Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2023-10-16 09:02:50
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 9497.43 | 837.13 | 837.13 |
Net Site Energy | 9497.43 | 837.13 | 837.13 |
Total Source Energy | 22150.30 | 1952.38 | 1952.38 |
Net Source Energy | 22150.30 | 1952.38 | 1952.38 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 884.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1150.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 603.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 174.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 641.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 550.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 120.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 188.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 489.84 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 43.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5691.35 | 3806.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 884.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1150.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 603.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 174.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 952.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 22.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 550.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 120.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 188.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.75 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Other | 399.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 21.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 884.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1150.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 603.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 174.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 641.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 550.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 120.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 188.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 489.84 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 43.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 203.75 | 177.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 229.36 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 501.65 | 335.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 203.75 | 177.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 229.36 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 501.65 | 335.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5691.350 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5691.350 | 100.00 |
Total On-Site and Utility Electric Sources | 5691.350 | 100.00 |
Total Electricity End Uses | 5691.350 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 566.41 | 16.27 |
Air to Air Heat Recovery for Heating | 2914.60 | 83.73 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 3481.01 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.33 |
Time Setpoint Not Met During Occupied Cooling | 114.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7904.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYSLAUNDRY HPWH TANK | SWHSYS1 HPWH TANK |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| SWHSYS1 HPWH FAN | SWHSYSLAUNDRY HPWH FAN | FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 6.6442 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 9.6995 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 9.6995 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 4.0903 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.7049 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 9.2569 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 9.0417 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 4.4132 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.4132 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.7327 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 4.4132 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8432 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8432 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.6442 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 4.0903 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.7049 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 9.2569 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 9.0417 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 4.4132 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.4132 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.7327 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 4.4132 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.8432 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.8432 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.6992 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-19:19 | 06-FEB-19:10 | - | - | - | - | - | - | - | - | - | - | 02-MAR-21:49 |
Heating | 0.00 | 201199.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 194004.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 50471.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 87982.85 | 87619.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31577.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 31960.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6619.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 38190.28 | 134072.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1344.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 463186.21 | 422891.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 201199.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 194004.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 50471.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58308.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1274.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 31960.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 6619.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3915.94 | 134072.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 431.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 671.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 959.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3644.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1911.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 551.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5473.02 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2031.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1742.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 382.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 597.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1551.32 | 1227.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 138.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 18024.51 | 4125.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 84.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 321.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 153.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 33.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 52.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 136.74 | 108.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1588.72 | 363.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 84.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 321.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 153.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 33.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 52.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 136.74 | 108.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1588.72 | 363.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.08 | 0.724871 | 0.559000 | 1.16 | 1.00 | 0.500000 | 0.000526 | 0.000070 | 1.16 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.352101 | 0.145153 | 0.559000 | 0.196825 | 0.559000 | 0.500000 | 0.002625 | 0.000032 | 0.196825 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.217343 | 0.272305 | 0.559000 | 0.121495 | 0.726148 | 0.500000 | 0.001399 | 0.000014 | 0.121495 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.183871 | 0.680660 | 0.559000 | 0.102784 | 1.00 | 0.500000 | 0.000560 | 0.000020 | 0.102784 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.098915 | 0.729984 | 0.559000 | 0.055294 | 1.00 | 0.500000 | 0.000522 | 0.000012 | 0.055294 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.26 | 0.072475 | 0.559000 | 1.82 | 0.559000 | 0.500000 | 0.020861 | 0.000103 | 1.82 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.50 | 0.095986 | 0.559000 | 0.838113 | 0.559000 | 0.500000 | 0.003969 | 0.000097 | 0.838113 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.68 | 0.213050 | 0.559000 | 2.62 | 0.568134 | 0.500000 | 0.001788 | 0.000261 | 2.62 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.24 | 0.959337 | 0.559000 | 0.691603 | 1.00 | 0.500000 | 0.000397 | 0.000118 | 0.691603 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.13 | 0.118565 | 0.559000 | 1.19 | 0.559000 | 0.500000 | 0.003213 | 0.000109 | 1.19 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.24 | 0.112957 | 0.559000 | 1.25 | 0.559000 | 0.500000 | 0.003373 | 0.000113 | 1.25 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.17 | 0.065109 | 0.559000 | 1.22 | 0.559000 | 0.500000 | 0.010525 | 0.000080 | 1.22 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.696363 | 0.450970 | 0.559000 | 0.389267 | 1.00 | 0.500000 | 0.000845 | 0.000074 | 0.389267 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 8003.05 | 0.000070 | 169.57 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3701.89 | 0.000032 | 89.24 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1549.89 | 0.000014 | 34.90 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2232.61 | 0.000020 | 55.74 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1383.48 | 0.000012 | 36.00 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11777.97 | 0.000103 | 248.53 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 11124.43 | 0.000097 | 251.92 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 29854.88 | 0.000261 | 662.74 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 6056.01 | 0.000053 | 173.03 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 6073.59 | 0.000053 | 173.53 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 34770.54 | 0.000304 | 993.44 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 35110.71 | 0.000307 | 1003.16 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 6020.24 | 0.000053 | 172.01 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 6037.84 | 0.000053 | 172.51 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 13467.55 | 0.000118 | 327.20 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1866.09 | 0.000016 | 53.32 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1871.97 | 0.000016 | 53.48 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8900.14 | 0.000078 | 254.29 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 12419.55 | 0.000109 | 272.83 |
DINING_FLR_6 VAV BOX REHEAT COIL | 12879.23 | 0.000113 | 282.59 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 9116.72 | 0.000080 | 194.37 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8453.95 | 0.000074 | 211.04 |
VAV WITH REHEAT HEATING COIL | 206143.07 | 0.001803 | 3402.47 |
FLR_3_DOAS HEATING COIL | 20393.42 | 0.000178 | 336.60 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.05 | 0.000053 | 0.000419 |
ROOM_2_FLR_3 FAN COIL | 1.01 | 0.000053 | 0.000407 |
ROOM_3_MULT19_FLR_3 FAN COIL | 6.12 | 0.000304 | 0.002402 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.49 | 0.000307 | 0.002311 |
ROOM_5_FLR_3 FAN COIL | 0.957161 | 0.000053 | 0.000384 |
ROOM_6_FLR_3 FAN COIL | 0.929662 | 0.000053 | 0.000374 |
ROOM_1_FLR_6 FAN COIL | 0.276262 | 0.000016 | 0.000111 |
ROOM_2_FLR_6 FAN COIL | 0.267172 | 0.000016 | 0.000107 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.28 | 0.000078 | 0.000521 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.05 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.01 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.12 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.49 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 0.957161 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.929662 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.276262 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.267172 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.28 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008599 | 12.80 | 0.008500 | 0.000419 | 1.05 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008602 | 12.80 | 0.008500 | 0.000407 | 1.01 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008526 | 12.80 | 0.008500 | 0.002402 | 6.12 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008784 | 12.80 | 0.008500 | 0.002311 | 5.49 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008608 | 12.80 | 0.008500 | 0.000384 | 0.957161 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008612 | 12.80 | 0.008500 | 0.000374 | 0.929662 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008594 | 12.80 | 0.008500 | 0.000111 | 0.276262 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008597 | 12.80 | 0.008500 | 0.000107 | 0.267172 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.68 | 6.70 | 0.008656 | 12.80 | 0.008500 | 0.000521 | 1.28 | |
VAV WITH REHEAT COOLING COIL | 28.55 | 6.70 | 0.012195 | 10.99 | 0.008500 | 0.024395 | 20.74 | 683001.78 |
FLR_3_DOAS COOLING COIL | 32.10 | 6.70 | 0.014120 | 11.94 | 0.008500 | 0.003084 | 2.05 | 86334.71 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.65 | 11.65 | 20.84 | 11.65 | 20.74 | 20.74 | 0.300000 | 0.561917 | 20.74 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 20.74 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 20.74 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.024395 | 0.000020 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001803 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.003084 | 0.000154 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000178 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Size Rated Evaporator Air Flow Rate [m3/s] | Design Size Rated Condenser Water Flow Rate [m3/s] | |
SWHSYSLAUNDRY HPWH DXCOIL | 4.90 | 0.004370 |
SWHSYS1 HPWH DXCOIL | 3.87 | 0.003451 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
SWHSYSLAUNDRY HPWH FAN | 4.90 | 700.51 |
SWHSYS1 HPWH FAN | 3.87 | 553.22 |
Condenser water flow rate [m3/s] | Evaporator air flow rate [m3/s] | |
SWHSYS1 HPWH | 0.003451 | 3.87 |
SWHSYSLAUNDRY HPWH | 0.004370 | 4.90 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.034515 | 7041.81 | |
HEATSYS1 PUMP | 0.004017 | 1197.87 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.004017 | 0.482083 |
COOLSYS1 | 0.034515 | 4.14 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 459208.84 | 459208.84 | 0.004017 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.034515 | 4875.28 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.034515 | 966322.88 | 966907.44 | 110.23 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 HPWH TANK | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 6.644 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.024 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 4.090 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.780 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.705 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.235 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 9.257 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.637 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 9.042 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.112 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.733 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2943.236 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 13147.704 | 6.644 | 123.454 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13147.704 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 650.557 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 650.557 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 753.347 | 9.699 | 60.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 753.347 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 387.592 | 4.090 | 189.996 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 387.592 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 445.205 | 5.705 | 53.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 445.205 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1748.285 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1748.285 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 11828.200 | 9.042 | 28.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11828.200 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 108.229 | 4.413 | 72.152 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.229 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1718.521 | 4.413 | 82.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1718.521 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1212.035 | 11.733 | 54.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1212.035 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1818.789 | 4.413 | 82.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1818.789 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.9242 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.217 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.286 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.107 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.174 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9147 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6546 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6103 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7359 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6841 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.28612306E-14 | 0.35438919E-16 | -0.14997333E-09 | 0.48037931E-16 |
29 | 8 | 0.21910456E-07 | 0.12451452E-12 | 0.37817107E-03 | -0.24912943E-09 |
30 | 7 | -0.12252860E-01 | 0.64616398E-08 | -0.23102096E-01 | 0.13931948E-03 |
31 | 6 | 0.40565756 | 0.22511349E-05 | 0.47235308 | -0.47513834E-02 |
32 | 5 | -5.1935619 | 0.84157732E-04 | -4.4432762 | 0.63221026E-01 |
33 | 4 | 33.016121 | 0.68920660E-03 | 21.448225 | -0.42229901 |
34 | 3 | -111.25447 | 0.15035857E-02 | -55.639617 | 1.5156026 |
35 | 2 | 197.15924 | 0.84653085E-03 | 77.889127 | -2.9011628 |
36 | 1 | -171.17492 | 0.90445513E-04 | -55.258822 | 2.7457697 |
37 | 0 | 57.057407 | 0.51539406E-06 | 15.557951 | |
38 | 9 | 0.12430042E-14 | 0.43603463E-16 | -0.13615479E-09 | -0.52742981E-17 |
39 | 8 | 0.19963588E-07 | 0.16114398E-12 | 0.35741204E-03 | -0.22699287E-09 |
40 | 7 | -0.11632381E-01 | 0.85488282E-08 | -0.22208377E-01 | 0.13226440E-03 |
41 | 6 | 0.38879653 | 0.30047059E-05 | 0.45796739 | -0.45526330E-02 |
42 | 5 | -5.0290001 | 0.11318598E-03 | -4.3326723 | 0.61180550E-01 |
43 | 4 | 32.288109 | 0.93328928E-03 | 21.015642 | -0.41263319 |
44 | 3 | -109.70522 | 0.20484795E-02 | -54.784283 | 1.4932205 |
45 | 2 | 195.62339 | 0.11595496E-02 | 77.105128 | -2.8767741 |
46 | 1 | -170.60747 | 0.12450863E-03 | -55.031726 | 2.7358244 |
47 | 0 | 57.057407 | 0.71328115E-06 | 15.596176 | |
48 | 9 | 0.10418955E-14 | 0.45554749E-16 | -0.13285794E-09 | -0.34221686E-17 |
49 | 8 | 0.19498290E-07 | 0.16949498E-12 | 0.35235048E-03 | -0.22170227E-09 |
50 | 7 | -0.11480752E-01 | 0.90423087E-08 | -0.21989859E-01 | 0.13054032E-03 |
51 | 6 | 0.38467563 | 0.31853038E-05 | 0.45444290 | -0.45040579E-02 |
52 | 5 | -4.9887746 | 0.12022067E-03 | -4.3055366 | 0.60681782E-01 |
53 | 4 | 32.110117 | 0.99300969E-03 | 20.909427 | -0.41027004 |
54 | 3 | -109.32633 | 0.21828955E-02 | -54.574228 | 1.4877470 |
55 | 2 | 195.24766 | 0.12373115E-02 | 76.912747 | -2.8708078 |
56 | 1 | -170.46860 | 0.13302463E-03 | -54.976289 | 2.7333905 |
57 | 0 | 57.057407 | 0.76310210E-06 | 15.605744 | |
58 | 9 | -0.19728226E-15 | 0.38070760E-16 | -0.14134637E-09 | 0.10329039E-17 |
59 | 8 | 0.20696804E-07 | 0.14765672E-12 | 0.36530744E-03 | -0.23532978E-09 |
60 | 7 | -0.11868633E-01 | 0.77667999E-08 | -0.22548754E-01 | 0.13495068E-03 |
61 | 6 | 0.39521686 | 0.27204939E-05 | 0.46345169 | -0.46283129E-02 |
62 | 5 | -5.0916664 | 0.10217830E-03 | -4.3748670 | 0.61957574E-01 |
63 | 4 | 32.565369 | 0.84029717E-03 | 21.180735 | -0.41631434 |
64 | 3 | -110.29532 | 0.18400486E-02 | -55.110745 | 1.5017457 |
65 | 2 | 196.20849 | 0.10394005E-02 | 77.404245 | -2.8860650 |
66 | 1 | -170.82368 | 0.11139293E-03 | -55.118150 | 2.7396138 |
67 | 0 | 57.057407 | 0.63685742E-06 | 15.581450 | |
68 | 9 | 0.13059652E-14 | 0.41030072E-16 | -0.13816519E-09 | -0.47111965E-17 |
69 | 8 | 0.20247126E-07 | 0.15597406E-12 | 0.36047671E-03 | -0.23021680E-09 |
70 | 7 | -0.11724123E-01 | 0.82470298E-08 | -0.22340566E-01 | 0.13330755E-03 |
71 | 6 | 0.39128975 | 0.28947446E-05 | 0.46009809 | -0.45820219E-02 |
72 | 5 | -5.0533361 | 0.10891817E-03 | -4.3490697 | 0.61482301E-01 |
73 | 4 | 32.395785 | 0.89717001E-03 | 21.079809 | -0.41406279 |
74 | 3 | -109.93440 | 0.19673976E-02 | -54.911173 | 1.4965315 |
75 | 2 | 195.85064 | 0.11127485E-02 | 77.221372 | -2.8803827 |
76 | 1 | -170.69145 | 0.11939355E-03 | -55.065279 | 2.7372963 |
77 | 0 | 57.057407 | 0.68346468E-06 | 15.590432 | |
78 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
79 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
80 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
81 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
82 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
83 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
84 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
85 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
86 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
87 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
88 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
89 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
90 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
91 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
92 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
93 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3672_SHGC_0.36 | 37 | 1 | VerySmooth | 2.086 | 2.086 | 1.000 | 0.361 | ||
2 | RESWINDOW_U_0.3672_SHGC_0.36 | 38 | 1 | VerySmooth | 2.086 | 2.086 | 1.000 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.58639E-002 | 0.27318 | 0.51921 | 0.51921 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11691 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.58639E-002 | 0.27318 | 0.51921 | 0.51921 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11691 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | "DX Coil Total Cooling Rate {W | HPWH Only}" | |
1 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | 1.1400 | 77706.2 | 48.891 | 1.7318 | 76621 | |
2 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | 2.8400 | 63053.7 | 4.646 | 9.4741 | 53264 |
Node Number | Height {m} | Volume {m3} | Maximum Capacity {W} | Off-Cycle UA {W/K} | On-Cycle UA {W/K} | Number Of Inlets | Number Of Outlets | |
1 | 1 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 0 | 1 |
2 | 2 | 0.2683 | 0.4733 | 47665.200 | 1.5573 | 1.5573 | 0 | 0 |
3 | 3 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
4 | 4 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
5 | 5 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 1 |
6 | 6 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 2 | 0 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 9.802E-003 | 1.461E-004 | 7.212E-005 | 0.133 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 3.784E-003 | 4.872E-005 | 1.327E-004 | 4.426E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 8.942E-003 | 5.445E-005 | 1.424E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 5.159E-003 | 5.445E-005 | 1.182E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 1.221E-002 | 1.565E-004 | 1.392E-004 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 2.167E-002 | 1.147E-004 | 6.318E-005 | 0.104 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 6.191E-002 | 4.733E-005 | 9.051E-005 | 4.300E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.587E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.588E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 6.879E-003 | 1.766E-005 | 1.424E-004 | 2.086E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 2.910E-003 | 1.186E-004 | 6.472E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1.243E-002 | 1.204E-004 | 6.523E-005 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1.217E-002 | 2.953E-005 | 2.446E-005 | 3.488E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1294 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 6.3911E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1448 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 7.1395E-002 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.4390E-002 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.6497E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 3.7870E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.2581E-002 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1470 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 7.7447E-002 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1651 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 8.6328E-002 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1045 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.5754E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 4.2527E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.7207E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.1438E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.8117E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.4121E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3639E-002 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.3277E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.3175E-003 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.7278E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3219E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.1438E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.8117E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.4121E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3639E-002 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.3277E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.3175E-003 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.7278E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3219E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 28616.45749 | 28616.45749 | 2.08019 | 2.08019 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 28.80700 | 1.41137E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1866.56785 | 1866.56785 | 8.00447E-002 | 0.85446 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4843.23257 | 4843.23257 | 0.35210 | 0.35210 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 31.79167 | 1.41191E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2663.52683 | 2663.52683 | 0.11422 | 0.11422 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 2989.57008 | 2989.57008 | 0.21734 | 0.21734 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 31.65600 | 1.41188E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 908.92196 | 908.92196 | 3.89773E-002 | 9.17347E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2529.69945 | 2529.69945 | 0.18387 | 0.18387 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 28.94267 | 1.41140E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1690.40636 | 1690.40636 | 7.24896E-002 | 7.24896E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1360.86906 | 1360.86906 | 9.89153E-002 | 9.89153E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 30.44733 | 1.41167E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1091.77909 | 1091.77909 | 4.68187E-002 | 5.77652E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44791.04400 | 44791.04400 | 3.25595 | 3.25595 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.41196E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2177.42918 | 2177.42918 | 9.33732E-002 | 9.33732E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 20606.50612 | 20606.50612 | 1.49931 | 1.49931 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 31.79167 | 1.41191E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 6702.68805 | 6702.68805 | 0.28743 | 0.67639 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 64340.90875 | 64340.90875 | 4.67889 | 4.67889 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 16056.07713 | 16056.07713 | 0.68853 | 1.89399 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 10689.52249 | 10689.52249 | 1.04708 | 1.04708 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 31.36000 | 1.41183E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 6056.06026 | 6056.06026 | 0.26122 | 0.26122 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -10.70000 | 1.50390E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10358.43506 | 10358.43506 | 1.01465 | 1.01465 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 6073.64085 | 6073.64085 | 0.26198 | 0.26198 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -10.70000 | 1.50390E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 62450.25328 | 62450.25328 | 6.11690 | 6.11690 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 34770.67161 | 34770.67161 | 1.49983 | 1.49983 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -10.70000 | 1.50390E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 56078.57803 | 56078.57803 | 5.49323 | 5.49323 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 32.10000 | 1.41196E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 35110.84228 | 35110.84228 | 1.51450 | 1.51450 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -10.70000 | 1.50390E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 9771.56168 | 9771.56168 | 0.95716 | 0.95716 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 28.86867 | 1.41138E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 6020.28899 | 6020.28899 | 0.25968 | 0.25968 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -10.70000 | 1.50390E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9490.82117 | 9490.82117 | 0.92966 | 0.92966 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 28.44933 | 1.41131E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 6037.88401 | 6037.88401 | 0.26044 | 0.26044 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -10.70000 | 1.50390E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 17020.31339 | 17020.31339 | 1.23721 | 1.23721 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 32.10000 | 1.41196E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 9818.45947 | 9818.45947 | 0.42105 | 0.47476 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2820.33531 | 2820.33531 | 0.27626 | 0.27626 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 31.36000 | 1.41183E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1866.10748 | 1866.10748 | 8.04935E-002 | 8.04935E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -10.70000 | 1.50390E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2727.53699 | 2727.53699 | 0.26717 | 0.26717 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1871.98815 | 1871.98815 | 8.07471E-002 | 8.07471E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -10.70000 | 1.50390E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 13079.10763 | 13079.10763 | 1.28117 | 1.28117 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.91500 | 1.41193E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 8900.19434 | 8900.19434 | 0.38391 | 0.38391 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -10.70000 | 1.50390E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29287.03997 | 29287.03997 | 2.13151 | 2.13151 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 32.10000 | 1.41196E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 6132.64387 | 6132.64387 | 0.26299 | 1.18780 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30741.70699 | 30741.70699 | 2.23735 | 2.23735 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 32.10000 | 1.41196E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 6280.13423 | 6280.13423 | 0.26931 | 1.18780 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -10.70000 | 1.50390E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 29837.65784 | 29837.65784 | 2.17457 | 2.17457 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 31.43400 | 1.41184E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2712.41549 | 2712.41549 | 0.11631 | 0.36735 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -10.70000 | 1.50390E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 9579.92213 | 9579.92213 | 0.69636 | 0.69636 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 32.03833 | 1.41195E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 6399.94065 | 6399.94065 | 0.27445 | 0.27445 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -10.70000 | 1.50390E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 394725.66 | 20.73536 | 20.73536 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 243456.16 | 7.34657 | 7.34657 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 47880.67 | 16.37335 | 2.05125 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 67975.66 | 4.60281 | 2.05125 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.08019 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.72487 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55900 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.16283 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.25611E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.00142E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.16283 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8003.05025 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.00142E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 169.56649 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.35210 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14515 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55900 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19682 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55900 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.62482E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.23858E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.19682 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3701.89038 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.23858E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 89.23689 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.21734 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27231 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55900 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12149 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72615 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.39916E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.35591E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12149 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1549.88802 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.35591E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 34.90296 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.18387 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.68066 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55900 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.10278 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.59751E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.95319E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.10278 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2232.61222 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.95319E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 55.73577 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.89153E-002 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.72998 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55900 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.52936E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.21929E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21033E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.52936E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1383.47689 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21033E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 36.00075 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.25595 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.24747E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55900 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.82007 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55900 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.08609E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.03039E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.82007 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11777.97307 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03039E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 248.52562 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.49931 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.59861E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55900 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.83811 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55900 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.96932E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.73214E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.83811 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11124.43440 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.73214E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 251.92386 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.67889 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21305 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55900 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.61550 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56813 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.78831E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.61184E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.61550 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29854.87916 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.61184E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 662.73624 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.04708 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.04708 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.29807E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.19405E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68317 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.59876E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.19405E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.04708 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6056.01420 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.29807E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 173.02923 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.01465 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.01465 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.31345E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.06768E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68316 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60195E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.06768E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.01465 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6073.59467 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.31345E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 173.53148 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.11690 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.11690 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.04188E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.40158E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68369 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.52592E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.40158E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.11690 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 34770.54304 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.04188E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 993.44041 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.49323 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.49323 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.07164E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.31140E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68277 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.78404E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.31140E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.49323 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 35110.71260 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.07164E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1003.15873 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.95716 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.95716 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.26677E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.84390E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68315 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60834E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.84390E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.95716 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6020.24316 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.26677E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 172.00729 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.92966 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.92966 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.28216E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.73677E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68315 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.61160E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.73677E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.92966 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6037.83807 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.28216E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 172.50995 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23721 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.95934 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55900 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.69160 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.97149E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.17820E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.69160 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13467.55266 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.17820E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 327.20467 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.27626 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.27626 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.63254E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.10503E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68318 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.59367E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.10503E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.27626 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1866.09394 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.63254E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 53.31616 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.26717 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.26717 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.63768E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.06960E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68317 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.59687E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.06960E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.26717 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1871.97457 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.63768E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 53.48416 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.28117 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.28117 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.78623E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.21220E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.68292 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.65636E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.21220E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.28117 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8900.14259 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.78623E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 254.28542 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.13151 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11857 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55900 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.19152 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55900 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.21342E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.08652E-004 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.19152 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12419.55277 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.08652E-004 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 272.83269 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.23735 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11296 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55900 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.25068 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55900 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.37298E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.12673E-004 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.25068 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12879.23257 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.12673E-004 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 282.58862 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.17457 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.51090E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55900 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.21559 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55900 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05251E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.97570E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.21559 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9116.71554 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.97570E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 194.36512 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69636 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.45097 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55900 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.38927 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.44845E-004 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.39588E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.38927 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8453.94501 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.39588E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 211.03743 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.65156 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.65156 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 20.84357 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.65156 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 20.73536 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 20.73536 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.56192 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 20.73536 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 20.73536 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.55482 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.98822 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.21953E-002 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 683001.77530 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.43952E-002 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 20.73536 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 206143.06527 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.80343E-003 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 3402.46928 |
350 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 20.73536 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.43952E-002 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.95198E-005 |
353 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.80343E-003 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
356 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 32.10000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.93776 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.41196E-002 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 86334.70852 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.08368E-003 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 20393.41537 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.78410E-004 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 336.60104 |
368 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.08368E-003 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.54423E-004 |
371 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.78410E-004 |
372 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 4.90359 |
373 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 4.36989E-003 |
374 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.90359 |
375 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Electric Power Consumption [W] | 700.51236 |
376 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 3.87257 |
377 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 3.45109E-003 |
378 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.87257 |
379 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Electric Power Consumption [W] | 553.22422 |
380 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Condenser water flow rate [m3/s] | 3.45109E-003 |
381 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Evaporator air flow rate [m3/s] | 3.87257 |
382 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 3.45148E-002 |
383 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 7041.80592 |
384 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.01736E-003 |
385 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.48208 |
386 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.01736E-003 |
387 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1197.87345 |
388 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
389 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 459208.84044 |
390 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 459208.84000 |
391 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.01736E-003 |
392 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 3.45148E-002 |
393 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 4.14178 |
394 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 3.45148E-002 |
395 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 4875.27975 |
396 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 3.45148E-002 |
397 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 966322.87821 |
398 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 966907.44000 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 110.22745 |
400 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
401 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
402 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
403 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
404 | WaterHeater:Stratified | SWHSYS1 HPWH TANK | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
405 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Condenser water flow rate [m3/s] | 4.36989E-003 |
406 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Evaporator air flow rate [m3/s] | 4.90359 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 8043.76 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3718.00 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1557.21 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2241.97 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1388.95 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11838.12 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 11176.71 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 29998.10 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 6522.08 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 6541.02 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 37446.41 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 37812.74 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 6483.56 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 6502.51 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 13525.65 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2009.69 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2016.02 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 9584.99 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 12479.79 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 12942.71 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 9162.82 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8489.39 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 146079.48 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 14451.42 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 17373.34 | 14058.65 | 3314.69 | 0.81 | 1949.75 | 19.78 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 16844.80 | 13628.02 | 3216.79 | 0.81 | 1890.30 | 19.17 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 100168.68 | 81463.47 | 18705.21 | 0.81 | 11260.37 | 114.21 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 94099.57 | 75233.64 | 18865.92 | 0.80 | 10522.36 | 106.72 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 15908.49 | 12864.96 | 3043.53 | 0.81 | 1784.98 | 18.10 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 15460.39 | 12499.84 | 2960.55 | 0.81 | 1734.58 | 17.59 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4579.64 | 3707.16 | 872.48 | 0.81 | 514.02 | 5.21 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4431.48 | 3586.45 | 845.03 | 0.81 | 497.35 | 5.04 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21474.28 | 17310.45 | 4163.83 | 0.81 | 2407.05 | 24.41 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 608769.61 | 404673.19 | 204096.43 | 0.66 | 71871.32 | 728.96 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 63544.84 | 41523.88 | 22020.96 | 0.65 | 7288.25 | 73.92 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.217 | 1.029 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.217 | 1.029 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.217 | 1.029 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.217 | 1.029 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.174 | 0.999 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.174 | 0.999 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.174 | 0.999 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.174 | 0.999 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.174 | 0.999 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.6263011699E-002 | 1.9944451344E-002 | Pass | Pass | 3.2096239304E-003 | 8.0971122512E-003 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.6378010592E-003 | 2.2349138682E-002 | Pass | Pass | 0.5397188524 | 3.9678486127 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.9154744436E-003 | 1.6108869896E-002 | Pass | Pass | 2.4699001740E-002 | 5.5567955013E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.5381800129E-004 | 3.8269191123E-004 | Pass | Pass | 6.9448484278E-002 | 0.1645488454 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.6337432675E-004 | 3.6794355874E-004 | Pass | Pass | 2.5094103203E-002 | 3.6662082070E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.9007031278E-002 | 0.2264114840 | Pass | Pass | 1.9190197677E-002 | 5.1250735447E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.6639416323E-002 | 7.4113907487E-002 | Pass | Pass | 4.3344568280E-002 | 8.4829370222E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.9656916728E-002 | 4.3548938860E-002 | Pass | Pass | 1.6795546977E-002 | 3.5169176059E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.7228296183E-002 | 0.2984685408 | Pass | Pass | 0.1678098483 | 0.7078154664 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2628509309E-002 | 0.3256232196 | Pass | Pass | 0.4332331511 | 4.0471664141 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.7079695634E-002 | 6.1386532905E-002 | Pass | Pass | 7.5845341911E-003 | 7.1342744595E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.1854303844E-002 | 0.1398443107 | Pass | Pass | 9.2739943431E-002 | 0.3313930732 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.4415368714E-002 | 0.2519875551 | Pass | Pass | 0.2497543887 | 1.0147412362 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.8639814781E-002 | 0.2760256888 | Pass | Pass | 0.1061766782 | 0.4141679889 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.0647131170E-004 | 3.2914780876E-004 | Pass | Pass | 0.2568561439 | 0.6170562385 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2821239489E-002 | 0.3334807166 | Pass | Pass | 0.1903796094 | 0.6427491362 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2632494774E-002 | 0.3474595908 | Pass | Pass | 0.1604432480 | 0.6216160865 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.2494698439E-002 | 0.1825583229 | Pass | Pass | 7.4062133918E-002 | 0.2563058723 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.3296177599E-002 | 9.8043171447E-002 | Pass | Pass | 8.4707983361E-003 | 1.9834311196E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.8564419705E-002 | 8.7632989058E-002 | Pass | Pass | 8.3517262072E-003 | 1.9353220092E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.9796708823E-002 | 0.1231527043 | Pass | Pass | 2.1906636729E-002 | 3.7690531054E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.9881242461E-004 | 6.3773261188E-004 | Pass | Pass | 0.1470019537 | 0.4261701258 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4397.64 | 26.01 | 1272.84 | 5444.95 | 5407.45 | 16548.89 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 172.00 | 59 | |||
Feb | 49.00 | 37 | |||
Mar | 40.00 | 38 | |||
Apr | 70.00 | 48 | |||
May | 70.00 | 36 | |||
Jun | 25.00 | 15 | |||
Jul | 64.00 | 20 | |||
Aug | 2.00 | 4 | |||
Sep | 73.00 | 32 | |||
Oct | 7.00 | 8 | |||
Nov | 88.00 | 34 | |||
Dec | 62.00 | 39 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.086 | 0.361 | 0.361 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.086 | 0.361 | 0.361 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.086 | 0.361 | 0.361 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.086 | 0.361 | 0.361 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.086 | 0.361 | 0.361 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.086 | 0.361 | 0.361 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.086 | 0.361 | 0.361 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.086 | 0.361 | 0.361 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.086 | 0.361 | 0.361 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.086 | 0.361 | 0.361 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.086 | 0.361 | 0.361 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.086 | 0.361 | 0.361 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.086 | 0.361 | 0.361 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.086 | 0.361 | 0.361 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.086 | 0.361 | 0.361 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.086 | 0.361 | 0.361 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.086 | 0.361 | 0.361 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.086 | 0.361 | 0.361 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.086 | 0.361 | 0.361 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.086 | 0.361 | 0.361 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.086 | 0.361 | 0.361 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.086 | 0.361 | 0.361 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.086 | 0.361 | 0.361 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.086 | 0.361 | 0.361 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.086 | 0.361 | 0.361 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.086 | 0.361 | 0.361 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.086 | 0.361 | 0.361 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.086 | 0.361 | 0.361 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.086 | 0.361 | 0.361 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.086 | 0.361 | 0.361 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.086 | 0.361 | 0.361 | |||||||||||||||||
North Total or Average | 432.95 | 2.086 | 0.361 | 0.361 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.086 | 0.361 | 0.361 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.6442 | 1978.83 | 13147.70 | LightsWired | LTG_SCH_BASEMENT | 45.99 | 168.00 | 45.94 | 0.0000 | Y | 113.37 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 9.6995 | 67.07 | 650.56 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 6.26 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 9.6995 | 77.67 | 753.35 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.25 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 4.0903 | 94.76 | 387.59 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 1.87 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.7049 | 78.04 | 445.21 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.90 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 9.2569 | 188.86 | 1748.29 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.34 | 0.0000 | Y | 12.91 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 9.0417 | 1308.19 | 11828.20 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 55.34 | 0.0000 | Y | 122.88 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.4132 | 1863.81 | 8225.38 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 73.68 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.4132 | 1864.32 | 8227.62 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 73.70 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 4.4132 | 1557.62 | 6874.08 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 56.74 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.21 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.54 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.19 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.54 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.4132 | 220.77 | 974.32 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 8.73 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.13 | 0.0000 | Y | 28.31 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.13 | 0.0000 | Y | 28.31 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.7327 | 103.30 | 1212.04 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.34 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 4.4132 | 412.12 | 1818.79 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 15.01 |
Interior Lighting Total | 5.8432 | 11345.29 | 66293.22 | 389.14 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 11096.45 | AstronomicalClock | - | 83.64 | 83.64 | 174.22 | |
Exterior Lighting Total | 11096.45 | 174.22 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 459208.84 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 966907.44 | 2.96 | 967077.40 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11742.45 | 17373.34 | 14058.65 | 3314.69 | 0.81 | - | 1949.75 | 19.78 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11388.64 | 16844.80 | 13628.02 | 3216.79 | 0.81 | - | 1890.30 | 19.17 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 67239.04 | 100168.68 | 81463.47 | 18705.21 | 0.81 | - | 11260.37 | 114.21 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 64714.14 | 94099.57 | 75233.64 | 18865.92 | 0.80 | - | 10522.36 | 106.72 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10762.09 | 15908.49 | 12864.96 | 3043.53 | 0.81 | - | 1784.98 | 18.10 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10462.16 | 15460.39 | 12499.84 | 2960.55 | 0.81 | - | 1734.58 | 17.59 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3093.84 | 4579.64 | 3707.16 | 872.48 | 0.81 | - | 514.02 | 5.21 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2994.66 | 4431.48 | 3586.45 | 845.03 | 0.81 | - | 497.35 | 5.04 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 14593.05 | 21474.28 | 17310.45 | 4163.83 | 0.81 | - | 2407.05 | 24.41 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 683001.78 | 608769.61 | 404673.19 | 204096.43 | 0.66 | - | 71871.32 | 728.96 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 86334.71 | 63544.84 | 41523.88 | 22020.96 | 0.65 | - | 7288.25 | 73.92 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 8003.05 | 8043.76 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3701.89 | 3718.00 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1549.89 | 1557.21 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2232.61 | 2241.97 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1383.48 | 1388.95 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11777.97 | 11838.12 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11124.43 | 11176.71 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 29854.88 | 29998.10 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6056.01 | 6522.08 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6073.59 | 6541.02 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 34770.54 | 37446.41 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 35110.71 | 37812.74 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6020.24 | 6483.56 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6037.84 | 6502.51 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 13467.55 | 13525.65 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1866.09 | 2009.69 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1871.97 | 2016.02 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 8900.14 | 9584.99 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12419.55 | 12479.79 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12879.23 | 12942.71 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 9116.72 | 9162.82 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8453.95 | 8489.39 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 206143.07 | 146079.48 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 20393.42 | 14451.42 | - |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 75921.46 | 3.40 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 54370.95 | 3.40 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.05 | 736.76 | 703.64 | 1.00 | 1.19 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.01 | 713.94 | 703.64 | 1.00 | 1.19 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.12 | 4304.07 | 703.64 | 1.00 | 0.96 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.49 | 3865.24 | 703.64 | 1.00 | 0.96 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.96 | 673.49 | 703.64 | 1.00 | 1.21 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.93 | 654.14 | 703.64 | 1.00 | 1.22 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.28 | 194.39 | 703.64 | 1.00 | 1.77 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.27 | 187.99 | 703.64 | 1.00 | 1.80 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.28 | 901.48 | 703.64 | 1.00 | 1.14 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 20.74 | 46460.45 | 2240.64 | 1.00 | 1.11 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 4.90 | 700.51 | 142.86 | 0.00 | 2.78 | General | ||
SWHSYS1 HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 3.87 | 553.22 | 142.86 | 0.00 | 2.84 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.034515 | 7041.81 | 204022.71 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.004017 | 1197.87 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.034515 | 4875.28 | 141251.80 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYSLAUNDRY HPWH | WaterHeater:HeatPump:PumpedCondenser | 1.14 | 77706.24 | 0.80 | 48.89 | 1.73 |
SWHSYS1 HPWH | WaterHeater:HeatPump:PumpedCondenser | 2.84 | 63053.73 | 0.80 | 4.65 | 9.47 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 28616.46 | 28616.46 | 14.46 | 2.080 | 2.080 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 24.00 | 24.00 | 0.00934 | 28.81 | 0.01411 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4843.23 | 4843.23 | 72.21 | 0.352 | 0.352 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00904 | 31.79 | 0.01412 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 2989.57 | 2989.57 | 38.49 | 0.217 | 0.217 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 24.00 | 24.00 | 0.00947 | 31.66 | 0.01412 | 0.092 | 0.00 |
MECH_FLR_1 | 2529.70 | 2529.70 | 15.40 | 0.184 | 0.184 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.00 | 24.00 | 0.00880 | 28.94 | 0.01411 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1360.87 | 1360.87 | 14.36 | 0.099 | 0.099 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 24.00 | 24.00 | 0.00890 | 30.45 | 0.01412 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44791.04 | 44791.04 | 573.95 | 3.256 | 3.256 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00855 | 32.10 | 0.01412 | 0.000 | 0.00 |
CAFE_FLR_1 | 20606.51 | 20606.51 | 109.11 | 1.499 | 1.499 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 23.99 | 0.01007 | 31.79 | 0.01412 | 0.676 | 0.00 |
LOBBY_FLR_1 | 64340.91 | 64340.91 | 49.18 | 4.679 | 4.679 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 23.99 | 0.01000 | 31.85 | 0.01412 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 10689.52 | 10689.52 | 273.94 | 1.047 | 1.047 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 21.11 | 21.11 | 0.00860 | 31.36 | 0.01412 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10358.44 | 10358.44 | 265.48 | 1.015 | 1.015 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00860 | 31.26 | 0.01412 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 62450.25 | 62450.25 | 2546.51 | 6.117 | 6.117 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 21.11 | 21.11 | 0.00853 | 31.85 | 0.01412 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 56078.58 | 56078.58 | 2286.07 | 5.493 | 5.493 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 21.11 | 21.11 | 0.00878 | 32.10 | 0.01412 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9771.56 | 9771.56 | 250.41 | 0.957 | 0.957 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 21.11 | 21.11 | 0.00861 | 28.87 | 0.01411 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9490.82 | 9490.82 | 243.25 | 0.930 | 0.930 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 21.11 | 21.11 | 0.00861 | 28.45 | 0.01411 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 17020.31 | 17020.31 | 43.71 | 1.237 | 1.237 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00965 | 32.10 | 0.01412 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2820.34 | 2820.34 | 72.28 | 0.276 | 0.276 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 21.11 | 21.11 | 0.00859 | 31.36 | 0.01412 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2727.54 | 2727.54 | 69.91 | 0.267 | 0.267 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00860 | 31.26 | 0.01412 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13079.11 | 13079.11 | 533.18 | 1.281 | 1.281 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00866 | 31.92 | 0.01412 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29287.04 | 29287.04 | 88.31 | 2.132 | 2.132 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 23.98 | 0.01043 | 32.10 | 0.01412 | 1.188 | 0.00 |
DINING_FLR_6 | 30741.71 | 30741.71 | 92.69 | 2.237 | 2.237 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 23.99 | 0.01034 | 32.10 | 0.01412 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 29837.66 | 29837.66 | 288.83 | 2.175 | 2.175 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01013 | 31.43 | 0.01412 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9579.92 | 9579.92 | 23.25 | 0.696 | 0.696 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00905 | 32.04 | 0.01412 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1866.57 | 1866.57 | 0.94 | 0.080 | 0.854 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00797 | -10.70 | 0.00150 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2663.53 | 2663.53 | 39.71 | 0.114 | 0.114 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00785 | -10.70 | 0.00150 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 908.92 | 908.92 | 11.70 | 0.039 | 0.092 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00783 | -10.70 | 0.00150 | 0.092 | 0.00 |
MECH_FLR_1 | 1690.41 | 1690.41 | 10.29 | 0.072 | 0.072 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00778 | -10.70 | 0.00150 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1091.78 | 1091.78 | 11.52 | 0.047 | 0.058 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00781 | -10.70 | 0.00150 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2177.43 | 2177.43 | 27.90 | 0.093 | 0.093 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00777 | -10.70 | 0.00150 | 0.000 | 0.00 |
CAFE_FLR_1 | 6702.69 | 6702.69 | 35.49 | 0.287 | 0.676 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00787 | -10.70 | 0.00150 | 0.676 | 0.00 |
LOBBY_FLR_1 | 16056.08 | 16056.08 | 12.27 | 0.689 | 1.894 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00784 | -10.70 | 0.00150 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 6056.06 | 6056.06 | 155.20 | 0.261 | 0.261 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00785 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 6073.64 | 6073.64 | 155.66 | 0.262 | 0.262 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00785 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 34770.67 | 34770.67 | 1417.83 | 1.500 | 1.500 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00786 | -10.70 | 0.00150 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 35110.84 | 35110.84 | 1431.31 | 1.515 | 1.515 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00786 | -10.70 | 0.00150 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 6020.29 | 6020.29 | 154.28 | 0.260 | 0.260 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00785 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 6037.88 | 6037.88 | 154.75 | 0.260 | 0.260 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00785 | -10.70 | 0.00150 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 9818.46 | 9818.46 | 25.21 | 0.421 | 0.475 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00788 | -10.70 | 0.00150 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1866.11 | 1866.11 | 47.82 | 0.080 | 0.080 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00787 | -10.70 | 0.00150 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1871.99 | 1871.99 | 47.98 | 0.081 | 0.081 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00787 | -10.70 | 0.00150 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8900.19 | 8900.19 | 362.82 | 0.384 | 0.384 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00788 | -10.70 | 0.00150 | 0.099 | 0.00 |
BANQUET_FLR_6 | 6132.64 | 6132.64 | 18.49 | 0.263 | 1.188 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00791 | -10.70 | 0.00150 | 1.188 | 0.00 |
DINING_FLR_6 | 6280.13 | 6280.13 | 18.94 | 0.269 | 1.188 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00791 | -10.70 | 0.00150 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 2712.42 | 2712.42 | 26.26 | 0.116 | 0.367 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00730 | -10.70 | 0.00150 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 6399.94 | 6399.94 | 15.53 | 0.274 | 0.274 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00792 | -10.70 | 0.00150 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 20.74 | 20.74 | 7.35 | 7.35 | 20.7354 | 11.6516 | 20.7354 | 0.5619 | 0.3000 |
FLR_3_DOAS | 16.37 | 2.05 | 4.60 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 8003.050 | 8003.050 | 1.162825 | 0.00007001 | 169.566 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8003.05 | 8003.05 | 1.162825 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00797372 | 51.5252 | 1866.57 | 0.00 | 8047.78 | 8047.78 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3701.890 | 3701.890 | 0.196825 | 0.00003239 | 89.237 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 3701.89 | 3701.89 | 0.196825 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00784836 | 50.7263 | 2663.53 | 0.00 | 3721.21 | 3721.21 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1549.888 | 1549.888 | 0.121495 | 0.00001356 | 34.903 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 1549.89 | 1549.89 | 0.121495 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00782899 | 50.6020 | 908.92 | 0.00 | 1558.26 | 1558.26 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2232.612 | 2232.612 | 0.102784 | 0.00001953 | 55.736 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 2232.61 | 2232.61 | 0.102784 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00778422 | 50.3162 | 1690.41 | 0.00 | 2244.13 | 2244.13 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1383.477 | 1383.477 | 0.055294 | 0.00001210 | 36.001 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 1383.48 | 1383.48 | 0.055294 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00780656 | 50.4588 | 1091.78 | 0.00 | 1390.44 | 1390.44 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11777.973 | 11777.973 | 1.820075 | 0.00010304 | 248.526 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 11777.97 | 11777.97 | 1.820075 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00777172 | 50.2371 | 2177.43 | 0.00 | 11843.89 | 11843.89 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 11124.434 | 11124.434 | 0.838113 | 0.00009732 | 251.924 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 11124.43 | 11124.43 | 0.838113 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00786641 | 50.8413 | 6702.69 | 0.00 | 11184.43 | 11184.43 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 29854.879 | 29854.879 | 2.615498 | 0.00026118 | 662.736 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 29854.88 | 29854.88 | 2.615498 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00784129 | 50.6805 | 16056.08 | 0.00 | 30017.12 | 30017.12 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 11742.449 | -999.000 | 1.047078 | 0.00041941 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | 7/21 16:30:00 | 11742.45 | 11463.14 | 1.047078 | 21.68 | 15.64 | 0.00859876 | 12.80 | 12.09 | 0.00850000 | 31.36 | 0.01411830 | 22.93 | 0.0000 | 21.11 | 0.00859876 | 55.1335 | 10689.52 | 0.00 | 11762.26 | 11296.08 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 6056.014 | 6056.014 | 0.261224 | 0.00005298 | 173.029 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 6056.01 | 6056.01 | 0.261224 | 21.11 | 14.75 | 0.00784611 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00784611 | 50.3670 | 6056.06 | 0.00 | 6528.57 | 6528.57 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 11388.644 | -999.000 | 1.014647 | 0.00040677 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 11388.64 | 11109.22 | 1.014647 | 21.68 | 15.64 | 0.00860195 | 12.80 | 12.09 | 0.00850000 | 31.26 | 0.01411813 | 22.90 | 0.0000 | 21.11 | 0.00860195 | 55.1536 | 10358.44 | 0.00 | 11407.84 | 10947.81 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 6073.595 | 6073.595 | 0.261983 | 0.00005313 | 173.531 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 6073.59 | 6073.59 | 0.261983 | 21.11 | 14.75 | 0.00784656 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00784656 | 50.3698 | 6073.64 | 0.00 | 6547.53 | 6547.53 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 67239.039 | -999.000 | 6.116899 | 0.00240158 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | unknown | 7/21 13:20:00 | 67239.04 | 66811.83 | 6.116899 | 21.68 | 15.57 | 0.00852592 | 12.80 | 12.09 | 0.00850000 | 31.85 | 0.01411920 | 23.06 | 0.0000 | 21.11 | 0.00852592 | 54.6712 | 62450.25 | 0.00 | 67355.04 | 65769.25 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 34770.543 | 34770.543 | 1.499830 | 0.00030419 | 993.440 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 34770.54 | 34770.54 | 1.499830 | 21.11 | 14.76 | 0.00785765 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00785765 | 50.4397 | 34770.67 | 0.00 | 37483.83 | 37483.83 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 64714.142 | -999.000 | 5.493234 | 0.00231140 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | 7/21 15:00:00 | 64714.14 | 60476.00 | 5.493234 | 21.68 | 15.80 | 0.00878404 | 12.80 | 12.09 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 0.0000 | 21.11 | 0.00878404 | 56.3056 | 56078.58 | 0.00 | 64817.73 | 59744.09 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 35110.713 | 35110.713 | 1.514503 | 0.00030716 | 1003.159 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 35110.71 | 35110.71 | 1.514503 | 21.11 | 14.76 | 0.00785896 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00785896 | 50.4480 | 35110.84 | 0.00 | 37850.54 | 37850.54 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 10762.091 | -999.000 | 0.957161 | 0.00038439 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | unknown | 7/21 09:40:00 | 10762.09 | 10481.93 | 0.957161 | 21.68 | 15.64 | 0.00860834 | 12.80 | 12.09 | 0.00850000 | 28.87 | 0.01411382 | 22.22 | 0.0000 | 21.11 | 0.00860834 | 55.1940 | 9771.56 | 0.00 | 10780.19 | 10330.56 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 6020.243 | 6020.243 | 0.259682 | 0.00005267 | 172.007 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 6020.24 | 6020.24 | 0.259682 | 21.11 | 14.75 | 0.00784522 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00784522 | 50.3613 | 6020.29 | 0.00 | 6490.01 | 6490.01 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10462.161 | -999.000 | 0.929662 | 0.00037368 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | unknown | 7/21 09:20:00 | 10462.16 | 10181.83 | 0.929662 | 21.68 | 15.65 | 0.00861160 | 12.80 | 12.09 | 0.00850000 | 28.45 | 0.01411307 | 22.10 | 0.0000 | 21.11 | 0.00861160 | 55.2147 | 9490.82 | 0.00 | 10479.74 | 10035.25 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 6037.838 | 6037.838 | 0.260440 | 0.00005282 | 172.510 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 6037.84 | 6037.84 | 0.260440 | 21.11 | 14.75 | 0.00784567 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00784567 | 50.3642 | 6037.88 | 0.00 | 6508.98 | 6508.98 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 13467.553 | 13467.553 | 0.691603 | 0.00011782 | 327.205 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 13467.55 | 13467.55 | 0.691603 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00788386 | 50.9519 | 9818.46 | 0.00 | 13537.64 | 13537.64 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3093.841 | -999.000 | 0.276262 | 0.00011050 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | 7/21 16:30:00 | 3093.84 | 3023.96 | 0.276262 | 21.68 | 15.63 | 0.00859367 | 12.80 | 12.09 | 0.00850000 | 31.36 | 0.01411830 | 22.93 | 0.0000 | 21.11 | 0.00859367 | 55.1013 | 2820.34 | 0.00 | 3099.07 | 2979.67 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1866.094 | 1866.094 | 0.080493 | 0.00001633 | 53.316 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1866.09 | 1866.09 | 0.080493 | 21.11 | 14.77 | 0.00787456 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00787456 | 50.5473 | 1866.11 | 0.00 | 2011.71 | 2011.71 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2994.656 | -999.000 | 0.267172 | 0.00010696 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 2994.66 | 2924.76 | 0.267172 | 21.68 | 15.63 | 0.00859687 | 12.80 | 12.09 | 0.00850000 | 31.26 | 0.01411813 | 22.90 | 0.0000 | 21.11 | 0.00859687 | 55.1215 | 2727.54 | 0.00 | 2999.71 | 2882.06 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1871.975 | 1871.975 | 0.080747 | 0.00001638 | 53.484 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1871.97 | 1871.97 | 0.080747 | 21.11 | 14.77 | 0.00787495 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00787495 | 50.5498 | 1871.99 | 0.00 | 2018.05 | 2018.05 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 14593.050 | -999.000 | 1.281175 | 0.00052122 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 14593.05 | 14051.00 | 1.281175 | 21.68 | 15.69 | 0.00865636 | 12.80 | 12.09 | 0.00850000 | 31.92 | 0.01411931 | 23.08 | 0.0000 | 21.11 | 0.00865636 | 55.4983 | 13079.11 | 0.00 | 14617.25 | 13857.34 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 8900.143 | 8900.143 | 0.383906 | 0.00007786 | 254.285 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8900.14 | 8900.14 | 0.383906 | 21.11 | 14.78 | 0.00787881 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00787881 | 50.5741 | 8900.19 | 0.00 | 9594.64 | 9594.64 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12419.553 | 12419.553 | 1.191515 | 0.00010865 | 272.833 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 12419.55 | 12419.55 | 1.191515 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00790579 | 51.0921 | 6132.64 | 0.00 | 12487.33 | 12487.33 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12879.233 | 12879.233 | 1.250677 | 0.00011267 | 282.589 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 12879.23 | 12879.23 | 1.250677 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00790797 | 51.1060 | 6280.13 | 0.00 | 12950.48 | 12950.48 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 9116.716 | 9116.716 | 1.215586 | 0.00007976 | 194.365 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 9116.72 | 9116.72 | 1.215586 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00730224 | 47.2419 | 2712.42 | 0.00 | 9167.57 | 9167.57 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 8453.945 | 8453.945 | 0.389267 | 0.00007396 | 211.037 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 8453.95 | 8453.95 | 0.389267 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00792072 | 51.1872 | 6399.94 | 0.00 | 8497.54 | 8497.54 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 683001.775 | -999.000 | 20.735361 | 0.02439524 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 683001.78 | 442038.99 | 20.735361 | 28.55 | 20.79 | 0.01219534 | 10.99 | 10.99 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 56.2395 | 23.99 | 0.00970705 | 52.1536 | 284788.07 | 0.00 | 683796.11 | 437534.34 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 206143.065 | 206143.065 | 6.220608 | 0.00180343 | 3402.469 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 206143.07 | 206143.07 | 6.220608 | -10.70 | -10.70 | 0.00150390 | 16.70 | 13.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 187.4649 | 21.00 | 0.00786191 | 50.8014 | 64092.50 | 0.00 | 176628.95 | 176628.95 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 86334.709 | -999.000 | 2.051317 | 0.00308368 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 86334.71 | 51162.86 | 2.051317 | 32.10 | 23.13 | 0.01411964 | 11.94 | 11.74 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 99.9965 | 21.11 | 0.00864996 | 55.4568 | 167155.63 | 0.00 | 86433.83 | 51479.65 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 20393.415 | 20393.415 | 0.615395 | 0.00017841 | 336.601 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 20393.42 | 20393.42 | 0.615395 | -10.70 | -10.70 | 0.00150390 | 16.70 | 13.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 333.3216 | 21.11 | 0.00785840 | 50.4445 | 106707.68 | 0.00 | 17473.63 | 17473.63 |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 46710.097 | 34378.631 | 4.903586 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 75921.46 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 36917.323 | 27171.150 | 3.872570 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 54370.95 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 8003.050 | 8003.050 | 1.162825 | 0.00007001 | 169.566 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 1.7084 | 1.742791 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8003.05 | 8003.05 | 1.0000 | 1.39957048 | 1.162825 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.07000703 | 60.00 | 32.22 | 27.78 | 0.000 | 8003.05 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00797372 | 21.00 | 0.00797372 | 51.5252 | 1866.57 | 0.00 | 8047.78 | 8047.78 | 1.39957048 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.24 | 15.31 | 0.00800000 | 42684.9 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3701.890 | 3701.890 | 0.196825 | 0.00003239 | 89.237 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 0.7902 | 0.806145 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 3701.89 | 3701.89 | 1.0000 | 0.23689704 | 0.196825 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.03238245 | 60.00 | 32.22 | 27.78 | 0.000 | 3701.89 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00784836 | 21.00 | 0.00784836 | 50.7263 | 2663.53 | 0.00 | 3721.21 | 3721.21 | 0.23689704 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.00 | 18.70 | 0.00800000 | 52642.9 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1549.888 | 1549.888 | 0.121495 | 0.00001356 | 34.903 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 0.3309 | 0.337513 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 1549.89 | 1549.89 | 1.0000 | 0.14623046 | 0.121495 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01355771 | 60.00 | 32.22 | 27.78 | 0.000 | 1549.89 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00782899 | 21.00 | 0.00782899 | 50.6020 | 908.92 | 0.00 | 1558.26 | 1558.26 | 0.14623046 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.05 | 17.03 | 0.00800000 | 47591.0 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2232.612 | 2232.612 | 0.102784 | 0.00001953 | 55.736 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 0.4766 | 0.486187 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 2232.61 | 2232.61 | 1.0000 | 0.12370990 | 0.102784 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01952987 | 60.00 | 32.22 | 27.78 | 0.000 | 2232.61 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00778422 | 21.00 | 0.00778422 | 50.3162 | 1690.41 | 0.00 | 2244.13 | 2244.13 | 0.12370990 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.39 | 19.46 | 0.00800000 | 55075.0 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1383.477 | 1383.477 | 0.055294 | 0.00001210 | 36.001 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 0.2953 | 0.301274 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 1383.48 | 1383.48 | 1.0000 | 0.06655113 | 0.055294 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01210202 | 60.00 | 32.22 | 27.78 | 0.000 | 1383.48 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00780656 | 21.00 | 0.00780656 | 50.4588 | 1091.78 | 0.00 | 1390.44 | 1390.44 | 0.06655113 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 37.09 | 20.31 | 0.00800000 | 57827.5 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11777.973 | 11777.973 | 1.820075 | 0.00010304 | 248.526 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 2.5142 | 2.564840 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 11777.97 | 11777.97 | 1.0000 | 2.19063257 | 1.820075 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.10302834 | 60.00 | 32.22 | 27.78 | 0.000 | 11777.97 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00777172 | 21.00 | 0.00777172 | 50.2371 | 2177.43 | 0.00 | 11843.89 | 11843.89 | 2.19063257 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.90 | 15.19 | 0.00800000 | 42341.3 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11124.434 | 11124.434 | 0.838113 | 0.00009732 | 251.924 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 2.3747 | 2.422522 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 11124.43 | 11124.43 | 1.0000 | 1.00874866 | 0.838113 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.09731148 | 60.00 | 32.22 | 27.78 | 0.000 | 11124.43 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00786641 | 21.00 | 0.00786641 | 50.8413 | 6702.69 | 0.00 | 11184.43 | 11184.43 | 1.00874866 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.47 | 17.18 | 0.00800000 | 48022.2 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29854.879 | 29854.879 | 2.615498 | 0.00026118 | 662.736 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 6.3731 | 6.501373 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 29854.88 | 29854.88 | 1.0000 | 3.14800018 | 2.615498 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.26115686 | 60.00 | 32.22 | 27.78 | 0.000 | 29854.88 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00784129 | 21.00 | 0.00784129 | 50.6805 | 16056.08 | 0.00 | 30017.12 | 30017.12 | 3.14800018 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.95 | 16.65 | 0.00800000 | 46470.0 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11742.449 | -999.000 | 1.047078 | 0.00041941 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8247 | 1004.8586 | 1.2036 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.047078 | 1.26025749 | 4197.9300 | 999.8980 | 34.51129336 | 13.37 | 6.70 | 6.67 | 966322.88 | 1.2152 | 1.215146 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | unknown | unknown | 7/21 16:30:00 | Sensible | 11742.45 | 11463.14 | 1.0000 | 1.26025749 | 1.047078 | 21.68 | 15.64 | 0.00859876 | 43639.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.41936246 | 6.70 | 13.37 | 6.67 | 0.000 | 11742.45 | 31.36 | 0.01411830 | 22.93 | 0.00000000 | 0.0000 | 21.11 | 0.00859876 | 21.11 | 0.00859876 | 55.1335 | 10689.52 | 0.00 | 11762.26 | 11296.08 | 1.26025749 | 21.68 | 15.64 | 0.00859876 | 43639.7 | 12.90 | 12.09 | 0.00845226 | 34306.5 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6056.014 | 6056.014 | 0.261224 | 0.00005298 | 173.029 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.047078 | 1.26025749 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 1.2928 | 1.318793 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 6056.01 | 6056.01 | 1.0000 | 0.31440849 | 0.261224 | 21.11 | 14.75 | 0.00784611 | 41143.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.05297525 | 60.00 | 32.22 | 27.78 | 0.000 | 6056.01 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00784611 | 21.11 | 0.00784611 | 50.3670 | 6056.06 | 0.00 | 6528.57 | 6528.57 | 0.31440849 | 16.60 | 13.00 | 0.00784611 | 36545.1 | 36.97 | 20.15 | 0.00784611 | 57309.7 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11388.644 | -999.000 | 1.014647 | 0.00040677 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8306 | 1004.8586 | 1.2036 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.014647 | 1.22122398 | 4197.9300 | 999.8980 | 34.51129336 | 13.37 | 6.70 | 6.67 | 966322.88 | 1.1786 | 1.178533 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | Sensible | 11388.64 | 11109.22 | 1.0000 | 1.22122398 | 1.014647 | 21.68 | 15.64 | 0.00860195 | 43647.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.40672689 | 6.70 | 13.37 | 6.67 | 0.000 | 11388.64 | 31.26 | 0.01411813 | 22.90 | 0.00000000 | 0.0000 | 21.11 | 0.00860195 | 21.11 | 0.00860195 | 55.1536 | 10358.44 | 0.00 | 11407.84 | 10947.81 | 1.22122398 | 21.68 | 15.64 | 0.00860195 | 43647.8 | 12.90 | 12.09 | 0.00845276 | 34306.5 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6073.595 | 6073.595 | 0.261983 | 0.00005313 | 173.531 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.014647 | 1.22122398 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 1.2965 | 1.322621 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 6073.59 | 6073.59 | 1.0000 | 0.31532121 | 0.261983 | 21.11 | 14.75 | 0.00784656 | 41144.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.05312904 | 60.00 | 32.22 | 27.78 | 0.000 | 6073.59 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00784656 | 21.11 | 0.00784656 | 50.3698 | 6073.64 | 0.00 | 6547.53 | 6547.53 | 0.31532121 | 16.60 | 13.00 | 0.00784656 | 36546.2 | 36.97 | 20.15 | 0.00784656 | 57310.9 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 67239.039 | -999.000 | 6.116899 | 0.00240158 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6893 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.116899 | 7.36226838 | 4197.9300 | 999.8980 | 34.51129336 | 13.37 | 6.70 | 6.67 | 966322.88 | 6.9582 | 6.958107 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | unknown | unknown | unknown | 7/21 13:20:00 | Sensible | 67239.04 | 66811.83 | 1.0000 | 7.36226838 | 6.116899 | 21.68 | 15.57 | 0.00852592 | 43455.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 2.40133286 | 6.70 | 13.37 | 6.67 | 0.000 | 67239.04 | 31.85 | 0.01411920 | 23.06 | 0.00000000 | 0.0000 | 21.11 | 0.00852592 | 21.11 | 0.00852592 | 54.6712 | 62450.25 | 0.00 | 67355.04 | 65769.25 | 7.36226838 | 21.68 | 15.58 | 0.00852592 | 43455.1 | 12.93 | 12.09 | 0.00844061 | 34306.4 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34770.543 | 34770.543 | 1.499830 | 0.00030419 | 993.440 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.116899 | 7.36226838 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 7.4225 | 7.571837 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 34770.54 | 34770.54 | 1.0000 | 1.80518727 | 1.499830 | 21.11 | 14.76 | 0.00785765 | 41172.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.30415685 | 60.00 | 32.22 | 27.78 | 0.000 | 34770.54 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00785765 | 21.11 | 0.00785765 | 50.4397 | 34770.67 | 0.00 | 37483.83 | 37483.83 | 1.80518727 | 16.60 | 13.01 | 0.00785765 | 36574.3 | 36.97 | 20.16 | 0.00785765 | 57338.8 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 64714.142 | -999.000 | 5.493234 | 0.00231140 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1691 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.493234 | 6.61162919 | 4197.9300 | 999.8980 | 34.51129336 | 13.37 | 6.70 | 6.67 | 966322.88 | 6.6969 | 6.696823 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | unknown | unknown | 7/21 15:00:00 | Sensible | 64714.14 | 60476.00 | 1.0000 | 6.61162919 | 5.493234 | 21.68 | 15.80 | 0.00878404 | 44110.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 2.31116025 | 6.70 | 13.37 | 6.67 | 0.000 | 64714.14 | 32.10 | 0.01411964 | 23.13 | 0.00000000 | 0.0000 | 21.11 | 0.00878404 | 21.11 | 0.00878404 | 56.3056 | 56078.58 | 0.00 | 64817.73 | 59744.09 | 6.61162919 | 21.68 | 15.80 | 0.00878404 | 44110.1 | 12.83 | 12.09 | 0.00848010 | 34306.5 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 35110.713 | 35110.713 | 1.514503 | 0.00030716 | 1003.159 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.493234 | 6.61162919 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 7.4951 | 7.645914 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 35110.71 | 35110.71 | 1.0000 | 1.82284790 | 1.514503 | 21.11 | 14.76 | 0.00785896 | 41176.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.30713250 | 60.00 | 32.22 | 27.78 | 0.000 | 35110.71 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00785896 | 21.11 | 0.00785896 | 50.4480 | 35110.84 | 0.00 | 37850.54 | 37850.54 | 1.82284790 | 16.60 | 13.01 | 0.00785896 | 36577.7 | 36.97 | 20.16 | 0.00785896 | 57342.2 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10762.091 | -999.000 | 0.957161 | 0.00038439 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8425 | 1004.8586 | 1.2036 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.957161 | 1.15203431 | 4197.9300 | 999.8980 | 34.51129336 | 13.37 | 6.70 | 6.67 | 966322.88 | 1.1137 | 1.113695 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | unknown | unknown | unknown | 7/21 09:40:00 | Sensible | 10762.09 | 10481.93 | 1.0000 | 1.15203431 | 0.957161 | 21.68 | 15.64 | 0.00860834 | 43664.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.38435055 | 6.70 | 13.37 | 6.67 | 0.000 | 10762.09 | 28.87 | 0.01411382 | 22.22 | 0.00000000 | 0.0000 | 21.11 | 0.00860834 | 21.11 | 0.00860834 | 55.1940 | 9771.56 | 0.00 | 10780.19 | 10330.56 | 1.15203431 | 21.68 | 15.65 | 0.00860834 | 43664.0 | 12.90 | 12.09 | 0.00845376 | 34306.5 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6020.243 | 6020.243 | 0.259682 | 0.00005267 | 172.007 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.957161 | 1.15203431 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 1.2851 | 1.311003 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 6020.24 | 6020.24 | 1.0000 | 0.31255138 | 0.259682 | 21.11 | 14.75 | 0.00784522 | 41141.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.05266234 | 60.00 | 32.22 | 27.78 | 0.000 | 6020.24 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00784522 | 21.11 | 0.00784522 | 50.3613 | 6020.29 | 0.00 | 6490.01 | 6490.01 | 0.31255138 | 16.60 | 13.00 | 0.00784522 | 36542.9 | 36.97 | 20.15 | 0.00784522 | 57307.5 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10462.161 | -999.000 | 0.929662 | 0.00037368 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8485 | 1004.8586 | 1.2036 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.929662 | 1.11893627 | 4197.9300 | 999.8980 | 34.51129336 | 13.37 | 6.70 | 6.67 | 966322.88 | 1.0827 | 1.082657 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | unknown | unknown | unknown | 7/21 09:20:00 | Sensible | 10462.16 | 10181.83 | 1.0000 | 1.11893627 | 0.929662 | 21.68 | 15.65 | 0.00861160 | 43672.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.37363906 | 6.70 | 13.37 | 6.67 | 0.000 | 10462.16 | 28.45 | 0.01411307 | 22.10 | 0.00000000 | 0.0000 | 21.11 | 0.00861160 | 21.11 | 0.00861160 | 55.2147 | 9490.82 | 0.00 | 10479.74 | 10035.25 | 1.11893627 | 21.68 | 15.65 | 0.00861160 | 43672.3 | 12.90 | 12.09 | 0.00845427 | 34306.5 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6037.838 | 6037.838 | 0.260440 | 0.00005282 | 172.510 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.929662 | 1.11893627 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 1.2889 | 1.314835 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 6037.84 | 6037.84 | 1.0000 | 0.31346485 | 0.260440 | 21.11 | 14.75 | 0.00784567 | 41142.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.05281625 | 60.00 | 32.22 | 27.78 | 0.000 | 6037.84 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00784567 | 21.11 | 0.00784567 | 50.3642 | 6037.88 | 0.00 | 6508.98 | 6508.98 | 0.31346485 | 16.60 | 13.00 | 0.00784567 | 36544.0 | 36.97 | 20.15 | 0.00784567 | 57308.6 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13467.553 | 13467.553 | 0.691603 | 0.00011782 | 327.205 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 2.8749 | 2.932773 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 13467.55 | 13467.55 | 1.0000 | 0.83240995 | 0.691603 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.11780801 | 60.00 | 32.22 | 27.78 | 0.000 | 13467.55 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00788386 | 21.00 | 0.00788386 | 50.9519 | 9818.46 | 0.00 | 13537.64 | 13537.64 | 0.83240995 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.55 | 18.88 | 0.00800000 | 53197.9 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3093.841 | -999.000 | 0.276262 | 0.00011050 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8152 | 1004.8586 | 1.2036 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.276262 | 0.33250751 | 4197.9300 | 999.8980 | 34.51129336 | 13.37 | 6.70 | 6.67 | 966322.88 | 0.3202 | 0.320160 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | unknown | unknown | 7/21 16:30:00 | Sensible | 3093.84 | 3023.96 | 1.0000 | 0.33250751 | 0.276262 | 21.68 | 15.63 | 0.00859367 | 43626.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.11049148 | 6.70 | 13.37 | 6.67 | 0.000 | 3093.84 | 31.36 | 0.01411830 | 22.93 | 0.00000000 | 0.0000 | 21.11 | 0.00859367 | 21.11 | 0.00859367 | 55.1013 | 2820.34 | 0.00 | 3099.07 | 2979.67 | 0.33250751 | 21.68 | 15.64 | 0.00859367 | 43626.8 | 12.90 | 12.09 | 0.00845146 | 34306.5 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1866.094 | 1866.094 | 0.080493 | 0.00001633 | 53.316 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.276262 | 0.33250751 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 0.3984 | 0.406372 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 1866.09 | 1866.09 | 1.0000 | 0.09688153 | 0.080493 | 21.11 | 14.77 | 0.00787456 | 41215.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01632374 | 60.00 | 32.22 | 27.78 | 0.000 | 1866.09 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00787456 | 21.11 | 0.00787456 | 50.5473 | 1866.11 | 0.00 | 2011.71 | 2011.71 | 0.09688153 | 16.60 | 13.03 | 0.00787456 | 36617.1 | 36.97 | 20.17 | 0.00787456 | 57381.8 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2994.656 | -999.000 | 0.267172 | 0.00010696 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8211 | 1004.8586 | 1.2036 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.267172 | 0.32156707 | 4197.9300 | 999.8980 | 34.51129336 | 13.37 | 6.70 | 6.67 | 966322.88 | 0.3099 | 0.309896 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | Sensible | 2994.66 | 2924.76 | 1.0000 | 0.32156707 | 0.267172 | 21.68 | 15.63 | 0.00859687 | 43634.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.10694926 | 6.70 | 13.37 | 6.67 | 0.000 | 2994.66 | 31.26 | 0.01411813 | 22.90 | 0.00000000 | 0.0000 | 21.11 | 0.00859687 | 21.11 | 0.00859687 | 55.1215 | 2727.54 | 0.00 | 2999.71 | 2882.06 | 0.32156707 | 21.68 | 15.64 | 0.00859687 | 43634.9 | 12.90 | 12.09 | 0.00845196 | 34306.5 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1871.975 | 1871.975 | 0.080747 | 0.00001638 | 53.484 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.267172 | 0.32156707 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 0.3996 | 0.407652 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 1871.97 | 1871.97 | 1.0000 | 0.09718683 | 0.080747 | 21.11 | 14.77 | 0.00787495 | 41216.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01637518 | 60.00 | 32.22 | 27.78 | 0.000 | 1871.97 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00787495 | 21.11 | 0.00787495 | 50.5498 | 1871.99 | 0.00 | 2018.05 | 2018.05 | 0.09718683 | 16.60 | 13.03 | 0.00787495 | 36618.1 | 36.97 | 20.17 | 0.00787495 | 57382.8 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14593.050 | -999.000 | 1.281175 | 0.00052122 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9317 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.281175 | 1.54201569 | 4197.9300 | 999.8980 | 34.51129336 | 13.37 | 6.70 | 6.67 | 966322.88 | 1.5102 | 1.510135 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | Sensible | 14593.05 | 14051.00 | 1.0000 | 1.54201569 | 1.281175 | 21.68 | 15.69 | 0.00865636 | 43785.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.52116704 | 6.70 | 13.37 | 6.67 | 0.000 | 14593.05 | 31.92 | 0.01411931 | 23.08 | 0.00000000 | 0.0000 | 21.11 | 0.00865636 | 21.11 | 0.00865636 | 55.4983 | 13079.11 | 0.00 | 14617.25 | 13857.34 | 1.54201569 | 21.68 | 15.69 | 0.00865636 | 43785.8 | 12.88 | 12.09 | 0.00846118 | 34306.5 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8900.143 | 8900.143 | 0.383906 | 0.00007786 | 254.285 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.281175 | 1.54201569 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 1.8999 | 1.938147 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 8900.14 | 8900.14 | 1.0000 | 0.46206771 | 0.383906 | 21.11 | 14.78 | 0.00787881 | 41226.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.07785439 | 60.00 | 32.22 | 27.78 | 0.000 | 8900.14 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00787881 | 21.11 | 0.00787881 | 50.5741 | 8900.19 | 0.00 | 9594.64 | 9594.64 | 0.46206771 | 16.60 | 13.03 | 0.00787881 | 36627.9 | 36.97 | 20.18 | 0.00787881 | 57392.5 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12419.553 | 12419.553 | 1.191515 | 0.00010865 | 272.833 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 2.6512 | 2.704554 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 12419.55 | 12419.55 | 1.0000 | 1.43410161 | 1.191515 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.10864058 | 60.00 | 32.22 | 27.78 | 0.000 | 12419.55 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00790579 | 21.00 | 0.00790579 | 51.0921 | 6132.64 | 0.00 | 12487.33 | 12487.33 | 1.43410161 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.14 | 16.36 | 0.00800000 | 45642.2 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12879.233 | 12879.233 | 1.250677 | 0.00011267 | 282.589 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 2.7493 | 2.804657 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 12879.23 | 12879.23 | 1.0000 | 1.50530879 | 1.250677 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.11266165 | 60.00 | 32.22 | 27.78 | 0.000 | 12879.23 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00790797 | 21.00 | 0.00790797 | 51.1060 | 6280.13 | 0.00 | 12950.48 | 12950.48 | 1.50530879 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.04 | 16.33 | 0.00800000 | 45537.9 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9116.716 | 9116.716 | 1.215586 | 0.00007976 | 194.365 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 1.9461 | 1.985309 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 9116.72 | 9116.72 | 1.0000 | 1.46307267 | 1.215586 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.07974887 | 60.00 | 32.22 | 27.78 | 0.000 | 9116.72 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.63 | 0.00730224 | 21.00 | 0.00730224 | 47.2419 | 2712.42 | 0.00 | 9167.57 | 9167.57 | 1.46307267 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.74 | 15.50 | 0.00800000 | 43200.7 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8453.945 | 8453.945 | 0.389267 | 0.00007396 | 211.037 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 1.8047 | 1.840980 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | Sensible | 8453.95 | 8453.95 | 1.0000 | 0.46851977 | 0.389267 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.07395125 | 60.00 | 32.22 | 27.78 | 0.000 | 8453.95 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00792072 | 21.00 | 0.00792072 | 51.1872 | 6399.94 | 0.00 | 8497.54 | 8497.54 | 0.46851977 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.39 | 19.46 | 0.00800000 | 55071.7 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 683001.775 | -999.000 | 20.735361 | 0.02439524 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.5105 | 1004.8586 | 1.2036 | VAV WITH REHEAT FAN | Fan:VariableVolume | 20.735361 | 24.95697608 | 4197.9300 | 999.8980 | 34.51129336 | 13.37 | 6.70 | 6.67 | 966322.88 | 70.6805 | 70.680493 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | Sensible | 683001.78 | 442038.99 | 1.0000 | 24.95697608 | 20.735361 | 28.55 | 20.79 | 0.01219534 | 59840.2 | 10.99 | 10.99 | 0.00850000 | 32473.0 | 24.39275232 | 6.70 | 13.37 | 6.67 | 46460.450 | 636541.33 | 32.10 | 0.01411964 | 23.13 | 11.66146000 | 56.2395 | 23.99 | 0.00971689 | 23.99 | 0.00970705 | 52.1536 | 284788.07 | 0.00 | 683796.11 | 437534.34 | 24.95697608 | 28.55 | 20.79 | 0.01219534 | 59840.2 | 11.49 | 11.33 | 0.00828326 | 32441.2 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 206143.065 | 206143.065 | 6.220608 | 0.00180343 | 3402.469 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV WITH REHEAT FAN | Fan:VariableVolume | 20.735361 | 24.95697608 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 44.0053 | 44.890918 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 206143.07 | 206143.07 | 1.0000 | 7.48709282 | 6.220608 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 1.80324549 | 60.00 | 32.22 | 27.78 | 0.000 | 206143.07 | -10.70 | 0.00150390 | -10.70 | 11.66146000 | 187.4649 | 20.98 | 0.00785805 | 21.00 | 0.00786191 | 50.8014 | 64092.50 | 0.00 | 176628.95 | 176628.95 | 7.48709282 | 2.80 | -1.97 | 0.00150390 | 6582.5 | 26.21 | 10.51 | 0.00150390 | 30173.7 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 86334.709 | -999.000 | 2.051317 | 0.00308368 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1031.0877 | 1004.8586 | 1.2036 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.46886833 | 4197.9300 | 999.8980 | 34.51129336 | 13.37 | 6.70 | 6.67 | 966322.88 | 8.9344 | 8.934354 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | Sensible | 86334.71 | 51162.86 | 1.0000 | 2.46895513 | 2.051317 | 32.10 | 23.13 | 0.01411964 | 68410.3 | 11.94 | 11.74 | 0.00850000 | 33442.2 | 3.08336118 | 6.70 | 13.37 | 6.67 | 2195.006 | 84139.70 | 32.10 | 0.01411964 | 23.13 | 2.05124512 | 99.9965 | 21.11 | 0.00864548 | 21.11 | 0.00864996 | 55.4568 | 167155.63 | 0.00 | 86433.83 | 51479.65 | 2.46895513 | 32.10 | 23.14 | 0.01411964 | 68410.3 | 11.88 | 11.73 | 0.00850831 | 33402.0 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 20393.415 | 20393.415 | 0.615395 | 0.00017841 | 336.601 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.46886833 | 4197.9300 | 999.8980 | 4.01694945 | 54.44 | 82.22 | 27.78 | 468450.60 | 4.3534 | 4.440989 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 20393.42 | 20393.42 | 1.0000 | 0.74068654 | 0.615395 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 0.17839229 | 60.00 | 32.22 | 27.78 | 0.000 | 20393.42 | -10.70 | 0.00150390 | -10.70 | 2.05124512 | 333.3216 | 21.11 | 0.00785778 | 21.11 | 0.00785840 | 50.4445 | 106707.68 | 0.00 | 17473.63 | 17473.63 | 0.74068654 | 2.80 | -1.97 | 0.00150390 | 6582.5 | 26.21 | 10.51 | 0.00150390 | 30173.7 | |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 46710.097 | 34378.631 | 4.903586 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 1.2036 | SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 4.903586 | 5.90193210 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 75921.46 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 75921.46 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 36917.323 | 27171.150 | 3.872570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 1.2036 | SWHSYS1 HPWH FAN | Fan:SystemModel | 3.872570 | 4.66100528 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 54370.95 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54370.95 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 20.74 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 319.00 | 7803.67 | 0.00 |
RETAIL_1_FLR_1 | 2436.83 | 6879.50 | 1286.33 |
RETAIL_2_FLR_1 | 1513.67 | 6401.17 | 95.50 |
MECH_FLR_1 | 1195.00 | 7427.67 | 898.00 |
STORAGE_FLR_1 | 1177.83 | 7863.17 | 1094.17 |
LAUNDRY_FLR_1 | 6374.83 | 3434.00 | 2465.50 |
CAFE_FLR_1 | 3104.33 | 5982.50 | 1117.67 |
LOBBY_FLR_1 | 2400.67 | 6131.33 | 853.17 |
ROOM_1_FLR_3 | 1746.83 | 8162.67 | 1666.17 |
ROOM_2_FLR_3 | 2871.50 | 7877.67 | 2547.17 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1197.33 | 8699.83 | 1182.50 |
ROOM_5_FLR_3 | 1647.33 | 8099.83 | 1632.33 |
ROOM_6_FLR_3 | 2702.67 | 7910.00 | 2463.17 |
CORRIDOR_FLR_3 | 1106.33 | 7687.17 | 1008.67 |
ROOM_1_FLR_6 | 2525.50 | 8062.17 | 2327.17 |
ROOM_2_FLR_6 | 3582.83 | 7788.00 | 3173.67 |
ROOM_3_MULT9_FLR_6 | 1219.33 | 8040.17 | 1063.83 |
BANQUET_FLR_6 | 4104.00 | 3854.00 | 862.67 |
DINING_FLR_6 | 4805.00 | 2751.50 | 770.33 |
KITCHEN_FLR_6 | 7961.00 | 6552.00 | 6145.33 |
CORRIDOR_FLR_6 | 1800.00 | 6898.00 | 862.17 |
Facility | 8698.00 | 8760.00 | 7904.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 3.33 | 0.00 | 3.33 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 16.83 | 0.00 | 16.83 |
ROOM_2_FLR_3 | 0.00 | 24.50 | 0.00 | 24.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.33 | 58.33 | 0.33 | 58.33 |
ROOM_5_FLR_3 | 0.00 | 5.67 | 0.00 | 5.67 |
ROOM_6_FLR_3 | 0.00 | 35.83 | 0.00 | 35.83 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 19.67 | 0.00 | 19.67 |
ROOM_2_FLR_6 | 0.00 | 29.33 | 0.00 | 29.33 |
ROOM_3_MULT9_FLR_6 | 0.00 | 17.50 | 0.00 | 17.50 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 13.00 | 0.00 | 13.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.33 | 114.50 | 0.33 | 114.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.76 | 106.50 | 4826.41 | 0.888 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.744 | 0.034 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.461 | 0.011 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.578 | 0.013 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.537 | 0.013 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 24.156 | 0.037 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.52 | 142.30 | 748.35 | 4.165 | 0.027 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.96 | 422.44 | 5183.56 | 1.892 | 0.011 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.044 | 0.000 | 0.065 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.044 | 0.000 | 0.061 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.403 | 0.020 | 0.000 | 0.104 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.044 | 0.000 | 0.065 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.044 | 0.000 | 0.066 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.532 | 0.005 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.355 | 0.044 | 0.000 | 0.079 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.044 | 0.000 | 0.068 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.403 | 0.036 | 0.000 | 0.126 |
BANQUET_FLR_6 | 144.91 | 249.90 | 1010.89 | 4.888 | 0.013 | 0.000 | 0.000 |
DINING_FLR_6 | 144.91 | 249.90 | 1010.89 | 5.253 | 0.013 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 21.223 | 0.037 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 1.138 | 0.009 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.76 | 106.50 | 4826.41 | 0.687 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.112 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.383 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.553 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.499 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 20.691 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.52 | 142.30 | 748.35 | 3.928 | 0.000 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.96 | 422.44 | 5183.56 | 1.773 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.000 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.416 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.91 | 249.90 | 1010.89 | 4.140 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 144.91 | 249.90 | 1010.89 | 4.351 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 13.633 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 1.005 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.76 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.52 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.96 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.15 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.91 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.91 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.86 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 872.83 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 36922829.53 | 0.00 | 36922829.53 | 0.00 | 36922829.53 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 6303393.16 | 0.00 | 6303393.16 | 78790.55 | 6382183.71 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3875712.74 | 0.00 | 3875712.74 | 30413.25 | 3906125.99 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 3249994.56 | 0.00 | 3249994.56 | 71878.86 | 3321873.42 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1743778.33 | 0.00 | 1743778.33 | 41470.14 | 1785248.47 | 1821682.01 | 8754.83 | 3.50 | 1.67 | 0.00 |
LAUNDRY_FLR_1 | 64398000.37 | 0.00 | 64398000.37 | 98146.91 | 64496147.27 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 26838179.14 | 0.00 | 26838179.14 | 174170.96 | 27012350.10 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 84331307.72 | 0.00 | 84331307.72 | 497646.22 | 84828953.95 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 66918.31 | 1527075.02 | 45732.42 | 1572807.44 | 1946875.62 | 2190.00 | 5869.33 | 700.67 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 62268.29 | 1522253.93 | 45728.93 | 1567982.85 | 1946647.51 | 2190.00 | 5925.89 | 644.11 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 0.00 | 1099911.97 | 12759.86 | 1112671.83 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.00 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 66933.68 | 19870762.97 | 12763.35 | 19883526.32 | 26405105.73 | 2190.00 | 5882.72 | 687.28 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 66970.37 | 1527127.08 | 45732.42 | 1572859.50 | 1946875.62 | 2190.00 | 5869.33 | 700.67 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 66996.35 | 1526981.98 | 45728.93 | 1572710.91 | 1946647.51 | 2190.00 | 5872.97 | 697.03 | 0.00 |
CORRIDOR_FLR_3 | 21808730.93 | 0.00 | 21808730.93 | 55299.69 | 21864030.62 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 81422.52 | 446461.69 | 45741.96 | 492203.65 | 486718.90 | 2014.42 | 5868.46 | 877.12 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 69634.96 | 434631.37 | 45738.47 | 480369.84 | 486661.88 | 2045.73 | 5965.59 | 748.68 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 81406.69 | 2426597.00 | 23403.19 | 2450000.18 | 3126920.42 | 2190.00 | 5867.33 | 702.67 | 0.00 |
BANQUET_FLR_6 | 42371235.50 | 0.00 | 42371235.50 | 111690.36 | 42482925.86 | 37458366.31 | 0.00 | 4346.20 | 4413.80 | 0.00 |
DINING_FLR_6 | 45522749.65 | 0.00 | 45522749.65 | 111690.36 | 45634440.02 | 37458366.31 | 0.00 | 0.00 | 8760.00 | 0.00 |
KITCHEN_FLR_6 | 57314972.45 | 0.00 | 57314972.45 | 99988.77 | 57414961.22 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12347393.63 | 0.00 | 12347393.63 | 97863.43 | 12445257.06 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 7023290.24 | 0.21E+10 | 4608511.80 | 0.21E+10 | 0.43E+10 | 8760.00 | 7942.24 | 8760.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.1708 | 0.0000 | 1.1708 | 0.0000 | 1.1708 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.1999 | 0.0000 | 0.1999 | 0.0025 | 0.2024 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1229 | 0.0000 | 0.1229 | 0.0010 | 0.1239 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.1031 | 0.0000 | 0.1031 | 0.0023 | 0.1053 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0553 | 0.0000 | 0.0553 | 0.0013 | 0.0566 | 0.0578 | 8754.83 | 3.50 | 1.67 |
LAUNDRY_FLR_1 | 2.0420 | 0.0000 | 2.0420 | 0.0031 | 2.0452 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.8510 | 0.0000 | 0.8510 | 0.0055 | 0.8566 | 0.6764 | 0.00 | 0.00 | 8760.00 |
LOBBY_FLR_1 | 2.6741 | 0.0000 | 2.6741 | 0.0158 | 2.6899 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0021 | 0.0484 | 0.0015 | 0.0499 | 0.0617 | 2190.00 | 5869.33 | 700.67 |
ROOM_2_FLR_3 | 0.0463 | 0.0020 | 0.0483 | 0.0015 | 0.0497 | 0.0617 | 2190.00 | 5925.89 | 644.11 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0021 | 0.6301 | 0.0004 | 0.6305 | 0.8373 | 2190.00 | 5882.72 | 687.28 |
ROOM_5_FLR_3 | 0.0463 | 0.0021 | 0.0484 | 0.0015 | 0.0499 | 0.0617 | 2190.00 | 5869.33 | 700.67 |
ROOM_6_FLR_3 | 0.0463 | 0.0021 | 0.0484 | 0.0015 | 0.0499 | 0.0617 | 2190.00 | 5872.97 | 697.03 |
CORRIDOR_FLR_3 | 0.6916 | 0.0000 | 0.6916 | 0.0018 | 0.6933 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0026 | 0.0142 | 0.0015 | 0.0156 | 0.0154 | 2014.42 | 5868.46 | 877.12 |
ROOM_2_FLR_6 | 0.0116 | 0.0022 | 0.0138 | 0.0015 | 0.0152 | 0.0154 | 2045.73 | 5965.59 | 748.68 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0026 | 0.0769 | 0.0007 | 0.0777 | 0.0992 | 2190.00 | 5867.33 | 702.67 |
BANQUET_FLR_6 | 1.3436 | 0.0000 | 1.3436 | 0.0035 | 1.3471 | 1.1878 | 0.00 | 4346.20 | 4413.80 |
DINING_FLR_6 | 1.4435 | 0.0000 | 1.4435 | 0.0035 | 1.4471 | 1.1878 | 0.00 | 0.00 | 8760.00 |
KITCHEN_FLR_6 | 1.8174 | 0.0000 | 1.8174 | 0.0032 | 1.8206 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3915 | 0.0000 | 0.3915 | 0.0031 | 0.3946 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 64.1408 | 0.2227 | 64.3635 | 0.1154 | 64.4789 | 73.9670 | 8760.00 | 7942.24 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.59E+09 | 0.00 | 0.59E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 43197387.25 | 562551.16 | 43759938.41 | 64690340.46 | 8699.72 | 31.84 | 28.44 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 18.6973 | 0.0000 | 18.6973 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.3698 | 0.0178 | 1.3876 | 2.0513 | 8699.72 | 31.84 | 28.44 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 3242.40 | 0.00 | 0.00 | 0.00 | 5517.60 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 18.8926 | 0.0000 | 0.0000 | 0.0000 | 18.5859 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.7302 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1363 |
Defaulted Fields | 1208 |
Fields with Defaults | 4115 |
Autosized Fields | 353 |
Autosizable Fields | 407 |
Autocalculated Fields | 289 |
Autocalculatable Fields | 549 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5691.35 | 69017.21 | 14-NOV-03:40 | 463186.21 | 04-AUG-19:20 |
Electricity:Building | 2338.65 | 30592.50 | 03-JUN-05:00 | 138695.41 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 256.48 | 3058.02 | 02-JAN-02:10 | 18903.76 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2331.56 | 30451.35 | 03-JUN-05:00 | 138454.08 | 02-JAN-20:10 |
InteriorLights:Electricity | 603.42 | 5169.18 | 03-JUN-05:00 | 50471.22 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 113.37 | 1030.12 | 02-JAN-02:10 | 9271.23 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 603.42 | 5169.18 | 03-JUN-05:00 | 50471.22 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 603.42 | 5169.18 | 03-JUN-05:00 | 50471.22 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 113.37 | 1030.12 | 02-JAN-02:10 | 9271.23 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 603.42 | 5169.18 | 03-JUN-05:00 | 50471.22 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 16.45 | 201.26 | 02-JAN-02:10 | 1197.92 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 19.05 | 233.06 | 02-JAN-02:10 | 1387.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.46 | 67.94 | 02-JAN-02:10 | 394.77 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.87 | 16.96 | 02-JAN-02:10 | 152.61 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.87 | 16.96 | 02-JAN-02:10 | 152.61 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.84 | 1007.22 | 02-JAN-02:10 | 4973.49 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 27.25 | 277.68 | 03-JUN-05:00 | 2538.73 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 12.91 | 74.47 | 03-JUN-05:00 | 1573.46 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 12.91 | 74.47 | 03-JUN-05:00 | 1573.46 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 271.88 | 3211.03 | 10-JUN-05:00 | 20674.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 122.88 | 1099.62 | 10-JUN-05:00 | 10645.38 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 122.88 | 1099.62 | 10-JUN-05:00 | 10645.38 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 18.46 | 262.96 | 01-JAN-02:10 | 1214.21 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 18.46 | 262.93 | 01-JAN-02:10 | 1214.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 302.44 | 4545.27 | 01-JAN-02:10 | 20822.55 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 73.68 | 623.81 | 01-JAN-02:10 | 5671.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 73.68 | 623.81 | 01-JAN-02:10 | 5671.40 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 302.52 | 4546.52 | 01-JAN-02:10 | 20828.25 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 73.70 | 623.98 | 01-JAN-02:10 | 5672.95 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 73.70 | 623.98 | 01-JAN-02:10 | 5672.95 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 18.46 | 262.96 | 01-JAN-02:10 | 1214.21 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 18.46 | 262.93 | 01-JAN-02:10 | 1214.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.62 | 65.74 | 01-JAN-02:10 | 303.55 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.74 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.74 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.62 | 65.73 | 01-JAN-02:10 | 303.52 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.73 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.73 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 35.82 | 538.40 | 01-JAN-02:10 | 2466.50 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 8.73 | 73.89 | 01-JAN-02:10 | 671.80 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 8.73 | 73.89 | 01-JAN-02:10 | 671.80 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 204.17 | 2433.51 | 03-JUN-05:00 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.31 | 184.21 | 03-JUN-05:00 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.31 | 184.21 | 03-JUN-05:00 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 204.17 | 2433.51 | 03-JUN-05:00 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.31 | 184.21 | 03-JUN-05:00 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.31 | 184.21 | 03-JUN-05:00 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 444.45 | 5944.83 | 02-JAN-02:10 | 18636.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 43.88 | 732.84 | 15-MAR-22:30 | 2790.48 | 17-SEP-10:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1798.08 | 2144.51 | 13-APR-02:40 | 242065.56 | 04-AUG-19:00 |
LowTempRefrigeration:Refrigeration:Electricity | 15.72 | 0.00 | 01-JAN-11:10 | 1320.20 | 22-JUN-10:40 |
MedTempRefrigeration:Refrigeration:Electricity | 21.07 | 600.19 | 06-FEB-04:10 | 719.28 | 28-MAY-14:00 |
WaterSystems:Electricity | 489.84 | 1086.57 | 02-SEP-00:20 | 43132.15 | 01-SEP-21:00 |
Electricity:HVAC | 761.37 | 13357.75 | 12-JAN-15:00 | 46524.58 | 04-AUG-20:20 |
Fans:Electricity | 550.32 | 12436.92 | 25-NOV-08:10 | 36355.97 | 18-AUG-21:10 |
General:Fans:Electricity | 550.32 | 12436.92 | 25-NOV-08:10 | 36355.97 | 18-AUG-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ExteriorEquipment:Electricity | 641.49 | 9451.24 | 02-JAN-02:20 | 39155.93 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 22.46 | 386.37 | 03-JUN-05:00 | 1283.34 | 15-JUN-20:10 |
ElectricityPurchased:Facility | 5691.35 | 69017.21 | 14-NOV-03:40 | 463186.21 | 04-AUG-19:20 |
ElectricityPurchased:Plant | 5691.35 | 69017.21 | 14-NOV-03:40 | 463186.21 | 04-AUG-19:20 |
Cogeneration:ElectricityPurchased | 5691.35 | 69017.21 | 14-NOV-03:40 | 463186.21 | 04-AUG-19:20 |
General:Cogeneration:ElectricityPurchased | 5691.35 | 69017.21 | 14-NOV-03:40 | 463186.21 | 04-AUG-19:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5691.35 | 69017.21 | 14-NOV-03:40 | 463186.21 | 04-AUG-19:20 |
ElectricityNet:Plant | 5691.35 | 69017.21 | 14-NOV-03:40 | 463186.21 | 04-AUG-19:20 |
Cogeneration:ElectricityNet | 5691.35 | 69017.21 | 14-NOV-03:40 | 463186.21 | 04-AUG-19:20 |
General:Cogeneration:ElectricityNet | 5691.35 | 69017.21 | 14-NOV-03:40 | 463186.21 | 04-AUG-19:20 |
ExteriorLights:Electricity | 174.22 | 0.00 | 01-JAN-07:30 | 11096.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 174.22 | 0.00 | 01-JAN-07:30 | 11096.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 188.60 | 0.00 | 03-JAN-08:50 | 9938.94 | 29-MAY-18:40 |
General:HeatRecovery:Electricity | 188.60 | 0.00 | 03-JAN-08:50 | 9938.94 | 29-MAY-18:40 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.57 | 02-SEP-00:20 | 4738.76 | 02-OCT-18:10 |
Water Heater Parasitic:WaterSystems:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1150.62 | 0.00 | 01-JAN-00:10 | 196240.11 | 04-AUG-19:10 |
General:Cooling:Electricity | 1150.62 | 0.00 | 01-JAN-00:10 | 196240.11 | 04-AUG-19:10 |
Pumps:Electricity | 120.83 | 51.18 | 01-NOV-07:30 | 7534.60 | 11-AUG-21:00 |
General:Pumps:Electricity | 120.83 | 51.18 | 01-NOV-07:30 | 7534.60 | 11-AUG-21:00 |
WIRED_LTG_ELECTRICITY | 21.24 | 0.00 | 01-JAN-00:10 | 1776.59 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 3806.08 | 29270.80 | 07-APR-01:10 | 422891.71 | 06-FEB-19:10 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 2017.24 | 15908.90 | 07-APR-10:10 | 344770.77 | 05-FEB-24:00 |
WaterSystems:NaturalGas | 1132.48 | 15908.90 | 01-JAN-09:10 | 136843.69 | 06-FEB-21:50 |
Water Heater:WaterSystems:NaturalGas | 1132.48 | 15908.90 | 01-JAN-09:10 | 136843.69 | 06-FEB-21:50 |
Heating:NaturalGas | 884.76 | 0.00 | 02-MAR-21:00 | 232046.90 | 06-FEB-09:10 |
Boiler:Heating:NaturalGas | 884.76 | 0.00 | 02-MAR-21:00 | 232046.90 | 06-FEB-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 3725.04 | 0.00 | 01-JAN-00:10 | 709188.43 | 11-AUG-22:00 |
PlantLoopCoolingDemand:HVAC | 3725.04 | 0.00 | 01-JAN-00:10 | 709188.43 | 11-AUG-22:00 |
CoolingCoils:PlantLoopCoolingDemand | 3725.04 | 0.00 | 01-JAN-00:10 | 709188.43 | 11-AUG-22:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-MAR-21:50 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-MAR-21:50 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-MAR-21:50 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-MAR-21:50 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-MAR-21:50 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-MAR-21:50 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 22-MAY-06:30 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 22-MAY-06:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 24281.28 | 131267.75 | 06-MAR-14:50 | 2873724.17 | 03-AUG-20:20 |
EnergyTransfer:Building | 4965.19 | 79077.49 | 15-JAN-15:00 | 331225.65 | 19-JUN-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 695.28 | 9955.98 | 06-FEB-04:00 | 35208.24 | 09-JUL-10:40 |
Refrigeration:EnergyTransfer | 183.23 | 3970.98 | 06-FEB-04:00 | 10379.00 | 10-NOV-07:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.62 | 1985.49 | 06-FEB-04:00 | 5189.50 | 10-NOV-07:30 |
General:Refrigeration:EnergyTransfer | 91.62 | 1985.49 | 06-FEB-04:00 | 5189.50 | 10-NOV-07:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.62 | 1985.49 | 06-FEB-04:00 | 5189.50 | 10-NOV-07:30 |
EnergyTransfer:Plant | 10278.00 | 16496.83 | 19-OCT-01:20 | 1642069.86 | 11-AUG-22:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.61 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 70.01 | 1746.31 | 06-FEB-04:10 | 2577.61 | 28-MAY-14:00 |
EnergyTransfer:HVAC | 9038.09 | 1546.69 | 08-MAY-14:40 | 1077527.01 | 03-AUG-20:20 |
CoolingCoils:EnergyTransfer | 4929.12 | 0.00 | 01-JAN-00:10 | 836974.30 | 11-AUG-22:00 |
EnergyTransfer:Zone:BASEMENT | 337.56 | 5214.24 | 28-MAY-13:50 | 17577.41 | 27-OCT-21:00 |
Heating:EnergyTransfer | 121.92 | 0.00 | 03-JAN-18:20 | 84202.96 | 14-JAN-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 121.92 | 0.00 | 03-JAN-18:20 | 84202.96 | 14-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4751.65 | 65889.28 | 08-JAN-15:00 | 327604.06 | 19-JUN-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 337.56 | 5214.24 | 28-MAY-13:50 | 17577.41 | 27-OCT-21:00 |
General:Cooling:EnergyTransfer | 4751.65 | 65889.28 | 08-JAN-15:00 | 327604.06 | 19-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 337.56 | 5214.24 | 28-MAY-13:50 | 17577.41 | 27-OCT-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 41.35 | 0.01 | 15-FEB-19:00 | 3981.32 | 04-OCT-12:10 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.70 | 0.00 | 01-JAN-08:20 | 1149.08 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.70 | 0.00 | 01-JAN-08:20 | 1149.08 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 40.65 | 0.00 | 01-JAN-00:10 | 3981.32 | 04-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 40.65 | 0.00 | 01-JAN-00:10 | 3981.32 | 04-OCT-12:10 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 34.34 | 251.25 | 02-JAN-15:00 | 2044.12 | 18-AUG-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 34.34 | 251.25 | 02-JAN-15:00 | 2044.12 | 18-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 34.34 | 251.25 | 02-JAN-15:00 | 2044.12 | 18-AUG-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 23.50 | 0.06 | 12-JAN-14:30 | 1705.12 | 18-AUG-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.19 | 0.00 | 01-JAN-19:10 | 463.94 | 02-JAN-15:00 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.19 | 0.00 | 01-JAN-19:10 | 463.94 | 02-JAN-15:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 23.32 | 0.00 | 01-JAN-00:10 | 1705.12 | 18-AUG-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 23.32 | 0.00 | 01-JAN-00:10 | 1705.12 | 18-AUG-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 11.70 | 0.01 | 01-FEB-12:20 | 733.29 | 08-JUL-10:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.37 | 0.00 | 03-JAN-18:20 | 415.76 | 06-FEB-16:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.37 | 0.00 | 03-JAN-18:20 | 415.76 | 06-FEB-16:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 11.33 | 0.00 | 01-JAN-00:10 | 733.29 | 08-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 11.33 | 0.00 | 01-JAN-00:10 | 733.29 | 08-JUL-10:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 598.14 | 8917.82 | 02-JAN-05:00 | 38815.87 | 04-AUG-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 598.14 | 8917.82 | 02-JAN-05:00 | 38815.87 | 04-AUG-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 598.14 | 8917.82 | 02-JAN-05:00 | 38815.87 | 04-AUG-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 237.38 | 7.74 | 08-JAN-15:50 | 14032.87 | 30-SEP-12:40 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 10.30 | 08-JAN-15:40 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 10.30 | 08-JAN-15:40 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 237.38 | 0.00 | 08-JAN-15:40 | 14032.87 | 30-SEP-12:40 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 237.38 | 0.00 | 08-JAN-15:40 | 14032.87 | 30-SEP-12:40 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 791.94 | 8734.75 | 08-JAN-16:00 | 42005.26 | 04-AUG-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 791.94 | 8734.75 | 08-JAN-16:00 | 42005.26 | 04-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 791.94 | 8734.75 | 08-JAN-16:00 | 42005.26 | 04-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 65.06 | 0.00 | 01-JAN-08:10 | 11615.94 | 02-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 14.11 | 0.00 | 01-JAN-08:10 | 6344.79 | 14-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 14.11 | 0.00 | 01-JAN-08:10 | 6344.79 | 14-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 50.95 | 0.00 | 01-JAN-00:10 | 11615.94 | 02-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 50.95 | 0.00 | 01-JAN-00:10 | 11615.94 | 02-AUG-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 56.33 | 0.00 | 01-JAN-08:10 | 10983.25 | 02-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 18.42 | 0.00 | 01-JAN-08:10 | 6458.33 | 14-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 18.42 | 0.00 | 01-JAN-08:10 | 6458.33 | 14-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 37.91 | 0.00 | 01-JAN-00:10 | 10983.25 | 02-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 37.91 | 0.00 | 01-JAN-00:10 | 10983.25 | 02-AUG-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 299.22 | 0.00 | 01-JAN-00:10 | 52021.22 | 04-OCT-12:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 299.22 | 0.00 | 01-JAN-00:10 | 52021.22 | 04-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 299.22 | 0.00 | 01-JAN-00:10 | 52021.22 | 04-OCT-12:10 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 376.71 | 0.00 | 01-JAN-08:10 | 67112.89 | 19-JUN-15:10 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 29.21 | 0.00 | 01-JAN-08:10 | 42098.22 | 06-FEB-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 29.21 | 0.00 | 01-JAN-08:10 | 42098.22 | 06-FEB-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 347.50 | 0.00 | 01-JAN-00:10 | 67112.89 | 19-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 347.50 | 0.00 | 01-JAN-00:10 | 67112.89 | 19-JUN-15:10 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 64.48 | 0.00 | 01-JAN-08:10 | 10673.57 | 22-AUG-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 13.93 | 0.00 | 01-JAN-08:10 | 6392.78 | 14-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 13.93 | 0.00 | 01-JAN-08:10 | 6392.78 | 14-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 50.55 | 0.00 | 01-JAN-00:10 | 10673.57 | 22-AUG-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 50.55 | 0.00 | 01-JAN-00:10 | 10673.57 | 22-AUG-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 55.57 | 0.00 | 01-JAN-08:10 | 10804.69 | 29-MAY-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 17.96 | 0.00 | 01-JAN-08:10 | 6535.83 | 14-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 17.96 | 0.00 | 01-JAN-08:10 | 6535.83 | 14-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 37.61 | 0.00 | 01-JAN-00:10 | 10804.69 | 29-MAY-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 37.61 | 0.00 | 01-JAN-00:10 | 10804.69 | 29-MAY-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 154.69 | 0.20 | 05-FEB-05:10 | 9242.35 | 24-AUG-17:00 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 1.21 | 0.00 | 01-JAN-08:00 | 3865.64 | 14-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 1.21 | 0.00 | 01-JAN-08:00 | 3865.64 | 14-JAN-16:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 153.47 | 0.00 | 01-JAN-00:10 | 9242.35 | 24-AUG-17:00 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 153.47 | 0.00 | 01-JAN-00:10 | 9242.35 | 24-AUG-17:00 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 18.34 | 0.00 | 01-JAN-08:10 | 3094.35 | 02-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.64 | 0.00 | 01-JAN-08:10 | 2066.85 | 14-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.64 | 0.00 | 01-JAN-08:10 | 2066.85 | 14-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 12.69 | 0.00 | 01-JAN-00:10 | 3094.35 | 02-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 12.69 | 0.00 | 01-JAN-00:10 | 3094.35 | 02-AUG-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 16.68 | 0.00 | 01-JAN-08:10 | 2937.39 | 02-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.05 | 0.00 | 01-JAN-08:10 | 2094.44 | 14-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.05 | 0.00 | 01-JAN-08:10 | 2094.44 | 14-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.63 | 0.00 | 01-JAN-00:10 | 2937.39 | 02-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.63 | 0.00 | 01-JAN-00:10 | 2937.39 | 02-AUG-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 94.23 | 0.00 | 01-JAN-08:10 | 14738.87 | 30-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 12.17 | 0.00 | 01-JAN-08:10 | 9613.75 | 14-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 12.17 | 0.00 | 01-JAN-08:10 | 9613.75 | 14-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 82.06 | 0.00 | 01-JAN-00:10 | 14738.87 | 30-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 82.06 | 0.00 | 01-JAN-00:10 | 14738.87 | 30-AUG-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 434.29 | 7981.97 | 06-FEB-15:00 | 23342.76 | 04-AUG-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 434.29 | 7981.97 | 06-FEB-15:00 | 23342.76 | 04-AUG-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 434.29 | 7981.97 | 06-FEB-15:00 | 23342.76 | 04-AUG-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 473.36 | 8983.58 | 06-FEB-15:00 | 24573.85 | 04-AUG-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 473.36 | 8983.58 | 06-FEB-15:00 | 24573.85 | 04-AUG-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 473.36 | 8983.58 | 06-FEB-15:00 | 24573.85 | 04-AUG-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 603.66 | 7970.50 | 06-FEB-04:00 | 30117.79 | 09-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 603.66 | 7970.50 | 06-FEB-04:00 | 30117.79 | 09-JUL-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 85.05 | 0.04 | 12-JAN-01:50 | 6425.54 | 16-AUG-12:50 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.96 | 0.00 | 01-JAN-09:20 | 2507.53 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.96 | 0.00 | 01-JAN-09:20 | 2507.53 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 84.09 | 0.00 | 01-JAN-00:10 | 6425.54 | 16-AUG-12:50 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 84.09 | 0.00 | 01-JAN-00:10 | 6425.54 | 16-AUG-12:50 |
PlantLoopHeatingDemand:Facility | 2979.83 | 8896.18 | 10-AUG-00:30 | 307254.19 | 05-FEB-23:00 |
PlantLoopHeatingDemand:Plant | 2351.87 | 8896.18 | 10-AUG-00:30 | 219611.31 | 03-JUL-20:40 |
WaterSystems:PlantLoopHeatingDemand | 2351.87 | 8896.18 | 10-AUG-00:30 | 219611.31 | 03-JUL-20:40 |
General:WaterSystems:PlantLoopHeatingDemand | 759.16 | 8892.19 | 10-AUG-00:20 | 57212.08 | 25-JAN-07:10 |
HeatingCoils:EnergyTransfer | 627.96 | 0.00 | 02-MAR-21:00 | 185338.80 | 14-JAN-16:10 |
PlantLoopHeatingDemand:HVAC | 627.96 | 0.00 | 02-MAR-21:00 | 185338.80 | 14-JAN-16:10 |
HeatingCoils:PlantLoopHeatingDemand | 627.96 | 0.00 | 02-MAR-21:00 | 185338.80 | 14-JAN-16:10 |
HeatRecoveryForHeating:EnergyTransfer | 2914.60 | 0.00 | 03-JAN-08:50 | 468219.91 | 06-FEB-03:00 |
HeatRecoveryForCooling:EnergyTransfer | 566.41 | 0.00 | 01-JAN-00:10 | 303349.67 | 20-JUL-21:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 1592.71 | 0.00 | 01-JAN-00:10 | 183948.72 | 03-JUL-20:40 |
WaterSystems:EnergyTransfer | 759.16 | 8892.19 | 10-AUG-00:20 | 57212.08 | 25-JAN-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 759.16 | 8892.19 | 10-AUG-00:20 | 57212.08 | 25-JAN-07:10 |
Boilers:EnergyTransfer | 621.81 | 0.00 | 02-MAR-21:00 | 187979.14 | 14-JAN-16:10 |
Chillers:EnergyTransfer | 3827.40 | 0.00 | 01-JAN-00:10 | 718114.86 | 11-AUG-22:00 |
HeatRejection:EnergyTransfer | 4978.02 | 0.00 | 01-JAN-00:10 | 894753.58 | 11-AUG-22:00 |
General:HeatRejection:EnergyTransfer | 4978.02 | 0.00 | 01-JAN-00:10 | 894753.58 | 11-AUG-22:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -337.558 | 0.000 | 0.000 | 143.827 | 113.371 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -62.745 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.698 | -40.650 | 0.000 | 0.000 | 15.519 | 6.265 | 10.186 | 24.596 | 0.000 | 0.046 | 0.000 | 0.000 | -9.474 | 0.000 | -0.980 | -6.206 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -34.344 | 0.000 | 0.000 | 17.054 | 7.255 | 11.795 | 0.000 | 0.000 | 0.017 | 0.000 | 0.000 | 0.000 | 0.000 | -0.402 | -1.375 |
MECH_FLR_1 | 0.000 | 0.000 | 0.190 | -23.315 | 0.000 | 0.000 | 3.726 | 8.366 | 12.471 | 0.000 | 0.000 | 0.040 | 0.000 | 0.000 | 0.000 | 0.000 | -0.907 | -0.571 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.370 | -11.334 | 0.000 | 0.000 | 2.886 | 1.866 | 3.598 | 0.000 | 0.000 | 0.024 | 3.109 | 0.000 | 0.000 | 0.000 | -0.518 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -598.142 | 0.000 | 0.000 | 11.404 | 4.900 | 658.131 | 0.000 | 0.000 | 0.070 | 0.000 | 0.000 | 0.000 | 0.000 | -1.337 | -75.025 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -237.381 | 0.000 | 0.000 | 192.916 | 12.911 | 14.341 | 68.391 | 0.000 | 0.096 | 0.000 | 0.000 | -28.377 | 0.000 | -2.317 | -20.579 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -791.945 | 0.000 | 0.000 | 560.119 | 122.882 | 148.998 | 90.416 | 0.000 | 0.273 | 0.000 | 0.000 | -38.595 | 0.000 | -6.800 | -85.349 |
ROOM_1_FLR_3 | 18.071 | -43.230 | 0.000 | -11.683 | 0.000 | 0.000 | 9.713 | 6.171 | 12.292 | 46.732 | 0.000 | 0.312 | 0.000 | 0.000 | -21.289 | 0.000 | -2.874 | -14.215 |
ROOM_2_FLR_3 | 22.740 | -29.998 | 0.000 | -12.238 | 0.000 | 0.000 | 9.583 | 6.170 | 12.291 | 33.104 | 0.000 | 0.164 | 0.000 | 0.000 | -22.242 | 0.000 | -3.354 | -16.220 |
ROOM_3_MULT19_FLR_3 | 0.000 | -284.107 | 0.000 | -15.108 | 0.000 | 0.000 | 0.000 | 73.685 | 228.754 | 273.458 | 0.000 | 0.144 | 0.001 | 0.000 | -153.441 | 0.000 | -15.979 | -107.405 |
ROOM_4_MULT19_FLR_3 | 65.289 | -219.929 | 0.000 | -163.627 | 0.000 | 0.000 | 182.710 | 73.705 | 228.817 | 90.047 | 0.000 | 1.254 | 0.000 | 0.000 | -125.456 | 0.000 | -29.573 | -103.236 |
ROOM_5_FLR_3 | 17.809 | -42.748 | 0.000 | -11.686 | 0.000 | 0.000 | 9.708 | 6.171 | 12.292 | 46.315 | 0.000 | 0.312 | 0.000 | 0.000 | -21.024 | 0.000 | -2.880 | -14.269 |
ROOM_6_FLR_3 | 22.234 | -29.682 | 0.000 | -12.196 | 0.000 | 0.000 | 9.601 | 6.170 | 12.291 | 32.412 | 0.000 | 0.165 | 0.000 | 0.000 | -21.647 | 0.000 | -3.355 | -15.992 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 1.213 | -153.473 | 0.000 | 0.000 | 118.121 | 56.739 | 0.000 | 42.959 | 0.000 | 0.119 | 0.000 | 0.000 | -27.762 | 0.000 | -2.790 | -35.125 |
ROOM_1_FLR_6 | 6.734 | -10.865 | 0.000 | -2.918 | 0.000 | 0.000 | 2.432 | 1.543 | 3.073 | 11.615 | 0.000 | 0.084 | 0.000 | 0.000 | -5.274 | 0.000 | -0.750 | -5.675 |
ROOM_2_FLR_6 | 8.214 | -7.728 | 0.000 | -3.062 | 0.000 | 0.000 | 2.397 | 1.543 | 3.073 | 8.226 | 0.000 | 0.042 | 0.000 | 0.000 | -5.523 | 0.000 | -0.862 | -6.319 |
ROOM_3_MULT9_FLR_6 | 17.151 | -68.189 | 0.000 | -18.852 | 0.000 | 0.000 | 21.790 | 8.728 | 27.097 | 64.044 | 0.000 | 0.585 | 0.000 | 0.000 | -24.848 | 0.000 | -4.331 | -23.175 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -434.289 | 0.000 | 0.000 | 318.545 | 28.313 | 175.857 | 9.205 | 0.000 | 0.051 | 0.000 | 0.000 | -17.112 | 0.000 | -1.621 | -78.949 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -473.362 | 0.000 | 0.000 | 316.820 | 28.313 | 175.857 | 8.987 | 0.000 | 0.050 | 0.000 | 0.000 | -17.672 | 0.000 | -1.639 | -37.354 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -603.649 | 0.000 | 0.000 | 28.651 | 13.339 | 540.650 | 22.151 | 0.000 | 0.044 | 11.448 | 0.000 | -11.166 | 0.000 | -1.467 | -0.001 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.957 | -84.091 | 0.000 | 0.000 | 31.364 | 15.012 | 0.000 | 20.905 | 0.000 | 0.047 | 29.517 | 0.000 | -12.478 | 0.000 | -1.234 | -0.001 |
Total Facility | 178.242 | -736.475 | 3.429 | -4074.905 | 0.000 | 0.000 | 2008.887 | 603.416 | 2434.967 | 893.560 | 0.000 | 3.940 | 44.075 | 0.000 | -563.380 | 0.000 | -85.968 | -709.787 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 27-OCT-21:00 | 0.00 | 0.00 | 0.00 | -17578.31 | 0.00 | 0.00 | 5924.40 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5712.76 |
RETAIL_1_FLR_1 | 04-OCT-12:10 | 0.00 | 0.00 | 0.00 | -3981.51 | 0.00 | 0.00 | 150.60 | 142.31 | 252.59 | 5778.29 | 0.00 | 1.46 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2343.74 |
RETAIL_2_FLR_1 | 18-AUG-21:00 | 0.00 | 0.00 | 0.00 | -2044.16 | 0.00 | 0.00 | 697.61 | 527.34 | 752.15 | 0.00 | 0.00 | 1.13 | 65.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 18-AUG-20:00 | 0.00 | 0.00 | 0.00 | -1705.12 | 0.00 | 0.00 | 129.08 | 684.18 | 839.45 | 0.00 | 0.00 | 5.58 | 46.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 24-AUG-19:30 | 0.00 | 0.00 | 0.00 | -752.52 | 0.00 | 0.00 | 100.36 | 152.61 | 242.16 | 0.00 | 0.00 | 6.79 | 250.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 24-AUG-19:30 | 0.00 | 0.00 | 0.00 | -40870.43 | 0.00 | 0.00 | 389.07 | 400.68 | 44299.38 | 0.00 | 0.00 | 14.26 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4232.96 |
CAFE_FLR_1 | 30-SEP-12:40 | 0.00 | 0.00 | 0.00 | -14031.96 | 0.00 | 0.00 | 2968.70 | 96.16 | 355.63 | 15572.18 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -23.91 | -4936.80 |
LOBBY_FLR_1 | 04-AUG-21:10 | 0.00 | 0.00 | 0.00 | -42010.90 | 0.00 | 0.00 | 26439.90 | 7096.92 | 7389.94 | 851.45 | 0.00 | 136.50 | 96.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 12-JUL-18:02 | 0.00 | -11688.88 | 0.00 | -757.78 | 0.00 | 0.00 | 335.49 | 422.72 | 516.26 | 6374.16 | 0.00 | 18.13 | 4779.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 29-MAY-18:31 | 0.00 | -12182.17 | 0.00 | -902.06 | 0.00 | 0.00 | 245.88 | 474.90 | 516.20 | 2388.19 | 0.00 | 0.59 | 9458.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 04-OCT-12:10 | 0.00 | -52022.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1587.99 | 5097.90 | 68168.87 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -79.95 | -22752.45 |
ROOM_4_MULT19_FLR_3 | 30-MAY-08:21 | 0.00 | -64598.62 | 0.00 | -10995.87 | 0.00 | 0.00 | 1615.94 | 2496.10 | 8433.45 | 12985.71 | 0.00 | 73.42 | 49989.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 23-JUN-08:61 | 0.00 | -10872.81 | 0.00 | -768.86 | 0.00 | 0.00 | 87.14 | 208.98 | 453.05 | 7594.57 | 0.00 | 25.04 | 3272.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 30-MAY-08:62 | 0.00 | -12243.15 | 0.00 | -1075.53 | 0.00 | 0.00 | 58.79 | 208.96 | 452.99 | 8708.89 | 0.00 | 0.00 | 3901.24 | 0.00 | -0.00 | 0.00 | -12.20 | 0.00 |
CORRIDOR_FLR_3 | 24-AUG-19:30 | 0.00 | 0.00 | 0.00 | -9538.47 | 0.00 | 0.00 | 4083.46 | 4640.01 | 0.00 | 262.78 | 0.00 | 34.80 | 517.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 15-AUG-18:02 | 0.00 | -3107.54 | 0.00 | -189.15 | 0.00 | 0.00 | 83.87 | 105.68 | 129.07 | 1111.50 | 0.00 | 5.99 | 1860.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 29-MAY-18:31 | 0.00 | -3264.38 | 0.00 | -230.91 | 0.00 | 0.00 | 59.88 | 118.73 | 129.05 | 586.33 | 0.00 | 0.00 | 2601.74 | 0.00 | -0.00 | 0.00 | -0.44 | 0.00 |
ROOM_3_MULT9_FLR_6 | 16-AUG-15:02 | 0.00 | -14682.90 | 0.00 | -1226.28 | 0.00 | 0.00 | 529.35 | 188.10 | 603.86 | 5532.74 | 0.00 | 69.18 | 8985.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 04-AUG-21:20 | 0.00 | 0.00 | 0.00 | -23347.70 | 0.00 | 0.00 | 15638.65 | 1842.08 | 6747.90 | 349.35 | 0.00 | 27.65 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1257.93 |
DINING_FLR_6 | 04-AUG-21:20 | 0.00 | 0.00 | 0.00 | -24579.16 | 0.00 | 0.00 | 15631.28 | 1842.08 | 6747.90 | 337.09 | 0.00 | 27.64 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6.84 |
KITCHEN_FLR_6 | 01-JUN-18:02 | 0.00 | 0.00 | 0.00 | -31663.55 | 0.00 | 0.00 | 1011.24 | 969.63 | 21452.40 | 637.21 | 0.00 | 11.64 | 7581.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 11-JUL-15:07 | 0.00 | 0.00 | 0.00 | -6497.30 | 0.00 | 0.00 | 771.14 | 341.02 | 0.00 | 1708.96 | 0.00 | 15.11 | 3661.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-AUG-18:02 | 0.00 | -153296.52 | 0.00 | -200099.37 | 0.00 | 0.00 | 73889.56 | 42173.89 | 121562.63 | 21842.06 | 0.00 | 598.27 | 93329.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 02-JAN-07:10 | 0.00 | 0.00 | 1157.23 | 0.00 | 0.00 | 0.00 | 357.95 | 284.62 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1301.48 | 0.00 | -110.93 | -820.39 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 02-JAN-15:00 | 0.00 | 0.00 | 463.93 | 0.00 | 0.00 | 0.00 | 43.84 | 190.05 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -82.16 | -924.94 |
STORAGE_FLR_1 | 06-FEB-16:00 | 0.00 | 0.00 | 415.76 | 0.00 | 0.00 | 0.00 | 50.59 | 42.39 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -48.09 | -549.87 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 08-JAN-15:40 | 0.00 | 0.00 | 10.30 | 0.00 | 0.00 | 0.00 | 2352.28 | 226.49 | 304.82 | 0.00 | 0.00 | 0.00 | 203.97 | 0.00 | -2936.98 | 0.00 | -160.88 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 02-JAN-09:01 | 9522.95 | 303.10 | 0.00 | -303.10 | 0.00 | 0.00 | 108.88 | 208.98 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -84.95 | 0.00 | -234.90 | -9974.01 |
ROOM_2_FLR_3 | 06-FEB-09:01 | 9590.14 | 297.07 | 0.00 | -297.07 | 0.00 | 0.00 | 108.89 | 208.96 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2022.93 | 0.00 | -242.02 | -8096.03 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 06-FEB-16:01 | 53938.18 | 3812.24 | 0.00 | -3812.24 | 0.00 | 0.00 | 5585.66 | 1588.43 | 5099.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11812.32 | 0.00 | -1052.81 | -53346.42 |
ROOM_5_FLR_3 | 14-JAN-16:02 | 9326.99 | 301.31 | 0.00 | -301.31 | 0.00 | 0.00 | 163.33 | 156.74 | 305.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2316.82 | 0.00 | -197.40 | -7438.38 |
ROOM_6_FLR_3 | 06-FEB-16:01 | 9347.72 | 298.01 | 0.00 | -298.01 | 0.00 | 0.00 | 293.98 | 132.97 | 273.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2127.55 | 0.00 | -200.18 | -7720.86 |
CORRIDOR_FLR_3 | 14-JAN-16:15 | 0.00 | 0.00 | 3891.37 | 0.00 | 0.00 | 0.00 | 2078.69 | 1288.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3198.65 | 0.00 | -252.73 | -3807.58 |
ROOM_1_FLR_6 | 14-JAN-16:02 | 2846.48 | 76.29 | 0.00 | -76.29 | 0.00 | 0.00 | 40.83 | 39.19 | 76.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -567.63 | 0.00 | -49.57 | -2385.68 |
ROOM_2_FLR_6 | 06-FEB-09:01 | 2859.76 | 74.94 | 0.00 | -74.94 | 0.00 | 0.00 | 27.22 | 52.24 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -508.71 | 0.00 | -60.70 | -2483.06 |
ROOM_3_MULT9_FLR_6 | 14-JAN-16:02 | 13442.27 | 484.45 | 0.00 | -484.45 | 0.00 | 0.00 | 367.49 | 221.70 | 673.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2666.58 | 0.00 | -227.86 | -11810.55 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 02-JAN-07:15 | 0.00 | 0.00 | 2515.90 | 0.00 | 0.00 | 0.00 | 733.32 | 682.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1694.55 | 0.00 | -137.74 | -2098.98 |
Total Facility | 14-JAN-16:02 | 37213.42 | 78581.13 | 7120.58 | -78581.13 | 0.00 | 0.00 | 36363.79 | 14412.26 | 78232.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -54655.55 | 0.00 | -5023.97 | -113663.17 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 20.8436 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 20.7354 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6516 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6516 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0802 | 2.0802 | 1.1628 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3521 | 0.3521 | 0.1968 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2173 | 0.2173 | 0.1215 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1839 | 0.1839 | 0.1028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0989 | 0.0989 | 0.0553 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2559 | 3.2559 | 1.8201 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4993 | 1.4993 | 0.8381 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.6789 | 4.6789 | 2.6155 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2372 | 1.2372 | 0.6916 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1315 | 2.1315 | 1.1915 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2373 | 2.2373 | 1.2507 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1746 | 2.1746 | 1.2156 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6964 | 0.6964 | 0.3893 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 20.8436 | 20.7354 | 20.8436 | 11.6516 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1628 | 1.1628 | 1.1628 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1968 | 0.1968 | 0.1968 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1215 | 0.1215 | 0.1215 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1028 | 0.1028 | 0.1028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0553 | 0.0553 | 0.0553 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8201 | 1.8201 | 1.8201 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8381 | 0.8381 | 0.8381 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6155 | 2.6155 | 2.6155 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6916 | 0.6916 | 0.6916 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1915 | 1.1915 | 1.1915 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2507 | 1.2507 | 1.2507 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2156 | 1.2156 | 1.2156 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3893 | 0.3893 | 0.3893 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6516 | 11.6516 | 11.6516 | 11.6516 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.33 |
Number of hours cooling loads not met | 114.50 |
Number of hours not met | 114.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 884.76 | 232046.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1150.62 | 196240.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 603.42 | 50471.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 174.22 | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 952.41 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 22.46 | 1283.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 550.32 | 36355.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 120.83 | 7534.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 188.60 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4738.76 | 1132.48 | 136843.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Other | 0.00 | 38393.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.72 | 1320.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 21.07 | 719.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1772.02 | 5691.35 |
Natural Gas | 1788.84 | 3806.08 |
Additional | 0.00 | 0.00 |
Total | 3560.86 | 9497.43 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 53.19 |
Space Heating | 0.00 |
Space Cooling | 101.42 |
Fans (All) | 48.51 |
Service Water Heating | 43.18 |
Receptacle Equipment | 152.32 |
Miscellaneous (All) | 501.65 |
Subtotal | 501.65 |
Natural Gas [MJ/m2] | |
Space Heating | 77.98 |
Service Water Heating | 99.82 |
Miscellaneous (All) | 335.48 |
Subtotal | 335.48 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.35 |
Space Heating | 9.32 |
Space Cooling | 12.12 |
Fans (All) | 5.79 |
Service Water Heating | 17.08 |
Receptacle Equipment | 37.03 |
Miscellaneous | 12.31 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2398. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 2482. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8732.33 | 27.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7568.83 | 1191.17 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8734.00 | 26.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8712.00 | 48.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7568.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1191.17 | 0.00 | 0.00 | 0.00 |
Average | 8701.23 | 58.77 | 0.00 | 0.00 | 0.00 |
Sum | 191427.17 | 1292.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4150.50 | 3.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4143.50 | 10.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 10.50 | 0.00 | 0.00 | 0.00 |
Average | 288886.41 | 0.64 | 0.00 | 0.00 | 0.00 |
Sum | 6355501.00 | 14.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8638.00 | 122.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 7861.67 | 898.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 7831.33 | 928.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8758.00 | 2.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8503.33 | 256.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 6997.33 | 1762.67 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8602.50 | 157.50 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8758.17 | 1.83 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8506.00 | 254.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8741.83 | 18.17 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8753.33 | 6.67 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8439.67 | 320.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8747.83 | 12.17 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 7726.83 | 1033.17 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 7819.83 | 940.17 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8569.17 | 190.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 6997.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1762.67 | 0.00 | 0.00 | 0.00 |
Average | 8446.13 | 313.87 | 0.00 | 0.00 | 0.00 |
Sum | 185814.83 | 6905.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 57846.00 | 1310.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 600361.17 | 110055.83 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1787271.67 | 328157.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4041.17 | 112.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4081.33 | 72.67 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4069.67 | 84.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100038.33 | 319.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4006.00 | 148.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1033677.33 | 212037.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1050821.83 | 194893.17 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 106611.17 | 1657.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1787271.67 | 328157.33 | 0.00 | 0.00 | 0.00 |
Average | 250302.98 | 38584.06 | 0.00 | 0.00 | 0.00 |
Sum | 5506665.67 | 848849.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:50
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Environment
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Environment
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.277965E+11 | 12233.89 | 20-JAN-21:00 | 3.30 | 2.32 | 0.745129E+10 | 4635.67 | 31-JAN-22:10 | -2.8 | -5.6 |
February | 0.235453E+11 | 12016.15 | 01-FEB-21:00 | 5.60 | 3.16 | 0.644487E+10 | 4583.99 | 01-FEB-22:10 | 4.90 | 2.79 |
March | 0.249571E+11 | 11335.68 | 03-MAR-21:00 | 11.10 | 6.67 | 0.688631E+10 | 4310.48 | 01-MAR-22:10 | 11.10 | 6.67 |
April | 0.237464E+11 | 11850.43 | 08-APR-10:33 | 23.90 | 16.13 | 0.649197E+10 | 4178.92 | 13-APR-21:10 | 5.00 | 4.72 |
May | 0.245312E+11 | 11967.36 | 29-MAY-10:33 | 27.43 | 17.92 | 0.660559E+10 | 4103.75 | 03-MAY-22:10 | 27.43 | 17.92 |
June | 0.259638E+11 | 13800.67 | 22-JUN-18:03 | 28.72 | 17.28 | 0.671317E+10 | 4319.80 | 30-JUN-22:10 | 20.00 | 18.86 |
July | 0.289951E+11 | 13920.50 | 11-JUL-17:09 | 28.12 | 17.29 | 0.722628E+10 | 4511.26 | 28-JUL-22:10 | 24.32 | 20.84 |
August | 0.309583E+11 | 15495.76 | 24-AUG-19:30 | 28.30 | 16.24 | 0.761932E+10 | 4732.93 | 25-AUG-22:10 | 20.92 | 14.50 |
September | 0.313842E+11 | 15276.08 | 22-SEP-21:00 | 18.90 | 17.11 | 0.771523E+10 | 4837.09 | 28-SEP-21:10 | 16.42 | 11.03 |
October | 0.337129E+11 | 17577.41 | 27-OCT-21:00 | 7.20 | 3.64 | 0.812842E+10 | 4837.08 | 04-OCT-22:10 | 7.20 | 3.64 |
November | 0.316349E+11 | 17229.19 | 03-NOV-21:00 | 12.80 | 10.14 | 0.784169E+10 | 4837.04 | 03-NOV-23:19 | 12.97 | 10.62 |
December | 0.303309E+11 | 15513.35 | 01-DEC-22:00 | 1.10 | -2.2 | 0.791012E+10 | 4837.06 | 19-DEC-23:10 | 4.60 | 3.31 |
Annual Sum or Average | 0.337557E+12 | 0.870343E+11 | ||||||||
Minimum of Months | 0.235453E+11 | 11335.68 | 1.10 | -2.2 | 0.644487E+10 | 4103.75 | -2.8 | -5.6 | ||
Maximum of Months | 0.337129E+11 | 17577.41 | 28.72 | 17.92 | 0.812842E+10 | 4837.09 | 27.43 | 20.84 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110462E+10 | 2422.95 | 17-JAN-13:10 | 10.18 | 5.51 | 0.623890E+09 | 364.18 | 19-JAN-22:19 | 5.60 | 1.07 |
February | 0.138520E+10 | 2170.79 | 02-FEB-13:40 | 5.97 | -0.5 | 0.566917E+09 | 364.14 | 06-FEB-05:10 | -13.2 | -14.5 |
March | 0.238265E+10 | 2978.21 | 03-MAR-13:20 | 14.60 | 8.23 | 0.636395E+09 | 406.50 | 03-MAR-22:30 | 10.30 | 6.29 |
April | 0.292599E+10 | 3139.42 | 08-APR-12:30 | 23.60 | 16.18 | 0.624034E+09 | 451.92 | 07-APR-21:30 | 23.60 | 16.18 |
May | 0.391484E+10 | 2482.87 | 31-MAY-10:35 | 25.60 | 19.79 | 0.659228E+09 | 457.17 | 31-MAY-21:40 | 20.13 | 17.44 |
June | 0.462840E+10 | 2707.41 | 19-JUN-13:20 | 34.80 | 23.85 | 0.694530E+09 | 486.43 | 19-JUN-21:30 | 28.35 | 20.38 |
July | 0.523377E+10 | 2941.11 | 08-JUL-12:10 | 32.02 | 26.06 | 0.749566E+09 | 486.54 | 10-JUL-21:30 | 26.95 | 19.92 |
August | 0.570759E+10 | 3616.68 | 22-AUG-12:40 | 30.40 | 18.62 | 0.772537E+09 | 491.82 | 04-AUG-21:19 | 30.40 | 18.62 |
September | 0.483710E+10 | 3793.76 | 07-SEP-12:40 | 26.50 | 22.82 | 0.694913E+09 | 491.80 | 01-SEP-21:30 | 26.50 | 22.82 |
October | 0.470524E+10 | 3981.32 | 04-OCT-12:10 | 24.50 | 18.64 | 0.694467E+09 | 464.76 | 04-OCT-21:30 | 16.95 | 15.74 |
November | 0.228943E+10 | 3087.30 | 02-NOV-12:40 | 15.40 | 8.14 | 0.611797E+09 | 414.78 | 03-NOV-21:30 | 12.80 | 10.23 |
December | 0.153535E+10 | 2948.09 | 17-DEC-12:50 | 12.20 | 4.87 | 0.626635E+09 | 364.32 | 18-DEC-22:19 | 2.20 | 0.87 |
Annual Sum or Average | 0.406502E+11 | 0.795491E+10 | ||||||||
Minimum of Months | 0.110462E+10 | 2170.79 | 5.97 | -0.5 | 0.566917E+09 | 364.14 | -13.2 | -14.5 | ||
Maximum of Months | 0.570759E+10 | 3981.32 | 34.80 | 26.06 | 0.772537E+09 | 491.82 | 30.40 | 22.82 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.220383E+10 | 1170.78 | 19-JAN-21:00 | 3.90 | 0.79 | 0.763517E+09 | 514.11 | 19-JAN-23:10 | 5.60 | 1.07 |
February | 0.205950E+10 | 1162.53 | 02-FEB-21:00 | -1.7 | -5.7 | 0.697218E+09 | 510.79 | 02-FEB-22:40 | -2.6 | -6.2 |
March | 0.258094E+10 | 1286.70 | 03-MAR-21:00 | 11.10 | 6.67 | 0.813125E+09 | 546.01 | 03-MAR-23:10 | 9.82 | 6.12 |
April | 0.268469E+10 | 1446.35 | 07-APR-21:00 | 19.40 | 13.83 | 0.813581E+09 | 569.55 | 07-APR-22:10 | 18.22 | 13.39 |
May | 0.302208E+10 | 1726.30 | 31-MAY-21:00 | 20.60 | 17.62 | 0.878432E+09 | 569.55 | 31-MAY-22:10 | 19.78 | 17.36 |
June | 0.326289E+10 | 1943.07 | 19-JUN-21:00 | 28.90 | 20.74 | 0.900423E+09 | 569.55 | 20-JUN-22:10 | 20.60 | 17.54 |
July | 0.356685E+10 | 1983.38 | 07-JUL-21:00 | 25.60 | 23.22 | 0.942809E+09 | 569.55 | 11-JUL-22:10 | 22.62 | 17.84 |
August | 0.370175E+10 | 2044.12 | 18-AUG-21:00 | 25.00 | 17.57 | 0.955061E+09 | 569.65 | 18-AUG-02:20 | 25.00 | 17.57 |
September | 0.323146E+10 | 1959.23 | 01-SEP-21:00 | 26.70 | 18.23 | 0.893706E+09 | 569.55 | 06-SEP-22:10 | 22.20 | 20.63 |
October | 0.312513E+10 | 1713.39 | 05-OCT-21:00 | 18.90 | 17.80 | 0.902115E+09 | 569.55 | 04-OCT-22:10 | 18.90 | 17.80 |
November | 0.252055E+10 | 1326.94 | 03-NOV-20:00 | 12.80 | 10.92 | 0.787278E+09 | 559.07 | 03-NOV-22:10 | 12.80 | 10.38 |
December | 0.238415E+10 | 1188.30 | 18-DEC-21:00 | 2.80 | 1.39 | 0.782008E+09 | 519.46 | 18-DEC-23:10 | 2.30 | 0.67 |
Annual Sum or Average | 0.343438E+11 | 0.101293E+11 | ||||||||
Minimum of Months | 0.205950E+10 | 1162.53 | -1.7 | -5.7 | 0.697218E+09 | 510.79 | -2.6 | -6.2 | ||
Maximum of Months | 0.370175E+10 | 2044.12 | 28.90 | 23.22 | 0.955061E+09 | 569.65 | 25.00 | 20.63 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.706143E+09 | 829.36 | 19-JAN-21:00 | 3.90 | 0.79 | 0.152071E+09 | 93.89 | 19-JAN-22:10 | 5.60 | 1.07 |
February | 0.614952E+09 | 811.32 | 24-FEB-21:00 | 1.10 | -2.8 | 0.137434E+09 | 92.80 | 24-FEB-22:10 | 0.32 | -3.7 |
March | 0.145774E+10 | 923.00 | 28-MAR-10:33 | 12.23 | 7.80 | 0.154972E+09 | 99.90 | 28-MAR-21:10 | 8.22 | 5.85 |
April | 0.189454E+10 | 1123.37 | 08-APR-10:33 | 23.90 | 16.13 | 0.156237E+09 | 108.83 | 10-APR-21:19 | 12.57 | 5.94 |
May | 0.237308E+10 | 1251.00 | 31-MAY-10:35 | 25.60 | 19.79 | 0.174474E+09 | 117.93 | 31-MAY-21:19 | 20.37 | 17.53 |
June | 0.265920E+10 | 1404.95 | 20-JUN-21:00 | 21.10 | 16.91 | 0.185717E+09 | 120.45 | 20-JUN-21:19 | 20.93 | 17.07 |
July | 0.294942E+10 | 1652.24 | 10-JUL-21:00 | 27.20 | 20.22 | 0.198051E+09 | 120.45 | 11-JUL-21:19 | 22.80 | 17.52 |
August | 0.298887E+10 | 1705.12 | 18-AUG-20:00 | 26.10 | 18.80 | 0.199695E+09 | 120.46 | 30-AUG-21:19 | 22.43 | 18.00 |
September | 0.258549E+10 | 1364.45 | 01-SEP-21:00 | 26.70 | 18.23 | 0.182655E+09 | 120.45 | 01-SEP-21:10 | 26.60 | 18.09 |
October | 0.238049E+10 | 1166.11 | 05-OCT-10:33 | 21.13 | 17.47 | 0.176146E+09 | 114.60 | 05-OCT-21:19 | 18.90 | 17.68 |
November | 0.161337E+10 | 1003.83 | 04-NOV-10:33 | 16.83 | 11.51 | 0.152771E+09 | 103.75 | 03-NOV-21:19 | 16.83 | 11.51 |
December | 0.109178E+10 | 834.78 | 19-DEC-21:00 | 8.30 | 3.94 | 0.152374E+09 | 94.23 | 19-DEC-22:10 | 5.40 | 2.50 |
Annual Sum or Average | 0.233151E+11 | 0.202260E+10 | ||||||||
Minimum of Months | 0.614952E+09 | 811.32 | 1.10 | -2.8 | 0.137434E+09 | 92.80 | 0.32 | -3.7 | ||
Maximum of Months | 0.298887E+10 | 1705.12 | 27.20 | 20.22 | 0.199695E+09 | 120.46 | 26.60 | 18.09 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186312E+09 | 415.76 | 19-JAN-21:00 | 3.90 | 0.79 | 0.116700E+09 | 69.42 | 19-JAN-23:10 | 5.60 | 1.07 |
February | 0.161827E+09 | 355.99 | 24-FEB-22:00 | 0.60 | -3.5 | 0.105501E+09 | 68.57 | 22-FEB-03:00 | 0.60 | -3.5 |
March | 0.612559E+09 | 489.59 | 28-MAR-10:33 | 12.23 | 7.80 | 0.118011E+09 | 73.96 | 03-MAR-23:10 | 12.23 | 7.80 |
April | 0.934811E+09 | 604.82 | 08-APR-10:33 | 23.90 | 16.13 | 0.118258E+09 | 80.70 | 10-APR-21:40 | 11.83 | 5.31 |
May | 0.124691E+10 | 670.53 | 31-MAY-10:35 | 25.60 | 19.79 | 0.131687E+09 | 87.81 | 31-MAY-22:10 | 19.78 | 17.36 |
June | 0.140159E+10 | 737.74 | 22-JUN-18:03 | 28.72 | 17.28 | 0.140520E+09 | 91.58 | 19-JUN-22:10 | 28.72 | 17.28 |
July | 0.154651E+10 | 748.94 | 11-JUL-17:09 | 28.12 | 17.29 | 0.150444E+09 | 92.66 | 10-JUL-21:19 | 28.12 | 17.29 |
August | 0.155967E+10 | 752.57 | 24-AUG-19:30 | 28.30 | 16.24 | 0.151782E+09 | 92.66 | 18-AUG-21:00 | 28.30 | 16.24 |
September | 0.136130E+10 | 723.17 | 01-SEP-17:01 | 27.80 | 17.38 | 0.138050E+09 | 91.52 | 01-SEP-21:10 | 26.60 | 18.09 |
October | 0.124980E+10 | 623.20 | 05-OCT-10:33 | 21.13 | 17.47 | 0.132914E+09 | 85.41 | 05-OCT-22:10 | 18.98 | 17.65 |
November | 0.730731E+09 | 535.33 | 04-NOV-10:33 | 16.83 | 11.51 | 0.115815E+09 | 77.14 | 03-NOV-22:10 | 16.83 | 11.51 |
December | 0.341884E+09 | 423.55 | 19-DEC-21:00 | 8.30 | 3.94 | 0.116720E+09 | 69.71 | 19-DEC-23:10 | 4.60 | 3.31 |
Annual Sum or Average | 0.113339E+11 | 0.153640E+10 | ||||||||
Minimum of Months | 0.161827E+09 | 355.99 | 0.60 | -3.5 | 0.105501E+09 | 68.57 | 0.60 | -3.5 | ||
Maximum of Months | 0.155967E+10 | 752.57 | 28.72 | 19.79 | 0.151782E+09 | 92.66 | 28.72 | 18.09 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.477901E+11 | 36560.90 | 19-JAN-21:00 | 3.90 | 0.79 | 0.569998E+09 | 381.61 | 20-JAN-22:10 | 3.72 | 3.02 |
February | 0.432189E+11 | 36466.59 | 17-FEB-21:00 | 1.10 | -0.8 | 0.515657E+09 | 381.60 | 03-FEB-22:10 | 1.10 | -0.8 |
March | 0.493260E+11 | 37263.65 | 03-MAR-21:00 | 11.10 | 6.67 | 0.576216E+09 | 381.63 | 28-MAR-21:10 | 8.22 | 5.85 |
April | 0.486873E+11 | 38041.22 | 07-APR-20:00 | 21.70 | 14.73 | 0.558554E+09 | 381.66 | 11-APR-21:19 | 9.03 | 1.57 |
May | 0.517875E+11 | 38433.30 | 30-MAY-20:00 | 20.00 | 15.55 | 0.580203E+09 | 381.69 | 12-MAY-21:10 | 20.00 | 15.55 |
June | 0.513723E+11 | 39040.60 | 01-JUN-19:13 | 26.27 | 15.74 | 0.564431E+09 | 382.20 | 22-JUN-21:10 | 25.92 | 16.12 |
July | 0.535717E+11 | 38710.21 | 10-JUL-20:00 | 28.30 | 20.24 | 0.582541E+09 | 381.69 | 21-JUL-21:10 | 25.60 | 23.68 |
August | 0.539903E+11 | 40843.41 | 24-AUG-19:30 | 28.30 | 16.24 | 0.584749E+09 | 383.01 | 24-AUG-21:10 | 25.40 | 15.20 |
September | 0.508780E+11 | 38492.16 | 14-SEP-19:30 | 26.65 | 17.03 | 0.563239E+09 | 392.20 | 01-SEP-21:10 | 26.65 | 17.03 |
October | 0.514210E+11 | 38068.91 | 04-OCT-20:00 | 18.90 | 16.06 | 0.580191E+09 | 381.71 | 26-OCT-21:10 | 8.22 | 3.60 |
November | 0.478286E+11 | 37351.45 | 03-NOV-20:00 | 12.80 | 10.92 | 0.557109E+09 | 381.72 | 03-NOV-21:10 | 12.80 | 10.17 |
December | 0.482666E+11 | 36590.45 | 20-DEC-21:00 | 5.00 | 1.74 | 0.572306E+09 | 381.62 | 22-DEC-22:10 | 2.20 | 1.31 |
Annual Sum or Average | 0.598138E+12 | 0.680519E+10 | ||||||||
Minimum of Months | 0.432189E+11 | 36466.59 | 1.10 | -0.8 | 0.515657E+09 | 381.60 | 1.10 | -0.8 | ||
Maximum of Months | 0.539903E+11 | 40843.41 | 28.30 | 20.24 | 0.584749E+09 | 392.20 | 26.65 | 23.68 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148659E+11 | 9959.43 | 17-JAN-13:00 | 10.00 | 5.56 | 0.878541E+10 | 6029.86 | 19-JAN-22:40 | 5.60 | 1.07 |
February | 0.146370E+11 | 9887.98 | 20-FEB-13:00 | 9.40 | 4.36 | 0.808134E+10 | 5967.28 | 22-FEB-22:40 | 2.20 | -0.9 |
March | 0.179713E+11 | 11547.53 | 03-MAR-13:10 | 14.50 | 8.14 | 0.939050E+10 | 6438.65 | 03-MAR-22:40 | 10.20 | 6.23 |
April | 0.184326E+11 | 12122.22 | 08-APR-12:20 | 23.87 | 16.21 | 0.928134E+10 | 6462.61 | 07-APR-22:10 | 23.87 | 16.21 |
May | 0.205951E+11 | 10697.89 | 29-MAY-10:33 | 27.43 | 17.92 | 0.994327E+10 | 6462.77 | 31-MAY-22:10 | 19.78 | 17.36 |
June | 0.218700E+11 | 11587.08 | 19-JUN-21:10 | 28.72 | 20.62 | 0.101165E+11 | 6462.77 | 20-JUN-22:10 | 20.60 | 17.54 |
July | 0.239928E+11 | 11505.01 | 10-JUL-21:10 | 27.12 | 20.12 | 0.106097E+11 | 6462.73 | 11-JUL-22:10 | 22.62 | 17.84 |
August | 0.254663E+11 | 12387.70 | 13-AUG-12:00 | 30.60 | 18.83 | 0.108014E+11 | 6464.46 | 18-AUG-02:20 | 25.60 | 18.81 |
September | 0.227998E+11 | 14032.87 | 30-SEP-12:40 | 20.40 | 12.36 | 0.101464E+11 | 6462.73 | 06-SEP-22:10 | 20.40 | 12.36 |
October | 0.230796E+11 | 13764.78 | 04-OCT-12:00 | 24.40 | 18.65 | 0.103777E+11 | 6462.62 | 04-OCT-22:10 | 16.88 | 15.73 |
November | 0.174443E+11 | 12329.02 | 04-NOV-12:30 | 17.80 | 12.61 | 0.902257E+10 | 6460.51 | 02-NOV-22:10 | 17.80 | 12.61 |
December | 0.162237E+11 | 12263.86 | 17-DEC-11:00 | 10.60 | 4.31 | 0.899621E+10 | 6044.20 | 18-DEC-22:40 | 2.20 | 0.72 |
Annual Sum or Average | 0.237378E+12 | 0.115552E+12 | ||||||||
Minimum of Months | 0.146370E+11 | 9887.98 | 9.40 | 4.31 | 0.808134E+10 | 5967.28 | 2.20 | -0.9 | ||
Maximum of Months | 0.254663E+11 | 14032.87 | 30.60 | 20.62 | 0.108014E+11 | 6464.46 | 25.60 | 18.81 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.544480E+11 | 26878.06 | 19-JAN-21:00 | 3.90 | 0.79 | 0.275664E+11 | 18652.22 | 19-JAN-23:10 | 5.60 | 1.07 |
February | 0.505757E+11 | 26598.31 | 02-FEB-21:00 | -1.7 | -5.7 | 0.251920E+11 | 18463.10 | 22-FEB-23:10 | 2.20 | -0.8 |
March | 0.604229E+11 | 29300.49 | 03-MAR-22:20 | 10.40 | 6.34 | 0.291392E+11 | 19183.55 | 15-MAR-21:00 | 8.90 | 2.77 |
April | 0.617723E+11 | 34406.61 | 07-APR-21:10 | 19.22 | 13.77 | 0.288379E+11 | 19186.01 | 07-APR-22:10 | 18.22 | 13.39 |
May | 0.685724E+11 | 36892.29 | 31-MAY-21:10 | 20.48 | 17.58 | 0.308259E+11 | 19186.23 | 31-MAY-22:10 | 19.78 | 17.36 |
June | 0.729755E+11 | 40426.69 | 19-JUN-21:10 | 28.72 | 20.62 | 0.308398E+11 | 19186.24 | 20-JUN-22:10 | 20.60 | 17.54 |
July | 0.794769E+11 | 40992.97 | 10-JUL-21:10 | 27.12 | 20.12 | 0.319854E+11 | 19186.18 | 11-JUL-22:10 | 22.62 | 17.84 |
August | 0.819543E+11 | 42005.26 | 04-AUG-21:10 | 31.55 | 23.93 | 0.322987E+11 | 19189.89 | 18-AUG-02:20 | 25.60 | 18.81 |
September | 0.732343E+11 | 41161.47 | 01-SEP-21:10 | 26.60 | 18.09 | 0.308103E+11 | 19186.18 | 06-SEP-22:10 | 22.20 | 20.63 |
October | 0.718033E+11 | 38211.22 | 05-OCT-21:10 | 18.90 | 17.74 | 0.315324E+11 | 19186.03 | 04-OCT-22:10 | 18.90 | 17.74 |
November | 0.593641E+11 | 31803.53 | 03-NOV-21:10 | 12.80 | 10.17 | 0.283206E+11 | 19183.53 | 01-NOV-21:40 | 12.80 | 10.17 |
December | 0.573386E+11 | 27960.08 | 17-DEC-11:33 | 11.67 | 4.45 | 0.282586E+11 | 18767.38 | 18-DEC-23:10 | 2.30 | 0.67 |
Annual Sum or Average | 0.791938E+12 | 0.355607E+12 | ||||||||
Minimum of Months | 0.505757E+11 | 26598.31 | -1.7 | -5.7 | 0.251920E+11 | 18463.10 | 2.20 | -0.8 | ||
Maximum of Months | 0.819543E+11 | 42005.26 | 31.55 | 23.93 | 0.322987E+11 | 19189.89 | 25.60 | 20.63 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26951406.26 | 2721.14 | 20-JAN-16:02 | 6.93 | 3.71 | 94027009.01 | 56.69 | 03-JAN-04:19 | 6.93 | 3.71 |
February | 52747826.56 | 2766.85 | 14-FEB-16:01 | 0.50 | -3.9 | 85538116.68 | 56.69 | 20-FEB-02:20 | 2.97 | 1.74 |
March | 0.273876E+09 | 2824.30 | 11-MAR-16:01 | 11.20 | 5.40 | 96416068.00 | 56.69 | 27-MAR-21:19 | 13.87 | 10.67 |
April | 0.638048E+09 | 2932.56 | 16-APR-15:01 | 21.60 | 13.95 | 94074441.04 | 56.69 | 08-APR-23:10 | 21.60 | 13.95 |
May | 0.127658E+10 | 3029.21 | 20-MAY-18:02 | 22.02 | 11.72 | 98508555.54 | 56.70 | 31-MAY-22:00 | 19.20 | 17.40 |
June | 0.208857E+10 | 3017.15 | 23-JUN-08:61 | 26.70 | 18.47 | 95886145.18 | 56.70 | 20-JUN-00:40 | 26.70 | 18.47 |
July | 0.252544E+10 | 3111.62 | 12-JUL-18:02 | 25.50 | 21.15 | 99098673.74 | 56.70 | 20-JUL-23:10 | 26.10 | 24.12 |
August | 0.274056E+10 | 3088.05 | 15-AUG-18:02 | 26.42 | 20.41 | 99201645.38 | 56.70 | 17-AUG-00:49 | 26.02 | 25.28 |
September | 0.174606E+10 | 3007.03 | 07-SEP-15:02 | 26.60 | 22.96 | 95597885.84 | 56.70 | 07-SEP-22:49 | 22.88 | 20.86 |
October | 0.118237E+10 | 2839.35 | 04-OCT-15:02 | 23.72 | 19.12 | 98362363.76 | 56.69 | 04-OCT-21:19 | 17.03 | 15.77 |
November | 0.151550E+09 | 2671.85 | 04-NOV-15:01 | 17.30 | 12.80 | 92695503.42 | 56.69 | 03-NOV-00:40 | 17.30 | 12.80 |
December | 34781476.97 | 2750.03 | 18-DEC-16:01 | 5.22 | 2.22 | 94536759.59 | 56.69 | 25-DEC-02:20 | 5.77 | 5.31 |
Annual Sum or Average | 0.127375E+11 | 0.114394E+10 | ||||||||
Minimum of Months | 26951406.26 | 2671.85 | 0.50 | -3.9 | 85538116.68 | 56.69 | 2.97 | 1.74 | ||
Maximum of Months | 0.274056E+10 | 3111.62 | 26.70 | 22.96 | 99201645.38 | 56.70 | 26.70 | 25.28 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9493222.05 | 2400.47 | 20-JAN-16:02 | 6.93 | 3.71 | 93129114.75 | 56.69 | 03-JAN-04:19 | 6.93 | 3.71 |
February | 16012844.27 | 2469.74 | 22-FEB-16:02 | 4.22 | -0.7 | 84366594.93 | 56.69 | 14-FEB-04:19 | 4.22 | -0.7 |
March | 0.128623E+09 | 2705.68 | 11-MAR-16:01 | 11.20 | 5.40 | 95587456.11 | 65.40 | 27-MAR-21:10 | 14.13 | 10.87 |
April | 0.409363E+09 | 3094.93 | 09-APR-18:11 | 14.43 | 12.85 | 94997500.43 | 71.56 | 07-APR-21:40 | 14.43 | 12.85 |
May | 0.950460E+09 | 3271.17 | 29-MAY-18:31 | 24.80 | 18.16 | 0.104182E+09 | 85.65 | 31-MAY-21:10 | 20.48 | 17.58 |
June | 0.162817E+10 | 3100.51 | 23-JUN-08:61 | 26.70 | 18.47 | 0.106734E+09 | 82.29 | 20-JUN-21:30 | 26.70 | 18.47 |
July | 0.224290E+10 | 3167.96 | 03-JUL-18:51 | 24.40 | 21.27 | 0.104385E+09 | 81.37 | 05-JUL-21:30 | 22.50 | 21.72 |
August | 0.230075E+10 | 3012.36 | 15-AUG-18:02 | 26.42 | 20.41 | 0.103720E+09 | 82.12 | 10-AUG-21:10 | 26.42 | 20.41 |
September | 0.115029E+10 | 2965.92 | 03-SEP-08:51 | 22.80 | 14.85 | 0.102895E+09 | 81.82 | 06-SEP-21:10 | 22.70 | 20.80 |
October | 0.582485E+09 | 2872.99 | 24-OCT-15:02 | 21.60 | 19.09 | 0.101331E+09 | 74.17 | 04-OCT-21:40 | 21.60 | 19.09 |
November | 50138081.10 | 2542.49 | 04-NOV-15:01 | 17.30 | 12.80 | 91736785.42 | 56.69 | 03-NOV-03:20 | 17.30 | 12.80 |
December | 9643452.81 | 2407.57 | 17-DEC-16:02 | 9.82 | 4.16 | 93337192.85 | 56.69 | 25-DEC-02:20 | 5.77 | 5.31 |
Annual Sum or Average | 0.947833E+10 | 0.117640E+10 | ||||||||
Minimum of Months | 9493222.05 | 2400.47 | 4.22 | -0.7 | 84366594.93 | 56.69 | 4.22 | -0.7 | ||
Maximum of Months | 0.230075E+10 | 3271.17 | 26.70 | 21.27 | 0.106734E+09 | 85.65 | 26.70 | 21.72 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9005968.85 | 145.74 | 31-JAN-15:20 | -1.5 | -6.0 | 0.00 | 0.00 | 01-JAN-00:10 | -1.5 | -6.0 |
February | 42510333.78 | 351.62 | 20-FEB-13:30 | 9.15 | 4.45 | 0.00 | 0.00 | 01-FEB-00:10 | 9.15 | 4.45 |
March | 0.102513E+09 | 413.56 | 15-MAR-13:15 | 13.50 | 6.64 | 0.00 | 0.00 | 01-MAR-00:10 | 13.50 | 6.64 |
April | 0.192894E+09 | 548.62 | 07-APR-12:30 | 26.15 | 15.90 | 0.00 | 0.00 | 01-APR-00:10 | 26.15 | 15.90 |
May | 0.323386E+09 | 420.31 | 30-MAY-12:50 | 29.90 | 17.93 | 0.00 | 0.00 | 01-MAY-00:10 | 29.90 | 17.93 |
June | 0.493698E+09 | 438.08 | 19-JUN-13:20 | 34.80 | 23.85 | 0.00 | 0.00 | 01-JUN-00:10 | 34.80 | 23.85 |
July | 0.640716E+09 | 465.56 | 10-JUL-13:10 | 32.30 | 20.52 | 0.00 | 0.00 | 01-JUL-00:10 | 32.30 | 20.52 |
August | 0.761599E+09 | 588.89 | 30-AUG-13:00 | 27.20 | 15.60 | 0.00 | 0.00 | 01-AUG-00:10 | 27.20 | 15.60 |
September | 0.586926E+09 | 645.41 | 28-SEP-12:40 | 22.97 | 13.90 | 0.00 | 0.00 | 01-SEP-00:10 | 22.97 | 13.90 |
October | 0.578983E+09 | 684.49 | 04-OCT-12:10 | 24.50 | 18.64 | 0.00 | 0.00 | 01-OCT-00:10 | 24.50 | 18.64 |
November | 0.146757E+09 | 577.38 | 02-NOV-12:50 | 15.50 | 8.17 | 0.00 | 0.00 | 01-NOV-00:10 | 15.50 | 8.17 |
December | 58105407.65 | 395.77 | 17-DEC-13:40 | 12.20 | 5.18 | 0.00 | 0.00 | 01-DEC-00:10 | 12.20 | 5.18 |
Annual Sum or Average | 0.393709E+10 | 0.00 | ||||||||
Minimum of Months | 9005968.85 | 145.74 | -1.5 | -6.0 | 0.00 | 0.00 | -1.5 | -6.0 | ||
Maximum of Months | 0.761599E+09 | 684.49 | 34.80 | 23.85 | 0.00 | 0.00 | 34.80 | 23.85 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33356663.92 | 729.57 | 23-JAN-19:02 | 9.50 | 9.50 | 94799435.84 | 56.69 | 09-JAN-00:20 | 9.50 | 9.50 |
February | 24952171.07 | 759.01 | 18-FEB-09:02 | 5.18 | 1.91 | 85595970.82 | 56.69 | 01-FEB-00:20 | 5.18 | 1.91 |
March | 0.139746E+09 | 811.18 | 03-MAR-19:02 | 12.12 | 7.02 | 96189359.96 | 65.71 | 27-MAR-21:10 | 14.13 | 10.87 |
April | 0.309292E+09 | 946.49 | 07-APR-15:02 | 25.60 | 15.98 | 94536550.47 | 69.52 | 07-APR-21:00 | 18.30 | 13.42 |
May | 0.526935E+09 | 994.68 | 30-MAY-08:21 | 25.55 | 16.31 | 0.101553E+09 | 76.63 | 31-MAY-21:40 | 20.13 | 17.44 |
June | 0.694465E+09 | 994.48 | 23-JUN-08:61 | 26.70 | 18.47 | 0.102393E+09 | 77.71 | 28-JUN-21:40 | 21.50 | 18.92 |
July | 0.895430E+09 | 984.25 | 03-JUL-15:02 | 28.03 | 21.81 | 0.103055E+09 | 77.38 | 25-JUL-21:10 | 22.70 | 20.79 |
August | 0.839805E+09 | 991.20 | 12-AUG-15:02 | 28.72 | 24.51 | 0.102206E+09 | 75.82 | 10-AUG-21:10 | 28.72 | 24.51 |
September | 0.556241E+09 | 979.18 | 01-SEP-18:02 | 27.70 | 17.44 | 0.100487E+09 | 76.57 | 05-SEP-21:10 | 23.90 | 20.42 |
October | 0.359999E+09 | 894.24 | 25-OCT-15:02 | 23.03 | 10.41 | 99310957.43 | 70.97 | 04-OCT-21:00 | 23.03 | 10.41 |
November | 0.154380E+09 | 807.18 | 02-NOV-18:02 | 13.80 | 7.37 | 93001164.42 | 56.69 | 09-NOV-22:49 | 12.20 | 12.20 |
December | 37736357.91 | 762.72 | 10-DEC-09:02 | 4.50 | 1.71 | 95024687.64 | 56.69 | 01-DEC-01:19 | 4.50 | 1.71 |
Annual Sum or Average | 0.457234E+10 | 0.116815E+10 | ||||||||
Minimum of Months | 24952171.07 | 729.57 | 4.50 | 1.71 | 85595970.82 | 56.69 | 4.50 | 1.71 | ||
Maximum of Months | 0.895430E+09 | 994.68 | 28.72 | 24.51 | 0.103055E+09 | 77.71 | 28.72 | 24.51 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 37416076.30 | 2284.89 | 20-JAN-09:02 | 5.40 | 0.62 | 94016325.87 | 56.69 | 03-JAN-04:19 | 5.40 | 0.62 |
February | 57984792.95 | 2562.22 | 25-FEB-09:01 | -2.0 | -5.5 | 85679198.15 | 56.69 | 17-FEB-04:19 | -2.0 | -5.5 |
March | 0.241582E+09 | 2550.27 | 11-MAR-16:01 | 11.20 | 5.40 | 96532752.07 | 56.69 | 27-MAR-21:19 | 13.87 | 10.67 |
April | 0.645334E+09 | 2677.25 | 08-APR-08:62 | 20.28 | 15.08 | 94308749.45 | 56.69 | 27-APR-21:10 | 14.40 | 13.08 |
May | 0.131331E+10 | 2754.93 | 29-MAY-08:62 | 24.27 | 16.71 | 98647661.43 | 56.69 | 30-MAY-22:40 | 18.50 | 15.37 |
June | 0.197518E+10 | 2910.35 | 23-JUN-08:61 | 26.70 | 18.47 | 95935820.42 | 56.69 | 22-JUN-22:40 | 26.70 | 18.47 |
July | 0.249332E+10 | 2872.29 | 13-JUL-08:62 | 27.07 | 22.43 | 99120857.08 | 56.70 | 13-JUL-23:00 | 26.70 | 22.05 |
August | 0.271656E+10 | 2900.60 | 22-AUG-08:62 | 26.88 | 18.45 | 99234054.84 | 56.70 | 05-AUG-02:39 | 26.88 | 18.45 |
September | 0.176001E+10 | 2806.63 | 06-SEP-08:62 | 24.18 | 18.63 | 95682987.34 | 56.70 | 06-SEP-22:00 | 22.20 | 20.63 |
October | 0.113596E+10 | 2670.80 | 02-OCT-15:02 | 22.88 | 16.78 | 98498715.43 | 56.69 | 02-OCT-22:40 | 15.97 | 15.02 |
November | 0.199891E+09 | 2502.87 | 04-NOV-15:01 | 17.30 | 12.80 | 92928548.61 | 56.69 | 03-NOV-03:20 | 17.30 | 12.80 |
December | 61625756.18 | 2376.18 | 02-DEC-09:01 | 2.38 | -1.7 | 94586067.00 | 56.69 | 25-DEC-02:20 | 5.77 | 5.31 |
Annual Sum or Average | 0.126382E+11 | 0.114517E+10 | ||||||||
Minimum of Months | 37416076.30 | 2284.89 | -2.0 | -5.5 | 85679198.15 | 56.69 | -2.0 | -5.5 | ||
Maximum of Months | 0.271656E+10 | 2910.35 | 27.07 | 22.43 | 99234054.84 | 56.70 | 26.88 | 22.05 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8885291.10 | 1314.16 | 19-JAN-09:01 | 4.97 | 3.19 | 93103098.71 | 56.69 | 03-JAN-04:19 | 4.97 | 3.19 |
February | 15183616.30 | 2334.97 | 25-FEB-09:01 | -2.0 | -5.5 | 84412674.36 | 56.69 | 10-FEB-04:19 | -2.0 | -5.5 |
March | 0.107308E+09 | 2321.81 | 26-MAR-08:62 | 8.68 | 7.99 | 95432029.75 | 58.99 | 27-MAR-21:10 | 14.13 | 10.87 |
April | 0.432591E+09 | 2982.25 | 08-APR-08:51 | 21.70 | 15.33 | 94759716.84 | 70.37 | 07-APR-21:40 | 21.70 | 15.33 |
May | 0.101026E+10 | 3330.19 | 30-MAY-08:62 | 25.18 | 15.91 | 0.103155E+09 | 80.56 | 31-MAY-21:30 | 20.25 | 17.49 |
June | 0.155165E+10 | 3229.63 | 26-JUN-08:32 | 24.63 | 19.00 | 0.104640E+09 | 79.19 | 20-JUN-21:19 | 24.63 | 19.00 |
July | 0.218999E+10 | 3192.04 | 11-JUL-08:32 | 23.53 | 16.28 | 0.104624E+09 | 79.95 | 14-JUL-21:30 | 21.70 | 21.06 |
August | 0.224526E+10 | 3185.73 | 23-AUG-08:51 | 22.80 | 15.80 | 0.104012E+09 | 79.44 | 10-AUG-21:10 | 22.80 | 15.80 |
September | 0.117927E+10 | 3158.72 | 03-SEP-08:51 | 22.80 | 14.85 | 0.102180E+09 | 80.03 | 05-SEP-21:10 | 23.90 | 20.42 |
October | 0.569467E+09 | 2771.49 | 05-OCT-08:51 | 18.90 | 16.77 | 0.100436E+09 | 71.07 | 04-OCT-21:40 | 18.90 | 16.77 |
November | 78826275.11 | 2346.22 | 04-NOV-15:01 | 17.30 | 12.80 | 91916667.24 | 56.69 | 26-NOV-02:20 | 6.70 | 6.50 |
December | 13453775.01 | 1910.60 | 20-DEC-09:01 | 6.47 | 4.26 | 93340616.73 | 56.69 | 25-DEC-04:19 | 7.93 | 7.57 |
Annual Sum or Average | 0.940214E+10 | 0.117201E+10 | ||||||||
Minimum of Months | 8885291.10 | 1314.16 | -2.0 | -5.5 | 84412674.36 | 56.69 | -2.0 | -5.5 | ||
Maximum of Months | 0.224526E+10 | 3330.19 | 25.18 | 19.00 | 0.104640E+09 | 80.56 | 24.63 | 21.06 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103974E+10 | 1253.05 | 19-JAN-22:00 | 5.60 | 1.07 | 0.119899E+10 | 714.01 | 19-JAN-22:49 | 5.60 | 1.07 |
February | 0.120317E+10 | 1426.77 | 19-FEB-11:33 | 7.97 | 4.38 | 0.108412E+10 | 711.14 | 22-FEB-22:49 | 2.20 | -0.8 |
March | 0.252293E+10 | 1548.29 | 29-MAR-10:33 | 8.17 | 4.49 | 0.121814E+10 | 755.78 | 03-MAR-22:49 | 8.17 | 4.49 |
April | 0.315520E+10 | 1903.83 | 08-APR-10:33 | 23.90 | 16.13 | 0.122930E+10 | 835.49 | 10-APR-21:40 | 11.83 | 5.31 |
May | 0.396507E+10 | 2138.69 | 31-MAY-10:35 | 25.60 | 19.79 | 0.136693E+10 | 912.73 | 31-MAY-21:49 | 20.02 | 17.39 |
June | 0.447109E+10 | 2348.73 | 22-JUN-18:03 | 28.72 | 17.28 | 0.146363E+10 | 933.29 | 23-JUN-22:10 | 22.70 | 21.24 |
July | 0.486039E+10 | 2375.07 | 11-JUL-17:09 | 28.12 | 17.29 | 0.154926E+10 | 948.92 | 11-JUL-22:10 | 22.62 | 17.84 |
August | 0.495309E+10 | 2384.73 | 24-AUG-19:30 | 28.30 | 16.24 | 0.157645E+10 | 951.85 | 23-AUG-22:10 | 28.30 | 16.24 |
September | 0.433870E+10 | 2334.98 | 01-SEP-17:01 | 27.80 | 17.38 | 0.143596E+10 | 946.51 | 01-SEP-21:49 | 26.20 | 17.54 |
October | 0.402699E+10 | 2002.43 | 05-OCT-10:33 | 21.13 | 17.47 | 0.139033E+10 | 885.84 | 05-OCT-21:49 | 18.90 | 17.51 |
November | 0.233566E+10 | 1687.18 | 04-NOV-10:45 | 17.02 | 11.62 | 0.118649E+10 | 786.77 | 03-NOV-22:10 | 17.02 | 11.62 |
December | 0.149610E+10 | 1449.29 | 17-DEC-11:33 | 11.67 | 4.45 | 0.119934E+10 | 714.11 | 18-DEC-22:49 | 2.20 | 0.64 |
Annual Sum or Average | 0.383681E+11 | 0.158989E+11 | ||||||||
Minimum of Months | 0.103974E+10 | 1253.05 | 5.60 | 1.07 | 0.108412E+10 | 711.14 | 2.20 | -0.8 | ||
Maximum of Months | 0.495309E+10 | 2384.73 | 28.72 | 19.79 | 0.157645E+10 | 951.85 | 28.30 | 21.24 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 23039942.09 | 2847.74 | 20-JAN-16:02 | 6.93 | 3.71 | 93461556.64 | 56.69 | 03-JAN-04:19 | 6.93 | 3.71 |
February | 47756930.43 | 2893.55 | 14-FEB-16:01 | 0.50 | -3.9 | 85017313.37 | 56.69 | 14-FEB-04:19 | 0.50 | -3.9 |
March | 0.259939E+09 | 2969.66 | 11-MAR-16:01 | 11.20 | 5.40 | 95994253.42 | 56.69 | 27-MAR-21:19 | 13.87 | 10.67 |
April | 0.625121E+09 | 3040.87 | 10-APR-18:02 | 19.22 | 10.01 | 93808768.10 | 56.69 | 27-APR-21:40 | 14.40 | 12.93 |
May | 0.127575E+10 | 3184.64 | 20-MAY-18:02 | 22.02 | 11.72 | 98411638.53 | 56.69 | 31-MAY-21:00 | 19.90 | 17.35 |
June | 0.212394E+10 | 3228.99 | 19-JUN-18:02 | 32.12 | 23.09 | 95846017.97 | 56.70 | 19-JUN-23:00 | 24.40 | 21.27 |
July | 0.261353E+10 | 3270.57 | 12-JUL-18:02 | 25.50 | 21.15 | 99091439.77 | 56.70 | 10-JUL-22:00 | 25.50 | 21.15 |
August | 0.281162E+10 | 3296.62 | 15-AUG-18:02 | 26.42 | 20.41 | 99192136.00 | 56.70 | 21-AUG-23:49 | 27.20 | 23.26 |
September | 0.170551E+10 | 3223.06 | 07-SEP-15:02 | 26.60 | 22.96 | 95501116.99 | 56.70 | 14-SEP-21:30 | 23.60 | 16.82 |
October | 0.106718E+10 | 2991.26 | 02-OCT-18:02 | 20.82 | 15.42 | 98123216.22 | 56.69 | 04-OCT-23:00 | 17.20 | 16.15 |
November | 0.113951E+09 | 2784.27 | 08-NOV-16:01 | 12.62 | 10.56 | 92132398.27 | 56.69 | 03-NOV-23:19 | 12.62 | 10.56 |
December | 26185603.44 | 2878.37 | 02-DEC-16:01 | 5.92 | 0.97 | 93921671.46 | 56.69 | 25-DEC-04:19 | 7.93 | 7.57 |
Annual Sum or Average | 0.126935E+11 | 0.114050E+10 | ||||||||
Minimum of Months | 23039942.09 | 2784.27 | 0.50 | -3.9 | 85017313.37 | 56.69 | 0.50 | -3.9 | ||
Maximum of Months | 0.281162E+10 | 3296.62 | 32.12 | 23.09 | 99192136.00 | 56.70 | 27.20 | 23.26 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5271389.27 | 1947.80 | 17-JAN-16:02 | 9.45 | 4.59 | 92684854.43 | 56.69 | 09-JAN-00:20 | 9.45 | 4.59 |
February | 10739972.99 | 2034.24 | 24-FEB-16:01 | 7.62 | 1.74 | 83965554.70 | 56.69 | 07-FEB-04:19 | 7.62 | 1.74 |
March | 0.113784E+09 | 2830.02 | 11-MAR-16:01 | 11.20 | 5.40 | 95136939.91 | 66.13 | 27-MAR-21:10 | 14.13 | 10.87 |
April | 0.393809E+09 | 3266.69 | 09-APR-18:11 | 14.43 | 12.85 | 94940118.69 | 75.25 | 10-APR-18:10 | 19.22 | 10.01 |
May | 0.964862E+09 | 3495.40 | 29-MAY-18:31 | 24.80 | 18.16 | 0.104910E+09 | 91.18 | 31-MAY-21:10 | 20.48 | 17.58 |
June | 0.172602E+10 | 3212.06 | 23-JUN-08:61 | 26.70 | 18.47 | 0.107774E+09 | 87.91 | 28-JUN-21:10 | 21.20 | 18.58 |
July | 0.236333E+10 | 3277.38 | 03-JUL-18:51 | 24.40 | 21.27 | 0.104448E+09 | 82.75 | 05-JUL-21:40 | 22.40 | 21.60 |
August | 0.239211E+10 | 3166.68 | 15-AUG-18:02 | 26.42 | 20.41 | 0.103635E+09 | 83.39 | 10-AUG-21:10 | 26.42 | 20.41 |
September | 0.113418E+10 | 3149.10 | 10-SEP-21:51 | 16.70 | 9.96 | 0.103100E+09 | 83.30 | 06-SEP-21:10 | 16.70 | 9.96 |
October | 0.487099E+09 | 2965.66 | 02-OCT-15:02 | 22.88 | 16.78 | 0.101088E+09 | 75.03 | 04-OCT-21:40 | 16.87 | 15.72 |
November | 30239636.40 | 2616.97 | 04-NOV-15:01 | 17.30 | 12.80 | 91145808.18 | 56.69 | 24-NOV-04:19 | -3.5 | -5.8 |
December | 5798893.68 | 1538.79 | 17-DEC-16:02 | 9.82 | 4.16 | 92778121.45 | 56.69 | 15-DEC-04:19 | 9.82 | 4.16 |
Annual Sum or Average | 0.962724E+10 | 0.117561E+10 | ||||||||
Minimum of Months | 5271389.27 | 1538.79 | 7.62 | 1.74 | 83965554.70 | 56.69 | -3.5 | -5.8 | ||
Maximum of Months | 0.239211E+10 | 3495.40 | 26.70 | 21.27 | 0.107774E+09 | 91.18 | 26.42 | 21.60 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135040E+09 | 1563.81 | 31-JAN-16:02 | -1.3 | -5.8 | 95487882.58 | 56.69 | 15-JAN-02:20 | -1.3 | -5.8 |
February | 0.197480E+09 | 1575.45 | 02-FEB-16:02 | 4.13 | -2.3 | 87103697.34 | 56.69 | 21-FEB-00:20 | 2.60 | 1.73 |
March | 0.354086E+09 | 1577.13 | 13-MAR-15:02 | 7.12 | 1.52 | 97136854.74 | 56.69 | 03-MAR-22:49 | 7.12 | 1.52 |
April | 0.491783E+09 | 1652.93 | 07-APR-15:02 | 25.60 | 15.98 | 94375238.11 | 56.69 | 07-APR-22:19 | 18.13 | 13.36 |
May | 0.753462E+09 | 1674.26 | 20-MAY-18:02 | 22.02 | 11.72 | 98466871.23 | 56.69 | 31-MAY-21:00 | 19.90 | 17.35 |
June | 0.112726E+10 | 1705.41 | 22-JUN-18:02 | 28.72 | 17.28 | 95777387.55 | 56.69 | 20-JUN-00:10 | 28.72 | 17.28 |
July | 0.147876E+10 | 1726.46 | 09-JUL-18:02 | 27.12 | 24.06 | 99084837.47 | 56.70 | 10-JUL-00:40 | 28.17 | 22.16 |
August | 0.167372E+10 | 1767.64 | 16-AUG-15:02 | 32.02 | 25.35 | 99168791.23 | 56.70 | 04-AUG-21:10 | 32.02 | 25.35 |
September | 0.124307E+10 | 1756.29 | 14-SEP-15:02 | 30.00 | 20.06 | 95621647.32 | 56.70 | 01-SEP-21:30 | 30.00 | 20.06 |
October | 0.110730E+10 | 1690.88 | 03-OCT-15:02 | 23.22 | 19.26 | 98631512.09 | 56.69 | 04-OCT-22:40 | 17.43 | 15.94 |
November | 0.334785E+09 | 1541.11 | 02-NOV-18:02 | 13.80 | 7.37 | 94148137.85 | 56.69 | 03-NOV-21:10 | 12.80 | 10.17 |
December | 0.221464E+09 | 1570.17 | 15-DEC-16:01 | 4.32 | 0.72 | 96098724.98 | 56.69 | 18-DEC-00:20 | 2.60 | 0.34 |
Annual Sum or Average | 0.911820E+10 | 0.115110E+10 | ||||||||
Minimum of Months | 0.135040E+09 | 1541.11 | -1.3 | -5.8 | 87103697.34 | 56.69 | -1.3 | -5.8 | ||
Maximum of Months | 0.167372E+10 | 1767.64 | 32.02 | 25.35 | 99168791.23 | 56.70 | 32.02 | 25.35 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.303805E+11 | 17089.75 | 23-JAN-23:00 | 10.60 | 10.26 | 0.183578E+11 | 11347.94 | 14-JAN-00:20 | 10.60 | 10.26 |
February | 0.273031E+11 | 16450.08 | 23-FEB-23:00 | 5.00 | 4.23 | 0.165832E+11 | 11347.98 | 04-FEB-00:20 | 5.00 | 4.23 |
March | 0.330478E+11 | 18823.89 | 27-MAR-21:04 | 14.13 | 10.87 | 0.188784E+11 | 11348.32 | 27-MAR-21:19 | 13.87 | 10.67 |
April | 0.345123E+11 | 20342.49 | 07-APR-21:53 | 18.30 | 13.42 | 0.183989E+11 | 11348.84 | 07-APR-22:10 | 18.22 | 13.39 |
May | 0.391487E+11 | 21840.84 | 31-MAY-21:52 | 19.90 | 17.35 | 0.192121E+11 | 11349.20 | 31-MAY-22:10 | 19.78 | 17.36 |
June | 0.414548E+11 | 23256.39 | 19-JUN-21:20 | 28.53 | 20.50 | 0.187128E+11 | 11351.68 | 23-JUN-21:19 | 22.80 | 20.95 |
July | 0.445449E+11 | 23053.39 | 10-JUL-21:20 | 27.03 | 20.02 | 0.192856E+11 | 11356.88 | 07-JUL-21:19 | 27.03 | 20.02 |
August | 0.443214E+11 | 23342.76 | 04-AUG-21:20 | 30.90 | 23.99 | 0.193540E+11 | 11361.91 | 18-AUG-21:19 | 24.63 | 17.59 |
September | 0.394134E+11 | 22420.78 | 01-SEP-21:50 | 26.20 | 17.54 | 0.186150E+11 | 11349.11 | 06-SEP-22:10 | 22.20 | 20.63 |
October | 0.371171E+11 | 20562.71 | 05-OCT-21:53 | 18.90 | 17.46 | 0.190665E+11 | 11348.84 | 04-OCT-22:10 | 18.90 | 17.46 |
November | 0.319592E+11 | 18537.89 | 03-NOV-22:00 | 12.80 | 10.33 | 0.181381E+11 | 11347.97 | 27-NOV-00:20 | 8.50 | 8.23 |
December | 0.310820E+11 | 16881.19 | 04-DEC-23:00 | 8.30 | 7.50 | 0.185603E+11 | 11347.97 | 22-DEC-00:20 | -3.3 | -6.0 |
Annual Sum or Average | 0.434285E+12 | 0.223163E+12 | ||||||||
Minimum of Months | 0.273031E+11 | 16450.08 | 5.00 | 4.23 | 0.165832E+11 | 11347.94 | -3.3 | -6.0 | ||
Maximum of Months | 0.445449E+11 | 23342.76 | 30.90 | 23.99 | 0.193540E+11 | 11361.91 | 27.03 | 20.95 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.337046E+11 | 19118.53 | 23-JAN-23:00 | 10.60 | 10.26 | 0.186813E+11 | 11348.08 | 30-JAN-00:20 | -3.1 | -4.6 |
February | 0.302580E+11 | 18423.32 | 23-FEB-23:00 | 5.00 | 4.23 | 0.168797E+11 | 11348.06 | 27-FEB-00:20 | -0.9 | -4.8 |
March | 0.366808E+11 | 20801.24 | 27-MAR-21:04 | 14.13 | 10.87 | 0.190845E+11 | 11348.34 | 27-MAR-21:19 | 13.87 | 10.67 |
April | 0.380618E+11 | 22042.84 | 07-APR-21:10 | 19.22 | 13.77 | 0.185477E+11 | 11348.84 | 07-APR-22:10 | 18.22 | 13.39 |
May | 0.427171E+11 | 23126.80 | 31-MAY-21:52 | 19.90 | 17.35 | 0.192846E+11 | 11349.21 | 31-MAY-22:10 | 19.78 | 17.36 |
June | 0.444442E+11 | 24540.21 | 19-JUN-21:20 | 28.53 | 20.50 | 0.187368E+11 | 11370.74 | 23-JUN-21:19 | 22.80 | 20.95 |
July | 0.474447E+11 | 24268.04 | 10-JUL-21:20 | 27.03 | 20.02 | 0.192994E+11 | 11371.77 | 05-JUL-21:19 | 27.03 | 20.02 |
August | 0.471572E+11 | 24573.85 | 04-AUG-21:20 | 30.90 | 23.99 | 0.193715E+11 | 11371.90 | 18-AUG-21:19 | 24.63 | 17.59 |
September | 0.424492E+11 | 23674.47 | 01-SEP-21:10 | 26.60 | 18.09 | 0.186597E+11 | 11358.29 | 14-SEP-21:19 | 23.87 | 17.02 |
October | 0.404622E+11 | 21973.72 | 05-OCT-21:53 | 18.90 | 17.46 | 0.191773E+11 | 11348.85 | 04-OCT-22:10 | 18.90 | 17.46 |
November | 0.354296E+11 | 20385.75 | 03-NOV-22:00 | 12.80 | 10.33 | 0.183465E+11 | 11348.07 | 24-NOV-00:20 | -3.3 | -5.8 |
December | 0.345483E+11 | 18872.66 | 04-DEC-23:00 | 8.30 | 7.50 | 0.188190E+11 | 11348.02 | 22-DEC-00:20 | -3.3 | -6.0 |
Annual Sum or Average | 0.473358E+12 | 0.224888E+12 | ||||||||
Minimum of Months | 0.302580E+11 | 18423.32 | 5.00 | 4.23 | 0.168797E+11 | 11348.02 | -3.3 | -6.0 | ||
Maximum of Months | 0.474447E+11 | 24573.85 | 30.90 | 23.99 | 0.193715E+11 | 11371.90 | 27.03 | 20.95 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.457762E+11 | 25171.17 | 17-JAN-11:50 | 9.13 | 4.92 | 0.187699E+11 | 11319.67 | 21-JAN-18:19 | 7.20 | 6.67 |
February | 0.415469E+11 | 25817.61 | 19-FEB-11:50 | 7.88 | 4.27 | 0.169521E+11 | 11319.66 | 18-FEB-18:19 | 7.88 | 4.27 |
March | 0.485933E+11 | 26825.67 | 29-MAR-10:33 | 8.17 | 4.49 | 0.187952E+11 | 11319.67 | 04-MAR-18:19 | 8.17 | 4.49 |
April | 0.491227E+11 | 28975.79 | 08-APR-10:33 | 23.90 | 16.13 | 0.181997E+11 | 11319.59 | 15-APR-17:19 | 9.40 | 9.40 |
May | 0.533702E+11 | 29757.83 | 29-MAY-10:33 | 27.43 | 17.92 | 0.188243E+11 | 11319.68 | 20-MAY-17:19 | 27.43 | 17.92 |
June | 0.536993E+11 | 31659.78 | 01-JUN-18:02 | 27.70 | 16.11 | 0.182387E+11 | 11319.69 | 17-JUN-17:19 | 22.60 | 20.38 |
July | 0.566848E+11 | 31221.33 | 11-JUL-17:09 | 28.12 | 17.29 | 0.188466E+11 | 11319.69 | 15-JUL-17:19 | 25.93 | 22.25 |
August | 0.569212E+11 | 31124.09 | 22-AUG-17:01 | 28.72 | 16.50 | 0.188549E+11 | 11319.68 | 19-AUG-17:19 | 28.72 | 16.50 |
September | 0.526318E+11 | 30737.00 | 01-SEP-17:01 | 27.80 | 17.38 | 0.182277E+11 | 11319.67 | 30-SEP-17:19 | 17.77 | 12.98 |
October | 0.520253E+11 | 28438.03 | 04-OCT-10:33 | 22.23 | 17.92 | 0.188154E+11 | 11319.64 | 28-OCT-17:19 | 9.03 | 2.93 |
November | 0.467366E+11 | 27157.26 | 04-NOV-10:45 | 17.02 | 11.62 | 0.181828E+11 | 11319.63 | 18-NOV-18:19 | 5.40 | 2.24 |
December | 0.465564E+11 | 25688.08 | 17-DEC-11:50 | 11.93 | 4.48 | 0.187776E+11 | 11319.64 | 16-DEC-18:19 | 11.93 | 4.48 |
Annual Sum or Average | 0.603665E+12 | 0.221485E+12 | ||||||||
Minimum of Months | 0.415469E+11 | 25171.17 | 7.88 | 4.27 | 0.169521E+11 | 11319.59 | 5.40 | 2.24 | ||
Maximum of Months | 0.569212E+11 | 31659.78 | 28.72 | 17.92 | 0.188549E+11 | 11319.69 | 28.72 | 22.25 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.195306E+10 | 3118.18 | 17-JAN-11:35 | 8.87 | 4.86 | 0.126906E+10 | 745.62 | 04-JAN-03:20 | 8.87 | 4.86 |
February | 0.203129E+10 | 3338.71 | 19-FEB-11:33 | 7.97 | 4.38 | 0.114802E+10 | 745.60 | 09-FEB-04:00 | 7.97 | 4.38 |
March | 0.512895E+10 | 3670.21 | 03-MAR-11:33 | 13.53 | 7.78 | 0.128813E+10 | 807.13 | 27-MAR-21:40 | 13.33 | 10.26 |
April | 0.688870E+10 | 4543.90 | 08-APR-10:50 | 23.35 | 15.96 | 0.129362E+10 | 888.82 | 07-APR-21:40 | 23.35 | 15.96 |
May | 0.895299E+10 | 5081.70 | 31-MAY-10:35 | 25.60 | 19.79 | 0.143899E+10 | 972.17 | 31-MAY-21:40 | 20.13 | 17.44 |
June | 0.101445E+11 | 5745.16 | 19-JUN-14:10 | 34.22 | 23.63 | 0.154371E+10 | 1007.39 | 19-JUN-23:19 | 25.93 | 20.91 |
July | 0.113685E+11 | 6497.62 | 11-JUL-15:07 | 28.30 | 17.52 | 0.165118E+10 | 1007.39 | 10-JUL-23:19 | 28.30 | 17.52 |
August | 0.116190E+11 | 6425.54 | 16-AUG-12:50 | 31.93 | 25.44 | 0.166239E+10 | 1007.39 | 04-AUG-23:19 | 31.93 | 25.44 |
September | 0.967251E+10 | 5709.03 | 01-SEP-14:10 | 31.02 | 17.36 | 0.149246E+10 | 1007.36 | 01-SEP-21:30 | 26.40 | 17.81 |
October | 0.863038E+10 | 4588.89 | 05-OCT-10:33 | 21.13 | 17.47 | 0.141743E+10 | 924.31 | 05-OCT-21:40 | 18.90 | 17.57 |
November | 0.488748E+10 | 3816.95 | 04-NOV-10:50 | 17.02 | 11.62 | 0.124144E+10 | 812.15 | 03-NOV-22:10 | 17.02 | 11.62 |
December | 0.281321E+10 | 3396.85 | 17-DEC-11:33 | 11.67 | 4.45 | 0.126950E+10 | 745.61 | 01-DEC-05:49 | 11.67 | 4.45 |
Annual Sum or Average | 0.840906E+11 | 0.167159E+11 | ||||||||
Minimum of Months | 0.195306E+10 | 3118.18 | 7.97 | 4.38 | 0.114802E+10 | 745.60 | 7.97 | 4.38 | ||
Maximum of Months | 0.116190E+11 | 6497.62 | 34.22 | 25.44 | 0.166239E+10 | 1007.39 | 31.93 | 25.44 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.335203E+09 | 1157.49 | 02-JAN-07:10 | -11.6 |
February | 0.209621E+09 | 1068.55 | 06-FEB-07:05 | -13.2 |
March | 17502615.58 | 372.98 | 17-MAR-06:30 | -1.1 |
April | 445859.72 | 61.74 | 02-APR-04:40 | 3.90 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 15257977.93 | 396.07 | 23-NOV-06:00 | -3.9 |
December | 0.120229E+09 | 542.72 | 30-DEC-17:00 | 1.70 |
Annual Sum or Average | 0.698260E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.335203E+09 | 1157.49 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 87822100.18 | 463.94 | 02-JAN-15:00 | -6.1 |
February | 0.101327E+09 | 459.92 | 06-FEB-15:00 | -7.2 |
March | 217615.63 | 26.50 | 17-MAR-13:00 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 453703.37 | 75.46 | 31-DEC-18:00 | -5.0 |
Annual Sum or Average | 0.189821E+09 | |||
Minimum of Months | 0.00 | 0.00 | -7.2 | |
Maximum of Months | 0.101327E+09 | 463.94 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172892E+09 | 405.31 | 02-JAN-15:00 | -6.1 |
February | 0.166676E+09 | 415.76 | 06-FEB-16:00 | -7.2 |
March | 3958320.03 | 123.96 | 17-MAR-12:30 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 6214740.50 | 90.25 | 25-NOV-17:00 | 3.90 |
December | 20726559.96 | 193.40 | 31-DEC-18:00 | -5.0 |
Annual Sum or Average | 0.370468E+09 | |||
Minimum of Months | 0.00 | 0.00 | -7.2 | |
Maximum of Months | 0.172892E+09 | 415.76 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16456.84 | 10.30 | 08-JAN-15:40 | -1.5 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 16456.84 | |||
Minimum of Months | 0.00 | 0.00 | -1.5 | |
Maximum of Months | 16456.84 | 10.30 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103580E+10 | 2380.80 | 02-JAN-09:01 | -10.3 |
February | 0.827382E+09 | 2378.71 | 06-FEB-16:01 | -7.1 |
March | 0.326969E+09 | 2317.50 | 17-MAR-08:61 | -1.1 |
April | 0.125397E+09 | 2223.78 | 21-APR-15:01 | 7.30 |
May | 3823585.12 | 833.10 | 01-MAY-18:04 | 12.43 |
June | 960593.42 | 740.05 | 29-JUN-08:05 | 20.18 |
July | 451022.29 | 482.54 | 18-JUL-08:05 | 24.32 |
August | 718055.86 | 917.40 | 08-AUG-08:04 | 21.47 |
September | 1795991.75 | 961.22 | 26-SEP-15:04 | 18.72 |
October | 12117896.66 | 842.38 | 19-OCT-08:03 | 10.97 |
November | 0.404005E+09 | 2294.40 | 25-NOV-09:01 | -0.3 |
December | 0.787374E+09 | 2358.92 | 31-DEC-19:01 | -5.7 |
Annual Sum or Average | 0.352680E+10 | |||
Minimum of Months | 451022.29 | 482.54 | -10.3 | |
Maximum of Months | 0.103580E+10 | 2380.80 | 24.32 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126810E+10 | 2393.93 | 02-JAN-09:01 | -10.3 |
February | 0.111492E+10 | 2397.59 | 06-FEB-09:01 | -12.0 |
March | 0.450927E+09 | 2315.14 | 17-MAR-08:61 | -1.1 |
April | 0.149347E+09 | 2219.35 | 21-APR-15:01 | 7.30 |
May | 3989199.37 | 785.67 | 01-MAY-18:04 | 12.43 |
June | 241541.82 | 454.31 | 12-JUN-08:55 | 19.40 |
July | 212081.41 | 516.94 | 18-JUL-08:05 | 24.32 |
August | 190033.19 | 523.20 | 13-AUG-06:54 | 25.00 |
September | 1256250.76 | 1024.44 | 28-SEP-08:53 | 20.60 |
October | 28878254.18 | 973.69 | 19-OCT-18:04 | 13.90 |
November | 0.554142E+09 | 2329.52 | 24-NOV-09:01 | -1.5 |
December | 0.103177E+10 | 2360.54 | 31-DEC-19:01 | -5.7 |
Annual Sum or Average | 0.460397E+10 | |||
Minimum of Months | 190033.19 | 454.31 | -12.0 | |
Maximum of Months | 0.126810E+10 | 2397.59 | 25.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135441E+09 | 700.56 | 02-JAN-16:02 | -6.0 |
February | 0.138933E+09 | 709.72 | 06-FEB-16:01 | -7.1 |
March | 16223325.41 | 660.72 | 16-MAR-15:01 | 0.68 |
April | 836538.41 | 342.24 | 03-APR-08:03 | 5.68 |
May | 183968.57 | 434.62 | 03-MAY-15:05 | 15.92 |
June | 1564.47 | 11.75 | 06-JUN-15:07 | 18.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 2654.77 | 21.61 | 25-AUG-21:57 | 21.10 |
September | 33383.01 | 89.60 | 24-SEP-15:07 | 17.70 |
October | 597070.21 | 465.78 | 30-OCT-15:05 | 16.52 |
November | 24871595.10 | 665.38 | 22-NOV-16:01 | 0.60 |
December | 67274628.79 | 677.96 | 31-DEC-16:01 | -3.1 |
Annual Sum or Average | 0.384399E+09 | |||
Minimum of Months | 0.00 | 0.00 | -7.1 | |
Maximum of Months | 0.138933E+09 | 709.72 | 21.10 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102722E+10 | 2331.80 | 14-JAN-16:02 | -6.1 |
February | 0.802481E+09 | 2327.36 | 06-FEB-16:01 | -7.1 |
March | 0.353158E+09 | 2266.30 | 16-MAR-15:01 | 0.68 |
April | 0.129161E+09 | 2179.63 | 21-APR-15:01 | 7.30 |
May | 3579613.98 | 871.54 | 02-MAY-18:05 | 14.72 |
June | 279149.70 | 740.43 | 13-JUN-08:05 | 20.10 |
July | 46356.57 | 219.60 | 18-JUL-08:05 | 24.32 |
August | 3775.78 | 37.76 | 07-AUG-08:05 | 20.28 |
September | 886942.88 | 731.77 | 21-SEP-08:05 | 20.68 |
October | 12605745.51 | 959.64 | 06-OCT-18:04 | 14.90 |
November | 0.375769E+09 | 2244.98 | 25-NOV-09:01 | -0.3 |
December | 0.776393E+09 | 2312.65 | 31-DEC-19:01 | -5.7 |
Annual Sum or Average | 0.348158E+10 | |||
Minimum of Months | 3775.78 | 37.76 | -7.1 | |
Maximum of Months | 0.102722E+10 | 2331.80 | 24.32 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125045E+10 | 2326.01 | 14-JAN-16:02 | -6.1 |
February | 0.107682E+10 | 2336.97 | 06-FEB-16:01 | -7.1 |
March | 0.478633E+09 | 2262.09 | 16-MAR-15:01 | 0.68 |
April | 0.152855E+09 | 2175.22 | 21-APR-15:01 | 7.30 |
May | 3829213.35 | 1010.39 | 01-MAY-18:04 | 12.43 |
June | 97076.77 | 376.58 | 01-JUN-21:55 | 20.60 |
July | 12831.48 | 67.51 | 23-JUL-21:56 | 22.80 |
August | 22325.18 | 154.03 | 06-AUG-21:56 | 20.00 |
September | 667637.36 | 566.88 | 23-SEP-08:05 | 13.30 |
October | 31667574.26 | 953.56 | 19-OCT-15:05 | 16.02 |
November | 0.499998E+09 | 2268.69 | 23-NOV-19:01 | -0.7 |
December | 0.995559E+09 | 2314.41 | 31-DEC-19:01 | -5.7 |
Annual Sum or Average | 0.449060E+10 | |||
Minimum of Months | 12831.48 | 67.51 | -7.1 | |
Maximum of Months | 0.125045E+10 | 2336.97 | 22.80 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.162652E+09 | 972.84 | 14-JAN-16:15 | -6.1 |
February | 84099385.71 | 750.70 | 06-FEB-07:10 | -13.2 |
March | 1874711.33 | 218.57 | 17-MAR-08:03 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 977354.08 | 139.09 | 25-NOV-17:00 | 3.90 |
December | 53571828.12 | 557.46 | 11-DEC-15:00 | 1.10 |
Annual Sum or Average | 0.303176E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.162652E+09 | 972.84 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154595E+10 | 2846.55 | 14-JAN-16:02 | -6.1 |
February | 0.127594E+10 | 2842.17 | 06-FEB-16:01 | -7.1 |
March | 0.579528E+09 | 2761.31 | 17-MAR-08:61 | -1.1 |
April | 0.249476E+09 | 2673.66 | 21-APR-15:01 | 7.30 |
May | 14655358.07 | 961.04 | 01-MAY-18:04 | 12.43 |
June | 943130.43 | 824.48 | 22-JUN-08:04 | 24.60 |
July | 615444.70 | 625.08 | 05-JUL-08:05 | 22.98 |
August | 1084873.26 | 886.07 | 08-AUG-08:04 | 21.47 |
September | 3020898.71 | 984.59 | 16-SEP-18:04 | 18.90 |
October | 57401563.62 | 1104.97 | 27-OCT-08:62 | 7.48 |
November | 0.686467E+09 | 2754.42 | 25-NOV-09:01 | -0.3 |
December | 0.122970E+10 | 2811.68 | 31-DEC-19:01 | -5.7 |
Annual Sum or Average | 0.564478E+10 | |||
Minimum of Months | 615444.70 | 625.08 | -7.1 | |
Maximum of Months | 0.154595E+10 | 2846.55 | 24.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.183057E+10 | 2854.71 | 02-JAN-09:01 | -10.3 |
February | 0.162575E+10 | 2859.83 | 06-FEB-09:01 | -12.0 |
March | 0.747221E+09 | 2756.09 | 22-MAR-08:61 | -2.0 |
April | 0.288281E+09 | 2663.96 | 21-APR-15:01 | 7.30 |
May | 14756724.56 | 1017.23 | 01-MAY-18:04 | 12.43 |
June | 267154.07 | 450.59 | 06-JUN-21:55 | 17.20 |
July | 292389.89 | 621.77 | 09-JUL-06:54 | 26.70 |
August | 244306.52 | 444.61 | 08-AUG-08:54 | 23.30 |
September | 2353053.97 | 1190.54 | 24-SEP-15:04 | 17.70 |
October | 0.107836E+09 | 2607.39 | 29-OCT-08:62 | 6.88 |
November | 0.896772E+09 | 2768.11 | 24-NOV-09:01 | -1.5 |
December | 0.153683E+10 | 2817.28 | 31-DEC-19:01 | -5.7 |
Annual Sum or Average | 0.705118E+10 | |||
Minimum of Months | 244306.52 | 444.61 | -12.0 | |
Maximum of Months | 0.183057E+10 | 2859.83 | 26.70 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.441824E+09 | 1493.63 | 14-JAN-16:02 | -6.1 |
February | 0.306835E+09 | 1457.98 | 26-FEB-16:01 | -1.6 |
March | 0.131455E+09 | 1442.04 | 16-MAR-15:01 | 0.68 |
April | 54664678.98 | 1388.15 | 21-APR-15:01 | 7.30 |
May | 1739277.92 | 524.10 | 03-MAY-15:05 | 15.92 |
June | 380126.54 | 353.43 | 04-JUN-08:05 | 22.38 |
July | 193058.25 | 379.84 | 18-JUL-08:05 | 24.32 |
August | 137034.43 | 402.99 | 08-AUG-08:04 | 21.47 |
September | 329566.09 | 367.54 | 21-SEP-08:05 | 20.68 |
October | 1839739.64 | 483.37 | 28-OCT-18:05 | 8.22 |
November | 0.112746E+09 | 1407.12 | 25-NOV-09:01 | -0.3 |
December | 0.300135E+09 | 1452.13 | 30-DEC-16:01 | 1.20 |
Annual Sum or Average | 0.135228E+10 | |||
Minimum of Months | 137034.43 | 353.43 | -6.1 | |
Maximum of Months | 0.441824E+09 | 1493.63 | 24.32 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.497162E+09 | 2515.84 | 02-JAN-07:15 | -11.5 |
February | 0.392708E+09 | 2458.42 | 06-FEB-07:05 | -13.2 |
March | 6347293.22 | 684.84 | 23-MAR-06:10 | -4.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 19608847.68 | 678.28 | 24-NOV-07:10 | -4.3 |
December | 41635309.32 | 596.52 | 15-DEC-07:10 | -3.6 |
Annual Sum or Average | 0.957462E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.497162E+09 | 2515.84 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.962539E+10 | 9271.23 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.869085E+10 | 9271.23 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.965507E+10 | 9271.23 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.929905E+10 | 9271.23 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.964208E+10 | 9271.23 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.934170E+10 | 9271.23 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.959943E+10 | 9271.23 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.965878E+10 | 9271.23 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.930276E+10 | 9271.23 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.962169E+10 | 9271.23 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.933428E+10 | 9271.23 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.959943E+10 | 9271.23 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.113371E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.869085E+10 | 9271.23 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.965878E+10 | 9271.23 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.531884E+09 | 512.31 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.480243E+09 | 512.31 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.533523E+09 | 512.31 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.513850E+09 | 512.31 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.532806E+09 | 512.31 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.516207E+09 | 512.31 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.530449E+09 | 512.31 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.533728E+09 | 512.31 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.514055E+09 | 512.31 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.531679E+09 | 512.31 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.515797E+09 | 512.31 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.530449E+09 | 512.31 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.626467E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.480243E+09 | 512.31 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.533728E+09 | 512.31 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.615923E+09 | 593.26 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.556123E+09 | 593.26 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.617822E+09 | 593.26 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.595041E+09 | 593.26 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.616991E+09 | 593.26 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.597770E+09 | 593.26 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.614262E+09 | 593.26 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.618059E+09 | 593.26 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.595278E+09 | 593.26 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.615686E+09 | 593.26 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.597295E+09 | 593.26 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.614262E+09 | 593.26 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.725451E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.556123E+09 | 593.26 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.618059E+09 | 593.26 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.158446E+09 | 152.61 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.143062E+09 | 152.61 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.158934E+09 | 152.61 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.153074E+09 | 152.61 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.158720E+09 | 152.61 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.153776E+09 | 152.61 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.158018E+09 | 152.61 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.158995E+09 | 152.61 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.153135E+09 | 152.61 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.158385E+09 | 152.61 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.153654E+09 | 152.61 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.158018E+09 | 152.61 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.186622E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.143062E+09 | 152.61 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.158995E+09 | 152.61 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.415991E+09 | 400.68 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.375602E+09 | 400.68 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.417273E+09 | 400.68 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.401887E+09 | 400.68 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.416712E+09 | 400.68 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.403730E+09 | 400.68 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.414869E+09 | 400.68 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.417433E+09 | 400.68 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.402047E+09 | 400.68 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.415830E+09 | 400.68 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.403409E+09 | 400.68 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.414869E+09 | 400.68 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.489965E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.375602E+09 | 400.68 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.417433E+09 | 400.68 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.125984E+10 | 1573.46 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.107756E+10 | 1573.46 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.113069E+10 | 1573.46 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.101172E+10 | 1573.46 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.950864E+09 | 1573.46 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.886205E+09 | 1573.46 | 01-JUN-19:19 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.920528E+09 | 1573.46 | 03-JUL-19:30 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.100414E+10 | 1573.46 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.105796E+10 | 1573.46 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.117843E+10 | 1573.46 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.118316E+10 | 1573.46 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.124968E+10 | 1573.46 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.129108E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.886205E+09 | 1573.46 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.125984E+10 | 1573.46 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.106226E+11 | 10645.38 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.951406E+10 | 10645.38 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.104990E+11 | 10645.38 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.100313E+11 | 10645.38 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.102854E+11 | 10645.38 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.993134E+10 | 10645.38 | 01-JUN-19:19 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.102193E+11 | 10645.38 | 03-JUL-19:30 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.103580E+11 | 10645.38 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.100828E+11 | 10645.38 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.105112E+11 | 10645.38 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.102462E+11 | 10645.38 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.105808E+11 | 10645.38 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.122882E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.951406E+10 | 10645.38 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.106226E+11 | 10645.38 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82476868.03 | 74.62 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 74484663.28 | 74.62 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 81821381.83 | 74.62 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 79911301.67 | 74.62 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 82149124.93 | 74.62 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 79277307.08 | 74.62 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 82793865.32 | 74.62 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 81821381.83 | 74.62 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 79932793.28 | 74.62 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 82466122.22 | 74.62 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 79594304.38 | 74.62 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 82804611.13 | 74.62 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.969534E+09 | 0.300992E+10 | ||||
Minimum of Months | 74484663.28 | 74.62 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 82804611.13 | 74.62 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82499421.18 | 74.64 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 74505030.97 | 74.64 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 81843755.73 | 74.64 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 79933153.27 | 74.64 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 82171588.45 | 74.64 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 79298985.31 | 74.64 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 82816505.16 | 74.64 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 81843755.73 | 74.64 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 79954650.76 | 74.64 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 82488672.43 | 74.64 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 79616069.29 | 74.64 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 82827253.90 | 74.64 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.969799E+09 | 0.301074E+10 | ||||
Minimum of Months | 74505030.97 | 74.64 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 82827253.90 | 74.64 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.120431E+10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.108739E+10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.120803E+10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.116348E+10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.120640E+10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.116882E+10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.120107E+10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.120849E+10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.116395E+10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.120385E+10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.116789E+10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.120107E+10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.141847E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.108739E+10 | 1160.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120849E+10 | 1160.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82499421.18 | 74.64 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 74505030.97 | 74.64 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 81843755.73 | 74.64 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 79933153.27 | 74.64 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 82171588.45 | 74.64 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 79298985.31 | 74.64 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 82816505.16 | 74.64 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 81843755.73 | 74.64 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 79954650.76 | 74.64 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 82488672.43 | 74.64 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 79616069.29 | 74.64 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 82827253.90 | 74.64 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.969799E+09 | 0.301074E+10 | ||||
Minimum of Months | 74505030.97 | 74.64 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 82827253.90 | 74.64 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.257787E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.226874E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.244509E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.227067E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.224791E+10 | 2763.12 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.214222E+10 | 2763.12 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.221387E+10 | 2763.12 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.230551E+10 | 2763.12 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.232023E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.248267E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.245588E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.258248E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.283131E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.214222E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.258248E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.257787E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.226874E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.244509E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.227067E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.224791E+10 | 2763.12 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.214222E+10 | 2763.12 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.221387E+10 | 2763.12 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.230551E+10 | 2763.12 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.232023E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.248267E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.245588E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.258248E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.283131E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.214222E+10 | 2763.12 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.258248E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113250E+10 | 1090.83 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.102255E+10 | 1090.83 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.113599E+10 | 1090.83 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.109410E+10 | 1090.83 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.113446E+10 | 1090.83 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.109912E+10 | 1090.83 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.112945E+10 | 1090.83 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.113643E+10 | 1090.83 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.109454E+10 | 1090.83 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.113207E+10 | 1090.83 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.109825E+10 | 1090.83 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.112945E+10 | 1090.83 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.133389E+11 | 0.424019E+12 | ||||
Minimum of Months | 0.102255E+10 | 1090.83 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.113643E+10 | 1090.83 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.127458E+10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.115083E+10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.127851E+10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.123137E+10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.127679E+10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.123701E+10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.127114E+10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.127900E+10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.123186E+10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.127409E+10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.123603E+10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.127114E+10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.150123E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.115083E+10 | 1227.68 | 0.00 | 0.00 | |
Maximum of Months | 0.127900E+10 | 1227.68 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.962539E+10 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.869085E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.965507E+10 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.929905E+10 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.964208E+10 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.934170E+10 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.959943E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.965878E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.930276E+10 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.962169E+10 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.933428E+10 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.959943E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.113371E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.869085E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.965878E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.531884E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172200E+09 |
February | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166090E+09 |
March | 0.199990E+10 | 0.533523E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.88 | 0.133409E+09 |
April | 0.192973E+10 | 0.513850E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 167133.29 | 84879702.47 |
May | 0.199475E+10 | 0.532806E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1224826.67 | 47175183.49 |
June | 0.193394E+10 | 0.516207E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6940429.42 | 12954148.43 |
July | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17885709.50 | 1486110.60 |
August | 0.199896E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17217655.45 | 5206128.52 |
September | 0.192879E+10 | 0.514055E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2791004.57 | 23149785.89 |
October | 0.199148E+10 | 0.531679E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40199.03 | 68530128.99 |
November | 0.192552E+10 | 0.515797E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113749E+09 |
December | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150881E+09 |
Annual Sum or Average | 0.234744E+11 | 0.626467E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46266961.82 | 0.979711E+09 |
Minimum of Months | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1486110.60 |
Maximum of Months | 0.199990E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17885709.50 | 0.172200E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.615923E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67448721.20 |
February | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65015289.40 |
March | 0.231589E+10 | 0.617822E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.31 | 53493135.46 |
April | 0.223463E+10 | 0.595041E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 104053.92 | 35406526.10 |
May | 0.230993E+10 | 0.616991E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 519995.23 | 21674752.99 |
June | 0.223950E+10 | 0.597770E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2516250.88 | 7520898.96 |
July | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6095822.32 | 1670383.58 |
August | 0.231480E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6470211.90 | 3222071.63 |
September | 0.223354E+10 | 0.595278E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1107330.26 | 11355250.73 |
October | 0.230614E+10 | 0.615686E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44656.19 | 28911411.87 |
November | 0.222975E+10 | 0.597295E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46109820.81 |
December | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59685555.78 |
Annual Sum or Average | 0.271834E+11 | 0.725451E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16858540.01 | 0.401514E+09 |
Minimum of Months | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1670383.58 |
Maximum of Months | 0.231589E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6470211.90 | 67448721.20 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156048E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149930E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9131.02 | 0.119957E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 375582.07 | 77887113.84 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1325979.50 | 47489802.49 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5913248.83 | 16600869.84 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14004410.89 | 3610913.64 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15238564.24 | 7168120.66 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2739929.35 | 25030578.71 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 197413.13 | 63006680.55 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103786E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136155E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39804259.03 | 0.906670E+09 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3610913.64 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15238564.24 | 0.156048E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.158446E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89962603.10 |
February | 0.339028E+09 | 0.143062E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86446253.64 |
March | 0.376747E+09 | 0.158934E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5012.83 | 68884180.44 |
April | 0.363528E+09 | 0.153074E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 216486.76 | 44397246.04 |
May | 0.375778E+09 | 0.158720E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 776903.38 | 26707222.26 |
June | 0.364321E+09 | 0.153776E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3508382.89 | 9069852.97 |
July | 0.374985E+09 | 0.158018E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8327859.59 | 1854879.88 |
August | 0.376571E+09 | 0.158995E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8985761.61 | 3867130.22 |
September | 0.363352E+09 | 0.153135E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1652919.89 | 13851386.46 |
October | 0.375161E+09 | 0.158385E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 115522.13 | 35614044.10 |
November | 0.362735E+09 | 0.153654E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59390016.31 |
December | 0.374985E+09 | 0.158018E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78431495.04 |
Annual Sum or Average | 0.442217E+10 | 0.186622E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23588849.08 | 0.518476E+09 |
Minimum of Months | 0.339028E+09 | 0.143062E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1854879.88 |
Maximum of Months | 0.376747E+09 | 0.158995E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8985761.61 | 89962603.10 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.415991E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230386E+09 |
February | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220455E+09 |
March | 0.155131E+10 | 0.417273E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 2178.89 | 0.180579E+09 |
April | 0.149688E+10 | 0.401887E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 408013.27 | 0.118691E+09 |
May | 0.154732E+10 | 0.416712E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 1967278.41 | 70562955.07 |
June | 0.150015E+10 | 0.403730E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 10163185.63 | 21202490.51 |
July | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 25135226.61 | 3546393.38 |
August | 0.155059E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 26517621.39 | 7731817.69 |
September | 0.149615E+10 | 0.402047E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 5459213.11 | 33761018.94 |
October | 0.154478E+10 | 0.415830E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 351610.57 | 90800004.98 |
November | 0.149361E+10 | 0.403409E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156008E+09 |
December | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203309E+09 |
Annual Sum or Average | 0.182090E+11 | 0.489965E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 70004327.87 | 0.133703E+10 |
Minimum of Months | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3546393.38 |
Maximum of Months | 0.155131E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 26517621.39 | 0.230386E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.125984E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389793E+09 |
February | 0.236489E+11 | 0.107756E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377424E+09 |
March | 0.262800E+11 | 0.113069E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310443E+09 |
April | 0.253579E+11 | 0.101172E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 326760.04 | 0.203503E+09 |
May | 0.262123E+11 | 0.950864E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2604439.15 | 0.122688E+09 |
June | 0.254132E+11 | 0.886205E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14592313.07 | 40560789.05 |
July | 0.261570E+11 | 0.920528E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36187750.95 | 8926387.78 |
August | 0.262677E+11 | 0.100414E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36214468.93 | 17413129.45 |
September | 0.253456E+11 | 0.105796E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5797481.65 | 64777180.90 |
October | 0.261693E+11 | 0.117843E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97517.34 | 0.169530E+09 |
November | 0.253025E+11 | 0.118316E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266454E+09 |
December | 0.261570E+11 | 0.124968E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345313E+09 |
Annual Sum or Average | 0.308468E+12 | 0.129108E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95820731.13 | 0.231682E+10 |
Minimum of Months | 0.236489E+11 | 0.886205E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8926387.78 |
Maximum of Months | 0.262800E+11 | 0.125984E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36214468.93 | 0.389793E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.106226E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113436E+10 |
February | 0.702046E+11 | 0.951406E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109290E+10 |
March | 0.780153E+11 | 0.104990E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904321E+09 |
April | 0.752779E+11 | 0.100313E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1403884.70 | 0.601734E+09 |
May | 0.778146E+11 | 0.102854E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7964623.79 | 0.372304E+09 |
June | 0.754422E+11 | 0.993134E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40690902.98 | 0.129019E+09 |
July | 0.776503E+11 | 0.102193E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99906354.08 | 29896119.73 |
August | 0.779788E+11 | 0.103580E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105608E+09 | 54110480.10 |
September | 0.752414E+11 | 0.100828E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17291582.01 | 0.196112E+09 |
October | 0.776868E+11 | 0.105112E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 470688.42 | 0.492292E+09 |
November | 0.751137E+11 | 0.102462E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784342E+09 |
December | 0.776503E+11 | 0.105808E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100855E+10 |
Annual Sum or Average | 0.915726E+12 | 0.122882E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273336E+09 | 0.679993E+10 |
Minimum of Months | 0.702046E+11 | 0.951406E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29896119.73 |
Maximum of Months | 0.780153E+11 | 0.106226E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105608E+09 | 0.113436E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98630623.32 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95392249.92 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4330.06 | 77126323.24 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 181474.79 | 49303895.69 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 945841.29 | 27650104.94 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5621339.81 | 6102808.46 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15076799.15 | 320527.60 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15185702.50 | 1725938.45 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3239449.03 | 11534597.56 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 118849.05 | 36834876.47 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65501749.72 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86443325.12 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40373785.68 | 0.556567E+09 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320527.60 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15185702.50 | 98630623.32 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97630381.28 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94141319.05 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76138878.90 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 159376.18 | 49420017.80 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 776923.07 | 29708072.49 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4918374.94 | 9725678.70 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13918659.08 | 1278163.14 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14538007.21 | 2901740.40 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2633315.38 | 13851870.71 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63407.41 | 37691938.65 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64470224.76 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85201427.79 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37008063.27 | 0.562160E+09 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1278163.14 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14538007.21 | 97630381.28 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 82476868.03 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27419157.20 |
February | 0.00 | 74484663.28 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30887540.52 |
March | 0.00 | 81821381.83 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27418480.95 |
April | 0.00 | 79911301.67 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19719312.79 |
May | 0.00 | 82149124.93 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31239.83 | 14007722.37 |
June | 0.00 | 79277307.08 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 275483.70 | 6548528.61 |
July | 0.00 | 82793865.32 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 644442.69 | 2797319.42 |
August | 0.00 | 81821381.83 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 872440.39 | 3385391.69 |
September | 0.00 | 79932793.28 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68293.26 | 8616530.13 |
October | 0.00 | 82466122.22 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16870881.79 |
November | 0.00 | 79594304.38 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24111609.55 |
December | 0.00 | 82804611.13 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28464951.53 |
Annual Sum or Average | 0.00 | 0.969534E+09 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1891899.87 | 0.210247E+09 |
Minimum of Months | 0.00 | 74484663.28 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2797319.42 |
Maximum of Months | 0.00 | 82804611.13 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 872440.39 | 30887540.52 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 82499421.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27671461.16 |
February | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26580175.82 |
March | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 110.38 | 21442433.34 |
April | 0.293479E+09 | 79933153.27 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50356.63 | 13790443.19 |
May | 0.303504E+09 | 82171588.45 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 223397.94 | 7997203.22 |
June | 0.293842E+09 | 79298985.31 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1390885.81 | 2258690.36 |
July | 0.303141E+09 | 82816505.16 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3928434.48 | 254254.68 |
August | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4110103.12 | 682317.41 |
September | 0.293479E+09 | 79954650.76 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 759323.81 | 3597498.18 |
October | 0.303322E+09 | 82488672.43 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25197.75 | 10251679.59 |
November | 0.293661E+09 | 79616069.29 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18297540.70 |
December | 0.303141E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24198507.65 |
Annual Sum or Average | 0.357224E+10 | 0.969799E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10487809.92 | 0.157022E+09 |
Minimum of Months | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254254.68 |
Maximum of Months | 0.303685E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4110103.12 | 27671461.16 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98625022.81 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95516941.66 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4337.19 | 77384538.70 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 181867.98 | 49563247.19 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 942459.09 | 27772009.20 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5610520.79 | 6135266.98 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15055023.19 | 324631.27 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15178326.43 | 1754551.54 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3239299.99 | 11605242.60 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 120209.28 | 36972615.98 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65687157.69 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86466760.99 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40332043.95 | 0.557808E+09 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324631.27 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15178326.43 | 98625022.81 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97601296.79 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94163405.83 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 759.64 | 76289613.19 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 155093.28 | 49585594.05 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 757047.17 | 29542279.08 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4890679.69 | 9180866.20 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13852493.62 | 1450020.86 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14467229.73 | 3228505.61 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2614482.46 | 13810444.79 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61908.07 | 37556087.61 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64636562.61 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85171791.14 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36799693.67 | 0.562216E+09 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1450020.86 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14467229.73 | 97601296.79 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.120431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120226E+09 |
February | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115521E+09 |
March | 0.387034E+10 | 0.120803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3481.16 | 92356625.60 |
April | 0.373454E+10 | 0.116348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252752.68 | 60035694.21 |
May | 0.386038E+10 | 0.120640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 925610.74 | 36354592.20 |
June | 0.374269E+10 | 0.116882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4403321.15 | 12857133.38 |
July | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10807779.95 | 2600719.28 |
August | 0.386853E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11362163.68 | 5498386.32 |
September | 0.373273E+10 | 0.116395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1869713.89 | 19115455.79 |
October | 0.385404E+10 | 0.120385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106672.84 | 48845101.61 |
November | 0.372639E+10 | 0.116789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79340471.32 |
December | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104860E+09 |
Annual Sum or Average | 0.454292E+11 | 0.141847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29731496.09 | 0.697612E+09 |
Minimum of Months | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2600719.28 |
Maximum of Months | 0.387034E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11362163.68 | 0.120226E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98398267.36 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95178908.79 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3840.16 | 77022790.31 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 175344.96 | 49356252.87 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 921561.98 | 27842173.54 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5501523.84 | 6226708.42 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14824051.73 | 337965.92 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14962519.95 | 1767971.44 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3147864.09 | 11650983.59 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 111142.59 | 36936375.30 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65289641.61 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86186711.55 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39647849.32 | 0.556195E+09 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337965.92 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14962519.95 | 98398267.36 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97514840.34 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94044272.32 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75992202.71 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 152481.62 | 49546466.92 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 758217.47 | 30193401.47 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4825975.97 | 10195352.86 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13705070.27 | 1343653.48 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14343469.97 | 2906940.64 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2567001.03 | 14070026.39 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59391.18 | 37731977.45 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64216856.11 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84987859.42 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36411607.50 | 0.562744E+09 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343653.48 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14343469.97 | 97514840.34 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 82499421.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51370536.77 |
February | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49724319.02 |
March | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1967.47 | 40005231.31 |
April | 0.293479E+09 | 79933153.27 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89639.62 | 25532187.14 |
May | 0.303504E+09 | 82171588.45 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 473361.83 | 14279947.15 |
June | 0.293842E+09 | 79298985.31 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2821379.55 | 3164530.47 |
July | 0.303141E+09 | 82816505.16 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7592221.84 | 173160.65 |
August | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7664765.04 | 906560.93 |
September | 0.293479E+09 | 79954650.76 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1610175.51 | 6009138.83 |
October | 0.303322E+09 | 82488672.43 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53748.10 | 19103402.28 |
November | 0.293661E+09 | 79616069.29 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34333847.56 |
December | 0.303141E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45127656.43 |
Annual Sum or Average | 0.357224E+10 | 0.969799E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20307258.97 | 0.289731E+09 |
Minimum of Months | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173160.65 |
Maximum of Months | 0.303685E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7664765.04 | 51370536.77 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.257787E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269239E+09 |
February | 0.415303E+11 | 0.226874E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257060E+09 |
March | 0.461508E+11 | 0.244509E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215235E+09 |
April | 0.445315E+11 | 0.227067E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 220398.59 | 0.145864E+09 |
May | 0.460320E+11 | 0.224791E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1198959.01 | 92177503.25 |
June | 0.446286E+11 | 0.214222E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7000232.17 | 32718450.52 |
July | 0.459349E+11 | 0.221387E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18257622.37 | 7602355.54 |
August | 0.461292E+11 | 0.230551E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20809050.72 | 13080584.06 |
September | 0.445099E+11 | 0.232023E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3073842.10 | 47804184.17 |
October | 0.459565E+11 | 0.248267E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91560.77 | 0.114489E+09 |
November | 0.444343E+11 | 0.245588E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186279E+09 |
December | 0.459349E+11 | 0.258248E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239314E+09 |
Annual Sum or Average | 0.541708E+12 | 0.283131E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 50651665.72 | 0.162086E+10 |
Minimum of Months | 0.415303E+11 | 0.214222E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7602355.54 |
Maximum of Months | 0.461508E+11 | 0.258248E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20809050.72 | 0.269239E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.257787E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272278E+09 |
February | 0.415303E+11 | 0.226874E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259797E+09 |
March | 0.461508E+11 | 0.244509E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217523E+09 |
April | 0.445315E+11 | 0.227067E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 194057.99 | 0.147559E+09 |
May | 0.460320E+11 | 0.224791E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1162467.09 | 93128060.59 |
June | 0.446286E+11 | 0.214222E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6874736.75 | 32980546.67 |
July | 0.459349E+11 | 0.221387E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18068260.35 | 7631194.71 |
August | 0.461292E+11 | 0.230551E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20582027.78 | 13133329.65 |
September | 0.445099E+11 | 0.232023E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2969038.70 | 48335890.81 |
October | 0.459565E+11 | 0.248267E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68103.50 | 0.115786E+09 |
November | 0.444343E+11 | 0.245588E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188487E+09 |
December | 0.459349E+11 | 0.258248E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241928E+09 |
Annual Sum or Average | 0.541708E+12 | 0.283131E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 49918692.17 | 0.163857E+10 |
Minimum of Months | 0.415303E+11 | 0.214222E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7631194.71 |
Maximum of Months | 0.461508E+11 | 0.258248E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20582027.78 | 0.272278E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113250E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245797E+09 |
February | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234365E+09 |
March | 0.410691E+10 | 0.113599E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194915E+09 |
April | 0.396281E+10 | 0.109410E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 150505.68 | 0.131387E+09 |
May | 0.409635E+10 | 0.113446E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 992621.90 | 82184815.29 |
June | 0.397146E+10 | 0.109912E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 6005752.26 | 28585408.78 |
July | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 16225661.07 | 6103031.16 |
August | 0.410499E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 18251229.90 | 11064990.09 |
September | 0.396089E+10 | 0.109454E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 2524447.87 | 42374081.68 |
October | 0.408962E+10 | 0.113207E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 27284.98 | 0.102991E+09 |
November | 0.395417E+10 | 0.109825E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169111E+09 |
December | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217875E+09 |
Annual Sum or Average | 0.482060E+11 | 0.133389E+11 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 44177503.66 | 0.146675E+10 |
Minimum of Months | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6103031.16 |
Maximum of Months | 0.410691E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 18251229.90 | 0.245797E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.127458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213435E+09 |
February | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205138E+09 |
March | 0.409620E+10 | 0.127851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1040.44 | 0.164352E+09 |
April | 0.395248E+10 | 0.123137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313620.25 | 0.106750E+09 |
May | 0.408566E+10 | 0.127679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1255251.88 | 64788897.72 |
June | 0.396110E+10 | 0.123701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6733567.47 | 22585068.72 |
July | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17122097.48 | 4533543.79 |
August | 0.409429E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18762318.89 | 9170360.98 |
September | 0.395056E+10 | 0.123186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2946278.83 | 32882142.93 |
October | 0.407896E+10 | 0.127409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117736.09 | 83895008.97 |
November | 0.394385E+10 | 0.123603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140242E+09 |
December | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186262E+09 |
Annual Sum or Average | 0.480803E+11 | 0.150123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47251911.33 | 0.123403E+10 |
Minimum of Months | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4533543.79 |
Maximum of Months | 0.409620E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18762318.89 | 0.213435E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 9271.23 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 9271.23 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 9271.23 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 9271.23 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 9271.23 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 9271.23 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 9271.23 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 9271.23 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 9271.23 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 9271.23 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 9271.23 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 9271.23 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 512.31 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 113.12 | 02-JAN-05:00 |
February | 1169.53 | 01-FEB-00:10 | 512.31 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 116.22 | 06-FEB-03:00 |
March | 1169.53 | 01-MAR-00:10 | 512.31 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 27-MAR-16:00 | 85.80 | 23-MAR-06:00 |
April | 1169.53 | 01-APR-00:10 | 512.31 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.90 | 08-APR-09:55 | 60.51 | 03-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 512.31 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 | 30-MAY-13:00 | 46.98 | 01-MAY-05:00 |
June | 1169.53 | 01-JUN-00:10 | 512.31 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.73 | 19-JUN-12:00 | 24.75 | 03-JUN-03:00 |
July | 1169.53 | 01-JUL-00:10 | 512.31 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.16 | 07-JUL-12:00 | 10.12 | 02-JUL-03:00 |
August | 1169.53 | 01-AUG-00:10 | 512.31 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.97 | 24-AUG-15:00 | 20.17 | 08-AUG-05:00 |
September | 1169.53 | 01-SEP-00:10 | 512.31 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.19 | 01-SEP-14:00 | 35.13 | 30-SEP-01:00 |
October | 1169.53 | 01-OCT-23:10 | 512.31 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.02 | 25-OCT-11:40 | 60.87 | 09-OCT-06:00 |
November | 1169.53 | 01-NOV-00:10 | 512.31 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 83.57 | 24-NOV-07:00 |
December | 1169.53 | 01-DEC-00:10 | 512.31 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 97.32 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.12 | |||||
Maximum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 35.73 | 116.22 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 593.26 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 43.67 | 02-JAN-05:00 |
February | 1354.32 | 01-FEB-00:10 | 593.26 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 44.86 | 06-FEB-03:00 |
March | 1354.32 | 01-MAR-00:10 | 593.26 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 | 27-MAR-15:55 | 34.25 | 23-MAR-06:00 |
April | 1354.32 | 01-APR-00:10 | 593.26 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.71 | 07-APR-13:00 | 24.52 | 03-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 593.26 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 30-MAY-13:00 | 19.78 | 01-MAY-05:00 |
June | 1354.32 | 01-JUN-00:10 | 593.26 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.95 | 19-JUN-12:00 | 11.91 | 03-JUN-03:00 |
July | 1354.32 | 01-JUL-00:10 | 593.26 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.77 | 07-JUL-12:00 | 5.92 | 02-JUL-03:00 |
August | 1354.32 | 01-AUG-00:10 | 593.26 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 24-AUG-15:00 | 10.11 | 08-AUG-05:00 |
September | 1354.32 | 01-SEP-00:10 | 593.26 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.29 | 01-SEP-14:00 | 15.66 | 30-SEP-01:00 |
October | 1354.32 | 01-OCT-23:10 | 593.26 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.46 | 25-OCT-10:55 | 25.44 | 09-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 593.26 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 32.95 | 24-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 593.26 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 38.16 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.92 | |||||
Maximum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 14.95 | 44.86 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 103.20 | 02-JAN-05:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 106.03 | 06-FEB-03:00 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 | 27-MAR-15:55 | 78.28 | 23-MAR-06:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.32 | 07-APR-13:00 | 55.20 | 03-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.13 | 30-MAY-13:00 | 44.35 | 01-MAY-05:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.96 | 19-JUN-12:00 | 26.73 | 03-JUN-03:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.22 | 07-JUL-12:00 | 13.37 | 02-JUL-03:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.09 | 24-AUG-16:00 | 23.18 | 08-AUG-05:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.96 | 01-SEP-14:00 | 35.38 | 24-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.59 | 25-OCT-10:55 | 57.79 | 09-OCT-06:00 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 76.24 | 24-NOV-07:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 88.78 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.37 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 34.96 | 106.03 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 152.61 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 59.54 | 02-JAN-05:00 |
February | 220.32 | 01-FEB-00:10 | 152.61 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 61.17 | 06-FEB-03:00 |
March | 220.32 | 01-MAR-00:10 | 152.61 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.82 | 27-MAR-15:55 | 45.16 | 23-MAR-06:00 |
April | 220.32 | 01-APR-00:10 | 152.61 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 | 07-APR-13:00 | 31.85 | 03-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 152.61 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.01 | 30-MAY-13:00 | 25.29 | 01-MAY-05:00 |
June | 220.32 | 01-JUN-00:10 | 152.61 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.10 | 19-JUN-12:00 | 15.19 | 03-JUN-03:00 |
July | 220.32 | 01-JUL-00:10 | 152.61 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 07-JUL-12:00 | 7.44 | 02-JUL-03:00 |
August | 220.32 | 01-AUG-00:10 | 152.61 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.55 | 24-AUG-16:00 | 13.10 | 08-AUG-05:00 |
September | 220.32 | 01-SEP-00:10 | 152.61 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.51 | 01-SEP-14:00 | 19.99 | 24-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 152.61 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 | 25-OCT-10:55 | 32.91 | 09-OCT-04:00 |
November | 220.32 | 01-NOV-00:10 | 152.61 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 43.98 | 24-NOV-07:00 |
December | 220.32 | 01-DEC-00:10 | 152.61 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 51.22 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.44 | |||||
Maximum of Months | 220.32 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 20.10 | 61.17 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 400.68 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 150.43 | 02-JAN-07:10 |
February | 907.20 | 01-FEB-00:10 | 400.68 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 153.67 | 06-FEB-07:10 |
March | 907.20 | 01-MAR-00:10 | 400.68 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 1.65 | 27-MAR-16:00 | 118.01 | 23-MAR-06:00 |
April | 907.20 | 01-APR-00:10 | 400.68 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 16.01 | 07-APR-13:00 | 86.54 | 03-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 400.68 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 28.35 | 30-MAY-13:00 | 67.21 | 01-MAY-05:10 |
June | 907.20 | 01-JUN-00:10 | 400.68 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 52.41 | 19-JUN-12:00 | 38.07 | 02-JUN-06:00 |
July | 907.20 | 01-JUL-00:10 | 400.68 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 43.02 | 07-JUL-12:00 | 18.55 | 01-JUL-23:00 |
August | 907.20 | 01-AUG-00:10 | 400.68 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 43.21 | 24-AUG-16:00 | 31.79 | 08-AUG-05:10 |
September | 907.20 | 01-SEP-00:10 | 400.68 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 30.05 | 01-SEP-14:20 | 52.16 | 24-SEP-06:10 |
October | 907.20 | 01-OCT-23:10 | 400.68 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 12.29 | 25-OCT-10:50 | 87.46 | 29-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 400.68 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 115.70 | 24-NOV-07:10 |
December | 907.20 | 01-DEC-00:10 | 400.68 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 131.19 | 31-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 18.55 | ||||||
Maximum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 52.41 | 153.67 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1573.46 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 250.10 | 02-JAN-05:00 |
February | 15368.40 | 01-FEB-00:10 | 1573.46 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 257.49 | 06-FEB-03:00 |
March | 15368.40 | 01-MAR-00:10 | 1573.46 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 197.35 | 23-MAR-04:20 |
April | 15368.40 | 01-APR-00:10 | 1573.46 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.68 | 08-APR-09:55 | 140.09 | 01-APR-04:00 |
May | 15368.40 | 01-MAY-00:10 | 1573.46 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.13 | 30-MAY-13:00 | 114.41 | 01-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 1573.46 | 01-JUN-19:19 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.06 | 19-JUN-10:55 | 68.63 | 03-JUN-03:00 |
July | 15368.40 | 01-JUL-00:10 | 1573.46 | 03-JUL-19:30 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.19 | 07-JUL-10:55 | 31.60 | 02-JUL-03:00 |
August | 15368.40 | 01-AUG-00:10 | 1573.46 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.83 | 24-AUG-15:40 | 58.30 | 08-AUG-05:00 |
September | 15368.40 | 01-SEP-00:10 | 1573.46 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.63 | 01-SEP-14:00 | 90.91 | 30-SEP-01:00 |
October | 15368.40 | 01-OCT-23:10 | 1573.46 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.89 | 25-OCT-11:40 | 143.00 | 29-OCT-07:00 |
November | 15368.40 | 01-NOV-00:10 | 1573.46 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 190.89 | 24-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 1573.46 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 217.09 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.60 | |||||
Maximum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 82.06 | 257.49 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 10645.38 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 730.62 | 02-JAN-05:00 |
February | 45622.98 | 01-FEB-00:10 | 10645.38 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 753.90 | 06-FEB-03:00 |
March | 45622.98 | 01-MAR-00:10 | 10645.38 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 577.39 | 23-MAR-04:40 |
April | 45622.98 | 01-APR-00:10 | 10645.38 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.43 | 07-APR-13:00 | 413.89 | 03-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 10645.38 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.85 | 30-MAY-13:00 | 339.88 | 01-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 10645.38 | 01-JUN-19:19 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.24 | 19-JUN-12:00 | 204.07 | 03-JUN-03:00 |
July | 45622.98 | 01-JUL-00:10 | 10645.38 | 03-JUL-19:30 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.69 | 07-JUL-12:00 | 101.91 | 02-JUL-03:00 |
August | 45622.98 | 01-AUG-00:10 | 10645.38 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.18 | 24-AUG-15:00 | 173.66 | 08-AUG-05:00 |
September | 45622.98 | 01-SEP-00:10 | 10645.38 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.29 | 01-SEP-14:00 | 263.27 | 30-SEP-01:00 |
October | 45622.98 | 01-OCT-23:10 | 10645.38 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.91 | 25-OCT-10:55 | 426.21 | 09-OCT-06:00 |
November | 45622.98 | 01-NOV-00:10 | 10645.38 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 559.14 | 24-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 10645.38 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 639.86 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 10645.38 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.91 | |||||
Maximum of Months | 45622.98 | 10645.38 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 244.24 | 753.90 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 65.96 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 67.75 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 | 27-MAR-16:00 | 50.09 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.36 | 08-APR-09:55 | 35.40 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.06 | 30-MAY-16:00 | 27.55 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.76 | 19-JUN-12:00 | 13.91 | 03-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.34 | 10-JUL-15:10 | 4.98 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 24-AUG-16:00 | 10.92 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 01-SEP-15:10 | 20.16 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.12 | 04-OCT-15:10 | 35.62 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 48.80 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 56.78 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.98 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 21.76 | 67.75 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 65.96 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 67.75 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 50.09 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.36 | 08-APR-09:55 | 35.40 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.06 | 30-MAY-16:00 | 27.55 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.76 | 19-JUN-12:00 | 18.43 | 03-JUN-18:02 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.41 | 10-JUL-15:10 | 10.71 | 01-JUL-18:00 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 | 24-AUG-16:00 | 10.92 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 01-SEP-15:10 | 20.16 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.37 | 04-OCT-15:10 | 35.62 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 48.79 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 56.78 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.71 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 21.76 | 67.75 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 74.62 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 17.20 | 31-JAN-07:20 |
February | 0.00 | 01-FEB-00:10 | 74.62 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 19.35 | 05-FEB-24:00 |
March | 0.00 | 01-MAR-00:10 | 74.62 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 15.93 | 23-MAR-06:00 |
April | 0.00 | 01-APR-00:10 | 74.62 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 11.76 | 12-APR-06:10 |
May | 0.00 | 01-MAY-00:10 | 74.62 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 | 30-MAY-13:00 | 9.96 | 01-MAY-05:10 |
June | 0.00 | 01-JUN-00:10 | 74.62 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.55 | 19-JUN-12:00 | 6.63 | 03-JUN-03:00 |
July | 0.00 | 01-JUL-00:10 | 74.62 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.31 | 07-JUL-12:00 | 4.09 | 02-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 74.62 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 | 24-AUG-15:00 | 5.79 | 08-AUG-05:00 |
September | 0.00 | 01-SEP-00:10 | 74.62 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.02 | 01-SEP-14:00 | 8.22 | 24-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 74.62 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 12.74 | 29-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 74.62 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 15.42 | 24-NOV-08:00 |
December | 0.00 | 01-DEC-00:10 | 74.62 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 16.13 | 22-DEC-07:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 74.62 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 | |||||
Maximum of Months | 0.00 | 74.62 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 4.55 | 19.35 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 74.64 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 18.41 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 74.64 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 18.91 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 74.64 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27-MAR-15:55 | 13.98 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 74.64 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 08-APR-10:00 | 9.88 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 74.64 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.37 | 30-MAY-16:00 | 7.69 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 74.64 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.07 | 19-JUN-12:00 | 3.96 | 02-JUN-21:20 |
July | 180.00 | 01-JUL-00:10 | 74.64 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.43 | 10-JUL-15:10 | 2.23 | 01-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 74.64 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 24-AUG-15:10 | 3.05 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 74.64 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 | 01-SEP-15:10 | 5.63 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 74.64 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.22 | 04-OCT-15:10 | 9.94 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 74.64 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 13.62 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 74.64 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 15.85 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.23 | |||||
Maximum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6.07 | 18.91 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 65.96 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 67.75 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 | 27-MAR-16:00 | 50.09 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.36 | 08-APR-10:00 | 35.40 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.06 | 30-MAY-16:00 | 27.55 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.76 | 19-JUN-12:00 | 15.24 | 02-JUN-07:10 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.45 | 10-JUL-15:10 | 4.97 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 24-AUG-15:10 | 10.92 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 01-SEP-15:10 | 20.16 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.37 | 04-OCT-15:10 | 35.62 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 48.80 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 56.78 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 21.76 | 67.75 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 65.96 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 67.75 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | 27-MAR-15:55 | 50.09 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.36 | 08-APR-10:00 | 35.40 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.06 | 30-MAY-15:50 | 27.55 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.76 | 19-JUN-12:00 | 17.34 | 02-JUN-08:50 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.45 | 10-JUL-15:10 | 8.92 | 11-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 24-AUG-15:10 | 12.67 | 25-AUG-07:50 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 01-SEP-15:10 | 20.16 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.37 | 04-OCT-15:10 | 35.62 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 48.79 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 56.78 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.92 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 21.76 | 67.75 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 79.50 | 02-JAN-05:00 |
February | 2263.36 | 01-FEB-00:10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 81.67 | 06-FEB-03:00 |
March | 2263.36 | 01-MAR-00:10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.75 | 27-MAR-15:55 | 60.32 | 23-MAR-06:00 |
April | 2263.36 | 01-APR-00:10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 | 07-APR-13:00 | 42.56 | 03-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.08 | 30-MAY-13:00 | 34.02 | 01-MAY-05:00 |
June | 2263.36 | 01-JUN-00:10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.56 | 19-JUN-12:00 | 21.08 | 03-JUN-03:00 |
July | 2263.36 | 01-JUL-00:10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.71 | 07-JUL-12:00 | 10.29 | 02-JUL-03:00 |
August | 2263.36 | 01-AUG-00:10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.77 | 24-AUG-16:00 | 17.73 | 08-AUG-05:00 |
September | 2263.36 | 01-SEP-00:10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.47 | 01-SEP-14:00 | 26.52 | 24-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.81 | 25-OCT-10:55 | 44.84 | 09-OCT-04:00 |
November | 2263.36 | 01-NOV-00:10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 58.75 | 24-NOV-07:00 |
December | 2263.36 | 01-DEC-00:10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 68.41 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.29 | ||||
Maximum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.56 | 81.67 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 66.09 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 67.88 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.69 | 27-MAR-16:00 | 50.22 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.26 | 08-APR-09:55 | 35.52 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.96 | 30-MAY-16:00 | 27.67 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 19-JUN-12:00 | 14.02 | 03-JUN-03:00 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.34 | 10-JUL-15:10 | 5.08 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.80 | 24-AUG-16:00 | 11.02 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.90 | 01-SEP-15:10 | 20.27 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.85 | 04-OCT-15:10 | 35.74 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 48.92 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 56.91 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.08 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 67.88 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 66.09 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 67.88 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 50.22 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.26 | 08-APR-09:55 | 35.52 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.95 | 30-MAY-16:00 | 27.66 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 19-JUN-12:00 | 19.89 | 03-JUN-18:02 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.24 | 10-JUL-15:10 | 11.73 | 01-JUL-18:00 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.80 | 24-AUG-16:00 | 11.02 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.90 | 01-SEP-15:10 | 20.27 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.26 | 04-OCT-15:10 | 35.74 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 48.92 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 56.90 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.02 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 67.88 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 74.64 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 33.81 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 74.64 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 34.73 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 74.64 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 | 27-MAR-16:00 | 25.69 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 74.64 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.23 | 08-APR-09:55 | 18.17 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 74.64 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.12 | 30-MAY-16:00 | 14.15 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 74.64 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.09 | 19-JUN-12:00 | 7.17 | 03-JUN-03:10 |
July | 180.00 | 01-JUL-00:10 | 74.64 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.90 | 10-JUL-15:10 | 2.60 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 74.64 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.64 | 24-AUG-16:00 | 5.64 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 74.64 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.62 | 01-SEP-15:10 | 10.37 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 74.64 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.82 | 02-OCT-16:00 | 18.29 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 74.64 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 25.03 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 74.64 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 29.12 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.60 | |||||
Maximum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 11.09 | 34.73 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 171.75 | 02-JAN-05:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 176.10 | 06-FEB-03:00 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 135.23 | 23-MAR-04:30 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.45 | 07-APR-13:00 | 99.90 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.59 | 30-MAY-13:00 | 80.44 | 01-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.91 | 19-JUN-12:00 | 46.71 | 03-JUN-03:10 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.78 | 07-JUL-12:00 | 24.67 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.24 | 24-AUG-15:40 | 39.40 | 08-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.21 | 01-SEP-14:00 | 62.24 | 24-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.08 | 25-OCT-10:55 | 100.51 | 09-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 131.53 | 24-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 152.53 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 50.91 | 176.10 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 172.75 | 02-JAN-05:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 177.12 | 06-FEB-03:00 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 135.98 | 23-MAR-04:30 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.24 | 07-APR-13:00 | 99.90 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.20 | 30-MAY-13:00 | 80.44 | 01-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2763.12 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.31 | 19-JUN-12:00 | 46.71 | 03-JUN-03:10 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.51 | 07-JUL-12:00 | 24.67 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.24 | 24-AUG-15:40 | 39.40 | 08-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.21 | 01-SEP-14:00 | 62.24 | 24-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.15 | 25-OCT-10:55 | 100.51 | 09-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 132.44 | 24-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 152.54 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 50.31 | 177.12 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1090.83 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 154.44 | 02-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 1090.83 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 157.51 | 05-FEB-24:00 |
March | 2401.70 | 01-MAR-00:10 | 1090.83 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 121.83 | 23-MAR-06:00 |
April | 2401.70 | 01-APR-00:10 | 1090.83 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 9.59 | 07-APR-13:00 | 89.41 | 03-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1090.83 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 21.70 | 30-MAY-13:00 | 71.20 | 01-MAY-05:10 |
June | 2401.70 | 01-JUN-00:10 | 1090.83 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 45.03 | 19-JUN-12:00 | 41.07 | 03-JUN-05:10 |
July | 2401.70 | 01-JUL-00:10 | 1090.83 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 35.41 | 07-JUL-12:00 | 21.44 | 02-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 1090.83 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 35.17 | 24-AUG-15:50 | 35.28 | 08-AUG-05:00 |
September | 2401.70 | 01-SEP-00:10 | 1090.83 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 25.29 | 01-SEP-14:00 | 55.70 | 24-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1090.83 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 3.36 | 04-OCT-13:00 | 89.96 | 09-OCT-06:00 |
November | 2401.70 | 01-NOV-00:10 | 1090.83 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 118.96 | 24-NOV-07:00 |
December | 2401.70 | 01-DEC-00:10 | 1090.83 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 136.55 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 21.44 | ||||||
Maximum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 45.03 | 157.51 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 140.94 | 02-JAN-05:00 |
February | 2395.44 | 01-FEB-00:10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 144.79 | 06-FEB-03:00 |
March | 2395.44 | 01-MAR-00:10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 | 27-MAR-15:55 | 106.99 | 23-MAR-06:00 |
April | 2395.44 | 01-APR-00:10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.47 | 07-APR-13:00 | 75.56 | 03-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.39 | 30-MAY-13:00 | 58.76 | 01-MAY-05:00 |
June | 2395.44 | 01-JUN-00:10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.03 | 19-JUN-12:00 | 35.82 | 03-JUN-03:00 |
July | 2395.44 | 01-JUL-00:10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.62 | 07-JUL-12:00 | 16.94 | 02-JUL-03:00 |
August | 2395.44 | 01-AUG-00:10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.38 | 24-AUG-15:00 | 29.80 | 08-AUG-05:00 |
September | 2395.44 | 01-SEP-00:10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.71 | 01-SEP-14:00 | 45.64 | 30-SEP-01:00 |
October | 2395.44 | 01-OCT-23:10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 25-OCT-10:55 | 76.02 | 09-OCT-06:00 |
November | 2395.44 | 01-NOV-00:10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 104.21 | 24-NOV-07:00 |
December | 2395.44 | 01-DEC-00:10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 121.30 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.94 | ||||
Maximum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.03 | 144.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 12233.89 | 20-JAN-21:00 | 8945.92 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12016.15 | 01-FEB-21:00 | 8945.92 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11335.68 | 03-MAR-21:00 | 8945.92 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11850.43 | 08-APR-10:33 | 11501.89 | 7726.12 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11967.36 | 29-MAY-10:33 | 11501.89 | 9271.10 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13800.67 | 22-JUN-18:03 | 53675.50 | 49446.67 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13920.50 | 11-JUL-17:09 | 51119.52 | 49446.94 | 56781.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15495.76 | 24-AUG-19:30 | 26837.75 | 27813.70 | 28897.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15276.08 | 22-SEP-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17577.41 | 27-OCT-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17229.19 | 03-NOV-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15513.35 | 01-DEC-22:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11335.68 | 8945.92 | 7726.12 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17577.41 | 53675.50 | 49446.94 | 56781.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2422.95 | 17-JAN-13:10 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.92 |
February | 2170.79 | 02-FEB-13:40 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.74 |
March | 2978.21 | 03-MAR-13:20 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.67 |
April | 3139.42 | 08-APR-12:30 | 389.84 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.18 |
May | 2482.87 | 31-MAY-10:35 | 519.79 | 284.62 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 | 0.00 |
June | 2707.41 | 19-JUN-13:20 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 | 0.00 |
July | 2941.11 | 08-JUL-12:10 | 389.84 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 23.01 | 0.00 |
August | 3616.68 | 22-AUG-12:40 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 18.36 | 0.00 |
September | 3793.76 | 07-SEP-12:40 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 7.28 | 0.00 |
October | 3981.32 | 04-OCT-12:10 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 | 0.00 |
November | 3087.30 | 02-NOV-12:40 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.05 |
December | 2948.09 | 17-DEC-12:50 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2170.79 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3981.32 | 519.79 | 284.62 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 | 55.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1170.78 | 19-JAN-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.82 |
February | 1162.53 | 02-FEB-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.09 |
March | 1286.70 | 03-MAR-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 |
April | 1446.35 | 07-APR-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 |
May | 1726.30 | 31-MAY-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.92 |
June | 1943.07 | 19-JUN-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.47 | 0.00 |
July | 1983.38 | 07-JUL-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.81 | 0.00 |
August | 2044.12 | 18-AUG-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 | 0.00 |
September | 1959.23 | 01-SEP-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.01 | 0.00 |
October | 1713.39 | 05-OCT-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.87 |
November | 1326.94 | 03-NOV-20:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 |
December | 1188.30 | 18-DEC-21:00 | 1053.36 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1162.53 | 1053.36 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2044.12 | 1203.84 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 5.47 | 30.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 829.36 | 19-JAN-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.29 |
February | 811.32 | 24-FEB-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.64 |
March | 923.00 | 28-MAR-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 |
April | 1123.37 | 08-APR-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 4.92 | 0.00 |
May | 1251.00 | 31-MAY-10:35 | 127.30 | 380.10 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 7.36 | 0.00 |
June | 1404.95 | 20-JUN-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.87 |
July | 1652.24 | 10-JUL-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 8.47 | 0.00 |
August | 1705.12 | 18-AUG-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 0.00 |
September | 1364.45 | 01-SEP-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 7.12 | 0.00 |
October | 1166.11 | 05-OCT-10:33 | 190.94 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.08 |
November | 1003.83 | 04-NOV-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.62 |
December | 834.78 | 19-DEC-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 811.32 | 127.30 | 380.10 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1705.12 | 286.42 | 684.18 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 8.47 | 58.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 415.76 | 19-JAN-21:00 | 171.36 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.34 |
February | 355.99 | 24-FEB-22:00 | 195.84 | 135.66 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.24 |
March | 489.59 | 28-MAR-10:33 | 146.88 | 127.18 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.54 |
April | 604.82 | 08-APR-10:33 | 220.32 | 127.18 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 0.00 |
May | 670.53 | 31-MAY-10:35 | 97.92 | 84.79 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 4.30 | 0.00 |
June | 737.74 | 22-JUN-18:03 | 1028.16 | 813.94 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 8.19 | 0.00 |
July | 748.94 | 11-JUL-17:09 | 979.20 | 813.94 | 1427.45 | 0.00 | 0.00 | 0.00 | 0.00 | 6.96 | 0.00 |
August | 752.57 | 24-AUG-19:30 | 514.08 | 457.84 | 726.47 | 0.00 | 0.00 | 0.00 | 0.00 | 6.79 | 0.00 |
September | 723.17 | 01-SEP-17:01 | 856.80 | 712.20 | 1249.02 | 0.00 | 0.00 | 0.00 | 0.00 | 6.69 | 0.00 |
October | 623.20 | 05-OCT-10:33 | 146.88 | 127.18 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.26 |
November | 535.33 | 04-NOV-10:33 | 220.32 | 127.18 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.75 |
December | 423.55 | 19-DEC-21:00 | 171.36 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 355.99 | 97.92 | 84.79 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 752.57 | 1028.16 | 813.94 | 1427.45 | 0.00 | 0.00 | 0.00 | 0.00 | 8.19 | 34.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36560.90 | 19-JAN-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 78.84 |
February | 36466.59 | 17-FEB-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 91.99 |
March | 37263.65 | 03-MAR-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 49.73 |
April | 38041.22 | 07-APR-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 8.46 |
May | 38433.30 | 30-MAY-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 14.93 |
June | 39040.60 | 01-JUN-19:13 | 2116.80 | 1202.05 | 13718.40 | 119179.73 | 0.00 | 0.00 | 0.00 | 6.89 | 0.00 |
July | 38710.21 | 10-JUL-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 15.48 | 0.00 |
August | 40843.41 | 24-AUG-19:30 | 2116.80 | 1202.05 | 13718.40 | 119179.73 | 0.00 | 0.00 | 0.00 | 14.26 | 0.00 |
September | 38492.16 | 14-SEP-19:30 | 1411.20 | 801.37 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 9.03 | 0.00 |
October | 38068.91 | 04-OCT-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 19.02 |
November | 37351.45 | 03-NOV-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 42.63 |
December | 36590.45 | 20-DEC-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 74.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36466.59 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40843.41 | 2116.80 | 1202.05 | 13718.40 | 119179.73 | 0.00 | 0.00 | 0.00 | 15.48 | 91.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9959.43 | 17-JAN-13:00 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.22 |
February | 9887.98 | 20-FEB-13:00 | 5122.80 | 115.39 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.97 |
March | 11547.53 | 03-MAR-13:10 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.08 |
April | 12122.22 | 08-APR-12:20 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 |
May | 10697.89 | 29-MAY-10:33 | 15368.40 | 346.16 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 27.03 | 0.00 |
June | 11587.08 | 19-JUN-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 30.20 | 0.00 |
July | 11505.01 | 10-JUL-21:10 | 15368.40 | 1048.97 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 20.02 | 0.00 |
August | 12387.70 | 13-AUG-12:00 | 5122.80 | 115.39 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 41.74 | 0.00 |
September | 14032.87 | 30-SEP-12:40 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.91 |
October | 13764.78 | 04-OCT-12:00 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 0.00 |
November | 12329.02 | 04-NOV-12:30 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.94 |
December | 12263.86 | 17-DEC-11:00 | 8538.00 | 115.39 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9887.98 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14032.87 | 15368.40 | 1048.97 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 41.74 | 98.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26878.06 | 19-JAN-21:00 | 35484.54 | 10645.38 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.70 |
February | 26598.31 | 02-FEB-21:00 | 35484.54 | 10645.38 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.13 |
March | 29300.49 | 03-MAR-22:20 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.18 |
April | 34406.61 | 07-APR-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.00 |
May | 36892.29 | 31-MAY-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.28 |
June | 40426.69 | 19-JUN-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 86.24 | 0.00 |
July | 40992.97 | 10-JUL-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 57.17 | 0.00 |
August | 42005.26 | 04-AUG-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 136.50 | 0.00 |
September | 41161.47 | 01-SEP-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 47.51 | 0.00 |
October | 38211.22 | 05-OCT-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.98 |
November | 31803.53 | 03-NOV-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.97 |
December | 27960.08 | 17-DEC-11:33 | 45622.98 | 9155.03 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 26598.31 | 35484.54 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42005.26 | 45622.98 | 10645.38 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 136.50 | 502.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2721.14 | 20-JAN-16:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.09 |
February | 2766.85 | 14-FEB-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.24 |
March | 2824.30 | 11-MAR-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.45 |
April | 2932.56 | 16-APR-15:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 |
May | 3029.21 | 20-MAY-18:02 | 702.00 | 712.44 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 |
June | 3017.15 | 23-JUN-08:61 | 360.00 | 522.46 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 6.54 | 0.00 |
July | 3111.62 | 12-JUL-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 4.53 | 0.00 |
August | 3088.05 | 15-AUG-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 6.10 | 0.00 |
September | 3007.03 | 07-SEP-15:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 | 0.00 |
October | 2839.35 | 04-OCT-15:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1.27 | 0.00 |
November | 2671.85 | 04-NOV-15:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.10 |
December | 2750.03 | 18-DEC-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2671.85 | 360.00 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3111.62 | 831.60 | 712.44 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 6.54 | 41.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2400.47 | 20-JAN-16:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.96 |
February | 2469.74 | 22-FEB-16:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.71 |
March | 2705.68 | 11-MAR-16:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.25 |
April | 3094.93 | 09-APR-18:11 | 1170.00 | 1187.26 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.41 |
May | 3271.17 | 29-MAY-18:31 | 1170.00 | 1187.26 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 | 0.00 |
June | 3100.51 | 23-JUN-08:61 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 3.39 | 0.00 |
July | 3167.96 | 03-JUL-18:51 | 1386.00 | 1056.67 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 | 0.00 |
August | 3012.36 | 15-AUG-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 | 0.00 |
September | 2965.92 | 03-SEP-08:51 | 486.00 | 598.38 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 |
October | 2872.99 | 24-OCT-15:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.77 |
November | 2542.49 | 04-NOV-15:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.87 |
December | 2407.57 | 17-DEC-16:02 | 324.00 | 235.08 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2400.47 | 324.00 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3271.17 | 1386.00 | 1187.26 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 | 31.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 145.74 | 31-JAN-15:20 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.87 |
February | 351.62 | 20-FEB-13:30 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.72 |
March | 413.56 | 15-MAR-13:15 | 0.00 | 41.79 | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 |
April | 548.62 | 07-APR-12:30 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
May | 420.31 | 30-MAY-12:50 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 | 0.00 |
June | 438.08 | 19-JUN-13:20 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 3.71 | 0.00 |
July | 465.56 | 10-JUL-13:10 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 0.00 |
August | 588.89 | 30-AUG-13:00 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 | 0.00 |
September | 645.41 | 28-SEP-12:40 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 |
October | 684.49 | 04-OCT-12:10 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 |
November | 577.38 | 02-NOV-12:50 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 |
December | 395.77 | 17-DEC-13:40 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 145.74 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 684.49 | 0.00 | 41.79 | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 3.71 | 14.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 729.57 | 23-JAN-19:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.88 |
February | 759.01 | 18-FEB-09:02 | 270.00 | 209.00 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.29 |
March | 811.18 | 03-MAR-19:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.92 |
April | 946.49 | 07-APR-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.28 | 0.00 |
May | 994.68 | 30-MAY-08:21 | 324.00 | 295.59 | 998.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 | 0.00 |
June | 994.48 | 23-JUN-08:61 | 360.00 | 328.43 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 0.00 |
July | 984.25 | 03-JUL-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 0.00 |
August | 991.20 | 12-AUG-15:02 | 324.00 | 147.80 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 2.68 | 0.00 |
September | 979.18 | 01-SEP-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 2.24 | 0.00 |
October | 894.24 | 25-OCT-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 | 0.00 |
November | 807.18 | 02-NOV-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 |
December | 762.72 | 10-DEC-09:02 | 324.00 | 250.80 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 729.57 | 270.00 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 994.68 | 831.60 | 398.60 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 2.68 | 8.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2284.89 | 20-JAN-09:02 | 216.00 | 313.47 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 |
February | 2562.22 | 25-FEB-09:01 | 378.00 | 465.46 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.37 |
March | 2550.27 | 11-MAR-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.18 |
April | 2677.25 | 08-APR-08:62 | 324.00 | 398.97 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 |
May | 2754.93 | 29-MAY-08:62 | 324.00 | 398.97 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 2.36 | 0.00 |
June | 2910.35 | 23-JUN-08:61 | 360.00 | 522.46 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 6.26 | 0.00 |
July | 2872.29 | 13-JUL-08:62 | 216.00 | 313.47 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 7.24 | 0.00 |
August | 2900.60 | 22-AUG-08:62 | 216.00 | 313.47 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 |
September | 2806.63 | 06-SEP-08:62 | 216.00 | 313.47 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 | 0.00 |
October | 2670.80 | 02-OCT-15:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 | 0.00 |
November | 2502.87 | 04-NOV-15:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 |
December | 2376.18 | 02-DEC-09:01 | 378.00 | 465.46 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2284.89 | 216.00 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2910.35 | 583.20 | 522.46 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 7.24 | 46.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1314.16 | 19-JAN-09:01 | 252.00 | 365.68 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.43 |
February | 2334.97 | 25-FEB-09:01 | 378.00 | 465.41 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.83 |
March | 2321.81 | 26-MAR-08:62 | 324.00 | 398.92 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 |
April | 2982.25 | 08-APR-08:51 | 540.00 | 664.87 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 |
May | 3330.19 | 30-MAY-08:62 | 216.00 | 313.44 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 |
June | 3229.63 | 26-JUN-08:32 | 216.00 | 313.44 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 |
July | 3192.04 | 11-JUL-08:32 | 180.00 | 261.20 | 566.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.73 |
August | 3185.73 | 23-AUG-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.47 |
September | 3158.72 | 03-SEP-08:51 | 486.00 | 598.38 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 |
October | 2771.49 | 05-OCT-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 |
November | 2346.22 | 04-NOV-15:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.64 |
December | 1910.60 | 20-DEC-09:01 | 252.00 | 365.68 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1314.16 | 180.00 | 261.20 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 | |
Maximum of Months | 3330.19 | 540.00 | 664.87 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1253.05 | 19-JAN-22:00 | 2011.87 | 1031.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.03 |
February | 1426.77 | 19-FEB-11:33 | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.74 |
March | 1548.29 | 29-MAR-10:33 | 1508.90 | 966.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.96 |
April | 1903.83 | 08-APR-10:33 | 2263.36 | 966.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.58 | 0.00 |
May | 2138.69 | 31-MAY-10:35 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 | 0.00 |
June | 2348.73 | 22-JUN-18:03 | 10562.33 | 6186.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.46 | 0.00 |
July | 2375.07 | 11-JUL-17:09 | 10059.36 | 6186.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.89 | 0.00 |
August | 2384.73 | 24-AUG-19:30 | 5281.16 | 3480.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.70 | 0.00 |
September | 2334.98 | 01-SEP-17:01 | 8801.94 | 5413.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.16 | 0.00 |
October | 2002.43 | 05-OCT-10:33 | 1508.90 | 966.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 |
November | 1687.18 | 04-NOV-10:45 | 1508.90 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.10 |
December | 1449.29 | 17-DEC-11:33 | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1253.05 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2384.73 | 10562.33 | 6186.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.46 | 34.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2847.74 | 20-JAN-16:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.13 |
February | 2893.55 | 14-FEB-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.27 |
March | 2969.66 | 11-MAR-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.55 |
April | 3040.87 | 10-APR-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.77 |
May | 3184.64 | 20-MAY-18:02 | 702.00 | 712.44 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 |
June | 3228.99 | 19-JUN-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 15.36 | 0.00 |
July | 3270.57 | 12-JUL-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 4.42 | 0.00 |
August | 3296.62 | 15-AUG-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 5.99 | 0.00 |
September | 3223.06 | 07-SEP-15:02 | 583.20 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 6.08 | 0.00 |
October | 2991.26 | 02-OCT-18:02 | 831.60 | 634.08 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.89 |
November | 2784.27 | 08-NOV-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.71 |
December | 2878.37 | 02-DEC-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2784.27 | 378.00 | 199.48 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3296.62 | 831.60 | 712.44 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 15.36 | 41.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1947.80 | 17-JAN-16:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.73 |
February | 2034.24 | 24-FEB-16:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.90 |
March | 2830.02 | 11-MAR-16:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 |
April | 3266.69 | 09-APR-18:11 | 1170.00 | 1187.26 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.02 |
May | 3495.40 | 29-MAY-18:31 | 1170.00 | 1187.26 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
June | 3212.06 | 23-JUN-08:61 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 3.31 | 0.00 |
July | 3277.38 | 03-JUL-18:51 | 1386.00 | 1056.67 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
August | 3166.68 | 15-AUG-18:02 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 5.96 | 0.00 |
September | 3149.10 | 10-SEP-21:51 | 1247.40 | 908.26 | 829.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.53 |
October | 2965.66 | 02-OCT-15:02 | 583.20 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 | 0.00 |
November | 2616.97 | 04-NOV-15:01 | 378.00 | 274.26 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.87 |
December | 1538.79 | 17-DEC-16:02 | 324.00 | 235.08 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1538.79 | 324.00 | 199.46 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3495.40 | 1386.00 | 1187.26 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 5.96 | 24.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1563.81 | 31-JAN-16:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.49 |
February | 1575.45 | 02-FEB-16:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 |
March | 1577.13 | 13-MAR-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.65 |
April | 1652.93 | 07-APR-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2.25 | 0.00 |
May | 1674.26 | 20-MAY-18:02 | 702.00 | 447.86 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
June | 1705.41 | 22-JUN-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 5.12 | 0.00 |
July | 1726.46 | 09-JUL-18:02 | 702.00 | 447.86 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 | 0.00 |
August | 1767.64 | 16-AUG-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 | 0.00 |
September | 1756.29 | 14-SEP-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 6.01 | 0.00 |
October | 1690.88 | 03-OCT-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 | 0.00 |
November | 1541.11 | 02-NOV-18:02 | 831.60 | 398.60 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 |
December | 1570.17 | 15-DEC-16:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1541.11 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1767.64 | 831.60 | 447.86 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 | 23.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17089.75 | 23-JAN-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.01 |
February | 16450.08 | 23-FEB-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.37 |
March | 18823.89 | 27-MAR-21:04 | 134943.84 | 9210.41 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.21 |
April | 20342.49 | 07-APR-21:53 | 188921.38 | 12894.57 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.58 |
May | 21840.84 | 31-MAY-21:52 | 269887.68 | 18420.82 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.81 |
June | 23256.39 | 19-JUN-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 18.21 | 0.00 |
July | 23053.39 | 10-JUL-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 12.07 | 0.00 |
August | 23342.76 | 04-AUG-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 27.65 | 0.00 |
September | 22420.78 | 01-SEP-21:50 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 0.00 |
October | 20562.71 | 05-OCT-21:53 | 188921.38 | 12894.57 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.97 |
November | 18537.89 | 03-NOV-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.86 |
December | 16881.19 | 04-DEC-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16450.08 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23342.76 | 269887.68 | 18420.82 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 27.65 | 84.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19118.53 | 23-JAN-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.01 |
February | 18423.32 | 23-FEB-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.37 |
March | 20801.24 | 27-MAR-21:04 | 134943.84 | 9210.41 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.21 |
April | 22042.84 | 07-APR-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.61 |
May | 23126.80 | 31-MAY-21:52 | 269887.68 | 18420.82 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.81 |
June | 24540.21 | 19-JUN-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 18.19 | 0.00 |
July | 24268.04 | 10-JUL-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 12.06 | 0.00 |
August | 24573.85 | 04-AUG-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 27.64 | 0.00 |
September | 23674.47 | 01-SEP-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 10.26 | 0.00 |
October | 21973.72 | 05-OCT-21:53 | 188921.38 | 12894.57 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.97 |
November | 20385.75 | 03-NOV-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.86 |
December | 18872.66 | 04-DEC-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18423.32 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24573.85 | 269887.68 | 18420.82 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 27.64 | 84.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25171.17 | 17-JAN-11:50 | 533.71 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 59.20 |
February | 25817.61 | 19-FEB-11:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 64.31 |
March | 26825.67 | 29-MAR-10:33 | 1601.14 | 909.03 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 63.68 |
April | 28975.79 | 08-APR-10:33 | 2401.70 | 909.03 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 |
May | 29757.83 | 29-MAY-10:33 | 2401.70 | 1090.83 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 12.36 | 0.00 |
June | 31659.78 | 01-JUN-18:02 | 11207.95 | 5817.77 | 87627.33 | 89971.33 | 0.00 | 0.00 | 0.00 | 11.64 | 0.00 |
July | 31221.33 | 11-JUL-17:09 | 10674.24 | 5817.77 | 116836.45 | 179942.65 | 0.00 | 0.00 | 0.00 | 14.06 | 0.00 |
August | 31124.09 | 22-AUG-17:01 | 10674.24 | 5817.77 | 116836.45 | 179942.65 | 0.00 | 0.00 | 0.00 | 15.50 | 0.00 |
September | 30737.00 | 01-SEP-17:01 | 9339.96 | 5090.55 | 102231.89 | 157449.82 | 0.00 | 0.00 | 0.00 | 12.73 | 0.00 |
October | 28438.03 | 04-OCT-10:33 | 1601.14 | 909.03 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 |
November | 27157.26 | 04-NOV-10:45 | 1601.14 | 606.02 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 26.95 |
December | 25688.08 | 17-DEC-11:50 | 800.57 | 363.61 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 46.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 25171.17 | 533.71 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31659.78 | 11207.95 | 5817.77 | 116836.45 | 179942.65 | 0.00 | 0.00 | 0.00 | 15.50 | 64.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3118.18 | 17-JAN-11:35 | 1064.64 | 682.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.77 |
February | 3338.71 | 19-FEB-11:33 | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.15 |
March | 3670.21 | 03-MAR-11:33 | 1596.96 | 1023.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.59 |
April | 4543.90 | 08-APR-10:50 | 1596.96 | 682.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 | 0.00 |
May | 5081.70 | 31-MAY-10:35 | 1064.64 | 682.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.02 | 0.00 |
June | 5745.16 | 19-JUN-14:10 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.63 | 0.00 |
July | 6497.62 | 11-JUL-15:07 | 7984.80 | 2046.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.11 | 0.00 |
August | 6425.54 | 16-AUG-12:50 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.82 | 0.00 |
September | 5709.03 | 01-SEP-14:10 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.43 | 0.00 |
October | 4588.89 | 05-OCT-10:33 | 1596.96 | 1023.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.26 |
November | 3816.95 | 04-NOV-10:50 | 1596.96 | 682.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.27 |
December | 3396.85 | 17-DEC-11:33 | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3118.18 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6497.62 | 7984.80 | 2046.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.63 | 52.15 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.390504E+12 | 259168.99 | 18-JAN-20:10 | 0.461879E+12 | 391126.56 | 14-JAN-17:19 |
February | 0.356021E+12 | 258459.45 | 23-FEB-20:10 | 0.412829E+12 | 422891.71 | 06-FEB-19:10 |
March | 0.394063E+12 | 280038.09 | 27-MAR-19:19 | 0.359011E+12 | 378449.12 | 31-MAR-17:00 |
April | 0.393268E+12 | 329933.27 | 07-APR-19:19 | 0.344061E+12 | 344773.69 | 20-APR-17:00 |
May | 0.448343E+12 | 357857.47 | 29-MAY-19:30 | 0.280977E+12 | 284396.84 | 01-MAY-20:30 |
June | 0.580951E+12 | 425859.04 | 19-JUN-19:40 | 0.218594E+12 | 169894.77 | 01-JUN-17:10 |
July | 0.702819E+12 | 434730.38 | 20-JUL-20:00 | 0.215013E+12 | 157024.01 | 11-JUL-17:40 |
August | 0.667218E+12 | 463186.21 | 04-AUG-19:19 | 0.217004E+12 | 165794.91 | 22-AUG-17:19 |
September | 0.528899E+12 | 413879.71 | 07-SEP-19:00 | 0.228021E+12 | 181565.27 | 24-SEP-06:10 |
October | 0.454826E+12 | 353386.88 | 05-OCT-19:10 | 0.300487E+12 | 297939.42 | 27-OCT-18:10 |
November | 0.381190E+12 | 267653.51 | 03-NOV-19:10 | 0.378932E+12 | 361729.73 | 17-NOV-18:40 |
December | 0.393248E+12 | 260912.05 | 18-DEC-20:30 | 0.389274E+12 | 365467.01 | 31-DEC-19:10 |
Annual Sum or Average | 0.569135E+13 | 0.380608E+13 | ||||
Minimum of Months | 0.356021E+12 | 258459.45 | 0.215013E+12 | 157024.01 | ||
Maximum of Months | 0.702819E+12 | 463186.21 | 0.461879E+12 | 422891.71 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.519633E+11 | 0.180295E+11 | 0.146779E+12 | 0.544823E+11 | 0.420299E+11 | 0.325864E+10 | 0.00 | 0.119572E+10 | 0.00 | 0.00 | 0.237958E+11 | 0.452836E+11 | 0.00 |
February | 0.466662E+11 | 0.151200E+11 | 0.132565E+12 | 0.492098E+11 | 0.381369E+11 | 0.406699E+10 | 0.00 | 0.236615E+10 | 0.00 | 0.00 | 0.228649E+11 | 0.417053E+11 | 0.00 |
March | 0.513801E+11 | 0.151400E+11 | 0.146789E+12 | 0.544839E+11 | 0.426250E+11 | 0.731005E+10 | 0.00 | 0.832625E+10 | 0.00 | 0.00 | 0.208745E+11 | 0.434317E+11 | 0.00 |
April | 0.493691E+11 | 0.130494E+11 | 0.142011E+12 | 0.527241E+11 | 0.427800E+11 | 0.104108E+11 | 0.00 | 0.286933E+11 | 0.00 | 0.00 | 0.102552E+11 | 0.403819E+11 | 0.00 |
May | 0.506285E+11 | 0.120641E+11 | 0.146789E+12 | 0.544825E+11 | 0.471001E+11 | 0.134604E+11 | 0.00 | 0.764897E+11 | 0.00 | 0.00 | 0.332265E+10 | 0.402639E+11 | 0.00 |
June | 0.488519E+11 | 0.109256E+11 | 0.142058E+12 | 0.527256E+11 | 0.493918E+11 | 0.138254E+11 | 0.00 | 0.209333E+12 | 0.00 | 0.00 | 0.128272E+11 | 0.373613E+11 | 0.00 |
July | 0.505008E+11 | 0.116246E+11 | 0.146742E+12 | 0.544805E+11 | 0.536880E+11 | 0.150662E+11 | 0.00 | 0.305102E+12 | 0.00 | 0.00 | 0.240513E+11 | 0.378001E+11 | 0.00 |
August | 0.508408E+11 | 0.128364E+11 | 0.146800E+12 | 0.544836E+11 | 0.548733E+11 | 0.147871E+11 | 0.00 | 0.273323E+12 | 0.00 | 0.00 | 0.172616E+11 | 0.382376E+11 | 0.00 |
September | 0.495775E+11 | 0.139482E+11 | 0.142022E+12 | 0.527243E+11 | 0.484441E+11 | 0.135130E+11 | 0.00 | 0.159053E+12 | 0.00 | 0.00 | 0.787531E+10 | 0.381004E+11 | 0.00 |
October | 0.515706E+11 | 0.160788E+11 | 0.146768E+12 | 0.544820E+11 | 0.474431E+11 | 0.131753E+11 | 0.00 | 0.744686E+11 | 0.00 | 0.00 | 0.624269E+10 | 0.408608E+11 | 0.00 |
November | 0.501363E+11 | 0.170242E+11 | 0.142074E+12 | 0.527252E+11 | 0.416924E+11 | 0.776822E+10 | 0.00 | 0.940008E+10 | 0.00 | 0.00 | 0.150618E+11 | 0.417264E+11 | 0.00 |
December | 0.519307E+11 | 0.183824E+11 | 0.146742E+12 | 0.544814E+11 | 0.421127E+11 | 0.418928E+10 | 0.00 | 0.286938E+10 | 0.00 | 0.00 | 0.241640E+11 | 0.446872E+11 | 0.00 |
Annual Sum or Average | 0.603416E+12 | 0.174223E+12 | 0.172814E+13 | 0.641485E+12 | 0.550317E+12 | 0.120831E+12 | 0.00 | 0.115062E+13 | 0.00 | 0.00 | 0.188597E+12 | 0.489840E+12 | 0.00 |
Minimum of Months | 0.466662E+11 | 0.109256E+11 | 0.132565E+12 | 0.492098E+11 | 0.381369E+11 | 0.325864E+10 | 0.00 | 0.119572E+10 | 0.00 | 0.00 | 0.332265E+10 | 0.373613E+11 | 0.00 |
Maximum of Months | 0.519633E+11 | 0.183824E+11 | 0.146800E+12 | 0.544839E+11 | 0.548733E+11 | 0.150662E+11 | 0.00 | 0.305102E+12 | 0.00 | 0.00 | 0.241640E+11 | 0.452836E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.182708E+12 | 0.00 | 0.127252E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.155834E+12 | 0.00 | 0.119792E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.892587E+11 | 0.00 | 0.117728E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.968087E+11 | 0.00 | 0.100297E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.400788E+11 | 0.00 | 0.889195E+11 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.950852E+09 | 0.00 | 0.705289E+11 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.150475E+09 | 0.00 | 0.630423E+11 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.481252E+09 | 0.00 | 0.644837E+11 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.976930E+10 | 0.00 | 0.712807E+11 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.612521E+11 | 0.00 | 0.873322E+11 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.129694E+12 | 0.00 | 0.102147E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.117775E+12 | 0.00 | 0.119678E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.884761E+12 | 0.00 | 0.113248E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.150475E+09 | 0.00 | 0.630423E+11 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.182708E+12 | 0.00 | 0.127252E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 50471.22 | 02-JAN-20:10 | 11096.45 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 39155.93 | 02-JAN-07:19 | 22651.05 | 02-JAN-19:10 | 5438.51 | 11-JAN-16:30 | 0.00 | 01-JAN-00:10 |
February | 50471.22 | 01-FEB-20:10 | 11096.45 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 39155.93 | 01-FEB-07:19 | 22876.91 | 06-FEB-19:10 | 5545.26 | 06-FEB-10:09 | 0.00 | 01-FEB-00:10 |
March | 50471.22 | 01-MAR-20:10 | 11096.45 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 39155.93 | 13-MAR-06:19 | 26169.20 | 27-MAR-21:10 | 5408.83 | 29-MAR-15:00 | 0.00 | 01-MAR-00:10 |
April | 50471.22 | 03-APR-19:10 | 11096.45 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 39154.88 | 18-APR-06:19 | 30650.03 | 07-APR-21:00 | 5673.13 | 07-APR-16:19 | 0.00 | 01-APR-00:10 |
May | 50471.22 | 01-MAY-19:10 | 11096.45 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 39154.91 | 04-MAY-06:19 | 34097.76 | 31-MAY-21:00 | 5755.88 | 31-MAY-18:10 | 0.00 | 01-MAY-00:10 |
June | 50471.22 | 01-JUN-19:19 | 11096.45 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 39154.46 | 29-JUN-06:19 | 35004.36 | 20-JUN-21:00 | 6841.42 | 24-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 50471.22 | 03-JUL-19:30 | 11096.45 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 39154.68 | 24-JUL-06:19 | 34985.77 | 13-JUL-21:10 | 6907.06 | 20-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 50471.22 | 01-AUG-19:10 | 11096.45 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 39154.65 | 16-AUG-06:19 | 36355.97 | 18-AUG-21:10 | 7534.60 | 11-AUG-20:00 | 0.00 | 01-AUG-00:10 |
September | 50471.22 | 01-SEP-19:10 | 11096.45 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 39155.45 | 27-SEP-06:19 | 36265.23 | 01-SEP-20:19 | 7085.22 | 07-SEP-19:00 | 0.00 | 01-SEP-00:10 |
October | 50471.22 | 02-OCT-19:10 | 11096.45 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 39155.93 | 16-OCT-06:19 | 33464.06 | 04-OCT-21:00 | 5667.80 | 05-OCT-15:09 | 0.00 | 01-OCT-00:10 |
November | 50471.22 | 01-NOV-19:10 | 11096.45 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 39155.93 | 01-NOV-06:19 | 27062.74 | 03-NOV-21:10 | 5425.00 | 06-NOV-09:09 | 0.00 | 01-NOV-00:10 |
December | 50471.22 | 01-DEC-20:10 | 11096.45 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 39155.93 | 08-DEC-07:19 | 22416.14 | 04-DEC-21:10 | 5445.95 | 16-DEC-16:19 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 50471.22 | 11096.45 | 88863.15 | 39154.46 | 22416.14 | 5408.83 | 0.00 | |||||||
Maximum of Months | 50471.22 | 11096.45 | 88863.15 | 39155.93 | 36355.97 | 7534.60 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 7821.64 | 17-JAN-16:10 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:20 | 39004.53 | 02-JAN-19:30 | 0.00 |
February | 13426.20 | 20-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:20 | 38417.31 | 27-FEB-19:10 | 0.00 |
March | 66935.54 | 27-MAR-15:00 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:20 | 39574.20 | 31-MAR-18:49 | 0.00 |
April | 101375.18 | 07-APR-15:09 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 40537.68 | 27-APR-18:19 | 0.00 |
May | 116100.09 | 31-MAY-15:20 | 0.00 | 0.00 | 9938.94 | 01-MAY-01:30 | 41877.02 | 31-MAY-20:30 | 0.00 |
June | 181404.06 | 19-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-09:00 | 42355.78 | 30-JUN-20:40 | 0.00 |
July | 174336.10 | 20-JUL-20:00 | 0.00 | 0.00 | 9938.94 | 01-JUL-08:20 | 41475.59 | 25-JUL-20:49 | 0.00 |
August | 196240.11 | 04-AUG-19:10 | 0.00 | 0.00 | 9938.94 | 01-AUG-00:10 | 42459.95 | 25-AUG-17:10 | 0.00 |
September | 158617.61 | 07-SEP-19:00 | 0.00 | 0.00 | 9938.94 | 01-SEP-00:10 | 43132.15 | 01-SEP-20:00 | 0.00 |
October | 113377.39 | 03-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 03-OCT-12:50 | 42691.68 | 03-OCT-17:00 | 0.00 |
November | 44076.79 | 04-NOV-11:50 | 0.00 | 0.00 | 9938.94 | 01-NOV-01:39 | 41669.62 | 01-NOV-18:40 | 0.00 |
December | 14615.99 | 18-DEC-10:00 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 40295.38 | 01-DEC-19:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 7821.64 | 0.00 | 0.00 | 9938.94 | 38417.31 | 0.00 | |||
Maximum of Months | 196240.11 | 0.00 | 0.00 | 9938.94 | 43132.15 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 259168.99 | 18-JAN-20:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 21404.69 | 5049.51 | 0.00 | 2448.42 | 0.00 |
February | 258459.45 | 23-FEB-20:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 21108.22 | 5079.96 | 0.00 | 1844.50 | 0.00 |
March | 280038.09 | 27-MAR-19:19 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 22651.90 | 5038.22 | 0.00 | 31250.31 | 0.00 |
April | 329933.27 | 07-APR-19:19 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 24410.02 | 5319.20 | 0.00 | 77356.80 | 0.00 |
May | 357857.47 | 29-MAY-19:30 | 46435.92 | 86521.75 | 11096.45 | 31540.10 | 26686.53 | 5511.42 | 0.00 | 100635.65 | 0.00 |
June | 425859.04 | 19-JUN-19:40 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 30049.93 | 6170.25 | 0.00 | 158930.96 | 0.00 |
July | 434730.38 | 20-JUL-20:00 | 44879.15 | 88373.09 | 11096.45 | 24006.45 | 32710.72 | 6819.94 | 0.00 | 174336.10 | 0.00 |
August | 463186.21 | 04-AUG-19:19 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 31960.30 | 6619.85 | 0.00 | 194004.49 | 0.00 |
September | 413879.71 | 07-SEP-19:00 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 29976.31 | 7085.22 | 0.00 | 158617.61 | 0.00 |
October | 353386.88 | 05-OCT-19:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 25184.38 | 5622.13 | 0.00 | 90852.66 | 0.00 |
November | 267653.51 | 03-NOV-19:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 24128.51 | 5018.57 | 0.00 | 13798.73 | 0.00 |
December | 260912.05 | 18-DEC-20:30 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 20855.88 | 5037.09 | 0.00 | 3452.80 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 258459.45 | 44879.15 | 86521.75 | 11096.45 | 24006.45 | 20855.88 | 5018.57 | 0.00 | 1844.50 | 0.00 | |
Maximum of Months | 463186.21 | 50471.22 | 88373.09 | 11096.45 | 31577.78 | 32710.72 | 7085.22 | 0.00 | 194004.49 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 231338.65 | 14-JAN-16:10 | 0.00 | 128423.66 | 25-JAN-21:49 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 232046.90 | 06-FEB-09:09 | 0.00 | 136843.69 | 06-FEB-21:49 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 164987.07 | 31-MAR-17:00 | 0.00 | 114499.24 | 01-MAR-19:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 159002.00 | 15-APR-15:09 | 0.00 | 98552.34 | 01-APR-18:10 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 129474.54 | 01-MAY-20:30 | 0.00 | 80204.41 | 01-MAY-21:00 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 28685.39 | 03-JUN-04:00 | 0.00 | 58927.81 | 01-JUN-22:30 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 22470.34 | 11-JUL-15:50 | 0.00 | 44885.45 | 01-JUL-18:00 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 22006.45 | 19-AUG-12:30 | 0.00 | 45094.81 | 31-AUG-19:19 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 116754.64 | 24-SEP-05:49 | 0.00 | 59052.73 | 30-SEP-22:49 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 143703.66 | 16-OCT-05:00 | 0.00 | 78158.85 | 31-OCT-17:10 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 171079.07 | 28-NOV-16:10 | 0.00 | 101270.24 | 30-NOV-19:19 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 167243.25 | 31-DEC-23:00 | 0.00 | 119088.51 | 21-DEC-21:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 22006.45 | 0.00 | 44885.45 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 232046.90 | 0.00 | 136843.69 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.76 | 1.17 | 24.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.75 | 0.83 | 24.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.63 | 1.33 | 24.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.33 | 24.70 | 3.33 | 24.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.76 | 1.33 | 24.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.72 | 0.33 | 21.72 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.76 | 0.67 | 21.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.79 | 1.50 | 21.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.76 | 2.50 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.78 | 3.17 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 21.86 | 4.67 | 21.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.83 | 2.50 | 21.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.77 | 1.50 | 21.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.83 | 21.80 | 16.83 | 21.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 21.86 | 4.67 | 21.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.91 | 0.67 | 21.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.88 | 2.67 | 21.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 21.82 | 6.67 | 21.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 21.79 | 6.83 | 21.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 21.82 | 5.50 | 21.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.75 | 2.17 | 21.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 24.50 | 21.81 | 24.50 | 21.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 21.91 | 6.83 | 21.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.54 | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
February | 0.17 | 20.47 | 0.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.70 | 0.50 | 21.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 21.83 | 7.50 | 21.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 21.89 | 15.17 | 21.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 21.85 | 17.00 | 21.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 21.78 | 11.00 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 21.81 | 6.33 | 21.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.73 | 0.83 | 21.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 20.50 | 0.33 | 20.50 | 58.33 | 21.82 | 58.33 | 21.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.54 | 0.17 | 20.54 | 17.00 | 21.89 | 17.00 | 21.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.78 | 1.17 | 21.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.83 | 1.17 | 21.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.75 | 0.83 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.72 | 1.83 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.80 | 0.67 | 21.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.67 | 21.77 | 5.67 | 21.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.83 | 1.83 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.20 | 0.33 | 22.20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 22.34 | 4.33 | 22.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 22.26 | 8.00 | 22.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 22.17 | 8.50 | 22.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 22.18 | 8.33 | 22.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 22.26 | 5.17 | 22.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 22.13 | 1.17 | 22.13 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 35.83 | 22.23 | 35.83 | 22.23 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 22.34 | 8.50 | 22.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.79 | 0.67 | 21.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.79 | 2.50 | 21.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.80 | 2.67 | 21.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.82 | 3.00 | 21.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 21.88 | 5.67 | 21.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.83 | 3.17 | 21.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.76 | 1.67 | 21.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 19.67 | 21.82 | 19.67 | 21.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 21.88 | 5.67 | 21.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 22.05 | 0.67 | 22.05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.90 | 4.83 | 21.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 21.88 | 7.50 | 21.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 21.83 | 7.17 | 21.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 21.84 | 6.33 | 21.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.76 | 2.67 | 21.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 29.33 | 21.85 | 29.33 | 21.85 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 22.05 | 7.50 | 22.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.76 | 0.17 | 21.76 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.88 | 1.33 | 21.88 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.76 | 1.00 | 21.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.71 | 1.50 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.76 | 3.67 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.79 | 3.50 | 21.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 21.88 | 5.00 | 21.88 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.76 | 0.50 | 21.76 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.73 | 0.33 | 21.73 |
Annual Sum or Average | 0.00 | 0.00 | 17.50 | 21.80 | 17.50 | 21.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 21.88 | 5.00 | 21.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.86 | 1.67 | 24.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.96 | 4.83 | 24.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.05 | 1.50 | 25.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.91 | 4.50 | 24.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.66 | 0.50 | 24.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 13.00 | 24.93 | 13.00 | 24.93 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 25.05 | 4.83 | 25.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.85 | 0.00 | 22.85 | 0.00 | 22.85 |
February | 672.00 | 22.40 | 0.00 | 22.40 | 0.00 | 22.40 |
March | 744.00 | 22.01 | 0.00 | 22.01 | 0.00 | 22.01 |
April | 720.00 | 21.79 | 0.00 | 21.79 | 0.00 | 21.79 |
May | 744.00 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
June | 720.00 | 22.09 | 0.00 | 22.09 | 0.00 | 22.09 |
July | 744.00 | 22.53 | 0.00 | 22.53 | 0.00 | 22.53 |
August | 713.33 | 23.00 | 0.00 | 23.00 | 0.00 | 23.00 |
September | 372.00 | 23.36 | 133.50 | 23.49 | 0.00 | 23.49 |
October | 333.00 | 23.75 | 174.00 | 23.81 | 0.00 | 23.81 |
November | 558.83 | 23.72 | 11.50 | 23.73 | 0.00 | 23.73 |
December | 738.50 | 23.48 | 0.00 | 23.48 | 0.00 | 23.48 |
Annual Sum or Average | 7803.67 | 22.62 | 319.00 | 22.67 | 0.00 | 22.67 |
Minimum of Months | 333.00 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
Maximum of Months | 744.00 | 23.75 | 174.00 | 23.81 | 0.00 | 23.81 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 736.00 | 21.12 | 374.50 | 21.08 | 374.50 | 21.06 |
February | 656.67 | 21.18 | 335.00 | 21.12 | 335.00 | 21.09 |
March | 708.67 | 21.23 | 117.67 | 21.22 | 112.33 | 21.19 |
April | 674.17 | 21.33 | 37.33 | 21.39 | 18.67 | 21.38 |
May | 685.50 | 21.53 | 17.67 | 21.58 | 0.00 | 21.58 |
June | 513.67 | 22.11 | 110.17 | 22.36 | 0.00 | 22.36 |
July | 302.50 | 22.37 | 268.00 | 22.94 | 0.00 | 22.94 |
August | 210.33 | 22.40 | 394.00 | 23.25 | 0.00 | 23.25 |
September | 459.17 | 21.93 | 186.33 | 22.47 | 0.00 | 22.47 |
October | 524.83 | 21.74 | 138.67 | 22.18 | 0.00 | 22.18 |
November | 686.67 | 21.21 | 117.83 | 21.23 | 106.17 | 21.20 |
December | 721.33 | 21.14 | 339.67 | 21.10 | 339.67 | 21.07 |
Annual Sum or Average | 6879.50 | 21.48 | 2436.83 | 21.69 | 1286.33 | 21.60 |
Minimum of Months | 210.33 | 21.12 | 17.67 | 21.08 | 0.00 | 21.06 |
Maximum of Months | 736.00 | 22.40 | 394.00 | 23.25 | 374.50 | 23.25 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.45 | 40.17 | 21.42 | 40.17 | 21.40 |
February | 672.00 | 21.54 | 43.17 | 21.51 | 43.17 | 21.48 |
March | 744.00 | 21.96 | 0.00 | 21.96 | 0.00 | 21.96 |
April | 698.50 | 22.27 | 0.17 | 22.27 | 0.00 | 22.27 |
May | 662.00 | 22.64 | 32.17 | 22.69 | 5.00 | 22.70 |
June | 305.83 | 22.91 | 252.00 | 23.32 | 0.67 | 23.32 |
July | 124.17 | 22.95 | 425.00 | 23.64 | 0.00 | 23.64 |
August | 85.33 | 23.10 | 438.50 | 23.76 | 2.50 | 23.76 |
September | 345.83 | 22.91 | 192.00 | 23.25 | 0.00 | 23.25 |
October | 557.00 | 22.90 | 87.00 | 23.02 | 0.50 | 23.02 |
November | 718.50 | 22.04 | 0.00 | 22.04 | 0.00 | 22.04 |
December | 744.00 | 21.67 | 3.50 | 21.66 | 3.50 | 21.66 |
Annual Sum or Average | 6401.17 | 22.15 | 1513.67 | 22.44 | 95.50 | 22.43 |
Minimum of Months | 85.33 | 21.45 | 0.00 | 21.42 | 0.00 | 21.40 |
Maximum of Months | 744.00 | 23.10 | 438.50 | 23.76 | 43.17 | 23.76 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.02 | 300.00 | 21.01 | 300.00 | 21.01 |
February | 672.00 | 21.01 | 342.33 | 21.01 | 342.33 | 21.01 |
March | 744.00 | 21.12 | 69.83 | 21.11 | 69.83 | 21.10 |
April | 720.00 | 21.50 | 9.33 | 21.50 | 9.33 | 21.49 |
May | 737.83 | 22.23 | 0.00 | 22.23 | 0.00 | 22.23 |
June | 554.33 | 23.04 | 12.67 | 23.07 | 0.00 | 23.07 |
July | 208.83 | 23.25 | 128.33 | 23.51 | 0.00 | 23.51 |
August | 243.83 | 23.34 | 149.83 | 23.57 | 0.00 | 23.57 |
September | 594.83 | 22.92 | 6.17 | 22.93 | 0.00 | 22.93 |
October | 744.00 | 22.36 | 0.00 | 22.36 | 0.00 | 22.36 |
November | 720.00 | 21.33 | 51.00 | 21.31 | 51.00 | 21.29 |
December | 744.00 | 21.03 | 125.50 | 21.03 | 125.50 | 21.02 |
Annual Sum or Average | 7427.67 | 21.80 | 1195.00 | 21.79 | 898.00 | 21.72 |
Minimum of Months | 208.83 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
Maximum of Months | 744.00 | 23.34 | 342.33 | 23.57 | 342.33 | 23.57 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 352.50 | 21.00 | 352.50 | 21.00 |
February | 672.00 | 21.00 | 394.33 | 21.00 | 394.33 | 21.00 |
March | 744.00 | 21.05 | 93.67 | 21.04 | 93.67 | 21.04 |
April | 720.00 | 21.37 | 11.33 | 21.37 | 11.33 | 21.36 |
May | 744.00 | 22.08 | 0.00 | 22.08 | 0.00 | 22.08 |
June | 644.00 | 22.98 | 0.00 | 22.98 | 0.00 | 22.98 |
July | 334.50 | 23.26 | 15.83 | 23.29 | 0.00 | 23.29 |
August | 373.67 | 23.31 | 67.83 | 23.40 | 0.00 | 23.40 |
September | 679.00 | 22.84 | 0.00 | 22.84 | 0.00 | 22.84 |
October | 744.00 | 22.19 | 0.00 | 22.19 | 0.00 | 22.19 |
November | 720.00 | 21.22 | 63.00 | 21.20 | 63.00 | 21.18 |
December | 744.00 | 21.00 | 179.33 | 21.00 | 179.33 | 21.00 |
Annual Sum or Average | 7863.17 | 21.80 | 1177.83 | 21.72 | 1094.17 | 21.64 |
Minimum of Months | 334.50 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 23.31 | 394.33 | 23.40 | 394.33 | 23.40 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 326.67 | 22.40 | 373.50 | 23.02 | 129.50 | 23.17 |
February | 282.67 | 22.38 | 305.00 | 23.07 | 110.17 | 23.22 |
March | 268.00 | 22.71 | 434.83 | 23.17 | 147.33 | 23.31 |
April | 267.50 | 23.05 | 499.83 | 23.19 | 180.17 | 23.34 |
May | 298.33 | 23.45 | 615.00 | 23.21 | 243.83 | 23.37 |
June | 287.83 | 23.88 | 666.33 | 23.23 | 278.33 | 23.40 |
July | 303.00 | 23.96 | 716.17 | 23.20 | 303.00 | 23.37 |
August | 302.50 | 23.95 | 710.00 | 23.21 | 300.17 | 23.39 |
September | 291.50 | 23.75 | 646.67 | 23.24 | 269.50 | 23.41 |
October | 278.00 | 23.42 | 589.17 | 23.24 | 223.67 | 23.39 |
November | 258.50 | 22.83 | 450.83 | 23.19 | 152.33 | 23.34 |
December | 269.50 | 22.53 | 367.50 | 23.17 | 127.50 | 23.31 |
Annual Sum or Average | 3434.00 | 23.20 | 6374.83 | 23.19 | 2465.50 | 23.35 |
Minimum of Months | 258.50 | 22.38 | 305.00 | 23.02 | 110.17 | 23.17 |
Maximum of Months | 326.67 | 23.96 | 716.17 | 23.24 | 303.00 | 23.41 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 719.00 | 21.57 | 87.17 | 21.52 | 82.17 | 21.48 |
February | 632.83 | 21.73 | 49.00 | 21.72 | 40.50 | 21.68 |
March | 667.67 | 22.02 | 34.00 | 22.11 | 0.00 | 22.11 |
April | 566.33 | 22.09 | 62.83 | 22.24 | 0.00 | 22.24 |
May | 543.00 | 22.47 | 128.67 | 22.67 | 47.50 | 22.72 |
June | 346.83 | 23.18 | 464.17 | 23.37 | 209.83 | 23.45 |
July | 295.83 | 23.73 | 663.00 | 23.62 | 276.67 | 23.67 |
August | 226.83 | 23.79 | 692.83 | 23.74 | 210.17 | 23.78 |
September | 281.67 | 22.98 | 475.17 | 23.43 | 145.67 | 23.48 |
October | 362.33 | 22.93 | 375.50 | 23.36 | 88.67 | 23.40 |
November | 637.67 | 21.99 | 37.17 | 22.09 | 1.83 | 22.10 |
December | 702.50 | 21.75 | 34.83 | 21.79 | 14.67 | 21.78 |
Annual Sum or Average | 5982.50 | 22.27 | 3104.33 | 22.70 | 1117.67 | 22.78 |
Minimum of Months | 226.83 | 21.57 | 34.00 | 21.52 | 0.00 | 21.48 |
Maximum of Months | 719.00 | 23.79 | 692.83 | 23.74 | 276.67 | 23.78 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.01 | 7.67 | 22.00 | 7.67 | 21.99 |
February | 672.00 | 22.14 | 0.50 | 22.14 | 0.50 | 22.14 |
March | 734.33 | 22.49 | 0.00 | 22.49 | 0.00 | 22.49 |
April | 610.83 | 22.60 | 33.33 | 22.67 | 0.00 | 22.67 |
May | 517.17 | 22.86 | 120.83 | 23.04 | 42.50 | 23.09 |
June | 339.00 | 23.44 | 387.67 | 23.66 | 188.33 | 23.72 |
July | 260.17 | 23.88 | 559.67 | 23.82 | 239.33 | 23.86 |
August | 185.50 | 23.93 | 621.50 | 23.83 | 175.50 | 23.86 |
September | 262.83 | 23.37 | 390.83 | 23.64 | 129.33 | 23.69 |
October | 387.83 | 23.27 | 270.50 | 23.47 | 68.17 | 23.52 |
November | 673.67 | 22.54 | 8.17 | 22.56 | 1.83 | 22.56 |
December | 744.00 | 22.27 | 0.00 | 22.27 | 0.00 | 22.27 |
Annual Sum or Average | 6131.33 | 22.66 | 2400.67 | 22.98 | 853.17 | 23.07 |
Minimum of Months | 185.50 | 22.01 | 0.00 | 22.00 | 0.00 | 21.99 |
Maximum of Months | 744.00 | 23.93 | 621.50 | 23.83 | 239.33 | 23.86 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.84 | 476.00 | 20.76 | 476.00 | 20.72 |
February | 672.00 | 20.97 | 430.83 | 20.88 | 430.83 | 20.84 |
March | 743.83 | 21.24 | 120.00 | 21.17 | 120.00 | 21.12 |
April | 700.17 | 21.37 | 22.00 | 21.33 | 21.83 | 21.31 |
May | 699.83 | 21.53 | 3.67 | 21.53 | 1.67 | 21.54 |
June | 616.33 | 21.46 | 11.00 | 21.49 | 2.50 | 21.50 |
July | 608.33 | 21.39 | 19.00 | 21.45 | 1.67 | 21.46 |
August | 593.00 | 21.35 | 39.00 | 21.47 | 1.00 | 21.48 |
September | 635.67 | 21.48 | 14.83 | 21.52 | 2.50 | 21.53 |
October | 685.50 | 21.49 | 3.83 | 21.50 | 1.50 | 21.50 |
November | 720.00 | 21.18 | 168.67 | 21.10 | 168.67 | 21.04 |
December | 744.00 | 20.95 | 438.00 | 20.86 | 438.00 | 20.82 |
Annual Sum or Average | 8162.67 | 21.26 | 1746.83 | 21.19 | 1666.17 | 21.12 |
Minimum of Months | 593.00 | 20.84 | 3.67 | 20.76 | 1.00 | 20.72 |
Maximum of Months | 744.00 | 21.53 | 476.00 | 21.53 | 476.00 | 21.54 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.64 | 598.67 | 20.59 | 598.67 | 20.57 |
February | 672.00 | 20.69 | 574.33 | 20.65 | 574.33 | 20.64 |
March | 741.67 | 21.03 | 215.50 | 20.95 | 213.50 | 20.90 |
April | 689.17 | 21.33 | 38.00 | 21.35 | 27.17 | 21.31 |
May | 639.83 | 21.72 | 61.17 | 22.02 | 8.67 | 22.05 |
June | 528.50 | 22.18 | 167.83 | 22.83 | 87.83 | 23.03 |
July | 570.83 | 21.79 | 96.50 | 22.15 | 55.67 | 22.32 |
August | 558.50 | 21.64 | 77.00 | 21.94 | 16.67 | 21.99 |
September | 587.67 | 21.96 | 93.33 | 22.31 | 37.33 | 22.40 |
October | 681.50 | 21.65 | 42.67 | 21.77 | 20.83 | 21.80 |
November | 720.00 | 20.96 | 271.67 | 20.86 | 271.67 | 20.80 |
December | 744.00 | 20.70 | 634.83 | 20.66 | 634.83 | 20.65 |
Annual Sum or Average | 7877.67 | 21.31 | 2871.50 | 21.32 | 2547.17 | 21.24 |
Minimum of Months | 528.50 | 20.64 | 38.00 | 20.59 | 8.67 | 20.57 |
Maximum of Months | 744.00 | 22.18 | 634.83 | 22.83 | 634.83 | 23.03 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.95 | 317.33 | 20.89 | 317.33 | 20.86 |
February | 672.00 | 20.94 | 352.67 | 20.88 | 352.67 | 20.86 |
March | 744.00 | 21.18 | 57.00 | 21.16 | 57.00 | 21.14 |
April | 720.00 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
May | 735.00 | 21.85 | 6.50 | 21.87 | 2.33 | 21.87 |
June | 699.67 | 22.27 | 94.83 | 22.43 | 88.50 | 22.54 |
July | 729.00 | 22.05 | 63.17 | 22.18 | 59.67 | 22.29 |
August | 738.67 | 21.99 | 16.67 | 22.02 | 16.67 | 22.05 |
September | 709.50 | 22.09 | 35.83 | 22.16 | 35.00 | 22.21 |
October | 744.00 | 21.62 | 13.83 | 21.63 | 13.83 | 21.65 |
November | 720.00 | 21.19 | 64.33 | 21.16 | 64.33 | 21.13 |
December | 744.00 | 21.00 | 175.17 | 20.94 | 175.17 | 20.90 |
Annual Sum or Average | 8699.83 | 21.55 | 1197.33 | 21.52 | 1182.50 | 21.49 |
Minimum of Months | 672.00 | 20.94 | 0.00 | 20.88 | 0.00 | 20.86 |
Maximum of Months | 744.00 | 22.27 | 352.67 | 22.43 | 352.67 | 22.54 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.84 | 479.17 | 20.77 | 479.17 | 20.73 |
February | 672.00 | 21.00 | 407.67 | 20.91 | 407.67 | 20.87 |
March | 744.00 | 21.30 | 125.50 | 21.22 | 125.50 | 21.17 |
April | 705.00 | 21.44 | 22.50 | 21.40 | 22.50 | 21.37 |
May | 709.33 | 21.58 | 2.17 | 21.58 | 1.67 | 21.58 |
June | 606.33 | 21.44 | 4.83 | 21.45 | 2.83 | 21.46 |
July | 586.00 | 21.33 | 4.50 | 21.34 | 1.33 | 21.35 |
August | 570.50 | 21.28 | 6.17 | 21.30 | 0.50 | 21.30 |
September | 614.50 | 21.44 | 6.00 | 21.45 | 2.83 | 21.46 |
October | 684.17 | 21.51 | 1.50 | 21.52 | 1.00 | 21.52 |
November | 720.00 | 21.22 | 155.67 | 21.14 | 155.67 | 21.08 |
December | 744.00 | 20.95 | 431.67 | 20.87 | 431.67 | 20.83 |
Annual Sum or Average | 8099.83 | 21.27 | 1647.33 | 21.18 | 1632.33 | 21.12 |
Minimum of Months | 570.50 | 20.84 | 1.50 | 20.77 | 0.50 | 20.73 |
Maximum of Months | 744.00 | 21.58 | 479.17 | 21.58 | 479.17 | 21.58 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.63 | 595.83 | 20.59 | 595.83 | 20.57 |
February | 672.00 | 20.70 | 558.33 | 20.66 | 558.33 | 20.65 |
March | 744.00 | 21.07 | 195.50 | 21.01 | 195.50 | 20.96 |
April | 712.83 | 21.46 | 27.50 | 21.44 | 25.17 | 21.41 |
May | 673.17 | 21.86 | 37.17 | 22.02 | 10.67 | 22.06 |
June | 517.17 | 22.10 | 152.67 | 22.61 | 92.83 | 22.80 |
July | 542.50 | 21.78 | 100.83 | 22.21 | 59.17 | 22.42 |
August | 505.67 | 21.53 | 82.83 | 21.97 | 20.00 | 22.07 |
September | 602.00 | 22.05 | 81.33 | 22.32 | 40.33 | 22.42 |
October | 732.67 | 21.77 | 27.17 | 21.82 | 21.83 | 21.84 |
November | 720.00 | 20.99 | 232.50 | 20.89 | 232.50 | 20.82 |
December | 744.00 | 20.69 | 611.00 | 20.65 | 611.00 | 20.64 |
Annual Sum or Average | 7910.00 | 21.34 | 2702.67 | 21.33 | 2463.17 | 21.26 |
Minimum of Months | 505.67 | 20.63 | 27.17 | 20.59 | 10.67 | 20.57 |
Maximum of Months | 744.00 | 22.10 | 611.00 | 22.61 | 611.00 | 22.80 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 272.00 | 21.00 | 272.00 | 21.00 |
February | 672.00 | 21.00 | 301.33 | 21.00 | 301.33 | 21.00 |
March | 744.00 | 21.09 | 38.50 | 21.09 | 38.50 | 21.08 |
April | 720.00 | 21.49 | 2.67 | 21.48 | 2.67 | 21.48 |
May | 743.33 | 22.18 | 4.67 | 22.18 | 4.67 | 22.19 |
June | 641.50 | 23.14 | 50.50 | 23.15 | 50.50 | 23.15 |
July | 393.50 | 23.37 | 111.17 | 23.41 | 89.67 | 23.42 |
August | 245.67 | 23.48 | 119.83 | 23.58 | 52.33 | 23.58 |
September | 575.17 | 22.87 | 39.17 | 22.91 | 30.50 | 22.93 |
October | 744.00 | 22.39 | 4.17 | 22.39 | 4.17 | 22.39 |
November | 720.00 | 21.20 | 38.67 | 21.19 | 38.67 | 21.18 |
December | 744.00 | 21.01 | 123.67 | 21.00 | 123.67 | 21.00 |
Annual Sum or Average | 7687.17 | 21.84 | 1106.33 | 21.83 | 1008.67 | 21.80 |
Minimum of Months | 245.67 | 21.00 | 2.67 | 21.00 | 2.67 | 21.00 |
Maximum of Months | 744.00 | 23.48 | 301.33 | 23.58 | 301.33 | 23.58 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.73 | 596.17 | 20.67 | 596.17 | 20.65 |
February | 672.00 | 20.86 | 529.50 | 20.79 | 529.50 | 20.76 |
March | 740.50 | 21.15 | 221.67 | 21.05 | 221.67 | 20.98 |
April | 693.33 | 21.30 | 63.67 | 21.24 | 61.17 | 21.19 |
May | 682.33 | 21.46 | 28.00 | 21.49 | 19.50 | 21.50 |
June | 598.67 | 21.40 | 41.83 | 21.51 | 11.50 | 21.53 |
July | 589.83 | 21.34 | 53.17 | 21.50 | 5.33 | 21.51 |
August | 578.00 | 21.31 | 70.17 | 21.53 | 2.00 | 21.53 |
September | 622.00 | 21.43 | 45.00 | 21.51 | 19.33 | 21.52 |
October | 679.00 | 21.43 | 40.50 | 21.47 | 25.17 | 21.46 |
November | 718.50 | 21.06 | 270.67 | 20.96 | 270.67 | 20.91 |
December | 744.00 | 20.83 | 565.17 | 20.77 | 565.17 | 20.74 |
Annual Sum or Average | 8062.17 | 21.18 | 2525.50 | 21.11 | 2327.17 | 21.04 |
Minimum of Months | 578.00 | 20.73 | 28.00 | 20.67 | 2.00 | 20.65 |
Maximum of Months | 744.00 | 21.46 | 596.17 | 21.53 | 596.17 | 21.53 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.55 | 683.00 | 20.53 | 683.00 | 20.52 |
February | 672.00 | 20.61 | 629.67 | 20.59 | 629.67 | 20.58 |
March | 741.17 | 20.94 | 327.33 | 20.84 | 325.00 | 20.77 |
April | 680.50 | 21.26 | 100.50 | 21.28 | 81.50 | 21.21 |
May | 625.83 | 21.73 | 94.50 | 22.12 | 34.83 | 22.19 |
June | 515.00 | 22.26 | 205.17 | 22.99 | 108.50 | 23.24 |
July | 557.00 | 21.77 | 127.33 | 22.21 | 69.67 | 22.39 |
August | 541.50 | 21.58 | 104.33 | 21.96 | 22.00 | 22.02 |
September | 574.33 | 21.91 | 127.67 | 22.32 | 64.50 | 22.42 |
October | 672.67 | 21.55 | 118.67 | 21.67 | 90.33 | 21.66 |
November | 720.00 | 20.84 | 366.67 | 20.74 | 366.67 | 20.69 |
December | 744.00 | 20.59 | 698.00 | 20.57 | 698.00 | 20.57 |
Annual Sum or Average | 7788.00 | 21.24 | 3582.83 | 21.27 | 3173.67 | 21.19 |
Minimum of Months | 515.00 | 20.55 | 94.50 | 20.53 | 22.00 | 20.52 |
Maximum of Months | 744.00 | 22.26 | 698.00 | 22.99 | 698.00 | 23.24 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 737.33 | 21.11 | 334.00 | 21.00 | 334.00 | 20.94 |
February | 665.33 | 21.29 | 272.67 | 21.16 | 272.67 | 21.09 |
March | 714.83 | 21.32 | 87.17 | 21.27 | 87.17 | 21.23 |
April | 686.00 | 21.40 | 16.50 | 21.39 | 13.17 | 21.36 |
May | 700.33 | 21.53 | 0.67 | 21.53 | 0.67 | 21.53 |
June | 631.00 | 21.48 | 18.33 | 21.51 | 17.50 | 21.54 |
July | 624.17 | 21.44 | 10.50 | 21.46 | 8.67 | 21.48 |
August | 608.17 | 21.39 | 62.83 | 21.57 | 2.33 | 21.57 |
September | 616.50 | 21.43 | 50.67 | 21.56 | 7.50 | 21.57 |
October | 629.33 | 21.38 | 47.83 | 21.51 | 2.83 | 21.52 |
November | 698.17 | 21.40 | 53.67 | 21.37 | 52.83 | 21.34 |
December | 729.00 | 21.20 | 264.50 | 21.09 | 264.50 | 21.02 |
Annual Sum or Average | 8040.17 | 21.36 | 1219.33 | 21.33 | 1063.83 | 21.29 |
Minimum of Months | 608.17 | 21.11 | 0.67 | 21.00 | 0.67 | 20.94 |
Maximum of Months | 737.33 | 21.53 | 334.00 | 21.57 | 334.00 | 21.57 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 612.83 | 22.94 | 11.67 | 22.95 | 0.00 | 22.95 |
February | 593.17 | 23.00 | 0.00 | 23.00 | 0.00 | 23.00 |
March | 423.00 | 23.05 | 47.00 | 23.14 | 0.00 | 23.14 |
April | 218.17 | 23.06 | 228.50 | 23.52 | 0.00 | 23.52 |
May | 82.33 | 23.60 | 523.83 | 23.87 | 48.00 | 23.88 |
June | 187.17 | 23.99 | 702.67 | 23.94 | 187.00 | 23.95 |
July | 229.00 | 24.00 | 744.00 | 23.97 | 229.00 | 23.97 |
August | 177.33 | 24.00 | 738.17 | 23.95 | 177.33 | 23.96 |
September | 135.00 | 23.98 | 626.00 | 23.93 | 133.00 | 23.94 |
October | 236.17 | 23.48 | 391.67 | 23.71 | 84.67 | 23.74 |
November | 391.83 | 22.99 | 84.83 | 23.16 | 3.67 | 23.17 |
December | 568.00 | 23.03 | 5.67 | 23.04 | 0.00 | 23.04 |
Annual Sum or Average | 3854.00 | 23.23 | 4104.00 | 23.59 | 862.67 | 23.63 |
Minimum of Months | 82.33 | 22.94 | 0.00 | 22.95 | 0.00 | 22.95 |
Maximum of Months | 612.83 | 24.00 | 744.00 | 23.97 | 229.00 | 23.97 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 466.00 | 23.02 | 39.67 | 23.10 | 0.00 | 23.10 |
February | 469.50 | 23.10 | 11.00 | 23.12 | 0.00 | 23.12 |
March | 248.17 | 23.08 | 169.50 | 23.44 | 0.00 | 23.44 |
April | 99.33 | 23.14 | 371.00 | 23.78 | 0.00 | 23.78 |
May | 42.33 | 23.93 | 646.17 | 23.93 | 38.83 | 23.94 |
June | 166.67 | 24.00 | 712.67 | 23.97 | 166.67 | 23.97 |
July | 212.50 | 24.00 | 744.00 | 23.98 | 212.50 | 23.98 |
August | 161.17 | 24.00 | 743.33 | 23.97 | 161.17 | 23.97 |
September | 118.67 | 24.00 | 690.83 | 23.94 | 118.67 | 23.95 |
October | 142.67 | 23.61 | 458.67 | 23.82 | 69.83 | 23.84 |
November | 241.00 | 23.07 | 179.83 | 23.45 | 2.67 | 23.46 |
December | 383.50 | 23.01 | 38.33 | 23.10 | 0.00 | 23.10 |
Annual Sum or Average | 2751.50 | 23.33 | 4805.00 | 23.72 | 770.33 | 23.75 |
Minimum of Months | 42.33 | 23.01 | 11.00 | 23.10 | 0.00 | 23.10 |
Maximum of Months | 469.50 | 24.00 | 744.00 | 23.98 | 212.50 | 23.98 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 550.67 | 23.60 | 585.33 | 23.77 | 444.83 | 23.83 |
February | 509.17 | 23.55 | 522.67 | 23.75 | 399.33 | 23.82 |
March | 543.17 | 23.83 | 626.17 | 23.86 | 497.33 | 23.90 |
April | 513.00 | 23.95 | 654.83 | 23.89 | 502.67 | 23.92 |
May | 547.83 | 23.99 | 735.50 | 23.89 | 547.83 | 23.92 |
June | 555.33 | 24.01 | 720.00 | 23.93 | 555.33 | 23.96 |
July | 589.83 | 23.99 | 744.00 | 23.94 | 589.83 | 23.96 |
August | 586.17 | 24.01 | 744.00 | 23.96 | 586.17 | 23.97 |
September | 542.00 | 23.99 | 718.83 | 23.91 | 542.00 | 23.94 |
October | 534.67 | 23.98 | 700.50 | 23.90 | 530.17 | 23.92 |
November | 522.17 | 23.84 | 614.83 | 23.86 | 482.00 | 23.90 |
December | 558.00 | 23.68 | 594.33 | 23.81 | 467.83 | 23.86 |
Annual Sum or Average | 6552.00 | 23.87 | 7961.00 | 23.88 | 6145.33 | 23.91 |
Minimum of Months | 509.17 | 23.55 | 522.67 | 23.75 | 399.33 | 23.82 |
Maximum of Months | 589.83 | 24.01 | 744.00 | 23.96 | 589.83 | 23.97 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 318.33 | 21.00 | 318.33 | 21.00 |
February | 672.00 | 21.02 | 313.83 | 21.01 | 313.83 | 21.01 |
March | 744.00 | 21.12 | 46.83 | 21.11 | 46.83 | 21.11 |
April | 720.00 | 21.50 | 0.00 | 21.50 | 0.00 | 21.50 |
May | 710.50 | 22.14 | 7.67 | 22.16 | 0.00 | 22.16 |
June | 406.00 | 22.94 | 108.67 | 23.13 | 0.00 | 23.13 |
July | 62.50 | 23.07 | 391.17 | 23.74 | 0.00 | 23.74 |
August | 124.67 | 23.14 | 364.83 | 23.70 | 0.00 | 23.70 |
September | 522.33 | 22.63 | 65.50 | 22.77 | 0.00 | 22.77 |
October | 728.00 | 22.06 | 0.00 | 22.06 | 0.00 | 22.06 |
November | 720.00 | 21.12 | 48.00 | 21.12 | 48.00 | 21.11 |
December | 744.00 | 21.01 | 135.17 | 21.01 | 135.17 | 21.01 |
Annual Sum or Average | 6898.00 | 21.61 | 1800.00 | 21.79 | 862.17 | 21.72 |
Minimum of Months | 62.50 | 21.01 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 23.14 | 391.17 | 23.74 | 318.33 | 23.74 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.85495 | 28.81650 | -0.0269 | 5.20200 |
February | 672.00000 | 22.40427 | 25.23653 | -0.1641 | 5.73466 |
March | 744.00000 | 22.01377 | 34.79812 | -0.2023 | 6.03534 |
April | 720.00000 | 21.78738 | 41.43073 | -0.2198 | 6.21319 |
May | 744.00000 | 21.62978 | 50.32649 | -1.3524 | 43.11460 |
June | 720.00000 | 22.08623 | 60.46737 | -1.1228 | 31.81555 |
July | 744.00000 | 22.53195 | 62.93495 | -0.9420 | 23.94982 |
August | 744.00000 | 23.02723 | 58.48943 | -0.7885 | 18.34379 |
September | 720.00000 | 23.55049 | 52.59713 | -0.6367 | 13.79873 |
October | 744.00000 | 23.78753 | 43.33274 | 0.31694 | 7.34379 |
November | 720.00000 | 23.76398 | 33.52142 | 0.24096 | 6.34286 |
December | 744.00000 | 23.48369 | 28.05814 | 0.12857 | 5.47636 |
Annual Sum or Average | 8760.00000 | 22.74564 | 43.44266 | -0.3989 | 14.51813 |
Minimum of Months | 672.00000 | 21.62978 | 25.23653 | -1.3524 | 5.20200 |
Maximum of Months | 744.00000 | 23.78753 | 62.93495 | 0.31694 | 43.11460 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.15030 | 29.40200 | -0.5042 | 11.09317 |
February | 672.00000 | 21.24211 | 24.80066 | -0.4781 | 10.82634 |
March | 744.00000 | 21.35246 | 34.23417 | -0.3408 | 8.61799 |
April | 720.00000 | 21.47582 | 40.33622 | -0.2409 | 7.68073 |
May | 744.00000 | 21.67025 | 48.60673 | -1.1929 | 36.41103 |
June | 720.00000 | 22.44863 | 57.72500 | -0.8086 | 20.28400 |
July | 744.00000 | 22.93516 | 60.10300 | -0.5952 | 13.60205 |
August | 744.00000 | 23.21306 | 56.23959 | -0.4981 | 11.79746 |
September | 720.00000 | 22.52751 | 53.82995 | -0.7963 | 21.72579 |
October | 744.00000 | 22.32234 | 44.89432 | 0.07754 | 7.69185 |
November | 720.00000 | 21.33145 | 36.12306 | -0.3364 | 8.57405 |
December | 744.00000 | 21.22504 | 29.37677 | -0.4536 | 10.27872 |
Annual Sum or Average | 8760.00000 | 21.91290 | 43.07781 | -0.5139 | 14.06941 |
Minimum of Months | 672.00000 | 21.15030 | 24.80066 | -1.1929 | 7.68073 |
Maximum of Months | 744.00000 | 23.21306 | 60.10300 | 0.07754 | 36.41103 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.44716 | 31.14744 | -0.3523 | 7.96500 |
February | 672.00000 | 21.54443 | 26.61131 | -0.3514 | 7.92654 |
March | 744.00000 | 21.96286 | 35.35168 | -0.1833 | 6.13551 |
April | 720.00000 | 22.31472 | 40.79665 | -0.0546 | 5.80375 |
May | 744.00000 | 22.75679 | 48.01981 | -0.9059 | 23.14700 |
June | 720.00000 | 23.34748 | 57.09927 | -0.6179 | 13.59068 |
July | 744.00000 | 23.55750 | 60.10867 | -0.5116 | 10.81514 |
August | 744.00000 | 23.66309 | 56.87892 | -0.4883 | 10.29410 |
September | 720.00000 | 23.31854 | 53.70754 | -0.6510 | 14.73907 |
October | 744.00000 | 23.08307 | 45.45067 | 0.18495 | 6.37253 |
November | 720.00000 | 22.03941 | 36.99273 | -0.1532 | 6.08811 |
December | 744.00000 | 21.66799 | 30.94347 | -0.2916 | 7.07265 |
Annual Sum or Average | 8760.00000 | 22.56477 | 43.69294 | -0.3647 | 10.01220 |
Minimum of Months | 672.00000 | 21.44716 | 26.61131 | -0.9059 | 5.80375 |
Maximum of Months | 744.00000 | 23.66309 | 60.10867 | 0.18495 | 23.14700 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.63846 | 24.89018 | 0.48207 | 12.94290 |
February | 672.00000 | 22.65051 | 20.76651 | 0.46080 | 12.50343 |
March | 744.00000 | 22.72019 | 29.40645 | 0.56756 | 14.79210 |
April | 720.00000 | 22.75089 | 35.28021 | 0.63767 | 16.55662 |
May | 744.00000 | 22.78985 | 43.22593 | -0.0111 | 11.00247 |
June | 720.00000 | 22.81253 | 54.04256 | 0.10876 | 11.11871 |
July | 744.00000 | 22.81072 | 57.85623 | 0.15230 | 11.07440 |
August | 744.00000 | 22.81491 | 54.95028 | 0.14498 | 11.20034 |
September | 720.00000 | 22.82263 | 50.47099 | 0.07619 | 10.97163 |
October | 744.00000 | 22.81376 | 41.48868 | 0.72060 | 18.93071 |
November | 720.00000 | 22.75386 | 31.10084 | 0.58919 | 15.26148 |
December | 744.00000 | 22.68848 | 24.89870 | 0.50744 | 13.29465 |
Annual Sum or Average | 8760.00000 | 22.75611 | 39.14112 | 0.36914 | 13.30880 |
Minimum of Months | 672.00000 | 22.63846 | 20.76651 | -0.0111 | 10.97163 |
Maximum of Months | 744.00000 | 22.82263 | 57.85623 | 0.72060 | 18.93071 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.63352 | 34.04535 | -0.2821 | 7.67808 |
February | 672.00000 | 21.84490 | 29.43627 | -0.2312 | 7.31183 |
March | 744.00000 | 22.18583 | 38.25994 | -0.0563 | 6.28489 |
April | 720.00000 | 22.37518 | 43.88492 | 0.04875 | 6.50690 |
May | 744.00000 | 22.69880 | 51.46665 | -0.7760 | 19.06254 |
June | 720.00000 | 23.18990 | 60.79531 | -0.4870 | 10.83020 |
July | 744.00000 | 23.44819 | 63.54493 | -0.3414 | 7.99879 |
August | 744.00000 | 23.65350 | 59.95373 | -0.2631 | 7.11440 |
September | 720.00000 | 23.33661 | 56.79998 | -0.4438 | 11.00618 |
October | 744.00000 | 23.31401 | 48.04794 | 0.38408 | 9.54794 |
November | 720.00000 | 22.17410 | 39.90020 | -0.0479 | 6.40762 |
December | 744.00000 | 21.85730 | 33.77551 | -0.2025 | 7.01184 |
Annual Sum or Average | 8760.00000 | 22.64783 | 46.76039 | -0.2247 | 8.91209 |
Minimum of Months | 672.00000 | 21.63352 | 29.43627 | -0.7760 | 6.28489 |
Maximum of Months | 744.00000 | 23.65350 | 63.54493 | 0.38408 | 19.06254 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.01348 | 33.18440 | -0.1863 | 6.31632 |
February | 672.00000 | 22.13988 | 28.75020 | -0.1765 | 6.18003 |
March | 744.00000 | 22.50792 | 37.33144 | -0.0172 | 5.55368 |
April | 720.00000 | 22.76347 | 42.75058 | 0.09263 | 5.95404 |
May | 744.00000 | 23.11135 | 49.98674 | -0.7282 | 17.06536 |
June | 720.00000 | 23.47926 | 59.26671 | -0.5044 | 10.91990 |
July | 744.00000 | 23.60531 | 62.32405 | -0.4204 | 9.04590 |
August | 744.00000 | 23.69584 | 59.13992 | -0.4002 | 8.59795 |
September | 720.00000 | 23.54440 | 55.65888 | -0.5037 | 10.94390 |
October | 744.00000 | 23.45909 | 47.35080 | 0.32700 | 7.81446 |
November | 720.00000 | 22.62412 | 38.80790 | 0.02463 | 5.73613 |
December | 744.00000 | 22.26813 | 32.90802 | -0.1155 | 5.81499 |
Annual Sum or Average | 8760.00000 | 22.93904 | 45.72196 | -0.2176 | 8.34556 |
Minimum of Months | 672.00000 | 22.01348 | 28.75020 | -0.7282 | 5.55368 |
Maximum of Months | 744.00000 | 23.69584 | 62.32405 | 0.32700 | 17.06536 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.84119 | 45.31844 | -0.5717 | 12.45666 |
February | 672.00000 | 20.97327 | 40.59249 | -0.5497 | 12.08353 |
March | 744.00000 | 21.24516 | 48.08850 | -0.3724 | 8.72104 |
April | 720.00000 | 21.41968 | 51.64978 | -0.2569 | 7.41731 |
May | 744.00000 | 21.63333 | 54.71278 | -1.2352 | 38.29339 |
June | 720.00000 | 21.72796 | 55.42137 | -1.0947 | 31.86489 |
July | 744.00000 | 21.74455 | 54.21492 | -1.0612 | 30.43619 |
August | 744.00000 | 21.74665 | 52.77817 | -1.0483 | 30.02390 |
September | 720.00000 | 21.69765 | 55.41936 | -1.1450 | 34.23407 |
October | 744.00000 | 21.63260 | 52.42777 | -0.1328 | 6.52138 |
November | 720.00000 | 21.17681 | 50.25756 | -0.3981 | 9.02312 |
December | 744.00000 | 20.94955 | 44.92749 | -0.5289 | 11.43027 |
Annual Sum or Average | 8760.00000 | 21.40137 | 50.53573 | -0.7005 | 19.42161 |
Minimum of Months | 672.00000 | 20.84119 | 40.59249 | -1.2352 | 6.52138 |
Maximum of Months | 744.00000 | 21.74665 | 55.42137 | -0.1328 | 38.29339 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.64097 | 45.81422 | -0.6396 | 14.08199 |
February | 672.00000 | 20.69350 | 41.21777 | -0.6461 | 14.28711 |
March | 744.00000 | 21.04502 | 48.60227 | -0.4455 | 9.75464 |
April | 720.00000 | 21.45407 | 51.80593 | -0.2700 | 7.78886 |
May | 744.00000 | 22.11388 | 54.02327 | -1.1117 | 34.33289 |
June | 720.00000 | 22.69696 | 54.87784 | -0.8162 | 23.64002 |
July | 744.00000 | 22.20498 | 54.88475 | -0.9300 | 25.97962 |
August | 744.00000 | 22.14211 | 53.36251 | -0.9554 | 26.60397 |
September | 720.00000 | 22.34960 | 55.85073 | -0.9862 | 28.57101 |
October | 744.00000 | 21.83227 | 53.81926 | -0.1258 | 6.96389 |
November | 720.00000 | 20.95688 | 50.94487 | -0.4746 | 10.27194 |
December | 744.00000 | 20.69512 | 45.58151 | -0.6123 | 13.20551 |
Annual Sum or Average | 8760.00000 | 21.57273 | 50.95123 | -0.6683 | 17.99121 |
Minimum of Months | 672.00000 | 20.64097 | 41.21777 | -1.1117 | 6.96389 |
Maximum of Months | 744.00000 | 22.69696 | 55.85073 | -0.1258 | 34.33289 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.94732 | 41.20523 | -0.5205 | 10.92646 |
February | 672.00000 | 20.93764 | 36.82140 | -0.5504 | 11.55916 |
March | 744.00000 | 21.18382 | 44.51890 | -0.4084 | 8.65598 |
April | 720.00000 | 21.44341 | 48.12457 | -0.2907 | 7.16218 |
May | 744.00000 | 21.88115 | 51.05234 | -1.2495 | 38.63852 |
June | 720.00000 | 22.31654 | 56.88914 | -1.0219 | 28.87661 |
July | 744.00000 | 22.09082 | 56.94378 | -1.0778 | 31.18905 |
August | 744.00000 | 22.00163 | 55.17409 | -1.1286 | 33.10737 |
September | 720.00000 | 22.11530 | 55.03551 | -1.1336 | 33.37451 |
October | 744.00000 | 21.61894 | 51.59232 | -0.2127 | 6.60801 |
November | 720.00000 | 21.18853 | 46.48678 | -0.3943 | 8.47279 |
December | 744.00000 | 21.00263 | 40.98935 | -0.5006 | 10.33173 |
Annual Sum or Average | 8760.00000 | 21.56352 | 48.80229 | -0.7087 | 19.13263 |
Minimum of Months | 672.00000 | 20.93764 | 36.82140 | -1.2495 | 6.60801 |
Maximum of Months | 744.00000 | 22.31654 | 56.94378 | -0.2127 | 38.63852 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.83957 | 45.31943 | -0.5698 | 12.33722 |
February | 672.00000 | 21.00043 | 40.54625 | -0.5398 | 11.77865 |
March | 744.00000 | 21.29734 | 48.02194 | -0.3650 | 8.65161 |
April | 720.00000 | 21.47539 | 51.33206 | -0.2433 | 7.37400 |
May | 744.00000 | 21.65995 | 54.50777 | -1.2217 | 37.72247 |
June | 720.00000 | 21.73758 | 55.71823 | -1.1000 | 32.08000 |
July | 744.00000 | 21.75021 | 54.25090 | -1.0609 | 30.43516 |
August | 744.00000 | 21.75440 | 52.78947 | -1.0460 | 29.92784 |
September | 720.00000 | 21.71316 | 55.30904 | -1.1375 | 33.91739 |
October | 744.00000 | 21.66095 | 52.52017 | -0.1282 | 6.50761 |
November | 720.00000 | 21.21649 | 50.01442 | -0.3815 | 8.80340 |
December | 744.00000 | 20.95395 | 44.94330 | -0.5235 | 11.27632 |
Annual Sum or Average | 8760.00000 | 21.42383 | 50.49164 | -0.6941 | 19.28124 |
Minimum of Months | 672.00000 | 20.83957 | 40.54625 | -1.2217 | 6.50761 |
Maximum of Months | 744.00000 | 21.75440 | 55.71823 | -0.1282 | 37.72247 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.63451 | 45.81432 | -0.6390 | 14.06733 |
February | 672.00000 | 20.69754 | 41.19814 | -0.6409 | 14.09492 |
March | 744.00000 | 21.07405 | 48.53123 | -0.4432 | 9.54644 |
April | 720.00000 | 21.48974 | 51.44904 | -0.2612 | 7.52875 |
May | 744.00000 | 22.08216 | 53.90832 | -1.1150 | 33.96144 |
June | 720.00000 | 22.58123 | 55.75326 | -0.8554 | 23.92973 |
July | 744.00000 | 22.25706 | 54.93583 | -0.9154 | 26.01520 |
August | 744.00000 | 22.22842 | 53.38103 | -0.9293 | 26.41048 |
September | 720.00000 | 22.34417 | 55.86155 | -0.9836 | 28.34331 |
October | 744.00000 | 21.80212 | 53.78236 | -0.1364 | 6.67777 |
November | 720.00000 | 20.99226 | 50.73172 | -0.4579 | 9.95516 |
December | 744.00000 | 20.68841 | 45.56714 | -0.6094 | 13.15002 |
Annual Sum or Average | 8760.00000 | 21.57677 | 50.96149 | -0.6660 | 17.84125 |
Minimum of Months | 672.00000 | 20.63451 | 41.19814 | -1.1150 | 6.67777 |
Maximum of Months | 744.00000 | 22.58123 | 55.86155 | -0.1364 | 33.96144 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.72997 | 46.66207 | -0.6320 | 14.05341 |
February | 672.00000 | 20.86114 | 41.63791 | -0.6116 | 13.70017 |
March | 744.00000 | 21.16130 | 49.49957 | -0.4107 | 9.54326 |
April | 720.00000 | 21.37096 | 53.01943 | -0.2770 | 7.89321 |
May | 744.00000 | 21.61883 | 55.94790 | -1.2387 | 38.70160 |
June | 720.00000 | 21.72333 | 56.49713 | -1.0867 | 31.72760 |
July | 744.00000 | 21.74500 | 55.07927 | -1.0470 | 30.04767 |
August | 744.00000 | 21.74600 | 53.61511 | -1.0370 | 29.81563 |
September | 720.00000 | 21.68420 | 56.80050 | -1.1496 | 34.66698 |
October | 744.00000 | 21.59496 | 53.96286 | -0.1518 | 6.83470 |
November | 720.00000 | 21.06912 | 51.88156 | -0.4460 | 10.02454 |
December | 744.00000 | 20.83331 | 46.22254 | -0.5879 | 12.87913 |
Annual Sum or Average | 8760.00000 | 21.34754 | 51.78764 | -0.7237 | 20.03045 |
Minimum of Months | 672.00000 | 20.72997 | 41.63791 | -1.2387 | 6.83470 |
Maximum of Months | 744.00000 | 21.74600 | 56.80050 | -0.1518 | 38.70160 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.55292 | 47.14763 | -0.6966 | 15.77449 |
February | 672.00000 | 20.60670 | 42.25336 | -0.7049 | 16.02712 |
March | 744.00000 | 20.95225 | 50.07872 | -0.4879 | 10.76841 |
April | 720.00000 | 21.42214 | 53.17019 | -0.2868 | 8.36199 |
May | 744.00000 | 22.16121 | 55.04283 | -1.0927 | 34.57172 |
June | 720.00000 | 22.76323 | 55.26511 | -0.7802 | 23.59192 |
July | 744.00000 | 22.20727 | 55.52418 | -0.9120 | 25.61514 |
August | 744.00000 | 22.12729 | 53.96811 | -0.9468 | 26.51251 |
September | 720.00000 | 22.35309 | 56.91593 | -0.9823 | 29.07124 |
October | 744.00000 | 21.78115 | 55.33888 | -0.1489 | 7.47202 |
November | 720.00000 | 20.83971 | 52.66528 | -0.5269 | 11.50436 |
December | 744.00000 | 20.58741 | 46.91875 | -0.6715 | 14.88547 |
Annual Sum or Average | 8760.00000 | 21.53366 | 52.07721 | -0.6868 | 18.70750 |
Minimum of Months | 672.00000 | 20.55292 | 42.25336 | -1.0927 | 7.47202 |
Maximum of Months | 744.00000 | 22.76323 | 56.91593 | -0.1489 | 34.57172 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.13395 | 45.18918 | -0.4673 | 10.70411 |
February | 672.00000 | 21.31013 | 40.73770 | -0.4218 | 10.11991 |
March | 744.00000 | 21.40000 | 48.01726 | -0.3155 | 8.26012 |
April | 720.00000 | 21.48849 | 51.19607 | -0.2446 | 7.41628 |
May | 744.00000 | 21.63245 | 54.64466 | -1.2712 | 40.08709 |
June | 720.00000 | 21.71109 | 57.34760 | -1.1498 | 34.34057 |
July | 744.00000 | 21.74177 | 55.62014 | -1.1045 | 32.35297 |
August | 744.00000 | 21.74276 | 54.16673 | -1.0833 | 31.73209 |
September | 720.00000 | 21.70505 | 55.71715 | -1.1477 | 34.67470 |
October | 744.00000 | 21.68006 | 52.15535 | -0.0990 | 6.65910 |
November | 720.00000 | 21.45681 | 49.45594 | -0.2934 | 7.90640 |
December | 744.00000 | 21.24749 | 44.75195 | -0.4140 | 9.83682 |
Annual Sum or Average | 8760.00000 | 21.52181 | 50.80291 | -0.6692 | 19.56739 |
Minimum of Months | 672.00000 | 21.13395 | 40.73770 | -1.2712 | 6.65910 |
Maximum of Months | 744.00000 | 21.74276 | 57.34760 | -0.0990 | 40.08709 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.11832 | 33.86716 | 0.08928 | 6.12317 |
February | 672.00000 | 23.11261 | 29.90014 | 0.05996 | 5.96552 |
March | 744.00000 | 23.43263 | 37.62740 | 0.22844 | 6.69150 |
April | 720.00000 | 23.62488 | 42.46160 | 0.34223 | 7.93703 |
May | 744.00000 | 23.81342 | 49.11610 | -0.3997 | 8.71775 |
June | 720.00000 | 23.92144 | 58.35643 | -0.2381 | 6.34249 |
July | 744.00000 | 23.95913 | 61.58211 | -0.1746 | 5.67297 |
August | 744.00000 | 23.93890 | 59.00327 | -0.2047 | 5.97208 |
September | 720.00000 | 23.86109 | 55.58696 | -0.3110 | 7.34675 |
October | 744.00000 | 23.70225 | 48.04523 | 0.41938 | 9.24552 |
November | 720.00000 | 23.41627 | 39.19793 | 0.23476 | 6.83063 |
December | 744.00000 | 23.25236 | 33.68036 | 0.13114 | 6.07404 |
Annual Sum or Average | 8760.00000 | 23.59888 | 45.79688 | 0.01447 | 6.91548 |
Minimum of Months | 672.00000 | 23.11261 | 29.90014 | -0.3997 | 5.67297 |
Maximum of Months | 744.00000 | 23.95913 | 61.58211 | 0.41938 | 9.24552 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.36857 | 32.85774 | 0.18905 | 6.49930 |
February | 672.00000 | 23.36277 | 28.96583 | 0.15922 | 6.23038 |
March | 744.00000 | 23.62468 | 36.53557 | 0.31352 | 7.48283 |
April | 720.00000 | 23.77734 | 41.43556 | 0.41614 | 8.97174 |
May | 744.00000 | 23.89977 | 48.23549 | -0.3202 | 7.39504 |
June | 720.00000 | 23.95722 | 57.73037 | -0.1846 | 5.83533 |
July | 744.00000 | 23.97884 | 61.05794 | -0.1300 | 5.37701 |
August | 744.00000 | 23.96413 | 58.47237 | -0.1589 | 5.60240 |
September | 720.00000 | 23.91914 | 54.86300 | -0.2482 | 6.52082 |
October | 744.00000 | 23.81640 | 47.14244 | 0.47973 | 10.27591 |
November | 720.00000 | 23.60971 | 38.11990 | 0.32010 | 7.63754 |
December | 744.00000 | 23.47181 | 32.62596 | 0.22330 | 6.55938 |
Annual Sum or Average | 8760.00000 | 23.73126 | 44.93222 | 0.08781 | 7.03661 |
Minimum of Months | 672.00000 | 23.36277 | 28.96583 | -0.3202 | 5.37701 |
Maximum of Months | 744.00000 | 23.97884 | 61.05794 | 0.47973 | 10.27591 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.55961 | 31.65231 | 0.84487 | 23.45624 |
February | 672.00000 | 23.54850 | 27.83637 | 0.82209 | 22.72800 |
March | 744.00000 | 23.64450 | 35.44504 | 0.95220 | 27.08990 |
April | 720.00000 | 23.71232 | 40.57112 | 1.04867 | 30.87506 |
May | 744.00000 | 23.79167 | 47.67019 | 0.59232 | 17.75428 |
June | 720.00000 | 23.87752 | 57.27862 | 0.74750 | 21.18368 |
July | 744.00000 | 23.90159 | 60.60109 | 0.81458 | 22.89528 |
August | 744.00000 | 23.91360 | 57.94384 | 0.80625 | 22.82000 |
September | 720.00000 | 23.84334 | 54.22079 | 0.68329 | 19.48326 |
October | 744.00000 | 23.75886 | 46.23150 | 1.12507 | 34.09390 |
November | 720.00000 | 23.64920 | 37.02304 | 0.95839 | 27.26884 |
December | 744.00000 | 23.59574 | 31.49259 | 0.87036 | 23.96347 |
Annual Sum or Average | 8760.00000 | 23.73414 | 44.09413 | 0.85570 | 24.47938 |
Minimum of Months | 672.00000 | 23.54850 | 27.83637 | 0.59232 | 17.75428 |
Maximum of Months | 744.00000 | 23.91360 | 60.60109 | 1.12507 | 34.09390 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00065 | 28.68730 | -0.5265 | 10.92292 |
February | 672.00000 | 21.00015 | 24.11354 | -0.5531 | 11.47865 |
March | 744.00000 | 21.04660 | 33.80239 | -0.4548 | 9.43795 |
April | 720.00000 | 21.37417 | 39.59900 | -0.3265 | 7.66256 |
May | 744.00000 | 22.07577 | 46.49022 | -1.1981 | 35.59285 |
June | 720.00000 | 23.03717 | 55.06694 | -0.8008 | 18.88358 |
July | 744.00000 | 23.45302 | 57.79608 | -0.6326 | 13.51352 |
August | 744.00000 | 23.49822 | 54.67014 | -0.6369 | 13.69834 |
September | 720.00000 | 22.88577 | 51.90765 | -0.8748 | 21.77952 |
October | 744.00000 | 22.18766 | 44.38185 | -0.0835 | 5.74437 |
November | 720.00000 | 21.21704 | 35.47292 | -0.3972 | 8.56165 |
December | 744.00000 | 21.00168 | 28.82290 | -0.5081 | 10.43967 |
Annual Sum or Average | 8760.00000 | 21.98795 | 41.83768 | -0.5828 | 13.99414 |
Minimum of Months | 672.00000 | 21.00015 | 24.11354 | -1.1981 | 5.74437 |
Maximum of Months | 744.00000 | 23.49822 | 57.79608 | -0.0835 | 35.59285 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00163 | 32.62512 | -0.5076 | 10.48073 |
February | 672.00000 | 21.00298 | 28.04585 | -0.5265 | 10.85277 |
March | 744.00000 | 21.08952 | 37.67236 | -0.4307 | 8.97662 |
April | 720.00000 | 21.48616 | 43.33530 | -0.2930 | 7.20345 |
May | 744.00000 | 22.18371 | 50.23946 | -1.1667 | 34.16598 |
June | 720.00000 | 23.18714 | 58.59202 | -0.7546 | 17.20398 |
July | 744.00000 | 23.48763 | 61.50181 | -0.6261 | 13.28710 |
August | 744.00000 | 23.63024 | 58.27253 | -0.5967 | 12.55351 |
September | 720.00000 | 23.02441 | 55.55025 | -0.8317 | 20.45400 |
October | 744.00000 | 22.38869 | 47.95176 | -0.0306 | 5.50539 |
November | 720.00000 | 21.19975 | 39.43925 | -0.3961 | 8.50543 |
December | 744.00000 | 21.00536 | 32.72026 | -0.4974 | 10.20996 |
Annual Sum or Average | 8760.00000 | 22.06410 | 45.59800 | -0.5549 | 13.30258 |
Minimum of Months | 672.00000 | 21.00163 | 28.04585 | -1.1667 | 5.50539 |
Maximum of Months | 744.00000 | 23.63024 | 61.50181 | -0.0306 | 34.16598 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00530 | 29.70312 | -0.5143 | 10.66069 |
February | 672.00000 | 21.01678 | 25.14908 | -0.5327 | 11.02495 |
March | 744.00000 | 21.11861 | 34.67955 | -0.4159 | 8.78404 |
April | 720.00000 | 21.49521 | 40.31277 | -0.2711 | 7.16040 |
May | 744.00000 | 22.21007 | 47.17139 | -1.1069 | 31.70285 |
June | 720.00000 | 23.22421 | 55.30060 | -0.6823 | 15.32046 |
July | 744.00000 | 23.62812 | 57.78616 | -0.5126 | 10.71022 |
August | 744.00000 | 23.65367 | 54.89167 | -0.5208 | 10.99275 |
September | 720.00000 | 22.90659 | 52.72213 | -0.8154 | 20.19682 |
October | 744.00000 | 22.09064 | 45.49001 | -0.0751 | 6.04954 |
November | 720.00000 | 21.12320 | 36.61572 | -0.4052 | 8.64628 |
December | 744.00000 | 21.01213 | 29.79247 | -0.4973 | 10.21668 |
Annual Sum or Average | 8760.00000 | 22.04718 | 42.56892 | -0.5289 | 12.63298 |
Minimum of Months | 672.00000 | 21.00530 | 25.14908 | -1.1069 | 6.04954 |
Maximum of Months | 744.00000 | 23.65367 | 57.78616 | -0.0751 | 31.70285 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.01610 | 28.17293 | -0.5135 | 10.64705 |
February | 672.00000 | 21.01379 | 23.61696 | -0.5413 | 11.21264 |
March | 744.00000 | 21.11999 | 33.17014 | -0.4339 | 9.08433 |
April | 720.00000 | 21.50218 | 38.82402 | -0.2958 | 7.30930 |
May | 744.00000 | 22.24037 | 45.54043 | -1.1435 | 33.04470 |
June | 720.00000 | 23.18645 | 54.05343 | -0.7494 | 17.24241 |
July | 744.00000 | 23.56776 | 56.83743 | -0.5913 | 12.48024 |
August | 744.00000 | 23.60932 | 53.74172 | -0.5963 | 12.65300 |
September | 720.00000 | 23.04750 | 50.89358 | -0.8198 | 19.83612 |
October | 744.00000 | 22.35861 | 43.46625 | -0.0445 | 5.62354 |
November | 720.00000 | 21.33317 | 34.73099 | -0.3674 | 8.15404 |
December | 744.00000 | 21.02935 | 28.29872 | -0.4939 | 10.14785 |
Annual Sum or Average | 8760.00000 | 22.09220 | 41.04765 | -0.5492 | 13.13510 |
Minimum of Months | 672.00000 | 21.01379 | 23.61696 | -1.1435 | 5.62354 |
Maximum of Months | 744.00000 | 23.60932 | 56.83743 | -0.0445 | 33.04470 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.119572E+10 | 14286.51 | 17-JAN-16:03 | 134.58 | 0.381009E+10 | 0.00 | 0.500581E+10 | 0.58 | 3.19 | 01-JAN-19:04 | 0.00 | 0.00 |
February | 0.236615E+10 | 19103.92 | 20-FEB-16:02 | 187.02 | 0.753959E+10 | 0.00 | 0.990575E+10 | 0.89 | 3.19 | 02-FEB-12:10 | 0.00 | 0.00 |
March | 0.832625E+10 | 72998.65 | 27-MAR-15:03 | 385.53 | 0.259449E+11 | 0.00 | 0.342712E+11 | 1.64 | 3.28 | 27-MAR-15:03 | 0.00 | 0.00 |
April | 0.286933E+11 | 106735.30 | 07-APR-15:05 | 561.85 | 0.860042E+11 | 0.00 | 0.114697E+12 | 2.43 | 3.45 | 08-APR-15:05 | 0.00 | 0.00 |
May | 0.764897E+11 | 117333.77 | 31-MAY-15:05 | 738.96 | 0.227628E+12 | 0.00 | 0.304117E+12 | 3.02 | 3.85 | 31-MAY-18:03 | 0.00 | 0.00 |
June | 0.209333E+12 | 186801.02 | 19-JUN-18:03 | 720.00 | 0.704818E+12 | 0.00 | 0.914151E+12 | 3.28 | 4.23 | 21-JUN-21:53 | 0.00 | 0.00 |
July | 0.305102E+12 | 182016.72 | 20-JUL-18:03 | 744.00 | 0.107245E+13 | 0.00 | 0.137755E+13 | 3.50 | 4.24 | 14-JUL-21:52 | 0.00 | 0.00 |
August | 0.273323E+12 | 197557.47 | 16-AUG-15:03 | 744.00 | 0.909214E+12 | 0.00 | 0.118254E+13 | 3.27 | 4.10 | 10-AUG-21:52 | 0.00 | 0.00 |
September | 0.159053E+12 | 158617.61 | 07-SEP-20:00 | 720.00 | 0.518037E+12 | 0.00 | 0.677091E+12 | 3.15 | 4.17 | 21-SEP-21:53 | 0.00 | 0.00 |
October | 0.744686E+11 | 118548.26 | 03-OCT-15:03 | 717.67 | 0.233342E+12 | 0.00 | 0.307811E+12 | 3.02 | 3.98 | 24-OCT-15:03 | 0.00 | 0.00 |
November | 0.940008E+10 | 59772.01 | 04-NOV-15:03 | 405.82 | 0.294693E+11 | 0.00 | 0.388694E+11 | 1.79 | 3.19 | 01-NOV-06:00 | 0.00 | 0.00 |
December | 0.286938E+10 | 14615.99 | 18-DEC-11:00 | 198.42 | 0.914310E+10 | 0.00 | 0.120125E+11 | 0.85 | 3.19 | 02-DEC-18:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115062E+13 | 6257.84 | 0.382740E+13 | 0.00 | 0.497802E+13 | 2.29 | 0.00 | 0.00 | ||||
Minimum of Months | 0.119572E+10 | 14286.51 | 134.58 | 0.381009E+10 | 0.00 | 0.500581E+10 | 0.58 | 3.19 | 0.00 | 0.00 | ||
Maximum of Months | 0.305102E+12 | 197557.47 | 744.00 | 0.107245E+13 | 0.00 | 0.137755E+13 | 3.50 | 4.24 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.131069E+12 | 0.00 | 744.00 | 228682.20 | 02-JAN-09:01 | 0.00 | 48.47 | 80.87 | 0.35 | 0.00 | 0.11 | 0.50 | 02-JAN-09:01 |
February | 0.112178E+12 | 0.00 | 672.00 | 236148.43 | 06-FEB-09:01 | 0.00 | 50.28 | 81.06 | 0.33 | 0.00 | 0.10 | 0.51 | 06-FEB-09:01 |
March | 0.599871E+11 | 0.00 | 727.14 | 173918.13 | 17-MAR-08:61 | 0.00 | 49.43 | 79.12 | 0.17 | 0.00 | 0.05 | 0.38 | 17-MAR-08:61 |
April | 0.678172E+11 | 0.00 | 584.89 | 157549.42 | 02-APR-18:05 | 0.00 | 38.64 | 70.38 | 0.15 | 0.00 | 0.06 | 0.34 | 02-APR-18:05 |
May | 0.288797E+11 | 0.00 | 363.66 | 99685.10 | 03-MAY-15:05 | 0.00 | 29.12 | 53.38 | 0.05 | 0.00 | 0.02 | 0.22 | 03-MAY-15:05 |
June | 0.706758E+09 | 0.00 | 56.40 | 24434.81 | 06-JUN-15:07 | 0.00 | 34.63 | 38.32 | 0.00 | 0.00 | 0.00 | 0.05 | 06-JUN-15:07 |
July | 97628851.95 | 0.00 | 30.74 | 26237.59 | 18-JUL-08:05 | 0.00 | 39.45 | 41.09 | 0.00 | 0.00 | 0.00 | 0.06 | 18-JUL-08:05 |
August | 0.303998E+09 | 0.00 | 35.24 | 25162.84 | 25-AUG-21:57 | 0.00 | 37.31 | 39.31 | 0.00 | 0.00 | 0.00 | 0.05 | 25-AUG-21:57 |
September | 0.715021E+10 | 0.00 | 146.49 | 72685.64 | 24-SEP-05:50 | 0.00 | 31.33 | 41.18 | 0.01 | 0.00 | 0.01 | 0.16 | 24-SEP-05:50 |
October | 0.443445E+11 | 0.00 | 415.06 | 133298.01 | 28-OCT-18:05 | 0.00 | 33.25 | 58.05 | 0.08 | 0.00 | 0.04 | 0.29 | 28-OCT-18:05 |
November | 0.889696E+11 | 0.00 | 693.53 | 159079.27 | 28-NOV-16:01 | 0.00 | 44.56 | 78.23 | 0.22 | 0.00 | 0.07 | 0.35 | 28-NOV-16:01 |
December | 0.803020E+11 | 0.00 | 744.00 | 186335.52 | 31-DEC-19:01 | 0.00 | 51.91 | 80.52 | 0.25 | 0.00 | 0.07 | 0.41 | 31-DEC-19:01 |
Annual Sum or Average | 0.621807E+12 | 0.00 | 5213.15 | 0.00 | 40.66 | 61.69 | 0.13 | 0.00 | 0.04 | ||||
Minimum of Months | 97628851.95 | 0.00 | 30.74 | 24434.81 | 0.00 | 29.12 | 38.32 | 0.00 | 0.00 | 0.00 | 0.05 | ||
Maximum of Months | 0.131069E+12 | 0.00 | 744.00 | 236148.43 | 0.00 | 51.91 | 81.06 | 0.35 | 0.00 | 0.11 | 0.51 |
Report: DXReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.539075E+11 | 0.00 | 472.34 | 0.539075E+11 | 0.00 | 0.00 | 1.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:03 | 37176.38 | 31-JAN-04:20 | 37176.38 | 31-JAN-06:30 | 0.00 | 01-JAN-07:30 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 0.477317E+11 | 0.00 | 443.01 | 0.477317E+11 | -0.0 | 0.00 | 1.00 | 01-FEB-00:07 | 0.00 | 01-FEB-00:03 | 34239.09 | 09-FEB-00:07 | 34239.09 | 09-FEB-07:15 | 0.00 | 10-FEB-19:01 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 0.558717E+11 | 0.00 | 442.51 | 0.558717E+11 | 0.00 | 0.00 | 1.00 | 01-MAR-00:20 | 0.00 | 01-MAR-00:03 | 50111.17 | 31-MAR-23:20 | 50111.17 | 31-MAR-23:20 | 0.00 | 01-MAR-18:07 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 0.531563E+11 | 0.00 | 400.83 | 0.531535E+11 | 2822619.74 | 0.00 | 1.00 | 01-APR-05:15 | 0.00 | 01-APR-00:10 | 50127.34 | 01-APR-05:15 | 50127.34 | 01-APR-18:05 | 3209.48 | 30-APR-23:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.524041E+11 | 0.00 | 382.98 | 0.492629E+11 | 0.314118E+10 | 0.00 | 1.00 | 01-MAY-05:13 | 0.00 | 01-MAY-00:05 | 63500.04 | 31-MAY-23:07 | 52824.89 | 01-MAY-15:07 | 18451.89 | 31-MAY-23:07 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.483817E+11 | 0.00 | 345.95 | 0.343300E+11 | 0.140518E+11 | 0.00 | 1.00 | 01-JUN-04:07 | 0.00 | 01-JUN-00:05 | 63461.80 | 01-JUN-04:07 | 45157.55 | 16-JUN-07:13 | 19002.17 | 01-JUN-13:37 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.477735E+11 | 0.00 | 357.31 | 0.272215E+11 | 0.205520E+11 | 0.00 | 1.00 | 01-JUL-05:17 | 0.00 | 01-JUL-00:10 | 67440.67 | 01-JUL-05:17 | 38750.63 | 04-JUL-09:17 | 29231.81 | 26-JUL-15:07 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.467088E+11 | 0.00 | 355.17 | 0.337453E+11 | 0.129635E+11 | 0.00 | 1.00 | 01-AUG-05:13 | 0.00 | 01-AUG-00:05 | 64949.78 | 31-AUG-05:13 | 47243.17 | 03-AUG-07:15 | 18479.41 | 12-AUG-15:07 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.457848E+11 | 0.00 | 345.64 | 0.373479E+11 | 0.843690E+10 | 0.00 | 1.00 | 01-SEP-04:07 | 0.00 | 01-SEP-00:05 | 59809.37 | 30-SEP-06:30 | 48921.15 | 28-SEP-18:35 | 11499.11 | 17-SEP-15:07 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.491227E+11 | 0.00 | 381.16 | 0.444038E+11 | 0.471896E+10 | 0.00 | 1.00 | 01-OCT-05:07 | 0.00 | 01-OCT-00:20 | 53535.79 | 31-OCT-06:15 | 48360.93 | 21-OCT-07:12 | 5716.19 | 25-OCT-17:13 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.490343E+11 | 0.00 | 406.78 | 0.490343E+11 | -0.0 | 0.00 | 1.00 | 01-NOV-05:13 | 0.00 | 01-NOV-00:05 | 44828.99 | 30-NOV-06:04 | 44828.99 | 30-NOV-06:04 | 0.00 | 27-NOV-21:10 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.523333E+11 | 0.00 | 451.91 | 0.523333E+11 | -0.0 | 0.00 | 1.00 | 01-DEC-00:07 | 0.00 | 01-DEC-00:03 | 39321.35 | 31-DEC-20:50 | 39321.35 | 31-DEC-06:50 | 0.00 | 30-DEC-00:20 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.602210E+12 | 0.00 | 4785.62 | 0.538343E+12 | 0.638671E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.457848E+11 | 0.00 | 345.64 | 0.272215E+11 | -0.0 | 0.00 | 1.00 | 0.00 | 34239.09 | 34239.09 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.558717E+11 | 0.00 | 472.34 | 0.558717E+11 | 0.205520E+11 | 0.00 | 1.00 | 0.00 | 67440.67 | 52824.89 | 29231.81 | 0.00 | 0.00 |
Report: DXReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.372806E+11 | 0.00 | 384.66 | 0.372806E+11 | 0.00 | 0.00 | 1.00 | 01-JAN-17:10 | 0.00 | 01-JAN-00:03 | 47038.12 | 31-JAN-23:00 | 47038.12 | 31-JAN-17:10 | 0.00 | 02-JAN-19:40 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 0.311321E+11 | 0.00 | 347.21 | 0.311321E+11 | -0.0 | 0.00 | 1.00 | 01-FEB-17:10 | 0.00 | 01-FEB-00:07 | 43318.83 | 09-FEB-22:50 | 43318.83 | 09-FEB-22:30 | 0.00 | 21-FEB-20:20 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 0.433818E+11 | 0.00 | 382.43 | 0.433818E+11 | 0.00 | 0.00 | 1.00 | 01-MAR-17:10 | 0.00 | 01-MAR-00:07 | 54906.72 | 01-MAR-17:10 | 54906.72 | 01-MAR-17:40 | 0.00 | 03-MAR-18:00 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 0.482845E+11 | 0.00 | 368.84 | 0.482839E+11 | 545241.35 | 0.00 | 1.00 | 01-APR-16:05 | 0.00 | 01-APR-00:10 | 63437.10 | 01-APR-17:50 | 63437.10 | 01-APR-17:50 | 2565.82 | 30-APR-23:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.557002E+11 | 0.00 | 348.04 | 0.523841E+11 | 0.331605E+10 | 0.00 | 1.00 | 01-MAY-16:10 | 0.00 | 01-MAY-00:05 | 71032.16 | 01-MAY-16:10 | 66874.12 | 01-MAY-16:10 | 12640.80 | 31-MAY-23:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.609469E+11 | 0.00 | 332.27 | 0.432314E+11 | 0.177155E+11 | 0.00 | 1.00 | 01-JUN-16:10 | 0.00 | 01-JUN-00:05 | 80321.66 | 01-JUN-20:45 | 57097.29 | 15-JUN-23:00 | 24037.55 | 01-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.671350E+11 | 0.00 | 348.60 | 0.382329E+11 | 0.289022E+11 | 0.00 | 1.00 | 01-JUL-16:10 | 0.00 | 01-JUL-00:20 | 85359.86 | 01-JUL-16:20 | 49056.51 | 04-JUL-20:20 | 36989.29 | 26-JUL-20:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.648274E+11 | 0.00 | 345.54 | 0.468133E+11 | 0.180141E+11 | 0.00 | 1.00 | 01-AUG-16:10 | 0.00 | 01-AUG-00:05 | 82205.79 | 31-AUG-18:50 | 59780.47 | 07-AUG-20:20 | 23374.72 | 12-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.575974E+11 | 0.00 | 334.13 | 0.469975E+11 | 0.105999E+11 | 0.00 | 1.00 | 01-SEP-16:10 | 0.00 | 01-SEP-00:05 | 75696.82 | 30-SEP-16:05 | 61952.13 | 28-SEP-19:20 | 14527.61 | 17-SEP-16:10 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.531736E+11 | 0.00 | 353.89 | 0.480779E+11 | 0.509571E+10 | 0.00 | 1.00 | 01-OCT-16:10 | 0.00 | 01-OCT-00:20 | 67752.99 | 31-OCT-21:10 | 61167.12 | 27-OCT-21:00 | 7217.10 | 25-OCT-17:13 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.431527E+11 | 0.00 | 369.73 | 0.431527E+11 | -0.0 | 0.00 | 1.00 | 01-NOV-16:10 | 0.00 | 01-NOV-00:05 | 56728.13 | 30-NOV-17:20 | 56728.13 | 30-NOV-19:40 | 0.00 | 05-NOV-20:50 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.392597E+11 | 0.00 | 385.15 | 0.392597E+11 | -0.0 | 0.00 | 1.00 | 01-DEC-17:10 | 0.00 | 01-DEC-00:07 | 49754.16 | 31-DEC-18:12 | 49754.16 | 31-DEC-24:00 | 0.00 | 01-DEC-19:00 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.601872E+12 | 0.00 | 4300.50 | 0.518228E+12 | 0.836441E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.311321E+11 | 0.00 | 332.27 | 0.311321E+11 | -0.0 | 0.00 | 1.00 | 0.00 | 43318.83 | 43318.83 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.671350E+11 | 0.00 | 385.15 | 0.523841E+11 | 0.289022E+11 | 0.00 | 1.00 | 0.00 | 85359.86 | 66874.12 | 36989.29 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.329359E+10 | 0.00 | 24.00 | 0.325708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 128470.33 | 27-MAR-16:00 | 128470.33 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.339278E+11 | 0.00 | 155.64 | 0.336599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 208088.51 | 09-APR-10:50 | 200530.17 | 07-APR-17:00 | 0.00 | 0.00 | 0.00 |
May | 0.125500E+12 | 0.00 | 467.03 | 0.107682E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 297829.63 | 31-MAY-17:17 | 216421.43 | 28-MAY-14:27 | 0.00 | 0.00 | 0.00 |
June | 0.520638E+12 | 0.00 | 707.50 | 0.300692E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 504405.71 | 24-JUN-17:17 | 283459.21 | 22-JUN-18:08 | 0.00 | 0.00 | 0.00 |
July | 0.826657E+12 | 0.00 | 744.00 | 0.431939E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 528638.08 | 05-JUL-19:10 | 253507.57 | 11-JUL-15:07 | 0.00 | 0.00 | 0.00 |
August | 0.668323E+12 | 0.00 | 744.00 | 0.425152E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 586630.65 | 11-AUG-21:53 | 332242.76 | 24-AUG-18:30 | 0.00 | 0.00 | 0.00 |
September | 0.360538E+12 | 0.00 | 642.17 | 0.242148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 536215.48 | 13-SEP-21:00 | 276090.45 | 01-SEP-18:27 | 0.00 | 0.00 | 0.00 |
October | 0.123645E+12 | 0.00 | 348.00 | 0.787861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 278389.69 | 05-OCT-19:10 | 175295.57 | 25-OCT-10:33 | 0.00 | 0.00 | 0.00 |
November | 0.332701E+10 | 0.00 | 34.83 | 0.303487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62625.09 | 04-NOV-10:45 | 62625.09 | 04-NOV-10:45 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.266585E+13 | 0.00 | 3867.17 | 0.162635E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.826657E+12 | 0.00 | 744.00 | 0.431939E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 586630.65 | 332242.76 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.274237E+09 | 0.00 | 15.00 | 0.236684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19369.32 | 27-MAR-13:00 | 14899.81 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.217150E+10 | 0.00 | 99.83 | 0.212913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20182.20 | 09-APR-10:00 | 17842.11 | 07-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.903150E+10 | 0.00 | 325.33 | 0.753219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31077.44 | 31-MAY-17:00 | 19489.00 | 30-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.428359E+11 | 0.00 | 557.83 | 0.239619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46753.17 | 24-JUN-18:07 | 22015.09 | 19-JUN-12:20 | 0.00 | 0.00 | 0.00 |
July | 0.583701E+11 | 0.00 | 589.00 | 0.326037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47889.79 | 28-JUL-08:03 | 21002.30 | 07-JUL-12:20 | 0.00 | 0.00 | 0.00 |
August | 0.471787E+11 | 0.00 | 589.00 | 0.307582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42812.08 | 10-AUG-21:51 | 20975.03 | 24-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.291741E+11 | 0.00 | 496.50 | 0.191404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46252.66 | 14-SEP-08:10 | 19566.49 | 01-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.100475E+11 | 0.00 | 251.50 | 0.576025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30632.72 | 03-OCT-15:02 | 17302.40 | 04-OCT-12:15 | 0.00 | 0.00 | 0.00 |
November | 0.209566E+09 | 0.00 | 19.17 | 0.180115E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7314.01 | 10-NOV-08:00 | 6401.27 | 04-NOV-13:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199293E+12 | 0.00 | 2943.17 | 0.122303E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.583701E+11 | 0.00 | 589.00 | 0.326037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47889.79 | 22015.09 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 64008021.92 | 0.00 | 13.66 | 45918715.32 | 0.00 | 0.00 | 0.00 | 0.00 | 12307.22 | 20-JAN-16:02 | 12307.22 | 20-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.153521E+09 | 0.00 | 31.48 | 0.131983E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12306.64 | 17-FEB-16:02 | 12306.64 | 17-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.920522E+09 | 0.00 | 149.61 | 0.695827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14298.29 | 27-MAR-15:02 | 12308.79 | 11-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.227997E+10 | 0.00 | 325.43 | 0.153042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13399.76 | 09-APR-08:62 | 12735.39 | 10-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.482789E+10 | 0.00 | 589.66 | 0.312487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15010.67 | 19-MAY-18:02 | 13071.31 | 20-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.893195E+10 | 0.00 | 675.05 | 0.549767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17147.21 | 27-JUN-08:62 | 13022.83 | 15-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.108408E+11 | 0.00 | 714.40 | 0.690828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17238.94 | 28-JUL-08:61 | 13130.30 | 12-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.115105E+11 | 0.00 | 716.50 | 0.783713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16550.83 | 06-AUG-08:62 | 13170.07 | 17-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.707456E+10 | 0.00 | 649.63 | 0.435295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18429.45 | 22-SEP-18:02 | 12945.70 | 14-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.467878E+10 | 0.00 | 559.70 | 0.289275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15358.74 | 06-OCT-08:62 | 12671.27 | 25-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.426031E+09 | 0.00 | 113.62 | 0.239759E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13153.85 | 10-NOV-16:02 | 11898.34 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 78715320.67 | 0.00 | 22.38 | 68580932.23 | 0.00 | 0.00 | 0.00 | 0.00 | 12310.17 | 17-DEC-16:02 | 12310.17 | 17-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.517873E+11 | 0.00 | 4561.12 | 0.333261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 64008021.92 | 0.00 | 13.66 | 45918715.32 | 0.00 | 0.00 | 0.00 | 0.00 | 12306.64 | 11898.34 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.115105E+11 | 0.00 | 716.50 | 0.783713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18429.45 | 13170.07 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 15174271.23 | 0.00 | 2.45 | 10870415.63 | 0.00 | 0.00 | 0.00 | 0.00 | 10928.86 | 20-JAN-16:02 | 10928.86 | 20-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 32967570.26 | 0.00 | 7.97 | 27810893.17 | 0.00 | 0.00 | 0.00 | 0.00 | 11201.20 | 22-FEB-16:02 | 11201.20 | 22-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.379900E+09 | 0.00 | 70.07 | 0.292778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14102.19 | 27-MAR-15:02 | 11932.30 | 11-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.131100E+10 | 0.00 | 231.81 | 0.812394E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13628.12 | 27-APR-18:21 | 13215.25 | 09-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.329105E+10 | 0.00 | 446.34 | 0.200994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16073.67 | 31-MAY-08:51 | 13736.71 | 29-MAY-18:31 | 0.00 | 0.00 | 0.00 |
June | 0.641567E+10 | 0.00 | 460.82 | 0.410867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18083.87 | 27-JUN-08:51 | 13465.56 | 22-JUN-07:51 | 0.00 | 0.00 | 0.00 |
July | 0.933381E+10 | 0.00 | 591.12 | 0.612687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18608.18 | 23-JUL-08:21 | 13330.99 | 03-JUL-18:51 | 0.00 | 0.00 | 0.00 |
August | 0.942814E+10 | 0.00 | 595.15 | 0.642379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18677.76 | 12-AUG-08:61 | 12837.06 | 17-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.416171E+10 | 0.00 | 433.14 | 0.240021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17218.38 | 14-SEP-08:51 | 12752.12 | 10-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.188223E+10 | 0.00 | 340.11 | 0.969775E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15041.74 | 05-OCT-21:51 | 12386.89 | 24-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 82711244.94 | 0.00 | 29.87 | 49508264.34 | 0.00 | 0.00 | 0.00 | 0.00 | 12961.75 | 10-NOV-16:02 | 11336.24 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 12636344.30 | 0.00 | 1.65 | 10178339.62 | 0.00 | 0.00 | 0.00 | 0.00 | 10980.93 | 17-DEC-16:02 | 10980.93 | 17-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.363470E+11 | 0.00 | 3210.48 | 0.232428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 12636344.30 | 0.00 | 1.65 | 10178339.62 | 0.00 | 0.00 | 0.00 | 0.00 | 10928.86 | 10928.86 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.942814E+10 | 0.00 | 595.15 | 0.642379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18677.76 | 13736.71 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 29177817.74 | 0.00 | 1.67 | 29177817.74 | 0.00 | 0.00 | 0.00 | 0.00 | 6195.67 | 31-JAN-15:00 | 6195.67 | 31-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.239358E+10 | 0.00 | 75.27 | 0.239358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27817.14 | 20-FEB-13:30 | 27817.14 | 20-FEB-13:30 | 0.00 | 0.00 | 0.00 |
March | 0.697116E+10 | 0.00 | 178.19 | 0.569826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33958.32 | 28-MAR-12:30 | 32670.35 | 15-MAR-13:15 | 0.00 | 0.00 | 0.00 |
April | 0.142742E+11 | 0.00 | 345.51 | 0.897074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44584.17 | 07-APR-13:15 | 40430.26 | 07-APR-13:20 | 0.00 | 0.00 | 0.00 |
May | 0.246644E+11 | 0.00 | 603.35 | 0.120522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34779.66 | 30-MAY-12:30 | 27182.17 | 30-MAY-12:50 | 0.00 | 0.00 | 0.00 |
June | 0.391544E+11 | 0.00 | 713.98 | 0.193201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36425.96 | 19-JUN-12:40 | 29459.21 | 19-JUN-13:20 | 0.00 | 0.00 | 0.00 |
July | 0.517813E+11 | 0.00 | 744.00 | 0.282616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38221.24 | 08-JUL-12:00 | 32917.53 | 10-JUL-13:10 | 0.00 | 0.00 | 0.00 |
August | 0.609320E+11 | 0.00 | 744.00 | 0.384272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46899.33 | 30-AUG-13:00 | 41357.56 | 24-AUG-13:10 | 0.00 | 0.00 | 0.00 |
September | 0.462527E+11 | 0.00 | 695.17 | 0.280961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51373.91 | 28-SEP-12:40 | 43049.86 | 30-SEP-12:30 | 0.00 | 0.00 | 0.00 |
October | 0.452908E+11 | 0.00 | 666.17 | 0.340191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54376.20 | 04-OCT-12:10 | 50163.59 | 30-OCT-13:25 | 0.00 | 0.00 | 0.00 |
November | 0.105538E+11 | 0.00 | 232.82 | 0.833222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46035.96 | 02-NOV-12:50 | 46035.96 | 02-NOV-12:50 | 0.00 | 0.00 | 0.00 |
December | 0.358407E+10 | 0.00 | 87.57 | 0.358407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31277.11 | 17-DEC-13:40 | 31277.11 | 17-DEC-13:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.305881E+12 | 0.00 | 5087.71 | 0.189184E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 29177817.74 | 0.00 | 1.67 | 29177817.74 | 0.00 | 0.00 | 0.00 | 0.00 | 6195.67 | 6195.67 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.609320E+11 | 0.00 | 744.00 | 0.384272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54376.20 | 50163.59 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.407319E+09 | 0.00 | 33.46 | 0.219243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63536.31 | 24-JAN-09:02 | 56105.05 | 23-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.223803E+09 | 0.00 | 21.93 | 0.190838E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59136.83 | 18-FEB-09:02 | 59136.83 | 18-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.379511E+10 | 0.00 | 198.30 | 0.256748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69818.68 | 27-MAR-15:02 | 61833.40 | 03-MAR-19:02 | 0.00 | 0.00 | 0.00 |
April | 0.144910E+11 | 0.00 | 383.04 | 0.942517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71865.85 | 08-APR-15:02 | 68890.76 | 07-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.316013E+11 | 0.00 | 458.46 | 0.223926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82026.19 | 31-MAY-21:51 | 70757.90 | 30-MAY-08:21 | 0.00 | 0.00 | 0.00 |
June | 0.455839E+11 | 0.00 | 424.48 | 0.316170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99538.92 | 25-JUN-07:51 | 72066.13 | 22-JUN-07:51 | 0.00 | 0.00 | 0.00 |
July | 0.634555E+11 | 0.00 | 557.27 | 0.438715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102657.74 | 23-JUL-08:21 | 71068.72 | 06-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.575539E+11 | 0.00 | 545.57 | 0.397391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 101738.43 | 12-AUG-08:61 | 71635.08 | 12-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.334056E+11 | 0.00 | 391.06 | 0.221502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94392.99 | 14-SEP-08:51 | 71124.04 | 01-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.183255E+11 | 0.00 | 393.06 | 0.117839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81501.38 | 05-OCT-21:51 | 65911.55 | 06-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.491074E+10 | 0.00 | 235.05 | 0.291000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67277.22 | 10-NOV-09:13 | 61743.24 | 04-NOV-19:42 | 0.00 | 0.00 | 0.00 |
December | 0.371310E+09 | 0.00 | 36.14 | 0.282932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58947.01 | 10-DEC-09:02 | 58947.01 | 10-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274125E+12 | 0.00 | 3677.81 | 0.187150E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.223803E+09 | 0.00 | 21.93 | 0.190838E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58947.01 | 56105.05 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.634555E+11 | 0.00 | 557.27 | 0.438715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102657.74 | 72066.13 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 92860610.84 | 0.00 | 18.77 | 69566319.03 | 0.00 | 0.00 | 0.00 | 0.00 | 10305.71 | 20-JAN-09:02 | 10305.71 | 20-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.153828E+09 | 0.00 | 32.21 | 0.129050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11262.09 | 25-FEB-09:01 | 11262.09 | 25-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.784220E+09 | 0.00 | 155.02 | 0.569701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13234.73 | 27-MAR-15:02 | 11266.44 | 11-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.231482E+10 | 0.00 | 347.72 | 0.150239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12140.13 | 27-APR-15:02 | 11502.56 | 10-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.499073E+10 | 0.00 | 604.79 | 0.326818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13605.28 | 05-MAY-15:01 | 11962.54 | 20-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.842043E+10 | 0.00 | 683.62 | 0.507595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15399.59 | 18-JUN-08:62 | 12148.98 | 01-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.107165E+11 | 0.00 | 722.79 | 0.682144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15228.46 | 28-JUL-08:61 | 12109.06 | 13-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.114162E+11 | 0.00 | 727.57 | 0.783926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15091.37 | 06-AUG-08:62 | 12108.84 | 04-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.714050E+10 | 0.00 | 662.87 | 0.446805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16921.09 | 22-SEP-18:02 | 12060.33 | 14-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.449384E+10 | 0.00 | 570.15 | 0.271379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14045.14 | 06-OCT-08:62 | 11511.56 | 25-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.613449E+09 | 0.00 | 140.57 | 0.375009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11870.23 | 11-NOV-09:02 | 11018.34 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.166047E+09 | 0.00 | 35.13 | 0.122841E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10569.25 | 02-DEC-09:01 | 10569.25 | 02-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.513035E+11 | 0.00 | 4701.20 | 0.329552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 92860610.84 | 0.00 | 18.77 | 69566319.03 | 0.00 | 0.00 | 0.00 | 0.00 | 10305.71 | 10305.71 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.114162E+11 | 0.00 | 727.57 | 0.783926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16921.09 | 12148.98 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 9629715.39 | 0.00 | 3.19 | 5133068.24 | 0.00 | 0.00 | 0.00 | 0.00 | 5418.67 | 19-JAN-09:01 | 4398.46 | 19-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 27497241.19 | 0.00 | 8.13 | 20559364.30 | 0.00 | 0.00 | 0.00 | 0.00 | 10327.48 | 25-FEB-09:01 | 10327.48 | 25-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.288949E+09 | 0.00 | 63.33 | 0.203514E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12442.37 | 27-MAR-15:02 | 10247.32 | 21-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.141435E+10 | 0.00 | 262.90 | 0.866272E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13000.01 | 08-APR-08:51 | 12369.66 | 08-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.357320E+10 | 0.00 | 467.73 | 0.227947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16701.56 | 31-MAY-08:32 | 14143.98 | 30-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.610197E+10 | 0.00 | 470.33 | 0.380820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17438.32 | 20-JUN-08:62 | 14232.78 | 22-JUN-07:32 | 0.00 | 0.00 | 0.00 |
July | 0.913634E+10 | 0.00 | 598.43 | 0.589054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17651.73 | 01-JUL-08:32 | 13795.85 | 11-JUL-08:32 | 0.00 | 0.00 | 0.00 |
August | 0.921035E+10 | 0.00 | 606.67 | 0.611833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17249.09 | 12-AUG-08:61 | 13377.60 | 10-AUG-08:32 | 0.00 | 0.00 | 0.00 |
September | 0.430448E+10 | 0.00 | 452.65 | 0.252589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17141.85 | 06-SEP-08:32 | 13274.11 | 06-SEP-08:32 | 0.00 | 0.00 | 0.00 |
October | 0.185074E+10 | 0.00 | 347.10 | 0.100177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14800.23 | 25-OCT-08:51 | 11528.94 | 15-OCT-08:51 | 0.00 | 0.00 | 0.00 |
November | 0.176482E+09 | 0.00 | 46.24 | 95178337.33 | 0.00 | 0.00 | 0.00 | 0.00 | 11285.76 | 11-NOV-09:02 | 10343.83 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 18289933.38 | 0.00 | 6.92 | 10622781.76 | 0.00 | 0.00 | 0.00 | 0.00 | 8520.73 | 20-DEC-09:01 | 8520.73 | 20-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.361123E+11 | 0.00 | 3333.63 | 0.228255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9629715.39 | 0.00 | 3.19 | 5133068.24 | 0.00 | 0.00 | 0.00 | 0.00 | 5418.67 | 4398.46 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.921035E+10 | 0.00 | 606.67 | 0.611833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17651.73 | 14232.78 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 15267966.29 | 0.00 | 10.83 | 10524263.99 | 0.00 | 0.00 | 0.00 | 0.00 | 3245.18 | 20-JAN-16:02 | 3245.18 | 20-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 36973141.25 | 0.00 | 26.23 | 31154800.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3245.07 | 17-FEB-16:02 | 3245.07 | 17-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.231152E+09 | 0.00 | 120.67 | 0.175484E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3761.88 | 27-MAR-15:02 | 3245.50 | 11-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.575878E+09 | 0.00 | 288.95 | 0.398531E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3678.56 | 09-APR-08:62 | 3357.43 | 10-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.122022E+10 | 0.00 | 549.98 | 0.820018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3981.73 | 19-MAY-18:02 | 3445.93 | 20-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.228670E+10 | 0.00 | 672.87 | 0.140240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4726.62 | 27-JUN-08:62 | 3433.19 | 22-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.282333E+10 | 0.00 | 714.87 | 0.178369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4750.67 | 28-JUL-08:61 | 3458.70 | 12-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.296197E+10 | 0.00 | 715.33 | 0.200274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4647.81 | 06-AUG-08:62 | 3492.76 | 15-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.173283E+10 | 0.00 | 625.36 | 0.106337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5054.60 | 22-SEP-18:02 | 3431.53 | 10-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.106882E+10 | 0.00 | 488.63 | 0.664043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4149.75 | 25-OCT-08:62 | 3339.27 | 25-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 81654892.82 | 0.00 | 75.27 | 47622023.48 | 0.00 | 0.00 | 0.00 | 0.00 | 3522.38 | 10-NOV-16:02 | 3131.03 | 08-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 16087127.78 | 0.00 | 14.55 | 14539145.18 | 0.00 | 0.00 | 0.00 | 0.00 | 3243.31 | 02-DEC-16:01 | 3243.31 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130509E+11 | 0.00 | 4303.54 | 0.841412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 15267966.29 | 0.00 | 10.83 | 10524263.99 | 0.00 | 0.00 | 0.00 | 0.00 | 3243.31 | 3131.03 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.296197E+10 | 0.00 | 715.33 | 0.200274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5054.60 | 3492.76 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2555629.22 | 0.00 | 1.93 | 1588351.87 | 0.00 | 0.00 | 0.00 | 0.00 | 2244.60 | 17-JAN-16:02 | 2244.60 | 17-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 5143422.57 | 0.00 | 6.09 | 4091140.97 | 0.00 | 0.00 | 0.00 | 0.00 | 2316.43 | 24-FEB-16:01 | 2316.43 | 24-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 87044921.26 | 0.00 | 60.67 | 65905348.16 | 0.00 | 0.00 | 0.00 | 0.00 | 3789.37 | 27-MAR-15:02 | 3140.05 | 11-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.328305E+09 | 0.00 | 206.39 | 0.207637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3610.91 | 27-APR-18:21 | 3502.45 | 09-APR-18:11 | 0.00 | 0.00 | 0.00 |
May | 0.852509E+09 | 0.00 | 418.68 | 0.536001E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4326.89 | 31-MAY-08:51 | 3687.60 | 29-MAY-18:31 | 0.00 | 0.00 | 0.00 |
June | 0.171569E+10 | 0.00 | 461.98 | 0.109970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4961.60 | 25-JUN-07:51 | 3563.02 | 22-JUN-07:51 | 0.00 | 0.00 | 0.00 |
July | 0.247700E+10 | 0.00 | 593.19 | 0.162321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5114.77 | 23-JUL-08:21 | 3467.39 | 03-JUL-18:51 | 0.00 | 0.00 | 0.00 |
August | 0.246169E+10 | 0.00 | 596.36 | 0.166899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5104.57 | 12-AUG-08:61 | 3366.49 | 17-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.102905E+10 | 0.00 | 411.27 | 0.593613E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4714.01 | 14-SEP-08:51 | 3403.36 | 10-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.389659E+09 | 0.00 | 277.33 | 0.195526E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4080.11 | 05-OCT-21:51 | 3211.67 | 02-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 13466654.68 | 0.00 | 13.76 | 7898471.69 | 0.00 | 0.00 | 0.00 | 0.00 | 3418.18 | 10-NOV-16:02 | 2943.92 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 1905516.15 | 0.00 | 1.37 | 1274314.01 | 0.00 | 0.00 | 0.00 | 0.00 | 1764.94 | 17-DEC-16:02 | 1594.27 | 17-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.936401E+10 | 0.00 | 3049.01 | 0.600543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1905516.15 | 0.00 | 1.37 | 1274314.01 | 0.00 | 0.00 | 0.00 | 0.00 | 1764.94 | 1594.27 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.247700E+10 | 0.00 | 596.36 | 0.166899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5114.77 | 3687.60 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.102791E+10 | 0.00 | 107.69 | 0.889214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15173.93 | 10-JAN-16:02 | 15173.93 | 10-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.152240E+10 | 0.00 | 166.94 | 0.137651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15174.68 | 10-FEB-16:01 | 15174.68 | 10-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.275534E+10 | 0.00 | 265.93 | 0.220136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16116.01 | 27-MAR-15:02 | 15173.16 | 15-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.389545E+10 | 0.00 | 375.25 | 0.268449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16734.02 | 30-APR-15:02 | 15364.37 | 10-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.614743E+10 | 0.00 | 596.33 | 0.387626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18740.17 | 31-MAY-18:02 | 16106.48 | 20-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.108056E+11 | 0.00 | 662.54 | 0.613684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22989.61 | 27-JUN-08:62 | 16191.20 | 22-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.142831E+11 | 0.00 | 712.56 | 0.885453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22859.02 | 28-JUL-08:61 | 16351.08 | 09-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.156806E+11 | 0.00 | 715.78 | 0.104904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21778.31 | 06-AUG-08:62 | 16438.55 | 12-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.114172E+11 | 0.00 | 656.58 | 0.740963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24359.34 | 22-SEP-18:02 | 16329.01 | 14-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.100800E+11 | 0.00 | 622.92 | 0.727584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19609.33 | 05-OCT-18:02 | 15661.94 | 02-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.258320E+10 | 0.00 | 271.71 | 0.187988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16082.27 | 11-NOV-16:02 | 15167.85 | 02-NOV-18:02 | 0.00 | 0.00 | 0.00 |
December | 0.172839E+10 | 0.00 | 164.58 | 0.153852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15244.06 | 25-DEC-16:02 | 15172.32 | 15-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.819266E+11 | 0.00 | 5318.82 | 0.546135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.102791E+10 | 0.00 | 107.69 | 0.889214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15173.93 | 15167.85 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.156806E+11 | 0.00 | 715.78 | 0.104904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24359.34 | 16438.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 609.38 | 399.88 | 209.50 | 603.30 | 602.95 | 0.00 | 0.00 | 0.00 |
February | 806.45 | 535.99 | 270.46 | 814.23 | 597.44 | 0.00 | 0.00 | 0.00 |
March | 714.52 | 393.33 | 321.18 | 766.94 | 423.82 | 0.00 | 0.00 | 0.00 |
April | 568.74 | 230.10 | 338.64 | 645.29 | 298.18 | 0.00 | 0.00 | 0.00 |
May | 488.48 | 100.01 | 388.47 | 603.81 | 169.99 | 0.00 | 0.00 | 0.00 |
June | 461.24 | 71.07 | 390.17 | 654.79 | 80.05 | 0.00 | 0.00 | 0.00 |
July | 479.92 | 81.00 | 398.92 | 748.56 | 32.97 | 0.00 | 0.00 | 0.00 |
August | 642.81 | 237.13 | 405.68 | 987.25 | 60.43 | 0.00 | 0.00 | 0.00 |
September | 678.34 | 340.59 | 337.75 | 929.40 | 129.67 | 0.00 | 0.00 | 0.00 |
October | 958.61 | 601.13 | 357.48 | 1208.00 | 269.44 | 0.00 | 0.00 | 0.00 |
November | 663.77 | 398.18 | 265.59 | 715.54 | 417.78 | 0.00 | 0.00 | 0.00 |
December | 658.37 | 467.61 | 190.76 | 679.69 | 542.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 643.45 | 320.24 | 323.20 | 779.93 | 300.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 461.24 | 71.07 | 190.76 | 603.30 | 32.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 958.61 | 601.13 | 405.68 | 1208.00 | 602.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1715.97 | 1126.05 | 589.93 | 1678.06 | 1751.23 | 0.00 | 0.00 | 0.00 |
February | 2270.92 | 1509.32 | 761.60 | 2264.07 | 1740.12 | 0.00 | 0.00 | 0.00 |
March | 2012.03 | 1107.60 | 904.43 | 2131.50 | 1266.22 | 0.00 | 0.00 | 0.00 |
April | 1601.52 | 647.94 | 953.59 | 1786.72 | 908.11 | 0.00 | 0.00 | 0.00 |
May | 1375.52 | 281.62 | 1093.90 | 1659.67 | 539.19 | 0.00 | 0.00 | 0.00 |
June | 1298.82 | 200.12 | 1098.70 | 1815.65 | 262.59 | 0.00 | 0.00 | 0.00 |
July | 1351.43 | 228.09 | 1123.34 | 2087.08 | 114.51 | 0.00 | 0.00 | 0.00 |
August | 1810.11 | 667.74 | 1142.38 | 2762.21 | 189.13 | 0.00 | 0.00 | 0.00 |
September | 1910.16 | 959.07 | 951.10 | 2589.61 | 415.79 | 0.00 | 0.00 | 0.00 |
October | 2699.38 | 1692.74 | 1006.64 | 3368.82 | 828.30 | 0.00 | 0.00 | 0.00 |
November | 1869.14 | 1121.25 | 747.90 | 1983.37 | 1248.39 | 0.00 | 0.00 | 0.00 |
December | 1853.92 | 1316.75 | 537.17 | 1890.29 | 1591.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1811.90 | 901.78 | 910.12 | 2168.66 | 899.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1298.82 | 200.12 | 537.17 | 1659.67 | 114.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2699.38 | 1692.74 | 1142.38 | 3368.82 | 1751.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2229.15 | 1462.80 | 766.35 | 2211.76 | 2389.44 | 0.00 | 0.00 | 0.00 |
February | 2950.05 | 1960.69 | 989.36 | 2992.97 | 2355.54 | 0.00 | 0.00 | 0.00 |
March | 2613.75 | 1438.84 | 1174.91 | 2819.57 | 1721.15 | 0.00 | 0.00 | 0.00 |
April | 2080.47 | 841.71 | 1238.76 | 2360.40 | 1245.75 | 0.00 | 0.00 | 0.00 |
May | 1786.87 | 365.84 | 1421.04 | 2187.20 | 744.96 | 0.00 | 0.00 | 0.00 |
June | 1687.25 | 259.97 | 1427.28 | 2397.78 | 359.56 | 0.00 | 0.00 | 0.00 |
July | 1755.59 | 296.31 | 1459.28 | 2767.34 | 154.95 | 0.00 | 0.00 | 0.00 |
August | 2351.44 | 867.43 | 1484.02 | 3669.63 | 246.45 | 0.00 | 0.00 | 0.00 |
September | 2481.41 | 1245.88 | 1235.53 | 3425.21 | 559.09 | 0.00 | 0.00 | 0.00 |
October | 3506.65 | 2198.97 | 1307.68 | 4459.40 | 1103.30 | 0.00 | 0.00 | 0.00 |
November | 2428.12 | 1456.56 | 971.56 | 2612.78 | 1709.19 | 0.00 | 0.00 | 0.00 |
December | 2408.35 | 1710.53 | 697.81 | 2491.33 | 2173.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2353.77 | 1171.47 | 1182.30 | 2867.07 | 1223.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1687.25 | 259.97 | 697.81 | 2187.20 | 154.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3506.65 | 2198.97 | 1484.02 | 4459.40 | 2389.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.49 | 79.06 | 41.42 | 119.75 | 120.98 | 0.00 | 0.00 | 0.00 |
February | 159.45 | 105.97 | 53.48 | 161.56 | 120.13 | 0.00 | 0.00 | 0.00 |
March | 141.27 | 77.77 | 63.50 | 151.34 | 85.63 | 0.00 | 0.00 | 0.00 |
April | 112.45 | 45.49 | 66.96 | 126.95 | 59.82 | 0.00 | 0.00 | 0.00 |
May | 96.58 | 19.77 | 76.81 | 118.00 | 33.47 | 0.00 | 0.00 | 0.00 |
June | 91.20 | 14.05 | 77.14 | 131.01 | 12.88 | 0.00 | 0.00 | 0.00 |
July | 94.89 | 16.02 | 78.87 | 153.80 | 3.20 | 0.00 | 0.00 | 0.00 |
August | 127.10 | 46.88 | 80.21 | 202.26 | 7.64 | 0.00 | 0.00 | 0.00 |
September | 134.12 | 67.34 | 66.78 | 186.68 | 21.75 | 0.00 | 0.00 | 0.00 |
October | 189.53 | 118.85 | 70.68 | 241.07 | 50.19 | 0.00 | 0.00 | 0.00 |
November | 131.24 | 78.73 | 52.51 | 142.50 | 82.65 | 0.00 | 0.00 | 0.00 |
December | 130.17 | 92.45 | 37.72 | 135.44 | 107.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127.22 | 63.32 | 63.90 | 155.92 | 58.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.20 | 14.05 | 37.72 | 118.00 | 3.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 189.53 | 118.85 | 80.21 | 241.07 | 120.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.55 | 36.76 | 52.79 | 53.79 | 244.31 | 0.00 | 0.00 | 0.00 |
February | 131.54 | 57.73 | 73.81 | 88.63 | 247.02 | 0.00 | 0.00 | 0.00 |
March | 195.39 | 90.55 | 104.84 | 175.55 | 159.57 | 0.00 | 0.00 | 0.00 |
April | 212.21 | 90.69 | 121.52 | 222.18 | 109.18 | 0.00 | 0.00 | 0.00 |
May | 247.91 | 94.24 | 153.67 | 300.02 | 60.57 | 0.00 | 0.00 | 0.00 |
June | 270.86 | 109.31 | 161.55 | 373.63 | 23.49 | 0.00 | 0.00 | 0.00 |
July | 253.41 | 95.23 | 158.18 | 382.36 | 5.91 | 0.00 | 0.00 | 0.00 |
August | 280.37 | 129.63 | 150.74 | 417.49 | 14.16 | 0.00 | 0.00 | 0.00 |
September | 199.48 | 87.09 | 112.39 | 263.00 | 40.71 | 0.00 | 0.00 | 0.00 |
October | 197.92 | 96.42 | 101.51 | 227.58 | 96.43 | 0.00 | 0.00 | 0.00 |
November | 93.21 | 27.23 | 65.98 | 63.59 | 164.25 | 0.00 | 0.00 | 0.00 |
December | 82.33 | 35.54 | 46.79 | 50.64 | 221.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 188.24 | 79.38 | 108.86 | 219.13 | 114.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.33 | 27.23 | 46.79 | 50.64 | 5.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 280.37 | 129.63 | 161.55 | 417.49 | 247.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.18 | 0.00 | 23.18 | 1.47 | 135.68 | 0.00 | 0.00 | 0.00 |
February | 31.72 | 0.00 | 31.72 | 3.13 | 138.75 | 0.00 | 0.00 | 0.00 |
March | 44.00 | 0.00 | 44.00 | 16.28 | 89.63 | 0.00 | 0.00 | 0.00 |
April | 52.95 | 0.22 | 52.73 | 35.44 | 59.42 | 0.00 | 0.00 | 0.00 |
May | 70.43 | 2.58 | 67.85 | 70.51 | 32.44 | 0.00 | 0.00 | 0.00 |
June | 74.30 | 3.95 | 70.35 | 96.76 | 14.73 | 0.00 | 0.00 | 0.00 |
July | 72.11 | 2.81 | 69.30 | 112.98 | 4.25 | 0.00 | 0.00 | 0.00 |
August | 63.77 | 0.85 | 62.92 | 99.38 | 8.47 | 0.00 | 0.00 | 0.00 |
September | 48.02 | 0.03 | 47.99 | 56.00 | 24.12 | 0.00 | 0.00 | 0.00 |
October | 41.52 | 0.00 | 41.52 | 33.05 | 53.23 | 0.00 | 0.00 | 0.00 |
November | 29.12 | 0.00 | 29.12 | 9.29 | 89.29 | 0.00 | 0.00 | 0.00 |
December | 20.22 | 0.00 | 20.22 | 1.00 | 122.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.70 | 0.87 | 46.83 | 44.90 | 63.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.22 | 0.00 | 20.22 | 1.00 | 4.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.30 | 3.95 | 70.35 | 112.98 | 138.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.55 | 36.76 | 52.79 | 56.58 | 241.72 | 0.00 | 0.00 | 0.00 |
February | 131.54 | 57.73 | 73.81 | 92.76 | 243.12 | 0.00 | 0.00 | 0.00 |
March | 195.39 | 90.55 | 104.84 | 179.90 | 157.36 | 0.00 | 0.00 | 0.00 |
April | 212.21 | 90.69 | 121.52 | 223.93 | 108.83 | 0.00 | 0.00 | 0.00 |
May | 247.91 | 94.24 | 153.67 | 297.52 | 62.75 | 0.00 | 0.00 | 0.00 |
June | 270.86 | 109.31 | 161.55 | 367.22 | 28.16 | 0.00 | 0.00 | 0.00 |
July | 253.41 | 95.23 | 158.18 | 379.97 | 7.93 | 0.00 | 0.00 | 0.00 |
August | 280.37 | 129.63 | 150.74 | 417.22 | 16.06 | 0.00 | 0.00 | 0.00 |
September | 199.48 | 87.09 | 112.39 | 261.97 | 44.23 | 0.00 | 0.00 | 0.00 |
October | 197.92 | 96.42 | 101.51 | 230.53 | 96.67 | 0.00 | 0.00 | 0.00 |
November | 93.21 | 27.23 | 65.98 | 67.25 | 161.45 | 0.00 | 0.00 | 0.00 |
December | 82.33 | 35.54 | 46.79 | 53.88 | 218.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 188.24 | 79.38 | 108.86 | 219.98 | 114.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.33 | 27.23 | 46.79 | 53.88 | 7.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 280.37 | 129.63 | 161.55 | 417.22 | 243.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.37 | 63.24 | 33.13 | 94.27 | 99.21 | 0.00 | 0.00 | 0.00 |
February | 127.53 | 84.76 | 42.77 | 121.13 | 116.52 | 0.00 | 0.00 | 0.00 |
March | 113.00 | 62.20 | 50.79 | 112.34 | 91.65 | 0.00 | 0.00 | 0.00 |
April | 89.94 | 36.39 | 53.55 | 91.34 | 69.47 | 0.00 | 0.00 | 0.00 |
May | 77.25 | 15.82 | 61.43 | 81.54 | 44.74 | 0.00 | 0.00 | 0.00 |
June | 72.94 | 11.24 | 61.70 | 90.82 | 24.49 | 0.00 | 0.00 | 0.00 |
July | 75.90 | 12.81 | 63.09 | 107.02 | 14.00 | 0.00 | 0.00 | 0.00 |
August | 101.66 | 37.50 | 64.16 | 146.61 | 18.38 | 0.00 | 0.00 | 0.00 |
September | 107.27 | 53.86 | 53.41 | 137.16 | 35.42 | 0.00 | 0.00 | 0.00 |
October | 151.60 | 95.06 | 56.53 | 181.11 | 61.66 | 0.00 | 0.00 | 0.00 |
November | 104.97 | 62.97 | 42.00 | 104.02 | 90.43 | 0.00 | 0.00 | 0.00 |
December | 104.12 | 73.95 | 30.17 | 101.40 | 106.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 101.76 | 50.64 | 51.11 | 114.10 | 64.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.94 | 11.24 | 30.17 | 81.54 | 14.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 151.60 | 95.06 | 64.16 | 181.11 | 116.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.55 | 0.00 | 18.55 | 0.80 | 114.00 | 0.00 | 0.00 | 0.00 |
February | 25.38 | 0.00 | 25.38 | 2.15 | 115.45 | 0.00 | 0.00 | 0.00 |
March | 35.20 | 0.00 | 35.20 | 12.83 | 73.57 | 0.00 | 0.00 | 0.00 |
April | 42.37 | 0.17 | 42.19 | 29.18 | 48.15 | 0.00 | 0.00 | 0.00 |
May | 56.35 | 2.06 | 54.29 | 59.14 | 25.32 | 0.00 | 0.00 | 0.00 |
June | 59.45 | 3.16 | 56.28 | 81.87 | 10.22 | 0.00 | 0.00 | 0.00 |
July | 57.70 | 2.25 | 55.45 | 94.78 | 2.53 | 0.00 | 0.00 | 0.00 |
August | 51.02 | 0.68 | 50.35 | 84.27 | 5.55 | 0.00 | 0.00 | 0.00 |
September | 38.42 | 0.02 | 38.40 | 47.43 | 17.83 | 0.00 | 0.00 | 0.00 |
October | 33.22 | 0.00 | 33.22 | 27.88 | 41.47 | 0.00 | 0.00 | 0.00 |
November | 23.30 | 0.00 | 23.30 | 6.97 | 75.03 | 0.00 | 0.00 | 0.00 |
December | 16.18 | 0.00 | 16.18 | 0.58 | 103.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.17 | 0.70 | 37.47 | 37.57 | 52.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.18 | 0.00 | 16.18 | 0.58 | 2.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.45 | 3.16 | 56.28 | 94.78 | 115.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 90.17 | 36.03 | 54.15 | 52.58 | 240.39 | 0.00 | 0.00 | 0.00 |
February | 140.00 | 65.20 | 74.81 | 94.43 | 238.59 | 0.00 | 0.00 | 0.00 |
March | 179.79 | 76.41 | 103.38 | 156.12 | 160.31 | 0.00 | 0.00 | 0.00 |
April | 215.22 | 94.46 | 120.76 | 223.69 | 105.98 | 0.00 | 0.00 | 0.00 |
May | 259.83 | 103.55 | 156.29 | 315.27 | 58.69 | 0.00 | 0.00 | 0.00 |
June | 241.27 | 87.39 | 153.88 | 333.26 | 22.40 | 0.00 | 0.00 | 0.00 |
July | 242.01 | 87.13 | 154.88 | 367.71 | 5.59 | 0.00 | 0.00 | 0.00 |
August | 273.01 | 123.17 | 149.84 | 407.03 | 13.27 | 0.00 | 0.00 | 0.00 |
September | 204.23 | 92.00 | 112.22 | 268.52 | 39.07 | 0.00 | 0.00 | 0.00 |
October | 184.50 | 83.51 | 100.99 | 208.70 | 93.83 | 0.00 | 0.00 | 0.00 |
November | 114.27 | 43.91 | 70.36 | 90.59 | 160.28 | 0.00 | 0.00 | 0.00 |
December | 89.34 | 42.15 | 47.19 | 58.19 | 216.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 186.43 | 78.00 | 108.44 | 215.50 | 112.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 89.34 | 36.03 | 47.19 | 52.58 | 5.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 273.01 | 123.17 | 156.29 | 407.03 | 240.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.49 | 79.06 | 41.42 | 119.45 | 120.82 | 0.00 | 0.00 | 0.00 |
February | 159.45 | 105.97 | 53.48 | 160.82 | 119.86 | 0.00 | 0.00 | 0.00 |
March | 141.27 | 77.77 | 63.50 | 150.48 | 84.87 | 0.00 | 0.00 | 0.00 |
April | 112.45 | 45.49 | 66.96 | 125.98 | 59.40 | 0.00 | 0.00 | 0.00 |
May | 96.58 | 19.77 | 76.81 | 117.10 | 33.02 | 0.00 | 0.00 | 0.00 |
June | 91.20 | 14.05 | 77.14 | 131.01 | 12.42 | 0.00 | 0.00 | 0.00 |
July | 94.89 | 16.02 | 78.87 | 153.73 | 3.02 | 0.00 | 0.00 | 0.00 |
August | 127.10 | 46.88 | 80.21 | 202.03 | 7.36 | 0.00 | 0.00 | 0.00 |
September | 134.12 | 67.34 | 66.78 | 186.19 | 21.46 | 0.00 | 0.00 | 0.00 |
October | 189.53 | 118.85 | 70.68 | 240.57 | 49.66 | 0.00 | 0.00 | 0.00 |
November | 131.24 | 78.73 | 52.51 | 141.74 | 82.76 | 0.00 | 0.00 | 0.00 |
December | 130.17 | 92.45 | 37.72 | 135.02 | 107.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127.22 | 63.32 | 63.90 | 155.40 | 58.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.20 | 14.05 | 37.72 | 117.10 | 3.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 189.53 | 118.85 | 80.21 | 240.57 | 120.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.18 | 0.00 | 23.18 | 1.31 | 135.62 | 0.00 | 0.00 | 0.00 |
February | 31.72 | 0.00 | 31.72 | 2.90 | 138.74 | 0.00 | 0.00 | 0.00 |
March | 44.00 | 0.00 | 44.00 | 15.55 | 88.87 | 0.00 | 0.00 | 0.00 |
April | 52.95 | 0.22 | 52.73 | 34.52 | 58.94 | 0.00 | 0.00 | 0.00 |
May | 70.43 | 2.58 | 67.85 | 69.76 | 31.77 | 0.00 | 0.00 | 0.00 |
June | 74.30 | 3.95 | 70.35 | 97.04 | 13.75 | 0.00 | 0.00 | 0.00 |
July | 72.11 | 2.81 | 69.30 | 112.50 | 3.98 | 0.00 | 0.00 | 0.00 |
August | 63.77 | 0.85 | 62.92 | 98.49 | 8.09 | 0.00 | 0.00 | 0.00 |
September | 48.02 | 0.03 | 47.99 | 55.17 | 23.38 | 0.00 | 0.00 | 0.00 |
October | 41.52 | 0.00 | 41.52 | 32.27 | 52.01 | 0.00 | 0.00 | 0.00 |
November | 29.12 | 0.00 | 29.12 | 8.75 | 89.50 | 0.00 | 0.00 | 0.00 |
December | 20.22 | 0.00 | 20.22 | 0.86 | 122.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.70 | 0.87 | 46.83 | 44.38 | 63.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.22 | 0.00 | 20.22 | 0.86 | 3.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.30 | 3.95 | 70.35 | 112.50 | 138.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 90.17 | 36.03 | 54.15 | 54.25 | 236.58 | 0.00 | 0.00 | 0.00 |
February | 140.00 | 65.20 | 74.81 | 97.20 | 232.94 | 0.00 | 0.00 | 0.00 |
March | 179.79 | 76.41 | 103.38 | 160.04 | 157.37 | 0.00 | 0.00 | 0.00 |
April | 215.22 | 94.46 | 120.76 | 225.53 | 105.34 | 0.00 | 0.00 | 0.00 |
May | 259.83 | 103.55 | 156.29 | 313.40 | 60.60 | 0.00 | 0.00 | 0.00 |
June | 241.27 | 87.39 | 153.88 | 327.82 | 26.36 | 0.00 | 0.00 | 0.00 |
July | 242.01 | 87.13 | 154.88 | 364.53 | 7.51 | 0.00 | 0.00 | 0.00 |
August | 273.01 | 123.17 | 149.84 | 405.39 | 14.97 | 0.00 | 0.00 | 0.00 |
September | 204.23 | 92.00 | 112.22 | 267.15 | 41.99 | 0.00 | 0.00 | 0.00 |
October | 184.50 | 83.51 | 100.99 | 211.82 | 93.18 | 0.00 | 0.00 | 0.00 |
November | 114.27 | 43.91 | 70.36 | 93.66 | 156.81 | 0.00 | 0.00 | 0.00 |
December | 89.34 | 42.15 | 47.19 | 59.94 | 211.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 186.43 | 78.00 | 108.44 | 215.88 | 111.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 89.34 | 36.03 | 47.19 | 54.25 | 7.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 273.01 | 123.17 | 156.29 | 405.39 | 236.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.36 | 0.00 | 29.36 | 1.04 | 184.72 | 0.00 | 0.00 | 0.00 |
February | 40.17 | 0.00 | 40.17 | 3.07 | 187.71 | 0.00 | 0.00 | 0.00 |
March | 55.72 | 0.00 | 55.72 | 19.95 | 118.48 | 0.00 | 0.00 | 0.00 |
April | 67.06 | 0.28 | 66.78 | 46.37 | 78.59 | 0.00 | 0.00 | 0.00 |
May | 89.19 | 3.26 | 85.93 | 93.33 | 42.89 | 0.00 | 0.00 | 0.00 |
June | 94.09 | 5.00 | 89.09 | 126.02 | 20.39 | 0.00 | 0.00 | 0.00 |
July | 91.33 | 3.56 | 87.76 | 141.38 | 7.91 | 0.00 | 0.00 | 0.00 |
August | 80.76 | 1.07 | 79.69 | 123.06 | 14.06 | 0.00 | 0.00 | 0.00 |
September | 60.81 | 0.04 | 60.78 | 71.27 | 34.18 | 0.00 | 0.00 | 0.00 |
October | 52.59 | 0.00 | 52.59 | 41.46 | 73.05 | 0.00 | 0.00 | 0.00 |
November | 36.88 | 0.00 | 36.88 | 10.61 | 121.65 | 0.00 | 0.00 | 0.00 |
December | 25.61 | 0.00 | 25.61 | 0.78 | 167.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.41 | 1.11 | 59.31 | 56.89 | 87.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.61 | 0.00 | 25.61 | 0.78 | 7.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.09 | 5.00 | 89.09 | 141.38 | 187.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.82 | 0.00 | 10.82 | 0.38 | 68.10 | 0.00 | 0.00 | 0.00 |
February | 14.81 | 0.00 | 14.81 | 1.13 | 69.20 | 0.00 | 0.00 | 0.00 |
March | 20.54 | 0.00 | 20.54 | 7.35 | 43.68 | 0.00 | 0.00 | 0.00 |
April | 24.72 | 0.10 | 24.62 | 17.09 | 28.97 | 0.00 | 0.00 | 0.00 |
May | 32.88 | 1.20 | 31.68 | 34.41 | 15.81 | 0.00 | 0.00 | 0.00 |
June | 34.69 | 1.84 | 32.84 | 46.45 | 7.52 | 0.00 | 0.00 | 0.00 |
July | 33.67 | 1.31 | 32.35 | 52.12 | 2.92 | 0.00 | 0.00 | 0.00 |
August | 29.77 | 0.40 | 29.38 | 45.37 | 5.18 | 0.00 | 0.00 | 0.00 |
September | 22.42 | 0.01 | 22.41 | 26.27 | 12.60 | 0.00 | 0.00 | 0.00 |
October | 19.39 | 0.00 | 19.39 | 15.28 | 26.93 | 0.00 | 0.00 | 0.00 |
November | 13.60 | 0.00 | 13.60 | 3.91 | 44.84 | 0.00 | 0.00 | 0.00 |
December | 9.44 | 0.00 | 9.44 | 0.29 | 61.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.27 | 0.41 | 21.86 | 20.97 | 32.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.44 | 0.00 | 9.44 | 0.29 | 2.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.69 | 1.84 | 32.84 | 52.12 | 69.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 56.22 | 36.89 | 19.33 | 55.57 | 59.51 | 0.00 | 0.00 | 0.00 |
February | 74.40 | 49.45 | 24.95 | 75.35 | 58.51 | 0.00 | 0.00 | 0.00 |
March | 65.92 | 36.29 | 29.63 | 71.36 | 41.13 | 0.00 | 0.00 | 0.00 |
April | 52.47 | 21.23 | 31.24 | 60.16 | 29.02 | 0.00 | 0.00 | 0.00 |
May | 45.06 | 9.23 | 35.84 | 55.98 | 16.90 | 0.00 | 0.00 | 0.00 |
June | 42.55 | 6.56 | 36.00 | 60.94 | 7.95 | 0.00 | 0.00 | 0.00 |
July | 44.28 | 7.47 | 36.80 | 70.52 | 2.98 | 0.00 | 0.00 | 0.00 |
August | 59.30 | 21.88 | 37.43 | 93.23 | 5.33 | 0.00 | 0.00 | 0.00 |
September | 62.58 | 31.42 | 31.16 | 86.98 | 12.45 | 0.00 | 0.00 | 0.00 |
October | 88.44 | 55.46 | 32.98 | 113.18 | 25.52 | 0.00 | 0.00 | 0.00 |
November | 61.24 | 36.73 | 24.50 | 66.60 | 40.46 | 0.00 | 0.00 | 0.00 |
December | 60.74 | 43.14 | 17.60 | 63.13 | 52.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 59.36 | 29.54 | 29.82 | 72.77 | 29.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.55 | 6.56 | 17.60 | 55.57 | 2.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 88.44 | 55.46 | 37.43 | 113.18 | 59.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.59 | 100.13 | 52.46 | 150.83 | 161.51 | 0.00 | 0.00 | 0.00 |
February | 201.93 | 134.21 | 67.72 | 204.52 | 158.81 | 0.00 | 0.00 | 0.00 |
March | 178.91 | 98.49 | 80.42 | 193.69 | 111.63 | 0.00 | 0.00 | 0.00 |
April | 142.41 | 57.62 | 84.79 | 163.30 | 78.77 | 0.00 | 0.00 | 0.00 |
May | 122.31 | 25.04 | 97.27 | 151.93 | 45.87 | 0.00 | 0.00 | 0.00 |
June | 115.49 | 17.80 | 97.70 | 165.41 | 21.59 | 0.00 | 0.00 | 0.00 |
July | 120.17 | 20.28 | 99.89 | 191.42 | 8.09 | 0.00 | 0.00 | 0.00 |
August | 160.96 | 59.38 | 101.58 | 253.04 | 14.48 | 0.00 | 0.00 | 0.00 |
September | 169.85 | 85.28 | 84.57 | 236.08 | 33.80 | 0.00 | 0.00 | 0.00 |
October | 240.03 | 150.52 | 89.51 | 307.18 | 69.27 | 0.00 | 0.00 | 0.00 |
November | 166.21 | 99.70 | 66.50 | 180.77 | 109.82 | 0.00 | 0.00 | 0.00 |
December | 164.85 | 117.09 | 47.77 | 171.34 | 143.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.12 | 80.19 | 80.93 | 197.52 | 79.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.49 | 17.80 | 47.77 | 150.83 | 8.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 240.03 | 150.52 | 101.58 | 307.18 | 161.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.49 | 79.06 | 41.42 | 119.46 | 120.19 | 0.00 | 0.00 | 0.00 |
February | 159.45 | 105.97 | 53.48 | 161.06 | 119.50 | 0.00 | 0.00 | 0.00 |
March | 141.27 | 77.77 | 63.50 | 150.43 | 85.26 | 0.00 | 0.00 | 0.00 |
April | 112.45 | 45.49 | 66.96 | 125.94 | 59.48 | 0.00 | 0.00 | 0.00 |
May | 96.58 | 19.77 | 76.81 | 116.73 | 33.27 | 0.00 | 0.00 | 0.00 |
June | 91.20 | 14.05 | 77.14 | 129.87 | 12.58 | 0.00 | 0.00 | 0.00 |
July | 94.89 | 16.02 | 78.87 | 152.80 | 2.98 | 0.00 | 0.00 | 0.00 |
August | 127.10 | 46.88 | 80.21 | 201.14 | 7.27 | 0.00 | 0.00 | 0.00 |
September | 134.12 | 67.34 | 66.78 | 185.57 | 21.24 | 0.00 | 0.00 | 0.00 |
October | 189.53 | 118.85 | 70.68 | 239.80 | 49.46 | 0.00 | 0.00 | 0.00 |
November | 131.24 | 78.73 | 52.51 | 142.17 | 81.74 | 0.00 | 0.00 | 0.00 |
December | 130.17 | 92.45 | 37.72 | 135.23 | 107.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127.22 | 63.32 | 63.90 | 155.07 | 57.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.20 | 14.05 | 37.72 | 116.73 | 2.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 189.53 | 118.85 | 80.21 | 239.80 | 120.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.55 | 36.76 | 52.79 | 53.77 | 242.80 | 0.00 | 0.00 | 0.00 |
February | 131.54 | 57.73 | 73.81 | 88.11 | 245.93 | 0.00 | 0.00 | 0.00 |
March | 195.39 | 90.55 | 104.84 | 174.23 | 158.63 | 0.00 | 0.00 | 0.00 |
April | 212.21 | 90.69 | 121.52 | 220.41 | 108.31 | 0.00 | 0.00 | 0.00 |
May | 247.91 | 94.24 | 153.67 | 297.43 | 60.05 | 0.00 | 0.00 | 0.00 |
June | 270.86 | 109.31 | 161.55 | 370.90 | 22.88 | 0.00 | 0.00 | 0.00 |
July | 253.41 | 95.23 | 158.18 | 380.11 | 5.48 | 0.00 | 0.00 | 0.00 |
August | 280.37 | 129.63 | 150.74 | 415.49 | 13.46 | 0.00 | 0.00 | 0.00 |
September | 199.48 | 87.09 | 112.39 | 261.45 | 39.67 | 0.00 | 0.00 | 0.00 |
October | 197.92 | 96.42 | 101.51 | 226.15 | 94.92 | 0.00 | 0.00 | 0.00 |
November | 93.21 | 27.23 | 65.98 | 63.53 | 162.46 | 0.00 | 0.00 | 0.00 |
December | 82.33 | 35.54 | 46.79 | 50.69 | 219.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 188.24 | 79.38 | 108.86 | 217.78 | 113.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.33 | 27.23 | 46.79 | 50.69 | 5.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 280.37 | 129.63 | 161.55 | 415.49 | 245.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.18 | 0.00 | 23.18 | 1.57 | 134.78 | 0.00 | 0.00 | 0.00 |
February | 31.72 | 0.00 | 31.72 | 3.24 | 138.17 | 0.00 | 0.00 | 0.00 |
March | 44.00 | 0.00 | 44.00 | 16.32 | 89.15 | 0.00 | 0.00 | 0.00 |
April | 52.95 | 0.22 | 52.73 | 35.15 | 59.13 | 0.00 | 0.00 | 0.00 |
May | 70.43 | 2.58 | 67.85 | 69.32 | 32.64 | 0.00 | 0.00 | 0.00 |
June | 74.30 | 3.95 | 70.35 | 95.58 | 15.10 | 0.00 | 0.00 | 0.00 |
July | 72.11 | 2.81 | 69.30 | 112.23 | 4.23 | 0.00 | 0.00 | 0.00 |
August | 63.77 | 0.85 | 62.92 | 99.02 | 8.26 | 0.00 | 0.00 | 0.00 |
September | 48.02 | 0.03 | 47.99 | 55.65 | 24.01 | 0.00 | 0.00 | 0.00 |
October | 41.52 | 0.00 | 41.52 | 33.15 | 52.54 | 0.00 | 0.00 | 0.00 |
November | 29.12 | 0.00 | 29.12 | 9.53 | 88.04 | 0.00 | 0.00 | 0.00 |
December | 20.22 | 0.00 | 20.22 | 1.11 | 121.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.70 | 0.87 | 46.83 | 44.61 | 63.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.22 | 0.00 | 20.22 | 1.11 | 4.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.30 | 3.95 | 70.35 | 112.23 | 138.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.55 | 36.76 | 52.79 | 56.65 | 240.33 | 0.00 | 0.00 | 0.00 |
February | 131.54 | 57.73 | 73.81 | 92.45 | 242.18 | 0.00 | 0.00 | 0.00 |
March | 195.39 | 90.55 | 104.84 | 178.97 | 156.32 | 0.00 | 0.00 | 0.00 |
April | 212.21 | 90.69 | 121.52 | 222.17 | 108.14 | 0.00 | 0.00 | 0.00 |
May | 247.91 | 94.24 | 153.67 | 294.35 | 62.95 | 0.00 | 0.00 | 0.00 |
June | 270.86 | 109.31 | 161.55 | 363.71 | 28.79 | 0.00 | 0.00 | 0.00 |
July | 253.41 | 95.23 | 158.18 | 377.60 | 7.83 | 0.00 | 0.00 | 0.00 |
August | 280.37 | 129.63 | 150.74 | 415.34 | 15.59 | 0.00 | 0.00 | 0.00 |
September | 199.48 | 87.09 | 112.39 | 260.31 | 43.83 | 0.00 | 0.00 | 0.00 |
October | 197.92 | 96.42 | 101.51 | 229.53 | 95.25 | 0.00 | 0.00 | 0.00 |
November | 93.21 | 27.23 | 65.98 | 67.54 | 159.46 | 0.00 | 0.00 | 0.00 |
December | 82.33 | 35.54 | 46.79 | 54.19 | 216.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 188.24 | 79.38 | 108.86 | 218.64 | 114.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.33 | 27.23 | 46.79 | 54.19 | 7.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 280.37 | 129.63 | 161.55 | 415.34 | 242.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 176.70 | 115.95 | 60.75 | 169.64 | 183.32 | 0.00 | 0.00 | 0.00 |
February | 233.85 | 155.42 | 78.43 | 229.12 | 182.45 | 0.00 | 0.00 | 0.00 |
March | 207.19 | 114.06 | 93.13 | 216.75 | 128.72 | 0.00 | 0.00 | 0.00 |
April | 164.92 | 66.72 | 98.20 | 183.00 | 88.41 | 0.00 | 0.00 | 0.00 |
May | 141.64 | 29.00 | 112.65 | 172.27 | 48.04 | 0.00 | 0.00 | 0.00 |
June | 133.75 | 20.61 | 113.14 | 193.75 | 16.98 | 0.00 | 0.00 | 0.00 |
July | 139.17 | 23.49 | 115.68 | 227.77 | 3.61 | 0.00 | 0.00 | 0.00 |
August | 186.40 | 68.76 | 117.64 | 297.99 | 9.78 | 0.00 | 0.00 | 0.00 |
September | 196.70 | 98.76 | 97.94 | 272.06 | 30.88 | 0.00 | 0.00 | 0.00 |
October | 277.97 | 174.31 | 103.66 | 348.79 | 74.29 | 0.00 | 0.00 | 0.00 |
November | 192.48 | 115.46 | 77.02 | 202.94 | 126.24 | 0.00 | 0.00 | 0.00 |
December | 190.91 | 135.59 | 55.32 | 192.36 | 164.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 186.58 | 92.86 | 93.72 | 225.65 | 87.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 133.75 | 20.61 | 55.32 | 169.64 | 3.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 277.97 | 174.31 | 117.64 | 348.79 | 183.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 162.25 | 0.00 | 162.25 | 2.36 | 1128.75 | 0.00 | 0.00 | 0.00 |
February | 222.04 | 0.00 | 222.04 | 10.67 | 1140.28 | 0.00 | 0.00 | 0.00 |
March | 307.98 | 0.01 | 307.98 | 85.61 | 756.33 | 0.00 | 0.00 | 0.00 |
April | 370.63 | 1.53 | 369.11 | 215.87 | 510.94 | 0.00 | 0.00 | 0.00 |
May | 492.96 | 18.04 | 474.92 | 460.40 | 277.55 | 0.00 | 0.00 | 0.00 |
June | 520.06 | 27.66 | 492.40 | 662.26 | 129.41 | 0.00 | 0.00 | 0.00 |
July | 504.77 | 19.70 | 485.07 | 754.97 | 53.58 | 0.00 | 0.00 | 0.00 |
August | 446.39 | 5.93 | 440.46 | 662.93 | 83.42 | 0.00 | 0.00 | 0.00 |
September | 336.12 | 0.20 | 335.92 | 371.49 | 213.42 | 0.00 | 0.00 | 0.00 |
October | 290.65 | 0.00 | 290.65 | 207.67 | 444.47 | 0.00 | 0.00 | 0.00 |
November | 203.86 | 0.00 | 203.86 | 43.16 | 773.90 | 0.00 | 0.00 | 0.00 |
December | 141.53 | 0.00 | 141.53 | 1.99 | 1039.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 333.92 | 6.12 | 327.79 | 291.88 | 542.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.53 | 0.00 | 141.53 | 1.99 | 53.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 520.06 | 27.66 | 492.40 | 754.97 | 1140.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 162.25 | 0.00 | 162.25 | 1.52 | 1163.36 | 0.00 | 0.00 | 0.00 |
February | 222.04 | 0.00 | 222.04 | 8.78 | 1173.46 | 0.00 | 0.00 | 0.00 |
March | 307.98 | 0.01 | 307.98 | 78.45 | 780.39 | 0.00 | 0.00 | 0.00 |
April | 370.63 | 1.53 | 369.11 | 205.26 | 528.06 | 0.00 | 0.00 | 0.00 |
May | 492.96 | 18.04 | 474.92 | 447.67 | 286.53 | 0.00 | 0.00 | 0.00 |
June | 520.06 | 27.66 | 492.40 | 652.69 | 135.10 | 0.00 | 0.00 | 0.00 |
July | 504.77 | 19.70 | 485.07 | 746.42 | 57.70 | 0.00 | 0.00 | 0.00 |
August | 446.39 | 5.93 | 440.46 | 654.29 | 87.71 | 0.00 | 0.00 | 0.00 |
September | 336.12 | 0.20 | 335.92 | 362.84 | 222.17 | 0.00 | 0.00 | 0.00 |
October | 290.65 | 0.00 | 290.65 | 198.85 | 458.51 | 0.00 | 0.00 | 0.00 |
November | 203.86 | 0.00 | 203.86 | 38.64 | 800.71 | 0.00 | 0.00 | 0.00 |
December | 141.53 | 0.00 | 141.53 | 1.45 | 1072.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 333.92 | 6.12 | 327.79 | 284.98 | 560.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.53 | 0.00 | 141.53 | 1.45 | 57.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 520.06 | 27.66 | 492.40 | 746.42 | 1173.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.18 | 0.00 | 23.18 | 2.21 | 140.24 | 0.00 | 0.00 | 0.00 |
February | 31.72 | 0.00 | 31.72 | 4.06 | 142.67 | 0.00 | 0.00 | 0.00 |
March | 44.00 | 0.00 | 44.00 | 20.08 | 92.22 | 0.00 | 0.00 | 0.00 |
April | 52.95 | 0.22 | 52.73 | 46.03 | 62.60 | 0.00 | 0.00 | 0.00 |
May | 70.43 | 2.58 | 67.85 | 90.10 | 35.47 | 0.00 | 0.00 | 0.00 |
June | 74.30 | 3.95 | 70.35 | 123.34 | 16.57 | 0.00 | 0.00 | 0.00 |
July | 72.11 | 2.81 | 69.30 | 139.52 | 7.13 | 0.00 | 0.00 | 0.00 |
August | 63.77 | 0.85 | 62.92 | 124.36 | 10.56 | 0.00 | 0.00 | 0.00 |
September | 48.02 | 0.03 | 47.99 | 76.57 | 24.34 | 0.00 | 0.00 | 0.00 |
October | 41.52 | 0.00 | 41.52 | 44.85 | 51.68 | 0.00 | 0.00 | 0.00 |
November | 29.12 | 0.00 | 29.12 | 12.23 | 92.71 | 0.00 | 0.00 | 0.00 |
December | 20.22 | 0.00 | 20.22 | 1.64 | 126.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.70 | 0.87 | 46.83 | 57.44 | 66.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.22 | 0.00 | 20.22 | 1.64 | 7.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.30 | 3.95 | 70.35 | 139.52 | 142.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 180.34 | 72.05 | 108.29 | 115.99 | 492.01 | 0.00 | 0.00 | 0.00 |
February | 279.99 | 130.38 | 149.60 | 204.89 | 481.25 | 0.00 | 0.00 | 0.00 |
March | 359.55 | 152.80 | 206.74 | 342.22 | 330.92 | 0.00 | 0.00 | 0.00 |
April | 430.41 | 188.91 | 241.50 | 497.20 | 226.51 | 0.00 | 0.00 | 0.00 |
May | 519.63 | 207.08 | 312.55 | 700.00 | 133.25 | 0.00 | 0.00 | 0.00 |
June | 482.51 | 174.77 | 307.74 | 752.14 | 62.22 | 0.00 | 0.00 | 0.00 |
July | 483.98 | 174.24 | 309.74 | 829.07 | 26.88 | 0.00 | 0.00 | 0.00 |
August | 545.99 | 246.33 | 299.66 | 907.33 | 39.55 | 0.00 | 0.00 | 0.00 |
September | 408.42 | 183.99 | 224.43 | 616.21 | 89.45 | 0.00 | 0.00 | 0.00 |
October | 368.98 | 167.02 | 201.96 | 476.54 | 187.88 | 0.00 | 0.00 | 0.00 |
November | 228.53 | 87.82 | 140.71 | 206.69 | 325.82 | 0.00 | 0.00 | 0.00 |
December | 178.67 | 84.30 | 94.36 | 128.63 | 438.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 372.84 | 155.98 | 216.86 | 483.28 | 234.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 178.67 | 72.05 | 94.36 | 115.99 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 545.99 | 246.33 | 312.55 | 907.33 | 492.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.49 | 79.06 | 41.42 | 123.97 | 124.55 | 0.00 | 0.00 | 0.00 |
February | 159.45 | 105.97 | 53.48 | 167.52 | 122.20 | 0.00 | 0.00 | 0.00 |
March | 141.27 | 77.77 | 63.50 | 160.10 | 87.94 | 0.00 | 0.00 | 0.00 |
April | 112.45 | 45.49 | 66.96 | 139.02 | 62.82 | 0.00 | 0.00 | 0.00 |
May | 96.58 | 19.77 | 76.81 | 135.77 | 36.96 | 0.00 | 0.00 | 0.00 |
June | 91.20 | 14.05 | 77.14 | 153.55 | 17.24 | 0.00 | 0.00 | 0.00 |
July | 94.89 | 16.02 | 78.87 | 178.51 | 7.27 | 0.00 | 0.00 | 0.00 |
August | 127.10 | 46.88 | 80.21 | 227.08 | 10.65 | 0.00 | 0.00 | 0.00 |
September | 134.12 | 67.34 | 66.78 | 207.49 | 24.14 | 0.00 | 0.00 | 0.00 |
October | 189.53 | 118.85 | 70.68 | 257.44 | 50.42 | 0.00 | 0.00 | 0.00 |
November | 131.24 | 78.73 | 52.51 | 150.00 | 84.95 | 0.00 | 0.00 | 0.00 |
December | 130.17 | 92.45 | 37.72 | 140.48 | 110.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127.22 | 63.32 | 63.90 | 170.18 | 61.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.20 | 14.05 | 37.72 | 123.97 | 7.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 189.53 | 118.85 | 80.21 | 257.44 | 124.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.36 | 0.00 | 29.36 | 0.77 | 188.33 | 0.00 | 0.00 | 0.00 |
February | 40.17 | 0.00 | 40.17 | 2.57 | 191.53 | 0.00 | 0.00 | 0.00 |
March | 55.72 | 0.00 | 55.72 | 17.99 | 121.38 | 0.00 | 0.00 | 0.00 |
April | 67.06 | 0.28 | 66.78 | 43.52 | 80.34 | 0.00 | 0.00 | 0.00 |
May | 89.19 | 3.26 | 85.93 | 89.23 | 44.20 | 0.00 | 0.00 | 0.00 |
June | 94.09 | 5.00 | 89.09 | 121.70 | 21.60 | 0.00 | 0.00 | 0.00 |
July | 91.33 | 3.56 | 87.76 | 136.18 | 9.44 | 0.00 | 0.00 | 0.00 |
August | 80.76 | 1.07 | 79.69 | 118.78 | 14.99 | 0.00 | 0.00 | 0.00 |
September | 60.81 | 0.04 | 60.78 | 68.56 | 34.94 | 0.00 | 0.00 | 0.00 |
October | 52.59 | 0.00 | 52.59 | 39.70 | 72.58 | 0.00 | 0.00 | 0.00 |
November | 36.88 | 0.00 | 36.88 | 9.64 | 123.97 | 0.00 | 0.00 | 0.00 |
December | 25.61 | 0.00 | 25.61 | 0.59 | 171.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.41 | 1.11 | 59.31 | 54.45 | 88.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.61 | 0.00 | 25.61 | 0.59 | 9.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.09 | 5.00 | 89.09 | 136.18 | 191.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.26 | 0.00 | 26.26 | 0.69 | 168.49 | 0.00 | 0.00 | 0.00 |
February | 35.94 | 0.00 | 35.94 | 2.30 | 171.36 | 0.00 | 0.00 | 0.00 |
March | 49.86 | 0.00 | 49.85 | 16.10 | 108.60 | 0.00 | 0.00 | 0.00 |
April | 60.00 | 0.25 | 59.75 | 38.94 | 71.88 | 0.00 | 0.00 | 0.00 |
May | 79.80 | 2.92 | 76.88 | 79.84 | 39.55 | 0.00 | 0.00 | 0.00 |
June | 84.18 | 4.48 | 79.71 | 108.88 | 19.32 | 0.00 | 0.00 | 0.00 |
July | 81.71 | 3.19 | 78.52 | 121.84 | 8.44 | 0.00 | 0.00 | 0.00 |
August | 72.26 | 0.96 | 71.30 | 106.28 | 13.41 | 0.00 | 0.00 | 0.00 |
September | 54.41 | 0.03 | 54.38 | 61.34 | 31.26 | 0.00 | 0.00 | 0.00 |
October | 47.05 | 0.00 | 47.05 | 35.52 | 64.94 | 0.00 | 0.00 | 0.00 |
November | 33.00 | 0.00 | 33.00 | 8.62 | 110.91 | 0.00 | 0.00 | 0.00 |
December | 22.91 | 0.00 | 22.91 | 0.53 | 153.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.05 | 0.99 | 53.06 | 48.72 | 79.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.91 | 0.00 | 22.91 | 0.53 | 8.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.18 | 4.48 | 79.71 | 121.84 | 171.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 449.81 | 295.17 | 154.64 | 438.17 | 484.07 | 0.00 | 0.00 | 0.00 |
February | 595.27 | 395.63 | 199.64 | 594.39 | 475.21 | 0.00 | 0.00 | 0.00 |
March | 527.41 | 290.33 | 237.08 | 560.68 | 336.86 | 0.00 | 0.00 | 0.00 |
April | 419.81 | 169.84 | 249.96 | 470.05 | 238.06 | 0.00 | 0.00 | 0.00 |
May | 360.56 | 73.82 | 286.74 | 434.67 | 139.99 | 0.00 | 0.00 | 0.00 |
June | 340.46 | 52.46 | 288.00 | 473.60 | 67.74 | 0.00 | 0.00 | 0.00 |
July | 354.25 | 59.79 | 294.46 | 547.54 | 28.48 | 0.00 | 0.00 | 0.00 |
August | 474.49 | 175.03 | 299.45 | 730.88 | 45.57 | 0.00 | 0.00 | 0.00 |
September | 500.71 | 251.40 | 249.31 | 685.21 | 102.10 | 0.00 | 0.00 | 0.00 |
October | 707.59 | 443.72 | 263.87 | 896.10 | 203.15 | 0.00 | 0.00 | 0.00 |
November | 489.96 | 293.91 | 196.05 | 525.51 | 329.12 | 0.00 | 0.00 | 0.00 |
December | 485.97 | 345.16 | 140.81 | 498.28 | 431.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 474.95 | 236.38 | 238.57 | 571.42 | 238.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 340.46 | 52.46 | 140.81 | 434.67 | 28.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 707.59 | 443.72 | 299.45 | 896.10 | 484.07 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163216E+10 | 0.107105E+10 | 0.561115E+09 | 0.161587E+10 | 0.161495E+10 |
February | 0.195097E+10 | 0.129667E+10 | 0.654301E+09 | 0.196978E+10 | 0.144532E+10 |
March | 0.191376E+10 | 0.105350E+10 | 0.860258E+09 | 0.205417E+10 | 0.113515E+10 |
April | 0.147416E+10 | 0.596411E+09 | 0.877753E+09 | 0.167258E+10 | 0.772889E+09 |
May | 0.130833E+10 | 0.267862E+09 | 0.104047E+10 | 0.161725E+10 | 0.455313E+09 |
June | 0.119554E+10 | 0.184207E+09 | 0.101133E+10 | 0.169721E+10 | 0.207490E+09 |
July | 0.128543E+10 | 0.216954E+09 | 0.106847E+10 | 0.200493E+10 | 88295919.91 |
August | 0.172171E+10 | 0.635122E+09 | 0.108658E+10 | 0.264424E+10 | 0.161856E+09 |
September | 0.175826E+10 | 0.882798E+09 | 0.875461E+09 | 0.240902E+10 | 0.336096E+09 |
October | 0.256754E+10 | 0.161007E+10 | 0.957474E+09 | 0.323551E+10 | 0.721673E+09 |
November | 0.172050E+10 | 0.103208E+10 | 0.688421E+09 | 0.185468E+10 | 0.108288E+10 |
December | 0.176337E+10 | 0.125244E+10 | 0.510933E+09 | 0.182048E+10 | 0.145214E+10 |
Annual Sum or Average | 0.202917E+11 | 0.100992E+11 | 0.101926E+11 | 0.245957E+11 | 0.947405E+10 |
Minimum of Months | 0.119554E+10 | 0.184207E+09 | 0.510933E+09 | 0.161587E+10 | 88295919.91 |
Maximum of Months | 0.256754E+10 | 0.161007E+10 | 0.108658E+10 | 0.323551E+10 | 0.161495E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.459606E+10 | 0.301600E+10 | 0.158006E+10 | 0.449451E+10 | 0.469049E+10 |
February | 0.549380E+10 | 0.365134E+10 | 0.184247E+10 | 0.547724E+10 | 0.420969E+10 |
March | 0.538903E+10 | 0.296660E+10 | 0.242243E+10 | 0.570900E+10 | 0.339143E+10 |
April | 0.415115E+10 | 0.167946E+10 | 0.247169E+10 | 0.463119E+10 | 0.235383E+10 |
May | 0.368418E+10 | 0.754282E+09 | 0.292990E+10 | 0.444525E+10 | 0.144418E+10 |
June | 0.336655E+10 | 0.518716E+09 | 0.284784E+10 | 0.470617E+10 | 0.680623E+09 |
July | 0.361968E+10 | 0.610929E+09 | 0.300875E+10 | 0.559003E+10 | 0.306697E+09 |
August | 0.484821E+10 | 0.178846E+10 | 0.305975E+10 | 0.739830E+10 | 0.506569E+09 |
September | 0.495114E+10 | 0.248590E+10 | 0.246524E+10 | 0.671227E+10 | 0.107772E+10 |
October | 0.723002E+10 | 0.453384E+10 | 0.269618E+10 | 0.902304E+10 | 0.221852E+10 |
November | 0.484482E+10 | 0.290627E+10 | 0.193855E+10 | 0.514090E+10 | 0.323582E+10 |
December | 0.496554E+10 | 0.352678E+10 | 0.143875E+10 | 0.506294E+10 | 0.426176E+10 |
Annual Sum or Average | 0.571402E+11 | 0.284386E+11 | 0.287016E+11 | 0.683909E+11 | 0.283773E+11 |
Minimum of Months | 0.336655E+10 | 0.518716E+09 | 0.143875E+10 | 0.444525E+10 | 0.306697E+09 |
Maximum of Months | 0.723002E+10 | 0.453384E+10 | 0.305975E+10 | 0.902304E+10 | 0.469049E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.597055E+10 | 0.391796E+10 | 0.205259E+10 | 0.592398E+10 | 0.639987E+10 |
February | 0.713676E+10 | 0.474329E+10 | 0.239347E+10 | 0.724059E+10 | 0.569852E+10 |
March | 0.700065E+10 | 0.385378E+10 | 0.314688E+10 | 0.755195E+10 | 0.460992E+10 |
April | 0.539258E+10 | 0.218171E+10 | 0.321087E+10 | 0.611816E+10 | 0.322898E+10 |
May | 0.478596E+10 | 0.979855E+09 | 0.380610E+10 | 0.585819E+10 | 0.199529E+10 |
June | 0.437334E+10 | 0.673841E+09 | 0.369950E+10 | 0.621505E+10 | 0.931974E+09 |
July | 0.470217E+10 | 0.793632E+09 | 0.390854E+10 | 0.741204E+10 | 0.415027E+09 |
August | 0.629810E+10 | 0.232331E+10 | 0.397479E+10 | 0.982874E+10 | 0.660101E+09 |
September | 0.643181E+10 | 0.322933E+10 | 0.320249E+10 | 0.887815E+10 | 0.144917E+10 |
October | 0.939221E+10 | 0.588972E+10 | 0.350250E+10 | 0.119441E+11 | 0.295507E+10 |
November | 0.629370E+10 | 0.377541E+10 | 0.251828E+10 | 0.677233E+10 | 0.443023E+10 |
December | 0.645052E+10 | 0.458149E+10 | 0.186902E+10 | 0.667277E+10 | 0.582107E+10 |
Annual Sum or Average | 0.742284E+11 | 0.369433E+11 | 0.372850E+11 | 0.904160E+11 | 0.385952E+11 |
Minimum of Months | 0.437334E+10 | 0.673841E+09 | 0.186902E+10 | 0.585819E+10 | 0.415027E+09 |
Maximum of Months | 0.939221E+10 | 0.588972E+10 | 0.397479E+10 | 0.119441E+11 | 0.639987E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.322707E+09 | 0.211765E+09 | 0.110943E+09 | 0.320735E+09 | 0.324045E+09 |
February | 0.385741E+09 | 0.256374E+09 | 0.129367E+09 | 0.390851E+09 | 0.290621E+09 |
March | 0.378385E+09 | 0.208296E+09 | 0.170089E+09 | 0.405343E+09 | 0.229345E+09 |
April | 0.291469E+09 | 0.117921E+09 | 0.173548E+09 | 0.329061E+09 | 0.155066E+09 |
May | 0.258682E+09 | 52960934.60 | 0.205721E+09 | 0.316060E+09 | 89632708.99 |
June | 0.236380E+09 | 36420939.70 | 0.199959E+09 | 0.339573E+09 | 33378112.16 |
July | 0.254153E+09 | 42895608.52 | 0.211258E+09 | 0.411944E+09 | 8582286.61 |
August | 0.340413E+09 | 0.125575E+09 | 0.214838E+09 | 0.541743E+09 | 20464750.29 |
September | 0.347639E+09 | 0.174544E+09 | 0.173095E+09 | 0.483873E+09 | 56386764.87 |
October | 0.507648E+09 | 0.318338E+09 | 0.189310E+09 | 0.645670E+09 | 0.134417E+09 |
November | 0.340174E+09 | 0.204060E+09 | 0.136113E+09 | 0.369361E+09 | 0.214231E+09 |
December | 0.348649E+09 | 0.247629E+09 | 0.101021E+09 | 0.362752E+09 | 0.289126E+09 |
Annual Sum or Average | 0.401204E+10 | 0.199678E+10 | 0.201526E+10 | 0.491697E+10 | 0.184530E+10 |
Minimum of Months | 0.236380E+09 | 36420939.70 | 0.101021E+09 | 0.316060E+09 | 8582286.61 |
Maximum of Months | 0.507648E+09 | 0.318338E+09 | 0.214838E+09 | 0.645670E+09 | 0.324045E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239844E+09 | 98462657.35 | 0.141382E+09 | 0.144077E+09 | 0.654367E+09 |
February | 0.318223E+09 | 0.139658E+09 | 0.178565E+09 | 0.214405E+09 | 0.597589E+09 |
March | 0.523325E+09 | 0.242520E+09 | 0.280804E+09 | 0.470195E+09 | 0.427382E+09 |
April | 0.550044E+09 | 0.235058E+09 | 0.314986E+09 | 0.575882E+09 | 0.282984E+09 |
May | 0.663989E+09 | 0.252408E+09 | 0.411582E+09 | 0.803568E+09 | 0.162241E+09 |
June | 0.702057E+09 | 0.283331E+09 | 0.418726E+09 | 0.968450E+09 | 60898204.53 |
July | 0.678728E+09 | 0.255057E+09 | 0.423671E+09 | 0.102412E+10 | 15818321.00 |
August | 0.750935E+09 | 0.347199E+09 | 0.403736E+09 | 0.111820E+10 | 37922988.37 |
September | 0.517041E+09 | 0.225725E+09 | 0.291316E+09 | 0.681694E+09 | 0.105522E+09 |
October | 0.530121E+09 | 0.258241E+09 | 0.271880E+09 | 0.609550E+09 | 0.258269E+09 |
November | 0.241596E+09 | 70580626.93 | 0.171015E+09 | 0.164835E+09 | 0.425730E+09 |
December | 0.220511E+09 | 95188244.85 | 0.125323E+09 | 0.135623E+09 | 0.592994E+09 |
Annual Sum or Average | 0.593641E+10 | 0.250343E+10 | 0.343299E+10 | 0.691060E+10 | 0.362172E+10 |
Minimum of Months | 0.220511E+09 | 70580626.93 | 0.125323E+09 | 0.135623E+09 | 15818321.00 |
Maximum of Months | 0.750935E+09 | 0.347199E+09 | 0.423671E+09 | 0.111820E+10 | 0.654367E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62085473.63 | 0.00 | 62085473.63 | 3929820.02 | 0.363400E+09 |
February | 76739382.29 | 0.00 | 76739382.29 | 7578722.51 | 0.335664E+09 |
March | 0.117848E+09 | 2454.62 | 0.117846E+09 | 43601677.06 | 0.240056E+09 |
April | 0.137245E+09 | 565514.21 | 0.136680E+09 | 91860771.19 | 0.154022E+09 |
May | 0.188627E+09 | 6903211.21 | 0.181724E+09 | 0.188860E+09 | 86890530.28 |
June | 0.192578E+09 | 10242901.02 | 0.182335E+09 | 0.250802E+09 | 38168815.51 |
July | 0.193148E+09 | 7538040.63 | 0.185610E+09 | 0.302608E+09 | 11384148.41 |
August | 0.170807E+09 | 2269513.75 | 0.168538E+09 | 0.266176E+09 | 22688535.04 |
September | 0.124465E+09 | 72357.39 | 0.124392E+09 | 0.145156E+09 | 62508890.35 |
October | 0.111214E+09 | 0.00 | 0.111214E+09 | 88524769.55 | 0.142571E+09 |
November | 75489568.31 | 0.00 | 75489568.31 | 24089198.21 | 0.231427E+09 |
December | 54155055.53 | 0.00 | 54155055.53 | 2687573.28 | 0.328014E+09 |
Annual Sum or Average | 0.150440E+10 | 27593992.83 | 0.147681E+10 | 0.141587E+10 | 0.201679E+10 |
Minimum of Months | 54155055.53 | 0.00 | 54155055.53 | 2687573.28 | 11384148.41 |
Maximum of Months | 0.193148E+09 | 10242901.02 | 0.185610E+09 | 0.302608E+09 | 0.363400E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239844E+09 | 98462657.35 | 0.141382E+09 | 0.151531E+09 | 0.647433E+09 |
February | 0.318223E+09 | 0.139658E+09 | 0.178565E+09 | 0.224405E+09 | 0.588152E+09 |
March | 0.523325E+09 | 0.242520E+09 | 0.280804E+09 | 0.481841E+09 | 0.421474E+09 |
April | 0.550044E+09 | 0.235058E+09 | 0.314986E+09 | 0.580439E+09 | 0.282100E+09 |
May | 0.663989E+09 | 0.252408E+09 | 0.411582E+09 | 0.796881E+09 | 0.168062E+09 |
June | 0.702057E+09 | 0.283331E+09 | 0.418726E+09 | 0.951833E+09 | 72985558.81 |
July | 0.678728E+09 | 0.255057E+09 | 0.423671E+09 | 0.101772E+10 | 21252315.00 |
August | 0.750935E+09 | 0.347199E+09 | 0.403736E+09 | 0.111747E+10 | 43022023.65 |
September | 0.517041E+09 | 0.225725E+09 | 0.291316E+09 | 0.679017E+09 | 0.114650E+09 |
October | 0.530121E+09 | 0.258241E+09 | 0.271880E+09 | 0.617455E+09 | 0.258928E+09 |
November | 0.241596E+09 | 70580626.93 | 0.171015E+09 | 0.174304E+09 | 0.418489E+09 |
December | 0.220511E+09 | 95188244.85 | 0.125323E+09 | 0.144316E+09 | 0.584363E+09 |
Annual Sum or Average | 0.593641E+10 | 0.250343E+10 | 0.343299E+10 | 0.693721E+10 | 0.362091E+10 |
Minimum of Months | 0.220511E+09 | 70580626.93 | 0.125323E+09 | 0.144316E+09 | 21252315.00 |
Maximum of Months | 0.750935E+09 | 0.347199E+09 | 0.423671E+09 | 0.111747E+10 | 0.647433E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258114E+09 | 0.169378E+09 | 88736490.59 | 0.252492E+09 | 0.265725E+09 |
February | 0.308532E+09 | 0.205058E+09 | 0.103473E+09 | 0.293033E+09 | 0.281893E+09 |
March | 0.302648E+09 | 0.166604E+09 | 0.136044E+09 | 0.300890E+09 | 0.245480E+09 |
April | 0.233129E+09 | 94317873.29 | 0.138811E+09 | 0.236750E+09 | 0.180058E+09 |
May | 0.206904E+09 | 42360323.35 | 0.164544E+09 | 0.218409E+09 | 0.119838E+09 |
June | 0.189067E+09 | 29130958.40 | 0.159936E+09 | 0.235408E+09 | 63488679.14 |
July | 0.203282E+09 | 34309663.55 | 0.168973E+09 | 0.286649E+09 | 37492584.72 |
August | 0.272276E+09 | 0.100440E+09 | 0.171837E+09 | 0.392672E+09 | 49239807.84 |
September | 0.278056E+09 | 0.139608E+09 | 0.138449E+09 | 0.355529E+09 | 91810725.07 |
October | 0.406038E+09 | 0.254620E+09 | 0.151418E+09 | 0.485075E+09 | 0.165147E+09 |
November | 0.272085E+09 | 0.163216E+09 | 0.108869E+09 | 0.269631E+09 | 0.234399E+09 |
December | 0.278864E+09 | 0.198063E+09 | 80800618.01 | 0.271589E+09 | 0.284383E+09 |
Annual Sum or Average | 0.320900E+10 | 0.159710E+10 | 0.161189E+10 | 0.359813E+10 | 0.201895E+10 |
Minimum of Months | 0.189067E+09 | 29130958.40 | 80800618.01 | 0.218409E+09 | 37492584.72 |
Maximum of Months | 0.406038E+09 | 0.254620E+09 | 0.171837E+09 | 0.485075E+09 | 0.284383E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 49674962.73 | 0.00 | 49674962.73 | 2153401.85 | 0.305343E+09 |
February | 61399643.62 | 0.00 | 61399643.62 | 5205628.84 | 0.279298E+09 |
March | 94290864.36 | 1963.96 | 94288900.41 | 34372280.97 | 0.197052E+09 |
April | 0.109811E+09 | 452471.34 | 0.109358E+09 | 75636488.89 | 0.124808E+09 |
May | 0.150921E+09 | 5523301.01 | 0.145398E+09 | 0.158410E+09 | 67804846.40 |
June | 0.154082E+09 | 8195407.02 | 0.145887E+09 | 0.212207E+09 | 26487307.31 |
July | 0.154539E+09 | 6031231.87 | 0.148507E+09 | 0.253871E+09 | 6775660.87 |
August | 0.136664E+09 | 1815851.67 | 0.134848E+09 | 0.225718E+09 | 14858196.39 |
September | 99584946.32 | 57893.59 | 99527052.73 | 0.122947E+09 | 46202933.90 |
October | 88983113.67 | 0.00 | 88983113.67 | 74683918.48 | 0.111078E+09 |
November | 60399659.90 | 0.00 | 60399659.90 | 18065266.28 | 0.194469E+09 |
December | 43329787.27 | 0.00 | 43329787.27 | 1558693.53 | 0.276560E+09 |
Annual Sum or Average | 0.120368E+10 | 22078120.45 | 0.118160E+10 | 0.118483E+10 | 0.165074E+10 |
Minimum of Months | 43329787.27 | 0.00 | 43329787.27 | 1558693.53 | 6775660.87 |
Maximum of Months | 0.154539E+09 | 8195407.02 | 0.148507E+09 | 0.253871E+09 | 0.305343E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.241522E+09 | 96495417.54 | 0.145026E+09 | 0.140828E+09 | 0.643865E+09 |
February | 0.338694E+09 | 0.157722E+09 | 0.180972E+09 | 0.228448E+09 | 0.577204E+09 |
March | 0.481538E+09 | 0.204650E+09 | 0.276888E+09 | 0.418150E+09 | 0.429387E+09 |
April | 0.557847E+09 | 0.244845E+09 | 0.313002E+09 | 0.579804E+09 | 0.274710E+09 |
May | 0.695935E+09 | 0.277340E+09 | 0.418595E+09 | 0.844425E+09 | 0.157205E+09 |
June | 0.625383E+09 | 0.226521E+09 | 0.398862E+09 | 0.863801E+09 | 58058836.11 |
July | 0.648197E+09 | 0.233361E+09 | 0.414837E+09 | 0.984867E+09 | 14963564.23 |
August | 0.731240E+09 | 0.329905E+09 | 0.401335E+09 | 0.109018E+10 | 35548042.60 |
September | 0.529355E+09 | 0.238470E+09 | 0.290885E+09 | 0.695999E+09 | 0.101262E+09 |
October | 0.494167E+09 | 0.223686E+09 | 0.270480E+09 | 0.558990E+09 | 0.251319E+09 |
November | 0.296195E+09 | 0.113821E+09 | 0.182374E+09 | 0.234801E+09 | 0.415440E+09 |
December | 0.239288E+09 | 0.112907E+09 | 0.126381E+09 | 0.155844E+09 | 0.579815E+09 |
Annual Sum or Average | 0.587936E+10 | 0.245972E+10 | 0.341964E+10 | 0.679614E+10 | 0.353878E+10 |
Minimum of Months | 0.239288E+09 | 96495417.54 | 0.126381E+09 | 0.140828E+09 | 14963564.23 |
Maximum of Months | 0.731240E+09 | 0.329905E+09 | 0.418595E+09 | 0.109018E+10 | 0.643865E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.322707E+09 | 0.211765E+09 | 0.110943E+09 | 0.319927E+09 | 0.323591E+09 |
February | 0.385741E+09 | 0.256374E+09 | 0.129367E+09 | 0.389050E+09 | 0.289959E+09 |
March | 0.378385E+09 | 0.208296E+09 | 0.170089E+09 | 0.403051E+09 | 0.227319E+09 |
April | 0.291469E+09 | 0.117921E+09 | 0.173548E+09 | 0.326549E+09 | 0.153957E+09 |
May | 0.258682E+09 | 52960934.60 | 0.205721E+09 | 0.313647E+09 | 88438173.83 |
June | 0.236380E+09 | 36420939.70 | 0.199959E+09 | 0.339565E+09 | 32199645.35 |
July | 0.254153E+09 | 42895608.52 | 0.211258E+09 | 0.411756E+09 | 8097151.49 |
August | 0.340413E+09 | 0.125575E+09 | 0.214838E+09 | 0.541108E+09 | 19708426.48 |
September | 0.347639E+09 | 0.174544E+09 | 0.173095E+09 | 0.482617E+09 | 55613056.29 |
October | 0.507648E+09 | 0.318338E+09 | 0.189310E+09 | 0.644332E+09 | 0.133020E+09 |
November | 0.340174E+09 | 0.204060E+09 | 0.136113E+09 | 0.367394E+09 | 0.214515E+09 |
December | 0.348649E+09 | 0.247629E+09 | 0.101021E+09 | 0.361640E+09 | 0.288806E+09 |
Annual Sum or Average | 0.401204E+10 | 0.199678E+10 | 0.201526E+10 | 0.490063E+10 | 0.183522E+10 |
Minimum of Months | 0.236380E+09 | 36420939.70 | 0.101021E+09 | 0.313647E+09 | 8097151.49 |
Maximum of Months | 0.507648E+09 | 0.318338E+09 | 0.214838E+09 | 0.644332E+09 | 0.323591E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62085473.63 | 0.00 | 62085473.63 | 3500378.64 | 0.363257E+09 |
February | 76739382.29 | 0.00 | 76739382.29 | 7013729.89 | 0.335651E+09 |
March | 0.117848E+09 | 2454.62 | 0.117846E+09 | 41655711.38 | 0.238030E+09 |
April | 0.137245E+09 | 565514.21 | 0.136680E+09 | 89467238.42 | 0.152781E+09 |
May | 0.188627E+09 | 6903211.21 | 0.181724E+09 | 0.186836E+09 | 85079572.00 |
June | 0.192578E+09 | 10242901.02 | 0.182335E+09 | 0.251532E+09 | 35630950.23 |
July | 0.193148E+09 | 7538040.63 | 0.185610E+09 | 0.301314E+09 | 10672182.23 |
August | 0.170807E+09 | 2269513.75 | 0.168538E+09 | 0.263790E+09 | 21659682.92 |
September | 0.124465E+09 | 72357.39 | 0.124392E+09 | 0.142995E+09 | 60596978.95 |
October | 0.111214E+09 | 0.00 | 0.111214E+09 | 86434540.41 | 0.139301E+09 |
November | 75489568.31 | 0.00 | 75489568.31 | 22691577.63 | 0.231991E+09 |
December | 54155055.53 | 0.00 | 54155055.53 | 2309357.52 | 0.327919E+09 |
Annual Sum or Average | 0.150440E+10 | 27593992.83 | 0.147681E+10 | 0.139954E+10 | 0.200257E+10 |
Minimum of Months | 54155055.53 | 0.00 | 54155055.53 | 2309357.52 | 10672182.23 |
Maximum of Months | 0.193148E+09 | 10242901.02 | 0.185610E+09 | 0.301314E+09 | 0.363257E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.241522E+09 | 96495417.54 | 0.145026E+09 | 0.145296E+09 | 0.633651E+09 |
February | 0.338694E+09 | 0.157722E+09 | 0.180972E+09 | 0.235142E+09 | 0.563523E+09 |
March | 0.481538E+09 | 0.204650E+09 | 0.276888E+09 | 0.428657E+09 | 0.421490E+09 |
April | 0.557847E+09 | 0.244845E+09 | 0.313002E+09 | 0.584583E+09 | 0.273038E+09 |
May | 0.695935E+09 | 0.277340E+09 | 0.418595E+09 | 0.839407E+09 | 0.162312E+09 |
June | 0.625383E+09 | 0.226521E+09 | 0.398862E+09 | 0.849700E+09 | 68314705.03 |
July | 0.648197E+09 | 0.233361E+09 | 0.414837E+09 | 0.976350E+09 | 20117519.17 |
August | 0.731240E+09 | 0.329905E+09 | 0.401335E+09 | 0.108579E+10 | 40084381.17 |
September | 0.529355E+09 | 0.238470E+09 | 0.290885E+09 | 0.692441E+09 | 0.108835E+09 |
October | 0.494167E+09 | 0.223686E+09 | 0.270480E+09 | 0.567331E+09 | 0.249565E+09 |
November | 0.296195E+09 | 0.113821E+09 | 0.182374E+09 | 0.242773E+09 | 0.406456E+09 |
December | 0.239288E+09 | 0.112907E+09 | 0.126381E+09 | 0.160541E+09 | 0.566463E+09 |
Annual Sum or Average | 0.587936E+10 | 0.245972E+10 | 0.341964E+10 | 0.680801E+10 | 0.351385E+10 |
Minimum of Months | 0.239288E+09 | 96495417.54 | 0.126381E+09 | 0.145296E+09 | 20117519.17 |
Maximum of Months | 0.731240E+09 | 0.329905E+09 | 0.418595E+09 | 0.108579E+10 | 0.633651E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78627334.97 | 0.00 | 78627334.97 | 2794991.17 | 0.494754E+09 |
February | 97185585.68 | 0.00 | 97185585.68 | 7425908.95 | 0.454111E+09 |
March | 0.149247E+09 | 3108.62 | 0.149244E+09 | 53431578.11 | 0.317343E+09 |
April | 0.173812E+09 | 716188.06 | 0.173096E+09 | 0.120191E+09 | 0.203712E+09 |
May | 0.238884E+09 | 8742481.42 | 0.230142E+09 | 0.249983E+09 | 0.114873E+09 |
June | 0.243887E+09 | 12971987.85 | 0.230915E+09 | 0.326634E+09 | 52858969.92 |
July | 0.244609E+09 | 9546452.84 | 0.235063E+09 | 0.378671E+09 | 21192049.97 |
August | 0.216317E+09 | 2874195.96 | 0.213443E+09 | 0.329606E+09 | 37670866.88 |
September | 0.157627E+09 | 91636.07 | 0.157535E+09 | 0.184728E+09 | 88602550.03 |
October | 0.140846E+09 | 0.00 | 0.140846E+09 | 0.111048E+09 | 0.195659E+09 |
November | 95602775.14 | 0.00 | 95602775.14 | 27496586.12 | 0.315306E+09 |
December | 68583960.84 | 0.00 | 68583960.84 | 2082042.68 | 0.448334E+09 |
Annual Sum or Average | 0.190523E+10 | 34946050.83 | 0.187028E+10 | 0.179409E+10 | 0.274442E+10 |
Minimum of Months | 68583960.84 | 0.00 | 68583960.84 | 2082042.68 | 21192049.97 |
Maximum of Months | 0.244609E+09 | 12971987.85 | 0.235063E+09 | 0.378671E+09 | 0.494754E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 28985291.37 | 0.00 | 28985291.37 | 1030349.48 | 0.182387E+09 |
February | 35826631.02 | 0.00 | 35826631.02 | 2737497.52 | 0.167404E+09 |
March | 55018625.63 | 1145.97 | 55017479.66 | 19697092.12 | 0.116986E+09 |
April | 64074374.08 | 264016.58 | 63810357.50 | 44307474.09 | 75096634.27 |
May | 88062541.06 | 3222840.65 | 84839700.41 | 92154263.84 | 42346811.60 |
June | 89906978.19 | 4782011.85 | 85124966.34 | 0.120411E+09 | 19486005.03 |
July | 90173173.31 | 3519217.80 | 86653955.51 | 0.139594E+09 | 7812267.11 |
August | 79743320.60 | 1059547.64 | 78683772.95 | 0.121506E+09 | 13887041.36 |
September | 58107717.19 | 33780.85 | 58073936.34 | 68098453.81 | 32662568.68 |
October | 51921558.38 | 0.00 | 51921558.38 | 40936805.62 | 72128057.10 |
November | 35243141.51 | 0.00 | 35243141.51 | 10136380.19 | 0.116235E+09 |
December | 25282887.80 | 0.00 | 25282887.80 | 767527.14 | 0.165274E+09 |
Annual Sum or Average | 0.702346E+09 | 12882561.34 | 0.689464E+09 | 0.661377E+09 | 0.101171E+10 |
Minimum of Months | 25282887.80 | 0.00 | 25282887.80 | 767527.14 | 7812267.11 |
Maximum of Months | 90173173.31 | 4782011.85 | 86653955.51 | 0.139594E+09 | 0.182387E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150574E+09 | 98808493.80 | 51765403.86 | 0.148845E+09 | 0.159382E+09 |
February | 0.179985E+09 | 0.119623E+09 | 60362290.71 | 0.182292E+09 | 0.141551E+09 |
March | 0.176553E+09 | 97190004.50 | 79362917.17 | 0.191135E+09 | 0.110160E+09 |
April | 0.135998E+09 | 55021364.60 | 80976996.46 | 0.155943E+09 | 75221666.53 |
May | 0.120700E+09 | 24711358.67 | 95988587.17 | 0.149928E+09 | 45268493.79 |
June | 0.110294E+09 | 16993863.70 | 93300242.89 | 0.157962E+09 | 20619143.23 |
July | 0.118587E+09 | 20014918.08 | 98572006.58 | 0.188894E+09 | 7985713.97 |
August | 0.158835E+09 | 58592560.64 | 0.100243E+09 | 0.249700E+09 | 14289173.68 |
September | 0.162207E+09 | 81441637.01 | 80765468.23 | 0.225453E+09 | 32276598.11 |
October | 0.236867E+09 | 0.148535E+09 | 88331451.67 | 0.303128E+09 | 68355750.52 |
November | 0.158724E+09 | 95213646.52 | 63509953.91 | 0.172627E+09 | 0.104875E+09 |
December | 0.162678E+09 | 0.115543E+09 | 47135925.66 | 0.169085E+09 | 0.141894E+09 |
Annual Sum or Average | 0.187200E+10 | 0.931688E+09 | 0.940314E+09 | 0.229499E+10 | 0.921879E+09 |
Minimum of Months | 0.110294E+09 | 16993863.70 | 47135925.66 | 0.148845E+09 | 7985713.97 |
Maximum of Months | 0.236867E+09 | 0.148535E+09 | 0.100243E+09 | 0.303128E+09 | 0.159382E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.408688E+09 | 0.268186E+09 | 0.140502E+09 | 0.403995E+09 | 0.432596E+09 |
February | 0.488517E+09 | 0.324681E+09 | 0.163836E+09 | 0.494777E+09 | 0.384199E+09 |
March | 0.479201E+09 | 0.263794E+09 | 0.215407E+09 | 0.518780E+09 | 0.298997E+09 |
April | 0.369127E+09 | 0.149339E+09 | 0.219788E+09 | 0.423261E+09 | 0.204167E+09 |
May | 0.327604E+09 | 67071682.02 | 0.260533E+09 | 0.406934E+09 | 0.122868E+09 |
June | 0.299361E+09 | 46124822.10 | 0.253236E+09 | 0.428740E+09 | 55964572.29 |
July | 0.321869E+09 | 54324581.63 | 0.267545E+09 | 0.512696E+09 | 21674861.16 |
August | 0.431112E+09 | 0.159032E+09 | 0.272079E+09 | 0.677736E+09 | 38783740.14 |
September | 0.440263E+09 | 0.221049E+09 | 0.219214E+09 | 0.611926E+09 | 87605289.31 |
October | 0.642904E+09 | 0.403155E+09 | 0.239750E+09 | 0.822753E+09 | 0.185531E+09 |
November | 0.430808E+09 | 0.258429E+09 | 0.172379E+09 | 0.468545E+09 | 0.284653E+09 |
December | 0.441543E+09 | 0.313606E+09 | 0.127937E+09 | 0.458930E+09 | 0.385129E+09 |
Annual Sum or Average | 0.508100E+10 | 0.252879E+10 | 0.255220E+10 | 0.622907E+10 | 0.250217E+10 |
Minimum of Months | 0.299361E+09 | 46124822.10 | 0.127937E+09 | 0.403995E+09 | 21674861.16 |
Maximum of Months | 0.642904E+09 | 0.403155E+09 | 0.272079E+09 | 0.822753E+09 | 0.432596E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.322707E+09 | 0.211765E+09 | 0.110943E+09 | 0.319965E+09 | 0.321913E+09 |
February | 0.385741E+09 | 0.256374E+09 | 0.129367E+09 | 0.389639E+09 | 0.289093E+09 |
March | 0.378385E+09 | 0.208296E+09 | 0.170089E+09 | 0.402914E+09 | 0.228373E+09 |
April | 0.291469E+09 | 0.117921E+09 | 0.173548E+09 | 0.326434E+09 | 0.154183E+09 |
May | 0.258682E+09 | 52960934.60 | 0.205721E+09 | 0.312637E+09 | 89119700.79 |
June | 0.236380E+09 | 36420939.70 | 0.199959E+09 | 0.336610E+09 | 32601621.60 |
July | 0.254153E+09 | 42895608.52 | 0.211258E+09 | 0.409258E+09 | 7972808.50 |
August | 0.340413E+09 | 0.125575E+09 | 0.214838E+09 | 0.538743E+09 | 19475966.16 |
September | 0.347639E+09 | 0.174544E+09 | 0.173095E+09 | 0.481000E+09 | 55042232.20 |
October | 0.507648E+09 | 0.318338E+09 | 0.189310E+09 | 0.642290E+09 | 0.132485E+09 |
November | 0.340174E+09 | 0.204060E+09 | 0.136113E+09 | 0.368498E+09 | 0.211865E+09 |
December | 0.348649E+09 | 0.247629E+09 | 0.101021E+09 | 0.362200E+09 | 0.286635E+09 |
Annual Sum or Average | 0.401204E+10 | 0.199678E+10 | 0.201526E+10 | 0.489019E+10 | 0.182876E+10 |
Minimum of Months | 0.236380E+09 | 36420939.70 | 0.101021E+09 | 0.312637E+09 | 7972808.50 |
Maximum of Months | 0.507648E+09 | 0.318338E+09 | 0.214838E+09 | 0.642290E+09 | 0.321913E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239844E+09 | 98462657.35 | 0.141382E+09 | 0.144015E+09 | 0.650323E+09 |
February | 0.318223E+09 | 0.139658E+09 | 0.178565E+09 | 0.213159E+09 | 0.594955E+09 |
March | 0.523325E+09 | 0.242520E+09 | 0.280804E+09 | 0.466660E+09 | 0.424867E+09 |
April | 0.550044E+09 | 0.235058E+09 | 0.314986E+09 | 0.571303E+09 | 0.280746E+09 |
May | 0.663989E+09 | 0.252408E+09 | 0.411582E+09 | 0.796630E+09 | 0.160844E+09 |
June | 0.702057E+09 | 0.283331E+09 | 0.418726E+09 | 0.961366E+09 | 59317504.30 |
July | 0.678728E+09 | 0.255057E+09 | 0.423671E+09 | 0.101809E+10 | 14678414.94 |
August | 0.750935E+09 | 0.347199E+09 | 0.403736E+09 | 0.111285E+10 | 36039378.97 |
September | 0.517041E+09 | 0.225725E+09 | 0.291316E+09 | 0.677681E+09 | 0.102833E+09 |
October | 0.530121E+09 | 0.258241E+09 | 0.271880E+09 | 0.605730E+09 | 0.254236E+09 |
November | 0.241596E+09 | 70580626.93 | 0.171015E+09 | 0.164677E+09 | 0.421097E+09 |
December | 0.220511E+09 | 95188244.85 | 0.125323E+09 | 0.135778E+09 | 0.587947E+09 |
Annual Sum or Average | 0.593641E+10 | 0.250343E+10 | 0.343299E+10 | 0.686794E+10 | 0.358789E+10 |
Minimum of Months | 0.220511E+09 | 70580626.93 | 0.125323E+09 | 0.135778E+09 | 14678414.94 |
Maximum of Months | 0.750935E+09 | 0.347199E+09 | 0.423671E+09 | 0.111285E+10 | 0.650323E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62085473.63 | 0.00 | 62085473.63 | 4210546.46 | 0.360983E+09 |
February | 76739382.29 | 0.00 | 76739382.29 | 7837026.90 | 0.334266E+09 |
March | 0.117848E+09 | 2454.62 | 0.117846E+09 | 43704551.97 | 0.238792E+09 |
April | 0.137245E+09 | 565514.21 | 0.136680E+09 | 91100337.26 | 0.153263E+09 |
May | 0.188627E+09 | 6903211.21 | 0.181724E+09 | 0.185658E+09 | 87432896.20 |
June | 0.192578E+09 | 10242901.02 | 0.182335E+09 | 0.247756E+09 | 39151921.76 |
July | 0.193148E+09 | 7538040.63 | 0.185610E+09 | 0.300588E+09 | 11325850.92 |
August | 0.170807E+09 | 2269513.75 | 0.168538E+09 | 0.265222E+09 | 22111628.57 |
September | 0.124465E+09 | 72357.39 | 0.124392E+09 | 0.144245E+09 | 62226723.50 |
October | 0.111214E+09 | 0.00 | 0.111214E+09 | 88778885.11 | 0.140713E+09 |
November | 75489568.31 | 0.00 | 75489568.31 | 24691433.11 | 0.228209E+09 |
December | 54155055.53 | 0.00 | 54155055.53 | 2979612.70 | 0.324541E+09 |
Annual Sum or Average | 0.150440E+10 | 27593992.83 | 0.147681E+10 | 0.140677E+10 | 0.200302E+10 |
Minimum of Months | 54155055.53 | 0.00 | 54155055.53 | 2979612.70 | 11325850.92 |
Maximum of Months | 0.193148E+09 | 10242901.02 | 0.185610E+09 | 0.300588E+09 | 0.360983E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239844E+09 | 98462657.35 | 0.141382E+09 | 0.151718E+09 | 0.643695E+09 |
February | 0.318223E+09 | 0.139658E+09 | 0.178565E+09 | 0.223648E+09 | 0.585881E+09 |
March | 0.523325E+09 | 0.242520E+09 | 0.280804E+09 | 0.479350E+09 | 0.418695E+09 |
April | 0.550044E+09 | 0.235058E+09 | 0.314986E+09 | 0.575862E+09 | 0.280299E+09 |
May | 0.663989E+09 | 0.252408E+09 | 0.411582E+09 | 0.788396E+09 | 0.168618E+09 |
June | 0.702057E+09 | 0.283331E+09 | 0.418726E+09 | 0.942730E+09 | 74624774.10 |
July | 0.678728E+09 | 0.255057E+09 | 0.423671E+09 | 0.101136E+10 | 20964889.05 |
August | 0.750935E+09 | 0.347199E+09 | 0.403736E+09 | 0.111243E+10 | 41755704.91 |
September | 0.517041E+09 | 0.225725E+09 | 0.291316E+09 | 0.674723E+09 | 0.113598E+09 |
October | 0.530121E+09 | 0.258241E+09 | 0.271880E+09 | 0.614777E+09 | 0.255123E+09 |
November | 0.241596E+09 | 70580626.93 | 0.171015E+09 | 0.175053E+09 | 0.413325E+09 |
December | 0.220511E+09 | 95188244.85 | 0.125323E+09 | 0.145134E+09 | 0.579363E+09 |
Annual Sum or Average | 0.593641E+10 | 0.250343E+10 | 0.343299E+10 | 0.689519E+10 | 0.359594E+10 |
Minimum of Months | 0.220511E+09 | 70580626.93 | 0.125323E+09 | 0.145134E+09 | 20964889.05 |
Maximum of Months | 0.750935E+09 | 0.347199E+09 | 0.423671E+09 | 0.111243E+10 | 0.643695E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.473281E+09 | 0.310573E+09 | 0.162708E+09 | 0.454368E+09 | 0.491010E+09 |
February | 0.565726E+09 | 0.375997E+09 | 0.189730E+09 | 0.554285E+09 | 0.441390E+09 |
March | 0.554938E+09 | 0.305486E+09 | 0.249452E+09 | 0.580553E+09 | 0.344758E+09 |
April | 0.427468E+09 | 0.172942E+09 | 0.254525E+09 | 0.474337E+09 | 0.229166E+09 |
May | 0.379382E+09 | 77672293.27 | 0.301710E+09 | 0.461409E+09 | 0.128679E+09 |
June | 0.346674E+09 | 53414803.41 | 0.293260E+09 | 0.502200E+09 | 44016097.34 |
July | 0.372740E+09 | 62910526.60 | 0.309830E+09 | 0.610069E+09 | 9667503.40 |
August | 0.499248E+09 | 0.184167E+09 | 0.315081E+09 | 0.798125E+09 | 26194167.46 |
September | 0.509846E+09 | 0.255986E+09 | 0.253861E+09 | 0.705190E+09 | 80033758.63 |
October | 0.744515E+09 | 0.466873E+09 | 0.277642E+09 | 0.934208E+09 | 0.198987E+09 |
November | 0.498897E+09 | 0.299274E+09 | 0.199623E+09 | 0.526027E+09 | 0.327201E+09 |
December | 0.511328E+09 | 0.363171E+09 | 0.148157E+09 | 0.515223E+09 | 0.439746E+09 |
Annual Sum or Average | 0.588404E+10 | 0.292847E+10 | 0.295558E+10 | 0.711599E+10 | 0.276085E+10 |
Minimum of Months | 0.346674E+09 | 53414803.41 | 0.148157E+09 | 0.454368E+09 | 9667503.40 |
Maximum of Months | 0.744515E+09 | 0.466873E+09 | 0.315081E+09 | 0.934208E+09 | 0.491010E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.434582E+09 | 0.00 | 0.434582E+09 | 6327816.72 | 0.302326E+10 |
February | 0.537155E+09 | 0.00 | 0.537155E+09 | 25804686.09 | 0.275856E+10 |
March | 0.824904E+09 | 17181.70 | 0.824887E+09 | 0.229288E+09 | 0.202576E+10 |
April | 0.960679E+09 | 3958449.54 | 0.956721E+09 | 0.559528E+09 | 0.132436E+10 |
May | 0.132034E+10 | 48320648.33 | 0.127202E+10 | 0.123314E+10 | 0.743398E+09 |
June | 0.134799E+10 | 71697591.63 | 0.127629E+10 | 0.171658E+10 | 0.335436E+09 |
July | 0.135198E+10 | 52764286.00 | 0.129922E+10 | 0.202210E+10 | 0.143517E+09 |
August | 0.119561E+10 | 15885994.55 | 0.117972E+10 | 0.177558E+10 | 0.223431E+09 |
September | 0.871220E+09 | 506482.57 | 0.870713E+09 | 0.962905E+09 | 0.553179E+09 |
October | 0.778470E+09 | 0.00 | 0.778470E+09 | 0.556231E+09 | 0.119046E+10 |
November | 0.528407E+09 | 0.00 | 0.528407E+09 | 0.111864E+09 | 0.200596E+10 |
December | 0.379071E+09 | 0.00 | 0.379071E+09 | 5329751.12 | 0.278444E+10 |
Annual Sum or Average | 0.105304E+11 | 0.193151E+09 | 0.103373E+11 | 0.920467E+10 | 0.171118E+11 |
Minimum of Months | 0.379071E+09 | 0.00 | 0.379071E+09 | 5329751.12 | 0.143517E+09 |
Maximum of Months | 0.135198E+10 | 71697591.63 | 0.129922E+10 | 0.202210E+10 | 0.302326E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.434582E+09 | 0.00 | 0.434582E+09 | 4065217.34 | 0.311594E+10 |
February | 0.537155E+09 | 0.00 | 0.537155E+09 | 21243687.90 | 0.283883E+10 |
March | 0.824904E+09 | 17181.70 | 0.824887E+09 | 0.210108E+09 | 0.209019E+10 |
April | 0.960679E+09 | 3958449.54 | 0.956721E+09 | 0.532038E+09 | 0.136873E+10 |
May | 0.132034E+10 | 48320648.33 | 0.127202E+10 | 0.119904E+10 | 0.767451E+09 |
June | 0.134799E+10 | 71697591.63 | 0.127629E+10 | 0.169178E+10 | 0.350188E+09 |
July | 0.135198E+10 | 52764286.00 | 0.129922E+10 | 0.199922E+10 | 0.154541E+09 |
August | 0.119561E+10 | 15885994.55 | 0.117972E+10 | 0.175245E+10 | 0.234910E+09 |
September | 0.871220E+09 | 506482.57 | 0.870713E+09 | 0.940470E+09 | 0.575868E+09 |
October | 0.778470E+09 | 0.00 | 0.778470E+09 | 0.532605E+09 | 0.122806E+10 |
November | 0.528407E+09 | 0.00 | 0.528407E+09 | 0.100161E+09 | 0.207544E+10 |
December | 0.379071E+09 | 0.00 | 0.379071E+09 | 3885915.31 | 0.287218E+10 |
Annual Sum or Average | 0.105304E+11 | 0.193151E+09 | 0.103373E+11 | 0.898707E+10 | 0.176723E+11 |
Minimum of Months | 0.379071E+09 | 0.00 | 0.379071E+09 | 3885915.31 | 0.154541E+09 |
Maximum of Months | 0.135198E+10 | 71697591.63 | 0.129922E+10 | 0.199922E+10 | 0.311594E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62085473.63 | 0.00 | 62085473.63 | 5919911.39 | 0.375606E+09 |
February | 76739382.29 | 0.00 | 76739382.29 | 9817939.68 | 0.345156E+09 |
March | 0.117848E+09 | 2454.62 | 0.117846E+09 | 53782817.87 | 0.247000E+09 |
April | 0.137245E+09 | 565514.21 | 0.136680E+09 | 0.119300E+09 | 0.162263E+09 |
May | 0.188627E+09 | 6903211.21 | 0.181724E+09 | 0.241332E+09 | 94990614.81 |
June | 0.192578E+09 | 10242901.02 | 0.182335E+09 | 0.319704E+09 | 42950838.34 |
July | 0.193148E+09 | 7538040.63 | 0.185610E+09 | 0.373692E+09 | 19108535.39 |
August | 0.170807E+09 | 2269513.75 | 0.168538E+09 | 0.333084E+09 | 28291428.51 |
September | 0.124465E+09 | 72357.39 | 0.124392E+09 | 0.198463E+09 | 63077374.74 |
October | 0.111214E+09 | 0.00 | 0.111214E+09 | 0.120119E+09 | 0.138408E+09 |
November | 75489568.31 | 0.00 | 75489568.31 | 31696851.97 | 0.240313E+09 |
December | 54155055.53 | 0.00 | 54155055.53 | 4384091.17 | 0.338461E+09 |
Annual Sum or Average | 0.150440E+10 | 27593992.83 | 0.147681E+10 | 0.181130E+10 | 0.209563E+10 |
Minimum of Months | 54155055.53 | 0.00 | 54155055.53 | 4384091.17 | 19108535.39 |
Maximum of Months | 0.193148E+09 | 10242901.02 | 0.185610E+09 | 0.373692E+09 | 0.375606E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.483009E+09 | 0.192977E+09 | 0.290032E+09 | 0.310676E+09 | 0.131779E+10 |
February | 0.677341E+09 | 0.315422E+09 | 0.361918E+09 | 0.495663E+09 | 0.116423E+10 |
March | 0.963008E+09 | 0.409271E+09 | 0.553737E+09 | 0.916608E+09 | 0.886335E+09 |
April | 0.111562E+10 | 0.489656E+09 | 0.625960E+09 | 0.128875E+10 | 0.587116E+09 |
May | 0.139177E+10 | 0.554641E+09 | 0.837130E+09 | 0.187488E+10 | 0.356890E+09 |
June | 0.125068E+10 | 0.453010E+09 | 0.797667E+09 | 0.194954E+10 | 0.161276E+09 |
July | 0.129630E+10 | 0.466688E+09 | 0.829615E+09 | 0.222059E+10 | 72002850.17 |
August | 0.146238E+10 | 0.659763E+09 | 0.802613E+09 | 0.243019E+10 | 0.105924E+09 |
September | 0.105863E+10 | 0.476906E+09 | 0.581729E+09 | 0.159723E+10 | 0.231862E+09 |
October | 0.988263E+09 | 0.447341E+09 | 0.540922E+09 | 0.127637E+10 | 0.503213E+09 |
November | 0.592348E+09 | 0.227626E+09 | 0.364722E+09 | 0.535732E+09 | 0.844529E+09 |
December | 0.478542E+09 | 0.225798E+09 | 0.252744E+09 | 0.344517E+09 | 0.117402E+10 |
Annual Sum or Average | 0.117579E+11 | 0.491910E+10 | 0.683879E+10 | 0.152407E+11 | 0.740518E+10 |
Minimum of Months | 0.478542E+09 | 0.192977E+09 | 0.252744E+09 | 0.310676E+09 | 72002850.17 |
Maximum of Months | 0.146238E+10 | 0.659763E+09 | 0.837130E+09 | 0.243019E+10 | 0.131779E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.322707E+09 | 0.211765E+09 | 0.110943E+09 | 0.332047E+09 | 0.333605E+09 |
February | 0.385741E+09 | 0.256374E+09 | 0.129367E+09 | 0.405264E+09 | 0.295635E+09 |
March | 0.378385E+09 | 0.208296E+09 | 0.170089E+09 | 0.428811E+09 | 0.235540E+09 |
April | 0.291469E+09 | 0.117921E+09 | 0.173548E+09 | 0.360346E+09 | 0.162829E+09 |
May | 0.258682E+09 | 52960934.60 | 0.205721E+09 | 0.363634E+09 | 98992723.38 |
June | 0.236380E+09 | 36420939.70 | 0.199959E+09 | 0.398009E+09 | 44675121.40 |
July | 0.254153E+09 | 42895608.52 | 0.211258E+09 | 0.478115E+09 | 19482260.96 |
August | 0.340413E+09 | 0.125575E+09 | 0.214838E+09 | 0.608213E+09 | 28524911.69 |
September | 0.347639E+09 | 0.174544E+09 | 0.173095E+09 | 0.537803E+09 | 62559101.49 |
October | 0.507648E+09 | 0.318338E+09 | 0.189310E+09 | 0.689521E+09 | 0.135047E+09 |
November | 0.340174E+09 | 0.204060E+09 | 0.136113E+09 | 0.388794E+09 | 0.220182E+09 |
December | 0.348649E+09 | 0.247629E+09 | 0.101021E+09 | 0.376257E+09 | 0.296384E+09 |
Annual Sum or Average | 0.401204E+10 | 0.199678E+10 | 0.201526E+10 | 0.536681E+10 | 0.193346E+10 |
Minimum of Months | 0.236380E+09 | 36420939.70 | 0.101021E+09 | 0.332047E+09 | 19482260.96 |
Maximum of Months | 0.507648E+09 | 0.318338E+09 | 0.214838E+09 | 0.689521E+09 | 0.333605E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78627334.97 | 0.00 | 78627334.97 | 2062530.47 | 0.504425E+09 |
February | 97185585.68 | 0.00 | 97185585.68 | 6229411.87 | 0.463343E+09 |
March | 0.149247E+09 | 3108.62 | 0.149244E+09 | 48182621.73 | 0.325107E+09 |
April | 0.173812E+09 | 716188.06 | 0.173096E+09 | 0.112809E+09 | 0.208242E+09 |
May | 0.238884E+09 | 8742481.42 | 0.230142E+09 | 0.239006E+09 | 0.118384E+09 |
June | 0.243887E+09 | 12971987.85 | 0.230915E+09 | 0.315445E+09 | 55983645.88 |
July | 0.244609E+09 | 9546452.84 | 0.235063E+09 | 0.364747E+09 | 25276959.95 |
August | 0.216317E+09 | 2874195.96 | 0.213443E+09 | 0.318154E+09 | 40138896.28 |
September | 0.157627E+09 | 91636.07 | 0.157535E+09 | 0.177696E+09 | 90570844.36 |
October | 0.140846E+09 | 0.00 | 0.140846E+09 | 0.106331E+09 | 0.194406E+09 |
November | 95602775.14 | 0.00 | 95602775.14 | 24980627.24 | 0.321324E+09 |
December | 68583960.84 | 0.00 | 68583960.84 | 1588982.08 | 0.458267E+09 |
Annual Sum or Average | 0.190523E+10 | 34946050.83 | 0.187028E+10 | 0.171723E+10 | 0.280547E+10 |
Minimum of Months | 68583960.84 | 0.00 | 68583960.84 | 1588982.08 | 25276959.95 |
Maximum of Months | 0.244609E+09 | 12971987.85 | 0.235063E+09 | 0.364747E+09 | 0.504425E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70348174.52 | 0.00 | 70348174.52 | 1845353.83 | 0.451292E+09 |
February | 86952311.75 | 0.00 | 86952311.75 | 5573478.40 | 0.414555E+09 |
March | 0.133532E+09 | 2781.30 | 0.133529E+09 | 43109174.23 | 0.290875E+09 |
April | 0.155510E+09 | 640776.17 | 0.154870E+09 | 0.100931E+09 | 0.186315E+09 |
May | 0.213730E+09 | 7821931.26 | 0.205909E+09 | 0.213840E+09 | 0.105918E+09 |
June | 0.218207E+09 | 11606086.68 | 0.206601E+09 | 0.282230E+09 | 50088780.09 |
July | 0.218853E+09 | 8541247.52 | 0.210312E+09 | 0.326340E+09 | 22615391.84 |
August | 0.193539E+09 | 2571554.02 | 0.190968E+09 | 0.284653E+09 | 35912422.58 |
September | 0.141029E+09 | 81987.14 | 0.140947E+09 | 0.158985E+09 | 81034077.62 |
October | 0.126015E+09 | 0.00 | 0.126015E+09 | 95134709.51 | 0.173936E+09 |
November | 85536165.15 | 0.00 | 85536165.15 | 22350261.85 | 0.287486E+09 |
December | 61362329.63 | 0.00 | 61362329.63 | 1421668.29 | 0.409958E+09 |
Annual Sum or Average | 0.170462E+10 | 31266364.09 | 0.167335E+10 | 0.153641E+10 | 0.250999E+10 |
Minimum of Months | 61362329.63 | 0.00 | 61362329.63 | 1421668.29 | 22615391.84 |
Maximum of Months | 0.218853E+09 | 11606086.68 | 0.210312E+09 | 0.326340E+09 | 0.451292E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120476E+10 | 0.790580E+09 | 0.414182E+09 | 0.117359E+10 | 0.129655E+10 |
February | 0.144009E+10 | 0.957120E+09 | 0.482967E+09 | 0.143796E+10 | 0.114962E+10 |
March | 0.141262E+10 | 0.777630E+09 | 0.634994E+09 | 0.150171E+10 | 0.902236E+09 |
April | 0.108814E+10 | 0.440233E+09 | 0.647908E+09 | 0.121838E+10 | 0.617044E+09 |
May | 0.965737E+09 | 0.197719E+09 | 0.768018E+09 | 0.116421E+10 | 0.374940E+09 |
June | 0.882478E+09 | 0.135970E+09 | 0.746508E+09 | 0.122757E+10 | 0.175589E+09 |
July | 0.948830E+09 | 0.160142E+09 | 0.788688E+09 | 0.146653E+10 | 76292809.71 |
August | 0.127086E+10 | 0.468807E+09 | 0.802056E+09 | 0.195758E+10 | 0.122053E+09 |
September | 0.129784E+10 | 0.651626E+09 | 0.646216E+09 | 0.177607E+10 | 0.264631E+09 |
October | 0.189520E+10 | 0.118845E+10 | 0.706752E+09 | 0.240012E+10 | 0.544118E+09 |
November | 0.126997E+10 | 0.761817E+09 | 0.508152E+09 | 0.136213E+10 | 0.853080E+09 |
December | 0.130161E+10 | 0.924471E+09 | 0.377141E+09 | 0.133460E+10 | 0.115589E+10 |
Annual Sum or Average | 0.149781E+11 | 0.745457E+10 | 0.752358E+10 | 0.180204E+11 | 0.753204E+10 |
Minimum of Months | 0.882478E+09 | 0.135970E+09 | 0.377141E+09 | 0.116421E+10 | 76292809.71 |
Maximum of Months | 0.189520E+10 | 0.118845E+10 | 0.802056E+09 | 0.240012E+10 | 0.129655E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 603.30 | 602.95 | 609.38 | 399.88 | 209.50 | 0.00 | 0.00 |
February | 814.23 | 597.44 | 806.45 | 535.99 | 270.46 | 0.00 | 0.00 |
March | 766.94 | 423.82 | 714.52 | 393.33 | 321.18 | 0.00 | 0.00 |
April | 645.29 | 298.18 | 568.74 | 230.10 | 338.64 | 0.00 | 0.00 |
May | 603.81 | 169.99 | 488.48 | 100.01 | 388.47 | 0.00 | 0.00 |
June | 654.79 | 80.05 | 461.24 | 71.07 | 390.17 | 0.00 | 0.00 |
July | 748.56 | 32.97 | 479.92 | 81.00 | 398.92 | 0.00 | 0.00 |
August | 987.25 | 60.43 | 642.81 | 237.13 | 405.68 | 0.00 | 0.00 |
September | 929.40 | 129.67 | 678.34 | 340.59 | 337.75 | 0.00 | 0.00 |
October | 1208.00 | 269.44 | 958.61 | 601.13 | 357.48 | 0.00 | 0.00 |
November | 715.54 | 417.78 | 663.77 | 398.18 | 265.59 | 0.00 | 0.00 |
December | 679.69 | 542.17 | 658.37 | 467.61 | 190.76 | 0.00 | 0.00 |
Annual Sum or Average | 779.93 | 300.42 | 643.45 | 320.24 | 323.20 | 0.00 | 0.00 |
Minimum of Months | 603.30 | 32.97 | 461.24 | 71.07 | 190.76 | 0.00 | 0.00 |
Maximum of Months | 1208.00 | 602.95 | 958.61 | 601.13 | 405.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1678.06 | 1751.23 | 1715.97 | 1126.05 | 589.93 | 0.00 | 0.00 |
February | 2264.07 | 1740.12 | 2270.92 | 1509.32 | 761.60 | 0.00 | 0.00 |
March | 2131.50 | 1266.22 | 2012.03 | 1107.60 | 904.43 | 0.00 | 0.00 |
April | 1786.72 | 908.11 | 1601.52 | 647.94 | 953.59 | 0.00 | 0.00 |
May | 1659.67 | 539.19 | 1375.52 | 281.62 | 1093.90 | 0.00 | 0.00 |
June | 1815.65 | 262.59 | 1298.82 | 200.12 | 1098.70 | 0.00 | 0.00 |
July | 2087.08 | 114.51 | 1351.43 | 228.09 | 1123.34 | 0.00 | 0.00 |
August | 2762.21 | 189.13 | 1810.11 | 667.74 | 1142.38 | 0.00 | 0.00 |
September | 2589.61 | 415.79 | 1910.16 | 959.07 | 951.10 | 0.00 | 0.00 |
October | 3368.82 | 828.30 | 2699.38 | 1692.74 | 1006.64 | 0.00 | 0.00 |
November | 1983.37 | 1248.39 | 1869.14 | 1121.25 | 747.90 | 0.00 | 0.00 |
December | 1890.29 | 1591.16 | 1853.92 | 1316.75 | 537.17 | 0.00 | 0.00 |
Annual Sum or Average | 2168.66 | 899.84 | 1811.90 | 901.78 | 910.12 | 0.00 | 0.00 |
Minimum of Months | 1659.67 | 114.51 | 1298.82 | 200.12 | 537.17 | 0.00 | 0.00 |
Maximum of Months | 3368.82 | 1751.23 | 2699.38 | 1692.74 | 1142.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2211.76 | 2389.44 | 2229.15 | 1462.80 | 766.35 | 0.00 | 0.00 |
February | 2992.97 | 2355.54 | 2950.05 | 1960.69 | 989.36 | 0.00 | 0.00 |
March | 2819.57 | 1721.15 | 2613.75 | 1438.84 | 1174.91 | 0.00 | 0.00 |
April | 2360.40 | 1245.75 | 2080.47 | 841.71 | 1238.76 | 0.00 | 0.00 |
May | 2187.20 | 744.96 | 1786.87 | 365.84 | 1421.04 | 0.00 | 0.00 |
June | 2397.78 | 359.56 | 1687.25 | 259.97 | 1427.28 | 0.00 | 0.00 |
July | 2767.34 | 154.95 | 1755.59 | 296.31 | 1459.28 | 0.00 | 0.00 |
August | 3669.63 | 246.45 | 2351.44 | 867.43 | 1484.02 | 0.00 | 0.00 |
September | 3425.21 | 559.09 | 2481.41 | 1245.88 | 1235.53 | 0.00 | 0.00 |
October | 4459.40 | 1103.30 | 3506.65 | 2198.97 | 1307.68 | 0.00 | 0.00 |
November | 2612.78 | 1709.19 | 2428.12 | 1456.56 | 971.56 | 0.00 | 0.00 |
December | 2491.33 | 2173.34 | 2408.35 | 1710.53 | 697.81 | 0.00 | 0.00 |
Annual Sum or Average | 2867.07 | 1223.85 | 2353.77 | 1171.47 | 1182.30 | 0.00 | 0.00 |
Minimum of Months | 2187.20 | 154.95 | 1687.25 | 259.97 | 697.81 | 0.00 | 0.00 |
Maximum of Months | 4459.40 | 2389.44 | 3506.65 | 2198.97 | 1484.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 161.58 | 353.34 | 210.03 | 115.83 | 94.21 | 0.00 | 0.00 |
February | 234.17 | 351.13 | 290.99 | 163.70 | 127.29 | 0.00 | 0.00 |
March | 322.00 | 240.30 | 336.66 | 168.32 | 168.34 | 0.00 | 0.00 |
April | 347.29 | 167.16 | 324.66 | 136.18 | 188.48 | 0.00 | 0.00 |
May | 417.02 | 93.04 | 344.49 | 114.01 | 230.47 | 0.00 | 0.00 |
June | 504.40 | 36.13 | 362.05 | 123.36 | 238.69 | 0.00 | 0.00 |
July | 536.15 | 9.10 | 348.30 | 111.24 | 237.06 | 0.00 | 0.00 |
August | 619.72 | 21.77 | 407.46 | 176.51 | 230.95 | 0.00 | 0.00 |
September | 449.31 | 62.10 | 333.60 | 154.42 | 179.17 | 0.00 | 0.00 |
October | 467.22 | 145.19 | 387.46 | 215.27 | 172.19 | 0.00 | 0.00 |
November | 200.57 | 241.37 | 224.45 | 105.96 | 118.49 | 0.00 | 0.00 |
December | 173.55 | 316.82 | 212.50 | 127.99 | 84.51 | 0.00 | 0.00 |
Annual Sum or Average | 370.46 | 168.77 | 315.46 | 142.70 | 172.76 | 0.00 | 0.00 |
Minimum of Months | 161.58 | 9.10 | 210.03 | 105.96 | 84.51 | 0.00 | 0.00 |
Maximum of Months | 619.72 | 353.34 | 407.46 | 215.27 | 238.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 52.82 | 372.18 | 112.73 | 36.76 | 75.97 | 0.00 | 0.00 |
February | 88.95 | 374.92 | 163.26 | 57.73 | 105.53 | 0.00 | 0.00 |
March | 191.14 | 241.95 | 239.39 | 90.55 | 148.84 | 0.00 | 0.00 |
April | 257.92 | 166.80 | 265.16 | 90.90 | 174.25 | 0.00 | 0.00 |
May | 367.13 | 94.28 | 318.33 | 96.82 | 221.51 | 0.00 | 0.00 |
June | 463.54 | 42.44 | 345.15 | 113.26 | 231.89 | 0.00 | 0.00 |
July | 492.86 | 12.09 | 325.52 | 98.04 | 227.48 | 0.00 | 0.00 |
August | 516.49 | 24.43 | 344.14 | 130.48 | 213.66 | 0.00 | 0.00 |
September | 317.52 | 67.90 | 247.49 | 87.11 | 160.38 | 0.00 | 0.00 |
October | 262.10 | 148.42 | 239.45 | 96.42 | 143.03 | 0.00 | 0.00 |
November | 74.22 | 248.42 | 122.33 | 27.23 | 95.10 | 0.00 | 0.00 |
December | 49.71 | 335.47 | 102.55 | 35.54 | 67.01 | 0.00 | 0.00 |
Annual Sum or Average | 262.43 | 176.32 | 235.95 | 80.26 | 155.69 | 0.00 | 0.00 |
Minimum of Months | 49.71 | 12.09 | 102.55 | 27.23 | 67.01 | 0.00 | 0.00 |
Maximum of Months | 516.49 | 374.92 | 345.15 | 130.48 | 231.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 94.27 | 99.21 | 96.37 | 63.24 | 33.13 | 0.00 | 0.00 |
February | 121.13 | 116.52 | 127.53 | 84.76 | 42.77 | 0.00 | 0.00 |
March | 112.34 | 91.65 | 113.00 | 62.20 | 50.79 | 0.00 | 0.00 |
April | 91.34 | 69.47 | 89.94 | 36.39 | 53.55 | 0.00 | 0.00 |
May | 81.54 | 44.74 | 77.25 | 15.82 | 61.43 | 0.00 | 0.00 |
June | 90.82 | 24.49 | 72.94 | 11.24 | 61.70 | 0.00 | 0.00 |
July | 107.02 | 14.00 | 75.90 | 12.81 | 63.09 | 0.00 | 0.00 |
August | 146.61 | 18.38 | 101.66 | 37.50 | 64.16 | 0.00 | 0.00 |
September | 137.16 | 35.42 | 107.27 | 53.86 | 53.41 | 0.00 | 0.00 |
October | 181.11 | 61.66 | 151.60 | 95.06 | 56.53 | 0.00 | 0.00 |
November | 104.02 | 90.43 | 104.97 | 62.97 | 42.00 | 0.00 | 0.00 |
December | 101.40 | 106.18 | 104.12 | 73.95 | 30.17 | 0.00 | 0.00 |
Annual Sum or Average | 114.10 | 64.02 | 101.76 | 50.64 | 51.11 | 0.00 | 0.00 |
Minimum of Months | 81.54 | 14.00 | 72.94 | 11.24 | 30.17 | 0.00 | 0.00 |
Maximum of Months | 181.11 | 116.52 | 151.60 | 95.06 | 64.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.80 | 114.00 | 18.55 | 0.00 | 18.55 | 0.00 | 0.00 |
February | 2.15 | 115.45 | 25.38 | 0.00 | 25.38 | 0.00 | 0.00 |
March | 12.83 | 73.57 | 35.20 | 0.00 | 35.20 | 0.00 | 0.00 |
April | 29.18 | 48.15 | 42.37 | 0.17 | 42.19 | 0.00 | 0.00 |
May | 59.14 | 25.32 | 56.35 | 2.06 | 54.29 | 0.00 | 0.00 |
June | 81.87 | 10.22 | 59.45 | 3.16 | 56.28 | 0.00 | 0.00 |
July | 94.78 | 2.53 | 57.70 | 2.25 | 55.45 | 0.00 | 0.00 |
August | 84.27 | 5.55 | 51.02 | 0.68 | 50.35 | 0.00 | 0.00 |
September | 47.43 | 17.83 | 38.42 | 0.02 | 38.40 | 0.00 | 0.00 |
October | 27.88 | 41.47 | 33.22 | 0.00 | 33.22 | 0.00 | 0.00 |
November | 6.97 | 75.03 | 23.30 | 0.00 | 23.30 | 0.00 | 0.00 |
December | 0.58 | 103.26 | 16.18 | 0.00 | 16.18 | 0.00 | 0.00 |
Annual Sum or Average | 37.57 | 52.34 | 38.17 | 0.70 | 37.47 | 0.00 | 0.00 |
Minimum of Months | 0.58 | 2.53 | 16.18 | 0.00 | 16.18 | 0.00 | 0.00 |
Maximum of Months | 94.78 | 115.45 | 59.45 | 3.16 | 56.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 161.99 | 351.17 | 210.66 | 115.09 | 95.57 | 0.00 | 0.00 |
February | 243.54 | 346.74 | 299.45 | 171.17 | 128.28 | 0.00 | 0.00 |
March | 303.41 | 241.99 | 321.06 | 154.18 | 166.88 | 0.00 | 0.00 |
April | 347.28 | 162.99 | 327.67 | 139.96 | 187.71 | 0.00 | 0.00 |
May | 431.02 | 90.36 | 356.41 | 123.32 | 233.09 | 0.00 | 0.00 |
June | 463.87 | 34.43 | 332.47 | 101.44 | 231.03 | 0.00 | 0.00 |
July | 521.39 | 8.56 | 336.90 | 103.14 | 233.76 | 0.00 | 0.00 |
August | 608.85 | 20.42 | 400.11 | 170.06 | 230.05 | 0.00 | 0.00 |
September | 454.09 | 59.90 | 338.35 | 159.34 | 179.00 | 0.00 | 0.00 |
October | 447.97 | 142.20 | 374.03 | 202.37 | 171.67 | 0.00 | 0.00 |
November | 228.66 | 239.37 | 245.51 | 122.64 | 122.87 | 0.00 | 0.00 |
December | 182.67 | 313.77 | 219.51 | 134.61 | 84.90 | 0.00 | 0.00 |
Annual Sum or Average | 367.16 | 166.66 | 313.65 | 141.31 | 172.34 | 0.00 | 0.00 |
Minimum of Months | 161.99 | 8.56 | 210.66 | 101.44 | 84.90 | 0.00 | 0.00 |
Maximum of Months | 608.85 | 351.17 | 400.11 | 202.37 | 233.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 48.54 | 365.18 | 113.35 | 36.03 | 77.33 | 0.00 | 0.00 |
February | 88.45 | 360.03 | 171.72 | 65.20 | 106.53 | 0.00 | 0.00 |
March | 171.61 | 242.25 | 223.79 | 76.41 | 147.38 | 0.00 | 0.00 |
April | 257.65 | 161.88 | 268.17 | 94.68 | 173.49 | 0.00 | 0.00 |
May | 382.33 | 91.54 | 330.26 | 106.12 | 224.13 | 0.00 | 0.00 |
June | 424.49 | 39.74 | 315.57 | 91.34 | 224.23 | 0.00 | 0.00 |
July | 476.98 | 11.45 | 314.12 | 89.94 | 224.18 | 0.00 | 0.00 |
August | 503.80 | 22.97 | 336.79 | 124.02 | 212.77 | 0.00 | 0.00 |
September | 321.44 | 64.49 | 252.25 | 92.03 | 160.22 | 0.00 | 0.00 |
October | 242.43 | 143.53 | 226.02 | 83.51 | 142.51 | 0.00 | 0.00 |
November | 98.29 | 242.18 | 143.40 | 43.91 | 99.48 | 0.00 | 0.00 |
December | 53.40 | 326.52 | 109.56 | 42.15 | 67.40 | 0.00 | 0.00 |
Annual Sum or Average | 256.94 | 171.61 | 234.14 | 78.87 | 155.27 | 0.00 | 0.00 |
Minimum of Months | 48.54 | 11.45 | 109.56 | 36.03 | 67.40 | 0.00 | 0.00 |
Maximum of Months | 503.80 | 365.18 | 336.79 | 124.02 | 224.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 185.42 | 451.42 | 248.98 | 137.02 | 111.96 | 0.00 | 0.00 |
February | 257.55 | 447.71 | 331.31 | 183.66 | 147.66 | 0.00 | 0.00 |
March | 288.40 | 310.96 | 321.09 | 134.78 | 186.32 | 0.00 | 0.00 |
April | 286.41 | 214.84 | 286.66 | 79.22 | 207.43 | 0.00 | 0.00 |
May | 333.95 | 119.77 | 289.45 | 38.74 | 250.71 | 0.00 | 0.00 |
June | 397.89 | 56.52 | 286.82 | 31.20 | 255.62 | 0.00 | 0.00 |
July | 455.22 | 21.68 | 289.44 | 32.63 | 256.81 | 0.00 | 0.00 |
August | 514.53 | 38.90 | 330.80 | 82.72 | 248.08 | 0.00 | 0.00 |
September | 420.34 | 92.77 | 315.67 | 116.75 | 198.92 | 0.00 | 0.00 |
October | 474.40 | 192.07 | 400.44 | 205.98 | 194.46 | 0.00 | 0.00 |
November | 252.04 | 306.93 | 277.92 | 136.44 | 141.49 | 0.00 | 0.00 |
December | 212.31 | 402.64 | 260.64 | 160.23 | 100.41 | 0.00 | 0.00 |
Annual Sum or Average | 340.56 | 220.08 | 303.16 | 111.25 | 191.92 | 0.00 | 0.00 |
Minimum of Months | 185.42 | 21.68 | 248.98 | 31.20 | 100.41 | 0.00 | 0.00 |
Maximum of Months | 514.53 | 451.42 | 400.44 | 205.98 | 256.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 161.40 | 351.16 | 210.03 | 115.83 | 94.21 | 0.00 | 0.00 |
February | 233.29 | 349.54 | 290.99 | 163.70 | 127.29 | 0.00 | 0.00 |
March | 319.78 | 239.01 | 336.66 | 168.32 | 168.34 | 0.00 | 0.00 |
April | 344.48 | 165.92 | 324.66 | 136.18 | 188.48 | 0.00 | 0.00 |
May | 413.09 | 92.27 | 344.49 | 114.01 | 230.47 | 0.00 | 0.00 |
June | 500.50 | 35.20 | 362.05 | 123.36 | 238.69 | 0.00 | 0.00 |
July | 532.90 | 8.44 | 348.30 | 111.24 | 237.06 | 0.00 | 0.00 |
August | 616.60 | 20.70 | 407.46 | 176.51 | 230.95 | 0.00 | 0.00 |
September | 446.66 | 60.55 | 333.60 | 154.42 | 179.17 | 0.00 | 0.00 |
October | 464.62 | 143.04 | 387.46 | 215.27 | 172.19 | 0.00 | 0.00 |
November | 200.34 | 238.84 | 224.45 | 105.96 | 118.49 | 0.00 | 0.00 |
December | 173.70 | 314.31 | 212.50 | 127.99 | 84.51 | 0.00 | 0.00 |
Annual Sum or Average | 368.32 | 167.23 | 315.46 | 142.70 | 172.76 | 0.00 | 0.00 |
Minimum of Months | 161.40 | 8.44 | 210.03 | 105.96 | 84.51 | 0.00 | 0.00 |
Maximum of Months | 616.60 | 351.16 | 407.46 | 215.27 | 238.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 53.16 | 370.04 | 112.73 | 36.76 | 75.97 | 0.00 | 0.00 |
February | 88.90 | 373.56 | 163.26 | 57.73 | 105.53 | 0.00 | 0.00 |
March | 190.22 | 240.41 | 239.39 | 90.55 | 148.84 | 0.00 | 0.00 |
April | 255.78 | 165.74 | 265.16 | 90.90 | 174.25 | 0.00 | 0.00 |
May | 362.75 | 94.68 | 318.33 | 96.82 | 221.51 | 0.00 | 0.00 |
June | 458.85 | 43.45 | 345.15 | 113.26 | 231.89 | 0.00 | 0.00 |
July | 489.74 | 11.97 | 325.52 | 98.04 | 227.48 | 0.00 | 0.00 |
August | 514.26 | 23.75 | 344.14 | 130.48 | 213.66 | 0.00 | 0.00 |
September | 315.43 | 67.31 | 247.49 | 87.11 | 160.38 | 0.00 | 0.00 |
October | 261.15 | 146.26 | 239.45 | 96.42 | 143.03 | 0.00 | 0.00 |
November | 74.85 | 245.29 | 122.33 | 27.23 | 95.10 | 0.00 | 0.00 |
December | 50.39 | 332.57 | 102.55 | 35.54 | 67.01 | 0.00 | 0.00 |
Annual Sum or Average | 260.84 | 175.13 | 235.95 | 80.26 | 155.69 | 0.00 | 0.00 |
Minimum of Months | 50.39 | 11.97 | 102.55 | 27.23 | 67.01 | 0.00 | 0.00 |
Maximum of Months | 514.26 | 373.56 | 345.15 | 130.48 | 231.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 169.64 | 183.32 | 176.70 | 115.95 | 60.75 | 0.00 | 0.00 |
February | 229.12 | 182.45 | 233.85 | 155.42 | 78.43 | 0.00 | 0.00 |
March | 216.75 | 128.72 | 207.19 | 114.06 | 93.13 | 0.00 | 0.00 |
April | 183.00 | 88.41 | 164.92 | 66.72 | 98.20 | 0.00 | 0.00 |
May | 172.27 | 48.04 | 141.64 | 29.00 | 112.65 | 0.00 | 0.00 |
June | 193.75 | 16.98 | 133.75 | 20.61 | 113.14 | 0.00 | 0.00 |
July | 227.77 | 3.61 | 139.17 | 23.49 | 115.68 | 0.00 | 0.00 |
August | 297.99 | 9.78 | 186.40 | 68.76 | 117.64 | 0.00 | 0.00 |
September | 272.06 | 30.88 | 196.70 | 98.76 | 97.94 | 0.00 | 0.00 |
October | 348.79 | 74.29 | 277.97 | 174.31 | 103.66 | 0.00 | 0.00 |
November | 202.94 | 126.24 | 192.48 | 115.46 | 77.02 | 0.00 | 0.00 |
December | 192.36 | 164.18 | 190.91 | 135.59 | 55.32 | 0.00 | 0.00 |
Annual Sum or Average | 225.65 | 87.55 | 186.58 | 92.86 | 93.72 | 0.00 | 0.00 |
Minimum of Months | 169.64 | 3.61 | 133.75 | 20.61 | 55.32 | 0.00 | 0.00 |
Maximum of Months | 348.79 | 183.32 | 277.97 | 174.31 | 117.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.36 | 1128.75 | 162.25 | 0.00 | 162.25 | 0.00 | 0.00 |
February | 10.67 | 1140.28 | 222.04 | 0.00 | 222.04 | 0.00 | 0.00 |
March | 85.61 | 756.33 | 307.98 | 0.01 | 307.98 | 0.00 | 0.00 |
April | 215.87 | 510.94 | 370.63 | 1.53 | 369.11 | 0.00 | 0.00 |
May | 460.40 | 277.55 | 492.96 | 18.04 | 474.92 | 0.00 | 0.00 |
June | 662.26 | 129.41 | 520.06 | 27.66 | 492.40 | 0.00 | 0.00 |
July | 754.97 | 53.58 | 504.77 | 19.70 | 485.07 | 0.00 | 0.00 |
August | 662.93 | 83.42 | 446.39 | 5.93 | 440.46 | 0.00 | 0.00 |
September | 371.49 | 213.42 | 336.12 | 0.20 | 335.92 | 0.00 | 0.00 |
October | 207.67 | 444.47 | 290.65 | 0.00 | 290.65 | 0.00 | 0.00 |
November | 43.16 | 773.90 | 203.86 | 0.00 | 203.86 | 0.00 | 0.00 |
December | 1.99 | 1039.59 | 141.53 | 0.00 | 141.53 | 0.00 | 0.00 |
Annual Sum or Average | 291.88 | 542.61 | 333.92 | 6.12 | 327.79 | 0.00 | 0.00 |
Minimum of Months | 1.99 | 53.58 | 141.53 | 0.00 | 141.53 | 0.00 | 0.00 |
Maximum of Months | 754.97 | 1140.28 | 520.06 | 27.66 | 492.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.52 | 1163.36 | 162.25 | 0.00 | 162.25 | 0.00 | 0.00 |
February | 8.78 | 1173.46 | 222.04 | 0.00 | 222.04 | 0.00 | 0.00 |
March | 78.45 | 780.39 | 307.98 | 0.01 | 307.98 | 0.00 | 0.00 |
April | 205.26 | 528.06 | 370.63 | 1.53 | 369.11 | 0.00 | 0.00 |
May | 447.67 | 286.53 | 492.96 | 18.04 | 474.92 | 0.00 | 0.00 |
June | 652.69 | 135.10 | 520.06 | 27.66 | 492.40 | 0.00 | 0.00 |
July | 746.42 | 57.70 | 504.77 | 19.70 | 485.07 | 0.00 | 0.00 |
August | 654.29 | 87.71 | 446.39 | 5.93 | 440.46 | 0.00 | 0.00 |
September | 362.84 | 222.17 | 336.12 | 0.20 | 335.92 | 0.00 | 0.00 |
October | 198.85 | 458.51 | 290.65 | 0.00 | 290.65 | 0.00 | 0.00 |
November | 38.64 | 800.71 | 203.86 | 0.00 | 203.86 | 0.00 | 0.00 |
December | 1.45 | 1072.35 | 141.53 | 0.00 | 141.53 | 0.00 | 0.00 |
Annual Sum or Average | 284.98 | 560.39 | 333.92 | 6.12 | 327.79 | 0.00 | 0.00 |
Minimum of Months | 1.45 | 57.70 | 141.53 | 0.00 | 141.53 | 0.00 | 0.00 |
Maximum of Months | 746.42 | 1173.46 | 520.06 | 27.66 | 492.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 217.14 | 731.76 | 324.00 | 151.11 | 172.89 | 0.00 | 0.00 |
February | 346.31 | 715.96 | 471.16 | 236.36 | 234.80 | 0.00 | 0.00 |
March | 516.29 | 504.97 | 544.82 | 230.57 | 314.24 | 0.00 | 0.00 |
April | 678.31 | 347.99 | 595.81 | 234.62 | 361.18 | 0.00 | 0.00 |
May | 923.98 | 203.78 | 686.63 | 229.43 | 457.20 | 0.00 | 0.00 |
June | 1028.41 | 95.41 | 648.01 | 192.78 | 455.23 | 0.00 | 0.00 |
July | 1146.98 | 41.17 | 650.99 | 193.07 | 457.92 | 0.00 | 0.00 |
August | 1258.62 | 60.61 | 736.86 | 294.06 | 442.80 | 0.00 | 0.00 |
September | 899.43 | 137.08 | 590.56 | 251.36 | 339.20 | 0.00 | 0.00 |
October | 776.95 | 288.09 | 600.03 | 285.87 | 314.16 | 0.00 | 0.00 |
November | 360.15 | 494.72 | 388.89 | 166.55 | 222.35 | 0.00 | 0.00 |
December | 246.70 | 651.31 | 329.06 | 176.76 | 152.30 | 0.00 | 0.00 |
Annual Sum or Average | 702.39 | 354.07 | 547.77 | 220.18 | 327.59 | 0.00 | 0.00 |
Minimum of Months | 217.14 | 41.17 | 324.00 | 151.11 | 152.30 | 0.00 | 0.00 |
Maximum of Months | 1258.62 | 731.76 | 736.86 | 294.06 | 457.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 405.67 | 806.95 | 505.43 | 295.17 | 210.26 | 0.00 | 0.00 |
February | 558.79 | 797.62 | 671.39 | 395.63 | 275.75 | 0.00 | 0.00 |
March | 588.35 | 560.43 | 632.99 | 290.34 | 342.65 | 0.00 | 0.00 |
April | 551.71 | 389.48 | 546.86 | 170.37 | 376.49 | 0.00 | 0.00 |
May | 600.66 | 220.65 | 529.55 | 80.00 | 449.55 | 0.00 | 0.00 |
June | 702.35 | 106.83 | 518.74 | 61.94 | 456.80 | 0.00 | 0.00 |
July | 805.05 | 45.86 | 527.29 | 66.54 | 460.75 | 0.00 | 0.00 |
August | 955.63 | 73.65 | 627.51 | 177.07 | 450.44 | 0.00 | 0.00 |
September | 814.69 | 167.88 | 615.93 | 251.47 | 364.47 | 0.00 | 0.00 |
October | 967.28 | 336.64 | 807.22 | 443.72 | 363.51 | 0.00 | 0.00 |
November | 528.44 | 548.67 | 559.84 | 293.91 | 265.93 | 0.00 | 0.00 |
December | 464.09 | 720.40 | 534.48 | 345.16 | 189.32 | 0.00 | 0.00 |
Annual Sum or Average | 662.88 | 395.67 | 589.42 | 238.48 | 350.94 | 0.00 | 0.00 |
Minimum of Months | 405.67 | 45.86 | 505.43 | 61.94 | 189.32 | 0.00 | 0.00 |
Maximum of Months | 967.28 | 806.95 | 807.22 | 443.72 | 460.75 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.161587E+10 | 0.161495E+10 | 0.163216E+10 | 0.107105E+10 | 0.561115E+09 | 0.00 | 0.00 |
February | 0.196978E+10 | 0.144532E+10 | 0.195097E+10 | 0.129667E+10 | 0.654301E+09 | 0.00 | 0.00 |
March | 0.205417E+10 | 0.113515E+10 | 0.191376E+10 | 0.105350E+10 | 0.860258E+09 | 0.00 | 0.00 |
April | 0.167258E+10 | 0.772889E+09 | 0.147416E+10 | 0.596411E+09 | 0.877753E+09 | 0.00 | 0.00 |
May | 0.161725E+10 | 0.455313E+09 | 0.130833E+10 | 0.267862E+09 | 0.104047E+10 | 0.00 | 0.00 |
June | 0.169721E+10 | 0.207490E+09 | 0.119554E+10 | 0.184207E+09 | 0.101133E+10 | 0.00 | 0.00 |
July | 0.200493E+10 | 88295919.91 | 0.128543E+10 | 0.216954E+09 | 0.106847E+10 | 0.00 | 0.00 |
August | 0.264424E+10 | 0.161856E+09 | 0.172171E+10 | 0.635122E+09 | 0.108658E+10 | 0.00 | 0.00 |
September | 0.240902E+10 | 0.336096E+09 | 0.175826E+10 | 0.882798E+09 | 0.875461E+09 | 0.00 | 0.00 |
October | 0.323551E+10 | 0.721673E+09 | 0.256754E+10 | 0.161007E+10 | 0.957474E+09 | 0.00 | 0.00 |
November | 0.185468E+10 | 0.108288E+10 | 0.172050E+10 | 0.103208E+10 | 0.688421E+09 | 0.00 | 0.00 |
December | 0.182048E+10 | 0.145214E+10 | 0.176337E+10 | 0.125244E+10 | 0.510933E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.245957E+11 | 0.947405E+10 | 0.202917E+11 | 0.100992E+11 | 0.101926E+11 | 0.00 | 0.00 |
Minimum of Months | 0.161587E+10 | 88295919.91 | 0.119554E+10 | 0.184207E+09 | 0.510933E+09 | 0.00 | 0.00 |
Maximum of Months | 0.323551E+10 | 0.161495E+10 | 0.256754E+10 | 0.161007E+10 | 0.108658E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.449451E+10 | 0.469049E+10 | 0.459606E+10 | 0.301600E+10 | 0.158006E+10 | 0.00 | 0.00 |
February | 0.547724E+10 | 0.420969E+10 | 0.549380E+10 | 0.365134E+10 | 0.184247E+10 | 0.00 | 0.00 |
March | 0.570900E+10 | 0.339143E+10 | 0.538903E+10 | 0.296660E+10 | 0.242243E+10 | 0.00 | 0.00 |
April | 0.463119E+10 | 0.235383E+10 | 0.415115E+10 | 0.167946E+10 | 0.247169E+10 | 0.00 | 0.00 |
May | 0.444525E+10 | 0.144418E+10 | 0.368418E+10 | 0.754282E+09 | 0.292990E+10 | 0.00 | 0.00 |
June | 0.470617E+10 | 0.680623E+09 | 0.336655E+10 | 0.518716E+09 | 0.284784E+10 | 0.00 | 0.00 |
July | 0.559003E+10 | 0.306697E+09 | 0.361968E+10 | 0.610929E+09 | 0.300875E+10 | 0.00 | 0.00 |
August | 0.739830E+10 | 0.506569E+09 | 0.484821E+10 | 0.178846E+10 | 0.305975E+10 | 0.00 | 0.00 |
September | 0.671227E+10 | 0.107772E+10 | 0.495114E+10 | 0.248590E+10 | 0.246524E+10 | 0.00 | 0.00 |
October | 0.902304E+10 | 0.221852E+10 | 0.723002E+10 | 0.453384E+10 | 0.269618E+10 | 0.00 | 0.00 |
November | 0.514090E+10 | 0.323582E+10 | 0.484482E+10 | 0.290627E+10 | 0.193855E+10 | 0.00 | 0.00 |
December | 0.506294E+10 | 0.426176E+10 | 0.496554E+10 | 0.352678E+10 | 0.143875E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.683909E+11 | 0.283773E+11 | 0.571402E+11 | 0.284386E+11 | 0.287016E+11 | 0.00 | 0.00 |
Minimum of Months | 0.444525E+10 | 0.306697E+09 | 0.336655E+10 | 0.518716E+09 | 0.143875E+10 | 0.00 | 0.00 |
Maximum of Months | 0.902304E+10 | 0.469049E+10 | 0.723002E+10 | 0.453384E+10 | 0.305975E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.592398E+10 | 0.639987E+10 | 0.597055E+10 | 0.391796E+10 | 0.205259E+10 | 0.00 | 0.00 |
February | 0.724059E+10 | 0.569852E+10 | 0.713676E+10 | 0.474329E+10 | 0.239347E+10 | 0.00 | 0.00 |
March | 0.755195E+10 | 0.460992E+10 | 0.700065E+10 | 0.385378E+10 | 0.314688E+10 | 0.00 | 0.00 |
April | 0.611816E+10 | 0.322898E+10 | 0.539258E+10 | 0.218171E+10 | 0.321087E+10 | 0.00 | 0.00 |
May | 0.585819E+10 | 0.199529E+10 | 0.478596E+10 | 0.979855E+09 | 0.380610E+10 | 0.00 | 0.00 |
June | 0.621505E+10 | 0.931974E+09 | 0.437334E+10 | 0.673841E+09 | 0.369950E+10 | 0.00 | 0.00 |
July | 0.741204E+10 | 0.415027E+09 | 0.470217E+10 | 0.793632E+09 | 0.390854E+10 | 0.00 | 0.00 |
August | 0.982874E+10 | 0.660101E+09 | 0.629810E+10 | 0.232331E+10 | 0.397479E+10 | 0.00 | 0.00 |
September | 0.887815E+10 | 0.144917E+10 | 0.643181E+10 | 0.322933E+10 | 0.320249E+10 | 0.00 | 0.00 |
October | 0.119441E+11 | 0.295507E+10 | 0.939221E+10 | 0.588972E+10 | 0.350250E+10 | 0.00 | 0.00 |
November | 0.677233E+10 | 0.443023E+10 | 0.629370E+10 | 0.377541E+10 | 0.251828E+10 | 0.00 | 0.00 |
December | 0.667277E+10 | 0.582107E+10 | 0.645052E+10 | 0.458149E+10 | 0.186902E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.904160E+11 | 0.385952E+11 | 0.742284E+11 | 0.369433E+11 | 0.372850E+11 | 0.00 | 0.00 |
Minimum of Months | 0.585819E+10 | 0.415027E+09 | 0.437334E+10 | 0.673841E+09 | 0.186902E+10 | 0.00 | 0.00 |
Maximum of Months | 0.119441E+11 | 0.639987E+10 | 0.939221E+10 | 0.588972E+10 | 0.397479E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.432784E+09 | 0.946384E+09 | 0.562551E+09 | 0.310227E+09 | 0.252324E+09 | 0.00 | 0.00 |
February | 0.566502E+09 | 0.849456E+09 | 0.703964E+09 | 0.396032E+09 | 0.307932E+09 | 0.00 | 0.00 |
March | 0.862436E+09 | 0.643625E+09 | 0.901710E+09 | 0.450816E+09 | 0.450894E+09 | 0.00 | 0.00 |
April | 0.900184E+09 | 0.433291E+09 | 0.841513E+09 | 0.352979E+09 | 0.488534E+09 | 0.00 | 0.00 |
May | 0.111695E+10 | 0.249197E+09 | 0.922671E+09 | 0.305369E+09 | 0.617303E+09 | 0.00 | 0.00 |
June | 0.130740E+10 | 93649428.71 | 0.938438E+09 | 0.319752E+09 | 0.618686E+09 | 0.00 | 0.00 |
July | 0.143602E+10 | 24361242.28 | 0.932881E+09 | 0.297952E+09 | 0.634929E+09 | 0.00 | 0.00 |
August | 0.165987E+10 | 58315812.33 | 0.109135E+10 | 0.472774E+09 | 0.618575E+09 | 0.00 | 0.00 |
September | 0.116462E+10 | 0.160965E+09 | 0.864680E+09 | 0.400269E+09 | 0.464411E+09 | 0.00 | 0.00 |
October | 0.125141E+10 | 0.388874E+09 | 0.103777E+10 | 0.576578E+09 | 0.461191E+09 | 0.00 | 0.00 |
November | 0.519870E+09 | 0.625635E+09 | 0.581769E+09 | 0.274641E+09 | 0.307129E+09 | 0.00 | 0.00 |
December | 0.464836E+09 | 0.848581E+09 | 0.569161E+09 | 0.342817E+09 | 0.226344E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.116829E+11 | 0.532234E+10 | 0.994846E+10 | 0.450021E+10 | 0.544825E+10 | 0.00 | 0.00 |
Minimum of Months | 0.432784E+09 | 24361242.28 | 0.562551E+09 | 0.274641E+09 | 0.226344E+09 | 0.00 | 0.00 |
Maximum of Months | 0.165987E+10 | 0.946384E+09 | 0.109135E+10 | 0.576578E+09 | 0.634929E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.141464E+09 | 0.996837E+09 | 0.301930E+09 | 98462657.35 | 0.203467E+09 | 0.00 | 0.00 |
February | 0.215179E+09 | 0.907010E+09 | 0.394962E+09 | 0.139658E+09 | 0.255304E+09 | 0.00 | 0.00 |
March | 0.511941E+09 | 0.648028E+09 | 0.641173E+09 | 0.242523E+09 | 0.398650E+09 | 0.00 | 0.00 |
April | 0.668527E+09 | 0.432348E+09 | 0.687289E+09 | 0.235623E+09 | 0.451665E+09 | 0.00 | 0.00 |
May | 0.983315E+09 | 0.252527E+09 | 0.852616E+09 | 0.259311E+09 | 0.593305E+09 | 0.00 | 0.00 |
June | 0.120149E+10 | 0.110012E+09 | 0.894635E+09 | 0.293574E+09 | 0.601061E+09 | 0.00 | 0.00 |
July | 0.132008E+10 | 32387513.44 | 0.871875E+09 | 0.262595E+09 | 0.609281E+09 | 0.00 | 0.00 |
August | 0.138337E+10 | 65433511.30 | 0.921743E+09 | 0.349469E+09 | 0.572274E+09 | 0.00 | 0.00 |
September | 0.823001E+09 | 0.175987E+09 | 0.641506E+09 | 0.225797E+09 | 0.415709E+09 | 0.00 | 0.00 |
October | 0.702014E+09 | 0.397533E+09 | 0.641335E+09 | 0.258241E+09 | 0.383094E+09 | 0.00 | 0.00 |
November | 0.192389E+09 | 0.643911E+09 | 0.317085E+09 | 70580626.93 | 0.246505E+09 | 0.00 | 0.00 |
December | 0.133156E+09 | 0.898530E+09 | 0.274666E+09 | 95188244.85 | 0.179478E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.827593E+10 | 0.556054E+10 | 0.744082E+10 | 0.253102E+10 | 0.490979E+10 | 0.00 | 0.00 |
Minimum of Months | 0.133156E+09 | 32387513.44 | 0.274666E+09 | 70580626.93 | 0.179478E+09 | 0.00 | 0.00 |
Maximum of Months | 0.138337E+10 | 0.996837E+09 | 0.921743E+09 | 0.349469E+09 | 0.609281E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.252492E+09 | 0.265725E+09 | 0.258114E+09 | 0.169378E+09 | 88736490.59 | 0.00 | 0.00 |
February | 0.293033E+09 | 0.281893E+09 | 0.308532E+09 | 0.205058E+09 | 0.103473E+09 | 0.00 | 0.00 |
March | 0.300890E+09 | 0.245480E+09 | 0.302648E+09 | 0.166604E+09 | 0.136044E+09 | 0.00 | 0.00 |
April | 0.236750E+09 | 0.180058E+09 | 0.233129E+09 | 94317873.29 | 0.138811E+09 | 0.00 | 0.00 |
May | 0.218409E+09 | 0.119838E+09 | 0.206904E+09 | 42360323.35 | 0.164544E+09 | 0.00 | 0.00 |
June | 0.235408E+09 | 63488679.14 | 0.189067E+09 | 29130958.40 | 0.159936E+09 | 0.00 | 0.00 |
July | 0.286649E+09 | 37492584.72 | 0.203282E+09 | 34309663.55 | 0.168973E+09 | 0.00 | 0.00 |
August | 0.392672E+09 | 49239807.84 | 0.272276E+09 | 0.100440E+09 | 0.171837E+09 | 0.00 | 0.00 |
September | 0.355529E+09 | 91810725.07 | 0.278056E+09 | 0.139608E+09 | 0.138449E+09 | 0.00 | 0.00 |
October | 0.485075E+09 | 0.165147E+09 | 0.406038E+09 | 0.254620E+09 | 0.151418E+09 | 0.00 | 0.00 |
November | 0.269631E+09 | 0.234399E+09 | 0.272085E+09 | 0.163216E+09 | 0.108869E+09 | 0.00 | 0.00 |
December | 0.271589E+09 | 0.284383E+09 | 0.278864E+09 | 0.198063E+09 | 80800618.01 | 0.00 | 0.00 |
Annual Sum or Average | 0.359813E+10 | 0.201895E+10 | 0.320900E+10 | 0.159710E+10 | 0.161189E+10 | 0.00 | 0.00 |
Minimum of Months | 0.218409E+09 | 37492584.72 | 0.189067E+09 | 29130958.40 | 80800618.01 | 0.00 | 0.00 |
Maximum of Months | 0.485075E+09 | 0.284383E+09 | 0.406038E+09 | 0.254620E+09 | 0.171837E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 2153401.85 | 0.305343E+09 | 49674962.73 | 0.00 | 49674962.73 | 0.00 | 0.00 |
February | 5205628.84 | 0.279298E+09 | 61399643.62 | 0.00 | 61399643.62 | 0.00 | 0.00 |
March | 34372280.97 | 0.197052E+09 | 94290864.36 | 1963.96 | 94288900.41 | 0.00 | 0.00 |
April | 75636488.89 | 0.124808E+09 | 0.109811E+09 | 452471.34 | 0.109358E+09 | 0.00 | 0.00 |
May | 0.158410E+09 | 67804846.40 | 0.150921E+09 | 5523301.01 | 0.145398E+09 | 0.00 | 0.00 |
June | 0.212207E+09 | 26487307.31 | 0.154082E+09 | 8195407.02 | 0.145887E+09 | 0.00 | 0.00 |
July | 0.253871E+09 | 6775660.87 | 0.154539E+09 | 6031231.87 | 0.148507E+09 | 0.00 | 0.00 |
August | 0.225718E+09 | 14858196.39 | 0.136664E+09 | 1815851.67 | 0.134848E+09 | 0.00 | 0.00 |
September | 0.122947E+09 | 46202933.90 | 99584946.32 | 57893.59 | 99527052.73 | 0.00 | 0.00 |
October | 74683918.48 | 0.111078E+09 | 88983113.67 | 0.00 | 88983113.67 | 0.00 | 0.00 |
November | 18065266.28 | 0.194469E+09 | 60399659.90 | 0.00 | 60399659.90 | 0.00 | 0.00 |
December | 1558693.53 | 0.276560E+09 | 43329787.27 | 0.00 | 43329787.27 | 0.00 | 0.00 |
Annual Sum or Average | 0.118483E+10 | 0.165074E+10 | 0.120368E+10 | 22078120.45 | 0.118160E+10 | 0.00 | 0.00 |
Minimum of Months | 1558693.53 | 6775660.87 | 43329787.27 | 0.00 | 43329787.27 | 0.00 | 0.00 |
Maximum of Months | 0.253871E+09 | 0.305343E+09 | 0.154539E+09 | 8195407.02 | 0.148507E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.433879E+09 | 0.940580E+09 | 0.564229E+09 | 0.308260E+09 | 0.255969E+09 | 0.00 | 0.00 |
February | 0.589170E+09 | 0.838835E+09 | 0.724436E+09 | 0.414096E+09 | 0.310339E+09 | 0.00 | 0.00 |
March | 0.812644E+09 | 0.648148E+09 | 0.859923E+09 | 0.412946E+09 | 0.446977E+09 | 0.00 | 0.00 |
April | 0.900147E+09 | 0.422461E+09 | 0.849316E+09 | 0.362766E+09 | 0.486550E+09 | 0.00 | 0.00 |
May | 0.115445E+10 | 0.242022E+09 | 0.954617E+09 | 0.330301E+09 | 0.624316E+09 | 0.00 | 0.00 |
June | 0.120235E+10 | 89240029.37 | 0.861763E+09 | 0.262942E+09 | 0.598821E+09 | 0.00 | 0.00 |
July | 0.139648E+10 | 22919623.61 | 0.902351E+09 | 0.276256E+09 | 0.626094E+09 | 0.00 | 0.00 |
August | 0.163073E+10 | 54701501.95 | 0.107165E+10 | 0.455479E+09 | 0.616174E+09 | 0.00 | 0.00 |
September | 0.117701E+10 | 0.155272E+09 | 0.876994E+09 | 0.413014E+09 | 0.463980E+09 | 0.00 | 0.00 |
October | 0.119984E+10 | 0.380861E+09 | 0.100181E+10 | 0.542024E+09 | 0.459791E+09 | 0.00 | 0.00 |
November | 0.592698E+09 | 0.620459E+09 | 0.636369E+09 | 0.317881E+09 | 0.318487E+09 | 0.00 | 0.00 |
December | 0.489255E+09 | 0.840393E+09 | 0.587937E+09 | 0.360535E+09 | 0.227402E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115787E+11 | 0.525589E+10 | 0.989140E+10 | 0.445650E+10 | 0.543490E+10 | 0.00 | 0.00 |
Minimum of Months | 0.433879E+09 | 22919623.61 | 0.564229E+09 | 0.262942E+09 | 0.227402E+09 | 0.00 | 0.00 |
Maximum of Months | 0.163073E+10 | 0.940580E+09 | 0.107165E+10 | 0.542024E+09 | 0.626094E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.129996E+09 | 0.978108E+09 | 0.303607E+09 | 96495417.54 | 0.207112E+09 | 0.00 | 0.00 |
February | 0.213977E+09 | 0.870995E+09 | 0.415434E+09 | 0.157722E+09 | 0.257711E+09 | 0.00 | 0.00 |
March | 0.459648E+09 | 0.648856E+09 | 0.599386E+09 | 0.204653E+09 | 0.394734E+09 | 0.00 | 0.00 |
April | 0.667818E+09 | 0.419587E+09 | 0.695092E+09 | 0.245411E+09 | 0.449682E+09 | 0.00 | 0.00 |
May | 0.102402E+10 | 0.245174E+09 | 0.884562E+09 | 0.284243E+09 | 0.600318E+09 | 0.00 | 0.00 |
June | 0.110029E+10 | 0.103004E+09 | 0.817960E+09 | 0.236764E+09 | 0.581196E+09 | 0.00 | 0.00 |
July | 0.127755E+10 | 30675499.61 | 0.841345E+09 | 0.240899E+09 | 0.600446E+09 | 0.00 | 0.00 |
August | 0.134937E+10 | 61528026.96 | 0.902047E+09 | 0.332174E+09 | 0.569873E+09 | 0.00 | 0.00 |
September | 0.833176E+09 | 0.167171E+09 | 0.653820E+09 | 0.238542E+09 | 0.415277E+09 | 0.00 | 0.00 |
October | 0.649334E+09 | 0.384434E+09 | 0.605381E+09 | 0.223686E+09 | 0.381695E+09 | 0.00 | 0.00 |
November | 0.254757E+09 | 0.627740E+09 | 0.371685E+09 | 0.113821E+09 | 0.257864E+09 | 0.00 | 0.00 |
December | 0.143019E+09 | 0.874550E+09 | 0.293443E+09 | 0.112907E+09 | 0.180536E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.810296E+10 | 0.541182E+10 | 0.738376E+10 | 0.248732E+10 | 0.489644E+10 | 0.00 | 0.00 |
Minimum of Months | 0.129996E+09 | 30675499.61 | 0.293443E+09 | 96495417.54 | 0.180536E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134937E+10 | 0.978108E+09 | 0.902047E+09 | 0.332174E+09 | 0.600446E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.496628E+09 | 0.120908E+10 | 0.666875E+09 | 0.366995E+09 | 0.299880E+09 | 0.00 | 0.00 |
February | 0.623075E+09 | 0.108311E+10 | 0.801514E+09 | 0.444304E+09 | 0.357210E+09 | 0.00 | 0.00 |
March | 0.772443E+09 | 0.832885E+09 | 0.860019E+09 | 0.360988E+09 | 0.499031E+09 | 0.00 | 0.00 |
April | 0.742380E+09 | 0.556875E+09 | 0.743012E+09 | 0.205341E+09 | 0.537671E+09 | 0.00 | 0.00 |
May | 0.894448E+09 | 0.320805E+09 | 0.775251E+09 | 0.103748E+09 | 0.671502E+09 | 0.00 | 0.00 |
June | 0.103133E+10 | 0.146512E+09 | 0.743449E+09 | 80872685.50 | 0.662577E+09 | 0.00 | 0.00 |
July | 0.121926E+10 | 58076113.59 | 0.775239E+09 | 87405170.35 | 0.687834E+09 | 0.00 | 0.00 |
August | 0.137812E+10 | 0.104200E+09 | 0.886007E+09 | 0.221558E+09 | 0.664449E+09 | 0.00 | 0.00 |
September | 0.108953E+10 | 0.240470E+09 | 0.818205E+09 | 0.302616E+09 | 0.515588E+09 | 0.00 | 0.00 |
October | 0.127062E+10 | 0.514428E+09 | 0.107254E+10 | 0.551690E+09 | 0.520848E+09 | 0.00 | 0.00 |
November | 0.653300E+09 | 0.795565E+09 | 0.720378E+09 | 0.353643E+09 | 0.366735E+09 | 0.00 | 0.00 |
December | 0.568656E+09 | 0.107842E+10 | 0.698088E+09 | 0.429149E+09 | 0.268939E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107398E+11 | 0.694043E+10 | 0.956058E+10 | 0.350831E+10 | 0.605227E+10 | 0.00 | 0.00 |
Minimum of Months | 0.496628E+09 | 58076113.59 | 0.666875E+09 | 80872685.50 | 0.268939E+09 | 0.00 | 0.00 |
Maximum of Months | 0.137812E+10 | 0.120908E+10 | 0.107254E+10 | 0.551690E+09 | 0.687834E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.432300E+09 | 0.940556E+09 | 0.562551E+09 | 0.310227E+09 | 0.252324E+09 | 0.00 | 0.00 |
February | 0.564366E+09 | 0.845617E+09 | 0.703964E+09 | 0.396032E+09 | 0.307932E+09 | 0.00 | 0.00 |
March | 0.856500E+09 | 0.640166E+09 | 0.901710E+09 | 0.450816E+09 | 0.450894E+09 | 0.00 | 0.00 |
April | 0.892883E+09 | 0.430075E+09 | 0.841513E+09 | 0.352979E+09 | 0.488534E+09 | 0.00 | 0.00 |
May | 0.110643E+10 | 0.247127E+09 | 0.922671E+09 | 0.305369E+09 | 0.617303E+09 | 0.00 | 0.00 |
June | 0.129731E+10 | 91248819.34 | 0.938438E+09 | 0.319752E+09 | 0.618686E+09 | 0.00 | 0.00 |
July | 0.142731E+10 | 22607141.02 | 0.932881E+09 | 0.297952E+09 | 0.634929E+09 | 0.00 | 0.00 |
August | 0.165151E+10 | 55432115.96 | 0.109135E+10 | 0.472774E+09 | 0.618575E+09 | 0.00 | 0.00 |
September | 0.115774E+10 | 0.156939E+09 | 0.864680E+09 | 0.400269E+09 | 0.464411E+09 | 0.00 | 0.00 |
October | 0.124443E+10 | 0.383129E+09 | 0.103777E+10 | 0.576578E+09 | 0.461191E+09 | 0.00 | 0.00 |
November | 0.519276E+09 | 0.619062E+09 | 0.581769E+09 | 0.274641E+09 | 0.307129E+09 | 0.00 | 0.00 |
December | 0.465250E+09 | 0.841853E+09 | 0.569161E+09 | 0.342817E+09 | 0.226344E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.116153E+11 | 0.527381E+10 | 0.994846E+10 | 0.450021E+10 | 0.544825E+10 | 0.00 | 0.00 |
Minimum of Months | 0.432300E+09 | 22607141.02 | 0.562551E+09 | 0.274641E+09 | 0.226344E+09 | 0.00 | 0.00 |
Maximum of Months | 0.165151E+10 | 0.940556E+09 | 0.109135E+10 | 0.576578E+09 | 0.634929E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.142377E+09 | 0.991126E+09 | 0.301930E+09 | 98462657.35 | 0.203467E+09 | 0.00 | 0.00 |
February | 0.215064E+09 | 0.903726E+09 | 0.394962E+09 | 0.139658E+09 | 0.255304E+09 | 0.00 | 0.00 |
March | 0.509472E+09 | 0.643904E+09 | 0.641173E+09 | 0.242523E+09 | 0.398650E+09 | 0.00 | 0.00 |
April | 0.662986E+09 | 0.429586E+09 | 0.687289E+09 | 0.235623E+09 | 0.451665E+09 | 0.00 | 0.00 |
May | 0.971599E+09 | 0.253597E+09 | 0.852616E+09 | 0.259311E+09 | 0.593305E+09 | 0.00 | 0.00 |
June | 0.118934E+10 | 0.112629E+09 | 0.894635E+09 | 0.293574E+09 | 0.601061E+09 | 0.00 | 0.00 |
July | 0.131171E+10 | 32051636.50 | 0.871875E+09 | 0.262595E+09 | 0.609281E+09 | 0.00 | 0.00 |
August | 0.137739E+10 | 63602251.49 | 0.921743E+09 | 0.349469E+09 | 0.572274E+09 | 0.00 | 0.00 |
September | 0.817603E+09 | 0.174459E+09 | 0.641506E+09 | 0.225797E+09 | 0.415709E+09 | 0.00 | 0.00 |
October | 0.699457E+09 | 0.391736E+09 | 0.641335E+09 | 0.258241E+09 | 0.383094E+09 | 0.00 | 0.00 |
November | 0.194014E+09 | 0.635804E+09 | 0.317085E+09 | 70580626.93 | 0.246505E+09 | 0.00 | 0.00 |
December | 0.134973E+09 | 0.890764E+09 | 0.274666E+09 | 95188244.85 | 0.179478E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.822598E+10 | 0.552298E+10 | 0.744082E+10 | 0.253102E+10 | 0.490979E+10 | 0.00 | 0.00 |
Minimum of Months | 0.134973E+09 | 32051636.50 | 0.274666E+09 | 70580626.93 | 0.179478E+09 | 0.00 | 0.00 |
Maximum of Months | 0.137739E+10 | 0.991126E+09 | 0.921743E+09 | 0.349469E+09 | 0.609281E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.454368E+09 | 0.491010E+09 | 0.473281E+09 | 0.310573E+09 | 0.162708E+09 | 0.00 | 0.00 |
February | 0.554285E+09 | 0.441390E+09 | 0.565726E+09 | 0.375997E+09 | 0.189730E+09 | 0.00 | 0.00 |
March | 0.580553E+09 | 0.344758E+09 | 0.554938E+09 | 0.305486E+09 | 0.249452E+09 | 0.00 | 0.00 |
April | 0.474337E+09 | 0.229166E+09 | 0.427468E+09 | 0.172942E+09 | 0.254525E+09 | 0.00 | 0.00 |
May | 0.461409E+09 | 0.128679E+09 | 0.379382E+09 | 77672293.27 | 0.301710E+09 | 0.00 | 0.00 |
June | 0.502200E+09 | 44016097.34 | 0.346674E+09 | 53414803.41 | 0.293260E+09 | 0.00 | 0.00 |
July | 0.610069E+09 | 9667503.40 | 0.372740E+09 | 62910526.60 | 0.309830E+09 | 0.00 | 0.00 |
August | 0.798125E+09 | 26194167.46 | 0.499248E+09 | 0.184167E+09 | 0.315081E+09 | 0.00 | 0.00 |
September | 0.705190E+09 | 80033758.63 | 0.509846E+09 | 0.255986E+09 | 0.253861E+09 | 0.00 | 0.00 |
October | 0.934208E+09 | 0.198987E+09 | 0.744515E+09 | 0.466873E+09 | 0.277642E+09 | 0.00 | 0.00 |
November | 0.526027E+09 | 0.327201E+09 | 0.498897E+09 | 0.299274E+09 | 0.199623E+09 | 0.00 | 0.00 |
December | 0.515223E+09 | 0.439746E+09 | 0.511328E+09 | 0.363171E+09 | 0.148157E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.711599E+10 | 0.276085E+10 | 0.588404E+10 | 0.292847E+10 | 0.295558E+10 | 0.00 | 0.00 |
Minimum of Months | 0.454368E+09 | 9667503.40 | 0.346674E+09 | 53414803.41 | 0.148157E+09 | 0.00 | 0.00 |
Maximum of Months | 0.934208E+09 | 0.491010E+09 | 0.744515E+09 | 0.466873E+09 | 0.315081E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 6327816.72 | 0.302326E+10 | 0.434582E+09 | 0.00 | 0.434582E+09 | 0.00 | 0.00 |
February | 25804686.09 | 0.275856E+10 | 0.537155E+09 | 0.00 | 0.537155E+09 | 0.00 | 0.00 |
March | 0.229288E+09 | 0.202576E+10 | 0.824904E+09 | 17181.70 | 0.824887E+09 | 0.00 | 0.00 |
April | 0.559528E+09 | 0.132436E+10 | 0.960679E+09 | 3958449.54 | 0.956721E+09 | 0.00 | 0.00 |
May | 0.123314E+10 | 0.743398E+09 | 0.132034E+10 | 48320648.33 | 0.127202E+10 | 0.00 | 0.00 |
June | 0.171658E+10 | 0.335436E+09 | 0.134799E+10 | 71697591.63 | 0.127629E+10 | 0.00 | 0.00 |
July | 0.202210E+10 | 0.143517E+09 | 0.135198E+10 | 52764286.00 | 0.129922E+10 | 0.00 | 0.00 |
August | 0.177558E+10 | 0.223431E+09 | 0.119561E+10 | 15885994.55 | 0.117972E+10 | 0.00 | 0.00 |
September | 0.962905E+09 | 0.553179E+09 | 0.871220E+09 | 506482.57 | 0.870713E+09 | 0.00 | 0.00 |
October | 0.556231E+09 | 0.119046E+10 | 0.778470E+09 | 0.00 | 0.778470E+09 | 0.00 | 0.00 |
November | 0.111864E+09 | 0.200596E+10 | 0.528407E+09 | 0.00 | 0.528407E+09 | 0.00 | 0.00 |
December | 5329751.12 | 0.278444E+10 | 0.379071E+09 | 0.00 | 0.379071E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.920467E+10 | 0.171118E+11 | 0.105304E+11 | 0.193151E+09 | 0.103373E+11 | 0.00 | 0.00 |
Minimum of Months | 5329751.12 | 0.143517E+09 | 0.379071E+09 | 0.00 | 0.379071E+09 | 0.00 | 0.00 |
Maximum of Months | 0.202210E+10 | 0.302326E+10 | 0.135198E+10 | 71697591.63 | 0.129922E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 4065217.34 | 0.311594E+10 | 0.434582E+09 | 0.00 | 0.434582E+09 | 0.00 | 0.00 |
February | 21243687.90 | 0.283883E+10 | 0.537155E+09 | 0.00 | 0.537155E+09 | 0.00 | 0.00 |
March | 0.210108E+09 | 0.209019E+10 | 0.824904E+09 | 17181.70 | 0.824887E+09 | 0.00 | 0.00 |
April | 0.532038E+09 | 0.136873E+10 | 0.960679E+09 | 3958449.54 | 0.956721E+09 | 0.00 | 0.00 |
May | 0.119904E+10 | 0.767451E+09 | 0.132034E+10 | 48320648.33 | 0.127202E+10 | 0.00 | 0.00 |
June | 0.169178E+10 | 0.350188E+09 | 0.134799E+10 | 71697591.63 | 0.127629E+10 | 0.00 | 0.00 |
July | 0.199922E+10 | 0.154541E+09 | 0.135198E+10 | 52764286.00 | 0.129922E+10 | 0.00 | 0.00 |
August | 0.175245E+10 | 0.234910E+09 | 0.119561E+10 | 15885994.55 | 0.117972E+10 | 0.00 | 0.00 |
September | 0.940470E+09 | 0.575868E+09 | 0.871220E+09 | 506482.57 | 0.870713E+09 | 0.00 | 0.00 |
October | 0.532605E+09 | 0.122806E+10 | 0.778470E+09 | 0.00 | 0.778470E+09 | 0.00 | 0.00 |
November | 0.100161E+09 | 0.207544E+10 | 0.528407E+09 | 0.00 | 0.528407E+09 | 0.00 | 0.00 |
December | 3885915.31 | 0.287218E+10 | 0.379071E+09 | 0.00 | 0.379071E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.898707E+10 | 0.176723E+11 | 0.105304E+11 | 0.193151E+09 | 0.103373E+11 | 0.00 | 0.00 |
Minimum of Months | 3885915.31 | 0.154541E+09 | 0.379071E+09 | 0.00 | 0.379071E+09 | 0.00 | 0.00 |
Maximum of Months | 0.199922E+10 | 0.311594E+10 | 0.135198E+10 | 71697591.63 | 0.129922E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.581592E+09 | 0.195995E+10 | 0.867802E+09 | 0.404742E+09 | 0.463060E+09 | 0.00 | 0.00 |
February | 0.837785E+09 | 0.173206E+10 | 0.113982E+10 | 0.571796E+09 | 0.568025E+09 | 0.00 | 0.00 |
March | 0.138284E+10 | 0.135252E+10 | 0.145924E+10 | 0.617570E+09 | 0.841672E+09 | 0.00 | 0.00 |
April | 0.175818E+10 | 0.901992E+09 | 0.154433E+10 | 0.608142E+09 | 0.936188E+09 | 0.00 | 0.00 |
May | 0.247479E+10 | 0.545811E+09 | 0.183908E+10 | 0.614505E+09 | 0.122457E+10 | 0.00 | 0.00 |
June | 0.266564E+10 | 0.247295E+09 | 0.167963E+10 | 0.499674E+09 | 0.117996E+10 | 0.00 | 0.00 |
July | 0.307208E+10 | 0.110282E+09 | 0.174360E+10 | 0.517122E+09 | 0.122648E+10 | 0.00 | 0.00 |
August | 0.337108E+10 | 0.162340E+09 | 0.197360E+10 | 0.787607E+09 | 0.118599E+10 | 0.00 | 0.00 |
September | 0.233132E+10 | 0.355320E+09 | 0.153074E+10 | 0.651522E+09 | 0.879216E+09 | 0.00 | 0.00 |
October | 0.208098E+10 | 0.771632E+09 | 0.160713E+10 | 0.765679E+09 | 0.841447E+09 | 0.00 | 0.00 |
November | 0.933520E+09 | 0.128232E+10 | 0.100801E+10 | 0.431686E+09 | 0.576325E+09 | 0.00 | 0.00 |
December | 0.660769E+09 | 0.174447E+10 | 0.881346E+09 | 0.473426E+09 | 0.407920E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.221506E+11 | 0.111660E+11 | 0.172743E+11 | 0.694347E+10 | 0.103309E+11 | 0.00 | 0.00 |
Minimum of Months | 0.581592E+09 | 0.110282E+09 | 0.867802E+09 | 0.404742E+09 | 0.407920E+09 | 0.00 | 0.00 |
Maximum of Months | 0.337108E+10 | 0.195995E+10 | 0.197360E+10 | 0.787607E+09 | 0.122648E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.108656E+10 | 0.216132E+10 | 0.135374E+10 | 0.790580E+09 | 0.563158E+09 | 0.00 | 0.00 |
February | 0.135183E+10 | 0.192959E+10 | 0.162422E+10 | 0.957120E+09 | 0.667105E+09 | 0.00 | 0.00 |
March | 0.157585E+10 | 0.150106E+10 | 0.169540E+10 | 0.777636E+09 | 0.917766E+09 | 0.00 | 0.00 |
April | 0.143004E+10 | 0.100953E+10 | 0.141746E+10 | 0.441590E+09 | 0.975874E+09 | 0.00 | 0.00 |
May | 0.160880E+10 | 0.590986E+09 | 0.141835E+10 | 0.214283E+09 | 0.120407E+10 | 0.00 | 0.00 |
June | 0.182049E+10 | 0.276900E+09 | 0.134457E+10 | 0.160548E+09 | 0.118402E+10 | 0.00 | 0.00 |
July | 0.215626E+10 | 0.122825E+09 | 0.141229E+10 | 0.178230E+09 | 0.123406E+10 | 0.00 | 0.00 |
August | 0.255955E+10 | 0.197264E+09 | 0.168072E+10 | 0.474253E+09 | 0.120647E+10 | 0.00 | 0.00 |
September | 0.211167E+10 | 0.435157E+09 | 0.159650E+10 | 0.651799E+09 | 0.944698E+09 | 0.00 | 0.00 |
October | 0.259078E+10 | 0.901647E+09 | 0.216206E+10 | 0.118845E+10 | 0.973613E+09 | 0.00 | 0.00 |
November | 0.136972E+10 | 0.142215E+10 | 0.145111E+10 | 0.761817E+09 | 0.689291E+09 | 0.00 | 0.00 |
December | 0.124302E+10 | 0.192953E+10 | 0.143156E+10 | 0.924471E+09 | 0.507087E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.209046E+11 | 0.124780E+11 | 0.185880E+11 | 0.752078E+10 | 0.110672E+11 | 0.00 | 0.00 |
Minimum of Months | 0.108656E+10 | 0.122825E+09 | 0.134457E+10 | 0.160548E+09 | 0.507087E+09 | 0.00 | 0.00 |
Maximum of Months | 0.259078E+10 | 0.216132E+10 | 0.216206E+10 | 0.118845E+10 | 0.123406E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.7 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.6 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.43 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 8.00 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.31 | 9.14 | 4.42 | 7.77 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.08 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.76 | 20.26 | 4.06 | 17.39 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.84 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.96 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.03 | 7.95 | 4.86 | 2.64 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 4.98 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.91 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.49 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.6 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.76 | 20.26 | 5.65 | 17.39 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.36 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.34 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.40 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 18.00 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.28 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.31 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.23 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.34 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.54 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.57 | 8.50 | 3.60 | 6.15 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.65 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.36 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.28 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.6 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.3 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.6 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.57 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.35 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.47 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.2 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.6 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.3 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.99 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.70 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.43 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.96 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.10 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.84 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.57 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.76 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.10 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.70 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.96 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.17 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.57 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770540E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162616781.8 | 81.21 | 0.00 | 0.00 |
February | 0.696287E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146907615.9 | 81.21 | 0.00 | 0.00 |
March | 0.770384E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162377684.8 | 81.21 | 0.00 | 0.00 |
April | 0.746556E+10 | -0.730860E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156956173.1 | 81.21 | 0.00 | 0.00 |
May | 0.770477E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161965594.0 | 81.21 | 0.00 | 0.00 |
June | 0.745704E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156508964.2 | 81.21 | 0.00 | 0.00 |
July | 0.771250E+10 | -0.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161661612.7 | 81.21 | 0.00 | 0.00 |
August | 0.770442E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161625201.4 | 81.21 | 0.00 | 0.00 |
September | 0.746655E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156600711.2 | 81.21 | 0.00 | 0.00 |
October | 0.770350E+10 | -0.754145E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162056539.6 | 81.21 | 0.00 | 0.00 |
November | 0.744956E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157127027.1 | 81.21 | 0.00 | 0.00 |
December | 0.771337E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162516125.6 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907494E+11 | -0.888405E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190892E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696287E+10 | -0.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162616781.8 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771337E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146907615.9 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYSLAUNDRY HPWH TANK
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.675920E+11 | -0.119226E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -879553526.1 | 81.67 | 0.00 | 0.00 |
February | 0.644977E+11 | -0.108438E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -804536045.5 | 81.67 | 0.00 | 0.00 |
March | 0.601803E+11 | -0.118172E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -845955030.1 | 81.67 | 0.00 | 0.00 |
April | 0.473379E+11 | -0.110276E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -778985284.3 | 81.67 | 0.00 | 0.00 |
May | 0.370866E+11 | -0.108516E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -765172156.1 | 81.67 | 0.00 | 0.00 |
June | 0.233861E+11 | -0.100002E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -698442467.8 | 81.68 | 0.00 | 0.00 |
July | 0.161925E+11 | -0.998143E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -695694438.8 | 81.68 | 0.00 | 0.00 |
August | 0.174105E+11 | -0.988899E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -698222260.1 | 81.68 | 0.00 | 0.00 |
September | 0.239715E+11 | -0.975879E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -711764269.1 | 81.68 | 0.00 | 0.00 |
October | 0.358243E+11 | -0.105126E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -781452914.8 | 81.67 | 0.00 | 0.00 |
November | 0.488709E+11 | -0.107006E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -805498110.9 | 81.67 | 0.00 | 0.00 |
December | 0.616465E+11 | -0.115720E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -863404081.0 | 81.67 | 0.00 | 0.00 |
Annual Sum or Average | 0.503997E+12 | -0.128877E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.932868E+10 | 81.68 | 0.00 | 0.00 |
Minimum of Months | 0.161925E+11 | -0.119226E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -879553526.1 | 81.67 | 0.00 | 0.00 |
Maximum of Months | 0.675920E+11 | -0.975879E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -695694438.8 | 81.68 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 HPWH TANK
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | -0.124709E+10 | -0.728220E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.143907E+10 | 59.19 | 0.00 | 0.00 |
February | -482541520.8 | -0.664084E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.132274E+10 | 59.13 | 0.00 | 0.00 |
March | -0.195230E+10 | -0.720460E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.135928E+10 | 59.23 | 0.00 | 0.00 |
April | -0.233533E+10 | -0.662045E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.122148E+10 | 59.29 | 0.00 | 0.00 |
May | -0.263661E+10 | -0.637481E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.116767E+10 | 59.32 | 0.00 | 0.00 |
June | -0.262546E+10 | -0.573915E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.103006E+10 | 59.36 | 0.00 | 0.00 |
July | -0.247664E+10 | -0.562054E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.100283E+10 | 59.39 | 0.00 | 0.00 |
August | -0.242478E+10 | -0.554648E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.100901E+10 | 59.40 | 0.00 | 0.00 |
September | -0.242776E+10 | -0.552793E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.106281E+10 | 59.38 | 0.00 | 0.00 |
October | -0.240121E+10 | -0.607850E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.120779E+10 | 59.35 | 0.00 | 0.00 |
November | -0.196627E+10 | -0.633502E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.128615E+10 | 59.31 | 0.00 | 0.00 |
December | -0.157102E+10 | -0.698473E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.140127E+10 | 59.23 | 0.00 | 0.00 |
Annual Sum or Average | -0.245470E+11 | -0.759552E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.145102E+11 | 59.30 | 0.00 | 0.00 |
Minimum of Months | -0.263661E+10 | -0.728220E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.143907E+10 | 59.13 | 0.00 | 0.00 |
Maximum of Months | -482541520.8 | -0.552793E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.100283E+10 | 59.40 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.87 | 0.86 | 01-JAN-07:49 | 5176.91 | 36.75 | 196.33 | 243.00 | 2471.04 | 33.51 | 185.67 | 185.33 |
February | 216.00 | 0.87 | 0.86 | 01-FEB-07:49 | 7576.97 | 37.36 | 208.17 | 257.67 | 1072.58 | 26.98 | 197.17 | 220.83 |
March | 275.00 | 0.87 | 0.86 | 01-MAR-06:00 | 3660.64 | 25.45 | 145.50 | 324.17 | 663.29 | 22.31 | 202.17 | 250.00 |
April | 261.17 | 0.87 | 0.86 | 01-APR-14:39 | 1301.07 | 20.12 | 41.33 | 339.33 | 530.10 | 21.86 | 192.00 | 269.33 |
May | 372.00 | 0.87 | 0.86 | 01-MAY-06:19 | 1177.25 | 19.83 | 26.50 | 392.33 | 467.29 | 21.55 | 232.17 | 306.83 |
June | 351.83 | 0.87 | 0.86 | 01-JUN-05:00 | 1116.40 | 19.73 | 24.50 | 382.00 | 450.38 | 21.48 | 237.00 | 308.50 |
July | 365.17 | 0.87 | 0.86 | 01-JUL-06:19 | 1244.71 | 19.90 | 61.67 | 389.83 | 492.77 | 21.64 | 249.67 | 313.00 |
August | 389.17 | 0.87 | 0.86 | 01-AUG-06:30 | 1332.88 | 20.19 | 89.83 | 371.00 | 539.25 | 21.91 | 297.17 | 315.17 |
September | 285.33 | 0.87 | 0.86 | 01-SEP-06:49 | 1483.28 | 20.30 | 56.67 | 324.17 | 598.62 | 22.07 | 221.83 | 266.67 |
October | 305.50 | 0.87 | 0.86 | 01-OCT-14:39 | 7320.58 | 35.44 | 274.17 | 307.17 | 916.73 | 24.67 | 272.50 | 277.50 |
November | 240.83 | 0.87 | 0.86 | 01-NOV-06:00 | 5136.25 | 36.19 | 234.83 | 257.17 | 1363.21 | 29.63 | 220.67 | 224.67 |
December | 211.17 | 0.87 | 0.86 | 01-DEC-07:40 | 4808.36 | 37.73 | 207.67 | 245.00 | 3714.00 | 37.71 | 204.50 | 201.17 |
Annual Sum or Average | 3472.67 | 0.87 | 3090.38 | 26.03 | 1567.17 | 3832.83 | 959.22 | 24.56 | 2712.50 | 3139.00 | ||
Minimum of Months | 199.50 | 0.87 | 0.86 | 1116.40 | 19.73 | 24.50 | 243.00 | 450.38 | 21.48 | 185.67 | 185.33 | |
Maximum of Months | 389.17 | 0.87 | 0.86 | 7576.97 | 37.73 | 274.17 | 392.33 | 3714.00 | 37.71 | 297.17 | 315.17 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.25 | 0.22 | 01-JAN-07:49 | 5567.01 | 36.81 | 196.50 | 257.17 | 2861.75 | 33.49 | 186.83 | 213.00 |
February | 216.00 | 0.24 | 0.22 | 01-FEB-07:40 | 8023.35 | 37.45 | 208.33 | 267.00 | 1518.58 | 26.71 | 185.83 | 243.33 |
March | 275.00 | 0.25 | 0.22 | 01-MAR-06:00 | 4025.46 | 25.63 | 139.50 | 334.50 | 1026.62 | 22.39 | 194.17 | 302.17 |
April | 261.17 | 0.25 | 0.22 | 01-APR-06:30 | 1583.06 | 20.48 | 67.00 | 354.33 | 811.38 | 22.06 | 196.50 | 314.67 |
May | 372.00 | 0.25 | 0.22 | 01-MAY-05:49 | 1380.02 | 20.47 | 113.67 | 407.33 | 669.35 | 22.00 | 253.67 | 364.83 |
June | 351.83 | 0.25 | 0.22 | 01-JUN-05:30 | 1310.30 | 20.39 | 114.00 | 400.67 | 643.63 | 21.94 | 259.00 | 355.67 |
July | 365.17 | 0.25 | 0.22 | 01-JUL-05:30 | 1451.21 | 20.54 | 128.50 | 410.17 | 698.52 | 22.09 | 279.33 | 359.33 |
August | 389.17 | 0.26 | 0.22 | 01-AUG-05:49 | 1593.31 | 20.62 | 147.17 | 381.17 | 798.93 | 22.18 | 305.83 | 352.00 |
September | 285.33 | 0.25 | 0.22 | 01-SEP-06:10 | 1809.01 | 20.54 | 81.00 | 337.17 | 923.45 | 22.17 | 215.50 | 302.00 |
October | 305.50 | 0.24 | 0.22 | 01-OCT-14:39 | 7766.46 | 35.50 | 272.33 | 315.67 | 1361.21 | 24.56 | 278.67 | 297.50 |
November | 240.83 | 0.24 | 0.22 | 01-NOV-06:49 | 5500.00 | 36.26 | 234.83 | 265.00 | 1723.72 | 29.57 | 222.00 | 247.33 |
December | 211.17 | 0.25 | 0.22 | 01-DEC-07:30 | 5196.41 | 37.79 | 207.83 | 254.50 | 4100.33 | 37.72 | 204.00 | 228.83 |
Annual Sum or Average | 3472.67 | 0.25 | 3397.73 | 26.37 | 1910.67 | 3984.67 | 1265.58 | 24.73 | 2781.33 | 3580.67 | ||
Minimum of Months | 199.50 | 0.24 | 0.22 | 1310.30 | 20.39 | 67.00 | 254.50 | 643.63 | 21.94 | 185.83 | 213.00 | |
Maximum of Months | 389.17 | 0.26 | 0.22 | 8023.35 | 37.79 | 272.33 | 410.17 | 4100.33 | 37.72 | 305.83 | 364.83 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.65 | 0.60 | 01-JAN-09:09 | 391.07 | 14.77 | 0.00 | 222.00 | 188.63 | 18.18 | 0.00 | 93.33 |
February | 216.00 | 0.64 | 0.60 | 01-FEB-08:00 | 401.96 | 15.47 | 0.00 | 241.83 | 206.10 | 18.94 | 0.00 | 132.00 |
March | 275.00 | 0.63 | 0.60 | 01-MAR-07:30 | 551.12 | 16.85 | 0.00 | 321.83 | 265.81 | 20.10 | 4.83 | 222.67 |
April | 261.17 | 0.62 | 0.60 | 01-APR-14:39 | 607.24 | 17.45 | 0.00 | 351.83 | 292.87 | 20.68 | 40.50 | 285.17 |
May | 372.00 | 0.61 | 0.60 | 01-MAY-05:49 | 833.94 | 18.16 | 0.00 | 415.33 | 372.56 | 22.06 | 183.33 | 364.17 |
June | 351.83 | 0.61 | 0.60 | 01-JUN-04:00 | 925.90 | 19.28 | 28.83 | 407.67 | 402.49 | 23.11 | 230.83 | 370.00 |
July | 365.17 | 0.61 | 0.60 | 01-JUL-04:00 | 930.54 | 18.21 | 0.00 | 416.67 | 401.47 | 22.75 | 233.50 | 370.83 |
August | 389.17 | 0.62 | 0.60 | 01-AUG-05:40 | 737.63 | 17.90 | 0.00 | 385.33 | 341.30 | 21.13 | 163.33 | 348.67 |
September | 285.33 | 0.62 | 0.60 | 01-SEP-06:19 | 556.44 | 17.07 | 0.00 | 329.00 | 271.92 | 20.32 | 14.00 | 255.00 |
October | 305.50 | 0.63 | 0.60 | 01-OCT-14:39 | 503.31 | 16.62 | 0.00 | 296.83 | 257.93 | 19.98 | 0.00 | 230.50 |
November | 240.83 | 0.64 | 0.60 | 01-NOV-07:30 | 439.45 | 15.33 | 0.00 | 244.83 | 206.05 | 18.65 | 0.00 | 131.50 |
December | 211.17 | 0.68 | 0.60 | 01-DEC-09:20 | 309.68 | 13.84 | 0.00 | 210.67 | 155.68 | 17.42 | 0.00 | 47.00 |
Annual Sum or Average | 3472.67 | 0.63 | 639.74 | 17.05 | 28.83 | 3843.83 | 296.67 | 20.61 | 870.33 | 2850.83 | ||
Minimum of Months | 199.50 | 0.61 | 0.60 | 309.68 | 13.84 | 0.00 | 210.67 | 155.68 | 17.42 | 0.00 | 47.00 | |
Maximum of Months | 389.17 | 0.68 | 0.60 | 930.54 | 19.28 | 28.83 | 416.67 | 402.49 | 23.11 | 233.50 | 370.83 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.65 | 0.60 | 01-JAN-09:09 | 391.07 | 14.77 | 0.00 | 222.00 | 188.63 | 18.18 | 0.00 | 93.33 |
February | 216.00 | 0.64 | 0.60 | 01-FEB-08:00 | 401.96 | 15.47 | 0.00 | 241.83 | 206.10 | 18.94 | 0.00 | 132.00 |
March | 275.00 | 0.63 | 0.60 | 01-MAR-07:30 | 551.12 | 16.85 | 0.00 | 321.83 | 265.81 | 20.10 | 4.83 | 222.67 |
April | 261.17 | 0.62 | 0.60 | 01-APR-14:39 | 607.24 | 17.45 | 0.00 | 351.83 | 292.87 | 20.68 | 40.50 | 285.17 |
May | 372.00 | 0.61 | 0.60 | 01-MAY-05:49 | 833.94 | 18.16 | 0.00 | 415.33 | 372.56 | 22.06 | 183.33 | 364.17 |
June | 351.83 | 0.61 | 0.60 | 01-JUN-04:00 | 925.90 | 19.28 | 28.83 | 407.67 | 402.49 | 23.11 | 230.83 | 370.00 |
July | 365.17 | 0.61 | 0.60 | 01-JUL-04:00 | 930.54 | 18.21 | 0.00 | 416.67 | 401.47 | 22.75 | 233.50 | 370.83 |
August | 389.17 | 0.62 | 0.60 | 01-AUG-05:40 | 737.63 | 17.90 | 0.00 | 385.33 | 341.30 | 21.13 | 163.33 | 348.67 |
September | 285.33 | 0.62 | 0.60 | 01-SEP-06:19 | 556.44 | 17.07 | 0.00 | 329.00 | 271.92 | 20.32 | 13.83 | 255.00 |
October | 305.50 | 0.63 | 0.60 | 01-OCT-14:39 | 503.31 | 16.62 | 0.00 | 296.83 | 257.93 | 19.98 | 0.00 | 230.50 |
November | 240.83 | 0.64 | 0.60 | 01-NOV-07:30 | 439.45 | 15.33 | 0.00 | 244.83 | 206.05 | 18.65 | 0.00 | 131.50 |
December | 211.17 | 0.68 | 0.60 | 01-DEC-09:20 | 309.68 | 13.84 | 0.00 | 210.67 | 155.68 | 17.42 | 0.00 | 47.00 |
Annual Sum or Average | 3472.67 | 0.63 | 639.74 | 17.05 | 28.83 | 3843.83 | 296.67 | 20.61 | 870.17 | 2850.83 | ||
Minimum of Months | 199.50 | 0.61 | 0.60 | 309.68 | 13.84 | 0.00 | 210.67 | 155.68 | 17.42 | 0.00 | 47.00 | |
Maximum of Months | 389.17 | 0.68 | 0.60 | 930.54 | 19.28 | 28.83 | 416.67 | 402.49 | 23.11 | 233.50 | 370.83 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.604557E+11 | 99408.61 | 19-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.520089E+11 | 108384.08 | 06-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.352494E+11 | 107471.80 | 29-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.593742E+11 | 107969.38 | 03-APR-17:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.282046E+11 | 101507.46 | 01-MAY-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.644478E+09 | 22381.29 | 03-JUN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 57108183.86 | 14898.28 | 11-JUL-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.277726E+09 | 19647.68 | 20-AUG-13:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.705125E+10 | 72830.43 | 24-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.430074E+11 | 109512.61 | 19-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.634692E+11 | 104010.29 | 17-NOV-18:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.280213E+11 | 105349.42 | 17-DEC-09:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.377821E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 57108183.86 | 14898.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.634692E+11 | 109512.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4903072.98 | 2204.40 | 30-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4903072.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4903072.98 | 2204.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.283603E+10 | 2445.40 | 02-JAN-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.213187E+10 | 2360.63 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145043E+10 | 1667.35 | 17-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.915901E+09 | 1425.18 | 21-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.264620E+09 | 903.79 | 04-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 87691.03 | 49.96 | 07-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 43143577.34 | 603.87 | 24-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127349E+09 | 803.77 | 28-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139559E+10 | 1690.21 | 23-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.225860E+10 | 1838.43 | 30-DEC-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.283603E+10 | 2445.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.141142E+09 | 544.24 | 02-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 92564437.78 | 477.73 | 06-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6820353.39 | 275.84 | 17-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1610291.75 | 147.74 | 21-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6648694.32 | 237.76 | 26-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 52861268.93 | 386.14 | 12-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.301647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.141142E+09 | 544.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.121834E+10 | 1153.71 | 02-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114392E+10 | 1132.99 | 06-FEB-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.445597E+09 | 754.06 | 18-MAR-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109541E+09 | 522.57 | 03-APR-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.292132E+09 | 709.66 | 24-NOV-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.753393E+09 | 748.80 | 31-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.396293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.121834E+10 | 1153.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.971748E+09 | 767.09 | 02-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.894243E+09 | 777.89 | 06-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.401961E+09 | 494.07 | 17-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120973E+09 | 360.95 | 21-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.280286E+09 | 454.66 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.666194E+09 | 555.57 | 31-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.333540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.971748E+09 | 777.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.488240E+09 | 3036.42 | 02-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.465503E+09 | 3036.42 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.376028E+09 | 2393.78 | 18-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.234889E+09 | 2056.20 | 22-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131035E+09 | 1445.13 | 01-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41923959.43 | 890.03 | 07-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 27961647.04 | 780.63 | 10-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20220626.88 | 929.43 | 23-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 58081361.73 | 1029.15 | 26-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129972E+09 | 1547.68 | 28-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.314415E+09 | 2449.65 | 24-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.434962E+09 | 2411.35 | 11-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.272323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 20220626.88 | 780.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.488240E+09 | 3036.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.184304E+10 | 5522.71 | 08-JAN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.982087E+09 | 4657.48 | 27-FEB-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.596724E+09 | 3844.56 | 16-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.336580E+09 | 3606.05 | 21-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81397309.81 | 2159.03 | 04-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 854483.34 | 868.45 | 26-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7400235.80 | 1220.94 | 31-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.454829E+09 | 3306.93 | 26-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121789E+10 | 4701.32 | 11-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.552080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.184304E+10 | 5522.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.932606E+09 | 8460.73 | 08-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.399278E+09 | 6325.53 | 27-FEB-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23794929.35 | 3262.96 | 17-MAR-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4959510.43 | 1308.85 | 21-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18527633.22 | 2635.46 | 26-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.316557E+09 | 5776.86 | 11-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.932606E+09 | 8460.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.882159E+10 | 8427.00 | 14-JAN-16:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.666063E+10 | 7525.51 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.266499E+10 | 5418.58 | 17-MAR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.844808E+09 | 4149.82 | 21-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.320181E+10 | 5113.34 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.659521E+10 | 6774.21 | 11-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.287890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.882159E+10 | 8427.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.548632E+10 | 5066.04 | 02-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.464285E+10 | 5012.05 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208498E+10 | 3239.02 | 23-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.695400E+09 | 2031.08 | 21-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1874336.66 | 367.33 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 46816947.80 | 1418.66 | 29-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.209102E+10 | 3234.01 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.419366E+10 | 3152.82 | 15-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.548632E+10 | 5066.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25824.95 | 43.04 | 06-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25824.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25824.95 | 43.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.151904E+10 | 5802.53 | 02-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172003E+10 | 6505.59 | 06-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125874E+09 | 2645.86 | 17-MAR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1091.90 | 0.23 | 09-APR-15:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9834.81 | 8.68 | 30-MAY-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11539.64 | 0.23 | 29-JUN-16:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6965.48 | 0.23 | 18-JUL-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6322.32 | 0.23 | 16-AUG-23:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15917.17 | 27.94 | 19-SEP-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4403.52 | 0.23 | 06-OCT-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137710E+09 | 1722.02 | 24-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.194570E+09 | 3445.85 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.369727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1091.90 | 0.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.172003E+10 | 6505.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.470603E+10 | 9897.66 | 14-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.381385E+10 | 9896.72 | 07-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179043E+10 | 9728.20 | 17-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.787244E+09 | 9400.19 | 21-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 61361206.62 | 3538.20 | 01-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5021474.20 | 3370.87 | 29-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2913115.27 | 2407.92 | 18-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4052865.28 | 4069.85 | 08-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12447502.13 | 4179.49 | 26-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132671E+09 | 3607.54 | 19-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.209604E+10 | 9649.28 | 25-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.373014E+10 | 9863.62 | 31-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2913115.27 | 2407.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.470603E+10 | 9897.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.562633E+10 | 9859.24 | 14-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.495387E+10 | 9858.30 | 07-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.234573E+10 | 9696.16 | 17-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.920469E+09 | 9388.49 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 62452585.34 | 3357.45 | 03-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1704254.08 | 2249.58 | 12-JUN-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1512428.89 | 2542.51 | 18-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1345081.77 | 2581.37 | 13-AUG-06:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9038527.66 | 4507.73 | 28-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.262747E+09 | 4115.46 | 19-OCT-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.275878E+10 | 9727.50 | 24-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.470884E+10 | 9825.30 | 31-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1345081.77 | 2249.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.562633E+10 | 9859.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.185970E+11 | 55996.36 | 02-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182580E+11 | 56213.14 | 06-FEB-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.527875E+10 | 53829.01 | 16-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.819898E+09 | 30589.68 | 03-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 45357882.20 | 36148.02 | 03-MAY-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1947155.99 | 7959.48 | 06-JUN-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1414881.70 | 3602.24 | 31-JUL-18:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3401794.55 | 9618.17 | 25-AUG-21:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13664268.13 | 14259.74 | 17-SEP-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.246526E+09 | 39301.76 | 30-OCT-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.535528E+10 | 53967.86 | 22-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132491E+11 | 54742.47 | 31-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.618704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1414881.70 | 3602.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.185970E+11 | 56213.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.467264E+10 | 9674.32 | 14-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.370968E+10 | 9673.05 | 05-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190502E+10 | 9491.71 | 17-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.797362E+09 | 9192.17 | 21-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 65456306.99 | 3720.76 | 02-MAY-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1680295.75 | 3386.12 | 13-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 402159.27 | 1394.02 | 18-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 67256.43 | 672.56 | 07-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8244628.79 | 3376.04 | 21-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143501E+09 | 4068.53 | 06-OCT-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.196638E+10 | 9428.10 | 25-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.367495E+10 | 9640.97 | 31-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 67256.43 | 672.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.467264E+10 | 9674.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.556923E+10 | 9637.15 | 14-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.481701E+10 | 9635.85 | 05-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.246331E+10 | 9471.96 | 17-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.923866E+09 | 9165.28 | 21-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 69652484.06 | 4268.68 | 01-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 901363.25 | 2005.66 | 01-JUN-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 251524.71 | 831.32 | 23-JUL-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 225898.90 | 1130.94 | 06-AUG-21:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6327875.56 | 2545.76 | 23-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.277220E+09 | 4076.89 | 19-OCT-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252542E+10 | 9456.82 | 23-NOV-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.457107E+10 | 9603.91 | 31-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 225898.90 | 831.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.556923E+10 | 9637.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.167590E+10 | 2953.30 | 14-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139301E+10 | 2953.00 | 07-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.705334E+09 | 2904.69 | 17-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.332573E+09 | 2833.66 | 21-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38410621.94 | 1013.52 | 01-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1335710.52 | 933.18 | 22-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 913689.33 | 738.63 | 05-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1418976.17 | 994.75 | 08-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7504712.14 | 1070.43 | 16-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 98095025.33 | 1201.89 | 27-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.811666E+09 | 2902.52 | 25-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136710E+10 | 2943.06 | 31-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.643326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 913689.33 | 738.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.167590E+10 | 2953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.195754E+10 | 2938.45 | 14-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173859E+10 | 2938.16 | 07-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.880532E+09 | 2900.33 | 22-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.378329E+09 | 2821.03 | 03-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 37643496.51 | 1068.31 | 01-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 416470.07 | 540.59 | 06-JUN-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 475255.38 | 742.85 | 09-JUL-06:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 447285.41 | 571.30 | 08-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7234513.83 | 1259.03 | 24-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163051E+09 | 2808.11 | 29-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103442E+10 | 2899.29 | 24-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167110E+10 | 2928.25 | 31-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.786978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 416470.07 | 540.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.195754E+10 | 2938.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.486231E+10 | 13974.02 | 14-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.348266E+10 | 13913.82 | 06-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181516E+10 | 13663.23 | 16-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.870112E+09 | 13266.51 | 21-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 63483967.92 | 5210.73 | 03-MAY-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6344753.98 | 3970.55 | 04-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3112264.06 | 4198.11 | 18-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2063358.60 | 4403.75 | 08-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7998177.28 | 4095.57 | 21-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 82354575.41 | 4794.96 | 28-OCT-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159491E+10 | 13439.29 | 25-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.351388E+10 | 13711.83 | 31-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2063358.60 | 3970.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.486231E+10 | 13974.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.539075E+11 | 0.539075E+11 | 37176.38 | 31-JAN-04:20 | 37176.38 | 0.00 |
February | 0.00 | 0.00 | 0.477317E+11 | 0.477317E+11 | 34239.09 | 09-FEB-00:07 | 34239.09 | 0.00 |
March | 0.00 | 0.00 | 0.558717E+11 | 0.558717E+11 | 50111.17 | 31-MAR-23:20 | 50111.17 | 0.00 |
April | 0.00 | 0.00 | 0.531563E+11 | 0.531535E+11 | 50127.34 | 01-APR-05:15 | 50127.34 | 0.00 |
May | 0.00 | 0.00 | 0.524041E+11 | 0.492629E+11 | 63500.04 | 31-MAY-23:07 | 45048.15 | 0.00 |
June | 0.00 | 0.00 | 0.483817E+11 | 0.343300E+11 | 63461.80 | 01-JUN-04:07 | 44617.23 | 0.00 |
July | 0.00 | 0.00 | 0.477735E+11 | 0.272215E+11 | 67440.67 | 01-JUL-05:17 | 38225.13 | 0.00 |
August | 0.00 | 0.00 | 0.467088E+11 | 0.337453E+11 | 64949.78 | 31-AUG-05:13 | 46904.66 | 0.00 |
September | 0.00 | 0.00 | 0.457848E+11 | 0.373479E+11 | 59809.37 | 30-SEP-06:30 | 48586.49 | 0.00 |
October | 0.00 | 0.00 | 0.491227E+11 | 0.444038E+11 | 53535.79 | 31-OCT-06:15 | 48189.26 | 0.00 |
November | 0.00 | 0.00 | 0.490343E+11 | 0.490343E+11 | 44828.99 | 30-NOV-06:04 | 44828.99 | 0.00 |
December | 0.00 | 0.00 | 0.523333E+11 | 0.523333E+11 | 39321.35 | 31-DEC-20:50 | 39321.35 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.602210E+12 | 0.538343E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.457848E+11 | 0.272215E+11 | 34239.09 | 34239.09 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.558717E+11 | 0.558717E+11 | 67440.67 | 50127.34 | 0.00 |
Report: CoilReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.372806E+11 | 0.372806E+11 | 47038.12 | 31-JAN-23:00 | 47038.12 | 0.00 |
February | 0.00 | 0.00 | 0.311321E+11 | 0.311321E+11 | 43318.83 | 09-FEB-22:50 | 43318.83 | 0.00 |
March | 0.00 | 0.00 | 0.433818E+11 | 0.433818E+11 | 54906.72 | 01-MAR-17:10 | 54906.72 | 0.00 |
April | 0.00 | 0.00 | 0.482845E+11 | 0.482839E+11 | 63437.10 | 01-APR-17:50 | 63437.10 | 0.00 |
May | 0.00 | 0.00 | 0.557002E+11 | 0.523841E+11 | 71032.16 | 01-MAY-16:10 | 66874.12 | 0.00 |
June | 0.00 | 0.00 | 0.609469E+11 | 0.432314E+11 | 80321.66 | 01-JUN-20:45 | 56406.18 | 0.00 |
July | 0.00 | 0.00 | 0.671350E+11 | 0.382329E+11 | 85359.86 | 01-JUL-16:20 | 48441.47 | 0.00 |
August | 0.00 | 0.00 | 0.648274E+11 | 0.468133E+11 | 82205.79 | 31-AUG-18:50 | 58848.41 | 0.00 |
September | 0.00 | 0.00 | 0.575974E+11 | 0.469975E+11 | 75696.82 | 30-SEP-16:05 | 61493.17 | 0.00 |
October | 0.00 | 0.00 | 0.531736E+11 | 0.480779E+11 | 67752.99 | 31-OCT-21:10 | 60987.13 | 0.00 |
November | 0.00 | 0.00 | 0.431527E+11 | 0.431527E+11 | 56728.13 | 30-NOV-17:20 | 56728.13 | 0.00 |
December | 0.00 | 0.00 | 0.392597E+11 | 0.392597E+11 | 49754.16 | 31-DEC-18:12 | 49754.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.601872E+12 | 0.518228E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.311321E+11 | 0.311321E+11 | 43318.83 | 43318.83 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.671350E+11 | 0.523841E+11 | 85359.86 | 66874.12 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.329359E+10 | 0.325708E+10 | 128470.33 | 27-MAR-16:00 | 128470.33 | 0.02 |
April | 0.00 | 0.00 | 0.339278E+11 | 0.336599E+11 | 208088.51 | 09-APR-10:50 | 137084.88 | 0.14 |
May | 0.00 | 0.00 | 0.125500E+12 | 0.107682E+12 | 297829.63 | 31-MAY-17:17 | 159214.44 | 0.38 |
June | 0.00 | 0.00 | 0.520638E+12 | 0.300692E+12 | 504405.71 | 24-JUN-17:17 | 171855.56 | 0.91 |
July | 0.00 | 0.00 | 0.826657E+12 | 0.431939E+12 | 528638.08 | 05-JUL-19:10 | 191496.70 | 1.00 |
August | 0.00 | 0.00 | 0.668323E+12 | 0.425152E+12 | 586630.65 | 11-AUG-21:53 | 203311.83 | 0.97 |
September | 0.00 | 0.00 | 0.360538E+12 | 0.242148E+12 | 536215.48 | 13-SEP-21:00 | 206325.43 | 0.79 |
October | 0.00 | 0.00 | 0.123645E+12 | 0.787861E+11 | 278389.69 | 05-OCT-19:10 | 113001.73 | 0.41 |
November | 0.00 | 0.00 | 0.332701E+10 | 0.303487E+10 | 62625.09 | 04-NOV-10:45 | 62625.09 | 0.02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.266585E+13 | 0.162635E+13 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.826657E+12 | 0.431939E+12 | 586630.65 | 206325.43 | 1.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.274237E+09 | 0.236684E+09 | 19369.32 | 27-MAR-13:00 | 12687.17 | 0.01 |
April | 0.00 | 0.00 | 0.217150E+10 | 0.212913E+10 | 20182.20 | 09-APR-10:00 | 13725.70 | 0.10 |
May | 0.00 | 0.00 | 0.903150E+10 | 0.753219E+10 | 31077.44 | 31-MAY-17:00 | 16337.38 | 0.28 |
June | 0.00 | 0.00 | 0.428359E+11 | 0.239619E+11 | 46753.17 | 24-JUN-18:07 | 16313.96 | 0.72 |
July | 0.00 | 0.00 | 0.583701E+11 | 0.326037E+11 | 47889.79 | 28-JUL-08:03 | 17975.02 | 0.79 |
August | 0.00 | 0.00 | 0.471787E+11 | 0.307582E+11 | 42812.08 | 10-AUG-21:51 | 17181.45 | 0.79 |
September | 0.00 | 0.00 | 0.291741E+11 | 0.191404E+11 | 46252.66 | 14-SEP-08:10 | 16585.46 | 0.62 |
October | 0.00 | 0.00 | 0.100475E+11 | 0.576025E+10 | 30632.72 | 03-OCT-15:02 | 16954.47 | 0.30 |
November | 0.00 | 0.00 | 0.209566E+09 | 0.180115E+09 | 7314.01 | 10-NOV-08:00 | 2644.12 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.199293E+12 | 0.122303E+12 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.583701E+11 | 0.326037E+11 | 47889.79 | 17975.02 | 0.79 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 64008021.92 | 45918715.32 | 12307.22 | 20-JAN-16:02 | 12307.22 | 0.01 |
February | 0.00 | 0.00 | 0.153521E+09 | 0.131983E+09 | 12306.64 | 17-FEB-16:02 | 12306.64 | 0.02 |
March | 0.00 | 0.00 | 0.920522E+09 | 0.695827E+09 | 14298.29 | 27-MAR-15:02 | 11292.68 | 0.14 |
April | 0.00 | 0.00 | 0.227997E+10 | 0.153042E+10 | 13399.76 | 09-APR-08:62 | 10894.59 | 0.37 |
May | 0.00 | 0.00 | 0.482789E+10 | 0.312487E+10 | 15010.67 | 19-MAY-18:02 | 10061.98 | 0.72 |
June | 0.00 | 0.00 | 0.893195E+10 | 0.549767E+10 | 17147.21 | 27-JUN-08:62 | 10204.52 | 0.92 |
July | 0.00 | 0.00 | 0.108408E+11 | 0.690828E+10 | 17238.94 | 28-JUL-08:61 | 10214.93 | 0.96 |
August | 0.00 | 0.00 | 0.115105E+11 | 0.783713E+10 | 16550.83 | 06-AUG-08:62 | 10341.07 | 0.96 |
September | 0.00 | 0.00 | 0.707456E+10 | 0.435295E+10 | 18429.45 | 22-SEP-18:02 | 9154.04 | 0.88 |
October | 0.00 | 0.00 | 0.467878E+10 | 0.289275E+10 | 15358.74 | 06-OCT-08:62 | 9649.39 | 0.63 |
November | 0.00 | 0.00 | 0.426031E+09 | 0.239759E+09 | 13153.85 | 10-NOV-16:02 | 10538.33 | 0.14 |
December | 0.00 | 0.00 | 78715320.67 | 68580932.23 | 12310.17 | 17-DEC-16:02 | 12310.17 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.517873E+11 | 0.333261E+11 | 0.48 | |||
Minimum of Months | 0.00 | 0.00 | 64008021.92 | 45918715.32 | 12306.64 | 9154.04 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.115105E+11 | 0.783713E+10 | 18429.45 | 12310.17 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 15174271.23 | 10870415.63 | 10928.86 | 20-JAN-16:02 | 10928.86 | 0.00 |
February | 0.00 | 0.00 | 32967570.26 | 27810893.17 | 11201.20 | 22-FEB-16:02 | 11201.20 | 0.00 |
March | 0.00 | 0.00 | 0.379900E+09 | 0.292778E+09 | 14102.19 | 27-MAR-15:02 | 10701.52 | 0.07 |
April | 0.00 | 0.00 | 0.131100E+10 | 0.812394E+09 | 13628.12 | 27-APR-18:21 | 12805.30 | 0.27 |
May | 0.00 | 0.00 | 0.329105E+10 | 0.200994E+10 | 16073.67 | 31-MAY-08:51 | 11806.82 | 0.56 |
June | 0.00 | 0.00 | 0.641567E+10 | 0.410867E+10 | 18083.87 | 27-JUN-08:51 | 10223.64 | 0.64 |
July | 0.00 | 0.00 | 0.933381E+10 | 0.612687E+10 | 18608.18 | 23-JUL-08:21 | 10405.85 | 0.79 |
August | 0.00 | 0.00 | 0.942814E+10 | 0.642379E+10 | 18677.76 | 12-AUG-08:61 | 11545.91 | 0.80 |
September | 0.00 | 0.00 | 0.416171E+10 | 0.240021E+10 | 17218.38 | 14-SEP-08:51 | 9709.84 | 0.59 |
October | 0.00 | 0.00 | 0.188223E+10 | 0.969775E+09 | 15041.74 | 05-OCT-21:51 | 10440.72 | 0.38 |
November | 0.00 | 0.00 | 82711244.94 | 49508264.34 | 12961.75 | 10-NOV-16:02 | 9469.45 | 0.03 |
December | 0.00 | 0.00 | 12636344.30 | 10178339.62 | 10980.93 | 17-DEC-16:02 | 10980.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.363470E+11 | 0.232428E+11 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 12636344.30 | 10178339.62 | 10928.86 | 9469.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.942814E+10 | 0.642379E+10 | 18677.76 | 12805.30 | 0.80 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 29177817.74 | 29177817.74 | 6195.67 | 31-JAN-15:00 | 6195.67 | 0.00 |
February | 0.00 | 0.00 | 0.239358E+10 | 0.239358E+10 | 27817.14 | 20-FEB-13:30 | 27817.14 | 0.00 |
March | 0.00 | 0.00 | 0.697116E+10 | 0.569826E+10 | 33958.32 | 28-MAR-12:30 | 27345.55 | 0.09 |
April | 0.00 | 0.00 | 0.142742E+11 | 0.897074E+10 | 44584.17 | 07-APR-13:15 | 40384.85 | 0.37 |
May | 0.00 | 0.00 | 0.246644E+11 | 0.120522E+11 | 34779.66 | 30-MAY-12:30 | 26956.32 | 0.80 |
June | 0.00 | 0.00 | 0.391544E+11 | 0.193201E+11 | 36425.96 | 19-JUN-12:40 | 28945.92 | 0.99 |
July | 0.00 | 0.00 | 0.517813E+11 | 0.282616E+11 | 38221.24 | 08-JUL-12:00 | 31235.16 | 1.00 |
August | 0.00 | 0.00 | 0.609320E+11 | 0.384272E+11 | 46899.33 | 30-AUG-13:00 | 35393.93 | 1.00 |
September | 0.00 | 0.00 | 0.462527E+11 | 0.280961E+11 | 51373.91 | 28-SEP-12:40 | 42013.46 | 0.97 |
October | 0.00 | 0.00 | 0.452908E+11 | 0.340191E+11 | 54376.20 | 04-OCT-12:10 | 45079.08 | 0.63 |
November | 0.00 | 0.00 | 0.105538E+11 | 0.833222E+10 | 46035.96 | 02-NOV-12:50 | 46035.96 | 0.17 |
December | 0.00 | 0.00 | 0.358407E+10 | 0.358407E+10 | 31277.11 | 17-DEC-13:40 | 31277.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.305881E+12 | 0.189184E+12 | 0.50 | |||
Minimum of Months | 0.00 | 0.00 | 29177817.74 | 29177817.74 | 6195.67 | 6195.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.609320E+11 | 0.384272E+11 | 54376.20 | 46035.96 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.407319E+09 | 0.219243E+09 | 63536.31 | 24-JAN-09:02 | 52755.98 | 0.03 |
February | 0.00 | 0.00 | 0.223803E+09 | 0.190838E+09 | 59136.83 | 18-FEB-09:02 | 59136.83 | 0.01 |
March | 0.00 | 0.00 | 0.379511E+10 | 0.256748E+10 | 69818.68 | 27-MAR-15:02 | 59401.13 | 0.16 |
April | 0.00 | 0.00 | 0.144910E+11 | 0.942517E+10 | 71865.85 | 08-APR-15:02 | 64851.03 | 0.42 |
May | 0.00 | 0.00 | 0.316013E+11 | 0.223926E+11 | 82026.19 | 31-MAY-21:51 | 63435.83 | 0.53 |
June | 0.00 | 0.00 | 0.455839E+11 | 0.316170E+11 | 99538.92 | 25-JUN-07:51 | 61015.25 | 0.57 |
July | 0.00 | 0.00 | 0.634555E+11 | 0.438715E+11 | 102657.74 | 23-JUL-08:21 | 53682.78 | 0.75 |
August | 0.00 | 0.00 | 0.575539E+11 | 0.397391E+11 | 101738.43 | 12-AUG-08:61 | 59840.06 | 0.73 |
September | 0.00 | 0.00 | 0.334056E+11 | 0.221502E+11 | 94392.99 | 14-SEP-08:51 | 51703.33 | 0.52 |
October | 0.00 | 0.00 | 0.183255E+11 | 0.117839E+11 | 81501.38 | 05-OCT-21:51 | 56324.84 | 0.34 |
November | 0.00 | 0.00 | 0.491074E+10 | 0.291000E+10 | 67277.22 | 10-NOV-09:13 | 44922.12 | 0.24 |
December | 0.00 | 0.00 | 0.371310E+09 | 0.282932E+09 | 58947.01 | 10-DEC-09:02 | 58947.01 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.274125E+12 | 0.187150E+12 | 0.36 | |||
Minimum of Months | 0.00 | 0.00 | 0.223803E+09 | 0.190838E+09 | 58947.01 | 44922.12 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.634555E+11 | 0.438715E+11 | 102657.74 | 64851.03 | 0.75 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 92860610.84 | 69566319.03 | 10305.71 | 20-JAN-09:02 | 10305.71 | 0.01 |
February | 0.00 | 0.00 | 0.153828E+09 | 0.129050E+09 | 11262.09 | 25-FEB-09:01 | 11262.09 | 0.02 |
March | 0.00 | 0.00 | 0.784220E+09 | 0.569701E+09 | 13234.73 | 27-MAR-15:02 | 9941.82 | 0.15 |
April | 0.00 | 0.00 | 0.231482E+10 | 0.150239E+10 | 12140.13 | 27-APR-15:02 | 10770.49 | 0.41 |
May | 0.00 | 0.00 | 0.499073E+10 | 0.326818E+10 | 13605.28 | 05-MAY-15:01 | 9772.45 | 0.74 |
June | 0.00 | 0.00 | 0.842043E+10 | 0.507595E+10 | 15399.59 | 18-JUN-08:62 | 9238.90 | 0.94 |
July | 0.00 | 0.00 | 0.107165E+11 | 0.682144E+10 | 15228.46 | 28-JUL-08:61 | 9692.16 | 0.97 |
August | 0.00 | 0.00 | 0.114162E+11 | 0.783926E+10 | 15091.37 | 06-AUG-08:62 | 9503.93 | 0.98 |
September | 0.00 | 0.00 | 0.714050E+10 | 0.446805E+10 | 16921.09 | 22-SEP-18:02 | 8351.67 | 0.90 |
October | 0.00 | 0.00 | 0.449384E+10 | 0.271379E+10 | 14045.14 | 06-OCT-08:62 | 8782.75 | 0.65 |
November | 0.00 | 0.00 | 0.613449E+09 | 0.375009E+09 | 11870.23 | 11-NOV-09:02 | 10279.00 | 0.17 |
December | 0.00 | 0.00 | 0.166047E+09 | 0.122841E+09 | 10569.25 | 02-DEC-09:01 | 10569.25 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.513035E+11 | 0.329552E+11 | 0.50 | |||
Minimum of Months | 0.00 | 0.00 | 92860610.84 | 69566319.03 | 10305.71 | 8351.67 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.114162E+11 | 0.783926E+10 | 16921.09 | 11262.09 | 0.98 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 9629715.39 | 5133068.24 | 5418.67 | 19-JAN-09:01 | 4398.46 | 0.00 |
February | 0.00 | 0.00 | 27497241.19 | 20559364.30 | 10327.48 | 25-FEB-09:01 | 10327.48 | 0.01 |
March | 0.00 | 0.00 | 0.288949E+09 | 0.203514E+09 | 12442.37 | 27-MAR-15:02 | 9044.35 | 0.06 |
April | 0.00 | 0.00 | 0.141435E+10 | 0.866272E+09 | 13000.01 | 08-APR-08:51 | 12369.66 | 0.32 |
May | 0.00 | 0.00 | 0.357320E+10 | 0.227947E+10 | 16701.56 | 31-MAY-08:32 | 13530.20 | 0.58 |
June | 0.00 | 0.00 | 0.610197E+10 | 0.380820E+10 | 17438.32 | 20-JUN-08:62 | 13258.60 | 0.65 |
July | 0.00 | 0.00 | 0.913634E+10 | 0.589054E+10 | 17651.73 | 01-JUL-08:32 | 13001.10 | 0.80 |
August | 0.00 | 0.00 | 0.921035E+10 | 0.611833E+10 | 17249.09 | 12-AUG-08:61 | 11132.00 | 0.82 |
September | 0.00 | 0.00 | 0.430448E+10 | 0.252589E+10 | 17141.85 | 06-SEP-08:32 | 13274.11 | 0.62 |
October | 0.00 | 0.00 | 0.185074E+10 | 0.100177E+10 | 14800.23 | 25-OCT-08:51 | 10877.23 | 0.40 |
November | 0.00 | 0.00 | 0.176482E+09 | 95178337.33 | 11285.76 | 11-NOV-09:02 | 9640.34 | 0.06 |
December | 0.00 | 0.00 | 18289933.38 | 10622781.76 | 8520.73 | 20-DEC-09:01 | 8520.73 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.361123E+11 | 0.228255E+11 | 0.36 | |||
Minimum of Months | 0.00 | 0.00 | 9629715.39 | 5133068.24 | 5418.67 | 4398.46 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.921035E+10 | 0.611833E+10 | 17651.73 | 13530.20 | 0.82 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 15267966.29 | 10524263.99 | 3245.18 | 20-JAN-16:02 | 3245.18 | 0.01 |
February | 0.00 | 0.00 | 36973141.25 | 31154800.13 | 3245.07 | 17-FEB-16:02 | 3245.07 | 0.02 |
March | 0.00 | 0.00 | 0.231152E+09 | 0.175484E+09 | 3761.88 | 27-MAR-15:02 | 2981.90 | 0.12 |
April | 0.00 | 0.00 | 0.575878E+09 | 0.398531E+09 | 3678.56 | 09-APR-08:62 | 2672.88 | 0.34 |
May | 0.00 | 0.00 | 0.122022E+10 | 0.820018E+09 | 3981.73 | 19-MAY-18:02 | 2580.04 | 0.67 |
June | 0.00 | 0.00 | 0.228670E+10 | 0.140240E+10 | 4726.62 | 27-JUN-08:62 | 2561.80 | 0.92 |
July | 0.00 | 0.00 | 0.282333E+10 | 0.178369E+10 | 4750.67 | 28-JUL-08:61 | 2564.28 | 0.96 |
August | 0.00 | 0.00 | 0.296197E+10 | 0.200274E+10 | 4647.81 | 06-AUG-08:62 | 2550.38 | 0.96 |
September | 0.00 | 0.00 | 0.173283E+10 | 0.106337E+10 | 5054.60 | 22-SEP-18:02 | 2283.36 | 0.85 |
October | 0.00 | 0.00 | 0.106882E+10 | 0.664043E+09 | 4149.75 | 25-OCT-08:62 | 2449.77 | 0.57 |
November | 0.00 | 0.00 | 81654892.82 | 47622023.48 | 3522.38 | 10-NOV-16:02 | 2681.67 | 0.09 |
December | 0.00 | 0.00 | 16087127.78 | 14539145.18 | 3243.31 | 02-DEC-16:01 | 3243.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.130509E+11 | 0.841412E+10 | 0.46 | |||
Minimum of Months | 0.00 | 0.00 | 15267966.29 | 10524263.99 | 3243.31 | 2283.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.296197E+10 | 0.200274E+10 | 5054.60 | 3245.18 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2555629.22 | 1588351.87 | 2244.60 | 17-JAN-16:02 | 2244.60 | 0.00 |
February | 0.00 | 0.00 | 5143422.57 | 4091140.97 | 2316.43 | 24-FEB-16:01 | 2316.43 | 0.00 |
March | 0.00 | 0.00 | 87044921.26 | 65905348.16 | 3789.37 | 27-MAR-15:02 | 2797.21 | 0.06 |
April | 0.00 | 0.00 | 0.328305E+09 | 0.207637E+09 | 3610.91 | 27-APR-18:21 | 3479.05 | 0.25 |
May | 0.00 | 0.00 | 0.852509E+09 | 0.536001E+09 | 4326.89 | 31-MAY-08:51 | 3173.90 | 0.53 |
June | 0.00 | 0.00 | 0.171569E+10 | 0.109970E+10 | 4961.60 | 25-JUN-07:51 | 2852.94 | 0.64 |
July | 0.00 | 0.00 | 0.247700E+10 | 0.162321E+10 | 5114.77 | 23-JUL-08:21 | 2561.12 | 0.80 |
August | 0.00 | 0.00 | 0.246169E+10 | 0.166899E+10 | 5104.57 | 12-AUG-08:61 | 2891.57 | 0.80 |
September | 0.00 | 0.00 | 0.102905E+10 | 0.593613E+09 | 4714.01 | 14-SEP-08:51 | 2424.51 | 0.56 |
October | 0.00 | 0.00 | 0.389659E+09 | 0.195526E+09 | 4080.11 | 05-OCT-21:51 | 2696.74 | 0.32 |
November | 0.00 | 0.00 | 13466654.68 | 7898471.69 | 3418.18 | 10-NOV-16:02 | 2387.46 | 0.02 |
December | 0.00 | 0.00 | 1905516.15 | 1274314.01 | 1764.94 | 17-DEC-16:02 | 1594.27 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.936401E+10 | 0.600543E+10 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 1905516.15 | 1274314.01 | 1764.94 | 1594.27 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.247700E+10 | 0.166899E+10 | 5114.77 | 3479.05 | 0.80 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.102791E+10 | 0.889214E+09 | 15173.93 | 10-JAN-16:02 | 15173.93 | 0.06 |
February | 0.00 | 0.00 | 0.152240E+10 | 0.137651E+10 | 15174.68 | 10-FEB-16:01 | 15174.68 | 0.07 |
March | 0.00 | 0.00 | 0.275534E+10 | 0.220136E+10 | 16116.01 | 27-MAR-15:02 | 14785.02 | 0.25 |
April | 0.00 | 0.00 | 0.389545E+10 | 0.268449E+10 | 16734.02 | 30-APR-15:02 | 11749.35 | 0.44 |
May | 0.00 | 0.00 | 0.614743E+10 | 0.387626E+10 | 18740.17 | 31-MAY-18:02 | 13728.65 | 0.72 |
June | 0.00 | 0.00 | 0.108056E+11 | 0.613684E+10 | 22989.61 | 27-JUN-08:62 | 11475.27 | 0.91 |
July | 0.00 | 0.00 | 0.142831E+11 | 0.885453E+10 | 22859.02 | 28-JUL-08:61 | 11638.53 | 0.96 |
August | 0.00 | 0.00 | 0.156806E+11 | 0.104904E+11 | 21778.31 | 06-AUG-08:62 | 11944.93 | 0.96 |
September | 0.00 | 0.00 | 0.114172E+11 | 0.740963E+10 | 24359.34 | 22-SEP-18:02 | 10303.84 | 0.89 |
October | 0.00 | 0.00 | 0.100800E+11 | 0.727584E+10 | 19609.33 | 05-OCT-18:02 | 12766.53 | 0.68 |
November | 0.00 | 0.00 | 0.258320E+10 | 0.187988E+10 | 16082.27 | 11-NOV-16:02 | 13838.44 | 0.32 |
December | 0.00 | 0.00 | 0.172839E+10 | 0.153852E+10 | 15244.06 | 25-DEC-16:02 | 13188.10 | 0.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.819266E+11 | 0.546135E+11 | 0.53 | |||
Minimum of Months | 0.00 | 0.00 | 0.102791E+10 | 0.889214E+09 | 15173.93 | 10303.84 | 0.06 | |
Maximum of Months | 0.00 | 0.00 | 0.156806E+11 | 0.104904E+11 | 24359.34 | 15174.68 | 0.96 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 48935.71 | 228682.20 | 02-JAN-09:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 46370.07 | 236148.43 | 06-FEB-09:01 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22396.61 | 173918.13 | 17-MAR-08:61 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26164.04 | 157549.42 | 02-APR-18:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10782.44 | 99685.10 | 03-MAY-15:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 272.67 | 24434.81 | 06-JUN-15:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 36.45 | 26237.59 | 18-JUL-08:05 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 113.50 | 25162.84 | 25-AUG-21:57 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 2758.57 | 72685.64 | 24-SEP-05:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16556.33 | 133298.01 | 28-OCT-18:05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 34324.70 | 159079.27 | 28-NOV-16:01 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 29981.33 | 186335.52 | 31-DEC-19:01 |
Annual Sum or Average | 0.00 | 19717.36 | ||||
Minimum of Months | 0.00 | 0.00 | 36.45 | 24434.81 | ||
Maximum of Months | 0.00 | 0.00 | 48935.71 | 236148.43 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1422.53 | 45523.04 | 17-JAN-16:03 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 3116.56 | 60873.42 | 20-FEB-16:02 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 9686.73 | 239121.02 | 27-MAR-15:03 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 33180.62 | 362407.34 | 07-APR-15:05 | 0.00 | 0.00 | 01-APR-00:10 |
May | 84986.45 | 411007.08 | 31-MAY-15:25 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 271920.56 | 644200.53 | 23-JUN-21:52 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 400406.82 | 662059.20 | 20-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 339461.76 | 758401.44 | 11-AUG-21:51 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 199860.10 | 636823.99 | 07-SEP-20:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 87120.02 | 455770.28 | 05-OCT-15:05 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 11369.33 | 177250.37 | 04-NOV-15:03 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 3413.64 | 46572.92 | 18-DEC-11:00 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 121366.08 | 0.00 | ||||
Minimum of Months | 1422.53 | 45523.04 | 0.00 | 0.00 | ||
Maximum of Months | 400406.82 | 758401.44 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 27303.87 | 57697.32 | 30-JAN-07:40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 27587.31 | 57701.11 | 09-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 26965.39 | 57220.21 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25576.07 | 54800.13 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 23821.86 | 51556.85 | 01-MAY-06:40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 22155.53 | 47702.70 | 01-JUN-06:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20997.59 | 44549.33 | 03-JUL-06:35 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20721.78 | 47335.41 | 25-AUG-17:01 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21342.56 | 45564.34 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22717.27 | 49172.57 | 31-OCT-06:40 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 24481.02 | 52946.39 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 26154.91 | 55882.63 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 24132.23 | ||||
Minimum of Months | 0.00 | 0.00 | 20721.78 | 44549.33 | ||
Maximum of Months | 0.00 | 0.00 | 27587.31 | 57701.11 |
Report: FanReportMonthly
For: SWHSYS1 HPWH FAN
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.827608E+09 | 0.07 | 553.22 | 01-JAN-00:15 | 0.10 |
February | 0.790848E+09 | 0.07 | 553.22 | 01-FEB-00:07 | 0.10 |
March | 0.741910E+09 | 0.06 | 553.22 | 01-MAR-00:20 | 0.10 |
April | 0.622214E+09 | 0.06 | 553.22 | 01-APR-05:15 | 0.10 |
May | 0.554681E+09 | 0.06 | 553.22 | 01-MAY-05:13 | 0.10 |
June | 0.458187E+09 | 0.05 | 553.22 | 01-JUN-04:07 | 0.10 |
July | 0.431644E+09 | 0.05 | 553.22 | 01-JUL-05:17 | 0.10 |
August | 0.435641E+09 | 0.05 | 553.22 | 01-AUG-05:13 | 0.10 |
September | 0.459364E+09 | 0.05 | 553.22 | 01-SEP-04:07 | 0.10 |
October | 0.546352E+09 | 0.06 | 553.22 | 01-OCT-05:07 | 0.10 |
November | 0.641047E+09 | 0.06 | 553.22 | 01-NOV-05:13 | 0.10 |
December | 0.767110E+09 | 0.06 | 553.22 | 01-DEC-00:07 | 0.10 |
Annual Sum or Average | 0.727661E+10 | 0.06 | |||
Minimum of Months | 0.431644E+09 | 0.05 | 553.22 | 0.10 | |
Maximum of Months | 0.827608E+09 | 0.07 | 553.22 | 0.10 |
Report: FanReportMonthly
For: SWHSYSLAUNDRY HPWH FAN
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.559241E+09 | 0.06 | 700.51 | 01-JAN-17:10 | 0.10 |
February | 0.506099E+09 | 0.06 | 700.51 | 01-FEB-17:10 | 0.10 |
March | 0.558168E+09 | 0.06 | 700.51 | 01-MAR-17:10 | 0.10 |
April | 0.539146E+09 | 0.06 | 700.51 | 01-APR-16:05 | 0.10 |
May | 0.556149E+09 | 0.05 | 700.51 | 01-MAY-16:10 | 0.10 |
June | 0.537289E+09 | 0.05 | 700.51 | 01-JUN-16:10 | 0.10 |
July | 0.555126E+09 | 0.05 | 700.51 | 01-JUL-16:10 | 0.10 |
August | 0.554899E+09 | 0.05 | 700.51 | 01-AUG-16:10 | 0.10 |
September | 0.537884E+09 | 0.05 | 700.51 | 01-SEP-16:10 | 0.10 |
October | 0.556495E+09 | 0.05 | 700.51 | 01-OCT-16:10 | 0.10 |
November | 0.539533E+09 | 0.06 | 700.51 | 01-NOV-16:10 | 0.10 |
December | 0.558885E+09 | 0.06 | 700.51 | 01-DEC-17:10 | 0.10 |
Annual Sum or Average | 0.655891E+10 | 0.06 | |||
Minimum of Months | 0.506099E+09 | 0.05 | 700.51 | 0.10 | |
Maximum of Months | 0.559241E+09 | 0.06 | 700.51 | 0.10 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.69 | 1299.30 | 01-JAN-16:01 | 0.88 |
February | 0.244774E+10 | 0.69 | 1299.30 | 01-FEB-09:01 | 0.88 |
March | 0.271000E+10 | 0.69 | 1299.30 | 01-MAR-09:02 | 0.88 |
April | 0.262258E+10 | 0.69 | 1299.30 | 01-APR-08:62 | 0.88 |
May | 0.271000E+10 | 0.69 | 1299.30 | 01-MAY-15:02 | 0.88 |
June | 0.262258E+10 | 0.69 | 1299.30 | 01-JUN-08:51 | 0.87 |
July | 0.271000E+10 | 0.69 | 1299.30 | 01-JUL-08:51 | 0.87 |
August | 0.271000E+10 | 0.69 | 1299.30 | 01-AUG-06:51 | 0.87 |
September | 0.262258E+10 | 0.69 | 1299.30 | 01-SEP-08:61 | 0.87 |
October | 0.271000E+10 | 0.69 | 1299.30 | 01-OCT-08:62 | 0.87 |
November | 0.262258E+10 | 0.69 | 1299.30 | 01-NOV-15:02 | 0.88 |
December | 0.271000E+10 | 0.69 | 1299.30 | 01-DEC-16:01 | 0.88 |
Annual Sum or Average | 0.319080E+11 | 0.69 | |||
Minimum of Months | 0.244774E+10 | 0.69 | 1299.30 | 0.87 | |
Maximum of Months | 0.271000E+10 | 0.69 | 1299.30 | 0.88 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.341031E+11 | 0.83 | 18321.79 | 23-JAN-21:10 | 1.03 |
February | 0.308165E+11 | 0.84 | 17948.16 | 23-FEB-21:10 | 1.02 |
March | 0.352063E+11 | 0.85 | 20149.35 | 03-MAR-22:10 | 1.09 |
April | 0.349857E+11 | 0.86 | 25035.39 | 07-APR-21:10 | 1.24 |
May | 0.375417E+11 | 0.88 | 26355.73 | 31-MAY-21:10 | 1.27 |
June | 0.384000E+11 | 0.90 | 27388.09 | 20-JUN-21:10 | 1.30 |
July | 0.408288E+11 | 0.91 | 28078.32 | 10-JUL-21:10 | 1.32 |
August | 0.416378E+11 | 0.92 | 29946.82 | 24-AUG-19:50 | 1.39 |
September | 0.380183E+11 | 0.90 | 29121.48 | 07-SEP-21:10 | 1.35 |
October | 0.378130E+11 | 0.88 | 28205.55 | 05-OCT-21:10 | 1.33 |
November | 0.343798E+11 | 0.85 | 22649.43 | 03-NOV-21:10 | 1.17 |
December | 0.344091E+11 | 0.84 | 18477.04 | 04-DEC-21:10 | 1.03 |
Annual Sum or Average | 0.438140E+12 | 0.87 | |||
Minimum of Months | 0.308165E+11 | 0.83 | 17948.16 | 1.02 | |
Maximum of Months | 0.416378E+11 | 0.92 | 29946.82 | 1.39 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:03 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:03 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:03 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.26 |
May | 0.205205E+09 | 0.26 | 76.61 | 01-MAY-00:05 | 0.26 |
June | 0.198586E+09 | 0.26 | 76.61 | 01-JUN-00:05 | 0.26 |
July | 0.205205E+09 | 0.26 | 76.61 | 01-JUL-00:10 | 0.26 |
August | 0.205205E+09 | 0.26 | 76.61 | 01-AUG-00:05 | 0.26 |
September | 0.198586E+09 | 0.26 | 76.61 | 01-SEP-00:05 | 0.26 |
October | 0.205205E+09 | 0.26 | 76.61 | 01-OCT-00:10 | 0.26 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:05 | 0.27 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:03 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.26 | 76.61 | 0.26 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:03 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.26 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:05 | 0.26 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.26 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.26 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:05 | 0.26 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.26 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.245600E+09 | 0.44 | 736.76 | 01-JAN-09:01 | 0.58 |
February | 0.209393E+09 | 0.44 | 736.76 | 01-FEB-09:01 | 0.57 |
March | 0.178282E+09 | 0.44 | 736.76 | 01-MAR-16:02 | 0.57 |
April | 0.197947E+09 | 0.46 | 736.76 | 01-APR-15:02 | 0.57 |
May | 0.294300E+09 | 0.50 | 736.76 | 01-MAY-15:02 | 0.57 |
June | 0.444007E+09 | 0.54 | 736.76 | 01-JUN-08:62 | 0.57 |
July | 0.511736E+09 | 0.55 | 736.76 | 01-JUL-08:62 | 0.57 |
August | 0.565953E+09 | 0.55 | 736.76 | 01-AUG-08:62 | 0.57 |
September | 0.367135E+09 | 0.52 | 736.76 | 01-SEP-08:61 | 0.57 |
October | 0.274043E+09 | 0.50 | 736.76 | 01-OCT-08:62 | 0.57 |
November | 0.159119E+09 | 0.42 | 736.76 | 01-NOV-15:02 | 0.57 |
December | 0.211879E+09 | 0.43 | 736.76 | 01-DEC-19:01 | 0.57 |
Annual Sum or Average | 0.365939E+10 | 0.48 | |||
Minimum of Months | 0.159119E+09 | 0.42 | 736.76 | 0.57 | |
Maximum of Months | 0.565953E+09 | 0.55 | 736.76 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.272248E+09 | 0.46 | 713.94 | 01-JAN-09:01 | 0.58 |
February | 0.241185E+09 | 0.46 | 713.94 | 01-FEB-09:01 | 0.57 |
March | 0.166743E+09 | 0.41 | 713.94 | 01-MAR-09:02 | 0.57 |
April | 0.145987E+09 | 0.41 | 713.94 | 01-APR-15:02 | 0.57 |
May | 0.200184E+09 | 0.39 | 713.94 | 01-MAY-15:02 | 0.57 |
June | 0.314027E+09 | 0.37 | 713.94 | 01-JUN-08:51 | 0.57 |
July | 0.444355E+09 | 0.46 | 713.94 | 01-JUL-08:51 | 0.57 |
August | 0.461852E+09 | 0.46 | 713.94 | 01-AUG-06:51 | 0.57 |
September | 0.211768E+09 | 0.35 | 713.94 | 01-SEP-08:61 | 0.57 |
October | 0.130825E+09 | 0.37 | 713.94 | 01-OCT-08:62 | 0.57 |
November | 0.163869E+09 | 0.41 | 713.94 | 01-NOV-15:02 | 0.57 |
December | 0.241925E+09 | 0.44 | 713.94 | 01-DEC-09:01 | 0.57 |
Annual Sum or Average | 0.299497E+10 | 0.41 | |||
Minimum of Months | 0.130825E+09 | 0.35 | 713.94 | 0.57 | |
Maximum of Months | 0.461852E+09 | 0.46 | 713.94 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 1920864.48 | 0.00 | 377.53 | 31-JAN-15:00 | 0.58 |
February | 0.121562E+09 | 0.06 | 1094.23 | 20-FEB-13:30 | 0.58 |
March | 0.339037E+09 | 0.14 | 1266.96 | 29-MAR-13:00 | 0.57 |
April | 0.668729E+09 | 0.28 | 2116.07 | 08-APR-13:10 | 0.57 |
May | 0.113015E+10 | 0.46 | 1166.07 | 30-MAY-12:50 | 0.57 |
June | 0.157127E+10 | 0.57 | 1212.58 | 19-JUN-13:20 | 0.57 |
July | 0.192357E+10 | 0.57 | 1275.42 | 10-JUL-13:10 | 0.57 |
August | 0.230199E+10 | 0.57 | 2173.19 | 22-AUG-12:40 | 0.57 |
September | 0.190441E+10 | 0.55 | 2393.43 | 30-SEP-12:30 | 0.57 |
October | 0.197140E+10 | 0.51 | 2454.85 | 10-OCT-12:30 | 0.57 |
November | 0.515927E+09 | 0.19 | 2387.63 | 04-NOV-12:30 | 0.57 |
December | 0.169675E+09 | 0.07 | 1198.74 | 17-DEC-13:40 | 0.58 |
Annual Sum or Average | 0.126197E+11 | 0.33 | |||
Minimum of Months | 1920864.48 | 0.00 | 377.53 | 0.57 | |
Maximum of Months | 0.230199E+10 | 0.57 | 2454.85 | 0.58 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.100143E+10 | 0.41 | 3865.24 | 01-JAN-16:01 | 0.58 |
February | 0.950093E+09 | 0.41 | 3865.24 | 01-FEB-16:02 | 0.58 |
March | 0.646464E+09 | 0.40 | 3865.24 | 01-MAR-09:02 | 0.57 |
April | 0.953795E+09 | 0.39 | 3865.24 | 01-APR-08:62 | 0.57 |
May | 0.176034E+10 | 0.36 | 3865.24 | 01-MAY-08:62 | 0.57 |
June | 0.230058E+10 | 0.34 | 3865.24 | 01-JUN-08:51 | 0.57 |
July | 0.307623E+10 | 0.43 | 3865.24 | 01-JUL-08:51 | 0.57 |
August | 0.279902E+10 | 0.42 | 3865.24 | 01-AUG-06:51 | 0.57 |
September | 0.168309E+10 | 0.31 | 3865.24 | 01-SEP-08:61 | 0.57 |
October | 0.101167E+10 | 0.33 | 3865.24 | 01-OCT-08:62 | 0.57 |
November | 0.682674E+09 | 0.40 | 3865.24 | 01-NOV-08:62 | 0.57 |
December | 0.817805E+09 | 0.41 | 3865.24 | 01-DEC-16:01 | 0.58 |
Annual Sum or Average | 0.176832E+11 | 0.38 | |||
Minimum of Months | 0.646464E+09 | 0.31 | 3865.24 | 0.57 | |
Maximum of Months | 0.307623E+10 | 0.43 | 3865.24 | 0.58 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.230461E+09 | 0.43 | 673.49 | 01-JAN-16:01 | 0.58 |
February | 0.191830E+09 | 0.43 | 673.49 | 01-FEB-19:01 | 0.57 |
March | 0.167507E+09 | 0.44 | 673.49 | 01-MAR-09:02 | 0.57 |
April | 0.192846E+09 | 0.47 | 673.49 | 01-APR-15:02 | 0.57 |
May | 0.294513E+09 | 0.51 | 673.49 | 01-MAY-08:62 | 0.57 |
June | 0.414201E+09 | 0.54 | 673.49 | 01-JUN-08:62 | 0.57 |
July | 0.501898E+09 | 0.56 | 673.49 | 01-JUL-08:62 | 0.57 |
August | 0.555527E+09 | 0.56 | 673.49 | 01-AUG-08:62 | 0.57 |
September | 0.365929E+09 | 0.53 | 673.49 | 01-SEP-08:61 | 0.57 |
October | 0.264315E+09 | 0.51 | 673.49 | 01-OCT-08:62 | 0.57 |
November | 0.155113E+09 | 0.43 | 673.49 | 01-NOV-08:62 | 0.57 |
December | 0.201574E+09 | 0.43 | 673.49 | 01-DEC-16:01 | 0.57 |
Annual Sum or Average | 0.353571E+10 | 0.49 | |||
Minimum of Months | 0.155113E+09 | 0.43 | 673.49 | 0.57 | |
Maximum of Months | 0.555527E+09 | 0.56 | 673.49 | 0.58 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.254813E+09 | 0.46 | 654.14 | 01-JAN-09:01 | 0.58 |
February | 0.222189E+09 | 0.46 | 654.14 | 01-FEB-09:01 | 0.57 |
March | 0.156927E+09 | 0.41 | 654.14 | 01-MAR-09:02 | 0.57 |
April | 0.147082E+09 | 0.42 | 654.14 | 01-APR-15:02 | 0.57 |
May | 0.214961E+09 | 0.41 | 654.14 | 01-MAY-08:62 | 0.57 |
June | 0.299977E+09 | 0.37 | 654.14 | 01-JUN-08:51 | 0.57 |
July | 0.431591E+09 | 0.46 | 654.14 | 01-JUL-08:32 | 0.57 |
August | 0.446685E+09 | 0.47 | 654.14 | 01-AUG-06:51 | 0.57 |
September | 0.221667E+09 | 0.36 | 654.14 | 01-SEP-08:61 | 0.57 |
October | 0.130007E+09 | 0.38 | 654.14 | 01-OCT-08:62 | 0.57 |
November | 0.149518E+09 | 0.41 | 654.14 | 01-NOV-08:62 | 0.57 |
December | 0.223041E+09 | 0.44 | 654.14 | 01-DEC-16:01 | 0.57 |
Annual Sum or Average | 0.289846E+10 | 0.42 | |||
Minimum of Months | 0.130007E+09 | 0.36 | 654.14 | 0.57 | |
Maximum of Months | 0.446685E+09 | 0.47 | 654.14 | 0.58 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 75748514.92 | 0.46 | 194.39 | 01-JAN-09:01 | 0.58 |
February | 65039537.12 | 0.46 | 194.39 | 01-FEB-09:01 | 0.57 |
March | 53860486.30 | 0.44 | 194.39 | 01-MAR-16:02 | 0.57 |
April | 55577492.82 | 0.46 | 194.39 | 01-APR-08:62 | 0.57 |
May | 76314516.79 | 0.50 | 194.39 | 01-MAY-15:02 | 0.57 |
June | 0.114657E+09 | 0.54 | 194.39 | 01-JUN-08:62 | 0.57 |
July | 0.134633E+09 | 0.55 | 194.39 | 01-JUL-08:62 | 0.57 |
August | 0.146985E+09 | 0.55 | 194.39 | 01-AUG-08:62 | 0.57 |
September | 90943265.44 | 0.52 | 194.39 | 01-SEP-08:61 | 0.57 |
October | 66895389.11 | 0.49 | 194.39 | 02-OCT-15:02 | 0.57 |
November | 48203783.39 | 0.43 | 194.39 | 01-NOV-15:02 | 0.57 |
December | 66181015.63 | 0.45 | 194.39 | 01-DEC-09:01 | 0.57 |
Annual Sum or Average | 0.995038E+09 | 0.49 | |||
Minimum of Months | 48203783.39 | 0.43 | 194.39 | 0.57 | |
Maximum of Months | 0.146985E+09 | 0.55 | 194.39 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 83142102.36 | 0.50 | 187.99 | 01-JAN-09:01 | 0.58 |
February | 73642227.93 | 0.49 | 187.99 | 01-FEB-09:01 | 0.57 |
March | 50822708.26 | 0.42 | 187.99 | 01-MAR-09:02 | 0.57 |
April | 42304720.94 | 0.41 | 187.99 | 01-APR-08:62 | 0.57 |
May | 53213272.70 | 0.39 | 187.99 | 01-MAY-15:02 | 0.57 |
June | 84953997.78 | 0.37 | 187.99 | 01-JUN-08:51 | 0.57 |
July | 0.119343E+09 | 0.46 | 187.99 | 01-JUL-08:51 | 0.57 |
August | 0.122006E+09 | 0.46 | 187.99 | 01-AUG-06:51 | 0.57 |
September | 52873013.29 | 0.35 | 187.99 | 01-SEP-08:61 | 0.57 |
October | 32871788.47 | 0.37 | 187.99 | 02-OCT-15:02 | 0.57 |
November | 51971593.94 | 0.43 | 187.99 | 01-NOV-08:62 | 0.57 |
December | 74698565.41 | 0.48 | 187.99 | 01-DEC-09:01 | 0.57 |
Annual Sum or Average | 0.841843E+09 | 0.43 | |||
Minimum of Months | 32871788.47 | 0.35 | 187.99 | 0.57 | |
Maximum of Months | 0.122006E+09 | 0.50 | 187.99 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.296580E+09 | 0.45 | 901.48 | 01-JAN-16:01 | 0.58 |
February | 0.265235E+09 | 0.47 | 901.48 | 01-FEB-16:02 | 0.57 |
March | 0.280851E+09 | 0.47 | 901.48 | 01-MAR-09:02 | 0.57 |
April | 0.282210E+09 | 0.47 | 901.48 | 02-APR-15:01 | 0.57 |
May | 0.345603E+09 | 0.50 | 901.48 | 01-MAY-08:62 | 0.57 |
June | 0.506200E+09 | 0.53 | 901.48 | 01-JUN-08:62 | 0.57 |
July | 0.651013E+09 | 0.55 | 901.48 | 01-JUL-08:62 | 0.57 |
August | 0.766842E+09 | 0.55 | 901.48 | 01-AUG-08:62 | 0.57 |
September | 0.584261E+09 | 0.53 | 901.48 | 01-SEP-08:61 | 0.57 |
October | 0.567294E+09 | 0.52 | 901.48 | 01-OCT-08:62 | 0.57 |
November | 0.259108E+09 | 0.47 | 901.48 | 01-NOV-08:62 | 0.57 |
December | 0.292774E+09 | 0.46 | 901.48 | 01-DEC-09:01 | 0.57 |
Annual Sum or Average | 0.509797E+10 | 0.50 | |||
Minimum of Months | 0.259108E+09 | 0.45 | 901.48 | 0.57 | |
Maximum of Months | 0.766842E+09 | 0.55 | 901.48 | 0.58 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.767378E+09 | 0.697547E+09 | 726.13 | 02-JAN-09:01 | 660.05 | 660.05 | 35.16 | 1.16 |
February | 0.665449E+09 | 0.604893E+09 | 740.07 | 06-FEB-09:01 | 672.72 | 672.72 | 35.32 | 1.21 |
March | 0.397664E+09 | 0.361477E+09 | 580.36 | 17-MAR-08:61 | 527.55 | 527.55 | 29.93 | 0.81 |
April | 0.338718E+09 | 0.307895E+09 | 579.66 | 02-APR-18:05 | 526.91 | 526.91 | 33.13 | 0.81 |
May | 0.125037E+09 | 0.113658E+09 | 428.59 | 01-MAY-06:20 | 389.58 | 389.58 | 56.57 | 0.53 |
June | 3123728.57 | 2839469.27 | 109.62 | 13-JUN-08:05 | 99.65 | 99.65 | 34.20 | 0.12 |
July | 547384.05 | 497572.10 | 139.66 | 18-JUL-08:05 | 126.95 | 126.95 | 37.94 | 0.15 |
August | 1680218.07 | 1527318.23 | 122.46 | 24-AUG-19:00 | 111.32 | 111.32 | 42.33 | 0.13 |
September | 30175696.21 | 27429707.85 | 326.78 | 24-SEP-05:50 | 297.04 | 297.04 | 34.52 | 0.39 |
October | 0.200966E+09 | 0.182678E+09 | 510.94 | 28-OCT-18:05 | 464.45 | 464.45 | 32.61 | 0.68 |
November | 0.501439E+09 | 0.455808E+09 | 569.55 | 28-NOV-16:01 | 517.72 | 517.72 | 31.24 | 0.79 |
December | 0.574348E+09 | 0.522083E+09 | 636.47 | 31-DEC-19:01 | 578.55 | 578.55 | 34.14 | 0.93 |
Annual Sum or Average | 0.360653E+10 | 0.327833E+10 | ||||||
Minimum of Months | 547384.05 | 497572.10 | 109.62 | 99.65 | 99.65 | 29.93 | 0.12 | |
Maximum of Months | 0.767378E+09 | 0.697547E+09 | 740.07 | 672.72 | 672.72 | 56.57 | 1.21 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1012437.31 | 920305.51 | 40.57 | 17-JAN-16:03 | 36.88 | 36.88 | 8.40 | 3.16 |
February | 3188575.69 | 2898415.30 | 88.70 | 20-FEB-16:02 | 80.63 | 80.63 | 8.40 | 4.85 |
March | 17595512.99 | 15994321.31 | 225.24 | 27-MAR-15:03 | 204.74 | 204.74 | 7.77 | 7.77 |
April | 86875652.07 | 78969967.73 | 752.23 | 07-APR-15:25 | 683.78 | 683.78 | 6.90 | 13.59 |
May | 0.237539E+09 | 0.215923E+09 | 858.16 | 31-MAY-18:03 | 780.07 | 780.07 | 7.50 | 14.40 |
June | 0.106142E+10 | 0.964831E+09 | 1960.14 | 24-JUN-18:03 | 1781.77 | 1781.77 | 7.33 | 20.53 |
July | 0.187935E+10 | 0.170833E+10 | 2109.99 | 20-JUL-18:03 | 1917.99 | 1917.99 | 6.73 | 21.17 |
August | 0.159916E+10 | 0.145364E+10 | 2611.41 | 11-AUG-21:00 | 2373.77 | 2373.77 | 7.15 | 23.12 |
September | 0.721947E+09 | 0.656249E+09 | 2162.03 | 07-SEP-20:00 | 1965.29 | 1965.29 | 7.15 | 21.38 |
October | 0.250232E+09 | 0.227461E+09 | 840.76 | 05-OCT-15:05 | 764.25 | 764.25 | 7.42 | 14.28 |
November | 20086054.80 | 18258223.81 | 282.21 | 04-NOV-15:01 | 256.53 | 256.53 | 8.15 | 8.66 |
December | 4187008.78 | 3805990.98 | 64.22 | 20-DEC-09:01 | 58.38 | 58.38 | 8.40 | 4.08 |
Annual Sum or Average | 0.588259E+10 | 0.534727E+10 | ||||||
Minimum of Months | 1012437.31 | 920305.51 | 40.57 | 36.88 | 36.88 | 6.73 | 3.16 | |
Maximum of Months | 0.187935E+10 | 0.170833E+10 | 2611.41 | 2373.77 | 2373.77 | 8.40 | 23.12 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.236193E+10 | 0.214700E+10 | 4875.28 | 01-JAN-09:03 | 4431.63 | 4431.63 | 8.45 | 34.51 |
February | 0.328246E+10 | 0.298375E+10 | 4875.28 | 01-FEB-09:01 | 4431.63 | 4431.63 | 8.43 | 34.51 |
March | 0.676648E+10 | 0.615073E+10 | 4875.28 | 01-MAR-07:15 | 4431.63 | 4431.63 | 8.41 | 34.51 |
April | 0.986104E+10 | 0.896369E+10 | 4875.28 | 01-APR-08:62 | 4431.63 | 4431.63 | 8.54 | 34.51 |
May | 0.129695E+11 | 0.117892E+11 | 4875.28 | 01-MAY-00:05 | 4431.63 | 4431.63 | 8.45 | 34.51 |
June | 0.126367E+11 | 0.114868E+11 | 4875.28 | 01-JUN-00:05 | 4431.63 | 4431.63 | 9.11 | 34.51 |
July | 0.130579E+11 | 0.118697E+11 | 4875.28 | 01-JUL-00:10 | 4431.63 | 4431.63 | 9.77 | 34.51 |
August | 0.130579E+11 | 0.118697E+11 | 4875.28 | 01-AUG-00:05 | 4431.63 | 4431.63 | 9.55 | 34.51 |
September | 0.126367E+11 | 0.114868E+11 | 4875.28 | 01-SEP-00:05 | 4431.63 | 4431.63 | 9.52 | 34.51 |
October | 0.125958E+11 | 0.114496E+11 | 4875.28 | 01-OCT-00:10 | 4431.63 | 4431.63 | 8.60 | 34.51 |
November | 0.712252E+10 | 0.647437E+10 | 4875.28 | 01-NOV-00:05 | 4431.63 | 4431.63 | 8.42 | 34.51 |
December | 0.348243E+10 | 0.316553E+10 | 4875.28 | 01-DEC-07:05 | 4431.63 | 4431.63 | 8.40 | 34.51 |
Annual Sum or Average | 0.109831E+12 | 0.998368E+11 | ||||||
Minimum of Months | 0.236193E+10 | 0.214700E+10 | 4875.28 | 4431.63 | 4431.63 | 8.40 | 34.51 | |
Maximum of Months | 0.130579E+11 | 0.118697E+11 | 4875.28 | 4431.63 | 4431.63 | 9.77 | 34.51 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:03 | 14.37 | 14.37 | 48.16 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 49.16 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 49.23 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.52 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 52.75 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 53.28 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 53.90 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 53.93 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 53.87 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 53.00 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 53.08 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 50.02 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 48.16 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 53.93 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 44.29 | 82.20 | 48935.71 | 228682.20 | 02-JAN-09:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 50.58 | 81.26 | 46370.07 | 236148.43 | 06-FEB-09:01 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 58.91 | 80.15 | 22396.61 | 173918.13 | 17-MAR-08:61 |
April | 0.00 | 0.00 | 01-APR-00:10 | 63.00 | 80.20 | 26164.04 | 157549.42 | 02-APR-18:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 34.61 | 79.40 | 10782.44 | 99685.10 | 03-MAY-15:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 33.21 | 33.21 | 272.67 | 24434.81 | 06-JUN-15:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 40.23 | 40.23 | 36.45 | 26237.59 | 18-JUL-08:05 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 42.71 | 42.71 | 113.50 | 25162.84 | 25-AUG-21:57 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 38.74 | 38.74 | 2758.57 | 72685.64 | 24-SEP-05:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.23 | 79.40 | 16556.33 | 133298.01 | 28-OCT-18:05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 35.95 | 79.40 | 34324.70 | 159079.27 | 28-NOV-16:01 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 61.67 | 80.08 | 29981.33 | 186335.52 | 31-DEC-19:01 |
Annual Sum or Average | 0.00 | 19717.36 | ||||||
Minimum of Months | 0.00 | 0.00 | 25.23 | 33.21 | 36.45 | 24434.81 | ||
Maximum of Months | 0.00 | 0.00 | 63.00 | 82.20 | 48935.71 | 236148.43 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1422.53 | 45523.04 | 17-JAN-16:03 | 8.68 | 8.37 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 3116.56 | 60873.42 | 20-FEB-16:02 | 8.79 | 8.37 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 9686.73 | 239121.02 | 27-MAR-15:03 | 9.38 | 7.73 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 33180.62 | 362407.34 | 07-APR-15:05 | 9.37 | 6.87 | 0.00 | 0.00 | 01-APR-00:10 |
May | 84986.45 | 411007.08 | 31-MAY-15:25 | 9.76 | 6.92 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 271920.56 | 644200.53 | 23-JUN-21:52 | 11.74 | 7.29 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 400406.82 | 662059.20 | 20-JUL-18:03 | 11.28 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 339461.76 | 758401.44 | 11-AUG-21:51 | 12.37 | 7.12 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 199860.10 | 636823.99 | 07-SEP-20:00 | 11.53 | 7.12 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 87120.02 | 455770.28 | 05-OCT-15:05 | 10.54 | 7.39 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 11369.33 | 177250.37 | 04-NOV-15:03 | 9.34 | 8.11 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 3413.64 | 46572.92 | 18-DEC-11:00 | 8.69 | 8.37 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 121366.08 | 0.00 | ||||||
Minimum of Months | 1422.53 | 45523.04 | 8.68 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 400406.82 | 758401.44 | 12.37 | 8.37 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 48.16 | 60.00 | 27303.87 | 57697.32 | 30-JAN-07:40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 49.16 | 59.96 | 27587.31 | 57701.11 | 09-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 49.23 | 60.00 | 26965.39 | 57220.21 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.52 | 59.99 | 25576.07 | 54800.13 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 52.75 | 59.99 | 23821.86 | 51556.85 | 01-MAY-06:40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 53.28 | 59.97 | 22155.53 | 47702.70 | 01-JUN-06:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 53.90 | 59.99 | 20997.59 | 44549.33 | 03-JUL-06:35 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 53.93 | 60.00 | 20721.78 | 47335.41 | 25-AUG-17:01 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 53.87 | 59.97 | 21342.56 | 45564.34 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.00 | 59.96 | 22717.27 | 49172.57 | 31-OCT-06:40 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 53.08 | 59.99 | 24481.02 | 52946.39 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 50.02 | 59.97 | 26154.91 | 55882.63 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 24132.23 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.16 | 59.96 | 20721.78 | 44549.33 | ||
Maximum of Months | 0.00 | 0.00 | 53.93 | 60.00 | 27587.31 | 57701.11 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.831948E+11 | 0.00 | 0.00 | 0.341031E+11 | 0.00 | 0.00 |
February | 0.694218E+11 | 0.00 | 0.00 | 0.308165E+11 | 0.00 | 0.00 |
March | 0.433008E+11 | 0.00 | 0.329359E+10 | 0.352063E+11 | 0.00 | 0.00 |
April | 0.626388E+11 | 0.00 | 0.339278E+11 | 0.349857E+11 | 0.00 | 0.00 |
May | 0.286884E+11 | 0.00 | 0.125500E+12 | 0.375417E+11 | 0.00 | 0.00 |
June | 0.686489E+09 | 0.00 | 0.520638E+12 | 0.384000E+11 | 0.00 | 0.00 |
July | 85069830.90 | 0.00 | 0.826657E+12 | 0.408288E+11 | 0.00 | 0.00 |
August | 0.297947E+09 | 0.00 | 0.668323E+12 | 0.416378E+11 | 0.00 | 0.00 |
September | 0.715333E+10 | 0.00 | 0.360538E+12 | 0.380183E+11 | 0.00 | 0.00 |
October | 0.433189E+11 | 0.00 | 0.123645E+12 | 0.378130E+11 | 0.00 | 0.00 |
November | 0.715244E+11 | 0.00 | 0.332701E+10 | 0.343798E+11 | 0.00 | 0.00 |
December | 0.445106E+11 | 0.00 | 0.00 | 0.344091E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.454821E+12 | 0.00 | 0.266585E+13 | 0.438140E+12 | 0.00 | 0.00 |
Minimum of Months | 85069830.90 | 0.00 | 0.00 | 0.308165E+11 | 0.00 | 0.00 |
Maximum of Months | 0.831948E+11 | 0.00 | 0.826657E+12 | 0.416378E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.151904E+10 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
February | 0.172003E+10 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
March | 0.125874E+09 | 0.00 | 0.274237E+09 | 0.271000E+10 | 0.00 | 0.00 |
April | 1091.90 | 0.00 | 0.217150E+10 | 0.262258E+10 | 0.00 | 0.00 |
May | 9834.81 | 0.00 | 0.903150E+10 | 0.271000E+10 | 0.00 | 0.00 |
June | 11539.64 | 0.00 | 0.428359E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 6965.48 | 0.00 | 0.583701E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 6322.32 | 0.00 | 0.471787E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 15917.17 | 0.00 | 0.291741E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 4403.52 | 0.00 | 0.100475E+11 | 0.271000E+10 | 0.00 | 0.00 |
November | 0.137710E+09 | 0.00 | 0.209566E+09 | 0.262258E+10 | 0.00 | 0.00 |
December | 0.194570E+09 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.369727E+10 | 0.00 | 0.199293E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 1091.90 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.172003E+10 | 0.00 | 0.583701E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.341031E+11 | 0.00 | 0.831948E+11 | 0.591265E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308165E+11 | 0.00 | 0.694218E+11 | 0.592818E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.352063E+11 | 0.329359E+10 | 0.433008E+11 | 0.418884E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.349857E+11 | 0.339278E+11 | 0.626388E+11 | 0.147483E+12 | 0.209163E+09 | 0.00 | 0.00 | 0.00 |
May | 0.375417E+11 | 0.125500E+12 | 0.286884E+11 | 0.106326E+11 | 0.337942E+10 | 0.00 | 0.00 | 0.00 |
June | 0.384000E+11 | 0.520638E+12 | 0.686489E+09 | 0.00 | 0.584417E+11 | 0.00 | 0.00 | 0.00 |
July | 0.408288E+11 | 0.826657E+12 | 85069830.90 | 0.00 | 0.228803E+12 | 0.00 | 0.00 | 0.00 |
August | 0.416378E+11 | 0.668323E+12 | 0.297947E+09 | 0.00 | 0.182090E+12 | 0.00 | 0.00 | 0.00 |
September | 0.380183E+11 | 0.360538E+12 | 0.715333E+10 | 0.00 | 0.243348E+11 | 0.00 | 0.00 | 0.00 |
October | 0.378130E+11 | 0.123645E+12 | 0.433189E+11 | 0.615758E+11 | 0.636522E+09 | 0.00 | 0.00 | 0.00 |
November | 0.343798E+11 | 0.332701E+10 | 0.715244E+11 | 0.286171E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.344091E+11 | 0.00 | 0.445106E+11 | 0.536468E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.438140E+12 | 0.266585E+13 | 0.454821E+12 | 0.264530E+13 | 0.497895E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.308165E+11 | 0.00 | 85069830.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.416378E+11 | 0.826657E+12 | 0.831948E+11 | 0.592818E+12 | 0.228803E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.00 | 0.151904E+10 | 0.556894E+11 | 50002.83 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.00 | 0.172003E+10 | 0.543396E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.274237E+09 | 0.125874E+09 | 0.403217E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.217150E+10 | 1091.90 | 0.201376E+11 | 38481789.28 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.903150E+10 | 9834.81 | 0.472421E+10 | 0.403141E+09 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.428359E+11 | 11539.64 | 96976156.38 | 0.789241E+10 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.583701E+11 | 6965.48 | 1817337.11 | 0.311228E+11 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.471787E+11 | 6322.32 | 0.111989E+09 | 0.237235E+11 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.291741E+11 | 15917.17 | 0.988926E+09 | 0.521879E+10 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.100475E+11 | 4403.52 | 0.108974E+11 | 0.112504E+09 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.209566E+09 | 0.137710E+09 | 0.324648E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.00 | 0.194570E+09 | 0.495336E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.199293E+12 | 0.369727E+10 | 0.269308E+12 | 0.685116E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.00 | 1091.90 | 1817337.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.583701E+11 | 0.172003E+10 | 0.556894E+11 | 0.311228E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.341031E+11 | 0.831948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308165E+11 | 0.694218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.352063E+11 | 0.433008E+11 | 0.329359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.349857E+11 | 0.626388E+11 | 0.339278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.375417E+11 | 0.286884E+11 | 0.125500E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.384000E+11 | 0.686489E+09 | 0.520638E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.408288E+11 | 85069830.90 | 0.826657E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.416378E+11 | 0.297947E+09 | 0.668323E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.380183E+11 | 0.715333E+10 | 0.360538E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.378130E+11 | 0.433189E+11 | 0.123645E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.343798E+11 | 0.715244E+11 | 0.332701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.344091E+11 | 0.445106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.438140E+12 | 0.454821E+12 | 0.266585E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.308165E+11 | 85069830.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.416378E+11 | 0.831948E+11 | 0.826657E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.151904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.172003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.125874E+09 | 0.274237E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 1091.90 | 0.217150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 9834.81 | 0.903150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 11539.64 | 0.428359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 6965.48 | 0.583701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 6322.32 | 0.471787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 15917.17 | 0.291741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 4403.52 | 0.100475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.137710E+09 | 0.209566E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.194570E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.369727E+10 | 0.199293E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 1091.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.172003E+10 | 0.583701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.451328E+11 | 0.00 | 0.00 | 251.36 | 0.00 | 0.00 | 21175333.67 | 0.00 | 0.88 |
February | 0.405962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 |
March | 0.435947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
April | 0.426905E+11 | 0.00 | 0.00 | 0.00 | 7486963.67 | 0.00 | 0.00 | 0.00 | 0.88 |
May | 0.349096E+11 | 0.00 | 0.00 | 0.00 | 0.241964E+09 | 0.00 | 0.00 | 0.00 | 0.88 |
June | 0.897679E+10 | 0.00 | 0.00 | 0.00 | 0.104770E+11 | 0.00 | 0.00 | 0.00 | 0.89 |
July | 0.476144E+09 | 0.00 | 0.00 | 0.00 | 0.255058E+11 | 0.00 | 0.00 | 0.00 | 0.89 |
August | 0.521993E+10 | 0.746570E+09 | 0.00 | 325013.23 | 0.150176E+11 | 0.00 | 0.288396E+09 | 0.00 | 0.89 |
September | 0.660698E+10 | 0.246276E+10 | 0.00 | 11757809.99 | 0.313146E+10 | 0.00 | 0.125538E+11 | 0.00 | 0.89 |
October | 0.743218E+10 | 36558070.37 | 0.00 | 37524304.24 | 0.399391E+09 | 0.00 | 0.321335E+11 | 0.00 | 0.92 |
November | 0.135488E+11 | 0.00 | 0.00 | 30068097.19 | 0.00 | 0.00 | 0.338259E+11 | 0.00 | 0.91 |
December | 0.290037E+11 | 0.00 | 0.00 | 9229725.94 | 0.00 | 0.00 | 0.141681E+11 | 0.00 | 0.89 |
Annual Sum or Average | 0.278188E+12 | 0.324589E+10 | 0.00 | 88905201.95 | 0.547806E+11 | 0.00 | 0.929908E+11 | 0.00 | 0.89 |
Minimum of Months | 0.476144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Maximum of Months | 0.451328E+11 | 0.246276E+10 | 0.00 | 37524304.24 | 0.255058E+11 | 0.00 | 0.338259E+11 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.458242E+10 | 0.00 | 0.00 | 136850.95 | 0.00 | 0.283276E+10 | 0.231863E+09 | 0.00 | 2.67 |
February | 0.447062E+10 | 0.00 | 0.00 | 220400.88 | 0.00 | 0.210738E+10 | 0.294395E+09 | 0.00 | 2.69 |
March | 0.647023E+10 | 0.00 | 0.00 | 546638.73 | 0.00 | 0.388656E+09 | 0.547946E+09 | 0.00 | 2.69 |
April | 0.685236E+10 | 1268721.44 | 0.00 | 470246.11 | 296100.35 | 49978883.63 | 0.325598E+09 | 0.00 | 2.70 |
May | 0.572722E+10 | 26126185.62 | 0.00 | 181429.55 | 15541537.07 | 0.00 | 0.181554E+09 | 0.00 | 2.70 |
June | 0.144531E+10 | 0.574127E+09 | 0.00 | 195542.92 | 0.120414E+10 | 0.00 | 73944604.76 | 0.00 | 2.73 |
July | 65155939.94 | 0.216481E+10 | 0.00 | 39181.23 | 0.221599E+10 | 0.00 | 15398910.69 | 0.00 | 2.76 |
August | 0.752290E+09 | 0.217737E+10 | 0.00 | 832371.32 | 0.669920E+09 | 0.00 | 0.180384E+09 | 0.00 | 2.89 |
September | 0.272753E+10 | 0.431667E+09 | 0.00 | 2110371.56 | 0.559459E+09 | 0.00 | 0.530720E+09 | 0.00 | 2.83 |
October | 0.525446E+10 | 94237072.83 | 0.00 | 2925039.25 | 3834617.84 | 0.00 | 0.132846E+10 | 0.00 | 2.84 |
November | 0.706284E+10 | 0.00 | 0.00 | 451059.39 | 0.00 | 0.304173E+09 | 0.405890E+09 | 0.00 | 2.71 |
December | 0.534341E+10 | 0.00 | 0.00 | 412667.94 | 0.00 | 0.158531E+10 | 0.380645E+09 | 0.00 | 2.71 |
Annual Sum or Average | 0.507538E+11 | 0.546960E+10 | 0.00 | 8521799.82 | 0.466918E+10 | 0.726826E+10 | 0.449680E+10 | 0.00 | 2.74 |
Minimum of Months | 65155939.94 | 0.00 | 0.00 | 39181.23 | 0.00 | 0.00 | 15398910.69 | 0.00 | 2.67 |
Maximum of Months | 0.706284E+10 | 0.217737E+10 | 0.00 | 2925039.25 | 0.221599E+10 | 0.283276E+10 | 0.132846E+10 | 0.00 | 2.89 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.471779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 |
February | 0.424159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.44 |
March | 0.448412E+10 | 0.00 | 0.00 | 9902.31 | 0.00 | 0.00 | 70758022.34 | 0.00 | 1.43 |
April | 0.409766E+10 | 0.00 | 0.00 | 209968.98 | 782255.81 | 0.00 | 0.363792E+09 | 0.00 | 1.44 |
May | 0.297861E+10 | 1313606.48 | 0.00 | 535057.27 | 23972557.00 | 0.00 | 0.672477E+09 | 0.00 | 1.45 |
June | 0.373850E+09 | 0.518362E+09 | 0.00 | 1028088.25 | 0.598719E+09 | 0.00 | 0.573445E+09 | 0.00 | 1.48 |
July | 3977130.37 | 0.178175E+10 | 0.00 | 320970.31 | 0.977092E+09 | 0.00 | 47404312.51 | 0.00 | 1.51 |
August | 70249930.92 | 0.137087E+10 | 0.00 | 1585271.82 | 0.384090E+09 | 0.00 | 0.526515E+09 | 0.00 | 1.54 |
September | 0.111600E+10 | 0.359335E+09 | 0.00 | 1326634.32 | 0.242937E+09 | 0.00 | 0.888456E+09 | 0.00 | 1.48 |
October | 0.283166E+10 | 8446250.01 | 0.00 | 1027738.50 | 37049286.57 | 0.00 | 0.115878E+10 | 0.00 | 1.45 |
November | 0.463205E+10 | 0.00 | 0.00 | 40768.94 | 0.00 | 0.00 | 0.151783E+09 | 0.00 | 1.44 |
December | 0.449728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.44 |
Annual Sum or Average | 0.340448E+11 | 0.404009E+10 | 0.00 | 6084400.69 | 0.226464E+10 | 0.00 | 0.445341E+10 | 0.00 | 1.46 |
Minimum of Months | 3977130.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 |
Maximum of Months | 0.471779E+10 | 0.178175E+10 | 0.00 | 1585271.82 | 0.977092E+09 | 0.00 | 0.115878E+10 | 0.00 | 1.54 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.305220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939015E+09 | 0.00 | 0.00 | 0.57 |
February | 0.261738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970977E+09 | 0.00 | 0.00 | 0.57 |
March | 0.383680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16592854.98 | 0.00 | 0.00 | 0.57 |
April | 0.377347E+10 | 0.00 | 0.00 | 0.00 | 661782.71 | 0.00 | 0.00 | 0.00 | 0.57 |
May | 0.307884E+10 | 0.00 | 0.00 | 3453.28 | 21387495.33 | 0.00 | 6863842.88 | 0.00 | 0.58 |
June | 0.778847E+09 | 0.121365E+09 | 0.00 | 79938.92 | 0.806744E+09 | 0.00 | 15342256.94 | 0.00 | 0.58 |
July | 16499643.98 | 0.688460E+09 | 0.00 | 107411.95 | 0.159260E+10 | 0.00 | 26033331.55 | 0.00 | 0.59 |
August | 0.367012E+09 | 0.658392E+09 | 0.00 | 355677.61 | 0.771836E+09 | 0.00 | 0.122104E+09 | 0.00 | 0.59 |
September | 0.163556E+10 | 59545007.93 | 0.00 | 99298.37 | 0.431399E+09 | 0.00 | 42665999.18 | 0.00 | 0.58 |
October | 0.336550E+10 | 0.00 | 0.00 | 0.00 | 38417941.96 | 0.00 | 0.00 | 0.00 | 0.58 |
November | 0.404712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
December | 0.377380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30872499.63 | 0.00 | 0.00 | 0.58 |
Annual Sum or Average | 0.303430E+11 | 0.152776E+10 | 0.00 | 645780.13 | 0.366305E+10 | 0.195746E+10 | 0.213009E+09 | 0.00 | 0.58 |
Minimum of Months | 16499643.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.404712E+10 | 0.688460E+09 | 0.00 | 355677.61 | 0.159260E+10 | 0.970977E+09 | 0.122104E+09 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105953E+10 | 0.00 | 0.00 | 0.53 |
February | 0.947934E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982462E+09 | 0.00 | 0.00 | 0.53 |
March | 0.198397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89013000.22 | 0.00 | 0.00 | 0.53 |
April | 0.202998E+10 | 0.00 | 0.00 | 0.00 | 356013.43 | 0.00 | 0.00 | 0.00 | 0.54 |
May | 0.165999E+10 | 0.00 | 0.00 | 0.00 | 11505643.17 | 0.00 | 0.00 | 0.00 | 0.54 |
June | 0.424067E+09 | 8508511.00 | 0.00 | 2689.49 | 0.489683E+09 | 0.00 | 2787322.68 | 0.00 | 0.54 |
July | 15505887.93 | 0.123799E+09 | 0.00 | 16283.64 | 0.108917E+10 | 0.00 | 7118988.56 | 0.00 | 0.54 |
August | 0.245029E+09 | 0.207994E+09 | 0.00 | 40835.97 | 0.543111E+09 | 0.00 | 16979730.34 | 0.00 | 0.54 |
September | 0.902072E+09 | 2129900.70 | 0.00 | 2822.47 | 0.261639E+09 | 0.00 | 761898.03 | 0.00 | 0.54 |
October | 0.181051E+10 | 0.00 | 0.00 | 0.00 | 20667363.09 | 0.00 | 0.00 | 0.00 | 0.54 |
November | 0.204815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129041E+09 | 0.00 | 0.00 | 0.54 |
December | 0.177130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275459E+09 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.149261E+11 | 0.342432E+09 | 0.00 | 62631.57 | 0.241613E+10 | 0.253551E+10 | 27647939.60 | 0.00 | 0.54 |
Minimum of Months | 15505887.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.204815E+10 | 0.207994E+09 | 0.00 | 40835.97 | 0.108917E+10 | 0.105953E+10 | 16979730.34 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.768413E+09 | 0.00 | 0.00 | 88623355.52 | 0.00 | 0.00 | 0.786716E+11 | 0.00 | 23.90 |
February | 0.685481E+09 | 0.00 | 0.00 | 80238294.84 | 0.00 | 0.00 | 0.706385E+11 | 0.00 | 24.05 |
March | 0.315788E+09 | 0.00 | 0.00 | 90713099.89 | 0.00 | 0.00 | 0.766947E+11 | 0.00 | 24.05 |
April | 0.258879E+09 | 11718728.47 | 0.00 | 92795183.50 | 0.00 | 0.00 | 0.752701E+11 | 0.00 | 24.11 |
May | 0.225493E+09 | 0.383193E+09 | 0.00 | 0.106627E+09 | 13022703.84 | 0.00 | 0.613990E+11 | 0.00 | 24.19 |
June | 68907981.71 | 0.184633E+11 | 0.00 | 52161459.95 | 93159505.24 | 0.00 | 0.155735E+11 | 0.00 | 24.36 |
July | 278518.67 | 0.448396E+11 | 0.00 | 6051195.53 | 0.128921E+09 | 0.00 | 0.778287E+09 | 0.00 | 24.20 |
August | 39033302.36 | 0.277892E+11 | 0.00 | 39662057.66 | 0.117407E+09 | 0.00 | 0.919684E+10 | 0.00 | 24.27 |
September | 0.121736E+09 | 0.100082E+11 | 0.00 | 74489764.29 | 19061472.74 | 0.00 | 0.329590E+11 | 0.00 | 24.21 |
October | 0.292866E+09 | 0.698621E+09 | 0.00 | 97281894.50 | 3645381.11 | 0.00 | 0.664192E+11 | 0.00 | 24.19 |
November | 0.388584E+09 | 0.00 | 0.00 | 87656175.27 | 0.00 | 0.00 | 0.802713E+11 | 0.00 | 24.18 |
December | 0.486099E+09 | 0.00 | 0.00 | 89722260.93 | 0.00 | 0.00 | 0.751371E+11 | 0.00 | 24.15 |
Annual Sum or Average | 0.365156E+10 | 0.102194E+12 | 0.00 | 0.906022E+09 | 0.375217E+09 | 0.00 | 0.643009E+12 | 0.00 | 24.16 |
Minimum of Months | 278518.67 | 0.00 | 0.00 | 6051195.53 | 0.00 | 0.00 | 0.778287E+09 | 0.00 | 23.90 |
Maximum of Months | 0.768413E+09 | 0.448396E+11 | 0.00 | 0.106627E+09 | 0.128921E+09 | 0.00 | 0.802713E+11 | 0.00 | 24.36 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.277807E+11 | 0.00 | 0.00 | 1810352.06 | 0.00 | 6437727.14 | 0.477167E+10 | 0.00 | 4.06 |
February | 0.225637E+11 | 0.00 | 0.00 | 2919715.11 | 0.00 | 0.00 | 0.671777E+10 | 0.00 | 4.08 |
March | 0.184856E+11 | 0.00 | 0.00 | 7273381.89 | 0.00 | 0.00 | 0.130485E+11 | 0.00 | 4.09 |
April | 0.157691E+11 | 5709803.33 | 0.00 | 9519538.52 | 439833.70 | 0.00 | 0.150094E+11 | 0.00 | 4.10 |
May | 0.841894E+10 | 0.131128E+09 | 0.00 | 12501157.64 | 43293518.09 | 0.00 | 0.167428E+11 | 0.00 | 4.11 |
June | 0.106304E+10 | 0.567457E+10 | 0.00 | 11171456.29 | 0.193890E+10 | 0.00 | 0.542228E+10 | 0.00 | 4.17 |
July | 28779138.12 | 0.164020E+11 | 0.00 | 2007348.46 | 0.235034E+10 | 0.00 | 0.327591E+09 | 0.00 | 4.23 |
August | 0.336821E+09 | 0.110635E+11 | 0.00 | 13207082.69 | 0.939723E+09 | 0.00 | 0.375477E+10 | 0.00 | 4.37 |
September | 0.280113E+10 | 0.325949E+10 | 0.00 | 22901536.77 | 0.949593E+09 | 0.00 | 0.110990E+11 | 0.00 | 4.28 |
October | 0.536362E+10 | 0.372130E+09 | 0.00 | 30208408.94 | 6358485.28 | 0.00 | 0.226442E+11 | 0.00 | 4.28 |
November | 0.193116E+11 | 0.00 | 0.00 | 7022059.96 | 0.00 | 0.00 | 0.137828E+11 | 0.00 | 4.11 |
December | 0.234310E+11 | 0.00 | 0.00 | 3800343.31 | 0.00 | 0.00 | 0.773825E+10 | 0.00 | 4.11 |
Annual Sum or Average | 0.145354E+12 | 0.369085E+11 | 0.00 | 0.124342E+09 | 0.622864E+10 | 6437727.14 | 0.121059E+12 | 0.00 | 4.17 |
Minimum of Months | 28779138.12 | 0.00 | 0.00 | 1810352.06 | 0.00 | 0.00 | 0.327591E+09 | 0.00 | 4.06 |
Maximum of Months | 0.277807E+11 | 0.164020E+11 | 0.00 | 30208408.94 | 0.235034E+10 | 6437727.14 | 0.226442E+11 | 0.00 | 4.37 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.966790E+11 | 0.00 | 0.00 | 1140112.13 | 0.00 | 0.00 | 0.488288E+10 | 0.00 | 1.83 |
February | 0.860913E+11 | 0.00 | 0.00 | 1215683.73 | 0.00 | 0.00 | 0.521907E+10 | 0.00 | 1.84 |
March | 0.763470E+11 | 0.00 | 0.00 | 8501634.30 | 0.00 | 0.00 | 0.217176E+11 | 0.00 | 1.84 |
April | 0.603024E+11 | 1071487.20 | 0.00 | 21644880.45 | 15768652.85 | 0.00 | 0.359398E+11 | 0.00 | 1.85 |
May | 0.304083E+11 | 0.118953E+09 | 0.00 | 46109824.24 | 0.425360E+09 | 0.00 | 0.486191E+11 | 0.00 | 1.87 |
June | 0.364672E+10 | 0.144433E+11 | 0.00 | 45475950.35 | 0.100088E+11 | 0.00 | 0.172084E+11 | 0.00 | 1.94 |
July | 51883650.00 | 0.477498E+11 | 0.00 | 8357919.51 | 0.131103E+11 | 0.00 | 0.113660E+10 | 0.00 | 1.99 |
August | 0.879960E+09 | 0.333570E+11 | 0.00 | 45032350.17 | 0.497229E+10 | 0.00 | 0.126787E+11 | 0.00 | 2.02 |
September | 0.889090E+10 | 0.967867E+10 | 0.00 | 60760565.74 | 0.364885E+10 | 0.00 | 0.352726E+11 | 0.00 | 1.94 |
October | 0.260216E+11 | 0.762226E+09 | 0.00 | 64193756.64 | 0.218227E+09 | 0.00 | 0.611945E+11 | 0.00 | 1.89 |
November | 0.750326E+11 | 0.00 | 0.00 | 13088516.75 | 0.00 | 0.00 | 0.280520E+11 | 0.00 | 1.85 |
December | 0.861994E+11 | 0.00 | 0.00 | 2682788.21 | 0.00 | 0.00 | 0.106139E+11 | 0.00 | 1.85 |
Annual Sum or Average | 0.550551E+12 | 0.106111E+12 | 0.00 | 0.318204E+09 | 0.323996E+11 | 0.00 | 0.282535E+12 | 0.00 | 1.89 |
Minimum of Months | 51883650.00 | 0.00 | 0.00 | 1140112.13 | 0.00 | 0.00 | 0.113660E+10 | 0.00 | 1.83 |
Maximum of Months | 0.966790E+11 | 0.477498E+11 | 0.00 | 64193756.64 | 0.131103E+11 | 0.00 | 0.611945E+11 | 0.00 | 2.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 61692004.57 | 0.00 | 0.00 | 496391.30 | 0.00 | 0.151197E+10 | 49348065.14 | 0.00 | 0.35 |
February | 63801272.34 | 0.00 | 0.00 | 815080.28 | 0.00 | 0.131864E+10 | 0.103294E+09 | 0.00 | 0.35 |
March | 64345584.27 | 37349.02 | 0.00 | 3420514.42 | 15399.90 | 0.100874E+10 | 0.483428E+09 | 0.00 | 0.35 |
April | 51258640.11 | 803694.06 | 0.00 | 7266132.66 | 0.00 | 0.550220E+09 | 0.785096E+09 | 0.00 | 0.35 |
May | 17674769.00 | 14493992.18 | 9446.10 | 13385093.77 | 633797.08 | 34978293.83 | 0.104088E+10 | 1080.36 | 0.36 |
June | 0.00 | 0.537760E+09 | 129636.06 | 7328245.05 | 0.00 | 496335.73 | 0.223578E+09 | 5858.05 | 0.36 |
July | 0.00 | 0.110914E+10 | 820019.65 | 309599.55 | 0.00 | 16103.23 | 1786432.54 | 15918.44 | 0.36 |
August | 0.00 | 0.765061E+09 | 409651.96 | 4067433.58 | 0.00 | 232322.07 | 80856769.76 | 8444.72 | 0.36 |
September | 5181335.13 | 0.265702E+09 | 171305.62 | 9524711.92 | 3857861.77 | 2500598.73 | 0.496992E+09 | 6457.61 | 0.35 |
October | 10079534.41 | 42993995.32 | 9329.16 | 10134146.27 | 0.00 | 0.108898E+09 | 0.974038E+09 | 1735.20 | 0.35 |
November | 69141020.57 | 0.00 | 0.00 | 1794932.33 | 0.00 | 0.104818E+10 | 0.391631E+09 | 0.00 | 0.36 |
December | 65184577.56 | 0.00 | 0.00 | 621010.55 | 0.00 | 0.141299E+10 | 88774267.03 | 0.00 | 0.36 |
Annual Sum or Average | 0.408359E+09 | 0.273599E+10 | 1549388.55 | 59163291.68 | 4507058.75 | 0.699786E+10 | 0.471970E+10 | 39494.37 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 309599.55 | 0.00 | 16103.23 | 1786432.54 | 0.00 | 0.35 |
Maximum of Months | 69141020.57 | 0.110914E+10 | 820019.65 | 13385093.77 | 3857861.77 | 0.151197E+10 | 0.104088E+10 | 15918.44 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 53877517.98 | 0.00 | 0.00 | 165215.10 | 0.00 | 0.155961E+10 | 9666008.66 | 0.00 | 0.35 |
February | 49507688.15 | 0.00 | 0.00 | 305700.76 | 0.00 | 0.140063E+10 | 35934506.04 | 0.00 | 0.35 |
March | 93729344.07 | 0.00 | 0.00 | 1883498.50 | 52742.74 | 0.119718E+10 | 0.266960E+09 | 0.00 | 0.35 |
April | 0.115718E+09 | 803599.90 | 0.00 | 5158135.64 | 0.00 | 0.626962E+09 | 0.645839E+09 | 0.00 | 0.35 |
May | 0.176893E+09 | 12928971.94 | 13652.34 | 10226724.16 | 2191486.99 | 37663303.43 | 0.882001E+09 | 2430.77 | 0.36 |
June | 93382787.09 | 0.428134E+09 | 247494.31 | 4346261.71 | 0.109444E+09 | 84589.43 | 0.133562E+09 | 6842.26 | 0.36 |
July | 1396546.03 | 0.948776E+09 | 576506.93 | 64753.44 | 0.160486E+09 | 0.00 | 650588.38 | 10038.72 | 0.36 |
August | 29284518.21 | 0.706543E+09 | 299592.12 | 2840204.89 | 58537843.55 | 27309.63 | 52994515.34 | 8098.20 | 0.36 |
September | 0.158225E+09 | 0.198883E+09 | 330775.24 | 5151329.60 | 70489088.62 | 2086565.74 | 0.348676E+09 | 3340.97 | 0.36 |
October | 0.166116E+09 | 34178459.44 | 46585.70 | 5150040.09 | 8768245.14 | 0.220490E+09 | 0.711264E+09 | 6730.73 | 0.35 |
November | 0.100099E+09 | 0.00 | 0.00 | 761118.91 | 0.00 | 0.120351E+10 | 0.206193E+09 | 0.00 | 0.36 |
December | 63061957.35 | 0.00 | 0.00 | 154050.76 | 0.00 | 0.149627E+10 | 7897138.07 | 0.00 | 0.36 |
Annual Sum or Average | 0.110129E+10 | 0.233025E+10 | 1514606.64 | 36207033.58 | 0.409970E+09 | 0.774452E+10 | 0.330164E+10 | 37481.65 | 0.36 |
Minimum of Months | 1396546.03 | 0.00 | 0.00 | 64753.44 | 0.00 | 0.00 | 650588.38 | 0.00 | 0.35 |
Maximum of Months | 0.176893E+09 | 0.948776E+09 | 576506.93 | 10226724.16 | 0.160486E+09 | 0.155961E+10 | 0.882001E+09 | 10038.72 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103024E+10 | 0.00 | 0.00 | 7115.25 | 3884537.56 | 0.00 | 20190270.83 | 0.00 | 0.02 |
February | 0.958718E+09 | 0.00 | 0.00 | 548620.58 | 0.00 | 0.00 | 0.423912E+09 | 0.00 | 0.02 |
March | 0.843551E+09 | 0.00 | 0.00 | 1351975.04 | 0.00 | 0.00 | 0.767492E+09 | 0.00 | 0.02 |
April | 0.621655E+09 | 0.00 | 0.00 | 2158900.99 | 0.00 | 0.00 | 0.783144E+09 | 0.00 | 0.02 |
May | 0.201875E+09 | 30970977.45 | 0.00 | 2411619.52 | 0.00 | 0.00 | 0.922235E+09 | 0.00 | 0.02 |
June | 0.00 | 0.626522E+09 | 0.00 | 1416638.88 | 0.00 | 0.00 | 0.202203E+09 | 0.00 | 0.02 |
July | 0.00 | 0.114215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
August | 0.00 | 0.787536E+09 | 0.00 | 1242755.97 | 0.00 | 0.00 | 20435089.03 | 0.00 | 0.02 |
September | 37572021.32 | 0.327925E+09 | 0.00 | 3023403.58 | 7128067.34 | 0.00 | 0.424657E+09 | 0.00 | 0.02 |
October | 84877373.61 | 86953394.93 | 0.00 | 4564528.88 | 0.00 | 0.00 | 0.961309E+09 | 0.00 | 0.02 |
November | 0.104874E+10 | 0.00 | 0.00 | 1106721.87 | 0.00 | 0.00 | 0.542636E+09 | 0.00 | 0.02 |
December | 0.113437E+10 | 0.00 | 0.00 | 576860.18 | 0.00 | 0.00 | 0.354964E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.596160E+10 | 0.300205E+10 | 0.00 | 18409140.74 | 11012604.90 | 0.00 | 0.542318E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.113437E+10 | 0.114215E+10 | 0.00 | 4564528.88 | 7128067.34 | 0.00 | 0.961309E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109399E+10 | 0.00 | 0.00 | 5521900.86 | 0.00 | 0.154873E+11 | 0.543251E+10 | 0.00 | 0.40 |
February | 0.104645E+10 | 0.00 | 0.00 | 4108068.21 | 0.00 | 0.149586E+11 | 0.415262E+10 | 0.00 | 0.40 |
March | 0.131214E+10 | 0.00 | 0.00 | 27909141.33 | 715423.66 | 0.464614E+10 | 0.151710E+11 | 0.00 | 0.40 |
April | 0.166347E+10 | 10582348.74 | 0.00 | 73934339.20 | 318001.78 | 0.151508E+09 | 0.170155E+11 | 0.00 | 0.40 |
May | 0.276882E+10 | 0.167009E+09 | 181503.53 | 0.134223E+09 | 38122047.53 | 14923711.82 | 0.120949E+11 | 5931.13 | 0.40 |
June | 0.130411E+10 | 0.574384E+10 | 61823.28 | 50238024.14 | 0.155148E+10 | 415078.68 | 0.178371E+10 | 889.72 | 0.41 |
July | 18943309.11 | 0.128532E+11 | 0.00 | 621469.55 | 0.220120E+10 | 0.00 | 9081713.10 | 0.00 | 0.40 |
August | 0.400327E+09 | 0.955518E+10 | 147664.27 | 28331506.17 | 0.826712E+09 | 146476.29 | 0.726157E+09 | 859.60 | 0.40 |
September | 0.225534E+10 | 0.264738E+10 | 82263.72 | 69204975.41 | 0.101093E+10 | 2495858.36 | 0.464694E+10 | 6734.41 | 0.40 |
October | 0.231295E+10 | 0.398910E+09 | 526472.94 | 71207038.30 | 0.183825E+09 | 81763619.29 | 0.124959E+11 | 7611.56 | 0.40 |
November | 0.136654E+10 | 0.00 | 0.00 | 30561168.33 | 0.00 | 0.421352E+10 | 0.148793E+11 | 0.00 | 0.40 |
December | 0.111219E+10 | 0.00 | 0.00 | 6387144.79 | 0.00 | 0.129202E+11 | 0.722184E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.166553E+11 | 0.313761E+11 | 999727.74 | 0.502247E+09 | 0.581330E+10 | 0.524771E+11 | 0.956294E+11 | 22026.41 | 0.40 |
Minimum of Months | 18943309.11 | 0.00 | 0.00 | 621469.55 | 0.00 | 0.00 | 9081713.10 | 0.00 | 0.40 |
Maximum of Months | 0.276882E+10 | 0.128532E+11 | 526472.94 | 0.134223E+09 | 0.220120E+10 | 0.154873E+11 | 0.170155E+11 | 7611.56 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 63946531.99 | 0.00 | 0.00 | 511564.67 | 0.00 | 0.147903E+10 | 80015291.71 | 0.00 | 0.35 |
February | 65485111.30 | 0.00 | 0.00 | 876460.76 | 0.00 | 0.128794E+10 | 0.132250E+09 | 0.00 | 0.35 |
March | 57853362.19 | 0.00 | 0.00 | 3253318.55 | 52748.92 | 0.104135E+10 | 0.457483E+09 | 0.00 | 0.35 |
April | 40957212.31 | 803694.06 | 0.00 | 7294833.49 | 0.00 | 0.537775E+09 | 0.807813E+09 | 0.00 | 0.35 |
May | 16168145.91 | 14890784.18 | 0.00 | 13625065.16 | 247531.53 | 34045314.86 | 0.104308E+10 | 0.00 | 0.36 |
June | 0.00 | 0.537875E+09 | 18810.91 | 7695757.82 | 0.00 | 127269.60 | 0.223580E+09 | 1577.82 | 0.36 |
July | 0.00 | 0.110982E+10 | 158273.09 | 414666.86 | 0.00 | 7815.23 | 1689653.23 | 1565.25 | 0.36 |
August | 0.00 | 0.765479E+09 | 0.00 | 4596369.03 | 0.00 | 20208.65 | 80539947.73 | 0.00 | 0.36 |
September | 4979724.39 | 0.265662E+09 | 212004.47 | 9955671.31 | 3857861.77 | 1389388.69 | 0.497874E+09 | 5434.66 | 0.35 |
October | 9965702.66 | 43005059.67 | 0.00 | 10094895.41 | 0.00 | 0.125955E+09 | 0.957134E+09 | 0.00 | 0.35 |
November | 66714128.45 | 0.00 | 0.00 | 2507407.42 | 0.00 | 0.992564E+09 | 0.448957E+09 | 0.00 | 0.36 |
December | 69160066.16 | 0.00 | 0.00 | 927708.68 | 0.00 | 0.136782E+10 | 0.129663E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.395230E+09 | 0.273754E+10 | 389088.47 | 61753719.16 | 4158142.22 | 0.686802E+10 | 0.486007E+10 | 8577.74 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 414666.86 | 0.00 | 7815.23 | 1689653.23 | 0.00 | 0.35 |
Maximum of Months | 69160066.16 | 0.110982E+10 | 212004.47 | 13625065.16 | 3857861.77 | 0.147903E+10 | 0.104308E+10 | 5434.66 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 45276102.77 | 0.00 | 0.00 | 116729.29 | 0.00 | 0.154672E+10 | 31201648.56 | 0.00 | 0.35 |
February | 43221856.72 | 0.00 | 0.00 | 252499.57 | 0.00 | 0.139641E+10 | 46494233.86 | 0.00 | 0.35 |
March | 93022422.99 | 0.00 | 0.00 | 1537338.25 | 52742.74 | 0.119308E+10 | 0.272111E+09 | 0.00 | 0.35 |
April | 0.110042E+09 | 803599.90 | 0.00 | 5242200.77 | 0.00 | 0.590896E+09 | 0.687496E+09 | 0.00 | 0.35 |
May | 0.165639E+09 | 13382658.79 | 0.00 | 10852346.59 | 1753883.25 | 38339395.69 | 0.891953E+09 | 0.00 | 0.36 |
June | 90529991.63 | 0.429019E+09 | 113099.64 | 5036295.65 | 0.108697E+09 | 22639.53 | 0.135787E+09 | 3103.03 | 0.36 |
July | 1361009.87 | 0.950964E+09 | 126537.92 | 76826.44 | 0.158758E+09 | 0.00 | 674051.53 | 541.21 | 0.36 |
August | 27579346.62 | 0.707775E+09 | 23741.66 | 3033251.60 | 57589200.71 | 2495.83 | 54531454.03 | 867.34 | 0.36 |
September | 0.153795E+09 | 0.197376E+09 | 232841.91 | 6332493.91 | 72095408.81 | 1432750.28 | 0.352578E+09 | 1938.23 | 0.36 |
October | 0.163461E+09 | 34330545.35 | 29024.13 | 5148864.60 | 8638466.15 | 0.218627E+09 | 0.715784E+09 | 1985.38 | 0.35 |
November | 0.100021E+09 | 0.00 | 0.00 | 1035926.67 | 0.00 | 0.112194E+10 | 0.287568E+09 | 0.00 | 0.36 |
December | 59501971.55 | 0.00 | 0.00 | 186030.24 | 0.00 | 0.146799E+10 | 39708049.27 | 0.00 | 0.36 |
Annual Sum or Average | 0.105345E+10 | 0.233365E+10 | 525245.27 | 38850803.58 | 0.407585E+09 | 0.757546E+10 | 0.351589E+10 | 8435.19 | 0.36 |
Minimum of Months | 1361009.87 | 0.00 | 0.00 | 76826.44 | 0.00 | 0.00 | 674051.53 | 0.00 | 0.35 |
Maximum of Months | 0.165639E+09 | 0.950964E+09 | 232841.91 | 10852346.59 | 0.158758E+09 | 0.154672E+10 | 0.891953E+09 | 3103.03 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.206708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.618503E+10 | 0.00 | 0.00 | 0.53 |
February | 0.200718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407327E+10 | 0.00 | 0.00 | 0.53 |
March | 0.257624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166097E+09 | 0.00 | 0.00 | 0.53 |
April | 0.253906E+11 | 0.00 | 0.00 | 0.00 | 4452954.03 | 0.00 | 0.00 | 0.00 | 0.53 |
May | 0.207629E+11 | 0.00 | 0.00 | 0.00 | 0.143911E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
June | 0.532537E+10 | 56504905.48 | 0.00 | 5566.74 | 0.617479E+10 | 0.00 | 13667760.05 | 0.00 | 0.54 |
July | 0.200783E+09 | 0.116338E+10 | 0.00 | 203956.24 | 0.140065E+11 | 0.00 | 82204285.80 | 0.00 | 0.54 |
August | 0.260660E+10 | 0.320172E+10 | 0.00 | 1398882.71 | 0.617530E+10 | 0.00 | 0.670239E+09 | 0.00 | 0.54 |
September | 0.112360E+11 | 0.492630E+09 | 0.00 | 105039.74 | 0.280655E+10 | 0.00 | 56459923.21 | 0.00 | 0.53 |
October | 0.226455E+11 | 0.00 | 0.00 | 0.00 | 0.258504E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
November | 0.270868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145122E+09 | 0.00 | 0.00 | 0.53 |
December | 0.232967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230382E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.205056E+12 | 0.491424E+10 | 0.00 | 1713445.43 | 0.295700E+11 | 0.128733E+11 | 0.822571E+09 | 0.00 | 0.53 |
Minimum of Months | 0.200783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.270868E+11 | 0.320172E+10 | 0.00 | 1398882.71 | 0.140065E+11 | 0.618503E+10 | 0.670239E+09 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 13347904.21 | 0.00 | 0.00 | 114433.06 | 0.00 | 0.384523E+09 | 7890619.38 | 0.00 | 0.35 |
February | 14645595.90 | 0.00 | 0.00 | 190772.04 | 0.00 | 0.342468E+09 | 14333495.84 | 0.00 | 0.35 |
March | 15368691.22 | 9337.25 | 0.00 | 819647.14 | 3849.98 | 0.285694E+09 | 88101808.23 | 0.00 | 0.35 |
April | 12885750.39 | 200923.52 | 0.00 | 1775118.20 | 0.00 | 0.171574E+09 | 0.162226E+09 | 0.00 | 0.35 |
May | 3306350.33 | 3713931.78 | 2322.66 | 3282736.26 | 68015.54 | 30486062.49 | 0.239653E+09 | 308.96 | 0.36 |
June | 0.00 | 0.134414E+09 | 32800.54 | 1779817.79 | 25952.08 | 95047.67 | 55975783.96 | 1412.78 | 0.36 |
July | 0.00 | 0.277254E+09 | 235031.26 | 72866.10 | 0.00 | 4025.81 | 451141.92 | 5609.27 | 0.36 |
August | 0.00 | 0.191219E+09 | 146647.60 | 967225.54 | 0.00 | 64913.17 | 20256992.64 | 3604.31 | 0.36 |
September | 1244931.10 | 66399770.81 | 67154.18 | 2248410.75 | 964465.44 | 3628804.71 | 0.121428E+09 | 3019.61 | 0.35 |
October | 4042691.27 | 10748498.83 | 2131.26 | 2216107.10 | 0.00 | 68315611.73 | 0.201213E+09 | 634.83 | 0.35 |
November | 17576044.58 | 0.00 | 0.00 | 341755.71 | 0.00 | 0.290932E+09 | 68835893.44 | 0.00 | 0.36 |
December | 14667628.20 | 0.00 | 0.00 | 139240.23 | 0.00 | 0.366054E+09 | 11031698.74 | 0.00 | 0.36 |
Annual Sum or Average | 97085587.20 | 0.683960E+09 | 486087.49 | 13948129.92 | 1062283.04 | 0.194384E+10 | 0.991397E+09 | 14589.76 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 72866.10 | 0.00 | 4025.81 | 451141.92 | 0.00 | 0.35 |
Maximum of Months | 17576044.58 | 0.277254E+09 | 235031.26 | 3282736.26 | 964465.44 | 0.384523E+09 | 0.239653E+09 | 5609.27 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 6963962.72 | 0.00 | 0.00 | 29654.84 | 0.00 | 0.396584E+09 | 2250848.46 | 0.00 | 0.35 |
February | 8969617.67 | 0.00 | 0.00 | 52061.77 | 0.00 | 0.355201E+09 | 7371353.87 | 0.00 | 0.35 |
March | 22452791.90 | 0.00 | 0.00 | 423092.81 | 13185.69 | 0.316913E+09 | 50149678.37 | 0.00 | 0.35 |
April | 27814790.69 | 200899.97 | 0.00 | 1269811.17 | 0.00 | 0.186719E+09 | 0.132616E+09 | 0.00 | 0.35 |
May | 42952843.19 | 3299034.64 | 1734.68 | 2594397.79 | 482782.12 | 30875333.15 | 0.200274E+09 | 584.06 | 0.36 |
June | 23345696.77 | 0.107104E+09 | 48989.15 | 1120357.93 | 27303535.72 | 33225.89 | 33344590.79 | 1271.05 | 0.36 |
July | 349136.51 | 0.237174E+09 | 163002.78 | 14285.51 | 40121586.40 | 0.00 | 164549.95 | 3396.64 | 0.36 |
August | 7321129.55 | 0.176599E+09 | 111040.74 | 693107.76 | 14634460.89 | 11369.47 | 13261030.24 | 2253.16 | 0.36 |
September | 39263680.53 | 49732205.96 | 53486.88 | 1179382.65 | 17639719.56 | 3188423.43 | 84903180.75 | 1096.71 | 0.36 |
October | 41675755.88 | 8560647.12 | 10875.31 | 1047130.74 | 2176694.71 | 0.101370E+09 | 0.131662E+09 | 1788.11 | 0.35 |
November | 21807199.35 | 0.00 | 0.00 | 133957.80 | 0.00 | 0.332320E+09 | 23379999.83 | 0.00 | 0.36 |
December | 10483937.70 | 0.00 | 0.00 | 24442.29 | 0.00 | 0.380012E+09 | 1325894.61 | 0.00 | 0.36 |
Annual Sum or Average | 0.253401E+09 | 0.582671E+09 | 389129.54 | 8581683.06 | 0.102372E+09 | 0.210323E+10 | 0.680703E+09 | 10389.73 | 0.36 |
Minimum of Months | 349136.51 | 0.00 | 0.00 | 14285.51 | 0.00 | 0.00 | 164549.95 | 0.00 | 0.35 |
Maximum of Months | 42952843.19 | 0.237174E+09 | 163002.78 | 2594397.79 | 40121586.40 | 0.396584E+09 | 0.200274E+09 | 3396.64 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 71278945.20 | 0.00 | 0.00 | 3159847.89 | 0.00 | 0.207266E+10 | 0.460455E+09 | 0.00 | 0.40 |
February | 42550027.68 | 0.00 | 0.00 | 4285746.10 | 0.00 | 0.166849E+10 | 0.672252E+09 | 0.00 | 0.40 |
March | 48685910.87 | 84721.22 | 0.00 | 7926029.46 | 0.00 | 0.116856E+10 | 0.128028E+10 | 0.00 | 0.40 |
April | 55023010.49 | 1290830.98 | 0.00 | 11342763.04 | 0.00 | 0.634223E+09 | 0.153809E+10 | 0.00 | 0.40 |
May | 20576434.18 | 23151950.65 | 0.00 | 17042765.05 | 1162036.34 | 29697353.63 | 0.171052E+10 | 0.00 | 0.40 |
June | 0.00 | 0.863408E+09 | 250721.00 | 8709077.70 | 263794.40 | 788185.61 | 0.362164E+09 | 3969.07 | 0.40 |
July | 0.00 | 0.178189E+10 | 857236.81 | 435421.57 | 0.00 | 38415.97 | 2918510.17 | 13627.09 | 0.40 |
August | 0.00 | 0.122938E+10 | 73258.34 | 5650368.94 | 0.00 | 159528.69 | 0.130962E+09 | 1421.89 | 0.40 |
September | 7998046.57 | 0.426950E+09 | 85329.20 | 15137095.17 | 6196197.96 | 1614194.05 | 0.801117E+09 | 572.39 | 0.40 |
October | 8657746.68 | 69071386.89 | 0.00 | 19836926.20 | 0.00 | 55302820.64 | 0.168800E+10 | 0.00 | 0.40 |
November | 60120801.83 | 0.00 | 0.00 | 7564355.14 | 0.00 | 0.109205E+10 | 0.126671E+10 | 0.00 | 0.40 |
December | 64475750.80 | 0.00 | 0.00 | 5041362.98 | 0.00 | 0.173990E+10 | 0.708293E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.379367E+09 | 0.439523E+10 | 1266545.36 | 0.106132E+09 | 7622028.69 | 0.846348E+10 | 0.106218E+11 | 19590.45 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 435421.57 | 0.00 | 38415.97 | 2918510.17 | 0.00 | 0.40 |
Maximum of Months | 71278945.20 | 0.178189E+10 | 857236.81 | 19836926.20 | 6196197.96 | 0.207266E+10 | 0.171052E+10 | 13627.09 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.132606E+11 | 0.00 | 0.00 | 32848928.01 | 0.00 | 0.00 | 0.341929E+11 | 0.00 | 4.40 |
February | 0.114792E+11 | 0.00 | 0.00 | 29227590.97 | 0.00 | 0.00 | 0.310014E+11 | 0.00 | 4.41 |
March | 0.568110E+10 | 0.00 | 0.00 | 45837921.18 | 0.00 | 0.00 | 0.416950E+11 | 0.00 | 4.55 |
April | 0.193819E+10 | 7773727.92 | 0.00 | 59074559.37 | 0.00 | 0.00 | 0.465163E+11 | 0.00 | 4.75 |
May | 0.423664E+09 | 0.262194E+09 | 0.00 | 84012542.68 | 525828.52 | 0.00 | 0.421703E+11 | 0.00 | 5.03 |
June | 14734953.57 | 0.128753E+11 | 0.00 | 48240842.76 | 9677607.71 | 0.00 | 0.118490E+11 | 0.00 | 5.40 |
July | 80023.02 | 0.327431E+11 | 0.00 | 5906396.54 | 0.00 | 0.00 | 0.661193E+09 | 0.00 | 5.52 |
August | 9073939.92 | 0.200547E+11 | 0.00 | 35848320.16 | 17167403.85 | 0.00 | 0.751631E+10 | 0.00 | 5.48 |
September | 0.220065E+09 | 0.683340E+10 | 0.00 | 61451380.62 | 18436139.35 | 0.00 | 0.233965E+11 | 0.00 | 5.17 |
October | 0.137031E+10 | 0.436646E+09 | 0.00 | 65889335.79 | 15635151.77 | 0.00 | 0.429137E+11 | 0.00 | 4.87 |
November | 0.575852E+10 | 0.00 | 0.00 | 44026852.83 | 0.00 | 0.00 | 0.441797E+11 | 0.00 | 4.59 |
December | 0.101186E+11 | 0.00 | 0.00 | 36862218.97 | 0.00 | 0.00 | 0.352845E+11 | 0.00 | 4.46 |
Annual Sum or Average | 0.502741E+11 | 0.732131E+11 | 0.00 | 0.549227E+09 | 61442131.20 | 0.00 | 0.361377E+12 | 0.00 | 4.89 |
Minimum of Months | 80023.02 | 0.00 | 0.00 | 5906396.54 | 0.00 | 0.00 | 0.661193E+09 | 0.00 | 4.40 |
Maximum of Months | 0.132606E+11 | 0.327431E+11 | 0.00 | 84012542.68 | 18436139.35 | 0.00 | 0.465163E+11 | 0.00 | 5.52 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.740375E+10 | 0.00 | 0.00 | 45000189.85 | 0.00 | 0.00 | 0.435547E+11 | 0.00 | 4.72 |
February | 0.726165E+10 | 0.00 | 0.00 | 40394776.63 | 0.00 | 0.00 | 0.382887E+11 | 0.00 | 4.73 |
March | 0.215831E+10 | 0.00 | 0.00 | 61004961.14 | 0.00 | 0.00 | 0.492538E+11 | 0.00 | 4.93 |
April | 0.572569E+09 | 8263256.90 | 0.00 | 74899719.60 | 0.00 | 0.00 | 0.520568E+11 | 0.00 | 5.15 |
May | 29775359.28 | 0.281487E+09 | 0.00 | 98764013.42 | 0.00 | 0.00 | 0.461321E+11 | 0.00 | 5.44 |
June | 0.00 | 0.137655E+11 | 0.00 | 53444543.70 | 0.00 | 0.00 | 0.126653E+11 | 0.00 | 5.76 |
July | 0.00 | 0.348289E+11 | 0.00 | 6399077.77 | 0.00 | 0.00 | 0.696187E+09 | 0.00 | 5.86 |
August | 818165.47 | 0.213110E+11 | 0.00 | 39380996.03 | 0.00 | 0.00 | 0.795967E+10 | 0.00 | 5.82 |
September | 35292836.67 | 0.731385E+10 | 0.00 | 70057411.21 | 992665.74 | 0.00 | 0.253430E+11 | 0.00 | 5.54 |
October | 0.468828E+09 | 0.474743E+09 | 0.00 | 80050549.09 | 8482736.89 | 0.00 | 0.472952E+11 | 0.00 | 5.24 |
November | 0.233902E+10 | 0.00 | 0.00 | 57967266.37 | 0.00 | 0.00 | 0.517953E+11 | 0.00 | 4.97 |
December | 0.385498E+10 | 0.00 | 0.00 | 50147760.09 | 0.00 | 0.00 | 0.452255E+11 | 0.00 | 4.82 |
Annual Sum or Average | 0.241250E+11 | 0.779837E+11 | 0.00 | 0.677511E+09 | 9475402.63 | 0.00 | 0.420266E+12 | 0.00 | 5.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 6399077.77 | 0.00 | 0.00 | 0.696187E+09 | 0.00 | 4.72 |
Maximum of Months | 0.740375E+10 | 0.348289E+11 | 0.00 | 98764013.42 | 8482736.89 | 0.00 | 0.520568E+11 | 0.00 | 5.86 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 61582302.35 | 0.00 | 0.00 | 0.103903E+09 | 0.00 | 0.00 | 0.662628E+11 | 0.00 | 19.86 |
February | 41060274.96 | 0.00 | 0.00 | 94386395.70 | 0.00 | 0.00 | 0.598314E+11 | 0.00 | 20.09 |
March | 0.00 | 0.00 | 0.00 | 0.109291E+09 | 0.00 | 0.00 | 0.663410E+11 | 0.00 | 20.66 |
April | 0.00 | 13973396.11 | 0.00 | 0.114936E+09 | 0.00 | 0.00 | 0.652530E+11 | 0.00 | 21.21 |
May | 0.00 | 0.451778E+09 | 0.00 | 0.134119E+09 | 0.00 | 0.00 | 0.521647E+11 | 0.00 | 21.75 |
June | 0.00 | 0.180254E+11 | 0.00 | 63809856.94 | 0.00 | 0.00 | 0.128415E+11 | 0.00 | 22.17 |
July | 0.00 | 0.423031E+11 | 0.00 | 6442106.98 | 0.00 | 0.00 | 0.611436E+09 | 0.00 | 22.26 |
August | 0.00 | 0.268928E+11 | 0.00 | 46028305.03 | 0.00 | 0.00 | 0.738795E+10 | 0.00 | 22.24 |
September | 0.00 | 0.934226E+10 | 0.00 | 94417571.00 | 0.00 | 0.00 | 0.279627E+11 | 0.00 | 21.88 |
October | 0.00 | 0.808872E+09 | 0.00 | 0.120071E+09 | 0.00 | 0.00 | 0.575403E+11 | 0.00 | 21.48 |
November | 9945442.39 | 0.00 | 0.00 | 0.104229E+09 | 0.00 | 0.00 | 0.692614E+11 | 0.00 | 20.71 |
December | 0.00 | 0.00 | 0.00 | 0.105192E+09 | 0.00 | 0.00 | 0.639454E+11 | 0.00 | 20.29 |
Annual Sum or Average | 0.112588E+09 | 0.978381E+11 | 0.00 | 0.109683E+10 | 0.00 | 0.00 | 0.549404E+12 | 0.00 | 21.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 6442106.98 | 0.00 | 0.00 | 0.611436E+09 | 0.00 | 19.86 |
Maximum of Months | 61582302.35 | 0.423031E+11 | 0.00 | 0.134119E+09 | 0.00 | 0.00 | 0.692614E+11 | 0.00 | 22.26 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105575E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455817E+10 | 0.00 | 0.00 | 1.12 |
February | 0.929729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429270E+10 | 0.00 | 0.00 | 1.12 |
March | 0.143706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223164E+09 | 0.00 | 0.00 | 1.12 |
April | 0.142911E+11 | 0.00 | 0.00 | 0.00 | 2506333.60 | 0.00 | 0.00 | 0.00 | 1.13 |
May | 0.116375E+11 | 50504747.53 | 0.00 | 32558.48 | 31312769.38 | 0.00 | 48768518.26 | 0.00 | 1.13 |
June | 0.287369E+10 | 0.130628E+10 | 0.00 | 428310.05 | 0.222281E+10 | 0.00 | 0.130963E+09 | 0.00 | 1.15 |
July | 74841850.02 | 0.555767E+10 | 0.00 | 295391.67 | 0.319950E+10 | 0.00 | 84271214.85 | 0.00 | 1.17 |
August | 0.147190E+10 | 0.467062E+10 | 0.00 | 1160338.14 | 0.923788E+09 | 0.00 | 0.371674E+09 | 0.00 | 1.19 |
September | 0.616055E+10 | 0.570290E+09 | 0.00 | 536595.46 | 0.130659E+10 | 0.00 | 0.195141E+09 | 0.00 | 1.14 |
October | 0.127460E+11 | 15575176.02 | 0.00 | 0.00 | 0.129923E+09 | 0.00 | 0.00 | 0.00 | 1.13 |
November | 0.149264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401021E+09 | 0.00 | 0.00 | 1.13 |
December | 0.133302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107905E+10 | 0.00 | 0.00 | 1.13 |
Annual Sum or Average | 0.111738E+12 | 0.121709E+11 | 0.00 | 2453193.80 | 0.781643E+10 | 0.105541E+11 | 0.830817E+09 | 0.00 | 1.14 |
Minimum of Months | 74841850.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 |
Maximum of Months | 0.149264E+11 | 0.555767E+10 | 0.00 | 1160338.14 | 0.319950E+10 | 0.455817E+10 | 0.371674E+09 | 0.00 | 1.19 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:02:50
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.140071E+12 | 0.521943E+10 | 0.251524E+12 | 0.107288E+13 | 0.695501E+11 |
February | 0.231559E+12 | 0.499891E+10 | 0.238527E+12 | 0.102677E+13 | 0.651638E+11 |
March | 0.415371E+12 | 0.427753E+10 | 0.205334E+12 | 0.894034E+12 | 0.763073E+11 |
April | 0.442917E+12 | 0.304546E+10 | 0.141160E+12 | 0.617825E+12 | 0.156476E+12 |
May | 0.571535E+12 | 0.217809E+10 | 0.880564E+11 | 0.391581E+12 | 0.330312E+12 |
June | 0.567902E+12 | -726308702.9 | -0.168530E+11 | -0.844543E+11 | 0.930143E+12 |
July | 0.540045E+12 | -0.289151E+10 | -0.109499E+12 | -0.530925E+12 | 0.139341E+13 |
August | 0.515234E+12 | -0.150025E+10 | -0.684024E+11 | -0.316397E+12 | 0.119851E+13 |
September | 0.354036E+12 | 0.556486E+09 | 0.276516E+11 | 0.115493E+12 | 0.694664E+12 |
October | 0.340982E+12 | 0.242687E+10 | 0.102690E+12 | 0.474240E+12 | 0.338819E+12 |
November | 0.165400E+12 | 0.369877E+10 | 0.179500E+12 | 0.785909E+12 | 0.918506E+11 |
December | 0.112589E+12 | 0.472246E+10 | 0.233153E+12 | 0.997877E+12 | 0.622423E+11 |
Annual Sum or Average | 0.439764E+13 | 0.260059E+11 | 0.127284E+13 | 0.544483E+13 | 0.540745E+13 |
Minimum of Months | 0.112589E+12 | -0.289151E+10 | -0.109499E+12 | -0.530925E+12 | 0.622423E+11 |
Maximum of Months | 0.571535E+12 | 0.521943E+10 | 0.251524E+12 | 0.107288E+13 | 0.139341E+13 |