Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2023-10-16 09:02:45
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 13449.05 | 1185.43 | 1185.43 |
Net Site Energy | 13449.05 | 1185.43 | 1185.43 |
Total Source Energy | 24226.25 | 2135.36 | 2135.36 |
Net Source Energy | 24226.25 | 2135.36 | 2135.36 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 4924.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 353.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 543.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 173.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 641.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 526.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 89.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 210.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 322.88 | 2104.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 43.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4631.53 | 8817.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 4924.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 353.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 543.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 173.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 952.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 22.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 526.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 89.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 210.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.75 | 2104.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Other | 232.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 20.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 4924.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 353.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 543.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 173.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 641.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 526.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 89.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 210.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 322.88 | 2104.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 43.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 63.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 113.92 | 619.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 231.19 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 408.23 | 777.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 63.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 113.92 | 619.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 231.19 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 408.23 | 777.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 4631.532 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 4631.532 | 100.00 |
Total On-Site and Utility Electric Sources | 4631.532 | 100.00 |
Total Electricity End Uses | 4631.532 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 1.45 | 0.02 |
Air to Air Heat Recovery for Heating | 6323.03 | 99.98 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 6324.48 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 78.83 |
Time Setpoint Not Met During Occupied Cooling | 74.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7813.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYSLAUNDRY HPWH TANK | SWHSYS1 HPWH TANK |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| SWHSYS1 HPWH FAN | SWHSYSLAUNDRY HPWH FAN | FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 5.9798 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 8.7295 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 8.7295 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.1656 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 3.6813 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.1344 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 8.3313 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 8.1375 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 3.9719 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 3.9719 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 3.9719 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 3.9719 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 8.3313 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 8.3313 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 10.5594 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 3.9719 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.2589 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.2589 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.9798 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 8.7295 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 8.7295 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.1656 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 3.6813 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.1344 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 8.3313 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 8.1375 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 3.9719 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 3.9719 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 3.9719 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 3.9719 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 3.9719 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 3.9719 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 3.9719 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 3.9719 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 3.9719 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 3.9719 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 8.3313 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 8.3313 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 10.5594 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 3.9719 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.2589 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.2589 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.3293 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 20-JUN-19:19 | 12-JAN-19:19 | - | - | - | - | - | - | - | - | - | - | 03-JAN-21:00 |
Heating | 0.00 | 1065187.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 96934.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 41114.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 87982.85 | 87619.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31569.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 29846.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 7219.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 35373.25 | 186966.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1333.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 341313.13 | 1339773.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1065187.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 96934.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 41114.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58308.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1266.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 29846.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 7219.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3938.56 | 186966.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 429.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 662.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 5337.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1117.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1719.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 547.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5473.02 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2031.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1668.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 283.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 665.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1022.57 | 2281.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 137.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 14668.06 | 9558.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 470.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 98.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 151.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 147.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 25.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 58.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.13 | 201.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1292.88 | 842.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 470.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 98.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 151.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 147.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 25.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 58.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.13 | 201.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1292.88 | 842.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 1.99 | 0.758010 | 0.528000 | 1.05 | 1.00 | 0.500000 | 0.000503 | 0.000080 | 1.05 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.498002 | 0.102627 | 0.528000 | 0.262945 | 0.528000 | 0.500000 | 0.003712 | 0.000044 | 0.262945 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.220806 | 0.268035 | 0.528000 | 0.116585 | 0.714760 | 0.500000 | 0.001421 | 0.000015 | 0.116585 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.170024 | 0.736093 | 0.528000 | 0.089773 | 1.00 | 0.500000 | 0.000518 | 0.000021 | 0.089773 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.091568 | 0.788559 | 0.528000 | 0.048348 | 1.00 | 0.500000 | 0.000483 | 0.000015 | 0.062193 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.31 | 0.071273 | 0.528000 | 1.75 | 0.528000 | 0.500000 | 0.021213 | 0.000102 | 1.75 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.94 | 0.074103 | 0.528000 | 1.03 | 0.528000 | 0.500000 | 0.005142 | 0.000129 | 1.03 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.19 | 0.191976 | 0.528000 | 2.74 | 0.528000 | 0.500000 | 0.001985 | 0.000304 | 2.74 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.38 | 0.860815 | 0.528000 | 0.728015 | 1.00 | 0.500000 | 0.000443 | 0.000143 | 0.728015 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.08 | 0.121288 | 0.528000 | 1.10 | 0.528000 | 0.500000 | 0.003141 | 0.000129 | 1.10 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.19 | 0.115570 | 0.528000 | 1.15 | 0.528000 | 0.500000 | 0.003297 | 0.000133 | 1.15 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.26 | 0.062616 | 0.528000 | 1.19 | 0.528000 | 0.500000 | 0.010944 | 0.000092 | 1.19 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.751230 | 0.418033 | 0.528000 | 0.396650 | 1.00 | 0.500000 | 0.000911 | 0.000104 | 0.422275 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 9144.34 | 0.000080 | 197.63 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4991.84 | 0.000044 | 121.00 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1717.82 | 0.000015 | 39.63 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2384.02 | 0.000021 | 63.64 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1751.55 | 0.000015 | 47.80 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11625.55 | 0.000102 | 246.00 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 14701.85 | 0.000129 | 337.66 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 34796.24 | 0.000304 | 784.70 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 8228.87 | 0.000072 | 235.11 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 8220.80 | 0.000072 | 234.88 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 46821.06 | 0.000410 | 1337.74 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 46702.53 | 0.000409 | 1334.35 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 8213.91 | 0.000072 | 234.68 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 8205.83 | 0.000072 | 234.45 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 16348.48 | 0.000143 | 413.62 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 2656.84 | 0.000023 | 75.91 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 2654.05 | 0.000023 | 75.83 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 12794.04 | 0.000112 | 365.54 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 14785.70 | 0.000129 | 336.20 |
DINING_FLR_6 VAV BOX REHEAT COIL | 15247.25 | 0.000133 | 345.80 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 10553.29 | 0.000092 | 228.40 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 11893.18 | 0.000104 | 324.59 |
VAV WITH REHEAT HEATING COIL | 459648.76 | 0.004021 | 6038.21 |
FLR_3_DOAS HEATING COIL | 42957.20 | 0.000376 | 564.31 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.17 | 0.000072 | 0.000456 |
ROOM_2_FLR_3 FAN COIL | 1.05 | 0.000072 | 0.000410 |
ROOM_3_MULT19_FLR_3 FAN COIL | 8.68 | 0.000410 | 0.003336 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.41 | 0.000409 | 0.002229 |
ROOM_5_FLR_3 FAN COIL | 1.10 | 0.000072 | 0.000431 |
ROOM_6_FLR_3 FAN COIL | 0.999387 | 0.000072 | 0.000391 |
ROOM_1_FLR_6 FAN COIL | 0.305479 | 0.000023 | 0.000119 |
ROOM_2_FLR_6 FAN COIL | 0.271079 | 0.000023 | 0.000106 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.83 | 0.000112 | 0.000721 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.17 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.05 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 8.68 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.41 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.10 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.999387 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.305479 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.271079 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.83 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008557 | 12.80 | 0.008500 | 0.000456 | 1.17 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008563 | 12.80 | 0.008500 | 0.000410 | 1.05 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008495 | 12.80 | 0.008495 | 0.003336 | 8.68 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008754 | 12.80 | 0.008500 | 0.002229 | 5.41 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008560 | 12.80 | 0.008500 | 0.000431 | 1.10 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008567 | 12.80 | 0.008500 | 0.000391 | 0.999387 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008555 | 12.80 | 0.008500 | 0.000119 | 0.305479 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008561 | 12.80 | 0.008500 | 0.000106 | 0.271079 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008587 | 12.80 | 0.008500 | 0.000721 | 1.83 | |
VAV WITH REHEAT COOLING COIL | 25.80 | 6.70 | 0.008246 | 10.95 | 0.008246 | 0.014083 | 21.95 | 394291.27 |
FLR_3_DOAS COOLING COIL | 27.40 | 6.70 | 0.007007 | 11.91 | 0.007007 | 0.001369 | 2.05 | 38332.30 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.66 | 11.66 | 22.08 | 11.66 | 21.95 | 21.95 | 0.300000 | 0.531061 | 21.95 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 21.95 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 21.95 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.014083 | 0.000034 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.004021 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001369 | 0.000348 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000376 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Size Rated Evaporator Air Flow Rate [m3/s] | Design Size Rated Condenser Water Flow Rate [m3/s] | |
SWHSYSLAUNDRY HPWH DXCOIL | 4.90 | 0.004370 |
SWHSYS1 HPWH DXCOIL | 3.87 | 0.003451 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
SWHSYSLAUNDRY HPWH FAN | 4.90 | 700.51 |
SWHSYS1 HPWH FAN | 3.87 | 553.22 |
Condenser water flow rate [m3/s] | Evaporator air flow rate [m3/s] | |
SWHSYS1 HPWH | 0.003451 | 3.87 |
SWHSYSLAUNDRY HPWH | 0.004370 | 4.90 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.023651 | 4825.41 | |
HEATSYS1 PUMP | 0.006973 | 2079.14 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.006973 | 0.836748 |
COOLSYS1 | 0.023651 | 2.84 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 797044.99 | 797044.99 | 0.006973 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.023651 | 3340.80 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.023651 | 662174.77 | 662787.61 | 75.56 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 HPWH TANK | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 5.980 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 11.360 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 8.730 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 19.490 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 8.730 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 19.490 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.166 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 9.546 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 3.681 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.371 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.134 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.664 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 8.331 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 13.711 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 8.138 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.208 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 3.972 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.492 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 3.972 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.492 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 3.972 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.972 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 3.972 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.492 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 8.331 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 76.151 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 8.331 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 76.151 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 10.559 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2942.062 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 3.972 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.972 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 11832.934 | 5.980 | 111.108 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11832.934 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 585.501 | 8.730 | 54.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 585.501 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 678.012 | 8.730 | 54.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 678.012 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 684.177 | 4.166 | 257.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 684.177 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 348.833 | 3.681 | 170.996 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 348.833 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 400.685 | 5.134 | 47.701 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 400.685 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1573.457 | 8.331 | 11.057 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1573.457 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 10645.380 | 8.138 | 25.200 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10645.380 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 154.991 | 3.972 | 103.327 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.991 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 154.973 | 3.972 | 103.315 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.973 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 97.406 | 3.972 | 64.937 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 97.406 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 97.432 | 3.972 | 64.955 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 97.432 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 154.991 | 3.972 | 103.327 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.991 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 154.973 | 3.972 | 103.315 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.973 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1546.669 | 3.972 | 73.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1546.669 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 154.991 | 3.972 | 103.327 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.991 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 154.973 | 3.972 | 103.315 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.973 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 97.432 | 3.972 | 64.955 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 97.432 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 2763.123 | 8.331 | 11.057 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2763.123 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 2763.123 | 8.331 | 11.057 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2763.123 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1090.832 | 10.559 | 49.053 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1090.832 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1636.910 | 3.972 | 73.801 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1636.910 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.4612 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 0.7186 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 0.7793 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.7186 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.7793 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1593 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1593 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.001 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.224 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.116 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.224 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.116 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.019 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.019 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
21 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
22 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
23 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
24 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
25 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
26 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
27 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
28 | 9 | 0.25591529E-14 | -0.24546362E-15 | -0.17137767E-09 | -0.37498604E-16 |
29 | 8 | 0.24911362E-07 | 0.63119435E-13 | 0.40899073E-03 | -0.28325075E-09 |
30 | 7 | -0.13170143E-01 | 0.31867977E-08 | -0.24422099E-01 | 0.14974934E-03 |
31 | 6 | 0.43057861 | 0.10968744E-05 | 0.49352007 | -0.50451440E-02 |
32 | 5 | -5.4367214 | 0.40580651E-04 | -4.6055917 | 0.66236131E-01 |
33 | 4 | 34.091430 | 0.32920396E-03 | 22.082094 | -0.43657653 |
34 | 3 | -113.54160 | 0.71214000E-03 | -56.892505 | 1.5486472 |
35 | 2 | 199.42519 | 0.39791500E-03 | 79.039217 | -2.9371477 |
36 | 1 | -172.01159 | 0.42217157E-04 | -55.595148 | 2.7604334 |
37 | 0 | 57.057407 | 0.23866585E-06 | 15.503950 | |
38 | 9 | -0.21110570E-14 | 0.25818275E-16 | -0.15956385E-09 | 0.44477997E-16 |
39 | 8 | 0.23256408E-07 | 0.97708352E-13 | 0.39215884E-03 | -0.26443334E-09 |
40 | 7 | -0.12669733E-01 | 0.50004454E-08 | -0.23702159E-01 | 0.14405949E-03 |
41 | 6 | 0.41698408 | 0.17322868E-05 | 0.48198684 | -0.48848961E-02 |
42 | 5 | -5.3040865 | 0.64447408E-04 | -4.5172119 | 0.64591488E-01 |
43 | 4 | 33.504945 | 0.52547767E-03 | 21.737094 | -0.42878933 |
44 | 3 | -112.29434 | 0.11419067E-02 | -56.210653 | 1.5306265 |
45 | 2 | 198.18968 | 0.64065682E-03 | 78.413072 | -2.9175266 |
46 | 1 | -171.55547 | 0.68228399E-04 | -55.411591 | 2.7524393 |
47 | 0 | 57.057407 | 0.38731579E-06 | 15.533056 | |
48 | 9 | -0.39522740E-14 | 0.27297438E-16 | -0.15675654E-09 | 0.81247232E-16 |
49 | 8 | 0.22861200E-07 | 0.10569610E-12 | 0.38808057E-03 | -0.25993968E-09 |
50 | 7 | -0.12548287E-01 | 0.54308815E-08 | -0.23527375E-01 | 0.14267860E-03 |
51 | 6 | 0.41368451 | 0.18844470E-05 | 0.47918278 | -0.48460020E-02 |
52 | 5 | -5.2718908 | 0.70206097E-04 | -4.4957024 | 0.64192273E-01 |
53 | 4 | 33.362562 | 0.57315507E-03 | 21.653080 | -0.42689883 |
54 | 3 | -111.99148 | 0.12469212E-02 | -56.044585 | 1.5262507 |
55 | 2 | 197.88960 | 0.70028077E-03 | 78.260657 | -2.9127612 |
56 | 1 | -171.44467 | 0.74647904E-04 | -55.367071 | 2.7504973 |
57 | 0 | 57.057407 | 0.42420572E-06 | 15.540246 | |
58 | 9 | -0.21110570E-14 | 0.25818275E-16 | -0.15956385E-09 | 0.44477997E-16 |
59 | 8 | 0.23256408E-07 | 0.97708352E-13 | 0.39215884E-03 | -0.26443334E-09 |
60 | 7 | -0.12669733E-01 | 0.50004454E-08 | -0.23702159E-01 | 0.14405949E-03 |
61 | 6 | 0.41698408 | 0.17322868E-05 | 0.48198684 | -0.48848961E-02 |
62 | 5 | -5.3040865 | 0.64447408E-04 | -4.5172119 | 0.64591488E-01 |
63 | 4 | 33.504945 | 0.52547767E-03 | 21.737094 | -0.42878933 |
64 | 3 | -112.29434 | 0.11419067E-02 | -56.210653 | 1.5306265 |
65 | 2 | 198.18968 | 0.64065682E-03 | 78.413072 | -2.9175266 |
66 | 1 | -171.55547 | 0.68228399E-04 | -55.411591 | 2.7524393 |
67 | 0 | 57.057407 | 0.38731579E-06 | 15.533056 | |
68 | 9 | -0.39522740E-14 | 0.27297438E-16 | -0.15675654E-09 | 0.81247232E-16 |
69 | 8 | 0.22861200E-07 | 0.10569610E-12 | 0.38808057E-03 | -0.25993968E-09 |
70 | 7 | -0.12548287E-01 | 0.54308815E-08 | -0.23527375E-01 | 0.14267860E-03 |
71 | 6 | 0.41368451 | 0.18844470E-05 | 0.47918278 | -0.48460020E-02 |
72 | 5 | -5.2718908 | 0.70206097E-04 | -4.4957024 | 0.64192273E-01 |
73 | 4 | 33.362562 | 0.57315507E-03 | 21.653080 | -0.42689883 |
74 | 3 | -111.99148 | 0.12469212E-02 | -56.044585 | 1.5262507 |
75 | 2 | 197.88960 | 0.70028077E-03 | 78.260657 | -2.9127612 |
76 | 1 | -171.44467 | 0.74647904E-04 | -55.367071 | 2.7504973 |
77 | 0 | 57.057407 | 0.42420572E-06 | 15.540246 | |
78 | 7 | -0.19147387E-14 | -0.13717675E-16 | -0.22389416E-13 | 0.54853152E-15 |
79 | 6 | 0.20210758E-10 | 0.18951096E-11 | 0.52387441E-09 | -0.18662741E-10 |
80 | 5 | -0.57595736E-07 | 0.92592455E-08 | -0.21946623E-05 | 0.17180500E-06 |
81 | 4 | 0.51775713E-04 | 0.34884876E-05 | 0.17695789E-02 | -0.28269358E-03 |
82 | 3 | -0.72897754E-02 | 0.12323952E-03 | -0.21573936 | 0.43368638E-01 |
83 | 2 | 0.10317303 | 0.53116266E-03 | 2.9018940 | -0.61935487 |
84 | 1 | -0.26095493 | 0.34096303E-03 | -7.1391298 | 1.5699863 |
85 | 0 | 0.16602045 | 0.17146927E-05 | 4.4522066 | |
86 | 7 | -0.22389416E-13 | -0.13717675E-16 | -0.19147387E-14 | 0.54853152E-15 |
87 | 6 | 0.52387441E-09 | 0.18951096E-11 | 0.20210758E-10 | -0.18662741E-10 |
88 | 5 | -0.21946623E-05 | 0.92592455E-08 | -0.57595736E-07 | 0.17180500E-06 |
89 | 4 | 0.17695789E-02 | 0.34884876E-05 | 0.51775713E-04 | -0.28269358E-03 |
90 | 3 | -0.21573936 | 0.12323952E-03 | -0.72897754E-02 | 0.43368638E-01 |
91 | 2 | 2.9018940 | 0.53116266E-03 | 0.10317303 | -0.61935487 |
92 | 1 | -7.1391298 | 0.34096303E-03 | -0.26095493 | 1.5699863 |
93 | 0 | 4.4522066 | 0.17146927E-05 | 0.16602045 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
103 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
104 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
105 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
106 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
107 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
108 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
109 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
110 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
111 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
112 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
113 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
114 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
115 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
116 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
117 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
118 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
119 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
120 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
121 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
122 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
123 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
124 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
125 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
126 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
127 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
128 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
129 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
130 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
131 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
132 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
133 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.2648_SHGC_0.4 | 37 | 1 | VerySmooth | 1.504 | 1.504 | 1.000 | 0.401 | ||
2 | RESWINDOW_U_0.2648_SHGC_0.4 | 38 | 1 | VerySmooth | 1.504 | 1.504 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 4.45658E-002 | 0.31435 | 0.49128 | 0.49128 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 9.09678E-002 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 4.45658E-002 | 0.31435 | 0.49128 | 0.49128 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 9.09678E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | "DX Coil Total Cooling Rate {W | HPWH Only}" | |
1 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | 1.1400 | 77279.0 | 48.891 | 1.7251 | 76621 | |
2 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | 2.8400 | 62811.3 | 4.643 | 9.4092 | 53264 |
Node Number | Height {m} | Volume {m3} | Maximum Capacity {W} | Off-Cycle UA {W/K} | On-Cycle UA {W/K} | Number Of Inlets | Number Of Outlets | |
1 | 1 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 0 | 1 |
2 | 2 | 0.2683 | 0.4733 | 93813.000 | 1.5573 | 1.5573 | 0 | 0 |
3 | 3 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
4 | 4 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
5 | 5 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 1 |
6 | 6 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 2 | 0 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 9.802E-003 | 1.461E-004 | 7.212E-005 | 0.133 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 3.784E-003 | 4.872E-005 | 1.327E-004 | 4.426E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 8.942E-003 | 5.445E-005 | 1.424E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 5.159E-003 | 5.445E-005 | 1.182E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 1.221E-002 | 1.565E-004 | 1.392E-004 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 2.167E-002 | 1.147E-004 | 6.318E-005 | 0.104 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 6.191E-002 | 4.733E-005 | 9.051E-005 | 4.300E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.587E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.588E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 6.879E-003 | 1.766E-005 | 1.424E-004 | 2.086E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 2.910E-003 | 1.186E-004 | 6.472E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1.243E-002 | 1.204E-004 | 6.523E-005 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1.217E-002 | 2.953E-005 | 2.446E-005 | 3.488E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1484 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.0897E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1754 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 0.1106 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 8.1388E-002 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.3320E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 4.2003E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.3948E-002 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1656 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1086 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1956 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1315 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 9.0045E-002 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.1905E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 4.7151E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.9061E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.8864E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.7906E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.8983E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.2006E-002 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.3418E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3128E-002 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 4.1343E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.4653E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.8864E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.7906E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.8983E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.2006E-002 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.3418E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3128E-002 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 4.1343E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.4653E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 26952.53364 | 26952.53364 | 1.98925 | 1.98925 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 23.23500 | 7.00086E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 3684.91068 | 3684.91068 | 0.16044 | 0.85446 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 6746.99877 | 6746.99877 | 0.49800 | 0.49800 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 27.40000 | 7.00714E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 3625.65408 | 3625.65408 | 0.15786 | 0.15786 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 2991.40165 | 2991.40165 | 0.22081 | 0.22081 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 26.99200 | 7.00652E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1112.06840 | 1112.06840 | 4.84190E-002 | 9.17347E-002 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2303.92771 | 2303.92771 | 0.17002 | 0.17002 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 27.19600 | 7.00683E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1917.64506 | 1917.64506 | 8.34934E-002 | 8.34934E-002 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1240.78928 | 1240.78928 | 9.15678E-002 | 9.15678E-002 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 27.29800 | 7.00699E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1428.41587 | 1428.41587 | 6.21926E-002 | 6.21926E-002 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44859.99852 | 44859.99852 | 3.31085 | 3.31085 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 27.40000 | 7.00714E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2544.80233 | 2544.80233 | 0.11080 | 0.11080 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 26290.46501 | 26290.46501 | 1.94207 | 1.94207 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 27.40000 | 7.00714E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 9373.75289 | 9373.75289 | 0.40812 | 0.67639 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 70327.33695 | 70327.33695 | 5.19250 | 5.19250 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 27.40000 | 7.00714E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 20550.74038 | 20550.74038 | 0.89477 | 1.89399 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11749.46858 | 11749.46858 | 1.16850 | 1.16850 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 25.46200 | 7.00420E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 8228.87148 | 8228.87148 | 0.36038 | 0.36038 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10541.79873 | 10541.79873 | 1.04840 | 1.04840 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 24.95200 | 7.00344E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 8220.79651 | 8220.79651 | 0.36003 | 0.36003 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 87286.87554 | 87286.87554 | 8.68045 | 8.68045 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 27.40000 | 7.00714E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 46821.06207 | 46821.06207 | 2.05054 | 2.05054 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 54443.26328 | 54443.26328 | 5.41467 | 5.41467 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:30:00 | 20.92300 | 6.99743E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 46702.52641 | 46702.52641 | 2.04535 | 2.04535 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 11091.40700 | 11091.40700 | 1.10306 | 1.10306 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | 24.54400 | 7.00282E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 8213.90820 | 8213.90820 | 0.35972 | 0.35972 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 10048.97886 | 10048.97886 | 0.99939 | 0.99939 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 22.36800 | 6.99957E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 8205.83432 | 8205.83432 | 0.35937 | 0.35937 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 18682.24000 | 18682.24000 | 1.37882 | 1.37882 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40000 | 7.00714E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 12565.30312 | 12565.30312 | 0.54709 | 0.54709 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3071.63590 | 3071.63590 | 0.30548 | 0.30548 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 25.46200 | 7.00420E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2656.84397 | 2656.84397 | 0.11636 | 0.11636 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2725.73646 | 2725.73646 | 0.27108 | 0.27108 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.69700 | 7.00305E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2654.04864 | 2654.04864 | 0.11623 | 0.11623 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 18418.69522 | 18418.69522 | 1.83181 | 1.83181 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 27.40000 | 7.00714E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 12794.03728 | 12794.03728 | 0.56031 | 0.56031 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 28197.29377 | 28197.29377 | 2.08366 | 2.08366 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 27.40000 | 7.00714E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 9068.35542 | 9068.35542 | 0.39483 | 1.18780 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 29592.78696 | 29592.78696 | 2.18675 | 2.18675 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 27.40000 | 7.00714E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 9247.02823 | 9247.02823 | 0.40261 | 1.18780 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30558.18283 | 30558.18283 | 2.26115 | 2.26115 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.48200 | 7.00575E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 4355.05815 | 4355.05815 | 0.18960 | 0.36735 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -41.90000 | 6.45023E-005 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10178.88996 | 10178.88996 | 0.75123 | 0.75123 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40000 | 7.00714E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 9698.61125 | 9698.61125 | 0.42228 | 0.42228 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 339931.11 | 21.94942 | 21.94942 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 533529.62 | 7.64323 | 7.64323 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 35674.24 | 18.87691 | 2.05125 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 143185.63 | 6.32829 | 2.05125 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.98925 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.75801 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52800 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.05032 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.02632E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.99987E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.05032 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9144.34345 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.99987E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 197.63057 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.49800 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10263 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52800 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26295 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52800 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.71248E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.36708E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26295 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4991.84305 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.36708E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 120.99668 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22081 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26804 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52800 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11659 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71476 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.42146E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.50282E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11659 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1717.82109 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.50282E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 39.63031 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.17002 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.73609 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52800 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.97725E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.17598E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.08565E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.97725E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2384.02109 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.08565E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 63.64146 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.15678E-002 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.78856 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52800 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.83478E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.83160E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.53233E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.21926E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1751.54603 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.53233E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 47.80311 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.31085 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.12729E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52800 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.74813 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52800 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.12126E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.01705E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.74813 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11625.54926 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.01705E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 245.99818 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.94207 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.41028E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52800 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.02541 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52800 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.14150E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.28618E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.02541 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14701.84752 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.28618E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 337.65962 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.19250 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19198 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52800 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.74164 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52800 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.98462E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.04413E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.74164 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 34796.24390 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.04413E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 784.69533 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.16850 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.16850 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.19898E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.56190E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69218 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55703E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.56190E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.16850 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8228.87148 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.19898E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 235.11019 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.04840 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.04840 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.19191E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.10007E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69216 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56330E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.10007E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.04840 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8220.79651 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.19191E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 234.87950 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.68045 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 8.68045 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.09611E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.33575E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69259 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.49502E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.49502E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.33575E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.68045 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 46821.06207 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.09611E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1337.73918 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.41467 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.41467 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.08574E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.22873E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69166 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.75430E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.22873E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.41467 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 46702.52641 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.08574E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1334.35277 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.10306 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.10306 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.18589E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.31033E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69217 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56034E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.31033E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.10306 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8213.90820 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.18589E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 234.68271 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.99939 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.99939 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.17882E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.91184E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69216 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56650E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.91184E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.99939 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8205.83432 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.17882E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 234.45205 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.37882 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.86082 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52800 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.72801 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.42604E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.43024E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.72801 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16348.47664 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.43024E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 413.62044 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.30548 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.30548 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.32432E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.19179E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69218 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55455E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.19179E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.30548 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2656.84397 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.32432E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 75.90817 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.27108 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.27108 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.32188E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.05959E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69217 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56145E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.05959E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.27108 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2654.04864 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.32188E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 75.82831 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.83181 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.83181 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.11928E-004 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 7.21005E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69194 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58683E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.21005E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.83181 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 12794.03728 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.11928E-004 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 365.53532 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.08366 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12129 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52800 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.10017 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52800 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.14129E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.29352E-004 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.10017 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14785.69773 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.29352E-004 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 336.19744 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.18675 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11557 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52800 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.15460 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52800 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.29670E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.33390E-004 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.15460 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15247.24537 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.33390E-004 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 345.79543 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.26115 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.26161E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52800 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.19389 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52800 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09441E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.23248E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.19389 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10553.28807 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.23248E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 228.39830 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75123 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.41803 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52800 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.39665 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.11411E-004 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.04047E-004 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42228 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11893.17660 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.04047E-004 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 324.59368 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.65648 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.65648 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.07667 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.65648 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.94942 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 21.94942 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.53106 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 21.94942 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.94942 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.80121 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.94724 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.24626E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.24626E-003 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 394291.27207 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.40832E-002 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 21.94942 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 459648.76358 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.02121E-003 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6038.20739 |
350 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 21.94942 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.40832E-002 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.38127E-005 |
353 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.02121E-003 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
356 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.40000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.91318 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00714E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00714E-003 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 38332.29647 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.36914E-003 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 42957.20027 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.75808E-004 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 564.31020 |
368 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.36914E-003 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.47802E-004 |
371 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.75808E-004 |
372 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 4.90359 |
373 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 4.36989E-003 |
374 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.90359 |
375 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Electric Power Consumption [W] | 700.51236 |
376 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 3.87257 |
377 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 3.45109E-003 |
378 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.87257 |
379 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Electric Power Consumption [W] | 553.22422 |
380 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Condenser water flow rate [m3/s] | 3.45109E-003 |
381 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Evaporator air flow rate [m3/s] | 3.87257 |
382 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.36513E-002 |
383 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 4825.41224 |
384 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 6.97290E-003 |
385 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.83675 |
386 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 6.97290E-003 |
387 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 2079.13906 |
388 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
389 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 797044.99254 |
390 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 797044.99000 |
391 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 6.97290E-003 |
392 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.36513E-002 |
393 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 2.83816 |
394 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.36513E-002 |
395 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3340.79565 |
396 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.36513E-002 |
397 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 662174.77459 |
398 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 662787.61000 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 75.55779 |
400 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
401 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
402 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
403 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
404 | WaterHeater:Stratified | SWHSYS1 HPWH TANK | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
405 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Condenser water flow rate [m3/s] | 4.36989E-003 |
406 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Evaporator air flow rate [m3/s] | 4.90359 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 9190.11 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 5013.55 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1725.78 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2393.27 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1758.19 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11684.85 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 14770.22 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 34961.01 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 8862.39 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 8853.69 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 50425.80 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 50298.14 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 8846.28 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 8837.58 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 16416.58 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2861.35 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2858.34 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 13778.86 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 14855.14 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 15319.04 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 10606.05 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 11938.31 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 244148.45 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 22817.28 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 19278.34 | 15552.83 | 3725.51 | 0.81 | 2215.77 | 22.47 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 17316.37 | 13963.76 | 3352.60 | 0.81 | 1989.90 | 20.18 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 141778.63 | 114851.96 | 26926.67 | 0.81 | 16335.06 | 165.68 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 92449.79 | 73584.28 | 18865.51 | 0.80 | 10570.17 | 107.21 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 18209.48 | 14687.05 | 3522.43 | 0.81 | 2092.72 | 21.23 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 16516.37 | 13315.61 | 3200.76 | 0.81 | 1897.79 | 19.25 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5037.64 | 4064.84 | 972.80 | 0.81 | 579.05 | 5.87 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4475.91 | 3609.81 | 866.10 | 0.81 | 514.38 | 5.22 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 30383.48 | 24460.25 | 5923.23 | 0.81 | 3489.13 | 35.39 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 516358.10 | 368262.06 | 148096.04 | 0.71 | 66438.35 | 673.85 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 52427.63 | 36468.44 | 15959.19 | 0.70 | 7931.52 | 80.45 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.270 | 0.259 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.270 | 0.259 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.270 | 0.259 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.270 | 0.259 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.461 | 0.431 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.461 | 0.431 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.461 | 0.431 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.461 | 0.431 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.461 | 0.431 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.461 | 0.431 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.461 | 0.431 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.461 | 0.431 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.461 | 0.431 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.461 | 0.431 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.461 | 0.431 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.461 | 0.431 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.461 | 0.431 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.719 | 0.649 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.719 | 0.649 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.719 | 0.649 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.719 | 0.649 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.719 | 0.649 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.719 | 0.649 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.719 | 0.649 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.719 | 0.649 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.719 | 0.649 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.719 | 0.649 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.719 | 0.649 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.719 | 0.649 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.719 | 0.649 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.719 | 0.649 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.779 | 0.698 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.779 | 0.698 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.779 | 0.698 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.779 | 0.698 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.779 | 0.698 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.779 | 0.698 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.779 | 0.698 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.779 | 0.698 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.779 | 0.698 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.779 | 0.698 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.779 | 0.698 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.779 | 0.698 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.779 | 0.698 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2648_SHGC_0.4 | N/A | 1.504 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.6023602003E-002 | 2.0205626143E-002 | Pass | Pass | 2.7654570399E-003 | 4.3658960982E-003 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.8573474247E-003 | 1.5009402197E-003 | Pass | Pass | 2.0289102067E-002 | 4.1616365968E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.8807046290E-003 | 1.5000648758E-002 | Pass | Pass | 3.5870005916E-002 | 0.1010748325 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.3155936051E-004 | 3.4546160005E-004 | Pass | Pass | 0.2096012244 | 1.1949934550 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.3102853624E-004 | 3.4164926397E-004 | Pass | Pass | 1.6870311388E-002 | 3.0510913681E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.6773574660E-002 | 0.2168539989 | Pass | Pass | 1.8896563185E-002 | 5.2403181249E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.5401625808E-003 | 1.8013830636E-003 | Pass | Pass | 0.1059466795 | 0.4437996285 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.7553872651E-002 | 3.1757249291E-002 | Pass | Pass | 2.2992498333E-002 | 7.6263897451E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2641443214E-002 | 0.3475489574 | Pass | Pass | 0.1014939815 | 0.3459495611 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2634160308E-002 | 0.3466754661 | Pass | Pass | 9.9939165784E-002 | 0.3219138354 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.0627085320E-005 | 4.9807810124E-005 | Pass | Pass | 3.6630815217E-002 | 9.5616371389E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.4992611461E-002 | 0.1862588535 | Pass | Pass | 8.8393174792E-002 | 0.2638120784 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2643178371E-002 | 0.3466114184 | Pass | Pass | 0.1036678957 | 0.3615246255 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2623868055E-002 | 0.3458392591 | Pass | Pass | 0.1052650996 | 0.3396538393 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.7120922529E-004 | 3.5758876078E-004 | Pass | Pass | 4.5379588843E-002 | 0.1269718333 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2625380490E-002 | 0.3712304804 | Pass | Pass | 9.2055569136E-002 | 0.3181733453 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2710008415E-002 | 0.3705965285 | Pass | Pass | 9.1600397068E-002 | 0.3188453237 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2632431229E-002 | 0.3478640230 | Pass | Pass | 0.2191643905 | 1.3822379817 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.1865975572E-002 | 9.9330987259E-002 | Pass | Pass | 8.9775914332E-003 | 2.2626490298E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.2795988077E-002 | 7.8883957782E-002 | Pass | Pass | 9.8270932218E-003 | 2.9623450624E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.7225429868E-002 | 0.1155857855 | Pass | Pass | 2.2147161776E-002 | 3.8985035052E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.7985656333E-004 | 6.1213958410E-004 | Pass | Pass | 1.6697451970E-002 | 2.5938290415E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2459.69 | 68.24 | 3076.54 | 13448.97 | 2725.10 | 21778.55 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.261 | 0.270 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.261 | 0.270 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.261 | 0.270 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.261 | 0.270 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.431 | 0.461 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.431 | 0.461 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.431 | 0.461 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.431 | 0.461 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.431 | 0.461 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.431 | 0.461 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.431 | 0.461 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.431 | 0.461 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.431 | 0.461 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.431 | 0.461 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.431 | 0.461 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.431 | 0.461 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.431 | 0.461 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.649 | 0.719 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.649 | 0.719 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.649 | 0.719 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.649 | 0.719 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.649 | 0.719 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.649 | 0.719 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.649 | 0.719 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.649 | 0.719 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.649 | 0.719 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.649 | 0.719 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.649 | 0.719 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.649 | 0.719 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.649 | 0.719 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.649 | 0.719 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.698 | 0.779 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.698 | 0.779 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.698 | 0.779 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.698 | 0.779 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.698 | 0.779 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.698 | 0.779 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.698 | 0.779 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.698 | 0.779 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.698 | 0.779 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.698 | 0.779 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.698 | 0.779 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.698 | 0.779 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.698 | 0.779 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.153 | 0.159 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.153 | 0.159 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.153 | 0.159 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.153 | 0.159 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.153 | 0.159 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.153 | 0.159 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.153 | 0.159 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.153 | 0.159 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.153 | 0.159 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.153 | 0.159 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.153 | 0.159 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.153 | 0.159 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.153 | 0.159 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.153 | 0.159 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.153 | 0.159 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.153 | 0.159 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.2648_SHGC_0.4 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 1.504 | 0.401 | 0.401 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.2648_SHGC_0.4 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 1.504 | 0.401 | 0.401 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.2648_SHGC_0.4 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 1.504 | 0.401 | 0.401 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.2648_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.504 | 0.401 | 0.401 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.2648_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.504 | 0.401 | 0.401 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.2648_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.504 | 0.401 | 0.401 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.2648_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.504 | 0.401 | 0.401 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.2648_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 1.504 | 0.401 | 0.401 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.2648_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 1.504 | 0.401 | 0.401 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.2648_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.504 | 0.401 | 0.401 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.2648_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.504 | 0.401 | 0.401 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.2648_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.504 | 0.401 | 0.401 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.2648_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.504 | 0.401 | 0.401 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.2648_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.504 | 0.401 | 0.401 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.2648_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 1.504 | 0.401 | 0.401 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.2648_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 1.504 | 0.401 | 0.401 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.2648_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.504 | 0.401 | 0.401 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.2648_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.504 | 0.401 | 0.401 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.2648_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.504 | 0.401 | 0.401 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.2648_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.504 | 0.401 | 0.401 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.2648_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.504 | 0.401 | 0.401 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.2648_SHGC_0.4 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 1.504 | 0.401 | 0.401 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.2648_SHGC_0.4 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.504 | 0.401 | 0.401 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.2648_SHGC_0.4 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.504 | 0.401 | 0.401 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.2648_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.504 | 0.401 | 0.401 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.2648_SHGC_0.4 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.504 | 0.401 | 0.401 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.2648_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.504 | 0.401 | 0.401 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.2648_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 1.504 | 0.401 | 0.401 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.2648_SHGC_0.4 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 1.504 | 0.401 | 0.401 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.2648_SHGC_0.4 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.504 | 0.401 | 0.401 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 1.504 | 0.401 | 0.401 | |||||||||||||||||
North Total or Average | 432.95 | 1.504 | 0.401 | 0.401 | |||||||||||||||||
Non-North Total or Average | 780.84 | 1.504 | 0.401 | 0.401 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.9798 | 1978.83 | 11832.93 | LightsWired | LTG_SCH_BASEMENT | 45.99 | 168.00 | 45.94 | 0.0000 | Y | 102.03 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 8.7295 | 67.07 | 585.50 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 5.64 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 8.7295 | 77.67 | 678.01 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 6.53 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.1656 | 164.24 | 684.18 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 7.53 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 3.6813 | 94.76 | 348.83 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 1.68 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.1344 | 78.04 | 400.68 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.41 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 8.3313 | 188.86 | 1573.46 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.29 | 0.0000 | Y | 11.61 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 8.1375 | 1308.19 | 10645.38 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 55.39 | 0.0000 | Y | 110.69 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 3.9719 | 156.09 | 619.96 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 5.55 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 3.9719 | 156.07 | 619.89 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 5.55 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 3.9719 | 1863.81 | 7402.84 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 66.32 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 3.9719 | 1864.32 | 7404.86 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 66.33 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 3.9719 | 156.09 | 619.96 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 5.55 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 3.9719 | 156.07 | 619.89 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 5.55 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 3.9719 | 1557.62 | 6186.67 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 51.06 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 3.9719 | 39.02 | 154.99 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.39 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 3.9719 | 39.02 | 154.97 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.39 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 3.9719 | 220.77 | 876.89 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 7.86 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 8.3313 | 331.66 | 2763.12 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.06 | 0.0000 | Y | 25.45 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 8.3313 | 331.66 | 2763.12 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.06 | 0.0000 | Y | 25.45 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 10.5594 | 103.30 | 1090.83 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.00 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 3.9719 | 412.12 | 1636.91 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 13.51 |
Interior Lighting Total | 5.2589 | 11345.29 | 59663.90 | 350.24 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 10645.38 | 745.18 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 10645.38 | 745.18 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1573.46 | 613.65 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1573.46 | 613.65 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2763.12 | 552.62 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2763.12 | 552.62 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2763.12 | 552.62 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2763.12 | 552.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 11096.45 | AstronomicalClock | - | 83.06 | 83.06 | 173.00 | |
Exterior Lighting Total | 11096.45 | 173.00 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 797044.99 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 662787.61 | 2.96 | 662904.11 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12772.34 | 19278.34 | 15552.83 | 3725.51 | 0.81 | - | 2215.77 | 22.47 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11479.32 | 17316.37 | 13963.76 | 3352.60 | 0.81 | - | 1989.90 | 20.18 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 93393.96 | 141778.63 | 114851.96 | 26926.67 | 0.81 | - | 16335.06 | 165.68 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 62399.55 | 92449.79 | 73584.28 | 18865.51 | 0.80 | - | 10570.17 | 107.21 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12067.99 | 18209.48 | 14687.05 | 3522.43 | 0.81 | - | 2092.72 | 21.23 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10952.32 | 16516.37 | 13315.61 | 3200.76 | 0.81 | - | 1897.79 | 19.25 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3336.76 | 5037.64 | 4064.84 | 972.80 | 0.81 | - | 579.05 | 5.87 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2966.64 | 4475.91 | 3609.81 | 866.10 | 0.81 | - | 514.38 | 5.22 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 20186.60 | 30383.48 | 24460.25 | 5923.23 | 0.81 | - | 3489.13 | 35.39 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 394291.27 | 516358.10 | 368262.06 | 148096.04 | 0.71 | - | 66438.35 | 673.85 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 38332.30 | 52427.63 | 36468.44 | 15959.19 | 0.70 | - | 7931.52 | 80.45 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 9144.34 | 9190.11 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4991.84 | 5013.55 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1717.82 | 1725.78 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2384.02 | 2393.27 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1751.55 | 1758.19 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11625.55 | 11684.85 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 14701.85 | 14770.22 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 34796.24 | 34961.01 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 8228.87 | 8862.39 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 8220.80 | 8853.69 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 46821.06 | 50425.80 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 46702.53 | 50298.14 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 8213.91 | 8846.28 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 8205.83 | 8837.58 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 16348.48 | 16416.58 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2656.84 | 2861.35 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2654.05 | 2858.34 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 12794.04 | 13778.86 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 14785.70 | 14855.14 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 15247.25 | 15319.04 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10553.29 | 10606.05 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11893.18 | 11938.31 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 459648.76 | 244148.45 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 42957.20 | 22817.28 | - |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 75921.46 | 3.40 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 54370.95 | 3.40 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.17 | 822.20 | 703.64 | 1.00 | 1.16 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.05 | 737.69 | 703.64 | 1.00 | 1.19 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 8.68 | 6107.88 | 703.64 | 1.00 | 0.94 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 5.41 | 3809.96 | 703.64 | 1.00 | 0.97 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:30:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.10 | 776.15 | 703.64 | 1.00 | 1.17 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.00 | 703.21 | 703.64 | 1.00 | 1.20 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.31 | 214.95 | 703.64 | 1.00 | 1.70 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.27 | 190.74 | 703.64 | 1.00 | 1.79 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.83 | 1288.93 | 703.64 | 1.00 | 1.08 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 21.95 | 49180.71 | 2240.64 | 1.00 | 1.11 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 4.90 | 700.51 | 142.86 | 0.00 | 2.78 | General | ||
SWHSYS1 HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 3.87 | 553.22 | 142.86 | 0.00 | 2.84 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.023651 | 4825.41 | 204022.71 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.006973 | 2079.14 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.023651 | 3340.80 | 141251.80 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYSLAUNDRY HPWH | WaterHeater:HeatPump:PumpedCondenser | 1.14 | 77279.00 | 0.80 | 48.89 | 1.73 |
SWHSYS1 HPWH | WaterHeater:HeatPump:PumpedCondenser | 2.84 | 62811.31 | 0.80 | 4.64 | 9.41 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 26952.53 | 26952.53 | 13.62 | 1.989 | 1.989 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 24.00 | 24.00 | 0.00940 | 23.23 | 0.00700 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 6747.00 | 6747.00 | 100.59 | 0.498 | 0.498 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00885 | 27.40 | 0.00701 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 2991.40 | 2991.40 | 38.51 | 0.221 | 0.221 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00944 | 26.99 | 0.00701 | 0.092 | 0.00 |
MECH_FLR_1 | 2303.93 | 2303.93 | 14.03 | 0.170 | 0.170 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00874 | 27.20 | 0.00701 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1240.79 | 1240.79 | 13.09 | 0.092 | 0.092 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00885 | 27.30 | 0.00701 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44860.00 | 44860.00 | 574.84 | 3.311 | 3.311 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00854 | 27.40 | 0.00701 | 0.000 | 0.00 |
CAFE_FLR_1 | 26290.47 | 26290.47 | 139.20 | 1.942 | 1.942 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 23.99 | 0.00972 | 27.40 | 0.00701 | 0.676 | 0.00 |
LOBBY_FLR_1 | 70327.34 | 70327.34 | 53.76 | 5.193 | 5.193 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.99 | 0.00985 | 27.40 | 0.00701 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 11749.47 | 11749.47 | 301.10 | 1.169 | 1.169 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 21.11 | 21.11 | 0.00856 | 25.46 | 0.00700 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10541.80 | 10541.80 | 270.18 | 1.048 | 1.048 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 21.11 | 21.11 | 0.00856 | 24.95 | 0.00700 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 87286.88 | 87286.88 | 3559.27 | 8.680 | 8.680 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 21.11 | 21.11 | 0.00850 | 27.40 | 0.00701 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 54443.26 | 54443.26 | 2219.41 | 5.415 | 5.415 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:30:00 | 21.11 | 21.11 | 0.00875 | 20.92 | 0.00700 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 11091.41 | 11091.41 | 284.23 | 1.103 | 1.103 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | 21.11 | 21.11 | 0.00856 | 24.54 | 0.00700 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 10048.98 | 10048.98 | 257.55 | 0.999 | 0.999 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 21.11 | 21.11 | 0.00857 | 22.37 | 0.00700 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 18682.24 | 18682.24 | 47.98 | 1.379 | 1.379 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00952 | 27.40 | 0.00701 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3071.64 | 3071.64 | 78.72 | 0.305 | 0.305 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 21.11 | 21.11 | 0.00855 | 25.46 | 0.00700 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2725.74 | 2725.74 | 69.86 | 0.271 | 0.271 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 21.11 | 21.11 | 0.00856 | 24.70 | 0.00700 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 18418.70 | 18418.70 | 750.85 | 1.832 | 1.832 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 21.11 | 21.11 | 0.00859 | 27.40 | 0.00701 | 0.099 | 0.00 |
BANQUET_FLR_6 | 28197.29 | 28197.29 | 85.02 | 2.084 | 2.084 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 23.98 | 0.01050 | 27.40 | 0.00701 | 1.188 | 0.00 |
DINING_FLR_6 | 29592.79 | 29592.79 | 89.23 | 2.187 | 2.187 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 23.98 | 0.01040 | 27.40 | 0.00701 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30558.18 | 30558.18 | 295.81 | 2.261 | 2.261 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01008 | 26.48 | 0.00701 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10178.89 | 10178.89 | 24.70 | 0.751 | 0.751 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00899 | 27.40 | 0.00701 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 3684.91 | 3684.91 | 1.86 | 0.160 | 0.854 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 3625.65 | 3625.65 | 54.06 | 0.158 | 0.158 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00785 | -41.90 | 0.00006 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1112.07 | 1112.07 | 14.32 | 0.048 | 0.092 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00781 | -41.90 | 0.00006 | 0.092 | 0.00 |
MECH_FLR_1 | 1917.65 | 1917.65 | 11.68 | 0.083 | 0.083 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00774 | -41.90 | 0.00006 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1428.42 | 1428.42 | 15.07 | 0.062 | 0.062 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00780 | -41.90 | 0.00006 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2544.80 | 2544.80 | 32.61 | 0.111 | 0.111 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00773 | -41.90 | 0.00006 | 0.000 | 0.00 |
CAFE_FLR_1 | 9373.75 | 9373.75 | 49.63 | 0.408 | 0.676 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00787 | -41.90 | 0.00006 | 0.676 | 0.00 |
LOBBY_FLR_1 | 20550.74 | 20550.74 | 15.71 | 0.895 | 1.894 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00783 | -41.90 | 0.00006 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 8228.87 | 8228.87 | 210.88 | 0.360 | 0.360 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00784 | -41.90 | 0.00006 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 8220.80 | 8220.80 | 210.70 | 0.360 | 0.360 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00784 | -41.90 | 0.00006 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 46821.06 | 46821.06 | 1909.21 | 2.051 | 2.051 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00785 | -41.90 | 0.00006 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 46702.53 | 46702.53 | 1903.85 | 2.045 | 2.045 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00785 | -41.90 | 0.00006 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 8213.91 | 8213.91 | 210.49 | 0.360 | 0.360 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00784 | -41.90 | 0.00006 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 8205.83 | 8205.83 | 210.31 | 0.359 | 0.359 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00784 | -41.90 | 0.00006 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 12565.30 | 12565.30 | 32.27 | 0.547 | 0.547 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00788 | -41.90 | 0.00006 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2656.84 | 2656.84 | 68.09 | 0.116 | 0.116 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00788 | -41.90 | 0.00006 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2654.05 | 2654.05 | 68.02 | 0.116 | 0.116 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00788 | -41.90 | 0.00006 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 12794.04 | 12794.04 | 521.56 | 0.560 | 0.560 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00788 | -41.90 | 0.00006 | 0.099 | 0.00 |
BANQUET_FLR_6 | 9068.36 | 9068.36 | 27.34 | 0.395 | 1.188 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00791 | -41.90 | 0.00006 | 1.188 | 0.00 |
DINING_FLR_6 | 9247.03 | 9247.03 | 27.88 | 0.403 | 1.188 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00791 | -41.90 | 0.00006 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 4355.06 | 4355.06 | 42.16 | 0.190 | 0.367 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00756 | -41.90 | 0.00006 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9698.61 | 9698.61 | 23.53 | 0.422 | 0.422 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00793 | -41.90 | 0.00006 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 21.95 | 21.95 | 7.64 | 7.64 | 21.9494 | 11.6565 | 21.9494 | 0.5311 | 0.3000 |
FLR_3_DOAS | 18.88 | 2.05 | 6.33 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 9144.343 | 9144.343 | 1.050322 | 0.00008000 | 197.631 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9144.34 | 9144.34 | 1.050322 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00799993 | 50.9126 | 3684.91 | 0.00 | 9195.13 | 9195.13 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4991.843 | 4991.843 | 0.262945 | 0.00004367 | 120.997 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4991.84 | 4991.84 | 0.262945 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00784686 | 49.9524 | 3625.65 | 0.00 | 5017.85 | 5017.85 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1717.821 | 1717.821 | 0.116585 | 0.00001503 | 39.630 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1717.82 | 1717.82 | 0.116585 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00780823 | 49.7084 | 1112.07 | 0.00 | 1727.03 | 1727.03 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2384.021 | 2384.021 | 0.089773 | 0.00002086 | 63.641 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2384.02 | 2384.02 | 0.089773 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00773950 | 49.2763 | 1917.65 | 0.00 | 2395.91 | 2395.91 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1751.546 | 1751.546 | 0.062193 | 0.00001532 | 47.803 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1751.55 | 1751.55 | 0.062193 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00779673 | 49.6362 | 1428.42 | 0.00 | 1760.23 | 1760.23 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11625.549 | 11625.549 | 1.748127 | 0.00010171 | 245.998 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11625.55 | 11625.55 | 1.748127 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00773222 | 49.2317 | 2544.80 | 0.00 | 11690.55 | 11690.55 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 14701.848 | 14701.848 | 1.025412 | 0.00012862 | 337.660 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 14701.85 | 14701.85 | 1.025412 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00786870 | 50.0893 | 9373.75 | 0.00 | 14780.74 | 14780.74 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 34796.244 | 34796.244 | 2.741641 | 0.00030441 | 784.695 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 34796.24 | 34796.24 | 2.741641 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00782973 | 49.8436 | 20550.74 | 0.00 | 34984.18 | 34984.18 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12772.343 | -999.000 | 1.168503 | 0.00045619 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | unknown | 7/21 17:30:00 | 12772.34 | 12599.16 | 1.168503 | 21.69 | 15.45 | 0.00855703 | 12.80 | 11.96 | 0.00850000 | 25.46 | 0.00700420 | 15.45 | 0.0000 | 21.11 | 0.00855703 | 54.0412 | 11749.47 | 0.00 | 12965.74 | 12563.88 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 8228.871 | 8228.871 | 0.360379 | 0.00007199 | 235.110 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8228.87 | 8228.87 | 0.360379 | 21.11 | 14.60 | 0.00784431 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.11 | 0.00784431 | 49.5972 | 8228.87 | 0.00 | 8870.92 | 8870.92 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 11479.319 | -999.000 | 1.048399 | 0.00041001 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | unknown | 7/21 18:00:00 | 11479.32 | 11306.83 | 1.048399 | 21.69 | 15.46 | 0.00856330 | 12.80 | 11.96 | 0.00850000 | 24.95 | 0.00700344 | 15.26 | 0.0000 | 21.11 | 0.00856330 | 54.0803 | 10541.80 | 0.00 | 11652.98 | 11275.58 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 8220.797 | 8220.797 | 0.360025 | 0.00007192 | 234.879 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8220.80 | 8220.80 | 0.360025 | 21.11 | 14.60 | 0.00784417 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.11 | 0.00784417 | 49.5963 | 8220.80 | 0.00 | 8862.22 | 8862.22 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 93393.963 | -999.000 | 8.680452 | 0.00333575 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | 7/21 14:10:00 | 93393.96 | 93393.96 | 8.680452 | 21.69 | 15.40 | 0.00849502 | 12.80 | 11.95 | 0.00849502 | 27.40 | 0.00700714 | 16.15 | 0.0000 | 21.11 | 0.00849502 | 53.6537 | 87286.88 | 0.00 | 94803.83 | 93158.11 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 46821.062 | 46821.062 | 2.050541 | 0.00040961 | 1337.739 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 46821.06 | 46821.06 | 2.050541 | 21.11 | 14.61 | 0.00785475 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.11 | 0.00785475 | 49.6613 | 46821.06 | 0.00 | 50474.54 | 50474.54 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 62399.555 | -999.000 | 5.414674 | 0.00222873 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:30:00 | unknown | 7/21 21:30:00 | 62399.55 | 58795.72 | 5.414674 | 21.69 | 15.62 | 0.00875430 | 12.80 | 11.96 | 0.00850000 | 20.92 | 0.00699743 | 13.74 | 0.0000 | 21.11 | 0.00875430 | 55.2708 | 54443.26 | 0.00 | 63319.47 | 58696.42 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 46702.526 | 46702.526 | 2.045349 | 0.00040857 | 1334.353 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 46702.53 | 46702.53 | 2.045349 | 21.11 | 14.61 | 0.00785435 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.11 | 0.00785435 | 49.6588 | 46702.53 | 0.00 | 50346.75 | 50346.75 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 12067.994 | -999.000 | 1.103058 | 0.00043103 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | unknown | 7/21 10:40:00 | 12067.99 | 11894.99 | 1.103058 | 21.69 | 15.45 | 0.00856034 | 12.80 | 11.96 | 0.00850000 | 24.54 | 0.00700282 | 15.11 | 0.0000 | 21.11 | 0.00856034 | 54.0619 | 11091.41 | 0.00 | 12250.64 | 11861.91 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 8213.908 | 8213.908 | 0.359724 | 0.00007186 | 234.683 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8213.91 | 8213.91 | 0.359724 | 21.11 | 14.60 | 0.00784403 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.11 | 0.00784403 | 49.5954 | 8213.91 | 0.00 | 8854.79 | 8854.79 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10952.324 | -999.000 | 0.999387 | 0.00039118 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | unknown | 7/21 09:20:00 | 10952.32 | 10779.54 | 0.999387 | 21.69 | 15.46 | 0.00856650 | 12.80 | 11.96 | 0.00850000 | 22.37 | 0.00699957 | 14.30 | 0.0000 | 21.11 | 0.00856650 | 54.1003 | 10048.98 | 0.00 | 11117.94 | 10749.95 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 8205.834 | 8205.834 | 0.359370 | 0.00007179 | 234.452 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8205.83 | 8205.83 | 0.359370 | 21.11 | 14.60 | 0.00784389 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.11 | 0.00784389 | 49.5946 | 8205.83 | 0.00 | 8846.09 | 8846.09 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 16348.477 | 16348.477 | 0.728015 | 0.00014302 | 413.620 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 16348.48 | 16348.48 | 0.728015 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00787548 | 50.1308 | 12565.30 | 0.00 | 16432.46 | 16432.46 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3336.763 | -999.000 | 0.305479 | 0.00011918 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | unknown | 7/21 17:30:00 | 3336.76 | 3293.46 | 0.305479 | 21.69 | 15.45 | 0.00855455 | 12.80 | 11.96 | 0.00850000 | 25.46 | 0.00700420 | 15.45 | 0.0000 | 21.11 | 0.00855455 | 54.0258 | 3071.64 | 0.00 | 3387.30 | 3284.19 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2656.844 | 2656.844 | 0.116355 | 0.00002324 | 75.908 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2656.84 | 2656.84 | 0.116355 | 21.11 | 14.63 | 0.00787888 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.11 | 0.00787888 | 49.8129 | 2656.84 | 0.00 | 2864.14 | 2864.14 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2966.637 | -999.000 | 0.271079 | 0.00010596 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | unknown | 7/21 18:10:00 | 2966.64 | 2923.34 | 0.271079 | 21.69 | 15.45 | 0.00856145 | 12.80 | 11.96 | 0.00850000 | 24.70 | 0.00700305 | 15.17 | 0.0000 | 21.11 | 0.00856145 | 54.0687 | 2725.74 | 0.00 | 3011.53 | 2915.23 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2654.049 | 2654.049 | 0.116233 | 0.00002322 | 75.828 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2654.05 | 2654.05 | 0.116233 | 21.11 | 14.63 | 0.00787876 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.11 | 0.00787876 | 49.8122 | 2654.05 | 0.00 | 2861.13 | 2861.13 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 20186.596 | -999.000 | 1.831812 | 0.00072100 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | 7/21 14:10:00 | 20186.60 | 19772.78 | 1.831812 | 21.69 | 15.48 | 0.00858683 | 12.80 | 11.96 | 0.00850000 | 27.40 | 0.00700714 | 16.15 | 0.0000 | 21.11 | 0.00858683 | 54.2275 | 18418.70 | 0.00 | 20491.00 | 19720.83 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 12794.037 | 12794.037 | 0.560312 | 0.00011193 | 365.535 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12794.04 | 12794.04 | 0.560312 | 21.11 | 14.63 | 0.00788410 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.11 | 0.00788410 | 49.8452 | 12794.04 | 0.00 | 13792.32 | 13792.32 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14785.698 | 14785.698 | 1.100173 | 0.00012935 | 336.197 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 14785.70 | 14785.70 | 1.100173 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00791247 | 50.3637 | 9068.36 | 0.00 | 14865.32 | 14865.32 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 15247.245 | 15247.245 | 1.154602 | 0.00013339 | 345.795 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 15247.25 | 15247.25 | 1.154602 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00791414 | 50.3742 | 9247.03 | 0.00 | 15329.43 | 15329.43 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10553.288 | 10553.288 | 1.193887 | 0.00009232 | 228.398 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 10553.29 | 10553.29 | 1.193887 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00756231 | 48.1661 | 4355.06 | 0.00 | 10611.88 | 10611.88 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 11893.177 | 11893.177 | 0.422275 | 0.00010405 | 324.594 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11893.18 | 11893.18 | 0.422275 | 16.70 | 13.04 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00792815 | 50.4620 | 9698.61 | 0.00 | 11952.16 | 11952.16 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 394291.272 | -999.000 | 21.949415 | 0.01408317 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 394291.27 | 394291.26 | 21.949415 | 25.80 | 16.64 | 0.00824626 | 10.95 | 10.93 | 0.00824626 | 27.40 | 0.00700714 | 16.15 | 53.1288 | 23.99 | 0.00963050 | 50.9674 | 297203.00 | 0.00 | 399432.65 | 384628.49 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 459648.764 | 459648.764 | 6.584825 | 0.00402121 | 6038.207 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 459648.76 | 459648.76 | 6.584825 | -41.90 | -41.90 | 0.00006450 | 16.70 | 13.04 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 177.0960 | 21.00 | 0.00786144 | 50.0429 | 88222.39 | 0.00 | 294762.27 | 294762.27 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 38332.296 | -999.000 | 2.051317 | 0.00136914 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38332.30 | 38332.30 | 2.051317 | 27.40 | 16.15 | 0.00700714 | 11.91 | 10.04 | 0.00700714 | 27.40 | 0.00700714 | 16.15 | 99.9965 | 21.11 | 0.00859868 | 54.3003 | 189811.32 | 0.00 | 38851.60 | 38851.60 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 42957.200 | 42957.200 | 0.615395 | 0.00037581 | 564.310 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 42957.20 | 42957.20 | 0.615395 | -41.90 | -41.90 | 0.00006450 | 16.70 | 13.04 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 333.3216 | 21.11 | 0.00785484 | 49.6619 | 144497.93 | 0.00 | 27547.47 | 27547.47 |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 54035.880 | 39770.408 | 4.903586 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 75921.46 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 42290.343 | 31125.692 | 3.872570 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 54370.95 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 9144.343 | 9144.343 | 1.050322 | 0.00008000 | 197.631 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 1.1246 | 1.147281 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9144.34 | 9144.34 | 1.0000 | 1.24509293 | 1.050322 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.07999054 | 60.00 | 32.22 | 27.78 | 0.000 | 9144.34 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00799993 | 21.00 | 0.00799993 | 50.9126 | 3684.91 | 0.00 | 9195.13 | 9195.13 | 1.24509293 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.84 | 15.90 | 0.00800000 | 44319.8 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4991.843 | 4991.843 | 0.262945 | 0.00004367 | 120.997 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 0.6139 | 0.626294 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 4991.84 | 4991.84 | 1.0000 | 0.31170567 | 0.262945 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.04366637 | 60.00 | 32.22 | 27.78 | 0.000 | 4991.84 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00784686 | 21.00 | 0.00784686 | 49.9524 | 3625.65 | 0.00 | 5017.85 | 5017.85 | 0.31170567 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.39 | 18.82 | 0.00800000 | 53032.8 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1717.821 | 1717.821 | 0.116585 | 0.00001503 | 39.630 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 0.2113 | 0.215524 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1717.82 | 1717.82 | 1.0000 | 0.13820501 | 0.116585 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.01502672 | 60.00 | 32.22 | 27.78 | 0.000 | 1717.82 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00780823 | 21.00 | 0.00780823 | 49.7084 | 1112.07 | 0.00 | 1727.03 | 1727.03 | 0.13820501 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.85 | 17.65 | 0.00800000 | 49430.8 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2384.021 | 2384.021 | 0.089773 | 0.00002086 | 63.641 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 0.2932 | 0.299107 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2384.02 | 2384.02 | 1.0000 | 0.10641989 | 0.089773 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.02085433 | 60.00 | 32.22 | 27.78 | 0.000 | 2384.02 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00773950 | 21.00 | 0.00773950 | 49.2763 | 1917.65 | 0.00 | 2395.91 | 2395.91 | 0.10641989 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 38.68 | 20.79 | 0.00800000 | 59448.5 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1751.546 | 1751.546 | 0.062193 | 0.00001532 | 47.803 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 0.2154 | 0.219755 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1751.55 | 1751.55 | 1.0000 | 0.07372554 | 0.062193 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.01532173 | 60.00 | 32.22 | 27.78 | 0.000 | 1751.55 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00779673 | 21.00 | 0.00779673 | 49.6362 | 1428.42 | 0.00 | 1760.23 | 1760.23 | 0.07372554 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60810.2 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11625.549 | 11625.549 | 1.748127 | 0.00010171 | 245.998 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 1.4298 | 1.458581 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11625.55 | 11625.55 | 1.0000 | 2.07229888 | 1.748127 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.10169500 | 60.00 | 32.22 | 27.78 | 0.000 | 11625.55 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00773222 | 21.00 | 0.00773222 | 49.2317 | 2544.80 | 0.00 | 11690.55 | 11690.55 | 2.07229888 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.13 | 15.27 | 0.00800000 | 42576.1 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14701.848 | 14701.848 | 1.025412 | 0.00012862 | 337.660 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 1.8082 | 1.844544 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 14701.85 | 14701.85 | 1.0000 | 1.21556384 | 1.025412 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.12860506 | 60.00 | 32.22 | 27.78 | 0.000 | 14701.85 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00786870 | 21.00 | 0.00786870 | 50.0893 | 9373.75 | 0.00 | 14780.74 | 14780.74 | 1.21556384 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.52 | 17.54 | 0.00800000 | 49094.3 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34796.244 | 34796.244 | 2.741641 | 0.00030441 | 784.695 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 4.2795 | 4.365656 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 34796.24 | 34796.24 | 1.0000 | 3.25004861 | 2.741641 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.30438167 | 60.00 | 32.22 | 27.78 | 0.000 | 34796.24 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00782973 | 21.00 | 0.00782973 | 49.8436 | 20550.74 | 0.00 | 34984.18 | 34984.18 | 3.25004861 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.16 | 17.07 | 0.00800000 | 47698.9 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12772.343 | -999.000 | 1.168503 | 0.00045619 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7471 | 1004.8586 | 1.1854 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.168503 | 1.38518906 | 4197.9300 | 999.8980 | 23.64893600 | 13.37 | 6.70 | 6.67 | 662174.77 | 1.9288 | 1.928812 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | unknown | unknown | unknown | 7/21 17:30:00 | Sensible | 12772.34 | 12599.16 | 1.0000 | 1.38518906 | 1.168503 | 21.69 | 15.45 | 0.00855703 | 43542.8 | 12.80 | 11.96 | 0.00850000 | 34322.2 | 0.45614345 | 6.70 | 13.37 | 6.67 | 0.000 | 12772.34 | 25.46 | 0.00700420 | 15.45 | 0.00000000 | 0.0000 | 21.11 | 0.00855703 | 21.11 | 0.00855703 | 54.0412 | 11749.47 | 0.00 | 12965.74 | 12563.88 | 1.38518906 | 21.69 | 15.61 | 0.00855703 | 43542.8 | 12.81 | 12.04 | 0.00844212 | 34182.6 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8228.871 | 8228.871 | 0.360379 | 0.00007199 | 235.110 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.168503 | 1.38518906 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 1.0121 | 1.032422 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8228.87 | 8228.87 | 1.0000 | 0.42720734 | 0.360379 | 21.11 | 14.60 | 0.00784431 | 41138.5 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.07198241 | 60.00 | 32.22 | 27.78 | 0.000 | 8228.87 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.11 | 0.00784431 | 21.11 | 0.00784431 | 49.5972 | 8228.87 | 0.00 | 8870.92 | 8870.92 | 0.42720734 | 16.60 | 13.00 | 0.00784431 | 36540.5 | 36.97 | 20.15 | 0.00784431 | 57305.5 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11479.319 | -999.000 | 1.048399 | 0.00041001 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7587 | 1004.8586 | 1.1854 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.048399 | 1.24281348 | 4197.9300 | 999.8980 | 23.64893600 | 13.37 | 6.70 | 6.67 | 662174.77 | 1.7336 | 1.733546 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | unknown | unknown | unknown | 7/21 18:00:00 | Sensible | 11479.32 | 11306.83 | 1.0000 | 1.24281348 | 1.048399 | 21.69 | 15.46 | 0.00856330 | 43558.8 | 12.80 | 11.96 | 0.00850000 | 34322.2 | 0.40996518 | 6.70 | 13.37 | 6.67 | 0.000 | 11479.32 | 24.95 | 0.00700344 | 15.26 | 0.00000000 | 0.0000 | 21.11 | 0.00856330 | 21.11 | 0.00856330 | 54.0803 | 10541.80 | 0.00 | 11652.98 | 11275.58 | 1.24281348 | 21.69 | 15.61 | 0.00856330 | 43558.8 | 12.80 | 12.04 | 0.00844302 | 34182.5 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8220.797 | 8220.797 | 0.360025 | 0.00007192 | 234.879 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.048399 | 1.24281348 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 1.0111 | 1.031409 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8220.80 | 8220.80 | 1.0000 | 0.42678812 | 0.360025 | 21.11 | 14.60 | 0.00784417 | 41138.1 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.07191178 | 60.00 | 32.22 | 27.78 | 0.000 | 8220.80 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.11 | 0.00784417 | 21.11 | 0.00784417 | 49.5963 | 8220.80 | 0.00 | 8862.22 | 8862.22 | 0.42678812 | 16.60 | 13.00 | 0.00784417 | 36540.2 | 36.97 | 20.15 | 0.00784417 | 57305.1 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 93393.963 | -999.000 | 8.680452 | 0.00333575 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6318 | 1004.8586 | 1.1854 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.680452 | 10.29014885 | 4197.9300 | 999.8980 | 23.64893600 | 13.37 | 6.70 | 6.67 | 662174.77 | 14.1041 | 14.103862 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | unknown | unknown | 7/21 14:10:00 | Sensible | 93393.96 | 93393.96 | 1.0000 | 10.29014885 | 8.680452 | 21.69 | 15.40 | 0.00849502 | 43385.7 | 12.80 | 11.95 | 0.00849502 | 34309.6 | 3.33541338 | 6.70 | 13.37 | 6.67 | 0.000 | 93393.96 | 27.40 | 0.00700714 | 16.15 | 0.00000000 | 0.0000 | 21.11 | 0.00849502 | 21.11 | 0.00849502 | 53.6537 | 87286.88 | 0.00 | 94803.83 | 93158.11 | 10.29014885 | 21.69 | 15.55 | 0.00849502 | 43385.7 | 12.82 | 12.04 | 0.00843167 | 34172.6 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 46821.062 | 46821.062 | 2.050541 | 0.00040961 | 1337.739 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.680452 | 10.29014885 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 5.7584 | 5.874331 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 46821.06 | 46821.06 | 1.0000 | 2.43079151 | 2.050541 | 21.11 | 14.61 | 0.00785475 | 41165.4 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.40956929 | 60.00 | 32.22 | 27.78 | 0.000 | 46821.06 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.11 | 0.00785475 | 21.11 | 0.00785475 | 49.6613 | 46821.06 | 0.00 | 50474.54 | 50474.54 | 2.43079151 | 16.60 | 13.01 | 0.00785475 | 36567.0 | 36.97 | 20.16 | 0.00785475 | 57331.6 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 62399.555 | -999.000 | 5.414674 | 0.00222873 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1138 | 1004.8586 | 1.1854 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.414674 | 6.41876734 | 4197.9300 | 999.8980 | 23.64893600 | 13.37 | 6.70 | 6.67 | 662174.77 | 9.4234 | 9.423251 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:30:00 | unknown | unknown | unknown | 7/21 21:30:00 | Sensible | 62399.55 | 58795.72 | 1.0000 | 6.41876734 | 5.414674 | 21.69 | 15.62 | 0.00875430 | 44043.6 | 12.80 | 11.96 | 0.00850000 | 34322.2 | 2.22849854 | 6.70 | 13.37 | 6.67 | 0.000 | 62399.55 | 20.92 | 0.00699743 | 13.74 | 0.00000000 | 0.0000 | 21.11 | 0.00875430 | 21.11 | 0.00875430 | 55.2708 | 54443.26 | 0.00 | 63319.47 | 58696.42 | 6.41876734 | 21.69 | 15.78 | 0.00875430 | 44043.6 | 12.74 | 12.04 | 0.00846901 | 34178.9 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 46702.526 | 46702.526 | 2.045349 | 0.00040857 | 1334.353 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.414674 | 6.41876734 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 5.7439 | 5.859459 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 46702.53 | 46702.53 | 1.0000 | 2.42463753 | 2.045349 | 21.11 | 14.61 | 0.00785435 | 41164.3 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.40853240 | 60.00 | 32.22 | 27.78 | 0.000 | 46702.53 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.11 | 0.00785435 | 21.11 | 0.00785435 | 49.6588 | 46702.53 | 0.00 | 50346.75 | 50346.75 | 2.42463753 | 16.60 | 13.01 | 0.00785435 | 36566.0 | 36.97 | 20.16 | 0.00785435 | 57330.6 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12067.994 | -999.000 | 1.103058 | 0.00043103 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7532 | 1004.8586 | 1.1854 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.103058 | 1.30760789 | 4197.9300 | 999.8980 | 23.64893600 | 13.37 | 6.70 | 6.67 | 662174.77 | 1.8225 | 1.822445 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | unknown | unknown | unknown | 7/21 10:40:00 | Sensible | 12067.99 | 11894.99 | 1.0000 | 1.30760789 | 1.103058 | 21.69 | 15.45 | 0.00856034 | 43551.3 | 12.80 | 11.96 | 0.00850000 | 34322.2 | 0.43098878 | 6.70 | 13.37 | 6.67 | 0.000 | 12067.99 | 24.54 | 0.00700282 | 15.11 | 0.00000000 | 0.0000 | 21.11 | 0.00856034 | 21.11 | 0.00856034 | 54.0619 | 11091.41 | 0.00 | 12250.64 | 11861.91 | 1.30760789 | 21.69 | 15.61 | 0.00856034 | 43551.3 | 12.81 | 12.04 | 0.00844260 | 34182.5 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8213.908 | 8213.908 | 0.359724 | 0.00007186 | 234.683 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.103058 | 1.30760789 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 1.0102 | 1.030545 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8213.91 | 8213.91 | 1.0000 | 0.42643051 | 0.359724 | 21.11 | 14.60 | 0.00784403 | 41137.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.07185152 | 60.00 | 32.22 | 27.78 | 0.000 | 8213.91 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.11 | 0.00784403 | 21.11 | 0.00784403 | 49.5954 | 8213.91 | 0.00 | 8854.79 | 8854.79 | 0.42643051 | 16.60 | 13.00 | 0.00784403 | 36539.8 | 36.97 | 20.15 | 0.00784403 | 57304.8 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10952.324 | -999.000 | 0.999387 | 0.00039118 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7647 | 1004.8586 | 1.1854 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.999387 | 1.18471286 | 4197.9300 | 999.8980 | 23.64893600 | 13.37 | 6.70 | 6.67 | 662174.77 | 1.6540 | 1.653962 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | unknown | unknown | unknown | 7/21 09:20:00 | Sensible | 10952.32 | 10779.54 | 1.0000 | 1.18471286 | 0.999387 | 21.69 | 15.46 | 0.00856650 | 43566.9 | 12.80 | 11.96 | 0.00850000 | 34322.2 | 0.39114441 | 6.70 | 13.37 | 6.67 | 0.000 | 10952.32 | 22.37 | 0.00699957 | 14.30 | 0.00000000 | 0.0000 | 21.11 | 0.00856650 | 21.11 | 0.00856650 | 54.1003 | 10048.98 | 0.00 | 11117.94 | 10749.95 | 1.18471286 | 21.69 | 15.62 | 0.00856650 | 43566.9 | 12.80 | 12.04 | 0.00844347 | 34182.4 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8205.834 | 8205.834 | 0.359370 | 0.00007179 | 234.452 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.999387 | 1.18471286 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 1.0092 | 1.029532 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8205.83 | 8205.83 | 1.0000 | 0.42601134 | 0.359370 | 21.11 | 14.60 | 0.00784389 | 41137.4 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.07178090 | 60.00 | 32.22 | 27.78 | 0.000 | 8205.83 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.11 | 0.00784389 | 21.11 | 0.00784389 | 49.5946 | 8205.83 | 0.00 | 8846.09 | 8846.09 | 0.42601134 | 16.60 | 13.00 | 0.00784389 | 36539.5 | 36.97 | 20.15 | 0.00784389 | 57304.4 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16348.477 | 16348.477 | 0.728015 | 0.00014302 | 413.620 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 2.0107 | 2.051136 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 16348.48 | 16348.48 | 1.0000 | 0.86301711 | 0.728015 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.14300902 | 60.00 | 32.22 | 27.78 | 0.000 | 16348.48 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00787548 | 21.00 | 0.00787548 | 50.1308 | 12565.30 | 0.00 | 16432.46 | 16432.46 | 0.86301711 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.27 | 19.74 | 0.00800000 | 55975.4 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3336.763 | -999.000 | 0.305479 | 0.00011918 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7425 | 1004.8586 | 1.1854 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.305479 | 0.36212661 | 4197.9300 | 999.8980 | 23.64893600 | 13.37 | 6.70 | 6.67 | 662174.77 | 0.5039 | 0.503900 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | unknown | unknown | unknown | 7/21 17:30:00 | Sensible | 3336.76 | 3293.46 | 1.0000 | 0.36212661 | 0.305479 | 21.69 | 15.45 | 0.00855455 | 43536.6 | 12.80 | 11.96 | 0.00850000 | 34322.2 | 0.11916706 | 6.70 | 13.37 | 6.67 | 0.000 | 3336.76 | 25.46 | 0.00700420 | 15.45 | 0.00000000 | 0.0000 | 21.11 | 0.00855455 | 21.11 | 0.00855455 | 54.0258 | 3071.64 | 0.00 | 3387.30 | 3284.19 | 0.36212661 | 21.69 | 15.61 | 0.00855455 | 43536.6 | 12.81 | 12.04 | 0.00844177 | 34182.6 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2656.844 | 2656.844 | 0.116355 | 0.00002324 | 75.908 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.305479 | 0.36212661 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 0.3268 | 0.333337 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2656.84 | 2656.84 | 1.0000 | 0.13793201 | 0.116355 | 21.11 | 14.63 | 0.00787888 | 41226.3 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.02324086 | 60.00 | 32.22 | 27.78 | 0.000 | 2656.84 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.11 | 0.00787888 | 21.11 | 0.00787888 | 49.8129 | 2656.84 | 0.00 | 2864.14 | 2864.14 | 0.13793201 | 16.60 | 13.03 | 0.00787888 | 36628.1 | 36.97 | 20.18 | 0.00787888 | 57393.0 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2966.637 | -999.000 | 0.271079 | 0.00010596 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7553 | 1004.8586 | 1.1854 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.271079 | 0.32134748 | 4197.9300 | 999.8980 | 23.64893600 | 13.37 | 6.70 | 6.67 | 662174.77 | 0.4480 | 0.448006 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | unknown | unknown | unknown | 7/21 18:10:00 | Sensible | 2966.64 | 2923.34 | 1.0000 | 0.32134748 | 0.271079 | 21.69 | 15.45 | 0.00856145 | 43554.1 | 12.80 | 11.96 | 0.00850000 | 34322.2 | 0.10594862 | 6.70 | 13.37 | 6.67 | 0.000 | 2966.64 | 24.70 | 0.00700305 | 15.17 | 0.00000000 | 0.0000 | 21.11 | 0.00856145 | 21.11 | 0.00856145 | 54.0687 | 2725.74 | 0.00 | 3011.53 | 2915.23 | 0.32134748 | 21.69 | 15.61 | 0.00856145 | 43554.1 | 12.80 | 12.04 | 0.00844275 | 34182.5 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2654.049 | 2654.049 | 0.116233 | 0.00002322 | 75.828 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.271079 | 0.32134748 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 0.3264 | 0.332986 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2654.05 | 2654.05 | 1.0000 | 0.13778689 | 0.116233 | 21.11 | 14.63 | 0.00787876 | 41226.0 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.02321641 | 60.00 | 32.22 | 27.78 | 0.000 | 2654.05 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.11 | 0.00787876 | 21.11 | 0.00787876 | 49.8122 | 2654.05 | 0.00 | 2861.13 | 2861.13 | 0.13778689 | 16.60 | 13.03 | 0.00787876 | 36627.8 | 36.97 | 20.18 | 0.00787876 | 57392.7 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20186.596 | -999.000 | 1.831812 | 0.00072100 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8025 | 1004.8586 | 1.1854 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.831812 | 2.17150213 | 4197.9300 | 999.8980 | 23.64893600 | 13.37 | 6.70 | 6.67 | 662174.77 | 3.0485 | 3.048473 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | unknown | unknown | 7/21 14:10:00 | Sensible | 20186.60 | 19772.78 | 1.0000 | 2.17150213 | 1.831812 | 21.69 | 15.48 | 0.00858683 | 43618.3 | 12.80 | 11.96 | 0.00850000 | 34322.2 | 0.72093141 | 6.70 | 13.37 | 6.67 | 0.000 | 20186.60 | 27.40 | 0.00700714 | 16.15 | 0.00000000 | 0.0000 | 21.11 | 0.00858683 | 21.11 | 0.00858683 | 54.2275 | 18418.70 | 0.00 | 20491.00 | 19720.83 | 2.17150213 | 21.69 | 15.63 | 0.00858683 | 43618.3 | 12.80 | 12.04 | 0.00844635 | 34182.0 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12794.037 | 12794.037 | 0.560312 | 0.00011193 | 365.535 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.831812 | 2.17150213 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 1.5735 | 1.605184 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 12794.04 | 12794.04 | 1.0000 | 0.66421626 | 0.560312 | 21.11 | 14.63 | 0.00788410 | 41239.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.11191640 | 60.00 | 32.22 | 27.78 | 0.000 | 12794.04 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.11 | 0.00788410 | 21.11 | 0.00788410 | 49.8452 | 12794.04 | 0.00 | 13792.32 | 13792.32 | 0.66421626 | 16.60 | 13.04 | 0.00788410 | 36641.3 | 36.97 | 20.18 | 0.00788410 | 57406.1 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14785.698 | 14785.698 | 1.100173 | 0.00012935 | 336.197 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 1.8185 | 1.855064 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 14785.70 | 14785.70 | 1.0000 | 1.30418863 | 1.100173 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.12933854 | 60.00 | 32.22 | 27.78 | 0.000 | 14785.70 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00791247 | 21.00 | 0.00791247 | 50.3637 | 9068.36 | 0.00 | 14865.32 | 14865.32 | 1.30418863 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.78 | 17.28 | 0.00800000 | 48332.9 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15247.245 | 15247.245 | 1.154602 | 0.00013339 | 345.795 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 1.8752 | 1.912972 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 15247.25 | 15247.25 | 1.0000 | 1.36871113 | 1.154602 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.13337595 | 60.00 | 32.22 | 27.78 | 0.000 | 15247.25 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00791414 | 21.00 | 0.00791414 | 50.3742 | 9247.03 | 0.00 | 15329.43 | 15329.43 | 1.36871113 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.58 | 17.22 | 0.00800000 | 48134.6 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10553.288 | 10553.288 | 1.193887 | 0.00009232 | 228.398 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 1.2979 | 1.324052 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 10553.29 | 10553.29 | 1.0000 | 1.41528018 | 1.193887 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.09231535 | 60.00 | 32.22 | 27.78 | 0.000 | 10553.29 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.77 | 0.00756231 | 21.00 | 0.00756231 | 48.1661 | 4355.06 | 0.00 | 10611.88 | 10611.88 | 1.41528018 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.95 | 15.94 | 0.00800000 | 44432.8 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11893.177 | 11893.177 | 0.422275 | 0.00010405 | 324.594 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 1.4627 | 1.492159 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11893.18 | 11893.18 | 1.0000 | 0.50058183 | 0.422275 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.10403608 | 60.00 | 32.22 | 27.78 | 0.000 | 11893.18 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00792815 | 21.00 | 0.00792815 | 50.4620 | 9698.61 | 0.00 | 11952.16 | 11952.16 | 0.50058183 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60811.3 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 394291.272 | -999.000 | 21.949415 | 0.01408317 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1694 | 1004.8586 | 1.1854 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.949415 | 26.01969948 | 4197.9300 | 999.8980 | 23.64893600 | 13.37 | 6.70 | 6.67 | 662174.77 | 59.5449 | 59.544895 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | Sensible | 394291.27 | 394291.26 | 1.0000 | 26.01969948 | 21.949415 | 25.80 | 16.64 | 0.00824626 | 46945.0 | 10.95 | 10.93 | 0.00824626 | 31791.4 | 14.08173403 | 6.70 | 13.37 | 6.67 | 49180.708 | 345110.56 | 27.40 | 0.00700714 | 16.15 | 11.66146000 | 53.1288 | 23.99 | 0.00965082 | 23.99 | 0.00963050 | 50.9674 | 297203.00 | 0.00 | 399432.65 | 384628.49 | 26.01969948 | 25.80 | 16.81 | 0.00824626 | 46945.0 | 11.31 | 10.98 | 0.00802066 | 31593.9 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 459648.764 | 459648.764 | 6.584825 | 0.00402121 | 6038.207 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.949415 | 26.01969948 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 56.5314 | 57.669111 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 459648.76 | 459648.76 | 1.0000 | 7.80590984 | 6.584825 | -41.90 | -41.90 | 0.00006450 | -41946.5 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 4.02079770 | 60.00 | 32.22 | 27.78 | 0.000 | 459648.76 | -41.90 | 0.00006450 | -41.90 | 11.66146000 | 177.0960 | 20.98 | 0.00786520 | 21.00 | 0.00786144 | 50.0429 | 88222.39 | 0.00 | 294762.27 | 294762.27 | 7.80590984 | 2.80 | -4.37 | 0.00006450 | 2975.2 | 40.38 | 14.79 | 0.00006450 | 40736.6 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 38332.296 | -999.000 | 2.051317 | 0.00136914 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8659 | 1004.8586 | 1.1854 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.43162656 | 4197.9300 | 999.8980 | 23.64893600 | 13.37 | 6.70 | 6.67 | 662174.77 | 5.7888 | 5.788849 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 38332.30 | 38332.30 | 1.0000 | 2.43171206 | 2.051317 | 27.40 | 16.15 | 0.00700714 | 45414.0 | 11.91 | 10.04 | 0.00700714 | 29650.5 | 1.36900115 | 6.70 | 13.37 | 6.67 | 2195.006 | 36137.29 | 27.40 | 0.00700714 | 16.15 | 2.05124512 | 99.9965 | 21.11 | 0.00859503 | 21.11 | 0.00859868 | 54.3003 | 189811.32 | 0.00 | 38851.60 | 38851.60 | 2.43171206 | 27.40 | 16.31 | 0.00700714 | 45414.0 | 11.70 | 10.08 | 0.00700714 | 29436.9 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 42957.200 | 42957.200 | 0.615395 | 0.00037581 | 564.310 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.43162656 | 4197.9300 | 999.8980 | 6.97218599 | 54.44 | 82.22 | 27.78 | 813085.84 | 5.2832 | 5.389558 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 42957.20 | 42957.20 | 1.0000 | 0.72951362 | 0.615395 | -41.90 | -41.90 | 0.00006450 | -41946.5 | 16.70 | 13.04 | 0.00800000 | 37036.7 | 0.37576999 | 60.00 | 32.22 | 27.78 | 0.000 | 42957.20 | -41.90 | 0.00006450 | -41.90 | 2.05124512 | 333.3216 | 21.11 | 0.00785568 | 21.11 | 0.00785484 | 49.6619 | 144497.93 | 0.00 | 27547.47 | 27547.47 | 0.72951362 | 2.80 | -4.37 | 0.00006450 | 2975.2 | 40.38 | 14.79 | 0.00006450 | 40736.6 | |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 54035.880 | 39770.408 | 4.903586 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 1.1854 | SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 4.903586 | 5.81290412 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 75921.46 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 75921.46 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 42290.343 | 31125.692 | 3.872570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 1.1854 | SWHSYS1 HPWH FAN | Fan:SystemModel | 3.872570 | 4.59069611 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 54370.95 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54370.95 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 21.95 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 613.00 | 8644.50 | 612.33 |
RETAIL_1_FLR_1 | 4106.00 | 8151.00 | 3785.17 |
RETAIL_2_FLR_1 | 2017.67 | 8196.17 | 1893.67 |
MECH_FLR_1 | 3640.00 | 8660.33 | 3640.00 |
STORAGE_FLR_1 | 3946.67 | 8752.33 | 3946.67 |
LAUNDRY_FLR_1 | 5578.00 | 3712.67 | 2096.00 |
CAFE_FLR_1 | 3527.50 | 7369.17 | 2765.17 |
LOBBY_FLR_1 | 1852.00 | 7082.50 | 1281.33 |
ROOM_1_FLR_3 | 4078.50 | 8475.33 | 4063.17 |
ROOM_2_FLR_3 | 4774.50 | 8307.50 | 4505.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 3756.83 | 8714.33 | 3751.67 |
ROOM_5_FLR_3 | 3895.00 | 8282.67 | 3835.33 |
ROOM_6_FLR_3 | 4376.00 | 8183.83 | 4213.50 |
CORRIDOR_FLR_3 | 3770.00 | 8729.17 | 3770.00 |
ROOM_1_FLR_6 | 4491.50 | 8435.33 | 4454.83 |
ROOM_2_FLR_6 | 5135.00 | 8292.00 | 4880.17 |
ROOM_3_MULT9_FLR_6 | 3774.17 | 8206.17 | 3619.83 |
BANQUET_FLR_6 | 2591.50 | 4776.33 | 481.00 |
DINING_FLR_6 | 2951.00 | 3985.00 | 277.17 |
KITCHEN_FLR_6 | 7470.17 | 6108.67 | 5249.00 |
CORRIDOR_FLR_6 | 3899.67 | 8461.33 | 3865.00 |
Facility | 8726.33 | 8760.00 | 7813.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.83 | 0.00 | 0.83 | 0.00 |
RETAIL_1_FLR_1 | 72.17 | 0.00 | 72.17 | 0.00 |
RETAIL_2_FLR_1 | 12.00 | 0.00 | 12.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 5.17 | 0.00 | 5.17 | 0.00 |
CAFE_FLR_1 | 48.50 | 0.00 | 48.50 | 0.00 |
LOBBY_FLR_1 | 23.67 | 0.00 | 23.67 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 3.17 | 0.00 | 3.17 |
ROOM_2_FLR_3 | 0.00 | 11.17 | 0.00 | 11.17 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4.83 | 41.00 | 4.83 | 41.00 |
ROOM_5_FLR_3 | 0.00 | 12.00 | 0.00 | 12.00 |
ROOM_6_FLR_3 | 0.00 | 32.00 | 0.00 | 32.00 |
CORRIDOR_FLR_3 | 3.50 | 0.00 | 3.50 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 3.67 | 0.00 | 3.67 |
ROOM_2_FLR_6 | 0.00 | 13.83 | 0.00 | 13.83 |
ROOM_3_MULT9_FLR_6 | 0.00 | 5.50 | 0.00 | 5.50 |
BANQUET_FLR_6 | 1.00 | 0.00 | 1.00 | 0.00 |
DINING_FLR_6 | 0.67 | 0.00 | 0.67 | 0.00 |
KITCHEN_FLR_6 | 0.50 | 0.00 | 0.50 | 0.00 |
CORRIDOR_FLR_6 | 1.33 | 0.00 | 1.33 | 0.00 |
Facility | 78.83 | 74.33 | 78.83 | 74.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 0.803 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 3.637 | 0.036 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.394 | 0.012 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.505 | 0.013 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.471 | 0.013 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 23.785 | 0.039 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.55 | 142.30 | 748.35 | 5.045 | 0.028 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.05 | 422.44 | 5183.56 | 1.957 | 0.012 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.357 | 0.047 | 0.000 | 0.031 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.357 | 0.047 | 0.000 | 0.025 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.405 | 0.021 | 0.000 | 0.055 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.357 | 0.047 | 0.000 | 0.031 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.357 | 0.047 | 0.000 | 0.035 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.562 | 0.006 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.357 | 0.047 | 0.000 | 0.037 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.357 | 0.047 | 0.000 | 0.027 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.405 | 0.038 | 0.000 | 0.058 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.562 | 0.014 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.929 | 0.014 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 20.891 | 0.039 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.157 | 0.010 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 0.772 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 3.505 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.342 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.489 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.456 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 19.867 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.55 | 142.30 | 748.35 | 4.852 | 0.000 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.05 | 422.44 | 5183.56 | 1.874 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.000 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.543 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 3.857 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.047 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 13.469 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.119 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.78 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.55 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.05 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.96 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.96 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.11 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 33285380.23 | 0.00 | 33285380.23 | 0.00 | 33285380.23 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 8337872.91 | 0.00 | 8337872.91 | 82845.47 | 8420718.39 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3686508.16 | 0.00 | 3686508.16 | 31978.46 | 3718486.62 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 2831401.31 | 0.00 | 2831401.31 | 75578.08 | 2906979.38 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1524695.41 | 0.00 | 1524695.41 | 43604.39 | 1568299.79 | 1821682.01 | 8760.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 63113306.46 | 0.00 | 63113306.46 | 103198.00 | 63216504.46 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 32475714.49 | 0.00 | 32475714.49 | 183134.61 | 32658849.11 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 87040861.61 | 0.00 | 87040861.61 | 523257.42 | 87564119.03 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 31947.24 | 1492103.95 | 48086.42 | 1540190.37 | 1946875.62 | 2190.00 | 6169.00 | 401.00 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 25694.84 | 1485680.47 | 48082.75 | 1533763.22 | 1946647.51 | 2190.00 | 6294.92 | 275.08 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 0.00 | 1099911.97 | 13416.65 | 1113328.62 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.00 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 35073.08 | 19838902.37 | 13420.32 | 19852322.69 | 26405105.73 | 2190.00 | 6178.38 | 391.62 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 31952.22 | 1492108.94 | 48086.42 | 1540195.35 | 1946875.62 | 2190.00 | 6169.00 | 401.00 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 35482.70 | 1495468.34 | 48082.75 | 1543551.08 | 1946647.51 | 2190.00 | 6177.51 | 392.49 | 0.00 |
CORRIDOR_FLR_3 | 22958668.37 | 0.00 | 22958668.37 | 58146.15 | 23016814.53 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 37456.40 | 402495.58 | 48097.01 | 450592.58 | 486718.90 | 2105.05 | 6170.46 | 484.49 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 27768.11 | 392764.52 | 48093.34 | 440857.86 | 486661.88 | 2131.72 | 6315.56 | 312.72 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 37432.41 | 2382622.72 | 24608.11 | 2407230.84 | 3126920.42 | 2190.00 | 6168.50 | 401.50 | 0.00 |
BANQUET_FLR_6 | 39408491.13 | 0.00 | 39408491.13 | 117440.80 | 39525931.94 | 37458366.31 | 5335.83 | 173.48 | 3250.69 | 0.00 |
DINING_FLR_6 | 42562144.07 | 0.00 | 42562144.07 | 117440.80 | 42679584.88 | 37458366.31 | 4095.17 | 192.98 | 4471.84 | 0.00 |
KITCHEN_FLR_6 | 56178079.74 | 0.00 | 56178079.74 | 105136.75 | 56283216.49 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12515611.79 | 0.00 | 12515611.79 | 102901.98 | 12618513.77 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 3567978.09 | 0.21E+10 | 4845727.63 | 0.21E+10 | 0.43E+10 | 8760.00 | 6778.13 | 8760.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.0555 | 0.0000 | 1.0555 | 0.0000 | 1.0555 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.2644 | 0.0000 | 0.2644 | 0.0026 | 0.2670 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1169 | 0.0000 | 0.1169 | 0.0010 | 0.1179 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.0898 | 0.0000 | 0.0898 | 0.0024 | 0.0922 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0483 | 0.0000 | 0.0483 | 0.0014 | 0.0497 | 0.0578 | 8760.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 2.0013 | 0.0000 | 2.0013 | 0.0033 | 2.0046 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 1.0298 | 0.0000 | 1.0298 | 0.0058 | 1.0356 | 0.6764 | 0.00 | 0.00 | 8760.00 |
LOBBY_FLR_1 | 2.7600 | 0.0000 | 2.7600 | 0.0166 | 2.7766 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0010 | 0.0473 | 0.0015 | 0.0488 | 0.0617 | 2190.00 | 6169.00 | 401.00 |
ROOM_2_FLR_3 | 0.0463 | 0.0008 | 0.0471 | 0.0015 | 0.0486 | 0.0617 | 2190.00 | 6294.92 | 275.08 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0011 | 0.6291 | 0.0004 | 0.6295 | 0.8373 | 2190.00 | 6178.38 | 391.62 |
ROOM_5_FLR_3 | 0.0463 | 0.0010 | 0.0473 | 0.0015 | 0.0488 | 0.0617 | 2190.00 | 6169.00 | 401.00 |
ROOM_6_FLR_3 | 0.0463 | 0.0011 | 0.0474 | 0.0015 | 0.0489 | 0.0617 | 2190.00 | 6177.51 | 392.49 |
CORRIDOR_FLR_3 | 0.7280 | 0.0000 | 0.7280 | 0.0018 | 0.7299 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0012 | 0.0128 | 0.0015 | 0.0143 | 0.0154 | 2105.05 | 6170.46 | 484.49 |
ROOM_2_FLR_6 | 0.0116 | 0.0009 | 0.0125 | 0.0015 | 0.0140 | 0.0154 | 2131.72 | 6315.56 | 312.72 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0012 | 0.0756 | 0.0008 | 0.0763 | 0.0992 | 2190.00 | 6168.50 | 401.50 |
BANQUET_FLR_6 | 1.2496 | 0.0000 | 1.2496 | 0.0037 | 1.2534 | 1.1878 | 5335.83 | 173.48 | 3250.69 |
DINING_FLR_6 | 1.3496 | 0.0000 | 1.3496 | 0.0037 | 1.3534 | 1.1878 | 4095.17 | 192.98 | 4471.84 |
KITCHEN_FLR_6 | 1.7814 | 0.0000 | 1.7814 | 0.0033 | 1.7847 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3969 | 0.0000 | 0.3969 | 0.0033 | 0.4001 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 64.2150 | 0.1131 | 64.3281 | 0.1213 | 64.4494 | 73.9670 | 8760.00 | 6778.13 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.57E+09 | 0.00 | 0.57E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 41903990.31 | 262807.00 | 42166797.31 | 64690340.46 | 8755.94 | 3.89 | 0.17 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 18.0880 | 0.0000 | 18.0880 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.3288 | 0.0083 | 1.3371 | 2.0513 | 8755.94 | 3.89 | 0.17 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 2759.84 | 0.00 | 0.00 | 0.00 | 6000.16 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 18.8787 | 0.0000 | 0.0000 | 0.0000 | 17.7274 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.6784 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1363 |
Defaulted Fields | 1208 |
Fields with Defaults | 4115 |
Autosized Fields | 353 |
Autosizable Fields | 407 |
Autocalculated Fields | 289 |
Autocalculatable Fields | 549 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 4631.53 | 67301.13 | 26-JUN-02:30 | 341313.13 | 20-JUN-19:20 |
Electricity:Building | 2278.33 | 29981.50 | 10-JUN-05:00 | 133648.28 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 245.14 | 2955.01 | 02-JAN-02:10 | 17976.64 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2271.24 | 29840.36 | 10-JUN-05:00 | 133406.95 | 02-JAN-20:10 |
InteriorLights:Electricity | 543.10 | 4558.18 | 10-JUN-05:00 | 45424.10 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 102.03 | 927.11 | 02-JAN-02:10 | 8344.11 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 543.10 | 4558.18 | 10-JUN-05:00 | 45424.10 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 543.10 | 4558.18 | 10-JUN-05:00 | 45424.10 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 102.03 | 927.11 | 02-JAN-02:10 | 8344.11 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 543.10 | 4558.18 | 10-JUN-05:00 | 45424.10 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 15.82 | 195.57 | 02-JAN-02:10 | 1146.69 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 5.64 | 51.23 | 02-JAN-02:10 | 461.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 5.64 | 51.23 | 02-JAN-02:10 | 461.08 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 18.32 | 226.47 | 02-JAN-02:10 | 1327.87 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 6.53 | 59.33 | 02-JAN-02:10 | 533.93 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 6.53 | 59.33 | 02-JAN-02:10 | 533.93 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.00 | 245.14 | 02-JAN-02:10 | 1455.21 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 7.53 | 68.42 | 02-JAN-02:10 | 615.76 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 7.53 | 68.42 | 02-JAN-02:10 | 615.76 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.28 | 66.24 | 02-JAN-02:10 | 379.51 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.68 | 15.26 | 02-JAN-02:10 | 137.35 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.68 | 15.26 | 02-JAN-02:10 | 137.35 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.35 | 1002.76 | 02-JAN-02:10 | 4933.42 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.41 | 40.07 | 02-JAN-02:10 | 360.62 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.41 | 40.07 | 02-JAN-02:10 | 360.62 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 25.95 | 237.83 | 20-MAY-05:00 | 2381.38 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 11.61 | 34.62 | 20-MAY-05:00 | 1416.11 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 11.61 | 34.62 | 20-MAY-05:00 | 1416.11 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 259.70 | 3045.05 | 10-JUN-05:00 | 19610.05 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.70 | 933.64 | 10-JUN-05:00 | 9580.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.70 | 933.64 | 10-JUN-05:00 | 9580.84 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 17.85 | 257.74 | 01-JAN-02:10 | 1187.62 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 5.55 | 47.02 | 01-JAN-02:10 | 427.46 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 5.55 | 47.02 | 01-JAN-02:10 | 427.46 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 17.84 | 257.71 | 01-JAN-02:10 | 1187.48 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 5.55 | 47.01 | 01-JAN-02:10 | 427.41 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 5.55 | 47.01 | 01-JAN-02:10 | 427.41 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 295.07 | 4482.89 | 01-JAN-02:10 | 20504.95 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 66.32 | 561.43 | 01-JAN-02:10 | 5104.26 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 66.32 | 561.43 | 01-JAN-02:10 | 5104.26 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 295.15 | 4484.12 | 01-JAN-02:10 | 20510.57 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 66.33 | 561.58 | 01-JAN-02:10 | 5105.65 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 66.33 | 561.58 | 01-JAN-02:10 | 5105.65 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 17.85 | 257.74 | 01-JAN-02:10 | 1187.62 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 5.55 | 47.02 | 01-JAN-02:10 | 427.46 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 5.55 | 47.02 | 01-JAN-02:10 | 427.46 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 17.84 | 257.71 | 01-JAN-02:10 | 1187.48 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 5.55 | 47.01 | 01-JAN-02:10 | 427.41 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 5.55 | 47.01 | 01-JAN-02:10 | 427.41 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 51.07 | 464.00 | 02-JAN-02:10 | 4176.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 51.07 | 464.00 | 02-JAN-02:10 | 4176.01 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 51.07 | 464.00 | 02-JAN-02:10 | 4176.01 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.46 | 64.43 | 01-JAN-02:10 | 296.90 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.39 | 11.75 | 01-JAN-02:10 | 106.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.39 | 11.75 | 01-JAN-02:10 | 106.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.46 | 64.43 | 01-JAN-02:10 | 296.87 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.39 | 11.75 | 01-JAN-02:10 | 106.85 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.39 | 11.75 | 01-JAN-02:10 | 106.85 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 34.95 | 531.01 | 01-JAN-02:10 | 2428.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 7.86 | 66.50 | 01-JAN-02:10 | 604.62 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 7.86 | 66.50 | 01-JAN-02:10 | 604.62 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 201.31 | 2415.09 | 06-MAY-04:50 | 9234.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 25.45 | 165.79 | 06-MAY-04:50 | 2486.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 25.45 | 165.79 | 06-MAY-04:50 | 2486.81 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 201.31 | 2415.09 | 06-MAY-04:50 | 9234.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 25.45 | 165.79 | 06-MAY-04:50 | 2486.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 25.45 | 165.79 | 06-MAY-04:50 | 2486.81 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 443.12 | 5932.71 | 02-JAN-02:10 | 18599.73 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.01 | 109.08 | 02-JAN-02:10 | 981.75 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.01 | 109.08 | 02-JAN-02:10 | 981.75 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 13.51 | 122.77 | 02-JAN-02:10 | 1104.91 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 13.51 | 122.77 | 02-JAN-02:10 | 1104.91 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 13.51 | 122.77 | 02-JAN-02:10 | 1104.91 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 43.38 | 695.18 | 11-JAN-23:30 | 2785.70 | 13-AUG-10:10 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 801.79 | 815.98 | 30-MAR-03:00 | 153899.60 | 29-JUL-18:20 |
LowTempRefrigeration:Refrigeration:Electricity | 15.60 | 0.00 | 01-JAN-11:10 | 1310.47 | 22-JUL-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 20.68 | 555.86 | 12-JAN-04:10 | 714.05 | 25-JUL-14:00 |
WaterSystems:Electricity | 322.88 | -166.94 | 23-MAR-01:20 | 37466.90 | 05-SEP-18:50 |
Electricity:HVAC | 759.38 | 13070.90 | 06-OCT-14:00 | 43814.51 | 21-JUN-21:00 |
Fans:Electricity | 526.95 | 10959.46 | 20-FEB-08:10 | 33044.04 | 12-JUL-22:00 |
General:Fans:Electricity | 526.95 | 10959.46 | 20-FEB-08:10 | 33044.04 | 12-JUL-22:00 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ExteriorEquipment:Electricity | 641.45 | 9451.07 | 17-JUN-03:00 | 39153.57 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 22.42 | 386.23 | 10-JUN-05:00 | 1279.09 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 4631.53 | 67301.13 | 26-JUN-02:30 | 341313.13 | 20-JUN-19:20 |
ElectricityPurchased:Plant | 4631.53 | 67301.13 | 26-JUN-02:30 | 341313.13 | 20-JUN-19:20 |
Cogeneration:ElectricityPurchased | 4631.53 | 67301.13 | 26-JUN-02:30 | 341313.13 | 20-JUN-19:20 |
General:Cogeneration:ElectricityPurchased | 4631.53 | 67301.13 | 26-JUN-02:30 | 341313.13 | 20-JUN-19:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 4631.53 | 67301.13 | 26-JUN-02:30 | 341313.13 | 20-JUN-19:20 |
ElectricityNet:Plant | 4631.53 | 67301.13 | 26-JUN-02:30 | 341313.13 | 20-JUN-19:20 |
Cogeneration:ElectricityNet | 4631.53 | 67301.13 | 26-JUN-02:30 | 341313.13 | 20-JUN-19:20 |
General:Cogeneration:ElectricityNet | 4631.53 | 67301.13 | 26-JUN-02:30 | 341313.13 | 20-JUN-19:20 |
ExteriorLights:Electricity | 173.00 | 0.00 | 01-JAN-11:20 | 11096.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 173.00 | 0.00 | 01-JAN-11:20 | 11096.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 210.00 | 0.00 | 05-APR-17:10 | 9938.94 | 01-JAN-00:10 |
General:HeatRecovery:Electricity | 210.00 | 0.00 | 05-APR-17:10 | 9938.94 | 01-JAN-00:10 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.58 | 05-AUG-00:20 | 4740.06 | 15-DEC-07:10 |
Water Heater Parasitic:WaterSystems:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 353.00 | 0.00 | 01-JAN-00:10 | 115436.70 | 29-JUL-15:20 |
General:Cooling:Electricity | 353.00 | 0.00 | 01-JAN-00:10 | 115436.70 | 29-JUL-15:20 |
Pumps:Electricity | 89.62 | 47.91 | 27-MAY-14:40 | 7361.44 | 20-JUL-18:50 |
General:Pumps:Electricity | 89.62 | 47.91 | 27-MAY-14:40 | 7361.44 | 20-JUL-18:50 |
WIRED_LTG_ELECTRICITY | 19.12 | 0.00 | 01-JAN-00:10 | 1598.93 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 8817.52 | 29270.80 | 10-MAY-01:10 | 1339773.95 | 12-JAN-19:20 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 7028.68 | 15908.90 | 10-MAY-15:10 | 1252154.17 | 12-JAN-19:20 |
WaterSystems:NaturalGas | 2104.44 | 15908.90 | 03-APR-15:10 | 203106.66 | 21-MAR-21:30 |
Water Heater:WaterSystems:NaturalGas | 2104.44 | 15908.90 | 03-APR-15:10 | 203106.66 | 21-MAR-21:30 |
Heating:NaturalGas | 4924.24 | 0.00 | 06-APR-18:30 | 1123356.46 | 12-JAN-09:10 |
Boiler:Heating:NaturalGas | 4924.24 | 0.00 | 06-APR-18:30 | 1123356.46 | 12-JAN-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 1072.02 | 0.00 | 01-JAN-00:10 | 393284.34 | 29-JUL-18:10 |
PlantLoopCoolingDemand:HVAC | 1072.02 | 0.00 | 01-JAN-00:10 | 393284.34 | 29-JUL-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 1072.02 | 0.00 | 01-JAN-00:10 | 393284.34 | 29-JUL-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-JAN-22:00 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-JAN-22:00 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-JAN-22:00 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-JAN-22:00 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-JAN-22:00 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 03-JAN-22:00 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 24497.59 | 156211.88 | 19-SEP-14:40 | 2100744.83 | 12-JAN-09:10 |
EnergyTransfer:Building | 4839.54 | 69881.08 | 28-FEB-11:10 | 326645.36 | 11-JUL-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 669.90 | 8632.13 | 13-JAN-04:00 | 36151.63 | 22-JUL-10:40 |
Refrigeration:EnergyTransfer | 177.59 | 3320.53 | 12-JAN-04:00 | 10320.38 | 25-JUL-06:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 88.79 | 1660.27 | 12-JAN-04:00 | 5160.19 | 25-JUL-06:30 |
General:Refrigeration:EnergyTransfer | 88.79 | 1660.27 | 12-JAN-04:00 | 5160.19 | 25-JUL-06:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 88.79 | 1660.27 | 12-JAN-04:00 | 5160.19 | 25-JUL-06:30 |
EnergyTransfer:Plant | 7585.83 | 20952.50 | 02-OCT-02:00 | 962612.51 | 12-JAN-09:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.46 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 67.34 | 1436.89 | 12-JAN-04:10 | 2541.06 | 25-JUL-14:00 |
EnergyTransfer:HVAC | 12072.23 | 1088.87 | 19-SEP-14:40 | 927901.35 | 12-JAN-09:10 |
CoolingCoils:EnergyTransfer | 1865.76 | 0.00 | 01-JAN-00:10 | 524277.35 | 29-JUL-18:20 |
EnergyTransfer:Zone:BASEMENT | 290.90 | 3051.98 | 27-FEB-16:00 | 19199.68 | 11-JAN-22:00 |
Heating:EnergyTransfer | 597.78 | 0.00 | 09-FEB-18:10 | 153272.42 | 15-DEC-16:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 597.78 | 0.00 | 09-FEB-18:10 | 153272.42 | 15-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4152.96 | 42241.59 | 13-JAN-15:00 | 323989.38 | 11-JUL-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 290.90 | 3051.98 | 27-FEB-16:00 | 19199.68 | 11-JAN-22:00 |
General:Cooling:EnergyTransfer | 4152.96 | 42241.59 | 13-JAN-15:00 | 323989.38 | 11-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 290.90 | 3051.98 | 27-FEB-16:00 | 19199.68 | 11-JAN-22:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 41.49 | 0.14 | 30-SEP-06:50 | 4635.84 | 25-AUG-13:30 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 9.11 | 0.00 | 16-JAN-12:30 | 2555.12 | 13-JAN-15:20 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 9.11 | 0.00 | 16-JAN-12:30 | 2555.12 | 13-JAN-15:20 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 32.38 | 0.00 | 01-JAN-00:10 | 4635.84 | 25-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 32.38 | 0.00 | 01-JAN-00:10 | 4635.84 | 25-AUG-13:30 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 27.91 | 0.15 | 14-DEC-12:40 | 1688.28 | 21-JUN-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 273.46 | 13-JAN-13:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 273.46 | 13-JAN-13:00 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 27.91 | 0.00 | 13-JAN-08:50 | 1688.28 | 21-JUN-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 27.91 | 0.00 | 13-JAN-08:50 | 1688.28 | 21-JUN-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 17.39 | 0.01 | 08-JAN-04:10 | 1177.66 | 12-JUL-21:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 1.99 | 0.00 | 01-JAN-19:10 | 989.34 | 12-JAN-16:00 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 1.99 | 0.00 | 01-JAN-19:10 | 989.34 | 12-JAN-16:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 15.40 | 0.00 | 01-JAN-00:10 | 1177.66 | 12-JUL-21:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 15.40 | 0.00 | 01-JAN-00:10 | 1177.66 | 12-JUL-21:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 10.91 | 0.02 | 13-FEB-20:10 | 904.14 | 13-JAN-10:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 3.87 | 0.00 | 06-JAN-23:00 | 904.14 | 13-JAN-10:40 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 3.87 | 0.00 | 06-JAN-23:00 | 904.14 | 13-JAN-10:40 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 7.04 | 0.00 | 01-JAN-00:10 | 609.95 | 23-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 7.04 | 0.00 | 01-JAN-00:10 | 609.95 | 23-JUL-10:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 588.64 | 8663.53 | 14-JAN-06:00 | 38710.36 | 21-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 588.64 | 8663.53 | 14-JAN-06:00 | 38710.36 | 21-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 588.64 | 8663.53 | 14-JAN-06:00 | 38710.36 | 21-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 211.93 | 0.04 | 15-JAN-12:10 | 15848.52 | 25-AUG-14:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 1.60 | 0.00 | 01-JAN-00:10 | 4082.63 | 13-JAN-14:40 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 1.60 | 0.00 | 01-JAN-00:10 | 4082.63 | 13-JAN-14:40 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 210.33 | 0.00 | 01-JAN-13:10 | 15848.52 | 25-AUG-14:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 210.33 | 0.00 | 01-JAN-13:10 | 15848.52 | 25-AUG-14:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 716.82 | 57.54 | 13-JAN-12:50 | 39052.68 | 11-AUG-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 1057.95 | 13-JAN-13:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 1057.95 | 13-JAN-13:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 716.81 | 0.00 | 13-JAN-12:50 | 39052.68 | 11-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 716.81 | 0.00 | 13-JAN-12:50 | 39052.68 | 11-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 79.64 | 0.00 | 01-JAN-08:10 | 11578.49 | 11-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 46.08 | 0.00 | 01-JAN-08:10 | 9589.72 | 12-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 46.08 | 0.00 | 01-JAN-08:10 | 9589.72 | 12-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 33.56 | 0.00 | 01-JAN-00:10 | 11578.49 | 11-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 33.56 | 0.00 | 01-JAN-00:10 | 11578.49 | 11-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 73.30 | 0.00 | 01-JAN-08:10 | 11521.16 | 06-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 51.33 | 0.00 | 01-JAN-08:10 | 9723.51 | 12-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 51.33 | 0.00 | 01-JAN-08:10 | 9723.51 | 12-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 21.97 | 0.00 | 01-JAN-00:10 | 11521.16 | 06-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 21.97 | 0.00 | 01-JAN-00:10 | 11521.16 | 06-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 363.30 | 0.00 | 07-JAN-08:30 | 64720.11 | 25-AUG-13:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 97.34 | 0.00 | 07-JAN-08:30 | 28877.00 | 12-JAN-04:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 97.34 | 0.00 | 07-JAN-08:30 | 28877.00 | 12-JAN-04:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 265.96 | 0.00 | 01-JAN-00:10 | 64720.11 | 25-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 265.96 | 0.00 | 01-JAN-00:10 | 64720.11 | 25-AUG-13:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 382.05 | 0.00 | 01-JAN-08:10 | 65656.90 | 22-JUN-22:00 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 151.26 | 0.00 | 01-JAN-08:10 | 57177.83 | 13-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 151.26 | 0.00 | 01-JAN-08:10 | 57177.83 | 13-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 230.79 | 0.00 | 01-JAN-00:10 | 65656.90 | 22-JUN-22:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 230.79 | 0.00 | 01-JAN-00:10 | 65656.90 | 22-JUN-22:00 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 83.82 | 0.00 | 01-JAN-08:10 | 11395.39 | 22-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 43.97 | 0.00 | 01-JAN-08:10 | 9524.84 | 12-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 43.97 | 0.00 | 01-JAN-08:10 | 9524.84 | 12-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 39.85 | 0.00 | 01-JAN-00:10 | 11395.39 | 22-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 39.85 | 0.00 | 01-JAN-00:10 | 11395.39 | 22-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 77.10 | 0.00 | 01-JAN-08:10 | 12081.27 | 11-JUL-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 48.79 | 0.00 | 01-JAN-08:10 | 9660.34 | 12-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 48.79 | 0.00 | 01-JAN-08:10 | 9660.34 | 12-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 28.31 | 0.00 | 01-JAN-00:10 | 12081.27 | 11-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 28.31 | 0.00 | 01-JAN-00:10 | 12081.27 | 11-JUL-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 135.67 | 0.32 | 24-NOV-06:00 | 9319.43 | 23-JUL-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 24.01 | 0.00 | 04-JAN-21:40 | 8687.22 | 13-JAN-15:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 24.01 | 0.00 | 04-JAN-21:40 | 8687.22 | 13-JAN-15:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 111.67 | 0.00 | 01-JAN-00:10 | 9319.43 | 23-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 111.67 | 0.00 | 01-JAN-00:10 | 9319.43 | 23-JUL-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 25.01 | 0.00 | 07-JAN-08:10 | 3097.30 | 12-JAN-16:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 17.08 | 0.00 | 07-JAN-08:10 | 3097.30 | 12-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 17.08 | 0.00 | 07-JAN-08:10 | 3097.30 | 12-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 7.93 | 0.00 | 01-JAN-00:10 | 3076.49 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 7.93 | 0.00 | 01-JAN-00:10 | 3076.49 | 10-AUG-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 23.95 | 0.00 | 07-JAN-08:10 | 3126.19 | 12-JAN-16:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 18.81 | 0.00 | 07-JAN-08:10 | 3126.19 | 12-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 18.81 | 0.00 | 07-JAN-08:10 | 3126.19 | 12-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.14 | 0.00 | 01-JAN-00:10 | 3063.05 | 06-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.14 | 0.00 | 01-JAN-00:10 | 3063.05 | 06-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 119.86 | 0.00 | 01-JAN-08:10 | 19280.10 | 25-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 57.80 | 0.00 | 01-JAN-08:10 | 14269.95 | 15-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 57.80 | 0.00 | 01-JAN-08:10 | 14269.95 | 15-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 62.06 | 0.00 | 01-JAN-00:10 | 19280.10 | 25-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 62.06 | 0.00 | 01-JAN-00:10 | 19280.10 | 25-AUG-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 389.41 | 4090.41 | 13-JAN-11:00 | 22776.91 | 11-JUL-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 389.41 | 4090.41 | 13-JAN-11:00 | 22776.91 | 11-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 389.41 | 4090.41 | 13-JAN-11:00 | 22776.91 | 11-JUL-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 429.46 | 5004.52 | 13-JAN-10:30 | 24083.28 | 11-JUL-21:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 429.46 | 5004.52 | 13-JAN-10:30 | 24083.28 | 11-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 429.46 | 5004.52 | 13-JAN-10:30 | 24083.28 | 11-JUL-21:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 581.10 | 6819.43 | 13-JAN-04:00 | 31081.36 | 22-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 581.10 | 6819.43 | 13-JAN-04:00 | 31081.36 | 22-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 81.08 | 0.23 | 07-MAR-11:00 | 6246.83 | 13-JAN-10:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 24.73 | 0.00 | 21-JAN-20:20 | 6246.83 | 13-JAN-10:30 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 24.73 | 0.00 | 21-JAN-20:20 | 6246.83 | 13-JAN-10:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 56.35 | 0.00 | 01-JAN-00:10 | 5996.52 | 23-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 56.35 | 0.00 | 01-JAN-00:10 | 5996.52 | 23-JUL-13:50 |
PlantLoopHeatingDemand:Facility | 5889.00 | 12611.67 | 29-AUG-01:50 | 967034.05 | 12-JAN-09:10 |
PlantLoopHeatingDemand:Plant | 2007.01 | 12602.84 | 05-SEP-00:20 | 219910.64 | 03-JUL-20:20 |
WaterSystems:PlantLoopHeatingDemand | 2007.01 | 12602.84 | 05-SEP-00:20 | 219910.64 | 03-JUL-20:20 |
General:WaterSystems:PlantLoopHeatingDemand | 986.50 | 12596.13 | 05-SEP-00:30 | 68017.24 | 14-APR-07:00 |
HeatingCoils:EnergyTransfer | 3881.99 | 0.00 | 06-APR-18:30 | 927901.35 | 12-JAN-09:10 |
PlantLoopHeatingDemand:HVAC | 3881.99 | 0.00 | 06-APR-18:30 | 927901.35 | 12-JAN-09:10 |
HeatingCoils:PlantLoopHeatingDemand | 3881.99 | 0.00 | 06-APR-18:30 | 927901.35 | 12-JAN-09:10 |
HeatRecoveryForHeating:EnergyTransfer | 6323.03 | 0.00 | 03-JAN-07:40 | 588647.89 | 07-NOV-06:40 |
HeatRecoveryForCooling:EnergyTransfer | 1.45 | 0.00 | 01-JAN-00:10 | 52682.75 | 29-JUL-16:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 1020.51 | 0.00 | 01-JAN-00:10 | 168892.25 | 01-JUL-21:50 |
WaterSystems:EnergyTransfer | 986.50 | 12596.13 | 05-SEP-00:30 | 68017.24 | 14-APR-07:00 |
WaterUse:WaterSystems:EnergyTransfer | 986.50 | 12596.13 | 05-SEP-00:30 | 68017.24 | 14-APR-07:00 |
Boilers:EnergyTransfer | 3860.29 | 0.00 | 06-APR-18:30 | 921019.90 | 12-JAN-09:10 |
Chillers:EnergyTransfer | 1148.62 | 0.00 | 01-JAN-00:10 | 397887.37 | 29-JUL-18:10 |
HeatRejection:EnergyTransfer | 1501.62 | 0.00 | 01-JAN-00:10 | 507656.17 | 29-JUL-18:10 |
General:HeatRejection:EnergyTransfer | 1501.62 | 0.00 | 01-JAN-00:10 | 507656.17 | 29-JUL-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -290.901 | 0.000 | 0.000 | 146.726 | 102.033 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -100.963 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 9.113 | -32.375 | 0.000 | 0.000 | 15.966 | 5.638 | 10.186 | 23.950 | 0.000 | 0.003 | 0.000 | 0.000 | -16.185 | 0.000 | -2.342 | -13.953 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.006 | -27.907 | 0.000 | 0.000 | 17.498 | 6.529 | 11.795 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -0.933 | -6.989 |
MECH_FLR_1 | 0.000 | 0.000 | 1.991 | -15.400 | 0.000 | 0.000 | 3.779 | 7.530 | 12.471 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -2.181 | -8.193 |
STORAGE_FLR_1 | 0.000 | 0.000 | 3.868 | -7.037 | 0.000 | 0.000 | 2.931 | 1.680 | 3.598 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -1.251 | -3.790 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -588.646 | 0.000 | 0.000 | 11.378 | 4.410 | 658.131 | 0.000 | 0.000 | 0.004 | 0.000 | 0.000 | 0.000 | 0.000 | -3.100 | -82.176 |
CAFE_FLR_1 | 0.000 | 0.000 | 1.599 | -210.334 | 0.000 | 0.000 | 202.749 | 11.606 | 14.341 | 66.939 | 0.000 | 0.005 | 0.000 | 0.000 | -45.832 | 0.000 | -5.278 | -35.793 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.007 | -716.816 | 0.000 | 0.000 | 577.949 | 110.697 | 148.998 | 87.616 | 0.000 | 0.013 | 0.000 | 0.000 | -62.575 | 0.000 | -15.449 | -130.439 |
ROOM_1_FLR_3 | 52.443 | -28.774 | 0.000 | -11.153 | 0.000 | 0.000 | 9.782 | 5.554 | 12.292 | 36.646 | 0.000 | 0.048 | 0.000 | 0.000 | -37.732 | 0.000 | -5.855 | -33.250 |
ROOM_2_FLR_3 | 58.034 | -17.095 | 0.000 | -11.571 | 0.000 | 0.000 | 9.666 | 5.553 | 12.291 | 22.943 | 0.000 | 0.013 | 0.000 | 0.000 | -39.893 | 0.000 | -6.084 | -33.858 |
ROOM_3_MULT19_FLR_3 | 97.358 | -255.887 | 0.041 | -10.124 | 0.000 | 0.000 | 0.000 | 66.316 | 228.754 | 275.604 | 0.000 | 0.002 | 0.000 | 0.000 | -203.210 | 0.000 | -30.052 | -168.802 |
ROOM_4_MULT19_FLR_3 | 226.856 | -152.224 | 0.000 | -154.169 | 0.000 | 0.000 | 184.425 | 66.334 | 228.817 | 69.587 | 0.000 | 0.168 | 0.000 | 0.000 | -221.825 | 0.000 | -41.619 | -206.349 |
ROOM_5_FLR_3 | 50.153 | -34.852 | 0.000 | -11.179 | 0.000 | 0.000 | 9.767 | 5.554 | 12.292 | 45.263 | 0.000 | 0.048 | 0.000 | 0.000 | -37.177 | 0.000 | -5.870 | -33.998 |
ROOM_6_FLR_3 | 55.322 | -23.338 | 0.000 | -11.504 | 0.000 | 0.000 | 9.689 | 5.553 | 12.291 | 31.269 | 0.000 | 0.013 | 0.000 | 0.000 | -38.971 | 0.000 | -6.259 | -34.065 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 24.006 | -111.668 | 0.000 | 0.000 | 120.303 | 51.065 | 0.000 | 38.381 | 0.000 | 0.006 | 0.000 | 0.000 | -47.316 | 0.000 | -6.691 | -68.087 |
ROOM_1_FLR_6 | 18.779 | -6.844 | 0.000 | -2.784 | 0.000 | 0.000 | 2.449 | 1.388 | 3.073 | 9.150 | 0.000 | 0.013 | 0.000 | 0.000 | -9.357 | 0.000 | -1.483 | -14.384 |
ROOM_2_FLR_6 | 20.581 | -4.006 | 0.000 | -2.901 | 0.000 | 0.000 | 2.416 | 1.388 | 3.073 | 5.720 | 0.000 | 0.003 | 0.000 | 0.000 | -9.901 | 0.000 | -1.538 | -14.836 |
ROOM_3_MULT9_FLR_6 | 67.143 | -53.384 | 0.000 | -18.013 | 0.000 | 0.000 | 21.945 | 7.855 | 27.097 | 62.111 | 0.000 | 0.107 | 0.000 | 0.000 | -43.049 | 0.000 | -7.446 | -64.366 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -389.409 | 0.000 | 0.000 | 323.754 | 25.449 | 175.857 | 7.487 | 0.000 | 0.002 | 0.000 | 0.000 | -26.744 | 0.000 | -3.608 | -112.788 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -429.466 | 0.000 | 0.000 | 321.494 | 25.449 | 175.857 | 7.345 | 0.000 | 0.002 | 0.000 | 0.000 | -27.247 | 0.000 | -3.631 | -69.803 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -581.085 | 0.000 | 0.000 | 28.908 | 12.005 | 540.650 | 23.077 | 0.000 | 0.002 | 0.004 | 0.000 | -16.294 | 0.000 | -3.269 | -3.994 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 24.730 | -56.354 | 0.000 | 0.000 | 32.018 | 13.511 | 0.000 | 19.302 | 0.000 | 0.002 | 0.000 | 0.000 | -20.843 | 0.000 | -2.958 | -9.408 |
Total Facility | 646.669 | -576.403 | 65.362 | -3690.796 | 0.000 | 0.000 | 2055.590 | 543.097 | 2434.967 | 832.390 | 0.000 | 0.459 | 0.004 | 0.000 | -904.151 | 0.000 | -156.898 | -1250.285 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 11-JAN-22:00 | 0.00 | 0.00 | 0.00 | -19200.22 | 0.00 | 0.00 | 7042.49 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4384.82 |
RETAIL_1_FLR_1 | 25-AUG-13:30 | 0.00 | 0.00 | 0.00 | -4636.38 | 0.00 | 0.00 | 150.60 | 128.08 | 252.59 | 7210.59 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -6.74 | -3098.73 |
RETAIL_2_FLR_1 | 21-JUN-21:00 | 0.00 | 0.00 | 0.00 | -1688.39 | 0.00 | 0.00 | 697.61 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -0.11 | -235.85 |
MECH_FLR_1 | 12-JUL-21:00 | 0.00 | 0.00 | 0.00 | -1177.66 | 0.00 | 0.00 | 147.52 | 547.34 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -13.57 | -298.90 |
STORAGE_FLR_1 | 23-JUL-10:33 | 0.00 | 0.00 | 0.00 | -611.13 | 0.00 | 0.00 | 44.66 | 45.78 | 101.96 | 0.00 | 0.00 | 0.00 | 420.26 | 0.00 | -0.00 | 0.00 | -1.54 | 0.00 |
LAUNDRY_FLR_1 | 21-JUL-20:00 | 0.00 | 0.00 | 0.00 | -38712.60 | 0.00 | 0.00 | 408.80 | 360.62 | 44299.38 | 0.00 | 0.00 | 3.51 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6359.70 |
CAFE_FLR_1 | 25-AUG-14:10 | 0.00 | 0.00 | 0.00 | -15851.39 | 0.00 | 0.00 | 2968.49 | 86.54 | 355.63 | 17826.36 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7.21 | -5378.42 |
LOBBY_FLR_1 | 11-AUG-21:10 | 0.00 | 0.00 | 0.00 | -39046.78 | 0.00 | 0.00 | 26438.95 | 6372.41 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -412.59 | 0.00 | -30.36 | -711.58 |
ROOM_1_FLR_3 | 22-JUN-18:02 | 0.00 | -12903.18 | 0.00 | -733.25 | 0.00 | 0.00 | 335.49 | 380.45 | 516.26 | 7087.18 | 0.00 | 61.26 | 5255.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 06-JUL-17:32 | 0.00 | -13768.96 | 0.00 | 0.00 | 0.00 | 0.00 | 158.86 | 286.37 | 537.27 | 10134.72 | 0.00 | 0.00 | 2669.53 | 0.00 | -0.00 | 0.00 | -17.80 | 0.00 |
ROOM_3_MULT19_FLR_3 | 25-AUG-13:30 | 0.00 | -64721.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1429.19 | 5097.90 | 86320.40 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -180.58 | -27945.71 |
ROOM_4_MULT19_FLR_3 | 22-JUN-21:51 | 0.00 | -66356.85 | 0.00 | -10654.84 | 0.00 | 0.00 | 7681.66 | 3420.82 | 6864.43 | 1176.11 | 0.00 | 0.00 | 58042.20 | 0.00 | -0.00 | 0.00 | -173.53 | 0.00 |
ROOM_5_FLR_3 | 22-JUN-18:02 | 0.00 | -11943.68 | 0.00 | -719.60 | 0.00 | 0.00 | 335.50 | 380.45 | 516.26 | 1200.47 | 0.00 | 83.16 | 10147.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 11-JUL-08:32 | 0.00 | -13364.41 | 0.00 | -1050.03 | 0.00 | 0.00 | 58.84 | 188.06 | 452.99 | 10934.08 | 0.00 | 0.00 | 2824.84 | 0.00 | -0.00 | 0.00 | -44.38 | 0.00 |
CORRIDOR_FLR_3 | 23-JUL-10:33 | 0.00 | 0.00 | 0.00 | -9333.00 | 0.00 | 0.00 | 1819.27 | 1392.00 | 0.00 | 8172.17 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -9.67 | -2040.76 |
ROOM_1_FLR_6 | 10-AUG-18:02 | 0.00 | -3380.29 | 0.00 | -184.74 | 0.00 | 0.00 | 83.87 | 95.11 | 129.07 | 2108.31 | 0.00 | 0.00 | 1155.11 | 0.00 | -0.00 | 0.00 | -6.45 | 0.00 |
ROOM_2_FLR_6 | 09-MAY-19:42 | 0.00 | -3549.44 | 0.00 | -208.32 | 0.00 | 0.00 | 57.21 | 106.85 | 173.82 | 1063.73 | 0.00 | 0.00 | 2377.68 | 0.00 | -0.00 | 0.00 | -21.54 | 0.00 |
ROOM_3_MULT9_FLR_6 | 23-JUL-15:02 | 0.00 | -19689.96 | 0.00 | -1194.47 | 0.00 | 0.00 | 294.10 | 199.53 | 673.54 | 10686.45 | 0.00 | 20.95 | 9009.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 11-JUL-21:10 | 0.00 | 0.00 | 0.00 | -22777.19 | 0.00 | 0.00 | 15643.86 | 994.72 | 6747.90 | 1887.65 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -9.30 | -2487.65 |
DINING_FLR_6 | 11-JUL-21:10 | 0.00 | 0.00 | 0.00 | -24083.79 | 0.00 | 0.00 | 15643.75 | 994.72 | 6747.90 | 1878.02 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -9.30 | -1171.31 |
KITCHEN_FLR_6 | 22-JUL-10:40 | 0.00 | 0.00 | 0.00 | -31122.08 | 0.00 | 0.00 | 464.20 | 272.71 | 23951.61 | 5162.09 | 0.00 | 0.00 | 1273.57 | 0.00 | -0.00 | 0.00 | -2.09 | 0.00 |
CORRIDOR_FLR_6 | 23-JUL-13:50 | 0.00 | 0.00 | 0.00 | -5995.86 | 0.00 | 0.00 | 308.46 | 245.54 | 0.00 | 5077.14 | 0.00 | 3.19 | 361.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-JUL-18:02 | 0.00 | -163747.98 | 0.00 | -189637.79 | 0.00 | 0.00 | 75795.05 | 36448.72 | 121562.63 | 50891.30 | 0.00 | 376.28 | 68336.25 | 0.00 | 0.00 | 0.00 | -24.46 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 13-JAN-15:20 | 0.00 | 0.00 | 2555.24 | 0.00 | 0.00 | 0.00 | 269.99 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1302.10 | 0.00 | -159.35 | -1744.44 |
RETAIL_2_FLR_1 | 13-JAN-13:00 | 0.00 | 0.00 | 273.47 | 0.00 | 0.00 | 0.00 | 207.94 | 148.32 | 292.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -67.64 | -854.58 |
MECH_FLR_1 | 12-JAN-16:00 | 0.00 | 0.00 | 989.34 | 0.00 | 0.00 | 0.00 | 65.86 | 171.04 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -186.78 | -1348.74 |
STORAGE_FLR_1 | 13-JAN-11:08 | 0.00 | 0.00 | 906.21 | 0.00 | 0.00 | 0.00 | 33.72 | 38.16 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -96.00 | -971.31 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 13-JAN-14:40 | 0.00 | 0.00 | 4082.69 | 0.00 | 0.00 | 0.00 | 2355.80 | 388.02 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3761.79 | 0.00 | -360.79 | -3059.56 |
LOBBY_FLR_1 | 13-JAN-13:10 | 0.00 | 0.00 | 1057.97 | 0.00 | 0.00 | 0.00 | 7010.61 | 2370.93 | 3694.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3185.29 | 0.00 | -1097.19 | -9851.99 |
ROOM_1_FLR_3 | 26-NOV-16:01 | 12409.34 | 301.53 | 0.00 | -301.53 | 0.00 | 0.00 | 163.33 | 141.07 | 305.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2828.77 | 0.00 | -338.32 | -9852.19 |
ROOM_2_FLR_3 | 26-NOV-16:01 | 12142.00 | 298.24 | 0.00 | -298.24 | 0.00 | 0.00 | 163.33 | 141.05 | 305.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2821.65 | 0.00 | -337.94 | -9592.29 |
ROOM_3_MULT19_FLR_3 | 12-JAN-04:10 | 28876.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 561.43 | 3921.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19393.30 | 0.00 | -2378.23 | -11588.34 |
ROOM_4_MULT19_FLR_3 | 26-NOV-16:01 | 66828.37 | 3783.27 | 0.00 | -3783.27 | 0.00 | 0.00 | 3103.17 | 1684.90 | 5687.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15268.75 | 0.00 | -1781.27 | -60254.09 |
ROOM_5_FLR_3 | 26-NOV-16:01 | 12245.68 | 300.49 | 0.00 | -300.49 | 0.00 | 0.00 | 163.33 | 141.07 | 305.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2828.16 | 0.00 | -338.20 | -9689.25 |
ROOM_6_FLR_3 | 26-NOV-16:01 | 11992.92 | 297.30 | 0.00 | -297.30 | 0.00 | 0.00 | 163.32 | 141.05 | 305.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2821.09 | 0.00 | -337.84 | -9443.87 |
CORRIDOR_FLR_3 | 13-JAN-15:00 | 0.00 | 0.00 | 8687.29 | 0.00 | 0.00 | 0.00 | 1385.82 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3803.25 | 0.00 | -454.39 | -6975.48 |
ROOM_1_FLR_6 | 13-JAN-16:02 | 3803.77 | 76.23 | 0.00 | -76.23 | 0.00 | 0.00 | 73.50 | 29.92 | 68.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -693.01 | 0.00 | -86.73 | -3195.94 |
ROOM_2_FLR_6 | 26-NOV-16:01 | 3695.35 | 75.30 | 0.00 | -75.30 | 0.00 | 0.00 | 40.83 | 35.26 | 76.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -696.29 | 0.00 | -84.70 | -3066.83 |
ROOM_3_MULT9_FLR_6 | 13-JAN-16:02 | 19168.65 | 491.28 | 0.00 | -491.28 | 0.00 | 0.00 | 661.48 | 169.29 | 603.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3232.29 | 0.00 | -399.47 | -16971.53 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 13-JAN-10:30 | 0.00 | 0.00 | 6246.75 | 0.00 | 0.00 | 0.00 | 366.68 | 306.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1875.90 | 0.00 | -228.31 | -4816.14 |
Total Facility | 13-JAN-16:02 | 112006.08 | 58546.89 | 16968.45 | -58546.89 | 0.00 | 0.00 | 62654.25 | 12646.14 | 76844.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -64203.65 | 0.00 | -8649.70 | -208265.70 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 22.0767 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 21.9494 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6565 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6565 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9892 | 1.9892 | 1.0503 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4980 | 0.4980 | 0.2629 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2208 | 0.2208 | 0.1166 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1700 | 0.1700 | 0.0898 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0916 | 0.0916 | 0.0483 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3108 | 3.3108 | 1.7481 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9421 | 1.9421 | 1.0254 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1925 | 5.1925 | 2.7416 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3788 | 1.3788 | 0.7280 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0837 | 2.0837 | 1.1002 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1867 | 2.1867 | 1.1546 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2611 | 2.2611 | 1.1939 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7512 | 0.7512 | 0.3966 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 22.0767 | 21.9494 | 22.0767 | 11.6565 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0503 | 1.0503 | 1.0503 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2629 | 0.2629 | 0.2629 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1166 | 0.1166 | 0.1166 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0898 | 0.0898 | 0.0898 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0483 | 0.0483 | 0.0483 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7481 | 1.7481 | 1.7481 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0254 | 1.0254 | 1.0254 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7416 | 2.7416 | 2.7416 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7280 | 0.7280 | 0.7280 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1002 | 1.1002 | 1.1002 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1546 | 1.1546 | 1.1546 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1939 | 1.1939 | 1.1939 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3966 | 0.3966 | 0.3966 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6565 | 11.6565 | 11.6565 | 11.6565 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 78.83 |
Number of hours cooling loads not met | 74.33 |
Number of hours not met | 153.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 4924.24 | 1123356.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 353.00 | 115436.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 543.10 | 45424.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 173.00 | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 952.41 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 22.42 | 1279.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 526.95 | 33044.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 89.62 | 7361.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 210.00 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4740.06 | 2104.44 | 203106.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Other | 0.00 | 32726.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.60 | 1310.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 20.68 | 714.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1771.52 | 4631.53 |
Natural Gas | 1788.84 | 8817.52 |
Additional | 0.00 | 0.00 |
Total | 3560.36 | 13449.05 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 47.87 |
Space Heating | 0.00 |
Space Cooling | 31.11 |
Fans (All) | 46.45 |
Service Water Heating | 28.46 |
Receptacle Equipment | 152.32 |
Miscellaneous (All) | 408.23 |
Subtotal | 408.23 |
Natural Gas [MJ/m2] | |
Space Heating | 434.03 |
Service Water Heating | 185.49 |
Miscellaneous (All) | 777.20 |
Subtotal | 777.20 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 4.04 |
Space Heating | 36.61 |
Space Cooling | 2.62 |
Fans (All) | 3.92 |
Service Water Heating | 18.05 |
Receptacle Equipment | 26.15 |
Miscellaneous | 8.61 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2398. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 2482. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8705.17 | 54.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8459.00 | 301.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8747.00 | 13.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8661.33 | 98.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8459.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 301.00 | 0.00 | 0.00 | 0.00 |
Average | 8738.75 | 21.25 | 0.00 | 0.00 | 0.00 |
Sum | 192252.50 | 467.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4127.50 | 26.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4098.83 | 55.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 55.17 | 0.00 | 0.00 | 0.00 |
Average | 288883.33 | 3.71 | 0.00 | 0.00 | 0.00 |
Sum | 6355433.33 | 81.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8746.33 | 13.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8700.00 | 60.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8294.83 | 465.17 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8740.83 | 19.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8653.50 | 106.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8745.67 | 14.33 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8750.33 | 9.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8294.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 465.17 | 0.00 | 0.00 | 0.00 |
Average | 8728.68 | 31.32 | 0.00 | 0.00 | 0.00 |
Sum | 192031.00 | 689.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2110476.50 | 4952.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4115.50 | 38.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4149.67 | 4.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4080.50 | 73.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1242787.67 | 2927.33 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1243799.67 | 1915.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108263.50 | 5.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2110476.50 | 4952.50 | 0.00 | 0.00 | 0.00 |
Average | 288436.27 | 450.77 | 0.00 | 0.00 | 0.00 |
Sum | 6345598.00 | 9917.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:45
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238846E+11 | 19199.68 | 11-JAN-22:00 | -34.4 | -34.5 | 0.680244E+10 | 4390.85 | 25-JAN-22:10 | -23.3 | -23.5 |
February | 0.183824E+11 | 13675.86 | 28-FEB-22:00 | -29.6 | -29.8 | 0.577891E+10 | 4132.21 | 01-FEB-22:10 | -29.6 | -29.8 |
March | 0.197106E+11 | 12385.60 | 01-MAR-21:53 | -23.9 | -24.5 | 0.642257E+10 | 4011.58 | 30-MAR-22:10 | -18.0 | -19.1 |
April | 0.202569E+11 | 10205.32 | 22-APR-10:33 | 11.87 | 5.55 | 0.633560E+10 | 4074.84 | 14-APR-22:10 | 11.87 | 5.55 |
May | 0.219585E+11 | 10602.56 | 14-MAY-10:33 | 16.83 | 8.94 | 0.662640E+10 | 4124.39 | 26-MAY-22:10 | 2.12 | 0.59 |
June | 0.226013E+11 | 11087.66 | 29-JUN-10:33 | 21.83 | 15.68 | 0.662622E+10 | 4246.30 | 15-JUN-22:10 | 21.83 | 15.68 |
July | 0.257503E+11 | 12222.00 | 23-JUL-10:33 | 22.23 | 15.22 | 0.729806E+10 | 4565.02 | 28-JUL-22:10 | 17.02 | 13.67 |
August | 0.279321E+11 | 12924.96 | 26-AUG-10:33 | 15.93 | 12.30 | 0.788200E+10 | 4837.10 | 31-AUG-21:00 | 8.20 | 4.88 |
September | 0.280049E+11 | 14747.31 | 20-SEP-21:00 | 8.30 | 7.74 | 0.781456E+10 | 4837.01 | 19-SEP-21:19 | 8.30 | 7.74 |
October | 0.285860E+11 | 14934.50 | 06-OCT-21:00 | 7.80 | 3.59 | 0.808162E+10 | 4837.01 | 06-OCT-21:19 | 7.60 | 3.54 |
November | 0.279112E+11 | 15977.81 | 28-NOV-23:00 | -28.9 | -29.1 | 0.748058E+10 | 4839.25 | 07-NOV-22:49 | -28.9 | -29.1 |
December | 0.259217E+11 | 16418.80 | 13-DEC-01:00 | -30.0 | -30.2 | 0.698619E+10 | 4587.29 | 26-DEC-22:10 | -21.9 | -22.1 |
Annual Sum or Average | 0.290901E+12 | 0.841352E+11 | ||||||||
Minimum of Months | 0.183824E+11 | 10205.32 | -34.4 | -34.5 | 0.577891E+10 | 4011.58 | -29.6 | -29.8 | ||
Maximum of Months | 0.285860E+11 | 19199.68 | 22.23 | 15.68 | 0.808162E+10 | 4839.25 | 21.83 | 15.68 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26864050.59 | 1098.90 | 30-JAN-12:30 | -23.9 | -24.3 | 0.610578E+09 | 364.23 | 26-JAN-00:49 | -23.9 | -24.3 |
February | 0.412857E+09 | 2141.94 | 15-FEB-13:40 | -8.7 | -9.6 | 0.559723E+09 | 364.36 | 18-FEB-04:49 | -24.0 | -24.3 |
March | 0.173170E+10 | 2950.45 | 27-MAR-14:10 | -5.0 | -8.3 | 0.630833E+09 | 364.35 | 03-MAR-01:39 | -5.0 | -8.3 |
April | 0.397084E+10 | 4378.13 | 22-APR-13:30 | 15.30 | 6.96 | 0.628242E+09 | 415.93 | 21-APR-21:30 | 15.30 | 6.96 |
May | 0.499941E+10 | 4157.26 | 12-MAY-13:30 | 20.60 | 9.86 | 0.651529E+09 | 420.61 | 31-MAY-21:30 | 16.00 | 9.64 |
June | 0.542741E+10 | 3671.52 | 29-JUN-14:10 | 25.68 | 16.21 | 0.648005E+09 | 431.61 | 21-JUN-21:19 | 25.68 | 16.21 |
July | 0.560863E+10 | 4378.24 | 23-JUL-13:30 | 25.00 | 15.26 | 0.665445E+09 | 434.38 | 21-JUL-21:19 | 25.00 | 15.26 |
August | 0.530643E+10 | 4635.84 | 25-AUG-13:30 | 21.70 | 14.78 | 0.661072E+09 | 437.49 | 11-AUG-21:30 | 21.70 | 14.78 |
September | 0.338483E+10 | 3968.31 | 09-SEP-13:30 | 13.35 | 8.71 | 0.612853E+09 | 391.60 | 08-SEP-21:30 | 13.35 | 8.71 |
October | 0.142776E+10 | 3048.49 | 03-OCT-13:30 | 10.85 | 6.24 | 0.622626E+09 | 366.01 | 03-OCT-21:30 | 7.20 | 2.97 |
November | 78115846.03 | 1809.77 | 08-NOV-13:30 | -13.6 | -14.4 | 0.599289E+09 | 364.24 | 07-NOV-22:49 | -13.6 | -14.4 |
December | 160570.13 | 45.16 | 24-DEC-22:00 | -5.0 | -5.4 | 0.618373E+09 | 364.25 | 19-DEC-00:00 | -5.0 | -5.4 |
Annual Sum or Average | 0.323750E+11 | 0.750857E+10 | ||||||||
Minimum of Months | 160570.13 | 45.16 | -23.9 | -24.3 | 0.559723E+09 | 364.23 | -24.0 | -24.3 | ||
Maximum of Months | 0.560863E+10 | 4635.84 | 25.68 | 16.21 | 0.665445E+09 | 437.49 | 25.68 | 16.21 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147558E+10 | 1184.30 | 30-JAN-19:25 | -23.9 | -24.3 | 0.728025E+09 | 470.24 | 23-JAN-23:10 | -23.9 | -24.3 |
February | 0.164103E+10 | 1312.76 | 21-FEB-19:53 | -23.9 | -24.1 | 0.670115E+09 | 494.17 | 09-FEB-23:10 | -23.9 | -24.1 |
March | 0.221620E+10 | 1362.84 | 01-MAR-21:53 | -23.9 | -24.5 | 0.778302E+09 | 520.45 | 22-MAR-22:10 | 1.42 | -0.3 |
April | 0.260695E+10 | 1428.72 | 21-APR-20:10 | 11.83 | 4.93 | 0.830929E+09 | 569.52 | 21-APR-21:49 | 7.67 | 2.50 |
May | 0.292786E+10 | 1464.32 | 10-MAY-21:00 | 14.40 | 6.20 | 0.893625E+09 | 569.55 | 11-MAY-21:40 | 12.20 | 6.17 |
June | 0.301612E+10 | 1688.28 | 21-JUN-21:00 | 23.90 | 13.75 | 0.892807E+09 | 569.56 | 02-JUN-21:40 | 23.90 | 13.75 |
July | 0.312389E+10 | 1674.12 | 12-JUL-21:00 | 18.90 | 11.72 | 0.917018E+09 | 569.56 | 21-JUL-23:10 | 19.72 | 15.53 |
August | 0.303826E+10 | 1663.20 | 11-AUG-21:00 | 22.80 | 14.12 | 0.914286E+09 | 569.55 | 03-AUG-22:10 | 22.80 | 14.12 |
September | 0.261372E+10 | 1310.94 | 10-SEP-10:33 | 13.87 | 7.59 | 0.831561E+09 | 566.13 | 08-SEP-21:40 | 13.87 | 7.59 |
October | 0.232184E+10 | 1204.47 | 03-OCT-20:00 | 6.10 | 2.72 | 0.795488E+09 | 539.48 | 03-OCT-22:10 | 7.30 | 3.10 |
November | 0.160209E+10 | 1386.55 | 08-NOV-20:53 | -23.9 | -24.2 | 0.709359E+09 | 477.69 | 01-NOV-22:10 | -23.9 | -24.2 |
December | 0.132310E+10 | 1340.78 | 27-DEC-20:13 | -24.1 | -24.3 | 0.723693E+09 | 459.91 | 26-DEC-23:10 | -24.1 | -24.3 |
Annual Sum or Average | 0.279067E+11 | 0.968521E+10 | ||||||||
Minimum of Months | 0.132310E+10 | 1184.30 | -24.1 | -24.5 | 0.670115E+09 | 459.91 | -24.1 | -24.3 | ||
Maximum of Months | 0.312389E+10 | 1688.28 | 23.90 | 14.12 | 0.917018E+09 | 569.56 | 23.90 | 15.53 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146744E+09 | 625.33 | 23-JAN-22:00 | -15.6 | -16.0 | 0.151695E+09 | 89.14 | 26-JAN-02:00 | -24.4 | -24.6 |
February | 0.284127E+09 | 706.07 | 09-FEB-21:00 | -8.9 | -9.2 | 0.137246E+09 | 92.52 | 09-FEB-22:10 | -9.6 | -9.9 |
March | 0.774074E+09 | 761.17 | 22-MAR-20:00 | 2.80 | 0.30 | 0.153255E+09 | 96.48 | 22-MAR-21:10 | 2.12 | 0.08 |
April | 0.164209E+10 | 956.27 | 22-APR-10:33 | 11.87 | 5.55 | 0.158179E+09 | 107.78 | 21-APR-21:19 | 11.87 | 5.55 |
May | 0.213609E+10 | 1058.66 | 14-MAY-10:33 | 16.83 | 8.94 | 0.180053E+09 | 114.49 | 12-MAY-21:19 | 16.83 | 8.94 |
June | 0.228136E+10 | 1128.87 | 22-JUN-21:00 | 20.60 | 12.02 | 0.185931E+09 | 120.45 | 22-JUN-22:10 | 19.22 | 11.60 |
July | 0.239167E+10 | 1177.66 | 12-JUL-21:00 | 18.90 | 11.72 | 0.192876E+09 | 120.45 | 14-JUL-21:49 | 16.28 | 14.14 |
August | 0.228680E+10 | 1084.73 | 01-AUG-10:33 | 15.93 | 12.83 | 0.189610E+09 | 120.01 | 02-AUG-21:10 | 20.40 | 14.60 |
September | 0.188776E+10 | 971.06 | 10-SEP-10:33 | 13.87 | 7.59 | 0.166434E+09 | 110.72 | 01-SEP-21:10 | 13.87 | 7.59 |
October | 0.128943E+10 | 829.53 | 04-OCT-20:00 | 3.30 | 1.48 | 0.156448E+09 | 102.62 | 04-OCT-21:10 | 3.30 | 1.41 |
November | 0.186478E+09 | 665.24 | 02-NOV-20:00 | -9.4 | -9.7 | 0.146749E+09 | 89.89 | 02-NOV-21:10 | -9.3 | -9.5 |
December | 92956000.07 | 598.40 | 24-DEC-21:00 | -7.2 | -7.4 | 0.151697E+09 | 89.14 | 09-DEC-01:10 | -7.2 | -7.4 |
Annual Sum or Average | 0.153996E+11 | 0.197017E+10 | ||||||||
Minimum of Months | 92956000.07 | 598.40 | -15.6 | -16.0 | 0.137246E+09 | 89.14 | -24.4 | -24.6 | ||
Maximum of Months | 0.239167E+10 | 1177.66 | 20.60 | 12.83 | 0.192876E+09 | 120.45 | 20.40 | 14.60 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 565534.42 | 51.81 | 21-JAN-21:50 | -2.5 | -3.6 | 0.116660E+09 | 68.57 | 26-JAN-01:49 | -23.9 | -24.2 |
February | 16801146.60 | 203.45 | 09-FEB-22:00 | -9.4 | -9.7 | 0.105502E+09 | 68.57 | 21-FEB-01:19 | -23.9 | -24.1 |
March | 0.130358E+09 | 380.59 | 22-MAR-20:00 | 2.80 | 0.30 | 0.117278E+09 | 70.74 | 22-MAR-22:10 | 1.42 | -0.3 |
April | 0.744183E+09 | 502.52 | 22-APR-10:33 | 11.87 | 5.55 | 0.118281E+09 | 79.35 | 21-APR-21:40 | 11.87 | 5.55 |
May | 0.110979E+10 | 560.24 | 14-MAY-10:33 | 16.83 | 8.94 | 0.134619E+09 | 84.77 | 12-MAY-21:40 | 16.83 | 8.94 |
June | 0.119887E+10 | 589.75 | 22-JUN-10:33 | 21.33 | 12.72 | 0.140164E+09 | 90.43 | 22-JUN-21:49 | 19.60 | 11.77 |
July | 0.125557E+10 | 611.14 | 23-JUL-10:33 | 22.23 | 15.22 | 0.145308E+09 | 90.73 | 12-JUL-21:40 | 22.23 | 15.22 |
August | 0.119172E+10 | 574.87 | 01-AUG-10:33 | 15.93 | 12.83 | 0.142031E+09 | 89.11 | 02-AUG-22:10 | 19.22 | 14.18 |
September | 0.948422E+09 | 509.88 | 10-SEP-10:33 | 13.87 | 7.59 | 0.123345E+09 | 81.33 | 01-SEP-22:10 | 13.87 | 7.59 |
October | 0.438488E+09 | 410.37 | 04-OCT-20:00 | 3.30 | 1.48 | 0.117989E+09 | 74.53 | 04-OCT-22:10 | 3.30 | 1.07 |
November | 2130327.49 | 81.15 | 01-NOV-21:00 | -8.9 | -9.5 | 0.112879E+09 | 68.57 | 08-NOV-02:30 | -24.1 | -24.4 |
December | 439429.46 | 54.63 | 24-DEC-22:00 | -5.0 | -5.4 | 0.116692E+09 | 68.57 | 19-DEC-01:39 | -5.0 | -5.4 |
Annual Sum or Average | 0.703733E+10 | 0.149075E+10 | ||||||||
Minimum of Months | 439429.46 | 51.81 | -9.4 | -9.7 | 0.105502E+09 | 68.57 | -24.1 | -24.4 | ||
Maximum of Months | 0.125557E+10 | 611.14 | 22.23 | 15.22 | 0.145308E+09 | 90.73 | 22.23 | 15.22 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.472666E+11 | 36248.61 | 20-JAN-21:00 | -13.3 | -13.4 | 0.555951E+09 | 381.59 | 06-JAN-22:10 | -13.3 | -13.4 |
February | 0.432031E+11 | 36794.18 | 09-FEB-21:00 | -8.9 | -9.2 | 0.508762E+09 | 381.59 | 02-FEB-22:10 | -8.9 | -9.2 |
March | 0.489643E+11 | 37385.98 | 22-MAR-20:00 | 2.80 | 0.30 | 0.580244E+09 | 381.59 | 22-MAR-21:10 | 2.12 | 0.08 |
April | 0.489321E+11 | 38048.19 | 21-APR-20:00 | 12.20 | 5.22 | 0.568928E+09 | 381.65 | 28-APR-21:10 | 3.53 | 1.78 |
May | 0.521718E+11 | 38460.06 | 31-MAY-20:00 | 17.20 | 10.12 | 0.591368E+09 | 381.70 | 17-MAY-21:10 | 17.20 | 10.12 |
June | 0.512468E+11 | 38634.16 | 29-JUN-20:00 | 25.00 | 16.66 | 0.574269E+09 | 381.80 | 16-JUN-21:10 | 25.00 | 16.66 |
July | 0.528367E+11 | 38710.36 | 21-JUL-20:00 | 25.00 | 16.11 | 0.591951E+09 | 381.68 | 12-JUL-21:10 | 25.00 | 16.11 |
August | 0.525956E+11 | 38583.89 | 11-AUG-20:00 | 24.40 | 14.81 | 0.593313E+09 | 381.73 | 23-AUG-21:10 | 18.43 | 14.55 |
September | 0.493727E+11 | 37970.16 | 01-SEP-20:00 | 12.20 | 9.06 | 0.570717E+09 | 381.71 | 08-SEP-21:10 | 7.20 | 5.85 |
October | 0.493672E+11 | 37597.35 | 03-OCT-20:00 | 6.10 | 2.72 | 0.585842E+09 | 381.60 | 19-OCT-21:10 | -1.7 | -1.7 |
November | 0.459273E+11 | 36363.20 | 01-NOV-20:00 | -8.9 | -9.5 | 0.548371E+09 | 383.63 | 07-NOV-22:49 | -23.8 | -24.0 |
December | 0.467599E+11 | 36015.14 | 26-DEC-21:00 | -21.1 | -21.5 | 0.561536E+09 | 382.76 | 08-DEC-22:30 | -21.1 | -21.5 |
Annual Sum or Average | 0.588644E+12 | 0.683125E+10 | ||||||||
Minimum of Months | 0.432031E+11 | 36015.14 | -21.1 | -21.5 | 0.508762E+09 | 381.59 | -23.8 | -24.0 | ||
Maximum of Months | 0.528367E+11 | 38710.36 | 25.00 | 16.66 | 0.593313E+09 | 383.63 | 25.00 | 16.66 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.795756E+10 | 7074.48 | 06-JAN-23:10 | -3.0 | -4.1 | 0.808938E+10 | 4944.37 | 06-JAN-23:10 | -3.0 | -4.1 |
February | 0.107175E+11 | 8570.05 | 20-FEB-13:00 | -18.3 | -18.9 | 0.741862E+10 | 5193.19 | 09-FEB-22:40 | -18.3 | -18.9 |
March | 0.174062E+11 | 12095.74 | 27-MAR-15:03 | -4.9 | -8.2 | 0.862640E+10 | 5721.80 | 22-MAR-21:40 | -4.9 | -8.2 |
April | 0.221410E+11 | 15780.72 | 22-APR-13:30 | 15.30 | 6.96 | 0.909617E+10 | 6336.35 | 21-APR-21:30 | 15.30 | 6.96 |
May | 0.245165E+11 | 14777.08 | 13-MAY-13:10 | 18.98 | 8.91 | 0.965625E+10 | 6382.57 | 31-MAY-21:40 | 15.77 | 9.56 |
June | 0.247237E+11 | 13734.39 | 20-JUN-15:03 | 25.10 | 14.57 | 0.964100E+10 | 6387.11 | 20-JUN-21:40 | 21.67 | 13.58 |
July | 0.256239E+11 | 15027.60 | 23-JUL-13:30 | 25.00 | 15.26 | 0.987819E+10 | 6462.66 | 21-JUL-22:10 | 25.00 | 15.26 |
August | 0.250948E+11 | 15848.52 | 25-AUG-14:10 | 22.88 | 15.43 | 0.983767E+10 | 6462.76 | 10-AUG-22:10 | 22.88 | 15.43 |
September | 0.205576E+11 | 14752.39 | 09-SEP-13:30 | 13.35 | 8.71 | 0.889734E+10 | 6150.83 | 08-SEP-21:40 | 13.35 | 8.71 |
October | 0.163453E+11 | 11240.88 | 03-OCT-13:30 | 10.85 | 6.24 | 0.855532E+10 | 5924.14 | 03-OCT-21:40 | 7.20 | 3.00 |
November | 0.859755E+10 | 7374.66 | 08-NOV-13:30 | -13.6 | -14.4 | 0.788707E+10 | 5046.79 | 01-NOV-21:40 | -13.6 | -14.4 |
December | 0.665055E+10 | 6825.55 | 19-DEC-23:10 | -8.7 | -9.2 | 0.813612E+10 | 4847.83 | 19-DEC-23:10 | -8.7 | -9.2 |
Annual Sum or Average | 0.210332E+12 | 0.105720E+12 | ||||||||
Minimum of Months | 0.665055E+10 | 6825.55 | -18.3 | -18.9 | 0.741862E+10 | 4847.83 | -18.3 | -18.9 | ||
Maximum of Months | 0.256239E+11 | 15848.52 | 25.10 | 15.43 | 0.987819E+10 | 6462.76 | 25.00 | 15.43 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.434805E+11 | 29613.07 | 30-JAN-22:05 | -25.8 | -26.1 | 0.254310E+11 | 16842.71 | 20-JAN-23:10 | -25.8 | -26.1 |
February | 0.455445E+11 | 31931.20 | 21-FEB-19:53 | -23.9 | -24.1 | 0.234495E+11 | 17595.57 | 09-FEB-22:49 | -23.9 | -24.1 |
March | 0.578282E+11 | 33353.56 | 01-MAR-21:53 | -23.9 | -24.5 | 0.275778E+11 | 18576.07 | 22-MAR-22:10 | 1.42 | -0.3 |
April | 0.646577E+11 | 34384.75 | 21-APR-21:10 | 9.53 | 3.30 | 0.291049E+11 | 19184.85 | 21-APR-23:19 | 4.80 | 1.11 |
May | 0.720505E+11 | 35850.61 | 31-MAY-21:10 | 16.47 | 9.79 | 0.310880E+11 | 19186.24 | 11-MAY-21:40 | 16.47 | 9.79 |
June | 0.736719E+11 | 38343.74 | 21-JUN-21:03 | 23.53 | 13.66 | 0.307359E+11 | 19186.29 | 02-JUN-21:40 | 23.53 | 13.66 |
July | 0.764041E+11 | 38929.12 | 21-JUL-21:10 | 22.70 | 14.59 | 0.315998E+11 | 19186.72 | 01-JUL-00:10 | 22.70 | 14.59 |
August | 0.746003E+11 | 39052.68 | 11-AUG-21:10 | 22.33 | 14.00 | 0.316275E+11 | 19186.27 | 01-AUG-22:10 | 22.33 | 14.00 |
September | 0.645385E+11 | 32532.47 | 10-SEP-10:33 | 13.87 | 7.59 | 0.291635E+11 | 19184.58 | 01-SEP-21:19 | 13.87 | 7.59 |
October | 0.584624E+11 | 29365.00 | 03-OCT-20:00 | 6.10 | 2.72 | 0.281175E+11 | 19177.05 | 03-OCT-22:10 | 7.30 | 3.10 |
November | 0.448195E+11 | 33419.15 | 08-NOV-20:53 | -23.9 | -24.2 | 0.248194E+11 | 17151.67 | 01-NOV-22:10 | -23.9 | -24.2 |
December | 0.407531E+11 | 32566.36 | 27-DEC-20:13 | -24.1 | -24.3 | 0.250627E+11 | 16535.05 | 19-DEC-23:10 | -24.1 | -24.3 |
Annual Sum or Average | 0.716811E+12 | 0.337778E+12 | ||||||||
Minimum of Months | 0.407531E+11 | 29365.00 | -25.8 | -26.1 | 0.234495E+11 | 16535.05 | -25.8 | -26.1 | ||
Maximum of Months | 0.764041E+11 | 39052.68 | 23.53 | 14.59 | 0.316275E+11 | 19186.72 | 23.53 | 14.59 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 900055.13 | 926.10 | 22-JAN-09:04 | -6.2 | -6.5 | 92318884.36 | 56.69 | 10-JAN-04:19 | -6.2 | -6.5 |
February | 5522401.23 | 1104.71 | 11-FEB-19:04 | -3.0 | -3.9 | 83674806.61 | 56.69 | 07-FEB-04:19 | -3.0 | -3.9 |
March | 75471428.14 | 3020.71 | 31-MAR-15:01 | -9.9 | -12.2 | 94572145.22 | 56.69 | 05-MAR-02:20 | -9.9 | -12.2 |
April | 0.811193E+09 | 3164.62 | 21-APR-18:01 | 14.22 | 5.92 | 94415532.09 | 56.69 | 21-APR-22:19 | 6.47 | 1.92 |
May | 0.145145E+10 | 3289.41 | 31-MAY-18:02 | 21.13 | 10.92 | 98713972.25 | 56.69 | 11-MAY-21:10 | 21.13 | 10.92 |
June | 0.205294E+10 | 3409.14 | 22-JUN-18:02 | 23.22 | 12.45 | 95840082.08 | 56.70 | 19-JUN-21:10 | 23.22 | 12.45 |
July | 0.197756E+10 | 3239.77 | 06-JUL-18:01 | 24.40 | 15.16 | 98918770.47 | 56.70 | 24-JUL-21:49 | 18.98 | 14.94 |
August | 0.153960E+10 | 3108.31 | 17-AUG-18:01 | 17.88 | 10.69 | 98805609.03 | 56.70 | 02-AUG-21:40 | 17.88 | 10.69 |
September | 0.439846E+09 | 3085.96 | 02-SEP-18:02 | 16.52 | 10.34 | 93963893.66 | 56.69 | 01-SEP-01:00 | 16.52 | 10.34 |
October | 33858519.41 | 2910.15 | 13-OCT-15:02 | 1.70 | -2.0 | 93979170.51 | 56.69 | 15-OCT-23:19 | -0.8 | -1.2 |
November | 1189307.77 | 790.66 | 04-NOV-08:04 | -8.3 | -9.8 | 89404508.08 | 56.69 | 10-NOV-04:19 | -18.9 | -19.3 |
December | 525399.18 | 949.08 | 24-DEC-19:04 | -4.0 | -4.2 | 92229385.86 | 56.69 | 29-DEC-04:19 | -15.8 | -16.2 |
Annual Sum or Average | 0.839006E+10 | 0.112684E+10 | ||||||||
Minimum of Months | 525399.18 | 790.66 | -9.9 | -12.2 | 83674806.61 | 56.69 | -18.9 | -19.3 | ||
Maximum of Months | 0.205294E+10 | 3409.14 | 24.40 | 15.16 | 98918770.47 | 56.70 | 23.22 | 14.94 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 637445.58 | 1014.68 | 22-JAN-09:04 | -6.2 | -6.5 | 92312686.38 | 56.69 | 27-JAN-04:19 | -14.8 | -15.1 |
February | 2008665.33 | 1193.95 | 08-FEB-19:04 | 0.22 | -1.6 | 83421134.23 | 56.69 | 20-FEB-02:20 | -18.7 | -19.0 |
March | 14287470.47 | 2227.06 | 27-MAR-18:01 | -7.2 | -9.8 | 93158705.65 | 56.69 | 03-MAR-00:20 | -7.2 | -9.8 |
April | 0.442817E+09 | 2851.78 | 21-APR-18:01 | 14.22 | 5.92 | 93038607.69 | 56.69 | 21-APR-21:30 | 8.60 | 2.92 |
May | 0.949512E+09 | 3330.00 | 09-MAY-20:01 | 13.35 | 5.95 | 0.103257E+09 | 89.83 | 10-MAY-21:10 | 14.13 | 6.05 |
June | 0.148517E+10 | 3232.01 | 26-JUN-21:51 | 19.40 | 13.93 | 0.107910E+09 | 103.81 | 28-JUN-21:10 | 19.72 | 14.76 |
July | 0.142475E+10 | 3442.23 | 06-JUL-17:32 | 24.23 | 15.21 | 0.108445E+09 | 91.25 | 11-JUL-21:30 | 21.10 | 13.07 |
August | 0.949049E+09 | 3064.05 | 02-AUG-21:51 | 19.40 | 14.21 | 0.105961E+09 | 92.29 | 10-AUG-21:10 | 17.93 | 10.68 |
September | 0.211650E+09 | 2886.78 | 02-SEP-19:41 | 13.27 | 9.27 | 93300601.73 | 56.69 | 01-SEP-01:19 | 13.27 | 9.27 |
October | 10590748.85 | 1929.36 | 03-OCT-15:02 | 12.62 | 6.83 | 93208660.44 | 56.69 | 24-OCT-03:20 | -4.4 | -4.6 |
November | 405836.84 | 858.45 | 04-NOV-08:04 | -8.3 | -9.8 | 89378448.58 | 56.69 | 17-NOV-04:19 | -20.6 | -20.8 |
December | 411384.28 | 867.16 | 24-DEC-19:04 | -4.0 | -4.2 | 92229193.27 | 56.69 | 17-DEC-02:20 | -4.0 | -4.2 |
Annual Sum or Average | 0.549130E+10 | 0.115562E+10 | ||||||||
Minimum of Months | 405836.84 | 858.45 | -8.3 | -9.8 | 83421134.23 | 56.69 | -20.6 | -20.8 | ||
Maximum of Months | 0.148517E+10 | 3442.23 | 24.23 | 15.21 | 0.108445E+09 | 103.81 | 21.10 | 14.76 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 64164.02 | 11.33 | 25-JAN-15:20 | -19.3 | -19.6 | 0.00 | 0.00 | 01-JAN-00:10 | -19.3 | -19.6 |
February | 2851208.93 | 84.94 | 15-FEB-15:20 | -7.2 | -8.6 | 0.00 | 0.00 | 01-FEB-00:10 | -7.2 | -8.6 |
March | 64963163.67 | 517.10 | 31-MAR-13:20 | -11.5 | -13.4 | 0.00 | 0.00 | 01-MAR-00:10 | -11.5 | -13.4 |
April | 0.457551E+09 | 804.77 | 22-APR-13:20 | 15.20 | 6.93 | 0.00 | 0.00 | 01-APR-00:10 | 15.20 | 6.93 |
May | 0.588920E+09 | 766.95 | 12-MAY-13:15 | 20.60 | 9.86 | 0.00 | 0.00 | 01-MAY-00:10 | 20.60 | 9.86 |
June | 0.661599E+09 | 678.42 | 30-JUN-12:30 | 26.15 | 17.75 | 0.00 | 0.00 | 01-JUN-00:10 | 26.15 | 17.75 |
July | 0.689610E+09 | 807.73 | 23-JUL-13:30 | 25.00 | 15.26 | 0.00 | 0.00 | 01-JUL-00:10 | 25.00 | 15.26 |
August | 0.640980E+09 | 851.58 | 25-AUG-13:30 | 21.70 | 14.78 | 0.00 | 0.00 | 01-AUG-00:10 | 21.70 | 14.78 |
September | 0.318637E+09 | 757.41 | 09-SEP-13:10 | 12.98 | 8.62 | 0.00 | 0.00 | 01-SEP-00:10 | 12.98 | 8.62 |
October | 73742497.36 | 601.57 | 03-OCT-12:50 | 9.63 | 5.75 | 0.00 | 0.00 | 01-OCT-00:10 | 9.63 | 5.75 |
November | 533368.96 | 44.64 | 08-NOV-15:20 | -14.6 | -15.2 | 0.00 | 0.00 | 01-NOV-00:10 | -14.6 | -15.2 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.349945E+10 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.00 | 0.00 | -25.8 | -26.0 | ||
Maximum of Months | 0.689610E+09 | 851.58 | 26.15 | 17.75 | 0.00 | 0.00 | 26.15 | 17.75 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3611699.38 | 376.29 | 09-JAN-09:04 | -18.9 | -19.1 | 93377305.08 | 56.69 | 03-JAN-22:10 | -18.9 | -19.1 |
February | 6666512.80 | 440.79 | 12-FEB-16:04 | -3.9 | -5.1 | 84622440.23 | 56.69 | 23-FEB-00:20 | -22.8 | -23.0 |
March | 26958233.65 | 762.84 | 22-MAR-18:02 | 2.98 | 0.38 | 94675159.82 | 56.69 | 22-MAR-23:19 | -0.2 | -1.5 |
April | 0.198791E+09 | 845.39 | 30-APR-18:02 | 9.72 | 3.97 | 93216591.99 | 56.69 | 27-APR-21:10 | 9.72 | 3.97 |
May | 0.516276E+09 | 939.03 | 31-MAY-15:02 | 21.28 | 10.75 | 99740394.52 | 74.62 | 11-MAY-21:10 | 21.28 | 10.75 |
June | 0.695087E+09 | 1013.31 | 22-JUN-21:51 | 19.40 | 11.71 | 0.101011E+09 | 79.78 | 19-JUN-21:19 | 19.40 | 11.71 |
July | 0.702403E+09 | 958.02 | 29-JUL-18:02 | 27.12 | 18.22 | 0.104191E+09 | 78.80 | 10-JUL-21:49 | 27.12 | 18.22 |
August | 0.531161E+09 | 950.70 | 02-AUG-21:51 | 19.40 | 14.21 | 0.102236E+09 | 75.66 | 02-AUG-21:40 | 19.40 | 14.21 |
September | 0.272813E+09 | 832.11 | 07-SEP-18:01 | 14.13 | 7.59 | 93761228.70 | 56.69 | 20-SEP-21:10 | 8.30 | 7.74 |
October | 76332899.45 | 777.26 | 03-OCT-18:01 | 9.72 | 4.62 | 95102720.29 | 56.69 | 05-OCT-21:10 | 7.30 | 3.88 |
November | 4347745.94 | 409.91 | 14-NOV-19:04 | -15.0 | -15.4 | 90449267.12 | 56.69 | 10-NOV-04:19 | -15.0 | -15.4 |
December | 2327295.90 | 456.99 | 24-DEC-09:01 | 0.18 | -1.3 | 93205534.50 | 56.69 | 19-DEC-04:19 | 0.18 | -1.3 |
Annual Sum or Average | 0.303678E+10 | 0.114559E+10 | ||||||||
Minimum of Months | 2327295.90 | 376.29 | -18.9 | -19.1 | 84622440.23 | 56.69 | -22.8 | -23.0 | ||
Maximum of Months | 0.702403E+09 | 1013.31 | 27.12 | 18.22 | 0.104191E+09 | 79.78 | 27.12 | 18.22 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 874361.60 | 942.63 | 22-JAN-09:04 | -6.2 | -6.5 | 92332621.14 | 56.69 | 10-JAN-04:19 | -6.2 | -6.5 |
February | 7533562.07 | 1122.34 | 07-FEB-19:04 | -1.1 | -2.8 | 83851225.51 | 56.69 | 07-FEB-04:19 | -1.1 | -2.8 |
March | 0.131688E+09 | 2868.95 | 31-MAR-15:01 | -9.9 | -12.2 | 95729466.76 | 56.69 | 14-MAR-03:20 | -9.9 | -12.2 |
April | 0.783111E+09 | 2950.90 | 20-APR-15:01 | 13.80 | 6.27 | 94894222.92 | 56.69 | 28-APR-21:30 | 2.80 | 1.37 |
May | 0.191433E+10 | 3111.00 | 12-MAY-15:01 | 20.00 | 9.30 | 99054396.77 | 56.69 | 13-MAY-23:00 | 12.20 | 5.89 |
June | 0.229481E+10 | 3165.85 | 22-JUN-18:02 | 23.22 | 12.45 | 95950308.79 | 56.69 | 30-JUN-21:00 | 17.60 | 14.01 |
July | 0.237473E+10 | 3093.71 | 29-JUL-18:02 | 27.12 | 18.22 | 99057114.12 | 56.70 | 24-JUL-21:00 | 27.12 | 18.22 |
August | 0.180396E+10 | 3040.70 | 23-AUG-18:02 | 24.90 | 15.24 | 99053219.20 | 56.70 | 04-AUG-21:10 | 24.90 | 15.24 |
September | 0.579545E+09 | 2871.95 | 07-SEP-18:01 | 14.13 | 7.59 | 94514460.96 | 56.69 | 01-SEP-00:30 | 14.13 | 7.59 |
October | 69648986.16 | 2784.33 | 04-OCT-08:62 | 7.88 | 2.97 | 94524578.97 | 56.69 | 01-OCT-01:19 | 7.88 | 2.97 |
November | 981601.25 | 834.13 | 04-NOV-08:04 | -8.3 | -9.8 | 89412544.91 | 56.69 | 10-NOV-04:19 | -18.9 | -19.3 |
December | 464058.39 | 897.79 | 24-DEC-09:04 | 0.18 | -1.3 | 92229783.98 | 56.69 | 29-DEC-04:19 | -15.8 | -16.2 |
Annual Sum or Average | 0.996168E+10 | 0.113060E+10 | ||||||||
Minimum of Months | 464058.39 | 834.13 | -9.9 | -12.2 | 83851225.51 | 56.69 | -18.9 | -19.3 | ||
Maximum of Months | 0.237473E+10 | 3165.85 | 27.12 | 18.22 | 99057114.12 | 56.70 | 27.12 | 18.22 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 558920.58 | 899.36 | 22-JAN-09:04 | -6.2 | -6.5 | 92317543.64 | 56.69 | 27-JAN-04:19 | -14.8 | -15.1 |
February | 2346392.99 | 1059.53 | 11-FEB-19:04 | -3.0 | -3.9 | 83485879.49 | 56.69 | 20-FEB-02:20 | -18.7 | -19.0 |
March | 41292874.34 | 2420.17 | 27-MAR-08:61 | -14.4 | -15.8 | 94108114.05 | 56.69 | 07-MAR-04:19 | -14.4 | -15.8 |
April | 0.385066E+09 | 2653.33 | 23-APR-08:62 | 6.97 | 1.91 | 93850291.49 | 56.69 | 28-APR-21:10 | 3.53 | 1.78 |
May | 0.143638E+10 | 2908.13 | 14-MAY-20:41 | 13.68 | 7.57 | 0.101710E+09 | 78.07 | 12-MAY-21:10 | 13.68 | 7.57 |
June | 0.179997E+10 | 3114.95 | 29-JUN-08:51 | 18.90 | 14.54 | 0.103646E+09 | 82.12 | 22-JUN-21:40 | 18.90 | 14.54 |
July | 0.181707E+10 | 3603.63 | 11-JUL-08:32 | 20.53 | 14.32 | 0.107360E+09 | 85.54 | 07-JUL-21:10 | 20.53 | 14.32 |
August | 0.124837E+10 | 2916.59 | 10-AUG-21:51 | 16.10 | 9.68 | 0.104178E+09 | 79.26 | 02-AUG-21:19 | 16.10 | 9.68 |
September | 0.320077E+09 | 2592.32 | 07-SEP-18:01 | 14.13 | 7.59 | 94025096.02 | 56.69 | 01-SEP-01:19 | 14.13 | 7.59 |
October | 25248175.73 | 2449.01 | 04-OCT-08:62 | 7.88 | 2.97 | 93715161.53 | 56.69 | 01-OCT-01:19 | 7.88 | 2.97 |
November | 308263.30 | 827.04 | 04-NOV-08:04 | -8.3 | -9.8 | 89383278.27 | 56.69 | 12-NOV-02:20 | -20.2 | -20.5 |
December | 371214.59 | 901.86 | 24-DEC-19:04 | -4.0 | -4.2 | 92229478.13 | 56.69 | 17-DEC-02:20 | -4.0 | -4.2 |
Annual Sum or Average | 0.707706E+10 | 0.115001E+10 | ||||||||
Minimum of Months | 308263.30 | 827.04 | -14.4 | -15.8 | 83485879.49 | 56.69 | -20.2 | -20.5 | ||
Maximum of Months | 0.181707E+10 | 3603.63 | 20.53 | 14.54 | 0.107360E+09 | 85.54 | 20.53 | 14.54 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 41848602.27 | 377.10 | 23-JAN-22:10 | -15.9 | -16.2 | 0.119782E+10 | 704.47 | 26-JAN-01:00 | -23.9 | -24.2 |
February | 0.260423E+09 | 818.16 | 09-FEB-22:10 | -9.6 | -9.9 | 0.108387E+10 | 704.46 | 27-FEB-03:49 | -34.5 | -34.6 |
March | 0.138346E+10 | 1424.17 | 22-MAR-18:07 | 2.98 | 0.38 | 0.120543E+10 | 723.26 | 22-MAR-21:49 | 1.78 | 0.04 |
April | 0.323414E+10 | 1967.89 | 22-APR-10:33 | 11.87 | 5.55 | 0.123680E+10 | 826.06 | 21-APR-21:40 | 11.87 | 5.55 |
May | 0.432405E+10 | 2191.28 | 14-MAY-10:33 | 16.83 | 8.94 | 0.141396E+10 | 892.60 | 12-MAY-21:40 | 16.83 | 8.94 |
June | 0.463888E+10 | 2300.42 | 13-JUN-10:33 | 21.83 | 12.30 | 0.146804E+10 | 945.22 | 22-JUN-21:40 | 19.80 | 11.82 |
July | 0.477898E+10 | 2333.29 | 23-JUL-10:33 | 22.23 | 15.22 | 0.150235E+10 | 943.62 | 12-JUL-21:40 | 22.23 | 15.22 |
August | 0.446169E+10 | 2194.78 | 01-AUG-10:33 | 15.93 | 12.83 | 0.145001E+10 | 923.01 | 02-AUG-21:40 | 19.80 | 14.37 |
September | 0.328144E+10 | 1917.46 | 10-SEP-10:33 | 13.87 | 7.59 | 0.123504E+10 | 830.68 | 01-SEP-00:10 | 13.87 | 7.59 |
October | 0.144746E+10 | 1551.08 | 03-OCT-10:33 | 5.37 | 3.67 | 0.120163E+10 | 733.97 | 03-OCT-22:10 | 7.30 | 3.10 |
November | 52927219.12 | 514.65 | 01-NOV-21:10 | -8.9 | -9.5 | 0.115966E+10 | 704.48 | 16-NOV-23:00 | -23.9 | -24.1 |
December | 11519967.43 | 380.26 | 24-DEC-22:00 | -5.0 | -5.4 | 0.119875E+10 | 704.48 | 22-DEC-00:00 | -5.0 | -5.4 |
Annual Sum or Average | 0.279168E+11 | 0.153534E+11 | ||||||||
Minimum of Months | 11519967.43 | 377.10 | -15.9 | -16.2 | 0.108387E+10 | 704.46 | -34.5 | -34.6 | ||
Maximum of Months | 0.477898E+10 | 2333.29 | 22.23 | 15.22 | 0.150235E+10 | 945.22 | 22.23 | 15.22 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 261921.01 | 374.55 | 22-JAN-09:04 | -6.2 | -6.5 | 92281510.87 | 56.69 | 27-JAN-04:19 | -14.8 | -15.1 |
February | 2054239.11 | 831.40 | 09-FEB-19:04 | -7.5 | -7.8 | 83415197.75 | 56.69 | 05-FEB-02:20 | -7.5 | -7.8 |
March | 55927854.09 | 3100.61 | 27-MAR-18:01 | -7.2 | -9.8 | 93816344.01 | 56.69 | 07-MAR-04:19 | -7.2 | -9.8 |
April | 0.759108E+09 | 3311.69 | 21-APR-18:01 | 14.22 | 5.92 | 93952705.21 | 56.69 | 12-APR-22:30 | 14.22 | 5.92 |
May | 0.134164E+10 | 3430.62 | 31-MAY-18:02 | 21.13 | 10.92 | 98540534.26 | 56.69 | 11-MAY-21:10 | 21.13 | 10.92 |
June | 0.200662E+10 | 3549.12 | 22-JUN-18:02 | 23.22 | 12.45 | 95757666.74 | 56.70 | 29-JUN-22:40 | 20.53 | 15.75 |
July | 0.193417E+10 | 3402.66 | 11-JUL-18:02 | 26.02 | 15.10 | 98835527.26 | 56.70 | 07-JUL-21:19 | 26.02 | 15.10 |
August | 0.144999E+10 | 3565.09 | 10-AUG-18:02 | 22.62 | 12.07 | 98647074.47 | 56.70 | 01-AUG-21:00 | 22.62 | 12.07 |
September | 0.356252E+09 | 3217.53 | 02-SEP-18:02 | 16.52 | 10.34 | 93478591.39 | 56.69 | 08-SEP-23:00 | 4.40 | 3.92 |
October | 22230779.05 | 2866.30 | 13-OCT-15:02 | 1.70 | -2.0 | 93346917.39 | 56.69 | 01-OCT-01:19 | 1.70 | -2.0 |
November | 282648.75 | 374.18 | 08-NOV-16:04 | -16.5 | -16.8 | 89354082.25 | 56.69 | 23-NOV-02:20 | -18.5 | -18.8 |
December | 207459.85 | 630.66 | 24-DEC-09:04 | 0.18 | -1.3 | 92205826.98 | 56.69 | 16-DEC-00:20 | 0.18 | -1.3 |
Annual Sum or Average | 0.792875E+10 | 0.112363E+10 | ||||||||
Minimum of Months | 207459.85 | 374.18 | -16.5 | -16.8 | 83415197.75 | 56.69 | -18.5 | -18.8 | ||
Maximum of Months | 0.200662E+10 | 3565.09 | 26.02 | 15.10 | 98835527.26 | 56.70 | 26.02 | 15.75 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 273707.93 | 449.84 | 22-JAN-09:04 | -6.2 | -6.5 | 92280492.47 | 56.69 | 17-JAN-04:19 | -6.2 | -6.5 |
February | 1034994.54 | 734.38 | 09-FEB-16:04 | 0.13 | -0.8 | 83360459.24 | 56.69 | 14-FEB-04:19 | -15.7 | -16.0 |
March | 6496507.66 | 1455.39 | 28-MAR-15:03 | -5.5 | -8.7 | 92810932.81 | 56.69 | 05-MAR-02:20 | -5.5 | -8.7 |
April | 0.389188E+09 | 2949.83 | 21-APR-18:01 | 14.22 | 5.92 | 92500970.39 | 56.69 | 20-APR-21:19 | 14.22 | 5.92 |
May | 0.833300E+09 | 3757.76 | 09-MAY-19:42 | 14.27 | 6.45 | 0.103605E+09 | 97.79 | 10-MAY-21:10 | 14.13 | 6.05 |
June | 0.147615E+10 | 3593.42 | 28-JUN-21:32 | 18.87 | 14.85 | 0.109181E+09 | 115.42 | 28-JUN-21:10 | 18.87 | 14.85 |
July | 0.140893E+10 | 3552.52 | 06-JUL-17:32 | 24.23 | 15.21 | 0.109299E+09 | 94.86 | 06-JUL-21:30 | 20.55 | 14.54 |
August | 0.870661E+09 | 3180.35 | 02-AUG-21:51 | 19.40 | 14.21 | 0.106600E+09 | 101.19 | 10-AUG-21:10 | 17.93 | 10.68 |
September | 0.143502E+09 | 3048.75 | 02-SEP-19:41 | 13.27 | 9.27 | 92672079.18 | 56.69 | 01-SEP-03:20 | 13.27 | 9.27 |
October | 7497992.50 | 1428.78 | 05-OCT-15:03 | 10.68 | 5.71 | 92762788.51 | 56.69 | 20-OCT-03:20 | -0.4 | -0.6 |
November | 172586.82 | 398.68 | 04-NOV-08:04 | -8.3 | -9.8 | 89353074.96 | 56.69 | 24-NOV-04:19 | -9.4 | -10.0 |
December | 207900.88 | 600.45 | 24-DEC-09:04 | 0.18 | -1.3 | 92206701.29 | 56.69 | 01-DEC-04:19 | 0.18 | -1.3 |
Annual Sum or Average | 0.513742E+10 | 0.115663E+10 | ||||||||
Minimum of Months | 172586.82 | 398.68 | -8.3 | -9.8 | 83360459.24 | 56.69 | -15.7 | -16.0 | ||
Maximum of Months | 0.147615E+10 | 3757.76 | 24.23 | 15.21 | 0.109299E+09 | 115.42 | 20.55 | 14.85 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2928529.84 | 598.75 | 22-JAN-19:04 | -6.7 | -7.0 | 92496909.17 | 56.69 | 14-JAN-00:20 | -6.7 | -7.0 |
February | 38713252.43 | 2102.16 | 15-FEB-16:01 | -7.3 | -8.7 | 85158432.60 | 56.69 | 06-FEB-00:20 | -7.3 | -8.7 |
March | 0.290666E+09 | 2187.98 | 15-MAR-15:01 | -10.6 | -12.6 | 96492955.44 | 56.69 | 22-MAR-23:19 | -0.2 | -1.5 |
April | 0.827192E+09 | 2238.11 | 20-APR-15:01 | 13.80 | 6.27 | 95042118.78 | 56.69 | 20-APR-21:00 | 5.60 | 1.90 |
May | 0.110278E+10 | 2286.80 | 10-MAY-15:01 | 18.90 | 9.17 | 98789384.45 | 56.69 | 11-MAY-22:19 | 10.73 | 5.23 |
June | 0.129343E+10 | 2303.50 | 22-JUN-18:02 | 23.22 | 12.45 | 95785023.32 | 56.69 | 29-JUN-21:30 | 23.05 | 16.39 |
July | 0.136467E+10 | 2320.49 | 23-JUL-15:02 | 25.60 | 15.39 | 98885192.46 | 56.70 | 10-JUL-21:19 | 25.60 | 15.39 |
August | 0.122638E+10 | 2306.41 | 10-AUG-18:02 | 22.62 | 12.07 | 98869028.30 | 56.70 | 24-AUG-21:49 | 14.97 | 12.21 |
September | 0.583218E+09 | 2117.98 | 07-SEP-18:01 | 14.13 | 7.59 | 94737768.06 | 56.69 | 01-SEP-01:49 | 14.13 | 7.59 |
October | 0.158857E+09 | 2146.98 | 13-OCT-15:02 | 1.70 | -2.0 | 95498810.43 | 56.69 | 01-OCT-23:19 | 1.70 | -2.0 |
November | 6156304.47 | 1996.45 | 08-NOV-16:01 | -16.5 | -16.8 | 89847255.54 | 56.69 | 05-NOV-23:19 | -16.5 | -16.8 |
December | 510622.18 | 590.80 | 24-DEC-19:04 | -4.0 | -4.2 | 92252232.03 | 56.69 | 19-DEC-04:19 | -4.0 | -4.2 |
Annual Sum or Average | 0.689549E+10 | 0.113386E+10 | ||||||||
Minimum of Months | 510622.18 | 590.80 | -16.5 | -16.8 | 85158432.60 | 56.69 | -16.5 | -16.8 | ||
Maximum of Months | 0.136467E+10 | 2320.49 | 25.60 | 15.39 | 98885192.46 | 56.70 | 25.60 | 16.39 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.267293E+11 | 16995.61 | 11-JAN-22:40 | -35.2 | -35.3 | 0.174215E+11 | 11347.89 | 19-JAN-00:20 | -9.2 | -9.3 |
February | 0.251730E+11 | 16363.52 | 28-FEB-22:10 | -29.6 | -29.7 | 0.158230E+11 | 11347.94 | 10-FEB-00:20 | -29.6 | -29.7 |
March | 0.292958E+11 | 17388.83 | 22-MAR-22:00 | 1.70 | 0.03 | 0.184171E+11 | 11347.93 | 12-MAR-23:19 | 1.70 | 0.03 |
April | 0.322445E+11 | 19132.88 | 21-APR-21:10 | 9.53 | 3.30 | 0.184308E+11 | 11347.96 | 09-APR-23:19 | 9.53 | 3.30 |
May | 0.381949E+11 | 20953.76 | 31-MAY-21:52 | 15.30 | 9.39 | 0.192701E+11 | 11349.18 | 11-MAY-21:40 | 15.30 | 9.39 |
June | 0.404833E+11 | 22498.82 | 21-JUN-21:03 | 23.53 | 13.66 | 0.187355E+11 | 11349.18 | 15-JUN-22:10 | 23.53 | 13.66 |
July | 0.416004E+11 | 22776.91 | 11-JUL-21:10 | 21.83 | 13.37 | 0.192833E+11 | 11349.22 | 10-JUL-22:10 | 21.83 | 13.37 |
August | 0.392548E+11 | 21547.80 | 02-AUG-21:52 | 19.40 | 14.21 | 0.193253E+11 | 11349.22 | 01-AUG-22:10 | 19.40 | 14.21 |
September | 0.334733E+11 | 19207.74 | 01-SEP-22:00 | 10.00 | 8.27 | 0.185155E+11 | 11347.98 | 10-SEP-23:19 | 7.60 | 6.01 |
October | 0.305786E+11 | 17931.77 | 06-OCT-22:00 | 7.20 | 3.44 | 0.188033E+11 | 11347.95 | 15-OCT-23:19 | -0.8 | -1.2 |
November | 0.260168E+11 | 16030.67 | 28-NOV-23:00 | -28.9 | -29.1 | 0.168920E+11 | 11367.58 | 07-NOV-22:49 | -28.9 | -29.1 |
December | 0.263612E+11 | 16708.36 | 14-DEC-24:00 | -30.0 | -30.1 | 0.170362E+11 | 11347.85 | 26-DEC-00:20 | -10.9 | -11.3 |
Annual Sum or Average | 0.389406E+12 | 0.217954E+12 | ||||||||
Minimum of Months | 0.251730E+11 | 16030.67 | -35.2 | -35.3 | 0.158230E+11 | 11347.85 | -29.6 | -29.7 | ||
Maximum of Months | 0.416004E+11 | 22776.91 | 23.53 | 14.21 | 0.193253E+11 | 11367.58 | 23.53 | 14.21 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.298302E+11 | 18391.62 | 11-JAN-22:30 | -35.0 | -35.1 | 0.177841E+11 | 11347.97 | 19-JAN-00:20 | -9.2 | -9.3 |
February | 0.280696E+11 | 18109.23 | 08-FEB-23:00 | -1.1 | -2.8 | 0.161135E+11 | 11348.01 | 13-FEB-00:20 | -14.3 | -14.6 |
March | 0.327573E+11 | 19404.36 | 22-MAR-22:00 | 1.70 | 0.03 | 0.186829E+11 | 11347.99 | 26-MAR-23:19 | -17.1 | -18.1 |
April | 0.358484E+11 | 20815.18 | 21-APR-21:10 | 9.53 | 3.30 | 0.185730E+11 | 11348.00 | 09-APR-23:19 | 9.53 | 3.30 |
May | 0.418489E+11 | 22387.14 | 31-MAY-21:52 | 15.30 | 9.39 | 0.193197E+11 | 11349.19 | 11-MAY-21:40 | 15.30 | 9.39 |
June | 0.436548E+11 | 23757.13 | 21-JUN-21:03 | 23.53 | 13.66 | 0.187541E+11 | 11366.01 | 15-JUN-21:19 | 23.53 | 13.66 |
July | 0.448479E+11 | 24083.28 | 11-JUL-21:10 | 21.83 | 13.37 | 0.193021E+11 | 11365.23 | 27-JUL-21:19 | 17.97 | 13.68 |
August | 0.426742E+11 | 22846.66 | 02-AUG-21:20 | 20.20 | 14.52 | 0.193640E+11 | 11373.05 | 25-AUG-21:19 | 17.60 | 13.41 |
September | 0.372607E+11 | 20940.96 | 01-SEP-22:00 | 10.00 | 8.27 | 0.186209E+11 | 11348.00 | 10-SEP-23:19 | 7.60 | 6.01 |
October | 0.343194E+11 | 19974.74 | 06-OCT-22:00 | 7.20 | 3.44 | 0.190214E+11 | 11348.01 | 29-OCT-23:19 | -11.3 | -12.1 |
November | 0.290419E+11 | 17036.98 | 28-NOV-23:00 | -28.9 | -29.1 | 0.172567E+11 | 11369.69 | 07-NOV-22:49 | -28.9 | -29.1 |
December | 0.293096E+11 | 17746.52 | 14-DEC-24:00 | -30.0 | -30.1 | 0.174216E+11 | 11347.95 | 27-DEC-00:20 | -22.4 | -22.7 |
Annual Sum or Average | 0.429463E+12 | 0.220214E+12 | ||||||||
Minimum of Months | 0.280696E+11 | 17036.98 | -35.0 | -35.1 | 0.161135E+11 | 11347.95 | -28.9 | -29.1 | ||
Maximum of Months | 0.448479E+11 | 24083.28 | 23.53 | 14.52 | 0.193640E+11 | 11373.05 | 23.53 | 13.68 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.428777E+11 | 23847.08 | 22-JAN-11:50 | -6.6 | -6.9 | 0.187155E+11 | 11319.68 | 14-JAN-18:19 | -6.6 | -6.9 |
February | 0.400966E+11 | 25243.48 | 09-FEB-11:50 | -2.0 | -2.3 | 0.169196E+11 | 11319.68 | 25-FEB-18:19 | -23.2 | -23.7 |
March | 0.472502E+11 | 27432.78 | 22-MAR-10:33 | 2.43 | 0.50 | 0.187712E+11 | 11319.65 | 04-MAR-18:19 | 2.43 | 0.50 |
April | 0.492996E+11 | 29469.86 | 22-APR-10:50 | 12.33 | 5.78 | 0.182008E+11 | 11319.67 | 22-APR-17:19 | 13.87 | 6.05 |
May | 0.546753E+11 | 30028.59 | 12-MAY-10:33 | 17.43 | 8.33 | 0.188341E+11 | 11319.61 | 20-MAY-17:19 | 13.30 | 6.36 |
June | 0.545354E+11 | 30522.26 | 29-JUN-10:45 | 22.02 | 15.69 | 0.182443E+11 | 11319.67 | 10-JUN-17:19 | 22.02 | 15.69 |
July | 0.564196E+11 | 31130.64 | 22-JUL-10:40 | 23.67 | 16.46 | 0.188451E+11 | 11319.68 | 29-JUL-17:19 | 29.07 | 18.36 |
August | 0.548379E+11 | 30286.61 | 10-AUG-10:33 | 18.87 | 11.69 | 0.188446E+11 | 11319.68 | 26-AUG-17:19 | 20.93 | 13.69 |
September | 0.496968E+11 | 29051.07 | 10-SEP-10:33 | 13.87 | 7.59 | 0.182135E+11 | 11319.65 | 09-SEP-17:19 | 13.87 | 7.59 |
October | 0.475950E+11 | 27381.66 | 03-OCT-10:33 | 5.37 | 3.67 | 0.187951E+11 | 11319.62 | 21-OCT-17:19 | -11.3 | -11.8 |
November | 0.416895E+11 | 23653.41 | 02-NOV-18:03 | -8.9 | -9.2 | 0.181274E+11 | 11319.69 | 25-NOV-18:19 | -21.3 | -21.6 |
December | 0.421300E+11 | 23917.98 | 24-DEC-11:50 | 1.60 | -0.2 | 0.187166E+11 | 11319.68 | 16-DEC-18:19 | 1.60 | -0.2 |
Annual Sum or Average | 0.581104E+12 | 0.221228E+12 | ||||||||
Minimum of Months | 0.400966E+11 | 23653.41 | -8.9 | -9.2 | 0.169196E+11 | 11319.61 | -23.2 | -23.7 | ||
Maximum of Months | 0.564196E+11 | 31130.64 | 23.67 | 16.46 | 0.188451E+11 | 11319.69 | 29.07 | 18.36 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2077390.50 | 263.82 | 21-JAN-21:50 | -2.5 | -3.6 | 0.126818E+10 | 745.69 | 26-JAN-02:09 | -24.0 | -24.3 |
February | 0.197147E+09 | 2104.21 | 09-FEB-13:30 | -0.3 | -1.5 | 0.114714E+10 | 745.81 | 18-FEB-05:19 | -23.5 | -23.8 |
March | 0.181985E+10 | 3159.56 | 22-MAR-17:13 | 4.67 | 1.29 | 0.127573E+10 | 756.96 | 22-MAR-21:40 | 1.87 | 0.05 |
April | 0.611369E+10 | 4247.17 | 22-APR-10:33 | 11.87 | 5.55 | 0.128222E+10 | 864.02 | 21-APR-21:30 | 11.87 | 5.55 |
May | 0.905575E+10 | 4747.29 | 14-MAY-10:33 | 16.83 | 8.94 | 0.144503E+10 | 933.15 | 31-MAY-21:40 | 15.77 | 9.56 |
June | 0.998615E+10 | 5234.84 | 21-JUN-15:30 | 25.30 | 14.00 | 0.152820E+10 | 1001.55 | 21-JUN-21:19 | 23.17 | 13.57 |
July | 0.103782E+11 | 5996.52 | 23-JUL-13:50 | 25.00 | 15.26 | 0.157070E+10 | 998.46 | 11-JUL-21:30 | 25.00 | 15.26 |
August | 0.950952E+10 | 4836.56 | 02-AUG-17:15 | 23.13 | 14.52 | 0.150217E+10 | 970.79 | 02-AUG-21:40 | 19.80 | 14.37 |
September | 0.669932E+10 | 4135.31 | 10-SEP-10:33 | 13.87 | 7.59 | 0.127665E+10 | 836.46 | 01-SEP-21:40 | 13.87 | 7.59 |
October | 0.258718E+10 | 3380.26 | 03-OCT-10:33 | 5.37 | 3.67 | 0.127056E+10 | 770.84 | 03-OCT-21:40 | 7.20 | 3.00 |
November | 1786739.32 | 168.34 | 01-NOV-21:20 | -8.9 | -9.5 | 0.122735E+10 | 745.69 | 08-NOV-02:30 | -24.1 | -24.4 |
December | 3071151.26 | 345.50 | 24-DEC-22:50 | -3.6 | -4.0 | 0.126881E+10 | 745.75 | 19-DEC-01:49 | -3.6 | -4.0 |
Annual Sum or Average | 0.563538E+11 | 0.160627E+11 | ||||||||
Minimum of Months | 1786739.32 | 168.34 | -8.9 | -9.5 | 0.114714E+10 | 745.69 | -24.1 | -24.4 | ||
Maximum of Months | 0.103782E+11 | 5996.52 | 25.30 | 15.26 | 0.157070E+10 | 1001.55 | 25.00 | 15.26 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -14.9 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -25.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242005E+10 | 2555.12 | 13-JAN-15:20 | -25.0 |
February | 0.109393E+10 | 1512.42 | 28-FEB-08:07 | -25.6 |
March | 0.276863E+09 | 1554.34 | 01-MAR-08:04 | -28.1 |
April | 7807039.54 | 397.24 | 03-APR-06:15 | -21.3 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 244.85 | 0.41 | 30-SEP-07:00 | -5.0 |
October | 0.202067E+09 | 1044.83 | 30-OCT-08:30 | -16.7 |
November | 0.198525E+10 | 1937.93 | 30-NOV-10:10 | -28.4 |
December | 0.312690E+10 | 2061.59 | 15-DEC-18:35 | -27.9 |
Annual Sum or Average | 0.911287E+10 | |||
Minimum of Months | 0.00 | 0.00 | -28.4 | |
Maximum of Months | 0.312690E+10 | 2555.12 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4830500.03 | 273.46 | 13-JAN-13:00 | -28.9 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -10.0 |
December | 1208908.90 | 158.35 | 15-DEC-15:40 | -30.2 |
Annual Sum or Average | 6039408.93 | |||
Minimum of Months | 0.00 | 0.00 | -30.2 | |
Maximum of Months | 4830500.03 | 273.46 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.537054E+09 | 989.34 | 12-JAN-16:00 | -35.6 |
February | 0.315214E+09 | 639.47 | 27-FEB-11:03 | -33.0 |
March | 87214387.94 | 583.99 | 01-MAR-05:00 | -28.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 8.08 |
October | 2916030.62 | 79.25 | 31-OCT-10:03 | -16.5 |
November | 0.338760E+09 | 652.82 | 30-NOV-11:38 | -27.8 |
December | 0.710100E+09 | 805.00 | 15-DEC-14:50 | -30.9 |
Annual Sum or Average | 0.199126E+10 | |||
Minimum of Months | 0.00 | 0.00 | -35.6 | |
Maximum of Months | 0.710100E+09 | 989.34 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.961457E+09 | 906.21 | 13-JAN-11:08 | -30.6 |
February | 0.638396E+09 | 687.54 | 27-FEB-11:03 | -33.0 |
March | 0.259675E+09 | 603.42 | 01-MAR-05:00 | -28.3 |
April | 9857727.49 | 155.68 | 03-APR-09:07 | -13.6 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 8.08 |
October | 86160083.65 | 285.64 | 31-OCT-09:40 | -16.9 |
November | 0.787838E+09 | 714.62 | 30-NOV-11:20 | -28.3 |
December | 0.112484E+10 | 841.98 | 15-DEC-14:20 | -31.7 |
Annual Sum or Average | 0.386822E+10 | |||
Minimum of Months | 0.00 | 0.00 | -33.0 | |
Maximum of Months | 0.112484E+10 | 906.21 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -14.9 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -25.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.427593E+09 | 4082.63 | 13-JAN-14:40 | -26.0 |
February | 14715567.83 | 1027.05 | 01-FEB-09:50 | -17.0 |
March | 3630.20 | 40.83 | 01-MAR-08:03 | -28.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 8.08 |
October | 608739.56 | 332.97 | 30-OCT-08:40 | -16.7 |
November | 0.214769E+09 | 2539.20 | 27-NOV-10:20 | -27.2 |
December | 0.941544E+09 | 2940.39 | 06-DEC-10:40 | -27.4 |
Annual Sum or Average | 0.159923E+10 | |||
Minimum of Months | 0.00 | 0.00 | -28.1 | |
Maximum of Months | 0.941544E+09 | 4082.63 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6579807.42 | 1057.95 | 13-JAN-13:10 | -28.5 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -25.8 |
Annual Sum or Average | 6579807.42 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 6579807.42 | 1057.95 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252001E+10 | 3100.22 | 13-JAN-16:02 | -23.6 |
February | 0.172397E+10 | 3080.78 | 25-FEB-16:01 | -21.8 |
March | 0.104475E+10 | 3045.42 | 15-MAR-08:61 | -22.4 |
April | 0.177561E+09 | 3026.54 | 03-APR-08:61 | -17.1 |
May | 4448481.12 | 978.02 | 28-MAY-08:03 | 6.57 |
June | 1959461.94 | 1081.32 | 24-JUN-18:04 | 12.12 |
July | 2463052.21 | 1028.75 | 25-JUL-08:04 | 13.90 |
August | 3058973.52 | 1151.26 | 29-AUG-15:04 | 15.50 |
September | 0.113173E+09 | 2929.44 | 29-SEP-08:61 | -4.4 |
October | 0.905145E+09 | 3063.10 | 30-OCT-08:61 | -16.7 |
November | 0.224460E+10 | 3102.38 | 26-NOV-16:01 | -22.4 |
December | 0.277787E+10 | 3090.98 | 12-DEC-09:01 | -22.1 |
Annual Sum or Average | 0.115190E+11 | |||
Minimum of Months | 1959461.94 | 978.02 | -23.6 | |
Maximum of Months | 0.277787E+10 | 3102.38 | 15.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.261599E+10 | 3031.24 | 30-JAN-16:01 | -22.9 |
February | 0.200515E+10 | 3018.12 | 25-FEB-16:01 | -21.8 |
March | 0.141238E+10 | 3006.57 | 03-MAR-09:01 | -21.0 |
April | 0.293927E+09 | 2970.91 | 03-APR-08:61 | -17.1 |
May | 5685411.92 | 1081.50 | 25-MAY-18:04 | 9.82 |
June | 560726.10 | 852.38 | 25-JUN-15:05 | 12.48 |
July | 1064328.84 | 817.36 | 26-JUL-08:04 | 12.38 |
August | 3313149.64 | 1001.67 | 19-AUG-15:04 | 12.80 |
September | 0.169964E+09 | 2900.60 | 29-SEP-08:61 | -4.4 |
October | 0.111336E+10 | 2998.03 | 31-OCT-15:01 | -11.6 |
November | 0.240375E+10 | 3035.55 | 26-NOV-16:01 | -22.4 |
December | 0.280821E+10 | 3018.89 | 28-DEC-19:01 | -19.3 |
Annual Sum or Average | 0.128334E+11 | |||
Minimum of Months | 560726.10 | 817.36 | -22.9 | |
Maximum of Months | 0.280821E+10 | 3035.55 | 12.80 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.398156E+09 | 379.96 | 12-JAN-04:10 | -37.3 |
February | 85571720.87 | 261.24 | 26-FEB-06:00 | -25.6 |
March | 6556487.85 | 229.92 | 01-MAR-05:00 | -28.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.263983E+09 | 302.28 | 29-NOV-05:00 | -28.9 |
December | 0.526549E+09 | 357.29 | 15-DEC-05:00 | -33.3 |
Annual Sum or Average | 0.128082E+10 | |||
Minimum of Months | 0.00 | 0.00 | -37.3 | |
Maximum of Months | 0.526549E+09 | 379.96 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.442017E+09 | 878.93 | 30-JAN-16:01 | -22.9 |
February | 0.326137E+09 | 877.46 | 28-FEB-16:01 | -22.4 |
March | 0.196981E+09 | 875.86 | 01-MAR-16:01 | -12.8 |
April | 25608709.26 | 839.86 | 03-APR-15:01 | -5.5 |
May | 137177.96 | 148.66 | 06-MAY-15:07 | 16.70 |
June | 17907.93 | 71.07 | 18-JUN-15:08 | 13.68 |
July | 13473.99 | 58.81 | 25-JUL-15:07 | 15.78 |
August | 83728.24 | 269.05 | 31-AUG-15:05 | 14.08 |
September | 1240449.97 | 317.82 | 26-SEP-08:03 | 0.60 |
October | 97814864.19 | 870.52 | 31-OCT-15:01 | -11.6 |
November | 0.405675E+09 | 879.33 | 26-NOV-16:01 | -22.4 |
December | 0.494478E+09 | 874.19 | 28-DEC-16:02 | -21.5 |
Annual Sum or Average | 0.199020E+10 | |||
Minimum of Months | 13473.99 | 58.81 | -22.9 | |
Maximum of Months | 0.494478E+09 | 879.33 | 16.70 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248842E+10 | 3058.27 | 13-JAN-16:02 | -23.6 |
February | 0.160474E+10 | 3042.86 | 25-FEB-16:01 | -21.8 |
March | 0.831401E+09 | 3003.07 | 01-MAR-19:01 | -19.7 |
April | 0.176072E+09 | 2953.44 | 04-APR-08:61 | -8.0 |
May | 2842383.68 | 985.33 | 03-MAY-18:04 | 13.03 |
June | 773183.58 | 986.63 | 27-JUN-08:04 | 13.40 |
July | 956363.33 | 1067.38 | 01-JUL-08:04 | 12.80 |
August | 1978366.55 | 1133.32 | 14-AUG-08:04 | 11.88 |
September | 85629515.36 | 2530.01 | 27-SEP-15:01 | 3.40 |
October | 0.788969E+09 | 3022.09 | 30-OCT-08:61 | -16.7 |
November | 0.223880E+10 | 3061.47 | 26-NOV-16:01 | -22.4 |
December | 0.277153E+10 | 3049.68 | 12-DEC-09:01 | -22.1 |
Annual Sum or Average | 0.109921E+11 | |||
Minimum of Months | 773183.58 | 985.33 | -23.6 | |
Maximum of Months | 0.277153E+10 | 3061.47 | 13.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258089E+10 | 2991.57 | 13-JAN-16:02 | -23.6 |
February | 0.186977E+10 | 2986.21 | 25-FEB-16:01 | -21.8 |
March | 0.114517E+10 | 2959.58 | 01-MAR-19:01 | -19.7 |
April | 0.298358E+09 | 2914.12 | 04-APR-08:61 | -8.0 |
May | 3678660.37 | 902.23 | 26-MAY-15:04 | 5.92 |
June | 404508.71 | 857.98 | 25-JUN-15:05 | 12.48 |
July | 254809.49 | 420.29 | 26-JUL-08:04 | 12.38 |
August | 2349776.12 | 960.85 | 20-AUG-15:04 | 17.02 |
September | 0.129365E+09 | 2778.87 | 27-SEP-15:01 | 3.40 |
October | 0.967568E+09 | 2959.18 | 27-OCT-08:61 | -18.2 |
November | 0.239824E+10 | 2998.27 | 26-NOV-16:01 | -22.4 |
December | 0.280116E+10 | 2981.32 | 28-DEC-19:01 | -19.3 |
Annual Sum or Average | 0.121972E+11 | |||
Minimum of Months | 254809.49 | 420.29 | -23.6 | |
Maximum of Months | 0.280116E+10 | 2998.27 | 17.02 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167430E+10 | 2171.81 | 13-JAN-15:00 | -25.6 |
February | 0.686788E+09 | 1315.16 | 27-FEB-15:00 | -28.3 |
March | 82455206.52 | 1073.55 | 01-MAR-08:03 | -28.1 |
April | 2360668.47 | 215.30 | 03-APR-08:03 | -17.1 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 8.08 |
October | 0.124180E+09 | 908.44 | 30-OCT-08:03 | -16.7 |
November | 0.130894E+10 | 1654.43 | 29-NOV-10:20 | -29.4 |
December | 0.212267E+10 | 1853.23 | 15-DEC-16:00 | -30.0 |
Annual Sum or Average | 0.600170E+10 | |||
Minimum of Months | 0.00 | 0.00 | -30.0 | |
Maximum of Months | 0.212267E+10 | 2171.81 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.357319E+10 | 3803.84 | 13-JAN-16:02 | -23.6 |
February | 0.255349E+10 | 3771.82 | 25-FEB-16:01 | -21.8 |
March | 0.166558E+10 | 3735.57 | 03-MAR-09:01 | -21.0 |
April | 0.373462E+09 | 3699.85 | 03-APR-08:61 | -17.1 |
May | 22966594.07 | 952.51 | 07-MAY-08:04 | 12.88 |
June | 2111495.45 | 972.64 | 05-JUN-08:04 | 13.58 |
July | 2313580.72 | 952.66 | 13-JUL-08:04 | 13.17 |
August | 12507657.71 | 1399.04 | 30-AUG-08:62 | 2.07 |
September | 0.272016E+09 | 3623.33 | 30-SEP-08:61 | -5.0 |
October | 0.146457E+10 | 3748.68 | 27-OCT-08:61 | -18.2 |
November | 0.324681E+10 | 3802.36 | 26-NOV-16:01 | -22.4 |
December | 0.389019E+10 | 3786.28 | 28-DEC-19:01 | -19.3 |
Annual Sum or Average | 0.170792E+11 | |||
Minimum of Months | 2111495.45 | 952.51 | -23.6 | |
Maximum of Months | 0.389019E+10 | 3803.84 | 13.58 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.368048E+10 | 3692.23 | 13-JAN-16:02 | -23.6 |
February | 0.288797E+10 | 3672.93 | 25-FEB-16:01 | -21.8 |
March | 0.214869E+10 | 3658.36 | 03-MAR-09:01 | -21.0 |
April | 0.564415E+09 | 3610.70 | 03-APR-08:61 | -17.1 |
May | 31504314.86 | 979.06 | 08-MAY-15:04 | 14.90 |
June | 847128.27 | 882.04 | 15-JUN-08:04 | 11.28 |
July | 1242469.74 | 969.58 | 03-JUL-08:04 | 14.50 |
August | 17868629.21 | 1947.36 | 31-AUG-08:62 | 2.48 |
September | 0.387022E+09 | 3553.08 | 30-SEP-08:61 | -5.0 |
October | 0.173851E+10 | 3646.74 | 31-OCT-15:01 | -11.6 |
November | 0.343057E+10 | 3695.41 | 26-NOV-16:01 | -22.4 |
December | 0.392347E+10 | 3673.42 | 28-DEC-19:01 | -19.3 |
Annual Sum or Average | 0.188126E+11 | |||
Minimum of Months | 847128.27 | 882.04 | -23.6 | |
Maximum of Months | 0.392347E+10 | 3695.41 | 14.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154608E+10 | 2129.90 | 13-JAN-16:02 | -23.6 |
February | 0.850323E+09 | 2111.72 | 01-FEB-16:01 | -12.2 |
March | 0.417006E+09 | 2073.70 | 13-MAR-08:61 | -23.0 |
April | 62178930.53 | 2054.88 | 03-APR-08:61 | -17.1 |
May | 2383993.11 | 582.81 | 26-MAY-08:03 | 6.88 |
June | 1217391.01 | 536.29 | 16-JUN-08:04 | 12.77 |
July | 1242364.06 | 531.04 | 10-JUL-08:04 | 15.97 |
August | 1343466.83 | 574.06 | 18-AUG-15:04 | 13.22 |
September | 32582351.02 | 1473.70 | 28-SEP-08:61 | -2.0 |
October | 0.393050E+09 | 2091.19 | 30-OCT-08:61 | -16.7 |
November | 0.131598E+10 | 2119.20 | 26-NOV-16:01 | -22.4 |
December | 0.179934E+10 | 2119.45 | 28-DEC-16:02 | -21.5 |
Annual Sum or Average | 0.642273E+10 | |||
Minimum of Months | 1217391.01 | 531.04 | -23.6 | |
Maximum of Months | 0.179934E+10 | 2129.90 | 15.97 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -14.9 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -25.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -14.9 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -25.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -14.9 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -25.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.629813E+10 | 6246.83 | 13-JAN-10:30 | -30.9 |
February | 0.351107E+10 | 5142.92 | 27-FEB-07:05 | -34.9 |
March | 0.107953E+10 | 4585.12 | 01-MAR-08:06 | -28.1 |
April | 60756288.11 | 1611.54 | 03-APR-06:05 | -21.5 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 8.08 |
October | 0.512580E+09 | 2314.73 | 27-OCT-08:15 | -18.5 |
November | 0.557858E+10 | 5402.97 | 29-NOV-10:20 | -29.4 |
December | 0.768941E+10 | 5864.76 | 15-DEC-11:09 | -33.3 |
Annual Sum or Average | 0.247301E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.9 | |
Maximum of Months | 0.768941E+10 | 6246.83 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.866285E+10 | 8344.11 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.782177E+10 | 8344.11 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.868956E+10 | 8344.11 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.836914E+10 | 8344.11 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.867788E+10 | 8344.11 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.840753E+10 | 8344.11 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.863949E+10 | 8344.11 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.869290E+10 | 8344.11 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.837248E+10 | 8344.11 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.865952E+10 | 8344.11 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.840085E+10 | 8344.11 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.863949E+10 | 8344.11 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.102033E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.782177E+10 | 8344.11 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.869290E+10 | 8344.11 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.478695E+09 | 461.08 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.432218E+09 | 461.08 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.480171E+09 | 461.08 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.462465E+09 | 461.08 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.479525E+09 | 461.08 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.464586E+09 | 461.08 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.477404E+09 | 461.08 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.480355E+09 | 461.08 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.462650E+09 | 461.08 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.478511E+09 | 461.08 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.464217E+09 | 461.08 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.477404E+09 | 461.08 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.563820E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.432218E+09 | 461.08 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.480355E+09 | 461.08 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.554331E+09 | 533.93 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.500510E+09 | 533.93 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.556040E+09 | 533.93 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.535537E+09 | 533.93 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.555292E+09 | 533.93 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.537993E+09 | 533.93 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.552836E+09 | 533.93 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.556253E+09 | 533.93 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.535750E+09 | 533.93 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.554117E+09 | 533.93 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.537566E+09 | 533.93 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.552836E+09 | 533.93 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.652906E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.500510E+09 | 533.93 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.556253E+09 | 533.93 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.639281E+09 | 615.76 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.577212E+09 | 615.76 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.641251E+09 | 615.76 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.617606E+09 | 615.76 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.640389E+09 | 615.76 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.620439E+09 | 615.76 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.637557E+09 | 615.76 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.641498E+09 | 615.76 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.617853E+09 | 615.76 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.639035E+09 | 615.76 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.619946E+09 | 615.76 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.637557E+09 | 615.76 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.752962E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.577212E+09 | 615.76 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.641498E+09 | 615.76 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142601E+09 | 137.35 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.128756E+09 | 137.35 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.143041E+09 | 137.35 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.137766E+09 | 137.35 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.142848E+09 | 137.35 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.138398E+09 | 137.35 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.142217E+09 | 137.35 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.143096E+09 | 137.35 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.137821E+09 | 137.35 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.142546E+09 | 137.35 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.138288E+09 | 137.35 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.142217E+09 | 137.35 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.167960E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.128756E+09 | 137.35 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.143096E+09 | 137.35 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.374392E+09 | 360.62 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.338042E+09 | 360.62 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.375546E+09 | 360.62 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.361698E+09 | 360.62 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.375041E+09 | 360.62 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.363357E+09 | 360.62 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.373382E+09 | 360.62 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.375690E+09 | 360.62 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.361842E+09 | 360.62 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.374247E+09 | 360.62 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.363068E+09 | 360.62 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.373382E+09 | 360.62 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.440969E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.338042E+09 | 360.62 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.375690E+09 | 360.62 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135983E+10 | 1416.11 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.109633E+10 | 1416.11 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.105043E+10 | 1416.11 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.742971E+09 | 1416.11 | 03-APR-19:40 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.658255E+09 | 1258.77 | 04-MAY-20:30 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.541148E+09 | 1106.77 | 02-JUN-20:00 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.602043E+09 | 1147.23 | 28-JUL-20:00 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.761890E+09 | 1416.11 | 29-AUG-19:30 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.949323E+09 | 1416.11 | 01-SEP-19:30 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.116678E+10 | 1416.11 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.125833E+10 | 1416.11 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.141852E+10 | 1416.11 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.116058E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.541148E+09 | 1106.77 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.141852E+10 | 1416.11 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.982886E+10 | 9580.84 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.871198E+10 | 9580.84 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.948314E+10 | 9580.84 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.884142E+10 | 9580.84 | 03-APR-19:40 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.904633E+10 | 9388.46 | 02-MAY-19:00 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.865456E+10 | 9231.95 | 02-JUN-19:00 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.894915E+10 | 9186.25 | 28-JUL-19:00 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.918033E+10 | 9580.84 | 29-AUG-19:30 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.907498E+10 | 9580.84 | 01-SEP-19:30 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.959021E+10 | 9580.84 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.945882E+10 | 9580.84 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.987693E+10 | 9580.84 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.110697E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.865456E+10 | 9186.25 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.987693E+10 | 9580.84 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118113E+09 | 106.87 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.106667E+09 | 106.87 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.117174E+09 | 106.87 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.114438E+09 | 106.87 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.117643E+09 | 106.87 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113531E+09 | 106.87 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.118566E+09 | 106.87 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.117174E+09 | 106.87 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.114469E+09 | 106.87 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.118097E+09 | 106.87 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113984E+09 | 106.87 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.118582E+09 | 106.87 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.138844E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.106667E+09 | 106.87 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.118582E+09 | 106.87 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118099E+09 | 106.85 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.106655E+09 | 106.85 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.117160E+09 | 106.85 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.114425E+09 | 106.85 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.117629E+09 | 106.85 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113517E+09 | 106.85 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.118553E+09 | 106.85 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.117160E+09 | 106.85 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.114456E+09 | 106.85 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.118083E+09 | 106.85 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113971E+09 | 106.85 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.118568E+09 | 106.85 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.138828E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.106655E+09 | 106.85 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.118568E+09 | 106.85 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 74229181.22 | 67.16 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 67036196.95 | 67.16 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 73639243.64 | 67.16 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 71920171.51 | 67.16 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 73934212.43 | 67.16 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 71349576.37 | 67.16 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 74514478.79 | 67.16 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 73639243.64 | 67.16 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 71939513.95 | 67.16 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 74219510.00 | 67.16 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 71634873.94 | 67.16 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 74524150.01 | 67.16 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.872580E+09 | 0.300992E+10 | ||||
Minimum of Months | 67036196.95 | 67.16 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 74524150.01 | 67.16 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 74249479.06 | 67.18 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 67054527.88 | 67.18 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 73659380.16 | 67.18 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 71939837.95 | 67.18 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 73954429.61 | 67.18 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 71369086.78 | 67.18 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 74534854.64 | 67.18 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 73659380.16 | 67.18 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 71959185.68 | 67.18 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 74239805.19 | 67.18 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 71654462.37 | 67.18 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 74544528.51 | 67.18 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.872819E+09 | 0.301074E+10 | ||||
Minimum of Months | 67054527.88 | 67.18 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 74544528.51 | 67.18 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118113E+09 | 106.87 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.106667E+09 | 106.87 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.117174E+09 | 106.87 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.114438E+09 | 106.87 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.117643E+09 | 106.87 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113531E+09 | 106.87 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.118566E+09 | 106.87 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.117174E+09 | 106.87 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.114469E+09 | 106.87 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.118097E+09 | 106.87 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113984E+09 | 106.87 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.118582E+09 | 106.87 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.138844E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.106667E+09 | 106.87 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.118582E+09 | 106.87 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118099E+09 | 106.85 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.106655E+09 | 106.85 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.117160E+09 | 106.85 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.114425E+09 | 106.85 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.117629E+09 | 106.85 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113517E+09 | 106.85 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.118553E+09 | 106.85 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.117160E+09 | 106.85 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.114456E+09 | 106.85 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.118083E+09 | 106.85 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113971E+09 | 106.85 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.118568E+09 | 106.85 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.138828E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.106655E+09 | 106.85 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.118568E+09 | 106.85 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.108388E+10 | 1044.00 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.978647E+09 | 1044.00 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.108722E+10 | 1044.00 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.104713E+10 | 1044.00 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.108576E+10 | 1044.00 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.105194E+10 | 1044.00 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.108096E+10 | 1044.00 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.108764E+10 | 1044.00 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.104755E+10 | 1044.00 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.108346E+10 | 1044.00 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.105110E+10 | 1044.00 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.108096E+10 | 1044.00 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.127663E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.978647E+09 | 1044.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108764E+10 | 1044.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118113E+09 | 106.87 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.106667E+09 | 106.87 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.117174E+09 | 106.87 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.114438E+09 | 106.87 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.117643E+09 | 106.87 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113531E+09 | 106.87 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.118566E+09 | 106.87 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.117174E+09 | 106.87 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.114469E+09 | 106.87 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.118097E+09 | 106.87 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113984E+09 | 106.87 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.118582E+09 | 106.87 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.138844E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.106667E+09 | 106.87 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.118582E+09 | 106.87 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118099E+09 | 106.85 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.106655E+09 | 106.85 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.117160E+09 | 106.85 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.114425E+09 | 106.85 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.117629E+09 | 106.85 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113517E+09 | 106.85 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.118553E+09 | 106.85 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.117160E+09 | 106.85 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.114456E+09 | 106.85 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.118083E+09 | 106.85 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113971E+09 | 106.85 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.118568E+09 | 106.85 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.138828E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.106655E+09 | 106.85 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.118568E+09 | 106.85 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 74249479.06 | 67.18 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 67054527.88 | 67.18 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 73659380.16 | 67.18 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 71939837.95 | 67.18 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 73954429.61 | 67.18 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 71369086.78 | 67.18 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 74534854.64 | 67.18 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 73659380.16 | 67.18 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 71959185.68 | 67.18 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 74239805.19 | 67.18 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 71654462.37 | 67.18 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 74544528.51 | 67.18 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.872819E+09 | 0.301074E+10 | ||||
Minimum of Months | 67054527.88 | 67.18 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 74544528.51 | 67.18 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.253350E+10 | 2486.81 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.217769E+10 | 2486.81 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.224613E+10 | 2486.81 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.188146E+10 | 2486.81 | 03-APR-19:40 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.180463E+10 | 2210.50 | 04-MAY-20:30 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.166014E+10 | 2130.81 | 02-JUN-19:00 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.175715E+10 | 2115.71 | 26-JUL-20:00 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.193996E+10 | 2486.81 | 29-AUG-19:30 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.210682E+10 | 2486.81 | 01-SEP-19:30 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.236109E+10 | 2486.81 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.242018E+10 | 2486.81 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.256026E+10 | 2486.81 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.254490E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.166014E+10 | 2115.71 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.256026E+10 | 2486.81 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.253350E+10 | 2486.81 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.217769E+10 | 2486.81 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.224613E+10 | 2486.81 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.188146E+10 | 2486.81 | 03-APR-19:40 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.180463E+10 | 2210.50 | 04-MAY-20:30 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.166014E+10 | 2130.81 | 02-JUN-19:00 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.175715E+10 | 2115.71 | 26-JUL-20:00 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.193993E+10 | 2486.81 | 29-AUG-19:30 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.210682E+10 | 2486.81 | 01-SEP-19:30 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.236109E+10 | 2486.81 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.242018E+10 | 2486.81 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.256026E+10 | 2486.81 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.254490E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.166014E+10 | 2115.71 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.256026E+10 | 2486.81 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101925E+10 | 981.75 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.920291E+09 | 981.75 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.102239E+10 | 981.75 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.984694E+09 | 981.75 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.102102E+10 | 981.75 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.989210E+09 | 981.75 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.101650E+10 | 981.75 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.102279E+10 | 981.75 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.985086E+09 | 981.75 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.101886E+10 | 981.75 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.988424E+09 | 981.75 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.101650E+10 | 981.75 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.120050E+11 | 0.424019E+12 | ||||
Minimum of Months | 0.920291E+09 | 981.75 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.102279E+10 | 981.75 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.114712E+10 | 1104.91 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.103575E+10 | 1104.91 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.115066E+10 | 1104.91 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.110823E+10 | 1104.91 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.114911E+10 | 1104.91 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.111331E+10 | 1104.91 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.114403E+10 | 1104.91 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.115110E+10 | 1104.91 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.110867E+10 | 1104.91 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.114668E+10 | 1104.91 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.111243E+10 | 1104.91 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.114403E+10 | 1104.91 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.135111E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.103575E+10 | 1104.91 | 0.00 | 0.00 | |
Maximum of Months | 0.115110E+10 | 1104.91 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.866285E+10 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.782177E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.868956E+10 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.836914E+10 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.867788E+10 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.840753E+10 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.863949E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.869290E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.837248E+10 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.865952E+10 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.840085E+10 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.863949E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.102033E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.782177E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.869290E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.478695E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343398E+09 |
February | 0.179968E+10 | 0.432218E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294598E+09 |
March | 0.199990E+10 | 0.480171E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276772E+09 |
April | 0.192973E+10 | 0.462465E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169670E+09 |
May | 0.199475E+10 | 0.479525E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89617917.42 |
June | 0.193394E+10 | 0.464586E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 765222.80 | 46426066.81 |
July | 0.199054E+10 | 0.477404E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1669583.84 | 41276309.64 |
August | 0.199896E+10 | 0.480355E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 227791.61 | 60985057.39 |
September | 0.192879E+10 | 0.462650E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115877E+09 |
October | 0.199148E+10 | 0.478511E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206303E+09 |
November | 0.192552E+10 | 0.464217E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334856E+09 |
December | 0.199054E+10 | 0.477404E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362222E+09 |
Annual Sum or Average | 0.234744E+11 | 0.563820E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2662598.25 | 0.234200E+10 |
Minimum of Months | 0.179968E+10 | 0.432218E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41276309.64 |
Maximum of Months | 0.199990E+10 | 0.480355E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1669583.84 | 0.362222E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.554331E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133349E+09 |
February | 0.208403E+10 | 0.500510E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114381E+09 |
March | 0.231589E+10 | 0.556040E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107942E+09 |
April | 0.223463E+10 | 0.535537E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68339681.91 |
May | 0.230993E+10 | 0.555292E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38664450.71 |
June | 0.223950E+10 | 0.537993E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 259600.23 | 22100655.86 |
July | 0.230505E+10 | 0.552836E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 605874.41 | 20301609.86 |
August | 0.231480E+10 | 0.556253E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77214.53 | 28044654.70 |
September | 0.223354E+10 | 0.535750E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48557856.37 |
October | 0.230614E+10 | 0.554117E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81963473.29 |
November | 0.222975E+10 | 0.537566E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129723E+09 |
December | 0.230505E+10 | 0.552836E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140100E+09 |
Annual Sum or Average | 0.271834E+11 | 0.652906E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 942689.17 | 0.933467E+09 |
Minimum of Months | 0.208403E+10 | 0.500510E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20301609.86 |
Maximum of Months | 0.231589E+10 | 0.556253E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 605874.41 | 0.140100E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.639281E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314546E+09 |
February | 0.440737E+09 | 0.577212E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268738E+09 |
March | 0.489771E+09 | 0.641251E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250897E+09 |
April | 0.472586E+09 | 0.617606E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154781E+09 |
May | 0.488511E+09 | 0.640389E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88553636.22 |
June | 0.473617E+09 | 0.620439E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 624884.83 | 51911320.31 |
July | 0.487480E+09 | 0.637557E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1417969.89 | 48313081.92 |
August | 0.489542E+09 | 0.641498E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 254709.43 | 65648769.97 |
September | 0.472357E+09 | 0.617853E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111600E+09 |
October | 0.487709E+09 | 0.639035E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189381E+09 |
November | 0.471555E+09 | 0.619946E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305474E+09 |
December | 0.487480E+09 | 0.637557E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330660E+09 |
Annual Sum or Average | 0.574883E+10 | 0.752962E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2297564.14 | 0.218050E+10 |
Minimum of Months | 0.440737E+09 | 0.577212E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48313081.92 |
Maximum of Months | 0.489771E+09 | 0.641498E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1417969.89 | 0.330660E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.142601E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181455E+09 |
February | 0.339028E+09 | 0.128756E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155029E+09 |
March | 0.376747E+09 | 0.143041E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144596E+09 |
April | 0.363528E+09 | 0.137766E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88285276.95 |
May | 0.375778E+09 | 0.142848E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49974644.43 |
June | 0.364321E+09 | 0.138398E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 383418.35 | 29182958.68 |
July | 0.374985E+09 | 0.142217E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 868238.69 | 27093875.67 |
August | 0.376571E+09 | 0.143096E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 163667.38 | 36804454.04 |
September | 0.363352E+09 | 0.137821E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62949940.94 |
October | 0.375161E+09 | 0.142546E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108561E+09 |
November | 0.362735E+09 | 0.138288E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176241E+09 |
December | 0.374985E+09 | 0.142217E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190773E+09 |
Annual Sum or Average | 0.442217E+10 | 0.167960E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1415324.42 | 0.125095E+10 |
Minimum of Months | 0.339028E+09 | 0.128756E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27093875.67 |
Maximum of Months | 0.376747E+09 | 0.143096E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 868238.69 | 0.190773E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.374392E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444163E+09 |
February | 0.139600E+10 | 0.338042E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382071E+09 |
March | 0.155131E+10 | 0.375546E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361876E+09 |
April | 0.149688E+10 | 0.361698E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224986E+09 |
May | 0.154732E+10 | 0.375041E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 213.60 | 0.125388E+09 |
June | 0.150015E+10 | 0.363357E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 1054946.30 | 69257975.10 |
July | 0.154405E+10 | 0.373382E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 2514915.08 | 63880390.83 |
August | 0.155059E+10 | 0.375690E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 418763.07 | 89354027.04 |
September | 0.149615E+10 | 0.361842E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161289E+09 |
October | 0.154478E+10 | 0.374247E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276643E+09 |
November | 0.149361E+10 | 0.363068E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433834E+09 |
December | 0.154405E+10 | 0.373382E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467546E+09 |
Annual Sum or Average | 0.182090E+11 | 0.440969E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 3988838.05 | 0.310029E+10 |
Minimum of Months | 0.139600E+10 | 0.338042E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63880390.83 |
Maximum of Months | 0.155131E+10 | 0.375690E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 2514915.08 | 0.467546E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.135983E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760143E+09 |
February | 0.236489E+11 | 0.109633E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652285E+09 |
March | 0.262800E+11 | 0.105043E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.617256E+09 |
April | 0.253579E+11 | 0.742971E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387527E+09 |
May | 0.262123E+11 | 0.658255E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213975E+09 |
June | 0.254132E+11 | 0.541148E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1388832.01 | 0.118119E+09 |
July | 0.261570E+11 | 0.602043E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3176265.36 | 0.106825E+09 |
August | 0.262677E+11 | 0.761890E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 368047.92 | 0.151016E+09 |
September | 0.253456E+11 | 0.949323E+09 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268447E+09 |
October | 0.261693E+11 | 0.116678E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461489E+09 |
November | 0.253025E+11 | 0.125833E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740395E+09 |
December | 0.261570E+11 | 0.141852E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.800861E+09 |
Annual Sum or Average | 0.308468E+12 | 0.116058E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4933145.29 | 0.527834E+10 |
Minimum of Months | 0.236489E+11 | 0.541148E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106825E+09 |
Maximum of Months | 0.262800E+11 | 0.141852E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3176265.36 | 0.800861E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.982886E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219435E+10 |
February | 0.702046E+11 | 0.871198E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188503E+10 |
March | 0.780153E+11 | 0.948314E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178971E+10 |
April | 0.752779E+11 | 0.884142E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113711E+10 |
May | 0.778146E+11 | 0.904633E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648096E+09 |
June | 0.754422E+11 | 0.865456E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3833117.95 | 0.370911E+09 |
July | 0.776503E+11 | 0.894915E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8697914.54 | 0.341508E+09 |
August | 0.779788E+11 | 0.918033E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 940013.25 | 0.471138E+09 |
September | 0.752414E+11 | 0.907498E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.811690E+09 |
October | 0.776868E+11 | 0.959021E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136114E+10 |
November | 0.751137E+11 | 0.945882E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213607E+10 |
December | 0.776503E+11 | 0.987693E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230229E+10 |
Annual Sum or Average | 0.915726E+12 | 0.110697E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 13471045.74 | 0.154490E+11 |
Minimum of Months | 0.702046E+11 | 0.865456E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341508E+09 |
Maximum of Months | 0.780153E+11 | 0.987693E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8697914.54 | 0.230229E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118113E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197694E+09 |
February | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169130E+09 |
March | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159206E+09 |
April | 0.293479E+09 | 0.114438E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97978386.74 |
May | 0.303504E+09 | 0.117643E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7308.36 | 52372806.19 |
June | 0.293842E+09 | 0.113531E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 802760.23 | 26988434.20 |
July | 0.303141E+09 | 0.118566E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1637552.58 | 24442108.09 |
August | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 413736.61 | 35757956.24 |
September | 0.293479E+09 | 0.114469E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67855170.15 |
October | 0.303322E+09 | 0.118097E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118606E+09 |
November | 0.293661E+09 | 0.113984E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192024E+09 |
December | 0.303141E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207897E+09 |
Annual Sum or Average | 0.357224E+10 | 0.138844E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2861357.78 | 0.134995E+10 |
Minimum of Months | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24442108.09 |
Maximum of Months | 0.303685E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1637552.58 | 0.207897E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118099E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197664E+09 |
February | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168794E+09 |
March | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157623E+09 |
April | 0.293479E+09 | 0.114425E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96508808.07 |
May | 0.303504E+09 | 0.117629E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.14 | 53825207.64 |
June | 0.293842E+09 | 0.113517E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 617412.50 | 30927319.61 |
July | 0.303141E+09 | 0.118553E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1216760.83 | 27455614.19 |
August | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 259023.54 | 37989226.48 |
September | 0.293479E+09 | 0.114456E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67028475.51 |
October | 0.303322E+09 | 0.118083E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117775E+09 |
November | 0.293661E+09 | 0.113971E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191968E+09 |
December | 0.303141E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207878E+09 |
Annual Sum or Average | 0.357224E+10 | 0.138828E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2093244.01 | 0.135544E+10 |
Minimum of Months | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27455614.19 |
Maximum of Months | 0.303685E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1216760.83 | 0.207878E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 74229181.22 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48127108.83 |
February | 0.00 | 67036196.95 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42491042.65 |
March | 0.00 | 73639243.64 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47120166.80 |
April | 0.00 | 71920171.51 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33841983.97 |
May | 0.00 | 73934212.43 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21113612.56 |
June | 0.00 | 71349576.37 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2510.87 | 13462209.29 |
July | 0.00 | 74514478.79 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25123.25 | 12723289.89 |
August | 0.00 | 73639243.64 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16347355.59 |
September | 0.00 | 71939513.95 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25483767.20 |
October | 0.00 | 74219510.00 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36899415.36 |
November | 0.00 | 71634873.94 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46941354.55 |
December | 0.00 | 74524150.01 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50864626.97 |
Annual Sum or Average | 0.00 | 0.872580E+09 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27634.12 | 0.395416E+09 |
Minimum of Months | 0.00 | 67036196.95 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12723289.89 |
Maximum of Months | 0.00 | 74524150.01 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25123.25 | 50864626.97 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 74249479.06 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55413448.65 |
February | 0.273974E+09 | 67054527.88 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47407645.91 |
March | 0.303685E+09 | 73659380.16 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44408127.40 |
April | 0.293479E+09 | 71939837.95 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27036773.98 |
May | 0.303504E+09 | 73954429.61 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.68 | 14640330.75 |
June | 0.293842E+09 | 71369086.78 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 175543.86 | 7975088.67 |
July | 0.303141E+09 | 74534854.64 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 356032.28 | 7251736.45 |
August | 0.303685E+09 | 73659380.16 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77861.12 | 10217387.32 |
September | 0.293479E+09 | 71959185.68 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18871926.57 |
October | 0.303322E+09 | 74239805.19 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33350928.29 |
November | 0.293661E+09 | 71654462.37 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53829427.96 |
December | 0.303141E+09 | 74544528.51 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58238535.90 |
Annual Sum or Average | 0.357224E+10 | 0.872819E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 609454.93 | 0.378641E+09 |
Minimum of Months | 0.273974E+09 | 67054527.88 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7251736.45 |
Maximum of Months | 0.303685E+09 | 74544528.51 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 356032.28 | 58238535.90 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118113E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197715E+09 |
February | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169361E+09 |
March | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160547E+09 |
April | 0.293479E+09 | 0.114438E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98497429.97 |
May | 0.303504E+09 | 0.117643E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7905.56 | 52665786.77 |
June | 0.293842E+09 | 0.113531E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 808752.04 | 27098352.40 |
July | 0.303141E+09 | 0.118566E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1640891.96 | 24574923.51 |
August | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 419823.52 | 35977029.92 |
September | 0.293479E+09 | 0.114469E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68383825.30 |
October | 0.303322E+09 | 0.118097E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119204E+09 |
November | 0.293661E+09 | 0.113984E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192036E+09 |
December | 0.303141E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207897E+09 |
Annual Sum or Average | 0.357224E+10 | 0.138844E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2877373.09 | 0.135396E+10 |
Minimum of Months | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24574923.51 |
Maximum of Months | 0.303685E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1640891.96 | 0.207897E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118099E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197673E+09 |
February | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168884E+09 |
March | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158816E+09 |
April | 0.293479E+09 | 0.114425E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97585208.29 |
May | 0.303504E+09 | 0.117629E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.79 | 53645197.65 |
June | 0.293842E+09 | 0.113517E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 622662.72 | 29782539.61 |
July | 0.303141E+09 | 0.118553E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1217379.01 | 27469370.37 |
August | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 263353.06 | 37664902.12 |
September | 0.293479E+09 | 0.114456E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67895760.14 |
October | 0.303322E+09 | 0.118083E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118346E+09 |
November | 0.293661E+09 | 0.113971E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191977E+09 |
December | 0.303141E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207878E+09 |
Annual Sum or Average | 0.357224E+10 | 0.138828E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2103457.58 | 0.135762E+10 |
Minimum of Months | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27469370.37 |
Maximum of Months | 0.303685E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1217379.01 | 0.207878E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.108388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242187E+09 |
February | 0.348285E+10 | 0.978647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206974E+09 |
March | 0.387034E+10 | 0.108722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193113E+09 |
April | 0.373454E+10 | 0.104713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118950E+09 |
May | 0.386038E+10 | 0.108576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68239323.01 |
June | 0.374269E+10 | 0.105194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420030.71 | 40186625.37 |
July | 0.385223E+10 | 0.108096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 984795.85 | 36625572.74 |
August | 0.386853E+10 | 0.108764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188779.28 | 49001679.36 |
September | 0.373273E+10 | 0.104755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82906373.18 |
October | 0.385404E+10 | 0.108346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144623E+09 |
November | 0.372639E+10 | 0.105110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235278E+09 |
December | 0.385223E+10 | 0.108096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254656E+09 |
Annual Sum or Average | 0.454292E+11 | 0.127663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1593605.85 | 0.167274E+10 |
Minimum of Months | 0.348285E+10 | 0.978647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36625572.74 |
Maximum of Months | 0.387034E+10 | 0.108764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 984795.85 | 0.254656E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118113E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197985E+09 |
February | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169136E+09 |
March | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158723E+09 |
April | 0.293479E+09 | 0.114438E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97837958.41 |
May | 0.303504E+09 | 0.117643E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5983.42 | 52528310.42 |
June | 0.293842E+09 | 0.113531E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 777467.67 | 27176990.38 |
July | 0.303141E+09 | 0.118566E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1593718.50 | 24621941.68 |
August | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 398256.41 | 35906597.54 |
September | 0.293479E+09 | 0.114469E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67701670.01 |
October | 0.303322E+09 | 0.118097E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118312E+09 |
November | 0.293661E+09 | 0.113984E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192282E+09 |
December | 0.303141E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208208E+09 |
Annual Sum or Average | 0.357224E+10 | 0.138844E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2775426.00 | 0.135042E+10 |
Minimum of Months | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24621941.68 |
Maximum of Months | 0.303685E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1593718.50 | 0.208208E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118099E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197963E+09 |
February | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169036E+09 |
March | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157643E+09 |
April | 0.293479E+09 | 0.114425E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96299500.87 |
May | 0.303504E+09 | 0.117629E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.06 | 54103216.73 |
June | 0.293842E+09 | 0.113517E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 603461.97 | 31512657.08 |
July | 0.303141E+09 | 0.118553E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1186814.92 | 27927745.38 |
August | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 251740.72 | 38354065.37 |
September | 0.293479E+09 | 0.114456E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66738665.61 |
October | 0.303322E+09 | 0.118083E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117695E+09 |
November | 0.293661E+09 | 0.113971E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192257E+09 |
December | 0.303141E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208189E+09 |
Annual Sum or Average | 0.357224E+10 | 0.138828E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2042036.67 | 0.135772E+10 |
Minimum of Months | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27927745.38 |
Maximum of Months | 0.303685E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1186814.92 | 0.208189E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 74249479.06 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101456E+09 |
February | 0.273974E+09 | 67054527.88 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87542055.27 |
March | 0.303685E+09 | 73659380.16 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82653242.87 |
April | 0.293479E+09 | 71939837.95 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50599722.15 |
May | 0.303504E+09 | 73954429.61 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3281.06 | 26981739.53 |
June | 0.293842E+09 | 71369086.78 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 401610.42 | 13920572.96 |
July | 0.303141E+09 | 74534854.64 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 817435.93 | 12621658.37 |
August | 0.303685E+09 | 73659380.16 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 205390.08 | 18469835.24 |
September | 0.293479E+09 | 71959185.68 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35224000.34 |
October | 0.303322E+09 | 74239805.19 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61613468.06 |
November | 0.293661E+09 | 71654462.37 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98703019.14 |
December | 0.303141E+09 | 74544528.51 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106562E+09 |
Annual Sum or Average | 0.357224E+10 | 0.872819E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1427717.50 | 0.696347E+09 |
Minimum of Months | 0.273974E+09 | 67054527.88 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12621658.37 |
Maximum of Months | 0.303685E+09 | 74544528.51 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 817435.93 | 0.106562E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.253350E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509120E+09 |
February | 0.415303E+11 | 0.217769E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437077E+09 |
March | 0.461508E+11 | 0.224613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416918E+09 |
April | 0.445315E+11 | 0.188146E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264895E+09 |
May | 0.460320E+11 | 0.180463E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153857E+09 |
June | 0.446286E+11 | 0.166014E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 580003.76 | 89554759.13 |
July | 0.459349E+11 | 0.175715E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1376933.51 | 82855014.89 |
August | 0.461292E+11 | 0.193996E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 137252.98 | 0.112412E+09 |
September | 0.445099E+11 | 0.210682E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192724E+09 |
October | 0.459565E+11 | 0.236109E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321674E+09 |
November | 0.444343E+11 | 0.242018E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495018E+09 |
December | 0.459349E+11 | 0.256026E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532137E+09 |
Annual Sum or Average | 0.541708E+12 | 0.254490E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2094190.25 | 0.360824E+10 |
Minimum of Months | 0.415303E+11 | 0.166014E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82855014.89 |
Maximum of Months | 0.461508E+11 | 0.256026E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1376933.51 | 0.532137E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.253350E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512348E+09 |
February | 0.415303E+11 | 0.217769E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439839E+09 |
March | 0.461508E+11 | 0.224613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419759E+09 |
April | 0.445315E+11 | 0.188146E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266667E+09 |
May | 0.460320E+11 | 0.180463E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154649E+09 |
June | 0.446286E+11 | 0.166014E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 578623.89 | 89864376.22 |
July | 0.459349E+11 | 0.175715E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1369336.40 | 83164422.72 |
August | 0.461292E+11 | 0.193993E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 137238.95 | 0.113056E+09 |
September | 0.445099E+11 | 0.210682E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194180E+09 |
October | 0.459565E+11 | 0.236109E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324188E+09 |
November | 0.444343E+11 | 0.242018E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498302E+09 |
December | 0.459349E+11 | 0.256026E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535344E+09 |
Annual Sum or Average | 0.541708E+12 | 0.254490E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2085199.24 | 0.363136E+10 |
Minimum of Months | 0.415303E+11 | 0.166014E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83164422.72 |
Maximum of Months | 0.461508E+11 | 0.256026E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1369336.40 | 0.535344E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.101925E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463337E+09 |
February | 0.369574E+10 | 0.920291E+09 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398484E+09 |
March | 0.410691E+10 | 0.102239E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377501E+09 |
April | 0.396281E+10 | 0.984694E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237804E+09 |
May | 0.409635E+10 | 0.102102E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137210E+09 |
June | 0.397146E+10 | 0.989210E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 521058.02 | 79588444.07 |
July | 0.408770E+10 | 0.101650E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 1230707.52 | 73545466.38 |
August | 0.410499E+10 | 0.102279E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 124319.71 | 0.100274E+09 |
September | 0.396089E+10 | 0.985086E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172970E+09 |
October | 0.408962E+10 | 0.101886E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290582E+09 |
November | 0.395417E+10 | 0.988424E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451493E+09 |
December | 0.408770E+10 | 0.101650E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486516E+09 |
Annual Sum or Average | 0.482060E+11 | 0.120050E+11 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 1876085.25 | 0.326931E+10 |
Minimum of Months | 0.369574E+10 | 0.920291E+09 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73545466.38 |
Maximum of Months | 0.410691E+10 | 0.102279E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 1230707.52 | 0.486516E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.114712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429324E+09 |
February | 0.368610E+10 | 0.103575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366882E+09 |
March | 0.409620E+10 | 0.115066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342437E+09 |
April | 0.395248E+10 | 0.110823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209717E+09 |
May | 0.408566E+10 | 0.114911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118544E+09 |
June | 0.396110E+10 | 0.111331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549406.93 | 70435600.03 |
July | 0.407704E+10 | 0.114403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1342599.77 | 64327956.02 |
August | 0.409429E+10 | 0.115110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223780.12 | 85557503.59 |
September | 0.395056E+10 | 0.110867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145522E+09 |
October | 0.407896E+10 | 0.114668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256537E+09 |
November | 0.394385E+10 | 0.111243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417018E+09 |
December | 0.407704E+10 | 0.114403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451357E+09 |
Annual Sum or Average | 0.480803E+11 | 0.135111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2115786.82 | 0.295766E+10 |
Minimum of Months | 0.368610E+10 | 0.103575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64327956.02 |
Maximum of Months | 0.409620E+10 | 0.115110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1342599.77 | 0.451357E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 8344.11 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 8344.11 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 8344.11 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 8344.11 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 8344.11 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 8344.11 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 8344.11 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 8344.11 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 8344.11 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 8344.11 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 8344.11 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 8344.11 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 8344.11 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 8344.11 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 461.08 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 206.81 | 12-JAN-06:00 |
February | 1169.53 | 01-FEB-00:10 | 461.08 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 199.67 | 27-FEB-05:03 |
March | 1169.53 | 01-MAR-00:10 | 461.08 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 176.36 | 01-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 461.08 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 145.14 | 03-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 461.08 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 65.62 | 28-MAY-02:00 |
June | 1169.53 | 01-JUN-00:10 | 461.08 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 | 30-JUN-15:00 | 55.50 | 02-JUN-04:00 |
July | 1169.53 | 01-JUL-00:10 | 461.08 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.65 | 29-JUL-17:00 | 42.82 | 31-JUL-03:40 |
August | 1169.53 | 01-AUG-00:10 | 461.08 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 | 11-AUG-18:00 | 72.53 | 31-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 461.08 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 83.67 | 30-SEP-09:00 |
October | 1169.53 | 01-OCT-23:10 | 461.08 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 141.94 | 22-OCT-06:40 |
November | 1169.53 | 01-NOV-00:10 | 461.08 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 178.05 | 29-NOV-10:00 |
December | 1169.53 | 01-DEC-00:10 | 461.08 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 192.71 | 15-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 461.08 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.82 | |||||
Maximum of Months | 1169.53 | 461.08 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 19.65 | 206.81 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 533.93 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 83.32 | 12-JAN-06:00 |
February | 1354.32 | 01-FEB-00:10 | 533.93 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 78.91 | 27-FEB-05:00 |
March | 1354.32 | 01-MAR-00:10 | 533.93 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 68.08 | 01-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 533.93 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 57.17 | 03-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 533.93 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 27.08 | 27-MAY-04:00 |
June | 1354.32 | 01-JUN-00:10 | 533.93 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.43 | 30-JUN-15:00 | 24.03 | 02-JUN-04:00 |
July | 1354.32 | 01-JUL-00:10 | 533.93 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.44 | 29-JUL-16:00 | 19.45 | 31-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 533.93 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.42 | 11-AUG-17:00 | 30.52 | 31-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 533.93 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 33.70 | 29-SEP-07:00 |
October | 1354.32 | 01-OCT-23:10 | 533.93 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 55.31 | 22-OCT-07:00 |
November | 1354.32 | 01-NOV-00:10 | 533.93 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 69.20 | 29-NOV-10:00 |
December | 1354.32 | 01-DEC-00:10 | 533.93 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 76.31 | 15-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 533.93 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.45 | |||||
Maximum of Months | 1354.32 | 533.93 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 7.44 | 83.32 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 615.76 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 198.45 | 12-JAN-07:40 |
February | 286.42 | 01-FEB-00:10 | 615.76 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 186.49 | 27-FEB-05:00 |
March | 286.42 | 01-MAR-00:10 | 615.76 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 160.88 | 01-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 615.76 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 132.41 | 03-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 615.76 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 62.73 | 27-MAY-07:00 |
June | 286.42 | 01-JUN-00:10 | 615.76 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.88 | 30-JUN-15:00 | 55.62 | 02-JUN-04:00 |
July | 286.42 | 01-JUL-00:10 | 615.76 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 | 29-JUL-17:00 | 45.34 | 31-JUL-05:00 |
August | 286.42 | 01-AUG-00:10 | 615.76 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.47 | 11-AUG-17:00 | 70.81 | 31-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 615.76 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 77.76 | 29-SEP-07:00 |
October | 286.42 | 01-OCT-23:10 | 615.76 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 129.48 | 22-OCT-06:20 |
November | 286.42 | 01-NOV-00:10 | 615.76 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 163.53 | 29-NOV-10:00 |
December | 286.42 | 01-DEC-00:10 | 615.76 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 180.34 | 15-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.34 | |||||
Maximum of Months | 286.42 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 | 198.45 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 137.35 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 114.49 | 12-JAN-06:50 |
February | 220.32 | 01-FEB-00:10 | 137.35 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 107.59 | 27-FEB-06:00 |
March | 220.32 | 01-MAR-00:10 | 137.35 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 92.82 | 01-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 137.35 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 76.39 | 03-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 137.35 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 35.70 | 27-MAY-04:00 |
June | 220.32 | 01-JUN-00:10 | 137.35 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.46 | 30-JUN-15:00 | 31.91 | 02-JUN-04:00 |
July | 220.32 | 01-JUL-00:10 | 137.35 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.13 | 29-JUL-17:00 | 25.99 | 31-JUL-05:00 |
August | 220.32 | 01-AUG-00:10 | 137.35 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.80 | 11-AUG-17:00 | 40.20 | 31-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 137.35 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 44.03 | 30-SEP-09:00 |
October | 220.32 | 01-OCT-23:10 | 137.35 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 74.70 | 22-OCT-07:00 |
November | 220.32 | 01-NOV-00:10 | 137.35 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 94.35 | 29-NOV-10:00 |
December | 220.32 | 01-DEC-00:10 | 137.35 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 104.05 | 15-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 137.35 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.99 | |||||
Maximum of Months | 220.32 | 137.35 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 10.13 | 114.49 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 360.62 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 263.90 | 12-JAN-21:00 |
February | 907.20 | 01-FEB-00:10 | 360.62 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 246.86 | 27-FEB-07:10 |
March | 907.20 | 01-MAR-00:10 | 360.62 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 219.68 | 01-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 360.62 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 193.37 | 03-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 360.62 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.26 | 31-MAY-16:00 | 92.01 | 27-MAY-07:10 |
June | 907.20 | 01-JUN-00:10 | 360.62 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 19.44 | 30-JUN-15:00 | 71.49 | 02-JUN-04:10 |
July | 907.20 | 01-JUL-00:10 | 360.62 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 28.85 | 29-JUL-17:00 | 62.61 | 31-JUL-05:10 |
August | 907.20 | 01-AUG-00:10 | 360.62 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 12.93 | 11-AUG-17:00 | 102.25 | 31-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 360.62 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 116.23 | 30-SEP-09:00 |
October | 907.20 | 01-OCT-23:10 | 360.62 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 189.51 | 22-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 360.62 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 228.95 | 30-NOV-21:00 |
December | 907.20 | 01-DEC-00:10 | 360.62 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 246.24 | 15-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 62.61 | ||||||
Maximum of Months | 907.20 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 28.85 | 263.90 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1416.11 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 471.51 | 12-JAN-06:00 |
February | 15368.40 | 01-FEB-00:10 | 1416.11 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 451.92 | 27-FEB-05:30 |
March | 15368.40 | 01-MAR-00:10 | 1416.11 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 389.91 | 01-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 1416.11 | 03-APR-19:40 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 320.86 | 03-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 1258.77 | 04-MAY-20:30 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 151.89 | 27-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 1106.77 | 02-JUN-20:00 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.45 | 30-JUN-15:00 | 134.67 | 02-JUN-04:00 |
July | 15368.40 | 01-JUL-00:10 | 1147.23 | 28-JUL-20:00 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.59 | 29-JUL-17:00 | 107.95 | 31-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 1416.11 | 29-AUG-19:30 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.60 | 11-AUG-18:00 | 167.34 | 31-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 1416.11 | 01-SEP-19:30 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 185.74 | 30-SEP-06:00 |
October | 15368.40 | 01-OCT-23:10 | 1416.11 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 313.79 | 22-OCT-06:00 |
November | 15368.40 | 01-NOV-00:10 | 1416.11 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 391.59 | 29-NOV-10:00 |
December | 15368.40 | 01-DEC-00:10 | 1416.11 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 432.04 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1106.77 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.95 | |||||
Maximum of Months | 15368.40 | 1416.11 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 41.59 | 471.51 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9580.84 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1370.13 | 12-JAN-06:00 |
February | 45622.98 | 01-FEB-00:10 | 9580.84 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1291.14 | 27-FEB-06:00 |
March | 45622.98 | 01-MAR-00:10 | 9580.84 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1113.88 | 01-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 9580.84 | 03-APR-19:40 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 944.61 | 03-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 9388.46 | 02-MAY-19:00 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 456.31 | 27-MAY-04:00 |
June | 45622.98 | 01-JUN-00:10 | 9231.95 | 02-JUN-19:00 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.19 | 30-JUN-15:00 | 404.07 | 02-JUN-04:00 |
July | 45622.98 | 01-JUL-00:10 | 9186.25 | 28-JUL-19:00 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.62 | 29-JUL-16:00 | 328.01 | 31-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 9580.84 | 29-AUG-19:30 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.16 | 11-AUG-17:00 | 506.63 | 31-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 9580.84 | 01-SEP-19:30 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 559.84 | 30-SEP-06:00 |
October | 45622.98 | 01-OCT-23:10 | 9580.84 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 915.48 | 22-OCT-07:00 |
November | 45622.98 | 01-NOV-00:10 | 9580.84 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1132.29 | 29-NOV-10:00 |
December | 45622.98 | 01-DEC-00:10 | 9580.84 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1247.10 | 15-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9186.25 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.01 | |||||
Maximum of Months | 45622.98 | 9580.84 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 118.62 | 1370.13 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.87 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 126.59 | 12-JAN-06:06 |
February | 180.00 | 01-FEB-00:10 | 106.87 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 118.97 | 27-FEB-05:10 |
March | 180.00 | 01-MAR-00:10 | 106.87 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 102.68 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 106.87 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 84.55 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 106.87 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.75 | 31-MAY-16:00 | 38.36 | 28-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 106.87 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.26 | 30-JUN-15:10 | 32.49 | 02-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 106.87 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.51 | 29-JUL-16:30 | 25.12 | 31-JUL-03:50 |
August | 180.00 | 01-AUG-00:10 | 106.87 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.37 | 11-AUG-16:00 | 42.38 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 106.87 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 48.85 | 30-SEP-09:00 |
October | 180.00 | 01-OCT-00:10 | 106.87 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 82.68 | 22-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 106.87 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 104.36 | 29-NOV-10:00 |
December | 180.00 | 01-DEC-00:10 | 106.87 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 115.06 | 15-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.12 | |||||
Maximum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 14.51 | 126.59 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.85 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 126.58 | 12-JAN-06:06 |
February | 180.00 | 01-FEB-00:10 | 106.85 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 118.96 | 27-FEB-05:10 |
March | 180.00 | 01-MAR-00:10 | 106.85 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 102.67 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 106.85 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 84.54 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 106.85 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 | 31-MAY-15:10 | 38.36 | 28-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 106.85 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 | 30-JUN-15:08 | 32.49 | 02-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 106.85 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.51 | 29-JUL-16:00 | 25.12 | 31-JUL-03:10 |
August | 180.00 | 01-AUG-00:10 | 106.85 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.37 | 11-AUG-16:10 | 42.37 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 106.85 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 48.84 | 30-SEP-09:00 |
October | 180.00 | 01-OCT-00:10 | 106.85 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 82.67 | 22-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 106.85 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 104.35 | 29-NOV-10:00 |
December | 180.00 | 01-DEC-00:10 | 106.85 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 115.05 | 15-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.12 | |||||
Maximum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 14.51 | 126.58 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 67.16 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 32.02 | 12-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 67.16 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 29.97 | 27-FEB-05:10 |
March | 0.00 | 01-MAR-00:10 | 67.16 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 28.57 | 31-MAR-06:00 |
April | 0.00 | 01-APR-00:10 | 67.16 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 25.70 | 03-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 67.16 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 13.42 | 27-MAY-07:00 |
June | 0.00 | 01-JUN-00:10 | 67.16 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 | 30-JUN-15:00 | 11.89 | 02-JUN-04:00 |
July | 0.00 | 01-JUL-00:10 | 67.16 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.51 | 29-JUL-16:10 | 9.80 | 31-JUL-03:30 |
August | 0.00 | 01-AUG-00:10 | 67.16 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 14.70 | 31-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 67.16 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 16.52 | 30-SEP-09:00 |
October | 0.00 | 01-OCT-00:10 | 67.16 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 22.86 | 22-OCT-09:00 |
November | 0.00 | 01-NOV-00:10 | 67.16 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 25.96 | 29-NOV-10:00 |
December | 0.00 | 01-DEC-00:10 | 67.16 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 28.87 | 15-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 67.16 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.80 | |||||
Maximum of Months | 0.00 | 67.16 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 1.51 | 32.02 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 67.18 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 35.33 | 12-JAN-06:10 |
February | 180.00 | 01-FEB-00:10 | 67.18 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 33.20 | 27-FEB-05:10 |
March | 180.00 | 01-MAR-00:10 | 67.18 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 28.66 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 67.18 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 23.60 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 67.18 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 | 31-MAY-15:10 | 11.21 | 27-MAY-07:30 |
June | 180.00 | 01-JUN-00:10 | 67.18 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.86 | 30-JUN-15:10 | 9.07 | 02-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 67.18 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.05 | 29-JUL-16:10 | 7.01 | 31-JUL-03:10 |
August | 180.00 | 01-AUG-00:10 | 67.18 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.06 | 11-AUG-16:00 | 11.83 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 67.18 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 13.94 | 30-SEP-08:00 |
October | 180.00 | 01-OCT-00:10 | 67.18 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 23.08 | 22-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 67.18 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 29.13 | 29-NOV-10:00 |
December | 180.00 | 01-DEC-00:10 | 67.18 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 32.11 | 15-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 67.18 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.01 | |||||
Maximum of Months | 180.00 | 67.18 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4.05 | 35.33 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.87 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 126.59 | 12-JAN-06:06 |
February | 180.00 | 01-FEB-00:10 | 106.87 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 118.97 | 27-FEB-05:10 |
March | 180.00 | 01-MAR-00:10 | 106.87 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 102.68 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 106.87 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 84.55 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 106.87 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.75 | 31-MAY-16:00 | 39.12 | 27-MAY-07:20 |
June | 180.00 | 01-JUN-00:10 | 106.87 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.26 | 30-JUN-15:10 | 32.49 | 02-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 106.87 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.51 | 29-JUL-16:20 | 25.12 | 31-JUL-03:10 |
August | 180.00 | 01-AUG-00:10 | 106.87 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.37 | 11-AUG-16:00 | 43.33 | 31-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 106.87 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 51.88 | 30-SEP-08:00 |
October | 180.00 | 01-OCT-00:10 | 106.87 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 82.68 | 22-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 106.87 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 104.36 | 29-NOV-10:00 |
December | 180.00 | 01-DEC-00:10 | 106.87 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 115.06 | 15-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.12 | |||||
Maximum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 14.51 | 126.59 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.85 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 126.58 | 12-JAN-06:06 |
February | 180.00 | 01-FEB-00:10 | 106.85 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 118.96 | 27-FEB-05:10 |
March | 180.00 | 01-MAR-00:10 | 106.85 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 102.67 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 106.85 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 84.54 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 106.85 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 | 31-MAY-15:08 | 39.05 | 27-MAY-07:20 |
June | 180.00 | 01-JUN-00:10 | 106.85 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 | 30-JUN-15:10 | 32.49 | 02-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 106.85 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.51 | 29-JUL-17:00 | 25.12 | 31-JUL-04:07 |
August | 180.00 | 01-AUG-00:10 | 106.85 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.37 | 11-AUG-16:00 | 43.33 | 31-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 106.85 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 51.06 | 30-SEP-08:00 |
October | 180.00 | 01-OCT-00:10 | 106.85 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 82.67 | 22-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 106.85 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 104.35 | 29-NOV-10:00 |
December | 180.00 | 01-DEC-00:10 | 106.85 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 115.05 | 15-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.12 | |||||
Maximum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 14.51 | 126.58 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1044.00 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 152.56 | 12-JAN-06:00 |
February | 2263.36 | 01-FEB-00:10 | 1044.00 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 143.58 | 27-FEB-05:50 |
March | 2263.36 | 01-MAR-00:10 | 1044.00 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 123.89 | 01-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1044.00 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 101.97 | 03-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1044.00 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 48.13 | 27-MAY-04:00 |
June | 2263.36 | 01-JUN-00:10 | 1044.00 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.47 | 30-JUN-15:00 | 42.95 | 02-JUN-04:00 |
July | 2263.36 | 01-JUL-00:10 | 1044.00 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.08 | 29-JUL-17:00 | 34.89 | 31-JUL-05:00 |
August | 2263.36 | 01-AUG-00:10 | 1044.00 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.58 | 23-AUG-18:00 | 53.90 | 31-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1044.00 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 58.82 | 30-SEP-09:00 |
October | 2263.36 | 01-OCT-23:10 | 1044.00 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 99.72 | 22-OCT-07:00 |
November | 2263.36 | 01-NOV-00:10 | 1044.00 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 125.93 | 29-NOV-10:00 |
December | 2263.36 | 01-DEC-00:10 | 1044.00 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 138.86 | 15-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1044.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.89 | ||||
Maximum of Months | 2263.36 | 1044.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.08 | 152.56 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.87 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 126.75 | 12-JAN-06:08 |
February | 180.00 | 01-FEB-00:10 | 106.87 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 119.12 | 27-FEB-05:10 |
March | 180.00 | 01-MAR-00:10 | 106.87 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 102.82 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 106.87 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 84.68 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 106.87 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.58 | 31-MAY-16:00 | 38.48 | 28-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 106.87 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.16 | 30-JUN-15:10 | 32.60 | 02-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 106.87 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.42 | 29-JUL-16:30 | 25.24 | 31-JUL-03:10 |
August | 180.00 | 01-AUG-00:10 | 106.87 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.27 | 11-AUG-16:00 | 42.50 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 106.87 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 48.97 | 30-SEP-09:00 |
October | 180.00 | 01-OCT-00:10 | 106.87 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 82.82 | 22-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 106.87 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 104.51 | 29-NOV-10:00 |
December | 180.00 | 01-DEC-00:10 | 106.87 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 115.21 | 15-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.24 | |||||
Maximum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 14.42 | 126.75 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.85 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 126.74 | 12-JAN-06:08 |
February | 180.00 | 01-FEB-00:10 | 106.85 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 119.11 | 27-FEB-05:10 |
March | 180.00 | 01-MAR-00:10 | 106.85 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 102.82 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 106.85 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 84.68 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 106.85 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 | 31-MAY-15:10 | 38.47 | 28-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 106.85 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.16 | 30-JUN-15:10 | 32.60 | 02-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 106.85 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.42 | 29-JUL-16:00 | 25.24 | 31-JUL-03:40 |
August | 180.00 | 01-AUG-00:10 | 106.85 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.27 | 11-AUG-16:00 | 42.49 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 106.85 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 48.96 | 30-SEP-09:00 |
October | 180.00 | 01-OCT-00:10 | 106.85 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 82.81 | 22-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 106.85 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 104.50 | 29-NOV-10:00 |
December | 180.00 | 01-DEC-00:10 | 106.85 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 115.21 | 15-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.24 | |||||
Maximum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 14.42 | 126.74 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 67.18 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 64.85 | 12-JAN-06:10 |
February | 180.00 | 01-FEB-00:10 | 67.18 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 60.95 | 27-FEB-05:10 |
March | 180.00 | 01-MAR-00:10 | 67.18 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 52.61 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 67.18 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 43.33 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 67.18 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 | 31-MAY-16:00 | 19.80 | 27-MAY-07:20 |
June | 180.00 | 01-JUN-00:10 | 67.18 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.20 | 30-JUN-15:10 | 16.68 | 02-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 67.18 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.38 | 29-JUL-16:10 | 12.91 | 31-JUL-03:10 |
August | 180.00 | 01-AUG-00:10 | 67.18 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.72 | 11-AUG-16:00 | 21.74 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 67.18 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 25.05 | 30-SEP-09:00 |
October | 180.00 | 01-OCT-00:10 | 67.18 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 42.37 | 22-OCT-06:10 |
November | 180.00 | 01-NOV-00:10 | 67.18 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 53.47 | 29-NOV-10:00 |
December | 180.00 | 01-DEC-00:10 | 67.18 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 58.95 | 15-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 67.18 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.91 | |||||
Maximum of Months | 180.00 | 67.18 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 7.38 | 64.85 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2486.81 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 308.94 | 12-JAN-08:00 |
February | 26988.77 | 01-FEB-00:10 | 2486.81 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 290.32 | 27-FEB-05:20 |
March | 26988.77 | 01-MAR-00:10 | 2486.81 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 251.71 | 01-MAR-00:05 |
April | 26988.77 | 01-APR-00:10 | 2486.81 | 03-APR-19:40 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 219.68 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2210.50 | 04-MAY-20:30 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 106.73 | 28-MAY-02:00 |
June | 26988.77 | 01-JUN-00:10 | 2130.81 | 02-JUN-19:00 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 30-JUN-15:00 | 92.42 | 02-JUN-04:00 |
July | 26988.77 | 01-JUL-00:10 | 2115.71 | 26-JUL-20:00 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.64 | 29-JUL-17:00 | 74.31 | 31-JUL-04:10 |
August | 26988.77 | 01-AUG-00:10 | 2486.81 | 29-AUG-19:30 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.06 | 11-AUG-16:00 | 116.83 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2486.81 | 01-SEP-19:30 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 132.46 | 30-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2486.81 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 216.11 | 22-OCT-07:00 |
November | 26988.77 | 01-NOV-00:10 | 2486.81 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 254.66 | 29-NOV-10:00 |
December | 26988.77 | 01-DEC-00:10 | 2486.81 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 280.79 | 15-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2115.71 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.31 | |||||
Maximum of Months | 26988.77 | 2486.81 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 23.64 | 308.94 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2486.81 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 308.93 | 12-JAN-07:40 |
February | 26988.77 | 01-FEB-00:10 | 2486.81 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 290.31 | 27-FEB-05:00 |
March | 26988.77 | 01-MAR-00:10 | 2486.81 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 252.37 | 01-MAR-00:05 |
April | 26988.77 | 01-APR-00:10 | 2486.81 | 03-APR-19:40 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 220.67 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2210.50 | 04-MAY-20:30 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 106.73 | 28-MAY-02:00 |
June | 26988.77 | 01-JUN-00:10 | 2130.81 | 02-JUN-19:00 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 30-JUN-15:00 | 92.42 | 02-JUN-04:00 |
July | 26988.77 | 01-JUL-00:10 | 2115.71 | 26-JUL-20:00 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.64 | 29-JUL-17:00 | 74.31 | 31-JUL-04:10 |
August | 26988.77 | 01-AUG-00:10 | 2486.81 | 29-AUG-19:30 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.06 | 11-AUG-16:00 | 116.83 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2486.81 | 01-SEP-19:30 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 132.61 | 30-SEP-07:13 |
October | 26988.77 | 01-OCT-23:10 | 2486.81 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 216.17 | 22-OCT-06:10 |
November | 26988.77 | 01-NOV-00:10 | 2486.81 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 254.64 | 29-NOV-10:00 |
December | 26988.77 | 01-DEC-00:10 | 2486.81 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 280.77 | 15-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2115.71 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.31 | |||||
Maximum of Months | 26988.77 | 2486.81 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 23.64 | 308.93 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 981.75 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 276.52 | 12-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 981.75 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 257.55 | 27-FEB-06:20 |
March | 2401.70 | 01-MAR-00:10 | 981.75 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 224.38 | 01-MAR-00:05 |
April | 2401.70 | 01-APR-00:10 | 981.75 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 197.53 | 03-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 981.75 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 94.97 | 27-MAY-07:00 |
June | 2401.70 | 01-JUN-00:10 | 981.75 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 15.10 | 30-JUN-15:00 | 82.74 | 02-JUN-04:00 |
July | 2401.70 | 01-JUL-00:10 | 981.75 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 21.21 | 29-JUL-17:00 | 66.49 | 31-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 981.75 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 5.47 | 11-AUG-16:00 | 104.57 | 31-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 981.75 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 118.80 | 30-SEP-09:00 |
October | 2401.70 | 01-OCT-23:10 | 981.75 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 193.51 | 22-OCT-06:10 |
November | 2401.70 | 01-NOV-00:10 | 981.75 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 231.48 | 29-NOV-20:00 |
December | 2401.70 | 01-DEC-00:10 | 981.75 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 251.32 | 15-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 981.75 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 66.49 | ||||||
Maximum of Months | 2401.70 | 981.75 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 21.21 | 276.52 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1104.91 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 269.84 | 12-JAN-06:00 |
February | 2395.44 | 01-FEB-00:10 | 1104.91 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 254.38 | 27-FEB-05:20 |
March | 2395.44 | 01-MAR-00:10 | 1104.91 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 219.51 | 01-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1104.91 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 180.71 | 03-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1104.91 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 82.21 | 27-MAY-04:00 |
June | 2395.44 | 01-JUN-00:10 | 1104.91 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.74 | 30-JUN-15:00 | 74.39 | 02-JUN-04:00 |
July | 2395.44 | 01-JUL-00:10 | 1104.91 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.42 | 29-JUL-17:00 | 60.11 | 31-JUL-05:00 |
August | 2395.44 | 01-AUG-00:10 | 1104.91 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 | 11-AUG-18:00 | 91.74 | 31-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1104.91 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 104.33 | 30-SEP-09:00 |
October | 2395.44 | 01-OCT-23:10 | 1104.91 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 176.73 | 22-OCT-06:30 |
November | 2395.44 | 01-NOV-00:10 | 1104.91 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 223.11 | 29-NOV-10:00 |
December | 2395.44 | 01-DEC-00:10 | 1104.91 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 246.02 | 15-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1104.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.11 | ||||
Maximum of Months | 2395.44 | 1104.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.42 | 269.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19199.68 | 11-JAN-22:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13675.86 | 28-FEB-22:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12385.60 | 01-MAR-21:53 | 30671.71 | 22251.00 | 27376.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10205.32 | 22-APR-10:33 | 11501.89 | 6953.51 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10602.56 | 14-MAY-10:33 | 11501.89 | 8343.99 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11087.66 | 29-JUN-10:33 | 7667.93 | 6953.51 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 12222.00 | 23-JUL-10:33 | 11501.89 | 8343.99 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 12924.96 | 26-AUG-10:33 | 11501.89 | 6953.51 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14747.31 | 20-SEP-21:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14934.50 | 06-OCT-21:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15977.81 | 28-NOV-23:00 | 11501.89 | 5562.78 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16418.80 | 13-DEC-01:00 | 11501.89 | 1854.22 | 3041.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 10205.32 | 7667.93 | 1854.22 | 3041.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19199.68 | 30671.71 | 22251.00 | 27376.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1098.90 | 30-JAN-12:30 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.60 |
February | 2141.94 | 15-FEB-13:40 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.31 |
March | 2950.45 | 27-MAR-14:10 | 389.84 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.06 |
April | 4378.13 | 22-APR-13:30 | 389.84 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 |
May | 4157.26 | 12-MAY-13:30 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.81 |
June | 3671.52 | 29-JUN-14:10 | 389.84 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 4.79 | 0.00 |
July | 4378.24 | 23-JUL-13:30 | 259.90 | 102.46 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 2.86 | 0.00 |
August | 4635.84 | 25-AUG-13:30 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.74 |
September | 3968.31 | 09-SEP-13:30 | 389.84 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.83 |
October | 3048.49 | 03-OCT-13:30 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.48 |
November | 1809.77 | 08-NOV-13:30 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.22 |
December | 45.16 | 24-DEC-22:00 | 1039.58 | 307.39 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 45.16 | 259.90 | 102.46 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4635.84 | 1039.58 | 307.39 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 4.79 | 151.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1184.30 | 30-JAN-19:25 | 2106.72 | 949.22 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.39 |
February | 1312.76 | 21-FEB-19:53 | 3160.08 | 1423.83 | 2256.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.11 |
March | 1362.84 | 01-MAR-21:53 | 3611.52 | 1423.83 | 2256.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.69 |
April | 1428.72 | 21-APR-20:10 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.01 |
May | 1464.32 | 10-MAY-21:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.91 |
June | 1688.28 | 21-JUN-21:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 |
July | 1674.12 | 12-JUL-21:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.74 |
August | 1663.20 | 11-AUG-21:00 | 2407.68 | 949.22 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 |
September | 1310.94 | 10-SEP-10:33 | 1354.32 | 533.93 | 1002.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 |
October | 1204.47 | 03-OCT-20:00 | 1053.36 | 533.93 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 |
November | 1386.55 | 08-NOV-20:53 | 3160.08 | 1601.80 | 2381.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.77 |
December | 1340.78 | 27-DEC-20:13 | 3160.08 | 1601.80 | 2381.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1184.30 | 1053.36 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 | |
Maximum of Months | 1688.28 | 3611.52 | 1601.80 | 2381.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 625.33 | 23-JAN-22:00 | 254.59 | 547.34 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.48 |
February | 706.07 | 09-FEB-21:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.06 |
March | 761.17 | 22-MAR-20:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.52 |
April | 956.27 | 22-APR-10:33 | 286.42 | 513.13 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.54 |
May | 1058.66 | 14-MAY-10:33 | 286.42 | 615.76 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.93 |
June | 1128.87 | 22-JUN-21:00 | 254.59 | 547.34 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 |
July | 1177.66 | 12-JUL-21:00 | 254.59 | 547.34 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.57 |
August | 1084.73 | 01-AUG-10:33 | 190.94 | 513.13 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.62 |
September | 971.06 | 10-SEP-10:33 | 286.42 | 615.76 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 |
October | 829.53 | 04-OCT-20:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.81 |
November | 665.24 | 02-NOV-20:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.60 |
December | 598.40 | 24-DEC-21:00 | 190.94 | 547.34 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 598.40 | 190.94 | 513.13 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 | |
Maximum of Months | 1177.66 | 286.42 | 615.76 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 51.81 | 21-JAN-21:50 | 171.36 | 106.83 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.48 |
February | 203.45 | 09-FEB-22:00 | 195.84 | 122.09 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.44 |
March | 380.59 | 22-MAR-20:00 | 171.36 | 137.35 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.05 |
April | 502.52 | 22-APR-10:33 | 220.32 | 114.47 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.55 |
May | 560.24 | 14-MAY-10:33 | 220.32 | 137.35 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.92 |
June | 589.75 | 22-JUN-10:33 | 146.88 | 114.47 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.92 |
July | 611.14 | 23-JUL-10:33 | 220.32 | 137.35 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 |
August | 574.87 | 01-AUG-10:33 | 146.88 | 114.47 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.06 |
September | 509.88 | 10-SEP-10:33 | 220.32 | 137.35 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.73 |
October | 410.37 | 04-OCT-20:00 | 171.36 | 137.35 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.46 |
November | 81.15 | 01-NOV-21:00 | 195.84 | 122.09 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.54 |
December | 54.63 | 24-DEC-22:00 | 195.84 | 91.57 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 51.81 | 146.88 | 91.57 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 | |
Maximum of Months | 611.14 | 220.32 | 137.35 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36248.61 | 20-JAN-21:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 152.55 |
February | 36794.18 | 09-FEB-21:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 134.06 |
March | 37385.98 | 22-MAR-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 82.18 |
April | 38048.19 | 21-APR-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 43.79 |
May | 38460.06 | 31-MAY-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 24.87 |
June | 38634.16 | 29-JUN-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 3.54 | 0.00 |
July | 38710.36 | 21-JUL-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 3.51 | 0.00 |
August | 38583.89 | 11-AUG-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 1.41 | 0.00 |
September | 37970.16 | 01-SEP-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 43.87 |
October | 37597.35 | 03-OCT-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 67.82 |
November | 36363.20 | 01-NOV-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 129.00 |
December | 36015.14 | 26-DEC-21:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 191.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36015.14 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38710.36 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 3.54 | 191.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7074.48 | 06-JAN-23:10 | 15368.40 | 472.04 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.23 |
February | 8570.05 | 20-FEB-13:00 | 5122.80 | 103.85 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.79 |
March | 12095.74 | 27-MAR-15:03 | 51228.00 | 519.24 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.55 |
April | 15780.72 | 22-APR-13:30 | 5122.80 | 86.54 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.37 |
May | 14777.08 | 13-MAY-13:10 | 5122.80 | 86.54 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.28 |
June | 13734.39 | 20-JUN-15:03 | 51228.00 | 519.24 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 6.94 | 0.00 |
July | 15027.60 | 23-JUL-13:30 | 3415.20 | 69.23 | 304.82 | 0.00 | 0.00 | 0.00 | 0.00 | 6.32 | 0.00 |
August | 15848.52 | 25-AUG-14:10 | 5122.80 | 86.54 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.21 |
September | 14752.39 | 09-SEP-13:30 | 5122.80 | 86.54 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.36 |
October | 11240.88 | 03-OCT-13:30 | 3415.20 | 86.54 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.26 |
November | 7374.66 | 08-NOV-13:30 | 3415.20 | 86.54 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.34 |
December | 6825.55 | 19-DEC-23:10 | 15368.40 | 472.04 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6825.55 | 3415.20 | 69.23 | 304.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15848.52 | 51228.00 | 519.24 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 6.94 | 303.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 29613.07 | 30-JAN-22:05 | 91245.96 | 12774.46 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1003.32 |
February | 31931.20 | 21-FEB-19:53 | 106453.62 | 25548.91 | 28504.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 990.51 |
March | 33353.56 | 01-MAR-21:53 | 121661.28 | 25548.91 | 28504.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1001.48 |
April | 34384.75 | 21-APR-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.73 |
May | 35850.61 | 31-MAY-21:10 | 91245.96 | 12567.80 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.03 |
June | 38343.74 | 21-JUN-21:03 | 273737.88 | 36460.67 | 44339.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 |
July | 38929.12 | 21-JUL-21:10 | 91245.96 | 12550.85 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 |
August | 39052.68 | 11-AUG-21:10 | 45622.98 | 6372.41 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.36 |
September | 32532.47 | 10-SEP-10:33 | 45622.98 | 8239.52 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.99 |
October | 29365.00 | 03-OCT-20:00 | 35484.54 | 9580.84 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.07 |
November | 33419.15 | 08-NOV-20:53 | 106453.62 | 28742.53 | 30087.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 983.19 |
December | 32566.36 | 27-DEC-20:13 | 106453.62 | 28742.53 | 30087.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1007.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 29365.00 | 35484.54 | 6372.41 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 | |
Maximum of Months | 39052.68 | 273737.88 | 36460.67 | 44339.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1007.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 926.10 | 22-JAN-09:04 | 378.00 | 418.92 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.77 |
February | 1104.71 | 11-FEB-19:04 | 819.00 | 748.06 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.96 |
March | 3020.71 | 31-MAR-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.19 |
April | 3164.62 | 21-APR-18:01 | 970.20 | 665.78 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.84 |
May | 3289.41 | 31-MAY-18:02 | 831.60 | 570.67 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.37 |
June | 3409.14 | 22-JUN-18:02 | 831.60 | 570.67 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 | 0.00 |
July | 3239.77 | 06-JUL-18:01 | 970.20 | 665.78 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 0.00 |
August | 3108.31 | 17-AUG-18:01 | 970.20 | 665.78 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.85 |
September | 3085.96 | 02-SEP-18:02 | 702.00 | 641.20 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.41 |
October | 2910.15 | 13-OCT-15:02 | 583.20 | 179.54 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.90 |
November | 790.66 | 04-NOV-08:04 | 378.00 | 418.92 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.85 |
December | 949.08 | 24-DEC-19:04 | 819.00 | 748.06 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 790.66 | 378.00 | 179.54 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3409.14 | 970.20 | 748.06 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 61.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1014.68 | 22-JAN-09:04 | 378.00 | 418.87 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.77 |
February | 1193.95 | 08-FEB-19:04 | 970.20 | 665.70 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.75 |
March | 2227.06 | 27-MAR-18:01 | 970.20 | 665.70 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.65 |
April | 2851.78 | 21-APR-18:01 | 970.20 | 665.70 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 |
May | 3330.00 | 09-MAY-20:01 | 1602.00 | 951.00 | 1843.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.14 |
June | 3232.01 | 26-JUN-21:51 | 1800.00 | 715.93 | 921.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.90 |
July | 3442.23 | 06-JUL-17:32 | 583.20 | 429.56 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.45 |
August | 3064.05 | 02-AUG-21:51 | 1800.00 | 715.93 | 921.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 |
September | 2886.78 | 02-SEP-19:41 | 936.00 | 854.83 | 1390.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.26 |
October | 1929.36 | 03-OCT-15:02 | 583.20 | 179.51 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.07 |
November | 858.45 | 04-NOV-08:04 | 378.00 | 418.87 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.85 |
December | 867.16 | 24-DEC-19:04 | 819.00 | 747.98 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 858.45 | 378.00 | 179.51 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.45 | |
Maximum of Months | 3442.23 | 1800.00 | 951.00 | 1843.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11.33 | 25-JAN-15:20 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.34 |
February | 84.94 | 15-FEB-15:20 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.30 |
March | 517.10 | 31-MAR-13:20 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.28 |
April | 804.77 | 22-APR-13:20 | 0.00 | 22.16 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.47 |
May | 766.95 | 12-MAY-13:15 | 0.00 | 37.61 | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.85 |
June | 678.42 | 30-JUN-12:30 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
July | 807.73 | 23-JUL-13:30 | 0.00 | 22.16 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 |
August | 851.58 | 25-AUG-13:30 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.38 |
September | 757.41 | 09-SEP-13:10 | 0.00 | 22.16 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.66 |
October | 601.57 | 03-OCT-12:50 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.34 |
November | 44.64 | 08-NOV-15:20 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.81 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 44.33 | 154.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 | |
Maximum of Months | 851.58 | 0.00 | 44.33 | 154.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 376.29 | 09-JAN-09:04 | 252.00 | 206.91 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.96 |
February | 440.79 | 12-FEB-16:04 | 378.00 | 155.19 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.05 |
March | 762.84 | 22-MAR-18:02 | 831.60 | 358.74 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.29 |
April | 845.39 | 30-APR-18:02 | 702.00 | 403.08 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.40 |
May | 939.03 | 31-MAY-15:02 | 583.20 | 112.86 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 |
June | 1013.31 | 22-JUN-21:51 | 1800.00 | 450.11 | 903.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.28 |
July | 958.02 | 29-JUL-18:02 | 702.00 | 403.08 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 1.95 | 0.00 |
August | 950.70 | 02-AUG-21:51 | 1800.00 | 450.11 | 903.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.07 |
September | 832.11 | 07-SEP-18:01 | 970.20 | 418.53 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 |
October | 777.26 | 03-OCT-18:01 | 970.20 | 418.53 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.81 |
November | 409.91 | 14-NOV-19:04 | 970.20 | 418.53 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.04 |
December | 456.99 | 24-DEC-09:01 | 378.00 | 263.34 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 376.29 | 252.00 | 112.86 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1013.31 | 1800.00 | 450.11 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 1.95 | 20.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 942.63 | 22-JAN-09:04 | 378.00 | 418.92 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.77 |
February | 1122.34 | 07-FEB-19:04 | 970.20 | 665.78 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.07 |
March | 2868.95 | 31-MAR-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.24 |
April | 2950.90 | 20-APR-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.40 |
May | 3111.00 | 12-MAY-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.49 |
June | 3165.85 | 22-JUN-18:02 | 831.60 | 570.67 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 0.00 |
July | 3093.71 | 29-JUL-18:02 | 702.00 | 641.20 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 7.55 | 0.00 |
August | 3040.70 | 23-AUG-18:02 | 831.60 | 570.67 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 4.05 | 0.00 |
September | 2871.95 | 07-SEP-18:01 | 970.20 | 665.78 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 |
October | 2784.33 | 04-OCT-08:62 | 216.00 | 282.13 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.97 |
November | 834.13 | 04-NOV-08:04 | 378.00 | 418.92 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.85 |
December | 897.79 | 24-DEC-09:04 | 378.00 | 418.92 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 834.13 | 216.00 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3165.85 | 970.20 | 665.78 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 7.55 | 61.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 899.36 | 22-JAN-09:04 | 378.00 | 418.87 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.77 |
February | 1059.53 | 11-FEB-19:04 | 819.00 | 747.98 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.96 |
March | 2420.17 | 27-MAR-08:61 | 252.00 | 329.11 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.79 |
April | 2653.33 | 23-APR-08:62 | 324.00 | 359.03 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.25 |
May | 2908.13 | 14-MAY-20:41 | 1386.00 | 1068.54 | 1843.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.26 |
June | 3114.95 | 29-JUN-08:51 | 288.00 | 376.12 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.07 |
July | 3603.63 | 11-JUL-08:32 | 216.00 | 282.09 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.10 |
August | 2916.59 | 10-AUG-21:51 | 1800.00 | 715.93 | 921.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.03 |
September | 2592.32 | 07-SEP-18:01 | 970.20 | 665.70 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.19 |
October | 2449.01 | 04-OCT-08:62 | 216.00 | 282.09 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.14 |
November | 827.04 | 04-NOV-08:04 | 378.00 | 418.87 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.85 |
December | 901.86 | 24-DEC-19:04 | 819.00 | 747.98 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 827.04 | 216.00 | 282.09 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.07 | |
Maximum of Months | 3603.63 | 1800.00 | 1068.54 | 1843.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 377.10 | 23-JAN-22:10 | 2263.36 | 696.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.25 |
February | 818.16 | 09-FEB-22:10 | 2263.36 | 696.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.54 |
March | 1424.17 | 22-MAR-18:07 | 10562.33 | 5568.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.43 |
April | 1967.89 | 22-APR-10:33 | 2263.36 | 870.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.54 |
May | 2191.28 | 14-MAY-10:33 | 2263.36 | 1044.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.74 |
June | 2300.42 | 13-JUN-10:33 | 1508.90 | 870.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.09 |
July | 2333.29 | 23-JUL-10:33 | 2263.36 | 1044.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.42 |
August | 2194.78 | 01-AUG-10:33 | 1508.90 | 870.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.12 |
September | 1917.46 | 10-SEP-10:33 | 2263.36 | 1044.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.03 |
October | 1551.08 | 03-OCT-10:33 | 1508.90 | 870.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.76 |
November | 514.65 | 01-NOV-21:10 | 2263.36 | 696.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.16 |
December | 380.26 | 24-DEC-22:00 | 2011.87 | 696.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 377.10 | 1508.90 | 696.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.42 | |
Maximum of Months | 2333.29 | 10562.33 | 5568.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 374.55 | 22-JAN-09:04 | 378.00 | 418.92 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.89 |
February | 831.40 | 09-FEB-19:04 | 970.20 | 665.78 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.22 |
March | 3100.61 | 27-MAR-18:01 | 970.20 | 665.78 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.78 |
April | 3311.69 | 21-APR-18:01 | 970.20 | 665.78 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.99 |
May | 3430.62 | 31-MAY-18:02 | 831.60 | 570.67 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 |
June | 3549.12 | 22-JUN-18:02 | 831.60 | 570.67 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 | 0.00 |
July | 3402.66 | 11-JUL-18:02 | 831.60 | 570.67 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 0.00 |
August | 3565.09 | 10-AUG-18:02 | 831.60 | 570.67 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
September | 3217.53 | 02-SEP-18:02 | 702.00 | 641.20 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.51 |
October | 2866.30 | 13-OCT-15:02 | 583.20 | 179.54 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.76 |
November | 374.18 | 08-NOV-16:04 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.19 |
December | 630.66 | 24-DEC-09:04 | 378.00 | 418.92 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 374.18 | 378.00 | 179.54 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3565.09 | 970.20 | 665.78 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 72.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 449.84 | 22-JAN-09:04 | 378.00 | 418.87 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.89 |
February | 734.38 | 09-FEB-16:04 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.69 |
March | 1455.39 | 28-MAR-15:03 | 583.20 | 179.51 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.16 |
April | 2949.83 | 21-APR-18:01 | 970.20 | 665.70 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.96 |
May | 3757.76 | 09-MAY-19:42 | 831.60 | 641.12 | 1042.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.54 |
June | 3593.42 | 28-JUN-21:32 | 1080.00 | 429.56 | 553.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.63 |
July | 3552.52 | 06-JUL-17:32 | 583.20 | 429.56 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 |
August | 3180.35 | 02-AUG-21:51 | 1800.00 | 715.93 | 921.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.13 |
September | 3048.75 | 02-SEP-19:41 | 936.00 | 854.83 | 1390.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.94 |
October | 1428.78 | 05-OCT-15:03 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.25 |
November | 398.68 | 04-NOV-08:04 | 378.00 | 418.87 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.98 |
December | 600.45 | 24-DEC-09:04 | 378.00 | 418.87 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 398.68 | 378.00 | 179.51 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | |
Maximum of Months | 3757.76 | 1800.00 | 854.83 | 1390.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 598.75 | 22-JAN-19:04 | 819.00 | 470.26 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.99 |
February | 2102.16 | 15-FEB-16:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.63 |
March | 2187.98 | 15-MAR-15:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.48 |
April | 2238.11 | 20-APR-15:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.12 |
May | 2286.80 | 10-MAY-15:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.37 |
June | 2303.50 | 22-JUN-18:02 | 831.60 | 358.74 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 0.00 |
July | 2320.49 | 23-JUL-15:02 | 324.00 | 133.02 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 0.00 |
August | 2306.41 | 10-AUG-18:02 | 831.60 | 358.74 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 | 0.00 |
September | 2117.98 | 07-SEP-18:01 | 970.20 | 418.53 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.42 |
October | 2146.98 | 13-OCT-15:02 | 583.20 | 112.86 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.41 |
November | 1996.45 | 08-NOV-16:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.59 |
December | 590.80 | 24-DEC-19:04 | 819.00 | 470.26 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 590.80 | 324.00 | 112.86 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2320.49 | 970.20 | 470.26 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 37.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16995.61 | 11-JAN-22:40 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.96 |
February | 16363.52 | 28-FEB-22:10 | 80966.30 | 4973.62 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.17 |
March | 17388.83 | 22-MAR-22:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.49 |
April | 19132.88 | 21-APR-21:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.08 |
May | 20953.76 | 31-MAY-21:52 | 242898.91 | 14777.55 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.87 |
June | 22498.82 | 21-JUN-21:03 | 161932.61 | 5968.35 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 |
July | 22776.91 | 11-JUL-21:10 | 26988.77 | 994.72 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.30 |
August | 21547.80 | 02-AUG-21:52 | 269887.68 | 16578.74 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.63 |
September | 19207.74 | 01-SEP-22:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.29 |
October | 17931.77 | 06-OCT-22:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.59 |
November | 16030.67 | 28-NOV-23:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.81 |
December | 16708.36 | 14-DEC-24:00 | 26988.77 | 828.94 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16030.67 | 26988.77 | 828.94 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 22776.91 | 269887.68 | 16578.74 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18391.62 | 11-JAN-22:30 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.69 |
February | 18109.23 | 08-FEB-23:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.94 |
March | 19404.36 | 22-MAR-22:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.50 |
April | 20815.18 | 21-APR-21:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.08 |
May | 22387.14 | 31-MAY-21:52 | 242898.91 | 14777.55 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.87 |
June | 23757.13 | 21-JUN-21:03 | 161932.61 | 5968.35 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 |
July | 24083.28 | 11-JUL-21:10 | 26988.77 | 994.72 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.30 |
August | 22846.66 | 02-AUG-21:20 | 26988.77 | 1642.02 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.25 |
September | 20940.96 | 01-SEP-22:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.29 |
October | 19974.74 | 06-OCT-22:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.59 |
November | 17036.98 | 28-NOV-23:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.58 |
December | 17746.52 | 14-DEC-24:00 | 26988.77 | 828.94 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17036.98 | 26988.77 | 828.94 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 24083.28 | 242898.91 | 14777.55 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23847.08 | 22-JAN-11:50 | 1601.14 | 654.50 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 122.19 |
February | 25243.48 | 09-FEB-11:50 | 1067.42 | 545.42 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 105.33 |
March | 27432.78 | 22-MAR-10:33 | 1601.14 | 818.12 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 85.40 |
April | 29469.86 | 22-APR-10:50 | 800.57 | 272.71 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 44.30 |
May | 30028.59 | 12-MAY-10:33 | 1601.14 | 818.12 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 24.65 |
June | 30522.26 | 29-JUN-10:45 | 1067.42 | 545.42 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 7.62 |
July | 31130.64 | 22-JUL-10:40 | 2401.70 | 818.12 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 2.09 |
August | 30286.61 | 10-AUG-10:33 | 1601.14 | 818.12 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 19.63 |
September | 29051.07 | 10-SEP-10:33 | 2401.70 | 981.75 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 38.19 |
October | 27381.66 | 03-OCT-10:33 | 1601.14 | 818.12 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 72.85 |
November | 23653.41 | 02-NOV-18:03 | 13075.94 | 6108.66 | 102231.89 | 104966.55 | 0.00 | 0.00 | 0.00 | 0.00 | 133.34 |
December | 23917.98 | 24-DEC-11:50 | 800.57 | 327.25 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 23653.41 | 800.57 | 272.71 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 2.09 | |
Maximum of Months | 31130.64 | 13075.94 | 6108.66 | 102231.89 | 104966.55 | 0.00 | 0.00 | 0.00 | 0.00 | 133.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 263.82 | 21-JAN-21:50 | 1863.12 | 859.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.21 |
February | 2104.21 | 09-FEB-13:30 | 532.32 | 306.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.17 |
March | 3159.56 | 22-MAR-17:13 | 3992.40 | 2209.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.79 |
April | 4247.17 | 22-APR-10:33 | 2395.44 | 920.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.06 |
May | 4747.29 | 14-MAY-10:33 | 2395.44 | 1104.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 |
June | 5234.84 | 21-JUN-15:30 | 1330.80 | 306.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.26 | 0.00 |
July | 5996.52 | 23-JUL-13:50 | 532.32 | 245.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.19 | 0.00 |
August | 4836.56 | 02-AUG-17:15 | 2661.60 | 1473.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 |
September | 4135.31 | 10-SEP-10:33 | 2395.44 | 1104.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.05 |
October | 3380.26 | 03-OCT-10:33 | 1596.96 | 920.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.99 |
November | 168.34 | 01-NOV-21:20 | 2395.44 | 736.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.35 |
December | 345.50 | 24-DEC-22:50 | 2129.28 | 613.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 168.34 | 532.32 | 245.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5996.52 | 3992.40 | 2209.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.26 | 117.35 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.352094E+12 | 211533.29 | 26-JAN-20:10 | 0.137033E+13 | 1339773.95 | 12-JAN-19:19 |
February | 0.312925E+12 | 211356.29 | 22-FEB-20:19 | 0.113873E+13 | 1181842.67 | 27-FEB-09:09 |
March | 0.347039E+12 | 222240.04 | 22-MAR-19:10 | 0.890886E+12 | 1086225.60 | 01-MAR-00:20 |
April | 0.390552E+12 | 260824.27 | 20-APR-20:40 | 0.419271E+12 | 402539.57 | 18-APR-17:00 |
May | 0.419378E+12 | 277996.98 | 30-MAY-19:10 | 0.351312E+12 | 360679.01 | 27-MAY-17:00 |
June | 0.439821E+12 | 341313.13 | 20-JUN-19:19 | 0.309050E+12 | 296298.18 | 24-JUN-20:00 |
July | 0.464499E+12 | 338232.73 | 11-JUL-19:30 | 0.311426E+12 | 284690.51 | 04-JUL-21:00 |
August | 0.437738E+12 | 331789.31 | 11-AUG-19:19 | 0.339784E+12 | 337645.13 | 30-AUG-19:40 |
September | 0.385551E+12 | 261069.47 | 18-SEP-19:10 | 0.354309E+12 | 366705.82 | 05-SEP-17:00 |
October | 0.389417E+12 | 259255.53 | 03-OCT-19:40 | 0.543013E+12 | 494473.99 | 30-OCT-18:10 |
November | 0.338336E+12 | 211440.69 | 16-NOV-20:19 | 0.127708E+13 | 1189471.76 | 30-NOV-17:00 |
December | 0.354182E+12 | 212430.65 | 06-DEC-20:40 | 0.151233E+13 | 1250979.35 | 15-DEC-17:10 |
Annual Sum or Average | 0.463153E+13 | 0.881752E+13 | ||||
Minimum of Months | 0.312925E+12 | 211356.29 | 0.309050E+12 | 284690.51 | ||
Maximum of Months | 0.464499E+12 | 341313.13 | 0.151233E+13 | 1339773.95 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.476883E+11 | 0.238751E+11 | 0.146779E+12 | 0.544798E+11 | 0.411857E+11 | 0.942819E+09 | 0.00 | 29344882.70 | 0.00 | 0.00 | 0.257713E+11 | 0.770634E+10 | 0.00 |
February | 0.425471E+11 | 0.178631E+11 | 0.132565E+12 | 0.492074E+11 | 0.357527E+11 | 0.120189E+10 | 0.00 | 0.254488E+09 | 0.00 | 0.00 | 0.232773E+11 | 0.696354E+10 | 0.00 |
March | 0.464000E+11 | 0.155861E+11 | 0.146789E+12 | 0.544811E+11 | 0.432693E+11 | 0.333037E+10 | 0.00 | 0.333107E+10 | 0.00 | 0.00 | 0.257713E+11 | 0.441749E+10 | 0.00 |
April | 0.437536E+11 | 0.109722E+11 | 0.142011E+12 | 0.527208E+11 | 0.430900E+11 | 0.918330E+10 | 0.00 | 0.215652E+11 | 0.00 | 0.00 | 0.206562E+11 | 0.430423E+11 | 0.00 |
May | 0.447206E+11 | 0.717053E+10 | 0.146789E+12 | 0.544790E+11 | 0.483561E+11 | 0.139332E+11 | 0.00 | 0.487784E+11 | 0.00 | 0.00 | 0.104637E+11 | 0.409864E+11 | 0.00 |
June | 0.428909E+11 | 0.399472E+10 | 0.142058E+12 | 0.527221E+11 | 0.502424E+11 | 0.150434E+11 | 0.00 | 0.876661E+11 | 0.00 | 0.00 | 0.358614E+10 | 0.380009E+11 | 0.00 |
July | 0.445054E+11 | 0.555266E+10 | 0.146742E+12 | 0.544770E+11 | 0.511049E+11 | 0.157338E+11 | 0.00 | 0.990996E+11 | 0.00 | 0.00 | 0.460646E+10 | 0.389412E+11 | 0.00 |
August | 0.452030E+11 | 0.958067E+10 | 0.146800E+12 | 0.544803E+11 | 0.489453E+11 | 0.146924E+11 | 0.00 | 0.699217E+11 | 0.00 | 0.00 | 0.451427E+10 | 0.398606E+11 | 0.00 |
September | 0.446546E+11 | 0.133224E+11 | 0.142022E+12 | 0.527215E+11 | 0.426805E+11 | 0.100446E+11 | 0.00 | 0.187577E+11 | 0.00 | 0.00 | 0.165492E+11 | 0.412041E+11 | 0.00 |
October | 0.469032E+11 | 0.179696E+11 | 0.146768E+12 | 0.544794E+11 | 0.418370E+11 | 0.354997E+10 | 0.00 | 0.353312E+10 | 0.00 | 0.00 | 0.240966E+11 | 0.465941E+11 | 0.00 |
November | 0.459732E+11 | 0.215515E+11 | 0.142074E+12 | 0.527228E+11 | 0.391989E+11 | 0.857320E+09 | 0.00 | 46433127.00 | 0.00 | 0.00 | 0.249400E+11 | 0.745066E+10 | 0.00 |
December | 0.478577E+11 | 0.255662E+11 | 0.146742E+12 | 0.544790E+11 | 0.412917E+11 | 0.110422E+10 | 0.00 | 18810348.00 | 0.00 | 0.00 | 0.257713E+11 | 0.771442E+10 | 0.00 |
Annual Sum or Average | 0.543097E+12 | 0.173005E+12 | 0.172814E+13 | 0.641450E+12 | 0.526955E+12 | 0.896173E+11 | 0.00 | 0.353002E+12 | 0.00 | 0.00 | 0.210004E+12 | 0.322882E+12 | 0.00 |
Minimum of Months | 0.425471E+11 | 0.399472E+10 | 0.132565E+12 | 0.492074E+11 | 0.357527E+11 | 0.857320E+09 | 0.00 | 18810348.00 | 0.00 | 0.00 | 0.358614E+10 | 0.441749E+10 | 0.00 |
Maximum of Months | 0.478577E+11 | 0.255662E+11 | 0.146800E+12 | 0.544811E+11 | 0.511049E+11 | 0.157338E+11 | 0.00 | 0.990996E+11 | 0.00 | 0.00 | 0.257713E+11 | 0.465941E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.964005E+12 | 0.00 | 0.254407E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.771380E+12 | 0.00 | 0.230143E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.481318E+12 | 0.00 | 0.257544E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.134889E+12 | 0.00 | 0.137426E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.662549E+11 | 0.00 | 0.133078E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.481338E+11 | 0.00 | 0.113802E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.492185E+11 | 0.00 | 0.110387E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.756532E+11 | 0.00 | 0.112092E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.860489E+11 | 0.00 | 0.121289E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.249838E+12 | 0.00 | 0.141271E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.889984E+12 | 0.00 | 0.240008E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.110752E+13 | 0.00 | 0.252988E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.492424E+13 | 0.00 | 0.210444E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.481338E+11 | 0.00 | 0.110387E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.110752E+13 | 0.00 | 0.257544E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 45424.10 | 02-JAN-20:10 | 11096.45 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 39153.57 | 02-JAN-07:19 | 21853.94 | 30-JAN-19:10 | 2002.96 | 12-JAN-09:20 | 0.00 | 01-JAN-00:10 |
February | 45424.10 | 01-FEB-20:10 | 11096.45 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 39153.57 | 01-FEB-07:19 | 21621.64 | 01-FEB-19:10 | 3943.62 | 15-FEB-16:10 | 0.00 | 01-FEB-00:10 |
March | 45424.10 | 01-MAR-20:10 | 11096.45 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 39153.57 | 01-MAR-07:19 | 22576.02 | 22-MAR-20:19 | 5487.99 | 29-MAR-15:09 | 0.00 | 01-MAR-00:10 |
April | 45424.10 | 03-APR-19:40 | 11096.45 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 39153.57 | 03-APR-06:19 | 28736.51 | 21-APR-21:10 | 6527.89 | 22-APR-16:10 | 0.00 | 01-APR-00:10 |
May | 44407.70 | 02-MAY-19:00 | 11096.45 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 39151.64 | 16-MAY-06:19 | 31741.99 | 10-MAY-21:40 | 6918.30 | 31-MAY-15:09 | 0.00 | 01-MAY-00:10 |
June | 43938.34 | 02-JUN-19:00 | 11096.45 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 39151.62 | 27-JUN-06:19 | 32603.36 | 21-JUN-20:00 | 7308.15 | 21-JUN-19:00 | 0.00 | 01-JUN-00:10 |
July | 43629.83 | 26-JUL-19:00 | 11096.45 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 39151.89 | 25-JUL-06:19 | 33044.04 | 12-JUL-21:00 | 7361.44 | 20-JUL-18:49 | 0.00 | 01-JUL-00:10 |
August | 45424.10 | 29-AUG-19:30 | 11096.45 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 39151.88 | 29-AUG-06:19 | 32347.66 | 10-AUG-21:00 | 7282.36 | 11-AUG-15:20 | 0.00 | 01-AUG-00:10 |
September | 45424.10 | 01-SEP-19:30 | 11096.45 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 39153.57 | 13-SEP-06:19 | 27658.35 | 08-SEP-21:10 | 6500.97 | 02-SEP-15:09 | 0.00 | 01-SEP-00:10 |
October | 45424.10 | 02-OCT-19:10 | 11096.45 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 39153.57 | 02-OCT-06:19 | 24358.78 | 03-OCT-21:10 | 5639.56 | 03-OCT-15:09 | 0.00 | 01-OCT-00:10 |
November | 45424.10 | 01-NOV-19:10 | 11096.45 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 39153.57 | 01-NOV-06:19 | 21798.44 | 15-NOV-19:10 | 3636.67 | 08-NOV-16:10 | 0.00 | 01-NOV-00:10 |
December | 45424.10 | 01-DEC-20:10 | 11096.45 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 39153.57 | 01-DEC-07:19 | 21900.62 | 06-DEC-19:10 | 1866.76 | 15-DEC-10:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 43629.83 | 11096.45 | 88863.15 | 39151.62 | 21621.64 | 1866.76 | 0.00 | |||||||
Maximum of Months | 45424.10 | 11096.45 | 88863.15 | 39153.57 | 33044.04 | 7361.44 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 1847.21 | 22-JAN-19:10 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 4739.88 | 12-JAN-19:00 | 0.00 |
February | 4344.38 | 15-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:20 | 4739.97 | 27-FEB-07:30 | 0.00 |
March | 21813.24 | 29-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:10 | 31259.53 | 31-MAR-23:10 | 0.00 |
April | 44427.54 | 22-APR-15:09 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 34464.21 | 26-APR-18:10 | 0.00 |
May | 73981.27 | 31-MAY-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAY-00:10 | 35580.17 | 31-MAY-18:00 | 0.00 |
June | 101658.74 | 20-JUN-18:19 | 0.00 | 0.00 | 9938.94 | 01-JUN-02:49 | 36280.77 | 28-JUN-18:19 | 0.00 |
July | 115436.70 | 29-JUL-15:20 | 0.00 | 0.00 | 9938.94 | 05-JUL-01:39 | 37031.83 | 28-JUL-18:19 | 0.00 |
August | 95381.85 | 11-AUG-18:10 | 0.00 | 0.00 | 9938.94 | 02-AUG-16:40 | 37460.01 | 30-AUG-18:10 | 0.00 |
September | 47586.18 | 02-SEP-15:09 | 0.00 | 0.00 | 9938.94 | 01-SEP-00:20 | 37466.90 | 05-SEP-18:49 | 0.00 |
October | 24844.42 | 03-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 01-OCT-00:10 | 36467.29 | 02-OCT-18:00 | 0.00 |
November | 1903.76 | 08-NOV-16:10 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 4739.75 | 28-NOV-07:10 | 0.00 |
December | 2282.25 | 24-DEC-19:10 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 4740.06 | 15-DEC-07:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1847.21 | 0.00 | 0.00 | 9938.94 | 4739.75 | 0.00 | |||
Maximum of Months | 115436.70 | 0.00 | 0.00 | 9938.94 | 37466.90 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 211533.29 | 26-JAN-20:10 | 45424.10 | 87982.85 | 11096.45 | 31569.36 | 19681.97 | 96.99 | 0.00 | 0.00 | 0.00 |
February | 211356.29 | 22-FEB-20:19 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 19139.72 | 806.88 | 0.00 | 0.00 | 0.00 |
March | 222240.04 | 22-MAR-19:10 | 45424.10 | 87982.85 | 11096.45 | 31569.27 | 21988.25 | 4464.85 | 0.00 | 5520.85 | 0.00 |
April | 260824.27 | 20-APR-20:40 | 40391.24 | 88373.09 | 11096.45 | 24002.42 | 25880.08 | 5858.85 | 0.00 | 20118.77 | 0.00 |
May | 277996.98 | 30-MAY-19:10 | 41184.17 | 87982.85 | 0.00 | 31566.16 | 24727.11 | 6191.25 | 0.00 | 50353.70 | 0.00 |
June | 341313.13 | 20-JUN-19:19 | 41114.58 | 87982.85 | 0.00 | 31569.86 | 29846.68 | 7219.52 | 0.00 | 96934.45 | 0.00 |
July | 338232.73 | 11-JUL-19:30 | 41231.65 | 87982.85 | 0.00 | 31570.02 | 30957.40 | 7179.68 | 0.00 | 92395.45 | 0.00 |
August | 331789.31 | 11-AUG-19:19 | 41914.73 | 87982.85 | 0.00 | 31570.37 | 28567.87 | 7162.39 | 0.00 | 86975.26 | 0.00 |
September | 261069.47 | 18-SEP-19:10 | 45424.10 | 87982.85 | 11096.45 | 31569.36 | 24487.22 | 5563.97 | 0.00 | 15546.64 | 0.00 |
October | 259255.53 | 03-OCT-19:40 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 22395.86 | 4833.52 | 0.00 | 8898.48 | 0.00 |
November | 211440.69 | 16-NOV-20:19 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 19653.59 | 99.43 | 0.00 | 0.00 | 0.00 |
December | 212430.65 | 06-DEC-20:40 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 19943.32 | 1073.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 211356.29 | 40391.24 | 87982.85 | 0.00 | 24002.42 | 19139.72 | 96.99 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 341313.13 | 45424.10 | 88373.09 | 11096.45 | 31573.56 | 30957.40 | 7219.52 | 0.00 | 96934.45 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 1123356.46 | 12-JAN-09:09 | 0.00 | 200852.03 | 18-JAN-22:30 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 1038561.70 | 27-FEB-05:19 | 0.00 | 200348.60 | 21-FEB-22:40 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 904264.70 | 01-MAR-04:00 | 0.00 | 203106.66 | 21-MAR-21:30 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 280515.16 | 03-APR-08:09 | 0.00 | 147434.04 | 13-APR-18:10 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 163874.65 | 26-MAY-10:00 | 0.00 | 137112.53 | 09-MAY-20:49 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 145943.93 | 01-JUN-06:19 | 0.00 | 115804.54 | 01-JUN-17:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 163251.98 | 05-JUL-06:00 | 0.00 | 105673.14 | 01-JUL-17:10 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 162338.81 | 22-AUG-07:30 | 0.00 | 106749.99 | 01-AUG-16:00 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 176111.95 | 21-SEP-09:09 | 0.00 | 126777.29 | 26-SEP-20:00 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 308500.56 | 27-OCT-08:09 | 0.00 | 145498.58 | 20-OCT-17:00 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 992464.22 | 29-NOV-09:09 | 0.00 | 197783.63 | 30-NOV-22:30 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 1070016.27 | 15-DEC-09:09 | 0.00 | 200601.75 | 08-DEC-22:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 145943.93 | 0.00 | 105673.14 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 1123356.46 | 0.00 | 203106.66 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.44 | 0.50 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
February | 0.33 | 20.44 | 0.33 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 20.44 | 0.83 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.44 | 0.50 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 51.00 | 18.91 | 51.00 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
February | 6.50 | 19.85 | 6.50 | 19.85 | 0.00 | 19.85 | 0.00 | 19.85 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14.67 | 19.79 | 14.67 | 19.79 | 0.00 | 19.79 | 0.00 | 19.79 |
Annual Sum or Average | 72.17 | 19.17 | 72.17 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 51.00 | 19.85 | 51.00 | 19.85 | 0.00 | 19.85 | 0.00 | 19.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.00 | 19.77 | 12.00 | 19.77 | 0.00 | 19.77 | 0.00 | 19.77 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 12.00 | 19.77 | 12.00 | 19.77 | 0.00 | 19.77 | 0.00 | 19.77 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.00 | 19.77 | 12.00 | 19.77 | 0.00 | 19.77 | 0.00 | 19.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.83 | 16.41 | 4.83 | 16.41 | 0.00 | 16.41 | 0.00 | 16.41 |
February | 0.17 | 16.80 | 0.17 | 16.80 | 0.00 | 16.80 | 0.00 | 16.80 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.51 | 0.17 | 19.51 | 0.00 | 19.51 | 0.00 | 19.51 |
Annual Sum or Average | 5.17 | 16.52 | 5.17 | 16.52 | 0.00 | 16.52 | 0.00 | 16.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.83 | 19.51 | 4.83 | 19.51 | 0.00 | 19.51 | 0.00 | 19.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 36.33 | 19.06 | 36.33 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
February | 2.67 | 20.10 | 2.67 | 20.10 | 0.00 | 20.10 | 0.00 | 20.10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 20.39 | 0.50 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
December | 9.00 | 19.36 | 9.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
Annual Sum or Average | 48.50 | 19.18 | 48.50 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 36.33 | 20.39 | 36.33 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.17 | 19.67 | 18.17 | 19.67 | 0.00 | 19.67 | 0.00 | 19.67 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5.50 | 20.18 | 5.50 | 20.18 | 0.00 | 20.18 | 0.00 | 20.18 |
Annual Sum or Average | 23.67 | 19.79 | 23.67 | 19.79 | 0.00 | 19.79 | 0.00 | 19.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 18.17 | 20.18 | 18.17 | 20.18 | 0.00 | 20.18 | 0.00 | 20.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.77 | 0.50 | 21.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.77 | 1.33 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.89 | 1.00 | 21.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.17 | 21.80 | 3.17 | 21.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.89 | 1.33 | 21.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.97 | 1.67 | 21.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 22.05 | 4.83 | 22.05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.94 | 3.83 | 21.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.90 | 0.83 | 21.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.17 | 21.99 | 11.17 | 21.99 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 22.05 | 4.83 | 22.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 20.44 | 2.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
February | 0.33 | 20.49 | 0.33 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.76 | 4.00 | 21.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 21.90 | 14.83 | 21.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 21.89 | 15.50 | 21.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 21.81 | 6.67 | 21.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 20.44 | 0.67 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
December | 1.83 | 20.48 | 1.83 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Annual Sum or Average | 4.83 | 20.46 | 4.83 | 20.46 | 41.00 | 21.60 | 41.00 | 21.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 20.49 | 2.00 | 20.49 | 15.50 | 21.90 | 15.50 | 21.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.91 | 0.17 | 21.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 21.91 | 5.00 | 21.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.90 | 2.67 | 21.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.89 | 2.50 | 21.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.83 | 1.67 | 21.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.00 | 21.89 | 12.00 | 21.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 21.91 | 5.00 | 21.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.89 | 0.17 | 21.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 21.96 | 7.17 | 21.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 22.06 | 10.83 | 22.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 22.31 | 11.00 | 22.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.87 | 2.83 | 21.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 32.00 | 22.11 | 32.00 | 22.11 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 22.31 | 11.00 | 22.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.50 | 20.41 | 3.50 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.50 | 20.41 | 3.50 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.50 | 20.41 | 3.50 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.81 | 0.50 | 21.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.81 | 1.50 | 21.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.71 | 0.67 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.83 | 1.00 | 21.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.67 | 21.79 | 3.67 | 21.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.83 | 1.50 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 22.09 | 2.17 | 22.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 22.21 | 6.00 | 22.21 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 22.06 | 4.33 | 22.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.98 | 1.33 | 21.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 13.83 | 22.12 | 13.83 | 22.12 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 22.21 | 6.00 | 22.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.90 | 1.00 | 21.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.81 | 0.83 | 21.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.72 | 0.67 | 21.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.70 | 0.50 | 21.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.85 | 1.17 | 21.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.82 | 1.33 | 21.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.50 | 21.82 | 5.50 | 21.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.90 | 1.33 | 21.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 20.20 | 1.00 | 20.20 | 0.00 | 20.20 | 0.00 | 20.20 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.00 | 20.20 | 1.00 | 20.20 | 0.00 | 20.20 | 0.00 | 20.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.20 | 1.00 | 20.20 | 0.00 | 20.20 | 0.00 | 20.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.36 | 0.67 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 20.36 | 0.67 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.36 | 0.67 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.32 | 0.50 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 18.32 | 0.50 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 18.32 | 0.50 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 20.40 | 1.33 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.33 | 20.40 | 1.33 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.40 | 1.33 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.94 | 89.50 | 21.84 | 89.50 | 21.76 |
February | 672.00 | 21.36 | 233.00 | 21.27 | 233.00 | 21.22 |
March | 744.00 | 21.35 | 208.00 | 21.28 | 208.00 | 21.23 |
April | 720.00 | 21.55 | 26.17 | 21.53 | 26.17 | 21.52 |
May | 744.00 | 21.65 | 0.00 | 21.65 | 0.00 | 21.65 |
June | 720.00 | 21.96 | 0.00 | 21.96 | 0.00 | 21.96 |
July | 744.00 | 22.63 | 0.00 | 22.63 | 0.00 | 22.63 |
August | 680.17 | 23.35 | 0.67 | 23.35 | 0.00 | 23.35 |
September | 669.67 | 23.68 | 0.00 | 23.68 | 0.00 | 23.68 |
October | 742.67 | 23.72 | 0.00 | 23.72 | 0.00 | 23.72 |
November | 720.00 | 23.24 | 17.50 | 23.19 | 17.50 | 23.14 |
December | 744.00 | 22.21 | 38.17 | 22.16 | 38.17 | 22.10 |
Annual Sum or Average | 8644.50 | 22.38 | 613.00 | 22.29 | 612.33 | 22.21 |
Minimum of Months | 669.67 | 21.35 | 0.00 | 21.27 | 0.00 | 21.22 |
Maximum of Months | 744.00 | 23.72 | 233.00 | 23.72 | 233.00 | 23.72 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.86 | 740.17 | 20.86 | 740.17 | 20.86 |
February | 672.00 | 21.01 | 612.33 | 21.00 | 612.33 | 21.00 |
March | 720.67 | 21.16 | 493.17 | 21.09 | 493.17 | 21.07 |
April | 629.83 | 21.31 | 138.17 | 21.39 | 103.17 | 21.35 |
May | 657.50 | 21.37 | 40.33 | 21.52 | 0.00 | 21.52 |
June | 609.33 | 21.54 | 56.83 | 21.73 | 0.00 | 21.73 |
July | 610.17 | 21.45 | 87.50 | 21.73 | 0.00 | 21.73 |
August | 633.17 | 21.37 | 77.00 | 21.64 | 0.00 | 21.64 |
September | 677.17 | 21.15 | 33.00 | 21.23 | 11.50 | 21.23 |
October | 733.17 | 21.05 | 375.00 | 21.04 | 372.33 | 21.03 |
November | 720.00 | 21.00 | 708.50 | 21.00 | 708.50 | 21.00 |
December | 744.00 | 20.98 | 744.00 | 20.98 | 744.00 | 20.98 |
Annual Sum or Average | 8151.00 | 21.17 | 4106.00 | 21.18 | 3785.17 | 21.13 |
Minimum of Months | 609.33 | 20.86 | 33.00 | 20.86 | 0.00 | 20.86 |
Maximum of Months | 744.00 | 21.54 | 744.00 | 21.73 | 744.00 | 21.73 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.08 | 454.50 | 21.04 | 454.50 | 21.01 |
February | 672.00 | 21.22 | 305.50 | 21.16 | 305.50 | 21.12 |
March | 744.00 | 21.57 | 116.33 | 21.49 | 116.33 | 21.44 |
April | 720.00 | 22.53 | 0.00 | 22.53 | 0.00 | 22.53 |
May | 739.17 | 22.94 | 0.00 | 22.94 | 0.00 | 22.94 |
June | 566.33 | 23.09 | 16.00 | 23.11 | 0.00 | 23.11 |
July | 494.33 | 22.98 | 79.83 | 23.11 | 0.00 | 23.11 |
August | 589.67 | 22.99 | 28.17 | 23.03 | 0.00 | 23.03 |
September | 718.67 | 22.55 | 0.00 | 22.55 | 0.00 | 22.55 |
October | 744.00 | 21.81 | 31.00 | 21.78 | 31.00 | 21.75 |
November | 720.00 | 21.14 | 412.67 | 21.09 | 412.67 | 21.07 |
December | 744.00 | 21.06 | 573.67 | 21.03 | 573.67 | 21.03 |
Annual Sum or Average | 8196.17 | 22.02 | 2017.67 | 21.85 | 1893.67 | 21.72 |
Minimum of Months | 494.33 | 21.06 | 0.00 | 21.03 | 0.00 | 21.01 |
Maximum of Months | 744.00 | 23.09 | 573.67 | 23.11 | 573.67 | 23.11 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 721.17 | 21.00 | 721.17 | 21.00 |
February | 672.00 | 21.00 | 589.00 | 21.00 | 589.00 | 21.00 |
March | 744.00 | 21.04 | 536.83 | 21.02 | 536.83 | 21.02 |
April | 720.00 | 21.62 | 126.17 | 21.53 | 126.17 | 21.46 |
May | 744.00 | 22.56 | 0.00 | 22.56 | 0.00 | 22.56 |
June | 709.50 | 23.20 | 0.00 | 23.20 | 0.00 | 23.20 |
July | 671.17 | 23.23 | 0.00 | 23.23 | 0.00 | 23.23 |
August | 727.67 | 23.05 | 0.00 | 23.05 | 0.00 | 23.05 |
September | 720.00 | 22.12 | 0.00 | 22.12 | 0.00 | 22.12 |
October | 744.00 | 21.25 | 224.67 | 21.19 | 224.67 | 21.15 |
November | 720.00 | 21.00 | 717.50 | 21.00 | 717.50 | 21.00 |
December | 744.00 | 21.00 | 724.67 | 21.00 | 724.67 | 21.00 |
Annual Sum or Average | 8660.33 | 21.83 | 3640.00 | 21.58 | 3640.00 | 21.45 |
Minimum of Months | 671.17 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 23.23 | 724.67 | 23.23 | 724.67 | 23.23 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 744.00 | 21.00 | 744.00 | 21.00 |
February | 672.00 | 21.00 | 641.00 | 21.00 | 641.00 | 21.00 |
March | 744.00 | 21.00 | 619.17 | 21.00 | 619.17 | 21.00 |
April | 720.00 | 21.38 | 184.83 | 21.30 | 184.83 | 21.25 |
May | 744.00 | 22.30 | 0.00 | 22.30 | 0.00 | 22.30 |
June | 718.33 | 23.01 | 0.00 | 23.01 | 0.00 | 23.01 |
July | 738.00 | 23.08 | 0.00 | 23.08 | 0.00 | 23.08 |
August | 744.00 | 22.81 | 0.00 | 22.81 | 0.00 | 22.81 |
September | 720.00 | 21.77 | 0.00 | 21.77 | 0.00 | 21.77 |
October | 744.00 | 21.08 | 293.67 | 21.06 | 293.67 | 21.05 |
November | 720.00 | 21.00 | 720.00 | 21.00 | 720.00 | 21.00 |
December | 744.00 | 21.00 | 744.00 | 21.00 | 744.00 | 21.00 |
Annual Sum or Average | 8752.33 | 21.71 | 3946.67 | 21.49 | 3946.67 | 21.37 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 23.08 | 744.00 | 23.08 | 744.00 | 23.08 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 396.50 | 21.77 | 302.50 | 22.46 | 125.83 | 22.52 |
February | 338.50 | 22.04 | 273.33 | 22.78 | 106.00 | 22.92 |
March | 278.67 | 22.52 | 363.50 | 23.20 | 128.50 | 23.34 |
April | 232.17 | 22.93 | 461.17 | 23.36 | 144.17 | 23.47 |
May | 259.00 | 23.28 | 586.83 | 23.35 | 193.33 | 23.47 |
June | 295.67 | 23.74 | 633.33 | 23.40 | 269.17 | 23.54 |
July | 305.00 | 23.87 | 675.50 | 23.40 | 292.00 | 23.54 |
August | 303.83 | 23.72 | 653.00 | 23.40 | 274.17 | 23.53 |
September | 263.67 | 23.31 | 597.00 | 23.33 | 201.17 | 23.46 |
October | 242.67 | 22.84 | 462.83 | 23.33 | 142.17 | 23.44 |
November | 350.83 | 22.09 | 283.67 | 22.87 | 106.17 | 23.03 |
December | 446.17 | 21.98 | 285.33 | 22.68 | 113.33 | 22.84 |
Annual Sum or Average | 3712.67 | 22.75 | 5578.00 | 23.16 | 2096.00 | 23.30 |
Minimum of Months | 232.17 | 21.77 | 273.33 | 22.46 | 106.00 | 22.52 |
Maximum of Months | 446.17 | 23.87 | 675.50 | 23.40 | 292.00 | 23.54 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.91 | 679.50 | 20.90 | 679.50 | 20.90 |
February | 672.00 | 21.07 | 429.83 | 21.04 | 429.83 | 21.03 |
March | 695.33 | 21.38 | 153.83 | 21.36 | 139.67 | 21.31 |
April | 593.83 | 22.03 | 81.33 | 22.23 | 7.50 | 22.22 |
May | 597.50 | 22.29 | 68.17 | 22.45 | 0.00 | 22.45 |
June | 404.00 | 22.33 | 141.67 | 22.65 | 0.00 | 22.65 |
July | 351.33 | 22.11 | 248.50 | 22.67 | 3.50 | 22.67 |
August | 466.50 | 22.15 | 175.00 | 22.55 | 3.17 | 22.56 |
September | 653.33 | 21.85 | 40.50 | 21.96 | 0.00 | 21.96 |
October | 727.33 | 21.33 | 125.67 | 21.31 | 118.50 | 21.27 |
November | 720.00 | 21.01 | 658.33 | 21.01 | 658.33 | 21.01 |
December | 744.00 | 20.98 | 725.17 | 20.98 | 725.17 | 20.98 |
Annual Sum or Average | 7369.17 | 21.53 | 3527.50 | 21.53 | 2765.17 | 21.42 |
Minimum of Months | 351.33 | 20.91 | 40.50 | 20.90 | 0.00 | 20.90 |
Maximum of Months | 744.00 | 22.33 | 725.17 | 22.67 | 725.17 | 22.67 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.31 | 332.67 | 21.19 | 332.67 | 21.12 |
February | 672.00 | 21.49 | 199.33 | 21.38 | 199.33 | 21.31 |
March | 744.00 | 22.00 | 32.83 | 21.96 | 32.83 | 21.92 |
April | 681.83 | 22.85 | 0.00 | 22.85 | 0.00 | 22.85 |
May | 596.17 | 23.08 | 0.00 | 23.08 | 0.00 | 23.08 |
June | 292.00 | 22.95 | 96.50 | 23.19 | 0.00 | 23.19 |
July | 212.33 | 22.84 | 300.17 | 23.45 | 11.33 | 23.46 |
August | 300.83 | 22.88 | 191.17 | 23.28 | 5.83 | 23.29 |
September | 631.83 | 22.77 | 0.00 | 22.77 | 0.00 | 22.77 |
October | 743.50 | 22.18 | 0.17 | 22.18 | 0.17 | 22.18 |
November | 720.00 | 21.39 | 278.50 | 21.28 | 278.50 | 21.22 |
December | 744.00 | 21.23 | 420.67 | 21.15 | 420.67 | 21.11 |
Annual Sum or Average | 7082.50 | 22.10 | 1852.00 | 22.06 | 1281.33 | 21.93 |
Minimum of Months | 212.33 | 21.23 | 0.00 | 21.15 | 0.00 | 21.11 |
Maximum of Months | 744.00 | 23.08 | 420.67 | 23.45 | 420.67 | 23.46 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.48 | 744.00 | 20.48 | 744.00 | 20.48 |
February | 672.00 | 20.56 | 664.33 | 20.56 | 664.33 | 20.56 |
March | 744.00 | 20.91 | 577.33 | 20.85 | 577.33 | 20.82 |
April | 709.00 | 21.44 | 115.33 | 21.37 | 115.33 | 21.31 |
May | 720.50 | 21.62 | 0.00 | 21.62 | 0.00 | 21.62 |
June | 638.50 | 21.51 | 6.33 | 21.53 | 0.00 | 21.53 |
July | 644.50 | 21.47 | 7.33 | 21.49 | 0.00 | 21.49 |
August | 678.83 | 21.52 | 1.67 | 21.53 | 0.00 | 21.53 |
September | 716.00 | 21.38 | 29.17 | 21.35 | 29.17 | 21.32 |
October | 744.00 | 20.82 | 469.00 | 20.73 | 469.00 | 20.70 |
November | 720.00 | 20.49 | 720.00 | 20.49 | 720.00 | 20.49 |
December | 744.00 | 20.48 | 744.00 | 20.48 | 744.00 | 20.48 |
Annual Sum or Average | 8475.33 | 21.04 | 4078.50 | 20.89 | 4063.17 | 20.81 |
Minimum of Months | 638.50 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Maximum of Months | 744.00 | 21.62 | 744.00 | 21.62 | 744.00 | 21.62 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.48 | 744.00 | 20.48 | 744.00 | 20.48 |
February | 672.00 | 20.49 | 672.00 | 20.49 | 672.00 | 20.49 |
March | 744.00 | 20.60 | 696.67 | 20.58 | 696.67 | 20.57 |
April | 719.00 | 21.15 | 230.67 | 21.04 | 230.67 | 20.97 |
May | 686.67 | 21.70 | 38.17 | 21.94 | 2.33 | 21.96 |
June | 586.50 | 22.16 | 107.67 | 22.81 | 31.83 | 23.04 |
July | 572.00 | 21.86 | 110.33 | 22.42 | 8.00 | 22.48 |
August | 658.17 | 21.86 | 60.50 | 22.19 | 6.83 | 22.25 |
September | 717.17 | 21.20 | 77.00 | 21.13 | 76.00 | 21.07 |
October | 744.00 | 20.65 | 573.50 | 20.59 | 573.50 | 20.57 |
November | 720.00 | 20.48 | 720.00 | 20.48 | 720.00 | 20.48 |
December | 744.00 | 20.48 | 744.00 | 20.48 | 744.00 | 20.48 |
Annual Sum or Average | 8307.50 | 21.05 | 4774.50 | 20.98 | 4505.83 | 20.88 |
Minimum of Months | 572.00 | 20.48 | 38.17 | 20.48 | 2.33 | 20.48 |
Maximum of Months | 744.00 | 22.16 | 744.00 | 22.81 | 744.00 | 23.04 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.65 | 731.83 | 20.65 | 731.83 | 20.65 |
February | 672.00 | 20.72 | 599.33 | 20.70 | 599.33 | 20.69 |
March | 744.00 | 20.89 | 553.50 | 20.86 | 553.50 | 20.84 |
April | 720.00 | 21.23 | 131.67 | 21.18 | 131.67 | 21.15 |
May | 744.00 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
June | 710.00 | 22.09 | 0.67 | 22.09 | 0.00 | 22.09 |
July | 713.67 | 22.05 | 4.50 | 22.06 | 0.00 | 22.06 |
August | 738.67 | 21.88 | 0.00 | 21.88 | 0.00 | 21.88 |
September | 720.00 | 21.33 | 2.67 | 21.33 | 2.67 | 21.33 |
October | 744.00 | 21.00 | 287.83 | 20.92 | 287.83 | 20.88 |
November | 720.00 | 20.66 | 720.00 | 20.66 | 720.00 | 20.66 |
December | 744.00 | 20.63 | 724.83 | 20.62 | 724.83 | 20.62 |
Annual Sum or Average | 8714.33 | 21.24 | 3756.83 | 21.07 | 3751.67 | 20.98 |
Minimum of Months | 672.00 | 20.63 | 0.00 | 20.62 | 0.00 | 20.62 |
Maximum of Months | 744.00 | 22.09 | 731.83 | 22.09 | 731.83 | 22.09 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.49 | 744.00 | 20.49 | 744.00 | 20.49 |
February | 672.00 | 20.61 | 645.67 | 20.60 | 645.67 | 20.60 |
March | 744.00 | 21.18 | 452.33 | 21.07 | 452.33 | 21.02 |
April | 706.33 | 21.55 | 104.33 | 21.48 | 104.33 | 21.43 |
May | 657.67 | 21.53 | 0.33 | 21.53 | 0.00 | 21.53 |
June | 585.33 | 21.38 | 16.67 | 21.43 | 0.00 | 21.43 |
July | 605.17 | 21.38 | 29.50 | 21.47 | 0.00 | 21.47 |
August | 652.83 | 21.50 | 13.17 | 21.54 | 0.00 | 21.54 |
September | 707.33 | 21.47 | 13.00 | 21.46 | 13.00 | 21.44 |
October | 744.00 | 20.94 | 412.00 | 20.83 | 412.00 | 20.79 |
November | 720.00 | 20.49 | 720.00 | 20.49 | 720.00 | 20.49 |
December | 744.00 | 20.48 | 744.00 | 20.48 | 744.00 | 20.48 |
Annual Sum or Average | 8282.67 | 21.06 | 3895.00 | 20.92 | 3835.33 | 20.84 |
Minimum of Months | 585.33 | 20.48 | 0.33 | 20.48 | 0.00 | 20.48 |
Maximum of Months | 744.00 | 21.55 | 744.00 | 21.54 | 744.00 | 21.54 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.48 | 744.00 | 20.48 | 744.00 | 20.48 |
February | 672.00 | 20.51 | 670.33 | 20.51 | 670.33 | 20.51 |
March | 744.00 | 20.83 | 587.67 | 20.78 | 587.67 | 20.76 |
April | 720.00 | 21.39 | 193.17 | 21.28 | 193.17 | 21.22 |
May | 707.17 | 21.87 | 1.33 | 21.87 | 0.00 | 21.87 |
June | 518.17 | 21.79 | 43.83 | 22.04 | 2.33 | 22.06 |
July | 503.00 | 21.77 | 113.67 | 22.36 | 11.83 | 22.46 |
August | 647.50 | 21.87 | 17.83 | 21.95 | 0.00 | 21.95 |
September | 720.00 | 21.40 | 36.50 | 21.37 | 36.50 | 21.34 |
October | 744.00 | 20.76 | 503.67 | 20.69 | 503.67 | 20.66 |
November | 720.00 | 20.48 | 720.00 | 20.48 | 720.00 | 20.48 |
December | 744.00 | 20.48 | 744.00 | 20.48 | 744.00 | 20.48 |
Annual Sum or Average | 8183.83 | 21.09 | 4376.00 | 20.97 | 4213.50 | 20.87 |
Minimum of Months | 503.00 | 20.48 | 1.33 | 20.48 | 0.00 | 20.48 |
Maximum of Months | 744.00 | 21.87 | 744.00 | 22.36 | 744.00 | 22.46 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.99 | 724.33 | 20.99 | 724.33 | 20.99 |
February | 672.00 | 21.00 | 618.33 | 21.00 | 618.33 | 21.00 |
March | 744.00 | 21.01 | 567.17 | 21.01 | 567.17 | 21.01 |
April | 720.00 | 21.55 | 116.33 | 21.48 | 116.33 | 21.42 |
May | 744.00 | 22.54 | 0.00 | 22.54 | 0.00 | 22.54 |
June | 718.00 | 23.22 | 0.00 | 23.22 | 0.00 | 23.22 |
July | 715.17 | 23.15 | 0.00 | 23.15 | 0.00 | 23.15 |
August | 744.00 | 22.76 | 0.00 | 22.76 | 0.00 | 22.76 |
September | 720.00 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
October | 744.00 | 21.01 | 287.33 | 21.01 | 287.33 | 21.01 |
November | 720.00 | 21.00 | 720.00 | 21.00 | 720.00 | 21.00 |
December | 744.00 | 21.00 | 736.50 | 21.00 | 736.50 | 21.00 |
Annual Sum or Average | 8729.17 | 21.73 | 3770.00 | 21.51 | 3770.00 | 21.39 |
Minimum of Months | 672.00 | 20.99 | 0.00 | 20.99 | 0.00 | 20.99 |
Maximum of Months | 744.00 | 23.22 | 736.50 | 23.22 | 736.50 | 23.22 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.47 | 744.00 | 20.47 | 744.00 | 20.47 |
February | 672.00 | 20.49 | 672.00 | 20.49 | 672.00 | 20.49 |
March | 744.00 | 20.75 | 656.17 | 20.71 | 656.17 | 20.69 |
April | 706.83 | 21.34 | 209.00 | 21.22 | 209.00 | 21.15 |
May | 713.50 | 21.57 | 4.17 | 21.57 | 3.33 | 21.57 |
June | 625.67 | 21.47 | 13.00 | 21.50 | 0.00 | 21.50 |
July | 634.00 | 21.42 | 14.50 | 21.47 | 0.00 | 21.47 |
August | 672.50 | 21.48 | 8.33 | 21.50 | 0.00 | 21.50 |
September | 714.83 | 21.28 | 111.17 | 21.20 | 111.17 | 21.14 |
October | 744.00 | 20.69 | 595.17 | 20.64 | 595.17 | 20.62 |
November | 720.00 | 20.47 | 720.00 | 20.47 | 720.00 | 20.47 |
December | 744.00 | 20.47 | 744.00 | 20.47 | 744.00 | 20.47 |
Annual Sum or Average | 8435.33 | 20.98 | 4491.50 | 20.83 | 4454.83 | 20.76 |
Minimum of Months | 625.67 | 20.47 | 4.17 | 20.47 | 0.00 | 20.47 |
Maximum of Months | 744.00 | 21.57 | 744.00 | 21.57 | 744.00 | 21.57 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.47 | 744.00 | 20.47 | 744.00 | 20.47 |
February | 672.00 | 20.47 | 672.00 | 20.47 | 672.00 | 20.47 |
March | 744.00 | 20.53 | 724.83 | 20.52 | 724.83 | 20.52 |
April | 718.17 | 21.04 | 328.83 | 20.92 | 328.83 | 20.86 |
May | 688.50 | 21.71 | 47.00 | 21.99 | 13.67 | 22.05 |
June | 585.33 | 22.31 | 117.67 | 23.04 | 48.50 | 23.38 |
July | 559.17 | 21.89 | 118.17 | 22.54 | 17.67 | 22.67 |
August | 656.33 | 21.89 | 71.00 | 22.28 | 20.33 | 22.41 |
September | 716.50 | 21.07 | 170.33 | 20.97 | 169.17 | 20.90 |
October | 744.00 | 20.56 | 677.17 | 20.54 | 677.17 | 20.53 |
November | 720.00 | 20.47 | 720.00 | 20.47 | 720.00 | 20.47 |
December | 744.00 | 20.47 | 744.00 | 20.47 | 744.00 | 20.47 |
Annual Sum or Average | 8292.00 | 21.03 | 5135.00 | 20.97 | 4880.17 | 20.88 |
Minimum of Months | 559.17 | 20.47 | 47.00 | 20.47 | 13.67 | 20.47 |
Maximum of Months | 744.00 | 22.31 | 744.00 | 23.04 | 744.00 | 23.38 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.53 | 738.50 | 20.53 | 738.50 | 20.53 |
February | 672.00 | 20.92 | 579.33 | 20.83 | 579.33 | 20.80 |
March | 720.50 | 21.24 | 422.50 | 21.12 | 422.50 | 21.07 |
April | 650.33 | 21.42 | 86.67 | 21.41 | 75.00 | 21.37 |
May | 660.17 | 21.48 | 14.17 | 21.52 | 0.00 | 21.52 |
June | 615.67 | 21.44 | 31.00 | 21.53 | 0.00 | 21.53 |
July | 630.50 | 21.42 | 40.17 | 21.54 | 0.00 | 21.54 |
August | 644.83 | 21.45 | 43.83 | 21.57 | 0.00 | 21.57 |
September | 673.83 | 21.42 | 20.00 | 21.44 | 8.83 | 21.43 |
October | 730.33 | 21.08 | 350.50 | 20.98 | 348.17 | 20.92 |
November | 720.00 | 20.60 | 703.50 | 20.58 | 703.50 | 20.58 |
December | 744.00 | 20.48 | 744.00 | 20.48 | 744.00 | 20.48 |
Annual Sum or Average | 8206.17 | 21.10 | 3774.17 | 20.99 | 3619.83 | 20.91 |
Minimum of Months | 615.67 | 20.48 | 14.17 | 20.48 | 0.00 | 20.48 |
Maximum of Months | 744.00 | 21.48 | 744.00 | 21.57 | 744.00 | 21.57 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.54 | 120.17 | 22.32 | 120.17 | 22.16 |
February | 659.33 | 22.60 | 80.17 | 22.43 | 80.17 | 22.29 |
March | 676.00 | 23.05 | 25.83 | 22.97 | 25.83 | 22.90 |
April | 384.33 | 23.35 | 0.00 | 23.35 | 0.00 | 23.35 |
May | 82.00 | 23.35 | 56.67 | 23.61 | 0.00 | 23.61 |
June | 0.83 | 23.24 | 630.67 | 23.98 | 0.00 | 23.98 |
July | 8.83 | 23.99 | 721.00 | 23.97 | 8.83 | 23.97 |
August | 25.17 | 23.44 | 579.50 | 23.95 | 8.00 | 23.95 |
September | 205.17 | 23.18 | 139.50 | 23.51 | 0.00 | 23.51 |
October | 526.67 | 23.20 | 0.00 | 23.20 | 0.00 | 23.20 |
November | 720.00 | 22.58 | 93.50 | 22.40 | 93.50 | 22.25 |
December | 744.00 | 22.36 | 144.50 | 22.14 | 144.50 | 21.98 |
Annual Sum or Average | 4776.33 | 22.78 | 2591.50 | 23.02 | 481.00 | 22.90 |
Minimum of Months | 0.83 | 22.36 | 0.00 | 22.14 | 0.00 | 21.98 |
Maximum of Months | 744.00 | 23.99 | 721.00 | 23.98 | 144.50 | 23.98 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 699.33 | 22.72 | 67.33 | 22.57 | 67.33 | 22.44 |
February | 594.67 | 22.73 | 43.00 | 22.61 | 43.00 | 22.51 |
March | 564.00 | 23.17 | 10.83 | 23.13 | 10.83 | 23.09 |
April | 234.17 | 23.44 | 9.33 | 23.47 | 0.00 | 23.47 |
May | 1.50 | 23.25 | 220.50 | 23.99 | 0.00 | 23.99 |
June | 0.00 | 0.00 | 694.33 | 23.99 | 0.00 | 23.99 |
July | 4.50 | 23.99 | 742.67 | 23.98 | 4.50 | 23.98 |
August | 17.33 | 23.57 | 674.17 | 23.96 | 6.17 | 23.96 |
September | 63.83 | 23.26 | 313.67 | 23.87 | 0.00 | 23.87 |
October | 373.67 | 23.31 | 29.83 | 23.36 | 0.00 | 23.36 |
November | 702.50 | 22.82 | 61.33 | 22.67 | 61.33 | 22.55 |
December | 729.50 | 22.58 | 84.00 | 22.42 | 84.00 | 22.29 |
Annual Sum or Average | 3985.00 | 22.89 | 2951.00 | 23.24 | 277.17 | 23.16 |
Minimum of Months | 0.00 | 0.00 | 9.33 | 22.42 | 0.00 | 22.29 |
Maximum of Months | 729.50 | 23.99 | 742.67 | 23.99 | 84.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 472.00 | 23.03 | 522.50 | 23.45 | 298.83 | 23.54 |
February | 454.67 | 23.25 | 490.67 | 23.58 | 318.17 | 23.67 |
March | 554.67 | 23.53 | 569.00 | 23.75 | 438.50 | 23.81 |
April | 507.00 | 23.88 | 610.67 | 23.90 | 475.50 | 23.93 |
May | 542.83 | 23.99 | 721.67 | 23.92 | 542.83 | 23.94 |
June | 543.17 | 23.99 | 720.00 | 23.94 | 543.17 | 23.95 |
July | 568.17 | 23.99 | 744.00 | 23.94 | 568.17 | 23.95 |
August | 554.83 | 23.99 | 738.83 | 23.92 | 554.83 | 23.94 |
September | 503.67 | 23.99 | 691.00 | 23.90 | 503.17 | 23.92 |
October | 509.67 | 23.80 | 619.17 | 23.87 | 457.83 | 23.90 |
November | 463.00 | 23.17 | 518.33 | 23.56 | 296.33 | 23.66 |
December | 435.00 | 22.95 | 524.33 | 23.47 | 251.67 | 23.58 |
Annual Sum or Average | 6108.67 | 23.66 | 7470.17 | 23.78 | 5249.00 | 23.84 |
Minimum of Months | 435.00 | 22.95 | 490.67 | 23.45 | 251.67 | 23.54 |
Maximum of Months | 568.17 | 23.99 | 744.00 | 23.94 | 568.17 | 23.95 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.99 | 744.00 | 20.99 | 744.00 | 20.99 |
February | 672.00 | 21.00 | 649.00 | 21.00 | 649.00 | 21.00 |
March | 744.00 | 21.01 | 574.83 | 21.01 | 574.83 | 21.00 |
April | 720.00 | 21.42 | 133.00 | 21.35 | 133.00 | 21.30 |
May | 744.00 | 22.26 | 0.00 | 22.26 | 0.00 | 22.26 |
June | 641.83 | 23.03 | 9.00 | 23.04 | 0.00 | 23.04 |
July | 570.00 | 22.92 | 24.67 | 22.96 | 0.00 | 22.96 |
August | 697.50 | 22.52 | 1.00 | 22.53 | 0.00 | 22.53 |
September | 720.00 | 21.36 | 0.00 | 21.36 | 0.00 | 21.36 |
October | 744.00 | 21.01 | 300.17 | 21.01 | 300.17 | 21.01 |
November | 720.00 | 21.00 | 720.00 | 21.00 | 720.00 | 21.00 |
December | 744.00 | 21.00 | 744.00 | 21.00 | 744.00 | 21.00 |
Annual Sum or Average | 8461.33 | 21.59 | 3899.67 | 21.41 | 3865.00 | 21.31 |
Minimum of Months | 570.00 | 20.99 | 0.00 | 20.99 | 0.00 | 20.99 |
Maximum of Months | 744.00 | 23.03 | 744.00 | 23.04 | 744.00 | 23.04 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.94172 | 15.56873 | -0.3409 | 7.82253 |
February | 672.00000 | 21.36168 | 16.84926 | -0.4807 | 10.09081 |
March | 744.00000 | 21.34820 | 19.06413 | -0.4731 | 9.84751 |
April | 720.00000 | 21.54892 | 23.42799 | -0.3967 | 8.46361 |
May | 744.00000 | 21.65460 | 28.82620 | -1.4844 | 50.08570 |
June | 720.00000 | 21.95585 | 42.71006 | -1.2923 | 40.01942 |
July | 744.00000 | 22.63334 | 50.42128 | -1.0007 | 26.42207 |
August | 744.00000 | 23.38865 | 43.58887 | -0.7749 | 17.90175 |
September | 720.00000 | 23.69910 | 33.16430 | -0.7320 | 16.46223 |
October | 744.00000 | 23.71894 | 24.33884 | 0.15517 | 5.61705 |
November | 720.00000 | 23.23750 | 14.34007 | -0.0258 | 5.65418 |
December | 744.00000 | 22.21395 | 13.87564 | -0.2804 | 7.07843 |
Annual Sum or Average | 8760.00000 | 22.39794 | 27.25273 | -0.5946 | 17.17412 |
Minimum of Months | 672.00000 | 21.34820 | 13.87564 | -1.4844 | 5.61705 |
Maximum of Months | 744.00000 | 23.71894 | 50.42128 | 0.15517 | 50.08570 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.85612 | 13.26037 | -0.8176 | 19.61637 |
February | 672.00000 | 21.00798 | 14.20164 | -0.6961 | 15.60047 |
March | 744.00000 | 21.24004 | 16.32933 | -0.5177 | 11.96492 |
April | 720.00000 | 21.62451 | 20.57040 | -0.2743 | 8.76710 |
May | 744.00000 | 21.64429 | 26.05570 | -1.2729 | 41.19751 |
June | 720.00000 | 21.83950 | 40.30475 | -1.0804 | 31.92927 |
July | 744.00000 | 21.80434 | 49.91477 | -1.0346 | 30.30852 |
August | 744.00000 | 21.71117 | 44.58481 | -1.1205 | 34.49182 |
September | 720.00000 | 21.29905 | 34.49979 | -1.4378 | 48.88059 |
October | 744.00000 | 21.08605 | 24.51888 | -0.5211 | 11.33058 |
November | 720.00000 | 21.00141 | 12.54757 | -0.7683 | 17.56935 |
December | 744.00000 | 20.97580 | 11.61480 | -0.8315 | 19.72857 |
Annual Sum or Average | 8760.00000 | 21.34249 | 25.78071 | -0.8655 | 24.32600 |
Minimum of Months | 672.00000 | 20.85612 | 11.61480 | -1.4378 | 8.76710 |
Maximum of Months | 744.00000 | 21.83950 | 49.91477 | -0.2743 | 48.88059 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.08025 | 16.19327 | -0.5657 | 11.93045 |
February | 672.00000 | 21.22471 | 17.08232 | -0.5060 | 10.64751 |
March | 744.00000 | 21.57032 | 19.06107 | -0.3917 | 8.60981 |
April | 720.00000 | 22.53276 | 22.68526 | -0.1174 | 5.91055 |
May | 744.00000 | 22.94283 | 27.49720 | -0.9796 | 25.77478 |
June | 720.00000 | 23.25271 | 40.34316 | -0.7776 | 18.25346 |
July | 744.00000 | 23.23923 | 49.08675 | -0.7237 | 16.59309 |
August | 744.00000 | 23.15922 | 44.24285 | -0.7893 | 18.78646 |
September | 720.00000 | 22.55223 | 35.29418 | -1.0767 | 30.11273 |
October | 744.00000 | 21.80886 | 26.60940 | -0.2849 | 7.21808 |
November | 720.00000 | 21.14408 | 15.49440 | -0.5431 | 11.33251 |
December | 744.00000 | 21.05685 | 14.57753 | -0.5899 | 12.41483 |
Annual Sum or Average | 8760.00000 | 22.13515 | 27.41952 | -0.6128 | 14.81523 |
Minimum of Months | 672.00000 | 21.05685 | 14.57753 | -1.0767 | 5.91055 |
Maximum of Months | 744.00000 | 23.25271 | 49.08675 | -0.1174 | 30.11273 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.35890 | 10.60940 | 0.31768 | 11.54890 |
February | 672.00000 | 22.52950 | 11.40475 | 0.37696 | 11.61472 |
March | 744.00000 | 22.82247 | 13.35266 | 0.48437 | 12.96091 |
April | 720.00000 | 22.97361 | 17.46660 | 0.58555 | 14.84151 |
May | 744.00000 | 23.00663 | 22.46700 | -0.0557 | 10.21575 |
June | 720.00000 | 23.01635 | 35.87839 | 0.05995 | 10.30939 |
July | 744.00000 | 23.01756 | 44.74463 | 0.11793 | 10.55626 |
August | 744.00000 | 23.02759 | 39.55880 | 0.07542 | 10.41140 |
September | 720.00000 | 23.01735 | 29.65872 | -0.0415 | 10.24451 |
October | 744.00000 | 22.95394 | 20.56384 | 0.57219 | 14.57949 |
November | 720.00000 | 22.56648 | 9.94009 | 0.36558 | 11.10375 |
December | 744.00000 | 22.45243 | 9.10244 | 0.31869 | 10.70619 |
Annual Sum or Average | 8760.00000 | 22.81333 | 22.13701 | 0.26409 | 11.59050 |
Minimum of Months | 672.00000 | 22.35890 | 9.10244 | -0.0557 | 10.21575 |
Maximum of Months | 744.00000 | 23.02759 | 44.74463 | 0.58555 | 14.84151 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.90529 | 17.62183 | -0.7033 | 15.89121 |
February | 672.00000 | 21.06822 | 18.58437 | -0.5696 | 12.25284 |
March | 744.00000 | 21.52393 | 20.61350 | -0.3421 | 8.89470 |
April | 720.00000 | 22.32386 | 24.38532 | -0.0266 | 6.87120 |
May | 744.00000 | 22.52956 | 29.48774 | -0.8912 | 23.76848 |
June | 720.00000 | 22.76437 | 42.95333 | -0.6952 | 16.69333 |
July | 744.00000 | 22.71967 | 51.98480 | -0.6512 | 15.81835 |
August | 744.00000 | 22.62697 | 46.99777 | -0.7325 | 18.82492 |
September | 720.00000 | 22.00235 | 37.71737 | -1.0999 | 32.51469 |
October | 744.00000 | 21.38222 | 28.55857 | -0.3466 | 8.38461 |
November | 720.00000 | 21.01106 | 16.93664 | -0.6585 | 14.28418 |
December | 744.00000 | 20.98301 | 16.00686 | -0.7298 | 16.40922 |
Annual Sum or Average | 8760.00000 | 21.82397 | 29.39601 | -0.6210 | 15.89512 |
Minimum of Months | 672.00000 | 20.90529 | 16.00686 | -1.0999 | 6.87120 |
Maximum of Months | 744.00000 | 22.76437 | 51.98480 | -0.0266 | 32.51469 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.30625 | 18.14861 | -0.4871 | 10.50290 |
February | 672.00000 | 21.49185 | 19.04429 | -0.4103 | 9.10078 |
March | 744.00000 | 21.99838 | 20.99798 | -0.2503 | 6.93702 |
April | 720.00000 | 22.90310 | 24.62724 | 0.02259 | 5.63171 |
May | 744.00000 | 23.24495 | 29.37978 | -0.7999 | 19.05635 |
June | 720.00000 | 23.45160 | 42.12184 | -0.6251 | 13.70146 |
July | 744.00000 | 23.44936 | 50.69888 | -0.5668 | 12.30551 |
August | 744.00000 | 23.40585 | 45.89267 | -0.6233 | 13.83973 |
September | 720.00000 | 22.89462 | 37.00355 | -0.8951 | 22.90894 |
October | 744.00000 | 22.18248 | 28.41337 | -0.1580 | 6.28510 |
November | 720.00000 | 21.39357 | 17.47380 | -0.4587 | 9.81985 |
December | 744.00000 | 21.23412 | 16.59733 | -0.5245 | 11.08316 |
Annual Sum or Average | 8760.00000 | 22.41787 | 29.27129 | -0.4819 | 11.77256 |
Minimum of Months | 672.00000 | 21.23412 | 16.59733 | -0.8951 | 5.63171 |
Maximum of Months | 744.00000 | 23.45160 | 50.69888 | 0.02259 | 22.90894 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.48360 | 29.82465 | -0.8509 | 20.88864 |
February | 672.00000 | 20.56023 | 30.60005 | -0.7827 | 18.44908 |
March | 744.00000 | 20.90984 | 32.64950 | -0.6158 | 13.59902 |
April | 720.00000 | 21.47009 | 36.49130 | -0.3185 | 8.45190 |
May | 744.00000 | 21.67237 | 39.05810 | -1.2913 | 41.14256 |
June | 720.00000 | 21.71957 | 48.25188 | -1.1434 | 34.09969 |
July | 744.00000 | 21.71546 | 53.96143 | -1.1267 | 33.29050 |
August | 744.00000 | 21.68130 | 52.59651 | -1.1970 | 36.57220 |
September | 720.00000 | 21.38784 | 48.36667 | -1.4781 | 50.30933 |
October | 744.00000 | 20.81574 | 41.30112 | -0.5896 | 12.91820 |
November | 720.00000 | 20.48926 | 29.24418 | -0.8386 | 20.35813 |
December | 744.00000 | 20.47843 | 27.70713 | -0.8810 | 21.99549 |
Annual Sum or Average | 8760.00000 | 21.11821 | 39.22596 | -0.9271 | 26.04315 |
Minimum of Months | 672.00000 | 20.47843 | 27.70713 | -1.4781 | 8.45190 |
Maximum of Months | 744.00000 | 21.71957 | 53.96143 | -0.3185 | 50.30933 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.48070 | 29.82427 | -0.8588 | 21.21145 |
February | 672.00000 | 20.48966 | 30.72954 | -0.8243 | 19.95242 |
March | 744.00000 | 20.59543 | 33.16089 | -0.7250 | 16.64986 |
April | 720.00000 | 21.15499 | 37.00263 | -0.4367 | 9.94406 |
May | 744.00000 | 21.99473 | 38.76491 | -1.2434 | 40.34340 |
June | 720.00000 | 22.65851 | 46.83915 | -0.8948 | 28.04158 |
July | 744.00000 | 22.47371 | 52.70004 | -0.9331 | 27.66965 |
August | 744.00000 | 22.20471 | 51.92760 | -1.0888 | 33.60534 |
September | 720.00000 | 21.20869 | 48.80476 | -1.5777 | 55.26853 |
October | 744.00000 | 20.64580 | 41.70520 | -0.6502 | 14.44209 |
November | 720.00000 | 20.48102 | 29.24196 | -0.8533 | 20.94274 |
December | 744.00000 | 20.47779 | 27.69923 | -0.8834 | 22.09480 |
Annual Sum or Average | 8760.00000 | 21.24347 | 39.08583 | -0.9146 | 25.86600 |
Minimum of Months | 672.00000 | 20.47779 | 27.69923 | -1.5777 | 9.94406 |
Maximum of Months | 744.00000 | 22.65851 | 52.70004 | -0.4367 | 55.26853 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.65251 | 25.38433 | -0.7182 | 16.39227 |
February | 672.00000 | 20.72045 | 26.14564 | -0.6880 | 15.43886 |
March | 744.00000 | 20.89274 | 28.64275 | -0.6109 | 13.16592 |
April | 720.00000 | 21.22930 | 33.03358 | -0.4550 | 9.59570 |
May | 744.00000 | 21.69358 | 35.18547 | -1.4128 | 46.53420 |
June | 720.00000 | 22.12031 | 45.22545 | -1.1623 | 34.48931 |
July | 744.00000 | 22.13517 | 52.17176 | -1.1199 | 32.74405 |
August | 744.00000 | 21.89796 | 49.31269 | -1.2548 | 38.80151 |
September | 720.00000 | 21.33412 | 44.86762 | -1.5311 | 52.66011 |
October | 744.00000 | 20.99788 | 37.12764 | -0.5183 | 10.91075 |
November | 720.00000 | 20.66077 | 24.78893 | -0.7169 | 16.29194 |
December | 744.00000 | 20.63015 | 23.22819 | -0.7418 | 17.12474 |
Annual Sum or Average | 8760.00000 | 21.25043 | 35.48543 | -0.9120 | 25.39528 |
Minimum of Months | 672.00000 | 20.63015 | 23.22819 | -1.5311 | 9.59570 |
Maximum of Months | 744.00000 | 22.13517 | 52.17176 | -0.4550 | 52.66011 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.48763 | 29.81715 | -0.8476 | 20.75973 |
February | 672.00000 | 20.60987 | 30.49103 | -0.7604 | 17.75920 |
March | 744.00000 | 21.17704 | 32.19510 | -0.5274 | 11.82558 |
April | 720.00000 | 21.57992 | 36.34868 | -0.2914 | 8.24651 |
May | 744.00000 | 21.73460 | 38.98482 | -1.2175 | 38.00163 |
June | 720.00000 | 21.74264 | 47.98065 | -1.1085 | 32.78857 |
July | 744.00000 | 21.74360 | 52.88103 | -1.0816 | 31.58097 |
August | 744.00000 | 21.72611 | 51.59258 | -1.1560 | 34.90773 |
September | 720.00000 | 21.50216 | 47.96713 | -1.4155 | 47.30066 |
October | 744.00000 | 20.93845 | 41.00779 | -0.5459 | 12.06065 |
November | 720.00000 | 20.49164 | 29.23021 | -0.8376 | 20.33185 |
December | 744.00000 | 20.47849 | 27.70235 | -0.8806 | 21.97767 |
Annual Sum or Average | 8760.00000 | 21.18748 | 38.90179 | -0.8900 | 24.82690 |
Minimum of Months | 672.00000 | 20.47849 | 27.70235 | -1.4155 | 8.24651 |
Maximum of Months | 744.00000 | 21.74360 | 52.88103 | -0.2914 | 47.30066 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.48252 | 29.81833 | -0.8559 | 21.09398 |
February | 672.00000 | 20.50911 | 30.67303 | -0.8082 | 19.38397 |
March | 744.00000 | 20.83404 | 32.70141 | -0.6431 | 14.29733 |
April | 720.00000 | 21.38651 | 36.56943 | -0.3869 | 9.24782 |
May | 744.00000 | 21.95253 | 38.48203 | -1.1996 | 37.02191 |
June | 720.00000 | 22.39610 | 46.78801 | -0.9466 | 26.68548 |
July | 744.00000 | 22.47575 | 51.91567 | -0.8940 | 26.06029 |
August | 744.00000 | 22.13017 | 50.99953 | -1.0829 | 31.79549 |
September | 720.00000 | 21.39701 | 48.23385 | -1.4937 | 51.01639 |
October | 744.00000 | 20.76445 | 41.37703 | -0.6076 | 13.37003 |
November | 720.00000 | 20.48285 | 29.22997 | -0.8525 | 20.91905 |
December | 744.00000 | 20.47784 | 27.69676 | -0.8829 | 22.07468 |
Annual Sum or Average | 8760.00000 | 21.27881 | 38.75670 | -0.8881 | 24.42723 |
Minimum of Months | 672.00000 | 20.47784 | 27.69676 | -1.4937 | 9.24782 |
Maximum of Months | 744.00000 | 22.47575 | 51.91567 | -0.3869 | 51.01639 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.47157 | 30.34555 | -0.9181 | 23.43003 |
February | 672.00000 | 20.49269 | 31.24644 | -0.8592 | 21.14778 |
March | 744.00000 | 20.74624 | 33.49431 | -0.7000 | 16.01329 |
April | 720.00000 | 21.37661 | 37.34246 | -0.3636 | 9.38759 |
May | 744.00000 | 21.64431 | 39.72000 | -1.3191 | 42.68622 |
June | 720.00000 | 21.70713 | 48.82194 | -1.1525 | 34.70629 |
July | 744.00000 | 21.70396 | 55.03384 | -1.1324 | 33.72207 |
August | 744.00000 | 21.65577 | 53.70929 | -1.2166 | 37.66893 |
September | 720.00000 | 21.29207 | 49.79616 | -1.5423 | 53.63321 |
October | 744.00000 | 20.68980 | 42.52049 | -0.6598 | 14.84483 |
November | 720.00000 | 20.47226 | 29.74248 | -0.9078 | 22.94455 |
December | 744.00000 | 20.46920 | 28.16347 | -0.9488 | 24.63577 |
Annual Sum or Average | 8760.00000 | 21.06313 | 40.05092 | -0.9775 | 27.93239 |
Minimum of Months | 672.00000 | 20.46920 | 28.16347 | -1.5423 | 9.38759 |
Maximum of Months | 744.00000 | 21.70713 | 55.03384 | -0.3636 | 53.63321 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.47012 | 30.34494 | -0.9251 | 23.73938 |
February | 672.00000 | 20.47349 | 31.28609 | -0.8898 | 22.36318 |
March | 744.00000 | 20.53120 | 33.87632 | -0.7922 | 18.86424 |
April | 720.00000 | 21.04585 | 37.92073 | -0.4908 | 11.21672 |
May | 744.00000 | 21.99342 | 39.45152 | -1.2635 | 42.11606 |
June | 720.00000 | 22.73356 | 47.25131 | -0.8689 | 28.75986 |
July | 744.00000 | 22.52359 | 53.39406 | -0.9150 | 28.01130 |
August | 744.00000 | 22.22479 | 52.96884 | -1.0912 | 34.77399 |
September | 720.00000 | 21.08265 | 50.35072 | -1.6566 | 59.28851 |
October | 744.00000 | 20.56260 | 42.85323 | -0.7132 | 16.32915 |
November | 720.00000 | 20.47022 | 29.74510 | -0.9206 | 23.49003 |
December | 744.00000 | 20.46874 | 28.16664 | -0.9509 | 24.73062 |
Annual Sum or Average | 8760.00000 | 21.21982 | 39.85416 | -0.9567 | 27.82008 |
Minimum of Months | 672.00000 | 20.46874 | 28.16664 | -1.6566 | 11.21672 |
Maximum of Months | 744.00000 | 22.73356 | 53.39406 | -0.4908 | 59.28851 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.53278 | 30.71375 | -0.8295 | 20.10237 |
February | 672.00000 | 20.91739 | 31.20494 | -0.6643 | 15.46682 |
March | 744.00000 | 21.30876 | 33.15717 | -0.4667 | 11.19956 |
April | 720.00000 | 21.60216 | 37.23849 | -0.2563 | 8.20399 |
May | 744.00000 | 21.68848 | 39.52674 | -1.2848 | 41.40195 |
June | 720.00000 | 21.71216 | 48.25224 | -1.1784 | 36.11419 |
July | 744.00000 | 21.71325 | 53.94868 | -1.1429 | 34.43010 |
August | 744.00000 | 21.69596 | 52.20982 | -1.1859 | 36.59731 |
September | 720.00000 | 21.54107 | 48.08627 | -1.3872 | 46.21972 |
October | 744.00000 | 21.12140 | 41.25027 | -0.4848 | 11.09002 |
November | 720.00000 | 20.59951 | 30.09716 | -0.7975 | 19.01933 |
December | 744.00000 | 20.48275 | 28.69014 | -0.8782 | 21.88751 |
Annual Sum or Average | 8760.00000 | 21.24433 | 39.58454 | -0.8812 | 25.19935 |
Minimum of Months | 672.00000 | 20.48275 | 28.69014 | -1.3872 | 8.20399 |
Maximum of Months | 744.00000 | 21.71325 | 53.94868 | -0.2563 | 46.21972 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.53868 | 20.88065 | -0.1932 | 7.55421 |
February | 672.00000 | 22.62839 | 21.66608 | -0.1491 | 7.23166 |
March | 744.00000 | 23.13489 | 23.28361 | 0.00825 | 6.23098 |
April | 720.00000 | 23.64618 | 26.19242 | 0.20862 | 6.37657 |
May | 744.00000 | 23.87888 | 29.88077 | -0.5231 | 10.88888 |
June | 720.00000 | 23.95591 | 41.82659 | -0.3545 | 7.73359 |
July | 744.00000 | 23.95472 | 50.22454 | -0.2996 | 6.98009 |
August | 744.00000 | 23.89623 | 45.91033 | -0.3899 | 8.46042 |
September | 720.00000 | 23.73307 | 37.50739 | -0.5850 | 12.72475 |
October | 744.00000 | 23.42790 | 29.77906 | 0.14235 | 6.22797 |
November | 720.00000 | 22.57569 | 20.30712 | -0.1854 | 7.32068 |
December | 744.00000 | 22.35637 | 19.57044 | -0.2541 | 7.86081 |
Annual Sum or Average | 8760.00000 | 23.31435 | 30.64950 | -0.2149 | 7.96564 |
Minimum of Months | 672.00000 | 22.35637 | 19.57044 | -0.5850 | 6.22797 |
Maximum of Months | 744.00000 | 23.95591 | 50.22454 | 0.20862 | 12.72475 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.79751 | 20.09339 | -0.0886 | 6.94766 |
February | 672.00000 | 22.87237 | 20.81659 | -0.0491 | 6.78132 |
March | 744.00000 | 23.36587 | 22.30399 | 0.10492 | 6.29799 |
April | 720.00000 | 23.80145 | 25.22370 | 0.28493 | 6.98426 |
May | 744.00000 | 23.94878 | 29.06838 | -0.4477 | 9.26125 |
June | 720.00000 | 23.98449 | 41.20362 | -0.3006 | 6.96905 |
July | 744.00000 | 23.98312 | 49.59281 | -0.2460 | 6.34051 |
August | 744.00000 | 23.95259 | 45.13911 | -0.3230 | 7.36717 |
September | 720.00000 | 23.86318 | 36.44421 | -0.4815 | 10.15090 |
October | 744.00000 | 23.63715 | 28.66975 | 0.23528 | 6.71467 |
November | 720.00000 | 22.84561 | 19.51449 | -0.0783 | 6.72300 |
December | 744.00000 | 22.61094 | 18.88659 | -0.1514 | 7.06577 |
Annual Sum or Average | 8760.00000 | 23.47519 | 29.81047 | -0.1289 | 7.30011 |
Minimum of Months | 672.00000 | 22.61094 | 18.88659 | -0.4815 | 6.29799 |
Maximum of Months | 744.00000 | 23.98449 | 49.59281 | 0.28493 | 10.15090 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.21167 | 19.60280 | 0.62090 | 17.76642 |
February | 672.00000 | 23.33504 | 20.07646 | 0.68814 | 19.48751 |
March | 744.00000 | 23.52391 | 20.95136 | 0.80192 | 22.60150 |
April | 720.00000 | 23.71590 | 24.22446 | 0.94775 | 26.83844 |
May | 744.00000 | 23.83129 | 28.57149 | 0.52386 | 15.81821 |
June | 720.00000 | 23.89716 | 40.88974 | 0.67630 | 18.86587 |
July | 744.00000 | 23.89389 | 49.10951 | 0.73108 | 20.73958 |
August | 744.00000 | 23.86233 | 44.44265 | 0.64103 | 18.37784 |
September | 720.00000 | 23.77888 | 35.45911 | 0.45106 | 14.28620 |
October | 744.00000 | 23.66989 | 27.46387 | 0.88784 | 24.41388 |
November | 720.00000 | 23.33253 | 18.94593 | 0.65126 | 18.01961 |
December | 744.00000 | 23.24356 | 18.53088 | 0.60451 | 17.11840 |
Annual Sum or Average | 8760.00000 | 23.60945 | 29.08649 | 0.68549 | 19.52840 |
Minimum of Months | 672.00000 | 23.21167 | 18.53088 | 0.45106 | 14.28620 |
Maximum of Months | 744.00000 | 23.89716 | 49.10951 | 0.94775 | 26.83844 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.99578 | 13.23602 | -0.6633 | 14.31500 |
February | 672.00000 | 21.00020 | 14.21153 | -0.6430 | 13.77158 |
March | 744.00000 | 21.00215 | 16.35376 | -0.6014 | 12.66205 |
April | 720.00000 | 21.37641 | 20.59977 | -0.4460 | 9.47480 |
May | 744.00000 | 22.29702 | 25.08337 | -1.2647 | 38.60125 |
June | 720.00000 | 23.01058 | 37.57112 | -0.9364 | 23.71061 |
July | 744.00000 | 23.08885 | 46.33438 | -0.8511 | 20.54244 |
August | 744.00000 | 22.80805 | 41.83225 | -0.9805 | 25.68912 |
September | 720.00000 | 21.77048 | 33.45024 | -1.3950 | 45.41921 |
October | 744.00000 | 21.08346 | 24.42500 | -0.5112 | 10.62075 |
November | 720.00000 | 21.00022 | 12.55926 | -0.6583 | 14.14869 |
December | 744.00000 | 21.00023 | 11.54992 | -0.6794 | 14.75558 |
Annual Sum or Average | 8760.00000 | 21.70761 | 24.83997 | -0.8032 | 20.33144 |
Minimum of Months | 672.00000 | 20.99578 | 11.54992 | -1.3950 | 9.47480 |
Maximum of Months | 744.00000 | 23.08885 | 46.33438 | -0.4460 | 45.41921 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.98854 | 16.63338 | -0.6373 | 13.59190 |
February | 672.00000 | 21.00052 | 17.64684 | -0.6132 | 12.94982 |
March | 744.00000 | 21.00786 | 19.82035 | -0.5712 | 11.88453 |
April | 720.00000 | 21.55263 | 23.92578 | -0.3902 | 8.59968 |
May | 744.00000 | 22.53868 | 28.34676 | -1.1766 | 34.34998 |
June | 720.00000 | 23.22209 | 40.80078 | -0.8564 | 20.68276 |
July | 744.00000 | 23.16828 | 49.70748 | -0.8162 | 19.35571 |
August | 744.00000 | 22.75808 | 45.55562 | -0.9899 | 26.15268 |
September | 720.00000 | 21.54113 | 37.34253 | -1.4711 | 49.46450 |
October | 744.00000 | 21.01404 | 27.95428 | -0.5246 | 10.82867 |
November | 720.00000 | 21.00057 | 15.97137 | -0.6344 | 13.48361 |
December | 744.00000 | 20.99895 | 14.95718 | -0.6499 | 13.91806 |
Annual Sum or Average | 8760.00000 | 21.73757 | 28.29466 | -0.7783 | 19.62203 |
Minimum of Months | 672.00000 | 20.98854 | 14.95718 | -1.4711 | 8.59968 |
Maximum of Months | 744.00000 | 23.22209 | 49.70748 | -0.3902 | 49.46450 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.99376 | 13.97082 | -0.6884 | 15.06371 |
February | 672.00000 | 21.00059 | 14.94077 | -0.6555 | 14.13637 |
March | 744.00000 | 21.01156 | 17.13529 | -0.5914 | 12.44014 |
April | 720.00000 | 21.41593 | 21.39136 | -0.4122 | 9.01471 |
May | 744.00000 | 22.26183 | 25.89222 | -1.2214 | 36.75095 |
June | 720.00000 | 23.11494 | 38.15625 | -0.8358 | 20.22890 |
July | 744.00000 | 23.10396 | 46.99434 | -0.7806 | 18.46998 |
August | 744.00000 | 22.59816 | 42.98102 | -0.9925 | 26.73344 |
September | 720.00000 | 21.35994 | 34.99934 | -1.4999 | 51.00142 |
October | 744.00000 | 21.01118 | 25.29261 | -0.5321 | 11.03052 |
November | 720.00000 | 21.00063 | 13.27465 | -0.6860 | 14.95516 |
December | 744.00000 | 21.00068 | 12.30614 | -0.7089 | 15.64780 |
Annual Sum or Average | 8760.00000 | 21.66075 | 25.68421 | -0.8009 | 20.47139 |
Minimum of Months | 672.00000 | 20.99376 | 12.30614 | -1.4999 | 9.01471 |
Maximum of Months | 744.00000 | 23.11494 | 46.99434 | -0.4122 | 51.00142 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.99985 | 12.69225 | -0.6392 | 13.64070 |
February | 672.00000 | 21.00456 | 13.65547 | -0.6199 | 13.15469 |
March | 744.00000 | 21.03737 | 15.76751 | -0.5757 | 12.04167 |
April | 720.00000 | 21.61697 | 19.77307 | -0.3879 | 8.55769 |
May | 744.00000 | 22.55958 | 24.14877 | -1.1792 | 34.42267 |
June | 720.00000 | 23.20597 | 36.56988 | -0.8720 | 21.27450 |
July | 744.00000 | 23.28816 | 45.20505 | -0.7852 | 18.27983 |
August | 744.00000 | 23.06452 | 40.63956 | -0.8962 | 22.34752 |
September | 720.00000 | 22.11539 | 32.24840 | -1.2828 | 39.68295 |
October | 744.00000 | 21.24526 | 23.62960 | -0.4627 | 9.73455 |
November | 720.00000 | 21.00042 | 12.01095 | -0.6337 | 13.47334 |
December | 744.00000 | 21.00012 | 11.00588 | -0.6566 | 14.10623 |
Annual Sum or Average | 8760.00000 | 21.85022 | 24.01690 | -0.7498 | 18.41028 |
Minimum of Months | 672.00000 | 20.99985 | 11.00588 | -1.2828 | 8.55769 |
Maximum of Months | 744.00000 | 23.28816 | 45.20505 | -0.3879 | 39.68295 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 29344882.70 | 8702.43 | 05-JAN-09:04 | 1.70 | 93505573.91 | 0.00 | 0.122850E+09 | 0.01 | 3.19 | 02-JAN-09:04 | 0.00 | 0.00 |
February | 0.254488E+09 | 14143.42 | 08-FEB-16:04 | 37.33 | 0.810909E+09 | 0.00 | 0.106540E+10 | 0.18 | 3.19 | 15-FEB-15:00 | 0.00 | 0.00 |
March | 0.333107E+10 | 28430.72 | 22-MAR-15:01 | 213.03 | 0.106142E+11 | 0.00 | 0.139453E+11 | 0.91 | 3.19 | 21-MAR-08:06 | 0.00 | 0.00 |
April | 0.215652E+11 | 49865.01 | 22-APR-15:03 | 537.50 | 0.686887E+11 | 0.00 | 0.902539E+11 | 2.38 | 3.77 | 22-APR-15:03 | 0.00 | 0.00 |
May | 0.487784E+11 | 79400.03 | 31-MAY-15:03 | 742.33 | 0.154437E+12 | 0.00 | 0.203215E+12 | 3.16 | 4.09 | 10-MAY-15:03 | 0.00 | 0.00 |
June | 0.876661E+11 | 110197.45 | 20-JUN-18:03 | 719.00 | 0.286963E+12 | 0.00 | 0.374629E+12 | 3.20 | 4.08 | 30-JUN-18:03 | 0.00 | 0.00 |
July | 0.990996E+11 | 122075.07 | 29-JUL-15:03 | 744.00 | 0.329041E+12 | 0.00 | 0.428141E+12 | 3.23 | 4.31 | 03-JUL-15:03 | 0.00 | 0.00 |
August | 0.699217E+11 | 103852.21 | 11-AUG-18:03 | 742.67 | 0.227330E+12 | 0.00 | 0.297252E+12 | 3.18 | 4.09 | 26-AUG-15:03 | 0.00 | 0.00 |
September | 0.187577E+11 | 54313.67 | 02-SEP-15:03 | 622.82 | 0.591785E+11 | 0.00 | 0.779362E+11 | 2.75 | 3.83 | 02-SEP-15:03 | 0.00 | 0.00 |
October | 0.353312E+10 | 37153.36 | 03-OCT-15:02 | 241.66 | 0.112564E+11 | 0.00 | 0.147895E+11 | 1.03 | 3.19 | 09-OCT-18:30 | 0.00 | 0.00 |
November | 46433127.00 | 9514.37 | 15-NOV-09:04 | 5.30 | 0.147956E+09 | 0.00 | 0.194389E+09 | 0.02 | 3.19 | 25-NOV-19:04 | 0.00 | 0.00 |
December | 18810348.00 | 9585.94 | 24-DEC-16:04 | 1.16 | 59937959.33 | 0.00 | 78748307.33 | 0.00 | 3.19 | 02-DEC-09:04 | 0.00 | 0.00 |
Annual Sum or Average | 0.353002E+12 | 4608.51 | 0.114862E+13 | 0.00 | 0.150162E+13 | 1.68 | 0.00 | 0.00 | ||||
Minimum of Months | 18810348.00 | 8702.43 | 1.16 | 59937959.33 | 0.00 | 78748307.33 | 0.00 | 3.19 | 0.00 | 0.00 | ||
Maximum of Months | 0.990996E+11 | 122075.07 | 744.00 | 0.329041E+12 | 0.00 | 0.428141E+12 | 3.23 | 4.31 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.775131E+12 | 0.00 | 744.00 | 938714.21 | 12-JAN-09:03 | 0.00 | 47.03 | 82.18 | 2.08 | 0.00 | 0.36 | 1.18 | 12-JAN-09:03 |
February | 0.612265E+12 | 0.00 | 672.00 | 883773.62 | 27-FEB-09:03 | 0.00 | 45.87 | 82.07 | 1.82 | 0.00 | 0.32 | 1.11 | 27-FEB-09:03 |
March | 0.361263E+12 | 0.00 | 744.00 | 781255.58 | 01-MAR-09:03 | 0.00 | 45.03 | 81.96 | 0.92 | 0.00 | 0.17 | 0.98 | 01-MAR-09:03 |
April | 0.927687E+11 | 0.00 | 631.55 | 315578.24 | 03-APR-08:61 | 0.00 | 44.12 | 75.78 | 0.23 | 0.00 | 0.04 | 0.40 | 03-APR-08:61 |
May | 0.493566E+11 | 0.00 | 514.98 | 125559.00 | 19-MAY-07:00 | 0.00 | 30.91 | 63.54 | 0.09 | 0.00 | 0.02 | 0.16 | 19-MAY-07:00 |
June | 0.364046E+11 | 0.00 | 284.85 | 114100.81 | 02-JUN-06:20 | 0.00 | 26.89 | 47.40 | 0.07 | 0.00 | 0.02 | 0.14 | 02-JUN-06:20 |
July | 0.367405E+11 | 0.00 | 294.18 | 127725.82 | 04-JUL-08:04 | 0.00 | 27.29 | 47.76 | 0.06 | 0.00 | 0.02 | 0.16 | 04-JUL-08:04 |
August | 0.547432E+11 | 0.00 | 416.00 | 139165.60 | 29-AUG-08:05 | 0.00 | 28.81 | 56.46 | 0.10 | 0.00 | 0.03 | 0.17 | 29-AUG-08:05 |
September | 0.596773E+11 | 0.00 | 663.90 | 136273.35 | 04-SEP-08:04 | 0.00 | 43.82 | 76.25 | 0.14 | 0.00 | 0.03 | 0.17 | 04-SEP-08:04 |
October | 0.173698E+12 | 0.00 | 742.83 | 308500.13 | 27-OCT-08:03 | 0.00 | 47.96 | 81.26 | 0.44 | 0.00 | 0.08 | 0.39 | 27-OCT-08:03 |
November | 0.710296E+12 | 0.00 | 720.00 | 843159.59 | 29-NOV-09:03 | 0.00 | 46.32 | 82.20 | 1.96 | 0.00 | 0.34 | 1.06 | 29-NOV-09:03 |
December | 0.897946E+12 | 0.00 | 744.00 | 898377.12 | 15-DEC-09:03 | 0.00 | 47.61 | 82.15 | 2.45 | 0.00 | 0.42 | 1.13 | 15-DEC-09:03 |
Annual Sum or Average | 0.386029E+13 | 0.00 | 7172.29 | 0.00 | 40.09 | 71.51 | 0.86 | 0.00 | 0.15 | ||||
Minimum of Months | 0.364046E+11 | 0.00 | 284.85 | 114100.81 | 0.00 | 26.89 | 47.40 | 0.06 | 0.00 | 0.02 | 0.14 | ||
Maximum of Months | 0.897946E+12 | 0.00 | 744.00 | 938714.21 | 0.00 | 47.96 | 82.20 | 2.45 | 0.00 | 0.42 | 1.18 |
Report: DXReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 0.197241E+10 | 0.00 | 744.00 | 0.197241E+10 | -0.0 | 0.00 | 1.00 | 01-MAR-00:05 | 1.00 | 01-MAR-00:05 | 36539.74 | 31-MAR-23:03 | 36539.74 | 31-MAR-23:30 | 0.00 | 31-MAR-23:03 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 0.620987E+11 | 0.00 | 515.10 | 0.620987E+11 | 0.00 | 0.00 | 1.00 | 01-APR-01:07 | 0.00 | 01-APR-00:20 | 50421.70 | 30-APR-23:20 | 50421.70 | 30-APR-23:20 | 0.00 | 01-APR-03:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.714947E+11 | 0.00 | 465.41 | 0.714947E+11 | 0.00 | 0.00 | 1.00 | 01-MAY-03:10 | 0.00 | 01-MAY-00:10 | 58188.26 | 31-MAY-23:05 | 58188.26 | 31-MAY-23:05 | 0.00 | 16-MAY-18:13 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.691695E+11 | 0.00 | 418.00 | 0.691624E+11 | 7151675.65 | 0.00 | 1.00 | 01-JUN-05:15 | 0.00 | 01-JUN-00:05 | 58643.99 | 01-JUN-05:15 | 58643.99 | 01-JUN-06:30 | 5973.25 | 30-JUN-23:05 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.690349E+11 | 0.00 | 417.44 | 0.618016E+11 | 0.723325E+10 | 0.00 | 1.00 | 01-JUL-05:13 | 0.00 | 01-JUL-00:10 | 60476.66 | 01-JUL-05:13 | 53994.40 | 01-JUL-21:50 | 6537.05 | 29-JUL-08:13 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.661186E+11 | 0.00 | 419.95 | 0.626988E+11 | 0.341982E+10 | 0.00 | 1.00 | 01-AUG-04:07 | 0.00 | 01-AUG-00:05 | 56481.89 | 01-AUG-07:00 | 53596.81 | 02-AUG-17:50 | 3251.20 | 02-AUG-17:25 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.602229E+11 | 0.00 | 441.34 | 0.602229E+11 | -0.0 | 0.00 | 1.00 | 01-SEP-03:07 | 0.00 | 01-SEP-00:10 | 45764.68 | 30-SEP-05:15 | 45764.68 | 30-SEP-05:50 | 0.00 | 18-SEP-19:10 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.551998E+11 | 0.00 | 532.63 | 0.551998E+11 | 0.00 | 0.00 | 1.00 | 01-OCT-01:07 | 0.00 | 01-OCT-00:20 | 31633.74 | 31-OCT-05:30 | 31633.74 | 31-OCT-10:00 | 0.00 | 04-OCT-08:40 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.455311E+12 | 0.00 | 3953.87 | 0.444651E+12 | 0.106602E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.714947E+11 | 0.00 | 744.00 | 0.714947E+11 | 0.723325E+10 | 0.00 | 1.00 | 1.00 | 60476.66 | 58643.99 | 6537.05 | 0.00 | 0.00 |
Report: DXReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 0.228861E+10 | 0.00 | 743.50 | 0.228861E+10 | -0.0 | 0.00 | 1.00 | 01-MAR-00:05 | 0.00 | 31-MAR-23:30 | 46231.99 | 31-MAR-23:03 | 46231.99 | 31-MAR-23:03 | 0.00 | 31-MAR-23:15 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 0.358380E+11 | 0.00 | 371.09 | 0.358380E+11 | -0.0 | 0.00 | 1.00 | 01-APR-16:05 | 0.00 | 01-APR-00:10 | 63809.82 | 30-APR-23:03 | 63809.82 | 30-APR-23:03 | 0.00 | 03-APR-16:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.505395E+11 | 0.00 | 361.77 | 0.505395E+11 | 0.00 | 0.00 | 1.00 | 01-MAY-16:10 | 0.00 | 01-MAY-00:05 | 63809.82 | 01-MAY-17:23 | 63809.82 | 01-MAY-20:30 | 0.00 | 03-MAY-19:10 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.565989E+11 | 0.00 | 341.36 | 0.565976E+11 | 1352081.76 | 0.00 | 1.00 | 01-JUN-16:10 | 0.00 | 01-JUN-00:05 | 74221.18 | 01-JUN-16:10 | 74221.18 | 01-JUN-16:10 | 4337.07 | 30-JUN-23:05 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.603495E+11 | 0.00 | 348.01 | 0.540421E+11 | 0.630738E+10 | 0.00 | 1.00 | 01-JUL-16:10 | 0.00 | 01-JUL-00:20 | 76541.78 | 01-JUL-20:10 | 68357.45 | 01-JUL-22:00 | 8252.87 | 31-JUL-18:40 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.565249E+11 | 0.00 | 355.93 | 0.536150E+11 | 0.290995E+10 | 0.00 | 1.00 | 01-AUG-16:10 | 0.00 | 01-AUG-00:05 | 71483.46 | 01-AUG-16:10 | 67850.84 | 02-AUG-17:50 | 4104.15 | 02-AUG-17:35 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.444114E+11 | 0.00 | 372.12 | 0.444114E+11 | -0.0 | 0.00 | 1.00 | 01-SEP-16:10 | 0.00 | 01-SEP-00:10 | 57912.94 | 30-SEP-16:05 | 57912.94 | 30-SEP-16:05 | 0.00 | 19-SEP-21:40 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.318854E+11 | 0.00 | 387.34 | 0.318854E+11 | 0.00 | 0.00 | 1.00 | 01-OCT-16:10 | 0.00 | 01-OCT-00:20 | 40019.83 | 31-OCT-16:40 | 40019.83 | 31-OCT-21:50 | 0.00 | 01-OCT-16:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.338436E+12 | 0.00 | 3281.12 | 0.329218E+12 | 0.921868E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.603495E+11 | 0.00 | 743.50 | 0.565976E+11 | 0.630738E+10 | 0.00 | 1.00 | 0.00 | 76541.78 | 74221.18 | 8252.87 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 |
April | 0.478836E+09 | 0.00 | 11.17 | 0.478836E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21907.64 | 22-APR-16:10 | 21907.64 | 22-APR-16:10 | 0.00 | 0.00 | 0.00 |
May | 0.332680E+11 | 0.00 | 204.33 | 0.332680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 147431.63 | 31-MAY-18:03 | 147431.63 | 31-MAY-18:03 | 0.00 | 0.00 | 0.00 |
June | 0.126537E+12 | 0.00 | 441.17 | 0.125554E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 217466.52 | 29-JUN-20:00 | 217158.33 | 20-JUN-19:10 | 0.00 | 0.00 | 0.00 |
July | 0.159515E+12 | 0.00 | 481.67 | 0.157099E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 244676.48 | 29-JUL-18:03 | 216645.99 | 29-JUL-17:15 | 0.00 | 0.00 | 0.00 |
August | 0.933007E+11 | 0.00 | 354.50 | 0.931520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 205710.39 | 11-AUG-19:10 | 205710.39 | 11-AUG-19:10 | 0.00 | 0.00 | 0.00 |
September | 0.438856E+10 | 0.00 | 55.83 | 0.438856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57277.58 | 02-SEP-18:00 | 57277.58 | 02-SEP-18:00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.417488E+12 | 0.00 | 1548.67 | 0.413940E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.159515E+12 | 0.00 | 481.67 | 0.157099E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 244676.48 | 217158.33 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 |
April | 2616979.37 | 0.00 | 2.17 | 2616979.37 | 0.00 | 0.00 | 0.00 | 0.00 | 594.90 | 22-APR-14:20 | 594.90 | 22-APR-14:20 | 0.00 | 0.00 | 0.00 |
May | 0.187749E+10 | 0.00 | 116.83 | 0.187749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14984.27 | 31-MAY-16:00 | 14984.27 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.875150E+10 | 0.00 | 318.17 | 0.866818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20268.27 | 30-JUN-12:20 | 18265.07 | 30-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.107248E+11 | 0.00 | 351.67 | 0.105096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19576.59 | 03-JUL-15:10 | 19046.08 | 29-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.644682E+10 | 0.00 | 251.67 | 0.640249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17539.91 | 11-AUG-18:02 | 17539.91 | 11-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.192142E+09 | 0.00 | 30.83 | 0.192142E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4990.98 | 07-SEP-16:00 | 4990.98 | 07-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279954E+11 | 0.00 | 1071.33 | 0.276525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.107248E+11 | 0.00 | 351.67 | 0.105096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20268.27 | 19046.08 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3002826.45 | 0.00 | 0.48 | 3002826.45 | 0.00 | 0.00 | 0.00 | 0.00 | 3456.20 | 22-JAN-09:04 | 3456.20 | 22-JAN-09:04 | 0.00 | 0.00 | 0.00 |
February | 10943996.63 | 0.00 | 1.17 | 10705249.52 | 0.00 | 0.00 | 0.00 | 0.00 | 4196.49 | 11-FEB-19:04 | 4196.49 | 11-FEB-19:04 | 0.00 | 0.00 | 0.00 |
March | 0.235378E+09 | 0.00 | 30.10 | 0.231857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13665.12 | 28-MAR-15:02 | 13665.12 | 28-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.298456E+10 | 0.00 | 337.30 | 0.292097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13681.20 | 18-APR-15:02 | 13681.20 | 18-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.534421E+10 | 0.00 | 631.06 | 0.493939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14437.85 | 31-MAY-18:02 | 14437.85 | 31-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.797876E+10 | 0.00 | 668.91 | 0.585427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14672.94 | 22-JUN-18:02 | 14672.94 | 22-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.790830E+10 | 0.00 | 687.31 | 0.492802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14962.95 | 26-JUL-15:01 | 14241.88 | 07-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.586013E+10 | 0.00 | 645.33 | 0.370601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14967.68 | 13-AUG-15:02 | 13969.58 | 17-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.141209E+10 | 0.00 | 275.34 | 0.944702E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13813.49 | 02-SEP-18:02 | 13813.49 | 02-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 77209575.93 | 0.00 | 18.45 | 59470141.29 | 0.00 | 0.00 | 0.00 | 0.00 | 13431.40 | 13-OCT-15:02 | 13431.40 | 13-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 3119513.88 | 0.00 | 0.52 | 3119513.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.83 | 04-NOV-08:04 | 2880.83 | 04-NOV-08:04 | 0.00 | 0.00 | 0.00 |
December | 1837285.95 | 0.00 | 0.24 | 1688269.36 | 0.00 | 0.00 | 0.00 | 0.00 | 3548.55 | 24-DEC-19:04 | 3548.55 | 24-DEC-19:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318195E+11 | 0.00 | 3296.21 | 0.236032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1837285.95 | 0.00 | 0.24 | 1688269.36 | 0.00 | 0.00 | 0.00 | 0.00 | 2880.83 | 2880.83 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.797876E+10 | 0.00 | 687.31 | 0.585427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14967.68 | 14672.94 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2102655.24 | 0.00 | 0.33 | 2102655.24 | 0.00 | 0.00 | 0.00 | 0.00 | 3819.93 | 22-JAN-09:04 | 3819.93 | 22-JAN-09:04 | 0.00 | 0.00 | 0.00 |
February | 7024243.77 | 0.00 | 0.76 | 6896742.40 | 0.00 | 0.00 | 0.00 | 0.00 | 4565.01 | 08-FEB-19:04 | 4565.01 | 08-FEB-19:04 | 0.00 | 0.00 | 0.00 |
March | 31823022.88 | 0.00 | 11.21 | 30988473.96 | 0.00 | 0.00 | 0.00 | 0.00 | 9984.54 | 27-MAR-18:01 | 9984.54 | 27-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.153260E+10 | 0.00 | 200.51 | 0.150840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12283.60 | 28-APR-15:02 | 12283.60 | 28-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.315291E+10 | 0.00 | 480.23 | 0.286982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14150.08 | 09-MAY-20:01 | 14150.08 | 09-MAY-20:01 | 0.00 | 0.00 | 0.00 |
June | 0.539385E+10 | 0.00 | 507.75 | 0.374820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15446.04 | 28-JUN-21:51 | 13650.09 | 26-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.537998E+10 | 0.00 | 520.48 | 0.329496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15953.38 | 06-JUL-17:32 | 15953.38 | 06-JUL-17:32 | 0.00 | 0.00 | 0.00 |
August | 0.321582E+10 | 0.00 | 457.94 | 0.177348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14134.02 | 01-AUG-21:51 | 13010.83 | 02-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.542942E+09 | 0.00 | 141.56 | 0.341978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12677.01 | 02-SEP-19:41 | 12677.01 | 02-SEP-19:41 | 0.00 | 0.00 | 0.00 |
October | 20797425.83 | 0.00 | 4.55 | 16424974.39 | 0.00 | 0.00 | 0.00 | 0.00 | 8895.12 | 03-OCT-15:02 | 8895.12 | 03-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 1226373.41 | 0.00 | 0.29 | 1226373.41 | 0.00 | 0.00 | 0.00 | 0.00 | 3159.45 | 04-NOV-08:04 | 3159.45 | 04-NOV-08:04 | 0.00 | 0.00 | 0.00 |
December | 1391987.19 | 0.00 | 0.21 | 1281709.54 | 0.00 | 0.00 | 0.00 | 0.00 | 3195.98 | 24-DEC-19:04 | 3195.98 | 24-DEC-19:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192825E+11 | 0.00 | 2325.83 | 0.135957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1226373.41 | 0.00 | 0.21 | 1226373.41 | 0.00 | 0.00 | 0.00 | 0.00 | 3159.45 | 3159.45 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.539385E+10 | 0.00 | 520.48 | 0.374820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15953.38 | 15953.38 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.422028E+10 | 0.00 | 83.58 | 0.422028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40899.66 | 31-MAR-13:20 | 40899.66 | 31-MAR-13:20 | 0.00 | 0.00 | 0.00 |
April | 0.351867E+11 | 0.00 | 499.90 | 0.351867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64181.56 | 22-APR-13:20 | 64181.56 | 22-APR-13:20 | 0.00 | 0.00 | 0.00 |
May | 0.455757E+11 | 0.00 | 691.23 | 0.454764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61116.90 | 12-MAY-13:15 | 61116.90 | 12-MAY-13:15 | 0.00 | 0.00 | 0.00 |
June | 0.514512E+11 | 0.00 | 716.58 | 0.325493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56929.73 | 30-JUN-12:30 | 51683.09 | 08-JUN-12:40 | 0.00 | 0.00 | 0.00 |
July | 0.539631E+11 | 0.00 | 739.08 | 0.295432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64460.04 | 23-JUL-13:30 | 57444.72 | 21-JUL-13:05 | 0.00 | 0.00 | 0.00 |
August | 0.499388E+11 | 0.00 | 722.45 | 0.291545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67963.16 | 25-AUG-13:30 | 59864.54 | 31-AUG-13:20 | 0.00 | 0.00 | 0.00 |
September | 0.242808E+11 | 0.00 | 501.96 | 0.198310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61022.06 | 09-SEP-13:10 | 53768.74 | 09-SEP-15:03 | 0.00 | 0.00 | 0.00 |
October | 0.494406E+10 | 0.00 | 144.14 | 0.494406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47516.46 | 03-OCT-12:50 | 47516.46 | 03-OCT-12:50 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269561E+12 | 0.00 | 4098.93 | 0.200905E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.539631E+11 | 0.00 | 739.08 | 0.454764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67963.16 | 64181.56 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 52117284.43 | 0.00 | 1.03 | 52117284.43 | 0.00 | 0.00 | 0.00 | 0.00 | 24147.22 | 09-JAN-09:04 | 24147.22 | 09-JAN-09:04 | 0.00 | 0.00 | 0.00 |
February | 59420822.73 | 0.00 | 1.57 | 59357957.94 | 0.00 | 0.00 | 0.00 | 0.00 | 29692.34 | 11-FEB-09:01 | 29692.34 | 11-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.407010E+09 | 0.00 | 31.22 | 0.407010E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58522.73 | 22-MAR-18:02 | 58522.73 | 22-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.811985E+10 | 0.00 | 270.37 | 0.808531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63911.09 | 30-APR-18:02 | 63911.09 | 30-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.290708E+11 | 0.00 | 484.39 | 0.284965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68395.94 | 31-MAY-15:02 | 68395.94 | 31-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.432211E+11 | 0.00 | 457.63 | 0.365669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74566.11 | 30-JUN-21:51 | 72182.29 | 22-JUN-21:51 | 0.00 | 0.00 | 0.00 |
July | 0.453224E+11 | 0.00 | 471.22 | 0.341936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75214.67 | 18-JUL-21:51 | 69524.51 | 29-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.311017E+11 | 0.00 | 437.79 | 0.228834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73200.55 | 12-AUG-21:52 | 67708.22 | 02-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.114475E+11 | 0.00 | 409.60 | 0.797220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62657.50 | 07-SEP-18:01 | 62657.50 | 07-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.171337E+10 | 0.00 | 115.96 | 0.148887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59758.09 | 04-OCT-18:02 | 59758.09 | 04-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 46571621.01 | 0.00 | 1.05 | 46571621.01 | 0.00 | 0.00 | 0.00 | 0.00 | 27234.34 | 14-NOV-19:04 | 27234.34 | 14-NOV-19:04 | 0.00 | 0.00 | 0.00 |
December | 35155540.58 | 0.00 | 0.87 | 35155540.58 | 0.00 | 0.00 | 0.00 | 0.00 | 31937.80 | 24-DEC-09:01 | 31937.80 | 24-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170597E+12 | 0.00 | 2682.69 | 0.140287E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 35155540.58 | 0.00 | 0.87 | 35155540.58 | 0.00 | 0.00 | 0.00 | 0.00 | 24147.22 | 24147.22 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.453224E+11 | 0.00 | 484.39 | 0.365669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75214.67 | 72182.29 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2806730.70 | 0.00 | 0.40 | 2806730.70 | 0.00 | 0.00 | 0.00 | 0.00 | 3523.67 | 22-JAN-09:04 | 3523.67 | 22-JAN-09:04 | 0.00 | 0.00 | 0.00 |
February | 13590458.02 | 0.00 | 1.86 | 13414853.22 | 0.00 | 0.00 | 0.00 | 0.00 | 4269.17 | 07-FEB-19:04 | 4269.17 | 07-FEB-19:04 | 0.00 | 0.00 | 0.00 |
March | 0.409574E+09 | 0.00 | 84.52 | 0.394685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12918.58 | 20-MAR-15:01 | 12918.58 | 20-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.284730E+10 | 0.00 | 370.52 | 0.275474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12919.95 | 29-APR-18:01 | 12919.95 | 29-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.730143E+10 | 0.00 | 678.87 | 0.687268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13634.72 | 31-MAY-18:02 | 13634.72 | 31-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.901863E+10 | 0.00 | 686.53 | 0.695474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13873.15 | 27-JUN-15:02 | 13856.32 | 22-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.966335E+10 | 0.00 | 712.90 | 0.671080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13818.26 | 26-JUL-15:01 | 13520.60 | 29-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.704057E+10 | 0.00 | 680.00 | 0.478007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13794.95 | 13-AUG-15:02 | 13389.74 | 23-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.196288E+10 | 0.00 | 343.52 | 0.127387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12954.99 | 02-SEP-18:02 | 12954.99 | 02-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.179546E+09 | 0.00 | 51.29 | 0.132343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12789.84 | 04-OCT-08:62 | 12789.84 | 04-OCT-08:62 | 0.00 | 0.00 | 0.00 |
November | 2403495.36 | 0.00 | 0.43 | 2403495.36 | 0.00 | 0.00 | 0.00 | 0.00 | 3059.82 | 04-NOV-08:04 | 3059.82 | 04-NOV-08:04 | 0.00 | 0.00 | 0.00 |
December | 1590622.10 | 0.00 | 0.21 | 1465744.91 | 0.00 | 0.00 | 0.00 | 0.00 | 3363.02 | 24-DEC-09:04 | 3091.45 | 24-DEC-19:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.384437E+11 | 0.00 | 3611.06 | 0.298940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1590622.10 | 0.00 | 0.21 | 1465744.91 | 0.00 | 0.00 | 0.00 | 0.00 | 3059.82 | 3059.82 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.966335E+10 | 0.00 | 712.90 | 0.695474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13873.15 | 13856.32 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1837742.01 | 0.00 | 0.26 | 1837742.01 | 0.00 | 0.00 | 0.00 | 0.00 | 3331.60 | 22-JAN-09:04 | 3331.60 | 22-JAN-09:04 | 0.00 | 0.00 | 0.00 |
February | 7264750.64 | 0.00 | 0.88 | 7178868.61 | 0.00 | 0.00 | 0.00 | 0.00 | 3993.72 | 11-FEB-19:04 | 3993.72 | 11-FEB-19:04 | 0.00 | 0.00 | 0.00 |
March | 0.104630E+09 | 0.00 | 20.74 | 98957766.06 | 0.00 | 0.00 | 0.00 | 0.00 | 10813.64 | 27-MAR-08:61 | 10813.64 | 27-MAR-08:61 | 0.00 | 0.00 | 0.00 |
April | 0.126980E+10 | 0.00 | 233.90 | 0.121190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11714.78 | 28-APR-15:02 | 11714.78 | 28-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.524135E+10 | 0.00 | 580.91 | 0.488245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12471.47 | 14-MAY-20:41 | 12471.47 | 14-MAY-20:41 | 0.00 | 0.00 | 0.00 |
June | 0.677613E+10 | 0.00 | 528.83 | 0.516035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14004.85 | 30-JUN-21:51 | 13592.29 | 29-JUN-08:32 | 0.00 | 0.00 | 0.00 |
July | 0.709816E+10 | 0.00 | 550.17 | 0.491412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15509.45 | 11-JUL-08:22 | 15170.90 | 11-JUL-08:22 | 0.00 | 0.00 | 0.00 |
August | 0.455910E+10 | 0.00 | 529.54 | 0.294840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13415.54 | 12-AUG-21:52 | 12479.30 | 10-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.940911E+09 | 0.00 | 228.08 | 0.578549E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11535.46 | 07-SEP-18:01 | 11535.46 | 07-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 45176043.37 | 0.00 | 14.23 | 32528541.08 | 0.00 | 0.00 | 0.00 | 0.00 | 11138.88 | 04-OCT-08:62 | 11138.88 | 04-OCT-08:62 | 0.00 | 0.00 | 0.00 |
November | 909331.70 | 0.00 | 0.21 | 909331.70 | 0.00 | 0.00 | 0.00 | 0.00 | 3024.12 | 04-NOV-08:04 | 3024.12 | 04-NOV-08:04 | 0.00 | 0.00 | 0.00 |
December | 1229432.66 | 0.00 | 0.19 | 1148899.79 | 0.00 | 0.00 | 0.00 | 0.00 | 3338.62 | 24-DEC-19:04 | 3338.62 | 24-DEC-19:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.260465E+11 | 0.00 | 2687.94 | 0.198383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 909331.70 | 0.00 | 0.19 | 909331.70 | 0.00 | 0.00 | 0.00 | 0.00 | 3024.12 | 3024.12 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.709816E+10 | 0.00 | 580.91 | 0.516035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15509.45 | 15170.90 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 146088.51 | 0.00 | 0.29 | 117842.74 | 0.00 | 0.00 | 0.00 | 0.00 | 291.85 | 22-JAN-09:04 | 216.63 | 20-JAN-09:04 | 0.00 | 0.00 | 0.00 |
February | 1233426.58 | 0.00 | 0.93 | 1125484.95 | 0.00 | 0.00 | 0.00 | 0.00 | 771.48 | 09-FEB-19:04 | 756.63 | 13-FEB-16:04 | 0.00 | 0.00 | 0.00 |
March | 44398467.36 | 0.00 | 22.43 | 43282675.32 | 0.00 | 0.00 | 0.00 | 0.00 | 3547.24 | 27-MAR-18:01 | 3547.24 | 27-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.716641E+09 | 0.00 | 268.18 | 0.699909E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3575.30 | 28-APR-15:02 | 3575.30 | 28-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.124089E+10 | 0.00 | 557.07 | 0.113562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3772.90 | 31-MAY-18:02 | 3772.90 | 31-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.195159E+10 | 0.00 | 653.23 | 0.143864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3845.81 | 24-JUN-15:01 | 3834.13 | 22-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.193161E+10 | 0.00 | 672.64 | 0.121228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3992.73 | 02-JUL-08:61 | 3699.13 | 07-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.138083E+10 | 0.00 | 603.26 | 0.893057E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.21 | 13-AUG-08:61 | 3817.01 | 10-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.303287E+09 | 0.00 | 181.97 | 0.214719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3610.09 | 02-SEP-18:02 | 3610.09 | 02-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 13826183.21 | 0.00 | 11.13 | 9834766.70 | 0.00 | 0.00 | 0.00 | 0.00 | 3341.28 | 13-OCT-15:02 | 3341.28 | 13-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 159680.41 | 0.00 | 0.33 | 159680.41 | 0.00 | 0.00 | 0.00 | 0.00 | 290.20 | 08-NOV-16:04 | 290.20 | 08-NOV-16:04 | 0.00 | 0.00 | 0.00 |
December | 137731.89 | 0.00 | 0.21 | 93612.51 | 0.00 | 0.00 | 0.00 | 0.00 | 560.92 | 24-DEC-09:04 | 299.28 | 24-DEC-09:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.758475E+10 | 0.00 | 2971.69 | 0.564884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 137731.89 | 0.00 | 0.21 | 93612.51 | 0.00 | 0.00 | 0.00 | 0.00 | 290.20 | 216.63 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.195159E+10 | 0.00 | 672.64 | 0.143864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.21 | 3834.13 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 173670.09 | 0.00 | 0.24 | 112167.29 | 0.00 | 0.00 | 0.00 | 0.00 | 370.15 | 22-JAN-09:04 | 294.69 | 21-JAN-09:04 | 0.00 | 0.00 | 0.00 |
February | 796325.23 | 0.00 | 0.74 | 678278.04 | 0.00 | 0.00 | 0.00 | 0.00 | 682.33 | 09-FEB-09:04 | 519.65 | 08-FEB-19:04 | 0.00 | 0.00 | 0.00 |
March | 3408816.74 | 0.00 | 2.37 | 3270803.40 | 0.00 | 0.00 | 0.00 | 0.00 | 1423.93 | 28-MAR-15:03 | 1423.93 | 28-MAR-15:03 | 0.00 | 0.00 | 0.00 |
April | 0.350095E+09 | 0.00 | 152.76 | 0.345432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3175.42 | 28-APR-15:02 | 3175.42 | 28-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.685509E+09 | 0.00 | 414.08 | 0.616840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4148.01 | 14-MAY-20:22 | 4148.01 | 14-MAY-20:22 | 0.00 | 0.00 | 0.00 |
June | 0.134120E+10 | 0.00 | 504.44 | 0.905775E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4353.89 | 28-JUN-21:32 | 3909.15 | 28-JUN-21:32 | 0.00 | 0.00 | 0.00 |
July | 0.132905E+10 | 0.00 | 510.39 | 0.804292E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4176.96 | 24-JUL-21:51 | 4099.24 | 06-JUL-17:32 | 0.00 | 0.00 | 0.00 |
August | 0.729695E+09 | 0.00 | 427.11 | 0.396401E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3893.24 | 02-AUG-21:51 | 3393.88 | 09-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 98911381.87 | 0.00 | 86.12 | 64189273.39 | 0.00 | 0.00 | 0.00 | 0.00 | 3355.38 | 02-SEP-19:41 | 3355.38 | 02-SEP-19:41 | 0.00 | 0.00 | 0.00 |
October | 4516792.09 | 0.00 | 2.38 | 3532129.72 | 0.00 | 0.00 | 0.00 | 0.00 | 1416.78 | 05-OCT-15:03 | 1237.69 | 05-OCT-15:03 | 0.00 | 0.00 | 0.00 |
November | 67155.43 | 0.00 | 0.24 | 67155.43 | 0.00 | 0.00 | 0.00 | 0.00 | 314.48 | 04-NOV-08:04 | 314.48 | 04-NOV-08:04 | 0.00 | 0.00 | 0.00 |
December | 136795.02 | 0.00 | 0.21 | 114374.37 | 0.00 | 0.00 | 0.00 | 0.00 | 526.80 | 24-DEC-09:04 | 349.46 | 24-DEC-19:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.454357E+10 | 0.00 | 2101.09 | 0.314070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 67155.43 | 0.00 | 0.21 | 67155.43 | 0.00 | 0.00 | 0.00 | 0.00 | 314.48 | 294.69 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.134120E+10 | 0.00 | 510.39 | 0.905775E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4353.89 | 4148.01 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 8409693.45 | 0.00 | 1.14 | 8409693.45 | 0.00 | 0.00 | 0.00 | 0.00 | 4983.22 | 22-JAN-19:04 | 4983.22 | 22-JAN-19:04 | 0.00 | 0.00 | 0.00 |
February | 0.279524E+09 | 0.00 | 36.00 | 0.256650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21517.02 | 15-FEB-16:01 | 21517.02 | 15-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.245093E+10 | 0.00 | 162.86 | 0.241849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21526.63 | 11-MAR-16:02 | 21526.63 | 11-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.698283E+10 | 0.00 | 443.87 | 0.682567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21529.82 | 16-APR-15:02 | 21529.82 | 16-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.917696E+10 | 0.00 | 653.16 | 0.840453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22712.64 | 31-MAY-18:02 | 22712.64 | 31-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.111255E+11 | 0.00 | 665.02 | 0.797320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23294.56 | 24-JUN-15:01 | 23082.09 | 22-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.122088E+11 | 0.00 | 689.48 | 0.765276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23223.98 | 13-JUL-18:02 | 23223.98 | 13-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.106150E+11 | 0.00 | 666.75 | 0.708060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22979.15 | 10-AUG-18:02 | 22979.15 | 10-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.459990E+10 | 0.00 | 434.94 | 0.326781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21731.89 | 02-SEP-18:02 | 21731.89 | 02-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.117305E+10 | 0.00 | 128.12 | 0.106236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21527.98 | 04-OCT-15:01 | 21527.98 | 04-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 29641570.50 | 0.00 | 4.82 | 29641570.50 | 0.00 | 0.00 | 0.00 | 0.00 | 20746.62 | 08-NOV-16:01 | 20746.62 | 08-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 3557625.53 | 0.00 | 0.43 | 3364208.95 | 0.00 | 0.00 | 0.00 | 0.00 | 4939.09 | 24-DEC-19:04 | 4273.04 | 25-DEC-09:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.586541E+11 | 0.00 | 3886.60 | 0.449835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3557625.53 | 0.00 | 0.43 | 3364208.95 | 0.00 | 0.00 | 0.00 | 0.00 | 4939.09 | 4273.04 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.122088E+11 | 0.00 | 689.48 | 0.840453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23294.56 | 23223.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 178.45 | 118.74 | 59.72 | 104.39 | 999.67 | 0.00 | 0.00 | 0.00 |
February | 596.34 | 413.90 | 182.44 | 508.29 | 802.61 | 0.00 | 0.00 | 0.00 |
March | 1010.02 | 683.17 | 326.84 | 1008.31 | 614.68 | 0.00 | 0.00 | 0.00 |
April | 1238.14 | 770.52 | 467.62 | 1385.95 | 389.15 | 0.00 | 0.00 | 0.00 |
May | 1022.70 | 531.05 | 491.65 | 1194.76 | 187.18 | 0.00 | 0.00 | 0.00 |
June | 929.31 | 379.54 | 549.77 | 1129.00 | 86.82 | 0.00 | 0.00 | 0.00 |
July | 893.91 | 387.23 | 506.68 | 1114.64 | 90.83 | 0.00 | 0.00 | 0.00 |
August | 931.01 | 513.72 | 417.28 | 1132.04 | 146.58 | 0.00 | 0.00 | 0.00 |
September | 742.98 | 444.06 | 298.93 | 813.28 | 289.94 | 0.00 | 0.00 | 0.00 |
October | 549.94 | 348.73 | 201.21 | 509.31 | 521.20 | 0.00 | 0.00 | 0.00 |
November | 298.10 | 209.99 | 88.10 | 195.30 | 933.49 | 0.00 | 0.00 | 0.00 |
December | 52.71 | 37.13 | 15.58 | 9.31 | 1112.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 703.44 | 402.54 | 300.90 | 759.43 | 513.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.71 | 37.13 | 15.58 | 9.31 | 86.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1238.14 | 770.52 | 549.77 | 1385.95 | 1112.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 502.51 | 334.36 | 168.16 | 291.89 | 2800.06 | 0.00 | 0.00 | 0.00 |
February | 1679.25 | 1165.53 | 513.73 | 1422.82 | 2248.23 | 0.00 | 0.00 | 0.00 |
March | 2844.14 | 1923.77 | 920.37 | 2823.57 | 1733.33 | 0.00 | 0.00 | 0.00 |
April | 3486.53 | 2169.73 | 1316.80 | 3883.00 | 1121.52 | 0.00 | 0.00 | 0.00 |
May | 2879.86 | 1495.40 | 1384.46 | 3338.45 | 556.39 | 0.00 | 0.00 | 0.00 |
June | 2616.88 | 1068.77 | 1548.11 | 3147.40 | 266.89 | 0.00 | 0.00 | 0.00 |
July | 2517.19 | 1090.40 | 1426.79 | 3108.38 | 278.20 | 0.00 | 0.00 | 0.00 |
August | 2621.65 | 1446.61 | 1175.04 | 3163.76 | 442.28 | 0.00 | 0.00 | 0.00 |
September | 2092.19 | 1250.44 | 841.75 | 2273.48 | 840.78 | 0.00 | 0.00 | 0.00 |
October | 1548.61 | 982.01 | 566.60 | 1423.08 | 1472.70 | 0.00 | 0.00 | 0.00 |
November | 839.42 | 591.33 | 248.09 | 545.72 | 2611.52 | 0.00 | 0.00 | 0.00 |
December | 148.43 | 104.57 | 43.86 | 25.90 | 3113.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1980.83 | 1133.52 | 847.32 | 2122.61 | 1453.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 148.43 | 104.57 | 43.86 | 25.90 | 266.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3486.53 | 2169.73 | 1548.11 | 3883.00 | 3113.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 652.79 | 434.35 | 218.44 | 376.96 | 3799.80 | 0.00 | 0.00 | 0.00 |
February | 2181.45 | 1514.09 | 667.36 | 1857.72 | 3044.39 | 0.00 | 0.00 | 0.00 |
March | 3694.70 | 2499.09 | 1195.62 | 3709.52 | 2348.64 | 0.00 | 0.00 | 0.00 |
April | 4529.20 | 2818.61 | 1710.60 | 5104.53 | 1528.19 | 0.00 | 0.00 | 0.00 |
May | 3741.10 | 1942.61 | 1798.50 | 4376.09 | 778.05 | 0.00 | 0.00 | 0.00 |
June | 3399.47 | 1388.39 | 2011.09 | 4118.45 | 381.47 | 0.00 | 0.00 | 0.00 |
July | 3269.98 | 1416.50 | 1853.48 | 4063.97 | 399.21 | 0.00 | 0.00 | 0.00 |
August | 3405.67 | 1879.23 | 1526.44 | 4136.83 | 625.87 | 0.00 | 0.00 | 0.00 |
September | 2717.87 | 1624.39 | 1093.49 | 2968.83 | 1180.64 | 0.00 | 0.00 | 0.00 |
October | 2011.73 | 1275.68 | 736.05 | 1854.61 | 2033.82 | 0.00 | 0.00 | 0.00 |
November | 1090.46 | 768.17 | 322.29 | 707.59 | 3541.46 | 0.00 | 0.00 | 0.00 |
December | 192.82 | 135.84 | 56.98 | 32.69 | 4209.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2573.21 | 1472.50 | 1100.71 | 2778.27 | 1984.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 192.82 | 135.84 | 56.98 | 32.69 | 381.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4529.20 | 2818.61 | 2011.09 | 5104.53 | 4209.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.28 | 23.48 | 11.81 | 21.04 | 200.31 | 0.00 | 0.00 | 0.00 |
February | 117.91 | 81.84 | 36.07 | 102.41 | 160.31 | 0.00 | 0.00 | 0.00 |
March | 199.70 | 135.07 | 64.62 | 201.83 | 123.33 | 0.00 | 0.00 | 0.00 |
April | 244.80 | 152.34 | 92.46 | 275.33 | 78.33 | 0.00 | 0.00 | 0.00 |
May | 202.21 | 105.00 | 97.21 | 236.02 | 37.57 | 0.00 | 0.00 | 0.00 |
June | 183.74 | 75.04 | 108.70 | 222.94 | 16.86 | 0.00 | 0.00 | 0.00 |
July | 176.74 | 76.56 | 100.18 | 220.62 | 17.59 | 0.00 | 0.00 | 0.00 |
August | 184.08 | 101.57 | 82.50 | 224.33 | 28.78 | 0.00 | 0.00 | 0.00 |
September | 146.90 | 87.80 | 59.10 | 161.88 | 57.88 | 0.00 | 0.00 | 0.00 |
October | 108.73 | 68.95 | 39.78 | 102.16 | 103.97 | 0.00 | 0.00 | 0.00 |
November | 58.94 | 41.52 | 17.42 | 39.87 | 185.41 | 0.00 | 0.00 | 0.00 |
December | 10.42 | 7.34 | 3.08 | 1.94 | 222.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.08 | 79.59 | 59.49 | 151.00 | 102.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.42 | 7.34 | 3.08 | 1.94 | 16.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 244.80 | 152.34 | 108.70 | 275.33 | 222.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.28 | 1.24 | 6.03 | 0.00 | 413.00 | 0.00 | 0.00 | 0.00 |
February | 43.35 | 15.12 | 28.23 | 8.66 | 351.84 | 0.00 | 0.00 | 0.00 |
March | 130.37 | 56.31 | 74.05 | 74.77 | 255.54 | 0.00 | 0.00 | 0.00 |
April | 308.78 | 160.28 | 148.51 | 300.98 | 142.20 | 0.00 | 0.00 | 0.00 |
May | 299.56 | 136.64 | 162.92 | 316.68 | 64.43 | 0.00 | 0.00 | 0.00 |
June | 328.13 | 140.06 | 188.07 | 382.02 | 29.08 | 0.00 | 0.00 | 0.00 |
July | 274.11 | 103.55 | 170.56 | 324.19 | 31.11 | 0.00 | 0.00 | 0.00 |
August | 226.16 | 96.14 | 130.02 | 251.09 | 51.78 | 0.00 | 0.00 | 0.00 |
September | 136.09 | 56.74 | 79.36 | 115.86 | 110.85 | 0.00 | 0.00 | 0.00 |
October | 53.38 | 16.00 | 37.38 | 19.62 | 222.48 | 0.00 | 0.00 | 0.00 |
November | 21.59 | 7.93 | 13.66 | 2.23 | 390.94 | 0.00 | 0.00 | 0.00 |
December | 1.91 | 0.20 | 1.72 | 0.00 | 435.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.95 | 65.99 | 86.96 | 150.28 | 207.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.91 | 0.20 | 1.72 | 0.00 | 29.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 328.13 | 160.28 | 188.07 | 382.02 | 435.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.83 | 0.00 | 2.83 | 0.00 | 222.27 | 0.00 | 0.00 | 0.00 |
February | 12.51 | 0.00 | 12.51 | 0.00 | 197.67 | 0.00 | 0.00 | 0.00 |
March | 33.50 | 0.01 | 33.49 | 3.08 | 146.69 | 0.00 | 0.00 | 0.00 |
April | 61.18 | 1.76 | 59.42 | 25.67 | 77.27 | 0.00 | 0.00 | 0.00 |
May | 93.56 | 15.03 | 78.53 | 76.96 | 30.23 | 0.00 | 0.00 | 0.00 |
June | 121.11 | 26.89 | 94.22 | 125.37 | 12.51 | 0.00 | 0.00 | 0.00 |
July | 102.40 | 17.14 | 85.27 | 110.28 | 14.93 | 0.00 | 0.00 | 0.00 |
August | 66.00 | 3.97 | 62.03 | 58.58 | 27.07 | 0.00 | 0.00 | 0.00 |
September | 36.38 | 0.12 | 36.26 | 15.83 | 60.80 | 0.00 | 0.00 | 0.00 |
October | 17.60 | 0.00 | 17.60 | 1.48 | 123.64 | 0.00 | 0.00 | 0.00 |
November | 5.46 | 0.00 | 5.46 | 0.00 | 216.04 | 0.00 | 0.00 | 0.00 |
December | 0.86 | 0.00 | 0.86 | 0.00 | 232.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.28 | 5.43 | 40.85 | 34.98 | 113.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.86 | 0.00 | 0.86 | 0.00 | 12.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.11 | 26.89 | 94.22 | 125.37 | 232.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.28 | 1.24 | 6.03 | 0.00 | 413.03 | 0.00 | 0.00 | 0.00 |
February | 43.35 | 15.12 | 28.23 | 9.23 | 350.99 | 0.00 | 0.00 | 0.00 |
March | 130.37 | 56.31 | 74.05 | 77.81 | 252.68 | 0.00 | 0.00 | 0.00 |
April | 308.78 | 160.28 | 148.51 | 306.64 | 140.23 | 0.00 | 0.00 | 0.00 |
May | 299.56 | 136.64 | 162.92 | 316.90 | 64.20 | 0.00 | 0.00 | 0.00 |
June | 328.13 | 140.06 | 188.07 | 376.36 | 29.68 | 0.00 | 0.00 | 0.00 |
July | 274.11 | 103.55 | 170.56 | 320.59 | 32.09 | 0.00 | 0.00 | 0.00 |
August | 226.16 | 96.14 | 130.02 | 250.41 | 53.04 | 0.00 | 0.00 | 0.00 |
September | 136.09 | 56.74 | 79.36 | 118.70 | 109.37 | 0.00 | 0.00 | 0.00 |
October | 53.38 | 16.00 | 37.38 | 20.98 | 220.85 | 0.00 | 0.00 | 0.00 |
November | 21.59 | 7.93 | 13.66 | 2.36 | 390.73 | 0.00 | 0.00 | 0.00 |
December | 1.91 | 0.20 | 1.72 | 0.00 | 435.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.95 | 65.99 | 86.96 | 150.60 | 206.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.91 | 0.20 | 1.72 | 0.00 | 29.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 328.13 | 160.28 | 188.07 | 376.36 | 435.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.22 | 18.78 | 9.44 | 18.06 | 141.55 | 0.00 | 0.00 | 0.00 |
February | 94.31 | 65.46 | 28.85 | 83.73 | 116.77 | 0.00 | 0.00 | 0.00 |
March | 159.73 | 108.04 | 51.69 | 156.20 | 106.74 | 0.00 | 0.00 | 0.00 |
April | 195.80 | 121.85 | 73.95 | 210.57 | 78.88 | 0.00 | 0.00 | 0.00 |
May | 161.73 | 83.98 | 77.75 | 178.42 | 43.34 | 0.00 | 0.00 | 0.00 |
June | 146.96 | 60.02 | 86.94 | 166.32 | 23.28 | 0.00 | 0.00 | 0.00 |
July | 141.37 | 61.24 | 80.13 | 164.60 | 24.21 | 0.00 | 0.00 | 0.00 |
August | 147.23 | 81.24 | 65.99 | 169.20 | 35.98 | 0.00 | 0.00 | 0.00 |
September | 117.50 | 70.22 | 47.27 | 120.34 | 63.44 | 0.00 | 0.00 | 0.00 |
October | 86.97 | 55.15 | 31.82 | 76.01 | 95.40 | 0.00 | 0.00 | 0.00 |
November | 47.14 | 33.21 | 13.93 | 33.87 | 131.61 | 0.00 | 0.00 | 0.00 |
December | 8.34 | 5.87 | 2.46 | 1.83 | 157.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 111.24 | 63.66 | 47.59 | 114.99 | 84.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.34 | 5.87 | 2.46 | 1.83 | 23.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 195.80 | 121.85 | 86.94 | 210.57 | 157.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.26 | 0.00 | 2.26 | 0.00 | 182.65 | 0.00 | 0.00 | 0.00 |
February | 10.01 | 0.00 | 10.01 | 0.00 | 162.97 | 0.00 | 0.00 | 0.00 |
March | 26.80 | 0.00 | 26.80 | 2.08 | 120.94 | 0.00 | 0.00 | 0.00 |
April | 48.95 | 1.41 | 47.54 | 21.12 | 62.02 | 0.00 | 0.00 | 0.00 |
May | 74.86 | 12.02 | 62.83 | 64.28 | 23.67 | 0.00 | 0.00 | 0.00 |
June | 96.90 | 21.52 | 75.38 | 104.81 | 9.41 | 0.00 | 0.00 | 0.00 |
July | 81.93 | 13.71 | 68.22 | 91.49 | 11.34 | 0.00 | 0.00 | 0.00 |
August | 52.81 | 3.18 | 49.63 | 49.09 | 20.82 | 0.00 | 0.00 | 0.00 |
September | 29.11 | 0.10 | 29.01 | 12.49 | 49.66 | 0.00 | 0.00 | 0.00 |
October | 14.09 | 0.00 | 14.09 | 0.96 | 102.99 | 0.00 | 0.00 | 0.00 |
November | 4.37 | 0.00 | 4.37 | 0.00 | 177.79 | 0.00 | 0.00 | 0.00 |
December | 0.69 | 0.00 | 0.69 | 0.00 | 190.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.03 | 4.35 | 32.68 | 29.03 | 92.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.69 | 0.00 | 0.69 | 0.00 | 9.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 96.90 | 21.52 | 75.38 | 104.81 | 190.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.66 | 5.81 | 9.85 | 2.03 | 403.48 | 0.00 | 0.00 | 0.00 |
February | 81.17 | 38.93 | 42.24 | 42.80 | 334.73 | 0.00 | 0.00 | 0.00 |
March | 227.53 | 115.19 | 112.35 | 195.50 | 249.16 | 0.00 | 0.00 | 0.00 |
April | 302.68 | 153.28 | 149.40 | 284.46 | 133.26 | 0.00 | 0.00 | 0.00 |
May | 440.73 | 248.70 | 192.03 | 500.44 | 60.27 | 0.00 | 0.00 | 0.00 |
June | 403.68 | 188.47 | 215.21 | 480.47 | 25.10 | 0.00 | 0.00 | 0.00 |
July | 384.47 | 186.89 | 197.57 | 470.00 | 28.38 | 0.00 | 0.00 | 0.00 |
August | 308.91 | 151.33 | 157.58 | 359.16 | 49.05 | 0.00 | 0.00 | 0.00 |
September | 193.37 | 87.44 | 105.93 | 187.82 | 107.48 | 0.00 | 0.00 | 0.00 |
October | 104.76 | 42.45 | 62.31 | 77.28 | 212.45 | 0.00 | 0.00 | 0.00 |
November | 21.73 | 7.91 | 13.83 | 1.64 | 389.82 | 0.00 | 0.00 | 0.00 |
December | 3.10 | 0.74 | 2.36 | 0.00 | 433.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 208.10 | 102.71 | 105.40 | 217.99 | 201.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3.10 | 0.74 | 2.36 | 0.00 | 25.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 440.73 | 248.70 | 215.21 | 500.44 | 433.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.28 | 23.48 | 11.81 | 20.96 | 200.36 | 0.00 | 0.00 | 0.00 |
February | 117.91 | 81.84 | 36.07 | 101.80 | 160.51 | 0.00 | 0.00 | 0.00 |
March | 199.70 | 135.07 | 64.62 | 199.50 | 123.95 | 0.00 | 0.00 | 0.00 |
April | 244.80 | 152.34 | 92.46 | 274.27 | 77.94 | 0.00 | 0.00 | 0.00 |
May | 202.21 | 105.00 | 97.21 | 234.15 | 37.12 | 0.00 | 0.00 | 0.00 |
June | 183.74 | 75.04 | 108.70 | 222.02 | 16.02 | 0.00 | 0.00 | 0.00 |
July | 176.74 | 76.56 | 100.18 | 219.33 | 17.17 | 0.00 | 0.00 | 0.00 |
August | 184.08 | 101.57 | 82.50 | 223.21 | 28.71 | 0.00 | 0.00 | 0.00 |
September | 146.90 | 87.80 | 59.10 | 160.61 | 58.15 | 0.00 | 0.00 | 0.00 |
October | 108.73 | 68.95 | 39.78 | 101.06 | 104.38 | 0.00 | 0.00 | 0.00 |
November | 58.94 | 41.52 | 17.42 | 39.82 | 185.40 | 0.00 | 0.00 | 0.00 |
December | 10.42 | 7.34 | 3.08 | 1.94 | 222.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.08 | 79.59 | 59.49 | 150.02 | 102.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.42 | 7.34 | 3.08 | 1.94 | 16.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 244.80 | 152.34 | 108.70 | 274.27 | 222.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.83 | 0.00 | 2.83 | 0.00 | 222.07 | 0.00 | 0.00 | 0.00 |
February | 12.51 | 0.00 | 12.51 | 0.00 | 197.45 | 0.00 | 0.00 | 0.00 |
March | 33.50 | 0.01 | 33.49 | 2.54 | 148.28 | 0.00 | 0.00 | 0.00 |
April | 61.18 | 1.76 | 59.42 | 24.41 | 77.27 | 0.00 | 0.00 | 0.00 |
May | 93.56 | 15.03 | 78.53 | 74.93 | 30.05 | 0.00 | 0.00 | 0.00 |
June | 121.11 | 26.89 | 94.22 | 125.48 | 12.22 | 0.00 | 0.00 | 0.00 |
July | 102.40 | 17.14 | 85.27 | 108.69 | 14.79 | 0.00 | 0.00 | 0.00 |
August | 66.00 | 3.97 | 62.03 | 57.52 | 26.81 | 0.00 | 0.00 | 0.00 |
September | 36.38 | 0.12 | 36.26 | 14.65 | 61.49 | 0.00 | 0.00 | 0.00 |
October | 17.60 | 0.00 | 17.60 | 1.23 | 124.28 | 0.00 | 0.00 | 0.00 |
November | 5.46 | 0.00 | 5.46 | 0.00 | 216.08 | 0.00 | 0.00 | 0.00 |
December | 0.86 | 0.00 | 0.86 | 0.00 | 232.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.28 | 5.43 | 40.85 | 34.32 | 113.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.86 | 0.00 | 0.86 | 0.00 | 12.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.11 | 26.89 | 94.22 | 125.48 | 232.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.66 | 5.81 | 9.85 | 2.08 | 403.03 | 0.00 | 0.00 | 0.00 |
February | 81.17 | 38.93 | 42.24 | 43.43 | 332.72 | 0.00 | 0.00 | 0.00 |
March | 227.53 | 115.19 | 112.35 | 197.83 | 244.71 | 0.00 | 0.00 | 0.00 |
April | 302.68 | 153.28 | 149.40 | 288.72 | 130.76 | 0.00 | 0.00 | 0.00 |
May | 440.73 | 248.70 | 192.03 | 501.68 | 60.54 | 0.00 | 0.00 | 0.00 |
June | 403.68 | 188.47 | 215.21 | 478.00 | 26.70 | 0.00 | 0.00 | 0.00 |
July | 384.47 | 186.89 | 197.57 | 466.90 | 30.08 | 0.00 | 0.00 | 0.00 |
August | 308.91 | 151.33 | 157.58 | 359.63 | 50.28 | 0.00 | 0.00 | 0.00 |
September | 193.37 | 87.44 | 105.93 | 189.95 | 105.84 | 0.00 | 0.00 | 0.00 |
October | 104.76 | 42.45 | 62.31 | 78.49 | 210.08 | 0.00 | 0.00 | 0.00 |
November | 21.73 | 7.91 | 13.83 | 1.68 | 389.52 | 0.00 | 0.00 | 0.00 |
December | 3.10 | 0.74 | 2.36 | 0.00 | 432.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 208.10 | 102.71 | 105.40 | 218.55 | 200.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3.10 | 0.74 | 2.36 | 0.00 | 26.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 440.73 | 248.70 | 215.21 | 501.68 | 432.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3.58 | 0.00 | 3.58 | 0.00 | 294.87 | 0.00 | 0.00 | 0.00 |
February | 15.84 | 0.00 | 15.84 | 0.00 | 263.64 | 0.00 | 0.00 | 0.00 |
March | 42.42 | 0.01 | 42.42 | 3.04 | 196.02 | 0.00 | 0.00 | 0.00 |
April | 77.48 | 2.22 | 75.25 | 31.51 | 101.89 | 0.00 | 0.00 | 0.00 |
May | 118.49 | 19.03 | 99.45 | 97.71 | 40.88 | 0.00 | 0.00 | 0.00 |
June | 153.38 | 34.06 | 119.32 | 160.59 | 17.54 | 0.00 | 0.00 | 0.00 |
July | 129.69 | 21.70 | 107.98 | 140.14 | 20.95 | 0.00 | 0.00 | 0.00 |
August | 83.58 | 5.03 | 78.55 | 74.08 | 36.85 | 0.00 | 0.00 | 0.00 |
September | 46.07 | 0.15 | 45.92 | 18.95 | 81.63 | 0.00 | 0.00 | 0.00 |
October | 22.30 | 0.00 | 22.30 | 1.50 | 166.11 | 0.00 | 0.00 | 0.00 |
November | 6.92 | 0.00 | 6.92 | 0.00 | 287.23 | 0.00 | 0.00 | 0.00 |
December | 1.09 | 0.00 | 1.09 | 0.00 | 308.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.61 | 6.88 | 51.73 | 44.22 | 150.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.09 | 0.00 | 1.09 | 0.00 | 17.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.38 | 34.06 | 119.32 | 160.59 | 308.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.32 | 0.00 | 1.32 | 0.00 | 108.69 | 0.00 | 0.00 | 0.00 |
February | 5.84 | 0.00 | 5.84 | 0.00 | 97.19 | 0.00 | 0.00 | 0.00 |
March | 15.64 | 0.00 | 15.64 | 1.12 | 72.26 | 0.00 | 0.00 | 0.00 |
April | 28.56 | 0.82 | 27.74 | 11.62 | 37.56 | 0.00 | 0.00 | 0.00 |
May | 43.68 | 7.02 | 36.66 | 36.02 | 15.07 | 0.00 | 0.00 | 0.00 |
June | 56.54 | 12.56 | 43.99 | 59.20 | 6.47 | 0.00 | 0.00 | 0.00 |
July | 47.81 | 8.00 | 39.81 | 51.66 | 7.72 | 0.00 | 0.00 | 0.00 |
August | 30.81 | 1.85 | 28.96 | 27.31 | 13.59 | 0.00 | 0.00 | 0.00 |
September | 16.98 | 0.06 | 16.93 | 6.99 | 30.09 | 0.00 | 0.00 | 0.00 |
October | 8.22 | 0.00 | 8.22 | 0.55 | 61.24 | 0.00 | 0.00 | 0.00 |
November | 2.55 | 0.00 | 2.55 | 0.00 | 105.88 | 0.00 | 0.00 | 0.00 |
December | 0.40 | 0.00 | 0.40 | 0.00 | 113.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.61 | 2.54 | 19.07 | 16.30 | 55.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.40 | 0.00 | 0.40 | 0.00 | 6.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 56.54 | 12.56 | 43.99 | 59.20 | 113.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.46 | 10.95 | 5.51 | 9.40 | 97.79 | 0.00 | 0.00 | 0.00 |
February | 55.01 | 38.18 | 16.83 | 46.88 | 77.85 | 0.00 | 0.00 | 0.00 |
March | 93.18 | 63.03 | 30.15 | 93.79 | 59.29 | 0.00 | 0.00 | 0.00 |
April | 114.22 | 71.08 | 43.14 | 129.48 | 37.42 | 0.00 | 0.00 | 0.00 |
May | 94.35 | 48.99 | 45.36 | 110.58 | 19.01 | 0.00 | 0.00 | 0.00 |
June | 85.73 | 35.01 | 50.72 | 103.64 | 9.41 | 0.00 | 0.00 | 0.00 |
July | 82.47 | 35.72 | 46.74 | 102.51 | 9.78 | 0.00 | 0.00 | 0.00 |
August | 85.89 | 47.39 | 38.50 | 104.81 | 15.07 | 0.00 | 0.00 | 0.00 |
September | 68.54 | 40.97 | 27.58 | 75.84 | 28.14 | 0.00 | 0.00 | 0.00 |
October | 50.73 | 32.17 | 18.56 | 47.14 | 50.50 | 0.00 | 0.00 | 0.00 |
November | 27.50 | 19.37 | 8.13 | 17.85 | 90.26 | 0.00 | 0.00 | 0.00 |
December | 4.86 | 3.43 | 1.44 | 0.81 | 108.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 64.90 | 37.14 | 27.76 | 70.29 | 50.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.86 | 3.43 | 1.44 | 0.81 | 9.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 114.22 | 71.08 | 50.72 | 129.48 | 108.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 44.68 | 29.73 | 14.95 | 25.52 | 265.41 | 0.00 | 0.00 | 0.00 |
February | 149.32 | 103.64 | 45.68 | 127.23 | 211.29 | 0.00 | 0.00 | 0.00 |
March | 252.91 | 171.06 | 81.84 | 254.57 | 160.93 | 0.00 | 0.00 | 0.00 |
April | 310.03 | 192.94 | 117.09 | 351.43 | 101.58 | 0.00 | 0.00 | 0.00 |
May | 256.08 | 132.97 | 123.11 | 300.14 | 51.60 | 0.00 | 0.00 | 0.00 |
June | 232.70 | 95.04 | 137.66 | 281.30 | 25.55 | 0.00 | 0.00 | 0.00 |
July | 223.83 | 96.96 | 126.87 | 278.25 | 26.54 | 0.00 | 0.00 | 0.00 |
August | 233.12 | 128.63 | 104.49 | 284.47 | 40.89 | 0.00 | 0.00 | 0.00 |
September | 186.04 | 111.19 | 74.85 | 205.84 | 76.37 | 0.00 | 0.00 | 0.00 |
October | 137.70 | 87.32 | 50.38 | 127.94 | 137.07 | 0.00 | 0.00 | 0.00 |
November | 74.64 | 52.58 | 22.06 | 48.46 | 244.98 | 0.00 | 0.00 | 0.00 |
December | 13.20 | 9.30 | 3.90 | 2.19 | 294.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 176.14 | 100.79 | 75.34 | 190.79 | 136.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.20 | 9.30 | 3.90 | 2.19 | 25.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 310.03 | 192.94 | 137.66 | 351.43 | 294.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.28 | 23.48 | 11.81 | 21.15 | 198.97 | 0.00 | 0.00 | 0.00 |
February | 117.91 | 81.84 | 36.07 | 102.88 | 159.14 | 0.00 | 0.00 | 0.00 |
March | 199.70 | 135.07 | 64.62 | 202.22 | 122.63 | 0.00 | 0.00 | 0.00 |
April | 244.80 | 152.34 | 92.46 | 274.85 | 77.97 | 0.00 | 0.00 | 0.00 |
May | 202.21 | 105.00 | 97.21 | 235.26 | 37.24 | 0.00 | 0.00 | 0.00 |
June | 183.74 | 75.04 | 108.70 | 222.04 | 16.63 | 0.00 | 0.00 | 0.00 |
July | 176.74 | 76.56 | 100.18 | 219.82 | 17.34 | 0.00 | 0.00 | 0.00 |
August | 184.08 | 101.57 | 82.50 | 223.75 | 28.43 | 0.00 | 0.00 | 0.00 |
September | 146.90 | 87.80 | 59.10 | 161.98 | 57.22 | 0.00 | 0.00 | 0.00 |
October | 108.73 | 68.95 | 39.78 | 102.55 | 103.17 | 0.00 | 0.00 | 0.00 |
November | 58.94 | 41.52 | 17.42 | 40.22 | 183.63 | 0.00 | 0.00 | 0.00 |
December | 10.42 | 7.34 | 3.08 | 1.97 | 220.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.08 | 79.59 | 59.49 | 150.85 | 101.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.42 | 7.34 | 3.08 | 1.97 | 16.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 244.80 | 152.34 | 108.70 | 274.85 | 220.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.28 | 1.24 | 6.03 | 0.00 | 410.27 | 0.00 | 0.00 | 0.00 |
February | 43.35 | 15.12 | 28.23 | 8.91 | 348.96 | 0.00 | 0.00 | 0.00 |
March | 130.37 | 56.31 | 74.05 | 75.22 | 253.56 | 0.00 | 0.00 | 0.00 |
April | 308.78 | 160.28 | 148.51 | 300.03 | 141.32 | 0.00 | 0.00 | 0.00 |
May | 299.56 | 136.64 | 162.92 | 315.62 | 63.77 | 0.00 | 0.00 | 0.00 |
June | 328.13 | 140.06 | 188.07 | 380.52 | 28.63 | 0.00 | 0.00 | 0.00 |
July | 274.11 | 103.55 | 170.56 | 322.95 | 30.62 | 0.00 | 0.00 | 0.00 |
August | 226.16 | 96.14 | 130.02 | 250.26 | 51.06 | 0.00 | 0.00 | 0.00 |
September | 136.09 | 56.74 | 79.36 | 116.13 | 109.36 | 0.00 | 0.00 | 0.00 |
October | 53.38 | 16.00 | 37.38 | 20.06 | 220.41 | 0.00 | 0.00 | 0.00 |
November | 21.59 | 7.93 | 13.66 | 2.33 | 387.00 | 0.00 | 0.00 | 0.00 |
December | 1.91 | 0.20 | 1.72 | 0.00 | 432.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.95 | 65.99 | 86.96 | 149.94 | 205.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.91 | 0.20 | 1.72 | 0.00 | 28.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 328.13 | 160.28 | 188.07 | 380.52 | 432.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.83 | 0.00 | 2.83 | 0.00 | 220.91 | 0.00 | 0.00 | 0.00 |
February | 12.51 | 0.00 | 12.51 | 0.00 | 196.32 | 0.00 | 0.00 | 0.00 |
March | 33.50 | 0.01 | 33.49 | 3.22 | 145.78 | 0.00 | 0.00 | 0.00 |
April | 61.18 | 1.76 | 59.42 | 25.99 | 76.81 | 0.00 | 0.00 | 0.00 |
May | 93.56 | 15.03 | 78.53 | 76.75 | 30.12 | 0.00 | 0.00 | 0.00 |
June | 121.11 | 26.89 | 94.22 | 124.34 | 12.59 | 0.00 | 0.00 | 0.00 |
July | 102.40 | 17.14 | 85.27 | 109.55 | 14.98 | 0.00 | 0.00 | 0.00 |
August | 66.00 | 3.97 | 62.03 | 58.40 | 27.04 | 0.00 | 0.00 | 0.00 |
September | 36.38 | 0.12 | 36.26 | 16.28 | 59.83 | 0.00 | 0.00 | 0.00 |
October | 17.60 | 0.00 | 17.60 | 1.63 | 122.61 | 0.00 | 0.00 | 0.00 |
November | 5.46 | 0.00 | 5.46 | 0.00 | 214.03 | 0.00 | 0.00 | 0.00 |
December | 0.86 | 0.00 | 0.86 | 0.00 | 231.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.28 | 5.43 | 40.85 | 34.89 | 112.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.86 | 0.00 | 0.86 | 0.00 | 12.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.11 | 26.89 | 94.22 | 124.34 | 231.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.28 | 1.24 | 6.03 | 0.00 | 410.33 | 0.00 | 0.00 | 0.00 |
February | 43.35 | 15.12 | 28.23 | 9.36 | 348.47 | 0.00 | 0.00 | 0.00 |
March | 130.37 | 56.31 | 74.05 | 78.15 | 251.19 | 0.00 | 0.00 | 0.00 |
April | 308.78 | 160.28 | 148.51 | 306.30 | 139.26 | 0.00 | 0.00 | 0.00 |
May | 299.56 | 136.64 | 162.92 | 315.74 | 63.69 | 0.00 | 0.00 | 0.00 |
June | 328.13 | 140.06 | 188.07 | 373.81 | 29.73 | 0.00 | 0.00 | 0.00 |
July | 274.11 | 103.55 | 170.56 | 318.66 | 32.03 | 0.00 | 0.00 | 0.00 |
August | 226.16 | 96.14 | 130.02 | 249.31 | 52.74 | 0.00 | 0.00 | 0.00 |
September | 136.09 | 56.74 | 79.36 | 119.45 | 107.68 | 0.00 | 0.00 | 0.00 |
October | 53.38 | 16.00 | 37.38 | 21.43 | 219.06 | 0.00 | 0.00 | 0.00 |
November | 21.59 | 7.93 | 13.66 | 2.44 | 386.87 | 0.00 | 0.00 | 0.00 |
December | 1.91 | 0.20 | 1.72 | 0.00 | 432.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.95 | 65.99 | 86.96 | 150.15 | 205.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.91 | 0.20 | 1.72 | 0.00 | 29.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 328.13 | 160.28 | 188.07 | 373.81 | 432.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.75 | 34.43 | 17.32 | 30.01 | 296.28 | 0.00 | 0.00 | 0.00 |
February | 172.92 | 120.02 | 52.90 | 146.02 | 238.74 | 0.00 | 0.00 | 0.00 |
March | 292.88 | 198.10 | 94.78 | 289.42 | 184.75 | 0.00 | 0.00 | 0.00 |
April | 359.03 | 223.43 | 135.60 | 399.04 | 115.93 | 0.00 | 0.00 | 0.00 |
May | 296.56 | 153.99 | 142.57 | 343.81 | 54.65 | 0.00 | 0.00 | 0.00 |
June | 269.47 | 110.06 | 159.42 | 326.36 | 23.94 | 0.00 | 0.00 | 0.00 |
July | 259.21 | 112.28 | 146.92 | 322.54 | 25.16 | 0.00 | 0.00 | 0.00 |
August | 269.97 | 148.97 | 121.00 | 326.99 | 41.79 | 0.00 | 0.00 | 0.00 |
September | 215.44 | 128.76 | 86.68 | 233.97 | 86.22 | 0.00 | 0.00 | 0.00 |
October | 159.47 | 101.12 | 58.35 | 145.61 | 155.80 | 0.00 | 0.00 | 0.00 |
November | 86.44 | 60.89 | 25.55 | 57.01 | 273.71 | 0.00 | 0.00 | 0.00 |
December | 15.28 | 10.77 | 4.52 | 2.76 | 328.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 203.98 | 116.72 | 87.25 | 218.84 | 151.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.28 | 10.77 | 4.52 | 2.76 | 23.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 359.03 | 223.43 | 159.42 | 399.04 | 328.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.80 | 0.00 | 19.80 | 0.00 | 1636.66 | 0.00 | 0.00 | 0.00 |
February | 87.53 | 0.00 | 87.53 | 0.00 | 1467.88 | 0.00 | 0.00 | 0.00 |
March | 234.48 | 0.04 | 234.44 | 13.56 | 1118.38 | 0.00 | 0.00 | 0.00 |
April | 428.23 | 12.29 | 415.94 | 159.47 | 596.55 | 0.00 | 0.00 | 0.00 |
May | 654.88 | 105.19 | 549.69 | 518.68 | 232.22 | 0.00 | 0.00 | 0.00 |
June | 847.73 | 188.24 | 659.49 | 879.34 | 96.55 | 0.00 | 0.00 | 0.00 |
July | 716.79 | 119.95 | 596.84 | 766.27 | 115.15 | 0.00 | 0.00 | 0.00 |
August | 461.98 | 27.81 | 434.18 | 397.04 | 206.90 | 0.00 | 0.00 | 0.00 |
September | 254.65 | 0.84 | 253.81 | 92.12 | 486.43 | 0.00 | 0.00 | 0.00 |
October | 123.23 | 0.00 | 123.23 | 5.39 | 972.29 | 0.00 | 0.00 | 0.00 |
November | 38.24 | 0.00 | 38.24 | 0.00 | 1589.03 | 0.00 | 0.00 | 0.00 |
December | 6.01 | 0.00 | 6.01 | 0.00 | 1698.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 323.97 | 38.04 | 285.93 | 237.42 | 848.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.01 | 0.00 | 6.01 | 0.00 | 96.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 847.73 | 188.24 | 659.49 | 879.34 | 1698.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.80 | 0.00 | 19.80 | 0.00 | 1662.73 | 0.00 | 0.00 | 0.00 |
February | 87.53 | 0.00 | 87.53 | 0.00 | 1492.91 | 0.00 | 0.00 | 0.00 |
March | 234.48 | 0.04 | 234.44 | 11.82 | 1141.51 | 0.00 | 0.00 | 0.00 |
April | 428.23 | 12.29 | 415.94 | 151.55 | 609.82 | 0.00 | 0.00 | 0.00 |
May | 654.88 | 105.19 | 549.69 | 507.64 | 236.93 | 0.00 | 0.00 | 0.00 |
June | 847.73 | 188.24 | 659.49 | 870.37 | 99.06 | 0.00 | 0.00 | 0.00 |
July | 716.79 | 119.95 | 596.84 | 757.93 | 118.15 | 0.00 | 0.00 | 0.00 |
August | 461.98 | 27.81 | 434.18 | 388.48 | 212.18 | 0.00 | 0.00 | 0.00 |
September | 254.65 | 0.84 | 253.81 | 86.14 | 500.32 | 0.00 | 0.00 | 0.00 |
October | 123.23 | 0.00 | 123.23 | 4.30 | 995.83 | 0.00 | 0.00 | 0.00 |
November | 38.24 | 0.00 | 38.24 | 0.00 | 1615.24 | 0.00 | 0.00 | 0.00 |
December | 6.01 | 0.00 | 6.01 | 0.00 | 1723.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 323.97 | 38.04 | 285.93 | 232.92 | 864.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.01 | 0.00 | 6.01 | 0.00 | 99.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 847.73 | 188.24 | 659.49 | 870.37 | 1723.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.83 | 0.00 | 2.83 | 0.00 | 189.85 | 0.00 | 0.00 | 0.00 |
February | 12.51 | 0.00 | 12.51 | 0.01 | 166.19 | 0.00 | 0.00 | 0.00 |
March | 33.50 | 0.01 | 33.49 | 8.41 | 123.46 | 0.00 | 0.00 | 0.00 |
April | 61.18 | 1.76 | 59.42 | 49.09 | 68.20 | 0.00 | 0.00 | 0.00 |
May | 93.56 | 15.03 | 78.53 | 114.59 | 29.03 | 0.00 | 0.00 | 0.00 |
June | 121.11 | 26.89 | 94.22 | 171.68 | 12.62 | 0.00 | 0.00 | 0.00 |
July | 102.40 | 17.14 | 85.27 | 154.95 | 14.51 | 0.00 | 0.00 | 0.00 |
August | 66.00 | 3.97 | 62.03 | 97.58 | 23.88 | 0.00 | 0.00 | 0.00 |
September | 36.38 | 0.12 | 36.26 | 37.09 | 48.07 | 0.00 | 0.00 | 0.00 |
October | 17.60 | 0.00 | 17.60 | 5.88 | 99.93 | 0.00 | 0.00 | 0.00 |
November | 5.46 | 0.00 | 5.46 | 0.00 | 182.93 | 0.00 | 0.00 | 0.00 |
December | 0.86 | 0.00 | 0.86 | 0.00 | 199.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.28 | 5.43 | 40.85 | 53.59 | 96.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.86 | 0.00 | 0.86 | 0.00 | 12.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.11 | 26.89 | 94.22 | 171.68 | 199.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.32 | 11.62 | 19.70 | 7.46 | 689.89 | 0.00 | 0.00 | 0.00 |
February | 162.33 | 77.85 | 84.47 | 109.33 | 570.03 | 0.00 | 0.00 | 0.00 |
March | 455.04 | 230.36 | 224.68 | 449.77 | 425.00 | 0.00 | 0.00 | 0.00 |
April | 605.32 | 306.54 | 298.78 | 686.34 | 240.71 | 0.00 | 0.00 | 0.00 |
May | 881.40 | 497.37 | 384.03 | 1148.04 | 111.95 | 0.00 | 0.00 | 0.00 |
June | 807.30 | 376.92 | 430.38 | 1124.01 | 50.08 | 0.00 | 0.00 | 0.00 |
July | 768.88 | 373.76 | 395.12 | 1103.92 | 55.88 | 0.00 | 0.00 | 0.00 |
August | 617.77 | 302.63 | 315.14 | 870.55 | 89.46 | 0.00 | 0.00 | 0.00 |
September | 386.71 | 174.87 | 211.84 | 480.84 | 176.05 | 0.00 | 0.00 | 0.00 |
October | 209.51 | 84.89 | 124.62 | 198.23 | 350.96 | 0.00 | 0.00 | 0.00 |
November | 43.47 | 15.81 | 27.65 | 7.00 | 658.98 | 0.00 | 0.00 | 0.00 |
December | 6.19 | 1.47 | 4.72 | 0.00 | 744.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 416.17 | 205.40 | 210.78 | 518.15 | 345.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.19 | 1.47 | 4.72 | 0.00 | 50.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 881.40 | 497.37 | 430.38 | 1148.04 | 744.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.28 | 23.48 | 11.81 | 25.41 | 172.11 | 0.00 | 0.00 | 0.00 |
February | 117.91 | 81.84 | 36.07 | 114.20 | 139.11 | 0.00 | 0.00 | 0.00 |
March | 199.70 | 135.07 | 64.62 | 221.52 | 109.57 | 0.00 | 0.00 | 0.00 |
April | 244.80 | 152.34 | 92.46 | 305.22 | 69.33 | 0.00 | 0.00 | 0.00 |
May | 202.21 | 105.00 | 97.21 | 272.66 | 33.84 | 0.00 | 0.00 | 0.00 |
June | 183.74 | 75.04 | 108.70 | 265.63 | 16.55 | 0.00 | 0.00 | 0.00 |
July | 176.74 | 76.56 | 100.18 | 263.05 | 17.12 | 0.00 | 0.00 | 0.00 |
August | 184.08 | 101.57 | 82.50 | 262.53 | 25.15 | 0.00 | 0.00 | 0.00 |
September | 146.90 | 87.80 | 59.10 | 189.27 | 47.64 | 0.00 | 0.00 | 0.00 |
October | 108.73 | 68.95 | 39.78 | 117.80 | 88.86 | 0.00 | 0.00 | 0.00 |
November | 58.94 | 41.52 | 17.42 | 47.09 | 158.78 | 0.00 | 0.00 | 0.00 |
December | 10.42 | 7.34 | 3.08 | 3.11 | 190.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.08 | 79.59 | 59.49 | 174.14 | 88.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.42 | 7.34 | 3.08 | 3.11 | 16.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 244.80 | 152.34 | 108.70 | 305.22 | 190.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3.58 | 0.00 | 3.58 | 0.00 | 294.85 | 0.00 | 0.00 | 0.00 |
February | 15.84 | 0.00 | 15.84 | 0.00 | 264.09 | 0.00 | 0.00 | 0.00 |
March | 42.42 | 0.01 | 42.42 | 2.77 | 197.82 | 0.00 | 0.00 | 0.00 |
April | 77.48 | 2.22 | 75.25 | 29.93 | 102.57 | 0.00 | 0.00 | 0.00 |
May | 118.49 | 19.03 | 99.45 | 95.95 | 40.72 | 0.00 | 0.00 | 0.00 |
June | 153.38 | 34.06 | 119.32 | 157.66 | 17.76 | 0.00 | 0.00 | 0.00 |
July | 129.69 | 21.70 | 107.98 | 137.16 | 21.33 | 0.00 | 0.00 | 0.00 |
August | 83.58 | 5.03 | 78.55 | 72.02 | 37.07 | 0.00 | 0.00 | 0.00 |
September | 46.07 | 0.15 | 45.92 | 18.14 | 82.22 | 0.00 | 0.00 | 0.00 |
October | 22.30 | 0.00 | 22.30 | 1.31 | 168.26 | 0.00 | 0.00 | 0.00 |
November | 6.92 | 0.00 | 6.92 | 0.00 | 286.36 | 0.00 | 0.00 | 0.00 |
December | 1.09 | 0.00 | 1.09 | 0.00 | 307.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.61 | 6.88 | 51.73 | 43.17 | 151.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.09 | 0.00 | 1.09 | 0.00 | 17.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.38 | 34.06 | 119.32 | 157.66 | 307.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3.21 | 0.00 | 3.21 | 0.00 | 263.80 | 0.00 | 0.00 | 0.00 |
February | 14.17 | 0.00 | 14.17 | 0.00 | 236.22 | 0.00 | 0.00 | 0.00 |
March | 37.96 | 0.01 | 37.95 | 2.48 | 176.99 | 0.00 | 0.00 | 0.00 |
April | 69.32 | 1.99 | 67.33 | 26.78 | 91.77 | 0.00 | 0.00 | 0.00 |
May | 106.01 | 17.03 | 88.98 | 85.85 | 36.43 | 0.00 | 0.00 | 0.00 |
June | 137.23 | 30.47 | 106.76 | 141.06 | 15.89 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 19.42 | 96.61 | 122.72 | 19.09 | 0.00 | 0.00 | 0.00 |
August | 74.78 | 4.50 | 70.28 | 64.43 | 33.16 | 0.00 | 0.00 | 0.00 |
September | 41.22 | 0.14 | 41.09 | 16.23 | 73.56 | 0.00 | 0.00 | 0.00 |
October | 19.95 | 0.00 | 19.95 | 1.17 | 150.51 | 0.00 | 0.00 | 0.00 |
November | 6.19 | 0.00 | 6.19 | 0.00 | 256.20 | 0.00 | 0.00 | 0.00 |
December | 0.97 | 0.00 | 0.97 | 0.00 | 275.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.44 | 6.16 | 46.29 | 38.63 | 135.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.97 | 0.00 | 0.97 | 0.00 | 15.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.23 | 30.47 | 106.76 | 141.06 | 275.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.72 | 87.64 | 44.08 | 74.97 | 782.64 | 0.00 | 0.00 | 0.00 |
February | 440.18 | 305.52 | 134.66 | 373.72 | 623.62 | 0.00 | 0.00 | 0.00 |
March | 745.53 | 504.28 | 241.26 | 745.46 | 477.43 | 0.00 | 0.00 | 0.00 |
April | 913.92 | 568.75 | 345.17 | 1027.99 | 300.46 | 0.00 | 0.00 | 0.00 |
May | 754.90 | 391.99 | 362.91 | 877.65 | 151.39 | 0.00 | 0.00 | 0.00 |
June | 685.96 | 280.15 | 405.81 | 819.53 | 76.44 | 0.00 | 0.00 | 0.00 |
July | 659.83 | 285.83 | 374.00 | 810.42 | 79.87 | 0.00 | 0.00 | 0.00 |
August | 687.21 | 379.20 | 308.01 | 831.06 | 121.52 | 0.00 | 0.00 | 0.00 |
September | 548.42 | 327.77 | 220.65 | 602.13 | 226.32 | 0.00 | 0.00 | 0.00 |
October | 405.94 | 257.41 | 148.52 | 373.47 | 408.59 | 0.00 | 0.00 | 0.00 |
November | 220.04 | 155.00 | 65.03 | 142.84 | 720.20 | 0.00 | 0.00 | 0.00 |
December | 38.91 | 27.41 | 11.50 | 6.48 | 867.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 519.23 | 297.13 | 222.11 | 557.65 | 402.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 38.91 | 27.41 | 11.50 | 6.48 | 76.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 913.92 | 568.75 | 405.81 | 1027.99 | 867.82 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.477969E+09 | 0.318027E+09 | 0.159942E+09 | 0.279606E+09 | 0.267752E+10 |
February | 0.144266E+10 | 0.100132E+10 | 0.441347E+09 | 0.122965E+10 | 0.194168E+10 |
March | 0.270523E+10 | 0.182981E+10 | 0.875421E+09 | 0.270065E+10 | 0.164635E+10 |
April | 0.320927E+10 | 0.199719E+10 | 0.121208E+10 | 0.359238E+10 | 0.100867E+10 |
May | 0.273921E+10 | 0.142236E+10 | 0.131684E+10 | 0.320004E+10 | 0.501355E+09 |
June | 0.240877E+10 | 0.983773E+09 | 0.142500E+10 | 0.292637E+10 | 0.225039E+09 |
July | 0.239425E+10 | 0.103715E+10 | 0.135710E+10 | 0.298546E+10 | 0.243274E+09 |
August | 0.249361E+10 | 0.137596E+10 | 0.111765E+10 | 0.303206E+10 | 0.392605E+09 |
September | 0.192581E+10 | 0.115100E+10 | 0.774815E+09 | 0.210803E+10 | 0.751531E+09 |
October | 0.147297E+10 | 0.934043E+09 | 0.538928E+09 | 0.136414E+10 | 0.139597E+10 |
November | 0.772670E+09 | 0.544306E+09 | 0.228364E+09 | 0.506214E+09 | 0.241962E+10 |
December | 0.141180E+09 | 99460103.64 | 41719703.73 | 24938342.03 | 0.298104E+10 |
Annual Sum or Average | 0.221836E+11 | 0.126944E+11 | 0.948921E+10 | 0.239495E+11 | 0.161846E+11 |
Minimum of Months | 0.141180E+09 | 99460103.64 | 41719703.73 | 24938342.03 | 0.225039E+09 |
Maximum of Months | 0.320927E+10 | 0.199719E+10 | 0.142500E+10 | 0.359238E+10 | 0.298104E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134593E+10 | 0.895543E+09 | 0.450387E+09 | 0.781804E+09 | 0.749969E+10 |
February | 0.406245E+10 | 0.281964E+10 | 0.124281E+10 | 0.344208E+10 | 0.543893E+10 |
March | 0.761775E+10 | 0.515262E+10 | 0.246513E+10 | 0.756266E+10 | 0.464255E+10 |
April | 0.903709E+10 | 0.562395E+10 | 0.341314E+10 | 0.100647E+11 | 0.290699E+10 |
May | 0.771342E+10 | 0.400528E+10 | 0.370815E+10 | 0.894170E+10 | 0.149025E+10 |
June | 0.678295E+10 | 0.277024E+10 | 0.401271E+10 | 0.815805E+10 | 0.691776E+09 |
July | 0.674205E+10 | 0.292054E+10 | 0.382151E+10 | 0.832547E+10 | 0.745137E+09 |
August | 0.702183E+10 | 0.387461E+10 | 0.314722E+10 | 0.847381E+10 | 0.118460E+10 |
September | 0.542296E+10 | 0.324113E+10 | 0.218183E+10 | 0.589286E+10 | 0.217929E+10 |
October | 0.414779E+10 | 0.263020E+10 | 0.151759E+10 | 0.381159E+10 | 0.394447E+10 |
November | 0.217579E+10 | 0.153273E+10 | 0.643057E+09 | 0.141449E+10 | 0.676905E+10 |
December | 0.397553E+09 | 0.280073E+09 | 0.117480E+09 | 69364993.15 | 0.833930E+10 |
Annual Sum or Average | 0.624676E+11 | 0.357466E+11 | 0.267210E+11 | 0.669386E+11 | 0.458320E+11 |
Minimum of Months | 0.397553E+09 | 0.280073E+09 | 0.117480E+09 | 69364993.15 | 0.691776E+09 |
Maximum of Months | 0.903709E+10 | 0.562395E+10 | 0.401271E+10 | 0.100647E+11 | 0.833930E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174844E+10 | 0.116336E+10 | 0.585078E+09 | 0.100964E+10 | 0.101774E+11 |
February | 0.527735E+10 | 0.366288E+10 | 0.161447E+10 | 0.449420E+10 | 0.736499E+10 |
March | 0.989589E+10 | 0.669355E+10 | 0.320234E+10 | 0.993558E+10 | 0.629061E+10 |
April | 0.117397E+11 | 0.730582E+10 | 0.443386E+10 | 0.132310E+11 | 0.396107E+10 |
May | 0.100202E+11 | 0.520308E+10 | 0.481709E+10 | 0.117209E+11 | 0.208392E+10 |
June | 0.881144E+10 | 0.359870E+10 | 0.521274E+10 | 0.106750E+11 | 0.988771E+09 |
July | 0.875830E+10 | 0.379395E+10 | 0.496436E+10 | 0.108849E+11 | 0.106924E+10 |
August | 0.912176E+10 | 0.503334E+10 | 0.408842E+10 | 0.110801E+11 | 0.167632E+10 |
September | 0.704473E+10 | 0.421041E+10 | 0.283432E+10 | 0.769521E+10 | 0.306021E+10 |
October | 0.538822E+10 | 0.341678E+10 | 0.197143E+10 | 0.496738E+10 | 0.544738E+10 |
November | 0.282647E+10 | 0.199110E+10 | 0.835368E+09 | 0.183408E+10 | 0.917947E+10 |
December | 0.516444E+09 | 0.363831E+09 | 0.152613E+09 | 87559714.80 | 0.112758E+11 |
Annual Sum or Average | 0.811489E+11 | 0.464368E+11 | 0.347121E+11 | 0.876155E+11 | 0.625752E+11 |
Minimum of Months | 0.516444E+09 | 0.363831E+09 | 0.152613E+09 | 87559714.80 | 0.988771E+09 |
Maximum of Months | 0.117397E+11 | 0.730582E+10 | 0.521274E+10 | 0.132310E+11 | 0.112758E+11 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94502736.66 | 62879372.15 | 31623364.51 | 56350517.08 | 0.536510E+09 |
February | 0.285240E+09 | 0.197978E+09 | 87262226.49 | 0.247750E+09 | 0.387826E+09 |
March | 0.534871E+09 | 0.361785E+09 | 0.173087E+09 | 0.540579E+09 | 0.330335E+09 |
April | 0.634529E+09 | 0.394878E+09 | 0.239651E+09 | 0.713667E+09 | 0.203034E+09 |
May | 0.541590E+09 | 0.281225E+09 | 0.260365E+09 | 0.632169E+09 | 0.100638E+09 |
June | 0.476258E+09 | 0.194509E+09 | 0.281749E+09 | 0.577857E+09 | 43707274.24 |
July | 0.473386E+09 | 0.205062E+09 | 0.268324E+09 | 0.590911E+09 | 47102833.67 |
August | 0.493030E+09 | 0.272051E+09 | 0.220980E+09 | 0.600832E+09 | 77088253.03 |
September | 0.380767E+09 | 0.227572E+09 | 0.153195E+09 | 0.419584E+09 | 0.150023E+09 |
October | 0.291232E+09 | 0.184676E+09 | 0.106556E+09 | 0.273626E+09 | 0.278482E+09 |
November | 0.152770E+09 | 0.107619E+09 | 45151531.58 | 0.103331E+09 | 0.480588E+09 |
December | 27913686.84 | 19664970.70 | 8248716.14 | 5196737.03 | 0.595068E+09 |
Annual Sum or Average | 0.438609E+10 | 0.250990E+10 | 0.187619E+10 | 0.476185E+10 | 0.323040E+10 |
Minimum of Months | 27913686.84 | 19664970.70 | 8248716.14 | 5196737.03 | 43707274.24 |
Maximum of Months | 0.634529E+09 | 0.394878E+09 | 0.281749E+09 | 0.713667E+09 | 0.595068E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 19486793.32 | 3327943.48 | 16158849.85 | 0.00 | 0.110619E+10 |
February | 0.104877E+09 | 36576040.05 | 68300506.74 | 20943770.21 | 0.851180E+09 |
March | 0.349173E+09 | 0.150831E+09 | 0.198342E+09 | 0.200251E+09 | 0.684449E+09 |
April | 0.800370E+09 | 0.415440E+09 | 0.384929E+09 | 0.780132E+09 | 0.368584E+09 |
May | 0.802333E+09 | 0.365965E+09 | 0.436368E+09 | 0.848196E+09 | 0.172559E+09 |
June | 0.850519E+09 | 0.363039E+09 | 0.487480E+09 | 0.990200E+09 | 75374990.17 |
July | 0.734165E+09 | 0.277339E+09 | 0.456826E+09 | 0.868316E+09 | 83329643.53 |
August | 0.605748E+09 | 0.257506E+09 | 0.348242E+09 | 0.672512E+09 | 0.138688E+09 |
September | 0.352757E+09 | 0.147061E+09 | 0.205696E+09 | 0.300321E+09 | 0.287321E+09 |
October | 0.142970E+09 | 42849611.93 | 0.100120E+09 | 52553188.73 | 0.595896E+09 |
November | 55952411.84 | 20544393.39 | 35408018.44 | 5790128.72 | 0.101331E+10 |
December | 5123481.58 | 522824.73 | 4600656.85 | 0.00 | 0.116533E+10 |
Annual Sum or Average | 0.482347E+10 | 0.208100E+10 | 0.274247E+10 | 0.473921E+10 | 0.654221E+10 |
Minimum of Months | 5123481.58 | 522824.73 | 4600656.85 | 0.00 | 75374990.17 |
Maximum of Months | 0.850519E+09 | 0.415440E+09 | 0.487480E+09 | 0.990200E+09 | 0.116533E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7577117.11 | 0.00 | 7577117.11 | 0.00 | 0.595333E+09 |
February | 30253127.37 | 0.00 | 30253127.37 | 0.00 | 0.478191E+09 |
March | 89721695.70 | 15520.03 | 89706175.66 | 8245737.05 | 0.392887E+09 |
April | 0.158573E+09 | 4551800.57 | 0.154022E+09 | 66535924.48 | 0.200287E+09 |
May | 0.250585E+09 | 40250733.32 | 0.210335E+09 | 0.206139E+09 | 80978113.94 |
June | 0.313916E+09 | 69706027.16 | 0.244210E+09 | 0.324955E+09 | 32432335.33 |
July | 0.274275E+09 | 45899189.55 | 0.228375E+09 | 0.295363E+09 | 39998703.97 |
August | 0.176774E+09 | 10639562.35 | 0.166135E+09 | 0.156891E+09 | 72517206.78 |
September | 94295413.67 | 309320.54 | 93986093.13 | 41030026.31 | 0.157602E+09 |
October | 47152640.75 | 0.00 | 47152640.75 | 3969015.33 | 0.331154E+09 |
November | 14161091.87 | 0.00 | 14161091.87 | 0.00 | 0.559979E+09 |
December | 2298499.28 | 0.00 | 2298499.28 | 0.00 | 0.622853E+09 |
Annual Sum or Average | 0.145958E+10 | 0.171372E+09 | 0.128821E+10 | 0.110313E+10 | 0.356421E+10 |
Minimum of Months | 2298499.28 | 0.00 | 2298499.28 | 0.00 | 32432335.33 |
Maximum of Months | 0.313916E+09 | 69706027.16 | 0.244210E+09 | 0.324955E+09 | 0.622853E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 19486793.32 | 3327943.48 | 16158849.85 | 0.00 | 0.110625E+10 |
February | 0.104877E+09 | 36576040.05 | 68300506.74 | 22324717.89 | 0.849119E+09 |
March | 0.349173E+09 | 0.150831E+09 | 0.198342E+09 | 0.208406E+09 | 0.676781E+09 |
April | 0.800370E+09 | 0.415440E+09 | 0.384929E+09 | 0.794806E+09 | 0.363488E+09 |
May | 0.802333E+09 | 0.365965E+09 | 0.436368E+09 | 0.848786E+09 | 0.171950E+09 |
June | 0.850519E+09 | 0.363039E+09 | 0.487480E+09 | 0.975513E+09 | 76938022.60 |
July | 0.734165E+09 | 0.277339E+09 | 0.456826E+09 | 0.858672E+09 | 85939409.90 |
August | 0.605748E+09 | 0.257506E+09 | 0.348242E+09 | 0.670705E+09 | 0.142062E+09 |
September | 0.352757E+09 | 0.147061E+09 | 0.205696E+09 | 0.307676E+09 | 0.283485E+09 |
October | 0.142970E+09 | 42849611.93 | 0.100120E+09 | 56191446.64 | 0.591531E+09 |
November | 55952411.84 | 20544393.39 | 35408018.44 | 6118014.26 | 0.101276E+10 |
December | 5123481.58 | 522824.73 | 4600656.85 | 0.00 | 0.116524E+10 |
Annual Sum or Average | 0.482347E+10 | 0.208100E+10 | 0.274247E+10 | 0.474920E+10 | 0.652555E+10 |
Minimum of Months | 5123481.58 | 522824.73 | 4600656.85 | 0.00 | 76938022.60 |
Maximum of Months | 0.850519E+09 | 0.415440E+09 | 0.487480E+09 | 0.975513E+09 | 0.116524E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75587157.08 | 50293495.70 | 25293661.38 | 48379921.37 | 0.379130E+09 |
February | 0.228147E+09 | 0.158351E+09 | 69795900.67 | 0.202571E+09 | 0.282488E+09 |
March | 0.427812E+09 | 0.289370E+09 | 0.138442E+09 | 0.418367E+09 | 0.285886E+09 |
April | 0.507522E+09 | 0.315840E+09 | 0.191683E+09 | 0.545800E+09 | 0.204468E+09 |
May | 0.433186E+09 | 0.224936E+09 | 0.208250E+09 | 0.477876E+09 | 0.116077E+09 |
June | 0.380931E+09 | 0.155576E+09 | 0.225355E+09 | 0.431103E+09 | 60347924.49 |
July | 0.378634E+09 | 0.164017E+09 | 0.214617E+09 | 0.440872E+09 | 64855482.50 |
August | 0.394346E+09 | 0.217597E+09 | 0.176749E+09 | 0.453191E+09 | 96362685.54 |
September | 0.304553E+09 | 0.182021E+09 | 0.122532E+09 | 0.311916E+09 | 0.164426E+09 |
October | 0.232939E+09 | 0.147712E+09 | 85227669.47 | 0.203584E+09 | 0.255518E+09 |
November | 0.122192E+09 | 86077848.02 | 36114043.15 | 87793737.94 | 0.341126E+09 |
December | 22326509.33 | 15728848.52 | 6597660.82 | 4911067.09 | 0.423135E+09 |
Annual Sum or Average | 0.350818E+10 | 0.200752E+10 | 0.150066E+10 | 0.362636E+10 | 0.267382E+10 |
Minimum of Months | 22326509.33 | 15728848.52 | 6597660.82 | 4911067.09 | 60347924.49 |
Maximum of Months | 0.507522E+09 | 0.315840E+09 | 0.225355E+09 | 0.545800E+09 | 0.423135E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6062497.20 | 0.00 | 6062497.20 | 0.00 | 0.489216E+09 |
February | 24205710.07 | 0.00 | 24205710.07 | 0.00 | 0.394266E+09 |
March | 71786871.05 | 12417.67 | 71774453.38 | 5580920.24 | 0.323918E+09 |
April | 0.126876E+09 | 3641923.15 | 0.123234E+09 | 54744836.60 | 0.160760E+09 |
May | 0.200495E+09 | 32204855.03 | 0.168290E+09 | 0.172162E+09 | 63387346.84 |
June | 0.251166E+09 | 55772213.67 | 0.195394E+09 | 0.271659E+09 | 24387097.91 |
July | 0.219449E+09 | 36724219.00 | 0.182725E+09 | 0.245040E+09 | 30383642.75 |
August | 0.141438E+09 | 8512778.15 | 0.132926E+09 | 0.131486E+09 | 55770069.12 |
September | 75446330.45 | 247489.23 | 75198841.21 | 32376635.22 | 0.128713E+09 |
October | 37727112.88 | 0.00 | 37727112.88 | 2570903.27 | 0.275846E+09 |
November | 11330375.20 | 0.00 | 11330375.20 | 0.00 | 0.460837E+09 |
December | 1839043.17 | 0.00 | 1839043.17 | 0.00 | 0.511259E+09 |
Annual Sum or Average | 0.116782E+10 | 0.137116E+09 | 0.103071E+10 | 0.915620E+09 | 0.291874E+10 |
Minimum of Months | 1839043.17 | 0.00 | 1839043.17 | 0.00 | 24387097.91 |
Maximum of Months | 0.251166E+09 | 55772213.67 | 0.195394E+09 | 0.271659E+09 | 0.511259E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41945160.70 | 15564344.25 | 26380816.45 | 5432305.48 | 0.108068E+10 |
February | 0.196367E+09 | 94179516.98 | 0.102187E+09 | 0.103540E+09 | 0.809771E+09 |
March | 0.609430E+09 | 0.308519E+09 | 0.300910E+09 | 0.523630E+09 | 0.667359E+09 |
April | 0.784554E+09 | 0.397306E+09 | 0.387248E+09 | 0.737314E+09 | 0.345415E+09 |
May | 0.118045E+10 | 0.666122E+09 | 0.514328E+09 | 0.134037E+10 | 0.161434E+09 |
June | 0.104634E+10 | 0.488518E+09 | 0.557817E+09 | 0.124538E+10 | 65064246.89 |
July | 0.102976E+10 | 0.500573E+09 | 0.529183E+09 | 0.125886E+10 | 76002569.07 |
August | 0.827373E+09 | 0.405310E+09 | 0.422063E+09 | 0.961968E+09 | 0.131378E+09 |
September | 0.501214E+09 | 0.226654E+09 | 0.274561E+09 | 0.486819E+09 | 0.278600E+09 |
October | 0.280596E+09 | 0.113695E+09 | 0.166901E+09 | 0.206975E+09 | 0.569035E+09 |
November | 56335260.54 | 20493623.86 | 35841636.68 | 4239047.01 | 0.101041E+10 |
December | 8291630.75 | 1972674.86 | 6318955.89 | 0.00 | 0.116007E+10 |
Annual Sum or Average | 0.656265E+10 | 0.323891E+10 | 0.332374E+10 | 0.687453E+10 | 0.635521E+10 |
Minimum of Months | 8291630.75 | 1972674.86 | 6318955.89 | 0.00 | 65064246.89 |
Maximum of Months | 0.118045E+10 | 0.666122E+09 | 0.557817E+09 | 0.134037E+10 | 0.116007E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94502736.66 | 62879372.15 | 31623364.51 | 56144461.15 | 0.536654E+09 |
February | 0.285240E+09 | 0.197978E+09 | 87262226.49 | 0.246273E+09 | 0.388313E+09 |
March | 0.534871E+09 | 0.361785E+09 | 0.173087E+09 | 0.534344E+09 | 0.331979E+09 |
April | 0.634529E+09 | 0.394878E+09 | 0.239651E+09 | 0.710912E+09 | 0.202019E+09 |
May | 0.541590E+09 | 0.281225E+09 | 0.260365E+09 | 0.627147E+09 | 99420447.65 |
June | 0.476258E+09 | 0.194509E+09 | 0.281749E+09 | 0.575468E+09 | 41536207.00 |
July | 0.473386E+09 | 0.205062E+09 | 0.268324E+09 | 0.587465E+09 | 45982338.04 |
August | 0.493030E+09 | 0.272051E+09 | 0.220980E+09 | 0.597837E+09 | 76890705.02 |
September | 0.380767E+09 | 0.227572E+09 | 0.153195E+09 | 0.416294E+09 | 0.150729E+09 |
October | 0.291232E+09 | 0.184676E+09 | 0.106556E+09 | 0.270685E+09 | 0.279561E+09 |
November | 0.152770E+09 | 0.107619E+09 | 45151531.58 | 0.103211E+09 | 0.480564E+09 |
December | 27913686.84 | 19664970.70 | 8248716.14 | 5188192.34 | 0.595107E+09 |
Annual Sum or Average | 0.438609E+10 | 0.250990E+10 | 0.187619E+10 | 0.473097E+10 | 0.322876E+10 |
Minimum of Months | 27913686.84 | 19664970.70 | 8248716.14 | 5188192.34 | 41536207.00 |
Maximum of Months | 0.634529E+09 | 0.394878E+09 | 0.281749E+09 | 0.710912E+09 | 0.595107E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7577117.11 | 0.00 | 7577117.11 | 0.00 | 0.594790E+09 |
February | 30253127.37 | 0.00 | 30253127.37 | 0.00 | 0.477669E+09 |
March | 89721695.70 | 15520.03 | 89706175.66 | 6802717.49 | 0.397149E+09 |
April | 0.158573E+09 | 4551800.57 | 0.154022E+09 | 63263038.87 | 0.200280E+09 |
May | 0.250585E+09 | 40250733.32 | 0.210335E+09 | 0.200703E+09 | 80477406.30 |
June | 0.313916E+09 | 69706027.16 | 0.244210E+09 | 0.325245E+09 | 31672399.17 |
July | 0.274275E+09 | 45899189.55 | 0.228375E+09 | 0.291118E+09 | 39606715.66 |
August | 0.176774E+09 | 10639562.35 | 0.166135E+09 | 0.154072E+09 | 71796340.45 |
September | 94295413.67 | 309320.54 | 93986093.13 | 37973908.75 | 0.159375E+09 |
October | 47152640.75 | 0.00 | 47152640.75 | 3281734.48 | 0.332876E+09 |
November | 14161091.87 | 0.00 | 14161091.87 | 0.00 | 0.560067E+09 |
December | 2298499.28 | 0.00 | 2298499.28 | 0.00 | 0.622780E+09 |
Annual Sum or Average | 0.145958E+10 | 0.171372E+09 | 0.128821E+10 | 0.108246E+10 | 0.356854E+10 |
Minimum of Months | 2298499.28 | 0.00 | 2298499.28 | 0.00 | 31672399.17 |
Maximum of Months | 0.313916E+09 | 69706027.16 | 0.244210E+09 | 0.325245E+09 | 0.622780E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41945160.70 | 15564344.25 | 26380816.45 | 5564510.74 | 0.107948E+10 |
February | 0.196367E+09 | 94179516.98 | 0.102187E+09 | 0.105076E+09 | 0.804926E+09 |
March | 0.609430E+09 | 0.308519E+09 | 0.300910E+09 | 0.529866E+09 | 0.655429E+09 |
April | 0.784554E+09 | 0.397306E+09 | 0.387248E+09 | 0.748369E+09 | 0.338939E+09 |
May | 0.118045E+10 | 0.666122E+09 | 0.514328E+09 | 0.134371E+10 | 0.162151E+09 |
June | 0.104634E+10 | 0.488518E+09 | 0.557817E+09 | 0.123898E+10 | 69195507.81 |
July | 0.102976E+10 | 0.500573E+09 | 0.529183E+09 | 0.125056E+10 | 80560861.84 |
August | 0.827373E+09 | 0.405310E+09 | 0.422063E+09 | 0.963225E+09 | 0.134664E+09 |
September | 0.501214E+09 | 0.226654E+09 | 0.274561E+09 | 0.492351E+09 | 0.274337E+09 |
October | 0.280596E+09 | 0.113695E+09 | 0.166901E+09 | 0.210218E+09 | 0.562674E+09 |
November | 56335260.54 | 20493623.86 | 35841636.68 | 4365800.65 | 0.100964E+10 |
December | 8291630.75 | 1972674.86 | 6318955.89 | 0.00 | 0.115969E+10 |
Annual Sum or Average | 0.656265E+10 | 0.323891E+10 | 0.332374E+10 | 0.689228E+10 | 0.633169E+10 |
Minimum of Months | 8291630.75 | 1972674.86 | 6318955.89 | 0.00 | 69195507.81 |
Maximum of Months | 0.118045E+10 | 0.666122E+09 | 0.557817E+09 | 0.134371E+10 | 0.115969E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 9595940.73 | 0.00 | 9595940.73 | 0.00 | 0.789785E+09 |
February | 38313676.95 | 0.00 | 38313676.95 | 0.00 | 0.637806E+09 |
March | 0.113627E+09 | 19655.14 | 0.113607E+09 | 8135475.56 | 0.525010E+09 |
April | 0.200823E+09 | 5764568.21 | 0.195059E+09 | 81672978.55 | 0.264089E+09 |
May | 0.317350E+09 | 50975014.07 | 0.266375E+09 | 0.261718E+09 | 0.109484E+09 |
June | 0.397554E+09 | 88278285.19 | 0.309276E+09 | 0.416250E+09 | 45469860.42 |
July | 0.347351E+09 | 58128427.49 | 0.289223E+09 | 0.375338E+09 | 56125683.94 |
August | 0.223874E+09 | 13474334.39 | 0.210399E+09 | 0.198406E+09 | 98711720.31 |
September | 0.119419E+09 | 391734.95 | 0.119027E+09 | 49125274.55 | 0.211577E+09 |
October | 59715844.34 | 0.00 | 59715844.34 | 4006230.04 | 0.444920E+09 |
November | 17934129.34 | 0.00 | 17934129.34 | 0.00 | 0.744488E+09 |
December | 2910904.31 | 0.00 | 2910904.31 | 0.00 | 0.825257E+09 |
Annual Sum or Average | 0.184847E+10 | 0.217032E+09 | 0.163144E+10 | 0.139465E+10 | 0.475272E+10 |
Minimum of Months | 2910904.31 | 0.00 | 2910904.31 | 0.00 | 45469860.42 |
Maximum of Months | 0.397554E+09 | 88278285.19 | 0.309276E+09 | 0.416250E+09 | 0.825257E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 3537461.09 | 0.00 | 3537461.09 | 0.00 | 0.291118E+09 |
February | 14124007.77 | 0.00 | 14124007.77 | 0.00 | 0.235122E+09 |
March | 41887567.90 | 7245.70 | 41880322.20 | 2999073.16 | 0.193541E+09 |
April | 74031794.50 | 2125058.54 | 71906735.96 | 30108041.70 | 97354319.59 |
May | 0.116988E+09 | 18791500.90 | 98196996.68 | 96480273.57 | 40360441.16 |
June | 0.146555E+09 | 32543031.24 | 0.114012E+09 | 0.153447E+09 | 16762073.31 |
July | 0.128048E+09 | 21428545.28 | 0.106620E+09 | 0.138365E+09 | 20690251.08 |
August | 82529134.27 | 4967197.59 | 77561936.69 | 73140778.89 | 36389227.44 |
September | 44022858.82 | 144409.72 | 43878449.10 | 18109610.32 | 77996155.62 |
October | 22013732.86 | 0.00 | 22013732.86 | 1476862.28 | 0.164016E+09 |
November | 6611262.67 | 0.00 | 6611262.67 | 0.00 | 0.274430E+09 |
December | 1073079.86 | 0.00 | 1073079.86 | 0.00 | 0.304133E+09 |
Annual Sum or Average | 0.681423E+09 | 80006988.96 | 0.601416E+09 | 0.514127E+09 | 0.175191E+10 |
Minimum of Months | 1073079.86 | 0.00 | 1073079.86 | 0.00 | 16762073.31 |
Maximum of Months | 0.146555E+09 | 32543031.24 | 0.114012E+09 | 0.153447E+09 | 0.304133E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44094596.11 | 29339261.66 | 14755334.45 | 25185578.68 | 0.261914E+09 |
February | 0.133092E+09 | 92375560.58 | 40716203.24 | 0.113405E+09 | 0.188327E+09 |
March | 0.249569E+09 | 0.168807E+09 | 80761524.82 | 0.251216E+09 | 0.158809E+09 |
April | 0.296069E+09 | 0.184249E+09 | 0.111820E+09 | 0.335607E+09 | 97002184.65 |
May | 0.252704E+09 | 0.131219E+09 | 0.121485E+09 | 0.296183E+09 | 50919046.00 |
June | 0.222220E+09 | 90757038.88 | 0.131463E+09 | 0.268639E+09 | 24397337.65 |
July | 0.220880E+09 | 95681062.38 | 0.125199E+09 | 0.274576E+09 | 26186163.55 |
August | 0.230046E+09 | 0.126938E+09 | 0.103108E+09 | 0.280720E+09 | 40350594.16 |
September | 0.177664E+09 | 0.106184E+09 | 71480204.43 | 0.196569E+09 | 72936017.08 |
October | 0.135888E+09 | 86169245.54 | 49718494.62 | 0.126249E+09 | 0.135259E+09 |
November | 71281978.28 | 50214455.59 | 21067522.69 | 46278131.18 | 0.233955E+09 |
December | 13024413.80 | 9175596.09 | 3848817.71 | 2164604.04 | 0.290755E+09 |
Annual Sum or Average | 0.204653E+10 | 0.117111E+10 | 0.875424E+09 | 0.221679E+10 | 0.158081E+10 |
Minimum of Months | 13024413.80 | 9175596.09 | 3848817.71 | 2164604.04 | 24397337.65 |
Maximum of Months | 0.296069E+09 | 0.184249E+09 | 0.131463E+09 | 0.335607E+09 | 0.290755E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119682E+09 | 79632757.36 | 40048995.83 | 68358812.13 | 0.710887E+09 |
February | 0.361238E+09 | 0.250726E+09 | 0.110512E+09 | 0.307804E+09 | 0.511157E+09 |
March | 0.677381E+09 | 0.458178E+09 | 0.219203E+09 | 0.681851E+09 | 0.431041E+09 |
April | 0.803591E+09 | 0.500088E+09 | 0.303503E+09 | 0.910907E+09 | 0.263284E+09 |
May | 0.685890E+09 | 0.356154E+09 | 0.329736E+09 | 0.803901E+09 | 0.138205E+09 |
June | 0.603151E+09 | 0.246333E+09 | 0.356818E+09 | 0.729142E+09 | 66219364.76 |
July | 0.599514E+09 | 0.259698E+09 | 0.339816E+09 | 0.745254E+09 | 71074604.14 |
August | 0.624392E+09 | 0.344535E+09 | 0.279857E+09 | 0.761931E+09 | 0.109520E+09 |
September | 0.482217E+09 | 0.288205E+09 | 0.194012E+09 | 0.533528E+09 | 0.197963E+09 |
October | 0.368827E+09 | 0.233881E+09 | 0.134946E+09 | 0.342667E+09 | 0.367121E+09 |
November | 0.193474E+09 | 0.136292E+09 | 57181565.84 | 0.125608E+09 | 0.635000E+09 |
December | 35350923.13 | 24904444.60 | 10446478.53 | 5875178.12 | 0.789167E+09 |
Annual Sum or Average | 0.555471E+10 | 0.317863E+10 | 0.237608E+10 | 0.601683E+10 | 0.429064E+10 |
Minimum of Months | 35350923.13 | 24904444.60 | 10446478.53 | 5875178.12 | 66219364.76 |
Maximum of Months | 0.803591E+09 | 0.500088E+09 | 0.356818E+09 | 0.910907E+09 | 0.789167E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94502736.66 | 62879372.15 | 31623364.51 | 56648308.90 | 0.532930E+09 |
February | 0.285240E+09 | 0.197978E+09 | 87262226.49 | 0.248883E+09 | 0.384987E+09 |
March | 0.534871E+09 | 0.361785E+09 | 0.173087E+09 | 0.541633E+09 | 0.328465E+09 |
April | 0.634529E+09 | 0.394878E+09 | 0.239651E+09 | 0.712412E+09 | 0.202087E+09 |
May | 0.541590E+09 | 0.281225E+09 | 0.260365E+09 | 0.630111E+09 | 99730843.07 |
June | 0.476258E+09 | 0.194509E+09 | 0.281749E+09 | 0.575531E+09 | 43105113.26 |
July | 0.473386E+09 | 0.205062E+09 | 0.268324E+09 | 0.588778E+09 | 46444752.52 |
August | 0.493030E+09 | 0.272051E+09 | 0.220980E+09 | 0.599301E+09 | 76148217.41 |
September | 0.380767E+09 | 0.227572E+09 | 0.153195E+09 | 0.419848E+09 | 0.148316E+09 |
October | 0.291232E+09 | 0.184676E+09 | 0.106556E+09 | 0.274667E+09 | 0.276325E+09 |
November | 0.152770E+09 | 0.107619E+09 | 45151531.58 | 0.104238E+09 | 0.475967E+09 |
December | 27913686.84 | 19664970.70 | 8248716.14 | 5279374.08 | 0.591159E+09 |
Annual Sum or Average | 0.438609E+10 | 0.250990E+10 | 0.187619E+10 | 0.475733E+10 | 0.320566E+10 |
Minimum of Months | 27913686.84 | 19664970.70 | 8248716.14 | 5279374.08 | 43105113.26 |
Maximum of Months | 0.634529E+09 | 0.394878E+09 | 0.281749E+09 | 0.712412E+09 | 0.591159E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 19486793.32 | 3327943.48 | 16158849.85 | 0.00 | 0.109886E+10 |
February | 0.104877E+09 | 36576040.05 | 68300506.74 | 21563116.69 | 0.844199E+09 |
March | 0.349173E+09 | 0.150831E+09 | 0.198342E+09 | 0.201463E+09 | 0.679127E+09 |
April | 0.800370E+09 | 0.415440E+09 | 0.384929E+09 | 0.777672E+09 | 0.366305E+09 |
May | 0.802333E+09 | 0.365965E+09 | 0.436368E+09 | 0.845370E+09 | 0.170796E+09 |
June | 0.850519E+09 | 0.363039E+09 | 0.487480E+09 | 0.986295E+09 | 74209080.81 |
July | 0.734165E+09 | 0.277339E+09 | 0.456826E+09 | 0.864980E+09 | 82020215.93 |
August | 0.605748E+09 | 0.257506E+09 | 0.348242E+09 | 0.670296E+09 | 0.136751E+09 |
September | 0.352757E+09 | 0.147061E+09 | 0.205696E+09 | 0.301003E+09 | 0.283453E+09 |
October | 0.142970E+09 | 42849611.93 | 0.100120E+09 | 53717907.07 | 0.590339E+09 |
November | 55952411.84 | 20544393.39 | 35408018.44 | 6037173.43 | 0.100310E+10 |
December | 5123481.58 | 522824.73 | 4600656.85 | 0.00 | 0.115777E+10 |
Annual Sum or Average | 0.482347E+10 | 0.208100E+10 | 0.274247E+10 | 0.472840E+10 | 0.648693E+10 |
Minimum of Months | 5123481.58 | 522824.73 | 4600656.85 | 0.00 | 74209080.81 |
Maximum of Months | 0.850519E+09 | 0.415440E+09 | 0.487480E+09 | 0.986295E+09 | 0.115777E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7577117.11 | 0.00 | 7577117.11 | 0.00 | 0.591692E+09 |
February | 30253127.37 | 0.00 | 30253127.37 | 0.00 | 0.474941E+09 |
March | 89721695.70 | 15520.03 | 89706175.66 | 8635273.23 | 0.390465E+09 |
April | 0.158573E+09 | 4551800.57 | 0.154022E+09 | 67363800.74 | 0.199099E+09 |
May | 0.250585E+09 | 40250733.32 | 0.210335E+09 | 0.205564E+09 | 80674807.34 |
June | 0.313916E+09 | 69706027.16 | 0.244210E+09 | 0.322287E+09 | 32620451.97 |
July | 0.274275E+09 | 45899189.55 | 0.228375E+09 | 0.293407E+09 | 40122513.34 |
August | 0.176774E+09 | 10639562.35 | 0.166135E+09 | 0.156414E+09 | 72435963.69 |
September | 94295413.67 | 309320.54 | 93986093.13 | 42208042.94 | 0.155070E+09 |
October | 47152640.75 | 0.00 | 47152640.75 | 4371493.34 | 0.328396E+09 |
November | 14161091.87 | 0.00 | 14161091.87 | 0.00 | 0.554768E+09 |
December | 2298499.28 | 0.00 | 2298499.28 | 0.00 | 0.618892E+09 |
Annual Sum or Average | 0.145958E+10 | 0.171372E+09 | 0.128821E+10 | 0.110025E+10 | 0.353918E+10 |
Minimum of Months | 2298499.28 | 0.00 | 2298499.28 | 0.00 | 32620451.97 |
Maximum of Months | 0.313916E+09 | 69706027.16 | 0.244210E+09 | 0.322287E+09 | 0.618892E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 19486793.32 | 3327943.48 | 16158849.85 | 0.00 | 0.109904E+10 |
February | 0.104877E+09 | 36576040.05 | 68300506.74 | 22651762.74 | 0.843024E+09 |
March | 0.349173E+09 | 0.150831E+09 | 0.198342E+09 | 0.209329E+09 | 0.672797E+09 |
April | 0.800370E+09 | 0.415440E+09 | 0.384929E+09 | 0.793923E+09 | 0.360953E+09 |
May | 0.802333E+09 | 0.365965E+09 | 0.436368E+09 | 0.845672E+09 | 0.170586E+09 |
June | 0.850519E+09 | 0.363039E+09 | 0.487480E+09 | 0.968910E+09 | 77054220.78 |
July | 0.734165E+09 | 0.277339E+09 | 0.456826E+09 | 0.853511E+09 | 85792833.01 |
August | 0.605748E+09 | 0.257506E+09 | 0.348242E+09 | 0.667743E+09 | 0.141262E+09 |
September | 0.352757E+09 | 0.147061E+09 | 0.205696E+09 | 0.309618E+09 | 0.279098E+09 |
October | 0.142970E+09 | 42849611.93 | 0.100120E+09 | 57395662.96 | 0.586728E+09 |
November | 55952411.84 | 20544393.39 | 35408018.44 | 6334855.59 | 0.100277E+10 |
December | 5123481.58 | 522824.73 | 4600656.85 | 0.00 | 0.115771E+10 |
Annual Sum or Average | 0.482347E+10 | 0.208100E+10 | 0.274247E+10 | 0.473509E+10 | 0.647681E+10 |
Minimum of Months | 5123481.58 | 522824.73 | 4600656.85 | 0.00 | 77054220.78 |
Maximum of Months | 0.850519E+09 | 0.415440E+09 | 0.487480E+09 | 0.968910E+09 | 0.115771E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138597E+09 | 92218633.81 | 46378698.96 | 80384615.70 | 0.793551E+09 |
February | 0.418332E+09 | 0.290353E+09 | 0.127978E+09 | 0.353258E+09 | 0.577567E+09 |
March | 0.784440E+09 | 0.530592E+09 | 0.253848E+09 | 0.775181E+09 | 0.494843E+09 |
April | 0.930598E+09 | 0.579127E+09 | 0.351471E+09 | 0.103430E+10 | 0.300503E+09 |
May | 0.794294E+09 | 0.412444E+09 | 0.381850E+09 | 0.920853E+09 | 0.146382E+09 |
June | 0.698478E+09 | 0.285266E+09 | 0.413213E+09 | 0.845928E+09 | 62052231.31 |
July | 0.694266E+09 | 0.300743E+09 | 0.393523E+09 | 0.863901E+09 | 67376693.26 |
August | 0.723076E+09 | 0.398988E+09 | 0.324088E+09 | 0.875812E+09 | 0.111925E+09 |
September | 0.558431E+09 | 0.333756E+09 | 0.224675E+09 | 0.606444E+09 | 0.223492E+09 |
October | 0.427120E+09 | 0.270846E+09 | 0.156274E+09 | 0.390015E+09 | 0.417290E+09 |
November | 0.224052E+09 | 0.157833E+09 | 66219054.27 | 0.147776E+09 | 0.709450E+09 |
December | 40938100.64 | 28840566.79 | 12097533.86 | 7403500.21 | 0.878814E+09 |
Annual Sum or Average | 0.643262E+10 | 0.368101E+10 | 0.275162E+10 | 0.690126E+10 | 0.478325E+10 |
Minimum of Months | 40938100.64 | 28840566.79 | 12097533.86 | 7403500.21 | 62052231.31 |
Maximum of Months | 0.930598E+09 | 0.579127E+09 | 0.413213E+09 | 0.103430E+10 | 0.878814E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53037810.99 | 0.00 | 53037810.99 | 0.00 | 0.438363E+10 |
February | 0.211764E+09 | 0.00 | 0.211764E+09 | 0.00 | 0.355110E+10 |
March | 0.628028E+09 | 108636.11 | 0.627919E+09 | 36320873.45 | 0.299546E+10 |
April | 0.110997E+10 | 31861397.22 | 0.107811E+10 | 0.413338E+09 | 0.154627E+10 |
May | 0.175403E+10 | 0.281744E+09 | 0.147229E+10 | 0.138923E+10 | 0.621982E+09 |
June | 0.219733E+10 | 0.487924E+09 | 0.170940E+10 | 0.227925E+10 | 0.250265E+09 |
July | 0.191985E+10 | 0.321282E+09 | 0.159857E+10 | 0.205237E+10 | 0.308413E+09 |
August | 0.123737E+10 | 74474115.76 | 0.116290E+10 | 0.106343E+10 | 0.554150E+09 |
September | 0.660043E+09 | 2165161.78 | 0.657878E+09 | 0.238784E+09 | 0.126084E+10 |
October | 0.330056E+09 | 0.00 | 0.330056E+09 | 14423248.61 | 0.260418E+10 |
November | 99123888.81 | 0.00 | 99123888.81 | 0.00 | 0.411877E+10 |
December | 16088885.60 | 0.00 | 16088885.60 | 0.00 | 0.454923E+10 |
Annual Sum or Average | 0.102167E+11 | 0.119956E+10 | 0.901713E+10 | 0.748715E+10 | 0.267443E+11 |
Minimum of Months | 16088885.60 | 0.00 | 16088885.60 | 0.00 | 0.250265E+09 |
Maximum of Months | 0.219733E+10 | 0.487924E+09 | 0.170940E+10 | 0.227925E+10 | 0.454923E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53037810.99 | 0.00 | 53037810.99 | 0.00 | 0.445346E+10 |
February | 0.211764E+09 | 0.00 | 0.211764E+09 | 0.00 | 0.361164E+10 |
March | 0.628028E+09 | 108636.11 | 0.627919E+09 | 31664141.86 | 0.305742E+10 |
April | 0.110997E+10 | 31861397.22 | 0.107811E+10 | 0.392813E+09 | 0.158066E+10 |
May | 0.175403E+10 | 0.281744E+09 | 0.147229E+10 | 0.135967E+10 | 0.634590E+09 |
June | 0.219733E+10 | 0.487924E+09 | 0.170940E+10 | 0.225600E+10 | 0.256769E+09 |
July | 0.191985E+10 | 0.321282E+09 | 0.159857E+10 | 0.203004E+10 | 0.316462E+09 |
August | 0.123737E+10 | 74474115.76 | 0.116290E+10 | 0.104051E+10 | 0.568304E+09 |
September | 0.660043E+09 | 2165161.78 | 0.657878E+09 | 0.223265E+09 | 0.129683E+10 |
October | 0.330056E+09 | 0.00 | 0.330056E+09 | 11510893.98 | 0.266722E+10 |
November | 99123888.81 | 0.00 | 99123888.81 | 0.00 | 0.418670E+10 |
December | 16088885.60 | 0.00 | 16088885.60 | 0.00 | 0.461702E+10 |
Annual Sum or Average | 0.102167E+11 | 0.119956E+10 | 0.901713E+10 | 0.734547E+10 | 0.272471E+11 |
Minimum of Months | 16088885.60 | 0.00 | 16088885.60 | 0.00 | 0.256769E+09 |
Maximum of Months | 0.219733E+10 | 0.487924E+09 | 0.170940E+10 | 0.225600E+10 | 0.461702E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7577117.11 | 0.00 | 7577117.11 | 0.00 | 0.508484E+09 |
February | 30253127.37 | 0.00 | 30253127.37 | 33464.59 | 0.402043E+09 |
March | 89721695.70 | 15520.03 | 89706175.66 | 22522372.60 | 0.330684E+09 |
April | 0.158573E+09 | 4551800.57 | 0.154022E+09 | 0.127235E+09 | 0.176776E+09 |
May | 0.250585E+09 | 40250733.32 | 0.210335E+09 | 0.306919E+09 | 77753113.62 |
June | 0.313916E+09 | 69706027.16 | 0.244210E+09 | 0.444983E+09 | 32723900.81 |
July | 0.274275E+09 | 45899189.55 | 0.228375E+09 | 0.415018E+09 | 38872363.88 |
August | 0.176774E+09 | 10639562.35 | 0.166135E+09 | 0.261368E+09 | 63970400.64 |
September | 94295413.67 | 309320.54 | 93986093.13 | 96128146.54 | 0.124592E+09 |
October | 47152640.75 | 0.00 | 47152640.75 | 15754366.43 | 0.267644E+09 |
November | 14161091.87 | 0.00 | 14161091.87 | 0.00 | 0.474155E+09 |
December | 2298499.28 | 0.00 | 2298499.28 | 0.00 | 0.534561E+09 |
Annual Sum or Average | 0.145958E+10 | 0.171372E+09 | 0.128821E+10 | 0.168996E+10 | 0.303226E+10 |
Minimum of Months | 2298499.28 | 0.00 | 2298499.28 | 0.00 | 32723900.81 |
Maximum of Months | 0.313916E+09 | 69706027.16 | 0.244210E+09 | 0.444983E+09 | 0.534561E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83884364.12 | 31126477.97 | 52757886.15 | 19968766.31 | 0.184781E+10 |
February | 0.392706E+09 | 0.188346E+09 | 0.204360E+09 | 0.264494E+09 | 0.137903E+10 |
March | 0.121877E+10 | 0.616995E+09 | 0.601778E+09 | 0.120465E+10 | 0.113831E+10 |
April | 0.156900E+10 | 0.794556E+09 | 0.774441E+09 | 0.177900E+10 | 0.623908E+09 |
May | 0.236073E+10 | 0.133215E+10 | 0.102858E+10 | 0.307491E+10 | 0.299850E+09 |
June | 0.209252E+10 | 0.976966E+09 | 0.111556E+10 | 0.291343E+10 | 0.129807E+09 |
July | 0.205937E+10 | 0.100108E+10 | 0.105829E+10 | 0.295673E+10 | 0.149658E+09 |
August | 0.165463E+10 | 0.810563E+09 | 0.844066E+09 | 0.233169E+10 | 0.239607E+09 |
September | 0.100236E+10 | 0.453276E+09 | 0.549082E+09 | 0.124634E+10 | 0.456311E+09 |
October | 0.561153E+09 | 0.227374E+09 | 0.333779E+09 | 0.530949E+09 | 0.940017E+09 |
November | 0.112663E+09 | 40984337.10 | 71678182.95 | 18139145.57 | 0.170807E+10 |
December | 16582083.87 | 3945069.55 | 12637014.32 | 0.00 | 0.199361E+10 |
Annual Sum or Average | 0.131244E+11 | 0.647736E+10 | 0.664701E+10 | 0.163403E+11 | 0.109060E+11 |
Minimum of Months | 16582083.87 | 3945069.55 | 12637014.32 | 0.00 | 0.129807E+09 |
Maximum of Months | 0.236073E+10 | 0.133215E+10 | 0.111556E+10 | 0.307491E+10 | 0.199361E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94502736.66 | 62879372.15 | 31623364.51 | 68047501.51 | 0.460981E+09 |
February | 0.285240E+09 | 0.197978E+09 | 87262226.49 | 0.276273E+09 | 0.336528E+09 |
March | 0.534871E+09 | 0.361785E+09 | 0.173087E+09 | 0.593322E+09 | 0.293462E+09 |
April | 0.634529E+09 | 0.394878E+09 | 0.239651E+09 | 0.791124E+09 | 0.179696E+09 |
May | 0.541590E+09 | 0.281225E+09 | 0.260365E+09 | 0.730300E+09 | 90645911.96 |
June | 0.476258E+09 | 0.194509E+09 | 0.281749E+09 | 0.688515E+09 | 42896898.24 |
July | 0.473386E+09 | 0.205062E+09 | 0.268324E+09 | 0.704565E+09 | 45856356.72 |
August | 0.493030E+09 | 0.272051E+09 | 0.220980E+09 | 0.703166E+09 | 67368449.33 |
September | 0.380767E+09 | 0.227572E+09 | 0.153195E+09 | 0.490598E+09 | 0.123475E+09 |
October | 0.291232E+09 | 0.184676E+09 | 0.106556E+09 | 0.315519E+09 | 0.237991E+09 |
November | 0.152770E+09 | 0.107619E+09 | 45151531.58 | 0.122054E+09 | 0.411547E+09 |
December | 27913686.84 | 19664970.70 | 8248716.14 | 8333539.85 | 0.510158E+09 |
Annual Sum or Average | 0.438609E+10 | 0.250990E+10 | 0.187619E+10 | 0.549182E+10 | 0.280060E+10 |
Minimum of Months | 27913686.84 | 19664970.70 | 8248716.14 | 8333539.85 | 42896898.24 |
Maximum of Months | 0.634529E+09 | 0.394878E+09 | 0.281749E+09 | 0.791124E+09 | 0.510158E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 9595940.73 | 0.00 | 9595940.73 | 0.00 | 0.789720E+09 |
February | 38313676.95 | 0.00 | 38313676.95 | 0.00 | 0.638882E+09 |
March | 0.113627E+09 | 19655.14 | 0.113607E+09 | 7418318.93 | 0.529853E+09 |
April | 0.200823E+09 | 5764568.21 | 0.195059E+09 | 77568626.17 | 0.265867E+09 |
May | 0.317350E+09 | 50975014.07 | 0.266375E+09 | 0.257005E+09 | 0.109066E+09 |
June | 0.397554E+09 | 88278285.19 | 0.309276E+09 | 0.408655E+09 | 46022380.93 |
July | 0.347351E+09 | 58128427.49 | 0.289223E+09 | 0.367370E+09 | 57142141.91 |
August | 0.223874E+09 | 13474334.39 | 0.210399E+09 | 0.192892E+09 | 99275006.88 |
September | 0.119419E+09 | 391734.95 | 0.119027E+09 | 47019437.15 | 0.213114E+09 |
October | 59715844.34 | 0.00 | 59715844.34 | 3516665.89 | 0.450663E+09 |
November | 17934129.34 | 0.00 | 17934129.34 | 0.00 | 0.742239E+09 |
December | 2910904.31 | 0.00 | 2910904.31 | 0.00 | 0.823988E+09 |
Annual Sum or Average | 0.184847E+10 | 0.217032E+09 | 0.163144E+10 | 0.136145E+10 | 0.476583E+10 |
Minimum of Months | 2910904.31 | 0.00 | 2910904.31 | 0.00 | 46022380.93 |
Maximum of Months | 0.397554E+09 | 88278285.19 | 0.309276E+09 | 0.408655E+09 | 0.823988E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 8585524.53 | 0.00 | 8585524.53 | 0.00 | 0.706565E+09 |
February | 34279391.93 | 0.00 | 34279391.93 | 0.00 | 0.571467E+09 |
March | 0.101662E+09 | 17585.53 | 0.101645E+09 | 6637198.06 | 0.474062E+09 |
April | 0.179677E+09 | 5157581.02 | 0.174520E+09 | 69400943.74 | 0.237872E+09 |
May | 0.283935E+09 | 45607538.23 | 0.238327E+09 | 0.229944E+09 | 97581412.03 |
June | 0.355693E+09 | 78982916.25 | 0.276710E+09 | 0.365625E+09 | 41176398.60 |
July | 0.310777E+09 | 52007724.32 | 0.258769E+09 | 0.328687E+09 | 51125290.88 |
August | 0.200301E+09 | 12055538.04 | 0.188245E+09 | 0.172582E+09 | 88821724.80 |
September | 0.106845E+09 | 350486.74 | 0.106494E+09 | 42068468.58 | 0.190674E+09 |
October | 53427992.19 | 0.00 | 53427992.19 | 3146374.30 | 0.403132E+09 |
November | 16045733.47 | 0.00 | 16045733.47 | 0.00 | 0.664083E+09 |
December | 2604397.12 | 0.00 | 2604397.12 | 0.00 | 0.737225E+09 |
Annual Sum or Average | 0.165383E+10 | 0.194179E+09 | 0.145965E+10 | 0.121809E+10 | 0.426378E+10 |
Minimum of Months | 2604397.12 | 0.00 | 2604397.12 | 0.00 | 41176398.60 |
Maximum of Months | 0.355693E+09 | 78982916.25 | 0.276710E+09 | 0.365625E+09 | 0.737225E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.352807E+09 | 0.234747E+09 | 0.118059E+09 | 0.200788E+09 | 0.209622E+10 |
February | 0.106489E+10 | 0.739109E+09 | 0.325776E+09 | 0.904102E+09 | 0.150866E+10 |
March | 0.199683E+10 | 0.135065E+10 | 0.646184E+09 | 0.199664E+10 | 0.127875E+10 |
April | 0.236889E+10 | 0.147420E+10 | 0.894689E+09 | 0.266454E+10 | 0.778789E+09 |
May | 0.202192E+10 | 0.104990E+10 | 0.972019E+09 | 0.235071E+10 | 0.405484E+09 |
June | 0.177801E+10 | 0.726159E+09 | 0.105185E+10 | 0.212421E+10 | 0.198127E+09 |
July | 0.176729E+10 | 0.765557E+09 | 0.100173E+10 | 0.217063E+10 | 0.213920E+09 |
August | 0.184063E+10 | 0.101565E+10 | 0.824983E+09 | 0.222592E+10 | 0.325477E+09 |
September | 0.142152E+10 | 0.849593E+09 | 0.571923E+09 | 0.156073E+10 | 0.586632E+09 |
October | 0.108726E+10 | 0.689452E+09 | 0.397804E+09 | 0.100029E+10 | 0.109436E+10 |
November | 0.570337E+09 | 0.401773E+09 | 0.168564E+09 | 0.370236E+09 | 0.186676E+10 |
December | 0.104210E+09 | 73415195.49 | 30794915.36 | 17361581.62 | 0.232437E+10 |
Annual Sum or Average | 0.163746E+11 | 0.937020E+10 | 0.700439E+10 | 0.175862E+11 | 0.126775E+11 |
Minimum of Months | 0.104210E+09 | 73415195.49 | 30794915.36 | 17361581.62 | 0.198127E+09 |
Maximum of Months | 0.236889E+10 | 0.147420E+10 | 0.105185E+10 | 0.266454E+10 | 0.232437E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 104.39 | 999.67 | 178.45 | 118.74 | 59.72 | 0.00 | 0.00 |
February | 508.29 | 802.61 | 596.34 | 413.90 | 182.44 | 0.00 | 0.00 |
March | 1008.31 | 614.68 | 1010.02 | 683.17 | 326.84 | 0.00 | 0.00 |
April | 1385.95 | 389.15 | 1238.14 | 770.52 | 467.62 | 0.00 | 0.00 |
May | 1194.76 | 187.18 | 1022.70 | 531.05 | 491.65 | 0.00 | 0.00 |
June | 1129.00 | 86.82 | 929.31 | 379.54 | 549.77 | 0.00 | 0.00 |
July | 1114.64 | 90.83 | 893.91 | 387.23 | 506.68 | 0.00 | 0.00 |
August | 1132.04 | 146.58 | 931.01 | 513.72 | 417.28 | 0.00 | 0.00 |
September | 813.28 | 289.94 | 742.98 | 444.06 | 298.93 | 0.00 | 0.00 |
October | 509.31 | 521.20 | 549.94 | 348.73 | 201.21 | 0.00 | 0.00 |
November | 195.30 | 933.49 | 298.10 | 209.99 | 88.10 | 0.00 | 0.00 |
December | 9.31 | 1112.99 | 52.71 | 37.13 | 15.58 | 0.00 | 0.00 |
Annual Sum or Average | 759.43 | 513.21 | 703.44 | 402.54 | 300.90 | 0.00 | 0.00 |
Minimum of Months | 9.31 | 86.82 | 52.71 | 37.13 | 15.58 | 0.00 | 0.00 |
Maximum of Months | 1385.95 | 1112.99 | 1238.14 | 770.52 | 549.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 291.89 | 2800.06 | 502.51 | 334.36 | 168.16 | 0.00 | 0.00 |
February | 1422.82 | 2248.23 | 1679.25 | 1165.53 | 513.73 | 0.00 | 0.00 |
March | 2823.57 | 1733.33 | 2844.14 | 1923.77 | 920.37 | 0.00 | 0.00 |
April | 3883.00 | 1121.52 | 3486.53 | 2169.73 | 1316.80 | 0.00 | 0.00 |
May | 3338.45 | 556.39 | 2879.86 | 1495.40 | 1384.46 | 0.00 | 0.00 |
June | 3147.40 | 266.89 | 2616.88 | 1068.77 | 1548.11 | 0.00 | 0.00 |
July | 3108.38 | 278.20 | 2517.19 | 1090.40 | 1426.79 | 0.00 | 0.00 |
August | 3163.76 | 442.28 | 2621.65 | 1446.61 | 1175.04 | 0.00 | 0.00 |
September | 2273.48 | 840.78 | 2092.19 | 1250.44 | 841.75 | 0.00 | 0.00 |
October | 1423.08 | 1472.70 | 1548.61 | 982.01 | 566.60 | 0.00 | 0.00 |
November | 545.72 | 2611.52 | 839.42 | 591.33 | 248.09 | 0.00 | 0.00 |
December | 25.90 | 3113.54 | 148.43 | 104.57 | 43.86 | 0.00 | 0.00 |
Annual Sum or Average | 2122.61 | 1453.32 | 1980.83 | 1133.52 | 847.32 | 0.00 | 0.00 |
Minimum of Months | 25.90 | 266.89 | 148.43 | 104.57 | 43.86 | 0.00 | 0.00 |
Maximum of Months | 3883.00 | 3113.54 | 3486.53 | 2169.73 | 1548.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 376.96 | 3799.80 | 652.79 | 434.35 | 218.44 | 0.00 | 0.00 |
February | 1857.72 | 3044.39 | 2181.45 | 1514.09 | 667.36 | 0.00 | 0.00 |
March | 3709.52 | 2348.64 | 3694.70 | 2499.09 | 1195.62 | 0.00 | 0.00 |
April | 5104.53 | 1528.19 | 4529.20 | 2818.61 | 1710.60 | 0.00 | 0.00 |
May | 4376.09 | 778.05 | 3741.10 | 1942.61 | 1798.50 | 0.00 | 0.00 |
June | 4118.45 | 381.47 | 3399.47 | 1388.39 | 2011.09 | 0.00 | 0.00 |
July | 4063.97 | 399.21 | 3269.98 | 1416.50 | 1853.48 | 0.00 | 0.00 |
August | 4136.83 | 625.87 | 3405.67 | 1879.23 | 1526.44 | 0.00 | 0.00 |
September | 2968.83 | 1180.64 | 2717.87 | 1624.39 | 1093.49 | 0.00 | 0.00 |
October | 1854.61 | 2033.82 | 2011.73 | 1275.68 | 736.05 | 0.00 | 0.00 |
November | 707.59 | 3541.46 | 1090.46 | 768.17 | 322.29 | 0.00 | 0.00 |
December | 32.69 | 4209.92 | 192.82 | 135.84 | 56.98 | 0.00 | 0.00 |
Annual Sum or Average | 2778.27 | 1984.25 | 2573.21 | 1472.50 | 1100.71 | 0.00 | 0.00 |
Minimum of Months | 32.69 | 381.47 | 192.82 | 135.84 | 56.98 | 0.00 | 0.00 |
Maximum of Months | 5104.53 | 4209.92 | 4529.20 | 2818.61 | 2011.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.68 | 597.95 | 42.56 | 24.72 | 17.84 | 0.00 | 0.00 |
February | 74.97 | 476.06 | 161.26 | 96.96 | 64.30 | 0.00 | 0.00 |
March | 254.31 | 356.59 | 330.06 | 191.39 | 138.68 | 0.00 | 0.00 |
April | 568.63 | 212.85 | 553.59 | 312.62 | 240.96 | 0.00 | 0.00 |
May | 550.70 | 100.00 | 501.76 | 241.63 | 260.13 | 0.00 | 0.00 |
June | 604.19 | 45.18 | 511.87 | 215.10 | 296.77 | 0.00 | 0.00 |
July | 544.32 | 48.20 | 450.85 | 180.11 | 270.74 | 0.00 | 0.00 |
August | 474.39 | 79.53 | 410.24 | 197.71 | 212.52 | 0.00 | 0.00 |
September | 274.12 | 165.11 | 283.00 | 144.53 | 138.46 | 0.00 | 0.00 |
October | 102.11 | 306.78 | 162.11 | 84.95 | 77.16 | 0.00 | 0.00 |
November | 21.69 | 555.94 | 80.53 | 49.45 | 31.08 | 0.00 | 0.00 |
December | 0.00 | 655.32 | 12.33 | 7.54 | 4.80 | 0.00 | 0.00 |
Annual Sum or Average | 290.51 | 299.12 | 292.03 | 145.58 | 146.46 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 45.18 | 12.33 | 7.54 | 4.80 | 0.00 | 0.00 |
Maximum of Months | 604.19 | 655.32 | 553.59 | 312.62 | 296.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 635.30 | 10.10 | 1.24 | 8.86 | 0.00 | 0.00 |
February | 4.38 | 543.81 | 55.86 | 15.12 | 40.74 | 0.00 | 0.00 |
March | 72.33 | 390.81 | 163.86 | 56.32 | 107.54 | 0.00 | 0.00 |
April | 327.80 | 213.00 | 369.96 | 162.03 | 207.93 | 0.00 | 0.00 |
May | 385.94 | 86.51 | 393.11 | 151.66 | 241.45 | 0.00 | 0.00 |
June | 496.82 | 37.29 | 449.24 | 166.95 | 282.29 | 0.00 | 0.00 |
July | 427.71 | 43.86 | 376.51 | 120.68 | 255.82 | 0.00 | 0.00 |
August | 305.41 | 76.53 | 292.16 | 100.11 | 192.05 | 0.00 | 0.00 |
September | 132.23 | 167.87 | 172.47 | 56.86 | 115.62 | 0.00 | 0.00 |
October | 19.32 | 341.35 | 70.98 | 16.00 | 54.99 | 0.00 | 0.00 |
November | 0.87 | 605.28 | 27.05 | 7.93 | 19.12 | 0.00 | 0.00 |
December | 0.00 | 667.60 | 2.77 | 0.20 | 2.58 | 0.00 | 0.00 |
Annual Sum or Average | 181.88 | 316.25 | 199.23 | 71.42 | 127.81 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 37.29 | 2.77 | 0.20 | 2.58 | 0.00 | 0.00 |
Maximum of Months | 496.82 | 667.60 | 449.24 | 166.95 | 282.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 18.06 | 141.55 | 28.22 | 18.78 | 9.44 | 0.00 | 0.00 |
February | 83.73 | 116.77 | 94.31 | 65.46 | 28.85 | 0.00 | 0.00 |
March | 156.20 | 106.74 | 159.73 | 108.04 | 51.69 | 0.00 | 0.00 |
April | 210.57 | 78.88 | 195.80 | 121.85 | 73.95 | 0.00 | 0.00 |
May | 178.42 | 43.34 | 161.73 | 83.98 | 77.75 | 0.00 | 0.00 |
June | 166.32 | 23.28 | 146.96 | 60.02 | 86.94 | 0.00 | 0.00 |
July | 164.60 | 24.21 | 141.37 | 61.24 | 80.13 | 0.00 | 0.00 |
August | 169.20 | 35.98 | 147.23 | 81.24 | 65.99 | 0.00 | 0.00 |
September | 120.34 | 63.44 | 117.50 | 70.22 | 47.27 | 0.00 | 0.00 |
October | 76.01 | 95.40 | 86.97 | 55.15 | 31.82 | 0.00 | 0.00 |
November | 33.87 | 131.61 | 47.14 | 33.21 | 13.93 | 0.00 | 0.00 |
December | 1.83 | 157.98 | 8.34 | 5.87 | 2.46 | 0.00 | 0.00 |
Annual Sum or Average | 114.99 | 84.79 | 111.24 | 63.66 | 47.59 | 0.00 | 0.00 |
Minimum of Months | 1.83 | 23.28 | 8.34 | 5.87 | 2.46 | 0.00 | 0.00 |
Maximum of Months | 210.57 | 157.98 | 195.80 | 121.85 | 86.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 182.65 | 2.26 | 0.00 | 2.26 | 0.00 | 0.00 |
February | 0.00 | 162.97 | 10.01 | 0.00 | 10.01 | 0.00 | 0.00 |
March | 2.08 | 120.94 | 26.80 | 0.00 | 26.80 | 0.00 | 0.00 |
April | 21.12 | 62.02 | 48.95 | 1.41 | 47.54 | 0.00 | 0.00 |
May | 64.28 | 23.67 | 74.86 | 12.02 | 62.83 | 0.00 | 0.00 |
June | 104.81 | 9.41 | 96.90 | 21.52 | 75.38 | 0.00 | 0.00 |
July | 91.49 | 11.34 | 81.93 | 13.71 | 68.22 | 0.00 | 0.00 |
August | 49.09 | 20.82 | 52.81 | 3.18 | 49.63 | 0.00 | 0.00 |
September | 12.49 | 49.66 | 29.11 | 0.10 | 29.01 | 0.00 | 0.00 |
October | 0.96 | 102.99 | 14.09 | 0.00 | 14.09 | 0.00 | 0.00 |
November | 0.00 | 177.79 | 4.37 | 0.00 | 4.37 | 0.00 | 0.00 |
December | 0.00 | 190.88 | 0.69 | 0.00 | 0.69 | 0.00 | 0.00 |
Annual Sum or Average | 29.03 | 92.55 | 37.03 | 4.35 | 32.68 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 9.41 | 0.69 | 0.00 | 0.69 | 0.00 | 0.00 |
Maximum of Months | 104.81 | 190.88 | 96.90 | 21.52 | 75.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 12.36 | 593.21 | 50.94 | 29.29 | 21.66 | 0.00 | 0.00 |
February | 121.09 | 471.73 | 199.08 | 120.77 | 78.31 | 0.00 | 0.00 |
March | 376.33 | 354.43 | 427.23 | 250.26 | 176.97 | 0.00 | 0.00 |
April | 549.63 | 202.10 | 547.49 | 305.63 | 241.86 | 0.00 | 0.00 |
May | 729.97 | 92.77 | 642.94 | 353.70 | 289.24 | 0.00 | 0.00 |
June | 700.36 | 38.99 | 587.42 | 263.51 | 323.91 | 0.00 | 0.00 |
July | 687.81 | 44.02 | 561.21 | 263.45 | 297.76 | 0.00 | 0.00 |
August | 579.76 | 75.16 | 492.98 | 252.90 | 240.08 | 0.00 | 0.00 |
September | 343.74 | 160.95 | 340.27 | 175.24 | 165.03 | 0.00 | 0.00 |
October | 167.26 | 305.75 | 213.50 | 111.40 | 102.10 | 0.00 | 0.00 |
November | 20.33 | 554.09 | 80.67 | 49.43 | 31.25 | 0.00 | 0.00 |
December | 0.00 | 653.37 | 13.52 | 8.08 | 5.44 | 0.00 | 0.00 |
Annual Sum or Average | 358.82 | 294.72 | 347.18 | 182.29 | 164.89 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 38.99 | 13.52 | 8.08 | 5.44 | 0.00 | 0.00 |
Maximum of Months | 729.97 | 653.37 | 642.94 | 353.70 | 323.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.73 | 623.76 | 18.49 | 5.81 | 12.68 | 0.00 | 0.00 |
February | 29.66 | 516.40 | 93.68 | 38.93 | 54.75 | 0.00 | 0.00 |
March | 183.32 | 375.94 | 261.03 | 115.19 | 145.84 | 0.00 | 0.00 |
April | 304.88 | 199.79 | 363.86 | 155.04 | 208.82 | 0.00 | 0.00 |
May | 575.18 | 89.15 | 534.29 | 263.73 | 270.56 | 0.00 | 0.00 |
June | 601.99 | 37.42 | 524.79 | 215.36 | 309.42 | 0.00 | 0.00 |
July | 574.83 | 44.10 | 486.87 | 204.03 | 282.84 | 0.00 | 0.00 |
August | 416.47 | 76.40 | 374.91 | 155.30 | 219.61 | 0.00 | 0.00 |
September | 199.83 | 162.56 | 229.75 | 87.56 | 142.19 | 0.00 | 0.00 |
October | 69.78 | 324.43 | 122.37 | 42.45 | 79.92 | 0.00 | 0.00 |
November | 0.51 | 604.43 | 27.20 | 7.91 | 19.29 | 0.00 | 0.00 |
December | 0.00 | 665.50 | 3.95 | 0.74 | 3.22 | 0.00 | 0.00 |
Annual Sum or Average | 247.88 | 308.94 | 254.38 | 108.14 | 146.24 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 37.42 | 3.95 | 0.74 | 3.22 | 0.00 | 0.00 |
Maximum of Months | 601.99 | 665.50 | 534.29 | 263.73 | 309.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 15.92 | 747.76 | 66.05 | 40.69 | 25.37 | 0.00 | 0.00 |
February | 121.78 | 597.65 | 226.01 | 141.82 | 84.19 | 0.00 | 0.00 |
March | 316.58 | 452.56 | 404.15 | 234.10 | 170.05 | 0.00 | 0.00 |
April | 517.50 | 271.91 | 530.29 | 267.06 | 263.23 | 0.00 | 0.00 |
May | 534.00 | 116.10 | 512.59 | 208.01 | 304.58 | 0.00 | 0.00 |
June | 596.53 | 50.76 | 528.35 | 176.66 | 351.69 | 0.00 | 0.00 |
July | 567.54 | 59.98 | 483.79 | 162.39 | 321.41 | 0.00 | 0.00 |
August | 486.56 | 102.29 | 433.41 | 182.91 | 250.50 | 0.00 | 0.00 |
September | 302.25 | 210.87 | 317.64 | 152.36 | 165.28 | 0.00 | 0.00 |
October | 148.35 | 386.14 | 218.95 | 119.49 | 99.46 | 0.00 | 0.00 |
November | 33.87 | 695.90 | 111.61 | 71.95 | 39.66 | 0.00 | 0.00 |
December | 0.12 | 821.98 | 19.55 | 12.72 | 6.82 | 0.00 | 0.00 |
Annual Sum or Average | 304.26 | 375.09 | 321.26 | 147.35 | 173.91 | 0.00 | 0.00 |
Minimum of Months | 0.12 | 50.76 | 19.55 | 12.72 | 6.82 | 0.00 | 0.00 |
Maximum of Months | 596.53 | 821.98 | 530.29 | 267.06 | 351.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.83 | 593.92 | 42.56 | 24.72 | 17.84 | 0.00 | 0.00 |
February | 76.19 | 472.50 | 161.26 | 96.96 | 64.30 | 0.00 | 0.00 |
March | 255.76 | 354.51 | 330.06 | 191.39 | 138.68 | 0.00 | 0.00 |
April | 567.25 | 211.65 | 553.59 | 312.62 | 240.96 | 0.00 | 0.00 |
May | 548.85 | 98.97 | 501.76 | 241.63 | 260.13 | 0.00 | 0.00 |
June | 601.79 | 44.49 | 511.87 | 215.10 | 296.77 | 0.00 | 0.00 |
July | 542.27 | 47.46 | 450.85 | 180.11 | 270.74 | 0.00 | 0.00 |
August | 472.99 | 78.46 | 410.24 | 197.71 | 212.52 | 0.00 | 0.00 |
September | 274.58 | 163.06 | 283.00 | 144.53 | 138.46 | 0.00 | 0.00 |
October | 103.34 | 304.31 | 162.11 | 84.95 | 77.16 | 0.00 | 0.00 |
November | 22.22 | 550.30 | 80.53 | 49.45 | 31.08 | 0.00 | 0.00 |
December | 0.00 | 651.00 | 12.33 | 7.54 | 4.80 | 0.00 | 0.00 |
Annual Sum or Average | 290.16 | 296.72 | 292.03 | 145.58 | 146.46 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 44.49 | 12.33 | 7.54 | 4.80 | 0.00 | 0.00 |
Maximum of Months | 601.79 | 651.00 | 553.59 | 312.62 | 296.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 631.25 | 10.10 | 1.24 | 8.86 | 0.00 | 0.00 |
February | 4.54 | 539.97 | 55.86 | 15.12 | 40.74 | 0.00 | 0.00 |
March | 72.96 | 388.55 | 163.86 | 56.32 | 107.54 | 0.00 | 0.00 |
April | 327.79 | 211.57 | 369.96 | 162.03 | 207.93 | 0.00 | 0.00 |
May | 384.74 | 86.06 | 393.11 | 151.66 | 241.45 | 0.00 | 0.00 |
June | 493.33 | 37.49 | 449.24 | 166.95 | 282.29 | 0.00 | 0.00 |
July | 425.13 | 43.93 | 376.51 | 120.68 | 255.82 | 0.00 | 0.00 |
August | 304.13 | 76.21 | 292.16 | 100.11 | 192.05 | 0.00 | 0.00 |
September | 133.51 | 165.28 | 172.47 | 56.86 | 115.62 | 0.00 | 0.00 |
October | 20.00 | 338.60 | 70.98 | 16.00 | 54.99 | 0.00 | 0.00 |
November | 0.90 | 599.36 | 27.05 | 7.93 | 19.12 | 0.00 | 0.00 |
December | 0.00 | 663.31 | 2.77 | 0.20 | 2.58 | 0.00 | 0.00 |
Annual Sum or Average | 181.39 | 313.96 | 199.23 | 71.42 | 127.81 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 37.49 | 2.77 | 0.20 | 2.58 | 0.00 | 0.00 |
Maximum of Months | 493.33 | 663.31 | 449.24 | 166.95 | 282.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 30.01 | 296.28 | 51.75 | 34.43 | 17.32 | 0.00 | 0.00 |
February | 146.02 | 238.74 | 172.92 | 120.02 | 52.90 | 0.00 | 0.00 |
March | 289.42 | 184.75 | 292.88 | 198.10 | 94.78 | 0.00 | 0.00 |
April | 399.04 | 115.93 | 359.03 | 223.43 | 135.60 | 0.00 | 0.00 |
May | 343.81 | 54.65 | 296.56 | 153.99 | 142.57 | 0.00 | 0.00 |
June | 326.36 | 23.94 | 269.47 | 110.06 | 159.42 | 0.00 | 0.00 |
July | 322.54 | 25.16 | 259.21 | 112.28 | 146.92 | 0.00 | 0.00 |
August | 326.99 | 41.79 | 269.97 | 148.97 | 121.00 | 0.00 | 0.00 |
September | 233.97 | 86.22 | 215.44 | 128.76 | 86.68 | 0.00 | 0.00 |
October | 145.61 | 155.80 | 159.47 | 101.12 | 58.35 | 0.00 | 0.00 |
November | 57.01 | 273.71 | 86.44 | 60.89 | 25.55 | 0.00 | 0.00 |
December | 2.76 | 328.11 | 15.28 | 10.77 | 4.52 | 0.00 | 0.00 |
Annual Sum or Average | 218.84 | 151.68 | 203.98 | 116.72 | 87.25 | 0.00 | 0.00 |
Minimum of Months | 2.76 | 23.94 | 15.28 | 10.77 | 4.52 | 0.00 | 0.00 |
Maximum of Months | 399.04 | 328.11 | 359.03 | 223.43 | 159.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1636.66 | 19.80 | 0.00 | 19.80 | 0.00 | 0.00 |
February | 0.00 | 1467.88 | 87.53 | 0.00 | 87.53 | 0.00 | 0.00 |
March | 13.56 | 1118.38 | 234.48 | 0.04 | 234.44 | 0.00 | 0.00 |
April | 159.47 | 596.55 | 428.23 | 12.29 | 415.94 | 0.00 | 0.00 |
May | 518.68 | 232.22 | 654.88 | 105.19 | 549.69 | 0.00 | 0.00 |
June | 879.34 | 96.55 | 847.73 | 188.24 | 659.49 | 0.00 | 0.00 |
July | 766.27 | 115.15 | 716.79 | 119.95 | 596.84 | 0.00 | 0.00 |
August | 397.04 | 206.90 | 461.98 | 27.81 | 434.18 | 0.00 | 0.00 |
September | 92.12 | 486.43 | 254.65 | 0.84 | 253.81 | 0.00 | 0.00 |
October | 5.39 | 972.29 | 123.23 | 0.00 | 123.23 | 0.00 | 0.00 |
November | 0.00 | 1589.03 | 38.24 | 0.00 | 38.24 | 0.00 | 0.00 |
December | 0.00 | 1698.49 | 6.01 | 0.00 | 6.01 | 0.00 | 0.00 |
Annual Sum or Average | 237.42 | 848.06 | 323.97 | 38.04 | 285.93 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 96.55 | 6.01 | 0.00 | 6.01 | 0.00 | 0.00 |
Maximum of Months | 879.34 | 1698.49 | 847.73 | 188.24 | 659.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1662.73 | 19.80 | 0.00 | 19.80 | 0.00 | 0.00 |
February | 0.00 | 1492.91 | 87.53 | 0.00 | 87.53 | 0.00 | 0.00 |
March | 11.82 | 1141.51 | 234.48 | 0.04 | 234.44 | 0.00 | 0.00 |
April | 151.55 | 609.82 | 428.23 | 12.29 | 415.94 | 0.00 | 0.00 |
May | 507.64 | 236.93 | 654.88 | 105.19 | 549.69 | 0.00 | 0.00 |
June | 870.37 | 99.06 | 847.73 | 188.24 | 659.49 | 0.00 | 0.00 |
July | 757.93 | 118.15 | 716.79 | 119.95 | 596.84 | 0.00 | 0.00 |
August | 388.48 | 212.18 | 461.98 | 27.81 | 434.18 | 0.00 | 0.00 |
September | 86.14 | 500.32 | 254.65 | 0.84 | 253.81 | 0.00 | 0.00 |
October | 4.30 | 995.83 | 123.23 | 0.00 | 123.23 | 0.00 | 0.00 |
November | 0.00 | 1615.24 | 38.24 | 0.00 | 38.24 | 0.00 | 0.00 |
December | 0.00 | 1723.80 | 6.01 | 0.00 | 6.01 | 0.00 | 0.00 |
Annual Sum or Average | 232.92 | 864.00 | 323.97 | 38.04 | 285.93 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 99.06 | 6.01 | 0.00 | 6.01 | 0.00 | 0.00 |
Maximum of Months | 870.37 | 1723.80 | 847.73 | 188.24 | 659.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 14.79 | 1033.78 | 69.43 | 35.10 | 34.33 | 0.00 | 0.00 |
February | 177.19 | 828.97 | 292.74 | 159.69 | 133.05 | 0.00 | 0.00 |
March | 651.96 | 630.29 | 688.23 | 365.44 | 322.79 | 0.00 | 0.00 |
April | 1031.26 | 368.85 | 911.30 | 460.64 | 450.66 | 0.00 | 0.00 |
May | 1530.70 | 170.24 | 1177.16 | 617.39 | 559.77 | 0.00 | 0.00 |
June | 1557.79 | 75.73 | 1112.15 | 478.85 | 633.30 | 0.00 | 0.00 |
July | 1519.91 | 85.50 | 1048.02 | 467.46 | 580.57 | 0.00 | 0.00 |
August | 1229.33 | 137.15 | 867.84 | 408.17 | 459.67 | 0.00 | 0.00 |
September | 705.01 | 269.55 | 569.99 | 262.79 | 307.20 | 0.00 | 0.00 |
October | 303.04 | 520.86 | 335.85 | 153.84 | 182.01 | 0.00 | 0.00 |
November | 19.14 | 965.74 | 107.87 | 57.33 | 50.54 | 0.00 | 0.00 |
December | 0.00 | 1131.27 | 17.47 | 8.81 | 8.66 | 0.00 | 0.00 |
Annual Sum or Average | 731.78 | 516.68 | 601.54 | 290.42 | 311.12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 75.73 | 17.47 | 8.81 | 8.66 | 0.00 | 0.00 |
Maximum of Months | 1557.79 | 1131.27 | 1177.16 | 617.39 | 633.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 44.84 | 1311.16 | 138.51 | 87.64 | 50.87 | 0.00 | 0.00 |
February | 297.46 | 1047.67 | 470.19 | 305.52 | 164.67 | 0.00 | 0.00 |
March | 697.63 | 799.17 | 825.91 | 504.29 | 321.62 | 0.00 | 0.00 |
April | 1074.71 | 484.83 | 1060.72 | 572.96 | 487.76 | 0.00 | 0.00 |
May | 1038.59 | 207.67 | 979.39 | 428.05 | 551.34 | 0.00 | 0.00 |
June | 1101.03 | 92.87 | 976.57 | 344.68 | 631.88 | 0.00 | 0.00 |
July | 1059.69 | 109.68 | 905.55 | 326.95 | 578.60 | 0.00 | 0.00 |
August | 959.53 | 183.76 | 845.58 | 388.73 | 456.85 | 0.00 | 0.00 |
September | 628.07 | 373.67 | 635.72 | 328.06 | 307.66 | 0.00 | 0.00 |
October | 333.31 | 684.71 | 448.18 | 257.41 | 190.77 | 0.00 | 0.00 |
November | 92.22 | 1212.15 | 233.15 | 155.00 | 78.14 | 0.00 | 0.00 |
December | 1.49 | 1445.72 | 40.97 | 27.41 | 13.56 | 0.00 | 0.00 |
Annual Sum or Average | 612.05 | 660.93 | 630.29 | 310.17 | 320.13 | 0.00 | 0.00 |
Minimum of Months | 1.49 | 92.87 | 40.97 | 27.41 | 13.56 | 0.00 | 0.00 |
Maximum of Months | 1101.03 | 1445.72 | 1060.72 | 572.96 | 631.88 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.279606E+09 | 0.267752E+10 | 0.477969E+09 | 0.318027E+09 | 0.159942E+09 | 0.00 | 0.00 |
February | 0.122965E+10 | 0.194168E+10 | 0.144266E+10 | 0.100132E+10 | 0.441347E+09 | 0.00 | 0.00 |
March | 0.270065E+10 | 0.164635E+10 | 0.270523E+10 | 0.182981E+10 | 0.875421E+09 | 0.00 | 0.00 |
April | 0.359238E+10 | 0.100867E+10 | 0.320927E+10 | 0.199719E+10 | 0.121208E+10 | 0.00 | 0.00 |
May | 0.320004E+10 | 0.501355E+09 | 0.273921E+10 | 0.142236E+10 | 0.131684E+10 | 0.00 | 0.00 |
June | 0.292637E+10 | 0.225039E+09 | 0.240877E+10 | 0.983773E+09 | 0.142500E+10 | 0.00 | 0.00 |
July | 0.298546E+10 | 0.243274E+09 | 0.239425E+10 | 0.103715E+10 | 0.135710E+10 | 0.00 | 0.00 |
August | 0.303206E+10 | 0.392605E+09 | 0.249361E+10 | 0.137596E+10 | 0.111765E+10 | 0.00 | 0.00 |
September | 0.210803E+10 | 0.751531E+09 | 0.192581E+10 | 0.115100E+10 | 0.774815E+09 | 0.00 | 0.00 |
October | 0.136414E+10 | 0.139597E+10 | 0.147297E+10 | 0.934043E+09 | 0.538928E+09 | 0.00 | 0.00 |
November | 0.506214E+09 | 0.241962E+10 | 0.772670E+09 | 0.544306E+09 | 0.228364E+09 | 0.00 | 0.00 |
December | 24938342.03 | 0.298104E+10 | 0.141180E+09 | 99460103.64 | 41719703.73 | 0.00 | 0.00 |
Annual Sum or Average | 0.239495E+11 | 0.161846E+11 | 0.221836E+11 | 0.126944E+11 | 0.948921E+10 | 0.00 | 0.00 |
Minimum of Months | 24938342.03 | 0.225039E+09 | 0.141180E+09 | 99460103.64 | 41719703.73 | 0.00 | 0.00 |
Maximum of Months | 0.359238E+10 | 0.298104E+10 | 0.320927E+10 | 0.199719E+10 | 0.142500E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.781804E+09 | 0.749969E+10 | 0.134593E+10 | 0.895543E+09 | 0.450387E+09 | 0.00 | 0.00 |
February | 0.344208E+10 | 0.543893E+10 | 0.406245E+10 | 0.281964E+10 | 0.124281E+10 | 0.00 | 0.00 |
March | 0.756266E+10 | 0.464255E+10 | 0.761775E+10 | 0.515262E+10 | 0.246513E+10 | 0.00 | 0.00 |
April | 0.100647E+11 | 0.290699E+10 | 0.903709E+10 | 0.562395E+10 | 0.341314E+10 | 0.00 | 0.00 |
May | 0.894170E+10 | 0.149025E+10 | 0.771342E+10 | 0.400528E+10 | 0.370815E+10 | 0.00 | 0.00 |
June | 0.815805E+10 | 0.691776E+09 | 0.678295E+10 | 0.277024E+10 | 0.401271E+10 | 0.00 | 0.00 |
July | 0.832547E+10 | 0.745137E+09 | 0.674205E+10 | 0.292054E+10 | 0.382151E+10 | 0.00 | 0.00 |
August | 0.847381E+10 | 0.118460E+10 | 0.702183E+10 | 0.387461E+10 | 0.314722E+10 | 0.00 | 0.00 |
September | 0.589286E+10 | 0.217929E+10 | 0.542296E+10 | 0.324113E+10 | 0.218183E+10 | 0.00 | 0.00 |
October | 0.381159E+10 | 0.394447E+10 | 0.414779E+10 | 0.263020E+10 | 0.151759E+10 | 0.00 | 0.00 |
November | 0.141449E+10 | 0.676905E+10 | 0.217579E+10 | 0.153273E+10 | 0.643057E+09 | 0.00 | 0.00 |
December | 69364993.15 | 0.833930E+10 | 0.397553E+09 | 0.280073E+09 | 0.117480E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.669386E+11 | 0.458320E+11 | 0.624676E+11 | 0.357466E+11 | 0.267210E+11 | 0.00 | 0.00 |
Minimum of Months | 69364993.15 | 0.691776E+09 | 0.397553E+09 | 0.280073E+09 | 0.117480E+09 | 0.00 | 0.00 |
Maximum of Months | 0.100647E+11 | 0.833930E+10 | 0.903709E+10 | 0.562395E+10 | 0.401271E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100964E+10 | 0.101774E+11 | 0.174844E+10 | 0.116336E+10 | 0.585078E+09 | 0.00 | 0.00 |
February | 0.449420E+10 | 0.736499E+10 | 0.527735E+10 | 0.366288E+10 | 0.161447E+10 | 0.00 | 0.00 |
March | 0.993558E+10 | 0.629061E+10 | 0.989589E+10 | 0.669355E+10 | 0.320234E+10 | 0.00 | 0.00 |
April | 0.132310E+11 | 0.396107E+10 | 0.117397E+11 | 0.730582E+10 | 0.443386E+10 | 0.00 | 0.00 |
May | 0.117209E+11 | 0.208392E+10 | 0.100202E+11 | 0.520308E+10 | 0.481709E+10 | 0.00 | 0.00 |
June | 0.106750E+11 | 0.988771E+09 | 0.881144E+10 | 0.359870E+10 | 0.521274E+10 | 0.00 | 0.00 |
July | 0.108849E+11 | 0.106924E+10 | 0.875830E+10 | 0.379395E+10 | 0.496436E+10 | 0.00 | 0.00 |
August | 0.110801E+11 | 0.167632E+10 | 0.912176E+10 | 0.503334E+10 | 0.408842E+10 | 0.00 | 0.00 |
September | 0.769521E+10 | 0.306021E+10 | 0.704473E+10 | 0.421041E+10 | 0.283432E+10 | 0.00 | 0.00 |
October | 0.496738E+10 | 0.544738E+10 | 0.538822E+10 | 0.341678E+10 | 0.197143E+10 | 0.00 | 0.00 |
November | 0.183408E+10 | 0.917947E+10 | 0.282647E+10 | 0.199110E+10 | 0.835368E+09 | 0.00 | 0.00 |
December | 87559714.80 | 0.112758E+11 | 0.516444E+09 | 0.363831E+09 | 0.152613E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.876155E+11 | 0.625752E+11 | 0.811489E+11 | 0.464368E+11 | 0.347121E+11 | 0.00 | 0.00 |
Minimum of Months | 87559714.80 | 0.988771E+09 | 0.516444E+09 | 0.363831E+09 | 0.152613E+09 | 0.00 | 0.00 |
Maximum of Months | 0.132310E+11 | 0.112758E+11 | 0.117397E+11 | 0.730582E+10 | 0.521274E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 15203732.51 | 0.160155E+10 | 0.113990E+09 | 66207315.62 | 47782214.36 | 0.00 | 0.00 |
February | 0.181365E+09 | 0.115168E+10 | 0.390116E+09 | 0.234554E+09 | 0.155563E+09 | 0.00 | 0.00 |
March | 0.681146E+09 | 0.955101E+09 | 0.884045E+09 | 0.512616E+09 | 0.371429E+09 | 0.00 | 0.00 |
April | 0.147389E+10 | 0.551709E+09 | 0.143490E+10 | 0.810318E+09 | 0.624580E+09 | 0.00 | 0.00 |
May | 0.147500E+10 | 0.267830E+09 | 0.134392E+10 | 0.647190E+09 | 0.696733E+09 | 0.00 | 0.00 |
June | 0.156607E+10 | 0.117097E+09 | 0.132678E+10 | 0.557548E+09 | 0.769229E+09 | 0.00 | 0.00 |
July | 0.145790E+10 | 0.129106E+09 | 0.120755E+10 | 0.482401E+09 | 0.725150E+09 | 0.00 | 0.00 |
August | 0.127059E+10 | 0.213026E+09 | 0.109878E+10 | 0.529556E+09 | 0.569222E+09 | 0.00 | 0.00 |
September | 0.710516E+09 | 0.427954E+09 | 0.733524E+09 | 0.374633E+09 | 0.358891E+09 | 0.00 | 0.00 |
October | 0.273486E+09 | 0.821686E+09 | 0.434202E+09 | 0.227526E+09 | 0.206676E+09 | 0.00 | 0.00 |
November | 56220115.98 | 0.144099E+10 | 0.208723E+09 | 0.128163E+09 | 80559550.02 | 0.00 | 0.00 |
December | 0.00 | 0.175521E+10 | 33037168.42 | 20187795.43 | 12849372.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.916139E+10 | 0.943294E+10 | 0.920957E+10 | 0.459090E+10 | 0.461866E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.117097E+09 | 33037168.42 | 20187795.43 | 12849372.99 | 0.00 | 0.00 |
Maximum of Months | 0.156607E+10 | 0.175521E+10 | 0.143490E+10 | 0.810318E+09 | 0.769229E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.170158E+10 | 27063910.43 | 3327943.48 | 23735966.96 | 0.00 | 0.00 |
February | 10606442.91 | 0.131559E+10 | 0.135130E+09 | 36576040.05 | 98553634.11 | 0.00 | 0.00 |
March | 0.193742E+09 | 0.104676E+10 | 0.438895E+09 | 0.150847E+09 | 0.288048E+09 | 0.00 | 0.00 |
April | 0.849662E+09 | 0.552095E+09 | 0.958943E+09 | 0.419992E+09 | 0.538951E+09 | 0.00 | 0.00 |
May | 0.103369E+10 | 0.231695E+09 | 0.105292E+10 | 0.406216E+09 | 0.646703E+09 | 0.00 | 0.00 |
June | 0.128775E+10 | 96651706.09 | 0.116443E+10 | 0.432745E+09 | 0.731690E+09 | 0.00 | 0.00 |
July | 0.114558E+10 | 0.117485E+09 | 0.100844E+10 | 0.323239E+09 | 0.685201E+09 | 0.00 | 0.00 |
August | 0.818005E+09 | 0.204988E+09 | 0.782523E+09 | 0.268145E+09 | 0.514377E+09 | 0.00 | 0.00 |
September | 0.342739E+09 | 0.435120E+09 | 0.447053E+09 | 0.147371E+09 | 0.299682E+09 | 0.00 | 0.00 |
October | 51753368.89 | 0.914278E+09 | 0.190123E+09 | 42849611.93 | 0.147273E+09 | 0.00 | 0.00 |
November | 2259431.59 | 0.156888E+10 | 70113503.71 | 20544393.39 | 49569110.31 | 0.00 | 0.00 |
December | 0.00 | 0.178810E+10 | 7421980.86 | 522824.73 | 6899156.13 | 0.00 | 0.00 |
Annual Sum or Average | 0.573579E+10 | 0.997322E+10 | 0.628306E+10 | 0.225237E+10 | 0.403068E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 96651706.09 | 7421980.86 | 522824.73 | 6899156.13 | 0.00 | 0.00 |
Maximum of Months | 0.128775E+10 | 0.178810E+10 | 0.116443E+10 | 0.432745E+09 | 0.731690E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 48379921.37 | 0.379130E+09 | 75587157.08 | 50293495.70 | 25293661.38 | 0.00 | 0.00 |
February | 0.202571E+09 | 0.282488E+09 | 0.228147E+09 | 0.158351E+09 | 69795900.67 | 0.00 | 0.00 |
March | 0.418367E+09 | 0.285886E+09 | 0.427812E+09 | 0.289370E+09 | 0.138442E+09 | 0.00 | 0.00 |
April | 0.545800E+09 | 0.204468E+09 | 0.507522E+09 | 0.315840E+09 | 0.191683E+09 | 0.00 | 0.00 |
May | 0.477876E+09 | 0.116077E+09 | 0.433186E+09 | 0.224936E+09 | 0.208250E+09 | 0.00 | 0.00 |
June | 0.431103E+09 | 60347924.49 | 0.380931E+09 | 0.155576E+09 | 0.225355E+09 | 0.00 | 0.00 |
July | 0.440872E+09 | 64855482.50 | 0.378634E+09 | 0.164017E+09 | 0.214617E+09 | 0.00 | 0.00 |
August | 0.453191E+09 | 96362685.54 | 0.394346E+09 | 0.217597E+09 | 0.176749E+09 | 0.00 | 0.00 |
September | 0.311916E+09 | 0.164426E+09 | 0.304553E+09 | 0.182021E+09 | 0.122532E+09 | 0.00 | 0.00 |
October | 0.203584E+09 | 0.255518E+09 | 0.232939E+09 | 0.147712E+09 | 85227669.47 | 0.00 | 0.00 |
November | 87793737.94 | 0.341126E+09 | 0.122192E+09 | 86077848.02 | 36114043.15 | 0.00 | 0.00 |
December | 4911067.09 | 0.423135E+09 | 22326509.33 | 15728848.52 | 6597660.82 | 0.00 | 0.00 |
Annual Sum or Average | 0.362636E+10 | 0.267382E+10 | 0.350818E+10 | 0.200752E+10 | 0.150066E+10 | 0.00 | 0.00 |
Minimum of Months | 4911067.09 | 60347924.49 | 22326509.33 | 15728848.52 | 6597660.82 | 0.00 | 0.00 |
Maximum of Months | 0.545800E+09 | 0.423135E+09 | 0.507522E+09 | 0.315840E+09 | 0.225355E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.489216E+09 | 6062497.20 | 0.00 | 6062497.20 | 0.00 | 0.00 |
February | 0.00 | 0.394266E+09 | 24205710.07 | 0.00 | 24205710.07 | 0.00 | 0.00 |
March | 5580920.24 | 0.323918E+09 | 71786871.05 | 12417.67 | 71774453.38 | 0.00 | 0.00 |
April | 54744836.60 | 0.160760E+09 | 0.126876E+09 | 3641923.15 | 0.123234E+09 | 0.00 | 0.00 |
May | 0.172162E+09 | 63387346.84 | 0.200495E+09 | 32204855.03 | 0.168290E+09 | 0.00 | 0.00 |
June | 0.271659E+09 | 24387097.91 | 0.251166E+09 | 55772213.67 | 0.195394E+09 | 0.00 | 0.00 |
July | 0.245040E+09 | 30383642.75 | 0.219449E+09 | 36724219.00 | 0.182725E+09 | 0.00 | 0.00 |
August | 0.131486E+09 | 55770069.12 | 0.141438E+09 | 8512778.15 | 0.132926E+09 | 0.00 | 0.00 |
September | 32376635.22 | 0.128713E+09 | 75446330.45 | 247489.23 | 75198841.21 | 0.00 | 0.00 |
October | 2570903.27 | 0.275846E+09 | 37727112.88 | 0.00 | 37727112.88 | 0.00 | 0.00 |
November | 0.00 | 0.460837E+09 | 11330375.20 | 0.00 | 11330375.20 | 0.00 | 0.00 |
December | 0.00 | 0.511259E+09 | 1839043.17 | 0.00 | 1839043.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.915620E+09 | 0.291874E+10 | 0.116782E+10 | 0.137116E+09 | 0.103071E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 24387097.91 | 1839043.17 | 0.00 | 1839043.17 | 0.00 | 0.00 |
Maximum of Months | 0.271659E+09 | 0.511259E+09 | 0.251166E+09 | 55772213.67 | 0.195394E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 33102665.11 | 0.158886E+10 | 0.136448E+09 | 78443716.40 | 58004180.96 | 0.00 | 0.00 |
February | 0.292945E+09 | 0.114122E+10 | 0.481607E+09 | 0.292157E+09 | 0.189449E+09 | 0.00 | 0.00 |
March | 0.100795E+10 | 0.949315E+09 | 0.114430E+10 | 0.670304E+09 | 0.473997E+09 | 0.00 | 0.00 |
April | 0.142464E+10 | 0.523849E+09 | 0.141908E+10 | 0.792184E+09 | 0.626899E+09 | 0.00 | 0.00 |
May | 0.195515E+10 | 0.248488E+09 | 0.172204E+10 | 0.947347E+09 | 0.774692E+09 | 0.00 | 0.00 |
June | 0.181532E+10 | 0.101073E+09 | 0.152259E+10 | 0.683027E+09 | 0.839567E+09 | 0.00 | 0.00 |
July | 0.184223E+10 | 0.117896E+09 | 0.150314E+10 | 0.705635E+09 | 0.797508E+09 | 0.00 | 0.00 |
August | 0.155283E+10 | 0.201297E+09 | 0.132040E+10 | 0.677361E+09 | 0.643043E+09 | 0.00 | 0.00 |
September | 0.890973E+09 | 0.417188E+09 | 0.881981E+09 | 0.454225E+09 | 0.427756E+09 | 0.00 | 0.00 |
October | 0.447990E+09 | 0.818927E+09 | 0.571828E+09 | 0.298371E+09 | 0.273457E+09 | 0.00 | 0.00 |
November | 52692413.81 | 0.143621E+10 | 0.209106E+09 | 0.128112E+09 | 80993168.26 | 0.00 | 0.00 |
December | 0.00 | 0.174999E+10 | 36205317.59 | 21637645.56 | 14567672.03 | 0.00 | 0.00 |
Annual Sum or Average | 0.113158E+11 | 0.929431E+10 | 0.109487E+11 | 0.574881E+10 | 0.519993E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.101073E+09 | 36205317.59 | 21637645.56 | 14567672.03 | 0.00 | 0.00 |
Maximum of Months | 0.195515E+10 | 0.174999E+10 | 0.172204E+10 | 0.947347E+09 | 0.839567E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1968221.05 | 0.167067E+10 | 49522277.81 | 15564344.25 | 33957933.56 | 0.00 | 0.00 |
February | 71749062.26 | 0.124927E+10 | 0.226620E+09 | 94179516.98 | 0.132440E+09 | 0.00 | 0.00 |
March | 0.491007E+09 | 0.100692E+10 | 0.699151E+09 | 0.308535E+09 | 0.390616E+09 | 0.00 | 0.00 |
April | 0.790261E+09 | 0.517848E+09 | 0.943127E+09 | 0.401858E+09 | 0.541270E+09 | 0.00 | 0.00 |
May | 0.154057E+10 | 0.238779E+09 | 0.143103E+10 | 0.706373E+09 | 0.724662E+09 | 0.00 | 0.00 |
June | 0.156036E+10 | 96999974.69 | 0.136025E+10 | 0.558224E+09 | 0.802027E+09 | 0.00 | 0.00 |
July | 0.153964E+10 | 0.118131E+09 | 0.130403E+10 | 0.546472E+09 | 0.757559E+09 | 0.00 | 0.00 |
August | 0.111547E+10 | 0.204630E+09 | 0.100415E+10 | 0.415950E+09 | 0.588198E+09 | 0.00 | 0.00 |
September | 0.517957E+09 | 0.421343E+09 | 0.595510E+09 | 0.226963E+09 | 0.368547E+09 | 0.00 | 0.00 |
October | 0.186893E+09 | 0.868943E+09 | 0.327749E+09 | 0.113695E+09 | 0.214054E+09 | 0.00 | 0.00 |
November | 1328772.72 | 0.156667E+10 | 70496352.41 | 20493623.86 | 50002728.55 | 0.00 | 0.00 |
December | 0.00 | 0.178247E+10 | 10590130.03 | 1972674.86 | 8617455.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.781719E+10 | 0.974267E+10 | 0.802223E+10 | 0.341028E+10 | 0.461195E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 96999974.69 | 10590130.03 | 1972674.86 | 8617455.17 | 0.00 | 0.00 |
Maximum of Months | 0.156036E+10 | 0.178247E+10 | 0.143103E+10 | 0.706373E+09 | 0.802027E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 42651471.69 | 0.200281E+10 | 0.176910E+09 | 0.108972E+09 | 67937732.10 | 0.00 | 0.00 |
February | 0.294621E+09 | 0.144582E+10 | 0.546768E+09 | 0.343102E+09 | 0.203666E+09 | 0.00 | 0.00 |
March | 0.847933E+09 | 0.121213E+10 | 0.108246E+10 | 0.627012E+09 | 0.455452E+09 | 0.00 | 0.00 |
April | 0.134135E+10 | 0.704783E+09 | 0.137451E+10 | 0.692226E+09 | 0.682289E+09 | 0.00 | 0.00 |
May | 0.143027E+10 | 0.310959E+09 | 0.137293E+10 | 0.557139E+09 | 0.815793E+09 | 0.00 | 0.00 |
June | 0.154620E+10 | 0.131569E+09 | 0.136948E+10 | 0.457912E+09 | 0.911569E+09 | 0.00 | 0.00 |
July | 0.152010E+10 | 0.160641E+09 | 0.129579E+10 | 0.434936E+09 | 0.860858E+09 | 0.00 | 0.00 |
August | 0.130319E+10 | 0.273962E+09 | 0.116084E+10 | 0.489914E+09 | 0.670926E+09 | 0.00 | 0.00 |
September | 0.783443E+09 | 0.546585E+09 | 0.823323E+09 | 0.394925E+09 | 0.428398E+09 | 0.00 | 0.00 |
October | 0.397330E+09 | 0.103425E+10 | 0.586444E+09 | 0.320050E+09 | 0.266394E+09 | 0.00 | 0.00 |
November | 87786904.26 | 0.180377E+10 | 0.289301E+09 | 0.186507E+09 | 0.102794E+09 | 0.00 | 0.00 |
December | 321765.69 | 0.220159E+10 | 52359321.10 | 34080040.69 | 18279280.41 | 0.00 | 0.00 |
Annual Sum or Average | 0.959520E+10 | 0.118289E+11 | 0.101311E+11 | 0.464678E+10 | 0.548436E+10 | 0.00 | 0.00 |
Minimum of Months | 321765.69 | 0.131569E+09 | 52359321.10 | 34080040.69 | 18279280.41 | 0.00 | 0.00 |
Maximum of Months | 0.154620E+10 | 0.220159E+10 | 0.137451E+10 | 0.692226E+09 | 0.911569E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 15607299.91 | 0.159075E+10 | 0.113990E+09 | 66207315.62 | 47782214.36 | 0.00 | 0.00 |
February | 0.184327E+09 | 0.114307E+10 | 0.390116E+09 | 0.234554E+09 | 0.155563E+09 | 0.00 | 0.00 |
March | 0.685018E+09 | 0.949514E+09 | 0.884045E+09 | 0.512616E+09 | 0.371429E+09 | 0.00 | 0.00 |
April | 0.147030E+10 | 0.548607E+09 | 0.143490E+10 | 0.810318E+09 | 0.624580E+09 | 0.00 | 0.00 |
May | 0.147005E+10 | 0.265094E+09 | 0.134392E+10 | 0.647190E+09 | 0.696733E+09 | 0.00 | 0.00 |
June | 0.155983E+10 | 0.115317E+09 | 0.132678E+10 | 0.557548E+09 | 0.769229E+09 | 0.00 | 0.00 |
July | 0.145241E+10 | 0.127115E+09 | 0.120755E+10 | 0.482401E+09 | 0.725150E+09 | 0.00 | 0.00 |
August | 0.126685E+10 | 0.210148E+09 | 0.109878E+10 | 0.529556E+09 | 0.569222E+09 | 0.00 | 0.00 |
September | 0.711723E+09 | 0.422641E+09 | 0.733524E+09 | 0.374633E+09 | 0.358891E+09 | 0.00 | 0.00 |
October | 0.276791E+09 | 0.815069E+09 | 0.434202E+09 | 0.227526E+09 | 0.206676E+09 | 0.00 | 0.00 |
November | 57601424.00 | 0.142639E+10 | 0.208723E+09 | 0.128163E+09 | 80559550.02 | 0.00 | 0.00 |
December | 0.00 | 0.174365E+10 | 33037168.42 | 20187795.43 | 12849372.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.915050E+10 | 0.935737E+10 | 0.920957E+10 | 0.459090E+10 | 0.461866E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.115317E+09 | 33037168.42 | 20187795.43 | 12849372.99 | 0.00 | 0.00 |
Maximum of Months | 0.155983E+10 | 0.174365E+10 | 0.143490E+10 | 0.810318E+09 | 0.769229E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.169073E+10 | 27063910.43 | 3327943.48 | 23735966.96 | 0.00 | 0.00 |
February | 10981426.42 | 0.130629E+10 | 0.135130E+09 | 36576040.05 | 98553634.11 | 0.00 | 0.00 |
March | 0.195406E+09 | 0.104070E+10 | 0.438895E+09 | 0.150847E+09 | 0.288048E+09 | 0.00 | 0.00 |
April | 0.849620E+09 | 0.548386E+09 | 0.958943E+09 | 0.419992E+09 | 0.538951E+09 | 0.00 | 0.00 |
May | 0.103048E+10 | 0.230508E+09 | 0.105292E+10 | 0.406216E+09 | 0.646703E+09 | 0.00 | 0.00 |
June | 0.127871E+10 | 97183768.10 | 0.116443E+10 | 0.432745E+09 | 0.731690E+09 | 0.00 | 0.00 |
July | 0.113866E+10 | 0.117656E+09 | 0.100844E+10 | 0.323239E+09 | 0.685201E+09 | 0.00 | 0.00 |
August | 0.814583E+09 | 0.204124E+09 | 0.782523E+09 | 0.268145E+09 | 0.514377E+09 | 0.00 | 0.00 |
September | 0.346054E+09 | 0.428396E+09 | 0.447053E+09 | 0.147371E+09 | 0.299682E+09 | 0.00 | 0.00 |
October | 53558490.09 | 0.906915E+09 | 0.190123E+09 | 42849611.93 | 0.147273E+09 | 0.00 | 0.00 |
November | 2338009.32 | 0.155354E+10 | 70113503.71 | 20544393.39 | 49569110.31 | 0.00 | 0.00 |
December | 0.00 | 0.177660E+10 | 7421980.86 | 522824.73 | 6899156.13 | 0.00 | 0.00 |
Annual Sum or Average | 0.572039E+10 | 0.990104E+10 | 0.628306E+10 | 0.225237E+10 | 0.403068E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 97183768.10 | 7421980.86 | 522824.73 | 6899156.13 | 0.00 | 0.00 |
Maximum of Months | 0.127871E+10 | 0.177660E+10 | 0.116443E+10 | 0.432745E+09 | 0.731690E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 80384615.70 | 0.793551E+09 | 0.138597E+09 | 92218633.81 | 46378698.96 | 0.00 | 0.00 |
February | 0.353258E+09 | 0.577567E+09 | 0.418332E+09 | 0.290353E+09 | 0.127978E+09 | 0.00 | 0.00 |
March | 0.775181E+09 | 0.494843E+09 | 0.784440E+09 | 0.530592E+09 | 0.253848E+09 | 0.00 | 0.00 |
April | 0.103430E+10 | 0.300503E+09 | 0.930598E+09 | 0.579127E+09 | 0.351471E+09 | 0.00 | 0.00 |
May | 0.920853E+09 | 0.146382E+09 | 0.794294E+09 | 0.412444E+09 | 0.381850E+09 | 0.00 | 0.00 |
June | 0.845928E+09 | 62052231.31 | 0.698478E+09 | 0.285266E+09 | 0.413213E+09 | 0.00 | 0.00 |
July | 0.863901E+09 | 67376693.26 | 0.694266E+09 | 0.300743E+09 | 0.393523E+09 | 0.00 | 0.00 |
August | 0.875812E+09 | 0.111925E+09 | 0.723076E+09 | 0.398988E+09 | 0.324088E+09 | 0.00 | 0.00 |
September | 0.606444E+09 | 0.223492E+09 | 0.558431E+09 | 0.333756E+09 | 0.224675E+09 | 0.00 | 0.00 |
October | 0.390015E+09 | 0.417290E+09 | 0.427120E+09 | 0.270846E+09 | 0.156274E+09 | 0.00 | 0.00 |
November | 0.147776E+09 | 0.709450E+09 | 0.224052E+09 | 0.157833E+09 | 66219054.27 | 0.00 | 0.00 |
December | 7403500.21 | 0.878814E+09 | 40938100.64 | 28840566.79 | 12097533.86 | 0.00 | 0.00 |
Annual Sum or Average | 0.690126E+10 | 0.478325E+10 | 0.643262E+10 | 0.368101E+10 | 0.275162E+10 | 0.00 | 0.00 |
Minimum of Months | 7403500.21 | 62052231.31 | 40938100.64 | 28840566.79 | 12097533.86 | 0.00 | 0.00 |
Maximum of Months | 0.103430E+10 | 0.878814E+09 | 0.930598E+09 | 0.579127E+09 | 0.413213E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.438363E+10 | 53037810.99 | 0.00 | 53037810.99 | 0.00 | 0.00 |
February | 0.00 | 0.355110E+10 | 0.211764E+09 | 0.00 | 0.211764E+09 | 0.00 | 0.00 |
March | 36320873.45 | 0.299546E+10 | 0.628028E+09 | 108636.11 | 0.627919E+09 | 0.00 | 0.00 |
April | 0.413338E+09 | 0.154627E+10 | 0.110997E+10 | 31861397.22 | 0.107811E+10 | 0.00 | 0.00 |
May | 0.138923E+10 | 0.621982E+09 | 0.175403E+10 | 0.281744E+09 | 0.147229E+10 | 0.00 | 0.00 |
June | 0.227925E+10 | 0.250265E+09 | 0.219733E+10 | 0.487924E+09 | 0.170940E+10 | 0.00 | 0.00 |
July | 0.205237E+10 | 0.308413E+09 | 0.191985E+10 | 0.321282E+09 | 0.159857E+10 | 0.00 | 0.00 |
August | 0.106343E+10 | 0.554150E+09 | 0.123737E+10 | 74474115.76 | 0.116290E+10 | 0.00 | 0.00 |
September | 0.238784E+09 | 0.126084E+10 | 0.660043E+09 | 2165161.78 | 0.657878E+09 | 0.00 | 0.00 |
October | 14423248.61 | 0.260418E+10 | 0.330056E+09 | 0.00 | 0.330056E+09 | 0.00 | 0.00 |
November | 0.00 | 0.411877E+10 | 99123888.81 | 0.00 | 99123888.81 | 0.00 | 0.00 |
December | 0.00 | 0.454923E+10 | 16088885.60 | 0.00 | 16088885.60 | 0.00 | 0.00 |
Annual Sum or Average | 0.748715E+10 | 0.267443E+11 | 0.102167E+11 | 0.119956E+10 | 0.901713E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.250265E+09 | 16088885.60 | 0.00 | 16088885.60 | 0.00 | 0.00 |
Maximum of Months | 0.227925E+10 | 0.454923E+10 | 0.219733E+10 | 0.487924E+09 | 0.170940E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.445346E+10 | 53037810.99 | 0.00 | 53037810.99 | 0.00 | 0.00 |
February | 0.00 | 0.361164E+10 | 0.211764E+09 | 0.00 | 0.211764E+09 | 0.00 | 0.00 |
March | 31664141.86 | 0.305742E+10 | 0.628028E+09 | 108636.11 | 0.627919E+09 | 0.00 | 0.00 |
April | 0.392813E+09 | 0.158066E+10 | 0.110997E+10 | 31861397.22 | 0.107811E+10 | 0.00 | 0.00 |
May | 0.135967E+10 | 0.634590E+09 | 0.175403E+10 | 0.281744E+09 | 0.147229E+10 | 0.00 | 0.00 |
June | 0.225600E+10 | 0.256769E+09 | 0.219733E+10 | 0.487924E+09 | 0.170940E+10 | 0.00 | 0.00 |
July | 0.203004E+10 | 0.316462E+09 | 0.191985E+10 | 0.321282E+09 | 0.159857E+10 | 0.00 | 0.00 |
August | 0.104051E+10 | 0.568304E+09 | 0.123737E+10 | 74474115.76 | 0.116290E+10 | 0.00 | 0.00 |
September | 0.223265E+09 | 0.129683E+10 | 0.660043E+09 | 2165161.78 | 0.657878E+09 | 0.00 | 0.00 |
October | 11510893.98 | 0.266722E+10 | 0.330056E+09 | 0.00 | 0.330056E+09 | 0.00 | 0.00 |
November | 0.00 | 0.418670E+10 | 99123888.81 | 0.00 | 99123888.81 | 0.00 | 0.00 |
December | 0.00 | 0.461702E+10 | 16088885.60 | 0.00 | 16088885.60 | 0.00 | 0.00 |
Annual Sum or Average | 0.734547E+10 | 0.272471E+11 | 0.102167E+11 | 0.119956E+10 | 0.901713E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.256769E+09 | 16088885.60 | 0.00 | 16088885.60 | 0.00 | 0.00 |
Maximum of Months | 0.225600E+10 | 0.461702E+10 | 0.219733E+10 | 0.487924E+09 | 0.170940E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 39624078.30 | 0.276888E+10 | 0.185964E+09 | 94005850.11 | 91958367.77 | 0.00 | 0.00 |
February | 0.428658E+09 | 0.200545E+10 | 0.708199E+09 | 0.386323E+09 | 0.321875E+09 | 0.00 | 0.00 |
March | 0.174620E+10 | 0.168817E+10 | 0.184337E+10 | 0.978795E+09 | 0.864570E+09 | 0.00 | 0.00 |
April | 0.267303E+10 | 0.956051E+09 | 0.236210E+10 | 0.119399E+10 | 0.116811E+10 | 0.00 | 0.00 |
May | 0.409984E+10 | 0.455960E+09 | 0.315291E+10 | 0.165363E+10 | 0.149928E+10 | 0.00 | 0.00 |
June | 0.403780E+10 | 0.196299E+09 | 0.288270E+10 | 0.124118E+10 | 0.164151E+10 | 0.00 | 0.00 |
July | 0.407093E+10 | 0.229010E+09 | 0.280703E+10 | 0.125204E+10 | 0.155499E+10 | 0.00 | 0.00 |
August | 0.329263E+10 | 0.367354E+09 | 0.232443E+10 | 0.109325E+10 | 0.123118E+10 | 0.00 | 0.00 |
September | 0.182737E+10 | 0.698684E+09 | 0.147742E+10 | 0.681156E+09 | 0.796263E+09 | 0.00 | 0.00 |
October | 0.811650E+09 | 0.139508E+10 | 0.899537E+09 | 0.412050E+09 | 0.487487E+09 | 0.00 | 0.00 |
November | 49622396.29 | 0.250320E+10 | 0.279594E+09 | 0.148603E+09 | 0.130991E+09 | 0.00 | 0.00 |
December | 3755.69 | 0.303000E+10 | 46794270.00 | 23610040.25 | 23184229.74 | 0.00 | 0.00 |
Annual Sum or Average | 0.230774E+11 | 0.162941E+11 | 0.189700E+11 | 0.915863E+10 | 0.981141E+10 | 0.00 | 0.00 |
Minimum of Months | 3755.69 | 0.196299E+09 | 46794270.00 | 23610040.25 | 23184229.74 | 0.00 | 0.00 |
Maximum of Months | 0.409984E+10 | 0.303000E+10 | 0.315291E+10 | 0.165363E+10 | 0.164151E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.120105E+09 | 0.351182E+10 | 0.370988E+09 | 0.234747E+09 | 0.136241E+09 | 0.00 | 0.00 |
February | 0.719615E+09 | 0.253452E+10 | 0.113748E+10 | 0.739109E+09 | 0.398369E+09 | 0.00 | 0.00 |
March | 0.186853E+10 | 0.214051E+10 | 0.221212E+10 | 0.135069E+10 | 0.861436E+09 | 0.00 | 0.00 |
April | 0.278566E+10 | 0.125667E+10 | 0.274939E+10 | 0.148512E+10 | 0.126427E+10 | 0.00 | 0.00 |
May | 0.278175E+10 | 0.556223E+09 | 0.262320E+10 | 0.114648E+10 | 0.147672E+10 | 0.00 | 0.00 |
June | 0.285388E+10 | 0.240716E+09 | 0.253126E+10 | 0.893421E+09 | 0.163784E+10 | 0.00 | 0.00 |
July | 0.283826E+10 | 0.293765E+09 | 0.242542E+10 | 0.875693E+09 | 0.154973E+10 | 0.00 | 0.00 |
August | 0.257001E+10 | 0.492183E+09 | 0.226480E+10 | 0.104118E+10 | 0.122363E+10 | 0.00 | 0.00 |
September | 0.162796E+10 | 0.968565E+09 | 0.164778E+10 | 0.850335E+09 | 0.797445E+09 | 0.00 | 0.00 |
October | 0.892739E+09 | 0.183394E+10 | 0.120040E+10 | 0.689452E+09 | 0.510948E+09 | 0.00 | 0.00 |
November | 0.239045E+09 | 0.314190E+10 | 0.604317E+09 | 0.401773E+09 | 0.202544E+09 | 0.00 | 0.00 |
December | 3992018.14 | 0.387221E+10 | 0.109725E+09 | 73415195.49 | 36310216.78 | 0.00 | 0.00 |
Annual Sum or Average | 0.193015E+11 | 0.208430E+11 | 0.198769E+11 | 0.978141E+10 | 0.100955E+11 | 0.00 | 0.00 |
Minimum of Months | 3992018.14 | 0.240716E+09 | 0.109725E+09 | 73415195.49 | 36310216.78 | 0.00 | 0.00 |
Maximum of Months | 0.285388E+10 | 0.387221E+10 | 0.274939E+10 | 0.148512E+10 | 0.163784E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770637E+10 | -0.754277E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163605664.3 | 81.21 | 0.00 | 0.00 |
February | 0.696341E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -147456292.2 | 81.21 | 0.00 | 0.00 |
March | 0.770419E+10 | -0.754147E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162719735.9 | 81.21 | 0.00 | 0.00 |
April | 0.746554E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156945672.8 | 81.21 | 0.00 | 0.00 |
May | 0.770465E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161856641.0 | 81.21 | 0.00 | 0.00 |
June | 0.745698E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156458394.4 | 81.21 | 0.00 | 0.00 |
July | 0.771253E+10 | -0.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161682650.9 | 81.21 | 0.00 | 0.00 |
August | 0.770457E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161768577.8 | 81.21 | 0.00 | 0.00 |
September | 0.746672E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156774193.9 | 81.21 | 0.00 | 0.00 |
October | 0.770375E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162306292.3 | 81.21 | 0.00 | 0.00 |
November | 0.745043E+10 | -0.729244E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157993300.7 | 81.21 | 0.00 | 0.00 |
December | 0.771437E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163515278.8 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907535E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.191308E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696341E+10 | -0.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -163605664.3 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771437E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -147456292.2 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYSLAUNDRY HPWH TANK
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.819268E+11 | -0.810385E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -888285912.5 | 70.68 | 0.00 | 0.00 |
February | 0.739858E+11 | -0.731994E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -786409744.6 | 70.66 | 0.00 | 0.00 |
March | 0.818195E+11 | -0.810617E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -830847953.7 | 70.66 | 0.00 | 0.00 |
April | 0.739688E+11 | -0.121925E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -833668887.4 | 79.93 | 0.00 | 0.00 |
May | 0.719928E+11 | -0.135457E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -807415349.7 | 81.67 | 0.00 | 0.00 |
June | 0.580105E+11 | -0.127520E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -741736379.9 | 81.67 | 0.00 | 0.00 |
July | 0.541566E+11 | -0.128187E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -759041229.1 | 81.67 | 0.00 | 0.00 |
August | 0.554851E+11 | -0.125914E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -778975212.5 | 81.67 | 0.00 | 0.00 |
September | 0.637725E+11 | -0.121579E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -810405073.1 | 81.67 | 0.00 | 0.00 |
October | 0.762001E+11 | -0.121345E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -900395962.7 | 80.64 | 0.00 | 0.00 |
November | 0.788244E+11 | -0.779538E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -870694110.7 | 71.60 | 0.00 | 0.00 |
December | 0.817957E+11 | -0.808919E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -903808131.5 | 70.92 | 0.00 | 0.00 |
Annual Sum or Average | 0.851939E+12 | -0.127607E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.991168E+10 | 76.99 | 0.00 | 0.00 |
Minimum of Months | 0.541566E+11 | -0.135457E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -903808131.5 | 70.66 | 0.00 | 0.00 |
Maximum of Months | 0.819268E+11 | -0.731994E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -741736379.9 | 81.67 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 HPWH TANK
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.885731E+11 | -0.871873E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.138587E+10 | 45.12 | 0.00 | 0.00 |
February | 0.799792E+11 | -0.787658E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.121346E+10 | 45.10 | 0.00 | 0.00 |
March | 0.883199E+11 | -0.872564E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.124177E+10 | 44.85 | 0.00 | 0.00 |
April | 0.187768E+10 | -0.846470E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.138690E+10 | 58.67 | 0.00 | 0.00 |
May | -0.223324E+10 | -0.869313E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.126133E+10 | 59.05 | 0.00 | 0.00 |
June | -0.314254E+10 | -0.811258E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.112715E+10 | 59.13 | 0.00 | 0.00 |
July | -0.327427E+10 | -0.806765E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.114802E+10 | 59.17 | 0.00 | 0.00 |
August | -0.287075E+10 | -0.787851E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.119586E+10 | 59.16 | 0.00 | 0.00 |
September | -0.183779E+10 | -0.759253E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.129197E+10 | 59.11 | 0.00 | 0.00 |
October | 0.201156E+10 | -0.798076E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150890E+10 | 58.78 | 0.00 | 0.00 |
November | 0.811306E+11 | -0.797675E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.136311E+10 | 45.90 | 0.00 | 0.00 |
December | 0.872366E+11 | -0.858149E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.142169E+10 | 45.32 | 0.00 | 0.00 |
Annual Sum or Average | 0.415770E+12 | -0.986690E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.155460E+11 | 53.32 | 0.00 | 0.00 |
Minimum of Months | -0.327427E+10 | -0.872564E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.150890E+10 | 44.85 | 0.00 | 0.00 |
Maximum of Months | 0.885731E+11 | -0.759253E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.112715E+10 | 59.17 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.90 | 0.86 | 10-JAN-10:00 | 527.07 | 26.08 | 71.33 | 69.83 | 374.81 | 27.64 | 72.67 | 39.50 |
February | 205.83 | 0.87 | 0.86 | 01-FEB-12:20 | 1968.45 | 34.93 | 190.00 | 180.00 | 1580.72 | 35.94 | 190.67 | 151.33 |
March | 329.50 | 0.87 | 0.86 | 01-MAR-08:39 | 4656.05 | 33.04 | 281.67 | 305.83 | 2499.05 | 30.92 | 279.67 | 267.50 |
April | 421.83 | 0.87 | 0.86 | 01-APR-07:00 | 6549.16 | 30.08 | 266.17 | 381.17 | 722.10 | 21.63 | 296.17 | 313.17 |
May | 545.00 | 0.88 | 0.86 | 01-MAY-06:40 | 2940.44 | 21.18 | 140.67 | 448.67 | 532.97 | 20.28 | 308.50 | 347.83 |
June | 583.50 | 0.88 | 0.86 | 01-JUN-05:49 | 1301.08 | 18.04 | 96.33 | 472.50 | 509.15 | 19.86 | 295.33 | 357.50 |
July | 562.83 | 0.88 | 0.86 | 01-JUL-05:19 | 1614.97 | 18.69 | 105.50 | 469.33 | 518.95 | 19.97 | 298.67 | 352.17 |
August | 467.17 | 0.88 | 0.86 | 01-AUG-06:19 | 4498.67 | 25.71 | 229.17 | 404.00 | 575.34 | 20.55 | 252.67 | 318.50 |
September | 356.33 | 0.88 | 0.86 | 01-SEP-06:49 | 3817.19 | 30.66 | 274.83 | 320.50 | 1032.49 | 23.05 | 205.00 | 260.17 |
October | 265.50 | 0.87 | 0.86 | 01-OCT-07:00 | 2071.53 | 32.65 | 240.33 | 236.50 | 1626.81 | 33.64 | 243.67 | 203.67 |
November | 135.83 | 0.88 | 0.86 | 01-NOV-09:00 | 774.86 | 32.28 | 117.50 | 121.50 | 566.26 | 33.54 | 117.67 | 86.50 |
December | 71.17 | 0.95 | 0.86 | 05-DEC-11:30 | 125.54 | 5.30 | 0.00 | 8.83 | 74.29 | 8.35 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.88 | 2999.13 | 25.30 | 2013.50 | 3418.67 | 869.59 | 23.56 | 2560.67 | 2697.83 | ||
Minimum of Months | 71.17 | 0.87 | 0.86 | 125.54 | 5.30 | 0.00 | 8.83 | 74.29 | 8.35 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.95 | 0.86 | 6549.16 | 34.93 | 281.67 | 472.50 | 2499.05 | 35.94 | 308.50 | 357.50 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.38 | 0.22 | 08-JAN-11:30 | 619.61 | 26.55 | 72.00 | 83.17 | 465.87 | 28.08 | 72.67 | 57.67 |
February | 205.83 | 0.28 | 0.22 | 01-FEB-11:20 | 2217.37 | 35.05 | 190.17 | 188.50 | 1828.92 | 36.05 | 191.50 | 171.67 |
March | 329.50 | 0.26 | 0.22 | 01-MAR-08:30 | 5029.28 | 33.24 | 284.67 | 312.17 | 2873.10 | 30.97 | 272.83 | 291.67 |
April | 421.83 | 0.27 | 0.22 | 01-APR-07:19 | 6940.67 | 30.50 | 281.33 | 398.50 | 1112.16 | 21.69 | 286.83 | 355.83 |
May | 545.00 | 0.30 | 0.22 | 01-MAY-05:10 | 3214.91 | 21.73 | 177.50 | 474.83 | 806.39 | 20.57 | 319.50 | 418.67 |
June | 583.50 | 0.31 | 0.22 | 01-JUN-04:00 | 1533.50 | 18.65 | 118.50 | 505.17 | 740.61 | 20.30 | 323.83 | 435.17 |
July | 562.83 | 0.30 | 0.22 | 01-JUL-04:40 | 1853.36 | 19.31 | 133.50 | 499.50 | 756.71 | 20.38 | 306.33 | 423.33 |
August | 467.17 | 0.28 | 0.22 | 01-AUG-05:40 | 4784.96 | 26.27 | 248.33 | 424.50 | 861.08 | 20.85 | 267.83 | 376.00 |
September | 356.33 | 0.28 | 0.22 | 01-SEP-06:19 | 4087.67 | 30.93 | 279.83 | 333.50 | 1300.61 | 23.36 | 224.33 | 295.17 |
October | 265.50 | 0.27 | 0.22 | 01-OCT-07:40 | 2291.74 | 32.78 | 241.17 | 246.67 | 1845.23 | 33.75 | 245.00 | 223.83 |
November | 135.83 | 0.30 | 0.22 | 01-NOV-09:39 | 912.06 | 32.52 | 117.50 | 134.67 | 702.98 | 33.76 | 117.67 | 109.17 |
December | 71.17 | 0.62 | 0.22 | 04-DEC-11:20 | 141.80 | 6.72 | 0.00 | 21.17 | 89.47 | 9.73 | 0.00 | 5.83 |
Annual Sum or Average | 4053.17 | 0.30 | 3264.89 | 25.76 | 2144.50 | 3622.33 | 1134.40 | 23.85 | 2628.33 | 3164.00 | ||
Minimum of Months | 71.17 | 0.26 | 0.22 | 141.80 | 6.72 | 0.00 | 21.17 | 89.47 | 9.73 | 0.00 | 5.83 | |
Maximum of Months | 583.50 | 0.62 | 0.22 | 6940.67 | 35.05 | 284.67 | 505.17 | 2873.10 | 36.05 | 323.83 | 435.17 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.85 | 0.67 | 31-JAN-11:30 | 109.98 | 7.60 | 0.00 | 7.67 | 53.17 | 11.11 | 0.00 | 0.00 |
February | 205.83 | 0.73 | 0.60 | 16-FEB-12:30 | 243.13 | 11.99 | 0.00 | 130.33 | 116.03 | 15.54 | 0.00 | 7.83 |
March | 329.50 | 0.65 | 0.60 | 01-MAR-10:20 | 432.84 | 15.06 | 0.00 | 285.17 | 203.34 | 18.46 | 0.00 | 153.17 |
April | 421.83 | 0.62 | 0.60 | 01-APR-07:00 | 547.44 | 17.26 | 10.17 | 403.67 | 272.15 | 20.59 | 41.83 | 327.00 |
May | 545.00 | 0.63 | 0.60 | 01-MAY-04:49 | 690.57 | 19.35 | 88.83 | 502.67 | 332.49 | 22.93 | 185.83 | 451.50 |
June | 583.50 | 0.63 | 0.60 | 01-JUN-03:00 | 861.14 | 20.91 | 148.67 | 542.50 | 404.73 | 23.22 | 244.83 | 495.33 |
July | 562.83 | 0.63 | 0.60 | 01-JUL-03:39 | 777.69 | 20.15 | 124.17 | 531.50 | 349.99 | 22.45 | 188.83 | 459.67 |
August | 467.17 | 0.63 | 0.60 | 01-AUG-04:49 | 583.29 | 17.55 | 34.67 | 431.00 | 278.00 | 21.15 | 86.00 | 334.50 |
September | 356.33 | 0.66 | 0.60 | 01-SEP-05:00 | 424.56 | 14.95 | 0.00 | 311.83 | 193.15 | 18.21 | 3.33 | 152.33 |
October | 265.50 | 0.70 | 0.60 | 01-OCT-08:20 | 302.88 | 13.00 | 0.00 | 201.67 | 132.54 | 16.34 | 0.00 | 12.17 |
November | 135.83 | 0.81 | 0.65 | 06-NOV-13:30 | 149.02 | 9.50 | 0.00 | 37.17 | 70.24 | 13.30 | 0.00 | 0.00 |
December | 71.17 | 0.94 | 0.83 | 04-DEC-11:30 | 40.46 | 2.93 | 0.00 | 0.00 | 20.19 | 5.93 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.66 | 562.37 | 16.80 | 406.50 | 3385.17 | 264.16 | 19.93 | 750.67 | 2393.50 | ||
Minimum of Months | 71.17 | 0.62 | 0.60 | 40.46 | 2.93 | 0.00 | 0.00 | 20.19 | 5.93 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.94 | 0.83 | 861.14 | 20.91 | 148.67 | 542.50 | 404.73 | 23.22 | 244.83 | 495.33 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.85 | 0.67 | 31-JAN-11:30 | 109.98 | 7.60 | 0.00 | 7.67 | 53.17 | 11.11 | 0.00 | 0.00 |
February | 205.83 | 0.73 | 0.60 | 16-FEB-12:30 | 243.13 | 11.99 | 0.00 | 130.33 | 116.03 | 15.54 | 0.00 | 7.83 |
March | 329.50 | 0.65 | 0.60 | 01-MAR-10:20 | 432.84 | 15.06 | 0.00 | 285.17 | 203.34 | 18.46 | 0.00 | 153.17 |
April | 421.83 | 0.62 | 0.60 | 01-APR-07:00 | 547.44 | 17.26 | 10.17 | 403.67 | 272.15 | 20.59 | 41.83 | 327.00 |
May | 545.00 | 0.63 | 0.60 | 01-MAY-04:49 | 690.57 | 19.35 | 88.83 | 502.67 | 332.49 | 22.93 | 185.83 | 451.50 |
June | 583.50 | 0.63 | 0.60 | 01-JUN-03:00 | 861.14 | 20.91 | 148.67 | 542.50 | 404.73 | 23.22 | 244.83 | 495.33 |
July | 562.83 | 0.63 | 0.60 | 01-JUL-03:39 | 777.69 | 20.15 | 124.17 | 531.50 | 349.99 | 22.45 | 188.83 | 459.67 |
August | 467.17 | 0.63 | 0.60 | 01-AUG-04:49 | 583.29 | 17.55 | 34.67 | 431.00 | 278.00 | 21.15 | 86.00 | 334.50 |
September | 356.33 | 0.66 | 0.60 | 01-SEP-05:00 | 424.56 | 14.95 | 0.00 | 311.83 | 193.15 | 18.21 | 3.33 | 152.33 |
October | 265.50 | 0.70 | 0.60 | 01-OCT-08:20 | 302.88 | 13.00 | 0.00 | 201.67 | 132.54 | 16.34 | 0.00 | 12.17 |
November | 135.83 | 0.81 | 0.65 | 06-NOV-13:30 | 149.02 | 9.50 | 0.00 | 37.17 | 70.24 | 13.30 | 0.00 | 0.00 |
December | 71.17 | 0.94 | 0.83 | 04-DEC-11:30 | 40.46 | 2.93 | 0.00 | 0.00 | 20.19 | 5.93 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.66 | 562.37 | 16.80 | 406.50 | 3385.17 | 264.16 | 19.93 | 750.67 | 2393.50 | ||
Minimum of Months | 71.17 | 0.62 | 0.60 | 40.46 | 2.93 | 0.00 | 0.00 | 20.19 | 5.93 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.94 | 0.83 | 861.14 | 20.91 | 148.67 | 542.50 | 404.73 | 23.22 | 244.83 | 495.33 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.511320E+12 | 553466.65 | 12-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.437044E+12 | 546254.68 | 27-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.264905E+12 | 521742.06 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.742363E+11 | 157728.36 | 03-APR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.485980E+11 | 120321.88 | 19-MAY-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.363342E+11 | 111679.75 | 01-JUN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.366328E+11 | 103197.41 | 05-JUL-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.543205E+11 | 118910.57 | 31-AUG-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.501852E+11 | 122133.49 | 09-SEP-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110843E+12 | 150831.05 | 27-OCT-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.487929E+12 | 525832.79 | 30-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.602592E+12 | 538892.85 | 15-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271494E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.363342E+11 | 103197.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.602592E+12 | 553466.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.169659E+10 | 10814.34 | 12-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.222231E+10 | 10631.22 | 27-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.872761E+09 | 6987.46 | 01-MAR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 807024.23 | 374.24 | 02-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 42659690.73 | 3224.09 | 30-NOV-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.445736E+09 | 10113.91 | 15-DEC-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.528086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.222231E+10 | 10814.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.787307E+10 | 5912.49 | 12-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.556268E+10 | 5810.21 | 27-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.360401E+10 | 5119.98 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127128E+10 | 2095.77 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.560069E+09 | 1372.74 | 27-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165041E+09 | 952.48 | 25-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.203333E+09 | 1041.67 | 05-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.393252E+09 | 1114.02 | 30-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149550E+10 | 1702.31 | 30-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.348964E+10 | 2742.06 | 30-OCT-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.703586E+10 | 5524.39 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.867384E+10 | 5707.47 | 15-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.403276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.165041E+09 | 952.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.867384E+10 | 5912.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.104537E+10 | 2033.32 | 12-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.599397E+09 | 1963.45 | 27-FEB-09:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151833E+09 | 1204.82 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 805774.17 | 130.78 | 04-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 42246363.71 | 389.75 | 29-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.726488E+09 | 1662.82 | 29-NOV-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117067E+10 | 1953.84 | 15-DEC-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.373682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.117067E+10 | 2033.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.230265E+10 | 2823.17 | 12-JAN-10:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.169704E+10 | 2438.99 | 27-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.980723E+09 | 1777.12 | 01-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106487E+09 | 627.95 | 03-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.368922E+09 | 686.25 | 31-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190330E+10 | 1894.16 | 29-NOV-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.251828E+10 | 2352.28 | 15-DEC-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.987740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.251828E+10 | 2823.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.198974E+10 | 1813.89 | 12-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151785E+10 | 1646.91 | 27-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102173E+10 | 1246.29 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171303E+09 | 499.57 | 03-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16386008.43 | 187.58 | 29-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.513976E+09 | 602.02 | 31-OCT-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172830E+10 | 1399.73 | 29-NOV-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.214783E+10 | 1683.03 | 15-DEC-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.910712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.214783E+10 | 1813.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.358130E+10 | 13744.33 | 12-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244550E+10 | 13512.55 | 27-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103643E+10 | 12679.65 | 01-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 57041245.40 | 1300.95 | 03-APR-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4134289.17 | 515.05 | 27-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 341475.49 | 205.74 | 26-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 374732.00 | 206.51 | 05-JUL-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 910650.26 | 206.97 | 21-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 25633786.24 | 818.28 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125326E+09 | 1485.25 | 30-OCT-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.247421E+10 | 12798.60 | 29-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.384698E+10 | 13215.64 | 15-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 341475.49 | 205.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.384698E+10 | 13744.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.140235E+11 | 17400.94 | 12-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.853679E+10 | 17077.96 | 27-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.330718E+10 | 13805.64 | 01-MAR-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.482771E+09 | 4647.21 | 04-APR-09:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 49698328.01 | 2855.61 | 27-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38709588.93 | 1890.62 | 27-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 23179557.49 | 2820.38 | 05-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 53441555.95 | 2579.80 | 07-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.768733E+09 | 4404.67 | 27-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.305029E+10 | 6953.08 | 30-OCT-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116715E+11 | 16269.05 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159679E+11 | 16803.30 | 15-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.579737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 23179557.49 | 1890.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.159679E+11 | 17400.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.177317E+11 | 41173.60 | 12-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.930925E+10 | 40085.74 | 27-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167640E+10 | 26062.59 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6871976.30 | 2192.05 | 04-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.477763E+09 | 7415.68 | 29-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121082E+11 | 37258.94 | 29-NOV-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.194682E+11 | 39764.16 | 15-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.607784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.194682E+11 | 41173.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.220037E+11 | 19375.30 | 12-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152044E+11 | 18686.72 | 27-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.825525E+10 | 14181.09 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112247E+10 | 5553.12 | 03-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.894074E+09 | 4463.82 | 27-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.759431E+10 | 8321.29 | 30-OCT-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192178E+11 | 17235.23 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.238494E+11 | 18698.46 | 15-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.981414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.238494E+11 | 19375.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.147339E+11 | 13627.87 | 12-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106673E+11 | 12861.81 | 27-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.659368E+10 | 10023.86 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142645E+10 | 4170.45 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5682601.47 | 688.25 | 28-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.708470E+09 | 2345.34 | 30-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.494042E+10 | 4870.90 | 27-OCT-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133099E+11 | 11185.01 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160825E+11 | 12906.73 | 15-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.684684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.160825E+11 | 13627.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.263268E+10 | 17497.57 | 12-JAN-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112070E+10 | 15034.34 | 27-FEB-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130400E+09 | 7332.70 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130931E+10 | 11379.06 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201992E+10 | 15207.02 | 15-DEC-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.721301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.263268E+10 | 17497.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.246152E+10 | 18043.10 | 12-JAN-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.957073E+09 | 14873.60 | 27-FEB-09:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 90299871.93 | 6697.08 | 01-MAR-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112594E+10 | 11115.48 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170884E+10 | 15117.62 | 15-DEC-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.634367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.246152E+10 | 18043.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.176632E+10 | 12480.81 | 12-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.984118E+09 | 12269.46 | 27-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.405989E+09 | 8191.16 | 01-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.748526E+09 | 9528.50 | 29-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.124552E+10 | 11891.96 | 15-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.515047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.176632E+10 | 12480.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.337919E+11 | 54393.46 | 12-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.302154E+11 | 53675.47 | 27-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164020E+11 | 51239.08 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.215662E+10 | 9215.67 | 03-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13294.10 | 0.51 | 30-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32189.03 | 0.51 | 30-JUN-20:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31761.24 | 0.51 | 02-JUL-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2803799.50 | 499.12 | 31-AUG-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.119726E+09 | 2206.27 | 29-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.418381E+10 | 9131.06 | 27-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.325190E+11 | 51610.98 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.408317E+11 | 52943.15 | 15-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160223E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 13294.10 | 0.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.408317E+11 | 54393.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107283E+11 | 12855.84 | 07-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.752455E+10 | 12855.19 | 02-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.477671E+10 | 12854.24 | 09-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.996792E+09 | 12852.86 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 50923000.14 | 4125.40 | 28-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8745909.41 | 4518.39 | 24-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11164539.75 | 4316.33 | 25-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 27736496.23 | 4791.75 | 29-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.751149E+09 | 12574.97 | 29-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.418124E+10 | 12855.07 | 21-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.957796E+10 | 12854.80 | 02-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117369E+11 | 12855.14 | 25-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.503722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8745909.41 | 4125.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.117369E+11 | 12855.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.111261E+11 | 12515.97 | 07-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.864169E+10 | 12515.25 | 02-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.625757E+10 | 12515.07 | 09-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154858E+10 | 12514.06 | 05-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 71424297.52 | 4533.91 | 25-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2808863.62 | 3659.20 | 25-JUN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5311674.40 | 3499.29 | 26-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 38256186.79 | 4233.43 | 19-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107313E+10 | 12351.12 | 29-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.503315E+10 | 12515.14 | 21-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102214E+11 | 12514.85 | 02-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118837E+11 | 12515.20 | 25-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.559031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2808863.62 | 3499.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.118837E+11 | 12515.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.285866E+11 | 27680.43 | 12-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.608178E+10 | 18895.47 | 26-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.468770E+09 | 16590.47 | 01-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188430E+11 | 21919.73 | 29-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379122E+11 | 25979.60 | 15-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.918923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.379122E+11 | 27680.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.460573E+11 | 69342.91 | 16-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.358044E+11 | 69334.47 | 01-FEB-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.244354E+11 | 69317.17 | 02-MAR-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.507328E+10 | 67973.97 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35931439.39 | 16837.10 | 06-MAY-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5690006.31 | 12616.82 | 21-JUN-21:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7950596.77 | 10345.14 | 31-JUL-21:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33157924.22 | 25142.67 | 31-AUG-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.946242E+09 | 28789.55 | 26-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138087E+11 | 69173.85 | 31-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.422631E+11 | 69337.48 | 24-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.501365E+11 | 69338.05 | 17-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5690006.31 | 10345.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.501365E+11 | 69342.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106192E+11 | 12664.95 | 07-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.706959E+10 | 12664.28 | 02-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.390744E+10 | 12662.11 | 05-MAR-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.984244E+09 | 12585.93 | 04-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31789685.88 | 4154.06 | 03-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3744054.15 | 4162.79 | 27-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4380706.42 | 4470.29 | 01-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20078002.73 | 4728.21 | 14-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.602611E+09 | 10787.03 | 27-SEP-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.369867E+10 | 12664.12 | 21-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.956898E+10 | 12663.88 | 02-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117278E+11 | 12664.22 | 25-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.482385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3744054.15 | 4154.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.117278E+11 | 12664.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.109978E+11 | 12347.60 | 07-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.812408E+10 | 12346.87 | 02-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.520006E+10 | 12345.66 | 07-MAR-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156061E+10 | 12343.43 | 04-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 47361739.64 | 3853.47 | 26-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2043476.99 | 3679.76 | 25-JUN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1600883.56 | 2103.46 | 21-JUL-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28184281.64 | 4107.95 | 20-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.857811E+09 | 11841.12 | 27-SEP-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.444499E+10 | 12346.73 | 21-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102104E+11 | 12346.46 | 02-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118679E+11 | 12346.81 | 25-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.533429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1600883.56 | 2103.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.118679E+11 | 12347.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.371274E+10 | 3937.53 | 07-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.269424E+10 | 3937.35 | 03-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180468E+10 | 3937.42 | 19-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.461536E+09 | 3937.04 | 05-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 49370336.43 | 1008.01 | 07-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2938639.01 | 1027.99 | 05-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4407011.11 | 1007.30 | 13-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 24627681.53 | 1503.05 | 30-AUG-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.375699E+09 | 3900.03 | 29-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159572E+10 | 3937.23 | 25-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.337699E+10 | 3937.18 | 02-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.402607E+10 | 3937.23 | 25-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2938639.01 | 1007.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.402607E+10 | 3937.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.382395E+10 | 3804.13 | 07-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.302672E+10 | 3803.92 | 03-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.228823E+10 | 3804.00 | 19-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.671252E+09 | 3803.60 | 05-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 62078490.71 | 1036.41 | 08-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1212989.36 | 944.31 | 15-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2388592.20 | 1028.50 | 03-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31922487.87 | 2072.70 | 31-AUG-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.510053E+09 | 3785.76 | 30-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.187134E+10 | 3803.80 | 25-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.356345E+10 | 3803.78 | 02-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.406672E+10 | 3803.83 | 25-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1212989.36 | 944.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.406672E+10 | 3804.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.150169E+11 | 20024.77 | 07-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.872480E+10 | 20024.52 | 02-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.466429E+10 | 20017.40 | 13-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.901297E+09 | 19911.70 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 60556546.04 | 5596.72 | 28-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12777467.29 | 5222.51 | 16-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13562485.81 | 5408.27 | 07-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 27547758.98 | 5544.56 | 18-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.563299E+09 | 14112.59 | 28-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.431923E+10 | 20023.94 | 25-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128745E+11 | 20023.89 | 02-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172478E+11 | 20023.65 | 25-DEC-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.644266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 12777467.29 | 5222.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.172478E+11 | 20024.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.197241E+10 | 0.197241E+10 | 36539.74 | 31-MAR-23:03 | 36539.74 | 0.00 |
April | 0.00 | 0.00 | 0.620987E+11 | 0.620987E+11 | 50421.70 | 30-APR-23:20 | 50421.70 | 0.00 |
May | 0.00 | 0.00 | 0.714947E+11 | 0.714947E+11 | 58188.26 | 31-MAY-23:05 | 58188.26 | 0.00 |
June | 0.00 | 0.00 | 0.691695E+11 | 0.691624E+11 | 58643.99 | 01-JUN-05:15 | 58643.99 | 0.00 |
July | 0.00 | 0.00 | 0.690349E+11 | 0.618016E+11 | 60476.66 | 01-JUL-05:13 | 53983.29 | 0.00 |
August | 0.00 | 0.00 | 0.661186E+11 | 0.626988E+11 | 56481.89 | 01-AUG-07:00 | 53353.87 | 0.00 |
September | 0.00 | 0.00 | 0.602229E+11 | 0.602229E+11 | 45764.68 | 30-SEP-05:15 | 45764.68 | 0.00 |
October | 0.00 | 0.00 | 0.551998E+11 | 0.551998E+11 | 31633.74 | 31-OCT-05:30 | 31633.74 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.455311E+12 | 0.444651E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.714947E+11 | 0.714947E+11 | 60476.66 | 58643.99 | 0.00 |
Report: CoilReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.228861E+10 | 0.228861E+10 | 46231.99 | 31-MAR-23:03 | 46231.99 | 0.00 |
April | 0.00 | 0.00 | 0.358380E+11 | 0.358380E+11 | 63809.82 | 30-APR-23:03 | 63809.82 | 0.00 |
May | 0.00 | 0.00 | 0.505395E+11 | 0.505395E+11 | 63809.82 | 01-MAY-17:23 | 63809.82 | 0.00 |
June | 0.00 | 0.00 | 0.565989E+11 | 0.565976E+11 | 74221.18 | 01-JUN-16:10 | 74221.18 | 0.00 |
July | 0.00 | 0.00 | 0.603495E+11 | 0.540421E+11 | 76541.78 | 01-JUL-20:10 | 68352.60 | 0.00 |
August | 0.00 | 0.00 | 0.565249E+11 | 0.536150E+11 | 71483.46 | 01-AUG-16:10 | 67535.31 | 0.00 |
September | 0.00 | 0.00 | 0.444114E+11 | 0.444114E+11 | 57912.94 | 30-SEP-16:05 | 57912.94 | 0.00 |
October | 0.00 | 0.00 | 0.318854E+11 | 0.318854E+11 | 40019.83 | 31-OCT-16:40 | 40019.83 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.338436E+12 | 0.329218E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.603495E+11 | 0.565976E+11 | 76541.78 | 74221.18 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.478836E+09 | 0.478836E+09 | 21907.64 | 22-APR-16:10 | 21907.64 | 0.00 |
May | 0.00 | 0.00 | 0.332680E+11 | 0.332680E+11 | 147431.63 | 31-MAY-18:03 | 147431.63 | 0.00 |
June | 0.00 | 0.00 | 0.126537E+12 | 0.125554E+12 | 217466.52 | 29-JUN-20:00 | 210546.81 | 0.18 |
July | 0.00 | 0.00 | 0.159515E+12 | 0.157099E+12 | 244676.48 | 29-JUL-18:03 | 210054.20 | 0.52 |
August | 0.00 | 0.00 | 0.933007E+11 | 0.931520E+11 | 205710.39 | 11-AUG-19:10 | 205710.39 | 0.32 |
September | 0.00 | 0.00 | 0.438856E+10 | 0.438856E+10 | 57277.58 | 02-SEP-18:00 | 57277.58 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.417488E+12 | 0.413940E+12 | 0.09 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.159515E+12 | 0.157099E+12 | 244676.48 | 210546.81 | 0.52 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 2616979.37 | 2616979.37 | 594.90 | 22-APR-14:20 | 594.90 | 0.00 |
May | 0.00 | 0.00 | 0.187749E+10 | 0.187749E+10 | 14984.27 | 31-MAY-16:00 | 14984.27 | 0.00 |
June | 0.00 | 0.00 | 0.875150E+10 | 0.866818E+10 | 20268.27 | 30-JUN-12:20 | 17681.75 | 0.13 |
July | 0.00 | 0.00 | 0.107248E+11 | 0.105096E+11 | 19576.59 | 03-JUL-15:10 | 10122.63 | 0.39 |
August | 0.00 | 0.00 | 0.644682E+10 | 0.640249E+10 | 17539.91 | 11-AUG-18:02 | 17539.91 | 0.23 |
September | 0.00 | 0.00 | 0.192142E+09 | 0.192142E+09 | 4990.98 | 07-SEP-16:00 | 4990.98 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.279954E+11 | 0.276525E+11 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.107248E+11 | 0.105096E+11 | 20268.27 | 17681.75 | 0.39 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3002826.45 | 3002826.45 | 3456.20 | 22-JAN-09:04 | 3456.20 | 0.00 |
February | 0.00 | 0.00 | 10943996.63 | 10705249.52 | 4196.49 | 11-FEB-19:04 | 4196.49 | 0.00 |
March | 0.00 | 0.00 | 0.235378E+09 | 0.231857E+09 | 13665.12 | 28-MAR-15:02 | 13665.12 | 0.00 |
April | 0.00 | 0.00 | 0.298456E+10 | 0.292097E+10 | 13681.20 | 18-APR-15:02 | 13681.20 | 0.04 |
May | 0.00 | 0.00 | 0.534421E+10 | 0.493939E+10 | 14437.85 | 31-MAY-18:02 | 14437.85 | 0.21 |
June | 0.00 | 0.00 | 0.797876E+10 | 0.585427E+10 | 14672.94 | 22-JUN-18:02 | 14672.94 | 0.78 |
July | 0.00 | 0.00 | 0.790830E+10 | 0.492802E+10 | 14962.95 | 26-JUL-15:01 | 12706.94 | 0.92 |
August | 0.00 | 0.00 | 0.586013E+10 | 0.370601E+10 | 14967.68 | 13-AUG-15:02 | 12707.02 | 0.81 |
September | 0.00 | 0.00 | 0.141209E+10 | 0.944702E+09 | 13813.49 | 02-SEP-18:02 | 13813.49 | 0.32 |
October | 0.00 | 0.00 | 77209575.93 | 59470141.29 | 13431.40 | 13-OCT-15:02 | 13431.40 | 0.01 |
November | 0.00 | 0.00 | 3119513.88 | 3119513.88 | 2880.83 | 04-NOV-08:04 | 2880.83 | 0.00 |
December | 0.00 | 0.00 | 1837285.95 | 1688269.36 | 3548.55 | 24-DEC-19:04 | 3548.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.318195E+11 | 0.236032E+11 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 1837285.95 | 1688269.36 | 2880.83 | 2880.83 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.797876E+10 | 0.585427E+10 | 14967.68 | 14672.94 | 0.92 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2102655.24 | 2102655.24 | 3819.93 | 22-JAN-09:04 | 3819.93 | 0.00 |
February | 0.00 | 0.00 | 7024243.77 | 6896742.40 | 4565.01 | 08-FEB-19:04 | 4565.01 | 0.00 |
March | 0.00 | 0.00 | 31823022.88 | 30988473.96 | 9984.54 | 27-MAR-18:01 | 9984.54 | 0.00 |
April | 0.00 | 0.00 | 0.153260E+10 | 0.150840E+10 | 12283.60 | 28-APR-15:02 | 12283.60 | 0.02 |
May | 0.00 | 0.00 | 0.315291E+10 | 0.286982E+10 | 14150.08 | 09-MAY-20:01 | 14150.08 | 0.17 |
June | 0.00 | 0.00 | 0.539385E+10 | 0.374820E+10 | 15446.04 | 28-JUN-21:51 | 13101.29 | 0.69 |
July | 0.00 | 0.00 | 0.537998E+10 | 0.329496E+10 | 15953.38 | 06-JUL-17:32 | 15953.38 | 0.70 |
August | 0.00 | 0.00 | 0.321582E+10 | 0.177348E+10 | 14134.02 | 01-AUG-21:51 | 12666.36 | 0.59 |
September | 0.00 | 0.00 | 0.542942E+09 | 0.341978E+09 | 12677.01 | 02-SEP-19:41 | 12677.01 | 0.16 |
October | 0.00 | 0.00 | 20797425.83 | 16424974.39 | 8895.12 | 03-OCT-15:02 | 8895.12 | 0.00 |
November | 0.00 | 0.00 | 1226373.41 | 1226373.41 | 3159.45 | 04-NOV-08:04 | 3159.45 | 0.00 |
December | 0.00 | 0.00 | 1391987.19 | 1281709.54 | 3195.98 | 24-DEC-19:04 | 3195.98 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.192825E+11 | 0.135957E+11 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 1226373.41 | 1226373.41 | 3159.45 | 3159.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.539385E+10 | 0.374820E+10 | 15953.38 | 15953.38 | 0.70 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.422028E+10 | 0.422028E+10 | 40899.66 | 31-MAR-13:20 | 40899.66 | 0.00 |
April | 0.00 | 0.00 | 0.351867E+11 | 0.351867E+11 | 64181.56 | 22-APR-13:20 | 64181.56 | 0.00 |
May | 0.00 | 0.00 | 0.455757E+11 | 0.454764E+11 | 61116.90 | 12-MAY-13:15 | 61116.90 | 0.01 |
June | 0.00 | 0.00 | 0.514512E+11 | 0.325493E+11 | 56929.73 | 30-JUN-12:30 | 49697.55 | 0.84 |
July | 0.00 | 0.00 | 0.539631E+11 | 0.295432E+11 | 64460.04 | 23-JUL-13:30 | 49127.82 | 0.99 |
August | 0.00 | 0.00 | 0.499388E+11 | 0.291545E+11 | 67963.16 | 25-AUG-13:30 | 54677.62 | 0.93 |
September | 0.00 | 0.00 | 0.242808E+11 | 0.198310E+11 | 61022.06 | 09-SEP-13:10 | 52375.30 | 0.30 |
October | 0.00 | 0.00 | 0.494406E+10 | 0.494406E+10 | 47516.46 | 03-OCT-12:50 | 47516.46 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.269561E+12 | 0.200905E+12 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.539631E+11 | 0.454764E+11 | 67963.16 | 64181.56 | 0.99 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 52117284.43 | 52117284.43 | 24147.22 | 09-JAN-09:04 | 24147.22 | 0.00 |
February | 0.00 | 0.00 | 59420822.73 | 59357957.94 | 29692.34 | 11-FEB-09:01 | 29692.34 | 0.00 |
March | 0.00 | 0.00 | 0.407010E+09 | 0.407010E+09 | 58522.73 | 22-MAR-18:02 | 58522.73 | 0.00 |
April | 0.00 | 0.00 | 0.811985E+10 | 0.808531E+10 | 63911.09 | 30-APR-18:02 | 63911.09 | 0.01 |
May | 0.00 | 0.00 | 0.290708E+11 | 0.284965E+11 | 68395.94 | 31-MAY-15:02 | 68395.94 | 0.06 |
June | 0.00 | 0.00 | 0.432211E+11 | 0.365669E+11 | 74566.11 | 30-JUN-21:51 | 62404.54 | 0.55 |
July | 0.00 | 0.00 | 0.453224E+11 | 0.341936E+11 | 75214.67 | 18-JUL-21:51 | 57829.79 | 0.63 |
August | 0.00 | 0.00 | 0.311017E+11 | 0.228834E+11 | 73200.55 | 12-AUG-21:52 | 58354.26 | 0.53 |
September | 0.00 | 0.00 | 0.114475E+11 | 0.797220E+10 | 62657.50 | 07-SEP-18:01 | 62657.50 | 0.40 |
October | 0.00 | 0.00 | 0.171337E+10 | 0.148887E+10 | 59758.09 | 04-OCT-18:02 | 59758.09 | 0.03 |
November | 0.00 | 0.00 | 46571621.01 | 46571621.01 | 27234.34 | 14-NOV-19:04 | 27234.34 | 0.00 |
December | 0.00 | 0.00 | 35155540.58 | 35155540.58 | 31937.80 | 24-DEC-09:01 | 31937.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.170597E+12 | 0.140287E+12 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 35155540.58 | 35155540.58 | 24147.22 | 24147.22 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.453224E+11 | 0.365669E+11 | 75214.67 | 68395.94 | 0.63 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2806730.70 | 2806730.70 | 3523.67 | 22-JAN-09:04 | 3523.67 | 0.00 |
February | 0.00 | 0.00 | 13590458.02 | 13414853.22 | 4269.17 | 07-FEB-19:04 | 4269.17 | 0.00 |
March | 0.00 | 0.00 | 0.409574E+09 | 0.394685E+09 | 12918.58 | 20-MAR-15:01 | 12918.58 | 0.01 |
April | 0.00 | 0.00 | 0.284730E+10 | 0.275474E+10 | 12919.95 | 29-APR-18:01 | 12919.95 | 0.06 |
May | 0.00 | 0.00 | 0.730143E+10 | 0.687268E+10 | 13634.72 | 31-MAY-18:02 | 13634.72 | 0.24 |
June | 0.00 | 0.00 | 0.901863E+10 | 0.695474E+10 | 13873.15 | 27-JUN-15:02 | 11635.26 | 0.80 |
July | 0.00 | 0.00 | 0.966335E+10 | 0.671080E+10 | 13818.26 | 26-JUL-15:01 | 12180.40 | 0.96 |
August | 0.00 | 0.00 | 0.704057E+10 | 0.478007E+10 | 13794.95 | 13-AUG-15:02 | 12196.50 | 0.85 |
September | 0.00 | 0.00 | 0.196288E+10 | 0.127387E+10 | 12954.99 | 02-SEP-18:02 | 12954.99 | 0.41 |
October | 0.00 | 0.00 | 0.179546E+09 | 0.132343E+09 | 12789.84 | 04-OCT-08:62 | 12789.84 | 0.03 |
November | 0.00 | 0.00 | 2403495.36 | 2403495.36 | 3059.82 | 04-NOV-08:04 | 3059.82 | 0.00 |
December | 0.00 | 0.00 | 1590622.10 | 1465744.91 | 3363.02 | 24-DEC-09:04 | 2682.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.384437E+11 | 0.298940E+11 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 1590622.10 | 1465744.91 | 3059.82 | 2682.23 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.966335E+10 | 0.695474E+10 | 13873.15 | 13634.72 | 0.96 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1837742.01 | 1837742.01 | 3331.60 | 22-JAN-09:04 | 3331.60 | 0.00 |
February | 0.00 | 0.00 | 7264750.64 | 7178868.61 | 3993.72 | 11-FEB-19:04 | 3993.72 | 0.00 |
March | 0.00 | 0.00 | 0.104630E+09 | 98957766.06 | 10813.64 | 27-MAR-08:61 | 10813.64 | 0.00 |
April | 0.00 | 0.00 | 0.126980E+10 | 0.121190E+10 | 11714.78 | 28-APR-15:02 | 11714.78 | 0.04 |
May | 0.00 | 0.00 | 0.524135E+10 | 0.488245E+10 | 12471.47 | 14-MAY-20:41 | 12471.47 | 0.22 |
June | 0.00 | 0.00 | 0.677613E+10 | 0.516035E+10 | 14004.85 | 30-JUN-21:51 | 11299.22 | 0.70 |
July | 0.00 | 0.00 | 0.709816E+10 | 0.491412E+10 | 15509.45 | 11-JUL-08:22 | 15170.90 | 0.74 |
August | 0.00 | 0.00 | 0.455910E+10 | 0.294840E+10 | 13415.54 | 12-AUG-21:52 | 10326.93 | 0.67 |
September | 0.00 | 0.00 | 0.940911E+09 | 0.578549E+09 | 11535.46 | 07-SEP-18:01 | 11535.46 | 0.28 |
October | 0.00 | 0.00 | 45176043.37 | 32528541.08 | 11138.88 | 04-OCT-08:62 | 11138.88 | 0.01 |
November | 0.00 | 0.00 | 909331.70 | 909331.70 | 3024.12 | 04-NOV-08:04 | 3024.12 | 0.00 |
December | 0.00 | 0.00 | 1229432.66 | 1148899.79 | 3338.62 | 24-DEC-19:04 | 3338.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.260465E+11 | 0.198383E+11 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 909331.70 | 909331.70 | 3024.12 | 3024.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.709816E+10 | 0.516035E+10 | 15509.45 | 15170.90 | 0.74 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 146088.51 | 117842.74 | 291.85 | 22-JAN-09:04 | 102.81 | 0.00 |
February | 0.00 | 0.00 | 1233426.58 | 1125484.95 | 771.48 | 09-FEB-19:04 | 521.94 | 0.00 |
March | 0.00 | 0.00 | 44398467.36 | 43282675.32 | 3547.24 | 27-MAR-18:01 | 3547.24 | 0.00 |
April | 0.00 | 0.00 | 0.716641E+09 | 0.699909E+09 | 3575.30 | 28-APR-15:02 | 3575.30 | 0.04 |
May | 0.00 | 0.00 | 0.124089E+10 | 0.113562E+10 | 3772.90 | 31-MAY-18:02 | 3772.90 | 0.22 |
June | 0.00 | 0.00 | 0.195159E+10 | 0.143864E+10 | 3845.81 | 24-JUN-15:01 | 3215.33 | 0.75 |
July | 0.00 | 0.00 | 0.193161E+10 | 0.121228E+10 | 3992.73 | 02-JUL-08:61 | 3064.67 | 0.90 |
August | 0.00 | 0.00 | 0.138083E+10 | 0.893057E+09 | 4114.21 | 13-AUG-08:61 | 3005.65 | 0.75 |
September | 0.00 | 0.00 | 0.303287E+09 | 0.214719E+09 | 3610.09 | 02-SEP-18:02 | 3610.09 | 0.20 |
October | 0.00 | 0.00 | 13826183.21 | 9834766.70 | 3341.28 | 13-OCT-15:02 | 3341.28 | 0.01 |
November | 0.00 | 0.00 | 159680.41 | 159680.41 | 290.20 | 08-NOV-16:04 | 290.20 | 0.00 |
December | 0.00 | 0.00 | 137731.89 | 93612.51 | 560.92 | 24-DEC-09:04 | 299.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.758475E+10 | 0.564884E+10 | 0.24 | |||
Minimum of Months | 0.00 | 0.00 | 137731.89 | 93612.51 | 290.20 | 102.81 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.195159E+10 | 0.143864E+10 | 4114.21 | 3772.90 | 0.90 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 173670.09 | 112167.29 | 370.15 | 22-JAN-09:04 | 166.81 | 0.00 |
February | 0.00 | 0.00 | 796325.23 | 678278.04 | 682.33 | 09-FEB-09:04 | 400.32 | 0.00 |
March | 0.00 | 0.00 | 3408816.74 | 3270803.40 | 1423.93 | 28-MAR-15:03 | 1423.93 | 0.00 |
April | 0.00 | 0.00 | 0.350095E+09 | 0.345432E+09 | 3175.42 | 28-APR-15:02 | 3175.42 | 0.01 |
May | 0.00 | 0.00 | 0.685509E+09 | 0.616840E+09 | 4148.01 | 14-MAY-20:22 | 4148.01 | 0.17 |
June | 0.00 | 0.00 | 0.134120E+10 | 0.905775E+09 | 4353.89 | 28-JUN-21:32 | 3909.15 | 0.69 |
July | 0.00 | 0.00 | 0.132905E+10 | 0.804292E+09 | 4176.96 | 24-JUL-21:51 | 3222.24 | 0.69 |
August | 0.00 | 0.00 | 0.729695E+09 | 0.396401E+09 | 3893.24 | 02-AUG-21:51 | 3380.74 | 0.56 |
September | 0.00 | 0.00 | 98911381.87 | 64189273.39 | 3355.38 | 02-SEP-19:41 | 3355.38 | 0.09 |
October | 0.00 | 0.00 | 4516792.09 | 3532129.72 | 1416.78 | 05-OCT-15:03 | 1237.69 | 0.00 |
November | 0.00 | 0.00 | 67155.43 | 67155.43 | 314.48 | 04-NOV-08:04 | 314.48 | 0.00 |
December | 0.00 | 0.00 | 136795.02 | 114374.37 | 526.80 | 24-DEC-09:04 | 292.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.454357E+10 | 0.314070E+10 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 67155.43 | 67155.43 | 314.48 | 166.81 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.134120E+10 | 0.905775E+09 | 4353.89 | 4148.01 | 0.69 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 8409693.45 | 8409693.45 | 4983.22 | 22-JAN-19:04 | 4983.22 | 0.00 |
February | 0.00 | 0.00 | 0.279524E+09 | 0.256650E+09 | 21517.02 | 15-FEB-16:01 | 21517.02 | 0.01 |
March | 0.00 | 0.00 | 0.245093E+10 | 0.241849E+10 | 21526.63 | 11-MAR-16:02 | 21526.63 | 0.01 |
April | 0.00 | 0.00 | 0.698283E+10 | 0.682567E+10 | 21529.82 | 16-APR-15:02 | 21529.82 | 0.06 |
May | 0.00 | 0.00 | 0.917696E+10 | 0.840453E+10 | 22712.64 | 31-MAY-18:02 | 22712.64 | 0.26 |
June | 0.00 | 0.00 | 0.111255E+11 | 0.797320E+10 | 23294.56 | 24-JUN-15:01 | 19291.30 | 0.76 |
July | 0.00 | 0.00 | 0.122088E+11 | 0.765276E+10 | 23223.98 | 13-JUL-18:02 | 23223.98 | 0.92 |
August | 0.00 | 0.00 | 0.106150E+11 | 0.708060E+10 | 22979.15 | 10-AUG-18:02 | 22979.15 | 0.82 |
September | 0.00 | 0.00 | 0.459990E+10 | 0.326781E+10 | 21731.89 | 02-SEP-18:02 | 21731.89 | 0.52 |
October | 0.00 | 0.00 | 0.117305E+10 | 0.106236E+10 | 21527.98 | 04-OCT-15:01 | 21527.98 | 0.05 |
November | 0.00 | 0.00 | 29641570.50 | 29641570.50 | 20746.62 | 08-NOV-16:01 | 20746.62 | 0.00 |
December | 0.00 | 0.00 | 3557625.53 | 3364208.95 | 4939.09 | 24-DEC-19:04 | 3713.42 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.586541E+11 | 0.449835E+11 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 3557625.53 | 3364208.95 | 4939.09 | 3713.42 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.122088E+11 | 0.840453E+10 | 23294.56 | 23223.98 | 0.92 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 289400.80 | 938714.21 | 12-JAN-09:03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 253085.67 | 883773.62 | 27-FEB-09:03 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 134880.24 | 781255.58 | 01-MAR-09:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 35790.37 | 315578.24 | 03-APR-08:61 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 18427.65 | 125559.00 | 19-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14044.99 | 114100.81 | 02-JUN-06:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 13717.36 | 127725.82 | 04-JUL-08:04 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20438.76 | 139165.60 | 29-AUG-08:05 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23023.63 | 136273.35 | 04-SEP-08:04 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 64851.56 | 308500.13 | 27-OCT-08:03 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 274033.95 | 843159.59 | 29-NOV-09:03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 335254.77 | 898377.12 | 15-DEC-09:03 |
Annual Sum or Average | 0.00 | 122409.02 | ||||
Minimum of Months | 0.00 | 0.00 | 13717.36 | 114100.81 | ||
Maximum of Months | 0.00 | 0.00 | 335254.77 | 938714.21 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 34.91 | 27729.75 | 05-JAN-09:04 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 335.20 | 45067.10 | 08-FEB-16:04 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 3962.90 | 90592.65 | 22-MAR-15:01 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 26500.28 | 187921.09 | 22-APR-15:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 57660.07 | 321511.18 | 31-MAY-15:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 110711.00 | 419566.85 | 21-JUN-15:05 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 122850.01 | 446965.72 | 29-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 84875.26 | 393262.12 | 11-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 22831.22 | 207945.00 | 02-SEP-15:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 4202.67 | 118386.79 | 03-OCT-15:02 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 57.08 | 30316.92 | 15-NOV-09:04 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 22.38 | 30544.97 | 24-DEC-16:04 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 36422.54 | 0.00 | ||||
Minimum of Months | 22.38 | 27729.75 | 0.00 | 0.00 | ||
Maximum of Months | 122850.01 | 446965.72 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 32956.75 | 68429.44 | 11-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 32963.39 | 68429.36 | 03-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 32987.36 | 68443.19 | 13-MAR-07:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 32809.74 | 68378.89 | 06-APR-06:20 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 32533.06 | 68507.71 | 08-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 31339.38 | 66781.25 | 01-JUN-06:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 30149.71 | 63898.83 | 03-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29451.49 | 61958.36 | 01-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 29360.13 | 61562.20 | 29-SEP-06:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 29958.71 | 63360.81 | 31-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 31166.75 | 65934.97 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 32440.51 | 68426.44 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 31501.53 | ||||
Minimum of Months | 0.00 | 0.00 | 29360.13 | 61562.20 | ||
Maximum of Months | 0.00 | 0.00 | 32987.36 | 68507.71 |
Report: FanReportMonthly
For: SWHSYS1 HPWH FAN
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.148176E+10 | 0.10 | 553.22 | 01-MAR-00:05 | 0.10 |
April | 0.955026E+09 | 0.07 | 553.22 | 01-APR-01:07 | 0.10 |
May | 0.809860E+09 | 0.07 | 553.22 | 01-MAY-03:10 | 0.10 |
June | 0.684162E+09 | 0.06 | 553.22 | 01-JUN-05:15 | 0.10 |
July | 0.665144E+09 | 0.06 | 553.22 | 01-JUL-05:13 | 0.10 |
August | 0.678910E+09 | 0.06 | 553.22 | 01-AUG-04:07 | 0.10 |
September | 0.754182E+09 | 0.06 | 553.22 | 01-SEP-03:07 | 0.10 |
October | 0.985779E+09 | 0.07 | 553.22 | 01-OCT-01:07 | 0.10 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.701482E+10 | 0.05 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.148176E+10 | 0.10 | 553.22 | 0.10 |
Report: FanReportMonthly
For: SWHSYSLAUNDRY HPWH FAN
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.187455E+10 | 0.10 | 700.51 | 01-MAR-00:05 | 0.10 |
April | 0.545469E+09 | 0.06 | 700.51 | 01-APR-16:05 | 0.10 |
May | 0.558189E+09 | 0.06 | 700.51 | 01-MAY-16:10 | 0.10 |
June | 0.539093E+09 | 0.05 | 700.51 | 01-JUN-16:10 | 0.10 |
July | 0.556892E+09 | 0.05 | 700.51 | 01-JUL-16:10 | 0.10 |
August | 0.557232E+09 | 0.05 | 700.51 | 01-AUG-16:10 | 0.10 |
September | 0.540295E+09 | 0.06 | 700.51 | 01-SEP-16:10 | 0.10 |
October | 0.563595E+09 | 0.06 | 700.51 | 01-OCT-16:10 | 0.10 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.573532E+10 | 0.04 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.187455E+10 | 0.10 | 700.51 | 0.10 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.71 | 1299.30 | 01-JAN-00:05 | 0.89 |
February | 0.244774E+10 | 0.71 | 1299.30 | 01-FEB-00:07 | 0.89 |
March | 0.271000E+10 | 0.71 | 1299.30 | 01-MAR-00:05 | 0.90 |
April | 0.262258E+10 | 0.71 | 1299.30 | 01-APR-00:40 | 0.89 |
May | 0.271000E+10 | 0.71 | 1299.30 | 01-MAY-00:50 | 0.89 |
June | 0.262258E+10 | 0.70 | 1299.30 | 01-JUN-02:30 | 0.89 |
July | 0.271000E+10 | 0.70 | 1299.30 | 01-JUL-00:30 | 0.88 |
August | 0.271000E+10 | 0.70 | 1299.30 | 01-AUG-00:50 | 0.88 |
September | 0.262258E+10 | 0.70 | 1299.30 | 01-SEP-00:10 | 0.89 |
October | 0.271000E+10 | 0.71 | 1299.30 | 01-OCT-00:10 | 0.89 |
November | 0.262258E+10 | 0.71 | 1299.30 | 01-NOV-00:10 | 0.89 |
December | 0.271000E+10 | 0.71 | 1299.30 | 01-DEC-00:03 | 0.90 |
Annual Sum or Average | 0.319080E+11 | 0.71 | |||
Minimum of Months | 0.244774E+10 | 0.70 | 1299.30 | 0.88 | |
Maximum of Months | 0.271000E+10 | 0.71 | 1299.30 | 0.90 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.310356E+11 | 0.78 | 16545.48 | 19-JAN-21:20 | 0.96 |
February | 0.284025E+11 | 0.79 | 17329.47 | 08-FEB-21:10 | 0.98 |
March | 0.330165E+11 | 0.81 | 18501.42 | 22-MAR-21:10 | 1.02 |
April | 0.337439E+11 | 0.83 | 22826.62 | 21-APR-21:10 | 1.16 |
May | 0.368886E+11 | 0.86 | 23806.32 | 12-MAY-21:10 | 1.19 |
June | 0.372904E+11 | 0.87 | 24227.56 | 12-JUN-21:10 | 1.19 |
July | 0.383043E+11 | 0.87 | 24921.23 | 12-JUL-21:10 | 1.21 |
August | 0.376084E+11 | 0.86 | 26051.86 | 25-AUG-21:10 | 1.24 |
September | 0.343469E+11 | 0.84 | 22321.93 | 08-SEP-21:10 | 1.14 |
October | 0.338241E+11 | 0.82 | 19837.62 | 03-OCT-21:10 | 1.06 |
November | 0.301028E+11 | 0.78 | 17255.88 | 01-NOV-20:20 | 0.98 |
December | 0.304991E+11 | 0.78 | 16237.05 | 24-DEC-20:10 | 0.94 |
Annual Sum or Average | 0.405063E+12 | 0.82 | |||
Minimum of Months | 0.284025E+11 | 0.78 | 16237.05 | 0.94 | |
Maximum of Months | 0.383043E+11 | 0.87 | 26051.86 | 1.24 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:05 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:03 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:05 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.27 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:05 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:05 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:05 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:05 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:05 | 0.27 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:03 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:05 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:10 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:10 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:05 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:05 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.437273E+09 | 0.56 | 822.20 | 01-JAN-09:01 | 0.58 |
February | 0.321388E+09 | 0.51 | 822.20 | 01-FEB-09:01 | 0.59 |
March | 0.244639E+09 | 0.44 | 822.20 | 01-MAR-09:01 | 0.59 |
April | 0.258396E+09 | 0.48 | 822.20 | 01-APR-08:61 | 0.58 |
May | 0.354791E+09 | 0.53 | 822.20 | 01-MAY-08:62 | 0.58 |
June | 0.481159E+09 | 0.54 | 822.20 | 01-JUN-08:61 | 0.58 |
July | 0.437334E+09 | 0.54 | 822.20 | 01-JUL-08:61 | 0.58 |
August | 0.348620E+09 | 0.52 | 822.20 | 01-AUG-08:61 | 0.58 |
September | 0.156453E+09 | 0.45 | 822.20 | 01-SEP-08:62 | 0.58 |
October | 0.220254E+09 | 0.45 | 822.20 | 01-OCT-15:02 | 0.58 |
November | 0.397316E+09 | 0.56 | 822.20 | 01-NOV-08:61 | 0.58 |
December | 0.466619E+09 | 0.57 | 822.20 | 01-DEC-09:01 | 0.59 |
Annual Sum or Average | 0.412424E+10 | 0.51 | |||
Minimum of Months | 0.156453E+09 | 0.44 | 822.20 | 0.58 | |
Maximum of Months | 0.481159E+09 | 0.57 | 822.20 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.421020E+09 | 0.56 | 737.69 | 01-JAN-09:01 | 0.58 |
February | 0.336377E+09 | 0.55 | 737.69 | 01-FEB-09:01 | 0.59 |
March | 0.270419E+09 | 0.50 | 737.69 | 01-MAR-09:01 | 0.59 |
April | 0.186272E+09 | 0.44 | 737.69 | 01-APR-08:61 | 0.58 |
May | 0.220583E+09 | 0.42 | 737.69 | 01-MAY-08:62 | 0.58 |
June | 0.312397E+09 | 0.41 | 737.69 | 01-JUN-08:61 | 0.58 |
July | 0.291027E+09 | 0.41 | 737.69 | 01-JUL-08:61 | 0.58 |
August | 0.190498E+09 | 0.38 | 737.69 | 01-AUG-08:61 | 0.58 |
September | 0.110889E+09 | 0.41 | 737.69 | 01-SEP-15:02 | 0.58 |
October | 0.233662E+09 | 0.48 | 737.69 | 03-OCT-08:61 | 0.58 |
November | 0.389437E+09 | 0.56 | 737.69 | 01-NOV-08:61 | 0.58 |
December | 0.438757E+09 | 0.57 | 737.69 | 01-DEC-09:01 | 0.59 |
Annual Sum or Average | 0.340134E+10 | 0.47 | |||
Minimum of Months | 0.110889E+09 | 0.38 | 737.69 | 0.58 | |
Maximum of Months | 0.438757E+09 | 0.57 | 737.69 | 0.59 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.170205E+10 | 0.55 | 1223.83 | 12-JAN-16:00 | 0.59 |
February | 0.419115E+09 | 0.21 | 958.76 | 26-FEB-06:00 | 0.59 |
March | 0.238093E+09 | 0.08 | 1600.37 | 31-MAR-13:20 | 0.59 |
April | 0.160749E+10 | 0.41 | 3019.14 | 22-APR-13:20 | 0.58 |
May | 0.211465E+10 | 0.54 | 3205.40 | 31-MAY-13:30 | 0.58 |
June | 0.235575E+10 | 0.58 | 1978.49 | 08-JUN-12:40 | 0.58 |
July | 0.234005E+10 | 0.58 | 3072.36 | 23-JUL-13:30 | 0.58 |
August | 0.228199E+10 | 0.56 | 3264.50 | 25-AUG-13:05 | 0.58 |
September | 0.125097E+10 | 0.41 | 3459.98 | 09-SEP-13:10 | 0.58 |
October | 0.269766E+09 | 0.11 | 1797.07 | 03-OCT-12:50 | 0.58 |
November | 0.121240E+10 | 0.47 | 1053.53 | 29-NOV-05:00 | 0.59 |
December | 0.210256E+10 | 0.58 | 1174.71 | 15-DEC-05:00 | 0.59 |
Annual Sum or Average | 0.178949E+11 | 0.42 | |||
Minimum of Months | 0.238093E+09 | 0.08 | 958.76 | 0.58 | |
Maximum of Months | 0.235575E+10 | 0.58 | 3459.98 | 0.59 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.179842E+10 | 0.47 | 3809.96 | 01-JAN-09:01 | 0.59 |
February | 0.137253E+10 | 0.44 | 3809.96 | 01-FEB-09:01 | 0.59 |
March | 0.107382E+10 | 0.42 | 3809.96 | 01-MAR-09:01 | 0.59 |
April | 0.816355E+09 | 0.41 | 3809.96 | 01-APR-15:02 | 0.59 |
May | 0.179199E+10 | 0.38 | 3809.96 | 01-MAY-08:62 | 0.58 |
June | 0.284006E+10 | 0.37 | 3809.96 | 01-JUN-08:61 | 0.58 |
July | 0.267084E+10 | 0.37 | 3809.96 | 01-JUL-08:61 | 0.58 |
August | 0.177518E+10 | 0.35 | 3809.96 | 01-AUG-08:61 | 0.58 |
September | 0.846025E+09 | 0.40 | 3809.96 | 01-SEP-08:62 | 0.58 |
October | 0.800405E+09 | 0.41 | 3809.96 | 01-OCT-08:62 | 0.58 |
November | 0.160292E+10 | 0.45 | 3809.96 | 01-NOV-08:61 | 0.59 |
December | 0.186530E+10 | 0.48 | 3809.96 | 01-DEC-09:01 | 0.59 |
Annual Sum or Average | 0.192538E+11 | 0.41 | |||
Minimum of Months | 0.800405E+09 | 0.35 | 3809.96 | 0.58 | |
Maximum of Months | 0.284006E+10 | 0.48 | 3809.96 | 0.59 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.418727E+09 | 0.56 | 776.15 | 01-JAN-09:01 | 0.58 |
February | 0.294656E+09 | 0.50 | 776.15 | 01-FEB-09:01 | 0.59 |
March | 0.213604E+09 | 0.44 | 776.15 | 01-MAR-09:01 | 0.59 |
April | 0.241932E+09 | 0.51 | 776.15 | 01-APR-15:02 | 0.58 |
May | 0.469382E+09 | 0.55 | 776.15 | 01-MAY-08:62 | 0.58 |
June | 0.537014E+09 | 0.56 | 776.15 | 01-JUN-08:61 | 0.58 |
July | 0.532812E+09 | 0.56 | 776.15 | 01-JUL-08:61 | 0.58 |
August | 0.410578E+09 | 0.54 | 776.15 | 01-AUG-08:61 | 0.58 |
September | 0.177765E+09 | 0.47 | 776.15 | 01-SEP-08:62 | 0.58 |
October | 0.198920E+09 | 0.45 | 776.15 | 01-OCT-08:62 | 0.58 |
November | 0.382061E+09 | 0.55 | 776.15 | 01-NOV-08:61 | 0.58 |
December | 0.449134E+09 | 0.57 | 776.15 | 01-DEC-09:01 | 0.59 |
Annual Sum or Average | 0.432658E+10 | 0.52 | |||
Minimum of Months | 0.177765E+09 | 0.44 | 776.15 | 0.58 | |
Maximum of Months | 0.537014E+09 | 0.57 | 776.15 | 0.59 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.408077E+09 | 0.56 | 703.21 | 01-JAN-09:01 | 0.58 |
February | 0.310796E+09 | 0.54 | 703.21 | 01-FEB-09:01 | 0.59 |
March | 0.226997E+09 | 0.44 | 703.21 | 01-MAR-09:01 | 0.59 |
April | 0.170226E+09 | 0.45 | 703.21 | 01-APR-08:61 | 0.58 |
May | 0.353214E+09 | 0.49 | 703.21 | 01-MAY-08:62 | 0.58 |
June | 0.416388E+09 | 0.43 | 703.21 | 01-JUN-08:61 | 0.58 |
July | 0.393009E+09 | 0.43 | 703.21 | 01-JUL-08:61 | 0.58 |
August | 0.274235E+09 | 0.43 | 703.21 | 01-AUG-08:61 | 0.58 |
September | 0.123382E+09 | 0.43 | 703.21 | 01-SEP-08:62 | 0.58 |
October | 0.206197E+09 | 0.46 | 703.21 | 01-OCT-08:62 | 0.58 |
November | 0.377426E+09 | 0.56 | 703.21 | 01-NOV-08:61 | 0.58 |
December | 0.425273E+09 | 0.57 | 703.21 | 01-DEC-09:01 | 0.59 |
Annual Sum or Average | 0.368522E+10 | 0.48 | |||
Minimum of Months | 0.123382E+09 | 0.43 | 703.21 | 0.58 | |
Maximum of Months | 0.425273E+09 | 0.57 | 703.21 | 0.59 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132246E+09 | 0.57 | 214.95 | 01-JAN-09:01 | 0.58 |
February | 98553249.96 | 0.55 | 214.95 | 01-FEB-09:01 | 0.58 |
March | 75777514.49 | 0.47 | 214.95 | 01-MAR-09:01 | 0.59 |
April | 70577031.52 | 0.48 | 214.95 | 01-APR-08:61 | 0.58 |
May | 85325018.67 | 0.52 | 214.95 | 01-MAY-15:02 | 0.58 |
June | 0.119165E+09 | 0.54 | 214.95 | 01-JUN-08:61 | 0.58 |
July | 0.108554E+09 | 0.53 | 214.95 | 01-JUL-08:61 | 0.58 |
August | 84110720.86 | 0.51 | 214.95 | 01-AUG-08:61 | 0.58 |
September | 43684199.98 | 0.44 | 214.95 | 01-SEP-15:02 | 0.58 |
October | 69856798.80 | 0.48 | 214.95 | 03-OCT-08:61 | 0.58 |
November | 0.119707E+09 | 0.57 | 214.95 | 01-NOV-08:61 | 0.58 |
December | 0.137683E+09 | 0.57 | 214.95 | 01-DEC-09:01 | 0.59 |
Annual Sum or Average | 0.114524E+10 | 0.52 | |||
Minimum of Months | 43684199.98 | 0.44 | 214.95 | 0.58 | |
Maximum of Months | 0.137683E+09 | 0.57 | 214.95 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.127746E+09 | 0.57 | 190.74 | 01-JAN-09:01 | 0.58 |
February | 0.100877E+09 | 0.57 | 190.74 | 01-FEB-09:01 | 0.58 |
March | 83439437.03 | 0.53 | 190.74 | 01-MAR-09:01 | 0.59 |
April | 53636096.51 | 0.45 | 190.74 | 01-APR-08:61 | 0.58 |
May | 51564919.29 | 0.42 | 190.74 | 01-MAY-15:02 | 0.58 |
June | 78927610.02 | 0.41 | 190.74 | 01-JUN-08:61 | 0.58 |
July | 72706402.28 | 0.41 | 190.74 | 01-JUL-08:61 | 0.58 |
August | 45002418.14 | 0.38 | 190.74 | 01-AUG-08:61 | 0.58 |
September | 34151980.41 | 0.41 | 190.74 | 01-SEP-15:02 | 0.58 |
October | 73157289.29 | 0.51 | 190.74 | 03-OCT-08:61 | 0.58 |
November | 0.116520E+09 | 0.57 | 190.74 | 01-NOV-08:61 | 0.58 |
December | 0.129590E+09 | 0.57 | 190.74 | 01-DEC-09:01 | 0.59 |
Annual Sum or Average | 0.967320E+09 | 0.48 | |||
Minimum of Months | 34151980.41 | 0.38 | 190.74 | 0.58 | |
Maximum of Months | 0.129590E+09 | 0.57 | 190.74 | 0.59 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.626546E+09 | 0.53 | 1288.93 | 01-JAN-09:01 | 0.58 |
February | 0.412499E+09 | 0.48 | 1288.93 | 01-FEB-09:01 | 0.59 |
March | 0.391729E+09 | 0.48 | 1288.93 | 01-MAR-09:01 | 0.59 |
April | 0.494234E+09 | 0.52 | 1288.93 | 01-APR-15:02 | 0.58 |
May | 0.580001E+09 | 0.54 | 1288.93 | 01-MAY-08:62 | 0.58 |
June | 0.641470E+09 | 0.54 | 1288.93 | 01-JUN-08:61 | 0.58 |
July | 0.654202E+09 | 0.54 | 1288.93 | 01-JUL-08:61 | 0.58 |
August | 0.612569E+09 | 0.53 | 1288.93 | 01-AUG-08:61 | 0.58 |
September | 0.349353E+09 | 0.49 | 1288.93 | 01-SEP-08:62 | 0.58 |
October | 0.313321E+09 | 0.45 | 1288.93 | 01-OCT-08:62 | 0.58 |
November | 0.551881E+09 | 0.52 | 1288.93 | 01-NOV-08:61 | 0.58 |
December | 0.699656E+09 | 0.56 | 1288.93 | 01-DEC-09:01 | 0.59 |
Annual Sum or Average | 0.632746E+10 | 0.52 | |||
Minimum of Months | 0.313321E+09 | 0.45 | 1288.93 | 0.58 | |
Maximum of Months | 0.699656E+09 | 0.56 | 1288.93 | 0.59 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.789587E+09 | 0.717735E+09 | 1979.65 | 12-JAN-09:13 | 1799.50 | 1799.50 | 49.20 | 6.74 |
February | 0.611699E+09 | 0.556034E+09 | 1735.82 | 27-FEB-09:03 | 1577.86 | 1577.86 | 49.19 | 6.40 |
March | 0.225203E+09 | 0.204710E+09 | 1328.73 | 01-MAR-05:00 | 1207.81 | 1207.81 | 51.50 | 5.75 |
April | 8793869.42 | 7993627.30 | 70.21 | 03-APR-08:61 | 63.82 | 63.82 | 35.08 | 1.60 |
May | 2899126.66 | 2635306.13 | 11.45 | 25-MAY-08:07 | 10.40 | 10.40 | 32.47 | 0.62 |
June | 1911392.74 | 1737456.00 | 9.59 | 01-JUN-06:20 | 8.72 | 8.72 | 31.27 | 0.56 |
July | 1968414.08 | 1789288.40 | 11.90 | 04-JUL-08:04 | 10.82 | 10.82 | 31.26 | 0.63 |
August | 3106303.06 | 2823629.49 | 14.21 | 29-AUG-08:05 | 12.92 | 12.92 | 32.28 | 0.70 |
September | 4310737.42 | 3918460.32 | 13.67 | 04-SEP-08:04 | 12.43 | 12.43 | 31.99 | 0.68 |
October | 22627745.40 | 20568620.56 | 76.77 | 27-OCT-08:61 | 69.79 | 69.79 | 38.15 | 1.67 |
November | 0.663843E+09 | 0.603433E+09 | 1638.74 | 29-NOV-10:20 | 1489.62 | 1489.62 | 51.54 | 6.25 |
December | 0.959195E+09 | 0.871909E+09 | 1820.70 | 15-DEC-09:02 | 1655.02 | 1655.02 | 49.92 | 6.52 |
Annual Sum or Average | 0.329515E+10 | 0.299529E+10 | ||||||
Minimum of Months | 1911392.74 | 1737456.00 | 9.59 | 8.72 | 8.72 | 31.26 | 0.56 | |
Maximum of Months | 0.959195E+09 | 0.871909E+09 | 1979.65 | 1799.50 | 1799.50 | 51.54 | 6.74 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 4443781.77 | 4039397.63 | 1393.74 | 27-JAN-09:04 | 1266.91 | 1266.91 | 8.40 | 2.45 |
February | 25291329.05 | 22989818.11 | 1986.39 | 08-FEB-16:04 | 1805.63 | 1805.63 | 8.40 | 3.82 |
March | 0.414777E+09 | 0.377033E+09 | 2785.93 | 22-MAR-15:01 | 2532.41 | 2532.41 | 8.40 | 6.31 |
April | 0.258591E+10 | 0.235060E+10 | 3185.74 | 13-APR-15:02 | 2895.84 | 2895.84 | 8.40 | 8.17 |
May | 0.487400E+10 | 0.443047E+10 | 3578.24 | 31-MAY-15:03 | 3252.62 | 3252.62 | 7.55 | 11.12 |
June | 0.627004E+10 | 0.569946E+10 | 3968.40 | 21-JUN-18:03 | 3607.28 | 3607.28 | 6.92 | 16.94 |
July | 0.665550E+10 | 0.604985E+10 | 4000.12 | 12-JUL-18:03 | 3636.11 | 3636.11 | 7.11 | 17.38 |
August | 0.562907E+10 | 0.511682E+10 | 3916.39 | 11-AUG-15:13 | 3560.00 | 3560.00 | 7.03 | 16.16 |
September | 0.242548E+10 | 0.220476E+10 | 3348.62 | 02-SEP-15:03 | 3043.89 | 3043.89 | 8.24 | 9.18 |
October | 0.492660E+09 | 0.447828E+09 | 2964.57 | 03-OCT-15:02 | 2694.80 | 2694.80 | 8.40 | 7.06 |
November | 5540850.54 | 5036633.14 | 1388.73 | 18-NOV-19:04 | 1262.36 | 1262.36 | 8.40 | 2.44 |
December | 2729747.82 | 2481340.77 | 1380.74 | 31-DEC-19:04 | 1255.09 | 1255.09 | 8.40 | 2.43 |
Annual Sum or Average | 0.293854E+11 | 0.267114E+11 | ||||||
Minimum of Months | 2729747.82 | 2481340.77 | 1380.74 | 1255.09 | 1255.09 | 6.92 | 2.43 | |
Maximum of Months | 0.665550E+10 | 0.604985E+10 | 4000.12 | 3636.11 | 3636.11 | 8.40 | 17.38 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 20474304.76 | 18611143.03 | 3340.80 | 01-JAN-09:03 | 3036.78 | 3036.78 | 8.57 | 23.65 |
February | 0.449003E+09 | 0.408144E+09 | 3340.80 | 01-FEB-19:04 | 3036.78 | 3036.78 | 8.54 | 23.65 |
March | 0.256208E+10 | 0.232893E+10 | 3340.80 | 01-MAR-09:04 | 3036.78 | 3036.78 | 8.48 | 23.65 |
April | 0.646442E+10 | 0.587615E+10 | 3340.80 | 01-APR-08:03 | 3036.78 | 3036.78 | 8.46 | 23.65 |
May | 0.892794E+10 | 0.811550E+10 | 3340.80 | 01-MAY-00:05 | 3036.78 | 3036.78 | 8.51 | 23.65 |
June | 0.864732E+10 | 0.786041E+10 | 3340.80 | 01-JUN-00:05 | 3036.78 | 3036.78 | 8.92 | 23.65 |
July | 0.894799E+10 | 0.813372E+10 | 3340.80 | 01-JUL-00:10 | 3036.78 | 3036.78 | 9.04 | 23.65 |
August | 0.893195E+10 | 0.811914E+10 | 3340.80 | 01-AUG-00:05 | 3036.78 | 3036.78 | 9.20 | 23.65 |
September | 0.749059E+10 | 0.680895E+10 | 3340.80 | 01-SEP-00:05 | 3036.78 | 3036.78 | 8.56 | 23.65 |
October | 0.290637E+10 | 0.264189E+10 | 3340.80 | 01-OCT-06:40 | 3036.78 | 3036.78 | 8.42 | 23.65 |
November | 63761471.23 | 57959177.35 | 3340.80 | 01-NOV-08:04 | 3036.78 | 3036.78 | 8.63 | 23.65 |
December | 13983616.07 | 12711107.01 | 3340.80 | 01-DEC-09:06 | 3036.78 | 3036.78 | 8.48 | 23.65 |
Annual Sum or Average | 0.554259E+11 | 0.503821E+11 | ||||||
Minimum of Months | 13983616.07 | 12711107.01 | 3340.80 | 3036.78 | 3036.78 | 8.42 | 23.65 | |
Maximum of Months | 0.894799E+10 | 0.813372E+10 | 3340.80 | 3036.78 | 3036.78 | 9.20 | 23.65 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 45.91 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 46.93 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 47.20 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 50.53 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 50.39 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 50.64 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 51.28 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 51.29 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 51.41 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 50.58 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 50.87 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 47.39 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 45.91 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 51.41 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 47.88 | 82.20 | 289400.80 | 938714.21 | 12-JAN-09:03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 46.77 | 82.20 | 253085.67 | 883773.62 | 27-FEB-09:03 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 51.34 | 82.20 | 134880.24 | 781255.58 | 01-MAR-09:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 50.98 | 82.20 | 35790.37 | 315578.24 | 03-APR-08:61 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 45.13 | 79.95 | 18427.65 | 125559.00 | 19-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.13 | 79.40 | 14044.99 | 114100.81 | 02-JUN-06:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.75 | 26.75 | 13717.36 | 127725.82 | 04-JUL-08:04 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 30.45 | 30.45 | 20438.76 | 139165.60 | 29-AUG-08:05 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.92 | 79.72 | 23023.63 | 136273.35 | 04-SEP-08:04 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 65.46 | 80.84 | 64851.56 | 308500.13 | 27-OCT-08:03 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 51.67 | 82.20 | 274033.95 | 843159.59 | 29-NOV-09:03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 52.19 | 82.20 | 335254.77 | 898377.12 | 15-DEC-09:03 |
Annual Sum or Average | 0.00 | 122409.02 | ||||||
Minimum of Months | 0.00 | 0.00 | 26.13 | 26.75 | 13717.36 | 114100.81 | ||
Maximum of Months | 0.00 | 0.00 | 65.46 | 82.20 | 335254.77 | 938714.21 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 34.91 | 27729.75 | 05-JAN-09:04 | 8.65 | 8.37 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 335.20 | 45067.10 | 08-FEB-16:04 | 8.82 | 8.37 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 3962.90 | 90592.65 | 22-MAR-15:01 | 9.28 | 8.37 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 26500.28 | 187921.09 | 22-APR-15:03 | 10.27 | 8.37 | 0.00 | 0.00 | 01-APR-00:10 |
May | 57660.07 | 321511.18 | 31-MAY-15:03 | 10.76 | 7.51 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 110711.00 | 419566.85 | 21-JUN-15:05 | 11.18 | 6.94 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 122850.01 | 446965.72 | 29-JUL-18:03 | 11.21 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 84875.26 | 393262.12 | 11-AUG-18:03 | 10.85 | 6.88 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 22831.22 | 207945.00 | 02-SEP-15:03 | 10.30 | 8.20 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 4202.67 | 118386.79 | 03-OCT-15:02 | 9.56 | 8.37 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 57.08 | 30316.92 | 15-NOV-09:04 | 8.68 | 8.37 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 22.38 | 30544.97 | 24-DEC-16:04 | 8.68 | 8.37 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 36422.54 | 0.00 | ||||||
Minimum of Months | 22.38 | 27729.75 | 8.65 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 122850.01 | 446965.72 | 11.21 | 8.37 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 45.91 | 59.99 | 32956.75 | 68429.44 | 11-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 46.93 | 59.73 | 32963.39 | 68429.36 | 03-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 47.20 | 59.74 | 32987.36 | 68443.19 | 13-MAR-07:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 50.53 | 59.81 | 32809.74 | 68378.89 | 06-APR-06:20 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 50.39 | 59.97 | 32533.06 | 68507.71 | 08-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 50.64 | 60.00 | 31339.38 | 66781.25 | 01-JUN-06:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 51.28 | 59.99 | 30149.71 | 63898.83 | 03-JUL-06:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 51.29 | 59.97 | 29451.49 | 61958.36 | 01-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 51.41 | 59.97 | 29360.13 | 61562.20 | 29-SEP-06:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 50.58 | 59.95 | 29958.71 | 63360.81 | 31-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 50.87 | 59.74 | 31166.75 | 65934.97 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 47.39 | 59.74 | 32440.51 | 68426.44 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 31501.53 | ||||||
Minimum of Months | 0.00 | 0.00 | 45.91 | 59.73 | 29360.13 | 61562.20 | ||
Maximum of Months | 0.00 | 0.00 | 51.41 | 60.00 | 32987.36 | 68507.71 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.605162E+12 | 0.00 | 0.00 | 0.310356E+11 | 0.00 | 0.00 |
February | 0.497869E+12 | 0.00 | 0.00 | 0.284025E+11 | 0.00 | 0.00 |
March | 0.293032E+12 | 0.00 | 0.00 | 0.330165E+11 | 0.00 | 0.00 |
April | 0.788826E+11 | 0.00 | 0.478836E+09 | 0.337439E+11 | 0.00 | 0.00 |
May | 0.492175E+11 | 0.00 | 0.332680E+11 | 0.368886E+11 | 0.00 | 0.00 |
June | 0.365383E+11 | 0.00 | 0.126537E+12 | 0.372904E+11 | 0.00 | 0.00 |
July | 0.368596E+11 | 0.00 | 0.159515E+12 | 0.383043E+11 | 0.00 | 0.00 |
August | 0.547681E+11 | 0.00 | 0.933007E+11 | 0.376084E+11 | 0.00 | 0.00 |
September | 0.540940E+11 | 0.00 | 0.438856E+10 | 0.343469E+11 | 0.00 | 0.00 |
October | 0.131446E+12 | 0.00 | 0.00 | 0.338241E+11 | 0.00 | 0.00 |
November | 0.561331E+12 | 0.00 | 0.00 | 0.301028E+11 | 0.00 | 0.00 |
December | 0.701737E+12 | 0.00 | 0.00 | 0.304991E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.310094E+13 | 0.00 | 0.417488E+12 | 0.405063E+12 | 0.00 | 0.00 |
Minimum of Months | 0.365383E+11 | 0.00 | 0.00 | 0.284025E+11 | 0.00 | 0.00 |
Maximum of Months | 0.701737E+12 | 0.00 | 0.159515E+12 | 0.383043E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.337919E+11 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
February | 0.302154E+11 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
March | 0.164020E+11 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
April | 0.215662E+10 | 0.00 | 2616979.37 | 0.262258E+10 | 0.00 | 0.00 |
May | 13294.10 | 0.00 | 0.187749E+10 | 0.271000E+10 | 0.00 | 0.00 |
June | 32189.03 | 0.00 | 0.875150E+10 | 0.262258E+10 | 0.00 | 0.00 |
July | 31761.24 | 0.00 | 0.107248E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 2803799.50 | 0.00 | 0.644682E+10 | 0.271000E+10 | 0.00 | 0.00 |
September | 0.119726E+09 | 0.00 | 0.192142E+09 | 0.262258E+10 | 0.00 | 0.00 |
October | 0.418381E+10 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
November | 0.325190E+11 | 0.00 | 0.00 | 0.262258E+10 | 0.00 | 0.00 |
December | 0.408317E+11 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.160223E+12 | 0.00 | 0.279954E+11 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 13294.10 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.408317E+11 | 0.00 | 0.107248E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.310356E+11 | 0.00 | 0.605162E+12 | 0.804626E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.284025E+11 | 0.00 | 0.497869E+12 | 0.682747E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.330165E+11 | 0.00 | 0.293032E+12 | 0.839225E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.337439E+11 | 0.478836E+09 | 0.788826E+11 | 0.571454E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.368886E+11 | 0.332680E+11 | 0.492175E+11 | 0.179070E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.372904E+11 | 0.126537E+12 | 0.365383E+11 | 0.193299E+11 | 0.178457E+09 | 0.00 | 0.00 | 0.00 |
July | 0.383043E+11 | 0.159515E+12 | 0.368596E+11 | 0.123250E+11 | 0.865165E+09 | 0.00 | 0.00 | 0.00 |
August | 0.376084E+11 | 0.933007E+11 | 0.547681E+11 | 0.494819E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.343469E+11 | 0.438856E+10 | 0.540940E+11 | 0.334877E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.338241E+11 | 0.00 | 0.131446E+12 | 0.724417E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.301028E+11 | 0.00 | 0.561331E+12 | 0.802780E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.304991E+11 | 0.00 | 0.701737E+12 | 0.759287E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.405063E+12 | 0.417488E+12 | 0.310094E+13 | 0.577962E+13 | 0.104362E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.284025E+11 | 0.00 | 0.365383E+11 | 0.123250E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.383043E+11 | 0.159515E+12 | 0.701737E+12 | 0.839225E+12 | 0.865165E+09 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.00 | 0.337919E+11 | 0.716220E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.00 | 0.302154E+11 | 0.601875E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.00 | 0.164020E+11 | 0.743703E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 2616979.37 | 0.215662E+10 | 0.544391E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.187749E+10 | 13294.10 | 0.225347E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.875150E+10 | 32189.03 | 0.563671E+10 | 0.104584E+09 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.107248E+11 | 31761.24 | 0.479875E+10 | 0.278699E+09 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.644682E+10 | 2803799.50 | 0.103310E+11 | 20121095.44 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.192142E+09 | 0.119726E+09 | 0.342303E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.00 | 0.418381E+10 | 0.657283E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.00 | 0.325190E+11 | 0.713916E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.00 | 0.408317E+11 | 0.681401E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.279954E+11 | 0.160223E+12 | 0.543410E+12 | 0.403405E+09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.00 | 13294.10 | 0.479875E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.107248E+11 | 0.408317E+11 | 0.743703E+11 | 0.278699E+09 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.310356E+11 | 0.605162E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.284025E+11 | 0.497869E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.330165E+11 | 0.293032E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.337439E+11 | 0.788826E+11 | 0.478836E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.368886E+11 | 0.492175E+11 | 0.332680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.372904E+11 | 0.365383E+11 | 0.126537E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.383043E+11 | 0.368596E+11 | 0.159515E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.376084E+11 | 0.547681E+11 | 0.933007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.343469E+11 | 0.540940E+11 | 0.438856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.338241E+11 | 0.131446E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.301028E+11 | 0.561331E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.304991E+11 | 0.701737E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.405063E+12 | 0.310094E+13 | 0.417488E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.284025E+11 | 0.365383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.383043E+11 | 0.701737E+12 | 0.159515E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.337919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.302154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.164020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.215662E+10 | 2616979.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 13294.10 | 0.187749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 32189.03 | 0.875150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 31761.24 | 0.107248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 2803799.50 | 0.644682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.119726E+09 | 0.192142E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.418381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.325190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.408317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.160223E+12 | 0.279954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 13294.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.408317E+11 | 0.107248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.790100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226171E+10 | 0.00 | 0.00 | 0.80 |
February | 0.689102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186560E+10 | 0.00 | 0.00 | 0.79 |
March | 0.578709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 |
April | 0.418639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.80 |
May | 0.399730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.80 |
June | 0.319016E+11 | 0.00 | 0.00 | 0.00 | 5092308.37 | 0.00 | 0.00 | 0.00 | 0.80 |
July | 0.309063E+11 | 0.00 | 0.00 | 0.00 | 20072063.38 | 0.00 | 0.00 | 0.00 | 0.80 |
August | 0.268273E+11 | 0.00 | 0.00 | 7446061.79 | 0.00 | 0.00 | 0.102322E+11 | 0.00 | 0.80 |
September | 0.151320E+11 | 0.00 | 0.00 | 20027574.88 | 0.00 | 0.00 | 0.260282E+11 | 0.00 | 0.82 |
October | 0.172847E+11 | 0.00 | 0.00 | 21579337.60 | 0.00 | 0.00 | 0.289134E+11 | 0.00 | 0.83 |
November | 0.623950E+11 | 0.00 | 0.00 | 6991047.38 | 0.00 | 0.00 | 0.155629E+11 | 0.00 | 0.80 |
December | 0.892453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.80 |
Annual Sum or Average | 0.561320E+12 | 0.00 | 0.00 | 56044021.65 | 25164371.76 | 0.412731E+10 | 0.807366E+11 | 0.00 | 0.80 |
Minimum of Months | 0.151320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 |
Maximum of Months | 0.892453E+11 | 0.00 | 0.00 | 21579337.60 | 20072063.38 | 0.226171E+10 | 0.289134E+11 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.500226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198459E+11 | 0.00 | 0.00 | 3.63 |
February | 0.363165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140869E+11 | 0.00 | 0.00 | 3.59 |
March | 0.782323E+10 | 0.00 | 0.00 | 496167.69 | 0.00 | 0.584931E+10 | 0.822019E+09 | 0.00 | 3.60 |
April | 0.849722E+10 | 0.00 | 0.00 | 1899298.46 | 0.00 | 0.338333E+09 | 0.178281E+10 | 0.00 | 3.68 |
May | 0.895887E+10 | 0.00 | 0.00 | 1692129.32 | 0.00 | 0.00 | 0.110776E+10 | 0.00 | 3.66 |
June | 0.734696E+10 | 1278029.84 | 0.00 | 1539154.62 | 33006.43 | 0.00 | 0.651799E+09 | 0.00 | 3.64 |
July | 0.732867E+10 | 4780004.79 | 0.00 | 1813527.57 | 500695.88 | 0.00 | 0.419100E+09 | 0.00 | 3.68 |
August | 0.848428E+10 | 0.00 | 0.00 | 2310795.80 | 0.00 | 0.00 | 0.860324E+09 | 0.00 | 3.68 |
September | 0.939869E+10 | 0.00 | 0.00 | 751944.34 | 0.00 | 2833699.83 | 0.673488E+09 | 0.00 | 3.63 |
October | 0.775400E+10 | 0.00 | 0.00 | 162995.08 | 0.00 | 0.327896E+10 | 0.215093E+09 | 0.00 | 3.62 |
November | 0.862275E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185868E+11 | 0.00 | 0.00 | 3.61 |
December | 31383090.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223109E+11 | 0.00 | 0.00 | 3.62 |
Annual Sum or Average | 0.706175E+11 | 6058034.63 | 0.00 | 10666012.88 | 533702.31 | 0.843000E+11 | 0.653239E+10 | 0.00 | 3.64 |
Minimum of Months | 31383090.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.59 |
Maximum of Months | 0.939869E+10 | 4780004.79 | 0.00 | 2310795.80 | 500695.88 | 0.223109E+11 | 0.178281E+10 | 0.00 | 3.68 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.806916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.951974E+09 | 0.00 | 0.00 | 1.39 |
February | 0.784206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14035727.85 | 0.00 | 0.00 | 1.38 |
March | 0.642365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.38 |
April | 0.411885E+10 | 0.00 | 0.00 | 283291.43 | 0.00 | 0.00 | 0.530482E+09 | 0.00 | 1.39 |
May | 0.337586E+10 | 0.00 | 0.00 | 750669.17 | 0.00 | 0.00 | 0.106912E+10 | 0.00 | 1.40 |
June | 0.196183E+10 | 0.00 | 0.00 | 1861554.18 | 565244.98 | 0.00 | 0.160212E+10 | 0.00 | 1.41 |
July | 0.187705E+10 | 730910.15 | 0.00 | 1827377.80 | 1497083.95 | 0.00 | 0.157733E+10 | 0.00 | 1.42 |
August | 0.259229E+10 | 0.00 | 0.00 | 1397486.02 | 0.00 | 0.00 | 0.153915E+10 | 0.00 | 1.40 |
September | 0.400340E+10 | 0.00 | 0.00 | 147976.03 | 0.00 | 0.00 | 0.451309E+09 | 0.00 | 1.39 |
October | 0.497025E+10 | 0.00 | 0.00 | 1495.15 | 0.00 | 0.00 | 15390510.30 | 0.00 | 1.39 |
November | 0.862341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.38 |
December | 0.959194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314260E+09 | 0.00 | 0.00 | 1.39 |
Annual Sum or Average | 0.634498E+11 | 730910.15 | 0.00 | 6269849.78 | 2062328.93 | 0.128027E+10 | 0.678491E+10 | 0.00 | 1.39 |
Minimum of Months | 0.187705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.38 |
Maximum of Months | 0.959194E+10 | 730910.15 | 0.00 | 1861554.18 | 1497083.95 | 0.951974E+09 | 0.160212E+10 | 0.00 | 1.42 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.151475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543166E+10 | 0.00 | 0.00 | 0.51 |
February | 0.214995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389936E+10 | 0.00 | 0.00 | 0.50 |
March | 0.371495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123136E+10 | 0.00 | 0.00 | 0.50 |
April | 0.357817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
May | 0.341655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
June | 0.262705E+10 | 0.00 | 0.00 | 156017.16 | 435246.94 | 0.00 | 0.100031E+09 | 0.00 | 0.51 |
July | 0.247458E+10 | 3115.73 | 0.00 | 300315.86 | 1712472.47 | 0.00 | 0.168902E+09 | 0.00 | 0.51 |
August | 0.310722E+10 | 0.00 | 0.00 | 47136.35 | 0.00 | 0.00 | 55553151.93 | 0.00 | 0.50 |
September | 0.343031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
October | 0.372443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114590E+09 | 0.00 | 0.00 | 0.50 |
November | 0.198910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465105E+10 | 0.00 | 0.00 | 0.50 |
December | 0.135390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627402E+10 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.330810E+11 | 3115.73 | 0.00 | 503469.36 | 2147719.41 | 0.216020E+11 | 0.324486E+09 | 0.00 | 0.51 |
Minimum of Months | 0.135390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.372443E+10 | 3115.73 | 0.00 | 300315.86 | 1712472.47 | 0.627402E+10 | 0.168902E+09 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 26460104.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371459E+10 | 0.00 | 0.00 | 0.47 |
February | 0.214871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304304E+10 | 0.00 | 0.00 | 0.47 |
March | 0.859302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180458E+10 | 0.00 | 0.00 | 0.47 |
April | 0.175856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168493E+09 | 0.00 | 0.00 | 0.47 |
May | 0.184001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.146739E+10 | 0.00 | 0.00 | 28.15 | 234406.00 | 0.00 | 1082579.47 | 0.00 | 0.47 |
July | 0.141887E+10 | 0.00 | 0.00 | 919.83 | 923944.87 | 0.00 | 3792586.82 | 0.00 | 0.48 |
August | 0.170337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.184742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 0.138438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683162E+09 | 0.00 | 0.00 | 0.47 |
November | 46157015.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352995E+10 | 0.00 | 0.00 | 0.47 |
December | 11167367.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409692E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.125779E+11 | 0.00 | 0.00 | 947.98 | 1158350.87 | 0.170407E+11 | 4875166.29 | 0.00 | 0.47 |
Minimum of Months | 11167367.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.184742E+10 | 0.00 | 0.00 | 919.83 | 923944.87 | 0.409692E+10 | 3792586.82 | 0.00 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.966928E+10 | 0.00 | 0.00 | 85206023.52 | 0.00 | 0.210308E+10 | 0.136617E+12 | 0.00 | 23.44 |
February | 0.489502E+10 | 0.00 | 0.00 | 80517306.52 | 0.00 | 0.104496E+09 | 0.124254E+12 | 0.00 | 23.19 |
March | 0.682962E+09 | 0.00 | 0.00 | 95485446.54 | 0.00 | 0.00 | 0.109038E+12 | 0.00 | 23.87 |
April | 0.211118E+09 | 0.00 | 0.00 | 97262647.43 | 0.00 | 0.00 | 0.805565E+11 | 0.00 | 24.09 |
May | 0.236444E+09 | 0.00 | 0.00 | 0.114024E+09 | 0.00 | 0.00 | 0.772954E+11 | 0.00 | 24.07 |
June | 87325910.66 | 8475499.87 | 0.00 | 0.122727E+09 | 0.00 | 0.00 | 0.599110E+11 | 0.00 | 24.06 |
July | 0.120040E+09 | 36816334.17 | 0.00 | 0.129100E+09 | 0.00 | 0.00 | 0.578672E+11 | 0.00 | 24.05 |
August | 0.169656E+09 | 0.00 | 0.00 | 0.116556E+09 | 0.00 | 0.00 | 0.702823E+11 | 0.00 | 24.02 |
September | 0.190963E+09 | 0.00 | 0.00 | 95584699.92 | 0.00 | 0.00 | 0.777693E+11 | 0.00 | 24.15 |
October | 0.291072E+09 | 0.00 | 0.00 | 96297713.45 | 0.00 | 0.00 | 0.864939E+11 | 0.00 | 24.07 |
November | 0.276841E+10 | 0.00 | 0.00 | 85575635.47 | 0.00 | 0.00 | 0.139390E+12 | 0.00 | 23.30 |
December | 0.474639E+10 | 0.00 | 0.00 | 84889945.75 | 0.00 | 83901552.28 | 0.157363E+12 | 0.00 | 23.07 |
Annual Sum or Average | 0.240687E+11 | 45291834.04 | 0.00 | 0.120323E+10 | 0.00 | 0.229148E+10 | 0.117684E+13 | 0.00 | 23.78 |
Minimum of Months | 87325910.66 | 0.00 | 0.00 | 80517306.52 | 0.00 | 0.00 | 0.578672E+11 | 0.00 | 23.07 |
Maximum of Months | 0.966928E+10 | 36816334.17 | 0.00 | 0.129100E+09 | 0.00 | 0.210308E+10 | 0.157363E+12 | 0.00 | 24.15 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.591012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202430E+11 | 0.00 | 0.00 | 5.04 |
February | 0.665830E+11 | 0.00 | 0.00 | 23973.87 | 0.00 | 0.226980E+10 | 0.244397E+09 | 0.00 | 4.98 |
March | 0.491895E+11 | 0.00 | 0.00 | 3579009.40 | 0.00 | 5363163.76 | 0.736157E+10 | 0.00 | 5.00 |
April | 0.189659E+11 | 0.00 | 0.00 | 14082269.08 | 0.00 | 0.00 | 0.223669E+11 | 0.00 | 5.11 |
May | 0.144983E+11 | 0.00 | 0.00 | 16685869.81 | 0.00 | 0.00 | 0.246900E+11 | 0.00 | 5.07 |
June | 0.959451E+10 | 4921544.88 | 0.00 | 21486286.02 | 69827.78 | 0.00 | 0.215637E+11 | 0.00 | 5.06 |
July | 0.967110E+10 | 19395882.06 | 0.00 | 21792343.20 | 908365.90 | 0.00 | 0.205115E+11 | 0.00 | 5.10 |
August | 0.129083E+11 | 0.00 | 0.00 | 21637897.54 | 0.00 | 0.00 | 0.234388E+11 | 0.00 | 5.09 |
September | 0.221239E+11 | 0.00 | 0.00 | 7716235.41 | 0.00 | 0.00 | 0.171699E+11 | 0.00 | 5.05 |
October | 0.394996E+11 | 0.00 | 0.00 | 1492554.75 | 0.00 | 83745153.53 | 0.427659E+10 | 0.00 | 5.02 |
November | 0.651596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106865E+11 | 0.00 | 0.00 | 5.01 |
December | 0.607466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263821E+11 | 0.00 | 0.00 | 5.01 |
Annual Sum or Average | 0.428041E+12 | 24317426.94 | 0.00 | 0.108496E+09 | 978193.68 | 0.596705E+11 | 0.141623E+12 | 0.00 | 5.05 |
Minimum of Months | 0.959451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.98 |
Maximum of Months | 0.665830E+11 | 19395882.06 | 0.00 | 21792343.20 | 908365.90 | 0.263821E+11 | 0.246900E+11 | 0.00 | 5.11 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.193914E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182284E+11 | 0.00 | 0.00 | 1.95 |
February | 0.183669E+12 | 0.00 | 0.00 | 8155.72 | 0.00 | 0.913959E+09 | 0.162212E+09 | 0.00 | 1.93 |
March | 0.143640E+12 | 0.00 | 0.00 | 1296149.56 | 0.00 | 0.00 | 0.741798E+10 | 0.00 | 1.93 |
April | 0.656007E+11 | 0.00 | 0.00 | 25591060.65 | 0.00 | 0.00 | 0.438977E+11 | 0.00 | 1.95 |
May | 0.443291E+11 | 0.00 | 0.00 | 53543755.39 | 0.00 | 0.00 | 0.608845E+11 | 0.00 | 1.96 |
June | 0.231587E+11 | 10101288.83 | 0.00 | 84174949.99 | 3191092.33 | 0.00 | 0.618196E+11 | 0.00 | 2.00 |
July | 0.203854E+11 | 47003447.14 | 0.00 | 86830681.25 | 5390378.48 | 0.00 | 0.620684E+11 | 0.00 | 2.01 |
August | 0.304793E+11 | 0.00 | 0.00 | 78625211.44 | 0.00 | 0.00 | 0.678720E+11 | 0.00 | 1.98 |
September | 0.567633E+11 | 0.00 | 0.00 | 25385636.03 | 0.00 | 0.00 | 0.481201E+11 | 0.00 | 1.95 |
October | 0.104679E+12 | 0.00 | 0.00 | 3993121.10 | 0.00 | 0.00 | 0.125603E+11 | 0.00 | 1.94 |
November | 0.202789E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 |
December | 0.228361E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459439E+10 | 0.00 | 0.00 | 1.94 |
Annual Sum or Average | 0.129777E+13 | 57104735.96 | 0.00 | 0.359449E+09 | 8581470.81 | 0.237367E+11 | 0.364803E+12 | 0.00 | 1.96 |
Minimum of Months | 0.203854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.93 |
Maximum of Months | 0.228361E+12 | 47003447.14 | 0.00 | 86830681.25 | 5390378.48 | 0.182284E+11 | 0.678720E+11 | 0.00 | 2.01 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 41124.34 | 0.00 | 0.342858E+10 | 1782194.73 | 0.00 | 0.36 |
February | 29163832.26 | 0.00 | 0.00 | 141451.23 | 0.00 | 0.306902E+10 | 4543514.03 | 0.00 | 0.35 |
March | 89269821.70 | 0.00 | 0.00 | 1231696.85 | 0.00 | 0.223836E+10 | 0.114710E+09 | 0.00 | 0.36 |
April | 46135459.49 | 0.00 | 0.00 | 8365964.55 | 0.00 | 0.662277E+09 | 0.911365E+09 | 0.00 | 0.36 |
May | 13869387.92 | 0.00 | 0.00 | 15798534.09 | 0.00 | 41681204.82 | 0.145684E+10 | 0.00 | 0.36 |
June | 2832445.21 | 1253612.77 | 0.00 | 22230168.40 | 0.00 | 2584775.74 | 0.111632E+10 | 0.00 | 0.36 |
July | 4370856.91 | 4796578.54 | 0.00 | 20463037.88 | 0.00 | 2641913.69 | 0.962672E+09 | 0.00 | 0.36 |
August | 12969537.51 | 0.00 | 0.00 | 16387367.92 | 0.00 | 13262670.06 | 0.117272E+10 | 0.00 | 0.35 |
September | 59087954.44 | 0.00 | 0.00 | 5164894.91 | 0.00 | 0.536062E+09 | 0.903793E+09 | 0.00 | 0.36 |
October | 65393688.76 | 0.00 | 0.00 | 546126.00 | 0.00 | 0.157622E+10 | 0.105699E+09 | 0.00 | 0.36 |
November | 3200088.67 | 0.00 | 0.00 | 43589.84 | 0.00 | 0.326107E+10 | 2164236.08 | 0.00 | 0.36 |
December | 0.00 | 0.00 | 0.00 | 24103.73 | 0.00 | 0.377586E+10 | 715490.27 | 0.00 | 0.36 |
Annual Sum or Average | 0.326293E+09 | 6050191.31 | 0.00 | 90438059.74 | 0.00 | 0.186076E+11 | 0.675333E+10 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 24103.73 | 0.00 | 2584775.74 | 715490.27 | 0.00 | 0.35 |
Maximum of Months | 89269821.70 | 4796578.54 | 0.00 | 22230168.40 | 0.00 | 0.377586E+10 | 0.145684E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 29098.03 | 0.00 | 0.342868E+10 | 1289825.48 | 0.00 | 0.36 |
February | 1306258.04 | 0.00 | 0.00 | 90010.27 | 0.00 | 0.309879E+10 | 2323271.95 | 0.00 | 0.35 |
March | 23148206.09 | 0.00 | 0.00 | 308450.68 | 0.00 | 0.237307E+10 | 46757077.81 | 0.00 | 0.36 |
April | 87486679.88 | 0.00 | 0.00 | 5237104.88 | 0.00 | 0.861536E+09 | 0.673692E+09 | 0.00 | 0.36 |
May | 0.204690E+09 | 0.00 | 0.00 | 12290711.41 | 0.00 | 59219641.65 | 0.125181E+10 | 0.00 | 0.36 |
June | 0.231093E+09 | 1114883.25 | 306.56 | 18759648.88 | 137871.11 | 1088407.70 | 0.892896E+09 | 404.98 | 0.36 |
July | 0.198480E+09 | 4231798.68 | 0.00 | 16580209.72 | 564217.87 | 1748875.40 | 0.773223E+09 | 0.00 | 0.36 |
August | 0.229824E+09 | 0.00 | 0.00 | 11246307.29 | 0.00 | 28114319.80 | 0.946016E+09 | 0.00 | 0.36 |
September | 0.121972E+09 | 0.00 | 0.00 | 2790785.30 | 0.00 | 0.695869E+09 | 0.683299E+09 | 0.00 | 0.36 |
October | 38067130.69 | 0.00 | 0.00 | 237588.22 | 0.00 | 0.168194E+10 | 27409808.60 | 0.00 | 0.36 |
November | 0.00 | 0.00 | 0.00 | 18366.68 | 0.00 | 0.326492E+10 | 1160410.24 | 0.00 | 0.36 |
December | 0.00 | 0.00 | 0.00 | 18803.01 | 0.00 | 0.377547E+10 | 663663.72 | 0.00 | 0.36 |
Annual Sum or Average | 0.113607E+10 | 5346681.93 | 306.56 | 67607084.37 | 702088.98 | 0.192704E+11 | 0.530054E+10 | 404.98 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 18366.68 | 0.00 | 1088407.70 | 663663.72 | 0.00 | 0.35 |
Maximum of Months | 0.231093E+09 | 4231798.68 | 306.56 | 18759648.88 | 564217.87 | 0.377547E+10 | 0.125181E+10 | 404.98 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.160238E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160528E+10 | 0.00 | 0.00 | 0.02 |
February | 0.880160E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337691E+09 | 0.00 | 0.00 | 0.02 |
March | 0.966252E+09 | 0.00 | 0.00 | 1226150.10 | 0.00 | 0.00 | 0.458521E+09 | 0.00 | 0.02 |
April | 90828918.28 | 0.00 | 0.00 | 6654669.67 | 0.00 | 0.00 | 0.165659E+10 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.00 | 6233072.23 | 0.00 | 0.00 | 0.175628E+10 | 0.00 | 0.02 |
June | 15671953.41 | 1909380.08 | 0.00 | 6077583.89 | 0.00 | 0.00 | 0.123195E+10 | 0.00 | 0.02 |
July | 0.00 | 7691744.39 | 0.00 | 6081020.28 | 0.00 | 0.00 | 0.819056E+09 | 0.00 | 0.02 |
August | 0.00 | 0.00 | 0.00 | 6567867.29 | 0.00 | 0.00 | 0.120257E+10 | 0.00 | 0.02 |
September | 0.397216E+09 | 0.00 | 0.00 | 3601832.17 | 0.00 | 0.00 | 0.130520E+10 | 0.00 | 0.02 |
October | 0.994988E+09 | 0.00 | 0.00 | 919381.22 | 0.00 | 0.00 | 0.497373E+09 | 0.00 | 0.02 |
November | 0.418463E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122724E+10 | 0.00 | 0.00 | 0.02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211008E+10 | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.392382E+10 | 9601124.47 | 0.00 | 37361576.86 | 0.00 | 0.528030E+10 | 0.892754E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.994988E+09 | 7691744.39 | 0.00 | 6654669.67 | 0.00 | 0.211008E+10 | 0.175628E+10 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.856117E+09 | 0.00 | 0.00 | 919474.28 | 0.00 | 0.454802E+11 | 0.188634E+09 | 0.00 | 0.41 |
February | 0.100845E+10 | 0.00 | 0.00 | 1281298.14 | 0.00 | 0.402560E+11 | 0.817985E+09 | 0.00 | 0.40 |
March | 0.124223E+10 | 0.00 | 0.00 | 4922873.46 | 0.00 | 0.276227E+11 | 0.427186E+10 | 0.00 | 0.40 |
April | 0.127394E+10 | 0.00 | 0.00 | 45878520.09 | 0.00 | 0.496348E+10 | 0.157989E+11 | 0.00 | 0.41 |
May | 0.312473E+10 | 0.00 | 0.00 | 0.145220E+09 | 0.00 | 23975020.66 | 0.174326E+11 | 0.00 | 0.40 |
June | 0.379322E+10 | 15132374.03 | 0.00 | 0.218198E+09 | 1870138.85 | 2876183.06 | 0.115012E+11 | 0.00 | 0.41 |
July | 0.306333E+10 | 57089203.89 | 0.00 | 0.218230E+09 | 7965883.48 | 2070648.11 | 0.101456E+11 | 0.00 | 0.41 |
August | 0.340896E+10 | 0.00 | 0.00 | 0.152012E+09 | 0.00 | 11607265.79 | 0.129109E+11 | 0.00 | 0.40 |
September | 0.165448E+10 | 0.00 | 0.00 | 60988991.79 | 0.00 | 0.614815E+09 | 0.180696E+11 | 0.00 | 0.41 |
October | 0.122965E+10 | 0.00 | 0.00 | 13991450.93 | 0.00 | 0.131618E+11 | 0.930048E+10 | 0.00 | 0.41 |
November | 0.111064E+10 | 0.00 | 0.00 | 896941.39 | 0.00 | 0.430718E+11 | 0.119379E+09 | 0.00 | 0.40 |
December | 0.494236E+09 | 0.00 | 0.00 | 721652.78 | 0.00 | 0.505597E+11 | 0.166632E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.222600E+11 | 72221577.92 | 0.00 | 0.863261E+09 | 9836022.33 | 0.225771E+12 | 0.100724E+12 | 0.00 | 0.40 |
Minimum of Months | 0.494236E+09 | 0.00 | 0.00 | 721652.78 | 0.00 | 2070648.11 | 0.119379E+09 | 0.00 | 0.40 |
Maximum of Months | 0.379322E+10 | 57089203.89 | 0.00 | 0.218230E+09 | 7965883.48 | 0.505597E+11 | 0.180696E+11 | 0.00 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1133454.42 | 0.00 | 0.00 | 38308.54 | 0.00 | 0.342761E+10 | 1614506.35 | 0.00 | 0.36 |
February | 35115073.29 | 0.00 | 0.00 | 178130.71 | 0.00 | 0.305092E+10 | 16663353.38 | 0.00 | 0.35 |
March | 74767720.88 | 0.00 | 0.00 | 1638400.29 | 0.00 | 0.210228E+10 | 0.264880E+09 | 0.00 | 0.36 |
April | 22862100.93 | 0.00 | 0.00 | 7756980.36 | 0.00 | 0.638025E+09 | 0.959499E+09 | 0.00 | 0.36 |
May | 3412163.15 | 0.00 | 0.00 | 19574821.52 | 0.00 | 27661924.72 | 0.147754E+10 | 0.00 | 0.36 |
June | 2832445.21 | 1253612.77 | 0.00 | 24201768.82 | 0.00 | 1079275.89 | 0.111586E+10 | 0.00 | 0.36 |
July | 2973105.15 | 4796578.54 | 0.00 | 25357919.10 | 0.00 | 1183068.45 | 0.960634E+09 | 0.00 | 0.36 |
August | 5042317.33 | 0.00 | 0.00 | 18205010.28 | 0.00 | 8821969.98 | 0.118327E+10 | 0.00 | 0.35 |
September | 40456383.98 | 0.00 | 0.00 | 6205728.38 | 0.00 | 0.448358E+09 | 0.100909E+10 | 0.00 | 0.36 |
October | 69866276.18 | 0.00 | 0.00 | 858392.67 | 0.00 | 0.148252E+10 | 0.194613E+09 | 0.00 | 0.36 |
November | 3200088.67 | 0.00 | 0.00 | 33935.36 | 0.00 | 0.326154E+10 | 1710854.13 | 0.00 | 0.36 |
December | 0.00 | 0.00 | 0.00 | 21228.21 | 0.00 | 0.377586E+10 | 718365.80 | 0.00 | 0.36 |
Annual Sum or Average | 0.261661E+09 | 6050191.31 | 0.00 | 0.104071E+09 | 0.00 | 0.182259E+11 | 0.718609E+10 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21228.21 | 0.00 | 1079275.89 | 718365.80 | 0.00 | 0.35 |
Maximum of Months | 74767720.88 | 4796578.54 | 0.00 | 25357919.10 | 0.00 | 0.377586E+10 | 0.147754E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 25506.02 | 0.00 | 0.342885E+10 | 1126769.93 | 0.00 | 0.36 |
February | 2653282.37 | 0.00 | 0.00 | 96375.79 | 0.00 | 0.309585E+10 | 3907827.30 | 0.00 | 0.35 |
March | 75249326.76 | 0.00 | 0.00 | 572162.60 | 0.00 | 0.225850E+10 | 0.108964E+09 | 0.00 | 0.36 |
April | 67437560.33 | 0.00 | 0.00 | 4561646.84 | 0.00 | 0.846695E+09 | 0.709259E+09 | 0.00 | 0.36 |
May | 0.140060E+09 | 0.00 | 0.00 | 16347193.66 | 0.00 | 32477327.93 | 0.133913E+10 | 0.00 | 0.36 |
June | 0.232938E+09 | 1115594.79 | 0.00 | 21489156.97 | 137871.11 | 709050.27 | 0.888701E+09 | 0.00 | 0.36 |
July | 0.192473E+09 | 4231798.68 | 0.00 | 21038160.19 | 564217.87 | 1028580.67 | 0.775492E+09 | 0.00 | 0.36 |
August | 0.199370E+09 | 0.00 | 0.00 | 13647565.02 | 0.00 | 20752936.29 | 0.981430E+09 | 0.00 | 0.36 |
September | 0.108895E+09 | 0.00 | 0.00 | 3844418.92 | 0.00 | 0.629007E+09 | 0.762184E+09 | 0.00 | 0.36 |
October | 54457971.38 | 0.00 | 0.00 | 358374.56 | 0.00 | 0.157480E+10 | 0.118043E+09 | 0.00 | 0.36 |
November | 0.00 | 0.00 | 0.00 | 13946.50 | 0.00 | 0.326518E+10 | 906848.08 | 0.00 | 0.36 |
December | 0.00 | 0.00 | 0.00 | 16949.18 | 0.00 | 0.377547E+10 | 665517.54 | 0.00 | 0.36 |
Annual Sum or Average | 0.107353E+10 | 5347393.47 | 0.00 | 82011456.26 | 702088.98 | 0.189293E+11 | 0.568980E+10 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 13946.50 | 0.00 | 709050.27 | 665517.54 | 0.00 | 0.35 |
Maximum of Months | 0.232938E+09 | 4231798.68 | 0.00 | 21489156.97 | 564217.87 | 0.377547E+10 | 0.133913E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.415295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521793E+11 | 0.00 | 0.00 | 0.56 |
February | 0.125214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365358E+11 | 0.00 | 0.00 | 0.56 |
March | 0.315577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.855462E+10 | 0.00 | 0.00 | 0.56 |
April | 0.286977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319590E+09 | 0.00 | 0.00 | 0.56 |
May | 0.277067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
June | 0.217956E+11 | 0.00 | 0.00 | 191526.45 | 3529655.63 | 0.00 | 0.316318E+09 | 0.00 | 0.57 |
July | 0.210004E+11 | 0.00 | 0.00 | 320843.19 | 13912643.60 | 0.00 | 0.421491E+09 | 0.00 | 0.57 |
August | 0.256491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.278182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
October | 0.249433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.618947E+10 | 0.00 | 0.00 | 0.56 |
November | 0.531283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485358E+11 | 0.00 | 0.00 | 0.56 |
December | 0.139468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604643E+11 | 0.00 | 0.00 | 0.56 |
Annual Sum or Average | 0.232550E+12 | 0.00 | 0.00 | 512369.64 | 17442299.23 | 0.212779E+12 | 0.737809E+09 | 0.00 | 0.56 |
Minimum of Months | 0.139468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.315577E+11 | 0.00 | 0.00 | 320843.19 | 13912643.60 | 0.604643E+11 | 0.421491E+09 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 2995.09 | 0.00 | 0.857270E+09 | 326774.43 | 0.00 | 0.36 |
February | 1543613.03 | 0.00 | 0.00 | 17753.41 | 0.00 | 0.773224E+09 | 932820.72 | 0.00 | 0.35 |
March | 16148983.79 | 0.00 | 0.00 | 224253.85 | 0.00 | 0.574716E+09 | 19802969.59 | 0.00 | 0.36 |
April | 13198079.65 | 0.00 | 0.00 | 1966752.97 | 0.00 | 0.216529E+09 | 0.175342E+09 | 0.00 | 0.36 |
May | 3716463.08 | 0.00 | 0.00 | 3692555.26 | 0.00 | 41189029.12 | 0.333449E+09 | 0.00 | 0.36 |
June | 1178363.99 | 313403.19 | 0.00 | 5417992.01 | 0.00 | 659524.65 | 0.278737E+09 | 0.00 | 0.36 |
July | 2023121.23 | 1199144.63 | 0.00 | 4940271.31 | 0.00 | 1003668.74 | 0.239570E+09 | 0.00 | 0.36 |
August | 3365638.76 | 0.00 | 0.00 | 3865991.29 | 0.00 | 19069168.11 | 0.277535E+09 | 0.00 | 0.35 |
September | 15836229.05 | 0.00 | 0.00 | 1093008.57 | 0.00 | 0.206663E+09 | 0.152435E+09 | 0.00 | 0.36 |
October | 11418440.38 | 0.00 | 0.00 | 97858.20 | 0.00 | 0.412647E+09 | 12801731.64 | 0.00 | 0.36 |
November | 0.00 | 0.00 | 0.00 | 3235.25 | 0.00 | 0.816283E+09 | 334893.03 | 0.00 | 0.36 |
December | 0.00 | 0.00 | 0.00 | 2384.28 | 0.00 | 0.943979E+09 | 168252.39 | 0.00 | 0.36 |
Annual Sum or Average | 68428932.97 | 1512547.83 | 0.00 | 21325051.49 | 0.00 | 0.486323E+10 | 0.149144E+10 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2384.28 | 0.00 | 659524.65 | 168252.39 | 0.00 | 0.35 |
Maximum of Months | 16148983.79 | 1199144.63 | 0.00 | 5417992.01 | 0.00 | 0.943979E+09 | 0.333449E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3123.57 | 0.00 | 0.857190E+09 | 306417.18 | 0.00 | 0.36 |
February | 0.00 | 0.00 | 0.00 | 11896.93 | 0.00 | 0.774983E+09 | 632848.60 | 0.00 | 0.35 |
March | 3976937.05 | 0.00 | 0.00 | 46602.29 | 0.00 | 0.599749E+09 | 7048234.36 | 0.00 | 0.36 |
April | 19114464.64 | 0.00 | 0.00 | 1161145.07 | 0.00 | 0.266375E+09 | 0.120337E+09 | 0.00 | 0.36 |
May | 48482443.30 | 0.00 | 0.00 | 2901102.89 | 0.00 | 50745519.83 | 0.279874E+09 | 0.00 | 0.36 |
June | 56936179.35 | 278898.70 | 0.00 | 4869996.37 | 34467.78 | 436883.67 | 0.223716E+09 | 0.00 | 0.36 |
July | 49114992.92 | 1057949.67 | 0.00 | 4165154.18 | 141054.47 | 493765.94 | 0.193734E+09 | 0.00 | 0.36 |
August | 56391672.63 | 0.00 | 0.00 | 2661609.41 | 0.00 | 23756859.43 | 0.220990E+09 | 0.00 | 0.36 |
September | 28654298.16 | 0.00 | 0.00 | 525969.62 | 0.00 | 0.258435E+09 | 88367522.45 | 0.00 | 0.36 |
October | 5680775.02 | 0.00 | 0.00 | 52210.71 | 0.00 | 0.427210E+09 | 3970585.67 | 0.00 | 0.36 |
November | 0.00 | 0.00 | 0.00 | 1945.61 | 0.00 | 0.816164E+09 | 358675.77 | 0.00 | 0.36 |
December | 0.00 | 0.00 | 0.00 | 2380.47 | 0.00 | 0.943868E+09 | 168236.21 | 0.00 | 0.36 |
Annual Sum or Average | 0.268352E+09 | 1336848.37 | 0.00 | 16403137.11 | 175522.24 | 0.501941E+10 | 0.113950E+10 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1945.61 | 0.00 | 436883.67 | 168236.21 | 0.00 | 0.35 |
Maximum of Months | 56936179.35 | 1057949.67 | 0.00 | 4869996.37 | 141054.47 | 0.943868E+09 | 0.279874E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 58147475.65 | 0.00 | 0.00 | 124515.18 | 0.00 | 0.544347E+10 | 7899726.59 | 0.00 | 0.41 |
February | 0.114691E+09 | 0.00 | 0.00 | 993202.61 | 0.00 | 0.473937E+10 | 0.128540E+09 | 0.00 | 0.40 |
March | 53447141.53 | 0.00 | 0.00 | 5608952.24 | 0.00 | 0.317357E+10 | 0.692047E+09 | 0.00 | 0.40 |
April | 12743231.92 | 0.00 | 0.00 | 15687797.95 | 0.00 | 0.712843E+09 | 0.187372E+10 | 0.00 | 0.41 |
May | 8868775.09 | 0.00 | 0.00 | 23888914.47 | 0.00 | 56664283.10 | 0.236504E+10 | 0.00 | 0.41 |
June | 6048069.37 | 2013455.47 | 0.00 | 29436167.43 | 0.00 | 4161599.28 | 0.179771E+10 | 0.00 | 0.40 |
July | 7020130.91 | 7703891.92 | 0.00 | 29420818.76 | 0.00 | 4016254.59 | 0.154984E+10 | 0.00 | 0.41 |
August | 15504893.77 | 0.00 | 0.00 | 26170751.34 | 0.00 | 12949384.22 | 0.189736E+10 | 0.00 | 0.40 |
September | 45428221.32 | 0.00 | 0.00 | 12516887.02 | 0.00 | 0.451264E+09 | 0.190657E+10 | 0.00 | 0.41 |
October | 93737611.17 | 0.00 | 0.00 | 3309256.66 | 0.00 | 0.203904E+10 | 0.671192E+09 | 0.00 | 0.41 |
November | 70887699.65 | 0.00 | 0.00 | 226749.86 | 0.00 | 0.515843E+10 | 16825404.31 | 0.00 | 0.40 |
December | 0.00 | 0.00 | 0.00 | 52547.64 | 0.00 | 0.606219E+10 | 3430218.93 | 0.00 | 0.41 |
Annual Sum or Average | 0.486524E+09 | 9717347.40 | 0.00 | 0.147437E+09 | 0.00 | 0.278580E+11 | 0.129102E+11 | 0.00 | 0.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 52547.64 | 0.00 | 4016254.59 | 3430218.93 | 0.00 | 0.40 |
Maximum of Months | 0.114691E+09 | 7703891.92 | 0.00 | 29436167.43 | 0.00 | 0.606219E+10 | 0.236504E+10 | 0.00 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.478151E+11 | 0.00 | 0.00 | 20716103.24 | 0.00 | 0.336279E+09 | 0.377800E+11 | 0.00 | 4.08 |
February | 0.407288E+11 | 0.00 | 0.00 | 20749312.47 | 0.00 | 0.00 | 0.344759E+11 | 0.00 | 4.07 |
March | 0.193930E+11 | 0.00 | 0.00 | 34287165.91 | 0.00 | 0.00 | 0.437384E+11 | 0.00 | 4.19 |
April | 0.334888E+10 | 0.00 | 0.00 | 56261035.46 | 0.00 | 0.00 | 0.459380E+11 | 0.00 | 4.55 |
May | 0.287355E+09 | 0.00 | 0.00 | 86766675.69 | 0.00 | 0.00 | 0.521204E+11 | 0.00 | 4.97 |
June | 15575864.62 | 5376670.39 | 0.00 | 0.106751E+09 | 0.00 | 0.00 | 0.454513E+11 | 0.00 | 5.34 |
July | 20642435.14 | 24817866.29 | 0.00 | 0.111032E+09 | 0.00 | 0.00 | 0.442871E+11 | 0.00 | 5.32 |
August | 0.302400E+09 | 0.00 | 0.00 | 91714133.15 | 0.00 | 0.00 | 0.497162E+11 | 0.00 | 5.06 |
September | 0.123721E+10 | 0.00 | 0.00 | 61411619.13 | 0.00 | 0.00 | 0.479047E+11 | 0.00 | 4.67 |
October | 0.873270E+10 | 0.00 | 0.00 | 43756936.87 | 0.00 | 0.00 | 0.420043E+11 | 0.00 | 4.35 |
November | 0.454014E+11 | 0.00 | 0.00 | 20081768.62 | 0.00 | 0.00 | 0.367897E+11 | 0.00 | 4.06 |
December | 0.547431E+11 | 0.00 | 0.00 | 16019689.10 | 0.00 | 0.00 | 0.391718E+11 | 0.00 | 4.03 |
Annual Sum or Average | 0.222026E+12 | 30194536.68 | 0.00 | 0.669548E+09 | 0.00 | 0.336279E+09 | 0.519378E+12 | 0.00 | 4.56 |
Minimum of Months | 15575864.62 | 0.00 | 0.00 | 16019689.10 | 0.00 | 0.00 | 0.344759E+11 | 0.00 | 4.03 |
Maximum of Months | 0.547431E+11 | 24817866.29 | 0.00 | 0.111032E+09 | 0.00 | 0.336279E+09 | 0.521204E+11 | 0.00 | 5.34 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.437455E+11 | 0.00 | 0.00 | 29478492.33 | 0.00 | 0.216427E+09 | 0.472165E+11 | 0.00 | 4.36 |
February | 0.346423E+11 | 0.00 | 0.00 | 29189675.62 | 0.00 | 0.00 | 0.453839E+11 | 0.00 | 4.37 |
March | 0.131660E+11 | 0.00 | 0.00 | 47379679.08 | 0.00 | 0.00 | 0.549847E+11 | 0.00 | 4.55 |
April | 0.103537E+10 | 0.00 | 0.00 | 70947499.58 | 0.00 | 0.00 | 0.528406E+11 | 0.00 | 4.97 |
May | 32775061.27 | 0.00 | 0.00 | 0.100795E+09 | 0.00 | 0.00 | 0.570135E+11 | 0.00 | 5.41 |
June | 0.00 | 5801561.14 | 0.00 | 0.118056E+09 | 0.00 | 0.00 | 0.488284E+11 | 0.00 | 5.75 |
July | 0.00 | 26954794.96 | 0.00 | 0.122987E+09 | 0.00 | 0.00 | 0.475383E+11 | 0.00 | 5.72 |
August | 58360641.41 | 0.00 | 0.00 | 0.104297E+09 | 0.00 | 0.00 | 0.539747E+11 | 0.00 | 5.47 |
September | 0.221208E+09 | 0.00 | 0.00 | 75900303.72 | 0.00 | 0.00 | 0.537463E+11 | 0.00 | 5.13 |
October | 0.437228E+10 | 0.00 | 0.00 | 58479999.82 | 0.00 | 0.00 | 0.511190E+11 | 0.00 | 4.77 |
November | 0.405657E+11 | 0.00 | 0.00 | 28700941.58 | 0.00 | 0.00 | 0.467346E+11 | 0.00 | 4.34 |
December | 0.475656E+11 | 0.00 | 0.00 | 23645749.43 | 0.00 | 0.00 | 0.516191E+11 | 0.00 | 4.28 |
Annual Sum or Average | 0.185405E+12 | 32756356.10 | 0.00 | 0.809858E+09 | 0.00 | 0.216427E+09 | 0.611000E+12 | 0.00 | 4.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23645749.43 | 0.00 | 0.00 | 0.453839E+11 | 0.00 | 4.28 |
Maximum of Months | 0.475656E+11 | 26954794.96 | 0.00 | 0.122987E+09 | 0.00 | 0.216427E+09 | 0.570135E+11 | 0.00 | 5.75 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.447735E+10 | 0.00 | 0.00 | 93661631.51 | 0.00 | 0.130281E+09 | 0.110332E+12 | 0.00 | 18.69 |
February | 0.222028E+10 | 0.00 | 0.00 | 90861816.28 | 0.00 | 0.00 | 0.993242E+11 | 0.00 | 18.99 |
March | 0.385425E+09 | 0.00 | 0.00 | 0.108849E+09 | 0.00 | 0.00 | 0.924103E+11 | 0.00 | 20.69 |
April | 0.00 | 0.00 | 0.00 | 0.115868E+09 | 0.00 | 0.00 | 0.741716E+11 | 0.00 | 21.84 |
May | 0.00 | 0.00 | 0.00 | 0.142661E+09 | 0.00 | 0.00 | 0.721335E+11 | 0.00 | 22.60 |
June | 0.00 | 10950497.29 | 0.00 | 0.154675E+09 | 0.00 | 0.00 | 0.554738E+11 | 0.00 | 22.87 |
July | 0.00 | 43149736.62 | 0.00 | 0.163359E+09 | 0.00 | 0.00 | 0.521966E+11 | 0.00 | 22.91 |
August | 0.00 | 0.00 | 0.00 | 0.143824E+09 | 0.00 | 0.00 | 0.641116E+11 | 0.00 | 22.46 |
September | 0.00 | 0.00 | 0.00 | 0.112762E+09 | 0.00 | 0.00 | 0.708751E+11 | 0.00 | 21.91 |
October | 0.00 | 0.00 | 0.00 | 0.107677E+09 | 0.00 | 0.00 | 0.761760E+11 | 0.00 | 20.93 |
November | 0.946963E+09 | 0.00 | 0.00 | 93417171.67 | 0.00 | 0.00 | 0.109498E+12 | 0.00 | 18.62 |
December | 0.147979E+10 | 0.00 | 0.00 | 91955825.46 | 0.00 | 0.00 | 0.121145E+12 | 0.00 | 18.04 |
Annual Sum or Average | 0.950980E+10 | 54100233.91 | 0.00 | 0.141957E+10 | 0.00 | 0.130281E+09 | 0.997848E+12 | 0.00 | 20.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 90861816.28 | 0.00 | 0.00 | 0.521966E+11 | 0.00 | 18.04 |
Maximum of Months | 0.447735E+10 | 43149736.62 | 0.00 | 0.163359E+09 | 0.00 | 0.130281E+09 | 0.121145E+12 | 0.00 | 22.91 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 97874945.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305940E+11 | 0.00 | 0.00 | 1.16 |
February | 0.258089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241473E+11 | 0.00 | 0.00 | 1.15 |
March | 0.109511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109035E+11 | 0.00 | 0.00 | 1.15 |
April | 0.147654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104435E+10 | 0.00 | 0.00 | 1.16 |
May | 0.150187E+11 | 0.00 | 0.00 | 60018.24 | 0.00 | 0.00 | 76872938.77 | 0.00 | 1.16 |
June | 0.109868E+11 | 1890701.34 | 0.00 | 2428183.63 | 49789.76 | 0.00 | 0.106109E+10 | 0.00 | 1.16 |
July | 0.107308E+11 | 7173042.30 | 0.00 | 2713508.44 | 501562.91 | 0.00 | 0.944033E+09 | 0.00 | 1.17 |
August | 0.135945E+11 | 0.00 | 0.00 | 691364.51 | 0.00 | 0.00 | 0.379391E+09 | 0.00 | 1.15 |
September | 0.151564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 |
October | 0.112914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567084E+10 | 0.00 | 0.00 | 1.15 |
November | 0.184955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291538E+11 | 0.00 | 0.00 | 1.15 |
December | 98879752.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336042E+11 | 0.00 | 0.00 | 1.15 |
Annual Sum or Average | 0.105458E+12 | 9063743.64 | 0.00 | 5893074.82 | 551352.67 | 0.135118E+12 | 0.246138E+10 | 0.00 | 1.16 |
Minimum of Months | 97874945.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 |
Maximum of Months | 0.151564E+11 | 7173042.30 | 0.00 | 2713508.44 | 501562.91 | 0.336042E+11 | 0.106109E+10 | 0.00 | 1.17 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:02:45
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | -0.362493E+11 | 0.902590E+10 | 0.419852E+12 | 0.172910E+13 | 0.201986E+12 |
February | 0.208529E+11 | 0.779002E+10 | 0.355315E+12 | 0.149377E+13 | 0.172046E+12 |
March | 0.187560E+12 | 0.761464E+10 | 0.346092E+12 | 0.152476E+13 | 0.146866E+12 |
April | 0.366875E+12 | 0.512324E+10 | 0.232114E+12 | 0.109482E+13 | 0.144733E+12 |
May | 0.491482E+12 | 0.342831E+10 | 0.138765E+12 | 0.694713E+12 | 0.234070E+12 |
June | 0.510632E+12 | 0.245340E+10 | 0.879920E+11 | 0.429080E+12 | 0.401144E+12 |
July | 0.454629E+12 | 0.205956E+10 | 0.817568E+11 | 0.402083E+12 | 0.456538E+12 |
August | 0.333671E+12 | 0.267593E+10 | 0.107955E+12 | 0.517421E+12 | 0.332548E+12 |
September | 0.142894E+12 | 0.384538E+10 | 0.181046E+12 | 0.838466E+12 | 0.116582E+12 |
October | 0.490607E+11 | 0.604268E+10 | 0.289065E+12 | 0.126772E+13 | 0.103558E+12 |
November | -0.127786E+11 | 0.880095E+10 | 0.405161E+12 | 0.168791E+13 | 0.192445E+12 |
December | -0.489366E+11 | 0.937791E+10 | 0.431426E+12 | 0.176893E+13 | 0.222574E+12 |
Annual Sum or Average | 0.245969E+13 | 0.682379E+11 | 0.307654E+13 | 0.134488E+14 | 0.272509E+13 |
Minimum of Months | -0.489366E+11 | 0.205956E+10 | 0.817568E+11 | 0.402083E+12 | 0.103558E+12 |