Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2023-10-16 09:02:46
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10209.82 | 899.92 | 899.92 |
Net Site Energy | 10209.82 | 899.92 | 899.92 |
Total Source Energy | 21474.12 | 1892.78 | 1892.78 |
Net Source Energy | 21474.12 | 1892.78 | 1892.78 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1944.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 537.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 602.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 174.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 641.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 532.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 87.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 179.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 469.03 | 1480.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 43.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4996.00 | 5213.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1944.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 537.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 602.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 174.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 952.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 22.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 532.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 87.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 179.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.75 | 1480.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Other | 378.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 20.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1944.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 537.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 602.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 174.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 641.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 532.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 87.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 179.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 469.03 | 1480.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 43.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 143.38 | 301.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 228.52 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 440.36 | 459.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 143.38 | 301.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 228.52 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 440.36 | 459.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 4996.002 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 4996.002 | 100.00 |
Total On-Site and Utility Electric Sources | 4996.002 | 100.00 |
Total Electricity End Uses | 4996.002 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 42.14 | 1.04 |
Air to Air Heat Recovery for Heating | 4027.63 | 98.96 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 4069.76 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 20.00 |
Time Setpoint Not Met During Occupied Cooling | 56.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7519.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYSLAUNDRY HPWH TANK | SWHSYS1 HPWH TANK |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| SWHSYS1 HPWH FAN | SWHSYSLAUNDRY HPWH FAN | FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 6.6442 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 9.6995 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 9.6995 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.6285 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 4.0903 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.7049 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 9.2569 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 9.0417 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 4.4132 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 4.4132 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 9.2569 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 11.7327 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 4.4132 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8432 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.8432 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.6442 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 9.6995 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.6285 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 4.0903 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.7049 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 9.2569 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 9.0417 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 4.4132 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 4.4132 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 4.4132 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 4.4132 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 4.4132 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 9.2569 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 11.7327 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 4.4132 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.8432 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.8432 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.6992 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-18:19 | 10-JAN-22:49 | - | - | - | - | - | - | - | - | - | - | 02-MAY-20:49 |
Heating | 0.00 | 893897.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 160159.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 40498.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 78653.57 | 54264.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31364.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 34999.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6015.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 35459.73 | 192816.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1675.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 398764.63 | 1140978.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 893897.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 160159.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 40498.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 48978.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 24992.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1060.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 34999.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 6015.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4578.54 | 192816.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 228.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 789.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 657.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2108.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1702.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1908.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 551.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5473.02 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2031.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1687.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 276.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 568.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1485.42 | 1604.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 137.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 15822.34 | 5651.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 185.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 148.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 50.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 130.93 | 141.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1394.62 | 498.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 185.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 148.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 50.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 130.93 | 141.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1394.62 | 498.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.35 | 0.642799 | 0.481000 | 1.13 | 1.00 | 0.500000 | 0.000593 | 0.000068 | 1.13 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.456137 | 0.112046 | 0.481000 | 0.219402 | 0.481000 | 0.500000 | 0.003400 | 0.000041 | 0.219402 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.248517 | 0.238147 | 0.481000 | 0.119537 | 0.635059 | 0.500000 | 0.001600 | 0.000015 | 0.119537 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.197590 | 0.633399 | 0.481000 | 0.095041 | 1.00 | 0.500000 | 0.000602 | 0.000023 | 0.105493 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.107861 | 0.669441 | 0.481000 | 0.051881 | 1.00 | 0.500000 | 0.000569 | 0.000015 | 0.070682 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.72 | 0.063410 | 0.481000 | 1.79 | 0.481000 | 0.500000 | 0.023843 | 0.000097 | 1.79 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.88 | 0.076537 | 0.481000 | 0.904424 | 0.481000 | 0.500000 | 0.004978 | 0.000117 | 0.904424 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.52 | 0.180678 | 0.481000 | 2.65 | 0.481807 | 0.500000 | 0.002109 | 0.000294 | 2.65 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.46 | 0.811449 | 0.481000 | 0.703558 | 1.00 | 0.500000 | 0.000470 | 0.000141 | 0.703558 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.42 | 0.104254 | 0.481000 | 1.17 | 0.481000 | 0.500000 | 0.003655 | 0.000122 | 1.17 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.54 | 0.099337 | 0.481000 | 1.22 | 0.481000 | 0.500000 | 0.003835 | 0.000126 | 1.22 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.51 | 0.056472 | 0.481000 | 1.21 | 0.481000 | 0.500000 | 0.012135 | 0.000086 | 1.21 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.828726 | 0.378942 | 0.481000 | 0.398617 | 1.00 | 0.500000 | 0.001005 | 0.000097 | 0.444532 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 7828.34 | 0.000068 | 167.62 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4638.42 | 0.000041 | 119.38 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1725.32 | 0.000015 | 40.50 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2639.47 | 0.000023 | 72.04 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1768.50 | 0.000015 | 48.27 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11068.83 | 0.000097 | 234.96 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 13384.61 | 0.000117 | 315.67 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 33556.05 | 0.000294 | 769.78 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 8139.82 | 0.000071 | 232.56 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 8144.70 | 0.000071 | 232.70 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 46639.64 | 0.000408 | 1332.54 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 46748.55 | 0.000409 | 1335.65 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 8150.45 | 0.000071 | 232.87 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 8155.33 | 0.000071 | 233.01 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 16134.60 | 0.000141 | 426.42 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 2565.06 | 0.000022 | 73.29 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 2564.22 | 0.000022 | 73.26 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 12328.96 | 0.000108 | 352.24 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 13976.28 | 0.000122 | 317.98 |
DINING_FLR_6 VAV BOX REHEAT COIL | 14427.77 | 0.000126 | 327.45 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 9840.34 | 0.000086 | 213.74 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 11122.77 | 0.000097 | 303.57 |
VAV WITH REHEAT HEATING COIL | 339119.45 | 0.002967 | 4886.98 |
FLR_3_DOAS HEATING COIL | 28850.20 | 0.000252 | 415.75 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.30 | 0.000071 | 0.000455 |
ROOM_2_FLR_3 FAN COIL | 1.24 | 0.000071 | 0.000434 |
ROOM_3_MULT19_FLR_3 FAN COIL | 7.83 | 0.000408 | 0.002696 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.06 | 0.000409 | 0.002233 |
ROOM_5_FLR_3 FAN COIL | 1.16 | 0.000071 | 0.000406 |
ROOM_6_FLR_3 FAN COIL | 1.10 | 0.000071 | 0.000387 |
ROOM_1_FLR_6 FAN COIL | 0.343408 | 0.000022 | 0.000120 |
ROOM_2_FLR_6 FAN COIL | 0.326298 | 0.000022 | 0.000114 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.66 | 0.000108 | 0.000586 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.30 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.24 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 7.83 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.06 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.16 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.10 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.343408 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.326298 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.66 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008556 | 12.80 | 0.008500 | 0.000455 | 1.30 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008558 | 12.80 | 0.008500 | 0.000434 | 1.24 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008492 | 12.80 | 0.008492 | 0.002696 | 7.83 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.76 | 6.70 | 0.008754 | 12.80 | 0.008500 | 0.002233 | 6.06 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008562 | 12.80 | 0.008500 | 0.000406 | 1.16 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008565 | 12.80 | 0.008500 | 0.000387 | 1.10 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008553 | 12.80 | 0.008500 | 0.000120 | 0.343408 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.77 | 6.70 | 0.008555 | 12.80 | 0.008500 | 0.000114 | 0.326298 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.76 | 6.70 | 0.008606 | 12.80 | 0.008500 | 0.000586 | 1.66 | |
VAV WITH REHEAT COOLING COIL | 28.54 | 6.70 | 0.008048 | 10.71 | 0.008048 | 0.016489 | 24.11 | 461637.53 |
FLR_3_DOAS COOLING COIL | 33.40 | 6.70 | 0.006307 | 11.80 | 0.006307 | 0.001694 | 2.05 | 47434.83 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 12.12 | 11.66 | 24.24 | 11.66 | 24.11 | 24.11 | 0.300000 | 0.483581 | 24.11 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 24.11 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 24.11 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.016489 | 0.000029 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.002967 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001694 | 0.000281 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000252 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Size Rated Evaporator Air Flow Rate [m3/s] | Design Size Rated Condenser Water Flow Rate [m3/s] | |
SWHSYSLAUNDRY HPWH DXCOIL | 4.90 | 0.004370 |
SWHSYS1 HPWH DXCOIL | 3.87 | 0.003451 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
SWHSYSLAUNDRY HPWH FAN | 4.90 | 700.51 |
SWHSYS1 HPWH FAN | 3.87 | 553.22 |
Condenser water flow rate [m3/s] | Evaporator air flow rate [m3/s] | |
SWHSYS1 HPWH | 0.003451 | 3.87 |
SWHSYSLAUNDRY HPWH | 0.004370 | 4.90 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.025615 | 5226.00 | |
HEATSYS1 PUMP | 0.005717 | 1704.74 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.005717 | 0.686071 |
COOLSYS1 | 0.025615 | 3.07 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 653517.68 | 653517.68 | 0.005717 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.025615 | 3618.13 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.025615 | 717145.58 | 717800.64 | 81.83 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 HPWH TANK | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 6.644 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.024 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 9.699 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 20.459 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.628 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 10.008 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 4.090 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.780 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.705 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.235 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 9.257 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.637 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 9.042 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.112 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.257 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.077 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.733 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2943.236 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 13147.704 | 6.644 | 123.454 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13147.704 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 650.557 | 9.699 | 60.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 650.557 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 753.347 | 9.699 | 60.076 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 753.347 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 760.196 | 4.628 | 286.650 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 760.196 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 387.592 | 4.090 | 189.996 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 387.592 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 445.205 | 5.705 | 53.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 445.205 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1748.285 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1748.285 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 11828.200 | 9.042 | 28.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11828.200 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 108.229 | 4.413 | 72.152 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.229 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1718.521 | 4.413 | 82.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1718.521 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 3070.136 | 9.257 | 12.286 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3070.136 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1212.035 | 11.733 | 54.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1212.035 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1818.789 | 4.413 | 82.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1818.789 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.7516 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.031 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.097 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.9632 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1593 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1593 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.163 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8028 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7445 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8708 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8054 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.019 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.019 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.35250174E-14 | 0.26127805E-16 | -0.15803304E-09 | 0.75035430E-16 |
29 | 8 | 0.23041583E-07 | 0.10206171E-12 | 0.38994494E-03 | -0.26199070E-09 |
30 | 7 | -0.12603816E-01 | 0.52345574E-08 | -0.23607294E-01 | 0.14330998E-03 |
31 | 6 | 0.41519318 | 0.18149763E-05 | 0.48046513 | -0.48637856E-02 |
32 | 5 | -5.2866119 | 0.67574728E-04 | -4.5055401 | 0.64374809E-01 |
33 | 4 | 33.427666 | 0.55135347E-03 | 21.691508 | -0.42776325 |
34 | 3 | -112.12997 | 0.11988703E-02 | -56.120546 | 1.5282515 |
35 | 2 | 198.02682 | 0.67298354E-03 | 78.330368 | -2.9149402 |
36 | 1 | -171.49534 | 0.71707488E-04 | -55.387426 | 2.7513853 |
37 | 0 | 57.057407 | 0.40727117E-06 | 15.536952 | |
38 | 9 | -0.20590843E-15 | 0.37601014E-16 | -0.14495918E-09 | 0.53749011E-17 |
39 | 8 | 0.21205398E-07 | 0.13808064E-12 | 0.37072834E-03 | -0.24111267E-09 |
40 | 7 | -0.12030653E-01 | 0.72214098E-08 | -0.22782120E-01 | 0.13679291E-03 |
41 | 6 | 0.39961963 | 0.25236359E-05 | 0.46720788 | -0.46802108E-02 |
42 | 5 | -5.1346368 | 0.94596970E-04 | -4.4037454 | 0.62490383E-01 |
43 | 4 | 32.755467 | 0.77656360E-03 | 21.293679 | -0.41883826 |
44 | 3 | -110.69986 | 0.16977958E-02 | -55.334066 | 1.5075900 |
45 | 2 | 196.60952 | 0.95769584E-03 | 77.608945 | -2.8924333 |
46 | 1 | -170.97185 | 0.10250317E-03 | -55.177451 | 2.7422106 |
47 | 0 | 57.057407 | 0.58520576E-06 | 15.571474 | |
48 | 9 | -0.13316196E-15 | 0.35962645E-16 | -0.14184186E-09 | 0.33595795E-17 |
49 | 8 | 0.20766565E-07 | 0.14634888E-12 | 0.36605364E-03 | -0.23612300E-09 |
50 | 7 | -0.11890945E-01 | 0.76921302E-08 | -0.22580893E-01 | 0.13520437E-03 |
51 | 6 | 0.39582317 | 0.26934781E-05 | 0.46396918 | -0.46354598E-02 |
52 | 5 | -5.0975841 | 0.10113583E-03 | -4.3788466 | 0.62030949E-01 |
53 | 4 | 32.591550 | 0.83151862E-03 | 21.196301 | -0.41666193 |
54 | 3 | -110.35104 | 0.18204263E-02 | -55.141525 | 1.5025506 |
55 | 2 | 196.26372 | 0.10281160E-02 | 77.432455 | -2.8869422 |
56 | 1 | -170.84409 | 0.11016374E-03 | -55.126315 | 2.7399715 |
57 | 0 | 57.057407 | 0.62970739E-06 | 15.580070 | |
58 | 9 | -0.85509233E-15 | 0.35217200E-16 | -0.14813881E-09 | 0.22506418E-17 |
59 | 8 | 0.21652630E-07 | 0.12951040E-12 | 0.37545894E-03 | -0.24619788E-09 |
60 | 7 | -0.12171920E-01 | 0.67399561E-08 | -0.22985554E-01 | 0.13839917E-03 |
61 | 6 | 0.40345826 | 0.23507276E-05 | 0.47047975 | -0.47254590E-02 |
62 | 5 | -5.1720992 | 0.87965781E-04 | -4.4288869 | 0.62954898E-01 |
63 | 4 | 32.921184 | 0.72101989E-03 | 21.391978 | -0.42103852 |
64 | 3 | -111.05248 | 0.15742106E-02 | -55.528415 | 1.5126844 |
65 | 2 | 196.95904 | 0.88690553E-03 | 77.787143 | -2.8979836 |
66 | 1 | -171.10097 | 0.94819913E-04 | -55.229177 | 2.7444736 |
67 | 0 | 57.057407 | 0.54066260E-06 | 15.562856 | |
68 | 9 | -0.15009784E-15 | 0.35929976E-16 | -0.14508672E-09 | -0.10757262E-17 |
69 | 8 | 0.21223339E-07 | 0.13773381E-12 | 0.37091876E-03 | -0.24131668E-09 |
70 | 7 | -0.12036342E-01 | 0.72021282E-08 | -0.22790313E-01 | 0.13685759E-03 |
71 | 6 | 0.39977421 | 0.25166957E-05 | 0.46733969 | -0.46820329E-02 |
72 | 5 | -5.1361454 | 0.94330313E-04 | -4.4047585 | 0.62509089E-01 |
73 | 4 | 32.762141 | 0.77432644E-03 | 21.297641 | -0.41892687 |
74 | 3 | -110.71406 | 0.16928112E-02 | -55.341898 | 1.5077952 |
75 | 2 | 196.62360 | 0.95483717E-03 | 77.616126 | -2.8926568 |
76 | 1 | -170.97705 | 0.10219256E-03 | -55.179534 | 2.7423018 |
77 | 0 | 57.057407 | 0.58340349E-06 | 15.571125 | |
78 | 7 | -0.19147387E-14 | -0.13717675E-16 | -0.22389416E-13 | 0.54853152E-15 |
79 | 6 | 0.20210758E-10 | 0.18951096E-11 | 0.52387441E-09 | -0.18662741E-10 |
80 | 5 | -0.57595736E-07 | 0.92592455E-08 | -0.21946623E-05 | 0.17180500E-06 |
81 | 4 | 0.51775713E-04 | 0.34884876E-05 | 0.17695789E-02 | -0.28269358E-03 |
82 | 3 | -0.72897754E-02 | 0.12323952E-03 | -0.21573936 | 0.43368638E-01 |
83 | 2 | 0.10317303 | 0.53116266E-03 | 2.9018940 | -0.61935487 |
84 | 1 | -0.26095493 | 0.34096303E-03 | -7.1391298 | 1.5699863 |
85 | 0 | 0.16602045 | 0.17146927E-05 | 4.4522066 | |
86 | 7 | -0.22389416E-13 | -0.13717675E-16 | -0.19147387E-14 | 0.54853152E-15 |
87 | 6 | 0.52387441E-09 | 0.18951096E-11 | 0.20210758E-10 | -0.18662741E-10 |
88 | 5 | -0.21946623E-05 | 0.92592455E-08 | -0.57595736E-07 | 0.17180500E-06 |
89 | 4 | 0.17695789E-02 | 0.34884876E-05 | 0.51775713E-04 | -0.28269358E-03 |
90 | 3 | -0.21573936 | 0.12323952E-03 | -0.72897754E-02 | 0.43368638E-01 |
91 | 2 | 2.9018940 | 0.53116266E-03 | 0.10317303 | -0.61935487 |
92 | 1 | -7.1391298 | 0.34096303E-03 | -0.26095493 | 1.5699863 |
93 | 0 | 4.4522066 | 0.17146927E-05 | 0.16602045 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
103 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
104 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
105 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
106 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
107 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
108 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
109 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
110 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
111 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
112 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
113 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
114 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
115 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
116 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
117 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
118 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
119 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
120 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
121 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
122 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
123 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
124 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
125 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
126 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
127 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
128 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
129 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
130 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
131 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
132 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
133 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3464_SHGC_0.38 | 37 | 1 | VerySmooth | 1.968 | 1.968 | 1.000 | 0.381 | ||
2 | RESWINDOW_U_0.3464_SHGC_0.38 | 38 | 1 | VerySmooth | 1.968 | 1.968 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.78357E-002 | 0.29373 | 0.50217 | 0.50217 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11289 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.78357E-002 | 0.29373 | 0.50217 | 0.50217 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11289 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | "DX Coil Total Cooling Rate {W | HPWH Only}" | |
1 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | 1.1400 | 73879.8 | 48.891 | 1.6861 | 76621 | |
2 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | 2.8400 | 60796.6 | 4.620 | 9.2413 | 53264 |
Node Number | Height {m} | Volume {m3} | Maximum Capacity {W} | Off-Cycle UA {W/K} | On-Cycle UA {W/K} | Number Of Inlets | Number Of Outlets | |
1 | 1 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 0 | 1 |
2 | 2 | 0.2683 | 0.4733 | 59202.150 | 1.5573 | 1.5573 | 0 | 0 |
3 | 3 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
4 | 4 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
5 | 5 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 1 |
6 | 6 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 2 | 0 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 9.802E-003 | 1.461E-004 | 7.212E-005 | 0.133 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 3.784E-003 | 4.872E-005 | 1.327E-004 | 4.426E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 8.942E-003 | 5.445E-005 | 1.424E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 5.159E-003 | 5.445E-005 | 1.182E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 1.221E-002 | 1.565E-004 | 1.392E-004 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 2.167E-002 | 1.147E-004 | 6.318E-005 | 0.104 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 6.191E-002 | 4.733E-005 | 9.051E-005 | 4.300E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.587E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.588E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 6.879E-003 | 1.766E-005 | 1.424E-004 | 2.086E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 2.910E-003 | 1.186E-004 | 6.472E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1.243E-002 | 1.204E-004 | 6.523E-005 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1.217E-002 | 2.953E-005 | 2.446E-005 | 3.488E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1485 |
2 | Clear Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.3494E-002 |
3 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1702 |
4 | Clear Turbid Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.7226E-002 |
5 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.7203E-002 |
6 | Intermediate Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.9288E-002 |
7 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 3.9974E-002 |
8 | Overcast Sky | 01/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.3280E-002 |
9 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1680 |
10 | Clear Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 9.7565E-002 |
11 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1930 |
12 | Clear Turbid Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1128 |
13 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1074 |
14 | Intermediate Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.8759E-002 |
15 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 4.4888E-002 |
16 | Overcast Sky | 01/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.8161E-002 |
17 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.6424E-002 |
18 | Clear Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.1025E-002 |
19 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.8092E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.5938E-002 |
21 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.6819E-002 |
22 | Intermediate Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0707E-002 |
23 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.9348E-002 |
24 | Overcast Sky | 01/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3953E-002 |
25 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.6424E-002 |
26 | Clear Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.1025E-002 |
27 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.8092E-002 |
28 | Clear Turbid Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.5938E-002 |
29 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.6819E-002 |
30 | Intermediate Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0708E-002 |
31 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.9348E-002 |
32 | Overcast Sky | 01/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3953E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 28235.96750 | 28235.96750 | 2.34579 | 2.34579 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:50:00 | 25.69333 | 6.29499E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 2618.01204 | 2618.01204 | 0.12831 | 0.85446 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 5490.00243 | 5490.00243 | 0.45614 | 0.45614 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.13333 | 6.30642E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 3625.62545 | 3625.62545 | 0.17769 | 0.17769 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 2991.02503 | 2991.02503 | 0.24852 | 0.24852 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 32.60000 | 6.30558E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1173.50476 | 1173.50476 | 5.75127E-002 | 9.17347E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2378.64959 | 2378.64959 | 0.19759 | 0.19759 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.58667 | 6.30401E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 2152.52208 | 2152.52208 | 0.10549 | 0.10549 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1298.45192 | 1298.45192 | 0.10786 | 0.10786 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 33.08000 | 6.30633E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1442.21979 | 1442.21979 | 7.06821E-002 | 7.06821E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44795.24704 | 44795.24704 | 3.72141 | 3.72141 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.24000 | 6.30658E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2807.07243 | 2807.07243 | 0.13757 | 0.13757 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 22611.41355 | 22611.41355 | 1.88030 | 1.88030 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.13333 | 6.30642E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 9209.40791 | 9209.40791 | 0.45134 | 0.67639 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 66382.84069 | 66382.84069 | 5.51722 | 5.51722 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.26667 | 6.30663E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 21305.04396 | 21305.04396 | 1.04415 | 1.89399 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11634.68961 | 11634.68961 | 1.30245 | 1.30245 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 30.62667 | 6.30253E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 8139.81937 | 8139.81937 | 0.40126 | 0.40126 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11093.25987 | 11093.25987 | 1.24184 | 1.24184 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 8144.69678 | 8144.69678 | 0.40150 | 0.40150 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 69980.44505 | 69980.44505 | 7.83363 | 7.83363 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40000 | 6.30683E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 46639.64470 | 46639.64470 | 2.29920 | 2.29920 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 54131.52235 | 54131.52235 | 6.06001 | 6.06001 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.28000 | 6.29588E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 46748.54802 | 46748.54802 | 2.30457 | 2.30457 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10371.10409 | 10371.10409 | 1.16100 | 1.16100 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 27.72000 | 6.29806E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 8150.44901 | 8150.44901 | 0.40179 | 0.40179 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9852.39094 | 9852.39094 | 1.10293 | 1.10293 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.96000 | 6.29539E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 8155.32541 | 8155.32541 | 0.40203 | 0.40203 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 17606.82907 | 17606.82907 | 1.46270 | 1.46270 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.40000 | 6.30683E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 12886.38274 | 12886.38274 | 0.63156 | 0.63156 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3067.65109 | 3067.65109 | 0.34341 | 0.34341 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 30.62667 | 6.30253E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2565.06405 | 2565.06405 | 0.12645 | 0.12645 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2914.80095 | 2914.80095 | 0.32630 | 0.32630 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2564.22067 | 2564.22067 | 0.12641 | 0.12641 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 14784.12852 | 14784.12852 | 1.65506 | 1.65506 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40000 | 6.30683E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 12328.95915 | 12328.95915 | 0.60778 | 0.60778 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29140.95569 | 29140.95569 | 2.42410 | 2.42410 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.40000 | 6.30683E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 8592.98275 | 8592.98275 | 0.42114 | 1.18780 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30583.98946 | 30583.98946 | 2.54409 | 2.54409 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.40000 | 6.30683E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 8777.98430 | 8777.98430 | 0.43020 | 1.18780 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30096.98831 | 30096.98831 | 2.50717 | 2.50717 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 31.96000 | 6.30459E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 4277.19840 | 4277.19840 | 0.20961 | 0.36735 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -27.60000 | 3.41898E-004 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 9975.67150 | 9975.67150 | 0.82873 | 0.82873 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.40000 | 6.30683E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 9070.32380 | 9070.32380 | 0.44453 | 0.44453 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 401638.46 | 24.11219 | 24.11219 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 366937.56 | 7.82704 | 7.82704 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 44717.32 | 19.56313 | 2.05125 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 96163.95 | 7.07098 | 2.05125 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.34579 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.64280 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48100 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.12832 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.92721E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.84857E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.12832 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7828.33925 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.84857E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 167.62406 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.45614 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11205 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48100 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21940 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48100 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.40038E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.05790E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.21940 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4638.42445 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.05790E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 119.37637 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.24852 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23815 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48100 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11954 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63506 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.59985E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.50939E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11954 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1725.32457 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.50939E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 40.49695 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.19759 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.63340 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48100 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 9.50408E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.01517E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.30913E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.10549 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2639.47294 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.30913E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 72.03651 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.10786 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.66944 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48100 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.18811E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.69132E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.54716E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.06821E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1768.49951 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54716E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 48.26606 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.72141 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.34098E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48100 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.79000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48100 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.38431E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.68350E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.79000 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11068.82995 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.68350E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 234.95810 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.88030 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.65371E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48100 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.90442 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48100 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.97798E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.17094E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.90442 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13384.60663 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.17094E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 315.66588 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.51722 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18068 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48100 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.65378 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48181 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.10873E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.93563E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.65378 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 33556.04644 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.93563E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 769.78391 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.30245 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.30245 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.12107E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.55209E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.76522 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55560E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.55209E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.30245 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8139.81937 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.12107E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 232.56223 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.24184 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.24184 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.12534E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.34323E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.76521 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55811E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.34323E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.24184 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8144.69678 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.12534E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 232.70157 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.83363 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 7.83363 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.08024E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.69633E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.76566 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.49203E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.49203E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.69633E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.83363 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 46639.64470 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.08024E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1332.53515 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.06001 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.06001 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.08977E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.23259E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.76465 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.75366E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.23259E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.06001 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 46748.54802 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.08977E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1335.64643 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.16100 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.16100 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.13037E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.06498E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.76521 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56215E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.06498E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.16100 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8150.44901 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.13037E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 232.86590 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.10293 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.10293 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.13463E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.86502E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.76520 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56534E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.86502E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.10293 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8155.32541 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.13463E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 233.00521 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.46270 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.81145 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48100 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.70356 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.69531E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.41153E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.70356 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16134.60132 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.41153E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 426.42346 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.34341 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.34341 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.24403E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.19929E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.76523 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55277E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.19929E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.34341 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2565.06405 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.24403E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 73.28517 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.32630 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.32630 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.24329E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.14034E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.76522 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55534E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.14034E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.32630 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2564.22067 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.24329E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 73.26107 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.65506 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.65506 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.07859E-004 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.86476E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.76493 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60646E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.86476E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.65506 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 12328.95915 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.07859E-004 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 352.24410 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.42410 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10425 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48100 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.16599 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48100 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.65452E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.22271E-004 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.16599 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13976.27762 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.22271E-004 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 317.97978 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.54409 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.93372E-002 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48100 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.22371 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48100 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.83542E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.26220E-004 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.22371 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14427.77029 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.26220E-004 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 327.44838 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.50717 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.64718E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48100 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.20595 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48100 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21348E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.60876E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20595 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9840.34105 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.60876E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 213.73975 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82873 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37894 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48100 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.39862 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.00543E-003 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.73069E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.44453 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11122.77112 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.73069E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 303.56783 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 12.12080 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.66021 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.24160 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.66021 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.11219 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 24.11219 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.48358 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 24.11219 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.11219 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.54010 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.71373 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.04799E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.04799E-003 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 461637.52860 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.64886E-002 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 24.11219 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 339119.44553 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.96676E-003 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 4886.97633 |
350 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 24.11219 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.64886E-002 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.88799E-005 |
353 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.96676E-003 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
356 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 33.40000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.80050 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.30683E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.30683E-003 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 47434.82677 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.69426E-003 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 28850.19938 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.52394E-004 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 415.75393 |
368 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.69426E-003 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.81061E-004 |
371 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.52394E-004 |
372 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 4.90359 |
373 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 4.36989E-003 |
374 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.90359 |
375 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Electric Power Consumption [W] | 700.51236 |
376 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 3.87257 |
377 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 3.45109E-003 |
378 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.87257 |
379 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Electric Power Consumption [W] | 553.22422 |
380 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Condenser water flow rate [m3/s] | 3.45109E-003 |
381 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Evaporator air flow rate [m3/s] | 3.87257 |
382 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.56148E-002 |
383 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 5225.99651 |
384 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 5.71726E-003 |
385 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.68607 |
386 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 5.71726E-003 |
387 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1704.73956 |
388 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
389 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 653517.67721 |
390 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 653517.68000 |
391 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 5.71726E-003 |
392 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.56148E-002 |
393 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.07377 |
394 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.56148E-002 |
395 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3618.13365 |
396 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.56148E-002 |
397 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 717145.57981 |
398 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 717800.64000 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 81.82927 |
400 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
401 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
402 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
403 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
404 | WaterHeater:Stratified | SWHSYS1 HPWH TANK | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
405 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Condenser water flow rate [m3/s] | 4.36989E-003 |
406 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Evaporator air flow rate [m3/s] | 4.90359 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 7868.47 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4658.35 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1733.48 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2650.32 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1775.77 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11125.92 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 13447.69 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 33717.29 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 8768.71 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 8773.96 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 50243.15 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 50360.46 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 8780.16 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 8785.41 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 16202.47 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2763.22 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2762.31 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 13281.39 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 14043.85 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 14497.66 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 9890.31 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 11168.49 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 203585.44 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 17319.80 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 21975.36 | 16700.49 | 5274.87 | 0.76 | 3408.86 | 34.57 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 20961.98 | 15926.63 | 5035.35 | 0.76 | 3250.49 | 32.97 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 130973.99 | 100049.37 | 30924.62 | 0.76 | 20550.69 | 208.44 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 105757.93 | 78973.97 | 26783.96 | 0.75 | 15993.08 | 162.21 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 19611.31 | 14894.80 | 4716.51 | 0.76 | 3039.27 | 30.83 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 18640.86 | 14153.55 | 4487.30 | 0.76 | 2887.56 | 29.29 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5791.23 | 4402.29 | 1388.94 | 0.76 | 898.71 | 9.12 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 5505.16 | 4183.83 | 1321.33 | 0.76 | 854.00 | 8.66 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 28173.04 | 21310.65 | 6862.39 | 0.76 | 4339.03 | 44.01 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 630176.66 | 397213.18 | 232963.49 | 0.63 | 101302.67 | 1027.47 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 47792.09 | 30829.10 | 16962.99 | 0.65 | 4769.70 | 48.38 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.354 | 0.336 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.354 | 0.336 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.963 | 0.842 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.963 | 0.842 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.963 | 0.842 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.963 | 0.842 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.963 | 0.842 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.963 | 0.842 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.963 | 0.842 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.963 | 0.842 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.963 | 0.842 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.963 | 0.842 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.031 | 0.893 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.031 | 0.893 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.031 | 0.893 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.031 | 0.893 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.159 | 0.155 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.028 | 0.891 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.028 | 0.891 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.028 | 0.891 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.028 | 0.891 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.028 | 0.891 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.097 | 0.942 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.097 | 0.942 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.097 | 0.942 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.097 | 0.942 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.097 | 0.942 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.097 | 0.942 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.097 | 0.942 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.097 | 0.942 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3464_SHGC_0.38 | N/A | 1.968 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.159 | 0.153 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.7154504191E-002 | 2.4498922492E-002 | Pass | Pass | 5.2891677258E-003 | 1.5972509815E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.3453534204E-002 | 8.7089802259E-002 | Pass | Pass | 4.2337688785E-002 | 5.4008812010E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.8078219386E-002 | 2.9480293642E-002 | Pass | Pass | 6.5938095728E-003 | 1.6454921436E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.4134200329E-002 | 1.4538982046E-002 | Pass | Pass | 6.6133758015E-003 | 2.0849790197E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.7953837817E-003 | 8.6539306111E-003 | Pass | Pass | 1.4032904213E-002 | 2.8880401142E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.4352371653E-002 | 0.1686656063 | Pass | Pass | 1.9584183387E-002 | 5.2534662901E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.7684225220E-002 | 9.0703639385E-002 | Pass | Pass | 1.6407163627E-002 | 2.1732572821E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.1822498536E-002 | 4.5458590033E-002 | Pass | Pass | 7.4753245946E-003 | 1.4866577946E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.1687948222E-002 | 0.1496041918 | Pass | Pass | 1.1082953808 | 6.0392275530 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.3954201162E-002 | 0.2097894626 | Pass | Pass | 8.2286309805E-002 | 0.3215316249 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.7421546334E-002 | 3.3979556088E-002 | Pass | Pass | 6.9392046489E-002 | 0.2010347957 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.7929875244E-002 | 5.2025743319E-002 | Pass | Pass | 1.2710106108 | 10.6277610135 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.8263442451E-002 | 0.1220221592 | Pass | Pass | 0.5088511442 | 4.7678951031 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.7390854950E-002 | 0.1912159711 | Pass | Pass | 0.3832626057 | 2.5960100456 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.1622053195E-003 | 1.1913268118E-002 | Pass | Pass | 2.1060426437E-002 | 4.9769587105E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.2160560908E-002 | 0.2103335222 | Pass | Pass | 0.1224989418 | 0.3981428877 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1001655247 | 0.3053349638 | Pass | Pass | 7.1488885147E-002 | 0.2177287809 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.5832484148E-002 | 0.2387904916 | Pass | Pass | 0.2502997094 | 0.7886426562 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.8942050326E-002 | 6.9649490285E-002 | Pass | Pass | 1.3987039349E-002 | 4.4080171989E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.8860444351E-002 | 4.8927994307E-002 | Pass | Pass | 1.4247244277E-002 | 4.2214087422E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.2632311131E-002 | 6.7585982484E-002 | Pass | Pass | 2.1424509102E-002 | 4.2757304407E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.5062606415E-003 | 1.8996264540E-002 | Pass | Pass | 3.3410631065E-002 | 5.5412990572E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4250.64 | 44.67 | 1922.40 | 9271.30 | 2898.90 | 18387.91 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.340 | 0.354 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.340 | 0.354 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.340 | 0.354 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.340 | 0.354 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.842 | 0.963 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.842 | 0.963 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.842 | 0.963 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.842 | 0.963 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.842 | 0.963 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.842 | 0.963 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.842 | 0.963 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.842 | 0.963 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.842 | 0.963 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.842 | 0.963 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.891 | 1.028 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.153 | 0.159 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.153 | 0.159 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.153 | 0.159 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.153 | 0.159 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.153 | 0.159 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.153 | 0.159 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.153 | 0.159 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.153 | 0.159 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.153 | 0.159 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.153 | 0.159 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.153 | 0.159 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.153 | 0.159 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.153 | 0.159 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.153 | 0.159 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.153 | 0.159 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.153 | 0.159 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.154 | 0.159 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.151 | 0.159 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3464_SHGC_0.38 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 1.968 | 0.381 | 0.381 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3464_SHGC_0.38 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 1.968 | 0.381 | 0.381 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3464_SHGC_0.38 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 1.968 | 0.381 | 0.381 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3464_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.968 | 0.381 | 0.381 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3464_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.968 | 0.381 | 0.381 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3464_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.968 | 0.381 | 0.381 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3464_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.968 | 0.381 | 0.381 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3464_SHGC_0.38 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 1.968 | 0.381 | 0.381 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3464_SHGC_0.38 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 1.968 | 0.381 | 0.381 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3464_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.968 | 0.381 | 0.381 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3464_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.968 | 0.381 | 0.381 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3464_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.968 | 0.381 | 0.381 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3464_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.968 | 0.381 | 0.381 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3464_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.968 | 0.381 | 0.381 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3464_SHGC_0.38 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 1.968 | 0.381 | 0.381 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3464_SHGC_0.38 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 1.968 | 0.381 | 0.381 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3464_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.968 | 0.381 | 0.381 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3464_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.968 | 0.381 | 0.381 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3464_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.968 | 0.381 | 0.381 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.3464_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.968 | 0.381 | 0.381 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3464_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.968 | 0.381 | 0.381 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3464_SHGC_0.38 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 1.968 | 0.381 | 0.381 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3464_SHGC_0.38 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.968 | 0.381 | 0.381 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3464_SHGC_0.38 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.968 | 0.381 | 0.381 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3464_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.968 | 0.381 | 0.381 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.3464_SHGC_0.38 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.968 | 0.381 | 0.381 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3464_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.968 | 0.381 | 0.381 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3464_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 1.968 | 0.381 | 0.381 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3464_SHGC_0.38 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 1.968 | 0.381 | 0.381 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3464_SHGC_0.38 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.968 | 0.381 | 0.381 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 1.968 | 0.381 | 0.381 | |||||||||||||||||
North Total or Average | 432.95 | 1.968 | 0.381 | 0.381 | |||||||||||||||||
Non-North Total or Average | 780.84 | 1.968 | 0.381 | 0.381 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.6442 | 1978.83 | 13147.70 | LightsWired | LTG_SCH_BASEMENT | 45.99 | 168.00 | 45.94 | 0.0000 | Y | 113.37 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 9.6995 | 67.07 | 650.56 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 6.26 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 9.6995 | 77.67 | 753.35 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 7.25 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.6285 | 164.24 | 760.20 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.37 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 4.0903 | 94.76 | 387.59 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 1.87 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.7049 | 78.04 | 445.21 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.90 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 9.2569 | 188.86 | 1748.29 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 38.75 | 0.0000 | Y | 12.72 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 9.0417 | 1308.19 | 11828.20 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 55.24 | 0.0000 | Y | 122.64 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 4.4132 | 1863.81 | 8225.38 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 73.68 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 4.4132 | 1864.32 | 8227.62 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 73.70 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 4.4132 | 156.09 | 688.85 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 4.4132 | 156.07 | 688.77 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 6.17 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 4.4132 | 1557.62 | 6874.08 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 56.74 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.21 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.54 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 4.4132 | 39.02 | 172.19 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.54 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 4.4132 | 220.77 | 974.32 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 8.73 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 48.84 | 0.0000 | Y | 28.15 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 9.2569 | 331.66 | 3070.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 48.84 | 0.0000 | Y | 28.15 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 11.7327 | 103.30 | 1212.04 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.34 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 4.4132 | 412.12 | 1818.79 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 15.01 |
Interior Lighting Total | 5.8432 | 11345.29 | 66293.22 | 388.38 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 11828.20 | 827.97 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1748.29 | 681.83 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 3070.14 | 614.03 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 11096.45 | AstronomicalClock | - | 83.57 | 83.57 | 174.07 | |
Exterior Lighting Total | 11096.45 | 174.07 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 653517.68 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 717800.64 | 2.96 | 717926.81 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12744.88 | 21975.36 | 16700.49 | 5274.87 | 0.76 | - | 3408.86 | 34.57 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12160.12 | 20961.98 | 15926.63 | 5035.35 | 0.76 | - | 3250.49 | 32.97 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 75491.45 | 130973.99 | 100049.37 | 30924.62 | 0.76 | - | 20550.69 | 208.44 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 62507.81 | 105757.93 | 78973.97 | 26783.96 | 0.75 | - | 15993.08 | 162.21 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11381.07 | 19611.31 | 14894.80 | 4716.51 | 0.76 | - | 3039.27 | 30.83 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10821.23 | 18640.86 | 14153.55 | 4487.30 | 0.76 | - | 2887.56 | 29.29 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3357.77 | 5791.23 | 4402.29 | 1388.94 | 0.76 | - | 898.71 | 9.12 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3192.70 | 5505.16 | 4183.83 | 1321.33 | 0.76 | - | 854.00 | 8.66 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 16420.07 | 28173.04 | 21310.65 | 6862.39 | 0.76 | - | 4339.03 | 44.01 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 461637.53 | 630176.66 | 397213.18 | 232963.49 | 0.63 | - | 101302.67 | 1027.47 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 47434.83 | 47792.09 | 30829.10 | 16962.99 | 0.65 | - | 4769.70 | 48.38 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 7828.34 | 7868.47 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4638.42 | 4658.35 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1725.32 | 1733.48 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2639.47 | 2650.32 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1768.50 | 1775.77 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11068.83 | 11125.92 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 13384.61 | 13447.69 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 33556.05 | 33717.29 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 8139.82 | 8768.71 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 8144.70 | 8773.96 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 46639.64 | 50243.15 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 46748.55 | 50360.46 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 8150.45 | 8780.16 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 8155.33 | 8785.41 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 16134.60 | 16202.47 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2565.06 | 2763.22 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2564.22 | 2762.31 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 12328.96 | 13281.39 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 13976.28 | 14043.85 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 14427.77 | 14497.66 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 9840.34 | 9890.31 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11122.77 | 11168.49 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 339119.45 | 203585.44 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 28850.20 | 17319.80 | - |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 75921.46 | 3.40 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 54370.95 | 3.40 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.30 | 916.45 | 703.64 | 1.00 | 1.14 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.24 | 873.80 | 703.64 | 1.00 | 1.15 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 7.83 | 5512.03 | 703.64 | 1.00 | 0.94 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.06 | 4264.04 | 703.64 | 1.00 | 0.96 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.16 | 816.92 | 703.64 | 1.00 | 1.16 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.10 | 776.06 | 703.64 | 1.00 | 1.17 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.34 | 241.63 | 703.64 | 1.00 | 1.62 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.33 | 229.59 | 703.64 | 1.00 | 1.66 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.66 | 1164.56 | 703.64 | 1.00 | 1.09 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 24.11 | 54026.71 | 2240.64 | 1.00 | 1.11 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 4.90 | 700.51 | 142.86 | 0.00 | 2.78 | General | ||
SWHSYS1 HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 3.87 | 553.22 | 142.86 | 0.00 | 2.84 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.025615 | 5226.00 | 204022.71 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.005717 | 1704.74 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.025615 | 3618.13 | 141251.80 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYSLAUNDRY HPWH | WaterHeater:HeatPump:PumpedCondenser | 1.14 | 73879.89 | 0.80 | 48.89 | 1.69 |
SWHSYS1 HPWH | WaterHeater:HeatPump:PumpedCondenser | 2.84 | 60796.61 | 0.80 | 4.62 | 9.24 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 28235.97 | 28235.97 | 14.27 | 2.346 | 2.346 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:50:00 | 24.00 | 24.00 | 0.00935 | 25.69 | 0.00629 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 5490.00 | 5490.00 | 81.85 | 0.456 | 0.456 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00893 | 33.13 | 0.00631 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 2991.03 | 2991.03 | 38.51 | 0.249 | 0.249 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00944 | 32.60 | 0.00631 | 0.092 | 0.00 |
MECH_FLR_1 | 2378.65 | 2378.65 | 14.48 | 0.198 | 0.198 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00873 | 31.59 | 0.00630 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1298.45 | 1298.45 | 13.70 | 0.108 | 0.108 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00883 | 33.08 | 0.00631 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44795.25 | 44795.25 | 574.01 | 3.721 | 3.721 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00854 | 33.24 | 0.00631 | 0.000 | 0.00 |
CAFE_FLR_1 | 22611.41 | 22611.41 | 119.72 | 1.880 | 1.880 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 23.99 | 0.00991 | 33.13 | 0.00631 | 0.676 | 0.00 |
LOBBY_FLR_1 | 66382.84 | 66382.84 | 50.74 | 5.517 | 5.517 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 23.99 | 0.00993 | 33.27 | 0.00631 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 11634.69 | 11634.69 | 298.16 | 1.302 | 1.302 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00856 | 30.63 | 0.00630 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11093.26 | 11093.26 | 284.32 | 1.242 | 1.242 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 21.11 | 21.11 | 0.00856 | 30.36 | 0.00630 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 69980.45 | 69980.45 | 2853.57 | 7.834 | 7.834 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 21.11 | 21.11 | 0.00849 | 33.40 | 0.00631 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 54131.52 | 54131.52 | 2206.70 | 6.060 | 6.060 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 21.11 | 21.11 | 0.00875 | 26.28 | 0.00630 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10371.10 | 10371.10 | 265.78 | 1.161 | 1.161 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 21.11 | 21.11 | 0.00856 | 27.72 | 0.00630 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9852.39 | 9852.39 | 252.51 | 1.103 | 1.103 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 21.11 | 21.11 | 0.00857 | 25.96 | 0.00630 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 17606.83 | 17606.83 | 45.21 | 1.463 | 1.463 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00958 | 33.40 | 0.00631 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3067.65 | 3067.65 | 78.61 | 0.343 | 0.343 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00855 | 30.63 | 0.00630 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2914.80 | 2914.80 | 74.71 | 0.326 | 0.326 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 21.11 | 21.11 | 0.00856 | 30.36 | 0.00630 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 14784.13 | 14784.13 | 602.68 | 1.655 | 1.655 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 21.11 | 21.11 | 0.00861 | 33.40 | 0.00631 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29140.96 | 29140.96 | 87.86 | 2.424 | 2.424 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 23.98 | 0.01043 | 33.40 | 0.00631 | 1.188 | 0.00 |
DINING_FLR_6 | 30583.99 | 30583.99 | 92.22 | 2.544 | 2.544 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 23.98 | 0.01034 | 33.40 | 0.00631 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30096.99 | 30096.99 | 291.34 | 2.507 | 2.507 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01011 | 31.96 | 0.00630 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9975.67 | 9975.67 | 24.21 | 0.829 | 0.829 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00900 | 33.40 | 0.00631 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 2618.01 | 2618.01 | 1.32 | 0.128 | 0.854 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 3625.63 | 3625.63 | 54.06 | 0.178 | 0.178 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00788 | -27.60 | 0.00034 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1173.50 | 1173.50 | 15.11 | 0.058 | 0.092 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00785 | -27.60 | 0.00034 | 0.092 | 0.00 |
MECH_FLR_1 | 2152.52 | 2152.52 | 13.11 | 0.105 | 0.105 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00781 | -27.60 | 0.00034 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1442.22 | 1442.22 | 15.22 | 0.071 | 0.071 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00784 | -27.60 | 0.00034 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2807.07 | 2807.07 | 35.97 | 0.138 | 0.138 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00780 | -27.60 | 0.00034 | 0.000 | 0.00 |
CAFE_FLR_1 | 9209.41 | 9209.41 | 48.76 | 0.451 | 0.676 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00789 | -27.60 | 0.00034 | 0.676 | 0.00 |
LOBBY_FLR_1 | 21305.04 | 21305.04 | 16.29 | 1.044 | 1.894 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00787 | -27.60 | 0.00034 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 8139.82 | 8139.82 | 208.60 | 0.401 | 0.401 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00787 | -27.60 | 0.00034 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 8144.70 | 8144.70 | 208.74 | 0.402 | 0.402 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00787 | -27.60 | 0.00034 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 46639.64 | 46639.64 | 1901.81 | 2.299 | 2.299 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00788 | -27.60 | 0.00034 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 46748.55 | 46748.55 | 1905.73 | 2.305 | 2.305 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00788 | -27.60 | 0.00034 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 8150.45 | 8150.45 | 208.87 | 0.402 | 0.402 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00787 | -27.60 | 0.00034 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 8155.33 | 8155.33 | 209.02 | 0.402 | 0.402 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00787 | -27.60 | 0.00034 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 12886.38 | 12886.38 | 33.09 | 0.632 | 0.632 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00790 | -27.60 | 0.00034 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2565.06 | 2565.06 | 65.73 | 0.126 | 0.126 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00790 | -27.60 | 0.00034 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2564.22 | 2564.22 | 65.72 | 0.126 | 0.126 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00790 | -27.60 | 0.00034 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 12328.96 | 12328.96 | 502.60 | 0.608 | 0.608 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00790 | -27.60 | 0.00034 | 0.099 | 0.00 |
BANQUET_FLR_6 | 8592.98 | 8592.98 | 25.91 | 0.421 | 1.188 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00793 | -27.60 | 0.00034 | 1.188 | 0.00 |
DINING_FLR_6 | 8777.98 | 8777.98 | 26.47 | 0.430 | 1.188 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00793 | -27.60 | 0.00034 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 4277.20 | 4277.20 | 41.40 | 0.210 | 0.367 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00764 | -27.60 | 0.00034 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9070.32 | 9070.32 | 22.01 | 0.445 | 0.445 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00794 | -27.60 | 0.00034 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 24.11 | 24.11 | 7.83 | 7.83 | 24.1122 | 11.6602 | 24.1122 | 0.4836 | 0.3000 |
FLR_3_DOAS | 19.56 | 2.05 | 7.07 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 7828.339 | 7828.339 | 1.128324 | 0.00006849 | 167.624 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7828.34 | 7828.34 | 1.128324 | 16.70 | 11.94 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00799929 | 45.2270 | 2618.01 | 0.00 | 7871.94 | 7871.94 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4638.424 | 4638.424 | 0.219402 | 0.00004058 | 119.376 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4638.42 | 4638.42 | 0.219402 | 16.70 | 11.94 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00787602 | 44.5401 | 3625.63 | 0.00 | 4661.85 | 4661.85 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1725.325 | 1725.325 | 0.119537 | 0.00001509 | 40.497 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1725.32 | 1725.32 | 0.119537 | 16.70 | 11.94 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00785260 | 44.4085 | 1173.50 | 0.00 | 1734.52 | 1734.52 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2639.473 | 2639.473 | 0.105493 | 0.00002309 | 72.037 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2639.47 | 2639.47 | 0.105493 | 16.70 | 11.94 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00781113 | 44.1770 | 2152.52 | 0.00 | 2652.56 | 2652.56 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1768.500 | 1768.500 | 0.070682 | 0.00001547 | 48.266 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1768.50 | 1768.50 | 0.070682 | 16.70 | 11.94 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00783680 | 44.3204 | 1442.22 | 0.00 | 1777.27 | 1777.27 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11068.830 | 11068.830 | 1.789997 | 0.00009683 | 234.958 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11068.83 | 11068.83 | 1.789997 | 16.70 | 11.94 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00780247 | 44.1295 | 2807.07 | 0.00 | 11130.66 | 11130.66 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 13384.607 | 13384.607 | 0.904424 | 0.00011709 | 315.666 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 13384.61 | 13384.61 | 0.904424 | 16.70 | 11.94 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00789187 | 44.6284 | 9209.41 | 0.00 | 13455.85 | 13455.85 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 33556.046 | 33556.046 | 2.653782 | 0.00029356 | 769.784 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 33556.05 | 33556.05 | 2.653782 | 16.70 | 11.94 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00786690 | 44.4884 | 21305.04 | 0.00 | 33736.18 | 33736.18 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12744.881 | -999.000 | 1.302447 | 0.00045521 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 12744.88 | 12601.59 | 1.302447 | 21.77 | 14.29 | 0.00855560 | 12.80 | 10.89 | 0.00850000 | 30.63 | 0.00630253 | 15.45 | 0.0000 | 21.11 | 0.00855560 | 48.0021 | 11634.69 | 0.00 | 14601.00 | 13951.00 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 8139.819 | 8139.819 | 0.401263 | 0.00007121 | 232.562 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8139.82 | 8139.82 | 0.401263 | 21.11 | 13.47 | 0.00787259 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.11 | 0.00787259 | 44.2185 | 8139.82 | 0.00 | 8774.94 | 8774.94 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 12160.125 | -999.000 | 1.241837 | 0.00043432 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | unknown | 7/21 17:30:00 | 12160.12 | 12017.31 | 1.241837 | 21.77 | 14.29 | 0.00855811 | 12.80 | 10.89 | 0.00850000 | 30.36 | 0.00630211 | 15.36 | 0.0000 | 21.11 | 0.00855811 | 48.0160 | 11093.26 | 0.00 | 13930.44 | 13302.30 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 8144.697 | 8144.697 | 0.401504 | 0.00007125 | 232.702 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8144.70 | 8144.70 | 0.401504 | 21.11 | 13.47 | 0.00787267 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.11 | 0.00787267 | 44.2190 | 8144.70 | 0.00 | 8780.20 | 8780.20 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 75491.453 | -999.000 | 7.833628 | 0.00269633 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | 7/21 14:00:00 | 75491.45 | 75491.45 | 7.833628 | 21.77 | 14.24 | 0.00849203 | 12.80 | 10.89 | 0.00849203 | 33.40 | 0.00630683 | 16.37 | 0.0000 | 21.11 | 0.00849203 | 47.6492 | 69980.45 | 0.00 | 86584.00 | 83935.32 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 46639.645 | 46639.645 | 2.299199 | 0.00040802 | 1332.535 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 46639.64 | 46639.64 | 2.299199 | 21.11 | 13.47 | 0.00788197 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.11 | 0.00788197 | 44.2698 | 46639.64 | 0.00 | 50279.00 | 50279.00 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 62507.814 | -999.000 | 6.060009 | 0.00223259 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | unknown | 7/21 19:30:00 | 62507.81 | 59425.19 | 6.060009 | 21.76 | 14.46 | 0.00875366 | 12.80 | 10.89 | 0.00850000 | 26.28 | 0.00629588 | 13.94 | 0.0000 | 21.11 | 0.00875366 | 49.0989 | 54131.52 | 0.00 | 71375.25 | 65122.70 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 46748.548 | 46748.548 | 2.304568 | 0.00040898 | 1335.646 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 46748.55 | 46748.55 | 2.304568 | 21.11 | 13.48 | 0.00788221 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.11 | 0.00788221 | 44.2711 | 46748.55 | 0.00 | 50396.40 | 50396.40 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 11381.068 | -999.000 | 1.160995 | 0.00040650 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | unknown | 7/21 10:10:00 | 11381.07 | 11238.23 | 1.160995 | 21.77 | 14.30 | 0.00856215 | 12.80 | 10.89 | 0.00850000 | 27.72 | 0.00629806 | 14.45 | 0.0000 | 21.11 | 0.00856215 | 48.0384 | 10371.10 | 0.00 | 13036.99 | 12437.12 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 8150.449 | 8150.449 | 0.401787 | 0.00007130 | 232.866 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8150.45 | 8150.45 | 0.401787 | 21.11 | 13.47 | 0.00787275 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.11 | 0.00787275 | 44.2194 | 8150.45 | 0.00 | 8786.40 | 8786.40 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10821.231 | -999.000 | 1.102928 | 0.00038650 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | unknown | 7/21 09:30:00 | 10821.23 | 10678.56 | 1.102928 | 21.77 | 14.30 | 0.00856534 | 12.80 | 10.89 | 0.00850000 | 25.96 | 0.00629539 | 13.83 | 0.0000 | 21.11 | 0.00856534 | 48.0560 | 9852.39 | 0.00 | 12394.97 | 11815.66 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 8155.325 | 8155.325 | 0.402028 | 0.00007135 | 233.005 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8155.33 | 8155.33 | 0.402028 | 21.11 | 13.47 | 0.00787284 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.11 | 0.00787284 | 44.2199 | 8155.33 | 0.00 | 8791.65 | 8791.65 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 16134.601 | 16134.601 | 0.703558 | 0.00014115 | 426.423 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 16134.60 | 16134.60 | 0.703558 | 16.70 | 11.94 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00790173 | 44.6826 | 12886.38 | 0.00 | 16215.33 | 16215.33 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3357.768 | -999.000 | 0.343408 | 0.00011993 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 3357.77 | 3321.92 | 0.343408 | 21.77 | 14.29 | 0.00855277 | 12.80 | 10.89 | 0.00850000 | 30.63 | 0.00630253 | 15.45 | 0.0000 | 21.11 | 0.00855277 | 47.9865 | 3067.65 | 0.00 | 3846.98 | 3678.22 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2565.064 | 2565.064 | 0.126448 | 0.00002244 | 73.285 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2565.06 | 2565.06 | 0.126448 | 21.11 | 13.49 | 0.00789855 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.11 | 0.00789855 | 44.3625 | 2565.06 | 0.00 | 2765.21 | 2765.21 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3192.704 | -999.000 | 0.326298 | 0.00011403 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | unknown | 7/21 17:30:00 | 3192.70 | 3156.98 | 0.326298 | 21.77 | 14.29 | 0.00855534 | 12.80 | 10.89 | 0.00850000 | 30.36 | 0.00630211 | 15.36 | 0.0000 | 21.11 | 0.00855534 | 48.0007 | 2914.80 | 0.00 | 3657.70 | 3495.09 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2564.221 | 2564.221 | 0.126407 | 0.00002243 | 73.261 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2564.22 | 2564.22 | 0.126407 | 21.11 | 13.49 | 0.00789852 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.11 | 0.00789852 | 44.3623 | 2564.22 | 0.00 | 2764.30 | 2764.30 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 16420.066 | -999.000 | 1.655058 | 0.00058648 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | 7/21 14:00:00 | 16420.07 | 16070.19 | 1.655058 | 21.76 | 14.33 | 0.00860646 | 12.80 | 10.89 | 0.00850000 | 33.40 | 0.00630683 | 16.37 | 0.0000 | 21.11 | 0.00860646 | 48.2843 | 14784.13 | 0.00 | 18793.96 | 17741.61 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 12328.959 | 12328.959 | 0.607777 | 0.00010786 | 352.244 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12328.96 | 12328.96 | 0.607777 | 21.11 | 13.49 | 0.00790275 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.11 | 0.00790275 | 44.3855 | 12328.96 | 0.00 | 13290.97 | 13290.97 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 13976.278 | 13976.278 | 1.165991 | 0.00012227 | 317.980 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 13976.28 | 13976.28 | 1.165991 | 16.70 | 11.94 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00792536 | 44.8148 | 8592.98 | 0.00 | 14051.52 | 14051.52 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14427.770 | 14427.770 | 1.223708 | 0.00012622 | 327.448 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 14427.77 | 14427.77 | 1.223708 | 16.70 | 11.94 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00792691 | 44.8235 | 8777.98 | 0.00 | 14505.51 | 14505.51 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 9840.341 | 9840.341 | 1.205947 | 0.00008609 | 213.740 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 9840.34 | 9840.34 | 1.205947 | 16.70 | 11.94 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00763621 | 43.2031 | 4277.20 | 0.00 | 9894.92 | 9894.92 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 11122.771 | 11122.771 | 0.444532 | 0.00009731 | 303.568 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11122.77 | 11122.77 | 0.444532 | 16.70 | 11.94 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00793794 | 44.8848 | 9070.32 | 0.00 | 11177.93 | 11177.93 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 461637.529 | -999.000 | 24.112193 | 0.01648862 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 461637.53 | 461637.53 | 24.112193 | 28.54 | 16.17 | 0.00804799 | 10.71 | 9.60 | 0.00804799 | 33.40 | 0.00630683 | 16.37 | 48.3633 | 23.99 | 0.00966379 | 45.4349 | 290034.30 | 0.00 | 511828.24 | 480562.22 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 339119.446 | 339119.446 | 7.233658 | 0.00296676 | 4886.976 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 339119.45 | 339119.45 | 7.233658 | -27.60 | -27.60 | 0.00034190 | 16.70 | 11.94 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 161.2111 | 21.00 | 0.00788706 | 44.6009 | 86985.09 | 0.00 | 245894.94 | 245894.94 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 47434.827 | -999.000 | 2.051317 | 0.00169426 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 47434.83 | 47434.83 | 2.051317 | 33.40 | 16.37 | 0.00630683 | 11.80 | 8.26 | 0.00630683 | 33.40 | 0.00630683 | 16.37 | 99.9965 | 21.11 | 0.00860790 | 48.2914 | 174756.72 | 0.00 | 40214.66 | 40214.66 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 28850.199 | 28850.199 | 0.615395 | 0.00025239 | 415.754 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 28850.20 | 28850.20 | 0.615395 | -27.60 | -27.60 | 0.00034190 | 16.70 | 11.94 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 333.3216 | 21.11 | 0.00788225 | 44.2713 | 143436.73 | 0.00 | 20919.23 | 20919.23 |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 835.512 | 614.937 | 4.903586 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 75921.46 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 688.224 | 506.533 | 3.872570 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 54370.95 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 7828.339 | 7828.339 | 1.128324 | 0.00006849 | 167.624 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 1.1742 | 1.197877 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7828.34 | 7828.34 | 1.0000 | 1.18828266 | 1.128324 | 16.70 | 11.94 | 0.00800000 | 37036.7 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.06847874 | 60.00 | 32.22 | 27.78 | 0.000 | 7828.34 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00799929 | 21.00 | 0.00799929 | 45.2270 | 2618.01 | 0.00 | 7871.94 | 7871.94 | 1.18828266 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.10 | 15.63 | 0.00800000 | 43559.4 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4638.424 | 4638.424 | 0.219402 | 0.00004058 | 119.376 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 0.6958 | 0.709763 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 4638.42 | 4638.42 | 1.0000 | 0.23106066 | 0.219402 | 16.70 | 11.94 | 0.00800000 | 37036.7 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.04057482 | 60.00 | 32.22 | 27.78 | 0.000 | 4638.42 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00787602 | 21.00 | 0.00787602 | 44.5401 | 3625.63 | 0.00 | 4661.85 | 4661.85 | 0.23106066 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 36.39 | 20.09 | 0.00800000 | 57110.6 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1725.325 | 1725.325 | 0.119537 | 0.00001509 | 40.497 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 0.2588 | 0.264006 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1725.32 | 1725.32 | 1.0000 | 0.12588894 | 0.119537 | 16.70 | 11.94 | 0.00800000 | 37036.7 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.01509235 | 60.00 | 32.22 | 27.78 | 0.000 | 1725.32 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00785260 | 21.00 | 0.00785260 | 44.4085 | 1173.50 | 0.00 | 1734.52 | 1734.52 | 0.12588894 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.11 | 18.07 | 0.00800000 | 50712.9 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2639.473 | 2639.473 | 0.105493 | 0.00002309 | 72.037 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 0.3959 | 0.403887 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2639.47 | 2639.47 | 1.0000 | 0.11109935 | 0.105493 | 16.70 | 11.94 | 0.00800000 | 37036.7 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.02308891 | 60.00 | 32.22 | 27.78 | 0.000 | 2639.47 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00781113 | 21.00 | 0.00781113 | 44.1770 | 2152.52 | 0.00 | 2652.56 | 2652.56 | 0.11109935 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60810.3 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1768.500 | 1768.500 | 0.070682 | 0.00001547 | 48.266 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 0.2653 | 0.270612 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1768.50 | 1768.50 | 1.0000 | 0.07443814 | 0.070682 | 16.70 | 11.94 | 0.00800000 | 37036.7 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.01547003 | 60.00 | 32.22 | 27.78 | 0.000 | 1768.50 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00783680 | 21.00 | 0.00783680 | 44.3204 | 1442.22 | 0.00 | 1777.27 | 1777.27 | 0.07443814 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.01 | 21.19 | 0.00800000 | 60810.5 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11068.830 | 11068.830 | 1.789997 | 0.00009683 | 234.958 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 1.6603 | 1.693731 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11068.83 | 11068.83 | 1.0000 | 1.88511709 | 1.789997 | 16.70 | 11.94 | 0.00800000 | 37036.7 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.09682507 | 60.00 | 32.22 | 27.78 | 0.000 | 11068.83 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00780247 | 21.00 | 0.00780247 | 44.1295 | 2807.07 | 0.00 | 11130.66 | 11130.66 | 1.88511709 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.39 | 15.37 | 0.00800000 | 42839.2 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13384.607 | 13384.607 | 0.904424 | 0.00011709 | 315.666 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 2.0077 | 2.048086 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 13384.61 | 13384.61 | 1.0000 | 0.95248513 | 0.904424 | 16.70 | 11.94 | 0.00800000 | 37036.7 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.11708243 | 60.00 | 32.22 | 27.78 | 0.000 | 13384.61 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00789187 | 21.00 | 0.00789187 | 44.6284 | 9209.41 | 0.00 | 13455.85 | 13455.85 | 0.95248513 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.45 | 18.19 | 0.00800000 | 51061.8 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 33556.046 | 33556.046 | 2.653782 | 0.00029356 | 769.784 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 5.0334 | 5.134681 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 33556.05 | 33556.05 | 1.0000 | 2.79480357 | 2.653782 | 16.70 | 11.94 | 0.00800000 | 37036.7 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.29353299 | 60.00 | 32.22 | 27.78 | 0.000 | 33556.05 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00786690 | 21.00 | 0.00786690 | 44.4884 | 21305.04 | 0.00 | 33736.18 | 33736.18 | 2.79480357 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.44 | 17.51 | 0.00800000 | 49005.8 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12744.881 | -999.000 | 1.302447 | 0.00045521 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7444 | 1004.8586 | 1.0531 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.302447 | 1.37165854 | 4197.9300 | 999.8980 | 25.61216550 | 13.37 | 6.70 | 6.67 | 717145.58 | 1.7772 | 1.777135 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | Sensible | 12744.88 | 12601.59 | 1.0000 | 1.37165854 | 1.302447 | 21.77 | 14.29 | 0.00855560 | 43613.8 | 12.80 | 10.89 | 0.00850000 | 34322.2 | 0.45516267 | 6.70 | 13.37 | 6.67 | 0.000 | 12744.88 | 30.63 | 0.00630253 | 15.45 | 0.00000000 | 0.0000 | 21.11 | 0.00855560 | 21.11 | 0.00855560 | 48.0021 | 11634.69 | 0.00 | 14601.00 | 13951.00 | 1.37165854 | 21.77 | 15.63 | 0.00855560 | 43613.8 | 11.80 | 11.55 | 0.00836777 | 32969.0 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8139.819 | 8139.819 | 0.401263 | 0.00007121 | 232.562 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.302447 | 1.37165854 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 1.2210 | 1.245539 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8139.82 | 8139.82 | 1.0000 | 0.42258627 | 0.401263 | 21.11 | 13.47 | 0.00787259 | 41210.4 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.07120343 | 60.00 | 32.22 | 27.78 | 0.000 | 8139.82 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.11 | 0.00787259 | 21.11 | 0.00787259 | 44.2185 | 8139.82 | 0.00 | 8774.94 | 8774.94 | 0.42258627 | 16.60 | 13.03 | 0.00787259 | 36612.2 | 36.97 | 20.17 | 0.00787259 | 57377.0 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12160.125 | -999.000 | 1.241837 | 0.00043432 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7491 | 1004.8586 | 1.0531 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.241837 | 1.30782801 | 4197.9300 | 999.8980 | 25.61216550 | 13.37 | 6.70 | 6.67 | 717145.58 | 1.6956 | 1.695597 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | unknown | unknown | unknown | 7/21 17:30:00 | Sensible | 12160.12 | 12017.31 | 1.0000 | 1.30782801 | 1.241837 | 21.77 | 14.29 | 0.00855811 | 43620.1 | 12.80 | 10.89 | 0.00850000 | 34322.2 | 0.43427906 | 6.70 | 13.37 | 6.67 | 0.000 | 12160.12 | 30.36 | 0.00630211 | 15.36 | 0.00000000 | 0.0000 | 21.11 | 0.00855811 | 21.11 | 0.00855811 | 48.0160 | 11093.26 | 0.00 | 13930.44 | 13302.30 | 1.30782801 | 21.77 | 15.64 | 0.00855811 | 43620.1 | 11.80 | 11.55 | 0.00836774 | 32968.6 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8144.697 | 8144.697 | 0.401504 | 0.00007125 | 232.702 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.241837 | 1.30782801 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 1.2217 | 1.246286 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8144.70 | 8144.70 | 1.0000 | 0.42283949 | 0.401504 | 21.11 | 13.47 | 0.00787267 | 41210.6 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.07124609 | 60.00 | 32.22 | 27.78 | 0.000 | 8144.70 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.11 | 0.00787267 | 21.11 | 0.00787267 | 44.2190 | 8144.70 | 0.00 | 8780.20 | 8780.20 | 0.42283949 | 16.60 | 13.03 | 0.00787267 | 36612.4 | 36.97 | 20.17 | 0.00787267 | 57377.2 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 75491.453 | -999.000 | 7.833628 | 0.00269633 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6263 | 1004.8586 | 1.0531 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.833628 | 8.24990632 | 4197.9300 | 999.8980 | 25.61216550 | 13.37 | 6.70 | 6.67 | 717145.58 | 10.5267 | 10.526460 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | unknown | unknown | 7/21 14:00:00 | Sensible | 75491.45 | 75491.45 | 1.0000 | 8.24990632 | 7.833628 | 21.77 | 14.24 | 0.00849203 | 43452.7 | 12.80 | 10.89 | 0.00849203 | 34302.1 | 2.69605437 | 6.70 | 13.37 | 6.67 | 0.000 | 75491.45 | 33.40 | 0.00630683 | 16.37 | 0.00000000 | 0.0000 | 21.11 | 0.00849203 | 21.11 | 0.00849203 | 47.6492 | 69980.45 | 0.00 | 86584.00 | 83935.32 | 8.24990632 | 21.77 | 15.58 | 0.00849203 | 43452.7 | 11.80 | 11.55 | 0.00836477 | 32957.5 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 46639.645 | 46639.645 | 2.299199 | 0.00040802 | 1332.535 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.833628 | 8.24990632 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 6.9959 | 7.136707 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 46639.64 | 46639.64 | 1.0000 | 2.42137866 | 2.299199 | 21.11 | 13.47 | 0.00788197 | 41234.6 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.40798234 | 60.00 | 32.22 | 27.78 | 0.000 | 46639.64 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.11 | 0.00788197 | 21.11 | 0.00788197 | 44.2698 | 46639.64 | 0.00 | 50279.00 | 50279.00 | 2.42137866 | 16.60 | 13.04 | 0.00788197 | 36635.9 | 36.97 | 20.18 | 0.00788197 | 57400.5 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 62507.814 | -999.000 | 6.060009 | 0.00223259 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1126 | 1004.8586 | 1.0531 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.060009 | 6.38203712 | 4197.9300 | 999.8980 | 25.61216550 | 13.37 | 6.70 | 6.67 | 717145.58 | 8.7162 | 8.716033 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | unknown | unknown | unknown | 7/21 19:30:00 | Sensible | 62507.81 | 59425.19 | 1.0000 | 6.38203712 | 6.060009 | 21.76 | 14.46 | 0.00875366 | 44116.5 | 12.80 | 10.89 | 0.00850000 | 34322.2 | 2.23236483 | 6.70 | 13.37 | 6.67 | 0.000 | 62507.81 | 26.28 | 0.00629588 | 13.94 | 0.00000000 | 0.0000 | 21.11 | 0.00875366 | 21.11 | 0.00875366 | 49.0989 | 54131.52 | 0.00 | 71375.25 | 65122.70 | 6.38203712 | 21.76 | 15.81 | 0.00875366 | 44116.5 | 11.77 | 11.54 | 0.00836532 | 32932.8 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 46748.548 | 46748.548 | 2.304568 | 0.00040898 | 1335.646 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.060009 | 6.38203712 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 7.0122 | 7.153372 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 46748.55 | 46748.55 | 1.0000 | 2.42703258 | 2.304568 | 21.11 | 13.48 | 0.00788221 | 41235.2 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.40893497 | 60.00 | 32.22 | 27.78 | 0.000 | 46748.55 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.11 | 0.00788221 | 21.11 | 0.00788221 | 44.2711 | 46748.55 | 0.00 | 50396.40 | 50396.40 | 2.42703258 | 16.60 | 13.04 | 0.00788221 | 36636.5 | 36.97 | 20.18 | 0.00788221 | 57401.1 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11381.068 | -999.000 | 1.160995 | 0.00040650 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7566 | 1004.8586 | 1.0531 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.160995 | 1.22269017 | 4197.9300 | 999.8980 | 25.61216550 | 13.37 | 6.70 | 6.67 | 717145.58 | 1.5870 | 1.586966 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | unknown | unknown | unknown | 7/21 10:10:00 | Sensible | 11381.07 | 11238.23 | 1.0000 | 1.22269017 | 1.160995 | 21.77 | 14.30 | 0.00856215 | 43630.4 | 12.80 | 10.89 | 0.00850000 | 34322.2 | 0.40645632 | 6.70 | 13.37 | 6.67 | 0.000 | 11381.07 | 27.72 | 0.00629806 | 14.45 | 0.00000000 | 0.0000 | 21.11 | 0.00856215 | 21.11 | 0.00856215 | 48.0384 | 10371.10 | 0.00 | 13036.99 | 12437.12 | 1.22269017 | 21.77 | 15.64 | 0.00856215 | 43630.4 | 11.80 | 11.55 | 0.00836769 | 32967.9 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8150.449 | 8150.449 | 0.401787 | 0.00007130 | 232.866 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.160995 | 1.22269017 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 1.2226 | 1.247166 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8150.45 | 8150.45 | 1.0000 | 0.42313812 | 0.401787 | 21.11 | 13.47 | 0.00787275 | 41210.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.07129641 | 60.00 | 32.22 | 27.78 | 0.000 | 8150.45 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.11 | 0.00787275 | 21.11 | 0.00787275 | 44.2194 | 8150.45 | 0.00 | 8786.40 | 8786.40 | 0.42313812 | 16.60 | 13.03 | 0.00787275 | 36612.6 | 36.97 | 20.17 | 0.00787275 | 57377.4 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10821.231 | -999.000 | 1.102928 | 0.00038650 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7625 | 1004.8586 | 1.0531 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.102928 | 1.16153734 | 4197.9300 | 999.8980 | 25.61216550 | 13.37 | 6.70 | 6.67 | 717145.58 | 1.5089 | 1.508903 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | unknown | unknown | unknown | 7/21 09:30:00 | Sensible | 10821.23 | 10678.56 | 1.0000 | 1.16153734 | 1.102928 | 21.77 | 14.30 | 0.00856534 | 43638.5 | 12.80 | 10.89 | 0.00850000 | 34322.2 | 0.38646267 | 6.70 | 13.37 | 6.67 | 0.000 | 10821.23 | 25.96 | 0.00629539 | 13.83 | 0.00000000 | 0.0000 | 21.11 | 0.00856534 | 21.11 | 0.00856534 | 48.0560 | 9852.39 | 0.00 | 12394.97 | 11815.66 | 1.16153734 | 21.77 | 15.64 | 0.00856534 | 43638.5 | 11.80 | 11.55 | 0.00836765 | 32967.3 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8155.325 | 8155.325 | 0.402028 | 0.00007135 | 233.005 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.102928 | 1.16153734 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 1.2233 | 1.247912 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8155.33 | 8155.33 | 1.0000 | 0.42339129 | 0.402028 | 21.11 | 13.47 | 0.00787284 | 41211.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.07133907 | 60.00 | 32.22 | 27.78 | 0.000 | 8155.33 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.11 | 0.00787284 | 21.11 | 0.00787284 | 44.2199 | 8155.33 | 0.00 | 8791.65 | 8791.65 | 0.42339129 | 16.60 | 13.03 | 0.00787284 | 36612.8 | 36.97 | 20.17 | 0.00787284 | 57377.6 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16134.601 | 16134.601 | 0.703558 | 0.00014115 | 426.423 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 2.4202 | 2.468885 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 16134.60 | 16134.60 | 1.0000 | 0.74094541 | 0.703558 | 16.70 | 11.94 | 0.00800000 | 37036.7 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.14113813 | 60.00 | 32.22 | 27.78 | 0.000 | 16134.60 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00790173 | 21.00 | 0.00790173 | 44.6826 | 12886.38 | 0.00 | 16215.33 | 16215.33 | 0.74094541 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 38.06 | 20.60 | 0.00800000 | 58819.4 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3357.768 | -999.000 | 0.343408 | 0.00011993 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7392 | 1004.8586 | 1.0531 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.343408 | 0.36165709 | 4197.9300 | 999.8980 | 25.61216550 | 13.37 | 6.70 | 6.67 | 717145.58 | 0.4682 | 0.468204 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | Sensible | 3357.77 | 3321.92 | 1.0000 | 0.36165709 | 0.343408 | 21.77 | 14.29 | 0.00855277 | 43606.6 | 12.80 | 10.89 | 0.00850000 | 34322.2 | 0.11991724 | 6.70 | 13.37 | 6.67 | 0.000 | 3357.77 | 30.63 | 0.00630253 | 15.45 | 0.00000000 | 0.0000 | 21.11 | 0.00855277 | 21.11 | 0.00855277 | 47.9865 | 3067.65 | 0.00 | 3846.98 | 3678.22 | 0.36165709 | 21.77 | 15.63 | 0.00855277 | 43606.6 | 11.80 | 11.55 | 0.00836781 | 32969.5 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2565.064 | 2565.064 | 0.126448 | 0.00002244 | 73.285 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.343408 | 0.36165709 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 0.3848 | 0.392501 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2565.06 | 2565.06 | 1.0000 | 0.13316783 | 0.126448 | 21.11 | 13.49 | 0.00789855 | 41276.4 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.02243801 | 60.00 | 32.22 | 27.78 | 0.000 | 2565.06 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.11 | 0.00789855 | 21.11 | 0.00789855 | 44.3625 | 2565.06 | 0.00 | 2765.21 | 2765.21 | 0.13316783 | 16.60 | 13.05 | 0.00789855 | 36677.9 | 36.97 | 20.19 | 0.00789855 | 57442.7 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3192.704 | -999.000 | 0.326298 | 0.00011403 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7440 | 1004.8586 | 1.0531 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.326298 | 0.34363720 | 4197.9300 | 999.8980 | 25.61216550 | 13.37 | 6.70 | 6.67 | 717145.58 | 0.4452 | 0.445188 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | unknown | unknown | unknown | 7/21 17:30:00 | Sensible | 3192.70 | 3156.98 | 1.0000 | 0.34363720 | 0.326298 | 21.77 | 14.29 | 0.00855534 | 43613.1 | 12.80 | 10.89 | 0.00850000 | 34322.2 | 0.11402224 | 6.70 | 13.37 | 6.67 | 0.000 | 3192.70 | 30.36 | 0.00630211 | 15.36 | 0.00000000 | 0.0000 | 21.11 | 0.00855534 | 21.11 | 0.00855534 | 48.0007 | 2914.80 | 0.00 | 3657.70 | 3495.09 | 0.34363720 | 21.77 | 15.63 | 0.00855534 | 43613.1 | 11.80 | 11.55 | 0.00836778 | 32969.0 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2564.221 | 2564.221 | 0.126407 | 0.00002243 | 73.261 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.326298 | 0.34363720 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 0.3846 | 0.392372 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2564.22 | 2564.22 | 1.0000 | 0.13312405 | 0.126407 | 21.11 | 13.49 | 0.00789852 | 41276.3 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.02243063 | 60.00 | 32.22 | 27.78 | 0.000 | 2564.22 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.11 | 0.00789852 | 21.11 | 0.00789852 | 44.3623 | 2564.22 | 0.00 | 2764.30 | 2764.30 | 0.13312405 | 16.60 | 13.05 | 0.00789852 | 36677.8 | 36.97 | 20.19 | 0.00789852 | 57442.6 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16420.066 | -999.000 | 1.655058 | 0.00058648 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8390 | 1004.8586 | 1.0531 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.655058 | 1.74300707 | 4197.9300 | 999.8980 | 25.61216550 | 13.37 | 6.70 | 6.67 | 717145.58 | 2.2896 | 2.289599 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | unknown | unknown | 7/21 14:00:00 | Sensible | 16420.07 | 16070.19 | 1.0000 | 1.74300707 | 1.655058 | 21.76 | 14.33 | 0.00860646 | 43742.7 | 12.80 | 10.89 | 0.00850000 | 34322.2 | 0.58641595 | 6.70 | 13.37 | 6.67 | 0.000 | 16420.07 | 33.40 | 0.00630683 | 16.37 | 0.00000000 | 0.0000 | 21.11 | 0.00860646 | 21.11 | 0.00860646 | 48.2843 | 14784.13 | 0.00 | 18793.96 | 17741.61 | 1.74300707 | 21.76 | 15.68 | 0.00860646 | 43742.7 | 11.79 | 11.55 | 0.00836715 | 32960.2 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12328.959 | 12328.959 | 0.607777 | 0.00010786 | 352.244 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.655058 | 1.74300707 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 1.8493 | 1.886553 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 12328.96 | 12328.96 | 1.0000 | 0.64007371 | 0.607777 | 21.11 | 13.49 | 0.00790275 | 41287.2 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.10784811 | 60.00 | 32.22 | 27.78 | 0.000 | 12328.96 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.11 | 0.00790275 | 21.11 | 0.00790275 | 44.3855 | 12328.96 | 0.00 | 13290.97 | 13290.97 | 0.64007371 | 16.60 | 13.06 | 0.00790275 | 36688.5 | 36.97 | 20.20 | 0.00790275 | 57453.3 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13976.278 | 13976.278 | 1.165991 | 0.00012227 | 317.980 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 2.0964 | 2.138623 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 13976.28 | 13976.28 | 1.0000 | 1.22795146 | 1.165991 | 16.70 | 11.94 | 0.00800000 | 37036.7 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.12225810 | 60.00 | 32.22 | 27.78 | 0.000 | 13976.28 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00792536 | 21.00 | 0.00792536 | 44.8148 | 8592.98 | 0.00 | 14051.52 | 14051.52 | 1.22795146 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.82 | 17.30 | 0.00800000 | 48377.8 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14427.770 | 14427.770 | 1.223708 | 0.00012622 | 327.448 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 2.1642 | 2.207709 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 14427.77 | 14427.77 | 1.0000 | 1.28873533 | 1.223708 | 16.70 | 11.94 | 0.00800000 | 37036.7 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.12620755 | 60.00 | 32.22 | 27.78 | 0.000 | 14427.77 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00792691 | 21.00 | 0.00792691 | 44.8235 | 8777.98 | 0.00 | 14505.51 | 14505.51 | 1.28873533 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.64 | 17.24 | 0.00800000 | 48190.4 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9840.341 | 9840.341 | 1.205947 | 0.00008609 | 213.740 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 1.4760 | 1.505750 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 9840.34 | 9840.34 | 1.0000 | 1.27003111 | 1.205947 | 16.70 | 11.94 | 0.00800000 | 37036.7 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.08607881 | 60.00 | 32.22 | 27.78 | 0.000 | 9840.34 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.77 | 0.00763621 | 21.00 | 0.00763621 | 43.2031 | 4277.20 | 0.00 | 9894.92 | 9894.92 | 1.27003111 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.24 | 16.04 | 0.00800000 | 44725.8 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11122.771 | 11122.771 | 0.444532 | 0.00009731 | 303.568 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 1.6684 | 1.701985 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11122.77 | 11122.77 | 1.0000 | 0.46815405 | 0.444532 | 16.70 | 11.94 | 0.00800000 | 37036.7 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.09729693 | 60.00 | 32.22 | 27.78 | 0.000 | 11122.77 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00793794 | 21.00 | 0.00793794 | 44.8848 | 9070.32 | 0.00 | 11177.93 | 11177.93 | 0.46815405 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 40.02 | 21.19 | 0.00800000 | 60811.3 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 461637.529 | -999.000 | 24.112193 | 0.01648862 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.8008 | 1004.8586 | 1.0531 | VAV WITH REHEAT FAN | Fan:VariableVolume | 24.112193 | 25.39351165 | 4197.9300 | 999.8980 | 25.61216550 | 13.37 | 6.70 | 6.67 | 717145.58 | 64.3715 | 64.371523 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | Sensible | 461637.53 | 461637.53 | 1.0000 | 25.39351165 | 24.112193 | 28.54 | 16.17 | 0.00804799 | 49232.8 | 10.71 | 9.60 | 0.00804799 | 31053.4 | 16.48694089 | 6.70 | 13.37 | 6.67 | 54026.710 | 407610.82 | 33.40 | 0.00630683 | 16.37 | 11.66146000 | 48.3633 | 23.99 | 0.00967878 | 23.99 | 0.00966379 | 45.4349 | 290034.30 | 0.00 | 511828.24 | 480562.22 | 25.39351165 | 28.54 | 17.59 | 0.00804799 | 49232.8 | 9.98 | 9.92 | 0.00755930 | 29076.9 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 339119.446 | 339119.446 | 7.233658 | 0.00296676 | 4886.976 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV WITH REHEAT FAN | Fan:VariableVolume | 24.112193 | 25.39351165 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 50.8677 | 51.891396 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 339119.45 | 339119.45 | 1.0000 | 7.61805350 | 7.233658 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 16.70 | 11.94 | 0.00800000 | 37036.7 | 2.96646221 | 60.00 | 32.22 | 27.78 | 0.000 | 339119.45 | -27.60 | 0.00034190 | -27.60 | 11.66146000 | 161.2111 | 20.98 | 0.00788950 | 21.00 | 0.00788706 | 44.6009 | 86985.09 | 0.00 | 245894.94 | 245894.94 | 7.61805350 | 2.80 | -3.89 | 0.00034190 | 3670.4 | 34.90 | 12.93 | 0.00034190 | 35948.3 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 47434.827 | -999.000 | 2.051317 | 0.00169426 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1016.5641 | 1004.8586 | 1.0531 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.16024804 | 4197.9300 | 999.8980 | 25.61216550 | 13.37 | 6.70 | 6.67 | 717145.58 | 6.6144 | 6.614393 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 47434.83 | 47434.83 | 1.0000 | 2.16032399 | 2.051317 | 33.40 | 16.37 | 0.00630683 | 49726.3 | 11.80 | 8.26 | 0.00630683 | 27769.0 | 1.69408927 | 6.70 | 13.37 | 6.67 | 2195.006 | 45239.82 | 33.40 | 0.00630683 | 16.37 | 2.05124512 | 99.9965 | 21.11 | 0.00860113 | 21.11 | 0.00860790 | 48.2914 | 174756.72 | 0.00 | 40214.66 | 40214.66 | 2.16032399 | 33.40 | 17.79 | 0.00630683 | 49726.3 | 15.09 | 10.82 | 0.00630683 | 31111.1 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 28850.199 | 28850.199 | 0.615395 | 0.00025239 | 415.754 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.16024804 | 4197.9300 | 999.8980 | 5.71667451 | 54.44 | 82.22 | 27.78 | 666669.98 | 4.3275 | 4.414601 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 28850.20 | 28850.20 | 1.0000 | 0.64809720 | 0.615395 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 16.70 | 11.94 | 0.00800000 | 37036.7 | 0.25236838 | 60.00 | 32.22 | 27.78 | 0.000 | 28850.20 | -27.60 | 0.00034190 | -27.60 | 2.05124512 | 333.3216 | 21.11 | 0.00788233 | 21.11 | 0.00788225 | 44.2713 | 143436.73 | 0.00 | 20919.23 | 20919.23 | 0.64809720 | 2.80 | -3.89 | 0.00034190 | 3670.4 | 34.90 | 12.93 | 0.00034190 | 35948.3 | |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 835.512 | 614.937 | 4.903586 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 1.0531 | SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 4.903586 | 5.16416250 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 75921.46 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 75921.46 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 688.224 | 506.533 | 3.872570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 1.0531 | SWHSYS1 HPWH FAN | Fan:SystemModel | 3.872570 | 4.07835743 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 54370.95 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54370.95 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 24.11 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 155.17 | 8186.50 | 114.50 |
RETAIL_1_FLR_1 | 2598.33 | 7284.50 | 1744.33 |
RETAIL_2_FLR_1 | 885.83 | 6963.83 | 491.17 |
MECH_FLR_1 | 1258.50 | 8090.83 | 1165.83 |
STORAGE_FLR_1 | 1493.17 | 8346.83 | 1447.17 |
LAUNDRY_FLR_1 | 7103.50 | 3111.67 | 2345.33 |
CAFE_FLR_1 | 2667.67 | 5664.00 | 684.50 |
LOBBY_FLR_1 | 1479.83 | 5414.17 | 327.50 |
ROOM_1_FLR_3 | 2178.67 | 8284.00 | 2061.33 |
ROOM_2_FLR_3 | 3097.67 | 8142.00 | 2832.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1453.67 | 8751.83 | 1453.67 |
ROOM_5_FLR_3 | 2140.33 | 8180.33 | 2024.83 |
ROOM_6_FLR_3 | 2898.17 | 8113.67 | 2733.83 |
CORRIDOR_FLR_3 | 1368.83 | 8211.50 | 1308.00 |
ROOM_1_FLR_6 | 3044.33 | 8225.17 | 2852.67 |
ROOM_2_FLR_6 | 3937.67 | 8093.50 | 3628.83 |
ROOM_3_MULT9_FLR_6 | 1649.50 | 8002.50 | 1427.83 |
BANQUET_FLR_6 | 2852.17 | 3337.83 | 281.33 |
DINING_FLR_6 | 3460.67 | 2086.50 | 200.33 |
KITCHEN_FLR_6 | 7996.17 | 6043.83 | 5731.50 |
CORRIDOR_FLR_6 | 1745.67 | 7867.33 | 1516.00 |
Facility | 8748.17 | 8760.00 | 7519.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 15.00 | 0.00 | 15.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 2.50 | 0.00 | 2.50 | 0.00 |
CAFE_FLR_1 | 3.33 | 0.00 | 3.33 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 3.83 | 0.00 | 3.83 |
ROOM_2_FLR_3 | 0.00 | 7.67 | 0.00 | 7.67 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1.33 | 17.83 | 1.33 | 17.83 |
ROOM_5_FLR_3 | 0.00 | 4.67 | 0.00 | 4.67 |
ROOM_6_FLR_3 | 0.00 | 23.67 | 0.00 | 23.67 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 5.83 | 0.00 | 5.83 |
ROOM_2_FLR_6 | 0.00 | 11.17 | 0.00 | 11.17 |
ROOM_3_MULT9_FLR_6 | 0.00 | 8.33 | 0.00 | 8.33 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.33 | 0.00 | 0.33 | 0.00 |
CORRIDOR_FLR_6 | 0.83 | 0.00 | 0.83 | 0.00 |
Facility | 20.00 | 56.67 | 20.00 | 56.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.880 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 3.100 | 0.035 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.462 | 0.012 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.538 | 0.013 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.504 | 0.013 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 25.521 | 0.038 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 4.577 | 0.028 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.971 | 0.011 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.046 | 0.000 | 0.043 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.046 | 0.000 | 0.038 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.403 | 0.020 | 0.000 | 0.073 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.046 | 0.000 | 0.044 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.046 | 0.000 | 0.045 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.542 | 0.006 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.355 | 0.046 | 0.000 | 0.053 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.046 | 0.000 | 0.043 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.403 | 0.037 | 0.000 | 0.084 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 5.164 | 0.013 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 5.618 | 0.013 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 23.459 | 0.038 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.169 | 0.009 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.512 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.932 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.370 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.515 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.454 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 18.165 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 3.413 | 0.000 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.754 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.000 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.444 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.090 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.300 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 13.548 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.878 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.80 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.58 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.14 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.39 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 36618598.31 | 0.00 | 36618598.31 | 0.00 | 36618598.31 | 26946214.98 | 14.33 | 2.83 | 8742.83 | 0.00 |
RETAIL_1_FLR_1 | 7134903.00 | 0.00 | 7134903.00 | 80709.31 | 7215612.31 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3879232.26 | 0.00 | 3879232.26 | 31153.90 | 3910386.16 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 3027647.94 | 0.00 | 3027647.94 | 73629.31 | 3101277.25 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1638723.43 | 0.00 | 1638723.43 | 42480.05 | 1681203.49 | 1821682.01 | 8710.63 | 9.73 | 39.65 | 0.00 |
LAUNDRY_FLR_1 | 68048956.17 | 0.00 | 68048956.17 | 100537.06 | 68149493.22 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 29528181.28 | 0.00 | 29528181.28 | 178412.51 | 29706593.79 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 87934764.09 | 0.00 | 87934764.09 | 509765.29 | 88444529.38 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 44697.96 | 1504854.67 | 46846.27 | 1551700.94 | 1946875.62 | 2190.00 | 6152.33 | 417.67 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 38603.14 | 1498588.78 | 46842.70 | 1545431.48 | 1946647.51 | 2190.00 | 6237.23 | 332.77 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 0.00 | 1099911.97 | 13070.64 | 1112982.61 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.00 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 47001.32 | 19850830.62 | 13074.21 | 19863904.83 | 26405105.73 | 2190.00 | 6154.12 | 415.88 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 44754.88 | 1504911.60 | 46846.27 | 1551757.87 | 1946875.62 | 2190.00 | 6152.33 | 417.67 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 46204.64 | 1506190.27 | 46842.70 | 1553032.97 | 1946647.51 | 2190.00 | 6156.50 | 413.50 | 0.00 |
CORRIDOR_FLR_3 | 22262064.47 | 0.00 | 22262064.47 | 56646.57 | 22318711.04 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 54117.85 | 419157.03 | 46856.25 | 466013.29 | 486718.90 | 2073.38 | 6151.44 | 535.18 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 44170.66 | 409167.07 | 46852.68 | 456019.75 | 486661.88 | 2101.68 | 6254.66 | 403.66 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 54088.35 | 2399278.66 | 23973.30 | 2423251.96 | 3126920.42 | 2190.00 | 6151.00 | 419.00 | 0.00 |
BANQUET_FLR_6 | 44819781.78 | 0.00 | 44819781.78 | 114411.20 | 44934192.98 | 37458366.31 | 3199.51 | 170.23 | 5390.25 | 0.00 |
DINING_FLR_6 | 48754629.23 | 0.00 | 48754629.23 | 114411.20 | 48869040.43 | 37458366.31 | 0.00 | 0.00 | 8760.00 | 0.00 |
KITCHEN_FLR_6 | 63447553.23 | 0.00 | 63447553.23 | 102424.55 | 63549977.77 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12713089.19 | 0.00 | 12713089.19 | 100247.43 | 12813336.62 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 4854226.72 | 0.21E+10 | 4720756.77 | 0.21E+10 | 0.43E+10 | 8760.00 | 6678.96 | 8760.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.1612 | 0.0000 | 1.1612 | 0.0000 | 1.1612 | 0.8545 | 14.33 | 2.83 | 8742.83 |
RETAIL_1_FLR_1 | 0.2262 | 0.0000 | 0.2262 | 0.0026 | 0.2288 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1230 | 0.0000 | 0.1230 | 0.0010 | 0.1240 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.0960 | 0.0000 | 0.0960 | 0.0023 | 0.0983 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0520 | 0.0000 | 0.0520 | 0.0013 | 0.0533 | 0.0578 | 8710.63 | 9.73 | 39.65 |
LAUNDRY_FLR_1 | 2.1578 | 0.0000 | 2.1578 | 0.0032 | 2.1610 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.9363 | 0.0000 | 0.9363 | 0.0057 | 0.9420 | 0.6764 | 0.00 | 0.00 | 8760.00 |
LOBBY_FLR_1 | 2.7884 | 0.0000 | 2.7884 | 0.0162 | 2.8046 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0014 | 0.0477 | 0.0015 | 0.0492 | 0.0617 | 2190.00 | 6152.33 | 417.67 |
ROOM_2_FLR_3 | 0.0463 | 0.0012 | 0.0475 | 0.0015 | 0.0490 | 0.0617 | 2190.00 | 6237.23 | 332.77 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0015 | 0.6295 | 0.0004 | 0.6299 | 0.8373 | 2190.00 | 6154.12 | 415.88 |
ROOM_5_FLR_3 | 0.0463 | 0.0014 | 0.0477 | 0.0015 | 0.0492 | 0.0617 | 2190.00 | 6152.33 | 417.67 |
ROOM_6_FLR_3 | 0.0463 | 0.0015 | 0.0478 | 0.0015 | 0.0492 | 0.0617 | 2190.00 | 6156.50 | 413.50 |
CORRIDOR_FLR_3 | 0.7059 | 0.0000 | 0.7059 | 0.0018 | 0.7077 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0017 | 0.0133 | 0.0015 | 0.0148 | 0.0154 | 2073.38 | 6151.44 | 535.18 |
ROOM_2_FLR_6 | 0.0116 | 0.0014 | 0.0130 | 0.0015 | 0.0145 | 0.0154 | 2101.68 | 6254.66 | 403.66 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0017 | 0.0761 | 0.0008 | 0.0768 | 0.0992 | 2190.00 | 6151.00 | 419.00 |
BANQUET_FLR_6 | 1.4212 | 0.0000 | 1.4212 | 0.0036 | 1.4249 | 1.1878 | 3199.51 | 170.23 | 5390.25 |
DINING_FLR_6 | 1.5460 | 0.0000 | 1.5460 | 0.0036 | 1.5496 | 1.1878 | 0.00 | 0.00 | 8760.00 |
KITCHEN_FLR_6 | 2.0119 | 0.0000 | 2.0119 | 0.0032 | 2.0152 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.4031 | 0.0000 | 0.4031 | 0.0032 | 0.4063 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 64.9062 | 0.1539 | 65.0602 | 0.1182 | 65.1784 | 73.9670 | 8760.00 | 6678.96 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.48E+09 | 0.00 | 0.48E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 33072639.80 | 373638.80 | 33446278.60 | 64690340.46 | 8760.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 15.1161 | 0.0000 | 15.1161 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.0487 | 0.0118 | 1.0606 | 2.0513 | 8760.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 3608.16 | 0.00 | 0.00 | 0.00 | 5151.84 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 15.5842 | 0.0000 | 0.0000 | 0.0000 | 14.7912 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.3247 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1363 |
Defaulted Fields | 1208 |
Fields with Defaults | 4115 |
Autosized Fields | 353 |
Autosizable Fields | 407 |
Autocalculated Fields | 289 |
Autocalculatable Fields | 549 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 4996.00 | 68137.23 | 17-NOV-03:10 | 398764.63 | 17-JUL-18:20 |
Electricity:Building | 2337.89 | 30634.48 | 10-JUN-05:00 | 138695.41 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 256.48 | 3058.02 | 02-JAN-02:10 | 18903.76 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2330.80 | 30493.34 | 10-JUN-05:00 | 138454.08 | 02-JAN-20:10 |
InteriorLights:Electricity | 602.66 | 5211.16 | 10-JUN-05:00 | 50471.22 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 113.37 | 1030.12 | 02-JAN-02:10 | 9271.23 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 602.66 | 5211.16 | 10-JUN-05:00 | 50471.22 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 602.66 | 5211.16 | 10-JUN-05:00 | 50471.22 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 113.37 | 1030.12 | 02-JAN-02:10 | 9271.23 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 602.66 | 5211.16 | 10-JUN-05:00 | 50471.22 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 16.45 | 201.26 | 02-JAN-02:10 | 1197.92 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.26 | 56.92 | 02-JAN-02:10 | 512.31 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 19.05 | 233.06 | 02-JAN-02:10 | 1387.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.25 | 65.92 | 02-JAN-02:10 | 593.26 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.84 | 252.75 | 02-JAN-02:10 | 1523.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 8.37 | 76.02 | 02-JAN-02:10 | 684.18 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.46 | 67.94 | 02-JAN-02:10 | 394.77 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.87 | 16.96 | 02-JAN-02:10 | 152.61 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.87 | 16.96 | 02-JAN-02:10 | 152.61 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.84 | 1007.22 | 02-JAN-02:10 | 4973.49 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 27.06 | 303.18 | 03-JUN-05:00 | 2538.73 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 12.72 | 76.92 | 01-JAN-13:10 | 1573.46 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 12.72 | 76.92 | 01-JAN-13:10 | 1573.46 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 271.64 | 3232.42 | 03-JUN-05:00 | 20674.59 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 122.65 | 1121.01 | 03-JUN-05:00 | 10645.38 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 122.65 | 1121.01 | 03-JUN-05:00 | 10645.38 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 18.46 | 262.96 | 01-JAN-02:10 | 1214.21 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 18.46 | 262.93 | 01-JAN-02:10 | 1214.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 302.44 | 4545.27 | 01-JAN-02:10 | 20822.55 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 73.68 | 623.81 | 01-JAN-02:10 | 5671.40 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 73.68 | 623.81 | 01-JAN-02:10 | 5671.40 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 302.52 | 4546.52 | 01-JAN-02:10 | 20828.25 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 73.70 | 623.98 | 01-JAN-02:10 | 5672.95 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 73.70 | 623.98 | 01-JAN-02:10 | 5672.95 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 18.46 | 262.96 | 01-JAN-02:10 | 1214.21 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.96 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 18.46 | 262.93 | 01-JAN-02:10 | 1214.07 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 6.17 | 52.24 | 01-JAN-02:10 | 474.90 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 56.74 | 515.56 | 02-JAN-02:10 | 4640.01 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.62 | 65.74 | 01-JAN-02:10 | 303.55 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.74 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.74 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.62 | 65.73 | 01-JAN-02:10 | 303.52 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.73 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.54 | 13.06 | 01-JAN-02:10 | 118.73 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 35.82 | 538.40 | 01-JAN-02:10 | 2466.50 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 8.73 | 73.89 | 01-JAN-02:10 | 671.80 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 8.73 | 73.89 | 01-JAN-02:10 | 671.80 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 204.01 | 2433.51 | 10-JUN-05:00 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.15 | 184.21 | 10-JUN-05:00 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 28.15 | 184.21 | 10-JUN-05:00 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 204.01 | 2433.51 | 10-JUN-05:00 | 9511.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.15 | 184.21 | 10-JUN-05:00 | 2763.12 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 28.15 | 184.21 | 10-JUN-05:00 | 2763.12 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 444.45 | 5944.83 | 02-JAN-02:10 | 18636.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 15.01 | 136.41 | 02-JAN-02:10 | 1227.68 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 43.55 | 695.04 | 10-JAN-23:30 | 2785.10 | 16-JUL-10:10 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1130.32 | 1083.25 | 14-JAN-01:50 | 203081.11 | 17-JUL-18:20 |
LowTempRefrigeration:Refrigeration:Electricity | 15.70 | 0.00 | 01-JAN-11:10 | 1310.92 | 06-AUG-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 20.76 | 560.57 | 11-JAN-02:20 | 715.88 | 07-SEP-13:40 |
WaterSystems:Electricity | 469.03 | -167.02 | 24-JAN-02:20 | 41476.33 | 06-SEP-18:20 |
Electricity:HVAC | 734.69 | 12037.92 | 17-MAR-14:00 | 52175.60 | 08-AUG-21:10 |
Fans:Electricity | 532.78 | 10661.32 | 01-FEB-08:10 | 41399.61 | 08-AUG-21:10 |
General:Fans:Electricity | 532.78 | 10661.32 | 01-FEB-08:10 | 41399.61 | 08-AUG-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ExteriorEquipment:Electricity | 641.48 | 9451.24 | 02-JAN-02:20 | 39155.93 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 22.46 | 386.38 | 10-JUN-05:00 | 1283.34 | 12-MAY-20:10 |
ElectricityPurchased:Facility | 4996.00 | 68137.23 | 17-NOV-03:10 | 398764.63 | 17-JUL-18:20 |
ElectricityPurchased:Plant | 4996.00 | 68137.23 | 17-NOV-03:10 | 398764.63 | 17-JUL-18:20 |
Cogeneration:ElectricityPurchased | 4996.00 | 68137.23 | 17-NOV-03:10 | 398764.63 | 17-JUL-18:20 |
General:Cogeneration:ElectricityPurchased | 4996.00 | 68137.23 | 17-NOV-03:10 | 398764.63 | 17-JUL-18:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 4996.00 | 68137.23 | 17-NOV-03:10 | 398764.63 | 17-JUL-18:20 |
ElectricityNet:Plant | 4996.00 | 68137.23 | 17-NOV-03:10 | 398764.63 | 17-JUL-18:20 |
Cogeneration:ElectricityNet | 4996.00 | 68137.23 | 17-NOV-03:10 | 398764.63 | 17-JUL-18:20 |
General:Cogeneration:ElectricityNet | 4996.00 | 68137.23 | 17-NOV-03:10 | 398764.63 | 17-JUL-18:20 |
ExteriorLights:Electricity | 174.07 | 0.00 | 01-JAN-08:20 | 11096.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 174.07 | 0.00 | 01-JAN-08:20 | 11096.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 179.45 | 0.00 | 01-JAN-11:10 | 9938.94 | 31-MAY-16:20 |
General:HeatRecovery:Electricity | 179.45 | 0.00 | 01-JAN-11:10 | 9938.94 | 31-MAY-16:20 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.56 | 08-AUG-00:50 | 4739.91 | 09-JAN-07:30 |
Water Heater Parasitic:WaterSystems:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 537.67 | 0.00 | 01-JAN-00:10 | 163968.97 | 17-JUL-18:10 |
General:Cooling:Electricity | 537.67 | 0.00 | 01-JAN-00:10 | 163968.97 | 17-JUL-18:10 |
Pumps:Electricity | 87.17 | 47.91 | 12-MAR-17:40 | 6114.54 | 17-JUL-18:10 |
General:Pumps:Electricity | 87.17 | 47.91 | 12-MAR-17:40 | 6114.54 | 17-JUL-18:10 |
WIRED_LTG_ELECTRICITY | 21.21 | 0.00 | 01-JAN-00:10 | 1776.59 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5213.82 | 29270.80 | 25-APR-01:10 | 1140978.70 | 10-JAN-22:50 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 3424.98 | 15908.90 | 28-FEB-11:10 | 1097940.46 | 10-JAN-23:10 |
WaterSystems:NaturalGas | 1480.31 | 15908.90 | 01-FEB-11:10 | 195185.26 | 17-JAN-22:20 |
Water Heater:WaterSystems:NaturalGas | 1480.31 | 15908.90 | 01-FEB-11:10 | 195185.26 | 17-JAN-22:20 |
Heating:NaturalGas | 1944.67 | 0.00 | 01-JAN-15:40 | 924327.37 | 11-JAN-06:00 |
Boiler:Heating:NaturalGas | 1944.67 | 0.00 | 01-JAN-15:40 | 924327.37 | 11-JAN-06:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 1625.63 | 0.00 | 01-JAN-00:10 | 462375.85 | 17-JUL-18:20 |
PlantLoopCoolingDemand:HVAC | 1625.63 | 0.00 | 01-JAN-00:10 | 462375.85 | 17-JUL-18:20 |
CoolingCoils:PlantLoopCoolingDemand | 1625.63 | 0.00 | 01-JAN-00:10 | 462375.85 | 17-JUL-18:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-MAY-20:50 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-MAY-20:50 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-MAY-20:50 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-MAY-20:50 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-MAY-20:50 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-MAY-20:50 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 11-JAN-07:50 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 11-JAN-07:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 19292.72 | 145402.96 | 24-NOV-15:40 | 2134584.90 | 17-JUL-18:20 |
EnergyTransfer:Building | 4746.81 | 76572.57 | 03-FEB-11:10 | 366609.29 | 17-JUL-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 679.65 | 7893.31 | 10-JAN-04:00 | 35603.35 | 15-JUL-10:50 |
Refrigeration:EnergyTransfer | 178.70 | 3388.63 | 11-JAN-02:20 | 10240.69 | 13-JUN-06:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 89.35 | 1694.31 | 11-JAN-02:20 | 5120.34 | 13-JUN-06:20 |
General:Refrigeration:EnergyTransfer | 89.35 | 1694.31 | 11-JAN-02:20 | 5120.34 | 13-JUN-06:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 89.35 | 1694.31 | 11-JAN-02:20 | 5120.34 | 13-JUN-06:20 |
EnergyTransfer:Plant | 6310.88 | 16929.82 | 21-SEP-02:50 | 1146554.82 | 17-JUL-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.49 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 67.86 | 1469.75 | 11-JAN-02:20 | 2553.85 | 07-SEP-13:40 |
EnergyTransfer:HVAC | 8235.03 | 2213.12 | 24-NOV-15:20 | 843646.74 | 28-DEC-19:10 |
CoolingCoils:EnergyTransfer | 2712.37 | 0.00 | 01-JAN-00:10 | 575782.68 | 17-JUL-18:20 |
EnergyTransfer:Zone:BASEMENT | 310.80 | 6659.57 | 11-JAN-15:00 | 21042.24 | 28-JAN-01:00 |
Heating:EnergyTransfer | 237.27 | 0.00 | 01-JAN-08:10 | 143470.93 | 10-JAN-16:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 237.27 | 0.00 | 01-JAN-08:10 | 143470.93 | 10-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4420.18 | 46840.81 | 10-JAN-11:10 | 363081.45 | 17-JUL-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 310.80 | 6659.57 | 11-JAN-15:00 | 21042.24 | 28-JAN-01:00 |
General:Cooling:EnergyTransfer | 4420.18 | 46840.81 | 10-JAN-11:10 | 363081.45 | 17-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 310.80 | 6659.57 | 11-JAN-15:00 | 21042.24 | 28-JAN-01:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 41.77 | 0.05 | 14-FEB-07:50 | 4692.93 | 18-OCT-13:10 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 2.65 | 0.00 | 01-JAN-00:10 | 3233.62 | 11-JAN-07:40 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 2.65 | 0.00 | 01-JAN-00:10 | 3233.62 | 11-JAN-07:40 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 39.12 | 0.00 | 04-JAN-02:40 | 4692.93 | 18-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 39.12 | 0.00 | 04-JAN-02:40 | 4692.93 | 18-OCT-13:10 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 30.97 | 0.58 | 31-DEC-15:20 | 2163.60 | 17-JUL-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 172.42 | 09-JAN-12:20 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 172.42 | 09-JAN-12:20 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 30.96 | 0.00 | 08-JAN-15:00 | 2163.60 | 17-JUL-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 30.96 | 0.00 | 08-JAN-15:00 | 2163.60 | 17-JUL-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 21.17 | 0.00 | 25-DEC-18:00 | 1777.87 | 17-JUL-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 1.08 | 0.00 | 01-JAN-00:10 | 1211.31 | 11-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 1.08 | 0.00 | 01-JAN-00:10 | 1211.31 | 11-JAN-05:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 20.09 | 0.00 | 05-JAN-13:10 | 1777.87 | 17-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 20.09 | 0.00 | 05-JAN-13:10 | 1777.87 | 17-JUL-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 11.15 | 0.00 | 08-FEB-16:50 | 985.58 | 11-JAN-07:30 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 1.29 | 0.00 | 01-JAN-00:10 | 985.58 | 11-JAN-07:30 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 1.29 | 0.00 | 01-JAN-00:10 | 985.58 | 11-JAN-07:30 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 9.86 | 0.00 | 04-JAN-14:10 | 816.71 | 17-JUL-18:50 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 9.86 | 0.00 | 04-JAN-14:10 | 816.71 | 17-JUL-18:50 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 591.75 | 7596.40 | 30-JAN-02:30 | 39208.71 | 17-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 591.75 | 7596.40 | 30-JAN-02:30 | 39208.71 | 17-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 591.75 | 7596.40 | 30-JAN-02:30 | 39208.71 | 17-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 228.56 | 10.91 | 25-JAN-09:50 | 16271.74 | 18-OCT-14:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.23 | 0.00 | 01-JAN-00:10 | 3131.62 | 10-JAN-09:30 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.23 | 0.00 | 01-JAN-00:10 | 3131.62 | 10-JAN-09:30 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 228.33 | 0.00 | 05-JAN-14:20 | 16271.74 | 18-OCT-14:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 228.33 | 0.00 | 05-JAN-14:20 | 16271.74 | 18-OCT-14:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 746.74 | 476.02 | 09-JAN-12:30 | 43364.40 | 17-JUL-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 746.74 | 476.02 | 09-JAN-12:30 | 43364.40 | 17-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 746.74 | 476.02 | 09-JAN-12:30 | 43364.40 | 17-JUL-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 64.89 | 0.00 | 01-JAN-08:10 | 12921.21 | 16-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 22.10 | 0.00 | 01-JAN-08:10 | 8788.61 | 10-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 22.10 | 0.00 | 01-JAN-08:10 | 8788.61 | 10-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 42.79 | 0.00 | 01-JAN-00:10 | 12921.21 | 16-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 42.79 | 0.00 | 01-JAN-00:10 | 12921.21 | 16-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 57.72 | 0.00 | 01-JAN-08:10 | 12726.87 | 16-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 28.03 | 0.00 | 01-JAN-08:10 | 9095.34 | 10-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 28.03 | 0.00 | 01-JAN-08:10 | 9095.34 | 10-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 29.70 | 0.00 | 01-JAN-00:10 | 12726.87 | 16-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 29.70 | 0.00 | 01-JAN-00:10 | 12726.87 | 16-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 289.46 | 0.00 | 01-JAN-00:10 | 61739.03 | 18-OCT-13:00 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 6.74 | 0.00 | 01-JAN-00:10 | 30232.84 | 11-JAN-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 6.74 | 0.00 | 01-JAN-00:10 | 30232.84 | 11-JAN-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 282.72 | 0.00 | 01-JAN-00:10 | 61739.03 | 18-OCT-13:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 282.72 | 0.00 | 01-JAN-00:10 | 61739.03 | 18-OCT-13:00 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 336.51 | 0.00 | 01-JAN-08:10 | 67285.72 | 17-JUL-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 68.59 | 0.00 | 01-JAN-00:10 | 56259.18 | 09-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 68.59 | 0.00 | 01-JAN-00:10 | 56259.18 | 09-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 267.92 | 0.00 | 01-JAN-00:20 | 67285.72 | 17-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 267.92 | 0.00 | 01-JAN-00:20 | 67285.72 | 17-JUL-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 66.44 | 0.00 | 01-JAN-08:10 | 11173.87 | 17-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 22.00 | 0.00 | 01-JAN-08:10 | 8871.90 | 10-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 22.00 | 0.00 | 01-JAN-08:10 | 8871.90 | 10-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 44.44 | 0.00 | 01-JAN-00:10 | 11173.87 | 17-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 44.44 | 0.00 | 01-JAN-00:10 | 11173.87 | 17-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 59.12 | 0.00 | 01-JAN-08:10 | 12763.96 | 23-JUN-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 27.74 | 0.00 | 01-JAN-08:10 | 9180.10 | 10-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 27.74 | 0.00 | 01-JAN-08:10 | 9180.10 | 10-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 31.39 | 0.00 | 01-JAN-00:10 | 12763.96 | 23-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 31.39 | 0.00 | 01-JAN-00:10 | 12763.96 | 23-JUN-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 141.21 | 0.55 | 05-MAR-12:00 | 11471.34 | 17-JUL-18:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 7.02 | 0.00 | 01-JAN-00:10 | 7686.38 | 09-JAN-10:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 7.02 | 0.00 | 01-JAN-00:10 | 7686.38 | 09-JAN-10:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 134.19 | 0.00 | 04-JAN-07:10 | 11471.34 | 17-JUL-18:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 134.19 | 0.00 | 04-JAN-07:10 | 11471.34 | 17-JUL-18:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 19.13 | 0.00 | 01-JAN-08:10 | 3496.16 | 16-JUL-18:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 8.82 | 0.00 | 01-JAN-08:10 | 2796.19 | 10-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 8.82 | 0.00 | 01-JAN-08:10 | 2796.19 | 10-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.31 | 0.00 | 01-JAN-00:10 | 3496.16 | 16-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.31 | 0.00 | 01-JAN-00:10 | 3496.16 | 16-JUL-18:20 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 17.98 | 0.00 | 01-JAN-08:10 | 3472.41 | 31-MAY-16:30 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 10.78 | 0.00 | 01-JAN-08:10 | 2879.03 | 10-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 10.78 | 0.00 | 01-JAN-08:10 | 2879.03 | 10-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.20 | 0.00 | 01-JAN-00:10 | 3472.41 | 31-MAY-16:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.20 | 0.00 | 01-JAN-00:10 | 3472.41 | 31-MAY-16:30 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 96.61 | 0.00 | 01-JAN-08:10 | 18558.75 | 18-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 22.91 | 0.00 | 01-JAN-00:10 | 12824.18 | 10-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 22.91 | 0.00 | 01-JAN-00:10 | 12824.18 | 10-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 73.70 | 0.00 | 01-JAN-00:20 | 18558.75 | 18-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 73.70 | 0.00 | 01-JAN-00:20 | 18558.75 | 18-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 407.71 | 4356.87 | 09-JAN-10:20 | 23166.16 | 17-JUL-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 407.71 | 4356.87 | 09-JAN-10:20 | 23166.16 | 17-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 407.71 | 4356.87 | 09-JAN-10:20 | 23166.16 | 17-JUL-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 448.68 | 5277.12 | 09-JAN-10:10 | 24358.90 | 17-JUL-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 448.68 | 5277.12 | 09-JAN-10:10 | 24358.90 | 17-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 448.68 | 5277.12 | 09-JAN-10:10 | 24358.90 | 17-JUL-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 590.30 | 5924.60 | 10-JAN-04:00 | 30565.33 | 06-AUG-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 590.30 | 5924.60 | 10-JAN-04:00 | 30565.33 | 06-AUG-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 78.77 | 0.24 | 22-DEC-20:30 | 7640.66 | 17-JUL-15:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 7.29 | 0.00 | 01-JAN-00:10 | 7485.70 | 11-JAN-07:40 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 7.29 | 0.00 | 01-JAN-00:10 | 7485.70 | 11-JAN-07:40 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 71.48 | 0.00 | 04-JAN-03:10 | 7640.66 | 17-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 71.48 | 0.00 | 04-JAN-03:10 | 7640.66 | 17-JUL-15:10 |
PlantLoopHeatingDemand:Facility | 3760.04 | 10263.49 | 22-AUG-00:50 | 787900.33 | 11-JAN-06:10 |
PlantLoopHeatingDemand:Plant | 2307.14 | 10262.57 | 21-AUG-00:20 | 211176.44 | 03-JUL-20:20 |
WaterSystems:PlantLoopHeatingDemand | 2307.14 | 10262.57 | 21-AUG-00:20 | 211176.44 | 03-JUL-20:20 |
General:WaterSystems:PlantLoopHeatingDemand | 851.54 | 10257.97 | 19-AUG-01:20 | 62851.72 | 17-FEB-08:00 |
HeatingCoils:EnergyTransfer | 1452.90 | 0.00 | 01-JAN-15:40 | 746476.18 | 11-JAN-06:00 |
PlantLoopHeatingDemand:HVAC | 1452.90 | 0.00 | 01-JAN-15:40 | 746476.18 | 11-JAN-06:00 |
HeatingCoils:PlantLoopHeatingDemand | 1452.90 | 0.00 | 01-JAN-15:40 | 746476.18 | 11-JAN-06:00 |
HeatRecoveryForHeating:EnergyTransfer | 4027.63 | 0.00 | 01-JAN-11:10 | 537147.32 | 28-DEC-21:50 |
HeatRecoveryForCooling:EnergyTransfer | 42.14 | 0.00 | 01-JAN-00:10 | 112429.03 | 17-JUL-15:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 1455.60 | 0.00 | 01-JAN-00:10 | 169726.60 | 01-JUL-21:50 |
WaterSystems:EnergyTransfer | 851.54 | 10257.97 | 19-AUG-01:20 | 62851.72 | 17-FEB-08:00 |
WaterUse:WaterSystems:EnergyTransfer | 851.54 | 10257.97 | 19-AUG-01:20 | 62851.72 | 17-FEB-08:00 |
Boilers:EnergyTransfer | 1439.77 | 0.00 | 01-JAN-15:40 | 741195.59 | 11-JAN-06:00 |
Chillers:EnergyTransfer | 1696.28 | 0.00 | 01-JAN-00:10 | 472929.87 | 17-JUL-18:10 |
HeatRejection:EnergyTransfer | 2233.95 | 0.00 | 01-JAN-00:10 | 636898.84 | 17-JUL-18:10 |
General:HeatRejection:EnergyTransfer | 2233.95 | 0.00 | 01-JAN-00:10 | 636898.84 | 17-JUL-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -310.803 | 0.000 | 0.000 | 141.061 | 113.371 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -86.734 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 2.649 | -39.123 | 0.000 | 0.000 | 15.574 | 6.265 | 10.186 | 29.225 | 0.000 | 0.024 | 0.000 | 0.000 | -13.390 | 0.000 | -1.341 | -10.069 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.007 | -30.961 | 0.000 | 0.000 | 16.800 | 7.255 | 11.795 | 0.000 | 0.000 | 0.009 | 0.000 | 0.000 | 0.000 | 0.000 | -0.550 | -4.355 |
MECH_FLR_1 | 0.000 | 0.000 | 1.079 | -20.094 | 0.000 | 0.000 | 3.701 | 8.366 | 12.471 | 0.000 | 0.000 | 0.023 | 0.000 | 0.000 | 0.000 | 0.000 | -1.251 | -4.296 |
STORAGE_FLR_1 | 0.000 | 0.000 | 1.290 | -9.858 | 0.000 | 0.000 | 2.880 | 1.866 | 3.598 | 0.000 | 0.000 | 0.013 | 0.923 | 0.000 | 0.000 | 0.000 | -0.713 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -591.751 | 0.000 | 0.000 | 11.149 | 4.900 | 658.131 | 0.000 | 0.000 | 0.034 | 0.000 | 0.000 | 0.000 | 0.000 | -1.819 | -80.643 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.231 | -228.334 | 0.000 | 0.000 | 192.211 | 12.718 | 14.341 | 81.336 | 0.000 | 0.052 | 0.003 | 0.000 | -39.551 | 0.000 | -3.126 | -29.876 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -746.746 | 0.000 | 0.000 | 552.222 | 122.646 | 148.998 | 107.076 | 0.000 | 0.150 | 0.000 | 0.000 | -53.851 | 0.000 | -9.195 | -121.300 |
ROOM_1_FLR_3 | 26.584 | -37.398 | 0.000 | -9.880 | 0.000 | 0.000 | 9.728 | 6.171 | 12.292 | 51.190 | 0.000 | 0.130 | 0.000 | 0.000 | -30.631 | 0.000 | -3.544 | -24.643 |
ROOM_2_FLR_3 | 32.946 | -24.401 | 0.000 | -10.210 | 0.000 | 0.000 | 9.637 | 6.170 | 12.291 | 33.691 | 0.000 | 0.087 | 0.000 | 0.000 | -32.072 | 0.000 | -3.777 | -24.361 |
ROOM_3_MULT19_FLR_3 | 6.772 | -270.154 | 0.001 | -12.587 | 0.000 | 0.000 | 0.000 | 73.685 | 228.754 | 331.779 | 0.000 | 0.133 | 0.023 | 0.000 | -198.278 | 0.000 | -19.726 | -140.380 |
ROOM_4_MULT19_FLR_3 | 111.627 | -174.793 | 0.000 | -136.162 | 0.000 | 0.000 | 183.870 | 73.705 | 228.817 | 79.229 | 0.000 | 0.697 | 0.000 | 0.000 | -179.072 | 0.000 | -28.875 | -159.044 |
ROOM_5_FLR_3 | 26.424 | -38.976 | 0.000 | -9.890 | 0.000 | 0.000 | 9.720 | 6.171 | 12.292 | 52.466 | 0.000 | 0.130 | 0.000 | 0.000 | -29.927 | 0.000 | -3.556 | -24.856 |
ROOM_6_FLR_3 | 32.598 | -26.073 | 0.000 | -10.171 | 0.000 | 0.000 | 9.657 | 6.170 | 12.291 | 34.647 | 0.000 | 0.087 | 0.000 | 0.000 | -31.005 | 0.000 | -3.859 | -24.342 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 7.020 | -134.189 | 0.000 | 0.000 | 118.504 | 56.739 | 0.000 | 47.304 | 0.000 | 0.068 | 0.000 | 0.000 | -39.166 | 0.000 | -3.807 | -52.472 |
ROOM_1_FLR_6 | 10.079 | -9.111 | 0.000 | -2.465 | 0.000 | 0.000 | 2.436 | 1.543 | 3.073 | 12.754 | 0.000 | 0.035 | 0.000 | 0.000 | -7.607 | 0.000 | -0.909 | -9.829 |
ROOM_2_FLR_6 | 12.114 | -5.984 | 0.000 | -2.553 | 0.000 | 0.000 | 2.411 | 1.543 | 3.073 | 8.402 | 0.000 | 0.022 | 0.000 | 0.000 | -7.970 | 0.000 | -0.962 | -10.097 |
ROOM_3_MULT9_FLR_6 | 28.943 | -63.768 | 0.000 | -15.962 | 0.000 | 0.000 | 21.818 | 8.728 | 27.097 | 75.720 | 0.000 | 0.226 | 0.000 | 0.000 | -35.486 | 0.000 | -4.871 | -42.445 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -407.712 | 0.000 | 0.000 | 318.118 | 28.149 | 175.857 | 8.037 | 0.000 | 0.031 | 0.000 | 0.000 | -23.384 | 0.000 | -2.131 | -96.965 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -448.683 | 0.000 | 0.000 | 316.914 | 28.149 | 175.857 | 7.842 | 0.000 | 0.031 | 0.000 | 0.000 | -23.918 | 0.000 | -2.145 | -54.048 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -590.286 | 0.000 | 0.000 | 28.477 | 13.339 | 540.650 | 24.358 | 0.000 | 0.028 | 0.725 | 0.000 | -15.370 | 0.000 | -1.922 | -0.003 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 7.289 | -71.482 | 0.000 | 0.000 | 31.595 | 15.012 | 0.000 | 23.681 | 0.000 | 0.028 | 12.975 | 0.000 | -17.419 | 0.000 | -1.679 | -0.000 |
Total Facility | 288.088 | -650.656 | 19.565 | -3839.900 | 0.000 | 0.000 | 1998.484 | 602.658 | 2434.967 | 1008.736 | 0.000 | 2.041 | 14.650 | 0.000 | -778.095 | 0.000 | -99.757 | -1000.758 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 28-JAN-01:00 | 0.00 | 0.00 | 0.00 | -21042.12 | 0.00 | 0.00 | 7872.29 | 2060.25 | 3041.85 | 0.00 | 0.00 | 0.00 | 8067.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 18-OCT-13:10 | 0.00 | 0.00 | 0.00 | -4693.32 | 0.00 | 0.00 | 150.59 | 142.31 | 252.59 | 7456.47 | 0.00 | 1.27 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3309.91 |
RETAIL_2_FLR_1 | 17-JUL-21:00 | 0.00 | 0.00 | 0.00 | -2163.83 | 0.00 | 0.00 | 697.60 | 527.34 | 752.15 | 0.00 | 0.00 | 2.66 | 184.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 17-JUL-20:00 | 0.00 | 0.00 | 0.00 | -1778.20 | 0.00 | 0.00 | 129.08 | 684.18 | 839.45 | 0.00 | 0.00 | 11.34 | 114.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 17-JUL-18:50 | 0.00 | 0.00 | 0.00 | -816.79 | 0.00 | 0.00 | 99.29 | 135.66 | 229.41 | 0.00 | 0.00 | 14.01 | 338.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 17-JUL-20:00 | 0.00 | 0.00 | 0.00 | -39216.70 | 0.00 | 0.00 | 408.81 | 400.68 | 44299.38 | 0.00 | 0.00 | 15.48 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5907.65 |
CAFE_FLR_1 | 18-OCT-14:10 | 0.00 | 0.00 | 0.00 | -16275.21 | 0.00 | 0.00 | 2968.55 | 96.16 | 355.63 | 18183.78 | 0.00 | 5.64 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5334.54 |
LOBBY_FLR_1 | 17-JUL-21:10 | 0.00 | 0.00 | 0.00 | -43370.00 | 0.00 | 0.00 | 26439.79 | 7096.92 | 7389.94 | 0.00 | 0.00 | 40.59 | 2481.08 | 0.00 | -78.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 11-AUG-15:01 | 0.00 | -15448.05 | 0.00 | -646.00 | 0.00 | 0.00 | 235.29 | 132.99 | 273.93 | 9604.94 | 0.00 | 46.21 | 5800.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 31-MAY-16:11 | 0.00 | -16908.17 | 0.00 | -812.14 | 0.00 | 0.00 | 193.48 | 132.97 | 537.27 | 10893.94 | 0.00 | 0.00 | 5963.39 | 0.00 | -0.00 | 0.00 | -0.75 | 0.00 |
ROOM_3_MULT19_FLR_3 | 18-OCT-13:00 | 0.00 | -61739.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1587.99 | 5097.90 | 89350.10 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -72.95 | -34223.80 |
ROOM_4_MULT19_FLR_3 | 26-JUL-08:61 | 0.00 | -78759.53 | 0.00 | -9822.66 | 0.00 | 0.00 | 1563.57 | 2496.10 | 8433.45 | 9404.87 | 0.00 | 65.35 | 66618.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 11-AUG-15:01 | 0.00 | -13753.27 | 0.00 | -644.61 | 0.00 | 0.00 | 235.29 | 132.99 | 273.93 | 4279.77 | 0.00 | 46.33 | 9429.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 11-AUG-08:51 | 0.00 | -15286.25 | 0.00 | -820.80 | 0.00 | 0.00 | 71.66 | 208.96 | 452.99 | 9750.52 | 0.00 | 4.89 | 5618.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 17-JUL-18:40 | 0.00 | 0.00 | 0.00 | -11472.14 | 0.00 | 0.00 | 4080.26 | 4124.45 | 0.00 | 3179.98 | 0.00 | 76.37 | 11.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 11-AUG-15:01 | 0.00 | -4067.50 | 0.00 | -161.29 | 0.00 | 0.00 | 58.82 | 33.25 | 68.48 | 2387.02 | 0.00 | 11.49 | 1669.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 31-MAY-16:11 | 0.00 | -4445.55 | 0.00 | -203.22 | 0.00 | 0.00 | 48.37 | 33.24 | 134.32 | 2702.44 | 0.00 | 0.00 | 1730.69 | 0.00 | -0.00 | 0.00 | -0.29 | 0.00 |
ROOM_3_MULT9_FLR_6 | 18-OCT-15:01 | 0.00 | -19786.63 | 0.00 | -1061.32 | 0.00 | 0.00 | 529.38 | 188.10 | 603.86 | 12652.18 | 0.00 | 13.73 | 6860.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 17-JUL-21:20 | 0.00 | 0.00 | 0.00 | -23169.06 | 0.00 | 0.00 | 15622.78 | 1842.08 | 6747.90 | 13.91 | 0.00 | 8.07 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1065.69 |
DINING_FLR_6 | 17-JUL-21:20 | 0.00 | 0.00 | 0.00 | -24362.04 | 0.00 | 0.00 | 15616.62 | 1842.08 | 6747.90 | 2.54 | 0.00 | 8.07 | 144.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 06-AUG-10:40 | 0.00 | 0.00 | 0.00 | -30600.41 | 0.00 | 0.00 | 464.31 | 363.61 | 23951.61 | 4561.49 | 0.00 | 19.70 | 1239.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 17-JUL-15:03 | 0.00 | 0.00 | 0.00 | -7641.46 | 0.00 | 0.00 | 771.14 | 341.02 | 0.00 | 2774.22 | 0.00 | 37.59 | 3717.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-JUL-18:02 | 0.00 | -168485.70 | 0.00 | -210975.65 | 0.00 | 0.00 | 74037.90 | 40498.58 | 121562.63 | 76265.54 | 0.00 | 1704.88 | 65391.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 11-JAN-07:31 | 0.00 | 0.00 | 3666.22 | 0.00 | 0.00 | 0.00 | 373.92 | 284.62 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1571.07 | 0.00 | -128.23 | -3058.47 |
RETAIL_2_FLR_1 | 09-JAN-12:20 | 0.00 | 0.00 | 172.42 | 0.00 | 0.00 | 0.00 | 207.46 | 164.79 | 292.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -54.26 | -782.91 |
MECH_FLR_1 | 11-JAN-05:00 | 0.00 | 0.00 | 1211.31 | 0.00 | 0.00 | 0.00 | 197.28 | 76.02 | 176.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -141.38 | -1519.96 |
STORAGE_FLR_1 | 11-JAN-07:31 | 0.00 | 0.00 | 989.19 | 0.00 | 0.00 | 0.00 | 67.46 | 84.79 | 152.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -68.67 | -1225.71 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 11-JAN-07:31 | 0.00 | 0.00 | 3588.74 | 0.00 | 0.00 | 0.00 | 4720.36 | 874.14 | 609.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4532.82 | 0.00 | -288.38 | -4971.69 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 07-JAN-16:01 | 12300.01 | 273.25 | 0.00 | -273.25 | 0.00 | 0.00 | 163.33 | 156.74 | 305.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3330.59 | 0.00 | -287.09 | -9307.94 |
ROOM_2_FLR_3 | 29-DEC-16:01 | 12253.83 | 268.35 | 0.00 | -268.35 | 0.00 | 0.00 | 293.99 | 132.97 | 273.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3068.57 | 0.00 | -276.46 | -9609.68 |
ROOM_3_MULT19_FLR_3 | 11-JAN-06:00 | 30232.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1247.71 | 3921.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21531.46 | 0.00 | -1877.88 | -11992.79 |
ROOM_4_MULT19_FLR_3 | 29-JAN-16:01 | 67511.27 | 3370.90 | 0.00 | -3370.90 | 0.00 | 0.00 | 3103.17 | 1872.11 | 5687.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15616.40 | 0.00 | -1460.18 | -61097.64 |
ROOM_5_FLR_3 | 29-DEC-16:01 | 12000.00 | 271.33 | 0.00 | -271.33 | 0.00 | 0.00 | 293.99 | 132.99 | 273.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3210.83 | 0.00 | -276.79 | -9213.29 |
ROOM_6_FLR_3 | 29-DEC-16:01 | 11931.48 | 266.84 | 0.00 | -266.84 | 0.00 | 0.00 | 293.99 | 132.97 | 273.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3268.87 | 0.00 | -276.30 | -9087.18 |
CORRIDOR_FLR_3 | 09-JAN-10:10 | 0.00 | 0.00 | 7685.89 | 0.00 | 0.00 | 0.00 | 1386.46 | 1288.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3719.55 | 0.00 | -403.04 | -6238.65 |
ROOM_1_FLR_6 | 07-JAN-16:01 | 3710.20 | 69.09 | 0.00 | -69.09 | 0.00 | 0.00 | 40.83 | 39.19 | 76.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -832.02 | 0.00 | -71.98 | -2962.61 |
ROOM_2_FLR_6 | 07-JAN-16:01 | 3683.09 | 68.03 | 0.00 | -68.03 | 0.00 | 0.00 | 40.83 | 39.18 | 76.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -835.54 | 0.00 | -71.86 | -2932.08 |
ROOM_3_MULT9_FLR_6 | 05-JAN-16:01 | 17681.66 | 447.41 | 0.00 | -447.41 | 0.00 | 0.00 | 661.48 | 188.10 | 603.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3381.36 | 0.00 | -314.83 | -15438.92 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 11-JAN-07:31 | 0.00 | 0.00 | 8418.58 | 0.00 | 0.00 | 0.00 | 743.14 | 682.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2135.70 | 0.00 | -161.65 | -7546.41 |
Total Facility | 10-JAN-09:02 | 101186.55 | 60422.13 | 19499.46 | -60422.13 | 0.00 | 0.00 | 24504.41 | 20915.41 | 87870.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -69870.41 | 0.00 | -7411.03 | -176695.01 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 24.2416 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 24.1122 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 12.1208 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6602 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3458 | 2.3458 | 1.1283 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4561 | 0.4561 | 0.2194 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2485 | 0.2485 | 0.1195 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1976 | 0.1976 | 0.0950 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1079 | 0.1079 | 0.0519 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7214 | 3.7214 | 1.7900 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8803 | 1.8803 | 0.9044 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5172 | 5.5172 | 2.6538 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4627 | 1.4627 | 0.7036 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4241 | 2.4241 | 1.1660 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5441 | 2.5441 | 1.2237 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5072 | 2.5072 | 1.2059 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8287 | 0.8287 | 0.3986 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 24.2416 | 24.1122 | 24.2416 | 11.6602 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1729 | 1.1729 | 1.1283 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2281 | 0.2281 | 0.2194 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1243 | 0.1243 | 0.1195 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0988 | 0.0988 | 0.0950 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0539 | 0.0539 | 0.0519 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8607 | 1.8607 | 1.7900 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9401 | 0.9401 | 0.9044 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7586 | 2.7586 | 2.6538 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7313 | 0.7313 | 0.7036 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2120 | 1.2120 | 1.1660 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2720 | 1.2720 | 1.2237 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2536 | 1.2536 | 1.2059 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4144 | 0.4144 | 0.3986 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 12.1208 | 11.6602 | 11.6602 | 11.6602 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 20.00 |
Number of hours cooling loads not met | 56.67 |
Number of hours not met | 76.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1944.67 | 924327.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 537.67 | 163968.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 602.66 | 50471.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 174.07 | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 952.41 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 22.46 | 1283.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 532.78 | 41399.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 87.17 | 6114.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 179.45 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4739.91 | 1480.31 | 195185.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Other | 0.00 | 36736.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.70 | 1310.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 20.76 | 715.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1771.69 | 4996.00 |
Natural Gas | 1788.84 | 5213.82 |
Additional | 0.00 | 0.00 |
Total | 3560.53 | 10209.82 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 53.12 |
Space Heating | 0.00 |
Space Cooling | 47.39 |
Fans (All) | 46.96 |
Service Water Heating | 41.34 |
Receptacle Equipment | 152.32 |
Miscellaneous (All) | 440.36 |
Subtotal | 440.36 |
Natural Gas [MJ/m2] | |
Space Heating | 171.41 |
Service Water Heating | 130.48 |
Miscellaneous (All) | 459.56 |
Subtotal | 459.56 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.90 |
Space Heating | 19.05 |
Space Cooling | 5.27 |
Fans (All) | 5.22 |
Service Water Heating | 19.09 |
Receptacle Equipment | 34.45 |
Miscellaneous | 11.03 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2398. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 2482. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8727.33 | 32.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8730.50 | 29.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8703.50 | 56.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8703.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 56.50 | 0.00 | 0.00 | 0.00 |
Average | 8754.19 | 5.81 | 0.00 | 0.00 | 0.00 |
Sum | 192592.17 | 127.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4145.17 | 8.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4134.67 | 19.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 19.33 | 0.00 | 0.00 | 0.00 |
Average | 288885.77 | 1.28 | 0.00 | 0.00 | 0.00 |
Sum | 6355486.83 | 28.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8741.83 | 18.17 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8749.33 | 10.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8744.00 | 16.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8725.83 | 34.17 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8732.83 | 27.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8758.00 | 2.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8729.33 | 30.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8747.00 | 13.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8749.17 | 10.83 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8725.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 34.17 | 0.00 | 0.00 | 0.00 |
Average | 8752.58 | 7.42 | 0.00 | 0.00 | 0.00 |
Sum | 192556.83 | 163.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 708120.67 | 2296.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2111446.50 | 3982.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4147.50 | 6.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100322.00 | 36.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4139.50 | 14.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1242836.33 | 2878.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1243313.33 | 2401.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108267.00 | 2.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2111446.50 | 3982.50 | 0.00 | 0.00 | 0.00 |
Average | 288358.95 | 528.10 | 0.00 | 0.00 | 0.00 |
Sum | 6343896.83 | 11618.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:46
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272961E+11 | 21042.24 | 28-JAN-01:00 | -30.6 | -30.9 | 0.728120E+10 | 4836.93 | 04-JAN-22:19 | -30.6 | -30.9 |
February | 0.215259E+11 | 16854.77 | 01-FEB-03:55 | -25.0 | -25.2 | 0.672690E+10 | 4681.00 | 28-FEB-22:19 | 0.00 | -1.7 |
March | 0.225843E+11 | 10701.31 | 01-MAR-21:00 | 1.70 | -0.4 | 0.720107E+10 | 4648.20 | 01-MAR-22:10 | 3.22 | 0.32 |
April | 0.207053E+11 | 10031.52 | 08-APR-10:33 | 12.43 | 6.03 | 0.661999E+10 | 4265.61 | 03-APR-22:10 | 12.43 | 6.03 |
May | 0.230704E+11 | 10913.15 | 13-MAY-10:33 | 21.13 | 9.82 | 0.714710E+10 | 4454.98 | 22-MAY-21:10 | -0.6 | -1.1 |
June | 0.237716E+11 | 11511.59 | 24-JUN-10:33 | 23.87 | 15.50 | 0.710530E+10 | 4576.75 | 16-JUN-21:10 | 23.87 | 15.50 |
July | 0.265392E+11 | 12284.13 | 17-JUL-18:10 | 35.82 | 16.61 | 0.766123E+10 | 4790.04 | 28-JUL-22:10 | 17.88 | 10.27 |
August | 0.276512E+11 | 13162.75 | 17-AUG-21:00 | 8.90 | 5.87 | 0.796766E+10 | 4837.09 | 23-AUG-22:10 | 16.52 | 10.16 |
September | 0.287762E+11 | 16374.88 | 28-SEP-21:00 | 8.30 | 5.79 | 0.789429E+10 | 4837.08 | 01-SEP-22:10 | 8.30 | 5.79 |
October | 0.312526E+11 | 17666.79 | 20-OCT-21:00 | 3.30 | 1.38 | 0.820235E+10 | 4837.06 | 18-OCT-21:19 | 3.30 | 1.38 |
November | 0.293164E+11 | 17335.51 | 01-NOV-21:00 | 3.70 | 0.55 | 0.792688E+10 | 4837.06 | 27-NOV-00:20 | -15.2 | -16.0 |
December | 0.283122E+11 | 20248.15 | 29-DEC-09:00 | -28.3 | -28.6 | 0.806638E+10 | 4837.04 | 01-DEC-00:20 | -28.3 | -28.6 |
Annual Sum or Average | 0.310801E+12 | 0.898003E+11 | ||||||||
Minimum of Months | 0.207053E+11 | 10031.52 | -30.6 | -30.9 | 0.661999E+10 | 4265.61 | -30.6 | -30.9 | ||
Maximum of Months | 0.312526E+11 | 21042.24 | 35.82 | 16.61 | 0.820235E+10 | 4837.09 | 23.87 | 15.50 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111897E+10 | 3193.04 | 15-JAN-13:30 | 5.30 | -0.5 | 0.622865E+09 | 367.07 | 02-JAN-22:30 | 5.30 | -0.5 |
February | 0.195916E+10 | 4105.26 | 26-FEB-13:00 | 15.00 | 5.51 | 0.576428E+09 | 407.13 | 27-FEB-22:30 | 0.85 | -0.9 |
March | 0.243116E+10 | 3866.08 | 01-MAR-13:40 | 6.33 | 2.52 | 0.642581E+09 | 404.02 | 01-MAR-22:30 | 3.05 | 0.15 |
April | 0.289402E+10 | 3492.05 | 06-APR-13:40 | 20.20 | 9.73 | 0.630560E+09 | 446.74 | 06-APR-21:30 | 14.70 | 7.53 |
May | 0.344697E+10 | 3040.20 | 20-MAY-12:40 | 25.20 | 14.21 | 0.661951E+09 | 463.79 | 19-MAY-21:30 | 25.20 | 14.21 |
June | 0.437439E+10 | 3032.40 | 23-JUN-13:10 | 31.20 | 15.18 | 0.683015E+09 | 476.37 | 30-JUN-21:30 | 21.75 | 12.44 |
July | 0.525747E+10 | 3866.71 | 17-JUL-13:20 | 36.30 | 17.01 | 0.742430E+09 | 491.82 | 25-JUL-21:19 | 26.10 | 13.36 |
August | 0.535070E+10 | 4242.59 | 09-AUG-13:20 | 33.50 | 16.27 | 0.743713E+09 | 491.84 | 07-AUG-22:10 | 33.50 | 16.27 |
September | 0.463931E+10 | 4593.50 | 03-SEP-12:40 | 33.13 | 15.93 | 0.687306E+09 | 480.45 | 01-SEP-21:30 | 33.13 | 15.93 |
October | 0.384895E+10 | 4692.93 | 18-OCT-13:10 | 24.50 | 10.91 | 0.666665E+09 | 461.30 | 18-OCT-21:19 | 14.80 | 7.08 |
November | 0.249278E+10 | 3813.36 | 03-NOV-13:10 | 13.92 | 7.65 | 0.616493E+09 | 422.28 | 03-NOV-21:30 | 9.70 | 5.41 |
December | 0.130866E+10 | 2415.74 | 12-DEC-12:30 | -2.8 | -5.7 | 0.625967E+09 | 364.19 | 28-DEC-22:10 | -23.5 | -23.8 |
Annual Sum or Average | 0.391225E+11 | 0.789997E+10 | ||||||||
Minimum of Months | 0.111897E+10 | 2415.74 | -2.8 | -5.7 | 0.576428E+09 | 364.19 | -23.5 | -23.8 | ||
Maximum of Months | 0.535070E+10 | 4692.93 | 36.30 | 17.01 | 0.743713E+09 | 491.84 | 33.50 | 16.27 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182201E+10 | 1652.55 | 05-JAN-22:53 | -23.9 | -24.4 | 0.776148E+09 | 545.85 | 02-JAN-23:10 | -23.9 | -24.4 |
February | 0.198054E+10 | 1620.66 | 01-FEB-03:43 | -24.4 | -24.7 | 0.740059E+09 | 569.51 | 27-FEB-22:19 | 0.93 | -0.9 |
March | 0.236295E+10 | 1234.45 | 01-MAR-22:00 | 3.30 | 0.41 | 0.851109E+09 | 569.50 | 01-MAR-22:19 | 3.13 | 0.24 |
April | 0.247184E+10 | 1501.77 | 06-APR-21:00 | 14.40 | 7.49 | 0.851578E+09 | 569.55 | 07-APR-22:10 | 14.63 | 5.97 |
May | 0.269101E+10 | 1719.92 | 19-MAY-21:00 | 20.60 | 12.23 | 0.899929E+09 | 569.56 | 31-MAY-22:40 | 16.27 | 10.04 |
June | 0.296347E+10 | 1935.51 | 23-JUN-20:02 | 23.53 | 14.25 | 0.911328E+09 | 569.55 | 22-JUN-22:10 | 23.53 | 14.25 |
July | 0.335888E+10 | 2163.60 | 17-JUL-21:00 | 26.70 | 14.26 | 0.954688E+09 | 569.65 | 01-JUL-00:49 | 26.70 | 14.26 |
August | 0.331271E+10 | 2121.81 | 07-AUG-21:00 | 23.90 | 12.75 | 0.957395E+09 | 569.60 | 01-AUG-01:10 | 23.90 | 12.75 |
September | 0.292806E+10 | 1945.86 | 01-SEP-20:10 | 19.13 | 10.10 | 0.906681E+09 | 569.55 | 01-SEP-22:10 | 17.20 | 9.47 |
October | 0.268329E+10 | 1672.64 | 18-OCT-21:00 | 14.40 | 6.96 | 0.904859E+09 | 569.55 | 18-OCT-21:19 | 14.80 | 7.08 |
November | 0.231658E+10 | 1279.56 | 03-NOV-21:00 | 9.80 | 5.39 | 0.828335E+09 | 569.52 | 03-NOV-21:40 | 9.67 | 5.41 |
December | 0.206944E+10 | 1575.90 | 28-DEC-22:33 | -24.0 | -24.3 | 0.801575E+09 | 547.04 | 07-DEC-22:30 | -24.0 | -24.3 |
Annual Sum or Average | 0.309608E+11 | 0.103837E+11 | ||||||||
Minimum of Months | 0.182201E+10 | 1234.45 | -24.4 | -24.7 | 0.740059E+09 | 545.85 | -24.0 | -24.4 | ||
Maximum of Months | 0.335888E+10 | 2163.60 | 26.70 | 14.26 | 0.957395E+09 | 569.65 | 26.70 | 14.26 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.639084E+09 | 723.98 | 02-JAN-21:00 | 3.90 | -0.8 | 0.153069E+09 | 98.24 | 02-JAN-22:10 | 3.90 | -0.9 |
February | 0.933157E+09 | 820.48 | 27-FEB-21:00 | 3.30 | 0.43 | 0.140974E+09 | 106.00 | 27-FEB-22:10 | 1.02 | -0.9 |
March | 0.139561E+10 | 784.26 | 02-MAR-21:00 | -0.6 | -1.7 | 0.159563E+09 | 103.28 | 02-MAR-22:10 | -4.4 | -5.3 |
April | 0.169738E+10 | 916.61 | 08-APR-10:33 | 12.43 | 6.03 | 0.162223E+09 | 111.63 | 07-APR-21:10 | 12.43 | 6.03 |
May | 0.189148E+10 | 1002.41 | 20-MAY-18:10 | 24.13 | 13.93 | 0.175261E+09 | 118.77 | 31-MAY-21:19 | 17.00 | 8.28 |
June | 0.219200E+10 | 1489.08 | 23-JUN-21:00 | 21.70 | 13.41 | 0.186849E+09 | 120.45 | 26-JUN-21:10 | 10.68 | 7.78 |
July | 0.253601E+10 | 1777.87 | 17-JUL-20:00 | 28.90 | 15.30 | 0.199853E+09 | 120.46 | 31-JUL-23:10 | 20.62 | 12.81 |
August | 0.244317E+10 | 1713.35 | 10-AUG-20:00 | 25.60 | 10.84 | 0.199111E+09 | 120.45 | 01-AUG-00:30 | 25.60 | 10.84 |
September | 0.212306E+10 | 1541.40 | 04-SEP-20:00 | 23.30 | 13.77 | 0.183375E+09 | 120.45 | 06-SEP-21:19 | 19.80 | 16.17 |
October | 0.189710E+10 | 926.26 | 18-OCT-20:00 | 16.10 | 7.67 | 0.176187E+09 | 116.05 | 19-OCT-21:19 | 11.50 | 5.57 |
November | 0.144502E+10 | 825.09 | 08-NOV-21:00 | 5.80 | 3.35 | 0.157541E+09 | 107.16 | 08-NOV-22:10 | 4.65 | 2.60 |
December | 0.900730E+09 | 753.14 | 06-DEC-21:00 | -1.1 | -3.0 | 0.153988E+09 | 100.49 | 06-DEC-22:10 | 1.20 | -1.1 |
Annual Sum or Average | 0.200938E+11 | 0.204799E+10 | ||||||||
Minimum of Months | 0.639084E+09 | 723.98 | -1.1 | -3.0 | 0.140974E+09 | 98.24 | -4.4 | -5.3 | ||
Maximum of Months | 0.253601E+10 | 1777.87 | 28.90 | 15.30 | 0.199853E+09 | 120.46 | 25.60 | 16.17 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.212082E+09 | 370.56 | 15-JAN-11:35 | 4.03 | -1.0 | 0.116824E+09 | 71.78 | 02-JAN-23:10 | 4.03 | -1.0 |
February | 0.388091E+09 | 423.67 | 27-FEB-11:33 | 15.53 | 5.85 | 0.106922E+09 | 77.39 | 27-FEB-22:40 | 0.77 | -0.9 |
March | 0.645015E+09 | 411.82 | 23-MAR-10:33 | 8.70 | 1.68 | 0.119651E+09 | 75.12 | 29-MAR-21:49 | 4.18 | 0.64 |
April | 0.857546E+09 | 490.11 | 08-APR-10:33 | 12.43 | 6.03 | 0.121052E+09 | 82.43 | 07-APR-22:10 | 12.43 | 6.03 |
May | 0.974734E+09 | 535.75 | 20-MAY-18:00 | 24.40 | 14.00 | 0.131184E+09 | 87.65 | 31-MAY-22:10 | 16.52 | 9.30 |
June | 0.114742E+10 | 627.74 | 23-JUN-19:40 | 25.00 | 14.47 | 0.140469E+09 | 92.66 | 22-JUN-22:10 | 25.00 | 14.47 |
July | 0.130157E+10 | 816.71 | 17-JUL-18:50 | 34.68 | 16.38 | 0.151462E+09 | 92.66 | 26-JUL-23:30 | 18.35 | 11.97 |
August | 0.126401E+10 | 730.21 | 09-AUG-19:10 | 29.63 | 14.86 | 0.150290E+09 | 92.66 | 08-AUG-21:00 | 29.63 | 14.86 |
September | 0.110298E+10 | 635.34 | 04-SEP-19:40 | 25.33 | 14.45 | 0.137579E+09 | 92.66 | 06-SEP-21:40 | 19.60 | 15.95 |
October | 0.989224E+09 | 492.59 | 18-OCT-10:33 | 21.13 | 9.17 | 0.131153E+09 | 85.51 | 18-OCT-22:10 | 15.50 | 7.23 |
November | 0.670874E+09 | 425.76 | 04-NOV-18:10 | 14.68 | 6.96 | 0.118031E+09 | 78.00 | 03-NOV-22:10 | 14.68 | 6.96 |
December | 0.304012E+09 | 377.35 | 06-DEC-21:00 | -1.1 | -3.0 | 0.117135E+09 | 72.98 | 06-DEC-23:10 | 2.07 | -0.6 |
Annual Sum or Average | 0.985755E+10 | 0.154175E+10 | ||||||||
Minimum of Months | 0.212082E+09 | 370.56 | -1.1 | -3.0 | 0.106922E+09 | 71.78 | 0.77 | -1.0 | ||
Maximum of Months | 0.130157E+10 | 816.71 | 34.68 | 16.38 | 0.151462E+09 | 92.66 | 29.63 | 15.95 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.472019E+11 | 36928.01 | 02-JAN-21:00 | 3.90 | -0.8 | 0.562457E+09 | 381.65 | 02-JAN-22:10 | 3.90 | -0.9 |
February | 0.435899E+11 | 37659.10 | 27-FEB-21:00 | 3.30 | 0.43 | 0.537741E+09 | 381.68 | 21-FEB-22:10 | 3.30 | 0.43 |
March | 0.491217E+11 | 37569.25 | 28-MAR-20:00 | 4.40 | -0.6 | 0.600026E+09 | 381.71 | 29-MAR-21:10 | 5.32 | 1.04 |
April | 0.484817E+11 | 38118.44 | 25-APR-20:00 | 12.20 | 5.56 | 0.583090E+09 | 381.76 | 24-APR-21:10 | 12.20 | 5.56 |
May | 0.508803E+11 | 38594.42 | 19-MAY-20:00 | 22.20 | 13.11 | 0.604376E+09 | 381.76 | 18-MAY-21:10 | 22.20 | 13.11 |
June | 0.507247E+11 | 38970.86 | 23-JUN-20:00 | 23.90 | 14.40 | 0.588799E+09 | 381.73 | 20-JUN-21:19 | 23.90 | 14.40 |
July | 0.530401E+11 | 39208.71 | 17-JUL-20:00 | 28.90 | 15.30 | 0.608924E+09 | 381.82 | 25-JUL-21:10 | 26.65 | 13.54 |
August | 0.529691E+11 | 39063.72 | 07-AUG-20:00 | 26.10 | 13.65 | 0.610410E+09 | 381.93 | 11-AUG-21:10 | 23.62 | 11.25 |
September | 0.500169E+11 | 38684.40 | 01-SEP-20:00 | 19.40 | 10.22 | 0.587301E+09 | 381.78 | 27-SEP-21:10 | 17.52 | 9.45 |
October | 0.504466E+11 | 38156.58 | 18-OCT-20:00 | 16.10 | 7.67 | 0.604674E+09 | 381.78 | 16-OCT-21:10 | 16.10 | 7.67 |
November | 0.475932E+11 | 37602.65 | 03-NOV-20:00 | 10.00 | 5.46 | 0.581060E+09 | 381.73 | 15-NOV-22:10 | 3.30 | -1.2 |
December | 0.476828E+11 | 37178.99 | 06-DEC-21:00 | -1.1 | -3.0 | 0.590949E+09 | 381.73 | 06-DEC-22:10 | 1.20 | -1.1 |
Annual Sum or Average | 0.591749E+12 | 0.705981E+10 | ||||||||
Minimum of Months | 0.435899E+11 | 36928.01 | -1.1 | -3.0 | 0.537741E+09 | 381.65 | 1.20 | -1.2 | ||
Maximum of Months | 0.530401E+11 | 39208.71 | 28.90 | 15.30 | 0.610410E+09 | 381.93 | 26.65 | 14.40 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128623E+11 | 12537.31 | 15-JAN-13:00 | 5.00 | -0.5 | 0.877122E+10 | 6185.14 | 02-JAN-22:40 | 5.00 | -0.5 |
February | 0.153345E+11 | 15562.85 | 26-FEB-13:00 | 15.00 | 5.51 | 0.840776E+10 | 6460.36 | 27-FEB-23:10 | 0.68 | -0.9 |
March | 0.177354E+11 | 14217.56 | 01-MAR-13:30 | 6.15 | 2.39 | 0.954594E+10 | 6460.17 | 01-MAR-23:10 | 2.62 | -0.4 |
April | 0.181729E+11 | 13649.89 | 06-APR-15:03 | 21.28 | 10.55 | 0.947543E+10 | 6462.43 | 07-APR-22:10 | 14.63 | 5.97 |
May | 0.194360E+11 | 11951.15 | 13-MAY-13:10 | 24.18 | 10.02 | 0.998278E+10 | 6462.76 | 31-MAY-22:10 | 16.52 | 9.30 |
June | 0.211724E+11 | 11320.97 | 30-JUN-15:03 | 29.68 | 14.20 | 0.101557E+11 | 6462.75 | 05-JUN-22:10 | 29.68 | 14.20 |
July | 0.239857E+11 | 13551.33 | 17-JUL-15:03 | 36.28 | 17.05 | 0.106975E+11 | 6463.31 | 01-JUL-00:49 | 36.28 | 17.05 |
August | 0.244302E+11 | 14354.03 | 25-AUG-15:03 | 31.02 | 14.57 | 0.107459E+11 | 6462.72 | 29-AUG-22:10 | 17.20 | 10.21 |
September | 0.223769E+11 | 15648.95 | 02-SEP-13:00 | 32.80 | 16.22 | 0.101642E+11 | 6462.68 | 01-SEP-22:10 | 32.80 | 16.22 |
October | 0.209394E+11 | 16271.74 | 18-OCT-14:10 | 25.00 | 11.44 | 0.101249E+11 | 6462.43 | 18-OCT-21:19 | 14.80 | 7.08 |
November | 0.174087E+11 | 14074.61 | 03-NOV-13:10 | 13.92 | 7.65 | 0.924559E+10 | 6461.36 | 03-NOV-23:19 | 9.23 | 5.34 |
December | 0.144775E+11 | 10425.77 | 02-DEC-13:30 | 9.40 | 4.37 | 0.894080E+10 | 6112.82 | 07-DEC-22:40 | 0.73 | -1.4 |
Annual Sum or Average | 0.228332E+12 | 0.116258E+12 | ||||||||
Minimum of Months | 0.128623E+11 | 10425.77 | 5.00 | -0.5 | 0.840776E+10 | 6112.82 | 0.68 | -1.4 | ||
Maximum of Months | 0.244302E+11 | 16271.74 | 36.28 | 17.05 | 0.107459E+11 | 6463.31 | 36.28 | 17.05 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.492631E+11 | 38528.71 | 05-JAN-22:53 | -23.9 | -24.4 | 0.276074E+11 | 19182.89 | 02-JAN-23:30 | -23.9 | -24.4 |
February | 0.497803E+11 | 37965.79 | 01-FEB-03:55 | -25.0 | -25.2 | 0.266328E+11 | 19184.64 | 27-FEB-00:20 | 5.73 | 1.15 |
March | 0.575808E+11 | 31968.03 | 01-MAR-22:10 | 3.22 | 0.32 | 0.304306E+11 | 19184.58 | 16-MAR-23:19 | -1.3 | -4.4 |
April | 0.590766E+11 | 35456.21 | 06-APR-21:10 | 14.50 | 7.51 | 0.300317E+11 | 19185.77 | 07-APR-22:10 | 14.63 | 5.97 |
May | 0.638181E+11 | 38091.45 | 19-MAY-21:10 | 20.32 | 12.17 | 0.314126E+11 | 19186.29 | 31-MAY-22:10 | 16.52 | 9.30 |
June | 0.694203E+11 | 40331.12 | 23-JUN-21:10 | 21.60 | 13.25 | 0.311712E+11 | 19186.27 | 05-JUN-22:10 | 21.60 | 13.25 |
July | 0.771258E+11 | 43364.40 | 17-JUL-21:10 | 26.52 | 14.20 | 0.323472E+11 | 19189.22 | 01-JUL-00:49 | 26.52 | 14.20 |
August | 0.770378E+11 | 42939.50 | 07-AUG-21:04 | 23.90 | 12.85 | 0.325066E+11 | 19186.85 | 01-AUG-01:10 | 23.90 | 12.85 |
September | 0.697307E+11 | 40647.17 | 01-SEP-20:10 | 19.13 | 10.10 | 0.311753E+11 | 19186.11 | 01-SEP-22:10 | 17.20 | 9.47 |
October | 0.651885E+11 | 38658.85 | 18-OCT-21:03 | 14.60 | 7.02 | 0.317313E+11 | 19185.79 | 18-OCT-21:19 | 14.80 | 7.08 |
November | 0.566431E+11 | 33801.88 | 03-NOV-21:10 | 9.77 | 5.40 | 0.296057E+11 | 19185.06 | 04-NOV-01:19 | 8.13 | 5.13 |
December | 0.520749E+11 | 36479.36 | 28-DEC-22:33 | -24.0 | -24.3 | 0.288521E+11 | 19182.92 | 06-DEC-22:19 | -24.0 | -24.3 |
Annual Sum or Average | 0.746740E+12 | 0.363504E+12 | ||||||||
Minimum of Months | 0.492631E+11 | 31968.03 | -25.0 | -25.2 | 0.266328E+11 | 19182.89 | -24.0 | -24.4 | ||
Maximum of Months | 0.771258E+11 | 43364.40 | 26.52 | 14.20 | 0.325066E+11 | 19189.22 | 26.52 | 14.20 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 17105405.45 | 3379.91 | 21-JAN-16:01 | 1.83 | -2.4 | 93624227.42 | 56.69 | 17-JAN-04:19 | 1.83 | -2.4 |
February | 0.157629E+09 | 3603.21 | 27-FEB-16:01 | 17.78 | 6.92 | 85964109.40 | 56.69 | 07-FEB-04:19 | 17.78 | 6.92 |
March | 0.240122E+09 | 3533.72 | 01-MAR-16:01 | 9.13 | 3.73 | 95960574.12 | 56.69 | 24-MAR-03:20 | -1.7 | -3.5 |
April | 0.574910E+09 | 3793.06 | 06-APR-15:01 | 21.28 | 10.55 | 93979758.62 | 56.69 | 07-APR-21:30 | 15.55 | 6.36 |
May | 0.105415E+10 | 3915.27 | 31-MAY-18:01 | 23.53 | 10.12 | 97917829.08 | 56.70 | 19-MAY-21:30 | 23.53 | 10.12 |
June | 0.180402E+10 | 3735.70 | 10-JUN-18:02 | 21.42 | 10.67 | 95637648.58 | 56.70 | 20-JUN-22:30 | 23.90 | 15.91 |
July | 0.246282E+10 | 3757.61 | 07-JUL-18:01 | 19.67 | 8.84 | 98973836.30 | 56.70 | 19-JUL-23:40 | 17.93 | 13.68 |
August | 0.220554E+10 | 4023.54 | 11-AUG-15:01 | 30.60 | 13.32 | 98961655.94 | 56.70 | 01-AUG-01:39 | 30.60 | 13.32 |
September | 0.142511E+10 | 3630.51 | 08-SEP-18:01 | 17.93 | 9.62 | 95189703.26 | 56.70 | 07-SEP-21:10 | 17.93 | 9.62 |
October | 0.596191E+09 | 3949.30 | 18-OCT-15:01 | 24.90 | 11.51 | 97425905.60 | 56.69 | 01-OCT-01:10 | 24.90 | 11.51 |
November | 0.140859E+09 | 3472.65 | 06-NOV-16:01 | 7.12 | 2.52 | 92720503.26 | 56.69 | 10-NOV-04:19 | -3.3 | -4.3 |
December | 20038629.05 | 3411.62 | 07-DEC-16:01 | 6.32 | 2.06 | 93892619.44 | 56.69 | 08-DEC-04:19 | -1.3 | -3.3 |
Annual Sum or Average | 0.106985E+11 | 0.114025E+10 | ||||||||
Minimum of Months | 17105405.45 | 3379.91 | 1.83 | -2.4 | 85964109.40 | 56.69 | -3.3 | -4.3 | ||
Maximum of Months | 0.246282E+10 | 4023.54 | 30.60 | 13.32 | 98973836.30 | 56.70 | 30.60 | 15.91 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5560692.42 | 1048.04 | 13-JAN-19:03 | 6.60 | 3.11 | 92738583.49 | 56.69 | 30-JAN-02:39 | -21.1 | -21.8 |
February | 45536838.60 | 3557.36 | 26-FEB-17:41 | 11.85 | 4.39 | 84838829.54 | 56.69 | 28-FEB-04:19 | -2.6 | -3.2 |
March | 0.100139E+09 | 3309.15 | 02-MAR-16:01 | 10.22 | 4.59 | 94788229.09 | 56.69 | 24-MAR-03:20 | -1.7 | -3.5 |
April | 0.299666E+09 | 3917.21 | 22-APR-19:01 | 12.93 | 7.38 | 95138030.59 | 84.27 | 25-APR-18:10 | 16.73 | 7.64 |
May | 0.720645E+09 | 4430.07 | 31-MAY-16:11 | 25.00 | 10.32 | 0.102353E+09 | 85.12 | 12-MAY-18:10 | 25.00 | 10.32 |
June | 0.143429E+10 | 3921.38 | 07-JUN-19:41 | 12.77 | 6.36 | 0.102468E+09 | 86.78 | 19-JUN-21:10 | 16.10 | 8.30 |
July | 0.201425E+10 | 3884.81 | 08-JUL-20:41 | 13.68 | 7.34 | 0.105590E+09 | 91.64 | 05-JUL-18:10 | 13.68 | 7.34 |
August | 0.161480E+10 | 3940.58 | 11-AUG-08:51 | 26.10 | 11.83 | 0.105521E+09 | 87.15 | 29-AUG-18:10 | 23.43 | 12.63 |
September | 0.902797E+09 | 3721.17 | 15-SEP-18:21 | 13.60 | 7.77 | 98335998.70 | 82.42 | 08-SEP-18:10 | 13.60 | 7.77 |
October | 0.239666E+09 | 3829.42 | 02-OCT-16:41 | 15.10 | 7.59 | 97157163.03 | 69.55 | 18-OCT-21:10 | 14.60 | 7.02 |
November | 38510274.88 | 3216.33 | 06-NOV-16:01 | 7.12 | 2.52 | 91281991.64 | 56.69 | 21-NOV-04:19 | -9.4 | -10.7 |
December | 7948640.85 | 2099.94 | 06-DEC-16:01 | 8.95 | 4.16 | 92829514.88 | 56.69 | 19-DEC-04:19 | 2.57 | -0.5 |
Annual Sum or Average | 0.742381E+10 | 0.116304E+10 | ||||||||
Minimum of Months | 5560692.42 | 1048.04 | 6.60 | 2.52 | 84838829.54 | 56.69 | -21.1 | -21.8 | ||
Maximum of Months | 0.201425E+10 | 4430.07 | 26.10 | 11.83 | 0.105590E+09 | 91.64 | 25.00 | 12.63 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28972153.06 | 557.93 | 01-JAN-13:30 | 8.05 | 2.94 | 0.00 | 0.00 | 01-JAN-00:10 | 8.05 | 2.94 |
February | 0.117559E+09 | 699.49 | 27-FEB-13:30 | 17.75 | 6.76 | 0.00 | 0.00 | 01-FEB-00:10 | 17.75 | 6.76 |
March | 0.152848E+09 | 676.53 | 01-MAR-13:30 | 6.15 | 2.39 | 0.00 | 0.00 | 01-MAR-00:10 | 6.15 | 2.39 |
April | 0.211676E+09 | 602.02 | 06-APR-13:40 | 20.20 | 9.73 | 0.00 | 0.00 | 01-APR-00:10 | 20.20 | 9.73 |
May | 0.248661E+09 | 504.36 | 19-MAY-13:30 | 26.65 | 14.96 | 0.00 | 0.00 | 01-MAY-00:10 | 26.65 | 14.96 |
June | 0.448766E+09 | 485.47 | 24-JUN-13:30 | 29.15 | 14.70 | 0.00 | 0.00 | 01-JUN-00:10 | 29.15 | 14.70 |
July | 0.643926E+09 | 602.13 | 17-JUL-13:30 | 36.40 | 17.01 | 0.00 | 0.00 | 01-JUL-00:10 | 36.40 | 17.01 |
August | 0.680017E+09 | 689.27 | 30-AUG-13:30 | 26.15 | 14.29 | 0.00 | 0.00 | 01-AUG-00:10 | 26.15 | 14.29 |
September | 0.556207E+09 | 754.83 | 03-SEP-13:00 | 33.30 | 15.94 | 0.00 | 0.00 | 01-SEP-00:10 | 33.30 | 15.94 |
October | 0.394779E+09 | 812.36 | 18-OCT-13:00 | 24.40 | 10.82 | 0.00 | 0.00 | 01-OCT-00:10 | 24.40 | 10.82 |
November | 0.214505E+09 | 673.26 | 03-NOV-13:30 | 14.35 | 7.74 | 0.00 | 0.00 | 01-NOV-00:10 | 14.35 | 7.74 |
December | 22045112.40 | 302.70 | 12-DEC-14:30 | -2.2 | -5.4 | 0.00 | 0.00 | 01-DEC-00:10 | -2.2 | -5.4 |
Annual Sum or Average | 0.371996E+10 | 0.00 | ||||||||
Minimum of Months | 22045112.40 | 302.70 | -2.2 | -5.4 | 0.00 | 0.00 | -2.2 | -5.4 | ||
Maximum of Months | 0.680017E+09 | 812.36 | 36.40 | 17.01 | 0.00 | 0.00 | 36.40 | 17.01 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16947217.19 | 841.83 | 15-JAN-09:01 | 0.28 | -2.6 | 93994335.55 | 56.69 | 30-JAN-02:39 | -21.1 | -21.8 |
February | 44260217.56 | 902.53 | 27-FEB-16:01 | 17.78 | 6.92 | 85698303.62 | 56.69 | 21-FEB-22:19 | 17.78 | 6.92 |
March | 94393965.88 | 897.82 | 29-MAR-18:01 | 9.72 | 2.38 | 95790551.80 | 56.69 | 29-MAR-21:19 | 5.03 | 0.95 |
April | 0.232816E+09 | 1043.13 | 07-APR-15:01 | 21.60 | 8.87 | 94076870.61 | 68.73 | 07-APR-21:49 | 15.18 | 6.20 |
May | 0.381910E+09 | 1082.30 | 31-MAY-16:11 | 25.00 | 10.32 | 99814581.28 | 74.85 | 31-MAY-21:49 | 16.70 | 8.85 |
June | 0.605282E+09 | 1079.53 | 28-JUN-21:51 | 20.60 | 10.08 | 98933594.15 | 76.74 | 21-JUN-21:10 | 20.60 | 10.08 |
July | 0.735800E+09 | 1165.56 | 26-JUL-08:61 | 25.87 | 13.83 | 0.102377E+09 | 76.43 | 27-JUL-21:30 | 15.30 | 9.43 |
August | 0.630876E+09 | 1118.58 | 07-AUG-08:21 | 26.70 | 14.17 | 0.102229E+09 | 74.39 | 14-AUG-21:30 | 15.30 | 8.83 |
September | 0.429162E+09 | 1078.54 | 03-SEP-08:51 | 25.00 | 13.69 | 96417532.78 | 72.41 | 01-SEP-21:00 | 25.00 | 13.69 |
October | 0.238966E+09 | 1039.28 | 18-OCT-15:01 | 24.90 | 11.51 | 96895912.14 | 67.93 | 18-OCT-21:10 | 14.60 | 7.02 |
November | 90481968.18 | 881.30 | 04-NOV-15:01 | 16.60 | 7.90 | 92348394.93 | 56.69 | 17-NOV-23:10 | 11.95 | 6.50 |
December | 24370625.32 | 850.48 | 10-DEC-09:02 | 5.50 | 1.55 | 94317280.03 | 56.69 | 19-DEC-04:19 | 2.57 | -0.5 |
Annual Sum or Average | 0.352527E+10 | 0.115289E+10 | ||||||||
Minimum of Months | 16947217.19 | 841.83 | 0.28 | -2.6 | 85698303.62 | 56.69 | -21.1 | -21.8 | ||
Maximum of Months | 0.735800E+09 | 1165.56 | 26.70 | 14.17 | 0.102377E+09 | 76.74 | 25.00 | 13.69 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26160917.72 | 2002.73 | 15-JAN-16:02 | 3.53 | -1.3 | 93652743.80 | 56.69 | 17-JAN-04:19 | 2.77 | -1.0 |
February | 0.156894E+09 | 3219.74 | 27-FEB-16:01 | 17.78 | 6.92 | 86141482.82 | 56.69 | 03-FEB-04:19 | 17.78 | 6.92 |
March | 0.254514E+09 | 3126.85 | 22-MAR-15:01 | 11.10 | 4.06 | 96270053.74 | 56.69 | 17-MAR-03:20 | 11.10 | 4.06 |
April | 0.613157E+09 | 3379.64 | 06-APR-15:01 | 21.28 | 10.55 | 94280326.03 | 56.69 | 24-APR-22:10 | 9.82 | 5.44 |
May | 0.970967E+09 | 3427.20 | 31-MAY-18:01 | 23.53 | 10.12 | 98186251.01 | 56.69 | 18-MAY-21:49 | 23.53 | 10.12 |
June | 0.192243E+10 | 3316.69 | 10-JUN-18:02 | 21.42 | 10.67 | 95849612.21 | 56.70 | 21-JUN-23:00 | 18.90 | 15.67 |
July | 0.263052E+10 | 3271.81 | 07-JUL-18:01 | 19.67 | 8.84 | 99095301.70 | 56.70 | 19-JUL-23:30 | 18.30 | 13.83 |
August | 0.235778E+10 | 3599.50 | 11-AUG-15:01 | 30.60 | 13.32 | 99145066.05 | 56.69 | 01-AUG-00:00 | 30.60 | 13.32 |
September | 0.142397E+10 | 3218.65 | 30-SEP-18:01 | 19.03 | 10.15 | 95368592.73 | 56.70 | 06-SEP-21:40 | 19.03 | 10.15 |
October | 0.592205E+09 | 3506.85 | 18-OCT-15:01 | 24.90 | 11.51 | 97608250.96 | 56.69 | 01-OCT-01:10 | 24.90 | 11.51 |
November | 0.135038E+09 | 3085.96 | 02-NOV-15:01 | 8.67 | 3.38 | 92766173.16 | 56.69 | 21-NOV-04:19 | -9.4 | -10.7 |
December | 26449670.06 | 2236.44 | 10-DEC-16:01 | 5.22 | -0.8 | 93817165.67 | 56.69 | 08-DEC-04:19 | 5.22 | -0.8 |
Annual Sum or Average | 0.111101E+11 | 0.114218E+10 | ||||||||
Minimum of Months | 26160917.72 | 2002.73 | 3.53 | -1.3 | 86141482.82 | 56.69 | -9.4 | -10.7 | ||
Maximum of Months | 0.263052E+10 | 3599.50 | 30.60 | 13.32 | 99145066.05 | 56.70 | 30.60 | 15.67 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6983746.80 | 1202.49 | 17-JAN-09:03 | 3.07 | -0.4 | 92775894.11 | 56.69 | 30-JAN-02:39 | -21.1 | -21.8 |
February | 43693180.15 | 2968.41 | 26-FEB-09:01 | 8.17 | 2.28 | 84904367.92 | 56.69 | 17-FEB-04:19 | 8.17 | 2.28 |
March | 89138735.30 | 2822.83 | 27-MAR-15:01 | 9.82 | 2.90 | 95151087.82 | 56.69 | 17-MAR-03:20 | 9.82 | 2.90 |
April | 0.354636E+09 | 3185.28 | 07-APR-15:01 | 21.60 | 8.87 | 94565313.66 | 66.61 | 07-APR-21:40 | 15.37 | 6.28 |
May | 0.692705E+09 | 3527.83 | 31-MAY-08:51 | 17.80 | 8.92 | 0.100648E+09 | 74.91 | 19-MAY-21:40 | 17.80 | 8.92 |
June | 0.155887E+10 | 3761.14 | 21-JUN-08:32 | 20.73 | 14.43 | 0.101219E+09 | 81.97 | 21-JUN-21:10 | 22.52 | 15.91 |
July | 0.214581E+10 | 3955.21 | 17-JUL-08:61 | 25.65 | 15.88 | 0.105351E+09 | 78.26 | 11-JUL-21:10 | 25.65 | 15.88 |
August | 0.176701E+10 | 4026.76 | 11-AUG-08:51 | 26.10 | 11.83 | 0.104722E+09 | 77.15 | 10-AUG-21:00 | 26.10 | 11.83 |
September | 0.911818E+09 | 3344.25 | 04-SEP-08:31 | 26.33 | 14.69 | 97725103.38 | 75.17 | 01-SEP-21:40 | 26.33 | 14.69 |
October | 0.238060E+09 | 3276.05 | 18-OCT-15:01 | 24.90 | 11.51 | 97016770.18 | 67.26 | 18-OCT-21:10 | 14.60 | 7.02 |
November | 30300756.63 | 1953.57 | 06-NOV-09:01 | -0.0 | -1.8 | 91113187.23 | 56.69 | 28-NOV-04:19 | -5.9 | -7.1 |
December | 7252485.11 | 1172.55 | 20-DEC-09:03 | 1.05 | -2.0 | 92734855.72 | 56.69 | 19-DEC-04:19 | 1.05 | -2.0 |
Annual Sum or Average | 0.784628E+10 | 0.115793E+10 | ||||||||
Minimum of Months | 6983746.80 | 1172.55 | -0.0 | -2.0 | 84904367.92 | 56.69 | -21.1 | -21.8 | ||
Maximum of Months | 0.214581E+10 | 4026.76 | 26.33 | 15.88 | 0.105351E+09 | 81.97 | 26.33 | 15.91 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.774626E+09 | 1282.82 | 15-JAN-11:35 | 4.03 | -1.0 | 0.119966E+10 | 721.14 | 02-JAN-22:49 | 4.03 | -1.0 |
February | 0.140947E+10 | 1446.45 | 26-FEB-11:33 | 12.77 | 4.68 | 0.109611E+10 | 779.35 | 28-FEB-22:40 | -0.5 | -2.0 |
March | 0.224630E+10 | 1426.73 | 23-MAR-10:33 | 8.70 | 1.68 | 0.123097E+10 | 776.97 | 01-MAR-22:49 | 8.70 | 1.68 |
April | 0.291266E+10 | 1657.46 | 08-APR-10:33 | 12.43 | 6.03 | 0.124096E+10 | 829.34 | 25-APR-21:40 | 10.57 | 4.38 |
May | 0.330443E+10 | 1795.92 | 20-MAY-18:00 | 24.40 | 14.00 | 0.134075E+10 | 888.39 | 31-MAY-21:40 | 16.80 | 8.67 |
June | 0.392477E+10 | 2140.06 | 30-JUN-19:30 | 25.80 | 13.08 | 0.144990E+10 | 951.85 | 30-JUN-22:10 | 21.17 | 12.42 |
July | 0.450584E+10 | 2867.83 | 17-JUL-18:40 | 34.97 | 16.44 | 0.157043E+10 | 951.85 | 18-JUL-22:10 | 19.50 | 17.44 |
August | 0.438890E+10 | 2647.33 | 10-AUG-18:15 | 30.17 | 12.28 | 0.155623E+10 | 951.85 | 10-AUG-22:10 | 21.20 | 9.51 |
September | 0.376050E+10 | 2270.86 | 04-SEP-18:15 | 30.93 | 16.02 | 0.141157E+10 | 951.85 | 06-SEP-22:10 | 19.32 | 15.78 |
October | 0.322466E+10 | 1665.33 | 18-OCT-10:33 | 21.13 | 9.17 | 0.132121E+10 | 861.89 | 18-OCT-21:49 | 15.40 | 7.25 |
November | 0.210744E+10 | 1383.48 | 04-NOV-18:00 | 14.80 | 7.00 | 0.118623E+10 | 776.36 | 03-NOV-21:49 | 14.80 | 7.00 |
December | 0.987504E+09 | 1203.49 | 07-DEC-11:35 | 7.23 | 2.88 | 0.119927E+10 | 718.16 | 06-DEC-22:49 | 7.23 | 2.88 |
Annual Sum or Average | 0.335471E+11 | 0.158033E+11 | ||||||||
Minimum of Months | 0.774626E+09 | 1203.49 | 4.03 | -1.0 | 0.109611E+10 | 718.16 | -0.5 | -2.0 | ||
Maximum of Months | 0.450584E+10 | 2867.83 | 34.97 | 16.44 | 0.157043E+10 | 951.85 | 21.20 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11581289.36 | 3437.57 | 21-JAN-16:01 | 1.83 | -2.4 | 93143560.42 | 56.69 | 30-JAN-02:39 | -21.1 | -21.8 |
February | 0.137792E+09 | 3780.73 | 27-FEB-16:01 | 17.78 | 6.92 | 85470106.87 | 56.69 | 14-FEB-04:19 | 17.78 | 6.92 |
March | 0.214204E+09 | 3704.69 | 01-MAR-16:01 | 9.13 | 3.73 | 95405886.08 | 56.69 | 24-MAR-03:20 | -1.7 | -3.5 |
April | 0.548206E+09 | 3983.90 | 06-APR-15:01 | 21.28 | 10.55 | 93548819.34 | 56.69 | 24-APR-22:10 | 9.82 | 5.44 |
May | 0.104422E+10 | 4118.15 | 31-MAY-18:01 | 23.53 | 10.12 | 97654584.04 | 56.69 | 19-MAY-21:19 | 23.53 | 10.12 |
June | 0.178609E+10 | 3921.88 | 10-JUN-18:02 | 21.42 | 10.67 | 95510357.42 | 56.70 | 21-JUN-21:00 | 21.10 | 15.72 |
July | 0.246998E+10 | 3936.72 | 07-JUL-18:01 | 19.67 | 8.84 | 98898145.15 | 56.70 | 18-JUL-21:00 | 19.40 | 17.51 |
August | 0.216295E+10 | 4228.82 | 11-AUG-15:01 | 30.60 | 13.32 | 98835219.24 | 56.69 | 08-AUG-23:00 | 30.60 | 13.32 |
September | 0.132414E+10 | 3808.38 | 08-SEP-18:01 | 17.93 | 9.62 | 94909338.04 | 56.70 | 06-SEP-21:19 | 17.93 | 9.62 |
October | 0.492488E+09 | 4146.52 | 18-OCT-15:01 | 24.90 | 11.51 | 96925702.67 | 56.69 | 01-OCT-01:10 | 24.90 | 11.51 |
November | 0.106939E+09 | 3640.58 | 06-NOV-16:01 | 7.12 | 2.52 | 92137970.70 | 56.69 | 28-NOV-04:19 | -5.9 | -7.1 |
December | 14674800.32 | 3571.11 | 10-DEC-16:01 | 5.22 | -0.8 | 93301613.25 | 56.69 | 19-DEC-04:19 | 2.57 | -0.5 |
Annual Sum or Average | 0.103133E+11 | 0.113574E+10 | ||||||||
Minimum of Months | 11581289.36 | 3437.57 | 1.83 | -2.4 | 85470106.87 | 56.69 | -21.1 | -21.8 | ||
Maximum of Months | 0.246998E+10 | 4228.82 | 30.60 | 13.32 | 98898145.15 | 56.70 | 30.60 | 17.51 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2667328.42 | 1089.14 | 01-JAN-16:03 | 4.82 | 1.06 | 92453412.36 | 56.69 | 20-JAN-04:19 | -5.9 | -7.7 |
February | 36555224.39 | 3781.52 | 26-FEB-17:41 | 11.85 | 4.39 | 84404614.92 | 56.69 | 17-FEB-04:19 | 11.85 | 4.39 |
March | 83337723.81 | 3447.76 | 22-MAR-18:01 | 9.45 | 3.47 | 94184755.67 | 56.69 | 31-MAR-03:20 | -2.4 | -3.8 |
April | 0.272025E+09 | 4313.26 | 25-APR-19:02 | 14.03 | 6.74 | 94920628.75 | 90.65 | 25-APR-18:10 | 14.03 | 6.74 |
May | 0.713611E+09 | 4648.76 | 31-MAY-16:11 | 25.00 | 10.32 | 0.102842E+09 | 91.93 | 12-MAY-18:10 | 25.00 | 10.32 |
June | 0.144082E+10 | 4128.34 | 07-JUN-19:41 | 12.77 | 6.36 | 0.103095E+09 | 92.43 | 05-JUN-21:10 | 12.77 | 6.36 |
July | 0.205055E+10 | 4154.16 | 08-JUL-20:41 | 13.68 | 7.34 | 0.105812E+09 | 97.46 | 05-JUL-18:10 | 13.68 | 7.34 |
August | 0.159048E+10 | 4073.32 | 11-AUG-08:51 | 26.10 | 11.83 | 0.105742E+09 | 93.12 | 29-AUG-18:10 | 23.43 | 12.63 |
September | 0.818277E+09 | 3956.25 | 15-SEP-18:21 | 13.60 | 7.77 | 97996757.42 | 85.83 | 08-SEP-18:10 | 13.60 | 7.77 |
October | 0.163787E+09 | 3989.55 | 02-OCT-16:41 | 15.10 | 7.59 | 96478028.48 | 67.91 | 18-OCT-21:10 | 14.60 | 7.02 |
November | 24374004.97 | 2428.19 | 04-NOV-18:01 | 14.68 | 6.96 | 90634130.71 | 56.69 | 28-NOV-04:19 | -5.9 | -7.1 |
December | 3820055.68 | 2143.05 | 06-DEC-16:01 | 8.95 | 4.16 | 92460382.69 | 56.69 | 30-DEC-02:20 | -20.6 | -21.0 |
Annual Sum or Average | 0.720030E+10 | 0.116102E+10 | ||||||||
Minimum of Months | 2667328.42 | 1089.14 | 4.82 | 1.06 | 84404614.92 | 56.69 | -20.6 | -21.0 | ||
Maximum of Months | 0.205055E+10 | 4648.76 | 26.10 | 11.83 | 0.105812E+09 | 97.46 | 25.00 | 12.63 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155450E+09 | 2018.67 | 19-JAN-16:01 | -5.3 | -7.3 | 95269876.46 | 56.69 | 30-JAN-02:39 | -21.1 | -21.8 |
February | 0.328076E+09 | 2106.94 | 27-FEB-16:01 | 17.78 | 6.92 | 87395829.86 | 56.69 | 27-FEB-22:19 | 0.93 | -0.9 |
March | 0.374446E+09 | 2065.39 | 01-MAR-16:01 | 9.13 | 3.73 | 96879401.53 | 56.69 | 20-MAR-21:10 | 4.13 | 0.90 |
April | 0.483493E+09 | 2211.89 | 06-APR-15:01 | 21.28 | 10.55 | 94206990.64 | 56.69 | 24-APR-21:10 | 10.92 | 6.42 |
May | 0.622051E+09 | 2170.29 | 29-MAY-18:01 | 23.03 | 12.37 | 97976144.91 | 56.69 | 31-MAY-21:30 | 16.90 | 8.47 |
June | 0.987264E+09 | 2115.84 | 10-JUN-18:02 | 21.42 | 10.67 | 95530664.36 | 56.70 | 20-JUN-22:49 | 23.90 | 14.80 |
July | 0.139596E+10 | 2155.55 | 30-JUL-08:61 | 23.35 | 12.74 | 98883286.16 | 56.70 | 18-JUL-22:00 | 23.35 | 12.74 |
August | 0.141933E+10 | 2158.06 | 11-AUG-08:61 | 23.77 | 11.08 | 98919446.67 | 56.69 | 09-AUG-00:40 | 23.77 | 11.08 |
September | 0.110357E+10 | 2065.15 | 06-SEP-15:02 | 26.20 | 18.81 | 95281704.85 | 56.70 | 07-SEP-21:00 | 20.00 | 15.02 |
October | 0.755363E+09 | 2316.45 | 18-OCT-15:01 | 24.90 | 11.51 | 98033721.57 | 56.69 | 23-OCT-21:10 | 11.52 | 5.57 |
November | 0.404231E+09 | 2043.76 | 13-NOV-16:01 | 3.38 | -2.4 | 94008369.69 | 56.69 | 03-NOV-22:19 | 3.38 | -2.4 |
December | 0.159703E+09 | 2007.88 | 10-DEC-16:01 | 5.22 | -0.8 | 95670107.13 | 56.69 | 08-DEC-04:19 | 5.22 | -0.8 |
Annual Sum or Average | 0.818894E+10 | 0.114806E+10 | ||||||||
Minimum of Months | 0.155450E+09 | 2007.88 | -5.3 | -7.3 | 87395829.86 | 56.69 | -21.1 | -21.8 | ||
Maximum of Months | 0.141933E+10 | 2316.45 | 26.20 | 18.81 | 98919446.67 | 56.70 | 23.90 | 15.02 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.280436E+11 | 18370.18 | 05-JAN-22:53 | -23.9 | -24.4 | 0.175826E+11 | 11347.74 | 19-JAN-00:20 | -15.2 | -15.6 |
February | 0.264873E+11 | 17678.84 | 27-FEB-22:10 | 1.02 | -0.9 | 0.169488E+11 | 11347.66 | 14-FEB-04:19 | 1.02 | -0.9 |
March | 0.310807E+11 | 17865.31 | 29-MAR-21:10 | 5.32 | 1.04 | 0.190743E+11 | 11347.70 | 04-MAR-00:20 | 5.32 | 1.04 |
April | 0.328807E+11 | 19871.06 | 07-APR-21:53 | 15.00 | 6.12 | 0.185831E+11 | 11348.43 | 07-APR-22:10 | 14.63 | 5.97 |
May | 0.364331E+11 | 21430.50 | 19-MAY-21:10 | 20.32 | 12.17 | 0.192640E+11 | 11349.14 | 31-MAY-22:10 | 16.52 | 9.30 |
June | 0.394168E+11 | 22477.46 | 23-JUN-21:20 | 21.50 | 13.09 | 0.187425E+11 | 11374.87 | 23-JUN-21:19 | 21.50 | 13.09 |
July | 0.427290E+11 | 23166.16 | 17-JUL-21:20 | 26.33 | 14.15 | 0.193045E+11 | 11385.52 | 18-JUL-21:19 | 19.80 | 17.22 |
August | 0.413826E+11 | 22566.60 | 09-AUG-21:04 | 23.90 | 12.72 | 0.193730E+11 | 11386.85 | 08-AUG-21:19 | 23.90 | 12.72 |
September | 0.366914E+11 | 21509.34 | 06-SEP-21:52 | 19.40 | 15.72 | 0.186529E+11 | 11349.71 | 01-SEP-21:19 | 19.40 | 15.72 |
October | 0.340811E+11 | 19743.62 | 18-OCT-22:00 | 15.60 | 7.30 | 0.191792E+11 | 11348.41 | 18-OCT-21:19 | 15.60 | 7.30 |
November | 0.299377E+11 | 18571.28 | 17-NOV-23:00 | 12.20 | 6.70 | 0.183535E+11 | 11347.76 | 27-NOV-00:20 | -15.2 | -16.0 |
December | 0.285436E+11 | 17657.98 | 28-DEC-22:33 | -24.0 | -24.3 | 0.185315E+11 | 11347.70 | 18-DEC-00:20 | -24.0 | -24.3 |
Annual Sum or Average | 0.407708E+12 | 0.223590E+12 | ||||||||
Minimum of Months | 0.264873E+11 | 17657.98 | -24.0 | -24.4 | 0.169488E+11 | 11347.66 | -24.0 | -24.3 | ||
Maximum of Months | 0.427290E+11 | 23166.16 | 26.33 | 15.72 | 0.193730E+11 | 11386.85 | 23.90 | 17.22 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.313134E+11 | 19480.04 | 05-JAN-22:53 | -23.9 | -24.4 | 0.177700E+11 | 11347.76 | 19-JAN-00:20 | -15.2 | -15.6 |
February | 0.296806E+11 | 19472.03 | 27-FEB-22:10 | 1.02 | -0.9 | 0.171464E+11 | 11347.82 | 06-FEB-00:20 | 1.02 | -0.9 |
March | 0.348167E+11 | 19777.70 | 29-MAR-21:10 | 5.32 | 1.04 | 0.192326E+11 | 11347.73 | 24-MAR-03:20 | 5.32 | 1.04 |
April | 0.366097E+11 | 21538.15 | 07-APR-21:10 | 15.92 | 6.52 | 0.186645E+11 | 11348.44 | 07-APR-22:10 | 14.63 | 5.97 |
May | 0.401832E+11 | 22954.77 | 19-MAY-21:20 | 20.03 | 12.11 | 0.193156E+11 | 11391.34 | 19-MAY-21:19 | 20.03 | 12.11 |
June | 0.425942E+11 | 23703.32 | 23-JUN-21:20 | 21.50 | 13.09 | 0.187561E+11 | 11392.30 | 29-JUN-21:19 | 19.43 | 10.13 |
July | 0.457392E+11 | 24358.90 | 17-JUL-21:20 | 26.33 | 14.15 | 0.193095E+11 | 11401.07 | 21-JUL-21:19 | 19.43 | 11.17 |
August | 0.444387E+11 | 23747.16 | 09-AUG-21:04 | 23.90 | 12.72 | 0.193859E+11 | 11396.21 | 08-AUG-21:19 | 23.90 | 12.72 |
September | 0.399380E+11 | 22705.35 | 06-SEP-21:20 | 19.80 | 16.17 | 0.186871E+11 | 11371.96 | 01-SEP-21:19 | 19.80 | 16.17 |
October | 0.377919E+11 | 21263.69 | 18-OCT-22:00 | 15.60 | 7.30 | 0.192592E+11 | 11348.43 | 18-OCT-21:19 | 15.60 | 7.30 |
November | 0.335266E+11 | 20548.39 | 17-NOV-22:10 | 13.12 | 7.04 | 0.185084E+11 | 11347.79 | 27-NOV-00:20 | -15.2 | -16.0 |
December | 0.320463E+11 | 19519.57 | 05-DEC-23:00 | 9.40 | 4.71 | 0.187584E+11 | 11347.80 | 18-DEC-00:20 | -3.7 | -6.2 |
Annual Sum or Average | 0.448678E+12 | 0.224794E+12 | ||||||||
Minimum of Months | 0.296806E+11 | 19472.03 | -23.9 | -24.4 | 0.171464E+11 | 11347.73 | -15.2 | -16.0 | ||
Maximum of Months | 0.457392E+11 | 24358.90 | 26.33 | 16.17 | 0.193859E+11 | 11401.07 | 23.90 | 16.17 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.438168E+11 | 25851.93 | 15-JAN-11:40 | 4.03 | -1.0 | 0.187217E+11 | 11319.69 | 28-JAN-18:19 | -22.8 | -23.3 |
February | 0.417917E+11 | 27067.41 | 26-FEB-11:33 | 12.77 | 4.68 | 0.169829E+11 | 11319.69 | 04-FEB-18:19 | 12.77 | 4.68 |
March | 0.477433E+11 | 27562.70 | 23-MAR-10:33 | 8.70 | 1.68 | 0.188218E+11 | 11319.66 | 04-MAR-18:19 | 8.70 | 1.68 |
April | 0.485515E+11 | 28513.67 | 24-APR-10:33 | 15.20 | 9.23 | 0.182265E+11 | 11319.66 | 22-APR-17:19 | 15.20 | 9.23 |
May | 0.517208E+11 | 29400.95 | 13-MAY-10:33 | 21.13 | 9.82 | 0.188427E+11 | 11319.65 | 27-MAY-17:19 | 22.43 | 11.51 |
June | 0.530878E+11 | 30262.07 | 24-JUN-10:33 | 23.87 | 15.50 | 0.182534E+11 | 11319.65 | 10-JUN-17:19 | 23.87 | 15.50 |
July | 0.563581E+11 | 30549.05 | 15-JUL-10:40 | 25.37 | 16.04 | 0.188615E+11 | 11319.63 | 01-JUL-17:19 | 25.37 | 16.04 |
August | 0.554150E+11 | 30609.51 | 06-AUG-10:40 | 30.40 | 14.95 | 0.188670E+11 | 11319.64 | 05-AUG-17:19 | 30.40 | 14.95 |
September | 0.511442E+11 | 30217.93 | 02-SEP-10:33 | 29.27 | 15.45 | 0.182435E+11 | 11319.65 | 09-SEP-17:19 | 27.03 | 13.32 |
October | 0.500107E+11 | 28016.72 | 15-OCT-10:33 | 17.77 | 9.16 | 0.188367E+11 | 11319.59 | 21-OCT-17:19 | 13.53 | 6.33 |
November | 0.457701E+11 | 26616.58 | 03-NOV-10:33 | 10.30 | 6.27 | 0.182095E+11 | 11319.53 | 25-NOV-18:19 | -4.7 | -5.9 |
December | 0.448928E+11 | 25224.41 | 06-DEC-11:50 | 12.33 | 6.43 | 0.187908E+11 | 11319.68 | 30-DEC-18:19 | -16.8 | -17.4 |
Annual Sum or Average | 0.590303E+12 | 0.221658E+12 | ||||||||
Minimum of Months | 0.417917E+11 | 25224.41 | 4.03 | -1.0 | 0.169829E+11 | 11319.53 | -22.8 | -23.3 | ||
Maximum of Months | 0.563581E+11 | 30609.51 | 30.40 | 16.04 | 0.188670E+11 | 11319.69 | 30.40 | 16.04 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130064E+10 | 2983.27 | 15-JAN-11:35 | 4.03 | -1.0 | 0.126824E+10 | 745.70 | 09-JAN-04:00 | 4.03 | -1.0 |
February | 0.266772E+10 | 3360.67 | 26-FEB-11:33 | 12.77 | 4.68 | 0.115633E+10 | 802.07 | 27-FEB-22:30 | 0.85 | -0.9 |
March | 0.413333E+10 | 3250.41 | 23-MAR-10:33 | 8.70 | 1.68 | 0.129033E+10 | 790.64 | 28-MAR-21:30 | 2.50 | -1.5 |
April | 0.600289E+10 | 3795.96 | 25-APR-17:12 | 17.60 | 7.71 | 0.129373E+10 | 878.23 | 25-APR-21:30 | 10.85 | 4.52 |
May | 0.723512E+10 | 4297.65 | 20-MAY-17:40 | 25.90 | 14.28 | 0.140704E+10 | 956.32 | 19-MAY-21:30 | 25.90 | 14.28 |
June | 0.898506E+10 | 6081.56 | 23-JUN-13:30 | 31.40 | 15.21 | 0.151429E+10 | 1007.40 | 22-JUN-22:10 | 31.40 | 15.21 |
July | 0.105266E+11 | 7641.29 | 17-JUL-15:03 | 36.28 | 17.05 | 0.163402E+10 | 1007.42 | 26-JUL-23:10 | 19.85 | 12.29 |
August | 0.100088E+11 | 7076.13 | 07-AUG-14:10 | 32.80 | 15.97 | 0.161171E+10 | 1007.39 | 10-AUG-22:10 | 21.20 | 9.51 |
September | 0.824937E+10 | 6079.71 | 03-SEP-12:50 | 33.22 | 15.94 | 0.144513E+10 | 1002.80 | 04-SEP-23:10 | 20.78 | 13.41 |
October | 0.669070E+10 | 3786.80 | 18-OCT-16:20 | 23.50 | 10.80 | 0.135360E+10 | 898.50 | 18-OCT-21:40 | 15.20 | 7.20 |
November | 0.397437E+10 | 3125.71 | 04-NOV-17:13 | 15.33 | 7.21 | 0.124133E+10 | 806.18 | 03-NOV-21:40 | 15.33 | 7.21 |
December | 0.170742E+10 | 2787.26 | 07-DEC-11:35 | 7.23 | 2.88 | 0.126933E+10 | 749.95 | 05-DEC-22:40 | 7.23 | 2.88 |
Annual Sum or Average | 0.714820E+11 | 0.164851E+11 | ||||||||
Minimum of Months | 0.130064E+10 | 2787.26 | 4.03 | -1.0 | 0.115633E+10 | 745.70 | 0.85 | -1.5 | ||
Maximum of Months | 0.105266E+11 | 7641.29 | 36.28 | 17.05 | 0.163402E+10 | 1007.42 | 31.40 | 15.21 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127702E+10 | 3666.08 | 11-JAN-07:31 | -22.2 |
February | 0.367751E+09 | 1642.93 | 05-FEB-06:00 | -20.0 |
March | 0.174643E+09 | 1528.80 | 05-MAR-05:10 | -20.3 |
April | 10132050.50 | 397.14 | 29-APR-06:10 | -6.8 |
May | 5692753.17 | 282.22 | 08-MAY-08:61 | -1.6 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 1852585.10 | 287.36 | 10-OCT-06:40 | -6.1 |
November | 0.135543E+09 | 1040.72 | 27-NOV-07:05 | -13.5 |
December | 0.675902E+09 | 1976.03 | 29-DEC-07:10 | -26.0 |
Annual Sum or Average | 0.264853E+10 | |||
Minimum of Months | 0.00 | 0.00 | -26.0 | |
Maximum of Months | 0.127702E+10 | 3666.08 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6870211.19 | 172.42 | 09-JAN-12:20 | -25.4 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 4.98 |
December | 53835.89 | 34.23 | 31-DEC-16:00 | -21.7 |
Annual Sum or Average | 6924047.08 | |||
Minimum of Months | 0.00 | 0.00 | -25.4 | |
Maximum of Months | 6870211.19 | 172.42 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.655792E+09 | 1211.31 | 11-JAN-05:00 | -28.9 |
February | 0.169693E+09 | 644.09 | 05-FEB-17:50 | -18.1 |
March | 43093851.61 | 426.83 | 06-MAR-05:00 | -18.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 13551637.07 | 242.91 | 27-NOV-12:50 | -9.0 |
December | 0.196996E+09 | 868.73 | 31-DEC-16:00 | -21.7 |
Annual Sum or Average | 0.107913E+10 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.655792E+09 | 1211.31 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.681980E+09 | 989.19 | 11-JAN-07:31 | -22.2 |
February | 0.226488E+09 | 582.96 | 05-FEB-06:00 | -20.0 |
March | 71840635.20 | 438.14 | 05-MAR-05:40 | -19.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 39573431.80 | 307.28 | 27-NOV-15:00 | -8.3 |
December | 0.270574E+09 | 744.59 | 31-DEC-17:00 | -21.7 |
Annual Sum or Average | 0.129046E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.2 | |
Maximum of Months | 0.681980E+09 | 989.19 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.168023E+09 | 3588.49 | 11-JAN-07:31 | -22.2 |
February | 514209.12 | 322.48 | 04-FEB-09:03 | -19.8 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 4.98 |
December | 62171084.03 | 2045.30 | 29-DEC-09:40 | -25.4 |
Annual Sum or Average | 0.230709E+09 | |||
Minimum of Months | 0.00 | 0.00 | -25.4 | |
Maximum of Months | 0.168023E+09 | 3588.49 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174933E+10 | 3075.07 | 07-JAN-16:01 | -21.2 |
February | 0.861727E+09 | 3055.62 | 04-FEB-09:01 | -19.8 |
March | 0.582408E+09 | 3036.61 | 04-MAR-19:01 | -18.4 |
April | 0.182628E+09 | 2929.88 | 28-APR-08:61 | -2.7 |
May | 0.109693E+09 | 2935.77 | 08-MAY-08:61 | -1.6 |
June | 7261833.98 | 881.64 | 02-JUN-08:03 | 12.48 |
July | 1454192.16 | 883.57 | 21-JUL-08:04 | 20.97 |
August | 3000249.00 | 887.02 | 30-AUG-08:04 | 15.47 |
September | 32526673.28 | 1800.03 | 19-SEP-08:62 | 4.08 |
October | 0.126099E+09 | 2941.71 | 10-OCT-08:61 | -3.7 |
November | 0.547260E+09 | 3028.09 | 27-NOV-09:01 | -11.7 |
December | 0.132163E+10 | 3073.27 | 29-DEC-16:01 | -20.2 |
Annual Sum or Average | 0.552502E+10 | |||
Minimum of Months | 1454192.16 | 881.64 | -21.2 | |
Maximum of Months | 0.174933E+10 | 3075.07 | 20.97 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.210472E+10 | 3062.92 | 07-JAN-16:01 | -21.2 |
February | 0.112873E+10 | 3039.12 | 05-FEB-09:01 | -20.4 |
March | 0.767262E+09 | 3015.06 | 04-MAR-19:01 | -18.4 |
April | 0.220882E+09 | 2904.68 | 28-APR-08:61 | -2.7 |
May | 0.119618E+09 | 2913.22 | 08-MAY-08:61 | -1.6 |
June | 6829945.96 | 1135.18 | 04-JUN-08:53 | 18.90 |
July | 982998.81 | 1104.17 | 12-JUL-08:53 | 18.90 |
August | 3212663.11 | 1015.12 | 12-AUG-08:54 | 23.30 |
September | 44606987.55 | 2420.37 | 19-SEP-08:62 | 4.08 |
October | 0.201615E+09 | 2949.76 | 10-OCT-08:61 | -3.7 |
November | 0.779646E+09 | 3013.61 | 27-NOV-09:01 | -11.7 |
December | 0.162931E+10 | 3063.50 | 29-DEC-16:01 | -20.2 |
Annual Sum or Average | 0.700742E+10 | |||
Minimum of Months | 982998.81 | 1015.12 | -21.2 | |
Maximum of Months | 0.210472E+10 | 3063.50 | 23.30 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 60990488.04 | 397.80 | 11-JAN-06:00 | -32.8 |
February | 2421111.43 | 132.50 | 05-FEB-06:00 | -20.0 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 4.98 |
December | 25332466.65 | 277.89 | 31-DEC-06:00 | -26.1 |
Annual Sum or Average | 88744066.12 | |||
Minimum of Months | 0.00 | 0.00 | -32.8 | |
Maximum of Months | 60990488.04 | 397.80 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.366635E+09 | 888.31 | 29-JAN-16:01 | -20.1 |
February | 0.159778E+09 | 883.82 | 05-FEB-16:01 | -16.8 |
March | 62519207.56 | 868.81 | 04-MAR-16:01 | -17.8 |
April | 3442281.57 | 400.50 | 16-APR-15:04 | 19.50 |
May | 1668351.02 | 281.37 | 23-MAY-08:03 | 1.28 |
June | 196020.52 | 280.69 | 07-JUN-15:06 | 17.20 |
July | 111618.81 | 242.37 | 08-JUL-15:06 | 19.72 |
August | 118151.92 | 222.37 | 19-AUG-15:06 | 22.20 |
September | 608701.60 | 441.84 | 21-SEP-15:04 | 19.22 |
October | 2855294.28 | 492.56 | 02-OCT-15:04 | 16.02 |
November | 75382525.96 | 876.46 | 27-NOV-16:01 | -8.3 |
December | 0.229201E+09 | 886.18 | 29-DEC-16:01 | -20.2 |
Annual Sum or Average | 0.902516E+09 | |||
Minimum of Months | 111618.81 | 222.37 | -20.2 | |
Maximum of Months | 0.366635E+09 | 888.31 | 22.20 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171743E+10 | 2999.27 | 07-JAN-16:01 | -21.2 |
February | 0.853548E+09 | 2990.30 | 04-FEB-16:01 | -17.8 |
March | 0.564898E+09 | 2970.93 | 04-MAR-19:01 | -18.4 |
April | 0.197707E+09 | 2840.50 | 28-APR-08:61 | -2.7 |
May | 0.123221E+09 | 2870.58 | 08-MAY-08:61 | -1.6 |
June | 6699964.90 | 780.12 | 01-JUN-18:04 | 12.88 |
July | 506580.30 | 790.13 | 04-JUL-08:04 | 13.75 |
August | 1719525.33 | 687.94 | 17-AUG-18:04 | 9.40 |
September | 31702550.40 | 1567.87 | 13-SEP-08:62 | 6.88 |
October | 0.129049E+09 | 2836.56 | 05-OCT-08:61 | -1.0 |
November | 0.563915E+09 | 2956.91 | 27-NOV-19:01 | -8.3 |
December | 0.130896E+10 | 3000.04 | 29-DEC-16:01 | -20.2 |
Annual Sum or Average | 0.549936E+10 | |||
Minimum of Months | 506580.30 | 687.94 | -21.2 | |
Maximum of Months | 0.171743E+10 | 3000.04 | 13.75 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.206344E+10 | 2980.36 | 07-JAN-16:01 | -21.2 |
February | 0.111535E+10 | 2967.48 | 04-FEB-16:01 | -17.8 |
March | 0.731547E+09 | 2943.32 | 04-MAR-19:01 | -18.4 |
April | 0.235859E+09 | 2810.98 | 28-APR-08:61 | -2.7 |
May | 0.135606E+09 | 2842.46 | 08-MAY-08:61 | -1.6 |
June | 6894235.06 | 859.30 | 01-JUN-18:04 | 12.88 |
July | 440124.42 | 823.61 | 04-JUL-08:04 | 13.75 |
August | 1910216.89 | 836.78 | 18-AUG-21:44 | 15.60 |
September | 42651441.00 | 1597.81 | 13-SEP-08:62 | 6.88 |
October | 0.200935E+09 | 2816.17 | 05-OCT-08:61 | -1.0 |
November | 0.789856E+09 | 2942.19 | 27-NOV-16:01 | -8.3 |
December | 0.161024E+10 | 2982.91 | 29-DEC-16:01 | -20.2 |
Annual Sum or Average | 0.693472E+10 | |||
Minimum of Months | 440124.42 | 823.61 | -21.2 | |
Maximum of Months | 0.206344E+10 | 2982.91 | 15.60 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.928396E+09 | 1921.59 | 09-JAN-10:10 | -26.1 |
February | 0.237220E+09 | 1242.99 | 04-FEB-09:03 | -19.8 |
March | 57844470.47 | 866.60 | 06-MAR-07:05 | -19.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 255841.64 | 76.25 | 08-MAY-08:03 | -1.6 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 80887442.05 | 861.47 | 27-NOV-09:03 | -11.7 |
December | 0.450305E+09 | 1737.52 | 29-DEC-09:03 | -27.6 |
Annual Sum or Average | 0.175491E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.6 | |
Maximum of Months | 0.928396E+09 | 1921.59 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.253591E+10 | 3710.29 | 07-JAN-16:01 | -21.2 |
February | 0.133102E+10 | 3685.58 | 04-FEB-09:01 | -19.8 |
March | 0.989358E+09 | 3663.67 | 04-MAR-19:01 | -18.4 |
April | 0.383833E+09 | 3535.37 | 28-APR-08:61 | -2.7 |
May | 0.224182E+09 | 3531.62 | 08-MAY-08:61 | -1.6 |
June | 23266942.76 | 1107.85 | 16-JUN-08:63 | 2.70 |
July | 1192987.13 | 744.29 | 29-JUL-08:04 | 15.87 |
August | 11359275.05 | 1149.37 | 18-AUG-08:62 | 12.67 |
September | 0.101242E+09 | 3360.61 | 19-SEP-08:62 | 4.08 |
October | 0.303416E+09 | 3548.87 | 10-OCT-08:61 | -3.7 |
November | 0.931929E+09 | 3650.42 | 27-NOV-09:01 | -11.7 |
December | 0.198044E+10 | 3708.15 | 29-DEC-19:01 | -23.2 |
Annual Sum or Average | 0.881716E+10 | |||
Minimum of Months | 1192987.13 | 744.29 | -23.2 | |
Maximum of Months | 0.253591E+10 | 3710.29 | 15.87 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.296015E+10 | 3683.18 | 07-JAN-16:01 | -21.2 |
February | 0.167209E+10 | 3654.29 | 05-FEB-09:01 | -20.4 |
March | 0.123776E+10 | 3627.47 | 04-MAR-19:01 | -18.4 |
April | 0.444205E+09 | 3496.66 | 28-APR-08:61 | -2.7 |
May | 0.240967E+09 | 3494.05 | 08-MAY-08:61 | -1.6 |
June | 21327727.65 | 1154.98 | 16-JUN-08:63 | 2.70 |
July | 1129880.09 | 1074.57 | 22-JUL-08:53 | 18.30 |
August | 11449034.00 | 1189.11 | 18-AUG-08:62 | 12.67 |
September | 0.131652E+09 | 3347.21 | 19-SEP-08:62 | 4.08 |
October | 0.445599E+09 | 3530.47 | 10-OCT-08:61 | -3.7 |
November | 0.125358E+10 | 3621.23 | 26-NOV-19:01 | -13.9 |
December | 0.235746E+10 | 3682.86 | 29-DEC-16:01 | -20.2 |
Annual Sum or Average | 0.107774E+11 | |||
Minimum of Months | 1129880.09 | 1074.57 | -21.2 | |
Maximum of Months | 0.296015E+10 | 3683.18 | 18.30 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.861110E+09 | 1964.68 | 05-JAN-16:01 | -19.5 |
February | 0.360018E+09 | 1957.34 | 04-FEB-09:01 | -19.8 |
March | 0.258027E+09 | 1948.49 | 04-MAR-19:01 | -18.4 |
April | 0.107390E+09 | 1880.59 | 28-APR-08:61 | -2.7 |
May | 75877355.65 | 1879.01 | 08-MAY-08:61 | -1.6 |
June | 6348102.95 | 485.71 | 02-JUN-08:03 | 12.48 |
July | 991622.14 | 502.40 | 04-JUL-18:04 | 14.32 |
August | 1782235.51 | 428.05 | 09-AUG-08:04 | 25.28 |
September | 16932072.06 | 1134.75 | 12-SEP-15:02 | 5.50 |
October | 45887071.92 | 1859.87 | 05-OCT-08:61 | -1.0 |
November | 0.220443E+09 | 1935.69 | 27-NOV-09:01 | -11.7 |
December | 0.591001E+09 | 1962.61 | 28-DEC-16:02 | -20.7 |
Annual Sum or Average | 0.254581E+10 | |||
Minimum of Months | 991622.14 | 428.05 | -20.7 | |
Maximum of Months | 0.861110E+09 | 1964.68 | 25.28 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.373315E+10 | 8418.45 | 11-JAN-07:31 | -22.2 |
February | 0.110055E+10 | 3715.20 | 01-FEB-07:40 | -24.6 |
March | 0.400886E+09 | 3434.47 | 05-MAR-05:20 | -20.0 |
April | 2378456.51 | 421.97 | 29-APR-05:08 | -7.7 |
May | 384737.83 | 142.40 | 08-MAY-08:03 | -1.6 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.43 |
October | 1041783.29 | 297.88 | 10-OCT-06:40 | -6.1 |
November | 0.305259E+09 | 2375.31 | 27-NOV-07:10 | -13.5 |
December | 0.174498E+10 | 5423.15 | 29-DEC-08:02 | -27.9 |
Annual Sum or Average | 0.728864E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.9 | |
Maximum of Months | 0.373315E+10 | 8418.45 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.962539E+10 | 9271.23 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.869085E+10 | 9271.23 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.965507E+10 | 9271.23 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.929905E+10 | 9271.23 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.964208E+10 | 9271.23 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.934170E+10 | 9271.23 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.959943E+10 | 9271.23 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.965878E+10 | 9271.23 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.930276E+10 | 9271.23 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.962169E+10 | 9271.23 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.933428E+10 | 9271.23 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.959943E+10 | 9271.23 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.113371E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.869085E+10 | 9271.23 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.965878E+10 | 9271.23 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.531884E+09 | 512.31 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.480243E+09 | 512.31 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.533523E+09 | 512.31 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.513850E+09 | 512.31 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.532806E+09 | 512.31 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.516207E+09 | 512.31 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.530449E+09 | 512.31 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.533728E+09 | 512.31 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.514055E+09 | 512.31 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.531679E+09 | 512.31 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.515797E+09 | 512.31 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.530449E+09 | 512.31 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.626467E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.480243E+09 | 512.31 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.533728E+09 | 512.31 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.615923E+09 | 593.26 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.556123E+09 | 593.26 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.617822E+09 | 593.26 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.595041E+09 | 593.26 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.616991E+09 | 593.26 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.597770E+09 | 593.26 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.614262E+09 | 593.26 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.618059E+09 | 593.26 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.595278E+09 | 593.26 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.615686E+09 | 593.26 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.597295E+09 | 593.26 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.614262E+09 | 593.26 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.725451E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.556123E+09 | 593.26 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.618059E+09 | 593.26 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.710312E+09 | 684.18 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.641347E+09 | 684.18 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.712502E+09 | 684.18 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.686229E+09 | 684.18 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.711544E+09 | 684.18 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.689376E+09 | 684.18 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.708397E+09 | 684.18 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.712775E+09 | 684.18 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.686503E+09 | 684.18 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.710039E+09 | 684.18 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.688829E+09 | 684.18 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.708397E+09 | 684.18 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.836625E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.641347E+09 | 684.18 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.712775E+09 | 684.18 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.158446E+09 | 152.61 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.143062E+09 | 152.61 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.158934E+09 | 152.61 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.153074E+09 | 152.61 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.158720E+09 | 152.61 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.153776E+09 | 152.61 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.158018E+09 | 152.61 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.158995E+09 | 152.61 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.153135E+09 | 152.61 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.158385E+09 | 152.61 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.153654E+09 | 152.61 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.158018E+09 | 152.61 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.186622E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.143062E+09 | 152.61 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.158995E+09 | 152.61 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.415991E+09 | 400.68 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.375602E+09 | 400.68 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.417273E+09 | 400.68 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.401887E+09 | 400.68 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.416712E+09 | 400.68 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.403730E+09 | 400.68 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.414869E+09 | 400.68 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.417433E+09 | 400.68 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.402047E+09 | 400.68 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.415830E+09 | 400.68 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.403409E+09 | 400.68 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.414869E+09 | 400.68 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.489965E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.375602E+09 | 400.68 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.417433E+09 | 400.68 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.129706E+10 | 1573.46 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.109653E+10 | 1573.46 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.113098E+10 | 1573.46 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.978292E+09 | 1573.46 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.901698E+09 | 1573.46 | 01-MAY-19:30 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.770753E+09 | 1398.63 | 01-JUN-20:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.882721E+09 | 1573.46 | 03-JUL-19:30 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.929478E+09 | 1573.46 | 01-AUG-19:00 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.103504E+10 | 1573.46 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.118874E+10 | 1573.46 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.121254E+10 | 1573.46 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.129380E+10 | 1573.46 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.127177E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.770753E+09 | 1398.63 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.129706E+10 | 1573.46 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.106571E+11 | 10645.38 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.953042E+10 | 10645.38 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.104993E+11 | 10645.38 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.998843E+10 | 10645.38 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.102286E+11 | 10645.38 | 01-MAY-19:30 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.980816E+10 | 10433.88 | 01-JUN-19:00 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.101635E+11 | 10645.38 | 03-JUL-19:30 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.102831E+11 | 10645.38 | 01-AUG-19:00 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.100578E+11 | 10645.38 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.105262E+11 | 10645.38 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.102774E+11 | 10645.38 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.106260E+11 | 10645.38 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.122646E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.953042E+10 | 10433.88 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.106571E+11 | 10645.38 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82476868.03 | 74.62 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 74484663.28 | 74.62 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 81821381.83 | 74.62 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 79911301.67 | 74.62 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 82149124.93 | 74.62 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 79277307.08 | 74.62 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 82793865.32 | 74.62 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 81821381.83 | 74.62 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 79932793.28 | 74.62 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 82466122.22 | 74.62 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 79594304.38 | 74.62 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 82804611.13 | 74.62 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.969534E+09 | 0.300992E+10 | ||||
Minimum of Months | 74484663.28 | 74.62 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 82804611.13 | 74.62 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82499421.18 | 74.64 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 74505030.97 | 74.64 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 81843755.73 | 74.64 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 79933153.27 | 74.64 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 82171588.45 | 74.64 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 79298985.31 | 74.64 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 82816505.16 | 74.64 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 81843755.73 | 74.64 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 79954650.76 | 74.64 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 82488672.43 | 74.64 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 79616069.29 | 74.64 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 82827253.90 | 74.64 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.969799E+09 | 0.301074E+10 | ||||
Minimum of Months | 74505030.97 | 74.64 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 82827253.90 | 74.64 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.120431E+10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.108739E+10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.120803E+10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.116348E+10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.120640E+10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.116882E+10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.120107E+10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.120849E+10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.116395E+10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.120385E+10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.116789E+10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.120107E+10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.141847E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.108739E+10 | 1160.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120849E+10 | 1160.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131236E+09 | 118.74 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.118519E+09 | 118.74 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.130193E+09 | 118.74 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.127154E+09 | 118.74 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.130715E+09 | 118.74 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.126145E+09 | 118.74 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.131741E+09 | 118.74 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.130193E+09 | 118.74 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.127188E+09 | 118.74 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.131219E+09 | 118.74 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.126649E+09 | 118.74 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.131758E+09 | 118.74 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.154271E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.118519E+09 | 118.74 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.131758E+09 | 118.74 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.131221E+09 | 118.73 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.118505E+09 | 118.73 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.130178E+09 | 118.73 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.127139E+09 | 118.73 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.130699E+09 | 118.73 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.126130E+09 | 118.73 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.131725E+09 | 118.73 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.130178E+09 | 118.73 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.127173E+09 | 118.73 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.131204E+09 | 118.73 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.126635E+09 | 118.73 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.131742E+09 | 118.73 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.154253E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.118505E+09 | 118.73 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.131742E+09 | 118.73 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 82499421.18 | 74.64 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 74505030.97 | 74.64 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 81843755.73 | 74.64 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 79933153.27 | 74.64 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 82171588.45 | 74.64 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 79298985.31 | 74.64 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 82816505.16 | 74.64 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 81843755.73 | 74.64 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 79954650.76 | 74.64 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 82488672.43 | 74.64 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 79616069.29 | 74.64 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 82827253.90 | 74.64 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.969799E+09 | 0.301074E+10 | ||||
Minimum of Months | 74505030.97 | 74.64 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 82827253.90 | 74.64 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261613E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.228818E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.244417E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.223896E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.220121E+10 | 2763.12 | 01-MAY-19:30 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.202369E+10 | 2514.17 | 26-JUN-19:00 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.217512E+10 | 2763.12 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.222801E+10 | 2763.12 | 01-AUG-19:00 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.230400E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.251297E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.250122E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.261545E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.281491E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.202369E+10 | 2514.17 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.261613E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.261613E+10 | 2763.12 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.228818E+10 | 2763.12 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.244417E+10 | 2763.12 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.223896E+10 | 2763.12 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.220121E+10 | 2763.12 | 01-MAY-19:30 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.202369E+10 | 2514.17 | 26-JUN-19:00 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.217512E+10 | 2763.12 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.222801E+10 | 2763.12 | 01-AUG-19:00 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.230400E+10 | 2763.12 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.251297E+10 | 2763.12 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.250122E+10 | 2763.12 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.261545E+10 | 2763.12 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.281491E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.202369E+10 | 2514.17 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.261613E+10 | 2763.12 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113250E+10 | 1090.83 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.102255E+10 | 1090.83 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.113599E+10 | 1090.83 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.109410E+10 | 1090.83 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.113446E+10 | 1090.83 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.109912E+10 | 1090.83 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.112945E+10 | 1090.83 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.113643E+10 | 1090.83 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.109454E+10 | 1090.83 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.113207E+10 | 1090.83 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.109825E+10 | 1090.83 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.112945E+10 | 1090.83 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.133389E+11 | 0.424019E+12 | ||||
Minimum of Months | 0.102255E+10 | 1090.83 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.113643E+10 | 1090.83 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.127458E+10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.115083E+10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.127851E+10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.123137E+10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.127679E+10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.123701E+10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.127114E+10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.127900E+10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.123186E+10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.127409E+10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.123603E+10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.127114E+10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.150123E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.115083E+10 | 1227.68 | 0.00 | 0.00 | |
Maximum of Months | 0.127900E+10 | 1227.68 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.962539E+10 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.869085E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.965507E+10 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.929905E+10 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.964208E+10 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.934170E+10 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.959943E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.965878E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.930276E+10 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.962169E+10 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.933428E+10 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.959943E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.113371E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.869085E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.965878E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.531884E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236501E+09 |
February | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164079E+09 |
March | 0.199990E+10 | 0.533523E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159045E+09 |
April | 0.192973E+10 | 0.513850E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106451E+09 |
May | 0.199475E+10 | 0.532806E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 508020.94 | 85585101.27 |
June | 0.193394E+10 | 0.516207E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3505575.99 | 44465460.44 |
July | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9879620.46 | 26685701.78 |
August | 0.199896E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7171209.89 | 33725853.62 |
September | 0.192879E+10 | 0.514055E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2978350.52 | 57416561.25 |
October | 0.199148E+10 | 0.531679E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22961.46 | 97130908.57 |
November | 0.192552E+10 | 0.515797E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135616E+09 |
December | 0.199054E+10 | 0.530449E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193829E+09 |
Annual Sum or Average | 0.234744E+11 | 0.626467E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24065739.26 | 0.134053E+10 |
Minimum of Months | 0.179968E+10 | 0.480243E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26685701.78 |
Maximum of Months | 0.199990E+10 | 0.533728E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9879620.46 | 0.236501E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.615923E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92625865.83 |
February | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65064790.71 |
March | 0.231589E+10 | 0.617822E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64127042.80 |
April | 0.223463E+10 | 0.595041E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 219.20 | 44327085.98 |
May | 0.230993E+10 | 0.616991E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 204868.45 | 36644550.17 |
June | 0.223950E+10 | 0.597770E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1377889.44 | 20346633.35 |
July | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3844261.46 | 12740329.06 |
August | 0.231480E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2815293.67 | 15491227.01 |
September | 0.223354E+10 | 0.595278E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1183219.00 | 25046109.96 |
October | 0.230614E+10 | 0.615686E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15854.46 | 40977553.75 |
November | 0.222975E+10 | 0.597295E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55408521.43 |
December | 0.230505E+10 | 0.614262E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76843125.27 |
Annual Sum or Average | 0.271834E+11 | 0.725451E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9441605.68 | 0.549643E+09 |
Minimum of Months | 0.208403E+10 | 0.556123E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12740329.06 |
Maximum of Months | 0.231589E+10 | 0.618059E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3844261.46 | 92625865.83 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.710312E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215104E+09 |
February | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148341E+09 |
March | 0.489771E+09 | 0.712502E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144510E+09 |
April | 0.472586E+09 | 0.686229E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6666.89 | 98789450.05 |
May | 0.488511E+09 | 0.711544E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 610630.39 | 81942493.88 |
June | 0.473617E+09 | 0.689376E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3376554.96 | 46662606.27 |
July | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9035625.59 | 29712021.37 |
August | 0.489542E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6783763.06 | 35926202.93 |
September | 0.472357E+09 | 0.686503E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2945552.08 | 56792265.89 |
October | 0.487709E+09 | 0.710039E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76162.97 | 91912431.12 |
November | 0.471555E+09 | 0.688829E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124816E+09 |
December | 0.487480E+09 | 0.708397E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176170E+09 |
Annual Sum or Average | 0.574883E+10 | 0.836625E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22834955.93 | 0.125068E+10 |
Minimum of Months | 0.440737E+09 | 0.641347E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29712021.37 |
Maximum of Months | 0.489771E+09 | 0.712775E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9035625.59 | 0.215104E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.158446E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123868E+09 |
February | 0.339028E+09 | 0.143062E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85202854.10 |
March | 0.376747E+09 | 0.158934E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82560516.64 |
April | 0.363528E+09 | 0.153074E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4457.52 | 56006313.50 |
May | 0.375778E+09 | 0.158720E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 363891.30 | 46362442.82 |
June | 0.364321E+09 | 0.153776E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2007488.48 | 26188602.74 |
July | 0.374985E+09 | 0.158018E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5288284.91 | 16666997.69 |
August | 0.376571E+09 | 0.158995E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3970744.92 | 20085527.68 |
September | 0.363352E+09 | 0.153135E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1728959.18 | 31911992.97 |
October | 0.375161E+09 | 0.158385E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46140.48 | 51865300.27 |
November | 0.362735E+09 | 0.153654E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71148373.27 |
December | 0.374985E+09 | 0.158018E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101310E+09 |
Annual Sum or Average | 0.442217E+10 | 0.186622E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13409966.79 | 0.713177E+09 |
Minimum of Months | 0.339028E+09 | 0.143062E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16666997.69 |
Maximum of Months | 0.376747E+09 | 0.158995E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5288284.91 | 0.123868E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.415991E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308192E+09 |
February | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218999E+09 |
March | 0.155131E+10 | 0.417273E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214374E+09 |
April | 0.149688E+10 | 0.401887E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147375E+09 |
May | 0.154732E+10 | 0.416712E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 733735.17 | 0.120913E+09 |
June | 0.150015E+10 | 0.403730E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 4857562.84 | 64554571.70 |
July | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 13492033.89 | 38774745.89 |
August | 0.155059E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 10001231.95 | 47635611.09 |
September | 0.149615E+10 | 0.402047E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 4338585.84 | 79982826.38 |
October | 0.154478E+10 | 0.415830E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 86880.68 | 0.134194E+09 |
November | 0.149361E+10 | 0.403409E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185267E+09 |
December | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259089E+09 |
Annual Sum or Average | 0.182090E+11 | 0.489965E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 33510030.37 | 0.181935E+10 |
Minimum of Months | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38774745.89 |
Maximum of Months | 0.155131E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 13492033.89 | 0.308192E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.129706E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531158E+09 |
February | 0.236489E+11 | 0.109653E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374364E+09 |
March | 0.262800E+11 | 0.113098E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366179E+09 |
April | 0.253579E+11 | 0.978292E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251033E+09 |
May | 0.262123E+11 | 0.901698E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1008196.94 | 0.205966E+09 |
June | 0.254132E+11 | 0.770753E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7417336.85 | 0.112885E+09 |
July | 0.261570E+11 | 0.882721E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21522366.27 | 70198670.73 |
August | 0.262677E+11 | 0.929478E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15710703.49 | 86306335.29 |
September | 0.253456E+11 | 0.103504E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6480378.83 | 0.141087E+09 |
October | 0.261693E+11 | 0.118874E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50909.41 | 0.232697E+09 |
November | 0.253025E+11 | 0.121254E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315531E+09 |
December | 0.261570E+11 | 0.129380E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438362E+09 |
Annual Sum or Average | 0.308468E+12 | 0.127177E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52189891.80 | 0.312577E+10 |
Minimum of Months | 0.236489E+11 | 0.770753E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70198670.73 |
Maximum of Months | 0.262800E+11 | 0.129706E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21522366.27 | 0.531158E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.106571E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153731E+10 |
February | 0.702046E+11 | 0.953042E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109083E+10 |
March | 0.780153E+11 | 0.104993E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107560E+10 |
April | 0.752779E+11 | 0.998843E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1575.64 | 0.744803E+09 |
May | 0.778146E+11 | 0.102286E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2968689.81 | 0.614791E+09 |
June | 0.754422E+11 | 0.980816E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21726611.28 | 0.339089E+09 |
July | 0.776503E+11 | 0.101635E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61684343.97 | 0.210472E+09 |
August | 0.779788E+11 | 0.102831E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44985051.10 | 0.256913E+09 |
September | 0.752414E+11 | 0.100578E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18616190.23 | 0.419090E+09 |
October | 0.776868E+11 | 0.105262E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 145338.76 | 0.689723E+09 |
November | 0.751137E+11 | 0.102774E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.932159E+09 |
December | 0.776503E+11 | 0.106260E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128471E+10 |
Annual Sum or Average | 0.915726E+12 | 0.122646E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150128E+09 | 0.919549E+10 |
Minimum of Months | 0.702046E+11 | 0.953042E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210472E+09 |
Maximum of Months | 0.780153E+11 | 0.106571E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61684343.97 | 0.153731E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135625E+09 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93856964.84 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91275744.53 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6396.58 | 61104718.54 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 506533.92 | 49231651.84 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3000325.69 | 24483609.23 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7892211.14 | 13299124.22 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5923482.27 | 16978937.29 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2558184.51 | 31097149.70 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56098.38 | 54884656.68 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77799371.22 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111066E+09 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19943232.49 | 0.760703E+09 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13299124.22 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7892211.14 | 0.135625E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134772E+09 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92788786.78 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90156344.03 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 415.93 | 61158884.10 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 400109.86 | 50394878.32 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2814080.80 | 26521981.04 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7618426.51 | 15244202.38 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5623267.41 | 18833665.30 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2456812.89 | 31882807.41 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52387.30 | 54234862.89 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76486782.24 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110030E+09 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18965500.70 | 0.762505E+09 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15244202.38 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7618426.51 | 0.134772E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 82476868.03 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37133043.65 |
February | 0.00 | 74484663.28 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27649937.43 |
March | 0.00 | 81821381.83 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30090420.38 |
April | 0.00 | 79911301.67 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22301970.44 |
May | 0.00 | 82149124.93 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14888.27 | 19014763.84 |
June | 0.00 | 79277307.08 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 179447.69 | 11639143.82 |
July | 0.00 | 82793865.32 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 749772.45 | 7855095.71 |
August | 0.00 | 81821381.83 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 597148.40 | 9308300.16 |
September | 0.00 | 79932793.28 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 213657.83 | 13692557.40 |
October | 0.00 | 82466122.22 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21158429.98 |
November | 0.00 | 79594304.38 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26621624.56 |
December | 0.00 | 82804611.13 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33091503.69 |
Annual Sum or Average | 0.00 | 0.969534E+09 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1754914.64 | 0.259557E+09 |
Minimum of Months | 0.00 | 74484663.28 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7855095.71 |
Maximum of Months | 0.00 | 82804611.13 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 749772.45 | 37133043.65 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 82499421.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37892171.64 |
February | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26092255.68 |
March | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25408963.42 |
April | 0.293479E+09 | 79933153.27 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 291.03 | 17030101.84 |
May | 0.303504E+09 | 82171588.45 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 119080.98 | 13870195.50 |
June | 0.293842E+09 | 79298985.31 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 801539.63 | 7085628.21 |
July | 0.303141E+09 | 82816505.16 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2158399.38 | 3978889.89 |
August | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1603047.60 | 4965333.50 |
September | 0.293479E+09 | 79954650.76 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 705047.84 | 8723456.66 |
October | 0.303322E+09 | 82488672.43 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21179.99 | 15162689.95 |
November | 0.293661E+09 | 79616069.29 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21576010.27 |
December | 0.303141E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31031473.55 |
Annual Sum or Average | 0.357224E+10 | 0.969799E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5408586.44 | 0.212817E+09 |
Minimum of Months | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3978889.89 |
Maximum of Months | 0.303685E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2158399.38 | 37892171.64 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135679E+09 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94036525.85 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91629771.92 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6403.73 | 61390670.88 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 509136.86 | 49506213.99 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3001123.49 | 24636943.08 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7888105.51 | 13388597.54 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5924542.07 | 17108474.36 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2562135.00 | 31241740.21 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56417.27 | 55103553.30 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77845988.77 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111023E+09 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19947863.93 | 0.762591E+09 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13388597.54 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7888105.51 | 0.135679E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134825E+09 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92910805.61 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90674245.79 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 419.82 | 61327357.07 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 409488.09 | 50190052.65 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2802604.93 | 26476111.55 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7575780.08 | 15557824.01 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5578361.07 | 18862032.21 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2445883.11 | 31929967.74 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47487.13 | 54484190.99 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76396309.06 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109960E+09 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18860024.22 | 0.763594E+09 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15557824.01 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7575780.08 | 0.134825E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.120431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165406E+09 |
February | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113780E+09 |
March | 0.387034E+10 | 0.120803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110441E+09 |
April | 0.373454E+10 | 0.116348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4927.06 | 74834419.18 |
May | 0.386038E+10 | 0.120640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471235.89 | 61800769.80 |
June | 0.374269E+10 | 0.116882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2542880.96 | 35261612.60 |
July | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6735617.18 | 22660095.80 |
August | 0.386853E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5047247.79 | 27202111.46 |
September | 0.373273E+10 | 0.116395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2186195.82 | 42614432.86 |
October | 0.385404E+10 | 0.120385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54156.06 | 68461525.44 |
November | 0.372639E+10 | 0.116789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94163021.26 |
December | 0.385223E+10 | 0.120107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135197E+09 |
Annual Sum or Average | 0.454292E+11 | 0.141847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17042260.76 | 0.951822E+09 |
Minimum of Months | 0.348285E+10 | 0.108739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22660095.80 |
Maximum of Months | 0.387034E+10 | 0.120849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6735617.18 | 0.165406E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131236E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135488E+09 |
February | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93670360.50 |
March | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91065320.03 |
April | 0.293479E+09 | 0.127154E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5576.80 | 61010138.67 |
May | 0.303504E+09 | 0.130715E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 494532.43 | 49275222.21 |
June | 0.293842E+09 | 0.126145E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2950056.05 | 24590438.13 |
July | 0.303141E+09 | 0.131741E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7787385.49 | 13395959.29 |
August | 0.303685E+09 | 0.130193E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5846140.68 | 17063419.95 |
September | 0.293479E+09 | 0.127188E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2522453.73 | 31095168.99 |
October | 0.303322E+09 | 0.131219E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53658.75 | 54751488.12 |
November | 0.293661E+09 | 0.126649E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77590376.07 |
December | 0.303141E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110827E+09 |
Annual Sum or Average | 0.357224E+10 | 0.154271E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19659803.92 | 0.759823E+09 |
Minimum of Months | 0.273974E+09 | 0.118519E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13395959.29 |
Maximum of Months | 0.303685E+09 | 0.131758E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7787385.49 | 0.135488E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.131221E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134830E+09 |
February | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92673412.39 |
March | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89903587.78 |
April | 0.293479E+09 | 0.127139E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 330.14 | 61110304.18 |
May | 0.303504E+09 | 0.130699E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 391528.88 | 50651540.26 |
June | 0.293842E+09 | 0.126130E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2770512.41 | 26832863.63 |
July | 0.303141E+09 | 0.131725E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7524084.21 | 15396012.52 |
August | 0.303685E+09 | 0.130178E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5563340.98 | 18997182.35 |
September | 0.293479E+09 | 0.127173E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2429713.38 | 31813368.86 |
October | 0.303322E+09 | 0.131204E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55615.19 | 53948541.50 |
November | 0.293661E+09 | 0.126635E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76223444.63 |
December | 0.303141E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109994E+09 |
Annual Sum or Average | 0.357224E+10 | 0.154253E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18735125.18 | 0.762374E+09 |
Minimum of Months | 0.273974E+09 | 0.118505E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15396012.52 |
Maximum of Months | 0.303685E+09 | 0.131742E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7524084.21 | 0.134830E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 82499421.18 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70320428.33 |
February | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48796060.60 |
March | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47241568.76 |
April | 0.293479E+09 | 79933153.27 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2826.82 | 31512907.00 |
May | 0.303504E+09 | 82171588.45 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 253662.76 | 25375629.07 |
June | 0.293842E+09 | 79298985.31 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1512666.56 | 12597713.47 |
July | 0.303141E+09 | 82816505.16 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3991812.98 | 6856136.07 |
August | 0.303685E+09 | 81843755.73 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2993145.18 | 8766704.74 |
September | 0.293479E+09 | 79954650.76 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1289870.44 | 16064111.32 |
October | 0.303322E+09 | 82488672.43 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26237.03 | 28459149.61 |
November | 0.293661E+09 | 79616069.29 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40455938.88 |
December | 0.303141E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57765520.71 |
Annual Sum or Average | 0.357224E+10 | 0.969799E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10070221.78 | 0.394212E+09 |
Minimum of Months | 0.273974E+09 | 74505030.97 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6856136.07 |
Maximum of Months | 0.303685E+09 | 82827253.90 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3991812.98 | 70320428.33 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.261613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353515E+09 |
February | 0.415303E+11 | 0.228818E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252801E+09 |
March | 0.461508E+11 | 0.244417E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249431E+09 |
April | 0.445315E+11 | 0.223896E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174189E+09 |
May | 0.460320E+11 | 0.220121E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 537288.26 | 0.144375E+09 |
June | 0.446286E+11 | 0.202369E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4170591.88 | 79430899.20 |
July | 0.459349E+11 | 0.217512E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12739964.46 | 49011651.59 |
August | 0.461292E+11 | 0.222801E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9642125.37 | 59775935.53 |
September | 0.445099E+11 | 0.230400E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4016083.51 | 96721806.15 |
October | 0.459565E+11 | 0.251297E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42481.69 | 0.158737E+09 |
November | 0.444343E+11 | 0.250122E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215372E+09 |
December | 0.459349E+11 | 0.261545E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298010E+09 |
Annual Sum or Average | 0.541708E+12 | 0.281491E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 31148535.17 | 0.213137E+10 |
Minimum of Months | 0.415303E+11 | 0.202369E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49011651.59 |
Maximum of Months | 0.461508E+11 | 0.261613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12739964.46 | 0.353515E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.261613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355342E+09 |
February | 0.415303E+11 | 0.228818E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254757E+09 |
March | 0.461508E+11 | 0.244417E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251213E+09 |
April | 0.445315E+11 | 0.223896E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175257E+09 |
May | 0.460320E+11 | 0.220121E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 537105.75 | 0.145114E+09 |
June | 0.446286E+11 | 0.202369E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4163536.48 | 79628402.02 |
July | 0.459349E+11 | 0.217512E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12728079.58 | 49072103.50 |
August | 0.461292E+11 | 0.222801E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9623499.02 | 59950422.05 |
September | 0.445099E+11 | 0.230400E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4001117.81 | 97202501.54 |
October | 0.459565E+11 | 0.251297E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35216.10 | 0.159799E+09 |
November | 0.444343E+11 | 0.250122E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217093E+09 |
December | 0.459349E+11 | 0.261545E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300248E+09 |
Annual Sum or Average | 0.541708E+12 | 0.281491E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 31088554.73 | 0.214468E+10 |
Minimum of Months | 0.415303E+11 | 0.202369E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49072103.50 |
Maximum of Months | 0.461508E+11 | 0.261613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12728079.58 | 0.355342E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113250E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321211E+09 |
February | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228666E+09 |
March | 0.410691E+10 | 0.113599E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224587E+09 |
April | 0.396281E+10 | 0.109410E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156173E+09 |
May | 0.409635E+10 | 0.113446E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 483015.53 | 0.129223E+09 |
June | 0.397146E+10 | 0.109912E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 3735393.80 | 70838102.79 |
July | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 11409890.84 | 43664953.63 |
August | 0.410499E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 8621454.73 | 53402805.05 |
September | 0.396089E+10 | 0.109454E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 3585974.19 | 86615154.59 |
October | 0.408962E+10 | 0.113207E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 25610.29 | 0.142536E+09 |
November | 0.395417E+10 | 0.109825E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194337E+09 |
December | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270252E+09 |
Annual Sum or Average | 0.482060E+11 | 0.133389E+11 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 27861339.38 | 0.192151E+10 |
Minimum of Months | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43664953.63 |
Maximum of Months | 0.410691E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 11409890.84 | 0.321211E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.127458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293254E+09 |
February | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201817E+09 |
March | 0.409620E+10 | 0.127851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195636E+09 |
April | 0.395248E+10 | 0.123137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3639.07 | 0.132238E+09 |
May | 0.408566E+10 | 0.127679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 593777.84 | 0.109484E+09 |
June | 0.396110E+10 | 0.123701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3838026.57 | 61636103.65 |
July | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11395724.17 | 38987421.46 |
August | 0.409429E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8585153.63 | 46774604.83 |
September | 0.395056E+10 | 0.123186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3689533.59 | 73311402.81 |
October | 0.407896E+10 | 0.127409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61312.70 | 0.119406E+09 |
November | 0.394385E+10 | 0.123603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166557E+09 |
December | 0.407704E+10 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239867E+09 |
Annual Sum or Average | 0.480803E+11 | 0.150123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28167167.58 | 0.167897E+10 |
Minimum of Months | 0.368610E+10 | 0.115083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38987421.46 |
Maximum of Months | 0.409620E+10 | 0.127900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11395724.17 | 0.293254E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 9271.23 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 9271.23 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 9271.23 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 9271.23 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 9271.23 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 9271.23 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 9271.23 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 9271.23 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 9271.23 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 9271.23 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 9271.23 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 9271.23 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 512.31 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 170.83 | 10-JAN-22:00 |
February | 1169.53 | 01-FEB-00:10 | 512.31 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 142.07 | 01-FEB-04:20 |
March | 1169.53 | 01-MAR-00:10 | 512.31 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 135.87 | 04-MAR-24:00 |
April | 1169.53 | 01-APR-00:10 | 512.31 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 83.03 | 29-APR-04:40 |
May | 1169.53 | 01-MAY-00:10 | 512.31 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.59 | 20-MAY-16:00 | 67.36 | 08-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 512.31 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.41 | 29-JUN-13:00 | 56.58 | 15-JUN-04:00 |
July | 1169.53 | 01-JUL-00:10 | 512.31 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.70 | 17-JUL-16:00 | 41.91 | 08-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 512.31 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.76 | 05-AUG-16:00 | 40.39 | 28-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 512.31 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.77 | 02-SEP-17:00 | 58.43 | 17-SEP-03:00 |
October | 1169.53 | 01-OCT-23:10 | 512.31 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 | 18-OCT-14:00 | 78.25 | 10-OCT-07:00 |
November | 1169.53 | 01-NOV-00:10 | 512.31 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 113.43 | 26-NOV-08:00 |
December | 1169.53 | 01-DEC-00:10 | 512.31 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 152.34 | 31-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.39 | |||||
Maximum of Months | 1169.53 | 512.31 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 32.70 | 170.83 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 593.26 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 67.34 | 10-JAN-23:00 |
February | 1354.32 | 01-FEB-00:10 | 593.26 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 54.83 | 01-FEB-04:40 |
March | 1354.32 | 01-MAR-00:10 | 593.26 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 52.87 | 04-MAR-24:00 |
April | 1354.32 | 01-APR-00:10 | 593.26 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 | 07-APR-14:00 | 33.30 | 29-APR-04:00 |
May | 1354.32 | 01-MAY-00:10 | 593.26 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.38 | 20-MAY-16:00 | 27.39 | 07-MAY-24:00 |
June | 1354.32 | 01-JUN-00:10 | 593.26 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.43 | 29-JUN-13:00 | 24.27 | 15-JUN-04:00 |
July | 1354.32 | 01-JUL-00:10 | 593.26 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.62 | 17-JUL-16:00 | 18.85 | 08-JUL-04:00 |
August | 1354.32 | 01-AUG-00:10 | 593.26 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.26 | 06-AUG-16:00 | 18.24 | 28-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 593.26 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.07 | 03-SEP-16:00 | 24.93 | 17-SEP-03:00 |
October | 1354.32 | 01-OCT-23:10 | 593.26 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.58 | 18-OCT-14:00 | 31.66 | 10-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 593.26 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 44.88 | 26-NOV-08:00 |
December | 1354.32 | 01-DEC-00:10 | 593.26 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 59.16 | 29-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.24 | |||||
Maximum of Months | 1354.32 | 593.26 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 12.62 | 67.34 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 684.18 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 159.15 | 10-JAN-23:00 |
February | 286.42 | 01-FEB-00:10 | 684.18 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 129.60 | 01-FEB-04:30 |
March | 286.42 | 01-MAR-00:10 | 684.18 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 123.95 | 04-MAR-24:00 |
April | 286.42 | 01-APR-00:10 | 684.18 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.30 | 07-APR-14:00 | 75.73 | 29-APR-04:20 |
May | 286.42 | 01-MAY-00:10 | 684.18 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 | 20-MAY-16:00 | 61.99 | 07-MAY-24:00 |
June | 286.42 | 01-JUN-00:10 | 684.18 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.76 | 29-JUN-13:00 | 56.11 | 15-JUN-04:00 |
July | 286.42 | 01-JUL-00:10 | 684.18 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.93 | 17-JUL-16:00 | 43.47 | 08-JUL-04:00 |
August | 286.42 | 01-AUG-00:10 | 684.18 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.09 | 05-AUG-16:00 | 42.27 | 28-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 684.18 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.32 | 02-SEP-17:00 | 57.20 | 17-SEP-03:00 |
October | 286.42 | 01-OCT-23:10 | 684.18 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.28 | 18-OCT-14:00 | 72.66 | 10-OCT-07:00 |
November | 286.42 | 01-NOV-00:10 | 684.18 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 103.60 | 26-NOV-08:00 |
December | 286.42 | 01-DEC-00:10 | 684.18 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 139.81 | 29-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.27 | |||||
Maximum of Months | 286.42 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 29.93 | 159.15 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 152.61 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 91.76 | 10-JAN-23:00 |
February | 220.32 | 01-FEB-00:10 | 152.61 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 74.77 | 01-FEB-04:20 |
March | 220.32 | 01-MAR-00:10 | 152.61 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 71.51 | 04-MAR-24:00 |
April | 220.32 | 01-APR-00:10 | 152.61 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 | 07-APR-14:00 | 43.69 | 29-APR-04:10 |
May | 220.32 | 01-MAY-00:10 | 152.61 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.06 | 20-MAY-16:00 | 35.46 | 08-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 152.61 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.48 | 29-JUN-13:00 | 31.94 | 15-JUN-04:00 |
July | 220.32 | 01-JUL-00:10 | 152.61 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.21 | 17-JUL-16:00 | 24.69 | 08-JUL-04:00 |
August | 220.32 | 01-AUG-00:10 | 152.61 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.61 | 05-AUG-16:00 | 23.88 | 28-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 152.61 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.99 | 02-SEP-17:00 | 32.48 | 17-SEP-03:00 |
October | 220.32 | 01-OCT-23:10 | 152.61 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.13 | 18-OCT-14:00 | 41.18 | 10-OCT-07:00 |
November | 220.32 | 01-NOV-00:10 | 152.61 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 59.70 | 26-NOV-08:00 |
December | 220.32 | 01-DEC-00:10 | 152.61 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 80.66 | 29-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.88 | |||||
Maximum of Months | 220.32 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 17.21 | 91.76 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 400.68 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 217.30 | 10-JAN-23:00 |
February | 907.20 | 01-FEB-00:10 | 400.68 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 178.60 | 01-FEB-09:10 |
March | 907.20 | 01-MAR-00:10 | 400.68 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 180.54 | 04-MAR-24:00 |
April | 907.20 | 01-APR-00:10 | 400.68 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 109.88 | 29-APR-05:20 |
May | 907.20 | 01-MAY-00:10 | 400.68 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 22.76 | 20-MAY-16:00 | 94.46 | 08-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 400.68 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 27.84 | 29-JUN-13:00 | 75.66 | 16-JUN-09:00 |
July | 907.20 | 01-JUL-00:10 | 400.68 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 45.19 | 17-JUL-16:00 | 57.73 | 08-JUL-05:08 |
August | 907.20 | 01-AUG-00:10 | 400.68 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 42.14 | 06-AUG-16:00 | 59.27 | 28-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 400.68 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 38.14 | 03-SEP-16:00 | 80.81 | 17-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 400.68 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 6.66 | 18-OCT-14:00 | 108.24 | 10-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 400.68 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 152.49 | 26-NOV-08:00 |
December | 907.20 | 01-DEC-00:10 | 400.68 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 190.92 | 29-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 57.73 | ||||||
Maximum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 45.19 | 217.30 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1573.46 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 384.97 | 10-JAN-22:30 |
February | 15368.40 | 01-FEB-00:10 | 1573.46 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 314.05 | 01-FEB-04:50 |
March | 15368.40 | 01-MAR-00:10 | 1573.46 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 300.41 | 04-MAR-24:00 |
April | 15368.40 | 01-APR-00:10 | 1573.46 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 188.57 | 29-APR-04:00 |
May | 15368.40 | 01-MAY-00:10 | 1573.46 | 01-MAY-19:30 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.12 | 20-MAY-16:00 | 155.41 | 07-MAY-24:00 |
June | 15368.40 | 01-JUN-00:10 | 1398.63 | 01-JUN-20:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.11 | 29-JUN-13:00 | 137.24 | 15-JUN-04:00 |
July | 15368.40 | 01-JUL-00:10 | 1573.46 | 03-JUL-19:30 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.30 | 17-JUL-16:00 | 106.44 | 08-JUL-04:00 |
August | 15368.40 | 01-AUG-00:10 | 1573.46 | 01-AUG-19:00 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.59 | 05-AUG-16:00 | 101.69 | 17-AUG-01:00 |
September | 15368.40 | 01-SEP-00:10 | 1573.46 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.97 | 02-SEP-17:00 | 138.85 | 17-SEP-03:00 |
October | 15368.40 | 01-OCT-23:10 | 1573.46 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 | 18-OCT-14:00 | 179.71 | 10-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1573.46 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 250.76 | 26-NOV-08:00 |
December | 15368.40 | 01-DEC-00:10 | 1573.46 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 338.46 | 31-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1398.63 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.69 | |||||
Maximum of Months | 15368.40 | 1573.46 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 72.30 | 384.97 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 10645.38 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1101.87 | 10-JAN-23:00 |
February | 45622.98 | 01-FEB-00:10 | 10645.38 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 902.67 | 01-FEB-03:55 |
March | 45622.98 | 01-MAR-00:10 | 10645.38 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 875.87 | 04-MAR-24:00 |
April | 45622.98 | 01-APR-00:10 | 10645.38 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.63 | 07-APR-14:00 | 559.70 | 29-APR-04:00 |
May | 45622.98 | 01-MAY-00:10 | 10645.38 | 01-MAY-19:30 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.14 | 20-MAY-16:00 | 462.85 | 07-MAY-24:00 |
June | 45622.98 | 01-JUN-00:10 | 10433.88 | 01-JUN-19:00 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.13 | 29-JUN-13:00 | 408.26 | 15-JUN-04:00 |
July | 45622.98 | 01-JUL-00:10 | 10645.38 | 03-JUL-19:30 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.54 | 17-JUL-16:00 | 316.21 | 08-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 10645.38 | 01-AUG-19:00 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.96 | 05-AUG-16:00 | 300.51 | 28-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 10645.38 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.76 | 03-SEP-16:00 | 415.45 | 17-SEP-03:00 |
October | 45622.98 | 01-OCT-23:10 | 10645.38 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.11 | 18-OCT-14:00 | 534.34 | 10-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 10645.38 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 746.35 | 26-NOV-08:00 |
December | 45622.98 | 01-DEC-00:10 | 10645.38 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 968.01 | 29-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 10433.88 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.51 | |||||
Maximum of Months | 45622.98 | 10645.38 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 206.54 | 1101.87 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 101.54 | 10-JAN-23:00 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 82.72 | 01-FEB-04:10 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 79.13 | 04-MAR-24:00 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.58 | 06-APR-16:00 | 48.44 | 29-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.82 | 20-MAY-16:00 | 39.35 | 08-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.68 | 29-JUN-15:10 | 33.09 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.05 | 17-JUL-16:00 | 24.57 | 08-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.79 | 05-AUG-16:00 | 23.07 | 28-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.05 | 02-SEP-17:00 | 34.16 | 17-SEP-03:00 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 | 18-OCT-15:09 | 45.67 | 10-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 66.10 | 26-NOV-08:00 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 89.13 | 31-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.07 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 23.05 | 101.54 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 101.53 | 10-JAN-23:00 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 82.72 | 01-FEB-04:10 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 79.13 | 04-MAR-24:00 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 | 07-APR-15:07 | 48.44 | 29-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.82 | 20-MAY-16:00 | 39.35 | 08-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.68 | 29-JUN-15:10 | 33.09 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.07 | 17-JUL-16:00 | 24.57 | 08-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.79 | 05-AUG-16:00 | 23.07 | 28-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.05 | 02-SEP-17:00 | 34.16 | 17-SEP-03:00 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 | 18-OCT-15:10 | 45.66 | 10-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 66.09 | 26-NOV-08:00 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 89.12 | 31-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.07 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 23.07 | 101.53 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 74.62 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 25.47 | 10-JAN-23:00 |
February | 0.00 | 01-FEB-00:10 | 74.62 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 21.99 | 01-FEB-03:55 |
March | 0.00 | 01-MAR-00:10 | 74.62 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 21.84 | 04-MAR-24:00 |
April | 0.00 | 01-APR-00:10 | 74.62 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 14.37 | 28-APR-01:00 |
May | 0.00 | 01-MAY-00:10 | 74.62 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 20-MAY-16:00 | 12.66 | 03-MAY-09:00 |
June | 0.00 | 01-JUN-00:10 | 74.62 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.21 | 29-JUN-13:00 | 11.35 | 15-JUN-04:00 |
July | 0.00 | 01-JUL-00:10 | 74.62 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 | 17-JUL-16:00 | 9.14 | 08-JUL-04:00 |
August | 0.00 | 01-AUG-00:10 | 74.62 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 | 05-AUG-16:00 | 8.91 | 28-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 74.62 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.09 | 02-SEP-17:00 | 11.79 | 17-SEP-03:00 |
October | 0.00 | 01-OCT-00:10 | 74.62 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 14.53 | 10-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 74.62 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 19.44 | 26-NOV-08:40 |
December | 0.00 | 01-DEC-00:10 | 74.62 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 22.10 | 29-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 74.62 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.91 | |||||
Maximum of Months | 0.00 | 74.62 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 | 25.47 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 74.64 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 28.34 | 10-JAN-23:00 |
February | 180.00 | 01-FEB-00:10 | 74.64 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 23.09 | 01-FEB-04:10 |
March | 180.00 | 01-MAR-00:10 | 74.64 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 22.09 | 04-MAR-24:00 |
April | 180.00 | 01-APR-00:10 | 74.64 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 | 07-APR-15:10 | 13.52 | 29-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 74.64 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.58 | 20-MAY-16:00 | 10.98 | 08-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 74.64 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.38 | 29-JUN-15:10 | 9.23 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 74.64 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.44 | 17-JUL-16:00 | 6.86 | 08-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 74.64 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.80 | 05-AUG-16:00 | 6.44 | 28-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 74.64 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.32 | 02-SEP-17:00 | 9.53 | 17-SEP-03:00 |
October | 180.00 | 01-OCT-00:10 | 74.64 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.55 | 18-OCT-15:07 | 12.75 | 10-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 74.64 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 18.45 | 26-NOV-08:00 |
December | 180.00 | 01-DEC-00:10 | 74.64 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 24.87 | 31-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.44 | |||||
Maximum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6.44 | 28.34 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 101.54 | 10-JAN-23:00 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 82.72 | 01-FEB-04:10 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 79.14 | 04-MAR-24:00 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.58 | 06-APR-16:00 | 48.44 | 29-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.82 | 20-MAY-16:00 | 39.35 | 08-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.68 | 29-JUN-15:10 | 33.09 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.07 | 17-JUL-16:00 | 24.57 | 08-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.79 | 05-AUG-16:00 | 23.07 | 28-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.05 | 02-SEP-17:00 | 34.16 | 17-SEP-03:00 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 | 18-OCT-15:10 | 45.67 | 10-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 66.10 | 26-NOV-08:00 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 89.12 | 31-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.07 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 23.07 | 101.54 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 101.53 | 10-JAN-23:00 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 82.72 | 01-FEB-04:10 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 79.13 | 04-MAR-24:00 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 | 07-APR-15:07 | 48.44 | 29-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.82 | 20-MAY-16:00 | 39.35 | 08-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.68 | 29-JUN-15:08 | 33.09 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.07 | 17-JUL-16:00 | 24.57 | 08-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.79 | 05-AUG-16:00 | 23.07 | 28-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.05 | 02-SEP-17:00 | 34.16 | 17-SEP-03:00 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 | 18-OCT-15:07 | 45.66 | 10-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 66.09 | 26-NOV-08:00 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 89.12 | 31-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.07 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 23.07 | 101.53 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1160.00 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 122.54 | 10-JAN-23:00 |
February | 2263.36 | 01-FEB-00:10 | 1160.00 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 99.80 | 01-FEB-04:20 |
March | 2263.36 | 01-MAR-00:10 | 1160.00 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 95.46 | 04-MAR-24:00 |
April | 2263.36 | 01-APR-00:10 | 1160.00 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.81 | 07-APR-14:00 | 58.35 | 29-APR-05:00 |
May | 2263.36 | 01-MAY-00:10 | 1160.00 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.15 | 20-MAY-16:00 | 47.36 | 08-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 1160.00 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.71 | 29-JUN-13:00 | 42.99 | 15-JUN-04:00 |
July | 2263.36 | 01-JUL-00:10 | 1160.00 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.88 | 17-JUL-16:00 | 33.26 | 08-JUL-04:00 |
August | 2263.36 | 01-AUG-00:10 | 1160.00 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.34 | 05-AUG-16:00 | 31.90 | 28-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1160.00 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.02 | 02-SEP-17:00 | 43.30 | 17-SEP-03:00 |
October | 2263.36 | 01-OCT-23:10 | 1160.00 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.88 | 18-OCT-14:00 | 55.00 | 10-OCT-07:00 |
November | 2263.36 | 01-NOV-00:10 | 1160.00 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 79.70 | 26-NOV-08:00 |
December | 2263.36 | 01-DEC-00:10 | 1160.00 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 107.66 | 29-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.90 | ||||
Maximum of Months | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.88 | 122.54 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 101.67 | 10-JAN-23:00 |
February | 180.00 | 01-FEB-00:10 | 118.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 82.85 | 01-FEB-04:10 |
March | 180.00 | 01-MAR-00:10 | 118.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 79.26 | 04-MAR-24:00 |
April | 180.00 | 01-APR-00:10 | 118.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 | 06-APR-16:00 | 48.55 | 29-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 118.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.73 | 20-MAY-16:00 | 39.46 | 08-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 118.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.60 | 29-JUN-15:10 | 33.19 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 118.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.57 | 17-JUL-16:00 | 24.67 | 08-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 118.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.70 | 05-AUG-16:00 | 23.17 | 28-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 118.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.97 | 02-SEP-17:00 | 34.27 | 17-SEP-03:00 |
October | 180.00 | 01-OCT-00:10 | 118.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.47 | 18-OCT-15:09 | 45.78 | 10-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 118.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 66.22 | 26-NOV-08:00 |
December | 180.00 | 01-DEC-00:10 | 118.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 89.25 | 31-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | |||||
Maximum of Months | 180.00 | 118.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 22.57 | 101.67 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 118.73 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 101.67 | 10-JAN-23:00 |
February | 180.00 | 01-FEB-00:10 | 118.73 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 82.84 | 01-FEB-04:10 |
March | 180.00 | 01-MAR-00:10 | 118.73 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 79.26 | 04-MAR-24:00 |
April | 180.00 | 01-APR-00:10 | 118.73 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 | 07-APR-15:06 | 48.55 | 29-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 118.73 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.73 | 20-MAY-16:00 | 39.45 | 08-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 118.73 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.60 | 29-JUN-15:10 | 33.19 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 118.73 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.68 | 17-JUL-16:00 | 24.66 | 08-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 118.73 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.71 | 05-AUG-16:00 | 23.17 | 28-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 118.73 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.97 | 02-SEP-17:00 | 34.26 | 17-SEP-03:00 |
October | 180.00 | 01-OCT-00:10 | 118.73 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.47 | 18-OCT-15:09 | 45.77 | 10-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 118.73 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 66.21 | 26-NOV-08:00 |
December | 180.00 | 01-DEC-00:10 | 118.73 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 89.25 | 31-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | |||||
Maximum of Months | 180.00 | 118.73 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 22.68 | 101.67 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 74.64 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 52.02 | 10-JAN-23:00 |
February | 180.00 | 01-FEB-00:10 | 74.64 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 42.39 | 01-FEB-04:10 |
March | 180.00 | 01-MAR-00:10 | 74.64 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 40.55 | 04-MAR-24:00 |
April | 180.00 | 01-APR-00:10 | 74.64 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 | 06-APR-15:55 | 24.84 | 29-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 74.64 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.52 | 20-MAY-16:00 | 20.19 | 08-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 74.64 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.98 | 29-JUN-15:10 | 16.98 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 74.64 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 | 17-JUL-16:00 | 12.62 | 08-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 74.64 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.60 | 05-AUG-16:00 | 11.86 | 28-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 74.64 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.70 | 02-SEP-17:00 | 17.53 | 17-SEP-03:00 |
October | 180.00 | 01-OCT-00:10 | 74.64 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 | 18-OCT-15:10 | 23.42 | 10-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 74.64 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 33.88 | 26-NOV-08:00 |
December | 180.00 | 01-DEC-00:10 | 74.64 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 45.66 | 31-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.86 | |||||
Maximum of Months | 180.00 | 74.64 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 | 52.02 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 247.76 | 10-JAN-23:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 206.03 | 01-FEB-03:32 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 205.32 | 04-MAR-24:00 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 130.33 | 29-APR-04:40 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:30 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.88 | 20-MAY-16:00 | 107.91 | 08-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2514.17 | 26-JUN-19:00 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.57 | 29-JUN-13:00 | 92.38 | 15-JUN-04:00 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.01 | 17-JUL-16:00 | 71.35 | 08-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:00 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.42 | 05-AUG-16:00 | 67.83 | 28-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.18 | 02-SEP-17:00 | 95.04 | 17-SEP-03:00 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 | 18-OCT-14:00 | 123.46 | 10-OCT-05:10 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 173.99 | 26-NOV-08:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 217.71 | 29-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2514.17 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.83 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 46.01 | 247.76 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2763.12 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 247.76 | 10-JAN-23:00 |
February | 26988.77 | 01-FEB-00:10 | 2763.12 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 206.89 | 01-FEB-03:32 |
March | 26988.77 | 01-MAR-00:10 | 2763.12 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 206.08 | 04-MAR-24:00 |
April | 26988.77 | 01-APR-00:10 | 2763.12 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 130.33 | 29-APR-04:30 |
May | 26988.77 | 01-MAY-00:10 | 2763.12 | 01-MAY-19:30 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.88 | 20-MAY-16:00 | 107.91 | 08-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 2514.17 | 26-JUN-19:00 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.57 | 29-JUN-13:00 | 92.38 | 15-JUN-04:00 |
July | 26988.77 | 01-JUL-00:10 | 2763.12 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.01 | 17-JUL-16:00 | 71.35 | 08-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2763.12 | 01-AUG-19:00 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.42 | 05-AUG-16:00 | 67.83 | 28-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2763.12 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.18 | 02-SEP-17:00 | 95.05 | 17-SEP-03:00 |
October | 26988.77 | 01-OCT-23:10 | 2763.12 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.30 | 18-OCT-14:00 | 123.46 | 10-OCT-05:10 |
November | 26988.77 | 01-NOV-00:10 | 2763.12 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 173.99 | 26-NOV-08:00 |
December | 26988.77 | 01-DEC-00:10 | 2763.12 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 217.72 | 29-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2514.17 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.83 | |||||
Maximum of Months | 26988.77 | 2763.12 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 46.01 | 247.76 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1090.83 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 221.80 | 10-JAN-23:00 |
February | 2401.70 | 01-FEB-00:10 | 1090.83 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 182.48 | 01-FEB-09:00 |
March | 2401.70 | 01-MAR-00:10 | 1090.83 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 184.47 | 04-MAR-24:00 |
April | 2401.70 | 01-APR-00:10 | 1090.83 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 116.29 | 29-APR-05:10 |
May | 2401.70 | 01-MAY-00:10 | 1090.83 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 18.73 | 20-MAY-16:00 | 96.59 | 08-MAY-06:00 |
June | 2401.70 | 01-JUN-00:10 | 1090.83 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 25.61 | 29-JUN-13:00 | 80.48 | 15-JUN-04:00 |
July | 2401.70 | 01-JUL-00:10 | 1090.83 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 41.23 | 17-JUL-16:00 | 63.68 | 08-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 1090.83 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 36.23 | 05-AUG-16:00 | 60.71 | 28-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1090.83 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 32.42 | 02-SEP-17:00 | 82.77 | 17-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1090.83 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 2.94 | 18-OCT-14:30 | 110.61 | 10-OCT-07:00 |
November | 2401.70 | 01-NOV-00:10 | 1090.83 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 155.74 | 26-NOV-08:00 |
December | 2401.70 | 01-DEC-00:10 | 1090.83 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 194.86 | 29-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 60.71 | ||||||
Maximum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 41.23 | 221.80 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1227.68 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 215.99 | 10-JAN-22:00 |
February | 2395.44 | 01-FEB-00:10 | 1227.68 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 176.86 | 01-FEB-04:20 |
March | 2395.44 | 01-MAR-00:10 | 1227.68 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 169.16 | 04-MAR-24:00 |
April | 2395.44 | 01-APR-00:10 | 1227.68 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.06 | 07-APR-14:00 | 103.49 | 29-APR-04:10 |
May | 2395.44 | 01-MAY-00:10 | 1227.68 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.12 | 20-MAY-16:00 | 84.03 | 08-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 1227.68 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.03 | 29-JUN-13:00 | 73.30 | 15-JUN-04:00 |
July | 2395.44 | 01-JUL-00:10 | 1227.68 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.30 | 17-JUL-16:00 | 56.57 | 12-JUL-04:03 |
August | 2395.44 | 01-AUG-00:10 | 1227.68 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.41 | 05-AUG-16:00 | 54.50 | 28-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1227.68 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.69 | 02-SEP-17:00 | 73.82 | 17-SEP-03:00 |
October | 2395.44 | 01-OCT-23:10 | 1227.68 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 | 18-OCT-14:00 | 97.55 | 10-OCT-07:00 |
November | 2395.44 | 01-NOV-00:10 | 1227.68 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 141.27 | 26-NOV-08:00 |
December | 2395.44 | 01-DEC-00:10 | 1227.68 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 190.75 | 29-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.50 | ||||
Maximum of Months | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.30 | 215.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 21042.24 | 28-JAN-01:00 | 11501.89 | 2060.25 | 3041.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16854.77 | 01-FEB-03:55 | 23003.78 | 2060.25 | 4055.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10701.31 | 01-MAR-21:00 | 8945.92 | 9271.23 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10031.52 | 08-APR-10:33 | 11501.89 | 7726.12 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10913.15 | 13-MAY-10:33 | 11501.89 | 7726.12 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11511.59 | 24-JUN-10:33 | 11501.89 | 7726.12 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 12284.13 | 17-JUL-18:10 | 53675.50 | 49446.67 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13162.75 | 17-AUG-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16374.88 | 28-SEP-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17666.79 | 20-OCT-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17335.51 | 01-NOV-21:00 | 10223.90 | 8241.11 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20248.15 | 29-DEC-09:00 | 5111.95 | 4120.49 | 5069.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 10031.52 | 5111.95 | 2060.25 | 3041.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21042.24 | 53675.50 | 49446.67 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3193.04 | 15-JAN-13:30 | 259.90 | 113.85 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.20 |
February | 4105.26 | 26-FEB-13:00 | 389.84 | 170.77 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.95 |
March | 3866.08 | 01-MAR-13:40 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.37 |
April | 3492.05 | 06-APR-13:40 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 |
May | 3040.20 | 20-MAY-12:40 | 389.84 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 | 0.00 |
June | 3032.40 | 23-JUN-13:10 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 18.02 | 0.00 |
July | 3866.71 | 17-JUL-13:20 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 30.59 | 0.00 |
August | 4242.59 | 09-AUG-13:20 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 23.68 | 0.00 |
September | 4593.50 | 03-SEP-12:40 | 259.90 | 113.85 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 22.72 | 0.00 |
October | 4692.93 | 18-OCT-13:10 | 519.79 | 284.62 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 1.27 | 0.00 |
November | 3813.36 | 03-NOV-13:10 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.16 |
December | 2415.74 | 12-DEC-12:30 | 259.90 | 142.31 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2415.74 | 259.90 | 113.85 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4692.93 | 519.79 | 284.62 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 30.59 | 75.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1652.55 | 05-JAN-22:53 | 5417.28 | 1582.03 | 2340.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.21 |
February | 1620.66 | 01-FEB-03:43 | 4062.96 | 197.75 | 501.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.08 |
March | 1234.45 | 01-MAR-22:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.02 |
April | 1501.77 | 06-APR-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.86 |
May | 1719.92 | 19-MAY-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.40 |
June | 1935.51 | 23-JUN-20:02 | 9630.72 | 4218.74 | 6017.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 2163.60 | 17-JUL-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 | 0.00 |
August | 2121.81 | 07-AUG-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
September | 1945.86 | 01-SEP-20:10 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.90 |
October | 1672.64 | 18-OCT-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.81 |
November | 1279.56 | 03-NOV-21:00 | 1203.84 | 527.34 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.93 |
December | 1575.90 | 28-DEC-22:33 | 4062.96 | 1186.52 | 1755.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1234.45 | 1203.84 | 197.75 | 501.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2163.60 | 9630.72 | 4218.74 | 6017.16 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 | 54.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 723.98 | 02-JAN-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.92 |
February | 820.48 | 27-FEB-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.13 |
March | 784.26 | 02-MAR-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.25 |
April | 916.61 | 08-APR-10:33 | 286.42 | 570.15 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.88 |
May | 1002.41 | 20-MAY-18:10 | 1145.66 | 3192.82 | 4241.42 | 0.00 | 0.00 | 0.00 | 0.00 | 1.55 | 0.00 |
June | 1489.08 | 23-JUN-21:00 | 254.59 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.43 |
July | 1777.87 | 17-JUL-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 0.00 |
August | 1713.35 | 10-AUG-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 3.69 | 0.00 |
September | 1541.40 | 04-SEP-20:00 | 190.94 | 608.16 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.65 |
October | 926.26 | 18-OCT-20:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.80 |
November | 825.09 | 08-NOV-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.36 |
December | 753.14 | 06-DEC-21:00 | 222.77 | 684.18 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 723.98 | 190.94 | 570.15 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1777.87 | 1145.66 | 3192.82 | 4241.42 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 58.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 370.56 | 15-JAN-11:35 | 146.88 | 101.74 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.60 |
February | 423.67 | 27-FEB-11:33 | 146.88 | 127.18 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 |
March | 411.82 | 23-MAR-10:33 | 146.88 | 127.18 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.54 |
April | 490.11 | 08-APR-10:33 | 220.32 | 127.18 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.52 |
May | 535.75 | 20-MAY-18:00 | 146.88 | 101.74 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 1.57 | 0.00 |
June | 627.74 | 23-JUN-19:40 | 171.36 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 | 0.00 |
July | 816.71 | 17-JUL-18:50 | 171.36 | 135.66 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 14.01 | 0.00 |
August | 730.21 | 09-AUG-19:10 | 171.36 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 7.47 | 0.00 |
September | 635.34 | 04-SEP-19:40 | 146.88 | 135.66 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 | 0.00 |
October | 492.59 | 18-OCT-10:33 | 146.88 | 127.18 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 |
November | 425.76 | 04-NOV-18:10 | 1028.16 | 830.90 | 1427.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.42 |
December | 377.35 | 06-DEC-21:00 | 171.36 | 152.61 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 370.56 | 146.88 | 101.74 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 816.71 | 1028.16 | 830.90 | 1427.45 | 0.00 | 0.00 | 0.00 | 0.00 | 14.01 | 33.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36928.01 | 02-JAN-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 68.75 |
February | 37659.10 | 27-FEB-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 71.93 |
March | 37569.25 | 28-MAR-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 67.22 |
April | 38118.44 | 25-APR-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 39.42 |
May | 38594.42 | 19-MAY-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 |
June | 38970.86 | 23-JUN-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
July | 39208.71 | 17-JUL-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 15.48 | 0.00 |
August | 39063.72 | 07-AUG-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 6.71 | 0.00 |
September | 38684.40 | 01-SEP-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 14.93 |
October | 38156.58 | 18-OCT-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 25.90 |
November | 37602.65 | 03-NOV-20:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 47.46 |
December | 37178.99 | 06-DEC-21:00 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 87.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36928.01 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39208.71 | 705.60 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 15.48 | 87.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12537.31 | 15-JAN-13:00 | 5122.80 | 115.39 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.11 |
February | 15562.85 | 26-FEB-13:00 | 5122.80 | 115.39 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.94 |
March | 14217.56 | 01-MAR-13:30 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.11 |
April | 13649.89 | 06-APR-15:03 | 59766.00 | 673.09 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.71 |
May | 11951.15 | 13-MAY-13:10 | 10245.60 | 192.31 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 | 0.00 |
June | 11320.97 | 30-JUN-15:03 | 51228.00 | 576.93 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 31.56 | 0.00 |
July | 13551.33 | 17-JUL-15:03 | 51228.00 | 576.93 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 67.46 | 0.00 |
August | 14354.03 | 25-AUG-15:03 | 59766.00 | 673.09 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 38.80 | 0.00 |
September | 15648.95 | 02-SEP-13:00 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 48.51 | 0.00 |
October | 16271.74 | 18-OCT-14:10 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 | 0.00 |
November | 14074.61 | 03-NOV-13:10 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.03 |
December | 10425.77 | 02-DEC-13:30 | 5122.80 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10425.77 | 3415.20 | 96.16 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16271.74 | 59766.00 | 673.09 | 2489.39 | 0.00 | 0.00 | 0.00 | 0.00 | 67.46 | 115.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 38528.71 | 05-JAN-22:53 | 182491.92 | 28387.68 | 29559.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 899.26 |
February | 37965.79 | 01-FEB-03:55 | 91245.96 | 2365.64 | 4222.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 902.67 |
March | 31968.03 | 01-MAR-22:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 361.78 |
April | 35456.21 | 06-APR-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.62 |
May | 38091.45 | 19-MAY-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.30 |
June | 40331.12 | 23-JUN-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.22 |
July | 43364.40 | 17-JUL-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 40.59 | 0.00 |
August | 42939.50 | 07-AUG-21:04 | 228114.90 | 35484.60 | 36949.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 |
September | 40647.17 | 01-SEP-20:10 | 40553.76 | 9462.56 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.15 |
October | 38658.85 | 18-OCT-21:03 | 273737.88 | 42581.52 | 44339.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.04 |
November | 33801.88 | 03-NOV-21:10 | 45622.98 | 7096.92 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.79 |
December | 36479.36 | 28-DEC-22:33 | 136868.94 | 21290.76 | 22169.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 881.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 31968.03 | 40553.76 | 2365.64 | 4222.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43364.40 | 273737.88 | 42581.52 | 44339.66 | 0.00 | 0.00 | 0.00 | 0.00 | 40.59 | 902.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3379.91 | 21-JAN-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.99 |
February | 3603.21 | 27-FEB-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.01 |
March | 3533.72 | 01-MAR-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.03 |
April | 3793.06 | 06-APR-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.92 |
May | 3915.27 | 31-MAY-18:01 | 970.20 | 739.76 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 1.38 | 0.00 |
June | 3735.70 | 10-JUN-18:02 | 702.00 | 712.44 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 |
July | 3757.61 | 07-JUL-18:01 | 970.20 | 739.76 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.39 |
August | 4023.54 | 11-AUG-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 11.55 | 0.00 |
September | 3630.51 | 08-SEP-18:01 | 970.20 | 739.76 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 |
October | 3949.30 | 18-OCT-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 | 0.00 |
November | 3472.65 | 06-NOV-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.42 |
December | 3411.62 | 07-DEC-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3379.91 | 378.00 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4023.54 | 970.20 | 739.76 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 11.55 | 32.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1048.04 | 13-JAN-19:03 | 831.60 | 634.00 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 |
February | 3557.36 | 26-FEB-17:41 | 858.60 | 352.62 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 |
March | 3309.15 | 02-MAR-16:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.76 |
April | 3917.21 | 22-APR-19:01 | 1170.00 | 1187.26 | 1738.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.25 |
May | 4430.07 | 31-MAY-16:11 | 972.00 | 332.43 | 1343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
June | 3921.38 | 07-JUN-19:41 | 1386.00 | 1187.26 | 1738.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.38 |
July | 3884.81 | 08-JUL-20:41 | 1386.00 | 1187.26 | 1843.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 |
August | 3940.58 | 11-AUG-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 4.30 | 0.00 |
September | 3721.17 | 15-SEP-18:21 | 1386.00 | 1056.67 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.81 |
October | 3829.42 | 02-OCT-16:41 | 972.00 | 332.43 | 1343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.18 |
November | 3216.33 | 06-NOV-16:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.84 |
December | 2099.94 | 06-DEC-16:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1048.04 | 360.00 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4430.07 | 1386.00 | 1187.26 | 1843.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.30 | 23.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 557.93 | 01-JAN-13:30 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 |
February | 699.49 | 27-FEB-13:30 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 |
March | 676.53 | 01-MAR-13:30 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.12 |
April | 602.02 | 06-APR-13:40 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 |
May | 504.36 | 19-MAY-13:30 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.03 |
June | 485.47 | 24-JUN-13:30 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 | 0.00 |
July | 602.13 | 17-JUL-13:30 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 3.90 | 0.00 |
August | 689.27 | 30-AUG-13:30 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
September | 754.83 | 03-SEP-13:00 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 2.65 | 0.00 |
October | 812.36 | 18-OCT-13:00 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 |
November | 673.26 | 03-NOV-13:30 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.38 |
December | 302.70 | 12-DEC-14:30 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 302.70 | 0.00 | 20.89 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 812.36 | 0.00 | 24.63 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 3.90 | 13.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 841.83 | 15-JAN-09:01 | 378.00 | 292.60 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.44 |
February | 902.53 | 27-FEB-16:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.58 |
March | 897.82 | 29-MAR-18:01 | 970.20 | 465.04 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 |
April | 1043.13 | 07-APR-15:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
May | 1082.30 | 31-MAY-16:11 | 972.00 | 209.00 | 1316.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 | 0.00 |
June | 1079.53 | 28-JUN-21:51 | 1800.00 | 500.12 | 903.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 |
July | 1165.56 | 26-JUL-08:61 | 360.00 | 328.43 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 | 0.00 |
August | 1118.58 | 07-AUG-08:21 | 324.00 | 295.59 | 998.70 | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 0.00 |
September | 1078.54 | 03-SEP-08:51 | 540.00 | 418.01 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 | 0.00 |
October | 1039.28 | 18-OCT-15:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 | 0.00 |
November | 881.30 | 04-NOV-15:01 | 378.00 | 172.43 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.11 |
December | 850.48 | 10-DEC-09:02 | 270.00 | 209.00 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 841.83 | 270.00 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1165.56 | 1800.00 | 500.12 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 9.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2002.73 | 15-JAN-16:02 | 324.00 | 235.11 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 |
February | 3219.74 | 27-FEB-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 |
March | 3126.85 | 22-MAR-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.55 |
April | 3379.64 | 06-APR-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.82 |
May | 3427.20 | 31-MAY-18:01 | 970.20 | 739.76 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 1.75 | 0.00 |
June | 3316.69 | 10-JUN-18:02 | 702.00 | 712.44 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 |
July | 3271.81 | 07-JUL-18:01 | 970.20 | 739.76 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.95 |
August | 3599.50 | 11-AUG-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 11.58 | 0.00 |
September | 3218.65 | 30-SEP-18:01 | 819.00 | 831.18 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 |
October | 3506.85 | 18-OCT-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 3.59 | 0.00 |
November | 3085.96 | 02-NOV-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.73 |
December | 2236.44 | 10-DEC-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2002.73 | 324.00 | 232.73 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3599.50 | 970.20 | 831.18 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 11.58 | 28.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1202.49 | 17-JAN-09:03 | 252.00 | 365.68 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.75 |
February | 2968.41 | 26-FEB-09:01 | 378.00 | 465.41 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 |
March | 2822.83 | 27-MAR-15:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 |
April | 3185.28 | 07-APR-15:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 |
May | 3527.83 | 31-MAY-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 |
June | 3761.14 | 21-JUN-08:32 | 216.00 | 313.44 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 |
July | 3955.21 | 17-JUL-08:61 | 252.00 | 365.68 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.85 |
August | 4026.76 | 11-AUG-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 1.22 | 0.00 |
September | 3344.25 | 04-SEP-08:31 | 540.00 | 664.87 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | 0.00 |
October | 3276.05 | 18-OCT-15:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 3.89 | 0.00 |
November | 1953.57 | 06-NOV-09:01 | 252.00 | 365.68 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.91 |
December | 1172.55 | 20-DEC-09:03 | 252.00 | 365.68 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1172.55 | 216.00 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4026.76 | 680.40 | 664.87 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 3.89 | 35.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1282.82 | 15-JAN-11:35 | 1508.90 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.14 |
February | 1446.45 | 26-FEB-11:33 | 2263.36 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 |
March | 1426.73 | 23-MAR-10:33 | 1508.90 | 966.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.76 |
April | 1657.46 | 08-APR-10:33 | 2263.36 | 966.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.05 |
May | 1795.92 | 20-MAY-18:00 | 1508.90 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.23 | 0.00 |
June | 2140.06 | 30-JUN-19:30 | 1760.39 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.13 | 0.00 |
July | 2867.83 | 17-JUL-18:40 | 1760.39 | 1031.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.09 | 0.00 |
August | 2647.33 | 10-AUG-18:15 | 3520.78 | 2062.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.71 | 0.00 |
September | 2270.86 | 04-SEP-18:15 | 3017.81 | 1804.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.09 | 0.00 |
October | 1665.33 | 18-OCT-10:33 | 1508.90 | 966.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.40 |
November | 1383.48 | 04-NOV-18:00 | 1508.90 | 773.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.11 |
December | 1203.49 | 07-DEC-11:35 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1203.49 | 1005.94 | 644.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2867.83 | 3520.78 | 2062.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.09 | 33.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3437.57 | 21-JAN-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.41 |
February | 3780.73 | 27-FEB-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.05 |
March | 3704.69 | 01-MAR-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.06 |
April | 3983.90 | 06-APR-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.98 |
May | 4118.15 | 31-MAY-18:01 | 970.20 | 739.76 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 1.29 | 0.00 |
June | 3921.88 | 10-JUN-18:02 | 702.00 | 712.44 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 |
July | 3936.72 | 07-JUL-18:01 | 970.20 | 739.76 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 |
August | 4228.82 | 11-AUG-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 11.49 | 0.00 |
September | 3808.38 | 08-SEP-18:01 | 970.20 | 739.76 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.95 |
October | 4146.52 | 18-OCT-15:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 3.38 | 0.00 |
November | 3640.58 | 06-NOV-16:01 | 680.40 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.46 |
December | 3571.11 | 10-DEC-16:01 | 378.00 | 274.30 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3437.57 | 378.00 | 232.73 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4228.82 | 970.20 | 739.76 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 11.49 | 32.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1089.14 | 01-JAN-16:03 | 324.00 | 235.08 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.13 |
February | 3781.52 | 26-FEB-17:41 | 858.60 | 352.62 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.24 |
March | 3447.76 | 22-MAR-18:01 | 970.20 | 739.67 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.09 |
April | 4313.26 | 25-APR-19:02 | 831.60 | 712.36 | 1042.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.04 |
May | 4648.76 | 31-MAY-16:11 | 972.00 | 332.43 | 1343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
June | 4128.34 | 07-JUN-19:41 | 1386.00 | 1187.26 | 1738.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.57 |
July | 4154.16 | 08-JUL-20:41 | 1386.00 | 1187.26 | 1843.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.23 |
August | 4073.32 | 11-AUG-08:51 | 360.00 | 522.40 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 4.51 | 0.00 |
September | 3956.25 | 15-SEP-18:21 | 1386.00 | 1056.67 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 |
October | 3989.55 | 02-OCT-16:41 | 972.00 | 332.43 | 1343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.14 |
November | 2428.19 | 04-NOV-18:01 | 819.00 | 831.08 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.19 |
December | 2143.05 | 06-DEC-16:01 | 680.40 | 232.70 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1089.14 | 324.00 | 232.70 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4648.76 | 1386.00 | 1187.26 | 1843.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.51 | 26.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2018.67 | 19-JAN-16:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.89 |
February | 2106.94 | 27-FEB-16:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.79 |
March | 2065.39 | 01-MAR-16:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.97 |
April | 2211.89 | 06-APR-15:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 |
May | 2170.29 | 29-MAY-18:01 | 819.00 | 522.51 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 | 0.00 |
June | 2115.84 | 10-JUN-18:02 | 702.00 | 447.86 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
July | 2155.55 | 30-JUL-08:61 | 378.00 | 292.60 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 | 0.00 |
August | 2158.06 | 11-AUG-08:61 | 252.00 | 229.90 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 | 0.00 |
September | 2065.15 | 06-SEP-15:02 | 583.20 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 0.00 |
October | 2316.45 | 18-OCT-15:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 | 0.00 |
November | 2043.76 | 13-NOV-16:01 | 680.40 | 146.30 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.74 |
December | 2007.88 | 10-DEC-16:01 | 378.00 | 172.43 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2007.88 | 252.00 | 125.40 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2316.45 | 819.00 | 522.51 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 23.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18370.18 | 05-JAN-22:53 | 107955.07 | 7368.33 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.27 |
February | 17678.84 | 27-FEB-22:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.03 |
March | 17865.31 | 29-MAR-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.49 |
April | 19871.06 | 07-APR-21:53 | 161932.61 | 11052.49 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.57 |
May | 21430.50 | 19-MAY-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 |
June | 22477.46 | 23-JUN-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.56 |
July | 23166.16 | 17-JUL-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 0.00 |
August | 22566.60 | 09-AUG-21:04 | 134943.84 | 9210.41 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 |
September | 21509.34 | 06-SEP-21:52 | 215910.14 | 14736.65 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.31 |
October | 19743.62 | 18-OCT-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.75 |
November | 18571.28 | 17-NOV-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.89 |
December | 17657.98 | 28-DEC-22:33 | 80966.30 | 5526.25 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17657.98 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23166.16 | 215910.14 | 14736.65 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 207.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19480.04 | 05-JAN-22:53 | 107955.07 | 7368.33 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.98 |
February | 19472.03 | 27-FEB-22:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.03 |
March | 19777.70 | 29-MAR-21:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.49 |
April | 21538.15 | 07-APR-21:10 | 53977.54 | 3684.16 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.11 |
May | 22954.77 | 19-MAY-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 |
June | 23703.32 | 23-JUN-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 |
July | 24358.90 | 17-JUL-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 0.00 |
August | 23747.16 | 09-AUG-21:04 | 134943.84 | 9210.41 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 |
September | 22705.35 | 06-SEP-21:20 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.81 |
October | 21263.69 | 18-OCT-22:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.75 |
November | 20548.39 | 17-NOV-22:10 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.30 |
December | 19519.57 | 05-DEC-23:00 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19472.03 | 26988.77 | 1842.08 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24358.90 | 134943.84 | 9210.41 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 207.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25851.93 | 15-JAN-11:40 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 70.09 |
February | 27067.41 | 26-FEB-11:33 | 2401.70 | 1090.83 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 38.56 |
March | 27562.70 | 23-MAR-10:33 | 1601.14 | 909.03 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 52.42 |
April | 28513.67 | 24-APR-10:33 | 1601.14 | 909.03 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 29.99 |
May | 29400.95 | 13-MAY-10:33 | 2401.70 | 909.03 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 9.82 |
June | 30262.07 | 24-JUN-10:33 | 2401.70 | 909.03 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 |
July | 30549.05 | 15-JUL-10:40 | 2401.70 | 909.03 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 3.88 | 0.00 |
August | 30609.51 | 06-AUG-10:40 | 1601.14 | 727.22 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 19.70 | 0.00 |
September | 30217.93 | 02-SEP-10:33 | 2401.70 | 909.03 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 16.59 | 0.00 |
October | 28016.72 | 15-OCT-10:33 | 2401.70 | 1090.83 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 21.23 |
November | 26616.58 | 03-NOV-10:33 | 1601.14 | 909.03 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 47.86 |
December | 25224.41 | 06-DEC-11:50 | 533.71 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 39.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 25224.41 | 533.71 | 303.01 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30609.51 | 2401.70 | 1090.83 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 19.70 | 70.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2983.27 | 15-JAN-11:35 | 1596.96 | 818.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.50 |
February | 3360.67 | 26-FEB-11:33 | 2395.44 | 1227.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.37 |
March | 3250.41 | 23-MAR-10:33 | 1596.96 | 1023.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.43 |
April | 3795.96 | 25-APR-17:12 | 5323.20 | 3273.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.63 |
May | 4297.65 | 20-MAY-17:40 | 1596.96 | 818.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.82 | 0.00 |
June | 6081.56 | 23-JUN-13:30 | 532.32 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.66 | 0.00 |
July | 7641.29 | 17-JUL-15:03 | 7984.80 | 2046.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.59 | 0.00 |
August | 7076.13 | 07-AUG-14:10 | 798.48 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.11 | 0.00 |
September | 6079.71 | 03-SEP-12:50 | 532.32 | 272.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.15 | 0.00 |
October | 3786.80 | 18-OCT-16:20 | 1330.80 | 341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 | 0.00 |
November | 3125.71 | 04-NOV-17:13 | 4790.88 | 2455.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.68 |
December | 2787.26 | 07-DEC-11:35 | 1064.64 | 682.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2787.26 | 532.32 | 272.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7641.29 | 7984.80 | 3273.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.59 | 59.50 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.351523E+12 | 223237.98 | 02-JAN-20:49 | 0.102995E+13 | 1140978.70 | 10-JAN-22:49 |
February | 0.356258E+12 | 265770.08 | 27-FEB-20:10 | 0.478900E+12 | 781958.44 | 01-FEB-07:10 |
March | 0.392254E+12 | 264944.84 | 28-MAR-19:10 | 0.449670E+12 | 522047.74 | 04-MAR-23:00 |
April | 0.384774E+12 | 293247.11 | 07-APR-19:10 | 0.360394E+12 | 415515.06 | 29-APR-17:00 |
May | 0.414849E+12 | 326958.08 | 19-MAY-18:19 | 0.350493E+12 | 374715.65 | 03-MAY-17:49 |
June | 0.450872E+12 | 362321.22 | 20-JUN-19:19 | 0.295128E+12 | 342747.58 | 16-JUN-18:10 |
July | 0.518958E+12 | 398764.63 | 17-JUL-18:19 | 0.266636E+12 | 264507.74 | 07-JUL-21:10 |
August | 0.499523E+12 | 377010.14 | 09-AUG-19:49 | 0.279376E+12 | 288462.58 | 17-AUG-20:00 |
September | 0.442254E+12 | 360280.92 | 04-SEP-19:19 | 0.296975E+12 | 305008.73 | 19-SEP-17:00 |
October | 0.408995E+12 | 291406.23 | 18-OCT-19:19 | 0.364858E+12 | 363712.88 | 26-OCT-17:40 |
November | 0.383425E+12 | 266531.83 | 01-NOV-19:10 | 0.429249E+12 | 453982.35 | 26-NOV-19:10 |
December | 0.392316E+12 | 257084.91 | 06-DEC-20:30 | 0.612187E+12 | 947269.90 | 31-DEC-20:00 |
Annual Sum or Average | 0.499600E+13 | 0.521382E+13 | ||||
Minimum of Months | 0.351523E+12 | 223237.98 | 0.266636E+12 | 264507.74 | ||
Maximum of Months | 0.518958E+12 | 398764.63 | 0.102995E+13 | 1140978.70 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.521115E+11 | 0.188817E+11 | 0.146779E+12 | 0.544824E+11 | 0.418808E+11 | 0.353282E+10 | 0.00 | 0.151843E+10 | 0.00 | 0.00 | 0.243457E+11 | 0.434946E+10 | 0.00 |
February | 0.467404E+11 | 0.155994E+11 | 0.132565E+12 | 0.492098E+11 | 0.368209E+11 | 0.405596E+10 | 0.00 | 0.567171E+10 | 0.00 | 0.00 | 0.204093E+11 | 0.418626E+11 | 0.00 |
March | 0.513788E+11 | 0.152332E+11 | 0.146789E+12 | 0.544840E+11 | 0.409864E+11 | 0.505039E+10 | 0.00 | 0.729396E+10 | 0.00 | 0.00 | 0.218944E+11 | 0.454574E+11 | 0.00 |
April | 0.492294E+11 | 0.126832E+11 | 0.142011E+12 | 0.527240E+11 | 0.409875E+11 | 0.722792E+10 | 0.00 | 0.193323E+11 | 0.00 | 0.00 | 0.152319E+11 | 0.417742E+11 | 0.00 |
May | 0.504291E+11 | 0.112784E+11 | 0.146789E+12 | 0.544823E+11 | 0.444677E+11 | 0.880824E+10 | 0.00 | 0.411658E+11 | 0.00 | 0.00 | 0.115032E+11 | 0.422155E+11 | 0.00 |
June | 0.483762E+11 | 0.996017E+10 | 0.142058E+12 | 0.527253E+11 | 0.481811E+11 | 0.993515E+10 | 0.00 | 0.892633E+11 | 0.00 | 0.00 | 0.751988E+10 | 0.392407E+11 | 0.00 |
July | 0.503297E+11 | 0.107325E+11 | 0.146742E+12 | 0.544804E+11 | 0.534764E+11 | 0.106568E+11 | 0.00 | 0.139575E+12 | 0.00 | 0.00 | 0.956806E+10 | 0.396728E+11 | 0.00 |
August | 0.505362E+11 | 0.122838E+11 | 0.146800E+12 | 0.544834E+11 | 0.528903E+11 | 0.105505E+11 | 0.00 | 0.120773E+12 | 0.00 | 0.00 | 0.723358E+10 | 0.402427E+11 | 0.00 |
September | 0.494971E+11 | 0.138417E+11 | 0.142022E+12 | 0.527243E+11 | 0.473907E+11 | 0.958461E+10 | 0.00 | 0.750072E+11 | 0.00 | 0.00 | 0.873339E+10 | 0.398453E+11 | 0.00 |
October | 0.516565E+11 | 0.164183E+11 | 0.146768E+12 | 0.544821E+11 | 0.446473E+11 | 0.865199E+10 | 0.00 | 0.273999E+11 | 0.00 | 0.00 | 0.122405E+11 | 0.430268E+11 | 0.00 |
November | 0.502876E+11 | 0.177499E+11 | 0.142074E+12 | 0.527253E+11 | 0.406784E+11 | 0.589060E+10 | 0.00 | 0.928117E+10 | 0.00 | 0.00 | 0.175195E+11 | 0.436546E+11 | 0.00 |
December | 0.520859E+11 | 0.194077E+11 | 0.146742E+12 | 0.544816E+11 | 0.403715E+11 | 0.322026E+10 | 0.00 | 0.138917E+10 | 0.00 | 0.00 | 0.232546E+11 | 0.476896E+11 | 0.00 |
Annual Sum or Average | 0.602658E+12 | 0.174070E+12 | 0.172814E+13 | 0.641485E+12 | 0.532779E+12 | 0.871653E+11 | 0.00 | 0.537671E+12 | 0.00 | 0.00 | 0.179454E+12 | 0.469032E+12 | 0.00 |
Minimum of Months | 0.467404E+11 | 0.996017E+10 | 0.132565E+12 | 0.492098E+11 | 0.368209E+11 | 0.322026E+10 | 0.00 | 0.138917E+10 | 0.00 | 0.00 | 0.723358E+10 | 0.434946E+10 | 0.00 |
Maximum of Months | 0.521115E+11 | 0.194077E+11 | 0.146800E+12 | 0.544840E+11 | 0.534764E+11 | 0.106568E+11 | 0.00 | 0.139575E+12 | 0.00 | 0.00 | 0.243457E+11 | 0.476896E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.632822E+12 | 0.00 | 0.245214E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.213671E+12 | 0.00 | 0.128026E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.158100E+12 | 0.00 | 0.139546E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.915450E+11 | 0.00 | 0.121893E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.849203E+11 | 0.00 | 0.113594E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.534081E+11 | 0.00 | 0.946058E+11 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.270877E+11 | 0.00 | 0.877275E+11 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.390107E+11 | 0.00 | 0.883270E+11 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.585656E+11 | 0.00 | 0.914381E+11 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.104644E+12 | 0.00 | 0.108310E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.161303E+12 | 0.00 | 0.120854E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.319595E+12 | 0.00 | 0.140772E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.194467E+13 | 0.00 | 0.148031E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.270877E+11 | 0.00 | 0.877275E+11 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.632822E+12 | 0.00 | 0.245214E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 50471.22 | 02-JAN-20:10 | 11096.45 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 39155.93 | 02-JAN-07:19 | 22817.44 | 02-JAN-22:10 | 5080.60 | 29-JAN-10:00 | 0.00 | 01-JAN-00:10 |
February | 50471.22 | 01-FEB-20:10 | 11096.45 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 39155.93 | 01-FEB-07:19 | 26534.44 | 27-FEB-22:10 | 4543.31 | 05-FEB-16:30 | 0.00 | 01-FEB-00:10 |
March | 50471.22 | 01-MAR-20:10 | 11096.45 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 39155.93 | 01-MAR-07:19 | 25422.76 | 29-MAR-21:10 | 4314.02 | 06-MAR-09:09 | 0.00 | 01-MAR-00:10 |
April | 50471.22 | 03-APR-19:10 | 11096.45 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 39155.81 | 05-APR-06:19 | 32019.74 | 06-APR-21:10 | 4238.28 | 02-APR-08:20 | 0.00 | 01-APR-00:10 |
May | 50471.22 | 01-MAY-19:30 | 11096.45 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 39155.27 | 03-MAY-06:19 | 35551.88 | 19-MAY-21:00 | 4675.12 | 19-MAY-15:20 | 0.00 | 01-MAY-00:10 |
June | 49463.84 | 01-JUN-19:00 | 11096.45 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 39154.23 | 01-JUN-06:19 | 36721.03 | 29-JUN-21:00 | 4967.41 | 23-JUN-18:19 | 0.00 | 01-JUN-00:10 |
July | 50471.22 | 03-JUL-19:30 | 11096.45 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 39154.78 | 19-JUL-06:19 | 40380.37 | 17-JUL-21:10 | 6114.54 | 17-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 50471.22 | 01-AUG-19:00 | 11096.45 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 39155.07 | 17-AUG-06:19 | 41399.61 | 08-AUG-21:10 | 5690.24 | 07-AUG-18:10 | 0.00 | 01-AUG-00:10 |
September | 50471.22 | 01-SEP-19:10 | 11096.45 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 39155.93 | 18-SEP-06:19 | 39904.85 | 05-SEP-21:10 | 5242.25 | 02-SEP-18:10 | 0.00 | 01-SEP-00:10 |
October | 50471.22 | 02-OCT-19:10 | 11096.45 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 39155.93 | 02-OCT-06:19 | 37167.70 | 18-OCT-21:10 | 4305.52 | 11-OCT-09:39 | 0.00 | 01-OCT-00:10 |
November | 50471.22 | 01-NOV-19:10 | 11096.45 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 39155.93 | 01-NOV-06:19 | 30390.10 | 03-NOV-21:10 | 4309.72 | 14-NOV-17:00 | 0.00 | 01-NOV-00:10 |
December | 50471.22 | 01-DEC-20:10 | 11096.45 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 39155.93 | 01-DEC-07:19 | 24060.94 | 06-DEC-22:10 | 4369.23 | 16-DEC-16:49 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 49463.84 | 11096.45 | 88863.15 | 39154.23 | 22817.44 | 4238.28 | 0.00 | |||||||
Maximum of Months | 50471.22 | 11096.45 | 88863.15 | 39155.93 | 41399.61 | 6114.54 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 17676.65 | 01-JAN-13:30 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 3486.17 | 09-JAN-07:30 | 0.00 |
February | 44994.84 | 27-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:10 | 36024.62 | 01-FEB-19:00 | 0.00 |
March | 29525.17 | 28-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:10 | 36771.69 | 31-MAR-18:10 | 0.00 |
April | 68567.24 | 06-APR-15:09 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 38129.03 | 28-APR-18:19 | 0.00 |
May | 99067.41 | 19-MAY-15:20 | 0.00 | 0.00 | 9938.94 | 01-MAY-00:10 | 39564.93 | 31-MAY-18:40 | 0.00 |
June | 119309.50 | 29-JUN-15:09 | 0.00 | 0.00 | 9938.94 | 01-JUN-21:19 | 40547.29 | 28-JUN-18:49 | 0.00 |
July | 163968.97 | 17-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUL-12:09 | 40848.16 | 28-JUL-17:00 | 0.00 |
August | 140554.30 | 10-AUG-15:09 | 0.00 | 0.00 | 9938.94 | 03-AUG-05:30 | 41447.01 | 15-AUG-18:30 | 0.00 |
September | 138901.06 | 02-SEP-15:20 | 0.00 | 0.00 | 9938.94 | 01-SEP-12:09 | 41476.33 | 06-SEP-18:19 | 0.00 |
October | 90075.07 | 18-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 01-OCT-05:10 | 40951.92 | 03-OCT-18:00 | 0.00 |
November | 36270.05 | 04-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 01-NOV-00:10 | 39630.17 | 02-NOV-18:00 | 0.00 |
December | 10702.40 | 12-DEC-14:30 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:10 | 37665.70 | 01-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 10702.40 | 0.00 | 0.00 | 9938.94 | 3486.17 | 0.00 | |||
Maximum of Months | 163968.97 | 0.00 | 0.00 | 9938.94 | 41476.33 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 223237.98 | 02-JAN-20:49 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 20739.77 | 3779.52 | 0.00 | 3227.58 | 0.00 |
February | 265770.08 | 27-FEB-20:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 23867.95 | 3704.24 | 0.00 | 10466.49 | 0.00 |
March | 264944.84 | 28-MAR-19:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 22668.44 | 3705.25 | 0.00 | 10695.95 | 0.00 |
April | 293247.11 | 07-APR-19:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 24123.64 | 3766.06 | 0.00 | 46187.62 | 0.00 |
May | 326958.08 | 19-MAY-18:19 | 40498.58 | 78653.57 | 0.00 | 31364.28 | 29865.12 | 4658.51 | 0.00 | 91609.50 | 0.00 |
June | 362321.22 | 20-JUN-19:19 | 46717.29 | 87982.85 | 0.00 | 31574.40 | 31115.54 | 4594.81 | 0.00 | 109814.31 | 0.00 |
July | 398764.63 | 17-JUL-18:19 | 40498.58 | 78653.57 | 0.00 | 31364.28 | 34999.34 | 6015.66 | 0.00 | 160159.11 | 0.00 |
August | 377010.14 | 09-AUG-19:49 | 50471.22 | 87982.85 | 11096.45 | 31577.52 | 33299.94 | 5115.62 | 0.00 | 106957.90 | 0.00 |
September | 360280.92 | 04-SEP-19:19 | 46435.92 | 86521.75 | 11096.45 | 31540.10 | 30801.74 | 4725.02 | 0.00 | 99455.78 | 0.00 |
October | 291406.23 | 18-OCT-19:19 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 28374.66 | 3774.61 | 0.00 | 37118.23 | 0.00 |
November | 266531.83 | 01-NOV-19:10 | 50471.22 | 87982.85 | 11096.45 | 31573.10 | 23990.82 | 3717.54 | 0.00 | 7208.33 | 0.00 |
December | 257084.91 | 06-DEC-20:30 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 21683.75 | 3788.97 | 0.00 | 2352.68 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 223237.98 | 40498.58 | 78653.57 | 0.00 | 31364.28 | 20739.77 | 3704.24 | 0.00 | 2352.68 | 0.00 | |
Maximum of Months | 398764.63 | 50471.22 | 87982.85 | 11096.45 | 31577.78 | 34999.34 | 6015.66 | 0.00 | 160159.11 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 924327.37 | 11-JAN-05:00 | 0.00 | 195185.26 | 17-JAN-22:19 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 696262.58 | 01-FEB-07:10 | 0.00 | 173147.36 | 01-FEB-00:10 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 355782.30 | 04-MAR-23:00 | 0.00 | 143977.96 | 03-MAR-18:49 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 192350.16 | 29-APR-17:00 | 0.00 | 128564.77 | 05-APR-17:40 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 174214.08 | 15-MAY-18:00 | 0.00 | 111225.23 | 01-MAY-19:49 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 167780.29 | 16-JUN-18:10 | 0.00 | 90935.03 | 01-JUN-19:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 142254.18 | 09-JUL-02:49 | 0.00 | 77193.30 | 01-JUL-22:10 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 173395.96 | 18-AUG-04:00 | 0.00 | 76141.01 | 01-AUG-19:49 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 179061.12 | 16-SEP-06:00 | 0.00 | 84973.96 | 30-SEP-17:00 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 185454.85 | 07-OCT-07:00 | 0.00 | 103813.27 | 31-OCT-21:00 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 253711.85 | 26-NOV-16:10 | 0.00 | 128586.45 | 30-NOV-18:49 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 859373.66 | 29-DEC-09:09 | 0.00 | 147765.60 | 07-DEC-21:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 142254.18 | 0.00 | 76141.01 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 924327.37 | 0.00 | 195185.26 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.67 | 19.77 | 14.67 | 19.77 | 0.00 | 19.77 | 0.00 | 19.77 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.43 | 0.33 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
Annual Sum or Average | 15.00 | 19.78 | 15.00 | 19.78 | 0.00 | 19.78 | 0.00 | 19.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.67 | 20.43 | 14.67 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 17.03 | 2.50 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.50 | 17.03 | 2.50 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 17.03 | 2.50 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.00 | 20.21 | 3.00 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.32 | 0.33 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Annual Sum or Average | 3.33 | 20.22 | 3.33 | 20.22 | 0.00 | 20.22 | 0.00 | 20.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.00 | 20.32 | 3.00 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.74 | 1.83 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.77 | 1.33 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.75 | 0.67 | 21.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.83 | 21.75 | 3.83 | 21.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.77 | 1.83 | 21.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.74 | 0.50 | 21.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.86 | 0.67 | 21.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.75 | 2.00 | 21.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.78 | 3.17 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.78 | 1.00 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.88 | 0.17 | 21.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.67 | 21.78 | 7.67 | 21.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.88 | 3.17 | 21.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 20.48 | 1.33 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.77 | 1.83 | 21.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 21.80 | 5.33 | 21.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 21.78 | 5.83 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.80 | 4.17 | 21.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.82 | 0.67 | 21.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.33 | 20.48 | 1.33 | 20.48 | 17.83 | 21.62 | 17.83 | 21.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.48 | 1.33 | 20.48 | 5.83 | 21.82 | 5.83 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.90 | 0.17 | 21.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.82 | 1.00 | 21.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.74 | 1.67 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.81 | 1.33 | 21.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.72 | 0.33 | 21.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.67 | 21.78 | 4.67 | 21.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.90 | 1.67 | 21.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.98 | 1.00 | 21.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 22.23 | 6.00 | 22.23 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 22.31 | 9.17 | 22.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 22.28 | 6.17 | 22.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 22.31 | 1.17 | 22.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 23.67 | 22.26 | 23.67 | 22.26 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 22.31 | 9.17 | 22.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.78 | 2.83 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.78 | 2.17 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.81 | 0.50 | 21.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.83 | 21.78 | 5.83 | 21.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.81 | 2.83 | 21.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.84 | 0.50 | 21.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.88 | 1.17 | 21.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.79 | 3.00 | 21.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.83 | 4.50 | 21.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.76 | 1.83 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.02 | 0.17 | 22.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.17 | 21.82 | 11.17 | 21.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 22.02 | 4.50 | 22.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.95 | 0.33 | 21.95 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.95 | 0.67 | 21.95 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.70 | 0.67 | 21.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.77 | 2.33 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.82 | 2.00 | 21.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.93 | 1.50 | 21.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.95 | 0.67 | 21.95 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.33 | 21.84 | 8.33 | 21.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.95 | 2.33 | 21.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.51 | 0.33 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 18.51 | 0.33 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 18.51 | 0.33 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.38 | 0.83 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 20.38 | 0.83 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 20.38 | 0.83 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.63 | 74.00 | 22.48 | 74.00 | 22.36 |
February | 672.00 | 22.84 | 0.00 | 22.84 | 0.00 | 22.84 |
March | 744.00 | 22.45 | 0.00 | 22.45 | 0.00 | 22.45 |
April | 720.00 | 21.97 | 0.00 | 21.97 | 0.00 | 21.97 |
May | 744.00 | 22.40 | 0.00 | 22.40 | 0.00 | 22.40 |
June | 720.00 | 22.65 | 5.00 | 22.65 | 5.00 | 22.66 |
July | 731.50 | 23.12 | 18.00 | 23.12 | 18.00 | 23.12 |
August | 687.67 | 23.46 | 0.00 | 23.46 | 0.00 | 23.46 |
September | 420.83 | 23.73 | 58.17 | 23.75 | 17.50 | 23.75 |
October | 578.83 | 23.89 | 0.00 | 23.89 | 0.00 | 23.89 |
November | 681.17 | 23.90 | 0.00 | 23.90 | 0.00 | 23.90 |
December | 742.50 | 23.71 | 0.00 | 23.71 | 0.00 | 23.71 |
Annual Sum or Average | 8186.50 | 23.02 | 155.17 | 23.00 | 114.50 | 22.99 |
Minimum of Months | 420.83 | 21.97 | 0.00 | 21.97 | 0.00 | 21.97 |
Maximum of Months | 744.00 | 23.90 | 74.00 | 23.90 | 74.00 | 23.90 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 726.17 | 21.10 | 512.50 | 21.04 | 509.67 | 21.02 |
February | 621.83 | 21.25 | 280.83 | 21.23 | 263.50 | 21.18 |
March | 679.67 | 21.22 | 202.50 | 21.23 | 185.50 | 21.19 |
April | 655.50 | 21.38 | 89.83 | 21.40 | 71.50 | 21.37 |
May | 678.67 | 21.53 | 60.17 | 21.57 | 38.33 | 21.54 |
June | 550.50 | 21.91 | 100.83 | 22.20 | 1.33 | 22.21 |
July | 421.83 | 22.20 | 231.83 | 22.77 | 12.83 | 22.77 |
August | 439.67 | 22.17 | 208.67 | 22.74 | 0.00 | 22.74 |
September | 498.33 | 21.84 | 166.33 | 22.35 | 8.83 | 22.36 |
October | 627.17 | 21.50 | 77.83 | 21.73 | 10.00 | 21.72 |
November | 661.33 | 21.22 | 218.33 | 21.25 | 194.17 | 21.20 |
December | 723.83 | 21.14 | 448.67 | 21.08 | 448.67 | 21.06 |
Annual Sum or Average | 7284.50 | 21.48 | 2598.33 | 21.61 | 1744.33 | 21.52 |
Minimum of Months | 421.83 | 21.10 | 60.17 | 21.04 | 0.00 | 21.02 |
Maximum of Months | 726.17 | 22.20 | 512.50 | 22.77 | 509.67 | 22.77 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.63 | 247.83 | 21.47 | 247.83 | 21.38 |
February | 672.00 | 22.11 | 75.33 | 22.00 | 75.33 | 21.90 |
March | 744.00 | 22.41 | 26.00 | 22.36 | 26.00 | 22.31 |
April | 708.67 | 22.75 | 0.00 | 22.75 | 0.00 | 22.75 |
May | 656.17 | 22.88 | 7.00 | 22.89 | 0.00 | 22.89 |
June | 401.83 | 23.19 | 95.50 | 23.33 | 4.50 | 23.34 |
July | 217.00 | 23.35 | 192.50 | 23.63 | 19.33 | 23.65 |
August | 252.17 | 23.31 | 54.67 | 23.43 | 0.00 | 23.43 |
September | 403.67 | 23.17 | 88.17 | 23.31 | 19.33 | 23.33 |
October | 701.33 | 23.05 | 0.00 | 23.05 | 0.00 | 23.05 |
November | 719.00 | 22.54 | 9.17 | 22.52 | 9.17 | 22.50 |
December | 744.00 | 21.91 | 89.67 | 21.81 | 89.67 | 21.73 |
Annual Sum or Average | 6963.83 | 22.55 | 885.83 | 22.54 | 491.17 | 22.47 |
Minimum of Months | 217.00 | 21.63 | 0.00 | 21.47 | 0.00 | 21.38 |
Maximum of Months | 744.00 | 23.35 | 247.83 | 23.63 | 247.83 | 23.65 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.07 | 415.17 | 21.04 | 415.17 | 21.03 |
February | 672.00 | 21.22 | 217.50 | 21.17 | 217.50 | 21.14 |
March | 744.00 | 21.36 | 100.67 | 21.32 | 100.67 | 21.29 |
April | 720.00 | 21.85 | 12.17 | 21.83 | 12.17 | 21.82 |
May | 742.50 | 22.27 | 3.33 | 22.27 | 3.33 | 22.26 |
June | 632.67 | 23.17 | 12.83 | 23.18 | 0.00 | 23.18 |
July | 442.33 | 23.50 | 60.67 | 23.56 | 6.17 | 23.56 |
August | 591.00 | 23.48 | 0.50 | 23.48 | 0.00 | 23.48 |
September | 594.33 | 22.93 | 24.83 | 22.97 | 0.00 | 22.97 |
October | 744.00 | 22.36 | 0.00 | 22.36 | 0.00 | 22.36 |
November | 720.00 | 21.61 | 90.67 | 21.54 | 90.67 | 21.49 |
December | 744.00 | 21.11 | 320.17 | 21.08 | 320.17 | 21.06 |
Annual Sum or Average | 8090.83 | 22.07 | 1258.50 | 21.96 | 1165.83 | 21.85 |
Minimum of Months | 442.33 | 21.07 | 0.00 | 21.04 | 0.00 | 21.03 |
Maximum of Months | 744.00 | 23.50 | 415.17 | 23.56 | 415.17 | 23.56 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 478.67 | 21.00 | 478.67 | 21.00 |
February | 672.00 | 21.11 | 254.00 | 21.08 | 254.00 | 21.07 |
March | 744.00 | 21.15 | 134.17 | 21.13 | 134.17 | 21.11 |
April | 720.00 | 21.58 | 22.17 | 21.56 | 22.17 | 21.55 |
May | 744.00 | 22.03 | 4.50 | 22.03 | 4.50 | 22.02 |
June | 676.33 | 22.98 | 1.67 | 22.98 | 0.00 | 22.98 |
July | 544.17 | 23.40 | 40.83 | 23.43 | 8.00 | 23.44 |
August | 667.33 | 23.33 | 0.00 | 23.33 | 0.00 | 23.33 |
September | 627.00 | 22.71 | 13.17 | 22.74 | 1.67 | 22.74 |
October | 744.00 | 22.05 | 0.00 | 22.05 | 0.00 | 22.05 |
November | 720.00 | 21.38 | 136.33 | 21.32 | 136.33 | 21.28 |
December | 744.00 | 21.03 | 407.67 | 21.02 | 407.67 | 21.01 |
Annual Sum or Average | 8346.83 | 21.93 | 1493.17 | 21.80 | 1447.17 | 21.70 |
Minimum of Months | 544.17 | 21.01 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 23.40 | 478.67 | 23.43 | 478.67 | 23.44 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 333.00 | 21.82 | 409.67 | 22.66 | 125.67 | 22.69 |
February | 214.00 | 22.86 | 482.83 | 23.39 | 122.00 | 23.48 |
March | 228.50 | 23.02 | 573.50 | 23.43 | 143.17 | 23.52 |
April | 220.17 | 23.37 | 604.33 | 23.50 | 168.17 | 23.59 |
May | 251.00 | 23.57 | 643.50 | 23.55 | 210.67 | 23.63 |
June | 280.33 | 23.89 | 666.33 | 23.58 | 269.50 | 23.67 |
July | 313.83 | 23.97 | 708.50 | 23.59 | 312.50 | 23.68 |
August | 294.67 | 23.96 | 685.33 | 23.62 | 290.00 | 23.70 |
September | 277.00 | 23.80 | 655.00 | 23.59 | 256.67 | 23.67 |
October | 228.83 | 23.45 | 640.17 | 23.54 | 180.17 | 23.62 |
November | 211.50 | 23.10 | 553.67 | 23.49 | 138.83 | 23.57 |
December | 258.83 | 22.69 | 480.67 | 23.33 | 128.00 | 23.43 |
Annual Sum or Average | 3111.67 | 23.29 | 7103.50 | 23.46 | 2345.33 | 23.55 |
Minimum of Months | 211.50 | 21.82 | 409.67 | 22.66 | 122.00 | 22.69 |
Maximum of Months | 333.00 | 23.97 | 708.50 | 23.62 | 312.50 | 23.70 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 706.83 | 21.56 | 284.67 | 21.44 | 269.00 | 21.35 |
February | 580.00 | 21.97 | 139.50 | 21.98 | 93.50 | 21.87 |
March | 645.50 | 22.12 | 110.50 | 22.19 | 51.17 | 22.12 |
April | 566.50 | 22.28 | 63.17 | 22.45 | 0.00 | 22.45 |
May | 525.33 | 22.40 | 92.50 | 22.62 | 0.00 | 22.62 |
June | 295.83 | 22.76 | 286.67 | 23.28 | 22.67 | 23.30 |
July | 140.17 | 22.90 | 523.17 | 23.64 | 32.17 | 23.65 |
August | 131.17 | 22.56 | 443.83 | 23.60 | 0.83 | 23.61 |
September | 284.67 | 22.65 | 349.33 | 23.35 | 38.83 | 23.38 |
October | 464.33 | 22.48 | 124.50 | 22.80 | 0.00 | 22.80 |
November | 624.67 | 22.22 | 94.67 | 22.29 | 38.00 | 22.23 |
December | 699.00 | 21.68 | 155.17 | 21.62 | 138.33 | 21.53 |
Annual Sum or Average | 5664.00 | 22.15 | 2667.67 | 22.50 | 684.50 | 22.42 |
Minimum of Months | 131.17 | 21.56 | 63.17 | 21.44 | 0.00 | 21.35 |
Maximum of Months | 706.83 | 22.90 | 523.17 | 23.64 | 269.00 | 23.65 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.08 | 178.33 | 21.87 | 178.33 | 21.73 |
February | 623.33 | 22.62 | 13.33 | 22.58 | 13.33 | 22.55 |
March | 689.67 | 22.89 | 1.67 | 22.88 | 1.67 | 22.88 |
April | 569.67 | 23.01 | 0.00 | 23.01 | 0.00 | 23.01 |
May | 457.67 | 22.99 | 57.17 | 23.09 | 0.00 | 23.09 |
June | 196.50 | 23.16 | 204.50 | 23.54 | 15.67 | 23.56 |
July | 82.67 | 23.42 | 422.83 | 23.85 | 27.67 | 23.86 |
August | 73.00 | 23.15 | 296.50 | 23.81 | 0.00 | 23.81 |
September | 200.33 | 23.25 | 247.83 | 23.64 | 33.83 | 23.66 |
October | 407.00 | 23.18 | 0.67 | 23.18 | 0.00 | 23.18 |
November | 630.33 | 22.98 | 0.00 | 22.98 | 0.00 | 22.98 |
December | 740.00 | 22.48 | 57.00 | 22.37 | 57.00 | 22.28 |
Annual Sum or Average | 5414.17 | 22.78 | 1479.83 | 22.92 | 327.50 | 22.87 |
Minimum of Months | 73.00 | 22.08 | 0.00 | 21.87 | 0.00 | 21.73 |
Maximum of Months | 744.00 | 23.42 | 422.83 | 23.85 | 178.33 | 23.86 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.76 | 589.83 | 20.69 | 589.83 | 20.66 |
February | 668.00 | 21.04 | 331.50 | 20.93 | 331.50 | 20.87 |
March | 740.83 | 21.16 | 235.17 | 21.05 | 235.17 | 20.97 |
April | 710.17 | 21.36 | 58.00 | 21.30 | 58.00 | 21.24 |
May | 712.00 | 21.43 | 34.33 | 21.40 | 31.33 | 21.36 |
June | 636.00 | 21.47 | 17.50 | 21.52 | 0.00 | 21.52 |
July | 609.33 | 21.38 | 41.83 | 21.51 | 0.33 | 21.51 |
August | 625.17 | 21.41 | 31.83 | 21.50 | 0.00 | 21.50 |
September | 644.00 | 21.42 | 22.83 | 21.48 | 0.00 | 21.48 |
October | 731.50 | 21.43 | 14.33 | 21.42 | 13.67 | 21.40 |
November | 719.00 | 21.18 | 246.17 | 21.06 | 246.17 | 21.00 |
December | 744.00 | 20.84 | 555.33 | 20.77 | 555.33 | 20.75 |
Annual Sum or Average | 8284.00 | 21.23 | 2178.67 | 21.14 | 2061.33 | 21.06 |
Minimum of Months | 609.33 | 20.76 | 14.33 | 20.69 | 0.00 | 20.66 |
Maximum of Months | 744.00 | 21.47 | 589.83 | 21.52 | 589.83 | 21.52 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.56 | 695.50 | 20.54 | 695.50 | 20.54 |
February | 672.00 | 20.78 | 481.33 | 20.71 | 481.33 | 20.68 |
March | 744.00 | 20.91 | 374.50 | 20.81 | 374.50 | 20.76 |
April | 703.33 | 21.30 | 92.50 | 21.33 | 78.50 | 21.28 |
May | 673.00 | 21.53 | 76.17 | 21.72 | 43.17 | 21.71 |
June | 577.83 | 21.72 | 77.17 | 22.15 | 4.67 | 22.19 |
July | 573.33 | 21.79 | 82.00 | 22.19 | 14.00 | 22.30 |
August | 604.00 | 21.81 | 56.50 | 22.11 | 7.33 | 22.17 |
September | 651.00 | 21.61 | 27.83 | 21.74 | 2.50 | 21.75 |
October | 735.50 | 21.27 | 57.67 | 21.23 | 54.33 | 21.18 |
November | 720.00 | 20.87 | 391.50 | 20.78 | 391.50 | 20.74 |
December | 744.00 | 20.60 | 685.00 | 20.58 | 685.00 | 20.57 |
Annual Sum or Average | 8142.00 | 21.20 | 3097.67 | 21.15 | 2832.33 | 21.05 |
Minimum of Months | 573.33 | 20.56 | 27.83 | 20.54 | 2.50 | 20.54 |
Maximum of Months | 744.00 | 21.81 | 695.50 | 22.19 | 695.50 | 22.30 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.79 | 473.67 | 20.72 | 473.67 | 20.69 |
February | 672.00 | 20.96 | 244.17 | 20.87 | 244.17 | 20.82 |
March | 744.00 | 21.11 | 116.67 | 21.07 | 116.67 | 21.03 |
April | 720.00 | 21.36 | 1.17 | 21.36 | 1.17 | 21.36 |
May | 744.00 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
June | 717.00 | 21.94 | 0.00 | 21.94 | 0.00 | 21.94 |
July | 739.33 | 21.99 | 1.00 | 21.99 | 1.00 | 21.99 |
August | 744.00 | 21.95 | 0.00 | 21.95 | 0.00 | 21.95 |
September | 719.50 | 21.66 | 0.17 | 21.66 | 0.17 | 21.66 |
October | 744.00 | 21.32 | 1.50 | 21.32 | 1.50 | 21.32 |
November | 720.00 | 21.06 | 193.83 | 20.99 | 193.83 | 20.95 |
December | 744.00 | 20.87 | 421.50 | 20.80 | 421.50 | 20.77 |
Annual Sum or Average | 8751.83 | 21.39 | 1453.67 | 21.29 | 1453.67 | 21.21 |
Minimum of Months | 672.00 | 20.79 | 0.00 | 20.72 | 0.00 | 20.69 |
Maximum of Months | 744.00 | 21.99 | 473.67 | 21.99 | 473.67 | 21.99 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.77 | 573.50 | 20.70 | 573.50 | 20.68 |
February | 672.00 | 21.10 | 327.33 | 20.98 | 327.33 | 20.92 |
March | 744.00 | 21.26 | 222.83 | 21.13 | 222.83 | 21.06 |
April | 708.83 | 21.42 | 60.00 | 21.36 | 60.00 | 21.31 |
May | 717.50 | 21.51 | 32.83 | 21.47 | 32.67 | 21.43 |
June | 602.67 | 21.41 | 14.83 | 21.46 | 0.00 | 21.46 |
July | 572.17 | 21.28 | 49.33 | 21.44 | 0.00 | 21.44 |
August | 588.33 | 21.32 | 39.50 | 21.45 | 0.00 | 21.45 |
September | 630.67 | 21.41 | 11.67 | 21.45 | 0.00 | 21.45 |
October | 736.17 | 21.50 | 8.17 | 21.49 | 8.17 | 21.48 |
November | 720.00 | 21.19 | 246.67 | 21.08 | 246.67 | 21.01 |
December | 744.00 | 20.83 | 553.67 | 20.77 | 553.67 | 20.75 |
Annual Sum or Average | 8180.33 | 21.24 | 2140.33 | 21.16 | 2024.83 | 21.08 |
Minimum of Months | 572.17 | 20.77 | 8.17 | 20.70 | 0.00 | 20.68 |
Maximum of Months | 744.00 | 21.51 | 573.50 | 21.49 | 573.50 | 21.48 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.57 | 683.67 | 20.55 | 683.67 | 20.55 |
February | 672.00 | 20.81 | 482.83 | 20.74 | 482.83 | 20.71 |
March | 744.00 | 21.03 | 317.00 | 20.93 | 317.00 | 20.88 |
April | 719.17 | 21.44 | 79.00 | 21.36 | 79.00 | 21.30 |
May | 718.83 | 21.70 | 37.67 | 21.65 | 35.33 | 21.60 |
June | 556.33 | 21.78 | 54.00 | 22.07 | 8.67 | 22.15 |
July | 509.33 | 21.71 | 94.00 | 22.24 | 18.67 | 22.39 |
August | 570.67 | 21.80 | 39.83 | 22.03 | 7.33 | 22.09 |
September | 671.33 | 21.72 | 10.17 | 21.77 | 1.33 | 21.78 |
October | 744.00 | 21.37 | 26.67 | 21.35 | 26.67 | 21.32 |
November | 720.00 | 20.84 | 396.33 | 20.77 | 396.33 | 20.73 |
December | 744.00 | 20.58 | 677.00 | 20.56 | 677.00 | 20.55 |
Annual Sum or Average | 8113.67 | 21.24 | 2898.17 | 21.16 | 2733.83 | 21.06 |
Minimum of Months | 509.33 | 20.57 | 10.17 | 20.55 | 1.33 | 20.55 |
Maximum of Months | 744.00 | 21.80 | 683.67 | 22.24 | 683.67 | 22.39 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 455.83 | 21.01 | 455.83 | 21.00 |
February | 672.00 | 21.11 | 203.67 | 21.08 | 203.67 | 21.07 |
March | 744.00 | 21.18 | 92.17 | 21.16 | 92.17 | 21.14 |
April | 720.00 | 21.57 | 6.17 | 21.57 | 6.17 | 21.56 |
May | 744.00 | 21.99 | 0.00 | 21.99 | 0.00 | 21.99 |
June | 676.17 | 23.04 | 8.33 | 23.04 | 8.33 | 23.05 |
July | 461.00 | 23.47 | 76.17 | 23.53 | 21.67 | 23.54 |
August | 610.67 | 23.39 | 0.50 | 23.39 | 0.00 | 23.39 |
September | 631.67 | 22.70 | 36.67 | 22.76 | 30.83 | 22.80 |
October | 744.00 | 21.88 | 0.00 | 21.88 | 0.00 | 21.88 |
November | 720.00 | 21.19 | 117.17 | 21.17 | 117.17 | 21.15 |
December | 744.00 | 21.00 | 372.17 | 21.00 | 372.17 | 21.00 |
Annual Sum or Average | 8211.50 | 21.88 | 1368.83 | 21.79 | 1308.00 | 21.71 |
Minimum of Months | 461.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 23.47 | 455.83 | 23.53 | 455.83 | 23.54 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.66 | 665.33 | 20.62 | 665.33 | 20.60 |
February | 667.67 | 20.93 | 462.00 | 20.83 | 462.00 | 20.79 |
March | 740.17 | 21.05 | 399.67 | 20.93 | 399.67 | 20.87 |
April | 706.17 | 21.26 | 144.33 | 21.14 | 143.17 | 21.06 |
May | 701.67 | 21.35 | 77.50 | 21.30 | 67.17 | 21.24 |
June | 624.00 | 21.41 | 35.17 | 21.51 | 0.17 | 21.51 |
July | 593.67 | 21.34 | 65.33 | 21.53 | 3.50 | 21.54 |
August | 612.50 | 21.35 | 51.50 | 21.51 | 0.00 | 21.51 |
September | 641.50 | 21.35 | 39.83 | 21.42 | 9.67 | 21.41 |
October | 730.83 | 21.34 | 83.17 | 21.28 | 81.50 | 21.23 |
November | 719.00 | 21.07 | 373.50 | 20.95 | 373.50 | 20.90 |
December | 744.00 | 20.72 | 647.00 | 20.68 | 647.00 | 20.67 |
Annual Sum or Average | 8225.17 | 21.14 | 3044.33 | 21.05 | 2852.67 | 20.97 |
Minimum of Months | 593.67 | 20.66 | 35.17 | 20.62 | 0.00 | 20.60 |
Maximum of Months | 744.00 | 21.41 | 665.33 | 21.53 | 665.33 | 21.54 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.50 | 734.00 | 20.50 | 734.00 | 20.50 |
February | 671.83 | 20.68 | 583.83 | 20.64 | 583.83 | 20.62 |
March | 744.00 | 20.79 | 555.50 | 20.72 | 555.50 | 20.69 |
April | 705.00 | 21.24 | 199.50 | 21.21 | 188.83 | 21.15 |
May | 669.00 | 21.51 | 132.67 | 21.73 | 91.17 | 21.72 |
June | 562.67 | 21.72 | 98.67 | 22.26 | 12.00 | 22.35 |
July | 558.83 | 21.78 | 98.83 | 22.25 | 21.17 | 22.39 |
August | 590.50 | 21.77 | 70.83 | 22.15 | 11.67 | 22.25 |
September | 648.50 | 21.53 | 48.50 | 21.66 | 19.00 | 21.65 |
October | 735.17 | 21.14 | 154.33 | 21.06 | 150.67 | 20.99 |
November | 720.00 | 20.74 | 530.83 | 20.68 | 530.83 | 20.66 |
December | 744.00 | 20.53 | 730.17 | 20.52 | 730.17 | 20.52 |
Annual Sum or Average | 8093.50 | 21.12 | 3937.67 | 21.09 | 3628.83 | 20.99 |
Minimum of Months | 558.83 | 20.50 | 48.50 | 20.50 | 11.67 | 20.50 |
Maximum of Months | 744.00 | 21.78 | 734.00 | 22.26 | 734.00 | 22.39 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 731.00 | 21.06 | 442.00 | 20.93 | 440.67 | 20.87 |
February | 640.33 | 21.28 | 217.17 | 21.18 | 211.33 | 21.10 |
March | 702.67 | 21.24 | 148.67 | 21.16 | 145.67 | 21.09 |
April | 678.00 | 21.32 | 63.50 | 21.28 | 60.67 | 21.23 |
May | 700.50 | 21.43 | 46.00 | 21.39 | 42.67 | 21.34 |
June | 635.67 | 21.45 | 8.67 | 21.47 | 0.00 | 21.47 |
July | 613.17 | 21.37 | 42.00 | 21.50 | 0.00 | 21.50 |
August | 614.33 | 21.36 | 61.67 | 21.54 | 0.00 | 21.54 |
September | 616.33 | 21.36 | 56.67 | 21.52 | 0.00 | 21.52 |
October | 670.50 | 21.39 | 34.33 | 21.45 | 7.17 | 21.45 |
November | 675.00 | 21.30 | 162.17 | 21.22 | 153.00 | 21.15 |
December | 725.00 | 21.14 | 366.67 | 21.02 | 366.67 | 20.96 |
Annual Sum or Average | 8002.50 | 21.30 | 1649.50 | 21.27 | 1427.83 | 21.20 |
Minimum of Months | 613.17 | 21.06 | 8.67 | 20.93 | 0.00 | 20.87 |
Maximum of Months | 731.00 | 21.45 | 442.00 | 21.54 | 440.67 | 21.54 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 666.67 | 22.62 | 165.00 | 22.30 | 165.00 | 22.09 |
February | 492.67 | 23.22 | 2.50 | 23.21 | 2.50 | 23.20 |
March | 422.33 | 23.33 | 0.00 | 23.33 | 0.00 | 23.33 |
April | 223.50 | 23.43 | 44.67 | 23.53 | 0.00 | 23.53 |
May | 109.50 | 23.30 | 233.17 | 23.77 | 0.00 | 23.77 |
June | 27.33 | 23.77 | 571.50 | 23.98 | 19.17 | 23.98 |
July | 31.50 | 24.00 | 703.50 | 23.99 | 31.50 | 23.99 |
August | 5.33 | 23.39 | 643.00 | 23.98 | 0.67 | 23.98 |
September | 86.83 | 23.57 | 426.67 | 23.92 | 37.50 | 23.92 |
October | 189.33 | 23.32 | 37.17 | 23.43 | 0.00 | 23.43 |
November | 452.33 | 23.37 | 0.00 | 23.37 | 0.00 | 23.37 |
December | 630.50 | 23.15 | 25.00 | 23.07 | 25.00 | 23.00 |
Annual Sum or Average | 3337.83 | 23.17 | 2852.17 | 23.45 | 281.33 | 23.39 |
Minimum of Months | 5.33 | 22.62 | 0.00 | 22.30 | 0.00 | 22.09 |
Maximum of Months | 666.67 | 24.00 | 703.50 | 23.99 | 165.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 517.50 | 22.47 | 114.67 | 22.20 | 114.67 | 22.02 |
February | 332.50 | 23.26 | 0.00 | 23.26 | 0.00 | 23.26 |
March | 247.00 | 23.39 | 4.50 | 23.40 | 0.00 | 23.40 |
April | 75.17 | 23.42 | 166.00 | 23.82 | 0.00 | 23.82 |
May | 31.33 | 23.31 | 341.67 | 23.94 | 0.00 | 23.94 |
June | 17.33 | 23.92 | 655.17 | 23.99 | 15.33 | 23.99 |
July | 28.67 | 24.00 | 729.67 | 23.99 | 28.67 | 23.99 |
August | 0.50 | 24.00 | 712.67 | 23.99 | 0.50 | 23.99 |
September | 46.33 | 23.86 | 544.17 | 23.98 | 35.50 | 23.98 |
October | 58.50 | 23.36 | 159.17 | 23.82 | 0.00 | 23.82 |
November | 277.17 | 23.44 | 23.17 | 23.48 | 0.00 | 23.48 |
December | 454.50 | 23.17 | 9.83 | 23.15 | 5.67 | 23.13 |
Annual Sum or Average | 2086.50 | 23.12 | 3460.67 | 23.60 | 200.33 | 23.55 |
Minimum of Months | 0.50 | 22.47 | 0.00 | 22.20 | 0.00 | 22.02 |
Maximum of Months | 517.50 | 24.00 | 729.67 | 23.99 | 114.67 | 23.99 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 464.50 | 23.17 | 550.83 | 23.47 | 345.17 | 23.55 |
February | 440.83 | 23.76 | 552.50 | 23.86 | 388.17 | 23.90 |
March | 483.00 | 23.89 | 637.50 | 23.91 | 456.67 | 23.94 |
April | 495.00 | 23.98 | 676.50 | 23.93 | 491.33 | 23.95 |
May | 523.17 | 23.99 | 720.83 | 23.94 | 522.33 | 23.95 |
June | 533.17 | 23.99 | 719.67 | 23.96 | 533.17 | 23.97 |
July | 568.17 | 23.99 | 744.00 | 23.98 | 568.17 | 23.98 |
August | 544.00 | 23.99 | 743.67 | 23.97 | 544.00 | 23.98 |
September | 523.67 | 23.99 | 716.67 | 23.95 | 523.67 | 23.96 |
October | 506.50 | 23.99 | 716.50 | 23.93 | 506.33 | 23.95 |
November | 478.33 | 23.89 | 624.17 | 23.91 | 450.17 | 23.93 |
December | 483.50 | 23.65 | 593.33 | 23.82 | 402.33 | 23.86 |
Annual Sum or Average | 6043.83 | 23.87 | 7996.17 | 23.89 | 5731.50 | 23.92 |
Minimum of Months | 440.83 | 23.17 | 550.83 | 23.47 | 345.17 | 23.55 |
Maximum of Months | 568.17 | 23.99 | 744.00 | 23.98 | 568.17 | 23.98 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 499.00 | 21.00 | 499.00 | 21.00 |
February | 672.00 | 21.10 | 233.00 | 21.08 | 233.00 | 21.06 |
March | 744.00 | 21.14 | 111.67 | 21.12 | 111.67 | 21.11 |
April | 720.00 | 21.49 | 7.67 | 21.49 | 7.67 | 21.48 |
May | 733.50 | 21.95 | 0.00 | 21.95 | 0.00 | 21.95 |
June | 564.67 | 22.79 | 53.83 | 22.89 | 1.33 | 22.89 |
July | 370.17 | 23.14 | 127.33 | 23.34 | 12.33 | 23.35 |
August | 510.83 | 23.04 | 33.17 | 23.10 | 0.00 | 23.10 |
September | 600.17 | 22.31 | 38.33 | 22.40 | 9.33 | 22.42 |
October | 744.00 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
November | 720.00 | 21.13 | 196.50 | 21.10 | 196.50 | 21.08 |
December | 744.00 | 21.01 | 445.17 | 21.01 | 445.17 | 21.00 |
Annual Sum or Average | 7867.33 | 21.69 | 1745.67 | 21.64 | 1516.00 | 21.56 |
Minimum of Months | 370.17 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 23.14 | 499.00 | 23.34 | 499.00 | 23.35 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.62744 | 17.61734 | -0.1545 | 6.59439 |
February | 672.00000 | 22.83629 | 21.80793 | -0.0898 | 5.39200 |
March | 744.00000 | 22.45269 | 23.33949 | -0.1757 | 5.81160 |
April | 720.00000 | 21.97351 | 27.53393 | -0.2692 | 6.69254 |
May | 744.00000 | 22.40302 | 30.97094 | -1.2153 | 36.19691 |
June | 720.00000 | 22.65092 | 38.49592 | -1.0770 | 29.65838 |
July | 744.00000 | 23.12699 | 41.64271 | -0.8847 | 21.75077 |
August | 744.00000 | 23.49839 | 35.75150 | -0.7917 | 18.40257 |
September | 720.00000 | 23.81880 | 35.34680 | -0.6729 | 14.70196 |
October | 744.00000 | 23.91210 | 26.40423 | 0.22407 | 6.09174 |
November | 720.00000 | 23.90259 | 22.13852 | 0.18934 | 5.80649 |
December | 744.00000 | 23.70819 | 20.05350 | 0.12205 | 5.50793 |
Annual Sum or Average | 8760.00000 | 23.07776 | 28.45274 | -0.4015 | 13.61038 |
Minimum of Months | 672.00000 | 21.97351 | 17.61734 | -1.2153 | 5.39200 |
Maximum of Months | 744.00000 | 23.91210 | 41.64271 | 0.22407 | 36.19691 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.16599 | 16.55891 | -0.6116 | 14.57867 |
February | 672.00000 | 21.44837 | 20.95204 | -0.4285 | 10.95551 |
March | 744.00000 | 21.45914 | 22.19822 | -0.3928 | 10.12449 |
April | 720.00000 | 21.59805 | 25.91886 | -0.3016 | 8.65100 |
May | 744.00000 | 21.71740 | 29.84051 | -1.3264 | 43.49466 |
June | 720.00000 | 22.31219 | 36.80127 | -1.0051 | 29.24391 |
July | 744.00000 | 22.84913 | 39.88359 | -0.7569 | 20.03909 |
August | 744.00000 | 22.83049 | 34.63790 | -0.7953 | 21.85124 |
September | 720.00000 | 22.43901 | 35.83255 | -0.9591 | 28.95301 |
October | 744.00000 | 21.87827 | 27.46585 | -0.1836 | 7.95057 |
November | 720.00000 | 21.44251 | 22.91497 | -0.3853 | 9.93010 |
December | 744.00000 | 21.21095 | 20.19819 | -0.5444 | 12.53070 |
Annual Sum or Average | 8760.00000 | 21.86510 | 27.79442 | -0.6424 | 18.24040 |
Minimum of Months | 672.00000 | 21.16599 | 16.55891 | -1.3264 | 7.95057 |
Maximum of Months | 744.00000 | 22.84913 | 39.88359 | -0.1836 | 43.49466 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.62518 | 18.69667 | -0.4032 | 9.32292 |
February | 672.00000 | 22.10645 | 22.82263 | -0.2440 | 7.14969 |
March | 744.00000 | 22.40568 | 23.74811 | -0.1586 | 6.21437 |
April | 720.00000 | 22.77368 | 26.99215 | -0.0414 | 5.60306 |
May | 744.00000 | 23.00068 | 30.47737 | -0.9581 | 25.52022 |
June | 720.00000 | 23.49124 | 37.08329 | -0.7217 | 16.64965 |
July | 744.00000 | 23.72570 | 40.29697 | -0.6003 | 12.93782 |
August | 744.00000 | 23.70935 | 35.34306 | -0.6431 | 14.07022 |
September | 720.00000 | 23.49449 | 36.33405 | -0.7273 | 17.05112 |
October | 744.00000 | 23.10674 | 28.38149 | 0.05584 | 5.45234 |
November | 720.00000 | 22.54464 | 24.34561 | -0.1203 | 5.94324 |
December | 744.00000 | 21.90879 | 22.07893 | -0.3025 | 7.56903 |
Annual Sum or Average | 8760.00000 | 22.82753 | 28.90791 | -0.4067 | 11.15424 |
Minimum of Months | 672.00000 | 21.62518 | 18.69667 | -0.9581 | 5.45234 |
Maximum of Months | 744.00000 | 23.72570 | 40.29697 | 0.05584 | 25.52022 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.60724 | 13.08561 | 0.38688 | 12.77553 |
February | 672.00000 | 23.15587 | 17.09911 | 0.56851 | 14.31318 |
March | 744.00000 | 23.20332 | 18.18583 | 0.60670 | 15.09201 |
April | 720.00000 | 23.26289 | 21.56866 | 0.66835 | 16.58913 |
May | 744.00000 | 23.28476 | 25.33573 | 0.01135 | 9.46235 |
June | 720.00000 | 23.31464 | 32.78010 | 0.12243 | 9.59115 |
July | 744.00000 | 23.33397 | 36.67545 | 0.17985 | 9.74264 |
August | 744.00000 | 23.33510 | 31.56812 | 0.13974 | 9.54405 |
September | 720.00000 | 23.33102 | 32.06517 | 0.10220 | 9.46176 |
October | 744.00000 | 23.31588 | 23.24280 | 0.70129 | 17.39509 |
November | 720.00000 | 23.25919 | 18.78528 | 0.62569 | 15.45241 |
December | 744.00000 | 23.08450 | 16.30177 | 0.53298 | 13.62203 |
Annual Sum or Average | 8760.00000 | 23.20686 | 23.92056 | 0.38576 | 12.74040 |
Minimum of Months | 672.00000 | 22.60724 | 13.08561 | 0.01135 | 9.46176 |
Maximum of Months | 744.00000 | 23.33510 | 36.67545 | 0.70129 | 17.39509 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.66794 | 21.07525 | -0.3914 | 10.52844 |
February | 672.00000 | 22.22928 | 25.16960 | -0.1505 | 7.78307 |
March | 744.00000 | 22.34916 | 26.28795 | -0.0969 | 7.20211 |
April | 720.00000 | 22.60125 | 29.72304 | 0.00909 | 6.67820 |
May | 744.00000 | 22.77204 | 33.39253 | -0.8976 | 24.46906 |
June | 720.00000 | 23.28716 | 40.12182 | -0.6089 | 14.51316 |
July | 744.00000 | 23.58235 | 43.29848 | -0.4344 | 10.15791 |
August | 744.00000 | 23.58512 | 38.18880 | -0.4628 | 11.11922 |
September | 720.00000 | 23.36540 | 39.12657 | -0.5682 | 14.72749 |
October | 744.00000 | 22.99297 | 31.02573 | 0.15045 | 7.00770 |
November | 720.00000 | 22.43621 | 26.90855 | -0.0681 | 6.97656 |
December | 744.00000 | 21.81008 | 24.57054 | -0.3035 | 8.70758 |
Annual Sum or Average | 8760.00000 | 22.72512 | 31.60045 | -0.3200 | 10.84860 |
Minimum of Months | 672.00000 | 21.66794 | 21.07525 | -0.8976 | 6.67820 |
Maximum of Months | 744.00000 | 23.58512 | 43.29848 | 0.15045 | 24.46906 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.07895 | 20.88284 | -0.2624 | 7.99132 |
February | 672.00000 | 22.71549 | 24.87854 | -0.0629 | 6.18952 |
March | 744.00000 | 22.96551 | 25.81984 | 0.01264 | 5.79379 |
April | 720.00000 | 23.20864 | 29.02351 | 0.10446 | 5.81809 |
May | 744.00000 | 23.33924 | 32.48422 | -0.7867 | 19.13107 |
June | 720.00000 | 23.65132 | 38.99716 | -0.5974 | 12.98756 |
July | 744.00000 | 23.79824 | 42.25357 | -0.4996 | 10.49073 |
August | 744.00000 | 23.81104 | 37.22534 | -0.5310 | 11.16955 |
September | 720.00000 | 23.72256 | 38.11306 | -0.5772 | 12.64087 |
October | 744.00000 | 23.52698 | 30.21691 | 0.20603 | 6.22765 |
November | 720.00000 | 23.10469 | 26.38454 | 0.05371 | 5.84224 |
December | 744.00000 | 22.48384 | 24.17108 | -0.1345 | 6.41144 |
Annual Sum or Average | 8760.00000 | 23.20210 | 30.89538 | -0.2578 | 9.24836 |
Minimum of Months | 672.00000 | 22.07895 | 20.88284 | -0.7867 | 5.79379 |
Maximum of Months | 744.00000 | 23.81104 | 42.25357 | 0.20603 | 19.13107 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.75564 | 32.38658 | -0.7117 | 16.73326 |
February | 672.00000 | 21.05725 | 36.92273 | -0.5413 | 12.33966 |
March | 744.00000 | 21.17376 | 38.14906 | -0.4707 | 10.70557 |
April | 720.00000 | 21.38255 | 40.36927 | -0.3431 | 8.54325 |
May | 744.00000 | 21.51164 | 42.71808 | -1.3930 | 46.24736 |
June | 720.00000 | 21.68223 | 45.92051 | -1.2046 | 37.08948 |
July | 744.00000 | 21.72777 | 47.33605 | -1.1168 | 33.13703 |
August | 744.00000 | 21.70676 | 45.36917 | -1.1634 | 35.30661 |
September | 720.00000 | 21.61610 | 46.40668 | -1.2746 | 40.62351 |
October | 744.00000 | 21.46412 | 41.87936 | -0.3064 | 7.89522 |
November | 720.00000 | 21.18271 | 38.67232 | -0.4756 | 10.72133 |
December | 744.00000 | 20.84129 | 36.83990 | -0.6407 | 14.42409 |
Annual Sum or Average | 8760.00000 | 21.34280 | 41.09568 | -0.8054 | 22.88428 |
Minimum of Months | 672.00000 | 20.75564 | 32.38658 | -1.3930 | 7.89522 |
Maximum of Months | 744.00000 | 21.72777 | 47.33605 | -0.3064 | 46.24736 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.56084 | 32.80989 | -0.7862 | 18.81976 |
February | 672.00000 | 20.78229 | 37.48841 | -0.6430 | 14.47264 |
March | 744.00000 | 20.91072 | 38.69146 | -0.5627 | 12.23316 |
April | 720.00000 | 21.40220 | 40.52663 | -0.3669 | 9.24775 |
May | 744.00000 | 21.82766 | 42.39917 | -1.3286 | 44.86288 |
June | 720.00000 | 22.25006 | 45.22416 | -1.0584 | 32.35617 |
July | 744.00000 | 22.27395 | 46.81561 | -0.9833 | 28.97366 |
August | 744.00000 | 22.23852 | 44.73539 | -1.0518 | 31.64643 |
September | 720.00000 | 21.84407 | 46.34736 | -1.2619 | 40.54313 |
October | 744.00000 | 21.31240 | 42.17744 | -0.3830 | 8.77295 |
November | 720.00000 | 20.86644 | 39.36609 | -0.5830 | 12.64535 |
December | 744.00000 | 20.60114 | 37.39616 | -0.7231 | 16.58109 |
Annual Sum or Average | 8760.00000 | 21.40896 | 41.17639 | -0.8123 | 22.65094 |
Minimum of Months | 672.00000 | 20.56084 | 32.80989 | -1.3286 | 8.77295 |
Maximum of Months | 744.00000 | 22.27395 | 46.81561 | -0.3669 | 44.86288 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.78688 | 28.18512 | -0.6604 | 14.78100 |
February | 672.00000 | 20.95730 | 33.14607 | -0.5659 | 12.04152 |
March | 744.00000 | 21.11343 | 34.35083 | -0.4986 | 10.34361 |
April | 720.00000 | 21.35971 | 36.52366 | -0.3929 | 8.43410 |
May | 744.00000 | 21.64495 | 38.89270 | -1.4386 | 48.10529 |
June | 720.00000 | 21.94513 | 43.16062 | -1.2575 | 39.04413 |
July | 744.00000 | 22.00205 | 45.89700 | -1.2023 | 36.39233 |
August | 744.00000 | 21.95075 | 42.61418 | -1.2613 | 39.09349 |
September | 720.00000 | 21.66460 | 43.74110 | -1.3882 | 45.41390 |
October | 744.00000 | 21.32320 | 38.16120 | -0.3920 | 8.33477 |
November | 720.00000 | 21.06079 | 34.91228 | -0.5119 | 10.67118 |
December | 744.00000 | 20.86638 | 32.86135 | -0.6007 | 12.90199 |
Annual Sum or Average | 8760.00000 | 21.39186 | 37.72069 | -0.8494 | 23.87011 |
Minimum of Months | 672.00000 | 20.78688 | 28.18512 | -1.4386 | 8.33477 |
Maximum of Months | 744.00000 | 22.00205 | 45.89700 | -0.3920 | 48.10529 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.76838 | 32.34618 | -0.7046 | 16.51734 |
February | 672.00000 | 21.10272 | 36.86241 | -0.5290 | 12.09276 |
March | 744.00000 | 21.25654 | 38.01942 | -0.4467 | 10.40330 |
April | 720.00000 | 21.45222 | 40.31319 | -0.3224 | 8.47612 |
May | 744.00000 | 21.57602 | 42.55022 | -1.3798 | 45.66065 |
June | 720.00000 | 21.72042 | 45.41638 | -1.1777 | 36.04165 |
July | 744.00000 | 21.75052 | 46.90620 | -1.0915 | 32.18715 |
August | 744.00000 | 21.73785 | 45.07833 | -1.1353 | 34.18519 |
September | 720.00000 | 21.65063 | 46.30983 | -1.2603 | 39.97036 |
October | 744.00000 | 21.51568 | 41.80105 | -0.2931 | 7.81661 |
November | 720.00000 | 21.19331 | 38.68113 | -0.4747 | 10.68327 |
December | 744.00000 | 20.83076 | 36.84632 | -0.6411 | 14.35353 |
Annual Sum or Average | 8760.00000 | 21.38050 | 40.94176 | -0.7899 | 22.43446 |
Minimum of Months | 672.00000 | 20.76838 | 32.34618 | -1.3798 | 7.81661 |
Maximum of Months | 744.00000 | 21.75052 | 46.90620 | -0.2931 | 45.66065 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.57312 | 32.75748 | -0.7798 | 18.63213 |
February | 672.00000 | 20.81328 | 37.39452 | -0.6344 | 14.20591 |
March | 744.00000 | 21.03267 | 38.39673 | -0.5319 | 11.59809 |
April | 720.00000 | 21.44122 | 40.23318 | -0.3543 | 8.71132 |
May | 744.00000 | 21.77157 | 42.14302 | -1.3519 | 44.43181 |
June | 720.00000 | 22.24048 | 44.62292 | -1.0466 | 31.60572 |
July | 744.00000 | 22.36131 | 46.12737 | -0.9396 | 27.97717 |
August | 744.00000 | 22.25649 | 44.28560 | -1.0271 | 30.44255 |
September | 720.00000 | 21.85721 | 46.19677 | -1.2541 | 39.76573 |
October | 744.00000 | 21.37205 | 42.03171 | -0.3693 | 8.39958 |
November | 720.00000 | 20.84342 | 39.36198 | -0.5897 | 12.77009 |
December | 744.00000 | 20.58437 | 37.40468 | -0.7255 | 16.65026 |
Annual Sum or Average | 8760.00000 | 21.43217 | 40.92339 | -0.8016 | 22.15186 |
Minimum of Months | 672.00000 | 20.57312 | 32.75748 | -1.3519 | 8.39958 |
Maximum of Months | 744.00000 | 22.36131 | 46.19677 | -0.3543 | 44.43181 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.65576 | 33.20423 | -0.7861 | 19.10220 |
February | 672.00000 | 20.94380 | 37.85903 | -0.6063 | 14.05488 |
March | 744.00000 | 21.05994 | 39.16439 | -0.5301 | 12.14127 |
April | 720.00000 | 21.29778 | 41.35790 | -0.3828 | 9.44364 |
May | 744.00000 | 21.46372 | 43.50336 | -1.4256 | 48.00667 |
June | 720.00000 | 21.66167 | 46.43877 | -1.2177 | 38.00941 |
July | 744.00000 | 21.71795 | 47.80520 | -1.1200 | 33.61110 |
August | 744.00000 | 21.68701 | 45.83537 | -1.1778 | 36.31099 |
September | 720.00000 | 21.56457 | 47.37252 | -1.3145 | 42.81362 |
October | 744.00000 | 21.37125 | 42.86977 | -0.3545 | 8.70039 |
November | 720.00000 | 21.06838 | 39.67807 | -0.5364 | 12.08069 |
December | 744.00000 | 20.71927 | 37.80626 | -0.7139 | 16.53365 |
Annual Sum or Average | 8760.00000 | 21.26882 | 41.92141 | -0.8490 | 24.30288 |
Minimum of Months | 672.00000 | 20.65576 | 33.20423 | -1.4256 | 8.70039 |
Maximum of Months | 744.00000 | 21.71795 | 47.80520 | -0.3545 | 48.00667 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.50478 | 33.59607 | -0.8530 | 21.17920 |
February | 672.00000 | 20.68558 | 38.44501 | -0.7068 | 16.36855 |
March | 744.00000 | 20.78628 | 39.76117 | -0.6268 | 13.95073 |
April | 720.00000 | 21.32881 | 41.57831 | -0.4047 | 10.36805 |
May | 744.00000 | 21.83120 | 43.19382 | -1.3432 | 46.51965 |
June | 720.00000 | 22.27967 | 45.65714 | -1.0505 | 33.03762 |
July | 744.00000 | 22.27483 | 47.17703 | -0.9790 | 29.49497 |
August | 744.00000 | 22.23376 | 45.17323 | -1.0579 | 32.63360 |
September | 720.00000 | 21.77321 | 47.37914 | -1.3077 | 43.10427 |
October | 744.00000 | 21.18089 | 43.34337 | -0.4421 | 9.91811 |
November | 720.00000 | 20.73794 | 40.45693 | -0.6494 | 14.40901 |
December | 744.00000 | 20.52548 | 38.30411 | -0.7884 | 18.72305 |
Annual Sum or Average | 8760.00000 | 21.34860 | 42.01539 | -0.8519 | 24.19421 |
Minimum of Months | 672.00000 | 20.50478 | 33.59607 | -1.3432 | 9.91811 |
Maximum of Months | 744.00000 | 22.27967 | 47.37914 | -0.4047 | 46.51965 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.09778 | 32.93135 | -0.5832 | 14.23689 |
February | 672.00000 | 21.37457 | 37.21379 | -0.4147 | 10.47399 |
March | 744.00000 | 21.35603 | 38.43350 | -0.3949 | 9.84846 |
April | 720.00000 | 21.43931 | 40.49768 | -0.3290 | 8.65709 |
May | 744.00000 | 21.53915 | 42.73395 | -1.4198 | 47.77237 |
June | 720.00000 | 21.66774 | 45.80477 | -1.2660 | 40.20527 |
July | 744.00000 | 21.71524 | 47.48098 | -1.1769 | 36.08072 |
August | 744.00000 | 21.70314 | 45.27124 | -1.1940 | 37.09877 |
September | 720.00000 | 21.63928 | 46.28224 | -1.2631 | 40.51330 |
October | 744.00000 | 21.57824 | 41.72732 | -0.2458 | 7.70130 |
November | 720.00000 | 21.42469 | 38.84252 | -0.3674 | 9.52101 |
December | 744.00000 | 21.20002 | 36.98499 | -0.5097 | 12.17533 |
Annual Sum or Average | 8760.00000 | 21.47807 | 41.19799 | -0.7661 | 22.93836 |
Minimum of Months | 672.00000 | 21.09778 | 32.93135 | -1.4198 | 7.70130 |
Maximum of Months | 744.00000 | 21.71524 | 47.48098 | -0.2458 | 47.77237 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.75973 | 22.37786 | -0.1085 | 7.69935 |
February | 672.00000 | 23.42737 | 26.06008 | 0.09931 | 6.11714 |
March | 744.00000 | 23.61846 | 26.63258 | 0.17404 | 6.08050 |
April | 720.00000 | 23.80474 | 29.29485 | 0.27597 | 6.83216 |
May | 744.00000 | 23.87169 | 32.42495 | -0.5415 | 11.57019 |
June | 720.00000 | 23.96722 | 38.81608 | -0.3911 | 8.43037 |
July | 744.00000 | 23.98745 | 42.32582 | -0.3264 | 7.36095 |
August | 744.00000 | 23.96742 | 37.61167 | -0.3890 | 8.28988 |
September | 720.00000 | 23.90806 | 38.63623 | -0.4596 | 9.83864 |
October | 744.00000 | 23.80306 | 30.92395 | 0.28937 | 6.93389 |
November | 720.00000 | 23.60138 | 27.33184 | 0.17307 | 6.12701 |
December | 744.00000 | 23.28065 | 25.38339 | 0.04725 | 6.18642 |
Annual Sum or Average | 8760.00000 | 23.66671 | 31.50723 | -0.0980 | 7.63255 |
Minimum of Months | 672.00000 | 22.75973 | 22.37786 | -0.5415 | 6.08050 |
Maximum of Months | 744.00000 | 23.98745 | 42.32582 | 0.28937 | 11.57019 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.92843 | 21.52993 | -0.0278 | 7.56643 |
February | 672.00000 | 23.62828 | 25.07558 | 0.18935 | 6.43040 |
March | 744.00000 | 23.78731 | 25.64228 | 0.25595 | 6.63906 |
April | 720.00000 | 23.91142 | 28.36692 | 0.34142 | 7.57435 |
May | 744.00000 | 23.94338 | 31.61034 | -0.4619 | 9.71363 |
June | 720.00000 | 23.98819 | 38.24298 | -0.3385 | 7.58093 |
July | 744.00000 | 23.99473 | 41.84986 | -0.2834 | 6.80556 |
August | 744.00000 | 23.98679 | 37.08821 | -0.3406 | 7.52203 |
September | 720.00000 | 23.95854 | 37.93611 | -0.3941 | 8.52216 |
October | 744.00000 | 23.90739 | 30.01227 | 0.35257 | 7.68960 |
November | 720.00000 | 23.76963 | 26.32727 | 0.25495 | 6.67473 |
December | 744.00000 | 23.48945 | 24.39267 | 0.13975 | 6.35933 |
Annual Sum or Average | 8760.00000 | 23.77421 | 30.69646 | -0.0277 | 7.42954 |
Minimum of Months | 672.00000 | 22.92843 | 21.52993 | -0.4619 | 6.35933 |
Maximum of Months | 744.00000 | 23.99473 | 41.84986 | 0.35257 | 9.71363 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.23820 | 21.32186 | 0.65454 | 19.25189 |
February | 672.00000 | 23.69529 | 23.90449 | 0.83655 | 22.67650 |
March | 744.00000 | 23.75774 | 24.64389 | 0.88948 | 24.29188 |
April | 720.00000 | 23.83301 | 27.64717 | 0.98052 | 27.49650 |
May | 744.00000 | 23.86984 | 31.11148 | 0.46196 | 14.24394 |
June | 720.00000 | 23.93696 | 37.96564 | 0.62470 | 17.77945 |
July | 744.00000 | 23.96379 | 41.62371 | 0.70455 | 19.78608 |
August | 744.00000 | 23.95688 | 36.85193 | 0.64149 | 18.00228 |
September | 720.00000 | 23.91328 | 37.38168 | 0.55274 | 15.93877 |
October | 744.00000 | 23.85338 | 29.25720 | 0.99420 | 27.86361 |
November | 720.00000 | 23.77024 | 25.32589 | 0.88907 | 24.05470 |
December | 744.00000 | 23.63872 | 23.35799 | 0.78918 | 21.18483 |
Annual Sum or Average | 8760.00000 | 23.78550 | 30.06068 | 0.75077 | 21.03119 |
Minimum of Months | 672.00000 | 23.23820 | 21.32186 | 0.46196 | 14.24394 |
Maximum of Months | 744.00000 | 23.96379 | 41.62371 | 0.99420 | 27.86361 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00876 | 16.23564 | -0.6156 | 13.14651 |
February | 672.00000 | 21.11480 | 20.67102 | -0.5355 | 11.18838 |
March | 744.00000 | 21.15486 | 21.90886 | -0.4989 | 10.32122 |
April | 720.00000 | 21.58181 | 25.34268 | -0.3650 | 8.04707 |
May | 744.00000 | 22.03406 | 28.67618 | -1.3389 | 42.90155 |
June | 720.00000 | 23.02766 | 34.90728 | -0.9519 | 24.78291 |
July | 744.00000 | 23.52473 | 37.89496 | -0.7556 | 17.46111 |
August | 744.00000 | 23.39563 | 33.08620 | -0.8347 | 20.10636 |
September | 720.00000 | 22.85052 | 34.45381 | -1.0160 | 28.05880 |
October | 744.00000 | 22.05373 | 26.63373 | -0.2386 | 6.46275 |
November | 720.00000 | 21.38169 | 22.37590 | -0.4387 | 9.31224 |
December | 744.00000 | 21.02813 | 19.86539 | -0.5665 | 11.83169 |
Annual Sum or Average | 8760.00000 | 22.01825 | 26.86167 | -0.6807 | 17.00951 |
Minimum of Months | 672.00000 | 21.00876 | 16.23564 | -1.3389 | 6.46275 |
Maximum of Months | 744.00000 | 23.52473 | 37.89496 | -0.2386 | 42.90155 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00781 | 19.95968 | -0.5910 | 12.43498 |
February | 672.00000 | 21.10609 | 24.44782 | -0.5217 | 10.83248 |
March | 744.00000 | 21.17965 | 25.65614 | -0.4834 | 9.99310 |
April | 720.00000 | 21.57040 | 29.14876 | -0.3603 | 7.96442 |
May | 744.00000 | 21.98911 | 32.57939 | -1.3522 | 43.46489 |
June | 720.00000 | 23.08440 | 38.78547 | -0.9293 | 23.84044 |
July | 744.00000 | 23.63540 | 41.61179 | -0.7144 | 16.11003 |
August | 744.00000 | 23.48928 | 36.85250 | -0.7989 | 18.87804 |
September | 720.00000 | 22.84740 | 38.33645 | -1.0137 | 28.17876 |
October | 744.00000 | 21.87596 | 30.69540 | -0.2735 | 6.86199 |
November | 720.00000 | 21.19480 | 26.37407 | -0.4781 | 9.92255 |
December | 744.00000 | 21.00381 | 23.61890 | -0.5626 | 11.68553 |
Annual Sum or Average | 8760.00000 | 22.00409 | 30.69608 | -0.6743 | 16.71994 |
Minimum of Months | 672.00000 | 21.00381 | 19.95968 | -1.3522 | 6.86199 |
Maximum of Months | 744.00000 | 23.63540 | 41.61179 | -0.2735 | 43.46489 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00413 | 17.06690 | -0.6253 | 13.45768 |
February | 672.00000 | 21.10169 | 21.58876 | -0.5336 | 11.18264 |
March | 744.00000 | 21.14198 | 22.82208 | -0.4947 | 10.28226 |
April | 720.00000 | 21.49274 | 26.32198 | -0.3658 | 8.22124 |
May | 744.00000 | 21.97479 | 29.66774 | -1.3202 | 42.19922 |
June | 720.00000 | 23.02043 | 35.70854 | -0.8979 | 23.38969 |
July | 744.00000 | 23.51263 | 38.69870 | -0.6936 | 15.95170 |
August | 744.00000 | 23.31843 | 34.03914 | -0.7988 | 19.47120 |
September | 720.00000 | 22.56892 | 35.79510 | -1.0612 | 30.84400 |
October | 744.00000 | 21.62905 | 28.08230 | -0.3162 | 7.46044 |
November | 720.00000 | 21.12618 | 23.57231 | -0.4946 | 10.27660 |
December | 744.00000 | 21.00909 | 20.74001 | -0.5802 | 12.17248 |
Annual Sum or Average | 8760.00000 | 21.91339 | 27.86588 | -0.6828 | 17.11207 |
Minimum of Months | 672.00000 | 21.00413 | 17.06690 | -1.3202 | 7.46044 |
Maximum of Months | 744.00000 | 23.51263 | 38.69870 | -0.3162 | 42.19922 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.06866 | 15.66972 | -0.5910 | 12.56633 |
February | 672.00000 | 21.22277 | 20.04354 | -0.5048 | 10.59682 |
March | 744.00000 | 21.36327 | 21.15422 | -0.4494 | 9.41963 |
April | 720.00000 | 21.84702 | 24.46225 | -0.3058 | 7.27093 |
May | 744.00000 | 22.27676 | 27.77604 | -1.2611 | 39.10152 |
June | 720.00000 | 23.24630 | 33.93104 | -0.8805 | 21.99084 |
July | 744.00000 | 23.67271 | 36.98958 | -0.7041 | 15.78660 |
August | 744.00000 | 23.58309 | 32.14746 | -0.7716 | 17.88673 |
September | 720.00000 | 23.09214 | 33.44347 | -0.9373 | 24.76139 |
October | 744.00000 | 22.35684 | 25.66922 | -0.1715 | 5.89898 |
November | 720.00000 | 21.61044 | 21.59029 | -0.3844 | 8.47855 |
December | 744.00000 | 21.11272 | 19.26887 | -0.5379 | 11.22026 |
Annual Sum or Average | 8760.00000 | 22.20978 | 26.03550 | -0.6259 | 15.45218 |
Minimum of Months | 672.00000 | 21.06866 | 15.66972 | -1.2611 | 5.89898 |
Maximum of Months | 744.00000 | 23.67271 | 36.98958 | -0.1715 | 39.10152 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.151843E+10 | 18801.07 | 02-JAN-16:03 | 128.59 | 0.483839E+10 | 0.00 | 0.635682E+10 | 0.55 | 3.19 | 01-JAN-15:35 | 0.00 | 0.00 |
February | 0.567171E+10 | 57375.62 | 27-FEB-16:01 | 234.60 | 0.177944E+11 | 0.00 | 0.234661E+11 | 1.11 | 3.66 | 27-FEB-16:01 | 0.00 | 0.00 |
March | 0.729396E+10 | 43011.43 | 28-MAR-15:02 | 323.75 | 0.232258E+11 | 0.00 | 0.305197E+11 | 1.39 | 3.19 | 01-MAR-11:05 | 0.00 | 0.00 |
April | 0.193323E+11 | 80001.24 | 06-APR-15:03 | 512.25 | 0.596487E+11 | 0.00 | 0.789809E+11 | 2.24 | 3.95 | 06-APR-15:03 | 0.00 | 0.00 |
May | 0.411658E+11 | 108398.57 | 19-MAY-15:03 | 630.57 | 0.127620E+12 | 0.00 | 0.168785E+12 | 2.66 | 3.81 | 20-MAY-18:03 | 0.00 | 0.00 |
June | 0.892633E+11 | 129046.28 | 20-JUN-18:03 | 709.12 | 0.282682E+12 | 0.00 | 0.371945E+12 | 3.09 | 3.92 | 21-JUN-21:53 | 0.00 | 0.00 |
July | 0.139575E+12 | 183165.32 | 17-JUL-18:02 | 744.00 | 0.442757E+12 | 0.00 | 0.582332E+12 | 3.15 | 4.33 | 18-JUL-21:52 | 0.00 | 0.00 |
August | 0.120773E+12 | 150968.90 | 05-AUG-18:03 | 742.76 | 0.381282E+12 | 0.00 | 0.502055E+12 | 3.13 | 3.95 | 10-AUG-21:52 | 0.00 | 0.00 |
September | 0.750072E+11 | 146093.14 | 02-SEP-15:03 | 681.40 | 0.236963E+12 | 0.00 | 0.311970E+12 | 2.97 | 3.96 | 07-SEP-18:01 | 0.00 | 0.00 |
October | 0.273999E+11 | 103138.02 | 18-OCT-15:03 | 617.56 | 0.856847E+11 | 0.00 | 0.113085E+12 | 2.62 | 4.01 | 16-OCT-15:03 | 0.00 | 0.00 |
November | 0.928117E+10 | 50922.21 | 17-NOV-16:01 | 388.02 | 0.293555E+11 | 0.00 | 0.386366E+11 | 1.71 | 3.40 | 04-NOV-15:01 | 0.00 | 0.00 |
December | 0.138917E+10 | 15386.46 | 07-DEC-16:03 | 145.40 | 0.442646E+10 | 0.00 | 0.581562E+10 | 0.62 | 3.19 | 03-DEC-14:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.537671E+12 | 5858.03 | 0.169628E+13 | 0.00 | 0.223395E+13 | 2.11 | 0.00 | 0.00 | ||||
Minimum of Months | 0.138917E+10 | 15386.46 | 128.59 | 0.442646E+10 | 0.00 | 0.581562E+10 | 0.55 | 3.19 | 0.00 | 0.00 | ||
Maximum of Months | 0.139575E+12 | 183165.32 | 744.00 | 0.442757E+12 | 0.00 | 0.582332E+12 | 3.15 | 4.33 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.492941E+12 | 0.00 | 739.83 | 741195.59 | 11-JAN-06:00 | 0.00 | 49.68 | 81.27 | 1.33 | 0.00 | 0.28 | 1.13 | 11-JAN-06:00 |
February | 0.156906E+12 | 0.00 | 657.40 | 581543.28 | 01-FEB-03:32 | 0.00 | 50.48 | 80.16 | 0.46 | 0.00 | 0.10 | 0.89 | 01-FEB-03:32 |
March | 0.110669E+12 | 0.00 | 724.73 | 292669.56 | 04-MAR-24:00 | 0.00 | 50.88 | 79.98 | 0.30 | 0.00 | 0.06 | 0.45 | 04-MAR-24:00 |
April | 0.642956E+11 | 0.00 | 610.15 | 171629.95 | 01-APR-08:62 | 0.00 | 43.97 | 72.80 | 0.16 | 0.00 | 0.04 | 0.26 | 01-APR-08:62 |
May | 0.611401E+11 | 0.00 | 496.08 | 157833.71 | 15-MAY-08:05 | 0.00 | 37.45 | 63.09 | 0.13 | 0.00 | 0.03 | 0.24 | 15-MAY-08:05 |
June | 0.403326E+11 | 0.00 | 267.94 | 130726.92 | 16-JUN-15:07 | 0.00 | 29.94 | 47.54 | 0.08 | 0.00 | 0.02 | 0.20 | 16-JUN-15:07 |
July | 0.209097E+11 | 0.00 | 149.33 | 110915.28 | 09-JUL-02:50 | 0.00 | 28.26 | 38.62 | 0.04 | 0.00 | 0.01 | 0.17 | 09-JUL-02:50 |
August | 0.291426E+11 | 0.00 | 197.00 | 115651.54 | 17-AUG-15:05 | 0.00 | 28.62 | 42.22 | 0.05 | 0.00 | 0.02 | 0.18 | 17-AUG-15:05 |
September | 0.427690E+11 | 0.00 | 349.67 | 176647.01 | 13-SEP-08:62 | 0.00 | 35.13 | 54.62 | 0.09 | 0.00 | 0.03 | 0.27 | 13-SEP-08:62 |
October | 0.737352E+11 | 0.00 | 615.48 | 168749.50 | 31-OCT-15:03 | 0.00 | 42.57 | 72.36 | 0.17 | 0.00 | 0.04 | 0.26 | 31-OCT-15:03 |
November | 0.111050E+12 | 0.00 | 700.19 | 258783.43 | 26-NOV-19:01 | 0.00 | 48.07 | 79.67 | 0.31 | 0.00 | 0.07 | 0.40 | 26-NOV-19:01 |
December | 0.235880E+12 | 0.00 | 743.67 | 717230.47 | 29-DEC-09:03 | 0.00 | 49.48 | 81.32 | 0.64 | 0.00 | 0.13 | 1.10 | 29-DEC-09:03 |
Annual Sum or Average | 0.143977E+13 | 0.00 | 6251.47 | 0.00 | 41.16 | 66.05 | 0.31 | 0.00 | 0.07 | ||||
Minimum of Months | 0.209097E+11 | 0.00 | 149.33 | 110915.28 | 0.00 | 28.26 | 38.62 | 0.04 | 0.00 | 0.01 | 0.17 | ||
Maximum of Months | 0.492941E+12 | 0.00 | 743.67 | 741195.59 | 0.00 | 50.88 | 81.32 | 1.33 | 0.00 | 0.28 | 1.13 |
Report: DXReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.184293E+10 | 0.00 | 743.83 | 0.184293E+10 | 0.00 | 0.00 | 1.00 | 01-JAN-00:20 | 0.00 | 01-JAN-00:10 | 688.22 | 01-JAN-00:30 | 688.22 | 12-JAN-22:40 | 0.00 | 09-JAN-17:20 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.509955E+11 | 0.00 | 481.86 | 0.509955E+11 | -0.0 | 0.00 | 1.00 | 01-FEB-00:05 | 0.00 | 01-FEB-01:10 | 32140.97 | 18-FEB-06:13 | 32140.97 | 18-FEB-05:50 | 0.00 | 02-FEB-00:07 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 0.582516E+11 | 0.00 | 512.82 | 0.582516E+11 | -0.0 | 0.00 | 1.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:20 | 44099.28 | 31-MAR-23:05 | 44099.28 | 31-MAR-23:05 | 0.00 | 01-MAR-01:05 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 0.585353E+11 | 0.00 | 445.02 | 0.585353E+11 | -0.0 | 0.00 | 1.00 | 01-APR-01:07 | 0.00 | 01-APR-00:20 | 44083.59 | 01-APR-01:07 | 44083.59 | 01-APR-13:15 | 0.00 | 07-APR-18:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.585291E+11 | 0.00 | 430.32 | 0.585291E+11 | 0.00 | 0.00 | 1.00 | 01-MAY-04:15 | 0.00 | 01-MAY-00:05 | 48253.29 | 01-MAY-04:15 | 48253.29 | 01-MAY-04:15 | 0.00 | 03-MAY-08:63 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.549686E+11 | 0.00 | 390.31 | 0.549686E+11 | -0.0 | 0.00 | 1.00 | 01-JUN-04:07 | 0.00 | 01-JUN-00:05 | 55372.00 | 01-JUN-18:20 | 55372.00 | 01-JUN-05:30 | 0.00 | 13-JUN-21:50 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.545650E+11 | 0.00 | 384.65 | 0.545650E+11 | 0.00 | 0.00 | 1.00 | 01-JUL-05:06 | 0.00 | 01-JUL-00:20 | 59052.04 | 01-JUL-06:05 | 59052.04 | 01-JUL-06:05 | 0.00 | 23-JUL-21:51 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.526655E+11 | 0.00 | 384.99 | 0.526655E+11 | -0.0 | 0.00 | 1.00 | 01-AUG-04:07 | 0.00 | 01-AUG-00:05 | 56352.05 | 01-AUG-04:07 | 56352.05 | 01-AUG-17:13 | 0.00 | 03-AUG-17:15 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.508223E+11 | 0.00 | 379.55 | 0.508223E+11 | -0.0 | 0.00 | 1.00 | 01-SEP-04:07 | 0.00 | 01-SEP-00:05 | 52589.66 | 30-SEP-05:06 | 52589.66 | 30-SEP-07:25 | 0.00 | 08-SEP-18:45 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.527402E+11 | 0.00 | 423.77 | 0.527402E+11 | 0.00 | 0.00 | 1.00 | 01-OCT-05:05 | 0.00 | 01-OCT-00:20 | 45382.29 | 31-OCT-05:20 | 45382.29 | 31-OCT-19:20 | 0.00 | 01-OCT-07:13 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.515484E+11 | 0.00 | 452.25 | 0.515484E+11 | 0.00 | 0.00 | 1.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:05 | 37962.03 | 30-NOV-08:40 | 37962.03 | 30-NOV-08:62 | 0.00 | 04-NOV-10:03 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.509856E+11 | 0.00 | 533.25 | 0.509856E+11 | -0.0 | 0.00 | 1.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:20 | 29253.12 | 31-DEC-02:20 | 29253.12 | 31-DEC-18:25 | 0.00 | 01-DEC-11:08 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.596450E+12 | 0.00 | 5562.62 | 0.596450E+12 | -0.0 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.184293E+10 | 0.00 | 379.55 | 0.184293E+10 | -0.0 | 0.00 | 1.00 | 0.00 | 688.22 | 688.22 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.585353E+11 | 0.00 | 743.83 | 0.585353E+11 | 0.00 | 0.00 | 1.00 | 0.00 | 59052.04 | 59052.04 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.223683E+10 | 0.00 | 743.67 | 0.223683E+10 | 0.00 | 0.00 | 1.00 | 01-JAN-00:30 | 0.00 | 01-JAN-00:10 | 835.51 | 01-JAN-22:50 | 835.51 | 09-JAN-04:50 | 0.00 | 14-JAN-08:63 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.294200E+11 | 0.00 | 349.27 | 0.294200E+11 | -0.0 | 0.00 | 1.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:30 | 40662.10 | 18-FEB-17:20 | 40662.10 | 18-FEB-18:00 | 0.00 | 01-FEB-23:20 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 0.356267E+11 | 0.00 | 386.92 | 0.356267E+11 | -0.0 | 0.00 | 1.00 | 01-MAR-17:10 | 0.00 | 01-MAR-00:10 | 44821.70 | 01-MAR-18:12 | 44821.70 | 01-MAR-17:10 | 0.00 | 01-MAR-23:30 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 0.427234E+11 | 0.00 | 369.96 | 0.427234E+11 | -0.0 | 0.00 | 1.00 | 01-APR-16:05 | 0.00 | 01-APR-00:20 | 55784.28 | 01-APR-21:10 | 55784.28 | 01-APR-20:30 | 0.00 | 03-APR-22:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.482360E+11 | 0.00 | 359.52 | 0.482360E+11 | -0.0 | 0.00 | 1.00 | 01-MAY-16:10 | 0.00 | 01-MAY-00:05 | 61064.10 | 01-MAY-17:01 | 61064.10 | 01-MAY-20:10 | 0.00 | 02-MAY-23:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.536336E+11 | 0.00 | 341.12 | 0.536336E+11 | -0.0 | 0.00 | 1.00 | 01-JUN-16:10 | 0.00 | 01-JUN-00:05 | 70078.08 | 01-JUN-22:00 | 70078.08 | 01-JUN-16:20 | 0.00 | 04-JUN-18:40 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.591764E+11 | 0.00 | 348.20 | 0.591764E+11 | 0.00 | 0.00 | 1.00 | 01-JUL-16:10 | 0.00 | 01-JUL-00:20 | 74737.86 | 01-JUL-16:20 | 74737.86 | 01-JUL-16:10 | 0.00 | 06-JUL-20:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.567339E+11 | 0.00 | 349.07 | 0.567339E+11 | -0.0 | 0.00 | 1.00 | 01-AUG-16:10 | 0.00 | 01-AUG-00:05 | 71319.05 | 01-AUG-18:30 | 71319.05 | 01-AUG-17:13 | 0.00 | 08-AUG-18:50 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.510606E+11 | 0.00 | 345.88 | 0.510606E+11 | -0.0 | 0.00 | 1.00 | 01-SEP-16:10 | 0.00 | 01-SEP-00:05 | 66554.97 | 30-SEP-16:10 | 66554.97 | 30-SEP-16:10 | 0.00 | 01-SEP-16:50 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.453604E+11 | 0.00 | 359.59 | 0.453604E+11 | 0.00 | 0.00 | 1.00 | 01-OCT-16:10 | 0.00 | 01-OCT-00:20 | 57428.75 | 31-OCT-16:10 | 57428.75 | 31-OCT-19:20 | 0.00 | 07-OCT-18:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.366880E+11 | 0.00 | 374.44 | 0.366880E+11 | -0.0 | 0.00 | 1.00 | 01-NOV-16:10 | 0.00 | 01-NOV-00:05 | 48032.94 | 30-NOV-17:10 | 48032.94 | 30-NOV-17:10 | 0.00 | 07-NOV-17:10 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.293913E+11 | 0.00 | 386.50 | 0.293913E+11 | -0.0 | 0.00 | 1.00 | 01-DEC-17:10 | 0.00 | 01-DEC-00:10 | 37005.41 | 31-DEC-17:20 | 37005.41 | 31-DEC-17:40 | 0.00 | 02-DEC-22:40 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.490287E+12 | 0.00 | 4714.14 | 0.490287E+12 | -0.0 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.223683E+10 | 0.00 | 341.12 | 0.223683E+10 | -0.0 | 0.00 | 1.00 | 0.00 | 835.51 | 835.51 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.591764E+11 | 0.00 | 743.67 | 0.591764E+11 | 0.00 | 0.00 | 1.00 | 0.00 | 74737.86 | 74737.86 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.118080E+10 | 0.00 | 14.52 | 0.118080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59928.27 | 27-FEB-15:20 | 59928.27 | 27-FEB-15:20 | 0.00 | 0.00 | 0.00 |
March | 17670844.71 | 0.00 | 1.67 | 17670844.71 | 0.00 | 0.00 | 0.00 | 0.00 | 3815.58 | 14-MAR-13:10 | 3815.58 | 14-MAR-13:10 | 0.00 | 0.00 | 0.00 |
April | 0.161152E+11 | 0.00 | 92.62 | 0.161152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 128061.42 | 06-APR-15:55 | 128061.42 | 06-APR-15:55 | 0.00 | 0.00 | 0.00 |
May | 0.587471E+11 | 0.00 | 226.83 | 0.587471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 199364.37 | 19-MAY-18:07 | 199364.37 | 19-MAY-18:07 | 0.00 | 0.00 | 0.00 |
June | 0.154886E+12 | 0.00 | 438.21 | 0.153330E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 282482.82 | 20-JUN-20:00 | 233608.63 | 28-JUN-18:05 | 0.00 | 0.00 | 0.00 |
July | 0.265505E+12 | 0.00 | 593.79 | 0.263821E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 281189.44 | 17-JUL-18:03 | 281189.44 | 17-JUL-18:03 | 0.00 | 0.00 | 0.00 |
August | 0.221511E+12 | 0.00 | 549.00 | 0.221511E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 255136.99 | 07-AUG-18:03 | 255136.99 | 07-AUG-18:03 | 0.00 | 0.00 | 0.00 |
September | 0.124345E+12 | 0.00 | 364.67 | 0.120704E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 279286.33 | 07-SEP-18:04 | 246698.47 | 02-SEP-17:02 | 0.00 | 0.00 | 0.00 |
October | 0.247539E+11 | 0.00 | 135.69 | 0.247539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 167408.73 | 18-OCT-15:03 | 167408.73 | 18-OCT-15:03 | 0.00 | 0.00 | 0.00 |
November | 0.167984E+10 | 0.00 | 25.33 | 0.167984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41891.42 | 17-NOV-18:20 | 41891.42 | 17-NOV-18:20 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.868743E+12 | 0.00 | 2442.34 | 0.861861E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.265505E+12 | 0.00 | 593.79 | 0.263821E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 282482.82 | 281189.44 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 66859211.40 | 0.00 | 8.50 | 66859211.40 | 0.00 | 0.00 | 0.00 | 0.00 | 6688.28 | 27-FEB-14:00 | 6688.28 | 27-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 1181470.97 | 0.00 | 0.83 | 1181470.97 | 0.00 | 0.00 | 0.00 | 0.00 | 652.55 | 14-MAR-13:00 | 652.55 | 14-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.100375E+10 | 0.00 | 54.50 | 0.100375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13445.87 | 07-APR-13:00 | 13445.87 | 07-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.373266E+10 | 0.00 | 150.17 | 0.373266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16748.25 | 20-MAY-15:02 | 16748.25 | 20-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.964258E+10 | 0.00 | 307.17 | 0.950698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20298.04 | 20-JUN-18:02 | 17823.33 | 29-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.168625E+11 | 0.00 | 444.17 | 0.163872E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21351.77 | 18-JUL-19:55 | 19241.03 | 17-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.135751E+11 | 0.00 | 406.83 | 0.135751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18704.16 | 05-AUG-15:02 | 18704.16 | 05-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.799166E+10 | 0.00 | 260.00 | 0.765167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24963.93 | 07-SEP-15:02 | 18604.84 | 02-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.154185E+10 | 0.00 | 87.33 | 0.154185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15094.57 | 18-OCT-15:01 | 15094.57 | 18-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 95107362.99 | 0.00 | 15.50 | 95107362.99 | 0.00 | 0.00 | 0.00 | 0.00 | 4584.43 | 17-NOV-17:00 | 4584.43 | 17-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.545133E+11 | 0.00 | 1735.00 | 0.535624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.168625E+11 | 0.00 | 444.17 | 0.163872E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24963.93 | 19241.03 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 38569846.48 | 0.00 | 8.09 | 35963137.43 | 0.00 | 0.00 | 0.00 | 0.00 | 15602.46 | 21-JAN-16:01 | 15602.46 | 21-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.545721E+09 | 0.00 | 80.88 | 0.539698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16197.97 | 27-FEB-16:01 | 16197.97 | 27-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.843069E+09 | 0.00 | 123.73 | 0.837400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15778.79 | 22-MAR-15:01 | 15778.79 | 22-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.206071E+10 | 0.00 | 283.76 | 0.191382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16673.34 | 07-APR-15:01 | 16673.34 | 07-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.390404E+10 | 0.00 | 452.09 | 0.316963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17000.68 | 31-MAY-18:01 | 17000.68 | 31-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.702393E+10 | 0.00 | 631.74 | 0.505010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16667.03 | 10-JUN-18:02 | 16667.03 | 10-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.985807E+10 | 0.00 | 701.72 | 0.682029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16937.70 | 19-JUL-08:61 | 16457.10 | 07-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.859106E+10 | 0.00 | 683.85 | 0.623608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17438.81 | 11-AUG-15:01 | 17438.81 | 11-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.549482E+10 | 0.00 | 541.58 | 0.386796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16313.88 | 30-SEP-18:01 | 16313.88 | 30-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.206531E+10 | 0.00 | 337.98 | 0.185518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17176.89 | 18-OCT-15:01 | 17176.89 | 18-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.431319E+09 | 0.00 | 98.74 | 0.394971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15778.91 | 06-NOV-16:01 | 15778.91 | 06-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 45549815.71 | 0.00 | 10.02 | 41566298.05 | 0.00 | 0.00 | 0.00 | 0.00 | 15778.93 | 07-DEC-16:01 | 15778.93 | 07-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.409022E+11 | 0.00 | 3954.18 | 0.307627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 38569846.48 | 0.00 | 8.09 | 35963137.43 | 0.00 | 0.00 | 0.00 | 0.00 | 15602.46 | 15602.46 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.985807E+10 | 0.00 | 701.72 | 0.682029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17438.81 | 17438.81 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 11089760.90 | 0.00 | 1.72 | 10295671.97 | 0.00 | 0.00 | 0.00 | 0.00 | 4001.86 | 13-JAN-19:03 | 3671.48 | 13-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.135686E+09 | 0.00 | 24.22 | 0.133533E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15853.44 | 26-FEB-17:41 | 15853.44 | 26-FEB-17:41 | 0.00 | 0.00 | 0.00 |
March | 0.322748E+09 | 0.00 | 50.72 | 0.321454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15046.11 | 02-MAR-16:01 | 15046.11 | 02-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.920392E+09 | 0.00 | 180.77 | 0.845479E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17225.31 | 24-APR-19:31 | 17225.31 | 24-APR-19:31 | 0.00 | 0.00 | 0.00 |
May | 0.244263E+10 | 0.00 | 329.85 | 0.185256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19003.47 | 31-MAY-16:11 | 19003.47 | 31-MAY-16:11 | 0.00 | 0.00 | 0.00 |
June | 0.535226E+10 | 0.00 | 504.49 | 0.372918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17183.73 | 07-JUN-19:41 | 17183.73 | 07-JUN-19:41 | 0.00 | 0.00 | 0.00 |
July | 0.783944E+10 | 0.00 | 571.28 | 0.537728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17769.40 | 19-JUL-08:51 | 17081.24 | 08-JUL-20:41 | 0.00 | 0.00 | 0.00 |
August | 0.597897E+10 | 0.00 | 539.39 | 0.411387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17198.61 | 11-AUG-08:51 | 17198.61 | 11-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.324238E+10 | 0.00 | 378.85 | 0.208538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16990.56 | 06-SEP-21:51 | 16422.40 | 15-SEP-18:21 | 0.00 | 0.00 | 0.00 |
October | 0.645347E+09 | 0.00 | 172.49 | 0.577821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16824.60 | 02-OCT-16:41 | 16824.60 | 02-OCT-16:41 | 0.00 | 0.00 | 0.00 |
November | 87067495.83 | 0.00 | 20.33 | 78879233.96 | 0.00 | 0.00 | 0.00 | 0.00 | 14766.62 | 06-NOV-16:01 | 14766.62 | 06-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 16987752.85 | 0.00 | 2.37 | 15498583.30 | 0.00 | 0.00 | 0.00 | 0.00 | 9841.16 | 06-DEC-16:01 | 9841.16 | 06-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269950E+11 | 0.00 | 2776.49 | 0.191412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 11089760.90 | 0.00 | 1.72 | 10295671.97 | 0.00 | 0.00 | 0.00 | 0.00 | 4001.86 | 3671.48 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.783944E+10 | 0.00 | 571.28 | 0.537728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19003.47 | 19003.47 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.171170E+10 | 0.00 | 30.92 | 0.171170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44069.03 | 01-JAN-13:30 | 44069.03 | 01-JAN-13:30 | 0.00 | 0.00 | 0.00 |
February | 0.860813E+10 | 0.00 | 117.42 | 0.860813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55663.85 | 27-FEB-13:30 | 55663.85 | 27-FEB-13:30 | 0.00 | 0.00 | 0.00 |
March | 0.111337E+11 | 0.00 | 194.11 | 0.111337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53887.05 | 01-MAR-13:30 | 53887.05 | 01-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.157491E+11 | 0.00 | 316.39 | 0.156626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47478.22 | 06-APR-13:40 | 47478.22 | 06-APR-13:40 | 0.00 | 0.00 | 0.00 |
May | 0.186344E+11 | 0.00 | 424.32 | 0.141638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41981.15 | 20-MAY-12:30 | 38629.89 | 13-MAY-13:30 | 0.00 | 0.00 | 0.00 |
June | 0.346473E+11 | 0.00 | 633.61 | 0.193680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39594.38 | 21-JUN-13:10 | 29108.33 | 24-JUN-13:30 | 0.00 | 0.00 | 0.00 |
July | 0.502243E+11 | 0.00 | 725.75 | 0.283873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48141.80 | 17-JUL-13:10 | 43811.48 | 17-JUL-13:30 | 0.00 | 0.00 | 0.00 |
August | 0.528963E+11 | 0.00 | 722.67 | 0.331645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55043.30 | 30-AUG-13:30 | 51596.80 | 25-AUG-12:30 | 0.00 | 0.00 | 0.00 |
September | 0.432250E+11 | 0.00 | 604.44 | 0.305352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60226.79 | 03-SEP-13:00 | 51519.49 | 02-SEP-15:13 | 0.00 | 0.00 | 0.00 |
October | 0.301767E+11 | 0.00 | 497.81 | 0.298469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64440.30 | 18-OCT-13:00 | 64440.30 | 18-OCT-13:00 | 0.00 | 0.00 | 0.00 |
November | 0.160596E+11 | 0.00 | 309.87 | 0.160596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53628.01 | 03-NOV-13:30 | 53628.01 | 03-NOV-13:30 | 0.00 | 0.00 | 0.00 |
December | 0.950476E+09 | 0.00 | 28.80 | 0.950476E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24005.31 | 12-DEC-14:30 | 24005.31 | 12-DEC-14:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.284017E+12 | 0.00 | 4606.10 | 0.209592E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.950476E+09 | 0.00 | 28.80 | 0.950476E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24005.31 | 24005.31 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.528963E+11 | 0.00 | 725.75 | 0.331645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64440.30 | 64440.30 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.201285E+09 | 0.00 | 18.47 | 0.201002E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66267.48 | 15-JAN-09:01 | 66267.48 | 15-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.923127E+09 | 0.00 | 63.42 | 0.923127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69965.04 | 27-FEB-16:01 | 69965.04 | 27-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.256485E+10 | 0.00 | 150.98 | 0.256485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69866.14 | 29-MAR-18:01 | 69866.14 | 29-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.969320E+10 | 0.00 | 333.93 | 0.904619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78564.19 | 07-APR-15:01 | 78564.19 | 07-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.200696E+11 | 0.00 | 407.08 | 0.175451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80089.97 | 31-MAY-15:01 | 80089.97 | 31-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.375177E+11 | 0.00 | 475.04 | 0.308624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81442.43 | 21-JUN-21:51 | 80105.58 | 05-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.474721E+11 | 0.00 | 520.98 | 0.368540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85975.39 | 26-JUL-08:61 | 85975.39 | 26-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.378458E+11 | 0.00 | 489.81 | 0.305515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83017.48 | 07-AUG-08:21 | 83017.48 | 07-AUG-08:21 | 0.00 | 0.00 | 0.00 |
September | 0.240020E+11 | 0.00 | 431.22 | 0.181737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83354.05 | 07-SEP-15:02 | 79787.87 | 03-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.964866E+10 | 0.00 | 365.41 | 0.886699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78416.60 | 18-OCT-15:01 | 78416.60 | 18-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.255121E+10 | 0.00 | 149.66 | 0.253137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69928.98 | 05-NOV-08:62 | 69928.98 | 05-NOV-08:62 | 0.00 | 0.00 | 0.00 |
December | 0.330955E+09 | 0.00 | 29.74 | 0.330955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67899.54 | 10-DEC-09:02 | 67899.54 | 10-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192821E+12 | 0.00 | 3435.75 | 0.158451E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.201285E+09 | 0.00 | 18.47 | 0.201002E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66267.48 | 66267.48 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.474721E+11 | 0.00 | 520.98 | 0.368540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85975.39 | 85975.39 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 60353161.10 | 0.00 | 16.23 | 54298081.14 | 0.00 | 0.00 | 0.00 | 0.00 | 9371.84 | 14-JAN-16:02 | 9371.84 | 14-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.535095E+09 | 0.00 | 93.08 | 0.517241E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14448.64 | 27-FEB-16:01 | 14448.64 | 27-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.882666E+09 | 0.00 | 162.18 | 0.872169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14074.32 | 22-MAR-15:01 | 14074.32 | 22-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.221916E+10 | 0.00 | 320.57 | 0.195448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14871.18 | 07-APR-15:01 | 14871.18 | 07-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.356499E+10 | 0.00 | 477.86 | 0.279710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15164.00 | 31-MAY-18:01 | 15164.00 | 31-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.756609E+10 | 0.00 | 655.44 | 0.553824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14863.18 | 10-JUN-18:02 | 14863.18 | 10-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.105946E+11 | 0.00 | 723.35 | 0.768439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14843.85 | 19-JUL-08:61 | 14676.51 | 07-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.924606E+10 | 0.00 | 710.14 | 0.698910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15553.08 | 11-AUG-15:01 | 15553.08 | 11-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.548901E+10 | 0.00 | 558.01 | 0.389892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14549.69 | 30-SEP-18:01 | 14549.69 | 30-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.205208E+10 | 0.00 | 357.03 | 0.176471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15321.96 | 18-OCT-15:01 | 15321.96 | 18-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.396287E+09 | 0.00 | 99.20 | 0.336044E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14072.60 | 02-NOV-15:01 | 14072.60 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 56619375.71 | 0.00 | 15.93 | 51821876.29 | 0.00 | 0.00 | 0.00 | 0.00 | 10060.49 | 10-DEC-16:01 | 10060.49 | 10-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.426631E+11 | 0.00 | 4189.02 | 0.324585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 56619375.71 | 0.00 | 15.93 | 51821876.29 | 0.00 | 0.00 | 0.00 | 0.00 | 9371.84 | 9371.84 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.105946E+11 | 0.00 | 723.35 | 0.768439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15553.08 | 15553.08 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 12304340.26 | 0.00 | 2.87 | 11729573.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4664.60 | 17-JAN-09:03 | 4664.60 | 17-JAN-09:03 | 0.00 | 0.00 | 0.00 |
February | 0.117544E+09 | 0.00 | 22.13 | 0.108844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13371.39 | 26-FEB-09:01 | 13371.39 | 26-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.251649E+09 | 0.00 | 57.89 | 0.243991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12821.01 | 27-MAR-15:01 | 12821.01 | 27-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.114964E+10 | 0.00 | 215.67 | 0.993700E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14130.89 | 07-APR-15:01 | 14130.89 | 07-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.235883E+10 | 0.00 | 366.97 | 0.176323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15189.27 | 31-MAY-08:51 | 15189.27 | 31-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.593560E+10 | 0.00 | 537.45 | 0.424232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17632.75 | 22-JUN-08:32 | 16512.83 | 21-JUN-08:32 | 0.00 | 0.00 | 0.00 |
July | 0.844115E+10 | 0.00 | 594.87 | 0.599903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17651.02 | 16-JUL-08:32 | 16988.42 | 17-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.665791E+10 | 0.00 | 576.53 | 0.474108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16978.40 | 11-AUG-08:51 | 16978.40 | 11-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.328789E+10 | 0.00 | 423.39 | 0.213587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14724.38 | 06-SEP-21:51 | 14446.08 | 02-SEP-08:32 | 0.00 | 0.00 | 0.00 |
October | 0.626696E+09 | 0.00 | 180.16 | 0.524462E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14560.19 | 18-OCT-15:01 | 14560.19 | 18-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 49288661.88 | 0.00 | 18.28 | 34534037.56 | 0.00 | 0.00 | 0.00 | 0.00 | 8950.03 | 06-NOV-09:01 | 8950.03 | 06-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 14034339.81 | 0.00 | 1.86 | 13271225.44 | 0.00 | 0.00 | 0.00 | 0.00 | 4653.61 | 20-DEC-09:03 | 3593.42 | 06-DEC-16:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.289025E+11 | 0.00 | 2998.06 | 0.208121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 12304340.26 | 0.00 | 1.86 | 11729573.63 | 0.00 | 0.00 | 0.00 | 0.00 | 4653.61 | 3593.42 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.844115E+10 | 0.00 | 594.87 | 0.599903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17651.02 | 16988.42 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 6781550.23 | 0.00 | 4.49 | 5901989.19 | 0.00 | 0.00 | 0.00 | 0.00 | 3999.20 | 21-JAN-16:01 | 3999.20 | 21-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.123777E+09 | 0.00 | 62.32 | 0.121737E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4270.06 | 27-FEB-16:01 | 4270.06 | 27-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.194383E+09 | 0.00 | 89.93 | 0.193287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4159.71 | 22-MAR-15:01 | 4159.71 | 22-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.505153E+09 | 0.00 | 237.42 | 0.468387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4395.31 | 07-APR-15:01 | 4395.31 | 07-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.984411E+09 | 0.00 | 400.06 | 0.812020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4481.18 | 31-MAY-18:01 | 4481.18 | 31-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.174933E+10 | 0.00 | 588.13 | 0.127390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4392.85 | 10-JUN-18:02 | 4392.85 | 10-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.247318E+10 | 0.00 | 687.90 | 0.172237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4627.63 | 19-JUL-08:61 | 4337.00 | 07-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.211030E+10 | 0.00 | 660.57 | 0.153933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4596.67 | 11-AUG-15:01 | 4596.67 | 11-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.128517E+10 | 0.00 | 477.99 | 0.907062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4299.78 | 30-SEP-18:01 | 4299.78 | 30-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.439763E+09 | 0.00 | 241.87 | 0.397041E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4528.04 | 18-OCT-15:01 | 4528.04 | 18-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 89230095.38 | 0.00 | 58.25 | 79587930.07 | 0.00 | 0.00 | 0.00 | 0.00 | 4159.66 | 06-NOV-16:01 | 4159.66 | 06-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 8309502.28 | 0.00 | 7.26 | 6720181.69 | 0.00 | 0.00 | 0.00 | 0.00 | 4158.13 | 10-DEC-16:01 | 4158.13 | 10-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.996978E+10 | 0.00 | 3516.19 | 0.752735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6781550.23 | 0.00 | 4.49 | 5901989.19 | 0.00 | 0.00 | 0.00 | 0.00 | 3999.20 | 3999.20 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.247318E+10 | 0.00 | 687.90 | 0.172237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4627.63 | 4596.67 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1645712.78 | 0.00 | 1.15 | 1343398.56 | 0.00 | 0.00 | 0.00 | 0.00 | 1044.21 | 01-JAN-16:03 | 1010.00 | 15-JAN-16:03 | 0.00 | 0.00 | 0.00 |
February | 28669679.24 | 0.00 | 19.10 | 27861978.38 | 0.00 | 0.00 | 0.00 | 0.00 | 4228.99 | 26-FEB-17:41 | 4228.99 | 26-FEB-17:41 | 0.00 | 0.00 | 0.00 |
March | 69479699.39 | 0.00 | 39.54 | 68825095.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3953.07 | 02-MAR-16:01 | 3953.07 | 02-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.213792E+09 | 0.00 | 146.80 | 0.196995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4925.92 | 25-APR-19:02 | 4925.92 | 25-APR-19:02 | 0.00 | 0.00 | 0.00 |
May | 0.619886E+09 | 0.00 | 297.83 | 0.474019E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4992.03 | 31-MAY-16:11 | 4992.03 | 31-MAY-16:11 | 0.00 | 0.00 | 0.00 |
June | 0.135427E+10 | 0.00 | 479.58 | 0.945123E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4576.79 | 21-JUN-21:51 | 4535.99 | 26-JUN-18:41 | 0.00 | 0.00 | 0.00 |
July | 0.200016E+10 | 0.00 | 567.58 | 0.137850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4708.61 | 19-JUL-08:51 | 4577.02 | 08-JUL-20:41 | 0.00 | 0.00 | 0.00 |
August | 0.147629E+10 | 0.00 | 519.05 | 0.102241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4473.56 | 11-AUG-08:51 | 4473.56 | 11-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.738480E+09 | 0.00 | 331.64 | 0.474138E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4526.80 | 06-SEP-21:51 | 4385.16 | 15-SEP-18:21 | 0.00 | 0.00 | 0.00 |
October | 0.111742E+09 | 0.00 | 98.48 | 98764486.84 | 0.00 | 0.00 | 0.00 | 0.00 | 4405.33 | 02-OCT-16:41 | 4405.33 | 02-OCT-16:41 | 0.00 | 0.00 | 0.00 |
November | 13465643.04 | 0.00 | 13.26 | 11168219.20 | 0.00 | 0.00 | 0.00 | 0.00 | 2789.04 | 04-NOV-15:01 | 2789.04 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 2129070.86 | 0.00 | 1.33 | 1789206.83 | 0.00 | 0.00 | 0.00 | 0.00 | 2537.43 | 06-DEC-16:01 | 2537.43 | 06-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.663000E+10 | 0.00 | 2515.34 | 0.470094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1645712.78 | 0.00 | 1.15 | 1343398.56 | 0.00 | 0.00 | 0.00 | 0.00 | 1044.21 | 1010.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.200016E+10 | 0.00 | 567.58 | 0.137850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4992.03 | 4992.03 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.127229E+10 | 0.00 | 116.42 | 0.119429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20125.42 | 03-JAN-16:01 | 20125.42 | 03-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.274022E+10 | 0.00 | 207.89 | 0.268339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20679.48 | 27-FEB-16:01 | 20679.48 | 27-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.309710E+10 | 0.00 | 238.02 | 0.306555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20138.86 | 14-MAR-18:01 | 20138.86 | 14-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.391787E+10 | 0.00 | 339.07 | 0.361397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21284.83 | 07-APR-15:01 | 21284.83 | 07-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.501681E+10 | 0.00 | 459.18 | 0.400880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21578.13 | 29-MAY-18:01 | 21578.13 | 29-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.841071E+10 | 0.00 | 616.37 | 0.575608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21259.98 | 10-JUN-18:02 | 21259.98 | 10-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.123112E+11 | 0.00 | 693.62 | 0.837665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22101.26 | 19-JUL-08:61 | 21547.00 | 30-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.122872E+11 | 0.00 | 684.36 | 0.914312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21602.22 | 11-AUG-08:61 | 21602.22 | 11-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.958768E+10 | 0.00 | 574.40 | 0.730120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20814.59 | 30-SEP-18:01 | 20814.59 | 30-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.626242E+10 | 0.00 | 474.89 | 0.575039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21923.92 | 18-OCT-15:01 | 21923.92 | 18-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.329726E+10 | 0.00 | 290.68 | 0.311506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20369.19 | 17-NOV-16:01 | 20369.19 | 17-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.127729E+10 | 0.00 | 124.94 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20138.19 | 01-DEC-16:01 | 20138.19 | 01-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.694781E+11 | 0.00 | 4819.84 | 0.552288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.127229E+10 | 0.00 | 116.42 | 0.119429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20125.42 | 20125.42 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.123112E+11 | 0.00 | 693.62 | 0.914312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22101.26 | 21923.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 796.96 | 569.00 | 227.96 | 754.34 | 839.77 | 0.00 | 0.00 | 0.00 |
February | 1001.24 | 716.20 | 285.04 | 1041.01 | 626.55 | 0.00 | 0.00 | 0.00 |
March | 895.56 | 497.89 | 397.67 | 931.96 | 550.67 | 0.00 | 0.00 | 0.00 |
April | 737.03 | 356.67 | 380.36 | 806.38 | 395.06 | 0.00 | 0.00 | 0.00 |
May | 653.41 | 220.80 | 432.60 | 737.87 | 302.53 | 0.00 | 0.00 | 0.00 |
June | 640.43 | 184.57 | 455.86 | 823.51 | 192.84 | 0.00 | 0.00 | 0.00 |
July | 692.31 | 254.77 | 437.54 | 984.73 | 150.36 | 0.00 | 0.00 | 0.00 |
August | 813.11 | 404.24 | 408.87 | 1115.49 | 173.10 | 0.00 | 0.00 | 0.00 |
September | 913.28 | 559.05 | 354.24 | 1159.17 | 258.65 | 0.00 | 0.00 | 0.00 |
October | 964.04 | 668.90 | 295.15 | 1120.16 | 382.36 | 0.00 | 0.00 | 0.00 |
November | 870.93 | 630.50 | 240.43 | 921.76 | 515.58 | 0.00 | 0.00 | 0.00 |
December | 757.49 | 547.07 | 210.42 | 735.31 | 716.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 809.98 | 465.81 | 344.18 | 926.71 | 424.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 640.43 | 184.57 | 210.42 | 735.31 | 150.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1001.24 | 716.20 | 455.86 | 1159.17 | 839.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2244.18 | 1602.26 | 641.92 | 2103.03 | 2408.80 | 0.00 | 0.00 | 0.00 |
February | 2819.44 | 2016.78 | 802.66 | 2899.71 | 1826.43 | 0.00 | 0.00 | 0.00 |
March | 2521.84 | 1402.02 | 1119.82 | 2594.49 | 1620.10 | 0.00 | 0.00 | 0.00 |
April | 2075.42 | 1004.36 | 1071.07 | 2239.50 | 1184.14 | 0.00 | 0.00 | 0.00 |
May | 1839.95 | 621.77 | 1218.17 | 2040.48 | 916.92 | 0.00 | 0.00 | 0.00 |
June | 1803.40 | 519.73 | 1283.68 | 2280.78 | 594.49 | 0.00 | 0.00 | 0.00 |
July | 1949.49 | 717.40 | 1232.09 | 2743.69 | 457.53 | 0.00 | 0.00 | 0.00 |
August | 2289.66 | 1138.31 | 1151.35 | 3113.83 | 527.63 | 0.00 | 0.00 | 0.00 |
September | 2571.75 | 1574.24 | 997.51 | 3234.58 | 787.57 | 0.00 | 0.00 | 0.00 |
October | 2714.68 | 1883.57 | 831.11 | 3121.35 | 1156.21 | 0.00 | 0.00 | 0.00 |
November | 2452.48 | 1775.44 | 677.04 | 2562.60 | 1527.64 | 0.00 | 0.00 | 0.00 |
December | 2133.05 | 1540.51 | 592.54 | 2046.61 | 2068.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2280.86 | 1311.68 | 969.18 | 2579.13 | 1254.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1803.40 | 519.73 | 592.54 | 2040.48 | 457.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2819.44 | 2016.78 | 1283.68 | 3234.58 | 2408.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2915.31 | 2081.43 | 833.89 | 2765.74 | 3264.02 | 0.00 | 0.00 | 0.00 |
February | 3662.61 | 2619.91 | 1042.70 | 3817.85 | 2476.85 | 0.00 | 0.00 | 0.00 |
March | 3276.01 | 1821.31 | 1454.71 | 3413.31 | 2210.58 | 0.00 | 0.00 | 0.00 |
April | 2696.09 | 1304.72 | 1391.37 | 2948.31 | 1629.86 | 0.00 | 0.00 | 0.00 |
May | 2390.19 | 807.72 | 1582.48 | 2683.80 | 1264.48 | 0.00 | 0.00 | 0.00 |
June | 2342.72 | 675.15 | 1667.57 | 3008.37 | 807.88 | 0.00 | 0.00 | 0.00 |
July | 2532.50 | 931.95 | 1600.55 | 3627.00 | 610.31 | 0.00 | 0.00 | 0.00 |
August | 2974.39 | 1478.73 | 1495.67 | 4112.10 | 703.36 | 0.00 | 0.00 | 0.00 |
September | 3340.85 | 2045.03 | 1295.82 | 4261.90 | 1062.53 | 0.00 | 0.00 | 0.00 |
October | 3526.52 | 2446.86 | 1079.66 | 4104.00 | 1573.12 | 0.00 | 0.00 | 0.00 |
November | 3185.91 | 2306.40 | 879.51 | 3361.22 | 2092.42 | 0.00 | 0.00 | 0.00 |
December | 2770.95 | 2001.21 | 769.74 | 2681.68 | 2830.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2962.97 | 1703.95 | 1259.02 | 3395.37 | 1707.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2342.72 | 675.15 | 769.74 | 2681.68 | 610.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3662.61 | 2619.91 | 1667.57 | 4261.90 | 3264.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 157.57 | 112.50 | 45.07 | 150.02 | 169.95 | 0.00 | 0.00 | 0.00 |
February | 197.96 | 141.61 | 56.36 | 207.09 | 125.75 | 0.00 | 0.00 | 0.00 |
March | 177.07 | 98.44 | 78.63 | 184.65 | 110.68 | 0.00 | 0.00 | 0.00 |
April | 145.72 | 70.52 | 75.20 | 159.85 | 79.09 | 0.00 | 0.00 | 0.00 |
May | 129.19 | 43.66 | 85.53 | 145.57 | 60.53 | 0.00 | 0.00 | 0.00 |
June | 126.62 | 36.49 | 90.13 | 164.14 | 36.52 | 0.00 | 0.00 | 0.00 |
July | 136.88 | 50.37 | 86.51 | 198.36 | 25.97 | 0.00 | 0.00 | 0.00 |
August | 160.77 | 79.92 | 80.84 | 224.14 | 30.10 | 0.00 | 0.00 | 0.00 |
September | 180.57 | 110.53 | 70.04 | 231.48 | 48.23 | 0.00 | 0.00 | 0.00 |
October | 190.61 | 132.25 | 58.36 | 223.22 | 74.43 | 0.00 | 0.00 | 0.00 |
November | 172.20 | 124.66 | 47.54 | 183.86 | 102.56 | 0.00 | 0.00 | 0.00 |
December | 149.77 | 108.16 | 41.60 | 146.68 | 143.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.15 | 92.10 | 68.05 | 184.74 | 83.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 126.62 | 36.49 | 41.60 | 145.57 | 25.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.96 | 141.61 | 90.13 | 231.48 | 169.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.19 | 35.31 | 51.88 | 43.47 | 358.10 | 0.00 | 0.00 | 0.00 |
February | 149.46 | 74.06 | 75.39 | 113.36 | 259.29 | 0.00 | 0.00 | 0.00 |
March | 190.42 | 70.19 | 120.23 | 152.87 | 211.36 | 0.00 | 0.00 | 0.00 |
April | 247.90 | 109.66 | 138.25 | 248.53 | 144.99 | 0.00 | 0.00 | 0.00 |
May | 306.60 | 140.11 | 166.49 | 340.21 | 109.84 | 0.00 | 0.00 | 0.00 |
June | 332.61 | 152.56 | 180.06 | 416.07 | 66.16 | 0.00 | 0.00 | 0.00 |
July | 340.86 | 172.11 | 168.75 | 463.39 | 48.34 | 0.00 | 0.00 | 0.00 |
August | 289.78 | 142.08 | 147.70 | 382.38 | 55.49 | 0.00 | 0.00 | 0.00 |
September | 233.45 | 118.03 | 115.42 | 280.49 | 91.06 | 0.00 | 0.00 | 0.00 |
October | 166.93 | 83.02 | 83.91 | 165.56 | 146.10 | 0.00 | 0.00 | 0.00 |
November | 118.15 | 58.71 | 59.44 | 93.09 | 214.28 | 0.00 | 0.00 | 0.00 |
December | 78.96 | 33.21 | 45.75 | 41.48 | 302.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 212.14 | 99.17 | 112.96 | 229.01 | 166.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 78.96 | 33.21 | 45.75 | 41.48 | 48.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 340.86 | 172.11 | 180.06 | 463.39 | 358.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.35 | 0.00 | 22.35 | 0.58 | 199.15 | 0.00 | 0.00 | 0.00 |
February | 31.55 | 0.00 | 31.55 | 5.47 | 145.73 | 0.00 | 0.00 | 0.00 |
March | 51.26 | 0.00 | 51.26 | 19.01 | 115.68 | 0.00 | 0.00 | 0.00 |
April | 58.78 | 0.56 | 58.22 | 33.08 | 77.77 | 0.00 | 0.00 | 0.00 |
May | 76.63 | 4.41 | 72.22 | 60.39 | 57.09 | 0.00 | 0.00 | 0.00 |
June | 89.62 | 10.51 | 79.12 | 97.55 | 33.34 | 0.00 | 0.00 | 0.00 |
July | 81.77 | 7.76 | 74.01 | 106.79 | 25.32 | 0.00 | 0.00 | 0.00 |
August | 66.04 | 2.28 | 63.76 | 78.77 | 29.53 | 0.00 | 0.00 | 0.00 |
September | 49.08 | 0.07 | 49.01 | 46.45 | 49.91 | 0.00 | 0.00 | 0.00 |
October | 35.74 | 0.00 | 35.74 | 18.94 | 79.18 | 0.00 | 0.00 | 0.00 |
November | 24.30 | 0.00 | 24.30 | 4.75 | 119.20 | 0.00 | 0.00 | 0.00 |
December | 18.74 | 0.00 | 18.74 | 0.52 | 168.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.59 | 2.14 | 48.45 | 39.57 | 91.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.74 | 0.00 | 18.74 | 0.52 | 25.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.62 | 10.51 | 79.12 | 106.79 | 199.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.19 | 35.31 | 51.88 | 45.92 | 354.98 | 0.00 | 0.00 | 0.00 |
February | 149.46 | 74.06 | 75.39 | 118.26 | 255.92 | 0.00 | 0.00 | 0.00 |
March | 190.42 | 70.19 | 120.23 | 158.00 | 208.82 | 0.00 | 0.00 | 0.00 |
April | 247.90 | 109.66 | 138.25 | 250.93 | 144.41 | 0.00 | 0.00 | 0.00 |
May | 306.60 | 140.11 | 166.49 | 339.89 | 111.17 | 0.00 | 0.00 | 0.00 |
June | 332.61 | 152.56 | 180.06 | 413.21 | 68.44 | 0.00 | 0.00 | 0.00 |
July | 340.86 | 172.11 | 168.75 | 461.67 | 50.77 | 0.00 | 0.00 | 0.00 |
August | 289.78 | 142.08 | 147.70 | 381.74 | 57.66 | 0.00 | 0.00 | 0.00 |
September | 233.45 | 118.03 | 115.42 | 282.84 | 91.66 | 0.00 | 0.00 | 0.00 |
October | 166.93 | 83.02 | 83.91 | 170.16 | 144.04 | 0.00 | 0.00 | 0.00 |
November | 118.15 | 58.71 | 59.44 | 97.52 | 210.57 | 0.00 | 0.00 | 0.00 |
December | 78.96 | 33.21 | 45.75 | 44.36 | 299.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 212.14 | 99.17 | 112.96 | 230.96 | 166.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 78.96 | 33.21 | 45.75 | 44.36 | 50.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 340.86 | 172.11 | 180.06 | 461.67 | 354.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 126.03 | 89.98 | 36.05 | 118.31 | 137.53 | 0.00 | 0.00 | 0.00 |
February | 158.34 | 113.26 | 45.08 | 160.23 | 108.74 | 0.00 | 0.00 | 0.00 |
March | 141.63 | 78.74 | 62.89 | 138.57 | 107.85 | 0.00 | 0.00 | 0.00 |
April | 116.56 | 56.40 | 60.15 | 118.24 | 83.94 | 0.00 | 0.00 | 0.00 |
May | 103.33 | 34.92 | 68.41 | 105.96 | 66.25 | 0.00 | 0.00 | 0.00 |
June | 101.28 | 29.19 | 72.09 | 118.96 | 44.81 | 0.00 | 0.00 | 0.00 |
July | 109.48 | 40.29 | 69.19 | 146.38 | 34.96 | 0.00 | 0.00 | 0.00 |
August | 128.59 | 63.93 | 64.66 | 167.53 | 40.07 | 0.00 | 0.00 | 0.00 |
September | 144.43 | 88.41 | 56.02 | 174.01 | 57.91 | 0.00 | 0.00 | 0.00 |
October | 152.46 | 105.78 | 46.68 | 167.11 | 81.97 | 0.00 | 0.00 | 0.00 |
November | 137.73 | 99.71 | 38.02 | 136.59 | 103.52 | 0.00 | 0.00 | 0.00 |
December | 119.79 | 86.51 | 33.28 | 111.18 | 126.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.09 | 73.66 | 54.43 | 138.43 | 82.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.28 | 29.19 | 33.28 | 105.96 | 34.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 158.34 | 113.26 | 72.09 | 174.01 | 137.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.88 | 0.00 | 17.88 | 0.30 | 165.42 | 0.00 | 0.00 | 0.00 |
February | 25.25 | 0.00 | 25.25 | 3.97 | 120.32 | 0.00 | 0.00 | 0.00 |
March | 41.01 | 0.00 | 41.01 | 14.66 | 95.00 | 0.00 | 0.00 | 0.00 |
April | 47.03 | 0.45 | 46.58 | 27.53 | 62.98 | 0.00 | 0.00 | 0.00 |
May | 61.31 | 3.53 | 57.78 | 50.75 | 45.59 | 0.00 | 0.00 | 0.00 |
June | 71.71 | 8.41 | 63.30 | 82.10 | 25.58 | 0.00 | 0.00 | 0.00 |
July | 65.42 | 6.21 | 59.21 | 89.92 | 18.57 | 0.00 | 0.00 | 0.00 |
August | 52.84 | 1.82 | 51.02 | 67.00 | 22.08 | 0.00 | 0.00 | 0.00 |
September | 39.27 | 0.05 | 39.21 | 39.31 | 38.95 | 0.00 | 0.00 | 0.00 |
October | 28.60 | 0.00 | 28.60 | 15.26 | 64.16 | 0.00 | 0.00 | 0.00 |
November | 19.44 | 0.00 | 19.44 | 3.46 | 99.11 | 0.00 | 0.00 | 0.00 |
December | 14.99 | 0.00 | 14.99 | 0.25 | 140.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.48 | 1.71 | 38.76 | 33.06 | 74.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.99 | 0.00 | 14.99 | 0.25 | 18.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.71 | 8.41 | 63.30 | 89.92 | 165.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.53 | 44.55 | 51.97 | 48.96 | 347.93 | 0.00 | 0.00 | 0.00 |
February | 151.21 | 75.59 | 75.63 | 111.30 | 252.78 | 0.00 | 0.00 | 0.00 |
March | 202.62 | 84.31 | 118.31 | 164.43 | 204.94 | 0.00 | 0.00 | 0.00 |
April | 257.88 | 128.11 | 129.77 | 256.02 | 138.88 | 0.00 | 0.00 | 0.00 |
May | 284.29 | 126.68 | 157.60 | 306.17 | 105.21 | 0.00 | 0.00 | 0.00 |
June | 367.43 | 189.04 | 178.39 | 458.07 | 60.66 | 0.00 | 0.00 | 0.00 |
July | 385.68 | 218.03 | 167.65 | 519.95 | 44.25 | 0.00 | 0.00 | 0.00 |
August | 336.19 | 187.55 | 148.65 | 440.21 | 51.73 | 0.00 | 0.00 | 0.00 |
September | 237.59 | 122.68 | 114.91 | 280.93 | 86.40 | 0.00 | 0.00 | 0.00 |
October | 169.62 | 85.74 | 83.88 | 163.52 | 139.89 | 0.00 | 0.00 | 0.00 |
November | 108.05 | 50.48 | 57.57 | 74.89 | 208.28 | 0.00 | 0.00 | 0.00 |
December | 79.70 | 34.34 | 45.35 | 38.50 | 295.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 223.44 | 112.45 | 110.99 | 239.31 | 161.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 79.70 | 34.34 | 45.35 | 38.50 | 44.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 385.68 | 218.03 | 178.39 | 519.95 | 347.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 157.57 | 112.50 | 45.07 | 149.63 | 169.95 | 0.00 | 0.00 | 0.00 |
February | 197.96 | 141.61 | 56.36 | 206.34 | 125.48 | 0.00 | 0.00 | 0.00 |
March | 177.07 | 98.44 | 78.63 | 183.49 | 110.49 | 0.00 | 0.00 | 0.00 |
April | 145.72 | 70.52 | 75.20 | 158.76 | 78.78 | 0.00 | 0.00 | 0.00 |
May | 129.19 | 43.66 | 85.53 | 144.84 | 59.96 | 0.00 | 0.00 | 0.00 |
June | 126.62 | 36.49 | 90.13 | 162.74 | 36.08 | 0.00 | 0.00 | 0.00 |
July | 136.88 | 50.37 | 86.51 | 197.15 | 25.51 | 0.00 | 0.00 | 0.00 |
August | 160.77 | 79.92 | 80.84 | 222.97 | 29.95 | 0.00 | 0.00 | 0.00 |
September | 180.57 | 110.53 | 70.04 | 230.74 | 47.87 | 0.00 | 0.00 | 0.00 |
October | 190.61 | 132.25 | 58.36 | 222.38 | 74.09 | 0.00 | 0.00 | 0.00 |
November | 172.20 | 124.66 | 47.54 | 183.56 | 102.23 | 0.00 | 0.00 | 0.00 |
December | 149.77 | 108.16 | 41.60 | 146.46 | 143.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.15 | 92.10 | 68.05 | 183.91 | 83.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 126.62 | 36.49 | 41.60 | 144.84 | 25.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.96 | 141.61 | 90.13 | 230.74 | 169.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.35 | 0.00 | 22.35 | 0.49 | 199.19 | 0.00 | 0.00 | 0.00 |
February | 31.55 | 0.00 | 31.55 | 4.95 | 145.53 | 0.00 | 0.00 | 0.00 |
March | 51.26 | 0.00 | 51.26 | 17.89 | 115.74 | 0.00 | 0.00 | 0.00 |
April | 58.78 | 0.56 | 58.22 | 32.22 | 77.54 | 0.00 | 0.00 | 0.00 |
May | 76.63 | 4.41 | 72.22 | 60.22 | 56.32 | 0.00 | 0.00 | 0.00 |
June | 89.62 | 10.51 | 79.12 | 96.16 | 32.68 | 0.00 | 0.00 | 0.00 |
July | 81.77 | 7.76 | 74.01 | 104.78 | 24.75 | 0.00 | 0.00 | 0.00 |
August | 66.04 | 2.28 | 63.76 | 77.26 | 29.10 | 0.00 | 0.00 | 0.00 |
September | 49.08 | 0.07 | 49.01 | 45.57 | 49.34 | 0.00 | 0.00 | 0.00 |
October | 35.74 | 0.00 | 35.74 | 17.99 | 78.65 | 0.00 | 0.00 | 0.00 |
November | 24.30 | 0.00 | 24.30 | 4.53 | 118.84 | 0.00 | 0.00 | 0.00 |
December | 18.74 | 0.00 | 18.74 | 0.47 | 168.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.59 | 2.14 | 48.45 | 38.75 | 91.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.74 | 0.00 | 18.74 | 0.47 | 24.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.62 | 10.51 | 79.12 | 104.78 | 199.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.53 | 44.55 | 51.97 | 50.44 | 343.59 | 0.00 | 0.00 | 0.00 |
February | 151.21 | 75.59 | 75.63 | 115.10 | 248.13 | 0.00 | 0.00 | 0.00 |
March | 202.62 | 84.31 | 118.31 | 168.89 | 202.18 | 0.00 | 0.00 | 0.00 |
April | 257.88 | 128.11 | 129.77 | 258.66 | 137.98 | 0.00 | 0.00 | 0.00 |
May | 284.29 | 126.68 | 157.60 | 306.90 | 105.87 | 0.00 | 0.00 | 0.00 |
June | 367.43 | 189.04 | 178.39 | 455.78 | 62.81 | 0.00 | 0.00 | 0.00 |
July | 385.68 | 218.03 | 167.65 | 516.91 | 46.37 | 0.00 | 0.00 | 0.00 |
August | 336.19 | 187.55 | 148.65 | 439.31 | 53.57 | 0.00 | 0.00 | 0.00 |
September | 237.59 | 122.68 | 114.91 | 283.05 | 86.47 | 0.00 | 0.00 | 0.00 |
October | 169.62 | 85.74 | 83.88 | 167.77 | 137.32 | 0.00 | 0.00 | 0.00 |
November | 108.05 | 50.48 | 57.57 | 77.72 | 202.70 | 0.00 | 0.00 | 0.00 |
December | 79.70 | 34.34 | 45.35 | 39.84 | 290.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 223.44 | 112.45 | 110.99 | 240.74 | 159.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 79.70 | 34.34 | 45.35 | 39.84 | 46.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 385.68 | 218.03 | 178.39 | 516.91 | 343.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.30 | 0.00 | 28.30 | 0.39 | 268.65 | 0.00 | 0.00 | 0.00 |
February | 39.96 | 0.00 | 39.96 | 5.54 | 195.71 | 0.00 | 0.00 | 0.00 |
March | 64.92 | 0.00 | 64.92 | 22.18 | 153.90 | 0.00 | 0.00 | 0.00 |
April | 74.44 | 0.71 | 73.73 | 42.68 | 103.33 | 0.00 | 0.00 | 0.00 |
May | 97.04 | 5.58 | 91.46 | 79.36 | 75.75 | 0.00 | 0.00 | 0.00 |
June | 113.50 | 13.31 | 100.20 | 124.68 | 46.01 | 0.00 | 0.00 | 0.00 |
July | 103.56 | 9.83 | 93.73 | 134.53 | 36.85 | 0.00 | 0.00 | 0.00 |
August | 83.64 | 2.89 | 80.75 | 99.07 | 43.20 | 0.00 | 0.00 | 0.00 |
September | 62.15 | 0.08 | 62.07 | 57.70 | 70.30 | 0.00 | 0.00 | 0.00 |
October | 45.26 | 0.00 | 45.26 | 22.14 | 108.05 | 0.00 | 0.00 | 0.00 |
November | 30.77 | 0.00 | 30.77 | 5.13 | 161.98 | 0.00 | 0.00 | 0.00 |
December | 23.73 | 0.00 | 23.73 | 0.32 | 228.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 64.07 | 2.71 | 61.36 | 49.75 | 124.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.73 | 0.00 | 23.73 | 0.32 | 36.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 113.50 | 13.31 | 100.20 | 134.53 | 268.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.43 | 0.00 | 10.43 | 0.14 | 99.03 | 0.00 | 0.00 | 0.00 |
February | 14.73 | 0.00 | 14.73 | 2.04 | 72.15 | 0.00 | 0.00 | 0.00 |
March | 23.93 | 0.00 | 23.93 | 8.17 | 56.73 | 0.00 | 0.00 | 0.00 |
April | 27.44 | 0.26 | 27.18 | 15.73 | 38.09 | 0.00 | 0.00 | 0.00 |
May | 35.77 | 2.06 | 33.72 | 29.25 | 27.93 | 0.00 | 0.00 | 0.00 |
June | 41.84 | 4.91 | 36.94 | 45.96 | 16.96 | 0.00 | 0.00 | 0.00 |
July | 38.18 | 3.62 | 34.55 | 49.59 | 13.59 | 0.00 | 0.00 | 0.00 |
August | 30.83 | 1.06 | 29.77 | 36.52 | 15.92 | 0.00 | 0.00 | 0.00 |
September | 22.91 | 0.03 | 22.88 | 21.27 | 25.92 | 0.00 | 0.00 | 0.00 |
October | 16.69 | 0.00 | 16.69 | 8.16 | 39.83 | 0.00 | 0.00 | 0.00 |
November | 11.34 | 0.00 | 11.34 | 1.89 | 59.71 | 0.00 | 0.00 | 0.00 |
December | 8.75 | 0.00 | 8.75 | 0.12 | 84.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.62 | 1.00 | 22.62 | 18.34 | 45.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.75 | 0.00 | 8.75 | 0.12 | 13.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.84 | 4.91 | 36.94 | 49.59 | 99.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.52 | 52.49 | 21.03 | 69.36 | 82.95 | 0.00 | 0.00 | 0.00 |
February | 92.37 | 66.07 | 26.30 | 96.68 | 60.89 | 0.00 | 0.00 | 0.00 |
March | 82.62 | 45.93 | 36.69 | 86.54 | 53.48 | 0.00 | 0.00 | 0.00 |
April | 67.99 | 32.90 | 35.09 | 75.42 | 38.51 | 0.00 | 0.00 | 0.00 |
May | 60.28 | 20.37 | 39.91 | 68.85 | 29.86 | 0.00 | 0.00 | 0.00 |
June | 59.08 | 17.03 | 42.06 | 76.58 | 19.48 | 0.00 | 0.00 | 0.00 |
July | 63.87 | 23.50 | 40.37 | 92.05 | 14.82 | 0.00 | 0.00 | 0.00 |
August | 75.01 | 37.29 | 37.72 | 104.26 | 16.96 | 0.00 | 0.00 | 0.00 |
September | 84.25 | 51.57 | 32.68 | 108.13 | 25.26 | 0.00 | 0.00 | 0.00 |
October | 88.94 | 61.71 | 27.23 | 104.66 | 36.82 | 0.00 | 0.00 | 0.00 |
November | 80.35 | 58.17 | 22.18 | 86.01 | 49.86 | 0.00 | 0.00 | 0.00 |
December | 69.88 | 50.47 | 19.41 | 67.91 | 70.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 74.72 | 42.97 | 31.75 | 86.28 | 41.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 59.08 | 17.03 | 19.41 | 67.91 | 14.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.37 | 66.07 | 42.06 | 108.13 | 82.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 199.56 | 142.47 | 57.08 | 188.26 | 225.13 | 0.00 | 0.00 | 0.00 |
February | 250.71 | 179.33 | 71.37 | 262.41 | 165.27 | 0.00 | 0.00 | 0.00 |
March | 224.25 | 124.67 | 99.58 | 234.88 | 145.14 | 0.00 | 0.00 | 0.00 |
April | 184.55 | 89.31 | 95.24 | 204.70 | 104.52 | 0.00 | 0.00 | 0.00 |
May | 163.61 | 55.29 | 108.32 | 186.86 | 81.04 | 0.00 | 0.00 | 0.00 |
June | 160.36 | 46.21 | 114.15 | 207.85 | 52.87 | 0.00 | 0.00 | 0.00 |
July | 173.35 | 63.79 | 109.56 | 249.83 | 40.22 | 0.00 | 0.00 | 0.00 |
August | 203.60 | 101.22 | 102.38 | 282.98 | 46.04 | 0.00 | 0.00 | 0.00 |
September | 228.68 | 139.98 | 88.70 | 293.49 | 68.57 | 0.00 | 0.00 | 0.00 |
October | 241.39 | 167.49 | 73.90 | 284.06 | 99.93 | 0.00 | 0.00 | 0.00 |
November | 218.08 | 157.87 | 60.20 | 233.44 | 135.32 | 0.00 | 0.00 | 0.00 |
December | 189.67 | 136.98 | 52.69 | 184.33 | 190.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 202.82 | 116.64 | 86.18 | 234.19 | 112.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 160.36 | 46.21 | 52.69 | 184.33 | 40.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 250.71 | 179.33 | 114.15 | 293.49 | 225.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 157.57 | 112.50 | 45.07 | 149.69 | 169.61 | 0.00 | 0.00 | 0.00 |
February | 197.96 | 141.61 | 56.36 | 206.57 | 125.34 | 0.00 | 0.00 | 0.00 |
March | 177.07 | 98.44 | 78.63 | 183.96 | 110.18 | 0.00 | 0.00 | 0.00 |
April | 145.72 | 70.52 | 75.20 | 159.18 | 78.49 | 0.00 | 0.00 | 0.00 |
May | 129.19 | 43.66 | 85.53 | 144.63 | 60.24 | 0.00 | 0.00 | 0.00 |
June | 126.62 | 36.49 | 90.13 | 163.08 | 36.16 | 0.00 | 0.00 | 0.00 |
July | 136.88 | 50.37 | 86.51 | 197.36 | 25.48 | 0.00 | 0.00 | 0.00 |
August | 160.77 | 79.92 | 80.84 | 223.08 | 29.51 | 0.00 | 0.00 | 0.00 |
September | 180.57 | 110.53 | 70.04 | 230.53 | 47.48 | 0.00 | 0.00 | 0.00 |
October | 190.61 | 132.25 | 58.36 | 222.64 | 73.58 | 0.00 | 0.00 | 0.00 |
November | 172.20 | 124.66 | 47.54 | 183.67 | 101.87 | 0.00 | 0.00 | 0.00 |
December | 149.77 | 108.16 | 41.60 | 146.61 | 143.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.15 | 92.10 | 68.05 | 184.07 | 83.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 126.62 | 36.49 | 41.60 | 144.63 | 25.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.96 | 141.61 | 90.13 | 230.53 | 169.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.19 | 35.31 | 51.88 | 43.63 | 357.43 | 0.00 | 0.00 | 0.00 |
February | 149.46 | 74.06 | 75.39 | 113.34 | 258.16 | 0.00 | 0.00 | 0.00 |
March | 190.42 | 70.19 | 120.23 | 152.31 | 210.39 | 0.00 | 0.00 | 0.00 |
April | 247.90 | 109.66 | 138.25 | 247.38 | 143.86 | 0.00 | 0.00 | 0.00 |
May | 306.60 | 140.11 | 166.49 | 338.07 | 109.21 | 0.00 | 0.00 | 0.00 |
June | 332.61 | 152.56 | 180.06 | 413.76 | 65.42 | 0.00 | 0.00 | 0.00 |
July | 340.86 | 172.11 | 168.75 | 461.37 | 47.43 | 0.00 | 0.00 | 0.00 |
August | 289.78 | 142.08 | 147.70 | 380.81 | 54.35 | 0.00 | 0.00 | 0.00 |
September | 233.45 | 118.03 | 115.42 | 279.48 | 89.58 | 0.00 | 0.00 | 0.00 |
October | 166.93 | 83.02 | 83.91 | 165.41 | 144.14 | 0.00 | 0.00 | 0.00 |
November | 118.15 | 58.71 | 59.44 | 93.23 | 212.52 | 0.00 | 0.00 | 0.00 |
December | 78.96 | 33.21 | 45.75 | 41.90 | 300.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 212.14 | 99.17 | 112.96 | 228.16 | 165.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 78.96 | 33.21 | 45.75 | 41.90 | 47.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 340.86 | 172.11 | 180.06 | 461.37 | 357.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.35 | 0.00 | 22.35 | 0.65 | 198.46 | 0.00 | 0.00 | 0.00 |
February | 31.55 | 0.00 | 31.55 | 5.82 | 144.96 | 0.00 | 0.00 | 0.00 |
March | 51.26 | 0.00 | 51.26 | 19.40 | 114.91 | 0.00 | 0.00 | 0.00 |
April | 58.78 | 0.56 | 58.22 | 33.08 | 77.24 | 0.00 | 0.00 | 0.00 |
May | 76.63 | 4.41 | 72.22 | 59.71 | 57.07 | 0.00 | 0.00 | 0.00 |
June | 89.62 | 10.51 | 79.12 | 96.70 | 33.37 | 0.00 | 0.00 | 0.00 |
July | 81.77 | 7.76 | 74.01 | 106.29 | 25.18 | 0.00 | 0.00 | 0.00 |
August | 66.04 | 2.28 | 63.76 | 78.51 | 29.27 | 0.00 | 0.00 | 0.00 |
September | 49.08 | 0.07 | 49.01 | 46.70 | 49.17 | 0.00 | 0.00 | 0.00 |
October | 35.74 | 0.00 | 35.74 | 19.61 | 77.89 | 0.00 | 0.00 | 0.00 |
November | 24.30 | 0.00 | 24.30 | 5.11 | 117.76 | 0.00 | 0.00 | 0.00 |
December | 18.74 | 0.00 | 18.74 | 0.63 | 167.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.59 | 2.14 | 48.45 | 39.56 | 90.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.74 | 0.00 | 18.74 | 0.63 | 25.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.62 | 10.51 | 79.12 | 106.29 | 198.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.19 | 35.31 | 51.88 | 46.08 | 354.61 | 0.00 | 0.00 | 0.00 |
February | 149.46 | 74.06 | 75.39 | 118.54 | 254.90 | 0.00 | 0.00 | 0.00 |
March | 190.42 | 70.19 | 120.23 | 157.89 | 207.76 | 0.00 | 0.00 | 0.00 |
April | 247.90 | 109.66 | 138.25 | 249.88 | 143.40 | 0.00 | 0.00 | 0.00 |
May | 306.60 | 140.11 | 166.49 | 337.45 | 111.13 | 0.00 | 0.00 | 0.00 |
June | 332.61 | 152.56 | 180.06 | 410.36 | 68.38 | 0.00 | 0.00 | 0.00 |
July | 340.86 | 172.11 | 168.75 | 459.54 | 50.37 | 0.00 | 0.00 | 0.00 |
August | 289.78 | 142.08 | 147.70 | 380.09 | 57.00 | 0.00 | 0.00 | 0.00 |
September | 233.45 | 118.03 | 115.42 | 282.20 | 90.27 | 0.00 | 0.00 | 0.00 |
October | 166.93 | 83.02 | 83.91 | 170.76 | 141.85 | 0.00 | 0.00 | 0.00 |
November | 118.15 | 58.71 | 59.44 | 98.19 | 208.74 | 0.00 | 0.00 | 0.00 |
December | 78.96 | 33.21 | 45.75 | 44.81 | 297.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 212.14 | 99.17 | 112.96 | 230.23 | 165.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 78.96 | 33.21 | 45.75 | 44.81 | 50.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 340.86 | 172.11 | 180.06 | 459.54 | 354.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 231.09 | 164.99 | 66.10 | 212.55 | 256.72 | 0.00 | 0.00 | 0.00 |
February | 290.33 | 207.68 | 82.65 | 295.36 | 190.21 | 0.00 | 0.00 | 0.00 |
March | 259.69 | 144.37 | 115.31 | 264.42 | 166.28 | 0.00 | 0.00 | 0.00 |
April | 213.72 | 103.42 | 110.29 | 231.14 | 116.78 | 0.00 | 0.00 | 0.00 |
May | 189.47 | 64.03 | 125.44 | 211.88 | 88.21 | 0.00 | 0.00 | 0.00 |
June | 185.71 | 53.52 | 132.19 | 240.94 | 52.01 | 0.00 | 0.00 | 0.00 |
July | 200.75 | 73.87 | 126.88 | 291.95 | 36.05 | 0.00 | 0.00 | 0.00 |
August | 235.78 | 117.22 | 118.56 | 327.87 | 42.64 | 0.00 | 0.00 | 0.00 |
September | 264.83 | 162.11 | 102.72 | 336.30 | 70.53 | 0.00 | 0.00 | 0.00 |
October | 279.54 | 193.96 | 85.58 | 321.66 | 111.37 | 0.00 | 0.00 | 0.00 |
November | 252.54 | 182.83 | 69.72 | 262.70 | 155.18 | 0.00 | 0.00 | 0.00 |
December | 219.65 | 158.63 | 61.02 | 207.53 | 217.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 234.87 | 135.07 | 99.80 | 266.78 | 125.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 185.71 | 53.52 | 61.02 | 207.53 | 36.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 290.33 | 207.68 | 132.19 | 336.30 | 256.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 156.42 | 0.00 | 156.42 | 0.74 | 1553.53 | 0.00 | 0.00 | 0.00 |
February | 220.86 | 0.00 | 220.86 | 19.66 | 1174.06 | 0.00 | 0.00 | 0.00 |
March | 358.81 | 0.01 | 358.80 | 96.59 | 936.25 | 0.00 | 0.00 | 0.00 |
April | 411.45 | 3.94 | 407.50 | 198.62 | 639.89 | 0.00 | 0.00 | 0.00 |
May | 536.37 | 30.84 | 505.53 | 390.19 | 466.44 | 0.00 | 0.00 | 0.00 |
June | 627.34 | 73.55 | 553.80 | 654.94 | 268.50 | 0.00 | 0.00 | 0.00 |
July | 572.37 | 54.33 | 518.03 | 727.55 | 207.17 | 0.00 | 0.00 | 0.00 |
August | 462.28 | 15.95 | 446.33 | 532.38 | 245.38 | 0.00 | 0.00 | 0.00 |
September | 343.53 | 0.47 | 343.07 | 300.07 | 416.47 | 0.00 | 0.00 | 0.00 |
October | 250.17 | 0.00 | 250.17 | 100.74 | 658.61 | 0.00 | 0.00 | 0.00 |
November | 170.07 | 0.00 | 170.07 | 18.19 | 991.94 | 0.00 | 0.00 | 0.00 |
December | 131.17 | 0.00 | 131.17 | 0.62 | 1360.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 354.11 | 15.00 | 339.12 | 254.84 | 741.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.17 | 0.00 | 131.17 | 0.62 | 207.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 627.34 | 73.55 | 553.80 | 727.55 | 1553.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 156.42 | 0.00 | 156.42 | 0.41 | 1581.61 | 0.00 | 0.00 | 0.00 |
February | 220.86 | 0.00 | 220.86 | 16.50 | 1202.38 | 0.00 | 0.00 | 0.00 |
March | 358.81 | 0.01 | 358.80 | 88.71 | 957.43 | 0.00 | 0.00 | 0.00 |
April | 411.45 | 3.94 | 407.50 | 189.06 | 654.90 | 0.00 | 0.00 | 0.00 |
May | 536.37 | 30.84 | 505.53 | 379.49 | 476.99 | 0.00 | 0.00 | 0.00 |
June | 627.34 | 73.55 | 553.80 | 645.55 | 273.90 | 0.00 | 0.00 | 0.00 |
July | 572.37 | 54.33 | 518.03 | 720.01 | 211.91 | 0.00 | 0.00 | 0.00 |
August | 462.28 | 15.95 | 446.33 | 524.91 | 251.50 | 0.00 | 0.00 | 0.00 |
September | 343.53 | 0.47 | 343.07 | 292.53 | 426.79 | 0.00 | 0.00 | 0.00 |
October | 250.17 | 0.00 | 250.17 | 93.35 | 674.88 | 0.00 | 0.00 | 0.00 |
November | 170.07 | 0.00 | 170.07 | 15.29 | 1018.28 | 0.00 | 0.00 | 0.00 |
December | 131.17 | 0.00 | 131.17 | 0.39 | 1392.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 354.11 | 15.00 | 339.12 | 248.66 | 758.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.17 | 0.00 | 131.17 | 0.39 | 211.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 627.34 | 73.55 | 553.80 | 720.01 | 1581.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.35 | 0.00 | 22.35 | 0.85 | 194.71 | 0.00 | 0.00 | 0.00 |
February | 31.55 | 0.00 | 31.55 | 7.43 | 145.22 | 0.00 | 0.00 | 0.00 |
March | 51.26 | 0.00 | 51.26 | 24.10 | 116.16 | 0.00 | 0.00 | 0.00 |
April | 58.78 | 0.56 | 58.22 | 45.01 | 79.22 | 0.00 | 0.00 | 0.00 |
May | 76.63 | 4.41 | 72.22 | 79.03 | 59.84 | 0.00 | 0.00 | 0.00 |
June | 89.62 | 10.51 | 79.12 | 123.65 | 36.69 | 0.00 | 0.00 | 0.00 |
July | 81.77 | 7.76 | 74.01 | 134.55 | 27.90 | 0.00 | 0.00 | 0.00 |
August | 66.04 | 2.28 | 63.76 | 104.09 | 31.60 | 0.00 | 0.00 | 0.00 |
September | 49.08 | 0.07 | 49.01 | 63.70 | 50.38 | 0.00 | 0.00 | 0.00 |
October | 35.74 | 0.00 | 35.74 | 27.43 | 78.16 | 0.00 | 0.00 | 0.00 |
November | 24.30 | 0.00 | 24.30 | 7.06 | 117.90 | 0.00 | 0.00 | 0.00 |
December | 18.74 | 0.00 | 18.74 | 0.85 | 166.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.59 | 2.14 | 48.45 | 51.75 | 91.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.74 | 0.00 | 18.74 | 0.85 | 27.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.62 | 10.51 | 79.12 | 134.55 | 194.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 193.04 | 89.10 | 103.94 | 109.51 | 675.61 | 0.00 | 0.00 | 0.00 |
February | 302.40 | 151.16 | 151.25 | 247.81 | 500.92 | 0.00 | 0.00 | 0.00 |
March | 405.22 | 168.61 | 236.61 | 368.33 | 410.35 | 0.00 | 0.00 | 0.00 |
April | 515.72 | 256.21 | 259.52 | 572.68 | 286.98 | 0.00 | 0.00 | 0.00 |
May | 568.53 | 253.35 | 315.18 | 686.15 | 224.51 | 0.00 | 0.00 | 0.00 |
June | 734.80 | 378.05 | 356.75 | 1012.79 | 138.17 | 0.00 | 0.00 | 0.00 |
July | 771.31 | 436.04 | 335.28 | 1146.04 | 104.44 | 0.00 | 0.00 | 0.00 |
August | 672.34 | 375.07 | 297.27 | 981.45 | 117.43 | 0.00 | 0.00 | 0.00 |
September | 475.14 | 245.34 | 229.80 | 640.63 | 180.76 | 0.00 | 0.00 | 0.00 |
October | 339.21 | 171.47 | 167.74 | 379.61 | 278.30 | 0.00 | 0.00 | 0.00 |
November | 216.09 | 100.96 | 115.13 | 173.90 | 408.41 | 0.00 | 0.00 | 0.00 |
December | 159.38 | 68.68 | 90.70 | 88.23 | 580.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 446.85 | 224.88 | 221.97 | 535.56 | 324.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 159.38 | 68.68 | 90.70 | 88.23 | 104.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 771.31 | 436.04 | 356.75 | 1146.04 | 675.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 157.57 | 112.50 | 45.07 | 155.09 | 167.57 | 0.00 | 0.00 | 0.00 |
February | 197.96 | 141.61 | 56.36 | 215.64 | 126.94 | 0.00 | 0.00 | 0.00 |
March | 177.07 | 98.44 | 78.63 | 194.45 | 111.52 | 0.00 | 0.00 | 0.00 |
April | 145.72 | 70.52 | 75.20 | 174.14 | 80.37 | 0.00 | 0.00 | 0.00 |
May | 129.19 | 43.66 | 85.53 | 163.66 | 63.16 | 0.00 | 0.00 | 0.00 |
June | 126.62 | 36.49 | 90.13 | 187.50 | 40.38 | 0.00 | 0.00 | 0.00 |
July | 136.88 | 50.37 | 86.51 | 224.80 | 29.49 | 0.00 | 0.00 | 0.00 |
August | 160.77 | 79.92 | 80.84 | 248.83 | 32.91 | 0.00 | 0.00 | 0.00 |
September | 180.57 | 110.53 | 70.04 | 250.95 | 49.85 | 0.00 | 0.00 | 0.00 |
October | 190.61 | 132.25 | 58.36 | 237.59 | 75.13 | 0.00 | 0.00 | 0.00 |
November | 172.20 | 124.66 | 47.54 | 193.57 | 103.72 | 0.00 | 0.00 | 0.00 |
December | 149.77 | 108.16 | 41.60 | 151.94 | 143.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.15 | 92.10 | 68.05 | 199.70 | 85.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 126.62 | 36.49 | 41.60 | 151.94 | 29.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.96 | 141.61 | 90.13 | 250.95 | 167.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.30 | 0.00 | 28.30 | 0.30 | 271.34 | 0.00 | 0.00 | 0.00 |
February | 39.96 | 0.00 | 39.96 | 4.70 | 198.45 | 0.00 | 0.00 | 0.00 |
March | 64.92 | 0.00 | 64.92 | 20.40 | 155.63 | 0.00 | 0.00 | 0.00 |
April | 74.44 | 0.71 | 73.73 | 40.26 | 104.30 | 0.00 | 0.00 | 0.00 |
May | 97.04 | 5.58 | 91.46 | 75.89 | 76.78 | 0.00 | 0.00 | 0.00 |
June | 113.50 | 13.31 | 100.20 | 121.02 | 46.56 | 0.00 | 0.00 | 0.00 |
July | 103.56 | 9.83 | 93.73 | 131.53 | 37.37 | 0.00 | 0.00 | 0.00 |
August | 83.64 | 2.89 | 80.75 | 96.48 | 43.47 | 0.00 | 0.00 | 0.00 |
September | 62.15 | 0.08 | 62.07 | 55.86 | 69.98 | 0.00 | 0.00 | 0.00 |
October | 45.26 | 0.00 | 45.26 | 20.78 | 108.05 | 0.00 | 0.00 | 0.00 |
November | 30.77 | 0.00 | 30.77 | 4.64 | 164.21 | 0.00 | 0.00 | 0.00 |
December | 23.73 | 0.00 | 23.73 | 0.25 | 231.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 64.07 | 2.71 | 61.36 | 47.94 | 125.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.73 | 0.00 | 23.73 | 0.25 | 37.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 113.50 | 13.31 | 100.20 | 131.53 | 271.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.32 | 0.00 | 25.32 | 0.27 | 242.74 | 0.00 | 0.00 | 0.00 |
February | 35.75 | 0.00 | 35.75 | 4.21 | 177.55 | 0.00 | 0.00 | 0.00 |
March | 58.08 | 0.00 | 58.08 | 18.25 | 139.25 | 0.00 | 0.00 | 0.00 |
April | 66.60 | 0.64 | 65.96 | 36.02 | 93.32 | 0.00 | 0.00 | 0.00 |
May | 86.82 | 4.99 | 81.83 | 67.90 | 68.69 | 0.00 | 0.00 | 0.00 |
June | 101.55 | 11.91 | 89.65 | 108.28 | 41.66 | 0.00 | 0.00 | 0.00 |
July | 92.65 | 8.80 | 83.86 | 117.68 | 33.44 | 0.00 | 0.00 | 0.00 |
August | 74.83 | 2.58 | 72.25 | 86.32 | 38.89 | 0.00 | 0.00 | 0.00 |
September | 55.61 | 0.08 | 55.53 | 49.98 | 62.61 | 0.00 | 0.00 | 0.00 |
October | 40.50 | 0.00 | 40.50 | 18.59 | 96.67 | 0.00 | 0.00 | 0.00 |
November | 27.53 | 0.00 | 27.53 | 4.15 | 146.91 | 0.00 | 0.00 | 0.00 |
December | 21.23 | 0.00 | 21.23 | 0.23 | 207.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.32 | 2.43 | 54.89 | 42.90 | 112.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.23 | 0.00 | 21.23 | 0.23 | 33.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.55 | 11.91 | 89.65 | 117.68 | 242.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 588.26 | 420.00 | 168.27 | 548.33 | 669.98 | 0.00 | 0.00 | 0.00 |
February | 739.06 | 528.66 | 210.40 | 763.63 | 493.18 | 0.00 | 0.00 | 0.00 |
March | 661.05 | 367.51 | 293.54 | 681.94 | 432.86 | 0.00 | 0.00 | 0.00 |
April | 544.03 | 263.27 | 280.76 | 593.60 | 311.33 | 0.00 | 0.00 | 0.00 |
May | 482.31 | 162.98 | 319.32 | 539.09 | 242.82 | 0.00 | 0.00 | 0.00 |
June | 472.73 | 136.24 | 336.49 | 600.47 | 158.18 | 0.00 | 0.00 | 0.00 |
July | 511.02 | 188.05 | 322.97 | 725.76 | 120.21 | 0.00 | 0.00 | 0.00 |
August | 600.19 | 298.38 | 301.80 | 823.79 | 136.74 | 0.00 | 0.00 | 0.00 |
September | 674.13 | 412.65 | 261.48 | 855.94 | 201.73 | 0.00 | 0.00 | 0.00 |
October | 711.60 | 493.74 | 217.86 | 828.65 | 294.97 | 0.00 | 0.00 | 0.00 |
November | 642.87 | 465.39 | 177.47 | 680.14 | 403.80 | 0.00 | 0.00 | 0.00 |
December | 559.13 | 403.81 | 155.32 | 536.30 | 567.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 597.88 | 343.83 | 254.05 | 680.78 | 335.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 472.73 | 136.24 | 155.32 | 536.30 | 120.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 739.06 | 528.66 | 336.49 | 855.94 | 669.98 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213457E+10 | 0.152400E+10 | 0.610565E+09 | 0.202042E+10 | 0.224923E+10 |
February | 0.242221E+10 | 0.173264E+10 | 0.689573E+09 | 0.251842E+10 | 0.151576E+10 |
March | 0.239867E+10 | 0.133355E+10 | 0.106512E+10 | 0.249617E+10 | 0.147490E+10 |
April | 0.191038E+10 | 0.924488E+09 | 0.985890E+09 | 0.209014E+10 | 0.102399E+10 |
May | 0.175008E+10 | 0.591403E+09 | 0.115868E+10 | 0.197631E+10 | 0.810300E+09 |
June | 0.165999E+10 | 0.478396E+09 | 0.118159E+10 | 0.213453E+10 | 0.499833E+09 |
July | 0.185428E+10 | 0.682365E+09 | 0.117191E+10 | 0.263751E+10 | 0.402727E+09 |
August | 0.217783E+10 | 0.108271E+10 | 0.109512E+10 | 0.298772E+10 | 0.463631E+09 |
September | 0.236723E+10 | 0.144905E+10 | 0.918181E+09 | 0.300458E+10 | 0.670412E+09 |
October | 0.258209E+10 | 0.179157E+10 | 0.790519E+09 | 0.300024E+10 | 0.102412E+10 |
November | 0.225745E+10 | 0.163425E+10 | 0.623199E+09 | 0.238921E+10 | 0.133638E+10 |
December | 0.202887E+10 | 0.146527E+10 | 0.563599E+09 | 0.196946E+10 | 0.191827E+10 |
Annual Sum or Average | 0.255436E+11 | 0.146897E+11 | 0.108540E+11 | 0.292247E+11 | 0.133895E+11 |
Minimum of Months | 0.165999E+10 | 0.478396E+09 | 0.563599E+09 | 0.196946E+10 | 0.402727E+09 |
Maximum of Months | 0.258209E+10 | 0.179157E+10 | 0.118159E+10 | 0.300458E+10 | 0.224923E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.601080E+10 | 0.429149E+10 | 0.171931E+10 | 0.563276E+10 | 0.645174E+10 |
February | 0.682078E+10 | 0.487899E+10 | 0.194179E+10 | 0.701497E+10 | 0.441851E+10 |
March | 0.675449E+10 | 0.375518E+10 | 0.299932E+10 | 0.694908E+10 | 0.433927E+10 |
April | 0.537950E+10 | 0.260330E+10 | 0.277620E+10 | 0.580479E+10 | 0.306929E+10 |
May | 0.492811E+10 | 0.166535E+10 | 0.326276E+10 | 0.546523E+10 | 0.245588E+10 |
June | 0.467442E+10 | 0.134713E+10 | 0.332729E+10 | 0.591178E+10 | 0.154092E+10 |
July | 0.522152E+10 | 0.192149E+10 | 0.330003E+10 | 0.734869E+10 | 0.122544E+10 |
August | 0.613262E+10 | 0.304884E+10 | 0.308377E+10 | 0.834008E+10 | 0.141320E+10 |
September | 0.666597E+10 | 0.408043E+10 | 0.258554E+10 | 0.838404E+10 | 0.204138E+10 |
October | 0.727099E+10 | 0.504494E+10 | 0.222605E+10 | 0.836024E+10 | 0.309680E+10 |
November | 0.635682E+10 | 0.460194E+10 | 0.175489E+10 | 0.664225E+10 | 0.395964E+10 |
December | 0.571315E+10 | 0.412609E+10 | 0.158706E+10 | 0.548165E+10 | 0.553929E+10 |
Annual Sum or Average | 0.719292E+11 | 0.413652E+11 | 0.305640E+11 | 0.813356E+11 | 0.395514E+11 |
Minimum of Months | 0.467442E+10 | 0.134713E+10 | 0.158706E+10 | 0.546523E+10 | 0.122544E+10 |
Maximum of Months | 0.727099E+10 | 0.504494E+10 | 0.332729E+10 | 0.838404E+10 | 0.645174E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.780837E+10 | 0.557489E+10 | 0.223348E+10 | 0.740775E+10 | 0.874236E+10 |
February | 0.886058E+10 | 0.633808E+10 | 0.252250E+10 | 0.923613E+10 | 0.599198E+10 |
March | 0.877447E+10 | 0.487819E+10 | 0.389629E+10 | 0.914222E+10 | 0.592081E+10 |
April | 0.698827E+10 | 0.338183E+10 | 0.360644E+10 | 0.764201E+10 | 0.422459E+10 |
May | 0.640190E+10 | 0.216339E+10 | 0.423851E+10 | 0.718829E+10 | 0.338679E+10 |
June | 0.607234E+10 | 0.175000E+10 | 0.432234E+10 | 0.779771E+10 | 0.209403E+10 |
July | 0.678306E+10 | 0.249613E+10 | 0.428693E+10 | 0.971457E+10 | 0.163467E+10 |
August | 0.796662E+10 | 0.396062E+10 | 0.400600E+10 | 0.110138E+11 | 0.188387E+10 |
September | 0.865948E+10 | 0.530072E+10 | 0.335876E+10 | 0.110468E+11 | 0.275408E+10 |
October | 0.944543E+10 | 0.655367E+10 | 0.289177E+10 | 0.109922E+11 | 0.421344E+10 |
November | 0.825787E+10 | 0.597818E+10 | 0.227970E+10 | 0.871228E+10 | 0.542356E+10 |
December | 0.742171E+10 | 0.536003E+10 | 0.206168E+10 | 0.718262E+10 | 0.758050E+10 |
Annual Sum or Average | 0.934401E+11 | 0.537357E+11 | 0.397044E+11 | 0.107076E+12 | 0.538507E+11 |
Minimum of Months | 0.607234E+10 | 0.175000E+10 | 0.206168E+10 | 0.718262E+10 | 0.163467E+10 |
Maximum of Months | 0.944543E+10 | 0.655367E+10 | 0.432234E+10 | 0.110468E+11 | 0.874236E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.422041E+09 | 0.301322E+09 | 0.120720E+09 | 0.401812E+09 | 0.455196E+09 |
February | 0.478913E+09 | 0.342572E+09 | 0.136341E+09 | 0.500992E+09 | 0.304215E+09 |
March | 0.474259E+09 | 0.263665E+09 | 0.210595E+09 | 0.494568E+09 | 0.296446E+09 |
April | 0.377716E+09 | 0.182787E+09 | 0.194929E+09 | 0.414332E+09 | 0.205009E+09 |
May | 0.346023E+09 | 0.116931E+09 | 0.229093E+09 | 0.389903E+09 | 0.162128E+09 |
June | 0.328211E+09 | 94587131.19 | 0.233624E+09 | 0.425462E+09 | 94668907.48 |
July | 0.366625E+09 | 0.134915E+09 | 0.231710E+09 | 0.531288E+09 | 69558429.40 |
August | 0.430596E+09 | 0.214070E+09 | 0.216526E+09 | 0.600345E+09 | 80632126.76 |
September | 0.468044E+09 | 0.286502E+09 | 0.181542E+09 | 0.600002E+09 | 0.125008E+09 |
October | 0.510524E+09 | 0.354224E+09 | 0.156300E+09 | 0.597868E+09 | 0.199359E+09 |
November | 0.446337E+09 | 0.323119E+09 | 0.123218E+09 | 0.476577E+09 | 0.265836E+09 |
December | 0.401142E+09 | 0.289708E+09 | 0.111434E+09 | 0.392861E+09 | 0.385135E+09 |
Annual Sum or Average | 0.505043E+10 | 0.290440E+10 | 0.214603E+10 | 0.582601E+10 | 0.264319E+10 |
Minimum of Months | 0.328211E+09 | 94587131.19 | 0.111434E+09 | 0.389903E+09 | 69558429.40 |
Maximum of Months | 0.510524E+09 | 0.354224E+09 | 0.233624E+09 | 0.600345E+09 | 0.455196E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233530E+09 | 94565909.88 | 0.138964E+09 | 0.116424E+09 | 0.959139E+09 |
February | 0.361562E+09 | 0.179167E+09 | 0.182395E+09 | 0.274251E+09 | 0.627270E+09 |
March | 0.510013E+09 | 0.187989E+09 | 0.322024E+09 | 0.409456E+09 | 0.566112E+09 |
April | 0.642563E+09 | 0.284226E+09 | 0.358337E+09 | 0.644200E+09 | 0.375824E+09 |
May | 0.821185E+09 | 0.375259E+09 | 0.445926E+09 | 0.911222E+09 | 0.294201E+09 |
June | 0.862137E+09 | 0.395433E+09 | 0.466704E+09 | 0.107846E+10 | 0.171497E+09 |
July | 0.912949E+09 | 0.460972E+09 | 0.451978E+09 | 0.124114E+10 | 0.129486E+09 |
August | 0.776139E+09 | 0.380536E+09 | 0.395603E+09 | 0.102416E+10 | 0.148632E+09 |
September | 0.605105E+09 | 0.305937E+09 | 0.299168E+09 | 0.727036E+09 | 0.236037E+09 |
October | 0.447106E+09 | 0.222368E+09 | 0.224738E+09 | 0.443448E+09 | 0.391304E+09 |
November | 0.306246E+09 | 0.152179E+09 | 0.154067E+09 | 0.241301E+09 | 0.555407E+09 |
December | 0.211486E+09 | 88951420.94 | 0.122535E+09 | 0.111110E+09 | 0.810261E+09 |
Annual Sum or Average | 0.669002E+10 | 0.312758E+10 | 0.356244E+10 | 0.722220E+10 | 0.526517E+10 |
Minimum of Months | 0.211486E+09 | 88951420.94 | 0.122535E+09 | 0.111110E+09 | 0.129486E+09 |
Maximum of Months | 0.912949E+09 | 0.460972E+09 | 0.466704E+09 | 0.124114E+10 | 0.959139E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 59854623.75 | 0.00 | 59854623.75 | 1550167.03 | 0.533410E+09 |
February | 76332549.51 | 0.00 | 76332549.51 | 13226102.48 | 0.352539E+09 |
March | 0.137298E+09 | 4398.64 | 0.137293E+09 | 50905780.20 | 0.309826E+09 |
April | 0.152359E+09 | 1460643.42 | 0.150898E+09 | 85746051.39 | 0.201584E+09 |
May | 0.205237E+09 | 11801087.02 | 0.193436E+09 | 0.161739E+09 | 0.152902E+09 |
June | 0.232305E+09 | 27234410.10 | 0.205070E+09 | 0.252849E+09 | 86411328.95 |
July | 0.219012E+09 | 20790737.71 | 0.198222E+09 | 0.286017E+09 | 67825887.06 |
August | 0.176889E+09 | 6103666.06 | 0.170785E+09 | 0.210985E+09 | 79095622.91 |
September | 0.127210E+09 | 172233.62 | 0.127038E+09 | 0.120392E+09 | 0.129369E+09 |
October | 95727014.26 | 0.00 | 95727014.26 | 50728060.79 | 0.212075E+09 |
November | 62976875.21 | 0.00 | 62976875.21 | 12323363.00 | 0.308959E+09 |
December | 50191471.95 | 0.00 | 50191471.95 | 1401247.90 | 0.452304E+09 |
Annual Sum or Average | 0.159539E+10 | 67567176.57 | 0.152783E+10 | 0.124786E+10 | 0.288630E+10 |
Minimum of Months | 50191471.95 | 0.00 | 50191471.95 | 1401247.90 | 67825887.06 |
Maximum of Months | 0.232305E+09 | 27234410.10 | 0.205070E+09 | 0.286017E+09 | 0.533410E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233530E+09 | 94565909.88 | 0.138964E+09 | 0.122997E+09 | 0.950786E+09 |
February | 0.361562E+09 | 0.179167E+09 | 0.182395E+09 | 0.286093E+09 | 0.619133E+09 |
March | 0.510013E+09 | 0.187989E+09 | 0.322024E+09 | 0.423189E+09 | 0.559308E+09 |
April | 0.642563E+09 | 0.284226E+09 | 0.358337E+09 | 0.650423E+09 | 0.374321E+09 |
May | 0.821185E+09 | 0.375259E+09 | 0.445926E+09 | 0.910370E+09 | 0.297766E+09 |
June | 0.862137E+09 | 0.395433E+09 | 0.466704E+09 | 0.107105E+10 | 0.177387E+09 |
July | 0.912949E+09 | 0.460972E+09 | 0.451978E+09 | 0.123655E+10 | 0.135993E+09 |
August | 0.776139E+09 | 0.380536E+09 | 0.395603E+09 | 0.102246E+10 | 0.154442E+09 |
September | 0.605105E+09 | 0.305937E+09 | 0.299168E+09 | 0.733112E+09 | 0.237585E+09 |
October | 0.447106E+09 | 0.222368E+09 | 0.224738E+09 | 0.455744E+09 | 0.385795E+09 |
November | 0.306246E+09 | 0.152179E+09 | 0.154067E+09 | 0.252778E+09 | 0.545795E+09 |
December | 0.211486E+09 | 88951420.94 | 0.122535E+09 | 0.118806E+09 | 0.801973E+09 |
Annual Sum or Average | 0.669002E+10 | 0.312758E+10 | 0.356244E+10 | 0.728357E+10 | 0.524028E+10 |
Minimum of Months | 0.211486E+09 | 88951420.94 | 0.122535E+09 | 0.118806E+09 | 0.135993E+09 |
Maximum of Months | 0.912949E+09 | 0.460972E+09 | 0.466704E+09 | 0.123655E+10 | 0.950786E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.337566E+09 | 0.241009E+09 | 96556546.53 | 0.316888E+09 | 0.368356E+09 |
February | 0.383054E+09 | 0.274003E+09 | 0.109051E+09 | 0.387631E+09 | 0.263072E+09 |
March | 0.379332E+09 | 0.210890E+09 | 0.168442E+09 | 0.371148E+09 | 0.288855E+09 |
April | 0.302113E+09 | 0.146201E+09 | 0.155912E+09 | 0.306486E+09 | 0.217563E+09 |
May | 0.276763E+09 | 93525809.26 | 0.183238E+09 | 0.283808E+09 | 0.177445E+09 |
June | 0.262517E+09 | 75654659.28 | 0.186862E+09 | 0.308344E+09 | 0.116137E+09 |
July | 0.293242E+09 | 0.107911E+09 | 0.185331E+09 | 0.392060E+09 | 93626197.73 |
August | 0.344408E+09 | 0.171222E+09 | 0.173186E+09 | 0.448716E+09 | 0.107334E+09 |
September | 0.374361E+09 | 0.229156E+09 | 0.145205E+09 | 0.451033E+09 | 0.150112E+09 |
October | 0.408338E+09 | 0.283323E+09 | 0.125015E+09 | 0.447588E+09 | 0.219547E+09 |
November | 0.356998E+09 | 0.258444E+09 | 98554623.67 | 0.354040E+09 | 0.268320E+09 |
December | 0.320850E+09 | 0.231721E+09 | 89129292.72 | 0.297774E+09 | 0.338553E+09 |
Annual Sum or Average | 0.403954E+10 | 0.232306E+10 | 0.171648E+10 | 0.436551E+10 | 0.260892E+10 |
Minimum of Months | 0.262517E+09 | 75654659.28 | 89129292.72 | 0.283808E+09 | 93626197.73 |
Maximum of Months | 0.408338E+09 | 0.283323E+09 | 0.186862E+09 | 0.451033E+09 | 0.368356E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 47890046.26 | 0.00 | 47890046.26 | 815180.68 | 0.443072E+09 |
February | 61074134.26 | 0.00 | 61074134.26 | 9614756.00 | 0.291090E+09 |
March | 0.109853E+09 | 3519.38 | 0.109849E+09 | 39265226.80 | 0.254436E+09 |
April | 0.121903E+09 | 1168669.63 | 0.120734E+09 | 71345097.35 | 0.163242E+09 |
May | 0.164211E+09 | 9442121.06 | 0.154769E+09 | 0.135936E+09 | 0.122101E+09 |
June | 0.185868E+09 | 21790416.14 | 0.164078E+09 | 0.212804E+09 | 66292561.51 |
July | 0.175233E+09 | 16634794.91 | 0.158598E+09 | 0.240844E+09 | 49743804.87 |
August | 0.141530E+09 | 4883580.11 | 0.136646E+09 | 0.179445E+09 | 59131974.00 |
September | 0.101782E+09 | 137805.16 | 0.101644E+09 | 0.101903E+09 | 0.100946E+09 |
October | 76591762.73 | 0.00 | 76591762.73 | 40874561.19 | 0.171857E+09 |
November | 50388178.52 | 0.00 | 50388178.52 | 8973314.87 | 0.256892E+09 |
December | 40158500.09 | 0.00 | 40158500.09 | 662898.96 | 0.377401E+09 |
Annual Sum or Average | 0.127648E+10 | 54060906.39 | 0.122242E+10 | 0.104248E+10 | 0.235621E+10 |
Minimum of Months | 40158500.09 | 0.00 | 40158500.09 | 662898.96 | 49743804.87 |
Maximum of Months | 0.185868E+09 | 21790416.14 | 0.164078E+09 | 0.240844E+09 | 0.443072E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258537E+09 | 0.119334E+09 | 0.139203E+09 | 0.131144E+09 | 0.931906E+09 |
February | 0.365815E+09 | 0.182855E+09 | 0.182960E+09 | 0.269269E+09 | 0.611531E+09 |
March | 0.542710E+09 | 0.225816E+09 | 0.316894E+09 | 0.440397E+09 | 0.548920E+09 |
April | 0.668426E+09 | 0.332068E+09 | 0.336358E+09 | 0.663603E+09 | 0.359985E+09 |
May | 0.761433E+09 | 0.339310E+09 | 0.422123E+09 | 0.820038E+09 | 0.281796E+09 |
June | 0.952373E+09 | 0.489989E+09 | 0.462384E+09 | 0.118730E+10 | 0.157236E+09 |
July | 0.103302E+10 | 0.583980E+09 | 0.449035E+09 | 0.139264E+10 | 0.118513E+09 |
August | 0.900455E+09 | 0.502324E+09 | 0.398132E+09 | 0.117907E+10 | 0.138557E+09 |
September | 0.615830E+09 | 0.317982E+09 | 0.297848E+09 | 0.728158E+09 | 0.223953E+09 |
October | 0.454304E+09 | 0.229650E+09 | 0.224654E+09 | 0.437982E+09 | 0.374677E+09 |
November | 0.280069E+09 | 0.130853E+09 | 0.149217E+09 | 0.194114E+09 | 0.539851E+09 |
December | 0.213461E+09 | 91984033.00 | 0.121477E+09 | 0.103132E+09 | 0.790924E+09 |
Annual Sum or Average | 0.704643E+10 | 0.354615E+10 | 0.350028E+10 | 0.754685E+10 | 0.507785E+10 |
Minimum of Months | 0.213461E+09 | 91984033.00 | 0.121477E+09 | 0.103132E+09 | 0.118513E+09 |
Maximum of Months | 0.103302E+10 | 0.583980E+09 | 0.462384E+09 | 0.139264E+10 | 0.931906E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.422041E+09 | 0.301322E+09 | 0.120720E+09 | 0.400776E+09 | 0.455191E+09 |
February | 0.478913E+09 | 0.342572E+09 | 0.136341E+09 | 0.499175E+09 | 0.303562E+09 |
March | 0.474259E+09 | 0.263665E+09 | 0.210595E+09 | 0.491450E+09 | 0.295928E+09 |
April | 0.377716E+09 | 0.182787E+09 | 0.194929E+09 | 0.411503E+09 | 0.204197E+09 |
May | 0.346023E+09 | 0.116931E+09 | 0.229093E+09 | 0.387927E+09 | 0.160584E+09 |
June | 0.328211E+09 | 94587131.19 | 0.233624E+09 | 0.421833E+09 | 93516673.58 |
July | 0.366625E+09 | 0.134915E+09 | 0.231710E+09 | 0.528052E+09 | 68327791.58 |
August | 0.430596E+09 | 0.214070E+09 | 0.216526E+09 | 0.597198E+09 | 80223180.15 |
September | 0.468044E+09 | 0.286502E+09 | 0.181542E+09 | 0.598066E+09 | 0.124084E+09 |
October | 0.510524E+09 | 0.354224E+09 | 0.156300E+09 | 0.595631E+09 | 0.198435E+09 |
November | 0.446337E+09 | 0.323119E+09 | 0.123218E+09 | 0.475783E+09 | 0.264970E+09 |
December | 0.401142E+09 | 0.289708E+09 | 0.111434E+09 | 0.392288E+09 | 0.384682E+09 |
Annual Sum or Average | 0.505043E+10 | 0.290440E+10 | 0.214603E+10 | 0.579968E+10 | 0.263370E+10 |
Minimum of Months | 0.328211E+09 | 94587131.19 | 0.111434E+09 | 0.387927E+09 | 68327791.58 |
Maximum of Months | 0.510524E+09 | 0.354224E+09 | 0.233624E+09 | 0.598066E+09 | 0.455191E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 59854623.75 | 0.00 | 59854623.75 | 1304211.17 | 0.533507E+09 |
February | 76332549.51 | 0.00 | 76332549.51 | 11984578.28 | 0.352071E+09 |
March | 0.137298E+09 | 4398.64 | 0.137293E+09 | 47915873.62 | 0.310001E+09 |
April | 0.152359E+09 | 1460643.42 | 0.150898E+09 | 83513079.89 | 0.200987E+09 |
May | 0.205237E+09 | 11801087.02 | 0.193436E+09 | 0.161286E+09 | 0.150857E+09 |
June | 0.232305E+09 | 27234410.10 | 0.205070E+09 | 0.249255E+09 | 84707870.68 |
July | 0.219012E+09 | 20790737.71 | 0.198222E+09 | 0.280646E+09 | 66300433.68 |
August | 0.176889E+09 | 6103666.06 | 0.170785E+09 | 0.206922E+09 | 77954559.41 |
September | 0.127210E+09 | 172233.62 | 0.127038E+09 | 0.118105E+09 | 0.127890E+09 |
October | 95727014.26 | 0.00 | 95727014.26 | 48189433.50 | 0.210645E+09 |
November | 62976875.21 | 0.00 | 62976875.21 | 11732796.51 | 0.308022E+09 |
December | 50191471.95 | 0.00 | 50191471.95 | 1263654.35 | 0.451841E+09 |
Annual Sum or Average | 0.159539E+10 | 67567176.57 | 0.152783E+10 | 0.122212E+10 | 0.287479E+10 |
Minimum of Months | 50191471.95 | 0.00 | 50191471.95 | 1263654.35 | 66300433.68 |
Maximum of Months | 0.232305E+09 | 27234410.10 | 0.205070E+09 | 0.280646E+09 | 0.533507E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258537E+09 | 0.119334E+09 | 0.139203E+09 | 0.135091E+09 | 0.920281E+09 |
February | 0.365815E+09 | 0.182855E+09 | 0.182960E+09 | 0.278449E+09 | 0.600273E+09 |
March | 0.542710E+09 | 0.225816E+09 | 0.316894E+09 | 0.452351E+09 | 0.541522E+09 |
April | 0.668426E+09 | 0.332068E+09 | 0.336358E+09 | 0.670434E+09 | 0.357640E+09 |
May | 0.761433E+09 | 0.339310E+09 | 0.422123E+09 | 0.821992E+09 | 0.283560E+09 |
June | 0.952373E+09 | 0.489989E+09 | 0.462384E+09 | 0.118137E+10 | 0.162802E+09 |
July | 0.103302E+10 | 0.583980E+09 | 0.449035E+09 | 0.138450E+10 | 0.124206E+09 |
August | 0.900455E+09 | 0.502324E+09 | 0.398132E+09 | 0.117664E+10 | 0.143486E+09 |
September | 0.615830E+09 | 0.317982E+09 | 0.297848E+09 | 0.733654E+09 | 0.224119E+09 |
October | 0.454304E+09 | 0.229650E+09 | 0.224654E+09 | 0.449357E+09 | 0.367800E+09 |
November | 0.280069E+09 | 0.130853E+09 | 0.149217E+09 | 0.201454E+09 | 0.525386E+09 |
December | 0.213461E+09 | 91984033.00 | 0.121477E+09 | 0.106720E+09 | 0.777886E+09 |
Annual Sum or Average | 0.704643E+10 | 0.354615E+10 | 0.350028E+10 | 0.759202E+10 | 0.502896E+10 |
Minimum of Months | 0.213461E+09 | 91984033.00 | 0.121477E+09 | 0.106720E+09 | 0.124206E+09 |
Maximum of Months | 0.103302E+10 | 0.583980E+09 | 0.462384E+09 | 0.138450E+10 | 0.920281E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75802104.36 | 0.00 | 75802104.36 | 1048172.58 | 0.719545E+09 |
February | 96670357.63 | 0.00 | 96670357.63 | 13392065.02 | 0.473473E+09 |
March | 0.173879E+09 | 5570.60 | 0.173873E+09 | 59394280.56 | 0.412195E+09 |
April | 0.192953E+09 | 1849812.73 | 0.191103E+09 | 0.110616E+09 | 0.267841E+09 |
May | 0.259920E+09 | 14945332.10 | 0.244974E+09 | 0.212553E+09 | 0.202897E+09 |
June | 0.294199E+09 | 34490662.00 | 0.259709E+09 | 0.323183E+09 | 0.119266E+09 |
July | 0.277365E+09 | 26330157.48 | 0.251035E+09 | 0.360322E+09 | 98710392.62 |
August | 0.224019E+09 | 7729907.95 | 0.216289E+09 | 0.265337E+09 | 0.115701E+09 |
September | 0.161103E+09 | 218123.01 | 0.160885E+09 | 0.149570E+09 | 0.182224E+09 |
October | 0.121232E+09 | 0.00 | 0.121232E+09 | 59287825.89 | 0.289398E+09 |
November | 79756238.83 | 0.00 | 79756238.83 | 13288245.69 | 0.419853E+09 |
December | 63564332.31 | 0.00 | 63564332.31 | 861685.97 | 0.612594E+09 |
Annual Sum or Average | 0.202046E+10 | 85569565.88 | 0.193489E+10 | 0.156885E+10 | 0.391370E+10 |
Minimum of Months | 63564332.31 | 0.00 | 63564332.31 | 861685.97 | 98710392.62 |
Maximum of Months | 0.294199E+09 | 34490662.00 | 0.259709E+09 | 0.360322E+09 | 0.719545E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 27943794.39 | 0.00 | 27943794.39 | 386399.81 | 0.265254E+09 |
February | 35636696.63 | 0.00 | 35636696.63 | 4936869.69 | 0.174542E+09 |
March | 64098970.43 | 2053.56 | 64096916.88 | 21895191.14 | 0.151952E+09 |
April | 71130366.98 | 681917.57 | 70448449.41 | 40777818.86 | 98737312.04 |
May | 95817166.69 | 5509468.25 | 90307698.44 | 78355824.17 | 74796242.68 |
June | 0.108454E+09 | 12714686.16 | 95739350.45 | 0.119139E+09 | 43966543.68 |
July | 0.102248E+09 | 9706386.29 | 92541943.46 | 0.132829E+09 | 36388737.99 |
August | 82582644.76 | 2849564.14 | 79733080.62 | 97814381.36 | 42652265.67 |
September | 59389417.13 | 80409.17 | 59309007.95 | 55137677.95 | 67175283.95 |
October | 44691217.42 | 0.00 | 44691217.42 | 21855947.54 | 0.106684E+09 |
November | 29401452.08 | 0.00 | 29401452.08 | 4898597.58 | 0.154775E+09 |
December | 23432444.88 | 0.00 | 23432444.88 | 317653.13 | 0.225828E+09 |
Annual Sum or Average | 0.744827E+09 | 31544485.14 | 0.713282E+09 | 0.578345E+09 | 0.144275E+10 |
Minimum of Months | 23432444.88 | 0.00 | 23432444.88 | 317653.13 | 36388737.99 |
Maximum of Months | 0.108454E+09 | 12714686.16 | 95739350.45 | 0.132829E+09 | 0.265254E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196923E+09 | 0.140595E+09 | 56327319.16 | 0.185776E+09 | 0.222163E+09 |
February | 0.223459E+09 | 0.159843E+09 | 63616331.40 | 0.233887E+09 | 0.147303E+09 |
March | 0.221288E+09 | 0.123025E+09 | 98262638.47 | 0.231779E+09 | 0.143230E+09 |
April | 0.176241E+09 | 85287714.47 | 90953128.82 | 0.195484E+09 | 99811941.42 |
May | 0.161453E+09 | 54559305.37 | 0.106894E+09 | 0.184397E+09 | 79972176.20 |
June | 0.153142E+09 | 44133974.26 | 0.109008E+09 | 0.198493E+09 | 50486576.34 |
July | 0.171066E+09 | 62950919.31 | 0.108115E+09 | 0.246536E+09 | 39691587.27 |
August | 0.200914E+09 | 99884391.19 | 0.101030E+09 | 0.279246E+09 | 45428123.73 |
September | 0.218388E+09 | 0.133681E+09 | 84706679.22 | 0.280277E+09 | 65485459.72 |
October | 0.238209E+09 | 0.165280E+09 | 72929103.04 | 0.280318E+09 | 98613381.61 |
November | 0.208259E+09 | 0.150766E+09 | 57492919.35 | 0.222927E+09 | 0.129227E+09 |
December | 0.187171E+09 | 0.135177E+09 | 51994549.28 | 0.181895E+09 | 0.187787E+09 |
Annual Sum or Average | 0.235651E+10 | 0.135518E+10 | 0.100133E+10 | 0.272101E+10 | 0.130920E+10 |
Minimum of Months | 0.153142E+09 | 44133974.26 | 51994549.28 | 0.181895E+09 | 39691587.27 |
Maximum of Months | 0.238209E+09 | 0.165280E+09 | 0.109008E+09 | 0.280318E+09 | 0.222163E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.534489E+09 | 0.381605E+09 | 0.152884E+09 | 0.504235E+09 | 0.602996E+09 |
February | 0.606513E+09 | 0.433846E+09 | 0.172668E+09 | 0.634818E+09 | 0.399811E+09 |
March | 0.600620E+09 | 0.333915E+09 | 0.266705E+09 | 0.629094E+09 | 0.388754E+09 |
April | 0.478354E+09 | 0.231488E+09 | 0.246865E+09 | 0.530583E+09 | 0.270910E+09 |
May | 0.438216E+09 | 0.148085E+09 | 0.290131E+09 | 0.500492E+09 | 0.217061E+09 |
June | 0.415659E+09 | 0.119789E+09 | 0.295870E+09 | 0.538750E+09 | 0.137031E+09 |
July | 0.464308E+09 | 0.170862E+09 | 0.293446E+09 | 0.669150E+09 | 0.107731E+09 |
August | 0.545323E+09 | 0.271107E+09 | 0.274216E+09 | 0.757929E+09 | 0.123302E+09 |
September | 0.592748E+09 | 0.362837E+09 | 0.229911E+09 | 0.760729E+09 | 0.177741E+09 |
October | 0.646547E+09 | 0.448603E+09 | 0.197945E+09 | 0.760839E+09 | 0.267657E+09 |
November | 0.565257E+09 | 0.409210E+09 | 0.156048E+09 | 0.605068E+09 | 0.350750E+09 |
December | 0.508021E+09 | 0.366897E+09 | 0.141124E+09 | 0.493701E+09 | 0.509693E+09 |
Annual Sum or Average | 0.639605E+10 | 0.367824E+10 | 0.271781E+10 | 0.738539E+10 | 0.355344E+10 |
Minimum of Months | 0.415659E+09 | 0.119789E+09 | 0.141124E+09 | 0.493701E+09 | 0.107731E+09 |
Maximum of Months | 0.646547E+09 | 0.448603E+09 | 0.295870E+09 | 0.760839E+09 | 0.602996E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.422041E+09 | 0.301322E+09 | 0.120720E+09 | 0.400933E+09 | 0.454274E+09 |
February | 0.478913E+09 | 0.342572E+09 | 0.136341E+09 | 0.499733E+09 | 0.303222E+09 |
March | 0.474259E+09 | 0.263665E+09 | 0.210595E+09 | 0.492729E+09 | 0.295115E+09 |
April | 0.377716E+09 | 0.182787E+09 | 0.194929E+09 | 0.412601E+09 | 0.203456E+09 |
May | 0.346023E+09 | 0.116931E+09 | 0.229093E+09 | 0.387377E+09 | 0.161345E+09 |
June | 0.328211E+09 | 94587131.19 | 0.233624E+09 | 0.422706E+09 | 93716174.34 |
July | 0.366625E+09 | 0.134915E+09 | 0.231710E+09 | 0.528619E+09 | 68240036.22 |
August | 0.430596E+09 | 0.214070E+09 | 0.216526E+09 | 0.597496E+09 | 79030423.81 |
September | 0.468044E+09 | 0.286502E+09 | 0.181542E+09 | 0.597534E+09 | 0.123078E+09 |
October | 0.510524E+09 | 0.354224E+09 | 0.156300E+09 | 0.596319E+09 | 0.197070E+09 |
November | 0.446337E+09 | 0.323119E+09 | 0.123218E+09 | 0.476067E+09 | 0.264052E+09 |
December | 0.401142E+09 | 0.289708E+09 | 0.111434E+09 | 0.392689E+09 | 0.383440E+09 |
Annual Sum or Average | 0.505043E+10 | 0.290440E+10 | 0.214603E+10 | 0.580480E+10 | 0.262604E+10 |
Minimum of Months | 0.328211E+09 | 94587131.19 | 0.111434E+09 | 0.387377E+09 | 68240036.22 |
Maximum of Months | 0.510524E+09 | 0.354224E+09 | 0.233624E+09 | 0.597534E+09 | 0.454274E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233530E+09 | 94565909.88 | 0.138964E+09 | 0.116856E+09 | 0.957336E+09 |
February | 0.361562E+09 | 0.179167E+09 | 0.182395E+09 | 0.274197E+09 | 0.624531E+09 |
March | 0.510013E+09 | 0.187989E+09 | 0.322024E+09 | 0.407947E+09 | 0.563512E+09 |
April | 0.642563E+09 | 0.284226E+09 | 0.358337E+09 | 0.641203E+09 | 0.372884E+09 |
May | 0.821185E+09 | 0.375259E+09 | 0.445926E+09 | 0.905484E+09 | 0.292500E+09 |
June | 0.862137E+09 | 0.395433E+09 | 0.466704E+09 | 0.107245E+10 | 0.169560E+09 |
July | 0.912949E+09 | 0.460972E+09 | 0.451978E+09 | 0.123573E+10 | 0.127043E+09 |
August | 0.776139E+09 | 0.380536E+09 | 0.395603E+09 | 0.101996E+10 | 0.145570E+09 |
September | 0.605105E+09 | 0.305937E+09 | 0.299168E+09 | 0.724421E+09 | 0.232197E+09 |
October | 0.447106E+09 | 0.222368E+09 | 0.224738E+09 | 0.443033E+09 | 0.386062E+09 |
November | 0.306246E+09 | 0.152179E+09 | 0.154067E+09 | 0.241649E+09 | 0.550852E+09 |
December | 0.211486E+09 | 88951420.94 | 0.122535E+09 | 0.112217E+09 | 0.805587E+09 |
Annual Sum or Average | 0.669002E+10 | 0.312758E+10 | 0.356244E+10 | 0.719515E+10 | 0.522763E+10 |
Minimum of Months | 0.211486E+09 | 88951420.94 | 0.122535E+09 | 0.112217E+09 | 0.127043E+09 |
Maximum of Months | 0.912949E+09 | 0.460972E+09 | 0.466704E+09 | 0.123573E+10 | 0.957336E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 59854623.75 | 0.00 | 59854623.75 | 1749101.59 | 0.531543E+09 |
February | 76332549.51 | 0.00 | 76332549.51 | 14087358.02 | 0.350682E+09 |
March | 0.137298E+09 | 4398.64 | 0.137293E+09 | 51970999.11 | 0.307781E+09 |
April | 0.152359E+09 | 1460643.42 | 0.150898E+09 | 85751457.67 | 0.200195E+09 |
May | 0.205237E+09 | 11801087.02 | 0.193436E+09 | 0.159926E+09 | 0.152869E+09 |
June | 0.232305E+09 | 27234410.10 | 0.205070E+09 | 0.250639E+09 | 86487479.42 |
July | 0.219012E+09 | 20790737.71 | 0.198222E+09 | 0.284681E+09 | 67450776.46 |
August | 0.176889E+09 | 6103666.06 | 0.170785E+09 | 0.210268E+09 | 78395105.53 |
September | 0.127210E+09 | 172233.62 | 0.127038E+09 | 0.121050E+09 | 0.127440E+09 |
October | 95727014.26 | 0.00 | 95727014.26 | 52528363.31 | 0.208627E+09 |
November | 62976875.21 | 0.00 | 62976875.21 | 13235836.35 | 0.305225E+09 |
December | 50191471.95 | 0.00 | 50191471.95 | 1682027.02 | 0.448772E+09 |
Annual Sum or Average | 0.159539E+10 | 67567176.57 | 0.152783E+10 | 0.124757E+10 | 0.286547E+10 |
Minimum of Months | 50191471.95 | 0.00 | 50191471.95 | 1682027.02 | 67450776.46 |
Maximum of Months | 0.232305E+09 | 27234410.10 | 0.205070E+09 | 0.284681E+09 | 0.531543E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233530E+09 | 94565909.88 | 0.138964E+09 | 0.123418E+09 | 0.949781E+09 |
February | 0.361562E+09 | 0.179167E+09 | 0.182395E+09 | 0.286783E+09 | 0.616651E+09 |
March | 0.510013E+09 | 0.187989E+09 | 0.322024E+09 | 0.422882E+09 | 0.556463E+09 |
April | 0.642563E+09 | 0.284226E+09 | 0.358337E+09 | 0.647700E+09 | 0.371689E+09 |
May | 0.821185E+09 | 0.375259E+09 | 0.445926E+09 | 0.903837E+09 | 0.297656E+09 |
June | 0.862137E+09 | 0.395433E+09 | 0.466704E+09 | 0.106366E+10 | 0.177251E+09 |
July | 0.912949E+09 | 0.460972E+09 | 0.451978E+09 | 0.123084E+10 | 0.134899E+09 |
August | 0.776139E+09 | 0.380536E+09 | 0.395603E+09 | 0.101803E+10 | 0.152662E+09 |
September | 0.605105E+09 | 0.305937E+09 | 0.299168E+09 | 0.731452E+09 | 0.233969E+09 |
October | 0.447106E+09 | 0.222368E+09 | 0.224738E+09 | 0.457350E+09 | 0.379927E+09 |
November | 0.306246E+09 | 0.152179E+09 | 0.154067E+09 | 0.254508E+09 | 0.541043E+09 |
December | 0.211486E+09 | 88951420.94 | 0.122535E+09 | 0.120023E+09 | 0.798120E+09 |
Annual Sum or Average | 0.669002E+10 | 0.312758E+10 | 0.356244E+10 | 0.726048E+10 | 0.521011E+10 |
Minimum of Months | 0.211486E+09 | 88951420.94 | 0.122535E+09 | 0.120023E+09 | 0.134899E+09 |
Maximum of Months | 0.912949E+09 | 0.460972E+09 | 0.466704E+09 | 0.123084E+10 | 0.949781E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.618964E+09 | 0.441917E+09 | 0.177047E+09 | 0.569302E+09 | 0.687589E+09 |
February | 0.702372E+09 | 0.502415E+09 | 0.199958E+09 | 0.714546E+09 | 0.460151E+09 |
March | 0.695547E+09 | 0.386690E+09 | 0.308857E+09 | 0.708215E+09 | 0.445357E+09 |
April | 0.553957E+09 | 0.268075E+09 | 0.285882E+09 | 0.599110E+09 | 0.302692E+09 |
May | 0.507476E+09 | 0.171490E+09 | 0.335986E+09 | 0.567509E+09 | 0.236264E+09 |
June | 0.481353E+09 | 0.138721E+09 | 0.342632E+09 | 0.624514E+09 | 0.134815E+09 |
July | 0.537691E+09 | 0.197866E+09 | 0.339825E+09 | 0.781961E+09 | 96544077.53 |
August | 0.631510E+09 | 0.313955E+09 | 0.317555E+09 | 0.878175E+09 | 0.114198E+09 |
September | 0.686432E+09 | 0.420183E+09 | 0.266248E+09 | 0.871686E+09 | 0.182825E+09 |
October | 0.748733E+09 | 0.519504E+09 | 0.229229E+09 | 0.861540E+09 | 0.298304E+09 |
November | 0.654596E+09 | 0.473885E+09 | 0.180711E+09 | 0.680928E+09 | 0.402229E+09 |
December | 0.588313E+09 | 0.424885E+09 | 0.163428E+09 | 0.555835E+09 | 0.581876E+09 |
Annual Sum or Average | 0.740694E+10 | 0.425959E+10 | 0.314736E+10 | 0.841332E+10 | 0.394285E+10 |
Minimum of Months | 0.481353E+09 | 0.138721E+09 | 0.163428E+09 | 0.555835E+09 | 96544077.53 |
Maximum of Months | 0.748733E+09 | 0.519504E+09 | 0.342632E+09 | 0.878175E+09 | 0.687589E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.418966E+09 | 0.00 | 0.418966E+09 | 1970969.81 | 0.416097E+10 |
February | 0.534308E+09 | 0.00 | 0.534308E+09 | 47572025.16 | 0.284028E+10 |
March | 0.961048E+09 | 30789.34 | 0.961017E+09 | 0.258709E+09 | 0.250765E+10 |
April | 0.106647E+10 | 10224116.70 | 0.105625E+10 | 0.514819E+09 | 0.165860E+10 |
May | 0.143660E+10 | 82604480.53 | 0.135400E+10 | 0.104507E+10 | 0.124932E+10 |
June | 0.162607E+10 | 0.190634E+09 | 0.143544E+10 | 0.169760E+10 | 0.695946E+09 |
July | 0.153303E+10 | 0.145530E+09 | 0.138750E+10 | 0.194866E+10 | 0.554888E+09 |
August | 0.123818E+10 | 42724044.28 | 0.119545E+10 | 0.142593E+10 | 0.657227E+09 |
September | 0.890437E+09 | 1205589.69 | 0.889231E+09 | 0.777791E+09 | 0.107950E+10 |
October | 0.670064E+09 | 0.00 | 0.670064E+09 | 0.269824E+09 | 0.176403E+10 |
November | 0.440821E+09 | 0.00 | 0.440821E+09 | 47156855.59 | 0.257110E+10 |
December | 0.351327E+09 | 0.00 | 0.351327E+09 | 1657106.30 | 0.364415E+10 |
Annual Sum or Average | 0.111673E+11 | 0.472952E+09 | 0.106944E+11 | 0.803677E+10 | 0.233837E+11 |
Minimum of Months | 0.351327E+09 | 0.00 | 0.351327E+09 | 1657106.30 | 0.554888E+09 |
Maximum of Months | 0.162607E+10 | 0.190634E+09 | 0.143544E+10 | 0.194866E+10 | 0.416097E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.418966E+09 | 0.00 | 0.418966E+09 | 1096289.03 | 0.423620E+10 |
February | 0.534308E+09 | 0.00 | 0.534308E+09 | 39910145.18 | 0.290881E+10 |
March | 0.961048E+09 | 30789.34 | 0.961017E+09 | 0.237592E+09 | 0.256438E+10 |
April | 0.106647E+10 | 10224116.70 | 0.105625E+10 | 0.490056E+09 | 0.169751E+10 |
May | 0.143660E+10 | 82604480.53 | 0.135400E+10 | 0.101641E+10 | 0.127757E+10 |
June | 0.162607E+10 | 0.190634E+09 | 0.143544E+10 | 0.167327E+10 | 0.709936E+09 |
July | 0.153303E+10 | 0.145530E+09 | 0.138750E+10 | 0.192849E+10 | 0.567586E+09 |
August | 0.123818E+10 | 42724044.28 | 0.119545E+10 | 0.140592E+10 | 0.673630E+09 |
September | 0.890437E+09 | 1205589.69 | 0.889231E+09 | 0.758250E+09 | 0.110625E+10 |
October | 0.670064E+09 | 0.00 | 0.670064E+09 | 0.250016E+09 | 0.180759E+10 |
November | 0.440821E+09 | 0.00 | 0.440821E+09 | 39637440.15 | 0.263937E+10 |
December | 0.351327E+09 | 0.00 | 0.351327E+09 | 1055608.46 | 0.372916E+10 |
Annual Sum or Average | 0.111673E+11 | 0.472952E+09 | 0.106944E+11 | 0.784171E+10 | 0.239180E+11 |
Minimum of Months | 0.351327E+09 | 0.00 | 0.351327E+09 | 1055608.46 | 0.567586E+09 |
Maximum of Months | 0.162607E+10 | 0.190634E+09 | 0.143544E+10 | 0.192849E+10 | 0.423620E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 59854623.75 | 0.00 | 59854623.75 | 2287519.65 | 0.521506E+09 |
February | 76332549.51 | 0.00 | 76332549.51 | 17962803.13 | 0.351320E+09 |
March | 0.137298E+09 | 4398.64 | 0.137293E+09 | 64552970.58 | 0.311124E+09 |
April | 0.152359E+09 | 1460643.42 | 0.150898E+09 | 0.116673E+09 | 0.205344E+09 |
May | 0.205237E+09 | 11801087.02 | 0.193436E+09 | 0.211662E+09 | 0.160264E+09 |
June | 0.232305E+09 | 27234410.10 | 0.205070E+09 | 0.320507E+09 | 95095343.33 |
July | 0.219012E+09 | 20790737.71 | 0.198222E+09 | 0.360369E+09 | 74725036.49 |
August | 0.176889E+09 | 6103666.06 | 0.170785E+09 | 0.278794E+09 | 84634532.08 |
September | 0.127210E+09 | 172233.62 | 0.127038E+09 | 0.165118E+09 | 0.130574E+09 |
October | 95727014.26 | 0.00 | 95727014.26 | 73467095.44 | 0.209335E+09 |
November | 62976875.21 | 0.00 | 62976875.21 | 18307368.50 | 0.305587E+09 |
December | 50191471.95 | 0.00 | 50191471.95 | 2277064.08 | 0.447193E+09 |
Annual Sum or Average | 0.159539E+10 | 67567176.57 | 0.152783E+10 | 0.163198E+10 | 0.289670E+10 |
Minimum of Months | 50191471.95 | 0.00 | 50191471.95 | 2277064.08 | 74725036.49 |
Maximum of Months | 0.232305E+09 | 27234410.10 | 0.205070E+09 | 0.360369E+09 | 0.521506E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.517037E+09 | 0.238651E+09 | 0.278386E+09 | 0.293308E+09 | 0.180956E+10 |
February | 0.731578E+09 | 0.365685E+09 | 0.365894E+09 | 0.599510E+09 | 0.121183E+10 |
March | 0.108534E+10 | 0.451600E+09 | 0.633742E+09 | 0.986524E+09 | 0.109907E+10 |
April | 0.133676E+10 | 0.664089E+09 | 0.672668E+09 | 0.148440E+10 | 0.743863E+09 |
May | 0.152276E+10 | 0.678572E+09 | 0.844185E+09 | 0.183778E+10 | 0.601336E+09 |
June | 0.190461E+10 | 0.979909E+09 | 0.924702E+09 | 0.262515E+10 | 0.358146E+09 |
July | 0.206588E+10 | 0.116788E+10 | 0.898006E+09 | 0.306956E+10 | 0.279722E+09 |
August | 0.180078E+10 | 0.100458E+10 | 0.796207E+09 | 0.262871E+10 | 0.314520E+09 |
September | 0.123157E+10 | 0.635919E+09 | 0.595654E+09 | 0.166052E+10 | 0.468521E+09 |
October | 0.908544E+09 | 0.459268E+09 | 0.449277E+09 | 0.101676E+10 | 0.745397E+09 |
November | 0.560099E+09 | 0.261686E+09 | 0.298412E+09 | 0.450757E+09 | 0.105860E+10 |
December | 0.426892E+09 | 0.183955E+09 | 0.242937E+09 | 0.236322E+09 | 0.155523E+10 |
Annual Sum or Average | 0.140919E+11 | 0.709179E+10 | 0.700007E+10 | 0.168893E+11 | 0.102458E+11 |
Minimum of Months | 0.426892E+09 | 0.183955E+09 | 0.242937E+09 | 0.236322E+09 | 0.279722E+09 |
Maximum of Months | 0.206588E+10 | 0.116788E+10 | 0.924702E+09 | 0.306956E+10 | 0.180956E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.422041E+09 | 0.301322E+09 | 0.120720E+09 | 0.415391E+09 | 0.448820E+09 |
February | 0.478913E+09 | 0.342572E+09 | 0.136341E+09 | 0.521681E+09 | 0.307088E+09 |
March | 0.474259E+09 | 0.263665E+09 | 0.210595E+09 | 0.520808E+09 | 0.298683E+09 |
April | 0.377716E+09 | 0.182787E+09 | 0.194929E+09 | 0.451367E+09 | 0.208308E+09 |
May | 0.346023E+09 | 0.116931E+09 | 0.229093E+09 | 0.438345E+09 | 0.169168E+09 |
June | 0.328211E+09 | 94587131.19 | 0.233624E+09 | 0.486005E+09 | 0.104669E+09 |
July | 0.366625E+09 | 0.134915E+09 | 0.231710E+09 | 0.602116E+09 | 78980356.28 |
August | 0.430596E+09 | 0.214070E+09 | 0.216526E+09 | 0.666470E+09 | 88158549.73 |
September | 0.468044E+09 | 0.286502E+09 | 0.181542E+09 | 0.650451E+09 | 0.129209E+09 |
October | 0.510524E+09 | 0.354224E+09 | 0.156300E+09 | 0.636363E+09 | 0.201227E+09 |
November | 0.446337E+09 | 0.323119E+09 | 0.123218E+09 | 0.501730E+09 | 0.268833E+09 |
December | 0.401142E+09 | 0.289708E+09 | 0.111434E+09 | 0.406960E+09 | 0.385430E+09 |
Annual Sum or Average | 0.505043E+10 | 0.290440E+10 | 0.214603E+10 | 0.629769E+10 | 0.268857E+10 |
Minimum of Months | 0.328211E+09 | 94587131.19 | 0.111434E+09 | 0.406960E+09 | 78980356.28 |
Maximum of Months | 0.510524E+09 | 0.354224E+09 | 0.233624E+09 | 0.666470E+09 | 0.448820E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 75802104.36 | 0.00 | 75802104.36 | 807794.01 | 0.726752E+09 |
February | 96670357.63 | 0.00 | 96670357.63 | 11375477.73 | 0.480099E+09 |
March | 0.173879E+09 | 5570.60 | 0.173873E+09 | 54628867.13 | 0.416850E+09 |
April | 0.192953E+09 | 1849812.73 | 0.191103E+09 | 0.104361E+09 | 0.270356E+09 |
May | 0.259920E+09 | 14945332.10 | 0.244974E+09 | 0.203257E+09 | 0.205646E+09 |
June | 0.294199E+09 | 34490662.00 | 0.259709E+09 | 0.313692E+09 | 0.120684E+09 |
July | 0.277365E+09 | 26330157.48 | 0.251035E+09 | 0.352295E+09 | 0.100094E+09 |
August | 0.224019E+09 | 7729907.95 | 0.216289E+09 | 0.258407E+09 | 0.116427E+09 |
September | 0.161103E+09 | 218123.01 | 0.160885E+09 | 0.144783E+09 | 0.181395E+09 |
October | 0.121232E+09 | 0.00 | 0.121232E+09 | 55646676.94 | 0.289399E+09 |
November | 79756238.83 | 0.00 | 79756238.83 | 12026161.39 | 0.425636E+09 |
December | 63564332.31 | 0.00 | 63564332.31 | 674372.60 | 0.619969E+09 |
Annual Sum or Average | 0.202046E+10 | 85569565.88 | 0.193489E+10 | 0.151196E+10 | 0.395331E+10 |
Minimum of Months | 63564332.31 | 0.00 | 63564332.31 | 674372.60 | 0.100094E+09 |
Maximum of Months | 0.294199E+09 | 34490662.00 | 0.259709E+09 | 0.352295E+09 | 0.726752E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 67820429.98 | 0.00 | 67820429.98 | 722736.36 | 0.650150E+09 |
February | 86491335.26 | 0.00 | 86491335.26 | 10177683.03 | 0.429538E+09 |
March | 0.155570E+09 | 4984.04 | 0.155565E+09 | 48876654.41 | 0.372957E+09 |
April | 0.172636E+09 | 1655034.46 | 0.170981E+09 | 93372424.23 | 0.241888E+09 |
May | 0.232551E+09 | 13371645.26 | 0.219180E+09 | 0.181855E+09 | 0.183992E+09 |
June | 0.263221E+09 | 30858925.97 | 0.232362E+09 | 0.280661E+09 | 0.107977E+09 |
July | 0.248160E+09 | 23557691.67 | 0.224602E+09 | 0.315200E+09 | 89554521.92 |
August | 0.200431E+09 | 6915977.93 | 0.193515E+09 | 0.231198E+09 | 0.104168E+09 |
September | 0.144140E+09 | 195155.49 | 0.143945E+09 | 0.129538E+09 | 0.162295E+09 |
October | 0.108467E+09 | 0.00 | 0.108467E+09 | 49787292.70 | 0.258926E+09 |
November | 71358209.08 | 0.00 | 71358209.08 | 10759852.16 | 0.380782E+09 |
December | 56871248.96 | 0.00 | 56871248.96 | 603363.72 | 0.554609E+09 |
Annual Sum or Average | 0.180772E+10 | 76559414.81 | 0.173116E+10 | 0.135275E+10 | 0.353684E+10 |
Minimum of Months | 56871248.96 | 0.00 | 56871248.96 | 603363.72 | 89554521.92 |
Maximum of Months | 0.263221E+09 | 30858925.97 | 0.232362E+09 | 0.315200E+09 | 0.650150E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.157561E+10 | 0.112492E+10 | 0.450683E+09 | 0.146865E+10 | 0.179447E+10 |
February | 0.178793E+10 | 0.127892E+10 | 0.509003E+09 | 0.184737E+10 | 0.119311E+10 |
March | 0.177055E+10 | 0.984339E+09 | 0.786213E+09 | 0.182650E+10 | 0.115937E+10 |
April | 0.141013E+10 | 0.682399E+09 | 0.727728E+09 | 0.153860E+10 | 0.806971E+09 |
May | 0.129181E+10 | 0.436536E+09 | 0.855271E+09 | 0.144390E+10 | 0.650366E+09 |
June | 0.122531E+10 | 0.353122E+09 | 0.872188E+09 | 0.155643E+10 | 0.410001E+09 |
July | 0.136872E+10 | 0.503679E+09 | 0.865042E+09 | 0.194388E+10 | 0.321981E+09 |
August | 0.160754E+10 | 0.799189E+09 | 0.808354E+09 | 0.220644E+10 | 0.366240E+09 |
September | 0.174735E+10 | 0.106960E+10 | 0.677750E+09 | 0.221860E+10 | 0.522875E+09 |
October | 0.190594E+10 | 0.132242E+10 | 0.583516E+09 | 0.221946E+10 | 0.790045E+09 |
November | 0.166631E+10 | 0.120630E+10 | 0.460009E+09 | 0.176291E+10 | 0.104664E+10 |
December | 0.149758E+10 | 0.108157E+10 | 0.416015E+09 | 0.143643E+10 | 0.151983E+10 |
Annual Sum or Average | 0.188548E+11 | 0.108430E+11 | 0.801177E+10 | 0.214692E+11 | 0.105819E+11 |
Minimum of Months | 0.122531E+10 | 0.353122E+09 | 0.416015E+09 | 0.143643E+10 | 0.321981E+09 |
Maximum of Months | 0.190594E+10 | 0.132242E+10 | 0.872188E+09 | 0.221946E+10 | 0.179447E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 754.34 | 839.77 | 796.96 | 569.00 | 227.96 | 0.00 | 0.00 |
February | 1041.01 | 626.55 | 1001.24 | 716.20 | 285.04 | 0.00 | 0.00 |
March | 931.96 | 550.67 | 895.56 | 497.89 | 397.67 | 0.00 | 0.00 |
April | 806.38 | 395.06 | 737.03 | 356.67 | 380.36 | 0.00 | 0.00 |
May | 737.87 | 302.53 | 653.41 | 220.80 | 432.60 | 0.00 | 0.00 |
June | 823.51 | 192.84 | 640.43 | 184.57 | 455.86 | 0.00 | 0.00 |
July | 984.73 | 150.36 | 692.31 | 254.77 | 437.54 | 0.00 | 0.00 |
August | 1115.49 | 173.10 | 813.11 | 404.24 | 408.87 | 0.00 | 0.00 |
September | 1159.17 | 258.65 | 913.28 | 559.05 | 354.24 | 0.00 | 0.00 |
October | 1120.16 | 382.36 | 964.04 | 668.90 | 295.15 | 0.00 | 0.00 |
November | 921.76 | 515.58 | 870.93 | 630.50 | 240.43 | 0.00 | 0.00 |
December | 735.31 | 716.20 | 757.49 | 547.07 | 210.42 | 0.00 | 0.00 |
Annual Sum or Average | 926.71 | 424.58 | 809.98 | 465.81 | 344.18 | 0.00 | 0.00 |
Minimum of Months | 735.31 | 150.36 | 640.43 | 184.57 | 210.42 | 0.00 | 0.00 |
Maximum of Months | 1159.17 | 839.77 | 1001.24 | 716.20 | 455.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2103.03 | 2408.80 | 2244.18 | 1602.26 | 641.92 | 0.00 | 0.00 |
February | 2899.71 | 1826.43 | 2819.44 | 2016.78 | 802.66 | 0.00 | 0.00 |
March | 2594.49 | 1620.10 | 2521.84 | 1402.02 | 1119.82 | 0.00 | 0.00 |
April | 2239.50 | 1184.14 | 2075.42 | 1004.36 | 1071.07 | 0.00 | 0.00 |
May | 2040.48 | 916.92 | 1839.95 | 621.77 | 1218.17 | 0.00 | 0.00 |
June | 2280.78 | 594.49 | 1803.40 | 519.73 | 1283.68 | 0.00 | 0.00 |
July | 2743.69 | 457.53 | 1949.49 | 717.40 | 1232.09 | 0.00 | 0.00 |
August | 3113.83 | 527.63 | 2289.66 | 1138.31 | 1151.35 | 0.00 | 0.00 |
September | 3234.58 | 787.57 | 2571.75 | 1574.24 | 997.51 | 0.00 | 0.00 |
October | 3121.35 | 1156.21 | 2714.68 | 1883.57 | 831.11 | 0.00 | 0.00 |
November | 2562.60 | 1527.64 | 2452.48 | 1775.44 | 677.04 | 0.00 | 0.00 |
December | 2046.61 | 2068.13 | 2133.05 | 1540.51 | 592.54 | 0.00 | 0.00 |
Annual Sum or Average | 2579.13 | 1254.17 | 2280.86 | 1311.68 | 969.18 | 0.00 | 0.00 |
Minimum of Months | 2040.48 | 457.53 | 1803.40 | 519.73 | 592.54 | 0.00 | 0.00 |
Maximum of Months | 3234.58 | 2408.80 | 2819.44 | 2016.78 | 1283.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2765.74 | 3264.02 | 2915.31 | 2081.43 | 833.89 | 0.00 | 0.00 |
February | 3817.85 | 2476.85 | 3662.61 | 2619.91 | 1042.70 | 0.00 | 0.00 |
March | 3413.31 | 2210.58 | 3276.01 | 1821.31 | 1454.71 | 0.00 | 0.00 |
April | 2948.31 | 1629.86 | 2696.09 | 1304.72 | 1391.37 | 0.00 | 0.00 |
May | 2683.80 | 1264.48 | 2390.19 | 807.72 | 1582.48 | 0.00 | 0.00 |
June | 3008.37 | 807.88 | 2342.72 | 675.15 | 1667.57 | 0.00 | 0.00 |
July | 3627.00 | 610.31 | 2532.50 | 931.95 | 1600.55 | 0.00 | 0.00 |
August | 4112.10 | 703.36 | 2974.39 | 1478.73 | 1495.67 | 0.00 | 0.00 |
September | 4261.90 | 1062.53 | 3340.85 | 2045.03 | 1295.82 | 0.00 | 0.00 |
October | 4104.00 | 1573.12 | 3526.52 | 2446.86 | 1079.66 | 0.00 | 0.00 |
November | 3361.22 | 2092.42 | 3185.91 | 2306.40 | 879.51 | 0.00 | 0.00 |
December | 2681.68 | 2830.23 | 2770.95 | 2001.21 | 769.74 | 0.00 | 0.00 |
Annual Sum or Average | 3395.37 | 1707.59 | 2962.97 | 1703.95 | 1259.02 | 0.00 | 0.00 |
Minimum of Months | 2681.68 | 610.31 | 2342.72 | 675.15 | 769.74 | 0.00 | 0.00 |
Maximum of Months | 4261.90 | 3264.02 | 3662.61 | 2619.91 | 1667.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 167.86 | 502.43 | 244.76 | 147.81 | 96.95 | 0.00 | 0.00 |
February | 304.21 | 368.79 | 347.42 | 215.67 | 131.75 | 0.00 | 0.00 |
March | 332.55 | 317.06 | 367.49 | 168.63 | 198.86 | 0.00 | 0.00 |
April | 405.90 | 221.60 | 393.63 | 180.17 | 213.45 | 0.00 | 0.00 |
May | 483.96 | 168.55 | 435.79 | 183.76 | 252.02 | 0.00 | 0.00 |
June | 579.24 | 101.71 | 459.24 | 189.05 | 270.19 | 0.00 | 0.00 |
July | 661.64 | 74.21 | 477.74 | 222.48 | 255.26 | 0.00 | 0.00 |
August | 606.19 | 85.27 | 450.54 | 222.00 | 228.54 | 0.00 | 0.00 |
September | 510.57 | 137.88 | 414.02 | 228.56 | 185.46 | 0.00 | 0.00 |
October | 383.98 | 215.73 | 357.54 | 215.27 | 142.26 | 0.00 | 0.00 |
November | 262.11 | 301.99 | 290.35 | 183.37 | 106.98 | 0.00 | 0.00 |
December | 165.98 | 424.13 | 228.73 | 141.38 | 87.35 | 0.00 | 0.00 |
Annual Sum or Average | 405.81 | 242.82 | 372.29 | 191.27 | 181.01 | 0.00 | 0.00 |
Minimum of Months | 165.98 | 74.21 | 228.73 | 141.38 | 87.35 | 0.00 | 0.00 |
Maximum of Months | 661.64 | 502.43 | 477.74 | 228.56 | 270.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 39.94 | 547.58 | 109.54 | 35.31 | 74.23 | 0.00 | 0.00 |
February | 117.06 | 394.98 | 181.01 | 74.06 | 106.95 | 0.00 | 0.00 |
March | 174.05 | 321.54 | 241.68 | 70.19 | 171.49 | 0.00 | 0.00 |
April | 282.51 | 220.68 | 306.68 | 110.22 | 196.46 | 0.00 | 0.00 |
May | 398.75 | 166.73 | 383.22 | 144.51 | 238.71 | 0.00 | 0.00 |
June | 507.54 | 98.55 | 422.24 | 163.07 | 259.17 | 0.00 | 0.00 |
July | 565.93 | 73.57 | 422.63 | 179.87 | 242.76 | 0.00 | 0.00 |
August | 459.45 | 86.13 | 355.82 | 144.35 | 211.47 | 0.00 | 0.00 |
September | 328.30 | 140.58 | 282.53 | 118.10 | 164.43 | 0.00 | 0.00 |
October | 187.08 | 221.21 | 202.67 | 83.02 | 119.65 | 0.00 | 0.00 |
November | 96.36 | 323.85 | 142.45 | 58.71 | 83.74 | 0.00 | 0.00 |
December | 38.27 | 461.68 | 97.70 | 33.21 | 64.49 | 0.00 | 0.00 |
Annual Sum or Average | 267.09 | 254.25 | 262.73 | 101.32 | 161.41 | 0.00 | 0.00 |
Minimum of Months | 38.27 | 73.57 | 97.70 | 33.21 | 64.49 | 0.00 | 0.00 |
Maximum of Months | 565.93 | 547.58 | 422.63 | 179.87 | 259.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 118.31 | 137.53 | 126.03 | 89.98 | 36.05 | 0.00 | 0.00 |
February | 160.23 | 108.74 | 158.34 | 113.26 | 45.08 | 0.00 | 0.00 |
March | 138.57 | 107.85 | 141.63 | 78.74 | 62.89 | 0.00 | 0.00 |
April | 118.24 | 83.94 | 116.56 | 56.40 | 60.15 | 0.00 | 0.00 |
May | 105.96 | 66.25 | 103.33 | 34.92 | 68.41 | 0.00 | 0.00 |
June | 118.96 | 44.81 | 101.28 | 29.19 | 72.09 | 0.00 | 0.00 |
July | 146.38 | 34.96 | 109.48 | 40.29 | 69.19 | 0.00 | 0.00 |
August | 167.53 | 40.07 | 128.59 | 63.93 | 64.66 | 0.00 | 0.00 |
September | 174.01 | 57.91 | 144.43 | 88.41 | 56.02 | 0.00 | 0.00 |
October | 167.11 | 81.97 | 152.46 | 105.78 | 46.68 | 0.00 | 0.00 |
November | 136.59 | 103.52 | 137.73 | 99.71 | 38.02 | 0.00 | 0.00 |
December | 111.18 | 126.40 | 119.79 | 86.51 | 33.28 | 0.00 | 0.00 |
Annual Sum or Average | 138.43 | 82.73 | 128.09 | 73.66 | 54.43 | 0.00 | 0.00 |
Minimum of Months | 105.96 | 34.96 | 101.28 | 29.19 | 33.28 | 0.00 | 0.00 |
Maximum of Months | 174.01 | 137.53 | 158.34 | 113.26 | 72.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.30 | 165.42 | 17.88 | 0.00 | 17.88 | 0.00 | 0.00 |
February | 3.97 | 120.32 | 25.25 | 0.00 | 25.25 | 0.00 | 0.00 |
March | 14.66 | 95.00 | 41.01 | 0.00 | 41.01 | 0.00 | 0.00 |
April | 27.53 | 62.98 | 47.03 | 0.45 | 46.58 | 0.00 | 0.00 |
May | 50.75 | 45.59 | 61.31 | 3.53 | 57.78 | 0.00 | 0.00 |
June | 82.10 | 25.58 | 71.71 | 8.41 | 63.30 | 0.00 | 0.00 |
July | 89.92 | 18.57 | 65.42 | 6.21 | 59.21 | 0.00 | 0.00 |
August | 67.00 | 22.08 | 52.84 | 1.82 | 51.02 | 0.00 | 0.00 |
September | 39.31 | 38.95 | 39.27 | 0.05 | 39.21 | 0.00 | 0.00 |
October | 15.26 | 64.16 | 28.60 | 0.00 | 28.60 | 0.00 | 0.00 |
November | 3.46 | 99.11 | 19.44 | 0.00 | 19.44 | 0.00 | 0.00 |
December | 0.25 | 140.91 | 14.99 | 0.00 | 14.99 | 0.00 | 0.00 |
Annual Sum or Average | 33.06 | 74.71 | 40.48 | 1.71 | 38.76 | 0.00 | 0.00 |
Minimum of Months | 0.25 | 18.57 | 14.99 | 0.00 | 14.99 | 0.00 | 0.00 |
Maximum of Months | 89.92 | 165.42 | 71.71 | 8.41 | 63.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 178.09 | 497.38 | 254.10 | 157.05 | 97.04 | 0.00 | 0.00 |
February | 303.41 | 364.03 | 349.18 | 217.19 | 131.99 | 0.00 | 0.00 |
March | 344.69 | 312.21 | 379.69 | 182.75 | 196.94 | 0.00 | 0.00 |
April | 410.46 | 213.34 | 403.60 | 198.63 | 204.97 | 0.00 | 0.00 |
May | 447.62 | 161.78 | 413.48 | 170.34 | 243.14 | 0.00 | 0.00 |
June | 617.76 | 93.69 | 494.05 | 225.53 | 268.52 | 0.00 | 0.00 |
July | 715.31 | 67.96 | 522.57 | 268.40 | 254.16 | 0.00 | 0.00 |
August | 661.18 | 79.68 | 496.96 | 267.47 | 229.49 | 0.00 | 0.00 |
September | 509.92 | 132.54 | 418.16 | 233.21 | 184.95 | 0.00 | 0.00 |
October | 383.50 | 211.57 | 360.23 | 217.99 | 142.23 | 0.00 | 0.00 |
November | 245.23 | 297.28 | 280.25 | 175.14 | 105.11 | 0.00 | 0.00 |
December | 166.91 | 420.86 | 229.47 | 142.51 | 86.96 | 0.00 | 0.00 |
Annual Sum or Average | 415.93 | 237.24 | 383.59 | 204.55 | 179.04 | 0.00 | 0.00 |
Minimum of Months | 166.91 | 67.96 | 229.47 | 142.51 | 86.96 | 0.00 | 0.00 |
Maximum of Months | 715.31 | 497.38 | 522.57 | 268.40 | 268.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 40.26 | 532.12 | 118.87 | 44.55 | 74.32 | 0.00 | 0.00 |
February | 110.72 | 384.33 | 182.77 | 75.59 | 107.18 | 0.00 | 0.00 |
March | 181.35 | 312.49 | 253.89 | 84.31 | 169.57 | 0.00 | 0.00 |
April | 286.78 | 211.43 | 316.66 | 128.68 | 187.98 | 0.00 | 0.00 |
May | 365.21 | 160.29 | 360.91 | 131.09 | 229.82 | 0.00 | 0.00 |
June | 550.72 | 94.27 | 457.05 | 199.55 | 257.51 | 0.00 | 0.00 |
July | 621.53 | 70.97 | 467.45 | 225.80 | 241.66 | 0.00 | 0.00 |
August | 515.80 | 81.92 | 402.23 | 189.83 | 212.41 | 0.00 | 0.00 |
September | 325.95 | 133.14 | 286.67 | 122.74 | 163.92 | 0.00 | 0.00 |
October | 181.17 | 211.38 | 205.36 | 85.74 | 119.62 | 0.00 | 0.00 |
November | 74.10 | 313.38 | 132.35 | 50.48 | 81.86 | 0.00 | 0.00 |
December | 30.95 | 449.76 | 98.44 | 34.34 | 64.09 | 0.00 | 0.00 |
Annual Sum or Average | 274.66 | 245.79 | 274.03 | 114.59 | 159.44 | 0.00 | 0.00 |
Minimum of Months | 30.95 | 70.97 | 98.44 | 34.34 | 64.09 | 0.00 | 0.00 |
Maximum of Months | 621.53 | 532.12 | 467.45 | 225.80 | 257.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 216.01 | 633.61 | 311.81 | 194.97 | 116.84 | 0.00 | 0.00 |
February | 338.69 | 466.04 | 397.77 | 245.41 | 152.36 | 0.00 | 0.00 |
March | 346.22 | 403.70 | 395.72 | 170.60 | 225.11 | 0.00 | 0.00 |
April | 337.79 | 283.71 | 354.43 | 123.19 | 231.24 | 0.00 | 0.00 |
May | 361.12 | 211.38 | 356.71 | 83.30 | 273.41 | 0.00 | 0.00 |
June | 449.60 | 129.84 | 374.79 | 81.45 | 293.34 | 0.00 | 0.00 |
July | 522.41 | 101.89 | 378.95 | 100.75 | 278.20 | 0.00 | 0.00 |
August | 521.31 | 120.61 | 393.08 | 142.46 | 250.62 | 0.00 | 0.00 |
September | 479.49 | 188.94 | 398.00 | 191.67 | 206.33 | 0.00 | 0.00 |
October | 412.22 | 277.83 | 392.28 | 229.20 | 163.08 | 0.00 | 0.00 |
November | 299.35 | 379.76 | 340.54 | 216.04 | 124.50 | 0.00 | 0.00 |
December | 214.47 | 535.23 | 292.04 | 187.45 | 104.58 | 0.00 | 0.00 |
Annual Sum or Average | 375.00 | 310.49 | 365.23 | 163.32 | 201.91 | 0.00 | 0.00 |
Minimum of Months | 214.47 | 101.89 | 292.04 | 81.45 | 104.58 | 0.00 | 0.00 |
Maximum of Months | 522.41 | 633.61 | 398.00 | 245.41 | 293.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 168.00 | 501.71 | 244.76 | 147.81 | 96.95 | 0.00 | 0.00 |
February | 303.97 | 367.55 | 347.42 | 215.67 | 131.75 | 0.00 | 0.00 |
March | 331.36 | 315.66 | 367.49 | 168.63 | 198.86 | 0.00 | 0.00 |
April | 404.09 | 219.88 | 393.63 | 180.17 | 213.45 | 0.00 | 0.00 |
May | 480.81 | 167.56 | 435.79 | 183.76 | 252.02 | 0.00 | 0.00 |
June | 575.83 | 100.57 | 459.24 | 189.05 | 270.19 | 0.00 | 0.00 |
July | 658.62 | 72.79 | 477.74 | 222.48 | 255.26 | 0.00 | 0.00 |
August | 603.55 | 83.52 | 450.54 | 222.00 | 228.54 | 0.00 | 0.00 |
September | 508.66 | 135.71 | 414.02 | 228.56 | 185.46 | 0.00 | 0.00 |
October | 383.47 | 213.13 | 357.54 | 215.27 | 142.26 | 0.00 | 0.00 |
November | 262.44 | 299.93 | 290.35 | 183.37 | 106.98 | 0.00 | 0.00 |
December | 166.80 | 422.22 | 228.73 | 141.38 | 87.35 | 0.00 | 0.00 |
Annual Sum or Average | 404.42 | 241.23 | 372.29 | 191.27 | 181.01 | 0.00 | 0.00 |
Minimum of Months | 166.80 | 72.79 | 228.73 | 141.38 | 87.35 | 0.00 | 0.00 |
Maximum of Months | 658.62 | 501.71 | 477.74 | 228.56 | 270.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 40.37 | 546.70 | 109.54 | 35.31 | 74.23 | 0.00 | 0.00 |
February | 117.85 | 393.34 | 181.01 | 74.06 | 106.95 | 0.00 | 0.00 |
March | 174.34 | 319.72 | 241.68 | 70.19 | 171.49 | 0.00 | 0.00 |
April | 281.44 | 219.11 | 306.68 | 110.22 | 196.46 | 0.00 | 0.00 |
May | 395.62 | 166.66 | 383.22 | 144.51 | 238.71 | 0.00 | 0.00 |
June | 503.89 | 98.58 | 422.24 | 163.07 | 259.17 | 0.00 | 0.00 |
July | 563.37 | 73.09 | 422.63 | 179.87 | 242.76 | 0.00 | 0.00 |
August | 457.53 | 85.21 | 355.82 | 144.35 | 211.47 | 0.00 | 0.00 |
September | 327.88 | 138.41 | 282.53 | 118.10 | 164.43 | 0.00 | 0.00 |
October | 188.39 | 217.77 | 202.67 | 83.02 | 119.65 | 0.00 | 0.00 |
November | 97.66 | 320.85 | 142.45 | 58.71 | 83.74 | 0.00 | 0.00 |
December | 39.09 | 459.18 | 97.70 | 33.21 | 64.49 | 0.00 | 0.00 |
Annual Sum or Average | 266.43 | 252.71 | 262.73 | 101.32 | 161.41 | 0.00 | 0.00 |
Minimum of Months | 39.09 | 73.09 | 97.70 | 33.21 | 64.49 | 0.00 | 0.00 |
Maximum of Months | 563.37 | 546.70 | 422.63 | 179.87 | 259.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 212.55 | 256.72 | 231.09 | 164.99 | 66.10 | 0.00 | 0.00 |
February | 295.36 | 190.21 | 290.33 | 207.68 | 82.65 | 0.00 | 0.00 |
March | 264.42 | 166.28 | 259.69 | 144.37 | 115.31 | 0.00 | 0.00 |
April | 231.14 | 116.78 | 213.72 | 103.42 | 110.29 | 0.00 | 0.00 |
May | 211.88 | 88.21 | 189.47 | 64.03 | 125.44 | 0.00 | 0.00 |
June | 240.94 | 52.01 | 185.71 | 53.52 | 132.19 | 0.00 | 0.00 |
July | 291.95 | 36.05 | 200.75 | 73.87 | 126.88 | 0.00 | 0.00 |
August | 327.87 | 42.64 | 235.78 | 117.22 | 118.56 | 0.00 | 0.00 |
September | 336.30 | 70.53 | 264.83 | 162.11 | 102.72 | 0.00 | 0.00 |
October | 321.66 | 111.37 | 279.54 | 193.96 | 85.58 | 0.00 | 0.00 |
November | 262.70 | 155.18 | 252.54 | 182.83 | 69.72 | 0.00 | 0.00 |
December | 207.53 | 217.25 | 219.65 | 158.63 | 61.02 | 0.00 | 0.00 |
Annual Sum or Average | 266.78 | 125.03 | 234.87 | 135.07 | 99.80 | 0.00 | 0.00 |
Minimum of Months | 207.53 | 36.05 | 185.71 | 53.52 | 61.02 | 0.00 | 0.00 |
Maximum of Months | 336.30 | 256.72 | 290.33 | 207.68 | 132.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.74 | 1553.53 | 156.42 | 0.00 | 156.42 | 0.00 | 0.00 |
February | 19.66 | 1174.06 | 220.86 | 0.00 | 220.86 | 0.00 | 0.00 |
March | 96.59 | 936.25 | 358.81 | 0.01 | 358.80 | 0.00 | 0.00 |
April | 198.62 | 639.89 | 411.45 | 3.94 | 407.50 | 0.00 | 0.00 |
May | 390.19 | 466.44 | 536.37 | 30.84 | 505.53 | 0.00 | 0.00 |
June | 654.94 | 268.50 | 627.34 | 73.55 | 553.80 | 0.00 | 0.00 |
July | 727.55 | 207.17 | 572.37 | 54.33 | 518.03 | 0.00 | 0.00 |
August | 532.38 | 245.38 | 462.28 | 15.95 | 446.33 | 0.00 | 0.00 |
September | 300.07 | 416.47 | 343.53 | 0.47 | 343.07 | 0.00 | 0.00 |
October | 100.74 | 658.61 | 250.17 | 0.00 | 250.17 | 0.00 | 0.00 |
November | 18.19 | 991.94 | 170.07 | 0.00 | 170.07 | 0.00 | 0.00 |
December | 0.62 | 1360.57 | 131.17 | 0.00 | 131.17 | 0.00 | 0.00 |
Annual Sum or Average | 254.84 | 741.49 | 354.11 | 15.00 | 339.12 | 0.00 | 0.00 |
Minimum of Months | 0.62 | 207.17 | 131.17 | 0.00 | 131.17 | 0.00 | 0.00 |
Maximum of Months | 727.55 | 1553.53 | 627.34 | 73.55 | 553.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.41 | 1581.61 | 156.42 | 0.00 | 156.42 | 0.00 | 0.00 |
February | 16.50 | 1202.38 | 220.86 | 0.00 | 220.86 | 0.00 | 0.00 |
March | 88.71 | 957.43 | 358.81 | 0.01 | 358.80 | 0.00 | 0.00 |
April | 189.06 | 654.90 | 411.45 | 3.94 | 407.50 | 0.00 | 0.00 |
May | 379.49 | 476.99 | 536.37 | 30.84 | 505.53 | 0.00 | 0.00 |
June | 645.55 | 273.90 | 627.34 | 73.55 | 553.80 | 0.00 | 0.00 |
July | 720.01 | 211.91 | 572.37 | 54.33 | 518.03 | 0.00 | 0.00 |
August | 524.91 | 251.50 | 462.28 | 15.95 | 446.33 | 0.00 | 0.00 |
September | 292.53 | 426.79 | 343.53 | 0.47 | 343.07 | 0.00 | 0.00 |
October | 93.35 | 674.88 | 250.17 | 0.00 | 250.17 | 0.00 | 0.00 |
November | 15.29 | 1018.28 | 170.07 | 0.00 | 170.07 | 0.00 | 0.00 |
December | 0.39 | 1392.31 | 131.17 | 0.00 | 131.17 | 0.00 | 0.00 |
Annual Sum or Average | 248.66 | 758.43 | 354.11 | 15.00 | 339.12 | 0.00 | 0.00 |
Minimum of Months | 0.39 | 211.91 | 131.17 | 0.00 | 131.17 | 0.00 | 0.00 |
Maximum of Months | 720.01 | 1581.61 | 627.34 | 73.55 | 553.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 219.02 | 991.46 | 372.96 | 201.60 | 171.36 | 0.00 | 0.00 |
February | 439.57 | 741.77 | 531.92 | 292.76 | 239.16 | 0.00 | 0.00 |
March | 579.54 | 630.69 | 633.55 | 267.05 | 366.50 | 0.00 | 0.00 |
April | 785.48 | 440.22 | 720.23 | 327.29 | 392.94 | 0.00 | 0.00 |
May | 924.50 | 343.17 | 774.35 | 301.41 | 472.94 | 0.00 | 0.00 |
June | 1320.22 | 211.52 | 951.05 | 425.05 | 526.00 | 0.00 | 0.00 |
July | 1503.78 | 160.21 | 989.96 | 494.17 | 495.80 | 0.00 | 0.00 |
August | 1332.71 | 180.29 | 899.14 | 457.27 | 441.87 | 0.00 | 0.00 |
September | 952.42 | 278.12 | 704.79 | 355.94 | 348.86 | 0.00 | 0.00 |
October | 639.73 | 426.68 | 565.56 | 303.72 | 261.84 | 0.00 | 0.00 |
November | 348.51 | 604.00 | 412.58 | 225.62 | 186.96 | 0.00 | 0.00 |
December | 201.06 | 851.56 | 327.89 | 176.85 | 151.05 | 0.00 | 0.00 |
Annual Sum or Average | 772.38 | 487.37 | 657.59 | 319.12 | 338.47 | 0.00 | 0.00 |
Minimum of Months | 201.06 | 160.21 | 327.89 | 176.85 | 151.05 | 0.00 | 0.00 |
Maximum of Months | 1503.78 | 991.46 | 989.96 | 494.17 | 526.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 486.48 | 1121.64 | 641.89 | 420.00 | 221.89 | 0.00 | 0.00 |
February | 730.53 | 827.19 | 814.77 | 528.66 | 286.11 | 0.00 | 0.00 |
March | 711.84 | 718.99 | 784.05 | 367.51 | 416.54 | 0.00 | 0.00 |
April | 668.70 | 507.77 | 685.08 | 264.62 | 420.45 | 0.00 | 0.00 |
May | 677.40 | 382.81 | 666.17 | 173.56 | 492.62 | 0.00 | 0.00 |
June | 819.35 | 235.97 | 687.78 | 161.45 | 526.33 | 0.00 | 0.00 |
July | 968.01 | 184.06 | 707.23 | 206.68 | 500.55 | 0.00 | 0.00 |
August | 1003.87 | 216.38 | 758.66 | 303.85 | 454.81 | 0.00 | 0.00 |
September | 960.09 | 332.64 | 791.90 | 412.81 | 379.08 | 0.00 | 0.00 |
October | 857.79 | 489.46 | 797.36 | 493.74 | 303.62 | 0.00 | 0.00 |
November | 648.14 | 674.13 | 701.17 | 465.39 | 235.77 | 0.00 | 0.00 |
December | 479.73 | 948.93 | 604.10 | 403.81 | 200.29 | 0.00 | 0.00 |
Annual Sum or Average | 750.91 | 552.35 | 719.27 | 348.97 | 370.30 | 0.00 | 0.00 |
Minimum of Months | 479.73 | 184.06 | 604.10 | 161.45 | 200.29 | 0.00 | 0.00 |
Maximum of Months | 1003.87 | 1121.64 | 814.77 | 528.66 | 526.33 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.202042E+10 | 0.224923E+10 | 0.213457E+10 | 0.152400E+10 | 0.610565E+09 | 0.00 | 0.00 |
February | 0.251842E+10 | 0.151576E+10 | 0.242221E+10 | 0.173264E+10 | 0.689573E+09 | 0.00 | 0.00 |
March | 0.249617E+10 | 0.147490E+10 | 0.239867E+10 | 0.133355E+10 | 0.106512E+10 | 0.00 | 0.00 |
April | 0.209014E+10 | 0.102399E+10 | 0.191038E+10 | 0.924488E+09 | 0.985890E+09 | 0.00 | 0.00 |
May | 0.197631E+10 | 0.810300E+09 | 0.175008E+10 | 0.591403E+09 | 0.115868E+10 | 0.00 | 0.00 |
June | 0.213453E+10 | 0.499833E+09 | 0.165999E+10 | 0.478396E+09 | 0.118159E+10 | 0.00 | 0.00 |
July | 0.263751E+10 | 0.402727E+09 | 0.185428E+10 | 0.682365E+09 | 0.117191E+10 | 0.00 | 0.00 |
August | 0.298772E+10 | 0.463631E+09 | 0.217783E+10 | 0.108271E+10 | 0.109512E+10 | 0.00 | 0.00 |
September | 0.300458E+10 | 0.670412E+09 | 0.236723E+10 | 0.144905E+10 | 0.918181E+09 | 0.00 | 0.00 |
October | 0.300024E+10 | 0.102412E+10 | 0.258209E+10 | 0.179157E+10 | 0.790519E+09 | 0.00 | 0.00 |
November | 0.238921E+10 | 0.133638E+10 | 0.225745E+10 | 0.163425E+10 | 0.623199E+09 | 0.00 | 0.00 |
December | 0.196946E+10 | 0.191827E+10 | 0.202887E+10 | 0.146527E+10 | 0.563599E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.292247E+11 | 0.133895E+11 | 0.255436E+11 | 0.146897E+11 | 0.108540E+11 | 0.00 | 0.00 |
Minimum of Months | 0.196946E+10 | 0.402727E+09 | 0.165999E+10 | 0.478396E+09 | 0.563599E+09 | 0.00 | 0.00 |
Maximum of Months | 0.300458E+10 | 0.224923E+10 | 0.258209E+10 | 0.179157E+10 | 0.118159E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.563276E+10 | 0.645174E+10 | 0.601080E+10 | 0.429149E+10 | 0.171931E+10 | 0.00 | 0.00 |
February | 0.701497E+10 | 0.441851E+10 | 0.682078E+10 | 0.487899E+10 | 0.194179E+10 | 0.00 | 0.00 |
March | 0.694908E+10 | 0.433927E+10 | 0.675449E+10 | 0.375518E+10 | 0.299932E+10 | 0.00 | 0.00 |
April | 0.580479E+10 | 0.306929E+10 | 0.537950E+10 | 0.260330E+10 | 0.277620E+10 | 0.00 | 0.00 |
May | 0.546523E+10 | 0.245588E+10 | 0.492811E+10 | 0.166535E+10 | 0.326276E+10 | 0.00 | 0.00 |
June | 0.591178E+10 | 0.154092E+10 | 0.467442E+10 | 0.134713E+10 | 0.332729E+10 | 0.00 | 0.00 |
July | 0.734869E+10 | 0.122544E+10 | 0.522152E+10 | 0.192149E+10 | 0.330003E+10 | 0.00 | 0.00 |
August | 0.834008E+10 | 0.141320E+10 | 0.613262E+10 | 0.304884E+10 | 0.308377E+10 | 0.00 | 0.00 |
September | 0.838404E+10 | 0.204138E+10 | 0.666597E+10 | 0.408043E+10 | 0.258554E+10 | 0.00 | 0.00 |
October | 0.836024E+10 | 0.309680E+10 | 0.727099E+10 | 0.504494E+10 | 0.222605E+10 | 0.00 | 0.00 |
November | 0.664225E+10 | 0.395964E+10 | 0.635682E+10 | 0.460194E+10 | 0.175489E+10 | 0.00 | 0.00 |
December | 0.548165E+10 | 0.553929E+10 | 0.571315E+10 | 0.412609E+10 | 0.158706E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.813356E+11 | 0.395514E+11 | 0.719292E+11 | 0.413652E+11 | 0.305640E+11 | 0.00 | 0.00 |
Minimum of Months | 0.546523E+10 | 0.122544E+10 | 0.467442E+10 | 0.134713E+10 | 0.158706E+10 | 0.00 | 0.00 |
Maximum of Months | 0.838404E+10 | 0.645174E+10 | 0.727099E+10 | 0.504494E+10 | 0.332729E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.740775E+10 | 0.874236E+10 | 0.780837E+10 | 0.557489E+10 | 0.223348E+10 | 0.00 | 0.00 |
February | 0.923613E+10 | 0.599198E+10 | 0.886058E+10 | 0.633808E+10 | 0.252250E+10 | 0.00 | 0.00 |
March | 0.914222E+10 | 0.592081E+10 | 0.877447E+10 | 0.487819E+10 | 0.389629E+10 | 0.00 | 0.00 |
April | 0.764201E+10 | 0.422459E+10 | 0.698827E+10 | 0.338183E+10 | 0.360644E+10 | 0.00 | 0.00 |
May | 0.718829E+10 | 0.338679E+10 | 0.640190E+10 | 0.216339E+10 | 0.423851E+10 | 0.00 | 0.00 |
June | 0.779771E+10 | 0.209403E+10 | 0.607234E+10 | 0.175000E+10 | 0.432234E+10 | 0.00 | 0.00 |
July | 0.971457E+10 | 0.163467E+10 | 0.678306E+10 | 0.249613E+10 | 0.428693E+10 | 0.00 | 0.00 |
August | 0.110138E+11 | 0.188387E+10 | 0.796662E+10 | 0.396062E+10 | 0.400600E+10 | 0.00 | 0.00 |
September | 0.110468E+11 | 0.275408E+10 | 0.865948E+10 | 0.530072E+10 | 0.335876E+10 | 0.00 | 0.00 |
October | 0.109922E+11 | 0.421344E+10 | 0.944543E+10 | 0.655367E+10 | 0.289177E+10 | 0.00 | 0.00 |
November | 0.871228E+10 | 0.542356E+10 | 0.825787E+10 | 0.597818E+10 | 0.227970E+10 | 0.00 | 0.00 |
December | 0.718262E+10 | 0.758050E+10 | 0.742171E+10 | 0.536003E+10 | 0.206168E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.107076E+12 | 0.538507E+11 | 0.934401E+11 | 0.537357E+11 | 0.397044E+11 | 0.00 | 0.00 |
Minimum of Months | 0.718262E+10 | 0.163467E+10 | 0.607234E+10 | 0.175000E+10 | 0.206168E+10 | 0.00 | 0.00 |
Maximum of Months | 0.110468E+11 | 0.874236E+10 | 0.944543E+10 | 0.655367E+10 | 0.432234E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.449604E+09 | 0.134570E+10 | 0.655571E+09 | 0.395888E+09 | 0.259684E+09 | 0.00 | 0.00 |
February | 0.735935E+09 | 0.892176E+09 | 0.840475E+09 | 0.521738E+09 | 0.318736E+09 | 0.00 | 0.00 |
March | 0.890692E+09 | 0.849225E+09 | 0.984273E+09 | 0.451654E+09 | 0.532619E+09 | 0.00 | 0.00 |
April | 0.105208E+10 | 0.574384E+09 | 0.102028E+10 | 0.467013E+09 | 0.553266E+09 | 0.00 | 0.00 |
May | 0.129625E+10 | 0.451451E+09 | 0.116721E+10 | 0.492189E+09 | 0.675019E+09 | 0.00 | 0.00 |
June | 0.150138E+10 | 0.263624E+09 | 0.119035E+10 | 0.490020E+09 | 0.700328E+09 | 0.00 | 0.00 |
July | 0.177213E+10 | 0.198752E+09 | 0.127957E+10 | 0.595887E+09 | 0.683688E+09 | 0.00 | 0.00 |
August | 0.162363E+10 | 0.228389E+09 | 0.120673E+10 | 0.594606E+09 | 0.612129E+09 | 0.00 | 0.00 |
September | 0.132339E+10 | 0.357396E+09 | 0.107315E+10 | 0.592439E+09 | 0.480710E+09 | 0.00 | 0.00 |
October | 0.102846E+10 | 0.577806E+09 | 0.957631E+09 | 0.576592E+09 | 0.381039E+09 | 0.00 | 0.00 |
November | 0.679387E+09 | 0.782753E+09 | 0.752583E+09 | 0.475298E+09 | 0.277285E+09 | 0.00 | 0.00 |
December | 0.444562E+09 | 0.113599E+10 | 0.612628E+09 | 0.378660E+09 | 0.233969E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127975E+11 | 0.765765E+10 | 0.117405E+11 | 0.603198E+10 | 0.570847E+10 | 0.00 | 0.00 |
Minimum of Months | 0.444562E+09 | 0.198752E+09 | 0.612628E+09 | 0.378660E+09 | 0.233969E+09 | 0.00 | 0.00 |
Maximum of Months | 0.177213E+10 | 0.134570E+10 | 0.127957E+10 | 0.595887E+09 | 0.700328E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.106977E+09 | 0.146663E+10 | 0.293385E+09 | 94565909.88 | 0.198819E+09 | 0.00 | 0.00 |
February | 0.283182E+09 | 0.955534E+09 | 0.437894E+09 | 0.179167E+09 | 0.258728E+09 | 0.00 | 0.00 |
March | 0.466167E+09 | 0.861206E+09 | 0.647311E+09 | 0.187993E+09 | 0.459318E+09 | 0.00 | 0.00 |
April | 0.732269E+09 | 0.572005E+09 | 0.794922E+09 | 0.285686E+09 | 0.509235E+09 | 0.00 | 0.00 |
May | 0.106802E+10 | 0.446583E+09 | 0.102642E+10 | 0.387060E+09 | 0.639362E+09 | 0.00 | 0.00 |
June | 0.131555E+10 | 0.255454E+09 | 0.109444E+10 | 0.422667E+09 | 0.671775E+09 | 0.00 | 0.00 |
July | 0.151579E+10 | 0.197045E+09 | 0.113196E+10 | 0.481762E+09 | 0.650199E+09 | 0.00 | 0.00 |
August | 0.123060E+10 | 0.230688E+09 | 0.953028E+09 | 0.386639E+09 | 0.566389E+09 | 0.00 | 0.00 |
September | 0.850943E+09 | 0.364393E+09 | 0.732315E+09 | 0.306109E+09 | 0.426206E+09 | 0.00 | 0.00 |
October | 0.501083E+09 | 0.592481E+09 | 0.542833E+09 | 0.222368E+09 | 0.320465E+09 | 0.00 | 0.00 |
November | 0.249773E+09 | 0.839425E+09 | 0.369223E+09 | 0.152179E+09 | 0.217044E+09 | 0.00 | 0.00 |
December | 0.102490E+09 | 0.123656E+10 | 0.261678E+09 | 88951420.94 | 0.172726E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.842285E+10 | 0.801800E+10 | 0.828541E+10 | 0.319515E+10 | 0.509027E+10 | 0.00 | 0.00 |
Minimum of Months | 0.102490E+09 | 0.197045E+09 | 0.261678E+09 | 88951420.94 | 0.172726E+09 | 0.00 | 0.00 |
Maximum of Months | 0.151579E+10 | 0.146663E+10 | 0.113196E+10 | 0.481762E+09 | 0.671775E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.316888E+09 | 0.368356E+09 | 0.337566E+09 | 0.241009E+09 | 96556546.53 | 0.00 | 0.00 |
February | 0.387631E+09 | 0.263072E+09 | 0.383054E+09 | 0.274003E+09 | 0.109051E+09 | 0.00 | 0.00 |
March | 0.371148E+09 | 0.288855E+09 | 0.379332E+09 | 0.210890E+09 | 0.168442E+09 | 0.00 | 0.00 |
April | 0.306486E+09 | 0.217563E+09 | 0.302113E+09 | 0.146201E+09 | 0.155912E+09 | 0.00 | 0.00 |
May | 0.283808E+09 | 0.177445E+09 | 0.276763E+09 | 93525809.26 | 0.183238E+09 | 0.00 | 0.00 |
June | 0.308344E+09 | 0.116137E+09 | 0.262517E+09 | 75654659.28 | 0.186862E+09 | 0.00 | 0.00 |
July | 0.392060E+09 | 93626197.73 | 0.293242E+09 | 0.107911E+09 | 0.185331E+09 | 0.00 | 0.00 |
August | 0.448716E+09 | 0.107334E+09 | 0.344408E+09 | 0.171222E+09 | 0.173186E+09 | 0.00 | 0.00 |
September | 0.451033E+09 | 0.150112E+09 | 0.374361E+09 | 0.229156E+09 | 0.145205E+09 | 0.00 | 0.00 |
October | 0.447588E+09 | 0.219547E+09 | 0.408338E+09 | 0.283323E+09 | 0.125015E+09 | 0.00 | 0.00 |
November | 0.354040E+09 | 0.268320E+09 | 0.356998E+09 | 0.258444E+09 | 98554623.67 | 0.00 | 0.00 |
December | 0.297774E+09 | 0.338553E+09 | 0.320850E+09 | 0.231721E+09 | 89129292.72 | 0.00 | 0.00 |
Annual Sum or Average | 0.436551E+10 | 0.260892E+10 | 0.403954E+10 | 0.232306E+10 | 0.171648E+10 | 0.00 | 0.00 |
Minimum of Months | 0.283808E+09 | 93626197.73 | 0.262517E+09 | 75654659.28 | 89129292.72 | 0.00 | 0.00 |
Maximum of Months | 0.451033E+09 | 0.368356E+09 | 0.408338E+09 | 0.283323E+09 | 0.186862E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 815180.68 | 0.443072E+09 | 47890046.26 | 0.00 | 47890046.26 | 0.00 | 0.00 |
February | 9614756.00 | 0.291090E+09 | 61074134.26 | 0.00 | 61074134.26 | 0.00 | 0.00 |
March | 39265226.80 | 0.254436E+09 | 0.109853E+09 | 3519.38 | 0.109849E+09 | 0.00 | 0.00 |
April | 71345097.35 | 0.163242E+09 | 0.121903E+09 | 1168669.63 | 0.120734E+09 | 0.00 | 0.00 |
May | 0.135936E+09 | 0.122101E+09 | 0.164211E+09 | 9442121.06 | 0.154769E+09 | 0.00 | 0.00 |
June | 0.212804E+09 | 66292561.51 | 0.185868E+09 | 21790416.14 | 0.164078E+09 | 0.00 | 0.00 |
July | 0.240844E+09 | 49743804.87 | 0.175233E+09 | 16634794.91 | 0.158598E+09 | 0.00 | 0.00 |
August | 0.179445E+09 | 59131974.00 | 0.141530E+09 | 4883580.11 | 0.136646E+09 | 0.00 | 0.00 |
September | 0.101903E+09 | 0.100946E+09 | 0.101782E+09 | 137805.16 | 0.101644E+09 | 0.00 | 0.00 |
October | 40874561.19 | 0.171857E+09 | 76591762.73 | 0.00 | 76591762.73 | 0.00 | 0.00 |
November | 8973314.87 | 0.256892E+09 | 50388178.52 | 0.00 | 50388178.52 | 0.00 | 0.00 |
December | 662898.96 | 0.377401E+09 | 40158500.09 | 0.00 | 40158500.09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104248E+10 | 0.235621E+10 | 0.127648E+10 | 54060906.39 | 0.122242E+10 | 0.00 | 0.00 |
Minimum of Months | 662898.96 | 49743804.87 | 40158500.09 | 0.00 | 40158500.09 | 0.00 | 0.00 |
Maximum of Months | 0.240844E+09 | 0.443072E+09 | 0.185868E+09 | 21790416.14 | 0.164078E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.476993E+09 | 0.133217E+10 | 0.680578E+09 | 0.420656E+09 | 0.259923E+09 | 0.00 | 0.00 |
February | 0.734006E+09 | 0.880655E+09 | 0.844728E+09 | 0.525427E+09 | 0.319301E+09 | 0.00 | 0.00 |
March | 0.923210E+09 | 0.836211E+09 | 0.101697E+10 | 0.489481E+09 | 0.527488E+09 | 0.00 | 0.00 |
April | 0.106390E+10 | 0.552977E+09 | 0.104614E+10 | 0.514855E+09 | 0.531287E+09 | 0.00 | 0.00 |
May | 0.119890E+10 | 0.433321E+09 | 0.110746E+10 | 0.456241E+09 | 0.651215E+09 | 0.00 | 0.00 |
June | 0.160123E+10 | 0.242846E+09 | 0.128058E+10 | 0.584577E+09 | 0.696008E+09 | 0.00 | 0.00 |
July | 0.191589E+10 | 0.182036E+09 | 0.139964E+10 | 0.718896E+09 | 0.680745E+09 | 0.00 | 0.00 |
August | 0.177091E+10 | 0.213426E+09 | 0.133105E+10 | 0.716394E+09 | 0.614657E+09 | 0.00 | 0.00 |
September | 0.132172E+10 | 0.343534E+09 | 0.108387E+10 | 0.604484E+09 | 0.479390E+09 | 0.00 | 0.00 |
October | 0.102717E+10 | 0.566669E+09 | 0.964829E+09 | 0.583874E+09 | 0.380955E+09 | 0.00 | 0.00 |
November | 0.635636E+09 | 0.770561E+09 | 0.726406E+09 | 0.453972E+09 | 0.272434E+09 | 0.00 | 0.00 |
December | 0.447047E+09 | 0.112723E+10 | 0.614604E+09 | 0.381692E+09 | 0.232911E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.131166E+11 | 0.748164E+10 | 0.120969E+11 | 0.645055E+10 | 0.564631E+10 | 0.00 | 0.00 |
Minimum of Months | 0.447047E+09 | 0.182036E+09 | 0.614604E+09 | 0.381692E+09 | 0.232911E+09 | 0.00 | 0.00 |
Maximum of Months | 0.191589E+10 | 0.133217E+10 | 0.139964E+10 | 0.718896E+09 | 0.696008E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.107845E+09 | 0.142524E+10 | 0.318392E+09 | 0.119334E+09 | 0.199058E+09 | 0.00 | 0.00 |
February | 0.267855E+09 | 0.929764E+09 | 0.442148E+09 | 0.182855E+09 | 0.259292E+09 | 0.00 | 0.00 |
March | 0.485718E+09 | 0.836975E+09 | 0.680007E+09 | 0.225820E+09 | 0.454187E+09 | 0.00 | 0.00 |
April | 0.743335E+09 | 0.548015E+09 | 0.820784E+09 | 0.333528E+09 | 0.487256E+09 | 0.00 | 0.00 |
May | 0.978176E+09 | 0.429315E+09 | 0.966670E+09 | 0.351111E+09 | 0.615558E+09 | 0.00 | 0.00 |
June | 0.142747E+10 | 0.244352E+09 | 0.118468E+10 | 0.517224E+09 | 0.667454E+09 | 0.00 | 0.00 |
July | 0.166471E+10 | 0.190074E+09 | 0.125203E+10 | 0.604771E+09 | 0.647257E+09 | 0.00 | 0.00 |
August | 0.138153E+10 | 0.219406E+09 | 0.107734E+10 | 0.508427E+09 | 0.568917E+09 | 0.00 | 0.00 |
September | 0.844859E+09 | 0.345111E+09 | 0.743040E+09 | 0.318154E+09 | 0.424886E+09 | 0.00 | 0.00 |
October | 0.485249E+09 | 0.566147E+09 | 0.550031E+09 | 0.229650E+09 | 0.320381E+09 | 0.00 | 0.00 |
November | 0.192066E+09 | 0.812287E+09 | 0.343046E+09 | 0.130853E+09 | 0.212193E+09 | 0.00 | 0.00 |
December | 82888485.53 | 0.120463E+10 | 0.263653E+09 | 91984033.00 | 0.171669E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.866171E+10 | 0.775132E+10 | 0.864182E+10 | 0.361371E+10 | 0.502811E+10 | 0.00 | 0.00 |
Minimum of Months | 82888485.53 | 0.190074E+09 | 0.263653E+09 | 91984033.00 | 0.171669E+09 | 0.00 | 0.00 |
Maximum of Months | 0.166471E+10 | 0.142524E+10 | 0.125203E+10 | 0.604771E+09 | 0.667454E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.578555E+09 | 0.169707E+10 | 0.835157E+09 | 0.522200E+09 | 0.312957E+09 | 0.00 | 0.00 |
February | 0.819351E+09 | 0.112745E+10 | 0.962280E+09 | 0.593688E+09 | 0.368591E+09 | 0.00 | 0.00 |
March | 0.927311E+09 | 0.108128E+10 | 0.105989E+10 | 0.456947E+09 | 0.602938E+09 | 0.00 | 0.00 |
April | 0.875541E+09 | 0.735381E+09 | 0.918678E+09 | 0.319308E+09 | 0.599370E+09 | 0.00 | 0.00 |
May | 0.967230E+09 | 0.566158E+09 | 0.955406E+09 | 0.223099E+09 | 0.732307E+09 | 0.00 | 0.00 |
June | 0.116537E+10 | 0.336557E+09 | 0.971454E+09 | 0.211128E+09 | 0.760326E+09 | 0.00 | 0.00 |
July | 0.139921E+10 | 0.272896E+09 | 0.101499E+10 | 0.269849E+09 | 0.745138E+09 | 0.00 | 0.00 |
August | 0.139628E+10 | 0.323036E+09 | 0.105284E+10 | 0.381571E+09 | 0.671268E+09 | 0.00 | 0.00 |
September | 0.124283E+10 | 0.489743E+09 | 0.103163E+10 | 0.496817E+09 | 0.534812E+09 | 0.00 | 0.00 |
October | 0.110409E+10 | 0.744142E+09 | 0.105068E+10 | 0.613882E+09 | 0.436797E+09 | 0.00 | 0.00 |
November | 0.775903E+09 | 0.984326E+09 | 0.882674E+09 | 0.559976E+09 | 0.322698E+09 | 0.00 | 0.00 |
December | 0.574440E+09 | 0.143357E+10 | 0.782189E+09 | 0.502074E+09 | 0.280115E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.118261E+11 | 0.979160E+10 | 0.115179E+11 | 0.515054E+10 | 0.636732E+10 | 0.00 | 0.00 |
Minimum of Months | 0.574440E+09 | 0.272896E+09 | 0.782189E+09 | 0.211128E+09 | 0.280115E+09 | 0.00 | 0.00 |
Maximum of Months | 0.139921E+10 | 0.169707E+10 | 0.105989E+10 | 0.613882E+09 | 0.760326E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.449967E+09 | 0.134379E+10 | 0.655571E+09 | 0.395888E+09 | 0.259684E+09 | 0.00 | 0.00 |
February | 0.735364E+09 | 0.889188E+09 | 0.840475E+09 | 0.521738E+09 | 0.318736E+09 | 0.00 | 0.00 |
March | 0.887512E+09 | 0.845462E+09 | 0.984273E+09 | 0.451654E+09 | 0.532619E+09 | 0.00 | 0.00 |
April | 0.104740E+10 | 0.569938E+09 | 0.102028E+10 | 0.467013E+09 | 0.553266E+09 | 0.00 | 0.00 |
May | 0.128781E+10 | 0.448794E+09 | 0.116721E+10 | 0.492189E+09 | 0.675019E+09 | 0.00 | 0.00 |
June | 0.149255E+10 | 0.260668E+09 | 0.119035E+10 | 0.490020E+09 | 0.700328E+09 | 0.00 | 0.00 |
July | 0.176404E+10 | 0.194971E+09 | 0.127957E+10 | 0.595887E+09 | 0.683688E+09 | 0.00 | 0.00 |
August | 0.161656E+10 | 0.223699E+09 | 0.120673E+10 | 0.594606E+09 | 0.612129E+09 | 0.00 | 0.00 |
September | 0.131844E+10 | 0.351759E+09 | 0.107315E+10 | 0.592439E+09 | 0.480710E+09 | 0.00 | 0.00 |
October | 0.102708E+10 | 0.570857E+09 | 0.957631E+09 | 0.576592E+09 | 0.381039E+09 | 0.00 | 0.00 |
November | 0.680241E+09 | 0.777429E+09 | 0.752583E+09 | 0.475298E+09 | 0.277285E+09 | 0.00 | 0.00 |
December | 0.446746E+09 | 0.113087E+10 | 0.612628E+09 | 0.378660E+09 | 0.233969E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127537E+11 | 0.760742E+10 | 0.117405E+11 | 0.603198E+10 | 0.570847E+10 | 0.00 | 0.00 |
Minimum of Months | 0.446746E+09 | 0.194971E+09 | 0.612628E+09 | 0.378660E+09 | 0.233969E+09 | 0.00 | 0.00 |
Maximum of Months | 0.176404E+10 | 0.134379E+10 | 0.127957E+10 | 0.595887E+09 | 0.700328E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.108131E+09 | 0.146429E+10 | 0.293385E+09 | 94565909.88 | 0.198819E+09 | 0.00 | 0.00 |
February | 0.285114E+09 | 0.951577E+09 | 0.437894E+09 | 0.179167E+09 | 0.258728E+09 | 0.00 | 0.00 |
March | 0.466946E+09 | 0.856336E+09 | 0.647311E+09 | 0.187993E+09 | 0.459318E+09 | 0.00 | 0.00 |
April | 0.729494E+09 | 0.567927E+09 | 0.794922E+09 | 0.285686E+09 | 0.509235E+09 | 0.00 | 0.00 |
May | 0.105963E+10 | 0.446393E+09 | 0.102642E+10 | 0.387060E+09 | 0.639362E+09 | 0.00 | 0.00 |
June | 0.130609E+10 | 0.255528E+09 | 0.109444E+10 | 0.422667E+09 | 0.671775E+09 | 0.00 | 0.00 |
July | 0.150894E+10 | 0.195767E+09 | 0.113196E+10 | 0.481762E+09 | 0.650199E+09 | 0.00 | 0.00 |
August | 0.122546E+10 | 0.228217E+09 | 0.953028E+09 | 0.386639E+09 | 0.566389E+09 | 0.00 | 0.00 |
September | 0.849860E+09 | 0.358767E+09 | 0.732315E+09 | 0.306109E+09 | 0.426206E+09 | 0.00 | 0.00 |
October | 0.504596E+09 | 0.583271E+09 | 0.542833E+09 | 0.222368E+09 | 0.320465E+09 | 0.00 | 0.00 |
November | 0.253125E+09 | 0.831648E+09 | 0.369223E+09 | 0.152179E+09 | 0.217044E+09 | 0.00 | 0.00 |
December | 0.104687E+09 | 0.122987E+10 | 0.261678E+09 | 88951420.94 | 0.172726E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.840207E+10 | 0.796959E+10 | 0.828541E+10 | 0.319515E+10 | 0.509027E+10 | 0.00 | 0.00 |
Minimum of Months | 0.104687E+09 | 0.195767E+09 | 0.261678E+09 | 88951420.94 | 0.172726E+09 | 0.00 | 0.00 |
Maximum of Months | 0.150894E+10 | 0.146429E+10 | 0.113196E+10 | 0.481762E+09 | 0.671775E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.569302E+09 | 0.687589E+09 | 0.618964E+09 | 0.441917E+09 | 0.177047E+09 | 0.00 | 0.00 |
February | 0.714546E+09 | 0.460151E+09 | 0.702372E+09 | 0.502415E+09 | 0.199958E+09 | 0.00 | 0.00 |
March | 0.708215E+09 | 0.445357E+09 | 0.695547E+09 | 0.386690E+09 | 0.308857E+09 | 0.00 | 0.00 |
April | 0.599110E+09 | 0.302692E+09 | 0.553957E+09 | 0.268075E+09 | 0.285882E+09 | 0.00 | 0.00 |
May | 0.567509E+09 | 0.236264E+09 | 0.507476E+09 | 0.171490E+09 | 0.335986E+09 | 0.00 | 0.00 |
June | 0.624514E+09 | 0.134815E+09 | 0.481353E+09 | 0.138721E+09 | 0.342632E+09 | 0.00 | 0.00 |
July | 0.781961E+09 | 96544077.53 | 0.537691E+09 | 0.197866E+09 | 0.339825E+09 | 0.00 | 0.00 |
August | 0.878175E+09 | 0.114198E+09 | 0.631510E+09 | 0.313955E+09 | 0.317555E+09 | 0.00 | 0.00 |
September | 0.871686E+09 | 0.182825E+09 | 0.686432E+09 | 0.420183E+09 | 0.266248E+09 | 0.00 | 0.00 |
October | 0.861540E+09 | 0.298304E+09 | 0.748733E+09 | 0.519504E+09 | 0.229229E+09 | 0.00 | 0.00 |
November | 0.680928E+09 | 0.402229E+09 | 0.654596E+09 | 0.473885E+09 | 0.180711E+09 | 0.00 | 0.00 |
December | 0.555835E+09 | 0.581876E+09 | 0.588313E+09 | 0.424885E+09 | 0.163428E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.841332E+10 | 0.394285E+10 | 0.740694E+10 | 0.425959E+10 | 0.314736E+10 | 0.00 | 0.00 |
Minimum of Months | 0.555835E+09 | 96544077.53 | 0.481353E+09 | 0.138721E+09 | 0.163428E+09 | 0.00 | 0.00 |
Maximum of Months | 0.878175E+09 | 0.687589E+09 | 0.748733E+09 | 0.519504E+09 | 0.342632E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1970969.81 | 0.416097E+10 | 0.418966E+09 | 0.00 | 0.418966E+09 | 0.00 | 0.00 |
February | 47572025.16 | 0.284028E+10 | 0.534308E+09 | 0.00 | 0.534308E+09 | 0.00 | 0.00 |
March | 0.258709E+09 | 0.250765E+10 | 0.961048E+09 | 30789.34 | 0.961017E+09 | 0.00 | 0.00 |
April | 0.514819E+09 | 0.165860E+10 | 0.106647E+10 | 10224116.70 | 0.105625E+10 | 0.00 | 0.00 |
May | 0.104507E+10 | 0.124932E+10 | 0.143660E+10 | 82604480.53 | 0.135400E+10 | 0.00 | 0.00 |
June | 0.169760E+10 | 0.695946E+09 | 0.162607E+10 | 0.190634E+09 | 0.143544E+10 | 0.00 | 0.00 |
July | 0.194866E+10 | 0.554888E+09 | 0.153303E+10 | 0.145530E+09 | 0.138750E+10 | 0.00 | 0.00 |
August | 0.142593E+10 | 0.657227E+09 | 0.123818E+10 | 42724044.28 | 0.119545E+10 | 0.00 | 0.00 |
September | 0.777791E+09 | 0.107950E+10 | 0.890437E+09 | 1205589.69 | 0.889231E+09 | 0.00 | 0.00 |
October | 0.269824E+09 | 0.176403E+10 | 0.670064E+09 | 0.00 | 0.670064E+09 | 0.00 | 0.00 |
November | 47156855.59 | 0.257110E+10 | 0.440821E+09 | 0.00 | 0.440821E+09 | 0.00 | 0.00 |
December | 1657106.30 | 0.364415E+10 | 0.351327E+09 | 0.00 | 0.351327E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.803677E+10 | 0.233837E+11 | 0.111673E+11 | 0.472952E+09 | 0.106944E+11 | 0.00 | 0.00 |
Minimum of Months | 1657106.30 | 0.554888E+09 | 0.351327E+09 | 0.00 | 0.351327E+09 | 0.00 | 0.00 |
Maximum of Months | 0.194866E+10 | 0.416097E+10 | 0.162607E+10 | 0.190634E+09 | 0.143544E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1096289.03 | 0.423620E+10 | 0.418966E+09 | 0.00 | 0.418966E+09 | 0.00 | 0.00 |
February | 39910145.18 | 0.290881E+10 | 0.534308E+09 | 0.00 | 0.534308E+09 | 0.00 | 0.00 |
March | 0.237592E+09 | 0.256438E+10 | 0.961048E+09 | 30789.34 | 0.961017E+09 | 0.00 | 0.00 |
April | 0.490056E+09 | 0.169751E+10 | 0.106647E+10 | 10224116.70 | 0.105625E+10 | 0.00 | 0.00 |
May | 0.101641E+10 | 0.127757E+10 | 0.143660E+10 | 82604480.53 | 0.135400E+10 | 0.00 | 0.00 |
June | 0.167327E+10 | 0.709936E+09 | 0.162607E+10 | 0.190634E+09 | 0.143544E+10 | 0.00 | 0.00 |
July | 0.192849E+10 | 0.567586E+09 | 0.153303E+10 | 0.145530E+09 | 0.138750E+10 | 0.00 | 0.00 |
August | 0.140592E+10 | 0.673630E+09 | 0.123818E+10 | 42724044.28 | 0.119545E+10 | 0.00 | 0.00 |
September | 0.758250E+09 | 0.110625E+10 | 0.890437E+09 | 1205589.69 | 0.889231E+09 | 0.00 | 0.00 |
October | 0.250016E+09 | 0.180759E+10 | 0.670064E+09 | 0.00 | 0.670064E+09 | 0.00 | 0.00 |
November | 39637440.15 | 0.263937E+10 | 0.440821E+09 | 0.00 | 0.440821E+09 | 0.00 | 0.00 |
December | 1055608.46 | 0.372916E+10 | 0.351327E+09 | 0.00 | 0.351327E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.784171E+10 | 0.239180E+11 | 0.111673E+11 | 0.472952E+09 | 0.106944E+11 | 0.00 | 0.00 |
Minimum of Months | 1055608.46 | 0.567586E+09 | 0.351327E+09 | 0.00 | 0.351327E+09 | 0.00 | 0.00 |
Maximum of Months | 0.192849E+10 | 0.423620E+10 | 0.162607E+10 | 0.190634E+09 | 0.143544E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.586616E+09 | 0.265552E+10 | 0.998933E+09 | 0.539973E+09 | 0.458960E+09 | 0.00 | 0.00 |
February | 0.106341E+10 | 0.179450E+10 | 0.128682E+10 | 0.708257E+09 | 0.578567E+09 | 0.00 | 0.00 |
March | 0.155224E+10 | 0.168924E+10 | 0.169690E+10 | 0.715269E+09 | 0.981630E+09 | 0.00 | 0.00 |
April | 0.203597E+10 | 0.114105E+10 | 0.186683E+10 | 0.848336E+09 | 0.101849E+10 | 0.00 | 0.00 |
May | 0.247617E+10 | 0.919148E+09 | 0.207402E+10 | 0.807304E+09 | 0.126671E+10 | 0.00 | 0.00 |
June | 0.342201E+10 | 0.548255E+09 | 0.246513E+10 | 0.110173E+10 | 0.136340E+10 | 0.00 | 0.00 |
July | 0.402772E+10 | 0.429102E+09 | 0.265152E+10 | 0.132358E+10 | 0.132794E+10 | 0.00 | 0.00 |
August | 0.356954E+10 | 0.482878E+09 | 0.240827E+10 | 0.122475E+10 | 0.118352E+10 | 0.00 | 0.00 |
September | 0.246867E+10 | 0.720889E+09 | 0.182683E+10 | 0.922593E+09 | 0.904233E+09 | 0.00 | 0.00 |
October | 0.171346E+10 | 0.114283E+10 | 0.151480E+10 | 0.813492E+09 | 0.701304E+09 | 0.00 | 0.00 |
November | 0.903350E+09 | 0.156557E+10 | 0.106941E+10 | 0.584805E+09 | 0.484607E+09 | 0.00 | 0.00 |
December | 0.538530E+09 | 0.228083E+10 | 0.878226E+09 | 0.473663E+09 | 0.404563E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.243577E+11 | 0.153698E+11 | 0.207377E+11 | 0.100638E+11 | 0.106739E+11 | 0.00 | 0.00 |
Minimum of Months | 0.538530E+09 | 0.429102E+09 | 0.878226E+09 | 0.473663E+09 | 0.404563E+09 | 0.00 | 0.00 |
Maximum of Months | 0.402772E+10 | 0.265552E+10 | 0.265152E+10 | 0.132358E+10 | 0.136340E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.130300E+10 | 0.300419E+10 | 0.171923E+10 | 0.112492E+10 | 0.594305E+09 | 0.00 | 0.00 |
February | 0.176731E+10 | 0.200114E+10 | 0.197109E+10 | 0.127892E+10 | 0.692165E+09 | 0.00 | 0.00 |
March | 0.190658E+10 | 0.192575E+10 | 0.210000E+10 | 0.984350E+09 | 0.111565E+10 | 0.00 | 0.00 |
April | 0.173326E+10 | 0.131614E+10 | 0.177572E+10 | 0.685903E+09 | 0.108981E+10 | 0.00 | 0.00 |
May | 0.181434E+10 | 0.102533E+10 | 0.178428E+10 | 0.464853E+09 | 0.131942E+10 | 0.00 | 0.00 |
June | 0.212375E+10 | 0.611629E+09 | 0.178273E+10 | 0.418472E+09 | 0.136426E+10 | 0.00 | 0.00 |
July | 0.259272E+10 | 0.492975E+09 | 0.189425E+10 | 0.553567E+09 | 0.134068E+10 | 0.00 | 0.00 |
August | 0.268877E+10 | 0.579565E+09 | 0.203199E+10 | 0.813835E+09 | 0.121816E+10 | 0.00 | 0.00 |
September | 0.248855E+10 | 0.862195E+09 | 0.205259E+10 | 0.107001E+10 | 0.982580E+09 | 0.00 | 0.00 |
October | 0.229750E+10 | 0.131098E+10 | 0.213564E+10 | 0.132242E+10 | 0.813215E+09 | 0.00 | 0.00 |
November | 0.167998E+10 | 0.174733E+10 | 0.181742E+10 | 0.120630E+10 | 0.611123E+09 | 0.00 | 0.00 |
December | 0.128492E+10 | 0.254161E+10 | 0.161802E+10 | 0.108157E+10 | 0.536451E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.236807E+11 | 0.174188E+11 | 0.226830E+11 | 0.110051E+11 | 0.116778E+11 | 0.00 | 0.00 |
Minimum of Months | 0.128492E+10 | 0.492975E+09 | 0.161802E+10 | 0.418472E+09 | 0.536451E+09 | 0.00 | 0.00 |
Maximum of Months | 0.268877E+10 | 0.300419E+10 | 0.213564E+10 | 0.132242E+10 | 0.136426E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770630E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163521590.1 | 81.21 | 0.00 | 0.00 |
February | 0.696250E+10 | -0.681597E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146533971.2 | 81.21 | 0.00 | 0.00 |
March | 0.770352E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162057180.8 | 81.21 | 0.00 | 0.00 |
April | 0.746521E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156627458.5 | 81.21 | 0.00 | 0.00 |
May | 0.770454E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161747212.0 | 81.21 | 0.00 | 0.00 |
June | 0.745687E+10 | -0.730052E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156350868.9 | 81.21 | 0.00 | 0.00 |
July | 0.771234E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161489045.5 | 81.21 | 0.00 | 0.00 |
August | 0.770431E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161507634.1 | 81.21 | 0.00 | 0.00 |
September | 0.746634E+10 | -0.730993E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156413956.5 | 81.21 | 0.00 | 0.00 |
October | 0.770323E+10 | -0.754143E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161792139.3 | 81.21 | 0.00 | 0.00 |
November | 0.744921E+10 | -0.729242E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156797223.6 | 81.21 | 0.00 | 0.00 |
December | 0.771325E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162393697.5 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907476E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190723E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696250E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -163521590.1 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771325E+10 | -0.681597E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146533971.2 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYSLAUNDRY HPWH TANK
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.810975E+11 | -0.802584E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -839076371.5 | 72.22 | 0.00 | 0.00 |
February | 0.688188E+11 | -0.110131E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -805029961.8 | 80.52 | 0.00 | 0.00 |
March | 0.759738E+11 | -0.124966E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -881142333.5 | 81.21 | 0.00 | 0.00 |
April | 0.640591E+11 | -0.120329E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -810266007.2 | 81.67 | 0.00 | 0.00 |
May | 0.566092E+11 | -0.119449E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -811132210.0 | 81.67 | 0.00 | 0.00 |
June | 0.423029E+11 | -0.110656E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -738100951.1 | 81.67 | 0.00 | 0.00 |
July | 0.356193E+11 | -0.110408E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -730467228.3 | 81.68 | 0.00 | 0.00 |
August | 0.361147E+11 | -0.108680E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -741679834.7 | 81.68 | 0.00 | 0.00 |
September | 0.398740E+11 | -0.106142E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -751434069.1 | 81.67 | 0.00 | 0.00 |
October | 0.524809E+11 | -0.113108E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -822435111.6 | 81.67 | 0.00 | 0.00 |
November | 0.634588E+11 | -0.114215E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -839156006.4 | 81.67 | 0.00 | 0.00 |
December | 0.760843E+11 | -0.119097E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -912029781.6 | 80.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.692493E+12 | -0.133744E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.968195E+10 | 80.68 | 0.00 | 0.00 |
Minimum of Months | 0.356193E+11 | -0.124966E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -912029781.6 | 72.22 | 0.00 | 0.00 |
Maximum of Months | 0.810975E+11 | -0.802584E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -730467228.3 | 81.68 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 HPWH TANK
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.803036E+11 | -0.790508E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.125285E+10 | 46.17 | 0.00 | 0.00 |
February | 0.175889E+10 | -0.730530E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.134464E+10 | 58.72 | 0.00 | 0.00 |
March | 0.483387E+09 | -0.801382E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.144979E+10 | 58.93 | 0.00 | 0.00 |
April | -0.165844E+10 | -0.748234E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.129166E+10 | 59.10 | 0.00 | 0.00 |
May | -0.238191E+10 | -0.731503E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.127552E+10 | 59.23 | 0.00 | 0.00 |
June | -0.272307E+10 | -0.665830E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.112289E+10 | 59.28 | 0.00 | 0.00 |
July | -0.282915E+10 | -0.653497E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.108383E+10 | 59.31 | 0.00 | 0.00 |
August | -0.265416E+10 | -0.639224E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.111132E+10 | 59.33 | 0.00 | 0.00 |
September | -0.253753E+10 | -0.626555E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.115610E+10 | 59.31 | 0.00 | 0.00 |
October | -0.210385E+10 | -0.676465E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.130463E+10 | 59.29 | 0.00 | 0.00 |
November | -0.121965E+10 | -0.695004E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.136348E+10 | 59.18 | 0.00 | 0.00 |
December | 0.180998E+10 | -0.760633E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152785E+10 | 58.83 | 0.00 | 0.00 |
Annual Sum or Average | 0.662481E+11 | -0.851937E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.152846E+11 | 58.04 | 0.00 | 0.00 |
Minimum of Months | -0.282915E+10 | -0.801382E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.152785E+10 | 46.17 | 0.00 | 0.00 |
Maximum of Months | 0.803036E+11 | -0.626555E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.108383E+10 | 59.33 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.87 | 0.86 | 01-JAN-08:50 | 4606.09 | 36.83 | 218.17 | 232.33 | 3938.11 | 37.79 | 220.83 | 207.83 |
February | 275.00 | 0.87 | 0.86 | 01-FEB-08:20 | 6396.30 | 36.79 | 265.17 | 258.50 | 1925.00 | 30.89 | 230.50 | 241.17 |
March | 304.00 | 0.87 | 0.86 | 01-MAR-07:49 | 6432.15 | 30.56 | 226.67 | 320.50 | 804.09 | 22.50 | 226.33 | 275.50 |
April | 325.17 | 0.87 | 0.86 | 01-APR-08:50 | 1480.29 | 20.20 | 75.00 | 346.00 | 589.44 | 21.93 | 224.50 | 283.33 |
May | 385.83 | 0.87 | 0.86 | 01-MAY-06:40 | 1317.09 | 19.95 | 77.33 | 394.50 | 519.22 | 21.67 | 252.33 | 320.00 |
June | 434.17 | 0.87 | 0.86 | 01-JUN-13:39 | 1108.58 | 19.63 | 51.50 | 407.17 | 453.24 | 21.40 | 275.00 | 317.83 |
July | 417.33 | 0.87 | 0.86 | 01-JUL-06:49 | 1153.15 | 20.20 | 53.17 | 402.00 | 479.06 | 21.96 | 301.33 | 328.00 |
August | 421.33 | 0.87 | 0.86 | 01-AUG-07:10 | 1224.25 | 19.75 | 59.33 | 381.17 | 502.16 | 21.51 | 265.00 | 310.33 |
September | 352.17 | 0.87 | 0.86 | 01-SEP-07:10 | 4300.26 | 25.43 | 159.83 | 329.33 | 593.13 | 21.66 | 234.83 | 276.50 |
October | 317.67 | 0.87 | 0.86 | 01-OCT-08:00 | 6617.78 | 34.85 | 288.67 | 302.00 | 1058.31 | 25.37 | 221.50 | 274.50 |
November | 269.50 | 0.87 | 0.86 | 01-NOV-07:00 | 4766.01 | 36.91 | 260.67 | 251.67 | 3577.47 | 36.92 | 258.33 | 235.67 |
December | 236.83 | 0.87 | 0.86 | 01-DEC-08:50 | 3609.03 | 37.43 | 231.50 | 232.00 | 3073.27 | 38.37 | 237.67 | 213.83 |
Annual Sum or Average | 3965.83 | 0.87 | 3273.69 | 26.76 | 1967.00 | 3857.17 | 1236.68 | 25.63 | 2948.17 | 3284.50 | ||
Minimum of Months | 226.83 | 0.87 | 0.86 | 1108.58 | 19.63 | 51.50 | 232.00 | 453.24 | 21.40 | 220.83 | 207.83 | |
Maximum of Months | 434.17 | 0.87 | 0.86 | 6617.78 | 37.43 | 288.67 | 407.17 | 3938.11 | 38.37 | 301.33 | 328.00 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.25 | 0.22 | 01-JAN-08:39 | 5020.28 | 36.91 | 218.83 | 241.33 | 4351.28 | 37.85 | 222.50 | 222.00 |
February | 275.00 | 0.24 | 0.22 | 01-FEB-08:20 | 6826.95 | 36.87 | 265.83 | 265.00 | 2353.01 | 30.65 | 224.50 | 252.00 |
March | 304.00 | 0.24 | 0.22 | 01-MAR-07:49 | 6841.96 | 30.76 | 233.50 | 330.33 | 1212.87 | 22.55 | 228.50 | 302.17 |
April | 325.17 | 0.25 | 0.22 | 01-APR-08:39 | 1795.85 | 20.51 | 83.33 | 358.50 | 903.98 | 22.09 | 222.00 | 325.83 |
May | 385.83 | 0.25 | 0.22 | 01-MAY-06:10 | 1569.69 | 20.43 | 107.33 | 406.67 | 770.98 | 21.98 | 270.17 | 370.50 |
June | 434.17 | 0.26 | 0.22 | 01-JUN-13:39 | 1327.34 | 20.19 | 115.50 | 427.17 | 671.35 | 21.77 | 295.33 | 380.00 |
July | 417.33 | 0.25 | 0.22 | 01-JUL-06:40 | 1407.49 | 20.62 | 98.67 | 416.50 | 732.69 | 22.22 | 305.00 | 382.17 |
August | 421.33 | 0.26 | 0.22 | 01-AUG-06:30 | 1511.87 | 20.09 | 93.67 | 397.83 | 789.08 | 21.69 | 258.50 | 360.33 |
September | 352.17 | 0.26 | 0.22 | 01-SEP-06:40 | 4657.43 | 25.69 | 167.83 | 341.17 | 948.99 | 21.70 | 204.83 | 309.33 |
October | 317.67 | 0.25 | 0.22 | 01-OCT-08:09 | 7025.08 | 35.00 | 289.50 | 310.33 | 1464.17 | 25.25 | 219.17 | 291.33 |
November | 269.50 | 0.24 | 0.22 | 01-NOV-07:49 | 5152.09 | 37.00 | 260.83 | 258.00 | 3962.98 | 36.93 | 257.83 | 246.00 |
December | 236.83 | 0.25 | 0.22 | 01-DEC-08:39 | 3973.74 | 37.49 | 231.83 | 238.33 | 3437.24 | 38.42 | 238.67 | 225.33 |
Annual Sum or Average | 3965.83 | 0.25 | 3602.73 | 27.05 | 2166.67 | 3991.17 | 1564.70 | 25.75 | 2947.00 | 3667.00 | ||
Minimum of Months | 226.83 | 0.24 | 0.22 | 1327.34 | 20.09 | 83.33 | 238.33 | 671.35 | 21.69 | 204.83 | 222.00 | |
Maximum of Months | 434.17 | 0.26 | 0.22 | 7025.08 | 37.49 | 289.50 | 427.17 | 4351.28 | 38.42 | 305.00 | 382.17 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.67 | 0.60 | 01-JAN-10:50 | 373.96 | 14.21 | 0.00 | 196.33 | 174.85 | 17.67 | 0.00 | 77.83 |
February | 275.00 | 0.65 | 0.60 | 02-FEB-10:09 | 393.15 | 15.05 | 0.00 | 233.50 | 190.53 | 18.51 | 0.00 | 114.67 |
March | 304.00 | 0.62 | 0.60 | 01-MAR-08:09 | 636.94 | 16.92 | 0.00 | 315.33 | 289.56 | 20.16 | 9.50 | 255.00 |
April | 325.17 | 0.62 | 0.60 | 01-APR-08:50 | 662.11 | 17.42 | 0.00 | 357.17 | 302.86 | 20.62 | 42.17 | 301.67 |
May | 385.83 | 0.61 | 0.60 | 01-MAY-05:00 | 830.09 | 19.27 | 33.33 | 415.33 | 382.64 | 22.29 | 157.83 | 374.67 |
June | 434.17 | 0.61 | 0.60 | 01-JUN-13:39 | 864.60 | 21.26 | 96.67 | 444.00 | 365.61 | 22.34 | 223.33 | 400.33 |
July | 417.33 | 0.61 | 0.60 | 01-JUL-06:40 | 826.31 | 20.50 | 62.83 | 428.83 | 362.24 | 21.84 | 176.17 | 396.33 |
August | 421.33 | 0.62 | 0.60 | 01-AUG-05:40 | 627.58 | 17.35 | 0.00 | 404.50 | 317.70 | 20.65 | 79.83 | 354.67 |
September | 352.17 | 0.63 | 0.60 | 01-SEP-06:49 | 509.98 | 16.50 | 0.00 | 332.33 | 246.19 | 19.79 | 6.00 | 242.00 |
October | 317.67 | 0.65 | 0.60 | 01-OCT-09:09 | 426.70 | 15.35 | 0.00 | 275.67 | 203.71 | 18.75 | 0.00 | 154.50 |
November | 269.50 | 0.67 | 0.60 | 01-NOV-08:00 | 346.11 | 14.29 | 0.00 | 209.00 | 164.77 | 17.79 | 0.00 | 75.83 |
December | 236.83 | 0.68 | 0.60 | 01-DEC-09:00 | 304.17 | 13.57 | 0.00 | 189.17 | 146.71 | 17.13 | 0.00 | 29.33 |
Annual Sum or Average | 3965.83 | 0.63 | 601.95 | 17.26 | 192.83 | 3801.17 | 277.50 | 20.13 | 694.83 | 2776.83 | ||
Minimum of Months | 226.83 | 0.61 | 0.60 | 304.17 | 13.57 | 0.00 | 189.17 | 146.71 | 17.13 | 0.00 | 29.33 | |
Maximum of Months | 434.17 | 0.68 | 0.60 | 864.60 | 21.26 | 96.67 | 444.00 | 382.64 | 22.34 | 223.33 | 400.33 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.67 | 0.60 | 01-JAN-10:50 | 373.96 | 14.21 | 0.00 | 196.33 | 174.85 | 17.67 | 0.00 | 77.83 |
February | 275.00 | 0.65 | 0.60 | 02-FEB-10:09 | 393.15 | 15.05 | 0.00 | 233.50 | 190.53 | 18.51 | 0.00 | 114.67 |
March | 304.00 | 0.62 | 0.60 | 01-MAR-08:09 | 636.94 | 16.92 | 0.00 | 315.33 | 289.56 | 20.16 | 9.50 | 255.00 |
April | 325.17 | 0.62 | 0.60 | 01-APR-08:50 | 662.11 | 17.42 | 0.00 | 357.17 | 302.86 | 20.62 | 42.00 | 301.67 |
May | 385.83 | 0.61 | 0.60 | 01-MAY-05:00 | 830.09 | 19.27 | 33.33 | 415.33 | 382.64 | 22.29 | 157.83 | 374.67 |
June | 434.17 | 0.61 | 0.60 | 01-JUN-13:39 | 864.60 | 21.26 | 96.67 | 444.00 | 365.61 | 22.34 | 223.33 | 400.33 |
July | 417.33 | 0.61 | 0.60 | 01-JUL-06:40 | 826.31 | 20.50 | 62.83 | 428.83 | 362.24 | 21.84 | 176.17 | 396.33 |
August | 421.33 | 0.62 | 0.60 | 01-AUG-05:40 | 627.58 | 17.35 | 0.00 | 404.50 | 317.70 | 20.65 | 79.83 | 354.67 |
September | 352.17 | 0.63 | 0.60 | 01-SEP-06:49 | 509.98 | 16.50 | 0.00 | 332.33 | 246.19 | 19.79 | 6.00 | 242.00 |
October | 317.67 | 0.65 | 0.60 | 01-OCT-09:09 | 426.70 | 15.35 | 0.00 | 275.67 | 203.71 | 18.75 | 0.00 | 154.50 |
November | 269.50 | 0.67 | 0.60 | 01-NOV-08:00 | 346.11 | 14.29 | 0.00 | 209.00 | 164.77 | 17.79 | 0.00 | 75.83 |
December | 236.83 | 0.68 | 0.60 | 01-DEC-09:00 | 304.17 | 13.57 | 0.00 | 189.17 | 146.71 | 17.13 | 0.00 | 29.33 |
Annual Sum or Average | 3965.83 | 0.63 | 601.95 | 17.26 | 192.83 | 3801.17 | 277.50 | 20.13 | 694.67 | 2776.83 | ||
Minimum of Months | 226.83 | 0.61 | 0.60 | 304.17 | 13.57 | 0.00 | 189.17 | 146.71 | 17.13 | 0.00 | 29.33 | |
Maximum of Months | 434.17 | 0.68 | 0.60 | 864.60 | 21.26 | 96.67 | 444.00 | 382.64 | 22.34 | 223.33 | 400.33 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.313801E+12 | 421520.06 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.970816E+11 | 396616.36 | 01-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.744564E+11 | 203546.10 | 04-MAR-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.537223E+11 | 123414.12 | 09-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.550775E+11 | 122647.20 | 03-MAY-17:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.401441E+11 | 119431.72 | 17-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.210278E+11 | 111502.76 | 09-JUL-02:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.291867E+11 | 113887.44 | 17-AUG-22:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.410421E+11 | 119288.93 | 17-SEP-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.664096E+11 | 122076.98 | 26-OCT-17:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.752457E+11 | 121300.25 | 02-NOV-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141121E+12 | 406677.35 | 29-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100832E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.210278E+11 | 111502.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.313801E+12 | 421520.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108654E+10 | 9309.88 | 11-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108654E+10 | 9309.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.480202E+10 | 5693.32 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.193020E+10 | 4161.91 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163117E+10 | 2786.56 | 05-MAR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.973904E+09 | 1663.35 | 29-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.642959E+09 | 1546.18 | 08-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.106987E+09 | 993.88 | 17-JUN-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8455782.20 | 267.67 | 09-JUL-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 35738917.34 | 824.87 | 18-AUG-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.219811E+09 | 1013.81 | 12-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.540900E+09 | 1549.48 | 10-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138512E+10 | 2299.96 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.306771E+10 | 5437.12 | 29-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8455782.20 | 267.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.480202E+10 | 5693.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.849214E+09 | 2087.20 | 11-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 76928796.66 | 963.85 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14693927.46 | 345.67 | 05-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17967442.25 | 322.24 | 28-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184084E+09 | 1841.52 | 29-DEC-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.849214E+09 | 2087.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.198099E+10 | 3037.49 | 11-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.651773E+09 | 1602.81 | 01-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.251741E+09 | 972.92 | 06-MAR-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11384977.84 | 303.61 | 30-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15318766.86 | 334.24 | 01-MAY-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.175766E+09 | 787.70 | 27-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.869391E+09 | 2220.73 | 29-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.395636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.198099E+10 | 3037.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.153508E+10 | 1840.36 | 10-JAN-22:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.596424E+09 | 1121.81 | 01-FEB-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271718E+09 | 735.74 | 05-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 37292969.71 | 266.67 | 30-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30265957.76 | 286.18 | 08-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1556978.01 | 140.07 | 10-OCT-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.213313E+09 | 604.60 | 27-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.812629E+09 | 1548.07 | 29-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.153508E+10 | 1840.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.460128E+10 | 13349.84 | 11-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185617E+09 | 12342.02 | 01-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13637659.30 | 1195.05 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 645275.62 | 304.77 | 29-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 459793.38 | 202.70 | 08-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10140747.79 | 969.47 | 27-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.685082E+09 | 12687.77 | 31-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.549686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.460128E+10 | 13349.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.772155E+10 | 16194.31 | 11-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105085E+10 | 10983.70 | 01-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.662207E+09 | 4302.06 | 04-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.362799E+09 | 3058.16 | 20-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.245111E+09 | 3498.21 | 08-MAY-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 27478565.03 | 1982.27 | 16-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3827035.17 | 939.10 | 17-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 49323795.55 | 2129.31 | 12-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 82696395.50 | 2500.19 | 05-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.556056E+09 | 4441.23 | 28-NOV-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.245140E+10 | 15658.38 | 29-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.772155E+10 | 16194.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.133841E+11 | 39827.26 | 11-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.450914E+09 | 18480.85 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18501302.23 | 3122.77 | 05-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 79898343.28 | 4040.28 | 28-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.240728E+10 | 38155.31 | 29-DEC-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.133841E+11 | 39827.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.150452E+11 | 19645.76 | 11-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.558119E+10 | 12630.49 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.276445E+10 | 7494.38 | 06-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.476567E+09 | 3586.53 | 21-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.338527E+09 | 4356.72 | 08-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195724E+09 | 3705.23 | 10-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.299355E+10 | 7472.05 | 27-NOV-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.928019E+10 | 18237.80 | 29-DEC-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.366754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.150452E+11 | 19645.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106147E+11 | 12879.60 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.424364E+10 | 9178.33 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.274445E+10 | 5719.62 | 05-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.777468E+09 | 2716.66 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.420935E+09 | 2438.32 | 08-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 226032.50 | 180.01 | 17-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 50569773.93 | 1217.87 | 20-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.439544E+09 | 2590.58 | 10-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.253874E+10 | 4659.97 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.651752E+10 | 12240.21 | 29-DEC-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.283477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106147E+11 | 12879.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.343369E+10 | 13450.73 | 09-JAN-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 42913929.60 | 5344.15 | 01-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.324087E+09 | 13224.36 | 29-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.380069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.343369E+10 | 13450.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.324078E+10 | 13355.45 | 09-JAN-09:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 34732636.33 | 4687.94 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.267311E+09 | 12775.64 | 29-DEC-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.354283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.324078E+10 | 13355.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.236210E+10 | 11876.79 | 11-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 78043469.86 | 8640.93 | 01-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.326338E+09 | 10696.16 | 29-DEC-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.276649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.236210E+10 | 11876.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.206232E+11 | 39711.37 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.402714E+10 | 37396.69 | 01-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190831E+10 | 15357.12 | 04-MAR-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.176933E+09 | 2669.46 | 29-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36183260.65 | 1151.07 | 08-MAY-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19332.93 | 0.37 | 30-JUN-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 18294.91 | 0.37 | 11-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18308.59 | 0.36 | 12-AUG-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15940.79 | 0.37 | 03-SEP-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 53932716.57 | 2014.17 | 10-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137829E+10 | 6409.22 | 26-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.671760E+10 | 38273.41 | 31-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 15940.79 | 0.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.206232E+11 | 39711.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.768519E+10 | 12706.38 | 05-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.380758E+10 | 12704.93 | 09-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.273693E+10 | 12705.82 | 03-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101151E+10 | 12488.51 | 28-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.598192E+09 | 12496.00 | 08-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 49220198.86 | 3685.08 | 02-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6762778.08 | 3867.89 | 21-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22928887.74 | 3712.67 | 30-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.218045E+09 | 7592.48 | 19-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.749650E+09 | 12546.23 | 10-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.259008E+10 | 12705.74 | 26-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.574884E+10 | 12706.46 | 13-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.252249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6762778.08 | 3685.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.768519E+10 | 12706.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.907711E+10 | 12570.99 | 05-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.489363E+10 | 12571.25 | 08-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.350950E+10 | 12570.39 | 03-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120187E+10 | 12355.11 | 28-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.652661E+09 | 12371.04 | 08-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 46012918.89 | 4786.26 | 04-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4666691.38 | 4670.33 | 12-JUL-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23698633.17 | 4374.68 | 12-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.297026E+09 | 10295.14 | 19-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113076E+10 | 12493.71 | 10-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.355990E+10 | 12570.28 | 26-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.695742E+10 | 12571.32 | 22-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.313542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4666691.38 | 4374.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.907711E+10 | 12571.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.441797E+10 | 29013.95 | 11-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.171292E+09 | 9467.86 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181166E+10 | 20155.50 | 31-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.640092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.441797E+10 | 29013.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.394793E+11 | 69216.47 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179481E+11 | 69209.03 | 02-FEB-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.944394E+10 | 68669.96 | 04-MAR-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148910E+10 | 35795.13 | 16-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.795703E+09 | 25400.20 | 23-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35991496.49 | 26043.04 | 07-JUN-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17773309.18 | 24278.48 | 08-JUL-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18977205.98 | 23321.25 | 19-AUG-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.212885E+09 | 38791.92 | 21-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129106E+10 | 40320.78 | 02-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103441E+11 | 69055.30 | 27-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.253302E+11 | 69212.88 | 27-DEC-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106407E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 17773309.18 | 23321.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.394793E+11 | 69216.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.756961E+10 | 12371.91 | 05-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.378556E+10 | 12372.17 | 08-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.266458E+10 | 12371.24 | 03-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106918E+10 | 12075.24 | 28-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.658862E+09 | 12160.51 | 08-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 51210206.78 | 3310.43 | 01-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2596967.39 | 3355.76 | 04-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15681602.95 | 2949.51 | 17-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.214576E+09 | 6676.88 | 13-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.769442E+09 | 12052.83 | 05-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.265735E+10 | 12369.88 | 26-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.570773E+10 | 12371.93 | 13-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.251664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2596967.39 | 2949.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.756961E+10 | 12372.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.892701E+10 | 12215.62 | 05-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.485263E+10 | 12215.85 | 08-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.337070E+10 | 12214.90 | 03-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125260E+10 | 11925.60 | 28-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.722167E+09 | 12014.44 | 08-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 51380144.87 | 3623.04 | 01-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2224164.84 | 3484.98 | 04-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16811632.73 | 3542.77 | 18-AUG-21:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.285229E+09 | 6800.83 | 13-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112285E+10 | 11931.90 | 05-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.361276E+10 | 12214.89 | 26-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.690755E+10 | 12215.61 | 13-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.311239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2224164.84 | 3484.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.892701E+10 | 12215.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.268697E+10 | 3832.16 | 05-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141469E+10 | 3832.14 | 23-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.108771E+10 | 3831.93 | 03-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.462109E+09 | 3791.08 | 28-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.275422E+09 | 3778.50 | 08-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37343986.83 | 1208.04 | 16-JUN-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2772594.09 | 796.07 | 29-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17889094.33 | 1226.65 | 18-AUG-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137331E+09 | 3690.22 | 19-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.386789E+09 | 3808.73 | 10-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103441E+10 | 3831.80 | 26-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207981E+10 | 3832.25 | 22-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.962324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2772594.09 | 796.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.268697E+10 | 3832.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.309666E+10 | 3779.03 | 05-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175575E+10 | 3779.03 | 23-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133962E+10 | 3778.80 | 03-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.527561E+09 | 3740.10 | 29-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.294946E+09 | 3726.21 | 08-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31960186.13 | 1257.60 | 16-JUN-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1764384.06 | 1134.47 | 22-JUL-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18355016.47 | 1267.60 | 18-AUG-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.173866E+09 | 3655.81 | 19-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.544101E+09 | 3755.98 | 10-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135512E+10 | 3778.92 | 11-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.245044E+10 | 3779.13 | 22-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1764384.06 | 1134.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.309666E+10 | 3779.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.890572E+10 | 18431.17 | 05-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.377968E+10 | 18428.29 | 09-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.290534E+10 | 18428.19 | 03-MAR-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137890E+10 | 18067.93 | 28-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.961062E+09 | 18036.02 | 08-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.110010E+09 | 4716.51 | 02-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13388509.32 | 4854.96 | 04-JUL-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33354523.79 | 4499.04 | 09-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.264419E+09 | 10850.11 | 12-SEP-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.663079E+09 | 17905.98 | 05-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.246188E+10 | 18427.79 | 27-NOV-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.607965E+10 | 18430.61 | 15-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.275565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 13388509.32 | 4499.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.890572E+10 | 18431.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.184293E+10 | 0.184293E+10 | 688.22 | 01-JAN-00:30 | 688.22 | 0.00 |
February | 0.00 | 0.00 | 0.509955E+11 | 0.509955E+11 | 32140.97 | 18-FEB-06:13 | 32140.97 | 0.00 |
March | 0.00 | 0.00 | 0.582516E+11 | 0.582516E+11 | 44099.28 | 31-MAR-23:05 | 44099.28 | 0.00 |
April | 0.00 | 0.00 | 0.585353E+11 | 0.585353E+11 | 44083.59 | 01-APR-01:07 | 44083.59 | 0.00 |
May | 0.00 | 0.00 | 0.585291E+11 | 0.585291E+11 | 48253.29 | 01-MAY-04:15 | 48253.29 | 0.00 |
June | 0.00 | 0.00 | 0.549686E+11 | 0.549686E+11 | 55372.00 | 01-JUN-18:20 | 55372.00 | 0.00 |
July | 0.00 | 0.00 | 0.545650E+11 | 0.545650E+11 | 59052.04 | 01-JUL-06:05 | 59052.04 | 0.00 |
August | 0.00 | 0.00 | 0.526655E+11 | 0.526655E+11 | 56352.05 | 01-AUG-04:07 | 56352.05 | 0.00 |
September | 0.00 | 0.00 | 0.508223E+11 | 0.508223E+11 | 52589.66 | 30-SEP-05:06 | 52589.66 | 0.00 |
October | 0.00 | 0.00 | 0.527402E+11 | 0.527402E+11 | 45382.29 | 31-OCT-05:20 | 45382.29 | 0.00 |
November | 0.00 | 0.00 | 0.515484E+11 | 0.515484E+11 | 37962.03 | 30-NOV-08:40 | 37962.03 | 0.00 |
December | 0.00 | 0.00 | 0.509856E+11 | 0.509856E+11 | 29253.12 | 31-DEC-02:20 | 29253.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.596450E+12 | 0.596450E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.184293E+10 | 0.184293E+10 | 688.22 | 688.22 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.585353E+11 | 0.585353E+11 | 59052.04 | 59052.04 | 0.00 |
Report: CoilReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.223683E+10 | 0.223683E+10 | 835.51 | 01-JAN-22:50 | 835.51 | 0.00 |
February | 0.00 | 0.00 | 0.294200E+11 | 0.294200E+11 | 40662.10 | 18-FEB-17:20 | 40662.10 | 0.00 |
March | 0.00 | 0.00 | 0.356267E+11 | 0.356267E+11 | 44821.70 | 01-MAR-18:12 | 44821.70 | 0.00 |
April | 0.00 | 0.00 | 0.427234E+11 | 0.427234E+11 | 55784.28 | 01-APR-21:10 | 55784.28 | 0.00 |
May | 0.00 | 0.00 | 0.482360E+11 | 0.482360E+11 | 61064.10 | 01-MAY-17:01 | 61064.10 | 0.00 |
June | 0.00 | 0.00 | 0.536336E+11 | 0.536336E+11 | 70078.08 | 01-JUN-22:00 | 70078.08 | 0.00 |
July | 0.00 | 0.00 | 0.591764E+11 | 0.591764E+11 | 74737.86 | 01-JUL-16:20 | 74737.86 | 0.00 |
August | 0.00 | 0.00 | 0.567339E+11 | 0.567339E+11 | 71319.05 | 01-AUG-18:30 | 71319.05 | 0.00 |
September | 0.00 | 0.00 | 0.510606E+11 | 0.510606E+11 | 66554.97 | 30-SEP-16:10 | 66554.97 | 0.00 |
October | 0.00 | 0.00 | 0.453604E+11 | 0.453604E+11 | 57428.75 | 31-OCT-16:10 | 57428.75 | 0.00 |
November | 0.00 | 0.00 | 0.366880E+11 | 0.366880E+11 | 48032.94 | 30-NOV-17:10 | 48032.94 | 0.00 |
December | 0.00 | 0.00 | 0.293913E+11 | 0.293913E+11 | 37005.41 | 31-DEC-17:20 | 37005.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.490287E+12 | 0.490287E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.223683E+10 | 0.223683E+10 | 835.51 | 835.51 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.591764E+11 | 0.591764E+11 | 74737.86 | 74737.86 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.118080E+10 | 0.118080E+10 | 59928.27 | 27-FEB-15:20 | 59928.27 | 0.00 |
March | 0.00 | 0.00 | 17670844.71 | 17670844.71 | 3815.58 | 14-MAR-13:10 | 3815.58 | 0.00 |
April | 0.00 | 0.00 | 0.161152E+11 | 0.161152E+11 | 128061.42 | 06-APR-15:55 | 128061.42 | 0.00 |
May | 0.00 | 0.00 | 0.587471E+11 | 0.587471E+11 | 199364.37 | 19-MAY-18:07 | 199364.37 | 0.04 |
June | 0.00 | 0.00 | 0.154886E+12 | 0.153330E+12 | 282482.82 | 20-JUN-20:00 | 212575.96 | 0.23 |
July | 0.00 | 0.00 | 0.265505E+12 | 0.263821E+12 | 281189.44 | 17-JUL-18:03 | 281189.44 | 0.40 |
August | 0.00 | 0.00 | 0.221511E+12 | 0.221511E+12 | 255136.99 | 07-AUG-18:03 | 255136.99 | 0.17 |
September | 0.00 | 0.00 | 0.124345E+12 | 0.120704E+12 | 279286.33 | 07-SEP-18:04 | 196864.22 | 0.20 |
October | 0.00 | 0.00 | 0.247539E+11 | 0.247539E+11 | 167408.73 | 18-OCT-15:03 | 167408.73 | 0.00 |
November | 0.00 | 0.00 | 0.167984E+10 | 0.167984E+10 | 41891.42 | 17-NOV-18:20 | 41891.42 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.868743E+12 | 0.861861E+12 | 0.09 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.265505E+12 | 0.263821E+12 | 282482.82 | 281189.44 | 0.40 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 66859211.40 | 66859211.40 | 6688.28 | 27-FEB-14:00 | 6688.28 | 0.00 |
March | 0.00 | 0.00 | 1181470.97 | 1181470.97 | 652.55 | 14-MAR-13:00 | 652.55 | 0.00 |
April | 0.00 | 0.00 | 0.100375E+10 | 0.100375E+10 | 13445.87 | 07-APR-13:00 | 13445.87 | 0.00 |
May | 0.00 | 0.00 | 0.373266E+10 | 0.373266E+10 | 16748.25 | 20-MAY-15:02 | 16748.25 | 0.03 |
June | 0.00 | 0.00 | 0.964258E+10 | 0.950698E+10 | 20298.04 | 20-JUN-18:02 | 16525.78 | 0.19 |
July | 0.00 | 0.00 | 0.168625E+11 | 0.163872E+11 | 21351.77 | 18-JUL-19:55 | 12999.34 | 0.35 |
August | 0.00 | 0.00 | 0.135751E+11 | 0.135751E+11 | 18704.16 | 05-AUG-15:02 | 18704.16 | 0.16 |
September | 0.00 | 0.00 | 0.799166E+10 | 0.765167E+10 | 24963.93 | 07-SEP-15:02 | 15643.27 | 0.16 |
October | 0.00 | 0.00 | 0.154185E+10 | 0.154185E+10 | 15094.57 | 18-OCT-15:01 | 15094.57 | 0.00 |
November | 0.00 | 0.00 | 95107362.99 | 95107362.99 | 4584.43 | 17-NOV-17:00 | 4584.43 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.545133E+11 | 0.535624E+11 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.168625E+11 | 0.163872E+11 | 24963.93 | 18704.16 | 0.35 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 38569846.48 | 35963137.43 | 15602.46 | 21-JAN-16:01 | 15602.46 | 0.00 |
February | 0.00 | 0.00 | 0.545721E+09 | 0.539698E+09 | 16197.97 | 27-FEB-16:01 | 16197.97 | 0.01 |
March | 0.00 | 0.00 | 0.843069E+09 | 0.837400E+09 | 15778.79 | 22-MAR-15:01 | 15778.79 | 0.00 |
April | 0.00 | 0.00 | 0.206071E+10 | 0.191382E+10 | 16673.34 | 07-APR-15:01 | 16673.34 | 0.09 |
May | 0.00 | 0.00 | 0.390404E+10 | 0.316963E+10 | 17000.68 | 31-MAY-18:01 | 17000.68 | 0.31 |
June | 0.00 | 0.00 | 0.702393E+10 | 0.505010E+10 | 16667.03 | 10-JUN-18:02 | 16667.03 | 0.66 |
July | 0.00 | 0.00 | 0.985807E+10 | 0.682029E+10 | 16937.70 | 19-JUL-08:61 | 14850.38 | 0.87 |
August | 0.00 | 0.00 | 0.859106E+10 | 0.623608E+10 | 17438.81 | 11-AUG-15:01 | 17438.81 | 0.77 |
September | 0.00 | 0.00 | 0.549482E+10 | 0.386796E+10 | 16313.88 | 30-SEP-18:01 | 16313.88 | 0.56 |
October | 0.00 | 0.00 | 0.206531E+10 | 0.185518E+10 | 17176.89 | 18-OCT-15:01 | 17176.89 | 0.12 |
November | 0.00 | 0.00 | 0.431319E+09 | 0.394971E+09 | 15778.91 | 06-NOV-16:01 | 15778.91 | 0.02 |
December | 0.00 | 0.00 | 45549815.71 | 41566298.05 | 15778.93 | 07-DEC-16:01 | 15778.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.409022E+11 | 0.307627E+11 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 38569846.48 | 35963137.43 | 15602.46 | 14850.38 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.985807E+10 | 0.682029E+10 | 17438.81 | 17438.81 | 0.87 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 11089760.90 | 10295671.97 | 4001.86 | 13-JAN-19:03 | 3361.19 | 0.00 |
February | 0.00 | 0.00 | 0.135686E+09 | 0.133533E+09 | 15853.44 | 26-FEB-17:41 | 15853.44 | 0.00 |
March | 0.00 | 0.00 | 0.322748E+09 | 0.321454E+09 | 15046.11 | 02-MAR-16:01 | 15046.11 | 0.00 |
April | 0.00 | 0.00 | 0.920392E+09 | 0.845479E+09 | 17225.31 | 24-APR-19:31 | 17225.31 | 0.06 |
May | 0.00 | 0.00 | 0.244263E+10 | 0.185256E+10 | 19003.47 | 31-MAY-16:11 | 19003.47 | 0.25 |
June | 0.00 | 0.00 | 0.535226E+10 | 0.372918E+10 | 17183.73 | 07-JUN-19:41 | 17183.73 | 0.56 |
July | 0.00 | 0.00 | 0.783944E+10 | 0.537728E+10 | 17769.40 | 19-JUL-08:51 | 14573.22 | 0.72 |
August | 0.00 | 0.00 | 0.597897E+10 | 0.411387E+10 | 17198.61 | 11-AUG-08:51 | 17198.61 | 0.65 |
September | 0.00 | 0.00 | 0.324238E+10 | 0.208538E+10 | 16990.56 | 06-SEP-21:51 | 13893.07 | 0.42 |
October | 0.00 | 0.00 | 0.645347E+09 | 0.577821E+09 | 16824.60 | 02-OCT-16:41 | 16824.60 | 0.05 |
November | 0.00 | 0.00 | 87067495.83 | 78879233.96 | 14766.62 | 06-NOV-16:01 | 14766.62 | 0.00 |
December | 0.00 | 0.00 | 16987752.85 | 15498583.30 | 9841.16 | 06-DEC-16:01 | 9841.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.269950E+11 | 0.191412E+11 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 11089760.90 | 10295671.97 | 4001.86 | 3361.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.783944E+10 | 0.537728E+10 | 19003.47 | 19003.47 | 0.72 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.171170E+10 | 0.171170E+10 | 44069.03 | 01-JAN-13:30 | 44069.03 | 0.00 |
February | 0.00 | 0.00 | 0.860813E+10 | 0.860813E+10 | 55663.85 | 27-FEB-13:30 | 55663.85 | 0.00 |
March | 0.00 | 0.00 | 0.111337E+11 | 0.111337E+11 | 53887.05 | 01-MAR-13:30 | 53887.05 | 0.00 |
April | 0.00 | 0.00 | 0.157491E+11 | 0.156626E+11 | 47478.22 | 06-APR-13:40 | 47478.22 | 0.00 |
May | 0.00 | 0.00 | 0.186344E+11 | 0.141638E+11 | 41981.15 | 20-MAY-12:30 | 31163.01 | 0.23 |
June | 0.00 | 0.00 | 0.346473E+11 | 0.193680E+11 | 39594.38 | 21-JUN-13:10 | 28730.30 | 0.70 |
July | 0.00 | 0.00 | 0.502243E+11 | 0.283873E+11 | 48141.80 | 17-JUL-13:10 | 43565.50 | 0.91 |
August | 0.00 | 0.00 | 0.528963E+11 | 0.331645E+11 | 55043.30 | 30-AUG-13:30 | 40226.07 | 0.91 |
September | 0.00 | 0.00 | 0.432250E+11 | 0.305352E+11 | 60226.79 | 03-SEP-13:00 | 47341.20 | 0.61 |
October | 0.00 | 0.00 | 0.301767E+11 | 0.298469E+11 | 64440.30 | 18-OCT-13:00 | 64440.30 | 0.03 |
November | 0.00 | 0.00 | 0.160596E+11 | 0.160596E+11 | 53628.01 | 03-NOV-13:30 | 53628.01 | 0.00 |
December | 0.00 | 0.00 | 0.950476E+09 | 0.950476E+09 | 24005.31 | 12-DEC-14:30 | 24005.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.284017E+12 | 0.209592E+12 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 0.950476E+09 | 0.950476E+09 | 24005.31 | 24005.31 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.528963E+11 | 0.331645E+11 | 64440.30 | 64440.30 | 0.91 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.201285E+09 | 0.201002E+09 | 66267.48 | 15-JAN-09:01 | 66267.48 | 0.00 |
February | 0.00 | 0.00 | 0.923127E+09 | 0.923127E+09 | 69965.04 | 27-FEB-16:01 | 69965.04 | 0.00 |
March | 0.00 | 0.00 | 0.256485E+10 | 0.256485E+10 | 69866.14 | 29-MAR-18:01 | 69866.14 | 0.00 |
April | 0.00 | 0.00 | 0.969320E+10 | 0.904619E+10 | 78564.19 | 07-APR-15:01 | 78564.19 | 0.08 |
May | 0.00 | 0.00 | 0.200696E+11 | 0.175451E+11 | 80089.97 | 31-MAY-15:01 | 80089.97 | 0.20 |
June | 0.00 | 0.00 | 0.375177E+11 | 0.308624E+11 | 81442.43 | 21-JUN-21:51 | 72499.34 | 0.43 |
July | 0.00 | 0.00 | 0.474721E+11 | 0.368540E+11 | 85975.39 | 26-JUL-08:61 | 85975.39 | 0.61 |
August | 0.00 | 0.00 | 0.378458E+11 | 0.305515E+11 | 83017.48 | 07-AUG-08:21 | 83017.48 | 0.51 |
September | 0.00 | 0.00 | 0.240020E+11 | 0.181737E+11 | 83354.05 | 07-SEP-15:02 | 70749.38 | 0.38 |
October | 0.00 | 0.00 | 0.964866E+10 | 0.886699E+10 | 78416.60 | 18-OCT-15:01 | 78416.60 | 0.09 |
November | 0.00 | 0.00 | 0.255121E+10 | 0.253137E+10 | 69928.98 | 05-NOV-08:62 | 69928.98 | 0.01 |
December | 0.00 | 0.00 | 0.330955E+09 | 0.330955E+09 | 67899.54 | 10-DEC-09:02 | 67899.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.192821E+12 | 0.158451E+12 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 0.201285E+09 | 0.201002E+09 | 66267.48 | 66267.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.474721E+11 | 0.368540E+11 | 85975.39 | 85975.39 | 0.61 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 60353161.10 | 54298081.14 | 9371.84 | 14-JAN-16:02 | 9371.84 | 0.00 |
February | 0.00 | 0.00 | 0.535095E+09 | 0.517241E+09 | 14448.64 | 27-FEB-16:01 | 14448.64 | 0.01 |
March | 0.00 | 0.00 | 0.882666E+09 | 0.872169E+09 | 14074.32 | 22-MAR-15:01 | 14074.32 | 0.01 |
April | 0.00 | 0.00 | 0.221916E+10 | 0.195448E+10 | 14871.18 | 07-APR-15:01 | 14871.18 | 0.13 |
May | 0.00 | 0.00 | 0.356499E+10 | 0.279710E+10 | 15164.00 | 31-MAY-18:01 | 15164.00 | 0.34 |
June | 0.00 | 0.00 | 0.756609E+10 | 0.553824E+10 | 14863.18 | 10-JUN-18:02 | 14863.18 | 0.70 |
July | 0.00 | 0.00 | 0.105946E+11 | 0.768439E+10 | 14843.85 | 19-JUL-08:61 | 13400.55 | 0.90 |
August | 0.00 | 0.00 | 0.924606E+10 | 0.698910E+10 | 15553.08 | 11-AUG-15:01 | 15553.08 | 0.80 |
September | 0.00 | 0.00 | 0.548901E+10 | 0.389892E+10 | 14549.69 | 30-SEP-18:01 | 14549.69 | 0.59 |
October | 0.00 | 0.00 | 0.205208E+10 | 0.176471E+10 | 15321.96 | 18-OCT-15:01 | 15321.96 | 0.14 |
November | 0.00 | 0.00 | 0.396287E+09 | 0.336044E+09 | 14072.60 | 02-NOV-15:01 | 14072.60 | 0.04 |
December | 0.00 | 0.00 | 56619375.71 | 51821876.29 | 10060.49 | 10-DEC-16:01 | 10060.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.426631E+11 | 0.324585E+11 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 56619375.71 | 51821876.29 | 9371.84 | 9371.84 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.105946E+11 | 0.768439E+10 | 15553.08 | 15553.08 | 0.90 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 12304340.26 | 11729573.63 | 4664.60 | 17-JAN-09:03 | 4664.60 | 0.00 |
February | 0.00 | 0.00 | 0.117544E+09 | 0.108844E+09 | 13371.39 | 26-FEB-09:01 | 13371.39 | 0.00 |
March | 0.00 | 0.00 | 0.251649E+09 | 0.243991E+09 | 12821.01 | 27-MAR-15:01 | 12821.01 | 0.00 |
April | 0.00 | 0.00 | 0.114964E+10 | 0.993700E+09 | 14130.89 | 07-APR-15:01 | 14130.89 | 0.10 |
May | 0.00 | 0.00 | 0.235883E+10 | 0.176323E+10 | 15189.27 | 31-MAY-08:51 | 15189.27 | 0.29 |
June | 0.00 | 0.00 | 0.593560E+10 | 0.424232E+10 | 17632.75 | 22-JUN-08:32 | 16301.24 | 0.59 |
July | 0.00 | 0.00 | 0.844115E+10 | 0.599903E+10 | 17651.02 | 16-JUL-08:32 | 16071.01 | 0.75 |
August | 0.00 | 0.00 | 0.665791E+10 | 0.474108E+10 | 16978.40 | 11-AUG-08:51 | 16978.40 | 0.69 |
September | 0.00 | 0.00 | 0.328789E+10 | 0.213587E+10 | 14724.38 | 06-SEP-21:51 | 11878.20 | 0.47 |
October | 0.00 | 0.00 | 0.626696E+09 | 0.524462E+09 | 14560.19 | 18-OCT-15:01 | 14560.19 | 0.07 |
November | 0.00 | 0.00 | 49288661.88 | 34534037.56 | 8950.03 | 06-NOV-09:01 | 8950.03 | 0.01 |
December | 0.00 | 0.00 | 14034339.81 | 13271225.44 | 4653.61 | 20-DEC-09:03 | 3508.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.289025E+11 | 0.208121E+11 | 0.25 | |||
Minimum of Months | 0.00 | 0.00 | 12304340.26 | 11729573.63 | 4653.61 | 3508.46 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.844115E+10 | 0.599903E+10 | 17651.02 | 16978.40 | 0.75 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6781550.23 | 5901989.19 | 3999.20 | 21-JAN-16:01 | 3999.20 | 0.00 |
February | 0.00 | 0.00 | 0.123777E+09 | 0.121737E+09 | 4270.06 | 27-FEB-16:01 | 4270.06 | 0.01 |
March | 0.00 | 0.00 | 0.194383E+09 | 0.193287E+09 | 4159.71 | 22-MAR-15:01 | 4159.71 | 0.00 |
April | 0.00 | 0.00 | 0.505153E+09 | 0.468387E+09 | 4395.31 | 07-APR-15:01 | 4395.31 | 0.08 |
May | 0.00 | 0.00 | 0.984411E+09 | 0.812020E+09 | 4481.18 | 31-MAY-18:01 | 4481.18 | 0.29 |
June | 0.00 | 0.00 | 0.174933E+10 | 0.127390E+10 | 4392.85 | 10-JUN-18:02 | 4392.85 | 0.63 |
July | 0.00 | 0.00 | 0.247318E+10 | 0.172237E+10 | 4627.63 | 19-JUL-08:61 | 3818.58 | 0.86 |
August | 0.00 | 0.00 | 0.211030E+10 | 0.153933E+10 | 4596.67 | 11-AUG-15:01 | 4596.67 | 0.74 |
September | 0.00 | 0.00 | 0.128517E+10 | 0.907062E+09 | 4299.78 | 30-SEP-18:01 | 4299.78 | 0.51 |
October | 0.00 | 0.00 | 0.439763E+09 | 0.397041E+09 | 4528.04 | 18-OCT-15:01 | 4528.04 | 0.09 |
November | 0.00 | 0.00 | 89230095.38 | 79587930.07 | 4159.66 | 06-NOV-16:01 | 4159.66 | 0.02 |
December | 0.00 | 0.00 | 8309502.28 | 6720181.69 | 4158.13 | 10-DEC-16:01 | 4158.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.996978E+10 | 0.752735E+10 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 6781550.23 | 5901989.19 | 3999.20 | 3818.58 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.247318E+10 | 0.172237E+10 | 4627.63 | 4596.67 | 0.86 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1645712.78 | 1343398.56 | 1044.21 | 01-JAN-16:03 | 892.69 | 0.00 |
February | 0.00 | 0.00 | 28669679.24 | 27861978.38 | 4228.99 | 26-FEB-17:41 | 4228.99 | 0.00 |
March | 0.00 | 0.00 | 69479699.39 | 68825095.63 | 3953.07 | 02-MAR-16:01 | 3953.07 | 0.00 |
April | 0.00 | 0.00 | 0.213792E+09 | 0.196995E+09 | 4925.92 | 25-APR-19:02 | 4925.92 | 0.05 |
May | 0.00 | 0.00 | 0.619886E+09 | 0.474019E+09 | 4992.03 | 31-MAY-16:11 | 4992.03 | 0.24 |
June | 0.00 | 0.00 | 0.135427E+10 | 0.945123E+09 | 4576.79 | 21-JUN-21:51 | 3929.50 | 0.55 |
July | 0.00 | 0.00 | 0.200016E+10 | 0.137850E+10 | 4708.61 | 19-JUL-08:51 | 3743.30 | 0.72 |
August | 0.00 | 0.00 | 0.147629E+10 | 0.102241E+10 | 4473.56 | 11-AUG-08:51 | 4473.56 | 0.62 |
September | 0.00 | 0.00 | 0.738480E+09 | 0.474138E+09 | 4526.80 | 06-SEP-21:51 | 3581.31 | 0.39 |
October | 0.00 | 0.00 | 0.111742E+09 | 98764486.84 | 4405.33 | 02-OCT-16:41 | 4405.33 | 0.03 |
November | 0.00 | 0.00 | 13465643.04 | 11168219.20 | 2789.04 | 04-NOV-15:01 | 2789.04 | 0.01 |
December | 0.00 | 0.00 | 2129070.86 | 1789206.83 | 2537.43 | 06-DEC-16:01 | 2537.43 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.663000E+10 | 0.470094E+10 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 1645712.78 | 1343398.56 | 1044.21 | 892.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.200016E+10 | 0.137850E+10 | 4992.03 | 4992.03 | 0.72 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.127229E+10 | 0.119429E+10 | 20125.42 | 03-JAN-16:01 | 20125.42 | 0.02 |
February | 0.00 | 0.00 | 0.274022E+10 | 0.268339E+10 | 20679.48 | 27-FEB-16:01 | 20679.48 | 0.02 |
March | 0.00 | 0.00 | 0.309710E+10 | 0.306555E+10 | 20138.86 | 14-MAR-18:01 | 20138.86 | 0.01 |
April | 0.00 | 0.00 | 0.391787E+10 | 0.361397E+10 | 21284.83 | 07-APR-15:01 | 21284.83 | 0.12 |
May | 0.00 | 0.00 | 0.501681E+10 | 0.400880E+10 | 21578.13 | 29-MAY-18:01 | 21578.13 | 0.31 |
June | 0.00 | 0.00 | 0.841071E+10 | 0.575608E+10 | 21259.98 | 10-JUN-18:02 | 21259.98 | 0.67 |
July | 0.00 | 0.00 | 0.123112E+11 | 0.837665E+10 | 22101.26 | 19-JUL-08:61 | 18716.66 | 0.85 |
August | 0.00 | 0.00 | 0.122872E+11 | 0.914312E+10 | 21602.22 | 11-AUG-08:61 | 21602.22 | 0.77 |
September | 0.00 | 0.00 | 0.958768E+10 | 0.730120E+10 | 20814.59 | 30-SEP-18:01 | 20814.59 | 0.60 |
October | 0.00 | 0.00 | 0.626242E+10 | 0.575039E+10 | 21923.92 | 18-OCT-15:01 | 21923.92 | 0.20 |
November | 0.00 | 0.00 | 0.329726E+10 | 0.311506E+10 | 20369.19 | 17-NOV-16:01 | 20369.19 | 0.08 |
December | 0.00 | 0.00 | 0.127729E+10 | 0.122027E+10 | 20138.19 | 01-DEC-16:01 | 20138.19 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.694781E+11 | 0.552288E+11 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.127229E+10 | 0.119429E+10 | 20125.42 | 18716.66 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.123112E+11 | 0.914312E+10 | 22101.26 | 21923.92 | 0.85 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 184043.16 | 741195.59 | 11-JAN-06:00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 64858.55 | 581543.28 | 01-FEB-03:32 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 41319.12 | 292669.56 | 04-MAR-24:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 24805.41 | 171629.95 | 01-APR-08:62 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22827.12 | 157833.71 | 15-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15560.44 | 130726.92 | 16-JUN-15:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 7806.79 | 110915.28 | 09-JUL-02:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 10880.62 | 115651.54 | 17-AUG-15:05 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16500.38 | 176647.01 | 13-SEP-08:62 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27529.58 | 168749.50 | 31-OCT-15:03 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 42843.33 | 258783.43 | 26-NOV-19:01 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 88067.47 | 717230.47 | 29-DEC-09:03 |
Annual Sum or Average | 0.00 | 45654.84 | ||||
Minimum of Months | 0.00 | 0.00 | 7806.79 | 110915.28 | ||
Maximum of Months | 0.00 | 0.00 | 184043.16 | 741195.59 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1806.45 | 59908.41 | 02-JAN-16:03 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 7355.47 | 209823.20 | 27-FEB-16:01 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 8671.52 | 137053.14 | 28-MAR-15:02 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 23012.60 | 315855.40 | 06-APR-15:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 47647.69 | 374956.63 | 19-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 109059.37 | 466859.70 | 20-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 165306.38 | 532189.85 | 17-JUL-18:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 142354.22 | 457241.05 | 07-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 91420.88 | 479485.10 | 03-SEP-18:02 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 31991.00 | 391333.36 | 18-OCT-15:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 11325.41 | 172785.93 | 04-NOV-15:01 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 1652.65 | 49027.95 | 07-DEC-16:03 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 53788.57 | 0.00 | ||||
Minimum of Months | 1652.65 | 49027.95 | 0.00 | 0.00 | ||
Maximum of Months | 165306.38 | 532189.85 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 30172.88 | 63136.42 | 31-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 30390.62 | 63397.47 | 17-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 30086.27 | 63304.05 | 02-MAR-07:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 28946.49 | 61567.92 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 27358.38 | 58928.39 | 01-MAY-06:50 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25711.97 | 55143.72 | 01-JUN-06:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 24415.25 | 51867.54 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23884.58 | 50058.19 | 01-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24196.75 | 51307.01 | 29-SEP-06:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25298.08 | 54363.96 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 26905.10 | 57846.90 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 28599.61 | 60903.94 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 27145.24 | ||||
Minimum of Months | 0.00 | 0.00 | 23884.58 | 50058.19 | ||
Maximum of Months | 0.00 | 0.00 | 30390.62 | 63397.47 |
Report: FanReportMonthly
For: SWHSYS1 HPWH FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148142E+10 | 0.11 | 553.22 | 01-JAN-00:20 | 0.11 |
February | 0.892476E+09 | 0.08 | 553.22 | 01-FEB-00:05 | 0.11 |
March | 0.931165E+09 | 0.08 | 553.22 | 01-MAR-00:05 | 0.11 |
April | 0.763445E+09 | 0.07 | 553.22 | 01-APR-01:07 | 0.11 |
May | 0.705299E+09 | 0.07 | 553.22 | 01-MAY-04:15 | 0.11 |
June | 0.585230E+09 | 0.07 | 553.22 | 01-JUN-04:07 | 0.11 |
July | 0.548383E+09 | 0.06 | 553.22 | 01-JUL-05:06 | 0.11 |
August | 0.551890E+09 | 0.06 | 553.22 | 01-AUG-04:07 | 0.11 |
September | 0.568516E+09 | 0.06 | 553.22 | 01-SEP-04:07 | 0.11 |
October | 0.678759E+09 | 0.07 | 553.22 | 01-OCT-05:05 | 0.11 |
November | 0.781199E+09 | 0.07 | 553.22 | 01-NOV-00:10 | 0.11 |
December | 0.987326E+09 | 0.08 | 553.22 | 01-DEC-00:05 | 0.11 |
Annual Sum or Average | 0.947511E+10 | 0.08 | |||
Minimum of Months | 0.548383E+09 | 0.06 | 553.22 | 0.11 | |
Maximum of Months | 0.148142E+10 | 0.11 | 553.22 | 0.11 |
Report: FanReportMonthly
For: SWHSYSLAUNDRY HPWH FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.187541E+10 | 0.11 | 700.51 | 01-JAN-00:30 | 0.11 |
February | 0.509582E+09 | 0.07 | 700.51 | 01-FEB-00:05 | 0.11 |
March | 0.561150E+09 | 0.07 | 700.51 | 01-MAR-17:10 | 0.11 |
April | 0.542173E+09 | 0.07 | 700.51 | 01-APR-16:05 | 0.11 |
May | 0.560228E+09 | 0.06 | 700.51 | 01-MAY-16:10 | 0.11 |
June | 0.542417E+09 | 0.06 | 700.51 | 01-JUN-16:10 | 0.11 |
July | 0.559822E+09 | 0.06 | 700.51 | 01-JUL-16:10 | 0.11 |
August | 0.560176E+09 | 0.06 | 700.51 | 01-AUG-16:10 | 0.11 |
September | 0.541932E+09 | 0.06 | 700.51 | 01-SEP-16:10 | 0.11 |
October | 0.559799E+09 | 0.06 | 700.51 | 01-OCT-16:10 | 0.11 |
November | 0.541890E+09 | 0.07 | 700.51 | 01-NOV-16:10 | 0.11 |
December | 0.563518E+09 | 0.07 | 700.51 | 01-DEC-17:10 | 0.11 |
Annual Sum or Average | 0.791810E+10 | 0.07 | |||
Minimum of Months | 0.509582E+09 | 0.06 | 700.51 | 0.11 | |
Maximum of Months | 0.187541E+10 | 0.11 | 700.51 | 0.11 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.80 | 1299.30 | 05-JAN-16:15 | 1.00 |
February | 0.244774E+10 | 0.79 | 1299.30 | 23-FEB-09:01 | 1.00 |
March | 0.271000E+10 | 0.79 | 1299.30 | 10-MAR-19:02 | 1.00 |
April | 0.262258E+10 | 0.79 | 1299.30 | 08-APR-15:15 | 1.00 |
May | 0.271000E+10 | 0.79 | 1299.30 | 19-MAY-15:40 | 1.00 |
June | 0.262258E+10 | 0.79 | 1299.30 | 20-JUN-15:50 | 0.99 |
July | 0.271000E+10 | 0.79 | 1299.30 | 01-JUL-09:08 | 0.99 |
August | 0.271000E+10 | 0.79 | 1299.30 | 05-AUG-16:10 | 1.00 |
September | 0.262258E+10 | 0.79 | 1299.30 | 01-SEP-09:15 | 1.00 |
October | 0.271000E+10 | 0.79 | 1299.30 | 23-OCT-15:03 | 1.00 |
November | 0.262258E+10 | 0.79 | 1299.30 | 07-NOV-16:01 | 1.01 |
December | 0.271000E+10 | 0.79 | 1299.30 | 16-DEC-19:03 | 1.00 |
Annual Sum or Average | 0.319080E+11 | 0.79 | |||
Minimum of Months | 0.244774E+10 | 0.79 | 1299.30 | 0.99 | |
Maximum of Months | 0.271000E+10 | 0.80 | 1299.30 | 1.01 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.300171E+11 | 0.82 | 18887.24 | 02-JAN-22:10 | 1.10 |
February | 0.289319E+11 | 0.85 | 22093.07 | 27-FEB-22:10 | 1.20 |
March | 0.328511E+11 | 0.86 | 21100.16 | 29-MAR-21:10 | 1.17 |
April | 0.330927E+11 | 0.88 | 26129.74 | 06-APR-21:10 | 1.33 |
May | 0.355174E+11 | 0.90 | 29649.74 | 19-MAY-21:10 | 1.43 |
June | 0.372041E+11 | 0.93 | 30645.52 | 30-JUN-21:10 | 1.46 |
July | 0.405781E+11 | 0.96 | 33043.26 | 17-JUL-21:10 | 1.53 |
August | 0.405539E+11 | 0.96 | 33912.98 | 08-AUG-21:10 | 1.55 |
September | 0.372652E+11 | 0.93 | 33796.11 | 01-SEP-21:10 | 1.56 |
October | 0.360810E+11 | 0.90 | 30193.47 | 18-OCT-21:03 | 1.46 |
November | 0.326639E+11 | 0.87 | 25767.44 | 03-NOV-21:10 | 1.32 |
December | 0.315504E+11 | 0.84 | 20220.34 | 06-DEC-22:10 | 1.14 |
Annual Sum or Average | 0.416307E+12 | 0.89 | |||
Minimum of Months | 0.289319E+11 | 0.82 | 18887.24 | 1.10 | |
Maximum of Months | 0.405781E+11 | 0.96 | 33912.98 | 1.56 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.31 | 76.61 | 01-JAN-00:10 | 0.30 |
February | 0.185347E+09 | 0.30 | 76.61 | 01-FEB-00:05 | 0.31 |
March | 0.205205E+09 | 0.30 | 76.61 | 01-MAR-00:05 | 0.30 |
April | 0.198586E+09 | 0.30 | 76.61 | 01-APR-00:10 | 0.30 |
May | 0.205205E+09 | 0.30 | 76.61 | 01-MAY-00:05 | 0.30 |
June | 0.198586E+09 | 0.30 | 76.61 | 01-JUN-00:05 | 0.30 |
July | 0.205205E+09 | 0.30 | 76.61 | 01-JUL-00:10 | 0.30 |
August | 0.205205E+09 | 0.30 | 76.61 | 01-AUG-00:05 | 0.30 |
September | 0.198586E+09 | 0.30 | 76.61 | 01-SEP-00:05 | 0.30 |
October | 0.205205E+09 | 0.30 | 76.61 | 01-OCT-00:10 | 0.30 |
November | 0.198586E+09 | 0.30 | 76.61 | 01-NOV-00:05 | 0.30 |
December | 0.205205E+09 | 0.30 | 76.61 | 01-DEC-00:05 | 0.30 |
Annual Sum or Average | 0.241613E+10 | 0.30 | |||
Minimum of Months | 0.185347E+09 | 0.30 | 76.61 | 0.30 | |
Maximum of Months | 0.205205E+09 | 0.31 | 76.61 | 0.31 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.22 | 612.92 | 01-JAN-07:10 | 0.30 |
February | 0.105030E+10 | 0.22 | 612.92 | 01-FEB-07:10 | 0.31 |
March | 0.116283E+10 | 0.22 | 612.92 | 01-MAR-07:05 | 0.30 |
April | 0.112532E+10 | 0.22 | 612.92 | 01-APR-06:05 | 0.30 |
May | 0.116283E+10 | 0.21 | 612.92 | 01-MAY-06:05 | 0.30 |
June | 0.112532E+10 | 0.21 | 612.92 | 01-JUN-06:05 | 0.30 |
July | 0.116283E+10 | 0.21 | 612.92 | 01-JUL-06:05 | 0.30 |
August | 0.116283E+10 | 0.21 | 612.92 | 01-AUG-06:05 | 0.30 |
September | 0.112532E+10 | 0.21 | 612.92 | 01-SEP-06:05 | 0.30 |
October | 0.116283E+10 | 0.21 | 612.92 | 01-OCT-06:10 | 0.30 |
November | 0.112532E+10 | 0.22 | 612.92 | 01-NOV-06:05 | 0.30 |
December | 0.116283E+10 | 0.22 | 612.92 | 01-DEC-07:05 | 0.30 |
Annual Sum or Average | 0.136914E+11 | 0.21 | |||
Minimum of Months | 0.105030E+10 | 0.21 | 612.92 | 0.30 | |
Maximum of Months | 0.116283E+10 | 0.22 | 612.92 | 0.31 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.369355E+09 | 0.54 | 916.45 | 01-JAN-16:02 | 0.66 |
February | 0.240707E+09 | 0.51 | 916.45 | 01-FEB-09:01 | 0.66 |
March | 0.221617E+09 | 0.51 | 916.45 | 01-MAR-16:01 | 0.66 |
April | 0.208941E+09 | 0.52 | 916.45 | 01-APR-15:01 | 0.66 |
May | 0.284891E+09 | 0.55 | 916.45 | 01-MAY-15:01 | 0.66 |
June | 0.411062E+09 | 0.60 | 916.45 | 01-JUN-08:61 | 0.65 |
July | 0.551597E+09 | 0.62 | 916.45 | 01-JUL-08:61 | 0.65 |
August | 0.498987E+09 | 0.61 | 916.45 | 01-AUG-08:62 | 0.65 |
September | 0.339490E+09 | 0.58 | 916.45 | 01-SEP-08:62 | 0.65 |
October | 0.196446E+09 | 0.53 | 916.45 | 01-OCT-15:02 | 0.65 |
November | 0.191452E+09 | 0.51 | 916.45 | 01-NOV-15:01 | 0.66 |
December | 0.302408E+09 | 0.52 | 916.45 | 01-DEC-09:01 | 0.66 |
Annual Sum or Average | 0.381695E+10 | 0.55 | |||
Minimum of Months | 0.191452E+09 | 0.51 | 916.45 | 0.65 | |
Maximum of Months | 0.551597E+09 | 0.62 | 916.45 | 0.66 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.415055E+09 | 0.58 | 873.80 | 01-JAN-09:01 | 0.66 |
February | 0.257089E+09 | 0.52 | 873.80 | 01-FEB-09:01 | 0.66 |
March | 0.221246E+09 | 0.49 | 873.80 | 01-MAR-09:01 | 0.66 |
April | 0.149683E+09 | 0.46 | 873.80 | 01-APR-15:01 | 0.66 |
May | 0.198373E+09 | 0.46 | 873.80 | 01-MAY-15:01 | 0.66 |
June | 0.314930E+09 | 0.48 | 873.80 | 01-JUN-08:61 | 0.65 |
July | 0.438106E+09 | 0.50 | 873.80 | 01-JUL-08:51 | 0.65 |
August | 0.347963E+09 | 0.49 | 873.80 | 01-AUG-08:51 | 0.65 |
September | 0.212087E+09 | 0.46 | 873.80 | 01-SEP-08:51 | 0.65 |
October | 0.130985E+09 | 0.46 | 873.80 | 01-OCT-15:02 | 0.65 |
November | 0.210350E+09 | 0.49 | 873.80 | 01-NOV-15:01 | 0.66 |
December | 0.339626E+09 | 0.55 | 873.80 | 01-DEC-09:01 | 0.66 |
Annual Sum or Average | 0.323549E+10 | 0.49 | |||
Minimum of Months | 0.130985E+09 | 0.46 | 873.80 | 0.65 | |
Maximum of Months | 0.438106E+09 | 0.58 | 873.80 | 0.66 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.321227E+09 | 0.12 | 1666.24 | 01-JAN-13:30 | 0.66 |
February | 0.390813E+09 | 0.12 | 2516.29 | 26-FEB-13:30 | 0.66 |
March | 0.495339E+09 | 0.17 | 2470.48 | 01-MAR-13:30 | 0.66 |
April | 0.715984E+09 | 0.29 | 1727.48 | 06-APR-13:25 | 0.66 |
May | 0.876380E+09 | 0.37 | 1440.72 | 20-MAY-12:30 | 0.65 |
June | 0.153688E+10 | 0.58 | 1383.20 | 24-JUN-13:30 | 0.65 |
July | 0.208463E+10 | 0.64 | 1679.79 | 17-JUL-13:30 | 0.66 |
August | 0.224908E+10 | 0.64 | 2683.17 | 29-AUG-13:05 | 0.66 |
September | 0.186964E+10 | 0.55 | 3035.22 | 26-SEP-12:40 | 0.65 |
October | 0.133024E+10 | 0.44 | 2705.98 | 18-OCT-12:40 | 0.66 |
November | 0.728975E+09 | 0.28 | 2460.06 | 03-NOV-13:30 | 0.66 |
December | 0.161443E+09 | 0.08 | 1000.20 | 12-DEC-14:30 | 0.66 |
Annual Sum or Average | 0.127606E+11 | 0.36 | |||
Minimum of Months | 0.161443E+09 | 0.08 | 1000.20 | 0.65 | |
Maximum of Months | 0.224908E+10 | 0.64 | 3035.22 | 0.66 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.186570E+10 | 0.51 | 4264.04 | 03-JAN-16:01 | 0.66 |
February | 0.949338E+09 | 0.48 | 4264.04 | 01-FEB-09:01 | 0.66 |
March | 0.740745E+09 | 0.47 | 4264.04 | 02-MAR-16:01 | 0.66 |
April | 0.758337E+09 | 0.44 | 4264.04 | 01-APR-08:62 | 0.66 |
May | 0.129084E+10 | 0.43 | 4264.04 | 01-MAY-15:01 | 0.66 |
June | 0.219600E+10 | 0.44 | 4264.04 | 01-JUN-08:61 | 0.65 |
July | 0.269184E+10 | 0.46 | 4264.04 | 01-JUL-08:51 | 0.65 |
August | 0.224074E+10 | 0.43 | 4264.04 | 01-AUG-08:51 | 0.65 |
September | 0.139899E+10 | 0.42 | 4264.04 | 01-SEP-08:51 | 0.66 |
October | 0.753255E+09 | 0.44 | 4264.04 | 01-OCT-08:62 | 0.65 |
November | 0.768370E+09 | 0.46 | 4264.04 | 01-NOV-15:01 | 0.66 |
December | 0.123177E+10 | 0.48 | 4264.04 | 01-DEC-16:01 | 0.66 |
Annual Sum or Average | 0.168859E+11 | 0.45 | |||
Minimum of Months | 0.740745E+09 | 0.42 | 4264.04 | 0.65 | |
Maximum of Months | 0.269184E+10 | 0.51 | 4264.04 | 0.66 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.342916E+09 | 0.53 | 816.92 | 02-JAN-09:01 | 0.66 |
February | 0.223233E+09 | 0.52 | 816.92 | 01-FEB-09:01 | 0.66 |
March | 0.207542E+09 | 0.53 | 816.92 | 01-MAR-09:01 | 0.66 |
April | 0.216374E+09 | 0.55 | 816.92 | 01-APR-15:01 | 0.66 |
May | 0.264374E+09 | 0.57 | 816.92 | 01-MAY-08:62 | 0.65 |
June | 0.436136E+09 | 0.62 | 816.92 | 01-JUN-08:61 | 0.65 |
July | 0.580485E+09 | 0.64 | 816.92 | 01-JUL-08:61 | 0.65 |
August | 0.525220E+09 | 0.63 | 816.92 | 01-AUG-08:62 | 0.65 |
September | 0.331621E+09 | 0.60 | 816.92 | 01-SEP-08:62 | 0.65 |
October | 0.190318E+09 | 0.54 | 816.92 | 01-OCT-15:02 | 0.65 |
November | 0.179101E+09 | 0.50 | 816.92 | 01-NOV-15:01 | 0.66 |
December | 0.277548E+09 | 0.51 | 816.92 | 01-DEC-09:01 | 0.66 |
Annual Sum or Average | 0.377487E+10 | 0.56 | |||
Minimum of Months | 0.179101E+09 | 0.50 | 816.92 | 0.65 | |
Maximum of Months | 0.580485E+09 | 0.64 | 816.92 | 0.66 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.394909E+09 | 0.57 | 776.06 | 01-JAN-16:02 | 0.66 |
February | 0.234693E+09 | 0.51 | 776.06 | 01-FEB-09:01 | 0.66 |
March | 0.195113E+09 | 0.48 | 776.06 | 03-MAR-09:01 | 0.66 |
April | 0.159966E+09 | 0.48 | 776.06 | 02-APR-08:62 | 0.65 |
May | 0.196782E+09 | 0.49 | 776.06 | 01-MAY-08:62 | 0.65 |
June | 0.348500E+09 | 0.51 | 776.06 | 01-JUN-08:61 | 0.65 |
July | 0.460258E+09 | 0.52 | 776.06 | 01-JUL-08:51 | 0.65 |
August | 0.381779E+09 | 0.51 | 776.06 | 01-AUG-08:51 | 0.65 |
September | 0.213854E+09 | 0.49 | 776.06 | 01-SEP-08:51 | 0.65 |
October | 0.121492E+09 | 0.45 | 776.06 | 01-OCT-15:02 | 0.65 |
November | 0.193587E+09 | 0.49 | 776.06 | 04-NOV-15:01 | 0.66 |
December | 0.312475E+09 | 0.56 | 776.06 | 01-DEC-09:01 | 0.66 |
Annual Sum or Average | 0.321341E+10 | 0.51 | |||
Minimum of Months | 0.121492E+09 | 0.45 | 776.06 | 0.65 | |
Maximum of Months | 0.460258E+09 | 0.57 | 776.06 | 0.66 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.115976E+09 | 0.57 | 241.63 | 01-JAN-09:01 | 0.65 |
February | 73844565.91 | 0.53 | 241.63 | 01-FEB-09:01 | 0.66 |
March | 68393189.03 | 0.51 | 241.63 | 01-MAR-09:01 | 0.66 |
April | 60693829.82 | 0.53 | 241.63 | 01-APR-08:62 | 0.66 |
May | 77498282.50 | 0.56 | 241.63 | 01-MAY-15:01 | 0.66 |
June | 0.104876E+09 | 0.59 | 241.63 | 01-JUN-08:61 | 0.65 |
July | 0.140261E+09 | 0.62 | 241.63 | 01-JUL-08:61 | 0.65 |
August | 0.125025E+09 | 0.61 | 241.63 | 01-AUG-08:62 | 0.65 |
September | 84881251.30 | 0.57 | 241.63 | 01-SEP-08:62 | 0.65 |
October | 54211141.89 | 0.52 | 241.63 | 02-OCT-15:01 | 0.65 |
November | 60930218.53 | 0.51 | 241.63 | 01-NOV-15:01 | 0.66 |
December | 93857376.02 | 0.54 | 241.63 | 01-DEC-09:01 | 0.66 |
Annual Sum or Average | 0.106045E+10 | 0.56 | |||
Minimum of Months | 54211141.89 | 0.51 | 241.63 | 0.65 | |
Maximum of Months | 0.140261E+09 | 0.62 | 241.63 | 0.66 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.133865E+09 | 0.61 | 229.59 | 01-JAN-09:01 | 0.65 |
February | 79176907.31 | 0.55 | 229.59 | 01-FEB-09:01 | 0.66 |
March | 69258871.04 | 0.51 | 229.59 | 01-MAR-09:01 | 0.66 |
April | 45409388.47 | 0.46 | 229.59 | 01-APR-08:62 | 0.66 |
May | 56156572.21 | 0.47 | 229.59 | 01-MAY-08:62 | 0.65 |
June | 81641124.29 | 0.48 | 229.59 | 01-JUN-08:61 | 0.65 |
July | 0.113526E+09 | 0.50 | 229.59 | 01-JUL-08:51 | 0.65 |
August | 87758497.79 | 0.48 | 229.59 | 01-AUG-08:51 | 0.65 |
September | 54237522.98 | 0.46 | 229.59 | 01-SEP-08:51 | 0.65 |
October | 41167538.28 | 0.45 | 229.59 | 02-OCT-15:01 | 0.65 |
November | 67127545.94 | 0.51 | 229.59 | 01-NOV-15:01 | 0.66 |
December | 0.104189E+09 | 0.59 | 229.59 | 01-DEC-09:01 | 0.66 |
Annual Sum or Average | 0.933515E+09 | 0.51 | |||
Minimum of Months | 41167538.28 | 0.45 | 229.59 | 0.65 | |
Maximum of Months | 0.133865E+09 | 0.61 | 229.59 | 0.66 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.469768E+09 | 0.56 | 1164.56 | 01-JAN-16:02 | 0.65 |
February | 0.354722E+09 | 0.56 | 1164.56 | 01-FEB-09:01 | 0.66 |
March | 0.345793E+09 | 0.54 | 1164.56 | 01-MAR-16:01 | 0.66 |
April | 0.327381E+09 | 0.55 | 1164.56 | 01-APR-15:01 | 0.66 |
May | 0.361478E+09 | 0.56 | 1164.56 | 01-MAY-15:01 | 0.65 |
June | 0.472892E+09 | 0.60 | 1164.56 | 01-JUN-08:61 | 0.65 |
July | 0.651413E+09 | 0.62 | 1164.56 | 01-JUL-08:61 | 0.65 |
August | 0.689763E+09 | 0.61 | 1164.56 | 01-AUG-08:62 | 0.65 |
September | 0.563750E+09 | 0.59 | 1164.56 | 01-SEP-08:62 | 0.66 |
October | 0.431636E+09 | 0.57 | 1164.56 | 01-OCT-15:02 | 0.65 |
November | 0.344998E+09 | 0.55 | 1164.56 | 01-NOV-15:01 | 0.66 |
December | 0.368845E+09 | 0.55 | 1164.56 | 01-DEC-09:01 | 0.66 |
Annual Sum or Average | 0.538244E+10 | 0.57 | |||
Minimum of Months | 0.327381E+09 | 0.54 | 1164.56 | 0.65 | |
Maximum of Months | 0.689763E+09 | 0.62 | 1164.56 | 0.66 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.172735E+10 | 0.157016E+10 | 1638.64 | 11-JAN-06:00 | 1489.52 | 1489.52 | 48.79 | 5.31 |
February | 0.871672E+09 | 0.792349E+09 | 1421.54 | 01-FEB-05:00 | 1292.18 | 1292.18 | 50.62 | 4.22 |
March | 0.687375E+09 | 0.624824E+09 | 1110.05 | 04-MAR-24:00 | 1009.04 | 1009.04 | 45.31 | 1.90 |
April | 0.378582E+09 | 0.344131E+09 | 664.99 | 01-APR-08:62 | 604.48 | 604.48 | 31.73 | 0.86 |
May | 0.321945E+09 | 0.292648E+09 | 680.00 | 06-MAY-08:05 | 618.12 | 618.12 | 50.79 | 0.88 |
June | 0.177699E+09 | 0.161529E+09 | 553.15 | 17-JUN-06:05 | 502.82 | 502.82 | 59.33 | 0.67 |
July | 89000646.86 | 80901588.00 | 476.09 | 09-JUL-04:10 | 432.76 | 432.76 | 34.12 | 0.57 |
August | 0.125299E+09 | 0.113897E+09 | 518.96 | 17-AUG-22:40 | 471.74 | 471.74 | 35.85 | 0.63 |
September | 0.209412E+09 | 0.190355E+09 | 715.59 | 13-SEP-08:62 | 650.47 | 650.47 | 35.08 | 0.94 |
October | 0.403228E+09 | 0.366534E+09 | 705.04 | 30-OCT-08:04 | 640.88 | 640.88 | 57.77 | 0.91 |
November | 0.692262E+09 | 0.629266E+09 | 927.34 | 26-NOV-19:01 | 842.95 | 842.95 | 37.13 | 1.37 |
December | 0.119642E+10 | 0.108754E+10 | 1578.25 | 29-DEC-09:03 | 1434.63 | 1434.63 | 48.52 | 5.09 |
Annual Sum or Average | 0.688024E+10 | 0.625414E+10 | ||||||
Minimum of Months | 89000646.86 | 80901588.00 | 476.09 | 432.76 | 432.76 | 31.73 | 0.57 | |
Maximum of Months | 0.172735E+10 | 0.157016E+10 | 1638.64 | 1489.52 | 1489.52 | 59.33 | 5.31 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 2219494.73 | 2017520.71 | 74.77 | 02-JAN-16:03 | 67.97 | 67.97 | 8.40 | 3.85 |
February | 12620041.02 | 11471617.29 | 350.36 | 27-FEB-16:01 | 318.47 | 318.47 | 7.96 | 8.17 |
March | 17715221.01 | 16103135.89 | 240.74 | 28-MAR-15:02 | 218.84 | 218.84 | 8.40 | 6.87 |
April | 52963332.23 | 48143669.00 | 521.35 | 06-APR-15:01 | 473.91 | 473.91 | 7.56 | 9.78 |
May | 0.144643E+09 | 0.131480E+09 | 1116.19 | 20-MAY-18:03 | 1014.62 | 1014.62 | 7.11 | 13.62 |
June | 0.396725E+09 | 0.360623E+09 | 1458.21 | 23-JUN-18:03 | 1325.51 | 1325.51 | 6.73 | 15.25 |
July | 0.748689E+09 | 0.680559E+09 | 2614.18 | 17-JUL-18:02 | 2376.29 | 2376.29 | 6.73 | 19.39 |
August | 0.622302E+09 | 0.565672E+09 | 2202.08 | 07-AUG-18:03 | 2001.69 | 2001.69 | 6.73 | 18.08 |
September | 0.375631E+09 | 0.341449E+09 | 1753.96 | 02-SEP-18:03 | 1594.35 | 1594.35 | 6.73 | 16.47 |
October | 76503793.38 | 69541948.18 | 550.12 | 12-OCT-15:02 | 500.06 | 500.06 | 7.58 | 10.02 |
November | 20042283.54 | 18218435.73 | 323.81 | 04-NOV-15:01 | 294.34 | 294.34 | 8.24 | 7.88 |
December | 1679324.82 | 1526506.26 | 63.01 | 06-DEC-16:01 | 57.28 | 57.28 | 8.40 | 3.52 |
Annual Sum or Average | 0.247173E+10 | 0.224681E+10 | ||||||
Minimum of Months | 1679324.82 | 1526506.26 | 63.01 | 57.28 | 57.28 | 6.73 | 3.52 | |
Maximum of Months | 0.748689E+09 | 0.680559E+09 | 2614.18 | 2376.29 | 2376.29 | 8.40 | 19.39 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.167494E+10 | 0.152252E+10 | 3618.13 | 01-JAN-09:00 | 3288.88 | 3288.88 | 8.43 | 25.61 |
February | 0.305577E+10 | 0.277769E+10 | 3618.13 | 01-FEB-09:03 | 3288.88 | 3288.88 | 8.43 | 25.61 |
March | 0.421699E+10 | 0.383324E+10 | 3618.13 | 01-MAR-00:05 | 3288.88 | 3288.88 | 8.41 | 25.61 |
April | 0.667220E+10 | 0.606503E+10 | 3618.13 | 01-APR-08:62 | 3288.88 | 3288.88 | 8.62 | 25.61 |
May | 0.821333E+10 | 0.746592E+10 | 3618.13 | 01-MAY-05:40 | 3288.88 | 3288.88 | 8.41 | 25.61 |
June | 0.923655E+10 | 0.839603E+10 | 3618.13 | 01-JUN-00:05 | 3288.88 | 3288.88 | 8.93 | 25.61 |
July | 0.969081E+10 | 0.880895E+10 | 3618.13 | 01-JUL-00:10 | 3288.88 | 3288.88 | 9.17 | 25.61 |
August | 0.967460E+10 | 0.879421E+10 | 3618.13 | 01-AUG-00:05 | 3288.88 | 3288.88 | 9.08 | 25.61 |
September | 0.887539E+10 | 0.806773E+10 | 3618.13 | 01-SEP-00:05 | 3288.88 | 3288.88 | 9.03 | 25.61 |
October | 0.804395E+10 | 0.731195E+10 | 3618.13 | 01-OCT-00:10 | 3288.88 | 3288.88 | 8.62 | 25.61 |
November | 0.505412E+10 | 0.459419E+10 | 3618.13 | 01-NOV-05:03 | 3288.88 | 3288.88 | 8.42 | 25.61 |
December | 0.189385E+10 | 0.172151E+10 | 3618.13 | 01-DEC-09:03 | 3288.88 | 3288.88 | 8.54 | 25.61 |
Annual Sum or Average | 0.763025E+11 | 0.693590E+11 | ||||||
Minimum of Months | 0.167494E+10 | 0.152252E+10 | 3618.13 | 3288.88 | 3288.88 | 8.41 | 25.61 | |
Maximum of Months | 0.969081E+10 | 0.880895E+10 | 3618.13 | 3288.88 | 3288.88 | 9.17 | 25.61 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 47.80 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:05 | 14.37 | 14.37 | 48.03 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 48.33 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 51.58 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 51.74 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 52.23 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 52.89 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 52.95 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 52.98 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 52.14 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 52.34 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:05 | 14.37 | 14.37 | 49.32 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 47.80 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 52.98 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 63.64 | 80.85 | 184043.16 | 741195.59 | 11-JAN-06:00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 48.33 | 82.20 | 64858.55 | 581543.28 | 01-FEB-03:32 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 55.88 | 81.58 | 41319.12 | 292669.56 | 04-MAR-24:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 64.44 | 80.63 | 24805.41 | 171629.95 | 01-APR-08:62 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 64.80 | 81.26 | 22827.12 | 157833.71 | 15-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.22 | 32.22 | 15560.44 | 130726.92 | 16-JUN-15:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.98 | 27.98 | 7806.79 | 110915.28 | 09-JUL-02:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.73 | 29.73 | 10880.62 | 115651.54 | 17-AUG-15:05 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.06 | 31.06 | 16500.38 | 176647.01 | 13-SEP-08:62 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.11 | 79.40 | 27529.58 | 168749.50 | 31-OCT-15:03 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 67.98 | 80.24 | 42843.33 | 258783.43 | 26-NOV-19:01 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 55.53 | 81.42 | 88067.47 | 717230.47 | 29-DEC-09:03 |
Annual Sum or Average | 0.00 | 45654.84 | ||||||
Minimum of Months | 0.00 | 0.00 | 27.11 | 27.98 | 7806.79 | 110915.28 | ||
Maximum of Months | 0.00 | 0.00 | 67.98 | 82.20 | 184043.16 | 741195.59 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1806.45 | 59908.41 | 02-JAN-16:03 | 8.93 | 8.37 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 7355.47 | 209823.20 | 27-FEB-16:01 | 10.00 | 8.04 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 8671.52 | 137053.14 | 28-MAR-15:02 | 9.65 | 8.37 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 23012.60 | 315855.40 | 06-APR-15:03 | 10.46 | 7.51 | 0.00 | 0.00 | 01-APR-00:10 |
May | 47647.69 | 374956.63 | 19-MAY-18:03 | 10.40 | 6.91 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 109059.37 | 466859.70 | 20-JUN-18:03 | 11.05 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 165306.38 | 532189.85 | 17-JUL-18:02 | 11.66 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 142354.22 | 457241.05 | 07-AUG-18:03 | 10.96 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 91420.88 | 479485.10 | 03-SEP-18:02 | 11.17 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 31991.00 | 391333.36 | 18-OCT-15:03 | 10.62 | 6.97 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 11325.41 | 172785.93 | 04-NOV-15:01 | 9.83 | 8.22 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 1652.65 | 49027.95 | 07-DEC-16:03 | 8.83 | 8.37 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 53788.57 | 0.00 | ||||||
Minimum of Months | 1652.65 | 49027.95 | 8.83 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 165306.38 | 532189.85 | 11.66 | 8.37 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 47.80 | 59.98 | 30172.88 | 63136.42 | 31-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 48.03 | 59.53 | 30390.62 | 63397.47 | 17-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 48.33 | 59.96 | 30086.27 | 63304.05 | 02-MAR-07:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 51.58 | 59.96 | 28946.49 | 61567.92 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 51.74 | 59.99 | 27358.38 | 58928.39 | 01-MAY-06:50 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 52.23 | 59.97 | 25711.97 | 55143.72 | 01-JUN-06:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 52.89 | 59.97 | 24415.25 | 51867.54 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 52.95 | 59.97 | 23884.58 | 50058.19 | 01-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 52.98 | 59.97 | 24196.75 | 51307.01 | 29-SEP-06:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 52.14 | 59.96 | 25298.08 | 54363.96 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 52.34 | 59.96 | 26905.10 | 57846.90 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 49.32 | 59.96 | 28599.61 | 60903.94 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 27145.24 | ||||||
Minimum of Months | 0.00 | 0.00 | 47.80 | 59.53 | 23884.58 | 50058.19 | ||
Maximum of Months | 0.00 | 0.00 | 52.98 | 59.99 | 30390.62 | 63397.47 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.384459E+12 | 0.00 | 0.00 | 0.300171E+11 | 0.00 | 0.00 |
February | 0.112005E+12 | 0.00 | 0.118080E+10 | 0.289319E+11 | 0.00 | 0.00 |
March | 0.828290E+11 | 0.00 | 17670844.71 | 0.328511E+11 | 0.00 | 0.00 |
April | 0.563624E+11 | 0.00 | 0.161152E+11 | 0.330927E+11 | 0.00 | 0.00 |
May | 0.567711E+11 | 0.00 | 0.587471E+11 | 0.355174E+11 | 0.00 | 0.00 |
June | 0.402788E+11 | 0.00 | 0.154886E+12 | 0.372041E+11 | 0.00 | 0.00 |
July | 0.210362E+11 | 0.00 | 0.265505E+12 | 0.405781E+11 | 0.00 | 0.00 |
August | 0.292263E+11 | 0.00 | 0.221511E+12 | 0.405539E+11 | 0.00 | 0.00 |
September | 0.413618E+11 | 0.00 | 0.124345E+12 | 0.372652E+11 | 0.00 | 0.00 |
October | 0.676700E+11 | 0.00 | 0.247539E+11 | 0.360810E+11 | 0.00 | 0.00 |
November | 0.832162E+11 | 0.00 | 0.167984E+10 | 0.326639E+11 | 0.00 | 0.00 |
December | 0.168314E+12 | 0.00 | 0.00 | 0.315504E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.114353E+13 | 0.00 | 0.868743E+12 | 0.416307E+12 | 0.00 | 0.00 |
Minimum of Months | 0.210362E+11 | 0.00 | 0.00 | 0.289319E+11 | 0.00 | 0.00 |
Maximum of Months | 0.384459E+12 | 0.00 | 0.265505E+12 | 0.405781E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.206232E+11 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
February | 0.402714E+10 | 0.00 | 66859211.40 | 0.244774E+10 | 0.00 | 0.00 |
March | 0.190831E+10 | 0.00 | 1181470.97 | 0.271000E+10 | 0.00 | 0.00 |
April | 0.176933E+09 | 0.00 | 0.100375E+10 | 0.262258E+10 | 0.00 | 0.00 |
May | 36183260.65 | 0.00 | 0.373266E+10 | 0.271000E+10 | 0.00 | 0.00 |
June | 19332.93 | 0.00 | 0.964258E+10 | 0.262258E+10 | 0.00 | 0.00 |
July | 18294.91 | 0.00 | 0.168625E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 18308.59 | 0.00 | 0.135751E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 15940.79 | 0.00 | 0.799166E+10 | 0.262258E+10 | 0.00 | 0.00 |
October | 53932716.57 | 0.00 | 0.154185E+10 | 0.271000E+10 | 0.00 | 0.00 |
November | 0.137829E+10 | 0.00 | 95107362.99 | 0.262258E+10 | 0.00 | 0.00 |
December | 0.671760E+10 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.349217E+11 | 0.00 | 0.545133E+11 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 15940.79 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.206232E+11 | 0.00 | 0.168625E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.300171E+11 | 0.00 | 0.384459E+12 | 0.545815E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.289319E+11 | 0.118080E+10 | 0.112005E+12 | 0.556118E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.328511E+11 | 17670844.71 | 0.828290E+11 | 0.565104E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.330927E+11 | 0.161152E+11 | 0.563624E+11 | 0.315345E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.355174E+11 | 0.587471E+11 | 0.567711E+11 | 0.210785E+12 | 0.243151E+09 | 0.00 | 0.00 | 0.00 |
June | 0.372041E+11 | 0.154886E+12 | 0.402788E+11 | 0.439846E+11 | 0.469080E+10 | 0.00 | 0.00 | 0.00 |
July | 0.405781E+11 | 0.265505E+12 | 0.210362E+11 | 0.121360E+11 | 0.155374E+11 | 0.00 | 0.00 | 0.00 |
August | 0.405539E+11 | 0.221511E+12 | 0.292263E+11 | 0.896404E+10 | 0.122852E+11 | 0.00 | 0.00 | 0.00 |
September | 0.372652E+11 | 0.124345E+12 | 0.413618E+11 | 0.889923E+11 | 0.575884E+10 | 0.00 | 0.00 | 0.00 |
October | 0.360810E+11 | 0.247539E+11 | 0.676700E+11 | 0.233551E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.326639E+11 | 0.167984E+10 | 0.832162E+11 | 0.435838E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.315504E+11 | 0.00 | 0.168314E+12 | 0.645745E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.416307E+12 | 0.868743E+12 | 0.114353E+13 | 0.366238E+13 | 0.385154E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.289319E+11 | 0.00 | 0.210362E+11 | 0.896404E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.405781E+11 | 0.265505E+12 | 0.384459E+12 | 0.645745E+12 | 0.155374E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.00 | 0.206232E+11 | 0.482149E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 66859211.40 | 0.402714E+10 | 0.504519E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 1181470.97 | 0.190831E+10 | 0.526968E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.100375E+10 | 0.176933E+09 | 0.328816E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.373266E+10 | 36183260.65 | 0.243866E+11 | 33367909.59 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.964258E+10 | 19332.93 | 0.851765E+10 | 0.633275E+09 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.168625E+11 | 18294.91 | 0.343232E+10 | 0.154063E+10 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.135751E+11 | 18308.59 | 0.444315E+10 | 0.852649E+09 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.799166E+10 | 15940.79 | 0.123877E+11 | 0.560629E+09 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.154185E+10 | 53932716.57 | 0.271336E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 95107362.99 | 0.137829E+10 | 0.423606E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.00 | 0.671760E+10 | 0.583416E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.545133E+11 | 0.349217E+11 | 0.365248E+12 | 0.362055E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.00 | 15940.79 | 0.343232E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.168625E+11 | 0.206232E+11 | 0.583416E+11 | 0.154063E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.300171E+11 | 0.384459E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.289319E+11 | 0.112005E+12 | 0.118080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.328511E+11 | 0.828290E+11 | 17670844.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.330927E+11 | 0.563624E+11 | 0.161152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.355174E+11 | 0.567711E+11 | 0.587471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.372041E+11 | 0.402788E+11 | 0.154886E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.405781E+11 | 0.210362E+11 | 0.265505E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.405539E+11 | 0.292263E+11 | 0.221511E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.372652E+11 | 0.413618E+11 | 0.124345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.360810E+11 | 0.676700E+11 | 0.247539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.326639E+11 | 0.832162E+11 | 0.167984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.315504E+11 | 0.168314E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.416307E+12 | 0.114353E+13 | 0.868743E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.289319E+11 | 0.210362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.405781E+11 | 0.384459E+12 | 0.265505E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.206232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.402714E+10 | 66859211.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.190831E+10 | 1181470.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.176933E+09 | 0.100375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 36183260.65 | 0.373266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 19332.93 | 0.964258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 18294.91 | 0.168625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 18308.59 | 0.135751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 15940.79 | 0.799166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 53932716.57 | 0.154185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.137829E+10 | 95107362.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.671760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.349217E+11 | 0.545133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 15940.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.206232E+11 | 0.168625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.647246E+11 | 0.00 | 0.00 | 2248328.59 | 0.00 | 0.00 | 0.436483E+10 | 0.00 | 0.85 |
February | 0.405462E+11 | 0.00 | 0.00 | 65731.33 | 0.00 | 0.00 | 0.656207E+09 | 0.00 | 0.85 |
March | 0.430037E+11 | 0.00 | 0.00 | 2488.34 | 0.00 | 0.00 | 37796774.13 | 0.00 | 0.86 |
April | 0.393262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 |
May | 0.380583E+11 | 0.00 | 0.00 | 0.00 | 38926.44 | 0.00 | 0.00 | 0.00 | 0.85 |
June | 0.298638E+11 | 0.00 | 0.00 | 0.00 | 0.122612E+09 | 0.00 | 0.00 | 0.00 | 0.86 |
July | 0.207808E+11 | 784376.22 | 0.00 | 1299504.95 | 0.314880E+09 | 0.00 | 0.170439E+10 | 0.00 | 0.85 |
August | 0.119649E+11 | 913281.63 | 0.00 | 12688521.98 | 0.236913E+09 | 0.00 | 0.145501E+11 | 0.00 | 0.86 |
September | 0.411851E+10 | 48097929.02 | 0.00 | 38134374.15 | 0.139702E+09 | 0.00 | 0.306169E+11 | 0.00 | 0.92 |
October | 0.179037E+10 | 0.00 | 0.00 | 51681287.64 | 0.00 | 0.00 | 0.458907E+11 | 0.00 | 0.97 |
November | 0.216654E+10 | 0.00 | 0.00 | 47647982.97 | 0.00 | 0.00 | 0.448303E+11 | 0.00 | 0.95 |
December | 0.209553E+11 | 0.00 | 0.00 | 26415007.84 | 0.00 | 0.00 | 0.301766E+11 | 0.00 | 0.90 |
Annual Sum or Average | 0.317299E+12 | 49795586.87 | 0.00 | 0.180183E+09 | 0.814146E+09 | 0.00 | 0.172828E+12 | 0.00 | 0.88 |
Minimum of Months | 0.179037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 |
Maximum of Months | 0.647246E+11 | 48097929.02 | 0.00 | 51681287.64 | 0.314880E+09 | 0.00 | 0.458907E+11 | 0.00 | 0.97 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.398553E+10 | 0.00 | 0.00 | 331790.75 | 0.00 | 0.915419E+10 | 0.430102E+09 | 0.00 | 3.01 |
February | 0.470351E+10 | 0.00 | 0.00 | 1220417.44 | 0.00 | 0.255266E+10 | 0.929029E+09 | 0.00 | 3.07 |
March | 0.616322E+10 | 0.00 | 0.00 | 1312103.84 | 0.00 | 0.128609E+10 | 0.111724E+10 | 0.00 | 3.08 |
April | 0.673424E+10 | 0.00 | 0.00 | 1207136.96 | 0.00 | 0.194494E+09 | 0.779831E+09 | 0.00 | 3.04 |
May | 0.674453E+10 | 7569.22 | 0.00 | 916903.75 | 0.00 | 0.174931E+09 | 0.491959E+09 | 0.00 | 3.03 |
June | 0.523874E+10 | 26392730.00 | 0.00 | 1462043.43 | 744979.18 | 0.00 | 0.570948E+09 | 0.00 | 3.06 |
July | 0.352768E+10 | 84419812.42 | 0.00 | 2907963.64 | 518750.50 | 0.00 | 0.856856E+09 | 0.00 | 3.15 |
August | 0.400330E+10 | 71272370.44 | 0.00 | 4164762.30 | 42402.92 | 0.00 | 0.115151E+10 | 0.00 | 3.25 |
September | 0.510313E+10 | 50852431.62 | 0.00 | 3841330.98 | 1313352.53 | 0.00 | 0.134682E+10 | 0.00 | 3.27 |
October | 0.681936E+10 | 0.00 | 0.00 | 2836839.91 | 0.00 | 59421431.73 | 0.152603E+10 | 0.00 | 3.17 |
November | 0.615958E+10 | 0.00 | 0.00 | 1249694.45 | 0.00 | 0.122360E+10 | 0.102664E+10 | 0.00 | 3.06 |
December | 0.490799E+10 | 0.00 | 0.00 | 313715.37 | 0.00 | 0.418757E+10 | 0.472576E+09 | 0.00 | 3.01 |
Annual Sum or Average | 0.640908E+11 | 0.232945E+09 | 0.00 | 21764702.83 | 2619485.13 | 0.188330E+11 | 0.106995E+11 | 0.00 | 3.10 |
Minimum of Months | 0.352768E+10 | 0.00 | 0.00 | 313715.37 | 0.00 | 0.00 | 0.430102E+09 | 0.00 | 3.01 |
Maximum of Months | 0.681936E+10 | 84419812.42 | 0.00 | 4164762.30 | 1313352.53 | 0.915419E+10 | 0.152603E+10 | 0.00 | 3.27 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.695795E+10 | 0.00 | 0.00 | 4512.67 | 0.00 | 0.345837E+09 | 19206903.51 | 0.00 | 1.41 |
February | 0.415431E+10 | 0.00 | 0.00 | 136216.90 | 0.00 | 0.00 | 0.213566E+09 | 0.00 | 1.41 |
March | 0.414995E+10 | 0.00 | 0.00 | 220981.45 | 0.00 | 0.00 | 0.410548E+09 | 0.00 | 1.42 |
April | 0.332694E+10 | 0.00 | 0.00 | 601776.83 | 0.00 | 0.00 | 0.857752E+09 | 0.00 | 1.42 |
May | 0.260599E+10 | 4123.94 | 0.00 | 1367540.17 | 0.00 | 0.00 | 0.147036E+10 | 0.00 | 1.44 |
June | 0.105954E+10 | 10595086.64 | 0.00 | 3196645.35 | 3153021.49 | 0.00 | 0.225076E+10 | 0.00 | 1.51 |
July | 0.360098E+09 | 32995228.24 | 0.00 | 4850661.81 | 1327895.08 | 0.00 | 0.225513E+10 | 0.00 | 1.57 |
August | 0.575347E+09 | 24788699.54 | 0.00 | 4738217.35 | 820448.11 | 0.00 | 0.246667E+10 | 0.00 | 1.57 |
September | 0.135522E+10 | 19710317.58 | 0.00 | 3162900.54 | 397907.88 | 0.00 | 0.223341E+10 | 0.00 | 1.51 |
October | 0.288655E+10 | 0.00 | 0.00 | 1110606.96 | 0.00 | 0.00 | 0.161394E+10 | 0.00 | 1.44 |
November | 0.396508E+10 | 0.00 | 0.00 | 249415.34 | 0.00 | 0.00 | 0.507008E+09 | 0.00 | 1.41 |
December | 0.515156E+10 | 0.00 | 0.00 | 10131.08 | 0.00 | 7485350.41 | 43896729.11 | 0.00 | 1.42 |
Annual Sum or Average | 0.365485E+11 | 88093455.95 | 0.00 | 19649606.45 | 5699272.56 | 0.353323E+09 | 0.143423E+11 | 0.00 | 1.46 |
Minimum of Months | 0.360098E+09 | 0.00 | 0.00 | 4512.67 | 0.00 | 0.00 | 19206903.51 | 0.00 | 1.41 |
Maximum of Months | 0.695795E+10 | 32995228.24 | 0.00 | 4850661.81 | 3153021.49 | 0.345837E+09 | 0.246667E+10 | 0.00 | 1.57 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.206947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375031E+10 | 0.00 | 0.00 | 0.53 |
February | 0.243294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103762E+10 | 0.00 | 0.00 | 0.53 |
March | 0.331245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313023E+09 | 0.00 | 0.00 | 0.53 |
April | 0.331252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
May | 0.317717E+10 | 0.00 | 0.00 | 15459.63 | 3278.85 | 0.00 | 28531884.74 | 0.00 | 0.53 |
June | 0.215511E+10 | 1515394.71 | 0.00 | 677987.73 | 8814928.74 | 0.00 | 0.383507E+09 | 0.00 | 0.54 |
July | 0.105911E+10 | 19813131.81 | 0.00 | 2295449.84 | 7254161.73 | 0.00 | 0.911115E+09 | 0.00 | 0.56 |
August | 0.152770E+10 | 14564587.43 | 0.00 | 1955231.74 | 5516887.74 | 0.00 | 0.747030E+09 | 0.00 | 0.55 |
September | 0.234254E+10 | 6011518.15 | 0.00 | 800621.80 | 9795256.01 | 0.00 | 0.406579E+09 | 0.00 | 0.55 |
October | 0.353424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
November | 0.339620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158182E+09 | 0.00 | 0.00 | 0.53 |
December | 0.299218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114456E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.313116E+11 | 41904632.10 | 0.00 | 5744750.74 | 31384513.07 | 0.640369E+10 | 0.247676E+10 | 0.00 | 0.54 |
Minimum of Months | 0.105911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.353424E+10 | 19813131.81 | 0.00 | 2295449.84 | 9795256.01 | 0.375031E+10 | 0.911115E+09 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.839133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234430E+10 | 0.00 | 0.00 | 0.50 |
February | 0.114312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751402E+09 | 0.00 | 0.00 | 0.50 |
March | 0.168201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297067E+09 | 0.00 | 0.00 | 0.50 |
April | 0.180825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
May | 0.174995E+10 | 0.00 | 0.00 | 0.00 | 1789.87 | 0.00 | 0.00 | 0.00 | 0.50 |
June | 0.131649E+10 | 10490.94 | 0.00 | 111025.25 | 5627298.54 | 0.00 | 57071626.85 | 0.00 | 0.51 |
July | 0.812881E+09 | 9959464.56 | 0.00 | 533206.40 | 4776960.19 | 0.00 | 0.228610E+09 | 0.00 | 0.51 |
August | 0.105342E+10 | 7681248.65 | 0.00 | 381241.21 | 3274642.01 | 0.00 | 0.163076E+09 | 0.00 | 0.51 |
September | 0.141038E+10 | 2884523.41 | 0.00 | 141281.43 | 5731157.12 | 0.00 | 75797781.49 | 0.00 | 0.51 |
October | 0.192928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
November | 0.170367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236611E+09 | 0.00 | 0.00 | 0.50 |
December | 0.116401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109416E+10 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.166126E+11 | 20535727.56 | 0.00 | 1166754.29 | 19411847.73 | 0.472354E+10 | 0.524555E+09 | 0.00 | 0.50 |
Minimum of Months | 0.812881E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.192928E+10 | 9959464.56 | 0.00 | 533206.40 | 5731157.12 | 0.234430E+10 | 0.228610E+09 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.793751E+10 | 0.00 | 0.00 | 90408494.76 | 0.00 | 0.100769E+10 | 0.112545E+12 | 0.00 | 24.42 |
February | 0.476791E+09 | 0.00 | 0.00 | 89337860.26 | 0.00 | 0.00 | 0.782847E+11 | 0.00 | 25.41 |
March | 0.142010E+09 | 0.00 | 0.00 | 99069035.32 | 0.00 | 0.00 | 0.824499E+11 | 0.00 | 25.75 |
April | 51732732.35 | 0.00 | 0.00 | 0.102844E+09 | 0.00 | 0.00 | 0.758792E+11 | 0.00 | 25.64 |
May | 43783602.50 | 61753.74 | 0.00 | 0.115516E+09 | 0.00 | 0.00 | 0.735153E+11 | 0.00 | 25.73 |
June | 2946066.68 | 0.231734E+09 | 0.00 | 0.128813E+09 | 0.00 | 0.00 | 0.574076E+11 | 0.00 | 25.82 |
July | 0.00 | 0.522289E+09 | 0.00 | 0.132453E+09 | 0.00 | 0.00 | 0.422947E+11 | 0.00 | 25.37 |
August | 0.00 | 0.383300E+09 | 0.00 | 0.127575E+09 | 0.00 | 0.00 | 0.506105E+11 | 0.00 | 25.63 |
September | 14773575.53 | 0.314374E+09 | 0.00 | 0.111524E+09 | 0.00 | 0.00 | 0.629429E+11 | 0.00 | 25.85 |
October | 52842983.70 | 0.00 | 0.00 | 0.104236E+09 | 0.00 | 0.00 | 0.813661E+11 | 0.00 | 25.74 |
November | 0.115735E+09 | 0.00 | 0.00 | 96161499.43 | 0.00 | 0.00 | 0.810274E+11 | 0.00 | 25.53 |
December | 0.796741E+09 | 0.00 | 0.00 | 97939785.72 | 0.00 | 0.00 | 0.916641E+11 | 0.00 | 25.38 |
Annual Sum or Average | 0.963487E+10 | 0.145176E+10 | 0.00 | 0.129588E+10 | 0.00 | 0.100769E+10 | 0.889988E+12 | 0.00 | 25.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 89337860.26 | 0.00 | 0.00 | 0.422947E+11 | 0.00 | 24.42 |
Maximum of Months | 0.793751E+10 | 0.522289E+09 | 0.00 | 0.132453E+09 | 0.00 | 0.100769E+10 | 0.112545E+12 | 0.00 | 25.85 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.414988E+11 | 0.00 | 0.00 | 3686572.68 | 0.00 | 0.595391E+10 | 0.823368E+10 | 0.00 | 4.42 |
February | 0.204268E+11 | 0.00 | 0.00 | 10102692.19 | 0.00 | 64627187.41 | 0.132845E+11 | 0.00 | 4.51 |
March | 0.168891E+11 | 0.00 | 0.00 | 12347241.05 | 0.00 | 0.00 | 0.184710E+11 | 0.00 | 4.54 |
April | 0.125992E+11 | 0.00 | 0.00 | 15646965.62 | 0.00 | 0.00 | 0.192902E+11 | 0.00 | 4.49 |
May | 0.111066E+11 | 31202.05 | 0.00 | 18182578.82 | 0.00 | 0.00 | 0.195134E+11 | 0.00 | 4.47 |
June | 0.474924E+10 | 0.106867E+09 | 0.00 | 27062293.77 | 361223.61 | 0.00 | 0.194880E+11 | 0.00 | 4.55 |
July | 0.212771E+10 | 0.306833E+09 | 0.00 | 35161809.39 | 2334223.80 | 0.00 | 0.165418E+11 | 0.00 | 4.69 |
August | 0.291651E+10 | 0.252710E+09 | 0.00 | 39138824.02 | 206525.83 | 0.00 | 0.190710E+11 | 0.00 | 4.83 |
September | 0.522173E+10 | 0.192486E+09 | 0.00 | 35103537.25 | 460069.62 | 0.00 | 0.217715E+11 | 0.00 | 4.82 |
October | 0.961339E+10 | 0.00 | 0.00 | 26067463.74 | 0.00 | 0.00 | 0.252049E+11 | 0.00 | 4.67 |
November | 0.163043E+11 | 0.00 | 0.00 | 12590517.89 | 0.00 | 0.00 | 0.183789E+11 | 0.00 | 4.51 |
December | 0.281673E+11 | 0.00 | 0.00 | 4077619.23 | 0.00 | 0.171995E+10 | 0.958533E+10 | 0.00 | 4.43 |
Annual Sum or Average | 0.171621E+12 | 0.858927E+09 | 0.00 | 0.239168E+09 | 3362042.86 | 0.773849E+10 | 0.208834E+12 | 0.00 | 4.58 |
Minimum of Months | 0.212771E+10 | 0.00 | 0.00 | 3686572.68 | 0.00 | 0.00 | 0.823368E+10 | 0.00 | 4.42 |
Maximum of Months | 0.414988E+11 | 0.306833E+09 | 0.00 | 39138824.02 | 2334223.80 | 0.595391E+10 | 0.252049E+11 | 0.00 | 4.83 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.143591E+12 | 0.00 | 0.00 | 6792942.69 | 0.00 | 0.120503E+10 | 0.177208E+11 | 0.00 | 1.86 |
February | 0.643427E+11 | 0.00 | 0.00 | 21159593.28 | 0.00 | 0.00 | 0.330796E+11 | 0.00 | 1.88 |
March | 0.556094E+11 | 0.00 | 0.00 | 31025137.34 | 0.00 | 0.00 | 0.463506E+11 | 0.00 | 1.89 |
April | 0.392141E+11 | 0.00 | 0.00 | 45356537.29 | 0.00 | 0.00 | 0.551167E+11 | 0.00 | 1.91 |
May | 0.345479E+11 | 91553.76 | 0.00 | 64828347.85 | 0.00 | 0.00 | 0.581786E+11 | 0.00 | 1.95 |
June | 0.127305E+11 | 0.289833E+09 | 0.00 | 0.100413E+09 | 13188973.42 | 0.00 | 0.648854E+11 | 0.00 | 2.06 |
July | 0.430224E+10 | 0.751710E+09 | 0.00 | 0.129317E+09 | 19742287.24 | 0.00 | 0.574519E+11 | 0.00 | 2.13 |
August | 0.598554E+10 | 0.586162E+09 | 0.00 | 0.133432E+09 | 8066696.87 | 0.00 | 0.660319E+11 | 0.00 | 2.15 |
September | 0.124337E+11 | 0.464435E+09 | 0.00 | 0.113273E+09 | 1262298.23 | 0.00 | 0.715749E+11 | 0.00 | 2.09 |
October | 0.258597E+11 | 0.00 | 0.00 | 78387491.94 | 0.00 | 0.00 | 0.776785E+11 | 0.00 | 1.97 |
November | 0.473653E+11 | 0.00 | 0.00 | 37092701.66 | 0.00 | 0.00 | 0.530398E+11 | 0.00 | 1.89 |
December | 0.899257E+11 | 0.00 | 0.00 | 10647880.65 | 0.00 | 0.00 | 0.256180E+11 | 0.00 | 1.88 |
Annual Sum or Average | 0.535908E+12 | 0.209223E+10 | 0.00 | 0.771726E+09 | 42260255.77 | 0.120503E+10 | 0.626727E+12 | 0.00 | 1.97 |
Minimum of Months | 0.430224E+10 | 0.00 | 0.00 | 6792942.69 | 0.00 | 0.00 | 0.177208E+11 | 0.00 | 1.86 |
Maximum of Months | 0.143591E+12 | 0.751710E+09 | 0.00 | 0.133432E+09 | 19742287.24 | 0.120503E+10 | 0.776785E+11 | 0.00 | 2.15 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 50035961.84 | 0.00 | 0.00 | 354717.93 | 0.00 | 0.273878E+10 | 35397895.82 | 0.00 | 0.35 |
February | 56863074.48 | 0.00 | 0.00 | 1832544.15 | 0.00 | 0.124586E+10 | 0.215214E+09 | 0.00 | 0.35 |
March | 70264775.98 | 0.00 | 0.00 | 2699006.02 | 0.00 | 0.117183E+10 | 0.311810E+09 | 0.00 | 0.36 |
April | 56824161.74 | 0.00 | 0.00 | 6907978.46 | 0.00 | 0.642163E+09 | 0.681402E+09 | 0.00 | 0.35 |
May | 39204916.81 | 838750.07 | 0.00 | 11934186.20 | 0.00 | 0.339296E+09 | 0.934196E+09 | 0.00 | 0.36 |
June | 4747160.23 | 11113074.32 | 0.00 | 17534327.72 | 0.00 | 32290958.14 | 0.948304E+09 | 0.00 | 0.36 |
July | 777558.30 | 26972750.75 | 0.00 | 19256496.87 | 0.00 | 1324920.64 | 0.711160E+09 | 0.00 | 0.35 |
August | 2537204.89 | 4099771.81 | 0.00 | 19012253.61 | 0.00 | 20967821.93 | 0.905641E+09 | 0.00 | 0.35 |
September | 15613963.41 | 10014848.14 | 21428.66 | 12215850.24 | 0.00 | 0.162643E+09 | 0.872107E+09 | 150.83 | 0.36 |
October | 43227376.16 | 0.00 | 0.00 | 6433687.63 | 0.00 | 0.514107E+09 | 0.845315E+09 | 0.00 | 0.35 |
November | 59664964.65 | 0.00 | 0.00 | 1768981.47 | 0.00 | 0.107886E+10 | 0.335346E+09 | 0.00 | 0.35 |
December | 59763543.30 | 0.00 | 0.00 | 443493.75 | 0.00 | 0.175076E+10 | 29248034.62 | 0.00 | 0.36 |
Annual Sum or Average | 0.459525E+09 | 53039195.09 | 21428.66 | 0.100394E+09 | 0.00 | 0.969888E+10 | 0.682514E+10 | 150.83 | 0.35 |
Minimum of Months | 777558.30 | 0.00 | 0.00 | 354717.93 | 0.00 | 1324920.64 | 29248034.62 | 0.00 | 0.35 |
Maximum of Months | 70264775.98 | 26972750.75 | 21428.66 | 19256496.87 | 0.00 | 0.273878E+10 | 0.948304E+09 | 150.83 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 25919219.60 | 0.00 | 0.00 | 143261.04 | 0.00 | 0.279074E+10 | 7434932.31 | 0.00 | 0.35 |
February | 60274192.83 | 0.00 | 0.00 | 788992.03 | 0.00 | 0.137758E+10 | 80946311.21 | 0.00 | 0.35 |
March | 74328780.36 | 0.00 | 0.00 | 1443221.63 | 0.00 | 0.130192E+10 | 0.178733E+09 | 0.00 | 0.36 |
April | 0.136761E+09 | 0.00 | 0.00 | 3973838.42 | 0.00 | 0.747377E+09 | 0.499023E+09 | 0.00 | 0.35 |
May | 0.168569E+09 | 0.00 | 0.00 | 8381795.80 | 838651.80 | 0.375984E+09 | 0.771541E+09 | 0.00 | 0.36 |
June | 0.186015E+09 | 10730101.46 | 88.79 | 13944695.97 | 381381.44 | 30717921.44 | 0.772081E+09 | 200.58 | 0.36 |
July | 0.139076E+09 | 25511968.45 | 9767.99 | 14999232.88 | 1442192.33 | 888237.67 | 0.577470E+09 | 5661.72 | 0.36 |
August | 0.167511E+09 | 4075524.41 | 3717.86 | 13537335.23 | 14763.48 | 20789589.41 | 0.746210E+09 | 5285.71 | 0.36 |
September | 0.151671E+09 | 9190883.08 | 21125.45 | 7587118.03 | 822731.59 | 0.228068E+09 | 0.675129E+09 | 511.59 | 0.36 |
October | 0.123747E+09 | 0.00 | 0.00 | 2993488.30 | 0.00 | 0.708997E+09 | 0.573180E+09 | 0.00 | 0.35 |
November | 76676675.53 | 0.00 | 0.00 | 660724.41 | 0.00 | 0.128259E+10 | 0.115536E+09 | 0.00 | 0.35 |
December | 36825587.19 | 0.00 | 0.00 | 215688.86 | 0.00 | 0.179532E+10 | 7639626.35 | 0.00 | 0.36 |
Annual Sum or Average | 0.134737E+10 | 49508477.41 | 34700.08 | 68669392.59 | 3499720.64 | 0.106610E+11 | 0.500492E+10 | 11659.60 | 0.36 |
Minimum of Months | 25919219.60 | 0.00 | 0.00 | 143261.04 | 0.00 | 888237.67 | 7434932.31 | 0.00 | 0.35 |
Maximum of Months | 0.186015E+09 | 25511968.45 | 21125.45 | 14999232.88 | 1442192.33 | 0.279074E+10 | 0.772081E+09 | 5661.72 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105173E+10 | 0.00 | 0.00 | 435834.41 | 0.00 | 0.307063E+09 | 0.166323E+09 | 0.00 | 0.02 |
February | 0.755514E+09 | 0.00 | 0.00 | 1618493.25 | 0.00 | 0.00 | 0.445359E+09 | 0.00 | 0.02 |
March | 0.691621E+09 | 0.00 | 0.00 | 2804375.98 | 0.00 | 0.00 | 0.841467E+09 | 0.00 | 0.02 |
April | 0.478526E+09 | 0.00 | 0.00 | 2977724.33 | 0.00 | 0.00 | 0.103234E+10 | 0.00 | 0.02 |
May | 0.403458E+09 | 0.00 | 0.00 | 2788845.35 | 0.00 | 0.00 | 0.963211E+09 | 0.00 | 0.02 |
June | 43257939.62 | 22257850.40 | 0.00 | 3837591.36 | 0.00 | 0.00 | 0.809959E+09 | 0.00 | 0.02 |
July | 0.00 | 37420192.96 | 0.00 | 4177974.43 | 0.00 | 0.00 | 0.432423E+09 | 0.00 | 0.02 |
August | 42179949.57 | 3883950.47 | 0.00 | 6242834.33 | 0.00 | 0.00 | 0.594002E+09 | 0.00 | 0.02 |
September | 0.131199E+09 | 64324107.35 | 0.00 | 5460785.35 | 0.00 | 0.00 | 0.755788E+09 | 0.00 | 0.02 |
October | 0.282315E+09 | 0.00 | 0.00 | 4906915.00 | 0.00 | 0.00 | 0.124471E+10 | 0.00 | 0.02 |
November | 0.346639E+09 | 0.00 | 0.00 | 3001528.52 | 0.00 | 0.00 | 0.114775E+10 | 0.00 | 0.02 |
December | 0.972133E+09 | 0.00 | 0.00 | 364499.34 | 0.00 | 42695495.80 | 0.349516E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.519857E+10 | 0.127886E+09 | 0.00 | 38617401.63 | 0.00 | 0.349758E+09 | 0.878284E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 364499.34 | 0.00 | 0.00 | 0.166323E+09 | 0.00 | 0.02 |
Maximum of Months | 0.105173E+10 | 64324107.35 | 0.00 | 6242834.33 | 0.00 | 0.307063E+09 | 0.124471E+10 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.714043E+09 | 0.00 | 0.00 | 2884604.48 | 0.00 | 0.346572E+11 | 0.293498E+10 | 0.00 | 0.40 |
February | 0.112231E+10 | 0.00 | 0.00 | 8376660.25 | 0.00 | 0.133268E+11 | 0.615480E+10 | 0.00 | 0.40 |
March | 0.115946E+10 | 0.00 | 0.00 | 18303409.55 | 0.00 | 0.775630E+10 | 0.121779E+11 | 0.00 | 0.40 |
April | 0.186612E+10 | 0.00 | 0.00 | 51931495.82 | 0.00 | 0.118837E+10 | 0.157092E+11 | 0.00 | 0.40 |
May | 0.247141E+10 | 0.00 | 0.00 | 99122670.88 | 11375808.56 | 0.669076E+09 | 0.147261E+11 | 0.00 | 0.40 |
June | 0.279186E+10 | 0.137285E+09 | 383055.62 | 0.152637E+09 | 13050103.54 | 18593100.57 | 0.106387E+11 | 6230.84 | 0.40 |
July | 0.204310E+10 | 0.346191E+09 | 64234.72 | 0.144875E+09 | 19562473.84 | 3581436.67 | 0.774346E+10 | 8230.17 | 0.40 |
August | 0.258166E+10 | 55286006.79 | 22502.47 | 0.140733E+09 | 288236.55 | 6976996.66 | 0.101303E+11 | 7683.73 | 0.40 |
September | 0.212954E+10 | 0.105442E+09 | 797897.35 | 87749347.51 | 29861882.62 | 66286750.39 | 0.121280E+11 | 20195.67 | 0.40 |
October | 0.167856E+10 | 0.00 | 0.00 | 47736570.06 | 0.00 | 0.910642E+09 | 0.164742E+11 | 0.00 | 0.40 |
November | 0.120023E+10 | 0.00 | 0.00 | 15981792.92 | 0.00 | 0.888899E+10 | 0.990861E+10 | 0.00 | 0.40 |
December | 0.945265E+09 | 0.00 | 0.00 | 4010823.08 | 0.00 | 0.203525E+11 | 0.365673E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.207035E+11 | 0.644205E+09 | 1267690.15 | 0.774342E+09 | 74138505.11 | 0.878453E+11 | 0.122383E+12 | 42340.42 | 0.40 |
Minimum of Months | 0.714043E+09 | 0.00 | 0.00 | 2884604.48 | 0.00 | 3581436.67 | 0.293498E+10 | 0.00 | 0.40 |
Maximum of Months | 0.279186E+10 | 0.346191E+09 | 797897.35 | 0.152637E+09 | 29861882.62 | 0.346572E+11 | 0.164742E+11 | 20195.67 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 54584354.98 | 0.00 | 0.00 | 322153.81 | 0.00 | 0.271173E+10 | 57930969.23 | 0.00 | 0.35 |
February | 51021016.17 | 0.00 | 0.00 | 1767354.28 | 0.00 | 0.123328E+10 | 0.233701E+09 | 0.00 | 0.35 |
March | 45195020.50 | 0.00 | 0.00 | 2600661.93 | 0.00 | 0.113481E+10 | 0.374003E+09 | 0.00 | 0.36 |
April | 37624269.00 | 0.00 | 0.00 | 6667898.56 | 0.00 | 0.635533E+09 | 0.707472E+09 | 0.00 | 0.35 |
May | 18103371.02 | 838750.07 | 0.00 | 10835708.68 | 0.00 | 0.359669E+09 | 0.936023E+09 | 0.00 | 0.36 |
June | 3991581.69 | 11113074.32 | 0.00 | 18924312.81 | 0.00 | 34309332.30 | 0.945651E+09 | 0.00 | 0.36 |
July | 527470.64 | 26972750.75 | 0.00 | 21439118.55 | 0.00 | 543668.04 | 0.710009E+09 | 0.00 | 0.35 |
August | 2537204.89 | 4099771.81 | 0.00 | 20176523.19 | 0.00 | 17802669.72 | 0.907642E+09 | 0.00 | 0.35 |
September | 12651835.03 | 10014848.14 | 20176.24 | 12098424.43 | 0.00 | 0.164317E+09 | 0.873512E+09 | 1403.25 | 0.36 |
October | 38122421.99 | 0.00 | 0.00 | 6093989.48 | 0.00 | 0.532609E+09 | 0.832258E+09 | 0.00 | 0.35 |
November | 59467927.18 | 0.00 | 0.00 | 1678517.22 | 0.00 | 0.107515E+10 | 0.339338E+09 | 0.00 | 0.35 |
December | 60141732.63 | 0.00 | 0.00 | 358038.07 | 0.00 | 0.172155E+10 | 58172348.95 | 0.00 | 0.36 |
Annual Sum or Average | 0.383968E+09 | 53039195.09 | 20176.24 | 0.102963E+09 | 0.00 | 0.962130E+10 | 0.697571E+10 | 1403.25 | 0.35 |
Minimum of Months | 527470.64 | 0.00 | 0.00 | 322153.81 | 0.00 | 543668.04 | 57930969.23 | 0.00 | 0.35 |
Maximum of Months | 60141732.63 | 26972750.75 | 20176.24 | 21439118.55 | 0.00 | 0.271173E+10 | 0.945651E+09 | 1403.25 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 28191587.89 | 0.00 | 0.00 | 149394.64 | 0.00 | 0.277629E+10 | 19609142.53 | 0.00 | 0.35 |
February | 60990473.57 | 0.00 | 0.00 | 596472.82 | 0.00 | 0.135354E+10 | 0.104464E+09 | 0.00 | 0.35 |
March | 75282119.26 | 0.00 | 0.00 | 1047220.09 | 0.00 | 0.126007E+10 | 0.220019E+09 | 0.00 | 0.36 |
April | 0.117982E+09 | 0.00 | 0.00 | 4094257.11 | 0.00 | 0.711889E+09 | 0.553170E+09 | 0.00 | 0.35 |
May | 0.150524E+09 | 838651.80 | 0.00 | 8218548.73 | 0.00 | 0.388464E+09 | 0.777269E+09 | 0.00 | 0.36 |
June | 0.164738E+09 | 10739802.82 | 0.00 | 15575164.47 | 371969.44 | 35073944.49 | 0.787372E+09 | 0.00 | 0.36 |
July | 0.128737E+09 | 25567743.85 | 0.00 | 16702189.01 | 1401846.65 | 634486.18 | 0.586360E+09 | 0.00 | 0.36 |
August | 0.162815E+09 | 4099291.46 | 0.00 | 14906790.20 | 0.00 | 17793106.83 | 0.752532E+09 | 0.00 | 0.36 |
September | 0.137771E+09 | 9135293.90 | 74449.01 | 7731970.69 | 822731.59 | 0.216649E+09 | 0.700303E+09 | 2777.21 | 0.36 |
October | 0.122530E+09 | 0.00 | 0.00 | 2676996.75 | 0.00 | 0.685625E+09 | 0.598086E+09 | 0.00 | 0.35 |
November | 73344449.34 | 0.00 | 0.00 | 378386.94 | 0.00 | 0.126705E+10 | 0.134694E+09 | 0.00 | 0.35 |
December | 35664424.32 | 0.00 | 0.00 | 180830.04 | 0.00 | 0.178750E+10 | 16660579.34 | 0.00 | 0.36 |
Annual Sum or Average | 0.125857E+10 | 50380783.83 | 74449.01 | 72258221.48 | 2596547.69 | 0.105006E+11 | 0.525054E+10 | 2777.21 | 0.35 |
Minimum of Months | 28191587.89 | 0.00 | 0.00 | 149394.64 | 0.00 | 634486.18 | 16660579.34 | 0.00 | 0.35 |
Maximum of Months | 0.164738E+09 | 25567743.85 | 74449.01 | 16702189.01 | 1401846.65 | 0.277629E+10 | 0.787372E+09 | 2777.21 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.134450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296815E+11 | 0.00 | 0.00 | 0.54 |
February | 0.184415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725006E+10 | 0.00 | 0.00 | 0.54 |
March | 0.242722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256606E+10 | 0.00 | 0.00 | 0.54 |
April | 0.245216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
May | 0.236708E+11 | 0.00 | 0.00 | 0.00 | 24272.31 | 60183645.77 | 0.00 | 0.00 | 0.54 |
June | 0.174784E+11 | 14385084.21 | 0.00 | 2196807.66 | 62068783.08 | 0.00 | 0.115123E+10 | 0.00 | 0.54 |
July | 0.969887E+10 | 0.188096E+09 | 0.00 | 10109646.40 | 28196194.76 | 0.00 | 0.444289E+10 | 0.00 | 0.55 |
August | 0.134930E+11 | 0.156902E+09 | 0.00 | 6586143.30 | 10478970.05 | 0.00 | 0.301133E+10 | 0.00 | 0.55 |
September | 0.184867E+11 | 94331825.87 | 0.00 | 3300839.92 | 30071800.65 | 0.00 | 0.167488E+10 | 0.00 | 0.55 |
October | 0.261629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
November | 0.238544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245759E+10 | 0.00 | 0.00 | 0.54 |
December | 0.188400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117858E+11 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.232365E+12 | 0.453715E+09 | 0.00 | 22193437.28 | 0.130840E+09 | 0.538011E+11 | 0.102803E+11 | 0.00 | 0.54 |
Minimum of Months | 0.969887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.261629E+11 | 0.188096E+09 | 0.00 | 10109646.40 | 62068783.08 | 0.296815E+11 | 0.444289E+10 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 8582597.95 | 0.00 | 0.00 | 66119.40 | 0.00 | 0.693340E+09 | 4153366.37 | 0.00 | 0.35 |
February | 11960050.45 | 0.00 | 0.00 | 409904.74 | 0.00 | 0.330680E+09 | 36891397.37 | 0.00 | 0.35 |
March | 16956175.81 | 0.00 | 0.00 | 621173.27 | 0.00 | 0.316471E+09 | 55102634.64 | 0.00 | 0.36 |
April | 14562462.17 | 0.00 | 0.00 | 1697875.34 | 0.00 | 0.197955E+09 | 0.132608E+09 | 0.00 | 0.35 |
May | 9451794.06 | 209687.52 | 0.00 | 2959095.33 | 0.00 | 0.121022E+09 | 0.197725E+09 | 0.00 | 0.36 |
June | 2587464.04 | 2778268.58 | 0.00 | 4240692.69 | 0.00 | 25099800.73 | 0.218791E+09 | 0.00 | 0.36 |
July | 325486.12 | 6743187.69 | 0.00 | 4633115.46 | 0.00 | 367904.76 | 0.177803E+09 | 0.00 | 0.35 |
August | 634301.22 | 1024942.95 | 0.00 | 4523488.43 | 0.00 | 11807545.79 | 0.220074E+09 | 0.00 | 0.35 |
September | 4758947.52 | 2509106.91 | 0.00 | 2785063.15 | 0.00 | 77777309.74 | 0.180324E+09 | 0.00 | 0.36 |
October | 13541059.35 | 0.00 | 0.00 | 1397478.11 | 0.00 | 0.192540E+09 | 0.144792E+09 | 0.00 | 0.35 |
November | 15343950.61 | 0.00 | 0.00 | 362909.90 | 0.00 | 0.313212E+09 | 39990649.02 | 0.00 | 0.35 |
December | 12622709.94 | 0.00 | 0.00 | 80564.97 | 0.00 | 0.443330E+09 | 4021576.42 | 0.00 | 0.36 |
Annual Sum or Average | 0.111327E+09 | 13265193.64 | 0.00 | 23777480.78 | 0.00 | 0.272360E+10 | 0.141228E+10 | 0.00 | 0.35 |
Minimum of Months | 325486.12 | 0.00 | 0.00 | 66119.40 | 0.00 | 367904.76 | 4021576.42 | 0.00 | 0.35 |
Maximum of Months | 16956175.81 | 6743187.69 | 0.00 | 4633115.46 | 0.00 | 0.693340E+09 | 0.220074E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2935496.29 | 0.00 | 0.00 | 21352.36 | 0.00 | 0.702299E+09 | 802765.78 | 0.00 | 0.35 |
February | 10472958.68 | 0.00 | 0.00 | 171424.98 | 0.00 | 0.356050E+09 | 13202150.49 | 0.00 | 0.35 |
March | 15881766.99 | 0.00 | 0.00 | 305566.18 | 0.00 | 0.341565E+09 | 31353599.90 | 0.00 | 0.36 |
April | 32796231.05 | 0.00 | 0.00 | 964704.14 | 0.00 | 0.215290E+09 | 97732484.50 | 0.00 | 0.36 |
May | 40364376.33 | 0.00 | 0.00 | 2102988.76 | 209662.95 | 0.129269E+09 | 0.159383E+09 | 0.00 | 0.36 |
June | 46175007.71 | 2682597.71 | 0.00 | 3446274.92 | 95345.36 | 19692379.68 | 0.181376E+09 | 0.00 | 0.36 |
July | 34205845.34 | 6378117.42 | 2764.26 | 3694054.80 | 360548.08 | 264589.70 | 0.144944E+09 | 967.87 | 0.36 |
August | 42089522.64 | 1019649.95 | 334.73 | 3211217.79 | 3690.87 | 12588470.12 | 0.179123E+09 | 1147.31 | 0.36 |
September | 38237223.67 | 2297720.77 | 5269.22 | 1672931.72 | 205682.90 | 95241263.14 | 0.130462E+09 | 140.04 | 0.36 |
October | 30419021.67 | 0.00 | 0.00 | 577791.04 | 0.00 | 0.240983E+09 | 80249625.69 | 0.00 | 0.35 |
November | 16441445.17 | 0.00 | 0.00 | 103806.27 | 0.00 | 0.339746E+09 | 12575363.07 | 0.00 | 0.35 |
December | 4421413.69 | 0.00 | 0.00 | 26890.19 | 0.00 | 0.454246E+09 | 1305862.30 | 0.00 | 0.36 |
Annual Sum or Average | 0.314440E+09 | 12378085.85 | 8368.21 | 16299003.16 | 874930.16 | 0.290724E+10 | 0.103251E+10 | 2255.21 | 0.36 |
Minimum of Months | 2935496.29 | 0.00 | 0.00 | 21352.36 | 0.00 | 264589.70 | 802765.78 | 0.00 | 0.35 |
Maximum of Months | 46175007.71 | 6378117.42 | 5269.22 | 3694054.80 | 360548.08 | 0.702299E+09 | 0.181376E+09 | 1147.31 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 43364196.70 | 0.00 | 0.00 | 2808783.65 | 0.00 | 0.408035E+10 | 0.410078E+09 | 0.00 | 0.40 |
February | 38412578.72 | 0.00 | 0.00 | 6235455.45 | 0.00 | 0.160167E+10 | 0.794612E+09 | 0.00 | 0.40 |
March | 54160822.36 | 0.00 | 0.00 | 7071764.63 | 0.00 | 0.147866E+10 | 0.960203E+09 | 0.00 | 0.40 |
April | 48067164.18 | 0.00 | 0.00 | 10964212.83 | 0.00 | 0.856955E+09 | 0.131218E+10 | 0.00 | 0.40 |
May | 32215747.75 | 1347135.22 | 0.00 | 15119298.34 | 0.00 | 0.567131E+09 | 0.151305E+10 | 0.00 | 0.40 |
June | 6410968.51 | 17848956.88 | 0.00 | 20737361.60 | 0.00 | 74698626.69 | 0.150890E+10 | 0.00 | 0.40 |
July | 2091082.12 | 43321471.13 | 0.00 | 23561039.81 | 0.00 | 2428157.10 | 0.114844E+10 | 66.30 | 0.40 |
August | 4075061.45 | 6584735.08 | 0.00 | 26322267.40 | 0.00 | 33578457.66 | 0.145888E+10 | 0.00 | 0.40 |
September | 16415790.63 | 16085071.28 | 34286.78 | 19838247.86 | 0.00 | 0.215728E+09 | 0.145465E+10 | 372.53 | 0.40 |
October | 35520052.84 | 0.00 | 0.00 | 15161798.93 | 0.00 | 0.473501E+09 | 0.173898E+10 | 0.00 | 0.40 |
November | 46358967.13 | 0.00 | 0.00 | 7590839.33 | 0.00 | 0.118885E+10 | 0.112725E+10 | 0.00 | 0.40 |
December | 51493761.85 | 0.00 | 0.00 | 2939375.68 | 0.00 | 0.241757E+10 | 0.483612E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.378586E+09 | 85187369.58 | 34286.78 | 0.158350E+09 | 0.00 | 0.129911E+11 | 0.139108E+11 | 438.83 | 0.40 |
Minimum of Months | 2091082.12 | 0.00 | 0.00 | 2808783.65 | 0.00 | 2428157.10 | 0.410078E+09 | 0.00 | 0.40 |
Maximum of Months | 54160822.36 | 43321471.13 | 34286.78 | 26322267.40 | 0.00 | 0.408035E+10 | 0.173898E+10 | 372.53 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.420310E+11 | 0.00 | 0.00 | 29346021.08 | 0.00 | 0.00 | 0.320372E+11 | 0.00 | 4.46 |
February | 0.773224E+10 | 0.00 | 0.00 | 39806330.52 | 0.00 | 0.00 | 0.386149E+11 | 0.00 | 4.62 |
March | 0.310309E+10 | 0.00 | 0.00 | 51609524.18 | 0.00 | 0.00 | 0.470342E+11 | 0.00 | 4.81 |
April | 0.553619E+09 | 0.00 | 0.00 | 66306532.74 | 0.00 | 0.00 | 0.484240E+11 | 0.00 | 5.07 |
May | 0.287557E+09 | 45467.15 | 0.00 | 82678902.81 | 0.00 | 0.00 | 0.497854E+11 | 0.00 | 5.36 |
June | 3427313.86 | 0.164797E+09 | 0.00 | 0.101699E+09 | 0.00 | 0.00 | 0.435576E+11 | 0.00 | 5.82 |
July | 0.00 | 0.416788E+09 | 0.00 | 0.107452E+09 | 0.00 | 0.00 | 0.345479E+11 | 0.00 | 5.96 |
August | 10343469.47 | 0.305533E+09 | 0.00 | 99321228.58 | 0.00 | 0.00 | 0.391978E+11 | 0.00 | 5.84 |
September | 0.153374E+09 | 0.238992E+09 | 0.00 | 81052672.28 | 0.00 | 0.00 | 0.440139E+11 | 0.00 | 5.53 |
October | 0.668579E+09 | 0.00 | 0.00 | 66227676.49 | 0.00 | 0.00 | 0.521242E+11 | 0.00 | 5.10 |
November | 0.363032E+10 | 0.00 | 0.00 | 48749784.40 | 0.00 | 0.00 | 0.460029E+11 | 0.00 | 4.78 |
December | 0.134623E+11 | 0.00 | 0.00 | 38426789.37 | 0.00 | 0.00 | 0.409268E+11 | 0.00 | 4.58 |
Annual Sum or Average | 0.716358E+11 | 0.112616E+10 | 0.00 | 0.812676E+09 | 0.00 | 0.00 | 0.516267E+12 | 0.00 | 5.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 29346021.08 | 0.00 | 0.00 | 0.320372E+11 | 0.00 | 4.46 |
Maximum of Months | 0.420310E+11 | 0.416788E+09 | 0.00 | 0.107452E+09 | 0.00 | 0.00 | 0.521242E+11 | 0.00 | 5.96 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.391797E+11 | 0.00 | 0.00 | 39263380.29 | 0.00 | 0.00 | 0.400562E+11 | 0.00 | 4.82 |
February | 0.514071E+10 | 0.00 | 0.00 | 52139019.40 | 0.00 | 0.00 | 0.454484E+11 | 0.00 | 5.06 |
March | 0.852876E+09 | 0.00 | 0.00 | 66271451.21 | 0.00 | 0.00 | 0.542232E+11 | 0.00 | 5.29 |
April | 67493005.17 | 0.00 | 0.00 | 79909182.61 | 0.00 | 0.00 | 0.538710E+11 | 0.00 | 5.59 |
May | 44757536.15 | 49750.45 | 0.00 | 95837608.81 | 0.00 | 0.00 | 0.547792E+11 | 0.00 | 5.87 |
June | 0.00 | 0.178206E+09 | 0.00 | 0.111753E+09 | 0.00 | 0.00 | 0.468716E+11 | 0.00 | 6.28 |
July | 0.00 | 0.447864E+09 | 0.00 | 0.116149E+09 | 0.00 | 0.00 | 0.368032E+11 | 0.00 | 6.37 |
August | 0.00 | 0.328799E+09 | 0.00 | 0.109030E+09 | 0.00 | 0.00 | 0.419251E+11 | 0.00 | 6.26 |
September | 14630926.85 | 0.257841E+09 | 0.00 | 91592719.41 | 0.00 | 0.00 | 0.478751E+11 | 0.00 | 5.99 |
October | 0.139609E+09 | 0.00 | 0.00 | 79574607.13 | 0.00 | 0.00 | 0.578414E+11 | 0.00 | 5.60 |
November | 0.123204E+10 | 0.00 | 0.00 | 62468185.00 | 0.00 | 0.00 | 0.533305E+11 | 0.00 | 5.25 |
December | 0.963556E+10 | 0.00 | 0.00 | 51824125.02 | 0.00 | 0.00 | 0.495363E+11 | 0.00 | 5.00 |
Annual Sum or Average | 0.563074E+11 | 0.121276E+10 | 0.00 | 0.955812E+09 | 0.00 | 0.00 | 0.582561E+12 | 0.00 | 5.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 39263380.29 | 0.00 | 0.00 | 0.368032E+11 | 0.00 | 4.82 |
Maximum of Months | 0.391797E+11 | 0.447864E+09 | 0.00 | 0.116149E+09 | 0.00 | 0.00 | 0.578414E+11 | 0.00 | 6.37 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.647497E+10 | 0.00 | 0.00 | 95792975.89 | 0.00 | 97646910.38 | 0.902932E+11 | 0.00 | 20.59 |
February | 0.281683E+09 | 0.00 | 0.00 | 96722489.93 | 0.00 | 0.00 | 0.695668E+11 | 0.00 | 22.51 |
March | 12986399.07 | 0.00 | 0.00 | 0.107901E+09 | 0.00 | 0.00 | 0.754071E+11 | 0.00 | 23.14 |
April | 0.00 | 0.00 | 0.00 | 0.115545E+09 | 0.00 | 0.00 | 0.702801E+11 | 0.00 | 23.71 |
May | 0.00 | 86350.87 | 0.00 | 0.131967E+09 | 0.00 | 0.00 | 0.672830E+11 | 0.00 | 24.14 |
June | 0.00 | 0.271620E+09 | 0.00 | 0.147562E+09 | 0.00 | 0.00 | 0.509126E+11 | 0.00 | 24.86 |
July | 0.00 | 0.700256E+09 | 0.00 | 0.150567E+09 | 0.00 | 0.00 | 0.367074E+11 | 0.00 | 24.82 |
August | 0.00 | 0.527664E+09 | 0.00 | 0.143108E+09 | 0.00 | 0.00 | 0.440438E+11 | 0.00 | 24.73 |
September | 0.00 | 0.414363E+09 | 0.00 | 0.124559E+09 | 0.00 | 0.00 | 0.558594E+11 | 0.00 | 24.42 |
October | 0.00 | 0.00 | 0.00 | 0.115981E+09 | 0.00 | 0.00 | 0.740374E+11 | 0.00 | 23.70 |
November | 0.00 | 0.00 | 0.00 | 0.102604E+09 | 0.00 | 0.00 | 0.731233E+11 | 0.00 | 22.83 |
December | 0.500874E+09 | 0.00 | 0.00 | 0.103751E+09 | 0.00 | 0.00 | 0.791515E+11 | 0.00 | 22.03 |
Annual Sum or Average | 0.727051E+10 | 0.191399E+10 | 0.00 | 0.143606E+10 | 0.00 | 97646910.38 | 0.786665E+12 | 0.00 | 23.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 95792975.89 | 0.00 | 0.00 | 0.367074E+11 | 0.00 | 20.59 |
Maximum of Months | 0.647497E+10 | 0.700256E+09 | 0.00 | 0.150567E+09 | 0.00 | 97646910.38 | 0.902932E+11 | 0.00 | 24.86 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.656857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179039E+11 | 0.00 | 0.00 | 1.15 |
February | 0.911875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543737E+10 | 0.00 | 0.00 | 1.15 |
March | 0.129184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228745E+10 | 0.00 | 0.00 | 1.16 |
April | 0.138042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89058737.85 | 0.00 | 0.00 | 1.15 |
May | 0.133662E+11 | 13752.03 | 0.00 | 153775.07 | 0.00 | 28074005.05 | 50956585.73 | 0.00 | 1.16 |
June | 0.954661E+10 | 47454806.86 | 0.00 | 3929030.64 | 728074.78 | 0.00 | 0.101724E+10 | 0.00 | 1.18 |
July | 0.577027E+10 | 0.163181E+09 | 0.00 | 8279954.60 | 213169.45 | 0.00 | 0.221331E+10 | 0.00 | 1.23 |
August | 0.753469E+10 | 0.121345E+09 | 0.00 | 5673299.14 | 399380.15 | 0.00 | 0.178755E+10 | 0.00 | 1.21 |
September | 0.106944E+11 | 78847698.02 | 0.00 | 2165326.71 | 2041650.79 | 0.00 | 0.720105E+09 | 0.00 | 1.18 |
October | 0.147913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31853183.15 | 0.00 | 0.00 | 1.15 |
November | 0.124258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248191E+10 | 0.00 | 0.00 | 1.15 |
December | 0.878260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.857219E+10 | 0.00 | 0.00 | 1.15 |
Annual Sum or Average | 0.125322E+12 | 0.410842E+09 | 0.00 | 20201386.17 | 3382275.17 | 0.368318E+11 | 0.578917E+10 | 0.00 | 1.17 |
Minimum of Months | 0.577027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 |
Maximum of Months | 0.147913E+11 | 0.163181E+09 | 0.00 | 8279954.60 | 2041650.79 | 0.179039E+11 | 0.221331E+10 | 0.00 | 1.23 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:02:46
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.141886E+12 | 0.655317E+10 | 0.299975E+12 | 0.129556E+13 | 0.159259E+12 |
February | 0.215657E+12 | 0.491504E+10 | 0.223733E+12 | 0.103195E+13 | 0.917539E+11 |
March | 0.394496E+12 | 0.493430E+10 | 0.225198E+12 | 0.107307E+13 | 0.904194E+11 |
April | 0.417857E+12 | 0.373291E+10 | 0.159665E+12 | 0.792310E+12 | 0.118640E+12 |
May | 0.559679E+12 | 0.328821E+10 | 0.132510E+12 | 0.678481E+12 | 0.206167E+12 |
June | 0.609581E+12 | 0.215205E+10 | 0.731466E+11 | 0.413926E+12 | 0.399895E+12 |
July | 0.597170E+12 | 0.144553E+10 | 0.450145E+11 | 0.278707E+12 | 0.604481E+12 |
August | 0.500591E+12 | 0.176397E+10 | 0.567136E+11 | 0.331803E+12 | 0.527192E+12 |
September | 0.386088E+12 | 0.238462E+10 | 0.916201E+11 | 0.484427E+12 | 0.341251E+12 |
October | 0.233515E+12 | 0.344608E+10 | 0.149636E+12 | 0.749272E+12 | 0.156591E+12 |
November | 0.110371E+12 | 0.432819E+10 | 0.197941E+12 | 0.937618E+12 | 0.100811E+12 |
December | 0.837457E+11 | 0.572853E+10 | 0.267246E+12 | 0.120392E+13 | 0.102426E+12 |
Annual Sum or Average | 0.425064E+13 | 0.446726E+11 | 0.192240E+13 | 0.927105E+13 | 0.289889E+13 |
Minimum of Months | 0.837457E+11 | 0.144553E+10 | 0.450145E+11 | 0.278707E+12 | 0.904194E+11 |
Maximum of Months | 0.609581E+12 | 0.655317E+10 | 0.299975E+12 | 0.129556E+13 | 0.604481E+12 |