Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860

Simulation Timestamp: 2023-10-16 09:02:50


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 9497.43 837.13 837.13
Net Site Energy 9497.43 837.13 837.13
Total Source Energy 22150.30 1952.38 1952.38
Net Source Energy 22150.30 1952.38 1952.38


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 884.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1150.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 603.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 174.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1728.14 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 641.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 550.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 120.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 188.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 489.84 1132.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 43.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 5691.35 3806.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 884.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 1150.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 603.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 174.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 952.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 8.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 4.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 22.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 616.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 550.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 120.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 188.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.75 1132.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
  Other 399.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 7.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 15.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 21.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 884.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 1150.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 603.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 174.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1728.14 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 641.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 550.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 120.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 188.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 489.84 1132.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 43.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 68.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 203.75 177.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 229.36 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 501.65 335.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 68.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 203.75 177.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 229.36 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 501.65 335.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 5691.350 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 5691.350 100.00
     
Total On-Site and Utility Electric Sources 5691.350 100.00
Total Electricity End Uses 5691.350 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 566.41 16.27
Air to Air Heat Recovery for Heating 2914.60 83.73
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 3481.01 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.33
Time Setpoint Not Met During Occupied Cooling 114.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 7904.33


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWHSYSLAUNDRY HPWH TANK | SWHSYS1 HPWH TANK |

DaylightingReportMonthly

| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| SWHSYS1 HPWH FAN | SWHSYSLAUNDRY HPWH FAN | FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02
RunPeriod RUNPERIOD 1
Weather File New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Latitude [deg] 40.65
Longitude [deg] -73.8
Elevation [m] 5.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 6.6442 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 9.6995 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 9.6995 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 4.6285 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 4.0903 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 5.7049 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 9.2569 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 9.0417 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 4.4132 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 4.4132 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 4.4132 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 4.4132 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 4.4132 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 9.2569 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 9.2569 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 11.7327 4.65 2931.5031
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 4.4132 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 5.8432 7.07 41.0437
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 5.8432 7.07 41.0437
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 6.6442 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 9.6995 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 9.6995 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 4.6285 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 4.0903 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 5.7049 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 9.2569 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 9.0417 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 4.4132 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 4.4132 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 4.4132 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 4.4132 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 4.4132 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 4.4132 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 4.4132 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 4.4132 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 4.4132 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 4.4132 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 9.2569 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 9.2569 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 11.7327 4.65 2931.5031  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 4.4132 18.58 0.0000  
Total 11345.29             5.8432 3.54 41.0437  
Conditioned Total 11345.29             5.8432 3.54 41.0437  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 3.6992 8.82 37.1717
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 04-AUG-19:19 06-FEB-19:10 - - - - - - - - - - 02-MAR-21:49
Heating 0.00 201199.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 194004.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 50471.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 11096.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 87982.85 87619.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 31577.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 31960.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 6619.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 38190.28 134072.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 1344.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 463186.21 422891.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 201199.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 194004.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 50471.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 11096.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 58308.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 49984.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 277.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 156.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 37635.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1274.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 30153.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 150.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 31960.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 6619.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 3915.94 134072.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 241.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 431.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 671.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 959.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 3644.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1911.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 551.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5473.02 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2031.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1742.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 382.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 597.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 1551.32 1227.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 138.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 18024.51 4125.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 84.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 321.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 168.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 48.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 482.40 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 179.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 153.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 33.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 52.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 136.74 108.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 12.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1588.72 363.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 84.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 321.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 168.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 48.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 482.40 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 179.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 153.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 33.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 52.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 136.74 108.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 12.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1588.72 363.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.08 0.724871 0.559000 1.16 1.00 0.500000 0.000526 0.000070 1.16 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.352101 0.145153 0.559000 0.196825 0.559000 0.500000 0.002625 0.000032 0.196825 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.217343 0.272305 0.559000 0.121495 0.726148 0.500000 0.001399 0.000014 0.121495 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.183871 0.680660 0.559000 0.102784 1.00 0.500000 0.000560 0.000020 0.102784 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.098915 0.729984 0.559000 0.055294 1.00 0.500000 0.000522 0.000012 0.055294 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.26 0.072475 0.559000 1.82 0.559000 0.500000 0.020861 0.000103 1.82 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.50 0.095986 0.559000 0.838113 0.559000 0.500000 0.003969 0.000097 0.838113 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 4.68 0.213050 0.559000 2.62 0.568134 0.500000 0.001788 0.000261 2.62 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.24 0.959337 0.559000 0.691603 1.00 0.500000 0.000397 0.000118 0.691603 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.13 0.118565 0.559000 1.19 0.559000 0.500000 0.003213 0.000109 1.19 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.24 0.112957 0.559000 1.25 0.559000 0.500000 0.003373 0.000113 1.25 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.17 0.065109 0.559000 1.22 0.559000 0.500000 0.010525 0.000080 1.22 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.696363 0.450970 0.559000 0.389267 1.00 0.500000 0.000845 0.000074 0.389267 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 8003.05 0.000070 169.57
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 3701.89 0.000032 89.24
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1549.89 0.000014 34.90
MECH_FLR_1 VAV BOX REHEAT COIL 2232.61 0.000020 55.74
STORAGE_FLR_1 VAV BOX REHEAT COIL 1383.48 0.000012 36.00
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 11777.97 0.000103 248.53
CAFE_FLR_1 VAV BOX REHEAT COIL 11124.43 0.000097 251.92
LOBBY_FLR_1 VAV BOX REHEAT COIL 29854.88 0.000261 662.74
ROOM_1_FLR_3 FAN COIL HEATING COIL 6056.01 0.000053 173.03
ROOM_2_FLR_3 FAN COIL HEATING COIL 6073.59 0.000053 173.53
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 34770.54 0.000304 993.44
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 35110.71 0.000307 1003.16
ROOM_5_FLR_3 FAN COIL HEATING COIL 6020.24 0.000053 172.01
ROOM_6_FLR_3 FAN COIL HEATING COIL 6037.84 0.000053 172.51
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 13467.55 0.000118 327.20
ROOM_1_FLR_6 FAN COIL HEATING COIL 1866.09 0.000016 53.32
ROOM_2_FLR_6 FAN COIL HEATING COIL 1871.97 0.000016 53.48
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 8900.14 0.000078 254.29
BANQUET_FLR_6 VAV BOX REHEAT COIL 12419.55 0.000109 272.83
DINING_FLR_6 VAV BOX REHEAT COIL 12879.23 0.000113 282.59
KITCHEN_FLR_6 VAV BOX REHEAT COIL 9116.72 0.000080 194.37
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 8453.95 0.000074 211.04
VAV WITH REHEAT HEATING COIL 206143.07 0.001803 3402.47
FLR_3_DOAS HEATING COIL 20393.42 0.000178 336.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ZoneExhaust

User-Specified Maximum Flow Rate [m3/s]
LOBBY_FLR_1 EXHAUST FAN 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 1.05 0.000053 0.000419
ROOM_2_FLR_3 FAN COIL 1.01 0.000053 0.000407
ROOM_3_MULT19_FLR_3 FAN COIL 6.12 0.000304 0.002402
ROOM_4_MULT19_FLR_3 FAN COIL 5.49 0.000307 0.002311
ROOM_5_FLR_3 FAN COIL 0.957161 0.000053 0.000384
ROOM_6_FLR_3 FAN COIL 0.929662 0.000053 0.000374
ROOM_1_FLR_6 FAN COIL 0.276262 0.000016 0.000111
ROOM_2_FLR_6 FAN COIL 0.267172 0.000016 0.000107
ROOM_3_MULT9_FLR_6 FAN COIL 1.28 0.000078 0.000521
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 1.05
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 1.01
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 6.12
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 5.49
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 0.957161
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 0.929662
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.276262
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.267172
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 1.28
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008599 12.80 0.008500 0.000419 1.05  
ROOM_2_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008602 12.80 0.008500 0.000407 1.01  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008526 12.80 0.008500 0.002402 6.12  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008784 12.80 0.008500 0.002311 5.49  
ROOM_5_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008608 12.80 0.008500 0.000384 0.957161  
ROOM_6_FLR_3 FAN COIL COOLING COIL 21.68 6.70 0.008612 12.80 0.008500 0.000374 0.929662  
ROOM_1_FLR_6 FAN COIL COOLING COIL 21.68 6.70 0.008594 12.80 0.008500 0.000111 0.276262  
ROOM_2_FLR_6 FAN COIL COOLING COIL 21.68 6.70 0.008597 12.80 0.008500 0.000107 0.267172  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21.68 6.70 0.008656 12.80 0.008500 0.000521 1.28  
VAV WITH REHEAT COOLING COIL 28.55 6.70 0.012195 10.99 0.008500 0.024395 20.74 683001.78
FLR_3_DOAS COOLING COIL 32.10 6.70 0.014120 11.94 0.008500 0.003084 2.05 86334.71
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 11.65 11.65 20.84 11.65 20.74 20.74 0.300000 0.561917 20.74
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 20.74  
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV WITH REHEAT OA HEAT RECOVERY 11.66
FLR_3_DOAS OA HEAT RECOVERY 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 20.74
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.024395 0.000020
VAV WITH REHEAT_HEATC_CONTROLLER 0.001803  
FLR_3_DOAS_COOLC_CONTROLLER 0.003084 0.000154
FLR_3_DOAS_HEATC_CONTROLLER 0.000178  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:WaterHeating:AirToWaterHeatPump:Pumped

Design Size Rated Evaporator Air Flow Rate [m3/s] Design Size Rated Condenser Water Flow Rate [m3/s]
SWHSYSLAUNDRY HPWH DXCOIL 4.90 0.004370
SWHSYS1 HPWH DXCOIL 3.87 0.003451
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:SystemModel

Design Size Design Maximum Air Flow Rate [m3/s] Design Electric Power Consumption [W]
SWHSYSLAUNDRY HPWH FAN 4.90 700.51
SWHSYS1 HPWH FAN 3.87 553.22
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:HeatPump:PumpedCondenser

Condenser water flow rate [m3/s] Evaporator air flow rate [m3/s]
SWHSYS1 HPWH 0.003451 3.87
SWHSYSLAUNDRY HPWH 0.004370 4.90
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.034515 7041.81  
HEATSYS1 PUMP 0.004017 1197.87 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.004017 0.482083
COOLSYS1 0.034515 4.14
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 459208.84 459208.84 0.004017
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.034515 4875.28
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.034515 966322.88 966907.44 110.23
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Stratified

Use Side Design Flow Rate [m3/s]
SWHSYS1 HPWH TANK 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 14.00 7.30 3.30 1.20 -0.20 5.60 10.90 16.10 21.70 25.00 24.80 19.90


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 40.65 -73.80 -5.00 5.00 101265 1.2036


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 12.47 25.20 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 6.644 5.380 0.000 0.000 0.000 0.000 12.024 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 9.699 10.760 0.000 0.000 0.000 0.000 20.459 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 9.699 10.760 0.000 0.000 0.000 0.000 20.459 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 4.628 5.380 0.000 0.000 0.000 0.000 10.008 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 4.090 2.690 0.000 0.000 0.000 0.000 6.780 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 5.705 61.680 535.850 0.000 0.000 0.000 603.235 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 9.257 5.380 0.000 0.000 0.000 0.000 14.637 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 9.042 8.070 0.000 0.000 0.000 0.000 17.112 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 4.413 10.520 0.000 0.000 0.000 0.000 14.933 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 4.413 10.520 0.000 0.000 0.000 0.000 14.933 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 4.413 0.000 0.000 0.000 0.000 0.000 4.413 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 4.413 6.750 0.000 0.000 0.000 0.000 11.163 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 4.413 10.520 0.000 0.000 0.000 0.000 14.933 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 9.257 67.820 0.000 0.000 0.000 0.000 77.077 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 9.257 67.820 0.000 0.000 0.000 0.000 77.077 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 11.733 512.243 2419.260 0.000 0.000 0.000 2943.236 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 4.413 0.000 0.000 0.000 0.000 0.000 4.413 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 13147.704 6.644 123.454 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 13147.704
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 650.557 9.699 60.075 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 650.557
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 753.347 9.699 60.076 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 753.347
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 760.196 4.628 286.650 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 760.196
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 387.592 4.090 189.996 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 387.592
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 445.205 5.705 53.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 445.205
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 1748.285 9.257 12.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1748.285
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 11828.200 9.042 28.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 11828.200
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 172.212 4.413 114.808 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.212
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 172.192 4.413 114.795 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.192
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 108.229 4.413 72.152 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 108.229
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 108.258 4.413 72.172 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 108.258
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 172.212 4.413 114.808 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.212
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 172.192 4.413 114.795 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.192
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 1718.521 4.413 82.002 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1718.521
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 172.212 4.413 114.808 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.212
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 172.192 4.413 114.795 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 172.192
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 108.258 4.413 72.172 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 108.258
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 3070.136 9.257 12.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3070.136
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 3070.136 9.257 12.286 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3070.136
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1212.035 11.733 54.503 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1212.035
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 1818.789 4.413 82.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1818.789


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 277.500 2.686 12.479 0.000 0.250 0.000 0.750 ReachInFreezer 277.500 277.500
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 156.700 1.517 7.046 0.000 0.250 0.000 0.750 ReachInRefrigerator 156.700 156.700


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.760 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.1864 0.900 0.900 0.770 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.1864 0.900 0.900 0.770 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 0.9242 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 1.217 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 1.286 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 1.107 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 1.174 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.5681
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.9147
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.6546
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.6103
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.7359
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.6841
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.312
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.312
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 2.312
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.312
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.7602615 1.7602615 1.7602615  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
21 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
22 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
23 0 21.357363 0.71091016E-01 5.4032014  
24 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
25 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
26 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
27 0 21.357363 0.71091016E-01 5.4032014  
28 9 -0.28612306E-14 0.35438919E-16 -0.14997333E-09 0.48037931E-16
29 8 0.21910456E-07 0.12451452E-12 0.37817107E-03 -0.24912943E-09
30 7 -0.12252860E-01 0.64616398E-08 -0.23102096E-01 0.13931948E-03
31 6 0.40565756 0.22511349E-05 0.47235308 -0.47513834E-02
32 5 -5.1935619 0.84157732E-04 -4.4432762 0.63221026E-01
33 4 33.016121 0.68920660E-03 21.448225 -0.42229901
34 3 -111.25447 0.15035857E-02 -55.639617 1.5156026
35 2 197.15924 0.84653085E-03 77.889127 -2.9011628
36 1 -171.17492 0.90445513E-04 -55.258822 2.7457697
37 0 57.057407 0.51539406E-06 15.557951  
38 9 0.12430042E-14 0.43603463E-16 -0.13615479E-09 -0.52742981E-17
39 8 0.19963588E-07 0.16114398E-12 0.35741204E-03 -0.22699287E-09
40 7 -0.11632381E-01 0.85488282E-08 -0.22208377E-01 0.13226440E-03
41 6 0.38879653 0.30047059E-05 0.45796739 -0.45526330E-02
42 5 -5.0290001 0.11318598E-03 -4.3326723 0.61180550E-01
43 4 32.288109 0.93328928E-03 21.015642 -0.41263319
44 3 -109.70522 0.20484795E-02 -54.784283 1.4932205
45 2 195.62339 0.11595496E-02 77.105128 -2.8767741
46 1 -170.60747 0.12450863E-03 -55.031726 2.7358244
47 0 57.057407 0.71328115E-06 15.596176  
48 9 0.10418955E-14 0.45554749E-16 -0.13285794E-09 -0.34221686E-17
49 8 0.19498290E-07 0.16949498E-12 0.35235048E-03 -0.22170227E-09
50 7 -0.11480752E-01 0.90423087E-08 -0.21989859E-01 0.13054032E-03
51 6 0.38467563 0.31853038E-05 0.45444290 -0.45040579E-02
52 5 -4.9887746 0.12022067E-03 -4.3055366 0.60681782E-01
53 4 32.110117 0.99300969E-03 20.909427 -0.41027004
54 3 -109.32633 0.21828955E-02 -54.574228 1.4877470
55 2 195.24766 0.12373115E-02 76.912747 -2.8708078
56 1 -170.46860 0.13302463E-03 -54.976289 2.7333905
57 0 57.057407 0.76310210E-06 15.605744  
58 9 -0.19728226E-15 0.38070760E-16 -0.14134637E-09 0.10329039E-17
59 8 0.20696804E-07 0.14765672E-12 0.36530744E-03 -0.23532978E-09
60 7 -0.11868633E-01 0.77667999E-08 -0.22548754E-01 0.13495068E-03
61 6 0.39521686 0.27204939E-05 0.46345169 -0.46283129E-02
62 5 -5.0916664 0.10217830E-03 -4.3748670 0.61957574E-01
63 4 32.565369 0.84029717E-03 21.180735 -0.41631434
64 3 -110.29532 0.18400486E-02 -55.110745 1.5017457
65 2 196.20849 0.10394005E-02 77.404245 -2.8860650
66 1 -170.82368 0.11139293E-03 -55.118150 2.7396138
67 0 57.057407 0.63685742E-06 15.581450  
68 9 0.13059652E-14 0.41030072E-16 -0.13816519E-09 -0.47111965E-17
69 8 0.20247126E-07 0.15597406E-12 0.36047671E-03 -0.23021680E-09
70 7 -0.11724123E-01 0.82470298E-08 -0.22340566E-01 0.13330755E-03
71 6 0.39128975 0.28947446E-05 0.46009809 -0.45820219E-02
72 5 -5.0533361 0.10891817E-03 -4.3490697 0.61482301E-01
73 4 32.395785 0.89717001E-03 21.079809 -0.41406279
74 3 -109.93440 0.19673976E-02 -54.911173 1.4965315
75 2 195.85064 0.11127485E-02 77.221372 -2.8803827
76 1 -170.69145 0.11939355E-03 -55.065279 2.7372963
77 0 57.057407 0.68346468E-06 15.590432  
78 7 -0.15963512E-14 -0.15187529E-16 -0.22427203E-13 0.56155309E-15
79 6 0.17983713E-10 0.23594901E-11 0.52322926E-09 -0.18637893E-10
80 5 -0.60139213E-07 0.11510628E-07 -0.21924491E-05 0.17161312E-06
81 4 0.62746279E-04 0.43399923E-05 0.17681060E-02 -0.28244642E-03
82 3 -0.90508353E-02 0.15320797E-03 -0.21560640 0.43341486E-01
83 2 0.12836503 0.66328859E-03 2.9007871 -0.61911613
84 1 -0.32478029 0.41934727E-03 -7.1379041 1.5697129
85 0 0.20664896 0.54311639E-05 4.4522013  
86 7 -0.22427203E-13 -0.15187529E-16 -0.15963512E-14 0.56155309E-15
87 6 0.52322926E-09 0.23594901E-11 0.17983713E-10 -0.18637893E-10
88 5 -0.21924491E-05 0.11510628E-07 -0.60139213E-07 0.17161312E-06
89 4 0.17681060E-02 0.43399923E-05 0.62746279E-04 -0.28244642E-03
90 3 -0.21560640 0.15320797E-03 -0.90508353E-02 0.43341486E-01
91 2 2.9007871 0.66328859E-03 0.12836503 -0.61911613
92 1 -7.1379041 0.41934727E-03 -0.32478029 1.5697129
93 0 4.4522013 0.54311639E-05 0.20664896  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
103 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
104 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
105 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
106 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
107 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
108 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
109 0 0.43108349 0.21254961E-04 60.838472  
110 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
111 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
112 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
113 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
114 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
115 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
116 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
117 0 0.43108349 0.21254961E-04 60.838472  
118 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
119 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
120 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
121 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
122 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
123 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
124 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
125 0 0.43108349 0.21254961E-04 60.838472  
126 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
127 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
128 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
129 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
130 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
131 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
132 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
133 0 0.43108349 0.21254961E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.3672_SHGC_0.36 37 1 VerySmooth 2.086 2.086 1.000 0.361    
2 RESWINDOW_U_0.3672_SHGC_0.36 38 1 VerySmooth 2.086 2.086 1.000 0.361    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   3.58639E-002 0.27318 0.51921 0.51921 0.36000 0.14234 0.19141 0.00000 0.84000 0.84000 0.11691 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   3.58639E-002 0.27318 0.51921 0.51921 0.36000 0.14234 0.19141 0.00000 0.84000 0.84000 0.11691 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CAFE_FLR_1 1 0
2 LOBBY_FLR_1 1 0
3 BANQUET_FLR_6 1 0
4 DINING_FLR_6 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CAFE_FLR_1 0  
2 LOBBY_FLR_1 0  
3 BANQUET_FLR_6 0  
4 DINING_FLR_6 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 2.320
2 RACK2 1 0 Zone Air-Cooled 6.980


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473


Heat Pump Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor "DX Coil Total Cooling Rate {W HPWH Only}"
1 WaterHeater:HeatPump:PumpedCondenser SWHSYSLAUNDRY HPWH 1.1400 77706.2 48.891 1.7318 76621  
2 WaterHeater:HeatPump:PumpedCondenser SWHSYS1 HPWH 2.8400 63053.7 4.646 9.4741 53264  


Water Heater Stratified Node Information

Node Number Height {m} Volume {m3} Maximum Capacity {W} Off-Cycle UA {W/K} On-Cycle UA {W/K} Number Of Inlets Number Of Outlets
1 1 0.2683 0.4733 0.000 2.4569 2.4569 0 1
2 2 0.2683 0.4733 47665.200 1.5573 1.5573 0 0
3 3 0.2683 0.4733 0.000 1.5573 1.5573 0 0
4 4 0.2683 0.4733 0.000 1.5573 1.5573 0 0
5 5 0.2683 0.4733 0.000 1.5573 1.5573 0 1
6 6 0.2683 0.4733 0.000 2.4569 2.4569 2 0


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 9.802E-003 1.461E-004 7.212E-005 0.133 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 3.784E-003 4.872E-005 1.327E-004 4.426E-002 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 8.942E-003 5.445E-005 1.424E-004 4.947E-002 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 5.159E-003 5.445E-005 1.182E-004 4.947E-002 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 1.221E-002 1.565E-004 1.392E-004 0.142 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 2.167E-002 1.147E-004 6.318E-005 0.104 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 6.191E-002 4.733E-005 9.051E-005 4.300E-002 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 5.689E-003 1.458E-004 1.424E-004 0.172 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 5.688E-003 1.458E-004 1.424E-004 0.172 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 1.587E-003 6.472E-005 1.424E-004 7.644E-002 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.588E-003 6.472E-005 1.424E-004 7.644E-002 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 5.689E-003 1.458E-004 1.424E-004 0.172 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 5.688E-003 1.458E-004 1.424E-004 0.172 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 6.879E-003 1.766E-005 1.424E-004 2.086E-002 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 5.689E-003 1.458E-004 7.203E-005 0.172 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 5.688E-003 1.458E-004 7.203E-005 0.172 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 2.910E-003 1.186E-004 6.472E-005 0.140 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 1.389E-002 4.188E-005 3.236E-005 4.947E-002 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 1.389E-002 4.188E-005 3.236E-005 4.947E-002 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 1.243E-002 1.204E-004 6.523E-005 0.142 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 1.217E-002 2.953E-005 2.446E-005 3.488E-002 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1294
2 Clear Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 6.3911E-002
3 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 0.1448
4 Clear Turbid Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 7.1395E-002
5 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 9.4390E-002
6 Intermediate Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 3.6497E-002
7 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 3.7870E-002
8 Overcast Sky 01/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 1.2581E-002
9 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1470
10 Clear Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 7.7447E-002
11 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1651
12 Clear Turbid Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 8.6328E-002
13 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1045
14 Intermediate Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 4.5754E-002
15 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 4.2527E-002
16 Overcast Sky 01/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 1.7207E-002
17 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 3.1438E-002
18 Clear Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.8117E-002
19 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.4121E-002
20 Clear Turbid Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.3639E-002
21 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.3277E-002
22 Intermediate Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 9.3175E-003
23 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 3.7278E-002
24 Overcast Sky 01/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.3219E-002
25 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 3.1438E-002
26 Clear Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.8117E-002
27 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.4121E-002
28 Clear Turbid Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.3639E-002
29 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.3277E-002
30 Intermediate Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 9.3175E-003
31 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 3.7278E-002
32 Overcast Sky 01/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.3219E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 28616.45749 28616.45749 2.08019 2.08019 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 28.80700 1.41137E-002 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 1866.56785 1866.56785 8.00447E-002 0.85446 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -10.70000 1.50390E-003 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 4843.23257 4843.23257 0.35210 0.35210 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 31.79167 1.41191E-002 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 2663.52683 2663.52683 0.11422 0.11422 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 2989.57008 2989.57008 0.21734 0.21734 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 31.65600 1.41188E-002 77.66889 12.54000 9.17347E-002 0.00000
6 RETAIL_2_FLR_1 Heating 908.92196 908.92196 3.89773E-002 9.17347E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 77.66889 12.54000 9.17347E-002 0.00000
7 MECH_FLR_1 Cooling 2529.69945 2529.69945 0.18387 0.18387 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 28.94267 1.41140E-002 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 1690.40636 1690.40636 7.24896E-002 7.24896E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1360.86906 1360.86906 9.89153E-002 9.89153E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 30.44733 1.41167E-002 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 1091.77909 1091.77909 4.68187E-002 5.77652E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 44791.04400 44791.04400 3.25595 3.25595 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 32.10000 1.41196E-002 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 2177.42918 2177.42918 9.33732E-002 9.33732E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 20606.50612 20606.50612 1.49931 1.49931 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 31.79167 1.41191E-002 188.86188 142.30000 0.67639 0.00000
14 CAFE_FLR_1 Heating 6702.68805 6702.68805 0.28743 0.67639 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 188.86188 142.30000 0.67639 0.00000
15 LOBBY_FLR_1 Cooling 64340.90875 64340.90875 4.67889 4.67889 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 31.85333 1.41192E-002 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 16056.07713 16056.07713 0.68853 1.89399 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 10689.52249 10689.52249 1.04708 1.04708 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 31.36000 1.41183E-002 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 6056.06026 6056.06026 0.26122 0.26122 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -10.70000 1.50390E-003 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 10358.43506 10358.43506 1.01465 1.01465 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 31.26133 1.41181E-002 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 6073.64085 6073.64085 0.26198 0.26198 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -10.70000 1.50390E-003 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 62450.25328 62450.25328 6.11690 6.11690 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 31.85333 1.41192E-002 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 34770.67161 34770.67161 1.49983 1.49983 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -10.70000 1.50390E-003 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 56078.57803 56078.57803 5.49323 5.49323 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 32.10000 1.41196E-002 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 35110.84228 35110.84228 1.51450 1.51450 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -10.70000 1.50390E-003 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 9771.56168 9771.56168 0.95716 0.95716 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 28.86867 1.41138E-002 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 6020.28899 6020.28899 0.25968 0.25968 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -10.70000 1.50390E-003 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 9490.82117 9490.82117 0.92966 0.92966 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 28.44933 1.41131E-002 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 6037.88401 6037.88401 0.26044 0.26044 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -10.70000 1.50390E-003 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 17020.31339 17020.31339 1.23721 1.23721 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 32.10000 1.41196E-002 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 9818.45947 9818.45947 0.42105 0.47476 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 2820.33531 2820.33531 0.27626 0.27626 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 31.36000 1.41183E-002 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 1866.10748 1866.10748 8.04935E-002 8.04935E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -10.70000 1.50390E-003 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2727.53699 2727.53699 0.26717 0.26717 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 31.26133 1.41181E-002 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 1871.98815 1871.98815 8.07471E-002 8.07471E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -10.70000 1.50390E-003 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 13079.10763 13079.10763 1.28117 1.28117 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 31.91500 1.41193E-002 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 8900.19434 8900.19434 0.38391 0.38391 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 -10.70000 1.50390E-003 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 29287.03997 29287.03997 2.13151 2.13151 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 32.10000 1.41196E-002 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 6132.64387 6132.64387 0.26299 1.18780 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 -10.70000 1.50390E-003 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 30741.70699 30741.70699 2.23735 2.23735 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 32.10000 1.41196E-002 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 6280.13423 6280.13423 0.26931 1.18780 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:40:00 -10.70000 1.50390E-003 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 29837.65784 29837.65784 2.17457 2.17457 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 31.43400 1.41184E-002 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 2712.41549 2712.41549 0.11631 0.36735 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 -10.70000 1.50390E-003 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 9579.92213 9579.92213 0.69636 0.69636 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 32.03833 1.41195E-002 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 6399.94065 6399.94065 0.27445 0.27445 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:40:00 -10.70000 1.50390E-003 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 394725.66 20.73536 20.73536 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 243456.16 7.34657 7.34657 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00
3 FLR_3_DOAS Cooling Sensible 47880.67 16.37335 2.05125 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 FLR_3_DOAS Heating Sensible 67975.66 4.60281 2.05125 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.08019
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.72487
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.55900
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.16283
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.25611E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.00142E-005
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.16283
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8003.05025
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.00142E-005
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 169.56649
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.35210
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14515
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.55900
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.19682
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.55900
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.62482E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.23858E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.19682
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3701.89038
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.23858E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 89.23689
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.21734
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.27231
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.55900
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.12149
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.72615
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.39916E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.35591E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.12149
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1549.88802
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.35591E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 34.90296
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.18387
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.68066
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.55900
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.10278
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.59751E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.95319E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.10278
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2232.61222
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.95319E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 55.73577
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.89153E-002
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.72998
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.55900
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.52936E-002
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.21929E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.21033E-005
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.52936E-002
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1383.47689
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.21033E-005
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 36.00075
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.25595
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.24747E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.55900
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.82007
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.55900
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.08609E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.03039E-004
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.82007
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11777.97307
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.03039E-004
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 248.52562
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.49931
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.59861E-002
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.55900
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.83811
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.55900
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.96932E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.73214E-005
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.83811
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11124.43440
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.73214E-005
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 251.92386
99 Fan:ZoneExhaust LOBBY_FLR_1 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.67889
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21305
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.55900
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.61550
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.56813
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.78831E-003
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.61184E-004
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.61550
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
110 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 29854.87916
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.61184E-004
113 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 662.73624
114 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
115 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.04708
116 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.04708
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 5.29807E-005
118 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.19405E-004
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68317
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.59876E-003
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.19405E-004
125 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.04708
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6056.01420
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.29807E-005
128 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 173.02923
129 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
130 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.01465
131 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.01465
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 5.31345E-005
133 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.06768E-004
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68316
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.60195E-003
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.06768E-004
140 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.01465
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6073.59467
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.31345E-005
143 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 173.53148
144 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
145 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 6.11690
146 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 6.11690
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.04188E-004
148 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.40158E-003
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68369
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.52592E-003
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.40158E-003
155 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 6.11690
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 34770.54304
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.04188E-004
158 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 993.44041
159 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
160 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 5.49323
161 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 5.49323
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.07164E-004
163 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.31140E-003
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68277
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.78404E-003
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.31140E-003
170 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.49323
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 35110.71260
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.07164E-004
173 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 1003.15873
174 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
175 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.95716
176 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.95716
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 5.26677E-005
178 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.84390E-004
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68315
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.60834E-003
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.84390E-004
185 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.95716
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6020.24316
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.26677E-005
188 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 172.00729
189 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
190 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.92966
191 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.92966
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 5.28216E-005
193 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.73677E-004
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68315
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.61160E-003
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.73677E-004
200 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.92966
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6037.83807
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.28216E-005
203 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 172.50995
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.23721
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.95934
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.55900
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.69160
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.97149E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.17820E-004
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.69160
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
214 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13467.55266
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.17820E-004
217 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 327.20467
218 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
219 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.27626
220 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.27626
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.63254E-005
222 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.10503E-004
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68318
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.59367E-003
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.10503E-004
229 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.27626
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1866.09394
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.63254E-005
232 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 53.31616
233 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
234 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.26717
235 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.26717
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.63768E-005
237 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.06960E-004
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68317
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.59687E-003
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.06960E-004
244 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.26717
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1871.97457
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.63768E-005
247 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 53.48416
248 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
249 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.28117
250 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.28117
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 7.78623E-005
252 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 5.21220E-004
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.68292
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.65636E-003
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.21220E-004
259 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.28117
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 8900.14259
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 7.78623E-005
262 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 254.28542
263 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.13151
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11857
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.55900
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.19152
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.55900
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.21342E-003
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.08652E-004
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.19152
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
273 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
274 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12419.55277
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.08652E-004
276 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 272.83269
277 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.23735
278 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11296
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.55900
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.25068
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.55900
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.37298E-003
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.12673E-004
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.25068
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
287 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
288 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12879.23257
289 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.12673E-004
290 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 282.58862
291 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.17457
292 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.51090E-002
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.55900
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.21559
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.55900
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.05251E-002
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.97570E-005
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.21559
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
301 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
302 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9116.71554
303 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.97570E-005
304 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 194.36512
305 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.69636
306 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.45097
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.55900
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.38927
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 8.44845E-004
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.39588E-005
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.38927
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
315 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
316 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8453.94501
317 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.39588E-005
318 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 211.03743
319 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 11.65156
320 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 11.65156
321 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 20.84357
322 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 11.65156
323 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 20.73536
324 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 20.73536
325 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
326 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.56192
327 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
328 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
329 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
333 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
334 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
335 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 20.73536
336 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
337 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 20.73536
338 HeatExchanger:AirToAir:SensibleAndLatent VAV WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 11.66146
339 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 28.55482
340 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
341 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.98822
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.21953E-002
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 683001.77530
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.43952E-002
346 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 20.73536
347 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 206143.06527
348 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.80343E-003
349 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 3402.46928
350 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 20.73536
351 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 2.43952E-002
352 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 1.95198E-005
353 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.80343E-003
354 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
355 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
356 HeatExchanger:AirToAir:SensibleAndLatent FLR_3_DOAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.05125
357 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 32.10000
358 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
359 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.93776
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.41196E-002
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 86334.70852
363 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.08368E-003
364 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
365 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 20393.41537
366 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.78410E-004
367 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 336.60104
368 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
369 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 3.08368E-003
370 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.54423E-004
371 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.78410E-004
372 Coil:WaterHeating:AirToWaterHeatPump:Pumped SWHSYSLAUNDRY HPWH DXCOIL Design Size Rated Evaporator Air Flow Rate [m3/s] 4.90359
373 Coil:WaterHeating:AirToWaterHeatPump:Pumped SWHSYSLAUNDRY HPWH DXCOIL Design Size Rated Condenser Water Flow Rate [m3/s] 4.36989E-003
374 Fan:SystemModel SWHSYSLAUNDRY HPWH FAN Design Size Design Maximum Air Flow Rate [m3/s] 4.90359
375 Fan:SystemModel SWHSYSLAUNDRY HPWH FAN Design Electric Power Consumption [W] 700.51236
376 Coil:WaterHeating:AirToWaterHeatPump:Pumped SWHSYS1 HPWH DXCOIL Design Size Rated Evaporator Air Flow Rate [m3/s] 3.87257
377 Coil:WaterHeating:AirToWaterHeatPump:Pumped SWHSYS1 HPWH DXCOIL Design Size Rated Condenser Water Flow Rate [m3/s] 3.45109E-003
378 Fan:SystemModel SWHSYS1 HPWH FAN Design Size Design Maximum Air Flow Rate [m3/s] 3.87257
379 Fan:SystemModel SWHSYS1 HPWH FAN Design Electric Power Consumption [W] 553.22422
380 WaterHeater:HeatPump:PumpedCondenser SWHSYS1 HPWH Condenser water flow rate [m3/s] 3.45109E-003
381 WaterHeater:HeatPump:PumpedCondenser SWHSYS1 HPWH Evaporator air flow rate [m3/s] 3.87257
382 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 3.45148E-002
383 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 7041.80592
384 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 4.01736E-003
385 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.48208
386 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 4.01736E-003
387 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 1197.87345
388 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
389 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 459208.84044
390 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 459208.84000
391 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 4.01736E-003
392 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 3.45148E-002
393 PlantLoop COOLSYS1 Plant Loop Volume [m3] 4.14178
394 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 3.45148E-002
395 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 4875.27975
396 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 3.45148E-002
397 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 966322.87821
398 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 966907.44000
399 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 110.22745
400 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
401 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
402 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
403 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
404 WaterHeater:Stratified SWHSYS1 HPWH TANK Use Side Design Flow Rate [m3/s] 3.75036E-004
405 WaterHeater:HeatPump:PumpedCondenser SWHSYSLAUNDRY HPWH Condenser water flow rate [m3/s] 4.36989E-003
406 WaterHeater:HeatPump:PumpedCondenser SWHSYSLAUNDRY HPWH Evaporator air flow rate [m3/s] 4.90359


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 8043.76
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 3718.00
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1557.21
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 2241.97
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 1388.95
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 11838.12
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 11176.71
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 29998.10
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 6522.08
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 6541.02
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 37446.41
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 37812.74
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 6483.56
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 6502.51
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 13525.65
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 2009.69
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 2016.02
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 9584.99
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 12479.79
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 12942.71
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 9162.82
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 8489.39
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 146079.48
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 14451.42


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 17373.34 14058.65 3314.69 0.81 1949.75 19.78
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 16844.80 13628.02 3216.79 0.81 1890.30 19.17
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 100168.68 81463.47 18705.21 0.81 11260.37 114.21
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 94099.57 75233.64 18865.92 0.80 10522.36 106.72
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 15908.49 12864.96 3043.53 0.81 1784.98 18.10
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 15460.39 12499.84 2960.55 0.81 1734.58 17.59
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 4579.64 3707.16 872.48 0.81 514.02 5.21
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 4431.48 3586.45 845.03 0.81 497.35 5.04
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21474.28 17310.45 4163.83 0.81 2407.05 24.41
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 608769.61 404673.19 204096.43 0.66 71871.32 728.96
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 63544.84 41523.88 22020.96 0.65 7288.25 73.92


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 3.93 13.40


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.419 0.394   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.419 0.394   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.419 0.394   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.419 0.394   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.760 1.760   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.924 0.812   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.107 0.950   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.107 0.950   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.107 0.950   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.107 0.950   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.107 0.950   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.107 0.950   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.107 0.950   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.107 0.950   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.107 0.950   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.107 0.950   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.217 1.029   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.217 1.029   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.217 1.029   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.217 1.029   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.174 0.999   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.174 0.999   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.174 0.999   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.174 0.999   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.174 0.999   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.186 0.180   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.286 1.078   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.286 1.078   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.286 1.078   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.286 1.078   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.286 1.078   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.286 1.078   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.286 1.078   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.286 1.078   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3672_SHGC_0.36 N/A 2.086 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 1.6263011699E-002 1.9944451344E-002 Pass Pass 3.2096239304E-003 8.0971122512E-003 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 7.6378010592E-003 2.2349138682E-002 Pass Pass 0.5397188524 3.9678486127 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 7.9154744436E-003 1.6108869896E-002 Pass Pass 2.4699001740E-002 5.5567955013E-002 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 4.5381800129E-004 3.8269191123E-004 Pass Pass 6.9448484278E-002 0.1645488454 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 4.6337432675E-004 3.6794355874E-004 Pass Pass 2.5094103203E-002 3.6662082070E-002 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 7.9007031278E-002 0.2264114840 Pass Pass 1.9190197677E-002 5.1250735447E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 3.6639416323E-002 7.4113907487E-002 Pass Pass 4.3344568280E-002 8.4829370222E-002 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 2.9656916728E-002 4.3548938860E-002 Pass Pass 1.6795546977E-002 3.5169176059E-002 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 9.7228296183E-002 0.2984685408 Pass Pass 0.1678098483 0.7078154664 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 9.2628509309E-002 0.3256232196 Pass Pass 0.4332331511 4.0471664141 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 5.7079695634E-002 6.1386532905E-002 Pass Pass 7.5845341911E-003 7.1342744595E-002 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 4.1854303844E-002 0.1398443107 Pass Pass 9.2739943431E-002 0.3313930732 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 7.4415368714E-002 0.2519875551 Pass Pass 0.2497543887 1.0147412362 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 7.8639814781E-002 0.2760256888 Pass Pass 0.1061766782 0.4141679889 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 4.0647131170E-004 3.2914780876E-004 Pass Pass 0.2568561439 0.6170562385 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 9.2821239489E-002 0.3334807166 Pass Pass 0.1903796094 0.6427491362 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 9.2632494774E-002 0.3474595908 Pass Pass 0.1604432480 0.6216160865 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 7.2494698439E-002 0.1825583229 Pass Pass 7.4062133918E-002 0.2563058723 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 5.3296177599E-002 9.8043171447E-002 Pass Pass 8.4707983361E-003 1.9834311196E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 4.8564419705E-002 8.7632989058E-002 Pass Pass 8.3517262072E-003 1.9353220092E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 3.9796708823E-002 0.1231527043 Pass Pass 2.1906636729E-002 3.7690531054E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 7.9881242461E-004 6.3773261188E-004 Pass Pass 0.1470019537 0.4261701258 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 4397.64 26.01 1272.84 5444.95 5407.45 16548.89



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB -10.70 0.00 -10.70 Wetbulb [C] 7.50 320.00
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 32.10 7.40 23.10 Wetbulb [C] 5.60 230.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 172.00 59      
Feb 49.00 37      
Mar 40.00 38      
Apr 70.00 48      
May 70.00 36      
Jun 25.00 15      
Jul 64.00 20      
Aug 2.00 4      
Sep 73.00 32      
Oct 7.00 8      
Nov 88.00 34      
Dec 62.00 39      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.399 0.419 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.399 0.419 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.399 0.419 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.812 0.924 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.812 0.924 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.23 0.182 0.186 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.812 0.924 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.812 0.924 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.812 0.924 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.812 0.924 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.812 0.924 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.812 0.924 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.812 0.924 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.23 0.182 0.186 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 0.812 0.924 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 0.812 0.924 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 0.812 0.924 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 0.812 0.924 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.23 0.182 0.186 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.950 1.107 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.950 1.107 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.950 1.107 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.950 1.107 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.950 1.107 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.950 1.107 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.950 1.107 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.950 1.107 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.950 1.107 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.950 1.107 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 1.029 1.217 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 1.029 1.217 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 1.029 1.217 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 1.029 1.217 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.999 1.174 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.999 1.174 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 0.999 1.174 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.999 1.174 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.999 1.174 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.23 0.182 0.186 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.078 1.286 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.078 1.286 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.078 1.286 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.078 1.286 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 1.078 1.286 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.23 0.182 0.186 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 1.078 1.286 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 1.078 1.286 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 1.078 1.286 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.23 0.182 0.186 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.23 0.182 0.186 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.186 0.196 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.186 0.196 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.186 0.196 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.186 0.196 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.186 0.196 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.186 0.196 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.186 0.196 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.186 0.196 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.186 0.196 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.186 0.196 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.185 0.196 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.185 0.196 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.185 0.196 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.188 0.196 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.3672_SHGC_0.36   23.26 0.00 0.00 23.26 23.26 2.086 0.361 0.361             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.3672_SHGC_0.36   65.50 0.00 0.00 65.50 65.50 2.086 0.361 0.361             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.3672_SHGC_0.36   85.08 0.00 0.00 85.08 85.08 2.086 0.361 0.361             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.3672_SHGC_0.36   4.60 0.00 0.00 4.60 18.40 2.086 0.361 0.361             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.3672_SHGC_0.36   8.58 0.00 0.00 8.58 34.34 2.086 0.361 0.361             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.3672_SHGC_0.36   4.60 0.00 0.00 4.60 18.40 2.086 0.361 0.361             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.3672_SHGC_0.36   8.58 0.00 0.00 8.58 34.34 2.086 0.361 0.361             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.3672_SHGC_0.36   3.68 0.00 0.00 3.68 279.56 2.086 0.361 0.361             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.3672_SHGC_0.36   3.68 0.00 0.00 3.68 279.65 2.086 0.361 0.361             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.3672_SHGC_0.36   8.58 0.00 0.00 8.58 34.34 2.086 0.361 0.361             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.3672_SHGC_0.36   4.60 0.00 0.00 4.60 18.40 2.086 0.361 0.361             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.3672_SHGC_0.36   4.60 0.00 0.00 4.60 18.40 2.086 0.361 0.361             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.3672_SHGC_0.36   8.58 0.00 0.00 8.58 34.34 2.086 0.361 0.361             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.3672_SHGC_0.36   5.82 0.00 0.00 5.82 23.30 2.086 0.361 0.361             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.3672_SHGC_0.36   2.15 0.00 0.00 2.15 8.59 2.086 0.361 0.361             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.3672_SHGC_0.36   2.15 0.00 0.00 2.15 8.58 2.086 0.361 0.361             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.3672_SHGC_0.36   5.82 0.00 0.00 5.82 23.30 2.086 0.361 0.361             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.3672_SHGC_0.36   4.60 0.00 0.00 4.60 4.60 2.086 0.361 0.361             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.3672_SHGC_0.36   8.58 0.00 0.00 8.58 8.58 2.086 0.361 0.361             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.3672_SHGC_0.36   4.60 0.00 0.00 4.60 4.60 2.086 0.361 0.361             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.3672_SHGC_0.36   8.58 0.00 0.00 8.58 8.58 2.086 0.361 0.361             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.3672_SHGC_0.36   6.74 0.00 0.00 6.74 60.70 2.086 0.361 0.361             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.3672_SHGC_0.36   32.19 0.00 0.00 32.19 32.19 2.086 0.361 0.361             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.3672_SHGC_0.36   32.19 0.00 0.00 32.19 32.19 2.086 0.361 0.361             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.3672_SHGC_0.36   4.60 0.00 0.00 4.60 4.60 2.086 0.361 0.361             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.3672_SHGC_0.36   17.17 0.00 0.00 17.17 17.17 2.086 0.361 0.361             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.3672_SHGC_0.36   4.60 0.00 0.00 4.60 4.60 2.086 0.361 0.361             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.3672_SHGC_0.36   5.82 0.00 0.00 5.82 5.82 2.086 0.361 0.361             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.3672_SHGC_0.36   5.21 0.00 0.00 5.21 5.21 2.086 0.361 0.361             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.3672_SHGC_0.36   17.17 0.00 0.00 17.17 17.17 2.086 0.361 0.361             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 2.086 0.361 0.361                      
North Total or Average             432.95 2.086 0.361 0.361                      
Non-North Total or Average             780.84 2.086 0.361 0.361                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.393 1.760 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 6.6442 1978.83 13147.70 LightsWired LTG_SCH_BASEMENT 45.99 168.00 45.94 0.0000 Y 113.37
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 9.6995 67.07 650.56 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 6.26
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 9.6995 77.67 753.35 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 7.25
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 4.6285 164.24 760.20 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 8.37
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 4.0903 94.76 387.59 LightsWired LTG_SCH_STORAGE 25.68 168.00 25.65 0.0000 Y 1.87
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 5.7049 78.04 445.21 LightsWired LTG_SCH_LAUNDRY 58.69 168.00 58.63 0.0000 Y 4.90
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 9.2569 188.86 1748.29 LightsWired LTG_SCH_DINING 58.69 168.00 39.34 0.0000 Y 12.91
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 9.0417 1308.19 11828.20 LightsWired LTG_SCH_LOBBY 58.69 168.00 55.34 0.0000 Y 122.88
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 4.4132 156.09 688.85 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.17
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 4.4132 156.07 688.77 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.17
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 4.4132 1863.81 8225.38 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 73.68
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 4.4132 1864.32 8227.62 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 73.70
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 4.4132 156.09 688.85 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.17
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 4.4132 156.07 688.77 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 6.17
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 4.4132 1557.62 6874.08 LightsWired LTG_SCH_CORRIDOR 44.02 168.00 43.97 0.0000 Y 56.74
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 4.4132 39.02 172.21 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.54
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 4.4132 39.02 172.19 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.54
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 4.4132 220.77 974.32 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 8.73
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 9.2569 331.66 3070.14 LightsWired LTG_SCH_DINING 58.69 168.00 49.13 0.0000 Y 28.31
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 9.2569 331.66 3070.14 LightsWired LTG_SCH_DINING 58.69 168.00 49.13 0.0000 Y 28.31
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 11.7327 103.30 1212.04 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 13.34
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 4.4132 412.12 1818.79 LightsWired LTG_SCH_CORRIDOR 44.02 168.00 43.97 0.0000 Y 15.01
Interior Lighting Total       5.8432 11345.29 66293.22               389.14


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
LOBBY_FLR_1_DAYLREFPT1 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.07 11828.20 827.97
LOBBY_FLR_1_DAYLREFPT2 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.07 11828.20 827.97
CAFE_FLR_1_DAYLREFPT1 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1748.29 681.83
CAFE_FLR_1_DAYLREFPT2 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1748.29 681.83
DINING_FLR_6_DAYLREFPT1 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 3070.14 614.03
DINING_FLR_6_DAYLREFPT2 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 3070.14 614.03
BANQUET_FLR_6_DAYLREFPT1 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 3070.14 614.03
BANQUET_FLR_6_DAYLREFPT2 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 3070.14 614.03


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 11096.45 AstronomicalClock -   83.64 83.64 174.22
Exterior Lighting Total 11096.45           174.22



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 459208.84 0.80        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 966907.44 2.96 967077.40 2.96 3.93 13.40


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11742.45 17373.34 14058.65 3314.69 0.81 - 1949.75 19.78
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11388.64 16844.80 13628.02 3216.79 0.81 - 1890.30 19.17
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 67239.04 100168.68 81463.47 18705.21 0.81 - 11260.37 114.21
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 64714.14 94099.57 75233.64 18865.92 0.80 - 10522.36 106.72
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 10762.09 15908.49 12864.96 3043.53 0.81 - 1784.98 18.10
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 10462.16 15460.39 12499.84 2960.55 0.81 - 1734.58 17.59
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3093.84 4579.64 3707.16 872.48 0.81 - 514.02 5.21
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 2994.66 4431.48 3586.45 845.03 0.81 - 497.35 5.04
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 14593.05 21474.28 17310.45 4163.83 0.81 - 2407.05 24.41
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 683001.78 608769.61 404673.19 204096.43 0.66 - 71871.32 728.96
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 86334.71 63544.84 41523.88 22020.96 0.65 - 7288.25 73.92
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 8003.05 8043.76 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 3701.89 3718.00 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1549.89 1557.21 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2232.61 2241.97 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1383.48 1388.95 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 11777.97 11838.12 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 11124.43 11176.71 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 29854.88 29998.10 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 6056.01 6522.08 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 6073.59 6541.02 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 34770.54 37446.41 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 35110.71 37812.74 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 6020.24 6483.56 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 6037.84 6502.51 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 13467.55 13525.65 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1866.09 2009.69 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1871.97 2016.02 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 8900.14 9584.99 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 12419.55 12479.79 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 12879.23 12942.71 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 9116.72 9162.82 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 8453.95 8489.39 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 206143.07 146079.48 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 20393.42 14451.42 -
SWHSYSLAUNDRY HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped   75921.46 3.40
SWHSYS1 HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped   54370.95 3.40
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.24 76.61 324.68 1.00 2.78 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.05 736.76 703.64 1.00 1.19 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.01 713.94 703.64 1.00 1.19 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 6.12 4304.07 703.64 1.00 0.96 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 5.49 3865.24 703.64 1.00 0.96 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.96 673.49 703.64 1.00 1.21 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.93 654.14 703.64 1.00 1.22 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.28 194.39 703.64 1.00 1.77 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.27 187.99 703.64 1.00 1.80 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.28 901.48 703.64 1.00 1.14 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 1.89 612.92 324.68 1.00 1.48 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 20.74 46460.45 2240.64 1.00 1.11 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00
SWHSYSLAUNDRY HPWH FAN Fan:SystemModel 0.70 100.00 4.90 700.51 142.86 0.00 2.78 General    
SWHSYS1 HPWH FAN Fan:SystemModel 0.70 100.00 3.87 553.22 142.86 0.00 2.84 General    


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.034515 7041.81 204022.71 0.91 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.004017 1197.87 298174.34 0.91 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.034515 4875.28 141251.80 0.91 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWHSYSLAUNDRY HPWH WaterHeater:HeatPump:PumpedCondenser 1.14 77706.24 0.80 48.89 1.73
SWHSYS1 HPWH WaterHeater:HeatPump:PumpedCondenser 2.84 63053.73 0.80 4.65 9.47



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 28616.46 28616.46 14.46 2.080 2.080 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 24.00 24.00 0.00934 28.81 0.01411 0.854 0.00
RETAIL_1_FLR_1 4843.23 4843.23 72.21 0.352 0.352 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 24.00 24.00 0.00904 31.79 0.01412 0.079 0.00
RETAIL_2_FLR_1 2989.57 2989.57 38.49 0.217 0.217 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 24.00 24.00 0.00947 31.66 0.01412 0.092 0.00
MECH_FLR_1 2529.70 2529.70 15.40 0.184 0.184 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 24.00 24.00 0.00880 28.94 0.01411 0.000 0.00
STORAGE_FLR_1 1360.87 1360.87 14.36 0.099 0.099 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 24.00 24.00 0.00890 30.45 0.01412 0.058 0.00
LAUNDRY_FLR_1 44791.04 44791.04 573.95 3.256 3.256 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 24.00 0.00855 32.10 0.01412 0.000 0.00
CAFE_FLR_1 20606.51 20606.51 109.11 1.499 1.499 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 24.00 23.99 0.01007 31.79 0.01412 0.676 0.00
LOBBY_FLR_1 64340.91 64340.91 49.18 4.679 4.679 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 24.00 23.99 0.01000 31.85 0.01412 1.894 0.00
ROOM_1_FLR_3 10689.52 10689.52 273.94 1.047 1.047 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 21.11 21.11 0.00860 31.36 0.01412 0.062 0.00
ROOM_2_FLR_3 10358.44 10358.44 265.48 1.015 1.015 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 21.11 21.11 0.00860 31.26 0.01412 0.062 0.00
ROOM_3_MULT19_FLR_3 62450.25 62450.25 2546.51 6.117 6.117 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 21.11 21.11 0.00853 31.85 0.01412 0.837 0.00
ROOM_4_MULT19_FLR_3 56078.58 56078.58 2286.07 5.493 5.493 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 21.11 21.11 0.00878 32.10 0.01412 0.837 0.00
ROOM_5_FLR_3 9771.56 9771.56 250.41 0.957 0.957 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 21.11 21.11 0.00861 28.87 0.01411 0.062 0.00
ROOM_6_FLR_3 9490.82 9490.82 243.25 0.930 0.930 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 21.11 21.11 0.00861 28.45 0.01411 0.062 0.00
CORRIDOR_FLR_3 17020.31 17020.31 43.71 1.237 1.237 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 24.00 24.00 0.00965 32.10 0.01412 0.475 0.00
ROOM_1_FLR_6 2820.34 2820.34 72.28 0.276 0.276 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 21.11 21.11 0.00859 31.36 0.01412 0.015 0.00
ROOM_2_FLR_6 2727.54 2727.54 69.91 0.267 0.267 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 21.11 21.11 0.00860 31.26 0.01412 0.015 0.00
ROOM_3_MULT9_FLR_6 13079.11 13079.11 533.18 1.281 1.281 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 21.11 21.11 0.00866 31.92 0.01412 0.099 0.00
BANQUET_FLR_6 29287.04 29287.04 88.31 2.132 2.132 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 24.00 23.98 0.01043 32.10 0.01412 1.188 0.00
DINING_FLR_6 30741.71 30741.71 92.69 2.237 2.237 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 24.00 23.99 0.01034 32.10 0.01412 1.188 0.00
KITCHEN_FLR_6 29837.66 29837.66 288.83 2.175 2.175 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 24.00 23.97 0.01013 31.43 0.01412 0.367 0.00
CORRIDOR_FLR_6 9579.92 9579.92 23.25 0.696 0.696 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 24.00 24.00 0.00905 32.04 0.01412 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 1866.57 1866.57 0.94 0.080 0.854 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00797 -10.70 0.00150 0.854 0.00
RETAIL_1_FLR_1 2663.53 2663.53 39.71 0.114 0.114 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00785 -10.70 0.00150 0.079 0.00
RETAIL_2_FLR_1 908.92 908.92 11.70 0.039 0.092 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00783 -10.70 0.00150 0.092 0.00
MECH_FLR_1 1690.41 1690.41 10.29 0.072 0.072 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00778 -10.70 0.00150 0.000 0.00
STORAGE_FLR_1 1091.78 1091.78 11.52 0.047 0.058 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00781 -10.70 0.00150 0.058 0.00
LAUNDRY_FLR_1 2177.43 2177.43 27.90 0.093 0.093 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00777 -10.70 0.00150 0.000 0.00
CAFE_FLR_1 6702.69 6702.69 35.49 0.287 0.676 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00787 -10.70 0.00150 0.676 0.00
LOBBY_FLR_1 16056.08 16056.08 12.27 0.689 1.894 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00784 -10.70 0.00150 1.894 0.00
ROOM_1_FLR_3 6056.06 6056.06 155.20 0.261 0.261 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00785 -10.70 0.00150 0.062 0.00
ROOM_2_FLR_3 6073.64 6073.64 155.66 0.262 0.262 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00785 -10.70 0.00150 0.062 0.00
ROOM_3_MULT19_FLR_3 34770.67 34770.67 1417.83 1.500 1.500 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00786 -10.70 0.00150 0.837 0.00
ROOM_4_MULT19_FLR_3 35110.84 35110.84 1431.31 1.515 1.515 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00786 -10.70 0.00150 0.837 0.00
ROOM_5_FLR_3 6020.29 6020.29 154.28 0.260 0.260 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00785 -10.70 0.00150 0.062 0.00
ROOM_6_FLR_3 6037.88 6037.88 154.75 0.260 0.260 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00785 -10.70 0.00150 0.062 0.00
CORRIDOR_FLR_3 9818.46 9818.46 25.21 0.421 0.475 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00788 -10.70 0.00150 0.475 0.00
ROOM_1_FLR_6 1866.11 1866.11 47.82 0.080 0.080 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00787 -10.70 0.00150 0.015 0.00
ROOM_2_FLR_6 1871.99 1871.99 47.98 0.081 0.081 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00787 -10.70 0.00150 0.015 0.00
ROOM_3_MULT9_FLR_6 8900.19 8900.19 362.82 0.384 0.384 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 21.11 21.11 0.00788 -10.70 0.00150 0.099 0.00
BANQUET_FLR_6 6132.64 6132.64 18.49 0.263 1.188 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00791 -10.70 0.00150 1.188 0.00
DINING_FLR_6 6280.13 6280.13 18.94 0.269 1.188 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:40:00 21.00 21.00 0.00791 -10.70 0.00150 1.188 0.00
KITCHEN_FLR_6 2712.42 2712.42 26.26 0.116 0.367 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 21.00 21.00 0.00730 -10.70 0.00150 0.367 0.00
CORRIDOR_FLR_6 6399.94 6399.94 15.53 0.274 0.274 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:40:00 21.00 21.00 0.00792 -10.70 0.00150 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 20.74 20.74 7.35 7.35 20.7354 11.6516 20.7354 0.5619 0.3000
FLR_3_DOAS 16.37 2.05 4.60 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 8003.050 8003.050 1.162825 0.00007001 169.566 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8003.05 8003.05 1.162825 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00797372 51.5252 1866.57 0.00 8047.78 8047.78
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 3701.890 3701.890 0.196825 0.00003239 89.237 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 3701.89 3701.89 0.196825 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00784836 50.7263 2663.53 0.00 3721.21 3721.21
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1549.888 1549.888 0.121495 0.00001356 34.903 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 1549.89 1549.89 0.121495 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00782899 50.6020 908.92 0.00 1558.26 1558.26
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 2232.612 2232.612 0.102784 0.00001953 55.736 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 2232.61 2232.61 0.102784 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00778422 50.3162 1690.41 0.00 2244.13 2244.13
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 1383.477 1383.477 0.055294 0.00001210 36.001 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 1383.48 1383.48 0.055294 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00780656 50.4588 1091.78 0.00 1390.44 1390.44
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 11777.973 11777.973 1.820075 0.00010304 248.526 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 11777.97 11777.97 1.820075 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00777172 50.2371 2177.43 0.00 11843.89 11843.89
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 11124.434 11124.434 0.838113 0.00009732 251.924 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 11124.43 11124.43 0.838113 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00786641 50.8413 6702.69 0.00 11184.43 11184.43
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 29854.879 29854.879 2.615498 0.00026118 662.736 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 29854.88 29854.88 2.615498 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00784129 50.6805 16056.08 0.00 30017.12 30017.12
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 11742.449 -999.000 1.047078 0.00041941 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 unknown 7/21 16:30:00 11742.45 11463.14 1.047078 21.68 15.64 0.00859876 12.80 12.09 0.00850000 31.36 0.01411830 22.93 0.0000 21.11 0.00859876 55.1335 10689.52 0.00 11762.26 11296.08
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 6056.014 6056.014 0.261224 0.00005298 173.029 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 6056.01 6056.01 0.261224 21.11 14.75 0.00784611 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00784611 50.3670 6056.06 0.00 6528.57 6528.57
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 11388.644 -999.000 1.014647 0.00040677 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown 7/21 16:40:00 11388.64 11109.22 1.014647 21.68 15.64 0.00860195 12.80 12.09 0.00850000 31.26 0.01411813 22.90 0.0000 21.11 0.00860195 55.1536 10358.44 0.00 11407.84 10947.81
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 6073.595 6073.595 0.261983 0.00005313 173.531 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 6073.59 6073.59 0.261983 21.11 14.75 0.00784656 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00784656 50.3698 6073.64 0.00 6547.53 6547.53
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 67239.039 -999.000 6.116899 0.00240158 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 unknown 7/21 13:20:00 67239.04 66811.83 6.116899 21.68 15.57 0.00852592 12.80 12.09 0.00850000 31.85 0.01411920 23.06 0.0000 21.11 0.00852592 54.6712 62450.25 0.00 67355.04 65769.25
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 34770.543 34770.543 1.499830 0.00030419 993.440 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 34770.54 34770.54 1.499830 21.11 14.76 0.00785765 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00785765 50.4397 34770.67 0.00 37483.83 37483.83
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 64714.142 -999.000 5.493234 0.00231140 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 unknown 7/21 15:00:00 64714.14 60476.00 5.493234 21.68 15.80 0.00878404 12.80 12.09 0.00850000 32.10 0.01411964 23.13 0.0000 21.11 0.00878404 56.3056 56078.58 0.00 64817.73 59744.09
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 35110.713 35110.713 1.514503 0.00030716 1003.159 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 35110.71 35110.71 1.514503 21.11 14.76 0.00785896 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00785896 50.4480 35110.84 0.00 37850.54 37850.54
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 10762.091 -999.000 0.957161 0.00038439 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 unknown 7/21 09:40:00 10762.09 10481.93 0.957161 21.68 15.64 0.00860834 12.80 12.09 0.00850000 28.87 0.01411382 22.22 0.0000 21.11 0.00860834 55.1940 9771.56 0.00 10780.19 10330.56
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 6020.243 6020.243 0.259682 0.00005267 172.007 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 6020.24 6020.24 0.259682 21.11 14.75 0.00784522 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00784522 50.3613 6020.29 0.00 6490.01 6490.01
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 10462.161 -999.000 0.929662 0.00037368 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 unknown 7/21 09:20:00 10462.16 10181.83 0.929662 21.68 15.65 0.00861160 12.80 12.09 0.00850000 28.45 0.01411307 22.10 0.0000 21.11 0.00861160 55.2147 9490.82 0.00 10479.74 10035.25
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 6037.838 6037.838 0.260440 0.00005282 172.510 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 6037.84 6037.84 0.260440 21.11 14.75 0.00784567 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00784567 50.3642 6037.88 0.00 6508.98 6508.98
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 13467.553 13467.553 0.691603 0.00011782 327.205 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 13467.55 13467.55 0.691603 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00788386 50.9519 9818.46 0.00 13537.64 13537.64
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 3093.841 -999.000 0.276262 0.00011050 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 unknown 7/21 16:30:00 3093.84 3023.96 0.276262 21.68 15.63 0.00859367 12.80 12.09 0.00850000 31.36 0.01411830 22.93 0.0000 21.11 0.00859367 55.1013 2820.34 0.00 3099.07 2979.67
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 1866.094 1866.094 0.080493 0.00001633 53.316 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 1866.09 1866.09 0.080493 21.11 14.77 0.00787456 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00787456 50.5473 1866.11 0.00 2011.71 2011.71
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 2994.656 -999.000 0.267172 0.00010696 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown 7/21 16:40:00 2994.66 2924.76 0.267172 21.68 15.63 0.00859687 12.80 12.09 0.00850000 31.26 0.01411813 22.90 0.0000 21.11 0.00859687 55.1215 2727.54 0.00 2999.71 2882.06
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 1871.975 1871.975 0.080747 0.00001638 53.484 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 1871.97 1871.97 0.080747 21.11 14.77 0.00787495 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00787495 50.5498 1871.99 0.00 2018.05 2018.05
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 14593.050 -999.000 1.281175 0.00052122 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 unknown 7/21 13:30:00 14593.05 14051.00 1.281175 21.68 15.69 0.00865636 12.80 12.09 0.00850000 31.92 0.01411931 23.08 0.0000 21.11 0.00865636 55.4983 13079.11 0.00 14617.25 13857.34
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 8900.143 8900.143 0.383906 0.00007786 254.285 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 8900.14 8900.14 0.383906 21.11 14.78 0.00787881 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.11 0.00787881 50.5741 8900.19 0.00 9594.64 9594.64
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 12419.553 12419.553 1.191515 0.00010865 272.833 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 12419.55 12419.55 1.191515 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00790579 51.0921 6132.64 0.00 12487.33 12487.33
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 12879.233 12879.233 1.250677 0.00011267 282.589 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:40:00 12879.23 12879.23 1.250677 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00790797 51.1060 6280.13 0.00 12950.48 12950.48
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 9116.716 9116.716 1.215586 0.00007976 194.365 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 9116.72 9116.72 1.215586 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00730224 47.2419 2712.42 0.00 9167.57 9167.57
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 8453.945 8453.945 0.389267 0.00007396 211.037 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:40:00 8453.95 8453.95 0.389267 16.70 13.18 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00792072 51.1872 6399.94 0.00 8497.54 8497.54
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 683001.775 -999.000 20.735361 0.02439524 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 683001.78 442038.99 20.735361 28.55 20.79 0.01219534 10.99 10.99 0.00850000 32.10 0.01411964 23.13 56.2395 23.99 0.00970705 52.1536 284788.07 0.00 683796.11 437534.34
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 206143.065 206143.065 6.220608 0.00180343 3402.469 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 206143.07 206143.07 6.220608 -10.70 -10.70 0.00150390 16.70 13.18 0.00800000 -10.70 0.00150390 -10.70 187.4649 21.00 0.00786191 50.8014 64092.50 0.00 176628.95 176628.95
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 86334.709 -999.000 2.051317 0.00308368 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 86334.71 51162.86 2.051317 32.10 23.13 0.01411964 11.94 11.74 0.00850000 32.10 0.01411964 23.13 99.9965 21.11 0.00864996 55.4568 167155.63 0.00 86433.83 51479.65
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 20393.415 20393.415 0.615395 0.00017841 336.601 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 20393.42 20393.42 0.615395 -10.70 -10.70 0.00150390 16.70 13.18 0.00800000 -10.70 0.00150390 -10.70 333.3216 21.11 0.00785840 50.4445 106707.68 0.00 17473.63 17473.63
SWHSYSLAUNDRY HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped unknown unknown 46710.097 34378.631 4.903586 -999.0 -999.000 unknown unknown unknown unknown 75921.46 -999.00 -999.0 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.00 -999.0 -999.00 -999.0000 -999.00 -999.0 -999.0000 -999.00 0.00 -999.00 -999.00
SWHSYS1 HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped unknown unknown 36917.323 27171.150 3.872570 -999.0 -999.000 unknown unknown unknown unknown 54370.95 -999.00 -999.0 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.00 -999.0 -999.00 -999.0000 -999.00 -999.0 -999.0000 -999.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 8003.050 8003.050 1.162825 0.00007001 169.566 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 1.7084 1.742791 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 8003.05 8003.05 1.0000 1.39957048 1.162825 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.07000703 60.00 32.22 27.78 0.000 8003.05 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00797372 21.00 0.00797372 51.5252 1866.57 0.00 8047.78 8047.78 1.39957048 16.60 13.15 0.00800000 36934.7 22.24 15.31 0.00800000 42684.9
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 3701.890 3701.890 0.196825 0.00003239 89.237 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 0.7902 0.806145 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 3701.89 3701.89 1.0000 0.23689704 0.196825 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.03238245 60.00 32.22 27.78 0.000 3701.89 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00784836 21.00 0.00784836 50.7263 2663.53 0.00 3721.21 3721.21 0.23689704 16.60 13.15 0.00800000 36934.7 32.00 18.70 0.00800000 52642.9
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1549.888 1549.888 0.121495 0.00001356 34.903 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 0.3309 0.337513 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 1549.89 1549.89 1.0000 0.14623046 0.121495 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.01355771 60.00 32.22 27.78 0.000 1549.89 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00782899 21.00 0.00782899 50.6020 908.92 0.00 1558.26 1558.26 0.14623046 16.60 13.15 0.00800000 36934.7 27.05 17.03 0.00800000 47591.0
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 2232.612 2232.612 0.102784 0.00001953 55.736 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 0.4766 0.486187 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 2232.61 2232.61 1.0000 0.12370990 0.102784 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.01952987 60.00 32.22 27.78 0.000 2232.61 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00778422 21.00 0.00778422 50.3162 1690.41 0.00 2244.13 2244.13 0.12370990 16.60 13.15 0.00800000 36934.7 34.39 19.46 0.00800000 55075.0
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 1383.477 1383.477 0.055294 0.00001210 36.001 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 0.2953 0.301274 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 1383.48 1383.48 1.0000 0.06655113 0.055294 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.01210202 60.00 32.22 27.78 0.000 1383.48 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00780656 21.00 0.00780656 50.4588 1091.78 0.00 1390.44 1390.44 0.06655113 16.60 13.15 0.00800000 36934.7 37.09 20.31 0.00800000 57827.5
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 11777.973 11777.973 1.820075 0.00010304 248.526 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 2.5142 2.564840 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 11777.97 11777.97 1.0000 2.19063257 1.820075 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.10302834 60.00 32.22 27.78 0.000 11777.97 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00777172 21.00 0.00777172 50.2371 2177.43 0.00 11843.89 11843.89 2.19063257 16.60 13.15 0.00800000 36934.7 21.90 15.19 0.00800000 42341.3
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 11124.434 11124.434 0.838113 0.00009732 251.924 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 2.3747 2.422522 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 11124.43 11124.43 1.0000 1.00874866 0.838113 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.09731148 60.00 32.22 27.78 0.000 11124.43 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00786641 21.00 0.00786641 50.8413 6702.69 0.00 11184.43 11184.43 1.00874866 16.60 13.15 0.00800000 36934.7 27.47 17.18 0.00800000 48022.2
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 29854.879 29854.879 2.615498 0.00026118 662.736 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 6.3731 6.501373 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 29854.88 29854.88 1.0000 3.14800018 2.615498 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.26115686 60.00 32.22 27.78 0.000 29854.88 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00784129 21.00 0.00784129 50.6805 16056.08 0.00 30017.12 30017.12 3.14800018 16.60 13.15 0.00800000 36934.7 25.95 16.65 0.00800000 46470.0
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 11742.449 -999.000 1.047078 0.00041941 -999.000 -999.0000 1.00000 1.00000 1020.8247 1004.8586 1.2036 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.047078 1.26025749   4197.9300 999.8980 34.51129336 13.37 6.70 6.67 966322.88 1.2152 1.215146 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 unknown unknown unknown 7/21 16:30:00 Sensible 11742.45 11463.14 1.0000 1.26025749 1.047078 21.68 15.64 0.00859876 43639.7 12.80 12.09 0.00850000 34322.2 0.41936246 6.70 13.37 6.67 0.000 11742.45 31.36 0.01411830 22.93 0.00000000 0.0000 21.11 0.00859876 21.11 0.00859876 55.1335 10689.52 0.00 11762.26 11296.08 1.26025749 21.68 15.64 0.00859876 43639.7 12.90 12.09 0.00845226 34306.5
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 6056.014 6056.014 0.261224 0.00005298 173.029 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.047078 1.26025749   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 1.2928 1.318793 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 6056.01 6056.01 1.0000 0.31440849 0.261224 21.11 14.75 0.00784611 41143.5 40.00 21.18 0.00800000 60796.0 0.05297525 60.00 32.22 27.78 0.000 6056.01 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00784611 21.11 0.00784611 50.3670 6056.06 0.00 6528.57 6528.57 0.31440849 16.60 13.00 0.00784611 36545.1 36.97 20.15 0.00784611 57309.7
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 11388.644 -999.000 1.014647 0.00040677 -999.000 -999.0000 1.00000 1.00000 1020.8306 1004.8586 1.2036 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.014647 1.22122398   4197.9300 999.8980 34.51129336 13.37 6.70 6.67 966322.88 1.1786 1.178533 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown unknown unknown 7/21 16:40:00 Sensible 11388.64 11109.22 1.0000 1.22122398 1.014647 21.68 15.64 0.00860195 43647.8 12.80 12.09 0.00850000 34322.2 0.40672689 6.70 13.37 6.67 0.000 11388.64 31.26 0.01411813 22.90 0.00000000 0.0000 21.11 0.00860195 21.11 0.00860195 55.1536 10358.44 0.00 11407.84 10947.81 1.22122398 21.68 15.64 0.00860195 43647.8 12.90 12.09 0.00845276 34306.5
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 6073.595 6073.595 0.261983 0.00005313 173.531 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.014647 1.22122398   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 1.2965 1.322621 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 6073.59 6073.59 1.0000 0.31532121 0.261983 21.11 14.75 0.00784656 41144.6 40.00 21.18 0.00800000 60796.0 0.05312904 60.00 32.22 27.78 0.000 6073.59 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00784656 21.11 0.00784656 50.3698 6073.64 0.00 6547.53 6547.53 0.31532121 16.60 13.00 0.00784656 36546.2 36.97 20.15 0.00784656 57310.9
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 67239.039 -999.000 6.116899 0.00240158 -999.000 -999.0000 1.00000 1.00000 1020.6893 1004.8586 1.2036 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 6.116899 7.36226838   4197.9300 999.8980 34.51129336 13.37 6.70 6.67 966322.88 6.9582 6.958107 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 unknown unknown unknown 7/21 13:20:00 Sensible 67239.04 66811.83 1.0000 7.36226838 6.116899 21.68 15.57 0.00852592 43455.1 12.80 12.09 0.00850000 34322.2 2.40133286 6.70 13.37 6.67 0.000 67239.04 31.85 0.01411920 23.06 0.00000000 0.0000 21.11 0.00852592 21.11 0.00852592 54.6712 62450.25 0.00 67355.04 65769.25 7.36226838 21.68 15.58 0.00852592 43455.1 12.93 12.09 0.00844061 34306.4
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 34770.543 34770.543 1.499830 0.00030419 993.440 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 6.116899 7.36226838   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 7.4225 7.571837 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 34770.54 34770.54 1.0000 1.80518727 1.499830 21.11 14.76 0.00785765 41172.9 40.00 21.18 0.00800000 60796.0 0.30415685 60.00 32.22 27.78 0.000 34770.54 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00785765 21.11 0.00785765 50.4397 34770.67 0.00 37483.83 37483.83 1.80518727 16.60 13.01 0.00785765 36574.3 36.97 20.16 0.00785765 57338.8
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 64714.142 -999.000 5.493234 0.00231140 -999.000 -999.0000 1.00000 1.00000 1021.1691 1004.8586 1.2036 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.493234 6.61162919   4197.9300 999.8980 34.51129336 13.37 6.70 6.67 966322.88 6.6969 6.696823 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 unknown unknown unknown 7/21 15:00:00 Sensible 64714.14 60476.00 1.0000 6.61162919 5.493234 21.68 15.80 0.00878404 44110.1 12.80 12.09 0.00850000 34322.2 2.31116025 6.70 13.37 6.67 0.000 64714.14 32.10 0.01411964 23.13 0.00000000 0.0000 21.11 0.00878404 21.11 0.00878404 56.3056 56078.58 0.00 64817.73 59744.09 6.61162919 21.68 15.80 0.00878404 44110.1 12.83 12.09 0.00848010 34306.5
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 35110.713 35110.713 1.514503 0.00030716 1003.159 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.493234 6.61162919   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 7.4951 7.645914 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 35110.71 35110.71 1.0000 1.82284790 1.514503 21.11 14.76 0.00785896 41176.3 40.00 21.18 0.00800000 60796.0 0.30713250 60.00 32.22 27.78 0.000 35110.71 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00785896 21.11 0.00785896 50.4480 35110.84 0.00 37850.54 37850.54 1.82284790 16.60 13.01 0.00785896 36577.7 36.97 20.16 0.00785896 57342.2
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 10762.091 -999.000 0.957161 0.00038439 -999.000 -999.0000 1.00000 1.00000 1020.8425 1004.8586 1.2036 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.957161 1.15203431   4197.9300 999.8980 34.51129336 13.37 6.70 6.67 966322.88 1.1137 1.113695 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 unknown unknown unknown 7/21 09:40:00 Sensible 10762.09 10481.93 1.0000 1.15203431 0.957161 21.68 15.64 0.00860834 43664.0 12.80 12.09 0.00850000 34322.2 0.38435055 6.70 13.37 6.67 0.000 10762.09 28.87 0.01411382 22.22 0.00000000 0.0000 21.11 0.00860834 21.11 0.00860834 55.1940 9771.56 0.00 10780.19 10330.56 1.15203431 21.68 15.65 0.00860834 43664.0 12.90 12.09 0.00845376 34306.5
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 6020.243 6020.243 0.259682 0.00005267 172.007 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.957161 1.15203431   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 1.2851 1.311003 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 6020.24 6020.24 1.0000 0.31255138 0.259682 21.11 14.75 0.00784522 41141.2 40.00 21.18 0.00800000 60796.0 0.05266234 60.00 32.22 27.78 0.000 6020.24 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00784522 21.11 0.00784522 50.3613 6020.29 0.00 6490.01 6490.01 0.31255138 16.60 13.00 0.00784522 36542.9 36.97 20.15 0.00784522 57307.5
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 10462.161 -999.000 0.929662 0.00037368 -999.000 -999.0000 1.00000 1.00000 1020.8485 1004.8586 1.2036 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.929662 1.11893627   4197.9300 999.8980 34.51129336 13.37 6.70 6.67 966322.88 1.0827 1.082657 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 unknown unknown unknown 7/21 09:20:00 Sensible 10462.16 10181.83 1.0000 1.11893627 0.929662 21.68 15.65 0.00861160 43672.3 12.80 12.09 0.00850000 34322.2 0.37363906 6.70 13.37 6.67 0.000 10462.16 28.45 0.01411307 22.10 0.00000000 0.0000 21.11 0.00861160 21.11 0.00861160 55.2147 9490.82 0.00 10479.74 10035.25 1.11893627 21.68 15.65 0.00861160 43672.3 12.90 12.09 0.00845427 34306.5
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 6037.838 6037.838 0.260440 0.00005282 172.510 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.929662 1.11893627   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 1.2889 1.314835 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 6037.84 6037.84 1.0000 0.31346485 0.260440 21.11 14.75 0.00784567 41142.3 40.00 21.18 0.00800000 60796.0 0.05281625 60.00 32.22 27.78 0.000 6037.84 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00784567 21.11 0.00784567 50.3642 6037.88 0.00 6508.98 6508.98 0.31346485 16.60 13.00 0.00784567 36544.0 36.97 20.15 0.00784567 57308.6
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 13467.553 13467.553 0.691603 0.00011782 327.205 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 2.8749 2.932773 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 13467.55 13467.55 1.0000 0.83240995 0.691603 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.11780801 60.00 32.22 27.78 0.000 13467.55 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00788386 21.00 0.00788386 50.9519 9818.46 0.00 13537.64 13537.64 0.83240995 16.60 13.15 0.00800000 36934.7 32.55 18.88 0.00800000 53197.9
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 3093.841 -999.000 0.276262 0.00011050 -999.000 -999.0000 1.00000 1.00000 1020.8152 1004.8586 1.2036 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.276262 0.33250751   4197.9300 999.8980 34.51129336 13.37 6.70 6.67 966322.88 0.3202 0.320160 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 unknown unknown unknown 7/21 16:30:00 Sensible 3093.84 3023.96 1.0000 0.33250751 0.276262 21.68 15.63 0.00859367 43626.8 12.80 12.09 0.00850000 34322.2 0.11049148 6.70 13.37 6.67 0.000 3093.84 31.36 0.01411830 22.93 0.00000000 0.0000 21.11 0.00859367 21.11 0.00859367 55.1013 2820.34 0.00 3099.07 2979.67 0.33250751 21.68 15.64 0.00859367 43626.8 12.90 12.09 0.00845146 34306.5
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 1866.094 1866.094 0.080493 0.00001633 53.316 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.276262 0.33250751   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 0.3984 0.406372 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 1866.09 1866.09 1.0000 0.09688153 0.080493 21.11 14.77 0.00787456 41215.7 40.00 21.18 0.00800000 60796.0 0.01632374 60.00 32.22 27.78 0.000 1866.09 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00787456 21.11 0.00787456 50.5473 1866.11 0.00 2011.71 2011.71 0.09688153 16.60 13.03 0.00787456 36617.1 36.97 20.17 0.00787456 57381.8
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 2994.656 -999.000 0.267172 0.00010696 -999.000 -999.0000 1.00000 1.00000 1020.8211 1004.8586 1.2036 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.267172 0.32156707   4197.9300 999.8980 34.51129336 13.37 6.70 6.67 966322.88 0.3099 0.309896 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown unknown unknown 7/21 16:40:00 Sensible 2994.66 2924.76 1.0000 0.32156707 0.267172 21.68 15.63 0.00859687 43634.9 12.80 12.09 0.00850000 34322.2 0.10694926 6.70 13.37 6.67 0.000 2994.66 31.26 0.01411813 22.90 0.00000000 0.0000 21.11 0.00859687 21.11 0.00859687 55.1215 2727.54 0.00 2999.71 2882.06 0.32156707 21.68 15.64 0.00859687 43634.9 12.90 12.09 0.00845196 34306.5
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 1871.975 1871.975 0.080747 0.00001638 53.484 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.267172 0.32156707   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 0.3996 0.407652 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 1871.97 1871.97 1.0000 0.09718683 0.080747 21.11 14.77 0.00787495 41216.7 40.00 21.18 0.00800000 60796.0 0.01637518 60.00 32.22 27.78 0.000 1871.97 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00787495 21.11 0.00787495 50.5498 1871.99 0.00 2018.05 2018.05 0.09718683 16.60 13.03 0.00787495 36618.1 36.97 20.17 0.00787495 57382.8
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 14593.050 -999.000 1.281175 0.00052122 -999.000 -999.0000 1.00000 1.00000 1020.9317 1004.8586 1.2036 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.281175 1.54201569   4197.9300 999.8980 34.51129336 13.37 6.70 6.67 966322.88 1.5102 1.510135 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 unknown unknown unknown 7/21 13:30:00 Sensible 14593.05 14051.00 1.0000 1.54201569 1.281175 21.68 15.69 0.00865636 43785.8 12.80 12.09 0.00850000 34322.2 0.52116704 6.70 13.37 6.67 0.000 14593.05 31.92 0.01411931 23.08 0.00000000 0.0000 21.11 0.00865636 21.11 0.00865636 55.4983 13079.11 0.00 14617.25 13857.34 1.54201569 21.68 15.69 0.00865636 43785.8 12.88 12.09 0.00846118 34306.5
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 8900.143 8900.143 0.383906 0.00007786 254.285 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.281175 1.54201569   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 1.8999 1.938147 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 8900.14 8900.14 1.0000 0.46206771 0.383906 21.11 14.78 0.00787881 41226.6 40.00 21.18 0.00800000 60796.0 0.07785439 60.00 32.22 27.78 0.000 8900.14 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.11 0.00787881 21.11 0.00787881 50.5741 8900.19 0.00 9594.64 9594.64 0.46206771 16.60 13.03 0.00787881 36627.9 36.97 20.18 0.00787881 57392.5
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 12419.553 12419.553 1.191515 0.00010865 272.833 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 2.6512 2.704554 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 12419.55 12419.55 1.0000 1.43410161 1.191515 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.10864058 60.00 32.22 27.78 0.000 12419.55 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00790579 21.00 0.00790579 51.0921 6132.64 0.00 12487.33 12487.33 1.43410161 16.60 13.15 0.00800000 36934.7 25.14 16.36 0.00800000 45642.2
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 12879.233 12879.233 1.250677 0.00011267 282.589 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 2.7493 2.804657 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:40:00 Sensible 12879.23 12879.23 1.0000 1.50530879 1.250677 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.11266165 60.00 32.22 27.78 0.000 12879.23 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00790797 21.00 0.00790797 51.1060 6280.13 0.00 12950.48 12950.48 1.50530879 16.60 13.15 0.00800000 36934.7 25.04 16.33 0.00800000 45537.9
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 9116.716 9116.716 1.215586 0.00007976 194.365 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 1.9461 1.985309 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 Sensible 9116.72 9116.72 1.0000 1.46307267 1.215586 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.07974887 60.00 32.22 27.78 0.000 9116.72 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.63 0.00730224 21.00 0.00730224 47.2419 2712.42 0.00 9167.57 9167.57 1.46307267 16.60 13.15 0.00800000 36934.7 22.74 15.50 0.00800000 43200.7
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 8453.945 8453.945 0.389267 0.00007396 211.037 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 1.8047 1.840980 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 11:40:00 Sensible 8453.95 8453.95 1.0000 0.46851977 0.389267 16.70 13.18 0.00800000 37036.7 40.00 21.18 0.00800000 60796.0 0.07395125 60.00 32.22 27.78 0.000 8453.95 -10.70 0.00150390 -10.70 0.00000000 0.0000 21.00 0.00792072 21.00 0.00792072 51.1872 6399.94 0.00 8497.54 8497.54 0.46851977 16.60 13.15 0.00800000 36934.7 34.39 19.46 0.00800000 55071.7
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 683001.775 -999.000 20.735361 0.02439524 -999.000 -999.0000 1.00000 1.00000 1027.5105 1004.8586 1.2036 VAV WITH REHEAT FAN Fan:VariableVolume 20.735361 24.95697608   4197.9300 999.8980 34.51129336 13.37 6.70 6.67 966322.88 70.6805 70.680493 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 Sensible 683001.78 442038.99 1.0000 24.95697608 20.735361 28.55 20.79 0.01219534 59840.2 10.99 10.99 0.00850000 32473.0 24.39275232 6.70 13.37 6.67 46460.450 636541.33 32.10 0.01411964 23.13 11.66146000 56.2395 23.99 0.00971689 23.99 0.00970705 52.1536 284788.07 0.00 683796.11 437534.34 24.95697608 28.55 20.79 0.01219534 59840.2 11.49 11.33 0.00828326 32441.2
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 206143.065 206143.065 6.220608 0.00180343 3402.469 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 VAV WITH REHEAT FAN Fan:VariableVolume 20.735361 24.95697608   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 44.0053 44.890918 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 206143.07 206143.07 1.0000 7.48709282 6.220608 -10.70 -10.70 0.00150390 -7020.5 16.70 13.18 0.00800000 37036.7 1.80324549 60.00 32.22 27.78 0.000 206143.07 -10.70 0.00150390 -10.70 11.66146000 187.4649 20.98 0.00785805 21.00 0.00786191 50.8014 64092.50 0.00 176628.95 176628.95 7.48709282 2.80 -1.97 0.00150390 6582.5 26.21 10.51 0.00150390 30173.7
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 86334.709 -999.000 2.051317 0.00308368 -999.000 -999.0000 1.00000 1.00000 1031.0877 1004.8586 1.2036 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.46886833   4197.9300 999.8980 34.51129336 13.37 6.70 6.67 966322.88 8.9344 8.934354 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 Sensible 86334.71 51162.86 1.0000 2.46895513 2.051317 32.10 23.13 0.01411964 68410.3 11.94 11.74 0.00850000 33442.2 3.08336118 6.70 13.37 6.67 2195.006 84139.70 32.10 0.01411964 23.13 2.05124512 99.9965 21.11 0.00864548 21.11 0.00864996 55.4568 167155.63 0.00 86433.83 51479.65 2.46895513 32.10 23.14 0.01411964 68410.3 11.88 11.73 0.00850831 33402.0
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 20393.415 20393.415 0.615395 0.00017841 336.601 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.46886833   4197.9300 999.8980 4.01694945 54.44 82.22 27.78 468450.60 4.3534 4.440989 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:00:00 Sensible 20393.42 20393.42 1.0000 0.74068654 0.615395 -10.70 -10.70 0.00150390 -7020.5 16.70 13.18 0.00800000 37036.7 0.17839229 60.00 32.22 27.78 0.000 20393.42 -10.70 0.00150390 -10.70 2.05124512 333.3216 21.11 0.00785778 21.11 0.00785840 50.4445 106707.68 0.00 17473.63 17473.63 0.74068654 2.80 -1.97 0.00150390 6582.5 26.21 10.51 0.00150390 30173.7
SWHSYSLAUNDRY HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped unknown unknown unknown N/A N/A N/A N/A No No unknown No 46710.097 34378.631 4.903586 -999.0 -999.000 -999.0000 1.00000 1.00000 1004.8586 1004.8586 1.2036 SWHSYSLAUNDRY HPWH FAN Fan:SystemModel 4.903586 5.90193210   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 unknown unknown unknown unknown unknown unknown Sensible 75921.46 -999.00 1.0000 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0 -999.0 -999.00 -999.00 -999.00 0.000 75921.46 -999.00 -999.0 -999.00 -999.0 -999.0000 -999.00 -999.0 -999.00 -999.0 -999.0000 -999.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
SWHSYS1 HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped unknown unknown unknown N/A N/A N/A N/A No No unknown No 36917.323 27171.150 3.872570 -999.0 -999.000 -999.0000 1.00000 1.00000 1004.8586 1004.8586 1.2036 SWHSYS1 HPWH FAN Fan:SystemModel 3.872570 4.66100528   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 unknown unknown unknown unknown unknown unknown Sensible 54370.95 -999.00 1.0000 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0 -999.0 -999.00 -999.00 -999.00 0.000 54370.95 -999.00 -999.0 -999.00 -999.0 -999.0000 -999.00 -999.0 -999.00 -999.0 -999.0000 -999.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 0.00 20.74 -      
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 319.00 7803.67 0.00
RETAIL_1_FLR_1 2436.83 6879.50 1286.33
RETAIL_2_FLR_1 1513.67 6401.17 95.50
MECH_FLR_1 1195.00 7427.67 898.00
STORAGE_FLR_1 1177.83 7863.17 1094.17
LAUNDRY_FLR_1 6374.83 3434.00 2465.50
CAFE_FLR_1 3104.33 5982.50 1117.67
LOBBY_FLR_1 2400.67 6131.33 853.17
ROOM_1_FLR_3 1746.83 8162.67 1666.17
ROOM_2_FLR_3 2871.50 7877.67 2547.17
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 1197.33 8699.83 1182.50
ROOM_5_FLR_3 1647.33 8099.83 1632.33
ROOM_6_FLR_3 2702.67 7910.00 2463.17
CORRIDOR_FLR_3 1106.33 7687.17 1008.67
ROOM_1_FLR_6 2525.50 8062.17 2327.17
ROOM_2_FLR_6 3582.83 7788.00 3173.67
ROOM_3_MULT9_FLR_6 1219.33 8040.17 1063.83
BANQUET_FLR_6 4104.00 3854.00 862.67
DINING_FLR_6 4805.00 2751.50 770.33
KITCHEN_FLR_6 7961.00 6552.00 6145.33
CORRIDOR_FLR_6 1800.00 6898.00 862.17
Facility 8698.00 8760.00 7904.33
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 3.33 0.00 3.33
CAFE_FLR_1 0.00 0.00 0.00 0.00
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 0.00 16.83 0.00 16.83
ROOM_2_FLR_3 0.00 24.50 0.00 24.50
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.33 58.33 0.33 58.33
ROOM_5_FLR_3 0.00 5.67 0.00 5.67
ROOM_6_FLR_3 0.00 35.83 0.00 35.83
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 19.67 0.00 19.67
ROOM_2_FLR_6 0.00 29.33 0.00 29.33
ROOM_3_MULT9_FLR_6 0.00 17.50 0.00 17.50
BANQUET_FLR_6 0.00 0.00 0.00 0.00
DINING_FLR_6 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 0.00 13.00 0.00 13.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 0.33 114.50 0.33 114.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.76 106.50 4826.41 0.888 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 2.744 0.034 0.000 0.000
RETAIL_2_FLR_1 7.27 12.54 307.76 1.461 0.011 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.578 0.013 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.537 0.013 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 24.156 0.037 0.000 0.000
CAFE_FLR_1 82.52 142.30 748.35 4.165 0.027 0.000 0.000
LOBBY_FLR_1 244.96 422.44 5183.56 1.892 0.011 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.355 0.044 0.000 0.065
ROOM_2_FLR_3 0.95 1.50 118.93 0.355 0.044 0.000 0.061
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.403 0.020 0.000 0.104
ROOM_5_FLR_3 0.95 1.50 118.94 0.355 0.044 0.000 0.065
ROOM_6_FLR_3 0.95 1.50 118.93 0.355 0.044 0.000 0.066
CORRIDOR_FLR_3 12.15 20.96 1186.91 0.532 0.005 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.355 0.044 0.000 0.079
ROOM_2_FLR_6 0.95 1.50 118.93 0.355 0.044 0.000 0.068
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.403 0.036 0.000 0.126
BANQUET_FLR_6 144.91 249.90 1010.89 4.888 0.013 0.000 0.000
DINING_FLR_6 144.91 249.90 1010.89 5.253 0.013 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 21.223 0.037 0.000 0.000
CORRIDOR_FLR_6 12.86 22.18 1256.16 1.138 0.009 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.76 106.50 4826.41 0.687 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 2.112 0.001 0.000 0.000
RETAIL_2_FLR_1 7.27 12.54 307.76 1.383 0.000 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.553 0.000 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.499 0.000 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 20.691 0.001 0.000 0.000
CAFE_FLR_1 82.52 142.30 748.35 3.928 0.000 0.000 0.000
LOBBY_FLR_1 244.96 422.44 5183.56 1.773 0.000 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.000 0.001 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.000 0.001 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.000 0.000 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.000 0.001 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.000 0.001 0.000 0.000
CORRIDOR_FLR_3 12.15 20.96 1186.91 0.416 0.000 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.000 0.001 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.000 0.001 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.000 0.001 0.000 0.000
BANQUET_FLR_6 144.91 249.90 1010.89 4.140 0.000 0.000 0.000
DINING_FLR_6 144.91 249.90 1010.89 4.351 0.000 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 13.633 0.001 0.000 0.000
CORRIDOR_FLR_6 12.86 22.18 1256.16 1.005 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.76 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.27 12.54 307.76 77.67 0.0000 0.092
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.52 142.30 748.35 188.86 0.0000 0.676
LOBBY_FLR_1 VAV WITH REHEAT 244.96 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.15 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 144.91 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 144.91 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.90 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.86 22.18 1256.16 412.12 0.0000 0.126
Total Facility   872.83 1604.23 35184.81 11345.29 0.0000 137.584


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 36922829.53 0.00 36922829.53 0.00 36922829.53 26946214.98 0.00 0.00 8760.00 0.00
RETAIL_1_FLR_1 6303393.16 0.00 6303393.16 78790.55 6382183.71 2498216.28 0.00 0.00 8760.00 0.00
RETAIL_2_FLR_1 3875712.74 0.00 3875712.74 30413.25 3906125.99 2892943.94 0.00 0.00 8760.00 0.00
MECH_FLR_1 3249994.56 0.00 3249994.56 71878.86 3321873.42 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 1743778.33 0.00 1743778.33 41470.14 1785248.47 1821682.01 8754.83 3.50 1.67 0.00
LAUNDRY_FLR_1 64398000.37 0.00 64398000.37 98146.91 64496147.27 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 26838179.14 0.00 26838179.14 174170.96 27012350.10 21330615.53 0.00 0.00 8760.00 0.00
LOBBY_FLR_1 84331307.72 0.00 84331307.72 497646.22 84828953.95 59728886.00 0.00 0.00 8760.00 0.00
ROOM_1_FLR_3 1460156.71 66918.31 1527075.02 45732.42 1572807.44 1946875.62 2190.00 5869.33 700.67 0.00
ROOM_2_FLR_3 1459985.63 62268.29 1522253.93 45728.93 1567982.85 1946647.51 2190.00 5925.89 644.11 0.00
ROOM_3_MULT19_FLR_3 1099911.97 0.00 1099911.97 12759.86 1112671.83 26397887.27 8395.00 365.00 0.00 365.00
ROOM_4_MULT19_FLR_3 19803829.30 66933.68 19870762.97 12763.35 19883526.32 26405105.73 2190.00 5882.72 687.28 0.00
ROOM_5_FLR_3 1460156.71 66970.37 1527127.08 45732.42 1572859.50 1946875.62 2190.00 5869.33 700.67 0.00
ROOM_6_FLR_3 1459985.63 66996.35 1526981.98 45728.93 1572710.91 1946647.51 2190.00 5872.97 697.03 0.00
CORRIDOR_FLR_3 21808730.93 0.00 21808730.93 55299.69 21864030.62 14972100.18 0.00 0.00 8760.00 0.00
ROOM_1_FLR_6 365039.18 81422.52 446461.69 45741.96 492203.65 486718.90 2014.42 5868.46 877.12 0.00
ROOM_2_FLR_6 364996.41 69634.96 434631.37 45738.47 480369.84 486661.88 2045.73 5965.59 748.68 0.00
ROOM_3_MULT9_FLR_6 2345190.31 81406.69 2426597.00 23403.19 2450000.18 3126920.42 2190.00 5867.33 702.67 0.00
BANQUET_FLR_6 42371235.50 0.00 42371235.50 111690.36 42482925.86 37458366.31 0.00 4346.20 4413.80 0.00
DINING_FLR_6 45522749.65 0.00 45522749.65 111690.36 45634440.02 37458366.31 0.00 0.00 8760.00 0.00
KITCHEN_FLR_6 57314972.45 0.00 57314972.45 99988.77 57414961.22 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 12347393.63 0.00 12347393.63 97863.43 12445257.06 3961413.96 0.00 0.00 8760.00 0.00
Total Facility 0.21E+10 7023290.24 0.21E+10 4608511.80 0.21E+10 0.43E+10 8760.00 7942.24 8760.00 365.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.1708 0.0000 1.1708 0.0000 1.1708 0.8545 0.00 0.00 8760.00
RETAIL_1_FLR_1 0.1999 0.0000 0.1999 0.0025 0.2024 0.0792 0.00 0.00 8760.00
RETAIL_2_FLR_1 0.1229 0.0000 0.1229 0.0010 0.1239 0.0917 0.00 0.00 8760.00
MECH_FLR_1 0.1031 0.0000 0.1031 0.0023 0.1053 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.0553 0.0000 0.0553 0.0013 0.0566 0.0578 8754.83 3.50 1.67
LAUNDRY_FLR_1 2.0420 0.0000 2.0420 0.0031 2.0452 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 0.8510 0.0000 0.8510 0.0055 0.8566 0.6764 0.00 0.00 8760.00
LOBBY_FLR_1 2.6741 0.0000 2.6741 0.0158 2.6899 1.8940 0.00 0.00 8760.00
ROOM_1_FLR_3 0.0463 0.0021 0.0484 0.0015 0.0499 0.0617 2190.00 5869.33 700.67
ROOM_2_FLR_3 0.0463 0.0020 0.0483 0.0015 0.0497 0.0617 2190.00 5925.89 644.11
ROOM_4_MULT19_FLR_3 0.6280 0.0021 0.6301 0.0004 0.6305 0.8373 2190.00 5882.72 687.28
ROOM_5_FLR_3 0.0463 0.0021 0.0484 0.0015 0.0499 0.0617 2190.00 5869.33 700.67
ROOM_6_FLR_3 0.0463 0.0021 0.0484 0.0015 0.0499 0.0617 2190.00 5872.97 697.03
CORRIDOR_FLR_3 0.6916 0.0000 0.6916 0.0018 0.6933 0.4748 0.00 0.00 8760.00
ROOM_1_FLR_6 0.0116 0.0026 0.0142 0.0015 0.0156 0.0154 2014.42 5868.46 877.12
ROOM_2_FLR_6 0.0116 0.0022 0.0138 0.0015 0.0152 0.0154 2045.73 5965.59 748.68
ROOM_3_MULT9_FLR_6 0.0744 0.0026 0.0769 0.0007 0.0777 0.0992 2190.00 5867.33 702.67
BANQUET_FLR_6 1.3436 0.0000 1.3436 0.0035 1.3471 1.1878 0.00 4346.20 4413.80
DINING_FLR_6 1.4435 0.0000 1.4435 0.0035 1.4471 1.1878 0.00 0.00 8760.00
KITCHEN_FLR_6 1.8174 0.0000 1.8174 0.0032 1.8206 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.3915 0.0000 0.3915 0.0031 0.3946 0.1256 0.00 0.00 8760.00
Total Facility 64.1408 0.2227 64.3635 0.1154 64.4789 73.9670 8760.00 7942.24 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.59E+09 0.00 0.59E+09 0.22E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 43197387.25 562551.16 43759938.41 64690340.46 8699.72 31.84 28.44 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 18.6973 0.0000 18.6973 6.9969 0.00 0.00 8760.00
FLR_3_DOAS 1.3698 0.0178 1.3876 2.0513 8699.72 31.84 28.44


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 0.00 3242.40 0.00 0.00 0.00 5517.60 0.00 0.00 0.00
FLR_3_DOAS 0.00 0.00 0.00 0.00 6935.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 0.0000 18.8926 0.0000 0.0000 0.0000 18.5859 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 0.0000 0.0000 0.0000 1.7302 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1363
Defaulted Fields 1208
Fields with Defaults 4115
Autosized Fields 353
Autosizable Fields 407
Autocalculated Fields 289
Autocalculatable Fields 549



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 5691.35 69017.21 14-NOV-03:40 463186.21 04-AUG-19:20
Electricity:Building 2338.65 30592.50 03-JUN-05:00 138695.41 02-JAN-20:10
Electricity:Zone:BASEMENT 256.48 3058.02 02-JAN-02:10 18903.76 02-JAN-20:10
Electricity:SpaceType:GENERAL 2331.56 30451.35 03-JUN-05:00 138454.08 02-JAN-20:10
InteriorLights:Electricity 603.42 5169.18 03-JUN-05:00 50471.22 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 113.37 1030.12 02-JAN-02:10 9271.23 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 603.42 5169.18 03-JUN-05:00 50471.22 02-JAN-20:10
LightsWired:InteriorLights:Electricity 603.42 5169.18 03-JUN-05:00 50471.22 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 113.37 1030.12 02-JAN-02:10 9271.23 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 603.42 5169.18 03-JUN-05:00 50471.22 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 16.45 201.26 02-JAN-02:10 1197.92 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 6.26 56.92 02-JAN-02:10 512.31 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 6.26 56.92 02-JAN-02:10 512.31 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 19.05 233.06 02-JAN-02:10 1387.19 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 7.25 65.92 02-JAN-02:10 593.26 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 7.25 65.92 02-JAN-02:10 593.26 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 20.84 252.75 02-JAN-02:10 1523.62 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 8.37 76.02 02-JAN-02:10 684.18 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 8.37 76.02 02-JAN-02:10 684.18 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 5.46 67.94 02-JAN-02:10 394.77 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 1.87 16.96 02-JAN-02:10 152.61 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 1.87 16.96 02-JAN-02:10 152.61 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 72.84 1007.22 02-JAN-02:10 4973.49 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.90 44.52 02-JAN-02:10 400.68 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.90 44.52 02-JAN-02:10 400.68 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 27.25 277.68 03-JUN-05:00 2538.73 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 12.91 74.47 03-JUN-05:00 1573.46 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 12.91 74.47 03-JUN-05:00 1573.46 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 271.88 3211.03 10-JUN-05:00 20674.59 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 122.88 1099.62 10-JUN-05:00 10645.38 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 122.88 1099.62 10-JUN-05:00 10645.38 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 18.46 262.96 01-JAN-02:10 1214.21 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 6.17 52.24 01-JAN-02:10 474.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 6.17 52.24 01-JAN-02:10 474.96 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 18.46 262.93 01-JAN-02:10 1214.07 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 6.17 52.24 01-JAN-02:10 474.90 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 6.17 52.24 01-JAN-02:10 474.90 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 302.44 4545.27 01-JAN-02:10 20822.55 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 73.68 623.81 01-JAN-02:10 5671.40 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 73.68 623.81 01-JAN-02:10 5671.40 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 302.52 4546.52 01-JAN-02:10 20828.25 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 73.70 623.98 01-JAN-02:10 5672.95 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 73.70 623.98 01-JAN-02:10 5672.95 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 18.46 262.96 01-JAN-02:10 1214.21 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 6.17 52.24 01-JAN-02:10 474.96 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 6.17 52.24 01-JAN-02:10 474.96 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 18.46 262.93 01-JAN-02:10 1214.07 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 6.17 52.24 01-JAN-02:10 474.90 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 6.17 52.24 01-JAN-02:10 474.90 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 56.74 515.56 02-JAN-02:10 4640.01 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 56.74 515.56 02-JAN-02:10 4640.01 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 56.74 515.56 02-JAN-02:10 4640.01 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 4.62 65.74 01-JAN-02:10 303.55 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.54 13.06 01-JAN-02:10 118.74 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.54 13.06 01-JAN-02:10 118.74 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 4.62 65.73 01-JAN-02:10 303.52 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.54 13.06 01-JAN-02:10 118.73 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.54 13.06 01-JAN-02:10 118.73 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 35.82 538.40 01-JAN-02:10 2466.50 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 8.73 73.89 01-JAN-02:10 671.80 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 8.73 73.89 01-JAN-02:10 671.80 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 204.17 2433.51 03-JUN-05:00 9511.03 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 28.31 184.21 03-JUN-05:00 2763.12 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 28.31 184.21 03-JUN-05:00 2763.12 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 204.17 2433.51 03-JUN-05:00 9511.03 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 28.31 184.21 03-JUN-05:00 2763.12 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 28.31 184.21 03-JUN-05:00 2763.12 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 444.45 5944.83 02-JAN-02:10 18636.09 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.34 121.20 02-JAN-02:10 1090.83 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 13.34 121.20 02-JAN-02:10 1090.83 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 15.01 136.41 02-JAN-02:10 1227.68 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 15.01 136.41 02-JAN-02:10 1227.68 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 15.01 136.41 02-JAN-02:10 1227.68 02-JAN-20:10
InteriorEquipment:Electricity 1728.14 25282.18 02-JAN-02:10 88863.15 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1728.14 25282.18 02-JAN-02:10 88863.15 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 952.41 15101.09 02-JAN-02:10 59188.31 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 952.41 15101.09 02-JAN-02:10 59188.31 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 424.02 5682.48 01-JAN-00:10 16179.04 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
Refrigeration:Electricity 43.88 732.84 15-MAR-22:30 2790.48 17-SEP-10:20
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
Electricity:Plant 1798.08 2144.51 13-APR-02:40 242065.56 04-AUG-19:00
LowTempRefrigeration:Refrigeration:Electricity 15.72 0.00 01-JAN-11:10 1320.20 22-JUN-10:40
MedTempRefrigeration:Refrigeration:Electricity 21.07 600.19 06-FEB-04:10 719.28 28-MAY-14:00
WaterSystems:Electricity 489.84 1086.57 02-SEP-00:20 43132.15 01-SEP-21:00
Electricity:HVAC 761.37 13357.75 12-JAN-15:00 46524.58 04-AUG-20:20
Fans:Electricity 550.32 12436.92 25-NOV-08:10 36355.97 18-AUG-21:10
General:Fans:Electricity 550.32 12436.92 25-NOV-08:10 36355.97 18-AUG-21:10
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ExteriorEquipment:Electricity 641.49 9451.24 02-JAN-02:20 39155.93 02-JAN-07:20
Transformer:ExteriorEquipment:Electricity 22.46 386.37 03-JUN-05:00 1283.34 15-JUN-20:10
ElectricityPurchased:Facility 5691.35 69017.21 14-NOV-03:40 463186.21 04-AUG-19:20
ElectricityPurchased:Plant 5691.35 69017.21 14-NOV-03:40 463186.21 04-AUG-19:20
Cogeneration:ElectricityPurchased 5691.35 69017.21 14-NOV-03:40 463186.21 04-AUG-19:20
General:Cogeneration:ElectricityPurchased 5691.35 69017.21 14-NOV-03:40 463186.21 04-AUG-19:20
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 5691.35 69017.21 14-NOV-03:40 463186.21 04-AUG-19:20
ElectricityNet:Plant 5691.35 69017.21 14-NOV-03:40 463186.21 04-AUG-19:20
Cogeneration:ElectricityNet 5691.35 69017.21 14-NOV-03:40 463186.21 04-AUG-19:20
General:Cogeneration:ElectricityNet 5691.35 69017.21 14-NOV-03:40 463186.21 04-AUG-19:20
ExteriorLights:Electricity 174.22 0.00 01-JAN-07:30 11096.45 01-JAN-00:10
General:ExteriorLights:Electricity 174.22 0.00 01-JAN-07:30 11096.45 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 616.11 9046.01 01-JAN-00:10 37691.69 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 2.91 18.80 01-JAN-00:10 188.00 01-JAN-07:10
HeatRecovery:Electricity 188.60 0.00 03-JAN-08:50 9938.94 29-MAY-18:40
General:HeatRecovery:Electricity 188.60 0.00 03-JAN-08:50 9938.94 29-MAY-18:40
Water Heater:WaterSystems:Electricity 90.75 1086.57 02-SEP-00:20 4738.76 02-OCT-18:10
Water Heater Parasitic:WaterSystems:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 1150.62 0.00 01-JAN-00:10 196240.11 04-AUG-19:10
General:Cooling:Electricity 1150.62 0.00 01-JAN-00:10 196240.11 04-AUG-19:10
Pumps:Electricity 120.83 51.18 01-NOV-07:30 7534.60 11-AUG-21:00
General:Pumps:Electricity 120.83 51.18 01-NOV-07:30 7534.60 11-AUG-21:00
WIRED_LTG_ELECTRICITY 21.24 0.00 01-JAN-00:10 1776.59 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 3806.08 29270.80 07-APR-01:10 422891.71 06-FEB-19:10
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 2017.24 15908.90 07-APR-10:10 344770.77 05-FEB-24:00
WaterSystems:NaturalGas 1132.48 15908.90 01-JAN-09:10 136843.69 06-FEB-21:50
Water Heater:WaterSystems:NaturalGas 1132.48 15908.90 01-JAN-09:10 136843.69 06-FEB-21:50
Heating:NaturalGas 884.76 0.00 02-MAR-21:00 232046.90 06-FEB-09:10
Boiler:Heating:NaturalGas 884.76 0.00 02-MAR-21:00 232046.90 06-FEB-09:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 3725.04 0.00 01-JAN-00:10 709188.43 11-AUG-22:00
PlantLoopCoolingDemand:HVAC 3725.04 0.00 01-JAN-00:10 709188.43 11-AUG-22:00
CoolingCoils:PlantLoopCoolingDemand 3725.04 0.00 01-JAN-00:10 709188.43 11-AUG-22:00


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 02-MAR-21:50
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 02-MAR-21:50
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 02-MAR-21:50
Water Heater:WaterSystems:Water 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:20
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 02-MAR-21:50
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 02-MAR-21:50
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 02-MAR-21:50
Water Heater:WaterSystems:MainsWater 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:20
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 22-MAY-06:30
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 22-MAY-06:30


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 24281.28 131267.75 06-MAR-14:50 2873724.17 03-AUG-20:20
EnergyTransfer:Building 4965.19 79077.49 15-JAN-15:00 331225.65 19-JUN-18:10
EnergyTransfer:Zone:KITCHEN_FLR_6 695.28 9955.98 06-FEB-04:00 35208.24 09-JUL-10:40
Refrigeration:EnergyTransfer 183.23 3970.98 06-FEB-04:00 10379.00 10-NOV-07:30
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 91.62 1985.49 06-FEB-04:00 5189.50 10-NOV-07:30
General:Refrigeration:EnergyTransfer 91.62 1985.49 06-FEB-04:00 5189.50 10-NOV-07:30
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 91.62 1985.49 06-FEB-04:00 5189.50 10-NOV-07:30
EnergyTransfer:Plant 10278.00 16496.83 19-OCT-01:20 1642069.86 11-AUG-22:00
LowTempRefrigeration:Refrigeration:EnergyTransfer 21.61 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 70.01 1746.31 06-FEB-04:10 2577.61 28-MAY-14:00
EnergyTransfer:HVAC 9038.09 1546.69 08-MAY-14:40 1077527.01 03-AUG-20:20
CoolingCoils:EnergyTransfer 4929.12 0.00 01-JAN-00:10 836974.30 11-AUG-22:00
EnergyTransfer:Zone:BASEMENT 337.56 5214.24 28-MAY-13:50 17577.41 27-OCT-21:00
Heating:EnergyTransfer 121.92 0.00 03-JAN-18:20 84202.96 14-JAN-16:10
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 121.92 0.00 03-JAN-18:20 84202.96 14-JAN-16:10
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 4751.65 65889.28 08-JAN-15:00 327604.06 19-JUN-18:10
Cooling:EnergyTransfer:Zone:BASEMENT 337.56 5214.24 28-MAY-13:50 17577.41 27-OCT-21:00
General:Cooling:EnergyTransfer 4751.65 65889.28 08-JAN-15:00 327604.06 19-JUN-18:10
General:Cooling:EnergyTransfer:Zone:BASEMENT 337.56 5214.24 28-MAY-13:50 17577.41 27-OCT-21:00
EnergyTransfer:Zone:RETAIL_1_FLR_1 41.35 0.01 15-FEB-19:00 3981.32 04-OCT-12:10
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.70 0.00 01-JAN-08:20 1149.08 02-JAN-07:10
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.70 0.00 01-JAN-08:20 1149.08 02-JAN-07:10
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 40.65 0.00 01-JAN-00:10 3981.32 04-OCT-12:10
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 40.65 0.00 01-JAN-00:10 3981.32 04-OCT-12:10
EnergyTransfer:Zone:RETAIL_2_FLR_1 34.34 251.25 02-JAN-15:00 2044.12 18-AUG-21:00
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 34.34 251.25 02-JAN-15:00 2044.12 18-AUG-21:00
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 34.34 251.25 02-JAN-15:00 2044.12 18-AUG-21:00
EnergyTransfer:Zone:MECH_FLR_1 23.50 0.06 12-JAN-14:30 1705.12 18-AUG-20:00
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.19 0.00 01-JAN-19:10 463.94 02-JAN-15:00
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.19 0.00 01-JAN-19:10 463.94 02-JAN-15:00
Cooling:EnergyTransfer:Zone:MECH_FLR_1 23.32 0.00 01-JAN-00:10 1705.12 18-AUG-20:00
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 23.32 0.00 01-JAN-00:10 1705.12 18-AUG-20:00
EnergyTransfer:Zone:STORAGE_FLR_1 11.70 0.01 01-FEB-12:20 733.29 08-JUL-10:40
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.37 0.00 03-JAN-18:20 415.76 06-FEB-16:00
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.37 0.00 03-JAN-18:20 415.76 06-FEB-16:00
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 11.33 0.00 01-JAN-00:10 733.29 08-JUL-10:40
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 11.33 0.00 01-JAN-00:10 733.29 08-JUL-10:40
EnergyTransfer:Zone:LAUNDRY_FLR_1 598.14 8917.82 02-JAN-05:00 38815.87 04-AUG-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 598.14 8917.82 02-JAN-05:00 38815.87 04-AUG-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 598.14 8917.82 02-JAN-05:00 38815.87 04-AUG-20:00
EnergyTransfer:Zone:CAFE_FLR_1 237.38 7.74 08-JAN-15:50 14032.87 30-SEP-12:40
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 10.30 08-JAN-15:40
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 10.30 08-JAN-15:40
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 237.38 0.00 08-JAN-15:40 14032.87 30-SEP-12:40
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 237.38 0.00 08-JAN-15:40 14032.87 30-SEP-12:40
EnergyTransfer:Zone:LOBBY_FLR_1 791.94 8734.75 08-JAN-16:00 42005.26 04-AUG-21:10
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 791.94 8734.75 08-JAN-16:00 42005.26 04-AUG-21:10
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 791.94 8734.75 08-JAN-16:00 42005.26 04-AUG-21:10
EnergyTransfer:Zone:ROOM_1_FLR_3 65.06 0.00 01-JAN-08:10 11615.94 02-AUG-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 14.11 0.00 01-JAN-08:10 6344.79 14-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 14.11 0.00 01-JAN-08:10 6344.79 14-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 50.95 0.00 01-JAN-00:10 11615.94 02-AUG-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 50.95 0.00 01-JAN-00:10 11615.94 02-AUG-15:10
EnergyTransfer:Zone:ROOM_2_FLR_3 56.33 0.00 01-JAN-08:10 10983.25 02-AUG-15:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 18.42 0.00 01-JAN-08:10 6458.33 14-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 18.42 0.00 01-JAN-08:10 6458.33 14-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 37.91 0.00 01-JAN-00:10 10983.25 02-AUG-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 37.91 0.00 01-JAN-00:10 10983.25 02-AUG-15:10
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 299.22 0.00 01-JAN-00:10 52021.22 04-OCT-12:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 299.22 0.00 01-JAN-00:10 52021.22 04-OCT-12:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 299.22 0.00 01-JAN-00:10 52021.22 04-OCT-12:10
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 376.71 0.00 01-JAN-08:10 67112.89 19-JUN-15:10
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 29.21 0.00 01-JAN-08:10 42098.22 06-FEB-16:10
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 29.21 0.00 01-JAN-08:10 42098.22 06-FEB-16:10
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 347.50 0.00 01-JAN-00:10 67112.89 19-JUN-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 347.50 0.00 01-JAN-00:10 67112.89 19-JUN-15:10
EnergyTransfer:Zone:ROOM_5_FLR_3 64.48 0.00 01-JAN-08:10 10673.57 22-AUG-08:10
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 13.93 0.00 01-JAN-08:10 6392.78 14-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 13.93 0.00 01-JAN-08:10 6392.78 14-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 50.55 0.00 01-JAN-00:10 10673.57 22-AUG-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 50.55 0.00 01-JAN-00:10 10673.57 22-AUG-08:10
EnergyTransfer:Zone:ROOM_6_FLR_3 55.57 0.00 01-JAN-08:10 10804.69 29-MAY-09:00
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 17.96 0.00 01-JAN-08:10 6535.83 14-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 17.96 0.00 01-JAN-08:10 6535.83 14-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 37.61 0.00 01-JAN-00:10 10804.69 29-MAY-09:00
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 37.61 0.00 01-JAN-00:10 10804.69 29-MAY-09:00
EnergyTransfer:Zone:CORRIDOR_FLR_3 154.69 0.20 05-FEB-05:10 9242.35 24-AUG-17:00
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 1.21 0.00 01-JAN-08:00 3865.64 14-JAN-16:30
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 1.21 0.00 01-JAN-08:00 3865.64 14-JAN-16:30
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 153.47 0.00 01-JAN-00:10 9242.35 24-AUG-17:00
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 153.47 0.00 01-JAN-00:10 9242.35 24-AUG-17:00
EnergyTransfer:Zone:ROOM_1_FLR_6 18.34 0.00 01-JAN-08:10 3094.35 02-AUG-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 5.64 0.00 01-JAN-08:10 2066.85 14-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 5.64 0.00 01-JAN-08:10 2066.85 14-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 12.69 0.00 01-JAN-00:10 3094.35 02-AUG-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 12.69 0.00 01-JAN-00:10 3094.35 02-AUG-15:10
EnergyTransfer:Zone:ROOM_2_FLR_6 16.68 0.00 01-JAN-08:10 2937.39 02-AUG-15:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 7.05 0.00 01-JAN-08:10 2094.44 14-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 7.05 0.00 01-JAN-08:10 2094.44 14-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 9.63 0.00 01-JAN-00:10 2937.39 02-AUG-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 9.63 0.00 01-JAN-00:10 2937.39 02-AUG-15:10
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 94.23 0.00 01-JAN-08:10 14738.87 30-AUG-15:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 12.17 0.00 01-JAN-08:10 9613.75 14-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 12.17 0.00 01-JAN-08:10 9613.75 14-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 82.06 0.00 01-JAN-00:10 14738.87 30-AUG-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 82.06 0.00 01-JAN-00:10 14738.87 30-AUG-15:10
EnergyTransfer:Zone:BANQUET_FLR_6 434.29 7981.97 06-FEB-15:00 23342.76 04-AUG-21:20
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 434.29 7981.97 06-FEB-15:00 23342.76 04-AUG-21:20
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 434.29 7981.97 06-FEB-15:00 23342.76 04-AUG-21:20
EnergyTransfer:Zone:DINING_FLR_6 473.36 8983.58 06-FEB-15:00 24573.85 04-AUG-21:20
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DINING_FLR_6 473.36 8983.58 06-FEB-15:00 24573.85 04-AUG-21:20
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 473.36 8983.58 06-FEB-15:00 24573.85 04-AUG-21:20
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 603.66 7970.50 06-FEB-04:00 30117.79 09-JUL-10:40
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 603.66 7970.50 06-FEB-04:00 30117.79 09-JUL-10:40
EnergyTransfer:Zone:CORRIDOR_FLR_6 85.05 0.04 12-JAN-01:50 6425.54 16-AUG-12:50
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.96 0.00 01-JAN-09:20 2507.53 02-JAN-07:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.96 0.00 01-JAN-09:20 2507.53 02-JAN-07:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 84.09 0.00 01-JAN-00:10 6425.54 16-AUG-12:50
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 84.09 0.00 01-JAN-00:10 6425.54 16-AUG-12:50
PlantLoopHeatingDemand:Facility 2979.83 8896.18 10-AUG-00:30 307254.19 05-FEB-23:00
PlantLoopHeatingDemand:Plant 2351.87 8896.18 10-AUG-00:30 219611.31 03-JUL-20:40
WaterSystems:PlantLoopHeatingDemand 2351.87 8896.18 10-AUG-00:30 219611.31 03-JUL-20:40
General:WaterSystems:PlantLoopHeatingDemand 759.16 8892.19 10-AUG-00:20 57212.08 25-JAN-07:10
HeatingCoils:EnergyTransfer 627.96 0.00 02-MAR-21:00 185338.80 14-JAN-16:10
PlantLoopHeatingDemand:HVAC 627.96 0.00 02-MAR-21:00 185338.80 14-JAN-16:10
HeatingCoils:PlantLoopHeatingDemand 627.96 0.00 02-MAR-21:00 185338.80 14-JAN-16:10
HeatRecoveryForHeating:EnergyTransfer 2914.60 0.00 03-JAN-08:50 468219.91 06-FEB-03:00
HeatRecoveryForCooling:EnergyTransfer 566.41 0.00 01-JAN-00:10 303349.67 20-JUL-21:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 1592.71 0.00 01-JAN-00:10 183948.72 03-JUL-20:40
WaterSystems:EnergyTransfer 759.16 8892.19 10-AUG-00:20 57212.08 25-JAN-07:10
WaterUse:WaterSystems:EnergyTransfer 759.16 8892.19 10-AUG-00:20 57212.08 25-JAN-07:10
Boilers:EnergyTransfer 621.81 0.00 02-MAR-21:00 187979.14 14-JAN-16:10
Chillers:EnergyTransfer 3827.40 0.00 01-JAN-00:10 718114.86 11-AUG-22:00
HeatRejection:EnergyTransfer 4978.02 0.00 01-JAN-00:10 894753.58 11-AUG-22:00
General:HeatRejection:EnergyTransfer 4978.02 0.00 01-JAN-00:10 894753.58 11-AUG-22:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.000 -337.558 0.000 0.000 143.827 113.371 143.105 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -62.745
RETAIL_1_FLR_1 0.000 0.000 0.698 -40.650 0.000 0.000 15.519 6.265 10.186 24.596 0.000 0.046 0.000 0.000 -9.474 0.000 -0.980 -6.206
RETAIL_2_FLR_1 0.000 0.000 0.000 -34.344 0.000 0.000 17.054 7.255 11.795 0.000 0.000 0.017 0.000 0.000 0.000 0.000 -0.402 -1.375
MECH_FLR_1 0.000 0.000 0.190 -23.315 0.000 0.000 3.726 8.366 12.471 0.000 0.000 0.040 0.000 0.000 0.000 0.000 -0.907 -0.571
STORAGE_FLR_1 0.000 0.000 0.370 -11.334 0.000 0.000 2.886 1.866 3.598 0.000 0.000 0.024 3.109 0.000 0.000 0.000 -0.518 -0.000
LAUNDRY_FLR_1 0.000 0.000 0.000 -598.142 0.000 0.000 11.404 4.900 658.131 0.000 0.000 0.070 0.000 0.000 0.000 0.000 -1.337 -75.025
CAFE_FLR_1 0.000 0.000 0.000 -237.381 0.000 0.000 192.916 12.911 14.341 68.391 0.000 0.096 0.000 0.000 -28.377 0.000 -2.317 -20.579
LOBBY_FLR_1 0.000 0.000 0.000 -791.945 0.000 0.000 560.119 122.882 148.998 90.416 0.000 0.273 0.000 0.000 -38.595 0.000 -6.800 -85.349
ROOM_1_FLR_3 18.071 -43.230 0.000 -11.683 0.000 0.000 9.713 6.171 12.292 46.732 0.000 0.312 0.000 0.000 -21.289 0.000 -2.874 -14.215
ROOM_2_FLR_3 22.740 -29.998 0.000 -12.238 0.000 0.000 9.583 6.170 12.291 33.104 0.000 0.164 0.000 0.000 -22.242 0.000 -3.354 -16.220
ROOM_3_MULT19_FLR_3 0.000 -284.107 0.000 -15.108 0.000 0.000 0.000 73.685 228.754 273.458 0.000 0.144 0.001 0.000 -153.441 0.000 -15.979 -107.405
ROOM_4_MULT19_FLR_3 65.289 -219.929 0.000 -163.627 0.000 0.000 182.710 73.705 228.817 90.047 0.000 1.254 0.000 0.000 -125.456 0.000 -29.573 -103.236
ROOM_5_FLR_3 17.809 -42.748 0.000 -11.686 0.000 0.000 9.708 6.171 12.292 46.315 0.000 0.312 0.000 0.000 -21.024 0.000 -2.880 -14.269
ROOM_6_FLR_3 22.234 -29.682 0.000 -12.196 0.000 0.000 9.601 6.170 12.291 32.412 0.000 0.165 0.000 0.000 -21.647 0.000 -3.355 -15.992
CORRIDOR_FLR_3 0.000 0.000 1.213 -153.473 0.000 0.000 118.121 56.739 0.000 42.959 0.000 0.119 0.000 0.000 -27.762 0.000 -2.790 -35.125
ROOM_1_FLR_6 6.734 -10.865 0.000 -2.918 0.000 0.000 2.432 1.543 3.073 11.615 0.000 0.084 0.000 0.000 -5.274 0.000 -0.750 -5.675
ROOM_2_FLR_6 8.214 -7.728 0.000 -3.062 0.000 0.000 2.397 1.543 3.073 8.226 0.000 0.042 0.000 0.000 -5.523 0.000 -0.862 -6.319
ROOM_3_MULT9_FLR_6 17.151 -68.189 0.000 -18.852 0.000 0.000 21.790 8.728 27.097 64.044 0.000 0.585 0.000 0.000 -24.848 0.000 -4.331 -23.175
BANQUET_FLR_6 0.000 0.000 0.000 -434.289 0.000 0.000 318.545 28.313 175.857 9.205 0.000 0.051 0.000 0.000 -17.112 0.000 -1.621 -78.949
DINING_FLR_6 0.000 0.000 0.000 -473.362 0.000 0.000 316.820 28.313 175.857 8.987 0.000 0.050 0.000 0.000 -17.672 0.000 -1.639 -37.354
KITCHEN_FLR_6 0.000 0.000 0.000 -603.649 0.000 0.000 28.651 13.339 540.650 22.151 0.000 0.044 11.448 0.000 -11.166 0.000 -1.467 -0.001
CORRIDOR_FLR_6 0.000 0.000 0.957 -84.091 0.000 0.000 31.364 15.012 0.000 20.905 0.000 0.047 29.517 0.000 -12.478 0.000 -1.234 -0.001
Total Facility 178.242 -736.475 3.429 -4074.905 0.000 0.000 2008.887 603.416 2434.967 893.560 0.000 3.940 44.075 0.000 -563.380 0.000 -85.968 -709.787


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 27-OCT-21:00 0.00 0.00 0.00 -17578.31 0.00 0.00 5924.40 8241.11 9125.55 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -5712.76
RETAIL_1_FLR_1 04-OCT-12:10 0.00 0.00 0.00 -3981.51 0.00 0.00 150.60 142.31 252.59 5778.29 0.00 1.46 0.00 0.00 -0.00 0.00 0.00 -2343.74
RETAIL_2_FLR_1 18-AUG-21:00 0.00 0.00 0.00 -2044.16 0.00 0.00 697.61 527.34 752.15 0.00 0.00 1.13 65.94 0.00 -0.00 0.00 0.00 0.00
MECH_FLR_1 18-AUG-20:00 0.00 0.00 0.00 -1705.12 0.00 0.00 129.08 684.18 839.45 0.00 0.00 5.58 46.84 0.00 -0.00 0.00 0.00 0.00
STORAGE_FLR_1 24-AUG-19:30 0.00 0.00 0.00 -752.52 0.00 0.00 100.36 152.61 242.16 0.00 0.00 6.79 250.60 0.00 -0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 24-AUG-19:30 0.00 0.00 0.00 -40870.43 0.00 0.00 389.07 400.68 44299.38 0.00 0.00 14.26 0.00 0.00 -0.00 0.00 0.00 -4232.96
CAFE_FLR_1 30-SEP-12:40 0.00 0.00 0.00 -14031.96 0.00 0.00 2968.70 96.16 355.63 15572.18 0.00 0.00 0.00 0.00 -0.00 0.00 -23.91 -4936.80
LOBBY_FLR_1 04-AUG-21:10 0.00 0.00 0.00 -42010.90 0.00 0.00 26439.90 7096.92 7389.94 851.45 0.00 136.50 96.19 0.00 -0.00 0.00 0.00 0.00
ROOM_1_FLR_3 12-JUL-18:02 0.00 -11688.88 0.00 -757.78 0.00 0.00 335.49 422.72 516.26 6374.16 0.00 18.13 4779.90 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_3 29-MAY-18:31 0.00 -12182.17 0.00 -902.06 0.00 0.00 245.88 474.90 516.20 2388.19 0.00 0.59 9458.46 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 04-OCT-12:10 0.00 -52022.35 0.00 0.00 0.00 0.00 0.00 1587.99 5097.90 68168.87 0.00 0.00 0.00 0.00 -0.00 0.00 -79.95 -22752.45
ROOM_4_MULT19_FLR_3 30-MAY-08:21 0.00 -64598.62 0.00 -10995.87 0.00 0.00 1615.94 2496.10 8433.45 12985.71 0.00 73.42 49989.89 0.00 -0.00 0.00 0.00 0.00
ROOM_5_FLR_3 23-JUN-08:61 0.00 -10872.81 0.00 -768.86 0.00 0.00 87.14 208.98 453.05 7594.57 0.00 25.04 3272.89 0.00 -0.00 0.00 0.00 0.00
ROOM_6_FLR_3 30-MAY-08:62 0.00 -12243.15 0.00 -1075.53 0.00 0.00 58.79 208.96 452.99 8708.89 0.00 0.00 3901.24 0.00 -0.00 0.00 -12.20 0.00
CORRIDOR_FLR_3 24-AUG-19:30 0.00 0.00 0.00 -9538.47 0.00 0.00 4083.46 4640.01 0.00 262.78 0.00 34.80 517.42 0.00 -0.00 0.00 0.00 0.00
ROOM_1_FLR_6 15-AUG-18:02 0.00 -3107.54 0.00 -189.15 0.00 0.00 83.87 105.68 129.07 1111.50 0.00 5.99 1860.57 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_6 29-MAY-18:31 0.00 -3264.38 0.00 -230.91 0.00 0.00 59.88 118.73 129.05 586.33 0.00 0.00 2601.74 0.00 -0.00 0.00 -0.44 0.00
ROOM_3_MULT9_FLR_6 16-AUG-15:02 0.00 -14682.90 0.00 -1226.28 0.00 0.00 529.35 188.10 603.86 5532.74 0.00 69.18 8985.95 0.00 -0.00 0.00 0.00 0.00
BANQUET_FLR_6 04-AUG-21:20 0.00 0.00 0.00 -23347.70 0.00 0.00 15638.65 1842.08 6747.90 349.35 0.00 27.65 0.00 0.00 -0.00 0.00 0.00 -1257.93
DINING_FLR_6 04-AUG-21:20 0.00 0.00 0.00 -24579.16 0.00 0.00 15631.28 1842.08 6747.90 337.09 0.00 27.64 0.00 0.00 -0.00 0.00 0.00 -6.84
KITCHEN_FLR_6 01-JUN-18:02 0.00 0.00 0.00 -31663.55 0.00 0.00 1011.24 969.63 21452.40 637.21 0.00 11.64 7581.43 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 11-JUL-15:07 0.00 0.00 0.00 -6497.30 0.00 0.00 771.14 341.02 0.00 1708.96 0.00 15.11 3661.07 0.00 -0.00 0.00 0.00 0.00
Total Facility 22-AUG-18:02 0.00 -153296.52 0.00 -200099.37 0.00 0.00 73889.56 42173.89 121562.63 21842.06 0.00 598.27 93329.47 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 02-JAN-07:10 0.00 0.00 1157.23 0.00 0.00 0.00 357.95 284.62 433.01 0.00 0.00 0.00 0.00 0.00 -1301.48 0.00 -110.93 -820.39
RETAIL_2_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MECH_FLR_1 02-JAN-15:00 0.00 0.00 463.93 0.00 0.00 0.00 43.84 190.05 309.27 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -82.16 -924.94
STORAGE_FLR_1 06-FEB-16:00 0.00 0.00 415.76 0.00 0.00 0.00 50.59 42.39 89.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -48.09 -549.87
LAUNDRY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 08-JAN-15:40 0.00 0.00 10.30 0.00 0.00 0.00 2352.28 226.49 304.82 0.00 0.00 0.00 203.97 0.00 -2936.98 0.00 -160.88 0.00
LOBBY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 02-JAN-09:01 9522.95 303.10 0.00 -303.10 0.00 0.00 108.88 208.98 453.05 0.00 0.00 0.00 0.00 0.00 -84.95 0.00 -234.90 -9974.01
ROOM_2_FLR_3 06-FEB-09:01 9590.14 297.07 0.00 -297.07 0.00 0.00 108.89 208.96 452.99 0.00 0.00 0.00 0.00 0.00 -2022.93 0.00 -242.02 -8096.03
ROOM_3_MULT19_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 06-FEB-16:01 53938.18 3812.24 0.00 -3812.24 0.00 0.00 5585.66 1588.43 5099.29 0.00 0.00 0.00 0.00 0.00 -11812.32 0.00 -1052.81 -53346.42
ROOM_5_FLR_3 14-JAN-16:02 9326.99 301.31 0.00 -301.31 0.00 0.00 163.33 156.74 305.54 0.00 0.00 0.00 0.00 0.00 -2316.82 0.00 -197.40 -7438.38
ROOM_6_FLR_3 06-FEB-16:01 9347.72 298.01 0.00 -298.01 0.00 0.00 293.98 132.97 273.90 0.00 0.00 0.00 0.00 0.00 -2127.55 0.00 -200.18 -7720.86
CORRIDOR_FLR_3 14-JAN-16:15 0.00 0.00 3891.37 0.00 0.00 0.00 2078.69 1288.89 0.00 0.00 0.00 0.00 0.00 0.00 -3198.65 0.00 -252.73 -3807.58
ROOM_1_FLR_6 14-JAN-16:02 2846.48 76.29 0.00 -76.29 0.00 0.00 40.83 39.19 76.39 0.00 0.00 0.00 0.00 0.00 -567.63 0.00 -49.57 -2385.68
ROOM_2_FLR_6 06-FEB-09:01 2859.76 74.94 0.00 -74.94 0.00 0.00 27.22 52.24 113.25 0.00 0.00 0.00 0.00 0.00 -508.71 0.00 -60.70 -2483.06
ROOM_3_MULT9_FLR_6 14-JAN-16:02 13442.27 484.45 0.00 -484.45 0.00 0.00 367.49 221.70 673.54 0.00 0.00 0.00 0.00 0.00 -2666.58 0.00 -227.86 -11810.55
BANQUET_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 02-JAN-07:15 0.00 0.00 2515.90 0.00 0.00 0.00 733.32 682.05 0.00 0.00 0.00 0.00 0.00 0.00 -1694.55 0.00 -137.74 -2098.98
Total Facility 14-JAN-16:02 37213.42 78581.13 7120.58 -78581.13 0.00 0.00 36363.79 14412.26 78232.63 0.00 0.00 0.00 0.00 0.00 -54655.55 0.00 -5023.97 -113663.17



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 20.8436 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 20.7354 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 11.6516 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.6516 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.000000 12.5400 0.001181 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.000000 142.3000 0.003581 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.001045 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.0802 2.0802 1.1628 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3521 0.3521 0.1968 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2173 0.2173 0.1215 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1839 0.1839 0.1028 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0989 0.0989 0.0553 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.2559 3.2559 1.8201 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4993 1.4993 0.8381 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.6789 4.6789 2.6155 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2372 1.2372 0.6916 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1315 2.1315 1.1915 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2373 2.2373 1.2507 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1746 2.1746 1.2156 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6964 0.6964 0.3893 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 20.8436 20.7354 20.8436 11.6516 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1628 1.1628 1.1628 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1968 0.1968 0.1968 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1215 0.1215 0.1215 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1028 0.1028 0.1028 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0553 0.0553 0.0553 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.8201 1.8201 1.8201 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8381 0.8381 0.8381 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6155 2.6155 2.6155 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6916 0.6916 0.6916 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1915 1.1915 1.1915 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2507 1.2507 1.2507 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2156 1.2156 1.2156 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3893 0.3893 0.3893 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 11.6516 11.6516 11.6516 11.6516 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.33
Number of hours cooling loads not met 114.50
Number of hours not met 114.83


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 884.76 232046.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 1150.62 196240.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 603.42 50471.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 174.22 11096.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 952.41 59188.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 8.75 277.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 4.94 156.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 22.46 1283.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 616.11 37691.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 2.91 188.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 550.32 36355.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 120.83 7534.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 188.60 9938.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.75 4738.76 1132.48 136843.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Other 0.00 38393.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.09 2093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 15.72 1320.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 21.07 719.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1772.02 5691.35
Natural Gas 1788.84 3806.08
Additional 0.00 0.00
Total 3560.86 9497.43


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 53.19
Space Heating 0.00
Space Cooling 101.42
Fans (All) 48.51
Service Water Heating 43.18
Receptacle Equipment 152.32
Miscellaneous (All) 501.65
Subtotal 501.65


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 77.98
Service Water Heating 99.82
Miscellaneous (All) 335.48
Subtotal 335.48


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 6.35
Space Heating 9.32
Space Cooling 12.12
Fans (All) 5.79
Service Water Heating 17.08
Receptacle Equipment 37.03
Miscellaneous 12.31


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2398. 8760.
LTG_SCH_LOBBY 3061. 8760.
LTG_SCH_STORAGE 1339. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 3061. 8760.
LTG_SCH_GUESTROOM 2482. 8760.
LTG_SCH_CORRIDOR 2295. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_2 1591. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3737. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 5740. 6205.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 0. 0.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 15.56 365 15.56 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 26.67 365 26.67 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8732.33 27.67 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 7568.83 1191.17 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8734.00 26.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8712.00 48.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 7568.83 0.00 0.00 0.00 0.00
Max 8760.00 1191.17 0.00 0.00 0.00
Average 8701.23 58.77 0.00 0.00 0.00
Sum 191427.17 1292.83 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4150.50 3.50 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4143.50 10.50 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 10.50 0.00 0.00 0.00
Average 288886.41 0.64 0.00 0.00 0.00
Sum 6355501.00 14.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8638.00 122.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 7861.67 898.33 0.00 0.00 0.00
LOBBY_FLR_1 7831.33 928.67 0.00 0.00 0.00
ROOM_1_FLR_3 8758.00 2.00 0.00 0.00 0.00
ROOM_2_FLR_3 8503.33 256.67 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 6997.33 1762.67 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8602.50 157.50 0.00 0.00 0.00
ROOM_5_FLR_3 8758.17 1.83 0.00 0.00 0.00
ROOM_6_FLR_3 8506.00 254.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8741.83 18.17 0.00 0.00 0.00
ROOM_1_FLR_6 8753.33 6.67 0.00 0.00 0.00
ROOM_2_FLR_6 8439.67 320.33 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8747.83 12.17 0.00 0.00 0.00
BANQUET_FLR_6 7726.83 1033.17 0.00 0.00 0.00
DINING_FLR_6 7819.83 940.17 0.00 0.00 0.00
KITCHEN_FLR_6 8569.17 190.83 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 6997.33 0.00 0.00 0.00 0.00
Max 8760.00 1762.67 0.00 0.00 0.00
Average 8446.13 313.87 0.00 0.00 0.00
Sum 185814.83 6905.17 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 57846.00 1310.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 600361.17 110055.83 0.00 0.00 0.00
LOBBY_FLR_1 1787271.67 328157.33 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4041.17 112.83 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4081.33 72.67 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4069.67 84.33 0.00 0.00 0.00
CORRIDOR_FLR_3 100038.33 319.67 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4006.00 148.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1033677.33 212037.67 0.00 0.00 0.00
DINING_FLR_6 1050821.83 194893.17 0.00 0.00 0.00
KITCHEN_FLR_6 106611.17 1657.83 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 1787271.67 328157.33 0.00 0.00 0.00
Average 250302.98 38584.06 0.00 0.00 0.00
Sum 5506665.67 848849.33 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:50

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 8760.00 0.00 0.00
LOBBY_FLR_1 0.00 8760.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 8760.00 0.00 0.00
DINING_FLR_6 0.00 8760.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 1592.73 0.00 0.00
Sum 0.00 35040.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 710417.00 0.00 0.00
LOBBY_FLR_1 0.00 2115429.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 1245715.00 0.00 0.00
DINING_FLR_6 0.00 1245715.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 2115429.00 0.00 0.00
Average 0.00 241694.36 0.00 0.00
Sum 0.00 5317276.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

For: Environment

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A

For: Environment

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK

For: Environment

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.277965E+11 12233.89 20-JAN-21:00 3.30 2.32 0.745129E+10 4635.67 31-JAN-22:10 -2.8 -5.6
February 0.235453E+11 12016.15 01-FEB-21:00 5.60 3.16 0.644487E+10 4583.99 01-FEB-22:10 4.90 2.79
March 0.249571E+11 11335.68 03-MAR-21:00 11.10 6.67 0.688631E+10 4310.48 01-MAR-22:10 11.10 6.67
April 0.237464E+11 11850.43 08-APR-10:33 23.90 16.13 0.649197E+10 4178.92 13-APR-21:10 5.00 4.72
May 0.245312E+11 11967.36 29-MAY-10:33 27.43 17.92 0.660559E+10 4103.75 03-MAY-22:10 27.43 17.92
June 0.259638E+11 13800.67 22-JUN-18:03 28.72 17.28 0.671317E+10 4319.80 30-JUN-22:10 20.00 18.86
July 0.289951E+11 13920.50 11-JUL-17:09 28.12 17.29 0.722628E+10 4511.26 28-JUL-22:10 24.32 20.84
August 0.309583E+11 15495.76 24-AUG-19:30 28.30 16.24 0.761932E+10 4732.93 25-AUG-22:10 20.92 14.50
September 0.313842E+11 15276.08 22-SEP-21:00 18.90 17.11 0.771523E+10 4837.09 28-SEP-21:10 16.42 11.03
October 0.337129E+11 17577.41 27-OCT-21:00 7.20 3.64 0.812842E+10 4837.08 04-OCT-22:10 7.20 3.64
November 0.316349E+11 17229.19 03-NOV-21:00 12.80 10.14 0.784169E+10 4837.04 03-NOV-23:19 12.97 10.62
December 0.303309E+11 15513.35 01-DEC-22:00 1.10 -2.2 0.791012E+10 4837.06 19-DEC-23:10 4.60 3.31
                     
Annual Sum or Average 0.337557E+12         0.870343E+11        
Minimum of Months 0.235453E+11 11335.68   1.10 -2.2 0.644487E+10 4103.75   -2.8 -5.6
Maximum of Months 0.337129E+11 17577.41   28.72 17.92 0.812842E+10 4837.09   27.43 20.84



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.110462E+10 2422.95 17-JAN-13:10 10.18 5.51 0.623890E+09 364.18 19-JAN-22:19 5.60 1.07
February 0.138520E+10 2170.79 02-FEB-13:40 5.97 -0.5 0.566917E+09 364.14 06-FEB-05:10 -13.2 -14.5
March 0.238265E+10 2978.21 03-MAR-13:20 14.60 8.23 0.636395E+09 406.50 03-MAR-22:30 10.30 6.29
April 0.292599E+10 3139.42 08-APR-12:30 23.60 16.18 0.624034E+09 451.92 07-APR-21:30 23.60 16.18
May 0.391484E+10 2482.87 31-MAY-10:35 25.60 19.79 0.659228E+09 457.17 31-MAY-21:40 20.13 17.44
June 0.462840E+10 2707.41 19-JUN-13:20 34.80 23.85 0.694530E+09 486.43 19-JUN-21:30 28.35 20.38
July 0.523377E+10 2941.11 08-JUL-12:10 32.02 26.06 0.749566E+09 486.54 10-JUL-21:30 26.95 19.92
August 0.570759E+10 3616.68 22-AUG-12:40 30.40 18.62 0.772537E+09 491.82 04-AUG-21:19 30.40 18.62
September 0.483710E+10 3793.76 07-SEP-12:40 26.50 22.82 0.694913E+09 491.80 01-SEP-21:30 26.50 22.82
October 0.470524E+10 3981.32 04-OCT-12:10 24.50 18.64 0.694467E+09 464.76 04-OCT-21:30 16.95 15.74
November 0.228943E+10 3087.30 02-NOV-12:40 15.40 8.14 0.611797E+09 414.78 03-NOV-21:30 12.80 10.23
December 0.153535E+10 2948.09 17-DEC-12:50 12.20 4.87 0.626635E+09 364.32 18-DEC-22:19 2.20 0.87
                     
Annual Sum or Average 0.406502E+11         0.795491E+10        
Minimum of Months 0.110462E+10 2170.79   5.97 -0.5 0.566917E+09 364.14   -13.2 -14.5
Maximum of Months 0.570759E+10 3981.32   34.80 26.06 0.772537E+09 491.82   30.40 22.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.220383E+10 1170.78 19-JAN-21:00 3.90 0.79 0.763517E+09 514.11 19-JAN-23:10 5.60 1.07
February 0.205950E+10 1162.53 02-FEB-21:00 -1.7 -5.7 0.697218E+09 510.79 02-FEB-22:40 -2.6 -6.2
March 0.258094E+10 1286.70 03-MAR-21:00 11.10 6.67 0.813125E+09 546.01 03-MAR-23:10 9.82 6.12
April 0.268469E+10 1446.35 07-APR-21:00 19.40 13.83 0.813581E+09 569.55 07-APR-22:10 18.22 13.39
May 0.302208E+10 1726.30 31-MAY-21:00 20.60 17.62 0.878432E+09 569.55 31-MAY-22:10 19.78 17.36
June 0.326289E+10 1943.07 19-JUN-21:00 28.90 20.74 0.900423E+09 569.55 20-JUN-22:10 20.60 17.54
July 0.356685E+10 1983.38 07-JUL-21:00 25.60 23.22 0.942809E+09 569.55 11-JUL-22:10 22.62 17.84
August 0.370175E+10 2044.12 18-AUG-21:00 25.00 17.57 0.955061E+09 569.65 18-AUG-02:20 25.00 17.57
September 0.323146E+10 1959.23 01-SEP-21:00 26.70 18.23 0.893706E+09 569.55 06-SEP-22:10 22.20 20.63
October 0.312513E+10 1713.39 05-OCT-21:00 18.90 17.80 0.902115E+09 569.55 04-OCT-22:10 18.90 17.80
November 0.252055E+10 1326.94 03-NOV-20:00 12.80 10.92 0.787278E+09 559.07 03-NOV-22:10 12.80 10.38
December 0.238415E+10 1188.30 18-DEC-21:00 2.80 1.39 0.782008E+09 519.46 18-DEC-23:10 2.30 0.67
                     
Annual Sum or Average 0.343438E+11         0.101293E+11        
Minimum of Months 0.205950E+10 1162.53   -1.7 -5.7 0.697218E+09 510.79   -2.6 -6.2
Maximum of Months 0.370175E+10 2044.12   28.90 23.22 0.955061E+09 569.65   25.00 20.63



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.706143E+09 829.36 19-JAN-21:00 3.90 0.79 0.152071E+09 93.89 19-JAN-22:10 5.60 1.07
February 0.614952E+09 811.32 24-FEB-21:00 1.10 -2.8 0.137434E+09 92.80 24-FEB-22:10 0.32 -3.7
March 0.145774E+10 923.00 28-MAR-10:33 12.23 7.80 0.154972E+09 99.90 28-MAR-21:10 8.22 5.85
April 0.189454E+10 1123.37 08-APR-10:33 23.90 16.13 0.156237E+09 108.83 10-APR-21:19 12.57 5.94
May 0.237308E+10 1251.00 31-MAY-10:35 25.60 19.79 0.174474E+09 117.93 31-MAY-21:19 20.37 17.53
June 0.265920E+10 1404.95 20-JUN-21:00 21.10 16.91 0.185717E+09 120.45 20-JUN-21:19 20.93 17.07
July 0.294942E+10 1652.24 10-JUL-21:00 27.20 20.22 0.198051E+09 120.45 11-JUL-21:19 22.80 17.52
August 0.298887E+10 1705.12 18-AUG-20:00 26.10 18.80 0.199695E+09 120.46 30-AUG-21:19 22.43 18.00
September 0.258549E+10 1364.45 01-SEP-21:00 26.70 18.23 0.182655E+09 120.45 01-SEP-21:10 26.60 18.09
October 0.238049E+10 1166.11 05-OCT-10:33 21.13 17.47 0.176146E+09 114.60 05-OCT-21:19 18.90 17.68
November 0.161337E+10 1003.83 04-NOV-10:33 16.83 11.51 0.152771E+09 103.75 03-NOV-21:19 16.83 11.51
December 0.109178E+10 834.78 19-DEC-21:00 8.30 3.94 0.152374E+09 94.23 19-DEC-22:10 5.40 2.50
                     
Annual Sum or Average 0.233151E+11         0.202260E+10        
Minimum of Months 0.614952E+09 811.32   1.10 -2.8 0.137434E+09 92.80   0.32 -3.7
Maximum of Months 0.298887E+10 1705.12   27.20 20.22 0.199695E+09 120.46   26.60 18.09



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.186312E+09 415.76 19-JAN-21:00 3.90 0.79 0.116700E+09 69.42 19-JAN-23:10 5.60 1.07
February 0.161827E+09 355.99 24-FEB-22:00 0.60 -3.5 0.105501E+09 68.57 22-FEB-03:00 0.60 -3.5
March 0.612559E+09 489.59 28-MAR-10:33 12.23 7.80 0.118011E+09 73.96 03-MAR-23:10 12.23 7.80
April 0.934811E+09 604.82 08-APR-10:33 23.90 16.13 0.118258E+09 80.70 10-APR-21:40 11.83 5.31
May 0.124691E+10 670.53 31-MAY-10:35 25.60 19.79 0.131687E+09 87.81 31-MAY-22:10 19.78 17.36
June 0.140159E+10 737.74 22-JUN-18:03 28.72 17.28 0.140520E+09 91.58 19-JUN-22:10 28.72 17.28
July 0.154651E+10 748.94 11-JUL-17:09 28.12 17.29 0.150444E+09 92.66 10-JUL-21:19 28.12 17.29
August 0.155967E+10 752.57 24-AUG-19:30 28.30 16.24 0.151782E+09 92.66 18-AUG-21:00 28.30 16.24
September 0.136130E+10 723.17 01-SEP-17:01 27.80 17.38 0.138050E+09 91.52 01-SEP-21:10 26.60 18.09
October 0.124980E+10 623.20 05-OCT-10:33 21.13 17.47 0.132914E+09 85.41 05-OCT-22:10 18.98 17.65
November 0.730731E+09 535.33 04-NOV-10:33 16.83 11.51 0.115815E+09 77.14 03-NOV-22:10 16.83 11.51
December 0.341884E+09 423.55 19-DEC-21:00 8.30 3.94 0.116720E+09 69.71 19-DEC-23:10 4.60 3.31
                     
Annual Sum or Average 0.113339E+11         0.153640E+10        
Minimum of Months 0.161827E+09 355.99   0.60 -3.5 0.105501E+09 68.57   0.60 -3.5
Maximum of Months 0.155967E+10 752.57   28.72 19.79 0.151782E+09 92.66   28.72 18.09



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.477901E+11 36560.90 19-JAN-21:00 3.90 0.79 0.569998E+09 381.61 20-JAN-22:10 3.72 3.02
February 0.432189E+11 36466.59 17-FEB-21:00 1.10 -0.8 0.515657E+09 381.60 03-FEB-22:10 1.10 -0.8
March 0.493260E+11 37263.65 03-MAR-21:00 11.10 6.67 0.576216E+09 381.63 28-MAR-21:10 8.22 5.85
April 0.486873E+11 38041.22 07-APR-20:00 21.70 14.73 0.558554E+09 381.66 11-APR-21:19 9.03 1.57
May 0.517875E+11 38433.30 30-MAY-20:00 20.00 15.55 0.580203E+09 381.69 12-MAY-21:10 20.00 15.55
June 0.513723E+11 39040.60 01-JUN-19:13 26.27 15.74 0.564431E+09 382.20 22-JUN-21:10 25.92 16.12
July 0.535717E+11 38710.21 10-JUL-20:00 28.30 20.24 0.582541E+09 381.69 21-JUL-21:10 25.60 23.68
August 0.539903E+11 40843.41 24-AUG-19:30 28.30 16.24 0.584749E+09 383.01 24-AUG-21:10 25.40 15.20
September 0.508780E+11 38492.16 14-SEP-19:30 26.65 17.03 0.563239E+09 392.20 01-SEP-21:10 26.65 17.03
October 0.514210E+11 38068.91 04-OCT-20:00 18.90 16.06 0.580191E+09 381.71 26-OCT-21:10 8.22 3.60
November 0.478286E+11 37351.45 03-NOV-20:00 12.80 10.92 0.557109E+09 381.72 03-NOV-21:10 12.80 10.17
December 0.482666E+11 36590.45 20-DEC-21:00 5.00 1.74 0.572306E+09 381.62 22-DEC-22:10 2.20 1.31
                     
Annual Sum or Average 0.598138E+12         0.680519E+10        
Minimum of Months 0.432189E+11 36466.59   1.10 -0.8 0.515657E+09 381.60   1.10 -0.8
Maximum of Months 0.539903E+11 40843.41   28.30 20.24 0.584749E+09 392.20   26.65 23.68



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.148659E+11 9959.43 17-JAN-13:00 10.00 5.56 0.878541E+10 6029.86 19-JAN-22:40 5.60 1.07
February 0.146370E+11 9887.98 20-FEB-13:00 9.40 4.36 0.808134E+10 5967.28 22-FEB-22:40 2.20 -0.9
March 0.179713E+11 11547.53 03-MAR-13:10 14.50 8.14 0.939050E+10 6438.65 03-MAR-22:40 10.20 6.23
April 0.184326E+11 12122.22 08-APR-12:20 23.87 16.21 0.928134E+10 6462.61 07-APR-22:10 23.87 16.21
May 0.205951E+11 10697.89 29-MAY-10:33 27.43 17.92 0.994327E+10 6462.77 31-MAY-22:10 19.78 17.36
June 0.218700E+11 11587.08 19-JUN-21:10 28.72 20.62 0.101165E+11 6462.77 20-JUN-22:10 20.60 17.54
July 0.239928E+11 11505.01 10-JUL-21:10 27.12 20.12 0.106097E+11 6462.73 11-JUL-22:10 22.62 17.84
August 0.254663E+11 12387.70 13-AUG-12:00 30.60 18.83 0.108014E+11 6464.46 18-AUG-02:20 25.60 18.81
September 0.227998E+11 14032.87 30-SEP-12:40 20.40 12.36 0.101464E+11 6462.73 06-SEP-22:10 20.40 12.36
October 0.230796E+11 13764.78 04-OCT-12:00 24.40 18.65 0.103777E+11 6462.62 04-OCT-22:10 16.88 15.73
November 0.174443E+11 12329.02 04-NOV-12:30 17.80 12.61 0.902257E+10 6460.51 02-NOV-22:10 17.80 12.61
December 0.162237E+11 12263.86 17-DEC-11:00 10.60 4.31 0.899621E+10 6044.20 18-DEC-22:40 2.20 0.72
                     
Annual Sum or Average 0.237378E+12         0.115552E+12        
Minimum of Months 0.146370E+11 9887.98   9.40 4.31 0.808134E+10 5967.28   2.20 -0.9
Maximum of Months 0.254663E+11 14032.87   30.60 20.62 0.108014E+11 6464.46   25.60 18.81



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.544480E+11 26878.06 19-JAN-21:00 3.90 0.79 0.275664E+11 18652.22 19-JAN-23:10 5.60 1.07
February 0.505757E+11 26598.31 02-FEB-21:00 -1.7 -5.7 0.251920E+11 18463.10 22-FEB-23:10 2.20 -0.8
March 0.604229E+11 29300.49 03-MAR-22:20 10.40 6.34 0.291392E+11 19183.55 15-MAR-21:00 8.90 2.77
April 0.617723E+11 34406.61 07-APR-21:10 19.22 13.77 0.288379E+11 19186.01 07-APR-22:10 18.22 13.39
May 0.685724E+11 36892.29 31-MAY-21:10 20.48 17.58 0.308259E+11 19186.23 31-MAY-22:10 19.78 17.36
June 0.729755E+11 40426.69 19-JUN-21:10 28.72 20.62 0.308398E+11 19186.24 20-JUN-22:10 20.60 17.54
July 0.794769E+11 40992.97 10-JUL-21:10 27.12 20.12 0.319854E+11 19186.18 11-JUL-22:10 22.62 17.84
August 0.819543E+11 42005.26 04-AUG-21:10 31.55 23.93 0.322987E+11 19189.89 18-AUG-02:20 25.60 18.81
September 0.732343E+11 41161.47 01-SEP-21:10 26.60 18.09 0.308103E+11 19186.18 06-SEP-22:10 22.20 20.63
October 0.718033E+11 38211.22 05-OCT-21:10 18.90 17.74 0.315324E+11 19186.03 04-OCT-22:10 18.90 17.74
November 0.593641E+11 31803.53 03-NOV-21:10 12.80 10.17 0.283206E+11 19183.53 01-NOV-21:40 12.80 10.17
December 0.573386E+11 27960.08 17-DEC-11:33 11.67 4.45 0.282586E+11 18767.38 18-DEC-23:10 2.30 0.67
                     
Annual Sum or Average 0.791938E+12         0.355607E+12        
Minimum of Months 0.505757E+11 26598.31   -1.7 -5.7 0.251920E+11 18463.10   2.20 -0.8
Maximum of Months 0.819543E+11 42005.26   31.55 23.93 0.322987E+11 19189.89   25.60 20.63



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 26951406.26 2721.14 20-JAN-16:02 6.93 3.71 94027009.01 56.69 03-JAN-04:19 6.93 3.71
February 52747826.56 2766.85 14-FEB-16:01 0.50 -3.9 85538116.68 56.69 20-FEB-02:20 2.97 1.74
March 0.273876E+09 2824.30 11-MAR-16:01 11.20 5.40 96416068.00 56.69 27-MAR-21:19 13.87 10.67
April 0.638048E+09 2932.56 16-APR-15:01 21.60 13.95 94074441.04 56.69 08-APR-23:10 21.60 13.95
May 0.127658E+10 3029.21 20-MAY-18:02 22.02 11.72 98508555.54 56.70 31-MAY-22:00 19.20 17.40
June 0.208857E+10 3017.15 23-JUN-08:61 26.70 18.47 95886145.18 56.70 20-JUN-00:40 26.70 18.47
July 0.252544E+10 3111.62 12-JUL-18:02 25.50 21.15 99098673.74 56.70 20-JUL-23:10 26.10 24.12
August 0.274056E+10 3088.05 15-AUG-18:02 26.42 20.41 99201645.38 56.70 17-AUG-00:49 26.02 25.28
September 0.174606E+10 3007.03 07-SEP-15:02 26.60 22.96 95597885.84 56.70 07-SEP-22:49 22.88 20.86
October 0.118237E+10 2839.35 04-OCT-15:02 23.72 19.12 98362363.76 56.69 04-OCT-21:19 17.03 15.77
November 0.151550E+09 2671.85 04-NOV-15:01 17.30 12.80 92695503.42 56.69 03-NOV-00:40 17.30 12.80
December 34781476.97 2750.03 18-DEC-16:01 5.22 2.22 94536759.59 56.69 25-DEC-02:20 5.77 5.31
                     
Annual Sum or Average 0.127375E+11         0.114394E+10        
Minimum of Months 26951406.26 2671.85   0.50 -3.9 85538116.68 56.69   2.97 1.74
Maximum of Months 0.274056E+10 3111.62   26.70 22.96 99201645.38 56.70   26.70 25.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 9493222.05 2400.47 20-JAN-16:02 6.93 3.71 93129114.75 56.69 03-JAN-04:19 6.93 3.71
February 16012844.27 2469.74 22-FEB-16:02 4.22 -0.7 84366594.93 56.69 14-FEB-04:19 4.22 -0.7
March 0.128623E+09 2705.68 11-MAR-16:01 11.20 5.40 95587456.11 65.40 27-MAR-21:10 14.13 10.87
April 0.409363E+09 3094.93 09-APR-18:11 14.43 12.85 94997500.43 71.56 07-APR-21:40 14.43 12.85
May 0.950460E+09 3271.17 29-MAY-18:31 24.80 18.16 0.104182E+09 85.65 31-MAY-21:10 20.48 17.58
June 0.162817E+10 3100.51 23-JUN-08:61 26.70 18.47 0.106734E+09 82.29 20-JUN-21:30 26.70 18.47
July 0.224290E+10 3167.96 03-JUL-18:51 24.40 21.27 0.104385E+09 81.37 05-JUL-21:30 22.50 21.72
August 0.230075E+10 3012.36 15-AUG-18:02 26.42 20.41 0.103720E+09 82.12 10-AUG-21:10 26.42 20.41
September 0.115029E+10 2965.92 03-SEP-08:51 22.80 14.85 0.102895E+09 81.82 06-SEP-21:10 22.70 20.80
October 0.582485E+09 2872.99 24-OCT-15:02 21.60 19.09 0.101331E+09 74.17 04-OCT-21:40 21.60 19.09
November 50138081.10 2542.49 04-NOV-15:01 17.30 12.80 91736785.42 56.69 03-NOV-03:20 17.30 12.80
December 9643452.81 2407.57 17-DEC-16:02 9.82 4.16 93337192.85 56.69 25-DEC-02:20 5.77 5.31
                     
Annual Sum or Average 0.947833E+10         0.117640E+10        
Minimum of Months 9493222.05 2400.47   4.22 -0.7 84366594.93 56.69   4.22 -0.7
Maximum of Months 0.230075E+10 3271.17   26.70 21.27 0.106734E+09 85.65   26.70 21.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 9005968.85 145.74 31-JAN-15:20 -1.5 -6.0 0.00 0.00 01-JAN-00:10 -1.5 -6.0
February 42510333.78 351.62 20-FEB-13:30 9.15 4.45 0.00 0.00 01-FEB-00:10 9.15 4.45
March 0.102513E+09 413.56 15-MAR-13:15 13.50 6.64 0.00 0.00 01-MAR-00:10 13.50 6.64
April 0.192894E+09 548.62 07-APR-12:30 26.15 15.90 0.00 0.00 01-APR-00:10 26.15 15.90
May 0.323386E+09 420.31 30-MAY-12:50 29.90 17.93 0.00 0.00 01-MAY-00:10 29.90 17.93
June 0.493698E+09 438.08 19-JUN-13:20 34.80 23.85 0.00 0.00 01-JUN-00:10 34.80 23.85
July 0.640716E+09 465.56 10-JUL-13:10 32.30 20.52 0.00 0.00 01-JUL-00:10 32.30 20.52
August 0.761599E+09 588.89 30-AUG-13:00 27.20 15.60 0.00 0.00 01-AUG-00:10 27.20 15.60
September 0.586926E+09 645.41 28-SEP-12:40 22.97 13.90 0.00 0.00 01-SEP-00:10 22.97 13.90
October 0.578983E+09 684.49 04-OCT-12:10 24.50 18.64 0.00 0.00 01-OCT-00:10 24.50 18.64
November 0.146757E+09 577.38 02-NOV-12:50 15.50 8.17 0.00 0.00 01-NOV-00:10 15.50 8.17
December 58105407.65 395.77 17-DEC-13:40 12.20 5.18 0.00 0.00 01-DEC-00:10 12.20 5.18
                     
Annual Sum or Average 0.393709E+10         0.00        
Minimum of Months 9005968.85 145.74   -1.5 -6.0 0.00 0.00   -1.5 -6.0
Maximum of Months 0.761599E+09 684.49   34.80 23.85 0.00 0.00   34.80 23.85



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 33356663.92 729.57 23-JAN-19:02 9.50 9.50 94799435.84 56.69 09-JAN-00:20 9.50 9.50
February 24952171.07 759.01 18-FEB-09:02 5.18 1.91 85595970.82 56.69 01-FEB-00:20 5.18 1.91
March 0.139746E+09 811.18 03-MAR-19:02 12.12 7.02 96189359.96 65.71 27-MAR-21:10 14.13 10.87
April 0.309292E+09 946.49 07-APR-15:02 25.60 15.98 94536550.47 69.52 07-APR-21:00 18.30 13.42
May 0.526935E+09 994.68 30-MAY-08:21 25.55 16.31 0.101553E+09 76.63 31-MAY-21:40 20.13 17.44
June 0.694465E+09 994.48 23-JUN-08:61 26.70 18.47 0.102393E+09 77.71 28-JUN-21:40 21.50 18.92
July 0.895430E+09 984.25 03-JUL-15:02 28.03 21.81 0.103055E+09 77.38 25-JUL-21:10 22.70 20.79
August 0.839805E+09 991.20 12-AUG-15:02 28.72 24.51 0.102206E+09 75.82 10-AUG-21:10 28.72 24.51
September 0.556241E+09 979.18 01-SEP-18:02 27.70 17.44 0.100487E+09 76.57 05-SEP-21:10 23.90 20.42
October 0.359999E+09 894.24 25-OCT-15:02 23.03 10.41 99310957.43 70.97 04-OCT-21:00 23.03 10.41
November 0.154380E+09 807.18 02-NOV-18:02 13.80 7.37 93001164.42 56.69 09-NOV-22:49 12.20 12.20
December 37736357.91 762.72 10-DEC-09:02 4.50 1.71 95024687.64 56.69 01-DEC-01:19 4.50 1.71
                     
Annual Sum or Average 0.457234E+10         0.116815E+10        
Minimum of Months 24952171.07 729.57   4.50 1.71 85595970.82 56.69   4.50 1.71
Maximum of Months 0.895430E+09 994.68   28.72 24.51 0.103055E+09 77.71   28.72 24.51



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 37416076.30 2284.89 20-JAN-09:02 5.40 0.62 94016325.87 56.69 03-JAN-04:19 5.40 0.62
February 57984792.95 2562.22 25-FEB-09:01 -2.0 -5.5 85679198.15 56.69 17-FEB-04:19 -2.0 -5.5
March 0.241582E+09 2550.27 11-MAR-16:01 11.20 5.40 96532752.07 56.69 27-MAR-21:19 13.87 10.67
April 0.645334E+09 2677.25 08-APR-08:62 20.28 15.08 94308749.45 56.69 27-APR-21:10 14.40 13.08
May 0.131331E+10 2754.93 29-MAY-08:62 24.27 16.71 98647661.43 56.69 30-MAY-22:40 18.50 15.37
June 0.197518E+10 2910.35 23-JUN-08:61 26.70 18.47 95935820.42 56.69 22-JUN-22:40 26.70 18.47
July 0.249332E+10 2872.29 13-JUL-08:62 27.07 22.43 99120857.08 56.70 13-JUL-23:00 26.70 22.05
August 0.271656E+10 2900.60 22-AUG-08:62 26.88 18.45 99234054.84 56.70 05-AUG-02:39 26.88 18.45
September 0.176001E+10 2806.63 06-SEP-08:62 24.18 18.63 95682987.34 56.70 06-SEP-22:00 22.20 20.63
October 0.113596E+10 2670.80 02-OCT-15:02 22.88 16.78 98498715.43 56.69 02-OCT-22:40 15.97 15.02
November 0.199891E+09 2502.87 04-NOV-15:01 17.30 12.80 92928548.61 56.69 03-NOV-03:20 17.30 12.80
December 61625756.18 2376.18 02-DEC-09:01 2.38 -1.7 94586067.00 56.69 25-DEC-02:20 5.77 5.31
                     
Annual Sum or Average 0.126382E+11         0.114517E+10        
Minimum of Months 37416076.30 2284.89   -2.0 -5.5 85679198.15 56.69   -2.0 -5.5
Maximum of Months 0.271656E+10 2910.35   27.07 22.43 99234054.84 56.70   26.88 22.05



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 8885291.10 1314.16 19-JAN-09:01 4.97 3.19 93103098.71 56.69 03-JAN-04:19 4.97 3.19
February 15183616.30 2334.97 25-FEB-09:01 -2.0 -5.5 84412674.36 56.69 10-FEB-04:19 -2.0 -5.5
March 0.107308E+09 2321.81 26-MAR-08:62 8.68 7.99 95432029.75 58.99 27-MAR-21:10 14.13 10.87
April 0.432591E+09 2982.25 08-APR-08:51 21.70 15.33 94759716.84 70.37 07-APR-21:40 21.70 15.33
May 0.101026E+10 3330.19 30-MAY-08:62 25.18 15.91 0.103155E+09 80.56 31-MAY-21:30 20.25 17.49
June 0.155165E+10 3229.63 26-JUN-08:32 24.63 19.00 0.104640E+09 79.19 20-JUN-21:19 24.63 19.00
July 0.218999E+10 3192.04 11-JUL-08:32 23.53 16.28 0.104624E+09 79.95 14-JUL-21:30 21.70 21.06
August 0.224526E+10 3185.73 23-AUG-08:51 22.80 15.80 0.104012E+09 79.44 10-AUG-21:10 22.80 15.80
September 0.117927E+10 3158.72 03-SEP-08:51 22.80 14.85 0.102180E+09 80.03 05-SEP-21:10 23.90 20.42
October 0.569467E+09 2771.49 05-OCT-08:51 18.90 16.77 0.100436E+09 71.07 04-OCT-21:40 18.90 16.77
November 78826275.11 2346.22 04-NOV-15:01 17.30 12.80 91916667.24 56.69 26-NOV-02:20 6.70 6.50
December 13453775.01 1910.60 20-DEC-09:01 6.47 4.26 93340616.73 56.69 25-DEC-04:19 7.93 7.57
                     
Annual Sum or Average 0.940214E+10         0.117201E+10        
Minimum of Months 8885291.10 1314.16   -2.0 -5.5 84412674.36 56.69   -2.0 -5.5
Maximum of Months 0.224526E+10 3330.19   25.18 19.00 0.104640E+09 80.56   24.63 21.06



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.103974E+10 1253.05 19-JAN-22:00 5.60 1.07 0.119899E+10 714.01 19-JAN-22:49 5.60 1.07
February 0.120317E+10 1426.77 19-FEB-11:33 7.97 4.38 0.108412E+10 711.14 22-FEB-22:49 2.20 -0.8
March 0.252293E+10 1548.29 29-MAR-10:33 8.17 4.49 0.121814E+10 755.78 03-MAR-22:49 8.17 4.49
April 0.315520E+10 1903.83 08-APR-10:33 23.90 16.13 0.122930E+10 835.49 10-APR-21:40 11.83 5.31
May 0.396507E+10 2138.69 31-MAY-10:35 25.60 19.79 0.136693E+10 912.73 31-MAY-21:49 20.02 17.39
June 0.447109E+10 2348.73 22-JUN-18:03 28.72 17.28 0.146363E+10 933.29 23-JUN-22:10 22.70 21.24
July 0.486039E+10 2375.07 11-JUL-17:09 28.12 17.29 0.154926E+10 948.92 11-JUL-22:10 22.62 17.84
August 0.495309E+10 2384.73 24-AUG-19:30 28.30 16.24 0.157645E+10 951.85 23-AUG-22:10 28.30 16.24
September 0.433870E+10 2334.98 01-SEP-17:01 27.80 17.38 0.143596E+10 946.51 01-SEP-21:49 26.20 17.54
October 0.402699E+10 2002.43 05-OCT-10:33 21.13 17.47 0.139033E+10 885.84 05-OCT-21:49 18.90 17.51
November 0.233566E+10 1687.18 04-NOV-10:45 17.02 11.62 0.118649E+10 786.77 03-NOV-22:10 17.02 11.62
December 0.149610E+10 1449.29 17-DEC-11:33 11.67 4.45 0.119934E+10 714.11 18-DEC-22:49 2.20 0.64
                     
Annual Sum or Average 0.383681E+11         0.158989E+11        
Minimum of Months 0.103974E+10 1253.05   5.60 1.07 0.108412E+10 711.14   2.20 -0.8
Maximum of Months 0.495309E+10 2384.73   28.72 19.79 0.157645E+10 951.85   28.30 21.24



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 23039942.09 2847.74 20-JAN-16:02 6.93 3.71 93461556.64 56.69 03-JAN-04:19 6.93 3.71
February 47756930.43 2893.55 14-FEB-16:01 0.50 -3.9 85017313.37 56.69 14-FEB-04:19 0.50 -3.9
March 0.259939E+09 2969.66 11-MAR-16:01 11.20 5.40 95994253.42 56.69 27-MAR-21:19 13.87 10.67
April 0.625121E+09 3040.87 10-APR-18:02 19.22 10.01 93808768.10 56.69 27-APR-21:40 14.40 12.93
May 0.127575E+10 3184.64 20-MAY-18:02 22.02 11.72 98411638.53 56.69 31-MAY-21:00 19.90 17.35
June 0.212394E+10 3228.99 19-JUN-18:02 32.12 23.09 95846017.97 56.70 19-JUN-23:00 24.40 21.27
July 0.261353E+10 3270.57 12-JUL-18:02 25.50 21.15 99091439.77 56.70 10-JUL-22:00 25.50 21.15
August 0.281162E+10 3296.62 15-AUG-18:02 26.42 20.41 99192136.00 56.70 21-AUG-23:49 27.20 23.26
September 0.170551E+10 3223.06 07-SEP-15:02 26.60 22.96 95501116.99 56.70 14-SEP-21:30 23.60 16.82
October 0.106718E+10 2991.26 02-OCT-18:02 20.82 15.42 98123216.22 56.69 04-OCT-23:00 17.20 16.15
November 0.113951E+09 2784.27 08-NOV-16:01 12.62 10.56 92132398.27 56.69 03-NOV-23:19 12.62 10.56
December 26185603.44 2878.37 02-DEC-16:01 5.92 0.97 93921671.46 56.69 25-DEC-04:19 7.93 7.57
                     
Annual Sum or Average 0.126935E+11         0.114050E+10        
Minimum of Months 23039942.09 2784.27   0.50 -3.9 85017313.37 56.69   0.50 -3.9
Maximum of Months 0.281162E+10 3296.62   32.12 23.09 99192136.00 56.70   27.20 23.26



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 5271389.27 1947.80 17-JAN-16:02 9.45 4.59 92684854.43 56.69 09-JAN-00:20 9.45 4.59
February 10739972.99 2034.24 24-FEB-16:01 7.62 1.74 83965554.70 56.69 07-FEB-04:19 7.62 1.74
March 0.113784E+09 2830.02 11-MAR-16:01 11.20 5.40 95136939.91 66.13 27-MAR-21:10 14.13 10.87
April 0.393809E+09 3266.69 09-APR-18:11 14.43 12.85 94940118.69 75.25 10-APR-18:10 19.22 10.01
May 0.964862E+09 3495.40 29-MAY-18:31 24.80 18.16 0.104910E+09 91.18 31-MAY-21:10 20.48 17.58
June 0.172602E+10 3212.06 23-JUN-08:61 26.70 18.47 0.107774E+09 87.91 28-JUN-21:10 21.20 18.58
July 0.236333E+10 3277.38 03-JUL-18:51 24.40 21.27 0.104448E+09 82.75 05-JUL-21:40 22.40 21.60
August 0.239211E+10 3166.68 15-AUG-18:02 26.42 20.41 0.103635E+09 83.39 10-AUG-21:10 26.42 20.41
September 0.113418E+10 3149.10 10-SEP-21:51 16.70 9.96 0.103100E+09 83.30 06-SEP-21:10 16.70 9.96
October 0.487099E+09 2965.66 02-OCT-15:02 22.88 16.78 0.101088E+09 75.03 04-OCT-21:40 16.87 15.72
November 30239636.40 2616.97 04-NOV-15:01 17.30 12.80 91145808.18 56.69 24-NOV-04:19 -3.5 -5.8
December 5798893.68 1538.79 17-DEC-16:02 9.82 4.16 92778121.45 56.69 15-DEC-04:19 9.82 4.16
                     
Annual Sum or Average 0.962724E+10         0.117561E+10        
Minimum of Months 5271389.27 1538.79   7.62 1.74 83965554.70 56.69   -3.5 -5.8
Maximum of Months 0.239211E+10 3495.40   26.70 21.27 0.107774E+09 91.18   26.42 21.60



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.135040E+09 1563.81 31-JAN-16:02 -1.3 -5.8 95487882.58 56.69 15-JAN-02:20 -1.3 -5.8
February 0.197480E+09 1575.45 02-FEB-16:02 4.13 -2.3 87103697.34 56.69 21-FEB-00:20 2.60 1.73
March 0.354086E+09 1577.13 13-MAR-15:02 7.12 1.52 97136854.74 56.69 03-MAR-22:49 7.12 1.52
April 0.491783E+09 1652.93 07-APR-15:02 25.60 15.98 94375238.11 56.69 07-APR-22:19 18.13 13.36
May 0.753462E+09 1674.26 20-MAY-18:02 22.02 11.72 98466871.23 56.69 31-MAY-21:00 19.90 17.35
June 0.112726E+10 1705.41 22-JUN-18:02 28.72 17.28 95777387.55 56.69 20-JUN-00:10 28.72 17.28
July 0.147876E+10 1726.46 09-JUL-18:02 27.12 24.06 99084837.47 56.70 10-JUL-00:40 28.17 22.16
August 0.167372E+10 1767.64 16-AUG-15:02 32.02 25.35 99168791.23 56.70 04-AUG-21:10 32.02 25.35
September 0.124307E+10 1756.29 14-SEP-15:02 30.00 20.06 95621647.32 56.70 01-SEP-21:30 30.00 20.06
October 0.110730E+10 1690.88 03-OCT-15:02 23.22 19.26 98631512.09 56.69 04-OCT-22:40 17.43 15.94
November 0.334785E+09 1541.11 02-NOV-18:02 13.80 7.37 94148137.85 56.69 03-NOV-21:10 12.80 10.17
December 0.221464E+09 1570.17 15-DEC-16:01 4.32 0.72 96098724.98 56.69 18-DEC-00:20 2.60 0.34
                     
Annual Sum or Average 0.911820E+10         0.115110E+10        
Minimum of Months 0.135040E+09 1541.11   -1.3 -5.8 87103697.34 56.69   -1.3 -5.8
Maximum of Months 0.167372E+10 1767.64   32.02 25.35 99168791.23 56.70   32.02 25.35



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.303805E+11 17089.75 23-JAN-23:00 10.60 10.26 0.183578E+11 11347.94 14-JAN-00:20 10.60 10.26
February 0.273031E+11 16450.08 23-FEB-23:00 5.00 4.23 0.165832E+11 11347.98 04-FEB-00:20 5.00 4.23
March 0.330478E+11 18823.89 27-MAR-21:04 14.13 10.87 0.188784E+11 11348.32 27-MAR-21:19 13.87 10.67
April 0.345123E+11 20342.49 07-APR-21:53 18.30 13.42 0.183989E+11 11348.84 07-APR-22:10 18.22 13.39
May 0.391487E+11 21840.84 31-MAY-21:52 19.90 17.35 0.192121E+11 11349.20 31-MAY-22:10 19.78 17.36
June 0.414548E+11 23256.39 19-JUN-21:20 28.53 20.50 0.187128E+11 11351.68 23-JUN-21:19 22.80 20.95
July 0.445449E+11 23053.39 10-JUL-21:20 27.03 20.02 0.192856E+11 11356.88 07-JUL-21:19 27.03 20.02
August 0.443214E+11 23342.76 04-AUG-21:20 30.90 23.99 0.193540E+11 11361.91 18-AUG-21:19 24.63 17.59
September 0.394134E+11 22420.78 01-SEP-21:50 26.20 17.54 0.186150E+11 11349.11 06-SEP-22:10 22.20 20.63
October 0.371171E+11 20562.71 05-OCT-21:53 18.90 17.46 0.190665E+11 11348.84 04-OCT-22:10 18.90 17.46
November 0.319592E+11 18537.89 03-NOV-22:00 12.80 10.33 0.181381E+11 11347.97 27-NOV-00:20 8.50 8.23
December 0.310820E+11 16881.19 04-DEC-23:00 8.30 7.50 0.185603E+11 11347.97 22-DEC-00:20 -3.3 -6.0
                     
Annual Sum or Average 0.434285E+12         0.223163E+12        
Minimum of Months 0.273031E+11 16450.08   5.00 4.23 0.165832E+11 11347.94   -3.3 -6.0
Maximum of Months 0.445449E+11 23342.76   30.90 23.99 0.193540E+11 11361.91   27.03 20.95



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.337046E+11 19118.53 23-JAN-23:00 10.60 10.26 0.186813E+11 11348.08 30-JAN-00:20 -3.1 -4.6
February 0.302580E+11 18423.32 23-FEB-23:00 5.00 4.23 0.168797E+11 11348.06 27-FEB-00:20 -0.9 -4.8
March 0.366808E+11 20801.24 27-MAR-21:04 14.13 10.87 0.190845E+11 11348.34 27-MAR-21:19 13.87 10.67
April 0.380618E+11 22042.84 07-APR-21:10 19.22 13.77 0.185477E+11 11348.84 07-APR-22:10 18.22 13.39
May 0.427171E+11 23126.80 31-MAY-21:52 19.90 17.35 0.192846E+11 11349.21 31-MAY-22:10 19.78 17.36
June 0.444442E+11 24540.21 19-JUN-21:20 28.53 20.50 0.187368E+11 11370.74 23-JUN-21:19 22.80 20.95
July 0.474447E+11 24268.04 10-JUL-21:20 27.03 20.02 0.192994E+11 11371.77 05-JUL-21:19 27.03 20.02
August 0.471572E+11 24573.85 04-AUG-21:20 30.90 23.99 0.193715E+11 11371.90 18-AUG-21:19 24.63 17.59
September 0.424492E+11 23674.47 01-SEP-21:10 26.60 18.09 0.186597E+11 11358.29 14-SEP-21:19 23.87 17.02
October 0.404622E+11 21973.72 05-OCT-21:53 18.90 17.46 0.191773E+11 11348.85 04-OCT-22:10 18.90 17.46
November 0.354296E+11 20385.75 03-NOV-22:00 12.80 10.33 0.183465E+11 11348.07 24-NOV-00:20 -3.3 -5.8
December 0.345483E+11 18872.66 04-DEC-23:00 8.30 7.50 0.188190E+11 11348.02 22-DEC-00:20 -3.3 -6.0
                     
Annual Sum or Average 0.473358E+12         0.224888E+12        
Minimum of Months 0.302580E+11 18423.32   5.00 4.23 0.168797E+11 11348.02   -3.3 -6.0
Maximum of Months 0.474447E+11 24573.85   30.90 23.99 0.193715E+11 11371.90   27.03 20.95



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.457762E+11 25171.17 17-JAN-11:50 9.13 4.92 0.187699E+11 11319.67 21-JAN-18:19 7.20 6.67
February 0.415469E+11 25817.61 19-FEB-11:50 7.88 4.27 0.169521E+11 11319.66 18-FEB-18:19 7.88 4.27
March 0.485933E+11 26825.67 29-MAR-10:33 8.17 4.49 0.187952E+11 11319.67 04-MAR-18:19 8.17 4.49
April 0.491227E+11 28975.79 08-APR-10:33 23.90 16.13 0.181997E+11 11319.59 15-APR-17:19 9.40 9.40
May 0.533702E+11 29757.83 29-MAY-10:33 27.43 17.92 0.188243E+11 11319.68 20-MAY-17:19 27.43 17.92
June 0.536993E+11 31659.78 01-JUN-18:02 27.70 16.11 0.182387E+11 11319.69 17-JUN-17:19 22.60 20.38
July 0.566848E+11 31221.33 11-JUL-17:09 28.12 17.29 0.188466E+11 11319.69 15-JUL-17:19 25.93 22.25
August 0.569212E+11 31124.09 22-AUG-17:01 28.72 16.50 0.188549E+11 11319.68 19-AUG-17:19 28.72 16.50
September 0.526318E+11 30737.00 01-SEP-17:01 27.80 17.38 0.182277E+11 11319.67 30-SEP-17:19 17.77 12.98
October 0.520253E+11 28438.03 04-OCT-10:33 22.23 17.92 0.188154E+11 11319.64 28-OCT-17:19 9.03 2.93
November 0.467366E+11 27157.26 04-NOV-10:45 17.02 11.62 0.181828E+11 11319.63 18-NOV-18:19 5.40 2.24
December 0.465564E+11 25688.08 17-DEC-11:50 11.93 4.48 0.187776E+11 11319.64 16-DEC-18:19 11.93 4.48
                     
Annual Sum or Average 0.603665E+12         0.221485E+12        
Minimum of Months 0.415469E+11 25171.17   7.88 4.27 0.169521E+11 11319.59   5.40 2.24
Maximum of Months 0.569212E+11 31659.78   28.72 17.92 0.188549E+11 11319.69   28.72 22.25



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.195306E+10 3118.18 17-JAN-11:35 8.87 4.86 0.126906E+10 745.62 04-JAN-03:20 8.87 4.86
February 0.203129E+10 3338.71 19-FEB-11:33 7.97 4.38 0.114802E+10 745.60 09-FEB-04:00 7.97 4.38
March 0.512895E+10 3670.21 03-MAR-11:33 13.53 7.78 0.128813E+10 807.13 27-MAR-21:40 13.33 10.26
April 0.688870E+10 4543.90 08-APR-10:50 23.35 15.96 0.129362E+10 888.82 07-APR-21:40 23.35 15.96
May 0.895299E+10 5081.70 31-MAY-10:35 25.60 19.79 0.143899E+10 972.17 31-MAY-21:40 20.13 17.44
June 0.101445E+11 5745.16 19-JUN-14:10 34.22 23.63 0.154371E+10 1007.39 19-JUN-23:19 25.93 20.91
July 0.113685E+11 6497.62 11-JUL-15:07 28.30 17.52 0.165118E+10 1007.39 10-JUL-23:19 28.30 17.52
August 0.116190E+11 6425.54 16-AUG-12:50 31.93 25.44 0.166239E+10 1007.39 04-AUG-23:19 31.93 25.44
September 0.967251E+10 5709.03 01-SEP-14:10 31.02 17.36 0.149246E+10 1007.36 01-SEP-21:30 26.40 17.81
October 0.863038E+10 4588.89 05-OCT-10:33 21.13 17.47 0.141743E+10 924.31 05-OCT-21:40 18.90 17.57
November 0.488748E+10 3816.95 04-NOV-10:50 17.02 11.62 0.124144E+10 812.15 03-NOV-22:10 17.02 11.62
December 0.281321E+10 3396.85 17-DEC-11:33 11.67 4.45 0.126950E+10 745.61 01-DEC-05:49 11.67 4.45
                     
Annual Sum or Average 0.840906E+11         0.167159E+11        
Minimum of Months 0.195306E+10 3118.18   7.97 4.38 0.114802E+10 745.60   7.97 4.38
Maximum of Months 0.116190E+11 6497.62   34.22 25.44 0.166239E+10 1007.39   31.93 25.44



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -9.6
February 0.00 0.00 01-FEB-00:03 -1.1
March 0.00 0.00 01-MAR-00:03 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:05 10.33
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:05 10.40
December 0.00 0.00 01-DEC-00:03 5.97
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -9.6
Maximum of Months 0.00 0.00   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.335203E+09 1157.49 02-JAN-07:10 -11.6
February 0.209621E+09 1068.55 06-FEB-07:05 -13.2
March 17502615.58 372.98 17-MAR-06:30 -1.1
April 445859.72 61.74 02-APR-04:40 3.90
May 0.00 0.00 01-MAY-00:05 10.33
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 15257977.93 396.07 23-NOV-06:00 -3.9
December 0.120229E+09 542.72 30-DEC-17:00 1.70
         
Annual Sum or Average 0.698260E+09      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.335203E+09 1157.49   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -9.6
February 0.00 0.00 01-FEB-00:03 -1.1
March 0.00 0.00 01-MAR-00:03 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:05 10.33
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:05 10.40
December 0.00 0.00 01-DEC-00:03 5.97
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -9.6
Maximum of Months 0.00 0.00   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 87822100.18 463.94 02-JAN-15:00 -6.1
February 0.101327E+09 459.92 06-FEB-15:00 -7.2
March 217615.63 26.50 17-MAR-13:00 -1.1
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:05 10.33
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:05 10.40
December 453703.37 75.46 31-DEC-18:00 -5.0
         
Annual Sum or Average 0.189821E+09      
Minimum of Months 0.00 0.00   -7.2
Maximum of Months 0.101327E+09 463.94   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.172892E+09 405.31 02-JAN-15:00 -6.1
February 0.166676E+09 415.76 06-FEB-16:00 -7.2
March 3958320.03 123.96 17-MAR-12:30 -1.1
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:05 10.33
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 6214740.50 90.25 25-NOV-17:00 3.90
December 20726559.96 193.40 31-DEC-18:00 -5.0
         
Annual Sum or Average 0.370468E+09      
Minimum of Months 0.00 0.00   -7.2
Maximum of Months 0.172892E+09 415.76   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -9.6
February 0.00 0.00 01-FEB-00:03 -1.1
March 0.00 0.00 01-MAR-00:03 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:05 10.33
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:05 10.40
December 0.00 0.00 01-DEC-00:03 5.97
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -9.6
Maximum of Months 0.00 0.00   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 16456.84 10.30 08-JAN-15:40 -1.5
February 0.00 0.00 01-FEB-00:03 -1.1
March 0.00 0.00 01-MAR-00:03 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:05 10.33
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:05 10.40
December 0.00 0.00 01-DEC-00:03 5.97
         
Annual Sum or Average 16456.84      
Minimum of Months 0.00 0.00   -1.5
Maximum of Months 16456.84 10.30   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -9.6
February 0.00 0.00 01-FEB-00:03 -1.1
March 0.00 0.00 01-MAR-00:03 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:05 10.33
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:05 10.40
December 0.00 0.00 01-DEC-00:03 5.97
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -9.6
Maximum of Months 0.00 0.00   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.103580E+10 2380.80 02-JAN-09:01 -10.3
February 0.827382E+09 2378.71 06-FEB-16:01 -7.1
March 0.326969E+09 2317.50 17-MAR-08:61 -1.1
April 0.125397E+09 2223.78 21-APR-15:01 7.30
May 3823585.12 833.10 01-MAY-18:04 12.43
June 960593.42 740.05 29-JUN-08:05 20.18
July 451022.29 482.54 18-JUL-08:05 24.32
August 718055.86 917.40 08-AUG-08:04 21.47
September 1795991.75 961.22 26-SEP-15:04 18.72
October 12117896.66 842.38 19-OCT-08:03 10.97
November 0.404005E+09 2294.40 25-NOV-09:01 -0.3
December 0.787374E+09 2358.92 31-DEC-19:01 -5.7
         
Annual Sum or Average 0.352680E+10      
Minimum of Months 451022.29 482.54   -10.3
Maximum of Months 0.103580E+10 2380.80   24.32



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.126810E+10 2393.93 02-JAN-09:01 -10.3
February 0.111492E+10 2397.59 06-FEB-09:01 -12.0
March 0.450927E+09 2315.14 17-MAR-08:61 -1.1
April 0.149347E+09 2219.35 21-APR-15:01 7.30
May 3989199.37 785.67 01-MAY-18:04 12.43
June 241541.82 454.31 12-JUN-08:55 19.40
July 212081.41 516.94 18-JUL-08:05 24.32
August 190033.19 523.20 13-AUG-06:54 25.00
September 1256250.76 1024.44 28-SEP-08:53 20.60
October 28878254.18 973.69 19-OCT-18:04 13.90
November 0.554142E+09 2329.52 24-NOV-09:01 -1.5
December 0.103177E+10 2360.54 31-DEC-19:01 -5.7
         
Annual Sum or Average 0.460397E+10      
Minimum of Months 190033.19 454.31   -12.0
Maximum of Months 0.126810E+10 2397.59   25.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -9.6
February 0.00 0.00 01-FEB-00:03 -1.1
March 0.00 0.00 01-MAR-00:03 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:05 10.33
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:05 10.40
December 0.00 0.00 01-DEC-00:03 5.97
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -9.6
Maximum of Months 0.00 0.00   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.135441E+09 700.56 02-JAN-16:02 -6.0
February 0.138933E+09 709.72 06-FEB-16:01 -7.1
March 16223325.41 660.72 16-MAR-15:01 0.68
April 836538.41 342.24 03-APR-08:03 5.68
May 183968.57 434.62 03-MAY-15:05 15.92
June 1564.47 11.75 06-JUN-15:07 18.98
July 0.00 0.00 01-JUL-00:10 20.00
August 2654.77 21.61 25-AUG-21:57 21.10
September 33383.01 89.60 24-SEP-15:07 17.70
October 597070.21 465.78 30-OCT-15:05 16.52
November 24871595.10 665.38 22-NOV-16:01 0.60
December 67274628.79 677.96 31-DEC-16:01 -3.1
         
Annual Sum or Average 0.384399E+09      
Minimum of Months 0.00 0.00   -7.1
Maximum of Months 0.138933E+09 709.72   21.10



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.102722E+10 2331.80 14-JAN-16:02 -6.1
February 0.802481E+09 2327.36 06-FEB-16:01 -7.1
March 0.353158E+09 2266.30 16-MAR-15:01 0.68
April 0.129161E+09 2179.63 21-APR-15:01 7.30
May 3579613.98 871.54 02-MAY-18:05 14.72
June 279149.70 740.43 13-JUN-08:05 20.10
July 46356.57 219.60 18-JUL-08:05 24.32
August 3775.78 37.76 07-AUG-08:05 20.28
September 886942.88 731.77 21-SEP-08:05 20.68
October 12605745.51 959.64 06-OCT-18:04 14.90
November 0.375769E+09 2244.98 25-NOV-09:01 -0.3
December 0.776393E+09 2312.65 31-DEC-19:01 -5.7
         
Annual Sum or Average 0.348158E+10      
Minimum of Months 3775.78 37.76   -7.1
Maximum of Months 0.102722E+10 2331.80   24.32



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.125045E+10 2326.01 14-JAN-16:02 -6.1
February 0.107682E+10 2336.97 06-FEB-16:01 -7.1
March 0.478633E+09 2262.09 16-MAR-15:01 0.68
April 0.152855E+09 2175.22 21-APR-15:01 7.30
May 3829213.35 1010.39 01-MAY-18:04 12.43
June 97076.77 376.58 01-JUN-21:55 20.60
July 12831.48 67.51 23-JUL-21:56 22.80
August 22325.18 154.03 06-AUG-21:56 20.00
September 667637.36 566.88 23-SEP-08:05 13.30
October 31667574.26 953.56 19-OCT-15:05 16.02
November 0.499998E+09 2268.69 23-NOV-19:01 -0.7
December 0.995559E+09 2314.41 31-DEC-19:01 -5.7
         
Annual Sum or Average 0.449060E+10      
Minimum of Months 12831.48 67.51   -7.1
Maximum of Months 0.125045E+10 2336.97   22.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.162652E+09 972.84 14-JAN-16:15 -6.1
February 84099385.71 750.70 06-FEB-07:10 -13.2
March 1874711.33 218.57 17-MAR-08:03 -1.1
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:05 10.33
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 977354.08 139.09 25-NOV-17:00 3.90
December 53571828.12 557.46 11-DEC-15:00 1.10
         
Annual Sum or Average 0.303176E+09      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.162652E+09 972.84   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.154595E+10 2846.55 14-JAN-16:02 -6.1
February 0.127594E+10 2842.17 06-FEB-16:01 -7.1
March 0.579528E+09 2761.31 17-MAR-08:61 -1.1
April 0.249476E+09 2673.66 21-APR-15:01 7.30
May 14655358.07 961.04 01-MAY-18:04 12.43
June 943130.43 824.48 22-JUN-08:04 24.60
July 615444.70 625.08 05-JUL-08:05 22.98
August 1084873.26 886.07 08-AUG-08:04 21.47
September 3020898.71 984.59 16-SEP-18:04 18.90
October 57401563.62 1104.97 27-OCT-08:62 7.48
November 0.686467E+09 2754.42 25-NOV-09:01 -0.3
December 0.122970E+10 2811.68 31-DEC-19:01 -5.7
         
Annual Sum or Average 0.564478E+10      
Minimum of Months 615444.70 625.08   -7.1
Maximum of Months 0.154595E+10 2846.55   24.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.183057E+10 2854.71 02-JAN-09:01 -10.3
February 0.162575E+10 2859.83 06-FEB-09:01 -12.0
March 0.747221E+09 2756.09 22-MAR-08:61 -2.0
April 0.288281E+09 2663.96 21-APR-15:01 7.30
May 14756724.56 1017.23 01-MAY-18:04 12.43
June 267154.07 450.59 06-JUN-21:55 17.20
July 292389.89 621.77 09-JUL-06:54 26.70
August 244306.52 444.61 08-AUG-08:54 23.30
September 2353053.97 1190.54 24-SEP-15:04 17.70
October 0.107836E+09 2607.39 29-OCT-08:62 6.88
November 0.896772E+09 2768.11 24-NOV-09:01 -1.5
December 0.153683E+10 2817.28 31-DEC-19:01 -5.7
         
Annual Sum or Average 0.705118E+10      
Minimum of Months 244306.52 444.61   -12.0
Maximum of Months 0.183057E+10 2859.83   26.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.441824E+09 1493.63 14-JAN-16:02 -6.1
February 0.306835E+09 1457.98 26-FEB-16:01 -1.6
March 0.131455E+09 1442.04 16-MAR-15:01 0.68
April 54664678.98 1388.15 21-APR-15:01 7.30
May 1739277.92 524.10 03-MAY-15:05 15.92
June 380126.54 353.43 04-JUN-08:05 22.38
July 193058.25 379.84 18-JUL-08:05 24.32
August 137034.43 402.99 08-AUG-08:04 21.47
September 329566.09 367.54 21-SEP-08:05 20.68
October 1839739.64 483.37 28-OCT-18:05 8.22
November 0.112746E+09 1407.12 25-NOV-09:01 -0.3
December 0.300135E+09 1452.13 30-DEC-16:01 1.20
         
Annual Sum or Average 0.135228E+10      
Minimum of Months 137034.43 353.43   -6.1
Maximum of Months 0.441824E+09 1493.63   24.32



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -9.6
February 0.00 0.00 01-FEB-00:03 -1.1
March 0.00 0.00 01-MAR-00:03 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:05 10.33
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:05 10.40
December 0.00 0.00 01-DEC-00:03 5.97
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -9.6
Maximum of Months 0.00 0.00   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -9.6
February 0.00 0.00 01-FEB-00:03 -1.1
March 0.00 0.00 01-MAR-00:03 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:05 10.33
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:05 10.40
December 0.00 0.00 01-DEC-00:03 5.97
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -9.6
Maximum of Months 0.00 0.00   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -9.6
February 0.00 0.00 01-FEB-00:03 -1.1
March 0.00 0.00 01-MAR-00:03 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:05 10.33
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:05 10.40
December 0.00 0.00 01-DEC-00:03 5.97
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -9.6
Maximum of Months 0.00 0.00   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.497162E+09 2515.84 02-JAN-07:15 -11.5
February 0.392708E+09 2458.42 06-FEB-07:05 -13.2
March 6347293.22 684.84 23-MAR-06:10 -4.7
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:05 10.33
June 0.00 0.00 01-JUN-00:05 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:05 23.90
September 0.00 0.00 01-SEP-00:05 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 19608847.68 678.28 24-NOV-07:10 -4.3
December 41635309.32 596.52 15-DEC-07:10 -3.6
         
Annual Sum or Average 0.957462E+09      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.497162E+09 2515.84   23.90



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.962539E+10 9271.23 02-JAN-20:10 0.121516E+11 9632.53 02-JAN-20:10
February 0.869085E+10 9271.23 01-FEB-20:10 0.109726E+11 9632.53 01-FEB-20:10
March 0.965507E+10 9271.23 01-MAR-20:10 0.121771E+11 9632.53 01-MAR-20:10
April 0.929905E+10 9271.23 03-APR-19:10 0.117446E+11 9632.53 03-APR-19:10
May 0.964208E+10 9271.23 01-MAY-19:10 0.121662E+11 9632.53 01-MAY-19:10
June 0.934170E+10 9271.23 01-JUN-19:10 0.117829E+11 9632.53 01-JUN-19:10
July 0.959943E+10 9271.23 03-JUL-19:10 0.121279E+11 9632.53 03-JUL-19:10
August 0.965878E+10 9271.23 01-AUG-19:10 0.121808E+11 9632.53 01-AUG-19:10
September 0.930276E+10 9271.23 01-SEP-19:10 0.117482E+11 9632.53 01-SEP-19:10
October 0.962169E+10 9271.23 02-OCT-19:10 0.121479E+11 9632.53 02-OCT-19:10
November 0.933428E+10 9271.23 01-NOV-19:10 0.117774E+11 9632.53 01-NOV-19:10
December 0.959943E+10 9271.23 01-DEC-20:10 0.121279E+11 9632.53 01-DEC-20:10
             
Annual Sum or Average 0.113371E+12     0.143105E+12    
Minimum of Months 0.869085E+10 9271.23   0.109726E+11 9632.53  
Maximum of Months 0.965878E+10 9271.23   0.121808E+11 9632.53  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.531884E+09 512.31 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.480243E+09 512.31 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.533523E+09 512.31 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.513850E+09 512.31 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.532806E+09 512.31 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.516207E+09 512.31 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.530449E+09 512.31 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.533728E+09 512.31 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.514055E+09 512.31 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.531679E+09 512.31 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.515797E+09 512.31 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.530449E+09 512.31 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.626467E+10     0.101856E+11    
Minimum of Months 0.480243E+09 512.31   0.780982E+09 685.60  
Maximum of Months 0.533728E+09 512.31   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.615923E+09 593.26 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.556123E+09 593.26 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.617822E+09 593.26 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.595041E+09 593.26 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.616991E+09 593.26 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.597770E+09 593.26 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.614262E+09 593.26 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.618059E+09 593.26 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.595278E+09 593.26 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.615686E+09 593.26 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.597295E+09 593.26 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.614262E+09 593.26 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.725451E+10     0.117950E+11    
Minimum of Months 0.556123E+09 593.26   0.904380E+09 793.93  
Maximum of Months 0.618059E+09 593.26   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.710312E+09 684.18 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.641347E+09 684.18 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.712502E+09 684.18 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.686229E+09 684.18 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.711544E+09 684.18 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.689376E+09 684.18 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.708397E+09 684.18 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.712775E+09 684.18 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.686503E+09 684.18 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.710039E+09 684.18 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.688829E+09 684.18 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.708397E+09 684.18 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.836625E+10     0.124712E+11    
Minimum of Months 0.641347E+09 684.18   0.956227E+09 839.45  
Maximum of Months 0.712775E+09 684.18   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.158446E+09 152.61 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.143062E+09 152.61 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.158934E+09 152.61 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.153074E+09 152.61 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.158720E+09 152.61 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.153776E+09 152.61 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.158018E+09 152.61 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.158995E+09 152.61 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.153135E+09 152.61 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.158385E+09 152.61 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.153654E+09 152.61 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.158018E+09 152.61 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.186622E+10     0.359760E+10    
Minimum of Months 0.143062E+09 152.61   0.275845E+09 242.16  
Maximum of Months 0.158995E+09 152.61   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.415991E+09 400.68 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.375602E+09 400.68 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.417273E+09 400.68 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.401887E+09 400.68 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.416712E+09 400.68 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.403730E+09 400.68 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.414869E+09 400.68 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.417433E+09 400.68 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.402047E+09 400.68 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.415830E+09 400.68 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.403409E+09 400.68 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.414869E+09 400.68 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.489965E+10     0.679355E+11    
Minimum of Months 0.375602E+09 400.68   0.520895E+10 4572.80  
Maximum of Months 0.417433E+09 400.68   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.125984E+10 1573.46 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.107756E+10 1573.46 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.113069E+10 1573.46 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.101172E+10 1573.46 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.950864E+09 1573.46 01-MAY-19:10 0.121917E+10 965.27 01-MAY-19:10
June 0.886205E+09 1573.46 01-JUN-19:19 0.118076E+10 965.27 01-JUN-19:10
July 0.920528E+09 1573.46 03-JUL-19:30 0.121533E+10 965.27 03-JUL-19:10
August 0.100414E+10 1573.46 01-AUG-19:10 0.122063E+10 965.27 01-AUG-19:10
September 0.105796E+10 1573.46 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.117843E+10 1573.46 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.118316E+10 1573.46 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.124968E+10 1573.46 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.129108E+11     0.143405E+11    
Minimum of Months 0.886205E+09 1573.46   0.109956E+10 965.27  
Maximum of Months 0.125984E+10 1573.46   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.106226E+11 10645.38 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.951406E+10 10645.38 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.104990E+11 10645.38 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.100313E+11 10645.38 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.102854E+11 10645.38 01-MAY-19:10 0.126672E+11 10029.21 01-MAY-19:10
June 0.993134E+10 10645.38 01-JUN-19:19 0.122682E+11 10029.21 01-JUN-19:10
July 0.102193E+11 10645.38 03-JUL-19:30 0.126273E+11 10029.21 03-JUL-19:10
August 0.103580E+11 10645.38 01-AUG-19:10 0.126824E+11 10029.21 01-AUG-19:10
September 0.100828E+11 10645.38 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.105112E+11 10645.38 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.102462E+11 10645.38 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.105808E+11 10645.38 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.122882E+12     0.148998E+12    
Minimum of Months 0.951406E+10 10645.38   0.114244E+11 10029.21  
Maximum of Months 0.106226E+11 10645.38   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.131236E+09 118.74 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.118519E+09 118.74 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.130193E+09 118.74 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.127154E+09 118.74 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.130715E+09 118.74 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.126145E+09 118.74 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.131741E+09 118.74 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.130193E+09 118.74 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.127188E+09 118.74 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.131219E+09 118.74 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.126649E+09 118.74 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.131758E+09 118.74 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.154271E+10     0.307301E+10    
Minimum of Months 0.118519E+09 118.74   0.235798E+09 237.06  
Maximum of Months 0.131758E+09 118.74   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.131221E+09 118.73 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.118505E+09 118.73 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.130178E+09 118.73 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.127139E+09 118.73 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.130699E+09 118.73 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.126130E+09 118.73 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.131725E+09 118.73 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.130178E+09 118.73 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.127173E+09 118.73 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.131204E+09 118.73 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.126635E+09 118.73 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.131742E+09 118.73 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.154253E+10     0.307265E+10    
Minimum of Months 0.118505E+09 118.73   0.235770E+09 237.03  
Maximum of Months 0.131742E+09 118.73   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 82476868.03 74.62 01-JAN-19:10 0.255708E+09 232.19 01-JAN-08:09
February 74484663.28 74.62 01-FEB-20:10 0.230956E+09 232.19 01-FEB-07:10
March 81821381.83 74.62 01-MAR-20:10 0.255355E+09 232.19 01-MAR-07:10
April 79911301.67 74.62 01-APR-18:10 0.247516E+09 232.19 01-APR-07:10
May 82149124.93 74.62 01-MAY-19:10 0.255532E+09 232.19 01-MAY-06:10
June 79277307.08 74.62 01-JUN-19:10 0.247163E+09 232.19 01-JUN-06:10
July 82793865.32 74.62 01-JUL-18:10 0.255885E+09 232.19 01-JUL-07:10
August 81821381.83 74.62 01-AUG-19:10 0.255355E+09 232.19 01-AUG-06:10
September 79932793.28 74.62 01-SEP-19:10 0.247516E+09 232.19 01-SEP-06:10
October 82466122.22 74.62 01-OCT-18:10 0.255708E+09 232.19 01-OCT-07:10
November 79594304.38 74.62 01-NOV-19:10 0.247340E+09 232.19 01-NOV-06:10
December 82804611.13 74.62 01-DEC-20:10 0.255885E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.969534E+09     0.300992E+10    
Minimum of Months 74484663.28 74.62   0.230956E+09 232.19  
Maximum of Months 82804611.13 74.62   0.255885E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 82499421.18 74.64 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 74505030.97 74.64 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 81843755.73 74.64 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 79933153.27 74.64 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 82171588.45 74.64 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 79298985.31 74.64 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 82816505.16 74.64 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 81843755.73 74.64 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 79954650.76 74.64 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 82488672.43 74.64 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 79616069.29 74.64 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 82827253.90 74.64 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.969799E+09     0.301074E+10    
Minimum of Months 74505030.97 74.64   0.231020E+09 232.26  
Maximum of Months 82827253.90 74.64   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.131236E+09 118.74 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.118519E+09 118.74 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.130193E+09 118.74 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.127154E+09 118.74 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.130715E+09 118.74 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.126145E+09 118.74 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.131741E+09 118.74 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.130193E+09 118.74 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.127188E+09 118.74 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.131219E+09 118.74 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.126649E+09 118.74 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.131758E+09 118.74 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.154271E+10     0.307301E+10    
Minimum of Months 0.118519E+09 118.74   0.235798E+09 237.06  
Maximum of Months 0.131758E+09 118.74   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.131221E+09 118.73 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.118505E+09 118.73 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.130178E+09 118.73 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.127139E+09 118.73 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.130699E+09 118.73 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.126130E+09 118.73 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.131725E+09 118.73 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.130178E+09 118.73 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.127173E+09 118.73 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.131204E+09 118.73 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.126635E+09 118.73 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.131742E+09 118.73 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.154253E+10     0.307265E+10    
Minimum of Months 0.118505E+09 118.73   0.235770E+09 237.03  
Maximum of Months 0.131742E+09 118.73   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.120431E+10 1160.00 02-JAN-20:10 0.00 0.00
February 0.108739E+10 1160.00 01-FEB-20:10 0.00 0.00
March 0.120803E+10 1160.00 01-MAR-20:10 0.00 0.00
April 0.116348E+10 1160.00 03-APR-19:10 0.00 0.00
May 0.120640E+10 1160.00 01-MAY-19:10 0.00 0.00
June 0.116882E+10 1160.00 01-JUN-19:10 0.00 0.00
July 0.120107E+10 1160.00 03-JUL-19:10 0.00 0.00
August 0.120849E+10 1160.00 01-AUG-19:10 0.00 0.00
September 0.116395E+10 1160.00 01-SEP-19:10 0.00 0.00
October 0.120385E+10 1160.00 02-OCT-19:10 0.00 0.00
November 0.116789E+10 1160.00 01-NOV-19:10 0.00 0.00
December 0.120107E+10 1160.00 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.141847E+11     0.00 0.00
Minimum of Months 0.108739E+10 1160.00   0.00 0.00
Maximum of Months 0.120849E+10 1160.00   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.131236E+09 118.74 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.118519E+09 118.74 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.130193E+09 118.74 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.127154E+09 118.74 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.130715E+09 118.74 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.126145E+09 118.74 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.131741E+09 118.74 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.130193E+09 118.74 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.127188E+09 118.74 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.131219E+09 118.74 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.126649E+09 118.74 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.131758E+09 118.74 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.154271E+10     0.307301E+10    
Minimum of Months 0.118519E+09 118.74   0.235798E+09 237.06  
Maximum of Months 0.131758E+09 118.74   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.131221E+09 118.73 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.118505E+09 118.73 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.130178E+09 118.73 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.127139E+09 118.73 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.130699E+09 118.73 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.126130E+09 118.73 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.131725E+09 118.73 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.130178E+09 118.73 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.127173E+09 118.73 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.131204E+09 118.73 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.126635E+09 118.73 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.131742E+09 118.73 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.154253E+10     0.307265E+10    
Minimum of Months 0.118505E+09 118.73   0.235770E+09 237.03  
Maximum of Months 0.131742E+09 118.73   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 82499421.18 74.64 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 74505030.97 74.64 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 81843755.73 74.64 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 79933153.27 74.64 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 82171588.45 74.64 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 79298985.31 74.64 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 82816505.16 74.64 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 81843755.73 74.64 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 79954650.76 74.64 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 82488672.43 74.64 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 79616069.29 74.64 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 82827253.90 74.64 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.969799E+09     0.301074E+10    
Minimum of Months 74505030.97 74.64   0.231020E+09 232.26  
Maximum of Months 82827253.90 74.64   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.257787E+10 2763.12 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.226874E+10 2763.12 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.244509E+10 2763.12 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.227067E+10 2763.12 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.224791E+10 2763.12 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.214222E+10 2763.12 01-JUN-19:19 0.144540E+11 6747.90 01-JUN-06:10
July 0.221387E+10 2763.12 03-JUL-19:30 0.149358E+11 6747.90 01-JUL-06:10
August 0.230551E+10 2763.12 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.232023E+10 2763.12 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.248267E+10 2763.12 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.245588E+10 2763.12 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.258248E+10 2763.12 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.283131E+11     0.175857E+12    
Minimum of Months 0.214222E+10 2763.12   0.134904E+11 6747.90  
Maximum of Months 0.258248E+10 2763.12   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.257787E+10 2763.12 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.226874E+10 2763.12 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.244509E+10 2763.12 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.227067E+10 2763.12 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.224791E+10 2763.12 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.214222E+10 2763.12 01-JUN-19:19 0.144540E+11 6747.90 01-JUN-06:10
July 0.221387E+10 2763.12 03-JUL-19:30 0.149358E+11 6747.90 01-JUL-06:10
August 0.230551E+10 2763.12 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.232023E+10 2763.12 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.248267E+10 2763.12 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.245588E+10 2763.12 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.258248E+10 2763.12 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.283131E+11     0.175857E+12    
Minimum of Months 0.214222E+10 2763.12   0.134904E+11 6747.90  
Maximum of Months 0.258248E+10 2763.12   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.113250E+10 1090.83 02-JAN-20:10 0.360126E+11 16179.04 01-JAN-07:10
February 0.102255E+10 1090.83 01-FEB-20:10 0.325275E+11 16179.04 01-FEB-07:10
March 0.113599E+10 1090.83 01-MAR-20:10 0.360126E+11 16179.04 01-MAR-07:10
April 0.109410E+10 1090.83 03-APR-19:10 0.348509E+11 16179.04 01-APR-06:10
May 0.113446E+10 1090.83 01-MAY-19:10 0.360126E+11 16179.04 01-MAY-06:10
June 0.109912E+10 1090.83 01-JUN-19:10 0.348509E+11 16179.04 01-JUN-06:10
July 0.112945E+10 1090.83 03-JUL-19:10 0.360126E+11 16179.04 01-JUL-06:10
August 0.113643E+10 1090.83 01-AUG-19:10 0.360126E+11 16179.04 01-AUG-06:10
September 0.109454E+10 1090.83 01-SEP-19:10 0.348509E+11 16179.04 01-SEP-06:10
October 0.113207E+10 1090.83 02-OCT-19:10 0.360126E+11 16179.04 01-OCT-06:10
November 0.109825E+10 1090.83 01-NOV-19:10 0.348509E+11 16179.04 01-NOV-06:10
December 0.112945E+10 1090.83 01-DEC-20:10 0.360126E+11 16179.04 01-DEC-07:10
             
Annual Sum or Average 0.133389E+11     0.424019E+12    
Minimum of Months 0.102255E+10 1090.83   0.325275E+11 16179.04  
Maximum of Months 0.113643E+10 1090.83   0.360126E+11 16179.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.127458E+10 1227.68 02-JAN-20:10 0.00 0.00
February 0.115083E+10 1227.68 01-FEB-20:10 0.00 0.00
March 0.127851E+10 1227.68 01-MAR-20:10 0.00 0.00
April 0.123137E+10 1227.68 03-APR-19:10 0.00 0.00
May 0.127679E+10 1227.68 01-MAY-19:10 0.00 0.00
June 0.123701E+10 1227.68 01-JUN-19:10 0.00 0.00
July 0.127114E+10 1227.68 03-JUL-19:10 0.00 0.00
August 0.127900E+10 1227.68 01-AUG-19:10 0.00 0.00
September 0.123186E+10 1227.68 01-SEP-19:10 0.00 0.00
October 0.127409E+10 1227.68 02-OCT-19:10 0.00 0.00
November 0.123603E+10 1227.68 01-NOV-19:10 0.00 0.00
December 0.127114E+10 1227.68 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.150123E+11     0.00 0.00
Minimum of Months 0.115083E+10 1227.68   0.00 0.00
Maximum of Months 0.127900E+10 1227.68   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.962539E+10 0.121516E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.869085E+10 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.965507E+10 0.121771E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.929905E+10 0.117446E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.964208E+10 0.121662E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.934170E+10 0.117829E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.959943E+10 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.965878E+10 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.930276E+10 0.117482E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.962169E+10 0.121479E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.933428E+10 0.117774E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.959943E+10 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.113371E+12 0.143105E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.869085E+10 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.965878E+10 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.531884E+09 0.864900E+09 0.00 0.00 0.00 0.00 0.00 0.172200E+09
February 0.179968E+10 0.480243E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 0.166090E+09
March 0.199990E+10 0.533523E+09 0.866718E+09 0.00 0.00 0.00 0.00 3.88 0.133409E+09
April 0.192973E+10 0.513850E+09 0.835931E+09 0.00 0.00 0.00 0.00 167133.29 84879702.47
May 0.199475E+10 0.532806E+09 0.865939E+09 0.00 0.00 0.00 0.00 1224826.67 47175183.49
June 0.193394E+10 0.516207E+09 0.838659E+09 0.00 0.00 0.00 0.00 6940429.42 12954148.43
July 0.199054E+10 0.530449E+09 0.863211E+09 0.00 0.00 0.00 0.00 17885709.50 1486110.60
August 0.199896E+10 0.533728E+09 0.866978E+09 0.00 0.00 0.00 0.00 17217655.45 5206128.52
September 0.192879E+10 0.514055E+09 0.836191E+09 0.00 0.00 0.00 0.00 2791004.57 23149785.89
October 0.199148E+10 0.531679E+09 0.864640E+09 0.00 0.00 0.00 0.00 40199.03 68530128.99
November 0.192552E+10 0.515797E+09 0.838269E+09 0.00 0.00 0.00 0.00 0.00 0.113749E+09
December 0.199054E+10 0.530449E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.00 0.150881E+09
                   
Annual Sum or Average 0.234744E+11 0.626467E+10 0.101856E+11 0.00 0.00 0.00 0.00 46266961.82 0.979711E+09
Minimum of Months 0.179968E+10 0.480243E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 1486110.60
Maximum of Months 0.199990E+10 0.533728E+09 0.866978E+09 0.00 0.00 0.00 0.00 17885709.50 0.172200E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.615923E+09 0.100156E+10 0.00 0.00 0.00 0.00 0.00 67448721.20
February 0.208403E+10 0.556123E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 65015289.40
March 0.231589E+10 0.617822E+09 0.100366E+10 0.00 0.00 0.00 0.00 219.31 53493135.46
April 0.223463E+10 0.595041E+09 0.968011E+09 0.00 0.00 0.00 0.00 104053.92 35406526.10
May 0.230993E+10 0.616991E+09 0.100276E+10 0.00 0.00 0.00 0.00 519995.23 21674752.99
June 0.223950E+10 0.597770E+09 0.971170E+09 0.00 0.00 0.00 0.00 2516250.88 7520898.96
July 0.230505E+10 0.614262E+09 0.999601E+09 0.00 0.00 0.00 0.00 6095822.32 1670383.58
August 0.231480E+10 0.618059E+09 0.100396E+10 0.00 0.00 0.00 0.00 6470211.90 3222071.63
September 0.223354E+10 0.595278E+09 0.968312E+09 0.00 0.00 0.00 0.00 1107330.26 11355250.73
October 0.230614E+10 0.615686E+09 0.100126E+10 0.00 0.00 0.00 0.00 44656.19 28911411.87
November 0.222975E+10 0.597295E+09 0.970719E+09 0.00 0.00 0.00 0.00 0.00 46109820.81
December 0.230505E+10 0.614262E+09 0.999601E+09 0.00 0.00 0.00 0.00 0.00 59685555.78
                   
Annual Sum or Average 0.271834E+11 0.725451E+10 0.117950E+11 0.00 0.00 0.00 0.00 16858540.01 0.401514E+09
Minimum of Months 0.208403E+10 0.556123E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 1670383.58
Maximum of Months 0.231589E+10 0.618059E+09 0.100396E+10 0.00 0.00 0.00 0.00 6470211.90 67448721.20



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.710312E+09 0.105898E+10 0.00 0.00 0.00 0.00 0.00 0.156048E+09
February 0.440737E+09 0.641347E+09 0.956227E+09 0.00 0.00 0.00 0.00 0.00 0.149930E+09
March 0.489771E+09 0.712502E+09 0.106120E+10 0.00 0.00 0.00 0.00 9131.02 0.119957E+09
April 0.472586E+09 0.686229E+09 0.102351E+10 0.00 0.00 0.00 0.00 375582.07 77887113.84
May 0.488511E+09 0.711544E+09 0.106025E+10 0.00 0.00 0.00 0.00 1325979.50 47489802.49
June 0.473617E+09 0.689376E+09 0.102685E+10 0.00 0.00 0.00 0.00 5913248.83 16600869.84
July 0.487480E+09 0.708397E+09 0.105691E+10 0.00 0.00 0.00 0.00 14004410.89 3610913.64
August 0.489542E+09 0.712775E+09 0.106152E+10 0.00 0.00 0.00 0.00 15238564.24 7168120.66
September 0.472357E+09 0.686503E+09 0.102382E+10 0.00 0.00 0.00 0.00 2739929.35 25030578.71
October 0.487709E+09 0.710039E+09 0.105866E+10 0.00 0.00 0.00 0.00 197413.13 63006680.55
November 0.471555E+09 0.688829E+09 0.102637E+10 0.00 0.00 0.00 0.00 0.00 0.103786E+09
December 0.487480E+09 0.708397E+09 0.105691E+10 0.00 0.00 0.00 0.00 0.00 0.136155E+09
                   
Annual Sum or Average 0.574883E+10 0.836625E+10 0.124712E+11 0.00 0.00 0.00 0.00 39804259.03 0.906670E+09
Minimum of Months 0.440737E+09 0.641347E+09 0.956227E+09 0.00 0.00 0.00 0.00 0.00 3610913.64
Maximum of Months 0.489771E+09 0.712775E+09 0.106152E+10 0.00 0.00 0.00 0.00 15238564.24 0.156048E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.158446E+09 0.305485E+09 0.00 0.00 0.00 0.00 0.00 89962603.10
February 0.339028E+09 0.143062E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 86446253.64
March 0.376747E+09 0.158934E+09 0.306128E+09 0.00 0.00 0.00 0.00 5012.83 68884180.44
April 0.363528E+09 0.153074E+09 0.295253E+09 0.00 0.00 0.00 0.00 216486.76 44397246.04
May 0.375778E+09 0.158720E+09 0.305852E+09 0.00 0.00 0.00 0.00 776903.38 26707222.26
June 0.364321E+09 0.153776E+09 0.296217E+09 0.00 0.00 0.00 0.00 3508382.89 9069852.97
July 0.374985E+09 0.158018E+09 0.304889E+09 0.00 0.00 0.00 0.00 8327859.59 1854879.88
August 0.376571E+09 0.158995E+09 0.306219E+09 0.00 0.00 0.00 0.00 8985761.61 3867130.22
September 0.363352E+09 0.153135E+09 0.295345E+09 0.00 0.00 0.00 0.00 1652919.89 13851386.46
October 0.375161E+09 0.158385E+09 0.305393E+09 0.00 0.00 0.00 0.00 115522.13 35614044.10
November 0.362735E+09 0.153654E+09 0.296079E+09 0.00 0.00 0.00 0.00 0.00 59390016.31
December 0.374985E+09 0.158018E+09 0.304889E+09 0.00 0.00 0.00 0.00 0.00 78431495.04
                   
Annual Sum or Average 0.442217E+10 0.186622E+10 0.359760E+10 0.00 0.00 0.00 0.00 23588849.08 0.518476E+09
Minimum of Months 0.339028E+09 0.143062E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 1854879.88
Maximum of Months 0.376747E+09 0.158995E+09 0.306219E+09 0.00 0.00 0.00 0.00 8985761.61 89962603.10



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.415991E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 0.00 0.230386E+09
February 0.139600E+10 0.375602E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 0.220455E+09
March 0.155131E+10 0.417273E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 2178.89 0.180579E+09
April 0.149688E+10 0.401887E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 408013.27 0.118691E+09
May 0.154732E+10 0.416712E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 1967278.41 70562955.07
June 0.150015E+10 0.403730E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 10163185.63 21202490.51
July 0.154405E+10 0.414869E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 25135226.61 3546393.38
August 0.155059E+10 0.417433E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 26517621.39 7731817.69
September 0.149615E+10 0.402047E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 5459213.11 33761018.94
October 0.154478E+10 0.415830E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 351610.57 90800004.98
November 0.149361E+10 0.403409E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 0.00 0.156008E+09
December 0.154405E+10 0.414869E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.00 0.203309E+09
                   
Annual Sum or Average 0.182090E+11 0.489965E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 70004327.87 0.133703E+10
Minimum of Months 0.139600E+10 0.375602E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 3546393.38
Maximum of Months 0.155131E+10 0.417433E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 26517621.39 0.230386E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.125984E+10 0.121771E+10 0.00 0.00 0.00 0.00 0.00 0.389793E+09
February 0.236489E+11 0.107756E+10 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.377424E+09
March 0.262800E+11 0.113069E+10 0.122027E+10 0.00 0.00 0.00 0.00 0.00 0.310443E+09
April 0.253579E+11 0.101172E+10 0.117692E+10 0.00 0.00 0.00 0.00 326760.04 0.203503E+09
May 0.262123E+11 0.950864E+09 0.121917E+10 0.00 0.00 0.00 0.00 2604439.15 0.122688E+09
June 0.254132E+11 0.886205E+09 0.118076E+10 0.00 0.00 0.00 0.00 14592313.07 40560789.05
July 0.261570E+11 0.920528E+09 0.121533E+10 0.00 0.00 0.00 0.00 36187750.95 8926387.78
August 0.262677E+11 0.100414E+10 0.122063E+10 0.00 0.00 0.00 0.00 36214468.93 17413129.45
September 0.253456E+11 0.105796E+10 0.117729E+10 0.00 0.00 0.00 0.00 5797481.65 64777180.90
October 0.261693E+11 0.117843E+10 0.121734E+10 0.00 0.00 0.00 0.00 97517.34 0.169530E+09
November 0.253025E+11 0.118316E+10 0.118021E+10 0.00 0.00 0.00 0.00 0.00 0.266454E+09
December 0.261570E+11 0.124968E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.00 0.345313E+09
                   
Annual Sum or Average 0.308468E+12 0.129108E+11 0.143405E+11 0.00 0.00 0.00 0.00 95820731.13 0.231682E+10
Minimum of Months 0.236489E+11 0.886205E+09 0.109956E+10 0.00 0.00 0.00 0.00 0.00 8926387.78
Maximum of Months 0.262800E+11 0.125984E+10 0.122063E+10 0.00 0.00 0.00 0.00 36214468.93 0.389793E+09



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.106226E+11 0.126520E+11 0.00 0.00 0.00 0.00 0.00 0.113436E+10
February 0.702046E+11 0.951406E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.109290E+10
March 0.780153E+11 0.104990E+11 0.126786E+11 0.00 0.00 0.00 0.00 0.00 0.904321E+09
April 0.752779E+11 0.100313E+11 0.122282E+11 0.00 0.00 0.00 0.00 1403884.70 0.601734E+09
May 0.778146E+11 0.102854E+11 0.126672E+11 0.00 0.00 0.00 0.00 7964623.79 0.372304E+09
June 0.754422E+11 0.993134E+10 0.122682E+11 0.00 0.00 0.00 0.00 40690902.98 0.129019E+09
July 0.776503E+11 0.102193E+11 0.126273E+11 0.00 0.00 0.00 0.00 99906354.08 29896119.73
August 0.779788E+11 0.103580E+11 0.126824E+11 0.00 0.00 0.00 0.00 0.105608E+09 54110480.10
September 0.752414E+11 0.100828E+11 0.122320E+11 0.00 0.00 0.00 0.00 17291582.01 0.196112E+09
October 0.776868E+11 0.105112E+11 0.126482E+11 0.00 0.00 0.00 0.00 470688.42 0.492292E+09
November 0.751137E+11 0.102462E+11 0.122624E+11 0.00 0.00 0.00 0.00 0.00 0.784342E+09
December 0.776503E+11 0.105808E+11 0.126273E+11 0.00 0.00 0.00 0.00 0.00 0.100855E+10
                   
Annual Sum or Average 0.915726E+12 0.122882E+12 0.148998E+12 0.00 0.00 0.00 0.00 0.273336E+09 0.679993E+10
Minimum of Months 0.702046E+11 0.951406E+10 0.114244E+11 0.00 0.00 0.00 0.00 0.00 29896119.73
Maximum of Months 0.780153E+11 0.106226E+11 0.126824E+11 0.00 0.00 0.00 0.00 0.105608E+09 0.113436E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.131236E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 98630623.32
February 0.273974E+09 0.118519E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 95392249.92
March 0.303685E+09 0.130193E+09 0.260708E+09 0.00 0.00 0.00 0.00 4330.06 77126323.24
April 0.293479E+09 0.127154E+09 0.252705E+09 0.00 0.00 0.00 0.00 181474.79 49303895.69
May 0.303504E+09 0.130715E+09 0.260888E+09 0.00 0.00 0.00 0.00 945841.29 27650104.94
June 0.293842E+09 0.126145E+09 0.252344E+09 0.00 0.00 0.00 0.00 5621339.81 6102808.46
July 0.303141E+09 0.131741E+09 0.261248E+09 0.00 0.00 0.00 0.00 15076799.15 320527.60
August 0.303685E+09 0.130193E+09 0.260708E+09 0.00 0.00 0.00 0.00 15185702.50 1725938.45
September 0.293479E+09 0.127188E+09 0.252705E+09 0.00 0.00 0.00 0.00 3239449.03 11534597.56
October 0.303322E+09 0.131219E+09 0.261068E+09 0.00 0.00 0.00 0.00 118849.05 36834876.47
November 0.293661E+09 0.126649E+09 0.252524E+09 0.00 0.00 0.00 0.00 0.00 65501749.72
December 0.303141E+09 0.131758E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 86443325.12
                   
Annual Sum or Average 0.357224E+10 0.154271E+10 0.307301E+10 0.00 0.00 0.00 0.00 40373785.68 0.556567E+09
Minimum of Months 0.273974E+09 0.118519E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 320527.60
Maximum of Months 0.303685E+09 0.131758E+09 0.261248E+09 0.00 0.00 0.00 0.00 15185702.50 98630623.32



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.131221E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 97630381.28
February 0.273974E+09 0.118505E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 94141319.05
March 0.303685E+09 0.130178E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.00 76138878.90
April 0.293479E+09 0.127139E+09 0.252675E+09 0.00 0.00 0.00 0.00 159376.18 49420017.80
May 0.303504E+09 0.130699E+09 0.260857E+09 0.00 0.00 0.00 0.00 776923.07 29708072.49
June 0.293842E+09 0.126130E+09 0.252315E+09 0.00 0.00 0.00 0.00 4918374.94 9725678.70
July 0.303141E+09 0.131725E+09 0.261218E+09 0.00 0.00 0.00 0.00 13918659.08 1278163.14
August 0.303685E+09 0.130178E+09 0.260677E+09 0.00 0.00 0.00 0.00 14538007.21 2901740.40
September 0.293479E+09 0.127173E+09 0.252675E+09 0.00 0.00 0.00 0.00 2633315.38 13851870.71
October 0.303322E+09 0.131204E+09 0.261038E+09 0.00 0.00 0.00 0.00 63407.41 37691938.65
November 0.293661E+09 0.126635E+09 0.252495E+09 0.00 0.00 0.00 0.00 0.00 64470224.76
December 0.303141E+09 0.131742E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 85201427.79
                   
Annual Sum or Average 0.357224E+10 0.154253E+10 0.307265E+10 0.00 0.00 0.00 0.00 37008063.27 0.562160E+09
Minimum of Months 0.273974E+09 0.118505E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 1278163.14
Maximum of Months 0.303685E+09 0.131742E+09 0.261218E+09 0.00 0.00 0.00 0.00 14538007.21 97630381.28



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 82476868.03 0.255708E+09 0.00 0.00 0.00 0.00 0.00 27419157.20
February 0.00 74484663.28 0.230956E+09 0.00 0.00 0.00 0.00 0.00 30887540.52
March 0.00 81821381.83 0.255355E+09 0.00 0.00 0.00 0.00 0.00 27418480.95
April 0.00 79911301.67 0.247516E+09 0.00 0.00 0.00 0.00 0.00 19719312.79
May 0.00 82149124.93 0.255532E+09 0.00 0.00 0.00 0.00 31239.83 14007722.37
June 0.00 79277307.08 0.247163E+09 0.00 0.00 0.00 0.00 275483.70 6548528.61
July 0.00 82793865.32 0.255885E+09 0.00 0.00 0.00 0.00 644442.69 2797319.42
August 0.00 81821381.83 0.255355E+09 0.00 0.00 0.00 0.00 872440.39 3385391.69
September 0.00 79932793.28 0.247516E+09 0.00 0.00 0.00 0.00 68293.26 8616530.13
October 0.00 82466122.22 0.255708E+09 0.00 0.00 0.00 0.00 0.00 16870881.79
November 0.00 79594304.38 0.247340E+09 0.00 0.00 0.00 0.00 0.00 24111609.55
December 0.00 82804611.13 0.255885E+09 0.00 0.00 0.00 0.00 0.00 28464951.53
                   
Annual Sum or Average 0.00 0.969534E+09 0.300992E+10 0.00 0.00 0.00 0.00 1891899.87 0.210247E+09
Minimum of Months 0.00 74484663.28 0.230956E+09 0.00 0.00 0.00 0.00 0.00 2797319.42
Maximum of Months 0.00 82804611.13 0.255885E+09 0.00 0.00 0.00 0.00 872440.39 30887540.52



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 82499421.18 0.255778E+09 0.00 0.00 0.00 0.00 0.00 27671461.16
February 0.273974E+09 74505030.97 0.231020E+09 0.00 0.00 0.00 0.00 0.00 26580175.82
March 0.303685E+09 81843755.73 0.255425E+09 0.00 0.00 0.00 0.00 110.38 21442433.34
April 0.293479E+09 79933153.27 0.247584E+09 0.00 0.00 0.00 0.00 50356.63 13790443.19
May 0.303504E+09 82171588.45 0.255602E+09 0.00 0.00 0.00 0.00 223397.94 7997203.22
June 0.293842E+09 79298985.31 0.247231E+09 0.00 0.00 0.00 0.00 1390885.81 2258690.36
July 0.303141E+09 82816505.16 0.255955E+09 0.00 0.00 0.00 0.00 3928434.48 254254.68
August 0.303685E+09 81843755.73 0.255425E+09 0.00 0.00 0.00 0.00 4110103.12 682317.41
September 0.293479E+09 79954650.76 0.247584E+09 0.00 0.00 0.00 0.00 759323.81 3597498.18
October 0.303322E+09 82488672.43 0.255778E+09 0.00 0.00 0.00 0.00 25197.75 10251679.59
November 0.293661E+09 79616069.29 0.247408E+09 0.00 0.00 0.00 0.00 0.00 18297540.70
December 0.303141E+09 82827253.90 0.255955E+09 0.00 0.00 0.00 0.00 0.00 24198507.65
                   
Annual Sum or Average 0.357224E+10 0.969799E+09 0.301074E+10 0.00 0.00 0.00 0.00 10487809.92 0.157022E+09
Minimum of Months 0.273974E+09 74505030.97 0.231020E+09 0.00 0.00 0.00 0.00 0.00 254254.68
Maximum of Months 0.303685E+09 82827253.90 0.255955E+09 0.00 0.00 0.00 0.00 4110103.12 27671461.16



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.131236E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 98625022.81
February 0.273974E+09 0.118519E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 95516941.66
March 0.303685E+09 0.130193E+09 0.260708E+09 0.00 0.00 0.00 0.00 4337.19 77384538.70
April 0.293479E+09 0.127154E+09 0.252705E+09 0.00 0.00 0.00 0.00 181867.98 49563247.19
May 0.303504E+09 0.130715E+09 0.260888E+09 0.00 0.00 0.00 0.00 942459.09 27772009.20
June 0.293842E+09 0.126145E+09 0.252344E+09 0.00 0.00 0.00 0.00 5610520.79 6135266.98
July 0.303141E+09 0.131741E+09 0.261248E+09 0.00 0.00 0.00 0.00 15055023.19 324631.27
August 0.303685E+09 0.130193E+09 0.260708E+09 0.00 0.00 0.00 0.00 15178326.43 1754551.54
September 0.293479E+09 0.127188E+09 0.252705E+09 0.00 0.00 0.00 0.00 3239299.99 11605242.60
October 0.303322E+09 0.131219E+09 0.261068E+09 0.00 0.00 0.00 0.00 120209.28 36972615.98
November 0.293661E+09 0.126649E+09 0.252524E+09 0.00 0.00 0.00 0.00 0.00 65687157.69
December 0.303141E+09 0.131758E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 86466760.99
                   
Annual Sum or Average 0.357224E+10 0.154271E+10 0.307301E+10 0.00 0.00 0.00 0.00 40332043.95 0.557808E+09
Minimum of Months 0.273974E+09 0.118519E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 324631.27
Maximum of Months 0.303685E+09 0.131758E+09 0.261248E+09 0.00 0.00 0.00 0.00 15178326.43 98625022.81



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.131221E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 97601296.79
February 0.273974E+09 0.118505E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 94163405.83
March 0.303685E+09 0.130178E+09 0.260677E+09 0.00 0.00 0.00 0.00 759.64 76289613.19
April 0.293479E+09 0.127139E+09 0.252675E+09 0.00 0.00 0.00 0.00 155093.28 49585594.05
May 0.303504E+09 0.130699E+09 0.260857E+09 0.00 0.00 0.00 0.00 757047.17 29542279.08
June 0.293842E+09 0.126130E+09 0.252315E+09 0.00 0.00 0.00 0.00 4890679.69 9180866.20
July 0.303141E+09 0.131725E+09 0.261218E+09 0.00 0.00 0.00 0.00 13852493.62 1450020.86
August 0.303685E+09 0.130178E+09 0.260677E+09 0.00 0.00 0.00 0.00 14467229.73 3228505.61
September 0.293479E+09 0.127173E+09 0.252675E+09 0.00 0.00 0.00 0.00 2614482.46 13810444.79
October 0.303322E+09 0.131204E+09 0.261038E+09 0.00 0.00 0.00 0.00 61908.07 37556087.61
November 0.293661E+09 0.126635E+09 0.252495E+09 0.00 0.00 0.00 0.00 0.00 64636562.61
December 0.303141E+09 0.131742E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 85171791.14
                   
Annual Sum or Average 0.357224E+10 0.154253E+10 0.307265E+10 0.00 0.00 0.00 0.00 36799693.67 0.562216E+09
Minimum of Months 0.273974E+09 0.118505E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 1450020.86
Maximum of Months 0.303685E+09 0.131742E+09 0.261218E+09 0.00 0.00 0.00 0.00 14467229.73 97601296.79



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.120431E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.120226E+09
February 0.348285E+10 0.108739E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.115521E+09
March 0.387034E+10 0.120803E+10 0.00 0.00 0.00 0.00 0.00 3481.16 92356625.60
April 0.373454E+10 0.116348E+10 0.00 0.00 0.00 0.00 0.00 252752.68 60035694.21
May 0.386038E+10 0.120640E+10 0.00 0.00 0.00 0.00 0.00 925610.74 36354592.20
June 0.374269E+10 0.116882E+10 0.00 0.00 0.00 0.00 0.00 4403321.15 12857133.38
July 0.385223E+10 0.120107E+10 0.00 0.00 0.00 0.00 0.00 10807779.95 2600719.28
August 0.386853E+10 0.120849E+10 0.00 0.00 0.00 0.00 0.00 11362163.68 5498386.32
September 0.373273E+10 0.116395E+10 0.00 0.00 0.00 0.00 0.00 1869713.89 19115455.79
October 0.385404E+10 0.120385E+10 0.00 0.00 0.00 0.00 0.00 106672.84 48845101.61
November 0.372639E+10 0.116789E+10 0.00 0.00 0.00 0.00 0.00 0.00 79340471.32
December 0.385223E+10 0.120107E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.104860E+09
                   
Annual Sum or Average 0.454292E+11 0.141847E+11 0.00 0.00 0.00 0.00 0.00 29731496.09 0.697612E+09
Minimum of Months 0.348285E+10 0.108739E+10 0.00 0.00 0.00 0.00 0.00 0.00 2600719.28
Maximum of Months 0.387034E+10 0.120849E+10 0.00 0.00 0.00 0.00 0.00 11362163.68 0.120226E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.131236E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 98398267.36
February 0.273974E+09 0.118519E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 95178908.79
March 0.303685E+09 0.130193E+09 0.260708E+09 0.00 0.00 0.00 0.00 3840.16 77022790.31
April 0.293479E+09 0.127154E+09 0.252705E+09 0.00 0.00 0.00 0.00 175344.96 49356252.87
May 0.303504E+09 0.130715E+09 0.260888E+09 0.00 0.00 0.00 0.00 921561.98 27842173.54
June 0.293842E+09 0.126145E+09 0.252344E+09 0.00 0.00 0.00 0.00 5501523.84 6226708.42
July 0.303141E+09 0.131741E+09 0.261248E+09 0.00 0.00 0.00 0.00 14824051.73 337965.92
August 0.303685E+09 0.130193E+09 0.260708E+09 0.00 0.00 0.00 0.00 14962519.95 1767971.44
September 0.293479E+09 0.127188E+09 0.252705E+09 0.00 0.00 0.00 0.00 3147864.09 11650983.59
October 0.303322E+09 0.131219E+09 0.261068E+09 0.00 0.00 0.00 0.00 111142.59 36936375.30
November 0.293661E+09 0.126649E+09 0.252524E+09 0.00 0.00 0.00 0.00 0.00 65289641.61
December 0.303141E+09 0.131758E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 86186711.55
                   
Annual Sum or Average 0.357224E+10 0.154271E+10 0.307301E+10 0.00 0.00 0.00 0.00 39647849.32 0.556195E+09
Minimum of Months 0.273974E+09 0.118519E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 337965.92
Maximum of Months 0.303685E+09 0.131758E+09 0.261248E+09 0.00 0.00 0.00 0.00 14962519.95 98398267.36



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.131221E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 97514840.34
February 0.273974E+09 0.118505E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 94044272.32
March 0.303685E+09 0.130178E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.00 75992202.71
April 0.293479E+09 0.127139E+09 0.252675E+09 0.00 0.00 0.00 0.00 152481.62 49546466.92
May 0.303504E+09 0.130699E+09 0.260857E+09 0.00 0.00 0.00 0.00 758217.47 30193401.47
June 0.293842E+09 0.126130E+09 0.252315E+09 0.00 0.00 0.00 0.00 4825975.97 10195352.86
July 0.303141E+09 0.131725E+09 0.261218E+09 0.00 0.00 0.00 0.00 13705070.27 1343653.48
August 0.303685E+09 0.130178E+09 0.260677E+09 0.00 0.00 0.00 0.00 14343469.97 2906940.64
September 0.293479E+09 0.127173E+09 0.252675E+09 0.00 0.00 0.00 0.00 2567001.03 14070026.39
October 0.303322E+09 0.131204E+09 0.261038E+09 0.00 0.00 0.00 0.00 59391.18 37731977.45
November 0.293661E+09 0.126635E+09 0.252495E+09 0.00 0.00 0.00 0.00 0.00 64216856.11
December 0.303141E+09 0.131742E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 84987859.42
                   
Annual Sum or Average 0.357224E+10 0.154253E+10 0.307265E+10 0.00 0.00 0.00 0.00 36411607.50 0.562744E+09
Minimum of Months 0.273974E+09 0.118505E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 1343653.48
Maximum of Months 0.303685E+09 0.131742E+09 0.261218E+09 0.00 0.00 0.00 0.00 14343469.97 97514840.34



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 82499421.18 0.255778E+09 0.00 0.00 0.00 0.00 0.00 51370536.77
February 0.273974E+09 74505030.97 0.231020E+09 0.00 0.00 0.00 0.00 0.00 49724319.02
March 0.303685E+09 81843755.73 0.255425E+09 0.00 0.00 0.00 0.00 1967.47 40005231.31
April 0.293479E+09 79933153.27 0.247584E+09 0.00 0.00 0.00 0.00 89639.62 25532187.14
May 0.303504E+09 82171588.45 0.255602E+09 0.00 0.00 0.00 0.00 473361.83 14279947.15
June 0.293842E+09 79298985.31 0.247231E+09 0.00 0.00 0.00 0.00 2821379.55 3164530.47
July 0.303141E+09 82816505.16 0.255955E+09 0.00 0.00 0.00 0.00 7592221.84 173160.65
August 0.303685E+09 81843755.73 0.255425E+09 0.00 0.00 0.00 0.00 7664765.04 906560.93
September 0.293479E+09 79954650.76 0.247584E+09 0.00 0.00 0.00 0.00 1610175.51 6009138.83
October 0.303322E+09 82488672.43 0.255778E+09 0.00 0.00 0.00 0.00 53748.10 19103402.28
November 0.293661E+09 79616069.29 0.247408E+09 0.00 0.00 0.00 0.00 0.00 34333847.56
December 0.303141E+09 82827253.90 0.255955E+09 0.00 0.00 0.00 0.00 0.00 45127656.43
                   
Annual Sum or Average 0.357224E+10 0.969799E+09 0.301074E+10 0.00 0.00 0.00 0.00 20307258.97 0.289731E+09
Minimum of Months 0.273974E+09 74505030.97 0.231020E+09 0.00 0.00 0.00 0.00 0.00 173160.65
Maximum of Months 0.303685E+09 82827253.90 0.255955E+09 0.00 0.00 0.00 0.00 7664765.04 51370536.77



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.257787E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.269239E+09
February 0.415303E+11 0.226874E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.257060E+09
March 0.461508E+11 0.244509E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.215235E+09
April 0.445315E+11 0.227067E+10 0.144540E+11 0.00 0.00 0.00 0.00 220398.59 0.145864E+09
May 0.460320E+11 0.224791E+10 0.149358E+11 0.00 0.00 0.00 0.00 1198959.01 92177503.25
June 0.446286E+11 0.214222E+10 0.144540E+11 0.00 0.00 0.00 0.00 7000232.17 32718450.52
July 0.459349E+11 0.221387E+10 0.149358E+11 0.00 0.00 0.00 0.00 18257622.37 7602355.54
August 0.461292E+11 0.230551E+10 0.149358E+11 0.00 0.00 0.00 0.00 20809050.72 13080584.06
September 0.445099E+11 0.232023E+10 0.144540E+11 0.00 0.00 0.00 0.00 3073842.10 47804184.17
October 0.459565E+11 0.248267E+10 0.149358E+11 0.00 0.00 0.00 0.00 91560.77 0.114489E+09
November 0.444343E+11 0.245588E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.186279E+09
December 0.459349E+11 0.258248E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.239314E+09
                   
Annual Sum or Average 0.541708E+12 0.283131E+11 0.175857E+12 0.00 0.00 0.00 0.00 50651665.72 0.162086E+10
Minimum of Months 0.415303E+11 0.214222E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 7602355.54
Maximum of Months 0.461508E+11 0.258248E+10 0.149358E+11 0.00 0.00 0.00 0.00 20809050.72 0.269239E+09



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.257787E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.272278E+09
February 0.415303E+11 0.226874E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.259797E+09
March 0.461508E+11 0.244509E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.217523E+09
April 0.445315E+11 0.227067E+10 0.144540E+11 0.00 0.00 0.00 0.00 194057.99 0.147559E+09
May 0.460320E+11 0.224791E+10 0.149358E+11 0.00 0.00 0.00 0.00 1162467.09 93128060.59
June 0.446286E+11 0.214222E+10 0.144540E+11 0.00 0.00 0.00 0.00 6874736.75 32980546.67
July 0.459349E+11 0.221387E+10 0.149358E+11 0.00 0.00 0.00 0.00 18068260.35 7631194.71
August 0.461292E+11 0.230551E+10 0.149358E+11 0.00 0.00 0.00 0.00 20582027.78 13133329.65
September 0.445099E+11 0.232023E+10 0.144540E+11 0.00 0.00 0.00 0.00 2969038.70 48335890.81
October 0.459565E+11 0.248267E+10 0.149358E+11 0.00 0.00 0.00 0.00 68103.50 0.115786E+09
November 0.444343E+11 0.245588E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.188487E+09
December 0.459349E+11 0.258248E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.241928E+09
                   
Annual Sum or Average 0.541708E+12 0.283131E+11 0.175857E+12 0.00 0.00 0.00 0.00 49918692.17 0.163857E+10
Minimum of Months 0.415303E+11 0.214222E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 7631194.71
Maximum of Months 0.461508E+11 0.258248E+10 0.149358E+11 0.00 0.00 0.00 0.00 20582027.78 0.272278E+09



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.113250E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.245797E+09
February 0.369574E+10 0.102255E+10 0.293798E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.234365E+09
March 0.410691E+10 0.113599E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.194915E+09
April 0.396281E+10 0.109410E+10 0.314783E+11 0.295556E+11 0.00 0.00 0.00 150505.68 0.131387E+09
May 0.409635E+10 0.113446E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 992621.90 82184815.29
June 0.397146E+10 0.109912E+10 0.314783E+11 0.295556E+11 0.00 0.00 0.00 6005752.26 28585408.78
July 0.408770E+10 0.112945E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 16225661.07 6103031.16
August 0.410499E+10 0.113643E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 18251229.90 11064990.09
September 0.396089E+10 0.109454E+10 0.314783E+11 0.295556E+11 0.00 0.00 0.00 2524447.87 42374081.68
October 0.408962E+10 0.113207E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 27284.98 0.102991E+09
November 0.395417E+10 0.109825E+10 0.314783E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.169111E+09
December 0.408770E+10 0.112945E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.217875E+09
                   
Annual Sum or Average 0.482060E+11 0.133389E+11 0.382987E+12 0.359593E+12 0.00 0.00 0.00 44177503.66 0.146675E+10
Minimum of Months 0.369574E+10 0.102255E+10 0.293798E+11 0.275852E+11 0.00 0.00 0.00 0.00 6103031.16
Maximum of Months 0.410691E+10 0.113643E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 18251229.90 0.245797E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.127458E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.213435E+09
February 0.368610E+10 0.115083E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.205138E+09
March 0.409620E+10 0.127851E+10 0.00 0.00 0.00 0.00 0.00 1040.44 0.164352E+09
April 0.395248E+10 0.123137E+10 0.00 0.00 0.00 0.00 0.00 313620.25 0.106750E+09
May 0.408566E+10 0.127679E+10 0.00 0.00 0.00 0.00 0.00 1255251.88 64788897.72
June 0.396110E+10 0.123701E+10 0.00 0.00 0.00 0.00 0.00 6733567.47 22585068.72
July 0.407704E+10 0.127114E+10 0.00 0.00 0.00 0.00 0.00 17122097.48 4533543.79
August 0.409429E+10 0.127900E+10 0.00 0.00 0.00 0.00 0.00 18762318.89 9170360.98
September 0.395056E+10 0.123186E+10 0.00 0.00 0.00 0.00 0.00 2946278.83 32882142.93
October 0.407896E+10 0.127409E+10 0.00 0.00 0.00 0.00 0.00 117736.09 83895008.97
November 0.394385E+10 0.123603E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.140242E+09
December 0.407704E+10 0.127114E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.186262E+09
                   
Annual Sum or Average 0.480803E+11 0.150123E+11 0.00 0.00 0.00 0.00 0.00 47251911.33 0.123403E+10
Minimum of Months 0.368610E+10 0.115083E+10 0.00 0.00 0.00 0.00 0.00 0.00 4533543.79
Maximum of Months 0.409620E+10 0.127900E+10 0.00 0.00 0.00 0.00 0.00 18762318.89 0.213435E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 9271.23 02-JAN-20:10 9632.53 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 9271.23 01-FEB-20:10 9632.53 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 9271.23 01-MAR-20:10 9632.53 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 9271.23 03-APR-19:10 9632.53 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 9271.23 01-MAY-19:10 9632.53 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 9271.23 01-JUN-19:10 9632.53 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 9271.23 03-JUL-19:10 9632.53 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 9271.23 01-AUG-19:10 9632.53 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 9271.23 01-SEP-19:10 9632.53 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 9271.23 02-OCT-19:10 9632.53 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 9271.23 01-NOV-19:10 9632.53 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 9271.23 01-DEC-20:10 9632.53 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   9271.23   9632.53   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   9271.23   9632.53   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 512.31 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 113.12 02-JAN-05:00
February 1169.53 01-FEB-00:10 512.31 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 116.22 06-FEB-03:00
March 1169.53 01-MAR-00:10 512.31 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 0.01 27-MAR-16:00 85.80 23-MAR-06:00
April 1169.53 01-APR-00:10 512.31 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 8.90 08-APR-09:55 60.51 03-APR-06:00
May 1169.53 01-MAY-00:10 512.31 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 17.36 30-MAY-13:00 46.98 01-MAY-05:00
June 1169.53 01-JUN-00:10 512.31 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 35.73 19-JUN-12:00 24.75 03-JUN-03:00
July 1169.53 01-JUL-00:10 512.31 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 28.16 07-JUL-12:00 10.12 02-JUL-03:00
August 1169.53 01-AUG-00:10 512.31 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 27.97 24-AUG-15:00 20.17 08-AUG-05:00
September 1169.53 01-SEP-00:10 512.31 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 20.19 01-SEP-14:00 35.13 30-SEP-01:00
October 1169.53 01-OCT-23:10 512.31 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 3.02 25-OCT-11:40 60.87 09-OCT-06:00
November 1169.53 01-NOV-00:10 512.31 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 83.57 24-NOV-07:00
December 1169.53 01-DEC-00:10 512.31 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 97.32 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   512.31   685.60   0.00 0.00 0.00 0.00 0.00   10.12  
Maximum of Months 1169.53   512.31   685.60   0.00 0.00 0.00 0.00 35.73   116.22  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 593.26 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 43.67 02-JAN-05:00
February 1354.32 01-FEB-00:10 593.26 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 44.86 06-FEB-03:00
March 1354.32 01-MAR-00:10 593.26 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 0.29 27-MAR-15:55 34.25 23-MAR-06:00
April 1354.32 01-APR-00:10 593.26 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 4.71 07-APR-13:00 24.52 03-APR-06:00
May 1354.32 01-MAY-00:10 593.26 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 8.07 30-MAY-13:00 19.78 01-MAY-05:00
June 1354.32 01-JUN-00:10 593.26 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 14.95 19-JUN-12:00 11.91 03-JUN-03:00
July 1354.32 01-JUL-00:10 593.26 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 11.77 07-JUL-12:00 5.92 02-JUL-03:00
August 1354.32 01-AUG-00:10 593.26 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 11.34 24-AUG-15:00 10.11 08-AUG-05:00
September 1354.32 01-SEP-00:10 593.26 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 8.29 01-SEP-14:00 15.66 30-SEP-01:00
October 1354.32 01-OCT-23:10 593.26 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 2.46 25-OCT-10:55 25.44 09-OCT-06:00
November 1354.32 01-NOV-00:10 593.26 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 32.95 24-NOV-07:00
December 1354.32 01-DEC-00:10 593.26 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 38.16 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   593.26   793.93   0.00 0.00 0.00 0.00 0.00   5.92  
Maximum of Months 1354.32   593.26   793.93   0.00 0.00 0.00 0.00 14.95   44.86  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 684.18 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 103.20 02-JAN-05:00
February 286.42 01-FEB-00:10 684.18 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 106.03 06-FEB-03:00
March 286.42 01-MAR-00:10 684.18 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 3.24 27-MAR-15:55 78.28 23-MAR-06:00
April 286.42 01-APR-00:10 684.18 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 13.32 07-APR-13:00 55.20 03-APR-06:00
May 286.42 01-MAY-00:10 684.18 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 19.13 30-MAY-13:00 44.35 01-MAY-05:00
June 286.42 01-JUN-00:10 684.18 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 34.96 19-JUN-12:00 26.73 03-JUN-03:00
July 286.42 01-JUL-00:10 684.18 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 27.22 07-JUL-12:00 13.37 02-JUL-03:00
August 286.42 01-AUG-00:10 684.18 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 27.09 24-AUG-16:00 23.18 08-AUG-05:00
September 286.42 01-SEP-00:10 684.18 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 19.96 01-SEP-14:00 35.38 24-SEP-06:00
October 286.42 01-OCT-23:10 684.18 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 6.59 25-OCT-10:55 57.79 09-OCT-06:00
November 286.42 01-NOV-00:10 684.18 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 76.24 24-NOV-07:00
December 286.42 01-DEC-00:10 684.18 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 88.78 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   684.18   839.45   0.00 0.00 0.00 0.00 0.00   13.37  
Maximum of Months 286.42   684.18   839.45   0.00 0.00 0.00 0.00 34.96   106.03  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 152.61 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 59.54 02-JAN-05:00
February 220.32 01-FEB-00:10 152.61 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 61.17 06-FEB-03:00
March 220.32 01-MAR-00:10 152.61 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 1.82 27-MAR-15:55 45.16 23-MAR-06:00
April 220.32 01-APR-00:10 152.61 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 7.61 07-APR-13:00 31.85 03-APR-06:00
May 220.32 01-MAY-00:10 152.61 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 11.01 30-MAY-13:00 25.29 01-MAY-05:00
June 220.32 01-JUN-00:10 152.61 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 20.10 19-JUN-12:00 15.19 03-JUN-03:00
July 220.32 01-JUL-00:10 152.61 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 15.67 07-JUL-12:00 7.44 02-JUL-03:00
August 220.32 01-AUG-00:10 152.61 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 15.55 24-AUG-16:00 13.10 08-AUG-05:00
September 220.32 01-SEP-00:10 152.61 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 11.51 01-SEP-14:00 19.99 24-SEP-06:00
October 220.32 01-OCT-23:10 152.61 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 3.82 25-OCT-10:55 32.91 09-OCT-04:00
November 220.32 01-NOV-00:10 152.61 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 43.98 24-NOV-07:00
December 220.32 01-DEC-00:10 152.61 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 51.22 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   152.61   242.16   0.00 0.00 0.00 0.00 0.00   7.44  
Maximum of Months 220.32   152.61   242.16   0.00 0.00 0.00 0.00 20.10   61.17  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 400.68 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 0.00 01-JAN-00:03 150.43 02-JAN-07:10
February 907.20 01-FEB-00:10 400.68 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 0.00 01-FEB-00:03 153.67 06-FEB-07:10
March 907.20 01-MAR-00:10 400.68 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 1.65 27-MAR-16:00 118.01 23-MAR-06:00
April 907.20 01-APR-00:10 400.68 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 16.01 07-APR-13:00 86.54 03-APR-06:00
May 907.20 01-MAY-00:10 400.68 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 28.35 30-MAY-13:00 67.21 01-MAY-05:10
June 907.20 01-JUN-00:10 400.68 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 52.41 19-JUN-12:00 38.07 02-JUN-06:00
July 907.20 01-JUL-00:10 400.68 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 43.02 07-JUL-12:00 18.55 01-JUL-23:00
August 907.20 01-AUG-00:10 400.68 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 43.21 24-AUG-16:00 31.79 08-AUG-05:10
September 907.20 01-SEP-00:10 400.68 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 30.05 01-SEP-14:20 52.16 24-SEP-06:10
October 907.20 01-OCT-23:10 400.68 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 12.29 25-OCT-10:50 87.46 29-OCT-07:00
November 907.20 01-NOV-00:10 400.68 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 0.00 01-NOV-00:05 115.70 24-NOV-07:10
December 907.20 01-DEC-00:10 400.68 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 0.00 01-DEC-00:03 131.19 31-DEC-23:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   400.68   4572.80   39726.58   0.00 0.00 0.00 0.00   18.55  
Maximum of Months 907.20   400.68   4572.80   39726.58   0.00 0.00 0.00 52.41   153.67  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 1573.46 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 250.10 02-JAN-05:00
February 15368.40 01-FEB-00:10 1573.46 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 257.49 06-FEB-03:00
March 15368.40 01-MAR-00:10 1573.46 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 197.35 23-MAR-04:20
April 15368.40 01-APR-00:10 1573.46 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 17.68 08-APR-09:55 140.09 01-APR-04:00
May 15368.40 01-MAY-00:10 1573.46 01-MAY-19:10 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 40.13 30-MAY-13:00 114.41 01-MAY-05:00
June 15368.40 01-JUN-00:10 1573.46 01-JUN-19:19 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 82.06 19-JUN-10:55 68.63 03-JUN-03:00
July 15368.40 01-JUL-00:10 1573.46 03-JUL-19:30 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 64.19 07-JUL-10:55 31.60 02-JUL-03:00
August 15368.40 01-AUG-00:10 1573.46 01-AUG-19:10 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 61.83 24-AUG-15:40 58.30 08-AUG-05:00
September 15368.40 01-SEP-00:10 1573.46 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 44.63 01-SEP-14:00 90.91 30-SEP-01:00
October 15368.40 01-OCT-23:10 1573.46 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 7.89 25-OCT-11:40 143.00 29-OCT-07:00
November 15368.40 01-NOV-00:10 1573.46 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 190.89 24-NOV-06:00
December 15368.40 01-DEC-00:10 1573.46 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 217.09 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   1573.46   965.27   0.00 0.00 0.00 0.00 0.00   31.60  
Maximum of Months 15368.40   1573.46   965.27   0.00 0.00 0.00 0.00 82.06   257.49  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 10645.38 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 730.62 02-JAN-05:00
February 45622.98 01-FEB-00:10 10645.38 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 753.90 06-FEB-03:00
March 45622.98 01-MAR-00:10 10645.38 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 577.39 23-MAR-04:40
April 45622.98 01-APR-00:10 10645.38 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 67.43 07-APR-13:00 413.89 03-APR-06:00
May 45622.98 01-MAY-00:10 10645.38 01-MAY-19:10 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 128.85 30-MAY-13:00 339.88 01-MAY-05:00
June 45622.98 01-JUN-00:10 10645.38 01-JUN-19:19 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 244.24 19-JUN-12:00 204.07 03-JUN-03:00
July 45622.98 01-JUL-00:10 10645.38 03-JUL-19:30 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 193.69 07-JUL-12:00 101.91 02-JUL-03:00
August 45622.98 01-AUG-00:10 10645.38 01-AUG-19:10 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 184.18 24-AUG-15:00 173.66 08-AUG-05:00
September 45622.98 01-SEP-00:10 10645.38 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 133.29 01-SEP-14:00 263.27 30-SEP-01:00
October 45622.98 01-OCT-23:10 10645.38 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 33.91 25-OCT-10:55 426.21 09-OCT-06:00
November 45622.98 01-NOV-00:10 10645.38 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 559.14 24-NOV-06:00
December 45622.98 01-DEC-00:10 10645.38 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 639.86 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   10645.38   10029.21   0.00 0.00 0.00 0.00 0.00   101.91  
Maximum of Months 45622.98   10645.38   10029.21   0.00 0.00 0.00 0.00 244.24   753.90  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 118.74 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 65.96 02-JAN-05:00
February 180.00 01-FEB-00:10 118.74 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 67.75 06-FEB-03:00
March 180.00 01-MAR-00:10 118.74 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 1.79 27-MAR-16:00 50.09 23-MAR-06:00
April 180.00 01-APR-00:10 118.74 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 8.36 08-APR-09:55 35.40 03-APR-06:00
May 180.00 01-MAY-00:10 118.74 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 12.06 30-MAY-16:00 27.55 01-MAY-05:00
June 180.00 01-JUN-00:10 118.74 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 21.76 19-JUN-12:00 13.91 03-JUN-05:00
July 180.00 01-JUL-00:10 118.74 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 19.34 10-JUL-15:10 4.98 02-JUL-05:00
August 180.00 01-AUG-00:10 118.74 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 20.90 24-AUG-16:00 10.92 08-AUG-05:00
September 180.00 01-SEP-00:10 118.74 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 15.00 01-SEP-15:10 20.16 24-SEP-06:00
October 180.00 01-OCT-00:10 118.74 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 4.12 04-OCT-15:10 35.62 09-OCT-06:00
November 180.00 01-NOV-00:10 118.74 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 48.80 24-NOV-07:00
December 180.00 01-DEC-00:10 118.74 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 56.78 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   118.74   237.06   0.00 0.00 0.00 0.00 0.00   4.98  
Maximum of Months 180.00   118.74   237.06   0.00 0.00 0.00 0.00 21.76   67.75  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 118.73 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 65.96 02-JAN-05:00
February 180.00 01-FEB-00:10 118.73 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 67.75 06-FEB-03:00
March 180.00 01-MAR-00:10 118.73 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 50.09 23-MAR-06:00
April 180.00 01-APR-00:10 118.73 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 8.36 08-APR-09:55 35.40 03-APR-06:00
May 180.00 01-MAY-00:10 118.73 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 12.06 30-MAY-16:00 27.55 01-MAY-05:00
June 180.00 01-JUN-00:10 118.73 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 21.76 19-JUN-12:00 18.43 03-JUN-18:02
July 180.00 01-JUL-00:10 118.73 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 19.41 10-JUL-15:10 10.71 01-JUL-18:00
August 180.00 01-AUG-00:10 118.73 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 20.89 24-AUG-16:00 10.92 08-AUG-05:00
September 180.00 01-SEP-00:10 118.73 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 15.00 01-SEP-15:10 20.16 24-SEP-06:00
October 180.00 01-OCT-00:10 118.73 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 4.37 04-OCT-15:10 35.62 09-OCT-06:00
November 180.00 01-NOV-00:10 118.73 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 48.79 24-NOV-07:00
December 180.00 01-DEC-00:10 118.73 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 56.78 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   118.73   237.03   0.00 0.00 0.00 0.00 0.00   10.71  
Maximum of Months 180.00   118.73   237.03   0.00 0.00 0.00 0.00 21.76   67.75  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 74.62 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 17.20 31-JAN-07:20
February 0.00 01-FEB-00:10 74.62 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 19.35 05-FEB-24:00
March 0.00 01-MAR-00:10 74.62 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 15.93 23-MAR-06:00
April 0.00 01-APR-00:10 74.62 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 11.76 12-APR-06:10
May 0.00 01-MAY-00:10 74.62 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 1.54 30-MAY-13:00 9.96 01-MAY-05:10
June 0.00 01-JUN-00:10 74.62 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 4.55 19-JUN-12:00 6.63 03-JUN-03:00
July 0.00 01-JUL-00:10 74.62 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 3.31 07-JUL-12:00 4.09 02-JUL-05:00
August 0.00 01-AUG-00:10 74.62 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 3.29 24-AUG-15:00 5.79 08-AUG-05:00
September 0.00 01-SEP-00:10 74.62 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 2.02 01-SEP-14:00 8.22 24-SEP-06:00
October 0.00 01-OCT-00:10 74.62 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 12.74 29-OCT-07:00
November 0.00 01-NOV-00:10 74.62 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 15.42 24-NOV-08:00
December 0.00 01-DEC-00:10 74.62 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 16.13 22-DEC-07:20
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   74.62   232.19   0.00 0.00 0.00 0.00 0.00   4.09  
Maximum of Months 0.00   74.62   232.19   0.00 0.00 0.00 0.00 4.55   19.35  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 74.64 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 18.41 02-JAN-05:00
February 180.00 01-FEB-00:10 74.64 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 18.91 06-FEB-03:00
March 180.00 01-MAR-00:10 74.64 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 0.17 27-MAR-15:55 13.98 23-MAR-06:00
April 180.00 01-APR-00:10 74.64 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 2.33 08-APR-10:00 9.88 03-APR-06:00
May 180.00 01-MAY-00:10 74.64 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 3.37 30-MAY-16:00 7.69 01-MAY-05:00
June 180.00 01-JUN-00:10 74.64 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 6.07 19-JUN-12:00 3.96 02-JUN-21:20
July 180.00 01-JUL-00:10 74.64 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 5.43 10-JUL-15:10 2.23 01-JUL-21:50
August 180.00 01-AUG-00:10 74.64 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 5.83 24-AUG-15:10 3.05 08-AUG-05:00
September 180.00 01-SEP-00:10 74.64 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 4.19 01-SEP-15:10 5.63 24-SEP-06:00
October 180.00 01-OCT-00:10 74.64 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 1.22 04-OCT-15:10 9.94 09-OCT-06:00
November 180.00 01-NOV-00:10 74.64 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 13.62 24-NOV-07:00
December 180.00 01-DEC-00:10 74.64 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 15.85 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   74.64   232.26   0.00 0.00 0.00 0.00 0.00   2.23  
Maximum of Months 180.00   74.64   232.26   0.00 0.00 0.00 0.00 6.07   18.91  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 118.74 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 65.96 02-JAN-05:00
February 180.00 01-FEB-00:10 118.74 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 67.75 06-FEB-03:00
March 180.00 01-MAR-00:10 118.74 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 1.79 27-MAR-16:00 50.09 23-MAR-06:00
April 180.00 01-APR-00:10 118.74 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 8.36 08-APR-10:00 35.40 03-APR-06:00
May 180.00 01-MAY-00:10 118.74 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 12.06 30-MAY-16:00 27.55 01-MAY-05:00
June 180.00 01-JUN-00:10 118.74 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 21.76 19-JUN-12:00 15.24 02-JUN-07:10
July 180.00 01-JUL-00:10 118.74 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 19.45 10-JUL-15:10 4.97 02-JUL-05:00
August 180.00 01-AUG-00:10 118.74 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 20.90 24-AUG-15:10 10.92 08-AUG-05:00
September 180.00 01-SEP-00:10 118.74 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 15.00 01-SEP-15:10 20.16 24-SEP-06:00
October 180.00 01-OCT-00:10 118.74 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 4.37 04-OCT-15:10 35.62 09-OCT-06:00
November 180.00 01-NOV-00:10 118.74 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 48.80 24-NOV-07:00
December 180.00 01-DEC-00:10 118.74 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 56.78 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   118.74   237.06   0.00 0.00 0.00 0.00 0.00   4.97  
Maximum of Months 180.00   118.74   237.06   0.00 0.00 0.00 0.00 21.76   67.75  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 118.73 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 65.96 02-JAN-05:00
February 180.00 01-FEB-00:10 118.73 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 67.75 06-FEB-03:00
March 180.00 01-MAR-00:10 118.73 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.81 27-MAR-15:55 50.09 23-MAR-06:00
April 180.00 01-APR-00:10 118.73 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 8.36 08-APR-10:00 35.40 03-APR-06:00
May 180.00 01-MAY-00:10 118.73 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 12.06 30-MAY-15:50 27.55 01-MAY-05:00
June 180.00 01-JUN-00:10 118.73 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 21.76 19-JUN-12:00 17.34 02-JUN-08:50
July 180.00 01-JUL-00:10 118.73 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 19.45 10-JUL-15:10 8.92 11-JUL-08:00
August 180.00 01-AUG-00:10 118.73 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 20.90 24-AUG-15:10 12.67 25-AUG-07:50
September 180.00 01-SEP-00:10 118.73 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 15.00 01-SEP-15:10 20.16 24-SEP-06:00
October 180.00 01-OCT-00:10 118.73 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 4.37 04-OCT-15:10 35.62 09-OCT-06:00
November 180.00 01-NOV-00:10 118.73 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 48.79 24-NOV-07:00
December 180.00 01-DEC-00:10 118.73 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 56.78 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   118.73   237.03   0.00 0.00 0.00 0.00 0.00   8.92  
Maximum of Months 180.00   118.73   237.03   0.00 0.00 0.00 0.00 21.76   67.75  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 1160.00 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 79.50 02-JAN-05:00
February 2263.36 01-FEB-00:10 1160.00 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 81.67 06-FEB-03:00
March 2263.36 01-MAR-00:10 1160.00 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 1.75 27-MAR-15:55 60.32 23-MAR-06:00
April 2263.36 01-APR-00:10 1160.00 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 9.51 07-APR-13:00 42.56 03-APR-06:00
May 2263.36 01-MAY-00:10 1160.00 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 14.08 30-MAY-13:00 34.02 01-MAY-05:00
June 2263.36 01-JUN-00:10 1160.00 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 26.56 19-JUN-12:00 21.08 03-JUN-03:00
July 2263.36 01-JUL-00:10 1160.00 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 20.71 07-JUL-12:00 10.29 02-JUL-03:00
August 2263.36 01-AUG-00:10 1160.00 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 19.77 24-AUG-16:00 17.73 08-AUG-05:00
September 2263.36 01-SEP-00:10 1160.00 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 14.47 01-SEP-14:00 26.52 24-SEP-06:00
October 2263.36 01-OCT-23:10 1160.00 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 4.81 25-OCT-10:55 44.84 09-OCT-04:00
November 2263.36 01-NOV-00:10 1160.00 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 58.75 24-NOV-07:00
December 2263.36 01-DEC-00:10 1160.00 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 68.41 31-DEC-24:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   1160.00   0.00 0.00 0.00 0.00 0.00 0.00   10.29  
Maximum of Months 2263.36   1160.00   0.00 0.00 0.00 0.00 0.00 26.56   81.67  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 118.74 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 66.09 02-JAN-05:00
February 180.00 01-FEB-00:10 118.74 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 67.88 06-FEB-03:00
March 180.00 01-MAR-00:10 118.74 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 1.69 27-MAR-16:00 50.22 23-MAR-06:00
April 180.00 01-APR-00:10 118.74 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 8.26 08-APR-09:55 35.52 03-APR-06:00
May 180.00 01-MAY-00:10 118.74 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 11.96 30-MAY-16:00 27.67 01-MAY-05:00
June 180.00 01-JUN-00:10 118.74 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 21.67 19-JUN-12:00 14.02 03-JUN-03:00
July 180.00 01-JUL-00:10 118.74 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 19.34 10-JUL-15:10 5.08 02-JUL-05:00
August 180.00 01-AUG-00:10 118.74 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 20.80 24-AUG-16:00 11.02 08-AUG-05:00
September 180.00 01-SEP-00:10 118.74 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 14.90 01-SEP-15:10 20.27 24-SEP-06:00
October 180.00 01-OCT-00:10 118.74 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 3.85 04-OCT-15:10 35.74 09-OCT-06:00
November 180.00 01-NOV-00:10 118.74 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 48.92 24-NOV-07:00
December 180.00 01-DEC-00:10 118.74 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 56.91 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   118.74   237.06   0.00 0.00 0.00 0.00 0.00   5.08  
Maximum of Months 180.00   118.74   237.06   0.00 0.00 0.00 0.00 21.67   67.88  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 118.73 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 66.09 02-JAN-05:00
February 180.00 01-FEB-00:10 118.73 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 67.88 06-FEB-03:00
March 180.00 01-MAR-00:10 118.73 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 50.22 23-MAR-06:00
April 180.00 01-APR-00:10 118.73 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 8.26 08-APR-09:55 35.52 03-APR-06:00
May 180.00 01-MAY-00:10 118.73 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 11.95 30-MAY-16:00 27.66 01-MAY-05:00
June 180.00 01-JUN-00:10 118.73 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 21.67 19-JUN-12:00 19.89 03-JUN-18:02
July 180.00 01-JUL-00:10 118.73 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 19.24 10-JUL-15:10 11.73 01-JUL-18:00
August 180.00 01-AUG-00:10 118.73 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 20.80 24-AUG-16:00 11.02 08-AUG-05:00
September 180.00 01-SEP-00:10 118.73 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 14.90 01-SEP-15:10 20.27 24-SEP-06:00
October 180.00 01-OCT-00:10 118.73 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 4.26 04-OCT-15:10 35.74 09-OCT-06:00
November 180.00 01-NOV-00:10 118.73 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 48.92 24-NOV-07:00
December 180.00 01-DEC-00:10 118.73 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 56.90 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   118.73   237.03   0.00 0.00 0.00 0.00 0.00   11.02  
Maximum of Months 180.00   118.73   237.03   0.00 0.00 0.00 0.00 21.67   67.88  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 74.64 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 33.81 02-JAN-05:00
February 180.00 01-FEB-00:10 74.64 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 34.73 06-FEB-03:00
March 180.00 01-MAR-00:10 74.64 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 0.87 27-MAR-16:00 25.69 23-MAR-06:00
April 180.00 01-APR-00:10 74.64 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 4.23 08-APR-09:55 18.17 03-APR-06:00
May 180.00 01-MAY-00:10 74.64 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 6.12 30-MAY-16:00 14.15 01-MAY-05:00
June 180.00 01-JUN-00:10 74.64 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 11.09 19-JUN-12:00 7.17 03-JUN-03:10
July 180.00 01-JUL-00:10 74.64 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 9.90 10-JUL-15:10 2.60 02-JUL-05:00
August 180.00 01-AUG-00:10 74.64 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 10.64 24-AUG-16:00 5.64 08-AUG-05:00
September 180.00 01-SEP-00:10 74.64 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 7.62 01-SEP-15:10 10.37 24-SEP-06:00
October 180.00 01-OCT-00:10 74.64 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 1.82 02-OCT-16:00 18.29 09-OCT-06:00
November 180.00 01-NOV-00:10 74.64 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 25.03 24-NOV-07:00
December 180.00 01-DEC-00:10 74.64 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 29.12 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   74.64   232.26   0.00 0.00 0.00 0.00 0.00   2.60  
Maximum of Months 180.00   74.64   232.26   0.00 0.00 0.00 0.00 11.09   34.73  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 2763.12 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 171.75 02-JAN-05:00
February 26988.77 01-FEB-00:10 2763.12 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 176.10 06-FEB-03:00
March 26988.77 01-MAR-00:10 2763.12 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 135.23 23-MAR-04:30
April 26988.77 01-APR-00:10 2763.12 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 13.45 07-APR-13:00 99.90 03-APR-06:00
May 26988.77 01-MAY-00:10 2763.12 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 24.59 30-MAY-13:00 80.44 01-MAY-05:00
June 26988.77 01-JUN-00:10 2763.12 01-JUN-19:19 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 50.91 19-JUN-12:00 46.71 03-JUN-03:10
July 26988.77 01-JUL-00:10 2763.12 03-JUL-19:30 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 39.78 07-JUL-12:00 24.67 02-JUL-05:00
August 26988.77 01-AUG-00:10 2763.12 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 39.24 24-AUG-15:40 39.40 08-AUG-05:00
September 26988.77 01-SEP-00:10 2763.12 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 28.21 01-SEP-14:00 62.24 24-SEP-06:00
October 26988.77 01-OCT-23:10 2763.12 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 8.08 25-OCT-10:55 100.51 09-OCT-06:00
November 26988.77 01-NOV-00:10 2763.12 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 131.53 24-NOV-06:00
December 26988.77 01-DEC-00:10 2763.12 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 152.53 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   2763.12   6747.90   0.00 0.00 0.00 0.00 0.00   24.67  
Maximum of Months 26988.77   2763.12   6747.90   0.00 0.00 0.00 0.00 50.91   176.10  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 2763.12 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 172.75 02-JAN-05:00
February 26988.77 01-FEB-00:10 2763.12 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 177.12 06-FEB-03:00
March 26988.77 01-MAR-00:10 2763.12 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 135.98 23-MAR-04:30
April 26988.77 01-APR-00:10 2763.12 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 12.24 07-APR-13:00 99.90 03-APR-06:00
May 26988.77 01-MAY-00:10 2763.12 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 24.20 30-MAY-13:00 80.44 01-MAY-05:00
June 26988.77 01-JUN-00:10 2763.12 01-JUN-19:19 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 50.31 19-JUN-12:00 46.71 03-JUN-03:10
July 26988.77 01-JUL-00:10 2763.12 03-JUL-19:30 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 39.51 07-JUL-12:00 24.67 02-JUL-05:00
August 26988.77 01-AUG-00:10 2763.12 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 39.24 24-AUG-15:40 39.40 08-AUG-05:00
September 26988.77 01-SEP-00:10 2763.12 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 28.21 01-SEP-14:00 62.24 24-SEP-06:00
October 26988.77 01-OCT-23:10 2763.12 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 7.15 25-OCT-10:55 100.51 09-OCT-06:00
November 26988.77 01-NOV-00:10 2763.12 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 132.44 24-NOV-06:00
December 26988.77 01-DEC-00:10 2763.12 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 152.54 31-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   2763.12   6747.90   0.00 0.00 0.00 0.00 0.00   24.67  
Maximum of Months 26988.77   2763.12   6747.90   0.00 0.00 0.00 0.00 50.31   177.12  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 1090.83 02-JAN-20:10 14604.56 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 0.00 01-JAN-00:03 154.44 02-JAN-07:00
February 2401.70 01-FEB-00:10 1090.83 01-FEB-20:10 14604.56 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 0.00 01-FEB-00:03 157.51 05-FEB-24:00
March 2401.70 01-MAR-00:10 1090.83 01-MAR-20:10 14604.56 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 0.00 01-MAR-00:03 121.83 23-MAR-06:00
April 2401.70 01-APR-00:10 1090.83 03-APR-19:10 14604.56 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 9.59 07-APR-13:00 89.41 03-APR-06:00
May 2401.70 01-MAY-00:10 1090.83 01-MAY-19:10 14604.56 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 21.70 30-MAY-13:00 71.20 01-MAY-05:10
June 2401.70 01-JUN-00:10 1090.83 01-JUN-19:10 14604.56 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 45.03 19-JUN-12:00 41.07 03-JUN-05:10
July 2401.70 01-JUL-00:10 1090.83 03-JUL-19:10 14604.56 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 35.41 07-JUL-12:00 21.44 02-JUL-05:00
August 2401.70 01-AUG-00:10 1090.83 01-AUG-19:10 14604.56 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 35.17 24-AUG-15:50 35.28 08-AUG-05:00
September 2401.70 01-SEP-00:10 1090.83 01-SEP-19:10 14604.56 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 25.29 01-SEP-14:00 55.70 24-SEP-06:00
October 2401.70 01-OCT-23:10 1090.83 02-OCT-19:10 14604.56 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 3.36 04-OCT-13:00 89.96 09-OCT-06:00
November 2401.70 01-NOV-00:10 1090.83 01-NOV-19:10 14604.56 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 0.00 01-NOV-00:05 118.96 24-NOV-07:00
December 2401.70 01-DEC-00:10 1090.83 01-DEC-20:10 14604.56 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 0.00 01-DEC-00:03 136.55 31-DEC-24:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   1090.83   14604.56   22492.83   0.00 0.00 0.00 0.00   21.44  
Maximum of Months 2401.70   1090.83   14604.56   22492.83   0.00 0.00 0.00 45.03   157.51  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 1227.68 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 140.94 02-JAN-05:00
February 2395.44 01-FEB-00:10 1227.68 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 144.79 06-FEB-03:00
March 2395.44 01-MAR-00:10 1227.68 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 1.20 27-MAR-15:55 106.99 23-MAR-06:00
April 2395.44 01-APR-00:10 1227.68 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 13.47 07-APR-13:00 75.56 03-APR-06:00
May 2395.44 01-MAY-00:10 1227.68 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 21.39 30-MAY-13:00 58.76 01-MAY-05:00
June 2395.44 01-JUN-00:10 1227.68 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 44.03 19-JUN-12:00 35.82 03-JUN-03:00
July 2395.44 01-JUL-00:10 1227.68 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 34.62 07-JUL-12:00 16.94 02-JUL-03:00
August 2395.44 01-AUG-00:10 1227.68 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 34.38 24-AUG-15:00 29.80 08-AUG-05:00
September 2395.44 01-SEP-00:10 1227.68 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 24.71 01-SEP-14:00 45.64 30-SEP-01:00
October 2395.44 01-OCT-23:10 1227.68 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 7.33 25-OCT-10:55 76.02 09-OCT-06:00
November 2395.44 01-NOV-00:10 1227.68 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:05 104.21 24-NOV-07:00
December 2395.44 01-DEC-00:10 1227.68 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 121.30 31-DEC-24:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   1227.68   0.00 0.00 0.00 0.00 0.00 0.00   16.94  
Maximum of Months 2395.44   1227.68   0.00 0.00 0.00 0.00 0.00 44.03   144.79  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 12233.89 20-JAN-21:00 8945.92 9271.23 9632.53 0.00 0.00 0.00 0.00 0.00 0.00
February 12016.15 01-FEB-21:00 8945.92 9271.23 9632.53 0.00 0.00 0.00 0.00 0.00 0.00
March 11335.68 03-MAR-21:00 8945.92 9271.23 9632.53 0.00 0.00 0.00 0.00 0.00 0.00
April 11850.43 08-APR-10:33 11501.89 7726.12 10646.48 0.00 0.00 0.00 0.00 0.00 0.00
May 11967.36 29-MAY-10:33 11501.89 9271.10 12167.41 0.00 0.00 0.00 0.00 0.00 0.00
June 13800.67 22-JUN-18:03 53675.50 49446.67 54753.33 0.00 0.00 0.00 0.00 0.00 0.00
July 13920.50 11-JUL-17:09 51119.52 49446.94 56781.23 0.00 0.00 0.00 0.00 0.00 0.00
August 15495.76 24-AUG-19:30 26837.75 27813.70 28897.59 0.00 0.00 0.00 0.00 0.00 0.00
September 15276.08 22-SEP-21:00 10223.90 8241.11 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
October 17577.41 27-OCT-21:00 10223.90 8241.11 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
November 17229.19 03-NOV-21:00 10223.90 8241.11 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
December 15513.35 01-DEC-22:00 10223.90 8241.11 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11335.68   8945.92 7726.12 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17577.41   53675.50 49446.94 56781.23 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2422.95 17-JAN-13:10 259.90 142.31 252.59 0.00 0.00 0.00 0.00 0.00 42.92
February 2170.79 02-FEB-13:40 259.90 142.31 252.59 0.00 0.00 0.00 0.00 0.00 55.74
March 2978.21 03-MAR-13:20 259.90 142.31 252.59 0.00 0.00 0.00 0.00 0.00 28.67
April 3139.42 08-APR-12:30 389.84 142.31 252.59 0.00 0.00 0.00 0.00 0.00 1.18
May 2482.87 31-MAY-10:35 519.79 284.62 505.18 0.00 0.00 0.00 0.00 6.99 0.00
June 2707.41 19-JUN-13:20 259.90 142.31 252.59 0.00 0.00 0.00 0.00 30.57 0.00
July 2941.11 08-JUL-12:10 389.84 142.31 252.59 0.00 0.00 0.00 0.00 23.01 0.00
August 3616.68 22-AUG-12:40 259.90 142.31 252.59 0.00 0.00 0.00 0.00 18.36 0.00
September 3793.76 07-SEP-12:40 259.90 142.31 252.59 0.00 0.00 0.00 0.00 7.28 0.00
October 3981.32 04-OCT-12:10 259.90 142.31 252.59 0.00 0.00 0.00 0.00 1.46 0.00
November 3087.30 02-NOV-12:40 259.90 142.31 252.59 0.00 0.00 0.00 0.00 0.00 26.05
December 2948.09 17-DEC-12:50 389.84 170.77 288.68 0.00 0.00 0.00 0.00 0.00 35.84
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2170.79   259.90 142.31 252.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3981.32   519.79 284.62 505.18 0.00 0.00 0.00 0.00 30.57 55.74



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1170.78 19-JAN-21:00 1053.36 593.26 793.93 0.00 0.00 0.00 0.00 0.00 22.82
February 1162.53 02-FEB-21:00 1053.36 593.26 793.93 0.00 0.00 0.00 0.00 0.00 30.09
March 1286.70 03-MAR-21:00 1053.36 593.26 793.93 0.00 0.00 0.00 0.00 0.00 14.55
April 1446.35 07-APR-21:00 1203.84 527.34 752.15 0.00 0.00 0.00 0.00 0.00 5.29
May 1726.30 31-MAY-21:00 1203.84 527.34 752.15 0.00 0.00 0.00 0.00 0.00 3.92
June 1943.07 19-JUN-21:00 1203.84 527.34 752.15 0.00 0.00 0.00 0.00 5.47 0.00
July 1983.38 07-JUL-21:00 1203.84 527.34 752.15 0.00 0.00 0.00 0.00 1.81 0.00
August 2044.12 18-AUG-21:00 1203.84 527.34 752.15 0.00 0.00 0.00 0.00 1.13 0.00
September 1959.23 01-SEP-21:00 1203.84 527.34 752.15 0.00 0.00 0.00 0.00 3.01 0.00
October 1713.39 05-OCT-21:00 1203.84 527.34 752.15 0.00 0.00 0.00 0.00 0.00 5.87
November 1326.94 03-NOV-20:00 1053.36 593.26 793.93 0.00 0.00 0.00 0.00 0.00 12.67
December 1188.30 18-DEC-21:00 1053.36 593.26 793.93 0.00 0.00 0.00 0.00 0.00 24.49
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1162.53   1053.36 527.34 752.15 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2044.12   1203.84 593.26 793.93 0.00 0.00 0.00 0.00 5.47 30.09



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 829.36 19-JAN-21:00 222.77 684.18 839.45 0.00 0.00 0.00 0.00 0.00 50.29
February 811.32 24-FEB-21:00 222.77 684.18 839.45 0.00 0.00 0.00 0.00 0.00 58.64
March 923.00 28-MAR-10:33 190.94 570.15 927.81 0.00 0.00 0.00 0.00 0.00 25.50
April 1123.37 08-APR-10:33 286.42 570.15 927.81 0.00 0.00 0.00 0.00 4.92 0.00
May 1251.00 31-MAY-10:35 127.30 380.10 618.54 0.00 0.00 0.00 0.00 7.36 0.00
June 1404.95 20-JUN-21:00 254.59 608.16 795.27 0.00 0.00 0.00 0.00 0.00 7.87
July 1652.24 10-JUL-21:00 254.59 608.16 795.27 0.00 0.00 0.00 0.00 8.47 0.00
August 1705.12 18-AUG-20:00 222.77 684.18 839.45 0.00 0.00 0.00 0.00 5.58 0.00
September 1364.45 01-SEP-21:00 254.59 608.16 795.27 0.00 0.00 0.00 0.00 7.12 0.00
October 1166.11 05-OCT-10:33 190.94 570.15 927.81 0.00 0.00 0.00 0.00 0.00 4.08
November 1003.83 04-NOV-10:33 286.42 570.15 927.81 0.00 0.00 0.00 0.00 0.00 13.62
December 834.78 19-DEC-21:00 222.77 684.18 839.45 0.00 0.00 0.00 0.00 0.00 37.08
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 811.32   127.30 380.10 618.54 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1705.12   286.42 684.18 927.81 0.00 0.00 0.00 0.00 8.47 58.64



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 415.76 19-JAN-21:00 171.36 152.61 242.16 0.00 0.00 0.00 0.00 0.00 28.34
February 355.99 24-FEB-22:00 195.84 135.66 229.41 0.00 0.00 0.00 0.00 0.00 34.24
March 489.59 28-MAR-10:33 146.88 127.18 267.65 0.00 0.00 0.00 0.00 0.00 14.54
April 604.82 08-APR-10:33 220.32 127.18 267.65 0.00 0.00 0.00 0.00 2.83 0.00
May 670.53 31-MAY-10:35 97.92 84.79 178.43 0.00 0.00 0.00 0.00 4.30 0.00
June 737.74 22-JUN-18:03 1028.16 813.94 1376.47 0.00 0.00 0.00 0.00 8.19 0.00
July 748.94 11-JUL-17:09 979.20 813.94 1427.45 0.00 0.00 0.00 0.00 6.96 0.00
August 752.57 24-AUG-19:30 514.08 457.84 726.47 0.00 0.00 0.00 0.00 6.79 0.00
September 723.17 01-SEP-17:01 856.80 712.20 1249.02 0.00 0.00 0.00 0.00 6.69 0.00
October 623.20 05-OCT-10:33 146.88 127.18 267.65 0.00 0.00 0.00 0.00 0.00 2.26
November 535.33 04-NOV-10:33 220.32 127.18 267.65 0.00 0.00 0.00 0.00 0.00 7.75
December 423.55 19-DEC-21:00 171.36 152.61 242.16 0.00 0.00 0.00 0.00 0.00 20.78
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 355.99   97.92 84.79 178.43 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 752.57   1028.16 813.94 1427.45 0.00 0.00 0.00 0.00 8.19 34.24



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 36560.90 19-JAN-21:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 78.84
February 36466.59 17-FEB-21:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 91.99
March 37263.65 03-MAR-21:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 49.73
April 38041.22 07-APR-20:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 8.46
May 38433.30 30-MAY-20:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 14.93
June 39040.60 01-JUN-19:13 2116.80 1202.05 13718.40 119179.73 0.00 0.00 0.00 6.89 0.00
July 38710.21 10-JUL-20:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 15.48 0.00
August 40843.41 24-AUG-19:30 2116.80 1202.05 13718.40 119179.73 0.00 0.00 0.00 14.26 0.00
September 38492.16 14-SEP-19:30 1411.20 801.37 9145.60 79453.15 0.00 0.00 0.00 9.03 0.00
October 38068.91 04-OCT-20:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 19.02
November 37351.45 03-NOV-20:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 42.63
December 36590.45 20-DEC-21:00 705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 74.24
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 36466.59   705.60 400.68 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 40843.41   2116.80 1202.05 13718.40 119179.73 0.00 0.00 0.00 15.48 91.99



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 9959.43 17-JAN-13:00 3415.20 96.16 355.63 0.00 0.00 0.00 0.00 0.00 96.22
February 9887.98 20-FEB-13:00 5122.80 115.39 406.43 0.00 0.00 0.00 0.00 0.00 98.97
March 11547.53 03-MAR-13:10 3415.20 96.16 355.63 0.00 0.00 0.00 0.00 0.00 64.08
April 12122.22 08-APR-12:20 5122.80 96.16 355.63 0.00 0.00 0.00 0.00 0.00 0.88
May 10697.89 29-MAY-10:33 15368.40 346.16 1219.29 0.00 0.00 0.00 0.00 27.03 0.00
June 11587.08 19-JUN-21:10 15368.40 1048.97 711.25 0.00 0.00 0.00 0.00 30.20 0.00
July 11505.01 10-JUL-21:10 15368.40 1048.97 711.25 0.00 0.00 0.00 0.00 20.02 0.00
August 12387.70 13-AUG-12:00 5122.80 115.39 406.43 0.00 0.00 0.00 0.00 41.74 0.00
September 14032.87 30-SEP-12:40 5122.80 96.16 355.63 0.00 0.00 0.00 0.00 0.00 23.91
October 13764.78 04-OCT-12:00 3415.20 96.16 355.63 0.00 0.00 0.00 0.00 2.58 0.00
November 12329.02 04-NOV-12:30 5122.80 96.16 355.63 0.00 0.00 0.00 0.00 0.00 40.94
December 12263.86 17-DEC-11:00 8538.00 115.39 406.43 0.00 0.00 0.00 0.00 0.00 90.52
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 9887.98   3415.20 96.16 355.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14032.87   15368.40 1048.97 1219.29 0.00 0.00 0.00 0.00 41.74 98.97



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 26878.06 19-JAN-21:00 35484.54 10645.38 10029.21 0.00 0.00 0.00 0.00 0.00 383.70
February 26598.31 02-FEB-21:00 35484.54 10645.38 10029.21 0.00 0.00 0.00 0.00 0.00 502.13
March 29300.49 03-MAR-22:20 45622.98 7096.92 7389.94 0.00 0.00 0.00 0.00 0.00 266.18
April 34406.61 07-APR-21:10 45622.98 7096.92 7389.94 0.00 0.00 0.00 0.00 0.00 90.00
May 36892.29 31-MAY-21:10 45622.98 7096.92 7389.94 0.00 0.00 0.00 0.00 0.00 66.28
June 40426.69 19-JUN-21:10 45622.98 7096.92 7389.94 0.00 0.00 0.00 0.00 86.24 0.00
July 40992.97 10-JUL-21:10 45622.98 7096.92 7389.94 0.00 0.00 0.00 0.00 57.17 0.00
August 42005.26 04-AUG-21:10 45622.98 7096.92 7389.94 0.00 0.00 0.00 0.00 136.50 0.00
September 41161.47 01-SEP-21:10 45622.98 7096.92 7389.94 0.00 0.00 0.00 0.00 47.51 0.00
October 38211.22 05-OCT-21:10 45622.98 7096.92 7389.94 0.00 0.00 0.00 0.00 0.00 95.98
November 31803.53 03-NOV-21:10 45622.98 7096.92 7389.94 0.00 0.00 0.00 0.00 0.00 215.97
December 27960.08 17-DEC-11:33 45622.98 9155.03 12668.47 0.00 0.00 0.00 0.00 0.00 219.42
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 26598.31   35484.54 7096.92 7389.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 42005.26   45622.98 10645.38 12668.47 0.00 0.00 0.00 0.00 136.50 502.13



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2721.14 20-JAN-16:02 583.20 199.48 410.90 0.00 0.00 0.00 0.00 0.00 28.09
February 2766.85 14-FEB-16:01 680.40 232.73 479.39 0.00 0.00 0.00 0.00 0.00 41.24
March 2824.30 11-MAR-16:01 378.00 274.30 534.70 0.00 0.00 0.00 0.00 0.00 20.45
April 2932.56 16-APR-15:01 378.00 274.30 534.70 0.00 0.00 0.00 0.00 0.00 1.91
May 3029.21 20-MAY-18:02 702.00 712.44 774.39 0.00 0.00 0.00 0.00 0.00 1.05
June 3017.15 23-JUN-08:61 360.00 522.46 1132.61 0.00 0.00 0.00 0.00 6.54 0.00
July 3111.62 12-JUL-18:02 831.60 634.08 774.39 0.00 0.00 0.00 0.00 4.53 0.00
August 3088.05 15-AUG-18:02 831.60 634.08 774.39 0.00 0.00 0.00 0.00 6.10 0.00
September 3007.03 07-SEP-15:02 583.20 199.48 410.90 0.00 0.00 0.00 0.00 6.16 0.00
October 2839.35 04-OCT-15:02 583.20 199.48 410.90 0.00 0.00 0.00 0.00 1.27 0.00
November 2671.85 04-NOV-15:01 378.00 274.30 534.70 0.00 0.00 0.00 0.00 0.00 9.10
December 2750.03 18-DEC-16:01 680.40 232.73 479.39 0.00 0.00 0.00 0.00 0.00 31.51
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2671.85   360.00 199.48 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3111.62   831.60 712.44 1132.61 0.00 0.00 0.00 0.00 6.54 41.24



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2400.47 20-JAN-16:02 583.20 199.46 410.85 0.00 0.00 0.00 0.00 0.00 25.96
February 2469.74 22-FEB-16:02 583.20 199.46 410.85 0.00 0.00 0.00 0.00 0.00 31.71
March 2705.68 11-MAR-16:01 378.00 274.26 534.64 0.00 0.00 0.00 0.00 0.00 20.25
April 3094.93 09-APR-18:11 1170.00 1187.26 1290.50 0.00 0.00 0.00 0.00 0.00 18.41
May 3271.17 29-MAY-18:31 1170.00 1187.26 1290.50 0.00 0.00 0.00 0.00 0.15 0.00
June 3100.51 23-JUN-08:61 360.00 522.40 1132.48 0.00 0.00 0.00 0.00 3.39 0.00
July 3167.96 03-JUL-18:51 1386.00 1056.67 1290.50 0.00 0.00 0.00 0.00 0.26 0.00
August 3012.36 15-AUG-18:02 831.60 634.00 774.30 0.00 0.00 0.00 0.00 6.09 0.00
September 2965.92 03-SEP-08:51 486.00 598.38 1469.59 0.00 0.00 0.00 0.00 0.00 0.88
October 2872.99 24-OCT-15:02 583.20 199.46 410.85 0.00 0.00 0.00 0.00 0.00 1.77
November 2542.49 04-NOV-15:01 378.00 274.26 534.64 0.00 0.00 0.00 0.00 0.00 8.87
December 2407.57 17-DEC-16:02 324.00 235.08 458.26 0.00 0.00 0.00 0.00 0.00 20.43
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2400.47   324.00 199.46 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3271.17   1386.00 1187.26 1469.59 0.00 0.00 0.00 0.00 6.09 31.71



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 145.74 31-JAN-15:20 0.00 20.89 67.08 0.00 0.00 0.00 0.00 0.00 14.87
February 351.62 20-FEB-13:30 0.00 24.63 74.82 0.00 0.00 0.00 0.00 0.00 8.72
March 413.56 15-MAR-13:15 0.00 41.79 134.16 0.00 0.00 0.00 0.00 0.00 6.53
April 548.62 07-APR-12:30 0.00 20.89 67.08 0.00 0.00 0.00 0.00 0.00 0.26
May 420.31 30-MAY-12:50 0.00 20.89 67.08 0.00 0.00 0.00 0.00 1.49 0.00
June 438.08 19-JUN-13:20 0.00 20.89 67.08 0.00 0.00 0.00 0.00 3.71 0.00
July 465.56 10-JUL-13:10 0.00 20.89 67.08 0.00 0.00 0.00 0.00 2.58 0.00
August 588.89 30-AUG-13:00 0.00 20.89 67.08 0.00 0.00 0.00 0.00 0.23 0.00
September 645.41 28-SEP-12:40 0.00 20.89 67.08 0.00 0.00 0.00 0.00 0.00 1.80
October 684.49 04-OCT-12:10 0.00 20.89 67.08 0.00 0.00 0.00 0.00 0.00 1.05
November 577.38 02-NOV-12:50 0.00 20.89 67.08 0.00 0.00 0.00 0.00 0.00 5.50
December 395.77 17-DEC-13:40 0.00 24.63 74.82 0.00 0.00 0.00 0.00 0.00 7.14
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 145.74   0.00 20.89 67.08 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 684.49   0.00 41.79 134.16 0.00 0.00 0.00 0.00 3.71 14.87



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 729.57 23-JAN-19:02 831.60 398.60 758.70 0.00 0.00 0.00 0.00 0.00 5.88
February 759.01 18-FEB-09:02 270.00 209.00 799.99 0.00 0.00 0.00 0.00 0.00 8.29
March 811.18 03-MAR-19:02 831.60 398.60 758.70 0.00 0.00 0.00 0.00 0.00 4.92
April 946.49 07-APR-15:02 583.20 125.40 402.58 0.00 0.00 0.00 0.00 1.28 0.00
May 994.68 30-MAY-08:21 324.00 295.59 998.70 0.00 0.00 0.00 0.00 0.97 0.00
June 994.48 23-JUN-08:61 360.00 328.43 1109.66 0.00 0.00 0.00 0.00 1.25 0.00
July 984.25 03-JUL-15:02 583.20 125.40 402.58 0.00 0.00 0.00 0.00 2.39 0.00
August 991.20 12-AUG-15:02 324.00 147.80 449.03 0.00 0.00 0.00 0.00 2.68 0.00
September 979.18 01-SEP-18:02 831.60 398.60 758.70 0.00 0.00 0.00 0.00 2.24 0.00
October 894.24 25-OCT-15:02 583.20 125.40 402.58 0.00 0.00 0.00 0.00 0.06 0.00
November 807.18 02-NOV-18:02 831.60 398.60 758.70 0.00 0.00 0.00 0.00 0.00 4.01
December 762.72 10-DEC-09:02 324.00 250.80 959.99 0.00 0.00 0.00 0.00 0.00 8.52
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 729.57   270.00 125.40 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 994.68   831.60 398.60 1109.66 0.00 0.00 0.00 0.00 2.68 8.52



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2284.89 20-JAN-09:02 216.00 313.47 679.57 0.00 0.00 0.00 0.00 0.00 29.00
February 2562.22 25-FEB-09:01 378.00 465.46 1143.15 0.00 0.00 0.00 0.00 0.00 46.37
March 2550.27 11-MAR-16:01 378.00 274.30 534.70 0.00 0.00 0.00 0.00 0.00 20.18
April 2677.25 08-APR-08:62 324.00 398.97 979.84 0.00 0.00 0.00 0.00 0.00 4.24
May 2754.93 29-MAY-08:62 324.00 398.97 979.84 0.00 0.00 0.00 0.00 2.36 0.00
June 2910.35 23-JUN-08:61 360.00 522.46 1132.61 0.00 0.00 0.00 0.00 6.26 0.00
July 2872.29 13-JUL-08:62 216.00 313.47 679.57 0.00 0.00 0.00 0.00 7.24 0.00
August 2900.60 22-AUG-08:62 216.00 313.47 679.57 0.00 0.00 0.00 0.00 6.70 0.00
September 2806.63 06-SEP-08:62 216.00 313.47 679.57 0.00 0.00 0.00 0.00 2.16 0.00
October 2670.80 02-OCT-15:02 583.20 199.48 410.90 0.00 0.00 0.00 0.00 0.40 0.00
November 2502.87 04-NOV-15:01 378.00 274.30 534.70 0.00 0.00 0.00 0.00 0.00 9.17
December 2376.18 02-DEC-09:01 378.00 465.46 1143.15 0.00 0.00 0.00 0.00 0.00 35.33
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2284.89   216.00 199.48 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2910.35   583.20 522.46 1143.15 0.00 0.00 0.00 0.00 7.24 46.37



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1314.16 19-JAN-09:01 252.00 365.68 792.74 0.00 0.00 0.00 0.00 0.00 29.43
February 2334.97 25-FEB-09:01 378.00 465.41 1143.02 0.00 0.00 0.00 0.00 0.00 44.83
March 2321.81 26-MAR-08:62 324.00 398.92 979.73 0.00 0.00 0.00 0.00 0.00 25.50
April 2982.25 08-APR-08:51 540.00 664.87 1632.88 0.00 0.00 0.00 0.00 0.00 5.33
May 3330.19 30-MAY-08:62 216.00 313.44 679.49 0.00 0.00 0.00 0.00 0.00 3.05
June 3229.63 26-JUN-08:32 216.00 313.44 679.49 0.00 0.00 0.00 0.00 0.00 3.99
July 3192.04 11-JUL-08:32 180.00 261.20 566.24 0.00 0.00 0.00 0.00 0.00 4.73
August 3185.73 23-AUG-08:51 360.00 522.40 1132.48 0.00 0.00 0.00 0.00 0.00 4.47
September 3158.72 03-SEP-08:51 486.00 598.38 1469.59 0.00 0.00 0.00 0.00 0.00 4.50
October 2771.49 05-OCT-08:51 360.00 522.40 1132.48 0.00 0.00 0.00 0.00 0.00 10.69
November 2346.22 04-NOV-15:01 378.00 274.26 534.64 0.00 0.00 0.00 0.00 0.00 8.64
December 1910.60 20-DEC-09:01 252.00 365.68 792.74 0.00 0.00 0.00 0.00 0.00 26.87
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1314.16   180.00 261.20 534.64 0.00 0.00 0.00 0.00 0.00 3.05
Maximum of Months 3330.19   540.00 664.87 1632.88 0.00 0.00 0.00 0.00 0.00 44.83



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1253.05 19-JAN-22:00 2011.87 1031.11 0.00 0.00 0.00 0.00 0.00 0.00 34.03
February 1426.77 19-FEB-11:33 2263.36 1160.00 0.00 0.00 0.00 0.00 0.00 0.00 28.74
March 1548.29 29-MAR-10:33 1508.90 966.67 0.00 0.00 0.00 0.00 0.00 0.00 28.96
April 1903.83 08-APR-10:33 2263.36 966.67 0.00 0.00 0.00 0.00 0.00 3.58 0.00
May 2138.69 31-MAY-10:35 1005.94 644.45 0.00 0.00 0.00 0.00 0.00 5.26 0.00
June 2348.73 22-JUN-18:03 10562.33 6186.67 0.00 0.00 0.00 0.00 0.00 10.46 0.00
July 2375.07 11-JUL-17:09 10059.36 6186.67 0.00 0.00 0.00 0.00 0.00 8.89 0.00
August 2384.73 24-AUG-19:30 5281.16 3480.00 0.00 0.00 0.00 0.00 0.00 8.70 0.00
September 2334.98 01-SEP-17:01 8801.94 5413.34 0.00 0.00 0.00 0.00 0.00 8.16 0.00
October 2002.43 05-OCT-10:33 1508.90 966.67 0.00 0.00 0.00 0.00 0.00 0.00 3.61
November 1687.18 04-NOV-10:45 1508.90 644.45 0.00 0.00 0.00 0.00 0.00 0.00 10.10
December 1449.29 17-DEC-11:33 2263.36 1160.00 0.00 0.00 0.00 0.00 0.00 0.00 20.41
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1253.05   1005.94 644.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2384.73   10562.33 6186.67 0.00 0.00 0.00 0.00 0.00 10.46 34.03



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2847.74 20-JAN-16:02 583.20 199.48 410.90 0.00 0.00 0.00 0.00 0.00 28.13
February 2893.55 14-FEB-16:01 680.40 232.73 479.39 0.00 0.00 0.00 0.00 0.00 41.27
March 2969.66 11-MAR-16:01 378.00 274.30 534.70 0.00 0.00 0.00 0.00 0.00 20.55
April 3040.87 10-APR-18:02 831.60 634.08 774.39 0.00 0.00 0.00 0.00 0.00 5.77
May 3184.64 20-MAY-18:02 702.00 712.44 774.39 0.00 0.00 0.00 0.00 0.00 1.16
June 3228.99 19-JUN-18:02 831.60 634.08 774.39 0.00 0.00 0.00 0.00 15.36 0.00
July 3270.57 12-JUL-18:02 831.60 634.08 774.39 0.00 0.00 0.00 0.00 4.42 0.00
August 3296.62 15-AUG-18:02 831.60 634.08 774.39 0.00 0.00 0.00 0.00 5.99 0.00
September 3223.06 07-SEP-15:02 583.20 199.48 410.90 0.00 0.00 0.00 0.00 6.08 0.00
October 2991.26 02-OCT-18:02 831.60 634.08 774.39 0.00 0.00 0.00 0.00 0.00 2.89
November 2784.27 08-NOV-16:01 680.40 232.73 479.39 0.00 0.00 0.00 0.00 0.00 17.71
December 2878.37 02-DEC-16:01 378.00 274.30 534.70 0.00 0.00 0.00 0.00 0.00 30.07
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2784.27   378.00 199.48 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3296.62   831.60 712.44 774.39 0.00 0.00 0.00 0.00 15.36 41.27



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1947.80 17-JAN-16:02 583.20 199.46 410.85 0.00 0.00 0.00 0.00 0.00 21.73
February 2034.24 24-FEB-16:01 680.40 232.70 479.33 0.00 0.00 0.00 0.00 0.00 24.90
March 2830.02 11-MAR-16:01 378.00 274.26 534.64 0.00 0.00 0.00 0.00 0.00 20.31
April 3266.69 09-APR-18:11 1170.00 1187.26 1290.50 0.00 0.00 0.00 0.00 0.00 19.02
May 3495.40 29-MAY-18:31 1170.00 1187.26 1290.50 0.00 0.00 0.00 0.00 0.00 0.44
June 3212.06 23-JUN-08:61 360.00 522.40 1132.48 0.00 0.00 0.00 0.00 3.31 0.00
July 3277.38 03-JUL-18:51 1386.00 1056.67 1290.50 0.00 0.00 0.00 0.00 0.00 0.02
August 3166.68 15-AUG-18:02 831.60 634.00 774.30 0.00 0.00 0.00 0.00 5.96 0.00
September 3149.10 10-SEP-21:51 1247.40 908.26 829.61 0.00 0.00 0.00 0.00 0.00 12.53
October 2965.66 02-OCT-15:02 583.20 199.46 410.85 0.00 0.00 0.00 0.00 0.32 0.00
November 2616.97 04-NOV-15:01 378.00 274.26 534.64 0.00 0.00 0.00 0.00 0.00 8.87
December 1538.79 17-DEC-16:02 324.00 235.08 458.26 0.00 0.00 0.00 0.00 0.00 20.39
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1538.79   324.00 199.46 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3495.40   1386.00 1187.26 1290.50 0.00 0.00 0.00 0.00 5.96 24.90



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1563.81 31-JAN-16:02 583.20 125.40 402.58 0.00 0.00 0.00 0.00 0.00 23.49
February 1575.45 02-FEB-16:02 583.20 125.40 402.58 0.00 0.00 0.00 0.00 0.00 17.29
March 1577.13 13-MAR-15:02 583.20 125.40 402.58 0.00 0.00 0.00 0.00 0.00 14.65
April 1652.93 07-APR-15:02 583.20 125.40 402.58 0.00 0.00 0.00 0.00 2.25 0.00
May 1674.26 20-MAY-18:02 702.00 447.86 758.70 0.00 0.00 0.00 0.00 0.00 0.51
June 1705.41 22-JUN-18:02 831.60 398.60 758.70 0.00 0.00 0.00 0.00 5.12 0.00
July 1726.46 09-JUL-18:02 702.00 447.86 758.70 0.00 0.00 0.00 0.00 3.78 0.00
August 1767.64 16-AUG-15:02 583.20 125.40 402.58 0.00 0.00 0.00 0.00 7.69 0.00
September 1756.29 14-SEP-15:02 583.20 125.40 402.58 0.00 0.00 0.00 0.00 6.01 0.00
October 1690.88 03-OCT-15:02 583.20 125.40 402.58 0.00 0.00 0.00 0.00 0.16 0.00
November 1541.11 02-NOV-18:02 831.60 398.60 758.70 0.00 0.00 0.00 0.00 0.00 8.00
December 1570.17 15-DEC-16:01 680.40 146.30 469.67 0.00 0.00 0.00 0.00 0.00 17.27
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1541.11   583.20 125.40 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1767.64   831.60 447.86 758.70 0.00 0.00 0.00 0.00 7.69 23.49



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 17089.75 23-JAN-23:00 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 0.00 59.01
February 16450.08 23-FEB-23:00 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 0.00 84.37
March 18823.89 27-MAR-21:04 134943.84 9210.41 33739.51 0.00 0.00 0.00 0.00 0.00 43.21
April 20342.49 07-APR-21:53 188921.38 12894.57 47235.32 0.00 0.00 0.00 0.00 0.00 24.58
May 21840.84 31-MAY-21:52 269887.68 18420.82 67479.03 0.00 0.00 0.00 0.00 0.00 17.81
June 23256.39 19-JUN-21:20 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 18.21 0.00
July 23053.39 10-JUL-21:20 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 12.07 0.00
August 23342.76 04-AUG-21:20 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 27.65 0.00
September 22420.78 01-SEP-21:50 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 8.63 0.00
October 20562.71 05-OCT-21:53 188921.38 12894.57 47235.32 0.00 0.00 0.00 0.00 0.00 21.97
November 18537.89 03-NOV-22:00 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 0.00 48.86
December 16881.19 04-DEC-23:00 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 0.00 68.44
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 16450.08   26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23342.76   269887.68 18420.82 67479.03 0.00 0.00 0.00 0.00 27.65 84.37



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 19118.53 23-JAN-23:00 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 0.00 59.01
February 18423.32 23-FEB-23:00 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 0.00 84.37
March 20801.24 27-MAR-21:04 134943.84 9210.41 33739.51 0.00 0.00 0.00 0.00 0.00 43.21
April 22042.84 07-APR-21:10 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 0.00 20.61
May 23126.80 31-MAY-21:52 269887.68 18420.82 67479.03 0.00 0.00 0.00 0.00 0.00 17.81
June 24540.21 19-JUN-21:20 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 18.19 0.00
July 24268.04 10-JUL-21:20 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 12.06 0.00
August 24573.85 04-AUG-21:20 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 27.64 0.00
September 23674.47 01-SEP-21:10 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 10.26 0.00
October 21973.72 05-OCT-21:53 188921.38 12894.57 47235.32 0.00 0.00 0.00 0.00 0.00 21.97
November 20385.75 03-NOV-22:00 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 0.00 48.86
December 18872.66 04-DEC-23:00 26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 0.00 68.44
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 18423.32   26988.77 1842.08 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24573.85   269887.68 18420.82 67479.03 0.00 0.00 0.00 0.00 27.64 84.37



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 25171.17 17-JAN-11:50 533.71 303.01 14604.56 18744.03 0.00 0.00 0.00 0.00 59.20
February 25817.61 19-FEB-11:50 800.57 363.61 14604.56 18744.03 0.00 0.00 0.00 0.00 64.31
March 26825.67 29-MAR-10:33 1601.14 909.03 43813.67 56232.08 0.00 0.00 0.00 0.00 63.68
April 28975.79 08-APR-10:33 2401.70 909.03 43813.67 56232.08 0.00 0.00 0.00 0.00 0.73
May 29757.83 29-MAY-10:33 2401.70 1090.83 43813.67 56232.08 0.00 0.00 0.00 12.36 0.00
June 31659.78 01-JUN-18:02 11207.95 5817.77 87627.33 89971.33 0.00 0.00 0.00 11.64 0.00
July 31221.33 11-JUL-17:09 10674.24 5817.77 116836.45 179942.65 0.00 0.00 0.00 14.06 0.00
August 31124.09 22-AUG-17:01 10674.24 5817.77 116836.45 179942.65 0.00 0.00 0.00 15.50 0.00
September 30737.00 01-SEP-17:01 9339.96 5090.55 102231.89 157449.82 0.00 0.00 0.00 12.73 0.00
October 28438.03 04-OCT-10:33 1601.14 909.03 43813.67 56232.08 0.00 0.00 0.00 0.00 6.99
November 27157.26 04-NOV-10:45 1601.14 606.02 29209.11 37488.05 0.00 0.00 0.00 0.00 26.95
December 25688.08 17-DEC-11:50 800.57 363.61 14604.56 18744.03 0.00 0.00 0.00 0.00 46.93
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 25171.17   533.71 303.01 14604.56 18744.03 0.00 0.00 0.00 0.00 0.00
Maximum of Months 31659.78   11207.95 5817.77 116836.45 179942.65 0.00 0.00 0.00 15.50 64.31



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3118.18 17-JAN-11:35 1064.64 682.05 0.00 0.00 0.00 0.00 0.00 0.00 47.77
February 3338.71 19-FEB-11:33 2395.44 1227.68 0.00 0.00 0.00 0.00 0.00 0.00 52.15
March 3670.21 03-MAR-11:33 1596.96 1023.07 0.00 0.00 0.00 0.00 0.00 0.00 31.59
April 4543.90 08-APR-10:50 1596.96 682.05 0.00 0.00 0.00 0.00 0.00 2.13 0.00
May 5081.70 31-MAY-10:35 1064.64 682.05 0.00 0.00 0.00 0.00 0.00 7.02 0.00
June 5745.16 19-JUN-14:10 798.48 341.02 0.00 0.00 0.00 0.00 0.00 35.63 0.00
July 6497.62 11-JUL-15:07 7984.80 2046.14 0.00 0.00 0.00 0.00 0.00 15.11 0.00
August 6425.54 16-AUG-12:50 532.32 341.02 0.00 0.00 0.00 0.00 0.00 27.82 0.00
September 5709.03 01-SEP-14:10 798.48 341.02 0.00 0.00 0.00 0.00 0.00 24.43 0.00
October 4588.89 05-OCT-10:33 1596.96 1023.07 0.00 0.00 0.00 0.00 0.00 0.00 7.26
November 3816.95 04-NOV-10:50 1596.96 682.05 0.00 0.00 0.00 0.00 0.00 0.00 18.27
December 3396.85 17-DEC-11:33 2395.44 1227.68 0.00 0.00 0.00 0.00 0.00 0.00 37.46
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 3118.18   532.32 341.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6497.62   7984.80 2046.14 0.00 0.00 0.00 0.00 0.00 35.63 52.15



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.390504E+12 259168.99 18-JAN-20:10 0.461879E+12 391126.56 14-JAN-17:19
February 0.356021E+12 258459.45 23-FEB-20:10 0.412829E+12 422891.71 06-FEB-19:10
March 0.394063E+12 280038.09 27-MAR-19:19 0.359011E+12 378449.12 31-MAR-17:00
April 0.393268E+12 329933.27 07-APR-19:19 0.344061E+12 344773.69 20-APR-17:00
May 0.448343E+12 357857.47 29-MAY-19:30 0.280977E+12 284396.84 01-MAY-20:30
June 0.580951E+12 425859.04 19-JUN-19:40 0.218594E+12 169894.77 01-JUN-17:10
July 0.702819E+12 434730.38 20-JUL-20:00 0.215013E+12 157024.01 11-JUL-17:40
August 0.667218E+12 463186.21 04-AUG-19:19 0.217004E+12 165794.91 22-AUG-17:19
September 0.528899E+12 413879.71 07-SEP-19:00 0.228021E+12 181565.27 24-SEP-06:10
October 0.454826E+12 353386.88 05-OCT-19:10 0.300487E+12 297939.42 27-OCT-18:10
November 0.381190E+12 267653.51 03-NOV-19:10 0.378932E+12 361729.73 17-NOV-18:40
December 0.393248E+12 260912.05 18-DEC-20:30 0.389274E+12 365467.01 31-DEC-19:10
             
Annual Sum or Average 0.569135E+13     0.380608E+13    
Minimum of Months 0.356021E+12 258459.45   0.215013E+12 157024.01  
Maximum of Months 0.702819E+12 463186.21   0.461879E+12 422891.71  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.519633E+11 0.180295E+11 0.146779E+12 0.544823E+11 0.420299E+11 0.325864E+10 0.00 0.119572E+10 0.00 0.00 0.237958E+11 0.452836E+11 0.00
February 0.466662E+11 0.151200E+11 0.132565E+12 0.492098E+11 0.381369E+11 0.406699E+10 0.00 0.236615E+10 0.00 0.00 0.228649E+11 0.417053E+11 0.00
March 0.513801E+11 0.151400E+11 0.146789E+12 0.544839E+11 0.426250E+11 0.731005E+10 0.00 0.832625E+10 0.00 0.00 0.208745E+11 0.434317E+11 0.00
April 0.493691E+11 0.130494E+11 0.142011E+12 0.527241E+11 0.427800E+11 0.104108E+11 0.00 0.286933E+11 0.00 0.00 0.102552E+11 0.403819E+11 0.00
May 0.506285E+11 0.120641E+11 0.146789E+12 0.544825E+11 0.471001E+11 0.134604E+11 0.00 0.764897E+11 0.00 0.00 0.332265E+10 0.402639E+11 0.00
June 0.488519E+11 0.109256E+11 0.142058E+12 0.527256E+11 0.493918E+11 0.138254E+11 0.00 0.209333E+12 0.00 0.00 0.128272E+11 0.373613E+11 0.00
July 0.505008E+11 0.116246E+11 0.146742E+12 0.544805E+11 0.536880E+11 0.150662E+11 0.00 0.305102E+12 0.00 0.00 0.240513E+11 0.378001E+11 0.00
August 0.508408E+11 0.128364E+11 0.146800E+12 0.544836E+11 0.548733E+11 0.147871E+11 0.00 0.273323E+12 0.00 0.00 0.172616E+11 0.382376E+11 0.00
September 0.495775E+11 0.139482E+11 0.142022E+12 0.527243E+11 0.484441E+11 0.135130E+11 0.00 0.159053E+12 0.00 0.00 0.787531E+10 0.381004E+11 0.00
October 0.515706E+11 0.160788E+11 0.146768E+12 0.544820E+11 0.474431E+11 0.131753E+11 0.00 0.744686E+11 0.00 0.00 0.624269E+10 0.408608E+11 0.00
November 0.501363E+11 0.170242E+11 0.142074E+12 0.527252E+11 0.416924E+11 0.776822E+10 0.00 0.940008E+10 0.00 0.00 0.150618E+11 0.417264E+11 0.00
December 0.519307E+11 0.183824E+11 0.146742E+12 0.544814E+11 0.421127E+11 0.418928E+10 0.00 0.286938E+10 0.00 0.00 0.241640E+11 0.446872E+11 0.00
                           
Annual Sum or Average 0.603416E+12 0.174223E+12 0.172814E+13 0.641485E+12 0.550317E+12 0.120831E+12 0.00 0.115062E+13 0.00 0.00 0.188597E+12 0.489840E+12 0.00
Minimum of Months 0.466662E+11 0.109256E+11 0.132565E+12 0.492098E+11 0.381369E+11 0.325864E+10 0.00 0.119572E+10 0.00 0.00 0.332265E+10 0.373613E+11 0.00
Maximum of Months 0.519633E+11 0.183824E+11 0.146800E+12 0.544839E+11 0.548733E+11 0.150662E+11 0.00 0.305102E+12 0.00 0.00 0.241640E+11 0.452836E+11 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.182708E+12 0.00 0.127252E+12 0.00 0.00
February 0.137204E+12 0.00 0.155834E+12 0.00 0.119792E+12 0.00 0.00
March 0.152024E+12 0.00 0.892587E+11 0.00 0.117728E+12 0.00 0.00
April 0.146956E+12 0.00 0.968087E+11 0.00 0.100297E+12 0.00 0.00
May 0.151978E+12 0.00 0.400788E+11 0.00 0.889195E+11 0.00 0.00
June 0.147114E+12 0.00 0.950852E+09 0.00 0.705289E+11 0.00 0.00
July 0.151820E+12 0.00 0.150475E+09 0.00 0.630423E+11 0.00 0.00
August 0.152039E+12 0.00 0.481252E+09 0.00 0.644837E+11 0.00 0.00
September 0.146971E+12 0.00 0.976930E+10 0.00 0.712807E+11 0.00 0.00
October 0.151903E+12 0.00 0.612521E+11 0.00 0.873322E+11 0.00 0.00
November 0.147091E+12 0.00 0.129694E+12 0.00 0.102147E+12 0.00 0.00
December 0.151820E+12 0.00 0.117775E+12 0.00 0.119678E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.884761E+12 0.00 0.113248E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 0.150475E+09 0.00 0.630423E+11 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.182708E+12 0.00 0.127252E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 50471.22 02-JAN-20:10 11096.45 01-JAN-00:10 88863.15 02-JAN-07:10 39155.93 02-JAN-07:19 22651.05 02-JAN-19:10 5438.51 11-JAN-16:30 0.00 01-JAN-00:10
February 50471.22 01-FEB-20:10 11096.45 01-FEB-00:10 88863.15 01-FEB-07:10 39155.93 01-FEB-07:19 22876.91 06-FEB-19:10 5545.26 06-FEB-10:09 0.00 01-FEB-00:10
March 50471.22 01-MAR-20:10 11096.45 01-MAR-00:10 88863.15 01-MAR-07:10 39155.93 13-MAR-06:19 26169.20 27-MAR-21:10 5408.83 29-MAR-15:00 0.00 01-MAR-00:10
April 50471.22 03-APR-19:10 11096.45 01-APR-00:10 88863.15 03-APR-06:10 39154.88 18-APR-06:19 30650.03 07-APR-21:00 5673.13 07-APR-16:19 0.00 01-APR-00:10
May 50471.22 01-MAY-19:10 11096.45 01-MAY-00:10 88863.15 01-MAY-06:10 39154.91 04-MAY-06:19 34097.76 31-MAY-21:00 5755.88 31-MAY-18:10 0.00 01-MAY-00:10
June 50471.22 01-JUN-19:19 11096.45 01-JUN-00:10 88863.15 01-JUN-06:10 39154.46 29-JUN-06:19 35004.36 20-JUN-21:00 6841.42 24-JUN-18:10 0.00 01-JUN-00:10
July 50471.22 03-JUL-19:30 11096.45 01-JUL-00:10 88863.15 03-JUL-06:10 39154.68 24-JUL-06:19 34985.77 13-JUL-21:10 6907.06 20-JUL-18:10 0.00 01-JUL-00:10
August 50471.22 01-AUG-19:10 11096.45 01-AUG-00:10 88863.15 01-AUG-06:10 39154.65 16-AUG-06:19 36355.97 18-AUG-21:10 7534.60 11-AUG-20:00 0.00 01-AUG-00:10
September 50471.22 01-SEP-19:10 11096.45 01-SEP-00:10 88863.15 01-SEP-06:10 39155.45 27-SEP-06:19 36265.23 01-SEP-20:19 7085.22 07-SEP-19:00 0.00 01-SEP-00:10
October 50471.22 02-OCT-19:10 11096.45 01-OCT-00:10 88863.15 02-OCT-06:10 39155.93 16-OCT-06:19 33464.06 04-OCT-21:00 5667.80 05-OCT-15:09 0.00 01-OCT-00:10
November 50471.22 01-NOV-19:10 11096.45 01-NOV-00:10 88863.15 01-NOV-06:10 39155.93 01-NOV-06:19 27062.74 03-NOV-21:10 5425.00 06-NOV-09:09 0.00 01-NOV-00:10
December 50471.22 01-DEC-20:10 11096.45 01-DEC-00:10 88863.15 01-DEC-07:10 39155.93 08-DEC-07:19 22416.14 04-DEC-21:10 5445.95 16-DEC-16:19 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 50471.22   11096.45   88863.15   39154.46   22416.14   5408.83   0.00  
Maximum of Months 50471.22   11096.45   88863.15   39155.93   36355.97   7534.60   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 7821.64 17-JAN-16:10 0.00 0.00 9938.94 01-JAN-00:20 39004.53 02-JAN-19:30 0.00
February 13426.20 20-FEB-16:10 0.00 0.00 9938.94 01-FEB-00:20 38417.31 27-FEB-19:10 0.00
March 66935.54 27-MAR-15:00 0.00 0.00 9938.94 01-MAR-00:20 39574.20 31-MAR-18:49 0.00
April 101375.18 07-APR-15:09 0.00 0.00 9938.94 01-APR-00:10 40537.68 27-APR-18:19 0.00
May 116100.09 31-MAY-15:20 0.00 0.00 9938.94 01-MAY-01:30 41877.02 31-MAY-20:30 0.00
June 181404.06 19-JUN-18:10 0.00 0.00 9938.94 01-JUN-09:00 42355.78 30-JUN-20:40 0.00
July 174336.10 20-JUL-20:00 0.00 0.00 9938.94 01-JUL-08:20 41475.59 25-JUL-20:49 0.00
August 196240.11 04-AUG-19:10 0.00 0.00 9938.94 01-AUG-00:10 42459.95 25-AUG-17:10 0.00
September 158617.61 07-SEP-19:00 0.00 0.00 9938.94 01-SEP-00:10 43132.15 01-SEP-20:00 0.00
October 113377.39 03-OCT-15:09 0.00 0.00 9938.94 03-OCT-12:50 42691.68 03-OCT-17:00 0.00
November 44076.79 04-NOV-11:50 0.00 0.00 9938.94 01-NOV-01:39 41669.62 01-NOV-18:40 0.00
December 14615.99 18-DEC-10:00 0.00 0.00 9938.94 01-DEC-00:20 40295.38 01-DEC-19:19 0.00
                   
Annual Sum or Average     0.00 0.00         0.00
Minimum of Months 7821.64   0.00 0.00 9938.94   38417.31   0.00
Maximum of Months 196240.11   0.00 0.00 9938.94   43132.15   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 259168.99 18-JAN-20:10 50471.22 87982.85 11096.45 31573.10 21404.69 5049.51 0.00 2448.42 0.00
February 258459.45 23-FEB-20:10 50471.22 87982.85 11096.45 31573.10 21108.22 5079.96 0.00 1844.50 0.00
March 280038.09 27-MAR-19:19 50471.22 87982.85 11096.45 31577.78 22651.90 5038.22 0.00 31250.31 0.00
April 329933.27 07-APR-19:19 50471.22 87982.85 11096.45 31577.78 24410.02 5319.20 0.00 77356.80 0.00
May 357857.47 29-MAY-19:30 46435.92 86521.75 11096.45 31540.10 26686.53 5511.42 0.00 100635.65 0.00
June 425859.04 19-JUN-19:40 50471.22 87982.85 11096.45 31577.78 30049.93 6170.25 0.00 158930.96 0.00
July 434730.38 20-JUL-20:00 44879.15 88373.09 11096.45 24006.45 32710.72 6819.94 0.00 174336.10 0.00
August 463186.21 04-AUG-19:19 50471.22 87982.85 11096.45 31577.78 31960.30 6619.85 0.00 194004.49 0.00
September 413879.71 07-SEP-19:00 50471.22 87982.85 11096.45 31577.78 29976.31 7085.22 0.00 158617.61 0.00
October 353386.88 05-OCT-19:10 50471.22 87982.85 11096.45 31573.10 25184.38 5622.13 0.00 90852.66 0.00
November 267653.51 03-NOV-19:10 50471.22 87982.85 11096.45 31573.10 24128.51 5018.57 0.00 13798.73 0.00
December 260912.05 18-DEC-20:30 50471.22 87982.85 11096.45 31577.78 20855.88 5037.09 0.00 3452.80 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 258459.45   44879.15 86521.75 11096.45 24006.45 20855.88 5018.57 0.00 1844.50 0.00
Maximum of Months 463186.21   50471.22 88373.09 11096.45 31577.78 32710.72 7085.22 0.00 194004.49 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 231338.65 14-JAN-16:10 0.00 128423.66 25-JAN-21:49 0.00
February 104248.32 01-FEB-18:10 0.00 232046.90 06-FEB-09:09 0.00 136843.69 06-FEB-21:49 0.00
March 104248.32 01-MAR-18:10 0.00 164987.07 31-MAR-17:00 0.00 114499.24 01-MAR-19:00 0.00
April 104248.32 01-APR-17:10 0.00 159002.00 15-APR-15:09 0.00 98552.34 01-APR-18:10 0.00
May 104248.32 01-MAY-17:10 0.00 129474.54 01-MAY-20:30 0.00 80204.41 01-MAY-21:00 0.00
June 104248.32 01-JUN-17:10 0.00 28685.39 03-JUN-04:00 0.00 58927.81 01-JUN-22:30 0.00
July 104248.32 01-JUL-17:10 0.00 22470.34 11-JUL-15:50 0.00 44885.45 01-JUL-18:00 0.00
August 104248.32 01-AUG-17:10 0.00 22006.45 19-AUG-12:30 0.00 45094.81 31-AUG-19:19 0.00
September 104248.32 01-SEP-17:10 0.00 116754.64 24-SEP-05:49 0.00 59052.73 30-SEP-22:49 0.00
October 104248.32 02-OCT-17:10 0.00 143703.66 16-OCT-05:00 0.00 78158.85 31-OCT-17:10 0.00
November 104248.32 01-NOV-17:10 0.00 171079.07 28-NOV-16:10 0.00 101270.24 30-NOV-19:19 0.00
December 104248.32 01-DEC-18:10 0.00 167243.25 31-DEC-23:00 0.00 119088.51 21-DEC-21:00 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 22006.45   0.00 44885.45   0.00
Maximum of Months 104248.32   0.00 232046.90   0.00 136843.69   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 1.17 24.76 1.17 24.76
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.83 24.75 0.83 24.75
September 0.00 0.00 0.00 0.00 1.33 24.63 1.33 24.63
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.33 24.70 3.33 24.70
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.33 24.76 1.33 24.76



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.33 21.72 0.33 21.72
April 0.00 0.00 0.00 0.00 0.67 21.76 0.67 21.76
May 0.00 0.00 0.00 0.00 1.50 21.79 1.50 21.79
June 0.00 0.00 0.00 0.00 2.50 21.76 2.50 21.76
July 0.00 0.00 0.00 0.00 3.17 21.78 3.17 21.78
August 0.00 0.00 0.00 0.00 4.67 21.86 4.67 21.86
September 0.00 0.00 0.00 0.00 2.50 21.83 2.50 21.83
October 0.00 0.00 0.00 0.00 1.50 21.77 1.50 21.77
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   16.83 21.80 16.83 21.80
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 4.67 21.86 4.67 21.86



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.67 21.91 0.67 21.91
May 0.00 0.00 0.00 0.00 2.67 21.88 2.67 21.88
June 0.00 0.00 0.00 0.00 6.67 21.82 6.67 21.82
July 0.00 0.00 0.00 0.00 6.83 21.79 6.83 21.79
August 0.00 0.00 0.00 0.00 5.50 21.82 5.50 21.82
September 0.00 0.00 0.00 0.00 2.17 21.75 2.17 21.75
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   24.50 21.81 24.50 21.81
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 6.83 21.91 6.83 21.91



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 20.54 0.17 20.54 0.00 20.54 0.00 20.54
February 0.17 20.47 0.17 20.47 0.00 20.47 0.00 20.47
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.50 21.70 0.50 21.70
May 0.00 0.00 0.00 0.00 7.50 21.83 7.50 21.83
June 0.00 0.00 0.00 0.00 15.17 21.89 15.17 21.89
July 0.00 0.00 0.00 0.00 17.00 21.85 17.00 21.85
August 0.00 0.00 0.00 0.00 11.00 21.78 11.00 21.78
September 0.00 0.00 0.00 0.00 6.33 21.81 6.33 21.81
October 0.00 0.00 0.00 0.00 0.83 21.73 0.83 21.73
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 20.50 0.33 20.50 58.33 21.82 58.33 21.83
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 20.54 0.17 20.54 17.00 21.89 17.00 21.89



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.17 21.78 1.17 21.78
June 0.00 0.00 0.00 0.00 1.17 21.83 1.17 21.83
July 0.00 0.00 0.00 0.00 0.83 21.75 0.83 21.75
August 0.00 0.00 0.00 0.00 1.83 21.72 1.83 21.72
September 0.00 0.00 0.00 0.00 0.67 21.80 0.67 21.80
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   5.67 21.77 5.67 21.77
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.83 21.83 1.83 21.83



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 22.20 0.33 22.20
May 0.00 0.00 0.00 0.00 4.33 22.34 4.33 22.34
June 0.00 0.00 0.00 0.00 8.00 22.26 8.00 22.26
July 0.00 0.00 0.00 0.00 8.50 22.17 8.50 22.17
August 0.00 0.00 0.00 0.00 8.33 22.18 8.33 22.18
September 0.00 0.00 0.00 0.00 5.17 22.26 5.17 22.26
October 0.00 0.00 0.00 0.00 1.17 22.13 1.17 22.13
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   35.83 22.23 35.83 22.23
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 8.50 22.34 8.50 22.34



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.33 21.69 0.33 21.69
April 0.00 0.00 0.00 0.00 0.67 21.79 0.67 21.79
May 0.00 0.00 0.00 0.00 2.50 21.79 2.50 21.79
June 0.00 0.00 0.00 0.00 2.67 21.80 2.67 21.80
July 0.00 0.00 0.00 0.00 3.00 21.82 3.00 21.82
August 0.00 0.00 0.00 0.00 5.67 21.88 5.67 21.88
September 0.00 0.00 0.00 0.00 3.17 21.83 3.17 21.83
October 0.00 0.00 0.00 0.00 1.67 21.76 1.67 21.76
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   19.67 21.82 19.67 21.82
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 5.67 21.88 5.67 21.88



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.67 22.05 0.67 22.05
May 0.00 0.00 0.00 0.00 4.83 21.90 4.83 21.90
June 0.00 0.00 0.00 0.00 7.50 21.88 7.50 21.88
July 0.00 0.00 0.00 0.00 7.17 21.83 7.17 21.83
August 0.00 0.00 0.00 0.00 6.33 21.84 6.33 21.84
September 0.00 0.00 0.00 0.00 2.67 21.76 2.67 21.76
October 0.00 0.00 0.00 0.00 0.17 21.69 0.17 21.69
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   29.33 21.85 29.33 21.85
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 7.50 22.05 7.50 22.05



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 21.76 0.17 21.76
February 0.00 0.00 0.00 0.00 0.17 21.74 0.17 21.74
March 0.00 0.00 0.00 0.00 1.33 21.88 1.33 21.88
April 0.00 0.00 0.00 0.00 1.00 21.76 1.00 21.76
May 0.00 0.00 0.00 0.00 0.33 21.68 0.33 21.68
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.50 21.71 1.50 21.71
August 0.00 0.00 0.00 0.00 3.67 21.76 3.67 21.76
September 0.00 0.00 0.00 0.00 3.50 21.79 3.50 21.79
October 0.00 0.00 0.00 0.00 5.00 21.88 5.00 21.88
November 0.00 0.00 0.00 0.00 0.50 21.76 0.50 21.76
December 0.00 0.00 0.00 0.00 0.33 21.73 0.33 21.73
                 
Annual Sum or Average 0.00   0.00   17.50 21.80 17.50 21.80
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 5.00 21.88 5.00 21.88



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.67 24.86 1.67 24.86
June 0.00 0.00 0.00 0.00 4.83 24.96 4.83 24.96
July 0.00 0.00 0.00 0.00 1.50 25.05 1.50 25.05
August 0.00 0.00 0.00 0.00 4.50 24.91 4.50 24.91
September 0.00 0.00 0.00 0.00 0.50 24.66 0.50 24.66
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   13.00 24.93 13.00 24.93
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 4.83 25.05 4.83 25.05



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 22.85 0.00 22.85 0.00 22.85
February 672.00 22.40 0.00 22.40 0.00 22.40
March 744.00 22.01 0.00 22.01 0.00 22.01
April 720.00 21.79 0.00 21.79 0.00 21.79
May 744.00 21.63 0.00 21.63 0.00 21.63
June 720.00 22.09 0.00 22.09 0.00 22.09
July 744.00 22.53 0.00 22.53 0.00 22.53
August 713.33 23.00 0.00 23.00 0.00 23.00
September 372.00 23.36 133.50 23.49 0.00 23.49
October 333.00 23.75 174.00 23.81 0.00 23.81
November 558.83 23.72 11.50 23.73 0.00 23.73
December 738.50 23.48 0.00 23.48 0.00 23.48
             
Annual Sum or Average 7803.67 22.62 319.00 22.67 0.00 22.67
Minimum of Months 333.00 21.63 0.00 21.63 0.00 21.63
Maximum of Months 744.00 23.75 174.00 23.81 0.00 23.81



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 736.00 21.12 374.50 21.08 374.50 21.06
February 656.67 21.18 335.00 21.12 335.00 21.09
March 708.67 21.23 117.67 21.22 112.33 21.19
April 674.17 21.33 37.33 21.39 18.67 21.38
May 685.50 21.53 17.67 21.58 0.00 21.58
June 513.67 22.11 110.17 22.36 0.00 22.36
July 302.50 22.37 268.00 22.94 0.00 22.94
August 210.33 22.40 394.00 23.25 0.00 23.25
September 459.17 21.93 186.33 22.47 0.00 22.47
October 524.83 21.74 138.67 22.18 0.00 22.18
November 686.67 21.21 117.83 21.23 106.17 21.20
December 721.33 21.14 339.67 21.10 339.67 21.07
             
Annual Sum or Average 6879.50 21.48 2436.83 21.69 1286.33 21.60
Minimum of Months 210.33 21.12 17.67 21.08 0.00 21.06
Maximum of Months 736.00 22.40 394.00 23.25 374.50 23.25



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.45 40.17 21.42 40.17 21.40
February 672.00 21.54 43.17 21.51 43.17 21.48
March 744.00 21.96 0.00 21.96 0.00 21.96
April 698.50 22.27 0.17 22.27 0.00 22.27
May 662.00 22.64 32.17 22.69 5.00 22.70
June 305.83 22.91 252.00 23.32 0.67 23.32
July 124.17 22.95 425.00 23.64 0.00 23.64
August 85.33 23.10 438.50 23.76 2.50 23.76
September 345.83 22.91 192.00 23.25 0.00 23.25
October 557.00 22.90 87.00 23.02 0.50 23.02
November 718.50 22.04 0.00 22.04 0.00 22.04
December 744.00 21.67 3.50 21.66 3.50 21.66
             
Annual Sum or Average 6401.17 22.15 1513.67 22.44 95.50 22.43
Minimum of Months 85.33 21.45 0.00 21.42 0.00 21.40
Maximum of Months 744.00 23.10 438.50 23.76 43.17 23.76



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.02 300.00 21.01 300.00 21.01
February 672.00 21.01 342.33 21.01 342.33 21.01
March 744.00 21.12 69.83 21.11 69.83 21.10
April 720.00 21.50 9.33 21.50 9.33 21.49
May 737.83 22.23 0.00 22.23 0.00 22.23
June 554.33 23.04 12.67 23.07 0.00 23.07
July 208.83 23.25 128.33 23.51 0.00 23.51
August 243.83 23.34 149.83 23.57 0.00 23.57
September 594.83 22.92 6.17 22.93 0.00 22.93
October 744.00 22.36 0.00 22.36 0.00 22.36
November 720.00 21.33 51.00 21.31 51.00 21.29
December 744.00 21.03 125.50 21.03 125.50 21.02
             
Annual Sum or Average 7427.67 21.80 1195.00 21.79 898.00 21.72
Minimum of Months 208.83 21.01 0.00 21.01 0.00 21.01
Maximum of Months 744.00 23.34 342.33 23.57 342.33 23.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 352.50 21.00 352.50 21.00
February 672.00 21.00 394.33 21.00 394.33 21.00
March 744.00 21.05 93.67 21.04 93.67 21.04
April 720.00 21.37 11.33 21.37 11.33 21.36
May 744.00 22.08 0.00 22.08 0.00 22.08
June 644.00 22.98 0.00 22.98 0.00 22.98
July 334.50 23.26 15.83 23.29 0.00 23.29
August 373.67 23.31 67.83 23.40 0.00 23.40
September 679.00 22.84 0.00 22.84 0.00 22.84
October 744.00 22.19 0.00 22.19 0.00 22.19
November 720.00 21.22 63.00 21.20 63.00 21.18
December 744.00 21.00 179.33 21.00 179.33 21.00
             
Annual Sum or Average 7863.17 21.80 1177.83 21.72 1094.17 21.64
Minimum of Months 334.50 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 23.31 394.33 23.40 394.33 23.40



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 326.67 22.40 373.50 23.02 129.50 23.17
February 282.67 22.38 305.00 23.07 110.17 23.22
March 268.00 22.71 434.83 23.17 147.33 23.31
April 267.50 23.05 499.83 23.19 180.17 23.34
May 298.33 23.45 615.00 23.21 243.83 23.37
June 287.83 23.88 666.33 23.23 278.33 23.40
July 303.00 23.96 716.17 23.20 303.00 23.37
August 302.50 23.95 710.00 23.21 300.17 23.39
September 291.50 23.75 646.67 23.24 269.50 23.41
October 278.00 23.42 589.17 23.24 223.67 23.39
November 258.50 22.83 450.83 23.19 152.33 23.34
December 269.50 22.53 367.50 23.17 127.50 23.31
             
Annual Sum or Average 3434.00 23.20 6374.83 23.19 2465.50 23.35
Minimum of Months 258.50 22.38 305.00 23.02 110.17 23.17
Maximum of Months 326.67 23.96 716.17 23.24 303.00 23.41



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 719.00 21.57 87.17 21.52 82.17 21.48
February 632.83 21.73 49.00 21.72 40.50 21.68
March 667.67 22.02 34.00 22.11 0.00 22.11
April 566.33 22.09 62.83 22.24 0.00 22.24
May 543.00 22.47 128.67 22.67 47.50 22.72
June 346.83 23.18 464.17 23.37 209.83 23.45
July 295.83 23.73 663.00 23.62 276.67 23.67
August 226.83 23.79 692.83 23.74 210.17 23.78
September 281.67 22.98 475.17 23.43 145.67 23.48
October 362.33 22.93 375.50 23.36 88.67 23.40
November 637.67 21.99 37.17 22.09 1.83 22.10
December 702.50 21.75 34.83 21.79 14.67 21.78
             
Annual Sum or Average 5982.50 22.27 3104.33 22.70 1117.67 22.78
Minimum of Months 226.83 21.57 34.00 21.52 0.00 21.48
Maximum of Months 719.00 23.79 692.83 23.74 276.67 23.78



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 22.01 7.67 22.00 7.67 21.99
February 672.00 22.14 0.50 22.14 0.50 22.14
March 734.33 22.49 0.00 22.49 0.00 22.49
April 610.83 22.60 33.33 22.67 0.00 22.67
May 517.17 22.86 120.83 23.04 42.50 23.09
June 339.00 23.44 387.67 23.66 188.33 23.72
July 260.17 23.88 559.67 23.82 239.33 23.86
August 185.50 23.93 621.50 23.83 175.50 23.86
September 262.83 23.37 390.83 23.64 129.33 23.69
October 387.83 23.27 270.50 23.47 68.17 23.52
November 673.67 22.54 8.17 22.56 1.83 22.56
December 744.00 22.27 0.00 22.27 0.00 22.27
             
Annual Sum or Average 6131.33 22.66 2400.67 22.98 853.17 23.07
Minimum of Months 185.50 22.01 0.00 22.00 0.00 21.99
Maximum of Months 744.00 23.93 621.50 23.83 239.33 23.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.84 476.00 20.76 476.00 20.72
February 672.00 20.97 430.83 20.88 430.83 20.84
March 743.83 21.24 120.00 21.17 120.00 21.12
April 700.17 21.37 22.00 21.33 21.83 21.31
May 699.83 21.53 3.67 21.53 1.67 21.54
June 616.33 21.46 11.00 21.49 2.50 21.50
July 608.33 21.39 19.00 21.45 1.67 21.46
August 593.00 21.35 39.00 21.47 1.00 21.48
September 635.67 21.48 14.83 21.52 2.50 21.53
October 685.50 21.49 3.83 21.50 1.50 21.50
November 720.00 21.18 168.67 21.10 168.67 21.04
December 744.00 20.95 438.00 20.86 438.00 20.82
             
Annual Sum or Average 8162.67 21.26 1746.83 21.19 1666.17 21.12
Minimum of Months 593.00 20.84 3.67 20.76 1.00 20.72
Maximum of Months 744.00 21.53 476.00 21.53 476.00 21.54



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.64 598.67 20.59 598.67 20.57
February 672.00 20.69 574.33 20.65 574.33 20.64
March 741.67 21.03 215.50 20.95 213.50 20.90
April 689.17 21.33 38.00 21.35 27.17 21.31
May 639.83 21.72 61.17 22.02 8.67 22.05
June 528.50 22.18 167.83 22.83 87.83 23.03
July 570.83 21.79 96.50 22.15 55.67 22.32
August 558.50 21.64 77.00 21.94 16.67 21.99
September 587.67 21.96 93.33 22.31 37.33 22.40
October 681.50 21.65 42.67 21.77 20.83 21.80
November 720.00 20.96 271.67 20.86 271.67 20.80
December 744.00 20.70 634.83 20.66 634.83 20.65
             
Annual Sum or Average 7877.67 21.31 2871.50 21.32 2547.17 21.24
Minimum of Months 528.50 20.64 38.00 20.59 8.67 20.57
Maximum of Months 744.00 22.18 634.83 22.83 634.83 23.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.95 317.33 20.89 317.33 20.86
February 672.00 20.94 352.67 20.88 352.67 20.86
March 744.00 21.18 57.00 21.16 57.00 21.14
April 720.00 21.44 0.00 21.44 0.00 21.44
May 735.00 21.85 6.50 21.87 2.33 21.87
June 699.67 22.27 94.83 22.43 88.50 22.54
July 729.00 22.05 63.17 22.18 59.67 22.29
August 738.67 21.99 16.67 22.02 16.67 22.05
September 709.50 22.09 35.83 22.16 35.00 22.21
October 744.00 21.62 13.83 21.63 13.83 21.65
November 720.00 21.19 64.33 21.16 64.33 21.13
December 744.00 21.00 175.17 20.94 175.17 20.90
             
Annual Sum or Average 8699.83 21.55 1197.33 21.52 1182.50 21.49
Minimum of Months 672.00 20.94 0.00 20.88 0.00 20.86
Maximum of Months 744.00 22.27 352.67 22.43 352.67 22.54



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.84 479.17 20.77 479.17 20.73
February 672.00 21.00 407.67 20.91 407.67 20.87
March 744.00 21.30 125.50 21.22 125.50 21.17
April 705.00 21.44 22.50 21.40 22.50 21.37
May 709.33 21.58 2.17 21.58 1.67 21.58
June 606.33 21.44 4.83 21.45 2.83 21.46
July 586.00 21.33 4.50 21.34 1.33 21.35
August 570.50 21.28 6.17 21.30 0.50 21.30
September 614.50 21.44 6.00 21.45 2.83 21.46
October 684.17 21.51 1.50 21.52 1.00 21.52
November 720.00 21.22 155.67 21.14 155.67 21.08
December 744.00 20.95 431.67 20.87 431.67 20.83
             
Annual Sum or Average 8099.83 21.27 1647.33 21.18 1632.33 21.12
Minimum of Months 570.50 20.84 1.50 20.77 0.50 20.73
Maximum of Months 744.00 21.58 479.17 21.58 479.17 21.58



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.63 595.83 20.59 595.83 20.57
February 672.00 20.70 558.33 20.66 558.33 20.65
March 744.00 21.07 195.50 21.01 195.50 20.96
April 712.83 21.46 27.50 21.44 25.17 21.41
May 673.17 21.86 37.17 22.02 10.67 22.06
June 517.17 22.10 152.67 22.61 92.83 22.80
July 542.50 21.78 100.83 22.21 59.17 22.42
August 505.67 21.53 82.83 21.97 20.00 22.07
September 602.00 22.05 81.33 22.32 40.33 22.42
October 732.67 21.77 27.17 21.82 21.83 21.84
November 720.00 20.99 232.50 20.89 232.50 20.82
December 744.00 20.69 611.00 20.65 611.00 20.64
             
Annual Sum or Average 7910.00 21.34 2702.67 21.33 2463.17 21.26
Minimum of Months 505.67 20.63 27.17 20.59 10.67 20.57
Maximum of Months 744.00 22.10 611.00 22.61 611.00 22.80



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 272.00 21.00 272.00 21.00
February 672.00 21.00 301.33 21.00 301.33 21.00
March 744.00 21.09 38.50 21.09 38.50 21.08
April 720.00 21.49 2.67 21.48 2.67 21.48
May 743.33 22.18 4.67 22.18 4.67 22.19
June 641.50 23.14 50.50 23.15 50.50 23.15
July 393.50 23.37 111.17 23.41 89.67 23.42
August 245.67 23.48 119.83 23.58 52.33 23.58
September 575.17 22.87 39.17 22.91 30.50 22.93
October 744.00 22.39 4.17 22.39 4.17 22.39
November 720.00 21.20 38.67 21.19 38.67 21.18
December 744.00 21.01 123.67 21.00 123.67 21.00
             
Annual Sum or Average 7687.17 21.84 1106.33 21.83 1008.67 21.80
Minimum of Months 245.67 21.00 2.67 21.00 2.67 21.00
Maximum of Months 744.00 23.48 301.33 23.58 301.33 23.58



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.73 596.17 20.67 596.17 20.65
February 672.00 20.86 529.50 20.79 529.50 20.76
March 740.50 21.15 221.67 21.05 221.67 20.98
April 693.33 21.30 63.67 21.24 61.17 21.19
May 682.33 21.46 28.00 21.49 19.50 21.50
June 598.67 21.40 41.83 21.51 11.50 21.53
July 589.83 21.34 53.17 21.50 5.33 21.51
August 578.00 21.31 70.17 21.53 2.00 21.53
September 622.00 21.43 45.00 21.51 19.33 21.52
October 679.00 21.43 40.50 21.47 25.17 21.46
November 718.50 21.06 270.67 20.96 270.67 20.91
December 744.00 20.83 565.17 20.77 565.17 20.74
             
Annual Sum or Average 8062.17 21.18 2525.50 21.11 2327.17 21.04
Minimum of Months 578.00 20.73 28.00 20.67 2.00 20.65
Maximum of Months 744.00 21.46 596.17 21.53 596.17 21.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.55 683.00 20.53 683.00 20.52
February 672.00 20.61 629.67 20.59 629.67 20.58
March 741.17 20.94 327.33 20.84 325.00 20.77
April 680.50 21.26 100.50 21.28 81.50 21.21
May 625.83 21.73 94.50 22.12 34.83 22.19
June 515.00 22.26 205.17 22.99 108.50 23.24
July 557.00 21.77 127.33 22.21 69.67 22.39
August 541.50 21.58 104.33 21.96 22.00 22.02
September 574.33 21.91 127.67 22.32 64.50 22.42
October 672.67 21.55 118.67 21.67 90.33 21.66
November 720.00 20.84 366.67 20.74 366.67 20.69
December 744.00 20.59 698.00 20.57 698.00 20.57
             
Annual Sum or Average 7788.00 21.24 3582.83 21.27 3173.67 21.19
Minimum of Months 515.00 20.55 94.50 20.53 22.00 20.52
Maximum of Months 744.00 22.26 698.00 22.99 698.00 23.24



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 737.33 21.11 334.00 21.00 334.00 20.94
February 665.33 21.29 272.67 21.16 272.67 21.09
March 714.83 21.32 87.17 21.27 87.17 21.23
April 686.00 21.40 16.50 21.39 13.17 21.36
May 700.33 21.53 0.67 21.53 0.67 21.53
June 631.00 21.48 18.33 21.51 17.50 21.54
July 624.17 21.44 10.50 21.46 8.67 21.48
August 608.17 21.39 62.83 21.57 2.33 21.57
September 616.50 21.43 50.67 21.56 7.50 21.57
October 629.33 21.38 47.83 21.51 2.83 21.52
November 698.17 21.40 53.67 21.37 52.83 21.34
December 729.00 21.20 264.50 21.09 264.50 21.02
             
Annual Sum or Average 8040.17 21.36 1219.33 21.33 1063.83 21.29
Minimum of Months 608.17 21.11 0.67 21.00 0.67 20.94
Maximum of Months 737.33 21.53 334.00 21.57 334.00 21.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 612.83 22.94 11.67 22.95 0.00 22.95
February 593.17 23.00 0.00 23.00 0.00 23.00
March 423.00 23.05 47.00 23.14 0.00 23.14
April 218.17 23.06 228.50 23.52 0.00 23.52
May 82.33 23.60 523.83 23.87 48.00 23.88
June 187.17 23.99 702.67 23.94 187.00 23.95
July 229.00 24.00 744.00 23.97 229.00 23.97
August 177.33 24.00 738.17 23.95 177.33 23.96
September 135.00 23.98 626.00 23.93 133.00 23.94
October 236.17 23.48 391.67 23.71 84.67 23.74
November 391.83 22.99 84.83 23.16 3.67 23.17
December 568.00 23.03 5.67 23.04 0.00 23.04
             
Annual Sum or Average 3854.00 23.23 4104.00 23.59 862.67 23.63
Minimum of Months 82.33 22.94 0.00 22.95 0.00 22.95
Maximum of Months 612.83 24.00 744.00 23.97 229.00 23.97



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 466.00 23.02 39.67 23.10 0.00 23.10
February 469.50 23.10 11.00 23.12 0.00 23.12
March 248.17 23.08 169.50 23.44 0.00 23.44
April 99.33 23.14 371.00 23.78 0.00 23.78
May 42.33 23.93 646.17 23.93 38.83 23.94
June 166.67 24.00 712.67 23.97 166.67 23.97
July 212.50 24.00 744.00 23.98 212.50 23.98
August 161.17 24.00 743.33 23.97 161.17 23.97
September 118.67 24.00 690.83 23.94 118.67 23.95
October 142.67 23.61 458.67 23.82 69.83 23.84
November 241.00 23.07 179.83 23.45 2.67 23.46
December 383.50 23.01 38.33 23.10 0.00 23.10
             
Annual Sum or Average 2751.50 23.33 4805.00 23.72 770.33 23.75
Minimum of Months 42.33 23.01 11.00 23.10 0.00 23.10
Maximum of Months 469.50 24.00 744.00 23.98 212.50 23.98



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 550.67 23.60 585.33 23.77 444.83 23.83
February 509.17 23.55 522.67 23.75 399.33 23.82
March 543.17 23.83 626.17 23.86 497.33 23.90
April 513.00 23.95 654.83 23.89 502.67 23.92
May 547.83 23.99 735.50 23.89 547.83 23.92
June 555.33 24.01 720.00 23.93 555.33 23.96
July 589.83 23.99 744.00 23.94 589.83 23.96
August 586.17 24.01 744.00 23.96 586.17 23.97
September 542.00 23.99 718.83 23.91 542.00 23.94
October 534.67 23.98 700.50 23.90 530.17 23.92
November 522.17 23.84 614.83 23.86 482.00 23.90
December 558.00 23.68 594.33 23.81 467.83 23.86
             
Annual Sum or Average 6552.00 23.87 7961.00 23.88 6145.33 23.91
Minimum of Months 509.17 23.55 522.67 23.75 399.33 23.82
Maximum of Months 589.83 24.01 744.00 23.96 589.83 23.97



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.01 318.33 21.00 318.33 21.00
February 672.00 21.02 313.83 21.01 313.83 21.01
March 744.00 21.12 46.83 21.11 46.83 21.11
April 720.00 21.50 0.00 21.50 0.00 21.50
May 710.50 22.14 7.67 22.16 0.00 22.16
June 406.00 22.94 108.67 23.13 0.00 23.13
July 62.50 23.07 391.17 23.74 0.00 23.74
August 124.67 23.14 364.83 23.70 0.00 23.70
September 522.33 22.63 65.50 22.77 0.00 22.77
October 728.00 22.06 0.00 22.06 0.00 22.06
November 720.00 21.12 48.00 21.12 48.00 21.11
December 744.00 21.01 135.17 21.01 135.17 21.01
             
Annual Sum or Average 6898.00 21.61 1800.00 21.79 862.17 21.72
Minimum of Months 62.50 21.01 0.00 21.00 0.00 21.00
Maximum of Months 744.00 23.14 391.17 23.74 318.33 23.74



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.85495 28.81650 -0.0269 5.20200
February 672.00000 22.40427 25.23653 -0.1641 5.73466
March 744.00000 22.01377 34.79812 -0.2023 6.03534
April 720.00000 21.78738 41.43073 -0.2198 6.21319
May 744.00000 21.62978 50.32649 -1.3524 43.11460
June 720.00000 22.08623 60.46737 -1.1228 31.81555
July 744.00000 22.53195 62.93495 -0.9420 23.94982
August 744.00000 23.02723 58.48943 -0.7885 18.34379
September 720.00000 23.55049 52.59713 -0.6367 13.79873
October 744.00000 23.78753 43.33274 0.31694 7.34379
November 720.00000 23.76398 33.52142 0.24096 6.34286
December 744.00000 23.48369 28.05814 0.12857 5.47636
           
Annual Sum or Average 8760.00000 22.74564 43.44266 -0.3989 14.51813
Minimum of Months 672.00000 21.62978 25.23653 -1.3524 5.20200
Maximum of Months 744.00000 23.78753 62.93495 0.31694 43.11460



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.15030 29.40200 -0.5042 11.09317
February 672.00000 21.24211 24.80066 -0.4781 10.82634
March 744.00000 21.35246 34.23417 -0.3408 8.61799
April 720.00000 21.47582 40.33622 -0.2409 7.68073
May 744.00000 21.67025 48.60673 -1.1929 36.41103
June 720.00000 22.44863 57.72500 -0.8086 20.28400
July 744.00000 22.93516 60.10300 -0.5952 13.60205
August 744.00000 23.21306 56.23959 -0.4981 11.79746
September 720.00000 22.52751 53.82995 -0.7963 21.72579
October 744.00000 22.32234 44.89432 0.07754 7.69185
November 720.00000 21.33145 36.12306 -0.3364 8.57405
December 744.00000 21.22504 29.37677 -0.4536 10.27872
           
Annual Sum or Average 8760.00000 21.91290 43.07781 -0.5139 14.06941
Minimum of Months 672.00000 21.15030 24.80066 -1.1929 7.68073
Maximum of Months 744.00000 23.21306 60.10300 0.07754 36.41103



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.44716 31.14744 -0.3523 7.96500
February 672.00000 21.54443 26.61131 -0.3514 7.92654
March 744.00000 21.96286 35.35168 -0.1833 6.13551
April 720.00000 22.31472 40.79665 -0.0546 5.80375
May 744.00000 22.75679 48.01981 -0.9059 23.14700
June 720.00000 23.34748 57.09927 -0.6179 13.59068
July 744.00000 23.55750 60.10867 -0.5116 10.81514
August 744.00000 23.66309 56.87892 -0.4883 10.29410
September 720.00000 23.31854 53.70754 -0.6510 14.73907
October 744.00000 23.08307 45.45067 0.18495 6.37253
November 720.00000 22.03941 36.99273 -0.1532 6.08811
December 744.00000 21.66799 30.94347 -0.2916 7.07265
           
Annual Sum or Average 8760.00000 22.56477 43.69294 -0.3647 10.01220
Minimum of Months 672.00000 21.44716 26.61131 -0.9059 5.80375
Maximum of Months 744.00000 23.66309 60.10867 0.18495 23.14700



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.63846 24.89018 0.48207 12.94290
February 672.00000 22.65051 20.76651 0.46080 12.50343
March 744.00000 22.72019 29.40645 0.56756 14.79210
April 720.00000 22.75089 35.28021 0.63767 16.55662
May 744.00000 22.78985 43.22593 -0.0111 11.00247
June 720.00000 22.81253 54.04256 0.10876 11.11871
July 744.00000 22.81072 57.85623 0.15230 11.07440
August 744.00000 22.81491 54.95028 0.14498 11.20034
September 720.00000 22.82263 50.47099 0.07619 10.97163
October 744.00000 22.81376 41.48868 0.72060 18.93071
November 720.00000 22.75386 31.10084 0.58919 15.26148
December 744.00000 22.68848 24.89870 0.50744 13.29465
           
Annual Sum or Average 8760.00000 22.75611 39.14112 0.36914 13.30880
Minimum of Months 672.00000 22.63846 20.76651 -0.0111 10.97163
Maximum of Months 744.00000 22.82263 57.85623 0.72060 18.93071



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.63352 34.04535 -0.2821 7.67808
February 672.00000 21.84490 29.43627 -0.2312 7.31183
March 744.00000 22.18583 38.25994 -0.0563 6.28489
April 720.00000 22.37518 43.88492 0.04875 6.50690
May 744.00000 22.69880 51.46665 -0.7760 19.06254
June 720.00000 23.18990 60.79531 -0.4870 10.83020
July 744.00000 23.44819 63.54493 -0.3414 7.99879
August 744.00000 23.65350 59.95373 -0.2631 7.11440
September 720.00000 23.33661 56.79998 -0.4438 11.00618
October 744.00000 23.31401 48.04794 0.38408 9.54794
November 720.00000 22.17410 39.90020 -0.0479 6.40762
December 744.00000 21.85730 33.77551 -0.2025 7.01184
           
Annual Sum or Average 8760.00000 22.64783 46.76039 -0.2247 8.91209
Minimum of Months 672.00000 21.63352 29.43627 -0.7760 6.28489
Maximum of Months 744.00000 23.65350 63.54493 0.38408 19.06254



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.01348 33.18440 -0.1863 6.31632
February 672.00000 22.13988 28.75020 -0.1765 6.18003
March 744.00000 22.50792 37.33144 -0.0172 5.55368
April 720.00000 22.76347 42.75058 0.09263 5.95404
May 744.00000 23.11135 49.98674 -0.7282 17.06536
June 720.00000 23.47926 59.26671 -0.5044 10.91990
July 744.00000 23.60531 62.32405 -0.4204 9.04590
August 744.00000 23.69584 59.13992 -0.4002 8.59795
September 720.00000 23.54440 55.65888 -0.5037 10.94390
October 744.00000 23.45909 47.35080 0.32700 7.81446
November 720.00000 22.62412 38.80790 0.02463 5.73613
December 744.00000 22.26813 32.90802 -0.1155 5.81499
           
Annual Sum or Average 8760.00000 22.93904 45.72196 -0.2176 8.34556
Minimum of Months 672.00000 22.01348 28.75020 -0.7282 5.55368
Maximum of Months 744.00000 23.69584 62.32405 0.32700 17.06536



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.84119 45.31844 -0.5717 12.45666
February 672.00000 20.97327 40.59249 -0.5497 12.08353
March 744.00000 21.24516 48.08850 -0.3724 8.72104
April 720.00000 21.41968 51.64978 -0.2569 7.41731
May 744.00000 21.63333 54.71278 -1.2352 38.29339
June 720.00000 21.72796 55.42137 -1.0947 31.86489
July 744.00000 21.74455 54.21492 -1.0612 30.43619
August 744.00000 21.74665 52.77817 -1.0483 30.02390
September 720.00000 21.69765 55.41936 -1.1450 34.23407
October 744.00000 21.63260 52.42777 -0.1328 6.52138
November 720.00000 21.17681 50.25756 -0.3981 9.02312
December 744.00000 20.94955 44.92749 -0.5289 11.43027
           
Annual Sum or Average 8760.00000 21.40137 50.53573 -0.7005 19.42161
Minimum of Months 672.00000 20.84119 40.59249 -1.2352 6.52138
Maximum of Months 744.00000 21.74665 55.42137 -0.1328 38.29339



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.64097 45.81422 -0.6396 14.08199
February 672.00000 20.69350 41.21777 -0.6461 14.28711
March 744.00000 21.04502 48.60227 -0.4455 9.75464
April 720.00000 21.45407 51.80593 -0.2700 7.78886
May 744.00000 22.11388 54.02327 -1.1117 34.33289
June 720.00000 22.69696 54.87784 -0.8162 23.64002
July 744.00000 22.20498 54.88475 -0.9300 25.97962
August 744.00000 22.14211 53.36251 -0.9554 26.60397
September 720.00000 22.34960 55.85073 -0.9862 28.57101
October 744.00000 21.83227 53.81926 -0.1258 6.96389
November 720.00000 20.95688 50.94487 -0.4746 10.27194
December 744.00000 20.69512 45.58151 -0.6123 13.20551
           
Annual Sum or Average 8760.00000 21.57273 50.95123 -0.6683 17.99121
Minimum of Months 672.00000 20.64097 41.21777 -1.1117 6.96389
Maximum of Months 744.00000 22.69696 55.85073 -0.1258 34.33289



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.94732 41.20523 -0.5205 10.92646
February 672.00000 20.93764 36.82140 -0.5504 11.55916
March 744.00000 21.18382 44.51890 -0.4084 8.65598
April 720.00000 21.44341 48.12457 -0.2907 7.16218
May 744.00000 21.88115 51.05234 -1.2495 38.63852
June 720.00000 22.31654 56.88914 -1.0219 28.87661
July 744.00000 22.09082 56.94378 -1.0778 31.18905
August 744.00000 22.00163 55.17409 -1.1286 33.10737
September 720.00000 22.11530 55.03551 -1.1336 33.37451
October 744.00000 21.61894 51.59232 -0.2127 6.60801
November 720.00000 21.18853 46.48678 -0.3943 8.47279
December 744.00000 21.00263 40.98935 -0.5006 10.33173
           
Annual Sum or Average 8760.00000 21.56352 48.80229 -0.7087 19.13263
Minimum of Months 672.00000 20.93764 36.82140 -1.2495 6.60801
Maximum of Months 744.00000 22.31654 56.94378 -0.2127 38.63852



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.83957 45.31943 -0.5698 12.33722
February 672.00000 21.00043 40.54625 -0.5398 11.77865
March 744.00000 21.29734 48.02194 -0.3650 8.65161
April 720.00000 21.47539 51.33206 -0.2433 7.37400
May 744.00000 21.65995 54.50777 -1.2217 37.72247
June 720.00000 21.73758 55.71823 -1.1000 32.08000
July 744.00000 21.75021 54.25090 -1.0609 30.43516
August 744.00000 21.75440 52.78947 -1.0460 29.92784
September 720.00000 21.71316 55.30904 -1.1375 33.91739
October 744.00000 21.66095 52.52017 -0.1282 6.50761
November 720.00000 21.21649 50.01442 -0.3815 8.80340
December 744.00000 20.95395 44.94330 -0.5235 11.27632
           
Annual Sum or Average 8760.00000 21.42383 50.49164 -0.6941 19.28124
Minimum of Months 672.00000 20.83957 40.54625 -1.2217 6.50761
Maximum of Months 744.00000 21.75440 55.71823 -0.1282 37.72247



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.63451 45.81432 -0.6390 14.06733
February 672.00000 20.69754 41.19814 -0.6409 14.09492
March 744.00000 21.07405 48.53123 -0.4432 9.54644
April 720.00000 21.48974 51.44904 -0.2612 7.52875
May 744.00000 22.08216 53.90832 -1.1150 33.96144
June 720.00000 22.58123 55.75326 -0.8554 23.92973
July 744.00000 22.25706 54.93583 -0.9154 26.01520
August 744.00000 22.22842 53.38103 -0.9293 26.41048
September 720.00000 22.34417 55.86155 -0.9836 28.34331
October 744.00000 21.80212 53.78236 -0.1364 6.67777
November 720.00000 20.99226 50.73172 -0.4579 9.95516
December 744.00000 20.68841 45.56714 -0.6094 13.15002
           
Annual Sum or Average 8760.00000 21.57677 50.96149 -0.6660 17.84125
Minimum of Months 672.00000 20.63451 41.19814 -1.1150 6.67777
Maximum of Months 744.00000 22.58123 55.86155 -0.1364 33.96144



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.72997 46.66207 -0.6320 14.05341
February 672.00000 20.86114 41.63791 -0.6116 13.70017
March 744.00000 21.16130 49.49957 -0.4107 9.54326
April 720.00000 21.37096 53.01943 -0.2770 7.89321
May 744.00000 21.61883 55.94790 -1.2387 38.70160
June 720.00000 21.72333 56.49713 -1.0867 31.72760
July 744.00000 21.74500 55.07927 -1.0470 30.04767
August 744.00000 21.74600 53.61511 -1.0370 29.81563
September 720.00000 21.68420 56.80050 -1.1496 34.66698
October 744.00000 21.59496 53.96286 -0.1518 6.83470
November 720.00000 21.06912 51.88156 -0.4460 10.02454
December 744.00000 20.83331 46.22254 -0.5879 12.87913
           
Annual Sum or Average 8760.00000 21.34754 51.78764 -0.7237 20.03045
Minimum of Months 672.00000 20.72997 41.63791 -1.2387 6.83470
Maximum of Months 744.00000 21.74600 56.80050 -0.1518 38.70160



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.55292 47.14763 -0.6966 15.77449
February 672.00000 20.60670 42.25336 -0.7049 16.02712
March 744.00000 20.95225 50.07872 -0.4879 10.76841
April 720.00000 21.42214 53.17019 -0.2868 8.36199
May 744.00000 22.16121 55.04283 -1.0927 34.57172
June 720.00000 22.76323 55.26511 -0.7802 23.59192
July 744.00000 22.20727 55.52418 -0.9120 25.61514
August 744.00000 22.12729 53.96811 -0.9468 26.51251
September 720.00000 22.35309 56.91593 -0.9823 29.07124
October 744.00000 21.78115 55.33888 -0.1489 7.47202
November 720.00000 20.83971 52.66528 -0.5269 11.50436
December 744.00000 20.58741 46.91875 -0.6715 14.88547
           
Annual Sum or Average 8760.00000 21.53366 52.07721 -0.6868 18.70750
Minimum of Months 672.00000 20.55292 42.25336 -1.0927 7.47202
Maximum of Months 744.00000 22.76323 56.91593 -0.1489 34.57172



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.13395 45.18918 -0.4673 10.70411
February 672.00000 21.31013 40.73770 -0.4218 10.11991
March 744.00000 21.40000 48.01726 -0.3155 8.26012
April 720.00000 21.48849 51.19607 -0.2446 7.41628
May 744.00000 21.63245 54.64466 -1.2712 40.08709
June 720.00000 21.71109 57.34760 -1.1498 34.34057
July 744.00000 21.74177 55.62014 -1.1045 32.35297
August 744.00000 21.74276 54.16673 -1.0833 31.73209
September 720.00000 21.70505 55.71715 -1.1477 34.67470
October 744.00000 21.68006 52.15535 -0.0990 6.65910
November 720.00000 21.45681 49.45594 -0.2934 7.90640
December 744.00000 21.24749 44.75195 -0.4140 9.83682
           
Annual Sum or Average 8760.00000 21.52181 50.80291 -0.6692 19.56739
Minimum of Months 672.00000 21.13395 40.73770 -1.2712 6.65910
Maximum of Months 744.00000 21.74276 57.34760 -0.0990 40.08709



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.11832 33.86716 0.08928 6.12317
February 672.00000 23.11261 29.90014 0.05996 5.96552
March 744.00000 23.43263 37.62740 0.22844 6.69150
April 720.00000 23.62488 42.46160 0.34223 7.93703
May 744.00000 23.81342 49.11610 -0.3997 8.71775
June 720.00000 23.92144 58.35643 -0.2381 6.34249
July 744.00000 23.95913 61.58211 -0.1746 5.67297
August 744.00000 23.93890 59.00327 -0.2047 5.97208
September 720.00000 23.86109 55.58696 -0.3110 7.34675
October 744.00000 23.70225 48.04523 0.41938 9.24552
November 720.00000 23.41627 39.19793 0.23476 6.83063
December 744.00000 23.25236 33.68036 0.13114 6.07404
           
Annual Sum or Average 8760.00000 23.59888 45.79688 0.01447 6.91548
Minimum of Months 672.00000 23.11261 29.90014 -0.3997 5.67297
Maximum of Months 744.00000 23.95913 61.58211 0.41938 9.24552



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.36857 32.85774 0.18905 6.49930
February 672.00000 23.36277 28.96583 0.15922 6.23038
March 744.00000 23.62468 36.53557 0.31352 7.48283
April 720.00000 23.77734 41.43556 0.41614 8.97174
May 744.00000 23.89977 48.23549 -0.3202 7.39504
June 720.00000 23.95722 57.73037 -0.1846 5.83533
July 744.00000 23.97884 61.05794 -0.1300 5.37701
August 744.00000 23.96413 58.47237 -0.1589 5.60240
September 720.00000 23.91914 54.86300 -0.2482 6.52082
October 744.00000 23.81640 47.14244 0.47973 10.27591
November 720.00000 23.60971 38.11990 0.32010 7.63754
December 744.00000 23.47181 32.62596 0.22330 6.55938
           
Annual Sum or Average 8760.00000 23.73126 44.93222 0.08781 7.03661
Minimum of Months 672.00000 23.36277 28.96583 -0.3202 5.37701
Maximum of Months 744.00000 23.97884 61.05794 0.47973 10.27591



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.55961 31.65231 0.84487 23.45624
February 672.00000 23.54850 27.83637 0.82209 22.72800
March 744.00000 23.64450 35.44504 0.95220 27.08990
April 720.00000 23.71232 40.57112 1.04867 30.87506
May 744.00000 23.79167 47.67019 0.59232 17.75428
June 720.00000 23.87752 57.27862 0.74750 21.18368
July 744.00000 23.90159 60.60109 0.81458 22.89528
August 744.00000 23.91360 57.94384 0.80625 22.82000
September 720.00000 23.84334 54.22079 0.68329 19.48326
October 744.00000 23.75886 46.23150 1.12507 34.09390
November 720.00000 23.64920 37.02304 0.95839 27.26884
December 744.00000 23.59574 31.49259 0.87036 23.96347
           
Annual Sum or Average 8760.00000 23.73414 44.09413 0.85570 24.47938
Minimum of Months 672.00000 23.54850 27.83637 0.59232 17.75428
Maximum of Months 744.00000 23.91360 60.60109 1.12507 34.09390



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00065 28.68730 -0.5265 10.92292
February 672.00000 21.00015 24.11354 -0.5531 11.47865
March 744.00000 21.04660 33.80239 -0.4548 9.43795
April 720.00000 21.37417 39.59900 -0.3265 7.66256
May 744.00000 22.07577 46.49022 -1.1981 35.59285
June 720.00000 23.03717 55.06694 -0.8008 18.88358
July 744.00000 23.45302 57.79608 -0.6326 13.51352
August 744.00000 23.49822 54.67014 -0.6369 13.69834
September 720.00000 22.88577 51.90765 -0.8748 21.77952
October 744.00000 22.18766 44.38185 -0.0835 5.74437
November 720.00000 21.21704 35.47292 -0.3972 8.56165
December 744.00000 21.00168 28.82290 -0.5081 10.43967
           
Annual Sum or Average 8760.00000 21.98795 41.83768 -0.5828 13.99414
Minimum of Months 672.00000 21.00015 24.11354 -1.1981 5.74437
Maximum of Months 744.00000 23.49822 57.79608 -0.0835 35.59285



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00163 32.62512 -0.5076 10.48073
February 672.00000 21.00298 28.04585 -0.5265 10.85277
March 744.00000 21.08952 37.67236 -0.4307 8.97662
April 720.00000 21.48616 43.33530 -0.2930 7.20345
May 744.00000 22.18371 50.23946 -1.1667 34.16598
June 720.00000 23.18714 58.59202 -0.7546 17.20398
July 744.00000 23.48763 61.50181 -0.6261 13.28710
August 744.00000 23.63024 58.27253 -0.5967 12.55351
September 720.00000 23.02441 55.55025 -0.8317 20.45400
October 744.00000 22.38869 47.95176 -0.0306 5.50539
November 720.00000 21.19975 39.43925 -0.3961 8.50543
December 744.00000 21.00536 32.72026 -0.4974 10.20996
           
Annual Sum or Average 8760.00000 22.06410 45.59800 -0.5549 13.30258
Minimum of Months 672.00000 21.00163 28.04585 -1.1667 5.50539
Maximum of Months 744.00000 23.63024 61.50181 -0.0306 34.16598



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00530 29.70312 -0.5143 10.66069
February 672.00000 21.01678 25.14908 -0.5327 11.02495
March 744.00000 21.11861 34.67955 -0.4159 8.78404
April 720.00000 21.49521 40.31277 -0.2711 7.16040
May 744.00000 22.21007 47.17139 -1.1069 31.70285
June 720.00000 23.22421 55.30060 -0.6823 15.32046
July 744.00000 23.62812 57.78616 -0.5126 10.71022
August 744.00000 23.65367 54.89167 -0.5208 10.99275
September 720.00000 22.90659 52.72213 -0.8154 20.19682
October 744.00000 22.09064 45.49001 -0.0751 6.04954
November 720.00000 21.12320 36.61572 -0.4052 8.64628
December 744.00000 21.01213 29.79247 -0.4973 10.21668
           
Annual Sum or Average 8760.00000 22.04718 42.56892 -0.5289 12.63298
Minimum of Months 672.00000 21.00530 25.14908 -1.1069 6.04954
Maximum of Months 744.00000 23.65367 57.78616 -0.0751 31.70285



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.01610 28.17293 -0.5135 10.64705
February 672.00000 21.01379 23.61696 -0.5413 11.21264
March 744.00000 21.11999 33.17014 -0.4339 9.08433
April 720.00000 21.50218 38.82402 -0.2958 7.30930
May 744.00000 22.24037 45.54043 -1.1435 33.04470
June 720.00000 23.18645 54.05343 -0.7494 17.24241
July 744.00000 23.56776 56.83743 -0.5913 12.48024
August 744.00000 23.60932 53.74172 -0.5963 12.65300
September 720.00000 23.04750 50.89358 -0.8198 19.83612
October 744.00000 22.35861 43.46625 -0.0445 5.62354
November 720.00000 21.33317 34.73099 -0.3674 8.15404
December 744.00000 21.02935 28.29872 -0.4939 10.14785
           
Annual Sum or Average 8760.00000 22.09220 41.04765 -0.5492 13.13510
Minimum of Months 672.00000 21.01379 23.61696 -1.1435 5.62354
Maximum of Months 744.00000 23.60932 56.83743 -0.0445 33.04470



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.119572E+10 14286.51 17-JAN-16:03 134.58 0.381009E+10 0.00 0.500581E+10 0.58 3.19 01-JAN-19:04 0.00 0.00
February 0.236615E+10 19103.92 20-FEB-16:02 187.02 0.753959E+10 0.00 0.990575E+10 0.89 3.19 02-FEB-12:10 0.00 0.00
March 0.832625E+10 72998.65 27-MAR-15:03 385.53 0.259449E+11 0.00 0.342712E+11 1.64 3.28 27-MAR-15:03 0.00 0.00
April 0.286933E+11 106735.30 07-APR-15:05 561.85 0.860042E+11 0.00 0.114697E+12 2.43 3.45 08-APR-15:05 0.00 0.00
May 0.764897E+11 117333.77 31-MAY-15:05 738.96 0.227628E+12 0.00 0.304117E+12 3.02 3.85 31-MAY-18:03 0.00 0.00
June 0.209333E+12 186801.02 19-JUN-18:03 720.00 0.704818E+12 0.00 0.914151E+12 3.28 4.23 21-JUN-21:53 0.00 0.00
July 0.305102E+12 182016.72 20-JUL-18:03 744.00 0.107245E+13 0.00 0.137755E+13 3.50 4.24 14-JUL-21:52 0.00 0.00
August 0.273323E+12 197557.47 16-AUG-15:03 744.00 0.909214E+12 0.00 0.118254E+13 3.27 4.10 10-AUG-21:52 0.00 0.00
September 0.159053E+12 158617.61 07-SEP-20:00 720.00 0.518037E+12 0.00 0.677091E+12 3.15 4.17 21-SEP-21:53 0.00 0.00
October 0.744686E+11 118548.26 03-OCT-15:03 717.67 0.233342E+12 0.00 0.307811E+12 3.02 3.98 24-OCT-15:03 0.00 0.00
November 0.940008E+10 59772.01 04-NOV-15:03 405.82 0.294693E+11 0.00 0.388694E+11 1.79 3.19 01-NOV-06:00 0.00 0.00
December 0.286938E+10 14615.99 18-DEC-11:00 198.42 0.914310E+10 0.00 0.120125E+11 0.85 3.19 02-DEC-18:00 0.00 0.00
                         
Annual Sum or Average 0.115062E+13     6257.84 0.382740E+13 0.00 0.497802E+13 2.29     0.00 0.00
Minimum of Months 0.119572E+10 14286.51   134.58 0.381009E+10 0.00 0.500581E+10 0.58 3.19   0.00 0.00
Maximum of Months 0.305102E+12 197557.47   744.00 0.107245E+13 0.00 0.137755E+13 3.50 4.24   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.131069E+12 0.00 744.00 228682.20 02-JAN-09:01 0.00 48.47 80.87 0.35 0.00 0.11 0.50 02-JAN-09:01
February 0.112178E+12 0.00 672.00 236148.43 06-FEB-09:01 0.00 50.28 81.06 0.33 0.00 0.10 0.51 06-FEB-09:01
March 0.599871E+11 0.00 727.14 173918.13 17-MAR-08:61 0.00 49.43 79.12 0.17 0.00 0.05 0.38 17-MAR-08:61
April 0.678172E+11 0.00 584.89 157549.42 02-APR-18:05 0.00 38.64 70.38 0.15 0.00 0.06 0.34 02-APR-18:05
May 0.288797E+11 0.00 363.66 99685.10 03-MAY-15:05 0.00 29.12 53.38 0.05 0.00 0.02 0.22 03-MAY-15:05
June 0.706758E+09 0.00 56.40 24434.81 06-JUN-15:07 0.00 34.63 38.32 0.00 0.00 0.00 0.05 06-JUN-15:07
July 97628851.95 0.00 30.74 26237.59 18-JUL-08:05 0.00 39.45 41.09 0.00 0.00 0.00 0.06 18-JUL-08:05
August 0.303998E+09 0.00 35.24 25162.84 25-AUG-21:57 0.00 37.31 39.31 0.00 0.00 0.00 0.05 25-AUG-21:57
September 0.715021E+10 0.00 146.49 72685.64 24-SEP-05:50 0.00 31.33 41.18 0.01 0.00 0.01 0.16 24-SEP-05:50
October 0.443445E+11 0.00 415.06 133298.01 28-OCT-18:05 0.00 33.25 58.05 0.08 0.00 0.04 0.29 28-OCT-18:05
November 0.889696E+11 0.00 693.53 159079.27 28-NOV-16:01 0.00 44.56 78.23 0.22 0.00 0.07 0.35 28-NOV-16:01
December 0.803020E+11 0.00 744.00 186335.52 31-DEC-19:01 0.00 51.91 80.52 0.25 0.00 0.07 0.41 31-DEC-19:01
                           
Annual Sum or Average 0.621807E+12 0.00 5213.15     0.00 40.66 61.69 0.13 0.00 0.04    
Minimum of Months 97628851.95 0.00 30.74 24434.81   0.00 29.12 38.32 0.00 0.00 0.00 0.05  
Maximum of Months 0.131069E+12 0.00 744.00 236148.43   0.00 51.91 81.06 0.35 0.00 0.11 0.51  



Table of Contents

Report: DXReportMonthly

For: SWHSYS1 HPWH DXCOIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.539075E+11 0.00 472.34 0.539075E+11 0.00 0.00 1.00 01-JAN-00:15 0.00 01-JAN-00:03 37176.38 31-JAN-04:20 37176.38 31-JAN-06:30 0.00 01-JAN-07:30 0.00 0.00 01-JAN-00:03
February 0.477317E+11 0.00 443.01 0.477317E+11 -0.0 0.00 1.00 01-FEB-00:07 0.00 01-FEB-00:03 34239.09 09-FEB-00:07 34239.09 09-FEB-07:15 0.00 10-FEB-19:01 0.00 0.00 01-FEB-00:03
March 0.558717E+11 0.00 442.51 0.558717E+11 0.00 0.00 1.00 01-MAR-00:20 0.00 01-MAR-00:03 50111.17 31-MAR-23:20 50111.17 31-MAR-23:20 0.00 01-MAR-18:07 0.00 0.00 01-MAR-00:03
April 0.531563E+11 0.00 400.83 0.531535E+11 2822619.74 0.00 1.00 01-APR-05:15 0.00 01-APR-00:10 50127.34 01-APR-05:15 50127.34 01-APR-18:05 3209.48 30-APR-23:20 0.00 0.00 01-APR-00:10
May 0.524041E+11 0.00 382.98 0.492629E+11 0.314118E+10 0.00 1.00 01-MAY-05:13 0.00 01-MAY-00:05 63500.04 31-MAY-23:07 52824.89 01-MAY-15:07 18451.89 31-MAY-23:07 0.00 0.00 01-MAY-00:05
June 0.483817E+11 0.00 345.95 0.343300E+11 0.140518E+11 0.00 1.00 01-JUN-04:07 0.00 01-JUN-00:05 63461.80 01-JUN-04:07 45157.55 16-JUN-07:13 19002.17 01-JUN-13:37 0.00 0.00 01-JUN-00:05
July 0.477735E+11 0.00 357.31 0.272215E+11 0.205520E+11 0.00 1.00 01-JUL-05:17 0.00 01-JUL-00:10 67440.67 01-JUL-05:17 38750.63 04-JUL-09:17 29231.81 26-JUL-15:07 0.00 0.00 01-JUL-00:10
August 0.467088E+11 0.00 355.17 0.337453E+11 0.129635E+11 0.00 1.00 01-AUG-05:13 0.00 01-AUG-00:05 64949.78 31-AUG-05:13 47243.17 03-AUG-07:15 18479.41 12-AUG-15:07 0.00 0.00 01-AUG-00:05
September 0.457848E+11 0.00 345.64 0.373479E+11 0.843690E+10 0.00 1.00 01-SEP-04:07 0.00 01-SEP-00:05 59809.37 30-SEP-06:30 48921.15 28-SEP-18:35 11499.11 17-SEP-15:07 0.00 0.00 01-SEP-00:05
October 0.491227E+11 0.00 381.16 0.444038E+11 0.471896E+10 0.00 1.00 01-OCT-05:07 0.00 01-OCT-00:20 53535.79 31-OCT-06:15 48360.93 21-OCT-07:12 5716.19 25-OCT-17:13 0.00 0.00 01-OCT-00:10
November 0.490343E+11 0.00 406.78 0.490343E+11 -0.0 0.00 1.00 01-NOV-05:13 0.00 01-NOV-00:05 44828.99 30-NOV-06:04 44828.99 30-NOV-06:04 0.00 27-NOV-21:10 0.00 0.00 01-NOV-00:05
December 0.523333E+11 0.00 451.91 0.523333E+11 -0.0 0.00 1.00 01-DEC-00:07 0.00 01-DEC-00:03 39321.35 31-DEC-20:50 39321.35 31-DEC-06:50 0.00 30-DEC-00:20 0.00 0.00 01-DEC-00:03
                                       
Annual Sum or Average 0.602210E+12 0.00 4785.62 0.538343E+12 0.638671E+11 0.00                     0.00    
Minimum of Months 0.457848E+11 0.00 345.64 0.272215E+11 -0.0 0.00 1.00   0.00   34239.09   34239.09   0.00   0.00 0.00  
Maximum of Months 0.558717E+11 0.00 472.34 0.558717E+11 0.205520E+11 0.00 1.00   0.00   67440.67   52824.89   29231.81   0.00 0.00  



Table of Contents

Report: DXReportMonthly

For: SWHSYSLAUNDRY HPWH DXCOIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.372806E+11 0.00 384.66 0.372806E+11 0.00 0.00 1.00 01-JAN-17:10 0.00 01-JAN-00:03 47038.12 31-JAN-23:00 47038.12 31-JAN-17:10 0.00 02-JAN-19:40 0.00 0.00 01-JAN-00:03
February 0.311321E+11 0.00 347.21 0.311321E+11 -0.0 0.00 1.00 01-FEB-17:10 0.00 01-FEB-00:07 43318.83 09-FEB-22:50 43318.83 09-FEB-22:30 0.00 21-FEB-20:20 0.00 0.00 01-FEB-00:03
March 0.433818E+11 0.00 382.43 0.433818E+11 0.00 0.00 1.00 01-MAR-17:10 0.00 01-MAR-00:07 54906.72 01-MAR-17:10 54906.72 01-MAR-17:40 0.00 03-MAR-18:00 0.00 0.00 01-MAR-00:03
April 0.482845E+11 0.00 368.84 0.482839E+11 545241.35 0.00 1.00 01-APR-16:05 0.00 01-APR-00:10 63437.10 01-APR-17:50 63437.10 01-APR-17:50 2565.82 30-APR-23:03 0.00 0.00 01-APR-00:10
May 0.557002E+11 0.00 348.04 0.523841E+11 0.331605E+10 0.00 1.00 01-MAY-16:10 0.00 01-MAY-00:05 71032.16 01-MAY-16:10 66874.12 01-MAY-16:10 12640.80 31-MAY-23:03 0.00 0.00 01-MAY-00:05
June 0.609469E+11 0.00 332.27 0.432314E+11 0.177155E+11 0.00 1.00 01-JUN-16:10 0.00 01-JUN-00:05 80321.66 01-JUN-20:45 57097.29 15-JUN-23:00 24037.55 01-JUN-16:10 0.00 0.00 01-JUN-00:05
July 0.671350E+11 0.00 348.60 0.382329E+11 0.289022E+11 0.00 1.00 01-JUL-16:10 0.00 01-JUL-00:20 85359.86 01-JUL-16:20 49056.51 04-JUL-20:20 36989.29 26-JUL-20:00 0.00 0.00 01-JUL-00:10
August 0.648274E+11 0.00 345.54 0.468133E+11 0.180141E+11 0.00 1.00 01-AUG-16:10 0.00 01-AUG-00:05 82205.79 31-AUG-18:50 59780.47 07-AUG-20:20 23374.72 12-AUG-16:10 0.00 0.00 01-AUG-00:05
September 0.575974E+11 0.00 334.13 0.469975E+11 0.105999E+11 0.00 1.00 01-SEP-16:10 0.00 01-SEP-00:05 75696.82 30-SEP-16:05 61952.13 28-SEP-19:20 14527.61 17-SEP-16:10 0.00 0.00 01-SEP-00:05
October 0.531736E+11 0.00 353.89 0.480779E+11 0.509571E+10 0.00 1.00 01-OCT-16:10 0.00 01-OCT-00:20 67752.99 31-OCT-21:10 61167.12 27-OCT-21:00 7217.10 25-OCT-17:13 0.00 0.00 01-OCT-00:10
November 0.431527E+11 0.00 369.73 0.431527E+11 -0.0 0.00 1.00 01-NOV-16:10 0.00 01-NOV-00:05 56728.13 30-NOV-17:20 56728.13 30-NOV-19:40 0.00 05-NOV-20:50 0.00 0.00 01-NOV-00:05
December 0.392597E+11 0.00 385.15 0.392597E+11 -0.0 0.00 1.00 01-DEC-17:10 0.00 01-DEC-00:07 49754.16 31-DEC-18:12 49754.16 31-DEC-24:00 0.00 01-DEC-19:00 0.00 0.00 01-DEC-00:03
                                       
Annual Sum or Average 0.601872E+12 0.00 4300.50 0.518228E+12 0.836441E+11 0.00                     0.00    
Minimum of Months 0.311321E+11 0.00 332.27 0.311321E+11 -0.0 0.00 1.00   0.00   43318.83   43318.83   0.00   0.00 0.00  
Maximum of Months 0.671350E+11 0.00 385.15 0.523841E+11 0.289022E+11 0.00 1.00   0.00   85359.86   66874.12   36989.29   0.00 0.00  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 0.00 0.00
March 0.329359E+10 0.00 24.00 0.325708E+10 0.00 0.00 0.00 0.00 128470.33 27-MAR-16:00 128470.33 27-MAR-16:00 0.00 0.00 0.00
April 0.339278E+11 0.00 155.64 0.336599E+11 0.00 0.00 0.00 0.00 208088.51 09-APR-10:50 200530.17 07-APR-17:00 0.00 0.00 0.00
May 0.125500E+12 0.00 467.03 0.107682E+12 0.00 0.00 0.00 0.00 297829.63 31-MAY-17:17 216421.43 28-MAY-14:27 0.00 0.00 0.00
June 0.520638E+12 0.00 707.50 0.300692E+12 0.00 0.00 0.00 0.00 504405.71 24-JUN-17:17 283459.21 22-JUN-18:08 0.00 0.00 0.00
July 0.826657E+12 0.00 744.00 0.431939E+12 0.00 0.00 0.00 0.00 528638.08 05-JUL-19:10 253507.57 11-JUL-15:07 0.00 0.00 0.00
August 0.668323E+12 0.00 744.00 0.425152E+12 0.00 0.00 0.00 0.00 586630.65 11-AUG-21:53 332242.76 24-AUG-18:30 0.00 0.00 0.00
September 0.360538E+12 0.00 642.17 0.242148E+12 0.00 0.00 0.00 0.00 536215.48 13-SEP-21:00 276090.45 01-SEP-18:27 0.00 0.00 0.00
October 0.123645E+12 0.00 348.00 0.787861E+11 0.00 0.00 0.00 0.00 278389.69 05-OCT-19:10 175295.57 25-OCT-10:33 0.00 0.00 0.00
November 0.332701E+10 0.00 34.83 0.303487E+10 0.00 0.00 0.00 0.00 62625.09 04-NOV-10:45 62625.09 04-NOV-10:45 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.266585E+13 0.00 3867.17 0.162635E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.826657E+12 0.00 744.00 0.431939E+12 0.00 0.00 0.00 0.00 586630.65   332242.76   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 0.00 0.00
March 0.274237E+09 0.00 15.00 0.236684E+09 0.00 0.00 0.00 0.00 19369.32 27-MAR-13:00 14899.81 27-MAR-16:00 0.00 0.00 0.00
April 0.217150E+10 0.00 99.83 0.212913E+10 0.00 0.00 0.00 0.00 20182.20 09-APR-10:00 17842.11 07-APR-15:02 0.00 0.00 0.00
May 0.903150E+10 0.00 325.33 0.753219E+10 0.00 0.00 0.00 0.00 31077.44 31-MAY-17:00 19489.00 30-MAY-13:00 0.00 0.00 0.00
June 0.428359E+11 0.00 557.83 0.239619E+11 0.00 0.00 0.00 0.00 46753.17 24-JUN-18:07 22015.09 19-JUN-12:20 0.00 0.00 0.00
July 0.583701E+11 0.00 589.00 0.326037E+11 0.00 0.00 0.00 0.00 47889.79 28-JUL-08:03 21002.30 07-JUL-12:20 0.00 0.00 0.00
August 0.471787E+11 0.00 589.00 0.307582E+11 0.00 0.00 0.00 0.00 42812.08 10-AUG-21:51 20975.03 24-AUG-15:02 0.00 0.00 0.00
September 0.291741E+11 0.00 496.50 0.191404E+11 0.00 0.00 0.00 0.00 46252.66 14-SEP-08:10 19566.49 01-SEP-15:02 0.00 0.00 0.00
October 0.100475E+11 0.00 251.50 0.576025E+10 0.00 0.00 0.00 0.00 30632.72 03-OCT-15:02 17302.40 04-OCT-12:15 0.00 0.00 0.00
November 0.209566E+09 0.00 19.17 0.180115E+09 0.00 0.00 0.00 0.00 7314.01 10-NOV-08:00 6401.27 04-NOV-13:00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.199293E+12 0.00 2943.17 0.122303E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.583701E+11 0.00 589.00 0.326037E+11 0.00 0.00 0.00 0.00 47889.79   22015.09   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 64008021.92 0.00 13.66 45918715.32 0.00 0.00 0.00 0.00 12307.22 20-JAN-16:02 12307.22 20-JAN-16:02 0.00 0.00 0.00
February 0.153521E+09 0.00 31.48 0.131983E+09 0.00 0.00 0.00 0.00 12306.64 17-FEB-16:02 12306.64 17-FEB-16:02 0.00 0.00 0.00
March 0.920522E+09 0.00 149.61 0.695827E+09 0.00 0.00 0.00 0.00 14298.29 27-MAR-15:02 12308.79 11-MAR-16:01 0.00 0.00 0.00
April 0.227997E+10 0.00 325.43 0.153042E+10 0.00 0.00 0.00 0.00 13399.76 09-APR-08:62 12735.39 10-APR-18:02 0.00 0.00 0.00
May 0.482789E+10 0.00 589.66 0.312487E+10 0.00 0.00 0.00 0.00 15010.67 19-MAY-18:02 13071.31 20-MAY-18:02 0.00 0.00 0.00
June 0.893195E+10 0.00 675.05 0.549767E+10 0.00 0.00 0.00 0.00 17147.21 27-JUN-08:62 13022.83 15-JUN-18:02 0.00 0.00 0.00
July 0.108408E+11 0.00 714.40 0.690828E+10 0.00 0.00 0.00 0.00 17238.94 28-JUL-08:61 13130.30 12-JUL-18:02 0.00 0.00 0.00
August 0.115105E+11 0.00 716.50 0.783713E+10 0.00 0.00 0.00 0.00 16550.83 06-AUG-08:62 13170.07 17-AUG-18:02 0.00 0.00 0.00
September 0.707456E+10 0.00 649.63 0.435295E+10 0.00 0.00 0.00 0.00 18429.45 22-SEP-18:02 12945.70 14-SEP-18:02 0.00 0.00 0.00
October 0.467878E+10 0.00 559.70 0.289275E+10 0.00 0.00 0.00 0.00 15358.74 06-OCT-08:62 12671.27 25-OCT-18:02 0.00 0.00 0.00
November 0.426031E+09 0.00 113.62 0.239759E+09 0.00 0.00 0.00 0.00 13153.85 10-NOV-16:02 11898.34 04-NOV-15:01 0.00 0.00 0.00
December 78715320.67 0.00 22.38 68580932.23 0.00 0.00 0.00 0.00 12310.17 17-DEC-16:02 12310.17 17-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.517873E+11 0.00 4561.12 0.333261E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 64008021.92 0.00 13.66 45918715.32 0.00 0.00 0.00 0.00 12306.64   11898.34   0.00 0.00 0.00
Maximum of Months 0.115105E+11 0.00 716.50 0.783713E+10 0.00 0.00 0.00 0.00 18429.45   13170.07   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 15174271.23 0.00 2.45 10870415.63 0.00 0.00 0.00 0.00 10928.86 20-JAN-16:02 10928.86 20-JAN-16:02 0.00 0.00 0.00
February 32967570.26 0.00 7.97 27810893.17 0.00 0.00 0.00 0.00 11201.20 22-FEB-16:02 11201.20 22-FEB-16:02 0.00 0.00 0.00
March 0.379900E+09 0.00 70.07 0.292778E+09 0.00 0.00 0.00 0.00 14102.19 27-MAR-15:02 11932.30 11-MAR-16:01 0.00 0.00 0.00
April 0.131100E+10 0.00 231.81 0.812394E+09 0.00 0.00 0.00 0.00 13628.12 27-APR-18:21 13215.25 09-APR-18:11 0.00 0.00 0.00
May 0.329105E+10 0.00 446.34 0.200994E+10 0.00 0.00 0.00 0.00 16073.67 31-MAY-08:51 13736.71 29-MAY-18:31 0.00 0.00 0.00
June 0.641567E+10 0.00 460.82 0.410867E+10 0.00 0.00 0.00 0.00 18083.87 27-JUN-08:51 13465.56 22-JUN-07:51 0.00 0.00 0.00
July 0.933381E+10 0.00 591.12 0.612687E+10 0.00 0.00 0.00 0.00 18608.18 23-JUL-08:21 13330.99 03-JUL-18:51 0.00 0.00 0.00
August 0.942814E+10 0.00 595.15 0.642379E+10 0.00 0.00 0.00 0.00 18677.76 12-AUG-08:61 12837.06 17-AUG-18:02 0.00 0.00 0.00
September 0.416171E+10 0.00 433.14 0.240021E+10 0.00 0.00 0.00 0.00 17218.38 14-SEP-08:51 12752.12 10-SEP-21:51 0.00 0.00 0.00
October 0.188223E+10 0.00 340.11 0.969775E+09 0.00 0.00 0.00 0.00 15041.74 05-OCT-21:51 12386.89 24-OCT-15:02 0.00 0.00 0.00
November 82711244.94 0.00 29.87 49508264.34 0.00 0.00 0.00 0.00 12961.75 10-NOV-16:02 11336.24 04-NOV-15:01 0.00 0.00 0.00
December 12636344.30 0.00 1.65 10178339.62 0.00 0.00 0.00 0.00 10980.93 17-DEC-16:02 10980.93 17-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.363470E+11 0.00 3210.48 0.232428E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 12636344.30 0.00 1.65 10178339.62 0.00 0.00 0.00 0.00 10928.86   10928.86   0.00 0.00 0.00
Maximum of Months 0.942814E+10 0.00 595.15 0.642379E+10 0.00 0.00 0.00 0.00 18677.76   13736.71   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 29177817.74 0.00 1.67 29177817.74 0.00 0.00 0.00 0.00 6195.67 31-JAN-15:00 6195.67 31-JAN-15:00 0.00 0.00 0.00
February 0.239358E+10 0.00 75.27 0.239358E+10 0.00 0.00 0.00 0.00 27817.14 20-FEB-13:30 27817.14 20-FEB-13:30 0.00 0.00 0.00
March 0.697116E+10 0.00 178.19 0.569826E+10 0.00 0.00 0.00 0.00 33958.32 28-MAR-12:30 32670.35 15-MAR-13:15 0.00 0.00 0.00
April 0.142742E+11 0.00 345.51 0.897074E+10 0.00 0.00 0.00 0.00 44584.17 07-APR-13:15 40430.26 07-APR-13:20 0.00 0.00 0.00
May 0.246644E+11 0.00 603.35 0.120522E+11 0.00 0.00 0.00 0.00 34779.66 30-MAY-12:30 27182.17 30-MAY-12:50 0.00 0.00 0.00
June 0.391544E+11 0.00 713.98 0.193201E+11 0.00 0.00 0.00 0.00 36425.96 19-JUN-12:40 29459.21 19-JUN-13:20 0.00 0.00 0.00
July 0.517813E+11 0.00 744.00 0.282616E+11 0.00 0.00 0.00 0.00 38221.24 08-JUL-12:00 32917.53 10-JUL-13:10 0.00 0.00 0.00
August 0.609320E+11 0.00 744.00 0.384272E+11 0.00 0.00 0.00 0.00 46899.33 30-AUG-13:00 41357.56 24-AUG-13:10 0.00 0.00 0.00
September 0.462527E+11 0.00 695.17 0.280961E+11 0.00 0.00 0.00 0.00 51373.91 28-SEP-12:40 43049.86 30-SEP-12:30 0.00 0.00 0.00
October 0.452908E+11 0.00 666.17 0.340191E+11 0.00 0.00 0.00 0.00 54376.20 04-OCT-12:10 50163.59 30-OCT-13:25 0.00 0.00 0.00
November 0.105538E+11 0.00 232.82 0.833222E+10 0.00 0.00 0.00 0.00 46035.96 02-NOV-12:50 46035.96 02-NOV-12:50 0.00 0.00 0.00
December 0.358407E+10 0.00 87.57 0.358407E+10 0.00 0.00 0.00 0.00 31277.11 17-DEC-13:40 31277.11 17-DEC-13:40 0.00 0.00 0.00
                               
Annual Sum or Average 0.305881E+12 0.00 5087.71 0.189184E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 29177817.74 0.00 1.67 29177817.74 0.00 0.00 0.00 0.00 6195.67   6195.67   0.00 0.00 0.00
Maximum of Months 0.609320E+11 0.00 744.00 0.384272E+11 0.00 0.00 0.00 0.00 54376.20   50163.59   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.407319E+09 0.00 33.46 0.219243E+09 0.00 0.00 0.00 0.00 63536.31 24-JAN-09:02 56105.05 23-JAN-19:02 0.00 0.00 0.00
February 0.223803E+09 0.00 21.93 0.190838E+09 0.00 0.00 0.00 0.00 59136.83 18-FEB-09:02 59136.83 18-FEB-09:02 0.00 0.00 0.00
March 0.379511E+10 0.00 198.30 0.256748E+10 0.00 0.00 0.00 0.00 69818.68 27-MAR-15:02 61833.40 03-MAR-19:02 0.00 0.00 0.00
April 0.144910E+11 0.00 383.04 0.942517E+10 0.00 0.00 0.00 0.00 71865.85 08-APR-15:02 68890.76 07-APR-15:02 0.00 0.00 0.00
May 0.316013E+11 0.00 458.46 0.223926E+11 0.00 0.00 0.00 0.00 82026.19 31-MAY-21:51 70757.90 30-MAY-08:21 0.00 0.00 0.00
June 0.455839E+11 0.00 424.48 0.316170E+11 0.00 0.00 0.00 0.00 99538.92 25-JUN-07:51 72066.13 22-JUN-07:51 0.00 0.00 0.00
July 0.634555E+11 0.00 557.27 0.438715E+11 0.00 0.00 0.00 0.00 102657.74 23-JUL-08:21 71068.72 06-JUL-18:02 0.00 0.00 0.00
August 0.575539E+11 0.00 545.57 0.397391E+11 0.00 0.00 0.00 0.00 101738.43 12-AUG-08:61 71635.08 12-AUG-15:02 0.00 0.00 0.00
September 0.334056E+11 0.00 391.06 0.221502E+11 0.00 0.00 0.00 0.00 94392.99 14-SEP-08:51 71124.04 01-SEP-18:02 0.00 0.00 0.00
October 0.183255E+11 0.00 393.06 0.117839E+11 0.00 0.00 0.00 0.00 81501.38 05-OCT-21:51 65911.55 06-OCT-18:01 0.00 0.00 0.00
November 0.491074E+10 0.00 235.05 0.291000E+10 0.00 0.00 0.00 0.00 67277.22 10-NOV-09:13 61743.24 04-NOV-19:42 0.00 0.00 0.00
December 0.371310E+09 0.00 36.14 0.282932E+09 0.00 0.00 0.00 0.00 58947.01 10-DEC-09:02 58947.01 10-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.274125E+12 0.00 3677.81 0.187150E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.223803E+09 0.00 21.93 0.190838E+09 0.00 0.00 0.00 0.00 58947.01   56105.05   0.00 0.00 0.00
Maximum of Months 0.634555E+11 0.00 557.27 0.438715E+11 0.00 0.00 0.00 0.00 102657.74   72066.13   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 92860610.84 0.00 18.77 69566319.03 0.00 0.00 0.00 0.00 10305.71 20-JAN-09:02 10305.71 20-JAN-09:02 0.00 0.00 0.00
February 0.153828E+09 0.00 32.21 0.129050E+09 0.00 0.00 0.00 0.00 11262.09 25-FEB-09:01 11262.09 25-FEB-09:01 0.00 0.00 0.00
March 0.784220E+09 0.00 155.02 0.569701E+09 0.00 0.00 0.00 0.00 13234.73 27-MAR-15:02 11266.44 11-MAR-16:01 0.00 0.00 0.00
April 0.231482E+10 0.00 347.72 0.150239E+10 0.00 0.00 0.00 0.00 12140.13 27-APR-15:02 11502.56 10-APR-18:02 0.00 0.00 0.00
May 0.499073E+10 0.00 604.79 0.326818E+10 0.00 0.00 0.00 0.00 13605.28 05-MAY-15:01 11962.54 20-MAY-18:02 0.00 0.00 0.00
June 0.842043E+10 0.00 683.62 0.507595E+10 0.00 0.00 0.00 0.00 15399.59 18-JUN-08:62 12148.98 01-JUN-18:02 0.00 0.00 0.00
July 0.107165E+11 0.00 722.79 0.682144E+10 0.00 0.00 0.00 0.00 15228.46 28-JUL-08:61 12109.06 13-JUL-08:62 0.00 0.00 0.00
August 0.114162E+11 0.00 727.57 0.783926E+10 0.00 0.00 0.00 0.00 15091.37 06-AUG-08:62 12108.84 04-AUG-18:02 0.00 0.00 0.00
September 0.714050E+10 0.00 662.87 0.446805E+10 0.00 0.00 0.00 0.00 16921.09 22-SEP-18:02 12060.33 14-SEP-18:02 0.00 0.00 0.00
October 0.449384E+10 0.00 570.15 0.271379E+10 0.00 0.00 0.00 0.00 14045.14 06-OCT-08:62 11511.56 25-OCT-18:02 0.00 0.00 0.00
November 0.613449E+09 0.00 140.57 0.375009E+09 0.00 0.00 0.00 0.00 11870.23 11-NOV-09:02 11018.34 04-NOV-15:01 0.00 0.00 0.00
December 0.166047E+09 0.00 35.13 0.122841E+09 0.00 0.00 0.00 0.00 10569.25 02-DEC-09:01 10569.25 02-DEC-09:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.513035E+11 0.00 4701.20 0.329552E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 92860610.84 0.00 18.77 69566319.03 0.00 0.00 0.00 0.00 10305.71   10305.71   0.00 0.00 0.00
Maximum of Months 0.114162E+11 0.00 727.57 0.783926E+10 0.00 0.00 0.00 0.00 16921.09   12148.98   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 9629715.39 0.00 3.19 5133068.24 0.00 0.00 0.00 0.00 5418.67 19-JAN-09:01 4398.46 19-JAN-09:01 0.00 0.00 0.00
February 27497241.19 0.00 8.13 20559364.30 0.00 0.00 0.00 0.00 10327.48 25-FEB-09:01 10327.48 25-FEB-09:01 0.00 0.00 0.00
March 0.288949E+09 0.00 63.33 0.203514E+09 0.00 0.00 0.00 0.00 12442.37 27-MAR-15:02 10247.32 21-MAR-08:62 0.00 0.00 0.00
April 0.141435E+10 0.00 262.90 0.866272E+09 0.00 0.00 0.00 0.00 13000.01 08-APR-08:51 12369.66 08-APR-08:51 0.00 0.00 0.00
May 0.357320E+10 0.00 467.73 0.227947E+10 0.00 0.00 0.00 0.00 16701.56 31-MAY-08:32 14143.98 30-MAY-08:62 0.00 0.00 0.00
June 0.610197E+10 0.00 470.33 0.380820E+10 0.00 0.00 0.00 0.00 17438.32 20-JUN-08:62 14232.78 22-JUN-07:32 0.00 0.00 0.00
July 0.913634E+10 0.00 598.43 0.589054E+10 0.00 0.00 0.00 0.00 17651.73 01-JUL-08:32 13795.85 11-JUL-08:32 0.00 0.00 0.00
August 0.921035E+10 0.00 606.67 0.611833E+10 0.00 0.00 0.00 0.00 17249.09 12-AUG-08:61 13377.60 10-AUG-08:32 0.00 0.00 0.00
September 0.430448E+10 0.00 452.65 0.252589E+10 0.00 0.00 0.00 0.00 17141.85 06-SEP-08:32 13274.11 06-SEP-08:32 0.00 0.00 0.00
October 0.185074E+10 0.00 347.10 0.100177E+10 0.00 0.00 0.00 0.00 14800.23 25-OCT-08:51 11528.94 15-OCT-08:51 0.00 0.00 0.00
November 0.176482E+09 0.00 46.24 95178337.33 0.00 0.00 0.00 0.00 11285.76 11-NOV-09:02 10343.83 04-NOV-15:01 0.00 0.00 0.00
December 18289933.38 0.00 6.92 10622781.76 0.00 0.00 0.00 0.00 8520.73 20-DEC-09:01 8520.73 20-DEC-09:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.361123E+11 0.00 3333.63 0.228255E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 9629715.39 0.00 3.19 5133068.24 0.00 0.00 0.00 0.00 5418.67   4398.46   0.00 0.00 0.00
Maximum of Months 0.921035E+10 0.00 606.67 0.611833E+10 0.00 0.00 0.00 0.00 17651.73   14232.78   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 15267966.29 0.00 10.83 10524263.99 0.00 0.00 0.00 0.00 3245.18 20-JAN-16:02 3245.18 20-JAN-16:02 0.00 0.00 0.00
February 36973141.25 0.00 26.23 31154800.13 0.00 0.00 0.00 0.00 3245.07 17-FEB-16:02 3245.07 17-FEB-16:02 0.00 0.00 0.00
March 0.231152E+09 0.00 120.67 0.175484E+09 0.00 0.00 0.00 0.00 3761.88 27-MAR-15:02 3245.50 11-MAR-16:01 0.00 0.00 0.00
April 0.575878E+09 0.00 288.95 0.398531E+09 0.00 0.00 0.00 0.00 3678.56 09-APR-08:62 3357.43 10-APR-18:02 0.00 0.00 0.00
May 0.122022E+10 0.00 549.98 0.820018E+09 0.00 0.00 0.00 0.00 3981.73 19-MAY-18:02 3445.93 20-MAY-18:02 0.00 0.00 0.00
June 0.228670E+10 0.00 672.87 0.140240E+10 0.00 0.00 0.00 0.00 4726.62 27-JUN-08:62 3433.19 22-JUN-08:61 0.00 0.00 0.00
July 0.282333E+10 0.00 714.87 0.178369E+10 0.00 0.00 0.00 0.00 4750.67 28-JUL-08:61 3458.70 12-JUL-18:02 0.00 0.00 0.00
August 0.296197E+10 0.00 715.33 0.200274E+10 0.00 0.00 0.00 0.00 4647.81 06-AUG-08:62 3492.76 15-AUG-18:02 0.00 0.00 0.00
September 0.173283E+10 0.00 625.36 0.106337E+10 0.00 0.00 0.00 0.00 5054.60 22-SEP-18:02 3431.53 10-SEP-18:02 0.00 0.00 0.00
October 0.106882E+10 0.00 488.63 0.664043E+09 0.00 0.00 0.00 0.00 4149.75 25-OCT-08:62 3339.27 25-OCT-18:02 0.00 0.00 0.00
November 81654892.82 0.00 75.27 47622023.48 0.00 0.00 0.00 0.00 3522.38 10-NOV-16:02 3131.03 08-NOV-16:01 0.00 0.00 0.00
December 16087127.78 0.00 14.55 14539145.18 0.00 0.00 0.00 0.00 3243.31 02-DEC-16:01 3243.31 02-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.130509E+11 0.00 4303.54 0.841412E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 15267966.29 0.00 10.83 10524263.99 0.00 0.00 0.00 0.00 3243.31   3131.03   0.00 0.00 0.00
Maximum of Months 0.296197E+10 0.00 715.33 0.200274E+10 0.00 0.00 0.00 0.00 5054.60   3492.76   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 2555629.22 0.00 1.93 1588351.87 0.00 0.00 0.00 0.00 2244.60 17-JAN-16:02 2244.60 17-JAN-16:02 0.00 0.00 0.00
February 5143422.57 0.00 6.09 4091140.97 0.00 0.00 0.00 0.00 2316.43 24-FEB-16:01 2316.43 24-FEB-16:01 0.00 0.00 0.00
March 87044921.26 0.00 60.67 65905348.16 0.00 0.00 0.00 0.00 3789.37 27-MAR-15:02 3140.05 11-MAR-16:01 0.00 0.00 0.00
April 0.328305E+09 0.00 206.39 0.207637E+09 0.00 0.00 0.00 0.00 3610.91 27-APR-18:21 3502.45 09-APR-18:11 0.00 0.00 0.00
May 0.852509E+09 0.00 418.68 0.536001E+09 0.00 0.00 0.00 0.00 4326.89 31-MAY-08:51 3687.60 29-MAY-18:31 0.00 0.00 0.00
June 0.171569E+10 0.00 461.98 0.109970E+10 0.00 0.00 0.00 0.00 4961.60 25-JUN-07:51 3563.02 22-JUN-07:51 0.00 0.00 0.00
July 0.247700E+10 0.00 593.19 0.162321E+10 0.00 0.00 0.00 0.00 5114.77 23-JUL-08:21 3467.39 03-JUL-18:51 0.00 0.00 0.00
August 0.246169E+10 0.00 596.36 0.166899E+10 0.00 0.00 0.00 0.00 5104.57 12-AUG-08:61 3366.49 17-AUG-18:02 0.00 0.00 0.00
September 0.102905E+10 0.00 411.27 0.593613E+09 0.00 0.00 0.00 0.00 4714.01 14-SEP-08:51 3403.36 10-SEP-21:51 0.00 0.00 0.00
October 0.389659E+09 0.00 277.33 0.195526E+09 0.00 0.00 0.00 0.00 4080.11 05-OCT-21:51 3211.67 02-OCT-15:02 0.00 0.00 0.00
November 13466654.68 0.00 13.76 7898471.69 0.00 0.00 0.00 0.00 3418.18 10-NOV-16:02 2943.92 04-NOV-15:01 0.00 0.00 0.00
December 1905516.15 0.00 1.37 1274314.01 0.00 0.00 0.00 0.00 1764.94 17-DEC-16:02 1594.27 17-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.936401E+10 0.00 3049.01 0.600543E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 1905516.15 0.00 1.37 1274314.01 0.00 0.00 0.00 0.00 1764.94   1594.27   0.00 0.00 0.00
Maximum of Months 0.247700E+10 0.00 596.36 0.166899E+10 0.00 0.00 0.00 0.00 5114.77   3687.60   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.102791E+10 0.00 107.69 0.889214E+09 0.00 0.00 0.00 0.00 15173.93 10-JAN-16:02 15173.93 10-JAN-16:02 0.00 0.00 0.00
February 0.152240E+10 0.00 166.94 0.137651E+10 0.00 0.00 0.00 0.00 15174.68 10-FEB-16:01 15174.68 10-FEB-16:01 0.00 0.00 0.00
March 0.275534E+10 0.00 265.93 0.220136E+10 0.00 0.00 0.00 0.00 16116.01 27-MAR-15:02 15173.16 15-MAR-18:01 0.00 0.00 0.00
April 0.389545E+10 0.00 375.25 0.268449E+10 0.00 0.00 0.00 0.00 16734.02 30-APR-15:02 15364.37 10-APR-18:02 0.00 0.00 0.00
May 0.614743E+10 0.00 596.33 0.387626E+10 0.00 0.00 0.00 0.00 18740.17 31-MAY-18:02 16106.48 20-MAY-18:02 0.00 0.00 0.00
June 0.108056E+11 0.00 662.54 0.613684E+10 0.00 0.00 0.00 0.00 22989.61 27-JUN-08:62 16191.20 22-JUN-18:02 0.00 0.00 0.00
July 0.142831E+11 0.00 712.56 0.885453E+10 0.00 0.00 0.00 0.00 22859.02 28-JUL-08:61 16351.08 09-JUL-18:02 0.00 0.00 0.00
August 0.156806E+11 0.00 715.78 0.104904E+11 0.00 0.00 0.00 0.00 21778.31 06-AUG-08:62 16438.55 12-AUG-18:02 0.00 0.00 0.00
September 0.114172E+11 0.00 656.58 0.740963E+10 0.00 0.00 0.00 0.00 24359.34 22-SEP-18:02 16329.01 14-SEP-18:02 0.00 0.00 0.00
October 0.100800E+11 0.00 622.92 0.727584E+10 0.00 0.00 0.00 0.00 19609.33 05-OCT-18:02 15661.94 02-OCT-15:02 0.00 0.00 0.00
November 0.258320E+10 0.00 271.71 0.187988E+10 0.00 0.00 0.00 0.00 16082.27 11-NOV-16:02 15167.85 02-NOV-18:02 0.00 0.00 0.00
December 0.172839E+10 0.00 164.58 0.153852E+10 0.00 0.00 0.00 0.00 15244.06 25-DEC-16:02 15172.32 15-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.819266E+11 0.00 5318.82 0.546135E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.102791E+10 0.00 107.69 0.889214E+09 0.00 0.00 0.00 0.00 15173.93   15167.85   0.00 0.00 0.00
Maximum of Months 0.156806E+11 0.00 715.78 0.104904E+11 0.00 0.00 0.00 0.00 24359.34   16438.55   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 609.38 399.88 209.50 603.30 602.95 0.00 0.00 0.00
February 806.45 535.99 270.46 814.23 597.44 0.00 0.00 0.00
March 714.52 393.33 321.18 766.94 423.82 0.00 0.00 0.00
April 568.74 230.10 338.64 645.29 298.18 0.00 0.00 0.00
May 488.48 100.01 388.47 603.81 169.99 0.00 0.00 0.00
June 461.24 71.07 390.17 654.79 80.05 0.00 0.00 0.00
July 479.92 81.00 398.92 748.56 32.97 0.00 0.00 0.00
August 642.81 237.13 405.68 987.25 60.43 0.00 0.00 0.00
September 678.34 340.59 337.75 929.40 129.67 0.00 0.00 0.00
October 958.61 601.13 357.48 1208.00 269.44 0.00 0.00 0.00
November 663.77 398.18 265.59 715.54 417.78 0.00 0.00 0.00
December 658.37 467.61 190.76 679.69 542.17 0.00 0.00 0.00
                 
Annual Sum or Average 643.45 320.24 323.20 779.93 300.42 0.00 0.00 0.00
Minimum of Months 461.24 71.07 190.76 603.30 32.97 0.00 0.00 0.00
Maximum of Months 958.61 601.13 405.68 1208.00 602.95 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1715.97 1126.05 589.93 1678.06 1751.23 0.00 0.00 0.00
February 2270.92 1509.32 761.60 2264.07 1740.12 0.00 0.00 0.00
March 2012.03 1107.60 904.43 2131.50 1266.22 0.00 0.00 0.00
April 1601.52 647.94 953.59 1786.72 908.11 0.00 0.00 0.00
May 1375.52 281.62 1093.90 1659.67 539.19 0.00 0.00 0.00
June 1298.82 200.12 1098.70 1815.65 262.59 0.00 0.00 0.00
July 1351.43 228.09 1123.34 2087.08 114.51 0.00 0.00 0.00
August 1810.11 667.74 1142.38 2762.21 189.13 0.00 0.00 0.00
September 1910.16 959.07 951.10 2589.61 415.79 0.00 0.00 0.00
October 2699.38 1692.74 1006.64 3368.82 828.30 0.00 0.00 0.00
November 1869.14 1121.25 747.90 1983.37 1248.39 0.00 0.00 0.00
December 1853.92 1316.75 537.17 1890.29 1591.16 0.00 0.00 0.00
                 
Annual Sum or Average 1811.90 901.78 910.12 2168.66 899.84 0.00 0.00 0.00
Minimum of Months 1298.82 200.12 537.17 1659.67 114.51 0.00 0.00 0.00
Maximum of Months 2699.38 1692.74 1142.38 3368.82 1751.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2229.15 1462.80 766.35 2211.76 2389.44 0.00 0.00 0.00
February 2950.05 1960.69 989.36 2992.97 2355.54 0.00 0.00 0.00
March 2613.75 1438.84 1174.91 2819.57 1721.15 0.00 0.00 0.00
April 2080.47 841.71 1238.76 2360.40 1245.75 0.00 0.00 0.00
May 1786.87 365.84 1421.04 2187.20 744.96 0.00 0.00 0.00
June 1687.25 259.97 1427.28 2397.78 359.56 0.00 0.00 0.00
July 1755.59 296.31 1459.28 2767.34 154.95 0.00 0.00 0.00
August 2351.44 867.43 1484.02 3669.63 246.45 0.00 0.00 0.00
September 2481.41 1245.88 1235.53 3425.21 559.09 0.00 0.00 0.00
October 3506.65 2198.97 1307.68 4459.40 1103.30 0.00 0.00 0.00
November 2428.12 1456.56 971.56 2612.78 1709.19 0.00 0.00 0.00
December 2408.35 1710.53 697.81 2491.33 2173.34 0.00 0.00 0.00
                 
Annual Sum or Average 2353.77 1171.47 1182.30 2867.07 1223.85 0.00 0.00 0.00
Minimum of Months 1687.25 259.97 697.81 2187.20 154.95 0.00 0.00 0.00
Maximum of Months 3506.65 2198.97 1484.02 4459.40 2389.44 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 120.49 79.06 41.42 119.75 120.98 0.00 0.00 0.00
February 159.45 105.97 53.48 161.56 120.13 0.00 0.00 0.00
March 141.27 77.77 63.50 151.34 85.63 0.00 0.00 0.00
April 112.45 45.49 66.96 126.95 59.82 0.00 0.00 0.00
May 96.58 19.77 76.81 118.00 33.47 0.00 0.00 0.00
June 91.20 14.05 77.14 131.01 12.88 0.00 0.00 0.00
July 94.89 16.02 78.87 153.80 3.20 0.00 0.00 0.00
August 127.10 46.88 80.21 202.26 7.64 0.00 0.00 0.00
September 134.12 67.34 66.78 186.68 21.75 0.00 0.00 0.00
October 189.53 118.85 70.68 241.07 50.19 0.00 0.00 0.00
November 131.24 78.73 52.51 142.50 82.65 0.00 0.00 0.00
December 130.17 92.45 37.72 135.44 107.95 0.00 0.00 0.00
                 
Annual Sum or Average 127.22 63.32 63.90 155.92 58.51 0.00 0.00 0.00
Minimum of Months 91.20 14.05 37.72 118.00 3.20 0.00 0.00 0.00
Maximum of Months 189.53 118.85 80.21 241.07 120.98 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 89.55 36.76 52.79 53.79 244.31 0.00 0.00 0.00
February 131.54 57.73 73.81 88.63 247.02 0.00 0.00 0.00
March 195.39 90.55 104.84 175.55 159.57 0.00 0.00 0.00
April 212.21 90.69 121.52 222.18 109.18 0.00 0.00 0.00
May 247.91 94.24 153.67 300.02 60.57 0.00 0.00 0.00
June 270.86 109.31 161.55 373.63 23.49 0.00 0.00 0.00
July 253.41 95.23 158.18 382.36 5.91 0.00 0.00 0.00
August 280.37 129.63 150.74 417.49 14.16 0.00 0.00 0.00
September 199.48 87.09 112.39 263.00 40.71 0.00 0.00 0.00
October 197.92 96.42 101.51 227.58 96.43 0.00 0.00 0.00
November 93.21 27.23 65.98 63.59 164.25 0.00 0.00 0.00
December 82.33 35.54 46.79 50.64 221.40 0.00 0.00 0.00
                 
Annual Sum or Average 188.24 79.38 108.86 219.13 114.84 0.00 0.00 0.00
Minimum of Months 82.33 27.23 46.79 50.64 5.91 0.00 0.00 0.00
Maximum of Months 280.37 129.63 161.55 417.49 247.02 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.18 0.00 23.18 1.47 135.68 0.00 0.00 0.00
February 31.72 0.00 31.72 3.13 138.75 0.00 0.00 0.00
March 44.00 0.00 44.00 16.28 89.63 0.00 0.00 0.00
April 52.95 0.22 52.73 35.44 59.42 0.00 0.00 0.00
May 70.43 2.58 67.85 70.51 32.44 0.00 0.00 0.00
June 74.30 3.95 70.35 96.76 14.73 0.00 0.00 0.00
July 72.11 2.81 69.30 112.98 4.25 0.00 0.00 0.00
August 63.77 0.85 62.92 99.38 8.47 0.00 0.00 0.00
September 48.02 0.03 47.99 56.00 24.12 0.00 0.00 0.00
October 41.52 0.00 41.52 33.05 53.23 0.00 0.00 0.00
November 29.12 0.00 29.12 9.29 89.29 0.00 0.00 0.00
December 20.22 0.00 20.22 1.00 122.47 0.00 0.00 0.00
                 
Annual Sum or Average 47.70 0.87 46.83 44.90 63.95 0.00 0.00 0.00
Minimum of Months 20.22 0.00 20.22 1.00 4.25 0.00 0.00 0.00
Maximum of Months 74.30 3.95 70.35 112.98 138.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 89.55 36.76 52.79 56.58 241.72 0.00 0.00 0.00
February 131.54 57.73 73.81 92.76 243.12 0.00 0.00 0.00
March 195.39 90.55 104.84 179.90 157.36 0.00 0.00 0.00
April 212.21 90.69 121.52 223.93 108.83 0.00 0.00 0.00
May 247.91 94.24 153.67 297.52 62.75 0.00 0.00 0.00
June 270.86 109.31 161.55 367.22 28.16 0.00 0.00 0.00
July 253.41 95.23 158.18 379.97 7.93 0.00 0.00 0.00
August 280.37 129.63 150.74 417.22 16.06 0.00 0.00 0.00
September 199.48 87.09 112.39 261.97 44.23 0.00 0.00 0.00
October 197.92 96.42 101.51 230.53 96.67 0.00 0.00 0.00
November 93.21 27.23 65.98 67.25 161.45 0.00 0.00 0.00
December 82.33 35.54 46.79 53.88 218.18 0.00 0.00 0.00
                 
Annual Sum or Average 188.24 79.38 108.86 219.98 114.82 0.00 0.00 0.00
Minimum of Months 82.33 27.23 46.79 53.88 7.93 0.00 0.00 0.00
Maximum of Months 280.37 129.63 161.55 417.22 243.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 96.37 63.24 33.13 94.27 99.21 0.00 0.00 0.00
February 127.53 84.76 42.77 121.13 116.52 0.00 0.00 0.00
March 113.00 62.20 50.79 112.34 91.65 0.00 0.00 0.00
April 89.94 36.39 53.55 91.34 69.47 0.00 0.00 0.00
May 77.25 15.82 61.43 81.54 44.74 0.00 0.00 0.00
June 72.94 11.24 61.70 90.82 24.49 0.00 0.00 0.00
July 75.90 12.81 63.09 107.02 14.00 0.00 0.00 0.00
August 101.66 37.50 64.16 146.61 18.38 0.00 0.00 0.00
September 107.27 53.86 53.41 137.16 35.42 0.00 0.00 0.00
October 151.60 95.06 56.53 181.11 61.66 0.00 0.00 0.00
November 104.97 62.97 42.00 104.02 90.43 0.00 0.00 0.00
December 104.12 73.95 30.17 101.40 106.18 0.00 0.00 0.00
                 
Annual Sum or Average 101.76 50.64 51.11 114.10 64.02 0.00 0.00 0.00
Minimum of Months 72.94 11.24 30.17 81.54 14.00 0.00 0.00 0.00
Maximum of Months 151.60 95.06 64.16 181.11 116.52 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 18.55 0.00 18.55 0.80 114.00 0.00 0.00 0.00
February 25.38 0.00 25.38 2.15 115.45 0.00 0.00 0.00
March 35.20 0.00 35.20 12.83 73.57 0.00 0.00 0.00
April 42.37 0.17 42.19 29.18 48.15 0.00 0.00 0.00
May 56.35 2.06 54.29 59.14 25.32 0.00 0.00 0.00
June 59.45 3.16 56.28 81.87 10.22 0.00 0.00 0.00
July 57.70 2.25 55.45 94.78 2.53 0.00 0.00 0.00
August 51.02 0.68 50.35 84.27 5.55 0.00 0.00 0.00
September 38.42 0.02 38.40 47.43 17.83 0.00 0.00 0.00
October 33.22 0.00 33.22 27.88 41.47 0.00 0.00 0.00
November 23.30 0.00 23.30 6.97 75.03 0.00 0.00 0.00
December 16.18 0.00 16.18 0.58 103.26 0.00 0.00 0.00
                 
Annual Sum or Average 38.17 0.70 37.47 37.57 52.34 0.00 0.00 0.00
Minimum of Months 16.18 0.00 16.18 0.58 2.53 0.00 0.00 0.00
Maximum of Months 59.45 3.16 56.28 94.78 115.45 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 90.17 36.03 54.15 52.58 240.39 0.00 0.00 0.00
February 140.00 65.20 74.81 94.43 238.59 0.00 0.00 0.00
March 179.79 76.41 103.38 156.12 160.31 0.00 0.00 0.00
April 215.22 94.46 120.76 223.69 105.98 0.00 0.00 0.00
May 259.83 103.55 156.29 315.27 58.69 0.00 0.00 0.00
June 241.27 87.39 153.88 333.26 22.40 0.00 0.00 0.00
July 242.01 87.13 154.88 367.71 5.59 0.00 0.00 0.00
August 273.01 123.17 149.84 407.03 13.27 0.00 0.00 0.00
September 204.23 92.00 112.22 268.52 39.07 0.00 0.00 0.00
October 184.50 83.51 100.99 208.70 93.83 0.00 0.00 0.00
November 114.27 43.91 70.36 90.59 160.28 0.00 0.00 0.00
December 89.34 42.15 47.19 58.19 216.48 0.00 0.00 0.00
                 
Annual Sum or Average 186.43 78.00 108.44 215.50 112.21 0.00 0.00 0.00
Minimum of Months 89.34 36.03 47.19 52.58 5.59 0.00 0.00 0.00
Maximum of Months 273.01 123.17 156.29 407.03 240.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 120.49 79.06 41.42 119.45 120.82 0.00 0.00 0.00
February 159.45 105.97 53.48 160.82 119.86 0.00 0.00 0.00
March 141.27 77.77 63.50 150.48 84.87 0.00 0.00 0.00
April 112.45 45.49 66.96 125.98 59.40 0.00 0.00 0.00
May 96.58 19.77 76.81 117.10 33.02 0.00 0.00 0.00
June 91.20 14.05 77.14 131.01 12.42 0.00 0.00 0.00
July 94.89 16.02 78.87 153.73 3.02 0.00 0.00 0.00
August 127.10 46.88 80.21 202.03 7.36 0.00 0.00 0.00
September 134.12 67.34 66.78 186.19 21.46 0.00 0.00 0.00
October 189.53 118.85 70.68 240.57 49.66 0.00 0.00 0.00
November 131.24 78.73 52.51 141.74 82.76 0.00 0.00 0.00
December 130.17 92.45 37.72 135.02 107.83 0.00 0.00 0.00
                 
Annual Sum or Average 127.22 63.32 63.90 155.40 58.19 0.00 0.00 0.00
Minimum of Months 91.20 14.05 37.72 117.10 3.02 0.00 0.00 0.00
Maximum of Months 189.53 118.85 80.21 240.57 120.82 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.18 0.00 23.18 1.31 135.62 0.00 0.00 0.00
February 31.72 0.00 31.72 2.90 138.74 0.00 0.00 0.00
March 44.00 0.00 44.00 15.55 88.87 0.00 0.00 0.00
April 52.95 0.22 52.73 34.52 58.94 0.00 0.00 0.00
May 70.43 2.58 67.85 69.76 31.77 0.00 0.00 0.00
June 74.30 3.95 70.35 97.04 13.75 0.00 0.00 0.00
July 72.11 2.81 69.30 112.50 3.98 0.00 0.00 0.00
August 63.77 0.85 62.92 98.49 8.09 0.00 0.00 0.00
September 48.02 0.03 47.99 55.17 23.38 0.00 0.00 0.00
October 41.52 0.00 41.52 32.27 52.01 0.00 0.00 0.00
November 29.12 0.00 29.12 8.75 89.50 0.00 0.00 0.00
December 20.22 0.00 20.22 0.86 122.43 0.00 0.00 0.00
                 
Annual Sum or Average 47.70 0.87 46.83 44.38 63.50 0.00 0.00 0.00
Minimum of Months 20.22 0.00 20.22 0.86 3.98 0.00 0.00 0.00
Maximum of Months 74.30 3.95 70.35 112.50 138.74 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 90.17 36.03 54.15 54.25 236.58 0.00 0.00 0.00
February 140.00 65.20 74.81 97.20 232.94 0.00 0.00 0.00
March 179.79 76.41 103.38 160.04 157.37 0.00 0.00 0.00
April 215.22 94.46 120.76 225.53 105.34 0.00 0.00 0.00
May 259.83 103.55 156.29 313.40 60.60 0.00 0.00 0.00
June 241.27 87.39 153.88 327.82 26.36 0.00 0.00 0.00
July 242.01 87.13 154.88 364.53 7.51 0.00 0.00 0.00
August 273.01 123.17 149.84 405.39 14.97 0.00 0.00 0.00
September 204.23 92.00 112.22 267.15 41.99 0.00 0.00 0.00
October 184.50 83.51 100.99 211.82 93.18 0.00 0.00 0.00
November 114.27 43.91 70.36 93.66 156.81 0.00 0.00 0.00
December 89.34 42.15 47.19 59.94 211.49 0.00 0.00 0.00
                 
Annual Sum or Average 186.43 78.00 108.44 215.88 111.42 0.00 0.00 0.00
Minimum of Months 89.34 36.03 47.19 54.25 7.51 0.00 0.00 0.00
Maximum of Months 273.01 123.17 156.29 405.39 236.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 29.36 0.00 29.36 1.04 184.72 0.00 0.00 0.00
February 40.17 0.00 40.17 3.07 187.71 0.00 0.00 0.00
March 55.72 0.00 55.72 19.95 118.48 0.00 0.00 0.00
April 67.06 0.28 66.78 46.37 78.59 0.00 0.00 0.00
May 89.19 3.26 85.93 93.33 42.89 0.00 0.00 0.00
June 94.09 5.00 89.09 126.02 20.39 0.00 0.00 0.00
July 91.33 3.56 87.76 141.38 7.91 0.00 0.00 0.00
August 80.76 1.07 79.69 123.06 14.06 0.00 0.00 0.00
September 60.81 0.04 60.78 71.27 34.18 0.00 0.00 0.00
October 52.59 0.00 52.59 41.46 73.05 0.00 0.00 0.00
November 36.88 0.00 36.88 10.61 121.65 0.00 0.00 0.00
December 25.61 0.00 25.61 0.78 167.39 0.00 0.00 0.00
                 
Annual Sum or Average 60.41 1.11 59.31 56.89 87.02 0.00 0.00 0.00
Minimum of Months 25.61 0.00 25.61 0.78 7.91 0.00 0.00 0.00
Maximum of Months 94.09 5.00 89.09 141.38 187.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.82 0.00 10.82 0.38 68.10 0.00 0.00 0.00
February 14.81 0.00 14.81 1.13 69.20 0.00 0.00 0.00
March 20.54 0.00 20.54 7.35 43.68 0.00 0.00 0.00
April 24.72 0.10 24.62 17.09 28.97 0.00 0.00 0.00
May 32.88 1.20 31.68 34.41 15.81 0.00 0.00 0.00
June 34.69 1.84 32.84 46.45 7.52 0.00 0.00 0.00
July 33.67 1.31 32.35 52.12 2.92 0.00 0.00 0.00
August 29.77 0.40 29.38 45.37 5.18 0.00 0.00 0.00
September 22.42 0.01 22.41 26.27 12.60 0.00 0.00 0.00
October 19.39 0.00 19.39 15.28 26.93 0.00 0.00 0.00
November 13.60 0.00 13.60 3.91 44.84 0.00 0.00 0.00
December 9.44 0.00 9.44 0.29 61.71 0.00 0.00 0.00
                 
Annual Sum or Average 22.27 0.41 21.86 20.97 32.08 0.00 0.00 0.00
Minimum of Months 9.44 0.00 9.44 0.29 2.92 0.00 0.00 0.00
Maximum of Months 34.69 1.84 32.84 52.12 69.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 56.22 36.89 19.33 55.57 59.51 0.00 0.00 0.00
February 74.40 49.45 24.95 75.35 58.51 0.00 0.00 0.00
March 65.92 36.29 29.63 71.36 41.13 0.00 0.00 0.00
April 52.47 21.23 31.24 60.16 29.02 0.00 0.00 0.00
May 45.06 9.23 35.84 55.98 16.90 0.00 0.00 0.00
June 42.55 6.56 36.00 60.94 7.95 0.00 0.00 0.00
July 44.28 7.47 36.80 70.52 2.98 0.00 0.00 0.00
August 59.30 21.88 37.43 93.23 5.33 0.00 0.00 0.00
September 62.58 31.42 31.16 86.98 12.45 0.00 0.00 0.00
October 88.44 55.46 32.98 113.18 25.52 0.00 0.00 0.00
November 61.24 36.73 24.50 66.60 40.46 0.00 0.00 0.00
December 60.74 43.14 17.60 63.13 52.98 0.00 0.00 0.00
                 
Annual Sum or Average 59.36 29.54 29.82 72.77 29.23 0.00 0.00 0.00
Minimum of Months 42.55 6.56 17.60 55.57 2.98 0.00 0.00 0.00
Maximum of Months 88.44 55.46 37.43 113.18 59.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 152.59 100.13 52.46 150.83 161.51 0.00 0.00 0.00
February 201.93 134.21 67.72 204.52 158.81 0.00 0.00 0.00
March 178.91 98.49 80.42 193.69 111.63 0.00 0.00 0.00
April 142.41 57.62 84.79 163.30 78.77 0.00 0.00 0.00
May 122.31 25.04 97.27 151.93 45.87 0.00 0.00 0.00
June 115.49 17.80 97.70 165.41 21.59 0.00 0.00 0.00
July 120.17 20.28 99.89 191.42 8.09 0.00 0.00 0.00
August 160.96 59.38 101.58 253.04 14.48 0.00 0.00 0.00
September 169.85 85.28 84.57 236.08 33.80 0.00 0.00 0.00
October 240.03 150.52 89.51 307.18 69.27 0.00 0.00 0.00
November 166.21 99.70 66.50 180.77 109.82 0.00 0.00 0.00
December 164.85 117.09 47.77 171.34 143.79 0.00 0.00 0.00
                 
Annual Sum or Average 161.12 80.19 80.93 197.52 79.34 0.00 0.00 0.00
Minimum of Months 115.49 17.80 47.77 150.83 8.09 0.00 0.00 0.00
Maximum of Months 240.03 150.52 101.58 307.18 161.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 120.49 79.06 41.42 119.46 120.19 0.00 0.00 0.00
February 159.45 105.97 53.48 161.06 119.50 0.00 0.00 0.00
March 141.27 77.77 63.50 150.43 85.26 0.00 0.00 0.00
April 112.45 45.49 66.96 125.94 59.48 0.00 0.00 0.00
May 96.58 19.77 76.81 116.73 33.27 0.00 0.00 0.00
June 91.20 14.05 77.14 129.87 12.58 0.00 0.00 0.00
July 94.89 16.02 78.87 152.80 2.98 0.00 0.00 0.00
August 127.10 46.88 80.21 201.14 7.27 0.00 0.00 0.00
September 134.12 67.34 66.78 185.57 21.24 0.00 0.00 0.00
October 189.53 118.85 70.68 239.80 49.46 0.00 0.00 0.00
November 131.24 78.73 52.51 142.17 81.74 0.00 0.00 0.00
December 130.17 92.45 37.72 135.23 107.02 0.00 0.00 0.00
                 
Annual Sum or Average 127.22 63.32 63.90 155.07 57.99 0.00 0.00 0.00
Minimum of Months 91.20 14.05 37.72 116.73 2.98 0.00 0.00 0.00
Maximum of Months 189.53 118.85 80.21 239.80 120.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 89.55 36.76 52.79 53.77 242.80 0.00 0.00 0.00
February 131.54 57.73 73.81 88.11 245.93 0.00 0.00 0.00
March 195.39 90.55 104.84 174.23 158.63 0.00 0.00 0.00
April 212.21 90.69 121.52 220.41 108.31 0.00 0.00 0.00
May 247.91 94.24 153.67 297.43 60.05 0.00 0.00 0.00
June 270.86 109.31 161.55 370.90 22.88 0.00 0.00 0.00
July 253.41 95.23 158.18 380.11 5.48 0.00 0.00 0.00
August 280.37 129.63 150.74 415.49 13.46 0.00 0.00 0.00
September 199.48 87.09 112.39 261.45 39.67 0.00 0.00 0.00
October 197.92 96.42 101.51 226.15 94.92 0.00 0.00 0.00
November 93.21 27.23 65.98 63.53 162.46 0.00 0.00 0.00
December 82.33 35.54 46.79 50.69 219.51 0.00 0.00 0.00
                 
Annual Sum or Average 188.24 79.38 108.86 217.78 113.77 0.00 0.00 0.00
Minimum of Months 82.33 27.23 46.79 50.69 5.48 0.00 0.00 0.00
Maximum of Months 280.37 129.63 161.55 415.49 245.93 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.18 0.00 23.18 1.57 134.78 0.00 0.00 0.00
February 31.72 0.00 31.72 3.24 138.17 0.00 0.00 0.00
March 44.00 0.00 44.00 16.32 89.15 0.00 0.00 0.00
April 52.95 0.22 52.73 35.15 59.13 0.00 0.00 0.00
May 70.43 2.58 67.85 69.32 32.64 0.00 0.00 0.00
June 74.30 3.95 70.35 95.58 15.10 0.00 0.00 0.00
July 72.11 2.81 69.30 112.23 4.23 0.00 0.00 0.00
August 63.77 0.85 62.92 99.02 8.26 0.00 0.00 0.00
September 48.02 0.03 47.99 55.65 24.01 0.00 0.00 0.00
October 41.52 0.00 41.52 33.15 52.54 0.00 0.00 0.00
November 29.12 0.00 29.12 9.53 88.04 0.00 0.00 0.00
December 20.22 0.00 20.22 1.11 121.17 0.00 0.00 0.00
                 
Annual Sum or Average 47.70 0.87 46.83 44.61 63.52 0.00 0.00 0.00
Minimum of Months 20.22 0.00 20.22 1.11 4.23 0.00 0.00 0.00
Maximum of Months 74.30 3.95 70.35 112.23 138.17 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 89.55 36.76 52.79 56.65 240.33 0.00 0.00 0.00
February 131.54 57.73 73.81 92.45 242.18 0.00 0.00 0.00
March 195.39 90.55 104.84 178.97 156.32 0.00 0.00 0.00
April 212.21 90.69 121.52 222.17 108.14 0.00 0.00 0.00
May 247.91 94.24 153.67 294.35 62.95 0.00 0.00 0.00
June 270.86 109.31 161.55 363.71 28.79 0.00 0.00 0.00
July 253.41 95.23 158.18 377.60 7.83 0.00 0.00 0.00
August 280.37 129.63 150.74 415.34 15.59 0.00 0.00 0.00
September 199.48 87.09 112.39 260.31 43.83 0.00 0.00 0.00
October 197.92 96.42 101.51 229.53 95.25 0.00 0.00 0.00
November 93.21 27.23 65.98 67.54 159.46 0.00 0.00 0.00
December 82.33 35.54 46.79 54.19 216.31 0.00 0.00 0.00
                 
Annual Sum or Average 188.24 79.38 108.86 218.64 114.03 0.00 0.00 0.00
Minimum of Months 82.33 27.23 46.79 54.19 7.83 0.00 0.00 0.00
Maximum of Months 280.37 129.63 161.55 415.34 242.18 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 176.70 115.95 60.75 169.64 183.32 0.00 0.00 0.00
February 233.85 155.42 78.43 229.12 182.45 0.00 0.00 0.00
March 207.19 114.06 93.13 216.75 128.72 0.00 0.00 0.00
April 164.92 66.72 98.20 183.00 88.41 0.00 0.00 0.00
May 141.64 29.00 112.65 172.27 48.04 0.00 0.00 0.00
June 133.75 20.61 113.14 193.75 16.98 0.00 0.00 0.00
July 139.17 23.49 115.68 227.77 3.61 0.00 0.00 0.00
August 186.40 68.76 117.64 297.99 9.78 0.00 0.00 0.00
September 196.70 98.76 97.94 272.06 30.88 0.00 0.00 0.00
October 277.97 174.31 103.66 348.79 74.29 0.00 0.00 0.00
November 192.48 115.46 77.02 202.94 126.24 0.00 0.00 0.00
December 190.91 135.59 55.32 192.36 164.18 0.00 0.00 0.00
                 
Annual Sum or Average 186.58 92.86 93.72 225.65 87.55 0.00 0.00 0.00
Minimum of Months 133.75 20.61 55.32 169.64 3.61 0.00 0.00 0.00
Maximum of Months 277.97 174.31 117.64 348.79 183.32 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 162.25 0.00 162.25 2.36 1128.75 0.00 0.00 0.00
February 222.04 0.00 222.04 10.67 1140.28 0.00 0.00 0.00
March 307.98 0.01 307.98 85.61 756.33 0.00 0.00 0.00
April 370.63 1.53 369.11 215.87 510.94 0.00 0.00 0.00
May 492.96 18.04 474.92 460.40 277.55 0.00 0.00 0.00
June 520.06 27.66 492.40 662.26 129.41 0.00 0.00 0.00
July 504.77 19.70 485.07 754.97 53.58 0.00 0.00 0.00
August 446.39 5.93 440.46 662.93 83.42 0.00 0.00 0.00
September 336.12 0.20 335.92 371.49 213.42 0.00 0.00 0.00
October 290.65 0.00 290.65 207.67 444.47 0.00 0.00 0.00
November 203.86 0.00 203.86 43.16 773.90 0.00 0.00 0.00
December 141.53 0.00 141.53 1.99 1039.59 0.00 0.00 0.00
                 
Annual Sum or Average 333.92 6.12 327.79 291.88 542.61 0.00 0.00 0.00
Minimum of Months 141.53 0.00 141.53 1.99 53.58 0.00 0.00 0.00
Maximum of Months 520.06 27.66 492.40 754.97 1140.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 162.25 0.00 162.25 1.52 1163.36 0.00 0.00 0.00
February 222.04 0.00 222.04 8.78 1173.46 0.00 0.00 0.00
March 307.98 0.01 307.98 78.45 780.39 0.00 0.00 0.00
April 370.63 1.53 369.11 205.26 528.06 0.00 0.00 0.00
May 492.96 18.04 474.92 447.67 286.53 0.00 0.00 0.00
June 520.06 27.66 492.40 652.69 135.10 0.00 0.00 0.00
July 504.77 19.70 485.07 746.42 57.70 0.00 0.00 0.00
August 446.39 5.93 440.46 654.29 87.71 0.00 0.00 0.00
September 336.12 0.20 335.92 362.84 222.17 0.00 0.00 0.00
October 290.65 0.00 290.65 198.85 458.51 0.00 0.00 0.00
November 203.86 0.00 203.86 38.64 800.71 0.00 0.00 0.00
December 141.53 0.00 141.53 1.45 1072.35 0.00 0.00 0.00
                 
Annual Sum or Average 333.92 6.12 327.79 284.98 560.39 0.00 0.00 0.00
Minimum of Months 141.53 0.00 141.53 1.45 57.70 0.00 0.00 0.00
Maximum of Months 520.06 27.66 492.40 746.42 1173.46 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.18 0.00 23.18 2.21 140.24 0.00 0.00 0.00
February 31.72 0.00 31.72 4.06 142.67 0.00 0.00 0.00
March 44.00 0.00 44.00 20.08 92.22 0.00 0.00 0.00
April 52.95 0.22 52.73 46.03 62.60 0.00 0.00 0.00
May 70.43 2.58 67.85 90.10 35.47 0.00 0.00 0.00
June 74.30 3.95 70.35 123.34 16.57 0.00 0.00 0.00
July 72.11 2.81 69.30 139.52 7.13 0.00 0.00 0.00
August 63.77 0.85 62.92 124.36 10.56 0.00 0.00 0.00
September 48.02 0.03 47.99 76.57 24.34 0.00 0.00 0.00
October 41.52 0.00 41.52 44.85 51.68 0.00 0.00 0.00
November 29.12 0.00 29.12 12.23 92.71 0.00 0.00 0.00
December 20.22 0.00 20.22 1.64 126.37 0.00 0.00 0.00
                 
Annual Sum or Average 47.70 0.87 46.83 57.44 66.45 0.00 0.00 0.00
Minimum of Months 20.22 0.00 20.22 1.64 7.13 0.00 0.00 0.00
Maximum of Months 74.30 3.95 70.35 139.52 142.67 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 180.34 72.05 108.29 115.99 492.01 0.00 0.00 0.00
February 279.99 130.38 149.60 204.89 481.25 0.00 0.00 0.00
March 359.55 152.80 206.74 342.22 330.92 0.00 0.00 0.00
April 430.41 188.91 241.50 497.20 226.51 0.00 0.00 0.00
May 519.63 207.08 312.55 700.00 133.25 0.00 0.00 0.00
June 482.51 174.77 307.74 752.14 62.22 0.00 0.00 0.00
July 483.98 174.24 309.74 829.07 26.88 0.00 0.00 0.00
August 545.99 246.33 299.66 907.33 39.55 0.00 0.00 0.00
September 408.42 183.99 224.43 616.21 89.45 0.00 0.00 0.00
October 368.98 167.02 201.96 476.54 187.88 0.00 0.00 0.00
November 228.53 87.82 140.71 206.69 325.82 0.00 0.00 0.00
December 178.67 84.30 94.36 128.63 438.33 0.00 0.00 0.00
                 
Annual Sum or Average 372.84 155.98 216.86 483.28 234.82 0.00 0.00 0.00
Minimum of Months 178.67 72.05 94.36 115.99 26.88 0.00 0.00 0.00
Maximum of Months 545.99 246.33 312.55 907.33 492.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 120.49 79.06 41.42 123.97 124.55 0.00 0.00 0.00
February 159.45 105.97 53.48 167.52 122.20 0.00 0.00 0.00
March 141.27 77.77 63.50 160.10 87.94 0.00 0.00 0.00
April 112.45 45.49 66.96 139.02 62.82 0.00 0.00 0.00
May 96.58 19.77 76.81 135.77 36.96 0.00 0.00 0.00
June 91.20 14.05 77.14 153.55 17.24 0.00 0.00 0.00
July 94.89 16.02 78.87 178.51 7.27 0.00 0.00 0.00
August 127.10 46.88 80.21 227.08 10.65 0.00 0.00 0.00
September 134.12 67.34 66.78 207.49 24.14 0.00 0.00 0.00
October 189.53 118.85 70.68 257.44 50.42 0.00 0.00 0.00
November 131.24 78.73 52.51 150.00 84.95 0.00 0.00 0.00
December 130.17 92.45 37.72 140.48 110.66 0.00 0.00 0.00
                 
Annual Sum or Average 127.22 63.32 63.90 170.18 61.31 0.00 0.00 0.00
Minimum of Months 91.20 14.05 37.72 123.97 7.27 0.00 0.00 0.00
Maximum of Months 189.53 118.85 80.21 257.44 124.55 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 29.36 0.00 29.36 0.77 188.33 0.00 0.00 0.00
February 40.17 0.00 40.17 2.57 191.53 0.00 0.00 0.00
March 55.72 0.00 55.72 17.99 121.38 0.00 0.00 0.00
April 67.06 0.28 66.78 43.52 80.34 0.00 0.00 0.00
May 89.19 3.26 85.93 89.23 44.20 0.00 0.00 0.00
June 94.09 5.00 89.09 121.70 21.60 0.00 0.00 0.00
July 91.33 3.56 87.76 136.18 9.44 0.00 0.00 0.00
August 80.76 1.07 79.69 118.78 14.99 0.00 0.00 0.00
September 60.81 0.04 60.78 68.56 34.94 0.00 0.00 0.00
October 52.59 0.00 52.59 39.70 72.58 0.00 0.00 0.00
November 36.88 0.00 36.88 9.64 123.97 0.00 0.00 0.00
December 25.61 0.00 25.61 0.59 171.10 0.00 0.00 0.00
                 
Annual Sum or Average 60.41 1.11 59.31 54.45 88.96 0.00 0.00 0.00
Minimum of Months 25.61 0.00 25.61 0.59 9.44 0.00 0.00 0.00
Maximum of Months 94.09 5.00 89.09 136.18 191.53 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.26 0.00 26.26 0.69 168.49 0.00 0.00 0.00
February 35.94 0.00 35.94 2.30 171.36 0.00 0.00 0.00
March 49.86 0.00 49.85 16.10 108.60 0.00 0.00 0.00
April 60.00 0.25 59.75 38.94 71.88 0.00 0.00 0.00
May 79.80 2.92 76.88 79.84 39.55 0.00 0.00 0.00
June 84.18 4.48 79.71 108.88 19.32 0.00 0.00 0.00
July 81.71 3.19 78.52 121.84 8.44 0.00 0.00 0.00
August 72.26 0.96 71.30 106.28 13.41 0.00 0.00 0.00
September 54.41 0.03 54.38 61.34 31.26 0.00 0.00 0.00
October 47.05 0.00 47.05 35.52 64.94 0.00 0.00 0.00
November 33.00 0.00 33.00 8.62 110.91 0.00 0.00 0.00
December 22.91 0.00 22.91 0.53 153.06 0.00 0.00 0.00
                 
Annual Sum or Average 54.05 0.99 53.06 48.72 79.59 0.00 0.00 0.00
Minimum of Months 22.91 0.00 22.91 0.53 8.44 0.00 0.00 0.00
Maximum of Months 84.18 4.48 79.71 121.84 171.36 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 449.81 295.17 154.64 438.17 484.07 0.00 0.00 0.00
February 595.27 395.63 199.64 594.39 475.21 0.00 0.00 0.00
March 527.41 290.33 237.08 560.68 336.86 0.00 0.00 0.00
April 419.81 169.84 249.96 470.05 238.06 0.00 0.00 0.00
May 360.56 73.82 286.74 434.67 139.99 0.00 0.00 0.00
June 340.46 52.46 288.00 473.60 67.74 0.00 0.00 0.00
July 354.25 59.79 294.46 547.54 28.48 0.00 0.00 0.00
August 474.49 175.03 299.45 730.88 45.57 0.00 0.00 0.00
September 500.71 251.40 249.31 685.21 102.10 0.00 0.00 0.00
October 707.59 443.72 263.87 896.10 203.15 0.00 0.00 0.00
November 489.96 293.91 196.05 525.51 329.12 0.00 0.00 0.00
December 485.97 345.16 140.81 498.28 431.56 0.00 0.00 0.00
                 
Annual Sum or Average 474.95 236.38 238.57 571.42 238.84 0.00 0.00 0.00
Minimum of Months 340.46 52.46 140.81 434.67 28.48 0.00 0.00 0.00
Maximum of Months 707.59 443.72 299.45 896.10 484.07 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.163216E+10 0.107105E+10 0.561115E+09 0.161587E+10 0.161495E+10
February 0.195097E+10 0.129667E+10 0.654301E+09 0.196978E+10 0.144532E+10
March 0.191376E+10 0.105350E+10 0.860258E+09 0.205417E+10 0.113515E+10
April 0.147416E+10 0.596411E+09 0.877753E+09 0.167258E+10 0.772889E+09
May 0.130833E+10 0.267862E+09 0.104047E+10 0.161725E+10 0.455313E+09
June 0.119554E+10 0.184207E+09 0.101133E+10 0.169721E+10 0.207490E+09
July 0.128543E+10 0.216954E+09 0.106847E+10 0.200493E+10 88295919.91
August 0.172171E+10 0.635122E+09 0.108658E+10 0.264424E+10 0.161856E+09
September 0.175826E+10 0.882798E+09 0.875461E+09 0.240902E+10 0.336096E+09
October 0.256754E+10 0.161007E+10 0.957474E+09 0.323551E+10 0.721673E+09
November 0.172050E+10 0.103208E+10 0.688421E+09 0.185468E+10 0.108288E+10
December 0.176337E+10 0.125244E+10 0.510933E+09 0.182048E+10 0.145214E+10
           
Annual Sum or Average 0.202917E+11 0.100992E+11 0.101926E+11 0.245957E+11 0.947405E+10
Minimum of Months 0.119554E+10 0.184207E+09 0.510933E+09 0.161587E+10 88295919.91
Maximum of Months 0.256754E+10 0.161007E+10 0.108658E+10 0.323551E+10 0.161495E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.459606E+10 0.301600E+10 0.158006E+10 0.449451E+10 0.469049E+10
February 0.549380E+10 0.365134E+10 0.184247E+10 0.547724E+10 0.420969E+10
March 0.538903E+10 0.296660E+10 0.242243E+10 0.570900E+10 0.339143E+10
April 0.415115E+10 0.167946E+10 0.247169E+10 0.463119E+10 0.235383E+10
May 0.368418E+10 0.754282E+09 0.292990E+10 0.444525E+10 0.144418E+10
June 0.336655E+10 0.518716E+09 0.284784E+10 0.470617E+10 0.680623E+09
July 0.361968E+10 0.610929E+09 0.300875E+10 0.559003E+10 0.306697E+09
August 0.484821E+10 0.178846E+10 0.305975E+10 0.739830E+10 0.506569E+09
September 0.495114E+10 0.248590E+10 0.246524E+10 0.671227E+10 0.107772E+10
October 0.723002E+10 0.453384E+10 0.269618E+10 0.902304E+10 0.221852E+10
November 0.484482E+10 0.290627E+10 0.193855E+10 0.514090E+10 0.323582E+10
December 0.496554E+10 0.352678E+10 0.143875E+10 0.506294E+10 0.426176E+10
           
Annual Sum or Average 0.571402E+11 0.284386E+11 0.287016E+11 0.683909E+11 0.283773E+11
Minimum of Months 0.336655E+10 0.518716E+09 0.143875E+10 0.444525E+10 0.306697E+09
Maximum of Months 0.723002E+10 0.453384E+10 0.305975E+10 0.902304E+10 0.469049E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.597055E+10 0.391796E+10 0.205259E+10 0.592398E+10 0.639987E+10
February 0.713676E+10 0.474329E+10 0.239347E+10 0.724059E+10 0.569852E+10
March 0.700065E+10 0.385378E+10 0.314688E+10 0.755195E+10 0.460992E+10
April 0.539258E+10 0.218171E+10 0.321087E+10 0.611816E+10 0.322898E+10
May 0.478596E+10 0.979855E+09 0.380610E+10 0.585819E+10 0.199529E+10
June 0.437334E+10 0.673841E+09 0.369950E+10 0.621505E+10 0.931974E+09
July 0.470217E+10 0.793632E+09 0.390854E+10 0.741204E+10 0.415027E+09
August 0.629810E+10 0.232331E+10 0.397479E+10 0.982874E+10 0.660101E+09
September 0.643181E+10 0.322933E+10 0.320249E+10 0.887815E+10 0.144917E+10
October 0.939221E+10 0.588972E+10 0.350250E+10 0.119441E+11 0.295507E+10
November 0.629370E+10 0.377541E+10 0.251828E+10 0.677233E+10 0.443023E+10
December 0.645052E+10 0.458149E+10 0.186902E+10 0.667277E+10 0.582107E+10
           
Annual Sum or Average 0.742284E+11 0.369433E+11 0.372850E+11 0.904160E+11 0.385952E+11
Minimum of Months 0.437334E+10 0.673841E+09 0.186902E+10 0.585819E+10 0.415027E+09
Maximum of Months 0.939221E+10 0.588972E+10 0.397479E+10 0.119441E+11 0.639987E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.322707E+09 0.211765E+09 0.110943E+09 0.320735E+09 0.324045E+09
February 0.385741E+09 0.256374E+09 0.129367E+09 0.390851E+09 0.290621E+09
March 0.378385E+09 0.208296E+09 0.170089E+09 0.405343E+09 0.229345E+09
April 0.291469E+09 0.117921E+09 0.173548E+09 0.329061E+09 0.155066E+09
May 0.258682E+09 52960934.60 0.205721E+09 0.316060E+09 89632708.99
June 0.236380E+09 36420939.70 0.199959E+09 0.339573E+09 33378112.16
July 0.254153E+09 42895608.52 0.211258E+09 0.411944E+09 8582286.61
August 0.340413E+09 0.125575E+09 0.214838E+09 0.541743E+09 20464750.29
September 0.347639E+09 0.174544E+09 0.173095E+09 0.483873E+09 56386764.87
October 0.507648E+09 0.318338E+09 0.189310E+09 0.645670E+09 0.134417E+09
November 0.340174E+09 0.204060E+09 0.136113E+09 0.369361E+09 0.214231E+09
December 0.348649E+09 0.247629E+09 0.101021E+09 0.362752E+09 0.289126E+09
           
Annual Sum or Average 0.401204E+10 0.199678E+10 0.201526E+10 0.491697E+10 0.184530E+10
Minimum of Months 0.236380E+09 36420939.70 0.101021E+09 0.316060E+09 8582286.61
Maximum of Months 0.507648E+09 0.318338E+09 0.214838E+09 0.645670E+09 0.324045E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.239844E+09 98462657.35 0.141382E+09 0.144077E+09 0.654367E+09
February 0.318223E+09 0.139658E+09 0.178565E+09 0.214405E+09 0.597589E+09
March 0.523325E+09 0.242520E+09 0.280804E+09 0.470195E+09 0.427382E+09
April 0.550044E+09 0.235058E+09 0.314986E+09 0.575882E+09 0.282984E+09
May 0.663989E+09 0.252408E+09 0.411582E+09 0.803568E+09 0.162241E+09
June 0.702057E+09 0.283331E+09 0.418726E+09 0.968450E+09 60898204.53
July 0.678728E+09 0.255057E+09 0.423671E+09 0.102412E+10 15818321.00
August 0.750935E+09 0.347199E+09 0.403736E+09 0.111820E+10 37922988.37
September 0.517041E+09 0.225725E+09 0.291316E+09 0.681694E+09 0.105522E+09
October 0.530121E+09 0.258241E+09 0.271880E+09 0.609550E+09 0.258269E+09
November 0.241596E+09 70580626.93 0.171015E+09 0.164835E+09 0.425730E+09
December 0.220511E+09 95188244.85 0.125323E+09 0.135623E+09 0.592994E+09
           
Annual Sum or Average 0.593641E+10 0.250343E+10 0.343299E+10 0.691060E+10 0.362172E+10
Minimum of Months 0.220511E+09 70580626.93 0.125323E+09 0.135623E+09 15818321.00
Maximum of Months 0.750935E+09 0.347199E+09 0.423671E+09 0.111820E+10 0.654367E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 62085473.63 0.00 62085473.63 3929820.02 0.363400E+09
February 76739382.29 0.00 76739382.29 7578722.51 0.335664E+09
March 0.117848E+09 2454.62 0.117846E+09 43601677.06 0.240056E+09
April 0.137245E+09 565514.21 0.136680E+09 91860771.19 0.154022E+09
May 0.188627E+09 6903211.21 0.181724E+09 0.188860E+09 86890530.28
June 0.192578E+09 10242901.02 0.182335E+09 0.250802E+09 38168815.51
July 0.193148E+09 7538040.63 0.185610E+09 0.302608E+09 11384148.41
August 0.170807E+09 2269513.75 0.168538E+09 0.266176E+09 22688535.04
September 0.124465E+09 72357.39 0.124392E+09 0.145156E+09 62508890.35
October 0.111214E+09 0.00 0.111214E+09 88524769.55 0.142571E+09
November 75489568.31 0.00 75489568.31 24089198.21 0.231427E+09
December 54155055.53 0.00 54155055.53 2687573.28 0.328014E+09
           
Annual Sum or Average 0.150440E+10 27593992.83 0.147681E+10 0.141587E+10 0.201679E+10
Minimum of Months 54155055.53 0.00 54155055.53 2687573.28 11384148.41
Maximum of Months 0.193148E+09 10242901.02 0.185610E+09 0.302608E+09 0.363400E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.239844E+09 98462657.35 0.141382E+09 0.151531E+09 0.647433E+09
February 0.318223E+09 0.139658E+09 0.178565E+09 0.224405E+09 0.588152E+09
March 0.523325E+09 0.242520E+09 0.280804E+09 0.481841E+09 0.421474E+09
April 0.550044E+09 0.235058E+09 0.314986E+09 0.580439E+09 0.282100E+09
May 0.663989E+09 0.252408E+09 0.411582E+09 0.796881E+09 0.168062E+09
June 0.702057E+09 0.283331E+09 0.418726E+09 0.951833E+09 72985558.81
July 0.678728E+09 0.255057E+09 0.423671E+09 0.101772E+10 21252315.00
August 0.750935E+09 0.347199E+09 0.403736E+09 0.111747E+10 43022023.65
September 0.517041E+09 0.225725E+09 0.291316E+09 0.679017E+09 0.114650E+09
October 0.530121E+09 0.258241E+09 0.271880E+09 0.617455E+09 0.258928E+09
November 0.241596E+09 70580626.93 0.171015E+09 0.174304E+09 0.418489E+09
December 0.220511E+09 95188244.85 0.125323E+09 0.144316E+09 0.584363E+09
           
Annual Sum or Average 0.593641E+10 0.250343E+10 0.343299E+10 0.693721E+10 0.362091E+10
Minimum of Months 0.220511E+09 70580626.93 0.125323E+09 0.144316E+09 21252315.00
Maximum of Months 0.750935E+09 0.347199E+09 0.423671E+09 0.111747E+10 0.647433E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.258114E+09 0.169378E+09 88736490.59 0.252492E+09 0.265725E+09
February 0.308532E+09 0.205058E+09 0.103473E+09 0.293033E+09 0.281893E+09
March 0.302648E+09 0.166604E+09 0.136044E+09 0.300890E+09 0.245480E+09
April 0.233129E+09 94317873.29 0.138811E+09 0.236750E+09 0.180058E+09
May 0.206904E+09 42360323.35 0.164544E+09 0.218409E+09 0.119838E+09
June 0.189067E+09 29130958.40 0.159936E+09 0.235408E+09 63488679.14
July 0.203282E+09 34309663.55 0.168973E+09 0.286649E+09 37492584.72
August 0.272276E+09 0.100440E+09 0.171837E+09 0.392672E+09 49239807.84
September 0.278056E+09 0.139608E+09 0.138449E+09 0.355529E+09 91810725.07
October 0.406038E+09 0.254620E+09 0.151418E+09 0.485075E+09 0.165147E+09
November 0.272085E+09 0.163216E+09 0.108869E+09 0.269631E+09 0.234399E+09
December 0.278864E+09 0.198063E+09 80800618.01 0.271589E+09 0.284383E+09
           
Annual Sum or Average 0.320900E+10 0.159710E+10 0.161189E+10 0.359813E+10 0.201895E+10
Minimum of Months 0.189067E+09 29130958.40 80800618.01 0.218409E+09 37492584.72
Maximum of Months 0.406038E+09 0.254620E+09 0.171837E+09 0.485075E+09 0.284383E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 49674962.73 0.00 49674962.73 2153401.85 0.305343E+09
February 61399643.62 0.00 61399643.62 5205628.84 0.279298E+09
March 94290864.36 1963.96 94288900.41 34372280.97 0.197052E+09
April 0.109811E+09 452471.34 0.109358E+09 75636488.89 0.124808E+09
May 0.150921E+09 5523301.01 0.145398E+09 0.158410E+09 67804846.40
June 0.154082E+09 8195407.02 0.145887E+09 0.212207E+09 26487307.31
July 0.154539E+09 6031231.87 0.148507E+09 0.253871E+09 6775660.87
August 0.136664E+09 1815851.67 0.134848E+09 0.225718E+09 14858196.39
September 99584946.32 57893.59 99527052.73 0.122947E+09 46202933.90
October 88983113.67 0.00 88983113.67 74683918.48 0.111078E+09
November 60399659.90 0.00 60399659.90 18065266.28 0.194469E+09
December 43329787.27 0.00 43329787.27 1558693.53 0.276560E+09
           
Annual Sum or Average 0.120368E+10 22078120.45 0.118160E+10 0.118483E+10 0.165074E+10
Minimum of Months 43329787.27 0.00 43329787.27 1558693.53 6775660.87
Maximum of Months 0.154539E+09 8195407.02 0.148507E+09 0.253871E+09 0.305343E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.241522E+09 96495417.54 0.145026E+09 0.140828E+09 0.643865E+09
February 0.338694E+09 0.157722E+09 0.180972E+09 0.228448E+09 0.577204E+09
March 0.481538E+09 0.204650E+09 0.276888E+09 0.418150E+09 0.429387E+09
April 0.557847E+09 0.244845E+09 0.313002E+09 0.579804E+09 0.274710E+09
May 0.695935E+09 0.277340E+09 0.418595E+09 0.844425E+09 0.157205E+09
June 0.625383E+09 0.226521E+09 0.398862E+09 0.863801E+09 58058836.11
July 0.648197E+09 0.233361E+09 0.414837E+09 0.984867E+09 14963564.23
August 0.731240E+09 0.329905E+09 0.401335E+09 0.109018E+10 35548042.60
September 0.529355E+09 0.238470E+09 0.290885E+09 0.695999E+09 0.101262E+09
October 0.494167E+09 0.223686E+09 0.270480E+09 0.558990E+09 0.251319E+09
November 0.296195E+09 0.113821E+09 0.182374E+09 0.234801E+09 0.415440E+09
December 0.239288E+09 0.112907E+09 0.126381E+09 0.155844E+09 0.579815E+09
           
Annual Sum or Average 0.587936E+10 0.245972E+10 0.341964E+10 0.679614E+10 0.353878E+10
Minimum of Months 0.239288E+09 96495417.54 0.126381E+09 0.140828E+09 14963564.23
Maximum of Months 0.731240E+09 0.329905E+09 0.418595E+09 0.109018E+10 0.643865E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.322707E+09 0.211765E+09 0.110943E+09 0.319927E+09 0.323591E+09
February 0.385741E+09 0.256374E+09 0.129367E+09 0.389050E+09 0.289959E+09
March 0.378385E+09 0.208296E+09 0.170089E+09 0.403051E+09 0.227319E+09
April 0.291469E+09 0.117921E+09 0.173548E+09 0.326549E+09 0.153957E+09
May 0.258682E+09 52960934.60 0.205721E+09 0.313647E+09 88438173.83
June 0.236380E+09 36420939.70 0.199959E+09 0.339565E+09 32199645.35
July 0.254153E+09 42895608.52 0.211258E+09 0.411756E+09 8097151.49
August 0.340413E+09 0.125575E+09 0.214838E+09 0.541108E+09 19708426.48
September 0.347639E+09 0.174544E+09 0.173095E+09 0.482617E+09 55613056.29
October 0.507648E+09 0.318338E+09 0.189310E+09 0.644332E+09 0.133020E+09
November 0.340174E+09 0.204060E+09 0.136113E+09 0.367394E+09 0.214515E+09
December 0.348649E+09 0.247629E+09 0.101021E+09 0.361640E+09 0.288806E+09
           
Annual Sum or Average 0.401204E+10 0.199678E+10 0.201526E+10 0.490063E+10 0.183522E+10
Minimum of Months 0.236380E+09 36420939.70 0.101021E+09 0.313647E+09 8097151.49
Maximum of Months 0.507648E+09 0.318338E+09 0.214838E+09 0.644332E+09 0.323591E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 62085473.63 0.00 62085473.63 3500378.64 0.363257E+09
February 76739382.29 0.00 76739382.29 7013729.89 0.335651E+09
March 0.117848E+09 2454.62 0.117846E+09 41655711.38 0.238030E+09
April 0.137245E+09 565514.21 0.136680E+09 89467238.42 0.152781E+09
May 0.188627E+09 6903211.21 0.181724E+09 0.186836E+09 85079572.00
June 0.192578E+09 10242901.02 0.182335E+09 0.251532E+09 35630950.23
July 0.193148E+09 7538040.63 0.185610E+09 0.301314E+09 10672182.23
August 0.170807E+09 2269513.75 0.168538E+09 0.263790E+09 21659682.92
September 0.124465E+09 72357.39 0.124392E+09 0.142995E+09 60596978.95
October 0.111214E+09 0.00 0.111214E+09 86434540.41 0.139301E+09
November 75489568.31 0.00 75489568.31 22691577.63 0.231991E+09
December 54155055.53 0.00 54155055.53 2309357.52 0.327919E+09
           
Annual Sum or Average 0.150440E+10 27593992.83 0.147681E+10 0.139954E+10 0.200257E+10
Minimum of Months 54155055.53 0.00 54155055.53 2309357.52 10672182.23
Maximum of Months 0.193148E+09 10242901.02 0.185610E+09 0.301314E+09 0.363257E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.241522E+09 96495417.54 0.145026E+09 0.145296E+09 0.633651E+09
February 0.338694E+09 0.157722E+09 0.180972E+09 0.235142E+09 0.563523E+09
March 0.481538E+09 0.204650E+09 0.276888E+09 0.428657E+09 0.421490E+09
April 0.557847E+09 0.244845E+09 0.313002E+09 0.584583E+09 0.273038E+09
May 0.695935E+09 0.277340E+09 0.418595E+09 0.839407E+09 0.162312E+09
June 0.625383E+09 0.226521E+09 0.398862E+09 0.849700E+09 68314705.03
July 0.648197E+09 0.233361E+09 0.414837E+09 0.976350E+09 20117519.17
August 0.731240E+09 0.329905E+09 0.401335E+09 0.108579E+10 40084381.17
September 0.529355E+09 0.238470E+09 0.290885E+09 0.692441E+09 0.108835E+09
October 0.494167E+09 0.223686E+09 0.270480E+09 0.567331E+09 0.249565E+09
November 0.296195E+09 0.113821E+09 0.182374E+09 0.242773E+09 0.406456E+09
December 0.239288E+09 0.112907E+09 0.126381E+09 0.160541E+09 0.566463E+09
           
Annual Sum or Average 0.587936E+10 0.245972E+10 0.341964E+10 0.680801E+10 0.351385E+10
Minimum of Months 0.239288E+09 96495417.54 0.126381E+09 0.145296E+09 20117519.17
Maximum of Months 0.731240E+09 0.329905E+09 0.418595E+09 0.108579E+10 0.633651E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 78627334.97 0.00 78627334.97 2794991.17 0.494754E+09
February 97185585.68 0.00 97185585.68 7425908.95 0.454111E+09
March 0.149247E+09 3108.62 0.149244E+09 53431578.11 0.317343E+09
April 0.173812E+09 716188.06 0.173096E+09 0.120191E+09 0.203712E+09
May 0.238884E+09 8742481.42 0.230142E+09 0.249983E+09 0.114873E+09
June 0.243887E+09 12971987.85 0.230915E+09 0.326634E+09 52858969.92
July 0.244609E+09 9546452.84 0.235063E+09 0.378671E+09 21192049.97
August 0.216317E+09 2874195.96 0.213443E+09 0.329606E+09 37670866.88
September 0.157627E+09 91636.07 0.157535E+09 0.184728E+09 88602550.03
October 0.140846E+09 0.00 0.140846E+09 0.111048E+09 0.195659E+09
November 95602775.14 0.00 95602775.14 27496586.12 0.315306E+09
December 68583960.84 0.00 68583960.84 2082042.68 0.448334E+09
           
Annual Sum or Average 0.190523E+10 34946050.83 0.187028E+10 0.179409E+10 0.274442E+10
Minimum of Months 68583960.84 0.00 68583960.84 2082042.68 21192049.97
Maximum of Months 0.244609E+09 12971987.85 0.235063E+09 0.378671E+09 0.494754E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 28985291.37 0.00 28985291.37 1030349.48 0.182387E+09
February 35826631.02 0.00 35826631.02 2737497.52 0.167404E+09
March 55018625.63 1145.97 55017479.66 19697092.12 0.116986E+09
April 64074374.08 264016.58 63810357.50 44307474.09 75096634.27
May 88062541.06 3222840.65 84839700.41 92154263.84 42346811.60
June 89906978.19 4782011.85 85124966.34 0.120411E+09 19486005.03
July 90173173.31 3519217.80 86653955.51 0.139594E+09 7812267.11
August 79743320.60 1059547.64 78683772.95 0.121506E+09 13887041.36
September 58107717.19 33780.85 58073936.34 68098453.81 32662568.68
October 51921558.38 0.00 51921558.38 40936805.62 72128057.10
November 35243141.51 0.00 35243141.51 10136380.19 0.116235E+09
December 25282887.80 0.00 25282887.80 767527.14 0.165274E+09
           
Annual Sum or Average 0.702346E+09 12882561.34 0.689464E+09 0.661377E+09 0.101171E+10
Minimum of Months 25282887.80 0.00 25282887.80 767527.14 7812267.11
Maximum of Months 90173173.31 4782011.85 86653955.51 0.139594E+09 0.182387E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.150574E+09 98808493.80 51765403.86 0.148845E+09 0.159382E+09
February 0.179985E+09 0.119623E+09 60362290.71 0.182292E+09 0.141551E+09
March 0.176553E+09 97190004.50 79362917.17 0.191135E+09 0.110160E+09
April 0.135998E+09 55021364.60 80976996.46 0.155943E+09 75221666.53
May 0.120700E+09 24711358.67 95988587.17 0.149928E+09 45268493.79
June 0.110294E+09 16993863.70 93300242.89 0.157962E+09 20619143.23
July 0.118587E+09 20014918.08 98572006.58 0.188894E+09 7985713.97
August 0.158835E+09 58592560.64 0.100243E+09 0.249700E+09 14289173.68
September 0.162207E+09 81441637.01 80765468.23 0.225453E+09 32276598.11
October 0.236867E+09 0.148535E+09 88331451.67 0.303128E+09 68355750.52
November 0.158724E+09 95213646.52 63509953.91 0.172627E+09 0.104875E+09
December 0.162678E+09 0.115543E+09 47135925.66 0.169085E+09 0.141894E+09
           
Annual Sum or Average 0.187200E+10 0.931688E+09 0.940314E+09 0.229499E+10 0.921879E+09
Minimum of Months 0.110294E+09 16993863.70 47135925.66 0.148845E+09 7985713.97
Maximum of Months 0.236867E+09 0.148535E+09 0.100243E+09 0.303128E+09 0.159382E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.408688E+09 0.268186E+09 0.140502E+09 0.403995E+09 0.432596E+09
February 0.488517E+09 0.324681E+09 0.163836E+09 0.494777E+09 0.384199E+09
March 0.479201E+09 0.263794E+09 0.215407E+09 0.518780E+09 0.298997E+09
April 0.369127E+09 0.149339E+09 0.219788E+09 0.423261E+09 0.204167E+09
May 0.327604E+09 67071682.02 0.260533E+09 0.406934E+09 0.122868E+09
June 0.299361E+09 46124822.10 0.253236E+09 0.428740E+09 55964572.29
July 0.321869E+09 54324581.63 0.267545E+09 0.512696E+09 21674861.16
August 0.431112E+09 0.159032E+09 0.272079E+09 0.677736E+09 38783740.14
September 0.440263E+09 0.221049E+09 0.219214E+09 0.611926E+09 87605289.31
October 0.642904E+09 0.403155E+09 0.239750E+09 0.822753E+09 0.185531E+09
November 0.430808E+09 0.258429E+09 0.172379E+09 0.468545E+09 0.284653E+09
December 0.441543E+09 0.313606E+09 0.127937E+09 0.458930E+09 0.385129E+09
           
Annual Sum or Average 0.508100E+10 0.252879E+10 0.255220E+10 0.622907E+10 0.250217E+10
Minimum of Months 0.299361E+09 46124822.10 0.127937E+09 0.403995E+09 21674861.16
Maximum of Months 0.642904E+09 0.403155E+09 0.272079E+09 0.822753E+09 0.432596E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.322707E+09 0.211765E+09 0.110943E+09 0.319965E+09 0.321913E+09
February 0.385741E+09 0.256374E+09 0.129367E+09 0.389639E+09 0.289093E+09
March 0.378385E+09 0.208296E+09 0.170089E+09 0.402914E+09 0.228373E+09
April 0.291469E+09 0.117921E+09 0.173548E+09 0.326434E+09 0.154183E+09
May 0.258682E+09 52960934.60 0.205721E+09 0.312637E+09 89119700.79
June 0.236380E+09 36420939.70 0.199959E+09 0.336610E+09 32601621.60
July 0.254153E+09 42895608.52 0.211258E+09 0.409258E+09 7972808.50
August 0.340413E+09 0.125575E+09 0.214838E+09 0.538743E+09 19475966.16
September 0.347639E+09 0.174544E+09 0.173095E+09 0.481000E+09 55042232.20
October 0.507648E+09 0.318338E+09 0.189310E+09 0.642290E+09 0.132485E+09
November 0.340174E+09 0.204060E+09 0.136113E+09 0.368498E+09 0.211865E+09
December 0.348649E+09 0.247629E+09 0.101021E+09 0.362200E+09 0.286635E+09
           
Annual Sum or Average 0.401204E+10 0.199678E+10 0.201526E+10 0.489019E+10 0.182876E+10
Minimum of Months 0.236380E+09 36420939.70 0.101021E+09 0.312637E+09 7972808.50
Maximum of Months 0.507648E+09 0.318338E+09 0.214838E+09 0.642290E+09 0.321913E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.239844E+09 98462657.35 0.141382E+09 0.144015E+09 0.650323E+09
February 0.318223E+09 0.139658E+09 0.178565E+09 0.213159E+09 0.594955E+09
March 0.523325E+09 0.242520E+09 0.280804E+09 0.466660E+09 0.424867E+09
April 0.550044E+09 0.235058E+09 0.314986E+09 0.571303E+09 0.280746E+09
May 0.663989E+09 0.252408E+09 0.411582E+09 0.796630E+09 0.160844E+09
June 0.702057E+09 0.283331E+09 0.418726E+09 0.961366E+09 59317504.30
July 0.678728E+09 0.255057E+09 0.423671E+09 0.101809E+10 14678414.94
August 0.750935E+09 0.347199E+09 0.403736E+09 0.111285E+10 36039378.97
September 0.517041E+09 0.225725E+09 0.291316E+09 0.677681E+09 0.102833E+09
October 0.530121E+09 0.258241E+09 0.271880E+09 0.605730E+09 0.254236E+09
November 0.241596E+09 70580626.93 0.171015E+09 0.164677E+09 0.421097E+09
December 0.220511E+09 95188244.85 0.125323E+09 0.135778E+09 0.587947E+09
           
Annual Sum or Average 0.593641E+10 0.250343E+10 0.343299E+10 0.686794E+10 0.358789E+10
Minimum of Months 0.220511E+09 70580626.93 0.125323E+09 0.135778E+09 14678414.94
Maximum of Months 0.750935E+09 0.347199E+09 0.423671E+09 0.111285E+10 0.650323E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 62085473.63 0.00 62085473.63 4210546.46 0.360983E+09
February 76739382.29 0.00 76739382.29 7837026.90 0.334266E+09
March 0.117848E+09 2454.62 0.117846E+09 43704551.97 0.238792E+09
April 0.137245E+09 565514.21 0.136680E+09 91100337.26 0.153263E+09
May 0.188627E+09 6903211.21 0.181724E+09 0.185658E+09 87432896.20
June 0.192578E+09 10242901.02 0.182335E+09 0.247756E+09 39151921.76
July 0.193148E+09 7538040.63 0.185610E+09 0.300588E+09 11325850.92
August 0.170807E+09 2269513.75 0.168538E+09 0.265222E+09 22111628.57
September 0.124465E+09 72357.39 0.124392E+09 0.144245E+09 62226723.50
October 0.111214E+09 0.00 0.111214E+09 88778885.11 0.140713E+09
November 75489568.31 0.00 75489568.31 24691433.11 0.228209E+09
December 54155055.53 0.00 54155055.53 2979612.70 0.324541E+09
           
Annual Sum or Average 0.150440E+10 27593992.83 0.147681E+10 0.140677E+10 0.200302E+10
Minimum of Months 54155055.53 0.00 54155055.53 2979612.70 11325850.92
Maximum of Months 0.193148E+09 10242901.02 0.185610E+09 0.300588E+09 0.360983E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.239844E+09 98462657.35 0.141382E+09 0.151718E+09 0.643695E+09
February 0.318223E+09 0.139658E+09 0.178565E+09 0.223648E+09 0.585881E+09
March 0.523325E+09 0.242520E+09 0.280804E+09 0.479350E+09 0.418695E+09
April 0.550044E+09 0.235058E+09 0.314986E+09 0.575862E+09 0.280299E+09
May 0.663989E+09 0.252408E+09 0.411582E+09 0.788396E+09 0.168618E+09
June 0.702057E+09 0.283331E+09 0.418726E+09 0.942730E+09 74624774.10
July 0.678728E+09 0.255057E+09 0.423671E+09 0.101136E+10 20964889.05
August 0.750935E+09 0.347199E+09 0.403736E+09 0.111243E+10 41755704.91
September 0.517041E+09 0.225725E+09 0.291316E+09 0.674723E+09 0.113598E+09
October 0.530121E+09 0.258241E+09 0.271880E+09 0.614777E+09 0.255123E+09
November 0.241596E+09 70580626.93 0.171015E+09 0.175053E+09 0.413325E+09
December 0.220511E+09 95188244.85 0.125323E+09 0.145134E+09 0.579363E+09
           
Annual Sum or Average 0.593641E+10 0.250343E+10 0.343299E+10 0.689519E+10 0.359594E+10
Minimum of Months 0.220511E+09 70580626.93 0.125323E+09 0.145134E+09 20964889.05
Maximum of Months 0.750935E+09 0.347199E+09 0.423671E+09 0.111243E+10 0.643695E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.473281E+09 0.310573E+09 0.162708E+09 0.454368E+09 0.491010E+09
February 0.565726E+09 0.375997E+09 0.189730E+09 0.554285E+09 0.441390E+09
March 0.554938E+09 0.305486E+09 0.249452E+09 0.580553E+09 0.344758E+09
April 0.427468E+09 0.172942E+09 0.254525E+09 0.474337E+09 0.229166E+09
May 0.379382E+09 77672293.27 0.301710E+09 0.461409E+09 0.128679E+09
June 0.346674E+09 53414803.41 0.293260E+09 0.502200E+09 44016097.34
July 0.372740E+09 62910526.60 0.309830E+09 0.610069E+09 9667503.40
August 0.499248E+09 0.184167E+09 0.315081E+09 0.798125E+09 26194167.46
September 0.509846E+09 0.255986E+09 0.253861E+09 0.705190E+09 80033758.63
October 0.744515E+09 0.466873E+09 0.277642E+09 0.934208E+09 0.198987E+09
November 0.498897E+09 0.299274E+09 0.199623E+09 0.526027E+09 0.327201E+09
December 0.511328E+09 0.363171E+09 0.148157E+09 0.515223E+09 0.439746E+09
           
Annual Sum or Average 0.588404E+10 0.292847E+10 0.295558E+10 0.711599E+10 0.276085E+10
Minimum of Months 0.346674E+09 53414803.41 0.148157E+09 0.454368E+09 9667503.40
Maximum of Months 0.744515E+09 0.466873E+09 0.315081E+09 0.934208E+09 0.491010E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.434582E+09 0.00 0.434582E+09 6327816.72 0.302326E+10
February 0.537155E+09 0.00 0.537155E+09 25804686.09 0.275856E+10
March 0.824904E+09 17181.70 0.824887E+09 0.229288E+09 0.202576E+10
April 0.960679E+09 3958449.54 0.956721E+09 0.559528E+09 0.132436E+10
May 0.132034E+10 48320648.33 0.127202E+10 0.123314E+10 0.743398E+09
June 0.134799E+10 71697591.63 0.127629E+10 0.171658E+10 0.335436E+09
July 0.135198E+10 52764286.00 0.129922E+10 0.202210E+10 0.143517E+09
August 0.119561E+10 15885994.55 0.117972E+10 0.177558E+10 0.223431E+09
September 0.871220E+09 506482.57 0.870713E+09 0.962905E+09 0.553179E+09
October 0.778470E+09 0.00 0.778470E+09 0.556231E+09 0.119046E+10
November 0.528407E+09 0.00 0.528407E+09 0.111864E+09 0.200596E+10
December 0.379071E+09 0.00 0.379071E+09 5329751.12 0.278444E+10
           
Annual Sum or Average 0.105304E+11 0.193151E+09 0.103373E+11 0.920467E+10 0.171118E+11
Minimum of Months 0.379071E+09 0.00 0.379071E+09 5329751.12 0.143517E+09
Maximum of Months 0.135198E+10 71697591.63 0.129922E+10 0.202210E+10 0.302326E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.434582E+09 0.00 0.434582E+09 4065217.34 0.311594E+10
February 0.537155E+09 0.00 0.537155E+09 21243687.90 0.283883E+10
March 0.824904E+09 17181.70 0.824887E+09 0.210108E+09 0.209019E+10
April 0.960679E+09 3958449.54 0.956721E+09 0.532038E+09 0.136873E+10
May 0.132034E+10 48320648.33 0.127202E+10 0.119904E+10 0.767451E+09
June 0.134799E+10 71697591.63 0.127629E+10 0.169178E+10 0.350188E+09
July 0.135198E+10 52764286.00 0.129922E+10 0.199922E+10 0.154541E+09
August 0.119561E+10 15885994.55 0.117972E+10 0.175245E+10 0.234910E+09
September 0.871220E+09 506482.57 0.870713E+09 0.940470E+09 0.575868E+09
October 0.778470E+09 0.00 0.778470E+09 0.532605E+09 0.122806E+10
November 0.528407E+09 0.00 0.528407E+09 0.100161E+09 0.207544E+10
December 0.379071E+09 0.00 0.379071E+09 3885915.31 0.287218E+10
           
Annual Sum or Average 0.105304E+11 0.193151E+09 0.103373E+11 0.898707E+10 0.176723E+11
Minimum of Months 0.379071E+09 0.00 0.379071E+09 3885915.31 0.154541E+09
Maximum of Months 0.135198E+10 71697591.63 0.129922E+10 0.199922E+10 0.311594E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 62085473.63 0.00 62085473.63 5919911.39 0.375606E+09
February 76739382.29 0.00 76739382.29 9817939.68 0.345156E+09
March 0.117848E+09 2454.62 0.117846E+09 53782817.87 0.247000E+09
April 0.137245E+09 565514.21 0.136680E+09 0.119300E+09 0.162263E+09
May 0.188627E+09 6903211.21 0.181724E+09 0.241332E+09 94990614.81
June 0.192578E+09 10242901.02 0.182335E+09 0.319704E+09 42950838.34
July 0.193148E+09 7538040.63 0.185610E+09 0.373692E+09 19108535.39
August 0.170807E+09 2269513.75 0.168538E+09 0.333084E+09 28291428.51
September 0.124465E+09 72357.39 0.124392E+09 0.198463E+09 63077374.74
October 0.111214E+09 0.00 0.111214E+09 0.120119E+09 0.138408E+09
November 75489568.31 0.00 75489568.31 31696851.97 0.240313E+09
December 54155055.53 0.00 54155055.53 4384091.17 0.338461E+09
           
Annual Sum or Average 0.150440E+10 27593992.83 0.147681E+10 0.181130E+10 0.209563E+10
Minimum of Months 54155055.53 0.00 54155055.53 4384091.17 19108535.39
Maximum of Months 0.193148E+09 10242901.02 0.185610E+09 0.373692E+09 0.375606E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.483009E+09 0.192977E+09 0.290032E+09 0.310676E+09 0.131779E+10
February 0.677341E+09 0.315422E+09 0.361918E+09 0.495663E+09 0.116423E+10
March 0.963008E+09 0.409271E+09 0.553737E+09 0.916608E+09 0.886335E+09
April 0.111562E+10 0.489656E+09 0.625960E+09 0.128875E+10 0.587116E+09
May 0.139177E+10 0.554641E+09 0.837130E+09 0.187488E+10 0.356890E+09
June 0.125068E+10 0.453010E+09 0.797667E+09 0.194954E+10 0.161276E+09
July 0.129630E+10 0.466688E+09 0.829615E+09 0.222059E+10 72002850.17
August 0.146238E+10 0.659763E+09 0.802613E+09 0.243019E+10 0.105924E+09
September 0.105863E+10 0.476906E+09 0.581729E+09 0.159723E+10 0.231862E+09
October 0.988263E+09 0.447341E+09 0.540922E+09 0.127637E+10 0.503213E+09
November 0.592348E+09 0.227626E+09 0.364722E+09 0.535732E+09 0.844529E+09
December 0.478542E+09 0.225798E+09 0.252744E+09 0.344517E+09 0.117402E+10
           
Annual Sum or Average 0.117579E+11 0.491910E+10 0.683879E+10 0.152407E+11 0.740518E+10
Minimum of Months 0.478542E+09 0.192977E+09 0.252744E+09 0.310676E+09 72002850.17
Maximum of Months 0.146238E+10 0.659763E+09 0.837130E+09 0.243019E+10 0.131779E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.322707E+09 0.211765E+09 0.110943E+09 0.332047E+09 0.333605E+09
February 0.385741E+09 0.256374E+09 0.129367E+09 0.405264E+09 0.295635E+09
March 0.378385E+09 0.208296E+09 0.170089E+09 0.428811E+09 0.235540E+09
April 0.291469E+09 0.117921E+09 0.173548E+09 0.360346E+09 0.162829E+09
May 0.258682E+09 52960934.60 0.205721E+09 0.363634E+09 98992723.38
June 0.236380E+09 36420939.70 0.199959E+09 0.398009E+09 44675121.40
July 0.254153E+09 42895608.52 0.211258E+09 0.478115E+09 19482260.96
August 0.340413E+09 0.125575E+09 0.214838E+09 0.608213E+09 28524911.69
September 0.347639E+09 0.174544E+09 0.173095E+09 0.537803E+09 62559101.49
October 0.507648E+09 0.318338E+09 0.189310E+09 0.689521E+09 0.135047E+09
November 0.340174E+09 0.204060E+09 0.136113E+09 0.388794E+09 0.220182E+09
December 0.348649E+09 0.247629E+09 0.101021E+09 0.376257E+09 0.296384E+09
           
Annual Sum or Average 0.401204E+10 0.199678E+10 0.201526E+10 0.536681E+10 0.193346E+10
Minimum of Months 0.236380E+09 36420939.70 0.101021E+09 0.332047E+09 19482260.96
Maximum of Months 0.507648E+09 0.318338E+09 0.214838E+09 0.689521E+09 0.333605E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 78627334.97 0.00 78627334.97 2062530.47 0.504425E+09
February 97185585.68 0.00 97185585.68 6229411.87 0.463343E+09
March 0.149247E+09 3108.62 0.149244E+09 48182621.73 0.325107E+09
April 0.173812E+09 716188.06 0.173096E+09 0.112809E+09 0.208242E+09
May 0.238884E+09 8742481.42 0.230142E+09 0.239006E+09 0.118384E+09
June 0.243887E+09 12971987.85 0.230915E+09 0.315445E+09 55983645.88
July 0.244609E+09 9546452.84 0.235063E+09 0.364747E+09 25276959.95
August 0.216317E+09 2874195.96 0.213443E+09 0.318154E+09 40138896.28
September 0.157627E+09 91636.07 0.157535E+09 0.177696E+09 90570844.36
October 0.140846E+09 0.00 0.140846E+09 0.106331E+09 0.194406E+09
November 95602775.14 0.00 95602775.14 24980627.24 0.321324E+09
December 68583960.84 0.00 68583960.84 1588982.08 0.458267E+09
           
Annual Sum or Average 0.190523E+10 34946050.83 0.187028E+10 0.171723E+10 0.280547E+10
Minimum of Months 68583960.84 0.00 68583960.84 1588982.08 25276959.95
Maximum of Months 0.244609E+09 12971987.85 0.235063E+09 0.364747E+09 0.504425E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70348174.52 0.00 70348174.52 1845353.83 0.451292E+09
February 86952311.75 0.00 86952311.75 5573478.40 0.414555E+09
March 0.133532E+09 2781.30 0.133529E+09 43109174.23 0.290875E+09
April 0.155510E+09 640776.17 0.154870E+09 0.100931E+09 0.186315E+09
May 0.213730E+09 7821931.26 0.205909E+09 0.213840E+09 0.105918E+09
June 0.218207E+09 11606086.68 0.206601E+09 0.282230E+09 50088780.09
July 0.218853E+09 8541247.52 0.210312E+09 0.326340E+09 22615391.84
August 0.193539E+09 2571554.02 0.190968E+09 0.284653E+09 35912422.58
September 0.141029E+09 81987.14 0.140947E+09 0.158985E+09 81034077.62
October 0.126015E+09 0.00 0.126015E+09 95134709.51 0.173936E+09
November 85536165.15 0.00 85536165.15 22350261.85 0.287486E+09
December 61362329.63 0.00 61362329.63 1421668.29 0.409958E+09
           
Annual Sum or Average 0.170462E+10 31266364.09 0.167335E+10 0.153641E+10 0.250999E+10
Minimum of Months 61362329.63 0.00 61362329.63 1421668.29 22615391.84
Maximum of Months 0.218853E+09 11606086.68 0.210312E+09 0.326340E+09 0.451292E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.120476E+10 0.790580E+09 0.414182E+09 0.117359E+10 0.129655E+10
February 0.144009E+10 0.957120E+09 0.482967E+09 0.143796E+10 0.114962E+10
March 0.141262E+10 0.777630E+09 0.634994E+09 0.150171E+10 0.902236E+09
April 0.108814E+10 0.440233E+09 0.647908E+09 0.121838E+10 0.617044E+09
May 0.965737E+09 0.197719E+09 0.768018E+09 0.116421E+10 0.374940E+09
June 0.882478E+09 0.135970E+09 0.746508E+09 0.122757E+10 0.175589E+09
July 0.948830E+09 0.160142E+09 0.788688E+09 0.146653E+10 76292809.71
August 0.127086E+10 0.468807E+09 0.802056E+09 0.195758E+10 0.122053E+09
September 0.129784E+10 0.651626E+09 0.646216E+09 0.177607E+10 0.264631E+09
October 0.189520E+10 0.118845E+10 0.706752E+09 0.240012E+10 0.544118E+09
November 0.126997E+10 0.761817E+09 0.508152E+09 0.136213E+10 0.853080E+09
December 0.130161E+10 0.924471E+09 0.377141E+09 0.133460E+10 0.115589E+10
           
Annual Sum or Average 0.149781E+11 0.745457E+10 0.752358E+10 0.180204E+11 0.753204E+10
Minimum of Months 0.882478E+09 0.135970E+09 0.377141E+09 0.116421E+10 76292809.71
Maximum of Months 0.189520E+10 0.118845E+10 0.802056E+09 0.240012E+10 0.129655E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 603.30 602.95 609.38 399.88 209.50 0.00 0.00
February 814.23 597.44 806.45 535.99 270.46 0.00 0.00
March 766.94 423.82 714.52 393.33 321.18 0.00 0.00
April 645.29 298.18 568.74 230.10 338.64 0.00 0.00
May 603.81 169.99 488.48 100.01 388.47 0.00 0.00
June 654.79 80.05 461.24 71.07 390.17 0.00 0.00
July 748.56 32.97 479.92 81.00 398.92 0.00 0.00
August 987.25 60.43 642.81 237.13 405.68 0.00 0.00
September 929.40 129.67 678.34 340.59 337.75 0.00 0.00
October 1208.00 269.44 958.61 601.13 357.48 0.00 0.00
November 715.54 417.78 663.77 398.18 265.59 0.00 0.00
December 679.69 542.17 658.37 467.61 190.76 0.00 0.00
               
Annual Sum or Average 779.93 300.42 643.45 320.24 323.20 0.00 0.00
Minimum of Months 603.30 32.97 461.24 71.07 190.76 0.00 0.00
Maximum of Months 1208.00 602.95 958.61 601.13 405.68 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1678.06 1751.23 1715.97 1126.05 589.93 0.00 0.00
February 2264.07 1740.12 2270.92 1509.32 761.60 0.00 0.00
March 2131.50 1266.22 2012.03 1107.60 904.43 0.00 0.00
April 1786.72 908.11 1601.52 647.94 953.59 0.00 0.00
May 1659.67 539.19 1375.52 281.62 1093.90 0.00 0.00
June 1815.65 262.59 1298.82 200.12 1098.70 0.00 0.00
July 2087.08 114.51 1351.43 228.09 1123.34 0.00 0.00
August 2762.21 189.13 1810.11 667.74 1142.38 0.00 0.00
September 2589.61 415.79 1910.16 959.07 951.10 0.00 0.00
October 3368.82 828.30 2699.38 1692.74 1006.64 0.00 0.00
November 1983.37 1248.39 1869.14 1121.25 747.90 0.00 0.00
December 1890.29 1591.16 1853.92 1316.75 537.17 0.00 0.00
               
Annual Sum or Average 2168.66 899.84 1811.90 901.78 910.12 0.00 0.00
Minimum of Months 1659.67 114.51 1298.82 200.12 537.17 0.00 0.00
Maximum of Months 3368.82 1751.23 2699.38 1692.74 1142.38 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2211.76 2389.44 2229.15 1462.80 766.35 0.00 0.00
February 2992.97 2355.54 2950.05 1960.69 989.36 0.00 0.00
March 2819.57 1721.15 2613.75 1438.84 1174.91 0.00 0.00
April 2360.40 1245.75 2080.47 841.71 1238.76 0.00 0.00
May 2187.20 744.96 1786.87 365.84 1421.04 0.00 0.00
June 2397.78 359.56 1687.25 259.97 1427.28 0.00 0.00
July 2767.34 154.95 1755.59 296.31 1459.28 0.00 0.00
August 3669.63 246.45 2351.44 867.43 1484.02 0.00 0.00
September 3425.21 559.09 2481.41 1245.88 1235.53 0.00 0.00
October 4459.40 1103.30 3506.65 2198.97 1307.68 0.00 0.00
November 2612.78 1709.19 2428.12 1456.56 971.56 0.00 0.00
December 2491.33 2173.34 2408.35 1710.53 697.81 0.00 0.00
               
Annual Sum or Average 2867.07 1223.85 2353.77 1171.47 1182.30 0.00 0.00
Minimum of Months 2187.20 154.95 1687.25 259.97 697.81 0.00 0.00
Maximum of Months 4459.40 2389.44 3506.65 2198.97 1484.02 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 161.58 353.34 210.03 115.83 94.21 0.00 0.00
February 234.17 351.13 290.99 163.70 127.29 0.00 0.00
March 322.00 240.30 336.66 168.32 168.34 0.00 0.00
April 347.29 167.16 324.66 136.18 188.48 0.00 0.00
May 417.02 93.04 344.49 114.01 230.47 0.00 0.00
June 504.40 36.13 362.05 123.36 238.69 0.00 0.00
July 536.15 9.10 348.30 111.24 237.06 0.00 0.00
August 619.72 21.77 407.46 176.51 230.95 0.00 0.00
September 449.31 62.10 333.60 154.42 179.17 0.00 0.00
October 467.22 145.19 387.46 215.27 172.19 0.00 0.00
November 200.57 241.37 224.45 105.96 118.49 0.00 0.00
December 173.55 316.82 212.50 127.99 84.51 0.00 0.00
               
Annual Sum or Average 370.46 168.77 315.46 142.70 172.76 0.00 0.00
Minimum of Months 161.58 9.10 210.03 105.96 84.51 0.00 0.00
Maximum of Months 619.72 353.34 407.46 215.27 238.69 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 52.82 372.18 112.73 36.76 75.97 0.00 0.00
February 88.95 374.92 163.26 57.73 105.53 0.00 0.00
March 191.14 241.95 239.39 90.55 148.84 0.00 0.00
April 257.92 166.80 265.16 90.90 174.25 0.00 0.00
May 367.13 94.28 318.33 96.82 221.51 0.00 0.00
June 463.54 42.44 345.15 113.26 231.89 0.00 0.00
July 492.86 12.09 325.52 98.04 227.48 0.00 0.00
August 516.49 24.43 344.14 130.48 213.66 0.00 0.00
September 317.52 67.90 247.49 87.11 160.38 0.00 0.00
October 262.10 148.42 239.45 96.42 143.03 0.00 0.00
November 74.22 248.42 122.33 27.23 95.10 0.00 0.00
December 49.71 335.47 102.55 35.54 67.01 0.00 0.00
               
Annual Sum or Average 262.43 176.32 235.95 80.26 155.69 0.00 0.00
Minimum of Months 49.71 12.09 102.55 27.23 67.01 0.00 0.00
Maximum of Months 516.49 374.92 345.15 130.48 231.89 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 94.27 99.21 96.37 63.24 33.13 0.00 0.00
February 121.13 116.52 127.53 84.76 42.77 0.00 0.00
March 112.34 91.65 113.00 62.20 50.79 0.00 0.00
April 91.34 69.47 89.94 36.39 53.55 0.00 0.00
May 81.54 44.74 77.25 15.82 61.43 0.00 0.00
June 90.82 24.49 72.94 11.24 61.70 0.00 0.00
July 107.02 14.00 75.90 12.81 63.09 0.00 0.00
August 146.61 18.38 101.66 37.50 64.16 0.00 0.00
September 137.16 35.42 107.27 53.86 53.41 0.00 0.00
October 181.11 61.66 151.60 95.06 56.53 0.00 0.00
November 104.02 90.43 104.97 62.97 42.00 0.00 0.00
December 101.40 106.18 104.12 73.95 30.17 0.00 0.00
               
Annual Sum or Average 114.10 64.02 101.76 50.64 51.11 0.00 0.00
Minimum of Months 81.54 14.00 72.94 11.24 30.17 0.00 0.00
Maximum of Months 181.11 116.52 151.60 95.06 64.16 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.80 114.00 18.55 0.00 18.55 0.00 0.00
February 2.15 115.45 25.38 0.00 25.38 0.00 0.00
March 12.83 73.57 35.20 0.00 35.20 0.00 0.00
April 29.18 48.15 42.37 0.17 42.19 0.00 0.00
May 59.14 25.32 56.35 2.06 54.29 0.00 0.00
June 81.87 10.22 59.45 3.16 56.28 0.00 0.00
July 94.78 2.53 57.70 2.25 55.45 0.00 0.00
August 84.27 5.55 51.02 0.68 50.35 0.00 0.00
September 47.43 17.83 38.42 0.02 38.40 0.00 0.00
October 27.88 41.47 33.22 0.00 33.22 0.00 0.00
November 6.97 75.03 23.30 0.00 23.30 0.00 0.00
December 0.58 103.26 16.18 0.00 16.18 0.00 0.00
               
Annual Sum or Average 37.57 52.34 38.17 0.70 37.47 0.00 0.00
Minimum of Months 0.58 2.53 16.18 0.00 16.18 0.00 0.00
Maximum of Months 94.78 115.45 59.45 3.16 56.28 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 161.99 351.17 210.66 115.09 95.57 0.00 0.00
February 243.54 346.74 299.45 171.17 128.28 0.00 0.00
March 303.41 241.99 321.06 154.18 166.88 0.00 0.00
April 347.28 162.99 327.67 139.96 187.71 0.00 0.00
May 431.02 90.36 356.41 123.32 233.09 0.00 0.00
June 463.87 34.43 332.47 101.44 231.03 0.00 0.00
July 521.39 8.56 336.90 103.14 233.76 0.00 0.00
August 608.85 20.42 400.11 170.06 230.05 0.00 0.00
September 454.09 59.90 338.35 159.34 179.00 0.00 0.00
October 447.97 142.20 374.03 202.37 171.67 0.00 0.00
November 228.66 239.37 245.51 122.64 122.87 0.00 0.00
December 182.67 313.77 219.51 134.61 84.90 0.00 0.00
               
Annual Sum or Average 367.16 166.66 313.65 141.31 172.34 0.00 0.00
Minimum of Months 161.99 8.56 210.66 101.44 84.90 0.00 0.00
Maximum of Months 608.85 351.17 400.11 202.37 233.76 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 48.54 365.18 113.35 36.03 77.33 0.00 0.00
February 88.45 360.03 171.72 65.20 106.53 0.00 0.00
March 171.61 242.25 223.79 76.41 147.38 0.00 0.00
April 257.65 161.88 268.17 94.68 173.49 0.00 0.00
May 382.33 91.54 330.26 106.12 224.13 0.00 0.00
June 424.49 39.74 315.57 91.34 224.23 0.00 0.00
July 476.98 11.45 314.12 89.94 224.18 0.00 0.00
August 503.80 22.97 336.79 124.02 212.77 0.00 0.00
September 321.44 64.49 252.25 92.03 160.22 0.00 0.00
October 242.43 143.53 226.02 83.51 142.51 0.00 0.00
November 98.29 242.18 143.40 43.91 99.48 0.00 0.00
December 53.40 326.52 109.56 42.15 67.40 0.00 0.00
               
Annual Sum or Average 256.94 171.61 234.14 78.87 155.27 0.00 0.00
Minimum of Months 48.54 11.45 109.56 36.03 67.40 0.00 0.00
Maximum of Months 503.80 365.18 336.79 124.02 224.23 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 185.42 451.42 248.98 137.02 111.96 0.00 0.00
February 257.55 447.71 331.31 183.66 147.66 0.00 0.00
March 288.40 310.96 321.09 134.78 186.32 0.00 0.00
April 286.41 214.84 286.66 79.22 207.43 0.00 0.00
May 333.95 119.77 289.45 38.74 250.71 0.00 0.00
June 397.89 56.52 286.82 31.20 255.62 0.00 0.00
July 455.22 21.68 289.44 32.63 256.81 0.00 0.00
August 514.53 38.90 330.80 82.72 248.08 0.00 0.00
September 420.34 92.77 315.67 116.75 198.92 0.00 0.00
October 474.40 192.07 400.44 205.98 194.46 0.00 0.00
November 252.04 306.93 277.92 136.44 141.49 0.00 0.00
December 212.31 402.64 260.64 160.23 100.41 0.00 0.00
               
Annual Sum or Average 340.56 220.08 303.16 111.25 191.92 0.00 0.00
Minimum of Months 185.42 21.68 248.98 31.20 100.41 0.00 0.00
Maximum of Months 514.53 451.42 400.44 205.98 256.81 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 161.40 351.16 210.03 115.83 94.21 0.00 0.00
February 233.29 349.54 290.99 163.70 127.29 0.00 0.00
March 319.78 239.01 336.66 168.32 168.34 0.00 0.00
April 344.48 165.92 324.66 136.18 188.48 0.00 0.00
May 413.09 92.27 344.49 114.01 230.47 0.00 0.00
June 500.50 35.20 362.05 123.36 238.69 0.00 0.00
July 532.90 8.44 348.30 111.24 237.06 0.00 0.00
August 616.60 20.70 407.46 176.51 230.95 0.00 0.00
September 446.66 60.55 333.60 154.42 179.17 0.00 0.00
October 464.62 143.04 387.46 215.27 172.19 0.00 0.00
November 200.34 238.84 224.45 105.96 118.49 0.00 0.00
December 173.70 314.31 212.50 127.99 84.51 0.00 0.00
               
Annual Sum or Average 368.32 167.23 315.46 142.70 172.76 0.00 0.00
Minimum of Months 161.40 8.44 210.03 105.96 84.51 0.00 0.00
Maximum of Months 616.60 351.16 407.46 215.27 238.69 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 53.16 370.04 112.73 36.76 75.97 0.00 0.00
February 88.90 373.56 163.26 57.73 105.53 0.00 0.00
March 190.22 240.41 239.39 90.55 148.84 0.00 0.00
April 255.78 165.74 265.16 90.90 174.25 0.00 0.00
May 362.75 94.68 318.33 96.82 221.51 0.00 0.00
June 458.85 43.45 345.15 113.26 231.89 0.00 0.00
July 489.74 11.97 325.52 98.04 227.48 0.00 0.00
August 514.26 23.75 344.14 130.48 213.66 0.00 0.00
September 315.43 67.31 247.49 87.11 160.38 0.00 0.00
October 261.15 146.26 239.45 96.42 143.03 0.00 0.00
November 74.85 245.29 122.33 27.23 95.10 0.00 0.00
December 50.39 332.57 102.55 35.54 67.01 0.00 0.00
               
Annual Sum or Average 260.84 175.13 235.95 80.26 155.69 0.00 0.00
Minimum of Months 50.39 11.97 102.55 27.23 67.01 0.00 0.00
Maximum of Months 514.26 373.56 345.15 130.48 231.89 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 169.64 183.32 176.70 115.95 60.75 0.00 0.00
February 229.12 182.45 233.85 155.42 78.43 0.00 0.00
March 216.75 128.72 207.19 114.06 93.13 0.00 0.00
April 183.00 88.41 164.92 66.72 98.20 0.00 0.00
May 172.27 48.04 141.64 29.00 112.65 0.00 0.00
June 193.75 16.98 133.75 20.61 113.14 0.00 0.00
July 227.77 3.61 139.17 23.49 115.68 0.00 0.00
August 297.99 9.78 186.40 68.76 117.64 0.00 0.00
September 272.06 30.88 196.70 98.76 97.94 0.00 0.00
October 348.79 74.29 277.97 174.31 103.66 0.00 0.00
November 202.94 126.24 192.48 115.46 77.02 0.00 0.00
December 192.36 164.18 190.91 135.59 55.32 0.00 0.00
               
Annual Sum or Average 225.65 87.55 186.58 92.86 93.72 0.00 0.00
Minimum of Months 169.64 3.61 133.75 20.61 55.32 0.00 0.00
Maximum of Months 348.79 183.32 277.97 174.31 117.64 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2.36 1128.75 162.25 0.00 162.25 0.00 0.00
February 10.67 1140.28 222.04 0.00 222.04 0.00 0.00
March 85.61 756.33 307.98 0.01 307.98 0.00 0.00
April 215.87 510.94 370.63 1.53 369.11 0.00 0.00
May 460.40 277.55 492.96 18.04 474.92 0.00 0.00
June 662.26 129.41 520.06 27.66 492.40 0.00 0.00
July 754.97 53.58 504.77 19.70 485.07 0.00 0.00
August 662.93 83.42 446.39 5.93 440.46 0.00 0.00
September 371.49 213.42 336.12 0.20 335.92 0.00 0.00
October 207.67 444.47 290.65 0.00 290.65 0.00 0.00
November 43.16 773.90 203.86 0.00 203.86 0.00 0.00
December 1.99 1039.59 141.53 0.00 141.53 0.00 0.00
               
Annual Sum or Average 291.88 542.61 333.92 6.12 327.79 0.00 0.00
Minimum of Months 1.99 53.58 141.53 0.00 141.53 0.00 0.00
Maximum of Months 754.97 1140.28 520.06 27.66 492.40 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1.52 1163.36 162.25 0.00 162.25 0.00 0.00
February 8.78 1173.46 222.04 0.00 222.04 0.00 0.00
March 78.45 780.39 307.98 0.01 307.98 0.00 0.00
April 205.26 528.06 370.63 1.53 369.11 0.00 0.00
May 447.67 286.53 492.96 18.04 474.92 0.00 0.00
June 652.69 135.10 520.06 27.66 492.40 0.00 0.00
July 746.42 57.70 504.77 19.70 485.07 0.00 0.00
August 654.29 87.71 446.39 5.93 440.46 0.00 0.00
September 362.84 222.17 336.12 0.20 335.92 0.00 0.00
October 198.85 458.51 290.65 0.00 290.65 0.00 0.00
November 38.64 800.71 203.86 0.00 203.86 0.00 0.00
December 1.45 1072.35 141.53 0.00 141.53 0.00 0.00
               
Annual Sum or Average 284.98 560.39 333.92 6.12 327.79 0.00 0.00
Minimum of Months 1.45 57.70 141.53 0.00 141.53 0.00 0.00
Maximum of Months 746.42 1173.46 520.06 27.66 492.40 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 217.14 731.76 324.00 151.11 172.89 0.00 0.00
February 346.31 715.96 471.16 236.36 234.80 0.00 0.00
March 516.29 504.97 544.82 230.57 314.24 0.00 0.00
April 678.31 347.99 595.81 234.62 361.18 0.00 0.00
May 923.98 203.78 686.63 229.43 457.20 0.00 0.00
June 1028.41 95.41 648.01 192.78 455.23 0.00 0.00
July 1146.98 41.17 650.99 193.07 457.92 0.00 0.00
August 1258.62 60.61 736.86 294.06 442.80 0.00 0.00
September 899.43 137.08 590.56 251.36 339.20 0.00 0.00
October 776.95 288.09 600.03 285.87 314.16 0.00 0.00
November 360.15 494.72 388.89 166.55 222.35 0.00 0.00
December 246.70 651.31 329.06 176.76 152.30 0.00 0.00
               
Annual Sum or Average 702.39 354.07 547.77 220.18 327.59 0.00 0.00
Minimum of Months 217.14 41.17 324.00 151.11 152.30 0.00 0.00
Maximum of Months 1258.62 731.76 736.86 294.06 457.92 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 405.67 806.95 505.43 295.17 210.26 0.00 0.00
February 558.79 797.62 671.39 395.63 275.75 0.00 0.00
March 588.35 560.43 632.99 290.34 342.65 0.00 0.00
April 551.71 389.48 546.86 170.37 376.49 0.00 0.00
May 600.66 220.65 529.55 80.00 449.55 0.00 0.00
June 702.35 106.83 518.74 61.94 456.80 0.00 0.00
July 805.05 45.86 527.29 66.54 460.75 0.00 0.00
August 955.63 73.65 627.51 177.07 450.44 0.00 0.00
September 814.69 167.88 615.93 251.47 364.47 0.00 0.00
October 967.28 336.64 807.22 443.72 363.51 0.00 0.00
November 528.44 548.67 559.84 293.91 265.93 0.00 0.00
December 464.09 720.40 534.48 345.16 189.32 0.00 0.00
               
Annual Sum or Average 662.88 395.67 589.42 238.48 350.94 0.00 0.00
Minimum of Months 405.67 45.86 505.43 61.94 189.32 0.00 0.00
Maximum of Months 967.28 806.95 807.22 443.72 460.75 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.161587E+10 0.161495E+10 0.163216E+10 0.107105E+10 0.561115E+09 0.00 0.00
February 0.196978E+10 0.144532E+10 0.195097E+10 0.129667E+10 0.654301E+09 0.00 0.00
March 0.205417E+10 0.113515E+10 0.191376E+10 0.105350E+10 0.860258E+09 0.00 0.00
April 0.167258E+10 0.772889E+09 0.147416E+10 0.596411E+09 0.877753E+09 0.00 0.00
May 0.161725E+10 0.455313E+09 0.130833E+10 0.267862E+09 0.104047E+10 0.00 0.00
June 0.169721E+10 0.207490E+09 0.119554E+10 0.184207E+09 0.101133E+10 0.00 0.00
July 0.200493E+10 88295919.91 0.128543E+10 0.216954E+09 0.106847E+10 0.00 0.00
August 0.264424E+10 0.161856E+09 0.172171E+10 0.635122E+09 0.108658E+10 0.00 0.00
September 0.240902E+10 0.336096E+09 0.175826E+10 0.882798E+09 0.875461E+09 0.00 0.00
October 0.323551E+10 0.721673E+09 0.256754E+10 0.161007E+10 0.957474E+09 0.00 0.00
November 0.185468E+10 0.108288E+10 0.172050E+10 0.103208E+10 0.688421E+09 0.00 0.00
December 0.182048E+10 0.145214E+10 0.176337E+10 0.125244E+10 0.510933E+09 0.00 0.00
               
Annual Sum or Average 0.245957E+11 0.947405E+10 0.202917E+11 0.100992E+11 0.101926E+11 0.00 0.00
Minimum of Months 0.161587E+10 88295919.91 0.119554E+10 0.184207E+09 0.510933E+09 0.00 0.00
Maximum of Months 0.323551E+10 0.161495E+10 0.256754E+10 0.161007E+10 0.108658E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.449451E+10 0.469049E+10 0.459606E+10 0.301600E+10 0.158006E+10 0.00 0.00
February 0.547724E+10 0.420969E+10 0.549380E+10 0.365134E+10 0.184247E+10 0.00 0.00
March 0.570900E+10 0.339143E+10 0.538903E+10 0.296660E+10 0.242243E+10 0.00 0.00
April 0.463119E+10 0.235383E+10 0.415115E+10 0.167946E+10 0.247169E+10 0.00 0.00
May 0.444525E+10 0.144418E+10 0.368418E+10 0.754282E+09 0.292990E+10 0.00 0.00
June 0.470617E+10 0.680623E+09 0.336655E+10 0.518716E+09 0.284784E+10 0.00 0.00
July 0.559003E+10 0.306697E+09 0.361968E+10 0.610929E+09 0.300875E+10 0.00 0.00
August 0.739830E+10 0.506569E+09 0.484821E+10 0.178846E+10 0.305975E+10 0.00 0.00
September 0.671227E+10 0.107772E+10 0.495114E+10 0.248590E+10 0.246524E+10 0.00 0.00
October 0.902304E+10 0.221852E+10 0.723002E+10 0.453384E+10 0.269618E+10 0.00 0.00
November 0.514090E+10 0.323582E+10 0.484482E+10 0.290627E+10 0.193855E+10 0.00 0.00
December 0.506294E+10 0.426176E+10 0.496554E+10 0.352678E+10 0.143875E+10 0.00 0.00
               
Annual Sum or Average 0.683909E+11 0.283773E+11 0.571402E+11 0.284386E+11 0.287016E+11 0.00 0.00
Minimum of Months 0.444525E+10 0.306697E+09 0.336655E+10 0.518716E+09 0.143875E+10 0.00 0.00
Maximum of Months 0.902304E+10 0.469049E+10 0.723002E+10 0.453384E+10 0.305975E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.592398E+10 0.639987E+10 0.597055E+10 0.391796E+10 0.205259E+10 0.00 0.00
February 0.724059E+10 0.569852E+10 0.713676E+10 0.474329E+10 0.239347E+10 0.00 0.00
March 0.755195E+10 0.460992E+10 0.700065E+10 0.385378E+10 0.314688E+10 0.00 0.00
April 0.611816E+10 0.322898E+10 0.539258E+10 0.218171E+10 0.321087E+10 0.00 0.00
May 0.585819E+10 0.199529E+10 0.478596E+10 0.979855E+09 0.380610E+10 0.00 0.00
June 0.621505E+10 0.931974E+09 0.437334E+10 0.673841E+09 0.369950E+10 0.00 0.00
July 0.741204E+10 0.415027E+09 0.470217E+10 0.793632E+09 0.390854E+10 0.00 0.00
August 0.982874E+10 0.660101E+09 0.629810E+10 0.232331E+10 0.397479E+10 0.00 0.00
September 0.887815E+10 0.144917E+10 0.643181E+10 0.322933E+10 0.320249E+10 0.00 0.00
October 0.119441E+11 0.295507E+10 0.939221E+10 0.588972E+10 0.350250E+10 0.00 0.00
November 0.677233E+10 0.443023E+10 0.629370E+10 0.377541E+10 0.251828E+10 0.00 0.00
December 0.667277E+10 0.582107E+10 0.645052E+10 0.458149E+10 0.186902E+10 0.00 0.00
               
Annual Sum or Average 0.904160E+11 0.385952E+11 0.742284E+11 0.369433E+11 0.372850E+11 0.00 0.00
Minimum of Months 0.585819E+10 0.415027E+09 0.437334E+10 0.673841E+09 0.186902E+10 0.00 0.00
Maximum of Months 0.119441E+11 0.639987E+10 0.939221E+10 0.588972E+10 0.397479E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.432784E+09 0.946384E+09 0.562551E+09 0.310227E+09 0.252324E+09 0.00 0.00
February 0.566502E+09 0.849456E+09 0.703964E+09 0.396032E+09 0.307932E+09 0.00 0.00
March 0.862436E+09 0.643625E+09 0.901710E+09 0.450816E+09 0.450894E+09 0.00 0.00
April 0.900184E+09 0.433291E+09 0.841513E+09 0.352979E+09 0.488534E+09 0.00 0.00
May 0.111695E+10 0.249197E+09 0.922671E+09 0.305369E+09 0.617303E+09 0.00 0.00
June 0.130740E+10 93649428.71 0.938438E+09 0.319752E+09 0.618686E+09 0.00 0.00
July 0.143602E+10 24361242.28 0.932881E+09 0.297952E+09 0.634929E+09 0.00 0.00
August 0.165987E+10 58315812.33 0.109135E+10 0.472774E+09 0.618575E+09 0.00 0.00
September 0.116462E+10 0.160965E+09 0.864680E+09 0.400269E+09 0.464411E+09 0.00 0.00
October 0.125141E+10 0.388874E+09 0.103777E+10 0.576578E+09 0.461191E+09 0.00 0.00
November 0.519870E+09 0.625635E+09 0.581769E+09 0.274641E+09 0.307129E+09 0.00 0.00
December 0.464836E+09 0.848581E+09 0.569161E+09 0.342817E+09 0.226344E+09 0.00 0.00
               
Annual Sum or Average 0.116829E+11 0.532234E+10 0.994846E+10 0.450021E+10 0.544825E+10 0.00 0.00
Minimum of Months 0.432784E+09 24361242.28 0.562551E+09 0.274641E+09 0.226344E+09 0.00 0.00
Maximum of Months 0.165987E+10 0.946384E+09 0.109135E+10 0.576578E+09 0.634929E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.141464E+09 0.996837E+09 0.301930E+09 98462657.35 0.203467E+09 0.00 0.00
February 0.215179E+09 0.907010E+09 0.394962E+09 0.139658E+09 0.255304E+09 0.00 0.00
March 0.511941E+09 0.648028E+09 0.641173E+09 0.242523E+09 0.398650E+09 0.00 0.00
April 0.668527E+09 0.432348E+09 0.687289E+09 0.235623E+09 0.451665E+09 0.00 0.00
May 0.983315E+09 0.252527E+09 0.852616E+09 0.259311E+09 0.593305E+09 0.00 0.00
June 0.120149E+10 0.110012E+09 0.894635E+09 0.293574E+09 0.601061E+09 0.00 0.00
July 0.132008E+10 32387513.44 0.871875E+09 0.262595E+09 0.609281E+09 0.00 0.00
August 0.138337E+10 65433511.30 0.921743E+09 0.349469E+09 0.572274E+09 0.00 0.00
September 0.823001E+09 0.175987E+09 0.641506E+09 0.225797E+09 0.415709E+09 0.00 0.00
October 0.702014E+09 0.397533E+09 0.641335E+09 0.258241E+09 0.383094E+09 0.00 0.00
November 0.192389E+09 0.643911E+09 0.317085E+09 70580626.93 0.246505E+09 0.00 0.00
December 0.133156E+09 0.898530E+09 0.274666E+09 95188244.85 0.179478E+09 0.00 0.00
               
Annual Sum or Average 0.827593E+10 0.556054E+10 0.744082E+10 0.253102E+10 0.490979E+10 0.00 0.00
Minimum of Months 0.133156E+09 32387513.44 0.274666E+09 70580626.93 0.179478E+09 0.00 0.00
Maximum of Months 0.138337E+10 0.996837E+09 0.921743E+09 0.349469E+09 0.609281E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.252492E+09 0.265725E+09 0.258114E+09 0.169378E+09 88736490.59 0.00 0.00
February 0.293033E+09 0.281893E+09 0.308532E+09 0.205058E+09 0.103473E+09 0.00 0.00
March 0.300890E+09 0.245480E+09 0.302648E+09 0.166604E+09 0.136044E+09 0.00 0.00
April 0.236750E+09 0.180058E+09 0.233129E+09 94317873.29 0.138811E+09 0.00 0.00
May 0.218409E+09 0.119838E+09 0.206904E+09 42360323.35 0.164544E+09 0.00 0.00
June 0.235408E+09 63488679.14 0.189067E+09 29130958.40 0.159936E+09 0.00 0.00
July 0.286649E+09 37492584.72 0.203282E+09 34309663.55 0.168973E+09 0.00 0.00
August 0.392672E+09 49239807.84 0.272276E+09 0.100440E+09 0.171837E+09 0.00 0.00
September 0.355529E+09 91810725.07 0.278056E+09 0.139608E+09 0.138449E+09 0.00 0.00
October 0.485075E+09 0.165147E+09 0.406038E+09 0.254620E+09 0.151418E+09 0.00 0.00
November 0.269631E+09 0.234399E+09 0.272085E+09 0.163216E+09 0.108869E+09 0.00 0.00
December 0.271589E+09 0.284383E+09 0.278864E+09 0.198063E+09 80800618.01 0.00 0.00
               
Annual Sum or Average 0.359813E+10 0.201895E+10 0.320900E+10 0.159710E+10 0.161189E+10 0.00 0.00
Minimum of Months 0.218409E+09 37492584.72 0.189067E+09 29130958.40 80800618.01 0.00 0.00
Maximum of Months 0.485075E+09 0.284383E+09 0.406038E+09 0.254620E+09 0.171837E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 2153401.85 0.305343E+09 49674962.73 0.00 49674962.73 0.00 0.00
February 5205628.84 0.279298E+09 61399643.62 0.00 61399643.62 0.00 0.00
March 34372280.97 0.197052E+09 94290864.36 1963.96 94288900.41 0.00 0.00
April 75636488.89 0.124808E+09 0.109811E+09 452471.34 0.109358E+09 0.00 0.00
May 0.158410E+09 67804846.40 0.150921E+09 5523301.01 0.145398E+09 0.00 0.00
June 0.212207E+09 26487307.31 0.154082E+09 8195407.02 0.145887E+09 0.00 0.00
July 0.253871E+09 6775660.87 0.154539E+09 6031231.87 0.148507E+09 0.00 0.00
August 0.225718E+09 14858196.39 0.136664E+09 1815851.67 0.134848E+09 0.00 0.00
September 0.122947E+09 46202933.90 99584946.32 57893.59 99527052.73 0.00 0.00
October 74683918.48 0.111078E+09 88983113.67 0.00 88983113.67 0.00 0.00
November 18065266.28 0.194469E+09 60399659.90 0.00 60399659.90 0.00 0.00
December 1558693.53 0.276560E+09 43329787.27 0.00 43329787.27 0.00 0.00
               
Annual Sum or Average 0.118483E+10 0.165074E+10 0.120368E+10 22078120.45 0.118160E+10 0.00 0.00
Minimum of Months 1558693.53 6775660.87 43329787.27 0.00 43329787.27 0.00 0.00
Maximum of Months 0.253871E+09 0.305343E+09 0.154539E+09 8195407.02 0.148507E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.433879E+09 0.940580E+09 0.564229E+09 0.308260E+09 0.255969E+09 0.00 0.00
February 0.589170E+09 0.838835E+09 0.724436E+09 0.414096E+09 0.310339E+09 0.00 0.00
March 0.812644E+09 0.648148E+09 0.859923E+09 0.412946E+09 0.446977E+09 0.00 0.00
April 0.900147E+09 0.422461E+09 0.849316E+09 0.362766E+09 0.486550E+09 0.00 0.00
May 0.115445E+10 0.242022E+09 0.954617E+09 0.330301E+09 0.624316E+09 0.00 0.00
June 0.120235E+10 89240029.37 0.861763E+09 0.262942E+09 0.598821E+09 0.00 0.00
July 0.139648E+10 22919623.61 0.902351E+09 0.276256E+09 0.626094E+09 0.00 0.00
August 0.163073E+10 54701501.95 0.107165E+10 0.455479E+09 0.616174E+09 0.00 0.00
September 0.117701E+10 0.155272E+09 0.876994E+09 0.413014E+09 0.463980E+09 0.00 0.00
October 0.119984E+10 0.380861E+09 0.100181E+10 0.542024E+09 0.459791E+09 0.00 0.00
November 0.592698E+09 0.620459E+09 0.636369E+09 0.317881E+09 0.318487E+09 0.00 0.00
December 0.489255E+09 0.840393E+09 0.587937E+09 0.360535E+09 0.227402E+09 0.00 0.00
               
Annual Sum or Average 0.115787E+11 0.525589E+10 0.989140E+10 0.445650E+10 0.543490E+10 0.00 0.00
Minimum of Months 0.433879E+09 22919623.61 0.564229E+09 0.262942E+09 0.227402E+09 0.00 0.00
Maximum of Months 0.163073E+10 0.940580E+09 0.107165E+10 0.542024E+09 0.626094E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.129996E+09 0.978108E+09 0.303607E+09 96495417.54 0.207112E+09 0.00 0.00
February 0.213977E+09 0.870995E+09 0.415434E+09 0.157722E+09 0.257711E+09 0.00 0.00
March 0.459648E+09 0.648856E+09 0.599386E+09 0.204653E+09 0.394734E+09 0.00 0.00
April 0.667818E+09 0.419587E+09 0.695092E+09 0.245411E+09 0.449682E+09 0.00 0.00
May 0.102402E+10 0.245174E+09 0.884562E+09 0.284243E+09 0.600318E+09 0.00 0.00
June 0.110029E+10 0.103004E+09 0.817960E+09 0.236764E+09 0.581196E+09 0.00 0.00
July 0.127755E+10 30675499.61 0.841345E+09 0.240899E+09 0.600446E+09 0.00 0.00
August 0.134937E+10 61528026.96 0.902047E+09 0.332174E+09 0.569873E+09 0.00 0.00
September 0.833176E+09 0.167171E+09 0.653820E+09 0.238542E+09 0.415277E+09 0.00 0.00
October 0.649334E+09 0.384434E+09 0.605381E+09 0.223686E+09 0.381695E+09 0.00 0.00
November 0.254757E+09 0.627740E+09 0.371685E+09 0.113821E+09 0.257864E+09 0.00 0.00
December 0.143019E+09 0.874550E+09 0.293443E+09 0.112907E+09 0.180536E+09 0.00 0.00
               
Annual Sum or Average 0.810296E+10 0.541182E+10 0.738376E+10 0.248732E+10 0.489644E+10 0.00 0.00
Minimum of Months 0.129996E+09 30675499.61 0.293443E+09 96495417.54 0.180536E+09 0.00 0.00
Maximum of Months 0.134937E+10 0.978108E+09 0.902047E+09 0.332174E+09 0.600446E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.496628E+09 0.120908E+10 0.666875E+09 0.366995E+09 0.299880E+09 0.00 0.00
February 0.623075E+09 0.108311E+10 0.801514E+09 0.444304E+09 0.357210E+09 0.00 0.00
March 0.772443E+09 0.832885E+09 0.860019E+09 0.360988E+09 0.499031E+09 0.00 0.00
April 0.742380E+09 0.556875E+09 0.743012E+09 0.205341E+09 0.537671E+09 0.00 0.00
May 0.894448E+09 0.320805E+09 0.775251E+09 0.103748E+09 0.671502E+09 0.00 0.00
June 0.103133E+10 0.146512E+09 0.743449E+09 80872685.50 0.662577E+09 0.00 0.00
July 0.121926E+10 58076113.59 0.775239E+09 87405170.35 0.687834E+09 0.00 0.00
August 0.137812E+10 0.104200E+09 0.886007E+09 0.221558E+09 0.664449E+09 0.00 0.00
September 0.108953E+10 0.240470E+09 0.818205E+09 0.302616E+09 0.515588E+09 0.00 0.00
October 0.127062E+10 0.514428E+09 0.107254E+10 0.551690E+09 0.520848E+09 0.00 0.00
November 0.653300E+09 0.795565E+09 0.720378E+09 0.353643E+09 0.366735E+09 0.00 0.00
December 0.568656E+09 0.107842E+10 0.698088E+09 0.429149E+09 0.268939E+09 0.00 0.00
               
Annual Sum or Average 0.107398E+11 0.694043E+10 0.956058E+10 0.350831E+10 0.605227E+10 0.00 0.00
Minimum of Months 0.496628E+09 58076113.59 0.666875E+09 80872685.50 0.268939E+09 0.00 0.00
Maximum of Months 0.137812E+10 0.120908E+10 0.107254E+10 0.551690E+09 0.687834E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.432300E+09 0.940556E+09 0.562551E+09 0.310227E+09 0.252324E+09 0.00 0.00
February 0.564366E+09 0.845617E+09 0.703964E+09 0.396032E+09 0.307932E+09 0.00 0.00
March 0.856500E+09 0.640166E+09 0.901710E+09 0.450816E+09 0.450894E+09 0.00 0.00
April 0.892883E+09 0.430075E+09 0.841513E+09 0.352979E+09 0.488534E+09 0.00 0.00
May 0.110643E+10 0.247127E+09 0.922671E+09 0.305369E+09 0.617303E+09 0.00 0.00
June 0.129731E+10 91248819.34 0.938438E+09 0.319752E+09 0.618686E+09 0.00 0.00
July 0.142731E+10 22607141.02 0.932881E+09 0.297952E+09 0.634929E+09 0.00 0.00
August 0.165151E+10 55432115.96 0.109135E+10 0.472774E+09 0.618575E+09 0.00 0.00
September 0.115774E+10 0.156939E+09 0.864680E+09 0.400269E+09 0.464411E+09 0.00 0.00
October 0.124443E+10 0.383129E+09 0.103777E+10 0.576578E+09 0.461191E+09 0.00 0.00
November 0.519276E+09 0.619062E+09 0.581769E+09 0.274641E+09 0.307129E+09 0.00 0.00
December 0.465250E+09 0.841853E+09 0.569161E+09 0.342817E+09 0.226344E+09 0.00 0.00
               
Annual Sum or Average 0.116153E+11 0.527381E+10 0.994846E+10 0.450021E+10 0.544825E+10 0.00 0.00
Minimum of Months 0.432300E+09 22607141.02 0.562551E+09 0.274641E+09 0.226344E+09 0.00 0.00
Maximum of Months 0.165151E+10 0.940556E+09 0.109135E+10 0.576578E+09 0.634929E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.142377E+09 0.991126E+09 0.301930E+09 98462657.35 0.203467E+09 0.00 0.00
February 0.215064E+09 0.903726E+09 0.394962E+09 0.139658E+09 0.255304E+09 0.00 0.00
March 0.509472E+09 0.643904E+09 0.641173E+09 0.242523E+09 0.398650E+09 0.00 0.00
April 0.662986E+09 0.429586E+09 0.687289E+09 0.235623E+09 0.451665E+09 0.00 0.00
May 0.971599E+09 0.253597E+09 0.852616E+09 0.259311E+09 0.593305E+09 0.00 0.00
June 0.118934E+10 0.112629E+09 0.894635E+09 0.293574E+09 0.601061E+09 0.00 0.00
July 0.131171E+10 32051636.50 0.871875E+09 0.262595E+09 0.609281E+09 0.00 0.00
August 0.137739E+10 63602251.49 0.921743E+09 0.349469E+09 0.572274E+09 0.00 0.00
September 0.817603E+09 0.174459E+09 0.641506E+09 0.225797E+09 0.415709E+09 0.00 0.00
October 0.699457E+09 0.391736E+09 0.641335E+09 0.258241E+09 0.383094E+09 0.00 0.00
November 0.194014E+09 0.635804E+09 0.317085E+09 70580626.93 0.246505E+09 0.00 0.00
December 0.134973E+09 0.890764E+09 0.274666E+09 95188244.85 0.179478E+09 0.00 0.00
               
Annual Sum or Average 0.822598E+10 0.552298E+10 0.744082E+10 0.253102E+10 0.490979E+10 0.00 0.00
Minimum of Months 0.134973E+09 32051636.50 0.274666E+09 70580626.93 0.179478E+09 0.00 0.00
Maximum of Months 0.137739E+10 0.991126E+09 0.921743E+09 0.349469E+09 0.609281E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.454368E+09 0.491010E+09 0.473281E+09 0.310573E+09 0.162708E+09 0.00 0.00
February 0.554285E+09 0.441390E+09 0.565726E+09 0.375997E+09 0.189730E+09 0.00 0.00
March 0.580553E+09 0.344758E+09 0.554938E+09 0.305486E+09 0.249452E+09 0.00 0.00
April 0.474337E+09 0.229166E+09 0.427468E+09 0.172942E+09 0.254525E+09 0.00 0.00
May 0.461409E+09 0.128679E+09 0.379382E+09 77672293.27 0.301710E+09 0.00 0.00
June 0.502200E+09 44016097.34 0.346674E+09 53414803.41 0.293260E+09 0.00 0.00
July 0.610069E+09 9667503.40 0.372740E+09 62910526.60 0.309830E+09 0.00 0.00
August 0.798125E+09 26194167.46 0.499248E+09 0.184167E+09 0.315081E+09 0.00 0.00
September 0.705190E+09 80033758.63 0.509846E+09 0.255986E+09 0.253861E+09 0.00 0.00
October 0.934208E+09 0.198987E+09 0.744515E+09 0.466873E+09 0.277642E+09 0.00 0.00
November 0.526027E+09 0.327201E+09 0.498897E+09 0.299274E+09 0.199623E+09 0.00 0.00
December 0.515223E+09 0.439746E+09 0.511328E+09 0.363171E+09 0.148157E+09 0.00 0.00
               
Annual Sum or Average 0.711599E+10 0.276085E+10 0.588404E+10 0.292847E+10 0.295558E+10 0.00 0.00
Minimum of Months 0.454368E+09 9667503.40 0.346674E+09 53414803.41 0.148157E+09 0.00 0.00
Maximum of Months 0.934208E+09 0.491010E+09 0.744515E+09 0.466873E+09 0.315081E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 6327816.72 0.302326E+10 0.434582E+09 0.00 0.434582E+09 0.00 0.00
February 25804686.09 0.275856E+10 0.537155E+09 0.00 0.537155E+09 0.00 0.00
March 0.229288E+09 0.202576E+10 0.824904E+09 17181.70 0.824887E+09 0.00 0.00
April 0.559528E+09 0.132436E+10 0.960679E+09 3958449.54 0.956721E+09 0.00 0.00
May 0.123314E+10 0.743398E+09 0.132034E+10 48320648.33 0.127202E+10 0.00 0.00
June 0.171658E+10 0.335436E+09 0.134799E+10 71697591.63 0.127629E+10 0.00 0.00
July 0.202210E+10 0.143517E+09 0.135198E+10 52764286.00 0.129922E+10 0.00 0.00
August 0.177558E+10 0.223431E+09 0.119561E+10 15885994.55 0.117972E+10 0.00 0.00
September 0.962905E+09 0.553179E+09 0.871220E+09 506482.57 0.870713E+09 0.00 0.00
October 0.556231E+09 0.119046E+10 0.778470E+09 0.00 0.778470E+09 0.00 0.00
November 0.111864E+09 0.200596E+10 0.528407E+09 0.00 0.528407E+09 0.00 0.00
December 5329751.12 0.278444E+10 0.379071E+09 0.00 0.379071E+09 0.00 0.00
               
Annual Sum or Average 0.920467E+10 0.171118E+11 0.105304E+11 0.193151E+09 0.103373E+11 0.00 0.00
Minimum of Months 5329751.12 0.143517E+09 0.379071E+09 0.00 0.379071E+09 0.00 0.00
Maximum of Months 0.202210E+10 0.302326E+10 0.135198E+10 71697591.63 0.129922E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 4065217.34 0.311594E+10 0.434582E+09 0.00 0.434582E+09 0.00 0.00
February 21243687.90 0.283883E+10 0.537155E+09 0.00 0.537155E+09 0.00 0.00
March 0.210108E+09 0.209019E+10 0.824904E+09 17181.70 0.824887E+09 0.00 0.00
April 0.532038E+09 0.136873E+10 0.960679E+09 3958449.54 0.956721E+09 0.00 0.00
May 0.119904E+10 0.767451E+09 0.132034E+10 48320648.33 0.127202E+10 0.00 0.00
June 0.169178E+10 0.350188E+09 0.134799E+10 71697591.63 0.127629E+10 0.00 0.00
July 0.199922E+10 0.154541E+09 0.135198E+10 52764286.00 0.129922E+10 0.00 0.00
August 0.175245E+10 0.234910E+09 0.119561E+10 15885994.55 0.117972E+10 0.00 0.00
September 0.940470E+09 0.575868E+09 0.871220E+09 506482.57 0.870713E+09 0.00 0.00
October 0.532605E+09 0.122806E+10 0.778470E+09 0.00 0.778470E+09 0.00 0.00
November 0.100161E+09 0.207544E+10 0.528407E+09 0.00 0.528407E+09 0.00 0.00
December 3885915.31 0.287218E+10 0.379071E+09 0.00 0.379071E+09 0.00 0.00
               
Annual Sum or Average 0.898707E+10 0.176723E+11 0.105304E+11 0.193151E+09 0.103373E+11 0.00 0.00
Minimum of Months 3885915.31 0.154541E+09 0.379071E+09 0.00 0.379071E+09 0.00 0.00
Maximum of Months 0.199922E+10 0.311594E+10 0.135198E+10 71697591.63 0.129922E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.581592E+09 0.195995E+10 0.867802E+09 0.404742E+09 0.463060E+09 0.00 0.00
February 0.837785E+09 0.173206E+10 0.113982E+10 0.571796E+09 0.568025E+09 0.00 0.00
March 0.138284E+10 0.135252E+10 0.145924E+10 0.617570E+09 0.841672E+09 0.00 0.00
April 0.175818E+10 0.901992E+09 0.154433E+10 0.608142E+09 0.936188E+09 0.00 0.00
May 0.247479E+10 0.545811E+09 0.183908E+10 0.614505E+09 0.122457E+10 0.00 0.00
June 0.266564E+10 0.247295E+09 0.167963E+10 0.499674E+09 0.117996E+10 0.00 0.00
July 0.307208E+10 0.110282E+09 0.174360E+10 0.517122E+09 0.122648E+10 0.00 0.00
August 0.337108E+10 0.162340E+09 0.197360E+10 0.787607E+09 0.118599E+10 0.00 0.00
September 0.233132E+10 0.355320E+09 0.153074E+10 0.651522E+09 0.879216E+09 0.00 0.00
October 0.208098E+10 0.771632E+09 0.160713E+10 0.765679E+09 0.841447E+09 0.00 0.00
November 0.933520E+09 0.128232E+10 0.100801E+10 0.431686E+09 0.576325E+09 0.00 0.00
December 0.660769E+09 0.174447E+10 0.881346E+09 0.473426E+09 0.407920E+09 0.00 0.00
               
Annual Sum or Average 0.221506E+11 0.111660E+11 0.172743E+11 0.694347E+10 0.103309E+11 0.00 0.00
Minimum of Months 0.581592E+09 0.110282E+09 0.867802E+09 0.404742E+09 0.407920E+09 0.00 0.00
Maximum of Months 0.337108E+10 0.195995E+10 0.197360E+10 0.787607E+09 0.122648E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.108656E+10 0.216132E+10 0.135374E+10 0.790580E+09 0.563158E+09 0.00 0.00
February 0.135183E+10 0.192959E+10 0.162422E+10 0.957120E+09 0.667105E+09 0.00 0.00
March 0.157585E+10 0.150106E+10 0.169540E+10 0.777636E+09 0.917766E+09 0.00 0.00
April 0.143004E+10 0.100953E+10 0.141746E+10 0.441590E+09 0.975874E+09 0.00 0.00
May 0.160880E+10 0.590986E+09 0.141835E+10 0.214283E+09 0.120407E+10 0.00 0.00
June 0.182049E+10 0.276900E+09 0.134457E+10 0.160548E+09 0.118402E+10 0.00 0.00
July 0.215626E+10 0.122825E+09 0.141229E+10 0.178230E+09 0.123406E+10 0.00 0.00
August 0.255955E+10 0.197264E+09 0.168072E+10 0.474253E+09 0.120647E+10 0.00 0.00
September 0.211167E+10 0.435157E+09 0.159650E+10 0.651799E+09 0.944698E+09 0.00 0.00
October 0.259078E+10 0.901647E+09 0.216206E+10 0.118845E+10 0.973613E+09 0.00 0.00
November 0.136972E+10 0.142215E+10 0.145111E+10 0.761817E+09 0.689291E+09 0.00 0.00
December 0.124302E+10 0.192953E+10 0.143156E+10 0.924471E+09 0.507087E+09 0.00 0.00
               
Annual Sum or Average 0.209046E+11 0.124780E+11 0.185880E+11 0.752078E+10 0.110672E+11 0.00 0.00
Minimum of Months 0.108656E+10 0.122825E+09 0.134457E+10 0.160548E+09 0.507087E+09 0.00 0.00
Maximum of Months 0.259078E+10 0.216132E+10 0.216206E+10 0.118845E+10 0.123406E+10 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 1.17 -0.7 -4.4 5.65 -10.4 36.91 88.07 0.05
February -0.2 -2.6 -7.5 5.07 -13.4 46.98 136.68 0.04
March 5.59 3.43 0.29 5.58 -4.1 68.24 153.73 0.03
April 10.94 8.00 4.75 4.99 0.53 82.64 161.98 0.05
May 16.05 12.31 9.14 4.42 7.77 109.28 173.60 0.03
June 21.71 18.08 15.84 4.92 13.23 112.36 186.51 0.01
July 25.05 21.76 20.26 4.06 17.39 114.46 172.96 0.02
August 24.79 19.84 17.14 4.19 14.42 95.56 226.16 0.00
September 19.96 15.96 13.24 3.91 10.59 73.65 166.08 0.03
October 14.02 11.03 7.95 4.86 2.64 61.34 179.75 0.00
November 7.31 4.98 2.14 5.60 -4.0 48.23 90.71 0.03
December 3.33 0.91 -2.8 5.64 -8.5 30.23 98.59 0.04
                 
Annual Sum or Average 12.55 9.49 6.43 4.91 2.28 73.48 153.05 0.03
Minimum of Months -0.2 -2.6 -7.5 3.91 -13.4 30.23 88.07 0.00
Maximum of Months 25.05 21.76 20.26 5.65 17.39 114.46 226.16 0.05



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 12.20 24-JAN-12:20 11.81 11.50 1.00 8.15 93.67 0.00
February 10.00 20-FEB-11:00 4.36 -3.3 2.60 -3.9 151.50 540.00
March 22.20 27-MAR-15:00 16.34 12.80 6.70 11.65 136.50 590.00
April 26.70 07-APR-12:00 16.40 9.40 6.20 11.65 179.00 713.50
May 30.00 30-MAY-12:00 18.00 10.60 5.20 17.39 233.50 730.00
June 36.70 19-JUN-11:00 24.28 19.40 5.20 24.83 185.00 771.50
July 33.90 07-JUL-11:00 23.31 18.90 3.60 23.82 331.00 570.00
August 33.90 24-AUG-14:00 20.23 12.80 8.80 21.61 240.00 432.00
September 31.10 01-SEP-13:00 17.34 8.30 4.60 18.46 182.00 662.00
October 25.00 04-OCT-12:00 18.54 15.00 5.20 11.27 171.50 695.00
November 17.80 04-NOV-12:20 12.57 8.50 3.60 6.15 182.50 595.67
December 12.20 17-DEC-12:20 4.65 -6.1 4.27 -4.7 53.17 801.67
                 
Annual Sum or Average                
Minimum of Months 10.00   4.36 -6.1 1.00 -4.7 53.17 0.00
Maximum of Months 36.70   24.28 19.40 8.80 24.83 331.00 801.67



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -12.2 02-JAN-04:00 -13.6 -19.4 2.60 -30.7 0.00 0.00
February -13.9 06-FEB-02:00 -15.3 -22.8 7.20 -34.1 0.00 0.00
March -5.0 23-MAR-03:00 -7.6 -14.4 1.50 -23.9 0.00 0.00
April 2.20 01-APR-03:00 0.57 -1.7 3.10 -6.6 0.00 0.00
May 6.10 01-MAY-04:00 4.33 2.20 3.60 -9.7 25.50 0.00
June 13.30 03-JUN-02:00 9.35 5.60 4.60 -2.1 0.00 0.00
July 18.30 02-JUL-02:00 17.54 17.20 0.00 5.33 0.00 0.00
August 15.00 08-AUG-04:00 12.47 10.60 3.10 3.06 0.00 0.00
September 10.00 24-SEP-05:00 8.56 7.20 2.60 -3.4 18.50 158.50
October 2.20 09-OCT-03:00 1.71 1.10 0.00 -13.7 0.00 0.00
November -4.4 24-NOV-05:00 -6.2 -10.0 1.50 -19.7 0.00 0.00
December -8.3 31-DEC-23:00 -10.6 -18.9 9.30 -26.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -13.9   -15.3 -22.8 0.00 -34.1 0.00 0.00
Maximum of Months 18.30   17.54 17.20 9.30 5.33 25.50 158.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 11.93 24-JAN-11:00 12.20 11.70 1.50 8.15 103.00 0.00
February 6.67 28-FEB-09:00 7.20 6.10 4.10 2.01 101.50 0.00
March 16.99 27-MAR-12:00 20.60 15.00 3.60 10.50 295.50 565.50
April 17.70 09-APR-10:00 21.70 15.60 4.10 14.84 244.50 281.50
May 20.43 31-MAY-12:00 26.10 17.80 4.10 17.03 214.00 772.00
June 24.96 15-JUN-11:00 31.10 22.80 5.20 22.47 380.00 460.00
July 26.10 08-JUL-11:00 32.20 23.90 5.20 22.47 354.00 501.50
August 25.84 03-AUG-13:00 30.00 24.40 6.20 20.57 298.00 500.00
September 23.57 07-SEP-13:00 27.20 22.20 6.20 15.02 148.00 730.50
October 19.76 25-OCT-10:00 25.00 17.20 7.70 14.84 189.00 308.50
November 16.10 10-NOV-07:00 16.10 16.10 8.20 12.98 71.50 0.00
December 10.26 25-DEC-08:00 10.60 10.00 3.60 6.15 43.00 0.00
                 
Annual Sum or Average                
Minimum of Months 6.67   7.20 6.10 1.50 2.01 43.00 0.00
Maximum of Months 26.10   32.20 24.40 8.20 22.47 380.00 772.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 11.70 18-JAN-15:00 12.20 11.93 14.90 8.15 22.00 2.00
February 6.10 28-FEB-10:20 7.03 6.58 3.43 1.87 109.83 0.00
March 15.00 27-MAR-12:20 18.00 16.18 3.93 10.11 271.83 611.17
April 15.60 09-APR-10:00 21.70 17.70 4.10 14.84 244.50 281.50
May 18.00 18-MAY-09:00 18.00 18.00 4.60 15.39 265.50 12.00
June 22.80 15-JUN-11:00 31.10 24.96 5.20 22.47 380.00 460.00
July 24.40 09-JUL-07:00 27.20 25.17 2.10 15.39 195.00 504.00
August 25.00 03-AUG-19:00 26.10 25.32 5.70 19.35 0.00 0.00
September 22.20 07-SEP-13:00 27.20 23.57 6.20 15.02 148.00 730.50
October 18.30 05-OCT-18:00 19.40 18.62 7.70 6.55 0.00 0.00
November 16.10 10-NOV-07:00 16.10 16.10 8.20 12.98 71.50 0.00
December 10.00 25-DEC-08:00 10.60 10.26 3.60 6.15 43.00 0.00
                 
Annual Sum or Average                
Minimum of Months 6.10   7.03 6.58 2.10 1.87 0.00 0.00
Maximum of Months 25.00   31.10 25.32 14.90 22.47 380.00 730.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 10.03 13.58 0.00
February 18.00 13.00 16.00 9.54 21.42 0.00
March 18.00 13.00 16.00 10.65 30.29 0.00
April 18.00 13.00 16.00 13.15 37.02 0.00
May 18.00 13.00 16.00 16.36 45.86 0.00
June 18.00 13.00 16.00 19.42 49.74 0.00
July 18.00 13.00 16.00 21.50 48.12 0.00
August 18.00 13.00 16.00 22.05 49.54 0.00
September 18.00 13.00 16.00 20.89 34.71 0.00
October 18.00 13.00 16.00 18.36 29.93 0.00
November 18.00 13.00 16.00 15.14 17.00 0.00
December 18.00 13.00 16.00 12.10 12.41 0.00
             
Annual Sum or Average 18.00 13.00 16.00 15.80 32.53 0.00
Minimum of Months 18.00 13.00 16.00 9.54 12.41 0.00
Maximum of Months 18.00 13.00 16.00 22.05 49.74 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770540E+10 -0.754278E+10 0.00 0.00 744.00 0.00 -162616781.8 81.21 0.00 0.00
February 0.696287E+10 -0.681596E+10 0.00 0.00 672.00 0.00 -146907615.9 81.21 0.00 0.00
March 0.770384E+10 -0.754146E+10 0.00 0.00 744.00 0.00 -162377684.8 81.21 0.00 0.00
April 0.746556E+10 -0.730860E+10 0.00 0.00 720.00 0.00 -156956173.1 81.21 0.00 0.00
May 0.770477E+10 -0.754280E+10 0.00 0.00 744.00 0.00 -161965594.0 81.21 0.00 0.00
June 0.745704E+10 -0.730053E+10 0.00 0.00 720.00 0.00 -156508964.2 81.21 0.00 0.00
July 0.771250E+10 -0.755084E+10 0.00 0.00 744.00 0.00 -161661612.7 81.21 0.00 0.00
August 0.770442E+10 -0.754280E+10 0.00 0.00 744.00 0.00 -161625201.4 81.21 0.00 0.00
September 0.746655E+10 -0.730994E+10 0.00 0.00 720.00 0.00 -156600711.2 81.21 0.00 0.00
October 0.770350E+10 -0.754145E+10 0.00 0.00 744.00 0.00 -162056539.6 81.21 0.00 0.00
November 0.744956E+10 -0.729243E+10 0.00 0.00 720.00 0.00 -157127027.1 81.21 0.00 0.00
December 0.771337E+10 -0.755085E+10 0.00 0.00 744.00 0.00 -162516125.6 81.21 0.00 0.00
                     
Annual Sum or Average 0.907494E+11 -0.888405E+11 0.00 0.00 8760.00 0.00 -0.190892E+10 81.21 0.00 0.00
Minimum of Months 0.696287E+10 -0.755085E+10 0.00 0.00 672.00 0.00 -162616781.8 81.21 0.00 0.00
Maximum of Months 0.771337E+10 -0.681596E+10 0.00 0.00 744.00 0.00 -146907615.9 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYSLAUNDRY HPWH TANK

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.675920E+11 -0.119226E+12 0.00 0.00 744.00 0.00 -879553526.1 81.67 0.00 0.00
February 0.644977E+11 -0.108438E+12 0.00 0.00 672.00 0.00 -804536045.5 81.67 0.00 0.00
March 0.601803E+11 -0.118172E+12 0.00 0.00 744.00 0.00 -845955030.1 81.67 0.00 0.00
April 0.473379E+11 -0.110276E+12 0.00 0.00 720.00 0.00 -778985284.3 81.67 0.00 0.00
May 0.370866E+11 -0.108516E+12 0.00 0.00 744.00 0.00 -765172156.1 81.67 0.00 0.00
June 0.233861E+11 -0.100002E+12 0.00 0.00 720.00 0.00 -698442467.8 81.68 0.00 0.00
July 0.161925E+11 -0.998143E+11 0.00 0.00 744.00 0.00 -695694438.8 81.68 0.00 0.00
August 0.174105E+11 -0.988899E+11 0.00 0.00 744.00 0.00 -698222260.1 81.68 0.00 0.00
September 0.239715E+11 -0.975879E+11 0.00 0.00 720.00 0.00 -711764269.1 81.68 0.00 0.00
October 0.358243E+11 -0.105126E+12 0.00 0.00 744.00 0.00 -781452914.8 81.67 0.00 0.00
November 0.488709E+11 -0.107006E+12 0.00 0.00 720.00 0.00 -805498110.9 81.67 0.00 0.00
December 0.616465E+11 -0.115720E+12 0.00 0.00 744.00 0.00 -863404081.0 81.67 0.00 0.00
                     
Annual Sum or Average 0.503997E+12 -0.128877E+13 0.00 0.00 8760.00 0.00 -0.932868E+10 81.68 0.00 0.00
Minimum of Months 0.161925E+11 -0.119226E+12 0.00 0.00 672.00 0.00 -879553526.1 81.67 0.00 0.00
Maximum of Months 0.675920E+11 -0.975879E+11 0.00 0.00 744.00 0.00 -695694438.8 81.68 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 HPWH TANK

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January -0.124709E+10 -0.728220E+11 0.00 0.00 744.00 0.00 -0.143907E+10 59.19 0.00 0.00
February -482541520.8 -0.664084E+11 0.00 0.00 672.00 0.00 -0.132274E+10 59.13 0.00 0.00
March -0.195230E+10 -0.720460E+11 0.00 0.00 744.00 0.00 -0.135928E+10 59.23 0.00 0.00
April -0.233533E+10 -0.662045E+11 0.00 0.00 720.00 0.00 -0.122148E+10 59.29 0.00 0.00
May -0.263661E+10 -0.637481E+11 0.00 0.00 744.00 0.00 -0.116767E+10 59.32 0.00 0.00
June -0.262546E+10 -0.573915E+11 0.00 0.00 720.00 0.00 -0.103006E+10 59.36 0.00 0.00
July -0.247664E+10 -0.562054E+11 0.00 0.00 744.00 0.00 -0.100283E+10 59.39 0.00 0.00
August -0.242478E+10 -0.554648E+11 0.00 0.00 744.00 0.00 -0.100901E+10 59.40 0.00 0.00
September -0.242776E+10 -0.552793E+11 0.00 0.00 720.00 0.00 -0.106281E+10 59.38 0.00 0.00
October -0.240121E+10 -0.607850E+11 0.00 0.00 744.00 0.00 -0.120779E+10 59.35 0.00 0.00
November -0.196627E+10 -0.633502E+11 0.00 0.00 720.00 0.00 -0.128615E+10 59.31 0.00 0.00
December -0.157102E+10 -0.698473E+11 0.00 0.00 744.00 0.00 -0.140127E+10 59.23 0.00 0.00
                     
Annual Sum or Average -0.245470E+11 -0.759552E+12 0.00 0.00 8760.00 0.00 -0.145102E+11 59.30 0.00 0.00
Minimum of Months -0.263661E+10 -0.728220E+11 0.00 0.00 672.00 0.00 -0.143907E+10 59.13 0.00 0.00
Maximum of Months -482541520.8 -0.552793E+11 0.00 0.00 744.00 0.00 -0.100283E+10 59.40 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.87 0.86 01-JAN-07:49 5176.91 36.75 196.33 243.00 2471.04 33.51 185.67 185.33
February 216.00 0.87 0.86 01-FEB-07:49 7576.97 37.36 208.17 257.67 1072.58 26.98 197.17 220.83
March 275.00 0.87 0.86 01-MAR-06:00 3660.64 25.45 145.50 324.17 663.29 22.31 202.17 250.00
April 261.17 0.87 0.86 01-APR-14:39 1301.07 20.12 41.33 339.33 530.10 21.86 192.00 269.33
May 372.00 0.87 0.86 01-MAY-06:19 1177.25 19.83 26.50 392.33 467.29 21.55 232.17 306.83
June 351.83 0.87 0.86 01-JUN-05:00 1116.40 19.73 24.50 382.00 450.38 21.48 237.00 308.50
July 365.17 0.87 0.86 01-JUL-06:19 1244.71 19.90 61.67 389.83 492.77 21.64 249.67 313.00
August 389.17 0.87 0.86 01-AUG-06:30 1332.88 20.19 89.83 371.00 539.25 21.91 297.17 315.17
September 285.33 0.87 0.86 01-SEP-06:49 1483.28 20.30 56.67 324.17 598.62 22.07 221.83 266.67
October 305.50 0.87 0.86 01-OCT-14:39 7320.58 35.44 274.17 307.17 916.73 24.67 272.50 277.50
November 240.83 0.87 0.86 01-NOV-06:00 5136.25 36.19 234.83 257.17 1363.21 29.63 220.67 224.67
December 211.17 0.87 0.86 01-DEC-07:40 4808.36 37.73 207.67 245.00 3714.00 37.71 204.50 201.17
                         
Annual Sum or Average 3472.67 0.87     3090.38 26.03 1567.17 3832.83 959.22 24.56 2712.50 3139.00
Minimum of Months 199.50 0.87 0.86   1116.40 19.73 24.50 243.00 450.38 21.48 185.67 185.33
Maximum of Months 389.17 0.87 0.86   7576.97 37.73 274.17 392.33 3714.00 37.71 297.17 315.17



Table of Contents

Report: DaylightingReportMonthly

For: CAFE_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.25 0.22 01-JAN-07:49 5567.01 36.81 196.50 257.17 2861.75 33.49 186.83 213.00
February 216.00 0.24 0.22 01-FEB-07:40 8023.35 37.45 208.33 267.00 1518.58 26.71 185.83 243.33
March 275.00 0.25 0.22 01-MAR-06:00 4025.46 25.63 139.50 334.50 1026.62 22.39 194.17 302.17
April 261.17 0.25 0.22 01-APR-06:30 1583.06 20.48 67.00 354.33 811.38 22.06 196.50 314.67
May 372.00 0.25 0.22 01-MAY-05:49 1380.02 20.47 113.67 407.33 669.35 22.00 253.67 364.83
June 351.83 0.25 0.22 01-JUN-05:30 1310.30 20.39 114.00 400.67 643.63 21.94 259.00 355.67
July 365.17 0.25 0.22 01-JUL-05:30 1451.21 20.54 128.50 410.17 698.52 22.09 279.33 359.33
August 389.17 0.26 0.22 01-AUG-05:49 1593.31 20.62 147.17 381.17 798.93 22.18 305.83 352.00
September 285.33 0.25 0.22 01-SEP-06:10 1809.01 20.54 81.00 337.17 923.45 22.17 215.50 302.00
October 305.50 0.24 0.22 01-OCT-14:39 7766.46 35.50 272.33 315.67 1361.21 24.56 278.67 297.50
November 240.83 0.24 0.22 01-NOV-06:49 5500.00 36.26 234.83 265.00 1723.72 29.57 222.00 247.33
December 211.17 0.25 0.22 01-DEC-07:30 5196.41 37.79 207.83 254.50 4100.33 37.72 204.00 228.83
                         
Annual Sum or Average 3472.67 0.25     3397.73 26.37 1910.67 3984.67 1265.58 24.73 2781.33 3580.67
Minimum of Months 199.50 0.24 0.22   1310.30 20.39 67.00 254.50 643.63 21.94 185.83 213.00
Maximum of Months 389.17 0.26 0.22   8023.35 37.79 272.33 410.17 4100.33 37.72 305.83 364.83



Table of Contents

Report: DaylightingReportMonthly

For: DINING_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.65 0.60 01-JAN-09:09 391.07 14.77 0.00 222.00 188.63 18.18 0.00 93.33
February 216.00 0.64 0.60 01-FEB-08:00 401.96 15.47 0.00 241.83 206.10 18.94 0.00 132.00
March 275.00 0.63 0.60 01-MAR-07:30 551.12 16.85 0.00 321.83 265.81 20.10 4.83 222.67
April 261.17 0.62 0.60 01-APR-14:39 607.24 17.45 0.00 351.83 292.87 20.68 40.50 285.17
May 372.00 0.61 0.60 01-MAY-05:49 833.94 18.16 0.00 415.33 372.56 22.06 183.33 364.17
June 351.83 0.61 0.60 01-JUN-04:00 925.90 19.28 28.83 407.67 402.49 23.11 230.83 370.00
July 365.17 0.61 0.60 01-JUL-04:00 930.54 18.21 0.00 416.67 401.47 22.75 233.50 370.83
August 389.17 0.62 0.60 01-AUG-05:40 737.63 17.90 0.00 385.33 341.30 21.13 163.33 348.67
September 285.33 0.62 0.60 01-SEP-06:19 556.44 17.07 0.00 329.00 271.92 20.32 14.00 255.00
October 305.50 0.63 0.60 01-OCT-14:39 503.31 16.62 0.00 296.83 257.93 19.98 0.00 230.50
November 240.83 0.64 0.60 01-NOV-07:30 439.45 15.33 0.00 244.83 206.05 18.65 0.00 131.50
December 211.17 0.68 0.60 01-DEC-09:20 309.68 13.84 0.00 210.67 155.68 17.42 0.00 47.00
                         
Annual Sum or Average 3472.67 0.63     639.74 17.05 28.83 3843.83 296.67 20.61 870.33 2850.83
Minimum of Months 199.50 0.61 0.60   309.68 13.84 0.00 210.67 155.68 17.42 0.00 47.00
Maximum of Months 389.17 0.68 0.60   930.54 19.28 28.83 416.67 402.49 23.11 233.50 370.83



Table of Contents

Report: DaylightingReportMonthly

For: BANQUET_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.65 0.60 01-JAN-09:09 391.07 14.77 0.00 222.00 188.63 18.18 0.00 93.33
February 216.00 0.64 0.60 01-FEB-08:00 401.96 15.47 0.00 241.83 206.10 18.94 0.00 132.00
March 275.00 0.63 0.60 01-MAR-07:30 551.12 16.85 0.00 321.83 265.81 20.10 4.83 222.67
April 261.17 0.62 0.60 01-APR-14:39 607.24 17.45 0.00 351.83 292.87 20.68 40.50 285.17
May 372.00 0.61 0.60 01-MAY-05:49 833.94 18.16 0.00 415.33 372.56 22.06 183.33 364.17
June 351.83 0.61 0.60 01-JUN-04:00 925.90 19.28 28.83 407.67 402.49 23.11 230.83 370.00
July 365.17 0.61 0.60 01-JUL-04:00 930.54 18.21 0.00 416.67 401.47 22.75 233.50 370.83
August 389.17 0.62 0.60 01-AUG-05:40 737.63 17.90 0.00 385.33 341.30 21.13 163.33 348.67
September 285.33 0.62 0.60 01-SEP-06:19 556.44 17.07 0.00 329.00 271.92 20.32 13.83 255.00
October 305.50 0.63 0.60 01-OCT-14:39 503.31 16.62 0.00 296.83 257.93 19.98 0.00 230.50
November 240.83 0.64 0.60 01-NOV-07:30 439.45 15.33 0.00 244.83 206.05 18.65 0.00 131.50
December 211.17 0.68 0.60 01-DEC-09:20 309.68 13.84 0.00 210.67 155.68 17.42 0.00 47.00
                         
Annual Sum or Average 3472.67 0.63     639.74 17.05 28.83 3843.83 296.67 20.61 870.17 2850.83
Minimum of Months 199.50 0.61 0.60   309.68 13.84 0.00 210.67 155.68 17.42 0.00 47.00
Maximum of Months 389.17 0.68 0.60   930.54 19.28 28.83 416.67 402.49 23.11 233.50 370.83



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.604557E+11 99408.61 19-JAN-16:10 0.00 0.00 0.00 0.00 0.00
February 0.520089E+11 108384.08 06-FEB-07:20 0.00 0.00 0.00 0.00 0.00
March 0.352494E+11 107471.80 29-MAR-16:00 0.00 0.00 0.00 0.00 0.00
April 0.593742E+11 107969.38 03-APR-17:50 0.00 0.00 0.00 0.00 0.00
May 0.282046E+11 101507.46 01-MAY-06:20 0.00 0.00 0.00 0.00 0.00
June 0.644478E+09 22381.29 03-JUN-05:00 0.00 0.00 0.00 0.00 0.00
July 57108183.86 14898.28 11-JUL-15:05 0.00 0.00 0.00 0.00 0.00
August 0.277726E+09 19647.68 20-AUG-13:45 0.00 0.00 0.00 0.00 0.00
September 0.705125E+10 72830.43 24-SEP-06:00 0.00 0.00 0.00 0.00 0.00
October 0.430074E+11 109512.61 19-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.634692E+11 104010.29 17-NOV-18:07 0.00 0.00 0.00 0.00 0.00
December 0.280213E+11 105349.42 17-DEC-09:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.377821E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 57108183.86 14898.28   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.634692E+11 109512.61   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 4903072.98 2204.40 30-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 4903072.98     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 4903072.98 2204.40   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.283603E+10 2445.40 02-JAN-07:20 0.00 0.00 0.00 0.00 0.00
February 0.213187E+10 2360.63 06-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 0.145043E+10 1667.35 17-MAR-06:05 0.00 0.00 0.00 0.00 0.00
April 0.915901E+09 1425.18 21-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 0.264620E+09 903.79 04-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 87691.03 49.96 07-JUN-04:00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 43143577.34 603.87 24-SEP-05:00 0.00 0.00 0.00 0.00 0.00
October 0.127349E+09 803.77 28-OCT-06:20 0.00 0.00 0.00 0.00 0.00
November 0.139559E+10 1690.21 23-NOV-06:00 0.00 0.00 0.00 0.00 0.00
December 0.225860E+10 1838.43 30-DEC-17:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.114236E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.283603E+10 2445.40   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.141142E+09 544.24 02-JAN-15:00 0.00 0.00 0.00 0.00 0.00
February 92564437.78 477.73 06-FEB-15:00 0.00 0.00 0.00 0.00 0.00
March 6820353.39 275.84 17-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 1610291.75 147.74 21-APR-14:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 6648694.32 237.76 26-NOV-16:00 0.00 0.00 0.00 0.00 0.00
December 52861268.93 386.14 12-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.301647E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.141142E+09 544.24   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.121834E+10 1153.71 02-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.114392E+10 1132.99 06-FEB-14:40 0.00 0.00 0.00 0.00 0.00
March 0.445597E+09 754.06 18-MAR-10:37 0.00 0.00 0.00 0.00 0.00
April 0.109541E+09 522.57 03-APR-10:33 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.292132E+09 709.66 24-NOV-11:35 0.00 0.00 0.00 0.00 0.00
December 0.753393E+09 748.80 31-DEC-18:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.396293E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.121834E+10 1153.71   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.971748E+09 767.09 02-JAN-15:00 0.00 0.00 0.00 0.00 0.00
February 0.894243E+09 777.89 06-FEB-16:00 0.00 0.00 0.00 0.00 0.00
March 0.401961E+09 494.07 17-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 0.120973E+09 360.95 21-APR-14:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.280286E+09 454.66 25-NOV-17:00 0.00 0.00 0.00 0.00 0.00
December 0.666194E+09 555.57 31-DEC-18:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.333540E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.971748E+09 777.89   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.488240E+09 3036.42 02-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 0.465503E+09 3036.42 06-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 0.376028E+09 2393.78 18-MAR-05:00 0.00 0.00 0.00 0.00 0.00
April 0.234889E+09 2056.20 22-APR-05:00 0.00 0.00 0.00 0.00 0.00
May 0.131035E+09 1445.13 01-MAY-04:00 0.00 0.00 0.00 0.00 0.00
June 41923959.43 890.03 07-JUN-04:00 0.00 0.00 0.00 0.00 0.00
July 27961647.04 780.63 10-JUL-10:40 0.00 0.00 0.00 0.00 0.00
August 20220626.88 929.43 23-AUG-10:50 0.00 0.00 0.00 0.00 0.00
September 58081361.73 1029.15 26-SEP-04:00 0.00 0.00 0.00 0.00 0.00
October 0.129972E+09 1547.68 28-OCT-05:00 0.00 0.00 0.00 0.00 0.00
November 0.314415E+09 2449.65 24-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.434962E+09 2411.35 11-DEC-05:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.272323E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 20220626.88 780.63   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.488240E+09 3036.42   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.184304E+10 5522.71 08-JAN-15:40 0.00 0.00 0.00 0.00 0.00
February 0.982087E+09 4657.48 27-FEB-14:50 0.00 0.00 0.00 0.00 0.00
March 0.596724E+09 3844.56 16-MAR-14:00 0.00 0.00 0.00 0.00 0.00
April 0.336580E+09 3606.05 21-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 81397309.81 2159.03 04-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 854483.34 868.45 26-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 7400235.80 1220.94 31-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.454829E+09 3306.93 26-NOV-16:00 0.00 0.00 0.00 0.00 0.00
December 0.121789E+10 4701.32 11-DEC-15:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.552080E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.184304E+10 5522.71   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.932606E+09 8460.73 08-JAN-16:00 0.00 0.00 0.00 0.00 0.00
February 0.399278E+09 6325.53 27-FEB-14:50 0.00 0.00 0.00 0.00 0.00
March 23794929.35 3262.96 17-MAR-12:30 0.00 0.00 0.00 0.00 0.00
April 4959510.43 1308.85 21-APR-14:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 18527633.22 2635.46 26-NOV-16:00 0.00 0.00 0.00 0.00 0.00
December 0.316557E+09 5776.86 11-DEC-15:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.169572E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.932606E+09 8460.73   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.882159E+10 8427.00 14-JAN-16:15 0.00 0.00 0.00 0.00 0.00
February 0.666063E+10 7525.51 06-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 0.266499E+10 5418.58 17-MAR-08:03 0.00 0.00 0.00 0.00 0.00
April 0.844808E+09 4149.82 21-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.320181E+10 5113.34 25-NOV-17:00 0.00 0.00 0.00 0.00 0.00
December 0.659521E+10 6774.21 11-DEC-15:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.287890E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.882159E+10 8427.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.548632E+10 5066.04 02-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.464285E+10 5012.05 06-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 0.208498E+10 3239.02 23-MAR-06:05 0.00 0.00 0.00 0.00 0.00
April 0.695400E+09 2031.08 21-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 1874336.66 367.33 01-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 46816947.80 1418.66 29-OCT-05:00 0.00 0.00 0.00 0.00 0.00
November 0.209102E+10 3234.01 24-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.419366E+10 3152.82 15-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.192429E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.548632E+10 5066.04   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 25824.95 43.04 06-FEB-04:00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 25824.95     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 25824.95 43.04   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.151904E+10 5802.53 02-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.172003E+10 6505.59 06-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.125874E+09 2645.86 17-MAR-12:10 0.00 0.00 0.00 0.00 0.00
April 1091.90 0.23 09-APR-15:55 0.00 0.00 0.00 0.00 0.00
May 9834.81 8.68 30-MAY-08:08 0.00 0.00 0.00 0.00 0.00
June 11539.64 0.23 29-JUN-16:05 0.00 0.00 0.00 0.00 0.00
July 6965.48 0.23 18-JUL-05:20 0.00 0.00 0.00 0.00 0.00
August 6322.32 0.23 16-AUG-23:03 0.00 0.00 0.00 0.00 0.00
September 15917.17 27.94 19-SEP-15:05 0.00 0.00 0.00 0.00 0.00
October 4403.52 0.23 06-OCT-09:40 0.00 0.00 0.00 0.00 0.00
November 0.137710E+09 1722.02 24-NOV-07:00 0.00 0.00 0.00 0.00 0.00
December 0.194570E+09 3445.85 31-DEC-24:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.369727E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1091.90 0.23   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.172003E+10 6505.59   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.470603E+10 9897.66 14-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.381385E+10 9896.72 07-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.179043E+10 9728.20 17-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.787244E+09 9400.19 21-APR-15:01 0.00 0.00 0.00 0.00 0.00
May 61361206.62 3538.20 01-MAY-18:04 0.00 0.00 0.00 0.00 0.00
June 5021474.20 3370.87 29-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 2913115.27 2407.92 18-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 4052865.28 4069.85 08-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 12447502.13 4179.49 26-SEP-15:04 0.00 0.00 0.00 0.00 0.00
October 0.132671E+09 3607.54 19-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.209604E+10 9649.28 25-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.373014E+10 9863.62 31-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.171422E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2913115.27 2407.92   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.470603E+10 9897.66   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.562633E+10 9859.24 14-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.495387E+10 9858.30 07-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.234573E+10 9696.16 17-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.920469E+09 9388.49 03-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 62452585.34 3357.45 03-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 1704254.08 2249.58 12-JUN-08:55 0.00 0.00 0.00 0.00 0.00
July 1512428.89 2542.51 18-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 1345081.77 2581.37 13-AUG-06:54 0.00 0.00 0.00 0.00 0.00
September 9038527.66 4507.73 28-SEP-08:53 0.00 0.00 0.00 0.00 0.00
October 0.262747E+09 4115.46 19-OCT-18:04 0.00 0.00 0.00 0.00 0.00
November 0.275878E+10 9727.50 24-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.470884E+10 9825.30 31-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.216528E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1345081.77 2249.58   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.562633E+10 9859.24   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.185970E+11 55996.36 02-JAN-16:02 0.00 0.00 0.00 0.00 0.00
February 0.182580E+11 56213.14 06-FEB-16:01 0.00 0.00 0.00 0.00 0.00
March 0.527875E+10 53829.01 16-MAR-15:01 0.00 0.00 0.00 0.00 0.00
April 0.819898E+09 30589.68 03-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 45357882.20 36148.02 03-MAY-15:05 0.00 0.00 0.00 0.00 0.00
June 1947155.99 7959.48 06-JUN-15:07 0.00 0.00 0.00 0.00 0.00
July 1414881.70 3602.24 31-JUL-18:58 0.00 0.00 0.00 0.00 0.00
August 3401794.55 9618.17 25-AUG-21:57 0.00 0.00 0.00 0.00 0.00
September 13664268.13 14259.74 17-SEP-15:07 0.00 0.00 0.00 0.00 0.00
October 0.246526E+09 39301.76 30-OCT-15:05 0.00 0.00 0.00 0.00 0.00
November 0.535528E+10 53967.86 22-NOV-16:01 0.00 0.00 0.00 0.00 0.00
December 0.132491E+11 54742.47 31-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.618704E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1414881.70 3602.24   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.185970E+11 56213.14   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.467264E+10 9674.32 14-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.370968E+10 9673.05 05-FEB-19:01 0.00 0.00 0.00 0.00 0.00
March 0.190502E+10 9491.71 17-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.797362E+09 9192.17 21-APR-15:01 0.00 0.00 0.00 0.00 0.00
May 65456306.99 3720.76 02-MAY-18:05 0.00 0.00 0.00 0.00 0.00
June 1680295.75 3386.12 13-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 402159.27 1394.02 18-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 67256.43 672.56 07-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 8244628.79 3376.04 21-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 0.143501E+09 4068.53 06-OCT-18:04 0.00 0.00 0.00 0.00 0.00
November 0.196638E+10 9428.10 25-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.367495E+10 9640.97 31-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.169454E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 67256.43 672.56   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.467264E+10 9674.32   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.556923E+10 9637.15 14-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.481701E+10 9635.85 05-FEB-19:01 0.00 0.00 0.00 0.00 0.00
March 0.246331E+10 9471.96 17-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.923866E+09 9165.28 21-APR-15:01 0.00 0.00 0.00 0.00 0.00
May 69652484.06 4268.68 01-MAY-18:04 0.00 0.00 0.00 0.00 0.00
June 901363.25 2005.66 01-JUN-21:55 0.00 0.00 0.00 0.00 0.00
July 251524.71 831.32 23-JUL-21:56 0.00 0.00 0.00 0.00 0.00
August 225898.90 1130.94 06-AUG-21:56 0.00 0.00 0.00 0.00 0.00
September 6327875.56 2545.76 23-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 0.277220E+09 4076.89 19-OCT-15:05 0.00 0.00 0.00 0.00 0.00
November 0.252542E+10 9456.82 23-NOV-19:01 0.00 0.00 0.00 0.00 0.00
December 0.457107E+10 9603.91 31-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.212245E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 225898.90 831.32   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.556923E+10 9637.15   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.167590E+10 2953.30 14-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.139301E+10 2953.00 07-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.705334E+09 2904.69 17-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.332573E+09 2833.66 21-APR-15:01 0.00 0.00 0.00 0.00 0.00
May 38410621.94 1013.52 01-MAY-18:04 0.00 0.00 0.00 0.00 0.00
June 1335710.52 933.18 22-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 913689.33 738.63 05-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 1418976.17 994.75 08-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 7504712.14 1070.43 16-SEP-18:04 0.00 0.00 0.00 0.00 0.00
October 98095025.33 1201.89 27-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.811666E+09 2902.52 25-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.136710E+10 2943.06 31-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.643326E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 913689.33 738.63   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.167590E+10 2953.30   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.195754E+10 2938.45 14-JAN-09:01 0.00 0.00 0.00 0.00 0.00
February 0.173859E+10 2938.16 07-FEB-09:01 0.00 0.00 0.00 0.00 0.00
March 0.880532E+09 2900.33 22-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.378329E+09 2821.03 03-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 37643496.51 1068.31 01-MAY-18:04 0.00 0.00 0.00 0.00 0.00
June 416470.07 540.59 06-JUN-21:55 0.00 0.00 0.00 0.00 0.00
July 475255.38 742.85 09-JUL-06:54 0.00 0.00 0.00 0.00 0.00
August 447285.41 571.30 08-AUG-08:54 0.00 0.00 0.00 0.00 0.00
September 7234513.83 1259.03 24-SEP-15:04 0.00 0.00 0.00 0.00 0.00
October 0.163051E+09 2808.11 29-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.103442E+10 2899.29 24-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.167110E+10 2928.25 31-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.786978E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 416470.07 540.59   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.195754E+10 2938.45   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.486231E+10 13974.02 14-JAN-16:02 0.00 0.00 0.00 0.00 0.00
February 0.348266E+10 13913.82 06-FEB-19:02 0.00 0.00 0.00 0.00 0.00
March 0.181516E+10 13663.23 16-MAR-15:01 0.00 0.00 0.00 0.00 0.00
April 0.870112E+09 13266.51 21-APR-15:01 0.00 0.00 0.00 0.00 0.00
May 63483967.92 5210.73 03-MAY-15:05 0.00 0.00 0.00 0.00 0.00
June 6344753.98 3970.55 04-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 3112264.06 4198.11 18-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 2063358.60 4403.75 08-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 7998177.28 4095.57 21-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 82354575.41 4794.96 28-OCT-18:05 0.00 0.00 0.00 0.00 0.00
November 0.159491E+10 13439.29 25-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.351388E+10 13711.83 31-DEC-19:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.163044E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2063358.60 3970.55   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.486231E+10 13974.02   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: SWHSYS1 HPWH DXCOIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.539075E+11 0.539075E+11 37176.38 31-JAN-04:20 37176.38 0.00
February 0.00 0.00 0.477317E+11 0.477317E+11 34239.09 09-FEB-00:07 34239.09 0.00
March 0.00 0.00 0.558717E+11 0.558717E+11 50111.17 31-MAR-23:20 50111.17 0.00
April 0.00 0.00 0.531563E+11 0.531535E+11 50127.34 01-APR-05:15 50127.34 0.00
May 0.00 0.00 0.524041E+11 0.492629E+11 63500.04 31-MAY-23:07 45048.15 0.00
June 0.00 0.00 0.483817E+11 0.343300E+11 63461.80 01-JUN-04:07 44617.23 0.00
July 0.00 0.00 0.477735E+11 0.272215E+11 67440.67 01-JUL-05:17 38225.13 0.00
August 0.00 0.00 0.467088E+11 0.337453E+11 64949.78 31-AUG-05:13 46904.66 0.00
September 0.00 0.00 0.457848E+11 0.373479E+11 59809.37 30-SEP-06:30 48586.49 0.00
October 0.00 0.00 0.491227E+11 0.444038E+11 53535.79 31-OCT-06:15 48189.26 0.00
November 0.00 0.00 0.490343E+11 0.490343E+11 44828.99 30-NOV-06:04 44828.99 0.00
December 0.00 0.00 0.523333E+11 0.523333E+11 39321.35 31-DEC-20:50 39321.35 0.00
                 
Annual Sum or Average 0.00 0.00 0.602210E+12 0.538343E+12       0.00
Minimum of Months 0.00 0.00 0.457848E+11 0.272215E+11 34239.09   34239.09 0.00
Maximum of Months 0.00 0.00 0.558717E+11 0.558717E+11 67440.67   50127.34 0.00



Table of Contents

Report: CoilReportMonthly

For: SWHSYSLAUNDRY HPWH DXCOIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.372806E+11 0.372806E+11 47038.12 31-JAN-23:00 47038.12 0.00
February 0.00 0.00 0.311321E+11 0.311321E+11 43318.83 09-FEB-22:50 43318.83 0.00
March 0.00 0.00 0.433818E+11 0.433818E+11 54906.72 01-MAR-17:10 54906.72 0.00
April 0.00 0.00 0.482845E+11 0.482839E+11 63437.10 01-APR-17:50 63437.10 0.00
May 0.00 0.00 0.557002E+11 0.523841E+11 71032.16 01-MAY-16:10 66874.12 0.00
June 0.00 0.00 0.609469E+11 0.432314E+11 80321.66 01-JUN-20:45 56406.18 0.00
July 0.00 0.00 0.671350E+11 0.382329E+11 85359.86 01-JUL-16:20 48441.47 0.00
August 0.00 0.00 0.648274E+11 0.468133E+11 82205.79 31-AUG-18:50 58848.41 0.00
September 0.00 0.00 0.575974E+11 0.469975E+11 75696.82 30-SEP-16:05 61493.17 0.00
October 0.00 0.00 0.531736E+11 0.480779E+11 67752.99 31-OCT-21:10 60987.13 0.00
November 0.00 0.00 0.431527E+11 0.431527E+11 56728.13 30-NOV-17:20 56728.13 0.00
December 0.00 0.00 0.392597E+11 0.392597E+11 49754.16 31-DEC-18:12 49754.16 0.00
                 
Annual Sum or Average 0.00 0.00 0.601872E+12 0.518228E+12       0.00
Minimum of Months 0.00 0.00 0.311321E+11 0.311321E+11 43318.83   43318.83 0.00
Maximum of Months 0.00 0.00 0.671350E+11 0.523841E+11 85359.86   66874.12 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00
March 0.00 0.00 0.329359E+10 0.325708E+10 128470.33 27-MAR-16:00 128470.33 0.02
April 0.00 0.00 0.339278E+11 0.336599E+11 208088.51 09-APR-10:50 137084.88 0.14
May 0.00 0.00 0.125500E+12 0.107682E+12 297829.63 31-MAY-17:17 159214.44 0.38
June 0.00 0.00 0.520638E+12 0.300692E+12 504405.71 24-JUN-17:17 171855.56 0.91
July 0.00 0.00 0.826657E+12 0.431939E+12 528638.08 05-JUL-19:10 191496.70 1.00
August 0.00 0.00 0.668323E+12 0.425152E+12 586630.65 11-AUG-21:53 203311.83 0.97
September 0.00 0.00 0.360538E+12 0.242148E+12 536215.48 13-SEP-21:00 206325.43 0.79
October 0.00 0.00 0.123645E+12 0.787861E+11 278389.69 05-OCT-19:10 113001.73 0.41
November 0.00 0.00 0.332701E+10 0.303487E+10 62625.09 04-NOV-10:45 62625.09 0.02
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.266585E+13 0.162635E+13       0.39
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.826657E+12 0.431939E+12 586630.65   206325.43 1.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00
March 0.00 0.00 0.274237E+09 0.236684E+09 19369.32 27-MAR-13:00 12687.17 0.01
April 0.00 0.00 0.217150E+10 0.212913E+10 20182.20 09-APR-10:00 13725.70 0.10
May 0.00 0.00 0.903150E+10 0.753219E+10 31077.44 31-MAY-17:00 16337.38 0.28
June 0.00 0.00 0.428359E+11 0.239619E+11 46753.17 24-JUN-18:07 16313.96 0.72
July 0.00 0.00 0.583701E+11 0.326037E+11 47889.79 28-JUL-08:03 17975.02 0.79
August 0.00 0.00 0.471787E+11 0.307582E+11 42812.08 10-AUG-21:51 17181.45 0.79
September 0.00 0.00 0.291741E+11 0.191404E+11 46252.66 14-SEP-08:10 16585.46 0.62
October 0.00 0.00 0.100475E+11 0.576025E+10 30632.72 03-OCT-15:02 16954.47 0.30
November 0.00 0.00 0.209566E+09 0.180115E+09 7314.01 10-NOV-08:00 2644.12 0.01
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.199293E+12 0.122303E+12       0.30
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.583701E+11 0.326037E+11 47889.79   17975.02 0.79



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 64008021.92 45918715.32 12307.22 20-JAN-16:02 12307.22 0.01
February 0.00 0.00 0.153521E+09 0.131983E+09 12306.64 17-FEB-16:02 12306.64 0.02
March 0.00 0.00 0.920522E+09 0.695827E+09 14298.29 27-MAR-15:02 11292.68 0.14
April 0.00 0.00 0.227997E+10 0.153042E+10 13399.76 09-APR-08:62 10894.59 0.37
May 0.00 0.00 0.482789E+10 0.312487E+10 15010.67 19-MAY-18:02 10061.98 0.72
June 0.00 0.00 0.893195E+10 0.549767E+10 17147.21 27-JUN-08:62 10204.52 0.92
July 0.00 0.00 0.108408E+11 0.690828E+10 17238.94 28-JUL-08:61 10214.93 0.96
August 0.00 0.00 0.115105E+11 0.783713E+10 16550.83 06-AUG-08:62 10341.07 0.96
September 0.00 0.00 0.707456E+10 0.435295E+10 18429.45 22-SEP-18:02 9154.04 0.88
October 0.00 0.00 0.467878E+10 0.289275E+10 15358.74 06-OCT-08:62 9649.39 0.63
November 0.00 0.00 0.426031E+09 0.239759E+09 13153.85 10-NOV-16:02 10538.33 0.14
December 0.00 0.00 78715320.67 68580932.23 12310.17 17-DEC-16:02 12310.17 0.01
                 
Annual Sum or Average 0.00 0.00 0.517873E+11 0.333261E+11       0.48
Minimum of Months 0.00 0.00 64008021.92 45918715.32 12306.64   9154.04 0.01
Maximum of Months 0.00 0.00 0.115105E+11 0.783713E+10 18429.45   12310.17 0.96



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 15174271.23 10870415.63 10928.86 20-JAN-16:02 10928.86 0.00
February 0.00 0.00 32967570.26 27810893.17 11201.20 22-FEB-16:02 11201.20 0.00
March 0.00 0.00 0.379900E+09 0.292778E+09 14102.19 27-MAR-15:02 10701.52 0.07
April 0.00 0.00 0.131100E+10 0.812394E+09 13628.12 27-APR-18:21 12805.30 0.27
May 0.00 0.00 0.329105E+10 0.200994E+10 16073.67 31-MAY-08:51 11806.82 0.56
June 0.00 0.00 0.641567E+10 0.410867E+10 18083.87 27-JUN-08:51 10223.64 0.64
July 0.00 0.00 0.933381E+10 0.612687E+10 18608.18 23-JUL-08:21 10405.85 0.79
August 0.00 0.00 0.942814E+10 0.642379E+10 18677.76 12-AUG-08:61 11545.91 0.80
September 0.00 0.00 0.416171E+10 0.240021E+10 17218.38 14-SEP-08:51 9709.84 0.59
October 0.00 0.00 0.188223E+10 0.969775E+09 15041.74 05-OCT-21:51 10440.72 0.38
November 0.00 0.00 82711244.94 49508264.34 12961.75 10-NOV-16:02 9469.45 0.03
December 0.00 0.00 12636344.30 10178339.62 10980.93 17-DEC-16:02 10980.93 0.00
                 
Annual Sum or Average 0.00 0.00 0.363470E+11 0.232428E+11       0.35
Minimum of Months 0.00 0.00 12636344.30 10178339.62 10928.86   9469.45 0.00
Maximum of Months 0.00 0.00 0.942814E+10 0.642379E+10 18677.76   12805.30 0.80



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 29177817.74 29177817.74 6195.67 31-JAN-15:00 6195.67 0.00
February 0.00 0.00 0.239358E+10 0.239358E+10 27817.14 20-FEB-13:30 27817.14 0.00
March 0.00 0.00 0.697116E+10 0.569826E+10 33958.32 28-MAR-12:30 27345.55 0.09
April 0.00 0.00 0.142742E+11 0.897074E+10 44584.17 07-APR-13:15 40384.85 0.37
May 0.00 0.00 0.246644E+11 0.120522E+11 34779.66 30-MAY-12:30 26956.32 0.80
June 0.00 0.00 0.391544E+11 0.193201E+11 36425.96 19-JUN-12:40 28945.92 0.99
July 0.00 0.00 0.517813E+11 0.282616E+11 38221.24 08-JUL-12:00 31235.16 1.00
August 0.00 0.00 0.609320E+11 0.384272E+11 46899.33 30-AUG-13:00 35393.93 1.00
September 0.00 0.00 0.462527E+11 0.280961E+11 51373.91 28-SEP-12:40 42013.46 0.97
October 0.00 0.00 0.452908E+11 0.340191E+11 54376.20 04-OCT-12:10 45079.08 0.63
November 0.00 0.00 0.105538E+11 0.833222E+10 46035.96 02-NOV-12:50 46035.96 0.17
December 0.00 0.00 0.358407E+10 0.358407E+10 31277.11 17-DEC-13:40 31277.11 0.00
                 
Annual Sum or Average 0.00 0.00 0.305881E+12 0.189184E+12       0.50
Minimum of Months 0.00 0.00 29177817.74 29177817.74 6195.67   6195.67 0.00
Maximum of Months 0.00 0.00 0.609320E+11 0.384272E+11 54376.20   46035.96 1.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.407319E+09 0.219243E+09 63536.31 24-JAN-09:02 52755.98 0.03
February 0.00 0.00 0.223803E+09 0.190838E+09 59136.83 18-FEB-09:02 59136.83 0.01
March 0.00 0.00 0.379511E+10 0.256748E+10 69818.68 27-MAR-15:02 59401.13 0.16
April 0.00 0.00 0.144910E+11 0.942517E+10 71865.85 08-APR-15:02 64851.03 0.42
May 0.00 0.00 0.316013E+11 0.223926E+11 82026.19 31-MAY-21:51 63435.83 0.53
June 0.00 0.00 0.455839E+11 0.316170E+11 99538.92 25-JUN-07:51 61015.25 0.57
July 0.00 0.00 0.634555E+11 0.438715E+11 102657.74 23-JUL-08:21 53682.78 0.75
August 0.00 0.00 0.575539E+11 0.397391E+11 101738.43 12-AUG-08:61 59840.06 0.73
September 0.00 0.00 0.334056E+11 0.221502E+11 94392.99 14-SEP-08:51 51703.33 0.52
October 0.00 0.00 0.183255E+11 0.117839E+11 81501.38 05-OCT-21:51 56324.84 0.34
November 0.00 0.00 0.491074E+10 0.291000E+10 67277.22 10-NOV-09:13 44922.12 0.24
December 0.00 0.00 0.371310E+09 0.282932E+09 58947.01 10-DEC-09:02 58947.01 0.02
                 
Annual Sum or Average 0.00 0.00 0.274125E+12 0.187150E+12       0.36
Minimum of Months 0.00 0.00 0.223803E+09 0.190838E+09 58947.01   44922.12 0.01
Maximum of Months 0.00 0.00 0.634555E+11 0.438715E+11 102657.74   64851.03 0.75



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 92860610.84 69566319.03 10305.71 20-JAN-09:02 10305.71 0.01
February 0.00 0.00 0.153828E+09 0.129050E+09 11262.09 25-FEB-09:01 11262.09 0.02
March 0.00 0.00 0.784220E+09 0.569701E+09 13234.73 27-MAR-15:02 9941.82 0.15
April 0.00 0.00 0.231482E+10 0.150239E+10 12140.13 27-APR-15:02 10770.49 0.41
May 0.00 0.00 0.499073E+10 0.326818E+10 13605.28 05-MAY-15:01 9772.45 0.74
June 0.00 0.00 0.842043E+10 0.507595E+10 15399.59 18-JUN-08:62 9238.90 0.94
July 0.00 0.00 0.107165E+11 0.682144E+10 15228.46 28-JUL-08:61 9692.16 0.97
August 0.00 0.00 0.114162E+11 0.783926E+10 15091.37 06-AUG-08:62 9503.93 0.98
September 0.00 0.00 0.714050E+10 0.446805E+10 16921.09 22-SEP-18:02 8351.67 0.90
October 0.00 0.00 0.449384E+10 0.271379E+10 14045.14 06-OCT-08:62 8782.75 0.65
November 0.00 0.00 0.613449E+09 0.375009E+09 11870.23 11-NOV-09:02 10279.00 0.17
December 0.00 0.00 0.166047E+09 0.122841E+09 10569.25 02-DEC-09:01 10569.25 0.03
                 
Annual Sum or Average 0.00 0.00 0.513035E+11 0.329552E+11       0.50
Minimum of Months 0.00 0.00 92860610.84 69566319.03 10305.71   8351.67 0.01
Maximum of Months 0.00 0.00 0.114162E+11 0.783926E+10 16921.09   11262.09 0.98



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 9629715.39 5133068.24 5418.67 19-JAN-09:01 4398.46 0.00
February 0.00 0.00 27497241.19 20559364.30 10327.48 25-FEB-09:01 10327.48 0.01
March 0.00 0.00 0.288949E+09 0.203514E+09 12442.37 27-MAR-15:02 9044.35 0.06
April 0.00 0.00 0.141435E+10 0.866272E+09 13000.01 08-APR-08:51 12369.66 0.32
May 0.00 0.00 0.357320E+10 0.227947E+10 16701.56 31-MAY-08:32 13530.20 0.58
June 0.00 0.00 0.610197E+10 0.380820E+10 17438.32 20-JUN-08:62 13258.60 0.65
July 0.00 0.00 0.913634E+10 0.589054E+10 17651.73 01-JUL-08:32 13001.10 0.80
August 0.00 0.00 0.921035E+10 0.611833E+10 17249.09 12-AUG-08:61 11132.00 0.82
September 0.00 0.00 0.430448E+10 0.252589E+10 17141.85 06-SEP-08:32 13274.11 0.62
October 0.00 0.00 0.185074E+10 0.100177E+10 14800.23 25-OCT-08:51 10877.23 0.40
November 0.00 0.00 0.176482E+09 95178337.33 11285.76 11-NOV-09:02 9640.34 0.06
December 0.00 0.00 18289933.38 10622781.76 8520.73 20-DEC-09:01 8520.73 0.01
                 
Annual Sum or Average 0.00 0.00 0.361123E+11 0.228255E+11       0.36
Minimum of Months 0.00 0.00 9629715.39 5133068.24 5418.67   4398.46 0.00
Maximum of Months 0.00 0.00 0.921035E+10 0.611833E+10 17651.73   13530.20 0.82



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 15267966.29 10524263.99 3245.18 20-JAN-16:02 3245.18 0.01
February 0.00 0.00 36973141.25 31154800.13 3245.07 17-FEB-16:02 3245.07 0.02
March 0.00 0.00 0.231152E+09 0.175484E+09 3761.88 27-MAR-15:02 2981.90 0.12
April 0.00 0.00 0.575878E+09 0.398531E+09 3678.56 09-APR-08:62 2672.88 0.34
May 0.00 0.00 0.122022E+10 0.820018E+09 3981.73 19-MAY-18:02 2580.04 0.67
June 0.00 0.00 0.228670E+10 0.140240E+10 4726.62 27-JUN-08:62 2561.80 0.92
July 0.00 0.00 0.282333E+10 0.178369E+10 4750.67 28-JUL-08:61 2564.28 0.96
August 0.00 0.00 0.296197E+10 0.200274E+10 4647.81 06-AUG-08:62 2550.38 0.96
September 0.00 0.00 0.173283E+10 0.106337E+10 5054.60 22-SEP-18:02 2283.36 0.85
October 0.00 0.00 0.106882E+10 0.664043E+09 4149.75 25-OCT-08:62 2449.77 0.57
November 0.00 0.00 81654892.82 47622023.48 3522.38 10-NOV-16:02 2681.67 0.09
December 0.00 0.00 16087127.78 14539145.18 3243.31 02-DEC-16:01 3243.31 0.00
                 
Annual Sum or Average 0.00 0.00 0.130509E+11 0.841412E+10       0.46
Minimum of Months 0.00 0.00 15267966.29 10524263.99 3243.31   2283.36 0.00
Maximum of Months 0.00 0.00 0.296197E+10 0.200274E+10 5054.60   3245.18 0.96



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 2555629.22 1588351.87 2244.60 17-JAN-16:02 2244.60 0.00
February 0.00 0.00 5143422.57 4091140.97 2316.43 24-FEB-16:01 2316.43 0.00
March 0.00 0.00 87044921.26 65905348.16 3789.37 27-MAR-15:02 2797.21 0.06
April 0.00 0.00 0.328305E+09 0.207637E+09 3610.91 27-APR-18:21 3479.05 0.25
May 0.00 0.00 0.852509E+09 0.536001E+09 4326.89 31-MAY-08:51 3173.90 0.53
June 0.00 0.00 0.171569E+10 0.109970E+10 4961.60 25-JUN-07:51 2852.94 0.64
July 0.00 0.00 0.247700E+10 0.162321E+10 5114.77 23-JUL-08:21 2561.12 0.80
August 0.00 0.00 0.246169E+10 0.166899E+10 5104.57 12-AUG-08:61 2891.57 0.80
September 0.00 0.00 0.102905E+10 0.593613E+09 4714.01 14-SEP-08:51 2424.51 0.56
October 0.00 0.00 0.389659E+09 0.195526E+09 4080.11 05-OCT-21:51 2696.74 0.32
November 0.00 0.00 13466654.68 7898471.69 3418.18 10-NOV-16:02 2387.46 0.02
December 0.00 0.00 1905516.15 1274314.01 1764.94 17-DEC-16:02 1594.27 0.00
                 
Annual Sum or Average 0.00 0.00 0.936401E+10 0.600543E+10       0.33
Minimum of Months 0.00 0.00 1905516.15 1274314.01 1764.94   1594.27 0.00
Maximum of Months 0.00 0.00 0.247700E+10 0.166899E+10 5114.77   3479.05 0.80



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.102791E+10 0.889214E+09 15173.93 10-JAN-16:02 15173.93 0.06
February 0.00 0.00 0.152240E+10 0.137651E+10 15174.68 10-FEB-16:01 15174.68 0.07
March 0.00 0.00 0.275534E+10 0.220136E+10 16116.01 27-MAR-15:02 14785.02 0.25
April 0.00 0.00 0.389545E+10 0.268449E+10 16734.02 30-APR-15:02 11749.35 0.44
May 0.00 0.00 0.614743E+10 0.387626E+10 18740.17 31-MAY-18:02 13728.65 0.72
June 0.00 0.00 0.108056E+11 0.613684E+10 22989.61 27-JUN-08:62 11475.27 0.91
July 0.00 0.00 0.142831E+11 0.885453E+10 22859.02 28-JUL-08:61 11638.53 0.96
August 0.00 0.00 0.156806E+11 0.104904E+11 21778.31 06-AUG-08:62 11944.93 0.96
September 0.00 0.00 0.114172E+11 0.740963E+10 24359.34 22-SEP-18:02 10303.84 0.89
October 0.00 0.00 0.100800E+11 0.727584E+10 19609.33 05-OCT-18:02 12766.53 0.68
November 0.00 0.00 0.258320E+10 0.187988E+10 16082.27 11-NOV-16:02 13838.44 0.32
December 0.00 0.00 0.172839E+10 0.153852E+10 15244.06 25-DEC-16:02 13188.10 0.09
                 
Annual Sum or Average 0.00 0.00 0.819266E+11 0.546135E+11       0.53
Minimum of Months 0.00 0.00 0.102791E+10 0.889214E+09 15173.93   10303.84 0.06
Maximum of Months 0.00 0.00 0.156806E+11 0.104904E+11 24359.34   15174.68 0.96



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 48935.71 228682.20 02-JAN-09:01
February 0.00 0.00 01-FEB-00:03 46370.07 236148.43 06-FEB-09:01
March 0.00 0.00 01-MAR-00:03 22396.61 173918.13 17-MAR-08:61
April 0.00 0.00 01-APR-00:10 26164.04 157549.42 02-APR-18:05
May 0.00 0.00 01-MAY-00:05 10782.44 99685.10 03-MAY-15:05
June 0.00 0.00 01-JUN-00:05 272.67 24434.81 06-JUN-15:07
July 0.00 0.00 01-JUL-00:10 36.45 26237.59 18-JUL-08:05
August 0.00 0.00 01-AUG-00:05 113.50 25162.84 25-AUG-21:57
September 0.00 0.00 01-SEP-00:05 2758.57 72685.64 24-SEP-05:50
October 0.00 0.00 01-OCT-00:10 16556.33 133298.01 28-OCT-18:05
November 0.00 0.00 01-NOV-00:05 34324.70 159079.27 28-NOV-16:01
December 0.00 0.00 01-DEC-00:03 29981.33 186335.52 31-DEC-19:01
             
Annual Sum or Average 0.00     19717.36    
Minimum of Months 0.00 0.00   36.45 24434.81  
Maximum of Months 0.00 0.00   48935.71 236148.43  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 1422.53 45523.04 17-JAN-16:03 0.00 0.00 01-JAN-00:03
February 3116.56 60873.42 20-FEB-16:02 0.00 0.00 01-FEB-00:03
March 9686.73 239121.02 27-MAR-15:03 0.00 0.00 01-MAR-00:03
April 33180.62 362407.34 07-APR-15:05 0.00 0.00 01-APR-00:10
May 84986.45 411007.08 31-MAY-15:25 0.00 0.00 01-MAY-00:05
June 271920.56 644200.53 23-JUN-21:52 0.00 0.00 01-JUN-00:05
July 400406.82 662059.20 20-JUL-18:03 0.00 0.00 01-JUL-00:10
August 339461.76 758401.44 11-AUG-21:51 0.00 0.00 01-AUG-00:05
September 199860.10 636823.99 07-SEP-20:00 0.00 0.00 01-SEP-00:05
October 87120.02 455770.28 05-OCT-15:05 0.00 0.00 01-OCT-00:10
November 11369.33 177250.37 04-NOV-15:03 0.00 0.00 01-NOV-00:05
December 3413.64 46572.92 18-DEC-11:00 0.00 0.00 01-DEC-00:03
             
Annual Sum or Average 121366.08     0.00    
Minimum of Months 1422.53 45523.04   0.00 0.00  
Maximum of Months 400406.82 758401.44   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 27303.87 57697.32 30-JAN-07:40
February 0.00 0.00 01-FEB-00:03 27587.31 57701.11 09-FEB-07:20
March 0.00 0.00 01-MAR-00:03 26965.39 57220.21 01-MAR-08:00
April 0.00 0.00 01-APR-00:10 25576.07 54800.13 03-APR-07:00
May 0.00 0.00 01-MAY-00:05 23821.86 51556.85 01-MAY-06:40
June 0.00 0.00 01-JUN-00:05 22155.53 47702.70 01-JUN-06:20
July 0.00 0.00 01-JUL-00:10 20997.59 44549.33 03-JUL-06:35
August 0.00 0.00 01-AUG-00:05 20721.78 47335.41 25-AUG-17:01
September 0.00 0.00 01-SEP-00:05 21342.56 45564.34 29-SEP-07:00
October 0.00 0.00 01-OCT-00:10 22717.27 49172.57 31-OCT-06:40
November 0.00 0.00 01-NOV-00:05 24481.02 52946.39 30-NOV-08:00
December 0.00 0.00 01-DEC-00:03 26154.91 55882.63 29-DEC-08:00
             
Annual Sum or Average 0.00     24132.23    
Minimum of Months 0.00 0.00   20721.78 44549.33  
Maximum of Months 0.00 0.00   27587.31 57701.11  



Table of Contents

Report: FanReportMonthly

For: SWHSYS1 HPWH FAN

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.827608E+09 0.07 553.22 01-JAN-00:15 0.10
February 0.790848E+09 0.07 553.22 01-FEB-00:07 0.10
March 0.741910E+09 0.06 553.22 01-MAR-00:20 0.10
April 0.622214E+09 0.06 553.22 01-APR-05:15 0.10
May 0.554681E+09 0.06 553.22 01-MAY-05:13 0.10
June 0.458187E+09 0.05 553.22 01-JUN-04:07 0.10
July 0.431644E+09 0.05 553.22 01-JUL-05:17 0.10
August 0.435641E+09 0.05 553.22 01-AUG-05:13 0.10
September 0.459364E+09 0.05 553.22 01-SEP-04:07 0.10
October 0.546352E+09 0.06 553.22 01-OCT-05:07 0.10
November 0.641047E+09 0.06 553.22 01-NOV-05:13 0.10
December 0.767110E+09 0.06 553.22 01-DEC-00:07 0.10
           
Annual Sum or Average 0.727661E+10 0.06      
Minimum of Months 0.431644E+09 0.05 553.22   0.10
Maximum of Months 0.827608E+09 0.07 553.22   0.10



Table of Contents

Report: FanReportMonthly

For: SWHSYSLAUNDRY HPWH FAN

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.559241E+09 0.06 700.51 01-JAN-17:10 0.10
February 0.506099E+09 0.06 700.51 01-FEB-17:10 0.10
March 0.558168E+09 0.06 700.51 01-MAR-17:10 0.10
April 0.539146E+09 0.06 700.51 01-APR-16:05 0.10
May 0.556149E+09 0.05 700.51 01-MAY-16:10 0.10
June 0.537289E+09 0.05 700.51 01-JUN-16:10 0.10
July 0.555126E+09 0.05 700.51 01-JUL-16:10 0.10
August 0.554899E+09 0.05 700.51 01-AUG-16:10 0.10
September 0.537884E+09 0.05 700.51 01-SEP-16:10 0.10
October 0.556495E+09 0.05 700.51 01-OCT-16:10 0.10
November 0.539533E+09 0.06 700.51 01-NOV-16:10 0.10
December 0.558885E+09 0.06 700.51 01-DEC-17:10 0.10
           
Annual Sum or Average 0.655891E+10 0.06      
Minimum of Months 0.506099E+09 0.05 700.51   0.10
Maximum of Months 0.559241E+09 0.06 700.51   0.10



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.271000E+10 0.69 1299.30 01-JAN-16:01 0.88
February 0.244774E+10 0.69 1299.30 01-FEB-09:01 0.88
March 0.271000E+10 0.69 1299.30 01-MAR-09:02 0.88
April 0.262258E+10 0.69 1299.30 01-APR-08:62 0.88
May 0.271000E+10 0.69 1299.30 01-MAY-15:02 0.88
June 0.262258E+10 0.69 1299.30 01-JUN-08:51 0.87
July 0.271000E+10 0.69 1299.30 01-JUL-08:51 0.87
August 0.271000E+10 0.69 1299.30 01-AUG-06:51 0.87
September 0.262258E+10 0.69 1299.30 01-SEP-08:61 0.87
October 0.271000E+10 0.69 1299.30 01-OCT-08:62 0.87
November 0.262258E+10 0.69 1299.30 01-NOV-15:02 0.88
December 0.271000E+10 0.69 1299.30 01-DEC-16:01 0.88
           
Annual Sum or Average 0.319080E+11 0.69      
Minimum of Months 0.244774E+10 0.69 1299.30   0.87
Maximum of Months 0.271000E+10 0.69 1299.30   0.88



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.341031E+11 0.83 18321.79 23-JAN-21:10 1.03
February 0.308165E+11 0.84 17948.16 23-FEB-21:10 1.02
March 0.352063E+11 0.85 20149.35 03-MAR-22:10 1.09
April 0.349857E+11 0.86 25035.39 07-APR-21:10 1.24
May 0.375417E+11 0.88 26355.73 31-MAY-21:10 1.27
June 0.384000E+11 0.90 27388.09 20-JUN-21:10 1.30
July 0.408288E+11 0.91 28078.32 10-JUL-21:10 1.32
August 0.416378E+11 0.92 29946.82 24-AUG-19:50 1.39
September 0.380183E+11 0.90 29121.48 07-SEP-21:10 1.35
October 0.378130E+11 0.88 28205.55 05-OCT-21:10 1.33
November 0.343798E+11 0.85 22649.43 03-NOV-21:10 1.17
December 0.344091E+11 0.84 18477.04 04-DEC-21:10 1.03
           
Annual Sum or Average 0.438140E+12 0.87      
Minimum of Months 0.308165E+11 0.83 17948.16   1.02
Maximum of Months 0.416378E+11 0.92 29946.82   1.39



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205205E+09 0.27 76.61 01-JAN-00:03 0.27
February 0.185347E+09 0.27 76.61 01-FEB-00:03 0.27
March 0.205205E+09 0.27 76.61 01-MAR-00:03 0.27
April 0.198586E+09 0.27 76.61 01-APR-00:10 0.26
May 0.205205E+09 0.26 76.61 01-MAY-00:05 0.26
June 0.198586E+09 0.26 76.61 01-JUN-00:05 0.26
July 0.205205E+09 0.26 76.61 01-JUL-00:10 0.26
August 0.205205E+09 0.26 76.61 01-AUG-00:05 0.26
September 0.198586E+09 0.26 76.61 01-SEP-00:05 0.26
October 0.205205E+09 0.26 76.61 01-OCT-00:10 0.26
November 0.198586E+09 0.27 76.61 01-NOV-00:05 0.27
December 0.205205E+09 0.27 76.61 01-DEC-00:03 0.27
           
Annual Sum or Average 0.241613E+10 0.27      
Minimum of Months 0.185347E+09 0.26 76.61   0.26
Maximum of Months 0.205205E+09 0.27 76.61   0.27



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:03 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:03 0.00
February 0.00 -0.0 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:05 0.00
June 0.00 -0.0 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:05 0.00
September 0.00 -0.0 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 -0.0 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:03 0.00
February 0.00 -0.0 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 -0.0 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 -0.0 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116283E+10 0.19 612.92 01-JAN-07:03 0.27
February 0.105030E+10 0.19 612.92 01-FEB-07:05 0.27
March 0.116283E+10 0.19 612.92 01-MAR-07:05 0.27
April 0.112532E+10 0.19 612.92 01-APR-06:05 0.27
May 0.116283E+10 0.19 612.92 01-MAY-06:05 0.27
June 0.112532E+10 0.19 612.92 01-JUN-06:05 0.26
July 0.116283E+10 0.19 612.92 01-JUL-06:05 0.26
August 0.116283E+10 0.19 612.92 01-AUG-06:05 0.26
September 0.112532E+10 0.19 612.92 01-SEP-06:05 0.26
October 0.116283E+10 0.19 612.92 01-OCT-06:05 0.26
November 0.112532E+10 0.19 612.92 01-NOV-06:05 0.27
December 0.116283E+10 0.19 612.92 01-DEC-07:05 0.27
           
Annual Sum or Average 0.136914E+11 0.19      
Minimum of Months 0.105030E+10 0.19 612.92   0.26
Maximum of Months 0.116283E+10 0.19 612.92   0.27



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.245600E+09 0.44 736.76 01-JAN-09:01 0.58
February 0.209393E+09 0.44 736.76 01-FEB-09:01 0.57
March 0.178282E+09 0.44 736.76 01-MAR-16:02 0.57
April 0.197947E+09 0.46 736.76 01-APR-15:02 0.57
May 0.294300E+09 0.50 736.76 01-MAY-15:02 0.57
June 0.444007E+09 0.54 736.76 01-JUN-08:62 0.57
July 0.511736E+09 0.55 736.76 01-JUL-08:62 0.57
August 0.565953E+09 0.55 736.76 01-AUG-08:62 0.57
September 0.367135E+09 0.52 736.76 01-SEP-08:61 0.57
October 0.274043E+09 0.50 736.76 01-OCT-08:62 0.57
November 0.159119E+09 0.42 736.76 01-NOV-15:02 0.57
December 0.211879E+09 0.43 736.76 01-DEC-19:01 0.57
           
Annual Sum or Average 0.365939E+10 0.48      
Minimum of Months 0.159119E+09 0.42 736.76   0.57
Maximum of Months 0.565953E+09 0.55 736.76   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.272248E+09 0.46 713.94 01-JAN-09:01 0.58
February 0.241185E+09 0.46 713.94 01-FEB-09:01 0.57
March 0.166743E+09 0.41 713.94 01-MAR-09:02 0.57
April 0.145987E+09 0.41 713.94 01-APR-15:02 0.57
May 0.200184E+09 0.39 713.94 01-MAY-15:02 0.57
June 0.314027E+09 0.37 713.94 01-JUN-08:51 0.57
July 0.444355E+09 0.46 713.94 01-JUL-08:51 0.57
August 0.461852E+09 0.46 713.94 01-AUG-06:51 0.57
September 0.211768E+09 0.35 713.94 01-SEP-08:61 0.57
October 0.130825E+09 0.37 713.94 01-OCT-08:62 0.57
November 0.163869E+09 0.41 713.94 01-NOV-15:02 0.57
December 0.241925E+09 0.44 713.94 01-DEC-09:01 0.57
           
Annual Sum or Average 0.299497E+10 0.41      
Minimum of Months 0.130825E+09 0.35 713.94   0.57
Maximum of Months 0.461852E+09 0.46 713.94   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 1920864.48 0.00 377.53 31-JAN-15:00 0.58
February 0.121562E+09 0.06 1094.23 20-FEB-13:30 0.58
March 0.339037E+09 0.14 1266.96 29-MAR-13:00 0.57
April 0.668729E+09 0.28 2116.07 08-APR-13:10 0.57
May 0.113015E+10 0.46 1166.07 30-MAY-12:50 0.57
June 0.157127E+10 0.57 1212.58 19-JUN-13:20 0.57
July 0.192357E+10 0.57 1275.42 10-JUL-13:10 0.57
August 0.230199E+10 0.57 2173.19 22-AUG-12:40 0.57
September 0.190441E+10 0.55 2393.43 30-SEP-12:30 0.57
October 0.197140E+10 0.51 2454.85 10-OCT-12:30 0.57
November 0.515927E+09 0.19 2387.63 04-NOV-12:30 0.57
December 0.169675E+09 0.07 1198.74 17-DEC-13:40 0.58
           
Annual Sum or Average 0.126197E+11 0.33      
Minimum of Months 1920864.48 0.00 377.53   0.57
Maximum of Months 0.230199E+10 0.57 2454.85   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.100143E+10 0.41 3865.24 01-JAN-16:01 0.58
February 0.950093E+09 0.41 3865.24 01-FEB-16:02 0.58
March 0.646464E+09 0.40 3865.24 01-MAR-09:02 0.57
April 0.953795E+09 0.39 3865.24 01-APR-08:62 0.57
May 0.176034E+10 0.36 3865.24 01-MAY-08:62 0.57
June 0.230058E+10 0.34 3865.24 01-JUN-08:51 0.57
July 0.307623E+10 0.43 3865.24 01-JUL-08:51 0.57
August 0.279902E+10 0.42 3865.24 01-AUG-06:51 0.57
September 0.168309E+10 0.31 3865.24 01-SEP-08:61 0.57
October 0.101167E+10 0.33 3865.24 01-OCT-08:62 0.57
November 0.682674E+09 0.40 3865.24 01-NOV-08:62 0.57
December 0.817805E+09 0.41 3865.24 01-DEC-16:01 0.58
           
Annual Sum or Average 0.176832E+11 0.38      
Minimum of Months 0.646464E+09 0.31 3865.24   0.57
Maximum of Months 0.307623E+10 0.43 3865.24   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.230461E+09 0.43 673.49 01-JAN-16:01 0.58
February 0.191830E+09 0.43 673.49 01-FEB-19:01 0.57
March 0.167507E+09 0.44 673.49 01-MAR-09:02 0.57
April 0.192846E+09 0.47 673.49 01-APR-15:02 0.57
May 0.294513E+09 0.51 673.49 01-MAY-08:62 0.57
June 0.414201E+09 0.54 673.49 01-JUN-08:62 0.57
July 0.501898E+09 0.56 673.49 01-JUL-08:62 0.57
August 0.555527E+09 0.56 673.49 01-AUG-08:62 0.57
September 0.365929E+09 0.53 673.49 01-SEP-08:61 0.57
October 0.264315E+09 0.51 673.49 01-OCT-08:62 0.57
November 0.155113E+09 0.43 673.49 01-NOV-08:62 0.57
December 0.201574E+09 0.43 673.49 01-DEC-16:01 0.57
           
Annual Sum or Average 0.353571E+10 0.49      
Minimum of Months 0.155113E+09 0.43 673.49   0.57
Maximum of Months 0.555527E+09 0.56 673.49   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.254813E+09 0.46 654.14 01-JAN-09:01 0.58
February 0.222189E+09 0.46 654.14 01-FEB-09:01 0.57
March 0.156927E+09 0.41 654.14 01-MAR-09:02 0.57
April 0.147082E+09 0.42 654.14 01-APR-15:02 0.57
May 0.214961E+09 0.41 654.14 01-MAY-08:62 0.57
June 0.299977E+09 0.37 654.14 01-JUN-08:51 0.57
July 0.431591E+09 0.46 654.14 01-JUL-08:32 0.57
August 0.446685E+09 0.47 654.14 01-AUG-06:51 0.57
September 0.221667E+09 0.36 654.14 01-SEP-08:61 0.57
October 0.130007E+09 0.38 654.14 01-OCT-08:62 0.57
November 0.149518E+09 0.41 654.14 01-NOV-08:62 0.57
December 0.223041E+09 0.44 654.14 01-DEC-16:01 0.57
           
Annual Sum or Average 0.289846E+10 0.42      
Minimum of Months 0.130007E+09 0.36 654.14   0.57
Maximum of Months 0.446685E+09 0.47 654.14   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 75748514.92 0.46 194.39 01-JAN-09:01 0.58
February 65039537.12 0.46 194.39 01-FEB-09:01 0.57
March 53860486.30 0.44 194.39 01-MAR-16:02 0.57
April 55577492.82 0.46 194.39 01-APR-08:62 0.57
May 76314516.79 0.50 194.39 01-MAY-15:02 0.57
June 0.114657E+09 0.54 194.39 01-JUN-08:62 0.57
July 0.134633E+09 0.55 194.39 01-JUL-08:62 0.57
August 0.146985E+09 0.55 194.39 01-AUG-08:62 0.57
September 90943265.44 0.52 194.39 01-SEP-08:61 0.57
October 66895389.11 0.49 194.39 02-OCT-15:02 0.57
November 48203783.39 0.43 194.39 01-NOV-15:02 0.57
December 66181015.63 0.45 194.39 01-DEC-09:01 0.57
           
Annual Sum or Average 0.995038E+09 0.49      
Minimum of Months 48203783.39 0.43 194.39   0.57
Maximum of Months 0.146985E+09 0.55 194.39   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 83142102.36 0.50 187.99 01-JAN-09:01 0.58
February 73642227.93 0.49 187.99 01-FEB-09:01 0.57
March 50822708.26 0.42 187.99 01-MAR-09:02 0.57
April 42304720.94 0.41 187.99 01-APR-08:62 0.57
May 53213272.70 0.39 187.99 01-MAY-15:02 0.57
June 84953997.78 0.37 187.99 01-JUN-08:51 0.57
July 0.119343E+09 0.46 187.99 01-JUL-08:51 0.57
August 0.122006E+09 0.46 187.99 01-AUG-06:51 0.57
September 52873013.29 0.35 187.99 01-SEP-08:61 0.57
October 32871788.47 0.37 187.99 02-OCT-15:02 0.57
November 51971593.94 0.43 187.99 01-NOV-08:62 0.57
December 74698565.41 0.48 187.99 01-DEC-09:01 0.57
           
Annual Sum or Average 0.841843E+09 0.43      
Minimum of Months 32871788.47 0.35 187.99   0.57
Maximum of Months 0.122006E+09 0.50 187.99   0.58



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.296580E+09 0.45 901.48 01-JAN-16:01 0.58
February 0.265235E+09 0.47 901.48 01-FEB-16:02 0.57
March 0.280851E+09 0.47 901.48 01-MAR-09:02 0.57
April 0.282210E+09 0.47 901.48 02-APR-15:01 0.57
May 0.345603E+09 0.50 901.48 01-MAY-08:62 0.57
June 0.506200E+09 0.53 901.48 01-JUN-08:62 0.57
July 0.651013E+09 0.55 901.48 01-JUL-08:62 0.57
August 0.766842E+09 0.55 901.48 01-AUG-08:62 0.57
September 0.584261E+09 0.53 901.48 01-SEP-08:61 0.57
October 0.567294E+09 0.52 901.48 01-OCT-08:62 0.57
November 0.259108E+09 0.47 901.48 01-NOV-08:62 0.57
December 0.292774E+09 0.46 901.48 01-DEC-09:01 0.57
           
Annual Sum or Average 0.509797E+10 0.50      
Minimum of Months 0.259108E+09 0.45 901.48   0.57
Maximum of Months 0.766842E+09 0.55 901.48   0.58



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.767378E+09 0.697547E+09 726.13 02-JAN-09:01 660.05 660.05 35.16 1.16
February 0.665449E+09 0.604893E+09 740.07 06-FEB-09:01 672.72 672.72 35.32 1.21
March 0.397664E+09 0.361477E+09 580.36 17-MAR-08:61 527.55 527.55 29.93 0.81
April 0.338718E+09 0.307895E+09 579.66 02-APR-18:05 526.91 526.91 33.13 0.81
May 0.125037E+09 0.113658E+09 428.59 01-MAY-06:20 389.58 389.58 56.57 0.53
June 3123728.57 2839469.27 109.62 13-JUN-08:05 99.65 99.65 34.20 0.12
July 547384.05 497572.10 139.66 18-JUL-08:05 126.95 126.95 37.94 0.15
August 1680218.07 1527318.23 122.46 24-AUG-19:00 111.32 111.32 42.33 0.13
September 30175696.21 27429707.85 326.78 24-SEP-05:50 297.04 297.04 34.52 0.39
October 0.200966E+09 0.182678E+09 510.94 28-OCT-18:05 464.45 464.45 32.61 0.68
November 0.501439E+09 0.455808E+09 569.55 28-NOV-16:01 517.72 517.72 31.24 0.79
December 0.574348E+09 0.522083E+09 636.47 31-DEC-19:01 578.55 578.55 34.14 0.93
                 
Annual Sum or Average 0.360653E+10 0.327833E+10            
Minimum of Months 547384.05 497572.10 109.62   99.65 99.65 29.93 0.12
Maximum of Months 0.767378E+09 0.697547E+09 740.07   672.72 672.72 56.57 1.21



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 1012437.31 920305.51 40.57 17-JAN-16:03 36.88 36.88 8.40 3.16
February 3188575.69 2898415.30 88.70 20-FEB-16:02 80.63 80.63 8.40 4.85
March 17595512.99 15994321.31 225.24 27-MAR-15:03 204.74 204.74 7.77 7.77
April 86875652.07 78969967.73 752.23 07-APR-15:25 683.78 683.78 6.90 13.59
May 0.237539E+09 0.215923E+09 858.16 31-MAY-18:03 780.07 780.07 7.50 14.40
June 0.106142E+10 0.964831E+09 1960.14 24-JUN-18:03 1781.77 1781.77 7.33 20.53
July 0.187935E+10 0.170833E+10 2109.99 20-JUL-18:03 1917.99 1917.99 6.73 21.17
August 0.159916E+10 0.145364E+10 2611.41 11-AUG-21:00 2373.77 2373.77 7.15 23.12
September 0.721947E+09 0.656249E+09 2162.03 07-SEP-20:00 1965.29 1965.29 7.15 21.38
October 0.250232E+09 0.227461E+09 840.76 05-OCT-15:05 764.25 764.25 7.42 14.28
November 20086054.80 18258223.81 282.21 04-NOV-15:01 256.53 256.53 8.15 8.66
December 4187008.78 3805990.98 64.22 20-DEC-09:01 58.38 58.38 8.40 4.08
                 
Annual Sum or Average 0.588259E+10 0.534727E+10            
Minimum of Months 1012437.31 920305.51 40.57   36.88 36.88 6.73 3.16
Maximum of Months 0.187935E+10 0.170833E+10 2611.41   2373.77 2373.77 8.40 23.12



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.236193E+10 0.214700E+10 4875.28 01-JAN-09:03 4431.63 4431.63 8.45 34.51
February 0.328246E+10 0.298375E+10 4875.28 01-FEB-09:01 4431.63 4431.63 8.43 34.51
March 0.676648E+10 0.615073E+10 4875.28 01-MAR-07:15 4431.63 4431.63 8.41 34.51
April 0.986104E+10 0.896369E+10 4875.28 01-APR-08:62 4431.63 4431.63 8.54 34.51
May 0.129695E+11 0.117892E+11 4875.28 01-MAY-00:05 4431.63 4431.63 8.45 34.51
June 0.126367E+11 0.114868E+11 4875.28 01-JUN-00:05 4431.63 4431.63 9.11 34.51
July 0.130579E+11 0.118697E+11 4875.28 01-JUL-00:10 4431.63 4431.63 9.77 34.51
August 0.130579E+11 0.118697E+11 4875.28 01-AUG-00:05 4431.63 4431.63 9.55 34.51
September 0.126367E+11 0.114868E+11 4875.28 01-SEP-00:05 4431.63 4431.63 9.52 34.51
October 0.125958E+11 0.114496E+11 4875.28 01-OCT-00:10 4431.63 4431.63 8.60 34.51
November 0.712252E+10 0.647437E+10 4875.28 01-NOV-00:05 4431.63 4431.63 8.42 34.51
December 0.348243E+10 0.316553E+10 4875.28 01-DEC-07:05 4431.63 4431.63 8.40 34.51
                 
Annual Sum or Average 0.109831E+12 0.998368E+11            
Minimum of Months 0.236193E+10 0.214700E+10 4875.28   4431.63 4431.63 8.40 34.51
Maximum of Months 0.130579E+11 0.118697E+11 4875.28   4431.63 4431.63 9.77 34.51



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:03 14.37 14.37 48.16 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:03 14.37 14.37 49.16 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:03 14.37 14.37 49.23 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 52.52 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:05 14.37 14.37 52.75 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:05 14.37 14.37 53.28 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 53.90 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:05 14.37 14.37 53.93 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:05 14.37 14.37 53.87 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 53.00 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:05 14.37 14.37 53.08 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:03 14.37 14.37 50.02 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 48.16 0.37
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 53.93 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 44.29 82.20 48935.71 228682.20 02-JAN-09:01
February 0.00 0.00 01-FEB-00:03 50.58 81.26 46370.07 236148.43 06-FEB-09:01
March 0.00 0.00 01-MAR-00:03 58.91 80.15 22396.61 173918.13 17-MAR-08:61
April 0.00 0.00 01-APR-00:10 63.00 80.20 26164.04 157549.42 02-APR-18:05
May 0.00 0.00 01-MAY-00:05 34.61 79.40 10782.44 99685.10 03-MAY-15:05
June 0.00 0.00 01-JUN-00:05 33.21 33.21 272.67 24434.81 06-JUN-15:07
July 0.00 0.00 01-JUL-00:10 40.23 40.23 36.45 26237.59 18-JUL-08:05
August 0.00 0.00 01-AUG-00:05 42.71 42.71 113.50 25162.84 25-AUG-21:57
September 0.00 0.00 01-SEP-00:05 38.74 38.74 2758.57 72685.64 24-SEP-05:50
October 0.00 0.00 01-OCT-00:10 25.23 79.40 16556.33 133298.01 28-OCT-18:05
November 0.00 0.00 01-NOV-00:05 35.95 79.40 34324.70 159079.27 28-NOV-16:01
December 0.00 0.00 01-DEC-00:03 61.67 80.08 29981.33 186335.52 31-DEC-19:01
                 
Annual Sum or Average 0.00         19717.36    
Minimum of Months 0.00 0.00   25.23 33.21 36.45 24434.81  
Maximum of Months 0.00 0.00   63.00 82.20 48935.71 236148.43  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 1422.53 45523.04 17-JAN-16:03 8.68 8.37 0.00 0.00 01-JAN-00:03
February 3116.56 60873.42 20-FEB-16:02 8.79 8.37 0.00 0.00 01-FEB-00:03
March 9686.73 239121.02 27-MAR-15:03 9.38 7.73 0.00 0.00 01-MAR-00:03
April 33180.62 362407.34 07-APR-15:05 9.37 6.87 0.00 0.00 01-APR-00:10
May 84986.45 411007.08 31-MAY-15:25 9.76 6.92 0.00 0.00 01-MAY-00:05
June 271920.56 644200.53 23-JUN-21:52 11.74 7.29 0.00 0.00 01-JUN-00:05
July 400406.82 662059.20 20-JUL-18:03 11.28 6.70 0.00 0.00 01-JUL-00:10
August 339461.76 758401.44 11-AUG-21:51 12.37 7.12 0.00 0.00 01-AUG-00:05
September 199860.10 636823.99 07-SEP-20:00 11.53 7.12 0.00 0.00 01-SEP-00:05
October 87120.02 455770.28 05-OCT-15:05 10.54 7.39 0.00 0.00 01-OCT-00:10
November 11369.33 177250.37 04-NOV-15:03 9.34 8.11 0.00 0.00 01-NOV-00:05
December 3413.64 46572.92 18-DEC-11:00 8.69 8.37 0.00 0.00 01-DEC-00:03
                 
Annual Sum or Average 121366.08         0.00    
Minimum of Months 1422.53 45523.04   8.68 6.70 0.00 0.00  
Maximum of Months 400406.82 758401.44   12.37 8.37 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 48.16 60.00 27303.87 57697.32 30-JAN-07:40
February 0.00 0.00 01-FEB-00:03 49.16 59.96 27587.31 57701.11 09-FEB-07:20
March 0.00 0.00 01-MAR-00:03 49.23 60.00 26965.39 57220.21 01-MAR-08:00
April 0.00 0.00 01-APR-00:10 52.52 59.99 25576.07 54800.13 03-APR-07:00
May 0.00 0.00 01-MAY-00:05 52.75 59.99 23821.86 51556.85 01-MAY-06:40
June 0.00 0.00 01-JUN-00:05 53.28 59.97 22155.53 47702.70 01-JUN-06:20
July 0.00 0.00 01-JUL-00:10 53.90 59.99 20997.59 44549.33 03-JUL-06:35
August 0.00 0.00 01-AUG-00:05 53.93 60.00 20721.78 47335.41 25-AUG-17:01
September 0.00 0.00 01-SEP-00:05 53.87 59.97 21342.56 45564.34 29-SEP-07:00
October 0.00 0.00 01-OCT-00:10 53.00 59.96 22717.27 49172.57 31-OCT-06:40
November 0.00 0.00 01-NOV-00:05 53.08 59.99 24481.02 52946.39 30-NOV-08:00
December 0.00 0.00 01-DEC-00:03 50.02 59.97 26154.91 55882.63 29-DEC-08:00
                 
Annual Sum or Average 0.00         24132.23    
Minimum of Months 0.00 0.00   48.16 59.96 20721.78 44549.33  
Maximum of Months 0.00 0.00   53.93 60.00 27587.31 57701.11  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.831948E+11 0.00 0.00 0.341031E+11 0.00 0.00
February 0.694218E+11 0.00 0.00 0.308165E+11 0.00 0.00
March 0.433008E+11 0.00 0.329359E+10 0.352063E+11 0.00 0.00
April 0.626388E+11 0.00 0.339278E+11 0.349857E+11 0.00 0.00
May 0.286884E+11 0.00 0.125500E+12 0.375417E+11 0.00 0.00
June 0.686489E+09 0.00 0.520638E+12 0.384000E+11 0.00 0.00
July 85069830.90 0.00 0.826657E+12 0.408288E+11 0.00 0.00
August 0.297947E+09 0.00 0.668323E+12 0.416378E+11 0.00 0.00
September 0.715333E+10 0.00 0.360538E+12 0.380183E+11 0.00 0.00
October 0.433189E+11 0.00 0.123645E+12 0.378130E+11 0.00 0.00
November 0.715244E+11 0.00 0.332701E+10 0.343798E+11 0.00 0.00
December 0.445106E+11 0.00 0.00 0.344091E+11 0.00 0.00
             
Annual Sum or Average 0.454821E+12 0.00 0.266585E+13 0.438140E+12 0.00 0.00
Minimum of Months 85069830.90 0.00 0.00 0.308165E+11 0.00 0.00
Maximum of Months 0.831948E+11 0.00 0.826657E+12 0.416378E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.151904E+10 0.00 0.00 0.271000E+10 0.00 0.00
February 0.172003E+10 0.00 0.00 0.244774E+10 0.00 0.00
March 0.125874E+09 0.00 0.274237E+09 0.271000E+10 0.00 0.00
April 1091.90 0.00 0.217150E+10 0.262258E+10 0.00 0.00
May 9834.81 0.00 0.903150E+10 0.271000E+10 0.00 0.00
June 11539.64 0.00 0.428359E+11 0.262258E+10 0.00 0.00
July 6965.48 0.00 0.583701E+11 0.271000E+10 0.00 0.00
August 6322.32 0.00 0.471787E+11 0.271000E+10 0.00 0.00
September 15917.17 0.00 0.291741E+11 0.262258E+10 0.00 0.00
October 4403.52 0.00 0.100475E+11 0.271000E+10 0.00 0.00
November 0.137710E+09 0.00 0.209566E+09 0.262258E+10 0.00 0.00
December 0.194570E+09 0.00 0.00 0.271000E+10 0.00 0.00
             
Annual Sum or Average 0.369727E+10 0.00 0.199293E+12 0.319080E+11 0.00 0.00
Minimum of Months 1091.90 0.00 0.00 0.244774E+10 0.00 0.00
Maximum of Months 0.172003E+10 0.00 0.583701E+11 0.271000E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.341031E+11 0.00 0.831948E+11 0.591265E+12 0.00 0.00 0.00 0.00
February 0.308165E+11 0.00 0.694218E+11 0.592818E+12 0.00 0.00 0.00 0.00
March 0.352063E+11 0.329359E+10 0.433008E+11 0.418884E+12 0.00 0.00 0.00 0.00
April 0.349857E+11 0.339278E+11 0.626388E+11 0.147483E+12 0.209163E+09 0.00 0.00 0.00
May 0.375417E+11 0.125500E+12 0.286884E+11 0.106326E+11 0.337942E+10 0.00 0.00 0.00
June 0.384000E+11 0.520638E+12 0.686489E+09 0.00 0.584417E+11 0.00 0.00 0.00
July 0.408288E+11 0.826657E+12 85069830.90 0.00 0.228803E+12 0.00 0.00 0.00
August 0.416378E+11 0.668323E+12 0.297947E+09 0.00 0.182090E+12 0.00 0.00 0.00
September 0.380183E+11 0.360538E+12 0.715333E+10 0.00 0.243348E+11 0.00 0.00 0.00
October 0.378130E+11 0.123645E+12 0.433189E+11 0.615758E+11 0.636522E+09 0.00 0.00 0.00
November 0.343798E+11 0.332701E+10 0.715244E+11 0.286171E+12 0.00 0.00 0.00 0.00
December 0.344091E+11 0.00 0.445106E+11 0.536468E+12 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.438140E+12 0.266585E+13 0.454821E+12 0.264530E+13 0.497895E+12 0.00 0.00 0.00
Minimum of Months 0.308165E+11 0.00 85069830.90 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.416378E+11 0.826657E+12 0.831948E+11 0.592818E+12 0.228803E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.271000E+10 0.00 0.151904E+10 0.556894E+11 50002.83 0.00 0.00 0.00
February 0.244774E+10 0.00 0.172003E+10 0.543396E+11 0.00 0.00 0.00 0.00
March 0.271000E+10 0.274237E+09 0.125874E+09 0.403217E+11 0.00 0.00 0.00 0.00
April 0.262258E+10 0.217150E+10 1091.90 0.201376E+11 38481789.28 0.00 0.00 0.00
May 0.271000E+10 0.903150E+10 9834.81 0.472421E+10 0.403141E+09 0.00 0.00 0.00
June 0.262258E+10 0.428359E+11 11539.64 96976156.38 0.789241E+10 0.00 0.00 0.00
July 0.271000E+10 0.583701E+11 6965.48 1817337.11 0.311228E+11 0.00 0.00 0.00
August 0.271000E+10 0.471787E+11 6322.32 0.111989E+09 0.237235E+11 0.00 0.00 0.00
September 0.262258E+10 0.291741E+11 15917.17 0.988926E+09 0.521879E+10 0.00 0.00 0.00
October 0.271000E+10 0.100475E+11 4403.52 0.108974E+11 0.112504E+09 0.00 0.00 0.00
November 0.262258E+10 0.209566E+09 0.137710E+09 0.324648E+11 0.00 0.00 0.00 0.00
December 0.271000E+10 0.00 0.194570E+09 0.495336E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.319080E+11 0.199293E+12 0.369727E+10 0.269308E+12 0.685116E+11 0.00 0.00 0.00
Minimum of Months 0.244774E+10 0.00 1091.90 1817337.11 0.00 0.00 0.00 0.00
Maximum of Months 0.271000E+10 0.583701E+11 0.172003E+10 0.556894E+11 0.311228E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.341031E+11 0.831948E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.308165E+11 0.694218E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.352063E+11 0.433008E+11 0.329359E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.349857E+11 0.626388E+11 0.339278E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.375417E+11 0.286884E+11 0.125500E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.384000E+11 0.686489E+09 0.520638E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.408288E+11 85069830.90 0.826657E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.416378E+11 0.297947E+09 0.668323E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.380183E+11 0.715333E+10 0.360538E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.378130E+11 0.433189E+11 0.123645E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.343798E+11 0.715244E+11 0.332701E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.344091E+11 0.445106E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.438140E+12 0.454821E+12 0.266585E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.308165E+11 85069830.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.416378E+11 0.831948E+11 0.826657E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.271000E+10 0.151904E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.244774E+10 0.172003E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.271000E+10 0.125874E+09 0.274237E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.262258E+10 1091.90 0.217150E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.271000E+10 9834.81 0.903150E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.262258E+10 11539.64 0.428359E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.271000E+10 6965.48 0.583701E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.271000E+10 6322.32 0.471787E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.262258E+10 15917.17 0.291741E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.271000E+10 4403.52 0.100475E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.262258E+10 0.137710E+09 0.209566E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.271000E+10 0.194570E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.319080E+11 0.369727E+10 0.199293E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.244774E+10 1091.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.271000E+10 0.172003E+10 0.583701E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.451328E+11 0.00 0.00 251.36 0.00 0.00 21175333.67 0.00 0.88
February 0.405962E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.88
March 0.435947E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
April 0.426905E+11 0.00 0.00 0.00 7486963.67 0.00 0.00 0.00 0.88
May 0.349096E+11 0.00 0.00 0.00 0.241964E+09 0.00 0.00 0.00 0.88
June 0.897679E+10 0.00 0.00 0.00 0.104770E+11 0.00 0.00 0.00 0.89
July 0.476144E+09 0.00 0.00 0.00 0.255058E+11 0.00 0.00 0.00 0.89
August 0.521993E+10 0.746570E+09 0.00 325013.23 0.150176E+11 0.00 0.288396E+09 0.00 0.89
September 0.660698E+10 0.246276E+10 0.00 11757809.99 0.313146E+10 0.00 0.125538E+11 0.00 0.89
October 0.743218E+10 36558070.37 0.00 37524304.24 0.399391E+09 0.00 0.321335E+11 0.00 0.92
November 0.135488E+11 0.00 0.00 30068097.19 0.00 0.00 0.338259E+11 0.00 0.91
December 0.290037E+11 0.00 0.00 9229725.94 0.00 0.00 0.141681E+11 0.00 0.89
                   
Annual Sum or Average 0.278188E+12 0.324589E+10 0.00 88905201.95 0.547806E+11 0.00 0.929908E+11 0.00 0.89
Minimum of Months 0.476144E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Maximum of Months 0.451328E+11 0.246276E+10 0.00 37524304.24 0.255058E+11 0.00 0.338259E+11 0.00 0.92



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.458242E+10 0.00 0.00 136850.95 0.00 0.283276E+10 0.231863E+09 0.00 2.67
February 0.447062E+10 0.00 0.00 220400.88 0.00 0.210738E+10 0.294395E+09 0.00 2.69
March 0.647023E+10 0.00 0.00 546638.73 0.00 0.388656E+09 0.547946E+09 0.00 2.69
April 0.685236E+10 1268721.44 0.00 470246.11 296100.35 49978883.63 0.325598E+09 0.00 2.70
May 0.572722E+10 26126185.62 0.00 181429.55 15541537.07 0.00 0.181554E+09 0.00 2.70
June 0.144531E+10 0.574127E+09 0.00 195542.92 0.120414E+10 0.00 73944604.76 0.00 2.73
July 65155939.94 0.216481E+10 0.00 39181.23 0.221599E+10 0.00 15398910.69 0.00 2.76
August 0.752290E+09 0.217737E+10 0.00 832371.32 0.669920E+09 0.00 0.180384E+09 0.00 2.89
September 0.272753E+10 0.431667E+09 0.00 2110371.56 0.559459E+09 0.00 0.530720E+09 0.00 2.83
October 0.525446E+10 94237072.83 0.00 2925039.25 3834617.84 0.00 0.132846E+10 0.00 2.84
November 0.706284E+10 0.00 0.00 451059.39 0.00 0.304173E+09 0.405890E+09 0.00 2.71
December 0.534341E+10 0.00 0.00 412667.94 0.00 0.158531E+10 0.380645E+09 0.00 2.71
                   
Annual Sum or Average 0.507538E+11 0.546960E+10 0.00 8521799.82 0.466918E+10 0.726826E+10 0.449680E+10 0.00 2.74
Minimum of Months 65155939.94 0.00 0.00 39181.23 0.00 0.00 15398910.69 0.00 2.67
Maximum of Months 0.706284E+10 0.217737E+10 0.00 2925039.25 0.221599E+10 0.283276E+10 0.132846E+10 0.00 2.89



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.471779E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.43
February 0.424159E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.44
March 0.448412E+10 0.00 0.00 9902.31 0.00 0.00 70758022.34 0.00 1.43
April 0.409766E+10 0.00 0.00 209968.98 782255.81 0.00 0.363792E+09 0.00 1.44
May 0.297861E+10 1313606.48 0.00 535057.27 23972557.00 0.00 0.672477E+09 0.00 1.45
June 0.373850E+09 0.518362E+09 0.00 1028088.25 0.598719E+09 0.00 0.573445E+09 0.00 1.48
July 3977130.37 0.178175E+10 0.00 320970.31 0.977092E+09 0.00 47404312.51 0.00 1.51
August 70249930.92 0.137087E+10 0.00 1585271.82 0.384090E+09 0.00 0.526515E+09 0.00 1.54
September 0.111600E+10 0.359335E+09 0.00 1326634.32 0.242937E+09 0.00 0.888456E+09 0.00 1.48
October 0.283166E+10 8446250.01 0.00 1027738.50 37049286.57 0.00 0.115878E+10 0.00 1.45
November 0.463205E+10 0.00 0.00 40768.94 0.00 0.00 0.151783E+09 0.00 1.44
December 0.449728E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.44
                   
Annual Sum or Average 0.340448E+11 0.404009E+10 0.00 6084400.69 0.226464E+10 0.00 0.445341E+10 0.00 1.46
Minimum of Months 3977130.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.43
Maximum of Months 0.471779E+10 0.178175E+10 0.00 1585271.82 0.977092E+09 0.00 0.115878E+10 0.00 1.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.305220E+10 0.00 0.00 0.00 0.00 0.939015E+09 0.00 0.00 0.57
February 0.261738E+10 0.00 0.00 0.00 0.00 0.970977E+09 0.00 0.00 0.57
March 0.383680E+10 0.00 0.00 0.00 0.00 16592854.98 0.00 0.00 0.57
April 0.377347E+10 0.00 0.00 0.00 661782.71 0.00 0.00 0.00 0.57
May 0.307884E+10 0.00 0.00 3453.28 21387495.33 0.00 6863842.88 0.00 0.58
June 0.778847E+09 0.121365E+09 0.00 79938.92 0.806744E+09 0.00 15342256.94 0.00 0.58
July 16499643.98 0.688460E+09 0.00 107411.95 0.159260E+10 0.00 26033331.55 0.00 0.59
August 0.367012E+09 0.658392E+09 0.00 355677.61 0.771836E+09 0.00 0.122104E+09 0.00 0.59
September 0.163556E+10 59545007.93 0.00 99298.37 0.431399E+09 0.00 42665999.18 0.00 0.58
October 0.336550E+10 0.00 0.00 0.00 38417941.96 0.00 0.00 0.00 0.58
November 0.404712E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.57
December 0.377380E+10 0.00 0.00 0.00 0.00 30872499.63 0.00 0.00 0.58
                   
Annual Sum or Average 0.303430E+11 0.152776E+10 0.00 645780.13 0.366305E+10 0.195746E+10 0.213009E+09 0.00 0.58
Minimum of Months 16499643.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.57
Maximum of Months 0.404712E+10 0.688460E+09 0.00 355677.61 0.159260E+10 0.970977E+09 0.122104E+09 0.00 0.59



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.108759E+10 0.00 0.00 0.00 0.00 0.105953E+10 0.00 0.00 0.53
February 0.947934E+09 0.00 0.00 0.00 0.00 0.982462E+09 0.00 0.00 0.53
March 0.198397E+10 0.00 0.00 0.00 0.00 89013000.22 0.00 0.00 0.53
April 0.202998E+10 0.00 0.00 0.00 356013.43 0.00 0.00 0.00 0.54
May 0.165999E+10 0.00 0.00 0.00 11505643.17 0.00 0.00 0.00 0.54
June 0.424067E+09 8508511.00 0.00 2689.49 0.489683E+09 0.00 2787322.68 0.00 0.54
July 15505887.93 0.123799E+09 0.00 16283.64 0.108917E+10 0.00 7118988.56 0.00 0.54
August 0.245029E+09 0.207994E+09 0.00 40835.97 0.543111E+09 0.00 16979730.34 0.00 0.54
September 0.902072E+09 2129900.70 0.00 2822.47 0.261639E+09 0.00 761898.03 0.00 0.54
October 0.181051E+10 0.00 0.00 0.00 20667363.09 0.00 0.00 0.00 0.54
November 0.204815E+10 0.00 0.00 0.00 0.00 0.129041E+09 0.00 0.00 0.54
December 0.177130E+10 0.00 0.00 0.00 0.00 0.275459E+09 0.00 0.00 0.54
                   
Annual Sum or Average 0.149261E+11 0.342432E+09 0.00 62631.57 0.241613E+10 0.253551E+10 27647939.60 0.00 0.54
Minimum of Months 15505887.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.53
Maximum of Months 0.204815E+10 0.207994E+09 0.00 40835.97 0.108917E+10 0.105953E+10 16979730.34 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.768413E+09 0.00 0.00 88623355.52 0.00 0.00 0.786716E+11 0.00 23.90
February 0.685481E+09 0.00 0.00 80238294.84 0.00 0.00 0.706385E+11 0.00 24.05
March 0.315788E+09 0.00 0.00 90713099.89 0.00 0.00 0.766947E+11 0.00 24.05
April 0.258879E+09 11718728.47 0.00 92795183.50 0.00 0.00 0.752701E+11 0.00 24.11
May 0.225493E+09 0.383193E+09 0.00 0.106627E+09 13022703.84 0.00 0.613990E+11 0.00 24.19
June 68907981.71 0.184633E+11 0.00 52161459.95 93159505.24 0.00 0.155735E+11 0.00 24.36
July 278518.67 0.448396E+11 0.00 6051195.53 0.128921E+09 0.00 0.778287E+09 0.00 24.20
August 39033302.36 0.277892E+11 0.00 39662057.66 0.117407E+09 0.00 0.919684E+10 0.00 24.27
September 0.121736E+09 0.100082E+11 0.00 74489764.29 19061472.74 0.00 0.329590E+11 0.00 24.21
October 0.292866E+09 0.698621E+09 0.00 97281894.50 3645381.11 0.00 0.664192E+11 0.00 24.19
November 0.388584E+09 0.00 0.00 87656175.27 0.00 0.00 0.802713E+11 0.00 24.18
December 0.486099E+09 0.00 0.00 89722260.93 0.00 0.00 0.751371E+11 0.00 24.15
                   
Annual Sum or Average 0.365156E+10 0.102194E+12 0.00 0.906022E+09 0.375217E+09 0.00 0.643009E+12 0.00 24.16
Minimum of Months 278518.67 0.00 0.00 6051195.53 0.00 0.00 0.778287E+09 0.00 23.90
Maximum of Months 0.768413E+09 0.448396E+11 0.00 0.106627E+09 0.128921E+09 0.00 0.802713E+11 0.00 24.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.277807E+11 0.00 0.00 1810352.06 0.00 6437727.14 0.477167E+10 0.00 4.06
February 0.225637E+11 0.00 0.00 2919715.11 0.00 0.00 0.671777E+10 0.00 4.08
March 0.184856E+11 0.00 0.00 7273381.89 0.00 0.00 0.130485E+11 0.00 4.09
April 0.157691E+11 5709803.33 0.00 9519538.52 439833.70 0.00 0.150094E+11 0.00 4.10
May 0.841894E+10 0.131128E+09 0.00 12501157.64 43293518.09 0.00 0.167428E+11 0.00 4.11
June 0.106304E+10 0.567457E+10 0.00 11171456.29 0.193890E+10 0.00 0.542228E+10 0.00 4.17
July 28779138.12 0.164020E+11 0.00 2007348.46 0.235034E+10 0.00 0.327591E+09 0.00 4.23
August 0.336821E+09 0.110635E+11 0.00 13207082.69 0.939723E+09 0.00 0.375477E+10 0.00 4.37
September 0.280113E+10 0.325949E+10 0.00 22901536.77 0.949593E+09 0.00 0.110990E+11 0.00 4.28
October 0.536362E+10 0.372130E+09 0.00 30208408.94 6358485.28 0.00 0.226442E+11 0.00 4.28
November 0.193116E+11 0.00 0.00 7022059.96 0.00 0.00 0.137828E+11 0.00 4.11
December 0.234310E+11 0.00 0.00 3800343.31 0.00 0.00 0.773825E+10 0.00 4.11
                   
Annual Sum or Average 0.145354E+12 0.369085E+11 0.00 0.124342E+09 0.622864E+10 6437727.14 0.121059E+12 0.00 4.17
Minimum of Months 28779138.12 0.00 0.00 1810352.06 0.00 0.00 0.327591E+09 0.00 4.06
Maximum of Months 0.277807E+11 0.164020E+11 0.00 30208408.94 0.235034E+10 6437727.14 0.226442E+11 0.00 4.37



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.966790E+11 0.00 0.00 1140112.13 0.00 0.00 0.488288E+10 0.00 1.83
February 0.860913E+11 0.00 0.00 1215683.73 0.00 0.00 0.521907E+10 0.00 1.84
March 0.763470E+11 0.00 0.00 8501634.30 0.00 0.00 0.217176E+11 0.00 1.84
April 0.603024E+11 1071487.20 0.00 21644880.45 15768652.85 0.00 0.359398E+11 0.00 1.85
May 0.304083E+11 0.118953E+09 0.00 46109824.24 0.425360E+09 0.00 0.486191E+11 0.00 1.87
June 0.364672E+10 0.144433E+11 0.00 45475950.35 0.100088E+11 0.00 0.172084E+11 0.00 1.94
July 51883650.00 0.477498E+11 0.00 8357919.51 0.131103E+11 0.00 0.113660E+10 0.00 1.99
August 0.879960E+09 0.333570E+11 0.00 45032350.17 0.497229E+10 0.00 0.126787E+11 0.00 2.02
September 0.889090E+10 0.967867E+10 0.00 60760565.74 0.364885E+10 0.00 0.352726E+11 0.00 1.94
October 0.260216E+11 0.762226E+09 0.00 64193756.64 0.218227E+09 0.00 0.611945E+11 0.00 1.89
November 0.750326E+11 0.00 0.00 13088516.75 0.00 0.00 0.280520E+11 0.00 1.85
December 0.861994E+11 0.00 0.00 2682788.21 0.00 0.00 0.106139E+11 0.00 1.85
                   
Annual Sum or Average 0.550551E+12 0.106111E+12 0.00 0.318204E+09 0.323996E+11 0.00 0.282535E+12 0.00 1.89
Minimum of Months 51883650.00 0.00 0.00 1140112.13 0.00 0.00 0.113660E+10 0.00 1.83
Maximum of Months 0.966790E+11 0.477498E+11 0.00 64193756.64 0.131103E+11 0.00 0.611945E+11 0.00 2.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 61692004.57 0.00 0.00 496391.30 0.00 0.151197E+10 49348065.14 0.00 0.35
February 63801272.34 0.00 0.00 815080.28 0.00 0.131864E+10 0.103294E+09 0.00 0.35
March 64345584.27 37349.02 0.00 3420514.42 15399.90 0.100874E+10 0.483428E+09 0.00 0.35
April 51258640.11 803694.06 0.00 7266132.66 0.00 0.550220E+09 0.785096E+09 0.00 0.35
May 17674769.00 14493992.18 9446.10 13385093.77 633797.08 34978293.83 0.104088E+10 1080.36 0.36
June 0.00 0.537760E+09 129636.06 7328245.05 0.00 496335.73 0.223578E+09 5858.05 0.36
July 0.00 0.110914E+10 820019.65 309599.55 0.00 16103.23 1786432.54 15918.44 0.36
August 0.00 0.765061E+09 409651.96 4067433.58 0.00 232322.07 80856769.76 8444.72 0.36
September 5181335.13 0.265702E+09 171305.62 9524711.92 3857861.77 2500598.73 0.496992E+09 6457.61 0.35
October 10079534.41 42993995.32 9329.16 10134146.27 0.00 0.108898E+09 0.974038E+09 1735.20 0.35
November 69141020.57 0.00 0.00 1794932.33 0.00 0.104818E+10 0.391631E+09 0.00 0.36
December 65184577.56 0.00 0.00 621010.55 0.00 0.141299E+10 88774267.03 0.00 0.36
                   
Annual Sum or Average 0.408359E+09 0.273599E+10 1549388.55 59163291.68 4507058.75 0.699786E+10 0.471970E+10 39494.37 0.35
Minimum of Months 0.00 0.00 0.00 309599.55 0.00 16103.23 1786432.54 0.00 0.35
Maximum of Months 69141020.57 0.110914E+10 820019.65 13385093.77 3857861.77 0.151197E+10 0.104088E+10 15918.44 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 53877517.98 0.00 0.00 165215.10 0.00 0.155961E+10 9666008.66 0.00 0.35
February 49507688.15 0.00 0.00 305700.76 0.00 0.140063E+10 35934506.04 0.00 0.35
March 93729344.07 0.00 0.00 1883498.50 52742.74 0.119718E+10 0.266960E+09 0.00 0.35
April 0.115718E+09 803599.90 0.00 5158135.64 0.00 0.626962E+09 0.645839E+09 0.00 0.35
May 0.176893E+09 12928971.94 13652.34 10226724.16 2191486.99 37663303.43 0.882001E+09 2430.77 0.36
June 93382787.09 0.428134E+09 247494.31 4346261.71 0.109444E+09 84589.43 0.133562E+09 6842.26 0.36
July 1396546.03 0.948776E+09 576506.93 64753.44 0.160486E+09 0.00 650588.38 10038.72 0.36
August 29284518.21 0.706543E+09 299592.12 2840204.89 58537843.55 27309.63 52994515.34 8098.20 0.36
September 0.158225E+09 0.198883E+09 330775.24 5151329.60 70489088.62 2086565.74 0.348676E+09 3340.97 0.36
October 0.166116E+09 34178459.44 46585.70 5150040.09 8768245.14 0.220490E+09 0.711264E+09 6730.73 0.35
November 0.100099E+09 0.00 0.00 761118.91 0.00 0.120351E+10 0.206193E+09 0.00 0.36
December 63061957.35 0.00 0.00 154050.76 0.00 0.149627E+10 7897138.07 0.00 0.36
                   
Annual Sum or Average 0.110129E+10 0.233025E+10 1514606.64 36207033.58 0.409970E+09 0.774452E+10 0.330164E+10 37481.65 0.36
Minimum of Months 1396546.03 0.00 0.00 64753.44 0.00 0.00 650588.38 0.00 0.35
Maximum of Months 0.176893E+09 0.948776E+09 576506.93 10226724.16 0.160486E+09 0.155961E+10 0.882001E+09 10038.72 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.103024E+10 0.00 0.00 7115.25 3884537.56 0.00 20190270.83 0.00 0.02
February 0.958718E+09 0.00 0.00 548620.58 0.00 0.00 0.423912E+09 0.00 0.02
March 0.843551E+09 0.00 0.00 1351975.04 0.00 0.00 0.767492E+09 0.00 0.02
April 0.621655E+09 0.00 0.00 2158900.99 0.00 0.00 0.783144E+09 0.00 0.02
May 0.201875E+09 30970977.45 0.00 2411619.52 0.00 0.00 0.922235E+09 0.00 0.02
June 0.00 0.626522E+09 0.00 1416638.88 0.00 0.00 0.202203E+09 0.00 0.02
July 0.00 0.114215E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.02
August 0.00 0.787536E+09 0.00 1242755.97 0.00 0.00 20435089.03 0.00 0.02
September 37572021.32 0.327925E+09 0.00 3023403.58 7128067.34 0.00 0.424657E+09 0.00 0.02
October 84877373.61 86953394.93 0.00 4564528.88 0.00 0.00 0.961309E+09 0.00 0.02
November 0.104874E+10 0.00 0.00 1106721.87 0.00 0.00 0.542636E+09 0.00 0.02
December 0.113437E+10 0.00 0.00 576860.18 0.00 0.00 0.354964E+09 0.00 0.02
                   
Annual Sum or Average 0.596160E+10 0.300205E+10 0.00 18409140.74 11012604.90 0.00 0.542318E+10 0.00 0.02
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
Maximum of Months 0.113437E+10 0.114215E+10 0.00 4564528.88 7128067.34 0.00 0.961309E+09 0.00 0.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.109399E+10 0.00 0.00 5521900.86 0.00 0.154873E+11 0.543251E+10 0.00 0.40
February 0.104645E+10 0.00 0.00 4108068.21 0.00 0.149586E+11 0.415262E+10 0.00 0.40
March 0.131214E+10 0.00 0.00 27909141.33 715423.66 0.464614E+10 0.151710E+11 0.00 0.40
April 0.166347E+10 10582348.74 0.00 73934339.20 318001.78 0.151508E+09 0.170155E+11 0.00 0.40
May 0.276882E+10 0.167009E+09 181503.53 0.134223E+09 38122047.53 14923711.82 0.120949E+11 5931.13 0.40
June 0.130411E+10 0.574384E+10 61823.28 50238024.14 0.155148E+10 415078.68 0.178371E+10 889.72 0.41
July 18943309.11 0.128532E+11 0.00 621469.55 0.220120E+10 0.00 9081713.10 0.00 0.40
August 0.400327E+09 0.955518E+10 147664.27 28331506.17 0.826712E+09 146476.29 0.726157E+09 859.60 0.40
September 0.225534E+10 0.264738E+10 82263.72 69204975.41 0.101093E+10 2495858.36 0.464694E+10 6734.41 0.40
October 0.231295E+10 0.398910E+09 526472.94 71207038.30 0.183825E+09 81763619.29 0.124959E+11 7611.56 0.40
November 0.136654E+10 0.00 0.00 30561168.33 0.00 0.421352E+10 0.148793E+11 0.00 0.40
December 0.111219E+10 0.00 0.00 6387144.79 0.00 0.129202E+11 0.722184E+10 0.00 0.40
                   
Annual Sum or Average 0.166553E+11 0.313761E+11 999727.74 0.502247E+09 0.581330E+10 0.524771E+11 0.956294E+11 22026.41 0.40
Minimum of Months 18943309.11 0.00 0.00 621469.55 0.00 0.00 9081713.10 0.00 0.40
Maximum of Months 0.276882E+10 0.128532E+11 526472.94 0.134223E+09 0.220120E+10 0.154873E+11 0.170155E+11 7611.56 0.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 63946531.99 0.00 0.00 511564.67 0.00 0.147903E+10 80015291.71 0.00 0.35
February 65485111.30 0.00 0.00 876460.76 0.00 0.128794E+10 0.132250E+09 0.00 0.35
March 57853362.19 0.00 0.00 3253318.55 52748.92 0.104135E+10 0.457483E+09 0.00 0.35
April 40957212.31 803694.06 0.00 7294833.49 0.00 0.537775E+09 0.807813E+09 0.00 0.35
May 16168145.91 14890784.18 0.00 13625065.16 247531.53 34045314.86 0.104308E+10 0.00 0.36
June 0.00 0.537875E+09 18810.91 7695757.82 0.00 127269.60 0.223580E+09 1577.82 0.36
July 0.00 0.110982E+10 158273.09 414666.86 0.00 7815.23 1689653.23 1565.25 0.36
August 0.00 0.765479E+09 0.00 4596369.03 0.00 20208.65 80539947.73 0.00 0.36
September 4979724.39 0.265662E+09 212004.47 9955671.31 3857861.77 1389388.69 0.497874E+09 5434.66 0.35
October 9965702.66 43005059.67 0.00 10094895.41 0.00 0.125955E+09 0.957134E+09 0.00 0.35
November 66714128.45 0.00 0.00 2507407.42 0.00 0.992564E+09 0.448957E+09 0.00 0.36
December 69160066.16 0.00 0.00 927708.68 0.00 0.136782E+10 0.129663E+09 0.00 0.36
                   
Annual Sum or Average 0.395230E+09 0.273754E+10 389088.47 61753719.16 4158142.22 0.686802E+10 0.486007E+10 8577.74 0.35
Minimum of Months 0.00 0.00 0.00 414666.86 0.00 7815.23 1689653.23 0.00 0.35
Maximum of Months 69160066.16 0.110982E+10 212004.47 13625065.16 3857861.77 0.147903E+10 0.104308E+10 5434.66 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 45276102.77 0.00 0.00 116729.29 0.00 0.154672E+10 31201648.56 0.00 0.35
February 43221856.72 0.00 0.00 252499.57 0.00 0.139641E+10 46494233.86 0.00 0.35
March 93022422.99 0.00 0.00 1537338.25 52742.74 0.119308E+10 0.272111E+09 0.00 0.35
April 0.110042E+09 803599.90 0.00 5242200.77 0.00 0.590896E+09 0.687496E+09 0.00 0.35
May 0.165639E+09 13382658.79 0.00 10852346.59 1753883.25 38339395.69 0.891953E+09 0.00 0.36
June 90529991.63 0.429019E+09 113099.64 5036295.65 0.108697E+09 22639.53 0.135787E+09 3103.03 0.36
July 1361009.87 0.950964E+09 126537.92 76826.44 0.158758E+09 0.00 674051.53 541.21 0.36
August 27579346.62 0.707775E+09 23741.66 3033251.60 57589200.71 2495.83 54531454.03 867.34 0.36
September 0.153795E+09 0.197376E+09 232841.91 6332493.91 72095408.81 1432750.28 0.352578E+09 1938.23 0.36
October 0.163461E+09 34330545.35 29024.13 5148864.60 8638466.15 0.218627E+09 0.715784E+09 1985.38 0.35
November 0.100021E+09 0.00 0.00 1035926.67 0.00 0.112194E+10 0.287568E+09 0.00 0.36
December 59501971.55 0.00 0.00 186030.24 0.00 0.146799E+10 39708049.27 0.00 0.36
                   
Annual Sum or Average 0.105345E+10 0.233365E+10 525245.27 38850803.58 0.407585E+09 0.757546E+10 0.351589E+10 8435.19 0.36
Minimum of Months 1361009.87 0.00 0.00 76826.44 0.00 0.00 674051.53 0.00 0.35
Maximum of Months 0.165639E+09 0.950964E+09 232841.91 10852346.59 0.158758E+09 0.154672E+10 0.891953E+09 3103.03 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.206708E+11 0.00 0.00 0.00 0.00 0.618503E+10 0.00 0.00 0.53
February 0.200718E+11 0.00 0.00 0.00 0.00 0.407327E+10 0.00 0.00 0.53
March 0.257624E+11 0.00 0.00 0.00 0.00 0.166097E+09 0.00 0.00 0.53
April 0.253906E+11 0.00 0.00 0.00 4452954.03 0.00 0.00 0.00 0.53
May 0.207629E+11 0.00 0.00 0.00 0.143911E+09 0.00 0.00 0.00 0.53
June 0.532537E+10 56504905.48 0.00 5566.74 0.617479E+10 0.00 13667760.05 0.00 0.54
July 0.200783E+09 0.116338E+10 0.00 203956.24 0.140065E+11 0.00 82204285.80 0.00 0.54
August 0.260660E+10 0.320172E+10 0.00 1398882.71 0.617530E+10 0.00 0.670239E+09 0.00 0.54
September 0.112360E+11 0.492630E+09 0.00 105039.74 0.280655E+10 0.00 56459923.21 0.00 0.53
October 0.226455E+11 0.00 0.00 0.00 0.258504E+09 0.00 0.00 0.00 0.53
November 0.270868E+11 0.00 0.00 0.00 0.00 0.145122E+09 0.00 0.00 0.53
December 0.232967E+11 0.00 0.00 0.00 0.00 0.230382E+10 0.00 0.00 0.53
                   
Annual Sum or Average 0.205056E+12 0.491424E+10 0.00 1713445.43 0.295700E+11 0.128733E+11 0.822571E+09 0.00 0.53
Minimum of Months 0.200783E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.53
Maximum of Months 0.270868E+11 0.320172E+10 0.00 1398882.71 0.140065E+11 0.618503E+10 0.670239E+09 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 13347904.21 0.00 0.00 114433.06 0.00 0.384523E+09 7890619.38 0.00 0.35
February 14645595.90 0.00 0.00 190772.04 0.00 0.342468E+09 14333495.84 0.00 0.35
March 15368691.22 9337.25 0.00 819647.14 3849.98 0.285694E+09 88101808.23 0.00 0.35
April 12885750.39 200923.52 0.00 1775118.20 0.00 0.171574E+09 0.162226E+09 0.00 0.35
May 3306350.33 3713931.78 2322.66 3282736.26 68015.54 30486062.49 0.239653E+09 308.96 0.36
June 0.00 0.134414E+09 32800.54 1779817.79 25952.08 95047.67 55975783.96 1412.78 0.36
July 0.00 0.277254E+09 235031.26 72866.10 0.00 4025.81 451141.92 5609.27 0.36
August 0.00 0.191219E+09 146647.60 967225.54 0.00 64913.17 20256992.64 3604.31 0.36
September 1244931.10 66399770.81 67154.18 2248410.75 964465.44 3628804.71 0.121428E+09 3019.61 0.35
October 4042691.27 10748498.83 2131.26 2216107.10 0.00 68315611.73 0.201213E+09 634.83 0.35
November 17576044.58 0.00 0.00 341755.71 0.00 0.290932E+09 68835893.44 0.00 0.36
December 14667628.20 0.00 0.00 139240.23 0.00 0.366054E+09 11031698.74 0.00 0.36
                   
Annual Sum or Average 97085587.20 0.683960E+09 486087.49 13948129.92 1062283.04 0.194384E+10 0.991397E+09 14589.76 0.35
Minimum of Months 0.00 0.00 0.00 72866.10 0.00 4025.81 451141.92 0.00 0.35
Maximum of Months 17576044.58 0.277254E+09 235031.26 3282736.26 964465.44 0.384523E+09 0.239653E+09 5609.27 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 6963962.72 0.00 0.00 29654.84 0.00 0.396584E+09 2250848.46 0.00 0.35
February 8969617.67 0.00 0.00 52061.77 0.00 0.355201E+09 7371353.87 0.00 0.35
March 22452791.90 0.00 0.00 423092.81 13185.69 0.316913E+09 50149678.37 0.00 0.35
April 27814790.69 200899.97 0.00 1269811.17 0.00 0.186719E+09 0.132616E+09 0.00 0.35
May 42952843.19 3299034.64 1734.68 2594397.79 482782.12 30875333.15 0.200274E+09 584.06 0.36
June 23345696.77 0.107104E+09 48989.15 1120357.93 27303535.72 33225.89 33344590.79 1271.05 0.36
July 349136.51 0.237174E+09 163002.78 14285.51 40121586.40 0.00 164549.95 3396.64 0.36
August 7321129.55 0.176599E+09 111040.74 693107.76 14634460.89 11369.47 13261030.24 2253.16 0.36
September 39263680.53 49732205.96 53486.88 1179382.65 17639719.56 3188423.43 84903180.75 1096.71 0.36
October 41675755.88 8560647.12 10875.31 1047130.74 2176694.71 0.101370E+09 0.131662E+09 1788.11 0.35
November 21807199.35 0.00 0.00 133957.80 0.00 0.332320E+09 23379999.83 0.00 0.36
December 10483937.70 0.00 0.00 24442.29 0.00 0.380012E+09 1325894.61 0.00 0.36
                   
Annual Sum or Average 0.253401E+09 0.582671E+09 389129.54 8581683.06 0.102372E+09 0.210323E+10 0.680703E+09 10389.73 0.36
Minimum of Months 349136.51 0.00 0.00 14285.51 0.00 0.00 164549.95 0.00 0.35
Maximum of Months 42952843.19 0.237174E+09 163002.78 2594397.79 40121586.40 0.396584E+09 0.200274E+09 3396.64 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 71278945.20 0.00 0.00 3159847.89 0.00 0.207266E+10 0.460455E+09 0.00 0.40
February 42550027.68 0.00 0.00 4285746.10 0.00 0.166849E+10 0.672252E+09 0.00 0.40
March 48685910.87 84721.22 0.00 7926029.46 0.00 0.116856E+10 0.128028E+10 0.00 0.40
April 55023010.49 1290830.98 0.00 11342763.04 0.00 0.634223E+09 0.153809E+10 0.00 0.40
May 20576434.18 23151950.65 0.00 17042765.05 1162036.34 29697353.63 0.171052E+10 0.00 0.40
June 0.00 0.863408E+09 250721.00 8709077.70 263794.40 788185.61 0.362164E+09 3969.07 0.40
July 0.00 0.178189E+10 857236.81 435421.57 0.00 38415.97 2918510.17 13627.09 0.40
August 0.00 0.122938E+10 73258.34 5650368.94 0.00 159528.69 0.130962E+09 1421.89 0.40
September 7998046.57 0.426950E+09 85329.20 15137095.17 6196197.96 1614194.05 0.801117E+09 572.39 0.40
October 8657746.68 69071386.89 0.00 19836926.20 0.00 55302820.64 0.168800E+10 0.00 0.40
November 60120801.83 0.00 0.00 7564355.14 0.00 0.109205E+10 0.126671E+10 0.00 0.40
December 64475750.80 0.00 0.00 5041362.98 0.00 0.173990E+10 0.708293E+09 0.00 0.40
                   
Annual Sum or Average 0.379367E+09 0.439523E+10 1266545.36 0.106132E+09 7622028.69 0.846348E+10 0.106218E+11 19590.45 0.40
Minimum of Months 0.00 0.00 0.00 435421.57 0.00 38415.97 2918510.17 0.00 0.40
Maximum of Months 71278945.20 0.178189E+10 857236.81 19836926.20 6196197.96 0.207266E+10 0.171052E+10 13627.09 0.40



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.132606E+11 0.00 0.00 32848928.01 0.00 0.00 0.341929E+11 0.00 4.40
February 0.114792E+11 0.00 0.00 29227590.97 0.00 0.00 0.310014E+11 0.00 4.41
March 0.568110E+10 0.00 0.00 45837921.18 0.00 0.00 0.416950E+11 0.00 4.55
April 0.193819E+10 7773727.92 0.00 59074559.37 0.00 0.00 0.465163E+11 0.00 4.75
May 0.423664E+09 0.262194E+09 0.00 84012542.68 525828.52 0.00 0.421703E+11 0.00 5.03
June 14734953.57 0.128753E+11 0.00 48240842.76 9677607.71 0.00 0.118490E+11 0.00 5.40
July 80023.02 0.327431E+11 0.00 5906396.54 0.00 0.00 0.661193E+09 0.00 5.52
August 9073939.92 0.200547E+11 0.00 35848320.16 17167403.85 0.00 0.751631E+10 0.00 5.48
September 0.220065E+09 0.683340E+10 0.00 61451380.62 18436139.35 0.00 0.233965E+11 0.00 5.17
October 0.137031E+10 0.436646E+09 0.00 65889335.79 15635151.77 0.00 0.429137E+11 0.00 4.87
November 0.575852E+10 0.00 0.00 44026852.83 0.00 0.00 0.441797E+11 0.00 4.59
December 0.101186E+11 0.00 0.00 36862218.97 0.00 0.00 0.352845E+11 0.00 4.46
                   
Annual Sum or Average 0.502741E+11 0.732131E+11 0.00 0.549227E+09 61442131.20 0.00 0.361377E+12 0.00 4.89
Minimum of Months 80023.02 0.00 0.00 5906396.54 0.00 0.00 0.661193E+09 0.00 4.40
Maximum of Months 0.132606E+11 0.327431E+11 0.00 84012542.68 18436139.35 0.00 0.465163E+11 0.00 5.52



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.740375E+10 0.00 0.00 45000189.85 0.00 0.00 0.435547E+11 0.00 4.72
February 0.726165E+10 0.00 0.00 40394776.63 0.00 0.00 0.382887E+11 0.00 4.73
March 0.215831E+10 0.00 0.00 61004961.14 0.00 0.00 0.492538E+11 0.00 4.93
April 0.572569E+09 8263256.90 0.00 74899719.60 0.00 0.00 0.520568E+11 0.00 5.15
May 29775359.28 0.281487E+09 0.00 98764013.42 0.00 0.00 0.461321E+11 0.00 5.44
June 0.00 0.137655E+11 0.00 53444543.70 0.00 0.00 0.126653E+11 0.00 5.76
July 0.00 0.348289E+11 0.00 6399077.77 0.00 0.00 0.696187E+09 0.00 5.86
August 818165.47 0.213110E+11 0.00 39380996.03 0.00 0.00 0.795967E+10 0.00 5.82
September 35292836.67 0.731385E+10 0.00 70057411.21 992665.74 0.00 0.253430E+11 0.00 5.54
October 0.468828E+09 0.474743E+09 0.00 80050549.09 8482736.89 0.00 0.472952E+11 0.00 5.24
November 0.233902E+10 0.00 0.00 57967266.37 0.00 0.00 0.517953E+11 0.00 4.97
December 0.385498E+10 0.00 0.00 50147760.09 0.00 0.00 0.452255E+11 0.00 4.82
                   
Annual Sum or Average 0.241250E+11 0.779837E+11 0.00 0.677511E+09 9475402.63 0.00 0.420266E+12 0.00 5.25
Minimum of Months 0.00 0.00 0.00 6399077.77 0.00 0.00 0.696187E+09 0.00 4.72
Maximum of Months 0.740375E+10 0.348289E+11 0.00 98764013.42 8482736.89 0.00 0.520568E+11 0.00 5.86



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 61582302.35 0.00 0.00 0.103903E+09 0.00 0.00 0.662628E+11 0.00 19.86
February 41060274.96 0.00 0.00 94386395.70 0.00 0.00 0.598314E+11 0.00 20.09
March 0.00 0.00 0.00 0.109291E+09 0.00 0.00 0.663410E+11 0.00 20.66
April 0.00 13973396.11 0.00 0.114936E+09 0.00 0.00 0.652530E+11 0.00 21.21
May 0.00 0.451778E+09 0.00 0.134119E+09 0.00 0.00 0.521647E+11 0.00 21.75
June 0.00 0.180254E+11 0.00 63809856.94 0.00 0.00 0.128415E+11 0.00 22.17
July 0.00 0.423031E+11 0.00 6442106.98 0.00 0.00 0.611436E+09 0.00 22.26
August 0.00 0.268928E+11 0.00 46028305.03 0.00 0.00 0.738795E+10 0.00 22.24
September 0.00 0.934226E+10 0.00 94417571.00 0.00 0.00 0.279627E+11 0.00 21.88
October 0.00 0.808872E+09 0.00 0.120071E+09 0.00 0.00 0.575403E+11 0.00 21.48
November 9945442.39 0.00 0.00 0.104229E+09 0.00 0.00 0.692614E+11 0.00 20.71
December 0.00 0.00 0.00 0.105192E+09 0.00 0.00 0.639454E+11 0.00 20.29
                   
Annual Sum or Average 0.112588E+09 0.978381E+11 0.00 0.109683E+10 0.00 0.00 0.549404E+12 0.00 21.22
Minimum of Months 0.00 0.00 0.00 6442106.98 0.00 0.00 0.611436E+09 0.00 19.86
Maximum of Months 61582302.35 0.423031E+11 0.00 0.134119E+09 0.00 0.00 0.692614E+11 0.00 22.26



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.105575E+11 0.00 0.00 0.00 0.00 0.455817E+10 0.00 0.00 1.12
February 0.929729E+10 0.00 0.00 0.00 0.00 0.429270E+10 0.00 0.00 1.12
March 0.143706E+11 0.00 0.00 0.00 0.00 0.223164E+09 0.00 0.00 1.12
April 0.142911E+11 0.00 0.00 0.00 2506333.60 0.00 0.00 0.00 1.13
May 0.116375E+11 50504747.53 0.00 32558.48 31312769.38 0.00 48768518.26 0.00 1.13
June 0.287369E+10 0.130628E+10 0.00 428310.05 0.222281E+10 0.00 0.130963E+09 0.00 1.15
July 74841850.02 0.555767E+10 0.00 295391.67 0.319950E+10 0.00 84271214.85 0.00 1.17
August 0.147190E+10 0.467062E+10 0.00 1160338.14 0.923788E+09 0.00 0.371674E+09 0.00 1.19
September 0.616055E+10 0.570290E+09 0.00 536595.46 0.130659E+10 0.00 0.195141E+09 0.00 1.14
October 0.127460E+11 15575176.02 0.00 0.00 0.129923E+09 0.00 0.00 0.00 1.13
November 0.149264E+11 0.00 0.00 0.00 0.00 0.401021E+09 0.00 0.00 1.13
December 0.133302E+11 0.00 0.00 0.00 0.00 0.107905E+10 0.00 0.00 1.13
                   
Annual Sum or Average 0.111738E+12 0.121709E+11 0.00 2453193.80 0.781643E+10 0.105541E+11 0.830817E+09 0.00 1.14
Minimum of Months 74841850.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.12
Maximum of Months 0.149264E+11 0.555767E+10 0.00 1160338.14 0.319950E+10 0.455817E+10 0.371674E+09 0.00 1.19



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 09:02:50

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.140071E+12 0.521943E+10 0.251524E+12 0.107288E+13 0.695501E+11
February 0.231559E+12 0.499891E+10 0.238527E+12 0.102677E+13 0.651638E+11
March 0.415371E+12 0.427753E+10 0.205334E+12 0.894034E+12 0.763073E+11
April 0.442917E+12 0.304546E+10 0.141160E+12 0.617825E+12 0.156476E+12
May 0.571535E+12 0.217809E+10 0.880564E+11 0.391581E+12 0.330312E+12
June 0.567902E+12 -726308702.9 -0.168530E+11 -0.844543E+11 0.930143E+12
July 0.540045E+12 -0.289151E+10 -0.109499E+12 -0.530925E+12 0.139341E+13
August 0.515234E+12 -0.150025E+10 -0.684024E+11 -0.316397E+12 0.119851E+13
September 0.354036E+12 0.556486E+09 0.276516E+11 0.115493E+12 0.694664E+12
October 0.340982E+12 0.242687E+10 0.102690E+12 0.474240E+12 0.338819E+12
November 0.165400E+12 0.369877E+10 0.179500E+12 0.785909E+12 0.918506E+11
December 0.112589E+12 0.472246E+10 0.233153E+12 0.997877E+12 0.622423E+11
           
Annual Sum or Average 0.439764E+13 0.260059E+11 0.127284E+13 0.544483E+13 0.540745E+13
Minimum of Months 0.112589E+12 -0.289151E+10 -0.109499E+12 -0.530925E+12 0.622423E+11
Maximum of Months 0.571535E+12 0.521943E+10 0.251524E+12 0.107288E+13 0.139341E+13