33 | 281.33 | 763.98 | 22.25 | 197.00 | 257.33 |
March | 364.50 | 0.27 | 0.22 | 01-MAR-07:40 | 1280.89 | 20.06 | 7.00 | 336.00 | 626.52 | 21.42 | 238.50 | 303.17 |
April | 379.83 | 0.28 | 0.22 | 01-APR-07:10 | 873.79 | 19.25 | 0.00 | 340.67 | 450.68 | 20.77 | 208.83 | 310.33 |
May | 406.00 | 0.28 | 0.22 | 01-MAY-06:00 | 727.71 | 18.82 | 0.00 | 362.50 | 369.95 | 20.36 | 183.50 | 324.50 |
June | 386.67 | 0.29 | 0.22 | 01-JUN-07:19 | 725.18 | 18.42 | 0.00 | 346.83 | 358.70 | 19.94 | 169.83 | 305.50 |
July | 379.83 | 0.28 | 0.22 | 01-JUL-06:00 | 833.83 | 18.49 | 0.00 | 348.67 | 376.26 | 19.96 | 123.00 | 298.33 |
August | 372.50 | 0.28 | 0.22 | 01-AUG-06:00 | 947.48 | 18.37 | 0.00 | 336.67 | 415.21 | 19.82 | 130.67 | 288.33 |
September | 344.33 | 0.27 | 0.22 | 01-SEP-07:19 | 1176.59 | 19.11 | 0.50 | 314.83 | 538.66 | 20.62 | 181.67 | 277.67 |
October | 347.33 | 0.28 | 0.22 | 01-OCT-07:10 | 1664.75 | 21.94 | 77.17 | 314.83 | 714.20 | 20.97 | 189.67 | 291.83 |
November | 317.83 | 0.26 | 0.22 | 01-NOV-07:19 | 5727.53 | 35.00 | 288.33 | 295.33 | 912.57 | 24.33 | 212.17 | 279.83 |
December | 315.50 | 0.25 | 0.22 | 01-DEC-07:19 | 5084.41 | 36.52 | 309.00 | 294.33 | 1030.73 | 26.77 | 264.00 | 284.67 |
Annual Sum or Average | 4237.50 | 0.27 | 2078.17 | 23.52 | 1142.67 | 3867.17 | 602.83 | 21.72 | 2347.83 | 3500.00 | ||
Minimum of Months | 303.83 | 0.25 | 0.22 | 725.18 | 18.37 | 0.00 | 281.33 | 358.70 | 19.82 | 123.00 | 257.33 | |
Maximum of Months | 406.00 | 0.29 | 0.22 | 5727.53 | 36.52 | 309.00 | 362.50 | 1030.73 | 26.77 | 264.00 | 324.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.67 | 0.60 | 01-JAN-09:00 | 318.28 | 14.06 | 0.00 | 257.00 | 155.93 | 17.44 | 0.00 | 39.67 |
February | 303.83 | 0.65 | 0.60 | 01-FEB-09:20 | 367.98 | 14.99 | 0.00 | 257.00 | 177.84 | 18.29 | 0.00 | 126.50 |
March | 364.50 | 0.64 | 0.60 | 01-MAR-08:39 | 434.04 | 16.00 | 0.00 | 322.50 | 208.23 | 19.24 | 0.00 | 243.83 |
April | 379.83 | 0.63 | 0.60 | 01-APR-07:30 | 464.16 | 16.31 | 0.00 | 339.83 | 224.83 | 19.52 | 0.00 | 280.83 |
May | 406.00 | 0.63 | 0.60 | 01-MAY-06:40 | 569.40 | 17.22 | 19.00 | 371.33 | 257.82 | 20.40 | 49.00 | 310.50 |
June | 386.67 | 0.63 | 0.60 | 01-JUN-07:30 | 651.52 | 17.45 | 25.50 | 353.17 | 280.06 | 20.91 | 86.83 | 291.33 |
July | 379.83 | 0.63 | 0.60 | 01-JUL-06:30 | 695.35 | 16.82 | 12.00 | 352.50 | 279.71 | 20.68 | 53.00 | 290.17 |
August | 372.50 | 0.64 | 0.60 | 01-AUG-06:00 | 624.90 | 15.80 | 0.00 | 335.17 | 250.24 | 18.87 | 0.00 | 263.00 |
September | 344.33 | 0.64 | 0.60 | 01-SEP-07:30 | 520.85 | 15.78 | 0.00 | 306.83 | 224.53 | 18.91 | 0.00 | 228.83 |
October | 347.33 | 0.65 | 0.60 | 01-OCT-07:00 | 376.84 | 14.91 | 0.00 | 296.83 | 186.48 | 18.19 | 0.00 | 179.33 |
November | 317.83 | 0.66 | 0.60 | 01-NOV-08:30 | 312.36 | 14.46 | 0.00 | 259.17 | 163.83 | 17.96 | 0.00 | 40.17 |
December | 315.50 | 0.67 | 0.60 | 01-DEC-09:00 | 312.56 | 14.18 | 0.00 | 251.83 | 155.57 | 17.61 | 0.00 | 17.83 |
Annual Sum or Average | 4237.50 | 0.64 | 480.49 | 15.76 | 56.50 | 3703.17 | 217.29 | 19.09 | 188.83 | 2312.00 | ||
Minimum of Months | 303.83 | 0.63 | 0.60 | 312.36 | 14.06 | 0.00 | 251.83 | 155.57 | 17.44 | 0.00 | 17.83 | |
Maximum of Months | 406.00 | 0.67 | 0.60 | 695.35 | 17.45 | 25.50 | 371.33 | 280.06 | 20.91 | 86.83 | 310.50 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.67 | 0.60 | 01-JAN-09:00 | 318.28 | 14.06 | 0.00 | 257.00 | 155.93 | 17.44 | 0.00 | 39.67 |
February | 303.83 | 0.65 | 0.60 | 01-FEB-09:20 | 367.98 | 14.99 | 0.00 | 257.00 | 177.84 | 18.29 | 0.00 | 126.50 |
March | 364.50 | 0.64 | 0.60 | 01-MAR-08:39 | 434.04 | 16.00 | 0.00 | 322.50 | 208.23 | 19.24 | 0.00 | 243.83 |
April | 379.83 | 0.63 | 0.60 | 01-APR-07:30 | 464.16 | 16.31 | 0.00 | 339.83 | 224.83 | 19.52 | 0.00 | 280.83 |
May | 406.00 | 0.63 | 0.60 | 01-MAY-06:40 | 569.40 | 17.22 | 19.00 | 371.33 | 257.82 | 20.40 | 49.00 | 310.50 |
June | 386.67 | 0.63 | 0.60 | 01-JUN-07:30 | 651.52 | 17.45 | 25.50 | 353.17 | 280.06 | 20.91 | 86.83 | 291.33 |
July | 379.83 | 0.63 | 0.60 | 01-JUL-06:30 | 695.35 | 16.82 | 12.00 | 352.50 | 279.71 | 20.68 | 53.00 | 290.17 |
August | 372.50 | 0.64 | 0.60 | 01-AUG-06:00 | 624.90 | 15.80 | 0.00 | 335.17 | 250.24 | 18.87 | 0.00 | 263.00 |
September | 344.33 | 0.64 | 0.60 | 01-SEP-07:30 | 520.85 | 15.78 | 0.00 | 306.83 | 224.53 | 18.91 | 0.00 | 228.83 |
October | 347.33 | 0.65 | 0.60 | 01-OCT-07:00 | 376.84 | 14.91 | 0.00 | 296.83 | 186.48 | 18.19 | 0.00 | 179.33 |
November | 317.83 | 0.66 | 0.60 | 01-NOV-08:30 | 312.36 | 14.46 | 0.00 | 259.17 | 163.83 | 17.96 | 0.00 | 40.17 |
December | 315.50 | 0.67 | 0.60 | 01-DEC-09:00 | 312.56 | 14.18 | 0.00 | 251.83 | 155.57 | 17.61 | 0.00 | 17.83 |
Annual Sum or Average | 4237.50 | 0.64 | 480.49 | 15.76 | 56.50 | 3703.17 | 217.29 | 19.09 | 188.83 | 2312.00 | ||
Minimum of Months | 303.83 | 0.63 | 0.60 | 312.36 | 14.06 | 0.00 | 251.83 | 155.57 | 17.44 | 0.00 | 17.83 | |
Maximum of Months | 406.00 | 0.67 | 0.60 | 695.35 | 17.45 | 25.50 | 371.33 | 280.06 | 20.91 | 86.83 | 310.50 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.245716E+09 | 14334.13 | 08-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 90967068.90 | 16797.39 | 03-FEB-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 27751.89 | 56.66 | 01-MAR-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1111.19 | 1.85 | 18-MAY-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 46301354.38 | 15989.53 | 26-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.257155E+09 | 23216.06 | 22-DEC-19:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.640169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.257155E+09 | 23216.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.369340E+09 | 1040.38 | 02-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106385E+09 | 918.08 | 11-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 321196.33 | 91.08 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149810E+09 | 912.97 | 23-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.625857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.369340E+09 | 1040.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 19208802.59 | 379.35 | 02-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19208802.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19208802.59 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 18633295.44 | 222.96 | 02-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18633295.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18633295.44 | 222.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 65333483.96 | 1121.60 | 02-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22901823.18 | 1033.35 | 11-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 28212.27 | 47.02 | 01-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2565209.46 | 361.88 | 25-NOV-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 41552682.99 | 922.28 | 23-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132381E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 65333483.96 | 1121.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 16530521.84 | 1299.09 | 16-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13144228.54 | 1190.80 | 10-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29674750.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16530521.84 | 1299.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.226019E+09 | 3037.48 | 02-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226019E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.226019E+09 | 3037.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.126534E+10 | 2812.30 | 02-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.248543E+09 | 2042.58 | 02-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1942055.49 | 407.74 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.628441E+09 | 2587.68 | 23-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.126534E+10 | 2812.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 3228.06 | 0.24 | 16-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5071.31 | 0.25 | 25-FEB-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8496.72 | 0.25 | 21-MAR-03:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6512.94 | 0.25 | 17-APR-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8469.26 | 0.25 | 17-MAY-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10731.15 | 0.25 | 25-JUN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10168.48 | 0.25 | 17-JUL-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9958.85 | 0.25 | 05-AUG-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12473.28 | 0.25 | 06-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10011.20 | 0.25 | 20-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8022.99 | 0.25 | 23-NOV-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2999.34 | 0.25 | 01-DEC-09:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96143.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2999.34 | 0.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12473.28 | 0.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.470538E+09 | 5982.40 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113905E+09 | 3543.13 | 14-FEB-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7286595.69 | 4443.27 | 14-MAR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3502388.46 | 4724.63 | 10-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1101979.37 | 1726.31 | 24-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1530961.34 | 1941.10 | 18-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1959977.42 | 2095.43 | 28-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3034199.22 | 2360.72 | 23-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5955031.26 | 4593.20 | 07-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6111901.13 | 4583.88 | 24-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9236382.25 | 3247.24 | 06-NOV-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207759E+09 | 4434.03 | 29-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.831921E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1101979.37 | 1726.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.470538E+09 | 5982.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.916346E+09 | 6057.93 | 03-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192622E+09 | 3925.41 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6298721.44 | 3971.12 | 26-MAR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1972356.38 | 3263.14 | 23-APR-08:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 906092.03 | 1709.67 | 24-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1527040.61 | 2413.16 | 18-JUN-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1954307.90 | 2198.51 | 28-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3422602.81 | 2519.54 | 23-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7009389.99 | 4605.67 | 07-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4526105.62 | 3369.80 | 15-OCT-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14946819.14 | 3650.72 | 12-NOV-09:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.514342E+09 | 6032.30 | 21-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 906092.03 | 1709.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.916346E+09 | 6057.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.855180E+09 | 35214.49 | 28-JAN-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127777E+09 | 32865.52 | 02-FEB-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 85820879.23 | 29124.54 | 25-MAR-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 41620896.94 | 16689.92 | 12-APR-08:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31104779.84 | 14906.49 | 29-MAY-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30707179.61 | 13865.13 | 27-JUN-18:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35118496.10 | 13316.60 | 18-JUL-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 35045531.44 | 12976.40 | 23-AUG-18:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 60155127.78 | 18118.76 | 09-SEP-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 79067169.44 | 25600.25 | 28-OCT-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100217E+09 | 30958.84 | 11-NOV-16:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.373374E+09 | 32950.06 | 15-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 30707179.61 | 12976.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.855180E+09 | 35214.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.479794E+09 | 4067.22 | 27-JAN-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110650E+09 | 2903.94 | 03-FEB-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2204707.51 | 2984.86 | 22-MAR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 549.06 | 5.49 | 24-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 50994.62 | 509.95 | 24-JUN-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 172301.14 | 1633.86 | 26-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 49673.82 | 496.74 | 20-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1088691.68 | 2228.96 | 07-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 526973.59 | 2657.08 | 12-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1733193.76 | 1708.59 | 02-NOV-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.228143E+09 | 4424.62 | 29-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.824413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.479794E+09 | 4424.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.877557E+09 | 5024.03 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.188711E+09 | 3659.30 | 12-FEB-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3668348.38 | 2479.21 | 03-MAR-22:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 71443.44 | 645.49 | 09-APR-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3124.60 | 31.25 | 24-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 182676.30 | 1284.80 | 18-JUN-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 180923.72 | 1677.39 | 26-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 56866.87 | 568.67 | 20-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1214541.20 | 2419.45 | 07-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1650267.73 | 1958.58 | 24-OCT-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15751410.50 | 3684.71 | 28-NOV-16:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.532789E+09 | 4145.73 | 25-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3124.60 | 31.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.877557E+09 | 5024.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.261653E+09 | 1881.37 | 03-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 79242598.22 | 1247.93 | 10-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2779363.12 | 1033.07 | 30-MAR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1257602.83 | 1017.00 | 05-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 310674.50 | 566.41 | 13-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 413666.67 | 669.77 | 25-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 658351.97 | 925.33 | 28-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1072435.80 | 960.05 | 23-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1749300.08 | 1040.04 | 07-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1892290.78 | 977.02 | 16-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8681959.94 | 1075.78 | 28-NOV-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163419E+09 | 1734.34 | 21-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.523130E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 310674.50 | 566.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.261653E+09 | 1881.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.433740E+09 | 1903.33 | 03-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117476E+09 | 1876.85 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2693099.59 | 1056.96 | 27-MAR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 787414.24 | 886.62 | 02-APR-06:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 253008.35 | 497.18 | 24-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 407213.14 | 688.76 | 25-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 639416.76 | 922.27 | 28-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1083659.68 | 967.03 | 16-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2020300.75 | 1033.97 | 07-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1711344.20 | 885.60 | 04-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19725419.20 | 923.89 | 01-NOV-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.307800E+09 | 1898.71 | 21-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.888337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 253008.35 | 497.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.433740E+09 | 1903.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.224977E+09 | 3724.68 | 04-JAN-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 81030707.93 | 4152.79 | 12-FEB-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4458047.61 | 2972.57 | 18-MAR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4425719.91 | 4217.11 | 03-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2218631.93 | 4316.50 | 15-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2711956.28 | 4121.57 | 28-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2714414.11 | 4216.27 | 26-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3097292.86 | 4277.85 | 17-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3059259.84 | 3939.64 | 19-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2119195.40 | 3929.53 | 05-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2441474.24 | 3111.19 | 01-NOV-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 80655194.47 | 4903.71 | 29-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.413908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2119195.40 | 2972.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.224977E+09 | 4903.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.453160E+11 | 0.437082E+11 | 51043.46 | 17-JAN-07:15 | 49217.62 | 0.00 |
February | 0.00 | 0.00 | 0.407558E+11 | 0.387422E+11 | 54932.34 | 01-FEB-21:30 | 52106.54 | 0.00 |
March | 0.00 | 0.00 | 0.427438E+11 | 0.419346E+11 | 59577.77 | 01-MAR-05:10 | 58143.07 | 0.00 |
April | 0.00 | 0.00 | 0.373598E+11 | 0.373584E+11 | 63622.14 | 01-APR-05:08 | 63622.14 | 0.00 |
May | 0.00 | 0.00 | 0.341945E+11 | 0.328169E+11 | 66769.86 | 01-MAY-07:15 | 63601.64 | 0.00 |
June | 0.00 | 0.00 | 0.296381E+11 | 0.229925E+11 | 67643.47 | 01-JUN-17:17 | 52243.36 | 0.00 |
July | 0.00 | 0.00 | 0.291927E+11 | 0.148491E+11 | 67767.70 | 01-JUL-07:15 | 34404.98 | 0.00 |
August | 0.00 | 0.00 | 0.303173E+11 | 0.129463E+11 | 68076.53 | 31-AUG-07:15 | 28949.54 | 0.00 |
September | 0.00 | 0.00 | 0.325601E+11 | 0.161551E+11 | 67626.37 | 30-SEP-07:23 | 33417.84 | 0.00 |
October | 0.00 | 0.00 | 0.375599E+11 | 0.317295E+11 | 62110.87 | 31-OCT-05:15 | 52121.43 | 0.00 |
November | 0.00 | 0.00 | 0.401866E+11 | 0.383187E+11 | 57033.31 | 30-NOV-06:15 | 54105.55 | 0.00 |
December | 0.00 | 0.00 | 0.440875E+11 | 0.435825E+11 | 51996.97 | 31-DEC-16:07 | 51264.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.443912E+12 | 0.375134E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.291927E+11 | 0.129463E+11 | 51043.46 | 28949.54 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.453160E+11 | 0.437082E+11 | 68076.53 | 63622.14 | 0.00 |
Report: CoilReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.511225E+11 | 0.493240E+11 | 64597.12 | 17-JAN-17:10 | 62304.58 | 0.00 |
February | 0.00 | 0.00 | 0.495120E+11 | 0.470809E+11 | 69521.36 | 01-FEB-17:10 | 65964.50 | 0.00 |
March | 0.00 | 0.00 | 0.591596E+11 | 0.580622E+11 | 75403.57 | 01-MAR-17:10 | 73610.15 | 0.00 |
April | 0.00 | 0.00 | 0.609690E+11 | 0.609683E+11 | 80524.70 | 01-APR-16:10 | 80524.70 | 0.00 |
May | 0.00 | 0.00 | 0.658649E+11 | 0.632495E+11 | 84510.45 | 01-MAY-16:10 | 80525.08 | 0.00 |
June | 0.00 | 0.00 | 0.611470E+11 | 0.474598E+11 | 83012.17 | 01-JUN-16:10 | 64135.49 | 0.00 |
July | 0.00 | 0.00 | 0.616396E+11 | 0.313578E+11 | 79277.88 | 01-JUL-16:10 | 40235.50 | 0.00 |
August | 0.00 | 0.00 | 0.628493E+11 | 0.268328E+11 | 82378.41 | 31-AUG-16:10 | 35031.29 | 0.00 |
September | 0.00 | 0.00 | 0.639769E+11 | 0.317289E+11 | 85595.00 | 30-SEP-19:00 | 42274.80 | 0.00 |
October | 0.00 | 0.00 | 0.614884E+11 | 0.519595E+11 | 78611.07 | 31-OCT-16:10 | 65985.94 | 0.00 |
November | 0.00 | 0.00 | 0.547697E+11 | 0.522443E+11 | 72181.68 | 30-NOV-23:50 | 68494.82 | 0.00 |
December | 0.00 | 0.00 | 0.518531E+11 | 0.512757E+11 | 65804.48 | 31-DEC-17:50 | 64897.43 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.704352E+12 | 0.571544E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.495120E+11 | 0.268328E+11 | 64597.12 | 35031.29 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.658649E+11 | 0.632495E+11 | 85595.00 | 80525.08 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.688318E+11 | 0.688318E+11 | 130618.92 | 12-JAN-16:20 | 130618.92 | 0.47 |
February | 0.00 | 0.00 | 0.147738E+12 | 0.144559E+12 | 191089.47 | 25-FEB-18:17 | 118000.36 | 0.74 |
March | 0.00 | 0.00 | 0.344814E+12 | 0.324207E+12 | 324255.14 | 10-MAR-20:30 | 221906.43 | 0.94 |
April | 0.00 | 0.00 | 0.541718E+12 | 0.483043E+12 | 376062.18 | 26-APR-21:00 | 268248.14 | 0.98 |
May | 0.00 | 0.00 | 0.773464E+12 | 0.576865E+12 | 501926.15 | 22-MAY-21:00 | 240218.05 | 1.00 |
June | 0.00 | 0.00 | 0.898044E+12 | 0.571125E+12 | 518410.97 | 29-JUN-21:00 | 282499.26 | 1.00 |
July | 0.00 | 0.00 | 0.106423E+13 | 0.564952E+12 | 542469.12 | 13-JUL-18:02 | 275826.15 | 1.00 |
August | 0.00 | 0.00 | 0.108202E+13 | 0.543959E+12 | 586608.26 | 28-AUG-18:02 | 280688.85 | 1.00 |
September | 0.00 | 0.00 | 0.931283E+12 | 0.501578E+12 | 546618.32 | 14-SEP-18:03 | 273209.15 | 1.00 |
October | 0.00 | 0.00 | 0.557453E+12 | 0.424398E+12 | 432702.71 | 12-OCT-20:00 | 211172.25 | 1.00 |
November | 0.00 | 0.00 | 0.244638E+12 | 0.235982E+12 | 278853.30 | 08-NOV-19:08 | 192883.18 | 0.92 |
December | 0.00 | 0.00 | 0.903586E+11 | 0.900716E+11 | 145916.58 | 03-DEC-13:00 | 145916.58 | 0.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.674460E+13 | 0.452957E+13 | 0.88 | |||
Minimum of Months | 0.00 | 0.00 | 0.688318E+11 | 0.688318E+11 | 130618.92 | 118000.36 | 0.47 | |
Maximum of Months | 0.00 | 0.00 | 0.108202E+13 | 0.576865E+12 | 586608.26 | 282499.26 | 1.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.415393E+10 | 0.413816E+10 | 15958.11 | 12-JAN-16:01 | 15958.11 | 0.16 |
February | 0.00 | 0.00 | 0.991351E+10 | 0.929049E+10 | 25529.81 | 25-FEB-17:00 | 13608.43 | 0.41 |
March | 0.00 | 0.00 | 0.260363E+11 | 0.231951E+11 | 26374.72 | 29-MAR-08:15 | 16132.14 | 0.71 |
April | 0.00 | 0.00 | 0.369569E+11 | 0.330189E+11 | 28762.85 | 25-APR-08:62 | 18736.52 | 0.79 |
May | 0.00 | 0.00 | 0.495726E+11 | 0.374273E+11 | 37779.09 | 22-MAY-23:00 | 16829.66 | 0.79 |
June | 0.00 | 0.00 | 0.593590E+11 | 0.371422E+11 | 44880.78 | 28-JUN-13:00 | 21188.51 | 0.79 |
July | 0.00 | 0.00 | 0.722065E+11 | 0.372628E+11 | 45460.97 | 18-JUL-15:00 | 14775.26 | 0.79 |
August | 0.00 | 0.00 | 0.727658E+11 | 0.359183E+11 | 45949.38 | 10-AUG-14:40 | 15118.03 | 0.79 |
September | 0.00 | 0.00 | 0.630464E+11 | 0.335756E+11 | 42526.37 | 12-SEP-15:02 | 19604.47 | 0.79 |
October | 0.00 | 0.00 | 0.411362E+11 | 0.293743E+11 | 40724.61 | 13-OCT-08:30 | 15837.14 | 0.79 |
November | 0.00 | 0.00 | 0.156078E+11 | 0.141733E+11 | 25915.92 | 08-NOV-19:40 | 15305.20 | 0.61 |
December | 0.00 | 0.00 | 0.545463E+10 | 0.543023E+10 | 16352.24 | 28-DEC-16:02 | 16352.24 | 0.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.456210E+12 | 0.299947E+12 | 0.64 | |||
Minimum of Months | 0.00 | 0.00 | 0.415393E+10 | 0.413816E+10 | 15958.11 | 13608.43 | 0.16 | |
Maximum of Months | 0.00 | 0.00 | 0.727658E+11 | 0.374273E+11 | 45949.38 | 21188.51 | 0.79 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.140800E+10 | 0.679201E+09 | 14348.18 | 18-JAN-16:01 | 10404.26 | 0.42 |
February | 0.00 | 0.00 | 0.329445E+10 | 0.168209E+10 | 13732.10 | 25-FEB-09:02 | 10919.88 | 0.75 |
March | 0.00 | 0.00 | 0.779512E+10 | 0.482717E+10 | 13739.02 | 10-MAR-09:01 | 11665.96 | 0.93 |
April | 0.00 | 0.00 | 0.121798E+11 | 0.895861E+10 | 14216.07 | 23-APR-08:61 | 11624.52 | 0.97 |
May | 0.00 | 0.00 | 0.146087E+11 | 0.109209E+11 | 14027.69 | 13-MAY-08:62 | 11801.93 | 0.98 |
June | 0.00 | 0.00 | 0.140376E+11 | 0.102193E+11 | 14331.17 | 25-JUN-08:61 | 11974.32 | 0.98 |
July | 0.00 | 0.00 | 0.130982E+11 | 0.909946E+10 | 14041.67 | 18-JUL-15:02 | 12077.69 | 0.97 |
August | 0.00 | 0.00 | 0.120518E+11 | 0.812054E+10 | 14158.81 | 20-AUG-08:62 | 12077.41 | 0.97 |
September | 0.00 | 0.00 | 0.109923E+11 | 0.734251E+10 | 15189.28 | 09-SEP-15:02 | 11463.23 | 0.96 |
October | 0.00 | 0.00 | 0.103007E+11 | 0.681957E+10 | 14414.01 | 12-OCT-08:62 | 11191.56 | 0.96 |
November | 0.00 | 0.00 | 0.636668E+10 | 0.361529E+10 | 13713.11 | 18-NOV-09:02 | 10982.02 | 0.92 |
December | 0.00 | 0.00 | 0.205811E+10 | 0.946334E+09 | 13646.09 | 10-DEC-16:01 | 10957.55 | 0.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.108191E+12 | 0.732310E+11 | 0.87 | |||
Minimum of Months | 0.00 | 0.00 | 0.140800E+10 | 0.679201E+09 | 13646.09 | 10404.26 | 0.42 | |
Maximum of Months | 0.00 | 0.00 | 0.146087E+11 | 0.109209E+11 | 15189.28 | 12077.69 | 0.98 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.209065E+09 | 98846938.88 | 14143.77 | 14-JAN-16:01 | 11199.91 | 0.13 |
February | 0.00 | 0.00 | 0.123338E+10 | 0.527474E+09 | 14432.82 | 14-FEB-16:01 | 11332.63 | 0.41 |
March | 0.00 | 0.00 | 0.552002E+10 | 0.324263E+10 | 15263.17 | 10-MAR-09:51 | 11363.28 | 0.70 |
April | 0.00 | 0.00 | 0.110291E+11 | 0.800578E+10 | 15876.11 | 22-APR-08:11 | 12611.26 | 0.90 |
May | 0.00 | 0.00 | 0.143877E+11 | 0.106904E+11 | 16672.32 | 13-MAY-08:11 | 11933.57 | 0.98 |
June | 0.00 | 0.00 | 0.140545E+11 | 0.102329E+11 | 15213.97 | 18-JUN-08:62 | 11419.44 | 0.98 |
July | 0.00 | 0.00 | 0.130876E+11 | 0.907357E+10 | 14102.68 | 18-JUL-15:02 | 12119.90 | 0.97 |
August | 0.00 | 0.00 | 0.118491E+11 | 0.790073E+10 | 14222.64 | 20-AUG-08:62 | 12118.22 | 0.97 |
September | 0.00 | 0.00 | 0.101911E+11 | 0.650244E+10 | 15283.98 | 09-SEP-15:02 | 11485.32 | 0.95 |
October | 0.00 | 0.00 | 0.754276E+10 | 0.464104E+10 | 16318.27 | 06-OCT-08:61 | 11937.64 | 0.77 |
November | 0.00 | 0.00 | 0.299955E+10 | 0.138714E+10 | 14624.95 | 09-NOV-09:51 | 11052.96 | 0.62 |
December | 0.00 | 0.00 | 0.372839E+09 | 0.151573E+09 | 13904.05 | 16-DEC-16:01 | 11377.07 | 0.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.924768E+11 | 0.624544E+11 | 0.71 | |||
Minimum of Months | 0.00 | 0.00 | 0.209065E+09 | 98846938.88 | 13904.05 | 11052.96 | 0.13 | |
Maximum of Months | 0.00 | 0.00 | 0.143877E+11 | 0.106904E+11 | 16672.32 | 12611.26 | 0.98 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.234026E+11 | 0.134423E+11 | 34975.98 | 08-JAN-14:00 | 29223.46 | 0.65 |
February | 0.00 | 0.00 | 0.306450E+11 | 0.178018E+11 | 38407.96 | 20-FEB-13:50 | 34877.94 | 0.86 |
March | 0.00 | 0.00 | 0.474737E+11 | 0.284167E+11 | 40649.88 | 13-MAR-13:30 | 38045.50 | 1.00 |
April | 0.00 | 0.00 | 0.591496E+11 | 0.386152E+11 | 40856.19 | 15-APR-13:50 | 39650.94 | 1.00 |
May | 0.00 | 0.00 | 0.653980E+11 | 0.427967E+11 | 40990.00 | 04-MAY-17:20 | 39252.48 | 1.00 |
June | 0.00 | 0.00 | 0.618619E+11 | 0.389999E+11 | 39707.18 | 12-JUN-17:20 | 36843.47 | 1.00 |
July | 0.00 | 0.00 | 0.622669E+11 | 0.370623E+11 | 38016.53 | 08-JUL-08:00 | 29684.79 | 1.00 |
August | 0.00 | 0.00 | 0.594712E+11 | 0.337568E+11 | 36309.01 | 07-AUG-16:20 | 28558.94 | 1.00 |
September | 0.00 | 0.00 | 0.581675E+11 | 0.355103E+11 | 44485.15 | 26-SEP-15:02 | 39970.30 | 1.00 |
October | 0.00 | 0.00 | 0.667148E+11 | 0.452637E+11 | 47725.48 | 02-OCT-13:30 | 37290.07 | 1.00 |
November | 0.00 | 0.00 | 0.550607E+11 | 0.369770E+11 | 46082.25 | 04-NOV-13:30 | 35267.20 | 1.00 |
December | 0.00 | 0.00 | 0.315606E+11 | 0.187764E+11 | 40572.24 | 02-DEC-13:30 | 39158.79 | 0.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.621173E+12 | 0.387419E+12 | 0.94 | |||
Minimum of Months | 0.00 | 0.00 | 0.234026E+11 | 0.134423E+11 | 34975.98 | 28558.94 | 0.65 | |
Maximum of Months | 0.00 | 0.00 | 0.667148E+11 | 0.452637E+11 | 47725.48 | 39970.30 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.894943E+10 | 0.421679E+10 | 88936.53 | 14-JAN-16:01 | 79860.86 | 0.40 |
February | 0.00 | 0.00 | 0.171292E+11 | 0.893412E+10 | 95726.92 | 24-FEB-22:52 | 75721.40 | 0.51 |
March | 0.00 | 0.00 | 0.407619E+11 | 0.252586E+11 | 97834.92 | 10-MAR-09:51 | 77726.98 | 0.62 |
April | 0.00 | 0.00 | 0.666016E+11 | 0.452124E+11 | 100208.73 | 22-APR-08:11 | 86152.33 | 0.83 |
May | 0.00 | 0.00 | 0.887475E+11 | 0.636151E+11 | 110815.97 | 13-MAY-08:11 | 79577.47 | 0.93 |
June | 0.00 | 0.00 | 0.887361E+11 | 0.627708E+11 | 102459.57 | 18-JUN-06:52 | 74928.84 | 0.93 |
July | 0.00 | 0.00 | 0.893342E+11 | 0.621389E+11 | 97527.61 | 18-JUL-15:02 | 83665.11 | 0.93 |
August | 0.00 | 0.00 | 0.826867E+11 | 0.557897E+11 | 97416.89 | 16-AUG-15:02 | 84184.07 | 0.92 |
September | 0.00 | 0.00 | 0.698769E+11 | 0.445230E+11 | 101159.67 | 09-SEP-15:02 | 82047.37 | 0.88 |
October | 0.00 | 0.00 | 0.517488E+11 | 0.314696E+11 | 110566.40 | 11-OCT-21:51 | 76788.09 | 0.70 |
November | 0.00 | 0.00 | 0.267623E+11 | 0.146192E+11 | 98551.39 | 05-NOV-15:01 | 83577.39 | 0.53 |
December | 0.00 | 0.00 | 0.111376E+11 | 0.525821E+10 | 89082.75 | 29-DEC-22:53 | 66899.86 | 0.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.642472E+12 | 0.423806E+12 | 0.72 | |||
Minimum of Months | 0.00 | 0.00 | 0.894943E+10 | 0.421679E+10 | 88936.53 | 66899.86 | 0.40 | |
Maximum of Months | 0.00 | 0.00 | 0.893342E+11 | 0.636151E+11 | 110815.97 | 86152.33 | 0.93 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.138503E+10 | 0.655288E+09 | 12551.27 | 18-JAN-16:01 | 8742.19 | 0.45 |
February | 0.00 | 0.00 | 0.347403E+10 | 0.187344E+10 | 12753.38 | 26-FEB-16:01 | 10005.05 | 0.77 |
March | 0.00 | 0.00 | 0.791238E+10 | 0.499131E+10 | 12391.02 | 18-MAR-08:62 | 9527.79 | 0.95 |
April | 0.00 | 0.00 | 0.122012E+11 | 0.914192E+10 | 11924.27 | 23-APR-08:61 | 11017.50 | 0.98 |
May | 0.00 | 0.00 | 0.146974E+11 | 0.112664E+11 | 12481.40 | 13-MAY-08:62 | 10757.29 | 0.98 |
June | 0.00 | 0.00 | 0.136421E+11 | 0.101247E+11 | 12862.96 | 25-JUN-08:61 | 10850.11 | 0.98 |
July | 0.00 | 0.00 | 0.131101E+11 | 0.933440E+10 | 12612.02 | 18-JUL-15:02 | 10936.91 | 0.98 |
August | 0.00 | 0.00 | 0.120297E+11 | 0.829579E+10 | 12696.08 | 20-AUG-08:62 | 10949.39 | 0.97 |
September | 0.00 | 0.00 | 0.108638E+11 | 0.742324E+10 | 13634.81 | 09-SEP-15:02 | 10392.79 | 0.97 |
October | 0.00 | 0.00 | 0.103469E+11 | 0.692972E+10 | 12947.28 | 12-OCT-08:62 | 10140.02 | 0.97 |
November | 0.00 | 0.00 | 0.633260E+10 | 0.365065E+10 | 12130.33 | 18-NOV-09:02 | 10067.16 | 0.94 |
December | 0.00 | 0.00 | 0.206703E+10 | 0.101257E+10 | 11999.86 | 10-DEC-16:01 | 10073.94 | 0.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.108062E+12 | 0.746995E+11 | 0.88 | |||
Minimum of Months | 0.00 | 0.00 | 0.138503E+10 | 0.655288E+09 | 11924.27 | 8742.19 | 0.45 | |
Maximum of Months | 0.00 | 0.00 | 0.146974E+11 | 0.112664E+11 | 13634.81 | 11017.50 | 0.98 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.256652E+09 | 0.107538E+09 | 12501.42 | 14-JAN-16:01 | 10212.01 | 0.14 |
February | 0.00 | 0.00 | 0.141526E+10 | 0.665601E+09 | 12972.79 | 26-FEB-16:01 | 9907.01 | 0.43 |
March | 0.00 | 0.00 | 0.552806E+10 | 0.328293E+10 | 14724.33 | 10-MAR-09:51 | 11739.72 | 0.72 |
April | 0.00 | 0.00 | 0.110080E+11 | 0.806373E+10 | 14878.53 | 23-APR-08:41 | 11941.55 | 0.91 |
May | 0.00 | 0.00 | 0.144767E+11 | 0.110833E+11 | 15204.18 | 13-MAY-08:11 | 11033.01 | 0.98 |
June | 0.00 | 0.00 | 0.136605E+11 | 0.101484E+11 | 13449.74 | 18-JUN-06:52 | 10054.25 | 0.98 |
July | 0.00 | 0.00 | 0.130978E+11 | 0.931639E+10 | 12638.43 | 18-JUL-15:02 | 10954.00 | 0.98 |
August | 0.00 | 0.00 | 0.118245E+11 | 0.806297E+10 | 12725.55 | 20-AUG-08:62 | 10964.81 | 0.97 |
September | 0.00 | 0.00 | 0.100658E+11 | 0.648251E+10 | 13689.59 | 09-SEP-15:02 | 10392.59 | 0.96 |
October | 0.00 | 0.00 | 0.754657E+10 | 0.466309E+10 | 15117.48 | 01-OCT-08:21 | 12098.22 | 0.78 |
November | 0.00 | 0.00 | 0.291690E+10 | 0.142022E+10 | 14022.08 | 09-NOV-09:51 | 11245.03 | 0.63 |
December | 0.00 | 0.00 | 0.451778E+09 | 0.196122E+09 | 12335.45 | 16-DEC-16:01 | 10257.22 | 0.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.922485E+11 | 0.634928E+11 | 0.72 | |||
Minimum of Months | 0.00 | 0.00 | 0.256652E+09 | 0.107538E+09 | 12335.45 | 9907.01 | 0.14 | |
Maximum of Months | 0.00 | 0.00 | 0.144767E+11 | 0.110833E+11 | 15204.18 | 12098.22 | 0.98 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.320344E+09 | 0.162029E+09 | 3999.31 | 18-JAN-16:01 | 2769.00 | 0.33 |
February | 0.00 | 0.00 | 0.770531E+09 | 0.398877E+09 | 3915.42 | 26-FEB-09:02 | 2389.46 | 0.65 |
March | 0.00 | 0.00 | 0.194047E+10 | 0.119178E+10 | 3936.19 | 10-MAR-09:01 | 3053.05 | 0.92 |
April | 0.00 | 0.00 | 0.318920E+10 | 0.230875E+10 | 4177.06 | 23-APR-08:61 | 2972.98 | 0.97 |
May | 0.00 | 0.00 | 0.391102E+10 | 0.291076E+10 | 4019.14 | 13-MAY-08:62 | 3086.45 | 0.98 |
June | 0.00 | 0.00 | 0.378606E+10 | 0.277832E+10 | 4146.75 | 25-JUN-08:61 | 3105.39 | 0.98 |
July | 0.00 | 0.00 | 0.347035E+10 | 0.239054E+10 | 3975.54 | 23-JUL-08:62 | 3208.43 | 0.97 |
August | 0.00 | 0.00 | 0.315491E+10 | 0.208724E+10 | 4053.81 | 20-AUG-08:62 | 3161.85 | 0.97 |
September | 0.00 | 0.00 | 0.283511E+10 | 0.183700E+10 | 4127.25 | 09-SEP-15:02 | 3117.01 | 0.96 |
October | 0.00 | 0.00 | 0.256131E+10 | 0.164377E+10 | 4137.66 | 12-OCT-08:62 | 2837.87 | 0.95 |
November | 0.00 | 0.00 | 0.146410E+10 | 0.815281E+09 | 3927.18 | 18-NOV-09:02 | 2745.37 | 0.88 |
December | 0.00 | 0.00 | 0.448662E+09 | 0.208528E+09 | 3758.30 | 10-DEC-16:01 | 2950.18 | 0.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.278521E+11 | 0.187329E+11 | 0.83 | |||
Minimum of Months | 0.00 | 0.00 | 0.320344E+09 | 0.162029E+09 | 3758.30 | 2389.46 | 0.33 | |
Maximum of Months | 0.00 | 0.00 | 0.391102E+10 | 0.291076E+10 | 4177.06 | 3208.43 | 0.98 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 34074785.69 | 18648407.98 | 3945.78 | 14-JAN-16:01 | 2981.50 | 0.06 |
February | 0.00 | 0.00 | 0.264597E+09 | 0.118238E+09 | 3999.77 | 14-FEB-16:01 | 3031.77 | 0.31 |
March | 0.00 | 0.00 | 0.139130E+10 | 0.811954E+09 | 4250.93 | 10-MAR-09:51 | 3004.12 | 0.70 |
April | 0.00 | 0.00 | 0.290855E+10 | 0.209051E+10 | 4375.79 | 03-APR-08:61 | 3301.56 | 0.90 |
May | 0.00 | 0.00 | 0.385503E+10 | 0.285154E+10 | 4706.10 | 13-MAY-08:11 | 3082.32 | 0.98 |
June | 0.00 | 0.00 | 0.379136E+10 | 0.278210E+10 | 4361.08 | 18-JUN-08:62 | 2963.72 | 0.98 |
July | 0.00 | 0.00 | 0.346748E+10 | 0.238533E+10 | 3988.20 | 23-JUL-08:62 | 3218.81 | 0.97 |
August | 0.00 | 0.00 | 0.310127E+10 | 0.202934E+10 | 4069.87 | 20-AUG-08:62 | 3170.06 | 0.97 |
September | 0.00 | 0.00 | 0.262586E+10 | 0.163699E+10 | 4169.44 | 27-SEP-08:62 | 3101.82 | 0.95 |
October | 0.00 | 0.00 | 0.188118E+10 | 0.112205E+10 | 4649.83 | 06-OCT-08:61 | 3007.57 | 0.77 |
November | 0.00 | 0.00 | 0.634446E+09 | 0.296483E+09 | 4096.97 | 09-NOV-09:51 | 2879.30 | 0.55 |
December | 0.00 | 0.00 | 59130111.79 | 26203457.81 | 3873.32 | 10-DEC-16:01 | 2786.02 | 0.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.240143E+11 | 0.161694E+11 | 0.69 | |||
Minimum of Months | 0.00 | 0.00 | 34074785.69 | 18648407.98 | 3873.32 | 2786.02 | 0.06 | |
Maximum of Months | 0.00 | 0.00 | 0.385503E+10 | 0.285154E+10 | 4706.10 | 3301.56 | 0.98 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.569563E+10 | 0.370669E+10 | 18364.65 | 17-JAN-16:01 | 13257.59 | 0.68 |
February | 0.00 | 0.00 | 0.770991E+10 | 0.505863E+10 | 17896.40 | 25-FEB-19:01 | 13654.67 | 0.85 |
March | 0.00 | 0.00 | 0.125172E+11 | 0.835405E+10 | 17480.15 | 18-MAR-18:01 | 14081.92 | 0.94 |
April | 0.00 | 0.00 | 0.161605E+11 | 0.117307E+11 | 18137.48 | 23-APR-08:61 | 14788.72 | 0.96 |
May | 0.00 | 0.00 | 0.184974E+11 | 0.136439E+11 | 18302.47 | 13-MAY-08:62 | 14777.97 | 0.97 |
June | 0.00 | 0.00 | 0.177513E+11 | 0.128137E+11 | 18397.31 | 18-JUN-08:62 | 15029.82 | 0.97 |
July | 0.00 | 0.00 | 0.175704E+11 | 0.123844E+11 | 17957.90 | 18-JUL-15:02 | 15336.89 | 0.97 |
August | 0.00 | 0.00 | 0.166179E+11 | 0.114881E+11 | 17661.28 | 20-AUG-08:62 | 15593.39 | 0.97 |
September | 0.00 | 0.00 | 0.158508E+11 | 0.108749E+11 | 18942.43 | 09-SEP-15:02 | 14847.31 | 0.96 |
October | 0.00 | 0.00 | 0.172560E+11 | 0.121877E+11 | 18926.19 | 12-OCT-08:62 | 13892.34 | 0.96 |
November | 0.00 | 0.00 | 0.135132E+11 | 0.938689E+10 | 16947.82 | 18-NOV-09:02 | 14302.10 | 0.95 |
December | 0.00 | 0.00 | 0.735324E+10 | 0.487386E+10 | 16666.35 | 29-DEC-16:01 | 14407.92 | 0.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.166494E+12 | 0.116503E+12 | 0.92 | |||
Minimum of Months | 0.00 | 0.00 | 0.569563E+10 | 0.370669E+10 | 16666.35 | 13257.59 | 0.68 | |
Maximum of Months | 0.00 | 0.00 | 0.184974E+11 | 0.136439E+11 | 18942.43 | 15593.39 | 0.97 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2485.61 | 47473.67 | 02-JAN-09:03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 610.31 | 31891.98 | 02-FEB-09:05 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 41.28 | 18714.46 | 16-MAR-08:54 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.83 | 14123.89 | 12-APR-08:35 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 13.25 | 12190.60 | 29-MAY-08:07 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.59 | 11188.98 | 27-JUN-18:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.99 | 11296.22 | 26-JUL-08:05 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.36 | 11100.08 | 23-AUG-18:07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.02 | 14732.08 | 09-SEP-15:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 35.59 | 21462.73 | 30-OCT-08:54 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 86.49 | 23401.07 | 14-NOV-09:54 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 1284.44 | 33477.96 | 21-DEC-09:04 |
Annual Sum or Average | 0.00 | 390.07 | ||||
Minimum of Months | 0.00 | 0.00 | 13.25 | 11100.08 | ||
Maximum of Months | 0.00 | 0.00 | 2485.61 | 47473.67 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 46879.86 | 312821.22 | 12-JAN-16:03 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 96775.93 | 360409.49 | 22-FEB-16:03 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 191773.04 | 519626.46 | 10-MAR-19:03 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 302838.05 | 571965.15 | 26-APR-18:05 | 0.00 | 0.00 | 01-APR-00:10 |
May | 401008.91 | 678175.61 | 17-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 463340.91 | 747575.72 | 22-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 514421.03 | 778732.26 | 01-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 515395.70 | 818732.12 | 28-AUG-18:02 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 462167.66 | 786417.95 | 14-SEP-18:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 293668.59 | 594061.04 | 12-OCT-21:53 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 149596.86 | 410665.82 | 04-NOV-18:03 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 60746.43 | 363936.68 | 01-DEC-16:01 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 292571.86 | 0.00 | ||||
Minimum of Months | 46879.86 | 312821.22 | 0.00 | 0.00 | ||
Maximum of Months | 515395.70 | 818732.12 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 21322.76 | 44575.16 | 17-JAN-07:30 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 20876.07 | 44302.25 | 01-FEB-07:30 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 19540.27 | 42406.81 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 17574.43 | 38400.38 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15567.16 | 34414.58 | 01-MAY-06:40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14046.78 | 30511.23 | 01-JUN-06:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 13408.12 | 28145.30 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 13873.31 | 30036.82 | 31-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 15258.82 | 33507.14 | 29-SEP-06:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17216.07 | 38029.88 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 19220.25 | 41831.56 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 20721.89 | 44110.48 | 29-DEC-07:30 |
Annual Sum or Average | 0.00 | 17366.23 | ||||
Minimum of Months | 0.00 | 0.00 | 13408.12 | 28145.30 | ||
Maximum of Months | 0.00 | 0.00 | 21322.76 | 44575.16 |
Report: FanReportMonthly
For: SWHSYS1 HPWH FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.527492E+09 | 0.06 | 553.22 | 01-JAN-06:15 | 0.10 |
February | 0.444566E+09 | 0.06 | 553.22 | 01-FEB-06:15 | 0.10 |
March | 0.437556E+09 | 0.05 | 553.22 | 01-MAR-05:10 | 0.10 |
April | 0.366650E+09 | 0.05 | 553.22 | 01-APR-05:08 | 0.10 |
May | 0.326533E+09 | 0.05 | 553.22 | 01-MAY-07:15 | 0.10 |
June | 0.282477E+09 | 0.05 | 553.22 | 01-JUN-07:05 | 0.10 |
July | 0.278244E+09 | 0.05 | 553.22 | 01-JUL-07:15 | 0.10 |
August | 0.287287E+09 | 0.05 | 553.22 | 01-AUG-07:15 | 0.10 |
September | 0.307750E+09 | 0.05 | 553.22 | 01-SEP-07:15 | 0.10 |
October | 0.377070E+09 | 0.05 | 553.22 | 01-OCT-05:23 | 0.10 |
November | 0.428555E+09 | 0.05 | 553.22 | 01-NOV-05:15 | 0.10 |
December | 0.507999E+09 | 0.06 | 553.22 | 01-DEC-06:15 | 0.10 |
Annual Sum or Average | 0.457218E+10 | 0.05 | |||
Minimum of Months | 0.278244E+09 | 0.05 | 553.22 | 0.10 | |
Maximum of Months | 0.527492E+09 | 0.06 | 553.22 | 0.10 |
Report: FanReportMonthly
For: SWHSYSLAUNDRY HPWH FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.556515E+09 | 0.05 | 700.51 | 01-JAN-17:10 | 0.10 |
February | 0.502486E+09 | 0.05 | 700.51 | 01-FEB-17:10 | 0.10 |
March | 0.556285E+09 | 0.05 | 700.51 | 01-MAR-17:10 | 0.10 |
April | 0.538082E+09 | 0.05 | 700.51 | 01-APR-16:10 | 0.10 |
May | 0.553839E+09 | 0.05 | 700.51 | 01-MAY-16:10 | 0.10 |
June | 0.511853E+09 | 0.05 | 684.41 | 01-JUN-16:10 | 0.10 |
July | 0.515963E+09 | 0.05 | 659.95 | 01-JUL-16:10 | 0.10 |
August | 0.524040E+09 | 0.05 | 677.17 | 31-AUG-16:10 | 0.10 |
September | 0.531467E+09 | 0.05 | 700.51 | 15-SEP-16:10 | 0.10 |
October | 0.556232E+09 | 0.05 | 700.51 | 01-OCT-16:10 | 0.10 |
November | 0.538167E+09 | 0.05 | 700.51 | 01-NOV-16:10 | 0.10 |
December | 0.556636E+09 | 0.05 | 700.51 | 01-DEC-17:10 | 0.10 |
Annual Sum or Average | 0.644157E+10 | 0.05 | |||
Minimum of Months | 0.502486E+09 | 0.05 | 659.95 | 0.10 | |
Maximum of Months | 0.556636E+09 | 0.05 | 700.51 | 0.10 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.71 | 1299.30 | 06-JAN-19:03 | 0.89 |
February | 0.244774E+10 | 0.71 | 1299.30 | 09-FEB-09:53 | 0.89 |
March | 0.271000E+10 | 0.71 | 1299.30 | 16-MAR-15:15 | 0.89 |
April | 0.262258E+10 | 0.71 | 1299.30 | 11-APR-15:05 | 0.90 |
May | 0.271000E+10 | 0.71 | 1299.30 | 01-MAY-15:08 | 0.89 |
June | 0.262258E+10 | 0.71 | 1299.30 | 02-JUN-15:25 | 0.89 |
July | 0.271000E+10 | 0.71 | 1299.30 | 01-JUL-15:07 | 0.89 |
August | 0.271000E+10 | 0.71 | 1299.30 | 08-AUG-15:07 | 0.89 |
September | 0.262258E+10 | 0.71 | 1299.30 | 20-SEP-18:05 | 0.89 |
October | 0.271000E+10 | 0.71 | 1299.30 | 17-OCT-18:15 | 0.89 |
November | 0.262258E+10 | 0.71 | 1299.30 | 06-NOV-16:15 | 0.89 |
December | 0.271000E+10 | 0.71 | 1299.30 | 25-DEC-21:15 | 0.90 |
Annual Sum or Average | 0.319080E+11 | 0.71 | |||
Minimum of Months | 0.244774E+10 | 0.71 | 1299.30 | 0.89 | |
Maximum of Months | 0.271000E+10 | 0.71 | 1299.30 | 0.90 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.339850E+11 | 0.82 | 22531.59 | 13-JAN-22:10 | 1.14 |
February | 0.316605E+11 | 0.83 | 24678.45 | 22-FEB-22:10 | 1.21 |
March | 0.378563E+11 | 0.87 | 29012.80 | 29-MAR-21:10 | 1.33 |
April | 0.404519E+11 | 0.91 | 34468.88 | 28-APR-21:20 | 1.48 |
May | 0.451866E+11 | 0.96 | 35560.44 | 04-MAY-21:20 | 1.51 |
June | 0.446221E+11 | 0.97 | 36069.75 | 12-JUN-21:10 | 1.53 |
July | 0.464325E+11 | 0.97 | 38231.23 | 05-JUL-21:10 | 1.58 |
August | 0.465196E+11 | 0.97 | 39104.21 | 07-AUG-21:20 | 1.61 |
September | 0.435118E+11 | 0.95 | 37626.75 | 22-SEP-21:10 | 1.57 |
October | 0.425059E+11 | 0.92 | 36169.36 | 03-OCT-21:10 | 1.53 |
November | 0.372796E+11 | 0.87 | 29223.53 | 09-NOV-22:10 | 1.34 |
December | 0.351662E+11 | 0.83 | 24570.95 | 28-DEC-22:10 | 1.20 |
Annual Sum or Average | 0.485178E+12 | 0.91 | |||
Minimum of Months | 0.316605E+11 | 0.82 | 22531.59 | 1.14 | |
Maximum of Months | 0.465196E+11 | 0.97 | 39104.21 | 1.61 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:10 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:03 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:03 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.27 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:05 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:05 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:05 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:05 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:05 | 0.27 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:03 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:05 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:10 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:10 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:10 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:10 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:10 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.139931E+09 | 0.46 | 721.89 | 01-JAN-16:02 | 0.58 |
February | 0.194475E+09 | 0.51 | 721.89 | 01-FEB-16:01 | 0.59 |
March | 0.394843E+09 | 0.55 | 721.89 | 01-MAR-09:02 | 0.59 |
April | 0.623899E+09 | 0.57 | 721.89 | 01-APR-08:61 | 0.59 |
May | 0.750476E+09 | 0.58 | 721.89 | 01-MAY-08:62 | 0.59 |
June | 0.719744E+09 | 0.57 | 721.89 | 01-JUN-08:62 | 0.59 |
July | 0.631218E+09 | 0.57 | 721.89 | 01-JUL-08:62 | 0.59 |
August | 0.560677E+09 | 0.57 | 721.89 | 01-AUG-08:62 | 0.59 |
September | 0.518936E+09 | 0.57 | 721.89 | 01-SEP-08:62 | 0.59 |
October | 0.498068E+09 | 0.56 | 721.89 | 01-OCT-08:62 | 0.59 |
November | 0.320932E+09 | 0.54 | 721.89 | 01-NOV-08:62 | 0.59 |
December | 0.150497E+09 | 0.49 | 721.89 | 01-DEC-09:02 | 0.59 |
Annual Sum or Average | 0.550369E+10 | 0.54 | |||
Minimum of Months | 0.139931E+09 | 0.46 | 721.89 | 0.58 | |
Maximum of Months | 0.750476E+09 | 0.58 | 721.89 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.102451E+09 | 0.36 | 724.69 | 02-JAN-09:02 | 0.59 |
February | 92786670.07 | 0.34 | 724.69 | 01-FEB-16:01 | 0.59 |
March | 0.278544E+09 | 0.41 | 724.69 | 01-MAR-09:51 | 0.59 |
April | 0.557787E+09 | 0.53 | 724.69 | 01-APR-08:61 | 0.58 |
May | 0.738225E+09 | 0.57 | 724.69 | 01-MAY-08:62 | 0.59 |
June | 0.721028E+09 | 0.57 | 724.69 | 01-JUN-08:62 | 0.59 |
July | 0.630784E+09 | 0.57 | 724.69 | 01-JUL-08:62 | 0.59 |
August | 0.549414E+09 | 0.57 | 724.69 | 01-AUG-08:62 | 0.59 |
September | 0.474861E+09 | 0.56 | 724.69 | 01-SEP-08:62 | 0.59 |
October | 0.359960E+09 | 0.45 | 724.69 | 01-OCT-08:21 | 0.58 |
November | 0.157913E+09 | 0.37 | 724.69 | 01-NOV-08:51 | 0.59 |
December | 83384621.99 | 0.36 | 724.69 | 01-DEC-16:01 | 0.59 |
Annual Sum or Average | 0.474714E+10 | 0.47 | |||
Minimum of Months | 83384621.99 | 0.34 | 724.69 | 0.58 | |
Maximum of Months | 0.738225E+09 | 0.57 | 724.69 | 0.59 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.107547E+10 | 0.41 | 1221.49 | 08-JAN-14:00 | 0.59 |
February | 0.131309E+10 | 0.51 | 1309.35 | 20-FEB-14:10 | 0.59 |
March | 0.188201E+10 | 0.59 | 1361.36 | 13-MAR-13:40 | 0.59 |
April | 0.219794E+10 | 0.59 | 1386.64 | 15-APR-14:00 | 0.59 |
May | 0.235545E+10 | 0.59 | 1380.26 | 04-MAY-17:20 | 0.59 |
June | 0.220781E+10 | 0.59 | 1339.87 | 12-JUN-17:20 | 0.59 |
July | 0.220566E+10 | 0.59 | 1270.76 | 04-JUL-20:10 | 0.59 |
August | 0.211581E+10 | 0.59 | 1203.39 | 07-AUG-17:20 | 0.59 |
September | 0.209225E+10 | 0.59 | 2058.49 | 26-SEP-13:30 | 0.59 |
October | 0.256667E+10 | 0.59 | 2203.23 | 01-OCT-13:30 | 0.59 |
November | 0.225960E+10 | 0.59 | 2149.24 | 04-NOV-13:30 | 0.59 |
December | 0.138219E+10 | 0.48 | 1393.36 | 02-DEC-13:30 | 0.59 |
Annual Sum or Average | 0.236539E+11 | 0.56 | |||
Minimum of Months | 0.107547E+10 | 0.41 | 1203.39 | 0.59 | |
Maximum of Months | 0.256667E+10 | 0.59 | 2203.23 | 0.59 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.702861E+09 | 0.35 | 4921.83 | 01-JAN-09:02 | 0.59 |
February | 0.952406E+09 | 0.31 | 4921.83 | 01-FEB-09:02 | 0.59 |
March | 0.203424E+10 | 0.37 | 4921.83 | 01-MAR-09:51 | 0.59 |
April | 0.327415E+10 | 0.49 | 4921.83 | 01-APR-07:52 | 0.59 |
May | 0.434161E+10 | 0.55 | 4921.83 | 01-MAY-08:62 | 0.59 |
June | 0.440570E+10 | 0.55 | 4921.83 | 01-JUN-08:62 | 0.59 |
July | 0.430307E+10 | 0.55 | 4921.83 | 01-JUL-08:62 | 0.59 |
August | 0.388974E+10 | 0.54 | 4921.83 | 01-AUG-08:62 | 0.59 |
September | 0.326787E+10 | 0.52 | 4921.83 | 01-SEP-08:62 | 0.59 |
October | 0.249751E+10 | 0.41 | 4921.83 | 01-OCT-08:21 | 0.59 |
November | 0.134117E+10 | 0.31 | 4921.83 | 01-NOV-08:51 | 0.59 |
December | 0.775891E+09 | 0.34 | 4921.83 | 01-DEC-09:52 | 0.59 |
Annual Sum or Average | 0.317862E+11 | 0.44 | |||
Minimum of Months | 0.702861E+09 | 0.31 | 4921.83 | 0.59 | |
Maximum of Months | 0.440570E+10 | 0.55 | 4921.83 | 0.59 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134512E+09 | 0.47 | 650.84 | 01-JAN-16:02 | 0.58 |
February | 0.199421E+09 | 0.52 | 650.84 | 01-FEB-09:02 | 0.59 |
March | 0.397120E+09 | 0.56 | 650.84 | 01-MAR-09:02 | 0.59 |
April | 0.615724E+09 | 0.58 | 650.84 | 01-APR-08:61 | 0.59 |
May | 0.762883E+09 | 0.58 | 650.84 | 01-MAY-08:62 | 0.59 |
June | 0.695656E+09 | 0.58 | 650.84 | 01-JUN-08:62 | 0.59 |
July | 0.643129E+09 | 0.57 | 650.84 | 01-JUL-08:62 | 0.59 |
August | 0.565083E+09 | 0.57 | 650.84 | 01-AUG-08:62 | 0.59 |
September | 0.508814E+09 | 0.57 | 650.84 | 01-SEP-08:62 | 0.59 |
October | 0.502038E+09 | 0.57 | 650.84 | 01-OCT-08:62 | 0.59 |
November | 0.323106E+09 | 0.55 | 650.84 | 01-NOV-08:62 | 0.59 |
December | 0.148778E+09 | 0.50 | 650.84 | 01-DEC-09:02 | 0.59 |
Annual Sum or Average | 0.549626E+10 | 0.55 | |||
Minimum of Months | 0.134512E+09 | 0.47 | 650.84 | 0.58 | |
Maximum of Months | 0.762883E+09 | 0.58 | 650.84 | 0.59 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 93535366.77 | 0.35 | 652.00 | 04-JAN-16:01 | 0.59 |
February | 98453358.85 | 0.35 | 652.00 | 01-FEB-16:01 | 0.59 |
March | 0.275378E+09 | 0.43 | 652.00 | 01-MAR-09:51 | 0.59 |
April | 0.549741E+09 | 0.53 | 652.00 | 01-APR-07:52 | 0.58 |
May | 0.747327E+09 | 0.58 | 652.00 | 01-MAY-08:62 | 0.59 |
June | 0.697675E+09 | 0.57 | 652.00 | 01-JUN-08:62 | 0.59 |
July | 0.642830E+09 | 0.57 | 652.00 | 01-JUL-08:62 | 0.59 |
August | 0.554236E+09 | 0.57 | 652.00 | 01-AUG-08:62 | 0.59 |
September | 0.469508E+09 | 0.57 | 652.00 | 01-SEP-08:62 | 0.59 |
October | 0.360089E+09 | 0.46 | 652.00 | 01-OCT-08:21 | 0.58 |
November | 0.152380E+09 | 0.38 | 652.00 | 01-NOV-08:51 | 0.59 |
December | 82573459.72 | 0.34 | 652.00 | 01-DEC-09:52 | 0.59 |
Annual Sum or Average | 0.472373E+10 | 0.48 | |||
Minimum of Months | 82573459.72 | 0.34 | 652.00 | 0.58 | |
Maximum of Months | 0.747327E+09 | 0.58 | 652.00 | 0.59 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 41646159.66 | 0.46 | 196.40 | 01-JAN-16:02 | 0.58 |
February | 49655894.56 | 0.51 | 196.40 | 01-FEB-16:01 | 0.59 |
March | 99472787.44 | 0.55 | 196.40 | 01-MAR-16:02 | 0.59 |
April | 0.164145E+09 | 0.57 | 196.40 | 01-APR-08:61 | 0.59 |
May | 0.199908E+09 | 0.58 | 196.40 | 01-MAY-08:62 | 0.59 |
June | 0.192440E+09 | 0.57 | 196.40 | 01-JUN-08:62 | 0.59 |
July | 0.166741E+09 | 0.57 | 196.40 | 01-JUL-08:62 | 0.59 |
August | 0.147047E+09 | 0.57 | 196.40 | 01-AUG-08:62 | 0.59 |
September | 0.134709E+09 | 0.57 | 196.40 | 01-SEP-08:62 | 0.59 |
October | 0.125347E+09 | 0.56 | 196.40 | 01-OCT-08:62 | 0.59 |
November | 75389196.49 | 0.54 | 196.40 | 01-NOV-08:62 | 0.59 |
December | 41970600.41 | 0.49 | 196.40 | 01-DEC-16:01 | 0.59 |
Annual Sum or Average | 0.143847E+10 | 0.54 | |||
Minimum of Months | 41646159.66 | 0.46 | 196.40 | 0.58 | |
Maximum of Months | 0.199908E+09 | 0.58 | 196.40 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 35533072.23 | 0.36 | 197.04 | 01-JAN-09:02 | 0.58 |
February | 25423640.25 | 0.34 | 197.04 | 01-FEB-16:01 | 0.59 |
March | 70985509.01 | 0.41 | 197.04 | 01-MAR-16:02 | 0.59 |
April | 0.148021E+09 | 0.53 | 197.04 | 01-APR-08:61 | 0.58 |
May | 0.196903E+09 | 0.57 | 197.04 | 01-MAY-08:62 | 0.59 |
June | 0.192808E+09 | 0.57 | 197.04 | 01-JUN-08:62 | 0.59 |
July | 0.166607E+09 | 0.57 | 197.04 | 01-JUL-08:62 | 0.59 |
August | 0.144116E+09 | 0.57 | 197.04 | 01-AUG-08:62 | 0.59 |
September | 0.122565E+09 | 0.56 | 197.04 | 01-SEP-08:62 | 0.59 |
October | 90819737.39 | 0.45 | 197.04 | 01-OCT-08:21 | 0.58 |
November | 35233992.02 | 0.37 | 197.04 | 01-NOV-15:01 | 0.59 |
December | 29812493.83 | 0.36 | 197.04 | 01-DEC-16:01 | 0.59 |
Annual Sum or Average | 0.125883E+10 | 0.47 | |||
Minimum of Months | 25423640.25 | 0.34 | 197.04 | 0.58 | |
Maximum of Months | 0.196903E+09 | 0.57 | 197.04 | 0.59 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.342985E+09 | 0.52 | 912.43 | 01-JAN-16:02 | 0.59 |
February | 0.413741E+09 | 0.53 | 912.43 | 01-FEB-09:02 | 0.59 |
March | 0.634562E+09 | 0.55 | 912.43 | 01-MAR-09:02 | 0.59 |
April | 0.807359E+09 | 0.57 | 912.43 | 01-APR-08:61 | 0.59 |
May | 0.921485E+09 | 0.57 | 912.43 | 01-MAY-08:62 | 0.59 |
June | 0.881565E+09 | 0.57 | 912.43 | 01-JUN-08:62 | 0.59 |
July | 0.842210E+09 | 0.57 | 912.43 | 01-JUL-08:62 | 0.59 |
August | 0.776257E+09 | 0.57 | 912.43 | 01-AUG-08:62 | 0.59 |
September | 0.757156E+09 | 0.57 | 912.43 | 01-SEP-08:62 | 0.59 |
October | 0.868944E+09 | 0.57 | 912.43 | 01-OCT-08:62 | 0.59 |
November | 0.705658E+09 | 0.56 | 912.43 | 01-NOV-08:62 | 0.59 |
December | 0.413458E+09 | 0.54 | 912.43 | 01-DEC-09:02 | 0.59 |
Annual Sum or Average | 0.836538E+10 | 0.56 | |||
Minimum of Months | 0.342985E+09 | 0.52 | 912.43 | 0.59 | |
Maximum of Months | 0.921485E+09 | 0.57 | 912.43 | 0.59 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 65845308.89 | 59853385.78 | 226.50 | 27-JAN-16:04 | 205.89 | 205.89 | 61.41 | 0.28 |
February | 15565416.87 | 14148963.93 | 222.77 | 01-FEB-16:04 | 202.50 | 202.50 | 55.01 | 0.27 |
March | 957078.63 | 869984.47 | 153.57 | 03-MAR-09:54 | 139.59 | 139.59 | 56.46 | 0.18 |
April | 461336.47 | 419354.85 | 114.84 | 12-APR-08:35 | 104.39 | 104.39 | 52.91 | 0.13 |
May | 321548.13 | 292287.25 | 107.33 | 29-MAY-08:07 | 97.56 | 97.56 | 54.77 | 0.12 |
June | 340523.76 | 309536.10 | 102.72 | 27-JUN-18:07 | 93.37 | 93.37 | 55.68 | 0.11 |
July | 394489.15 | 358590.64 | 103.51 | 26-JUL-08:05 | 94.09 | 94.09 | 55.65 | 0.11 |
August | 435764.44 | 396109.88 | 98.63 | 23-AUG-18:07 | 89.65 | 89.65 | 54.82 | 0.11 |
September | 708476.66 | 644005.28 | 122.94 | 07-SEP-08:04 | 111.76 | 111.76 | 53.87 | 0.14 |
October | 793904.22 | 721658.94 | 161.19 | 30-OCT-08:54 | 146.52 | 146.52 | 51.86 | 0.19 |
November | 1996006.01 | 1814369.46 | 177.48 | 27-NOV-09:05 | 161.33 | 161.33 | 58.72 | 0.21 |
December | 37305652.28 | 33910837.92 | 217.23 | 09-DEC-16:04 | 197.47 | 197.47 | 57.17 | 0.26 |
Annual Sum or Average | 0.125126E+09 | 0.113739E+09 | ||||||
Minimum of Months | 321548.13 | 292287.25 | 98.63 | 89.65 | 89.65 | 51.86 | 0.11 | |
Maximum of Months | 65845308.89 | 59853385.78 | 226.50 | 205.89 | 205.89 | 61.41 | 0.28 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.101910E+09 | 92636328.01 | 665.97 | 12-JAN-16:03 | 605.37 | 605.37 | 7.26 | 12.69 |
February | 0.253105E+09 | 0.230073E+09 | 846.60 | 06-FEB-16:03 | 769.56 | 769.56 | 6.96 | 14.11 |
March | 0.729355E+09 | 0.662984E+09 | 1146.15 | 10-MAR-19:03 | 1041.85 | 1041.85 | 6.73 | 16.10 |
April | 0.137959E+10 | 0.125405E+10 | 1942.54 | 19-APR-18:03 | 1765.76 | 1765.76 | 6.73 | 20.14 |
May | 0.212508E+10 | 0.193170E+10 | 2599.41 | 17-MAY-18:03 | 2362.87 | 2362.87 | 6.73 | 22.72 |
June | 0.262527E+10 | 0.238637E+10 | 3287.41 | 22-JUN-18:03 | 2988.26 | 2988.26 | 6.73 | 25.01 |
July | 0.325677E+10 | 0.296041E+10 | 3496.33 | 01-JUL-18:03 | 3178.16 | 3178.16 | 6.73 | 25.64 |
August | 0.326302E+10 | 0.296609E+10 | 3955.37 | 28-AUG-18:02 | 3595.43 | 3595.43 | 6.73 | 26.95 |
September | 0.249703E+10 | 0.226980E+10 | 3425.08 | 14-SEP-18:03 | 3113.40 | 3113.40 | 6.73 | 25.43 |
October | 0.123288E+10 | 0.112069E+10 | 1688.44 | 12-OCT-20:00 | 1534.79 | 1534.79 | 7.15 | 18.99 |
November | 0.488467E+09 | 0.444017E+09 | 894.62 | 01-NOV-15:01 | 813.21 | 813.21 | 6.73 | 14.45 |
December | 0.160488E+09 | 0.145883E+09 | 752.72 | 01-DEC-16:03 | 684.22 | 684.22 | 7.41 | 13.40 |
Annual Sum or Average | 0.181130E+11 | 0.164647E+11 | ||||||
Minimum of Months | 0.101910E+09 | 92636328.01 | 665.97 | 605.37 | 605.37 | 6.73 | 12.69 | |
Maximum of Months | 0.326302E+10 | 0.296609E+10 | 3955.37 | 3595.43 | 3595.43 | 7.41 | 26.95 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.119371E+11 | 0.108509E+11 | 4747.70 | 01-JAN-00:20 | 4315.66 | 4315.66 | 8.40 | 33.61 |
February | 0.114322E+11 | 0.103919E+11 | 4747.70 | 01-FEB-00:03 | 4315.66 | 4315.66 | 8.46 | 33.61 |
March | 0.127162E+11 | 0.115591E+11 | 4747.70 | 01-MAR-00:03 | 4315.66 | 4315.66 | 8.96 | 33.61 |
April | 0.123060E+11 | 0.111862E+11 | 4747.70 | 01-APR-00:10 | 4315.66 | 4315.66 | 8.72 | 33.61 |
May | 0.127162E+11 | 0.115591E+11 | 4747.70 | 01-MAY-00:05 | 4315.66 | 4315.66 | 8.75 | 33.61 |
June | 0.123060E+11 | 0.111862E+11 | 4747.70 | 01-JUN-00:05 | 4315.66 | 4315.66 | 9.28 | 33.61 |
July | 0.127162E+11 | 0.115591E+11 | 4747.70 | 01-JUL-00:10 | 4315.66 | 4315.66 | 9.86 | 33.61 |
August | 0.127162E+11 | 0.115591E+11 | 4747.70 | 01-AUG-00:05 | 4315.66 | 4315.66 | 10.08 | 33.61 |
September | 0.123060E+11 | 0.111862E+11 | 4747.70 | 01-SEP-00:05 | 4315.66 | 4315.66 | 10.06 | 33.61 |
October | 0.127162E+11 | 0.115591E+11 | 4747.70 | 01-OCT-00:10 | 4315.66 | 4315.66 | 9.21 | 33.61 |
November | 0.123060E+11 | 0.111862E+11 | 4747.70 | 01-NOV-00:05 | 4315.66 | 4315.66 | 9.01 | 33.61 |
December | 0.124000E+11 | 0.112716E+11 | 4747.70 | 01-DEC-00:03 | 4315.66 | 4315.66 | 8.61 | 33.61 |
Annual Sum or Average | 0.148575E+12 | 0.135054E+12 | ||||||
Minimum of Months | 0.114322E+11 | 0.103919E+11 | 4747.70 | 4315.66 | 4315.66 | 8.40 | 33.61 | |
Maximum of Months | 0.127162E+11 | 0.115591E+11 | 4747.70 | 4315.66 | 4315.66 | 10.08 | 33.61 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 51.20 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 51.64 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 51.99 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 54.72 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 55.15 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 55.70 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 56.15 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 56.06 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 55.76 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 54.83 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 54.63 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 52.10 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 51.20 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 56.15 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 54.27 | 79.76 | 2485.61 | 47473.67 | 02-JAN-09:03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 53.68 | 79.44 | 610.31 | 31891.98 | 02-FEB-09:05 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 58.54 | 58.54 | 41.28 | 18714.46 | 16-MAR-08:54 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.50 | 52.50 | 20.83 | 14123.89 | 12-APR-08:35 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 54.26 | 54.26 | 13.25 | 12190.60 | 29-MAY-08:07 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 54.27 | 54.27 | 14.59 | 11188.98 | 27-JUN-18:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 55.58 | 55.58 | 15.99 | 11296.22 | 26-JUL-08:05 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 55.47 | 55.47 | 17.36 | 11100.08 | 23-AUG-18:07 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 55.85 | 55.85 | 31.02 | 14732.08 | 09-SEP-15:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 54.26 | 54.26 | 35.59 | 21462.73 | 30-OCT-08:54 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 52.14 | 52.14 | 86.49 | 23401.07 | 14-NOV-09:54 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 57.59 | 57.59 | 1284.44 | 33477.96 | 21-DEC-09:04 |
Annual Sum or Average | 0.00 | 390.07 | ||||||
Minimum of Months | 0.00 | 0.00 | 52.14 | 52.14 | 13.25 | 11100.08 | ||
Maximum of Months | 0.00 | 0.00 | 58.54 | 79.76 | 2485.61 | 47473.67 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 46879.86 | 312821.22 | 12-JAN-16:03 | 9.46 | 7.24 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 96775.93 | 360409.49 | 22-FEB-16:03 | 9.31 | 6.75 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 191773.04 | 519626.46 | 10-MAR-19:03 | 10.39 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 302838.05 | 571965.15 | 26-APR-18:05 | 10.76 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 401008.91 | 678175.61 | 17-MAY-18:03 | 11.52 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 463340.91 | 747575.72 | 22-JUN-18:03 | 12.01 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 514421.03 | 778732.26 | 01-JUL-18:03 | 12.23 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 515395.70 | 818732.12 | 28-AUG-18:02 | 12.52 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 462167.66 | 786417.95 | 14-SEP-18:03 | 12.29 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 293668.59 | 594061.04 | 12-OCT-21:53 | 11.46 | 7.24 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 149596.86 | 410665.82 | 04-NOV-18:03 | 9.81 | 6.89 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 60746.43 | 363936.68 | 01-DEC-16:01 | 9.97 | 7.39 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 292571.86 | 0.00 | ||||||
Minimum of Months | 46879.86 | 312821.22 | 9.31 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 515395.70 | 818732.12 | 12.52 | 7.39 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 51.20 | 59.99 | 21322.76 | 44575.16 | 17-JAN-07:30 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 51.64 | 60.00 | 20876.07 | 44302.25 | 01-FEB-07:30 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 51.99 | 59.97 | 19540.27 | 42406.81 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 54.72 | 59.97 | 17574.43 | 38400.38 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 55.15 | 60.00 | 15567.16 | 34414.58 | 01-MAY-06:40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 55.70 | 59.98 | 14046.78 | 30511.23 | 01-JUN-06:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.15 | 59.99 | 13408.12 | 28145.30 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 56.06 | 60.00 | 13873.31 | 30036.82 | 31-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 55.76 | 59.98 | 15258.82 | 33507.14 | 29-SEP-06:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 54.83 | 59.97 | 17216.07 | 38029.88 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 54.63 | 59.99 | 19220.25 | 41831.56 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 52.10 | 60.00 | 20721.89 | 44110.48 | 29-DEC-07:30 |
Annual Sum or Average | 0.00 | 17366.23 | ||||||
Minimum of Months | 0.00 | 0.00 | 51.20 | 59.97 | 13408.12 | 28145.30 | ||
Maximum of Months | 0.00 | 0.00 | 56.15 | 60.00 | 21322.76 | 44575.16 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.222612E+10 | 0.00 | 0.688318E+11 | 0.339850E+11 | 0.00 | 0.00 |
February | 0.481941E+09 | 0.00 | 0.147738E+12 | 0.316605E+11 | 0.00 | 0.00 |
March | 55964.16 | 0.00 | 0.344814E+12 | 0.378563E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.541718E+12 | 0.404519E+11 | 0.00 | 0.00 |
May | 1111.19 | 0.00 | 0.773464E+12 | 0.451866E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.898044E+12 | 0.446221E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.106423E+13 | 0.464325E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.108202E+13 | 0.465196E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.931283E+12 | 0.435118E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.557453E+12 | 0.425059E+11 | 0.00 | 0.00 |
November | 51129815.66 | 0.00 | 0.244638E+12 | 0.372796E+11 | 0.00 | 0.00 |
December | 0.107696E+10 | 0.00 | 0.903586E+11 | 0.351662E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.383621E+10 | 0.00 | 0.674460E+13 | 0.485178E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.688318E+11 | 0.316605E+11 | 0.00 | 0.00 |
Maximum of Months | 0.222612E+10 | 0.00 | 0.108202E+13 | 0.465196E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 3228.06 | 0.00 | 0.415393E+10 | 0.271000E+10 | 0.00 | 0.00 |
February | 5071.31 | 0.00 | 0.991351E+10 | 0.244774E+10 | 0.00 | 0.00 |
March | 8496.72 | 0.00 | 0.260363E+11 | 0.271000E+10 | 0.00 | 0.00 |
April | 6512.94 | 0.00 | 0.369569E+11 | 0.262258E+10 | 0.00 | 0.00 |
May | 8469.26 | 0.00 | 0.495726E+11 | 0.271000E+10 | 0.00 | 0.00 |
June | 10731.15 | 0.00 | 0.593590E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 10168.48 | 0.00 | 0.722065E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 9958.85 | 0.00 | 0.727658E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 12473.28 | 0.00 | 0.630464E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 10011.20 | 0.00 | 0.411362E+11 | 0.271000E+10 | 0.00 | 0.00 |
November | 8022.99 | 0.00 | 0.156078E+11 | 0.262258E+10 | 0.00 | 0.00 |
December | 2999.34 | 0.00 | 0.545463E+10 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 96143.59 | 0.00 | 0.456210E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 2999.34 | 0.00 | 0.415393E+10 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 12473.28 | 0.00 | 0.727658E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.339850E+11 | 0.688318E+11 | 0.222612E+10 | 0.102977E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.316605E+11 | 0.147738E+12 | 0.481941E+09 | 0.321669E+11 | 0.363040E+09 | 0.00 | 0.00 | 0.00 |
March | 0.378563E+11 | 0.344814E+12 | 55964.16 | 0.733640E+10 | 0.183239E+11 | 0.00 | 0.00 | 0.00 |
April | 0.404519E+11 | 0.541718E+12 | 0.00 | 0.118763E+11 | 0.935271E+11 | 0.00 | 0.00 | 0.00 |
May | 0.451866E+11 | 0.773464E+12 | 1111.19 | 0.134339E+10 | 0.273033E+12 | 0.00 | 0.00 | 0.00 |
June | 0.446221E+11 | 0.898044E+12 | 0.00 | 0.00 | 0.409641E+12 | 0.00 | 0.00 | 0.00 |
July | 0.464325E+11 | 0.106423E+13 | 0.00 | 0.00 | 0.541752E+12 | 0.00 | 0.00 | 0.00 |
August | 0.465196E+11 | 0.108202E+13 | 0.00 | 0.00 | 0.551950E+12 | 0.00 | 0.00 | 0.00 |
September | 0.435118E+11 | 0.931283E+12 | 0.00 | 0.00 | 0.429137E+12 | 0.00 | 0.00 | 0.00 |
October | 0.425059E+11 | 0.557453E+12 | 0.00 | 0.102816E+10 | 0.728234E+11 | 0.00 | 0.00 | 0.00 |
November | 0.372796E+11 | 0.244638E+12 | 51129815.66 | 0.948808E+10 | 0.515157E+10 | 0.00 | 0.00 | 0.00 |
December | 0.351662E+11 | 0.903586E+11 | 0.107696E+10 | 0.700927E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.485178E+12 | 0.674460E+13 | 0.383621E+10 | 0.236309E+12 | 0.239570E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.316605E+11 | 0.688318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.465196E+11 | 0.108202E+13 | 0.222612E+10 | 0.102977E+12 | 0.551950E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.415393E+10 | 3228.06 | 0.135534E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.991351E+10 | 5071.31 | 0.508782E+10 | 0.102857E+09 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.260363E+11 | 8496.72 | 0.368391E+09 | 0.464157E+10 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.369569E+11 | 6512.94 | 93841748.57 | 0.189676E+11 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.495726E+11 | 8469.26 | 0.00 | 0.438920E+11 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.593590E+11 | 10731.15 | 0.00 | 0.592019E+11 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.722065E+11 | 10168.48 | 0.00 | 0.744980E+11 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.727658E+11 | 9958.85 | 0.00 | 0.732561E+11 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.630464E+11 | 12473.28 | 0.00 | 0.584460E+11 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.411362E+11 | 10011.20 | 10649850.51 | 0.156342E+11 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.156078E+11 | 8022.99 | 0.157128E+10 | 0.129674E+10 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.545463E+10 | 2999.34 | 0.106927E+11 | 295124.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.456210E+12 | 96143.59 | 0.313781E+11 | 0.349937E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.415393E+10 | 2999.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.727658E+11 | 12473.28 | 0.135534E+11 | 0.744980E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.339850E+11 | 0.222612E+10 | 0.688318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.316605E+11 | 0.481941E+09 | 0.147738E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.378563E+11 | 55964.16 | 0.344814E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.404519E+11 | 0.00 | 0.541718E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.451866E+11 | 1111.19 | 0.773464E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.446221E+11 | 0.00 | 0.898044E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.464325E+11 | 0.00 | 0.106423E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.465196E+11 | 0.00 | 0.108202E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.435118E+11 | 0.00 | 0.931283E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.425059E+11 | 0.00 | 0.557453E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.372796E+11 | 51129815.66 | 0.244638E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.351662E+11 | 0.107696E+10 | 0.903586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.485178E+12 | 0.383621E+10 | 0.674460E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.316605E+11 | 0.00 | 0.688318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.465196E+11 | 0.222612E+10 | 0.108202E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 3228.06 | 0.415393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 5071.31 | 0.991351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 8496.72 | 0.260363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 6512.94 | 0.369569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 8469.26 | 0.495726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 10731.15 | 0.593590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 10168.48 | 0.722065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 9958.85 | 0.727658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 12473.28 | 0.630464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 10011.20 | 0.411362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 8022.99 | 0.156078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 2999.34 | 0.545463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 96143.59 | 0.456210E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 2999.34 | 0.415393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 12473.28 | 0.727658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.750469E+10 | 0.00 | 0.00 | 32920822.46 | 0.00 | 0.00 | 0.310886E+11 | 0.00 | 0.86 |
February | 0.216757E+11 | 0.00 | 0.00 | 3407040.02 | 2484905.41 | 0.00 | 0.514881E+10 | 0.00 | 0.82 |
March | 0.159623E+11 | 0.00 | 0.00 | 13947.64 | 0.770257E+09 | 0.00 | 69100936.09 | 0.00 | 0.78 |
April | 0.359068E+10 | 0.00 | 0.00 | 0.00 | 0.451099E+10 | 0.00 | 0.00 | 0.00 | 0.73 |
May | 0.277474E+09 | 0.00 | 0.00 | 0.00 | 0.170201E+11 | 0.00 | 0.00 | 0.00 | 0.69 |
June | 774074.47 | 0.123556E+11 | 0.00 | 72883.22 | 0.157138E+11 | 0.00 | 4510109.95 | 0.00 | 0.69 |
July | 0.00 | 0.433302E+11 | 0.00 | 0.00 | 0.200031E+10 | 0.00 | 0.00 | 0.00 | 0.77 |
August | 0.00 | 0.518309E+11 | 0.00 | 0.00 | 26847181.55 | 0.00 | 0.00 | 0.00 | 0.88 |
September | 0.00 | 0.406548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 |
October | 0.00 | 0.724915E+10 | 0.00 | 44209227.26 | 5638769.23 | 0.00 | 0.752752E+10 | 0.00 | 0.92 |
November | 10329113.30 | 98191401.49 | 0.00 | 85630871.88 | 1778159.98 | 0.00 | 0.288031E+11 | 0.00 | 0.94 |
December | 0.361564E+09 | 0.00 | 0.00 | 71159504.38 | 0.00 | 0.00 | 0.413790E+11 | 0.00 | 0.94 |
Annual Sum or Average | 0.493835E+11 | 0.155519E+12 | 0.00 | 0.237414E+09 | 0.400522E+11 | 0.00 | 0.114021E+12 | 0.00 | 0.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 |
Maximum of Months | 0.216757E+11 | 0.518309E+11 | 0.00 | 85630871.88 | 0.170201E+11 | 0.00 | 0.413790E+11 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.520404E+10 | 0.00 | 0.00 | 639462.14 | 0.00 | 0.00 | 0.303434E+09 | 0.00 | 2.23 |
February | 0.366552E+10 | 312260.42 | 0.00 | 1476144.00 | 116362.95 | 0.00 | 0.306488E+09 | 0.00 | 2.22 |
March | 0.195324E+10 | 0.128849E+09 | 0.00 | 2062302.81 | 6774356.19 | 0.00 | 0.421107E+09 | 0.00 | 2.19 |
April | 0.255958E+09 | 0.774435E+09 | 0.00 | 1786457.95 | 32993119.46 | 0.00 | 0.278044E+09 | 0.00 | 2.20 |
May | 632203.37 | 0.281203E+10 | 0.00 | 680348.02 | 97535245.06 | 0.00 | 40549848.73 | 0.00 | 2.13 |
June | 0.00 | 0.444860E+10 | 0.00 | 44870.27 | 0.298628E+09 | 0.00 | 882393.72 | 0.00 | 2.10 |
July | 0.00 | 0.631674E+10 | 0.00 | 0.00 | 0.281020E+09 | 0.00 | 0.00 | 0.00 | 2.01 |
August | 0.00 | 0.633410E+10 | 0.00 | 0.00 | 0.392927E+09 | 0.00 | 0.00 | 0.00 | 2.02 |
September | 0.00 | 0.411867E+10 | 0.00 | 0.00 | 0.115493E+10 | 0.00 | 0.00 | 0.00 | 2.16 |
October | 0.614700E+09 | 0.894486E+09 | 0.00 | 1821367.37 | 0.166957E+09 | 0.00 | 0.243986E+09 | 0.00 | 2.34 |
November | 0.272274E+10 | 18702027.34 | 0.00 | 4311722.58 | 525294.03 | 0.00 | 0.717597E+09 | 0.00 | 2.36 |
December | 0.495884E+10 | 0.00 | 0.00 | 1111355.43 | 0.00 | 0.00 | 0.355484E+09 | 0.00 | 2.23 |
Annual Sum or Average | 0.193757E+11 | 0.258469E+11 | 0.00 | 13934030.56 | 0.243240E+10 | 0.00 | 0.266757E+10 | 0.00 | 2.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.01 |
Maximum of Months | 0.520404E+10 | 0.633410E+10 | 0.00 | 4311722.58 | 0.115493E+10 | 0.00 | 0.717597E+09 | 0.00 | 2.36 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.333297E+10 | 0.00 | 0.00 | 272764.06 | 0.00 | 0.00 | 0.575470E+09 | 0.00 | 1.37 |
February | 0.196691E+10 | 0.00 | 0.00 | 875684.71 | 260990.89 | 0.00 | 0.855110E+09 | 0.00 | 1.35 |
March | 0.542038E+09 | 50359019.99 | 0.00 | 2501228.61 | 33812850.27 | 0.00 | 0.117041E+10 | 0.00 | 1.32 |
April | 21880886.26 | 0.431367E+09 | 0.00 | 2780808.85 | 82213539.67 | 0.00 | 0.383150E+09 | 0.00 | 1.34 |
May | 0.00 | 0.185331E+10 | 0.00 | 732090.23 | 0.150173E+09 | 0.00 | 34578552.08 | 0.00 | 1.31 |
June | 0.00 | 0.307527E+10 | 0.00 | 37915.94 | 0.280295E+09 | 0.00 | 740877.66 | 0.00 | 1.30 |
July | 0.00 | 0.444420E+10 | 0.00 | 0.00 | 0.300756E+09 | 0.00 | 0.00 | 0.00 | 1.26 |
August | 0.00 | 0.447199E+10 | 0.00 | 0.00 | 0.411040E+09 | 0.00 | 0.00 | 0.00 | 1.28 |
September | 0.00 | 0.299627E+10 | 0.00 | 0.00 | 0.691536E+09 | 0.00 | 0.00 | 0.00 | 1.31 |
October | 49014859.84 | 0.563691E+09 | 0.00 | 2414096.33 | 0.119110E+09 | 0.00 | 0.582042E+09 | 0.00 | 1.33 |
November | 0.742824E+09 | 5864872.85 | 0.00 | 2392411.83 | 4384528.19 | 0.00 | 0.172621E+10 | 0.00 | 1.34 |
December | 0.294978E+10 | 0.00 | 0.00 | 469910.59 | 0.00 | 0.00 | 0.817774E+09 | 0.00 | 1.36 |
Annual Sum or Average | 0.960541E+10 | 0.178923E+11 | 0.00 | 12476911.15 | 0.207358E+10 | 0.00 | 0.614548E+10 | 0.00 | 1.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 |
Maximum of Months | 0.333297E+10 | 0.447199E+10 | 0.00 | 2780808.85 | 0.691536E+09 | 0.00 | 0.172621E+10 | 0.00 | 1.37 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.390152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
February | 0.280940E+10 | 0.00 | 0.00 | 0.00 | 260510.98 | 0.00 | 0.00 | 0.00 | 0.63 |
March | 0.167671E+10 | 1568068.25 | 0.00 | 13581.46 | 79183657.62 | 0.00 | 3965230.79 | 0.00 | 0.60 |
April | 0.277751E+09 | 0.194066E+09 | 0.00 | 723281.16 | 0.288353E+09 | 0.00 | 99451977.05 | 0.00 | 0.58 |
May | 150986.44 | 0.157464E+10 | 0.00 | 633538.73 | 0.351656E+09 | 0.00 | 32048777.76 | 0.00 | 0.59 |
June | 0.00 | 0.281060E+10 | 0.00 | 37597.56 | 0.510136E+09 | 0.00 | 737820.56 | 0.00 | 0.60 |
July | 0.00 | 0.442682E+10 | 0.00 | 0.00 | 0.347048E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.439709E+10 | 0.00 | 0.00 | 0.411770E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.222442E+10 | 0.00 | 0.00 | 0.128968E+10 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.558769E+09 | 0.195031E+09 | 0.00 | 167993.42 | 0.443369E+09 | 0.00 | 48802871.16 | 0.00 | 0.59 |
November | 0.241516E+10 | 0.00 | 0.00 | 0.00 | 10211050.46 | 0.00 | 0.00 | 0.00 | 0.62 |
December | 0.375975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
Annual Sum or Average | 0.153992E+11 | 0.158242E+11 | 0.00 | 1575992.34 | 0.373167E+10 | 0.00 | 0.185007E+09 | 0.00 | 0.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.390152E+10 | 0.442682E+10 | 0.00 | 723281.16 | 0.128968E+10 | 0.00 | 99451977.05 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.213358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
February | 0.153635E+10 | 0.00 | 0.00 | 0.00 | 142462.83 | 0.00 | 0.00 | 0.00 | 0.60 |
March | 0.919101E+09 | 0.00 | 0.00 | 0.00 | 44159826.26 | 0.00 | 0.00 | 0.00 | 0.57 |
April | 0.180737E+09 | 81747503.69 | 0.00 | 166031.87 | 0.177423E+09 | 0.00 | 25009751.27 | 0.00 | 0.54 |
May | 284057.89 | 0.774520E+09 | 0.00 | 306850.37 | 0.238941E+09 | 0.00 | 16229918.89 | 0.00 | 0.54 |
June | 0.00 | 0.140857E+10 | 0.00 | 19259.93 | 0.345963E+09 | 0.00 | 378987.84 | 0.00 | 0.55 |
July | 0.00 | 0.220385E+10 | 0.00 | 0.00 | 0.302742E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.213648E+10 | 0.00 | 0.00 | 0.372649E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.978929E+09 | 0.00 | 0.00 | 0.887804E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 0.328812E+09 | 54026564.78 | 0.00 | 7251.42 | 0.291324E+09 | 0.00 | 3495970.53 | 0.00 | 0.55 |
November | 0.132075E+10 | 0.00 | 0.00 | 0.00 | 5584007.15 | 0.00 | 0.00 | 0.00 | 0.58 |
December | 0.205606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
Annual Sum or Average | 0.847567E+10 | 0.763812E+10 | 0.00 | 499393.59 | 0.266673E+10 | 0.00 | 45114628.54 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.213358E+10 | 0.220385E+10 | 0.00 | 306850.37 | 0.887804E+09 | 0.00 | 25009751.27 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.183624E+09 | 0.00 | 0.00 | 97197149.73 | 0.00 | 0.00 | 0.635361E+11 | 0.00 | 21.83 |
February | 0.149414E+09 | 3646546.22 | 0.00 | 97338040.80 | 0.00 | 0.00 | 0.452821E+11 | 0.00 | 21.33 |
March | 65959822.05 | 0.129791E+10 | 0.00 | 0.101176E+09 | 4108094.26 | 0.00 | 0.264230E+11 | 0.00 | 20.46 |
April | 3795169.09 | 0.755691E+10 | 0.00 | 47893487.83 | 7809323.60 | 0.00 | 0.578377E+10 | 0.00 | 19.30 |
May | 0.00 | 0.291259E+11 | 0.00 | 6776669.50 | 13552685.91 | 0.00 | 0.413362E+09 | 0.00 | 18.11 |
June | 0.00 | 0.475320E+11 | 0.00 | 380089.19 | 25547358.73 | 0.00 | 8381958.75 | 0.00 | 17.84 |
July | 0.00 | 0.682664E+11 | 0.00 | 0.00 | 12416510.02 | 0.00 | 0.00 | 0.00 | 17.78 |
August | 0.00 | 0.713871E+11 | 0.00 | 0.00 | 12044548.85 | 0.00 | 0.00 | 0.00 | 18.33 |
September | 0.00 | 0.547369E+11 | 0.00 | 0.00 | 6502110.43 | 0.00 | 0.00 | 0.00 | 19.05 |
October | 17788438.18 | 0.104423E+11 | 0.00 | 48500755.33 | 5156162.42 | 0.00 | 0.922993E+10 | 0.00 | 19.74 |
November | 0.116787E+09 | 0.148660E+09 | 0.00 | 0.109429E+09 | 1442978.41 | 0.00 | 0.389349E+11 | 0.00 | 20.79 |
December | 0.190772E+09 | 0.00 | 0.00 | 0.101064E+09 | 0.00 | 0.00 | 0.613662E+11 | 0.00 | 21.67 |
Annual Sum or Average | 0.728141E+09 | 0.290498E+12 | 0.00 | 0.609756E+09 | 88579772.63 | 0.00 | 0.250978E+12 | 0.00 | 19.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.78 |
Maximum of Months | 0.190772E+09 | 0.713871E+11 | 0.00 | 0.109429E+09 | 25547358.73 | 0.00 | 0.635361E+11 | 0.00 | 21.83 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.693127E+10 | 0.00 | 0.00 | 16582365.56 | 0.00 | 0.00 | 0.164460E+11 | 0.00 | 3.39 |
February | 0.331685E+10 | 1597878.13 | 0.00 | 24357953.47 | 106716.33 | 0.00 | 0.137155E+11 | 0.00 | 3.38 |
March | 0.135695E+10 | 0.533711E+09 | 0.00 | 29713857.84 | 10110640.43 | 0.00 | 0.915188E+10 | 0.00 | 3.37 |
April | 0.116021E+09 | 0.311153E+10 | 0.00 | 16767130.17 | 85692668.83 | 0.00 | 0.239753E+10 | 0.00 | 3.39 |
May | 463449.17 | 0.117091E+11 | 0.00 | 4227332.10 | 0.340361E+09 | 0.00 | 0.205009E+09 | 0.00 | 3.27 |
June | 0.00 | 0.194264E+11 | 0.00 | 224022.75 | 0.621361E+09 | 0.00 | 4353728.76 | 0.00 | 3.22 |
July | 0.00 | 0.277536E+11 | 0.00 | 0.00 | 0.867268E+09 | 0.00 | 0.00 | 0.00 | 3.17 |
August | 0.00 | 0.284625E+11 | 0.00 | 0.00 | 0.107479E+10 | 0.00 | 0.00 | 0.00 | 3.22 |
September | 0.00 | 0.214995E+11 | 0.00 | 0.00 | 0.129453E+10 | 0.00 | 0.00 | 0.00 | 3.37 |
October | 0.214149E+09 | 0.418213E+10 | 0.00 | 19146047.88 | 0.227483E+09 | 0.00 | 0.373708E+10 | 0.00 | 3.56 |
November | 0.106215E+10 | 73937053.90 | 0.00 | 40403596.90 | 0.00 | 0.00 | 0.140824E+11 | 0.00 | 3.55 |
December | 0.454275E+10 | 0.00 | 0.00 | 21697551.59 | 0.00 | 0.00 | 0.180425E+11 | 0.00 | 3.40 |
Annual Sum or Average | 0.175406E+11 | 0.116754E+12 | 0.00 | 0.173120E+09 | 0.452170E+10 | 0.00 | 0.777823E+11 | 0.00 | 3.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 |
Maximum of Months | 0.693127E+10 | 0.284625E+11 | 0.00 | 40403596.90 | 0.129453E+10 | 0.00 | 0.180425E+11 | 0.00 | 3.56 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.346206E+11 | 0.00 | 0.00 | 36553622.43 | 0.00 | 0.00 | 0.446068E+11 | 0.00 | 1.65 |
February | 0.150259E+11 | 1900739.78 | 0.00 | 55916452.31 | 3351665.66 | 0.00 | 0.429861E+11 | 0.00 | 1.64 |
March | 0.449247E+10 | 0.146804E+10 | 0.00 | 84622482.94 | 0.238927E+09 | 0.00 | 0.316189E+11 | 0.00 | 1.63 |
April | 0.265100E+09 | 0.917750E+10 | 0.00 | 61003997.91 | 0.116848E+10 | 0.00 | 0.847412E+10 | 0.00 | 1.64 |
May | 0.00 | 0.381305E+11 | 0.00 | 15124070.23 | 0.252769E+10 | 0.00 | 0.721984E+09 | 0.00 | 1.60 |
June | 0.00 | 0.647925E+11 | 0.00 | 783926.41 | 0.360961E+10 | 0.00 | 15237341.50 | 0.00 | 1.59 |
July | 0.00 | 0.944599E+11 | 0.00 | 0.00 | 0.409965E+10 | 0.00 | 0.00 | 0.00 | 1.57 |
August | 0.00 | 0.969870E+11 | 0.00 | 0.00 | 0.493035E+10 | 0.00 | 0.00 | 0.00 | 1.61 |
September | 0.00 | 0.684850E+11 | 0.00 | 0.00 | 0.857999E+10 | 0.00 | 0.00 | 0.00 | 1.64 |
October | 0.341146E+09 | 0.129984E+11 | 0.00 | 63951116.46 | 0.119400E+10 | 0.00 | 0.134939E+11 | 0.00 | 1.67 |
November | 0.343704E+10 | 0.194762E+09 | 0.00 | 0.100574E+09 | 12483661.96 | 0.00 | 0.490103E+11 | 0.00 | 1.66 |
December | 0.254628E+11 | 0.00 | 0.00 | 50129095.31 | 0.00 | 0.00 | 0.514301E+11 | 0.00 | 1.65 |
Annual Sum or Average | 0.836451E+11 | 0.386695E+12 | 0.00 | 0.468658E+09 | 0.263645E+11 | 0.00 | 0.242357E+12 | 0.00 | 1.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.57 |
Maximum of Months | 0.346206E+11 | 0.969870E+11 | 0.00 | 0.100574E+09 | 0.857999E+10 | 0.00 | 0.514301E+11 | 0.00 | 1.67 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 43637941.13 | 0.00 | 0.00 | 5372646.85 | 0.00 | 0.444923E+09 | 0.863790E+09 | 0.00 | 0.36 |
February | 8289740.39 | 3370372.93 | 11672.77 | 8840398.55 | 0.00 | 89002506.47 | 0.826421E+09 | 1911.68 | 0.36 |
March | 0.00 | 0.118934E+09 | 52347.86 | 9019526.24 | 0.00 | 1045933.63 | 0.398377E+09 | 4423.49 | 0.36 |
April | 0.00 | 0.400618E+09 | 292155.71 | 3431160.10 | 0.00 | 95585.77 | 33959704.79 | 12687.40 | 0.36 |
May | 0.00 | 0.106556E+10 | 480847.64 | 0.00 | 43097.29 | 0.00 | 0.00 | 6123.51 | 0.36 |
June | 0.00 | 0.158601E+10 | 897784.86 | 0.00 | 0.00 | 0.00 | 0.00 | 9799.23 | 0.36 |
July | 0.00 | 0.218708E+10 | 1306570.73 | 0.00 | 0.00 | 0.00 | 0.00 | 12958.48 | 0.36 |
August | 0.00 | 0.221007E+10 | 1964656.55 | 0.00 | 0.00 | 0.00 | 0.00 | 18729.67 | 0.36 |
September | 0.00 | 0.174521E+10 | 2493651.38 | 0.00 | 0.00 | 0.00 | 0.00 | 47897.07 | 0.36 |
October | 0.00 | 0.556400E+09 | 315706.82 | 2067535.63 | 0.00 | 293897.72 | 56176304.68 | 19282.73 | 0.36 |
November | 0.00 | 27505304.82 | 54384.49 | 10822656.62 | 0.00 | 1682301.79 | 0.701542E+09 | 3647.35 | 0.36 |
December | 22689219.66 | 3478.52 | 0.00 | 7226479.07 | 0.00 | 0.155774E+09 | 0.113894E+10 | 0.00 | 0.35 |
Annual Sum or Average | 74616901.18 | 0.990076E+10 | 7869778.81 | 46780403.05 | 43097.29 | 0.692817E+09 | 0.401921E+10 | 137460.60 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 43637941.13 | 0.221007E+10 | 2493651.38 | 10822656.62 | 43097.29 | 0.444923E+09 | 0.113894E+10 | 47897.07 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.202759E+09 | 0.00 | 0.00 | 1953648.14 | 0.00 | 0.756686E+09 | 0.396165E+09 | 0.00 | 0.36 |
February | 0.198206E+09 | 1487269.62 | 2379.56 | 4038707.24 | 1893590.66 | 0.174350E+09 | 0.555850E+09 | 321.06 | 0.36 |
March | 0.127494E+09 | 0.106482E+09 | 112824.19 | 5771354.67 | 12369059.72 | 810656.77 | 0.274318E+09 | 13170.43 | 0.36 |
April | 14983628.06 | 0.390918E+09 | 258851.20 | 2523797.92 | 9688701.10 | 35010.82 | 19939621.77 | 10188.21 | 0.36 |
May | 0.00 | 0.106358E+10 | 472070.68 | 0.00 | 1909219.10 | 0.00 | 0.00 | 4572.50 | 0.36 |
June | 0.00 | 0.158320E+10 | 895566.70 | 0.00 | 2628492.52 | 0.00 | 0.00 | 9763.58 | 0.36 |
July | 0.00 | 0.218682E+10 | 1306667.62 | 0.00 | 0.00 | 0.00 | 0.00 | 12706.99 | 0.36 |
August | 0.00 | 0.220981E+10 | 1961932.58 | 0.00 | 0.00 | 0.00 | 0.00 | 21221.26 | 0.36 |
September | 0.00 | 0.174032E+10 | 2961367.28 | 0.00 | 4204558.03 | 0.00 | 0.00 | 57001.52 | 0.36 |
October | 33149829.47 | 0.478099E+09 | 492524.99 | 869610.62 | 78048814.82 | 8210.13 | 24503229.25 | 30048.13 | 0.36 |
November | 0.186282E+09 | 21678034.21 | 31198.25 | 5507358.88 | 5842397.75 | 2014097.76 | 0.520161E+09 | 8477.00 | 0.36 |
December | 0.195395E+09 | 3478.11 | 0.00 | 2602019.92 | 0.00 | 0.448757E+09 | 0.677722E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.958269E+09 | 0.978241E+10 | 8495383.04 | 23266497.38 | 0.116585E+09 | 0.138266E+10 | 0.246866E+10 | 167470.68 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.202759E+09 | 0.220981E+10 | 2961367.28 | 5771354.67 | 78048814.82 | 0.756686E+09 | 0.677722E+09 | 57001.52 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.150369E+09 | 0.00 | 0.00 | 3423964.87 | 0.00 | 0.00 | 0.106524E+10 | 0.00 | 0.02 |
February | 70274849.85 | 9610017.18 | 0.00 | 3584075.40 | 0.00 | 0.00 | 0.504509E+09 | 0.00 | 0.02 |
March | 0.00 | 0.126036E+09 | 0.00 | 2048145.80 | 0.00 | 0.00 | 0.209540E+09 | 0.00 | 0.02 |
April | 0.00 | 0.254473E+09 | 0.00 | 1226022.62 | 0.00 | 0.00 | 24536380.89 | 0.00 | 0.02 |
May | 0.00 | 0.718191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.109137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
July | 0.00 | 0.157361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
August | 0.00 | 0.166124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
September | 0.00 | 0.122772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
October | 0.00 | 0.393175E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
November | 0.00 | 60780194.80 | 0.00 | 3441078.75 | 0.00 | 0.00 | 0.211724E+09 | 0.00 | 0.02 |
December | 4226595.43 | 0.00 | 0.00 | 4139265.46 | 0.00 | 0.00 | 0.101805E+10 | 0.00 | 0.02 |
Annual Sum or Average | 0.224870E+09 | 0.711620E+10 | 0.00 | 17862552.90 | 0.00 | 0.00 | 0.303359E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.150369E+09 | 0.166124E+10 | 0.00 | 4139265.46 | 0.00 | 0.00 | 0.106524E+10 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.275031E+10 | 0.00 | 0.00 | 46754748.96 | 0.00 | 0.231529E+09 | 0.153859E+11 | 0.00 | 0.40 |
February | 0.272133E+10 | 18905423.91 | 456338.35 | 68776057.74 | 26511669.70 | 57875980.40 | 0.980006E+10 | 22541.87 | 0.40 |
March | 0.178795E+10 | 0.141669E+10 | 5319510.43 | 66463345.92 | 0.191680E+09 | 8278029.63 | 0.367693E+10 | 160634.10 | 0.41 |
April | 0.207632E+09 | 0.530029E+10 | 5515617.36 | 22555449.35 | 0.131765E+09 | 676034.00 | 0.277558E+09 | 70414.74 | 0.41 |
May | 0.00 | 0.144126E+11 | 20616046.23 | 0.00 | 25897411.80 | 0.00 | 0.00 | 57201.33 | 0.41 |
June | 0.00 | 0.214082E+11 | 23702246.42 | 0.00 | 91100772.75 | 0.00 | 0.00 | 53750.10 | 0.41 |
July | 0.00 | 0.296213E+11 | 30842672.76 | 0.00 | 28678886.76 | 0.00 | 0.00 | 63273.78 | 0.41 |
August | 0.00 | 0.299211E+11 | 29625587.50 | 0.00 | 50931772.87 | 0.00 | 0.00 | 61029.54 | 0.41 |
September | 0.00 | 0.233745E+11 | 48637138.76 | 0.00 | 0.281067E+09 | 0.00 | 0.00 | 179617.68 | 0.41 |
October | 0.449658E+09 | 0.641657E+10 | 15829166.03 | 9901149.24 | 0.111821E+10 | 47075.04 | 0.334330E+09 | 293377.91 | 0.41 |
November | 0.259625E+10 | 0.276242E+09 | 1401853.71 | 72068946.76 | 96021804.38 | 12403631.23 | 0.700377E+10 | 170920.46 | 0.41 |
December | 0.265042E+10 | 47178.47 | 0.00 | 55711929.81 | 0.00 | 0.115483E+09 | 0.151441E+11 | 0.00 | 0.40 |
Annual Sum or Average | 0.131635E+11 | 0.132166E+12 | 0.181946E+09 | 0.342232E+09 | 0.204186E+10 | 0.426293E+09 | 0.516227E+11 | 1132761.51 | 0.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.275031E+10 | 0.299211E+11 | 48637138.76 | 72068946.76 | 0.111821E+10 | 0.231529E+09 | 0.153859E+11 | 293377.91 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 33497466.21 | 0.00 | 0.00 | 5473692.11 | 0.00 | 0.435171E+09 | 0.883581E+09 | 0.00 | 0.36 |
February | 6577487.40 | 3370372.93 | 13148.43 | 9573460.68 | 0.00 | 94188980.66 | 0.822213E+09 | 436.01 | 0.36 |
March | 0.00 | 0.118991E+09 | 0.00 | 9706123.34 | 0.00 | 572111.65 | 0.398164E+09 | 0.00 | 0.36 |
April | 0.00 | 0.400923E+09 | 0.00 | 3595534.80 | 0.00 | 0.00 | 33890915.86 | 0.00 | 0.36 |
May | 0.00 | 0.106609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.158692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
July | 0.00 | 0.218831E+10 | 90065.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1115.19 | 0.36 |
August | 0.00 | 0.221206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
September | 0.00 | 0.174700E+10 | 746842.65 | 0.00 | 0.00 | 0.00 | 0.00 | 6714.47 | 0.36 |
October | 0.00 | 0.556575E+09 | 156686.96 | 2263365.28 | 0.00 | 0.00 | 56274372.74 | 3354.29 | 0.36 |
November | 0.00 | 27552770.34 | 10407.17 | 11545891.88 | 0.00 | 485799.23 | 0.702016E+09 | 159.14 | 0.36 |
December | 21543729.26 | 3478.52 | 0.00 | 7542097.70 | 0.00 | 0.172872E+09 | 0.112267E+10 | 0.00 | 0.35 |
Annual Sum or Average | 61618682.88 | 0.990779E+10 | 1017151.11 | 49700165.80 | 0.00 | 0.703290E+09 | 0.401881E+10 | 11779.10 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 33497466.21 | 0.221206E+10 | 746842.65 | 11545891.88 | 0.00 | 0.435171E+09 | 0.112267E+10 | 6714.47 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.202759E+09 | 0.00 | 0.00 | 1778953.53 | 0.00 | 0.659363E+09 | 0.493663E+09 | 0.00 | 0.36 |
February | 0.196578E+09 | 1491007.38 | 1659.39 | 4991154.19 | 1889852.91 | 0.162957E+09 | 0.567918E+09 | 1041.23 | 0.36 |
March | 0.126748E+09 | 0.106582E+09 | 23504.53 | 6157220.17 | 12369059.72 | 738745.27 | 0.274750E+09 | 2256.92 | 0.36 |
April | 14917356.71 | 0.391197E+09 | 0.00 | 2558803.47 | 9679198.17 | 18310.27 | 19987588.13 | 0.00 | 0.36 |
May | 0.00 | 0.106406E+10 | 0.00 | 0.00 | 1909219.10 | 0.00 | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.158405E+10 | 47091.07 | 0.00 | 2628492.52 | 0.00 | 0.00 | 748.47 | 0.36 |
July | 0.00 | 0.218805E+10 | 90009.38 | 0.00 | 0.00 | 0.00 | 0.00 | 1161.02 | 0.36 |
August | 0.00 | 0.221180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
September | 0.00 | 0.174259E+10 | 745870.73 | 0.00 | 4204558.03 | 0.00 | 0.00 | 7598.10 | 0.36 |
October | 33149829.47 | 0.478414E+09 | 231521.19 | 852209.15 | 78015123.57 | 0.00 | 24528840.84 | 9302.29 | 0.36 |
November | 0.187431E+09 | 21648463.25 | 61078.09 | 5976796.52 | 5842397.75 | 1810548.02 | 0.518746E+09 | 8168.12 | 0.36 |
December | 0.195569E+09 | 3478.11 | 0.00 | 2723243.78 | 0.00 | 0.488580E+09 | 0.637604E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.957153E+09 | 0.978989E+10 | 1200734.37 | 25038380.81 | 0.116538E+09 | 0.131347E+10 | 0.253720E+10 | 30276.15 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.202759E+09 | 0.221180E+10 | 745870.73 | 6157220.17 | 78015123.57 | 0.659363E+09 | 0.637604E+09 | 9302.29 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.223252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
February | 0.160759E+11 | 0.00 | 0.00 | 0.00 | 1490689.15 | 0.00 | 0.00 | 0.00 | 0.50 |
March | 0.961720E+10 | 0.00 | 0.00 | 0.00 | 0.462075E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
April | 0.165096E+10 | 0.141223E+10 | 0.00 | 3198125.61 | 0.132432E+10 | 0.00 | 0.506247E+09 | 0.00 | 0.46 |
May | 1726499.45 | 0.825263E+10 | 0.00 | 3095969.34 | 0.243802E+10 | 0.00 | 0.170947E+09 | 0.00 | 0.45 |
June | 0.00 | 0.125819E+11 | 0.00 | 187004.18 | 0.519954E+10 | 0.00 | 3652486.30 | 0.00 | 0.45 |
July | 0.00 | 0.169812E+11 | 0.00 | 0.00 | 0.815597E+10 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.126825E+11 | 0.00 | 0.00 | 0.129098E+11 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.743032E+10 | 0.00 | 0.00 | 0.120523E+11 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 0.332363E+10 | 0.114154E+10 | 0.00 | 446188.76 | 0.248960E+10 | 0.00 | 0.153218E+09 | 0.00 | 0.46 |
November | 0.138200E+11 | 0.00 | 0.00 | 0.00 | 58429407.18 | 0.00 | 0.00 | 0.00 | 0.48 |
December | 0.215140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.883285E+11 | 0.604823E+11 | 0.00 | 6927287.89 | 0.450915E+11 | 0.00 | 0.834064E+09 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.223252E+11 | 0.169812E+11 | 0.00 | 3198125.61 | 0.129098E+11 | 0.00 | 0.506247E+09 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 10619393.61 | 0.00 | 0.00 | 1177815.05 | 0.00 | 0.175607E+09 | 0.152027E+09 | 0.00 | 0.36 |
February | 1725495.39 | 842593.23 | 2965.46 | 1980584.16 | 0.00 | 59643925.18 | 0.169788E+09 | 430.65 | 0.36 |
March | 0.00 | 29729652.50 | 16283.16 | 2043096.21 | 0.00 | 271217.05 | 99796194.38 | 1828.30 | 0.36 |
April | 0.00 | 0.100148E+09 | 77160.27 | 826992.71 | 0.00 | 28087.95 | 8516532.01 | 5212.44 | 0.36 |
May | 0.00 | 0.266390E+09 | 130967.51 | 0.00 | 0.00 | 0.00 | 0.00 | 1549.59 | 0.36 |
June | 0.00 | 0.396502E+09 | 224324.01 | 0.00 | 0.00 | 0.00 | 0.00 | 2572.01 | 0.36 |
July | 0.00 | 0.546713E+09 | 382566.51 | 0.00 | 0.00 | 0.00 | 0.00 | 4396.64 | 0.36 |
August | 0.00 | 0.552350E+09 | 655825.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7558.74 | 0.36 |
September | 0.00 | 0.436196E+09 | 727403.47 | 0.00 | 0.00 | 0.00 | 0.00 | 14131.41 | 0.36 |
October | 0.00 | 0.139061E+09 | 113586.03 | 425210.94 | 0.00 | 65327.32 | 14143896.25 | 9246.81 | 0.36 |
November | 0.00 | 6859419.03 | 29870.80 | 2295791.90 | 0.00 | 5002716.34 | 0.171213E+09 | 1544.31 | 0.36 |
December | 5726177.68 | 869.63 | 0.00 | 1499310.29 | 0.00 | 0.138593E+09 | 0.185340E+09 | 0.00 | 0.35 |
Annual Sum or Average | 18071066.68 | 0.247479E+10 | 2360952.46 | 10248801.25 | 0.00 | 0.379211E+09 | 0.800825E+09 | 48470.93 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 10619393.61 | 0.552350E+09 | 727403.47 | 2295791.90 | 0.00 | 0.175607E+09 | 0.185340E+09 | 14131.41 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 50689834.51 | 0.00 | 0.00 | 381533.96 | 0.00 | 0.232640E+09 | 55679616.04 | 0.00 | 0.36 |
February | 49410342.68 | 372751.84 | 593.06 | 816491.37 | 472463.23 | 81195587.33 | 0.101689E+09 | 82.09 | 0.36 |
March | 31818241.96 | 26614607.72 | 33723.95 | 1299662.51 | 3092264.93 | 231589.18 | 68749050.26 | 3681.98 | 0.36 |
April | 3745907.02 | 97711975.82 | 79757.04 | 622541.73 | 2422175.27 | 9293.41 | 4992772.49 | 5131.89 | 0.36 |
May | 0.00 | 0.265881E+09 | 131538.01 | 0.00 | 477304.78 | 0.00 | 0.00 | 1070.01 | 0.36 |
June | 0.00 | 0.395787E+09 | 236363.11 | 0.00 | 657123.13 | 0.00 | 0.00 | 2466.21 | 0.36 |
July | 0.00 | 0.546677E+09 | 355038.51 | 0.00 | 0.00 | 0.00 | 0.00 | 4233.01 | 0.36 |
August | 0.00 | 0.552286E+09 | 655627.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7679.02 | 0.36 |
September | 0.00 | 0.435084E+09 | 734604.94 | 0.00 | 1051139.51 | 0.00 | 0.00 | 16884.29 | 0.36 |
October | 8287457.37 | 0.119486E+09 | 160070.57 | 174851.58 | 19512203.71 | 10191.07 | 6160219.85 | 9783.91 | 0.36 |
November | 46513313.52 | 5418590.30 | 8537.15 | 1030077.76 | 1460599.44 | 16718749.46 | 0.114229E+09 | 2299.89 | 0.36 |
December | 48848767.29 | 869.53 | 0.00 | 470945.84 | 0.00 | 0.214791E+09 | 67008734.10 | 0.00 | 0.36 |
Annual Sum or Average | 0.239314E+09 | 0.244532E+10 | 2395853.58 | 4796104.75 | 29145273.99 | 0.545596E+09 | 0.418508E+09 | 53312.31 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 50689834.51 | 0.552286E+09 | 734604.94 | 1299662.51 | 19512203.71 | 0.232640E+09 | 0.114229E+09 | 16884.29 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 22785601.65 | 0.00 | 0.00 | 15500654.12 | 0.00 | 0.172617E+09 | 0.196977E+10 | 0.00 | 0.40 |
February | 5996958.18 | 5435049.53 | 0.00 | 18293505.15 | 0.00 | 54409485.36 | 0.141909E+10 | 0.00 | 0.40 |
March | 0.00 | 0.191097E+09 | 15858.28 | 14120399.09 | 0.00 | 1342346.67 | 0.640545E+09 | 1406.70 | 0.41 |
April | 0.00 | 0.643477E+09 | 430041.14 | 4757503.50 | 0.00 | 129273.88 | 55321048.32 | 24472.02 | 0.41 |
May | 0.00 | 0.171158E+10 | 676303.27 | 0.00 | 0.00 | 0.00 | 0.00 | 14313.00 | 0.41 |
June | 0.00 | 0.254746E+10 | 1308332.90 | 0.00 | 0.00 | 0.00 | 0.00 | 17799.74 | 0.41 |
July | 0.00 | 0.351306E+10 | 1757987.12 | 0.00 | 0.00 | 0.00 | 0.00 | 17582.01 | 0.41 |
August | 0.00 | 0.355043E+10 | 2385989.45 | 0.00 | 0.00 | 0.00 | 0.00 | 17361.28 | 0.41 |
September | 0.00 | 0.280524E+10 | 1851036.24 | 0.00 | 0.00 | 0.00 | 0.00 | 15224.90 | 0.41 |
October | 0.00 | 0.894074E+09 | 104605.05 | 3259642.71 | 0.00 | 238418.11 | 90520707.69 | 6936.55 | 0.41 |
November | 0.00 | 44270090.65 | 0.00 | 20947751.26 | 0.00 | 733580.38 | 0.112517E+10 | 0.00 | 0.40 |
December | 795370.28 | 5586.92 | 0.00 | 19275829.17 | 0.00 | 68204520.20 | 0.203924E+10 | 0.00 | 0.40 |
Annual Sum or Average | 29577930.11 | 0.159061E+11 | 8530153.45 | 96155285.00 | 0.00 | 0.297675E+09 | 0.733966E+10 | 115096.21 | 0.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 22785601.65 | 0.355043E+10 | 2385989.45 | 20947751.26 | 0.00 | 0.172617E+09 | 0.203924E+10 | 24472.02 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.197381E+10 | 0.00 | 0.00 | 51904520.53 | 0.00 | 0.00 | 0.387316E+11 | 0.00 | 4.31 |
February | 0.668418E+09 | 2541370.51 | 0.00 | 62298895.57 | 0.00 | 0.00 | 0.301186E+11 | 0.00 | 4.36 |
March | 0.183611E+09 | 0.887195E+09 | 0.00 | 74738246.82 | 351858.50 | 0.00 | 0.197019E+11 | 0.00 | 4.47 |
April | 2883524.08 | 0.556855E+10 | 0.00 | 42249824.96 | 118840.16 | 0.00 | 0.485920E+10 | 0.00 | 4.56 |
May | 0.00 | 0.223067E+11 | 0.00 | 8329194.06 | 0.00 | 0.00 | 0.390089E+09 | 0.00 | 4.49 |
June | 0.00 | 0.375133E+11 | 0.00 | 421827.18 | 0.00 | 0.00 | 8217268.88 | 0.00 | 4.46 |
July | 0.00 | 0.536186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.39 |
August | 0.00 | 0.549691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.45 |
September | 0.00 | 0.410600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 |
October | 36013976.00 | 0.733716E+10 | 0.00 | 39081225.15 | 27253308.24 | 0.00 | 0.722854E+10 | 0.00 | 4.42 |
November | 0.269837E+09 | 0.102217E+09 | 0.00 | 73328116.24 | 0.00 | 0.00 | 0.271821E+11 | 0.00 | 4.34 |
December | 0.132452E+10 | 0.00 | 0.00 | 56564719.07 | 0.00 | 0.00 | 0.384698E+11 | 0.00 | 4.31 |
Annual Sum or Average | 0.445910E+10 | 0.223365E+12 | 0.00 | 0.408917E+09 | 27724006.90 | 0.00 | 0.166690E+12 | 0.00 | 4.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
Maximum of Months | 0.197381E+10 | 0.549691E+11 | 0.00 | 74738246.82 | 27253308.24 | 0.00 | 0.387316E+11 | 0.00 | 4.56 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.815063E+09 | 0.00 | 0.00 | 67724907.66 | 0.00 | 0.00 | 0.434102E+11 | 0.00 | 4.65 |
February | 0.242433E+09 | 2689783.35 | 0.00 | 76663705.72 | 0.00 | 0.00 | 0.331511E+11 | 0.00 | 4.71 |
March | 61211863.13 | 0.954615E+09 | 0.00 | 85471256.04 | 0.00 | 0.00 | 0.212715E+11 | 0.00 | 4.79 |
April | 0.00 | 0.592974E+10 | 0.00 | 45783915.40 | 0.00 | 0.00 | 0.513894E+10 | 0.00 | 4.84 |
May | 0.00 | 0.236529E+11 | 0.00 | 8721980.91 | 0.00 | 0.00 | 0.407915E+09 | 0.00 | 4.75 |
June | 0.00 | 0.397275E+11 | 0.00 | 438832.96 | 0.00 | 0.00 | 8550660.33 | 0.00 | 4.72 |
July | 0.00 | 0.568060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.65 |
August | 0.00 | 0.583319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.71 |
September | 0.00 | 0.436647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.77 |
October | 15270129.83 | 0.785103E+10 | 0.00 | 43113536.79 | 0.00 | 0.00 | 0.771596E+10 | 0.00 | 4.71 |
November | 0.127091E+09 | 0.109789E+09 | 0.00 | 86253454.28 | 0.00 | 0.00 | 0.294503E+11 | 0.00 | 4.66 |
December | 0.519772E+09 | 0.00 | 0.00 | 73066231.06 | 0.00 | 0.00 | 0.427163E+11 | 0.00 | 4.65 |
Annual Sum or Average | 0.178084E+10 | 0.237031E+12 | 0.00 | 0.487238E+09 | 0.00 | 0.00 | 0.183271E+12 | 0.00 | 4.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.65 |
Maximum of Months | 0.815063E+09 | 0.583319E+11 | 0.00 | 86253454.28 | 0.00 | 0.00 | 0.434102E+11 | 0.00 | 4.84 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.112391E+09 | 0.00 | 0.00 | 0.538910E+11 | 0.00 | 19.55 |
February | 0.00 | 4564822.90 | 0.00 | 0.114238E+09 | 0.00 | 0.00 | 0.376786E+11 | 0.00 | 19.52 |
March | 0.00 | 0.142780E+10 | 0.00 | 0.113516E+09 | 0.00 | 0.00 | 0.216368E+11 | 0.00 | 19.14 |
April | 0.00 | 0.811481E+10 | 0.00 | 50906097.41 | 0.00 | 0.00 | 0.471768E+10 | 0.00 | 18.47 |
May | 0.00 | 0.298278E+11 | 0.00 | 7537921.84 | 0.00 | 0.00 | 0.338387E+09 | 0.00 | 17.63 |
June | 0.00 | 0.478185E+11 | 0.00 | 369867.54 | 0.00 | 0.00 | 7388733.26 | 0.00 | 17.37 |
July | 0.00 | 0.686139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 |
August | 0.00 | 0.714870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.69 |
September | 0.00 | 0.541919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.22 |
October | 0.00 | 0.104254E+11 | 0.00 | 51915972.44 | 0.00 | 0.00 | 0.748586E+10 | 0.00 | 18.66 |
November | 0.00 | 0.180427E+09 | 0.00 | 0.124376E+09 | 0.00 | 0.00 | 0.313514E+11 | 0.00 | 19.31 |
December | 0.00 | 0.00 | 0.00 | 0.117502E+09 | 0.00 | 0.00 | 0.515139E+11 | 0.00 | 19.58 |
Annual Sum or Average | 0.00 | 0.292092E+12 | 0.00 | 0.692753E+09 | 0.00 | 0.00 | 0.208621E+12 | 0.00 | 18.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 |
Maximum of Months | 0.00 | 0.714870E+11 | 0.00 | 0.124376E+09 | 0.00 | 0.00 | 0.538910E+11 | 0.00 | 19.58 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.134340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 |
February | 0.967356E+10 | 0.00 | 0.00 | 0.00 | 897013.41 | 0.00 | 0.00 | 0.00 | 1.12 |
March | 0.572106E+10 | 0.198067E+09 | 0.00 | 178839.47 | 84409243.51 | 0.00 | 65859022.95 | 0.00 | 1.08 |
April | 0.942905E+09 | 0.165405E+10 | 0.00 | 2350529.66 | 0.202559E+09 | 0.00 | 0.352560E+09 | 0.00 | 1.09 |
May | 3740941.18 | 0.691644E+10 | 0.00 | 1310559.22 | 0.349683E+09 | 0.00 | 96677002.99 | 0.00 | 1.12 |
June | 0.00 | 0.111683E+11 | 0.00 | 102831.90 | 0.814262E+09 | 0.00 | 2036199.20 | 0.00 | 1.12 |
July | 0.00 | 0.153749E+11 | 0.00 | 0.00 | 0.969361E+09 | 0.00 | 0.00 | 0.00 | 1.05 |
August | 0.00 | 0.144612E+11 | 0.00 | 0.00 | 0.181751E+10 | 0.00 | 0.00 | 0.00 | 1.03 |
September | 0.00 | 0.758721E+10 | 0.00 | 0.00 | 0.452217E+10 | 0.00 | 0.00 | 0.00 | 1.05 |
October | 0.205311E+10 | 0.122225E+10 | 0.00 | 241464.70 | 0.102394E+10 | 0.00 | 39063022.98 | 0.00 | 1.06 |
November | 0.831133E+10 | 12627141.43 | 0.00 | 19778.30 | 22532409.87 | 0.00 | 4723202.88 | 0.00 | 1.10 |
December | 0.129459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 |
Annual Sum or Average | 0.530856E+11 | 0.585950E+11 | 0.00 | 4204003.26 | 0.980732E+10 | 0.00 | 0.560919E+09 | 0.00 | 1.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 |
Maximum of Months | 0.134340E+11 | 0.153749E+11 | 0.00 | 2350529.66 | 0.452217E+10 | 0.00 | 0.352560E+09 | 0.00 | 1.15 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:02:47
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.142617E+12 | 0.279504E+10 | 0.115756E+12 | 0.498264E+12 | 0.185861E+12 |
February | 0.168590E+12 | 0.191936E+10 | 0.739282E+11 | 0.315769E+12 | 0.329198E+12 |
March | 0.227610E+12 | 0.919041E+09 | 0.350038E+11 | 0.142387E+12 | 0.703147E+12 |
April | 0.259822E+12 | -580242522.6 | -0.287947E+11 | -0.110785E+12 | 0.107176E+13 |
May | 0.283030E+12 | -0.247888E+10 | -0.132737E+12 | -0.486113E+12 | 0.146366E+13 |
June | 0.259564E+12 | -0.385512E+10 | -0.203279E+12 | -0.755319E+12 | 0.162783E+13 |
July | 0.218118E+12 | -0.525565E+10 | -0.277853E+12 | -0.103314E+13 | 0.183123E+13 |
August | 0.181892E+12 | -0.528605E+10 | -0.281265E+12 | -0.106264E+13 | 0.181505E+13 |
September | 0.192675E+12 | -0.402586E+10 | -0.206590E+12 | -0.824567E+12 | 0.157184E+13 |
October | 0.172508E+12 | -572791492.2 | -0.245818E+11 | -0.981731E+11 | 0.104964E+13 |
November | 0.146275E+12 | 0.152137E+10 | 0.562084E+11 | 0.249499E+12 | 0.533639E+12 |
December | 0.126570E+12 | 0.257194E+10 | 0.104108E+12 | 0.457479E+12 | 0.234594E+12 |
Annual Sum or Average | 0.237927E+13 | -0.123278E+11 | -0.770096E+12 | -0.270734E+13 | 0.124174E+14 |
Minimum of Months | 0.126570E+12 | -0.528605E+10 | -0.281265E+12 | -0.106264E+13 | 0.185861E+12 |
Maximum of Months | 0.283030E+12 | 0.279504E+10 | 0.115756E+12 | 0.498264E+12 | 0.183123E+13 |