Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2023-10-16 09:03:03
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 9193.99 | 810.38 | 810.38 |
Net Site Energy | 9193.99 | 810.38 | 810.38 |
Total Source Energy | 22866.57 | 2015.51 | 2015.51 |
Net Source Energy | 22866.57 | 2015.51 | 2015.51 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 392.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1689.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 543.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 174.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 641.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 611.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 134.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 150.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 475.79 | 819.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 43.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 6193.13 | 3000.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 392.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1689.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 543.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 174.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 952.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 22.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 611.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 134.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 150.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.75 | 819.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Other | 385.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 20.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 392.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1689.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 543.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 174.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 641.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 611.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 134.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 150.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 475.79 | 819.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 43.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 63.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 256.60 | 106.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 225.97 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 545.88 | 264.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 63.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 256.60 | 106.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 225.97 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 545.88 | 264.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 6193.126 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 6193.126 | 100.00 |
Total On-Site and Utility Electric Sources | 6193.126 | 100.00 |
Total Electricity End Uses | 6193.126 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 499.55 | 64.66 |
Air to Air Heat Recovery for Heating | 272.99 | 35.34 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 772.53 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 76.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7330.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYSLAUNDRY HPWH TANK | SWHSYS1 HPWH TANK |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| SWHSYS1 HPWH FAN | SWHSYSLAUNDRY HPWH FAN | FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 5.9798 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 8.7295 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 8.7295 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.1656 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 3.6813 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.1344 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 8.3313 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 8.1375 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 3.9719 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 3.9719 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 3.9719 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 3.9719 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 8.3313 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 8.3313 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 10.5594 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 3.9719 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.2589 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.2589 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.9798 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 8.7295 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 8.7295 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.1656 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 3.6813 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.1344 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 8.3313 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 8.1375 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 3.9719 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 3.9719 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 3.9719 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 3.9719 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 3.9719 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 3.9719 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 3.9719 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 3.9719 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 3.9719 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 3.9719 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 8.3313 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 8.3313 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 10.5594 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 3.9719 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.2589 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.2589 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.3293 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-JUN-19:30 | 07-DEC-20:00 | - | - | - | - | - | - | - | - | - | - | 24-JAN-21:00 |
Heating | 0.00 | 127860.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 163272.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 45424.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 87982.85 | 89710.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31572.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 40833.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6314.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 39568.85 | 80105.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1670.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 437675.20 | 297676.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 127860.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 163272.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 45424.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58308.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1268.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 40833.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 6314.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3932.42 | 80105.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 769.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 660.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 425.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5349.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1722.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5473.02 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2031.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1936.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 427.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 475.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1506.82 | 888.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 138.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 19613.63 | 3252.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 37.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 471.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 151.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 170.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 37.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 41.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 132.81 | 78.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1728.79 | 286.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 37.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 471.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 151.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 170.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 37.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 41.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 132.81 | 78.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1728.79 | 286.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.35 | 0.641157 | 0.500000 | 1.18 | 1.00 | 0.500000 | 0.000594 | 0.000049 | 1.18 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.368816 | 0.138574 | 0.500000 | 0.184408 | 0.500000 | 0.500000 | 0.002749 | 0.000029 | 0.184408 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.256356 | 0.230865 | 0.500000 | 0.128178 | 0.615640 | 0.500000 | 0.001650 | 0.000013 | 0.128178 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.246191 | 0.508359 | 0.500000 | 0.123095 | 1.00 | 0.500000 | 0.000749 | 0.000020 | 0.123095 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.135714 | 0.532048 | 0.500000 | 0.067857 | 1.00 | 0.500000 | 0.000716 | 0.000012 | 0.067857 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.64 | 0.064844 | 0.500000 | 1.82 | 0.500000 | 0.500000 | 0.023316 | 0.000096 | 1.82 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.56 | 0.092187 | 0.500000 | 0.780549 | 0.500000 | 0.500000 | 0.004133 | 0.000086 | 0.780549 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.15 | 0.193547 | 0.500000 | 2.58 | 0.516125 | 0.500000 | 0.001969 | 0.000238 | 2.58 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.40 | 0.845454 | 0.500000 | 0.701934 | 1.00 | 0.500000 | 0.000451 | 0.000105 | 0.701934 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.43 | 0.104097 | 0.500000 | 1.21 | 0.500000 | 0.500000 | 0.003660 | 0.000099 | 1.21 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.54 | 0.099330 | 0.500000 | 1.27 | 0.500000 | 0.500000 | 0.003836 | 0.000102 | 1.27 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.42 | 0.058618 | 0.500000 | 1.21 | 0.500000 | 0.500000 | 0.011690 | 0.000071 | 1.21 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.806287 | 0.389488 | 0.500000 | 0.403144 | 1.00 | 0.500000 | 0.000978 | 0.000067 | 0.403144 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 5636.53 | 0.000049 | 117.54 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3350.08 | 0.000029 | 81.91 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1466.36 | 0.000013 | 32.96 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2260.59 | 0.000020 | 55.41 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1335.69 | 0.000012 | 33.32 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10927.93 | 0.000096 | 230.91 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 9799.95 | 0.000086 | 223.27 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 27159.03 | 0.000238 | 604.15 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 5394.73 | 0.000047 | 154.17 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 5398.46 | 0.000047 | 154.28 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 30986.17 | 0.000271 | 885.50 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 31074.58 | 0.000272 | 888.02 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 5386.51 | 0.000047 | 153.93 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 5390.25 | 0.000047 | 154.04 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12031.39 | 0.000105 | 290.24 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1639.59 | 0.000014 | 46.85 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1640.02 | 0.000014 | 46.87 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 7877.01 | 0.000069 | 225.09 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 11271.28 | 0.000099 | 247.11 |
DINING_FLR_6 VAV BOX REHEAT COIL | 11669.80 | 0.000102 | 255.52 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8098.04 | 0.000071 | 172.44 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7641.14 | 0.000067 | 188.78 |
VAV WITH REHEAT HEATING COIL | 123843.92 | 0.001083 | 2173.01 |
FLR_3_DOAS HEATING COIL | 10951.44 | 0.000096 | 192.16 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.20 | 0.000047 | 0.000428 |
ROOM_2_FLR_3 FAN COIL | 1.19 | 0.000047 | 0.000424 |
ROOM_3_MULT19_FLR_3 FAN COIL | 6.55 | 0.000271 | 0.002333 |
ROOM_4_MULT19_FLR_3 FAN COIL | 7.09 | 0.000272 | 0.002620 |
ROOM_5_FLR_3 FAN COIL | 1.05 | 0.000047 | 0.000374 |
ROOM_6_FLR_3 FAN COIL | 1.04 | 0.000047 | 0.000371 |
ROOM_1_FLR_6 FAN COIL | 0.320201 | 0.000014 | 0.000114 |
ROOM_2_FLR_6 FAN COIL | 0.317616 | 0.000014 | 0.000113 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.40 | 0.000069 | 0.000504 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.20 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.19 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.55 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 7.09 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.05 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.04 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.320201 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.317616 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.40 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008478 | 12.80 | 0.008478 | 0.000428 | 1.20 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008477 | 12.80 | 0.008477 | 0.000424 | 1.19 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008415 | 12.80 | 0.008415 | 0.002333 | 6.55 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008634 | 12.80 | 0.008500 | 0.002620 | 7.09 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008473 | 12.80 | 0.008473 | 0.000374 | 1.05 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008473 | 12.80 | 0.008473 | 0.000371 | 1.04 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008479 | 12.80 | 0.008479 | 0.000114 | 0.320201 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008479 | 12.80 | 0.008479 | 0.000113 | 0.317616 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.74 | 6.70 | 0.008541 | 12.80 | 0.008500 | 0.000504 | 1.40 | |
VAV WITH REHEAT COOLING COIL | 32.44 | 6.70 | 0.007619 | 10.79 | 0.007619 | 0.019984 | 23.20 | 559492.50 |
FLR_3_DOAS COOLING COIL | 40.80 | 6.70 | 0.005631 | 11.84 | 0.005631 | 0.002355 | 2.05 | 65945.86 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.65 | 11.65 | 23.31 | 11.65 | 23.20 | 23.20 | 0.300000 | 0.502366 | 23.20 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 23.20 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 23.20 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.019984 | 0.000024 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001083 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002355 | 0.000202 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000096 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Size Rated Evaporator Air Flow Rate [m3/s] | Design Size Rated Condenser Water Flow Rate [m3/s] | |
SWHSYSLAUNDRY HPWH DXCOIL | 4.90 | 0.004370 |
SWHSYS1 HPWH DXCOIL | 3.87 | 0.003451 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
SWHSYSLAUNDRY HPWH FAN | 4.90 | 700.51 |
SWHSYS1 HPWH FAN | 3.87 | 553.22 |
Condenser water flow rate [m3/s] | Evaporator air flow rate [m3/s] | |
SWHSYS1 HPWH | 0.003451 | 3.87 |
SWHSYSLAUNDRY HPWH | 0.004370 | 4.90 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.029621 | 6043.44 | |
HEATSYS1 PUMP | 0.002994 | 892.73 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.002994 | 0.359278 |
COOLSYS1 | 0.029621 | 3.55 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 342230.51 | 342230.51 | 0.002994 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.029621 | 4184.08 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.029621 | 829321.15 | 829958.35 | 94.62 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 HPWH TANK | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 5.980 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 11.360 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 8.730 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 19.490 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 8.730 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 19.490 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.166 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 9.546 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 3.681 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.371 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.134 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.664 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 8.331 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 13.711 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 8.138 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.208 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 3.972 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.492 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 3.972 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.492 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 3.972 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.972 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 3.972 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.492 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 8.331 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 76.151 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 8.331 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 76.151 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 10.559 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2942.062 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 3.972 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.972 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 11832.934 | 5.980 | 111.108 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11832.934 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 585.501 | 8.730 | 54.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 585.501 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 678.012 | 8.730 | 54.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 678.012 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 684.177 | 4.166 | 257.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 684.177 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 348.833 | 3.681 | 170.996 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 348.833 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 400.685 | 5.134 | 47.701 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 400.685 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1573.457 | 8.331 | 11.057 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1573.457 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 10645.380 | 8.138 | 25.200 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10645.380 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 154.991 | 3.972 | 103.327 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.991 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 154.973 | 3.972 | 103.315 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.973 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 97.406 | 3.972 | 64.937 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 97.406 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 97.432 | 3.972 | 64.955 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 97.432 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 154.991 | 3.972 | 103.327 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.991 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 154.973 | 3.972 | 103.315 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.973 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1546.669 | 3.972 | 73.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1546.669 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 154.991 | 3.972 | 103.327 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.991 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 154.973 | 3.972 | 103.315 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.973 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 97.432 | 3.972 | 64.955 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 97.432 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 2763.123 | 8.331 | 11.057 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2763.123 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 2763.123 | 8.331 | 11.057 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2763.123 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1090.832 | 10.559 | 49.053 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1090.832 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1636.910 | 3.972 | 73.801 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1636.910 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 1.287 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.608 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.684 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.370 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.442 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6100 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4545 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4264 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5624 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5260 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | 0.16691074E-14 | 0.45207920E-16 | -0.13282787E-09 | -0.59403108E-17 |
29 | 8 | 0.19494068E-07 | 0.16957001E-12 | 0.35230437E-03 | -0.22165426E-09 |
30 | 7 | -0.11479370E-01 | 0.90467759E-08 | -0.21987867E-01 | 0.13052461E-03 |
31 | 6 | 0.38463807 | 0.31869432E-05 | 0.45441076 | -0.45036152E-02 |
32 | 5 | -4.9884079 | 0.12028467E-03 | -4.3052891 | 0.60677235E-01 |
33 | 4 | 32.108494 | 0.99355415E-03 | 20.908458 | -0.41024850 |
34 | 3 | -109.32288 | 0.21841230E-02 | -54.572312 | 1.4876971 |
35 | 2 | 195.24423 | 0.12380226E-02 | 76.910992 | -2.8707534 |
36 | 1 | -170.46733 | 0.13310261E-03 | -54.975783 | 2.7333683 |
37 | 0 | 57.057407 | 0.76355891E-06 | 15.605832 | |
38 | 9 | 0.14115123E-14 | 0.53960859E-16 | -0.11739578E-09 | -0.22900007E-17 |
39 | 8 | 0.17311930E-07 | 0.20639465E-12 | 0.32798840E-03 | -0.19684260E-09 |
40 | 7 | -0.10748946E-01 | 0.11327704E-07 | -0.20934514E-01 | 0.12221941E-03 |
41 | 6 | 0.36478417 | 0.40360747E-05 | 0.43737925 | -0.42695883E-02 |
42 | 5 | -4.7945715 | 0.15382307E-03 | -4.1739388 | 0.58273831E-01 |
43 | 4 | 31.250576 | 0.12816568E-02 | 20.393829 | -0.39885853 |
44 | 3 | -107.49604 | 0.28390629E-02 | -53.554356 | 1.4613070 |
45 | 2 | 193.43186 | 0.16201491E-02 | 75.979619 | -2.8419759 |
46 | 1 | -169.79719 | 0.17527083E-03 | -54.709122 | 2.7216233 |
47 | 0 | 57.057407 | 0.10123612E-05 | 15.653272 | |
48 | 9 | 0.65135446E-15 | 0.56204292E-16 | -0.11372497E-09 | -0.53489081E-17 |
49 | 8 | 0.16791160E-07 | 0.21454591E-12 | 0.32203280E-03 | -0.19092129E-09 |
50 | 7 | -0.10569524E-01 | 0.11862766E-07 | -0.20675571E-01 | 0.12017931E-03 |
51 | 6 | 0.35990649 | 0.42391557E-05 | 0.43318136 | -0.42120931E-02 |
52 | 5 | -4.7469406 | 0.16196889E-03 | -4.1415055 | 0.57683257E-01 |
53 | 4 | 31.039704 | 0.13525358E-02 | 20.266625 | -0.39605902 |
54 | 3 | -107.04684 | 0.30019179E-02 | -53.302690 | 1.4548183 |
55 | 2 | 192.98603 | 0.17160237E-02 | 75.749609 | -2.8348971 |
56 | 1 | -169.63227 | 0.18593554E-03 | -54.643729 | 2.7187328 |
57 | 0 | 57.057407 | 0.10758168E-05 | 15.665287 | |
58 | 9 | 0.10314710E-14 | 0.47183642E-16 | -0.12881513E-09 | -0.40099708E-17 |
59 | 8 | 0.18927665E-07 | 0.17950474E-12 | 0.34608657E-03 | -0.21521408E-09 |
60 | 7 | -0.11292911E-01 | 0.96443222E-08 | -0.21719088E-01 | 0.12840450E-03 |
61 | 6 | 0.37957032 | 0.34070209E-05 | 0.45007157 | -0.44438791E-02 |
62 | 5 | -4.9389364 | 0.12890179E-03 | -4.2718596 | 0.60063826E-01 |
63 | 4 | 31.889569 | 0.10670331E-02 | 20.777560 | -0.40734193 |
64 | 3 | -108.85680 | 0.23501275E-02 | -54.313423 | 1.4809641 |
65 | 2 | 194.78196 | 0.13343675E-02 | 76.673975 | -2.8634131 |
66 | 1 | -170.29645 | 0.14368413E-03 | -54.907648 | 2.7303734 |
67 | 0 | 57.057407 | 0.82565881E-06 | 15.617726 | |
68 | 9 | 0.86975537E-15 | 0.52023775E-16 | -0.12536948E-09 | -0.54620444E-17 |
69 | 8 | 0.18440443E-07 | 0.18784465E-12 | 0.34068694E-03 | -0.20967419E-09 |
70 | 7 | -0.11130813E-01 | 0.10155400E-07 | -0.21485363E-01 | 0.12656138E-03 |
71 | 6 | 0.37516444 | 0.35965268E-05 | 0.44629465 | -0.43919449E-02 |
72 | 5 | -4.8959230 | 0.13636263E-03 | -4.2427425 | 0.59530495E-01 |
73 | 4 | 31.699203 | 0.11309484E-02 | 20.663505 | -0.40481456 |
74 | 3 | -108.45147 | 0.24950915E-02 | -54.087828 | 1.4751087 |
75 | 2 | 194.37988 | 0.14187814E-02 | 76.467519 | -2.8570287 |
76 | 1 | -170.14779 | 0.15298304E-03 | -54.848449 | 2.7277680 |
77 | 0 | 57.057407 | 0.88039223E-06 | 15.628184 | |
78 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
79 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
80 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
81 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
82 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
83 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
84 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
85 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
86 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
87 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
88 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
89 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
90 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
91 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
92 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
93 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.4619_SHGC_0.25 | 37 | 1 | VerySmooth | 2.626 | 2.626 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.4619_SHGC_0.25 | 38 | 1 | VerySmooth | 2.626 | 2.626 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.51406E-002 | 0.16139 | 0.61584 | 0.61584 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11972 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.51406E-002 | 0.16139 | 0.61584 | 0.61584 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11972 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | "DX Coil Total Cooling Rate {W | HPWH Only}" | |
1 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | 1.1400 | 74956.0 | 48.891 | 1.6882 | 76621 | |
2 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | 2.8400 | 61437.9 | 4.627 | 9.4219 | 53264 |
Node Number | Height {m} | Volume {m3} | Maximum Capacity {W} | Off-Cycle UA {W/K} | On-Cycle UA {W/K} | Number Of Inlets | Number Of Outlets | |
1 | 1 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 0 | 1 |
2 | 2 | 0.2683 | 0.4733 | 33820.860 | 1.5573 | 1.5573 | 0 | 0 |
3 | 3 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
4 | 4 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
5 | 5 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 1 |
6 | 6 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 2 | 0 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 7.058E-002 | 1.052E-003 | 5.193E-004 | 0.956 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 2.724E-002 | 3.507E-004 | 9.551E-004 | 0.319 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 6.438E-002 | 3.920E-004 | 1.025E-003 | 0.356 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 3.715E-002 | 3.920E-004 | 8.507E-004 | 0.356 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.791E-002 | 1.127E-003 | 1.002E-003 | 1.023 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 0.156 | 8.261E-004 | 4.549E-004 | 0.751 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.446 | 3.407E-004 | 6.517E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 4.096E-002 | 1.050E-003 | 1.025E-003 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 4.095E-002 | 1.050E-003 | 1.025E-003 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.143E-002 | 4.660E-004 | 1.025E-003 | 0.550 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.143E-002 | 4.660E-004 | 1.025E-003 | 0.550 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 4.096E-002 | 1.050E-003 | 1.025E-003 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 4.095E-002 | 1.050E-003 | 1.025E-003 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 4.953E-002 | 1.272E-004 | 1.025E-003 | 0.150 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 4.096E-002 | 1.050E-003 | 5.186E-004 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 4.095E-002 | 1.050E-003 | 5.186E-004 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 2.096E-002 | 8.543E-004 | 4.660E-004 | 1.009 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 0.100 | 3.015E-004 | 2.330E-004 | 0.356 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 0.100 | 3.015E-004 | 2.330E-004 | 0.356 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 8.953E-002 | 8.667E-004 | 4.697E-004 | 1.024 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 8.763E-002 | 2.126E-004 | 1.761E-004 | 0.251 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 8.7310E-002 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.8709E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.7087E-002 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 4.2189E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 6.5660E-002 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 2.4295E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 2.6511E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.7811E-003 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 9.8430E-002 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.7382E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1097 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 5.1591E-002 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 7.2656E-002 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 3.0684E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 2.9789E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.2036E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.1147E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.2078E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.6306E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.1307E-003 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 1.5594E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 6.2294E-003 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.6108E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.2309E-003 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.1147E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.2078E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.6306E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.1307E-003 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 1.5594E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 6.2294E-003 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.6108E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.2309E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 29385.03001 | 29385.03001 | 2.35179 | 2.35179 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 21:40:00 | 32.15500 | 5.61779E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | 00:10:00 | 0.50000 | 4.31558E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 4608.12023 | 4608.12023 | 0.36882 | 0.36882 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 40.80000 | 5.63111E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2467.08866 | 2467.08866 | 0.11647 | 0.11647 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 0.50000 | 4.31558E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3202.81781 | 3202.81781 | 0.25636 | 0.25636 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 37.27550 | 5.62563E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 852.61573 | 852.61573 | 4.02546E-002 | 9.17347E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 0.50000 | 4.31558E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3076.51658 | 3076.51658 | 0.24619 | 0.24619 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 36.94300 | 5.62512E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1671.28756 | 1671.28756 | 7.89064E-002 | 7.89064E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 0.50000 | 4.31558E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1695.93451 | 1695.93451 | 0.13571 | 0.13571 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 38.05133 | 5.62683E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1010.82151 | 1010.82151 | 4.77239E-002 | 5.77652E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 0.50000 | 4.31558E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 45472.57422 | 45472.57422 | 3.63910 | 3.63910 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 40.00200 | 5.62986E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2218.13291 | 2218.13291 | 0.10472 | 0.10472 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 0.50000 | 4.31558E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 19487.96049 | 19487.96049 | 1.56110 | 1.56110 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 40.80000 | 5.63111E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 6062.09902 | 6062.09902 | 0.28620 | 0.67639 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 0.50000 | 4.31558E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 64328.34052 | 64328.34052 | 5.15037 | 5.15037 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 40.80000 | 5.63111E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 14828.15282 | 14828.15282 | 0.70008 | 1.89399 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 0.50000 | 4.31558E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11127.85728 | 11127.85728 | 1.20000 | 1.20000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 39.11533 | 5.62848E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5394.85623 | 5394.85623 | 0.25619 | 0.25619 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 0.50000 | 4.31558E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11046.95574 | 11046.95574 | 1.19128 | 1.19128 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5398.58833 | 5398.58833 | 0.25637 | 0.25637 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 0.50000 | 4.31558E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 60724.71143 | 60724.71143 | 6.54831 | 6.54831 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 40.80000 | 5.63111E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 30986.53334 | 30986.53334 | 1.47154 | 1.47154 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 0.50000 | 4.31558E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 65736.33021 | 65736.33021 | 7.08930 | 7.08930 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 40.26800 | 5.63027E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 31074.94285 | 31074.94285 | 1.47574 | 1.47574 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 0.50000 | 4.31558E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 9731.70093 | 9731.70093 | 1.04944 | 1.04944 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 36.74350 | 5.62481E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5386.63968 | 5386.63968 | 0.25580 | 0.25580 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 0.50000 | 4.31558E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9664.76972 | 9664.76972 | 1.04222 | 1.04222 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 36.41100 | 5.62429E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5390.37386 | 5390.37386 | 0.25598 | 0.25598 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 0.50000 | 4.31558E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 17541.62489 | 17541.62489 | 1.40387 | 1.40387 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 40.40100 | 5.63048E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 8669.45538 | 8669.45538 | 0.40932 | 0.47476 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2969.29324 | 2969.29324 | 0.32020 | 0.32020 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 39.11533 | 5.62848E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1639.63181 | 1639.63181 | 7.78623E-002 | 7.78623E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 0.50000 | 4.31558E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2945.32337 | 2945.32337 | 0.31762 | 0.31762 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1640.05880 | 1640.05880 | 7.78826E-002 | 7.78826E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 0.50000 | 4.31558E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 12979.35154 | 12979.35154 | 1.39971 | 1.39971 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 40.80000 | 5.63111E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 7877.08900 | 7877.08900 | 0.37407 | 0.37407 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 30297.17293 | 30297.17293 | 2.42777 | 2.42777 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5456.83577 | 5456.83577 | 0.25763 | 1.18780 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 0.50000 | 4.31558E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 31751.73870 | 31751.73870 | 2.54428 | 2.54428 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 5576.22822 | 5576.22822 | 0.26327 | 1.18780 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 0.50000 | 4.31558E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30100.94432 | 30100.94432 | 2.41535 | 2.41535 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 39.60300 | 5.62924E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2324.30134 | 2324.30134 | 0.10972 | 0.36735 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 0.50000 | 4.31558E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10074.88827 | 10074.88827 | 0.80629 | 0.80629 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 40.80000 | 5.63111E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 5709.86637 | 5709.86637 | 0.26958 | 0.26958 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 0.50000 | 4.31558E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 500471.20 | 23.19723 | 23.19723 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 131007.29 | 7.36170 | 7.36170 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 63092.52 | 19.67809 | 2.05125 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 36503.53 | 4.50144 | 2.05125 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.35179 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.64116 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.17590 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.94238E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.93108E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.17590 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5636.53228 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.93108E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 117.54016 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.36882 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13857 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18441 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50000 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.74943E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.93079E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.18441 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3350.07529 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.93079E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 81.90666 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.25636 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23087 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12818 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61564 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.65031E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.28284E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12818 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1466.36278 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.28284E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 32.96455 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.24619 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.50836 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12310 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.49471E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.97766E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12310 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2260.59230 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.97766E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 55.41418 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.13571 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.53205 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.78572E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.16101E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.16852E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.78572E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1335.69440 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.16852E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 33.32443 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.63910 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.48440E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.81955 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.33158E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.56023E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.81955 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10927.93315 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.56023E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 230.91395 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.56110 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.21869E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78055 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.13291E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.57342E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.78055 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9799.94702 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.57342E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 223.26544 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.15037 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19355 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.57519 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51612 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.96852E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.37599E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.57519 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 27159.03141 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.37599E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 604.15387 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.20000 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.20000 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.71954E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.27596E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74179 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47772E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47772E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.27596E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.20000 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5394.72927 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.71954E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 154.16859 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.19128 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.19128 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.72281E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.24487E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74179 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47747E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47747E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.24487E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.19128 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5398.46129 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.72281E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 154.27521 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.54831 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.54831 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.71081E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.33314E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74198 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.41460E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.41460E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.33314E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.54831 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 30986.16828 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.71081E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 885.49848 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.08930 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 7.08930 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.71854E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.62002E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74107 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63362E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.62002E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.08930 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 31074.57679 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.71854E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 888.02437 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.04944 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.04944 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.71236E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.73945E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74180 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47339E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47339E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.73945E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.04944 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5386.51290 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.71236E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 153.93385 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.04222 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.04222 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.71562E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.71373E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74180 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47308E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47308E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.71373E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.04222 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5390.24700 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.71562E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 154.04053 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.40387 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.84545 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.70193 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.50645E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.05256E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.70193 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12031.39344 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.05256E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 290.24174 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.32020 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.32020 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.43439E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.14097E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74178 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47905E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47905E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.14097E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.32020 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1639.59447 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.43439E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 46.85343 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.31762 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.31762 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.43476E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.13176E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74178 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47880E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.47880E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.13176E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.31762 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1640.02146 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.43476E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 46.86563 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.39971 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.39971 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.89115E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.04386E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.74140 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.54051E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.04386E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.39971 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7877.01115 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.89115E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 225.09365 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.42777 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10410 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.21388 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50000 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.66005E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.86061E-005 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.21388 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11271.28134 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.86061E-005 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 247.11456 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.54428 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.93297E-002 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.27214 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50000 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.83571E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.02093E-004 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.27214 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11669.80274 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.02093E-004 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 255.52270 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.41535 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.86184E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.20768 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50000 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.16905E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.08452E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20768 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8098.03680 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.08452E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 172.44332 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80629 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38949 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50000 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40314 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.78208E-004 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.68480E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40314 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7641.13964 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.68480E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 188.77997 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.65350 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.65350 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 23.30700 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.65350 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 23.19723 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 23.19723 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.50237 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 23.19723 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 23.19723 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 32.43996 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.78860 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.61887E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.61887E-003 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 559492.50099 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.99838E-002 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 23.19723 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 123843.92334 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.08344E-003 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2173.01460 |
350 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 23.19723 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.99838E-002 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.38289E-005 |
353 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.08344E-003 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
356 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 40.80000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.83593 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 5.63111E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 5.63111E-003 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 65945.85541 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.35543E-003 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 10951.44367 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.58080E-005 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 192.15837 |
368 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.35543E-003 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.02167E-004 |
371 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.58080E-005 |
372 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 4.90359 |
373 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 4.36989E-003 |
374 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.90359 |
375 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Electric Power Consumption [W] | 700.51236 |
376 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 3.87257 |
377 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 3.45109E-003 |
378 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.87257 |
379 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Electric Power Consumption [W] | 553.22422 |
380 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Condenser water flow rate [m3/s] | 3.45109E-003 |
381 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Evaporator air flow rate [m3/s] | 3.87257 |
382 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.96214E-002 |
383 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 6043.44438 |
384 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.99398E-003 |
385 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.35928 |
386 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.99398E-003 |
387 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 892.72856 |
388 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
389 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 342230.51222 |
390 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 342230.51000 |
391 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.99398E-003 |
392 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.96214E-002 |
393 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.55457 |
394 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.96214E-002 |
395 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 4184.08038 |
396 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.96214E-002 |
397 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 829321.14812 |
398 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 829958.35000 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 94.61525 |
400 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
401 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
402 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
403 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
404 | WaterHeater:Stratified | SWHSYS1 HPWH TANK | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
405 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Condenser water flow rate [m3/s] | 4.36989E-003 |
406 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Evaporator air flow rate [m3/s] | 4.90359 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 5665.88 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3364.99 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1473.46 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2270.64 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1341.54 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10984.24 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 9846.82 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 27291.59 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 5811.80 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 5815.82 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 33381.62 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 33476.85 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 5802.95 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 5806.97 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12085.60 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1766.30 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1766.76 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8485.72 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 11327.79 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 11728.37 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8139.51 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7674.86 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 99741.28 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 8820.06 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 19923.35 | 15527.68 | 4395.67 | 0.78 | 2762.10 | 28.01 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 19778.99 | 15415.14 | 4363.85 | 0.78 | 2742.31 | 27.81 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 109419.02 | 85229.29 | 24189.74 | 0.78 | 15494.90 | 157.16 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 120245.48 | 92664.37 | 27581.11 | 0.77 | 16359.72 | 165.93 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 17431.27 | 13584.93 | 3846.35 | 0.78 | 2420.05 | 24.55 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 17311.92 | 13491.87 | 3820.04 | 0.78 | 2403.72 | 24.38 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5315.52 | 4142.81 | 1172.71 | 0.78 | 736.60 | 7.47 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 5272.74 | 4109.46 | 1163.28 | 0.78 | 730.73 | 7.41 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 23357.91 | 18143.07 | 5214.83 | 0.78 | 3203.76 | 32.49 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 660362.05 | 415215.44 | 245146.61 | 0.63 | 98541.05 | 999.46 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 54169.20 | 34464.63 | 19704.58 | 0.64 | 5364.64 | 54.41 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 4.32 | 14.74 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.287 | 1.079 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.370 | 1.137 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.370 | 1.137 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.370 | 1.137 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.370 | 1.137 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.370 | 1.137 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.370 | 1.137 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.370 | 1.137 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.370 | 1.137 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.370 | 1.137 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.370 | 1.137 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.608 | 1.296 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.608 | 1.296 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.608 | 1.296 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.608 | 1.296 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.442 | 1.186 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.442 | 1.186 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.442 | 1.186 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.442 | 1.186 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.442 | 1.186 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.684 | 1.345 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4619_SHGC_0.25 | N/A | 2.626 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.6385816137E-002 | 2.1092505897E-002 | Pass | Pass | 4.1393240640E-003 | 1.2654183016E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.5698354407E-002 | 6.5813946193E-002 | Pass | Pass | 0.2104291494 | 1.0477230339 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.5564329664E-002 | 2.5044190596E-002 | Pass | Pass | 5.7740496865E-003 | 1.4586561666E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.7993814969E-003 | 6.9053129615E-003 | Pass | Pass | 5.2107236045E-002 | 8.1931154934E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.1425646909E-004 | 2.9684449150E-004 | Pass | Pass | 0.1888917467 | 0.6584415041 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.6505901775E-002 | 0.1933371978 | Pass | Pass | 1.9329361816E-002 | 5.2597062705E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.3204181543E-002 | 6.4679787164E-002 | Pass | Pass | 1.3445612880E-002 | 1.8687098784E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.4652393170E-002 | 3.6902953897E-002 | Pass | Pass | 6.3246247878E-003 | 1.3408879618E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.5770722794E-002 | 0.1974577480 | Pass | Pass | 0.2712098638 | 1.1950965840 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.6573488596E-002 | 0.2280953177 | Pass | Pass | 0.3310390111 | 2.2228382739 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.5481038942E-002 | 4.7747269011E-002 | Pass | Pass | 6.9717769433E-002 | 0.2238999083 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.5811338211E-002 | 3.8614702510E-002 | Pass | Pass | 0.1573466878 | 0.4424018127 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.2451808803E-002 | 0.1906400833 | Pass | Pass | 0.1560908620 | 0.3801852792 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.0923542155E-002 | 0.1199091981 | Pass | Pass | 0.4090825797 | 3.3815343619 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.3381649544E-003 | 9.4028255897E-003 | Pass | Pass | 1.9962598074E-002 | 3.7717984043E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.2682966019E-002 | 0.2279912310 | Pass | Pass | 0.2128634877 | 0.5544882704 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.7858497188E-002 | 0.2556859101 | Pass | Pass | 0.2356822958 | 0.9534273750 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.5182590585E-002 | 0.2808797704 | Pass | Pass | 0.2117299230 | 0.6579511489 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.2554044753E-002 | 8.0848776749E-002 | Pass | Pass | 1.0000935717E-002 | 2.9522484067E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.3523832038E-002 | 6.6066376824E-002 | Pass | Pass | 1.1232881754E-002 | 3.4291090152E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.0629308903E-002 | 9.2616368164E-002 | Pass | Pass | 2.1868903405E-002 | 4.1181935411E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.8333161233E-003 | 1.4491895165E-002 | Pass | Pass | 0.1071777039 | 0.2425496753 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2713.05 | 74.05 | 440.84 | 2306.58 | 7457.42 | 12991.95 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.079 | 1.287 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.137 | 1.370 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.296 | 1.608 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.186 | 1.442 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.345 | 1.684 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4619_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.626 | 0.251 | 0.251 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4619_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.626 | 0.251 | 0.251 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4619_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.626 | 0.251 | 0.251 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4619_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.626 | 0.251 | 0.251 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.4619_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.626 | 0.251 | 0.251 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.4619_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.626 | 0.251 | 0.251 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.4619_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.626 | 0.251 | 0.251 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4619_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.626 | 0.251 | 0.251 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.4619_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.626 | 0.251 | 0.251 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.4619_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.626 | 0.251 | 0.251 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4619_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.626 | 0.251 | 0.251 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.4619_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.626 | 0.251 | 0.251 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.4619_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.626 | 0.251 | 0.251 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.4619_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.626 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.4619_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.626 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.4619_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.626 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.4619_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.626 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4619_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.626 | 0.251 | 0.251 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.4619_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.626 | 0.251 | 0.251 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.4619_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.626 | 0.251 | 0.251 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.4619_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.626 | 0.251 | 0.251 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4619_SHGC_0.25 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.626 | 0.251 | 0.251 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.4619_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.626 | 0.251 | 0.251 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.4619_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.626 | 0.251 | 0.251 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.4619_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.626 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.4619_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.626 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.4619_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.626 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.4619_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.626 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.4619_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.626 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.4619_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.626 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.626 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 432.95 | 2.626 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.626 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.9798 | 1978.83 | 11832.93 | LightsWired | LTG_SCH_BASEMENT | 45.99 | 168.00 | 45.94 | 0.0000 | Y | 102.03 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 8.7295 | 67.07 | 585.50 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 5.64 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 8.7295 | 77.67 | 678.01 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 6.53 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.1656 | 164.24 | 684.18 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 7.53 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 3.6813 | 94.76 | 348.83 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 1.68 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.1344 | 78.04 | 400.68 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.41 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 8.3313 | 188.86 | 1573.46 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.51 | 0.0000 | Y | 11.67 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 8.1375 | 1308.19 | 10645.38 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 55.43 | 0.0000 | Y | 110.76 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 3.9719 | 156.09 | 619.96 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 5.55 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 3.9719 | 156.07 | 619.89 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 5.55 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 3.9719 | 1863.81 | 7402.84 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 66.32 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 3.9719 | 1864.32 | 7404.86 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 66.33 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 3.9719 | 156.09 | 619.96 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 5.55 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 3.9719 | 156.07 | 619.89 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 5.55 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 3.9719 | 1557.62 | 6186.67 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 51.06 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 3.9719 | 39.02 | 154.99 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.39 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 3.9719 | 39.02 | 154.97 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.39 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 3.9719 | 220.77 | 876.89 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 7.86 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 8.3313 | 331.66 | 2763.12 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.56 | 0.0000 | Y | 25.71 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 8.3313 | 331.66 | 2763.12 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.56 | 0.0000 | Y | 25.71 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 10.5594 | 103.30 | 1090.83 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.00 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 3.9719 | 412.12 | 1636.91 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 13.51 |
Interior Lighting Total | 5.2589 | 11345.29 | 59663.90 | 350.88 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 10645.38 | 745.18 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 10645.38 | 745.18 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1573.46 | 613.65 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1573.46 | 613.65 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2763.12 | 552.62 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2763.12 | 552.62 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2763.12 | 552.62 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2763.12 | 552.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 11096.45 | AstronomicalClock | - | 83.79 | 83.79 | 174.52 | |
Exterior Lighting Total | 11096.45 | 174.52 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 342230.51 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 829958.35 | 3.26 | 830104.24 | 3.26 | 4.32 | 14.74 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11971.77 | 19923.35 | 15527.68 | 4395.67 | 0.78 | - | 2762.10 | 28.01 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11884.73 | 19778.99 | 15415.14 | 4363.85 | 0.78 | - | 2742.31 | 27.81 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 65322.88 | 109419.02 | 85229.29 | 24189.74 | 0.78 | - | 15494.90 | 157.16 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 73355.04 | 120245.48 | 92664.37 | 27581.11 | 0.77 | - | 16359.72 | 165.93 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10469.65 | 17431.27 | 13584.93 | 3846.35 | 0.78 | - | 2420.05 | 24.55 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10397.64 | 17311.92 | 13491.87 | 3820.04 | 0.78 | - | 2403.72 | 24.38 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3194.48 | 5315.52 | 4142.81 | 1172.71 | 0.78 | - | 736.60 | 7.47 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3168.70 | 5272.74 | 4109.46 | 1163.28 | 0.78 | - | 730.73 | 7.41 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 14121.72 | 23357.91 | 18143.07 | 5214.83 | 0.78 | - | 3203.76 | 32.49 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 559492.50 | 660362.05 | 415215.44 | 245146.61 | 0.63 | - | 98541.05 | 999.46 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 65945.86 | 54169.20 | 34464.63 | 19704.58 | 0.64 | - | 5364.64 | 54.41 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 5636.53 | 5665.88 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3350.08 | 3364.99 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1466.36 | 1473.46 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2260.59 | 2270.64 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1335.69 | 1341.54 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10927.93 | 10984.24 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9799.95 | 9846.82 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 27159.03 | 27291.59 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5394.73 | 5811.80 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5398.46 | 5815.82 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 30986.17 | 33381.62 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 31074.58 | 33476.85 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5386.51 | 5802.95 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5390.25 | 5806.97 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 12031.39 | 12085.60 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1639.59 | 1766.30 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1640.02 | 1766.76 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 7877.01 | 8485.72 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11271.28 | 11327.79 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11669.80 | 11728.37 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8098.04 | 8139.51 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7641.14 | 7674.86 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 123843.92 | 99741.28 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 10951.44 | 8820.06 | - |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 75921.46 | 3.40 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 54370.95 | 3.40 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.20 | 844.36 | 703.64 | 1.00 | 1.15 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.19 | 838.22 | 703.64 | 1.00 | 1.16 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.55 | 4607.63 | 703.64 | 1.00 | 0.95 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 7.09 | 4988.29 | 703.64 | 1.00 | 0.95 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.05 | 738.42 | 703.64 | 1.00 | 1.19 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.04 | 733.35 | 703.64 | 1.00 | 1.19 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.32 | 225.31 | 703.64 | 1.00 | 1.67 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.32 | 223.49 | 703.64 | 1.00 | 1.67 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.40 | 984.89 | 703.64 | 1.00 | 1.12 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 23.20 | 51976.61 | 2240.64 | 1.00 | 1.11 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 4.90 | 700.51 | 142.86 | 0.00 | 2.78 | General | ||
SWHSYS1 HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 3.87 | 553.22 | 142.86 | 0.00 | 2.84 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.029621 | 6043.44 | 204022.71 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.002994 | 892.73 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.029621 | 4184.08 | 141251.80 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYSLAUNDRY HPWH | WaterHeater:HeatPump:PumpedCondenser | 1.14 | 74956.02 | 0.80 | 48.89 | 1.69 |
SWHSYS1 HPWH | WaterHeater:HeatPump:PumpedCondenser | 2.84 | 61437.95 | 0.80 | 4.63 | 9.42 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 29385.03 | 29385.03 | 14.85 | 2.352 | 2.352 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 21:40:00 | 24.00 | 24.00 | 0.00932 | 32.15 | 0.00562 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4608.12 | 4608.12 | 68.70 | 0.369 | 0.369 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00889 | 40.80 | 0.00563 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3202.82 | 3202.82 | 41.24 | 0.256 | 0.256 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00930 | 37.28 | 0.00563 | 0.092 | 0.00 |
MECH_FLR_1 | 3076.52 | 3076.52 | 18.73 | 0.246 | 0.246 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.00 | 24.00 | 0.00852 | 36.94 | 0.00563 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1695.93 | 1695.93 | 17.90 | 0.136 | 0.136 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 24.00 | 24.00 | 0.00858 | 38.05 | 0.00563 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 45472.57 | 45472.57 | 582.69 | 3.639 | 3.639 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 24.00 | 24.00 | 0.00853 | 40.00 | 0.00563 | 0.000 | 0.00 |
CAFE_FLR_1 | 19487.96 | 19487.96 | 103.19 | 1.561 | 1.561 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.99 | 0.01005 | 40.80 | 0.00563 | 0.676 | 0.00 |
LOBBY_FLR_1 | 64328.34 | 64328.34 | 49.17 | 5.150 | 5.150 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.99 | 0.00990 | 40.80 | 0.00563 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 11127.86 | 11127.86 | 285.17 | 1.200 | 1.200 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00848 | 39.12 | 0.00563 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11046.96 | 11046.96 | 283.13 | 1.191 | 1.191 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00848 | 38.94 | 0.00563 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 60724.71 | 60724.71 | 2476.15 | 6.548 | 6.548 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 21.11 | 21.11 | 0.00841 | 40.80 | 0.00563 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 65736.33 | 65736.33 | 2679.77 | 7.089 | 7.089 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 21.11 | 21.11 | 0.00863 | 40.27 | 0.00563 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9731.70 | 9731.70 | 249.39 | 1.049 | 1.049 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 21.11 | 21.11 | 0.00847 | 36.74 | 0.00562 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9664.77 | 9664.77 | 247.70 | 1.042 | 1.042 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 21.11 | 21.11 | 0.00847 | 36.41 | 0.00562 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 17541.62 | 17541.62 | 45.05 | 1.404 | 1.404 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00946 | 40.40 | 0.00563 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2969.29 | 2969.29 | 76.09 | 0.320 | 0.320 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00848 | 39.12 | 0.00563 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2945.32 | 2945.32 | 75.49 | 0.318 | 0.318 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00848 | 38.94 | 0.00563 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 12979.35 | 12979.35 | 529.11 | 1.400 | 1.400 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 21.11 | 21.11 | 0.00854 | 40.80 | 0.00563 | 0.099 | 0.00 |
BANQUET_FLR_6 | 30297.17 | 30297.17 | 91.35 | 2.428 | 2.428 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.98 | 0.01032 | 40.67 | 0.00563 | 1.188 | 0.00 |
DINING_FLR_6 | 31751.74 | 31751.74 | 95.74 | 2.544 | 2.544 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 23.98 | 0.01024 | 40.67 | 0.00563 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30100.94 | 30100.94 | 291.38 | 2.415 | 2.415 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01007 | 39.60 | 0.00563 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10074.89 | 10074.89 | 24.45 | 0.806 | 0.806 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00892 | 40.80 | 0.00563 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | 00:10:00 | 21.00 | 23.73 | 0.00432 | 0.50 | 0.00432 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 2467.09 | 2467.09 | 36.78 | 0.116 | 0.116 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 21.00 | 21.00 | 0.00749 | 0.50 | 0.00432 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 852.62 | 852.62 | 10.98 | 0.040 | 0.092 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 21.00 | 21.00 | 0.00744 | 0.50 | 0.00432 | 0.092 | 0.00 |
MECH_FLR_1 | 1671.29 | 1671.29 | 10.18 | 0.079 | 0.079 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 21.00 | 21.00 | 0.00734 | 0.50 | 0.00432 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1010.82 | 1010.82 | 10.67 | 0.048 | 0.058 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 21.00 | 21.00 | 0.00737 | 0.50 | 0.00432 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2218.13 | 2218.13 | 28.42 | 0.105 | 0.105 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 21.00 | 21.00 | 0.00733 | 0.50 | 0.00432 | 0.000 | 0.00 |
CAFE_FLR_1 | 6062.10 | 6062.10 | 32.10 | 0.286 | 0.676 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 21.00 | 21.00 | 0.00753 | 0.50 | 0.00432 | 0.676 | 0.00 |
LOBBY_FLR_1 | 14828.15 | 14828.15 | 11.33 | 0.700 | 1.894 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00747 | 0.50 | 0.00432 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5394.86 | 5394.86 | 138.25 | 0.256 | 0.256 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00746 | 0.50 | 0.00432 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5398.59 | 5398.59 | 138.36 | 0.256 | 0.256 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00746 | 0.50 | 0.00432 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 30986.53 | 30986.53 | 1263.53 | 1.472 | 1.472 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00750 | 0.50 | 0.00432 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 31074.94 | 31074.94 | 1266.79 | 1.476 | 1.476 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00750 | 0.50 | 0.00432 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5386.64 | 5386.64 | 138.04 | 0.256 | 0.256 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00746 | 0.50 | 0.00432 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5390.37 | 5390.37 | 138.15 | 0.256 | 0.256 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00746 | 0.50 | 0.00432 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 8669.46 | 8669.46 | 22.26 | 0.409 | 0.475 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00758 | 0.50 | 0.00432 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1639.63 | 1639.63 | 42.02 | 0.078 | 0.078 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00755 | 0.50 | 0.00432 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1640.06 | 1640.06 | 42.03 | 0.078 | 0.078 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00755 | 0.50 | 0.00432 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 7877.09 | 7877.09 | 321.11 | 0.374 | 0.374 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00756 | 0.50 | 0.00432 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5456.84 | 5456.84 | 16.45 | 0.258 | 1.188 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00766 | 0.50 | 0.00432 | 1.188 | 0.00 |
DINING_FLR_6 | 5576.23 | 5576.23 | 16.81 | 0.263 | 1.188 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00766 | 0.50 | 0.00432 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 2324.30 | 2324.30 | 22.50 | 0.110 | 0.367 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00691 | 0.50 | 0.00432 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 5709.87 | 5709.87 | 13.85 | 0.270 | 0.270 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00771 | 0.50 | 0.00432 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 23.20 | 23.20 | 7.36 | 7.36 | 23.1972 | 11.6535 | 23.1972 | 0.5024 | 0.3000 |
FLR_3_DOAS | 19.68 | 2.05 | 4.50 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 5636.532 | 5636.532 | 1.175896 | 0.00004931 | 117.540 | 12/21 00:10:00 | 12/21 00:10:00 | 5636.53 | 5636.53 | 1.175896 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 0.00 | 0.00 | 5668.21 | 5668.21 | ||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3350.075 | 3350.075 | 0.184408 | 0.00002931 | 81.907 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 3350.08 | 3350.08 | 0.184408 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00748860 | 43.9873 | 2467.09 | 0.00 | 3367.47 | 3367.47 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1466.363 | 1466.363 | 0.128178 | 0.00001283 | 32.965 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 1466.36 | 1466.36 | 0.128178 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00743791 | 43.6920 | 852.62 | 0.00 | 1474.29 | 1474.29 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2260.592 | 2260.592 | 0.123095 | 0.00001978 | 55.414 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 2260.59 | 2260.59 | 0.123095 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00734289 | 43.1404 | 1671.29 | 0.00 | 2272.32 | 2272.32 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1335.694 | 1335.694 | 0.067857 | 0.00001169 | 33.324 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 1335.69 | 1335.69 | 0.067857 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00736798 | 43.2861 | 1010.82 | 0.00 | 1342.58 | 1342.58 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10927.933 | 10927.933 | 1.819549 | 0.00009560 | 230.914 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 10927.93 | 10927.93 | 1.819549 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00732744 | 43.0517 | 2218.13 | 0.00 | 10989.07 | 10989.07 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 9799.947 | 9799.947 | 0.780549 | 0.00008573 | 223.265 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 9799.95 | 9799.95 | 0.780549 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00753344 | 44.2472 | 6062.10 | 0.00 | 9852.68 | 9852.68 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 27159.031 | 27159.031 | 2.575187 | 0.00023760 | 604.154 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 27159.03 | 27159.03 | 2.575187 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00746637 | 43.8575 | 14828.15 | 0.00 | 27306.50 | 27306.50 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 11971.769 | -999.000 | 1.200000 | 0.00042760 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 11971.77 | 11971.77 | 1.200000 | 21.74 | 14.59 | 0.00847772 | 12.80 | 11.21 | 0.00847772 | 39.12 | 0.00562848 | 18.06 | 0.0000 | 21.11 | 0.00847772 | 49.3789 | 11127.86 | 0.00 | 13173.75 | 12889.85 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5394.729 | 5394.729 | 0.256189 | 0.00004720 | 154.169 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 5394.73 | 5394.73 | 0.256189 | 21.11 | 13.47 | 0.00746433 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00746433 | 43.5497 | 5394.86 | 0.00 | 5815.61 | 5815.61 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 11884.727 | -999.000 | 1.191276 | 0.00042449 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 11884.73 | 11884.73 | 1.191276 | 21.74 | 14.59 | 0.00847747 | 12.80 | 11.21 | 0.00847747 | 38.94 | 0.00562821 | 18.00 | 0.0000 | 21.11 | 0.00847747 | 49.3775 | 11046.96 | 0.00 | 13078.01 | 12796.62 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5398.461 | 5398.461 | 0.256366 | 0.00004723 | 154.275 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 5398.46 | 5398.46 | 0.256366 | 21.11 | 13.47 | 0.00746468 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00746468 | 43.5517 | 5398.59 | 0.00 | 5819.63 | 5819.63 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 65322.883 | -999.000 | 6.548308 | 0.00233314 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | unknown | 7/21 14:30:00 | 65322.88 | 65322.88 | 6.548308 | 21.74 | 14.54 | 0.00841460 | 12.80 | 11.15 | 0.00841460 | 40.80 | 0.00563111 | 18.58 | 0.0000 | 21.11 | 0.00841460 | 49.0158 | 60724.71 | 0.00 | 71939.89 | 71939.89 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 30986.168 | 30986.168 | 1.471541 | 0.00027108 | 885.498 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 30986.17 | 30986.17 | 1.471541 | 21.11 | 13.50 | 0.00750001 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00750001 | 43.7538 | 30986.53 | 0.00 | 33403.91 | 33403.91 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 73355.035 | -999.000 | 7.089300 | 0.00262002 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | 7/21 15:40:00 | 73355.04 | 71309.08 | 7.089300 | 21.74 | 14.73 | 0.00863362 | 12.80 | 11.23 | 0.00850000 | 40.27 | 0.00563027 | 18.42 | 0.0000 | 21.11 | 0.00863362 | 50.2762 | 65736.33 | 0.00 | 80571.93 | 76138.57 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 31074.577 | 31074.577 | 1.475739 | 0.00027185 | 888.024 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 31074.58 | 31074.58 | 1.475739 | 21.11 | 13.50 | 0.00750112 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00750112 | 43.7602 | 31074.94 | 0.00 | 33499.22 | 33499.22 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 10469.651 | -999.000 | 1.049441 | 0.00037394 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | 7/21 10:30:00 | 10469.65 | 10469.65 | 1.049441 | 21.74 | 14.59 | 0.00847339 | 12.80 | 11.21 | 0.00847339 | 36.74 | 0.00562481 | 17.31 | 0.0000 | 21.11 | 0.00847339 | 49.3540 | 9731.70 | 0.00 | 11521.45 | 11280.05 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5386.513 | 5386.513 | 0.255799 | 0.00004712 | 153.934 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 5386.51 | 5386.51 | 0.255799 | 21.11 | 13.47 | 0.00746363 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00746363 | 43.5457 | 5386.64 | 0.00 | 5806.75 | 5806.75 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10397.638 | -999.000 | 1.042223 | 0.00037137 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | 7/21 10:20:00 | 10397.64 | 10397.64 | 1.042223 | 21.74 | 14.59 | 0.00847308 | 12.80 | 11.21 | 0.00847308 | 36.41 | 0.00562429 | 17.20 | 0.0000 | 21.11 | 0.00847308 | 49.3523 | 9664.77 | 0.00 | 11442.25 | 11202.99 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5390.247 | 5390.247 | 0.255976 | 0.00004716 | 154.041 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 5390.25 | 5390.25 | 0.255976 | 21.11 | 13.47 | 0.00746399 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00746399 | 43.5477 | 5390.37 | 0.00 | 5810.77 | 5810.77 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 12031.393 | 12031.393 | 0.701934 | 0.00010526 | 290.242 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 12031.39 | 12031.39 | 0.701934 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00757960 | 44.5141 | 8669.46 | 0.00 | 12094.18 | 12094.18 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3194.485 | -999.000 | 0.320201 | 0.00011410 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 3194.48 | 3194.48 | 0.320201 | 21.74 | 14.59 | 0.00847905 | 12.80 | 11.21 | 0.00847905 | 39.12 | 0.00562848 | 18.06 | 0.0000 | 21.11 | 0.00847905 | 49.3866 | 2969.29 | 0.00 | 3515.16 | 3438.76 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1639.594 | 1639.594 | 0.077862 | 0.00001434 | 46.853 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 1639.59 | 1639.59 | 0.077862 | 21.11 | 13.54 | 0.00754763 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00754763 | 44.0298 | 1639.63 | 0.00 | 1767.51 | 1767.51 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3168.696 | -999.000 | 0.317616 | 0.00011318 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3168.70 | 3168.70 | 0.317616 | 21.74 | 14.59 | 0.00847880 | 12.80 | 11.21 | 0.00847880 | 38.94 | 0.00562821 | 18.00 | 0.0000 | 21.11 | 0.00847880 | 49.3852 | 2945.32 | 0.00 | 3486.79 | 3411.12 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1640.021 | 1640.021 | 0.077883 | 0.00001435 | 46.866 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 1640.02 | 1640.02 | 0.077883 | 21.11 | 13.54 | 0.00754776 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00754776 | 44.0306 | 1640.06 | 0.00 | 1767.97 | 1767.97 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 14121.716 | -999.000 | 1.399714 | 0.00050439 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | unknown | 7/21 14:30:00 | 14121.72 | 13999.93 | 1.399714 | 21.74 | 14.65 | 0.00854051 | 12.80 | 11.23 | 0.00850000 | 40.80 | 0.00563111 | 18.58 | 0.0000 | 21.11 | 0.00854051 | 49.7407 | 12979.35 | 0.00 | 15528.83 | 14999.69 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 7877.011 | 7877.011 | 0.374074 | 0.00006891 | 225.094 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 7877.01 | 7877.01 | 0.374074 | 21.11 | 13.56 | 0.00756421 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.11 | 0.00756421 | 44.1248 | 7877.09 | 0.00 | 8491.58 | 8491.58 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11271.281 | 11271.281 | 1.213883 | 0.00009861 | 247.115 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 11271.28 | 11271.28 | 1.213883 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00765506 | 44.9525 | 5456.84 | 0.00 | 11333.64 | 11333.64 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11669.803 | 11669.803 | 1.272141 | 0.00010209 | 255.523 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 11669.80 | 11669.80 | 1.272141 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00766177 | 44.9914 | 5576.23 | 0.00 | 11734.39 | 11734.39 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 8098.037 | 8098.037 | 1.207677 | 0.00007085 | 172.443 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 8098.04 | 8098.04 | 1.207677 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00690728 | 40.6153 | 2324.30 | 0.00 | 8143.22 | 8143.22 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7641.140 | 7641.140 | 0.403144 | 0.00006685 | 188.780 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 7641.14 | 7641.14 | 0.403144 | 16.70 | 12.29 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00770669 | 45.2516 | 5709.87 | 0.00 | 7680.67 | 7680.67 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 559492.501 | -999.000 | 23.197232 | 0.01998378 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 559492.50 | 559492.49 | 23.197232 | 32.44 | 17.49 | 0.00761887 | 10.79 | 9.51 | 0.00761887 | 40.80 | 0.00563111 | 18.58 | 50.2709 | 23.99 | 0.00960390 | 46.8737 | 289655.46 | 0.00 | 596888.39 | 585277.27 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 123843.923 | 123843.923 | 6.959169 | 0.00108344 | 2173.015 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 123843.92 | 123843.92 | 6.959169 | 0.50 | 0.50 | 0.00431558 | 16.70 | 12.29 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 167.5697 | 21.53 | 0.00693754 | 39.4884 | 56501.82 | 0.00 | 120693.93 | 120693.93 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 65945.855 | -999.000 | 2.051317 | 0.00235543 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 65945.86 | 65945.86 | 2.051317 | 40.80 | 18.58 | 0.00563111 | 11.84 | 7.85 | 0.00563111 | 40.80 | 0.00563111 | 18.58 | 99.9965 | 21.11 | 0.00852784 | 49.6676 | 181821.95 | 0.00 | 66000.58 | 66000.58 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 10951.444 | 10951.444 | 0.615395 | 0.00009581 | 192.158 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10951.44 | 10951.44 | 0.615395 | 0.50 | 0.50 | 0.00431558 | 16.70 | 12.29 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 333.3216 | 21.11 | 0.00750089 | 43.7589 | 94788.32 | 0.00 | 10672.89 | 10672.89 |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 63116.212 | 46453.532 | 4.903586 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 75921.46 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 49873.925 | 36707.209 | 3.872570 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 54370.95 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 5636.532 | 5636.532 | 1.175896 | 0.00004931 | 117.540 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 1.6145 | 1.646999 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 5636.53 | 5636.53 | 1.0000 | 1.28548254 | 1.175896 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.04930581 | 60.00 | 32.22 | 27.78 | 0.000 | 5636.53 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 0.00 | 0.00 | 5668.21 | 5668.21 | 1.28548254 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3350.075 | 3350.075 | 0.184408 | 0.00002931 | 81.907 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 0.9596 | 0.978894 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 3350.08 | 3350.08 | 1.0000 | 0.20159402 | 0.184408 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.02930493 | 60.00 | 32.22 | 27.78 | 0.000 | 3350.08 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00748860 | 21.00 | 0.00748860 | 43.9873 | 2467.09 | 0.00 | 3367.47 | 3367.47 | 0.20159402 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.98 | 19.02 | 0.00800000 | 53639.0 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1466.363 | 1466.363 | 0.128178 | 0.00001283 | 32.965 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 0.4200 | 0.428472 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 1466.36 | 1466.36 | 1.0000 | 0.14012359 | 0.128178 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.01282707 | 60.00 | 32.22 | 27.78 | 0.000 | 1466.36 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00743791 | 21.00 | 0.00743791 | 43.6920 | 852.62 | 0.00 | 1474.29 | 1474.29 | 0.14012359 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.92 | 16.99 | 0.00800000 | 47456.1 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2260.592 | 2260.592 | 0.123095 | 0.00001978 | 55.414 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 0.6475 | 0.660547 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 2260.59 | 2260.59 | 1.0000 | 0.13456726 | 0.123095 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.01977463 | 60.00 | 32.22 | 27.78 | 0.000 | 2260.59 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00734289 | 21.00 | 0.00734289 | 43.1404 | 1671.29 | 0.00 | 2272.32 | 2272.32 | 0.13456726 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 33.16 | 19.07 | 0.00800000 | 53820.9 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1335.694 | 1335.694 | 0.067857 | 0.00001169 | 33.324 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 0.3826 | 0.390291 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 1335.69 | 1335.69 | 1.0000 | 0.07418106 | 0.067857 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.01168405 | 60.00 | 32.22 | 27.78 | 0.000 | 1335.69 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00736798 | 21.00 | 0.00736798 | 43.2861 | 1010.82 | 0.00 | 1342.58 | 1342.58 | 0.07418106 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.35 | 19.45 | 0.00800000 | 55033.5 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10927.933 | 10927.933 | 1.819549 | 0.00009560 | 230.914 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 3.1302 | 3.193150 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 10927.93 | 10927.93 | 1.0000 | 1.98912075 | 1.819549 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.09559257 | 60.00 | 32.22 | 27.78 | 0.000 | 10927.93 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00732744 | 21.00 | 0.00732744 | 43.0517 | 2218.13 | 0.00 | 10989.07 | 10989.07 | 1.98912075 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.02 | 15.23 | 0.00800000 | 42459.3 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9799.947 | 9799.947 | 0.780549 | 0.00008573 | 223.265 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 2.8071 | 2.863552 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 9799.95 | 9799.95 | 1.0000 | 0.85329162 | 0.780549 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.08572547 | 60.00 | 32.22 | 27.78 | 0.000 | 9799.95 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00753344 | 21.00 | 0.00753344 | 44.2472 | 6062.10 | 0.00 | 9852.68 | 9852.68 | 0.85329162 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.92 | 17.33 | 0.00800000 | 48481.4 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 27159.031 | 27159.031 | 2.575187 | 0.00023760 | 604.154 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 7.7793 | 7.935888 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 27159.03 | 27159.03 | 1.0000 | 2.81517932 | 2.575187 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.23757482 | 60.00 | 32.22 | 27.78 | 0.000 | 27159.03 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00746637 | 21.00 | 0.00746637 | 43.8575 | 14828.15 | 0.00 | 27306.50 | 27306.50 | 2.81517932 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.11 | 16.71 | 0.00800000 | 46634.5 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11971.769 | -999.000 | 1.200000 | 0.00042760 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5996 | 1004.8586 | 1.0932 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.200000 | 1.31183310 | 4197.9300 | 999.8980 | 29.61840817 | 13.37 | 6.70 | 6.67 | 829321.15 | 1.4436 | 1.443535 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 11971.77 | 11971.77 | 1.0000 | 1.31183310 | 1.200000 | 21.74 | 14.59 | 0.00847772 | 43391.9 | 12.80 | 11.21 | 0.00847772 | 34265.9 | 0.42755223 | 6.70 | 13.37 | 6.67 | 0.000 | 11971.77 | 39.12 | 0.00562848 | 18.06 | 0.00000000 | 0.0000 | 21.11 | 0.00847772 | 21.11 | 0.00847772 | 49.3789 | 11127.86 | 0.00 | 13173.75 | 12889.85 | 1.31183310 | 21.74 | 15.56 | 0.00847772 | 43391.9 | 12.11 | 11.71 | 0.00839195 | 33349.7 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5394.729 | 5394.729 | 0.256189 | 0.00004720 | 154.169 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.200000 | 1.31183310 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 1.5452 | 1.576344 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 5394.73 | 5394.73 | 1.0000 | 0.28006435 | 0.256189 | 21.11 | 13.47 | 0.00746433 | 40172.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.04719063 | 60.00 | 32.22 | 27.78 | 0.000 | 5394.73 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00746433 | 21.11 | 0.00746433 | 43.5497 | 5394.86 | 0.00 | 5815.61 | 5815.61 | 0.28006435 | 16.60 | 12.63 | 0.00746433 | 35578.5 | 36.98 | 19.87 | 0.00746433 | 56343.8 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11884.727 | -999.000 | 1.191276 | 0.00042449 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5992 | 1004.8586 | 1.0932 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.191276 | 1.30229581 | 4197.9300 | 999.8980 | 29.61840817 | 13.37 | 6.70 | 6.67 | 829321.15 | 1.4331 | 1.433040 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 11884.73 | 11884.73 | 1.0000 | 1.30229581 | 1.191276 | 21.74 | 14.59 | 0.00847747 | 43391.3 | 12.80 | 11.21 | 0.00847747 | 34265.3 | 0.42444367 | 6.70 | 13.37 | 6.67 | 0.000 | 11884.73 | 38.94 | 0.00562821 | 18.00 | 0.00000000 | 0.0000 | 21.11 | 0.00847747 | 21.11 | 0.00847747 | 49.3775 | 11046.96 | 0.00 | 13078.01 | 12796.62 | 1.30229581 | 21.74 | 15.56 | 0.00847747 | 43391.3 | 12.11 | 11.71 | 0.00839184 | 33349.0 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5398.461 | 5398.461 | 0.256366 | 0.00004723 | 154.275 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.191276 | 1.30229581 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 1.5463 | 1.577434 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 5398.46 | 5398.46 | 1.0000 | 0.28025809 | 0.256366 | 21.11 | 13.47 | 0.00746468 | 40173.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.04722328 | 60.00 | 32.22 | 27.78 | 0.000 | 5398.46 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00746468 | 21.11 | 0.00746468 | 43.5517 | 5398.59 | 0.00 | 5819.63 | 5819.63 | 0.28025809 | 16.60 | 12.63 | 0.00746468 | 35579.4 | 36.98 | 19.87 | 0.00746468 | 56344.7 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 65322.883 | -999.000 | 6.548308 | 0.00233314 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4823 | 1004.8586 | 1.0932 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.548308 | 7.15857200 | 4197.9300 | 999.8980 | 29.61840817 | 13.37 | 6.70 | 6.67 | 829321.15 | 7.8767 | 7.876522 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | unknown | unknown | unknown | 7/21 14:30:00 | Sensible | 65322.88 | 65322.88 | 1.0000 | 7.15857200 | 6.548308 | 21.74 | 14.54 | 0.00841460 | 43231.7 | 12.80 | 11.15 | 0.00841460 | 34106.6 | 2.33290046 | 6.70 | 13.37 | 6.67 | 0.000 | 65322.88 | 40.80 | 0.00563111 | 18.58 | 0.00000000 | 0.0000 | 21.11 | 0.00841460 | 21.11 | 0.00841460 | 49.0158 | 60724.71 | 0.00 | 71939.89 | 71939.89 | 7.15857200 | 21.74 | 15.50 | 0.00841460 | 43231.7 | 11.89 | 11.64 | 0.00841460 | 33182.2 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30986.168 | 30986.168 | 1.471541 | 0.00027108 | 885.498 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.548308 | 7.15857200 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 8.8756 | 9.054180 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 30986.17 | 30986.17 | 1.0000 | 1.60867973 | 1.471541 | 21.11 | 13.50 | 0.00750001 | 40264.0 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.27105286 | 60.00 | 32.22 | 27.78 | 0.000 | 30986.17 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00750001 | 21.11 | 0.00750001 | 43.7538 | 30986.53 | 0.00 | 33403.91 | 33403.91 | 1.60867973 | 16.60 | 12.66 | 0.00750001 | 35668.8 | 36.98 | 19.90 | 0.00750001 | 56433.6 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 73355.035 | -999.000 | 7.089300 | 0.00262002 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8895 | 1004.8586 | 1.0932 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.089300 | 7.74998171 | 4197.9300 | 999.8980 | 29.61840817 | 13.37 | 6.70 | 6.67 | 829321.15 | 8.8452 | 8.845025 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | unknown | unknown | unknown | 7/21 15:40:00 | Sensible | 73355.04 | 71309.08 | 1.0000 | 7.74998171 | 7.089300 | 21.74 | 14.73 | 0.00863362 | 43787.4 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 2.61975569 | 6.70 | 13.37 | 6.67 | 0.000 | 73355.04 | 40.27 | 0.00563027 | 18.42 | 0.00000000 | 0.0000 | 21.11 | 0.00863362 | 21.11 | 0.00863362 | 50.2762 | 65736.33 | 0.00 | 80571.93 | 76138.57 | 7.74998171 | 21.74 | 15.69 | 0.00863362 | 43787.4 | 12.12 | 11.72 | 0.00840692 | 33391.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 31074.577 | 31074.577 | 1.475739 | 0.00027185 | 888.024 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.089300 | 7.74998171 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 8.9009 | 9.080014 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 31074.58 | 31074.58 | 1.0000 | 1.61326955 | 1.475739 | 21.11 | 13.50 | 0.00750112 | 40266.9 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.27182622 | 60.00 | 32.22 | 27.78 | 0.000 | 31074.58 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00750112 | 21.11 | 0.00750112 | 43.7602 | 31074.94 | 0.00 | 33499.22 | 33499.22 | 1.61326955 | 16.60 | 12.66 | 0.00750112 | 35671.7 | 36.98 | 19.90 | 0.00750112 | 56436.5 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10469.651 | -999.000 | 1.049441 | 0.00037394 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5916 | 1004.8586 | 1.0932 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.049441 | 1.14724241 | 4197.9300 | 999.8980 | 29.61840817 | 13.37 | 6.70 | 6.67 | 829321.15 | 1.2624 | 1.262413 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | unknown | unknown | 7/21 10:30:00 | Sensible | 10469.65 | 10469.65 | 1.0000 | 1.14724241 | 1.049441 | 21.74 | 14.59 | 0.00847339 | 43380.9 | 12.80 | 11.21 | 0.00847339 | 34255.0 | 0.37390653 | 6.70 | 13.37 | 6.67 | 0.000 | 10469.65 | 36.74 | 0.00562481 | 17.31 | 0.00000000 | 0.0000 | 21.11 | 0.00847339 | 21.11 | 0.00847339 | 49.3540 | 9731.70 | 0.00 | 11521.45 | 11280.05 | 1.14724241 | 21.74 | 15.55 | 0.00847339 | 43380.9 | 12.11 | 11.70 | 0.00839000 | 33338.2 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5386.513 | 5386.513 | 0.255799 | 0.00004712 | 153.934 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.049441 | 1.14724241 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 1.5429 | 1.573943 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 5386.51 | 5386.51 | 1.0000 | 0.27963780 | 0.255799 | 21.11 | 13.47 | 0.00746363 | 40171.1 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.04711876 | 60.00 | 32.22 | 27.78 | 0.000 | 5386.51 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00746363 | 21.11 | 0.00746363 | 43.5457 | 5386.64 | 0.00 | 5806.75 | 5806.75 | 0.27963780 | 16.60 | 12.63 | 0.00746363 | 35576.8 | 36.98 | 19.87 | 0.00746363 | 56342.0 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10397.638 | -999.000 | 1.042223 | 0.00037137 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5910 | 1004.8586 | 1.0932 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.042223 | 1.13935197 | 4197.9300 | 999.8980 | 29.61840817 | 13.37 | 6.70 | 6.67 | 829321.15 | 1.2538 | 1.253730 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | unknown | unknown | 7/21 10:20:00 | Sensible | 10397.64 | 10397.64 | 1.0000 | 1.13935197 | 1.042223 | 21.74 | 14.59 | 0.00847308 | 43380.2 | 12.80 | 11.21 | 0.00847308 | 34254.2 | 0.37133474 | 6.70 | 13.37 | 6.67 | 0.000 | 10397.64 | 36.41 | 0.00562429 | 17.20 | 0.00000000 | 0.0000 | 21.11 | 0.00847308 | 21.11 | 0.00847308 | 49.3523 | 9664.77 | 0.00 | 11442.25 | 11202.99 | 1.13935197 | 21.74 | 15.55 | 0.00847308 | 43380.2 | 12.11 | 11.70 | 0.00838987 | 33337.4 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5390.247 | 5390.247 | 0.255976 | 0.00004716 | 154.041 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.042223 | 1.13935197 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 1.5440 | 1.575034 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 5390.25 | 5390.25 | 1.0000 | 0.27983165 | 0.255976 | 21.11 | 13.47 | 0.00746399 | 40171.9 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.04715142 | 60.00 | 32.22 | 27.78 | 0.000 | 5390.25 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00746399 | 21.11 | 0.00746399 | 43.5477 | 5390.37 | 0.00 | 5810.77 | 5810.77 | 0.27983165 | 16.60 | 12.63 | 0.00746399 | 35577.7 | 36.98 | 19.87 | 0.00746399 | 56342.9 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12031.393 | 12031.393 | 0.701934 | 0.00010526 | 290.242 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 3.4462 | 3.515582 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 12031.39 | 12031.39 | 1.0000 | 0.76734987 | 0.701934 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.10524514 | 60.00 | 32.22 | 27.78 | 0.000 | 12031.39 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00757960 | 21.00 | 0.00757960 | 44.5141 | 8669.46 | 0.00 | 12094.18 | 12094.18 | 0.76734987 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.06 | 18.72 | 0.00800000 | 52695.7 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3194.485 | -999.000 | 0.320201 | 0.00011410 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6021 | 1004.8586 | 1.0932 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.320201 | 0.35004203 | 4197.9300 | 999.8980 | 29.61840817 | 13.37 | 6.70 | 6.67 | 829321.15 | 0.3852 | 0.385186 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 3194.48 | 3194.48 | 1.0000 | 0.35004203 | 0.320201 | 21.74 | 14.59 | 0.00847905 | 43395.3 | 12.80 | 11.21 | 0.00847905 | 34269.3 | 0.11408583 | 6.70 | 13.37 | 6.67 | 0.000 | 3194.48 | 39.12 | 0.00562848 | 18.06 | 0.00000000 | 0.0000 | 21.11 | 0.00847905 | 21.11 | 0.00847905 | 49.3866 | 2969.29 | 0.00 | 3515.16 | 3438.76 | 0.35004203 | 21.74 | 15.56 | 0.00847905 | 43395.3 | 12.12 | 11.71 | 0.00839256 | 33353.2 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1639.594 | 1639.594 | 0.077862 | 0.00001434 | 46.853 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.320201 | 0.35004203 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 0.4696 | 0.479091 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 1639.59 | 1639.59 | 1.0000 | 0.08511863 | 0.077862 | 21.11 | 13.54 | 0.00754763 | 40384.4 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.01434242 | 60.00 | 32.22 | 27.78 | 0.000 | 1639.59 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00754763 | 21.11 | 0.00754763 | 44.0298 | 1639.63 | 0.00 | 1767.51 | 1767.51 | 0.08511863 | 16.60 | 12.71 | 0.00754763 | 35789.4 | 36.98 | 19.93 | 0.00754763 | 56554.7 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3168.696 | -999.000 | 0.317616 | 0.00011318 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6017 | 1004.8586 | 1.0932 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.317616 | 0.34721628 | 4197.9300 | 999.8980 | 29.61840817 | 13.37 | 6.70 | 6.67 | 829321.15 | 0.3821 | 0.382076 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 3168.70 | 3168.70 | 1.0000 | 0.34721628 | 0.317616 | 21.74 | 14.59 | 0.00847880 | 43394.7 | 12.80 | 11.21 | 0.00847880 | 34268.7 | 0.11316482 | 6.70 | 13.37 | 6.67 | 0.000 | 3168.70 | 38.94 | 0.00562821 | 18.00 | 0.00000000 | 0.0000 | 21.11 | 0.00847880 | 21.11 | 0.00847880 | 49.3852 | 2945.32 | 0.00 | 3486.79 | 3411.12 | 0.34721628 | 21.74 | 15.56 | 0.00847880 | 43394.7 | 12.12 | 11.71 | 0.00839244 | 33352.6 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1640.021 | 1640.021 | 0.077883 | 0.00001435 | 46.866 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.317616 | 0.34721628 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 0.4698 | 0.479215 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 1640.02 | 1640.02 | 1.0000 | 0.08514079 | 0.077883 | 21.11 | 13.54 | 0.00754776 | 40384.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.01434616 | 60.00 | 32.22 | 27.78 | 0.000 | 1640.02 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00754776 | 21.11 | 0.00754776 | 44.0306 | 1640.06 | 0.00 | 1767.97 | 1767.97 | 0.08514079 | 16.60 | 12.71 | 0.00754776 | 35789.8 | 36.98 | 19.93 | 0.00754776 | 56555.0 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14121.716 | -999.000 | 1.399714 | 0.00050439 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7164 | 1004.8586 | 1.0932 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.399714 | 1.53015928 | 4197.9300 | 999.8980 | 29.61840817 | 13.37 | 6.70 | 6.67 | 829321.15 | 1.7028 | 1.702772 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | unknown | unknown | unknown | 7/21 14:30:00 | Sensible | 14121.72 | 13999.93 | 1.0000 | 1.53015928 | 1.399714 | 21.74 | 14.65 | 0.00854051 | 43551.1 | 12.80 | 11.23 | 0.00850000 | 34322.2 | 0.50433409 | 6.70 | 13.37 | 6.67 | 0.000 | 14121.72 | 40.80 | 0.00563111 | 18.58 | 0.00000000 | 0.0000 | 21.11 | 0.00854051 | 21.11 | 0.00854051 | 49.7407 | 12979.35 | 0.00 | 15528.83 | 14999.69 | 1.53015928 | 21.74 | 15.61 | 0.00854051 | 43551.1 | 12.14 | 11.73 | 0.00840348 | 33402.6 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7877.011 | 7877.011 | 0.374074 | 0.00006891 | 225.094 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.399714 | 1.53015928 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 2.2563 | 2.301668 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 7877.01 | 7877.01 | 1.0000 | 0.40893557 | 0.374074 | 21.11 | 13.56 | 0.00756421 | 40426.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.06890450 | 60.00 | 32.22 | 27.78 | 0.000 | 7877.01 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.11 | 0.00756421 | 21.11 | 0.00756421 | 44.1248 | 7877.09 | 0.00 | 8491.58 | 8491.58 | 0.40893557 | 16.60 | 12.73 | 0.00756421 | 35831.4 | 36.98 | 19.94 | 0.00756421 | 56596.5 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11271.281 | 11271.281 | 1.213883 | 0.00009861 | 247.115 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 3.2285 | 3.293476 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 11271.28 | 11271.28 | 1.0000 | 1.32701009 | 1.213883 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.09859603 | 60.00 | 32.22 | 27.78 | 0.000 | 11271.28 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00765506 | 21.00 | 0.00765506 | 44.9525 | 5456.84 | 0.00 | 11333.64 | 11333.64 | 1.32701009 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.98 | 16.30 | 0.00800000 | 45475.5 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11669.803 | 11669.803 | 1.272141 | 0.00010209 | 255.523 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 3.3427 | 3.409925 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 11669.80 | 11669.80 | 1.0000 | 1.39069765 | 1.272141 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.10208211 | 60.00 | 32.22 | 27.78 | 0.000 | 11669.80 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00766177 | 21.00 | 0.00766177 | 44.9914 | 5576.23 | 0.00 | 11734.39 | 11734.39 | 1.39069765 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.87 | 16.27 | 0.00800000 | 45372.5 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8098.037 | 8098.037 | 1.207677 | 0.00007085 | 172.443 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 2.3196 | 2.366252 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 8098.04 | 8098.04 | 1.0000 | 1.32022532 | 1.207677 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.07083793 | 60.00 | 32.22 | 27.78 | 0.000 | 8098.04 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.56 | 0.00690728 | 21.00 | 0.00690728 | 40.6153 | 2324.30 | 0.00 | 8143.22 | 8143.22 | 1.32022532 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.65 | 15.46 | 0.00800000 | 43102.8 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7641.140 | 7641.140 | 0.403144 | 0.00006685 | 188.780 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 2.1887 | 2.232746 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 7641.14 | 7641.14 | 1.0000 | 0.44071426 | 0.403144 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.06684120 | 60.00 | 32.22 | 27.78 | 0.000 | 7641.14 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00770669 | 21.00 | 0.00770669 | 45.2516 | 5709.87 | 0.00 | 7680.67 | 7680.67 | 0.44071426 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 33.69 | 19.24 | 0.00800000 | 54362.5 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 559492.501 | -999.000 | 23.197232 | 0.01998378 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.0031 | 1004.8586 | 1.0932 | VAV WITH REHEAT FAN | Fan:VariableVolume | 23.197232 | 25.35907940 | 4197.9300 | 999.8980 | 29.61840817 | 13.37 | 6.70 | 6.67 | 829321.15 | 67.4639 | 67.463913 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 559492.50 | 559492.49 | 1.0000 | 25.35907940 | 23.197232 | 32.44 | 17.49 | 0.00761887 | 52110.7 | 10.79 | 9.51 | 0.00761887 | 30047.9 | 19.98173723 | 6.70 | 13.37 | 6.67 | 51976.613 | 507515.89 | 40.80 | 0.00563111 | 18.58 | 11.66146000 | 50.2709 | 23.99 | 0.00962828 | 23.99 | 0.00960390 | 46.8737 | 289655.46 | 0.00 | 596888.39 | 585277.27 | 25.35907940 | 32.44 | 18.54 | 0.00761887 | 52110.7 | 9.79 | 9.70 | 0.00743711 | 28573.3 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 123843.923 | 123843.923 | 6.959169 | 0.00108344 | 2173.015 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | VAV WITH REHEAT FAN | Fan:VariableVolume | 23.197232 | 25.35907940 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 35.4734 | 36.187283 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 123843.92 | 123843.92 | 1.0000 | 7.60772382 | 6.959169 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 1.08333014 | 60.00 | 32.22 | 27.78 | 0.000 | 123843.92 | 0.50 | 0.00431558 | 0.50 | 11.66146000 | 167.5697 | 18.54 | 0.00715333 | 21.53 | 0.00693754 | 39.4884 | 56501.82 | 0.00 | 120693.93 | 120693.93 | 7.60772382 | 2.80 | 2.38 | 0.00431558 | 13629.0 | 18.46 | 10.16 | 0.00431558 | 29493.7 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 65945.855 | -999.000 | 2.051317 | 0.00235543 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1015.3079 | 1004.8586 | 1.0932 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.24240930 | 4197.9300 | 999.8980 | 29.61840817 | 13.37 | 6.70 | 6.67 | 829321.15 | 7.9518 | 7.951788 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 65945.86 | 65945.86 | 1.0000 | 2.24248814 | 2.051317 | 40.80 | 18.58 | 0.00563111 | 55507.6 | 11.84 | 7.85 | 0.00563111 | 26100.2 | 2.35519288 | 6.70 | 13.37 | 6.67 | 2195.006 | 63750.85 | 40.80 | 0.00563111 | 18.58 | 2.05124512 | 99.9965 | 21.11 | 0.00851674 | 21.11 | 0.00852784 | 49.6676 | 181821.95 | 0.00 | 66000.58 | 66000.58 | 2.24248814 | 40.80 | 19.66 | 0.00563111 | 55507.6 | 11.81 | 8.61 | 0.00563111 | 26075.8 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 10951.444 | 10951.444 | 0.615395 | 0.00009581 | 192.158 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.24240930 | 4197.9300 | 999.8980 | 2.99367640 | 54.44 | 82.22 | 27.78 | 349118.04 | 3.1369 | 3.200020 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10951.44 | 10951.44 | 1.0000 | 0.67274644 | 0.615395 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 16.70 | 12.29 | 0.00800000 | 37036.7 | 0.09579823 | 60.00 | 32.22 | 27.78 | 0.000 | 10951.44 | 0.50 | 0.00431558 | 0.50 | 2.05124512 | 333.3216 | 21.11 | 0.00749921 | 21.11 | 0.00750089 | 43.7589 | 94788.32 | 0.00 | 10672.89 | 10672.89 | 0.67274644 | 2.80 | 2.38 | 0.00431558 | 13629.0 | 18.46 | 10.16 | 0.00431558 | 29493.7 | |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 63116.212 | 46453.532 | 4.903586 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 1.0932 | SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 4.903586 | 5.36057240 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 75921.46 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 75921.46 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 49873.925 | 36707.209 | 3.872570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 1.0932 | SWHSYS1 HPWH FAN | Fan:SystemModel | 3.872570 | 4.23347064 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 54370.95 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54370.95 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 23.20 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1696.33 | 6633.67 | 642.00 |
RETAIL_1_FLR_1 | 2966.67 | 4849.67 | 580.17 |
RETAIL_2_FLR_1 | 2160.33 | 5580.50 | 684.17 |
MECH_FLR_1 | 1808.00 | 6183.00 | 260.00 |
STORAGE_FLR_1 | 1738.17 | 6434.50 | 370.33 |
LAUNDRY_FLR_1 | 7744.17 | 3413.50 | 3020.33 |
CAFE_FLR_1 | 4488.67 | 3291.83 | 1112.17 |
LOBBY_FLR_1 | 2871.67 | 4273.83 | 997.67 |
ROOM_1_FLR_3 | 359.17 | 8088.33 | 277.33 |
ROOM_2_FLR_3 | 747.17 | 8121.17 | 675.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 334.50 | 8755.83 | 334.50 |
ROOM_5_FLR_3 | 325.50 | 7966.00 | 266.00 |
ROOM_6_FLR_3 | 818.67 | 7817.83 | 640.67 |
CORRIDOR_FLR_3 | 1704.17 | 7145.83 | 898.17 |
ROOM_1_FLR_6 | 787.00 | 7905.67 | 581.00 |
ROOM_2_FLR_6 | 1315.83 | 7976.83 | 1153.17 |
ROOM_3_MULT9_FLR_6 | 236.00 | 7864.50 | 140.17 |
BANQUET_FLR_6 | 4597.83 | 2446.00 | 1096.17 |
DINING_FLR_6 | 5319.33 | 1585.67 | 1028.83 |
KITCHEN_FLR_6 | 8404.00 | 6716.50 | 6664.50 |
CORRIDOR_FLR_6 | 2027.67 | 6049.50 | 552.50 |
Facility | 8714.17 | 8760.00 | 7330.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 16.67 | 0.00 | 16.67 |
ROOM_2_FLR_3 | 0.00 | 15.33 | 0.00 | 15.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 12.00 | 0.00 | 12.00 |
ROOM_5_FLR_3 | 0.00 | 12.83 | 0.00 | 12.83 |
ROOM_6_FLR_3 | 0.00 | 33.67 | 0.00 | 33.67 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 23.33 | 0.00 | 23.33 |
ROOM_2_FLR_6 | 0.00 | 24.83 | 0.00 | 24.83 |
ROOM_3_MULT9_FLR_6 | 0.00 | 26.00 | 0.00 | 26.00 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 76.00 | 0.00 | 76.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 0.853 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.406 | 0.240 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.427 | 0.080 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.629 | 0.089 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.591 | 0.089 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 21.992 | 0.257 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 3.730 | 0.189 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 1.756 | 0.078 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.310 | 0.000 | 0.052 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.311 | 0.000 | 0.051 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.403 | 0.138 | 0.000 | 0.080 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.310 | 0.000 | 0.052 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.311 | 0.000 | 0.051 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.482 | 0.038 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.355 | 0.310 | 0.000 | 0.061 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.311 | 0.000 | 0.058 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.403 | 0.253 | 0.000 | 0.097 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.801 | 0.090 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 5.150 | 0.090 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 20.633 | 0.259 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.078 | 0.063 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 0.501 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.416 | 0.004 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 0.965 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.484 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.426 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 11.397 | 0.004 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 2.640 | 0.003 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 1.178 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.005 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.005 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.005 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.005 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.298 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.005 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.005 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.004 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 3.436 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 3.628 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 8.915 | 0.004 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.678 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.79 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.56 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.09 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.25 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 35342185.32 | 0.00 | 35342185.32 | 0.00 | 35342185.32 | 26946214.98 | 855.52 | 98.04 | 7806.44 | 0.00 |
RETAIL_1_FLR_1 | 5500456.04 | 0.00 | 5500456.04 | 549390.10 | 6049846.14 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3770049.42 | 0.00 | 3770049.42 | 212065.27 | 3982114.69 | 2892943.94 | 111.22 | 44.35 | 8604.43 | 0.00 |
MECH_FLR_1 | 3523660.34 | 0.00 | 3523660.34 | 501196.32 | 4024856.66 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1910609.59 | 0.00 | 1910609.59 | 289162.67 | 2199772.26 | 1821682.01 | 3621.44 | 220.44 | 4918.12 | 0.00 |
LAUNDRY_FLR_1 | 58462542.29 | 0.00 | 58462542.29 | 684357.98 | 59146900.27 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 23916111.64 | 0.00 | 23916111.64 | 1214457.92 | 25130569.56 | 21330615.53 | 2765.26 | 229.66 | 5765.08 | 0.00 |
LOBBY_FLR_1 | 77991532.53 | 0.00 | 77991532.53 | 3469983.66 | 81461516.20 | 59728886.00 | 153.11 | 42.27 | 8564.62 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 53574.19 | 1513730.90 | 318881.11 | 1832612.02 | 1946875.62 | 2190.00 | 5876.17 | 693.83 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 52429.65 | 1512415.29 | 318856.78 | 1831272.07 | 1946647.51 | 2190.00 | 5880.07 | 689.93 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 0.00 | 1099911.97 | 88971.41 | 1188883.38 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.00 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 51355.53 | 19855184.83 | 88995.74 | 19944180.56 | 26405105.73 | 2190.00 | 5908.88 | 661.12 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 53686.25 | 1513842.96 | 318881.11 | 1832724.07 | 1946875.62 | 2190.00 | 5876.17 | 693.83 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 52019.20 | 1512004.83 | 318856.78 | 1830861.61 | 1946647.51 | 2190.00 | 5876.67 | 693.33 | 0.00 |
CORRIDOR_FLR_3 | 19686529.60 | 0.00 | 19686529.60 | 385591.42 | 20072121.02 | 14972100.18 | 168.58 | 48.09 | 8543.33 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 62508.23 | 427547.41 | 318945.54 | 746492.95 | 486718.90 | 2021.80 | 5878.95 | 859.24 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 59049.52 | 424045.93 | 318921.20 | 742967.13 | 486661.88 | 2045.01 | 5888.09 | 826.90 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 62732.30 | 2407922.61 | 163183.70 | 2571106.31 | 3126920.42 | 2190.00 | 5876.17 | 693.83 | 0.00 |
BANQUET_FLR_6 | 41526711.44 | 0.00 | 41526711.44 | 778784.84 | 42305496.28 | 37458366.31 | 2336.17 | 1032.02 | 5391.81 | 0.00 |
DINING_FLR_6 | 44545606.02 | 0.00 | 44545606.02 | 778784.84 | 45324390.86 | 37458366.31 | 415.20 | 258.87 | 8085.93 | 0.00 |
KITCHEN_FLR_6 | 55639790.54 | 0.00 | 55639790.54 | 697192.99 | 56336983.53 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 11647708.10 | 0.00 | 11647708.10 | 682373.60 | 12330081.69 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 5436005.91 | 0.21E+10 | 32134041.92 | 0.21E+10 | 0.43E+10 | 8760.00 | 6802.01 | 8760.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.1207 | 0.0000 | 1.1207 | 0.0000 | 1.1207 | 0.8545 | 855.52 | 98.04 | 7806.44 |
RETAIL_1_FLR_1 | 0.1744 | 0.0000 | 0.1744 | 0.0174 | 0.1918 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1195 | 0.0000 | 0.1195 | 0.0067 | 0.1263 | 0.0917 | 111.22 | 44.35 | 8604.43 |
MECH_FLR_1 | 0.1117 | 0.0000 | 0.1117 | 0.0159 | 0.1276 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0606 | 0.0000 | 0.0606 | 0.0092 | 0.0698 | 0.0578 | 3621.44 | 220.44 | 4918.12 |
LAUNDRY_FLR_1 | 1.8538 | 0.0000 | 1.8538 | 0.0217 | 1.8755 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.7584 | 0.0000 | 0.7584 | 0.0385 | 0.7969 | 0.6764 | 2765.26 | 229.66 | 5765.08 |
LOBBY_FLR_1 | 2.4731 | 0.0000 | 2.4731 | 0.1100 | 2.5831 | 1.8940 | 153.11 | 42.27 | 8564.62 |
ROOM_1_FLR_3 | 0.0463 | 0.0017 | 0.0480 | 0.0101 | 0.0581 | 0.0617 | 2190.00 | 5876.17 | 693.83 |
ROOM_2_FLR_3 | 0.0463 | 0.0017 | 0.0480 | 0.0101 | 0.0581 | 0.0617 | 2190.00 | 5880.07 | 689.93 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0016 | 0.6296 | 0.0028 | 0.6324 | 0.8373 | 2190.00 | 5908.88 | 661.12 |
ROOM_5_FLR_3 | 0.0463 | 0.0017 | 0.0480 | 0.0101 | 0.0581 | 0.0617 | 2190.00 | 5876.17 | 693.83 |
ROOM_6_FLR_3 | 0.0463 | 0.0016 | 0.0479 | 0.0101 | 0.0581 | 0.0617 | 2190.00 | 5876.67 | 693.33 |
CORRIDOR_FLR_3 | 0.6243 | 0.0000 | 0.6243 | 0.0122 | 0.6365 | 0.4748 | 168.58 | 48.09 | 8543.33 |
ROOM_1_FLR_6 | 0.0116 | 0.0020 | 0.0136 | 0.0101 | 0.0237 | 0.0154 | 2021.80 | 5878.95 | 859.24 |
ROOM_2_FLR_6 | 0.0116 | 0.0019 | 0.0134 | 0.0101 | 0.0236 | 0.0154 | 2045.01 | 5888.09 | 826.90 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0020 | 0.0764 | 0.0052 | 0.0815 | 0.0992 | 2190.00 | 5876.17 | 693.83 |
BANQUET_FLR_6 | 1.3168 | 0.0000 | 1.3168 | 0.0247 | 1.3415 | 1.1878 | 2336.17 | 1032.02 | 5391.81 |
DINING_FLR_6 | 1.4125 | 0.0000 | 1.4125 | 0.0247 | 1.4372 | 1.1878 | 415.20 | 258.87 | 8085.93 |
KITCHEN_FLR_6 | 1.7643 | 0.0000 | 1.7643 | 0.0221 | 1.7864 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3693 | 0.0000 | 0.3693 | 0.0216 | 0.3910 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 63.1917 | 0.1724 | 63.3640 | 0.8045 | 64.1686 | 73.9670 | 8760.00 | 6802.01 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.46E+09 | 0.00 | 0.46E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 35636200.53 | 447354.87 | 36083555.41 | 64690340.46 | 8760.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 14.5316 | 0.0000 | 14.5316 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.1300 | 0.0142 | 1.1442 | 2.0513 | 8760.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 4693.17 | 0.00 | 0.00 | 0.00 | 4066.83 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 15.4533 | 0.0000 | 0.0000 | 0.0000 | 13.4712 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.4274 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1363 |
Defaulted Fields | 1208 |
Fields with Defaults | 4115 |
Autosized Fields | 353 |
Autosizable Fields | 407 |
Autocalculated Fields | 289 |
Autocalculatable Fields | 549 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 6193.13 | 67247.62 | 08-MAR-02:50 | 437675.20 | 29-JUN-19:30 |
Electricity:Building | 2278.97 | 30456.19 | 02-JAN-02:10 | 133648.28 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 245.14 | 2955.01 | 02-JAN-02:10 | 17976.64 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2271.88 | 30315.04 | 02-JAN-02:10 | 133406.95 | 02-JAN-20:10 |
InteriorLights:Electricity | 543.74 | 5032.86 | 02-JAN-02:10 | 45424.10 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 102.03 | 927.11 | 02-JAN-02:10 | 8344.11 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 543.74 | 5032.86 | 02-JAN-02:10 | 45424.10 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 543.74 | 5032.86 | 02-JAN-02:10 | 45424.10 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 102.03 | 927.11 | 02-JAN-02:10 | 8344.11 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 543.74 | 5032.86 | 02-JAN-02:10 | 45424.10 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 15.82 | 195.57 | 02-JAN-02:10 | 1146.69 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 5.64 | 51.23 | 02-JAN-02:10 | 461.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 5.64 | 51.23 | 02-JAN-02:10 | 461.08 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 18.32 | 226.47 | 02-JAN-02:10 | 1327.87 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 6.53 | 59.33 | 02-JAN-02:10 | 533.93 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 6.53 | 59.33 | 02-JAN-02:10 | 533.93 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.00 | 245.14 | 02-JAN-02:10 | 1455.21 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 7.53 | 68.42 | 02-JAN-02:10 | 615.76 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 7.53 | 68.42 | 02-JAN-02:10 | 615.76 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.28 | 66.24 | 02-JAN-02:10 | 379.51 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.68 | 15.26 | 02-JAN-02:10 | 137.35 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.68 | 15.26 | 02-JAN-02:10 | 137.35 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.35 | 1002.76 | 02-JAN-02:10 | 4933.42 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.41 | 40.07 | 02-JAN-02:10 | 360.62 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.41 | 40.07 | 02-JAN-02:10 | 360.62 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 26.01 | 360.56 | 02-JAN-02:10 | 2381.38 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 11.67 | 69.23 | 01-JAN-13:10 | 1416.11 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 11.67 | 69.23 | 01-JAN-13:10 | 1416.11 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 259.76 | 3175.95 | 02-JAN-02:10 | 19610.05 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.76 | 1064.54 | 02-JAN-02:10 | 9580.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.76 | 1064.54 | 02-JAN-02:10 | 9580.84 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 17.85 | 257.74 | 01-JAN-02:10 | 1187.62 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 5.55 | 47.02 | 01-JAN-02:10 | 427.46 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 5.55 | 47.02 | 01-JAN-02:10 | 427.46 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 17.84 | 257.71 | 01-JAN-02:10 | 1187.48 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 5.55 | 47.01 | 01-JAN-02:10 | 427.41 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 5.55 | 47.01 | 01-JAN-02:10 | 427.41 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 295.07 | 4482.89 | 01-JAN-02:10 | 20504.95 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 66.32 | 561.43 | 01-JAN-02:10 | 5104.26 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 66.32 | 561.43 | 01-JAN-02:10 | 5104.26 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 295.15 | 4484.12 | 01-JAN-02:10 | 20510.57 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 66.33 | 561.58 | 01-JAN-02:10 | 5105.65 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 66.33 | 561.58 | 01-JAN-02:10 | 5105.65 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 17.85 | 257.74 | 01-JAN-02:10 | 1187.62 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 5.55 | 47.02 | 01-JAN-02:10 | 427.46 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 5.55 | 47.02 | 01-JAN-02:10 | 427.46 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 17.84 | 257.71 | 01-JAN-02:10 | 1187.48 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 5.55 | 47.01 | 01-JAN-02:10 | 427.41 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 5.55 | 47.01 | 01-JAN-02:10 | 427.41 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 51.07 | 464.00 | 02-JAN-02:10 | 4176.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 51.07 | 464.00 | 02-JAN-02:10 | 4176.01 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 51.07 | 464.00 | 02-JAN-02:10 | 4176.01 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.46 | 64.43 | 01-JAN-02:10 | 296.90 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.39 | 11.75 | 01-JAN-02:10 | 106.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.39 | 11.75 | 01-JAN-02:10 | 106.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.46 | 64.43 | 01-JAN-02:10 | 296.87 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.39 | 11.75 | 01-JAN-02:10 | 106.85 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.39 | 11.75 | 01-JAN-02:10 | 106.85 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 34.95 | 531.01 | 01-JAN-02:10 | 2428.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 7.86 | 66.50 | 01-JAN-02:10 | 604.62 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 7.86 | 66.50 | 01-JAN-02:10 | 604.62 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 201.56 | 2525.61 | 02-JAN-02:10 | 9234.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 25.71 | 276.31 | 02-JAN-02:10 | 2486.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 25.71 | 276.31 | 02-JAN-02:10 | 2486.81 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 201.56 | 2525.61 | 02-JAN-02:10 | 9234.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 25.71 | 276.31 | 02-JAN-02:10 | 2486.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 25.71 | 276.31 | 02-JAN-02:10 | 2486.81 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 443.12 | 5932.71 | 02-JAN-02:10 | 18599.73 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.01 | 109.08 | 02-JAN-02:10 | 981.75 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.01 | 109.08 | 02-JAN-02:10 | 981.75 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 13.51 | 122.77 | 02-JAN-02:10 | 1104.91 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 13.51 | 122.77 | 02-JAN-02:10 | 1104.91 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 13.51 | 122.77 | 02-JAN-02:10 | 1104.91 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 43.82 | 732.79 | 23-APR-22:30 | 2790.51 | 12-NOV-11:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 2336.54 | 2223.08 | 12-DEC-01:50 | 234862.41 | 28-JUN-18:20 |
LowTempRefrigeration:Refrigeration:Electricity | 15.77 | 0.00 | 01-JAN-11:10 | 1308.17 | 17-JUN-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 20.96 | 610.13 | 07-DEC-04:10 | 716.75 | 13-NOV-14:10 |
WaterSystems:Electricity | 475.79 | 1086.56 | 04-AUG-00:40 | 44847.95 | 01-NOV-18:40 |
Electricity:HVAC | 784.07 | 12218.33 | 12-FEB-15:00 | 60975.80 | 07-SEP-21:10 |
Fans:Electricity | 611.35 | 11423.93 | 29-JAN-03:50 | 50202.41 | 07-SEP-21:10 |
General:Fans:Electricity | 611.35 | 11423.93 | 29-JAN-03:50 | 50202.41 | 07-SEP-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ExteriorEquipment:Electricity | 641.45 | 9451.13 | 02-JAN-02:20 | 39153.57 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 22.42 | 386.32 | 02-JAN-02:20 | 1279.09 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 6193.13 | 67247.62 | 08-MAR-02:50 | 437675.20 | 29-JUN-19:30 |
ElectricityPurchased:Plant | 6193.13 | 67247.62 | 08-MAR-02:50 | 437675.20 | 29-JUN-19:30 |
Cogeneration:ElectricityPurchased | 6193.13 | 67247.62 | 08-MAR-02:50 | 437675.20 | 29-JUN-19:30 |
General:Cogeneration:ElectricityPurchased | 6193.13 | 67247.62 | 08-MAR-02:50 | 437675.20 | 29-JUN-19:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 6193.13 | 67247.62 | 08-MAR-02:50 | 437675.20 | 29-JUN-19:30 |
ElectricityNet:Plant | 6193.13 | 67247.62 | 08-MAR-02:50 | 437675.20 | 29-JUN-19:30 |
Cogeneration:ElectricityNet | 6193.13 | 67247.62 | 08-MAR-02:50 | 437675.20 | 29-JUN-19:30 |
General:Cogeneration:ElectricityNet | 6193.13 | 67247.62 | 08-MAR-02:50 | 437675.20 | 29-JUN-19:30 |
ExteriorLights:Electricity | 174.52 | 0.00 | 01-JAN-07:30 | 11096.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 174.52 | 0.00 | 01-JAN-07:30 | 11096.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 150.30 | 0.00 | 01-JAN-11:10 | 9938.94 | 01-APR-09:00 |
General:HeatRecovery:Electricity | 150.30 | 0.00 | 01-JAN-11:10 | 9938.94 | 01-APR-09:00 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.56 | 04-AUG-00:40 | 4738.76 | 05-OCT-18:10 |
Water Heater Parasitic:WaterSystems:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1689.08 | 0.00 | 01-JAN-00:10 | 188698.43 | 28-JUN-18:10 |
General:Cooling:Electricity | 1689.08 | 0.00 | 01-JAN-00:10 | 188698.43 | 28-JUN-18:10 |
Pumps:Electricity | 134.94 | 48.12 | 24-MAR-14:50 | 6743.74 | 28-JUN-19:10 |
General:Pumps:Electricity | 134.94 | 48.12 | 24-MAR-14:50 | 6743.74 | 28-JUN-19:10 |
WIRED_LTG_ELECTRICITY | 19.14 | 0.00 | 01-JAN-00:10 | 1598.93 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 3000.86 | 29270.80 | 11-MAR-02:10 | 297676.92 | 07-DEC-21:00 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 1212.03 | 15908.90 | 05-JAN-11:10 | 248946.80 | 16-DEC-23:40 |
WaterSystems:NaturalGas | 819.38 | 15908.90 | 01-JAN-09:10 | 83451.25 | 31-DEC-21:00 |
Water Heater:WaterSystems:NaturalGas | 819.38 | 15908.90 | 01-JAN-09:10 | 83451.25 | 31-DEC-21:00 |
Heating:NaturalGas | 392.65 | 0.00 | 02-JAN-19:20 | 186036.48 | 01-JAN-00:10 |
Boiler:Heating:NaturalGas | 392.65 | 0.00 | 02-JAN-19:20 | 186036.48 | 01-JAN-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 5376.87 | 0.00 | 01-JAN-00:10 | 598761.53 | 10-SEP-22:00 |
PlantLoopCoolingDemand:HVAC | 5376.87 | 0.00 | 01-JAN-00:10 | 598761.53 | 10-SEP-22:00 |
CoolingCoils:PlantLoopCoolingDemand | 5376.87 | 0.00 | 01-JAN-00:10 | 598761.53 | 10-SEP-22:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 24-JAN-22:00 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 24-JAN-22:00 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 24-JAN-22:00 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 24-JAN-22:00 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 24-JAN-22:00 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 24-JAN-22:00 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 04-APR-06:40 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 04-APR-06:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 27083.55 | 119820.48 | 06-MAR-11:30 | 2387254.25 | 13-JUL-18:20 |
EnergyTransfer:Building | 5875.95 | 86196.34 | 12-FEB-15:00 | 390308.45 | 28-JUN-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 721.23 | 10289.60 | 07-DEC-04:00 | 35505.96 | 13-AUG-10:40 |
Refrigeration:EnergyTransfer | 181.60 | 4016.05 | 23-APR-22:20 | 10366.86 | 04-AUG-06:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.80 | 2008.03 | 23-APR-22:20 | 5183.43 | 04-AUG-06:30 |
General:Refrigeration:EnergyTransfer | 90.80 | 2008.03 | 23-APR-22:20 | 5183.43 | 04-AUG-06:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.80 | 2008.03 | 23-APR-22:20 | 5183.43 | 04-AUG-06:30 |
EnergyTransfer:Plant | 13647.02 | 17102.43 | 24-MAR-14:50 | 1378041.68 | 10-SEP-22:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.56 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.24 | 1815.73 | 07-DEC-04:10 | 2559.91 | 13-NOV-14:10 |
EnergyTransfer:HVAC | 7560.58 | 372.03 | 24-MAR-14:20 | 798271.57 | 13-JUL-18:20 |
CoolingCoils:EnergyTransfer | 6505.50 | 0.00 | 01-JAN-00:10 | 677961.63 | 02-SEP-20:30 |
EnergyTransfer:Zone:BASEMENT | 368.36 | 7698.31 | 27-MAR-14:00 | 21680.88 | 20-SEP-21:00 |
Heating:EnergyTransfer | 19.93 | 0.00 | 01-JAN-11:10 | 29888.41 | 07-DEC-06:00 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 19.93 | 0.00 | 01-JAN-11:10 | 29888.41 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 5765.22 | 81862.95 | 01-JAN-06:00 | 386765.84 | 28-JUN-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 368.36 | 7698.31 | 27-MAR-14:00 | 21680.88 | 20-SEP-21:00 |
General:Cooling:EnergyTransfer | 5765.22 | 81862.95 | 01-JAN-06:00 | 386765.84 | 28-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 368.36 | 7698.31 | 27-MAR-14:00 | 21680.88 | 20-SEP-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 54.38 | 0.35 | 26-MAR-02:40 | 3946.58 | 02-OCT-12:40 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.02 | 0.00 | 01-JAN-00:10 | 386.94 | 16-DEC-07:20 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.02 | 0.00 | 01-JAN-00:10 | 386.94 | 16-DEC-07:20 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 54.36 | 0.00 | 01-JAN-05:30 | 3946.58 | 02-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 54.36 | 0.00 | 01-JAN-05:30 | 3946.58 | 02-OCT-12:40 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 40.60 | 767.79 | 12-FEB-16:00 | 2550.53 | 28-JUN-20:40 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 40.60 | 767.79 | 12-FEB-16:00 | 2550.53 | 28-JUN-20:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 40.60 | 767.79 | 12-FEB-16:00 | 2550.53 | 28-JUN-20:40 |
EnergyTransfer:Zone:MECH_FLR_1 | 34.53 | 1.49 | 07-DEC-03:50 | 2615.74 | 28-JUN-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 57.73 | 07-DEC-05:00 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 57.73 | 07-DEC-05:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 34.53 | 0.00 | 07-DEC-03:50 | 2615.74 | 28-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 34.53 | 0.00 | 07-DEC-03:50 | 2615.74 | 28-JUN-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 18.26 | 0.03 | 06-DEC-05:40 | 1314.73 | 28-JUN-18:50 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 89.31 | 07-DEC-05:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 89.31 | 07-DEC-05:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 18.26 | 0.00 | 01-JAN-04:20 | 1314.73 | 28-JUN-18:50 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 18.26 | 0.00 | 01-JAN-04:20 | 1314.73 | 28-JUN-18:50 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 618.91 | 9700.14 | 07-DEC-05:00 | 40074.74 | 28-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 618.91 | 9700.14 | 07-DEC-05:00 | 40074.74 | 28-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 618.91 | 9700.14 | 07-DEC-05:00 | 40074.74 | 28-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 262.35 | 2736.75 | 12-FEB-16:00 | 14213.89 | 01-NOV-15:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 262.35 | 2736.75 | 12-FEB-16:00 | 14213.89 | 01-NOV-15:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 262.35 | 2736.75 | 12-FEB-16:00 | 14213.89 | 01-NOV-15:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 863.06 | 16314.22 | 12-FEB-16:00 | 47581.75 | 28-JUN-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 863.06 | 16314.22 | 12-FEB-16:00 | 47581.75 | 28-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 863.06 | 16314.22 | 12-FEB-16:00 | 47581.75 | 28-JUN-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 93.29 | 0.00 | 01-JAN-08:10 | 13017.83 | 27-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 2.21 | 0.00 | 01-JAN-08:10 | 2824.24 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 2.21 | 0.00 | 01-JAN-08:10 | 2824.24 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 91.08 | 0.00 | 01-JAN-00:10 | 13017.83 | 27-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 91.08 | 0.00 | 01-JAN-00:10 | 13017.83 | 27-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 79.90 | 0.00 | 01-JAN-08:10 | 13283.21 | 27-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 4.11 | 0.00 | 01-JAN-08:10 | 4419.37 | 07-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 4.11 | 0.00 | 01-JAN-08:10 | 4419.37 | 07-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 75.79 | 0.00 | 01-JAN-00:10 | 13283.21 | 27-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 75.79 | 0.00 | 01-JAN-00:10 | 13283.21 | 27-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 490.09 | 0.00 | 01-JAN-00:10 | 50084.80 | 20-NOV-14:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 721.34 | 09-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 721.34 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 490.09 | 0.00 | 01-JAN-00:10 | 50084.80 | 20-NOV-14:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 490.09 | 0.00 | 01-JAN-00:10 | 50084.80 | 20-NOV-14:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 570.16 | 0.00 | 01-JAN-08:10 | 79584.72 | 26-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 3.25 | 0.00 | 01-JAN-08:10 | 15827.15 | 07-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 3.25 | 0.00 | 01-JAN-08:10 | 15827.15 | 07-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 566.92 | 0.00 | 01-JAN-00:10 | 79584.72 | 26-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 566.92 | 0.00 | 01-JAN-00:10 | 79584.72 | 26-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 96.31 | 0.00 | 01-JAN-08:10 | 10638.92 | 19-JUN-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 2.21 | 0.00 | 01-JAN-08:10 | 2840.65 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 2.21 | 0.00 | 01-JAN-08:10 | 2840.65 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 94.10 | 0.00 | 01-JAN-00:10 | 10638.92 | 19-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 94.10 | 0.00 | 01-JAN-00:10 | 10638.92 | 19-JUN-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 82.24 | 0.00 | 01-JAN-08:10 | 11972.11 | 01-JUL-08:20 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 3.98 | 0.00 | 01-JAN-08:10 | 3551.37 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 3.98 | 0.00 | 01-JAN-08:10 | 3551.37 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 78.26 | 0.00 | 01-JAN-00:10 | 11972.11 | 01-JUL-08:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 78.26 | 0.00 | 01-JAN-00:10 | 11972.11 | 01-JUL-08:20 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 197.23 | 552.33 | 18-DEC-07:10 | 13562.06 | 28-JUN-18:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 197.23 | 552.33 | 18-DEC-07:10 | 13562.06 | 28-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 197.23 | 552.33 | 18-DEC-07:10 | 13562.06 | 28-JUN-18:30 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 24.18 | 0.00 | 01-JAN-08:10 | 3506.03 | 27-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 1.17 | 0.00 | 01-JAN-08:10 | 997.37 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 1.17 | 0.00 | 01-JAN-08:10 | 997.37 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 23.01 | 0.00 | 01-JAN-00:10 | 3506.03 | 27-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 23.01 | 0.00 | 01-JAN-00:10 | 3506.03 | 27-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 21.32 | 0.00 | 01-JAN-08:10 | 3569.78 | 27-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 1.92 | 0.00 | 01-JAN-08:10 | 1212.92 | 07-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 1.92 | 0.00 | 01-JAN-08:10 | 1212.92 | 07-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 19.40 | 0.00 | 01-JAN-00:10 | 3569.78 | 27-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 19.40 | 0.00 | 01-JAN-00:10 | 3569.78 | 27-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 141.27 | 0.00 | 01-JAN-08:10 | 16568.90 | 18-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 1.05 | 0.00 | 01-JAN-00:10 | 2786.58 | 27-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 1.05 | 0.00 | 01-JAN-00:10 | 2786.58 | 27-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 140.22 | 0.00 | 01-JAN-01:20 | 16568.90 | 18-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 140.22 | 0.00 | 01-JAN-01:20 | 16568.90 | 18-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 472.92 | 8948.31 | 07-DEC-09:50 | 24852.60 | 28-JUN-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 472.92 | 8948.31 | 07-DEC-09:50 | 24852.60 | 28-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 472.92 | 8948.31 | 07-DEC-09:50 | 24852.60 | 28-JUN-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 509.62 | 9930.37 | 07-DEC-10:10 | 26035.81 | 28-JUN-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 509.62 | 9930.37 | 07-DEC-10:10 | 26035.81 | 28-JUN-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 509.62 | 9930.37 | 07-DEC-10:10 | 26035.81 | 28-JUN-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 630.43 | 8230.89 | 07-DEC-04:00 | 30420.69 | 13-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 630.43 | 8230.89 | 07-DEC-04:00 | 30420.69 | 13-AUG-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 115.74 | 0.14 | 17-DEC-04:30 | 7817.70 | 28-JUN-18:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 665.30 | 07-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 665.30 | 07-DEC-07:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 115.73 | 0.00 | 01-JAN-05:10 | 7817.70 | 28-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 115.73 | 0.00 | 01-JAN-05:10 | 7817.70 | 28-JUN-18:10 |
PlantLoopHeatingDemand:Facility | 2384.59 | 6709.43 | 25-JUL-00:20 | 286159.54 | 16-DEC-22:50 |
PlantLoopHeatingDemand:Plant | 2102.04 | 6709.43 | 25-JUL-00:20 | 199686.11 | 03-APR-20:40 |
WaterSystems:PlantLoopHeatingDemand | 2102.04 | 6709.43 | 25-JUL-00:20 | 199686.11 | 03-APR-20:40 |
General:WaterSystems:PlantLoopHeatingDemand | 601.64 | 6705.93 | 25-JUL-00:10 | 47140.96 | 24-JAN-07:10 |
HeatingCoils:EnergyTransfer | 282.55 | 0.00 | 02-JAN-19:20 | 150227.63 | 01-JAN-00:10 |
PlantLoopHeatingDemand:HVAC | 282.55 | 0.00 | 02-JAN-19:20 | 150227.63 | 01-JAN-00:10 |
HeatingCoils:PlantLoopHeatingDemand | 282.55 | 0.00 | 02-JAN-19:20 | 150227.63 | 01-JAN-00:10 |
HeatRecoveryForHeating:EnergyTransfer | 272.99 | 0.00 | 01-JAN-11:10 | 307388.31 | 05-DEC-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 499.55 | 0.00 | 01-JAN-00:10 | 170936.50 | 17-JUN-16:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 1500.40 | 0.00 | 01-JAN-00:10 | 165700.75 | 03-APR-20:40 |
WaterSystems:EnergyTransfer | 601.64 | 6705.93 | 25-JUL-00:10 | 47140.96 | 24-JAN-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 601.64 | 6705.93 | 25-JUL-00:10 | 47140.96 | 24-JAN-07:10 |
Boilers:EnergyTransfer | 279.96 | 0.00 | 02-JAN-19:20 | 153038.25 | 01-JAN-00:10 |
Chillers:EnergyTransfer | 5492.77 | 0.00 | 01-JAN-00:10 | 607345.13 | 10-SEP-22:00 |
HeatRejection:EnergyTransfer | 7181.86 | 0.00 | 01-JAN-00:10 | 743008.09 | 10-SEP-22:00 |
General:HeatRejection:EnergyTransfer | 7181.86 | 0.00 | 01-JAN-00:10 | 743008.09 | 10-SEP-22:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -368.364 | 0.000 | 0.000 | 139.859 | 102.033 | 143.105 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -16.634 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.015 | -54.361 | 0.000 | 0.000 | 14.634 | 5.638 | 10.186 | 26.079 | 0.000 | 1.644 | 5.282 | 0.000 | -6.569 | 0.000 | -2.548 | -0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -40.596 | 0.000 | 0.000 | 16.269 | 6.529 | 11.795 | 0.000 | 0.000 | 0.641 | 6.461 | 0.000 | 0.000 | 0.000 | -1.098 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -34.528 | 0.000 | 0.000 | 3.592 | 7.530 | 12.471 | 0.000 | 0.000 | 1.551 | 11.644 | 0.000 | 0.000 | 0.000 | -2.260 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.002 | -18.259 | 0.000 | 0.000 | 2.777 | 1.680 | 3.598 | 0.000 | 0.000 | 0.899 | 10.587 | 0.000 | 0.000 | 0.000 | -1.284 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -618.910 | 0.000 | 0.000 | 11.134 | 4.410 | 658.131 | 0.000 | 0.000 | 2.217 | 0.000 | 0.000 | 0.000 | 0.000 | -3.562 | -53.419 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -262.353 | 0.000 | 0.000 | 182.506 | 11.670 | 14.341 | 72.547 | 0.000 | 3.621 | 4.473 | 0.000 | -20.269 | 0.000 | -6.535 | -0.000 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -863.064 | 0.000 | 0.000 | 538.855 | 110.757 | 148.998 | 96.713 | 0.000 | 10.394 | 2.939 | 0.000 | -26.678 | 0.000 | -18.915 | -0.000 |
ROOM_1_FLR_3 | 3.731 | -80.778 | 0.000 | -11.825 | 0.000 | 0.000 | 9.648 | 5.554 | 12.292 | 56.941 | 0.000 | 5.091 | 18.770 | 0.000 | -13.446 | 0.000 | -5.978 | -0.000 |
ROOM_2_FLR_3 | 6.226 | -65.806 | 0.000 | -12.104 | 0.000 | 0.000 | 9.587 | 5.553 | 12.291 | 44.087 | 0.000 | 4.973 | 15.311 | 0.000 | -13.900 | 0.000 | -6.219 | -0.001 |
ROOM_3_MULT19_FLR_3 | 0.000 | -473.840 | 0.000 | -16.241 | 0.000 | 0.000 | 0.000 | 66.316 | 228.754 | 289.257 | 0.000 | 12.352 | 59.530 | 0.000 | -114.984 | 0.000 | -51.146 | -0.001 |
ROOM_4_MULT19_FLR_3 | 12.306 | -413.265 | 0.000 | -162.709 | 0.000 | 0.000 | 182.692 | 66.334 | 228.817 | 135.693 | 0.000 | 27.041 | 37.698 | 0.000 | -73.108 | 0.000 | -41.499 | -0.008 |
ROOM_5_FLR_3 | 3.701 | -83.755 | 0.000 | -11.831 | 0.000 | 0.000 | 9.638 | 5.554 | 12.292 | 58.746 | 0.000 | 5.085 | 19.448 | 0.000 | -12.838 | 0.000 | -6.041 | -0.001 |
ROOM_6_FLR_3 | 5.931 | -68.084 | 0.000 | -12.129 | 0.000 | 0.000 | 9.578 | 5.553 | 12.291 | 45.281 | 0.000 | 4.955 | 15.645 | 0.000 | -12.757 | 0.000 | -6.263 | -0.001 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.000 | -197.230 | 0.000 | 0.000 | 112.530 | 51.065 | 0.000 | 50.759 | 0.000 | 4.677 | 3.261 | 0.000 | -17.838 | 0.000 | -7.225 | -0.000 |
ROOM_1_FLR_6 | 1.675 | -20.563 | 0.000 | -2.956 | 0.000 | 0.000 | 2.413 | 1.388 | 3.073 | 14.177 | 0.000 | 1.265 | 4.347 | 0.000 | -3.301 | 0.000 | -1.519 | -0.000 |
ROOM_2_FLR_6 | 2.550 | -17.008 | 0.000 | -3.016 | 0.000 | 0.000 | 2.401 | 1.388 | 3.073 | 10.997 | 0.000 | 1.236 | 3.343 | 0.000 | -3.396 | 0.000 | -1.566 | -0.000 |
ROOM_3_MULT9_FLR_6 | 2.280 | -122.420 | 0.000 | -19.026 | 0.000 | 0.000 | 21.678 | 7.855 | 27.097 | 71.709 | 0.000 | 5.911 | 28.090 | 0.000 | -15.269 | 0.000 | -7.906 | -0.000 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -472.928 | 0.000 | 0.000 | 315.199 | 25.706 | 175.857 | 13.104 | 0.000 | 2.240 | 0.000 | 0.000 | -11.099 | 0.000 | -4.433 | -43.647 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -509.621 | 0.000 | 0.000 | 314.585 | 25.706 | 175.857 | 12.810 | 0.000 | 2.233 | 0.001 | 0.000 | -11.461 | 0.000 | -4.478 | -5.631 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -630.414 | 0.000 | 0.000 | 28.241 | 12.005 | 540.650 | 27.503 | 0.000 | 1.997 | 32.072 | 0.000 | -8.084 | 0.000 | -3.970 | -0.001 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.011 | -115.733 | 0.000 | 0.000 | 29.983 | 13.511 | 0.000 | 24.136 | 0.000 | 2.014 | 57.201 | 0.000 | -7.987 | 0.000 | -3.135 | -0.000 |
Total Facility | 38.401 | -1345.518 | 0.029 | -4438.199 | 0.000 | 0.000 | 1957.799 | 543.736 | 2434.967 | 1050.540 | 0.000 | 102.037 | 336.102 | 0.000 | -372.983 | 0.000 | -187.578 | -119.345 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 20-SEP-21:00 | 0.00 | 0.00 | 0.00 | -21683.07 | 0.00 | 0.00 | 5924.36 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -783.84 |
RETAIL_1_FLR_1 | 02-OCT-12:40 | 0.00 | 0.00 | 0.00 | -3946.68 | 0.00 | 0.00 | 150.60 | 128.08 | 252.59 | 4115.96 | 0.00 | 185.46 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -886.00 |
RETAIL_2_FLR_1 | 28-JUN-20:40 | 0.00 | 0.00 | 0.00 | -2550.22 | 0.00 | 0.00 | 697.62 | 474.61 | 752.15 | 0.00 | 0.00 | 82.75 | 543.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 28-JUN-20:00 | 0.00 | 0.00 | 0.00 | -2615.22 | 0.00 | 0.00 | 129.09 | 615.76 | 839.45 | 0.00 | 0.00 | 216.98 | 813.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 28-JUN-18:40 | 0.00 | 0.00 | 0.00 | -1314.60 | 0.00 | 0.00 | 99.30 | 122.09 | 229.41 | 0.00 | 0.00 | 155.82 | 707.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 28-JUN-20:00 | 0.00 | 0.00 | 0.00 | -40067.37 | 0.00 | 0.00 | 408.91 | 360.62 | 44299.38 | 0.00 | 0.00 | 296.31 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5297.85 |
CAFE_FLR_1 | 01-NOV-15:03 | 0.00 | 0.00 | 0.00 | -14229.08 | 0.00 | 0.00 | 4947.93 | 86.54 | 355.63 | 10241.48 | 0.00 | 201.28 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1603.78 |
LOBBY_FLR_1 | 28-JUN-21:10 | 0.00 | 0.00 | 0.00 | -47579.00 | 0.00 | 0.00 | 26440.45 | 6387.23 | 7389.94 | 1187.04 | 0.00 | 1242.24 | 4932.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 27-JUN-18:02 | 0.00 | -14108.28 | 0.00 | -679.26 | 0.00 | 0.00 | 335.50 | 380.45 | 516.26 | 7397.47 | 0.00 | 718.78 | 5439.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 01-JUL-08:61 | 0.00 | -15759.20 | 0.00 | -818.79 | 0.00 | 0.00 | 109.58 | 239.35 | 653.15 | 1157.97 | 0.00 | 117.65 | 14300.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 20-NOV-14:30 | 0.00 | -50083.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1429.19 | 5097.90 | 54276.09 | 0.00 | 67.06 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10786.63 |
ROOM_4_MULT19_FLR_3 | 01-JUL-08:61 | 0.00 | -93367.56 | 0.00 | -10668.99 | 0.00 | 0.00 | 2238.95 | 2859.17 | 12159.85 | 8677.56 | 0.00 | 730.84 | 77370.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 01-JUL-08:61 | 0.00 | -12506.30 | 0.00 | -687.90 | 0.00 | 0.00 | 130.71 | 239.38 | 653.23 | 6967.05 | 0.00 | 202.09 | 5001.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 21-MAY-08:61 | 0.00 | -14953.53 | 0.00 | -942.17 | 0.00 | 0.00 | 89.64 | 239.35 | 653.15 | 7244.13 | 0.00 | 0.00 | 7725.37 | 0.00 | -0.00 | 0.00 | -55.94 | 0.00 |
CORRIDOR_FLR_3 | 28-JUN-18:25 | 0.00 | 0.00 | 0.00 | -13564.49 | 0.00 | 0.00 | 4080.30 | 3712.00 | 0.00 | 4120.49 | 0.00 | 837.02 | 814.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 27-JUN-18:02 | 0.00 | -3763.68 | 0.00 | -169.81 | 0.00 | 0.00 | 83.87 | 95.11 | 129.07 | 1838.51 | 0.00 | 179.11 | 1607.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 01-JUL-08:61 | 0.00 | -4129.91 | 0.00 | -200.09 | 0.00 | 0.00 | 27.91 | 59.84 | 163.29 | 296.70 | 0.00 | 31.72 | 3750.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 18-OCT-15:01 | 0.00 | -16733.13 | 0.00 | -1108.41 | 0.00 | 0.00 | 529.39 | 169.29 | 603.86 | 8090.22 | 0.00 | 352.20 | 8096.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 28-JUN-21:20 | 0.00 | 0.00 | 0.00 | -24852.43 | 0.00 | 0.00 | 15617.93 | 1657.87 | 6747.90 | 490.43 | 0.00 | 267.65 | 70.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 28-JUN-21:20 | 0.00 | 0.00 | 0.00 | -26035.71 | 0.00 | 0.00 | 15616.83 | 1657.87 | 6747.90 | 476.87 | 0.00 | 267.64 | 1268.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 13-AUG-10:50 | 0.00 | 0.00 | 0.00 | -30414.78 | 0.00 | 0.00 | 462.87 | 327.25 | 23951.61 | 3055.87 | 0.00 | 229.19 | 2387.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 28-JUN-18:04 | 0.00 | 0.00 | 0.00 | -7824.75 | 0.00 | 0.00 | 1079.64 | 982.15 | 0.00 | 1710.65 | 0.00 | 376.09 | 3676.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 27-JUN-18:02 | 0.00 | -194984.86 | 0.00 | -220313.14 | 0.00 | 0.00 | 74262.07 | 36672.72 | 121562.63 | 81275.35 | 0.00 | 16735.94 | 84789.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 16-DEC-07:20 | 0.00 | 0.00 | 386.89 | 0.00 | 0.00 | 0.00 | 447.54 | 153.69 | 288.68 | 0.00 | 0.00 | 0.00 | 120.72 | 0.00 | -993.58 | 0.00 | -403.93 | 0.00 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 07-DEC-05:00 | 0.00 | 0.00 | 57.73 | 0.00 | 0.00 | 0.00 | 197.29 | 68.42 | 176.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -419.50 | -80.67 |
STORAGE_FLR_1 | 07-DEC-05:00 | 0.00 | 0.00 | 89.32 | 0.00 | 0.00 | 0.00 | 151.77 | 15.26 | 50.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -242.03 | -65.29 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 07-DEC-09:01 | 8242.30 | 343.96 | 0.00 | -343.96 | 0.00 | 0.00 | 104.56 | 188.08 | 453.05 | 1441.44 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -655.92 | -9773.50 |
ROOM_2_FLR_3 | 06-DEC-09:01 | 8474.53 | 277.06 | 0.00 | -277.06 | 0.00 | 0.00 | 108.88 | 188.06 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -892.87 | 0.00 | -619.18 | -7712.42 |
ROOM_3_MULT19_FLR_3 | 09-JAN-08:10 | 1442.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2245.87 | 8431.14 | 9130.47 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4290.58 | -16959.56 |
ROOM_4_MULT19_FLR_3 | 07-DEC-09:01 | 46912.85 | 4950.85 | 0.00 | -4950.85 | 0.00 | 0.00 | 1928.32 | 2246.49 | 8433.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5322.14 | 0.00 | -3556.08 | -50642.88 |
ROOM_5_FLR_3 | 12-FEB-19:02 | 7425.56 | 378.78 | 0.00 | -378.78 | 0.00 | 0.00 | 335.46 | 427.46 | 516.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1020.20 | 0.00 | -419.13 | -7265.41 |
ROOM_6_FLR_3 | 07-DEC-16:01 | 7851.21 | 372.99 | 0.00 | -372.99 | 0.00 | 0.00 | 277.09 | 119.68 | 273.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -583.87 | 0.00 | -679.02 | -7258.99 |
CORRIDOR_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 06-DEC-09:01 | 2462.13 | 77.19 | 0.00 | -77.19 | 0.00 | 0.00 | 26.86 | 47.02 | 113.26 | 399.46 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -161.01 | -2887.73 |
ROOM_2_FLR_6 | 06-DEC-09:01 | 2503.09 | 70.44 | 0.00 | -70.44 | 0.00 | 0.00 | 27.22 | 47.02 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -211.93 | 0.00 | -156.33 | -2322.31 |
ROOM_3_MULT9_FLR_6 | 27-MAR-08:62 | 11058.80 | 604.78 | 0.00 | -604.78 | 0.00 | 0.00 | 230.87 | 266.03 | 998.70 | 233.26 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -609.36 | -12178.29 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 07-DEC-07:05 | 0.00 | 0.00 | 665.46 | 0.00 | 0.00 | 0.00 | 733.29 | 613.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1349.76 | 0.00 | -507.07 | -155.76 |
Total Facility | 07-DEC-09:01 | -41867.10 | 106613.63 | 14.63 | -106613.63 | 0.00 | 0.00 | 22704.08 | 18329.68 | 87870.62 | 70468.54 | 0.00 | 0.00 | 0.00 | 0.00 | -8025.17 | 0.00 | -18715.08 | -130780.20 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 23.3070 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 23.1972 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6535 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6535 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3518 | 2.3518 | 1.1759 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3688 | 0.3688 | 0.1844 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2564 | 0.2564 | 0.1282 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2462 | 0.2462 | 0.1231 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1357 | 0.1357 | 0.0679 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.6391 | 3.6391 | 1.8195 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5611 | 1.5611 | 0.7805 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1504 | 5.1504 | 2.5752 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4039 | 1.4039 | 0.7019 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4278 | 2.4278 | 1.2139 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5443 | 2.5443 | 1.2721 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4154 | 2.4154 | 1.2077 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8063 | 0.8063 | 0.4031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 23.3070 | 23.1972 | 23.3070 | 11.6535 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1759 | 1.1759 | 1.1759 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1844 | 0.1844 | 0.1844 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1282 | 0.1282 | 0.1282 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1231 | 0.1231 | 0.1231 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0679 | 0.0679 | 0.0679 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8195 | 1.8195 | 1.8195 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7805 | 0.7805 | 0.7805 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5752 | 2.5752 | 2.5752 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7019 | 0.7019 | 0.7019 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2139 | 1.2139 | 1.2139 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2721 | 1.2721 | 1.2721 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2077 | 1.2077 | 1.2077 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4031 | 0.4031 | 0.4031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6535 | 11.6535 | 11.6535 | 11.6535 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 76.00 |
Number of hours not met | 76.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 392.65 | 186036.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1689.08 | 188698.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 543.74 | 45424.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 174.52 | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 952.41 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 22.42 | 1279.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 611.35 | 50202.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 134.94 | 6743.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 150.30 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4738.76 | 819.38 | 83451.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Other | 0.00 | 40109.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.77 | 1308.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 20.96 | 716.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1771.96 | 6193.13 |
Natural Gas | 1788.84 | 3000.86 |
Additional | 0.00 | 0.00 |
Total | 3560.80 | 9193.99 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 47.93 |
Space Heating | 0.00 |
Space Cooling | 148.88 |
Fans (All) | 53.89 |
Service Water Heating | 41.94 |
Receptacle Equipment | 152.32 |
Miscellaneous (All) | 545.88 |
Subtotal | 545.88 |
Natural Gas [MJ/m2] | |
Space Heating | 34.61 |
Service Water Heating | 72.22 |
Miscellaneous (All) | 264.50 |
Subtotal | 264.50 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.91 |
Space Heating | 4.27 |
Space Cooling | 18.37 |
Fans (All) | 6.65 |
Service Water Heating | 14.09 |
Receptacle Equipment | 38.25 |
Miscellaneous | 12.45 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2398. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 2482. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8322.00 | 438.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8322.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 438.00 | 0.00 | 0.00 | 0.00 |
Average | 8739.98 | 20.02 | 0.00 | 0.00 | 0.00 |
Sum | 192279.50 | 440.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8747.33 | 12.67 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8221.33 | 538.67 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8347.50 | 412.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8744.83 | 15.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8154.50 | 605.50 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8726.17 | 33.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8648.50 | 111.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8743.33 | 16.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8265.00 | 495.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8305.33 | 454.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8727.50 | 32.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8154.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 605.50 | 0.00 | 0.00 | 0.00 |
Average | 8635.70 | 124.30 | 0.00 | 0.00 | 0.00 |
Sum | 189985.33 | 2734.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59017.67 | 138.33 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 646172.83 | 64244.17 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1969793.50 | 145635.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4150.33 | 3.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4152.17 | 1.83 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4150.50 | 3.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 98418.33 | 1939.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4150.00 | 4.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1142247.50 | 103467.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1149615.50 | 96099.50 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108027.67 | 241.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1969793.50 | 145635.50 | 0.00 | 0.00 | 0.00 |
Average | 270169.82 | 18717.23 | 0.00 | 0.00 | 0.00 |
Sum | 5943736.00 | 411779.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:03:03
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.289497E+11 | 14006.18 | 20-JAN-22:00 | 13.30 | 10.27 | 0.799088E+10 | 4837.08 | 27-JAN-22:19 | 11.67 | 4.41 |
February | 0.229889E+11 | 12045.86 | 01-FEB-22:00 | 10.00 | 5.32 | 0.665323E+10 | 4836.94 | 01-FEB-22:19 | 9.33 | 4.99 |
March | 0.233525E+11 | 10688.80 | 01-MAR-21:00 | 15.50 | 11.31 | 0.691660E+10 | 4439.42 | 01-MAR-22:10 | 14.30 | 10.92 |
April | 0.247833E+11 | 11953.78 | 30-APR-10:33 | 30.00 | 11.09 | 0.692779E+10 | 4459.12 | 21-APR-22:10 | 30.00 | 11.09 |
May | 0.248376E+11 | 11598.97 | 04-MAY-18:10 | 33.67 | 13.32 | 0.693779E+10 | 4384.09 | 01-MAY-22:10 | 33.67 | 13.32 |
June | 0.259680E+11 | 12622.55 | 28-JUN-18:10 | 40.83 | 17.83 | 0.694571E+10 | 4436.77 | 13-JUN-22:10 | 40.83 | 17.83 |
July | 0.315993E+11 | 16060.55 | 14-JUL-21:00 | 28.00 | 20.32 | 0.802823E+10 | 4837.13 | 07-JUL-22:10 | 28.00 | 20.32 |
August | 0.351071E+11 | 18522.66 | 04-AUG-21:00 | 23.00 | 18.90 | 0.821754E+10 | 4837.08 | 21-AUG-00:20 | 26.00 | 16.49 |
September | 0.390186E+11 | 21680.88 | 20-SEP-21:00 | 28.30 | 17.23 | 0.797177E+10 | 4837.12 | 15-SEP-03:09 | 28.30 | 17.23 |
October | 0.392465E+11 | 21257.09 | 19-OCT-21:00 | 20.00 | 8.80 | 0.823198E+10 | 4837.25 | 19-OCT-21:00 | 20.00 | 11.28 |
November | 0.369414E+11 | 20936.10 | 22-NOV-22:00 | 8.80 | 1.39 | 0.796067E+10 | 4837.23 | 01-NOV-01:39 | 8.80 | 1.39 |
December | 0.355687E+11 | 20099.51 | 01-DEC-22:00 | 10.00 | 4.18 | 0.822005E+10 | 4837.35 | 12-DEC-22:10 | 12.83 | 9.59 |
Annual Sum or Average | 0.368362E+12 | 0.910022E+11 | ||||||||
Minimum of Months | 0.229889E+11 | 10688.80 | 8.80 | 1.39 | 0.665323E+10 | 4384.09 | 8.80 | 1.39 | ||
Maximum of Months | 0.392465E+11 | 21680.88 | 40.83 | 20.32 | 0.823198E+10 | 4837.35 | 40.83 | 20.32 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.427772E+10 | 3521.93 | 14-JAN-13:40 | 26.67 | 10.98 | 0.705078E+09 | 459.50 | 19-JAN-22:19 | 14.33 | 6.76 |
February | 0.259851E+10 | 2491.68 | 01-FEB-14:00 | 16.00 | 7.74 | 0.591069E+09 | 429.94 | 01-FEB-00:10 | 16.00 | 7.74 |
March | 0.321325E+10 | 2656.38 | 18-MAR-13:40 | 26.27 | 12.12 | 0.674469E+09 | 473.73 | 16-MAR-21:30 | 26.27 | 12.12 |
April | 0.459690E+10 | 3114.38 | 14-APR-14:10 | 34.17 | 14.15 | 0.746877E+09 | 491.85 | 12-APR-23:10 | 34.17 | 14.15 |
May | 0.479845E+10 | 2625.40 | 31-MAY-18:15 | 35.33 | 13.34 | 0.789310E+09 | 491.86 | 10-MAY-23:10 | 35.33 | 13.34 |
June | 0.564041E+10 | 3504.82 | 28-JUN-18:13 | 40.67 | 17.68 | 0.798714E+09 | 491.86 | 09-JUN-23:19 | 40.67 | 17.68 |
July | 0.559898E+10 | 3229.85 | 21-JUL-18:30 | 38.00 | 19.28 | 0.820573E+09 | 491.86 | 01-JUL-00:10 | 38.00 | 19.28 |
August | 0.577296E+10 | 3682.42 | 28-AUG-12:30 | 37.00 | 20.85 | 0.819944E+09 | 491.84 | 27-AUG-23:30 | 37.00 | 20.85 |
September | 0.550748E+10 | 3936.80 | 28-SEP-13:30 | 36.10 | 16.03 | 0.786333E+09 | 491.84 | 19-SEP-21:19 | 36.10 | 16.03 |
October | 0.494349E+10 | 3946.58 | 02-OCT-12:40 | 34.00 | 19.29 | 0.756905E+09 | 491.85 | 19-OCT-21:49 | 20.00 | 10.88 |
November | 0.401968E+10 | 3716.97 | 21-NOV-13:40 | 25.00 | 10.74 | 0.679959E+09 | 491.33 | 01-NOV-21:19 | 25.00 | 10.74 |
December | 0.339302E+10 | 3392.75 | 25-DEC-13:30 | 25.50 | 11.81 | 0.671432E+09 | 455.17 | 26-DEC-22:19 | 14.67 | 7.12 |
Annual Sum or Average | 0.543608E+11 | 0.884066E+10 | ||||||||
Minimum of Months | 0.259851E+10 | 2491.68 | 16.00 | 7.74 | 0.591069E+09 | 429.94 | 14.33 | 6.76 | ||
Maximum of Months | 0.577296E+10 | 3946.58 | 40.67 | 20.85 | 0.820573E+09 | 491.86 | 40.67 | 20.85 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.293819E+10 | 1544.21 | 27-JAN-21:10 | 16.17 | 6.63 | 0.900152E+09 | 569.55 | 27-JAN-22:19 | 11.67 | 4.41 |
February | 0.242151E+10 | 1288.98 | 01-FEB-21:00 | 11.00 | 5.83 | 0.770259E+09 | 569.51 | 01-FEB-22:19 | 9.33 | 4.99 |
March | 0.282043E+10 | 1619.35 | 17-MAR-21:00 | 21.60 | 12.64 | 0.880347E+09 | 569.55 | 22-MAR-21:40 | 12.00 | 6.59 |
April | 0.343005E+10 | 2222.83 | 14-APR-20:40 | 29.67 | 13.44 | 0.920248E+09 | 569.56 | 16-APR-23:10 | 18.83 | 12.52 |
May | 0.374746E+10 | 2175.68 | 19-MAY-20:10 | 30.67 | 12.42 | 0.960315E+09 | 569.57 | 10-MAY-23:19 | 30.67 | 12.42 |
June | 0.417705E+10 | 2550.53 | 28-JUN-20:40 | 35.67 | 14.90 | 0.938790E+09 | 569.57 | 09-JUN-23:19 | 35.67 | 14.90 |
July | 0.413458E+10 | 2403.65 | 20-JUL-20:10 | 35.17 | 18.52 | 0.965007E+09 | 569.56 | 01-JUL-00:10 | 35.17 | 18.52 |
August | 0.411570E+10 | 2447.72 | 15-AUG-20:10 | 34.67 | 18.05 | 0.968429E+09 | 569.55 | 04-AUG-22:10 | 34.67 | 18.05 |
September | 0.379683E+10 | 2399.50 | 07-SEP-21:00 | 33.30 | 19.43 | 0.933720E+09 | 569.55 | 21-SEP-22:10 | 20.92 | 16.58 |
October | 0.339218E+10 | 2197.55 | 05-OCT-20:10 | 26.50 | 13.28 | 0.937683E+09 | 569.57 | 19-OCT-21:00 | 20.00 | 11.28 |
November | 0.288773E+10 | 1848.56 | 01-NOV-20:10 | 20.50 | 13.68 | 0.875598E+09 | 569.55 | 02-NOV-22:10 | 19.83 | 16.01 |
December | 0.273433E+10 | 1443.37 | 26-DEC-22:00 | 15.00 | 7.29 | 0.863942E+09 | 569.52 | 26-DEC-22:10 | 14.83 | 7.20 |
Annual Sum or Average | 0.405960E+11 | 0.109145E+11 | ||||||||
Minimum of Months | 0.242151E+10 | 1288.98 | 11.00 | 5.83 | 0.770259E+09 | 569.51 | 9.33 | 4.41 | ||
Maximum of Months | 0.417705E+10 | 2550.53 | 35.67 | 19.43 | 0.968429E+09 | 569.57 | 35.67 | 18.52 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.221534E+10 | 1087.04 | 08-JAN-11:33 | 20.33 | 13.54 | 0.163125E+09 | 104.83 | 27-JAN-22:10 | 11.83 | 4.49 |
February | 0.180984E+10 | 988.46 | 01-FEB-21:00 | 11.00 | 5.83 | 0.141462E+09 | 101.00 | 01-FEB-00:10 | 11.00 | 5.83 |
March | 0.220743E+10 | 1176.39 | 18-MAR-18:10 | 25.13 | 12.09 | 0.163878E+09 | 110.08 | 17-MAR-21:19 | 25.13 | 12.09 |
April | 0.280369E+10 | 1512.28 | 14-APR-20:00 | 31.00 | 13.66 | 0.182269E+09 | 120.45 | 14-APR-21:19 | 28.33 | 13.07 |
May | 0.322654E+10 | 1818.16 | 19-MAY-20:00 | 31.00 | 12.54 | 0.198931E+09 | 120.46 | 10-MAY-23:30 | 31.00 | 12.54 |
June | 0.405634E+10 | 2615.74 | 28-JUN-20:00 | 37.00 | 15.57 | 0.198971E+09 | 120.46 | 09-JUN-23:40 | 37.00 | 15.57 |
July | 0.404284E+10 | 2501.02 | 21-JUL-20:00 | 37.00 | 20.84 | 0.204528E+09 | 120.46 | 07-JUL-22:10 | 37.00 | 20.84 |
August | 0.381745E+10 | 2357.90 | 15-AUG-20:00 | 35.00 | 18.06 | 0.204562E+09 | 120.46 | 30-AUG-21:19 | 31.67 | 17.46 |
September | 0.339383E+10 | 2217.87 | 08-SEP-20:00 | 33.80 | 19.77 | 0.196216E+09 | 120.46 | 19-SEP-21:19 | 27.73 | 15.69 |
October | 0.283228E+10 | 1971.04 | 02-OCT-19:50 | 27.50 | 19.95 | 0.184397E+09 | 120.46 | 06-OCT-22:10 | 26.00 | 14.45 |
November | 0.227366E+10 | 1208.48 | 02-NOV-18:06 | 23.67 | 15.30 | 0.161463E+09 | 112.01 | 02-NOV-21:10 | 20.00 | 15.60 |
December | 0.184824E+10 | 1026.93 | 26-DEC-21:00 | 15.00 | 6.89 | 0.156920E+09 | 102.27 | 26-DEC-22:10 | 14.83 | 7.20 |
Annual Sum or Average | 0.345275E+11 | 0.215672E+10 | ||||||||
Minimum of Months | 0.180984E+10 | 988.46 | 11.00 | 5.83 | 0.141462E+09 | 101.00 | 11.00 | 4.49 | ||
Maximum of Months | 0.405634E+10 | 2615.74 | 37.00 | 20.84 | 0.204562E+09 | 120.46 | 37.00 | 20.84 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119853E+10 | 598.06 | 08-JAN-11:33 | 20.33 | 13.54 | 0.124112E+09 | 78.09 | 27-JAN-22:19 | 11.67 | 4.41 |
February | 0.948884E+09 | 540.79 | 18-FEB-11:33 | 19.33 | 14.12 | 0.107658E+09 | 76.55 | 01-FEB-00:10 | 19.33 | 14.12 |
March | 0.117795E+10 | 638.99 | 18-MAR-17:40 | 26.07 | 12.43 | 0.124462E+09 | 82.30 | 17-MAR-21:40 | 26.07 | 12.43 |
April | 0.151820E+10 | 769.58 | 15-APR-10:33 | 28.00 | 13.04 | 0.138137E+09 | 91.92 | 14-APR-21:40 | 28.00 | 13.04 |
May | 0.171178E+10 | 801.72 | 31-MAY-18:10 | 35.67 | 13.49 | 0.151154E+09 | 92.66 | 18-MAY-21:19 | 35.67 | 13.49 |
June | 0.211860E+10 | 1314.73 | 28-JUN-18:50 | 40.17 | 17.22 | 0.152837E+09 | 92.66 | 09-JUN-23:40 | 40.17 | 17.22 |
July | 0.210823E+10 | 1216.87 | 21-JUL-19:10 | 37.83 | 19.56 | 0.157121E+09 | 92.66 | 07-JUL-22:10 | 37.83 | 19.56 |
August | 0.199097E+10 | 1122.43 | 15-AUG-19:40 | 35.67 | 18.27 | 0.156902E+09 | 92.66 | 27-AUG-23:49 | 30.17 | 17.39 |
September | 0.177583E+10 | 1043.16 | 08-SEP-19:40 | 34.37 | 19.90 | 0.150076E+09 | 92.66 | 19-SEP-21:19 | 27.73 | 15.69 |
October | 0.152033E+10 | 889.18 | 03-OCT-21:00 | 30.00 | 18.69 | 0.140038E+09 | 92.66 | 06-OCT-22:10 | 26.00 | 14.45 |
November | 0.123048E+10 | 652.21 | 02-NOV-18:06 | 23.67 | 15.30 | 0.122605E+09 | 83.73 | 02-NOV-22:10 | 19.83 | 16.01 |
December | 0.959523E+09 | 567.03 | 25-DEC-11:33 | 22.33 | 10.13 | 0.119624E+09 | 76.52 | 26-DEC-22:40 | 14.33 | 6.96 |
Annual Sum or Average | 0.182593E+11 | 0.164472E+10 | ||||||||
Minimum of Months | 0.948884E+09 | 540.79 | 19.33 | 10.13 | 0.107658E+09 | 76.52 | 11.67 | 4.41 | ||
Maximum of Months | 0.211860E+10 | 1314.73 | 40.17 | 19.90 | 0.157121E+09 | 92.66 | 40.17 | 19.56 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.502827E+11 | 37727.31 | 27-JAN-21:00 | 17.00 | 6.99 | 0.594357E+09 | 381.76 | 10-JAN-22:10 | 17.00 | 6.99 |
February | 0.447414E+11 | 37292.37 | 22-FEB-21:00 | 13.00 | 10.72 | 0.534442E+09 | 381.75 | 16-FEB-22:10 | 13.00 | 10.72 |
March | 0.505214E+11 | 38160.02 | 16-MAR-20:00 | 22.20 | 12.56 | 0.595663E+09 | 381.73 | 21-MAR-21:10 | 18.62 | 10.88 |
April | 0.515510E+11 | 39213.00 | 14-APR-20:00 | 31.00 | 13.66 | 0.583875E+09 | 381.80 | 14-APR-21:10 | 28.67 | 13.19 |
May | 0.542517E+11 | 39332.35 | 18-MAY-20:00 | 30.00 | 12.86 | 0.606355E+09 | 381.83 | 09-MAY-21:10 | 30.00 | 12.86 |
June | 0.540926E+11 | 40074.74 | 28-JUN-20:00 | 37.00 | 15.57 | 0.590722E+09 | 381.90 | 23-JUN-21:10 | 37.00 | 15.57 |
July | 0.552316E+11 | 39896.83 | 21-JUL-20:00 | 37.00 | 20.84 | 0.607440E+09 | 381.89 | 07-JUL-21:10 | 37.00 | 20.84 |
August | 0.552110E+11 | 39772.08 | 15-AUG-20:00 | 35.00 | 18.06 | 0.607895E+09 | 382.20 | 09-AUG-21:10 | 35.00 | 18.06 |
September | 0.525381E+11 | 39593.85 | 08-SEP-20:00 | 33.80 | 19.77 | 0.585773E+09 | 381.94 | 19-SEP-21:10 | 28.02 | 15.82 |
October | 0.523148E+11 | 39148.75 | 03-OCT-20:00 | 30.00 | 18.25 | 0.600674E+09 | 381.88 | 06-OCT-21:10 | 26.00 | 13.09 |
November | 0.489335E+11 | 38119.13 | 01-NOV-20:00 | 21.00 | 13.76 | 0.576014E+09 | 381.80 | 01-NOV-21:10 | 18.00 | 13.11 |
December | 0.492362E+11 | 37400.89 | 22-DEC-21:00 | 14.00 | 5.51 | 0.591595E+09 | 381.80 | 12-DEC-22:10 | 14.00 | 5.51 |
Annual Sum or Average | 0.618906E+12 | 0.707480E+10 | ||||||||
Minimum of Months | 0.447414E+11 | 37292.37 | 13.00 | 5.51 | 0.534442E+09 | 381.73 | 13.00 | 5.51 | ||
Maximum of Months | 0.552316E+11 | 40074.74 | 37.00 | 20.84 | 0.607895E+09 | 382.20 | 37.00 | 20.84 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215908E+11 | 13769.61 | 14-JAN-13:30 | 26.50 | 10.97 | 0.106512E+11 | 6462.45 | 30-JAN-22:10 | 12.83 | 5.60 |
February | 0.160721E+11 | 10453.01 | 01-FEB-16:03 | 15.83 | 6.96 | 0.915414E+10 | 6463.27 | 01-FEB-01:10 | 15.83 | 6.96 |
March | 0.182820E+11 | 10784.06 | 16-MAR-15:15 | 28.80 | 13.79 | 0.103274E+11 | 6462.61 | 16-MAR-22:10 | 19.80 | 12.35 |
April | 0.215898E+11 | 12143.92 | 14-APR-21:10 | 28.67 | 13.19 | 0.104923E+11 | 6462.69 | 26-APR-22:10 | 15.83 | 9.46 |
May | 0.223815E+11 | 11692.02 | 09-MAY-21:10 | 28.83 | 12.76 | 0.108580E+11 | 6462.04 | 06-MAY-01:19 | 28.83 | 12.76 |
June | 0.243855E+11 | 13321.30 | 28-JUN-21:10 | 34.67 | 14.46 | 0.106176E+11 | 6462.33 | 05-JUN-04:19 | 34.67 | 14.46 |
July | 0.248981E+11 | 13209.92 | 21-JUL-21:10 | 33.83 | 20.81 | 0.109305E+11 | 6462.12 | 07-JUL-04:19 | 33.83 | 20.81 |
August | 0.254669E+11 | 13104.78 | 15-AUG-21:10 | 32.67 | 17.73 | 0.109739E+11 | 6462.63 | 04-AUG-22:10 | 32.67 | 17.73 |
September | 0.245740E+11 | 13997.98 | 28-SEP-15:03 | 37.52 | 15.49 | 0.106004E+11 | 6462.58 | 21-SEP-22:10 | 37.52 | 15.49 |
October | 0.232909E+11 | 13924.86 | 05-OCT-15:03 | 34.00 | 15.75 | 0.108010E+11 | 6462.70 | 19-OCT-22:10 | 19.83 | 11.29 |
November | 0.203319E+11 | 14228.08 | 01-NOV-15:03 | 28.83 | 16.12 | 0.102550E+11 | 6462.58 | 01-NOV-22:10 | 17.67 | 13.01 |
December | 0.194868E+11 | 13279.69 | 25-DEC-13:00 | 25.00 | 11.61 | 0.103011E+11 | 6461.96 | 26-DEC-00:20 | 9.67 | 3.36 |
Annual Sum or Average | 0.262350E+12 | 0.125963E+12 | ||||||||
Minimum of Months | 0.160721E+11 | 10453.01 | 15.83 | 6.96 | 0.915414E+10 | 6461.96 | 9.67 | 3.36 | ||
Maximum of Months | 0.254669E+11 | 14228.08 | 37.52 | 20.81 | 0.109739E+11 | 6463.27 | 37.52 | 20.81 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.652219E+11 | 35047.05 | 31-JAN-19:06 | 23.00 | 8.93 | 0.318096E+11 | 19185.83 | 27-JAN-22:19 | 23.00 | 8.93 |
February | 0.536329E+11 | 30935.06 | 01-FEB-22:10 | 9.67 | 5.16 | 0.277569E+11 | 19189.49 | 01-FEB-01:10 | 9.67 | 5.16 |
March | 0.617494E+11 | 35809.78 | 17-MAR-21:10 | 21.42 | 12.50 | 0.312520E+11 | 19186.08 | 22-MAR-21:40 | 12.00 | 6.59 |
April | 0.716991E+11 | 42474.73 | 14-APR-21:10 | 28.67 | 13.19 | 0.312533E+11 | 19186.17 | 26-APR-22:10 | 15.83 | 9.46 |
May | 0.774530E+11 | 42018.62 | 09-MAY-21:10 | 28.83 | 12.76 | 0.323854E+11 | 19185.69 | 26-MAY-03:09 | 21.00 | 13.54 |
June | 0.836774E+11 | 47581.75 | 28-JUN-21:10 | 34.67 | 14.46 | 0.315860E+11 | 19186.06 | 05-JUN-04:19 | 34.67 | 14.46 |
July | 0.853619E+11 | 46881.30 | 21-JUL-20:10 | 36.50 | 20.90 | 0.325079E+11 | 19185.49 | 07-JUL-04:19 | 36.50 | 20.90 |
August | 0.851628E+11 | 46376.66 | 15-AUG-20:10 | 34.67 | 18.05 | 0.326620E+11 | 19186.04 | 04-AUG-22:10 | 34.67 | 18.05 |
September | 0.806828E+11 | 46264.11 | 07-SEP-21:10 | 32.75 | 19.42 | 0.315328E+11 | 19185.98 | 21-SEP-22:10 | 20.92 | 16.58 |
October | 0.738353E+11 | 44172.60 | 03-OCT-21:10 | 29.50 | 18.57 | 0.322777E+11 | 19186.33 | 19-OCT-22:10 | 19.83 | 11.29 |
November | 0.636837E+11 | 38443.39 | 01-NOV-20:10 | 20.50 | 13.68 | 0.307898E+11 | 19185.96 | 01-NOV-22:10 | 17.67 | 13.01 |
December | 0.608957E+11 | 33991.72 | 26-DEC-22:10 | 14.83 | 7.20 | 0.310581E+11 | 19185.16 | 26-DEC-00:20 | 14.83 | 7.20 |
Annual Sum or Average | 0.863056E+12 | 0.376872E+12 | ||||||||
Minimum of Months | 0.536329E+11 | 30935.06 | 9.67 | 5.16 | 0.277569E+11 | 19185.16 | 9.67 | 5.16 | ||
Maximum of Months | 0.853619E+11 | 47581.75 | 36.50 | 20.90 | 0.326620E+11 | 19189.49 | 36.50 | 20.90 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.927742E+09 | 3639.41 | 31-JAN-16:01 | 29.00 | 10.73 | 98255232.52 | 56.69 | 18-JAN-22:10 | 29.00 | 10.73 |
February | 0.324077E+09 | 3347.73 | 28-FEB-16:01 | 19.00 | 8.42 | 87571843.68 | 56.69 | 01-FEB-01:10 | 19.00 | 8.42 |
March | 0.751158E+09 | 3618.40 | 16-MAR-15:01 | 28.80 | 13.75 | 97960930.04 | 56.69 | 22-MAR-21:30 | 12.45 | 6.77 |
April | 0.227008E+10 | 3680.74 | 14-APR-18:01 | 33.50 | 13.96 | 95713523.15 | 56.70 | 24-APR-23:19 | 26.67 | 12.88 |
May | 0.271877E+10 | 3658.00 | 03-MAY-15:01 | 33.17 | 12.99 | 99129666.61 | 56.70 | 10-MAY-23:30 | 25.50 | 14.96 |
June | 0.348394E+10 | 3696.87 | 27-JUN-18:02 | 39.83 | 15.83 | 96141501.97 | 56.70 | 29-JUN-21:30 | 34.50 | 16.25 |
July | 0.318559E+10 | 3676.15 | 05-JUL-18:02 | 37.83 | 16.08 | 99132032.75 | 56.70 | 20-JUL-23:19 | 32.67 | 18.65 |
August | 0.312533E+10 | 3681.43 | 26-AUG-15:02 | 41.00 | 16.32 | 99255227.45 | 56.70 | 11-AUG-21:00 | 41.00 | 16.32 |
September | 0.273387E+10 | 3680.18 | 28-SEP-15:02 | 37.52 | 15.49 | 95917494.22 | 56.70 | 08-SEP-22:10 | 37.52 | 15.49 |
October | 0.184375E+10 | 3674.36 | 15-OCT-15:01 | 31.00 | 12.59 | 98741103.00 | 56.70 | 03-OCT-00:40 | 31.00 | 12.59 |
November | 0.936842E+09 | 3664.81 | 20-NOV-16:01 | 26.83 | 12.13 | 95054938.80 | 56.69 | 01-NOV-21:00 | 26.83 | 12.13 |
December | 0.469299E+09 | 3610.89 | 25-DEC-16:01 | 25.67 | 11.87 | 97467265.65 | 56.69 | 26-DEC-22:19 | 14.67 | 7.12 |
Annual Sum or Average | 0.227704E+11 | 0.116034E+10 | ||||||||
Minimum of Months | 0.324077E+09 | 3347.73 | 19.00 | 8.42 | 87571843.68 | 56.69 | 12.45 | 6.77 | ||
Maximum of Months | 0.348394E+10 | 3696.87 | 41.00 | 16.32 | 99255227.45 | 56.70 | 41.00 | 18.65 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.299023E+09 | 3557.33 | 31-JAN-16:01 | 29.00 | 10.73 | 98923983.32 | 65.11 | 31-JAN-22:10 | 14.48 | 5.13 |
February | 0.100307E+09 | 3268.37 | 28-FEB-16:01 | 19.00 | 8.42 | 87036267.57 | 56.69 | 21-FEB-22:10 | 19.00 | 8.42 |
March | 0.397231E+09 | 3561.89 | 16-MAR-15:01 | 28.80 | 13.75 | 0.100412E+09 | 72.26 | 17-MAR-21:10 | 21.42 | 12.50 |
April | 0.191134E+10 | 3705.07 | 26-APR-08:41 | 25.67 | 12.21 | 98396481.79 | 76.73 | 20-APR-18:10 | 25.67 | 12.21 |
May | 0.257486E+10 | 4003.06 | 08-MAY-08:61 | 27.17 | 12.22 | 0.100700E+09 | 57.01 | 13-MAY-21:00 | 22.00 | 7.76 |
June | 0.346469E+10 | 4033.51 | 14-JUN-08:61 | 27.67 | 11.24 | 97611382.39 | 56.70 | 30-JUN-21:40 | 33.47 | 15.37 |
July | 0.314942E+10 | 4144.52 | 01-JUL-08:61 | 27.50 | 10.46 | 99742450.98 | 56.70 | 20-JUL-23:19 | 32.67 | 18.65 |
August | 0.292337E+10 | 3840.76 | 24-AUG-08:21 | 27.50 | 13.17 | 0.100610E+09 | 78.50 | 04-AUG-21:10 | 27.50 | 13.17 |
September | 0.239377E+10 | 3621.88 | 28-SEP-15:02 | 37.52 | 15.49 | 97661774.93 | 75.68 | 21-SEP-21:10 | 37.52 | 15.49 |
October | 0.123799E+10 | 3607.25 | 06-OCT-15:02 | 35.00 | 14.90 | 0.101671E+09 | 73.85 | 17-OCT-21:10 | 20.67 | 7.69 |
November | 0.381918E+09 | 3582.56 | 20-NOV-16:01 | 26.83 | 12.13 | 96308408.78 | 71.16 | 01-NOV-21:30 | 26.83 | 12.13 |
December | 0.114578E+09 | 3519.09 | 25-DEC-16:01 | 25.67 | 11.87 | 96302796.96 | 56.73 | 26-DEC-21:40 | 15.00 | 7.15 |
Annual Sum or Average | 0.189485E+11 | 0.117538E+10 | ||||||||
Minimum of Months | 0.100307E+09 | 3268.37 | 19.00 | 8.42 | 87036267.57 | 56.69 | 14.48 | 5.13 | ||
Maximum of Months | 0.346469E+10 | 4144.52 | 37.52 | 15.49 | 0.101671E+09 | 78.50 | 37.52 | 18.65 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.558278E+09 | 630.65 | 14-JAN-13:50 | 26.83 | 10.99 | 0.00 | 0.00 | 01-JAN-00:10 | 26.83 | 10.99 |
February | 0.186993E+09 | 475.30 | 01-FEB-15:30 | 15.50 | 6.96 | 0.00 | 0.00 | 01-FEB-00:10 | 15.50 | 6.96 |
March | 0.226214E+09 | 447.12 | 18-MAR-14:10 | 26.28 | 11.98 | 0.00 | 0.00 | 01-MAR-00:10 | 26.28 | 11.98 |
April | 0.528259E+09 | 466.63 | 14-APR-13:40 | 34.00 | 14.40 | 0.00 | 0.00 | 01-APR-00:10 | 34.00 | 14.40 |
May | 0.534876E+09 | 376.91 | 09-MAY-17:20 | 34.67 | 14.40 | 0.00 | 0.00 | 01-MAY-00:10 | 34.67 | 14.40 |
June | 0.699746E+09 | 473.91 | 28-JUN-17:15 | 41.67 | 18.88 | 0.00 | 0.00 | 01-JUN-00:10 | 41.67 | 18.88 |
July | 0.707038E+09 | 448.02 | 21-JUL-19:10 | 37.83 | 19.56 | 0.00 | 0.00 | 01-JUL-00:10 | 37.83 | 19.56 |
August | 0.748407E+09 | 536.82 | 27-AUG-14:00 | 40.00 | 18.27 | 0.00 | 0.00 | 01-AUG-00:10 | 40.00 | 18.27 |
September | 0.744934E+09 | 612.10 | 28-SEP-13:40 | 36.47 | 16.05 | 0.00 | 0.00 | 01-SEP-00:10 | 36.47 | 16.05 |
October | 0.644542E+09 | 632.37 | 18-OCT-13:50 | 30.83 | 12.20 | 0.00 | 0.00 | 01-OCT-00:10 | 30.83 | 12.20 |
November | 0.475255E+09 | 659.01 | 20-NOV-14:30 | 27.00 | 11.68 | 0.00 | 0.00 | 01-NOV-00:10 | 27.00 | 11.68 |
December | 0.393954E+09 | 624.13 | 25-DEC-13:40 | 25.67 | 11.87 | 0.00 | 0.00 | 01-DEC-00:10 | 25.67 | 11.87 |
Annual Sum or Average | 0.644850E+10 | 0.00 | ||||||||
Minimum of Months | 0.186993E+09 | 376.91 | 15.50 | 6.96 | 0.00 | 0.00 | 15.50 | 6.96 | ||
Maximum of Months | 0.748407E+09 | 659.01 | 41.67 | 19.56 | 0.00 | 0.00 | 41.67 | 19.56 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222827E+09 | 1195.62 | 27-JAN-16:01 | 26.83 | 9.65 | 97857042.35 | 67.03 | 27-JAN-22:10 | 11.83 | 4.49 |
February | 0.178037E+09 | 1065.68 | 09-FEB-16:01 | 20.83 | 9.61 | 87376247.27 | 61.74 | 09-FEB-22:40 | 14.67 | 8.47 |
March | 0.308421E+09 | 1232.00 | 15-MAR-18:01 | 26.55 | 12.82 | 99586367.36 | 70.92 | 23-MAR-21:10 | 14.80 | 7.70 |
April | 0.675005E+09 | 1237.46 | 12-APR-15:01 | 33.00 | 14.97 | 97146270.34 | 71.48 | 26-APR-21:49 | 16.17 | 9.55 |
May | 0.896567E+09 | 1327.45 | 20-MAY-08:61 | 26.50 | 11.05 | 0.100177E+09 | 56.69 | 10-MAY-23:00 | 26.50 | 11.05 |
June | 0.116751E+10 | 1357.06 | 11-JUN-08:61 | 26.33 | 12.62 | 97065669.00 | 56.70 | 15-JUN-21:19 | 33.67 | 14.96 |
July | 0.114148E+10 | 1368.91 | 01-JUL-08:61 | 27.50 | 10.46 | 99504991.36 | 56.69 | 25-JUL-22:19 | 28.00 | 17.83 |
August | 0.104282E+10 | 1255.80 | 24-AUG-08:21 | 27.50 | 13.17 | 0.100203E+09 | 76.27 | 04-AUG-21:10 | 27.50 | 13.17 |
September | 0.903371E+09 | 1247.39 | 29-SEP-08:21 | 27.75 | 14.34 | 97205977.77 | 74.22 | 21-SEP-21:10 | 27.75 | 14.34 |
October | 0.535602E+09 | 1236.75 | 06-OCT-18:01 | 31.67 | 14.16 | 0.100526E+09 | 70.66 | 11-OCT-21:19 | 15.00 | 6.77 |
November | 0.257320E+09 | 1207.47 | 20-NOV-16:01 | 26.83 | 12.13 | 95418419.25 | 69.93 | 02-NOV-21:49 | 26.83 | 12.13 |
December | 0.130507E+09 | 1167.91 | 25-DEC-16:01 | 25.67 | 11.87 | 96329448.14 | 58.31 | 26-DEC-21:40 | 15.00 | 7.15 |
Annual Sum or Average | 0.745947E+10 | 0.116840E+10 | ||||||||
Minimum of Months | 0.130507E+09 | 1065.68 | 20.83 | 9.61 | 87376247.27 | 56.69 | 11.83 | 4.49 | ||
Maximum of Months | 0.116751E+10 | 1368.91 | 33.00 | 14.97 | 0.100526E+09 | 76.27 | 33.67 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.883829E+09 | 3194.21 | 31-JAN-16:01 | 29.00 | 10.73 | 98560492.73 | 56.69 | 19-JAN-22:30 | 29.00 | 10.73 |
February | 0.376077E+09 | 2973.90 | 09-FEB-16:01 | 20.83 | 9.61 | 88055631.89 | 56.69 | 21-FEB-22:49 | 14.00 | 12.80 |
March | 0.787057E+09 | 3193.97 | 16-MAR-15:01 | 28.80 | 13.75 | 98419475.86 | 56.69 | 22-MAR-21:30 | 12.45 | 6.77 |
April | 0.230838E+10 | 3237.75 | 13-APR-15:01 | 34.00 | 14.95 | 95939308.32 | 56.70 | 25-APR-00:00 | 25.00 | 12.85 |
May | 0.281301E+10 | 3294.33 | 17-MAY-08:61 | 27.17 | 13.67 | 99207230.96 | 56.70 | 10-MAY-23:49 | 27.17 | 13.67 |
June | 0.356713E+10 | 3290.67 | 14-JUN-08:61 | 27.67 | 11.24 | 96065002.19 | 56.70 | 27-JUN-21:10 | 35.50 | 14.88 |
July | 0.339749E+10 | 3298.57 | 01-JUL-08:61 | 27.50 | 10.46 | 99141663.18 | 56.70 | 07-JUL-21:00 | 32.00 | 16.73 |
August | 0.330208E+10 | 3258.50 | 27-AUG-08:61 | 29.67 | 14.57 | 99249445.43 | 56.70 | 17-AUG-22:00 | 29.67 | 14.57 |
September | 0.282874E+10 | 3237.92 | 28-SEP-15:02 | 37.52 | 15.49 | 95953849.80 | 56.70 | 07-SEP-22:40 | 37.52 | 15.49 |
October | 0.191355E+10 | 3227.79 | 06-OCT-15:02 | 35.00 | 14.90 | 98974934.59 | 56.70 | 02-OCT-21:10 | 35.00 | 14.90 |
November | 0.871968E+09 | 3200.61 | 20-NOV-16:01 | 26.83 | 12.13 | 95281882.81 | 56.69 | 01-NOV-21:30 | 26.83 | 12.13 |
December | 0.475209E+09 | 3161.64 | 25-DEC-16:01 | 25.67 | 11.87 | 97852174.14 | 56.69 | 26-DEC-22:10 | 14.83 | 7.20 |
Annual Sum or Average | 0.235245E+11 | 0.116270E+10 | ||||||||
Minimum of Months | 0.376077E+09 | 2973.90 | 20.83 | 9.61 | 88055631.89 | 56.69 | 12.45 | 6.77 | ||
Maximum of Months | 0.356713E+10 | 3298.57 | 37.52 | 15.49 | 99249445.43 | 56.70 | 37.52 | 16.73 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292023E+09 | 3119.26 | 31-JAN-16:01 | 29.00 | 10.73 | 98476980.35 | 63.90 | 31-JAN-22:10 | 14.48 | 5.13 |
February | 0.148398E+09 | 2802.46 | 09-FEB-16:01 | 20.83 | 9.61 | 87198491.62 | 57.37 | 09-FEB-22:30 | 15.00 | 8.57 |
March | 0.450340E+09 | 3147.10 | 16-MAR-15:01 | 28.80 | 13.75 | 0.100220E+09 | 70.52 | 16-MAR-21:10 | 20.92 | 12.27 |
April | 0.190436E+10 | 3744.95 | 14-APR-08:41 | 26.50 | 12.19 | 98873129.50 | 73.09 | 19-APR-21:30 | 20.50 | 9.19 |
May | 0.259240E+10 | 3974.01 | 21-MAY-08:61 | 25.33 | 11.05 | 0.102038E+09 | 56.70 | 10-MAY-23:49 | 25.33 | 11.05 |
June | 0.352317E+10 | 3772.57 | 14-JUN-08:61 | 27.67 | 11.24 | 98009485.10 | 58.56 | 19-JUN-05:00 | 23.00 | 10.71 |
July | 0.334918E+10 | 3781.11 | 01-JUL-08:61 | 27.50 | 10.46 | 99980087.80 | 56.98 | 05-JUL-05:00 | 23.00 | 11.31 |
August | 0.308249E+10 | 3762.07 | 24-AUG-08:21 | 27.50 | 13.17 | 0.100901E+09 | 78.20 | 04-AUG-21:10 | 27.50 | 13.17 |
September | 0.246250E+10 | 3420.92 | 15-SEP-08:51 | 25.00 | 16.27 | 98081983.24 | 75.60 | 21-SEP-21:10 | 22.02 | 16.74 |
October | 0.128564E+10 | 3562.99 | 17-OCT-08:51 | 24.00 | 9.54 | 0.101906E+09 | 72.61 | 10-OCT-21:00 | 24.00 | 9.54 |
November | 0.348681E+09 | 3289.83 | 10-NOV-09:51 | 23.00 | 9.98 | 95833207.26 | 69.46 | 02-NOV-21:30 | 23.00 | 9.98 |
December | 0.126050E+09 | 3085.53 | 25-DEC-16:01 | 25.67 | 11.87 | 96135561.98 | 56.69 | 13-DEC-00:20 | 25.67 | 11.87 |
Annual Sum or Average | 0.195652E+11 | 0.117765E+10 | ||||||||
Minimum of Months | 0.126050E+09 | 2802.46 | 20.83 | 9.54 | 87198491.62 | 56.69 | 14.48 | 5.13 | ||
Maximum of Months | 0.352317E+10 | 3974.01 | 29.00 | 16.27 | 0.102038E+09 | 78.20 | 27.50 | 16.74 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.346471E+10 | 1644.18 | 29-JAN-11:33 | 21.33 | 8.67 | 0.134625E+10 | 847.88 | 31-JAN-22:40 | 13.83 | 4.56 |
February | 0.276955E+10 | 1522.85 | 01-FEB-11:35 | 13.67 | 6.91 | 0.114318E+10 | 839.00 | 01-FEB-00:10 | 13.67 | 6.91 |
March | 0.337362E+10 | 1722.49 | 18-MAR-17:40 | 26.07 | 12.43 | 0.132469E+10 | 850.94 | 20-MAR-22:10 | 19.03 | 10.57 |
April | 0.408547E+10 | 2050.82 | 15-APR-10:33 | 28.00 | 13.04 | 0.146125E+10 | 951.84 | 14-APR-21:40 | 28.00 | 13.04 |
May | 0.451061E+10 | 2085.28 | 18-MAY-18:10 | 34.67 | 14.15 | 0.157427E+10 | 951.87 | 10-MAY-23:40 | 34.67 | 14.15 |
June | 0.532050E+10 | 3391.19 | 28-JUN-18:25 | 40.50 | 17.53 | 0.156959E+10 | 951.87 | 09-JUN-23:49 | 40.50 | 17.53 |
July | 0.521561E+10 | 3017.71 | 20-JUL-18:30 | 38.00 | 19.12 | 0.161319E+10 | 951.86 | 07-JUL-22:10 | 38.00 | 19.12 |
August | 0.512480E+10 | 2903.19 | 15-AUG-18:15 | 37.67 | 18.63 | 0.161419E+10 | 951.85 | 27-AUG-23:49 | 30.17 | 17.39 |
September | 0.470222E+10 | 2772.02 | 08-SEP-18:15 | 35.90 | 20.02 | 0.155373E+10 | 951.85 | 20-SEP-21:19 | 27.20 | 17.73 |
October | 0.421414E+10 | 2478.28 | 05-OCT-18:03 | 31.50 | 15.38 | 0.150057E+10 | 951.86 | 06-OCT-23:19 | 25.67 | 15.00 |
November | 0.345124E+10 | 1757.72 | 01-NOV-18:10 | 23.67 | 14.38 | 0.132260E+10 | 877.18 | 02-NOV-22:10 | 19.83 | 16.01 |
December | 0.307465E+10 | 1566.81 | 25-DEC-11:33 | 22.33 | 10.13 | 0.127308E+10 | 823.00 | 26-DEC-22:40 | 14.33 | 6.96 |
Annual Sum or Average | 0.493071E+11 | 0.172966E+11 | ||||||||
Minimum of Months | 0.276955E+10 | 1522.85 | 13.67 | 6.91 | 0.114318E+10 | 823.00 | 13.67 | 4.56 | ||
Maximum of Months | 0.532050E+10 | 3391.19 | 40.50 | 20.02 | 0.161419E+10 | 951.87 | 40.50 | 19.12 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.849000E+09 | 3862.11 | 31-JAN-16:01 | 29.00 | 10.73 | 98044321.46 | 56.70 | 07-JAN-01:00 | 29.00 | 10.73 |
February | 0.292818E+09 | 3553.33 | 28-FEB-16:01 | 19.00 | 8.42 | 87321604.03 | 56.69 | 16-FEB-22:40 | 19.00 | 8.42 |
March | 0.724602E+09 | 3844.30 | 16-MAR-15:01 | 28.80 | 13.75 | 97780221.67 | 56.69 | 24-MAR-21:10 | 12.52 | 4.62 |
April | 0.230180E+10 | 3916.12 | 14-APR-18:01 | 33.50 | 13.96 | 95628566.39 | 56.70 | 14-APR-23:49 | 23.50 | 11.85 |
May | 0.277802E+10 | 3893.49 | 03-MAY-15:01 | 33.17 | 12.99 | 99092126.26 | 56.70 | 10-MAY-23:10 | 25.83 | 15.07 |
June | 0.366558E+10 | 3933.48 | 27-JUN-18:02 | 39.83 | 15.83 | 96179628.11 | 56.70 | 29-JUN-21:19 | 34.67 | 16.35 |
July | 0.333425E+10 | 3907.74 | 05-JUL-18:02 | 37.83 | 16.08 | 99130061.52 | 56.70 | 11-JUL-21:40 | 31.00 | 19.81 |
August | 0.325431E+10 | 3924.49 | 26-AUG-15:02 | 41.00 | 16.32 | 99257848.48 | 56.70 | 17-AUG-21:30 | 41.00 | 16.32 |
September | 0.277631E+10 | 3875.19 | 18-SEP-15:02 | 36.00 | 16.76 | 95891616.22 | 56.70 | 07-SEP-21:00 | 36.00 | 16.76 |
October | 0.176201E+10 | 3903.46 | 15-OCT-15:01 | 31.00 | 12.59 | 98586808.07 | 56.70 | 06-OCT-22:10 | 31.00 | 12.59 |
November | 0.848799E+09 | 3897.32 | 20-NOV-16:01 | 26.83 | 12.13 | 94820676.48 | 56.69 | 10-NOV-03:00 | 26.83 | 12.13 |
December | 0.426155E+09 | 3834.17 | 25-DEC-16:01 | 25.67 | 11.87 | 97167276.75 | 56.69 | 26-DEC-22:49 | 14.17 | 6.88 |
Annual Sum or Average | 0.230137E+11 | 0.115890E+10 | ||||||||
Minimum of Months | 0.292818E+09 | 3553.33 | 19.00 | 8.42 | 87321604.03 | 56.69 | 12.52 | 4.62 | ||
Maximum of Months | 0.366558E+10 | 3933.48 | 41.00 | 16.76 | 99257848.48 | 56.70 | 41.00 | 19.81 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249911E+09 | 3763.24 | 31-JAN-16:01 | 29.00 | 10.73 | 98429955.53 | 63.02 | 31-JAN-22:10 | 14.48 | 5.13 |
February | 83110141.60 | 3458.42 | 28-FEB-16:01 | 19.00 | 8.42 | 86679966.10 | 56.69 | 21-FEB-22:19 | 19.00 | 8.42 |
March | 0.370976E+09 | 3779.23 | 16-MAR-15:01 | 28.80 | 13.75 | 0.100338E+09 | 72.52 | 17-MAR-21:19 | 21.23 | 12.36 |
April | 0.195820E+10 | 3879.20 | 26-APR-08:41 | 25.67 | 12.21 | 98204295.56 | 79.27 | 20-APR-18:10 | 25.67 | 12.21 |
May | 0.265952E+10 | 4189.12 | 08-MAY-08:61 | 27.17 | 12.22 | 0.100344E+09 | 56.70 | 10-MAY-23:10 | 25.83 | 15.07 |
June | 0.366538E+10 | 4217.64 | 14-JUN-08:61 | 27.67 | 11.24 | 97488896.89 | 56.70 | 29-JUN-21:30 | 34.50 | 16.25 |
July | 0.330538E+10 | 4330.02 | 01-JUL-08:61 | 27.50 | 10.46 | 99653592.42 | 56.70 | 20-JUL-22:40 | 33.00 | 18.53 |
August | 0.306090E+10 | 4004.16 | 24-AUG-08:21 | 27.50 | 13.17 | 0.100481E+09 | 78.30 | 04-AUG-21:10 | 27.50 | 13.17 |
September | 0.244913E+10 | 3848.46 | 28-SEP-15:02 | 37.52 | 15.49 | 97399993.71 | 74.73 | 21-SEP-21:10 | 37.52 | 15.49 |
October | 0.117882E+10 | 3825.17 | 06-OCT-15:02 | 35.00 | 14.90 | 0.101099E+09 | 72.69 | 17-OCT-21:10 | 20.67 | 7.69 |
November | 0.321741E+09 | 3797.76 | 20-NOV-16:01 | 26.83 | 12.13 | 95737018.78 | 70.87 | 01-NOV-21:30 | 26.83 | 12.13 |
December | 95920297.89 | 3722.45 | 25-DEC-16:01 | 25.67 | 11.87 | 95765147.89 | 56.69 | 26-DEC-22:10 | 14.83 | 7.20 |
Annual Sum or Average | 0.193990E+11 | 0.117162E+10 | ||||||||
Minimum of Months | 83110141.60 | 3458.42 | 19.00 | 8.42 | 86679966.10 | 56.69 | 14.48 | 5.13 | ||
Maximum of Months | 0.366538E+10 | 4330.02 | 37.52 | 15.49 | 0.101099E+09 | 79.27 | 37.52 | 18.53 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118269E+10 | 1975.29 | 14-JAN-16:01 | 26.67 | 10.69 | 98816161.51 | 56.69 | 04-JAN-22:10 | 26.67 | 10.69 |
February | 0.510331E+09 | 1829.62 | 09-FEB-16:01 | 20.83 | 9.61 | 88407931.33 | 56.69 | 21-FEB-22:10 | 14.00 | 12.80 |
March | 0.650112E+09 | 1952.31 | 16-MAR-15:01 | 28.80 | 13.75 | 98378228.87 | 56.69 | 16-MAR-21:00 | 20.00 | 12.36 |
April | 0.131407E+10 | 1963.01 | 13-APR-15:01 | 34.00 | 14.95 | 95667035.36 | 56.69 | 25-APR-00:30 | 25.50 | 13.09 |
May | 0.139758E+10 | 1940.98 | 03-MAY-15:01 | 33.17 | 12.99 | 99083752.74 | 56.70 | 10-MAY-23:19 | 25.67 | 15.01 |
June | 0.177489E+10 | 1943.05 | 27-JUN-15:02 | 41.00 | 15.93 | 96030913.68 | 56.70 | 30-JUN-21:30 | 33.85 | 15.58 |
July | 0.178704E+10 | 1941.14 | 01-JUL-08:61 | 27.50 | 10.46 | 99122641.87 | 56.70 | 20-JUL-23:40 | 32.33 | 18.59 |
August | 0.184190E+10 | 1961.25 | 26-AUG-15:02 | 41.00 | 16.32 | 99217568.01 | 56.70 | 07-AUG-21:30 | 41.00 | 16.32 |
September | 0.176737E+10 | 1960.25 | 18-SEP-15:02 | 36.00 | 16.76 | 95952550.60 | 56.70 | 05-SEP-21:40 | 36.00 | 16.76 |
October | 0.144588E+10 | 1982.41 | 18-OCT-15:01 | 30.00 | 11.77 | 98899784.99 | 56.70 | 03-OCT-22:10 | 30.00 | 11.77 |
November | 0.103484E+10 | 1981.74 | 20-NOV-16:01 | 26.83 | 12.13 | 95506587.94 | 56.69 | 10-NOV-22:40 | 26.83 | 12.13 |
December | 0.873044E+09 | 1964.25 | 25-DEC-16:01 | 25.67 | 11.87 | 98515068.96 | 56.69 | 26-DEC-22:00 | 14.00 | 6.79 |
Annual Sum or Average | 0.155798E+11 | 0.116360E+10 | ||||||||
Minimum of Months | 0.510331E+09 | 1829.62 | 20.83 | 9.61 | 88407931.33 | 56.69 | 14.00 | 6.79 | ||
Maximum of Months | 0.184190E+10 | 1982.41 | 41.00 | 16.76 | 99217568.01 | 56.70 | 41.00 | 18.59 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.343599E+11 | 18854.98 | 06-JAN-22:10 | 17.67 | 9.28 | 0.191034E+11 | 11348.39 | 30-JAN-22:10 | 12.83 | 5.60 |
February | 0.302786E+11 | 18402.59 | 21-FEB-23:00 | 14.00 | 12.80 | 0.172283E+11 | 11349.65 | 01-FEB-00:00 | 14.00 | 12.80 |
March | 0.355163E+11 | 20556.38 | 17-MAR-21:53 | 20.50 | 11.82 | 0.192268E+11 | 11348.77 | 16-MAR-22:10 | 20.50 | 11.82 |
April | 0.401424E+11 | 22797.28 | 14-APR-21:10 | 28.67 | 13.19 | 0.186921E+11 | 11348.95 | 26-APR-22:10 | 15.83 | 9.46 |
May | 0.439962E+11 | 23078.06 | 09-MAY-21:10 | 28.83 | 12.76 | 0.193431E+11 | 11354.38 | 26-MAY-21:19 | 25.00 | 9.45 |
June | 0.464519E+11 | 24852.60 | 28-JUN-21:20 | 34.33 | 14.34 | 0.187605E+11 | 11379.38 | 09-JUN-21:19 | 34.33 | 14.34 |
July | 0.471299E+11 | 24474.13 | 21-JUL-21:20 | 33.67 | 20.69 | 0.193091E+11 | 11373.52 | 07-JUL-21:19 | 33.67 | 20.69 |
August | 0.463093E+11 | 23969.11 | 15-AUG-21:10 | 32.67 | 17.73 | 0.193891E+11 | 11357.47 | 10-AUG-21:19 | 32.67 | 17.73 |
September | 0.432711E+11 | 23766.85 | 07-SEP-21:10 | 32.75 | 19.42 | 0.187050E+11 | 11363.54 | 19-SEP-21:19 | 27.73 | 15.69 |
October | 0.391404E+11 | 22885.91 | 03-OCT-21:10 | 29.50 | 18.57 | 0.192419E+11 | 11348.93 | 19-OCT-22:10 | 19.83 | 11.29 |
November | 0.339239E+11 | 20407.82 | 02-NOV-21:53 | 20.00 | 16.05 | 0.185113E+11 | 11348.73 | 01-NOV-22:10 | 20.00 | 16.05 |
December | 0.324035E+11 | 18407.67 | 26-DEC-22:30 | 14.50 | 7.04 | 0.189982E+11 | 11348.15 | 19-DEC-04:19 | 14.50 | 7.04 |
Annual Sum or Average | 0.472923E+12 | 0.226509E+12 | ||||||||
Minimum of Months | 0.302786E+11 | 18402.59 | 14.00 | 7.04 | 0.172283E+11 | 11348.15 | 12.83 | 5.60 | ||
Maximum of Months | 0.471299E+11 | 24852.60 | 34.33 | 20.69 | 0.193891E+11 | 11379.38 | 34.33 | 20.69 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.377371E+11 | 20588.81 | 06-JAN-22:10 | 17.67 | 9.28 | 0.192065E+11 | 11348.40 | 30-JAN-22:10 | 12.83 | 5.60 |
February | 0.335524E+11 | 20162.73 | 21-FEB-23:00 | 14.00 | 12.80 | 0.173435E+11 | 11349.92 | 01-FEB-00:00 | 14.00 | 12.80 |
March | 0.390842E+11 | 22052.06 | 17-MAR-21:10 | 21.42 | 12.50 | 0.193172E+11 | 11348.78 | 16-MAR-22:10 | 21.42 | 12.50 |
April | 0.430988E+11 | 24004.85 | 14-APR-21:10 | 28.67 | 13.19 | 0.187096E+11 | 11348.95 | 26-APR-22:10 | 15.83 | 9.46 |
May | 0.468910E+11 | 24270.79 | 09-MAY-21:20 | 28.67 | 12.70 | 0.193488E+11 | 11370.80 | 26-MAY-21:19 | 25.00 | 9.45 |
June | 0.491554E+11 | 26035.81 | 28-JUN-21:20 | 34.33 | 14.34 | 0.187613E+11 | 11385.42 | 09-JUN-21:19 | 34.33 | 14.34 |
July | 0.498875E+11 | 25653.76 | 21-JUL-21:20 | 33.67 | 20.69 | 0.193100E+11 | 11378.33 | 05-JUL-21:19 | 33.67 | 20.69 |
August | 0.490676E+11 | 25150.23 | 10-AUG-21:20 | 32.67 | 17.86 | 0.193909E+11 | 11362.14 | 10-AUG-21:19 | 32.67 | 17.86 |
September | 0.459225E+11 | 24913.60 | 07-SEP-21:10 | 32.75 | 19.42 | 0.187091E+11 | 11370.73 | 19-SEP-21:19 | 27.73 | 15.69 |
October | 0.421936E+11 | 24051.61 | 03-OCT-21:10 | 29.50 | 18.57 | 0.192817E+11 | 11348.93 | 19-OCT-22:10 | 19.83 | 11.29 |
November | 0.371773E+11 | 21814.74 | 02-NOV-21:53 | 20.00 | 16.05 | 0.185991E+11 | 11348.74 | 01-NOV-22:10 | 20.00 | 16.05 |
December | 0.358491E+11 | 20036.07 | 26-DEC-22:10 | 14.83 | 7.20 | 0.191455E+11 | 11348.20 | 19-DEC-04:19 | 14.83 | 7.20 |
Annual Sum or Average | 0.509616E+12 | 0.227123E+12 | ||||||||
Minimum of Months | 0.335524E+11 | 20036.07 | 14.00 | 7.20 | 0.173435E+11 | 11348.20 | 12.83 | 5.60 | ||
Maximum of Months | 0.498875E+11 | 26035.81 | 34.33 | 20.69 | 0.193909E+11 | 11385.42 | 34.33 | 20.69 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.498125E+11 | 26831.10 | 29-JAN-11:50 | 21.67 | 8.74 | 0.188199E+11 | 11319.61 | 14-JAN-18:19 | 21.67 | 8.74 |
February | 0.442306E+11 | 26689.33 | 18-FEB-11:33 | 19.33 | 14.12 | 0.169992E+11 | 11319.57 | 11-FEB-18:19 | 19.33 | 14.12 |
March | 0.502598E+11 | 27769.42 | 18-MAR-10:45 | 24.12 | 14.75 | 0.188328E+11 | 11319.67 | 18-MAR-17:19 | 26.63 | 12.71 |
April | 0.529117E+11 | 29280.80 | 30-APR-10:33 | 30.00 | 11.09 | 0.182471E+11 | 11319.67 | 08-APR-17:19 | 30.00 | 11.09 |
May | 0.560558E+11 | 29521.36 | 20-MAY-10:50 | 31.67 | 12.61 | 0.188634E+11 | 11319.67 | 06-MAY-17:19 | 31.67 | 12.61 |
June | 0.568723E+11 | 30410.76 | 18-JUN-10:50 | 35.67 | 17.76 | 0.182650E+11 | 11319.65 | 10-JUN-17:19 | 35.67 | 17.76 |
July | 0.581477E+11 | 30418.88 | 22-JUL-10:37 | 35.67 | 19.48 | 0.188671E+11 | 11319.67 | 29-JUL-17:19 | 35.90 | 19.14 |
August | 0.577927E+11 | 30428.27 | 13-AUG-10:37 | 33.67 | 21.36 | 0.188734E+11 | 11319.65 | 12-AUG-17:19 | 33.67 | 21.36 |
September | 0.546860E+11 | 30158.27 | 09-SEP-10:50 | 33.62 | 20.75 | 0.182580E+11 | 11319.67 | 23-SEP-17:19 | 33.27 | 17.89 |
October | 0.529749E+11 | 29336.59 | 02-OCT-10:45 | 32.67 | 19.11 | 0.188450E+11 | 11319.66 | 14-OCT-17:19 | 30.00 | 11.31 |
November | 0.484600E+11 | 27656.71 | 01-NOV-10:45 | 24.67 | 16.10 | 0.182164E+11 | 11319.58 | 04-NOV-17:19 | 17.67 | 8.15 |
December | 0.482267E+11 | 26683.87 | 25-DEC-11:50 | 22.67 | 10.24 | 0.188074E+11 | 11319.65 | 30-DEC-18:19 | 16.07 | 7.26 |
Annual Sum or Average | 0.630431E+12 | 0.221895E+12 | ||||||||
Minimum of Months | 0.442306E+11 | 26683.87 | 19.33 | 8.74 | 0.169992E+11 | 11319.57 | 16.07 | 7.26 | ||
Maximum of Months | 0.581477E+11 | 30428.27 | 35.67 | 21.36 | 0.188734E+11 | 11319.67 | 35.90 | 21.36 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.763260E+10 | 3801.14 | 31-JAN-17:20 | 27.67 | 10.33 | 0.138681E+10 | 874.97 | 31-JAN-22:19 | 14.27 | 4.94 |
February | 0.608291E+10 | 3531.89 | 26-FEB-11:33 | 15.33 | 10.16 | 0.119405E+10 | 858.09 | 01-FEB-00:10 | 15.33 | 10.16 |
March | 0.748290E+10 | 4234.65 | 18-MAR-17:12 | 26.63 | 12.71 | 0.138672E+10 | 919.68 | 17-MAR-21:40 | 26.63 | 12.71 |
April | 0.962646E+10 | 6230.78 | 14-APR-15:03 | 35.00 | 14.57 | 0.154795E+10 | 1007.40 | 14-APR-23:30 | 24.50 | 12.18 |
May | 0.108337E+11 | 5935.19 | 09-MAY-15:03 | 35.00 | 14.52 | 0.166186E+10 | 1007.44 | 10-MAY-23:19 | 25.67 | 15.01 |
June | 0.132076E+11 | 7825.09 | 28-JUN-18:04 | 40.83 | 17.83 | 0.165490E+10 | 1007.44 | 09-JUN-23:30 | 40.83 | 17.83 |
July | 0.130921E+11 | 7147.31 | 20-JUL-15:03 | 39.83 | 20.05 | 0.170405E+10 | 1007.43 | 01-JUL-00:10 | 39.83 | 20.05 |
August | 0.128043E+11 | 7371.01 | 11-AUG-15:30 | 38.00 | 21.21 | 0.170407E+10 | 1007.41 | 21-AUG-00:10 | 26.00 | 16.49 |
September | 0.114725E+11 | 7397.26 | 07-SEP-15:03 | 37.28 | 19.77 | 0.163480E+10 | 1007.41 | 19-SEP-21:19 | 27.73 | 15.69 |
October | 0.953567E+10 | 6879.81 | 02-OCT-13:20 | 34.33 | 19.52 | 0.154246E+10 | 1007.42 | 06-OCT-23:19 | 25.67 | 15.00 |
November | 0.760177E+10 | 4214.22 | 01-NOV-17:12 | 25.33 | 14.39 | 0.135600E+10 | 929.56 | 01-NOV-21:30 | 18.00 | 13.11 |
December | 0.636030E+10 | 3668.99 | 25-DEC-11:50 | 22.67 | 10.24 | 0.132372E+10 | 857.50 | 26-DEC-22:40 | 14.33 | 6.96 |
Annual Sum or Average | 0.115733E+12 | 0.180974E+11 | ||||||||
Minimum of Months | 0.608291E+10 | 3531.89 | 15.33 | 10.16 | 0.119405E+10 | 857.50 | 14.27 | 4.94 | ||
Maximum of Months | 0.132076E+11 | 7825.09 | 40.83 | 21.21 | 0.170407E+10 | 1007.44 | 40.83 | 20.05 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 143233.01 | 57.52 | 01-JAN-06:00 | 0.80 |
February | 62720.85 | 82.51 | 13-FEB-07:05 | 8.33 |
March | 5054698.76 | 318.60 | 27-MAR-06:05 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 9846938.57 | 386.94 | 16-DEC-07:20 | 1.33 |
Annual Sum or Average | 15107591.20 | |||
Minimum of Months | 0.00 | 0.00 | 0.80 | |
Maximum of Months | 9846938.57 | 386.94 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 159765.07 | 57.73 | 07-DEC-05:00 | -1.1 |
Annual Sum or Average | 159765.07 | |||
Minimum of Months | 0.00 | 0.00 | -1.1 | |
Maximum of Months | 159765.07 | 57.73 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 437145.30 | 53.05 | 01-JAN-06:00 | 0.80 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 1823137.93 | 89.31 | 07-DEC-05:00 | -1.1 |
Annual Sum or Average | 2260283.23 | |||
Minimum of Months | 0.00 | 0.00 | -1.1 | |
Maximum of Months | 1823137.93 | 89.31 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 57442195.93 | 1966.90 | 01-JAN-09:01 | 5.90 |
February | 0.127913E+09 | 1938.36 | 12-FEB-16:02 | 14.00 |
March | 85182855.67 | 2003.40 | 26-MAR-08:62 | 7.75 |
April | 1423859.74 | 1045.95 | 07-APR-08:03 | 14.67 |
May | 1236322.83 | 706.70 | 02-MAY-08:04 | 24.33 |
June | 103719.66 | 346.61 | 13-JUN-08:04 | 25.50 |
July | 381155.85 | 767.74 | 27-JUL-08:04 | 25.33 |
August | 676253.68 | 847.66 | 07-AUG-08:04 | 23.50 |
September | 1020923.56 | 859.18 | 26-SEP-08:04 | 23.85 |
October | 9632328.84 | 1200.29 | 29-OCT-08:03 | 13.50 |
November | 41905674.89 | 1112.07 | 25-NOV-19:03 | 15.00 |
December | 0.225467E+09 | 2060.61 | 07-DEC-09:01 | 6.67 |
Annual Sum or Average | 0.552385E+09 | |||
Minimum of Months | 103719.66 | 346.61 | 5.90 | |
Maximum of Months | 0.225467E+09 | 2060.61 | 25.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140973E+09 | 2106.16 | 01-JAN-09:01 | 5.90 |
February | 0.216885E+09 | 2009.94 | 09-FEB-09:02 | 8.50 |
March | 0.114057E+09 | 2017.76 | 26-MAR-08:62 | 7.75 |
April | 1544994.05 | 1280.74 | 05-APR-08:53 | 25.00 |
May | 719352.02 | 917.11 | 19-MAY-08:14 | 26.67 |
June | 138624.87 | 1178.69 | 13-JUN-08:14 | 26.00 |
July | 167829.66 | 491.54 | 18-JUL-08:04 | 27.17 |
August | 435432.83 | 774.74 | 24-AUG-08:24 | 27.50 |
September | 410136.74 | 887.94 | 16-SEP-08:54 | 26.60 |
October | 18288798.88 | 1675.12 | 25-OCT-08:62 | 8.50 |
November | 95315605.37 | 2042.28 | 24-NOV-09:01 | 9.00 |
December | 0.438392E+09 | 2118.67 | 06-DEC-09:01 | 6.50 |
Annual Sum or Average | 0.102733E+10 | |||
Minimum of Months | 138624.87 | 491.54 | 5.90 | |
Maximum of Months | 0.438392E+09 | 2118.67 | 27.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5694.78 | 18.98 | 09-JAN-08:10 | 9.50 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 9.20 |
Annual Sum or Average | 5694.78 | |||
Minimum of Months | 0.00 | 0.00 | 9.20 | |
Maximum of Months | 5694.78 | 18.98 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6077414.66 | 407.66 | 16-JAN-16:04 | 24.00 |
February | 2187418.40 | 600.34 | 05-FEB-16:03 | 15.83 |
March | 2434008.86 | 548.12 | 12-MAR-15:04 | 16.18 |
April | 693183.37 | 365.18 | 01-APR-08:53 | 24.00 |
May | 335191.86 | 311.14 | 02-MAY-08:44 | 25.67 |
June | 38983.53 | 95.77 | 27-JUN-08:06 | 31.17 |
July | 28026.54 | 97.94 | 27-JUL-08:16 | 25.67 |
August | 110623.92 | 216.68 | 22-AUG-08:06 | 27.50 |
September | 29181.70 | 163.65 | 23-SEP-08:55 | 26.10 |
October | 811367.41 | 440.50 | 12-OCT-15:04 | 19.00 |
November | 3096810.15 | 447.27 | 25-NOV-16:03 | 17.00 |
December | 26857189.88 | 617.29 | 07-DEC-09:01 | 6.67 |
Annual Sum or Average | 42699400.28 | |||
Minimum of Months | 28026.54 | 95.77 | 6.67 | |
Maximum of Months | 26857189.88 | 617.29 | 31.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 68281171.06 | 957.28 | 20-JAN-16:04 | 21.32 |
February | 0.121515E+09 | 1856.41 | 12-FEB-19:02 | 12.00 |
March | 80957621.43 | 992.33 | 07-MAR-19:03 | 18.80 |
April | 125625.64 | 651.39 | 29-APR-08:04 | 24.33 |
May | 113172.39 | 788.14 | 26-MAY-08:04 | 24.50 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 34972.07 | 349.72 | 05-AUG-18:05 | 17.17 |
September | 21557.39 | 160.79 | 03-SEP-18:05 | 27.02 |
October | 8178969.00 | 917.53 | 27-OCT-15:04 | 21.00 |
November | 50221005.76 | 995.63 | 08-NOV-19:04 | 18.83 |
December | 0.223693E+09 | 1195.08 | 11-DEC-09:02 | 13.17 |
Annual Sum or Average | 0.553143E+09 | |||
Minimum of Months | 0.00 | 0.00 | 12.00 | |
Maximum of Months | 0.223693E+09 | 1856.41 | 27.73 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158228E+09 | 1936.54 | 01-JAN-19:02 | 11.03 |
February | 0.189475E+09 | 1899.03 | 12-FEB-16:02 | 14.00 |
March | 0.107968E+09 | 1099.49 | 08-MAR-16:03 | 19.30 |
April | 530030.84 | 758.54 | 27-APR-21:54 | 21.00 |
May | 51710.07 | 734.68 | 25-MAY-08:14 | 25.67 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 660.49 | 11.01 | 05-AUG-08:56 | 25.00 |
September | 126759.89 | 404.80 | 20-SEP-06:05 | 24.30 |
October | 16554573.96 | 1017.35 | 22-OCT-15:04 | 15.83 |
November | 0.108971E+09 | 1545.37 | 23-NOV-19:02 | 8.83 |
December | 0.412453E+09 | 1962.85 | 07-DEC-16:01 | 15.67 |
Annual Sum or Average | 0.994358E+09 | |||
Minimum of Months | 0.00 | 0.00 | 8.83 | |
Maximum of Months | 0.412453E+09 | 1962.85 | 27.73 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152366E+09 | 2451.22 | 01-JAN-09:01 | 5.90 |
February | 0.262895E+09 | 2337.98 | 09-FEB-09:02 | 8.50 |
March | 0.174012E+09 | 2391.34 | 26-MAR-08:62 | 7.75 |
April | 2586815.14 | 1115.24 | 18-APR-08:03 | 20.50 |
May | 1468461.89 | 1455.28 | 09-MAY-08:03 | 26.33 |
June | 176954.24 | 881.37 | 14-JUN-08:03 | 27.67 |
July | 421287.06 | 770.80 | 27-JUL-08:04 | 25.33 |
August | 723938.66 | 807.38 | 07-AUG-08:04 | 23.50 |
September | 1295847.07 | 822.61 | 14-SEP-08:04 | 23.67 |
October | 39860416.07 | 2232.87 | 25-OCT-08:62 | 8.50 |
November | 0.116917E+09 | 2369.78 | 24-NOV-09:01 | 9.00 |
December | 0.416539E+09 | 2462.18 | 06-DEC-09:01 | 6.50 |
Annual Sum or Average | 0.116926E+10 | |||
Minimum of Months | 176954.24 | 770.80 | 5.90 | |
Maximum of Months | 0.416539E+09 | 2462.18 | 27.67 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.303438E+09 | 2503.13 | 01-JAN-09:01 | 5.90 |
February | 0.401063E+09 | 2385.09 | 09-FEB-09:02 | 8.50 |
March | 0.215580E+09 | 2405.54 | 26-MAR-08:62 | 7.75 |
April | 2289776.16 | 1403.92 | 24-APR-08:53 | 26.00 |
May | 937365.40 | 1543.21 | 14-MAY-08:43 | 25.92 |
June | 221085.24 | 865.79 | 13-JUN-08:14 | 26.00 |
July | 305102.65 | 935.86 | 02-JUL-08:14 | 27.07 |
August | 439167.16 | 693.32 | 30-AUG-08:04 | 26.67 |
September | 875609.06 | 930.27 | 25-SEP-08:24 | 25.25 |
October | 62490693.42 | 2364.79 | 25-OCT-08:62 | 8.50 |
November | 0.216784E+09 | 2436.59 | 23-NOV-09:02 | 5.45 |
December | 0.719805E+09 | 2503.14 | 06-DEC-09:01 | 6.50 |
Annual Sum or Average | 0.192423E+10 | |||
Minimum of Months | 221085.24 | 693.32 | 5.45 | |
Maximum of Months | 0.719805E+09 | 2503.14 | 27.07 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6835860.54 | 339.02 | 01-JAN-19:05 | 11.03 |
February | 26211261.48 | 738.23 | 07-FEB-16:04 | 16.00 |
March | 29028006.44 | 1228.78 | 27-MAR-08:62 | 9.77 |
April | 737882.18 | 478.99 | 19-APR-08:03 | 19.50 |
May | 989995.49 | 470.49 | 16-MAY-08:04 | 25.50 |
June | 357285.73 | 455.76 | 13-JUN-08:04 | 25.50 |
July | 470406.29 | 435.01 | 03-JUL-08:04 | 28.50 |
August | 522269.20 | 483.01 | 17-AUG-08:04 | 28.33 |
September | 305319.05 | 420.45 | 29-SEP-08:04 | 26.65 |
October | 1448863.18 | 493.24 | 12-OCT-08:03 | 12.33 |
November | 7050840.25 | 395.21 | 04-NOV-08:03 | 9.50 |
December | 42680633.04 | 609.03 | 15-DEC-16:04 | 12.83 |
Annual Sum or Average | 0.116639E+09 | |||
Minimum of Months | 305319.05 | 339.02 | 9.50 | |
Maximum of Months | 42680633.04 | 1228.78 | 28.50 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 816890.16 | 161.13 | 01-JAN-06:00 | 0.80 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 17.23 |
December | 10438255.77 | 665.49 | 07-DEC-07:05 | 1.33 |
Annual Sum or Average | 11255145.93 | |||
Minimum of Months | 0.00 | 0.00 | 0.80 | |
Maximum of Months | 10438255.77 | 665.49 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.866285E+10 | 8344.11 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.782177E+10 | 8344.11 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.868956E+10 | 8344.11 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.836914E+10 | 8344.11 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.867788E+10 | 8344.11 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.840753E+10 | 8344.11 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.863949E+10 | 8344.11 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.869290E+10 | 8344.11 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.837248E+10 | 8344.11 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.865952E+10 | 8344.11 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.840085E+10 | 8344.11 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.863949E+10 | 8344.11 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.102033E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.782177E+10 | 8344.11 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.869290E+10 | 8344.11 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.478695E+09 | 461.08 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.432218E+09 | 461.08 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.480171E+09 | 461.08 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.462465E+09 | 461.08 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.479525E+09 | 461.08 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.464586E+09 | 461.08 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.477404E+09 | 461.08 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.480355E+09 | 461.08 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.462650E+09 | 461.08 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.478511E+09 | 461.08 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.464217E+09 | 461.08 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.477404E+09 | 461.08 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.563820E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.432218E+09 | 461.08 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.480355E+09 | 461.08 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.554331E+09 | 533.93 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.500510E+09 | 533.93 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.556040E+09 | 533.93 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.535537E+09 | 533.93 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.555292E+09 | 533.93 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.537993E+09 | 533.93 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.552836E+09 | 533.93 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.556253E+09 | 533.93 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.535750E+09 | 533.93 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.554117E+09 | 533.93 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.537566E+09 | 533.93 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.552836E+09 | 533.93 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.652906E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.500510E+09 | 533.93 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.556253E+09 | 533.93 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.639281E+09 | 615.76 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.577212E+09 | 615.76 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.641251E+09 | 615.76 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.617606E+09 | 615.76 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.640389E+09 | 615.76 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.620439E+09 | 615.76 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.637557E+09 | 615.76 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.641498E+09 | 615.76 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.617853E+09 | 615.76 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.639035E+09 | 615.76 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.619946E+09 | 615.76 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.637557E+09 | 615.76 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.752962E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.577212E+09 | 615.76 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.641498E+09 | 615.76 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142601E+09 | 137.35 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.128756E+09 | 137.35 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.143041E+09 | 137.35 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.137766E+09 | 137.35 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.142848E+09 | 137.35 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.138398E+09 | 137.35 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.142217E+09 | 137.35 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.143096E+09 | 137.35 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.137821E+09 | 137.35 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.142546E+09 | 137.35 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.138288E+09 | 137.35 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.142217E+09 | 137.35 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.167960E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.128756E+09 | 137.35 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.143096E+09 | 137.35 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.374392E+09 | 360.62 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.338042E+09 | 360.62 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.375546E+09 | 360.62 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.361698E+09 | 360.62 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.375041E+09 | 360.62 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.363357E+09 | 360.62 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.373382E+09 | 360.62 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.375690E+09 | 360.62 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.361842E+09 | 360.62 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.374247E+09 | 360.62 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.363068E+09 | 360.62 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.373382E+09 | 360.62 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.440969E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.338042E+09 | 360.62 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.375690E+09 | 360.62 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.108770E+10 | 1416.11 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.976596E+09 | 1416.11 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.100980E+10 | 1416.11 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.920387E+09 | 1416.11 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.906806E+09 | 1416.11 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.816973E+09 | 1416.11 | 01-JUN-19:19 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.863816E+09 | 1416.11 | 03-JUL-19:30 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.955966E+09 | 1416.11 | 01-AUG-19:19 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.954911E+09 | 1416.11 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.104060E+10 | 1416.11 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.104134E+10 | 1416.11 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.109538E+10 | 1416.11 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.116703E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.816973E+09 | 1416.11 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.109538E+10 | 1416.11 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.948818E+10 | 9580.84 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.857628E+10 | 9580.84 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.944828E+10 | 9580.84 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.904072E+10 | 9580.84 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.933403E+10 | 9580.84 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.900083E+10 | 9580.84 | 01-JUN-19:19 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.926915E+10 | 9580.84 | 03-JUL-19:30 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.940571E+10 | 9580.84 | 01-AUG-19:19 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.908263E+10 | 9580.84 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.944395E+10 | 9580.84 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.919119E+10 | 9580.84 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.947627E+10 | 9580.84 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.110757E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.857628E+10 | 9580.84 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.948818E+10 | 9580.84 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118113E+09 | 106.87 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.106667E+09 | 106.87 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.117174E+09 | 106.87 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.114438E+09 | 106.87 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.117643E+09 | 106.87 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113531E+09 | 106.87 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.118566E+09 | 106.87 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.117174E+09 | 106.87 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.114469E+09 | 106.87 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.118097E+09 | 106.87 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113984E+09 | 106.87 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.118582E+09 | 106.87 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.138844E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.106667E+09 | 106.87 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.118582E+09 | 106.87 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118099E+09 | 106.85 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.106655E+09 | 106.85 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.117160E+09 | 106.85 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.114425E+09 | 106.85 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.117629E+09 | 106.85 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113517E+09 | 106.85 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.118553E+09 | 106.85 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.117160E+09 | 106.85 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.114456E+09 | 106.85 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.118083E+09 | 106.85 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113971E+09 | 106.85 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.118568E+09 | 106.85 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.138828E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.106655E+09 | 106.85 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.118568E+09 | 106.85 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 74229181.22 | 67.16 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 67036196.95 | 67.16 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 73639243.64 | 67.16 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 71920171.51 | 67.16 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 73934212.43 | 67.16 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 71349576.37 | 67.16 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 74514478.79 | 67.16 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 73639243.64 | 67.16 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 71939513.95 | 67.16 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 74219510.00 | 67.16 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 71634873.94 | 67.16 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 74524150.01 | 67.16 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.872580E+09 | 0.300992E+10 | ||||
Minimum of Months | 67036196.95 | 67.16 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 74524150.01 | 67.16 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 74249479.06 | 67.18 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 67054527.88 | 67.18 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 73659380.16 | 67.18 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 71939837.95 | 67.18 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 73954429.61 | 67.18 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 71369086.78 | 67.18 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 74534854.64 | 67.18 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 73659380.16 | 67.18 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 71959185.68 | 67.18 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 74239805.19 | 67.18 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 71654462.37 | 67.18 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 74544528.51 | 67.18 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.872819E+09 | 0.301074E+10 | ||||
Minimum of Months | 67054527.88 | 67.18 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 74544528.51 | 67.18 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118113E+09 | 106.87 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.106667E+09 | 106.87 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.117174E+09 | 106.87 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.114438E+09 | 106.87 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.117643E+09 | 106.87 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113531E+09 | 106.87 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.118566E+09 | 106.87 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.117174E+09 | 106.87 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.114469E+09 | 106.87 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.118097E+09 | 106.87 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113984E+09 | 106.87 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.118582E+09 | 106.87 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.138844E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.106667E+09 | 106.87 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.118582E+09 | 106.87 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118099E+09 | 106.85 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.106655E+09 | 106.85 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.117160E+09 | 106.85 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.114425E+09 | 106.85 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.117629E+09 | 106.85 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113517E+09 | 106.85 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.118553E+09 | 106.85 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.117160E+09 | 106.85 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.114456E+09 | 106.85 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.118083E+09 | 106.85 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113971E+09 | 106.85 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.118568E+09 | 106.85 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.138828E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.106655E+09 | 106.85 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.118568E+09 | 106.85 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.108388E+10 | 1044.00 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.978647E+09 | 1044.00 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.108722E+10 | 1044.00 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.104713E+10 | 1044.00 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.108576E+10 | 1044.00 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.105194E+10 | 1044.00 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.108096E+10 | 1044.00 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.108764E+10 | 1044.00 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.104755E+10 | 1044.00 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.108346E+10 | 1044.00 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.105110E+10 | 1044.00 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.108096E+10 | 1044.00 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.127663E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.978647E+09 | 1044.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108764E+10 | 1044.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118113E+09 | 106.87 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.106667E+09 | 106.87 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.117174E+09 | 106.87 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.114438E+09 | 106.87 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.117643E+09 | 106.87 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113531E+09 | 106.87 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.118566E+09 | 106.87 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.117174E+09 | 106.87 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.114469E+09 | 106.87 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.118097E+09 | 106.87 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113984E+09 | 106.87 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.118582E+09 | 106.87 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.138844E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.106667E+09 | 106.87 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.118582E+09 | 106.87 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118099E+09 | 106.85 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.106655E+09 | 106.85 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.117160E+09 | 106.85 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.114425E+09 | 106.85 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.117629E+09 | 106.85 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113517E+09 | 106.85 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.118553E+09 | 106.85 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.117160E+09 | 106.85 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.114456E+09 | 106.85 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.118083E+09 | 106.85 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113971E+09 | 106.85 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.118568E+09 | 106.85 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.138828E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.106655E+09 | 106.85 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.118568E+09 | 106.85 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 74249479.06 | 67.18 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 67054527.88 | 67.18 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 73659380.16 | 67.18 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 71939837.95 | 67.18 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 73954429.61 | 67.18 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 71369086.78 | 67.18 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 74534854.64 | 67.18 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 73659380.16 | 67.18 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 71959185.68 | 67.18 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 74239805.19 | 67.18 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 71654462.37 | 67.18 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 74544528.51 | 67.18 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.872819E+09 | 0.301074E+10 | ||||
Minimum of Months | 67054527.88 | 67.18 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 74544528.51 | 67.18 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232262E+10 | 2486.81 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.207615E+10 | 2486.81 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.221234E+10 | 2486.81 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.205172E+10 | 2486.81 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.205514E+10 | 2486.81 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.192029E+10 | 2486.81 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.200786E+10 | 2486.81 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.213003E+10 | 2486.81 | 01-AUG-19:19 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.209741E+10 | 2486.81 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.227261E+10 | 2486.81 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.223592E+10 | 2486.81 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.232388E+10 | 2486.81 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.257060E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.192029E+10 | 2486.81 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.232388E+10 | 2486.81 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.232262E+10 | 2486.81 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.207615E+10 | 2486.81 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.221234E+10 | 2486.81 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.205172E+10 | 2486.81 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.205514E+10 | 2486.81 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.192029E+10 | 2486.81 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.200786E+10 | 2486.81 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.213003E+10 | 2486.81 | 01-AUG-19:19 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.209741E+10 | 2486.81 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.227261E+10 | 2486.81 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.223592E+10 | 2486.81 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.232388E+10 | 2486.81 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.257060E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.192029E+10 | 2486.81 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.232388E+10 | 2486.81 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101925E+10 | 981.75 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.920291E+09 | 981.75 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.102239E+10 | 981.75 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.984694E+09 | 981.75 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.102102E+10 | 981.75 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.989210E+09 | 981.75 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.101650E+10 | 981.75 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.102279E+10 | 981.75 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.985086E+09 | 981.75 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.101886E+10 | 981.75 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.988424E+09 | 981.75 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.101650E+10 | 981.75 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.120050E+11 | 0.424019E+12 | ||||
Minimum of Months | 0.920291E+09 | 981.75 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.102279E+10 | 981.75 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.114712E+10 | 1104.91 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.103575E+10 | 1104.91 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.115066E+10 | 1104.91 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.110823E+10 | 1104.91 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.114911E+10 | 1104.91 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.111331E+10 | 1104.91 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.114403E+10 | 1104.91 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.115110E+10 | 1104.91 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.110867E+10 | 1104.91 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.114668E+10 | 1104.91 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.111243E+10 | 1104.91 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.114403E+10 | 1104.91 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.135111E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.103575E+10 | 1104.91 | 0.00 | 0.00 | |
Maximum of Months | 0.115110E+10 | 1104.91 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.866285E+10 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.782177E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.868956E+10 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.836914E+10 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.867788E+10 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.840753E+10 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.863949E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.869290E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.837248E+10 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.865952E+10 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.840085E+10 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.863949E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.102033E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.782177E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.869290E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.478695E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4243426.49 | 0.418914E+09 |
February | 0.179968E+10 | 0.432218E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1987.13 | 0.433433E+09 |
March | 0.199990E+10 | 0.480171E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13322648.08 | 0.358907E+09 |
April | 0.192973E+10 | 0.462465E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117231E+09 | 0.116249E+09 |
May | 0.199475E+10 | 0.479525E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200662E+09 | 55935533.56 |
June | 0.193394E+10 | 0.464586E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361530E+09 | 8823688.02 |
July | 0.199054E+10 | 0.477404E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335578E+09 | 5350721.22 |
August | 0.199896E+10 | 0.480355E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309462E+09 | 7351922.70 |
September | 0.192879E+10 | 0.462650E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214471E+09 | 18474472.52 |
October | 0.199148E+10 | 0.478511E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78491068.92 | 0.199287E+09 |
November | 0.192552E+10 | 0.464217E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8109971.55 | 0.372182E+09 |
December | 0.199054E+10 | 0.477404E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1171282.61 | 0.552894E+09 |
Annual Sum or Average | 0.234744E+11 | 0.563820E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164427E+10 | 0.254780E+10 |
Minimum of Months | 0.179968E+10 | 0.432218E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1987.13 | 5350721.22 |
Maximum of Months | 0.199990E+10 | 0.480355E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361530E+09 | 0.552894E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.554331E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3335774.37 | 0.175116E+09 |
February | 0.208403E+10 | 0.500510E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182265E+09 |
March | 0.231589E+10 | 0.556040E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6114773.98 | 0.157733E+09 |
April | 0.223463E+10 | 0.535537E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47197694.08 | 55966057.01 |
May | 0.230993E+10 | 0.555292E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77513250.00 | 29623974.27 |
June | 0.223950E+10 | 0.537993E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139190E+09 | 5162441.63 |
July | 0.230505E+10 | 0.552836E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128625E+09 | 3279118.38 |
August | 0.231480E+10 | 0.556253E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118645E+09 | 4971964.76 |
September | 0.223354E+10 | 0.535750E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83047444.54 | 10862471.79 |
October | 0.230614E+10 | 0.554117E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32045247.18 | 88181597.47 |
November | 0.222975E+10 | 0.537566E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4270359.00 | 0.158617E+09 |
December | 0.230505E+10 | 0.552836E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1063156.91 | 0.226605E+09 |
Annual Sum or Average | 0.271834E+11 | 0.652906E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641047E+09 | 0.109838E+10 |
Minimum of Months | 0.208403E+10 | 0.500510E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3279118.38 |
Maximum of Months | 0.231589E+10 | 0.556253E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139190E+09 | 0.226605E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.639281E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16152251.81 | 0.352130E+09 |
February | 0.440737E+09 | 0.577212E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 103714.83 | 0.376154E+09 |
March | 0.489771E+09 | 0.641251E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19903649.72 | 0.323526E+09 |
April | 0.472586E+09 | 0.617606E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123066E+09 | 0.114986E+09 |
May | 0.488511E+09 | 0.640389E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185100E+09 | 63773997.60 |
June | 0.473617E+09 | 0.620439E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326008E+09 | 12063963.42 |
July | 0.487480E+09 | 0.637557E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300710E+09 | 7546936.82 |
August | 0.489542E+09 | 0.641498E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278619E+09 | 11042906.28 |
September | 0.472357E+09 | 0.617853E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196020E+09 | 23682512.11 |
October | 0.487709E+09 | 0.639035E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82675850.39 | 0.181915E+09 |
November | 0.471555E+09 | 0.619946E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16531877.48 | 0.321311E+09 |
December | 0.487480E+09 | 0.637557E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5871988.32 | 0.471649E+09 |
Annual Sum or Average | 0.574883E+10 | 0.752962E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155076E+10 | 0.225978E+10 |
Minimum of Months | 0.440737E+09 | 0.577212E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 103714.83 | 7546936.82 |
Maximum of Months | 0.489771E+09 | 0.641498E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326008E+09 | 0.471649E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.142601E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9068671.78 | 0.200635E+09 |
February | 0.339028E+09 | 0.128756E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57244.76 | 0.214999E+09 |
March | 0.376747E+09 | 0.143041E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11497266.03 | 0.183922E+09 |
April | 0.363528E+09 | 0.137766E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72151225.88 | 64136434.54 |
May | 0.375778E+09 | 0.142848E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108323E+09 | 35206063.88 |
June | 0.364321E+09 | 0.138398E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188252E+09 | 6718795.77 |
July | 0.374985E+09 | 0.142217E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173698E+09 | 4210726.03 |
August | 0.376571E+09 | 0.143096E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161147E+09 | 5972785.56 |
September | 0.363352E+09 | 0.137821E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113815E+09 | 12864085.69 |
October | 0.375161E+09 | 0.142546E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48087529.59 | 0.102223E+09 |
November | 0.362735E+09 | 0.138288E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9403016.41 | 0.182509E+09 |
December | 0.374985E+09 | 0.142217E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3266915.48 | 0.270211E+09 |
Annual Sum or Average | 0.442217E+10 | 0.167960E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898767E+09 | 0.128361E+10 |
Minimum of Months | 0.339028E+09 | 0.128756E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57244.76 | 4210726.03 |
Maximum of Months | 0.376747E+09 | 0.143096E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188252E+09 | 0.270211E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.374392E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 10834577.83 | 0.569602E+09 |
February | 0.139600E+10 | 0.338042E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624068E+09 |
March | 0.155131E+10 | 0.375546E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 17754043.32 | 0.531523E+09 |
April | 0.149688E+10 | 0.361698E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 0.159384E+09 | 0.162672E+09 |
May | 0.154732E+10 | 0.375041E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 0.260470E+09 | 75061635.94 |
June | 0.150015E+10 | 0.363357E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 0.478821E+09 | 9442135.75 |
July | 0.154405E+10 | 0.373382E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.448524E+09 | 6314702.68 |
August | 0.155059E+10 | 0.375690E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.416297E+09 | 10673434.85 |
September | 0.149615E+10 | 0.361842E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 0.293845E+09 | 23778989.88 |
October | 0.154478E+10 | 0.374247E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.113324E+09 | 0.275099E+09 |
November | 0.149361E+10 | 0.363068E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 14225683.29 | 0.513736E+09 |
December | 0.154405E+10 | 0.373382E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 3248039.72 | 0.760094E+09 |
Annual Sum or Average | 0.182090E+11 | 0.440969E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.221673E+10 | 0.356207E+10 |
Minimum of Months | 0.139600E+10 | 0.338042E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6314702.68 |
Maximum of Months | 0.155131E+10 | 0.375690E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.478821E+09 | 0.760094E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.108770E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9261832.08 | 0.105784E+10 |
February | 0.236489E+11 | 0.976596E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109637E+10 |
March | 0.262800E+11 | 0.100980E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25696707.44 | 0.933958E+09 |
April | 0.253579E+11 | 0.920387E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255775E+09 | 0.314351E+09 |
May | 0.262123E+11 | 0.906806E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443535E+09 | 0.162878E+09 |
June | 0.254132E+11 | 0.816973E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.803860E+09 | 28830599.32 |
July | 0.261570E+11 | 0.863816E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740278E+09 | 18370578.97 |
August | 0.262677E+11 | 0.955966E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680545E+09 | 27210862.85 |
September | 0.253456E+11 | 0.954911E+09 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471082E+09 | 59868627.17 |
October | 0.261693E+11 | 0.104060E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171767E+09 | 0.519319E+09 |
November | 0.253025E+11 | 0.104134E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17212323.07 | 0.947885E+09 |
December | 0.261570E+11 | 0.109538E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2415330.75 | 0.136851E+10 |
Annual Sum or Average | 0.308468E+12 | 0.116703E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362143E+10 | 0.653540E+10 |
Minimum of Months | 0.236489E+11 | 0.816973E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18370578.97 |
Maximum of Months | 0.262800E+11 | 0.109538E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.803860E+09 | 0.136851E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.948818E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33463188.93 | 0.302107E+10 |
February | 0.702046E+11 | 0.857628E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317788E+10 |
March | 0.780153E+11 | 0.944828E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85081613.80 | 0.273467E+10 |
April | 0.752779E+11 | 0.904072E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758064E+09 | 0.930706E+09 |
May | 0.778146E+11 | 0.933403E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126900E+10 | 0.487033E+09 |
June | 0.754422E+11 | 0.900083E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228726E+10 | 84353040.92 |
July | 0.776503E+11 | 0.926915E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210742E+10 | 54029213.57 |
August | 0.779788E+11 | 0.940571E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193954E+10 | 83514604.63 |
September | 0.752414E+11 | 0.908263E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134771E+10 | 0.180058E+09 |
October | 0.776868E+11 | 0.944395E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502166E+09 | 0.150614E+10 |
November | 0.751137E+11 | 0.919119E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54416371.47 | 0.273033E+10 |
December | 0.776503E+11 | 0.947627E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9896923.81 | 0.392481E+10 |
Annual Sum or Average | 0.915726E+12 | 0.110757E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103940E+11 | 0.189146E+11 |
Minimum of Months | 0.702046E+11 | 0.857628E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54029213.57 |
Maximum of Months | 0.780153E+11 | 0.948818E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228726E+10 | 0.392481E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118113E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6152101.41 | 0.220495E+09 |
February | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.10 | 0.244774E+09 |
March | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10749663.09 | 0.202667E+09 |
April | 0.293479E+09 | 0.114438E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93805780.78 | 52208613.23 |
May | 0.303504E+09 | 0.117643E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150605E+09 | 19707092.98 |
June | 0.293842E+09 | 0.113531E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262017E+09 | 983483.68 |
July | 0.303141E+09 | 0.118566E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250964E+09 | 782284.06 |
August | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233480E+09 | 1060281.73 |
September | 0.293479E+09 | 0.114469E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171768E+09 | 3549442.12 |
October | 0.303322E+09 | 0.118097E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65746970.75 | 96040062.26 |
November | 0.293661E+09 | 0.113984E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8141537.08 | 0.195898E+09 |
December | 0.303141E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1689823.33 | 0.305863E+09 |
Annual Sum or Average | 0.357224E+10 | 0.138844E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125512E+10 | 0.134403E+10 |
Minimum of Months | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4077.10 | 782284.06 |
Maximum of Months | 0.303685E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262017E+09 | 0.305863E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118099E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6894887.49 | 0.219485E+09 |
February | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11071.93 | 0.239973E+09 |
March | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10112508.20 | 0.205993E+09 |
April | 0.293479E+09 | 0.114425E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91700778.38 | 57373789.74 |
May | 0.303504E+09 | 0.117629E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147999E+09 | 23341197.48 |
June | 0.293842E+09 | 0.113517E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258604E+09 | 2221881.94 |
July | 0.303141E+09 | 0.118553E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249615E+09 | 1398959.94 |
August | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231079E+09 | 2725515.30 |
September | 0.293479E+09 | 0.114456E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168602E+09 | 6130487.30 |
October | 0.303322E+09 | 0.118083E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64186802.39 | 0.100888E+09 |
November | 0.293661E+09 | 0.113971E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8291255.16 | 0.197026E+09 |
December | 0.303141E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2202592.27 | 0.297919E+09 |
Annual Sum or Average | 0.357224E+10 | 0.138828E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123930E+10 | 0.135447E+10 |
Minimum of Months | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11071.93 | 1398959.94 |
Maximum of Months | 0.303685E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258604E+09 | 0.297919E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 74229181.22 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85515.63 | 0.102606E+09 |
February | 0.00 | 67036196.95 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106016E+09 |
March | 0.00 | 73639243.64 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 228831.07 | 95185873.60 |
April | 0.00 | 71920171.51 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9208781.85 | 37486340.26 |
May | 0.00 | 73934212.43 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18326400.00 | 22493033.24 |
June | 0.00 | 71349576.37 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40718162.17 | 6368949.35 |
July | 0.00 | 74514478.79 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34755507.26 | 5112636.76 |
August | 0.00 | 73639243.64 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32010315.21 | 7378828.92 |
September | 0.00 | 71939513.95 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20349346.78 | 12654997.59 |
October | 0.00 | 74219510.00 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6715436.13 | 56764167.16 |
November | 0.00 | 71634873.94 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 122635.28 | 93618213.25 |
December | 0.00 | 74524150.01 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127283E+09 |
Annual Sum or Average | 0.00 | 0.872580E+09 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162521E+09 | 0.672967E+09 |
Minimum of Months | 0.00 | 67036196.95 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5112636.76 |
Maximum of Months | 0.00 | 74524150.01 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40718162.17 | 0.127283E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 74249479.06 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2526717.00 | 60676415.64 |
February | 0.273974E+09 | 67054527.88 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1355.28 | 67571650.08 |
March | 0.303685E+09 | 73659380.16 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3064257.92 | 57168348.36 |
April | 0.293479E+09 | 71939837.95 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26025930.26 | 15334413.79 |
May | 0.303504E+09 | 73954429.61 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41626782.59 | 6208222.84 |
June | 0.293842E+09 | 71369086.78 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72527495.41 | 465633.85 |
July | 0.303141E+09 | 74534854.64 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69875771.41 | 323206.77 |
August | 0.303685E+09 | 73659380.16 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64773031.40 | 626317.70 |
September | 0.293479E+09 | 71959185.68 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47340758.59 | 1508963.56 |
October | 0.303322E+09 | 74239805.19 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18384245.32 | 27584294.91 |
November | 0.293661E+09 | 71654462.37 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2758817.26 | 54390008.37 |
December | 0.303141E+09 | 74544528.51 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 848660.33 | 83457387.83 |
Annual Sum or Average | 0.357224E+10 | 0.872819E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349754E+09 | 0.375315E+09 |
Minimum of Months | 0.273974E+09 | 67054527.88 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1355.28 | 323206.77 |
Maximum of Months | 0.303685E+09 | 74544528.51 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72527495.41 | 83457387.83 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118113E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6159183.24 | 0.222102E+09 |
February | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4008.99 | 0.247550E+09 |
March | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10666434.96 | 0.205537E+09 |
April | 0.293479E+09 | 0.114438E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93656490.34 | 53102704.81 |
May | 0.303504E+09 | 0.117643E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150338E+09 | 19970453.99 |
June | 0.293842E+09 | 0.113531E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261915E+09 | 983666.74 |
July | 0.303141E+09 | 0.118566E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250702E+09 | 787067.94 |
August | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233337E+09 | 1106511.26 |
September | 0.293479E+09 | 0.114469E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171625E+09 | 3671143.03 |
October | 0.303322E+09 | 0.118097E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65723168.29 | 97246586.48 |
November | 0.293661E+09 | 0.113984E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8097443.10 | 0.197009E+09 |
December | 0.303141E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1688356.29 | 0.307936E+09 |
Annual Sum or Average | 0.357224E+10 | 0.138844E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125391E+10 | 0.135700E+10 |
Minimum of Months | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4008.99 | 787067.94 |
Maximum of Months | 0.303685E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261915E+09 | 0.307936E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118099E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6573350.97 | 0.219302E+09 |
February | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4105.43 | 0.242038E+09 |
March | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9850046.42 | 0.208058E+09 |
April | 0.293479E+09 | 0.114425E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91013590.68 | 60633615.92 |
May | 0.303504E+09 | 0.117629E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147077E+09 | 27855408.47 |
June | 0.293842E+09 | 0.113517E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257973E+09 | 3267403.09 |
July | 0.303141E+09 | 0.118553E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249201E+09 | 1962914.08 |
August | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230552E+09 | 3550966.61 |
September | 0.293479E+09 | 0.114456E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167874E+09 | 7487349.50 |
October | 0.303322E+09 | 0.118083E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63727529.88 | 0.103416E+09 |
November | 0.293661E+09 | 0.113971E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8104299.98 | 0.196602E+09 |
December | 0.303141E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2075168.91 | 0.298048E+09 |
Annual Sum or Average | 0.357224E+10 | 0.138828E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123403E+10 | 0.137222E+10 |
Minimum of Months | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4105.43 | 1962914.08 |
Maximum of Months | 0.303685E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257973E+09 | 0.298048E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.108388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8499401.37 | 0.285292E+09 |
February | 0.348285E+10 | 0.978647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63900.65 | 0.298308E+09 |
March | 0.387034E+10 | 0.108722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13404856.64 | 0.257134E+09 |
April | 0.373454E+10 | 0.104713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90360273.48 | 91761097.80 |
May | 0.386038E+10 | 0.108576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140638E+09 | 49835616.85 |
June | 0.374269E+10 | 0.105194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250401E+09 | 9258989.50 |
July | 0.385223E+10 | 0.108096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231083E+09 | 5843820.61 |
August | 0.386853E+10 | 0.108764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213752E+09 | 8520274.29 |
September | 0.373273E+10 | 0.104755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148918E+09 | 18642042.55 |
October | 0.385404E+10 | 0.108346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58928092.89 | 0.148851E+09 |
November | 0.372639E+10 | 0.105110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9896174.00 | 0.259534E+09 |
December | 0.385223E+10 | 0.108096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3216082.16 | 0.373218E+09 |
Annual Sum or Average | 0.454292E+11 | 0.127663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116916E+10 | 0.180620E+10 |
Minimum of Months | 0.348285E+10 | 0.978647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63900.65 | 5843820.61 |
Maximum of Months | 0.387034E+10 | 0.108764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250401E+09 | 0.373218E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118113E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5959403.60 | 0.221184E+09 |
February | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3336.61 | 0.245134E+09 |
March | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10521665.84 | 0.203369E+09 |
April | 0.293479E+09 | 0.114438E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92813627.27 | 52601168.02 |
May | 0.303504E+09 | 0.117643E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149348E+09 | 20068732.24 |
June | 0.293842E+09 | 0.113531E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260351E+09 | 1043800.43 |
July | 0.303141E+09 | 0.118566E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249309E+09 | 824952.71 |
August | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231823E+09 | 1115378.45 |
September | 0.293479E+09 | 0.114469E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170285E+09 | 3640345.91 |
October | 0.303322E+09 | 0.118097E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65044118.56 | 96402583.31 |
November | 0.293661E+09 | 0.113984E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7961426.22 | 0.196423E+09 |
December | 0.303141E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1620149.14 | 0.306213E+09 |
Annual Sum or Average | 0.357224E+10 | 0.138844E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124504E+10 | 0.134802E+10 |
Minimum of Months | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3336.61 | 824952.71 |
Maximum of Months | 0.303685E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260351E+09 | 0.306213E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118099E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6943808.95 | 0.219284E+09 |
February | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8913.49 | 0.239796E+09 |
March | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9876410.19 | 0.206788E+09 |
April | 0.293479E+09 | 0.114425E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90844950.61 | 57335356.10 |
May | 0.303504E+09 | 0.117629E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146949E+09 | 22795276.59 |
June | 0.293842E+09 | 0.113517E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257157E+09 | 2036709.48 |
July | 0.303141E+09 | 0.118553E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248068E+09 | 1295219.12 |
August | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229600E+09 | 2550941.65 |
September | 0.293479E+09 | 0.114456E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167371E+09 | 5678882.12 |
October | 0.303322E+09 | 0.118083E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63704249.48 | 0.100084E+09 |
November | 0.293661E+09 | 0.113971E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8235198.26 | 0.196306E+09 |
December | 0.303141E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2243903.99 | 0.297167E+09 |
Annual Sum or Average | 0.357224E+10 | 0.138828E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123100E+10 | 0.135112E+10 |
Minimum of Months | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8913.49 | 1295219.12 |
Maximum of Months | 0.303685E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257157E+09 | 0.297167E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 74249479.06 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3005604.23 | 0.115015E+09 |
February | 0.273974E+09 | 67054527.88 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1607.45 | 0.128390E+09 |
March | 0.303685E+09 | 73659380.16 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5319026.02 | 0.105878E+09 |
April | 0.293479E+09 | 71939837.95 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47460100.59 | 26980022.77 |
May | 0.303504E+09 | 73954429.61 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 76460637.17 | 10267868.78 |
June | 0.293842E+09 | 71369086.78 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133451E+09 | 533903.58 |
July | 0.303141E+09 | 74534854.64 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127587E+09 | 421985.49 |
August | 0.303685E+09 | 73659380.16 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118673E+09 | 572871.01 |
September | 0.293479E+09 | 71959185.68 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87014425.32 | 1891093.38 |
October | 0.303322E+09 | 74239805.19 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33151176.72 | 50051079.62 |
November | 0.293661E+09 | 71654462.37 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3976013.20 | 0.102076E+09 |
December | 0.303141E+09 | 74544528.51 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 815675.22 | 0.160056E+09 |
Annual Sum or Average | 0.357224E+10 | 0.872819E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636915E+09 | 0.702135E+09 |
Minimum of Months | 0.273974E+09 | 67054527.88 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1607.45 | 421985.49 |
Maximum of Months | 0.303685E+09 | 74544528.51 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133451E+09 | 0.160056E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.232262E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7425908.28 | 0.696626E+09 |
February | 0.415303E+11 | 0.207615E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758697E+09 |
March | 0.461508E+11 | 0.221234E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14010436.62 | 0.655690E+09 |
April | 0.445315E+11 | 0.205172E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156068E+09 | 0.217340E+09 |
May | 0.460320E+11 | 0.205514E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266077E+09 | 0.113398E+09 |
June | 0.446286E+11 | 0.192029E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499916E+09 | 19981942.37 |
July | 0.459349E+11 | 0.200786E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458977E+09 | 12889068.32 |
August | 0.461292E+11 | 0.213003E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422732E+09 | 20030718.08 |
September | 0.445099E+11 | 0.209741E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292732E+09 | 42741579.62 |
October | 0.459565E+11 | 0.227261E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108870E+09 | 0.349955E+09 |
November | 0.444343E+11 | 0.223592E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11378669.55 | 0.632573E+09 |
December | 0.459349E+11 | 0.232388E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2176491.03 | 0.912996E+09 |
Annual Sum or Average | 0.541708E+12 | 0.257060E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224036E+10 | 0.443292E+10 |
Minimum of Months | 0.415303E+11 | 0.192029E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12889068.32 |
Maximum of Months | 0.461508E+11 | 0.232388E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499916E+09 | 0.912996E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.232262E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6222733.75 | 0.703983E+09 |
February | 0.415303E+11 | 0.207615E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768105E+09 |
March | 0.461508E+11 | 0.221234E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13180179.67 | 0.662953E+09 |
April | 0.445315E+11 | 0.205172E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154948E+09 | 0.218083E+09 |
May | 0.460320E+11 | 0.205514E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265500E+09 | 0.113436E+09 |
June | 0.446286E+11 | 0.192029E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499838E+09 | 19982450.37 |
July | 0.459349E+11 | 0.200786E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458894E+09 | 12889492.48 |
August | 0.461292E+11 | 0.213003E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422556E+09 | 20034763.82 |
September | 0.445099E+11 | 0.209741E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292327E+09 | 42775793.98 |
October | 0.459565E+11 | 0.227261E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107852E+09 | 0.352754E+09 |
November | 0.444343E+11 | 0.223592E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10185226.53 | 0.638840E+09 |
December | 0.459349E+11 | 0.232388E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1678346.04 | 0.923674E+09 |
Annual Sum or Average | 0.541708E+12 | 0.257060E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223318E+10 | 0.447751E+10 |
Minimum of Months | 0.415303E+11 | 0.192029E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12889492.48 |
Maximum of Months | 0.461508E+11 | 0.232388E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499838E+09 | 0.923674E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.101925E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 4982205.78 | 0.624045E+09 |
February | 0.369574E+10 | 0.920291E+09 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684533E+09 |
March | 0.410691E+10 | 0.102239E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 11441414.55 | 0.587864E+09 |
April | 0.396281E+10 | 0.984694E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.138413E+09 | 0.191389E+09 |
May | 0.409635E+10 | 0.102102E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.237715E+09 | 99160337.68 |
June | 0.397146E+10 | 0.989210E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.447688E+09 | 17571945.37 |
July | 0.408770E+10 | 0.101650E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.411070E+09 | 11269289.80 |
August | 0.410499E+10 | 0.102279E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.378497E+09 | 17422158.68 |
September | 0.396089E+10 | 0.985086E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.261771E+09 | 37325929.80 |
October | 0.408962E+10 | 0.101886E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 96178124.06 | 0.311879E+09 |
November | 0.395417E+10 | 0.988424E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 8416271.90 | 0.565625E+09 |
December | 0.408770E+10 | 0.101650E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 1224665.42 | 0.821882E+09 |
Annual Sum or Average | 0.482060E+11 | 0.120050E+11 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.199740E+10 | 0.396997E+10 |
Minimum of Months | 0.369574E+10 | 0.920291E+09 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11269289.80 |
Maximum of Months | 0.410691E+10 | 0.102279E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.447688E+09 | 0.821882E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.114712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11788514.50 | 0.493772E+09 |
February | 0.368610E+10 | 0.103575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1624.22 | 0.528166E+09 |
March | 0.409620E+10 | 0.115066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19714328.61 | 0.452064E+09 |
April | 0.395248E+10 | 0.110823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147064E+09 | 0.157606E+09 |
May | 0.408566E+10 | 0.114911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239051E+09 | 83864462.01 |
June | 0.396110E+10 | 0.111331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439327E+09 | 14995444.10 |
July | 0.407704E+10 | 0.114403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404063E+09 | 9489850.67 |
August | 0.409429E+10 | 0.115110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373344E+09 | 13856776.15 |
September | 0.395056E+10 | 0.110867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259451E+09 | 30413241.14 |
October | 0.407896E+10 | 0.114668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101320E+09 | 0.248139E+09 |
November | 0.394385E+10 | 0.111243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14930252.95 | 0.445830E+09 |
December | 0.407704E+10 | 0.114403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3992340.18 | 0.657068E+09 |
Annual Sum or Average | 0.480803E+11 | 0.135111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201405E+10 | 0.313526E+10 |
Minimum of Months | 0.368610E+10 | 0.103575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1624.22 | 9489850.67 |
Maximum of Months | 0.409620E+10 | 0.115110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439327E+09 | 0.657068E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 8344.11 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 8344.11 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 8344.11 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 8344.11 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 8344.11 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 8344.11 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 8344.11 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 8344.11 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 8344.11 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 8344.11 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 8344.11 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 8344.11 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 8344.11 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 8344.11 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 461.08 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.54 | 31-JAN-16:00 | 427.08 | 01-JAN-08:00 |
February | 1169.53 | 01-FEB-00:10 | 461.08 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.25 | 18-FEB-16:00 | 327.81 | 28-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 461.08 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.43 | 20-MAR-17:00 | 425.65 | 26-MAR-06:00 |
April | 1169.53 | 01-APR-00:10 | 461.08 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.53 | 14-APR-16:00 | 262.88 | 21-APR-04:03 |
May | 1169.53 | 01-MAY-00:10 | 461.08 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.26 | 31-MAY-17:00 | 199.62 | 01-MAY-04:00 |
June | 1169.53 | 01-JUN-00:10 | 461.08 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 325.11 | 28-JUN-16:00 | 95.70 | 21-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 461.08 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.68 | 19-JUL-13:00 | 99.42 | 01-JUL-05:55 |
August | 1169.53 | 01-AUG-00:10 | 461.08 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.44 | 25-AUG-14:00 | 114.89 | 05-AUG-18:00 |
September | 1169.53 | 01-SEP-00:10 | 461.08 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.26 | 08-SEP-15:00 | 108.75 | 22-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 461.08 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.13 | 01-OCT-13:00 | 325.80 | 25-OCT-07:00 |
November | 1169.53 | 01-NOV-00:10 | 461.08 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.14 | 01-NOV-15:00 | 438.27 | 23-NOV-06:40 |
December | 1169.53 | 01-DEC-00:10 | 461.08 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.51 | 02-DEC-15:00 | 460.74 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 461.08 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 2.25 | 95.70 | |||||
Maximum of Months | 1169.53 | 461.08 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 325.11 | 460.74 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 533.93 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.80 | 31-JAN-16:00 | 173.11 | 01-JAN-08:00 |
February | 1354.32 | 01-FEB-00:10 | 533.93 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 143.12 | 01-FEB-05:30 |
March | 1354.32 | 01-MAR-00:10 | 533.93 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.71 | 20-MAR-17:00 | 172.68 | 26-MAR-04:00 |
April | 1354.32 | 01-APR-00:10 | 533.93 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.62 | 14-APR-15:00 | 120.14 | 21-APR-04:30 |
May | 1354.32 | 01-MAY-00:10 | 533.93 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.93 | 15-MAY-17:00 | 90.77 | 01-MAY-04:00 |
June | 1354.32 | 01-JUN-00:10 | 533.93 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.50 | 28-JUN-16:00 | 45.02 | 21-JUN-06:00 |
July | 1354.32 | 01-JUL-00:10 | 533.93 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.48 | 19-JUL-13:00 | 45.35 | 01-JUL-06:00 |
August | 1354.32 | 01-AUG-00:10 | 533.93 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.60 | 25-AUG-14:00 | 52.08 | 05-AUG-18:00 |
September | 1354.32 | 01-SEP-00:10 | 533.93 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.23 | 08-SEP-15:00 | 54.93 | 22-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 533.93 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.45 | 01-OCT-13:00 | 141.04 | 25-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 533.93 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.59 | 01-NOV-15:00 | 182.92 | 23-NOV-06:20 |
December | 1354.32 | 01-DEC-00:10 | 533.93 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 21-DEC-15:00 | 188.94 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 533.93 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.02 | |||||
Maximum of Months | 1354.32 | 533.93 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 125.50 | 188.94 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 615.76 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.12 | 31-JAN-16:50 | 389.61 | 01-JAN-08:00 |
February | 286.42 | 01-FEB-00:10 | 615.76 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.97 | 18-FEB-14:00 | 310.80 | 01-FEB-07:30 |
March | 286.42 | 01-MAR-00:10 | 615.76 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.75 | 16-MAR-15:40 | 388.26 | 26-MAR-06:00 |
April | 286.42 | 01-APR-00:10 | 615.76 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.12 | 14-APR-15:50 | 264.19 | 21-APR-04:30 |
May | 286.42 | 01-MAY-00:10 | 615.76 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.79 | 15-MAY-17:00 | 201.41 | 01-MAY-04:00 |
June | 286.42 | 01-JUN-00:10 | 615.76 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 296.59 | 28-JUN-16:00 | 106.42 | 21-JUN-06:00 |
July | 286.42 | 01-JUL-00:10 | 615.76 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.00 | 19-JUL-13:00 | 107.18 | 01-JUL-06:00 |
August | 286.42 | 01-AUG-00:10 | 615.76 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.29 | 25-AUG-14:00 | 121.25 | 05-AUG-18:00 |
September | 286.42 | 01-SEP-00:10 | 615.76 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.25 | 08-SEP-15:00 | 125.19 | 22-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 615.76 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.17 | 01-OCT-13:00 | 315.03 | 25-OCT-06:20 |
November | 286.42 | 01-NOV-00:10 | 615.76 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.92 | 01-NOV-15:00 | 406.87 | 23-NOV-06:10 |
December | 286.42 | 01-DEC-00:10 | 615.76 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.92 | 21-DEC-15:00 | 420.31 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 11.97 | 106.42 | |||||
Maximum of Months | 286.42 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 296.59 | 420.31 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 137.35 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.45 | 31-JAN-17:00 | 224.79 | 01-JAN-08:00 |
February | 220.32 | 01-FEB-00:10 | 137.35 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 18-FEB-14:00 | 177.42 | 01-FEB-05:20 |
March | 220.32 | 01-MAR-00:10 | 137.35 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.62 | 20-MAR-17:00 | 224.01 | 26-MAR-06:00 |
April | 220.32 | 01-APR-00:10 | 137.35 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.22 | 14-APR-16:30 | 150.54 | 21-APR-04:03 |
May | 220.32 | 01-MAY-00:10 | 137.35 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.86 | 15-MAY-17:00 | 114.63 | 01-MAY-04:00 |
June | 220.32 | 01-JUN-00:10 | 137.35 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.12 | 28-JUN-16:00 | 59.91 | 21-JUN-06:00 |
July | 220.32 | 01-JUL-00:10 | 137.35 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.05 | 19-JUL-13:00 | 61.57 | 01-JUL-06:00 |
August | 220.32 | 01-AUG-00:10 | 137.35 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.87 | 25-AUG-14:00 | 67.16 | 05-AUG-18:00 |
September | 220.32 | 01-SEP-00:10 | 137.35 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.04 | 08-SEP-15:00 | 69.88 | 22-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 137.35 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.61 | 01-OCT-13:00 | 179.17 | 25-OCT-06:00 |
November | 220.32 | 01-NOV-00:10 | 137.35 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.39 | 01-NOV-15:00 | 232.52 | 23-NOV-06:03 |
December | 220.32 | 01-DEC-00:10 | 137.35 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.28 | 21-DEC-15:00 | 242.50 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 137.35 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 59.91 | |||||
Maximum of Months | 220.32 | 137.35 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 171.12 | 242.50 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 360.62 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 148.85 | 31-JAN-17:00 | 609.69 | 01-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 360.62 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 484.68 | 28-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 360.62 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 150.89 | 20-MAR-17:00 | 596.61 | 26-MAR-06:10 |
April | 907.20 | 01-APR-00:10 | 360.62 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 289.69 | 14-APR-17:00 | 396.09 | 21-APR-05:10 |
May | 907.20 | 01-MAY-00:10 | 360.62 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 335.20 | 15-MAY-17:00 | 272.62 | 01-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 360.62 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 443.25 | 28-JUN-17:00 | 145.30 | 21-JUN-06:00 |
July | 907.20 | 01-JUL-00:10 | 360.62 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 386.53 | 19-JUL-13:00 | 146.19 | 01-JUL-06:00 |
August | 907.20 | 01-AUG-00:10 | 360.62 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 423.43 | 25-AUG-17:00 | 171.48 | 05-AUG-18:00 |
September | 907.20 | 01-SEP-00:10 | 360.62 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 359.69 | 08-SEP-16:00 | 181.23 | 22-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 360.62 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 330.03 | 01-OCT-13:00 | 481.96 | 25-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 360.62 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 138.59 | 01-NOV-15:20 | 611.64 | 23-NOV-07:10 |
December | 907.20 | 01-DEC-00:10 | 360.62 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 81.66 | 25-DEC-16:00 | 651.81 | 05-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 145.30 | ||||||
Maximum of Months | 907.20 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 443.25 | 651.81 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1416.11 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.06 | 31-JAN-17:00 | 999.63 | 01-JAN-08:00 |
February | 15368.40 | 01-FEB-00:10 | 1416.11 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 834.52 | 01-FEB-05:20 |
March | 15368.40 | 01-MAR-00:10 | 1416.11 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.83 | 20-MAR-17:00 | 971.02 | 26-MAR-04:00 |
April | 15368.40 | 01-APR-00:10 | 1416.11 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 447.80 | 14-APR-16:00 | 688.86 | 21-APR-04:10 |
May | 15368.40 | 01-MAY-00:10 | 1416.11 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 526.79 | 31-MAY-17:00 | 525.90 | 01-MAY-04:00 |
June | 15368.40 | 01-JUN-00:10 | 1416.11 | 01-JUN-19:19 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 718.77 | 28-JUN-16:00 | 257.37 | 21-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1416.11 | 03-JUL-19:30 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 647.02 | 19-JUL-13:00 | 259.63 | 01-JUL-06:00 |
August | 15368.40 | 01-AUG-00:10 | 1416.11 | 01-AUG-19:19 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 684.06 | 25-AUG-14:00 | 276.73 | 05-AUG-18:00 |
September | 15368.40 | 01-SEP-00:10 | 1416.11 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 579.79 | 08-SEP-15:00 | 307.56 | 22-SEP-06:00 |
October | 15368.40 | 01-OCT-23:10 | 1416.11 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 528.65 | 01-OCT-13:00 | 796.14 | 25-OCT-06:00 |
November | 15368.40 | 01-NOV-00:10 | 1416.11 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.21 | 01-NOV-15:00 | 1023.37 | 23-NOV-06:10 |
December | 15368.40 | 01-DEC-00:10 | 1416.11 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.41 | 21-DEC-15:00 | 1098.67 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1416.11 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.37 | |||||
Maximum of Months | 15368.40 | 1416.11 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 718.77 | 1098.67 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9580.84 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 612.33 | 31-JAN-16:00 | 2932.62 | 01-JAN-08:00 |
February | 45622.98 | 01-FEB-00:10 | 9580.84 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2431.45 | 01-FEB-05:40 |
March | 45622.98 | 01-MAR-00:10 | 9580.84 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 654.52 | 20-MAR-17:00 | 2902.88 | 26-MAR-06:00 |
April | 45622.98 | 01-APR-00:10 | 9580.84 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1289.08 | 14-APR-17:00 | 2033.17 | 21-APR-04:30 |
May | 45622.98 | 01-MAY-00:10 | 9580.84 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1536.16 | 15-MAY-17:00 | 1511.59 | 01-MAY-04:00 |
June | 45622.98 | 01-JUN-00:10 | 9580.84 | 01-JUN-19:19 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2053.54 | 28-JUN-16:00 | 736.66 | 21-JUN-06:00 |
July | 45622.98 | 01-JUL-00:10 | 9580.84 | 03-JUL-19:30 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1879.65 | 19-JUL-13:00 | 741.96 | 01-JUL-06:00 |
August | 45622.98 | 01-AUG-00:10 | 9580.84 | 01-AUG-19:19 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1956.82 | 26-AUG-16:00 | 869.18 | 05-AUG-18:00 |
September | 45622.98 | 01-SEP-00:10 | 9580.84 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1656.52 | 08-SEP-15:00 | 919.03 | 22-SEP-06:00 |
October | 45622.98 | 01-OCT-23:10 | 9580.84 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1533.81 | 01-OCT-13:00 | 2388.01 | 25-OCT-06:00 |
November | 45622.98 | 01-NOV-00:10 | 9580.84 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 594.80 | 01-NOV-15:00 | 3054.04 | 23-NOV-06:40 |
December | 45622.98 | 01-DEC-00:10 | 9580.84 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.05 | 21-DEC-15:00 | 3209.25 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9580.84 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 736.66 | |||||
Maximum of Months | 45622.98 | 9580.84 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 2053.54 | 3209.25 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.87 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.12 | 31-JAN-17:00 | 249.74 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 106.87 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 18-FEB-16:10 | 192.07 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 106.87 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.58 | 16-MAR-15:10 | 248.88 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 106.87 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.98 | 14-APR-16:00 | 154.25 | 21-APR-04:07 |
May | 180.00 | 01-MAY-00:10 | 106.87 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.58 | 31-MAY-17:00 | 105.99 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 106.87 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.30 | 16-JUN-16:00 | 35.60 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 106.87 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.65 | 20-JUL-15:10 | 35.86 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 106.87 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.48 | 25-AUG-15:10 | 72.79 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 106.87 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.23 | 08-SEP-16:00 | 52.00 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 106.87 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.37 | 03-OCT-16:00 | 190.93 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 106.87 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.99 | 01-NOV-15:10 | 256.21 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 106.87 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.89 | 25-DEC-16:07 | 269.28 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 35.60 | |||||
Maximum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 218.30 | 269.28 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.85 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.12 | 31-JAN-16:50 | 249.72 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 106.85 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 18-FEB-16:10 | 192.06 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 106.85 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.57 | 16-MAR-15:07 | 248.85 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 106.85 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.97 | 14-APR-16:00 | 154.24 | 21-APR-04:07 |
May | 180.00 | 01-MAY-00:10 | 106.85 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.57 | 31-MAY-17:00 | 105.98 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 106.85 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.28 | 16-JUN-16:00 | 56.75 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 106.85 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.71 | 20-JUL-15:10 | 56.23 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 106.85 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.47 | 25-AUG-15:10 | 72.36 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 106.85 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.43 | 08-SEP-15:10 | 61.17 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 106.85 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.36 | 03-OCT-16:00 | 190.91 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 106.85 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.98 | 01-NOV-15:10 | 256.19 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 106.85 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.88 | 25-DEC-16:07 | 269.26 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 56.23 | |||||
Maximum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 218.28 | 269.26 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 67.16 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.01 | 31-JAN-16:00 | 83.98 | 01-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 67.16 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 71.77 | 01-FEB-08:00 |
March | 0.00 | 01-MAR-00:10 | 67.16 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.37 | 16-MAR-15:00 | 81.05 | 26-MAR-04:00 |
April | 0.00 | 01-APR-00:10 | 67.16 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.72 | 14-APR-15:00 | 58.81 | 21-APR-04:00 |
May | 0.00 | 01-MAY-00:10 | 67.16 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.54 | 31-MAY-17:00 | 47.23 | 01-MAY-04:00 |
June | 0.00 | 01-JUN-00:10 | 67.16 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.72 | 28-JUN-16:00 | 27.42 | 21-JUN-06:00 |
July | 0.00 | 01-JUL-00:10 | 67.16 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.37 | 19-JUL-13:00 | 27.62 | 01-JUL-05:55 |
August | 0.00 | 01-AUG-00:10 | 67.16 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.12 | 25-AUG-14:00 | 30.92 | 05-AUG-18:00 |
September | 0.00 | 01-SEP-00:10 | 67.16 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.42 | 08-SEP-15:00 | 32.20 | 22-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 67.16 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.65 | 01-OCT-13:00 | 71.27 | 25-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 67.16 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.98 | 01-NOV-15:00 | 85.78 | 23-NOV-06:20 |
December | 0.00 | 01-DEC-00:10 | 67.16 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 89.26 | 05-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 67.16 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.42 | |||||
Maximum of Months | 0.00 | 67.16 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 44.72 | 89.26 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 67.18 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.04 | 31-JAN-16:40 | 69.70 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 67.18 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 | 18-FEB-16:09 | 53.60 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 67.18 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 16-MAR-15:10 | 69.46 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 67.18 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.30 | 14-APR-15:50 | 43.05 | 21-APR-04:07 |
May | 180.00 | 01-MAY-00:10 | 67.18 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.05 | 31-MAY-17:00 | 29.58 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 67.18 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.99 | 28-JUN-16:00 | 14.30 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 67.18 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.21 | 20-JUL-15:10 | 13.32 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 67.18 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.46 | 25-AUG-15:50 | 18.28 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 67.18 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.93 | 08-SEP-15:10 | 17.01 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 67.18 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.41 | 03-OCT-16:00 | 53.29 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 67.18 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.44 | 01-NOV-15:09 | 71.51 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 67.18 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.92 | 25-DEC-16:07 | 75.15 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 67.18 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 | 13.32 | |||||
Maximum of Months | 180.00 | 67.18 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 60.99 | 75.15 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.87 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.13 | 31-JAN-17:00 | 249.74 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 106.87 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 18-FEB-16:07 | 192.07 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 106.87 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.58 | 16-MAR-15:07 | 248.88 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 106.87 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.98 | 14-APR-15:10 | 154.25 | 21-APR-04:07 |
May | 180.00 | 01-MAY-00:10 | 106.87 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.58 | 31-MAY-17:00 | 105.99 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 106.87 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.50 | 28-JUN-16:00 | 35.60 | 21-JUN-05:55 |
July | 180.00 | 01-JUL-00:10 | 106.87 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.68 | 20-JUL-15:10 | 35.86 | 01-JUL-05:55 |
August | 180.00 | 01-AUG-00:10 | 106.87 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.48 | 25-AUG-15:50 | 72.79 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 106.87 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.30 | 08-SEP-15:50 | 52.00 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 106.87 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.37 | 03-OCT-16:00 | 190.93 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 106.87 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.99 | 01-NOV-15:10 | 256.21 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 106.87 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.89 | 25-DEC-16:10 | 269.28 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 35.60 | |||||
Maximum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 218.50 | 269.28 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.85 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.12 | 31-JAN-16:50 | 249.72 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 106.85 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 18-FEB-16:10 | 192.06 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 106.85 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.57 | 16-MAR-15:07 | 248.86 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 106.85 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.97 | 14-APR-16:00 | 154.24 | 21-APR-04:07 |
May | 180.00 | 01-MAY-00:10 | 106.85 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.55 | 31-MAY-17:00 | 105.98 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 106.85 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.47 | 28-JUN-16:10 | 63.63 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 106.85 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.73 | 20-JUL-15:10 | 60.68 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 106.85 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.47 | 25-AUG-15:10 | 73.84 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 106.85 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.47 | 08-SEP-15:10 | 61.14 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 106.85 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.36 | 03-OCT-16:00 | 190.91 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 106.85 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.98 | 01-NOV-15:07 | 256.19 | 23-NOV-06:07 |
December | 180.00 | 01-DEC-00:10 | 106.85 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.88 | 25-DEC-16:07 | 269.26 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 60.68 | |||||
Maximum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 218.47 | 269.26 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1044.00 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.81 | 31-JAN-16:00 | 300.38 | 01-JAN-08:00 |
February | 2263.36 | 01-FEB-00:10 | 1044.00 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.82 | 18-FEB-14:00 | 248.21 | 01-FEB-05:03 |
March | 2263.36 | 01-MAR-00:10 | 1044.00 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.94 | 16-MAR-15:00 | 304.16 | 26-MAR-04:00 |
April | 2263.36 | 01-APR-00:10 | 1044.00 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.86 | 14-APR-17:00 | 211.63 | 21-APR-04:03 |
May | 2263.36 | 01-MAY-00:10 | 1044.00 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.44 | 15-MAY-17:00 | 157.84 | 01-MAY-04:00 |
June | 2263.36 | 01-JUN-00:10 | 1044.00 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.64 | 28-JUN-16:00 | 81.05 | 21-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1044.00 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.87 | 19-JUL-13:00 | 82.17 | 01-JUL-06:00 |
August | 2263.36 | 01-AUG-00:10 | 1044.00 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.63 | 25-AUG-14:00 | 91.49 | 05-AUG-18:00 |
September | 2263.36 | 01-SEP-00:10 | 1044.00 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.52 | 08-SEP-15:00 | 95.72 | 22-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 1044.00 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.46 | 01-OCT-13:00 | 246.71 | 25-OCT-06:00 |
November | 2263.36 | 01-NOV-00:10 | 1044.00 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.87 | 01-NOV-15:00 | 321.75 | 23-NOV-06:00 |
December | 2263.36 | 01-DEC-00:10 | 1044.00 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.20 | 21-DEC-15:00 | 330.28 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1044.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.82 | 81.05 | ||||
Maximum of Months | 2263.36 | 1044.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.64 | 330.28 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.87 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.49 | 31-JAN-17:00 | 250.50 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 106.87 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.04 | 18-FEB-16:07 | 192.82 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 106.87 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.95 | 16-MAR-15:10 | 249.65 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 106.87 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.36 | 14-APR-15:10 | 154.98 | 21-APR-04:07 |
May | 180.00 | 01-MAY-00:10 | 106.87 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.98 | 31-MAY-17:00 | 106.70 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 106.87 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.72 | 16-JUN-16:00 | 36.28 | 21-JUN-05:55 |
July | 180.00 | 01-JUL-00:10 | 106.87 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.03 | 20-JUL-15:10 | 36.54 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 106.87 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.89 | 25-AUG-15:10 | 71.68 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 106.87 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.56 | 08-SEP-16:00 | 52.68 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 106.87 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.76 | 03-OCT-16:00 | 191.67 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 106.87 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.34 | 01-NOV-15:10 | 256.99 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 106.87 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.24 | 25-DEC-16:07 | 270.06 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 5.04 | 36.28 | |||||
Maximum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 217.72 | 270.06 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.85 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.48 | 31-JAN-16:50 | 250.49 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 106.85 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.04 | 18-FEB-16:07 | 192.80 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 106.85 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.94 | 16-MAR-15:10 | 249.63 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 106.85 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.36 | 14-APR-16:00 | 154.96 | 21-APR-04:07 |
May | 180.00 | 01-MAY-00:10 | 106.85 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.97 | 31-MAY-17:00 | 106.69 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 106.85 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.71 | 16-JUN-16:00 | 53.19 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 106.85 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.63 | 20-JUL-15:10 | 53.16 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 106.85 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.87 | 25-AUG-15:10 | 70.84 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 106.85 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.65 | 08-SEP-16:00 | 56.88 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 106.85 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.75 | 03-OCT-16:00 | 191.65 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 106.85 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.35 | 01-NOV-15:10 | 256.97 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 106.85 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.24 | 25-DEC-16:07 | 270.04 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 5.04 | 53.16 | |||||
Maximum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 217.71 | 270.04 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 67.18 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.74 | 31-JAN-17:00 | 128.17 | 01-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 67.18 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 18-FEB-16:09 | 98.65 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 67.18 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.44 | 16-MAR-15:10 | 127.73 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 67.18 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.40 | 14-APR-16:00 | 79.29 | 21-APR-04:10 |
May | 180.00 | 01-MAY-00:10 | 67.18 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.94 | 31-MAY-17:00 | 54.59 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 67.18 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.49 | 28-JUN-16:10 | 18.56 | 21-JUN-05:55 |
July | 180.00 | 01-JUL-00:10 | 67.18 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.71 | 20-JUL-15:10 | 18.69 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 67.18 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.88 | 25-AUG-16:30 | 35.49 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 67.18 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.95 | 08-SEP-16:00 | 26.96 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 67.18 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.60 | 03-OCT-16:00 | 98.07 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 67.18 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.79 | 01-NOV-15:10 | 131.48 | 23-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 67.18 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.19 | 25-DEC-16:10 | 138.17 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 67.18 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 18.56 | |||||
Maximum of Months | 180.00 | 67.18 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 111.49 | 138.17 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2486.81 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.14 | 31-JAN-16:00 | 696.84 | 01-JAN-08:00 |
February | 26988.77 | 01-FEB-00:10 | 2486.81 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 554.58 | 28-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2486.81 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.45 | 16-MAR-15:00 | 692.14 | 26-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 2486.81 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.51 | 14-APR-16:00 | 461.06 | 21-APR-04:10 |
May | 26988.77 | 01-MAY-00:10 | 2486.81 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 335.17 | 31-MAY-17:00 | 342.03 | 01-MAY-04:00 |
June | 26988.77 | 01-JUN-00:10 | 2486.81 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 458.32 | 28-JUN-16:00 | 168.09 | 21-JUN-06:00 |
July | 26988.77 | 01-JUL-00:10 | 2486.81 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 412.26 | 19-JUL-13:00 | 169.30 | 01-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 2486.81 | 01-AUG-19:19 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 436.03 | 25-AUG-14:00 | 197.89 | 05-AUG-18:00 |
September | 26988.77 | 01-SEP-00:10 | 2486.81 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 369.15 | 08-SEP-15:00 | 209.03 | 22-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2486.81 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 336.35 | 01-OCT-13:00 | 551.16 | 25-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2486.81 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.81 | 01-NOV-15:00 | 712.77 | 23-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 2486.81 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.51 | 21-DEC-15:00 | 745.00 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2486.81 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.09 | |||||
Maximum of Months | 26988.77 | 2486.81 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 458.32 | 745.00 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2486.81 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.35 | 31-JAN-17:00 | 696.85 | 01-JAN-08:00 |
February | 26988.77 | 01-FEB-00:10 | 2486.81 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 554.59 | 28-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 2486.81 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.45 | 16-MAR-15:00 | 694.46 | 26-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 2486.81 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.51 | 14-APR-16:00 | 461.06 | 21-APR-04:10 |
May | 26988.77 | 01-MAY-00:10 | 2486.81 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 335.17 | 31-MAY-17:00 | 342.04 | 01-MAY-04:00 |
June | 26988.77 | 01-JUN-00:10 | 2486.81 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 458.32 | 28-JUN-16:00 | 168.09 | 21-JUN-06:00 |
July | 26988.77 | 01-JUL-00:10 | 2486.81 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 412.26 | 19-JUL-13:00 | 169.30 | 01-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 2486.81 | 01-AUG-19:19 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 436.03 | 25-AUG-14:00 | 197.89 | 05-AUG-18:00 |
September | 26988.77 | 01-SEP-00:10 | 2486.81 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 369.15 | 08-SEP-15:00 | 209.03 | 22-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2486.81 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 336.35 | 01-OCT-13:00 | 551.16 | 25-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2486.81 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.81 | 01-NOV-15:00 | 712.81 | 23-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 2486.81 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.48 | 21-DEC-15:00 | 745.01 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2486.81 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.09 | |||||
Maximum of Months | 26988.77 | 2486.81 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 458.32 | 745.01 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 981.75 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 117.91 | 31-JAN-16:40 | 623.67 | 01-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 981.75 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 496.39 | 28-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 981.75 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 112.57 | 16-MAR-15:40 | 621.55 | 26-MAR-06:00 |
April | 2401.70 | 01-APR-00:10 | 981.75 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 255.03 | 14-APR-15:40 | 412.75 | 21-APR-04:07 |
May | 2401.70 | 01-MAY-00:10 | 981.75 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 300.36 | 31-MAY-17:00 | 296.66 | 01-MAY-04:00 |
June | 2401.70 | 01-JUN-00:10 | 981.75 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 410.59 | 28-JUN-16:00 | 150.38 | 21-JUN-05:55 |
July | 2401.70 | 01-JUL-00:10 | 981.75 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 369.30 | 19-JUL-13:00 | 151.45 | 01-JUL-06:00 |
August | 2401.70 | 01-AUG-00:10 | 981.75 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 390.54 | 25-AUG-14:00 | 176.87 | 05-AUG-18:00 |
September | 2401.70 | 01-SEP-00:10 | 981.75 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 330.69 | 08-SEP-15:00 | 187.03 | 22-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 981.75 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 301.36 | 01-OCT-13:00 | 493.40 | 25-OCT-06:10 |
November | 2401.70 | 01-NOV-00:10 | 981.75 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 117.33 | 01-NOV-15:00 | 637.98 | 23-NOV-07:00 |
December | 2401.70 | 01-DEC-00:10 | 981.75 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 46.21 | 21-DEC-15:00 | 666.80 | 05-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 981.75 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 150.38 | ||||||
Maximum of Months | 2401.70 | 981.75 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 410.59 | 666.80 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1104.91 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.53 | 31-JAN-17:00 | 533.14 | 01-JAN-08:00 |
February | 2395.44 | 01-FEB-00:10 | 1104.91 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 | 18-FEB-14:00 | 422.52 | 01-FEB-05:03 |
March | 2395.44 | 01-MAR-00:10 | 1104.91 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.67 | 15-MAR-15:00 | 531.29 | 26-MAR-06:00 |
April | 2395.44 | 01-APR-00:10 | 1104.91 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.22 | 14-APR-15:00 | 353.06 | 21-APR-04:00 |
May | 2395.44 | 01-MAY-00:10 | 1104.91 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.60 | 31-MAY-17:00 | 271.55 | 01-MAY-04:00 |
June | 2395.44 | 01-JUN-00:10 | 1104.91 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.51 | 28-JUN-16:00 | 135.30 | 21-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1104.91 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 361.19 | 19-JUL-13:00 | 139.32 | 01-JUL-05:55 |
August | 2395.44 | 01-AUG-00:10 | 1104.91 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.02 | 25-AUG-14:00 | 161.95 | 05-AUG-18:00 |
September | 2395.44 | 01-SEP-00:10 | 1104.91 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.41 | 08-SEP-15:00 | 157.46 | 22-SEP-06:00 |
October | 2395.44 | 01-OCT-23:10 | 1104.91 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.67 | 01-OCT-13:00 | 414.95 | 25-OCT-06:00 |
November | 2395.44 | 01-NOV-00:10 | 1104.91 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.07 | 01-NOV-15:00 | 546.98 | 23-NOV-06:40 |
December | 2395.44 | 01-DEC-00:10 | 1104.91 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.49 | 21-DEC-15:00 | 574.93 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1104.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 | 135.30 | ||||
Maximum of Months | 2395.44 | 1104.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.51 | 574.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 14006.18 | 20-JAN-22:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12045.86 | 01-FEB-22:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10688.80 | 01-MAR-21:00 | 8945.92 | 8344.11 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11953.78 | 30-APR-10:33 | 11501.89 | 8343.99 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11598.97 | 04-MAY-18:10 | 62621.41 | 51919.01 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12622.55 | 28-JUN-18:10 | 44729.58 | 37085.01 | 45627.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16060.55 | 14-JUL-21:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18522.66 | 04-AUG-21:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21680.88 | 20-SEP-21:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21257.09 | 19-OCT-21:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20936.10 | 22-NOV-22:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20099.51 | 01-DEC-22:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 10688.80 | 8945.92 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21680.88 | 62621.41 | 51919.01 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3521.93 | 14-JAN-13:40 | 389.84 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 50.93 | 0.00 |
February | 2491.68 | 01-FEB-14:00 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.44 |
March | 2656.38 | 18-MAR-13:40 | 389.84 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 43.31 | 0.00 |
April | 3114.38 | 14-APR-14:10 | 389.84 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 187.86 | 0.00 |
May | 2625.40 | 31-MAY-18:15 | 1819.27 | 819.70 | 1299.04 | 0.00 | 0.00 | 0.00 | 0.00 | 208.52 | 0.00 |
June | 3504.82 | 28-JUN-18:13 | 2728.91 | 1229.55 | 1948.56 | 0.00 | 0.00 | 0.00 | 0.00 | 301.79 | 0.00 |
July | 3229.85 | 21-JUL-18:30 | 909.64 | 409.85 | 649.52 | 0.00 | 0.00 | 0.00 | 0.00 | 256.14 | 0.00 |
August | 3682.42 | 28-AUG-12:30 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 239.14 | 0.00 |
September | 3936.80 | 28-SEP-13:30 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 223.40 | 0.00 |
October | 3946.58 | 02-OCT-12:40 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 185.46 | 0.00 |
November | 3716.97 | 21-NOV-13:40 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 | 0.00 |
December | 3392.75 | 25-DEC-13:30 | 259.90 | 102.46 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 28.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2491.68 | 259.90 | 102.46 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3946.58 | 2728.91 | 1229.55 | 1948.56 | 0.00 | 0.00 | 0.00 | 0.00 | 301.79 | 157.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1544.21 | 27-JAN-21:10 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.57 |
February | 1288.98 | 01-FEB-21:00 | 1053.36 | 533.93 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.51 |
March | 1619.35 | 17-MAR-21:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.96 |
April | 2222.83 | 14-APR-20:40 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 40.89 | 0.00 |
May | 2175.68 | 19-MAY-20:10 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 48.15 | 0.00 |
June | 2550.53 | 28-JUN-20:40 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 82.75 | 0.00 |
July | 2403.65 | 20-JUL-20:10 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 79.66 | 0.00 |
August | 2447.72 | 15-AUG-20:10 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 76.07 | 0.00 |
September | 2399.50 | 07-SEP-21:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 66.93 | 0.00 |
October | 2197.55 | 05-OCT-20:10 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 18.24 | 0.00 |
November | 1848.56 | 01-NOV-20:10 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.19 |
December | 1443.37 | 26-DEC-22:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1288.98 | 1053.36 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2550.53 | 1203.84 | 533.93 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 82.75 | 99.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1087.04 | 08-JAN-11:33 | 286.42 | 615.76 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.48 |
February | 988.46 | 01-FEB-21:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.06 |
March | 1176.39 | 18-MAR-18:10 | 1145.66 | 2873.54 | 4241.42 | 0.00 | 0.00 | 0.00 | 0.00 | 44.63 | 0.00 |
April | 1512.28 | 14-APR-20:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 118.86 | 0.00 |
May | 1818.16 | 19-MAY-20:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 119.34 | 0.00 |
June | 2615.74 | 28-JUN-20:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 216.98 | 0.00 |
July | 2501.02 | 21-JUL-20:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 217.80 | 0.00 |
August | 2357.90 | 15-AUG-20:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 185.15 | 0.00 |
September | 2217.87 | 08-SEP-20:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 166.06 | 0.00 |
October | 1971.04 | 02-OCT-19:50 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 60.30 | 0.00 |
November | 1208.48 | 02-NOV-18:06 | 1559.38 | 3831.39 | 5566.86 | 0.00 | 0.00 | 0.00 | 0.00 | 15.02 | 0.00 |
December | 1026.93 | 26-DEC-21:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 988.46 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2615.74 | 1559.38 | 3831.39 | 5566.86 | 0.00 | 0.00 | 0.00 | 0.00 | 217.80 | 202.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 598.06 | 08-JAN-11:33 | 220.32 | 137.35 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.42 |
February | 540.79 | 18-FEB-11:33 | 220.32 | 114.47 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.54 |
March | 638.99 | 18-MAR-17:40 | 293.76 | 183.14 | 356.86 | 0.00 | 0.00 | 0.00 | 0.00 | 36.99 | 0.00 |
April | 769.58 | 15-APR-10:33 | 220.32 | 114.47 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 46.60 | 0.00 |
May | 801.72 | 31-MAY-18:10 | 1028.16 | 732.55 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 114.47 | 0.00 |
June | 1314.73 | 28-JUN-18:50 | 171.36 | 122.09 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 154.31 | 0.00 |
July | 1216.87 | 21-JUL-19:10 | 171.36 | 137.35 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 133.29 | 0.00 |
August | 1122.43 | 15-AUG-19:40 | 171.36 | 137.35 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 113.09 | 0.00 |
September | 1043.16 | 08-SEP-19:40 | 171.36 | 137.35 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 101.16 | 0.00 |
October | 889.18 | 03-OCT-21:00 | 195.84 | 122.09 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 59.32 | 0.00 |
November | 652.21 | 02-NOV-18:06 | 1199.52 | 854.64 | 1605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 10.53 | 0.00 |
December | 567.03 | 25-DEC-11:33 | 220.32 | 137.35 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 7.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 540.79 | 171.36 | 114.47 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1314.73 | 1199.52 | 854.64 | 1605.89 | 0.00 | 0.00 | 0.00 | 0.00 | 154.31 | 19.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37727.31 | 27-JAN-21:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 171.36 |
February | 37292.37 | 22-FEB-21:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 272.17 |
March | 38160.02 | 16-MAR-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 43.25 |
April | 39213.00 | 14-APR-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 162.25 | 0.00 |
May | 39332.35 | 18-MAY-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 140.29 | 0.00 |
June | 40074.74 | 28-JUN-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 296.31 | 0.00 |
July | 39896.83 | 21-JUL-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 297.40 | 0.00 |
August | 39772.08 | 15-AUG-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 252.80 | 0.00 |
September | 39593.85 | 08-SEP-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 226.76 | 0.00 |
October | 39148.75 | 03-OCT-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 140.16 | 0.00 |
November | 38119.13 | 01-NOV-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 72.33 |
December | 37400.89 | 22-DEC-21:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 247.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37292.37 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40074.74 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 297.40 | 272.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13769.61 | 14-JAN-13:30 | 5122.80 | 86.54 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 105.68 | 0.00 |
February | 10453.01 | 01-FEB-16:03 | 59766.00 | 605.78 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.11 |
March | 10784.06 | 16-MAR-15:15 | 17076.00 | 173.08 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 199.77 | 0.00 |
April | 12143.92 | 14-APR-21:10 | 15368.40 | 944.07 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 193.63 | 0.00 |
May | 11692.02 | 09-MAY-21:10 | 15368.40 | 944.07 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 200.84 | 0.00 |
June | 13321.30 | 28-JUN-21:10 | 15368.40 | 944.07 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 434.86 | 0.00 |
July | 13209.92 | 21-JUL-21:10 | 15368.40 | 944.07 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 403.94 | 0.00 |
August | 13104.78 | 15-AUG-21:10 | 15368.40 | 944.07 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 356.73 | 0.00 |
September | 13997.98 | 28-SEP-15:03 | 51228.00 | 519.24 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 548.10 | 0.00 |
October | 13924.86 | 05-OCT-15:03 | 51228.00 | 519.24 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 408.88 | 0.00 |
November | 14228.08 | 01-NOV-15:03 | 59766.00 | 605.78 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 201.28 | 0.00 |
December | 13279.69 | 25-DEC-13:00 | 5122.80 | 103.85 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 42.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10453.01 | 5122.80 | 86.54 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14228.08 | 59766.00 | 944.07 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 548.10 | 355.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35047.05 | 31-JAN-19:06 | 248391.78 | 59614.13 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.22 |
February | 30935.06 | 01-FEB-22:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1822.87 |
March | 35809.78 | 17-MAR-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.43 |
April | 42474.73 | 14-APR-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 552.99 | 0.00 |
May | 42018.62 | 09-MAY-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 573.59 | 0.00 |
June | 47581.75 | 28-JUN-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 1242.24 | 0.00 |
July | 46881.30 | 21-JUL-20:10 | 40553.76 | 8516.30 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1452.83 | 0.00 |
August | 46376.66 | 15-AUG-20:10 | 40553.76 | 8516.30 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1244.80 | 0.00 |
September | 46264.11 | 07-SEP-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 1032.21 | 0.00 |
October | 44172.60 | 03-OCT-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 653.74 | 0.00 |
November | 38443.39 | 01-NOV-20:10 | 40553.76 | 8516.30 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.36 |
December | 33991.72 | 26-DEC-22:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1147.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 30935.06 | 40553.76 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 47581.75 | 248391.78 | 59614.13 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 1452.83 | 1822.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3639.41 | 31-JAN-16:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 70.09 | 0.00 |
February | 3347.73 | 28-FEB-16:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.36 |
March | 3618.40 | 16-MAR-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 68.46 | 0.00 |
April | 3680.74 | 14-APR-18:01 | 970.20 | 665.78 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 115.61 | 0.00 |
May | 3658.00 | 03-MAY-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 113.57 | 0.00 |
June | 3696.87 | 27-JUN-18:02 | 831.60 | 570.67 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 179.69 | 0.00 |
July | 3676.15 | 05-JUL-18:02 | 831.60 | 570.67 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 160.99 | 0.00 |
August | 3681.43 | 26-AUG-15:02 | 324.00 | 211.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 192.58 | 0.00 |
September | 3680.18 | 28-SEP-15:02 | 583.20 | 179.54 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 157.66 | 0.00 |
October | 3674.36 | 15-OCT-15:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 90.50 | 0.00 |
November | 3664.81 | 20-NOV-16:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 45.77 | 0.00 |
December | 3610.89 | 25-DEC-16:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 33.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3347.73 | 324.00 | 179.54 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3696.87 | 970.20 | 665.78 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 192.58 | 40.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3557.33 | 31-JAN-16:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 71.89 | 0.00 |
February | 3268.37 | 28-FEB-16:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.53 |
March | 3561.89 | 16-MAR-15:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 69.44 | 0.00 |
April | 3705.07 | 26-APR-08:41 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 27.61 | 0.00 |
May | 4003.06 | 08-MAY-08:61 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 32.37 | 0.00 |
June | 4033.51 | 14-JUN-08:61 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 36.22 | 0.00 |
July | 4144.52 | 01-JUL-08:61 | 540.00 | 598.38 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 29.41 | 0.00 |
August | 3840.76 | 24-AUG-08:21 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 43.53 | 0.00 |
September | 3621.88 | 28-SEP-15:02 | 583.20 | 179.51 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 158.65 | 0.00 |
October | 3607.25 | 06-OCT-15:02 | 583.20 | 179.51 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 132.63 | 0.00 |
November | 3582.56 | 20-NOV-16:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 47.57 | 0.00 |
December | 3519.09 | 25-DEC-16:01 | 378.00 | 246.84 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 36.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3268.37 | 360.00 | 179.51 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4144.52 | 680.40 | 598.38 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 158.65 | 38.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 630.65 | 14-JAN-13:50 | 0.00 | 22.16 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | 0.00 |
February | 475.30 | 01-FEB-15:30 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.74 |
March | 447.12 | 18-MAR-14:10 | 0.00 | 22.16 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 |
April | 466.63 | 14-APR-13:40 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 21.85 | 0.00 |
May | 376.91 | 09-MAY-17:20 | 0.00 | 135.00 | 394.73 | 0.00 | 0.00 | 0.00 | 0.00 | 23.75 | 0.00 |
June | 473.91 | 28-JUN-17:15 | 0.00 | 90.00 | 263.15 | 0.00 | 0.00 | 0.00 | 0.00 | 43.73 | 0.00 |
July | 448.02 | 21-JUL-19:10 | 0.00 | 67.16 | 170.27 | 0.00 | 0.00 | 0.00 | 0.00 | 32.98 | 0.00 |
August | 536.82 | 27-AUG-14:00 | 0.00 | 22.16 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 39.15 | 0.00 |
September | 612.10 | 28-SEP-13:40 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 29.13 | 0.00 |
October | 632.37 | 18-OCT-13:50 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 12.54 | 0.00 |
November | 659.01 | 20-NOV-14:30 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 | 0.00 |
December | 624.13 | 25-DEC-13:40 | 0.00 | 22.16 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 376.91 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 659.01 | 0.00 | 135.00 | 394.73 | 0.00 | 0.00 | 0.00 | 0.00 | 43.73 | 35.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1195.62 | 27-JAN-16:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 13.74 | 0.00 |
February | 1065.68 | 09-FEB-16:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.21 |
March | 1232.00 | 15-MAR-18:01 | 970.20 | 418.53 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 11.61 | 0.00 |
April | 1237.46 | 12-APR-15:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 30.75 | 0.00 |
May | 1327.45 | 20-MAY-08:61 | 540.00 | 376.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 | 0.00 |
June | 1357.06 | 11-JUN-08:61 | 540.00 | 376.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 6.36 | 0.00 |
July | 1368.91 | 01-JUL-08:61 | 540.00 | 376.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 9.62 | 0.00 |
August | 1255.80 | 24-AUG-08:21 | 360.00 | 295.59 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 13.85 | 0.00 |
September | 1247.39 | 29-SEP-08:21 | 324.00 | 266.03 | 998.70 | 0.00 | 0.00 | 0.00 | 0.00 | 14.86 | 0.00 |
October | 1236.75 | 06-OCT-18:01 | 970.20 | 418.53 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 26.63 | 0.00 |
November | 1207.47 | 20-NOV-16:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 0.00 |
December | 1167.91 | 25-DEC-16:01 | 378.00 | 155.19 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1065.68 | 324.00 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1368.91 | 970.20 | 418.53 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 30.75 | 2.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3194.21 | 31-JAN-16:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 70.51 | 0.00 |
February | 2973.90 | 09-FEB-16:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.73 |
March | 3193.97 | 16-MAR-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 68.22 | 0.00 |
April | 3237.75 | 13-APR-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 121.61 | 0.00 |
May | 3294.33 | 17-MAY-08:61 | 360.00 | 470.21 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 47.10 | 0.00 |
June | 3290.67 | 14-JUN-08:61 | 360.00 | 470.21 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 52.51 | 0.00 |
July | 3298.57 | 01-JUL-08:61 | 540.00 | 598.45 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 50.52 | 0.00 |
August | 3258.50 | 27-AUG-08:61 | 378.00 | 418.92 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 75.28 | 0.00 |
September | 3237.92 | 28-SEP-15:02 | 583.20 | 179.54 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 157.79 | 0.00 |
October | 3227.79 | 06-OCT-15:02 | 583.20 | 179.54 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 131.66 | 0.00 |
November | 3200.61 | 20-NOV-16:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 46.76 | 0.00 |
December | 3161.64 | 25-DEC-16:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 34.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2973.90 | 360.00 | 179.54 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3298.57 | 680.40 | 598.45 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 157.79 | 17.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3119.26 | 31-JAN-16:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 72.45 | 0.00 |
February | 2802.46 | 09-FEB-16:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.82 |
March | 3147.10 | 16-MAR-15:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 69.15 | 0.00 |
April | 3744.95 | 14-APR-08:41 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 13.89 | 0.00 |
May | 3974.01 | 21-MAY-08:61 | 378.00 | 418.87 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.99 |
June | 3772.57 | 14-JUN-08:61 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 26.23 | 0.00 |
July | 3781.11 | 01-JUL-08:61 | 540.00 | 598.38 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 24.12 | 0.00 |
August | 3762.07 | 24-AUG-08:21 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 25.02 | 0.00 |
September | 3420.92 | 15-SEP-08:51 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 |
October | 3562.99 | 17-OCT-08:51 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.51 |
November | 3289.83 | 10-NOV-09:51 | 324.00 | 423.14 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.11 |
December | 3085.53 | 25-DEC-16:01 | 378.00 | 246.84 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 36.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2802.46 | 324.00 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3974.01 | 680.40 | 598.38 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 72.45 | 13.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1644.18 | 29-JAN-11:33 | 2263.36 | 1044.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 |
February | 1522.85 | 01-FEB-11:35 | 1005.94 | 580.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.96 |
March | 1722.49 | 18-MAR-17:40 | 3017.81 | 1392.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.09 | 0.00 |
April | 2050.82 | 15-APR-10:33 | 2263.36 | 870.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.64 | 0.00 |
May | 2085.28 | 18-MAY-18:10 | 10562.33 | 5568.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.63 | 0.00 |
June | 3391.19 | 28-JUN-18:25 | 3520.78 | 1856.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.25 | 0.00 |
July | 3017.71 | 20-JUL-18:30 | 1760.39 | 928.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.50 | 0.00 |
August | 2903.19 | 15-AUG-18:15 | 3520.78 | 1856.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.10 | 0.00 |
September | 2772.02 | 08-SEP-18:15 | 3520.78 | 1856.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.52 | 0.00 |
October | 2478.28 | 05-OCT-18:03 | 10562.33 | 5568.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.50 | 0.00 |
November | 1757.72 | 01-NOV-18:10 | 12322.72 | 6496.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.01 | 0.00 |
December | 1566.81 | 25-DEC-11:33 | 2263.36 | 1044.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.61 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1522.85 | 1005.94 | 580.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3391.19 | 12322.72 | 6496.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.25 | 119.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3862.11 | 31-JAN-16:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 69.76 | 0.00 |
February | 3553.33 | 28-FEB-16:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.76 |
March | 3844.30 | 16-MAR-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 67.99 | 0.00 |
April | 3916.12 | 14-APR-18:01 | 970.20 | 665.78 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 115.00 | 0.00 |
May | 3893.49 | 03-MAY-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 112.91 | 0.00 |
June | 3933.48 | 27-JUN-18:02 | 831.60 | 570.67 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 179.11 | 0.00 |
July | 3907.74 | 05-JUL-18:02 | 831.60 | 570.67 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 160.50 | 0.00 |
August | 3924.49 | 26-AUG-15:02 | 324.00 | 211.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 191.79 | 0.00 |
September | 3875.19 | 18-SEP-15:02 | 583.20 | 179.54 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 143.07 | 0.00 |
October | 3903.46 | 15-OCT-15:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 90.05 | 0.00 |
November | 3897.32 | 20-NOV-16:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 45.19 | 0.00 |
December | 3834.17 | 25-DEC-16:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 33.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3553.33 | 324.00 | 179.54 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3933.48 | 970.20 | 665.78 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 191.79 | 40.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3763.24 | 31-JAN-16:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 71.81 | 0.00 |
February | 3458.42 | 28-FEB-16:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.70 |
March | 3779.23 | 16-MAR-15:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 69.04 | 0.00 |
April | 3879.20 | 26-APR-08:41 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 29.27 | 0.00 |
May | 4189.12 | 08-MAY-08:61 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 34.29 | 0.00 |
June | 4217.64 | 14-JUN-08:61 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 38.29 | 0.00 |
July | 4330.02 | 01-JUL-08:61 | 540.00 | 598.38 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 31.72 | 0.00 |
August | 4004.16 | 24-AUG-08:21 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 46.03 | 0.00 |
September | 3848.46 | 28-SEP-15:02 | 583.20 | 179.51 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 158.12 | 0.00 |
October | 3825.17 | 06-OCT-15:02 | 583.20 | 179.51 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 132.31 | 0.00 |
November | 3797.76 | 20-NOV-16:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 47.26 | 0.00 |
December | 3722.45 | 25-DEC-16:01 | 378.00 | 246.84 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 35.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3458.42 | 360.00 | 179.51 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4330.02 | 680.40 | 598.38 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 158.12 | 38.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1975.29 | 14-JAN-16:01 | 378.00 | 155.19 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 21.05 | 0.00 |
February | 1829.62 | 09-FEB-16:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.80 |
March | 1952.31 | 16-MAR-15:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 33.47 | 0.00 |
April | 1963.01 | 13-APR-15:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 61.28 | 0.00 |
May | 1940.98 | 03-MAY-15:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 57.54 | 0.00 |
June | 1943.05 | 27-JUN-15:02 | 583.20 | 112.86 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 98.05 | 0.00 |
July | 1941.14 | 01-JUL-08:61 | 540.00 | 376.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 26.64 | 0.00 |
August | 1961.25 | 26-AUG-15:02 | 324.00 | 133.02 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 97.76 | 0.00 |
September | 1960.25 | 18-SEP-15:02 | 583.20 | 112.86 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 72.13 | 0.00 |
October | 1982.41 | 18-OCT-15:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 39.13 | 0.00 |
November | 1981.74 | 20-NOV-16:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 21.70 | 0.00 |
December | 1964.25 | 25-DEC-16:01 | 378.00 | 155.19 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 15.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1829.62 | 324.00 | 112.86 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1982.41 | 680.40 | 376.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 98.05 | 10.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18854.98 | 06-JAN-22:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.37 |
February | 18402.59 | 21-FEB-23:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.69 |
March | 20556.38 | 17-MAR-21:53 | 188921.38 | 11605.12 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.44 |
April | 22797.28 | 14-APR-21:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 121.49 | 0.00 |
May | 23078.06 | 09-MAY-21:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 126.10 | 0.00 |
June | 24852.60 | 28-JUN-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 267.65 | 0.00 |
July | 24474.13 | 21-JUL-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 251.95 | 0.00 |
August | 23969.11 | 15-AUG-21:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 226.09 | 0.00 |
September | 23766.85 | 07-SEP-21:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 229.04 | 0.00 |
October | 22885.91 | 03-OCT-21:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 144.08 | 0.00 |
November | 20407.82 | 02-NOV-21:53 | 161932.61 | 9947.24 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.95 |
December | 18407.67 | 26-DEC-22:30 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18402.59 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24852.60 | 188921.38 | 11605.12 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 267.65 | 283.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20588.81 | 06-JAN-22:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.38 |
February | 20162.73 | 21-FEB-23:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.70 |
March | 22052.06 | 17-MAR-21:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.72 |
April | 24004.85 | 14-APR-21:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 121.48 | 0.00 |
May | 24270.79 | 09-MAY-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 121.65 | 0.00 |
June | 26035.81 | 28-JUN-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 267.64 | 0.00 |
July | 25653.76 | 21-JUL-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 251.93 | 0.00 |
August | 25150.23 | 10-AUG-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 225.81 | 0.00 |
September | 24913.60 | 07-SEP-21:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 228.95 | 0.00 |
October | 24051.61 | 03-OCT-21:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 144.08 | 0.00 |
November | 21814.74 | 02-NOV-21:53 | 161932.61 | 9947.24 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.95 |
December | 20036.07 | 26-DEC-22:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20036.07 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26035.81 | 161932.61 | 9947.24 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 267.64 | 283.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26831.10 | 29-JAN-11:50 | 800.57 | 327.25 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 59.94 |
February | 26689.33 | 18-FEB-11:33 | 2401.70 | 818.12 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 117.53 |
March | 27769.42 | 18-MAR-10:45 | 1601.14 | 545.42 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.55 | 0.00 |
April | 29280.80 | 30-APR-10:33 | 2401.70 | 981.75 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 140.86 | 0.00 |
May | 29521.36 | 20-MAY-10:50 | 800.57 | 272.71 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 179.93 | 0.00 |
June | 30410.76 | 18-JUN-10:50 | 800.57 | 327.25 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 269.19 | 0.00 |
July | 30418.88 | 22-JUL-10:37 | 2401.70 | 818.12 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 270.64 | 0.00 |
August | 30428.27 | 13-AUG-10:37 | 2401.70 | 981.75 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 225.59 | 0.00 |
September | 30158.27 | 09-SEP-10:50 | 800.57 | 272.71 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 225.53 | 0.00 |
October | 29336.59 | 02-OCT-10:45 | 1067.42 | 545.42 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 202.92 | 0.00 |
November | 27656.71 | 01-NOV-10:45 | 1067.42 | 545.42 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 13.92 | 0.00 |
December | 26683.87 | 25-DEC-11:50 | 800.57 | 327.25 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 34.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26683.87 | 800.57 | 272.71 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30428.27 | 2401.70 | 981.75 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 270.64 | 117.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3801.14 | 31-JAN-17:20 | 1330.80 | 306.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.65 | 0.00 |
February | 3531.89 | 26-FEB-11:33 | 2395.44 | 1104.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.66 |
March | 4234.65 | 18-MAR-17:12 | 6387.84 | 2946.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.28 | 0.00 |
April | 6230.78 | 14-APR-15:03 | 7984.80 | 1841.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.21 | 0.00 |
May | 5935.19 | 09-MAY-15:03 | 7984.80 | 1841.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.48 | 0.00 |
June | 7825.09 | 28-JUN-18:04 | 9315.60 | 4910.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.09 | 0.00 |
July | 7147.31 | 20-JUL-15:03 | 7984.80 | 1841.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.50 | 0.00 |
August | 7371.01 | 11-AUG-15:30 | 1330.80 | 306.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.37 | 0.00 |
September | 7397.26 | 07-SEP-15:03 | 7984.80 | 1841.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.20 | 0.00 |
October | 6879.81 | 02-OCT-13:20 | 532.32 | 306.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.26 | 0.00 |
November | 4214.22 | 01-NOV-17:12 | 5323.20 | 2946.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.62 | 0.00 |
December | 3668.99 | 25-DEC-11:50 | 798.48 | 368.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3531.89 | 532.32 | 306.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7825.09 | 9315.60 | 4910.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.09 | 164.66 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.428317E+12 | 295017.09 | 31-JAN-19:10 | 0.315597E+12 | 259039.04 | 01-JAN-19:10 |
February | 0.345825E+12 | 266717.32 | 09-FEB-20:19 | 0.301027E+12 | 268608.24 | 04-FEB-18:00 |
March | 0.420581E+12 | 321304.74 | 20-MAR-18:40 | 0.290708E+12 | 247250.53 | 07-MAR-07:10 |
April | 0.513770E+12 | 377703.09 | 14-APR-19:19 | 0.218765E+12 | 175759.91 | 21-APR-06:10 |
May | 0.574343E+12 | 384854.75 | 09-MAY-19:10 | 0.214557E+12 | 150705.65 | 01-MAY-17:40 |
June | 0.638417E+12 | 437675.20 | 29-JUN-19:30 | 0.196993E+12 | 135455.87 | 01-JUN-17:10 |
July | 0.665410E+12 | 437604.16 | 21-JUL-19:49 | 0.197979E+12 | 126227.72 | 01-JUL-17:49 |
August | 0.658138E+12 | 421121.90 | 15-AUG-19:10 | 0.199163E+12 | 128402.69 | 31-AUG-17:19 |
September | 0.612502E+12 | 426493.46 | 08-SEP-19:10 | 0.197623E+12 | 136815.50 | 30-SEP-17:40 |
October | 0.508963E+12 | 392522.28 | 03-OCT-19:19 | 0.238519E+12 | 212672.71 | 25-OCT-07:40 |
November | 0.421367E+12 | 324708.65 | 01-NOV-18:10 | 0.276334E+12 | 276512.70 | 23-NOV-20:19 |
December | 0.405493E+12 | 278904.83 | 26-DEC-20:10 | 0.353601E+12 | 297676.92 | 07-DEC-20:00 |
Annual Sum or Average | 0.619313E+13 | 0.300086E+13 | ||||
Minimum of Months | 0.345825E+12 | 266717.32 | 0.196993E+12 | 126227.72 | ||
Maximum of Months | 0.665410E+12 | 437675.20 | 0.353601E+12 | 297676.92 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.466537E+11 | 0.170908E+11 | 0.146779E+12 | 0.544793E+11 | 0.441908E+11 | 0.108461E+11 | 0.00 | 0.581470E+11 | 0.00 | 0.00 | 0.480544E+10 | 0.416263E+11 | 0.00 |
February | 0.420886E+11 | 0.146606E+11 | 0.132565E+12 | 0.492072E+11 | 0.370657E+11 | 0.841864E+10 | 0.00 | 0.186456E+11 | 0.00 | 0.00 | 0.228502E+10 | 0.375255E+11 | 0.00 |
March | 0.462569E+11 | 0.150734E+11 | 0.146789E+12 | 0.544810E+11 | 0.426516E+11 | 0.105714E+11 | 0.00 | 0.544503E+11 | 0.00 | 0.00 | 0.520993E+10 | 0.413860E+11 | 0.00 |
April | 0.444708E+11 | 0.134023E+11 | 0.142011E+12 | 0.527213E+11 | 0.496601E+11 | 0.114725E+11 | 0.00 | 0.144547E+12 | 0.00 | 0.00 | 0.128858E+11 | 0.390214E+11 | 0.00 |
May | 0.457578E+11 | 0.128297E+11 | 0.146789E+12 | 0.544797E+11 | 0.543392E+11 | 0.119625E+11 | 0.00 | 0.187604E+12 | 0.00 | 0.00 | 0.168455E+11 | 0.400325E+11 | 0.00 |
June | 0.440333E+11 | 0.119908E+11 | 0.142058E+12 | 0.527229E+11 | 0.612521E+11 | 0.121843E+11 | 0.00 | 0.250710E+12 | 0.00 | 0.00 | 0.219891E+11 | 0.378651E+11 | 0.00 |
July | 0.455886E+11 | 0.125501E+11 | 0.146742E+12 | 0.544777E+11 | 0.612229E+11 | 0.126912E+11 | 0.00 | 0.265582E+12 | 0.00 | 0.00 | 0.240847E+11 | 0.387218E+11 | 0.00 |
August | 0.460026E+11 | 0.133890E+11 | 0.146800E+12 | 0.544809E+11 | 0.614739E+11 | 0.126499E+11 | 0.00 | 0.258192E+12 | 0.00 | 0.00 | 0.226535E+11 | 0.387255E+11 | 0.00 |
September | 0.446490E+11 | 0.140614E+11 | 0.142022E+12 | 0.527215E+11 | 0.588258E+11 | 0.122221E+11 | 0.00 | 0.227341E+12 | 0.00 | 0.00 | 0.193894E+11 | 0.376217E+11 | 0.00 |
October | 0.464538E+11 | 0.157658E+11 | 0.146768E+12 | 0.544791E+11 | 0.524520E+11 | 0.118008E+11 | 0.00 | 0.127568E+12 | 0.00 | 0.00 | 0.952265E+10 | 0.404341E+11 | 0.00 |
November | 0.451200E+11 | 0.162918E+11 | 0.142074E+12 | 0.527224E+11 | 0.447494E+11 | 0.105397E+11 | 0.00 | 0.617852E+11 | 0.00 | 0.00 | 0.446377E+10 | 0.400344E+11 | 0.00 |
December | 0.466611E+11 | 0.174170E+11 | 0.146742E+12 | 0.544784E+11 | 0.434643E+11 | 0.958493E+10 | 0.00 | 0.345104E+11 | 0.00 | 0.00 | 0.616137E+10 | 0.427935E+11 | 0.00 |
Annual Sum or Average | 0.543736E+12 | 0.174523E+12 | 0.172814E+13 | 0.641451E+12 | 0.611348E+12 | 0.134944E+12 | 0.00 | 0.168908E+13 | 0.00 | 0.00 | 0.150296E+12 | 0.475788E+12 | 0.00 |
Minimum of Months | 0.420886E+11 | 0.119908E+11 | 0.132565E+12 | 0.492072E+11 | 0.370657E+11 | 0.841864E+10 | 0.00 | 0.186456E+11 | 0.00 | 0.00 | 0.228502E+10 | 0.375255E+11 | 0.00 |
Maximum of Months | 0.466611E+11 | 0.174170E+11 | 0.146800E+12 | 0.544810E+11 | 0.614739E+11 | 0.126912E+11 | 0.00 | 0.265582E+12 | 0.00 | 0.00 | 0.240847E+11 | 0.427935E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.732478E+11 | 0.00 | 0.904307E+11 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.835989E+11 | 0.00 | 0.802243E+11 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.547436E+11 | 0.00 | 0.839404E+11 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.266919E+10 | 0.00 | 0.691406E+11 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.143110E+09 | 0.00 | 0.624352E+11 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 23261178.36 | 0.00 | 0.498559E+11 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 39399393.08 | 0.00 | 0.461191E+11 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 56688803.15 | 0.00 | 0.470673E+11 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 56009579.40 | 0.00 | 0.505958E+11 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.182430E+11 | 0.00 | 0.683725E+11 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.512764E+11 | 0.00 | 0.779667E+11 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.108549E+12 | 0.00 | 0.932316E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.392646E+12 | 0.00 | 0.819380E+12 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 23261178.36 | 0.00 | 0.461191E+11 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.108549E+12 | 0.00 | 0.932316E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 45424.10 | 02-JAN-20:10 | 11096.45 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 39153.57 | 02-JAN-07:19 | 31806.27 | 31-JAN-22:10 | 4779.11 | 01-JAN-09:20 | 0.00 | 01-JAN-00:10 |
February | 45424.10 | 01-FEB-20:10 | 11096.45 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 39153.57 | 01-FEB-07:19 | 26614.50 | 21-FEB-21:19 | 4753.45 | 08-FEB-07:10 | 0.00 | 01-FEB-00:10 |
March | 45424.10 | 01-MAR-20:10 | 11096.45 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 39153.57 | 13-MAR-06:19 | 32442.47 | 16-MAR-21:00 | 5187.30 | 17-MAR-18:10 | 0.00 | 01-MAR-00:10 |
April | 45424.10 | 03-APR-19:10 | 11096.45 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 39153.57 | 03-APR-06:19 | 39708.73 | 25-APR-21:10 | 5588.24 | 25-APR-19:10 | 0.00 | 01-APR-00:10 |
May | 45424.10 | 01-MAY-19:10 | 11096.45 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 39153.18 | 26-MAY-06:19 | 40743.42 | 09-MAY-21:10 | 5197.00 | 29-MAY-20:49 | 0.00 | 01-MAY-00:10 |
June | 45424.10 | 01-JUN-19:19 | 11096.45 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 39152.12 | 27-JUN-06:19 | 47147.45 | 30-JUN-20:10 | 6743.74 | 28-JUN-19:10 | 0.00 | 01-JUN-00:10 |
July | 45424.10 | 03-JUL-19:30 | 11096.45 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 39153.04 | 17-JUL-06:19 | 47131.68 | 21-JUL-21:10 | 5995.02 | 07-JUL-20:19 | 0.00 | 01-JUL-00:10 |
August | 45424.10 | 01-AUG-19:19 | 11096.45 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 39153.50 | 30-AUG-06:19 | 48033.53 | 15-AUG-21:10 | 6179.45 | 27-AUG-18:10 | 0.00 | 01-AUG-00:10 |
September | 45424.10 | 01-SEP-19:10 | 11096.45 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 39153.57 | 14-SEP-06:19 | 50202.41 | 07-SEP-21:10 | 6127.29 | 18-SEP-18:19 | 0.00 | 01-SEP-00:10 |
October | 45424.10 | 02-OCT-19:10 | 11096.45 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 39153.57 | 02-OCT-06:19 | 48482.58 | 06-OCT-21:10 | 5686.48 | 05-OCT-20:19 | 0.00 | 01-OCT-00:10 |
November | 45424.10 | 01-NOV-19:10 | 11096.45 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 39153.57 | 01-NOV-06:19 | 36513.54 | 01-NOV-21:00 | 5320.76 | 01-NOV-18:10 | 0.00 | 01-NOV-00:10 |
December | 45424.10 | 01-DEC-20:10 | 11096.45 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 39153.57 | 01-DEC-07:19 | 31360.76 | 26-DEC-22:10 | 4786.31 | 07-DEC-09:09 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 45424.10 | 11096.45 | 88863.15 | 39152.12 | 26614.50 | 4753.45 | 0.00 | |||||||
Maximum of Months | 45424.10 | 11096.45 | 88863.15 | 39153.57 | 50202.41 | 6743.74 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 95079.96 | 31-JAN-16:10 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:20 | 42597.28 | 02-JAN-19:00 | 0.00 |
February | 59178.97 | 22-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-07:10 | 42835.31 | 17-FEB-19:10 | 0.00 |
March | 91988.17 | 16-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 09-MAR-13:50 | 43955.68 | 30-MAR-20:49 | 0.00 |
April | 127895.76 | 14-APR-15:09 | 0.00 | 0.00 | 9938.94 | 01-APR-08:50 | 44294.73 | 26-APR-20:40 | 0.00 |
May | 140866.06 | 31-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAY-09:39 | 44167.62 | 30-MAY-20:49 | 0.00 |
June | 188698.43 | 28-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-00:10 | 43288.09 | 30-JUN-20:49 | 0.00 |
July | 168834.12 | 20-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUL-00:10 | 42805.76 | 25-JUL-20:30 | 0.00 |
August | 169741.69 | 25-AUG-15:09 | 0.00 | 0.00 | 9938.94 | 01-AUG-00:10 | 42841.05 | 01-AUG-20:30 | 0.00 |
September | 157889.02 | 08-SEP-18:30 | 0.00 | 0.00 | 9938.94 | 01-SEP-00:10 | 42995.91 | 01-SEP-20:49 | 0.00 |
October | 135230.43 | 02-OCT-18:10 | 0.00 | 0.00 | 9938.94 | 01-OCT-00:10 | 44572.48 | 06-OCT-20:49 | 0.00 |
November | 101064.04 | 01-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 01-NOV-12:09 | 44847.95 | 01-NOV-18:40 | 0.00 |
December | 80481.00 | 25-DEC-16:10 | 0.00 | 0.00 | 9938.94 | 02-DEC-13:09 | 43597.71 | 04-DEC-19:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 59178.97 | 0.00 | 0.00 | 9938.94 | 42597.28 | 0.00 | |||
Maximum of Months | 188698.43 | 0.00 | 0.00 | 9938.94 | 44847.95 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 295017.09 | 31-JAN-19:10 | 40391.24 | 78653.57 | 11096.45 | 31357.01 | 26311.84 | 4598.41 | 0.00 | 74395.96 | 0.00 |
February | 266717.32 | 09-FEB-20:19 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 21866.78 | 4273.03 | 0.00 | 22016.94 | 0.00 |
March | 321304.74 | 20-MAR-18:40 | 40391.24 | 78653.57 | 11096.45 | 31363.95 | 25171.98 | 4636.46 | 0.00 | 75723.66 | 0.00 |
April | 377703.09 | 14-APR-19:19 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 34520.56 | 4732.56 | 0.00 | 110835.27 | 0.00 |
May | 384854.75 | 09-MAY-19:10 | 45424.10 | 87982.85 | 11096.45 | 31569.36 | 34123.27 | 4756.15 | 0.00 | 118348.62 | 0.00 |
June | 437675.20 | 29-JUN-19:30 | 45424.10 | 87982.85 | 11096.45 | 31572.57 | 40833.89 | 6314.03 | 0.00 | 163272.77 | 0.00 |
July | 437604.16 | 21-JUL-19:49 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 41106.15 | 5426.44 | 0.00 | 164665.88 | 0.00 |
August | 421121.90 | 15-AUG-19:10 | 45424.10 | 87982.85 | 11096.45 | 31569.36 | 39973.00 | 5352.13 | 0.00 | 149035.68 | 0.00 |
September | 426493.46 | 08-SEP-19:10 | 45424.10 | 87982.85 | 11096.45 | 31569.36 | 41057.74 | 5386.87 | 0.00 | 153363.38 | 0.00 |
October | 392522.28 | 03-OCT-19:19 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 39364.60 | 5081.94 | 0.00 | 120163.60 | 0.00 |
November | 324708.65 | 01-NOV-18:10 | 40391.24 | 78653.57 | 11096.45 | 31357.01 | 29843.55 | 5320.76 | 0.00 | 84835.94 | 0.00 |
December | 278904.83 | 26-DEC-20:10 | 45424.10 | 87982.85 | 11096.45 | 31569.36 | 26270.23 | 4305.86 | 0.00 | 28666.38 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 266717.32 | 40391.24 | 78653.57 | 11096.45 | 31357.01 | 21866.78 | 4273.03 | 0.00 | 22016.94 | 0.00 | |
Maximum of Months | 437675.20 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 41106.15 | 6314.03 | 0.00 | 164665.88 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 186036.48 | 01-JAN-00:10 | 0.00 | 78547.73 | 23-JAN-20:40 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 171872.65 | 28-FEB-06:49 | 0.00 | 77383.69 | 01-FEB-23:30 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 168763.10 | 07-MAR-07:10 | 0.00 | 72751.09 | 01-MAR-19:10 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 97272.48 | 21-APR-06:10 | 0.00 | 57583.74 | 01-APR-17:10 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 7435.45 | 01-MAY-03:00 | 0.00 | 46490.34 | 01-MAY-19:49 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 4481.22 | 20-JUN-08:09 | 0.00 | 31230.08 | 01-JUN-20:30 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 4395.14 | 03-JUL-08:09 | 0.00 | 21979.44 | 01-JUL-20:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 5284.24 | 29-AUG-08:09 | 0.00 | 24154.42 | 31-AUG-22:40 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 3462.41 | 03-SEP-18:10 | 0.00 | 32567.36 | 30-SEP-20:00 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 132603.78 | 30-OCT-06:10 | 0.00 | 53613.02 | 31-OCT-20:00 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 169177.15 | 05-NOV-04:10 | 0.00 | 68736.95 | 30-NOV-22:30 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 170194.04 | 24-DEC-03:00 | 0.00 | 83451.25 | 31-DEC-20:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 3462.41 | 0.00 | 21979.44 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 186036.48 | 0.00 | 83451.25 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.86 | 0.33 | 21.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 21.91 | 7.17 | 21.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.79 | 1.50 | 21.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.83 | 5.17 | 21.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.81 | 1.67 | 21.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.84 | 0.83 | 21.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.67 | 21.86 | 16.67 | 21.86 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 21.91 | 7.17 | 21.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.03 | 0.17 | 22.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 21.94 | 9.17 | 21.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.79 | 1.67 | 21.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.79 | 3.33 | 21.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.70 | 0.83 | 21.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 15.33 | 21.88 | 15.33 | 21.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 22.03 | 9.17 | 22.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.74 | 0.50 | 21.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 21.83 | 5.50 | 21.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.74 | 2.17 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.78 | 1.83 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.77 | 1.50 | 21.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.75 | 0.17 | 21.75 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.00 | 21.79 | 12.00 | 21.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 21.83 | 5.50 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.88 | 0.33 | 21.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 21.86 | 6.33 | 21.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.75 | 1.67 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.79 | 2.33 | 21.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.76 | 1.50 | 21.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.79 | 0.50 | 21.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.83 | 21.82 | 12.83 | 21.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 21.88 | 6.33 | 21.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.85 | 0.33 | 21.85 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 22.05 | 4.83 | 22.05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 22.15 | 5.17 | 22.15 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 21.98 | 11.50 | 21.98 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.89 | 2.67 | 21.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.93 | 3.50 | 21.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 22.06 | 3.33 | 22.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 22.04 | 2.33 | 22.04 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 33.67 | 22.01 | 33.67 | 22.01 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 22.15 | 11.50 | 22.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.95 | 0.33 | 21.95 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 21.93 | 11.17 | 21.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.84 | 1.50 | 21.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 21.87 | 7.17 | 21.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.86 | 1.83 | 21.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.84 | 1.17 | 21.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 23.33 | 21.90 | 23.33 | 21.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 21.95 | 11.17 | 21.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.94 | 0.33 | 21.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 21.92 | 16.17 | 21.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.80 | 2.00 | 21.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 21.81 | 5.00 | 21.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.74 | 1.00 | 21.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 24.83 | 21.88 | 24.83 | 21.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 21.94 | 16.17 | 21.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.96 | 2.17 | 21.96 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.76 | 0.17 | 21.76 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.78 | 0.50 | 21.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.90 | 1.00 | 21.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.79 | 4.17 | 21.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.78 | 1.83 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.86 | 2.67 | 21.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 21.93 | 6.00 | 21.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 22.00 | 4.83 | 22.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.86 | 2.00 | 21.86 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.70 | 0.67 | 21.70 |
Annual Sum or Average | 0.00 | 0.00 | 26.00 | 21.89 | 26.00 | 21.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 22.00 | 6.00 | 22.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 698.83 | 23.58 | 4.17 | 23.58 | 0.00 | 23.58 |
February | 672.00 | 22.72 | 0.00 | 22.72 | 0.00 | 22.72 |
March | 744.00 | 22.05 | 0.00 | 22.05 | 0.00 | 22.05 |
April | 720.00 | 22.42 | 0.00 | 22.42 | 0.00 | 22.42 |
May | 744.00 | 22.10 | 0.00 | 22.10 | 0.00 | 22.10 |
June | 720.00 | 22.42 | 0.50 | 22.42 | 0.50 | 22.42 |
July | 416.17 | 23.60 | 357.33 | 23.74 | 214.67 | 23.78 |
August | 300.00 | 23.95 | 509.33 | 23.94 | 224.17 | 23.95 |
September | 144.17 | 24.00 | 534.83 | 23.99 | 138.67 | 23.99 |
October | 340.17 | 23.99 | 141.00 | 23.99 | 26.67 | 23.99 |
November | 421.83 | 23.99 | 144.00 | 23.99 | 37.33 | 23.99 |
December | 712.50 | 23.96 | 5.17 | 23.96 | 0.00 | 23.96 |
Annual Sum or Average | 6633.67 | 23.02 | 1696.33 | 23.21 | 642.00 | 23.26 |
Minimum of Months | 144.17 | 22.05 | 0.00 | 22.05 | 0.00 | 22.05 |
Maximum of Months | 744.00 | 24.00 | 534.83 | 23.99 | 224.17 | 23.99 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 545.17 | 22.01 | 89.67 | 22.29 | 0.00 | 22.29 |
February | 606.50 | 21.46 | 17.50 | 21.53 | 0.00 | 21.53 |
March | 677.83 | 21.68 | 37.50 | 21.72 | 18.83 | 21.71 |
April | 401.83 | 22.61 | 78.67 | 22.84 | 0.00 | 22.84 |
May | 379.67 | 22.85 | 11.67 | 22.88 | 0.00 | 22.88 |
June | 117.50 | 23.24 | 397.00 | 23.81 | 0.00 | 23.81 |
July | 197.00 | 23.51 | 629.33 | 23.76 | 152.67 | 23.73 |
August | 200.33 | 23.41 | 654.17 | 23.71 | 163.17 | 23.67 |
September | 191.50 | 23.25 | 599.67 | 23.67 | 134.67 | 23.64 |
October | 394.67 | 22.34 | 230.67 | 22.92 | 21.50 | 22.94 |
November | 527.83 | 21.93 | 121.50 | 22.17 | 32.50 | 22.13 |
December | 609.83 | 21.65 | 99.33 | 21.74 | 56.83 | 21.69 |
Annual Sum or Average | 4849.67 | 22.18 | 2966.67 | 22.78 | 580.17 | 22.80 |
Minimum of Months | 117.50 | 21.46 | 11.67 | 21.53 | 0.00 | 21.53 |
Maximum of Months | 677.83 | 23.51 | 654.17 | 23.81 | 163.17 | 23.81 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 699.67 | 23.03 | 0.00 | 23.03 | 0.00 | 23.03 |
February | 657.50 | 22.45 | 0.67 | 22.45 | 0.67 | 22.45 |
March | 697.67 | 22.67 | 0.00 | 22.67 | 0.00 | 22.67 |
April | 465.67 | 23.47 | 11.83 | 23.48 | 0.00 | 23.48 |
May | 442.17 | 23.61 | 6.50 | 23.61 | 0.00 | 23.61 |
June | 110.00 | 23.64 | 199.00 | 23.86 | 0.00 | 23.86 |
July | 256.83 | 23.95 | 556.50 | 23.93 | 201.67 | 23.94 |
August | 234.33 | 23.94 | 604.00 | 23.92 | 222.50 | 23.93 |
September | 182.33 | 23.93 | 558.33 | 23.91 | 175.50 | 23.92 |
October | 475.67 | 23.31 | 143.83 | 23.45 | 34.50 | 23.48 |
November | 619.33 | 23.03 | 79.67 | 23.07 | 49.33 | 23.07 |
December | 739.33 | 22.65 | 0.00 | 22.65 | 0.00 | 22.65 |
Annual Sum or Average | 5580.50 | 23.09 | 2160.33 | 23.32 | 684.17 | 23.36 |
Minimum of Months | 110.00 | 22.45 | 0.00 | 22.45 | 0.00 | 22.45 |
Maximum of Months | 739.33 | 23.95 | 604.00 | 23.93 | 222.50 | 23.94 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.64 | 13.33 | 21.63 | 13.33 | 21.61 |
February | 672.00 | 21.24 | 0.00 | 21.24 | 0.00 | 21.24 |
March | 744.00 | 21.61 | 35.00 | 21.58 | 35.00 | 21.56 |
April | 711.17 | 23.00 | 0.00 | 23.00 | 0.00 | 23.00 |
May | 715.17 | 23.57 | 0.00 | 23.57 | 0.00 | 23.57 |
June | 222.33 | 23.95 | 52.50 | 23.96 | 0.00 | 23.96 |
July | 106.33 | 23.98 | 523.17 | 23.97 | 19.83 | 23.97 |
August | 73.00 | 23.82 | 547.50 | 23.93 | 4.50 | 23.93 |
September | 125.50 | 23.71 | 398.17 | 23.85 | 32.50 | 23.85 |
October | 605.50 | 22.58 | 86.17 | 22.75 | 2.67 | 22.75 |
November | 720.00 | 21.85 | 11.67 | 21.84 | 11.67 | 21.83 |
December | 744.00 | 21.28 | 140.50 | 21.24 | 140.50 | 21.21 |
Annual Sum or Average | 6183.00 | 22.24 | 1808.00 | 22.55 | 260.00 | 22.52 |
Minimum of Months | 73.00 | 21.24 | 0.00 | 21.24 | 0.00 | 21.21 |
Maximum of Months | 744.00 | 23.98 | 547.50 | 23.97 | 140.50 | 23.97 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.56 | 12.50 | 21.55 | 12.50 | 21.54 |
February | 672.00 | 21.16 | 0.00 | 21.16 | 0.00 | 21.16 |
March | 744.00 | 21.51 | 33.67 | 21.49 | 33.67 | 21.47 |
April | 718.50 | 22.88 | 0.00 | 22.88 | 0.00 | 22.88 |
May | 739.00 | 23.47 | 0.00 | 23.47 | 0.00 | 23.47 |
June | 269.83 | 23.92 | 43.50 | 23.93 | 0.00 | 23.93 |
July | 142.83 | 23.93 | 511.17 | 23.95 | 43.50 | 23.94 |
August | 122.83 | 23.74 | 518.83 | 23.89 | 30.50 | 23.88 |
September | 192.83 | 23.64 | 353.17 | 23.78 | 54.33 | 23.77 |
October | 624.67 | 22.49 | 74.17 | 22.64 | 4.67 | 22.65 |
November | 720.00 | 21.75 | 22.67 | 21.75 | 22.67 | 21.74 |
December | 744.00 | 21.22 | 168.50 | 21.18 | 168.50 | 21.15 |
Annual Sum or Average | 6434.50 | 22.21 | 1738.17 | 22.49 | 370.33 | 22.47 |
Minimum of Months | 122.83 | 21.16 | 0.00 | 21.16 | 0.00 | 21.15 |
Maximum of Months | 744.00 | 23.93 | 518.83 | 23.95 | 168.50 | 23.94 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 244.17 | 23.20 | 606.17 | 23.41 | 174.67 | 23.51 |
February | 253.67 | 23.42 | 578.17 | 23.38 | 203.33 | 23.50 |
March | 269.83 | 23.41 | 614.50 | 23.43 | 213.33 | 23.54 |
April | 244.83 | 23.69 | 625.33 | 23.53 | 215.83 | 23.62 |
May | 251.17 | 23.86 | 655.67 | 23.58 | 236.83 | 23.67 |
June | 310.50 | 23.97 | 686.83 | 23.56 | 310.50 | 23.66 |
July | 367.83 | 23.91 | 732.33 | 23.52 | 367.33 | 23.61 |
August | 369.00 | 23.92 | 734.83 | 23.50 | 369.00 | 23.60 |
September | 346.67 | 23.94 | 711.50 | 23.50 | 346.67 | 23.61 |
October | 275.17 | 23.62 | 663.67 | 23.47 | 238.83 | 23.58 |
November | 250.50 | 23.44 | 602.00 | 23.45 | 201.00 | 23.55 |
December | 230.17 | 22.94 | 533.17 | 23.37 | 143.00 | 23.47 |
Annual Sum or Average | 3413.50 | 23.65 | 7744.17 | 23.48 | 3020.33 | 23.58 |
Minimum of Months | 230.17 | 22.94 | 533.17 | 23.37 | 143.00 | 23.47 |
Maximum of Months | 369.00 | 23.97 | 734.83 | 23.58 | 369.00 | 23.67 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 232.50 | 23.04 | 252.17 | 23.51 | 10.83 | 23.50 |
February | 416.00 | 22.53 | 156.00 | 22.86 | 40.50 | 22.89 |
March | 447.67 | 22.64 | 135.33 | 22.93 | 5.50 | 22.94 |
April | 156.83 | 23.05 | 245.33 | 23.61 | 0.00 | 23.61 |
May | 155.00 | 23.06 | 225.33 | 23.61 | 0.00 | 23.61 |
June | 28.67 | 23.32 | 534.67 | 23.93 | 9.33 | 23.93 |
July | 308.17 | 23.90 | 676.00 | 23.88 | 300.17 | 23.89 |
August | 343.17 | 23.87 | 710.00 | 23.87 | 339.67 | 23.88 |
September | 271.50 | 23.88 | 702.00 | 23.90 | 271.50 | 23.89 |
October | 201.17 | 23.29 | 401.50 | 23.73 | 56.33 | 23.74 |
November | 272.17 | 23.03 | 329.00 | 23.40 | 78.33 | 23.35 |
December | 459.00 | 22.91 | 121.33 | 23.14 | 0.00 | 23.14 |
Annual Sum or Average | 3291.83 | 23.16 | 4488.67 | 23.58 | 1112.17 | 23.61 |
Minimum of Months | 28.67 | 22.53 | 121.33 | 22.86 | 0.00 | 22.89 |
Maximum of Months | 459.00 | 23.90 | 710.00 | 23.93 | 339.67 | 23.93 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 442.17 | 23.40 | 30.17 | 23.43 | 10.00 | 23.43 |
February | 515.50 | 22.91 | 68.17 | 23.01 | 31.50 | 23.04 |
March | 509.83 | 22.96 | 32.33 | 23.02 | 4.67 | 23.02 |
April | 318.50 | 23.47 | 39.67 | 23.53 | 0.00 | 23.53 |
May | 284.50 | 23.47 | 28.17 | 23.51 | 0.00 | 23.51 |
June | 61.17 | 23.46 | 338.50 | 23.90 | 5.50 | 23.90 |
July | 284.50 | 23.95 | 619.00 | 23.91 | 269.83 | 23.93 |
August | 310.67 | 23.96 | 665.33 | 23.92 | 308.83 | 23.93 |
September | 240.33 | 23.96 | 665.00 | 23.93 | 240.33 | 23.93 |
October | 261.33 | 23.52 | 218.00 | 23.71 | 51.33 | 23.74 |
November | 404.00 | 23.40 | 167.33 | 23.49 | 75.67 | 23.48 |
December | 641.33 | 23.23 | 0.00 | 23.23 | 0.00 | 23.23 |
Annual Sum or Average | 4273.83 | 23.39 | 2871.67 | 23.60 | 997.67 | 23.63 |
Minimum of Months | 61.17 | 22.91 | 0.00 | 23.01 | 0.00 | 23.02 |
Maximum of Months | 641.33 | 23.96 | 665.33 | 23.93 | 308.83 | 23.93 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 737.00 | 21.61 | 12.67 | 21.60 | 12.67 | 21.59 |
February | 670.33 | 21.39 | 1.83 | 21.39 | 1.83 | 21.38 |
March | 740.00 | 21.52 | 32.83 | 21.50 | 32.83 | 21.48 |
April | 689.67 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
May | 708.33 | 21.66 | 0.00 | 21.66 | 0.00 | 21.66 |
June | 622.83 | 21.53 | 9.17 | 21.55 | 0.00 | 21.55 |
July | 611.00 | 21.41 | 16.50 | 21.46 | 0.17 | 21.46 |
August | 595.33 | 21.36 | 29.00 | 21.46 | 1.00 | 21.46 |
September | 584.50 | 21.38 | 27.67 | 21.46 | 5.50 | 21.48 |
October | 687.50 | 21.55 | 4.17 | 21.56 | 0.00 | 21.56 |
November | 699.17 | 21.56 | 62.17 | 21.55 | 60.17 | 21.53 |
December | 742.67 | 21.50 | 163.17 | 21.42 | 163.17 | 21.36 |
Annual Sum or Average | 8088.33 | 21.51 | 359.17 | 21.52 | 277.33 | 21.51 |
Minimum of Months | 584.50 | 21.36 | 0.00 | 21.39 | 0.00 | 21.36 |
Maximum of Months | 742.67 | 21.66 | 163.17 | 21.66 | 163.17 | 21.66 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.67 | 21.56 | 51.00 | 21.52 | 51.00 | 21.48 |
February | 672.00 | 21.22 | 29.83 | 21.19 | 29.83 | 21.16 |
March | 734.33 | 21.62 | 57.33 | 21.58 | 54.83 | 21.54 |
April | 690.67 | 21.87 | 6.83 | 21.91 | 0.00 | 21.91 |
May | 704.83 | 21.86 | 0.00 | 21.86 | 0.00 | 21.86 |
June | 603.17 | 21.63 | 13.83 | 21.67 | 0.00 | 21.67 |
July | 608.83 | 21.47 | 19.67 | 21.53 | 5.67 | 21.55 |
August | 601.50 | 21.54 | 39.33 | 21.66 | 17.00 | 21.72 |
September | 597.00 | 21.64 | 35.00 | 21.75 | 24.50 | 21.81 |
October | 707.00 | 21.81 | 10.00 | 21.82 | 8.83 | 21.82 |
November | 714.17 | 21.63 | 118.67 | 21.59 | 118.00 | 21.55 |
December | 744.00 | 21.23 | 365.67 | 21.12 | 365.67 | 21.07 |
Annual Sum or Average | 8121.17 | 21.59 | 747.17 | 21.58 | 675.33 | 21.55 |
Minimum of Months | 597.00 | 21.22 | 0.00 | 21.12 | 0.00 | 21.07 |
Maximum of Months | 744.00 | 21.87 | 365.67 | 21.91 | 365.67 | 21.91 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.42 | 17.33 | 21.41 | 17.33 | 21.41 |
February | 672.00 | 21.30 | 2.83 | 21.29 | 2.83 | 21.29 |
March | 744.00 | 21.60 | 10.67 | 21.59 | 10.67 | 21.58 |
April | 720.00 | 21.83 | 0.00 | 21.83 | 0.00 | 21.83 |
May | 744.00 | 21.87 | 0.00 | 21.87 | 0.00 | 21.87 |
June | 719.83 | 21.86 | 0.00 | 21.86 | 0.00 | 21.86 |
July | 743.50 | 21.78 | 2.50 | 21.79 | 2.50 | 21.79 |
August | 741.67 | 21.83 | 10.33 | 21.85 | 10.33 | 21.88 |
September | 718.83 | 21.88 | 13.17 | 21.90 | 13.17 | 21.92 |
October | 744.00 | 21.77 | 2.67 | 21.77 | 2.67 | 21.77 |
November | 720.00 | 21.51 | 57.33 | 21.52 | 57.33 | 21.52 |
December | 744.00 | 21.23 | 217.67 | 21.19 | 217.67 | 21.16 |
Annual Sum or Average | 8755.83 | 21.66 | 334.50 | 21.65 | 334.50 | 21.63 |
Minimum of Months | 672.00 | 21.23 | 0.00 | 21.19 | 0.00 | 21.16 |
Maximum of Months | 744.00 | 21.88 | 217.67 | 21.90 | 217.67 | 21.92 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.67 | 14.67 | 21.66 | 14.67 | 21.65 |
February | 672.00 | 21.49 | 2.67 | 21.49 | 2.67 | 21.49 |
March | 740.83 | 21.62 | 26.00 | 21.60 | 26.00 | 21.59 |
April | 694.67 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
May | 728.17 | 21.72 | 0.00 | 21.72 | 0.00 | 21.72 |
June | 561.67 | 21.33 | 5.67 | 21.35 | 0.00 | 21.35 |
July | 569.67 | 21.28 | 19.67 | 21.35 | 0.00 | 21.35 |
August | 553.83 | 21.22 | 21.83 | 21.30 | 0.50 | 21.30 |
September | 558.50 | 21.30 | 14.33 | 21.35 | 2.83 | 21.36 |
October | 686.17 | 21.59 | 1.33 | 21.59 | 0.00 | 21.59 |
November | 712.50 | 21.63 | 70.17 | 21.60 | 70.17 | 21.57 |
December | 744.00 | 21.57 | 149.17 | 21.49 | 149.17 | 21.43 |
Annual Sum or Average | 7966.00 | 21.53 | 325.50 | 21.53 | 266.00 | 21.52 |
Minimum of Months | 553.83 | 21.22 | 0.00 | 21.30 | 0.00 | 21.30 |
Maximum of Months | 744.00 | 21.72 | 149.17 | 21.72 | 149.17 | 21.72 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.57 | 57.33 | 21.53 | 57.33 | 21.50 |
February | 672.00 | 21.30 | 18.83 | 21.28 | 18.83 | 21.27 |
March | 742.83 | 21.74 | 41.67 | 21.70 | 41.17 | 21.67 |
April | 671.33 | 21.89 | 23.17 | 22.02 | 0.00 | 22.02 |
May | 673.33 | 21.81 | 40.33 | 22.05 | 0.50 | 22.06 |
June | 518.33 | 21.35 | 35.83 | 21.57 | 0.17 | 21.58 |
July | 557.83 | 21.32 | 27.67 | 21.46 | 5.33 | 21.49 |
August | 542.17 | 21.37 | 42.83 | 21.58 | 16.67 | 21.67 |
September | 546.00 | 21.53 | 45.00 | 21.76 | 22.33 | 21.85 |
October | 687.50 | 21.85 | 13.33 | 21.90 | 5.83 | 21.90 |
November | 718.50 | 21.63 | 130.00 | 21.57 | 129.83 | 21.52 |
December | 744.00 | 21.23 | 342.67 | 21.15 | 342.67 | 21.11 |
Annual Sum or Average | 7817.83 | 21.56 | 818.67 | 21.61 | 640.67 | 21.59 |
Minimum of Months | 518.33 | 21.23 | 13.33 | 21.15 | 0.00 | 21.11 |
Maximum of Months | 744.00 | 21.89 | 342.67 | 22.05 | 342.67 | 22.06 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.09 | 0.00 | 22.09 | 0.00 | 22.09 |
February | 672.00 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
March | 744.00 | 21.84 | 0.00 | 21.84 | 0.00 | 21.84 |
April | 719.50 | 23.19 | 0.00 | 23.19 | 0.00 | 23.19 |
May | 737.67 | 23.62 | 0.00 | 23.62 | 0.00 | 23.62 |
June | 391.33 | 23.92 | 34.67 | 23.92 | 0.00 | 23.92 |
July | 377.17 | 23.93 | 503.83 | 23.93 | 249.00 | 23.93 |
August | 362.00 | 23.86 | 542.00 | 23.88 | 279.17 | 23.88 |
September | 303.17 | 23.81 | 422.00 | 23.85 | 221.33 | 23.84 |
October | 631.00 | 23.01 | 91.00 | 23.12 | 38.00 | 23.16 |
November | 720.00 | 22.23 | 64.17 | 22.22 | 64.17 | 22.21 |
December | 744.00 | 21.55 | 46.50 | 21.53 | 46.50 | 21.50 |
Annual Sum or Average | 7145.83 | 22.67 | 1704.17 | 22.88 | 898.17 | 22.95 |
Minimum of Months | 303.17 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
Maximum of Months | 744.00 | 23.93 | 542.00 | 23.93 | 279.17 | 23.93 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 729.83 | 21.56 | 42.00 | 21.53 | 42.00 | 21.50 |
February | 667.50 | 21.33 | 37.00 | 21.30 | 37.00 | 21.27 |
March | 734.00 | 21.48 | 65.83 | 21.43 | 65.83 | 21.40 |
April | 662.67 | 21.56 | 6.83 | 21.56 | 6.33 | 21.55 |
May | 685.33 | 21.60 | 0.00 | 21.60 | 0.00 | 21.60 |
June | 579.33 | 21.42 | 27.00 | 21.50 | 0.00 | 21.50 |
July | 588.33 | 21.34 | 49.33 | 21.49 | 0.83 | 21.50 |
August | 575.50 | 21.31 | 65.17 | 21.52 | 2.00 | 21.52 |
September | 570.00 | 21.33 | 59.00 | 21.51 | 10.17 | 21.52 |
October | 679.17 | 21.50 | 38.50 | 21.52 | 25.67 | 21.50 |
November | 693.50 | 21.51 | 128.00 | 21.47 | 122.83 | 21.43 |
December | 740.50 | 21.44 | 268.33 | 21.33 | 268.33 | 21.27 |
Annual Sum or Average | 7905.67 | 21.45 | 787.00 | 21.47 | 581.00 | 21.45 |
Minimum of Months | 570.00 | 21.31 | 0.00 | 21.30 | 0.00 | 21.27 |
Maximum of Months | 740.50 | 21.60 | 268.33 | 21.60 | 268.33 | 21.60 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.50 | 21.49 | 148.67 | 21.39 | 148.67 | 21.32 |
February | 671.50 | 21.15 | 94.83 | 21.08 | 94.83 | 21.02 |
March | 730.17 | 21.57 | 97.83 | 21.53 | 92.33 | 21.46 |
April | 672.33 | 21.79 | 12.17 | 21.84 | 3.67 | 21.84 |
May | 689.00 | 21.79 | 0.00 | 21.79 | 0.00 | 21.79 |
June | 563.33 | 21.54 | 31.17 | 21.63 | 0.00 | 21.63 |
July | 585.67 | 21.40 | 49.17 | 21.55 | 8.00 | 21.57 |
August | 580.33 | 21.47 | 67.83 | 21.67 | 20.17 | 21.73 |
September | 585.00 | 21.58 | 59.33 | 21.74 | 33.33 | 21.82 |
October | 699.50 | 21.72 | 57.00 | 21.68 | 55.17 | 21.64 |
November | 712.50 | 21.54 | 207.17 | 21.44 | 206.33 | 21.38 |
December | 744.00 | 21.14 | 490.67 | 21.03 | 490.67 | 20.98 |
Annual Sum or Average | 7976.83 | 21.51 | 1315.83 | 21.49 | 1153.17 | 21.44 |
Minimum of Months | 563.33 | 21.14 | 0.00 | 21.03 | 0.00 | 20.98 |
Maximum of Months | 744.00 | 21.79 | 490.67 | 21.84 | 490.67 | 21.84 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 640.83 | 21.45 | 3.33 | 21.46 | 0.00 | 21.46 |
February | 628.00 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
March | 723.67 | 21.57 | 26.50 | 21.55 | 26.50 | 21.54 |
April | 682.00 | 21.62 | 3.50 | 21.62 | 3.50 | 21.61 |
May | 742.17 | 21.73 | 0.00 | 21.73 | 0.00 | 21.73 |
June | 660.50 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
July | 631.17 | 21.47 | 0.50 | 21.47 | 0.50 | 21.47 |
August | 603.33 | 21.38 | 18.17 | 21.44 | 2.00 | 21.44 |
September | 580.33 | 21.37 | 47.33 | 21.51 | 6.83 | 21.52 |
October | 643.67 | 21.47 | 23.00 | 21.53 | 0.00 | 21.53 |
November | 641.33 | 21.48 | 61.67 | 21.51 | 48.83 | 21.50 |
December | 687.50 | 21.53 | 52.00 | 21.50 | 52.00 | 21.48 |
Annual Sum or Average | 7864.50 | 21.52 | 236.00 | 21.53 | 140.17 | 21.53 |
Minimum of Months | 580.33 | 21.37 | 0.00 | 21.43 | 0.00 | 21.43 |
Maximum of Months | 742.17 | 21.73 | 61.67 | 21.73 | 52.00 | 21.73 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 258.17 | 23.36 | 94.83 | 23.52 | 9.50 | 23.53 |
February | 224.83 | 23.31 | 283.00 | 23.67 | 51.00 | 23.70 |
March | 171.50 | 23.28 | 275.33 | 23.71 | 5.33 | 23.72 |
April | 16.50 | 23.60 | 252.00 | 23.97 | 0.00 | 23.97 |
May | 0.00 | 0.00 | 327.83 | 23.99 | 0.00 | 23.99 |
June | 9.67 | 24.00 | 666.67 | 24.00 | 9.67 | 24.00 |
July | 286.67 | 24.00 | 698.17 | 23.99 | 286.67 | 23.99 |
August | 332.33 | 24.00 | 721.33 | 23.99 | 332.33 | 23.99 |
September | 264.67 | 23.99 | 719.83 | 23.99 | 264.67 | 23.99 |
October | 135.50 | 23.62 | 317.67 | 23.87 | 58.00 | 23.88 |
November | 270.17 | 23.55 | 231.50 | 23.71 | 79.00 | 23.73 |
December | 476.00 | 23.46 | 9.67 | 23.47 | 0.00 | 23.47 |
Annual Sum or Average | 2446.00 | 23.64 | 4597.83 | 23.86 | 1096.17 | 23.88 |
Minimum of Months | 0.00 | 0.00 | 9.67 | 23.47 | 0.00 | 23.47 |
Maximum of Months | 476.00 | 24.00 | 721.33 | 24.00 | 332.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 102.67 | 23.41 | 170.83 | 23.76 | 8.00 | 23.76 |
February | 93.83 | 23.57 | 396.50 | 23.88 | 39.33 | 23.89 |
March | 66.67 | 23.47 | 405.33 | 23.90 | 4.50 | 23.91 |
April | 2.50 | 23.60 | 354.83 | 23.99 | 0.00 | 23.99 |
May | 0.00 | 0.00 | 441.50 | 24.00 | 0.00 | 24.00 |
June | 8.17 | 24.00 | 693.67 | 24.00 | 8.17 | 24.00 |
July | 273.33 | 24.00 | 709.50 | 24.00 | 273.33 | 24.00 |
August | 313.50 | 24.00 | 730.33 | 23.99 | 313.50 | 24.00 |
September | 248.00 | 24.00 | 720.00 | 23.99 | 248.00 | 23.99 |
October | 89.67 | 23.78 | 405.00 | 23.95 | 56.00 | 23.95 |
November | 148.17 | 23.70 | 279.33 | 23.86 | 78.00 | 23.87 |
December | 239.17 | 23.45 | 12.50 | 23.47 | 0.00 | 23.47 |
Annual Sum or Average | 1585.67 | 23.79 | 5319.33 | 23.94 | 1028.83 | 23.95 |
Minimum of Months | 0.00 | 0.00 | 12.50 | 23.47 | 0.00 | 23.47 |
Maximum of Months | 313.50 | 24.00 | 730.33 | 24.00 | 313.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 506.83 | 23.97 | 671.67 | 23.93 | 502.00 | 23.94 |
February | 471.50 | 23.99 | 646.17 | 23.89 | 470.50 | 23.92 |
March | 518.83 | 23.97 | 705.50 | 23.91 | 513.33 | 23.93 |
April | 510.67 | 23.99 | 712.33 | 23.96 | 510.67 | 23.97 |
May | 534.33 | 23.99 | 743.17 | 23.97 | 534.33 | 23.98 |
June | 559.00 | 23.99 | 720.00 | 23.99 | 559.00 | 23.99 |
July | 694.17 | 23.99 | 744.00 | 23.99 | 694.17 | 23.99 |
August | 706.17 | 23.98 | 744.00 | 23.98 | 706.17 | 23.98 |
September | 643.83 | 23.99 | 720.00 | 23.98 | 643.83 | 23.98 |
October | 547.00 | 23.99 | 721.00 | 23.95 | 546.83 | 23.96 |
November | 519.17 | 23.96 | 662.00 | 23.92 | 514.83 | 23.94 |
December | 505.00 | 23.87 | 614.17 | 23.91 | 468.83 | 23.93 |
Annual Sum or Average | 6716.50 | 23.97 | 8404.00 | 23.95 | 6664.50 | 23.96 |
Minimum of Months | 471.50 | 23.87 | 614.17 | 23.89 | 468.83 | 23.92 |
Maximum of Months | 706.17 | 23.99 | 744.00 | 23.99 | 706.17 | 23.99 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.91 | 0.00 | 21.91 | 0.00 | 21.91 |
February | 672.00 | 21.41 | 0.00 | 21.41 | 0.00 | 21.41 |
March | 744.00 | 21.80 | 0.00 | 21.80 | 0.00 | 21.80 |
April | 627.83 | 23.16 | 0.00 | 23.16 | 0.00 | 23.16 |
May | 541.00 | 23.53 | 0.00 | 23.53 | 0.00 | 23.53 |
June | 120.83 | 23.68 | 119.83 | 23.84 | 0.00 | 23.84 |
July | 186.00 | 23.82 | 578.33 | 23.92 | 136.50 | 23.91 |
August | 187.00 | 23.74 | 615.83 | 23.87 | 149.50 | 23.85 |
September | 177.17 | 23.61 | 484.33 | 23.80 | 120.33 | 23.79 |
October | 589.67 | 22.65 | 103.33 | 22.84 | 20.17 | 22.86 |
November | 716.00 | 22.00 | 27.67 | 21.99 | 27.67 | 21.99 |
December | 744.00 | 21.47 | 98.33 | 21.42 | 98.33 | 21.37 |
Annual Sum or Average | 6049.50 | 22.35 | 2027.67 | 22.70 | 552.50 | 22.73 |
Minimum of Months | 120.83 | 21.41 | 0.00 | 21.41 | 0.00 | 21.37 |
Maximum of Months | 744.00 | 23.82 | 615.83 | 23.92 | 149.50 | 23.91 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.59316 | 26.65345 | 0.14182 | 5.59166 |
February | 672.00000 | 22.72375 | 41.08002 | 0.01200 | 5.18093 |
March | 744.00000 | 22.05465 | 33.86427 | -0.2026 | 6.08464 |
April | 720.00000 | 22.42295 | 25.11913 | -0.1626 | 5.75541 |
May | 744.00000 | 22.10310 | 24.86994 | -1.3453 | 42.72544 |
June | 720.00000 | 22.41839 | 36.38637 | -1.1583 | 33.46026 |
July | 744.00000 | 23.63954 | 50.49982 | -0.6228 | 13.92467 |
August | 744.00000 | 23.88017 | 52.39569 | -0.5132 | 10.69524 |
September | 720.00000 | 23.98484 | 50.54075 | -0.4695 | 9.71923 |
October | 744.00000 | 23.98731 | 30.90834 | 0.29570 | 7.01243 |
November | 720.00000 | 23.99036 | 30.23486 | 0.28883 | 6.95669 |
December | 744.00000 | 23.96491 | 18.95957 | 0.19774 | 5.85442 |
Annual Sum or Average | 8760.00000 | 23.23471 | 35.07221 | -0.2965 | 12.79550 |
Minimum of Months | 672.00000 | 22.05465 | 18.95957 | -1.3453 | 5.18093 |
Maximum of Months | 744.00000 | 23.99036 | 52.39569 | 0.29570 | 42.72544 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.52445 | 26.24636 | 0.00202 | 7.02718 |
February | 672.00000 | 21.68246 | 41.75613 | -0.1685 | 6.83546 |
March | 744.00000 | 21.86237 | 32.37454 | -0.1662 | 6.94249 |
April | 720.00000 | 23.18110 | 22.10791 | 0.14532 | 6.67774 |
May | 744.00000 | 23.36841 | 21.26981 | -0.7371 | 17.77705 |
June | 720.00000 | 23.80853 | 31.29469 | -0.4691 | 10.21786 |
July | 744.00000 | 23.79156 | 48.34713 | -0.3691 | 8.49456 |
August | 744.00000 | 23.74179 | 51.19294 | -0.3579 | 8.44253 |
September | 720.00000 | 23.69425 | 50.44356 | -0.3791 | 8.92102 |
October | 744.00000 | 23.06035 | 31.24182 | 0.18710 | 7.92938 |
November | 720.00000 | 22.45116 | 31.99123 | 0.01461 | 7.03926 |
December | 744.00000 | 22.06885 | 19.37693 | -0.1853 | 8.04195 |
Annual Sum or Average | 8760.00000 | 22.94277 | 33.90638 | -0.2077 | 8.71611 |
Minimum of Months | 672.00000 | 21.68246 | 19.37693 | -0.7371 | 6.67774 |
Maximum of Months | 744.00000 | 23.80853 | 51.19294 | 0.18710 | 17.77705 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.07649 | 27.39159 | 0.06227 | 5.42336 |
February | 672.00000 | 22.47982 | 41.68799 | -0.0038 | 5.37248 |
March | 744.00000 | 22.74313 | 32.77390 | 0.01012 | 5.60536 |
April | 720.00000 | 23.64187 | 23.41351 | 0.19232 | 6.07434 |
May | 744.00000 | 23.76286 | 22.57630 | -0.6878 | 15.24998 |
June | 720.00000 | 23.91720 | 32.71471 | -0.5382 | 11.28337 |
July | 744.00000 | 23.89635 | 49.44760 | -0.4390 | 9.30418 |
August | 744.00000 | 23.88759 | 52.19405 | -0.4242 | 8.96424 |
September | 720.00000 | 23.87133 | 51.42820 | -0.4422 | 9.29406 |
October | 744.00000 | 23.51980 | 32.40565 | 0.22025 | 6.66726 |
November | 720.00000 | 23.13548 | 32.58563 | 0.11267 | 5.80169 |
December | 744.00000 | 22.66032 | 20.82554 | -0.0883 | 5.59896 |
Annual Sum or Average | 8760.00000 | 23.38727 | 34.89748 | -0.1702 | 7.90479 |
Minimum of Months | 672.00000 | 22.47982 | 20.82554 | -0.6878 | 5.37248 |
Maximum of Months | 744.00000 | 23.91720 | 52.19405 | 0.22025 | 15.24998 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.14538 | 22.97999 | 0.66511 | 16.73072 |
February | 672.00000 | 23.08133 | 36.11530 | 0.72050 | 18.46219 |
March | 744.00000 | 23.11761 | 27.96217 | 0.69411 | 17.60104 |
April | 720.00000 | 23.24220 | 19.90505 | 0.72783 | 18.37457 |
May | 744.00000 | 23.28010 | 19.28771 | 0.07777 | 9.45338 |
June | 720.00000 | 23.30813 | 30.49518 | 0.20631 | 9.99438 |
July | 744.00000 | 23.29653 | 47.47253 | 0.29753 | 10.91512 |
August | 744.00000 | 23.27081 | 50.34934 | 0.30371 | 11.05893 |
September | 720.00000 | 23.26587 | 49.31680 | 0.27273 | 10.76910 |
October | 744.00000 | 23.21753 | 28.93301 | 0.76238 | 19.58138 |
November | 720.00000 | 23.15917 | 28.28151 | 0.70823 | 18.10430 |
December | 744.00000 | 23.09700 | 16.22601 | 0.58887 | 14.71043 |
Annual Sum or Average | 8760.00000 | 23.20743 | 31.39923 | 0.50055 | 14.61861 |
Minimum of Months | 672.00000 | 23.08133 | 16.22601 | 0.07777 | 9.45338 |
Maximum of Months | 744.00000 | 23.30813 | 50.34934 | 0.76238 | 19.58138 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.63247 | 30.30622 | 0.33270 | 7.98811 |
February | 672.00000 | 22.97660 | 44.62573 | 0.20329 | 6.81924 |
March | 744.00000 | 23.08962 | 36.13453 | 0.18526 | 6.69196 |
April | 720.00000 | 23.72191 | 26.92669 | 0.33953 | 7.89299 |
May | 744.00000 | 23.70859 | 26.27181 | -0.5438 | 11.74518 |
June | 720.00000 | 23.84841 | 36.23050 | -0.3715 | 8.29735 |
July | 744.00000 | 23.86091 | 52.80188 | -0.2571 | 6.77788 |
August | 744.00000 | 23.86788 | 55.38014 | -0.2264 | 6.42316 |
September | 720.00000 | 23.89299 | 54.38944 | -0.2216 | 6.42901 |
October | 744.00000 | 23.74825 | 35.40930 | 0.41981 | 9.52165 |
November | 720.00000 | 23.55148 | 35.68112 | 0.33932 | 8.21861 |
December | 744.00000 | 23.29582 | 24.08315 | 0.17620 | 6.73775 |
Annual Sum or Average | 8760.00000 | 23.60301 | 38.13247 | 0.03001 | 7.80420 |
Minimum of Months | 672.00000 | 22.97660 | 24.08315 | -0.5438 | 6.42316 |
Maximum of Months | 744.00000 | 23.89299 | 55.38014 | 0.41981 | 11.74518 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.60245 | 29.69621 | 0.22914 | 6.31915 |
February | 672.00000 | 23.12239 | 43.42111 | 0.18263 | 6.12085 |
March | 744.00000 | 23.24663 | 35.03718 | 0.16546 | 6.13601 |
April | 720.00000 | 23.73428 | 26.01341 | 0.25802 | 6.61831 |
May | 744.00000 | 23.76773 | 25.15126 | -0.6291 | 13.58010 |
June | 720.00000 | 23.88484 | 35.26241 | -0.4873 | 10.21681 |
July | 744.00000 | 23.88882 | 51.79462 | -0.3752 | 8.22958 |
August | 744.00000 | 23.89998 | 54.48295 | -0.3539 | 7.79270 |
September | 720.00000 | 23.91514 | 53.55787 | -0.3583 | 7.83861 |
October | 744.00000 | 23.77812 | 34.65177 | 0.32958 | 7.69932 |
November | 720.00000 | 23.59959 | 34.78995 | 0.26457 | 6.85907 |
December | 744.00000 | 23.32336 | 23.39128 | 0.10616 | 5.58810 |
Annual Sum or Average | 8760.00000 | 23.64976 | 37.21880 | -0.0574 | 7.76181 |
Minimum of Months | 672.00000 | 23.12239 | 23.39128 | -0.6291 | 5.58810 |
Maximum of Months | 744.00000 | 23.91514 | 54.48295 | 0.32958 | 13.58010 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.62133 | 32.86884 | -0.2664 | 7.45263 |
February | 672.00000 | 21.39454 | 47.55733 | -0.2929 | 7.39436 |
March | 744.00000 | 21.53226 | 37.85055 | -0.2789 | 7.44317 |
April | 720.00000 | 21.71347 | 27.86297 | -0.1764 | 6.68022 |
May | 744.00000 | 21.73694 | 26.82496 | -1.2243 | 37.70613 |
June | 720.00000 | 21.76535 | 35.62174 | -1.0893 | 31.55719 |
July | 744.00000 | 21.75115 | 45.74669 | -1.0686 | 30.58741 |
August | 744.00000 | 21.75324 | 47.94396 | -1.0596 | 30.28703 |
September | 720.00000 | 21.74486 | 49.29467 | -1.0755 | 30.98020 |
October | 744.00000 | 21.68577 | 35.75037 | -0.1682 | 6.77342 |
November | 720.00000 | 21.61008 | 37.78794 | -0.2351 | 7.20129 |
December | 744.00000 | 21.50134 | 25.38567 | -0.3913 | 9.17898 |
Annual Sum or Average | 8760.00000 | 21.65234 | 37.45788 | -0.6128 | 17.84083 |
Minimum of Months | 672.00000 | 21.39454 | 25.38567 | -1.2243 | 6.68022 |
Maximum of Months | 744.00000 | 21.76535 | 49.29467 | -0.1682 | 37.70613 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.56445 | 32.98715 | -0.3459 | 8.20640 |
February | 672.00000 | 21.22171 | 47.99849 | -0.3687 | 8.24434 |
March | 744.00000 | 21.66456 | 37.68275 | -0.2829 | 7.64126 |
April | 720.00000 | 21.96323 | 27.59697 | -0.1477 | 6.59668 |
May | 744.00000 | 21.94490 | 26.58398 | -1.1750 | 35.39456 |
June | 720.00000 | 21.92649 | 35.43454 | -1.0406 | 29.50341 |
July | 744.00000 | 21.81619 | 45.77244 | -1.0510 | 29.81774 |
August | 744.00000 | 21.88815 | 48.08966 | -1.0340 | 29.22178 |
September | 720.00000 | 21.94236 | 49.77568 | -1.0429 | 29.57813 |
October | 744.00000 | 21.89879 | 35.64648 | -0.1672 | 6.79039 |
November | 720.00000 | 21.64439 | 38.04250 | -0.2819 | 7.72755 |
December | 744.00000 | 21.22582 | 25.69974 | -0.5138 | 11.19304 |
Annual Sum or Average | 8760.00000 | 21.72765 | 37.52268 | -0.6229 | 17.55955 |
Minimum of Months | 672.00000 | 21.22171 | 25.69974 | -1.1750 | 6.59668 |
Maximum of Months | 744.00000 | 21.96323 | 49.77568 | -0.1477 | 35.39456 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.42218 | 32.68124 | -0.3948 | 8.45023 |
February | 672.00000 | 21.29711 | 47.00959 | -0.3418 | 7.62027 |
March | 744.00000 | 21.59501 | 37.14988 | -0.3120 | 7.46348 |
April | 720.00000 | 21.82546 | 27.45273 | -0.2697 | 7.11760 |
May | 744.00000 | 21.86957 | 26.50655 | -1.3468 | 43.33406 |
June | 720.00000 | 21.86297 | 36.06093 | -1.2443 | 38.32558 |
July | 744.00000 | 21.78304 | 46.59375 | -1.2162 | 36.97715 |
August | 744.00000 | 21.83831 | 48.90103 | -1.2000 | 36.27709 |
September | 720.00000 | 21.88204 | 50.47524 | -1.1908 | 35.82963 |
October | 744.00000 | 21.77332 | 35.29343 | -0.2528 | 7.03262 |
November | 720.00000 | 21.51468 | 37.27683 | -0.3356 | 7.91985 |
December | 744.00000 | 21.23117 | 25.23252 | -0.5022 | 10.44740 |
Annual Sum or Average | 8760.00000 | 21.65963 | 37.47219 | -0.7199 | 20.65367 |
Minimum of Months | 672.00000 | 21.23117 | 25.23252 | -1.3468 | 7.03262 |
Maximum of Months | 744.00000 | 21.88204 | 50.47524 | -0.2528 | 43.33406 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.67272 | 32.77894 | -0.2568 | 7.37452 |
February | 672.00000 | 21.49402 | 47.08941 | -0.2627 | 7.20143 |
March | 744.00000 | 21.62840 | 37.67846 | -0.2500 | 7.22393 |
April | 720.00000 | 21.74902 | 27.85946 | -0.1614 | 6.65827 |
May | 744.00000 | 21.75468 | 26.83814 | -1.2045 | 36.88306 |
June | 720.00000 | 21.76865 | 35.73419 | -1.0758 | 31.10024 |
July | 744.00000 | 21.76016 | 45.65847 | -1.0435 | 29.65099 |
August | 744.00000 | 21.75951 | 47.74525 | -1.0391 | 29.51957 |
September | 720.00000 | 21.75400 | 49.10544 | -1.0621 | 30.47528 |
October | 744.00000 | 21.72582 | 35.63288 | -0.1515 | 6.72719 |
November | 720.00000 | 21.64858 | 37.83572 | -0.2307 | 7.13847 |
December | 744.00000 | 21.56794 | 25.32805 | -0.3735 | 8.88580 |
Annual Sum or Average | 8760.00000 | 21.69147 | 37.35894 | -0.5949 | 17.47130 |
Minimum of Months | 672.00000 | 21.49402 | 25.32805 | -1.2045 | 6.65827 |
Maximum of Months | 744.00000 | 21.76865 | 49.10544 | -0.1515 | 36.88306 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.56801 | 32.98436 | -0.3472 | 8.05364 |
February | 672.00000 | 21.29549 | 47.62812 | -0.3421 | 7.81172 |
March | 744.00000 | 21.73984 | 37.48506 | -0.2582 | 7.25405 |
April | 720.00000 | 22.09859 | 27.42373 | -0.1132 | 6.80411 |
May | 744.00000 | 22.12666 | 26.50350 | -1.1084 | 33.85728 |
June | 720.00000 | 21.98463 | 35.53475 | -1.0110 | 28.94623 |
July | 744.00000 | 21.84904 | 45.71398 | -1.0189 | 28.82145 |
August | 744.00000 | 21.93336 | 47.92129 | -1.0016 | 28.31009 |
September | 720.00000 | 22.01441 | 49.43070 | -1.0114 | 28.87605 |
October | 744.00000 | 21.99730 | 35.37245 | -0.1388 | 6.76702 |
November | 720.00000 | 21.63572 | 38.08850 | -0.2886 | 7.63365 |
December | 744.00000 | 21.23276 | 25.66698 | -0.5076 | 10.85608 |
Annual Sum or Average | 8760.00000 | 21.79214 | 37.39450 | -0.5976 | 17.06312 |
Minimum of Months | 672.00000 | 21.23276 | 25.66698 | -1.1084 | 6.76702 |
Maximum of Months | 744.00000 | 22.12666 | 49.43070 | -0.1132 | 33.85728 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.58913 | 33.22589 | -0.2937 | 7.96838 |
February | 672.00000 | 21.34617 | 48.38930 | -0.3220 | 7.94325 |
March | 744.00000 | 21.50198 | 38.24728 | -0.2985 | 7.86256 |
April | 720.00000 | 21.70243 | 27.94538 | -0.1780 | 6.91040 |
May | 744.00000 | 21.73323 | 26.82877 | -1.2199 | 37.75453 |
June | 720.00000 | 21.76929 | 35.72759 | -1.0672 | 30.89901 |
July | 744.00000 | 21.75144 | 45.95635 | -1.0504 | 30.03656 |
August | 744.00000 | 21.75389 | 48.27511 | -1.0434 | 29.86158 |
September | 720.00000 | 21.74183 | 49.85528 | -1.0686 | 30.90180 |
October | 744.00000 | 21.66189 | 36.04342 | -0.1851 | 7.12802 |
November | 720.00000 | 21.57310 | 38.38483 | -0.2611 | 7.67068 |
December | 744.00000 | 21.45321 | 25.62674 | -0.4280 | 10.01086 |
Annual Sum or Average | 8760.00000 | 21.63310 | 37.78796 | -0.6201 | 17.98127 |
Minimum of Months | 672.00000 | 21.34617 | 25.62674 | -1.2199 | 6.91040 |
Maximum of Months | 744.00000 | 21.76929 | 49.85528 | -0.1780 | 37.75453 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.49519 | 33.44754 | -0.3855 | 8.96322 |
February | 672.00000 | 21.15400 | 48.88687 | -0.4047 | 8.98729 |
March | 744.00000 | 21.63778 | 38.09389 | -0.3020 | 8.13112 |
April | 720.00000 | 21.93277 | 27.72352 | -0.1516 | 6.82987 |
May | 744.00000 | 21.90406 | 26.65986 | -1.1795 | 35.77765 |
June | 720.00000 | 21.91430 | 35.59383 | -1.0218 | 28.92815 |
July | 744.00000 | 21.80802 | 45.95814 | -1.0350 | 29.32997 |
August | 744.00000 | 21.87518 | 48.38303 | -1.0213 | 28.87741 |
September | 720.00000 | 21.91195 | 50.30038 | -1.0435 | 29.71924 |
October | 744.00000 | 21.82906 | 36.01194 | -0.1942 | 7.20887 |
November | 720.00000 | 21.56105 | 38.71337 | -0.3208 | 8.42455 |
December | 744.00000 | 21.13789 | 26.01974 | -0.5629 | 12.44074 |
Annual Sum or Average | 8760.00000 | 21.68278 | 37.89196 | -0.6371 | 17.86657 |
Minimum of Months | 672.00000 | 21.13789 | 26.01974 | -1.1795 | 6.82987 |
Maximum of Months | 744.00000 | 21.93277 | 50.30038 | -0.1516 | 35.77765 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.70884 | 34.00935 | -0.1860 | 7.16548 |
February | 672.00000 | 21.55496 | 47.78091 | -0.2180 | 6.99720 |
March | 744.00000 | 21.62278 | 38.67035 | -0.2459 | 7.35154 |
April | 720.00000 | 21.70871 | 29.55772 | -0.2018 | 7.03186 |
May | 744.00000 | 21.72994 | 28.68084 | -1.2934 | 41.09995 |
June | 720.00000 | 21.75182 | 37.35775 | -1.1755 | 35.44935 |
July | 744.00000 | 21.74927 | 46.51380 | -1.1260 | 33.17768 |
August | 744.00000 | 21.74962 | 48.66845 | -1.1047 | 32.37464 |
September | 720.00000 | 21.75135 | 50.02593 | -1.0935 | 31.99100 |
October | 744.00000 | 21.71685 | 36.75678 | -0.1441 | 6.88456 |
November | 720.00000 | 21.68320 | 38.55457 | -0.1779 | 7.00478 |
December | 744.00000 | 21.66822 | 26.95129 | -0.2763 | 8.09924 |
Annual Sum or Average | 8760.00000 | 21.70056 | 38.54937 | -0.6061 | 18.79720 |
Minimum of Months | 672.00000 | 21.55496 | 26.95129 | -1.2934 | 6.88456 |
Maximum of Months | 744.00000 | 21.75182 | 50.02593 | -0.1441 | 41.09995 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.74584 | 30.62579 | 0.28458 | 6.95104 |
February | 672.00000 | 23.68775 | 43.26429 | 0.34682 | 7.86457 |
March | 744.00000 | 23.77282 | 35.06847 | 0.33492 | 7.64412 |
April | 720.00000 | 23.95297 | 26.44704 | 0.38489 | 8.23342 |
May | 744.00000 | 23.98426 | 25.51725 | -0.4273 | 8.92491 |
June | 720.00000 | 23.99462 | 35.80009 | -0.2977 | 6.98042 |
July | 744.00000 | 23.99429 | 52.06625 | -0.1957 | 6.00152 |
August | 744.00000 | 23.99202 | 54.84103 | -0.1901 | 5.88549 |
September | 720.00000 | 23.98656 | 54.03203 | -0.2178 | 6.11937 |
October | 744.00000 | 23.88916 | 35.40718 | 0.40621 | 8.90279 |
November | 720.00000 | 23.78061 | 35.49212 | 0.33501 | 7.80212 |
December | 744.00000 | 23.64270 | 24.49542 | 0.19382 | 6.09609 |
Annual Sum or Average | 8760.00000 | 23.86946 | 37.70740 | 0.07792 | 7.27905 |
Minimum of Months | 672.00000 | 23.64270 | 24.49542 | -0.4273 | 5.88549 |
Maximum of Months | 744.00000 | 23.99462 | 54.84103 | 0.40621 | 8.92491 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.86038 | 29.80589 | 0.34641 | 7.67700 |
February | 672.00000 | 23.82651 | 42.26314 | 0.41781 | 8.89081 |
March | 744.00000 | 23.88143 | 34.22452 | 0.39684 | 8.49067 |
April | 720.00000 | 23.97942 | 25.93481 | 0.41999 | 8.80758 |
May | 744.00000 | 23.99281 | 25.09438 | -0.3858 | 8.21311 |
June | 720.00000 | 23.99577 | 35.45379 | -0.2611 | 6.55712 |
July | 744.00000 | 23.99546 | 51.70813 | -0.1594 | 5.73504 |
August | 744.00000 | 23.99454 | 54.46869 | -0.1531 | 5.62219 |
September | 720.00000 | 23.99286 | 53.62990 | -0.1794 | 5.79886 |
October | 744.00000 | 23.94086 | 34.80808 | 0.44805 | 9.56958 |
November | 720.00000 | 23.88424 | 34.68550 | 0.39373 | 8.60650 |
December | 744.00000 | 23.79153 | 23.63396 | 0.26625 | 6.67552 |
Annual Sum or Average | 8760.00000 | 23.92843 | 37.09737 | 0.12721 | 7.54389 |
Minimum of Months | 672.00000 | 23.79153 | 23.63396 | -0.3858 | 5.62219 |
Maximum of Months | 744.00000 | 23.99577 | 54.46869 | 0.44805 | 9.56958 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.78288 | 29.13967 | 0.98245 | 27.76744 |
February | 672.00000 | 23.77890 | 41.28203 | 1.04577 | 30.25398 |
March | 744.00000 | 23.80687 | 33.63971 | 1.02702 | 29.49406 |
April | 720.00000 | 23.92485 | 25.98977 | 1.09002 | 31.94656 |
May | 744.00000 | 23.95614 | 25.35343 | 0.58317 | 16.18886 |
June | 720.00000 | 23.98717 | 35.66050 | 0.73315 | 19.83823 |
July | 744.00000 | 23.98737 | 51.44711 | 0.82053 | 22.53604 |
August | 744.00000 | 23.98344 | 54.09175 | 0.82460 | 22.69386 |
September | 720.00000 | 23.97649 | 53.21559 | 0.78271 | 21.29625 |
October | 744.00000 | 23.88929 | 34.45451 | 1.10455 | 32.76473 |
November | 720.00000 | 23.80243 | 34.01694 | 1.02523 | 29.52696 |
December | 744.00000 | 23.72842 | 22.85944 | 0.89737 | 24.72059 |
Annual Sum or Average | 8760.00000 | 23.88412 | 36.72037 | 0.90862 | 25.71640 |
Minimum of Months | 672.00000 | 23.72842 | 22.85944 | 0.58317 | 16.18886 |
Maximum of Months | 744.00000 | 23.98737 | 54.09175 | 1.10455 | 32.76473 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.55579 | 26.18729 | -0.3445 | 7.65144 |
February | 672.00000 | 21.15595 | 41.39604 | -0.3553 | 7.76122 |
March | 744.00000 | 21.51264 | 31.59749 | -0.3229 | 7.59500 |
April | 720.00000 | 22.88352 | 21.03365 | -0.0516 | 5.43341 |
May | 744.00000 | 23.47454 | 19.71707 | -0.8748 | 21.39724 |
June | 720.00000 | 23.96626 | 29.71698 | -0.6214 | 13.22009 |
July | 744.00000 | 23.95139 | 46.73234 | -0.5120 | 10.68835 |
August | 744.00000 | 23.88255 | 49.62034 | -0.5217 | 10.86871 |
September | 720.00000 | 23.77546 | 49.10879 | -0.5667 | 11.92907 |
October | 744.00000 | 22.70743 | 30.39235 | -0.0302 | 6.33607 |
November | 720.00000 | 21.75312 | 31.56326 | -0.2606 | 7.02578 |
December | 744.00000 | 21.22082 | 18.87825 | -0.4741 | 9.85425 |
Annual Sum or Average | 8760.00000 | 22.66076 | 32.92780 | -0.4122 | 10.00462 |
Minimum of Months | 672.00000 | 21.15595 | 18.87825 | -0.8748 | 5.43341 |
Maximum of Months | 744.00000 | 23.96626 | 49.62034 | -0.0302 | 21.39724 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.08552 | 29.56904 | -0.2247 | 6.25480 |
February | 672.00000 | 21.45690 | 44.77898 | -0.2900 | 6.84051 |
March | 744.00000 | 21.84191 | 35.12336 | -0.2500 | 6.64945 |
April | 720.00000 | 23.18617 | 25.12212 | 0.01666 | 5.34821 |
May | 744.00000 | 23.61903 | 24.12269 | -0.8404 | 20.07624 |
June | 720.00000 | 23.95085 | 33.97491 | -0.6479 | 13.92526 |
July | 744.00000 | 23.93041 | 50.74852 | -0.5433 | 11.36892 |
August | 744.00000 | 23.88741 | 53.63584 | -0.5399 | 11.23420 |
September | 720.00000 | 23.85858 | 52.95322 | -0.5564 | 11.61647 |
October | 744.00000 | 23.14955 | 34.00903 | 0.06987 | 6.05138 |
November | 720.00000 | 22.23311 | 34.97243 | -0.1539 | 5.87157 |
December | 744.00000 | 21.55357 | 22.61644 | -0.3968 | 8.57531 |
Annual Sum or Average | 8760.00000 | 22.90341 | 36.73716 | -0.3640 | 9.50931 |
Minimum of Months | 672.00000 | 21.45690 | 22.61644 | -0.8404 | 5.34821 |
Maximum of Months | 744.00000 | 23.95085 | 53.63584 | 0.06987 | 20.07624 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.91261 | 27.02321 | -0.2412 | 6.58433 |
February | 672.00000 | 21.40669 | 42.13422 | -0.2808 | 6.84790 |
March | 744.00000 | 21.80303 | 32.40653 | -0.2347 | 6.69983 |
April | 720.00000 | 23.26383 | 22.07899 | 0.07222 | 5.66323 |
May | 744.00000 | 23.65101 | 21.06084 | -0.7631 | 17.71976 |
June | 720.00000 | 23.93281 | 31.24444 | -0.5655 | 11.89962 |
July | 744.00000 | 23.93628 | 47.79367 | -0.4561 | 9.62697 |
August | 744.00000 | 23.88830 | 50.67361 | -0.4571 | 9.60528 |
September | 720.00000 | 23.82556 | 50.01124 | -0.4933 | 10.35934 |
October | 744.00000 | 22.90532 | 31.42263 | 0.04572 | 6.49730 |
November | 720.00000 | 22.00818 | 32.44623 | -0.1815 | 6.41659 |
December | 744.00000 | 21.47209 | 19.94285 | -0.4000 | 8.74205 |
Annual Sum or Average | 8760.00000 | 22.84089 | 33.95400 | -0.3304 | 8.90862 |
Minimum of Months | 672.00000 | 21.40669 | 19.94285 | -0.7631 | 5.66323 |
Maximum of Months | 744.00000 | 23.93628 | 50.67361 | 0.07222 | 17.71976 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.63603 | 25.71897 | -0.3269 | 7.44895 |
February | 672.00000 | 21.23537 | 40.86957 | -0.3368 | 7.53806 |
March | 744.00000 | 21.61104 | 31.08060 | -0.3003 | 7.35410 |
April | 720.00000 | 23.01046 | 20.53362 | -0.0212 | 5.44229 |
May | 744.00000 | 23.59004 | 19.25820 | -0.8313 | 19.84280 |
June | 720.00000 | 23.98181 | 29.39557 | -0.6051 | 12.79240 |
July | 744.00000 | 23.96423 | 46.33389 | -0.4976 | 10.38065 |
August | 744.00000 | 23.91197 | 49.17004 | -0.5029 | 10.45485 |
September | 720.00000 | 23.83357 | 48.56589 | -0.5401 | 11.30564 |
October | 744.00000 | 22.82042 | 29.86321 | -0.0028 | 6.31516 |
November | 720.00000 | 21.85362 | 31.02278 | -0.2379 | 6.84113 |
December | 744.00000 | 21.28355 | 18.48157 | -0.4597 | 9.60504 |
Annual Sum or Average | 8760.00000 | 22.73510 | 32.45749 | -0.3894 | 9.63276 |
Minimum of Months | 672.00000 | 21.23537 | 18.48157 | -0.8313 | 5.44229 |
Maximum of Months | 744.00000 | 23.98181 | 49.17004 | -0.0028 | 19.84280 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.581470E+11 | 111445.89 | 31-JAN-16:01 | 685.15 | 0.189243E+12 | 0.00 | 0.247390E+12 | 3.09 | 4.16 | 31-JAN-19:01 | 0.00 | 0.00 |
February | 0.186456E+11 | 70808.01 | 09-FEB-16:01 | 528.65 | 0.615216E+11 | 0.00 | 0.801672E+11 | 2.68 | 4.07 | 09-FEB-16:01 | 0.00 | 0.00 |
March | 0.544503E+11 | 105663.07 | 16-MAR-15:03 | 671.32 | 0.173316E+12 | 0.00 | 0.227767E+12 | 2.99 | 4.13 | 03-MAR-16:01 | 0.00 | 0.00 |
April | 0.144547E+12 | 141599.60 | 14-APR-18:03 | 719.75 | 0.469569E+12 | 0.00 | 0.614116E+12 | 3.26 | 4.12 | 03-APR-21:51 | 0.00 | 0.00 |
May | 0.187604E+12 | 153589.21 | 31-MAY-18:03 | 744.00 | 0.598986E+12 | 0.00 | 0.786589E+12 | 3.19 | 4.03 | 13-MAY-21:51 | 0.00 | 0.00 |
June | 0.250710E+12 | 190697.88 | 28-JUN-18:04 | 720.00 | 0.770244E+12 | 0.00 | 0.102095E+13 | 3.11 | 3.89 | 20-JUN-06:41 | 0.00 | 0.00 |
July | 0.265582E+12 | 174489.18 | 20-JUL-18:03 | 744.00 | 0.870349E+12 | 0.00 | 0.113593E+13 | 3.30 | 4.40 | 14-JUL-01:00 | 0.00 | 0.00 |
August | 0.258192E+12 | 181421.86 | 25-AUG-15:03 | 744.00 | 0.848422E+12 | 0.00 | 0.110661E+13 | 3.32 | 4.51 | 18-AUG-22:00 | 0.00 | 0.00 |
September | 0.227341E+12 | 167695.37 | 08-SEP-18:03 | 720.00 | 0.775380E+12 | 0.00 | 0.100272E+13 | 3.41 | 4.63 | 03-SEP-08:53 | 0.00 | 0.00 |
October | 0.127568E+12 | 149163.27 | 02-OCT-18:03 | 736.08 | 0.422058E+12 | 0.00 | 0.549626E+12 | 3.29 | 4.19 | 03-OCT-03:00 | 0.00 | 0.00 |
November | 0.617852E+11 | 110368.47 | 01-NOV-15:03 | 668.37 | 0.201931E+12 | 0.00 | 0.263716E+12 | 3.11 | 4.56 | 12-NOV-16:02 | 0.00 | 0.00 |
December | 0.345104E+11 | 93272.93 | 25-DEC-16:03 | 595.98 | 0.111753E+12 | 0.00 | 0.146263E+12 | 2.71 | 4.16 | 02-DEC-16:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.168908E+13 | 8277.31 | 0.549277E+13 | 0.00 | 0.718186E+13 | 3.12 | 0.00 | 0.00 | ||||
Minimum of Months | 0.186456E+11 | 70808.01 | 528.65 | 0.615216E+11 | 0.00 | 0.801672E+11 | 2.68 | 3.89 | 0.00 | 0.00 | ||
Maximum of Months | 0.265582E+12 | 190697.88 | 744.00 | 0.870349E+12 | 0.00 | 0.113593E+13 | 3.41 | 4.63 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.522493E+11 | 0.00 | 414.29 | 153038.25 | 01-JAN-00:10 | 0.00 | 45.10 | 65.71 | 0.12 | 0.00 | 0.06 | 0.45 | 01-JAN-00:10 |
February | 0.593167E+11 | 0.00 | 557.13 | 129376.60 | 03-FEB-07:05 | 0.00 | 43.90 | 73.17 | 0.15 | 0.00 | 0.07 | 0.38 | 03-FEB-07:05 |
March | 0.395670E+11 | 0.00 | 381.21 | 141317.24 | 26-MAR-08:03 | 0.00 | 41.03 | 60.13 | 0.09 | 0.00 | 0.04 | 0.41 | 26-MAR-08:03 |
April | 0.189051E+10 | 0.00 | 33.79 | 78856.42 | 21-APR-06:05 | 0.00 | 45.03 | 46.97 | 0.00 | 0.00 | 0.00 | 0.23 | 21-APR-06:05 |
May | 94145143.99 | 0.00 | 3.89 | 36987.42 | 02-MAY-08:44 | 0.00 | 52.19 | 52.35 | 0.00 | 0.00 | 0.00 | 0.11 | 02-MAY-08:44 |
June | 14481253.82 | 0.00 | 0.85 | 13087.83 | 27-JUN-08:06 | 0.00 | 57.03 | 57.06 | 0.00 | 0.00 | 0.00 | 0.04 | 27-JUN-08:06 |
July | 24528104.41 | 0.00 | 1.51 | 12243.17 | 03-JUL-08:06 | 0.00 | 59.71 | 59.74 | 0.00 | 0.00 | 0.00 | 0.04 | 03-JUL-08:06 |
August | 35291632.03 | 0.00 | 1.99 | 15781.92 | 22-AUG-08:06 | 0.00 | 60.68 | 60.73 | 0.00 | 0.00 | 0.00 | 0.05 | 22-AUG-08:06 |
September | 34870762.77 | 0.00 | 2.42 | 13355.82 | 23-SEP-08:55 | 0.00 | 61.06 | 61.12 | 0.00 | 0.00 | 0.00 | 0.04 | 23-SEP-08:55 |
October | 0.126883E+11 | 0.00 | 140.73 | 124926.18 | 25-OCT-08:03 | 0.00 | 51.16 | 58.21 | 0.03 | 0.00 | 0.01 | 0.37 | 25-OCT-08:03 |
November | 0.357855E+11 | 0.00 | 346.17 | 129653.99 | 23-NOV-19:03 | 0.00 | 45.39 | 62.48 | 0.08 | 0.00 | 0.04 | 0.38 | 23-NOV-19:03 |
December | 0.782579E+11 | 0.00 | 589.93 | 162599.47 | 06-DEC-09:01 | 0.00 | 46.29 | 73.93 | 0.19 | 0.00 | 0.09 | 0.48 | 06-DEC-09:01 |
Annual Sum or Average | 0.279959E+12 | 0.00 | 2473.90 | 0.00 | 50.75 | 60.91 | 0.06 | 0.00 | 0.03 | ||||
Minimum of Months | 14481253.82 | 0.00 | 0.85 | 12243.17 | 0.00 | 41.03 | 46.97 | 0.00 | 0.00 | 0.00 | 0.04 | ||
Maximum of Months | 0.782579E+11 | 0.00 | 589.93 | 162599.47 | 0.00 | 61.06 | 73.93 | 0.19 | 0.00 | 0.09 | 0.48 |
Report: DXReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.479448E+11 | 0.00 | 387.56 | 0.479448E+11 | -0.0 | 0.00 | 1.00 | 01-JAN-06:15 | 0.00 | 01-JAN-00:10 | 50005.68 | 23-JAN-08:50 | 50005.68 | 23-JAN-06:50 | 0.00 | 03-JAN-07:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.429777E+11 | 0.00 | 352.25 | 0.412571E+11 | 0.172057E+10 | 0.00 | 1.00 | 01-FEB-06:15 | 0.00 | 01-FEB-00:05 | 50632.36 | 01-FEB-06:15 | 48540.52 | 01-FEB-21:20 | 2094.91 | 01-FEB-06:15 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 0.451658E+11 | 0.00 | 378.40 | 0.451658E+11 | -0.0 | 0.00 | 1.00 | 01-MAR-06:15 | 0.00 | 01-MAR-00:05 | 51140.41 | 01-MAR-06:15 | 51140.41 | 01-MAR-07:15 | 0.00 | 28-MAR-06:30 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 0.408598E+11 | 0.00 | 349.65 | 0.408598E+11 | -0.0 | 0.00 | 1.00 | 01-APR-05:17 | 0.00 | 01-APR-00:10 | 55691.74 | 01-APR-05:17 | 55691.74 | 01-APR-10:04 | 0.00 | 05-APR-10:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.380775E+11 | 0.00 | 359.76 | 0.380775E+11 | -0.0 | 0.00 | 1.00 | 01-MAY-06:15 | 0.00 | 01-MAY-00:05 | 56749.03 | 01-MAY-06:15 | 56749.03 | 01-MAY-07:14 | 0.00 | 24-MAY-06:15 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.341349E+11 | 0.00 | 336.75 | 0.341349E+11 | 0.00 | 0.00 | 1.00 | 01-JUN-05:10 | 0.00 | 01-JUN-00:05 | 60458.41 | 01-JUN-05:10 | 60458.41 | 01-JUN-05:10 | 0.00 | 29-JUN-10:18 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.338582E+11 | 0.00 | 347.17 | 0.338582E+11 | -0.0 | 0.00 | 1.00 | 01-JUL-05:08 | 0.00 | 01-JUL-00:20 | 62130.92 | 01-JUL-05:08 | 62130.92 | 01-JUL-07:12 | 0.00 | 03-JUL-17:17 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.344209E+11 | 0.00 | 346.21 | 0.344209E+11 | 0.00 | 0.00 | 1.00 | 01-AUG-05:10 | 0.00 | 01-AUG-00:05 | 62274.97 | 31-AUG-05:10 | 62274.97 | 31-AUG-07:15 | 0.00 | 15-AUG-10:37 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.357718E+11 | 0.00 | 336.66 | 0.357718E+11 | -0.0 | 0.00 | 1.00 | 01-SEP-05:10 | 0.00 | 01-SEP-00:05 | 62074.83 | 30-SEP-05:08 | 62074.83 | 30-SEP-07:15 | 0.00 | 24-SEP-08:54 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.396390E+11 | 0.00 | 357.95 | 0.396390E+11 | 0.00 | 0.00 | 1.00 | 01-OCT-05:10 | 0.00 | 01-OCT-00:20 | 54713.42 | 31-OCT-05:15 | 54713.42 | 31-OCT-07:13 | 0.00 | 29-OCT-07:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.416766E+11 | 0.00 | 362.28 | 0.416766E+11 | -0.0 | 0.00 | 1.00 | 01-NOV-05:15 | 0.00 | 01-NOV-00:05 | 50952.66 | 30-NOV-06:15 | 50952.66 | 30-NOV-11:37 | 0.00 | 28-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.450274E+11 | 0.00 | 393.34 | 0.450274E+11 | 0.00 | 0.00 | 1.00 | 01-DEC-04:10 | 0.00 | 01-DEC-00:05 | 45484.54 | 31-DEC-02:10 | 45484.54 | 31-DEC-07:20 | 0.00 | 03-DEC-08:30 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.479554E+12 | 0.00 | 4307.99 | 0.477834E+12 | 0.172057E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.338582E+11 | 0.00 | 336.66 | 0.338582E+11 | -0.0 | 0.00 | 1.00 | 0.00 | 45484.54 | 45484.54 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.479448E+11 | 0.00 | 393.34 | 0.479448E+11 | 0.172057E+10 | 0.00 | 1.00 | 0.00 | 62274.97 | 62274.97 | 2094.91 | 0.00 | 0.00 |
Report: DXReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.501268E+11 | 0.00 | 354.97 | 0.501268E+11 | -0.0 | 0.00 | 1.00 | 01-JAN-17:10 | 0.00 | 01-JAN-00:10 | 63283.04 | 23-JAN-17:10 | 63283.04 | 23-JAN-17:30 | 0.00 | 06-JAN-19:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.457469E+11 | 0.00 | 338.43 | 0.439298E+11 | 0.181714E+10 | 0.00 | 1.00 | 01-FEB-17:10 | 0.00 | 01-FEB-00:10 | 64076.57 | 01-FEB-17:10 | 61448.63 | 01-FEB-20:00 | 2629.37 | 01-FEB-17:10 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 0.509446E+11 | 0.00 | 349.19 | 0.509446E+11 | -0.0 | 0.00 | 1.00 | 01-MAR-17:10 | 0.00 | 01-MAR-00:10 | 64719.88 | 01-MAR-17:10 | 64719.88 | 01-MAR-17:10 | 0.00 | 26-MAR-22:10 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 0.536847E+11 | 0.00 | 336.79 | 0.536847E+11 | -0.0 | 0.00 | 1.00 | 01-APR-16:10 | 0.00 | 01-APR-00:20 | 70482.94 | 01-APR-16:10 | 70482.94 | 01-APR-16:10 | 0.00 | 05-APR-22:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.566123E+11 | 0.00 | 345.34 | 0.566123E+11 | -0.0 | 0.00 | 1.00 | 01-MAY-16:10 | 0.00 | 01-MAY-00:05 | 71821.71 | 01-MAY-19:20 | 71821.71 | 01-MAY-16:50 | 0.00 | 08-MAY-22:10 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.585014E+11 | 0.00 | 324.97 | 0.585014E+11 | 0.00 | 0.00 | 1.00 | 01-JUN-16:10 | 0.00 | 01-JUN-00:05 | 76518.66 | 01-JUN-16:10 | 76518.66 | 01-JUN-16:10 | 0.00 | 02-JUN-16:30 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.623813E+11 | 0.00 | 337.75 | 0.623813E+11 | -0.0 | 0.00 | 1.00 | 01-JUL-16:10 | 0.00 | 01-JUL-00:10 | 78636.46 | 01-JUL-19:10 | 78636.46 | 01-JUL-19:10 | 0.00 | 11-JUL-16:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.623611E+11 | 0.00 | 338.32 | 0.623611E+11 | 0.00 | 0.00 | 1.00 | 01-AUG-16:10 | 0.00 | 01-AUG-00:05 | 78818.87 | 31-AUG-16:10 | 78818.87 | 31-AUG-16:10 | 0.00 | 22-AUG-17:40 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.598770E+11 | 0.00 | 327.66 | 0.598770E+11 | -0.0 | 0.00 | 1.00 | 01-SEP-16:10 | 0.00 | 01-SEP-00:05 | 78565.43 | 30-SEP-16:10 | 78565.43 | 30-SEP-16:20 | 0.00 | 04-SEP-16:10 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.543738E+11 | 0.00 | 348.46 | 0.543738E+11 | 0.00 | 0.00 | 1.00 | 01-OCT-16:10 | 0.00 | 01-OCT-00:20 | 69244.15 | 31-OCT-16:10 | 69244.15 | 31-OCT-16:10 | 0.00 | 06-OCT-17:25 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.490453E+11 | 0.00 | 337.69 | 0.490453E+11 | -0.0 | 0.00 | 1.00 | 01-NOV-16:10 | 0.00 | 01-NOV-00:05 | 64482.14 | 30-NOV-17:10 | 64482.14 | 30-NOV-21:10 | 0.00 | 15-NOV-23:20 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.454228E+11 | 0.00 | 375.71 | 0.454228E+11 | 0.00 | 0.00 | 1.00 | 01-DEC-17:10 | 0.00 | 01-DEC-00:10 | 57558.21 | 31-DEC-21:13 | 57558.21 | 31-DEC-21:05 | 0.00 | 05-DEC-18:00 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.649078E+12 | 0.00 | 4115.28 | 0.647261E+12 | 0.181714E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.454228E+11 | 0.00 | 324.97 | 0.439298E+11 | -0.0 | 0.00 | 1.00 | 0.00 | 57558.21 | 57558.21 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.623813E+11 | 0.00 | 375.71 | 0.623813E+11 | 0.181714E+10 | 0.00 | 1.00 | 0.00 | 78818.87 | 78818.87 | 2629.37 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.104113E+12 | 0.00 | 376.36 | 0.103683E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 175247.19 | 31-JAN-16:30 | 175247.19 | 31-JAN-16:30 | 0.00 | 0.00 | 0.00 |
February | 0.254135E+11 | 0.00 | 218.50 | 0.253868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103488.11 | 18-FEB-14:00 | 103488.11 | 18-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.113067E+12 | 0.00 | 421.06 | 0.113067E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 191576.16 | 20-MAR-18:10 | 191576.16 | 20-MAR-18:10 | 0.00 | 0.00 | 0.00 |
April | 0.312352E+12 | 0.00 | 658.67 | 0.312352E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 256058.23 | 14-APR-18:03 | 256058.23 | 14-APR-18:03 | 0.00 | 0.00 | 0.00 |
May | 0.407289E+12 | 0.00 | 734.83 | 0.407289E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 267662.90 | 31-MAY-18:20 | 267662.90 | 31-MAY-18:20 | 0.00 | 0.00 | 0.00 |
June | 0.517999E+12 | 0.00 | 720.00 | 0.517076E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 331934.51 | 17-JUN-17:17 | 317522.75 | 28-JUN-18:40 | 0.00 | 0.00 | 0.00 |
July | 0.601837E+12 | 0.00 | 744.00 | 0.523581E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 397546.17 | 13-JUL-18:03 | 305650.47 | 21-JUL-20:10 | 0.00 | 0.00 | 0.00 |
August | 0.587308E+12 | 0.00 | 744.00 | 0.515820E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 428459.16 | 18-AUG-22:00 | 296813.64 | 25-AUG-18:20 | 0.00 | 0.00 | 0.00 |
September | 0.539199E+12 | 0.00 | 720.00 | 0.463913E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 456570.15 | 10-SEP-20:40 | 294506.61 | 08-SEP-20:10 | 0.00 | 0.00 | 0.00 |
October | 0.274308E+12 | 0.00 | 604.50 | 0.266176E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 328698.51 | 02-OCT-20:00 | 268286.74 | 04-OCT-18:15 | 0.00 | 0.00 | 0.00 |
November | 0.118824E+12 | 0.00 | 421.79 | 0.105397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 194134.92 | 01-NOV-18:04 | 194134.92 | 01-NOV-18:04 | 0.00 | 0.00 | 0.00 |
December | 0.554235E+11 | 0.00 | 293.76 | 0.554235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 151356.41 | 22-DEC-16:08 | 151356.41 | 22-DEC-16:08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.365713E+13 | 0.00 | 6657.47 | 0.340916E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.254135E+11 | 0.00 | 218.50 | 0.253868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103488.11 | 103488.11 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.601837E+12 | 0.00 | 744.00 | 0.523581E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 456570.15 | 317522.75 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.673483E+10 | 0.00 | 239.17 | 0.667920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17033.11 | 31-JAN-16:01 | 17033.11 | 31-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.173087E+10 | 0.00 | 131.50 | 0.173087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13753.19 | 18-FEB-14:00 | 13753.19 | 18-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.788829E+10 | 0.00 | 282.00 | 0.788829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17335.41 | 16-MAR-15:01 | 17335.41 | 16-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.209353E+11 | 0.00 | 514.83 | 0.209353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19381.36 | 14-APR-15:02 | 19381.36 | 14-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.271398E+11 | 0.00 | 580.50 | 0.271398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19739.01 | 31-MAY-15:02 | 19739.01 | 31-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.322302E+11 | 0.00 | 570.00 | 0.321956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23390.50 | 17-JUN-16:00 | 21846.18 | 28-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.381408E+11 | 0.00 | 589.00 | 0.329353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30505.29 | 27-JUL-06:50 | 21327.50 | 19-JUL-13:00 | 0.00 | 0.00 | 0.00 |
August | 0.378353E+11 | 0.00 | 589.00 | 0.325800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34897.84 | 05-AUG-08:10 | 21421.42 | 25-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.358848E+11 | 0.00 | 570.00 | 0.298955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38778.16 | 02-SEP-21:51 | 20640.11 | 08-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.181404E+11 | 0.00 | 461.33 | 0.174558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28988.59 | 03-OCT-08:61 | 20196.64 | 01-OCT-13:00 | 0.00 | 0.00 | 0.00 |
November | 0.850451E+10 | 0.00 | 283.00 | 0.712220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24612.65 | 12-NOV-13:40 | 17436.07 | 01-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.357415E+10 | 0.00 | 152.17 | 0.357415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15816.12 | 25-DEC-16:01 | 15816.12 | 25-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238739E+12 | 0.00 | 4962.50 | 0.220132E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.173087E+10 | 0.00 | 131.50 | 0.173087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13753.19 | 13753.19 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.381408E+11 | 0.00 | 589.00 | 0.329353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38778.16 | 21846.18 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.329611E+10 | 0.00 | 452.67 | 0.312237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15754.45 | 14-JAN-16:01 | 15754.45 | 14-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.103762E+10 | 0.00 | 203.83 | 0.840036E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14984.97 | 09-FEB-16:01 | 14984.97 | 09-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.255717E+10 | 0.00 | 400.47 | 0.217631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15771.97 | 16-MAR-15:01 | 15771.97 | 16-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.856984E+10 | 0.00 | 674.03 | 0.838302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15776.38 | 25-APR-15:02 | 15776.38 | 25-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.103449E+11 | 0.00 | 713.92 | 0.102701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15770.49 | 10-MAY-18:02 | 15770.49 | 10-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.136647E+11 | 0.00 | 704.95 | 0.127924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15778.25 | 22-JUN-08:62 | 15778.25 | 22-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.134399E+11 | 0.00 | 724.72 | 0.990940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17326.61 | 27-JUL-08:61 | 15774.75 | 05-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.132283E+11 | 0.00 | 722.52 | 0.946548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17524.44 | 04-AUG-08:61 | 15771.28 | 25-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.115249E+11 | 0.00 | 694.88 | 0.777417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18513.58 | 04-SEP-08:61 | 15779.14 | 28-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.708136E+10 | 0.00 | 621.40 | 0.587925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16801.33 | 03-OCT-08:61 | 15778.30 | 20-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.339622E+10 | 0.00 | 464.33 | 0.279351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17262.23 | 12-NOV-16:02 | 15761.75 | 20-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.158942E+10 | 0.00 | 277.37 | 0.158844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15652.64 | 25-DEC-16:01 | 15652.64 | 25-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.897304E+11 | 0.00 | 6655.08 | 0.749946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.103762E+10 | 0.00 | 203.83 | 0.840036E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14984.97 | 14984.97 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.136647E+11 | 0.00 | 724.72 | 0.127924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18513.58 | 15779.14 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.759514E+09 | 0.00 | 156.79 | 0.712087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15638.67 | 14-JAN-16:01 | 15638.67 | 14-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.192908E+09 | 0.00 | 58.63 | 0.157466E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14608.27 | 28-FEB-16:01 | 14608.27 | 28-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.105003E+10 | 0.00 | 205.94 | 0.863321E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15658.15 | 16-MAR-15:01 | 15658.15 | 16-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.701342E+10 | 0.00 | 577.00 | 0.686176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16067.60 | 26-APR-08:41 | 16067.60 | 26-APR-08:41 | 0.00 | 0.00 | 0.00 |
May | 0.970403E+10 | 0.00 | 633.44 | 0.964531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17330.45 | 08-MAY-08:61 | 17330.45 | 08-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.135659E+11 | 0.00 | 664.53 | 0.127242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17448.66 | 14-JUN-08:61 | 17448.66 | 14-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.132667E+11 | 0.00 | 703.94 | 0.980455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19507.59 | 27-JUL-08:11 | 17896.31 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.122921E+11 | 0.00 | 676.72 | 0.875982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19587.47 | 28-AUG-18:31 | 16732.09 | 25-AUG-07:31 | 0.00 | 0.00 | 0.00 |
September | 0.992510E+10 | 0.00 | 619.60 | 0.657654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19965.47 | 04-SEP-08:51 | 15663.74 | 29-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.446806E+10 | 0.00 | 435.56 | 0.349845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19474.70 | 03-OCT-08:61 | 15663.48 | 20-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.104709E+10 | 0.00 | 214.59 | 0.783906E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17360.35 | 13-NOV-16:01 | 15647.17 | 20-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.229621E+09 | 0.00 | 53.96 | 0.229508E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15538.70 | 25-DEC-16:01 | 15538.70 | 25-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.735145E+11 | 0.00 | 5000.70 | 0.606169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.192908E+09 | 0.00 | 53.96 | 0.157466E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14608.27 | 14608.27 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.135659E+11 | 0.00 | 703.94 | 0.127242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19965.47 | 17896.31 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.428116E+11 | 0.00 | 566.17 | 0.422562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50051.37 | 14-JAN-13:50 | 50051.37 | 14-JAN-13:50 | 0.00 | 0.00 | 0.00 |
February | 0.137627E+11 | 0.00 | 319.57 | 0.120945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37257.07 | 01-FEB-14:20 | 37257.07 | 01-FEB-14:20 | 0.00 | 0.00 | 0.00 |
March | 0.166165E+11 | 0.00 | 431.13 | 0.155726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35158.70 | 18-MAR-13:50 | 34509.23 | 18-MAR-15:03 | 0.00 | 0.00 | 0.00 |
April | 0.404277E+11 | 0.00 | 674.53 | 0.402191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36751.51 | 14-APR-13:40 | 36751.51 | 14-APR-13:40 | 0.00 | 0.00 | 0.00 |
May | 0.409313E+11 | 0.00 | 733.41 | 0.409313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29724.55 | 09-MAY-17:20 | 29724.55 | 09-MAY-17:20 | 0.00 | 0.00 | 0.00 |
June | 0.539388E+11 | 0.00 | 720.00 | 0.520781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37318.23 | 28-JUN-17:15 | 37318.23 | 28-JUN-17:15 | 0.00 | 0.00 | 0.00 |
July | 0.574046E+11 | 0.00 | 744.00 | 0.365001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36565.36 | 23-JUL-08:00 | 32467.50 | 07-JUL-17:20 | 0.00 | 0.00 | 0.00 |
August | 0.606380E+11 | 0.00 | 742.75 | 0.383410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44698.93 | 28-AUG-12:30 | 42246.51 | 27-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.605291E+11 | 0.00 | 720.00 | 0.410281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49017.14 | 28-SEP-13:30 | 48593.34 | 28-SEP-13:40 | 0.00 | 0.00 | 0.00 |
October | 0.501088E+11 | 0.00 | 664.98 | 0.437793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50188.51 | 18-OCT-13:50 | 50188.51 | 18-OCT-13:50 | 0.00 | 0.00 | 0.00 |
November | 0.365164E+11 | 0.00 | 541.16 | 0.329734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52279.83 | 20-NOV-14:30 | 52279.83 | 20-NOV-14:30 | 0.00 | 0.00 | 0.00 |
December | 0.298966E+11 | 0.00 | 460.74 | 0.297814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49552.87 | 25-DEC-13:40 | 49552.87 | 25-DEC-13:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.503582E+12 | 0.00 | 7318.43 | 0.425555E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.137627E+11 | 0.00 | 319.57 | 0.120945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29724.55 | 29724.55 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.606380E+11 | 0.00 | 744.00 | 0.520781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52279.83 | 52279.83 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.730109E+10 | 0.00 | 279.60 | 0.655732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91840.99 | 27-JAN-16:01 | 91840.99 | 27-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.614641E+10 | 0.00 | 260.38 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83937.34 | 18-FEB-16:01 | 82330.78 | 09-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.130380E+11 | 0.00 | 333.62 | 0.105506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94177.33 | 16-MAR-15:01 | 94177.33 | 16-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.397296E+11 | 0.00 | 515.49 | 0.388675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94210.62 | 25-APR-15:02 | 94210.62 | 25-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.560950E+11 | 0.00 | 596.61 | 0.558059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99554.07 | 20-MAY-08:61 | 99554.07 | 20-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.783339E+11 | 0.00 | 646.58 | 0.730647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 101572.92 | 11-JUN-08:61 | 101572.92 | 11-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.834699E+11 | 0.00 | 680.00 | 0.625755E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110338.33 | 27-JUL-08:11 | 102433.01 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.755523E+11 | 0.00 | 652.20 | 0.539590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 115898.68 | 28-AUG-18:31 | 95113.00 | 26-AUG-07:11 | 0.00 | 0.00 | 0.00 |
September | 0.637333E+11 | 0.00 | 588.64 | 0.431307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 113258.32 | 04-SEP-08:51 | 94247.36 | 29-SEP-08:21 | 0.00 | 0.00 | 0.00 |
October | 0.303180E+11 | 0.00 | 454.59 | 0.243818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109791.66 | 03-OCT-08:61 | 94207.97 | 06-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.105451E+11 | 0.00 | 287.16 | 0.749942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98136.77 | 13-NOV-16:01 | 92681.29 | 20-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.328537E+10 | 0.00 | 161.14 | 0.324031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89932.30 | 25-DEC-16:01 | 89932.30 | 25-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.467548E+12 | 0.00 | 5456.02 | 0.383031E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.328537E+10 | 0.00 | 161.14 | 0.324031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83937.34 | 82330.78 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.834699E+11 | 0.00 | 680.00 | 0.730647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 115898.68 | 102433.01 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.313128E+10 | 0.00 | 460.80 | 0.295795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13785.41 | 14-JAN-16:01 | 13785.41 | 14-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.124973E+10 | 0.00 | 263.09 | 0.940675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13112.48 | 09-FEB-16:01 | 13112.48 | 09-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.268518E+10 | 0.00 | 454.23 | 0.223740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13801.46 | 16-MAR-15:01 | 13801.46 | 16-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.872733E+10 | 0.00 | 698.20 | 0.855249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13805.68 | 25-APR-15:02 | 13805.68 | 25-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.107425E+11 | 0.00 | 731.40 | 0.106809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13800.08 | 10-MAY-18:02 | 13800.08 | 10-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.140170E+11 | 0.00 | 712.86 | 0.133729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13806.74 | 21-JUN-18:02 | 13806.74 | 21-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.143522E+11 | 0.00 | 734.03 | 0.111290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14177.43 | 09-JUL-08:61 | 13804.11 | 05-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.139996E+11 | 0.00 | 732.38 | 0.105750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15227.59 | 04-AUG-08:61 | 13806.29 | 27-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.119586E+11 | 0.00 | 703.89 | 0.846719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15763.48 | 03-SEP-08:61 | 13806.30 | 29-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.738676E+10 | 0.00 | 649.06 | 0.625552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13806.42 | 20-OCT-15:02 | 13806.42 | 20-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.312494E+10 | 0.00 | 465.42 | 0.260635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15582.49 | 13-NOV-16:01 | 13792.29 | 20-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.160238E+10 | 0.00 | 290.00 | 0.159491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13696.61 | 25-DEC-16:01 | 13696.61 | 25-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.929774E+11 | 0.00 | 6895.37 | 0.793704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.124973E+10 | 0.00 | 263.09 | 0.940675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13112.48 | 13112.48 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.143522E+11 | 0.00 | 734.03 | 0.133729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15763.48 | 13806.74 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.722099E+09 | 0.00 | 164.68 | 0.660865E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13690.08 | 14-JAN-16:01 | 13690.08 | 14-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.355271E+09 | 0.00 | 87.11 | 0.221937E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12429.67 | 09-FEB-16:01 | 12429.67 | 09-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.124233E+10 | 0.00 | 253.60 | 0.997063E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13707.02 | 16-MAR-15:01 | 13707.02 | 16-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.697595E+10 | 0.00 | 597.19 | 0.683296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15795.19 | 14-APR-08:41 | 15795.19 | 14-APR-08:41 | 0.00 | 0.00 | 0.00 |
May | 0.977124E+10 | 0.00 | 646.69 | 0.972326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17203.91 | 21-MAY-08:61 | 17203.91 | 21-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.138127E+11 | 0.00 | 673.84 | 0.131743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17041.83 | 13-JUN-07:52 | 17041.83 | 13-JUN-07:52 | 0.00 | 0.00 | 0.00 |
July | 0.141252E+11 | 0.00 | 712.85 | 0.109503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17730.22 | 27-JUL-08:11 | 17201.16 | 01-JUL-07:42 | 0.00 | 0.00 | 0.00 |
August | 0.129789E+11 | 0.00 | 685.42 | 0.965962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17436.54 | 28-AUG-18:31 | 15871.20 | 24-AUG-08:21 | 0.00 | 0.00 | 0.00 |
September | 0.102597E+11 | 0.00 | 627.21 | 0.704191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18743.75 | 04-SEP-08:51 | 14436.23 | 15-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.467521E+10 | 0.00 | 467.23 | 0.370896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17794.70 | 03-OCT-08:61 | 15097.24 | 17-OCT-08:51 | 0.00 | 0.00 | 0.00 |
November | 0.916822E+09 | 0.00 | 197.64 | 0.691117E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15043.34 | 13-NOV-16:01 | 14102.75 | 10-NOV-09:51 | 0.00 | 0.00 | 0.00 |
December | 0.243553E+09 | 0.00 | 64.73 | 0.241943E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13602.85 | 25-DEC-16:01 | 13602.85 | 25-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.760790E+11 | 0.00 | 5178.18 | 0.639042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.243553E+09 | 0.00 | 64.73 | 0.221937E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12429.67 | 12429.67 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.141252E+11 | 0.00 | 712.85 | 0.131743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18743.75 | 17203.91 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.768928E+09 | 0.00 | 378.91 | 0.735741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4203.09 | 14-JAN-16:01 | 4203.09 | 14-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.244785E+09 | 0.00 | 167.57 | 0.202265E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3997.80 | 09-FEB-16:01 | 3997.80 | 09-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.629867E+09 | 0.00 | 351.41 | 0.542883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4207.78 | 16-MAR-15:01 | 4207.78 | 16-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.217993E+10 | 0.00 | 660.39 | 0.213141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4208.97 | 25-APR-15:02 | 4208.97 | 25-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.265007E+10 | 0.00 | 712.26 | 0.263061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4207.33 | 10-MAY-18:02 | 4207.33 | 10-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.361201E+10 | 0.00 | 704.07 | 0.337249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4209.11 | 04-JUN-18:02 | 4209.11 | 04-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.352819E+10 | 0.00 | 724.59 | 0.259303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4793.99 | 27-JUL-08:61 | 4208.50 | 05-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.345140E+10 | 0.00 | 721.40 | 0.246039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4849.37 | 04-AUG-08:61 | 4207.48 | 25-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.292631E+10 | 0.00 | 692.66 | 0.194366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5176.47 | 04-SEP-08:61 | 4209.33 | 29-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.169627E+10 | 0.00 | 578.35 | 0.139032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4677.36 | 03-OCT-08:61 | 4209.49 | 20-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.778248E+09 | 0.00 | 395.03 | 0.648690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4607.63 | 12-NOV-16:02 | 4205.06 | 20-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.370822E+09 | 0.00 | 226.14 | 0.370756E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4175.88 | 25-DEC-16:01 | 4175.88 | 25-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.228368E+11 | 0.00 | 6312.77 | 0.190222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.244785E+09 | 0.00 | 167.57 | 0.202265E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3997.80 | 3997.80 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.361201E+10 | 0.00 | 724.59 | 0.337249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5176.47 | 4209.49 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.161627E+09 | 0.00 | 105.61 | 0.155307E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4168.87 | 14-JAN-16:01 | 4168.87 | 14-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 40547484.80 | 0.00 | 36.21 | 33477486.24 | 0.00 | 0.00 | 0.00 | 0.00 | 3908.96 | 09-FEB-16:01 | 3908.96 | 09-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.251363E+09 | 0.00 | 162.61 | 0.208248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4173.98 | 16-MAR-15:01 | 4173.98 | 16-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.180650E+10 | 0.00 | 569.47 | 0.176549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4241.85 | 26-APR-08:41 | 4241.85 | 26-APR-08:41 | 0.00 | 0.00 | 0.00 |
May | 0.251760E+10 | 0.00 | 635.23 | 0.250166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4572.53 | 08-MAY-08:61 | 4572.53 | 08-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.360752E+10 | 0.00 | 664.72 | 0.337225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4601.13 | 14-JUN-08:61 | 4601.13 | 14-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.349350E+10 | 0.00 | 704.20 | 0.257573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5262.68 | 27-JUL-08:11 | 4714.06 | 01-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.322769E+10 | 0.00 | 677.26 | 0.228902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5290.81 | 28-AUG-18:31 | 4373.67 | 24-AUG-08:21 | 0.00 | 0.00 | 0.00 |
September | 0.254267E+10 | 0.00 | 619.88 | 0.166012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5444.32 | 04-SEP-08:51 | 4175.52 | 29-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.106801E+10 | 0.00 | 397.29 | 0.820019E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5295.25 | 03-OCT-08:61 | 4175.47 | 20-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.219824E+09 | 0.00 | 152.29 | 0.168781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4700.06 | 13-NOV-16:01 | 4171.11 | 20-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 48464492.11 | 0.00 | 34.80 | 48464492.11 | 0.00 | 0.00 | 0.00 | 0.00 | 4142.19 | 25-DEC-16:01 | 4142.19 | 25-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189853E+11 | 0.00 | 4759.56 | 0.155986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 40547484.80 | 0.00 | 34.80 | 33477486.24 | 0.00 | 0.00 | 0.00 | 0.00 | 3908.96 | 3908.96 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.360752E+10 | 0.00 | 704.20 | 0.337225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5444.32 | 4714.06 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.100092E+11 | 0.00 | 614.16 | 0.962246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18409.92 | 14-JAN-16:01 | 18409.92 | 14-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.407910E+10 | 0.00 | 384.39 | 0.324475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17510.56 | 09-FEB-16:01 | 17510.56 | 09-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.504670E+10 | 0.00 | 498.48 | 0.423207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18428.26 | 16-MAR-15:01 | 18428.26 | 16-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.108396E+11 | 0.00 | 670.98 | 0.105204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18426.04 | 12-APR-18:01 | 18426.04 | 12-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.114508E+11 | 0.00 | 705.99 | 0.113594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18425.83 | 10-MAY-18:02 | 18425.83 | 10-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.151459E+11 | 0.00 | 698.48 | 0.138571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18428.17 | 16-JUN-08:61 | 18428.17 | 16-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.166655E+11 | 0.00 | 720.50 | 0.123382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20777.39 | 27-JUL-08:61 | 18427.65 | 03-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.172799E+11 | 0.00 | 720.01 | 0.126056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21167.39 | 04-AUG-08:61 | 18427.12 | 25-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.165638E+11 | 0.00 | 694.79 | 0.117511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21926.66 | 04-SEP-08:61 | 18427.68 | 18-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.125328E+11 | 0.00 | 664.76 | 0.109093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19559.93 | 03-OCT-08:61 | 18418.30 | 19-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.882525E+10 | 0.00 | 575.96 | 0.781353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20178.02 | 12-NOV-09:02 | 18416.98 | 20-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.730529E+10 | 0.00 | 491.27 | 0.727561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18287.81 | 25-DEC-16:01 | 18287.81 | 25-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135744E+12 | 0.00 | 7439.76 | 0.115529E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.407910E+10 | 0.00 | 384.39 | 0.324475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17510.56 | 17510.56 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.172799E+11 | 0.00 | 720.50 | 0.138571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21926.66 | 18428.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 835.71 | 667.64 | 168.07 | 1286.65 | 372.79 | 0.00 | 0.00 | 0.00 |
February | 521.47 | 349.59 | 171.87 | 735.59 | 344.34 | 0.00 | 0.00 | 0.00 |
March | 431.69 | 218.75 | 212.94 | 662.75 | 312.36 | 0.00 | 0.00 | 0.00 |
April | 378.88 | 156.07 | 222.81 | 724.38 | 179.52 | 0.00 | 0.00 | 0.00 |
May | 253.16 | 44.04 | 209.12 | 537.01 | 121.04 | 0.00 | 0.00 | 0.00 |
June | 214.28 | 16.35 | 197.94 | 596.06 | 45.88 | 0.00 | 0.00 | 0.00 |
July | 217.14 | 20.65 | 196.50 | 588.53 | 29.79 | 0.00 | 0.00 | 0.00 |
August | 268.51 | 75.62 | 192.88 | 678.70 | 39.75 | 0.00 | 0.00 | 0.00 |
September | 381.40 | 161.20 | 220.20 | 813.60 | 61.93 | 0.00 | 0.00 | 0.00 |
October | 612.22 | 423.82 | 188.40 | 1038.82 | 223.07 | 0.00 | 0.00 | 0.00 |
November | 719.63 | 552.71 | 166.92 | 1099.17 | 331.79 | 0.00 | 0.00 | 0.00 |
December | 778.28 | 616.61 | 161.67 | 1150.88 | 443.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 467.74 | 275.23 | 192.51 | 826.95 | 208.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 214.28 | 16.35 | 161.67 | 537.01 | 29.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 835.71 | 667.64 | 222.81 | 1286.65 | 443.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2353.32 | 1880.03 | 473.29 | 3576.23 | 1148.56 | 0.00 | 0.00 | 0.00 |
February | 1468.41 | 984.43 | 483.99 | 2022.75 | 1092.53 | 0.00 | 0.00 | 0.00 |
March | 1215.60 | 615.98 | 599.62 | 1813.93 | 985.64 | 0.00 | 0.00 | 0.00 |
April | 1066.89 | 439.48 | 627.41 | 2014.82 | 542.66 | 0.00 | 0.00 | 0.00 |
May | 712.87 | 124.01 | 588.87 | 1497.02 | 361.48 | 0.00 | 0.00 | 0.00 |
June | 603.41 | 46.04 | 557.38 | 1681.30 | 130.27 | 0.00 | 0.00 | 0.00 |
July | 611.46 | 58.14 | 553.32 | 1654.43 | 89.18 | 0.00 | 0.00 | 0.00 |
August | 756.09 | 212.94 | 543.15 | 1904.22 | 120.91 | 0.00 | 0.00 | 0.00 |
September | 1074.00 | 453.93 | 620.07 | 2276.49 | 187.00 | 0.00 | 0.00 | 0.00 |
October | 1723.96 | 1193.45 | 530.51 | 2890.99 | 682.98 | 0.00 | 0.00 | 0.00 |
November | 2026.44 | 1556.40 | 470.05 | 3049.44 | 1030.29 | 0.00 | 0.00 | 0.00 |
December | 2191.58 | 1736.32 | 455.26 | 3191.08 | 1362.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1317.12 | 775.03 | 542.09 | 2300.45 | 642.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 603.41 | 46.04 | 455.26 | 1497.02 | 89.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2353.32 | 1880.03 | 627.41 | 3576.23 | 1362.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3057.09 | 2442.27 | 614.83 | 4748.49 | 1497.51 | 0.00 | 0.00 | 0.00 |
February | 1907.55 | 1278.83 | 628.73 | 2690.52 | 1463.26 | 0.00 | 0.00 | 0.00 |
March | 1579.13 | 800.19 | 778.94 | 2412.22 | 1317.42 | 0.00 | 0.00 | 0.00 |
April | 1385.95 | 570.91 | 815.04 | 2696.58 | 710.85 | 0.00 | 0.00 | 0.00 |
May | 926.06 | 161.09 | 764.97 | 2006.00 | 476.44 | 0.00 | 0.00 | 0.00 |
June | 783.87 | 59.80 | 724.06 | 2259.32 | 169.47 | 0.00 | 0.00 | 0.00 |
July | 794.32 | 75.52 | 718.79 | 2223.33 | 114.58 | 0.00 | 0.00 | 0.00 |
August | 982.21 | 276.63 | 705.58 | 2552.23 | 153.72 | 0.00 | 0.00 | 0.00 |
September | 1395.19 | 589.68 | 805.51 | 3040.86 | 236.86 | 0.00 | 0.00 | 0.00 |
October | 2239.52 | 1550.35 | 689.17 | 3844.70 | 891.39 | 0.00 | 0.00 | 0.00 |
November | 2632.46 | 2021.85 | 610.62 | 4046.82 | 1352.81 | 0.00 | 0.00 | 0.00 |
December | 2846.99 | 2255.58 | 591.41 | 4236.39 | 1797.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1711.02 | 1006.81 | 704.21 | 3066.76 | 845.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 783.87 | 59.80 | 591.41 | 2006.00 | 114.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3057.09 | 2442.27 | 815.04 | 4748.49 | 1797.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.24 | 132.00 | 33.23 | 259.36 | 69.03 | 0.00 | 0.00 | 0.00 |
February | 103.10 | 69.12 | 33.98 | 147.49 | 66.63 | 0.00 | 0.00 | 0.00 |
March | 85.35 | 43.25 | 42.10 | 132.36 | 60.33 | 0.00 | 0.00 | 0.00 |
April | 74.91 | 30.86 | 44.05 | 149.94 | 28.26 | 0.00 | 0.00 | 0.00 |
May | 50.05 | 8.71 | 41.35 | 115.89 | 16.91 | 0.00 | 0.00 | 0.00 |
June | 42.37 | 3.23 | 39.14 | 135.33 | 4.39 | 0.00 | 0.00 | 0.00 |
July | 42.93 | 4.08 | 38.85 | 135.31 | 2.73 | 0.00 | 0.00 | 0.00 |
August | 53.09 | 14.95 | 38.14 | 150.63 | 3.08 | 0.00 | 0.00 | 0.00 |
September | 75.41 | 31.87 | 43.54 | 174.55 | 5.38 | 0.00 | 0.00 | 0.00 |
October | 121.05 | 83.80 | 37.25 | 212.29 | 37.09 | 0.00 | 0.00 | 0.00 |
November | 142.28 | 109.28 | 33.00 | 221.39 | 61.02 | 0.00 | 0.00 | 0.00 |
December | 153.88 | 121.91 | 31.97 | 232.41 | 85.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.48 | 54.42 | 38.06 | 172.47 | 36.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.37 | 3.23 | 31.97 | 115.89 | 2.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 165.24 | 132.00 | 44.05 | 259.36 | 85.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.00 | 79.12 | 47.88 | 187.34 | 141.79 | 0.00 | 0.00 | 0.00 |
February | 102.87 | 49.92 | 52.94 | 124.91 | 134.27 | 0.00 | 0.00 | 0.00 |
March | 136.12 | 65.10 | 71.02 | 194.24 | 115.06 | 0.00 | 0.00 | 0.00 |
April | 208.46 | 118.98 | 89.48 | 371.15 | 52.46 | 0.00 | 0.00 | 0.00 |
May | 209.22 | 117.24 | 91.97 | 402.35 | 31.26 | 0.00 | 0.00 | 0.00 |
June | 221.79 | 130.41 | 91.37 | 491.99 | 7.94 | 0.00 | 0.00 | 0.00 |
July | 161.33 | 75.18 | 86.15 | 385.81 | 4.98 | 0.00 | 0.00 | 0.00 |
August | 154.44 | 77.66 | 76.78 | 360.89 | 5.63 | 0.00 | 0.00 | 0.00 |
September | 134.39 | 56.51 | 77.89 | 298.96 | 10.14 | 0.00 | 0.00 | 0.00 |
October | 138.07 | 79.18 | 58.89 | 237.55 | 73.99 | 0.00 | 0.00 | 0.00 |
November | 126.39 | 76.26 | 50.13 | 184.26 | 124.56 | 0.00 | 0.00 | 0.00 |
December | 101.41 | 57.49 | 43.91 | 134.22 | 175.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.96 | 82.04 | 69.93 | 281.81 | 72.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.41 | 49.92 | 43.91 | 124.91 | 4.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.79 | 130.41 | 91.97 | 491.99 | 175.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.04 | 0.00 | 20.04 | 19.73 | 74.94 | 0.00 | 0.00 | 0.00 |
February | 22.83 | 0.00 | 22.83 | 14.59 | 71.45 | 0.00 | 0.00 | 0.00 |
March | 30.35 | 0.00 | 30.35 | 33.70 | 63.44 | 0.00 | 0.00 | 0.00 |
April | 37.17 | 0.55 | 36.63 | 69.78 | 27.81 | 0.00 | 0.00 | 0.00 |
May | 43.60 | 3.70 | 39.90 | 96.38 | 15.18 | 0.00 | 0.00 | 0.00 |
June | 50.36 | 9.20 | 41.15 | 148.27 | 3.90 | 0.00 | 0.00 | 0.00 |
July | 43.08 | 4.63 | 38.45 | 133.22 | 2.47 | 0.00 | 0.00 | 0.00 |
August | 34.66 | 0.85 | 33.81 | 109.14 | 3.15 | 0.00 | 0.00 | 0.00 |
September | 32.69 | 0.02 | 32.67 | 91.08 | 5.76 | 0.00 | 0.00 | 0.00 |
October | 25.27 | 0.00 | 25.27 | 44.51 | 40.55 | 0.00 | 0.00 | 0.00 |
November | 21.06 | 0.00 | 21.06 | 20.19 | 66.63 | 0.00 | 0.00 | 0.00 |
December | 18.72 | 0.00 | 18.72 | 12.85 | 92.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.68 | 1.58 | 30.10 | 66.37 | 38.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.72 | 0.00 | 18.72 | 12.85 | 2.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.36 | 9.20 | 41.15 | 148.27 | 92.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.00 | 79.12 | 47.88 | 193.63 | 138.75 | 0.00 | 0.00 | 0.00 |
February | 102.87 | 49.92 | 52.94 | 129.40 | 130.85 | 0.00 | 0.00 | 0.00 |
March | 136.12 | 65.10 | 71.02 | 196.65 | 115.30 | 0.00 | 0.00 | 0.00 |
April | 208.46 | 118.98 | 89.48 | 371.59 | 53.60 | 0.00 | 0.00 | 0.00 |
May | 209.22 | 117.24 | 91.97 | 400.92 | 31.73 | 0.00 | 0.00 | 0.00 |
June | 221.79 | 130.41 | 91.37 | 489.98 | 8.28 | 0.00 | 0.00 | 0.00 |
July | 161.33 | 75.18 | 86.15 | 385.28 | 5.13 | 0.00 | 0.00 | 0.00 |
August | 154.44 | 77.66 | 76.78 | 361.02 | 6.18 | 0.00 | 0.00 | 0.00 |
September | 134.39 | 56.51 | 77.89 | 299.62 | 10.73 | 0.00 | 0.00 | 0.00 |
October | 138.07 | 79.18 | 58.89 | 240.71 | 74.47 | 0.00 | 0.00 | 0.00 |
November | 126.39 | 76.26 | 50.13 | 189.07 | 122.73 | 0.00 | 0.00 | 0.00 |
December | 101.41 | 57.49 | 43.91 | 141.09 | 170.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.96 | 82.04 | 69.93 | 283.92 | 72.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.41 | 49.92 | 43.91 | 129.40 | 5.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.79 | 130.41 | 91.97 | 489.98 | 170.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.16 | 105.58 | 26.58 | 192.44 | 80.82 | 0.00 | 0.00 | 0.00 |
February | 82.47 | 55.29 | 27.18 | 105.38 | 80.93 | 0.00 | 0.00 | 0.00 |
March | 68.27 | 34.59 | 33.67 | 91.69 | 72.61 | 0.00 | 0.00 | 0.00 |
April | 59.92 | 24.68 | 35.24 | 105.18 | 41.53 | 0.00 | 0.00 | 0.00 |
May | 40.04 | 6.96 | 33.07 | 76.11 | 29.10 | 0.00 | 0.00 | 0.00 |
June | 33.89 | 2.59 | 31.30 | 86.29 | 12.23 | 0.00 | 0.00 | 0.00 |
July | 34.34 | 3.26 | 31.07 | 83.43 | 9.60 | 0.00 | 0.00 | 0.00 |
August | 42.46 | 11.96 | 30.50 | 98.56 | 12.92 | 0.00 | 0.00 | 0.00 |
September | 60.32 | 25.49 | 34.82 | 119.50 | 17.86 | 0.00 | 0.00 | 0.00 |
October | 96.82 | 67.02 | 29.79 | 153.89 | 50.60 | 0.00 | 0.00 | 0.00 |
November | 113.80 | 87.41 | 26.40 | 162.70 | 74.19 | 0.00 | 0.00 | 0.00 |
December | 123.08 | 97.51 | 25.57 | 171.31 | 95.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.97 | 43.53 | 30.44 | 120.69 | 47.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.89 | 2.59 | 25.57 | 76.11 | 9.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 132.16 | 105.58 | 35.24 | 192.44 | 95.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.03 | 0.00 | 16.03 | 16.79 | 59.40 | 0.00 | 0.00 | 0.00 |
February | 18.27 | 0.00 | 18.27 | 11.78 | 58.59 | 0.00 | 0.00 | 0.00 |
March | 24.29 | 0.00 | 24.28 | 28.08 | 50.50 | 0.00 | 0.00 | 0.00 |
April | 29.74 | 0.44 | 29.30 | 60.44 | 20.30 | 0.00 | 0.00 | 0.00 |
May | 34.89 | 2.96 | 31.92 | 82.56 | 10.67 | 0.00 | 0.00 | 0.00 |
June | 40.29 | 7.36 | 32.93 | 126.14 | 2.29 | 0.00 | 0.00 | 0.00 |
July | 34.47 | 3.70 | 30.76 | 113.19 | 1.55 | 0.00 | 0.00 | 0.00 |
August | 27.73 | 0.68 | 27.05 | 93.65 | 1.92 | 0.00 | 0.00 | 0.00 |
September | 26.15 | 0.02 | 26.14 | 78.05 | 3.60 | 0.00 | 0.00 | 0.00 |
October | 20.22 | 0.00 | 20.22 | 38.49 | 31.00 | 0.00 | 0.00 | 0.00 |
November | 16.85 | 0.00 | 16.85 | 17.28 | 52.55 | 0.00 | 0.00 | 0.00 |
December | 14.98 | 0.00 | 14.98 | 10.38 | 74.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.35 | 1.27 | 24.08 | 56.62 | 30.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.98 | 0.00 | 14.98 | 10.38 | 1.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 40.29 | 7.36 | 32.93 | 126.14 | 74.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.94 | 75.91 | 45.03 | 162.94 | 128.66 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 69.17 | 51.05 | 144.34 | 125.73 | 0.00 | 0.00 | 0.00 |
March | 149.29 | 76.81 | 72.48 | 206.49 | 106.77 | 0.00 | 0.00 | 0.00 |
April | 212.74 | 126.76 | 85.99 | 374.71 | 47.06 | 0.00 | 0.00 | 0.00 |
May | 220.85 | 131.04 | 89.80 | 420.28 | 27.45 | 0.00 | 0.00 | 0.00 |
June | 229.78 | 142.76 | 87.03 | 509.16 | 6.96 | 0.00 | 0.00 | 0.00 |
July | 194.36 | 109.67 | 84.69 | 444.20 | 4.46 | 0.00 | 0.00 | 0.00 |
August | 184.63 | 105.48 | 79.14 | 412.42 | 5.40 | 0.00 | 0.00 | 0.00 |
September | 151.29 | 72.97 | 78.32 | 326.89 | 9.50 | 0.00 | 0.00 | 0.00 |
October | 151.83 | 92.35 | 59.47 | 254.91 | 68.28 | 0.00 | 0.00 | 0.00 |
November | 116.83 | 70.11 | 46.72 | 156.69 | 114.47 | 0.00 | 0.00 | 0.00 |
December | 106.72 | 64.54 | 42.18 | 127.22 | 161.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.49 | 94.92 | 68.57 | 295.75 | 66.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 106.72 | 64.54 | 42.18 | 127.22 | 4.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.78 | 142.76 | 89.80 | 509.16 | 161.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.24 | 132.00 | 33.23 | 258.44 | 68.43 | 0.00 | 0.00 | 0.00 |
February | 103.10 | 69.12 | 33.98 | 145.92 | 66.65 | 0.00 | 0.00 | 0.00 |
March | 85.35 | 43.25 | 42.10 | 130.71 | 60.14 | 0.00 | 0.00 | 0.00 |
April | 74.91 | 30.86 | 44.05 | 149.06 | 28.09 | 0.00 | 0.00 | 0.00 |
May | 50.05 | 8.71 | 41.35 | 114.96 | 16.70 | 0.00 | 0.00 | 0.00 |
June | 42.37 | 3.23 | 39.14 | 134.63 | 4.18 | 0.00 | 0.00 | 0.00 |
July | 42.93 | 4.08 | 38.85 | 134.13 | 2.66 | 0.00 | 0.00 | 0.00 |
August | 53.09 | 14.95 | 38.14 | 149.66 | 3.06 | 0.00 | 0.00 | 0.00 |
September | 75.41 | 31.87 | 43.54 | 173.89 | 5.34 | 0.00 | 0.00 | 0.00 |
October | 121.05 | 83.80 | 37.25 | 211.14 | 36.83 | 0.00 | 0.00 | 0.00 |
November | 142.28 | 109.28 | 33.00 | 220.70 | 60.34 | 0.00 | 0.00 | 0.00 |
December | 153.88 | 121.91 | 31.97 | 231.32 | 84.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.48 | 54.42 | 38.06 | 171.44 | 36.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.37 | 3.23 | 31.97 | 114.96 | 2.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 165.24 | 132.00 | 44.05 | 258.44 | 84.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.04 | 0.00 | 20.04 | 18.76 | 73.85 | 0.00 | 0.00 | 0.00 |
February | 22.83 | 0.00 | 22.83 | 13.53 | 71.77 | 0.00 | 0.00 | 0.00 |
March | 30.35 | 0.00 | 30.35 | 32.12 | 63.14 | 0.00 | 0.00 | 0.00 |
April | 37.17 | 0.55 | 36.63 | 68.07 | 27.60 | 0.00 | 0.00 | 0.00 |
May | 43.60 | 3.70 | 39.90 | 94.11 | 14.94 | 0.00 | 0.00 | 0.00 |
June | 50.36 | 9.20 | 41.15 | 147.17 | 3.75 | 0.00 | 0.00 | 0.00 |
July | 43.08 | 4.63 | 38.45 | 131.85 | 2.41 | 0.00 | 0.00 | 0.00 |
August | 34.66 | 0.85 | 33.81 | 107.83 | 3.14 | 0.00 | 0.00 | 0.00 |
September | 32.69 | 0.02 | 32.67 | 89.98 | 5.77 | 0.00 | 0.00 | 0.00 |
October | 25.27 | 0.00 | 25.27 | 43.04 | 40.45 | 0.00 | 0.00 | 0.00 |
November | 21.06 | 0.00 | 21.06 | 19.40 | 65.46 | 0.00 | 0.00 | 0.00 |
December | 18.72 | 0.00 | 18.72 | 12.08 | 91.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.68 | 1.58 | 30.10 | 65.07 | 38.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.72 | 0.00 | 18.72 | 12.08 | 2.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.36 | 9.20 | 41.15 | 147.17 | 91.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.94 | 75.91 | 45.03 | 169.60 | 124.84 | 0.00 | 0.00 | 0.00 |
February | 120.23 | 69.17 | 51.05 | 149.15 | 122.22 | 0.00 | 0.00 | 0.00 |
March | 149.29 | 76.81 | 72.48 | 209.04 | 106.66 | 0.00 | 0.00 | 0.00 |
April | 212.74 | 126.76 | 85.99 | 373.15 | 47.85 | 0.00 | 0.00 | 0.00 |
May | 220.85 | 131.04 | 89.80 | 415.62 | 27.62 | 0.00 | 0.00 | 0.00 |
June | 229.78 | 142.76 | 87.03 | 505.78 | 7.05 | 0.00 | 0.00 | 0.00 |
July | 194.36 | 109.67 | 84.69 | 443.12 | 4.50 | 0.00 | 0.00 | 0.00 |
August | 184.63 | 105.48 | 79.14 | 411.73 | 5.84 | 0.00 | 0.00 | 0.00 |
September | 151.29 | 72.97 | 78.32 | 326.27 | 9.93 | 0.00 | 0.00 | 0.00 |
October | 151.83 | 92.35 | 59.47 | 257.04 | 68.60 | 0.00 | 0.00 | 0.00 |
November | 116.83 | 70.11 | 46.72 | 161.41 | 111.63 | 0.00 | 0.00 | 0.00 |
December | 106.72 | 64.54 | 42.18 | 134.16 | 154.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.49 | 94.92 | 68.57 | 297.05 | 65.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 106.72 | 64.54 | 42.18 | 134.16 | 4.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.78 | 142.76 | 89.80 | 505.78 | 154.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.38 | 0.00 | 25.38 | 23.46 | 102.56 | 0.00 | 0.00 | 0.00 |
February | 28.92 | 0.00 | 28.92 | 17.87 | 96.92 | 0.00 | 0.00 | 0.00 |
March | 38.44 | 0.00 | 38.44 | 43.57 | 84.16 | 0.00 | 0.00 | 0.00 |
April | 47.08 | 0.69 | 46.38 | 88.76 | 41.18 | 0.00 | 0.00 | 0.00 |
May | 55.22 | 4.69 | 50.53 | 119.82 | 25.44 | 0.00 | 0.00 | 0.00 |
June | 63.77 | 11.65 | 52.12 | 181.89 | 8.20 | 0.00 | 0.00 | 0.00 |
July | 54.55 | 5.86 | 48.69 | 158.74 | 5.52 | 0.00 | 0.00 | 0.00 |
August | 43.90 | 1.08 | 42.82 | 129.83 | 7.49 | 0.00 | 0.00 | 0.00 |
September | 41.39 | 0.03 | 41.37 | 108.18 | 12.93 | 0.00 | 0.00 | 0.00 |
October | 32.01 | 0.00 | 32.01 | 53.35 | 59.53 | 0.00 | 0.00 | 0.00 |
November | 26.67 | 0.00 | 26.67 | 24.45 | 92.03 | 0.00 | 0.00 | 0.00 |
December | 23.71 | 0.00 | 23.71 | 14.56 | 125.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.13 | 2.00 | 38.12 | 80.66 | 54.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.71 | 0.00 | 23.71 | 14.56 | 5.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.77 | 11.65 | 52.12 | 181.89 | 125.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.36 | 0.00 | 9.36 | 8.65 | 37.81 | 0.00 | 0.00 | 0.00 |
February | 10.66 | 0.00 | 10.66 | 6.59 | 35.73 | 0.00 | 0.00 | 0.00 |
March | 14.17 | 0.00 | 14.17 | 16.06 | 31.02 | 0.00 | 0.00 | 0.00 |
April | 17.35 | 0.26 | 17.10 | 32.72 | 15.18 | 0.00 | 0.00 | 0.00 |
May | 20.36 | 1.73 | 18.63 | 44.17 | 9.38 | 0.00 | 0.00 | 0.00 |
June | 23.51 | 4.30 | 19.21 | 67.05 | 3.02 | 0.00 | 0.00 | 0.00 |
July | 20.11 | 2.16 | 17.95 | 58.52 | 2.04 | 0.00 | 0.00 | 0.00 |
August | 16.18 | 0.40 | 15.78 | 47.86 | 2.76 | 0.00 | 0.00 | 0.00 |
September | 15.26 | 0.01 | 15.25 | 39.88 | 4.77 | 0.00 | 0.00 | 0.00 |
October | 11.80 | 0.00 | 11.80 | 19.67 | 21.95 | 0.00 | 0.00 | 0.00 |
November | 9.83 | 0.00 | 9.83 | 9.01 | 33.93 | 0.00 | 0.00 | 0.00 |
December | 8.74 | 0.00 | 8.74 | 5.37 | 46.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14.79 | 0.74 | 14.05 | 29.74 | 20.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.74 | 0.00 | 8.74 | 5.37 | 2.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.51 | 4.30 | 19.21 | 67.05 | 46.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.10 | 61.59 | 15.51 | 122.04 | 34.00 | 0.00 | 0.00 | 0.00 |
February | 48.11 | 32.25 | 15.86 | 69.62 | 32.47 | 0.00 | 0.00 | 0.00 |
March | 39.82 | 20.18 | 19.64 | 62.68 | 29.66 | 0.00 | 0.00 | 0.00 |
April | 34.95 | 14.40 | 20.56 | 70.15 | 15.72 | 0.00 | 0.00 | 0.00 |
May | 23.36 | 4.06 | 19.29 | 53.04 | 10.51 | 0.00 | 0.00 | 0.00 |
June | 19.77 | 1.51 | 18.26 | 60.55 | 3.47 | 0.00 | 0.00 | 0.00 |
July | 20.03 | 1.90 | 18.13 | 59.34 | 2.25 | 0.00 | 0.00 | 0.00 |
August | 24.77 | 6.98 | 17.79 | 67.21 | 2.92 | 0.00 | 0.00 | 0.00 |
September | 35.19 | 14.87 | 20.31 | 78.80 | 4.73 | 0.00 | 0.00 | 0.00 |
October | 56.48 | 39.10 | 17.38 | 98.43 | 20.26 | 0.00 | 0.00 | 0.00 |
November | 66.39 | 50.99 | 15.40 | 104.00 | 30.57 | 0.00 | 0.00 | 0.00 |
December | 71.80 | 56.88 | 14.92 | 109.45 | 41.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.15 | 25.39 | 17.76 | 79.70 | 18.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.77 | 1.51 | 14.92 | 53.04 | 2.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.10 | 61.59 | 20.56 | 122.04 | 41.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 209.26 | 167.17 | 42.09 | 331.24 | 92.30 | 0.00 | 0.00 | 0.00 |
February | 130.57 | 87.54 | 43.04 | 188.97 | 88.13 | 0.00 | 0.00 | 0.00 |
March | 108.09 | 54.77 | 53.32 | 170.13 | 80.50 | 0.00 | 0.00 | 0.00 |
April | 94.87 | 39.08 | 55.79 | 190.39 | 42.67 | 0.00 | 0.00 | 0.00 |
May | 63.39 | 11.03 | 52.36 | 143.96 | 28.53 | 0.00 | 0.00 | 0.00 |
June | 53.66 | 4.09 | 49.56 | 164.33 | 9.42 | 0.00 | 0.00 | 0.00 |
July | 54.37 | 5.17 | 49.20 | 161.07 | 6.11 | 0.00 | 0.00 | 0.00 |
August | 67.23 | 18.94 | 48.30 | 182.41 | 7.92 | 0.00 | 0.00 | 0.00 |
September | 95.50 | 40.36 | 55.14 | 213.87 | 12.83 | 0.00 | 0.00 | 0.00 |
October | 153.30 | 106.12 | 47.17 | 267.16 | 54.98 | 0.00 | 0.00 | 0.00 |
November | 180.19 | 138.40 | 41.80 | 282.28 | 82.97 | 0.00 | 0.00 | 0.00 |
December | 194.88 | 154.40 | 40.48 | 297.08 | 111.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 117.12 | 68.92 | 48.20 | 216.33 | 51.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 53.66 | 4.09 | 40.48 | 143.96 | 6.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.26 | 167.17 | 55.79 | 331.24 | 111.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.24 | 132.00 | 33.23 | 258.02 | 68.25 | 0.00 | 0.00 | 0.00 |
February | 103.10 | 69.12 | 33.98 | 146.57 | 65.89 | 0.00 | 0.00 | 0.00 |
March | 85.35 | 43.25 | 42.10 | 131.29 | 59.86 | 0.00 | 0.00 | 0.00 |
April | 74.91 | 30.86 | 44.05 | 148.96 | 27.43 | 0.00 | 0.00 | 0.00 |
May | 50.05 | 8.71 | 41.35 | 115.79 | 16.09 | 0.00 | 0.00 | 0.00 |
June | 42.37 | 3.23 | 39.14 | 135.61 | 3.99 | 0.00 | 0.00 | 0.00 |
July | 42.93 | 4.08 | 38.85 | 135.44 | 2.55 | 0.00 | 0.00 | 0.00 |
August | 53.09 | 14.95 | 38.14 | 150.52 | 2.81 | 0.00 | 0.00 | 0.00 |
September | 75.41 | 31.87 | 43.54 | 174.07 | 4.90 | 0.00 | 0.00 | 0.00 |
October | 121.05 | 83.80 | 37.25 | 211.23 | 36.09 | 0.00 | 0.00 | 0.00 |
November | 142.28 | 109.28 | 33.00 | 220.17 | 60.21 | 0.00 | 0.00 | 0.00 |
December | 153.88 | 121.91 | 31.97 | 231.63 | 84.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.48 | 54.42 | 38.06 | 171.83 | 35.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.37 | 3.23 | 31.97 | 115.79 | 2.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 165.24 | 132.00 | 44.05 | 258.02 | 84.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.00 | 79.12 | 47.88 | 186.06 | 139.49 | 0.00 | 0.00 | 0.00 |
February | 102.87 | 49.92 | 52.94 | 123.58 | 132.28 | 0.00 | 0.00 | 0.00 |
March | 136.12 | 65.10 | 71.02 | 192.45 | 113.73 | 0.00 | 0.00 | 0.00 |
April | 208.46 | 118.98 | 89.48 | 368.50 | 50.90 | 0.00 | 0.00 | 0.00 |
May | 209.22 | 117.24 | 91.97 | 400.54 | 29.84 | 0.00 | 0.00 | 0.00 |
June | 221.79 | 130.41 | 91.37 | 490.33 | 7.31 | 0.00 | 0.00 | 0.00 |
July | 161.33 | 75.18 | 86.15 | 384.82 | 4.70 | 0.00 | 0.00 | 0.00 |
August | 154.44 | 77.66 | 76.78 | 359.94 | 5.23 | 0.00 | 0.00 | 0.00 |
September | 134.39 | 56.51 | 77.89 | 298.16 | 9.35 | 0.00 | 0.00 | 0.00 |
October | 138.07 | 79.18 | 58.89 | 236.43 | 71.79 | 0.00 | 0.00 | 0.00 |
November | 126.39 | 76.26 | 50.13 | 182.92 | 122.41 | 0.00 | 0.00 | 0.00 |
December | 101.41 | 57.49 | 43.91 | 133.39 | 173.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.96 | 82.04 | 69.93 | 280.44 | 71.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.41 | 49.92 | 43.91 | 123.58 | 4.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.79 | 130.41 | 91.97 | 490.33 | 173.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.04 | 0.00 | 20.04 | 20.22 | 73.40 | 0.00 | 0.00 | 0.00 |
February | 22.83 | 0.00 | 22.83 | 14.66 | 70.24 | 0.00 | 0.00 | 0.00 |
March | 30.35 | 0.00 | 30.35 | 33.58 | 62.88 | 0.00 | 0.00 | 0.00 |
April | 37.17 | 0.55 | 36.63 | 69.66 | 27.10 | 0.00 | 0.00 | 0.00 |
May | 43.60 | 3.70 | 39.90 | 96.63 | 14.51 | 0.00 | 0.00 | 0.00 |
June | 50.36 | 9.20 | 41.15 | 148.39 | 3.62 | 0.00 | 0.00 | 0.00 |
July | 43.08 | 4.63 | 38.45 | 133.33 | 2.33 | 0.00 | 0.00 | 0.00 |
August | 34.66 | 0.85 | 33.81 | 109.30 | 2.94 | 0.00 | 0.00 | 0.00 |
September | 32.69 | 0.02 | 32.67 | 91.36 | 5.28 | 0.00 | 0.00 | 0.00 |
October | 25.27 | 0.00 | 25.27 | 44.95 | 39.18 | 0.00 | 0.00 | 0.00 |
November | 21.06 | 0.00 | 21.06 | 20.59 | 65.20 | 0.00 | 0.00 | 0.00 |
December | 18.72 | 0.00 | 18.72 | 13.32 | 90.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.68 | 1.58 | 30.10 | 66.58 | 37.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.72 | 0.00 | 18.72 | 13.32 | 2.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.36 | 9.20 | 41.15 | 148.39 | 90.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.00 | 79.12 | 47.88 | 193.19 | 135.88 | 0.00 | 0.00 | 0.00 |
February | 102.87 | 49.92 | 52.94 | 128.59 | 128.55 | 0.00 | 0.00 | 0.00 |
March | 136.12 | 65.10 | 71.02 | 195.03 | 114.14 | 0.00 | 0.00 | 0.00 |
April | 208.46 | 118.98 | 89.48 | 369.04 | 52.11 | 0.00 | 0.00 | 0.00 |
May | 209.22 | 117.24 | 91.97 | 399.29 | 30.14 | 0.00 | 0.00 | 0.00 |
June | 221.79 | 130.41 | 91.37 | 488.35 | 7.57 | 0.00 | 0.00 | 0.00 |
July | 161.33 | 75.18 | 86.15 | 384.32 | 4.81 | 0.00 | 0.00 | 0.00 |
August | 154.44 | 77.66 | 76.78 | 360.15 | 5.72 | 0.00 | 0.00 | 0.00 |
September | 134.39 | 56.51 | 77.89 | 299.00 | 9.81 | 0.00 | 0.00 | 0.00 |
October | 138.07 | 79.18 | 58.89 | 240.12 | 71.94 | 0.00 | 0.00 | 0.00 |
November | 126.39 | 76.26 | 50.13 | 188.50 | 120.06 | 0.00 | 0.00 | 0.00 |
December | 101.41 | 57.49 | 43.91 | 141.12 | 167.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.96 | 82.04 | 69.93 | 282.90 | 70.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.41 | 49.92 | 43.91 | 128.59 | 4.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.79 | 130.41 | 91.97 | 488.35 | 167.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 242.33 | 193.60 | 48.74 | 373.26 | 103.86 | 0.00 | 0.00 | 0.00 |
February | 151.21 | 101.37 | 49.84 | 210.36 | 101.03 | 0.00 | 0.00 | 0.00 |
March | 125.18 | 63.43 | 61.75 | 190.01 | 89.15 | 0.00 | 0.00 | 0.00 |
April | 109.86 | 45.26 | 64.61 | 221.58 | 38.79 | 0.00 | 0.00 | 0.00 |
May | 73.41 | 12.77 | 60.64 | 175.47 | 22.00 | 0.00 | 0.00 | 0.00 |
June | 62.14 | 4.74 | 57.40 | 207.54 | 4.83 | 0.00 | 0.00 | 0.00 |
July | 62.97 | 5.99 | 56.98 | 205.12 | 3.29 | 0.00 | 0.00 | 0.00 |
August | 77.86 | 21.93 | 55.93 | 226.15 | 3.68 | 0.00 | 0.00 | 0.00 |
September | 110.60 | 46.74 | 63.85 | 258.03 | 6.74 | 0.00 | 0.00 | 0.00 |
October | 177.53 | 122.90 | 54.63 | 308.13 | 53.74 | 0.00 | 0.00 | 0.00 |
November | 208.67 | 160.27 | 48.40 | 318.84 | 91.22 | 0.00 | 0.00 | 0.00 |
December | 225.68 | 178.80 | 46.88 | 333.09 | 129.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 135.63 | 79.81 | 55.82 | 252.65 | 53.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.14 | 4.74 | 46.88 | 175.47 | 3.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 242.33 | 193.60 | 64.61 | 373.26 | 129.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 140.27 | 0.00 | 140.27 | 102.53 | 646.66 | 0.00 | 0.00 | 0.00 |
February | 159.84 | 0.00 | 159.84 | 66.84 | 653.59 | 0.00 | 0.00 | 0.00 |
March | 212.46 | 0.01 | 212.45 | 191.03 | 555.18 | 0.00 | 0.00 | 0.00 |
April | 260.20 | 3.83 | 256.37 | 450.88 | 258.39 | 0.00 | 0.00 | 0.00 |
May | 305.21 | 25.92 | 279.29 | 628.03 | 155.82 | 0.00 | 0.00 | 0.00 |
June | 352.47 | 64.40 | 288.07 | 978.82 | 51.99 | 0.00 | 0.00 | 0.00 |
July | 301.52 | 32.40 | 269.12 | 847.53 | 37.16 | 0.00 | 0.00 | 0.00 |
August | 242.62 | 5.96 | 236.66 | 691.29 | 51.60 | 0.00 | 0.00 | 0.00 |
September | 228.79 | 0.14 | 228.65 | 575.02 | 84.78 | 0.00 | 0.00 | 0.00 |
October | 176.90 | 0.00 | 176.90 | 271.82 | 365.05 | 0.00 | 0.00 | 0.00 |
November | 147.39 | 0.00 | 147.39 | 107.12 | 584.70 | 0.00 | 0.00 | 0.00 |
December | 131.03 | 0.00 | 131.03 | 56.33 | 793.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 221.78 | 11.08 | 210.70 | 415.54 | 351.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.03 | 0.00 | 131.03 | 56.33 | 37.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 352.47 | 64.40 | 288.07 | 978.82 | 793.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 140.27 | 0.00 | 140.27 | 93.55 | 665.50 | 0.00 | 0.00 | 0.00 |
February | 159.84 | 0.00 | 159.84 | 59.15 | 677.47 | 0.00 | 0.00 | 0.00 |
March | 212.46 | 0.01 | 212.45 | 179.36 | 572.09 | 0.00 | 0.00 | 0.00 |
April | 260.20 | 3.83 | 256.37 | 441.30 | 266.18 | 0.00 | 0.00 | 0.00 |
May | 305.21 | 25.92 | 279.29 | 618.39 | 160.84 | 0.00 | 0.00 | 0.00 |
June | 352.47 | 64.40 | 288.07 | 968.38 | 54.34 | 0.00 | 0.00 | 0.00 |
July | 301.52 | 32.40 | 269.12 | 836.95 | 39.37 | 0.00 | 0.00 | 0.00 |
August | 242.62 | 5.96 | 236.66 | 681.51 | 54.89 | 0.00 | 0.00 | 0.00 |
September | 228.79 | 0.14 | 228.65 | 565.98 | 89.41 | 0.00 | 0.00 | 0.00 |
October | 176.90 | 0.00 | 176.90 | 262.99 | 376.37 | 0.00 | 0.00 | 0.00 |
November | 147.39 | 0.00 | 147.39 | 98.52 | 602.90 | 0.00 | 0.00 | 0.00 |
December | 131.03 | 0.00 | 131.03 | 49.39 | 818.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 221.78 | 11.08 | 210.70 | 406.21 | 363.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.03 | 0.00 | 131.03 | 49.39 | 39.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 352.47 | 64.40 | 288.07 | 968.38 | 818.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.04 | 0.00 | 20.04 | 22.33 | 85.60 | 0.00 | 0.00 | 0.00 |
February | 22.83 | 0.00 | 22.83 | 14.88 | 85.95 | 0.00 | 0.00 | 0.00 |
March | 30.35 | 0.00 | 30.35 | 36.96 | 75.37 | 0.00 | 0.00 | 0.00 |
April | 37.17 | 0.55 | 36.63 | 80.34 | 36.83 | 0.00 | 0.00 | 0.00 |
May | 43.60 | 3.70 | 39.90 | 108.83 | 24.55 | 0.00 | 0.00 | 0.00 |
June | 50.36 | 9.20 | 41.15 | 159.64 | 9.82 | 0.00 | 0.00 | 0.00 |
July | 43.08 | 4.63 | 38.45 | 140.45 | 7.25 | 0.00 | 0.00 | 0.00 |
August | 34.66 | 0.85 | 33.81 | 118.20 | 9.25 | 0.00 | 0.00 | 0.00 |
September | 32.69 | 0.02 | 32.67 | 100.99 | 13.72 | 0.00 | 0.00 | 0.00 |
October | 25.27 | 0.00 | 25.27 | 51.19 | 49.67 | 0.00 | 0.00 | 0.00 |
November | 21.06 | 0.00 | 21.06 | 23.07 | 77.00 | 0.00 | 0.00 | 0.00 |
December | 18.72 | 0.00 | 18.72 | 13.89 | 103.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.68 | 1.58 | 30.10 | 72.84 | 48.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.72 | 0.00 | 18.72 | 13.89 | 7.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.36 | 9.20 | 41.15 | 159.64 | 103.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 241.87 | 151.81 | 90.06 | 353.16 | 293.50 | 0.00 | 0.00 | 0.00 |
February | 240.43 | 138.34 | 102.10 | 304.55 | 297.78 | 0.00 | 0.00 | 0.00 |
March | 298.56 | 153.60 | 144.96 | 436.63 | 259.94 | 0.00 | 0.00 | 0.00 |
April | 425.45 | 253.49 | 171.96 | 794.48 | 132.35 | 0.00 | 0.00 | 0.00 |
May | 441.66 | 262.07 | 179.60 | 885.88 | 91.28 | 0.00 | 0.00 | 0.00 |
June | 459.53 | 285.49 | 174.04 | 1056.38 | 36.76 | 0.00 | 0.00 | 0.00 |
July | 388.70 | 219.32 | 169.38 | 916.92 | 27.03 | 0.00 | 0.00 | 0.00 |
August | 369.23 | 210.95 | 158.27 | 860.55 | 34.62 | 0.00 | 0.00 | 0.00 |
September | 302.56 | 145.93 | 156.63 | 692.99 | 50.64 | 0.00 | 0.00 | 0.00 |
October | 303.63 | 184.69 | 118.94 | 546.92 | 173.30 | 0.00 | 0.00 | 0.00 |
November | 233.65 | 140.21 | 93.44 | 337.94 | 266.87 | 0.00 | 0.00 | 0.00 |
December | 213.43 | 129.08 | 84.35 | 275.99 | 355.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 326.95 | 189.82 | 137.13 | 623.39 | 167.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 213.43 | 129.08 | 84.35 | 275.99 | 27.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 459.53 | 285.49 | 179.60 | 1056.38 | 355.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 165.24 | 132.00 | 33.23 | 267.36 | 78.29 | 0.00 | 0.00 | 0.00 |
February | 103.10 | 69.12 | 33.98 | 151.33 | 78.93 | 0.00 | 0.00 | 0.00 |
March | 85.35 | 43.25 | 42.10 | 137.68 | 72.57 | 0.00 | 0.00 | 0.00 |
April | 74.91 | 30.86 | 44.05 | 160.66 | 37.92 | 0.00 | 0.00 | 0.00 |
May | 50.05 | 8.71 | 41.35 | 127.10 | 26.32 | 0.00 | 0.00 | 0.00 |
June | 42.37 | 3.23 | 39.14 | 145.19 | 10.35 | 0.00 | 0.00 | 0.00 |
July | 42.93 | 4.08 | 38.85 | 142.27 | 7.53 | 0.00 | 0.00 | 0.00 |
August | 53.09 | 14.95 | 38.14 | 159.79 | 9.36 | 0.00 | 0.00 | 0.00 |
September | 75.41 | 31.87 | 43.54 | 184.69 | 13.67 | 0.00 | 0.00 | 0.00 |
October | 121.05 | 83.80 | 37.25 | 221.64 | 46.61 | 0.00 | 0.00 | 0.00 |
November | 142.28 | 109.28 | 33.00 | 228.76 | 70.72 | 0.00 | 0.00 | 0.00 |
December | 153.88 | 121.91 | 31.97 | 239.11 | 93.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 92.48 | 54.42 | 38.06 | 180.71 | 45.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 42.37 | 3.23 | 31.97 | 127.10 | 7.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 165.24 | 132.00 | 44.05 | 267.36 | 93.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.38 | 0.00 | 25.38 | 21.50 | 102.76 | 0.00 | 0.00 | 0.00 |
February | 28.92 | 0.00 | 28.92 | 15.67 | 98.84 | 0.00 | 0.00 | 0.00 |
March | 38.44 | 0.00 | 38.44 | 40.61 | 85.56 | 0.00 | 0.00 | 0.00 |
April | 47.08 | 0.69 | 46.38 | 84.32 | 42.46 | 0.00 | 0.00 | 0.00 |
May | 55.22 | 4.69 | 50.53 | 115.65 | 26.38 | 0.00 | 0.00 | 0.00 |
June | 63.77 | 11.65 | 52.12 | 177.46 | 8.79 | 0.00 | 0.00 | 0.00 |
July | 54.55 | 5.86 | 48.69 | 153.63 | 6.14 | 0.00 | 0.00 | 0.00 |
August | 43.90 | 1.08 | 42.82 | 125.17 | 8.40 | 0.00 | 0.00 | 0.00 |
September | 41.39 | 0.03 | 41.37 | 104.25 | 14.05 | 0.00 | 0.00 | 0.00 |
October | 32.01 | 0.00 | 32.01 | 51.22 | 58.91 | 0.00 | 0.00 | 0.00 |
November | 26.67 | 0.00 | 26.67 | 22.56 | 91.93 | 0.00 | 0.00 | 0.00 |
December | 23.71 | 0.00 | 23.71 | 12.83 | 126.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.13 | 2.00 | 38.12 | 77.36 | 55.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.71 | 0.00 | 23.71 | 12.83 | 6.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.77 | 11.65 | 52.12 | 177.46 | 126.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.71 | 0.00 | 22.71 | 19.24 | 91.93 | 0.00 | 0.00 | 0.00 |
February | 25.87 | 0.00 | 25.87 | 14.02 | 88.44 | 0.00 | 0.00 | 0.00 |
March | 34.39 | 0.00 | 34.39 | 36.34 | 76.55 | 0.00 | 0.00 | 0.00 |
April | 42.12 | 0.62 | 41.50 | 75.45 | 37.99 | 0.00 | 0.00 | 0.00 |
May | 49.41 | 4.20 | 45.21 | 103.48 | 23.61 | 0.00 | 0.00 | 0.00 |
June | 57.06 | 10.43 | 46.63 | 158.78 | 7.86 | 0.00 | 0.00 | 0.00 |
July | 48.81 | 5.24 | 43.56 | 137.45 | 5.49 | 0.00 | 0.00 | 0.00 |
August | 39.27 | 0.96 | 38.31 | 111.99 | 7.52 | 0.00 | 0.00 | 0.00 |
September | 37.04 | 0.02 | 37.01 | 93.27 | 12.57 | 0.00 | 0.00 | 0.00 |
October | 28.64 | 0.00 | 28.64 | 45.83 | 52.71 | 0.00 | 0.00 | 0.00 |
November | 23.86 | 0.00 | 23.86 | 20.18 | 82.25 | 0.00 | 0.00 | 0.00 |
December | 21.21 | 0.00 | 21.21 | 11.48 | 112.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.90 | 1.79 | 34.11 | 69.21 | 49.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.21 | 0.00 | 21.21 | 11.48 | 5.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.06 | 10.43 | 46.63 | 158.78 | 112.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 616.87 | 492.81 | 124.06 | 964.36 | 273.49 | 0.00 | 0.00 | 0.00 |
February | 384.91 | 258.05 | 126.87 | 546.08 | 265.55 | 0.00 | 0.00 | 0.00 |
March | 318.65 | 161.47 | 157.18 | 489.01 | 242.28 | 0.00 | 0.00 | 0.00 |
April | 279.66 | 115.20 | 164.46 | 545.30 | 129.69 | 0.00 | 0.00 | 0.00 |
May | 186.87 | 32.51 | 154.36 | 411.51 | 86.79 | 0.00 | 0.00 | 0.00 |
June | 158.17 | 12.07 | 146.11 | 472.04 | 29.37 | 0.00 | 0.00 | 0.00 |
July | 160.28 | 15.24 | 145.04 | 459.71 | 19.76 | 0.00 | 0.00 | 0.00 |
August | 198.20 | 55.82 | 142.38 | 523.02 | 25.93 | 0.00 | 0.00 | 0.00 |
September | 281.53 | 118.99 | 162.54 | 616.30 | 40.93 | 0.00 | 0.00 | 0.00 |
October | 451.90 | 312.84 | 139.06 | 776.75 | 161.03 | 0.00 | 0.00 | 0.00 |
November | 531.19 | 407.98 | 123.21 | 821.29 | 245.23 | 0.00 | 0.00 | 0.00 |
December | 574.48 | 455.14 | 119.34 | 864.81 | 332.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 345.26 | 203.16 | 142.10 | 624.94 | 153.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 158.17 | 12.07 | 119.34 | 411.51 | 19.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 616.87 | 492.81 | 164.46 | 964.36 | 332.03 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223838E+10 | 0.178821E+10 | 0.450171E+09 | 0.344615E+10 | 0.998473E+09 |
February | 0.126153E+10 | 0.845731E+09 | 0.415798E+09 | 0.177955E+10 | 0.833035E+09 |
March | 0.115623E+10 | 0.585894E+09 | 0.570335E+09 | 0.177511E+10 | 0.836636E+09 |
April | 0.982044E+09 | 0.404532E+09 | 0.577512E+09 | 0.187759E+10 | 0.465311E+09 |
May | 0.678057E+09 | 0.117952E+09 | 0.560105E+09 | 0.143832E+10 | 0.324184E+09 |
June | 0.555427E+09 | 42376069.35 | 0.513050E+09 | 0.154499E+10 | 0.118922E+09 |
July | 0.581591E+09 | 55297824.35 | 0.526293E+09 | 0.157633E+10 | 79792522.46 |
August | 0.719166E+09 | 0.202544E+09 | 0.516622E+09 | 0.181783E+10 | 0.106469E+09 |
September | 0.988595E+09 | 0.417832E+09 | 0.570763E+09 | 0.210885E+10 | 0.160522E+09 |
October | 0.163976E+10 | 0.113516E+10 | 0.504604E+09 | 0.278237E+10 | 0.597458E+09 |
November | 0.186529E+10 | 0.143263E+10 | 0.432667E+09 | 0.284904E+10 | 0.860010E+09 |
December | 0.208454E+10 | 0.165152E+10 | 0.433026E+09 | 0.308252E+10 | 0.118777E+10 |
Annual Sum or Average | 0.147506E+11 | 0.867966E+10 | 0.607095E+10 | 0.260786E+11 | 0.656858E+10 |
Minimum of Months | 0.555427E+09 | 42376069.35 | 0.415798E+09 | 0.143832E+10 | 79792522.46 |
Maximum of Months | 0.223838E+10 | 0.178821E+10 | 0.577512E+09 | 0.344615E+10 | 0.118777E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.630312E+10 | 0.503547E+10 | 0.126765E+10 | 0.957856E+10 | 0.307630E+10 |
February | 0.355238E+10 | 0.238152E+10 | 0.117086E+10 | 0.489343E+10 | 0.264305E+10 |
March | 0.325586E+10 | 0.164984E+10 | 0.160603E+10 | 0.485843E+10 | 0.263994E+10 |
April | 0.276537E+10 | 0.113914E+10 | 0.162624E+10 | 0.522241E+10 | 0.140659E+10 |
May | 0.190936E+10 | 0.332145E+09 | 0.157722E+10 | 0.400961E+10 | 0.968175E+09 |
June | 0.156404E+10 | 0.119328E+09 | 0.144472E+10 | 0.435793E+10 | 0.337671E+09 |
July | 0.163772E+10 | 0.155715E+09 | 0.148201E+10 | 0.443123E+10 | 0.238849E+09 |
August | 0.202512E+10 | 0.570351E+09 | 0.145477E+10 | 0.510027E+10 | 0.323834E+09 |
September | 0.278382E+10 | 0.117659E+10 | 0.160723E+10 | 0.590065E+10 | 0.484691E+09 |
October | 0.461746E+10 | 0.319653E+10 | 0.142093E+10 | 0.774322E+10 | 0.182929E+10 |
November | 0.525254E+10 | 0.403418E+10 | 0.121836E+10 | 0.790414E+10 | 0.267051E+10 |
December | 0.586993E+10 | 0.465056E+10 | 0.121937E+10 | 0.854699E+10 | 0.365044E+10 |
Annual Sum or Average | 0.415367E+11 | 0.244414E+11 | 0.170954E+11 | 0.725469E+11 | 0.202693E+11 |
Minimum of Months | 0.156404E+10 | 0.119328E+09 | 0.117086E+10 | 0.400961E+10 | 0.238849E+09 |
Maximum of Months | 0.630312E+10 | 0.503547E+10 | 0.162624E+10 | 0.957856E+10 | 0.365044E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.818812E+10 | 0.654136E+10 | 0.164675E+10 | 0.127184E+11 | 0.401093E+10 |
February | 0.461475E+10 | 0.309374E+10 | 0.152101E+10 | 0.650890E+10 | 0.353992E+10 |
March | 0.422955E+10 | 0.214323E+10 | 0.208632E+10 | 0.646088E+10 | 0.352858E+10 |
April | 0.359238E+10 | 0.147980E+10 | 0.211257E+10 | 0.698953E+10 | 0.184253E+10 |
May | 0.248037E+10 | 0.431476E+09 | 0.204890E+10 | 0.537288E+10 | 0.127611E+10 |
June | 0.203178E+10 | 0.155014E+09 | 0.187677E+10 | 0.585616E+10 | 0.439275E+09 |
July | 0.212749E+10 | 0.202283E+09 | 0.192521E+10 | 0.595496E+10 | 0.306900E+09 |
August | 0.263075E+10 | 0.740919E+09 | 0.188983E+10 | 0.683589E+10 | 0.411725E+09 |
September | 0.361634E+10 | 0.152845E+10 | 0.208788E+10 | 0.788192E+10 | 0.613953E+09 |
October | 0.599834E+10 | 0.415247E+10 | 0.184587E+10 | 0.102976E+11 | 0.238749E+10 |
November | 0.682335E+10 | 0.524063E+10 | 0.158272E+10 | 0.104893E+11 | 0.350648E+10 |
December | 0.762538E+10 | 0.604134E+10 | 0.158404E+10 | 0.113468E+11 | 0.481384E+10 |
Annual Sum or Average | 0.539586E+11 | 0.317507E+11 | 0.222079E+11 | 0.967132E+11 | 0.266777E+11 |
Minimum of Months | 0.203178E+10 | 0.155014E+09 | 0.152101E+10 | 0.537288E+10 | 0.306900E+09 |
Maximum of Months | 0.818812E+10 | 0.654136E+10 | 0.211257E+10 | 0.127184E+11 | 0.481384E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442566E+09 | 0.353559E+09 | 89007348.67 | 0.694665E+09 | 0.184881E+09 |
February | 0.249427E+09 | 0.167216E+09 | 82211105.16 | 0.356818E+09 | 0.161198E+09 |
March | 0.228607E+09 | 0.115841E+09 | 0.112766E+09 | 0.354505E+09 | 0.161594E+09 |
April | 0.194169E+09 | 79982898.78 | 0.114186E+09 | 0.388644E+09 | 73247186.25 |
May | 0.134065E+09 | 23321164.89 | 0.110744E+09 | 0.310398E+09 | 45293818.10 |
June | 0.109819E+09 | 8378476.71 | 0.101441E+09 | 0.350777E+09 | 11386945.92 |
July | 0.114992E+09 | 10933329.61 | 0.104059E+09 | 0.362408E+09 | 7304744.41 |
August | 0.142193E+09 | 40046470.60 | 0.102146E+09 | 0.403453E+09 | 8237695.84 |
September | 0.195463E+09 | 82612529.72 | 0.112851E+09 | 0.452429E+09 | 13955623.17 |
October | 0.324210E+09 | 0.224440E+09 | 99769849.61 | 0.568600E+09 | 99354615.45 |
November | 0.368801E+09 | 0.283255E+09 | 85546508.11 | 0.573844E+09 | 0.158162E+09 |
December | 0.412151E+09 | 0.326533E+09 | 85617432.54 | 0.622491E+09 | 0.227984E+09 |
Annual Sum or Average | 0.291646E+10 | 0.171612E+10 | 0.120034E+10 | 0.543903E+10 | 0.115260E+10 |
Minimum of Months | 0.109819E+09 | 8378476.71 | 82211105.16 | 0.310398E+09 | 7304744.41 |
Maximum of Months | 0.442566E+09 | 0.353559E+09 | 0.114186E+09 | 0.694665E+09 | 0.227984E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340154E+09 | 0.211926E+09 | 0.128229E+09 | 0.501769E+09 | 0.379772E+09 |
February | 0.248858E+09 | 0.120775E+09 | 0.128083E+09 | 0.302176E+09 | 0.324832E+09 |
March | 0.364588E+09 | 0.174372E+09 | 0.190216E+09 | 0.520244E+09 | 0.308182E+09 |
April | 0.540336E+09 | 0.308393E+09 | 0.231943E+09 | 0.962031E+09 | 0.135966E+09 |
May | 0.560366E+09 | 0.314023E+09 | 0.246343E+09 | 0.107765E+10 | 83732692.12 |
June | 0.574867E+09 | 0.338034E+09 | 0.236833E+09 | 0.127524E+10 | 20581844.20 |
July | 0.432114E+09 | 0.201359E+09 | 0.230755E+09 | 0.103337E+10 | 13351401.88 |
August | 0.413642E+09 | 0.208000E+09 | 0.205642E+09 | 0.966597E+09 | 15089462.75 |
September | 0.348351E+09 | 0.146469E+09 | 0.201882E+09 | 0.774892E+09 | 26284509.98 |
October | 0.369811E+09 | 0.212073E+09 | 0.157738E+09 | 0.636244E+09 | 0.198176E+09 |
November | 0.327596E+09 | 0.197665E+09 | 0.129932E+09 | 0.477609E+09 | 0.322863E+09 |
December | 0.271608E+09 | 0.153993E+09 | 0.117616E+09 | 0.359485E+09 | 0.471178E+09 |
Annual Sum or Average | 0.479229E+10 | 0.258708E+10 | 0.220521E+10 | 0.888730E+10 | 0.230001E+10 |
Minimum of Months | 0.248858E+09 | 0.120775E+09 | 0.117616E+09 | 0.302176E+09 | 13351401.88 |
Maximum of Months | 0.574867E+09 | 0.338034E+09 | 0.246343E+09 | 0.127524E+10 | 0.471178E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53674072.02 | 0.00 | 53674072.02 | 52837478.77 | 0.200728E+09 |
February | 55241433.50 | 0.00 | 55241433.50 | 35291653.23 | 0.172848E+09 |
March | 81295770.76 | 3216.16 | 81292554.60 | 90274098.04 | 0.169930E+09 |
April | 96350800.51 | 1418628.78 | 94932171.74 | 0.180864E+09 | 72079428.85 |
May | 0.116786E+09 | 9916509.70 | 0.106870E+09 | 0.258132E+09 | 40648567.08 |
June | 0.130521E+09 | 23848337.92 | 0.106672E+09 | 0.384307E+09 | 10110829.60 |
July | 0.115375E+09 | 12397170.40 | 0.102978E+09 | 0.356825E+09 | 6602779.74 |
August | 92836668.46 | 2279405.50 | 90557262.96 | 0.292315E+09 | 8438969.16 |
September | 84720382.40 | 52432.38 | 84667950.02 | 0.236075E+09 | 14923324.96 |
October | 67690153.51 | 0.00 | 67690153.51 | 0.119222E+09 | 0.108606E+09 |
November | 54578999.93 | 0.00 | 54578999.93 | 52320865.40 | 0.172696E+09 |
December | 50136496.34 | 0.00 | 50136496.34 | 34429785.83 | 0.247144E+09 |
Annual Sum or Average | 0.999207E+09 | 49915700.83 | 0.949291E+09 | 0.209289E+10 | 0.122476E+10 |
Minimum of Months | 50136496.34 | 0.00 | 50136496.34 | 34429785.83 | 6602779.74 |
Maximum of Months | 0.130521E+09 | 23848337.92 | 0.106870E+09 | 0.384307E+09 | 0.247144E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340154E+09 | 0.211926E+09 | 0.128229E+09 | 0.518625E+09 | 0.371637E+09 |
February | 0.248858E+09 | 0.120775E+09 | 0.128083E+09 | 0.313036E+09 | 0.316558E+09 |
March | 0.364588E+09 | 0.174372E+09 | 0.190216E+09 | 0.526716E+09 | 0.308824E+09 |
April | 0.540336E+09 | 0.308393E+09 | 0.231943E+09 | 0.963153E+09 | 0.138926E+09 |
May | 0.560366E+09 | 0.314023E+09 | 0.246343E+09 | 0.107382E+10 | 84987211.56 |
June | 0.574867E+09 | 0.338034E+09 | 0.236833E+09 | 0.127002E+10 | 21453394.63 |
July | 0.432114E+09 | 0.201359E+09 | 0.230755E+09 | 0.103193E+10 | 13729523.86 |
August | 0.413642E+09 | 0.208000E+09 | 0.205642E+09 | 0.966962E+09 | 16549047.55 |
September | 0.348351E+09 | 0.146469E+09 | 0.201882E+09 | 0.776604E+09 | 27815376.19 |
October | 0.369811E+09 | 0.212073E+09 | 0.157738E+09 | 0.644705E+09 | 0.199447E+09 |
November | 0.327596E+09 | 0.197665E+09 | 0.129932E+09 | 0.490062E+09 | 0.318105E+09 |
December | 0.271608E+09 | 0.153993E+09 | 0.117616E+09 | 0.377905E+09 | 0.456832E+09 |
Annual Sum or Average | 0.479229E+10 | 0.258708E+10 | 0.220521E+10 | 0.895355E+10 | 0.227486E+10 |
Minimum of Months | 0.248858E+09 | 0.120775E+09 | 0.117616E+09 | 0.313036E+09 | 13729523.86 |
Maximum of Months | 0.574867E+09 | 0.338034E+09 | 0.246343E+09 | 0.127002E+10 | 0.456832E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353983E+09 | 0.282791E+09 | 71191720.82 | 0.515427E+09 | 0.216473E+09 |
February | 0.199502E+09 | 0.133746E+09 | 65755807.07 | 0.254931E+09 | 0.195788E+09 |
March | 0.182850E+09 | 92654621.17 | 90194909.73 | 0.245587E+09 | 0.194482E+09 |
April | 0.155304E+09 | 63973596.40 | 91330373.15 | 0.272617E+09 | 0.107637E+09 |
May | 0.107231E+09 | 18653222.29 | 88577606.46 | 0.203861E+09 | 77940440.26 |
June | 87837819.98 | 6701448.63 | 81136371.35 | 0.223671E+09 | 31694479.29 |
July | 91975290.32 | 8744924.55 | 83230365.76 | 0.223455E+09 | 25718572.16 |
August | 0.113732E+09 | 32030806.41 | 81700800.92 | 0.263983E+09 | 34614846.93 |
September | 0.156339E+09 | 66076882.86 | 90262586.66 | 0.309741E+09 | 46291136.88 |
October | 0.259316E+09 | 0.179516E+09 | 79800009.62 | 0.412189E+09 | 0.135520E+09 |
November | 0.294982E+09 | 0.226559E+09 | 68423598.87 | 0.421723E+09 | 0.192298E+09 |
December | 0.329655E+09 | 0.261175E+09 | 68480327.14 | 0.458834E+09 | 0.254488E+09 |
Annual Sum or Average | 0.233271E+10 | 0.137262E+10 | 0.960084E+09 | 0.380602E+10 | 0.151294E+10 |
Minimum of Months | 87837819.98 | 6701448.63 | 65755807.07 | 0.203861E+09 | 25718572.16 |
Maximum of Months | 0.353983E+09 | 0.282791E+09 | 91330373.15 | 0.515427E+09 | 0.254488E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42944949.46 | 0.00 | 42944949.46 | 44969283.45 | 0.159105E+09 |
February | 44199004.85 | 0.00 | 44199004.85 | 28505234.56 | 0.141751E+09 |
March | 65045237.58 | 2573.27 | 65042664.31 | 75209227.30 | 0.135265E+09 |
April | 77090857.89 | 1135053.46 | 75955804.43 | 0.156673E+09 | 52622517.15 |
May | 93441433.49 | 7934259.35 | 85507174.14 | 0.221138E+09 | 28578151.11 |
June | 0.104430E+09 | 19081199.32 | 85349110.47 | 0.326954E+09 | 5932446.51 |
July | 92312481.83 | 9919050.97 | 82393430.86 | 0.303174E+09 | 4151725.71 |
August | 74279179.59 | 1823766.12 | 72455413.47 | 0.250834E+09 | 5135567.25 |
September | 67785290.05 | 41951.47 | 67743338.59 | 0.202303E+09 | 9337060.59 |
October | 54159300.98 | 0.00 | 54159300.98 | 0.103089E+09 | 83022949.90 |
November | 43668987.75 | 0.00 | 43668987.75 | 44793566.67 | 0.136219E+09 |
December | 40114513.77 | 0.00 | 40114513.77 | 27791154.22 | 0.200822E+09 |
Annual Sum or Average | 0.799472E+09 | 39937853.95 | 0.759534E+09 | 0.178543E+10 | 0.961943E+09 |
Minimum of Months | 40114513.77 | 0.00 | 40114513.77 | 27791154.22 | 4151725.71 |
Maximum of Months | 0.104430E+09 | 19081199.32 | 85507174.14 | 0.326954E+09 | 0.200822E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.323939E+09 | 0.203319E+09 | 0.120620E+09 | 0.436421E+09 | 0.344600E+09 |
February | 0.290851E+09 | 0.167343E+09 | 0.123508E+09 | 0.349189E+09 | 0.304168E+09 |
March | 0.399855E+09 | 0.205717E+09 | 0.194139E+09 | 0.553071E+09 | 0.285986E+09 |
April | 0.551427E+09 | 0.328551E+09 | 0.222876E+09 | 0.971257E+09 | 0.121987E+09 |
May | 0.591518E+09 | 0.350985E+09 | 0.240533E+09 | 0.112567E+10 | 73532071.19 |
June | 0.595597E+09 | 0.370022E+09 | 0.225575E+09 | 0.131975E+10 | 18034708.24 |
July | 0.520577E+09 | 0.293732E+09 | 0.226845E+09 | 0.118975E+10 | 11949007.10 |
August | 0.494504E+09 | 0.282527E+09 | 0.211977E+09 | 0.110463E+10 | 14468939.71 |
September | 0.392148E+09 | 0.189135E+09 | 0.203013E+09 | 0.847312E+09 | 24615420.31 |
October | 0.406651E+09 | 0.247359E+09 | 0.159292E+09 | 0.682747E+09 | 0.182885E+09 |
November | 0.302834E+09 | 0.181731E+09 | 0.121103E+09 | 0.406134E+09 | 0.296694E+09 |
December | 0.285842E+09 | 0.172873E+09 | 0.112970E+09 | 0.340746E+09 | 0.431761E+09 |
Annual Sum or Average | 0.515574E+10 | 0.299329E+10 | 0.216245E+10 | 0.932669E+10 | 0.211068E+10 |
Minimum of Months | 0.285842E+09 | 0.167343E+09 | 0.112970E+09 | 0.340746E+09 | 11949007.10 |
Maximum of Months | 0.595597E+09 | 0.370022E+09 | 0.240533E+09 | 0.131975E+10 | 0.431761E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442566E+09 | 0.353559E+09 | 89007348.67 | 0.692219E+09 | 0.183283E+09 |
February | 0.249427E+09 | 0.167216E+09 | 82211105.16 | 0.353006E+09 | 0.161237E+09 |
March | 0.228607E+09 | 0.115841E+09 | 0.112766E+09 | 0.350088E+09 | 0.161067E+09 |
April | 0.194169E+09 | 79982898.78 | 0.114186E+09 | 0.386370E+09 | 72805465.95 |
May | 0.134065E+09 | 23321164.89 | 0.110744E+09 | 0.307903E+09 | 44720205.63 |
June | 0.109819E+09 | 8378476.71 | 0.101441E+09 | 0.348959E+09 | 10844433.77 |
July | 0.114992E+09 | 10933329.61 | 0.104059E+09 | 0.359241E+09 | 7130579.91 |
August | 0.142193E+09 | 40046470.60 | 0.102146E+09 | 0.400854E+09 | 8203992.83 |
September | 0.195463E+09 | 82612529.72 | 0.112851E+09 | 0.450719E+09 | 13832082.06 |
October | 0.324210E+09 | 0.224440E+09 | 99769849.61 | 0.565506E+09 | 98642573.21 |
November | 0.368801E+09 | 0.283255E+09 | 85546508.11 | 0.572045E+09 | 0.156399E+09 |
December | 0.412151E+09 | 0.326533E+09 | 85617432.54 | 0.619576E+09 | 0.227241E+09 |
Annual Sum or Average | 0.291646E+10 | 0.171612E+10 | 0.120034E+10 | 0.540649E+10 | 0.114541E+10 |
Minimum of Months | 0.109819E+09 | 8378476.71 | 82211105.16 | 0.307903E+09 | 7130579.91 |
Maximum of Months | 0.442566E+09 | 0.353559E+09 | 0.114186E+09 | 0.692219E+09 | 0.227241E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53674072.02 | 0.00 | 53674072.02 | 50248873.00 | 0.197806E+09 |
February | 55241433.50 | 0.00 | 55241433.50 | 32728258.72 | 0.173626E+09 |
March | 81295770.76 | 3216.16 | 81292554.60 | 86040357.35 | 0.169105E+09 |
April | 96350800.51 | 1418628.78 | 94932171.74 | 0.176433E+09 | 71530154.34 |
May | 0.116786E+09 | 9916509.70 | 0.106870E+09 | 0.252074E+09 | 40013865.83 |
June | 0.130521E+09 | 23848337.92 | 0.106672E+09 | 0.381462E+09 | 9718777.43 |
July | 0.115375E+09 | 12397170.40 | 0.102978E+09 | 0.353157E+09 | 6462275.36 |
August | 92836668.46 | 2279405.50 | 90557262.96 | 0.288802E+09 | 8421278.39 |
September | 84720382.40 | 52432.38 | 84667950.02 | 0.233222E+09 | 14957815.04 |
October | 67690153.51 | 0.00 | 67690153.51 | 0.115269E+09 | 0.108331E+09 |
November | 54578999.93 | 0.00 | 54578999.93 | 50293085.47 | 0.169665E+09 |
December | 50136496.34 | 0.00 | 50136496.34 | 32349607.32 | 0.245849E+09 |
Annual Sum or Average | 0.999207E+09 | 49915700.83 | 0.949291E+09 | 0.205208E+10 | 0.121549E+10 |
Minimum of Months | 50136496.34 | 0.00 | 50136496.34 | 32349607.32 | 6462275.36 |
Maximum of Months | 0.130521E+09 | 23848337.92 | 0.106870E+09 | 0.381462E+09 | 0.245849E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.323939E+09 | 0.203319E+09 | 0.120620E+09 | 0.454268E+09 | 0.334381E+09 |
February | 0.290851E+09 | 0.167343E+09 | 0.123508E+09 | 0.360825E+09 | 0.295667E+09 |
March | 0.399855E+09 | 0.205717E+09 | 0.194139E+09 | 0.559891E+09 | 0.285675E+09 |
April | 0.551427E+09 | 0.328551E+09 | 0.222876E+09 | 0.967215E+09 | 0.124040E+09 |
May | 0.591518E+09 | 0.350985E+09 | 0.240533E+09 | 0.111321E+10 | 73970729.55 |
June | 0.595597E+09 | 0.370022E+09 | 0.225575E+09 | 0.131098E+10 | 18278181.01 |
July | 0.520577E+09 | 0.293732E+09 | 0.226845E+09 | 0.118685E+10 | 12041891.72 |
August | 0.494504E+09 | 0.282527E+09 | 0.211977E+09 | 0.110279E+10 | 15645937.59 |
September | 0.392148E+09 | 0.189135E+09 | 0.203013E+09 | 0.845692E+09 | 25747950.90 |
October | 0.406651E+09 | 0.247359E+09 | 0.159292E+09 | 0.688455E+09 | 0.183725E+09 |
November | 0.302834E+09 | 0.181731E+09 | 0.121103E+09 | 0.418379E+09 | 0.289343E+09 |
December | 0.285842E+09 | 0.172873E+09 | 0.112970E+09 | 0.359329E+09 | 0.415038E+09 |
Annual Sum or Average | 0.515574E+10 | 0.299329E+10 | 0.216245E+10 | 0.936788E+10 | 0.207355E+10 |
Minimum of Months | 0.285842E+09 | 0.167343E+09 | 0.112970E+09 | 0.359329E+09 | 12041891.72 |
Maximum of Months | 0.595597E+09 | 0.370022E+09 | 0.240533E+09 | 0.131098E+10 | 0.415038E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 67974825.56 | 0.00 | 67974825.56 | 62835363.54 | 0.274683E+09 |
February | 69959789.98 | 0.00 | 69959789.98 | 43222815.33 | 0.234458E+09 |
March | 0.102956E+09 | 4073.06 | 0.102952E+09 | 0.116707E+09 | 0.225405E+09 |
April | 0.122022E+09 | 1796603.83 | 0.120226E+09 | 0.230070E+09 | 0.106729E+09 |
May | 0.147902E+09 | 12558633.84 | 0.135344E+09 | 0.320933E+09 | 68143526.67 |
June | 0.165296E+09 | 30202415.22 | 0.135094E+09 | 0.471455E+09 | 21260307.29 |
July | 0.146116E+09 | 15700234.09 | 0.130415E+09 | 0.425178E+09 | 14788985.41 |
August | 0.117572E+09 | 2886723.24 | 0.114685E+09 | 0.347744E+09 | 20055893.45 |
September | 0.107293E+09 | 66402.30 | 0.107227E+09 | 0.280393E+09 | 33505536.18 |
October | 85725308.41 | 0.00 | 85725308.41 | 0.142896E+09 | 0.159454E+09 |
November | 69120859.66 | 0.00 | 69120859.66 | 63372232.06 | 0.238541E+09 |
December | 63494709.17 | 0.00 | 63494709.17 | 38989201.31 | 0.335288E+09 |
Annual Sum or Average | 0.126543E+10 | 63215085.59 | 0.120222E+10 | 0.254380E+10 | 0.173231E+10 |
Minimum of Months | 63494709.17 | 0.00 | 63494709.17 | 38989201.31 | 14788985.41 |
Maximum of Months | 0.165296E+09 | 30202415.22 | 0.135344E+09 | 0.471455E+09 | 0.335288E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 25058335.32 | 0.00 | 25058335.32 | 23163716.81 | 0.101260E+09 |
February | 25790075.39 | 0.00 | 25790075.39 | 15933719.45 | 86430812.91 |
March | 37953831.47 | 1501.50 | 37952329.97 | 43023005.56 | 83093625.28 |
April | 44982438.94 | 662302.56 | 44320136.38 | 84813246.62 | 39344756.43 |
May | 54522983.56 | 4629632.44 | 49893351.11 | 0.118309E+09 | 25120525.53 |
June | 60934981.96 | 11133860.83 | 49801121.12 | 0.173798E+09 | 7837429.59 |
July | 53864241.38 | 5787756.38 | 48076485.00 | 0.156738E+09 | 5451832.38 |
August | 43341827.45 | 1064165.72 | 42277661.74 | 0.128193E+09 | 7393432.78 |
September | 39552649.37 | 24478.64 | 39528170.73 | 0.103365E+09 | 12351527.99 |
October | 31601898.29 | 0.00 | 31601898.29 | 52677268.60 | 58781537.67 |
November | 25480810.94 | 0.00 | 25480810.94 | 23361628.77 | 87936116.28 |
December | 23406778.91 | 0.00 | 23406778.91 | 14373034.02 | 0.123601E+09 |
Annual Sum or Average | 0.466491E+09 | 23303698.08 | 0.443187E+09 | 0.937748E+09 | 0.638602E+09 |
Minimum of Months | 23406778.91 | 0.00 | 23406778.91 | 14373034.02 | 5451832.38 |
Maximum of Months | 60934981.96 | 11133860.83 | 49893351.11 | 0.173798E+09 | 0.123601E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206500E+09 | 0.164969E+09 | 41530470.22 | 0.326866E+09 | 91077597.39 |
February | 0.116382E+09 | 78022138.43 | 38359370.38 | 0.168427E+09 | 78554207.36 |
March | 0.106667E+09 | 54051088.25 | 52616188.64 | 0.167889E+09 | 79442167.38 |
April | 90598271.93 | 37319698.27 | 53278573.67 | 0.181822E+09 | 40751638.83 |
May | 62554278.62 | 10881561.56 | 51672717.06 | 0.142064E+09 | 28155532.11 |
June | 51241154.51 | 3909363.47 | 47331791.04 | 0.156935E+09 | 8995313.15 |
July | 53654793.16 | 5101447.54 | 48553345.62 | 0.158941E+09 | 6028291.86 |
August | 66346579.02 | 18685521.81 | 47661057.22 | 0.180003E+09 | 7814630.31 |
September | 91202342.18 | 38546673.46 | 52655668.72 | 0.204242E+09 | 12251540.42 |
October | 0.151275E+09 | 0.104723E+09 | 46552209.79 | 0.263632E+09 | 54259198.68 |
November | 0.172081E+09 | 0.132165E+09 | 39915655.96 | 0.269567E+09 | 79230908.83 |
December | 0.192308E+09 | 0.152359E+09 | 39948749.01 | 0.293159E+09 | 0.110065E+09 |
Annual Sum or Average | 0.136081E+10 | 0.800734E+09 | 0.560076E+09 | 0.251355E+10 | 0.596626E+09 |
Minimum of Months | 51241154.51 | 3909363.47 | 38359370.38 | 0.142064E+09 | 6028291.86 |
Maximum of Months | 0.206500E+09 | 0.164969E+09 | 53278573.67 | 0.326866E+09 | 0.110065E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.560483E+09 | 0.447760E+09 | 0.112722E+09 | 0.887181E+09 | 0.247203E+09 |
February | 0.315883E+09 | 0.211768E+09 | 0.104115E+09 | 0.457146E+09 | 0.213212E+09 |
March | 0.289517E+09 | 0.146706E+09 | 0.142811E+09 | 0.455685E+09 | 0.215622E+09 |
April | 0.245902E+09 | 0.101293E+09 | 0.144609E+09 | 0.493502E+09 | 0.110608E+09 |
May | 0.169785E+09 | 29534783.85 | 0.140250E+09 | 0.385590E+09 | 76419873.22 |
June | 0.139079E+09 | 10610812.10 | 0.128468E+09 | 0.425954E+09 | 24415119.84 |
July | 0.145630E+09 | 13846372.09 | 0.131784E+09 | 0.431399E+09 | 16362017.17 |
August | 0.180078E+09 | 50716328.22 | 0.129362E+09 | 0.488565E+09 | 21210505.10 |
September | 0.247542E+09 | 0.104624E+09 | 0.142918E+09 | 0.554355E+09 | 33253186.70 |
October | 0.410591E+09 | 0.284239E+09 | 0.126352E+09 | 0.715552E+09 | 0.147271E+09 |
November | 0.467063E+09 | 0.358724E+09 | 0.108339E+09 | 0.731661E+09 | 0.215049E+09 |
December | 0.521963E+09 | 0.413534E+09 | 0.108429E+09 | 0.795693E+09 | 0.298738E+09 |
Annual Sum or Average | 0.369352E+10 | 0.217336E+10 | 0.152016E+10 | 0.682228E+10 | 0.161936E+10 |
Minimum of Months | 0.139079E+09 | 10610812.10 | 0.104115E+09 | 0.385590E+09 | 16362017.17 |
Maximum of Months | 0.560483E+09 | 0.447760E+09 | 0.144609E+09 | 0.887181E+09 | 0.298738E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442566E+09 | 0.353559E+09 | 89007348.67 | 0.691092E+09 | 0.182810E+09 |
February | 0.249427E+09 | 0.167216E+09 | 82211105.16 | 0.354573E+09 | 0.159389E+09 |
March | 0.228607E+09 | 0.115841E+09 | 0.112766E+09 | 0.351652E+09 | 0.160334E+09 |
April | 0.194169E+09 | 79982898.78 | 0.114186E+09 | 0.386093E+09 | 71086432.67 |
May | 0.134065E+09 | 23321164.89 | 0.110744E+09 | 0.310129E+09 | 43100156.02 |
June | 0.109819E+09 | 8378476.71 | 0.101441E+09 | 0.351492E+09 | 10329360.97 |
July | 0.114992E+09 | 10933329.61 | 0.104059E+09 | 0.362771E+09 | 6826456.69 |
August | 0.142193E+09 | 40046470.60 | 0.102146E+09 | 0.403164E+09 | 7538194.66 |
September | 0.195463E+09 | 82612529.72 | 0.112851E+09 | 0.451181E+09 | 12703384.60 |
October | 0.324210E+09 | 0.224440E+09 | 99769849.61 | 0.565746E+09 | 96674450.41 |
November | 0.368801E+09 | 0.283255E+09 | 85546508.11 | 0.570674E+09 | 0.156075E+09 |
December | 0.412151E+09 | 0.326533E+09 | 85617432.54 | 0.620386E+09 | 0.225813E+09 |
Annual Sum or Average | 0.291646E+10 | 0.171612E+10 | 0.120034E+10 | 0.541895E+10 | 0.113268E+10 |
Minimum of Months | 0.109819E+09 | 8378476.71 | 82211105.16 | 0.310129E+09 | 6826456.69 |
Maximum of Months | 0.442566E+09 | 0.353559E+09 | 0.114186E+09 | 0.691092E+09 | 0.225813E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340154E+09 | 0.211926E+09 | 0.128229E+09 | 0.498332E+09 | 0.373608E+09 |
February | 0.248858E+09 | 0.120775E+09 | 0.128083E+09 | 0.298969E+09 | 0.320019E+09 |
March | 0.364588E+09 | 0.174372E+09 | 0.190216E+09 | 0.515451E+09 | 0.304606E+09 |
April | 0.540336E+09 | 0.308393E+09 | 0.231943E+09 | 0.955157E+09 | 0.131944E+09 |
May | 0.560366E+09 | 0.314023E+09 | 0.246343E+09 | 0.107280E+10 | 79918236.34 |
June | 0.574867E+09 | 0.338034E+09 | 0.236833E+09 | 0.127094E+10 | 18942652.11 |
July | 0.432114E+09 | 0.201359E+09 | 0.230755E+09 | 0.103070E+10 | 12597294.22 |
August | 0.413642E+09 | 0.208000E+09 | 0.205642E+09 | 0.964073E+09 | 13995131.58 |
September | 0.348351E+09 | 0.146469E+09 | 0.201882E+09 | 0.772843E+09 | 24225575.64 |
October | 0.369811E+09 | 0.212073E+09 | 0.157738E+09 | 0.633249E+09 | 0.192270E+09 |
November | 0.327596E+09 | 0.197665E+09 | 0.129932E+09 | 0.474117E+09 | 0.317297E+09 |
December | 0.271608E+09 | 0.153993E+09 | 0.117616E+09 | 0.357278E+09 | 0.464385E+09 |
Annual Sum or Average | 0.479229E+10 | 0.258708E+10 | 0.220521E+10 | 0.884391E+10 | 0.225381E+10 |
Minimum of Months | 0.248858E+09 | 0.120775E+09 | 0.117616E+09 | 0.298969E+09 | 12597294.22 |
Maximum of Months | 0.574867E+09 | 0.338034E+09 | 0.246343E+09 | 0.127094E+10 | 0.464385E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53674072.02 | 0.00 | 53674072.02 | 54154783.44 | 0.196606E+09 |
February | 55241433.50 | 0.00 | 55241433.50 | 35462314.07 | 0.169927E+09 |
March | 81295770.76 | 3216.16 | 81292554.60 | 89928589.19 | 0.168405E+09 |
April | 96350800.51 | 1418628.78 | 94932171.74 | 0.180567E+09 | 70253488.17 |
May | 0.116786E+09 | 9916509.70 | 0.106870E+09 | 0.258816E+09 | 38867831.25 |
June | 0.130521E+09 | 23848337.92 | 0.106672E+09 | 0.384634E+09 | 9372017.85 |
July | 0.115375E+09 | 12397170.40 | 0.102978E+09 | 0.357105E+09 | 6244048.19 |
August | 92836668.46 | 2279405.50 | 90557262.96 | 0.292751E+09 | 7873337.27 |
September | 84720382.40 | 52432.38 | 84667950.02 | 0.236809E+09 | 13680340.02 |
October | 67690153.51 | 0.00 | 67690153.51 | 0.120385E+09 | 0.104942E+09 |
November | 54578999.93 | 0.00 | 54578999.93 | 53362221.56 | 0.168989E+09 |
December | 50136496.34 | 0.00 | 50136496.34 | 35665104.24 | 0.242596E+09 |
Annual Sum or Average | 0.999207E+09 | 49915700.83 | 0.949291E+09 | 0.209964E+10 | 0.119776E+10 |
Minimum of Months | 50136496.34 | 0.00 | 50136496.34 | 35462314.07 | 6244048.19 |
Maximum of Months | 0.130521E+09 | 23848337.92 | 0.106870E+09 | 0.384634E+09 | 0.242596E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340154E+09 | 0.211926E+09 | 0.128229E+09 | 0.517443E+09 | 0.363941E+09 |
February | 0.248858E+09 | 0.120775E+09 | 0.128083E+09 | 0.311092E+09 | 0.310994E+09 |
March | 0.364588E+09 | 0.174372E+09 | 0.190216E+09 | 0.522372E+09 | 0.305721E+09 |
April | 0.540336E+09 | 0.308393E+09 | 0.231943E+09 | 0.956554E+09 | 0.135059E+09 |
May | 0.560366E+09 | 0.314023E+09 | 0.246343E+09 | 0.106945E+10 | 80724014.47 |
June | 0.574867E+09 | 0.338034E+09 | 0.236833E+09 | 0.126579E+10 | 19620814.81 |
July | 0.432114E+09 | 0.201359E+09 | 0.230755E+09 | 0.102936E+10 | 12886749.94 |
August | 0.413642E+09 | 0.208000E+09 | 0.205642E+09 | 0.964614E+09 | 15328690.24 |
September | 0.348351E+09 | 0.146469E+09 | 0.201882E+09 | 0.775000E+09 | 25424381.99 |
October | 0.369811E+09 | 0.212073E+09 | 0.157738E+09 | 0.643141E+09 | 0.192676E+09 |
November | 0.327596E+09 | 0.197665E+09 | 0.129932E+09 | 0.488584E+09 | 0.311196E+09 |
December | 0.271608E+09 | 0.153993E+09 | 0.117616E+09 | 0.377973E+09 | 0.448613E+09 |
Annual Sum or Average | 0.479229E+10 | 0.258708E+10 | 0.220521E+10 | 0.892138E+10 | 0.222219E+10 |
Minimum of Months | 0.248858E+09 | 0.120775E+09 | 0.117616E+09 | 0.311092E+09 | 12886749.94 |
Maximum of Months | 0.574867E+09 | 0.338034E+09 | 0.246343E+09 | 0.126579E+10 | 0.448613E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.649066E+09 | 0.518528E+09 | 0.130538E+09 | 0.999741E+09 | 0.278183E+09 |
February | 0.365808E+09 | 0.245238E+09 | 0.120570E+09 | 0.508914E+09 | 0.244404E+09 |
March | 0.335275E+09 | 0.169892E+09 | 0.165382E+09 | 0.508935E+09 | 0.238779E+09 |
April | 0.284767E+09 | 0.117303E+09 | 0.167464E+09 | 0.574325E+09 | 0.100553E+09 |
May | 0.196619E+09 | 34202726.45 | 0.162417E+09 | 0.469984E+09 | 58937734.31 |
June | 0.161060E+09 | 12287840.18 | 0.148772E+09 | 0.537932E+09 | 12518009.60 |
July | 0.168647E+09 | 16034777.14 | 0.152612E+09 | 0.549401E+09 | 8815810.18 |
August | 0.208539E+09 | 58731992.40 | 0.149807E+09 | 0.605727E+09 | 9847902.11 |
September | 0.286666E+09 | 0.121159E+09 | 0.165506E+09 | 0.668822E+09 | 17477789.56 |
October | 0.475485E+09 | 0.329163E+09 | 0.146322E+09 | 0.825307E+09 | 0.143943E+09 |
November | 0.540882E+09 | 0.415420E+09 | 0.125462E+09 | 0.826441E+09 | 0.236441E+09 |
December | 0.604458E+09 | 0.478892E+09 | 0.125566E+09 | 0.892158E+09 | 0.346644E+09 |
Annual Sum or Average | 0.427727E+10 | 0.251685E+10 | 0.176042E+10 | 0.796769E+10 | 0.169654E+10 |
Minimum of Months | 0.161060E+09 | 12287840.18 | 0.120570E+09 | 0.469984E+09 | 8815810.18 |
Maximum of Months | 0.649066E+09 | 0.518528E+09 | 0.167464E+09 | 0.999741E+09 | 0.346644E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.375704E+09 | 0.00 | 0.375704E+09 | 0.274615E+09 | 0.173201E+10 |
February | 0.386675E+09 | 0.00 | 0.386675E+09 | 0.161711E+09 | 0.158116E+10 |
March | 0.569049E+09 | 22512.27 | 0.569026E+09 | 0.511658E+09 | 0.148698E+10 |
April | 0.674430E+09 | 9930025.34 | 0.664500E+09 | 0.116867E+10 | 0.669740E+09 |
May | 0.817473E+09 | 69412938.91 | 0.748060E+09 | 0.168212E+10 | 0.417349E+09 |
June | 0.913609E+09 | 0.166932E+09 | 0.746677E+09 | 0.253710E+10 | 0.134757E+09 |
July | 0.807597E+09 | 86776906.14 | 0.720820E+09 | 0.227002E+10 | 99533346.31 |
August | 0.649832E+09 | 15955234.21 | 0.633877E+09 | 0.185156E+10 | 0.138196E+09 |
September | 0.593020E+09 | 367012.78 | 0.592653E+09 | 0.149046E+10 | 0.219743E+09 |
October | 0.473813E+09 | 0.00 | 0.473813E+09 | 0.728050E+09 | 0.977737E+09 |
November | 0.382039E+09 | 0.00 | 0.382039E+09 | 0.277655E+09 | 0.151554E+10 |
December | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.150861E+09 | 0.212655E+10 |
Annual Sum or Average | 0.699418E+10 | 0.349397E+09 | 0.664479E+10 | 0.131045E+11 | 0.110993E+11 |
Minimum of Months | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.150861E+09 | 99533346.31 |
Maximum of Months | 0.913609E+09 | 0.166932E+09 | 0.748060E+09 | 0.253710E+10 | 0.212655E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.375704E+09 | 0.00 | 0.375704E+09 | 0.250570E+09 | 0.178247E+10 |
February | 0.386675E+09 | 0.00 | 0.386675E+09 | 0.143100E+09 | 0.163894E+10 |
March | 0.569049E+09 | 22512.27 | 0.569026E+09 | 0.480399E+09 | 0.153228E+10 |
April | 0.674430E+09 | 9930025.34 | 0.664500E+09 | 0.114386E+10 | 0.689936E+09 |
May | 0.817473E+09 | 69412938.91 | 0.748060E+09 | 0.165629E+10 | 0.430795E+09 |
June | 0.913609E+09 | 0.166932E+09 | 0.746677E+09 | 0.251004E+10 | 0.140860E+09 |
July | 0.807597E+09 | 86776906.14 | 0.720820E+09 | 0.224168E+10 | 0.105448E+09 |
August | 0.649832E+09 | 15955234.21 | 0.633877E+09 | 0.182535E+10 | 0.147004E+09 |
September | 0.593020E+09 | 367012.78 | 0.592653E+09 | 0.146702E+10 | 0.231752E+09 |
October | 0.473813E+09 | 0.00 | 0.473813E+09 | 0.704404E+09 | 0.100806E+10 |
November | 0.382039E+09 | 0.00 | 0.382039E+09 | 0.255353E+09 | 0.156271E+10 |
December | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.132286E+09 | 0.219119E+10 |
Annual Sum or Average | 0.699418E+10 | 0.349397E+09 | 0.664479E+10 | 0.128104E+11 | 0.114614E+11 |
Minimum of Months | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.132286E+09 | 0.105448E+09 |
Maximum of Months | 0.913609E+09 | 0.166932E+09 | 0.748060E+09 | 0.251004E+10 | 0.219119E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53674072.02 | 0.00 | 53674072.02 | 59818890.50 | 0.229261E+09 |
February | 55241433.50 | 0.00 | 55241433.50 | 36000024.24 | 0.207932E+09 |
March | 81295770.76 | 3216.16 | 81292554.60 | 98980526.22 | 0.201878E+09 |
April | 96350800.51 | 1418628.78 | 94932171.74 | 0.208246E+09 | 95472978.54 |
May | 0.116786E+09 | 9916509.70 | 0.106870E+09 | 0.291480E+09 | 65746083.42 |
June | 0.130521E+09 | 23848337.92 | 0.106672E+09 | 0.413792E+09 | 25446915.31 |
July | 0.115375E+09 | 12397170.40 | 0.102978E+09 | 0.376177E+09 | 19420047.86 |
August | 92836668.46 | 2279405.50 | 90557262.96 | 0.316599E+09 | 24779302.70 |
September | 84720382.40 | 52432.38 | 84667950.02 | 0.261766E+09 | 35568313.02 |
October | 67690153.51 | 0.00 | 67690153.51 | 0.137120E+09 | 0.133035E+09 |
November | 54578999.93 | 0.00 | 54578999.93 | 59802201.93 | 0.199588E+09 |
December | 50136496.34 | 0.00 | 50136496.34 | 37207154.19 | 0.278381E+09 |
Annual Sum or Average | 0.999207E+09 | 49915700.83 | 0.949291E+09 | 0.229699E+10 | 0.151651E+10 |
Minimum of Months | 50136496.34 | 0.00 | 50136496.34 | 36000024.24 | 19420047.86 |
Maximum of Months | 0.130521E+09 | 23848337.92 | 0.106870E+09 | 0.413792E+09 | 0.278381E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.647832E+09 | 0.406608E+09 | 0.241223E+09 | 0.945909E+09 | 0.786116E+09 |
February | 0.581660E+09 | 0.334662E+09 | 0.246998E+09 | 0.736769E+09 | 0.720383E+09 |
March | 0.799654E+09 | 0.411405E+09 | 0.388250E+09 | 0.116946E+10 | 0.696216E+09 |
April | 0.110278E+10 | 0.657056E+09 | 0.445720E+09 | 0.205928E+10 | 0.343050E+09 |
May | 0.118295E+10 | 0.701920E+09 | 0.481032E+09 | 0.237275E+10 | 0.244477E+09 |
June | 0.119111E+10 | 0.739991E+09 | 0.451119E+09 | 0.273813E+10 | 95286102.54 |
July | 0.104108E+10 | 0.587423E+09 | 0.453658E+09 | 0.245587E+10 | 72402116.89 |
August | 0.988937E+09 | 0.565014E+09 | 0.423923E+09 | 0.230489E+10 | 92736010.00 |
September | 0.784240E+09 | 0.378243E+09 | 0.405997E+09 | 0.179622E+10 | 0.131253E+09 |
October | 0.813243E+09 | 0.494683E+09 | 0.318561E+09 | 0.146488E+10 | 0.464178E+09 |
November | 0.605626E+09 | 0.363437E+09 | 0.242189E+09 | 0.875946E+09 | 0.691719E+09 |
December | 0.571644E+09 | 0.345721E+09 | 0.225923E+09 | 0.739222E+09 | 0.951347E+09 |
Annual Sum or Average | 0.103108E+11 | 0.598616E+10 | 0.432459E+10 | 0.196593E+11 | 0.528916E+10 |
Minimum of Months | 0.571644E+09 | 0.334662E+09 | 0.225923E+09 | 0.736769E+09 | 72402116.89 |
Maximum of Months | 0.119111E+10 | 0.739991E+09 | 0.481032E+09 | 0.273813E+10 | 0.951347E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.442566E+09 | 0.353559E+09 | 89007348.67 | 0.716085E+09 | 0.209700E+09 |
February | 0.249427E+09 | 0.167216E+09 | 82211105.16 | 0.366101E+09 | 0.190955E+09 |
March | 0.228607E+09 | 0.115841E+09 | 0.112766E+09 | 0.368767E+09 | 0.194382E+09 |
April | 0.194169E+09 | 79982898.78 | 0.114186E+09 | 0.416432E+09 | 98289897.73 |
May | 0.134065E+09 | 23321164.89 | 0.110744E+09 | 0.340426E+09 | 70504609.14 |
June | 0.109819E+09 | 8378476.71 | 0.101441E+09 | 0.376340E+09 | 26833289.79 |
July | 0.114992E+09 | 10933329.61 | 0.104059E+09 | 0.381061E+09 | 20179051.68 |
August | 0.142193E+09 | 40046470.60 | 0.102146E+09 | 0.427977E+09 | 25066245.57 |
September | 0.195463E+09 | 82612529.72 | 0.112851E+09 | 0.478714E+09 | 35423831.48 |
October | 0.324210E+09 | 0.224440E+09 | 99769849.61 | 0.593631E+09 | 0.124851E+09 |
November | 0.368801E+09 | 0.283255E+09 | 85546508.11 | 0.592949E+09 | 0.183297E+09 |
December | 0.412151E+09 | 0.326533E+09 | 85617432.54 | 0.640428E+09 | 0.251706E+09 |
Annual Sum or Average | 0.291646E+10 | 0.171612E+10 | 0.120034E+10 | 0.569891E+10 | 0.143119E+10 |
Minimum of Months | 0.109819E+09 | 8378476.71 | 82211105.16 | 0.340426E+09 | 20179051.68 |
Maximum of Months | 0.442566E+09 | 0.353559E+09 | 0.114186E+09 | 0.716085E+09 | 0.251706E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 67974825.56 | 0.00 | 67974825.56 | 57582953.50 | 0.275241E+09 |
February | 69959789.98 | 0.00 | 69959789.98 | 37905466.71 | 0.239125E+09 |
March | 0.102956E+09 | 4073.06 | 0.102952E+09 | 0.108776E+09 | 0.229165E+09 |
April | 0.122022E+09 | 1796603.83 | 0.120226E+09 | 0.218569E+09 | 0.110055E+09 |
May | 0.147902E+09 | 12558633.84 | 0.135344E+09 | 0.309768E+09 | 70666027.33 |
June | 0.165296E+09 | 30202415.22 | 0.135094E+09 | 0.459984E+09 | 22775878.43 |
July | 0.146116E+09 | 15700234.09 | 0.130415E+09 | 0.411482E+09 | 16439998.88 |
August | 0.117572E+09 | 2886723.24 | 0.114685E+09 | 0.335267E+09 | 22502449.29 |
September | 0.107293E+09 | 66402.30 | 0.107227E+09 | 0.270214E+09 | 36412519.70 |
October | 85725308.41 | 0.00 | 85725308.41 | 0.137187E+09 | 0.157779E+09 |
November | 69120859.66 | 0.00 | 69120859.66 | 58469399.15 | 0.238283E+09 |
December | 63494709.17 | 0.00 | 63494709.17 | 34354383.82 | 0.338278E+09 |
Annual Sum or Average | 0.126543E+10 | 63215085.59 | 0.120222E+10 | 0.243956E+10 | 0.175672E+10 |
Minimum of Months | 63494709.17 | 0.00 | 63494709.17 | 34354383.82 | 16439998.88 |
Maximum of Months | 0.165296E+09 | 30202415.22 | 0.135344E+09 | 0.459984E+09 | 0.338278E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60817333.99 | 0.00 | 60817333.99 | 51519686.68 | 0.246229E+09 |
February | 62593289.17 | 0.00 | 62593289.17 | 33914164.69 | 0.213946E+09 |
March | 92115091.26 | 3644.19 | 92111447.08 | 97322673.45 | 0.205035E+09 |
April | 0.109174E+09 | 1607428.26 | 0.107566E+09 | 0.195555E+09 | 98466203.95 |
May | 0.132329E+09 | 11236257.28 | 0.121093E+09 | 0.277151E+09 | 63225162.40 |
June | 0.147891E+09 | 27022215.34 | 0.120869E+09 | 0.411550E+09 | 20377664.73 |
July | 0.130730E+09 | 14047058.93 | 0.116683E+09 | 0.368154E+09 | 14708929.28 |
August | 0.105192E+09 | 2582762.23 | 0.102609E+09 | 0.299964E+09 | 20133026.64 |
September | 95995470.41 | 59410.39 | 95936060.02 | 0.241761E+09 | 32578419.34 |
October | 76698758.25 | 0.00 | 76698758.25 | 0.122742E+09 | 0.141168E+09 |
November | 61842695.04 | 0.00 | 61842695.04 | 52312792.96 | 0.213183E+09 |
December | 56808956.88 | 0.00 | 56808956.88 | 30736997.37 | 0.302616E+09 |
Annual Sum or Average | 0.113219E+10 | 56558776.60 | 0.107563E+10 | 0.218268E+10 | 0.157167E+10 |
Minimum of Months | 56808956.88 | 0.00 | 56808956.88 | 30736997.37 | 14708929.28 |
Maximum of Months | 0.147891E+09 | 27022215.34 | 0.121093E+09 | 0.411550E+09 | 0.302616E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.165223E+10 | 0.131994E+10 | 0.332291E+09 | 0.258295E+10 | 0.732516E+09 |
February | 0.931184E+09 | 0.624266E+09 | 0.306919E+09 | 0.132108E+10 | 0.642410E+09 |
March | 0.853459E+09 | 0.432470E+09 | 0.420989E+09 | 0.130976E+10 | 0.648917E+09 |
April | 0.724889E+09 | 0.298600E+09 | 0.426289E+09 | 0.141341E+10 | 0.336153E+09 |
May | 0.500505E+09 | 87064857.88 | 0.413440E+09 | 0.110218E+10 | 0.232466E+09 |
June | 0.409987E+09 | 31279350.23 | 0.378708E+09 | 0.122353E+10 | 76132272.91 |
July | 0.429299E+09 | 40817377.39 | 0.388482E+09 | 0.123129E+10 | 52920675.31 |
August | 0.530848E+09 | 0.149505E+09 | 0.381343E+09 | 0.140086E+10 | 69454160.10 |
September | 0.729722E+09 | 0.308417E+09 | 0.421305E+09 | 0.159745E+10 | 0.106089E+09 |
October | 0.121037E+10 | 0.837901E+09 | 0.372471E+09 | 0.208045E+10 | 0.431295E+09 |
November | 0.137684E+10 | 0.105747E+10 | 0.319371E+09 | 0.212877E+10 | 0.635647E+09 |
December | 0.153868E+10 | 0.121905E+10 | 0.319635E+09 | 0.231630E+10 | 0.889322E+09 |
Annual Sum or Average | 0.108880E+11 | 0.640678E+10 | 0.448124E+10 | 0.197080E+11 | 0.485332E+10 |
Minimum of Months | 0.409987E+09 | 31279350.23 | 0.306919E+09 | 0.110218E+10 | 52920675.31 |
Maximum of Months | 0.165223E+10 | 0.131994E+10 | 0.426289E+09 | 0.258295E+10 | 0.889322E+09 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1286.65 | 372.79 | 835.71 | 667.64 | 168.07 | 0.00 | 0.00 |
February | 735.59 | 344.34 | 521.47 | 349.59 | 171.87 | 0.00 | 0.00 |
March | 662.75 | 312.36 | 431.69 | 218.75 | 212.94 | 0.00 | 0.00 |
April | 724.38 | 179.52 | 378.88 | 156.07 | 222.81 | 0.00 | 0.00 |
May | 537.01 | 121.04 | 253.16 | 44.04 | 209.12 | 0.00 | 0.00 |
June | 596.06 | 45.88 | 214.28 | 16.35 | 197.94 | 0.00 | 0.00 |
July | 588.53 | 29.79 | 217.14 | 20.65 | 196.50 | 0.00 | 0.00 |
August | 678.70 | 39.75 | 268.51 | 75.62 | 192.88 | 0.00 | 0.00 |
September | 813.60 | 61.93 | 381.40 | 161.20 | 220.20 | 0.00 | 0.00 |
October | 1038.82 | 223.07 | 612.22 | 423.82 | 188.40 | 0.00 | 0.00 |
November | 1099.17 | 331.79 | 719.63 | 552.71 | 166.92 | 0.00 | 0.00 |
December | 1150.88 | 443.46 | 778.28 | 616.61 | 161.67 | 0.00 | 0.00 |
Annual Sum or Average | 826.95 | 208.29 | 467.74 | 275.23 | 192.51 | 0.00 | 0.00 |
Minimum of Months | 537.01 | 29.79 | 214.28 | 16.35 | 161.67 | 0.00 | 0.00 |
Maximum of Months | 1286.65 | 443.46 | 835.71 | 667.64 | 222.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3576.23 | 1148.56 | 2353.32 | 1880.03 | 473.29 | 0.00 | 0.00 |
February | 2022.75 | 1092.53 | 1468.41 | 984.43 | 483.99 | 0.00 | 0.00 |
March | 1813.93 | 985.64 | 1215.60 | 615.98 | 599.62 | 0.00 | 0.00 |
April | 2014.82 | 542.66 | 1066.89 | 439.48 | 627.41 | 0.00 | 0.00 |
May | 1497.02 | 361.48 | 712.87 | 124.01 | 588.87 | 0.00 | 0.00 |
June | 1681.30 | 130.27 | 603.41 | 46.04 | 557.38 | 0.00 | 0.00 |
July | 1654.43 | 89.18 | 611.46 | 58.14 | 553.32 | 0.00 | 0.00 |
August | 1904.22 | 120.91 | 756.09 | 212.94 | 543.15 | 0.00 | 0.00 |
September | 2276.49 | 187.00 | 1074.00 | 453.93 | 620.07 | 0.00 | 0.00 |
October | 2890.99 | 682.98 | 1723.96 | 1193.45 | 530.51 | 0.00 | 0.00 |
November | 3049.44 | 1030.29 | 2026.44 | 1556.40 | 470.05 | 0.00 | 0.00 |
December | 3191.08 | 1362.92 | 2191.58 | 1736.32 | 455.26 | 0.00 | 0.00 |
Annual Sum or Average | 2300.45 | 642.74 | 1317.12 | 775.03 | 542.09 | 0.00 | 0.00 |
Minimum of Months | 1497.02 | 89.18 | 603.41 | 46.04 | 455.26 | 0.00 | 0.00 |
Maximum of Months | 3576.23 | 1362.92 | 2353.32 | 1880.03 | 627.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4748.49 | 1497.51 | 3057.09 | 2442.27 | 614.83 | 0.00 | 0.00 |
February | 2690.52 | 1463.26 | 1907.55 | 1278.83 | 628.73 | 0.00 | 0.00 |
March | 2412.22 | 1317.42 | 1579.13 | 800.19 | 778.94 | 0.00 | 0.00 |
April | 2696.58 | 710.85 | 1385.95 | 570.91 | 815.04 | 0.00 | 0.00 |
May | 2006.00 | 476.44 | 926.06 | 161.09 | 764.97 | 0.00 | 0.00 |
June | 2259.32 | 169.47 | 783.87 | 59.80 | 724.06 | 0.00 | 0.00 |
July | 2223.33 | 114.58 | 794.32 | 75.52 | 718.79 | 0.00 | 0.00 |
August | 2552.23 | 153.72 | 982.21 | 276.63 | 705.58 | 0.00 | 0.00 |
September | 3040.86 | 236.86 | 1395.19 | 589.68 | 805.51 | 0.00 | 0.00 |
October | 3844.70 | 891.39 | 2239.52 | 1550.35 | 689.17 | 0.00 | 0.00 |
November | 4046.82 | 1352.81 | 2632.46 | 2021.85 | 610.62 | 0.00 | 0.00 |
December | 4236.39 | 1797.28 | 2846.99 | 2255.58 | 591.41 | 0.00 | 0.00 |
Annual Sum or Average | 3066.76 | 845.95 | 1711.02 | 1006.81 | 704.21 | 0.00 | 0.00 |
Minimum of Months | 2006.00 | 114.58 | 783.87 | 59.80 | 591.41 | 0.00 | 0.00 |
Maximum of Months | 4748.49 | 1797.28 | 3057.09 | 2442.27 | 815.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 438.97 | 203.09 | 292.23 | 211.13 | 81.11 | 0.00 | 0.00 |
February | 266.91 | 195.42 | 205.97 | 119.04 | 86.93 | 0.00 | 0.00 |
March | 324.55 | 173.35 | 221.47 | 108.35 | 113.12 | 0.00 | 0.00 |
April | 520.93 | 80.55 | 283.37 | 149.84 | 133.54 | 0.00 | 0.00 |
May | 518.24 | 48.17 | 259.27 | 125.95 | 133.32 | 0.00 | 0.00 |
June | 627.32 | 12.33 | 264.15 | 133.65 | 130.51 | 0.00 | 0.00 |
July | 521.12 | 7.71 | 204.27 | 79.26 | 125.00 | 0.00 | 0.00 |
August | 511.51 | 8.70 | 207.52 | 92.61 | 114.91 | 0.00 | 0.00 |
September | 473.49 | 15.51 | 209.80 | 88.38 | 121.42 | 0.00 | 0.00 |
October | 447.33 | 108.58 | 259.12 | 162.98 | 96.14 | 0.00 | 0.00 |
November | 399.14 | 179.07 | 268.67 | 185.54 | 83.13 | 0.00 | 0.00 |
December | 356.30 | 250.71 | 255.29 | 179.41 | 75.88 | 0.00 | 0.00 |
Annual Sum or Average | 451.39 | 106.59 | 244.44 | 136.45 | 107.99 | 0.00 | 0.00 |
Minimum of Months | 266.91 | 7.71 | 204.27 | 79.26 | 75.88 | 0.00 | 0.00 |
Maximum of Months | 627.32 | 250.71 | 292.23 | 211.13 | 133.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 212.64 | 212.98 | 147.04 | 79.12 | 67.91 | 0.00 | 0.00 |
February | 142.58 | 200.89 | 125.70 | 49.92 | 75.78 | 0.00 | 0.00 |
March | 228.72 | 177.10 | 166.47 | 65.10 | 101.37 | 0.00 | 0.00 |
April | 441.15 | 81.19 | 245.64 | 119.53 | 126.11 | 0.00 | 0.00 |
May | 495.79 | 45.40 | 252.82 | 120.95 | 131.87 | 0.00 | 0.00 |
June | 637.36 | 11.29 | 272.14 | 139.62 | 132.53 | 0.00 | 0.00 |
July | 518.19 | 7.28 | 204.41 | 79.81 | 124.60 | 0.00 | 0.00 |
August | 470.01 | 9.18 | 189.10 | 78.51 | 110.59 | 0.00 | 0.00 |
September | 390.69 | 16.48 | 167.08 | 56.53 | 110.55 | 0.00 | 0.00 |
October | 284.69 | 114.49 | 163.34 | 79.18 | 84.17 | 0.00 | 0.00 |
November | 208.33 | 188.43 | 147.44 | 76.26 | 71.18 | 0.00 | 0.00 |
December | 152.85 | 261.73 | 120.13 | 57.49 | 62.63 | 0.00 | 0.00 |
Annual Sum or Average | 349.50 | 110.19 | 183.65 | 83.62 | 100.03 | 0.00 | 0.00 |
Minimum of Months | 142.58 | 7.28 | 120.13 | 49.92 | 62.63 | 0.00 | 0.00 |
Maximum of Months | 637.36 | 261.73 | 272.14 | 139.62 | 132.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 192.44 | 80.82 | 132.16 | 105.58 | 26.58 | 0.00 | 0.00 |
February | 105.38 | 80.93 | 82.47 | 55.29 | 27.18 | 0.00 | 0.00 |
March | 91.69 | 72.61 | 68.27 | 34.59 | 33.67 | 0.00 | 0.00 |
April | 105.18 | 41.53 | 59.92 | 24.68 | 35.24 | 0.00 | 0.00 |
May | 76.11 | 29.10 | 40.04 | 6.96 | 33.07 | 0.00 | 0.00 |
June | 86.29 | 12.23 | 33.89 | 2.59 | 31.30 | 0.00 | 0.00 |
July | 83.43 | 9.60 | 34.34 | 3.26 | 31.07 | 0.00 | 0.00 |
August | 98.56 | 12.92 | 42.46 | 11.96 | 30.50 | 0.00 | 0.00 |
September | 119.50 | 17.86 | 60.32 | 25.49 | 34.82 | 0.00 | 0.00 |
October | 153.89 | 50.60 | 96.82 | 67.02 | 29.79 | 0.00 | 0.00 |
November | 162.70 | 74.19 | 113.80 | 87.41 | 26.40 | 0.00 | 0.00 |
December | 171.31 | 95.01 | 123.08 | 97.51 | 25.57 | 0.00 | 0.00 |
Annual Sum or Average | 120.69 | 47.98 | 73.97 | 43.53 | 30.44 | 0.00 | 0.00 |
Minimum of Months | 76.11 | 9.60 | 33.89 | 2.59 | 25.57 | 0.00 | 0.00 |
Maximum of Months | 192.44 | 95.01 | 132.16 | 105.58 | 35.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 16.79 | 59.40 | 16.03 | 0.00 | 16.03 | 0.00 | 0.00 |
February | 11.78 | 58.59 | 18.27 | 0.00 | 18.27 | 0.00 | 0.00 |
March | 28.08 | 50.50 | 24.29 | 0.00 | 24.28 | 0.00 | 0.00 |
April | 60.44 | 20.30 | 29.74 | 0.44 | 29.30 | 0.00 | 0.00 |
May | 82.56 | 10.67 | 34.89 | 2.96 | 31.92 | 0.00 | 0.00 |
June | 126.14 | 2.29 | 40.29 | 7.36 | 32.93 | 0.00 | 0.00 |
July | 113.19 | 1.55 | 34.47 | 3.70 | 30.76 | 0.00 | 0.00 |
August | 93.65 | 1.92 | 27.73 | 0.68 | 27.05 | 0.00 | 0.00 |
September | 78.05 | 3.60 | 26.15 | 0.02 | 26.14 | 0.00 | 0.00 |
October | 38.49 | 31.00 | 20.22 | 0.00 | 20.22 | 0.00 | 0.00 |
November | 17.28 | 52.55 | 16.85 | 0.00 | 16.85 | 0.00 | 0.00 |
December | 10.38 | 74.98 | 14.98 | 0.00 | 14.98 | 0.00 | 0.00 |
Annual Sum or Average | 56.62 | 30.50 | 25.35 | 1.27 | 24.08 | 0.00 | 0.00 |
Minimum of Months | 10.38 | 1.55 | 14.98 | 0.00 | 14.98 | 0.00 | 0.00 |
Maximum of Months | 126.14 | 74.98 | 40.29 | 7.36 | 32.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 419.97 | 195.67 | 286.18 | 207.91 | 78.27 | 0.00 | 0.00 |
February | 288.19 | 190.31 | 223.33 | 138.29 | 85.04 | 0.00 | 0.00 |
March | 333.89 | 163.60 | 234.64 | 120.06 | 114.59 | 0.00 | 0.00 |
April | 520.91 | 72.28 | 287.65 | 157.61 | 130.04 | 0.00 | 0.00 |
May | 533.34 | 42.26 | 270.90 | 139.75 | 131.15 | 0.00 | 0.00 |
June | 643.39 | 10.74 | 272.15 | 145.99 | 126.16 | 0.00 | 0.00 |
July | 578.08 | 6.87 | 237.29 | 113.75 | 123.55 | 0.00 | 0.00 |
August | 561.93 | 8.31 | 237.72 | 120.44 | 117.28 | 0.00 | 0.00 |
September | 500.56 | 14.61 | 226.70 | 104.84 | 121.86 | 0.00 | 0.00 |
October | 465.08 | 104.15 | 272.87 | 176.15 | 96.72 | 0.00 | 0.00 |
November | 375.73 | 173.15 | 259.12 | 179.39 | 79.73 | 0.00 | 0.00 |
December | 355.96 | 243.46 | 260.60 | 186.46 | 74.14 | 0.00 | 0.00 |
Annual Sum or Average | 465.71 | 101.77 | 255.97 | 149.33 | 106.63 | 0.00 | 0.00 |
Minimum of Months | 288.19 | 6.87 | 223.33 | 104.84 | 74.14 | 0.00 | 0.00 |
Maximum of Months | 643.39 | 243.46 | 287.65 | 207.91 | 131.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 181.88 | 192.21 | 140.98 | 75.91 | 65.07 | 0.00 | 0.00 |
February | 156.63 | 187.94 | 143.06 | 69.17 | 73.89 | 0.00 | 0.00 |
March | 235.76 | 164.39 | 179.64 | 76.81 | 102.83 | 0.00 | 0.00 |
April | 439.16 | 73.39 | 249.91 | 127.30 | 122.61 | 0.00 | 0.00 |
May | 509.57 | 42.39 | 264.45 | 134.75 | 129.71 | 0.00 | 0.00 |
June | 652.95 | 10.80 | 280.14 | 151.96 | 128.18 | 0.00 | 0.00 |
July | 574.96 | 6.89 | 237.44 | 114.30 | 123.14 | 0.00 | 0.00 |
August | 519.54 | 8.96 | 219.29 | 106.33 | 112.95 | 0.00 | 0.00 |
September | 415.87 | 15.33 | 183.98 | 72.99 | 110.99 | 0.00 | 0.00 |
October | 296.45 | 105.42 | 177.10 | 92.35 | 84.75 | 0.00 | 0.00 |
November | 175.19 | 171.46 | 137.89 | 70.11 | 67.78 | 0.00 | 0.00 |
December | 137.98 | 238.49 | 125.44 | 64.54 | 60.90 | 0.00 | 0.00 |
Annual Sum or Average | 358.96 | 101.13 | 195.17 | 96.50 | 98.67 | 0.00 | 0.00 |
Minimum of Months | 137.98 | 6.89 | 125.44 | 64.54 | 60.90 | 0.00 | 0.00 |
Maximum of Months | 652.95 | 238.49 | 280.14 | 151.96 | 129.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 475.51 | 256.79 | 321.09 | 228.77 | 92.33 | 0.00 | 0.00 |
February | 275.77 | 245.98 | 218.26 | 119.79 | 98.47 | 0.00 | 0.00 |
March | 290.77 | 223.66 | 200.53 | 74.96 | 125.57 | 0.00 | 0.00 |
April | 381.84 | 114.57 | 194.25 | 54.43 | 139.83 | 0.00 | 0.00 |
May | 359.04 | 71.91 | 162.32 | 21.51 | 140.82 | 0.00 | 0.00 |
June | 472.58 | 22.88 | 160.71 | 21.55 | 139.16 | 0.00 | 0.00 |
July | 437.19 | 15.44 | 149.07 | 15.10 | 133.97 | 0.00 | 0.00 |
August | 427.07 | 20.85 | 152.08 | 27.39 | 124.70 | 0.00 | 0.00 |
September | 440.68 | 35.21 | 187.34 | 55.27 | 132.07 | 0.00 | 0.00 |
October | 435.16 | 153.28 | 253.58 | 145.22 | 108.36 | 0.00 | 0.00 |
November | 410.87 | 230.62 | 283.08 | 189.39 | 93.69 | 0.00 | 0.00 |
December | 413.08 | 310.58 | 299.12 | 211.28 | 87.84 | 0.00 | 0.00 |
Annual Sum or Average | 402.39 | 141.41 | 215.19 | 97.05 | 118.14 | 0.00 | 0.00 |
Minimum of Months | 275.77 | 15.44 | 149.07 | 15.10 | 87.84 | 0.00 | 0.00 |
Maximum of Months | 475.51 | 310.58 | 321.09 | 228.77 | 140.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 436.86 | 200.53 | 292.23 | 211.13 | 81.11 | 0.00 | 0.00 |
February | 264.96 | 192.98 | 205.97 | 119.04 | 86.93 | 0.00 | 0.00 |
March | 321.75 | 171.60 | 221.47 | 108.35 | 113.12 | 0.00 | 0.00 |
April | 517.29 | 78.16 | 283.37 | 149.84 | 133.54 | 0.00 | 0.00 |
May | 516.32 | 45.93 | 259.27 | 125.95 | 133.32 | 0.00 | 0.00 |
June | 625.94 | 11.29 | 264.15 | 133.65 | 130.51 | 0.00 | 0.00 |
July | 520.26 | 7.25 | 204.27 | 79.26 | 125.00 | 0.00 | 0.00 |
August | 510.46 | 8.03 | 207.52 | 92.61 | 114.91 | 0.00 | 0.00 |
September | 472.22 | 14.23 | 209.80 | 88.38 | 121.42 | 0.00 | 0.00 |
October | 445.37 | 105.60 | 259.12 | 162.98 | 96.14 | 0.00 | 0.00 |
November | 396.93 | 176.48 | 268.67 | 185.54 | 83.13 | 0.00 | 0.00 |
December | 355.28 | 247.95 | 255.29 | 179.41 | 75.88 | 0.00 | 0.00 |
Annual Sum or Average | 449.55 | 104.66 | 244.44 | 136.45 | 107.99 | 0.00 | 0.00 |
Minimum of Months | 264.96 | 7.25 | 204.27 | 79.26 | 75.88 | 0.00 | 0.00 |
Maximum of Months | 625.94 | 247.95 | 292.23 | 211.13 | 133.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 212.70 | 208.57 | 147.04 | 79.12 | 67.91 | 0.00 | 0.00 |
February | 141.83 | 197.37 | 125.70 | 49.92 | 75.78 | 0.00 | 0.00 |
March | 226.91 | 175.32 | 166.47 | 65.10 | 101.37 | 0.00 | 0.00 |
April | 438.47 | 78.98 | 245.64 | 119.53 | 126.11 | 0.00 | 0.00 |
May | 494.52 | 43.26 | 252.82 | 120.95 | 131.87 | 0.00 | 0.00 |
June | 635.98 | 10.42 | 272.14 | 139.62 | 132.53 | 0.00 | 0.00 |
July | 517.37 | 6.86 | 204.41 | 79.81 | 124.60 | 0.00 | 0.00 |
August | 469.32 | 8.53 | 189.10 | 78.51 | 110.59 | 0.00 | 0.00 |
September | 390.35 | 15.08 | 167.08 | 56.53 | 110.55 | 0.00 | 0.00 |
October | 284.57 | 110.62 | 163.34 | 79.18 | 84.17 | 0.00 | 0.00 |
November | 208.17 | 184.34 | 147.44 | 76.26 | 71.18 | 0.00 | 0.00 |
December | 153.40 | 257.04 | 120.13 | 57.49 | 62.63 | 0.00 | 0.00 |
Annual Sum or Average | 348.72 | 107.69 | 183.65 | 83.62 | 100.03 | 0.00 | 0.00 |
Minimum of Months | 141.83 | 6.86 | 120.13 | 49.92 | 62.63 | 0.00 | 0.00 |
Maximum of Months | 635.98 | 257.04 | 272.14 | 139.62 | 132.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 373.26 | 103.86 | 242.33 | 193.60 | 48.74 | 0.00 | 0.00 |
February | 210.36 | 101.03 | 151.21 | 101.37 | 49.84 | 0.00 | 0.00 |
March | 190.01 | 89.15 | 125.18 | 63.43 | 61.75 | 0.00 | 0.00 |
April | 221.58 | 38.79 | 109.86 | 45.26 | 64.61 | 0.00 | 0.00 |
May | 175.47 | 22.00 | 73.41 | 12.77 | 60.64 | 0.00 | 0.00 |
June | 207.54 | 4.83 | 62.14 | 4.74 | 57.40 | 0.00 | 0.00 |
July | 205.12 | 3.29 | 62.97 | 5.99 | 56.98 | 0.00 | 0.00 |
August | 226.15 | 3.68 | 77.86 | 21.93 | 55.93 | 0.00 | 0.00 |
September | 258.03 | 6.74 | 110.60 | 46.74 | 63.85 | 0.00 | 0.00 |
October | 308.13 | 53.74 | 177.53 | 122.90 | 54.63 | 0.00 | 0.00 |
November | 318.84 | 91.22 | 208.67 | 160.27 | 48.40 | 0.00 | 0.00 |
December | 333.09 | 129.42 | 225.68 | 178.80 | 46.88 | 0.00 | 0.00 |
Annual Sum or Average | 252.65 | 53.80 | 135.63 | 79.81 | 55.82 | 0.00 | 0.00 |
Minimum of Months | 175.47 | 3.29 | 62.14 | 4.74 | 46.88 | 0.00 | 0.00 |
Maximum of Months | 373.26 | 129.42 | 242.33 | 193.60 | 64.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 102.53 | 646.66 | 140.27 | 0.00 | 140.27 | 0.00 | 0.00 |
February | 66.84 | 653.59 | 159.84 | 0.00 | 159.84 | 0.00 | 0.00 |
March | 191.03 | 555.18 | 212.46 | 0.01 | 212.45 | 0.00 | 0.00 |
April | 450.88 | 258.39 | 260.20 | 3.83 | 256.37 | 0.00 | 0.00 |
May | 628.03 | 155.82 | 305.21 | 25.92 | 279.29 | 0.00 | 0.00 |
June | 978.82 | 51.99 | 352.47 | 64.40 | 288.07 | 0.00 | 0.00 |
July | 847.53 | 37.16 | 301.52 | 32.40 | 269.12 | 0.00 | 0.00 |
August | 691.29 | 51.60 | 242.62 | 5.96 | 236.66 | 0.00 | 0.00 |
September | 575.02 | 84.78 | 228.79 | 0.14 | 228.65 | 0.00 | 0.00 |
October | 271.82 | 365.05 | 176.90 | 0.00 | 176.90 | 0.00 | 0.00 |
November | 107.12 | 584.70 | 147.39 | 0.00 | 147.39 | 0.00 | 0.00 |
December | 56.33 | 793.96 | 131.03 | 0.00 | 131.03 | 0.00 | 0.00 |
Annual Sum or Average | 415.54 | 351.96 | 221.78 | 11.08 | 210.70 | 0.00 | 0.00 |
Minimum of Months | 56.33 | 37.16 | 131.03 | 0.00 | 131.03 | 0.00 | 0.00 |
Maximum of Months | 978.82 | 793.96 | 352.47 | 64.40 | 288.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 93.55 | 665.50 | 140.27 | 0.00 | 140.27 | 0.00 | 0.00 |
February | 59.15 | 677.47 | 159.84 | 0.00 | 159.84 | 0.00 | 0.00 |
March | 179.36 | 572.09 | 212.46 | 0.01 | 212.45 | 0.00 | 0.00 |
April | 441.30 | 266.18 | 260.20 | 3.83 | 256.37 | 0.00 | 0.00 |
May | 618.39 | 160.84 | 305.21 | 25.92 | 279.29 | 0.00 | 0.00 |
June | 968.38 | 54.34 | 352.47 | 64.40 | 288.07 | 0.00 | 0.00 |
July | 836.95 | 39.37 | 301.52 | 32.40 | 269.12 | 0.00 | 0.00 |
August | 681.51 | 54.89 | 242.62 | 5.96 | 236.66 | 0.00 | 0.00 |
September | 565.98 | 89.41 | 228.79 | 0.14 | 228.65 | 0.00 | 0.00 |
October | 262.99 | 376.37 | 176.90 | 0.00 | 176.90 | 0.00 | 0.00 |
November | 98.52 | 602.90 | 147.39 | 0.00 | 147.39 | 0.00 | 0.00 |
December | 49.39 | 818.10 | 131.03 | 0.00 | 131.03 | 0.00 | 0.00 |
Annual Sum or Average | 406.21 | 363.44 | 221.78 | 11.08 | 210.70 | 0.00 | 0.00 |
Minimum of Months | 49.39 | 39.37 | 131.03 | 0.00 | 131.03 | 0.00 | 0.00 |
Maximum of Months | 968.38 | 818.10 | 352.47 | 64.40 | 288.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 634.53 | 449.07 | 427.15 | 283.81 | 143.33 | 0.00 | 0.00 |
February | 462.02 | 453.91 | 366.37 | 207.46 | 158.92 | 0.00 | 0.00 |
March | 602.46 | 399.08 | 414.26 | 196.85 | 217.41 | 0.00 | 0.00 |
April | 1031.20 | 202.82 | 537.54 | 284.90 | 252.64 | 0.00 | 0.00 |
May | 1119.69 | 140.02 | 535.32 | 274.48 | 260.84 | 0.00 | 0.00 |
June | 1360.69 | 56.41 | 552.26 | 297.92 | 254.33 | 0.00 | 0.00 |
July | 1199.29 | 41.47 | 474.70 | 228.03 | 246.68 | 0.00 | 0.00 |
August | 1138.36 | 53.05 | 456.98 | 226.75 | 230.22 | 0.00 | 0.00 |
September | 978.24 | 77.60 | 410.66 | 177.82 | 232.84 | 0.00 | 0.00 |
October | 815.53 | 265.37 | 449.95 | 268.49 | 181.46 | 0.00 | 0.00 |
November | 581.83 | 406.64 | 396.99 | 249.50 | 147.50 | 0.00 | 0.00 |
December | 516.75 | 540.86 | 386.03 | 250.99 | 135.03 | 0.00 | 0.00 |
Annual Sum or Average | 872.11 | 256.36 | 451.12 | 245.82 | 205.30 | 0.00 | 0.00 |
Minimum of Months | 462.02 | 41.47 | 366.37 | 177.82 | 135.03 | 0.00 | 0.00 |
Maximum of Months | 1360.69 | 540.86 | 552.26 | 297.92 | 260.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 990.58 | 453.67 | 664.96 | 492.81 | 172.15 | 0.00 | 0.00 |
February | 564.61 | 441.67 | 439.71 | 258.05 | 181.66 | 0.00 | 0.00 |
March | 563.30 | 401.73 | 391.48 | 161.47 | 230.01 | 0.00 | 0.00 |
April | 704.78 | 209.85 | 368.86 | 116.51 | 252.35 | 0.00 | 0.00 |
May | 627.24 | 133.38 | 291.49 | 41.39 | 250.10 | 0.00 | 0.00 |
June | 805.81 | 43.55 | 279.00 | 34.15 | 244.86 | 0.00 | 0.00 |
July | 749.84 | 30.43 | 263.64 | 26.35 | 237.30 | 0.00 | 0.00 |
August | 759.71 | 41.37 | 281.37 | 57.86 | 223.51 | 0.00 | 0.00 |
September | 813.75 | 67.47 | 359.96 | 119.04 | 240.92 | 0.00 | 0.00 |
October | 868.88 | 267.72 | 512.54 | 312.84 | 199.71 | 0.00 | 0.00 |
November | 850.99 | 406.37 | 581.72 | 407.98 | 173.74 | 0.00 | 0.00 |
December | 868.91 | 551.12 | 619.39 | 455.14 | 164.25 | 0.00 | 0.00 |
Annual Sum or Average | 765.34 | 253.28 | 421.29 | 206.96 | 214.33 | 0.00 | 0.00 |
Minimum of Months | 563.30 | 30.43 | 263.64 | 26.35 | 164.25 | 0.00 | 0.00 |
Maximum of Months | 990.58 | 551.12 | 664.96 | 492.81 | 252.35 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.344615E+10 | 0.998473E+09 | 0.223838E+10 | 0.178821E+10 | 0.450171E+09 | 0.00 | 0.00 |
February | 0.177955E+10 | 0.833035E+09 | 0.126153E+10 | 0.845731E+09 | 0.415798E+09 | 0.00 | 0.00 |
March | 0.177511E+10 | 0.836636E+09 | 0.115623E+10 | 0.585894E+09 | 0.570335E+09 | 0.00 | 0.00 |
April | 0.187759E+10 | 0.465311E+09 | 0.982044E+09 | 0.404532E+09 | 0.577512E+09 | 0.00 | 0.00 |
May | 0.143832E+10 | 0.324184E+09 | 0.678057E+09 | 0.117952E+09 | 0.560105E+09 | 0.00 | 0.00 |
June | 0.154499E+10 | 0.118922E+09 | 0.555427E+09 | 42376069.35 | 0.513050E+09 | 0.00 | 0.00 |
July | 0.157633E+10 | 79792522.46 | 0.581591E+09 | 55297824.35 | 0.526293E+09 | 0.00 | 0.00 |
August | 0.181783E+10 | 0.106469E+09 | 0.719166E+09 | 0.202544E+09 | 0.516622E+09 | 0.00 | 0.00 |
September | 0.210885E+10 | 0.160522E+09 | 0.988595E+09 | 0.417832E+09 | 0.570763E+09 | 0.00 | 0.00 |
October | 0.278237E+10 | 0.597458E+09 | 0.163976E+10 | 0.113516E+10 | 0.504604E+09 | 0.00 | 0.00 |
November | 0.284904E+10 | 0.860010E+09 | 0.186529E+10 | 0.143263E+10 | 0.432667E+09 | 0.00 | 0.00 |
December | 0.308252E+10 | 0.118777E+10 | 0.208454E+10 | 0.165152E+10 | 0.433026E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.260786E+11 | 0.656858E+10 | 0.147506E+11 | 0.867966E+10 | 0.607095E+10 | 0.00 | 0.00 |
Minimum of Months | 0.143832E+10 | 79792522.46 | 0.555427E+09 | 42376069.35 | 0.415798E+09 | 0.00 | 0.00 |
Maximum of Months | 0.344615E+10 | 0.118777E+10 | 0.223838E+10 | 0.178821E+10 | 0.577512E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.957856E+10 | 0.307630E+10 | 0.630312E+10 | 0.503547E+10 | 0.126765E+10 | 0.00 | 0.00 |
February | 0.489343E+10 | 0.264305E+10 | 0.355238E+10 | 0.238152E+10 | 0.117086E+10 | 0.00 | 0.00 |
March | 0.485843E+10 | 0.263994E+10 | 0.325586E+10 | 0.164984E+10 | 0.160603E+10 | 0.00 | 0.00 |
April | 0.522241E+10 | 0.140659E+10 | 0.276537E+10 | 0.113914E+10 | 0.162624E+10 | 0.00 | 0.00 |
May | 0.400961E+10 | 0.968175E+09 | 0.190936E+10 | 0.332145E+09 | 0.157722E+10 | 0.00 | 0.00 |
June | 0.435793E+10 | 0.337671E+09 | 0.156404E+10 | 0.119328E+09 | 0.144472E+10 | 0.00 | 0.00 |
July | 0.443123E+10 | 0.238849E+09 | 0.163772E+10 | 0.155715E+09 | 0.148201E+10 | 0.00 | 0.00 |
August | 0.510027E+10 | 0.323834E+09 | 0.202512E+10 | 0.570351E+09 | 0.145477E+10 | 0.00 | 0.00 |
September | 0.590065E+10 | 0.484691E+09 | 0.278382E+10 | 0.117659E+10 | 0.160723E+10 | 0.00 | 0.00 |
October | 0.774322E+10 | 0.182929E+10 | 0.461746E+10 | 0.319653E+10 | 0.142093E+10 | 0.00 | 0.00 |
November | 0.790414E+10 | 0.267051E+10 | 0.525254E+10 | 0.403418E+10 | 0.121836E+10 | 0.00 | 0.00 |
December | 0.854699E+10 | 0.365044E+10 | 0.586993E+10 | 0.465056E+10 | 0.121937E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.725469E+11 | 0.202693E+11 | 0.415367E+11 | 0.244414E+11 | 0.170954E+11 | 0.00 | 0.00 |
Minimum of Months | 0.400961E+10 | 0.238849E+09 | 0.156404E+10 | 0.119328E+09 | 0.117086E+10 | 0.00 | 0.00 |
Maximum of Months | 0.957856E+10 | 0.365044E+10 | 0.630312E+10 | 0.503547E+10 | 0.162624E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.127184E+11 | 0.401093E+10 | 0.818812E+10 | 0.654136E+10 | 0.164675E+10 | 0.00 | 0.00 |
February | 0.650890E+10 | 0.353992E+10 | 0.461475E+10 | 0.309374E+10 | 0.152101E+10 | 0.00 | 0.00 |
March | 0.646088E+10 | 0.352858E+10 | 0.422955E+10 | 0.214323E+10 | 0.208632E+10 | 0.00 | 0.00 |
April | 0.698953E+10 | 0.184253E+10 | 0.359238E+10 | 0.147980E+10 | 0.211257E+10 | 0.00 | 0.00 |
May | 0.537288E+10 | 0.127611E+10 | 0.248037E+10 | 0.431476E+09 | 0.204890E+10 | 0.00 | 0.00 |
June | 0.585616E+10 | 0.439275E+09 | 0.203178E+10 | 0.155014E+09 | 0.187677E+10 | 0.00 | 0.00 |
July | 0.595496E+10 | 0.306900E+09 | 0.212749E+10 | 0.202283E+09 | 0.192521E+10 | 0.00 | 0.00 |
August | 0.683589E+10 | 0.411725E+09 | 0.263075E+10 | 0.740919E+09 | 0.188983E+10 | 0.00 | 0.00 |
September | 0.788192E+10 | 0.613953E+09 | 0.361634E+10 | 0.152845E+10 | 0.208788E+10 | 0.00 | 0.00 |
October | 0.102976E+11 | 0.238749E+10 | 0.599834E+10 | 0.415247E+10 | 0.184587E+10 | 0.00 | 0.00 |
November | 0.104893E+11 | 0.350648E+10 | 0.682335E+10 | 0.524063E+10 | 0.158272E+10 | 0.00 | 0.00 |
December | 0.113468E+11 | 0.481384E+10 | 0.762538E+10 | 0.604134E+10 | 0.158404E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.967132E+11 | 0.266777E+11 | 0.539586E+11 | 0.317507E+11 | 0.222079E+11 | 0.00 | 0.00 |
Minimum of Months | 0.537288E+10 | 0.306900E+09 | 0.203178E+10 | 0.155014E+09 | 0.152101E+10 | 0.00 | 0.00 |
Maximum of Months | 0.127184E+11 | 0.481384E+10 | 0.818812E+10 | 0.654136E+10 | 0.211257E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.117574E+10 | 0.543957E+09 | 0.782721E+09 | 0.565485E+09 | 0.217236E+09 | 0.00 | 0.00 |
February | 0.645720E+09 | 0.472756E+09 | 0.498285E+09 | 0.287991E+09 | 0.210294E+09 | 0.00 | 0.00 |
March | 0.869269E+09 | 0.464296E+09 | 0.593196E+09 | 0.290214E+09 | 0.302982E+09 | 0.00 | 0.00 |
April | 0.135024E+10 | 0.208775E+09 | 0.734505E+09 | 0.388376E+09 | 0.346129E+09 | 0.00 | 0.00 |
May | 0.138805E+10 | 0.129024E+09 | 0.694431E+09 | 0.337345E+09 | 0.357087E+09 | 0.00 | 0.00 |
June | 0.162601E+10 | 31966378.67 | 0.684686E+09 | 0.346412E+09 | 0.338274E+09 | 0.00 | 0.00 |
July | 0.139577E+10 | 20655235.49 | 0.547106E+09 | 0.212292E+09 | 0.334813E+09 | 0.00 | 0.00 |
August | 0.137004E+10 | 23311634.47 | 0.555835E+09 | 0.248047E+09 | 0.307788E+09 | 0.00 | 0.00 |
September | 0.122728E+10 | 40201487.18 | 0.543814E+09 | 0.229081E+09 | 0.314733E+09 | 0.00 | 0.00 |
October | 0.119812E+10 | 0.290808E+09 | 0.694021E+09 | 0.436513E+09 | 0.257508E+09 | 0.00 | 0.00 |
November | 0.103458E+10 | 0.464154E+09 | 0.696397E+09 | 0.480919E+09 | 0.215478E+09 | 0.00 | 0.00 |
December | 0.954320E+09 | 0.671506E+09 | 0.683759E+09 | 0.480526E+09 | 0.203233E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.142351E+11 | 0.336141E+10 | 0.770875E+10 | 0.430320E+10 | 0.340555E+10 | 0.00 | 0.00 |
Minimum of Months | 0.645720E+09 | 20655235.49 | 0.498285E+09 | 0.212292E+09 | 0.203233E+09 | 0.00 | 0.00 |
Maximum of Months | 0.162601E+10 | 0.671506E+09 | 0.782721E+09 | 0.565485E+09 | 0.357087E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.569548E+09 | 0.570450E+09 | 0.393828E+09 | 0.211926E+09 | 0.181903E+09 | 0.00 | 0.00 |
February | 0.344923E+09 | 0.486001E+09 | 0.304099E+09 | 0.120775E+09 | 0.183324E+09 | 0.00 | 0.00 |
March | 0.612593E+09 | 0.474358E+09 | 0.445884E+09 | 0.174376E+09 | 0.271508E+09 | 0.00 | 0.00 |
April | 0.114347E+10 | 0.210456E+09 | 0.636687E+09 | 0.309812E+09 | 0.326875E+09 | 0.00 | 0.00 |
May | 0.132793E+10 | 0.121610E+09 | 0.677152E+09 | 0.323940E+09 | 0.353213E+09 | 0.00 | 0.00 |
June | 0.165204E+10 | 29271833.55 | 0.705388E+09 | 0.361882E+09 | 0.343505E+09 | 0.00 | 0.00 |
July | 0.138792E+10 | 19495420.10 | 0.547489E+09 | 0.213756E+09 | 0.333733E+09 | 0.00 | 0.00 |
August | 0.125889E+10 | 24595735.77 | 0.506479E+09 | 0.210280E+09 | 0.296199E+09 | 0.00 | 0.00 |
September | 0.101266E+10 | 42724492.66 | 0.433071E+09 | 0.146521E+09 | 0.286550E+09 | 0.00 | 0.00 |
October | 0.762524E+09 | 0.306650E+09 | 0.437501E+09 | 0.212073E+09 | 0.225428E+09 | 0.00 | 0.00 |
November | 0.539988E+09 | 0.488407E+09 | 0.382175E+09 | 0.197665E+09 | 0.184511E+09 | 0.00 | 0.00 |
December | 0.409384E+09 | 0.701024E+09 | 0.321745E+09 | 0.153993E+09 | 0.167752E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110219E+11 | 0.347504E+10 | 0.579150E+10 | 0.263700E+10 | 0.315450E+10 | 0.00 | 0.00 |
Minimum of Months | 0.344923E+09 | 19495420.10 | 0.304099E+09 | 0.120775E+09 | 0.167752E+09 | 0.00 | 0.00 |
Maximum of Months | 0.165204E+10 | 0.701024E+09 | 0.705388E+09 | 0.361882E+09 | 0.353213E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.515427E+09 | 0.216473E+09 | 0.353983E+09 | 0.282791E+09 | 71191720.82 | 0.00 | 0.00 |
February | 0.254931E+09 | 0.195788E+09 | 0.199502E+09 | 0.133746E+09 | 65755807.07 | 0.00 | 0.00 |
March | 0.245587E+09 | 0.194482E+09 | 0.182850E+09 | 92654621.17 | 90194909.73 | 0.00 | 0.00 |
April | 0.272617E+09 | 0.107637E+09 | 0.155304E+09 | 63973596.40 | 91330373.15 | 0.00 | 0.00 |
May | 0.203861E+09 | 77940440.26 | 0.107231E+09 | 18653222.29 | 88577606.46 | 0.00 | 0.00 |
June | 0.223671E+09 | 31694479.29 | 87837819.98 | 6701448.63 | 81136371.35 | 0.00 | 0.00 |
July | 0.223455E+09 | 25718572.16 | 91975290.32 | 8744924.55 | 83230365.76 | 0.00 | 0.00 |
August | 0.263983E+09 | 34614846.93 | 0.113732E+09 | 32030806.41 | 81700800.92 | 0.00 | 0.00 |
September | 0.309741E+09 | 46291136.88 | 0.156339E+09 | 66076882.86 | 90262586.66 | 0.00 | 0.00 |
October | 0.412189E+09 | 0.135520E+09 | 0.259316E+09 | 0.179516E+09 | 79800009.62 | 0.00 | 0.00 |
November | 0.421723E+09 | 0.192298E+09 | 0.294982E+09 | 0.226559E+09 | 68423598.87 | 0.00 | 0.00 |
December | 0.458834E+09 | 0.254488E+09 | 0.329655E+09 | 0.261175E+09 | 68480327.14 | 0.00 | 0.00 |
Annual Sum or Average | 0.380602E+10 | 0.151294E+10 | 0.233271E+10 | 0.137262E+10 | 0.960084E+09 | 0.00 | 0.00 |
Minimum of Months | 0.203861E+09 | 25718572.16 | 87837819.98 | 6701448.63 | 65755807.07 | 0.00 | 0.00 |
Maximum of Months | 0.515427E+09 | 0.254488E+09 | 0.353983E+09 | 0.282791E+09 | 91330373.15 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 44969283.45 | 0.159105E+09 | 42944949.46 | 0.00 | 42944949.46 | 0.00 | 0.00 |
February | 28505234.56 | 0.141751E+09 | 44199004.85 | 0.00 | 44199004.85 | 0.00 | 0.00 |
March | 75209227.30 | 0.135265E+09 | 65045237.58 | 2573.27 | 65042664.31 | 0.00 | 0.00 |
April | 0.156673E+09 | 52622517.15 | 77090857.89 | 1135053.46 | 75955804.43 | 0.00 | 0.00 |
May | 0.221138E+09 | 28578151.11 | 93441433.49 | 7934259.35 | 85507174.14 | 0.00 | 0.00 |
June | 0.326954E+09 | 5932446.51 | 0.104430E+09 | 19081199.32 | 85349110.47 | 0.00 | 0.00 |
July | 0.303174E+09 | 4151725.71 | 92312481.83 | 9919050.97 | 82393430.86 | 0.00 | 0.00 |
August | 0.250834E+09 | 5135567.25 | 74279179.59 | 1823766.12 | 72455413.47 | 0.00 | 0.00 |
September | 0.202303E+09 | 9337060.59 | 67785290.05 | 41951.47 | 67743338.59 | 0.00 | 0.00 |
October | 0.103089E+09 | 83022949.90 | 54159300.98 | 0.00 | 54159300.98 | 0.00 | 0.00 |
November | 44793566.67 | 0.136219E+09 | 43668987.75 | 0.00 | 43668987.75 | 0.00 | 0.00 |
December | 27791154.22 | 0.200822E+09 | 40114513.77 | 0.00 | 40114513.77 | 0.00 | 0.00 |
Annual Sum or Average | 0.178543E+10 | 0.961943E+09 | 0.799472E+09 | 39937853.95 | 0.759534E+09 | 0.00 | 0.00 |
Minimum of Months | 27791154.22 | 4151725.71 | 40114513.77 | 0.00 | 40114513.77 | 0.00 | 0.00 |
Maximum of Months | 0.326954E+09 | 0.200822E+09 | 0.104430E+09 | 19081199.32 | 85507174.14 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112484E+10 | 0.524079E+09 | 0.766505E+09 | 0.556878E+09 | 0.209627E+09 | 0.00 | 0.00 |
February | 0.697192E+09 | 0.460402E+09 | 0.540277E+09 | 0.334558E+09 | 0.205719E+09 | 0.00 | 0.00 |
March | 0.894294E+09 | 0.438188E+09 | 0.628463E+09 | 0.321558E+09 | 0.306905E+09 | 0.00 | 0.00 |
April | 0.135019E+10 | 0.187357E+09 | 0.745596E+09 | 0.408534E+09 | 0.337062E+09 | 0.00 | 0.00 |
May | 0.142850E+10 | 0.113176E+09 | 0.725583E+09 | 0.374306E+09 | 0.351277E+09 | 0.00 | 0.00 |
June | 0.166768E+10 | 27842868.77 | 0.705417E+09 | 0.378400E+09 | 0.327016E+09 | 0.00 | 0.00 |
July | 0.154833E+10 | 18410556.48 | 0.635569E+09 | 0.304666E+09 | 0.330904E+09 | 0.00 | 0.00 |
August | 0.150507E+10 | 22260150.69 | 0.636696E+09 | 0.322574E+09 | 0.314123E+09 | 0.00 | 0.00 |
September | 0.129745E+10 | 37866460.45 | 0.587611E+09 | 0.271747E+09 | 0.315864E+09 | 0.00 | 0.00 |
October | 0.124567E+10 | 0.278946E+09 | 0.730860E+09 | 0.471799E+09 | 0.259061E+09 | 0.00 | 0.00 |
November | 0.973891E+09 | 0.448806E+09 | 0.671635E+09 | 0.464986E+09 | 0.206650E+09 | 0.00 | 0.00 |
December | 0.953391E+09 | 0.652071E+09 | 0.697993E+09 | 0.499406E+09 | 0.198587E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.146865E+11 | 0.320941E+10 | 0.807221E+10 | 0.470941E+10 | 0.336279E+10 | 0.00 | 0.00 |
Minimum of Months | 0.697192E+09 | 18410556.48 | 0.540277E+09 | 0.271747E+09 | 0.198587E+09 | 0.00 | 0.00 |
Maximum of Months | 0.166768E+10 | 0.652071E+09 | 0.766505E+09 | 0.556878E+09 | 0.351277E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.487148E+09 | 0.514817E+09 | 0.377613E+09 | 0.203319E+09 | 0.174294E+09 | 0.00 | 0.00 |
February | 0.378912E+09 | 0.454653E+09 | 0.346092E+09 | 0.167343E+09 | 0.178749E+09 | 0.00 | 0.00 |
March | 0.631451E+09 | 0.440300E+09 | 0.481151E+09 | 0.205720E+09 | 0.275431E+09 | 0.00 | 0.00 |
April | 0.113830E+10 | 0.190217E+09 | 0.647778E+09 | 0.329970E+09 | 0.317808E+09 | 0.00 | 0.00 |
May | 0.136484E+10 | 0.113547E+09 | 0.708304E+09 | 0.360901E+09 | 0.347403E+09 | 0.00 | 0.00 |
June | 0.169244E+10 | 27992835.43 | 0.726118E+09 | 0.393870E+09 | 0.332248E+09 | 0.00 | 0.00 |
July | 0.153997E+10 | 18462762.21 | 0.635953E+09 | 0.306130E+09 | 0.329823E+09 | 0.00 | 0.00 |
August | 0.139153E+10 | 24005927.81 | 0.587340E+09 | 0.284806E+09 | 0.302534E+09 | 0.00 | 0.00 |
September | 0.107793E+10 | 39724144.68 | 0.476868E+09 | 0.189187E+09 | 0.287681E+09 | 0.00 | 0.00 |
October | 0.794021E+09 | 0.282353E+09 | 0.474341E+09 | 0.247359E+09 | 0.226982E+09 | 0.00 | 0.00 |
November | 0.454083E+09 | 0.444419E+09 | 0.357413E+09 | 0.181731E+09 | 0.175682E+09 | 0.00 | 0.00 |
December | 0.369568E+09 | 0.638777E+09 | 0.335979E+09 | 0.172873E+09 | 0.163106E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.113202E+11 | 0.318927E+10 | 0.615495E+10 | 0.304321E+10 | 0.311174E+10 | 0.00 | 0.00 |
Minimum of Months | 0.369568E+09 | 18462762.21 | 0.335979E+09 | 0.167343E+09 | 0.163106E+09 | 0.00 | 0.00 |
Maximum of Months | 0.169244E+10 | 0.638777E+09 | 0.726118E+09 | 0.393870E+09 | 0.347403E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.127361E+10 | 0.687790E+09 | 0.860015E+09 | 0.612730E+09 | 0.247286E+09 | 0.00 | 0.00 |
February | 0.667146E+09 | 0.595072E+09 | 0.528015E+09 | 0.289790E+09 | 0.238224E+09 | 0.00 | 0.00 |
March | 0.778795E+09 | 0.599054E+09 | 0.537094E+09 | 0.200762E+09 | 0.336332E+09 | 0.00 | 0.00 |
April | 0.989734E+09 | 0.296960E+09 | 0.503505E+09 | 0.141072E+09 | 0.362433E+09 | 0.00 | 0.00 |
May | 0.961651E+09 | 0.192594E+09 | 0.434765E+09 | 57604611.69 | 0.377160E+09 | 0.00 | 0.00 |
June | 0.122493E+10 | 59295807.78 | 0.416551E+09 | 55856451.63 | 0.360695E+09 | 0.00 | 0.00 |
July | 0.117097E+10 | 41345615.89 | 0.399265E+09 | 40435810.09 | 0.358829E+09 | 0.00 | 0.00 |
August | 0.114387E+10 | 55840361.70 | 0.407338E+09 | 73352738.99 | 0.333986E+09 | 0.00 | 0.00 |
September | 0.114225E+10 | 91256314.32 | 0.485590E+09 | 0.143261E+09 | 0.342329E+09 | 0.00 | 0.00 |
October | 0.116554E+10 | 0.410546E+09 | 0.679193E+09 | 0.388962E+09 | 0.290232E+09 | 0.00 | 0.00 |
November | 0.106498E+10 | 0.597777E+09 | 0.733746E+09 | 0.490890E+09 | 0.242857E+09 | 0.00 | 0.00 |
December | 0.110639E+10 | 0.831866E+09 | 0.801172E+09 | 0.565893E+09 | 0.235279E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.126899E+11 | 0.445940E+10 | 0.678625E+10 | 0.306061E+10 | 0.372564E+10 | 0.00 | 0.00 |
Minimum of Months | 0.667146E+09 | 41345615.89 | 0.399265E+09 | 40435810.09 | 0.235279E+09 | 0.00 | 0.00 |
Maximum of Months | 0.127361E+10 | 0.831866E+09 | 0.860015E+09 | 0.612730E+09 | 0.377160E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.117009E+10 | 0.537088E+09 | 0.782721E+09 | 0.565485E+09 | 0.217236E+09 | 0.00 | 0.00 |
February | 0.640996E+09 | 0.466862E+09 | 0.498285E+09 | 0.287991E+09 | 0.210294E+09 | 0.00 | 0.00 |
March | 0.861773E+09 | 0.459610E+09 | 0.593196E+09 | 0.290214E+09 | 0.302982E+09 | 0.00 | 0.00 |
April | 0.134081E+10 | 0.202592E+09 | 0.734505E+09 | 0.388376E+09 | 0.346129E+09 | 0.00 | 0.00 |
May | 0.138292E+10 | 0.123011E+09 | 0.694431E+09 | 0.337345E+09 | 0.357087E+09 | 0.00 | 0.00 |
June | 0.162243E+10 | 29269275.41 | 0.684686E+09 | 0.346412E+09 | 0.338274E+09 | 0.00 | 0.00 |
July | 0.139347E+10 | 19423595.23 | 0.547106E+09 | 0.212292E+09 | 0.334813E+09 | 0.00 | 0.00 |
August | 0.136722E+10 | 21517376.02 | 0.555835E+09 | 0.248047E+09 | 0.307788E+09 | 0.00 | 0.00 |
September | 0.122399E+10 | 36893692.40 | 0.543814E+09 | 0.229081E+09 | 0.314733E+09 | 0.00 | 0.00 |
October | 0.119288E+10 | 0.282826E+09 | 0.694021E+09 | 0.436513E+09 | 0.257508E+09 | 0.00 | 0.00 |
November | 0.102884E+10 | 0.457424E+09 | 0.696397E+09 | 0.480919E+09 | 0.215478E+09 | 0.00 | 0.00 |
December | 0.951578E+09 | 0.664113E+09 | 0.683759E+09 | 0.480526E+09 | 0.203233E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.141770E+11 | 0.330063E+10 | 0.770875E+10 | 0.430320E+10 | 0.340555E+10 | 0.00 | 0.00 |
Minimum of Months | 0.640996E+09 | 19423595.23 | 0.498285E+09 | 0.212292E+09 | 0.203233E+09 | 0.00 | 0.00 |
Maximum of Months | 0.162243E+10 | 0.664113E+09 | 0.782721E+09 | 0.565485E+09 | 0.357087E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.569694E+09 | 0.558644E+09 | 0.393828E+09 | 0.211926E+09 | 0.181903E+09 | 0.00 | 0.00 |
February | 0.343120E+09 | 0.477487E+09 | 0.304099E+09 | 0.120775E+09 | 0.183324E+09 | 0.00 | 0.00 |
March | 0.607761E+09 | 0.469586E+09 | 0.445884E+09 | 0.174376E+09 | 0.271508E+09 | 0.00 | 0.00 |
April | 0.113651E+10 | 0.204705E+09 | 0.636687E+09 | 0.309812E+09 | 0.326875E+09 | 0.00 | 0.00 |
May | 0.132453E+10 | 0.115855E+09 | 0.677152E+09 | 0.323940E+09 | 0.353213E+09 | 0.00 | 0.00 |
June | 0.164845E+10 | 27017860.61 | 0.705388E+09 | 0.361882E+09 | 0.343505E+09 | 0.00 | 0.00 |
July | 0.138572E+10 | 18385255.04 | 0.547489E+09 | 0.213756E+09 | 0.333733E+09 | 0.00 | 0.00 |
August | 0.125702E+10 | 22852889.94 | 0.506479E+09 | 0.210280E+09 | 0.296199E+09 | 0.00 | 0.00 |
September | 0.101180E+10 | 39093983.89 | 0.433071E+09 | 0.146521E+09 | 0.286550E+09 | 0.00 | 0.00 |
October | 0.762181E+09 | 0.296273E+09 | 0.437501E+09 | 0.212073E+09 | 0.225428E+09 | 0.00 | 0.00 |
November | 0.539570E+09 | 0.477809E+09 | 0.382175E+09 | 0.197665E+09 | 0.184511E+09 | 0.00 | 0.00 |
December | 0.410875E+09 | 0.688445E+09 | 0.321745E+09 | 0.153993E+09 | 0.167752E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.109972E+11 | 0.339615E+10 | 0.579150E+10 | 0.263700E+10 | 0.315450E+10 | 0.00 | 0.00 |
Minimum of Months | 0.343120E+09 | 18385255.04 | 0.304099E+09 | 0.120775E+09 | 0.167752E+09 | 0.00 | 0.00 |
Maximum of Months | 0.164845E+10 | 0.688445E+09 | 0.705388E+09 | 0.361882E+09 | 0.353213E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.999741E+09 | 0.278183E+09 | 0.649066E+09 | 0.518528E+09 | 0.130538E+09 | 0.00 | 0.00 |
February | 0.508914E+09 | 0.244404E+09 | 0.365808E+09 | 0.245238E+09 | 0.120570E+09 | 0.00 | 0.00 |
March | 0.508935E+09 | 0.238779E+09 | 0.335275E+09 | 0.169892E+09 | 0.165382E+09 | 0.00 | 0.00 |
April | 0.574325E+09 | 0.100553E+09 | 0.284767E+09 | 0.117303E+09 | 0.167464E+09 | 0.00 | 0.00 |
May | 0.469984E+09 | 58937734.31 | 0.196619E+09 | 34202726.45 | 0.162417E+09 | 0.00 | 0.00 |
June | 0.537932E+09 | 12518009.60 | 0.161060E+09 | 12287840.18 | 0.148772E+09 | 0.00 | 0.00 |
July | 0.549401E+09 | 8815810.18 | 0.168647E+09 | 16034777.14 | 0.152612E+09 | 0.00 | 0.00 |
August | 0.605727E+09 | 9847902.11 | 0.208539E+09 | 58731992.40 | 0.149807E+09 | 0.00 | 0.00 |
September | 0.668822E+09 | 17477789.56 | 0.286666E+09 | 0.121159E+09 | 0.165506E+09 | 0.00 | 0.00 |
October | 0.825307E+09 | 0.143943E+09 | 0.475485E+09 | 0.329163E+09 | 0.146322E+09 | 0.00 | 0.00 |
November | 0.826441E+09 | 0.236441E+09 | 0.540882E+09 | 0.415420E+09 | 0.125462E+09 | 0.00 | 0.00 |
December | 0.892158E+09 | 0.346644E+09 | 0.604458E+09 | 0.478892E+09 | 0.125566E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.796769E+10 | 0.169654E+10 | 0.427727E+10 | 0.251685E+10 | 0.176042E+10 | 0.00 | 0.00 |
Minimum of Months | 0.469984E+09 | 8815810.18 | 0.161060E+09 | 12287840.18 | 0.120570E+09 | 0.00 | 0.00 |
Maximum of Months | 0.999741E+09 | 0.346644E+09 | 0.649066E+09 | 0.518528E+09 | 0.167464E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.274615E+09 | 0.173201E+10 | 0.375704E+09 | 0.00 | 0.375704E+09 | 0.00 | 0.00 |
February | 0.161711E+09 | 0.158116E+10 | 0.386675E+09 | 0.00 | 0.386675E+09 | 0.00 | 0.00 |
March | 0.511658E+09 | 0.148698E+10 | 0.569049E+09 | 22512.27 | 0.569026E+09 | 0.00 | 0.00 |
April | 0.116867E+10 | 0.669740E+09 | 0.674430E+09 | 9930025.34 | 0.664500E+09 | 0.00 | 0.00 |
May | 0.168212E+10 | 0.417349E+09 | 0.817473E+09 | 69412938.91 | 0.748060E+09 | 0.00 | 0.00 |
June | 0.253710E+10 | 0.134757E+09 | 0.913609E+09 | 0.166932E+09 | 0.746677E+09 | 0.00 | 0.00 |
July | 0.227002E+10 | 99533346.31 | 0.807597E+09 | 86776906.14 | 0.720820E+09 | 0.00 | 0.00 |
August | 0.185156E+10 | 0.138196E+09 | 0.649832E+09 | 15955234.21 | 0.633877E+09 | 0.00 | 0.00 |
September | 0.149046E+10 | 0.219743E+09 | 0.593020E+09 | 367012.78 | 0.592653E+09 | 0.00 | 0.00 |
October | 0.728050E+09 | 0.977737E+09 | 0.473813E+09 | 0.00 | 0.473813E+09 | 0.00 | 0.00 |
November | 0.277655E+09 | 0.151554E+10 | 0.382039E+09 | 0.00 | 0.382039E+09 | 0.00 | 0.00 |
December | 0.150861E+09 | 0.212655E+10 | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.131045E+11 | 0.110993E+11 | 0.699418E+10 | 0.349397E+09 | 0.664479E+10 | 0.00 | 0.00 |
Minimum of Months | 0.150861E+09 | 99533346.31 | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.00 | 0.00 |
Maximum of Months | 0.253710E+10 | 0.212655E+10 | 0.913609E+09 | 0.166932E+09 | 0.748060E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.250570E+09 | 0.178247E+10 | 0.375704E+09 | 0.00 | 0.375704E+09 | 0.00 | 0.00 |
February | 0.143100E+09 | 0.163894E+10 | 0.386675E+09 | 0.00 | 0.386675E+09 | 0.00 | 0.00 |
March | 0.480399E+09 | 0.153228E+10 | 0.569049E+09 | 22512.27 | 0.569026E+09 | 0.00 | 0.00 |
April | 0.114386E+10 | 0.689936E+09 | 0.674430E+09 | 9930025.34 | 0.664500E+09 | 0.00 | 0.00 |
May | 0.165629E+10 | 0.430795E+09 | 0.817473E+09 | 69412938.91 | 0.748060E+09 | 0.00 | 0.00 |
June | 0.251004E+10 | 0.140860E+09 | 0.913609E+09 | 0.166932E+09 | 0.746677E+09 | 0.00 | 0.00 |
July | 0.224168E+10 | 0.105448E+09 | 0.807597E+09 | 86776906.14 | 0.720820E+09 | 0.00 | 0.00 |
August | 0.182535E+10 | 0.147004E+09 | 0.649832E+09 | 15955234.21 | 0.633877E+09 | 0.00 | 0.00 |
September | 0.146702E+10 | 0.231752E+09 | 0.593020E+09 | 367012.78 | 0.592653E+09 | 0.00 | 0.00 |
October | 0.704404E+09 | 0.100806E+10 | 0.473813E+09 | 0.00 | 0.473813E+09 | 0.00 | 0.00 |
November | 0.255353E+09 | 0.156271E+10 | 0.382039E+09 | 0.00 | 0.382039E+09 | 0.00 | 0.00 |
December | 0.132286E+09 | 0.219119E+10 | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.128104E+11 | 0.114614E+11 | 0.699418E+10 | 0.349397E+09 | 0.664479E+10 | 0.00 | 0.00 |
Minimum of Months | 0.132286E+09 | 0.105448E+09 | 0.350942E+09 | 0.00 | 0.350942E+09 | 0.00 | 0.00 |
Maximum of Months | 0.251004E+10 | 0.219119E+10 | 0.913609E+09 | 0.166932E+09 | 0.748060E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.169952E+10 | 0.120278E+10 | 0.114407E+10 | 0.760168E+09 | 0.383905E+09 | 0.00 | 0.00 |
February | 0.111771E+10 | 0.109811E+10 | 0.886328E+09 | 0.501877E+09 | 0.384451E+09 | 0.00 | 0.00 |
March | 0.161362E+10 | 0.106888E+10 | 0.110956E+10 | 0.527249E+09 | 0.582308E+09 | 0.00 | 0.00 |
April | 0.267286E+10 | 0.525716E+09 | 0.139330E+10 | 0.738458E+09 | 0.654838E+09 | 0.00 | 0.00 |
May | 0.299897E+10 | 0.375037E+09 | 0.143380E+10 | 0.735158E+09 | 0.698645E+09 | 0.00 | 0.00 |
June | 0.352690E+10 | 0.146205E+09 | 0.143145E+10 | 0.772218E+09 | 0.659232E+09 | 0.00 | 0.00 |
July | 0.321218E+10 | 0.111076E+09 | 0.127145E+10 | 0.610754E+09 | 0.660695E+09 | 0.00 | 0.00 |
August | 0.304898E+10 | 0.142096E+09 | 0.122397E+10 | 0.607340E+09 | 0.616627E+09 | 0.00 | 0.00 |
September | 0.253560E+10 | 0.201142E+09 | 0.106442E+10 | 0.460908E+09 | 0.603516E+09 | 0.00 | 0.00 |
October | 0.218433E+10 | 0.710764E+09 | 0.120514E+10 | 0.719123E+09 | 0.486021E+09 | 0.00 | 0.00 |
November | 0.150810E+10 | 0.105400E+10 | 0.102901E+10 | 0.646691E+09 | 0.382315E+09 | 0.00 | 0.00 |
December | 0.138407E+10 | 0.144865E+10 | 0.103393E+10 | 0.672254E+09 | 0.361677E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.275028E+11 | 0.808447E+10 | 0.142264E+11 | 0.775220E+10 | 0.647423E+10 | 0.00 | 0.00 |
Minimum of Months | 0.111771E+10 | 0.111076E+09 | 0.886328E+09 | 0.460908E+09 | 0.361677E+09 | 0.00 | 0.00 |
Maximum of Months | 0.352690E+10 | 0.144865E+10 | 0.143380E+10 | 0.772218E+09 | 0.698645E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.265317E+10 | 0.121510E+10 | 0.178102E+10 | 0.131994E+10 | 0.461083E+09 | 0.00 | 0.00 |
February | 0.136591E+10 | 0.106849E+10 | 0.106374E+10 | 0.624266E+09 | 0.439472E+09 | 0.00 | 0.00 |
March | 0.150875E+10 | 0.107601E+10 | 0.104853E+10 | 0.432478E+09 | 0.616053E+09 | 0.00 | 0.00 |
April | 0.182678E+10 | 0.543927E+09 | 0.956085E+09 | 0.302004E+09 | 0.654081E+09 | 0.00 | 0.00 |
May | 0.167999E+10 | 0.357246E+09 | 0.780737E+09 | 0.110860E+09 | 0.669877E+09 | 0.00 | 0.00 |
June | 0.208867E+10 | 0.112893E+09 | 0.723175E+09 | 88503980.79 | 0.634671E+09 | 0.00 | 0.00 |
July | 0.200836E+10 | 81504069.35 | 0.706145E+09 | 70564670.40 | 0.635580E+09 | 0.00 | 0.00 |
August | 0.203480E+10 | 0.110798E+09 | 0.753612E+09 | 0.154975E+09 | 0.598637E+09 | 0.00 | 0.00 |
September | 0.210923E+10 | 0.174886E+09 | 0.933011E+09 | 0.308543E+09 | 0.624468E+09 | 0.00 | 0.00 |
October | 0.232720E+10 | 0.717060E+09 | 0.137280E+10 | 0.837901E+09 | 0.534895E+09 | 0.00 | 0.00 |
November | 0.220576E+10 | 0.105332E+10 | 0.150781E+10 | 0.105747E+10 | 0.450334E+09 | 0.00 | 0.00 |
December | 0.232729E+10 | 0.147611E+10 | 0.165898E+10 | 0.121905E+10 | 0.439939E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.241359E+11 | 0.798734E+10 | 0.132856E+11 | 0.652656E+10 | 0.675909E+10 | 0.00 | 0.00 |
Minimum of Months | 0.136591E+10 | 81504069.35 | 0.706145E+09 | 70564670.40 | 0.439472E+09 | 0.00 | 0.00 |
Maximum of Months | 0.265317E+10 | 0.147611E+10 | 0.178102E+10 | 0.131994E+10 | 0.669877E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770478E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161987629.2 | 81.21 | 0.00 | 0.00 |
February | 0.696230E+10 | -0.681597E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146321798.8 | 81.21 | 0.00 | 0.00 |
March | 0.770338E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161921234.8 | 81.21 | 0.00 | 0.00 |
April | 0.746496E+10 | -0.730858E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156382444.0 | 81.21 | 0.00 | 0.00 |
May | 0.770430E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161509746.8 | 81.21 | 0.00 | 0.00 |
June | 0.745674E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156217636.7 | 81.21 | 0.00 | 0.00 |
July | 0.771227E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161424234.7 | 81.21 | 0.00 | 0.00 |
August | 0.770424E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161435283.3 | 81.21 | 0.00 | 0.00 |
September | 0.746618E+10 | -0.730993E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156246270.3 | 81.21 | 0.00 | 0.00 |
October | 0.770313E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161693552.3 | 81.21 | 0.00 | 0.00 |
November | 0.744914E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156710094.1 | 81.21 | 0.00 | 0.00 |
December | 0.771300E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162140399.1 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907444E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190399E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696230E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162140399.1 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771300E+10 | -0.681597E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146321798.8 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYSLAUNDRY HPWH TANK
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.382773E+11 | -0.104633E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -775173231.5 | 81.67 | 0.00 | 0.00 |
February | 0.334173E+11 | -0.938768E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -714761227.6 | 81.68 | 0.00 | 0.00 |
March | 0.330274E+11 | -0.100666E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -770119075.9 | 81.67 | 0.00 | 0.00 |
April | 0.219693E+11 | -0.924524E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -686430617.7 | 81.68 | 0.00 | 0.00 |
May | 0.152680E+11 | -0.899623E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -686890165.5 | 81.67 | 0.00 | 0.00 |
June | 0.621109E+10 | -0.827034E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -627528271.4 | 81.68 | 0.00 | 0.00 |
July | 0.208187E+10 | -0.832655E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -654731490.1 | 81.68 | 0.00 | 0.00 |
August | 0.286586E+10 | -0.839337E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -659691541.9 | 81.68 | 0.00 | 0.00 |
September | 0.692823E+10 | -0.844744E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -654031456.3 | 81.67 | 0.00 | 0.00 |
October | 0.203719E+11 | -0.924481E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -728036071.1 | 81.68 | 0.00 | 0.00 |
November | 0.293439E+11 | -0.948505E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -745358706.1 | 81.67 | 0.00 | 0.00 |
December | 0.405699E+11 | -0.102466E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -797549778.7 | 81.67 | 0.00 | 0.00 |
Annual Sum or Average | 0.250332E+12 | -0.110573E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.850030E+10 | 81.68 | 0.00 | 0.00 |
Minimum of Months | 0.208187E+10 | -0.104633E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -797549778.7 | 81.67 | 0.00 | 0.00 |
Maximum of Months | 0.405699E+11 | -0.827034E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -627528271.4 | 81.68 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 HPWH TANK
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | -0.230704E+10 | -0.603625E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.119291E+10 | 59.36 | 0.00 | 0.00 |
February | -0.206131E+10 | -0.539864E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.111283E+10 | 59.37 | 0.00 | 0.00 |
March | -0.214362E+10 | -0.569923E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.118204E+10 | 59.40 | 0.00 | 0.00 |
April | -0.202927E+10 | -0.508397E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.100333E+10 | 59.43 | 0.00 | 0.00 |
May | -0.171256E+10 | -0.477275E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -984788288.7 | 59.48 | 0.00 | 0.00 |
June | -0.146481E+10 | -0.424280E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -864693561.9 | 59.51 | 0.00 | 0.00 |
July | -0.139935E+10 | -0.418751E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -909120989.6 | 59.53 | 0.00 | 0.00 |
August | -0.144585E+10 | -0.425041E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -920923976.3 | 59.53 | 0.00 | 0.00 |
September | -0.160212E+10 | -0.439386E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -927844080.2 | 59.50 | 0.00 | 0.00 |
October | -0.185524E+10 | -0.498465E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.108275E+10 | 59.46 | 0.00 | 0.00 |
November | -0.195891E+10 | -0.528857E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.114485E+10 | 59.42 | 0.00 | 0.00 |
December | -0.207638E+10 | -0.584832E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.124729E+10 | 59.38 | 0.00 | 0.00 |
Annual Sum or Average | -0.220565E+11 | -0.601870E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.125734E+11 | 59.45 | 0.00 | 0.00 |
Minimum of Months | -0.230704E+10 | -0.603625E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.124729E+10 | 59.36 | 0.00 | 0.00 |
Maximum of Months | -0.139935E+10 | -0.418751E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -864693561.9 | 59.53 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.87 | 0.86 | 01-JAN-07:49 | 7548.65 | 38.83 | 306.67 | 291.83 | 1049.88 | 27.72 | 175.83 | 285.67 |
February | 241.00 | 0.87 | 0.86 | 01-FEB-07:49 | 4376.20 | 32.33 | 187.33 | 264.83 | 538.29 | 23.04 | 122.00 | 199.33 |
March | 344.33 | 0.87 | 0.86 | 01-MAR-07:49 | 1012.94 | 19.32 | 11.50 | 321.50 | 384.40 | 20.69 | 124.00 | 245.67 |
April | 380.33 | 0.88 | 0.86 | 01-APR-08:39 | 701.83 | 18.92 | 0.00 | 329.83 | 305.99 | 20.68 | 122.67 | 245.33 |
May | 403.17 | 0.87 | 0.86 | 01-MAY-07:00 | 566.05 | 18.71 | 0.00 | 352.67 | 250.58 | 20.50 | 53.50 | 182.83 |
June | 418.17 | 0.88 | 0.86 | 01-JUN-08:09 | 458.03 | 18.07 | 0.00 | 354.67 | 208.58 | 19.90 | 8.83 | 81.00 |
July | 399.50 | 0.88 | 0.86 | 01-JUL-09:09 | 564.08 | 18.14 | 0.00 | 356.00 | 240.66 | 19.94 | 40.33 | 154.17 |
August | 361.83 | 0.88 | 0.86 | 01-AUG-08:50 | 629.07 | 18.52 | 0.00 | 333.00 | 267.69 | 20.29 | 62.83 | 173.17 |
September | 350.17 | 0.87 | 0.86 | 01-SEP-07:19 | 927.38 | 18.84 | 0.00 | 317.83 | 371.98 | 20.61 | 128.50 | 253.50 |
October | 348.00 | 0.87 | 0.86 | 01-OCT-07:49 | 2543.93 | 25.40 | 135.17 | 318.67 | 414.12 | 21.33 | 111.83 | 263.17 |
November | 288.50 | 0.87 | 0.86 | 01-NOV-07:49 | 7196.60 | 37.59 | 282.50 | 286.00 | 822.19 | 26.25 | 149.50 | 261.50 |
December | 290.67 | 0.86 | 0.86 | 01-DEC-07:40 | 6943.82 | 38.65 | 287.33 | 280.17 | 1201.32 | 28.46 | 172.67 | 271.17 |
Annual Sum or Average | 4135.50 | 0.87 | 2463.19 | 24.24 | 1210.50 | 3807.00 | 470.50 | 22.13 | 1272.50 | 2616.50 | ||
Minimum of Months | 241.00 | 0.86 | 0.86 | 458.03 | 18.07 | 0.00 | 264.83 | 208.58 | 19.90 | 8.83 | 81.00 | |
Maximum of Months | 418.17 | 0.88 | 0.86 | 7548.65 | 38.83 | 306.67 | 356.00 | 1201.32 | 28.46 | 175.83 | 285.67 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.25 | 0.22 | 01-JAN-07:49 | 7971.05 | 38.88 | 306.67 | 294.50 | 1469.74 | 27.24 | 157.17 | 291.50 |
February | 241.00 | 0.26 | 0.22 | 01-FEB-07:49 | 4690.33 | 32.30 | 187.33 | 271.67 | 852.00 | 22.97 | 122.17 | 241.33 |
March | 344.33 | 0.27 | 0.22 | 01-MAR-07:30 | 1228.41 | 19.82 | 15.00 | 336.17 | 600.44 | 21.02 | 161.17 | 300.83 |
April | 380.33 | 0.28 | 0.22 | 01-APR-07:19 | 879.80 | 19.53 | 6.50 | 341.33 | 483.58 | 21.07 | 181.50 | 315.67 |
May | 403.17 | 0.26 | 0.22 | 01-MAY-06:00 | 692.89 | 19.54 | 0.00 | 373.33 | 377.09 | 21.09 | 159.00 | 333.17 |
June | 418.17 | 0.27 | 0.22 | 01-JUN-06:49 | 563.05 | 18.98 | 0.00 | 378.17 | 313.32 | 20.58 | 59.67 | 332.17 |
July | 399.50 | 0.27 | 0.22 | 01-JUL-07:19 | 675.12 | 19.06 | 0.00 | 380.50 | 351.37 | 20.61 | 123.50 | 319.50 |
August | 361.83 | 0.27 | 0.22 | 01-AUG-07:30 | 769.63 | 19.31 | 0.17 | 352.17 | 407.88 | 20.85 | 123.00 | 305.50 |
September | 350.17 | 0.27 | 0.22 | 01-SEP-06:00 | 1118.13 | 19.48 | 10.00 | 330.33 | 562.20 | 21.03 | 172.67 | 299.33 |
October | 348.00 | 0.26 | 0.22 | 01-OCT-07:19 | 2836.22 | 25.50 | 135.17 | 325.00 | 705.54 | 21.33 | 121.50 | 305.17 |
November | 288.50 | 0.24 | 0.22 | 01-NOV-07:30 | 7574.02 | 37.66 | 282.67 | 290.83 | 1200.00 | 25.90 | 140.83 | 274.83 |
December | 290.67 | 0.24 | 0.22 | 01-DEC-07:30 | 7361.07 | 38.71 | 287.67 | 284.50 | 1616.80 | 28.02 | 162.67 | 277.33 |
Annual Sum or Average | 4135.50 | 0.26 | 2689.86 | 24.74 | 1231.17 | 3958.50 | 696.63 | 22.37 | 1684.83 | 3596.33 | ||
Minimum of Months | 241.00 | 0.24 | 0.22 | 563.05 | 18.98 | 0.00 | 271.67 | 313.32 | 20.58 | 59.67 | 241.33 | |
Maximum of Months | 418.17 | 0.28 | 0.22 | 7971.05 | 38.88 | 306.67 | 380.50 | 1616.80 | 28.02 | 181.50 | 333.17 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.70 | 0.60 | 01-JAN-10:39 | 242.49 | 13.26 | 0.00 | 196.50 | 134.54 | 16.92 | 0.00 | 15.67 |
February | 241.00 | 0.68 | 0.60 | 02-FEB-14:39 | 315.97 | 14.16 | 0.00 | 210.00 | 158.01 | 17.58 | 0.00 | 59.00 |
March | 344.33 | 0.66 | 0.60 | 01-MAR-08:09 | 372.30 | 15.40 | 0.00 | 302.83 | 179.12 | 18.67 | 0.00 | 134.83 |
April | 380.33 | 0.63 | 0.60 | 01-APR-09:09 | 417.91 | 16.43 | 0.00 | 339.00 | 213.58 | 19.70 | 11.17 | 215.00 |
May | 403.17 | 0.61 | 0.60 | 01-MAY-06:10 | 522.00 | 18.09 | 23.33 | 391.83 | 272.37 | 21.68 | 75.50 | 324.17 |
June | 418.17 | 0.61 | 0.60 | 01-JUN-05:49 | 556.90 | 19.39 | 60.67 | 401.50 | 304.18 | 23.23 | 119.33 | 310.67 |
July | 399.50 | 0.62 | 0.60 | 01-JUL-05:49 | 541.48 | 18.86 | 47.83 | 399.17 | 280.91 | 22.69 | 101.83 | 295.83 |
August | 361.83 | 0.63 | 0.60 | 01-AUG-06:19 | 434.93 | 16.38 | 0.00 | 354.67 | 213.67 | 19.94 | 16.17 | 181.83 |
September | 350.17 | 0.64 | 0.60 | 01-SEP-06:00 | 431.51 | 15.92 | 0.00 | 321.50 | 204.29 | 19.13 | 0.00 | 186.17 |
October | 348.00 | 0.69 | 0.60 | 01-OCT-07:49 | 286.69 | 14.27 | 0.00 | 224.83 | 148.91 | 17.74 | 0.00 | 60.67 |
November | 288.50 | 0.69 | 0.60 | 01-NOV-08:39 | 271.55 | 13.83 | 0.00 | 210.17 | 142.47 | 17.43 | 0.00 | 29.50 |
December | 290.67 | 0.70 | 0.60 | 01-DEC-12:20 | 251.40 | 13.39 | 0.00 | 191.00 | 135.46 | 17.08 | 0.00 | 13.33 |
Annual Sum or Average | 4135.50 | 0.65 | 400.85 | 16.05 | 131.83 | 3543.00 | 206.28 | 19.59 | 324.00 | 1826.67 | ||
Minimum of Months | 241.00 | 0.61 | 0.60 | 242.49 | 13.26 | 0.00 | 191.00 | 134.54 | 16.92 | 0.00 | 13.33 | |
Maximum of Months | 418.17 | 0.70 | 0.60 | 556.90 | 19.39 | 60.67 | 401.50 | 304.18 | 23.23 | 119.33 | 324.17 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.70 | 0.60 | 01-JAN-10:39 | 242.49 | 13.26 | 0.00 | 196.50 | 134.54 | 16.92 | 0.00 | 15.67 |
February | 241.00 | 0.68 | 0.60 | 02-FEB-14:39 | 315.97 | 14.16 | 0.00 | 210.00 | 158.01 | 17.58 | 0.00 | 59.00 |
March | 344.33 | 0.66 | 0.60 | 01-MAR-08:09 | 372.30 | 15.40 | 0.00 | 302.83 | 179.12 | 18.67 | 0.00 | 134.83 |
April | 380.33 | 0.63 | 0.60 | 01-APR-09:09 | 417.91 | 16.43 | 0.00 | 339.00 | 213.58 | 19.70 | 11.17 | 215.00 |
May | 403.17 | 0.61 | 0.60 | 01-MAY-06:10 | 522.00 | 18.09 | 23.33 | 391.83 | 272.37 | 21.68 | 75.50 | 324.17 |
June | 418.17 | 0.61 | 0.60 | 01-JUN-05:49 | 556.90 | 19.39 | 60.67 | 401.50 | 304.18 | 23.23 | 119.33 | 310.67 |
July | 399.50 | 0.62 | 0.60 | 01-JUL-05:49 | 541.48 | 18.86 | 47.83 | 399.17 | 280.91 | 22.69 | 101.83 | 295.83 |
August | 361.83 | 0.63 | 0.60 | 01-AUG-06:19 | 434.93 | 16.38 | 0.00 | 354.67 | 213.67 | 19.94 | 16.17 | 181.83 |
September | 350.17 | 0.64 | 0.60 | 01-SEP-06:00 | 431.51 | 15.92 | 0.00 | 321.50 | 204.29 | 19.13 | 0.00 | 186.17 |
October | 348.00 | 0.69 | 0.60 | 01-OCT-07:49 | 286.69 | 14.27 | 0.00 | 224.83 | 148.91 | 17.74 | 0.00 | 60.67 |
November | 288.50 | 0.69 | 0.60 | 01-NOV-08:39 | 271.55 | 13.83 | 0.00 | 210.17 | 142.47 | 17.43 | 0.00 | 29.50 |
December | 290.67 | 0.70 | 0.60 | 01-DEC-12:20 | 251.40 | 13.39 | 0.00 | 191.00 | 135.46 | 17.08 | 0.00 | 13.33 |
Annual Sum or Average | 4135.50 | 0.65 | 400.85 | 16.05 | 131.83 | 3543.00 | 206.28 | 19.59 | 324.00 | 1826.67 | ||
Minimum of Months | 241.00 | 0.61 | 0.60 | 242.49 | 13.26 | 0.00 | 191.00 | 134.54 | 16.92 | 0.00 | 13.33 | |
Maximum of Months | 418.17 | 0.70 | 0.60 | 556.90 | 19.39 | 60.67 | 401.50 | 304.18 | 23.23 | 119.33 | 324.17 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.470862E+11 | 132540.70 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.515978E+11 | 118582.95 | 02-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.348975E+11 | 121688.82 | 25-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.176759E+10 | 75279.70 | 21-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18787969.24 | 9187.62 | 01-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119255E+11 | 113531.24 | 25-OCT-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.322999E+11 | 119591.84 | 04-NOV-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.625171E+11 | 119223.25 | 16-DEC-23:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242110E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.625171E+11 | 132540.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.121547E+09 | 1161.77 | 01-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.518533E+09 | 1192.14 | 13-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.371022E+09 | 1421.58 | 27-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2543979.26 | 246.82 | 21-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40691634.05 | 691.54 | 25-OCT-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113292E+09 | 867.25 | 23-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.467570E+09 | 1486.64 | 16-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.518533E+09 | 1486.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2001.00 | 3.34 | 12-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2001.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2001.00 | 3.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 59319165.52 | 696.37 | 01-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100254E+09 | 452.79 | 13-FEB-11:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 71925324.66 | 662.14 | 27-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9597857.86 | 331.38 | 24-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.269802E+09 | 792.19 | 07-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.510899E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.269802E+09 | 792.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 39782279.59 | 459.32 | 01-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 89635843.52 | 273.05 | 12-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 58828038.59 | 386.01 | 27-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8681590.65 | 203.17 | 24-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197283E+09 | 494.22 | 07-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.394211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.197283E+09 | 494.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 13245836.98 | 1057.66 | 02-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24255521.32 | 1003.08 | 13-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15061398.31 | 1019.39 | 27-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1349165.22 | 333.71 | 23-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10432699.96 | 927.11 | 24-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 52413087.53 | 1160.43 | 07-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116758E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 52413087.53 | 1160.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 49607490.91 | 1962.28 | 12-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8931317.78 | 1653.30 | 27-MAR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 170876.58 | 284.79 | 13-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1174336.58 | 535.66 | 12-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 59884021.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 49607490.91 | 1962.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 68279192.49 | 2827.75 | 02-JAN-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.246537E+09 | 3214.22 | 12-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4470882.70 | 1104.61 | 27-MAR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.356957E+09 | 3667.07 | 18-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.676244E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.356957E+09 | 3667.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.152044E+09 | 2574.70 | 01-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.361126E+09 | 1795.19 | 13-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.215803E+09 | 2253.21 | 27-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2396164.65 | 532.78 | 26-OCT-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 58283703.58 | 1708.25 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.814344E+09 | 3068.62 | 07-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.814344E+09 | 3068.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 7757.08 | 0.27 | 08-JAN-02:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4447.77 | 0.27 | 25-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11148.34 | 0.27 | 15-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20059.15 | 0.27 | 17-APR-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20155.90 | 0.27 | 06-MAY-08:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13501.22 | 0.27 | 08-JUN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14404.88 | 0.27 | 21-JUL-22:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10694.92 | 0.27 | 15-AUG-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9250.09 | 0.27 | 27-SEP-01:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13116.32 | 0.27 | 01-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12677.87 | 0.27 | 03-NOV-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1143834.25 | 111.49 | 07-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1281047.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4447.77 | 0.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1143834.25 | 111.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.412392E+09 | 8248.53 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.821395E+09 | 8452.26 | 12-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.542210E+09 | 8523.38 | 26-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7512776.68 | 4302.18 | 07-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5913841.81 | 3202.89 | 02-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 743171.09 | 1815.60 | 13-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2254866.43 | 3425.05 | 27-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3472805.98 | 3738.36 | 07-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5036730.89 | 3783.03 | 26-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 91757679.10 | 4907.34 | 29-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.305938E+09 | 4553.11 | 25-NOV-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122670E+10 | 8644.84 | 06-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 743171.09 | 1815.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.122670E+10 | 8644.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.872715E+09 | 8772.41 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125814E+10 | 8544.11 | 09-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.688677E+09 | 8557.59 | 26-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7848510.48 | 5398.07 | 05-APR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3493644.53 | 4012.67 | 19-MAY-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 724714.54 | 4997.26 | 13-JUN-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1174682.37 | 2366.53 | 18-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2554765.22 | 3465.72 | 24-AUG-08:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2502225.90 | 3895.28 | 16-SEP-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154199E+09 | 7073.69 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.600248E+09 | 8667.73 | 23-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.216850E+10 | 8795.13 | 06-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.576077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 724714.54 | 2366.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.216850E+10 | 8795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.173501E+10 | 35774.81 | 26-JAN-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153755E+10 | 45927.54 | 05-FEB-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.902097E+09 | 43700.79 | 12-MAR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 94573985.22 | 33718.01 | 01-APR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44031620.68 | 29812.33 | 02-MAY-08:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7148784.18 | 14061.79 | 27-JUN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11808256.74 | 14338.53 | 27-JUL-08:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22928617.10 | 22939.80 | 22-AUG-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19389619.55 | 19091.83 | 23-SEP-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162760E+09 | 37020.28 | 12-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107479E+10 | 36616.13 | 25-NOV-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.564258E+10 | 49492.66 | 06-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112547E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 7148784.18 | 14061.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.564258E+10 | 49492.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.473810E+09 | 4183.00 | 20-JAN-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.772723E+09 | 8049.26 | 12-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.510305E+09 | 4236.71 | 07-MAR-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3017686.85 | 2992.33 | 29-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 519778.82 | 3528.94 | 26-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9715.20 | 97.15 | 16-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 202876.85 | 1712.57 | 05-AUG-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 193334.01 | 1118.68 | 03-SEP-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 85812891.83 | 4028.04 | 27-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.359916E+09 | 4257.72 | 08-NOV-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121867E+10 | 5124.00 | 11-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.121867E+10 | 8049.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.926023E+09 | 8228.86 | 01-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111214E+10 | 8231.71 | 12-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.637109E+09 | 4660.59 | 08-MAR-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5172345.02 | 3401.42 | 27-APR-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 270091.72 | 3292.31 | 25-MAY-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 509.88 | 5.10 | 16-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 50488.59 | 563.04 | 05-AUG-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 803318.40 | 2056.34 | 20-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138959E+09 | 4236.73 | 22-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.659324E+09 | 6521.45 | 23-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.204811E+10 | 8280.74 | 07-DEC-17:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.552796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.204811E+10 | 8280.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.218315E+09 | 2591.05 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.350215E+09 | 2530.01 | 12-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.236674E+09 | 2560.05 | 26-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5883990.05 | 1182.38 | 18-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1723866.44 | 1519.68 | 09-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 290221.46 | 960.53 | 14-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 594836.60 | 862.03 | 27-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 915192.94 | 897.94 | 07-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1541844.62 | 912.38 | 14-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 63318323.64 | 2398.98 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170783E+09 | 2514.84 | 24-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.506548E+09 | 2599.33 | 06-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 290221.46 | 862.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.506548E+09 | 2599.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.393981E+09 | 2618.43 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.499760E+09 | 2557.70 | 09-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.283939E+09 | 2568.08 | 26-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4799969.67 | 1469.68 | 24-APR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1112344.26 | 1604.76 | 14-MAY-08:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 293019.98 | 954.56 | 13-JUN-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 418300.70 | 1018.60 | 02-JUL-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 624555.80 | 788.36 | 30-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1152502.24 | 1016.10 | 25-SEP-08:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 92039054.43 | 2537.91 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.286143E+09 | 2605.27 | 23-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.822012E+09 | 2611.22 | 16-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 293019.98 | 788.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.822012E+09 | 2618.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.157883E+09 | 3466.04 | 01-JAN-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.519397E+09 | 6969.60 | 07-FEB-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.491779E+09 | 11824.81 | 27-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14221834.12 | 4879.14 | 19-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11185341.99 | 4882.12 | 16-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4235309.87 | 4753.58 | 13-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6059957.19 | 4572.10 | 03-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6373650.94 | 4992.52 | 17-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4111427.96 | 4449.79 | 29-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 57734465.49 | 4794.44 | 12-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165882E+09 | 3927.59 | 04-NOV-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.662584E+09 | 5795.86 | 15-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4111427.96 | 3466.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.662584E+09 | 11824.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.479448E+11 | 0.479448E+11 | 50005.68 | 23-JAN-08:50 | 50005.68 | 0.00 |
February | 0.00 | 0.00 | 0.429777E+11 | 0.412571E+11 | 50632.36 | 01-FEB-06:15 | 48537.44 | 0.00 |
March | 0.00 | 0.00 | 0.451658E+11 | 0.451658E+11 | 51140.41 | 01-MAR-06:15 | 51140.41 | 0.00 |
April | 0.00 | 0.00 | 0.408598E+11 | 0.408598E+11 | 55691.74 | 01-APR-05:17 | 55691.74 | 0.00 |
May | 0.00 | 0.00 | 0.380775E+11 | 0.380775E+11 | 56749.03 | 01-MAY-06:15 | 56749.03 | 0.00 |
June | 0.00 | 0.00 | 0.341349E+11 | 0.341349E+11 | 60458.41 | 01-JUN-05:10 | 60458.41 | 0.00 |
July | 0.00 | 0.00 | 0.338582E+11 | 0.338582E+11 | 62130.92 | 01-JUL-05:08 | 62130.92 | 0.00 |
August | 0.00 | 0.00 | 0.344209E+11 | 0.344209E+11 | 62274.97 | 31-AUG-05:10 | 62274.97 | 0.00 |
September | 0.00 | 0.00 | 0.357718E+11 | 0.357718E+11 | 62074.83 | 30-SEP-05:08 | 62074.83 | 0.00 |
October | 0.00 | 0.00 | 0.396390E+11 | 0.396390E+11 | 54713.42 | 31-OCT-05:15 | 54713.42 | 0.00 |
November | 0.00 | 0.00 | 0.416766E+11 | 0.416766E+11 | 50952.66 | 30-NOV-06:15 | 50952.66 | 0.00 |
December | 0.00 | 0.00 | 0.450274E+11 | 0.450274E+11 | 45484.54 | 31-DEC-02:10 | 45484.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.479554E+12 | 0.477834E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.338582E+11 | 0.338582E+11 | 45484.54 | 45484.54 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.479448E+11 | 0.479448E+11 | 62274.97 | 62274.97 | 0.00 |
Report: CoilReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.501268E+11 | 0.501268E+11 | 63283.04 | 23-JAN-17:10 | 63283.04 | 0.00 |
February | 0.00 | 0.00 | 0.457469E+11 | 0.439298E+11 | 64076.57 | 01-FEB-17:10 | 61447.19 | 0.00 |
March | 0.00 | 0.00 | 0.509446E+11 | 0.509446E+11 | 64719.88 | 01-MAR-17:10 | 64719.88 | 0.00 |
April | 0.00 | 0.00 | 0.536847E+11 | 0.536847E+11 | 70482.94 | 01-APR-16:10 | 70482.94 | 0.00 |
May | 0.00 | 0.00 | 0.566123E+11 | 0.566123E+11 | 71821.71 | 01-MAY-19:20 | 71821.71 | 0.00 |
June | 0.00 | 0.00 | 0.585014E+11 | 0.585014E+11 | 76518.66 | 01-JUN-16:10 | 76518.66 | 0.00 |
July | 0.00 | 0.00 | 0.623813E+11 | 0.623813E+11 | 78636.46 | 01-JUL-19:10 | 78636.46 | 0.00 |
August | 0.00 | 0.00 | 0.623611E+11 | 0.623611E+11 | 78818.87 | 31-AUG-16:10 | 78818.87 | 0.00 |
September | 0.00 | 0.00 | 0.598770E+11 | 0.598770E+11 | 78565.43 | 30-SEP-16:10 | 78565.43 | 0.00 |
October | 0.00 | 0.00 | 0.543738E+11 | 0.543738E+11 | 69244.15 | 31-OCT-16:10 | 69244.15 | 0.00 |
November | 0.00 | 0.00 | 0.490453E+11 | 0.490453E+11 | 64482.14 | 30-NOV-17:10 | 64482.14 | 0.00 |
December | 0.00 | 0.00 | 0.454228E+11 | 0.454228E+11 | 57558.21 | 31-DEC-21:13 | 57558.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.649078E+12 | 0.647261E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.454228E+11 | 0.439298E+11 | 57558.21 | 57558.21 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.623813E+11 | 0.623813E+11 | 78818.87 | 78818.87 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.104113E+12 | 0.103683E+12 | 175247.19 | 31-JAN-16:30 | 175247.19 | 0.02 |
February | 0.00 | 0.00 | 0.254135E+11 | 0.253868E+11 | 103488.11 | 18-FEB-14:00 | 103488.11 | 0.11 |
March | 0.00 | 0.00 | 0.113067E+12 | 0.113067E+12 | 191576.16 | 20-MAR-18:10 | 191576.16 | 0.06 |
April | 0.00 | 0.00 | 0.312352E+12 | 0.312352E+12 | 256058.23 | 14-APR-18:03 | 256058.23 | 0.03 |
May | 0.00 | 0.00 | 0.407289E+12 | 0.407289E+12 | 267662.90 | 31-MAY-18:20 | 267662.90 | 0.01 |
June | 0.00 | 0.00 | 0.517999E+12 | 0.517076E+12 | 331934.51 | 17-JUN-17:17 | 269326.11 | 0.30 |
July | 0.00 | 0.00 | 0.601837E+12 | 0.523581E+12 | 397546.17 | 13-JUL-18:03 | 216471.21 | 0.81 |
August | 0.00 | 0.00 | 0.587308E+12 | 0.515820E+12 | 428459.16 | 18-AUG-22:00 | 200323.79 | 0.86 |
September | 0.00 | 0.00 | 0.539199E+12 | 0.463913E+12 | 456570.15 | 10-SEP-20:40 | 201614.08 | 0.86 |
October | 0.00 | 0.00 | 0.274308E+12 | 0.266176E+12 | 328698.51 | 02-OCT-20:00 | 244364.00 | 0.26 |
November | 0.00 | 0.00 | 0.118824E+12 | 0.105397E+12 | 194134.92 | 01-NOV-18:04 | 194134.92 | 0.21 |
December | 0.00 | 0.00 | 0.554235E+11 | 0.554235E+11 | 151356.41 | 22-DEC-16:08 | 151356.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.365713E+13 | 0.340916E+13 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 0.254135E+11 | 0.253868E+11 | 103488.11 | 103488.11 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.601837E+12 | 0.523581E+12 | 456570.15 | 269326.11 | 0.86 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.673483E+10 | 0.667920E+10 | 17033.11 | 31-JAN-16:01 | 17033.11 | 0.01 |
February | 0.00 | 0.00 | 0.173087E+10 | 0.173087E+10 | 13753.19 | 18-FEB-14:00 | 13753.19 | 0.06 |
March | 0.00 | 0.00 | 0.788829E+10 | 0.788829E+10 | 17335.41 | 16-MAR-15:01 | 17335.41 | 0.04 |
April | 0.00 | 0.00 | 0.209353E+11 | 0.209353E+11 | 19381.36 | 14-APR-15:02 | 19381.36 | 0.02 |
May | 0.00 | 0.00 | 0.271398E+11 | 0.271398E+11 | 19739.01 | 31-MAY-15:02 | 19739.01 | 0.01 |
June | 0.00 | 0.00 | 0.322302E+11 | 0.321956E+11 | 23390.50 | 17-JUN-16:00 | 19483.95 | 0.12 |
July | 0.00 | 0.00 | 0.381408E+11 | 0.329353E+11 | 30505.29 | 27-JUL-06:50 | 15040.28 | 0.62 |
August | 0.00 | 0.00 | 0.378353E+11 | 0.325800E+11 | 34897.84 | 05-AUG-08:10 | 15756.33 | 0.68 |
September | 0.00 | 0.00 | 0.358848E+11 | 0.298955E+11 | 38778.16 | 02-SEP-21:51 | 14928.22 | 0.67 |
October | 0.00 | 0.00 | 0.181404E+11 | 0.174558E+11 | 28988.59 | 03-OCT-08:61 | 17333.13 | 0.19 |
November | 0.00 | 0.00 | 0.850451E+10 | 0.712220E+10 | 24612.65 | 12-NOV-13:40 | 13863.56 | 0.17 |
December | 0.00 | 0.00 | 0.357415E+10 | 0.357415E+10 | 15816.12 | 25-DEC-16:01 | 15816.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.238739E+12 | 0.220132E+12 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 0.173087E+10 | 0.173087E+10 | 13753.19 | 13753.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.381408E+11 | 0.329353E+11 | 38778.16 | 19739.01 | 0.68 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.329611E+10 | 0.312237E+10 | 15754.45 | 14-JAN-16:01 | 15754.45 | 0.10 |
February | 0.00 | 0.00 | 0.103762E+10 | 0.840036E+09 | 14984.97 | 09-FEB-16:01 | 14984.97 | 0.15 |
March | 0.00 | 0.00 | 0.255717E+10 | 0.217631E+10 | 15771.97 | 16-MAR-15:01 | 15771.97 | 0.21 |
April | 0.00 | 0.00 | 0.856984E+10 | 0.838302E+10 | 15776.38 | 25-APR-15:02 | 15776.38 | 0.07 |
May | 0.00 | 0.00 | 0.103449E+11 | 0.102701E+11 | 15770.49 | 10-MAY-18:02 | 15770.49 | 0.03 |
June | 0.00 | 0.00 | 0.136647E+11 | 0.127924E+11 | 15778.25 | 22-JUN-08:62 | 15778.25 | 0.34 |
July | 0.00 | 0.00 | 0.134399E+11 | 0.990940E+10 | 17326.61 | 27-JUL-08:61 | 13047.06 | 0.78 |
August | 0.00 | 0.00 | 0.132283E+11 | 0.946548E+10 | 17524.44 | 04-AUG-08:61 | 12294.90 | 0.86 |
September | 0.00 | 0.00 | 0.115249E+11 | 0.777417E+10 | 18513.58 | 04-SEP-08:61 | 11824.44 | 0.93 |
October | 0.00 | 0.00 | 0.708136E+10 | 0.587925E+10 | 16801.33 | 03-OCT-08:61 | 13571.56 | 0.36 |
November | 0.00 | 0.00 | 0.339622E+10 | 0.279351E+10 | 17262.23 | 12-NOV-16:02 | 10727.77 | 0.25 |
December | 0.00 | 0.00 | 0.158942E+10 | 0.158844E+10 | 15652.64 | 25-DEC-16:01 | 15652.64 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.897304E+11 | 0.749946E+11 | 0.34 | |||
Minimum of Months | 0.00 | 0.00 | 0.103762E+10 | 0.840036E+09 | 14984.97 | 10727.77 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.136647E+11 | 0.127924E+11 | 18513.58 | 15778.25 | 0.93 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.759514E+09 | 0.712087E+09 | 15638.67 | 14-JAN-16:01 | 15638.67 | 0.04 |
February | 0.00 | 0.00 | 0.192908E+09 | 0.157466E+09 | 14608.27 | 28-FEB-16:01 | 14608.27 | 0.04 |
March | 0.00 | 0.00 | 0.105003E+10 | 0.863321E+09 | 15658.15 | 16-MAR-15:01 | 15658.15 | 0.11 |
April | 0.00 | 0.00 | 0.701342E+10 | 0.686176E+10 | 16067.60 | 26-APR-08:41 | 16067.60 | 0.06 |
May | 0.00 | 0.00 | 0.970403E+10 | 0.964531E+10 | 17330.45 | 08-MAY-08:61 | 17330.45 | 0.02 |
June | 0.00 | 0.00 | 0.135659E+11 | 0.127242E+11 | 17448.66 | 14-JUN-08:61 | 17448.66 | 0.33 |
July | 0.00 | 0.00 | 0.132667E+11 | 0.980455E+10 | 19507.59 | 27-JUL-08:11 | 12657.10 | 0.77 |
August | 0.00 | 0.00 | 0.122921E+11 | 0.875982E+10 | 19587.47 | 28-AUG-18:31 | 13761.79 | 0.81 |
September | 0.00 | 0.00 | 0.992510E+10 | 0.657654E+10 | 19965.47 | 04-SEP-08:51 | 11553.34 | 0.83 |
October | 0.00 | 0.00 | 0.446806E+10 | 0.349845E+10 | 19474.70 | 03-OCT-08:61 | 13424.94 | 0.28 |
November | 0.00 | 0.00 | 0.104709E+10 | 0.783906E+09 | 17360.35 | 13-NOV-16:01 | 11291.22 | 0.14 |
December | 0.00 | 0.00 | 0.229621E+09 | 0.229508E+09 | 15538.70 | 25-DEC-16:01 | 15538.70 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.735145E+11 | 0.606169E+11 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 0.192908E+09 | 0.157466E+09 | 14608.27 | 11291.22 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.135659E+11 | 0.127242E+11 | 19965.47 | 17448.66 | 0.83 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.428116E+11 | 0.422562E+11 | 50051.37 | 14-JAN-13:50 | 50051.37 | 0.03 |
February | 0.00 | 0.00 | 0.137627E+11 | 0.120945E+11 | 37257.07 | 01-FEB-14:20 | 37257.07 | 0.15 |
March | 0.00 | 0.00 | 0.166165E+11 | 0.155726E+11 | 35158.70 | 18-MAR-13:50 | 30163.44 | 0.07 |
April | 0.00 | 0.00 | 0.404277E+11 | 0.402191E+11 | 36751.51 | 14-APR-13:40 | 36751.51 | 0.01 |
May | 0.00 | 0.00 | 0.409313E+11 | 0.409313E+11 | 29724.55 | 09-MAY-17:20 | 29724.55 | 0.00 |
June | 0.00 | 0.00 | 0.539388E+11 | 0.520781E+11 | 37318.23 | 28-JUN-17:15 | 37318.23 | 0.09 |
July | 0.00 | 0.00 | 0.574046E+11 | 0.365001E+11 | 36565.36 | 23-JUL-08:00 | 22836.89 | 0.76 |
August | 0.00 | 0.00 | 0.606380E+11 | 0.383410E+11 | 44698.93 | 28-AUG-12:30 | 40218.28 | 0.85 |
September | 0.00 | 0.00 | 0.605291E+11 | 0.410281E+11 | 49017.14 | 28-SEP-13:30 | 41234.74 | 0.80 |
October | 0.00 | 0.00 | 0.501088E+11 | 0.437793E+11 | 50188.51 | 18-OCT-13:50 | 50188.51 | 0.28 |
November | 0.00 | 0.00 | 0.365164E+11 | 0.329734E+11 | 52279.83 | 20-NOV-14:30 | 52279.83 | 0.22 |
December | 0.00 | 0.00 | 0.298966E+11 | 0.297814E+11 | 49552.87 | 25-DEC-13:40 | 49552.87 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.503582E+12 | 0.425555E+12 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 0.137627E+11 | 0.120945E+11 | 29724.55 | 22836.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.606380E+11 | 0.520781E+11 | 52279.83 | 52279.83 | 0.85 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.730109E+10 | 0.655732E+10 | 91840.99 | 27-JAN-16:01 | 91840.99 | 0.07 |
February | 0.00 | 0.00 | 0.614641E+10 | 0.339814E+10 | 83937.34 | 18-FEB-16:01 | 81490.88 | 0.28 |
March | 0.00 | 0.00 | 0.130380E+11 | 0.105506E+11 | 94177.33 | 16-MAR-15:01 | 94177.33 | 0.22 |
April | 0.00 | 0.00 | 0.397296E+11 | 0.388675E+11 | 94210.62 | 25-APR-15:02 | 94210.62 | 0.06 |
May | 0.00 | 0.00 | 0.560950E+11 | 0.558059E+11 | 99554.07 | 20-MAY-08:61 | 99554.07 | 0.02 |
June | 0.00 | 0.00 | 0.783339E+11 | 0.730647E+11 | 101572.92 | 11-JUN-08:61 | 101572.92 | 0.34 |
July | 0.00 | 0.00 | 0.834699E+11 | 0.625755E+11 | 110338.33 | 27-JUL-08:11 | 76907.32 | 0.74 |
August | 0.00 | 0.00 | 0.755523E+11 | 0.539590E+11 | 115898.68 | 28-AUG-18:31 | 76400.19 | 0.78 |
September | 0.00 | 0.00 | 0.637333E+11 | 0.431307E+11 | 113258.32 | 04-SEP-08:51 | 72638.84 | 0.79 |
October | 0.00 | 0.00 | 0.303180E+11 | 0.243818E+11 | 109791.66 | 03-OCT-08:61 | 80615.12 | 0.26 |
November | 0.00 | 0.00 | 0.105451E+11 | 0.749942E+10 | 98136.77 | 13-NOV-16:01 | 68070.89 | 0.17 |
December | 0.00 | 0.00 | 0.328537E+10 | 0.324031E+10 | 89932.30 | 25-DEC-16:01 | 89932.30 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.467548E+12 | 0.383031E+12 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.328537E+10 | 0.324031E+10 | 83937.34 | 68070.89 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.834699E+11 | 0.730647E+11 | 115898.68 | 101572.92 | 0.79 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.313128E+10 | 0.295795E+10 | 13785.41 | 14-JAN-16:01 | 13785.41 | 0.10 |
February | 0.00 | 0.00 | 0.124973E+10 | 0.940675E+09 | 13112.48 | 09-FEB-16:01 | 13112.48 | 0.22 |
March | 0.00 | 0.00 | 0.268518E+10 | 0.223740E+10 | 13801.46 | 16-MAR-15:01 | 13801.46 | 0.24 |
April | 0.00 | 0.00 | 0.872733E+10 | 0.855249E+10 | 13805.68 | 25-APR-15:02 | 13805.68 | 0.08 |
May | 0.00 | 0.00 | 0.107425E+11 | 0.106809E+11 | 13800.08 | 10-MAY-18:02 | 13800.08 | 0.03 |
June | 0.00 | 0.00 | 0.140170E+11 | 0.133729E+11 | 13806.74 | 21-JUN-18:02 | 13806.74 | 0.35 |
July | 0.00 | 0.00 | 0.143522E+11 | 0.111290E+11 | 14177.43 | 09-JUL-08:61 | 12195.76 | 0.79 |
August | 0.00 | 0.00 | 0.139996E+11 | 0.105750E+11 | 15227.59 | 04-AUG-08:61 | 10821.42 | 0.87 |
September | 0.00 | 0.00 | 0.119586E+11 | 0.846719E+10 | 15763.48 | 03-SEP-08:61 | 10102.80 | 0.94 |
October | 0.00 | 0.00 | 0.738676E+10 | 0.625552E+10 | 13806.42 | 20-OCT-15:02 | 13806.42 | 0.37 |
November | 0.00 | 0.00 | 0.312494E+10 | 0.260635E+10 | 15582.49 | 13-NOV-16:01 | 9342.06 | 0.24 |
December | 0.00 | 0.00 | 0.160238E+10 | 0.159491E+10 | 13696.61 | 25-DEC-16:01 | 13696.61 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.929774E+11 | 0.793704E+11 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 0.124973E+10 | 0.940675E+09 | 13112.48 | 9342.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.143522E+11 | 0.133729E+11 | 15763.48 | 13806.74 | 0.94 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.722099E+09 | 0.660865E+09 | 13690.08 | 14-JAN-16:01 | 13690.08 | 0.04 |
February | 0.00 | 0.00 | 0.355271E+09 | 0.221937E+09 | 12429.67 | 09-FEB-16:01 | 12429.67 | 0.09 |
March | 0.00 | 0.00 | 0.124233E+10 | 0.997063E+09 | 13707.02 | 16-MAR-15:01 | 13707.02 | 0.15 |
April | 0.00 | 0.00 | 0.697595E+10 | 0.683296E+10 | 15795.19 | 14-APR-08:41 | 15795.19 | 0.07 |
May | 0.00 | 0.00 | 0.977124E+10 | 0.972326E+10 | 17203.91 | 21-MAY-08:61 | 17203.91 | 0.02 |
June | 0.00 | 0.00 | 0.138127E+11 | 0.131743E+11 | 17041.83 | 13-JUN-07:52 | 17041.83 | 0.35 |
July | 0.00 | 0.00 | 0.141252E+11 | 0.109503E+11 | 17730.22 | 27-JUL-08:11 | 12943.07 | 0.78 |
August | 0.00 | 0.00 | 0.129789E+11 | 0.965962E+10 | 17436.54 | 28-AUG-18:31 | 12087.82 | 0.82 |
September | 0.00 | 0.00 | 0.102597E+11 | 0.704191E+10 | 18743.75 | 04-SEP-08:51 | 12056.88 | 0.84 |
October | 0.00 | 0.00 | 0.467521E+10 | 0.370896E+10 | 17794.70 | 03-OCT-08:61 | 13022.24 | 0.30 |
November | 0.00 | 0.00 | 0.916822E+09 | 0.691117E+09 | 15043.34 | 13-NOV-16:01 | 8552.59 | 0.12 |
December | 0.00 | 0.00 | 0.243553E+09 | 0.241943E+09 | 13602.85 | 25-DEC-16:01 | 13602.85 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.760790E+11 | 0.639042E+11 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 0.243553E+09 | 0.221937E+09 | 12429.67 | 8552.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.141252E+11 | 0.131743E+11 | 18743.75 | 17203.91 | 0.84 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.768928E+09 | 0.735741E+09 | 4203.09 | 14-JAN-16:01 | 4203.09 | 0.08 |
February | 0.00 | 0.00 | 0.244785E+09 | 0.202265E+09 | 3997.80 | 09-FEB-16:01 | 3997.80 | 0.12 |
March | 0.00 | 0.00 | 0.629867E+09 | 0.542883E+09 | 4207.78 | 16-MAR-15:01 | 4207.78 | 0.18 |
April | 0.00 | 0.00 | 0.217993E+10 | 0.213141E+10 | 4208.97 | 25-APR-15:02 | 4208.97 | 0.07 |
May | 0.00 | 0.00 | 0.265007E+10 | 0.263061E+10 | 4207.33 | 10-MAY-18:02 | 4207.33 | 0.03 |
June | 0.00 | 0.00 | 0.361201E+10 | 0.337249E+10 | 4209.11 | 04-JUN-18:02 | 4209.11 | 0.34 |
July | 0.00 | 0.00 | 0.352819E+10 | 0.259303E+10 | 4793.99 | 27-JUL-08:61 | 3374.73 | 0.78 |
August | 0.00 | 0.00 | 0.345140E+10 | 0.246039E+10 | 4849.37 | 04-AUG-08:61 | 3171.39 | 0.86 |
September | 0.00 | 0.00 | 0.292631E+10 | 0.194366E+10 | 5176.47 | 04-SEP-08:61 | 3003.08 | 0.93 |
October | 0.00 | 0.00 | 0.169627E+10 | 0.139032E+10 | 4677.36 | 03-OCT-08:61 | 3501.51 | 0.35 |
November | 0.00 | 0.00 | 0.778248E+09 | 0.648690E+09 | 4607.63 | 12-NOV-16:02 | 2765.03 | 0.21 |
December | 0.00 | 0.00 | 0.370822E+09 | 0.370756E+09 | 4175.88 | 25-DEC-16:01 | 4175.88 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.228368E+11 | 0.190222E+11 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 0.244785E+09 | 0.202265E+09 | 3997.80 | 2765.03 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.361201E+10 | 0.337249E+10 | 5176.47 | 4209.11 | 0.93 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.161627E+09 | 0.155307E+09 | 4168.87 | 14-JAN-16:01 | 4168.87 | 0.02 |
February | 0.00 | 0.00 | 40547484.80 | 33477486.24 | 3908.96 | 09-FEB-16:01 | 3908.96 | 0.02 |
March | 0.00 | 0.00 | 0.251363E+09 | 0.208248E+09 | 4173.98 | 16-MAR-15:01 | 4173.98 | 0.09 |
April | 0.00 | 0.00 | 0.180650E+10 | 0.176549E+10 | 4241.85 | 26-APR-08:41 | 4241.85 | 0.06 |
May | 0.00 | 0.00 | 0.251760E+10 | 0.250166E+10 | 4572.53 | 08-MAY-08:61 | 4572.53 | 0.02 |
June | 0.00 | 0.00 | 0.360752E+10 | 0.337225E+10 | 4601.13 | 14-JUN-08:61 | 4601.13 | 0.33 |
July | 0.00 | 0.00 | 0.349350E+10 | 0.257573E+10 | 5262.68 | 27-JUL-08:11 | 3267.67 | 0.77 |
August | 0.00 | 0.00 | 0.322769E+10 | 0.228902E+10 | 5290.81 | 28-AUG-18:31 | 3611.55 | 0.81 |
September | 0.00 | 0.00 | 0.254267E+10 | 0.166012E+10 | 5444.32 | 04-SEP-08:51 | 2972.18 | 0.83 |
October | 0.00 | 0.00 | 0.106801E+10 | 0.820019E+09 | 5295.25 | 03-OCT-08:61 | 3407.90 | 0.27 |
November | 0.00 | 0.00 | 0.219824E+09 | 0.168781E+09 | 4700.06 | 13-NOV-16:01 | 2965.02 | 0.10 |
December | 0.00 | 0.00 | 48464492.11 | 48464492.11 | 4142.19 | 25-DEC-16:01 | 4142.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.189853E+11 | 0.155986E+11 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 40547484.80 | 33477486.24 | 3908.96 | 2965.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.360752E+10 | 0.337225E+10 | 5444.32 | 4601.13 | 0.83 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.100092E+11 | 0.962246E+10 | 18409.92 | 14-JAN-16:01 | 18409.92 | 0.15 |
February | 0.00 | 0.00 | 0.407910E+10 | 0.324475E+10 | 17510.56 | 09-FEB-16:01 | 17510.56 | 0.35 |
March | 0.00 | 0.00 | 0.504670E+10 | 0.423207E+10 | 18428.26 | 16-MAR-15:01 | 18428.26 | 0.32 |
April | 0.00 | 0.00 | 0.108396E+11 | 0.105204E+11 | 18426.04 | 12-APR-18:01 | 18426.04 | 0.11 |
May | 0.00 | 0.00 | 0.114508E+11 | 0.113594E+11 | 18425.83 | 10-MAY-18:02 | 18425.83 | 0.03 |
June | 0.00 | 0.00 | 0.151459E+11 | 0.138571E+11 | 18428.17 | 16-JUN-08:61 | 18428.17 | 0.42 |
July | 0.00 | 0.00 | 0.166655E+11 | 0.123382E+11 | 20777.39 | 27-JUL-08:61 | 14963.58 | 0.79 |
August | 0.00 | 0.00 | 0.172799E+11 | 0.126056E+11 | 21167.39 | 04-AUG-08:61 | 13988.83 | 0.86 |
September | 0.00 | 0.00 | 0.165638E+11 | 0.117511E+11 | 21926.66 | 04-SEP-08:61 | 13689.46 | 0.95 |
October | 0.00 | 0.00 | 0.125328E+11 | 0.109093E+11 | 19559.93 | 03-OCT-08:61 | 15937.97 | 0.38 |
November | 0.00 | 0.00 | 0.882525E+10 | 0.781353E+10 | 20178.02 | 12-NOV-09:02 | 12166.79 | 0.30 |
December | 0.00 | 0.00 | 0.730529E+10 | 0.727561E+10 | 18287.81 | 25-DEC-16:01 | 18287.81 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.135744E+12 | 0.115529E+12 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 0.407910E+10 | 0.324475E+10 | 17510.56 | 12166.79 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.172799E+11 | 0.138571E+11 | 21926.66 | 18428.26 | 0.95 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 19507.67 | 153038.25 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 24519.15 | 129376.60 | 03-FEB-07:05 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 14772.63 | 141317.24 | 26-MAR-08:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 729.37 | 78856.42 | 21-APR-06:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 35.15 | 36987.42 | 02-MAY-08:44 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 5.59 | 13087.83 | 27-JUN-08:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 9.16 | 12243.17 | 03-JUL-08:06 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 13.18 | 15781.92 | 22-AUG-08:06 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 13.45 | 13355.82 | 23-SEP-08:55 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 4737.28 | 124926.18 | 25-OCT-08:03 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 13806.15 | 129653.99 | 23-NOV-19:03 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 29218.14 | 162599.47 | 06-DEC-09:01 |
Annual Sum or Average | 0.00 | 8877.43 | ||||
Minimum of Months | 0.00 | 0.00 | 5.59 | 12243.17 | ||
Maximum of Months | 0.00 | 0.00 | 29218.14 | 162599.47 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 70655.22 | 409434.49 | 31-JAN-16:01 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 25430.57 | 288047.93 | 09-FEB-16:01 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 64708.87 | 388609.42 | 15-MAR-18:01 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 181160.81 | 472343.03 | 14-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 223635.64 | 483834.53 | 31-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 297162.08 | 552617.69 | 01-JUN-18:07 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 324951.02 | 627285.99 | 13-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 316764.52 | 575686.59 | 09-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 299143.60 | 654878.94 | 10-SEP-21:52 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 157578.43 | 518055.06 | 01-OCT-18:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 77905.53 | 406666.31 | 01-NOV-15:03 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 41723.72 | 364509.58 | 21-DEC-16:01 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 174174.68 | 0.00 | ||||
Minimum of Months | 25430.57 | 288047.93 | 0.00 | 0.00 | ||
Maximum of Months | 324951.02 | 654878.94 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 22560.38 | 47235.72 | 23-JAN-07:40 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 22340.51 | 47144.79 | 01-FEB-07:40 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 21300.56 | 45774.42 | 01-MAR-07:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 19629.82 | 42466.12 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 17834.70 | 38979.10 | 01-MAY-06:30 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 16382.63 | 35369.71 | 01-JUN-06:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15649.29 | 32965.93 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 15884.09 | 33931.48 | 31-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16966.62 | 36761.59 | 29-SEP-06:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18628.46 | 40734.79 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 20424.42 | 44227.33 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21862.94 | 46590.18 | 29-DEC-07:40 |
Annual Sum or Average | 0.00 | 19104.03 | ||||
Minimum of Months | 0.00 | 0.00 | 15649.29 | 32965.93 | ||
Maximum of Months | 0.00 | 0.00 | 22560.38 | 47235.72 |
Report: FanReportMonthly
For: SWHSYS1 HPWH FAN
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.564829E+09 | 0.06 | 553.22 | 01-JAN-06:15 | 0.11 |
February | 0.503216E+09 | 0.06 | 553.22 | 01-FEB-06:15 | 0.11 |
March | 0.527714E+09 | 0.06 | 553.22 | 01-MAR-06:15 | 0.11 |
April | 0.445219E+09 | 0.06 | 553.22 | 01-APR-05:17 | 0.11 |
May | 0.414241E+09 | 0.06 | 553.22 | 01-MAY-06:15 | 0.11 |
June | 0.352637E+09 | 0.06 | 553.22 | 01-JUN-05:10 | 0.11 |
July | 0.342246E+09 | 0.06 | 553.22 | 01-JUL-05:08 | 0.11 |
August | 0.346799E+09 | 0.06 | 553.22 | 01-AUG-05:10 | 0.11 |
September | 0.359518E+09 | 0.06 | 553.22 | 01-SEP-05:10 | 0.11 |
October | 0.442719E+09 | 0.06 | 553.22 | 01-OCT-05:10 | 0.11 |
November | 0.491470E+09 | 0.06 | 553.22 | 01-NOV-05:15 | 0.11 |
December | 0.583871E+09 | 0.06 | 553.22 | 01-DEC-04:10 | 0.11 |
Annual Sum or Average | 0.537448E+10 | 0.06 | |||
Minimum of Months | 0.342246E+09 | 0.06 | 553.22 | 0.11 | |
Maximum of Months | 0.583871E+09 | 0.06 | 553.22 | 0.11 |
Report: FanReportMonthly
For: SWHSYSLAUNDRY HPWH FAN
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.557204E+09 | 0.06 | 700.51 | 01-JAN-17:10 | 0.11 |
February | 0.503205E+09 | 0.06 | 700.51 | 01-FEB-17:10 | 0.11 |
March | 0.557180E+09 | 0.06 | 700.51 | 01-MAR-17:10 | 0.11 |
April | 0.540487E+09 | 0.06 | 700.51 | 01-APR-16:10 | 0.11 |
May | 0.559702E+09 | 0.06 | 700.51 | 01-MAY-16:10 | 0.11 |
June | 0.541281E+09 | 0.06 | 700.51 | 01-JUN-16:10 | 0.11 |
July | 0.559020E+09 | 0.05 | 700.51 | 01-JUL-16:10 | 0.11 |
August | 0.558912E+09 | 0.06 | 700.51 | 01-AUG-16:10 | 0.11 |
September | 0.540367E+09 | 0.06 | 700.51 | 01-SEP-16:10 | 0.11 |
October | 0.557540E+09 | 0.06 | 700.51 | 01-OCT-16:10 | 0.11 |
November | 0.539145E+09 | 0.06 | 700.51 | 01-NOV-16:10 | 0.11 |
December | 0.557749E+09 | 0.06 | 700.51 | 01-DEC-17:10 | 0.11 |
Annual Sum or Average | 0.657179E+10 | 0.06 | |||
Minimum of Months | 0.503205E+09 | 0.05 | 700.51 | 0.11 | |
Maximum of Months | 0.559702E+09 | 0.06 | 700.51 | 0.11 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.76 | 1299.30 | 03-JAN-16:01 | 0.97 |
February | 0.244774E+10 | 0.76 | 1299.30 | 10-FEB-19:03 | 0.96 |
March | 0.271000E+10 | 0.76 | 1299.30 | 04-MAR-09:03 | 0.96 |
April | 0.262258E+10 | 0.77 | 1299.30 | 03-APR-21:52 | 0.97 |
May | 0.271000E+10 | 0.77 | 1299.30 | 04-MAY-18:04 | 0.97 |
June | 0.262258E+10 | 0.76 | 1299.30 | 01-JUN-18:07 | 0.96 |
July | 0.271000E+10 | 0.76 | 1299.30 | 01-JUL-08:13 | 0.97 |
August | 0.271000E+10 | 0.76 | 1299.30 | 03-AUG-19:41 | 0.96 |
September | 0.262258E+10 | 0.76 | 1299.30 | 02-SEP-21:54 | 0.96 |
October | 0.271000E+10 | 0.76 | 1299.30 | 01-OCT-08:15 | 0.96 |
November | 0.262258E+10 | 0.76 | 1299.30 | 01-NOV-08:52 | 0.96 |
December | 0.271000E+10 | 0.77 | 1299.30 | 03-DEC-19:12 | 0.97 |
Annual Sum or Average | 0.319080E+11 | 0.76 | |||
Minimum of Months | 0.244774E+10 | 0.76 | 1299.30 | 0.96 | |
Maximum of Months | 0.271000E+10 | 0.77 | 1299.30 | 0.97 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.351513E+11 | 0.88 | 24718.19 | 19-JAN-22:10 | 1.27 |
February | 0.302624E+11 | 0.85 | 20612.11 | 22-FEB-22:10 | 1.13 |
March | 0.346638E+11 | 0.87 | 26608.29 | 16-MAR-21:10 | 1.32 |
April | 0.382987E+11 | 0.94 | 32860.89 | 14-APR-21:10 | 1.51 |
May | 0.414597E+11 | 0.96 | 33070.97 | 09-MAY-21:10 | 1.52 |
June | 0.455737E+11 | 1.03 | 37304.93 | 29-JUN-21:10 | 1.63 |
July | 0.461046E+11 | 1.01 | 38040.28 | 21-JUL-21:10 | 1.64 |
August | 0.467846E+11 | 1.02 | 39246.81 | 15-AUG-21:10 | 1.67 |
September | 0.452927E+11 | 1.02 | 41407.90 | 07-SEP-21:10 | 1.73 |
October | 0.414731E+11 | 0.96 | 40126.64 | 06-OCT-21:10 | 1.71 |
November | 0.362198E+11 | 0.90 | 31191.12 | 01-NOV-21:10 | 1.46 |
December | 0.349692E+11 | 0.88 | 26333.48 | 26-DEC-22:10 | 1.32 |
Annual Sum or Average | 0.476254E+12 | 0.94 | |||
Minimum of Months | 0.302624E+11 | 0.85 | 20612.11 | 1.13 | |
Maximum of Months | 0.467846E+11 | 1.03 | 41407.90 | 1.73 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.29 | 76.61 | 01-JAN-00:10 | 0.29 |
February | 0.185347E+09 | 0.29 | 76.61 | 01-FEB-00:05 | 0.29 |
March | 0.205205E+09 | 0.29 | 76.61 | 01-MAR-00:05 | 0.29 |
April | 0.198586E+09 | 0.29 | 76.61 | 01-APR-00:10 | 0.29 |
May | 0.205205E+09 | 0.29 | 76.61 | 01-MAY-00:05 | 0.29 |
June | 0.198586E+09 | 0.29 | 76.61 | 01-JUN-00:05 | 0.29 |
July | 0.205205E+09 | 0.29 | 76.61 | 01-JUL-00:10 | 0.29 |
August | 0.205205E+09 | 0.29 | 76.61 | 01-AUG-00:05 | 0.29 |
September | 0.198586E+09 | 0.29 | 76.61 | 01-SEP-00:05 | 0.29 |
October | 0.205205E+09 | 0.29 | 76.61 | 01-OCT-00:10 | 0.29 |
November | 0.198586E+09 | 0.29 | 76.61 | 01-NOV-00:05 | 0.29 |
December | 0.205205E+09 | 0.29 | 76.61 | 01-DEC-00:05 | 0.29 |
Annual Sum or Average | 0.241613E+10 | 0.29 | |||
Minimum of Months | 0.185347E+09 | 0.29 | 76.61 | 0.29 | |
Maximum of Months | 0.205205E+09 | 0.29 | 76.61 | 0.29 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.21 | 612.92 | 01-JAN-07:05 | 0.29 |
February | 0.105030E+10 | 0.21 | 612.92 | 01-FEB-07:05 | 0.29 |
March | 0.116283E+10 | 0.21 | 612.92 | 01-MAR-07:05 | 0.29 |
April | 0.112532E+10 | 0.21 | 612.92 | 01-APR-06:05 | 0.29 |
May | 0.116283E+10 | 0.21 | 612.92 | 01-MAY-06:05 | 0.29 |
June | 0.112532E+10 | 0.21 | 612.92 | 01-JUN-06:05 | 0.29 |
July | 0.116283E+10 | 0.21 | 612.92 | 01-JUL-06:05 | 0.29 |
August | 0.116283E+10 | 0.21 | 612.92 | 01-AUG-06:10 | 0.29 |
September | 0.112532E+10 | 0.21 | 612.92 | 01-SEP-06:10 | 0.29 |
October | 0.116283E+10 | 0.21 | 612.92 | 01-OCT-06:10 | 0.29 |
November | 0.112532E+10 | 0.21 | 612.92 | 01-NOV-06:05 | 0.29 |
December | 0.116283E+10 | 0.21 | 612.92 | 01-DEC-07:05 | 0.29 |
Annual Sum or Average | 0.136914E+11 | 0.21 | |||
Minimum of Months | 0.105030E+10 | 0.21 | 612.92 | 0.29 | |
Maximum of Months | 0.116283E+10 | 0.21 | 612.92 | 0.29 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.242220E+09 | 0.55 | 844.36 | 01-JAN-16:01 | 0.63 |
February | 0.145456E+09 | 0.48 | 844.36 | 01-FEB-16:01 | 0.63 |
March | 0.212236E+09 | 0.52 | 844.36 | 01-MAR-16:01 | 0.63 |
April | 0.471379E+09 | 0.60 | 844.36 | 01-APR-08:62 | 0.63 |
May | 0.550608E+09 | 0.61 | 844.36 | 01-MAY-08:62 | 0.64 |
June | 0.754745E+09 | 0.62 | 844.36 | 01-JUN-08:61 | 0.63 |
July | 0.661050E+09 | 0.62 | 844.36 | 01-JUL-08:61 | 0.64 |
August | 0.660342E+09 | 0.61 | 844.36 | 01-AUG-08:62 | 0.63 |
September | 0.570126E+09 | 0.61 | 844.36 | 01-SEP-08:61 | 0.63 |
October | 0.397975E+09 | 0.58 | 844.36 | 01-OCT-08:61 | 0.63 |
November | 0.231680E+09 | 0.54 | 844.36 | 01-NOV-08:62 | 0.63 |
December | 0.198849E+09 | 0.52 | 844.36 | 01-DEC-16:01 | 0.63 |
Annual Sum or Average | 0.509666E+10 | 0.57 | |||
Minimum of Months | 0.145456E+09 | 0.48 | 844.36 | 0.63 | |
Maximum of Months | 0.754745E+09 | 0.62 | 844.36 | 0.64 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.126344E+09 | 0.40 | 838.22 | 01-JAN-09:01 | 0.63 |
February | 0.121353E+09 | 0.41 | 838.22 | 01-FEB-16:01 | 0.63 |
March | 0.129908E+09 | 0.37 | 838.22 | 01-MAR-16:01 | 0.63 |
April | 0.388506E+09 | 0.51 | 838.22 | 01-APR-08:51 | 0.63 |
May | 0.513526E+09 | 0.54 | 838.22 | 01-MAY-08:51 | 0.64 |
June | 0.753670E+09 | 0.58 | 838.22 | 01-JUN-07:21 | 0.63 |
July | 0.653604E+09 | 0.60 | 838.22 | 01-JUL-08:61 | 0.64 |
August | 0.609916E+09 | 0.57 | 838.22 | 01-AUG-08:62 | 0.63 |
September | 0.486462E+09 | 0.54 | 838.22 | 01-SEP-08:61 | 0.63 |
October | 0.260596E+09 | 0.44 | 838.22 | 01-OCT-08:61 | 0.63 |
November | 0.119584E+09 | 0.39 | 838.22 | 01-NOV-15:01 | 0.63 |
December | 0.171542E+09 | 0.41 | 838.22 | 01-DEC-16:01 | 0.63 |
Annual Sum or Average | 0.433501E+10 | 0.48 | |||
Minimum of Months | 0.119584E+09 | 0.37 | 838.22 | 0.63 | |
Maximum of Months | 0.753670E+09 | 0.60 | 838.22 | 0.64 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.174997E+10 | 0.48 | 2248.50 | 09-JAN-15:00 | 0.63 |
February | 0.633522E+09 | 0.30 | 1397.73 | 01-FEB-14:40 | 0.63 |
March | 0.772018E+09 | 0.37 | 1310.98 | 18-MAR-14:00 | 0.63 |
April | 0.165120E+10 | 0.60 | 1287.50 | 14-APR-13:40 | 0.64 |
May | 0.169670E+10 | 0.63 | 1079.48 | 09-MAY-17:20 | 0.64 |
June | 0.210187E+10 | 0.63 | 1340.61 | 30-JUN-17:13 | 0.63 |
July | 0.209604E+10 | 0.63 | 1249.89 | 21-JUL-19:10 | 0.63 |
August | 0.219625E+10 | 0.63 | 1463.85 | 28-AUG-12:30 | 0.63 |
September | 0.221262E+10 | 0.63 | 2558.21 | 28-SEP-13:30 | 0.63 |
October | 0.200301E+10 | 0.57 | 2445.48 | 09-OCT-13:40 | 0.63 |
November | 0.151640E+10 | 0.48 | 2346.18 | 01-NOV-15:03 | 0.63 |
December | 0.126553E+10 | 0.39 | 2119.60 | 25-DEC-13:30 | 0.64 |
Annual Sum or Average | 0.198951E+11 | 0.53 | |||
Minimum of Months | 0.633522E+09 | 0.30 | 1079.48 | 0.63 | |
Maximum of Months | 0.221262E+10 | 0.63 | 2558.21 | 0.64 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.678473E+09 | 0.36 | 4988.29 | 03-JAN-16:01 | 0.64 |
February | 0.589144E+09 | 0.40 | 4988.29 | 01-FEB-16:01 | 0.63 |
March | 0.931587E+09 | 0.36 | 4988.29 | 01-MAR-09:02 | 0.63 |
April | 0.224308E+10 | 0.46 | 4988.29 | 01-APR-08:51 | 0.64 |
May | 0.307984E+10 | 0.51 | 4988.29 | 01-MAY-08:51 | 0.64 |
June | 0.444503E+10 | 0.57 | 4988.29 | 01-JUN-07:21 | 0.63 |
July | 0.415250E+10 | 0.58 | 4988.29 | 01-JUL-08:61 | 0.64 |
August | 0.371541E+10 | 0.55 | 4988.29 | 01-AUG-08:62 | 0.63 |
September | 0.320284E+10 | 0.52 | 4988.29 | 01-SEP-08:61 | 0.63 |
October | 0.169288E+10 | 0.40 | 4988.29 | 01-OCT-07:42 | 0.63 |
November | 0.748964E+09 | 0.35 | 4988.29 | 01-NOV-08:52 | 0.63 |
December | 0.724276E+09 | 0.40 | 4988.29 | 01-DEC-16:01 | 0.63 |
Annual Sum or Average | 0.262040E+11 | 0.45 | |||
Minimum of Months | 0.589144E+09 | 0.35 | 4988.29 | 0.63 | |
Maximum of Months | 0.444503E+10 | 0.58 | 4988.29 | 0.64 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.226974E+09 | 0.57 | 738.42 | 01-JAN-16:01 | 0.63 |
February | 0.144824E+09 | 0.51 | 738.42 | 01-FEB-09:02 | 0.63 |
March | 0.208821E+09 | 0.55 | 738.42 | 01-MAR-16:01 | 0.63 |
April | 0.477289E+09 | 0.62 | 738.42 | 01-APR-08:62 | 0.63 |
May | 0.573438E+09 | 0.62 | 738.42 | 01-MAY-08:62 | 0.64 |
June | 0.777464E+09 | 0.63 | 738.42 | 01-JUN-08:61 | 0.63 |
July | 0.713137E+09 | 0.62 | 738.42 | 01-JUL-08:61 | 0.64 |
August | 0.693692E+09 | 0.62 | 738.42 | 01-AUG-08:62 | 0.63 |
September | 0.593852E+09 | 0.62 | 738.42 | 01-SEP-08:61 | 0.63 |
October | 0.412979E+09 | 0.60 | 738.42 | 01-OCT-08:61 | 0.63 |
November | 0.215328E+09 | 0.56 | 738.42 | 01-NOV-08:62 | 0.63 |
December | 0.187117E+09 | 0.52 | 738.42 | 01-DEC-09:02 | 0.63 |
Annual Sum or Average | 0.522491E+10 | 0.59 | |||
Minimum of Months | 0.144824E+09 | 0.51 | 738.42 | 0.63 | |
Maximum of Months | 0.777464E+09 | 0.63 | 738.42 | 0.64 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.118028E+09 | 0.39 | 733.35 | 01-JAN-19:02 | 0.63 |
February | 0.109848E+09 | 0.40 | 733.35 | 01-FEB-09:02 | 0.63 |
March | 0.130023E+09 | 0.39 | 733.35 | 01-MAR-16:01 | 0.63 |
April | 0.383631E+09 | 0.53 | 733.35 | 01-APR-08:51 | 0.63 |
May | 0.520476E+09 | 0.55 | 733.35 | 01-MAY-08:51 | 0.64 |
June | 0.773757E+09 | 0.59 | 733.35 | 01-JUN-07:21 | 0.63 |
July | 0.704441E+09 | 0.60 | 733.35 | 01-JUL-07:42 | 0.64 |
August | 0.643768E+09 | 0.58 | 733.35 | 01-AUG-08:62 | 0.63 |
September | 0.508370E+09 | 0.55 | 733.35 | 01-SEP-07:02 | 0.63 |
October | 0.267504E+09 | 0.46 | 733.35 | 01-OCT-07:42 | 0.63 |
November | 0.109099E+09 | 0.37 | 733.35 | 01-NOV-08:52 | 0.63 |
December | 0.149653E+09 | 0.40 | 733.35 | 01-DEC-09:02 | 0.63 |
Annual Sum or Average | 0.441860E+10 | 0.48 | |||
Minimum of Months | 0.109099E+09 | 0.37 | 733.35 | 0.63 | |
Maximum of Months | 0.773757E+09 | 0.60 | 733.35 | 0.64 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 64632788.36 | 0.55 | 225.31 | 01-JAN-09:01 | 0.63 |
February | 43315297.72 | 0.49 | 225.31 | 01-FEB-16:01 | 0.63 |
March | 58093009.19 | 0.52 | 225.31 | 01-MAR-16:01 | 0.63 |
April | 0.120514E+09 | 0.60 | 225.31 | 01-APR-15:01 | 0.64 |
May | 0.141867E+09 | 0.61 | 225.31 | 01-MAY-15:01 | 0.64 |
June | 0.200135E+09 | 0.62 | 225.31 | 01-JUN-08:61 | 0.63 |
July | 0.174443E+09 | 0.62 | 225.31 | 01-JUL-08:61 | 0.64 |
August | 0.173305E+09 | 0.61 | 225.31 | 01-AUG-08:62 | 0.63 |
September | 0.145984E+09 | 0.61 | 225.31 | 01-SEP-08:61 | 0.63 |
October | 98802871.19 | 0.58 | 225.31 | 01-OCT-08:61 | 0.63 |
November | 60141316.51 | 0.54 | 225.31 | 01-NOV-15:01 | 0.63 |
December | 57817181.29 | 0.52 | 225.31 | 01-DEC-16:01 | 0.63 |
Annual Sum or Average | 0.133905E+10 | 0.57 | |||
Minimum of Months | 43315297.72 | 0.49 | 225.31 | 0.63 | |
Maximum of Months | 0.200135E+09 | 0.62 | 225.31 | 0.64 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 39102210.79 | 0.40 | 223.49 | 01-JAN-09:01 | 0.63 |
February | 38637734.21 | 0.40 | 223.49 | 01-FEB-09:02 | 0.63 |
March | 37598272.63 | 0.38 | 223.49 | 01-MAR-16:01 | 0.63 |
April | 0.100404E+09 | 0.51 | 223.49 | 01-APR-15:01 | 0.64 |
May | 0.133732E+09 | 0.54 | 223.49 | 01-MAY-08:51 | 0.64 |
June | 0.200686E+09 | 0.58 | 223.49 | 01-JUN-07:21 | 0.63 |
July | 0.172795E+09 | 0.60 | 223.49 | 01-JUL-08:61 | 0.64 |
August | 0.161745E+09 | 0.57 | 223.49 | 01-AUG-08:62 | 0.63 |
September | 0.125629E+09 | 0.54 | 223.49 | 01-SEP-08:61 | 0.63 |
October | 66026399.58 | 0.44 | 223.49 | 01-OCT-08:61 | 0.63 |
November | 34972729.52 | 0.38 | 223.49 | 01-NOV-15:01 | 0.63 |
December | 53990362.70 | 0.41 | 223.49 | 01-DEC-09:02 | 0.63 |
Annual Sum or Average | 0.116532E+10 | 0.48 | |||
Minimum of Months | 34972729.52 | 0.38 | 223.49 | 0.63 | |
Maximum of Months | 0.200686E+09 | 0.60 | 223.49 | 0.64 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.593659E+09 | 0.59 | 984.89 | 01-JAN-09:01 | 0.63 |
February | 0.287359E+09 | 0.54 | 984.89 | 01-FEB-09:02 | 0.63 |
March | 0.344673E+09 | 0.55 | 984.89 | 01-MAR-16:01 | 0.63 |
April | 0.593206E+09 | 0.60 | 984.89 | 01-APR-08:62 | 0.63 |
May | 0.617336E+09 | 0.60 | 984.89 | 01-MAY-08:62 | 0.64 |
June | 0.830605E+09 | 0.61 | 984.89 | 01-JUN-08:61 | 0.63 |
July | 0.811048E+09 | 0.61 | 984.89 | 01-JUL-08:61 | 0.64 |
August | 0.851109E+09 | 0.61 | 984.89 | 01-AUG-08:62 | 0.63 |
September | 0.840897E+09 | 0.61 | 984.89 | 01-SEP-08:61 | 0.63 |
October | 0.700898E+09 | 0.60 | 984.89 | 01-OCT-08:61 | 0.63 |
November | 0.516312E+09 | 0.58 | 984.89 | 01-NOV-08:62 | 0.63 |
December | 0.466610E+09 | 0.58 | 984.89 | 01-DEC-09:02 | 0.63 |
Annual Sum or Average | 0.745371E+10 | 0.59 | |||
Minimum of Months | 0.287359E+09 | 0.54 | 984.89 | 0.63 | |
Maximum of Months | 0.851109E+09 | 0.61 | 984.89 | 0.64 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.258877E+09 | 0.235320E+09 | 609.71 | 01-JAN-00:10 | 554.22 | 554.22 | 47.23 | 1.11 |
February | 0.299515E+09 | 0.272259E+09 | 536.93 | 03-FEB-07:10 | 488.07 | 488.07 | 44.39 | 0.85 |
March | 0.198660E+09 | 0.180582E+09 | 555.40 | 25-MAR-23:10 | 504.86 | 504.86 | 45.25 | 0.91 |
April | 8877895.78 | 8070007.27 | 321.83 | 21-APR-06:10 | 292.54 | 292.54 | 34.02 | 0.40 |
May | 712214.38 | 647402.87 | 204.61 | 02-MAY-08:44 | 185.99 | 185.99 | 41.84 | 0.24 |
June | 146489.57 | 133159.02 | 131.49 | 27-JUN-08:06 | 119.53 | 119.53 | 57.61 | 0.14 |
July | 286830.01 | 260728.48 | 133.12 | 27-JUL-08:16 | 121.00 | 121.00 | 61.19 | 0.15 |
August | 420907.94 | 382605.32 | 176.17 | 22-AUG-08:06 | 160.13 | 160.13 | 60.30 | 0.20 |
September | 430811.01 | 391607.21 | 157.92 | 23-SEP-08:55 | 143.55 | 143.55 | 61.16 | 0.17 |
October | 61436280.60 | 55845579.07 | 487.49 | 25-OCT-08:03 | 443.12 | 443.12 | 38.34 | 0.72 |
November | 0.179874E+09 | 0.163505E+09 | 534.99 | 04-NOV-06:20 | 486.31 | 486.31 | 44.43 | 0.85 |
December | 0.408607E+09 | 0.371424E+09 | 613.38 | 06-DEC-09:01 | 557.56 | 557.56 | 45.32 | 1.12 |
Annual Sum or Average | 0.141784E+10 | 0.128882E+10 | ||||||
Minimum of Months | 146489.57 | 133159.02 | 131.49 | 119.53 | 119.53 | 34.02 | 0.14 | |
Maximum of Months | 0.408607E+09 | 0.371424E+09 | 613.38 | 557.56 | 557.56 | 61.19 | 1.12 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.138706E+09 | 0.126083E+09 | 523.51 | 31-JAN-16:01 | 475.87 | 475.87 | 6.73 | 10.62 |
February | 40291502.07 | 36624975.39 | 420.04 | 18-FEB-16:01 | 381.82 | 381.82 | 7.46 | 9.61 |
March | 0.132594E+09 | 0.120528E+09 | 1113.82 | 17-MAR-18:03 | 1012.46 | 1012.46 | 7.11 | 14.79 |
April | 0.498101E+09 | 0.452774E+09 | 1356.25 | 25-APR-19:10 | 1232.83 | 1232.83 | 6.73 | 16.09 |
May | 0.626855E+09 | 0.569811E+09 | 965.01 | 29-MAY-20:50 | 877.19 | 877.19 | 6.73 | 13.91 |
June | 0.121487E+10 | 0.110432E+10 | 2511.75 | 28-JUN-19:10 | 2283.18 | 2283.18 | 6.73 | 20.79 |
July | 0.135596E+10 | 0.123257E+10 | 1763.03 | 07-JUL-20:20 | 1602.59 | 1602.59 | 6.73 | 17.96 |
August | 0.131456E+10 | 0.119493E+10 | 2024.35 | 27-AUG-18:02 | 1840.13 | 1840.13 | 6.73 | 19.03 |
September | 0.125239E+10 | 0.113843E+10 | 2015.04 | 18-SEP-18:05 | 1831.67 | 1831.67 | 6.73 | 18.99 |
October | 0.523648E+09 | 0.475996E+09 | 1454.49 | 05-OCT-20:20 | 1322.13 | 1322.13 | 6.82 | 16.57 |
November | 0.168079E+09 | 0.152784E+09 | 1229.77 | 01-NOV-18:03 | 1117.86 | 1117.86 | 7.17 | 15.43 |
December | 70977514.30 | 64518560.49 | 459.12 | 21-DEC-16:01 | 417.34 | 417.34 | 7.00 | 10.01 |
Annual Sum or Average | 0.733704E+10 | 0.666937E+10 | ||||||
Minimum of Months | 40291502.07 | 36624975.39 | 420.04 | 381.82 | 381.82 | 6.73 | 9.61 | |
Maximum of Months | 0.135596E+10 | 0.123257E+10 | 2511.75 | 2283.18 | 2283.18 | 7.46 | 20.79 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.103202E+11 | 0.938110E+10 | 4184.08 | 01-JAN-00:20 | 3803.33 | 3803.33 | 8.40 | 29.62 |
February | 0.796293E+10 | 0.723831E+10 | 4184.08 | 01-FEB-00:05 | 3803.33 | 3803.33 | 8.56 | 29.62 |
March | 0.101119E+11 | 0.919170E+10 | 4184.08 | 01-MAR-00:05 | 3803.33 | 3803.33 | 8.44 | 29.62 |
April | 0.108414E+11 | 0.985481E+10 | 4184.08 | 01-APR-00:10 | 3803.33 | 3803.33 | 8.57 | 29.62 |
May | 0.112066E+11 | 0.101868E+11 | 4184.08 | 01-MAY-00:05 | 3803.33 | 3803.33 | 8.81 | 29.62 |
June | 0.108451E+11 | 0.985823E+10 | 4184.08 | 01-JUN-00:05 | 3803.33 | 3803.33 | 8.70 | 29.62 |
July | 0.112066E+11 | 0.101868E+11 | 4184.08 | 01-JUL-00:10 | 3803.33 | 3803.33 | 8.97 | 29.62 |
August | 0.112066E+11 | 0.101868E+11 | 4184.08 | 01-AUG-00:05 | 3803.33 | 3803.33 | 9.21 | 29.62 |
September | 0.108451E+11 | 0.985823E+10 | 4184.08 | 01-SEP-00:05 | 3803.33 | 3803.33 | 8.84 | 29.62 |
October | 0.110874E+11 | 0.100784E+11 | 4184.08 | 01-OCT-00:10 | 3803.33 | 3803.33 | 8.80 | 29.62 |
November | 0.100675E+11 | 0.915138E+10 | 4184.08 | 01-NOV-00:05 | 3803.33 | 3803.33 | 8.73 | 29.62 |
December | 0.897703E+10 | 0.816012E+10 | 4184.08 | 01-DEC-00:05 | 3803.33 | 3803.33 | 8.43 | 29.62 |
Annual Sum or Average | 0.124679E+12 | 0.113333E+12 | ||||||
Minimum of Months | 0.796293E+10 | 0.723831E+10 | 4184.08 | 3803.33 | 3803.33 | 8.40 | 29.62 | |
Maximum of Months | 0.112066E+11 | 0.101868E+11 | 4184.08 | 3803.33 | 3803.33 | 9.21 | 29.62 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 50.72 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:05 | 14.37 | 14.37 | 51.30 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 51.55 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 54.18 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 54.51 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 55.01 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 55.48 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 55.42 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 55.21 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 54.34 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 54.26 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:05 | 14.37 | 14.37 | 51.81 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 50.72 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 55.48 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 47.23 | 80.36 | 19507.67 | 153038.25 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 44.90 | 79.40 | 24519.15 | 129376.60 | 03-FEB-07:05 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 56.66 | 79.40 | 14772.63 | 141317.24 | 26-MAR-08:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.96 | 52.96 | 729.37 | 78856.42 | 21-APR-06:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 45.41 | 45.41 | 35.15 | 36987.42 | 02-MAY-08:44 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 56.21 | 56.21 | 5.59 | 13087.83 | 27-JUN-08:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.83 | 57.83 | 9.16 | 12243.17 | 03-JUL-08:06 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 61.19 | 61.19 | 13.18 | 15781.92 | 22-AUG-08:06 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 59.41 | 59.41 | 13.45 | 13355.82 | 23-SEP-08:55 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 60.26 | 60.26 | 4737.28 | 124926.18 | 25-OCT-08:03 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 43.46 | 43.46 | 13806.15 | 129653.99 | 23-NOV-19:03 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 34.88 | 79.53 | 29218.14 | 162599.47 | 06-DEC-09:01 |
Annual Sum or Average | 0.00 | 8877.43 | ||||||
Minimum of Months | 0.00 | 0.00 | 34.88 | 43.46 | 5.59 | 12243.17 | ||
Maximum of Months | 0.00 | 0.00 | 61.19 | 80.36 | 29218.14 | 162599.47 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 70655.22 | 409434.49 | 31-JAN-16:01 | 10.00 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 25430.57 | 288047.93 | 09-FEB-16:01 | 9.90 | 7.58 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 64708.87 | 388609.42 | 15-MAR-18:01 | 9.85 | 6.72 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 181160.81 | 472343.03 | 14-APR-18:03 | 10.51 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 223635.64 | 483834.53 | 31-MAY-18:03 | 10.60 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 297162.08 | 552617.69 | 01-JUN-18:07 | 11.15 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 324951.02 | 627285.99 | 13-JUL-18:03 | 11.86 | 6.81 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 316764.52 | 575686.59 | 09-AUG-18:03 | 11.55 | 6.91 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 299143.60 | 654878.94 | 10-SEP-21:52 | 12.42 | 7.14 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 157578.43 | 518055.06 | 01-OCT-18:03 | 10.87 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 77905.53 | 406666.31 | 01-NOV-15:03 | 9.98 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 41723.72 | 364509.58 | 21-DEC-16:01 | 9.94 | 7.01 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 174174.68 | 0.00 | ||||||
Minimum of Months | 25430.57 | 288047.93 | 9.85 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 324951.02 | 654878.94 | 12.42 | 7.58 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 50.72 | 59.99 | 22560.38 | 47235.72 | 23-JAN-07:40 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 51.30 | 59.99 | 22340.51 | 47144.79 | 01-FEB-07:40 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 51.55 | 59.99 | 21300.56 | 45774.42 | 01-MAR-07:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 54.18 | 59.99 | 19629.82 | 42466.12 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 54.51 | 60.00 | 17834.70 | 38979.10 | 01-MAY-06:30 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 55.01 | 59.98 | 16382.63 | 35369.71 | 01-JUN-06:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 55.48 | 59.97 | 15649.29 | 32965.93 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 55.42 | 59.98 | 15884.09 | 33931.48 | 31-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 55.21 | 59.97 | 16966.62 | 36761.59 | 29-SEP-06:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 54.34 | 59.97 | 18628.46 | 40734.79 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 54.26 | 59.99 | 20424.42 | 44227.33 | 30-NOV-07:30 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 51.81 | 59.97 | 21862.94 | 46590.18 | 29-DEC-07:40 |
Annual Sum or Average | 0.00 | 19104.03 | ||||||
Minimum of Months | 0.00 | 0.00 | 50.72 | 59.97 | 15649.29 | 32965.93 | ||
Maximum of Months | 0.00 | 0.00 | 55.48 | 60.00 | 22560.38 | 47235.72 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.475404E+11 | 0.00 | 0.104113E+12 | 0.351513E+11 | 0.00 | 0.00 |
February | 0.529878E+11 | 0.00 | 0.254135E+11 | 0.302624E+11 | 0.00 | 0.00 |
March | 0.356435E+11 | 0.00 | 0.113067E+12 | 0.346638E+11 | 0.00 | 0.00 |
April | 0.177013E+10 | 0.00 | 0.312352E+12 | 0.382987E+11 | 0.00 | 0.00 |
May | 18787969.24 | 0.00 | 0.407289E+12 | 0.414597E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.517999E+12 | 0.455737E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.601837E+12 | 0.461046E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.587308E+12 | 0.467846E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.539199E+12 | 0.452927E+11 | 0.00 | 0.00 |
October | 0.119699E+11 | 0.00 | 0.274308E+12 | 0.414731E+11 | 0.00 | 0.00 |
November | 0.325003E+11 | 0.00 | 0.118824E+12 | 0.362198E+11 | 0.00 | 0.00 |
December | 0.646766E+11 | 0.00 | 0.554235E+11 | 0.349692E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.247108E+12 | 0.00 | 0.365713E+13 | 0.476254E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.254135E+11 | 0.302624E+11 | 0.00 | 0.00 |
Maximum of Months | 0.646766E+11 | 0.00 | 0.601837E+12 | 0.467846E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 7757.08 | 0.00 | 0.673483E+10 | 0.271000E+10 | 0.00 | 0.00 |
February | 4447.77 | 0.00 | 0.173087E+10 | 0.244774E+10 | 0.00 | 0.00 |
March | 11148.34 | 0.00 | 0.788829E+10 | 0.271000E+10 | 0.00 | 0.00 |
April | 20059.15 | 0.00 | 0.209353E+11 | 0.262258E+10 | 0.00 | 0.00 |
May | 20155.90 | 0.00 | 0.271398E+11 | 0.271000E+10 | 0.00 | 0.00 |
June | 13501.22 | 0.00 | 0.322302E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 14404.88 | 0.00 | 0.381408E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 10694.92 | 0.00 | 0.378353E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 9250.09 | 0.00 | 0.358848E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 13116.32 | 0.00 | 0.181404E+11 | 0.271000E+10 | 0.00 | 0.00 |
November | 12677.87 | 0.00 | 0.850451E+10 | 0.262258E+10 | 0.00 | 0.00 |
December | 1143834.25 | 0.00 | 0.357415E+10 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 1281047.79 | 0.00 | 0.238739E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 4447.77 | 0.00 | 0.173087E+10 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 1143834.25 | 0.00 | 0.381408E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.351513E+11 | 0.104113E+12 | 0.475404E+11 | 0.153135E+11 | 0.272373E+09 | 0.00 | 0.00 | 0.00 |
February | 0.302624E+11 | 0.254135E+11 | 0.529878E+11 | 0.154968E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.346638E+11 | 0.113067E+12 | 0.356435E+11 | 0.194415E+11 | 0.944986E+09 | 0.00 | 0.00 | 0.00 |
April | 0.382987E+11 | 0.312352E+12 | 0.177013E+10 | 0.104693E+11 | 0.208326E+11 | 0.00 | 0.00 | 0.00 |
May | 0.414597E+11 | 0.407289E+12 | 18787969.24 | 0.136889E+11 | 0.397826E+11 | 0.00 | 0.00 | 0.00 |
June | 0.455737E+11 | 0.517999E+12 | 0.00 | 0.239555E+11 | 0.760526E+11 | 0.00 | 0.00 | 0.00 |
July | 0.461046E+11 | 0.601837E+12 | 0.00 | 0.113214E+11 | 0.104512E+12 | 0.00 | 0.00 | 0.00 |
August | 0.467846E+11 | 0.587308E+12 | 0.00 | 0.130861E+11 | 0.912816E+11 | 0.00 | 0.00 | 0.00 |
September | 0.452927E+11 | 0.539199E+12 | 0.00 | 0.114277E+11 | 0.672399E+11 | 0.00 | 0.00 | 0.00 |
October | 0.414731E+11 | 0.274308E+12 | 0.119699E+11 | 0.787444E+10 | 0.180903E+11 | 0.00 | 0.00 | 0.00 |
November | 0.362198E+11 | 0.118824E+12 | 0.325003E+11 | 0.138718E+11 | 0.556333E+09 | 0.00 | 0.00 | 0.00 |
December | 0.349692E+11 | 0.554235E+11 | 0.646766E+11 | 0.682606E+11 | 26471929.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.476254E+12 | 0.365713E+13 | 0.247108E+12 | 0.210261E+12 | 0.419592E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.302624E+11 | 0.254135E+11 | 0.00 | 0.154968E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.467846E+11 | 0.601837E+12 | 0.646766E+11 | 0.682606E+11 | 0.104512E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.673483E+10 | 7757.08 | 0.106506E+11 | 26409250.95 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.173087E+10 | 4447.77 | 0.995077E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.788829E+10 | 11148.34 | 0.901147E+10 | 0.125806E+09 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.209353E+11 | 20059.15 | 0.139925E+10 | 0.257348E+10 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.271398E+11 | 20155.90 | 0.108394E+10 | 0.488519E+10 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.322302E+11 | 13501.22 | 0.994597E+09 | 0.108349E+11 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.381408E+11 | 14404.88 | 0.261646E+09 | 0.226615E+11 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.378353E+11 | 10694.92 | 0.227527E+09 | 0.202570E+11 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.358848E+11 | 9250.09 | 0.283852E+09 | 0.150677E+11 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.181404E+11 | 13116.32 | 0.285604E+10 | 0.339428E+10 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.850451E+10 | 12677.87 | 0.815553E+10 | 0.118395E+09 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.357415E+10 | 1143834.25 | 0.178494E+11 | 9109897.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.238739E+12 | 1281047.79 | 0.627246E+11 | 0.799537E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.173087E+10 | 4447.77 | 0.227527E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.381408E+11 | 1143834.25 | 0.178494E+11 | 0.226615E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.351513E+11 | 0.475404E+11 | 0.104113E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.302624E+11 | 0.529878E+11 | 0.254135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.346638E+11 | 0.356435E+11 | 0.113067E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.382987E+11 | 0.177013E+10 | 0.312352E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.414597E+11 | 18787969.24 | 0.407289E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.455737E+11 | 0.00 | 0.517999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.461046E+11 | 0.00 | 0.601837E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.467846E+11 | 0.00 | 0.587308E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.452927E+11 | 0.00 | 0.539199E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.414731E+11 | 0.119699E+11 | 0.274308E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.362198E+11 | 0.325003E+11 | 0.118824E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.349692E+11 | 0.646766E+11 | 0.554235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.476254E+12 | 0.247108E+12 | 0.365713E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.302624E+11 | 0.00 | 0.254135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.467846E+11 | 0.646766E+11 | 0.601837E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 7757.08 | 0.673483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 4447.77 | 0.173087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 11148.34 | 0.788829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 20059.15 | 0.209353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 20155.90 | 0.271398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 13501.22 | 0.322302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 14404.88 | 0.381408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 10694.92 | 0.378353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 9250.09 | 0.358848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 13116.32 | 0.181404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 12677.87 | 0.850451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 1143834.25 | 0.357415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 1281047.79 | 0.238739E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 4447.77 | 0.173087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 1143834.25 | 0.381408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.118588E+11 | 0.00 | 0.00 | 14974946.74 | 1159387.49 | 0.00 | 0.251426E+11 | 0.00 | 0.84 |
February | 0.369299E+11 | 0.00 | 0.00 | 617066.40 | 0.00 | 0.00 | 0.137883E+10 | 0.00 | 0.82 |
March | 0.335454E+11 | 0.00 | 0.00 | 0.00 | 11618973.18 | 0.00 | 0.00 | 0.00 | 0.83 |
April | 0.161232E+11 | 0.00 | 0.00 | 0.00 | 0.539809E+09 | 0.00 | 0.00 | 0.00 | 0.81 |
May | 0.109088E+11 | 0.00 | 0.00 | 0.00 | 0.117879E+10 | 0.00 | 0.00 | 0.00 | 0.78 |
June | 0.484418E+10 | 0.00 | 0.00 | 0.00 | 0.272902E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
July | 0.101795E+10 | 0.217315E+10 | 0.00 | 9890864.35 | 0.313459E+10 | 0.00 | 0.123575E+10 | 0.00 | 0.67 |
August | 1117210.21 | 0.406820E+10 | 0.00 | 28407595.71 | 0.630867E+09 | 0.00 | 0.309865E+10 | 0.00 | 0.75 |
September | 0.00 | 0.481465E+10 | 0.00 | 41897097.80 | 23251208.68 | 0.00 | 0.615916E+10 | 0.00 | 0.94 |
October | 2530.77 | 0.691420E+09 | 0.00 | 83897689.49 | 1706158.38 | 0.00 | 0.301231E+11 | 0.00 | 1.06 |
November | 2058473.45 | 15239049.12 | 0.00 | 85734044.92 | 0.00 | 0.00 | 0.434014E+11 | 0.00 | 1.06 |
December | 0.123218E+09 | 0.00 | 0.00 | 73455398.70 | 0.00 | 0.00 | 0.505136E+11 | 0.00 | 0.98 |
Annual Sum or Average | 0.115354E+12 | 0.117627E+11 | 0.00 | 0.338875E+09 | 0.825082E+10 | 0.00 | 0.161053E+12 | 0.00 | 0.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
Maximum of Months | 0.369299E+11 | 0.481465E+10 | 0.00 | 85734044.92 | 0.313459E+10 | 0.00 | 0.505136E+11 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.464700E+10 | 330754.11 | 0.00 | 4609375.32 | 0.00 | 15231450.00 | 0.121956E+10 | 0.00 | 2.63 |
February | 0.554046E+10 | 0.00 | 0.00 | 760006.48 | 0.00 | 4218185.08 | 0.494936E+09 | 0.00 | 2.36 |
March | 0.496173E+10 | 1251227.13 | 0.00 | 684506.76 | 694434.92 | 87395462.32 | 0.214043E+09 | 0.00 | 2.38 |
April | 0.184971E+10 | 0.109846E+09 | 0.00 | 2948224.82 | 539427.04 | 0.00 | 0.686293E+09 | 0.00 | 2.45 |
May | 0.115319E+10 | 0.201910E+09 | 0.00 | 2263597.35 | 5410643.73 | 0.00 | 0.563354E+09 | 0.00 | 2.32 |
June | 0.163177E+09 | 0.542856E+09 | 0.00 | 3260902.69 | 1880427.69 | 0.00 | 0.615574E+09 | 0.00 | 2.19 |
July | 82800854.89 | 0.910978E+09 | 0.00 | 1824544.57 | 36142107.18 | 0.00 | 0.276978E+09 | 0.00 | 2.11 |
August | 0.119236E+09 | 0.833561E+09 | 0.00 | 2068244.43 | 32585636.12 | 0.00 | 0.321828E+09 | 0.00 | 2.26 |
September | 0.259390E+09 | 0.673741E+09 | 0.00 | 2400462.11 | 0.108652E+09 | 0.00 | 0.445084E+09 | 0.00 | 2.45 |
October | 0.256038E+10 | 0.149582E+09 | 0.00 | 4220386.67 | 1480019.58 | 0.00 | 0.958639E+09 | 0.00 | 2.65 |
November | 0.416024E+10 | 286641.35 | 0.00 | 3787971.19 | 2224382.81 | 0.00 | 0.110657E+10 | 0.00 | 2.60 |
December | 0.542609E+10 | 0.00 | 0.00 | 2714652.62 | 0.00 | 0.186673E+09 | 0.914317E+09 | 0.00 | 2.47 |
Annual Sum or Average | 0.309234E+11 | 0.342434E+10 | 0.00 | 31542874.99 | 0.189609E+09 | 0.293518E+09 | 0.781718E+10 | 0.00 | 2.41 |
Minimum of Months | 82800854.89 | 0.00 | 0.00 | 684506.76 | 0.00 | 0.00 | 0.214043E+09 | 0.00 | 2.11 |
Maximum of Months | 0.554046E+10 | 0.910978E+09 | 0.00 | 4609375.32 | 0.108652E+09 | 0.186673E+09 | 0.121956E+10 | 0.00 | 2.65 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.275719E+10 | 0.00 | 0.00 | 1002504.57 | 126378.64 | 0.00 | 0.124760E+10 | 0.00 | 1.43 |
February | 0.377305E+10 | 0.00 | 0.00 | 182740.17 | 0.00 | 0.00 | 0.402449E+09 | 0.00 | 1.41 |
March | 0.291702E+10 | 0.00 | 0.00 | 676333.52 | 1266522.28 | 0.00 | 0.749012E+09 | 0.00 | 1.43 |
April | 0.276911E+09 | 37116499.01 | 0.00 | 3944247.99 | 21814932.10 | 0.00 | 0.159908E+10 | 0.00 | 1.50 |
May | 49581164.51 | 0.100317E+09 | 0.00 | 4358371.98 | 29048119.06 | 0.00 | 0.125545E+10 | 0.00 | 1.49 |
June | 456560.61 | 0.303068E+09 | 0.00 | 5018434.51 | 10981273.17 | 0.00 | 0.665598E+09 | 0.00 | 1.39 |
July | 588324.39 | 0.597840E+09 | 0.00 | 2677600.69 | 36327534.38 | 0.00 | 0.301607E+09 | 0.00 | 1.32 |
August | 4840335.29 | 0.488544E+09 | 0.00 | 3082810.96 | 40298967.91 | 0.00 | 0.357194E+09 | 0.00 | 1.36 |
September | 8251716.76 | 0.438759E+09 | 0.00 | 3172662.65 | 44531366.95 | 0.00 | 0.541305E+09 | 0.00 | 1.43 |
October | 0.103013E+10 | 67578950.28 | 0.00 | 3212319.11 | 5625679.59 | 0.00 | 0.148763E+10 | 0.00 | 1.50 |
November | 0.230291E+10 | 63503.10 | 0.00 | 1189354.64 | 1595842.72 | 0.00 | 0.129787E+10 | 0.00 | 1.45 |
December | 0.385115E+10 | 0.00 | 0.00 | 335082.55 | 0.00 | 0.00 | 0.617971E+09 | 0.00 | 1.41 |
Annual Sum or Average | 0.169721E+11 | 0.203329E+10 | 0.00 | 28852463.34 | 0.191617E+09 | 0.00 | 0.105228E+11 | 0.00 | 1.43 |
Minimum of Months | 456560.61 | 0.00 | 0.00 | 182740.17 | 0.00 | 0.00 | 0.301607E+09 | 0.00 | 1.32 |
Maximum of Months | 0.385115E+10 | 0.597840E+09 | 0.00 | 5018434.51 | 44531366.95 | 0.00 | 0.159908E+10 | 0.00 | 1.50 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.382457E+10 | 0.00 | 0.00 | 0.00 | 121367.34 | 0.00 | 0.00 | 0.00 | 0.64 |
February | 0.401009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
March | 0.351161E+10 | 0.00 | 0.00 | 0.00 | 1216300.79 | 0.00 | 0.00 | 0.00 | 0.64 |
April | 0.159859E+10 | 193174.29 | 0.00 | 259467.21 | 56315224.20 | 0.00 | 89723588.81 | 0.00 | 0.63 |
May | 0.781556E+09 | 29020944.81 | 0.00 | 1293909.60 | 94474019.92 | 0.00 | 0.371360E+09 | 0.00 | 0.62 |
June | 2598059.78 | 0.324452E+09 | 0.00 | 4611192.83 | 2929320.52 | 0.00 | 0.581000E+09 | 0.00 | 0.63 |
July | 10030910.71 | 0.607424E+09 | 0.00 | 2422106.37 | 26546484.10 | 0.00 | 0.260549E+09 | 0.00 | 0.61 |
August | 40997586.33 | 0.462548E+09 | 0.00 | 2329002.77 | 49519822.37 | 0.00 | 0.268939E+09 | 0.00 | 0.60 |
September | 0.152180E+09 | 0.330356E+09 | 0.00 | 1656867.70 | 0.123368E+09 | 0.00 | 0.326240E+09 | 0.00 | 0.61 |
October | 0.219186E+10 | 46777926.44 | 0.00 | 503517.01 | 22493459.95 | 0.00 | 0.135710E+09 | 0.00 | 0.65 |
November | 0.342448E+10 | 0.00 | 0.00 | 0.00 | 1593547.67 | 0.00 | 0.00 | 0.00 | 0.65 |
December | 0.427548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12737217.98 | 0.00 | 0.00 | 0.63 |
Annual Sum or Average | 0.238240E+11 | 0.180077E+10 | 0.00 | 13076063.49 | 0.378577E+09 | 12737217.98 | 0.203352E+10 | 0.00 | 0.63 |
Minimum of Months | 2598059.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
Maximum of Months | 0.427548E+10 | 0.607424E+09 | 0.00 | 4611192.83 | 0.123368E+09 | 12737217.98 | 0.581000E+09 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.209486E+10 | 0.00 | 0.00 | 0.00 | 66904.52 | 13457812.45 | 0.00 | 0.00 | 0.61 |
February | 0.221059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
March | 0.193580E+10 | 0.00 | 0.00 | 0.00 | 670493.55 | 0.00 | 0.00 | 0.00 | 0.62 |
April | 0.922388E+09 | 1801.92 | 0.00 | 21462.58 | 31148812.02 | 0.00 | 8007772.40 | 0.00 | 0.60 |
May | 0.539203E+09 | 12555571.78 | 0.00 | 323469.30 | 55468879.86 | 0.00 | 90544467.09 | 0.00 | 0.59 |
June | 19748266.14 | 0.178279E+09 | 0.00 | 2047984.84 | 2854708.82 | 0.00 | 0.281577E+09 | 0.00 | 0.57 |
July | 10523510.88 | 0.317351E+09 | 0.00 | 1108851.62 | 19089433.97 | 0.00 | 0.128729E+09 | 0.00 | 0.55 |
August | 40051662.92 | 0.235647E+09 | 0.00 | 920444.19 | 37027050.33 | 0.00 | 0.124140E+09 | 0.00 | 0.54 |
September | 0.141587E+09 | 0.154292E+09 | 0.00 | 528357.26 | 87124769.02 | 0.00 | 0.115931E+09 | 0.00 | 0.56 |
October | 0.124262E+10 | 23532738.53 | 0.00 | 146133.18 | 13834032.77 | 0.00 | 38854130.20 | 0.00 | 0.61 |
November | 0.188776E+10 | 0.00 | 0.00 | 0.00 | 878453.29 | 0.00 | 0.00 | 0.00 | 0.62 |
December | 0.230951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54401699.37 | 0.00 | 0.00 | 0.61 |
Annual Sum or Average | 0.133546E+11 | 0.921660E+09 | 0.00 | 5096702.97 | 0.248164E+09 | 67859511.82 | 0.787783E+09 | 0.00 | 0.59 |
Minimum of Months | 10523510.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.230951E+10 | 0.317351E+09 | 0.00 | 2047984.84 | 87124769.02 | 54401699.37 | 0.281577E+09 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.189273E+09 | 1794004.69 | 0.00 | 0.106723E+09 | 0.00 | 0.00 | 0.672117E+11 | 0.00 | 23.66 |
February | 0.197018E+09 | 0.00 | 0.00 | 87431333.49 | 0.00 | 0.00 | 0.693773E+11 | 0.00 | 23.29 |
March | 0.176748E+09 | 17978883.33 | 0.00 | 0.108143E+09 | 0.00 | 0.00 | 0.610067E+11 | 0.00 | 23.90 |
April | 9659609.62 | 0.841420E+09 | 0.00 | 0.105844E+09 | 0.00 | 0.00 | 0.284957E+11 | 0.00 | 23.07 |
May | 0.00 | 0.187242E+10 | 0.00 | 92548839.75 | 0.00 | 0.00 | 0.187063E+11 | 0.00 | 22.23 |
June | 0.00 | 0.451910E+10 | 0.00 | 62614659.55 | 0.00 | 0.00 | 0.807421E+10 | 0.00 | 18.83 |
July | 0.00 | 0.934038E+10 | 0.00 | 32014244.13 | 0.00 | 0.00 | 0.372816E+10 | 0.00 | 18.44 |
August | 0.00 | 0.787861E+10 | 0.00 | 39931664.38 | 0.00 | 0.00 | 0.465971E+10 | 0.00 | 19.21 |
September | 0.00 | 0.725935E+10 | 0.00 | 50464587.89 | 0.00 | 0.00 | 0.763636E+10 | 0.00 | 20.75 |
October | 76670826.47 | 0.107225E+10 | 0.00 | 0.103949E+09 | 0.00 | 0.00 | 0.404823E+11 | 0.00 | 23.50 |
November | 0.160471E+09 | 23555199.39 | 0.00 | 0.103950E+09 | 0.00 | 0.00 | 0.602621E+11 | 0.00 | 23.94 |
December | 0.195082E+09 | 0.00 | 0.00 | 0.100203E+09 | 0.00 | 0.00 | 0.754422E+11 | 0.00 | 23.17 |
Annual Sum or Average | 0.100492E+10 | 0.328269E+11 | 0.00 | 0.993818E+09 | 0.00 | 0.00 | 0.445083E+12 | 0.00 | 21.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 32014244.13 | 0.00 | 0.00 | 0.372816E+10 | 0.00 | 18.44 |
Maximum of Months | 0.197018E+09 | 0.934038E+10 | 0.00 | 0.108143E+09 | 0.00 | 0.00 | 0.754422E+11 | 0.00 | 23.94 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.308455E+10 | 1235083.93 | 0.00 | 40491326.08 | 0.00 | 0.00 | 0.224688E+11 | 0.00 | 4.03 |
February | 0.805151E+10 | 0.00 | 0.00 | 15912804.35 | 0.00 | 0.00 | 0.176871E+11 | 0.00 | 3.60 |
March | 0.627357E+10 | 7993427.62 | 0.00 | 19930342.14 | 267366.87 | 0.00 | 0.162037E+11 | 0.00 | 3.64 |
April | 0.137521E+10 | 0.414733E+09 | 0.00 | 29833934.25 | 2033187.01 | 0.00 | 0.101915E+11 | 0.00 | 3.86 |
May | 0.510052E+09 | 0.794402E+09 | 0.00 | 24591549.77 | 21479789.44 | 0.00 | 0.754141E+10 | 0.00 | 3.72 |
June | 34268749.02 | 0.193435E+10 | 0.00 | 24213673.23 | 36796376.13 | 0.00 | 0.391912E+10 | 0.00 | 3.38 |
July | 9666264.46 | 0.374856E+10 | 0.00 | 14229935.04 | 0.115438E+09 | 0.00 | 0.179016E+10 | 0.00 | 3.30 |
August | 27313868.55 | 0.330306E+10 | 0.00 | 17090179.36 | 67687984.99 | 0.00 | 0.220908E+10 | 0.00 | 3.50 |
September | 84635140.70 | 0.308948E+10 | 0.00 | 19494074.31 | 66587322.35 | 0.00 | 0.344058E+10 | 0.00 | 3.83 |
October | 0.181136E+10 | 0.559066E+09 | 0.00 | 36517485.93 | 3674005.41 | 0.00 | 0.140567E+11 | 0.00 | 4.11 |
November | 0.237954E+10 | 1100032.44 | 0.00 | 35446095.81 | 9399951.57 | 0.00 | 0.205323E+11 | 0.00 | 3.99 |
December | 0.539865E+10 | 0.00 | 0.00 | 26902740.44 | 0.00 | 0.00 | 0.226136E+11 | 0.00 | 3.79 |
Annual Sum or Average | 0.290403E+11 | 0.138540E+11 | 0.00 | 0.304654E+09 | 0.323364E+09 | 0.00 | 0.142654E+12 | 0.00 | 3.73 |
Minimum of Months | 9666264.46 | 0.00 | 0.00 | 14229935.04 | 0.00 | 0.00 | 0.179016E+10 | 0.00 | 3.30 |
Maximum of Months | 0.805151E+10 | 0.374856E+10 | 0.00 | 40491326.08 | 0.115438E+09 | 0.00 | 0.226136E+11 | 0.00 | 4.11 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.170357E+11 | 2539033.84 | 0.00 | 74825185.48 | 0.00 | 0.00 | 0.662752E+11 | 0.00 | 1.76 |
February | 0.396367E+11 | 0.00 | 0.00 | 29441046.13 | 0.00 | 0.00 | 0.448940E+11 | 0.00 | 1.70 |
March | 0.263855E+11 | 6696071.00 | 0.00 | 49419264.07 | 18749232.18 | 0.00 | 0.485059E+11 | 0.00 | 1.74 |
April | 0.294616E+10 | 0.108735E+10 | 0.00 | 96972606.79 | 96430230.67 | 0.00 | 0.371084E+11 | 0.00 | 1.85 |
May | 0.563705E+09 | 0.236348E+10 | 0.00 | 98070687.36 | 0.229513E+09 | 0.00 | 0.279644E+11 | 0.00 | 1.85 |
June | 21470400.54 | 0.594967E+10 | 0.00 | 99883239.03 | 0.270777E+09 | 0.00 | 0.141680E+11 | 0.00 | 1.67 |
July | 2757033.68 | 0.123585E+11 | 0.00 | 56907590.59 | 0.548547E+09 | 0.00 | 0.647917E+10 | 0.00 | 1.63 |
August | 13346072.48 | 0.101905E+11 | 0.00 | 66611487.91 | 0.522488E+09 | 0.00 | 0.782469E+10 | 0.00 | 1.68 |
September | 85805747.14 | 0.970091E+10 | 0.00 | 72397767.94 | 0.362105E+09 | 0.00 | 0.122819E+11 | 0.00 | 1.81 |
October | 0.763440E+10 | 0.150964E+10 | 0.00 | 0.103120E+09 | 20999992.31 | 0.00 | 0.459876E+11 | 0.00 | 1.88 |
November | 0.131191E+11 | 2174683.08 | 0.00 | 74086742.98 | 31165319.08 | 0.00 | 0.619941E+11 | 0.00 | 1.79 |
December | 0.339122E+11 | 0.00 | 0.00 | 43333746.35 | 0.00 | 0.00 | 0.570911E+11 | 0.00 | 1.70 |
Annual Sum or Average | 0.141357E+12 | 0.431715E+11 | 0.00 | 0.865069E+09 | 0.210078E+10 | 0.00 | 0.430574E+12 | 0.00 | 1.76 |
Minimum of Months | 2757033.68 | 0.00 | 0.00 | 29441046.13 | 0.00 | 0.00 | 0.647917E+10 | 0.00 | 1.63 |
Maximum of Months | 0.396367E+11 | 0.123585E+11 | 0.00 | 0.103120E+09 | 0.548547E+09 | 0.00 | 0.662752E+11 | 0.00 | 1.88 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5070070.01 | 358710.98 | 14459.55 | 9250179.58 | 0.00 | 0.301460E+09 | 0.769108E+09 | 1719.46 | 0.35 |
February | 43568509.11 | 41223.64 | 0.00 | 3843727.97 | 0.00 | 0.549462E+09 | 0.498378E+09 | 0.00 | 0.36 |
March | 30414801.98 | 298251.43 | 0.00 | 7924409.54 | 0.00 | 0.354433E+09 | 0.648378E+09 | 0.00 | 0.36 |
April | 0.00 | 14033970.06 | 0.00 | 12558226.01 | 0.00 | 863675.98 | 0.538674E+09 | 259.56 | 0.35 |
May | 0.00 | 28708054.71 | 4524.02 | 11372326.86 | 0.00 | 251749.60 | 0.344107E+09 | 2704.23 | 0.35 |
June | 0.00 | 90486150.31 | 0.00 | 9078746.81 | 0.00 | 16156.59 | 0.104155E+09 | 52.08 | 0.36 |
July | 0.00 | 0.481276E+09 | 190858.13 | 2303242.46 | 0.00 | 7204.31 | 39270754.44 | 12764.65 | 0.36 |
August | 0.00 | 0.436386E+09 | 178425.20 | 1914516.04 | 0.00 | 41292.67 | 26182883.84 | 22746.44 | 0.36 |
September | 0.00 | 0.351201E+09 | 150857.47 | 3426891.51 | 0.00 | 60700.97 | 51042017.81 | 18134.03 | 0.36 |
October | 4254173.26 | 60948645.33 | 21332.52 | 10104440.72 | 0.00 | 69347976.05 | 0.592921E+09 | 5337.52 | 0.36 |
November | 7040006.47 | 4114261.59 | 1265.26 | 8521818.10 | 310079.10 | 0.221722E+09 | 0.719860E+09 | 2798.44 | 0.35 |
December | 26574236.91 | 0.00 | 0.00 | 4954528.25 | 401365.07 | 0.628734E+09 | 0.519079E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.116922E+09 | 0.146785E+10 | 561722.14 | 85253053.85 | 711444.17 | 0.212640E+10 | 0.485116E+10 | 66516.42 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1914516.04 | 0.00 | 7204.31 | 26182883.84 | 0.00 | 0.35 |
Maximum of Months | 43568509.11 | 0.481276E+09 | 190858.13 | 12558226.01 | 401365.07 | 0.628734E+09 | 0.769108E+09 | 22746.44 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.159204E+09 | 82471.43 | 12786.84 | 2758290.84 | 276197.51 | 0.559168E+09 | 0.363630E+09 | 3390.27 | 0.35 |
February | 0.142479E+09 | 41218.81 | 0.00 | 1351094.75 | 0.00 | 0.767222E+09 | 0.184072E+09 | 0.00 | 0.36 |
March | 0.199333E+09 | 298216.49 | 0.00 | 3695878.51 | 0.00 | 0.423826E+09 | 0.414173E+09 | 0.00 | 0.36 |
April | 95196532.91 | 13957903.98 | 2487.52 | 9542432.35 | 69485.03 | 641044.51 | 0.446652E+09 | 2708.78 | 0.35 |
May | 73305972.33 | 28698181.44 | 4267.57 | 8877120.00 | 3157.95 | 45676.09 | 0.273461E+09 | 6311.59 | 0.35 |
June | 27982158.02 | 90466309.08 | 0.00 | 7245590.41 | 9291.54 | 10769.41 | 77998586.17 | 0.00 | 0.36 |
July | 9194637.63 | 0.474604E+09 | 132435.21 | 1844607.24 | 6678788.99 | 0.00 | 30537084.51 | 8037.43 | 0.36 |
August | 7804957.79 | 0.421010E+09 | 189542.45 | 1309304.17 | 15314095.50 | 0.00 | 19021133.73 | 22102.40 | 0.36 |
September | 17264862.19 | 0.318556E+09 | 259854.97 | 2543167.54 | 32495693.57 | 3032.50 | 34712159.13 | 17420.90 | 0.36 |
October | 0.152068E+09 | 57682812.35 | 30513.62 | 5505795.31 | 3241016.78 | 0.119731E+09 | 0.399243E+09 | 13828.47 | 0.36 |
November | 0.182175E+09 | 2579469.61 | 4742.03 | 3109013.40 | 1839816.28 | 0.406150E+09 | 0.365597E+09 | 3857.61 | 0.36 |
December | 0.136620E+09 | 0.00 | 0.00 | 1317196.72 | 401318.04 | 0.889154E+09 | 0.152111E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.120263E+10 | 0.140798E+10 | 636630.19 | 49099491.23 | 60328861.17 | 0.316595E+10 | 0.276121E+10 | 77657.47 | 0.36 |
Minimum of Months | 7804957.79 | 0.00 | 0.00 | 1309304.17 | 0.00 | 0.00 | 19021133.73 | 0.00 | 0.35 |
Maximum of Months | 0.199333E+09 | 0.474604E+09 | 259854.97 | 9542432.35 | 32495693.57 | 0.889154E+09 | 0.446652E+09 | 22102.40 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 7735.34 | 0.00 | 7002149.49 | 0.00 | 0.00 | 0.671541E+09 | 0.00 | 0.02 |
February | 0.259380E+09 | 0.00 | 0.00 | 2284608.18 | 0.00 | 0.00 | 0.833219E+09 | 0.00 | 0.02 |
March | 0.150530E+09 | 0.00 | 0.00 | 2615466.77 | 0.00 | 0.00 | 0.578083E+09 | 0.00 | 0.02 |
April | 0.00 | 33023610.05 | 0.00 | 2680322.75 | 0.00 | 0.00 | 97270353.60 | 0.00 | 0.02 |
May | 0.00 | 57085898.46 | 0.00 | 1047163.40 | 0.00 | 0.00 | 15798481.57 | 0.00 | 0.02 |
June | 0.00 | 0.209012E+09 | 0.00 | 42869.40 | 0.00 | 0.00 | 135079.31 | 0.00 | 0.02 |
July | 0.00 | 0.312068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
August | 0.00 | 0.334504E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
September | 0.00 | 0.281709E+09 | 0.00 | 750633.68 | 0.00 | 0.00 | 5909090.99 | 0.00 | 0.02 |
October | 0.00 | 52022977.83 | 0.00 | 4494751.26 | 0.00 | 0.00 | 0.336408E+09 | 0.00 | 0.02 |
November | 8132998.50 | 981973.44 | 0.00 | 5295291.49 | 0.00 | 0.00 | 0.674230E+09 | 0.00 | 0.02 |
December | 44560601.64 | 0.00 | 0.00 | 5141808.41 | 0.00 | 0.00 | 0.818015E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.462604E+09 | 0.128042E+10 | 0.00 | 31355064.84 | 0.00 | 0.00 | 0.403061E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.259380E+09 | 0.334504E+09 | 0.00 | 7002149.49 | 0.00 | 0.00 | 0.833219E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.216010E+10 | 1118675.52 | 219208.48 | 40916131.41 | 3746453.58 | 0.885194E+09 | 0.116279E+11 | 224.31 | 0.40 |
February | 0.193264E+10 | 559108.40 | 0.00 | 33005753.09 | 0.00 | 0.599930E+09 | 0.122891E+11 | 0.00 | 0.40 |
March | 0.273423E+10 | 4016969.99 | 22935.59 | 59711185.78 | 0.00 | 0.559715E+09 | 0.107673E+11 | 5222.21 | 0.40 |
April | 0.133348E+10 | 0.179637E+09 | 1505170.59 | 85565624.27 | 8941690.81 | 6649924.74 | 0.606228E+10 | 259797.80 | 0.40 |
May | 0.100002E+10 | 0.388801E+09 | 474639.05 | 76919425.35 | 42835.74 | 819471.41 | 0.374696E+10 | 141817.93 | 0.40 |
June | 0.379561E+09 | 0.122698E+10 | 127848.08 | 60908063.70 | 126034.12 | 78088.69 | 0.109545E+10 | 14425.22 | 0.40 |
July | 0.124720E+09 | 0.643783E+10 | 1771503.44 | 14688903.52 | 90593765.99 | 1199.34 | 0.424548E+09 | 19767.66 | 0.40 |
August | 0.105870E+09 | 0.571107E+10 | 2460288.06 | 9828207.18 | 0.207727E+09 | 0.00 | 0.265942E+09 | 93694.17 | 0.40 |
September | 0.234187E+09 | 0.432049E+10 | 1518572.46 | 22386440.55 | 0.443529E+09 | 0.00 | 0.483001E+09 | 29480.21 | 0.40 |
October | 0.207678E+10 | 0.768261E+09 | 810859.05 | 63016015.91 | 57787427.66 | 43566942.53 | 0.699361E+10 | 137004.71 | 0.40 |
November | 0.249142E+10 | 34750651.96 | 86057.41 | 43071753.48 | 25212646.60 | 0.554087E+09 | 0.989298E+10 | 12254.98 | 0.40 |
December | 0.185317E+10 | 0.00 | 0.00 | 22384819.31 | 5443638.48 | 0.428542E+10 | 0.983421E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.164262E+11 | 0.190735E+11 | 8997082.22 | 0.532402E+09 | 0.843150E+09 | 0.693546E+10 | 0.734833E+11 | 713689.20 | 0.40 |
Minimum of Months | 0.105870E+09 | 0.00 | 0.00 | 9828207.18 | 0.00 | 0.00 | 0.265942E+09 | 0.00 | 0.40 |
Maximum of Months | 0.273423E+10 | 0.643783E+10 | 2460288.06 | 85565624.27 | 0.443529E+09 | 0.428542E+10 | 0.122891E+11 | 259797.80 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4800030.96 | 358710.98 | 12509.04 | 9207640.07 | 0.00 | 0.321407E+09 | 0.749473E+09 | 3669.97 | 0.35 |
February | 31472089.04 | 41223.64 | 0.00 | 4560419.33 | 0.00 | 0.502664E+09 | 0.556556E+09 | 0.00 | 0.36 |
March | 23238773.78 | 298251.43 | 0.00 | 8442240.20 | 0.00 | 0.323362E+09 | 0.686107E+09 | 0.00 | 0.36 |
April | 0.00 | 14034229.62 | 0.00 | 13752457.67 | 0.00 | 153576.98 | 0.538190E+09 | 0.00 | 0.35 |
May | 0.00 | 28715282.96 | 0.00 | 12761067.25 | 0.00 | 13652.61 | 0.342957E+09 | 0.00 | 0.35 |
June | 0.00 | 90486202.40 | 0.00 | 9625627.24 | 0.00 | 0.00 | 0.103625E+09 | 0.00 | 0.36 |
July | 0.00 | 0.481480E+09 | 0.00 | 2361516.09 | 0.00 | 0.00 | 39219685.13 | 0.00 | 0.36 |
August | 0.00 | 0.436587E+09 | 0.00 | 1873039.06 | 0.00 | 40316.90 | 26225336.60 | 0.00 | 0.36 |
September | 0.00 | 0.351323E+09 | 45517.14 | 3521882.91 | 0.00 | 0.00 | 51007727.39 | 820.30 | 0.36 |
October | 675509.48 | 60975315.36 | 0.00 | 10738227.69 | 0.00 | 73856719.01 | 0.591357E+09 | 0.00 | 0.36 |
November | 7302457.26 | 4110007.28 | 6254.48 | 8542470.96 | 310079.10 | 0.255477E+09 | 0.685822E+09 | 2063.53 | 0.35 |
December | 24715528.49 | 0.00 | 0.00 | 5414086.87 | 401365.07 | 0.618969E+09 | 0.530242E+09 | 0.00 | 0.35 |
Annual Sum or Average | 92204389.00 | 0.146841E+10 | 64280.65 | 90800675.33 | 711444.17 | 0.209594E+10 | 0.490078E+10 | 6553.80 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1873039.06 | 0.00 | 0.00 | 26225336.60 | 0.00 | 0.35 |
Maximum of Months | 31472089.04 | 0.481480E+09 | 45517.14 | 13752457.67 | 401365.07 | 0.618969E+09 | 0.749473E+09 | 3669.97 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.159544E+09 | 82471.43 | 13301.85 | 3095267.43 | 276197.51 | 0.550768E+09 | 0.371354E+09 | 2875.26 | 0.35 |
February | 0.142829E+09 | 41218.81 | 0.00 | 1801841.77 | 0.00 | 0.652332E+09 | 0.298161E+09 | 0.00 | 0.36 |
March | 0.195639E+09 | 296979.21 | 0.00 | 4612943.04 | 0.00 | 0.376121E+09 | 0.464655E+09 | 1237.28 | 0.36 |
April | 92631289.88 | 14001029.99 | 3643.11 | 10060766.29 | 26436.59 | 428645.89 | 0.448911E+09 | 1475.62 | 0.35 |
May | 71512921.72 | 28708760.59 | 0.00 | 9102746.14 | 3157.95 | 5438.76 | 0.275069E+09 | 0.00 | 0.35 |
June | 27361563.98 | 90466309.08 | 0.00 | 7283503.28 | 9291.54 | 0.00 | 78592036.74 | 0.00 | 0.36 |
July | 9136614.85 | 0.474828E+09 | 0.00 | 1814726.54 | 6595277.27 | 0.00 | 30624987.99 | 0.00 | 0.36 |
August | 7788109.76 | 0.421378E+09 | 18930.71 | 1217985.89 | 15139010.13 | 0.00 | 19129300.04 | 43.08 | 0.36 |
September | 17193383.81 | 0.319313E+09 | 128740.46 | 2506913.48 | 31882704.46 | 2506.96 | 34820417.10 | 4065.15 | 0.36 |
October | 0.149830E+09 | 57857749.43 | 2875.15 | 5993416.67 | 3104458.58 | 0.114635E+09 | 0.406091E+09 | 3088.06 | 0.36 |
November | 0.182172E+09 | 2579469.61 | 4473.14 | 3166251.58 | 1839816.28 | 0.407000E+09 | 0.364693E+09 | 4126.50 | 0.36 |
December | 0.136620E+09 | 0.00 | 0.00 | 1299442.04 | 401318.04 | 0.835905E+09 | 0.205379E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.119226E+10 | 0.140955E+10 | 171964.42 | 51955804.15 | 59277668.36 | 0.293720E+10 | 0.299748E+10 | 16910.95 | 0.36 |
Minimum of Months | 7788109.76 | 0.00 | 0.00 | 1217985.89 | 0.00 | 0.00 | 19129300.04 | 0.00 | 0.35 |
Maximum of Months | 0.195639E+09 | 0.474828E+09 | 128740.46 | 10060766.29 | 31882704.46 | 0.835905E+09 | 0.464655E+09 | 4126.50 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.218090E+11 | 0.00 | 0.00 | 0.00 | 692079.28 | 0.00 | 0.00 | 0.00 | 0.50 |
February | 0.228670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
March | 0.200244E+11 | 0.00 | 0.00 | 0.00 | 6935774.88 | 0.00 | 0.00 | 0.00 | 0.50 |
April | 0.936729E+10 | 15589598.28 | 0.00 | 621792.55 | 0.306641E+09 | 0.00 | 0.256955E+09 | 0.00 | 0.49 |
May | 0.487092E+10 | 0.177688E+09 | 0.00 | 4340943.21 | 0.525987E+09 | 0.00 | 0.164428E+10 | 0.00 | 0.48 |
June | 0.253585E+09 | 0.170406E+10 | 0.00 | 17081124.30 | 0.101420E+09 | 0.00 | 0.285089E+10 | 0.00 | 0.46 |
July | 0.134132E+09 | 0.290343E+10 | 0.00 | 8979421.07 | 0.415347E+09 | 0.00 | 0.128909E+10 | 0.00 | 0.43 |
August | 0.385024E+09 | 0.223251E+10 | 0.00 | 9390724.09 | 0.555480E+09 | 0.00 | 0.133339E+10 | 0.00 | 0.44 |
September | 0.911836E+09 | 0.165225E+10 | 0.00 | 7451369.38 | 0.868597E+09 | 0.00 | 0.177539E+10 | 0.00 | 0.47 |
October | 0.124468E+11 | 0.276186E+09 | 0.00 | 2509748.36 | 0.122025E+09 | 0.00 | 0.828587E+09 | 0.00 | 0.51 |
November | 0.195276E+11 | 0.00 | 0.00 | 0.00 | 9086969.27 | 0.00 | 0.00 | 0.00 | 0.51 |
December | 0.244529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.137050E+12 | 0.896171E+10 | 0.00 | 50375122.97 | 0.291221E+10 | 0.00 | 0.997858E+10 | 0.00 | 0.48 |
Minimum of Months | 0.134132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.244529E+11 | 0.290343E+10 | 0.00 | 17081124.30 | 0.868597E+09 | 0.00 | 0.285089E+10 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1398344.26 | 89677.74 | 3682.11 | 2106183.01 | 0.00 | 0.127029E+09 | 0.140689E+09 | 362.64 | 0.35 |
February | 10526715.20 | 10305.91 | 0.00 | 896622.85 | 0.00 | 0.173843E+09 | 88546610.76 | 0.00 | 0.36 |
March | 7565075.21 | 74562.86 | 0.00 | 1890875.86 | 0.00 | 0.120728E+09 | 0.130104E+09 | 0.00 | 0.36 |
April | 0.00 | 3508492.52 | 0.00 | 2929626.33 | 0.00 | 3228202.57 | 0.131866E+09 | 64.89 | 0.35 |
May | 0.00 | 7177013.68 | 200.19 | 2632847.76 | 0.00 | 65385.59 | 86234623.44 | 1606.88 | 0.35 |
June | 0.00 | 22621537.58 | 0.00 | 2167407.62 | 0.00 | 5939.56 | 26139246.05 | 13.02 | 0.36 |
July | 0.00 | 0.120326E+09 | 40343.36 | 543873.93 | 0.00 | 2583.42 | 9848842.96 | 3549.60 | 0.36 |
August | 0.00 | 0.109096E+09 | 44924.48 | 452114.78 | 0.00 | 10901.65 | 6571656.71 | 6090.62 | 0.36 |
September | 0.00 | 87809280.42 | 27477.81 | 792114.30 | 0.00 | 19324.50 | 12820963.77 | 5699.70 | 0.36 |
October | 1575045.11 | 15237161.33 | 4854.21 | 2257112.81 | 0.00 | 40313725.59 | 0.125011E+09 | 1813.30 | 0.36 |
November | 2685508.88 | 1029151.44 | 67.90 | 1893517.50 | 77519.77 | 96880527.40 | 0.137826E+09 | 361.98 | 0.35 |
December | 7083635.02 | 0.00 | 0.00 | 1121667.01 | 100341.27 | 0.192501E+09 | 94129430.62 | 0.00 | 0.35 |
Annual Sum or Average | 30834323.67 | 0.366979E+09 | 121550.07 | 19683963.77 | 177861.04 | 0.754627E+09 | 0.989788E+09 | 19562.61 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 452114.78 | 0.00 | 2583.42 | 6571656.71 | 0.00 | 0.35 |
Maximum of Months | 10526715.20 | 0.120326E+09 | 44924.48 | 2929626.33 | 100341.27 | 0.192501E+09 | 0.140689E+09 | 6090.62 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 39804205.60 | 20617.86 | 3207.32 | 582302.71 | 69049.38 | 0.184241E+09 | 46562257.75 | 836.96 | 0.35 |
February | 35688957.55 | 0.00 | 10291.78 | 299105.73 | 0.00 | 0.210093E+09 | 27699435.07 | 12.92 | 0.36 |
March | 49743353.44 | 74554.12 | 0.00 | 835489.34 | 0.00 | 0.134215E+09 | 75463057.93 | 0.00 | 0.36 |
April | 23525280.15 | 3488741.56 | 0.00 | 2240225.63 | 17371.26 | 2243818.42 | 0.109999E+09 | 2033.51 | 0.35 |
May | 18326493.08 | 7174555.89 | 1289.84 | 2100473.45 | 789.49 | 15511.97 | 68479958.50 | 1344.42 | 0.35 |
June | 6995539.50 | 22616577.27 | 0.00 | 1763540.27 | 2322.88 | 4923.07 | 19545273.16 | 0.00 | 0.36 |
July | 2298659.41 | 0.118655E+09 | 27865.05 | 445354.17 | 1669697.25 | 383.38 | 7649685.39 | 3308.07 | 0.36 |
August | 1951239.45 | 0.105260E+09 | 40238.52 | 314639.79 | 3828523.87 | 0.00 | 4767969.69 | 5768.03 | 0.36 |
September | 4316215.55 | 79639227.85 | 60007.52 | 593498.09 | 8123923.39 | 5097.77 | 8715993.93 | 9007.14 | 0.36 |
October | 38087140.42 | 14399863.13 | 7177.00 | 1178346.38 | 830678.12 | 53939128.61 | 75932485.16 | 4324.55 | 0.36 |
November | 45555269.83 | 645523.28 | 952.12 | 631359.67 | 459954.07 | 0.133810E+09 | 59261378.03 | 541.91 | 0.36 |
December | 34248730.61 | 0.00 | 0.00 | 272564.45 | 100329.51 | 0.242026E+09 | 18253095.55 | 0.00 | 0.35 |
Annual Sum or Average | 0.300541E+09 | 0.351974E+09 | 151029.16 | 11256899.69 | 15102639.22 | 0.960595E+09 | 0.522329E+09 | 27177.52 | 0.36 |
Minimum of Months | 1951239.45 | 0.00 | 0.00 | 272564.45 | 0.00 | 0.00 | 4767969.69 | 0.00 | 0.35 |
Maximum of Months | 49743353.44 | 0.118655E+09 | 60007.52 | 2240225.63 | 8123923.39 | 0.242026E+09 | 0.109999E+09 | 9007.14 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 602119.17 | 0.00 | 23019973.18 | 0.00 | 96900320.57 | 0.162254E+10 | 0.00 | 0.40 |
February | 22950992.62 | 66210.21 | 0.00 | 11018064.23 | 0.00 | 0.386649E+09 | 0.133849E+10 | 0.00 | 0.41 |
March | 14873218.61 | 479028.29 | 0.00 | 14308326.53 | 0.00 | 0.326875E+09 | 0.131616E+10 | 0.00 | 0.40 |
April | 0.00 | 22540272.77 | 0.00 | 16471873.03 | 0.00 | 6161490.04 | 0.864101E+09 | 416.89 | 0.40 |
May | 0.00 | 46119078.45 | 0.00 | 13977348.64 | 0.00 | 413490.66 | 0.556957E+09 | 1178.89 | 0.40 |
June | 0.00 | 0.145324E+09 | 4383.94 | 10912222.85 | 0.00 | 62694.83 | 0.170919E+09 | 3307.68 | 0.40 |
July | 0.00 | 0.772501E+09 | 780348.05 | 2734857.15 | 0.00 | 14556.67 | 64035082.19 | 34177.13 | 0.40 |
August | 0.00 | 0.700487E+09 | 685025.85 | 2401159.84 | 0.00 | 66183.62 | 42726839.14 | 41221.92 | 0.40 |
September | 0.00 | 0.563976E+09 | 353736.10 | 4861343.32 | 0.00 | 46003.94 | 82673877.79 | 13146.66 | 0.40 |
October | 0.00 | 97878172.70 | 50124.52 | 17728426.77 | 0.00 | 42034068.65 | 0.102698E+10 | 5518.70 | 0.40 |
November | 1944964.46 | 6610320.08 | 1318.84 | 19542555.39 | 498024.97 | 0.118803E+09 | 0.139700E+10 | 2895.31 | 0.40 |
December | 3833059.37 | 0.00 | 0.00 | 16833909.22 | 644641.40 | 0.425298E+09 | 0.144820E+10 | 0.00 | 0.40 |
Annual Sum or Average | 43602235.06 | 0.235658E+10 | 1874937.30 | 0.153810E+09 | 1142666.37 | 0.140332E+10 | 0.993079E+10 | 101863.18 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2401159.84 | 0.00 | 14556.67 | 42726839.14 | 0.00 | 0.40 |
Maximum of Months | 22950992.62 | 0.772501E+09 | 780348.05 | 23019973.18 | 644641.40 | 0.425298E+09 | 0.162254E+10 | 41221.92 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.756370E+09 | 1196841.53 | 0.00 | 67127738.31 | 0.00 | 0.00 | 0.433104E+11 | 0.00 | 4.64 |
February | 0.995122E+09 | 0.00 | 0.00 | 53443774.59 | 0.00 | 0.00 | 0.437577E+11 | 0.00 | 4.53 |
March | 0.554711E+09 | 12285474.66 | 0.00 | 71654753.19 | 0.00 | 0.00 | 0.406916E+11 | 0.00 | 4.79 |
April | 26964835.89 | 0.626036E+09 | 0.00 | 79876402.22 | 93881.62 | 0.00 | 0.226192E+11 | 0.00 | 5.20 |
May | 0.00 | 0.143244E+10 | 0.00 | 76179363.45 | 0.00 | 0.00 | 0.163142E+11 | 0.00 | 5.27 |
June | 0.00 | 0.351439E+10 | 0.00 | 59607391.82 | 0.00 | 0.00 | 0.783554E+10 | 0.00 | 4.72 |
July | 0.00 | 0.705153E+10 | 0.00 | 32879508.42 | 0.00 | 0.00 | 0.356062E+10 | 0.00 | 4.58 |
August | 0.00 | 0.576611E+10 | 0.00 | 39134804.74 | 0.00 | 0.00 | 0.428351E+10 | 0.00 | 4.67 |
September | 0.00 | 0.536564E+10 | 0.00 | 43871537.18 | 0.00 | 0.00 | 0.673831E+10 | 0.00 | 4.96 |
October | 0.252633E+09 | 0.775133E+09 | 0.00 | 74802056.79 | 0.00 | 0.00 | 0.287079E+11 | 0.00 | 5.05 |
November | 0.458616E+09 | 15741389.90 | 0.00 | 66680779.75 | 4352.83 | 0.00 | 0.393867E+11 | 0.00 | 4.76 |
December | 0.175381E+10 | 0.00 | 0.00 | 55939556.18 | 0.00 | 0.00 | 0.453833E+11 | 0.00 | 4.42 |
Annual Sum or Average | 0.479823E+10 | 0.245605E+11 | 0.00 | 0.721198E+09 | 98234.44 | 0.00 | 0.302589E+12 | 0.00 | 4.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 32879508.42 | 0.00 | 0.00 | 0.356062E+10 | 0.00 | 4.42 |
Maximum of Months | 0.175381E+10 | 0.705153E+10 | 0.00 | 79876402.22 | 93881.62 | 0.00 | 0.453833E+11 | 0.00 | 5.27 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.250847E+09 | 1260515.11 | 0.00 | 81162284.72 | 0.00 | 0.00 | 0.476592E+11 | 0.00 | 5.03 |
February | 0.237066E+09 | 0.00 | 0.00 | 66471465.52 | 0.00 | 0.00 | 0.486528E+11 | 0.00 | 4.94 |
March | 0.144352E+09 | 13481084.40 | 0.00 | 85655453.31 | 0.00 | 0.00 | 0.447672E+11 | 0.00 | 5.21 |
April | 4021906.74 | 0.680100E+09 | 0.00 | 88813966.78 | 0.00 | 0.00 | 0.241442E+11 | 0.00 | 5.57 |
May | 0.00 | 0.154443E+10 | 0.00 | 81908910.48 | 0.00 | 0.00 | 0.172285E+11 | 0.00 | 5.61 |
June | 0.00 | 0.375659E+10 | 0.00 | 62829538.60 | 0.00 | 0.00 | 0.820170E+10 | 0.00 | 5.00 |
July | 0.00 | 0.750765E+10 | 0.00 | 34603743.33 | 0.00 | 0.00 | 0.373057E+10 | 0.00 | 4.84 |
August | 0.00 | 0.615838E+10 | 0.00 | 41283870.30 | 0.00 | 0.00 | 0.449369E+10 | 0.00 | 4.95 |
September | 0.00 | 0.572373E+10 | 0.00 | 46936940.53 | 0.00 | 0.00 | 0.708973E+10 | 0.00 | 5.27 |
October | 82408591.03 | 0.829607E+09 | 0.00 | 84554781.01 | 0.00 | 0.00 | 0.310505E+11 | 0.00 | 5.42 |
November | 0.159450E+09 | 16564273.28 | 0.00 | 80030368.62 | 0.00 | 0.00 | 0.431321E+11 | 0.00 | 5.16 |
December | 0.774425E+09 | 0.00 | 0.00 | 70882248.99 | 0.00 | 0.00 | 0.506959E+11 | 0.00 | 4.81 |
Annual Sum or Average | 0.165257E+10 | 0.262318E+11 | 0.00 | 0.825134E+09 | 0.00 | 0.00 | 0.330846E+12 | 0.00 | 5.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 34603743.33 | 0.00 | 0.00 | 0.373057E+10 | 0.00 | 4.81 |
Maximum of Months | 0.774425E+09 | 0.750765E+10 | 0.00 | 88813966.78 | 0.00 | 0.00 | 0.506959E+11 | 0.00 | 5.61 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 2278679.47 | 0.00 | 0.123184E+09 | 0.00 | 0.00 | 0.556009E+11 | 0.00 | 21.70 |
February | 0.00 | 0.00 | 0.00 | 99816941.82 | 0.00 | 0.00 | 0.602926E+11 | 0.00 | 21.28 |
March | 0.00 | 22964560.52 | 0.00 | 0.121820E+09 | 0.00 | 0.00 | 0.510676E+11 | 0.00 | 21.83 |
April | 0.00 | 0.110695E+10 | 0.00 | 0.112008E+09 | 0.00 | 0.00 | 0.230227E+11 | 0.00 | 21.63 |
May | 0.00 | 0.241736E+10 | 0.00 | 95503598.72 | 0.00 | 0.00 | 0.148922E+11 | 0.00 | 21.07 |
June | 0.00 | 0.559752E+10 | 0.00 | 63853508.69 | 0.00 | 0.00 | 0.649591E+10 | 0.00 | 18.45 |
July | 0.00 | 0.101517E+11 | 0.00 | 33082736.21 | 0.00 | 0.00 | 0.298003E+10 | 0.00 | 18.17 |
August | 0.00 | 0.888620E+10 | 0.00 | 40399321.52 | 0.00 | 0.00 | 0.370274E+10 | 0.00 | 18.73 |
September | 0.00 | 0.772082E+10 | 0.00 | 51536984.84 | 0.00 | 0.00 | 0.616893E+10 | 0.00 | 19.93 |
October | 0.00 | 0.125260E+10 | 0.00 | 0.112929E+09 | 0.00 | 0.00 | 0.335249E+11 | 0.00 | 21.83 |
November | 0.00 | 27229812.42 | 0.00 | 0.118351E+09 | 0.00 | 0.00 | 0.504646E+11 | 0.00 | 21.92 |
December | 0.00 | 0.00 | 0.00 | 0.114145E+09 | 0.00 | 0.00 | 0.636115E+11 | 0.00 | 21.10 |
Annual Sum or Average | 0.00 | 0.371857E+11 | 0.00 | 0.108663E+10 | 0.00 | 0.00 | 0.371825E+12 | 0.00 | 20.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 33082736.21 | 0.00 | 0.00 | 0.298003E+10 | 0.00 | 18.17 |
Maximum of Months | 0.00 | 0.101517E+11 | 0.00 | 0.123184E+09 | 0.00 | 0.00 | 0.636115E+11 | 0.00 | 21.92 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.124832E+11 | 0.00 | 0.00 | 0.00 | 397483.89 | 42411276.65 | 0.00 | 0.00 | 1.09 |
February | 0.131332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 |
March | 0.114947E+11 | 0.00 | 0.00 | 4260.75 | 3983443.59 | 0.00 | 5939111.43 | 0.00 | 1.09 |
April | 0.488730E+10 | 0.178199E+09 | 0.00 | 2500854.20 | 23270757.36 | 0.00 | 0.641130E+09 | 0.00 | 1.08 |
May | 0.254455E+10 | 0.450330E+09 | 0.00 | 4807031.23 | 14981808.91 | 0.00 | 0.120180E+10 | 0.00 | 1.08 |
June | 0.293534E+09 | 0.132635E+10 | 0.00 | 8283409.56 | 482327.57 | 0.00 | 0.143215E+10 | 0.00 | 1.07 |
July | 0.166398E+09 | 0.217506E+10 | 0.00 | 4839084.41 | 44840368.64 | 0.00 | 0.630396E+09 | 0.00 | 1.03 |
August | 0.249447E+09 | 0.184201E+10 | 0.00 | 4807876.78 | 59484791.75 | 0.00 | 0.715090E+09 | 0.00 | 1.05 |
September | 0.623578E+09 | 0.137574E+10 | 0.00 | 4517517.39 | 0.227880E+09 | 0.00 | 0.908841E+09 | 0.00 | 1.07 |
October | 0.707817E+10 | 0.244264E+09 | 0.00 | 1788438.38 | 14560936.38 | 0.00 | 0.536989E+09 | 0.00 | 1.11 |
November | 0.112094E+11 | 74662.90 | 0.00 | 20212.29 | 5144282.37 | 0.00 | 5908393.12 | 0.00 | 1.10 |
December | 0.138012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242913E+09 | 0.00 | 0.00 | 1.08 |
Annual Sum or Average | 0.779648E+11 | 0.759203E+10 | 0.00 | 31568685.00 | 0.395026E+09 | 0.285324E+09 | 0.607824E+10 | 0.00 | 1.08 |
Minimum of Months | 0.166398E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 |
Maximum of Months | 0.138012E+11 | 0.217506E+10 | 0.00 | 8283409.56 | 0.227880E+09 | 0.242913E+09 | 0.143215E+10 | 0.00 | 1.11 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:03:03
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.147919E+12 | 0.146810E+11 | 0.907387E+11 | 0.424536E+12 | 0.281739E+12 |
February | 0.185161E+12 | 0.147859E+11 | 0.103141E+12 | 0.421095E+12 | 0.115926E+12 |
March | 0.246604E+12 | 0.137196E+11 | 0.865155E+11 | 0.393376E+12 | 0.256359E+12 |
April | 0.294133E+12 | 0.529601E+10 | 0.289627E+11 | 0.172222E+12 | 0.628966E+12 |
May | 0.299716E+12 | 0.249615E+10 | 0.915974E+10 | 0.914536E+11 | 0.801121E+12 |
June | 0.313723E+12 | -0.145121E+10 | -0.229294E+11 | -0.236074E+11 | 0.103486E+13 |
July | 0.298037E+12 | -0.608980E+10 | -0.441497E+11 | -0.147450E+12 | 0.114967E+13 |
August | 0.249687E+12 | -0.497054E+10 | -0.360300E+11 | -0.117672E+12 | 0.112084E+13 |
September | 0.210394E+12 | -0.313512E+10 | -0.205953E+11 | -0.664536E+11 | 0.101689E+13 |
October | 0.189950E+12 | 0.741678E+10 | 0.460637E+11 | 0.240424E+12 | 0.569375E+12 |
November | 0.160978E+12 | 0.130113E+11 | 0.833607E+11 | 0.389825E+12 | 0.292210E+12 |
December | 0.116746E+12 | 0.182925E+11 | 0.116604E+12 | 0.528634E+12 | 0.189438E+12 |
Annual Sum or Average | 0.271305E+13 | 0.740524E+11 | 0.440842E+12 | 0.230638E+13 | 0.745740E+13 |
Minimum of Months | 0.116746E+12 | -0.608980E+10 | -0.441497E+11 | -0.147450E+12 | 0.115926E+12 |
Maximum of Months | 0.313723E+12 | 0.182925E+11 | 0.116604E+12 | 0.528634E+12 | 0.114967E+13 |