Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904

Simulation Timestamp: 2023-10-16 09:02:48


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 8748.63 771.12 771.12
Net Site Energy 8748.63 771.12 771.12
Total Source Energy 20086.85 1770.50 1770.50
Net Source Energy 20086.85 1770.50 1770.50


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 898.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 819.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 543.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 174.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1728.14 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 641.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 555.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 108.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 475.42 971.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 44.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 5090.42 3658.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 898.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 819.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 543.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 174.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 952.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 8.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 4.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 22.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 616.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 2.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 555.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 108.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.75 971.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
  Other 384.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 7.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 15.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 21.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 898.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 819.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 543.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 174.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1728.14 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 641.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 555.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 108.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 475.42 971.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 44.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 63.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 172.62 164.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 212.74 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 448.68 322.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 63.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 172.62 164.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 212.74 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 448.68 322.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 5090.416 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 5090.416 100.00
     
Total On-Site and Utility Electric Sources 5090.416 100.00
Total Electricity End Uses 5090.416 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 105.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 7219.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWHSYSLAUNDRY HPWH TANK | SWHSYS1 HPWH TANK |

DaylightingReportMonthly

| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| SWHSYS1 HPWH FAN | SWHSYSLAUNDRY HPWH FAN | FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02
RunPeriod RUNPERIOD 1
Weather File San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Latitude [deg] 32.58
Longitude [deg] -117.0
Elevation [m] 159.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 5.9798 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 8.7295 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 8.7295 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 4.1656 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 3.6813 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 5.1344 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 8.3313 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 8.1375 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 3.9719 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 3.9719 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 3.9719 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 3.9719 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 3.9719 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 3.9719 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 3.9719 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 3.9719 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 3.9719 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 3.9719 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 8.3313 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 8.3313 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 10.5594 4.65 2931.5031
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 3.9719 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 5.2589 7.07 41.0437
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 5.2589 7.07 41.0437
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 5.9798 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 8.7295 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 8.7295 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 4.1656 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 3.6813 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 5.1344 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 8.3313 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 8.1375 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 3.9719 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 3.9719 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 3.9719 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 3.9719 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 3.9719 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 3.9719 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 3.9719 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 3.9719 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 3.9719 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 3.9719 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 8.3313 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 8.3313 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 10.5594 4.65 2931.5031  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 3.9719 18.58 0.0000  
Total 11345.29             5.2589 3.54 41.0437  
Conditioned Total 11345.29             5.2589 3.54 41.0437  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 3.3293 8.82 37.1717
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 29-SEP-19:10 29-MAR-19:49 - - - - - - - - - - 19-JAN-21:10
Heating 0.00 175080.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 107030.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 45424.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 11096.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 87982.85 89710.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 31569.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 29112.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 4233.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 39714.32 76859.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 1323.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 357486.34 341650.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 175080.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 107030.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 45424.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 11096.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 58308.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 49984.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 277.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 156.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1265.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 30153.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 150.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 29112.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 4233.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 3871.05 76859.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 241.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 427.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 654.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 973.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 2594.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1722.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 552.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5473.02 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2031.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1759.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 343.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 1505.66 1052.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 139.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 16121.35 3965.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 85.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 228.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 151.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 48.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 482.40 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 179.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 155.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 30.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 132.71 92.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 12.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1420.97 349.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 85.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 228.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 151.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 48.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 482.40 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 179.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 155.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 30.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 132.71 92.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 12.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1420.97 349.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 1.93 0.781816 0.585000 1.13 1.00 0.500000 0.000487 0.000063 1.13 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.303469 0.168414 0.585000 0.177529 0.585000 0.500000 0.002262 0.000024 0.177529 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.213448 0.277275 0.585000 0.124867 0.739400 0.500000 0.001374 0.000011 0.124867 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.174514 0.717154 0.585000 0.102091 1.00 0.500000 0.000531 0.000015 0.102091 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.092881 0.777412 0.585000 0.054335 1.00 0.500000 0.000490 0.000009 0.054335 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.31 0.071363 0.585000 1.93 0.585000 0.500000 0.021186 0.000101 1.93 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.37 0.105290 0.585000 0.799593 0.585000 0.500000 0.003619 0.000077 0.799593 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 4.45 0.223945 0.585000 2.60 0.597186 0.500000 0.001701 0.000217 2.60 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.08 1.00 0.585000 0.632362 1.00 0.500000 0.000347 0.000086 0.632362 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.08 0.121447 0.585000 1.22 0.585000 0.500000 0.003137 0.000092 1.22 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.19 0.115588 0.585000 1.28 0.585000 0.500000 0.003296 0.000096 1.28 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.14 0.066123 0.585000 1.25 0.585000 0.500000 0.010364 0.000069 1.25 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.619790 0.506687 0.585000 0.362577 1.00 0.500000 0.000752 0.000055 0.362577 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 7188.37 0.000063 151.71
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 2763.92 0.000024 64.41
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1289.08 0.000011 28.35
MECH_FLR_1 VAV BOX REHEAT COIL 1741.76 0.000015 41.30
STORAGE_FLR_1 VAV BOX REHEAT COIL 1036.35 0.000009 25.16
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 11568.10 0.000101 243.18
CAFE_FLR_1 VAV BOX REHEAT COIL 8762.37 0.000077 193.99
LOBBY_FLR_1 VAV BOX REHEAT COIL 24768.51 0.000217 540.01
ROOM_1_FLR_3 FAN COIL HEATING COIL 4006.15 0.000035 114.47
ROOM_2_FLR_3 FAN COIL HEATING COIL 4006.20 0.000035 114.48
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 23240.74 0.000203 664.09
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 23253.68 0.000203 664.46
ROOM_5_FLR_3 FAN COIL HEATING COIL 4005.54 0.000035 114.46
ROOM_6_FLR_3 FAN COIL HEATING COIL 4005.59 0.000035 114.46
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 9832.60 0.000086 229.07
ROOM_1_FLR_6 FAN COIL HEATING COIL 1242.95 0.000011 35.52
ROOM_2_FLR_6 FAN COIL HEATING COIL 1242.58 0.000011 35.51
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 6000.03 0.000052 171.44
BANQUET_FLR_6 VAV BOX REHEAT COIL 10503.61 0.000092 226.89
DINING_FLR_6 VAV BOX REHEAT COIL 10920.60 0.000096 235.67
KITCHEN_FLR_6 VAV BOX REHEAT COIL 7859.86 0.000069 165.72
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 6333.37 0.000055 150.88
VAV WITH REHEAT HEATING COIL 91186.95 0.000798 1634.38
FLR_3_DOAS HEATING COIL 9427.25 0.000082 168.97
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ZoneExhaust

User-Specified Maximum Flow Rate [m3/s]
LOBBY_FLR_1 EXHAUST FAN 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 0.930494 0.000035 0.000364
ROOM_2_FLR_3 FAN COIL 0.891760 0.000035 0.000349
ROOM_3_MULT19_FLR_3 FAN COIL 5.40 0.000203 0.002071
ROOM_4_MULT19_FLR_3 FAN COIL 5.03 0.000203 0.002076
ROOM_5_FLR_3 FAN COIL 0.815198 0.000035 0.000320
ROOM_6_FLR_3 FAN COIL 0.781488 0.000035 0.000307
ROOM_1_FLR_6 FAN COIL 0.242249 0.000011 0.000095
ROOM_2_FLR_6 FAN COIL 0.231518 0.000011 0.000091
ROOM_3_MULT9_FLR_6 FAN COIL 1.12 0.000052 0.000446
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 0.930494
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 0.891760
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 5.40
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 5.03
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 0.815198
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 0.781488
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.242249
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.231518
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 1.12
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008573 12.80 0.008500 0.000364 0.930494  
ROOM_2_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008576 12.80 0.008500 0.000349 0.891760  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008494 12.80 0.008494 0.002071 5.40  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008773 12.80 0.008500 0.002076 5.03  
ROOM_5_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008583 12.80 0.008500 0.000320 0.815198  
ROOM_6_FLR_3 FAN COIL COOLING COIL 21.69 6.70 0.008586 12.80 0.008500 0.000307 0.781488  
ROOM_1_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008570 12.80 0.008500 0.000095 0.242249  
ROOM_2_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008573 12.80 0.008500 0.000091 0.231518  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21.69 6.70 0.008643 12.80 0.008500 0.000446 1.12  
VAV WITH REHEAT COOLING COIL 28.29 6.70 0.008866 10.94 0.008500 0.015608 19.84 436984.21
FLR_3_DOAS COOLING COIL 31.30 6.70 0.008233 11.91 0.008233 0.001713 2.05 47946.25
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 11.67 11.67 19.95 11.67 19.84 19.84 0.300000 0.588104 19.84
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 19.84  
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 19.84
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.015608 0.000031
VAV WITH REHEAT_HEATC_CONTROLLER 0.000798  
FLR_3_DOAS_COOLC_CONTROLLER 0.001713 0.000278
FLR_3_DOAS_HEATC_CONTROLLER 0.000082  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:WaterHeating:AirToWaterHeatPump:Pumped

Design Size Rated Evaporator Air Flow Rate [m3/s] Design Size Rated Condenser Water Flow Rate [m3/s]
SWHSYSLAUNDRY HPWH DXCOIL 4.90 0.004370
SWHSYS1 HPWH DXCOIL 3.87 0.003451
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:SystemModel

Design Size Design Maximum Air Flow Rate [m3/s] Design Electric Power Consumption [W]
SWHSYSLAUNDRY HPWH FAN 4.90 700.51
SWHSYS1 HPWH FAN 3.87 553.22
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:HeatPump:PumpedCondenser

Condenser water flow rate [m3/s] Evaporator air flow rate [m3/s]
SWHSYS1 HPWH 0.003451 3.87
SWHSYSLAUNDRY HPWH 0.004370 4.90
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.023437 4781.66  
HEATSYS1 PUMP 0.002416 720.45 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.002416 0.289944
COOLSYS1 0.023437 2.81
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 276186.18 276186.18 0.002416
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.023437 3310.50
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.023437 656170.47 656741.91 74.87
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Stratified

Use Side Design Flow Rate [m3/s]
SWHSYS1 HPWH TANK 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.80 14.30 13.60 13.20 13.30 12.60 15.30 15.60 17.70 19.40 19.70 18.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 32.58 -116.98 -8.00 159.00 99429 1.1818


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 16.00 7.10 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 5.980 5.380 0.000 0.000 0.000 0.000 11.360 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 8.730 10.760 0.000 0.000 0.000 0.000 19.490 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 8.730 10.760 0.000 0.000 0.000 0.000 19.490 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 4.166 5.380 0.000 0.000 0.000 0.000 9.546 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 3.681 2.690 0.000 0.000 0.000 0.000 6.371 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 5.134 61.680 535.850 0.000 0.000 0.000 602.664 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 8.331 5.380 0.000 0.000 0.000 0.000 13.711 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 8.138 8.070 0.000 0.000 0.000 0.000 16.208 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 3.972 6.750 0.000 0.000 0.000 0.000 10.722 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 3.972 6.750 0.000 0.000 0.000 0.000 10.722 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 3.972 10.520 0.000 0.000 0.000 0.000 14.492 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 3.972 10.520 0.000 0.000 0.000 0.000 14.492 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 3.972 6.750 0.000 0.000 0.000 0.000 10.722 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 3.972 6.750 0.000 0.000 0.000 0.000 10.722 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 3.972 0.000 0.000 0.000 0.000 0.000 3.972 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 3.972 6.750 0.000 0.000 0.000 0.000 10.722 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 3.972 6.750 0.000 0.000 0.000 0.000 10.722 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 3.972 10.520 0.000 0.000 0.000 0.000 14.492 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 8.331 67.820 0.000 0.000 0.000 0.000 76.151 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 8.331 67.820 0.000 0.000 0.000 0.000 76.151 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 10.559 512.243 2419.260 0.000 0.000 0.000 2942.062 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 3.972 0.000 0.000 0.000 0.000 0.000 3.972 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 11832.934 5.980 111.108 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 11832.934
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 585.501 8.730 54.068 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 585.501
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 678.012 8.730 54.068 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 678.012
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 684.177 4.166 257.985 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 684.177
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 348.833 3.681 170.996 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 348.833
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 400.685 5.134 47.701 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 400.685
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 1573.457 8.331 11.057 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1573.457
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 10645.380 8.138 25.200 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 10645.380
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 154.991 3.972 103.327 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 154.991
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 154.973 3.972 103.315 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 154.973
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 97.406 3.972 64.937 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 97.406
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 97.432 3.972 64.955 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 97.432
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 154.991 3.972 103.327 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 154.991
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 154.973 3.972 103.315 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 154.973
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 1546.669 3.972 73.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1546.669
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 154.991 3.972 103.327 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 154.991
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 154.973 3.972 103.315 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 154.973
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 97.432 3.972 64.955 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 97.432
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 2763.123 8.331 11.057 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2763.123
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 2763.123 8.331 11.057 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2763.123
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1090.832 10.559 49.053 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1090.832
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 1636.910 3.972 73.801 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1636.910


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 277.500 2.686 12.479 0.000 0.250 0.000 0.750 ReachInFreezer 277.500 277.500
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 156.700 1.517 7.046 0.000 0.250 0.000 0.750 ReachInRefrigerator 156.700 156.700


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.760 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 1.067 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 1.370 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 1.442 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 1.217 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 1.286 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.5681
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.7702
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.5624
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.5260
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.6546
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.6103
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.7602615 1.7602615 1.7602615  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
21 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
22 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
23 0 21.361010 0.87247630E-01 5.4456762  
24 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
25 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
26 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
27 0 21.361010 0.87247630E-01 5.4456762  
28 9 -0.55514967E-15 0.35055860E-16 -0.14326465E-09 0.28783368E-17
29 8 0.20966873E-07 0.14258959E-12 0.36819155E-03 -0.23840058E-09
30 7 -0.11954852E-01 0.74774803E-08 -0.22672946E-01 0.13593102E-03
31 6 0.39755982 0.26159305E-05 0.46545104 -0.46559307E-02
32 5 -5.1145337 0.98147117E-04 -4.3902405 0.62241115E-01
33 4 32.666535 0.80637729E-03 21.240866 -0.41765750
34 3 -110.51061 0.17642800E-02 -55.229641 1.5048560
35 2 196.42192 0.99585215E-03 77.513220 -2.8894543
36 1 -170.90254 0.10665179E-03 -55.149704 2.7409959
37 0 57.057407 0.60929387E-06 15.576129  
38 9 0.10314710E-14 0.47183642E-16 -0.12881513E-09 -0.40099708E-17
39 8 0.18927665E-07 0.17950474E-12 0.34608657E-03 -0.21521408E-09
40 7 -0.11292911E-01 0.96443222E-08 -0.21719088E-01 0.12840450E-03
41 6 0.37957032 0.34070209E-05 0.45007157 -0.44438791E-02
42 5 -4.9389364 0.12890179E-03 -4.2718596 0.60063826E-01
43 4 31.889569 0.10670331E-02 20.777560 -0.40734193
44 3 -108.85680 0.23501275E-02 -54.313423 1.4809641
45 2 194.78196 0.13343675E-02 76.673975 -2.8634131
46 1 -170.29645 0.14368413E-03 -54.907648 2.7303734
47 0 57.057407 0.82565881E-06 15.617726  
48 9 0.86975537E-15 0.52023775E-16 -0.12536948E-09 -0.54620444E-17
49 8 0.18440443E-07 0.18784465E-12 0.34068694E-03 -0.20967419E-09
50 7 -0.11130813E-01 0.10155400E-07 -0.21485363E-01 0.12656138E-03
51 6 0.37516444 0.35965268E-05 0.44629465 -0.43919449E-02
52 5 -4.8959230 0.13636263E-03 -4.2427425 0.59530495E-01
53 4 31.699203 0.11309484E-02 20.663505 -0.40481456
54 3 -108.45147 0.24950915E-02 -54.087828 1.4751087
55 2 194.37988 0.14187814E-02 76.467519 -2.8570287
56 1 -170.14779 0.15298304E-03 -54.848449 2.7277680
57 0 57.057407 0.88039223E-06 15.628184  
58 9 0.12430042E-14 0.43603463E-16 -0.13615479E-09 -0.52742981E-17
59 8 0.19963588E-07 0.16114398E-12 0.35741204E-03 -0.22699287E-09
60 7 -0.11632381E-01 0.85488282E-08 -0.22208377E-01 0.13226440E-03
61 6 0.38879653 0.30047059E-05 0.45796739 -0.45526330E-02
62 5 -5.0290001 0.11318598E-03 -4.3326723 0.61180550E-01
63 4 32.288109 0.93328928E-03 21.015642 -0.41263319
64 3 -109.70522 0.20484795E-02 -54.784283 1.4932205
65 2 195.62339 0.11595496E-02 77.105128 -2.8767741
66 1 -170.60747 0.12450863E-03 -55.031726 2.7358244
67 0 57.057407 0.71328115E-06 15.596176  
68 9 0.10418955E-14 0.45554749E-16 -0.13285794E-09 -0.34221686E-17
69 8 0.19498290E-07 0.16949498E-12 0.35235048E-03 -0.22170227E-09
70 7 -0.11480752E-01 0.90423087E-08 -0.21989859E-01 0.13054032E-03
71 6 0.38467563 0.31853038E-05 0.45444290 -0.45040579E-02
72 5 -4.9887746 0.12022067E-03 -4.3055366 0.60681782E-01
73 4 32.110117 0.99300969E-03 20.909427 -0.41027004
74 3 -109.32633 0.21828955E-02 -54.574228 1.4877470
75 2 195.24766 0.12373115E-02 76.912747 -2.8708078
76 1 -170.46860 0.13302463E-03 -54.976289 2.7333905
77 0 57.057407 0.76310210E-06 15.605744  
78 7 -0.15963512E-14 -0.15187529E-16 -0.22427203E-13 0.56155309E-15
79 6 0.17983713E-10 0.23594901E-11 0.52322926E-09 -0.18637893E-10
80 5 -0.60139213E-07 0.11510628E-07 -0.21924491E-05 0.17161312E-06
81 4 0.62746279E-04 0.43399923E-05 0.17681060E-02 -0.28244642E-03
82 3 -0.90508353E-02 0.15320797E-03 -0.21560640 0.43341486E-01
83 2 0.12836503 0.66328859E-03 2.9007871 -0.61911613
84 1 -0.32478029 0.41934727E-03 -7.1379041 1.5697129
85 0 0.20664896 0.54311639E-05 4.4522013  
86 7 -0.22427203E-13 -0.15187529E-16 -0.15963512E-14 0.56155309E-15
87 6 0.52322926E-09 0.23594901E-11 0.17983713E-10 -0.18637893E-10
88 5 -0.21924491E-05 0.11510628E-07 -0.60139213E-07 0.17161312E-06
89 4 0.17681060E-02 0.43399923E-05 0.62746279E-04 -0.28244642E-03
90 3 -0.21560640 0.15320797E-03 -0.90508353E-02 0.43341486E-01
91 2 2.9007871 0.66328859E-03 0.12836503 -0.61911613
92 1 -7.1379041 0.41934727E-03 -0.32478029 1.5697129
93 0 4.4522013 0.54311639E-05 0.20664896  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
103 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
104 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
105 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
106 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
107 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
108 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
109 0 1.0055995 0.48413807E-04 60.838472  
110 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
111 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
112 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
113 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
114 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
115 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
116 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
117 0 1.0055995 0.48413807E-04 60.838472  
118 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
119 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
120 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
121 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
122 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
123 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
124 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
125 0 1.0055995 0.48413807E-04 60.838472  
126 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
127 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
128 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
129 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
130 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
131 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
132 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
133 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.4295_SHGC_0.25 37 1 VerySmooth 2.441 2.441 1.000 0.251    
2 RESWINDOW_U_0.4295_SHGC_0.25 38 1 VerySmooth 2.441 2.441 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   2.91738E-002 0.16139 0.61970 0.61970 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.12244 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   2.91738E-002 0.16139 0.61970 0.61970 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.12244 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 CAFE_FLR_1 1 0
2 LOBBY_FLR_1 1 0
3 BANQUET_FLR_6 1 0
4 DINING_FLR_6 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 CAFE_FLR_1 0  
2 LOBBY_FLR_1 0  
3 BANQUET_FLR_6 0  
4 DINING_FLR_6 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 2.320
2 RACK2 1 0 Zone Air-Cooled 6.980


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473


Heat Pump Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor "DX Coil Total Cooling Rate {W HPWH Only}"
1 WaterHeater:HeatPump:PumpedCondenser SWHSYSLAUNDRY HPWH 1.1400 77190.6 48.891 1.7238 76621  
2 WaterHeater:HeatPump:PumpedCondenser SWHSYS1 HPWH 2.8400 62753.2 4.643 9.4630 53264  


Water Heater Stratified Node Information

Node Number Height {m} Volume {m3} Maximum Capacity {W} Off-Cycle UA {W/K} On-Cycle UA {W/K} Number Of Inlets Number Of Outlets
1 1 0.2683 0.4733 0.000 2.4569 2.4569 0 1
2 2 0.2683 0.4733 28436.950 1.5573 1.5573 0 0
3 3 0.2683 0.4733 0.000 1.5573 1.5573 0 0
4 4 0.2683 0.4733 0.000 1.5573 1.5573 0 0
5 5 0.2683 0.4733 0.000 1.5573 1.5573 0 1
6 6 0.2683 0.4733 0.000 2.4569 2.4569 2 0


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 3.921E-002 5.846E-004 2.885E-004 0.531 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 1.513E-002 1.949E-004 5.306E-004 0.177 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 3.577E-002 2.178E-004 5.696E-004 0.198 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 2.064E-002 2.178E-004 4.726E-004 0.198 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 4.884E-002 6.258E-004 5.569E-004 0.569 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 8.667E-002 4.589E-004 2.527E-004 0.417 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.248 1.893E-004 3.620E-004 0.172 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 6.349E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 6.350E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 2.751E-002 7.066E-005 5.696E-004 8.345E-002 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.164E-002 4.746E-004 2.589E-004 0.561 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 4.974E-002 4.815E-004 2.609E-004 0.569 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 4.868E-002 1.181E-004 9.784E-005 0.140 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 8.7013E-002
2 Clear Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 3.9098E-002
3 Clear Turbid Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 9.6674E-002
4 Clear Turbid Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 4.2679E-002
5 Intermediate Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 6.5685E-002
6 Intermediate Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 2.4415E-002
7 Overcast Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT1 2.6511E-002
8 Overcast Sky 12/21 LOBBY_FLR_1_DAYLCTRL LOBBY_FLR_1 LOBBY_FLR_1_WALL_SOUTH_WINDOW LOBBY_FLR_1_DAYLREFPT2 8.7811E-003
9 Clear Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 9.8305E-002
10 Clear Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 4.7836E-002
11 Clear Turbid Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 0.1095
12 Clear Turbid Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 5.2162E-002
13 Intermediate Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 7.2719E-002
14 Intermediate Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 3.0822E-002
15 Overcast Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT1 2.9789E-002
16 Overcast Sky 12/21 CAFE_FLR_1_DAYLCTRL CAFE_FLR_1 CAFE_FLR_1_WALL_SOUTH_WINDOW CAFE_FLR_1_DAYLREFPT2 1.2036E-002
17 Clear Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.1172E-002
18 Clear Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 1.2102E-002
19 Clear Turbid Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.6312E-002
20 Clear Turbid Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 9.1416E-003
21 Intermediate Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 1.5604E-002
22 Intermediate Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 6.2330E-003
23 Overcast Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT1 2.6108E-002
24 Overcast Sky 12/21 DINING_FLR_6_DAYLCTRL DINING_FLR_6 DINING_FLR_6_WALL_NORTH_WINDOW DINING_FLR_6_DAYLREFPT2 9.2309E-003
25 Clear Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.1172E-002
26 Clear Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 1.2102E-002
27 Clear Turbid Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.6312E-002
28 Clear Turbid Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 9.1416E-003
29 Intermediate Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 1.5604E-002
30 Intermediate Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 6.2330E-003
31 Overcast Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT1 2.6108E-002
32 Overcast Sky 12/21 BANQUET_FLR_6_DAYLCTRL BANQUET_FLR_6 BANQUET_FLR_6_WALL_NORTH_WINDOW BANQUET_FLR_6_DAYLREFPT2 9.2309E-003


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 26051.10188 26051.10188 1.92867 1.92867 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:40:00 27.17633 8.22696E-003 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 1342.21853 1342.21853 5.86214E-002 0.85446 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 4098.69073 4098.69073 0.30347 0.30347 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 30.92917 8.23290E-003 67.07136 10.82900 7.92170E-002 0.00000
4 RETAIL_1_FLR_1 Heating 1844.61752 1844.61752 8.05615E-002 8.05615E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 67.07136 10.82900 7.92170E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 2882.78792 2882.78792 0.21345 0.21345 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 29.75733 8.23104E-003 77.66889 12.54000 9.17335E-002 0.00000
6 RETAIL_2_FLR_1 Heating 642.49277 642.49277 2.80606E-002 9.17335E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 77.66889 12.54000 9.17335E-002 0.00000
7 MECH_FLR_1 Cooling 2357.47027 2357.47027 0.17451 0.17451 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 29.16400 8.23009E-003 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 1213.18142 1213.18142 5.29851E-002 5.29851E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1254.69464 1254.69464 9.28807E-002 9.28807E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 31.12200 8.23321E-003 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 755.02012 755.02012 3.29751E-002 5.77652E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 44664.92776 44664.92776 3.30666 3.30666 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 31.30000 8.23349E-003 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 1553.65381 1553.65381 6.78539E-002 6.78539E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 18445.11790 18445.11790 1.36683 1.36683 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 30.92917 8.23290E-003 188.86188 142.30000 0.67638 0.00000
14 CAFE_FLR_1 Heating 4621.50655 4621.50655 0.20184 0.67638 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 188.86188 142.30000 0.67638 0.00000
15 LOBBY_FLR_1 Cooling 60101.48069 60101.48069 4.45127 4.45127 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 31.07750 8.23314E-003 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 11283.85015 11283.85015 0.49282 1.89399 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 9327.34536 9327.34536 0.93049 0.93049 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 30.52867 8.23226E-003 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 4006.17594 4006.17594 0.17599 0.17599 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 3.80000 5.05843E-003 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 8939.06398 8939.06398 0.89176 0.89176 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 30.41000 8.23207E-003 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 4006.22707 4006.22707 0.17600 0.17600 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 3.80000 5.05843E-003 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 54172.82451 54172.82451 5.40404 5.40404 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 31.07750 8.23314E-003 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 23240.80647 23240.80647 1.02099 1.02099 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 3.80000 5.05843E-003 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 50451.54565 50451.54565 5.03322 5.03322 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 31.30000 8.23349E-003 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 23253.74603 23253.74603 1.02156 1.02156 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 3.80000 5.05843E-003 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 8171.60738 8171.60738 0.81520 0.81520 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 27.16150 8.22694E-003 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 4005.56277 4005.56277 0.17597 0.17597 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 3.80000 5.05843E-003 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 7833.68576 7833.68576 0.78149 0.78149 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 26.65717 8.22614E-003 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 4005.61390 4005.61390 0.17597 0.17597 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 3.80000 5.05843E-003 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 14601.21214 14601.21214 1.08096 1.08096 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 31.30000 8.23349E-003 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 6557.46013 6557.46013 0.28640 0.47476 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 2428.32435 2428.32435 0.24225 0.24225 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 30.52867 8.23226E-003 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 1242.95501 1242.95501 5.46036E-002 5.46036E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 3.80000 5.05843E-003 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2320.75714 2320.75714 0.23152 0.23152 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 30.41000 8.23207E-003 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 1242.58941 1242.58941 5.45875E-002 5.45875E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 3.80000 5.05843E-003 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 11212.06202 11212.06202 1.11854 1.11854 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 31.07750 8.23314E-003 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 6000.05977 6000.05977 0.26359 0.26359 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 3.80000 5.05843E-003 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 28073.39109 28073.39109 2.08093 2.08093 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 31.30000 8.23349E-003 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 4198.26307 4198.26307 0.18336 1.18780 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 3.80000 5.05843E-003 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 29496.86569 29496.86569 2.18640 2.18640 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 31.30000 8.23349E-003 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 4295.60135 4295.60135 0.18761 1.18780 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 11:40:00 3.80000 5.05843E-003 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 28847.39734 28847.39734 2.14123 2.14123 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 30.49900 8.23222E-003 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 1393.06664 1393.06664 6.08343E-002 0.36735 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 3.80000 5.05843E-003 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 8371.97466 8371.97466 0.61979 0.61979 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 31.30000 8.23349E-003 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 4455.23012 4455.23012 0.19458 0.19458 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 11:40:00 3.80000 5.05843E-003 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 364825.39 19.84178 19.84178 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 110112.99 7.18799 7.18799 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 11:50:00
3 FLR_3_DOAS Cooling Sensible 45064.07 14.73886 2.05125 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
4 FLR_3_DOAS Heating Sensible 31423.05 3.11926 2.05125 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.92867
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.78182
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.58500
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.12827
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.87327E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.28870E-005
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.12827
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7188.37295
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.28870E-005
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 151.70759
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.30347
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16841
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.58500
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.17753
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.58500
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.26228E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.41800E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.17753
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2763.91939
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.41800E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 64.40709
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.21345
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.27728
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.58500
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.12487
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.73940
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.37409E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.12775E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.12487
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1289.08390
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.12775E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 28.34557
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.17451
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.71715
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.58500
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.10209
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.31267E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.52376E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.10209
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1741.75514
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.52376E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 41.29675
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.28807E-002
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.77741
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.58500
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.43352E-002
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.90088E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.06648E-006
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.43352E-002
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1036.35464
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.06648E-006
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 25.16486
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.30666
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.13631E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.58500
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.93440
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.58500
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.11858E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.01203E-004
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.93440
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11568.10215
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.01203E-004
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 243.17574
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.36683
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10529
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.58500
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.79959
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.58500
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.61858E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.66570E-005
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.79959
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8762.36853
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.66570E-005
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 193.99044
99 Fan:ZoneExhaust LOBBY_FLR_1 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.45127
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22394
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.58500
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.60399
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.59719
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.70131E-003
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.16686E-004
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.60399
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
110 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 24768.50823
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.16686E-004
113 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 540.00992
114 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
115 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.93049
116 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.93049
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.50476E-005
118 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.63810E-004
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69394
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57297E-003
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.63810E-004
125 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.93049
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 4006.15248
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.50476E-005
128 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 114.47483
129 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
130 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.89176
131 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.89176
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.50480E-005
133 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.48956E-004
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69394
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57601E-003
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.48956E-004
140 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.89176
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 4006.20361
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.50480E-005
143 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 114.47629
144 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
145 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 5.40404
146 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 5.40404
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.03320E-004
148 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.07069E-003
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69438
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.49444E-003
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.49444E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.07069E-003
155 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.40404
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 23240.74069
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.03320E-004
158 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 664.08953
159 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
160 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 5.03322
161 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 5.03322
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.03433E-004
163 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.07573E-003
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69343
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.77287E-003
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.07573E-003
170 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.03322
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 23253.68022
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.03433E-004
173 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 664.45924
174 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
175 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.81520
176 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.81520
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.50422E-005
178 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.19595E-004
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69393
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.58286E-003
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.19595E-004
185 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.81520
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 4005.53932
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.50422E-005
188 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 114.45731
189 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
190 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.78149
191 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.78149
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.50427E-005
193 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.06669E-004
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69392
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.58632E-003
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.06669E-004
200 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.78149
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 4005.59045
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.50427E-005
203 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 114.45877
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.08096
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.58500
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.63236
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.46991E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.60198E-005
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.63236
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
214 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9832.59559
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.60198E-005
217 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 229.07498
218 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
219 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.24225
220 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.24225
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.08739E-005
222 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 9.46436E-005
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69395
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57018E-003
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 9.46436E-005
229 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.24225
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1242.94791
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.08739E-005
232 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 35.51565
233 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
234 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.23152
235 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.23152
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.08707E-005
237 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 9.05289E-005
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69394
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57331E-003
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 9.05289E-005
244 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.23152
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1242.58232
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.08707E-005
247 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 35.50520
248 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
249 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.11854
250 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.11854
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 5.24909E-005
252 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.45677E-004
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 21.69364
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.64262E-003
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.45677E-004
259 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.11854
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6000.03242
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.24909E-005
262 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 171.44217
263 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.08093
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12145
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.58500
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.21734
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.58500
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.13716E-003
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.18902E-005
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.21734
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
273 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
274 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10503.61462
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.18902E-005
276 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 226.88656
277 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.18640
278 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11559
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.58500
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.27905
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.58500
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.29618E-003
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.55382E-005
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.27905
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
287 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
288 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10920.59952
289 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.55382E-005
290 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 235.67160
291 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.14123
292 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.61227E-002
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.58500
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.25262
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.58500
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.03637E-002
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.87615E-005
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.25262
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
301 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
302 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7859.86047
303 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.87615E-005
304 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 165.71697
305 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.61979
306 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.50669
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.58500
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.36258
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.51944E-004
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.54071E-005
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.36258
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
315 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
316 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6333.37171
317 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.54071E-005
318 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 150.88398
319 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 11.66903
320 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 11.66903
321 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 19.94706
322 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 11.66903
323 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 19.84178
324 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 19.84178
325 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
326 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.58810
327 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
328 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
329 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
333 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
334 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
335 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 19.84178
336 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
337 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 19.84178
338 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 28.28650
339 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
340 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.94359
341 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.86614E-003
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 436984.21116
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.56081E-002
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 19.84178
346 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 91186.95413
347 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 7.97743E-004
348 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1634.37624
349 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 19.84178
350 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.56081E-002
351 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 3.05093E-005
352 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 7.97743E-004
353 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
354 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
355 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 31.30000
356 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
357 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.91243
358 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.23349E-003
359 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.23349E-003
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 47946.24805
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.71253E-003
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
363 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 9427.24706
364 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.24737E-005
365 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 168.96790
366 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
367 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.71253E-003
368 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 2.78063E-004
369 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 8.24737E-005
370 Coil:WaterHeating:AirToWaterHeatPump:Pumped SWHSYSLAUNDRY HPWH DXCOIL Design Size Rated Evaporator Air Flow Rate [m3/s] 4.90359
371 Coil:WaterHeating:AirToWaterHeatPump:Pumped SWHSYSLAUNDRY HPWH DXCOIL Design Size Rated Condenser Water Flow Rate [m3/s] 4.36989E-003
372 Fan:SystemModel SWHSYSLAUNDRY HPWH FAN Design Size Design Maximum Air Flow Rate [m3/s] 4.90359
373 Fan:SystemModel SWHSYSLAUNDRY HPWH FAN Design Electric Power Consumption [W] 700.51236
374 Coil:WaterHeating:AirToWaterHeatPump:Pumped SWHSYS1 HPWH DXCOIL Design Size Rated Evaporator Air Flow Rate [m3/s] 3.87257
375 Coil:WaterHeating:AirToWaterHeatPump:Pumped SWHSYS1 HPWH DXCOIL Design Size Rated Condenser Water Flow Rate [m3/s] 3.45109E-003
376 Fan:SystemModel SWHSYS1 HPWH FAN Design Size Design Maximum Air Flow Rate [m3/s] 3.87257
377 Fan:SystemModel SWHSYS1 HPWH FAN Design Electric Power Consumption [W] 553.22422
378 WaterHeater:HeatPump:PumpedCondenser SWHSYS1 HPWH Condenser water flow rate [m3/s] 3.45109E-003
379 WaterHeater:HeatPump:PumpedCondenser SWHSYS1 HPWH Evaporator air flow rate [m3/s] 3.87257
380 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 2.34369E-002
381 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 4781.65758
382 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 2.41620E-003
383 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.28994
384 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 2.41620E-003
385 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 720.44800
386 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
387 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 276186.17746
388 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 276186.18000
389 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 2.41620E-003
390 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 2.34369E-002
391 PlantLoop COOLSYS1 Plant Loop Volume [m3] 2.81243
392 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 2.34369E-002
393 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 3310.50282
394 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 2.34369E-002
395 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 656170.47228
396 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 656741.91000
397 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 74.86858
398 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
399 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
400 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
401 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
402 WaterHeater:Stratified SWHSYS1 HPWH TANK Use Side Design Flow Rate [m3/s] 3.75036E-004
403 WaterHeater:HeatPump:PumpedCondenser SWHSYSLAUNDRY HPWH Condenser water flow rate [m3/s] 4.36989E-003
404 WaterHeater:HeatPump:PumpedCondenser SWHSYSLAUNDRY HPWH Evaporator air flow rate [m3/s] 4.90359


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 7225.14
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 2776.61
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1295.35
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 1749.63
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 1040.86
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 11627.49
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 8804.67
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 24891.61
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 4314.91
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 4314.97
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 25031.80
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 25045.73
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 4314.25
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 4314.31
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 9877.74
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 1338.72
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 1338.32
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 6462.31
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 10556.24
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 10975.35
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 7900.10
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 6361.87
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 76523.86
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 7911.32


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 15403.04 12394.54 3008.50 0.80 1778.73 18.04
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 14769.88 11882.47 2887.41 0.80 1705.45 17.30
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 88312.45 71440.27 16872.18 0.81 10230.25 103.76
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 86242.57 68455.67 17786.90 0.79 9904.55 100.46
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 13518.36 10870.30 2648.06 0.80 1560.62 15.83
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 12967.34 10424.66 2542.69 0.80 1496.85 15.18
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 4008.09 3225.88 782.21 0.80 462.89 4.69
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 3832.70 3084.02 748.67 0.80 442.59 4.49
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 18745.18 15010.22 3734.95 0.80 2160.23 21.91
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 496894.73 343981.26 152913.46 0.69 58848.60 596.88
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 51527.24 35531.42 15995.82 0.69 5813.13 58.96


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 4.12 14.07


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.940 0.824   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.760 1.760   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.067 0.920   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.370 1.137   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.370 1.137   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.370 1.137   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.370 1.137   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.286 1.078   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.286 1.078   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.286 1.078   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.286 1.078   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.286 1.078   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.442 1.186   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4295_SHGC_0.25 N/A 2.441 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 1.6972741034E-002 2.0735537038E-002 Pass Pass 5.8075506864E-003 1.7136889100E-002 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 1.3839237302E-002 3.5612339039E-002 Pass Pass 5.5876871785E-002 6.8257964936E-002 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 2.7230337002E-002 2.9487911438E-002 Pass Pass 7.6708884604E-003 1.9567771136E-002 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 5.1807601398E-003 1.0356621526E-002 Pass Pass 1.8786644373E-002 3.9504071625E-002 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 1.3617515299E-003 3.6027976945E-003 Pass Pass 2.5237281850E-002 3.3588470268E-002 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 8.7211154076E-002 0.2192638581 Pass Pass 1.8579175604E-002 4.8799014327E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 5.5684396526E-002 7.6439122548E-002 Pass Pass 1.6668891135E-002 2.8055380108E-002 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 4.0410023201E-002 4.5254748930E-002 Pass Pass 8.3573993623E-003 1.8501698337E-002 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 3.4871640328E-002 8.3191659942E-002 Pass Pass 0.2793494718 0.9797869274 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 3.0720000563E-002 8.0121724691E-002 Pass Pass 0.1415930450 0.6580821446 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 5.6403167219E-002 6.9761931556E-002 Pass Pass 2.9342315860E-002 0.2040910988 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 4.5467750654E-002 0.1300470710 Pass Pass 0.2839190702 1.2802074379 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 4.9092175334E-002 0.1856966186 Pass Pass 0.2322985140 0.6428758339 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 3.8098238967E-002 0.1381634992 Pass Pass 0.5411119102 2.3131761203 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 3.8799490127E-003 7.9761540400E-003 Pass Pass 2.4320520167E-002 4.9264869507E-002 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 3.5341683727E-002 8.3175878719E-002 Pass Pass 0.1530112654 0.5295461527 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 4.7433401308E-002 0.1398026393 Pass Pass 0.1166153689 0.4539126503 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 7.7474868972E-002 0.2269792456 Pass Pass 0.7863131014 6.0294549908 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 4.1820627372E-002 7.4204103582E-002 Pass Pass 1.1130377700E-002 3.0837427889E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 3.1798039139E-002 6.5982847533E-002 Pass Pass 1.1898661387E-002 3.4503511482E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 3.0255239014E-002 9.2696739226E-002 Pass Pass 2.1036492703E-002 3.7540619113E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 4.3594247009E-003 8.4059833992E-003 Pass Pass 2.1951796756E-002 2.4006790921E-002 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3546.82 78.58 970.06 4240.89 4113.74 12950.11



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 3.80 0.00 3.80 Wetbulb [C] 3.00 120.00
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 31.30 8.90 18.40 Wetbulb [C] 4.10 280.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 2.00 2      
Feb 59.00 53      
Mar 58.58 43      
Apr 46.42 14      
May 18.00 12      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 3.00 6      
Oct 0.00 0      
Nov 18.00 12      
Dec 4.00 4      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.845 0.940 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.920 1.067 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.920 1.067 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.920 1.067 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.920 1.067 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.55 0.221 0.228 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 0.920 1.067 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 0.920 1.067 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.55 0.221 0.228 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.029 1.217 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.029 1.217 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.029 1.217 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.029 1.217 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.029 1.217 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.029 1.217 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.029 1.217 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.029 1.217 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.029 1.217 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.029 1.217 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 1.137 1.370 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 1.137 1.370 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 1.137 1.370 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 1.137 1.370 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.078 1.286 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.078 1.286 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 1.078 1.286 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.078 1.286 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.078 1.286 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.55 0.221 0.228 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.186 1.442 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.186 1.442 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.186 1.442 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.186 1.442 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 1.186 1.442 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.55 0.221 0.228 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 1.186 1.442 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 1.186 1.442 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 1.186 1.442 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.55 0.221 0.228 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.55 0.221 0.228 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.186 0.196 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.186 0.196 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.186 0.196 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.186 0.196 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.186 0.196 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.186 0.196 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.186 0.196 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.186 0.196 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.186 0.196 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.186 0.196 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.185 0.196 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.185 0.196 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.185 0.196 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.188 0.196 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.4295_SHGC_0.25   23.26 0.00 0.00 23.26 23.26 2.441 0.251 0.251             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.4295_SHGC_0.25   65.50 0.00 0.00 65.50 65.50 2.441 0.251 0.251             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.4295_SHGC_0.25   85.08 0.00 0.00 85.08 85.08 2.441 0.251 0.251             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.4295_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.441 0.251 0.251             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.4295_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.441 0.251 0.251             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.4295_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.441 0.251 0.251             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.4295_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.441 0.251 0.251             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.4295_SHGC_0.25   3.68 0.00 0.00 3.68 279.56 2.441 0.251 0.251             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.4295_SHGC_0.25   3.68 0.00 0.00 3.68 279.65 2.441 0.251 0.251             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.4295_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.441 0.251 0.251             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.4295_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.441 0.251 0.251             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.4295_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.441 0.251 0.251             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.4295_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.441 0.251 0.251             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.4295_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 2.441 0.251 0.251             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.4295_SHGC_0.25   2.15 0.00 0.00 2.15 8.59 2.441 0.251 0.251             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.4295_SHGC_0.25   2.15 0.00 0.00 2.15 8.58 2.441 0.251 0.251             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.4295_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 2.441 0.251 0.251             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.4295_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.441 0.251 0.251             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.4295_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 2.441 0.251 0.251             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.4295_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.441 0.251 0.251             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.4295_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 2.441 0.251 0.251             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.4295_SHGC_0.25   6.74 0.00 0.00 6.74 60.70 2.441 0.251 0.251             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.4295_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 2.441 0.251 0.251             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.4295_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 2.441 0.251 0.251             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.4295_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.441 0.251 0.251             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.4295_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 2.441 0.251 0.251             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.4295_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.441 0.251 0.251             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.4295_SHGC_0.25   5.82 0.00 0.00 5.82 5.82 2.441 0.251 0.251             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.4295_SHGC_0.25   5.21 0.00 0.00 5.21 5.21 2.441 0.251 0.251             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.4295_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 2.441 0.251 0.251             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 2.441 0.251 0.251                      
North Total or Average             432.95 2.441 0.251 0.251                      
Non-North Total or Average             780.84 2.441 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.393 1.760 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 5.9798 1978.83 11832.93 LightsWired LTG_SCH_BASEMENT 45.99 168.00 45.94 0.0000 Y 102.03
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 8.7295 67.07 585.50 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 5.64
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 8.7295 77.67 678.01 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 6.53
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 4.1656 164.24 684.18 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 7.53
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 3.6813 94.76 348.83 LightsWired LTG_SCH_STORAGE 25.68 168.00 25.65 0.0000 Y 1.68
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 5.1344 78.04 400.68 LightsWired LTG_SCH_LAUNDRY 58.69 168.00 58.63 0.0000 Y 4.41
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 8.3313 188.86 1573.46 LightsWired LTG_SCH_DINING 58.69 168.00 39.98 0.0000 Y 11.81
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 8.1375 1308.19 10645.38 LightsWired LTG_SCH_LOBBY 58.69 168.00 55.44 0.0000 Y 110.79
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 3.9719 156.09 619.96 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 5.55
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 3.9719 156.07 619.89 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 5.55
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 3.9719 1863.81 7402.84 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 66.32
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 3.9719 1864.32 7404.86 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 66.33
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 3.9719 156.09 619.96 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 5.55
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 3.9719 156.07 619.89 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 5.55
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 3.9719 1557.62 6186.67 LightsWired LTG_SCH_CORRIDOR 44.02 168.00 43.97 0.0000 Y 51.06
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 3.9719 39.02 154.99 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.39
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 3.9719 39.02 154.97 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 1.39
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 3.9719 220.77 876.89 LightsWired LTG_SCH_GUESTROOM 47.59 168.00 47.72 0.0000 Y 7.86
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 8.3313 331.66 2763.12 LightsWired LTG_SCH_DINING 58.69 168.00 49.61 0.0000 Y 25.73
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 8.3313 331.66 2763.12 LightsWired LTG_SCH_DINING 58.69 168.00 49.61 0.0000 Y 25.73
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 10.5594 103.30 1090.83 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 12.00
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 3.9719 412.12 1636.91 LightsWired LTG_SCH_CORRIDOR 44.02 168.00 43.97 0.0000 Y 13.51
Interior Lighting Total       5.2589 11345.29 59663.90               351.11


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
LOBBY_FLR_1_DAYLREFPT1 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.07 10645.38 745.18
LOBBY_FLR_1_DAYLREFPT2 LOBBY_FLR_1 LOBBY_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.07 10645.38 745.18
CAFE_FLR_1_DAYLREFPT1 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1573.46 613.65
CAFE_FLR_1_DAYLREFPT2 CAFE_FLR_1 CAFE_FLR_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1573.46 613.65
DINING_FLR_6_DAYLREFPT1 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2763.12 552.62
DINING_FLR_6_DAYLREFPT2 DINING_FLR_6 DINING_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2763.12 552.62
BANQUET_FLR_6_DAYLREFPT1 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2763.12 552.62
BANQUET_FLR_6_DAYLREFPT2 BANQUET_FLR_6 BANQUET_FLR_6_DAYLCTRL SplitFlux Continuous/Off 0.20 2763.12 552.62


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 11096.45 AstronomicalClock -   83.75 83.75 174.46
Exterior Lighting Total 11096.45           174.46



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 276186.18 0.80        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 656741.91 3.11 656857.35 3.11 4.12 14.07


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 10185.92 15403.04 12394.54 3008.50 0.80 - 1778.73 18.04
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 9770.03 14769.88 11882.47 2887.41 0.80 - 1705.45 17.30
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 57974.75 88312.45 71440.27 16872.18 0.81 - 10230.25 103.76
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 58116.00 86242.57 68455.67 17786.90 0.79 - 9904.55 100.46
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 8947.99 13518.36 10870.30 2648.06 0.80 - 1560.62 15.83
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 8586.08 12967.34 10424.66 2542.69 0.80 - 1496.85 15.18
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 2649.82 4008.09 3225.88 782.21 0.80 - 462.89 4.69
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 2534.61 3832.70 3084.02 748.67 0.80 - 442.59 4.49
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 12478.01 18745.18 15010.22 3734.95 0.80 - 2160.23 21.91
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 436984.21 496894.73 343981.26 152913.46 0.69 - 58848.60 596.88
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 47946.25 51527.24 35531.42 15995.82 0.69 - 5813.13 58.96
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 7188.37 7225.14 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2763.92 2776.61 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1289.08 1295.35 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1741.76 1749.63 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1036.35 1040.86 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 11568.10 11627.49 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 8762.37 8804.67 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 24768.51 24891.61 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 4006.15 4314.91 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 4006.20 4314.97 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 23240.74 25031.80 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 23253.68 25045.73 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 4005.54 4314.25 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 4005.59 4314.31 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 9832.60 9877.74 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1242.95 1338.72 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1242.58 1338.32 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 6000.03 6462.31 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 10503.61 10556.24 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 10920.60 10975.35 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 7859.86 7900.10 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 6333.37 6361.87 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 91186.95 76523.86 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 9427.25 7911.32 -
SWHSYSLAUNDRY HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped   75921.46 3.40
SWHSYS1 HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped   54370.95 3.40
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 0.24 76.61 324.68 1.00 2.78 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.93 654.73 703.64 1.00 1.21 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.89 627.47 703.64 1.00 1.23 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 5.40 3802.48 703.64 1.00 0.97 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 5.03 3541.55 703.64 1.00 0.97 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.82 573.60 703.64 1.00 1.25 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.78 549.88 703.64 1.00 1.26 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.24 170.46 703.64 1.00 1.88 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 0.23 162.90 703.64 1.00 1.92 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.39 270.90 1.12 787.05 703.64 1.00 1.17 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.87 0.00 0.00 1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.39 125.00 1.89 612.92 324.68 1.00 1.48 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 19.84 44458.26 2240.64 1.00 1.11 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00
SWHSYSLAUNDRY HPWH FAN Fan:SystemModel 0.70 100.00 4.90 700.51 142.86 0.00 2.78 General    
SWHSYS1 HPWH FAN Fan:SystemModel 0.70 100.00 3.87 553.22 142.86 0.00 2.84 General    


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.023437 4781.66 204022.71 0.91 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.002416 720.45 298174.34 0.91 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.023437 3310.50 141251.80 0.91 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWHSYSLAUNDRY HPWH WaterHeater:HeatPump:PumpedCondenser 1.14 77190.64 0.80 48.89 1.72
SWHSYS1 HPWH WaterHeater:HeatPump:PumpedCondenser 2.84 62753.28 0.80 4.64 9.46



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 26051.10 26051.10 13.16 1.929 1.929 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:40:00 24.00 24.00 0.00943 27.18 0.00823 0.854 0.00
RETAIL_1_FLR_1 4098.69 4098.69 61.11 0.303 0.303 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 24.00 24.00 0.00907 30.93 0.00823 0.079 0.00
RETAIL_2_FLR_1 2882.79 2882.79 37.12 0.213 0.213 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 24.00 24.00 0.00946 29.76 0.00823 0.092 0.00
MECH_FLR_1 2357.47 2357.47 14.35 0.175 0.175 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 24.00 24.00 0.00873 29.16 0.00823 0.000 0.00
STORAGE_FLR_1 1254.69 1254.69 13.24 0.093 0.093 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 24.00 24.00 0.00884 31.12 0.00823 0.058 0.00
LAUNDRY_FLR_1 44664.93 44664.93 572.34 3.307 3.307 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 24.00 24.00 0.00854 31.30 0.00823 0.000 0.00
CAFE_FLR_1 18445.12 18445.12 97.66 1.367 1.367 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:10:00 24.00 23.99 0.01021 30.93 0.00823 0.676 0.00
LOBBY_FLR_1 60101.48 60101.48 45.94 4.451 4.451 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 24.00 23.99 0.01007 31.08 0.00823 1.894 0.00
ROOM_1_FLR_3 9327.35 9327.35 239.03 0.930 0.930 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 21.11 21.11 0.00857 30.53 0.00823 0.062 0.00
ROOM_2_FLR_3 8939.06 8939.06 229.10 0.892 0.892 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 21.11 21.11 0.00858 30.41 0.00823 0.062 0.00
ROOM_3_MULT19_FLR_3 54172.82 54172.82 2208.99 5.404 5.404 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 21.11 21.11 0.00849 31.08 0.00823 0.837 0.00
ROOM_4_MULT19_FLR_3 50451.55 50451.55 2056.68 5.033 5.033 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 21.11 21.11 0.00877 31.30 0.00823 0.837 0.00
ROOM_5_FLR_3 8171.61 8171.61 209.41 0.815 0.815 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 21.11 21.11 0.00858 27.16 0.00823 0.062 0.00
ROOM_6_FLR_3 7833.69 7833.69 200.77 0.781 0.781 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 21.11 21.11 0.00859 26.66 0.00823 0.062 0.00
CORRIDOR_FLR_3 14601.21 14601.21 37.50 1.081 1.081 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 24.00 24.00 0.00978 31.30 0.00823 0.475 0.00
ROOM_1_FLR_6 2428.32 2428.32 62.23 0.242 0.242 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 21.11 21.11 0.00857 30.53 0.00823 0.015 0.00
ROOM_2_FLR_6 2320.76 2320.76 59.48 0.232 0.232 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 21.11 21.11 0.00857 30.41 0.00823 0.015 0.00
ROOM_3_MULT9_FLR_6 11212.06 11212.06 457.07 1.119 1.119 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 21.11 21.11 0.00864 31.08 0.00823 0.099 0.00
BANQUET_FLR_6 28073.39 28073.39 84.65 2.081 2.081 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 24.00 23.98 0.01050 31.30 0.00823 1.188 0.00
DINING_FLR_6 29496.87 29496.87 88.94 2.186 2.186 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 24.00 23.99 0.01040 31.30 0.00823 1.188 0.00
KITCHEN_FLR_6 28847.40 28847.40 279.25 2.141 2.141 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 24.00 23.97 0.01017 30.50 0.00823 0.367 0.00
CORRIDOR_FLR_6 8371.97 8371.97 20.31 0.620 0.620 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 24.00 24.00 0.00909 31.30 0.00823 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 1342.22 1342.22 0.68 0.059 0.854 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00797 3.80 0.00506 0.854 0.00
RETAIL_1_FLR_1 1844.62 1844.62 27.50 0.081 0.081 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00767 3.80 0.00506 0.079 0.00
RETAIL_2_FLR_1 642.49 642.49 8.27 0.028 0.092 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00764 3.80 0.00506 0.092 0.00
MECH_FLR_1 1213.18 1213.18 7.39 0.053 0.053 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00756 3.80 0.00506 0.000 0.00
STORAGE_FLR_1 755.02 755.02 7.97 0.033 0.058 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00758 3.80 0.00506 0.058 0.00
LAUNDRY_FLR_1 1553.65 1553.65 19.91 0.068 0.068 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00753 3.80 0.00506 0.000 0.00
CAFE_FLR_1 4621.51 4621.51 24.47 0.202 0.676 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00770 3.80 0.00506 0.676 0.00
LOBBY_FLR_1 11283.85 11283.85 8.63 0.493 1.894 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00766 3.80 0.00506 1.894 0.00
ROOM_1_FLR_3 4006.18 4006.18 102.66 0.176 0.176 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 21.11 21.11 0.00765 3.80 0.00506 0.062 0.00
ROOM_2_FLR_3 4006.23 4006.23 102.68 0.176 0.176 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 21.11 21.11 0.00765 3.80 0.00506 0.062 0.00
ROOM_3_MULT19_FLR_3 23240.81 23240.81 947.68 1.021 1.021 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 21.11 21.11 0.00768 3.80 0.00506 0.837 0.00
ROOM_4_MULT19_FLR_3 23253.75 23253.75 947.95 1.022 1.022 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 21.11 21.11 0.00768 3.80 0.00506 0.837 0.00
ROOM_5_FLR_3 4005.56 4005.56 102.65 0.176 0.176 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 21.11 21.11 0.00765 3.80 0.00506 0.062 0.00
ROOM_6_FLR_3 4005.61 4005.61 102.66 0.176 0.176 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 21.11 21.11 0.00765 3.80 0.00506 0.062 0.00
CORRIDOR_FLR_3 6557.46 6557.46 16.84 0.286 0.475 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00773 3.80 0.00506 0.475 0.00
ROOM_1_FLR_6 1242.96 1242.96 31.85 0.055 0.055 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 21.11 21.11 0.00771 3.80 0.00506 0.015 0.00
ROOM_2_FLR_6 1242.59 1242.59 31.85 0.055 0.055 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 21.11 21.11 0.00771 3.80 0.00506 0.015 0.00
ROOM_3_MULT9_FLR_6 6000.06 6000.06 244.60 0.264 0.264 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 21.11 21.11 0.00772 3.80 0.00506 0.099 0.00
BANQUET_FLR_6 4198.26 4198.26 12.66 0.183 1.188 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 21.00 21.00 0.00778 3.80 0.00506 1.188 0.00
DINING_FLR_6 4295.60 4295.60 12.95 0.188 1.188 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 11:40:00 21.00 21.00 0.00779 3.80 0.00506 1.188 0.00
KITCHEN_FLR_6 1393.07 1393.07 13.49 0.061 0.367 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 21.00 21.00 0.00631 3.80 0.00506 0.367 0.00
CORRIDOR_FLR_6 4455.23 4455.23 10.81 0.195 0.195 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 11:40:00 21.00 21.00 0.00782 3.80 0.00506 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 19.84 19.84 7.19 7.19 19.8418 11.6690 19.8418 0.5881 0.3000
FLR_3_DOAS 14.74 2.05 3.12 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 7188.373 7188.373 1.128274 0.00006289 151.708 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 7188.37 7188.37 1.128274 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00796678 50.5477 1342.22 0.00 7228.60 7228.60
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 2763.919 2763.919 0.177529 0.00002418 64.407 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2763.92 2763.92 0.177529 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00766676 48.6682 1844.62 0.00 2778.68 2778.68
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1289.084 1289.084 0.124867 0.00001128 28.346 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1289.08 1289.08 0.124867 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00763516 48.4695 642.49 0.00 1296.12 1296.12
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 1741.755 1741.755 0.102091 0.00001524 41.297 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1741.76 1741.76 0.102091 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00755716 47.9803 1213.18 0.00 1751.01 1751.01
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 1036.355 1036.355 0.054335 0.00000907 25.165 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1036.35 1036.35 0.054335 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00758491 48.1544 755.02 0.00 1041.75 1041.75
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 11568.102 11568.102 1.934398 0.00010120 243.176 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 11568.10 11568.10 1.934398 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00753250 47.8262 1553.65 0.00 11632.93 11632.93
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 8762.369 8762.369 0.799593 0.00007666 193.990 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 8762.37 8762.37 0.799593 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00770200 48.8890 4621.51 0.00 8810.04 8810.04
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 24768.508 24768.508 2.603993 0.00021669 540.010 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 24768.51 24768.51 2.603993 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00765718 48.6076 11283.85 0.00 24905.74 24905.74
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 10185.915 -999.000 0.930494 0.00036381 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 unknown 8/21 16:20:00 10185.92 10010.67 0.930494 21.69 15.43 0.00857297 12.80 11.93 0.00850000 30.53 0.00823226 18.20 0.0000 21.11 0.00857297 53.9734 9327.35 0.00 10369.53 10010.05
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 4006.152 4006.152 0.175993 0.00003505 114.475 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 4006.15 4006.15 0.175993 21.11 14.39 0.00764834 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00764834 48.2230 4006.18 0.00 4318.75 4318.75
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 9770.029 -999.000 0.891760 0.00034896 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown 8/21 16:30:00 9770.03 9595.06 0.891760 21.69 15.44 0.00857601 12.80 11.93 0.00850000 30.41 0.00823207 18.16 0.0000 21.11 0.00857601 53.9923 8939.06 0.00 9946.07 9594.59
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 4006.204 4006.204 0.175995 0.00003505 114.476 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 4006.20 4006.20 0.175995 21.11 14.39 0.00764836 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00764836 48.2232 4006.23 0.00 4318.80 4318.80
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 57974.752 -999.000 5.404037 0.00207069 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown 8/21 13:30:00 57974.75 57974.75 5.404037 21.69 15.37 0.00849444 12.80 11.93 0.00849444 31.08 0.00823314 18.38 0.0000 21.11 0.00849444 53.4845 54172.82 0.00 59020.58 57994.37
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 23240.741 23240.741 1.020994 0.00020332 664.090 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 23240.74 23240.74 1.020994 21.11 14.41 0.00767530 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00767530 48.3903 23240.81 0.00 25054.28 25054.28
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 58115.999 -999.000 5.033217 0.00207573 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 unknown 8/21 15:00:00 58116.00 54545.24 5.033217 21.69 15.61 0.00877287 12.80 11.93 0.00850000 31.30 0.00823349 18.45 0.0000 21.11 0.00877287 55.2154 50451.55 0.00 59136.04 54584.98
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 23253.680 23253.680 1.021562 0.00020343 664.459 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 23253.68 23253.68 1.021562 21.11 14.41 0.00767538 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00767538 48.3908 23253.75 0.00 25068.23 25068.23
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 8947.987 -999.000 0.815198 0.00031960 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 unknown 8/21 09:30:00 8947.99 8773.59 0.815198 21.69 15.44 0.00858286 12.80 11.93 0.00850000 27.16 0.00822694 17.07 0.0000 21.11 0.00858286 54.0348 8171.61 0.00 9109.07 8773.40
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 4005.539 4005.539 0.175966 0.00003504 114.457 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 4005.54 4005.54 0.175966 21.11 14.39 0.00764829 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00764829 48.2227 4005.56 0.00 4318.09 4318.09
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 8586.084 -999.000 0.781488 0.00030667 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 unknown 8/21 09:10:00 8586.08 8411.88 0.781488 21.69 15.45 0.00858632 12.80 11.93 0.00850000 26.66 0.00822614 16.89 0.0000 21.11 0.00858632 54.0563 7833.69 0.00 8740.58 8411.82
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 4005.590 4005.590 0.175968 0.00003504 114.459 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 4005.59 4005.59 0.175968 21.11 14.39 0.00764832 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00764832 48.2229 4005.61 0.00 4318.14 4318.14
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 9832.596 9832.596 0.632362 0.00008602 229.075 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 9832.60 9832.60 0.632362 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00773040 49.0665 6557.46 0.00 9885.12 9885.12
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 2649.819 -999.000 0.242249 0.00009464 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 unknown 8/21 16:20:00 2649.82 2605.94 0.242249 21.69 15.43 0.00857018 12.80 11.93 0.00850000 30.53 0.00823226 18.20 0.0000 21.11 0.00857018 53.9561 2428.32 0.00 2697.60 2605.75
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 1242.948 1242.948 0.054604 0.00001087 35.516 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 1242.95 1242.95 0.054604 21.11 14.45 0.00770985 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00770985 48.6061 1242.96 0.00 1339.93 1339.93
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 2534.614 -999.000 0.231518 0.00009053 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown 8/21 16:30:00 2534.61 2490.81 0.231518 21.69 15.44 0.00857331 12.80 11.93 0.00850000 30.41 0.00823207 18.16 0.0000 21.11 0.00857331 53.9755 2320.76 0.00 2580.30 2490.66
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 1242.582 1242.582 0.054588 0.00001087 35.505 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 1242.58 1242.58 0.054588 21.11 14.44 0.00770979 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00770979 48.6058 1242.59 0.00 1339.54 1339.54
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 12478.012 -999.000 1.118544 0.00044568 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown 8/21 13:30:00 12478.01 12065.19 1.118544 21.69 15.50 0.00864262 12.80 11.93 0.00850000 31.08 0.00823314 18.38 0.0000 21.11 0.00864262 54.4066 11212.06 0.00 12700.83 12067.83
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 6000.032 6000.032 0.263587 0.00005249 171.442 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 6000.03 6000.03 0.263587 21.11 14.46 0.00772196 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.11 0.00772196 48.6813 6000.06 0.00 6468.22 6468.22
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10503.615 10503.615 1.217342 0.00009189 226.887 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 10503.61 10503.61 1.217342 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00778318 49.3976 4198.26 0.00 10561.96 10561.96
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 10920.600 10920.600 1.279047 0.00009554 235.672 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 11:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 11:40:00 10920.60 10920.60 1.279047 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00778773 49.4262 4295.60 0.00 10981.28 10981.28
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 7859.860 7859.860 1.252622 0.00006876 165.717 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 7859.86 7859.86 1.252622 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00630789 40.1347 1393.07 0.00 7903.86 7903.86
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 6333.372 6333.372 0.362577 0.00005541 150.884 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 11:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 11:40:00 6333.37 6333.37 0.362577 16.70 13.02 0.00800000 40.00 20.96 0.00800000 3.80 0.00505843 3.80 0.0000 21.00 0.00781865 49.6198 4455.23 0.00 6367.00 6367.00
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 436984.211 -999.000 19.841781 0.01560806 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 436984.21 414605.60 19.841781 28.29 17.97 0.00886614 10.94 10.94 0.00850000 31.30 0.00823349 18.45 58.7722 23.99 0.00977091 51.5405 267773.32 0.00 442861.68 399475.34
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 91186.954 91186.954 5.952534 0.00079774 1634.376 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 11:50:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 11:50:00 91186.95 91186.95 5.952534 3.80 3.80 0.00505843 16.70 13.02 0.00800000 3.80 0.00505843 3.80 195.9075 21.02 0.00770072 48.8203 43690.32 0.00 92629.45 92629.45
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 47946.248 -999.000 2.051317 0.00171253 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 47946.25 47946.25 2.051317 31.30 18.45 0.00823349 11.91 11.29 0.00823349 31.30 0.00823349 18.45 99.9965 21.11 0.00862984 54.3264 147743.57 0.00 48572.77 47970.12
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 9427.247 9427.247 0.615395 0.00008247 168.968 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 9427.25 9427.25 0.615395 3.80 3.80 0.00505843 16.70 13.02 0.00800000 3.80 0.00505843 3.80 333.3216 21.11 0.00767558 48.3920 71003.74 0.00 9576.38 9576.38
SWHSYSLAUNDRY HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped unknown unknown 64989.913 47832.576 4.903586 -999.0 -999.000 unknown unknown unknown unknown 75921.46 -999.00 -999.0 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.00 -999.0 -999.00 -999.0000 -999.00 -999.0 -999.0000 -999.00 0.00 -999.00 -999.00
SWHSYS1 HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped unknown unknown 51353.666 37796.298 3.872570 -999.0 -999.000 unknown unknown unknown unknown 54370.95 -999.00 -999.0 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.00 -999.0 -999.00 -999.0000 -999.00 -999.0 -999.0000 -999.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 7188.373 7188.373 1.128274 0.00006289 151.708 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 2.5514 2.602727 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 7188.37 7188.37 1.0000 1.33337069 1.128274 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.06288061 60.00 32.22 27.78 0.000 7188.37 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00796678 21.00 0.00796678 50.5477 1342.22 0.00 7228.60 7228.60 1.33337069 16.60 13.15 0.00800000 36934.7 21.92 15.19 0.00800000 42356.0
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 2763.919 2763.919 0.177529 0.00002418 64.407 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 0.9810 1.000745 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2763.92 2763.92 1.0000 0.20980023 0.177529 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.02417751 60.00 32.22 27.78 0.000 2763.92 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00766676 21.00 0.00766676 48.6682 1844.62 0.00 2778.68 2778.68 0.20980023 16.60 13.15 0.00800000 36934.7 29.59 17.90 0.00800000 50179.1
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1289.084 1289.084 0.124867 0.00001128 28.346 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 0.4575 0.466745 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1289.08 1289.08 1.0000 0.14756495 0.124867 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.01127632 60.00 32.22 27.78 0.000 1289.08 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00763516 21.00 0.00763516 48.4695 642.49 0.00 1296.12 1296.12 0.14756495 16.60 13.15 0.00800000 36934.7 25.21 16.39 0.00800000 45718.1
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 1741.755 1741.755 0.102091 0.00001524 41.297 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 0.6182 0.630645 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1741.76 1741.76 1.0000 0.12064849 0.102091 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.01523608 60.00 32.22 27.78 0.000 1741.76 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00755716 21.00 0.00755716 47.9803 1213.18 0.00 1751.01 1751.01 0.12064849 16.60 13.15 0.00800000 36934.7 30.83 18.31 0.00800000 51448.1
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 1036.355 1036.355 0.054335 0.00000907 25.165 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 0.3678 0.375238 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1036.35 1036.35 1.0000 0.06421217 0.054335 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.00906556 60.00 32.22 27.78 0.000 1036.35 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00758491 21.00 0.00758491 48.1544 755.02 0.00 1041.75 1041.75 0.06421217 16.60 13.15 0.00800000 36934.7 32.51 18.86 0.00800000 53158.3
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 11568.102 11568.102 1.934398 0.00010120 243.176 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 4.1059 4.188516 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 11568.10 11568.10 1.0000 2.28603057 1.934398 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.10119248 60.00 32.22 27.78 0.000 11568.10 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00753250 21.00 0.00753250 47.8262 1553.65 0.00 11632.93 11632.93 2.28603057 16.60 13.15 0.00800000 36934.7 21.59 15.07 0.00800000 42023.4
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 8762.369 8762.369 0.799593 0.00007666 193.990 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 3.1100 3.172631 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 8762.37 8762.37 1.0000 0.94494158 0.799593 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.07664920 60.00 32.22 27.78 0.000 8762.37 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00770200 21.00 0.00770200 48.8890 4621.51 0.00 8810.04 8810.04 0.94494158 16.60 13.15 0.00800000 36934.7 25.74 16.58 0.00800000 46258.1
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 24768.508 24768.508 2.603993 0.00021669 540.010 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 8.7911 8.968048 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 24768.51 24768.51 1.0000 3.07734355 2.603993 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.21666361 60.00 32.22 27.78 0.000 24768.51 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00765718 21.00 0.00765718 48.6076 11283.85 0.00 24905.74 24905.74 3.07734355 16.60 13.15 0.00800000 36934.7 24.54 16.15 0.00800000 45028.0
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 10185.915 -999.000 0.930494 0.00036381 -999.000 -999.0000 1.00000 1.00000 1020.7767 1004.8586 1.1818 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.930494 1.09963850   4197.9300 999.8980 23.43449811 13.37 6.70 6.67 656170.47 1.5523 1.552299 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 unknown unknown unknown 8/21 16:20:00 Sensible 10185.92 10010.67 1.0000 1.09963850 0.930494 21.69 15.43 0.00857297 43585.2 12.80 11.93 0.00850000 34322.2 0.36377338 6.70 13.37 6.67 0.000 10185.92 30.53 0.00823226 18.20 0.00000000 0.0000 21.11 0.00857297 21.11 0.00857297 53.9734 9327.35 0.00 10369.53 10010.05 1.09963850 21.69 15.62 0.00857297 43585.2 12.78 12.03 0.00844349 34155.2
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 4006.152 4006.152 0.175993 0.00003505 114.475 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.930494 1.09963850   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 1.4219 1.450526 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 Sensible 4006.15 4006.15 1.0000 0.20798489 0.175993 21.11 14.39 0.00764834 40640.9 40.00 20.96 0.00800000 60796.0 0.03504399 60.00 32.22 27.78 0.000 4006.15 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00764834 21.11 0.00764834 48.2230 4006.18 0.00 4318.75 4318.75 0.20798489 16.60 12.81 0.00764834 36044.4 36.98 20.01 0.00764834 56809.1
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 9770.029 -999.000 0.891760 0.00034896 -999.000 -999.0000 1.00000 1.00000 1020.7824 1004.8586 1.1818 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.891760 1.05386279   4197.9300 999.8980 23.43449811 13.37 6.70 6.67 656170.47 1.4889 1.488919 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown unknown unknown 8/21 16:30:00 Sensible 9770.03 9595.06 1.0000 1.05386279 0.891760 21.69 15.44 0.00857601 43592.9 12.80 11.93 0.00850000 34322.2 0.34892070 6.70 13.37 6.67 0.000 9770.03 30.41 0.00823207 18.16 0.00000000 0.0000 21.11 0.00857601 21.11 0.00857601 53.9923 8939.06 0.00 9946.07 9594.59 1.05386279 21.69 15.63 0.00857601 43592.9 12.78 12.03 0.00844391 34155.2
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 4006.204 4006.204 0.175995 0.00003505 114.476 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.891760 1.05386279   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 1.4219 1.450545 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 Sensible 4006.20 4006.20 1.0000 0.20798754 0.175995 21.11 14.39 0.00764836 40641.0 40.00 20.96 0.00800000 60796.0 0.03504444 60.00 32.22 27.78 0.000 4006.20 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00764836 21.11 0.00764836 48.2232 4006.23 0.00 4318.80 4318.80 0.20798754 16.60 12.81 0.00764836 36044.5 36.98 20.01 0.00764836 56809.2
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 57974.752 -999.000 5.404037 0.00207069 -999.000 -999.0000 1.00000 1.00000 1020.6307 1004.8586 1.1818 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.404037 6.38637523   4197.9300 999.8980 23.43449811 13.37 6.70 6.67 656170.47 8.8353 8.835154 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown unknown unknown 8/21 13:30:00 Sensible 57974.75 57974.75 1.0000 6.38637523 5.404037 21.69 15.37 0.00849444 43386.0 12.80 11.93 0.00849444 34308.2 2.07047390 6.70 13.37 6.67 0.000 57974.75 31.08 0.00823314 18.38 0.00000000 0.0000 21.11 0.00849444 21.11 0.00849444 53.4845 54172.82 0.00 59020.58 57994.37 6.38637523 21.69 15.55 0.00849444 43386.0 12.80 12.03 0.00843080 34144.4
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 23240.741 23240.741 1.020994 0.00020332 664.090 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.404037 6.38637523   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 8.2489 8.414882 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 Sensible 23240.74 23240.74 1.0000 1.20658877 1.020994 21.11 14.41 0.00767530 40709.7 40.00 20.96 0.00800000 60796.0 0.20329940 60.00 32.22 27.78 0.000 23240.74 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00767530 21.11 0.00767530 48.3903 23240.81 0.00 25054.28 25054.28 1.20658877 16.60 12.83 0.00767530 36112.7 36.98 20.03 0.00767530 56877.2
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 58115.999 -999.000 5.033217 0.00207573 -999.000 -999.0000 1.00000 1.00000 1021.1483 1004.8586 1.1818 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.033217 5.94814858   4197.9300 999.8980 23.43449811 13.37 6.70 6.67 656170.47 8.8568 8.856679 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 unknown unknown unknown 8/21 15:00:00 Sensible 58116.00 54545.24 1.0000 5.94814858 5.033217 21.69 15.61 0.00877287 44092.6 12.80 11.93 0.00850000 34322.2 2.07551833 6.70 13.37 6.67 0.000 58116.00 31.30 0.00823349 18.45 0.00000000 0.0000 21.11 0.00877287 21.11 0.00877287 55.2154 50451.55 0.00 59136.04 54584.98 5.94814858 21.69 15.80 0.00877287 44092.6 12.71 12.03 0.00846980 34150.7
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 23253.680 23253.680 1.021562 0.00020343 664.459 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.033217 5.94814858   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 8.2535 8.419567 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 Sensible 23253.68 23253.68 1.0000 1.20726055 1.021562 21.11 14.41 0.00767538 40709.9 40.00 20.96 0.00800000 60796.0 0.20341259 60.00 32.22 27.78 0.000 23253.68 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00767538 21.11 0.00767538 48.3908 23253.75 0.00 25068.23 25068.23 1.20726055 16.60 12.83 0.00767538 36112.9 36.98 20.03 0.00767538 56877.4
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 8947.987 -999.000 0.815198 0.00031960 -999.000 -999.0000 1.00000 1.00000 1020.7951 1004.8586 1.1818 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.815198 0.96338418   4197.9300 999.8980 23.43449811 13.37 6.70 6.67 656170.47 1.3637 1.363643 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 unknown unknown unknown 8/21 09:30:00 Sensible 8947.99 8773.59 1.0000 0.96338418 0.815198 21.69 15.44 0.00858286 43610.3 12.80 11.93 0.00850000 34322.2 0.31956278 6.70 13.37 6.67 0.000 8947.99 27.16 0.00822694 17.07 0.00000000 0.0000 21.11 0.00858286 21.11 0.00858286 54.0348 8171.61 0.00 9109.07 8773.40 0.96338418 21.69 15.63 0.00858286 43610.3 12.77 12.03 0.00844485 34155.0
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 4005.539 4005.539 0.175966 0.00003504 114.457 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.815198 0.96338418   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 1.4217 1.450304 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 Sensible 4005.54 4005.54 1.0000 0.20795305 0.175966 21.11 14.39 0.00764829 40640.8 40.00 20.96 0.00800000 60796.0 0.03503863 60.00 32.22 27.78 0.000 4005.54 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00764829 21.11 0.00764829 48.2227 4005.56 0.00 4318.09 4318.09 0.20795305 16.60 12.81 0.00764829 36044.3 36.98 20.01 0.00764829 56809.0
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 8586.084 -999.000 0.781488 0.00030667 -999.000 -999.0000 1.00000 1.00000 1020.8015 1004.8586 1.1818 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.781488 0.92354538   4197.9300 999.8980 23.43449811 13.37 6.70 6.67 656170.47 1.3085 1.308490 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 unknown unknown unknown 8/21 09:10:00 Sensible 8586.08 8411.88 1.0000 0.92354538 0.781488 21.69 15.45 0.00858632 43619.1 12.80 11.93 0.00850000 34322.2 0.30663803 6.70 13.37 6.67 0.000 8586.08 26.66 0.00822614 16.89 0.00000000 0.0000 21.11 0.00858632 21.11 0.00858632 54.0563 7833.69 0.00 8740.58 8411.82 0.92354538 21.69 15.63 0.00858632 43619.1 12.77 12.03 0.00844533 34154.9
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 4005.590 4005.590 0.175968 0.00003504 114.459 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.781488 0.92354538   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 1.4217 1.450323 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 Sensible 4005.59 4005.59 1.0000 0.20795571 0.175968 21.11 14.39 0.00764832 40640.9 40.00 20.96 0.00800000 60796.0 0.03503908 60.00 32.22 27.78 0.000 4005.59 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00764832 21.11 0.00764832 48.2229 4005.61 0.00 4318.14 4318.14 0.20795571 16.60 12.81 0.00764832 36044.3 36.98 20.01 0.00764832 56809.1
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 9832.596 9832.596 0.632362 0.00008602 229.075 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 3.4899 3.560133 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 9832.60 9832.60 1.0000 0.74731202 0.632362 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.08601106 60.00 32.22 27.78 0.000 9832.60 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00773040 21.00 0.00773040 49.0665 6557.46 0.00 9885.12 9885.12 0.74731202 16.60 13.15 0.00800000 36934.7 29.57 17.89 0.00800000 50162.3
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 2649.819 -999.000 0.242249 0.00009464 -999.000 -999.0000 1.00000 1.00000 1020.7715 1004.8586 1.1818 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.242249 0.28628489   4197.9300 999.8980 23.43449811 13.37 6.70 6.67 656170.47 0.4038 0.403823 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:20:00 unknown unknown unknown 8/21 16:20:00 Sensible 2649.82 2605.94 1.0000 0.28628489 0.242249 21.69 15.43 0.00857018 43578.1 12.80 11.93 0.00850000 34322.2 0.09463396 6.70 13.37 6.67 0.000 2649.82 30.53 0.00823226 18.20 0.00000000 0.0000 21.11 0.00857018 21.11 0.00857018 53.9561 2428.32 0.00 2697.60 2605.75 0.28628489 21.69 15.62 0.00857018 43578.1 12.78 12.03 0.00844310 34155.3
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 1242.948 1242.948 0.054604 0.00001087 35.516 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.242249 0.28628489   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 0.4412 0.450040 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 Sensible 1242.95 1242.95 1.0000 0.06452934 0.054604 21.11 14.45 0.00770985 40797.2 40.00 20.96 0.00800000 60796.0 0.01087274 60.00 32.22 27.78 0.000 1242.95 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00770985 21.11 0.00770985 48.6061 1242.96 0.00 1339.93 1339.93 0.06452934 16.60 12.87 0.00770985 36200.1 36.97 20.05 0.00770985 56964.8
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 2534.614 -999.000 0.231518 0.00009053 -999.000 -999.0000 1.00000 1.00000 1020.7774 1004.8586 1.1818 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.231518 0.27360346   4197.9300 999.8980 23.43449811 13.37 6.70 6.67 656170.47 0.3863 0.386267 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown unknown unknown 8/21 16:30:00 Sensible 2534.61 2490.81 1.0000 0.27360346 0.231518 21.69 15.44 0.00857331 43586.0 12.80 11.93 0.00850000 34322.2 0.09051962 6.70 13.37 6.67 0.000 2534.61 30.41 0.00823207 18.16 0.00000000 0.0000 21.11 0.00857331 21.11 0.00857331 53.9755 2320.76 0.00 2580.30 2490.66 0.27360346 21.69 15.62 0.00857331 43586.0 12.78 12.03 0.00844354 34155.2
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 1242.582 1242.582 0.054588 0.00001087 35.505 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.231518 0.27360346   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 0.4410 0.449907 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 Sensible 1242.58 1242.58 1.0000 0.06451036 0.054588 21.11 14.44 0.00770979 40797.1 40.00 20.96 0.00800000 60796.0 0.01086954 60.00 32.22 27.78 0.000 1242.58 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00770979 21.11 0.00770979 48.6058 1242.59 0.00 1339.54 1339.54 0.06451036 16.60 12.87 0.00770979 36200.0 36.97 20.05 0.00770979 56964.7
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 12478.012 -999.000 1.118544 0.00044568 -999.000 -999.0000 1.00000 1.00000 1020.9062 1004.8586 1.1818 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.118544 1.32187116   4197.9300 999.8980 23.43449811 13.37 6.70 6.67 656170.47 1.9016 1.901606 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown unknown unknown 8/21 13:30:00 Sensible 12478.01 12065.19 1.0000 1.32187116 1.118544 21.69 15.50 0.00864262 43761.9 12.80 11.93 0.00850000 34322.2 0.44563188 6.70 13.37 6.67 0.000 12478.01 31.08 0.00823314 18.38 0.00000000 0.0000 21.11 0.00864262 21.11 0.00864262 54.4066 11212.06 0.00 12700.83 12067.83 1.32187116 21.69 15.68 0.00864262 43761.9 12.75 12.03 0.00845295 34153.6
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 6000.032 6000.032 0.263587 0.00005249 171.442 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.118544 1.32187116   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 2.1296 2.172459 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 Sensible 6000.03 6000.03 1.0000 0.31150113 0.263587 21.11 14.46 0.00772196 40828.0 40.00 20.96 0.00800000 60796.0 0.05248555 60.00 32.22 27.78 0.000 6000.03 3.80 0.00505843 3.80 0.00000000 0.0000 21.11 0.00772196 21.11 0.00772196 48.6813 6000.06 0.00 6468.22 6468.22 0.31150113 16.60 12.88 0.00772196 36230.8 36.97 20.06 0.00772196 56995.5
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 10503.615 10503.615 1.217342 0.00009189 226.887 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 3.7281 3.803092 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 Sensible 10503.61 10503.61 1.0000 1.43862890 1.217342 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.09188083 60.00 32.22 27.78 0.000 10503.61 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00778318 21.00 0.00778318 49.3976 4198.26 0.00 10561.96 10561.96 1.43862890 16.60 13.15 0.00800000 36934.7 23.80 15.88 0.00800000 44276.4
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 10920.600 10920.600 1.279047 0.00009554 235.672 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 3.8761 3.954072 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 11:40:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 11:40:00 Sensible 10920.60 10920.60 1.0000 1.51155019 1.279047 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.09552842 60.00 32.22 27.78 0.000 10920.60 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00778773 21.00 0.00778773 49.4262 4295.60 0.00 10981.28 10981.28 1.51155019 16.60 13.15 0.00800000 36934.7 23.72 15.86 0.00800000 44199.6
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 7859.860 7859.860 1.252622 0.00006876 165.717 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 2.7897 2.845856 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 Sensible 7859.86 7859.86 1.0000 1.48032145 1.252622 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.06875447 60.00 32.22 27.78 0.000 7859.86 3.80 0.00505843 3.80 0.00000000 0.0000 20.26 0.00630789 21.00 0.00630789 40.1347 1393.07 0.00 7903.86 7903.86 1.48032145 16.60 13.15 0.00800000 36934.7 21.84 15.16 0.00800000 42274.0
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 6333.372 6333.372 0.362577 0.00005541 150.884 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 2.2479 2.293153 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 11:40:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 11:40:00 Sensible 6333.37 6333.37 1.0000 0.42848565 0.362577 16.70 13.02 0.00800000 37036.7 40.00 20.96 0.00800000 60796.0 0.05540145 60.00 32.22 27.78 0.000 6333.37 3.80 0.00505843 3.80 0.00000000 0.0000 21.00 0.00781865 21.00 0.00781865 49.6198 4455.23 0.00 6367.00 6367.00 0.42848565 16.60 13.15 0.00800000 36934.7 31.17 18.43 0.00800000 51794.0
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 436984.211 -999.000 19.841781 0.01560806 -999.000 -999.0000 1.00000 1.00000 1021.3217 1004.8586 1.1818 VAV WITH REHEAT FAN Fan:VariableVolume 19.841781 23.44859336   4197.9300 999.8980 23.43449811 13.37 6.70 6.67 656170.47 66.5961 66.596141 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 Sensible 436984.21 414605.60 1.0000 23.44859336 19.841781 28.29 17.97 0.00886614 51063.3 10.94 10.94 0.00850000 32427.5 15.60647134 6.70 13.37 6.67 44458.260 392525.95 31.30 0.00823349 18.45 11.66146000 58.7722 23.99 0.00976847 23.99 0.00977091 51.5405 267773.32 0.00 442861.68 399475.34 23.44859336 28.29 18.17 0.00886614 51063.3 11.61 11.23 0.00813264 32176.8
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 91186.954 91186.954 5.952534 0.00079774 1634.376 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 VAV WITH REHEAT FAN Fan:VariableVolume 19.841781 23.44859336   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 32.3651 33.016480 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 11:50:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 11:50:00 Sensible 91186.95 91186.95 1.0000 7.03457801 5.952534 3.80 3.80 0.00505843 16505.0 16.70 13.02 0.00800000 37036.7 0.79766188 60.00 32.22 27.78 0.000 91186.95 3.80 0.00505843 3.80 11.66146000 195.9075 20.96 0.00767907 21.02 0.00770072 48.8203 43690.32 0.00 92629.45 92629.45 7.03457801 2.80 2.80 0.00505843 15490.7 15.78 9.78 0.00505843 28658.4
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 47946.248 -999.000 2.051317 0.00171253 -999.000 -999.0000 1.00000 1.00000 1020.1456 1004.8586 1.1818 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.42411771   4197.9300 999.8980 23.43449811 13.37 6.70 6.67 656170.47 7.3070 7.306980 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 Sensible 47946.25 47946.25 1.0000 2.42420295 2.051317 31.30 18.45 0.00823349 52522.0 11.91 11.29 0.00823349 32743.9 1.71235419 6.70 13.37 6.67 2195.006 45751.24 31.30 0.00823349 18.45 2.05124512 99.9965 21.11 0.00862259 21.11 0.00862984 54.3264 147743.57 0.00 48572.77 47970.12 2.42420295 31.30 18.65 0.00823349 52522.0 11.90 11.35 0.00813496 32485.4
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 9427.247 9427.247 0.615395 0.00008247 168.968 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.42411771   4197.9300 999.8980 2.41595069 54.44 82.22 27.78 281744.53 3.3460 3.413367 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 12:10:00 Sensible 9427.25 9427.25 1.0000 0.72726088 0.615395 3.80 3.80 0.00505843 16505.0 16.70 13.02 0.00800000 37036.7 0.08246526 60.00 32.22 27.78 0.000 9427.25 3.80 0.00505843 3.80 2.05124512 333.3216 21.11 0.00767439 21.11 0.00767558 48.3920 71003.74 0.00 9576.38 9576.38 0.72726088 2.80 2.80 0.00505843 15490.7 15.78 9.78 0.00505843 28658.4
SWHSYSLAUNDRY HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped unknown unknown unknown N/A N/A N/A N/A No No unknown No 64989.913 47832.576 4.903586 -999.0 -999.000 -999.0000 1.00000 1.00000 1004.8586 1004.8586 1.1818 SWHSYSLAUNDRY HPWH FAN Fan:SystemModel 4.903586 5.79495390   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 unknown unknown unknown unknown unknown unknown Sensible 75921.46 -999.00 1.0000 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0 -999.0 -999.00 -999.00 -999.00 0.000 75921.46 -999.00 -999.0 -999.00 -999.0 -999.0000 -999.00 -999.0 -999.00 -999.0 -999.0000 -999.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
SWHSYS1 HPWH DXCOIL Coil:WaterHeating:AirToWaterHeatPump:Pumped unknown unknown unknown N/A N/A N/A N/A No No unknown No 51353.666 37796.298 3.872570 -999.0 -999.000 -999.0000 1.00000 1.00000 1004.8586 1004.8586 1.1818 SWHSYS1 HPWH FAN Fan:SystemModel 3.872570 4.57652007   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 unknown unknown unknown unknown unknown unknown Sensible 54370.95 -999.00 1.0000 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0 -999.0 -999.00 -999.00 -999.00 0.000 54370.95 -999.00 -999.0 -999.00 -999.0 -999.0000 -999.00 -999.0 -999.00 -999.0 -999.0000 -999.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 19.84 -      
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.002360 0.000305 0.000000 0.000000 Sum   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.003540 0.000610 0.000000 0.000000 Sum   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.003540 0.000610 0.000000 0.000000 Sum   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.003540 0.000914 0.000000 0.000000 Sum   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.003540 0.000305 0.000000 0.000000 Sum   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Sum   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 0.00 8731.83 0.00
RETAIL_1_FLR_1 668.17 7573.17 23.17
RETAIL_2_FLR_1 718.00 7502.33 229.00
MECH_FLR_1 0.00 8742.83 0.00
STORAGE_FLR_1 3.00 8760.00 3.00
LAUNDRY_FLR_1 7076.17 3345.33 2665.67
CAFE_FLR_1 2583.67 5862.83 991.83
LOBBY_FLR_1 1871.67 6270.50 866.67
ROOM_1_FLR_3 65.83 8237.83 64.67
ROOM_2_FLR_3 908.50 7749.33 350.83
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 139.17 8731.83 136.00
ROOM_5_FLR_3 67.50 8505.67 67.50
ROOM_6_FLR_3 562.83 8188.33 336.83
CORRIDOR_FLR_3 342.50 8756.67 342.50
ROOM_1_FLR_6 249.83 8091.17 238.67
ROOM_2_FLR_6 1313.67 7656.67 748.00
ROOM_3_MULT9_FLR_6 67.33 8076.67 25.83
BANQUET_FLR_6 5499.50 2381.83 929.00
DINING_FLR_6 6630.00 1312.33 800.50
KITCHEN_FLR_6 8326.00 6444.83 6335.33
CORRIDOR_FLR_6 20.67 8618.00 15.50
Facility 8630.50 8760.00 7219.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 0.00 0.00 0.00
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 0.00 7.67 0.00 7.67
ROOM_2_FLR_3 0.00 14.83 0.00 14.83
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 44.50 0.00 44.50
ROOM_5_FLR_3 0.00 5.33 0.00 5.33
ROOM_6_FLR_3 0.00 36.50 0.00 36.50
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 14.00 0.00 14.00
ROOM_2_FLR_6 0.00 29.33 0.00 29.33
ROOM_3_MULT9_FLR_6 0.00 22.50 0.00 22.50
BANQUET_FLR_6 0.00 0.00 0.00 0.00
DINING_FLR_6 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 0.00 105.50 0.00 105.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.78 106.50 4826.41 0.858 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 2.482 0.135 0.000 0.000
RETAIL_2_FLR_1 7.27 12.54 307.76 1.492 0.045 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.574 0.050 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.530 0.050 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 25.235 0.145 0.000 0.000
CAFE_FLR_1 82.55 142.30 748.35 3.971 0.107 0.000 0.000
LOBBY_FLR_1 245.05 422.44 5183.56 1.861 0.044 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.356 0.176 0.000 0.093
ROOM_2_FLR_3 0.95 1.50 118.93 0.356 0.176 0.000 0.095
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.404 0.078 0.000 0.156
ROOM_5_FLR_3 0.95 1.50 118.94 0.356 0.176 0.000 0.093
ROOM_6_FLR_3 0.95 1.50 118.93 0.356 0.176 0.000 0.101
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.488 0.021 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.356 0.176 0.000 0.104
ROOM_2_FLR_6 0.95 1.50 118.93 0.356 0.176 0.000 0.098
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.404 0.143 0.000 0.166
BANQUET_FLR_6 144.96 249.90 1010.89 4.940 0.051 0.000 0.000
DINING_FLR_6 144.96 249.90 1010.89 5.320 0.051 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 21.617 0.146 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 1.057 0.036 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.78 106.50 4826.41 0.838 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 2.385 0.002 0.000 0.000
RETAIL_2_FLR_1 7.27 12.54 307.76 1.450 0.001 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 0.560 0.001 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 0.516 0.001 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 22.384 0.002 0.000 0.000
CAFE_FLR_1 82.55 142.30 748.35 3.824 0.002 0.000 0.000
LOBBY_FLR_1 245.05 422.44 5183.56 1.800 0.001 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.000 0.003 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.000 0.003 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.000 0.001 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.000 0.003 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.000 0.003 0.000 0.000
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.475 0.000 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.000 0.003 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.000 0.003 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.000 0.002 0.000 0.000
BANQUET_FLR_6 144.96 249.90 1010.89 4.318 0.001 0.000 0.000
DINING_FLR_6 144.96 249.90 1010.89 4.542 0.001 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 14.290 0.002 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 1.030 0.001 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.78 106.50 4826.41 1978.83 0.0000 0.603
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.041
RETAIL_2_FLR_1 VAV WITH REHEAT 7.27 12.54 307.76 77.67 0.0000 0.047
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.55 142.30 748.35 188.86 0.0000 0.173
LOBBY_FLR_1 VAV WITH REHEAT 245.05 422.44 5183.56 1308.19 0.0000 0.399
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.16 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 144.96 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 144.96 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.90 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.87 22.18 1256.16 412.12 0.0000 0.126
Total Facility   873.11 1604.23 35184.81 11345.29 0.0000 135.251


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 35581263.49 0.00 35581263.49 0.00 35581263.49 23560625.38 0.00 0.00 8760.00 0.00
RETAIL_1_FLR_1 5682459.46 0.00 5682459.46 310101.36 5992560.81 1981818.02 0.00 0.00 8760.00 0.00
RETAIL_2_FLR_1 3943461.55 0.00 3943461.55 119699.52 4063161.07 2294951.32 0.00 0.00 8760.00 0.00
MECH_FLR_1 3219529.14 0.00 3219529.14 282898.54 3502427.69 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 1713514.72 0.00 1713514.72 163216.88 1876731.60 1821682.01 8760.00 0.00 0.00 0.00
LAUNDRY_FLR_1 67087049.60 0.00 67087049.60 386283.51 67473333.11 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 25481765.53 0.00 25481765.53 685496.60 26167262.14 14544917.54 0.00 0.00 8760.00 0.00
LOBBY_FLR_1 82666024.67 0.00 82666024.67 1958620.37 84624645.05 39585427.43 0.00 0.00 8760.00 0.00
ROOM_1_FLR_3 1460156.71 95196.47 1555353.18 179991.83 1735345.01 1946875.62 2190.00 5347.50 1222.50 0.00
ROOM_2_FLR_3 1459985.63 96871.97 1556857.61 179978.09 1736835.70 1946647.51 2190.00 5429.71 1140.29 0.00
ROOM_3_MULT19_FLR_3 1099911.97 216.06 1100128.03 50219.74 1150347.77 26397887.27 8395.00 365.00 0.00 367.33
ROOM_4_MULT19_FLR_3 19803829.30 100487.63 19904316.93 50233.47 19954550.40 26405105.73 2190.00 5359.96 1210.04 0.00
ROOM_5_FLR_3 1460156.71 95386.22 1555542.93 179991.83 1735534.76 1946875.62 2190.00 5347.50 1222.50 0.00
ROOM_6_FLR_3 1459985.63 103083.52 1563069.15 179978.09 1743047.25 1946647.51 2190.00 5347.50 1222.50 0.00
CORRIDOR_FLR_3 19942170.60 0.00 19942170.60 217646.33 20159816.93 14972100.18 0.00 0.00 8760.00 0.00
ROOM_1_FLR_6 365039.18 107077.59 472116.77 180028.86 652145.63 486718.90 1890.66 5357.13 1512.21 0.00
ROOM_2_FLR_6 364996.41 99704.64 464701.05 180015.12 644716.17 486661.88 1945.87 5508.32 1305.81 0.00
ROOM_3_MULT9_FLR_6 2345190.31 106950.50 2452140.81 92109.06 2544249.88 3126920.42 2190.00 5347.50 1222.50 0.00
BANQUET_FLR_6 42682439.19 0.00 42682439.19 439585.22 43122024.41 37458366.31 0.00 0.00 8760.00 0.00
DINING_FLR_6 45956230.31 0.00 45956230.31 439585.22 46395815.54 37458366.31 0.00 0.00 8760.00 0.00
KITCHEN_FLR_6 58196005.83 0.00 58196005.83 393530.69 58589536.52 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 11435180.51 0.00 11435180.51 385165.88 11820346.39 3961413.96 0.00 0.00 8760.00 0.00
Total Facility 0.21E+10 10384970.06 0.21E+10 18137997.94 0.21E+10 0.43E+10 8760.00 5894.77 8760.00 367.33


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.1283 0.0000 1.1283 0.0000 1.1283 0.7471 0.00 0.00 8760.00
RETAIL_1_FLR_1 0.1802 0.0000 0.1802 0.0098 0.1900 0.0628 0.00 0.00 8760.00
RETAIL_2_FLR_1 0.1250 0.0000 0.1250 0.0038 0.1288 0.0728 0.00 0.00 8760.00
MECH_FLR_1 0.1021 0.0000 0.1021 0.0090 0.1111 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.0543 0.0000 0.0543 0.0052 0.0595 0.0578 8760.00 0.00 0.00
LAUNDRY_FLR_1 2.1273 0.0000 2.1273 0.0122 2.1396 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 0.8080 0.0000 0.8080 0.0217 0.8298 0.4612 0.00 0.00 8760.00
LOBBY_FLR_1 2.6213 0.0000 2.6213 0.0621 2.6834 1.2552 0.00 0.00 8760.00
ROOM_1_FLR_3 0.0463 0.0030 0.0493 0.0057 0.0550 0.0617 2190.00 5347.50 1222.50
ROOM_2_FLR_3 0.0463 0.0031 0.0494 0.0057 0.0551 0.0617 2190.00 5429.71 1140.29
ROOM_4_MULT19_FLR_3 0.6280 0.0032 0.6312 0.0016 0.6328 0.8373 2190.00 5359.96 1210.04
ROOM_5_FLR_3 0.0463 0.0030 0.0493 0.0057 0.0550 0.0617 2190.00 5347.50 1222.50
ROOM_6_FLR_3 0.0463 0.0033 0.0496 0.0057 0.0553 0.0617 2190.00 5347.50 1222.50
CORRIDOR_FLR_3 0.6324 0.0000 0.6324 0.0069 0.6393 0.4748 0.00 0.00 8760.00
ROOM_1_FLR_6 0.0116 0.0034 0.0150 0.0057 0.0207 0.0154 1890.66 5357.13 1512.21
ROOM_2_FLR_6 0.0116 0.0032 0.0147 0.0057 0.0204 0.0154 1945.87 5508.32 1305.81
ROOM_3_MULT9_FLR_6 0.0744 0.0034 0.0778 0.0029 0.0807 0.0992 2190.00 5347.50 1222.50
BANQUET_FLR_6 1.3535 0.0000 1.3535 0.0139 1.3674 1.1878 0.00 0.00 8760.00
DINING_FLR_6 1.4573 0.0000 1.4573 0.0139 1.4712 1.1878 0.00 0.00 8760.00
KITCHEN_FLR_6 1.8454 0.0000 1.8454 0.0125 1.8579 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.3626 0.0000 0.3626 0.0122 0.3748 0.1256 0.00 0.00 8760.00
Total Facility 63.8541 0.3288 64.1829 0.4541 64.6370 72.9703 8760.00 5894.77 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.56E+09 0.00 0.56E+09 0.19E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 41645591.30 804974.61 42450565.91 64690340.46 8758.83 1.17 0.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 17.8732 0.0000 17.8732 6.0003 0.00 0.00 8760.00
FLR_3_DOAS 1.3206 0.0255 1.3461 2.0513 8758.83 1.17 0.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 0.00 7394.42 0.00 0.00 0.00 1365.58 0.00 0.00 0.00
FLR_3_DOAS 0.00 0.00 0.00 0.00 6935.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 0.0000 17.9341 0.0000 0.0000 0.0000 17.5567 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 0.0000 0.0000 0.0000 1.6681 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1359
Defaulted Fields 1202
Fields with Defaults 4075
Autosized Fields 351
Autosizable Fields 405
Autocalculated Fields 289
Autocalculatable Fields 549



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 5090.42 67243.31 23-DEC-03:50 357486.34 29-SEP-19:10
Electricity:Building 2279.19 30243.95 03-JUN-05:00 133648.28 02-JAN-20:10
Electricity:Zone:BASEMENT 245.14 2955.01 02-JAN-02:10 17976.64 02-JAN-20:10
Electricity:SpaceType:GENERAL 2272.10 30102.80 03-JUN-05:00 133406.95 02-JAN-20:10
InteriorLights:Electricity 543.96 4820.63 03-JUN-05:00 45424.10 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 102.03 927.11 02-JAN-02:10 8344.11 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 543.96 4820.63 03-JUN-05:00 45424.10 02-JAN-20:10
LightsWired:InteriorLights:Electricity 543.96 4820.63 03-JUN-05:00 45424.10 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 102.03 927.11 02-JAN-02:10 8344.11 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 543.96 4820.63 03-JUN-05:00 45424.10 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 15.82 195.57 02-JAN-02:10 1146.69 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 5.64 51.23 02-JAN-02:10 461.08 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 5.64 51.23 02-JAN-02:10 461.08 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 18.32 226.47 02-JAN-02:10 1327.87 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 6.53 59.33 02-JAN-02:10 533.93 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 6.53 59.33 02-JAN-02:10 533.93 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 20.00 245.14 02-JAN-02:10 1455.21 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 7.53 68.42 02-JAN-02:10 615.76 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 7.53 68.42 02-JAN-02:10 615.76 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 5.28 66.24 02-JAN-02:10 379.51 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 1.68 15.26 02-JAN-02:10 137.35 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 1.68 15.26 02-JAN-02:10 137.35 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 72.35 1002.76 02-JAN-02:10 4933.42 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.41 40.07 02-JAN-02:10 360.62 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.41 40.07 02-JAN-02:10 360.62 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 26.15 315.69 03-JUN-05:00 2381.38 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 11.81 69.23 01-JAN-13:10 1416.11 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 11.81 69.23 01-JAN-13:10 1416.11 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 259.79 3138.77 03-JUN-05:00 19610.05 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 110.79 1027.35 03-JUN-05:00 9580.84 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 110.79 1027.35 03-JUN-05:00 9580.84 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 17.85 257.74 01-JAN-02:10 1187.62 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 5.55 47.02 01-JAN-02:10 427.46 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 5.55 47.02 01-JAN-02:10 427.46 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 17.84 257.71 01-JAN-02:10 1187.48 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 5.55 47.01 01-JAN-02:10 427.41 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 5.55 47.01 01-JAN-02:10 427.41 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 295.07 4482.89 01-JAN-02:10 20504.95 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 66.32 561.43 01-JAN-02:10 5104.26 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 66.32 561.43 01-JAN-02:10 5104.26 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 295.15 4484.12 01-JAN-02:10 20510.57 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 66.33 561.58 01-JAN-02:10 5105.65 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 66.33 561.58 01-JAN-02:10 5105.65 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 17.85 257.74 01-JAN-02:10 1187.62 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 5.55 47.02 01-JAN-02:10 427.46 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 5.55 47.02 01-JAN-02:10 427.46 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 17.84 257.71 01-JAN-02:10 1187.48 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 5.55 47.01 01-JAN-02:10 427.41 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 5.55 47.01 01-JAN-02:10 427.41 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 51.07 464.00 02-JAN-02:10 4176.01 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 51.07 464.00 02-JAN-02:10 4176.01 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 51.07 464.00 02-JAN-02:10 4176.01 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 4.46 64.43 01-JAN-02:10 296.90 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.39 11.75 01-JAN-02:10 106.87 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 1.39 11.75 01-JAN-02:10 106.87 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 4.46 64.43 01-JAN-02:10 296.87 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.39 11.75 01-JAN-02:10 106.85 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 1.39 11.75 01-JAN-02:10 106.85 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 34.95 531.01 01-JAN-02:10 2428.88 01-JAN-08:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 7.86 66.50 01-JAN-02:10 604.62 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 7.86 66.50 01-JAN-02:10 604.62 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 201.59 2460.52 03-JUN-05:00 9234.71 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 25.73 211.22 03-JUN-05:00 2486.81 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 25.73 211.22 03-JUN-05:00 2486.81 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 201.59 2460.52 03-JUN-05:00 9234.71 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 25.73 211.22 03-JUN-05:00 2486.81 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 25.73 211.22 03-JUN-05:00 2486.81 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 443.12 5932.71 02-JAN-02:10 18599.73 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 12.01 109.08 02-JAN-02:10 981.75 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 12.01 109.08 02-JAN-02:10 981.75 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 13.51 122.77 02-JAN-02:10 1104.91 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 13.51 122.77 02-JAN-02:10 1104.91 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 13.51 122.77 02-JAN-02:10 1104.91 02-JAN-20:10
InteriorEquipment:Electricity 1728.14 25282.18 02-JAN-02:10 88863.15 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1728.14 25282.18 02-JAN-02:10 88863.15 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 952.41 15101.09 02-JAN-02:10 59188.31 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 143.11 2027.90 02-JAN-02:10 9632.53 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 952.41 15101.09 02-JAN-02:10 59188.31 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 424.02 5682.48 01-JAN-00:10 16179.04 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 8.75 277.50 01-JAN-00:10 277.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 4.94 156.70 01-JAN-00:10 156.70 01-JAN-00:10
Refrigeration:Electricity 44.03 732.85 25-OCT-22:30 2789.56 24-SEP-10:20
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 7.09 88.82 02-JAN-11:30 2093.44 01-JAN-11:10
Electricity:Plant 1439.77 2394.30 28-FEB-01:50 172556.81 16-OCT-11:00
LowTempRefrigeration:Refrigeration:Electricity 15.74 0.00 01-JAN-11:10 1307.48 30-SEP-10:50
MedTempRefrigeration:Refrigeration:Electricity 21.20 600.36 07-JAN-02:10 716.73 11-FEB-14:10
WaterSystems:Electricity 475.42 1086.70 03-JUN-00:30 43106.26 29-JUN-20:50
Electricity:HVAC 577.97 13532.83 12-MAR-03:30 37478.90 16-OCT-22:00
Fans:Electricity 555.55 13129.03 12-MAR-03:30 36650.23 16-OCT-22:00
General:Fans:Electricity 555.55 13129.03 12-MAR-03:30 36650.23 16-OCT-22:00
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ExteriorEquipment:Electricity 641.45 9451.13 02-JAN-02:20 39153.57 03-NOV-06:20
Transformer:ExteriorEquipment:Electricity 22.42 386.30 03-JUN-05:00 1279.09 19-JAN-21:10
ElectricityPurchased:Facility 5090.42 67243.31 23-DEC-03:50 357486.34 29-SEP-19:10
ElectricityPurchased:Plant 5090.42 67243.31 23-DEC-03:50 357486.34 29-SEP-19:10
Cogeneration:ElectricityPurchased 5090.42 67243.31 23-DEC-03:50 357486.34 29-SEP-19:10
General:Cogeneration:ElectricityPurchased 5090.42 67243.31 23-DEC-03:50 357486.34 29-SEP-19:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 5090.42 67243.31 23-DEC-03:50 357486.34 29-SEP-19:10
ElectricityNet:Plant 5090.42 67243.31 23-DEC-03:50 357486.34 29-SEP-19:10
Cogeneration:ElectricityNet 5090.42 67243.31 23-DEC-03:50 357486.34 29-SEP-19:10
General:Cogeneration:ElectricityNet 5090.42 67243.31 23-DEC-03:50 357486.34 29-SEP-19:10
ExteriorLights:Electricity 174.46 0.00 01-JAN-07:00 11096.45 01-JAN-00:10
General:ExteriorLights:Electricity 174.46 0.00 01-JAN-07:00 11096.45 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 616.11 9046.01 01-JAN-00:10 37691.69 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 2.91 18.80 01-JAN-00:10 188.00 01-JAN-07:10
Water Heater:WaterSystems:Electricity 90.75 1086.67 18-OCT-00:30 4738.71 09-JAN-19:10
Water Heater Parasitic:WaterSystems:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 819.08 0.00 01-JAN-00:30 157368.80 16-OCT-10:50
General:Cooling:Electricity 819.08 0.00 01-JAN-00:30 157368.80 16-OCT-10:50
Pumps:Electricity 108.32 56.70 12-MAY-07:50 6784.48 29-SEP-15:20
General:Pumps:Electricity 108.32 56.70 12-MAY-07:50 6784.48 29-SEP-15:20
WIRED_LTG_ELECTRICITY 19.15 0.00 01-JAN-00:10 1598.93 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 3658.21 29270.80 24-JUN-01:10 341650.43 29-MAR-19:50
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 1869.37 15908.90 04-JAN-11:10 262504.74 29-MAR-22:50
WaterSystems:NaturalGas 971.35 15908.90 03-JAN-16:10 80009.60 31-DEC-23:30
Water Heater:WaterSystems:NaturalGas 971.35 15908.90 03-JAN-16:10 80009.60 31-DEC-23:30
Heating:NaturalGas 898.02 0.00 04-JAN-11:10 221129.21 08-JAN-07:00
Boiler:Heating:NaturalGas 898.02 0.00 04-JAN-11:10 221129.21 08-JAN-07:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 2746.59 0.00 01-JAN-00:10 505976.37 18-AUG-15:20
PlantLoopCoolingDemand:HVAC 2746.59 0.00 01-JAN-00:10 505976.37 18-AUG-15:20
CoolingCoils:PlantLoopCoolingDemand 2746.59 0.00 01-JAN-00:10 505976.37 18-AUG-15:20


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 19-JAN-21:10
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 19-JAN-21:10
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 19-JAN-21:10
Water Heater:WaterSystems:Water 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:10
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 19-JAN-21:10
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 19-JAN-21:10
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 19-JAN-21:10
Water Heater:WaterSystems:MainsWater 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:10
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 03-JAN-07:10
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 03-JAN-07:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 17349.22 122639.62 27-MAR-13:40 1953802.33 17-AUG-15:20
EnergyTransfer:Building 4860.11 88943.62 29-MAR-10:30 292326.97 16-OCT-18:10
EnergyTransfer:Zone:KITCHEN_FLR_6 701.87 11402.45 29-MAR-03:00 34045.89 30-SEP-10:50
Refrigeration:EnergyTransfer 185.24 3970.64 07-JAN-02:10 10372.88 18-JUL-06:20
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 92.62 1985.32 07-JAN-02:10 5186.44 18-JUL-06:20
General:Refrigeration:EnergyTransfer 92.62 1985.32 07-JAN-02:10 5186.44 18-JUL-06:20
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 92.62 1985.32 07-JAN-02:10 5186.44 18-JUL-06:20
EnergyTransfer:Plant 7903.79 20711.74 27-MAR-13:40 1169131.92 17-AUG-15:20
LowTempRefrigeration:Refrigeration:EnergyTransfer 21.66 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 70.95 1747.55 07-JAN-02:10 2559.80 11-FEB-14:10
EnergyTransfer:HVAC 4585.33 778.27 12-MAY-07:50 575363.97 18-JUL-16:20
CoolingCoils:EnergyTransfer 3966.34 0.00 01-JAN-00:10 575363.97 18-JUL-16:20
EnergyTransfer:Zone:BASEMENT 310.97 7854.96 26-JUN-13:20 15861.34 08-JAN-07:00
Heating:EnergyTransfer 8.96 0.00 01-JAN-08:10 16181.73 29-MAR-08:10
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 8.96 0.00 01-JAN-08:10 16181.73 29-MAR-08:10
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 4758.53 86267.54 29-MAR-12:00 288779.33 16-OCT-18:10
Cooling:EnergyTransfer:Zone:BASEMENT 310.97 7854.96 26-JUN-13:20 15861.34 08-JAN-07:00
General:Cooling:EnergyTransfer 4758.53 86267.54 29-MAR-12:00 288779.33 16-OCT-18:10
General:Cooling:EnergyTransfer:Zone:BASEMENT 310.97 7854.96 26-JUN-13:20 15861.34 08-JAN-07:00
EnergyTransfer:Zone:RETAIL_1_FLR_1 44.12 0.29 30-MAR-06:50 3998.47 16-OCT-12:10
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.00 0.00 01-JAN-00:10 133.63 30-MAR-06:10
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.00 0.00 01-JAN-00:10 133.63 30-MAR-06:10
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 44.12 0.00 29-MAR-10:30 3998.47 16-OCT-12:10
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 44.12 0.00 29-MAR-10:30 3998.47 16-OCT-12:10
EnergyTransfer:Zone:RETAIL_2_FLR_1 35.96 691.45 29-MAR-12:40 1854.00 16-OCT-20:10
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 35.96 691.45 29-MAR-12:40 1854.00 16-OCT-20:10
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 35.96 691.45 29-MAR-12:40 1854.00 16-OCT-20:10
EnergyTransfer:Zone:MECH_FLR_1 26.68 238.78 30-MAR-03:50 1249.73 30-SEP-10:40
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:MECH_FLR_1 26.68 238.78 30-MAR-03:50 1249.73 30-SEP-10:40
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 26.68 238.78 30-MAR-03:50 1249.73 30-SEP-10:40
EnergyTransfer:Zone:STORAGE_FLR_1 13.88 48.63 29-MAR-12:00 667.59 30-SEP-10:40
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 13.88 48.63 29-MAR-12:00 667.59 30-SEP-10:40
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 13.88 48.63 29-MAR-12:00 667.59 30-SEP-10:40
EnergyTransfer:Zone:LAUNDRY_FLR_1 606.70 9856.04 30-MAR-04:00 38384.54 29-SEP-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 606.70 9856.04 30-MAR-04:00 38384.54 29-SEP-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 606.70 9856.04 30-MAR-04:00 38384.54 29-SEP-20:00
EnergyTransfer:Zone:CAFE_FLR_1 236.42 2317.37 29-MAR-12:10 13854.22 19-NOV-11:00
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 236.42 2317.37 29-MAR-12:10 13854.22 19-NOV-11:00
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 236.42 2317.37 29-MAR-12:10 13854.22 19-NOV-11:00
EnergyTransfer:Zone:LOBBY_FLR_1 790.29 16578.28 29-MAR-12:10 38344.96 16-OCT-21:10
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 790.29 16578.28 29-MAR-12:10 38344.96 16-OCT-21:10
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 790.29 16578.28 29-MAR-12:10 38344.96 16-OCT-21:10
EnergyTransfer:Zone:ROOM_1_FLR_3 52.04 0.00 01-JAN-08:10 9699.24 30-SEP-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 0.97 0.00 01-JAN-08:10 2167.34 29-MAR-08:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 0.97 0.00 01-JAN-08:10 2167.34 29-MAR-08:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 51.07 0.00 01-JAN-00:10 9699.24 30-SEP-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 51.07 0.00 01-JAN-00:10 9699.24 30-SEP-15:10
EnergyTransfer:Zone:ROOM_2_FLR_3 32.32 0.00 01-JAN-08:10 9005.98 17-AUG-15:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 1.90 0.00 01-JAN-08:10 2620.17 30-MAR-08:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 1.90 0.00 01-JAN-08:10 2620.17 30-MAR-08:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 30.42 0.00 01-JAN-00:10 9005.98 17-AUG-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 30.42 0.00 01-JAN-00:10 9005.98 17-AUG-15:10
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 301.08 0.00 01-JAN-00:10 50819.34 16-OCT-12:30
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 301.08 0.00 01-JAN-00:10 50819.34 16-OCT-12:30
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 301.08 0.00 01-JAN-00:10 50819.34 16-OCT-12:30
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 344.95 0.00 01-JAN-08:10 56227.45 19-JUL-15:20
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 0.39 0.00 01-JAN-00:10 5584.44 20-FEB-16:10
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 0.39 0.00 01-JAN-00:10 5584.44 20-FEB-16:10
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 344.56 0.00 01-JAN-08:10 56227.45 19-JUL-15:20
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 344.56 0.00 01-JAN-08:10 56227.45 19-JUL-15:20
EnergyTransfer:Zone:ROOM_5_FLR_3 48.23 0.00 01-JAN-08:10 9088.47 15-OCT-08:10
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 1.08 0.00 01-JAN-07:20 2063.57 30-MAR-04:00
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 1.08 0.00 01-JAN-07:20 2063.57 30-MAR-04:00
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 47.15 0.00 01-JAN-00:10 9088.47 15-OCT-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 47.15 0.00 01-JAN-00:10 9088.47 15-OCT-08:10
EnergyTransfer:Zone:ROOM_6_FLR_3 30.95 0.00 01-JAN-08:10 9210.48 17-OCT-08:40
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 2.11 0.00 01-JAN-07:30 2154.76 30-MAR-04:00
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 2.11 0.00 01-JAN-07:30 2154.76 30-MAR-04:00
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 28.84 0.00 01-JAN-00:10 9210.48 17-OCT-08:40
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 28.84 0.00 01-JAN-00:10 9210.48 17-OCT-08:40
EnergyTransfer:Zone:CORRIDOR_FLR_3 168.96 1212.35 30-MAR-06:10 7897.60 16-OCT-10:40
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 168.96 1212.35 30-MAR-06:10 7897.60 16-OCT-10:40
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 168.96 1212.35 30-MAR-06:10 7897.60 16-OCT-10:40
EnergyTransfer:Zone:ROOM_1_FLR_6 12.72 0.00 01-JAN-08:10 2545.09 30-SEP-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 0.72 0.00 01-JAN-08:10 809.24 29-MAR-08:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 0.72 0.00 01-JAN-08:10 809.24 29-MAR-08:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 12.00 0.00 01-JAN-00:10 2545.09 30-SEP-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 12.00 0.00 01-JAN-00:10 2545.09 30-SEP-15:10
EnergyTransfer:Zone:ROOM_2_FLR_6 8.42 0.00 01-JAN-08:10 2435.88 17-AUG-15:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 1.25 0.00 01-JAN-08:10 848.12 03-JAN-09:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 1.25 0.00 01-JAN-08:10 848.12 03-JAN-09:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 7.18 0.00 01-JAN-00:10 2435.88 17-AUG-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 7.18 0.00 01-JAN-00:10 2435.88 17-AUG-15:10
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 84.19 0.00 01-JAN-08:10 12957.01 26-OCT-15:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 0.55 0.00 01-JAN-07:20 2552.03 30-MAR-04:00
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 0.55 0.00 01-JAN-07:20 2552.03 30-MAR-04:00
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 83.64 0.00 01-JAN-00:10 12957.01 26-OCT-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 83.64 0.00 01-JAN-00:10 12957.01 26-OCT-15:10
EnergyTransfer:Zone:BANQUET_FLR_6 438.00 9604.41 29-MAR-11:00 21011.37 29-SEP-22:00
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 438.00 9604.41 29-MAR-11:00 21011.37 29-SEP-22:00
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 438.00 9604.41 29-MAR-11:00 21011.37 29-SEP-22:00
EnergyTransfer:Zone:DINING_FLR_6 477.56 10672.02 29-MAR-11:00 22414.40 29-SEP-21:10
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DINING_FLR_6 477.56 10672.02 29-MAR-11:00 22414.40 29-SEP-21:10
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 477.56 10672.02 29-MAR-11:00 22414.40 29-SEP-21:10
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 609.25 9279.19 29-MAR-03:00 29031.83 30-SEP-10:50
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 609.25 9279.19 29-MAR-03:00 29031.83 30-SEP-10:50
EnergyTransfer:Zone:CORRIDOR_FLR_6 93.80 186.34 30-MAR-06:10 4881.41 30-SEP-13:50
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 93.80 186.34 30-MAR-06:10 4881.41 30-SEP-13:50
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 93.80 186.34 30-MAR-06:10 4881.41 30-SEP-13:50
PlantLoopHeatingDemand:Facility 2910.81 9085.27 04-AUG-00:20 333171.42 29-MAR-20:50
PlantLoopHeatingDemand:Plant 2291.82 9085.27 04-AUG-00:20 210735.82 31-AUG-20:40
WaterSystems:PlantLoopHeatingDemand 2291.82 9085.27 04-AUG-00:20 210735.82 31-AUG-20:40
General:WaterSystems:PlantLoopHeatingDemand 698.91 9080.99 04-AUG-00:10 48516.96 02-FEB-07:10
HeatingCoils:EnergyTransfer 618.99 0.00 04-JAN-11:10 176439.41 08-JAN-07:00
PlantLoopHeatingDemand:HVAC 618.99 0.00 04-JAN-11:10 176439.41 08-JAN-07:00
HeatingCoils:PlantLoopHeatingDemand 618.99 0.00 04-JAN-11:10 176439.41 08-JAN-07:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 1592.91 0.00 01-JAN-00:10 175346.33 31-AUG-20:40
WaterSystems:EnergyTransfer 698.91 9080.99 04-AUG-00:10 48516.96 02-FEB-07:10
WaterUse:WaterSystems:EnergyTransfer 698.91 9080.99 04-AUG-00:10 48516.96 02-FEB-07:10
Boilers:EnergyTransfer 613.76 0.00 04-JAN-11:10 175069.70 08-JAN-07:00
Chillers:EnergyTransfer 2839.71 0.00 01-JAN-00:30 512312.70 17-AUG-15:20
HeatRejection:EnergyTransfer 3658.79 0.00 01-JAN-00:30 639768.36 17-AUG-15:20
General:HeatRejection:EnergyTransfer 3658.79 0.00 01-JAN-00:30 639768.36 17-AUG-15:20



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.000 -310.973 0.000 0.000 146.376 102.033 143.105 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -80.541
RETAIL_1_FLR_1 0.000 0.000 0.001 -44.116 0.000 0.000 15.555 5.638 10.186 21.331 0.000 0.050 1.430 0.000 -7.791 0.000 -2.284 -0.000
RETAIL_2_FLR_1 0.000 0.000 0.000 -35.960 0.000 0.000 16.861 6.529 11.795 0.000 0.000 0.022 1.759 0.000 0.000 0.000 -1.007 -0.000
MECH_FLR_1 0.000 0.000 0.000 -26.677 0.000 0.000 3.724 7.530 12.471 0.000 0.000 0.059 5.057 0.000 0.000 0.000 -2.164 -0.000
STORAGE_FLR_1 0.000 0.000 0.000 -13.882 0.000 0.000 2.888 1.680 3.598 0.000 0.000 0.034 6.906 0.000 0.000 0.000 -1.224 0.000
LAUNDRY_FLR_1 0.000 0.000 0.000 -606.699 0.000 0.000 11.483 4.410 658.131 0.000 0.000 0.098 0.000 0.000 0.000 0.000 -3.210 -64.213
CAFE_FLR_1 0.000 0.000 0.000 -236.423 0.000 0.000 190.006 11.808 14.341 58.977 0.000 0.113 0.000 0.000 -24.239 0.000 -5.852 -8.731
LOBBY_FLR_1 0.000 0.000 0.000 -790.289 0.000 0.000 553.921 110.792 148.998 78.115 0.000 0.333 0.000 0.000 -32.714 0.000 -17.284 -51.873
ROOM_1_FLR_3 2.335 -41.197 0.000 -11.232 0.000 0.000 9.655 5.554 12.292 44.156 0.000 0.179 2.111 0.000 -17.105 0.000 -6.749 -0.002
ROOM_2_FLR_3 3.988 -20.421 0.000 -12.092 0.000 0.000 9.448 5.553 12.291 31.533 0.000 0.138 0.000 0.000 -17.719 0.000 -7.842 -4.878
ROOM_3_MULT19_FLR_3 0.000 -284.391 0.000 -16.692 0.000 0.000 0.000 66.316 228.754 227.174 0.000 0.141 0.010 0.000 -144.414 0.000 -49.358 -27.530
ROOM_4_MULT19_FLR_3 4.783 -190.514 0.000 -158.426 0.000 0.000 181.689 66.334 228.817 68.941 0.000 0.940 0.001 0.000 -93.378 0.000 -67.088 -42.097
ROOM_5_FLR_3 2.573 -37.405 0.000 -11.235 0.000 0.000 9.650 5.554 12.292 41.056 0.000 0.179 0.804 0.000 -16.688 0.000 -6.779 -0.001
ROOM_6_FLR_3 4.285 -19.101 0.000 -11.911 0.000 0.000 9.512 5.553 12.291 28.288 0.000 0.132 0.000 0.000 -16.858 0.000 -7.673 -4.517
CORRIDOR_FLR_3 0.000 0.000 0.000 -168.957 0.000 0.000 117.071 51.065 0.000 36.883 0.000 0.156 0.000 0.000 -22.344 0.000 -6.809 -7.066
ROOM_1_FLR_6 1.308 -9.780 0.000 -2.809 0.000 0.000 2.416 1.388 3.073 10.926 0.000 0.045 0.000 0.000 -4.219 0.000 -1.739 -0.609
ROOM_2_FLR_6 2.013 -4.912 0.000 -3.032 0.000 0.000 2.360 1.388 3.073 7.785 0.000 0.034 0.000 0.000 -4.384 0.000 -1.986 -2.338
ROOM_3_MULT9_FLR_6 1.743 -66.765 0.000 -18.070 0.000 0.000 21.707 7.855 27.097 55.266 0.000 0.252 0.638 0.000 -19.715 0.000 -10.009 -0.001
BANQUET_FLR_6 0.000 0.000 0.000 -438.003 0.000 0.000 317.330 25.733 175.857 6.494 0.000 0.051 0.000 0.000 -13.422 0.000 -4.212 -69.828
DINING_FLR_6 0.000 0.000 0.000 -477.562 0.000 0.000 315.943 25.733 175.857 6.157 0.000 0.047 0.000 0.000 -13.892 0.000 -4.269 -28.014
KITCHEN_FLR_6 0.000 0.000 0.000 -609.240 0.000 0.000 28.663 12.005 540.650 19.230 0.000 0.036 21.815 0.000 -9.379 0.000 -3.781 -0.000
CORRIDOR_FLR_6 0.000 0.000 0.000 -93.801 0.000 0.000 31.398 13.511 0.000 17.984 0.000 0.057 43.735 0.000 -9.930 0.000 -2.954 0.000
Total Facility 23.029 -674.487 0.001 -4098.080 0.000 0.000 1997.656 543.962 2434.967 760.297 0.000 3.098 84.267 0.000 -468.192 0.000 -214.272 -392.239


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 08-JAN-07:00 0.00 0.00 0.00 -15859.04 0.00 0.00 5720.68 2781.33 4055.80 0.00 0.00 0.00 3301.22 0.00 -0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 16-OCT-12:10 0.00 0.00 0.00 -3998.50 0.00 0.00 150.60 128.08 252.59 4726.06 0.00 129.44 0.00 0.00 -0.00 0.00 0.00 -1388.27
RETAIL_2_FLR_1 16-OCT-20:10 0.00 0.00 0.00 -1853.61 0.00 0.00 697.63 474.61 752.15 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -15.74 -55.03
MECH_FLR_1 30-SEP-10:35 0.00 0.00 0.00 -1252.26 0.00 0.00 58.83 171.04 309.27 0.00 0.00 77.47 635.65 0.00 -0.00 0.00 0.00 0.00
STORAGE_FLR_1 30-SEP-10:35 0.00 0.00 0.00 -668.68 0.00 0.00 45.18 38.16 89.22 0.00 0.00 44.50 451.62 0.00 -0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 29-SEP-20:00 0.00 0.00 0.00 -38384.51 0.00 0.00 408.88 360.62 44299.38 0.00 0.00 14.22 0.00 0.00 -0.00 0.00 0.00 -6698.58
CAFE_FLR_1 19-NOV-11:00 0.00 0.00 0.00 -13859.45 0.00 0.00 4947.83 103.85 406.43 13641.16 0.00 50.65 0.00 0.00 -0.00 0.00 0.00 -5290.48
LOBBY_FLR_1 16-OCT-21:10 0.00 0.00 0.00 -38336.01 0.00 0.00 26440.89 6387.23 7389.94 0.00 0.00 0.00 56.59 0.00 -1518.76 0.00 -419.88 0.00
ROOM_1_FLR_3 13-OCT-15:01 0.00 -10813.90 0.00 -740.85 0.00 0.00 235.28 119.69 273.93 6679.18 0.00 127.45 4119.22 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_3 14-OCT-08:61 0.00 -10623.87 0.00 -771.53 0.00 0.00 126.09 239.35 653.15 1217.71 0.00 116.14 9042.96 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 16-OCT-12:30 0.00 -50819.72 0.00 0.00 0.00 0.00 0.00 1429.19 5097.90 54143.08 0.00 1139.37 0.00 0.00 -0.00 0.00 0.00 -10989.82
ROOM_4_MULT19_FLR_3 14-OCT-08:61 0.00 -62579.90 0.00 -10555.94 0.00 0.00 2425.03 2859.17 12159.85 6633.91 0.00 600.58 48457.29 0.00 -0.00 0.00 0.00 0.00
ROOM_5_FLR_3 14-OCT-08:61 0.00 -9615.80 0.00 -749.71 0.00 0.00 130.71 239.38 653.23 6952.56 0.00 123.91 2265.71 0.00 -0.00 0.00 0.00 0.00
ROOM_6_FLR_3 17-OCT-08:21 0.00 -10654.14 0.00 -932.52 0.00 0.00 71.80 188.06 452.99 6503.22 0.00 54.58 4316.00 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 16-OCT-10:35 0.00 0.00 0.00 -7904.89 0.00 0.00 1221.86 1160.00 0.00 8201.08 0.00 404.68 0.00 0.00 -0.00 0.00 0.00 -3082.72
ROOM_1_FLR_6 13-OCT-15:01 0.00 -2817.37 0.00 -185.42 0.00 0.00 58.82 29.92 68.48 1654.13 0.00 31.41 1160.02 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_6 14-OCT-08:61 0.00 -2681.51 0.00 -185.06 0.00 0.00 32.39 59.84 163.29 314.21 0.00 31.44 2265.41 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 14-OCT-08:61 0.00 -13207.66 0.00 -1195.64 0.00 0.00 294.11 338.59 1439.98 5391.78 0.00 143.02 6795.83 0.00 -0.00 0.00 0.00 0.00
BANQUET_FLR_6 29-SEP-22:00 0.00 0.00 0.00 -21012.41 0.00 0.00 15644.40 1657.87 6747.90 0.00 0.00 6.51 0.00 0.00 -203.16 0.00 0.00 -2841.12
DINING_FLR_6 29-SEP-21:10 0.00 0.00 0.00 -22414.94 0.00 0.00 15644.17 1657.87 6747.90 0.00 0.00 7.86 0.00 0.00 -214.66 0.00 0.00 -1428.21
KITCHEN_FLR_6 30-SEP-10:50 0.00 0.00 0.00 -29045.00 0.00 0.00 462.90 272.71 23951.61 2372.30 0.00 94.66 1890.83 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 30-SEP-13:50 0.00 0.00 0.00 -4881.99 0.00 0.00 462.68 306.92 0.00 2722.52 0.00 109.47 1280.41 0.00 -0.00 0.00 0.00 0.00
Total Facility 29-SEP-18:02 0.00 -129410.33 0.00 -180918.81 0.00 0.00 75733.03 40391.24 121562.63 979.04 0.00 2275.61 71228.75 0.00 -1841.15 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 30-MAR-06:07 0.00 0.00 143.62 0.00 0.00 0.00 357.99 256.16 433.01 0.00 0.00 0.00 0.00 0.00 -666.34 0.00 -189.69 -334.74
RETAIL_2_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MECH_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 30-MAR-08:62 6090.69 381.68 0.00 -381.68 0.00 0.00 103.46 188.08 453.05 399.21 0.00 0.00 0.00 0.00 -0.00 0.00 -315.44 -6919.05
ROOM_2_FLR_3 30-MAR-08:62 6094.63 363.23 0.00 -363.23 0.00 0.00 104.58 188.06 452.99 0.00 0.00 0.00 0.00 0.00 -237.81 0.00 -308.43 -6294.02
ROOM_3_MULT19_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 05-FEB-16:04 34282.14 5804.26 0.00 -5804.26 0.00 0.00 2642.68 1684.90 5687.67 0.00 0.00 0.00 0.00 0.00 -329.99 0.00 -11047.91 -32919.49
ROOM_5_FLR_3 28-MAR-08:62 5830.90 408.61 0.00 -408.61 0.00 0.00 102.17 188.08 453.05 0.00 0.00 0.00 0.00 0.00 -1036.93 0.00 -326.90 -5210.37
ROOM_6_FLR_3 28-MAR-08:62 5797.13 405.00 0.00 -405.00 0.00 0.00 102.38 188.06 452.99 0.00 0.00 0.00 0.00 0.00 -1032.89 0.00 -325.54 -5182.14
CORRIDOR_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 30-MAR-08:62 1842.64 88.06 0.00 -88.06 0.00 0.00 26.45 47.02 113.26 107.42 0.00 0.00 0.00 0.00 -0.00 0.00 -76.48 -2060.31
ROOM_2_FLR_6 30-MAR-08:62 1840.66 83.63 0.00 -83.63 0.00 0.00 26.71 47.02 113.25 0.00 0.00 0.00 0.00 0.00 -49.09 0.00 -74.80 -1903.75
ROOM_3_MULT9_FLR_6 12-MAY-15:04 8503.02 691.67 0.00 -691.67 0.00 0.00 537.00 169.29 603.86 428.34 0.00 0.00 0.00 0.00 -0.00 0.00 -2995.48 -7246.04
BANQUET_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 31-DEC-16:04 -118527.05 117678.05 0.00 -117678.05 0.00 0.00 33619.61 10762.97 74680.66 33760.21 0.00 0.00 0.00 0.00 -4588.25 0.00 -16640.51 -13067.63



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 19.9471 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 19.8418 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 11.6690 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 11.6690 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.002360 106.4990 0.000305 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.003540 10.8290 0.000610 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.003540 12.5400 0.000610 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.003540 142.3000 0.000914 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.003540 422.4350 0.000305 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.000697 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.9287 1.9287 1.1283 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3035 0.3035 0.1775 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2134 0.2134 0.1249 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1745 0.1745 0.1021 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0929 0.0929 0.0543 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.3067 3.3067 1.9344 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3668 1.3668 0.7996 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.4513 4.4513 2.6040 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0810 1.0810 0.6324 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.0809 2.0809 1.2173 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1864 2.1864 1.2790 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1412 2.1412 1.2526 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6198 0.6198 0.3626 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 19.9471 19.8418 19.9471 11.6690 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1283 1.1283 1.1283 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1775 0.1775 0.1775 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1249 0.1249 0.1249 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1021 0.1021 0.1021 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.0543 0.0543 0.0543 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.9344 1.9344 1.9344 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7996 0.7996 0.7996 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6040 2.6040 2.6040 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6324 0.6324 0.6324 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2173 1.2173 1.2173 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2790 1.2790 1.2790 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2526 1.2526 1.2526 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3626 0.3626 0.3626 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 11.6690 11.6690 11.6690 11.6690 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 105.50
Number of hours not met 105.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 898.02 221129.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 819.08 157368.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 543.96 45424.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 174.46 11096.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 952.41 59188.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 8.75 277.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 4.94 156.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 22.42 1279.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 616.11 37691.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 2.91 188.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 555.55 36650.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 108.32 6784.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.75 4738.71 971.35 80009.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Other 0.00 38367.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.09 2093.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 15.74 1307.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 21.20 716.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1772.17 5090.42
Natural Gas 1788.84 3658.21
Additional 0.00 0.00
Total 3561.01 8748.63


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 47.95
Space Heating 0.00
Space Cooling 72.20
Fans (All) 48.97
Service Water Heating 41.90
Receptacle Equipment 152.32
Miscellaneous (All) 448.68
Subtotal 448.68


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 79.15
Service Water Heating 85.62
Miscellaneous (All) 322.44
Subtotal 322.44


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 6.22
Space Heating 10.26
Space Cooling 9.36
Fans (All) 6.35
Service Water Heating 16.54
Receptacle Equipment 40.20
Miscellaneous 11.07


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2398. 8760.
LTG_SCH_LOBBY 3061. 8760.
LTG_SCH_STORAGE 1339. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 3061. 8760.
LTG_SCH_GUESTROOM 2482. 8760.
LTG_SCH_CORRIDOR 2295. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_2 1591. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3737. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 5740. 6205.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 0. 0.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 15.56 365 15.56 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 26.67 365 26.67 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8717.33 42.67 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 5953.83 2806.17 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8755.50 4.50 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8666.33 93.67 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 5953.83 0.00 0.00 0.00 0.00
Max 8760.00 2806.17 0.00 0.00 0.00
Average 8626.05 133.95 0.00 0.00 0.00
Sum 189773.00 2947.00 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4150.83 3.17 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4138.17 15.83 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 15.83 0.00 0.00 0.00
Average 288886.18 0.86 0.00 0.00 0.00
Sum 6355496.00 19.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8133.67 626.33 0.00 0.00 0.00
LOBBY_FLR_1 8053.33 706.67 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8488.17 271.83 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 4797.50 3962.50 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8752.83 7.17 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8632.50 127.50 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8759.67 0.33 0.00 0.00 0.00
ROOM_2_FLR_6 8369.50 390.50 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 7864.00 896.00 0.00 0.00 0.00
DINING_FLR_6 7983.00 777.00 0.00 0.00 0.00
KITCHEN_FLR_6 8688.33 71.67 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 4797.50 0.00 0.00 0.00 0.00
Max 8760.00 3962.50 0.00 0.00 0.00
Average 8403.75 356.25 0.00 0.00 0.00
Sum 184882.50 7837.50 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 631428.50 78988.50 0.00 0.00 0.00
LOBBY_FLR_1 1856569.00 258860.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4039.50 114.50 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4153.17 0.83 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4143.83 10.17 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 3974.50 179.50 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1059427.67 186287.33 0.00 0.00 0.00
DINING_FLR_6 1082854.50 162860.50 0.00 0.00 0.00
KITCHEN_FLR_6 107560.50 708.50 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 1856569.00 258860.00 0.00 0.00 0.00
Average 257613.87 31273.17 0.00 0.00 0.00
Sum 5667505.17 688009.83 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:02:48

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 8760.00 0.00 0.00
LOBBY_FLR_1 0.00 8760.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 8760.00 0.00 0.00
DINING_FLR_6 0.00 8760.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 1592.73 0.00 0.00
Sum 0.00 35040.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 710417.00 0.00 0.00
LOBBY_FLR_1 0.00 2115429.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 0.00 0.00 0.00 0.00
BANQUET_FLR_6 0.00 1245715.00 0.00 0.00
DINING_FLR_6 0.00 1245715.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 2115429.00 0.00 0.00
Average 0.00 241694.36 0.00 0.00
Sum 0.00 5317276.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

For: Environment

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C

For: Environment

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO

For: Environment

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.279337E+11 15861.34 08-JAN-07:00 1.00 -0.3 0.749580E+10 4662.29 27-JAN-22:10 9.17 8.99
February 0.228331E+11 12102.54 01-FEB-11:35 25.00 14.29 0.637200E+10 4569.40 01-FEB-22:19 13.00 11.68
March 0.246111E+11 11656.91 08-MAR-02:00 4.00 3.53 0.689478E+10 4274.88 01-MAR-23:10 4.00 3.53
April 0.237312E+11 11575.87 30-APR-10:33 25.67 16.97 0.658697E+10 4221.41 14-APR-22:10 25.67 16.97
May 0.244862E+11 11417.12 04-MAY-18:10 18.83 14.89 0.681238E+10 4231.20 12-MAY-21:10 11.83 11.29
June 0.235854E+11 11462.08 25-JUN-10:33 23.00 17.26 0.652587E+10 4179.76 01-JUN-22:10 23.00 17.26
July 0.261516E+11 12341.08 23-JUL-10:33 25.67 20.39 0.698985E+10 4358.70 14-JUL-22:10 25.67 20.39
August 0.266165E+11 12316.24 13-AUG-10:33 24.00 19.90 0.710912E+10 4389.48 25-AUG-22:10 16.00 16.00
September 0.267366E+11 12988.76 30-SEP-10:35 30.57 17.23 0.711846E+10 4564.87 28-SEP-22:10 30.57 17.23
October 0.287551E+11 13474.76 15-OCT-10:33 31.67 16.43 0.759443E+10 4713.52 27-OCT-22:10 12.83 10.12
November 0.276513E+11 12998.52 19-NOV-11:33 26.00 15.32 0.743123E+10 4753.99 30-NOV-23:10 11.03 5.21
December 0.278811E+11 12295.82 12-DEC-22:00 6.00 5.49 0.755467E+10 4738.82 01-DEC-22:10 6.00 5.49
                     
Annual Sum or Average 0.310973E+12         0.844856E+11        
Minimum of Months 0.228331E+11 11417.12   1.00 -0.3 0.637200E+10 4179.76   4.00 3.53
Maximum of Months 0.287551E+11 15861.34   31.67 20.39 0.759443E+10 4753.99   30.57 20.39



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.366727E+10 3161.42 14-JAN-12:40 25.33 11.70 0.664809E+09 428.35 18-JAN-22:30 16.50 13.26
February 0.298389E+10 2741.89 02-FEB-12:40 19.33 12.36 0.592581E+09 427.64 01-FEB-22:30 19.33 12.36
March 0.295649E+10 2448.53 11-MAR-13:00 24.00 13.82 0.646501E+09 425.45 23-MAR-21:30 13.50 12.93
April 0.339695E+10 1999.71 08-APR-10:35 21.67 16.37 0.634564E+09 426.08 26-APR-22:10 16.00 15.29
May 0.325210E+10 1939.41 04-MAY-10:35 22.00 15.73 0.639844E+09 427.34 04-MAY-21:30 17.00 15.07
June 0.348183E+10 1856.46 25-JUN-10:33 23.00 17.26 0.634675E+09 424.26 28-JUN-21:40 17.00 16.37
July 0.396283E+10 2044.19 30-JUL-10:33 24.67 20.10 0.681650E+09 440.29 31-JUL-21:40 18.80 17.92
August 0.417532E+10 2119.38 27-AUG-10:33 23.33 18.72 0.706573E+09 448.21 18-AUG-21:40 23.33 18.72
September 0.404488E+10 3398.01 30-SEP-13:10 32.00 16.98 0.680243E+09 490.50 29-SEP-21:40 32.00 16.98
October 0.447302E+10 3998.47 16-OCT-12:10 35.68 17.48 0.712571E+09 488.93 16-OCT-21:40 19.33 11.10
November 0.381139E+10 3489.96 19-NOV-12:30 26.50 15.22 0.652473E+09 432.57 27-NOV-22:30 16.00 5.61
December 0.390959E+10 3335.61 19-DEC-12:50 25.83 11.54 0.673007E+09 445.97 05-DEC-22:30 25.83 11.54
                     
Annual Sum or Average 0.441156E+11         0.791949E+10        
Minimum of Months 0.295649E+10 1856.46   19.33 11.54 0.592581E+09 424.26   13.50 5.61
Maximum of Months 0.447302E+10 3998.47   35.68 20.10 0.712571E+09 490.50   32.00 18.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.291937E+10 1551.65 08-JAN-07:00 1.00 -0.3 0.849119E+09 557.94 20-JAN-23:10 13.83 13.83
February 0.258953E+10 1362.14 03-FEB-21:00 13.00 7.33 0.767570E+09 563.18 03-FEB-23:10 11.67 3.87
March 0.282721E+10 1384.25 23-MAR-18:10 16.50 14.36 0.839712E+09 562.14 24-MAR-22:10 13.00 11.29
April 0.289787E+10 1428.50 26-APR-18:10 18.67 15.37 0.838383E+09 569.55 26-APR-22:10 16.00 15.29
May 0.296437E+10 1428.99 04-MAY-18:10 18.83 14.89 0.862255E+09 569.55 03-MAY-22:10 18.83 14.89
June 0.299196E+10 1456.41 29-JUN-18:10 21.50 18.39 0.855117E+09 569.55 30-JUN-22:10 16.13 16.03
July 0.324798E+10 1513.89 31-JUL-21:00 19.00 17.66 0.903316E+09 569.55 13-JUL-22:10 19.00 17.66
August 0.330510E+10 1594.46 18-AUG-21:00 19.00 17.66 0.916854E+09 569.55 10-AUG-22:10 19.00 17.66
September 0.312212E+10 1805.05 29-SEP-21:00 24.60 13.50 0.875872E+09 569.55 13-SEP-22:10 24.60 13.50
October 0.324003E+10 1854.00 16-OCT-20:10 20.50 12.73 0.906447E+09 569.55 18-OCT-21:30 14.50 14.21
November 0.290071E+10 1436.15 19-NOV-11:33 26.00 15.32 0.843954E+09 562.37 01-NOV-22:10 26.00 15.32
December 0.295362E+10 1381.16 05-DEC-21:00 16.00 9.09 0.863653E+09 569.54 05-DEC-23:10 17.33 9.21
                     
Annual Sum or Average 0.359599E+11         0.103223E+11        
Minimum of Months 0.258953E+10 1362.14   1.00 -0.3 0.767570E+09 557.94   11.67 3.87
Maximum of Months 0.330510E+10 1854.00   26.00 18.39 0.916854E+09 569.55   26.00 17.66



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.202619E+10 1064.80 28-JAN-07:00 3.00 2.55 0.162132E+09 106.79 18-JAN-22:19 3.00 2.55
February 0.184237E+10 994.91 02-FEB-11:33 19.33 10.71 0.146777E+09 104.71 03-FEB-22:10 9.50 4.24
March 0.196743E+10 1014.73 19-MAR-10:33 19.33 15.06 0.161057E+09 104.39 24-MAR-21:19 13.00 11.68
April 0.211776E+10 1085.13 30-APR-10:33 25.67 16.97 0.162042E+09 107.71 27-APR-21:19 25.67 16.97
May 0.224929E+10 1105.27 04-MAY-18:10 18.83 14.89 0.170803E+09 110.48 04-MAY-21:19 17.00 15.07
June 0.233772E+10 1154.89 25-JUN-10:33 23.00 17.26 0.172720E+09 113.35 30-JUN-21:19 16.03 15.21
July 0.255684E+10 1212.39 23-JUL-10:33 25.67 20.39 0.183667E+09 115.08 19-JUL-22:10 25.67 20.39
August 0.255427E+10 1202.25 19-AUG-10:35 24.67 20.11 0.184228E+09 115.24 18-AUG-21:19 24.67 20.11
September 0.236056E+10 1252.29 30-SEP-10:35 30.57 17.23 0.173436E+09 116.20 29-SEP-22:10 30.57 17.23
October 0.246891E+10 1241.63 16-OCT-10:35 36.33 17.49 0.181118E+09 118.39 16-OCT-22:10 20.17 11.06
November 0.209697E+10 1068.15 19-NOV-11:33 26.00 15.32 0.162282E+09 106.88 01-NOV-21:10 26.00 15.32
December 0.209833E+10 1037.39 19-DEC-11:35 25.00 11.16 0.164429E+09 106.84 05-DEC-22:19 25.00 11.16
                     
Annual Sum or Average 0.266766E+11         0.202469E+10        
Minimum of Months 0.184237E+10 994.91   3.00 2.55 0.146777E+09 104.39   3.00 2.55
Maximum of Months 0.255684E+10 1252.29   36.33 20.39 0.184228E+09 118.39   30.57 20.39



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.103999E+10 552.97 20-JAN-11:35 21.67 15.71 0.123062E+09 79.65 18-JAN-23:10 21.67 15.71
February 0.953649E+09 528.43 04-FEB-11:33 20.67 8.25 0.111198E+09 77.98 03-FEB-23:10 20.67 8.25
March 0.100168E+10 538.24 23-MAR-10:35 22.00 16.70 0.122087E+09 77.82 24-MAR-22:10 13.00 11.29
April 0.110520E+10 576.83 30-APR-10:33 25.67 16.97 0.122736E+09 80.19 27-APR-22:10 25.67 16.97
May 0.117223E+10 585.63 04-MAY-10:35 22.00 15.73 0.129134E+09 82.43 04-MAY-22:10 16.83 15.02
June 0.122059E+10 611.30 25-JUN-10:33 23.00 17.26 0.130687E+09 84.23 30-JUN-22:10 16.13 16.03
July 0.133680E+10 642.86 23-JUL-10:33 25.67 20.39 0.139029E+09 85.74 19-JUL-22:10 25.67 20.39
August 0.133632E+10 637.83 19-AUG-10:35 24.67 20.11 0.139528E+09 85.84 18-AUG-22:10 24.67 20.11
September 0.123550E+10 668.69 30-SEP-10:35 30.57 17.23 0.131477E+09 87.20 29-SEP-22:10 30.57 17.23
October 0.129175E+10 665.51 16-OCT-10:35 36.33 17.49 0.137228E+09 88.50 16-OCT-22:10 20.17 11.06
November 0.109527E+10 572.44 19-NOV-11:33 26.00 15.32 0.122930E+09 79.68 01-NOV-00:10 26.00 15.32
December 0.109334E+10 554.70 19-DEC-11:35 25.00 11.16 0.124610E+09 80.11 05-DEC-23:10 25.00 11.16
                     
Annual Sum or Average 0.138823E+11         0.153371E+10        
Minimum of Months 0.953649E+09 528.43   20.67 8.25 0.111198E+09 77.82   13.00 8.25
Maximum of Months 0.133680E+10 668.69   36.33 20.39 0.139528E+09 88.50   30.57 20.39



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.506135E+11 37428.41 24-JAN-21:00 17.00 11.91 0.567973E+09 381.69 18-JAN-22:10 17.00 11.91
February 0.455882E+11 37314.88 03-FEB-21:00 13.00 7.33 0.514612E+09 381.67 01-FEB-22:10 13.00 7.33
March 0.505857E+11 37539.82 23-MAR-20:00 14.00 13.42 0.569832E+09 381.72 24-MAR-21:10 13.00 11.77
April 0.497317E+11 37832.76 26-APR-20:00 17.00 15.07 0.552170E+09 381.64 24-APR-21:10 17.00 15.07
May 0.514867E+11 37854.53 04-MAY-20:00 17.00 15.07 0.571435E+09 381.73 03-MAY-21:10 17.00 15.07
June 0.504977E+11 37865.34 30-JUN-20:00 16.00 15.39 0.554487E+09 381.74 22-JUN-21:10 16.00 15.39
July 0.526511E+11 38124.39 19-JUL-20:00 19.00 18.34 0.572091E+09 381.71 21-JUL-21:10 17.00 15.73
August 0.529437E+11 38082.93 18-AUG-20:00 19.00 17.66 0.573876E+09 381.71 22-AUG-21:10 16.05 14.19
September 0.504483E+11 38384.54 29-SEP-20:00 25.00 13.58 0.553570E+09 381.72 29-SEP-21:10 24.58 13.52
October 0.521578E+11 38223.91 16-OCT-20:00 21.00 13.07 0.572897E+09 381.74 23-OCT-21:10 17.00 13.47
November 0.493672E+11 37314.36 28-NOV-21:00 13.00 6.31 0.552872E+09 381.75 01-NOV-21:10 13.00 6.31
December 0.506272E+11 37569.15 05-DEC-21:00 16.00 9.09 0.569949E+09 381.73 28-DEC-22:10 9.83 3.98
                     
Annual Sum or Average 0.606699E+12         0.672577E+10        
Minimum of Months 0.455882E+11 37314.36   13.00 6.31 0.514612E+09 381.64   9.83 3.98
Maximum of Months 0.529437E+11 38384.54   25.00 18.34 0.573876E+09 381.75   24.58 15.73



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.204747E+11 12632.85 14-JAN-12:40 25.33 11.70 0.100376E+11 6462.41 18-JAN-23:10 15.67 12.73
February 0.174335E+11 10599.02 04-FEB-12:30 21.00 8.26 0.896517E+10 6460.69 01-FEB-23:49 21.00 8.26
March 0.185334E+11 10471.12 11-MAR-12:50 24.00 13.82 0.971573E+10 6460.20 23-MAR-22:10 12.83 12.37
April 0.186934E+11 9278.63 08-APR-10:35 21.67 16.37 0.956555E+10 6462.68 26-APR-22:10 16.00 15.29
May 0.184750E+11 8811.40 04-MAY-18:10 18.83 14.89 0.968125E+10 6462.65 03-MAY-22:10 18.83 14.89
June 0.185086E+11 8771.21 29-JUN-18:10 21.50 18.39 0.956626E+10 6433.47 27-JUN-22:10 21.50 18.39
July 0.200531E+11 9335.90 30-JUL-10:33 24.67 20.10 0.100603E+11 6462.67 24-JUL-22:10 24.67 20.10
August 0.208205E+11 9671.00 27-AUG-10:33 23.33 18.72 0.103366E+11 6462.68 10-AUG-22:10 23.33 18.72
September 0.203158E+11 12075.89 30-SEP-12:00 32.00 17.11 0.100134E+11 6462.61 11-SEP-22:10 32.00 17.11
October 0.220121E+11 13648.97 15-OCT-12:00 32.00 16.89 0.104600E+11 6462.64 18-OCT-21:30 14.50 14.21
November 0.201153E+11 13854.22 19-NOV-11:00 26.00 15.07 0.988115E+10 6462.43 10-NOV-22:30 26.00 15.07
December 0.209866E+11 12513.62 16-DEC-13:00 26.00 13.31 0.101789E+11 6462.37 05-DEC-23:10 26.00 13.31
                     
Annual Sum or Average 0.236422E+12         0.118462E+12        
Minimum of Months 0.174335E+11 8771.21   18.83 8.26 0.896517E+10 6433.47   12.83 8.26
Maximum of Months 0.220121E+11 13854.22   32.00 20.10 0.104600E+11 6462.68   32.00 20.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.656253E+11 33315.50 08-JAN-07:00 1.00 -0.3 0.302775E+11 19185.72 18-JAN-23:10 15.67 12.73
February 0.579087E+11 30893.74 03-FEB-21:20 11.67 6.29 0.272924E+11 19183.43 02-FEB-00:10 11.67 6.29
March 0.630287E+11 29915.33 24-MAR-21:10 13.00 11.77 0.298324E+11 19183.48 02-MAR-23:10 13.00 11.77
April 0.632939E+11 30487.90 26-APR-21:52 16.00 15.39 0.293459E+11 19186.11 26-APR-22:10 16.00 15.29
May 0.647211E+11 31535.99 04-MAY-21:53 17.00 15.07 0.302276E+11 19186.01 04-MAY-22:10 16.83 15.02
June 0.649118E+11 31561.52 30-JUN-21:52 16.10 16.10 0.297987E+11 19186.18 30-JUN-22:10 16.13 16.03
July 0.696412E+11 32990.25 19-JUL-21:52 18.00 17.35 0.311018E+11 19186.17 07-JUL-21:30 18.00 17.35
August 0.708808E+11 33772.15 18-AUG-21:10 19.00 17.66 0.314978E+11 19186.11 10-AUG-22:10 19.00 17.66
September 0.677826E+11 37786.55 29-SEP-21:10 24.58 13.52 0.303244E+11 19186.02 13-SEP-22:10 24.58 13.52
October 0.714322E+11 38344.96 16-OCT-21:10 18.33 11.06 0.315263E+11 19186.08 18-OCT-21:30 14.50 14.21
November 0.646971E+11 32274.65 19-NOV-11:33 26.00 15.32 0.298708E+11 19185.70 10-NOV-22:30 26.00 15.32
December 0.663625E+11 33179.01 05-DEC-22:10 17.17 9.45 0.307092E+11 19185.65 06-DEC-22:19 15.00 9.64
                     
Annual Sum or Average 0.790286E+12         0.361805E+12        
Minimum of Months 0.579087E+11 29915.33   1.00 -0.3 0.272924E+11 19183.43   11.67 6.29
Maximum of Months 0.714322E+11 38344.96   26.00 17.66 0.315263E+11 19186.18   26.00 17.66



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.593594E+09 2750.24 14-JAN-16:01 23.00 12.42 97964030.19 56.69 20-JAN-22:10 13.17 13.17
February 0.517917E+09 2708.39 03-FEB-16:01 20.50 10.05 88188243.95 56.69 16-FEB-22:10 12.00 11.46
March 0.538776E+09 2498.79 07-MAR-16:02 13.83 8.92 97648781.44 56.69 23-MAR-22:30 12.50 12.23
April 0.101676E+10 2543.88 11-APR-15:02 22.83 17.12 95280134.22 56.69 26-APR-21:19 16.00 15.39
May 0.970380E+09 2615.10 28-MAY-15:01 20.83 15.28 98438010.15 56.69 03-MAY-21:30 20.83 15.28
June 0.127560E+10 2637.56 18-JUN-15:02 22.83 17.78 95523091.43 56.69 27-JUN-21:49 17.00 16.37
July 0.172881E+10 2745.57 22-JUL-15:02 25.67 19.89 98869731.25 56.69 21-JUL-21:10 25.67 19.89
August 0.178121E+10 2685.55 06-AUG-15:02 24.83 20.15 98984803.44 56.69 11-AUG-21:49 17.00 16.37
September 0.145733E+10 2620.57 09-SEP-15:02 21.83 18.58 95576853.89 56.69 30-SEP-23:30 18.30 17.65
October 0.143994E+10 2888.68 13-OCT-15:01 27.67 14.85 98696420.53 56.69 19-OCT-21:10 17.00 14.51
November 0.765797E+09 2648.20 27-NOV-16:01 19.67 7.55 95115353.78 56.69 10-NOV-23:10 19.67 7.55
December 0.681136E+09 2764.27 05-DEC-16:01 22.67 12.42 98081901.71 56.69 07-DEC-22:10 12.67 12.59
                     
Annual Sum or Average 0.127673E+11         0.115837E+10        
Minimum of Months 0.517917E+09 2498.79   13.83 7.55 88188243.95 56.69   12.00 7.55
Maximum of Months 0.178121E+10 2888.68   27.67 20.15 98984803.44 56.69   25.67 19.89



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.193147E+09 2621.32 14-JAN-16:01 23.00 12.42 97301545.60 63.75 18-JAN-22:40 16.33 13.19
February 0.219153E+09 2579.95 03-FEB-16:01 20.50 10.05 87795653.43 56.69 16-FEB-22:10 12.00 11.46
March 0.279732E+09 2491.60 23-MAR-15:02 21.83 17.37 97877898.73 56.90 22-MAR-18:10 21.83 17.37
April 0.647031E+09 2599.43 23-APR-18:11 14.67 13.07 98553731.48 74.25 26-APR-21:40 16.00 15.39
May 0.726457E+09 2515.41 17-MAY-15:02 21.67 15.72 0.102779E+09 74.39 03-MAY-21:40 21.67 15.72
June 0.910085E+09 2538.84 13-JUN-15:02 21.83 16.35 0.104954E+09 78.75 30-JUN-18:10 18.83 16.43
July 0.123449E+10 2609.10 22-JUL-15:02 25.67 19.89 0.111657E+09 78.36 25-JUL-18:10 20.67 18.14
August 0.117330E+10 2602.21 06-AUG-15:02 24.83 20.15 0.110816E+09 77.39 09-AUG-21:40 18.00 17.36
September 0.897005E+09 2575.53 30-SEP-08:61 25.38 14.89 0.102023E+09 73.17 13-SEP-21:40 25.38 14.89
October 0.809604E+09 2848.89 14-OCT-08:61 27.67 13.01 0.103889E+09 75.22 16-OCT-21:40 19.33 11.10
November 0.304890E+09 2524.83 27-NOV-16:01 19.67 7.55 95041679.21 65.03 10-NOV-22:10 19.67 7.55
December 0.211099E+09 2635.48 05-DEC-16:01 22.67 12.42 97435367.74 64.41 05-DEC-22:40 17.67 9.41
                     
Annual Sum or Average 0.760599E+10         0.121012E+10        
Minimum of Months 0.193147E+09 2491.60   14.67 7.55 87795653.43 56.69   12.00 7.55
Maximum of Months 0.123449E+10 2848.89   27.67 20.15 0.111657E+09 78.75   25.38 18.14



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.424931E+09 591.66 14-JAN-12:40 25.33 11.70 0.00 0.00 01-JAN-00:10 25.33 11.70
February 0.271613E+09 519.18 02-FEB-12:40 19.33 12.36 0.00 0.00 01-FEB-00:10 19.33 12.36
March 0.199491E+09 443.09 11-MAR-13:20 24.00 13.46 0.00 0.00 01-MAR-00:10 24.00 13.46
April 0.224717E+09 315.82 08-APR-12:50 22.17 16.56 0.00 0.00 01-APR-00:10 22.17 16.56
May 0.133485E+09 250.78 02-MAY-15:03 21.50 16.24 0.00 0.00 01-MAY-00:10 21.50 16.24
June 0.177382E+09 230.86 28-JUN-15:05 22.83 18.37 0.00 0.00 01-JUN-00:10 22.83 18.37
July 0.275722E+09 259.06 18-JUL-15:03 26.00 20.07 0.00 0.00 01-JUL-00:10 26.00 20.07
August 0.371340E+09 303.94 30-AUG-13:00 24.00 18.12 0.00 0.00 01-AUG-00:10 24.00 18.12
September 0.416897E+09 563.61 30-SEP-13:10 32.00 16.98 0.00 0.00 01-SEP-00:10 32.00 16.98
October 0.540451E+09 668.68 16-OCT-12:30 35.05 17.21 0.00 0.00 01-OCT-00:10 35.05 17.21
November 0.439646E+09 630.35 19-NOV-13:00 27.00 14.96 0.00 0.00 01-NOV-00:10 27.00 14.96
December 0.485952E+09 605.49 19-DEC-13:00 26.00 11.60 0.00 0.00 01-DEC-00:10 26.00 11.60
                     
Annual Sum or Average 0.396163E+10         0.00        
Minimum of Months 0.133485E+09 230.86   19.33 11.60 0.00 0.00   19.33 11.60
Maximum of Months 0.540451E+09 668.68   35.05 20.07 0.00 0.00   35.05 20.07



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.242612E+09 878.30 15-JAN-16:01 21.83 10.39 97458600.90 67.97 18-JAN-22:00 16.00 13.03
February 0.252822E+09 838.64 03-FEB-16:01 20.50 10.05 87753681.42 57.64 13-FEB-21:19 14.67 14.08
March 0.290777E+09 841.83 10-MAR-16:02 21.67 12.40 97450220.28 57.44 29-MAR-21:00 5.80 5.00
April 0.375201E+09 863.00 01-APR-15:02 22.83 11.17 95770880.53 70.73 25-APR-21:10 14.83 14.24
May 0.435658E+09 858.77 03-MAY-15:02 21.83 15.33 99943270.38 71.02 04-MAY-21:00 17.00 15.07
June 0.470960E+09 844.56 20-JUN-15:02 21.83 15.76 0.100135E+09 73.64 30-JUN-21:00 16.10 16.10
July 0.549609E+09 869.08 18-JUL-18:02 23.33 19.62 0.105606E+09 74.96 07-JUL-21:10 23.33 19.62
August 0.516332E+09 845.11 19-AUG-15:02 25.83 18.86 0.105110E+09 72.99 07-AUG-21:00 25.83 18.86
September 0.431049E+09 829.99 01-SEP-15:02 20.67 15.86 98724764.69 70.70 22-SEP-21:00 17.00 16.37
October 0.438469E+09 962.32 14-OCT-08:61 27.67 13.01 0.102010E+09 73.38 04-OCT-21:19 27.67 13.01
November 0.283936E+09 872.84 19-NOV-09:41 25.67 13.67 94407827.15 67.40 10-NOV-22:10 25.67 13.67
December 0.246257E+09 880.10 05-DEC-16:01 22.67 12.42 97221654.08 67.85 06-DEC-22:10 14.50 9.28
                     
Annual Sum or Average 0.453368E+10         0.118159E+10        
Minimum of Months 0.242612E+09 829.99   20.50 10.05 87753681.42 57.44   5.80 5.00
Maximum of Months 0.549609E+09 962.32   27.67 19.62 0.105606E+09 74.96   27.67 19.62



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.621067E+09 2438.42 14-JAN-16:01 23.00 12.42 98276304.84 56.69 20-JAN-23:10 13.83 13.83
February 0.485295E+09 2403.80 01-FEB-09:02 22.33 11.86 88269661.18 56.69 01-FEB-22:19 13.00 11.68
March 0.527963E+09 2318.61 23-MAR-15:02 21.83 17.37 97839959.92 56.69 23-MAR-22:19 12.67 12.30
April 0.924342E+09 2346.25 30-APR-15:02 22.83 16.53 95420342.43 56.69 27-APR-00:00 22.83 16.53
May 0.841065E+09 2303.81 24-MAY-08:62 18.00 8.80 98515440.79 56.69 03-MAY-00:10 18.00 8.80
June 0.109125E+10 2285.31 30-JUN-15:02 22.95 17.86 95554417.60 56.69 27-JUN-01:10 22.95 17.86
July 0.157323E+10 2410.67 19-JUL-15:02 26.67 20.20 99027130.29 56.69 31-JUL-21:40 18.80 17.92
August 0.168633E+10 2433.56 14-AUG-15:02 25.83 19.19 99135528.49 56.69 09-AUG-21:19 25.83 19.19
September 0.126818E+10 2356.63 13-SEP-15:02 22.83 18.37 95492076.93 56.69 30-SEP-23:00 18.40 17.30
October 0.137400E+10 2591.41 14-OCT-08:61 27.67 13.01 98749340.80 56.69 01-OCT-00:20 27.67 13.01
November 0.714392E+09 2389.28 27-NOV-09:02 21.17 8.41 95264045.21 56.69 09-NOV-22:40 21.17 8.41
December 0.680746E+09 2474.12 05-DEC-09:02 24.33 12.02 98315238.89 56.69 07-DEC-22:10 12.67 12.59
                     
Annual Sum or Average 0.117878E+11         0.115986E+10        
Minimum of Months 0.485295E+09 2285.31   18.00 8.41 88269661.18 56.69   12.67 8.41
Maximum of Months 0.168633E+10 2591.41   27.67 20.20 99135528.49 56.69   27.67 19.19



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.227183E+09 2324.13 14-JAN-16:01 23.00 12.42 97401408.71 62.82 24-JAN-22:30 15.50 11.34
February 0.213083E+09 2369.17 01-FEB-09:51 24.00 12.54 87592475.42 56.69 24-FEB-00:20 13.00 11.87
March 0.289387E+09 2372.21 23-MAR-08:51 19.00 14.76 97700460.63 56.69 23-MAR-21:49 13.17 12.60
April 0.618824E+09 2551.76 26-APR-08:51 23.00 16.66 97235442.37 70.07 26-APR-21:49 16.00 15.39
May 0.659957E+09 2544.50 04-MAY-08:51 20.00 14.58 0.101273E+09 71.36 04-MAY-21:40 17.00 15.07
June 0.828443E+09 2608.02 23-JUN-08:51 21.00 15.42 0.101566E+09 72.22 30-JUN-21:49 16.08 15.88
July 0.116050E+10 2606.57 04-JUL-08:51 22.00 15.83 0.108226E+09 74.34 19-JUL-21:40 18.00 17.57
August 0.114193E+10 2462.42 14-AUG-08:51 25.00 20.20 0.108087E+09 74.17 18-AUG-21:30 19.00 17.66
September 0.783313E+09 2493.60 30-SEP-08:61 25.38 14.89 99971037.55 69.72 13-SEP-21:40 25.38 14.89
October 0.771129E+09 2896.67 17-OCT-08:21 27.50 13.36 0.103075E+09 73.28 16-OCT-21:40 27.50 13.36
November 0.292359E+09 2246.88 27-NOV-09:52 22.00 8.90 94701543.00 61.60 10-NOV-22:10 22.00 8.90
December 0.223640E+09 2541.12 05-DEC-09:41 25.67 12.88 97472611.65 64.27 05-DEC-22:40 17.67 9.41
                     
Annual Sum or Average 0.720975E+10         0.119430E+10        
Minimum of Months 0.213083E+09 2246.88   19.00 8.90 87592475.42 56.69   13.00 8.90
Maximum of Months 0.116050E+10 2896.67   27.50 20.20 0.108226E+09 74.34   27.50 17.66



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.329826E+10 1806.72 09-JAN-06:00 2.00 -0.2 0.130382E+10 823.68 20-JAN-23:10 13.83 13.83
February 0.295066E+10 1620.41 04-FEB-11:33 20.67 8.25 0.117942E+10 820.27 03-FEB-23:10 20.67 8.25
March 0.316689E+10 1627.04 12-MAR-10:33 21.33 14.69 0.128510E+10 816.65 24-MAR-21:49 13.00 11.39
April 0.335375E+10 1727.95 30-APR-10:33 25.67 16.97 0.129519E+10 832.25 27-APR-21:49 25.67 16.97
May 0.349851E+10 1735.63 04-MAY-10:35 22.00 15.73 0.135040E+10 854.92 04-MAY-22:10 16.83 15.02
June 0.358823E+10 1794.07 25-JUN-10:33 23.00 17.26 0.135314E+10 870.50 30-JUN-22:10 16.13 16.03
July 0.396218E+10 1883.94 23-JUL-10:33 25.67 20.39 0.144819E+10 885.06 31-JUL-22:10 18.65 17.88
August 0.402089E+10 1901.25 19-AUG-10:35 24.67 20.11 0.146973E+10 895.49 18-AUG-22:10 24.67 20.11
September 0.372175E+10 1974.64 30-SEP-10:35 30.57 17.23 0.138443E+10 897.69 29-SEP-22:10 30.57 17.23
October 0.391110E+10 1976.23 16-OCT-10:35 36.33 17.49 0.145004E+10 924.75 17-OCT-21:49 18.00 14.47
November 0.336621E+10 1736.41 19-NOV-11:33 26.00 15.32 0.130868E+10 860.35 01-NOV-00:10 26.00 15.32
December 0.340062E+10 1661.66 05-DEC-11:35 23.33 12.89 0.133326E+10 837.60 05-DEC-23:10 17.33 9.21
                     
Annual Sum or Average 0.422391E+11         0.161614E+11        
Minimum of Months 0.295066E+10 1620.41   2.00 -0.2 0.117942E+10 816.65   13.00 8.25
Maximum of Months 0.402089E+10 1976.23   36.33 20.39 0.146973E+10 924.75   30.57 20.11



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.492142E+09 2858.48 14-JAN-16:01 23.00 12.42 97697625.18 56.69 17-JAN-23:40 16.33 13.18
February 0.431049E+09 2809.84 03-FEB-16:01 20.50 10.05 87916187.10 56.69 01-FEB-22:10 20.50 10.05
March 0.486182E+09 2593.19 07-MAR-16:02 13.83 8.92 97435591.40 56.69 23-MAR-21:40 13.33 12.77
April 0.980936E+09 2578.95 11-APR-15:02 22.83 17.12 95213030.70 56.70 04-APR-02:30 22.83 17.12
May 0.917840E+09 2689.80 06-MAY-15:01 20.00 15.11 98365174.06 56.69 02-MAY-04:00 20.00 15.11
June 0.126295E+10 2689.83 13-JUN-15:02 21.83 16.35 95474537.71 56.69 30-JUN-00:00 17.00 16.37
July 0.174967E+10 2765.89 22-JUL-15:02 25.67 19.89 98835228.28 56.69 24-JUL-21:19 18.00 17.35
August 0.177638E+10 2713.70 06-AUG-15:02 24.83 20.15 98935469.37 56.69 02-AUG-21:19 24.83 20.15
September 0.139426E+10 2740.96 21-SEP-15:02 27.67 19.86 95507656.71 56.69 05-SEP-22:00 27.67 19.86
October 0.131845E+10 3002.77 13-OCT-15:01 27.67 14.85 98575576.15 56.69 17-OCT-21:00 18.00 14.37
November 0.630260E+09 2744.41 27-NOV-16:01 19.67 7.55 94877547.54 56.69 11-NOV-03:49 19.67 7.55
December 0.558785E+09 2872.54 05-DEC-16:01 22.67 12.42 97779121.63 56.69 18-DEC-22:49 17.17 5.90
                     
Annual Sum or Average 0.119989E+11         0.115661E+10        
Minimum of Months 0.431049E+09 2578.95   13.83 7.55 87916187.10 56.69   13.33 5.90
Maximum of Months 0.177638E+10 3002.77   27.67 20.15 98935469.37 56.70   27.67 20.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.129770E+09 2711.76 14-JAN-16:01 23.00 12.42 96740759.64 62.14 18-JAN-22:30 16.50 13.26
February 0.154835E+09 2664.01 03-FEB-16:01 20.50 10.05 87410550.36 56.70 14-FEB-22:00 13.00 12.44
March 0.228617E+09 2627.72 23-MAR-15:02 21.83 17.37 97748202.26 59.31 22-MAR-18:10 21.83 17.37
April 0.601773E+09 2739.41 23-APR-18:11 14.67 13.07 99075261.74 78.17 26-APR-18:10 18.67 15.37
May 0.685469E+09 2615.33 24-MAY-19:11 14.67 13.07 0.103276E+09 76.23 03-MAY-21:40 14.67 13.07
June 0.938720E+09 2616.97 04-JUN-19:31 15.00 13.18 0.106348E+09 83.39 30-JUN-18:10 18.83 16.43
July 0.131568E+10 2665.97 18-JUL-18:02 23.33 19.62 0.113276E+09 82.53 25-JUL-18:10 20.67 18.14
August 0.121943E+10 2617.61 06-AUG-15:02 24.83 20.15 0.112013E+09 80.63 03-AUG-18:10 24.83 20.15
September 0.855979E+09 2634.48 30-SEP-08:61 25.38 14.89 0.102136E+09 73.58 13-SEP-21:40 25.38 14.89
October 0.715000E+09 2866.61 14-OCT-08:61 27.67 13.01 0.103350E+09 74.81 16-OCT-21:40 19.33 11.10
November 0.198409E+09 2603.72 27-NOV-16:01 19.67 7.55 94508829.26 62.76 10-NOV-22:10 19.67 7.55
December 0.133414E+09 2725.09 05-DEC-16:01 22.67 12.42 96752080.85 62.40 05-DEC-22:40 17.67 9.41
                     
Annual Sum or Average 0.717709E+10         0.121263E+10        
Minimum of Months 0.129770E+09 2603.72   14.67 7.55 87410550.36 56.70   13.00 7.55
Maximum of Months 0.131568E+10 2866.61   27.67 20.15 0.113276E+09 83.39   25.38 20.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.901131E+09 1552.94 14-JAN-16:01 23.00 12.42 98742047.72 57.45 08-JAN-01:39 23.00 12.42
February 0.611329E+09 1515.19 03-FEB-16:01 20.50 10.05 88744859.40 57.19 09-FEB-01:30 7.50 6.72
March 0.524490E+09 1353.64 18-MAR-15:01 16.83 13.88 98097796.33 57.27 07-MAR-23:40 16.83 13.88
April 0.619613E+09 1456.03 30-APR-15:02 22.83 16.53 95247172.96 56.69 12-APR-21:10 22.83 16.53
May 0.436398E+09 1444.98 02-MAY-15:02 21.50 16.24 98102180.69 56.69 02-MAY-23:40 16.33 14.87
June 0.530624E+09 1401.64 30-JUN-15:02 22.95 17.86 95165816.59 56.69 19-JUN-22:40 22.95 17.86
July 0.758948E+09 1491.92 31-JUL-15:02 25.67 20.38 98675543.86 56.69 31-JUL-21:19 18.90 17.79
August 0.927351E+09 1495.79 13-AUG-15:02 24.83 19.65 98872615.29 56.69 14-AUG-21:40 18.33 17.46
September 0.939020E+09 1495.13 30-SEP-15:02 31.50 17.45 95431918.55 56.69 06-SEP-21:49 31.50 17.45
October 0.115161E+10 1600.39 14-OCT-08:61 27.67 13.01 98813456.21 56.70 17-OCT-21:10 18.00 14.87
November 0.909306E+09 1554.04 19-NOV-09:02 24.33 12.78 95633502.34 57.31 30-NOV-03:09 7.33 2.58
December 0.983628E+09 1542.08 05-DEC-09:02 24.33 12.02 98801148.74 57.53 25-DEC-03:49 6.50 5.88
                     
Annual Sum or Average 0.929345E+10         0.116033E+10        
Minimum of Months 0.436398E+09 1353.64   16.83 10.05 88744859.40 56.69   6.50 2.58
Maximum of Months 0.115161E+10 1600.39   31.50 20.38 98872615.29 57.53   31.50 17.86



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.346821E+11 18977.69 18-JAN-22:54 16.00 13.03 0.187896E+11 11348.36 18-JAN-23:10 15.67 12.73
February 0.314814E+11 18398.79 01-FEB-23:00 13.00 11.29 0.170892E+11 11347.79 08-FEB-00:20 12.67 6.27
March 0.351278E+11 18773.49 24-MAR-22:00 13.00 11.29 0.189783E+11 11347.73 13-MAR-23:19 13.00 11.29
April 0.358033E+11 19779.09 26-APR-21:52 16.00 15.39 0.184646E+11 11348.97 26-APR-22:10 16.00 15.29
May 0.375092E+11 20215.54 04-MAY-21:53 17.00 15.07 0.191282E+11 11348.92 03-MAY-22:10 17.00 15.07
June 0.379684E+11 20468.06 27-JUN-21:52 17.00 16.37 0.186179E+11 11349.09 30-JUN-22:10 16.13 16.03
July 0.403653E+11 20712.58 19-JUL-21:52 18.00 17.35 0.192020E+11 11349.08 07-JUL-21:30 18.00 17.35
August 0.402431E+11 20551.07 17-AUG-21:52 19.00 17.66 0.192669E+11 11348.97 01-AUG-22:10 19.00 17.66
September 0.374833E+11 21011.37 29-SEP-22:00 24.50 13.61 0.185377E+11 11348.82 06-SEP-22:10 24.50 13.61
October 0.384210E+11 20724.42 16-OCT-21:53 20.00 11.09 0.191099E+11 11348.86 18-OCT-21:30 14.50 14.21
November 0.342340E+11 18639.95 10-NOV-23:00 15.00 13.80 0.183254E+11 11348.33 10-NOV-22:30 15.00 13.80
December 0.346834E+11 19122.75 05-DEC-22:54 18.00 9.37 0.188683E+11 11348.80 01-DEC-00:49 18.00 9.37
                     
Annual Sum or Average 0.438002E+12         0.224378E+12        
Minimum of Months 0.314814E+11 18398.79   13.00 9.37 0.170892E+11 11347.73   12.67 6.27
Maximum of Months 0.403653E+11 21011.37   24.50 17.66 0.192669E+11 11349.09   24.50 17.66



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.380554E+11 20724.66 18-JAN-22:10 16.83 13.41 0.189725E+11 11348.37 18-JAN-23:10 15.67 12.73
February 0.346291E+11 20138.11 01-FEB-23:00 13.00 11.29 0.172375E+11 11347.81 08-FEB-00:20 12.67 6.27
March 0.386695E+11 20442.85 24-MAR-22:00 13.00 11.29 0.191494E+11 11347.88 31-MAR-03:20 6.33 5.52
April 0.391668E+11 21401.12 26-APR-21:52 16.00 15.39 0.185882E+11 11348.97 26-APR-22:10 16.00 15.29
May 0.410356E+11 21731.08 04-MAY-21:53 17.00 15.07 0.192427E+11 11348.93 03-MAY-22:10 17.00 15.07
June 0.413010E+11 21941.07 27-JUN-21:52 17.00 16.37 0.186881E+11 11349.09 30-JUN-22:10 16.13 16.03
July 0.436289E+11 22143.09 19-JUL-21:52 18.00 17.35 0.192519E+11 11349.09 07-JUL-21:30 18.00 17.35
August 0.434005E+11 21933.42 17-AUG-21:52 19.00 17.66 0.193211E+11 11348.98 01-AUG-22:10 19.00 17.66
September 0.406134E+11 22414.40 29-SEP-21:10 24.58 13.52 0.186161E+11 11348.82 06-SEP-22:10 24.58 13.52
October 0.415453E+11 22137.05 04-OCT-21:53 21.00 18.98 0.191966E+11 11348.87 18-OCT-21:30 14.50 14.21
November 0.374819E+11 20376.00 10-NOV-22:14 15.00 13.80 0.184664E+11 11348.36 10-NOV-22:30 15.00 13.80
December 0.380337E+11 20776.75 05-DEC-22:54 18.00 9.37 0.190344E+11 11349.07 01-DEC-00:49 18.00 9.37
                     
Annual Sum or Average 0.477561E+12         0.225765E+12        
Minimum of Months 0.346291E+11 20138.11   13.00 9.37 0.172375E+11 11347.81   6.33 5.52
Maximum of Months 0.436289E+11 22414.40   24.58 18.98 0.193211E+11 11349.09   24.58 17.66



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.500472E+11 26908.00 14-JAN-11:50 26.00 11.78 0.187857E+11 11319.59 14-JAN-18:19 20.33 11.24
February 0.450757E+11 26760.36 01-FEB-11:50 25.50 14.48 0.169795E+11 11319.56 25-FEB-18:19 11.00 9.85
March 0.501856E+11 27567.08 12-MAR-10:40 21.33 14.69 0.187979E+11 11319.55 25-MAR-17:19 11.00 10.47
April 0.502167E+11 28037.77 30-APR-10:33 25.67 16.97 0.182031E+11 11319.58 15-APR-17:19 25.67 16.97
May 0.518512E+11 27745.47 04-MAY-10:50 22.00 15.56 0.188123E+11 11319.58 06-MAY-17:19 17.33 14.13
June 0.512622E+11 28117.27 25-JUN-10:33 23.00 17.26 0.182175E+11 11319.62 03-JUN-17:19 23.00 17.26
July 0.540069E+11 28602.39 23-JUL-10:33 25.67 20.39 0.188244E+11 11319.65 01-JUL-17:19 25.67 20.39
August 0.540877E+11 28462.65 19-AUG-10:40 24.67 20.11 0.188324E+11 11319.65 19-AUG-17:19 23.67 17.53
September 0.511796E+11 29031.83 30-SEP-10:50 30.78 17.57 0.182148E+11 11319.64 30-SEP-17:19 25.00 17.45
October 0.525126E+11 28877.81 15-OCT-10:37 31.67 16.43 0.188182E+11 11319.60 14-OCT-17:19 31.67 16.43
November 0.488241E+11 27545.46 19-NOV-11:45 26.00 15.39 0.181926E+11 11319.53 25-NOV-18:19 13.00 11.13
December 0.500033E+11 26847.71 05-DEC-11:50 23.17 12.83 0.187944E+11 11319.54 02-DEC-18:19 23.17 12.83
                     
Annual Sum or Average 0.609253E+12         0.221473E+12        
Minimum of Months 0.450757E+11 26760.36   21.33 11.78 0.169795E+11 11319.53   11.00 9.85
Maximum of Months 0.540877E+11 29031.83   31.67 20.39 0.188324E+11 11319.65   31.67 20.39



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.703682E+10 3932.96 20-JAN-11:35 21.67 15.71 0.133921E+10 856.24 18-JAN-22:40 21.67 15.71
February 0.638029E+10 3731.19 02-FEB-11:33 19.33 10.71 0.120559E+10 834.94 01-FEB-22:40 19.33 10.71
March 0.687411E+10 3924.35 11-MAR-11:35 24.00 13.82 0.133455E+10 852.76 24-MAR-21:40 13.00 11.48
April 0.761269E+10 4057.80 30-APR-10:33 25.67 16.97 0.135064E+10 878.35 27-APR-21:40 25.67 16.97
May 0.787745E+10 4131.69 04-MAY-10:35 22.00 15.73 0.139989E+10 902.08 04-MAY-21:40 17.00 15.07
June 0.818238E+10 4208.99 30-JUN-10:35 23.33 17.95 0.141463E+10 909.71 27-JUN-21:40 23.33 17.95
July 0.903238E+10 4436.77 30-JUL-10:33 24.67 20.10 0.151288E+10 928.39 31-JUL-21:40 18.80 17.92
August 0.913794E+10 4428.78 19-AUG-10:35 24.67 20.11 0.153167E+10 933.03 18-AUG-21:40 24.67 20.11
September 0.838286E+10 4881.41 30-SEP-13:50 32.00 17.49 0.143347E+10 959.28 29-SEP-21:40 32.00 17.49
October 0.869215E+10 4745.49 16-OCT-12:20 35.37 17.35 0.148763E+10 966.19 16-OCT-21:40 19.33 11.10
November 0.732180E+10 4136.44 19-NOV-11:33 26.00 15.32 0.132369E+10 876.41 01-NOV-00:10 26.00 15.32
December 0.727002E+10 3986.35 19-DEC-11:35 25.00 11.16 0.134898E+10 867.72 05-DEC-22:40 25.00 11.16
                     
Annual Sum or Average 0.938009E+11         0.166828E+11        
Minimum of Months 0.638029E+10 3731.19   19.33 10.71 0.120559E+10 834.94   13.00 10.71
Maximum of Months 0.913794E+10 4881.41   35.37 20.11 0.153167E+10 966.19   32.00 20.11



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 620840.72 143.63 30-MAR-06:07 5.58
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 620840.72      
Minimum of Months 0.00 0.00   5.58
Maximum of Months 620840.72 143.63   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 60717361.68 935.90 29-JAN-16:05 13.83
February 37592370.77 1072.64 25-FEB-16:03 11.00
March 75940628.32 1522.71 30-MAR-08:62 9.50
April 9727194.08 877.36 06-APR-18:05 13.00
May 5938615.35 1346.94 12-MAY-15:04 15.83
June 1570353.79 822.60 11-JUN-15:05 18.00
July 1302137.15 770.20 05-JUL-08:05 20.17
August 1066620.98 690.15 08-AUG-08:05 19.13
September 1434446.50 688.13 22-SEP-18:05 18.00
October 1969197.36 855.88 02-OCT-18:05 19.00
November 9970706.03 1006.40 11-NOV-16:04 16.83
December 36061663.12 1107.10 17-DEC-16:04 16.83
         
Annual Sum or Average 0.243291E+09      
Minimum of Months 1066620.98 688.13   9.50
Maximum of Months 75940628.32 1522.71   20.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.147260E+09 1513.86 03-JAN-09:02 11.33
February 65825780.17 1296.08 25-FEB-16:03 11.00
March 0.103959E+09 1523.69 30-MAR-08:62 9.50
April 11046663.38 884.54 06-APR-18:05 13.00
May 4927747.67 986.83 08-MAY-15:05 17.00
June 644415.96 891.98 11-JUN-15:05 18.00
July 89040.18 291.91 13-JUL-08:54 22.00
August 73487.11 207.47 11-AUG-08:55 21.00
September 799220.16 708.31 03-SEP-08:53 20.00
October 1191723.68 914.34 17-OCT-08:24 27.50
November 33521483.18 901.93 24-NOV-16:03 15.83
December 0.105134E+09 1498.63 14-DEC-09:02 12.33
         
Annual Sum or Average 0.474474E+09      
Minimum of Months 73487.11 207.47   9.50
Maximum of Months 0.147260E+09 1523.69   27.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1047650.80 349.93 03-JAN-16:03 16.33
February 722618.13 451.09 05-FEB-16:04 15.83
March 845466.13 373.21 01-MAR-16:04 16.83
April 228701.42 300.59 18-APR-15:06 16.00
May 164869.78 208.81 08-MAY-15:07 17.00
June 63849.00 128.32 02-JUN-08:54 19.00
July 3154.51 34.71 08-JUL-08:57 19.00
August 12973.25 114.49 22-AUG-08:54 19.00
September 102819.54 226.97 20-SEP-08:54 18.00
October 114428.99 186.40 13-OCT-08:54 24.00
November 756220.39 450.09 14-NOV-16:04 15.83
December 1036747.64 449.72 31-DEC-16:04 15.67
         
Annual Sum or Average 5099499.57      
Minimum of Months 3154.51 34.71   15.67
Maximum of Months 1047650.80 451.09   24.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 59890643.35 826.69 18-JAN-19:05 18.83
February 46215068.82 1035.40 25-FEB-19:03 10.83
March 87320127.32 1457.79 28-MAR-08:62 9.33
April 9292714.46 1068.49 22-APR-15:04 16.83
May 7616827.60 992.10 12-MAY-15:04 15.83
June 1034112.76 785.81 11-JUN-15:05 18.00
July 76393.20 444.02 09-JUL-18:05 17.83
August 30450.05 304.50 21-AUG-18:05 16.83
September 1363138.21 615.17 19-SEP-18:04 15.67
October 1154830.46 641.67 02-OCT-18:05 19.00
November 14213067.41 816.43 11-NOV-16:04 16.83
December 42468310.66 911.48 10-DEC-16:05 14.00
         
Annual Sum or Average 0.270676E+09      
Minimum of Months 30450.05 304.50   9.33
Maximum of Months 87320127.32 1457.79   19.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.140937E+09 1445.65 02-JAN-19:02 8.67
February 84541985.03 1292.26 25-FEB-16:03 11.00
March 0.118849E+09 1449.35 28-MAR-08:62 9.33
April 11451696.66 907.13 22-APR-15:04 16.83
May 6792838.61 944.88 08-MAY-15:05 17.00
June 517444.25 829.66 11-JUN-15:05 18.00
July 69331.70 247.77 11-JUL-21:55 16.00
August 21797.07 146.33 21-AUG-20:15 15.00
September 696776.24 407.22 26-SEP-21:55 17.00
October 1140522.74 528.70 24-OCT-15:04 19.00
November 47946260.60 1038.41 29-NOV-16:04 16.83
December 0.114542E+09 1438.32 12-DEC-16:02 12.00
         
Annual Sum or Average 0.527506E+09      
Minimum of Months 21797.07 146.33   8.67
Maximum of Months 0.140937E+09 1449.35   19.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.161941E+09 1488.78 02-JAN-09:02 13.00
February 0.121298E+09 1746.31 25-FEB-16:03 11.00
March 0.177579E+09 1842.68 30-MAR-08:62 9.50
April 27265295.71 757.91 06-APR-18:05 13.00
May 20919453.62 1415.77 12-MAY-15:04 15.83
June 2135117.82 808.59 13-JUN-08:03 19.33
July 1209926.47 719.17 04-JUL-08:05 19.50
August 1050438.88 655.50 03-AUG-08:05 21.17
September 1352700.18 743.74 21-SEP-18:05 19.00
October 8786394.25 1011.43 23-OCT-15:04 17.00
November 60552276.27 863.10 11-NOV-16:04 16.83
December 0.133907E+09 1153.31 12-DEC-19:03 9.67
         
Annual Sum or Average 0.717996E+09      
Minimum of Months 1050438.88 655.50   9.50
Maximum of Months 0.177579E+09 1842.68   21.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.331335E+09 1833.79 03-JAN-09:02 11.33
February 0.196863E+09 1793.14 09-FEB-09:02 11.90
March 0.232918E+09 1840.70 30-MAR-08:62 9.50
April 30020383.24 1242.92 01-APR-08:62 15.67
May 16799858.40 1223.86 12-MAY-15:04 15.83
June 743248.32 853.41 11-JUN-15:05 18.00
July 63748.14 339.40 06-JUL-08:54 20.00
August 171433.37 403.55 23-AUG-08:53 21.00
September 1067354.33 695.74 11-SEP-08:53 21.00
October 12895223.20 1060.70 24-OCT-15:04 19.00
November 0.136963E+09 1541.20 05-NOV-08:62 11.33
December 0.285635E+09 1815.02 15-DEC-09:02 12.33
         
Annual Sum or Average 0.124548E+10      
Minimum of Months 63748.14 339.40   9.50
Maximum of Months 0.331335E+09 1840.70   21.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 6524339.97 421.30 25-JAN-16:05 15.00
February 7775548.98 475.61 13-FEB-16:05 16.83
March 30131338.68 919.77 29-MAR-08:62 8.00
April 3840482.75 486.01 01-APR-18:05 17.83
May 4811891.45 944.92 12-MAY-15:04 15.83
June 1197803.92 498.79 14-JUN-18:05 17.83
July 607297.43 396.04 05-JUL-18:05 17.83
August 369631.03 326.08 09-AUG-08:05 19.50
September 642610.85 331.02 22-SEP-18:05 18.00
October 476306.52 330.50 21-OCT-18:05 16.83
November 309351.55 309.31 09-NOV-09:05 18.17
December 4133683.56 287.87 12-DEC-19:05 9.67
         
Annual Sum or Average 60820286.70      
Minimum of Months 309351.55 287.87   8.00
Maximum of Months 30131338.68 944.92   19.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:03 13.23
March 0.00 0.00 01-MAR-00:03 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:05 15.20
June 0.00 0.00 01-JUN-00:05 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:05 18.07
September 0.00 0.00 01-SEP-00:05 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:05 14.77
December 0.00 0.00 01-DEC-00:03 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.866285E+10 8344.11 02-JAN-20:10 0.121516E+11 9632.53 02-JAN-20:10
February 0.782177E+10 8344.11 01-FEB-20:10 0.109726E+11 9632.53 01-FEB-20:10
March 0.868956E+10 8344.11 01-MAR-20:10 0.121771E+11 9632.53 01-MAR-20:10
April 0.836914E+10 8344.11 03-APR-19:10 0.117446E+11 9632.53 03-APR-19:10
May 0.867788E+10 8344.11 01-MAY-19:10 0.121662E+11 9632.53 01-MAY-19:10
June 0.840753E+10 8344.11 01-JUN-19:10 0.117829E+11 9632.53 01-JUN-19:10
July 0.863949E+10 8344.11 03-JUL-19:10 0.121279E+11 9632.53 03-JUL-19:10
August 0.869290E+10 8344.11 01-AUG-19:10 0.121808E+11 9632.53 01-AUG-19:10
September 0.837248E+10 8344.11 01-SEP-19:10 0.117482E+11 9632.53 01-SEP-19:10
October 0.865952E+10 8344.11 02-OCT-19:10 0.121479E+11 9632.53 02-OCT-19:10
November 0.840085E+10 8344.11 01-NOV-19:10 0.117774E+11 9632.53 01-NOV-19:10
December 0.863949E+10 8344.11 01-DEC-20:10 0.121279E+11 9632.53 01-DEC-20:10
             
Annual Sum or Average 0.102033E+12     0.143105E+12    
Minimum of Months 0.782177E+10 8344.11   0.109726E+11 9632.53  
Maximum of Months 0.869290E+10 8344.11   0.121808E+11 9632.53  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.478695E+09 461.08 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.432218E+09 461.08 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.480171E+09 461.08 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.462465E+09 461.08 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.479525E+09 461.08 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.464586E+09 461.08 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.477404E+09 461.08 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.480355E+09 461.08 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.462650E+09 461.08 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.478511E+09 461.08 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.464217E+09 461.08 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.477404E+09 461.08 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.563820E+10     0.101856E+11    
Minimum of Months 0.432218E+09 461.08   0.780982E+09 685.60  
Maximum of Months 0.480355E+09 461.08   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.554331E+09 533.93 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.500510E+09 533.93 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.556040E+09 533.93 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.535537E+09 533.93 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.555292E+09 533.93 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.537993E+09 533.93 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.552836E+09 533.93 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.556253E+09 533.93 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.535750E+09 533.93 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.554117E+09 533.93 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.537566E+09 533.93 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.552836E+09 533.93 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.652906E+10     0.117950E+11    
Minimum of Months 0.500510E+09 533.93   0.904380E+09 793.93  
Maximum of Months 0.556253E+09 533.93   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.639281E+09 615.76 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.577212E+09 615.76 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.641251E+09 615.76 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.617606E+09 615.76 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.640389E+09 615.76 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.620439E+09 615.76 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.637557E+09 615.76 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.641498E+09 615.76 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.617853E+09 615.76 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.639035E+09 615.76 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.619946E+09 615.76 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.637557E+09 615.76 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.752962E+10     0.124712E+11    
Minimum of Months 0.577212E+09 615.76   0.956227E+09 839.45  
Maximum of Months 0.641498E+09 615.76   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.142601E+09 137.35 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.128756E+09 137.35 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.143041E+09 137.35 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.137766E+09 137.35 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.142848E+09 137.35 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.138398E+09 137.35 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.142217E+09 137.35 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.143096E+09 137.35 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.137821E+09 137.35 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.142546E+09 137.35 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.138288E+09 137.35 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.142217E+09 137.35 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.167960E+10     0.359760E+10    
Minimum of Months 0.128756E+09 137.35   0.275845E+09 242.16  
Maximum of Months 0.143096E+09 137.35   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.374392E+09 360.62 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.338042E+09 360.62 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.375546E+09 360.62 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.361698E+09 360.62 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.375041E+09 360.62 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.363357E+09 360.62 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.373382E+09 360.62 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.375690E+09 360.62 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.361842E+09 360.62 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.374247E+09 360.62 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.363068E+09 360.62 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.373382E+09 360.62 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.440969E+10     0.679355E+11    
Minimum of Months 0.338042E+09 360.62   0.520895E+10 4572.80  
Maximum of Months 0.375690E+09 360.62   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.108210E+10 1416.11 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.948803E+09 1416.11 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.103327E+10 1416.11 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.938974E+09 1416.11 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.918358E+09 1416.11 01-MAY-19:10 0.121917E+10 965.27 01-MAY-19:10
June 0.876102E+09 1416.11 01-JUN-19:10 0.118076E+10 965.27 01-JUN-19:10
July 0.908835E+09 1416.11 03-JUL-19:10 0.121533E+10 965.27 03-JUL-19:10
August 0.947850E+09 1416.11 01-AUG-19:10 0.122063E+10 965.27 01-AUG-19:10
September 0.988665E+09 1416.11 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.105520E+10 1416.11 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.103508E+10 1416.11 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.107466E+10 1416.11 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.118079E+11     0.143405E+11    
Minimum of Months 0.876102E+09 1416.11   0.109956E+10 965.27  
Maximum of Months 0.108210E+10 1416.11   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.948628E+10 9580.84 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.853408E+10 9580.84 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.946565E+10 9580.84 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.905604E+10 9580.84 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.933467E+10 9580.84 01-MAY-19:10 0.126672E+11 10029.21 01-MAY-19:10
June 0.903408E+10 9580.84 01-JUN-19:10 0.122682E+11 10029.21 01-JUN-19:10
July 0.928823E+10 9580.84 03-JUL-19:10 0.126273E+11 10029.21 03-JUL-19:10
August 0.937932E+10 9580.84 01-AUG-19:10 0.126824E+11 10029.21 01-AUG-19:10
September 0.911699E+10 9580.84 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.946287E+10 9580.84 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.917997E+10 9580.84 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.945373E+10 9580.84 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.110792E+12     0.148998E+12    
Minimum of Months 0.853408E+10 9580.84   0.114244E+11 10029.21  
Maximum of Months 0.948628E+10 9580.84   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.118113E+09 106.87 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.106667E+09 106.87 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.117174E+09 106.87 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.114438E+09 106.87 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.117643E+09 106.87 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.113531E+09 106.87 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.118566E+09 106.87 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.117174E+09 106.87 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.114469E+09 106.87 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.118097E+09 106.87 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.113984E+09 106.87 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.118582E+09 106.87 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.138844E+10     0.307301E+10    
Minimum of Months 0.106667E+09 106.87   0.235798E+09 237.06  
Maximum of Months 0.118582E+09 106.87   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.118099E+09 106.85 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.106655E+09 106.85 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.117160E+09 106.85 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.114425E+09 106.85 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.117629E+09 106.85 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.113517E+09 106.85 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.118553E+09 106.85 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.117160E+09 106.85 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.114456E+09 106.85 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.118083E+09 106.85 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.113971E+09 106.85 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.118568E+09 106.85 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.138828E+10     0.307265E+10    
Minimum of Months 0.106655E+09 106.85   0.235770E+09 237.03  
Maximum of Months 0.118568E+09 106.85   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 74229181.22 67.16 01-JAN-19:10 0.255708E+09 232.19 01-JAN-08:09
February 67036196.95 67.16 01-FEB-20:10 0.230956E+09 232.19 01-FEB-07:10
March 73639243.64 67.16 01-MAR-20:10 0.255355E+09 232.19 01-MAR-07:10
April 71920171.51 67.16 01-APR-18:10 0.247516E+09 232.19 01-APR-07:10
May 73934212.43 67.16 01-MAY-19:10 0.255532E+09 232.19 01-MAY-06:10
June 71349576.37 67.16 01-JUN-19:10 0.247163E+09 232.19 01-JUN-06:10
July 74514478.79 67.16 01-JUL-18:10 0.255885E+09 232.19 01-JUL-07:10
August 73639243.64 67.16 01-AUG-19:10 0.255355E+09 232.19 01-AUG-06:10
September 71939513.95 67.16 01-SEP-19:10 0.247516E+09 232.19 01-SEP-06:10
October 74219510.00 67.16 01-OCT-18:10 0.255708E+09 232.19 01-OCT-07:10
November 71634873.94 67.16 01-NOV-19:10 0.247340E+09 232.19 01-NOV-06:10
December 74524150.01 67.16 01-DEC-20:10 0.255885E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.872580E+09     0.300992E+10    
Minimum of Months 67036196.95 67.16   0.230956E+09 232.19  
Maximum of Months 74524150.01 67.16   0.255885E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 74249479.06 67.18 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 67054527.88 67.18 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 73659380.16 67.18 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 71939837.95 67.18 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 73954429.61 67.18 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 71369086.78 67.18 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 74534854.64 67.18 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 73659380.16 67.18 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 71959185.68 67.18 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 74239805.19 67.18 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 71654462.37 67.18 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 74544528.51 67.18 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.872819E+09     0.301074E+10    
Minimum of Months 67054527.88 67.18   0.231020E+09 232.26  
Maximum of Months 74544528.51 67.18   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.118113E+09 106.87 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.106667E+09 106.87 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.117174E+09 106.87 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.114438E+09 106.87 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.117643E+09 106.87 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.113531E+09 106.87 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.118566E+09 106.87 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.117174E+09 106.87 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.114469E+09 106.87 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.118097E+09 106.87 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.113984E+09 106.87 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.118582E+09 106.87 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.138844E+10     0.307301E+10    
Minimum of Months 0.106667E+09 106.87   0.235798E+09 237.06  
Maximum of Months 0.118582E+09 106.87   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.118099E+09 106.85 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.106655E+09 106.85 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.117160E+09 106.85 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.114425E+09 106.85 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.117629E+09 106.85 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.113517E+09 106.85 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.118553E+09 106.85 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.117160E+09 106.85 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.114456E+09 106.85 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.118083E+09 106.85 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.113971E+09 106.85 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.118568E+09 106.85 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.138828E+10     0.307265E+10    
Minimum of Months 0.106655E+09 106.85   0.235770E+09 237.03  
Maximum of Months 0.118568E+09 106.85   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.108388E+10 1044.00 02-JAN-20:10 0.00 0.00
February 0.978647E+09 1044.00 01-FEB-20:10 0.00 0.00
March 0.108722E+10 1044.00 01-MAR-20:10 0.00 0.00
April 0.104713E+10 1044.00 03-APR-19:10 0.00 0.00
May 0.108576E+10 1044.00 01-MAY-19:10 0.00 0.00
June 0.105194E+10 1044.00 01-JUN-19:10 0.00 0.00
July 0.108096E+10 1044.00 03-JUL-19:10 0.00 0.00
August 0.108764E+10 1044.00 01-AUG-19:10 0.00 0.00
September 0.104755E+10 1044.00 01-SEP-19:10 0.00 0.00
October 0.108346E+10 1044.00 02-OCT-19:10 0.00 0.00
November 0.105110E+10 1044.00 01-NOV-19:10 0.00 0.00
December 0.108096E+10 1044.00 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.127663E+11     0.00 0.00
Minimum of Months 0.978647E+09 1044.00   0.00 0.00
Maximum of Months 0.108764E+10 1044.00   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.118113E+09 106.87 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.106667E+09 106.87 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.117174E+09 106.87 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.114438E+09 106.87 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.117643E+09 106.87 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.113531E+09 106.87 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.118566E+09 106.87 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.117174E+09 106.87 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.114469E+09 106.87 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.118097E+09 106.87 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.113984E+09 106.87 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.118582E+09 106.87 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.138844E+10     0.307301E+10    
Minimum of Months 0.106667E+09 106.87   0.235798E+09 237.06  
Maximum of Months 0.118582E+09 106.87   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.118099E+09 106.85 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.106655E+09 106.85 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.117160E+09 106.85 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.114425E+09 106.85 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.117629E+09 106.85 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.113517E+09 106.85 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.118553E+09 106.85 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.117160E+09 106.85 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.114456E+09 106.85 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.118083E+09 106.85 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.113971E+09 106.85 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.118568E+09 106.85 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.138828E+10     0.307265E+10    
Minimum of Months 0.106655E+09 106.85   0.235770E+09 237.03  
Maximum of Months 0.118568E+09 106.85   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 74249479.06 67.18 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 67054527.88 67.18 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 73659380.16 67.18 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 71939837.95 67.18 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 73954429.61 67.18 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 71369086.78 67.18 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 74534854.64 67.18 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 73659380.16 67.18 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 71959185.68 67.18 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 74239805.19 67.18 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 71654462.37 67.18 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 74544528.51 67.18 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.872819E+09     0.301074E+10    
Minimum of Months 67054527.88 67.18   0.231020E+09 232.26  
Maximum of Months 74544528.51 67.18   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.229342E+10 2486.81 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.202878E+10 2486.81 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.221640E+10 2486.81 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.206608E+10 2486.81 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.207546E+10 2486.81 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.199013E+10 2486.81 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.205834E+10 2486.81 03-JUL-19:10 0.149358E+11 6747.90 01-JUL-06:10
August 0.211343E+10 2486.81 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.212400E+10 2486.81 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.226395E+10 2486.81 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.220824E+10 2486.81 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.229443E+10 2486.81 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.257326E+11     0.175857E+12    
Minimum of Months 0.199013E+10 2486.81   0.134904E+11 6747.90  
Maximum of Months 0.229443E+10 2486.81   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.229342E+10 2486.81 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.202878E+10 2486.81 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.221640E+10 2486.81 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.206608E+10 2486.81 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.207546E+10 2486.81 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.199013E+10 2486.81 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.205834E+10 2486.81 03-JUL-19:10 0.149358E+11 6747.90 01-JUL-06:10
August 0.211343E+10 2486.81 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.212400E+10 2486.81 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.226395E+10 2486.81 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.220824E+10 2486.81 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.229443E+10 2486.81 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.257326E+11     0.175857E+12    
Minimum of Months 0.199013E+10 2486.81   0.134904E+11 6747.90  
Maximum of Months 0.229443E+10 2486.81   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.101925E+10 981.75 02-JAN-20:10 0.360126E+11 16179.04 01-JAN-07:10
February 0.920291E+09 981.75 01-FEB-20:10 0.325275E+11 16179.04 01-FEB-07:10
March 0.102239E+10 981.75 01-MAR-20:10 0.360126E+11 16179.04 01-MAR-07:10
April 0.984694E+09 981.75 03-APR-19:10 0.348509E+11 16179.04 01-APR-06:10
May 0.102102E+10 981.75 01-MAY-19:10 0.360126E+11 16179.04 01-MAY-06:10
June 0.989210E+09 981.75 01-JUN-19:10 0.348509E+11 16179.04 01-JUN-06:10
July 0.101650E+10 981.75 03-JUL-19:10 0.360126E+11 16179.04 01-JUL-06:10
August 0.102279E+10 981.75 01-AUG-19:10 0.360126E+11 16179.04 01-AUG-06:10
September 0.985086E+09 981.75 01-SEP-19:10 0.348509E+11 16179.04 01-SEP-06:10
October 0.101886E+10 981.75 02-OCT-19:10 0.360126E+11 16179.04 01-OCT-06:10
November 0.988424E+09 981.75 01-NOV-19:10 0.348509E+11 16179.04 01-NOV-06:10
December 0.101650E+10 981.75 01-DEC-20:10 0.360126E+11 16179.04 01-DEC-07:10
             
Annual Sum or Average 0.120050E+11     0.424019E+12    
Minimum of Months 0.920291E+09 981.75   0.325275E+11 16179.04  
Maximum of Months 0.102279E+10 981.75   0.360126E+11 16179.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.114712E+10 1104.91 02-JAN-20:10 0.00 0.00
February 0.103575E+10 1104.91 01-FEB-20:10 0.00 0.00
March 0.115066E+10 1104.91 01-MAR-20:10 0.00 0.00
April 0.110823E+10 1104.91 03-APR-19:10 0.00 0.00
May 0.114911E+10 1104.91 01-MAY-19:10 0.00 0.00
June 0.111331E+10 1104.91 01-JUN-19:10 0.00 0.00
July 0.114403E+10 1104.91 03-JUL-19:10 0.00 0.00
August 0.115110E+10 1104.91 01-AUG-19:10 0.00 0.00
September 0.110867E+10 1104.91 01-SEP-19:10 0.00 0.00
October 0.114668E+10 1104.91 02-OCT-19:10 0.00 0.00
November 0.111243E+10 1104.91 01-NOV-19:10 0.00 0.00
December 0.114403E+10 1104.91 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.135111E+11     0.00 0.00
Minimum of Months 0.103575E+10 1104.91   0.00 0.00
Maximum of Months 0.115110E+10 1104.91   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.866285E+10 0.121516E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.782177E+10 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.868956E+10 0.121771E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.836914E+10 0.117446E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.867788E+10 0.121662E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.840753E+10 0.117829E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.863949E+10 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.869290E+10 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.837248E+10 0.117482E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.865952E+10 0.121479E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.840085E+10 0.117774E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.863949E+10 0.121279E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.102033E+12 0.143105E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.782177E+10 0.109726E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.869290E+10 0.121808E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.478695E+09 0.864900E+09 0.00 0.00 0.00 0.00 1138040.04 0.285084E+09
February 0.179968E+10 0.432218E+09 0.780982E+09 0.00 0.00 0.00 0.00 80360.53 0.245712E+09
March 0.199990E+10 0.480171E+09 0.866718E+09 0.00 0.00 0.00 0.00 1244.27 0.285676E+09
April 0.192973E+10 0.462465E+09 0.835931E+09 0.00 0.00 0.00 0.00 1482231.09 0.198292E+09
May 0.199475E+10 0.479525E+09 0.865939E+09 0.00 0.00 0.00 0.00 248859.14 0.184830E+09
June 0.193394E+10 0.464586E+09 0.838659E+09 0.00 0.00 0.00 0.00 3847722.96 0.122186E+09
July 0.199054E+10 0.477404E+09 0.863211E+09 0.00 0.00 0.00 0.00 10929815.57 90488341.91
August 0.199896E+10 0.480355E+09 0.866978E+09 0.00 0.00 0.00 0.00 9140373.48 92821567.37
September 0.192879E+10 0.462650E+09 0.836191E+09 0.00 0.00 0.00 0.00 8304375.89 0.126917E+09
October 0.199148E+10 0.478511E+09 0.864640E+09 0.00 0.00 0.00 0.00 14238175.16 0.133503E+09
November 0.192552E+10 0.464217E+09 0.838269E+09 0.00 0.00 0.00 0.00 626410.78 0.242554E+09
December 0.199054E+10 0.477404E+09 0.863211E+09 0.00 0.00 0.00 0.00 399978.11 0.275657E+09
                   
Annual Sum or Average 0.234744E+11 0.563820E+10 0.101856E+11 0.00 0.00 0.00 0.00 50437587.03 0.228372E+10
Minimum of Months 0.179968E+10 0.432218E+09 0.780982E+09 0.00 0.00 0.00 0.00 1244.27 90488341.91
Maximum of Months 0.199990E+10 0.480355E+09 0.866978E+09 0.00 0.00 0.00 0.00 14238175.16 0.285676E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.554331E+09 0.100156E+10 0.00 0.00 0.00 0.00 865659.72 0.117029E+09
February 0.208403E+10 0.500510E+09 0.904380E+09 0.00 0.00 0.00 0.00 119424.62 0.103005E+09
March 0.231589E+10 0.556040E+09 0.100366E+10 0.00 0.00 0.00 0.00 154029.13 0.120297E+09
April 0.223463E+10 0.535537E+09 0.968011E+09 0.00 0.00 0.00 0.00 882612.88 88548389.49
May 0.230993E+10 0.555292E+09 0.100276E+10 0.00 0.00 0.00 0.00 136997.57 86647476.96
June 0.223950E+10 0.537993E+09 0.971170E+09 0.00 0.00 0.00 0.00 933910.42 61645745.42
July 0.230505E+10 0.552836E+09 0.999601E+09 0.00 0.00 0.00 0.00 3658433.52 47954177.00
August 0.231480E+10 0.556253E+09 0.100396E+10 0.00 0.00 0.00 0.00 4058804.17 46897597.08
September 0.223354E+10 0.535750E+09 0.968312E+09 0.00 0.00 0.00 0.00 3371051.10 58038172.97
October 0.230614E+10 0.554117E+09 0.100126E+10 0.00 0.00 0.00 0.00 6721307.38 60470208.27
November 0.222975E+10 0.537566E+09 0.970719E+09 0.00 0.00 0.00 0.00 597312.86 0.101989E+09
December 0.230505E+10 0.552836E+09 0.999601E+09 0.00 0.00 0.00 0.00 687373.13 0.114112E+09
                   
Annual Sum or Average 0.271834E+11 0.652906E+10 0.117950E+11 0.00 0.00 0.00 0.00 22186916.50 0.100663E+10
Minimum of Months 0.208403E+10 0.500510E+09 0.904380E+09 0.00 0.00 0.00 0.00 119424.62 46897597.08
Maximum of Months 0.231589E+10 0.556253E+09 0.100396E+10 0.00 0.00 0.00 0.00 6721307.38 0.120297E+09



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.639281E+09 0.105898E+10 0.00 0.00 0.00 0.00 2915055.56 0.250550E+09
February 0.440737E+09 0.577212E+09 0.956227E+09 0.00 0.00 0.00 0.00 484598.11 0.220425E+09
March 0.489771E+09 0.641251E+09 0.106120E+10 0.00 0.00 0.00 0.00 883660.34 0.260520E+09
April 0.472586E+09 0.617606E+09 0.102351E+10 0.00 0.00 0.00 0.00 2919874.89 0.188456E+09
May 0.488511E+09 0.640389E+09 0.106025E+10 0.00 0.00 0.00 0.00 476033.95 0.189773E+09
June 0.473617E+09 0.620439E+09 0.102685E+10 0.00 0.00 0.00 0.00 1935419.20 0.136213E+09
July 0.487480E+09 0.637557E+09 0.105691E+10 0.00 0.00 0.00 0.00 8138987.69 0.104921E+09
August 0.489542E+09 0.641498E+09 0.106152E+10 0.00 0.00 0.00 0.00 9903235.14 99681927.08
September 0.472357E+09 0.617853E+09 0.102382E+10 0.00 0.00 0.00 0.00 8770809.77 0.122501E+09
October 0.487709E+09 0.639035E+09 0.105866E+10 0.00 0.00 0.00 0.00 17139139.28 0.130304E+09
November 0.471555E+09 0.619946E+09 0.102637E+10 0.00 0.00 0.00 0.00 2238373.15 0.217695E+09
December 0.487480E+09 0.637557E+09 0.105691E+10 0.00 0.00 0.00 0.00 2941333.08 0.242996E+09
                   
Annual Sum or Average 0.574883E+10 0.752962E+10 0.124712E+11 0.00 0.00 0.00 0.00 58746520.16 0.216404E+10
Minimum of Months 0.440737E+09 0.577212E+09 0.956227E+09 0.00 0.00 0.00 0.00 476033.95 99681927.08
Maximum of Months 0.489771E+09 0.641498E+09 0.106152E+10 0.00 0.00 0.00 0.00 17139139.28 0.260520E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.142601E+09 0.305485E+09 0.00 0.00 0.00 0.00 1656330.81 0.142784E+09
February 0.339028E+09 0.128756E+09 0.275845E+09 0.00 0.00 0.00 0.00 278855.61 0.125303E+09
March 0.376747E+09 0.143041E+09 0.306128E+09 0.00 0.00 0.00 0.00 494868.03 0.148365E+09
April 0.363528E+09 0.137766E+09 0.295253E+09 0.00 0.00 0.00 0.00 1673107.84 0.106695E+09
May 0.375778E+09 0.142848E+09 0.305852E+09 0.00 0.00 0.00 0.00 285323.43 0.107098E+09
June 0.364321E+09 0.138398E+09 0.296217E+09 0.00 0.00 0.00 0.00 1191030.29 76406729.59
July 0.374985E+09 0.142217E+09 0.304889E+09 0.00 0.00 0.00 0.00 4830480.88 58386939.04
August 0.376571E+09 0.143096E+09 0.306219E+09 0.00 0.00 0.00 0.00 5844063.72 55444524.25
September 0.363352E+09 0.137821E+09 0.295345E+09 0.00 0.00 0.00 0.00 5096793.20 68725786.15
October 0.375161E+09 0.142546E+09 0.305393E+09 0.00 0.00 0.00 0.00 9893059.07 73050870.63
November 0.362735E+09 0.138288E+09 0.296079E+09 0.00 0.00 0.00 0.00 1269652.72 0.123550E+09
December 0.374985E+09 0.142217E+09 0.304889E+09 0.00 0.00 0.00 0.00 1659683.21 0.138141E+09
                   
Annual Sum or Average 0.442217E+10 0.167960E+10 0.359760E+10 0.00 0.00 0.00 0.00 34173248.80 0.122395E+10
Minimum of Months 0.339028E+09 0.128756E+09 0.275845E+09 0.00 0.00 0.00 0.00 278855.61 55444524.25
Maximum of Months 0.376747E+09 0.143096E+09 0.306219E+09 0.00 0.00 0.00 0.00 9893059.07 0.148365E+09



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.374392E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 3328226.36 0.382372E+09
February 0.139600E+10 0.338042E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 501939.70 0.337854E+09
March 0.155131E+10 0.375546E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 700869.73 0.400033E+09
April 0.149688E+10 0.361698E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 3553672.92 0.285644E+09
May 0.154732E+10 0.375041E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 723351.39 0.281997E+09
June 0.150015E+10 0.363357E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 4769331.97 0.194433E+09
July 0.154405E+10 0.373382E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 17147574.70 0.142926E+09
August 0.155059E+10 0.375690E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 20514847.04 0.137188E+09
September 0.149615E+10 0.361842E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 14330258.62 0.173282E+09
October 0.154478E+10 0.374247E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 26994328.15 0.181503E+09
November 0.149361E+10 0.363068E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 2680939.64 0.325613E+09
December 0.154405E+10 0.373382E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 2975944.47 0.367376E+09
                   
Annual Sum or Average 0.182090E+11 0.440969E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 98221284.68 0.321022E+10
Minimum of Months 0.139600E+10 0.338042E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 501939.70 0.137188E+09
Maximum of Months 0.155131E+10 0.375690E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 26994328.15 0.400033E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.108210E+10 0.121771E+10 0.00 0.00 0.00 0.00 2268807.76 0.705224E+09
February 0.236489E+11 0.948803E+09 0.109956E+10 0.00 0.00 0.00 0.00 164822.91 0.610596E+09
March 0.262800E+11 0.103327E+10 0.122027E+10 0.00 0.00 0.00 0.00 652.78 0.702079E+09
April 0.253579E+11 0.938974E+09 0.117692E+10 0.00 0.00 0.00 0.00 2989083.85 0.508051E+09
May 0.262123E+11 0.918358E+09 0.121917E+10 0.00 0.00 0.00 0.00 660518.53 0.482168E+09
June 0.254132E+11 0.876102E+09 0.118076E+10 0.00 0.00 0.00 0.00 8147090.53 0.338053E+09
July 0.261570E+11 0.908835E+09 0.121533E+10 0.00 0.00 0.00 0.00 24874958.82 0.258995E+09
August 0.262677E+11 0.947850E+09 0.122063E+10 0.00 0.00 0.00 0.00 22279657.59 0.259722E+09
September 0.253456E+11 0.988665E+09 0.117729E+10 0.00 0.00 0.00 0.00 17653678.78 0.336364E+09
October 0.261693E+11 0.105520E+10 0.121734E+10 0.00 0.00 0.00 0.00 31574703.31 0.354335E+09
November 0.253025E+11 0.103508E+10 0.118021E+10 0.00 0.00 0.00 0.00 1389573.56 0.610476E+09
December 0.261570E+11 0.107466E+10 0.121533E+10 0.00 0.00 0.00 0.00 884276.67 0.685977E+09
                   
Annual Sum or Average 0.308468E+12 0.118079E+11 0.143405E+11 0.00 0.00 0.00 0.00 0.112888E+09 0.585204E+10
Minimum of Months 0.236489E+11 0.876102E+09 0.109956E+10 0.00 0.00 0.00 0.00 652.78 0.258995E+09
Maximum of Months 0.262800E+11 0.108210E+10 0.122063E+10 0.00 0.00 0.00 0.00 31574703.31 0.705224E+09



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.948628E+10 0.126520E+11 0.00 0.00 0.00 0.00 10082917.41 0.202082E+10
February 0.702046E+11 0.853408E+10 0.114244E+11 0.00 0.00 0.00 0.00 1255624.95 0.177455E+10
March 0.780153E+11 0.946565E+10 0.126786E+11 0.00 0.00 0.00 0.00 1386759.20 0.206194E+10
April 0.752779E+11 0.905604E+10 0.122282E+11 0.00 0.00 0.00 0.00 11657304.36 0.151038E+10
May 0.778146E+11 0.933467E+10 0.126672E+11 0.00 0.00 0.00 0.00 1871721.88 0.148289E+10
June 0.754422E+11 0.903408E+10 0.122682E+11 0.00 0.00 0.00 0.00 14571024.27 0.105972E+10
July 0.776503E+11 0.928823E+10 0.126273E+11 0.00 0.00 0.00 0.00 59591311.28 0.816078E+09
August 0.779788E+11 0.937932E+10 0.126824E+11 0.00 0.00 0.00 0.00 64654705.14 0.794764E+09
September 0.752414E+11 0.911699E+10 0.122320E+11 0.00 0.00 0.00 0.00 53038517.50 0.993519E+09
October 0.776868E+11 0.946287E+10 0.126482E+11 0.00 0.00 0.00 0.00 0.101863E+09 0.104264E+10
November 0.751137E+11 0.917997E+10 0.122624E+11 0.00 0.00 0.00 0.00 6436319.91 0.175756E+10
December 0.776503E+11 0.945373E+10 0.126273E+11 0.00 0.00 0.00 0.00 6656982.90 0.196890E+10
                   
Annual Sum or Average 0.915726E+12 0.110792E+12 0.148998E+12 0.00 0.00 0.00 0.00 0.333066E+09 0.172838E+11
Minimum of Months 0.702046E+11 0.853408E+10 0.114244E+11 0.00 0.00 0.00 0.00 1255624.95 0.794764E+09
Maximum of Months 0.780153E+11 0.948628E+10 0.126824E+11 0.00 0.00 0.00 0.00 0.101863E+09 0.206194E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.118113E+09 0.261068E+09 0.00 0.00 0.00 0.00 1067861.70 0.159445E+09
February 0.273974E+09 0.106667E+09 0.235798E+09 0.00 0.00 0.00 0.00 189387.92 0.139597E+09
March 0.303685E+09 0.117174E+09 0.260708E+09 0.00 0.00 0.00 0.00 177385.00 0.166542E+09
April 0.293479E+09 0.114438E+09 0.252705E+09 0.00 0.00 0.00 0.00 975484.11 0.115917E+09
May 0.303504E+09 0.117643E+09 0.260888E+09 0.00 0.00 0.00 0.00 89947.56 0.113503E+09
June 0.293842E+09 0.113531E+09 0.252344E+09 0.00 0.00 0.00 0.00 1199900.57 73322459.45
July 0.303141E+09 0.118566E+09 0.261248E+09 0.00 0.00 0.00 0.00 5642876.97 48333163.32
August 0.303685E+09 0.117174E+09 0.260708E+09 0.00 0.00 0.00 0.00 6648459.17 45153663.83
September 0.293479E+09 0.114469E+09 0.252705E+09 0.00 0.00 0.00 0.00 6402819.82 64651567.56
October 0.303322E+09 0.118097E+09 0.261068E+09 0.00 0.00 0.00 0.00 11164226.16 66344885.50
November 0.293661E+09 0.113984E+09 0.252524E+09 0.00 0.00 0.00 0.00 842532.87 0.133566E+09
December 0.303141E+09 0.118582E+09 0.261248E+09 0.00 0.00 0.00 0.00 934778.35 0.152322E+09
                   
Annual Sum or Average 0.357224E+10 0.138844E+10 0.307301E+10 0.00 0.00 0.00 0.00 35335660.20 0.127870E+10
Minimum of Months 0.273974E+09 0.106667E+09 0.235798E+09 0.00 0.00 0.00 0.00 89947.56 45153663.83
Maximum of Months 0.303685E+09 0.118582E+09 0.261248E+09 0.00 0.00 0.00 0.00 11164226.16 0.166542E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.118099E+09 0.261038E+09 0.00 0.00 0.00 0.00 1245587.41 0.156378E+09
February 0.273974E+09 0.106655E+09 0.235770E+09 0.00 0.00 0.00 0.00 224862.25 0.137764E+09
March 0.303685E+09 0.117160E+09 0.260677E+09 0.00 0.00 0.00 0.00 225037.01 0.165969E+09
April 0.293479E+09 0.114425E+09 0.252675E+09 0.00 0.00 0.00 0.00 877826.88 0.121184E+09
May 0.303504E+09 0.117629E+09 0.260857E+09 0.00 0.00 0.00 0.00 61957.20 0.121124E+09
June 0.293842E+09 0.113517E+09 0.252315E+09 0.00 0.00 0.00 0.00 806407.71 88306912.18
July 0.303141E+09 0.118553E+09 0.261218E+09 0.00 0.00 0.00 0.00 4694917.84 67738074.81
August 0.303685E+09 0.117160E+09 0.260677E+09 0.00 0.00 0.00 0.00 5434757.37 62627170.13
September 0.293479E+09 0.114456E+09 0.252675E+09 0.00 0.00 0.00 0.00 6154439.82 75047754.74
October 0.303322E+09 0.118083E+09 0.261038E+09 0.00 0.00 0.00 0.00 10743956.46 74013707.66
November 0.293661E+09 0.113971E+09 0.252495E+09 0.00 0.00 0.00 0.00 985825.35 0.132488E+09
December 0.303141E+09 0.118568E+09 0.261218E+09 0.00 0.00 0.00 0.00 1233300.25 0.149699E+09
                   
Annual Sum or Average 0.357224E+10 0.138828E+10 0.307265E+10 0.00 0.00 0.00 0.00 32688875.55 0.135234E+10
Minimum of Months 0.273974E+09 0.106655E+09 0.235770E+09 0.00 0.00 0.00 0.00 61957.20 62627170.13
Maximum of Months 0.303685E+09 0.118568E+09 0.261218E+09 0.00 0.00 0.00 0.00 10743956.46 0.165969E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 74229181.22 0.255708E+09 0.00 0.00 0.00 0.00 0.00 69984215.46
February 0.00 67036196.95 0.230956E+09 0.00 0.00 0.00 0.00 0.00 61942644.17
March 0.00 73639243.64 0.255355E+09 0.00 0.00 0.00 0.00 0.00 71254714.55
April 0.00 71920171.51 0.247516E+09 0.00 0.00 0.00 0.00 585.51 56475850.01
May 0.00 73934212.43 0.255532E+09 0.00 0.00 0.00 0.00 0.00 56622393.24
June 0.00 71349576.37 0.247163E+09 0.00 0.00 0.00 0.00 0.00 44476924.42
July 0.00 74514478.79 0.255885E+09 0.00 0.00 0.00 0.00 43996.69 37088610.88
August 0.00 73639243.64 0.255355E+09 0.00 0.00 0.00 0.00 30152.17 35936712.63
September 0.00 71939513.95 0.247516E+09 0.00 0.00 0.00 0.00 657845.32 41393358.28
October 0.00 74219510.00 0.255708E+09 0.00 0.00 0.00 0.00 1127530.47 41809445.23
November 0.00 71634873.94 0.247340E+09 0.00 0.00 0.00 0.00 451.90 62048506.94
December 0.00 74524150.01 0.255885E+09 0.00 0.00 0.00 0.00 0.00 68171473.72
                   
Annual Sum or Average 0.00 0.872580E+09 0.300992E+10 0.00 0.00 0.00 0.00 1860562.06 0.647205E+09
Minimum of Months 0.00 67036196.95 0.230956E+09 0.00 0.00 0.00 0.00 0.00 35936712.63
Maximum of Months 0.00 74524150.01 0.255885E+09 0.00 0.00 0.00 0.00 1127530.47 71254714.55



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 74249479.06 0.255778E+09 0.00 0.00 0.00 0.00 419451.49 43650796.28
February 0.273974E+09 67054527.88 0.231020E+09 0.00 0.00 0.00 0.00 78762.81 38387409.48
March 0.303685E+09 73659380.16 0.255425E+09 0.00 0.00 0.00 0.00 88432.64 46140277.79
April 0.293479E+09 71939837.95 0.247584E+09 0.00 0.00 0.00 0.00 300524.02 32307496.70
May 0.303504E+09 73954429.61 0.255602E+09 0.00 0.00 0.00 0.00 29182.52 32308391.66
June 0.293842E+09 71369086.78 0.247231E+09 0.00 0.00 0.00 0.00 267533.90 22493512.01
July 0.303141E+09 74534854.64 0.255955E+09 0.00 0.00 0.00 0.00 1403032.56 16340830.45
August 0.303685E+09 73659380.16 0.255425E+09 0.00 0.00 0.00 0.00 1671399.75 15078503.40
September 0.293479E+09 71959185.68 0.247584E+09 0.00 0.00 0.00 0.00 1766749.65 19287547.04
October 0.303322E+09 74239805.19 0.255778E+09 0.00 0.00 0.00 0.00 3172082.81 19772758.97
November 0.293661E+09 71654462.37 0.247408E+09 0.00 0.00 0.00 0.00 365369.93 36446443.36
December 0.303141E+09 74544528.51 0.255955E+09 0.00 0.00 0.00 0.00 450584.81 41556763.33
                   
Annual Sum or Average 0.357224E+10 0.872819E+09 0.301074E+10 0.00 0.00 0.00 0.00 10013106.89 0.363771E+09
Minimum of Months 0.273974E+09 67054527.88 0.231020E+09 0.00 0.00 0.00 0.00 29182.52 15078503.40
Maximum of Months 0.303685E+09 74544528.51 0.255955E+09 0.00 0.00 0.00 0.00 3172082.81 46140277.79



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.118113E+09 0.261068E+09 0.00 0.00 0.00 0.00 1039050.39 0.160330E+09
February 0.273974E+09 0.106667E+09 0.235798E+09 0.00 0.00 0.00 0.00 185360.53 0.139872E+09
March 0.303685E+09 0.117174E+09 0.260708E+09 0.00 0.00 0.00 0.00 169639.46 0.167335E+09
April 0.293479E+09 0.114438E+09 0.252705E+09 0.00 0.00 0.00 0.00 938686.47 0.116555E+09
May 0.303504E+09 0.117643E+09 0.260888E+09 0.00 0.00 0.00 0.00 88390.22 0.114081E+09
June 0.293842E+09 0.113531E+09 0.252344E+09 0.00 0.00 0.00 0.00 1135142.02 73502903.57
July 0.303141E+09 0.118566E+09 0.261248E+09 0.00 0.00 0.00 0.00 5561902.86 48717931.43
August 0.303685E+09 0.117174E+09 0.260708E+09 0.00 0.00 0.00 0.00 6517404.77 45480616.41
September 0.293479E+09 0.114469E+09 0.252705E+09 0.00 0.00 0.00 0.00 6379423.70 64622904.62
October 0.303322E+09 0.118097E+09 0.261068E+09 0.00 0.00 0.00 0.00 11187309.83 66623563.17
November 0.293661E+09 0.113984E+09 0.252524E+09 0.00 0.00 0.00 0.00 826460.57 0.134029E+09
December 0.303141E+09 0.118582E+09 0.261248E+09 0.00 0.00 0.00 0.00 921683.38 0.152938E+09
                   
Annual Sum or Average 0.357224E+10 0.138844E+10 0.307301E+10 0.00 0.00 0.00 0.00 34950454.19 0.128409E+10
Minimum of Months 0.273974E+09 0.106667E+09 0.235798E+09 0.00 0.00 0.00 0.00 88390.22 45480616.41
Maximum of Months 0.303685E+09 0.118582E+09 0.261248E+09 0.00 0.00 0.00 0.00 11187309.83 0.167335E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.118099E+09 0.261038E+09 0.00 0.00 0.00 0.00 1153124.47 0.156663E+09
February 0.273974E+09 0.106655E+09 0.235770E+09 0.00 0.00 0.00 0.00 167486.81 0.137486E+09
March 0.303685E+09 0.117160E+09 0.260677E+09 0.00 0.00 0.00 0.00 167654.31 0.166208E+09
April 0.293479E+09 0.114425E+09 0.252675E+09 0.00 0.00 0.00 0.00 712819.66 0.119769E+09
May 0.303504E+09 0.117629E+09 0.260857E+09 0.00 0.00 0.00 0.00 59649.19 0.119605E+09
June 0.293842E+09 0.113517E+09 0.252315E+09 0.00 0.00 0.00 0.00 708843.74 84222662.75
July 0.303141E+09 0.118553E+09 0.261218E+09 0.00 0.00 0.00 0.00 4494381.06 64144235.57
August 0.303685E+09 0.117160E+09 0.260677E+09 0.00 0.00 0.00 0.00 5130744.88 60067702.98
September 0.293479E+09 0.114456E+09 0.252675E+09 0.00 0.00 0.00 0.00 6043747.65 72372625.22
October 0.303322E+09 0.118083E+09 0.261038E+09 0.00 0.00 0.00 0.00 10408814.95 73193185.02
November 0.293661E+09 0.113971E+09 0.252495E+09 0.00 0.00 0.00 0.00 909513.01 0.131747E+09
December 0.303141E+09 0.118568E+09 0.261218E+09 0.00 0.00 0.00 0.00 1058910.67 0.149745E+09
                   
Annual Sum or Average 0.357224E+10 0.138828E+10 0.307265E+10 0.00 0.00 0.00 0.00 31015690.38 0.133522E+10
Minimum of Months 0.273974E+09 0.106655E+09 0.235770E+09 0.00 0.00 0.00 0.00 59649.19 60067702.98
Maximum of Months 0.303685E+09 0.118568E+09 0.261218E+09 0.00 0.00 0.00 0.00 10408814.95 0.166208E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.108388E+10 0.00 0.00 0.00 0.00 0.00 1870266.84 0.197903E+09
February 0.348285E+10 0.978647E+09 0.00 0.00 0.00 0.00 0.00 277227.57 0.174043E+09
March 0.387034E+10 0.108722E+10 0.00 0.00 0.00 0.00 0.00 401752.81 0.203630E+09
April 0.373454E+10 0.104713E+10 0.00 0.00 0.00 0.00 0.00 1811130.80 0.148312E+09
May 0.386038E+10 0.108576E+10 0.00 0.00 0.00 0.00 0.00 234393.11 0.147249E+09
June 0.374269E+10 0.105194E+10 0.00 0.00 0.00 0.00 0.00 1371541.26 0.103964E+09
July 0.385223E+10 0.108096E+10 0.00 0.00 0.00 0.00 0.00 5710247.63 80956568.32
August 0.386853E+10 0.108764E+10 0.00 0.00 0.00 0.00 0.00 6251326.41 78789091.07
September 0.373273E+10 0.104755E+10 0.00 0.00 0.00 0.00 0.00 6293851.80 97291463.40
October 0.385404E+10 0.108346E+10 0.00 0.00 0.00 0.00 0.00 11979778.99 0.103510E+09
November 0.372639E+10 0.105110E+10 0.00 0.00 0.00 0.00 0.00 1297368.66 0.172992E+09
December 0.385223E+10 0.108096E+10 0.00 0.00 0.00 0.00 0.00 1575302.51 0.193654E+09
                   
Annual Sum or Average 0.454292E+11 0.127663E+11 0.00 0.00 0.00 0.00 0.00 39074188.38 0.170229E+10
Minimum of Months 0.348285E+10 0.978647E+09 0.00 0.00 0.00 0.00 0.00 234393.11 78789091.07
Maximum of Months 0.387034E+10 0.108764E+10 0.00 0.00 0.00 0.00 0.00 11979778.99 0.203630E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.118113E+09 0.261068E+09 0.00 0.00 0.00 0.00 1021445.76 0.159848E+09
February 0.273974E+09 0.106667E+09 0.235798E+09 0.00 0.00 0.00 0.00 183090.98 0.139821E+09
March 0.303685E+09 0.117174E+09 0.260708E+09 0.00 0.00 0.00 0.00 163692.78 0.166979E+09
April 0.293479E+09 0.114438E+09 0.252705E+09 0.00 0.00 0.00 0.00 915371.72 0.116791E+09
May 0.303504E+09 0.117643E+09 0.260888E+09 0.00 0.00 0.00 0.00 78291.19 0.114470E+09
June 0.293842E+09 0.113531E+09 0.252344E+09 0.00 0.00 0.00 0.00 1097631.04 74208748.33
July 0.303141E+09 0.118566E+09 0.261248E+09 0.00 0.00 0.00 0.00 5396702.09 49134168.33
August 0.303685E+09 0.117174E+09 0.260708E+09 0.00 0.00 0.00 0.00 6358178.24 45866262.53
September 0.293479E+09 0.114469E+09 0.252705E+09 0.00 0.00 0.00 0.00 6289847.24 65426307.28
October 0.303322E+09 0.118097E+09 0.261068E+09 0.00 0.00 0.00 0.00 10954663.10 66913174.46
November 0.293661E+09 0.113984E+09 0.252524E+09 0.00 0.00 0.00 0.00 811890.41 0.134023E+09
December 0.303141E+09 0.118582E+09 0.261248E+09 0.00 0.00 0.00 0.00 898142.46 0.152646E+09
                   
Annual Sum or Average 0.357224E+10 0.138844E+10 0.307301E+10 0.00 0.00 0.00 0.00 34168947.02 0.128613E+10
Minimum of Months 0.273974E+09 0.106667E+09 0.235798E+09 0.00 0.00 0.00 0.00 78291.19 45866262.53
Maximum of Months 0.303685E+09 0.118582E+09 0.261248E+09 0.00 0.00 0.00 0.00 10954663.10 0.166979E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.118099E+09 0.261038E+09 0.00 0.00 0.00 0.00 1250283.65 0.156006E+09
February 0.273974E+09 0.106655E+09 0.235770E+09 0.00 0.00 0.00 0.00 235761.28 0.137622E+09
March 0.303685E+09 0.117160E+09 0.260677E+09 0.00 0.00 0.00 0.00 200232.74 0.166536E+09
April 0.293479E+09 0.114425E+09 0.252675E+09 0.00 0.00 0.00 0.00 802148.28 0.123065E+09
May 0.303504E+09 0.117629E+09 0.260857E+09 0.00 0.00 0.00 0.00 53766.40 0.122967E+09
June 0.293842E+09 0.113517E+09 0.252315E+09 0.00 0.00 0.00 0.00 726594.26 91101224.92
July 0.303141E+09 0.118553E+09 0.261218E+09 0.00 0.00 0.00 0.00 4486345.48 70725988.04
August 0.303685E+09 0.117160E+09 0.260677E+09 0.00 0.00 0.00 0.00 5189877.93 64941194.76
September 0.293479E+09 0.114456E+09 0.252675E+09 0.00 0.00 0.00 0.00 6082113.62 76043842.83
October 0.303322E+09 0.118083E+09 0.261038E+09 0.00 0.00 0.00 0.00 10648085.18 73858479.75
November 0.293661E+09 0.113971E+09 0.252495E+09 0.00 0.00 0.00 0.00 1007355.81 0.132205E+09
December 0.303141E+09 0.118568E+09 0.261218E+09 0.00 0.00 0.00 0.00 1302320.93 0.149042E+09
                   
Annual Sum or Average 0.357224E+10 0.138828E+10 0.307265E+10 0.00 0.00 0.00 0.00 31984885.56 0.136411E+10
Minimum of Months 0.273974E+09 0.106655E+09 0.235770E+09 0.00 0.00 0.00 0.00 53766.40 64941194.76
Maximum of Months 0.303685E+09 0.118568E+09 0.261218E+09 0.00 0.00 0.00 0.00 10648085.18 0.166536E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 74249479.06 0.255778E+09 0.00 0.00 0.00 0.00 486392.17 83191590.52
February 0.273974E+09 67054527.88 0.231020E+09 0.00 0.00 0.00 0.00 89805.43 72801416.19
March 0.303685E+09 73659380.16 0.255425E+09 0.00 0.00 0.00 0.00 78621.89 86569564.43
April 0.293479E+09 71939837.95 0.247584E+09 0.00 0.00 0.00 0.00 462134.05 59913496.95
May 0.303504E+09 73954429.61 0.255602E+09 0.00 0.00 0.00 0.00 40707.33 58370751.43
June 0.293842E+09 71369086.78 0.247231E+09 0.00 0.00 0.00 0.00 572713.64 37631377.28
July 0.303141E+09 74534854.64 0.255955E+09 0.00 0.00 0.00 0.00 2782130.04 24942635.41
August 0.303685E+09 73659380.16 0.255425E+09 0.00 0.00 0.00 0.00 3247833.89 23369968.14
September 0.293479E+09 71959185.68 0.247584E+09 0.00 0.00 0.00 0.00 3211188.51 33462120.41
October 0.303322E+09 74239805.19 0.255778E+09 0.00 0.00 0.00 0.00 5545279.36 34542928.92
November 0.293661E+09 71654462.37 0.247408E+09 0.00 0.00 0.00 0.00 390801.59 69604325.04
December 0.303141E+09 74544528.51 0.255955E+09 0.00 0.00 0.00 0.00 441924.70 79474489.85
                   
Annual Sum or Average 0.357224E+10 0.872819E+09 0.301074E+10 0.00 0.00 0.00 0.00 17349532.59 0.663875E+09
Minimum of Months 0.273974E+09 67054527.88 0.231020E+09 0.00 0.00 0.00 0.00 40707.33 23369968.14
Maximum of Months 0.303685E+09 74544528.51 0.255955E+09 0.00 0.00 0.00 0.00 5545279.36 86569564.43



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.229342E+10 0.149358E+11 0.00 0.00 0.00 0.00 1641399.52 0.478917E+09
February 0.415303E+11 0.202878E+10 0.134904E+11 0.00 0.00 0.00 0.00 260294.40 0.427266E+09
March 0.461508E+11 0.221640E+10 0.149358E+11 0.00 0.00 0.00 0.00 123907.90 0.503594E+09
April 0.445315E+11 0.206608E+10 0.144540E+11 0.00 0.00 0.00 0.00 1105218.68 0.374552E+09
May 0.460320E+11 0.207546E+10 0.149358E+11 0.00 0.00 0.00 0.00 61260.51 0.375236E+09
June 0.446286E+11 0.199013E+10 0.144540E+11 0.00 0.00 0.00 0.00 492962.60 0.272004E+09
July 0.459349E+11 0.205834E+10 0.149358E+11 0.00 0.00 0.00 0.00 5904242.05 0.208235E+09
August 0.461292E+11 0.211343E+10 0.149358E+11 0.00 0.00 0.00 0.00 7082567.95 0.198042E+09
September 0.445099E+11 0.212400E+10 0.144540E+11 0.00 0.00 0.00 0.00 10345470.62 0.245122E+09
October 0.459565E+11 0.226395E+10 0.149358E+11 0.00 0.00 0.00 0.00 21255907.83 0.250843E+09
November 0.444343E+11 0.220824E+10 0.144540E+11 0.00 0.00 0.00 0.00 1396456.62 0.415140E+09
December 0.459349E+11 0.229443E+10 0.149358E+11 0.00 0.00 0.00 0.00 1568672.82 0.462784E+09
                   
Annual Sum or Average 0.541708E+12 0.257326E+11 0.175857E+12 0.00 0.00 0.00 0.00 51238361.51 0.421173E+10
Minimum of Months 0.415303E+11 0.199013E+10 0.134904E+11 0.00 0.00 0.00 0.00 61260.51 0.198042E+09
Maximum of Months 0.461508E+11 0.229443E+10 0.149358E+11 0.00 0.00 0.00 0.00 21255907.83 0.503594E+09



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.229342E+10 0.149358E+11 0.00 0.00 0.00 0.00 1278484.77 0.485877E+09
February 0.415303E+11 0.202878E+10 0.134904E+11 0.00 0.00 0.00 0.00 195656.56 0.433523E+09
March 0.461508E+11 0.221640E+10 0.149358E+11 0.00 0.00 0.00 0.00 53902.51 0.510794E+09
April 0.445315E+11 0.206608E+10 0.144540E+11 0.00 0.00 0.00 0.00 902059.61 0.379892E+09
May 0.460320E+11 0.207546E+10 0.149358E+11 0.00 0.00 0.00 0.00 30358.95 0.380534E+09
June 0.446286E+11 0.199013E+10 0.144540E+11 0.00 0.00 0.00 0.00 295900.24 0.275481E+09
July 0.459349E+11 0.205834E+10 0.149358E+11 0.00 0.00 0.00 0.00 5137778.04 0.210222E+09
August 0.461292E+11 0.211343E+10 0.149358E+11 0.00 0.00 0.00 0.00 6109071.55 0.199963E+09
September 0.445099E+11 0.212400E+10 0.144540E+11 0.00 0.00 0.00 0.00 10087539.41 0.248665E+09
October 0.459565E+11 0.226395E+10 0.149358E+11 0.00 0.00 0.00 0.00 20446106.36 0.254022E+09
November 0.444343E+11 0.220824E+10 0.144540E+11 0.00 0.00 0.00 0.00 1159600.34 0.420955E+09
December 0.459349E+11 0.229443E+10 0.149358E+11 0.00 0.00 0.00 0.00 1185766.58 0.469235E+09
                   
Annual Sum or Average 0.541708E+12 0.257326E+11 0.175857E+12 0.00 0.00 0.00 0.00 46882224.92 0.426916E+10
Minimum of Months 0.415303E+11 0.199013E+10 0.134904E+11 0.00 0.00 0.00 0.00 30358.95 0.199963E+09
Maximum of Months 0.461508E+11 0.229443E+10 0.149358E+11 0.00 0.00 0.00 0.00 20446106.36 0.510794E+09



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.101925E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 602883.72 0.432996E+09
February 0.369574E+10 0.920291E+09 0.293798E+11 0.275852E+11 0.00 0.00 0.00 79982.33 0.386788E+09
March 0.410691E+10 0.102239E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.454667E+09
April 0.396281E+10 0.984694E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 607301.34 0.335990E+09
May 0.409635E+10 0.102102E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.335813E+09
June 0.397146E+10 0.989210E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 43362.89 0.242057E+09
July 0.408770E+10 0.101650E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 3741462.81 0.182976E+09
August 0.410499E+10 0.102279E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 4236160.24 0.174356E+09
September 0.396089E+10 0.985086E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 8893317.52 0.219397E+09
October 0.408962E+10 0.101886E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 16670513.09 0.223073E+09
November 0.395417E+10 0.988424E+09 0.314783E+11 0.295556E+11 0.00 0.00 0.00 744979.13 0.374640E+09
December 0.408770E+10 0.101650E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 450768.07 0.418075E+09
                   
Annual Sum or Average 0.482060E+11 0.120050E+11 0.382987E+12 0.359593E+12 0.00 0.00 0.00 36070731.14 0.378083E+10
Minimum of Months 0.369574E+10 0.920291E+09 0.293798E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.174356E+09
Maximum of Months 0.410691E+10 0.102279E+10 0.325276E+11 0.305408E+11 0.00 0.00 0.00 16670513.09 0.454667E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.114712E+10 0.00 0.00 0.00 0.00 0.00 2745420.14 0.344126E+09
February 0.368610E+10 0.103575E+10 0.00 0.00 0.00 0.00 0.00 428735.13 0.301078E+09
March 0.409620E+10 0.115066E+10 0.00 0.00 0.00 0.00 0.00 401150.27 0.358349E+09
April 0.395248E+10 0.110823E+10 0.00 0.00 0.00 0.00 0.00 2064262.47 0.261611E+09
May 0.408566E+10 0.114911E+10 0.00 0.00 0.00 0.00 0.00 125072.41 0.258019E+09
June 0.396110E+10 0.111331E+10 0.00 0.00 0.00 0.00 0.00 1207128.75 0.183634E+09
July 0.407704E+10 0.114403E+10 0.00 0.00 0.00 0.00 0.00 7724284.17 0.141626E+09
August 0.409429E+10 0.115110E+10 0.00 0.00 0.00 0.00 0.00 8397379.41 0.136552E+09
September 0.395056E+10 0.110867E+10 0.00 0.00 0.00 0.00 0.00 10300593.12 0.168475E+09
October 0.407896E+10 0.114668E+10 0.00 0.00 0.00 0.00 0.00 19669589.14 0.174730E+09
November 0.394385E+10 0.111243E+10 0.00 0.00 0.00 0.00 0.00 1927402.26 0.294711E+09
December 0.407704E+10 0.114403E+10 0.00 0.00 0.00 0.00 0.00 2260993.79 0.330817E+09
                   
Annual Sum or Average 0.480803E+11 0.135111E+11 0.00 0.00 0.00 0.00 0.00 57252011.05 0.295373E+10
Minimum of Months 0.368610E+10 0.103575E+10 0.00 0.00 0.00 0.00 0.00 125072.41 0.136552E+09
Maximum of Months 0.409620E+10 0.115110E+10 0.00 0.00 0.00 0.00 0.00 19669589.14 0.358349E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 8344.11 02-JAN-20:10 9632.53 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 8344.11 01-FEB-20:10 9632.53 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 8344.11 01-MAR-20:10 9632.53 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 8344.11 03-APR-19:10 9632.53 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 8344.11 01-MAY-19:10 9632.53 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 8344.11 01-JUN-19:10 9632.53 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 8344.11 03-JUL-19:10 9632.53 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 8344.11 01-AUG-19:10 9632.53 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 8344.11 01-SEP-19:10 9632.53 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 8344.11 02-OCT-19:10 9632.53 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 8344.11 01-NOV-19:10 9632.53 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 8344.11 01-DEC-20:10 9632.53 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   8344.11   9632.53   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   8344.11   9632.53   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 461.08 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 32.43 17-JAN-11:55 250.85 08-JAN-07:00
February 1169.53 01-FEB-00:10 461.08 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 22.85 01-FEB-12:00 196.97 04-FEB-06:00
March 1169.53 01-MAR-00:10 461.08 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 1.16 11-MAR-11:00 210.82 08-MAR-04:00
April 1169.53 01-APR-00:10 461.08 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 44.10 30-APR-10:55 170.87 01-APR-06:00
May 1169.53 01-MAY-00:10 461.08 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 14.65 03-MAY-12:00 158.99 15-MAY-02:00
June 1169.53 01-JUN-00:10 461.08 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 37.06 29-JUN-10:55 121.18 13-JUN-04:30
July 1169.53 01-JUL-00:10 461.08 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 66.38 19-JUL-10:55 99.82 06-JUL-01:00
August 1169.53 01-AUG-00:10 461.08 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 60.65 14-AUG-10:55 90.91 28-AUG-03:00
September 1169.53 01-SEP-00:10 461.08 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 132.69 29-SEP-11:00 121.35 20-SEP-03:00
October 1169.53 01-OCT-23:10 461.08 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 143.55 16-OCT-11:00 148.81 30-OCT-03:00
November 1169.53 01-NOV-00:10 461.08 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 34.19 19-NOV-13:00 184.99 29-NOV-23:00
December 1169.53 01-DEC-00:10 461.08 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 23.02 16-DEC-13:00 197.48 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   461.08   685.60   0.00 0.00 0.00 0.00 1.16   90.91  
Maximum of Months 1169.53   461.08   685.60   0.00 0.00 0.00 0.00 143.55   250.85  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 533.93 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 16.72 18-JAN-13:00 96.90 08-JAN-07:00
February 1354.32 01-FEB-00:10 533.93 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 16.68 01-FEB-11:55 84.00 04-FEB-05:55
March 1354.32 01-MAR-00:10 533.93 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 8.12 11-MAR-11:50 85.64 08-MAR-02:00
April 1354.32 01-APR-00:10 533.93 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 20.77 26-APR-13:00 70.01 01-APR-06:00
May 1354.32 01-MAY-00:10 533.93 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 7.92 03-MAY-12:00 69.55 19-MAY-05:00
June 1354.32 01-JUN-00:10 533.93 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 12.64 29-JUN-10:55 54.82 13-JUN-04:40
July 1354.32 01-JUL-00:10 533.93 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 25.09 19-JUL-10:55 47.64 06-JUL-01:00
August 1354.32 01-AUG-00:10 533.93 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 24.95 14-AUG-10:55 42.66 24-AUG-02:00
September 1354.32 01-SEP-00:10 533.93 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 56.99 29-SEP-11:00 55.92 20-SEP-03:00
October 1354.32 01-OCT-23:10 533.93 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 59.73 16-OCT-11:00 65.97 27-OCT-04:30
November 1354.32 01-NOV-00:10 533.93 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 17.99 19-NOV-13:00 79.21 29-NOV-23:00
December 1354.32 01-DEC-00:10 533.93 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 15.96 16-DEC-13:00 83.24 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   533.93   793.93   0.00 0.00 0.00 0.00 7.92   42.66  
Maximum of Months 1354.32   533.93   793.93   0.00 0.00 0.00 0.00 59.73   96.90  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 615.76 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 49.76 13-JAN-14:00 228.85 08-JAN-07:00
February 286.42 01-FEB-00:10 615.76 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 45.52 01-FEB-11:55 187.46 04-FEB-05:55
March 286.42 01-MAR-00:10 615.76 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 28.10 11-MAR-11:50 192.30 08-MAR-04:00
April 286.42 01-APR-00:10 615.76 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 52.66 26-APR-13:00 155.87 01-APR-06:00
May 286.42 01-MAY-00:10 615.76 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 19.98 03-MAY-12:00 155.51 27-MAY-03:00
June 286.42 01-JUN-00:10 615.76 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 27.38 29-JUN-10:55 122.50 13-JUN-04:40
July 286.42 01-JUL-00:10 615.76 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 56.05 19-JUL-10:55 106.16 06-JUL-01:00
August 286.42 01-AUG-00:10 615.76 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 57.36 14-AUG-10:55 93.73 28-AUG-06:50
September 286.42 01-SEP-00:10 615.76 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 136.58 29-SEP-11:00 122.31 20-SEP-03:00
October 286.42 01-OCT-23:10 615.76 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 141.83 16-OCT-11:00 146.43 12-OCT-06:00
November 286.42 01-NOV-00:10 615.76 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 51.29 19-NOV-13:00 173.28 29-NOV-23:00
December 286.42 01-DEC-00:10 615.76 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 49.25 16-DEC-13:00 186.76 03-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   615.76   839.45   0.00 0.00 0.00 0.00 19.98   93.73  
Maximum of Months 286.42   615.76   839.45   0.00 0.00 0.00 0.00 141.83   228.85  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 137.35 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 28.14 13-JAN-14:00 132.04 08-JAN-07:00
February 220.32 01-FEB-00:10 137.35 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 25.98 01-FEB-11:55 107.67 04-FEB-05:55
March 220.32 01-MAR-00:10 137.35 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 15.68 11-MAR-11:50 110.95 08-MAR-04:00
April 220.32 01-APR-00:10 137.35 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 30.23 26-APR-13:00 89.93 01-APR-06:00
May 220.32 01-MAY-00:10 137.35 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 11.56 03-MAY-12:00 88.82 27-MAY-03:00
June 220.32 01-JUN-00:10 137.35 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 16.01 29-JUN-10:55 69.95 13-JUN-05:00
July 220.32 01-JUL-00:10 137.35 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 32.44 19-JUL-10:55 60.23 06-JUL-01:00
August 220.32 01-AUG-00:10 137.35 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 33.09 14-AUG-10:55 52.95 24-AUG-02:00
September 220.32 01-SEP-00:10 137.35 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 78.17 29-SEP-11:00 69.96 20-SEP-03:00
October 220.32 01-OCT-23:10 137.35 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 81.26 16-OCT-11:00 83.54 27-OCT-04:20
November 220.32 01-NOV-00:10 137.35 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 29.14 19-NOV-13:00 97.87 29-NOV-23:00
December 220.32 01-DEC-00:10 137.35 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 27.78 16-DEC-13:00 106.51 03-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   137.35   242.16   0.00 0.00 0.00 0.00 11.56   52.95  
Maximum of Months 220.32   137.35   242.16   0.00 0.00 0.00 0.00 81.26   132.04  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 360.62 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 70.21 14-JAN-11:50 312.56 08-JAN-07:00
February 907.20 01-FEB-00:10 360.62 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 64.14 01-FEB-11:55 258.57 06-FEB-23:00
March 907.20 01-MAR-00:10 360.62 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 41.78 11-MAR-11:50 277.64 29-MAR-22:00
April 907.20 01-APR-00:10 360.62 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 71.46 26-APR-13:00 233.64 01-APR-06:00
May 907.20 01-MAY-00:10 360.62 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 33.90 04-MAY-12:00 222.58 15-MAY-05:08
June 907.20 01-JUN-00:10 360.62 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 54.15 29-JUN-10:50 180.30 12-JUN-21:00
July 907.20 01-JUL-00:10 360.62 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 95.77 19-JUL-10:50 138.32 08-JUL-24:00
August 907.20 01-AUG-00:10 360.62 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 95.59 14-AUG-10:50 147.78 28-AUG-07:00
September 907.20 01-SEP-00:10 360.62 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 203.55 29-SEP-10:50 176.15 20-SEP-06:10
October 907.20 01-OCT-23:10 360.62 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 217.44 16-OCT-11:00 223.23 12-OCT-06:00
November 907.20 01-NOV-00:10 360.62 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 71.63 19-NOV-13:10 259.59 23-NOV-22:00
December 907.20 01-DEC-00:10 360.62 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 63.25 16-DEC-13:00 280.04 22-DEC-07:10
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   360.62   4572.80   39726.58   0.00 0.00 0.00 33.90   138.32  
Maximum of Months 907.20   360.62   4572.80   39726.58   0.00 0.00 0.00 217.44   312.56  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 1416.11 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 67.76 17-JAN-11:55 554.53 08-JAN-07:00
February 15368.40 01-FEB-00:10 1416.11 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 50.77 01-FEB-11:55 486.96 04-FEB-05:55
March 15368.40 01-MAR-00:10 1416.11 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 0.75 11-MAR-11:40 490.48 08-MAR-02:00
April 15368.40 01-APR-00:10 1416.11 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 103.59 26-APR-13:00 400.55 01-APR-06:00
May 15368.40 01-MAY-00:10 1416.11 01-MAY-19:10 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 38.14 03-MAY-12:00 400.24 19-MAY-05:00
June 15368.40 01-JUN-00:10 1416.11 01-JUN-19:10 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 87.73 29-JUN-10:55 320.94 13-JUN-05:00
July 15368.40 01-JUL-00:10 1416.11 03-JUL-19:10 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 154.27 19-JUL-10:55 272.76 06-JUL-01:00
August 15368.40 01-AUG-00:10 1416.11 01-AUG-19:10 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 143.38 14-AUG-10:55 251.48 28-AUG-03:00
September 15368.40 01-SEP-00:10 1416.11 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 294.30 29-SEP-10:50 326.80 20-SEP-03:00
October 15368.40 01-OCT-23:10 1416.11 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 317.37 16-OCT-11:00 388.30 30-OCT-03:00
November 15368.40 01-NOV-00:10 1416.11 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 75.61 19-NOV-13:00 456.54 29-NOV-23:00
December 15368.40 01-DEC-00:10 1416.11 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 50.92 16-DEC-13:00 480.77 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   1416.11   965.27   0.00 0.00 0.00 0.00 0.75   251.48  
Maximum of Months 15368.40   1416.11   965.27   0.00 0.00 0.00 0.00 317.37   554.53  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 9580.84 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 224.17 18-JAN-13:00 1608.97 08-JAN-07:00
February 45622.98 01-FEB-00:10 9580.84 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 235.32 01-FEB-11:55 1427.18 04-FEB-05:55
March 45622.98 01-MAR-00:10 9580.84 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 94.66 11-MAR-11:50 1446.54 08-MAR-02:00
April 45622.98 01-APR-00:10 9580.84 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 330.60 26-APR-13:00 1199.85 01-APR-06:00
May 45622.98 01-MAY-00:10 9580.84 01-MAY-19:10 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 121.08 03-MAY-12:00 1185.37 19-MAY-05:00
June 45622.98 01-JUN-00:10 9580.84 01-JUN-19:10 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 213.28 29-JUN-10:55 954.64 13-JUN-05:00
July 45622.98 01-JUL-00:10 9580.84 03-JUL-19:10 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 414.47 19-JUL-10:55 812.33 06-JUL-01:00
August 45622.98 01-AUG-00:10 9580.84 01-AUG-19:10 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 408.40 14-AUG-10:55 735.91 28-AUG-05:00
September 45622.98 01-SEP-00:10 9580.84 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 918.31 29-SEP-11:00 957.84 20-SEP-03:00
October 45622.98 01-OCT-23:10 9580.84 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 958.93 16-OCT-11:00 1129.61 27-OCT-04:40
November 45622.98 01-NOV-00:10 9580.84 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 247.38 19-NOV-13:00 1314.20 29-NOV-23:00
December 45622.98 01-DEC-00:10 9580.84 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 204.45 16-DEC-13:00 1405.55 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   9580.84   10029.21   0.00 0.00 0.00 0.00 94.66   735.91  
Maximum of Months 45622.98   9580.84   10029.21   0.00 0.00 0.00 0.00 958.93   1608.97  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 106.87 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 32.34 14-JAN-11:00 146.71 08-JAN-07:00
February 180.00 01-FEB-00:10 106.87 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 19.02 01-FEB-09:51 115.41 04-FEB-06:00
March 180.00 01-MAR-00:10 106.87 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 19.03 11-MAR-11:00 123.45 08-MAR-02:00
April 180.00 01-APR-00:10 106.87 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 25.70 30-APR-10:00 100.25 01-APR-06:00
May 180.00 01-MAY-00:10 106.87 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 12.41 03-MAY-10:00 93.35 15-MAY-02:00
June 180.00 01-JUN-00:10 106.87 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 19.03 30-JUN-10:00 71.39 13-JUN-04:50
July 180.00 01-JUL-00:10 106.87 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 38.70 19-JUL-10:00 56.57 06-JUL-01:00
August 180.00 01-AUG-00:10 106.87 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 38.71 15-AUG-10:00 53.83 28-AUG-07:20
September 180.00 01-SEP-00:10 106.87 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 89.14 29-SEP-10:00 70.90 20-SEP-03:10
October 180.00 01-OCT-00:10 106.87 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 89.32 16-OCT-10:00 85.84 30-OCT-04:00
November 180.00 01-NOV-00:10 106.87 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 32.26 19-NOV-09:53 100.72 24-NOV-01:00
December 180.00 01-DEC-00:10 106.87 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 32.32 05-DEC-10:00 115.70 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   106.87   237.06   0.00 0.00 0.00 0.00 12.41   53.83  
Maximum of Months 180.00   106.87   237.06   0.00 0.00 0.00 0.00 89.32   146.71  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 106.85 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 32.34 14-JAN-11:00 146.70 08-JAN-07:00
February 180.00 01-FEB-00:10 106.85 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 23.20 01-FEB-11:55 115.40 04-FEB-06:00
March 180.00 01-MAR-00:10 106.85 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 19.03 11-MAR-11:00 123.44 08-MAR-04:00
April 180.00 01-APR-00:10 106.85 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 25.70 30-APR-10:00 100.25 01-APR-06:00
May 180.00 01-MAY-00:10 106.85 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 12.41 03-MAY-10:00 93.35 15-MAY-02:00
June 180.00 01-JUN-00:10 106.85 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 19.03 30-JUN-10:00 71.39 13-JUN-05:00
July 180.00 01-JUL-00:10 106.85 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 38.69 19-JUL-10:00 64.73 07-JUL-21:00
August 180.00 01-AUG-00:10 106.85 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 38.70 15-AUG-10:00 63.10 26-AUG-18:00
September 180.00 01-SEP-00:10 106.85 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 89.14 29-SEP-10:00 70.89 20-SEP-03:10
October 180.00 01-OCT-00:10 106.85 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 89.66 16-OCT-10:01 85.84 30-OCT-04:00
November 180.00 01-NOV-00:10 106.85 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 32.26 19-NOV-10:00 100.71 24-NOV-01:00
December 180.00 01-DEC-00:10 106.85 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 32.31 05-DEC-10:00 115.69 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   106.85   237.03   0.00 0.00 0.00 0.00 12.41   63.10  
Maximum of Months 180.00   106.85   237.03   0.00 0.00 0.00 0.00 89.66   146.70  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 67.16 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 50.17 08-JAN-07:00
February 0.00 01-FEB-00:10 67.16 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 42.26 04-FEB-05:55
March 0.00 01-MAR-00:10 67.16 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 43.75 08-MAR-02:00
April 0.00 01-APR-00:10 67.16 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 0.53 26-APR-13:00 34.81 15-APR-22:00
May 0.00 01-MAY-00:10 67.16 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:05 34.93 27-MAY-03:00
June 0.00 01-JUN-00:10 67.16 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 0.00 01-JUN-00:05 29.24 13-JUN-04:00
July 0.00 01-JUL-00:10 67.16 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 2.37 19-JUL-12:00 26.18 06-JUL-01:00
August 0.00 01-AUG-00:10 67.16 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 2.38 18-AUG-12:00 24.49 24-AUG-02:00
September 0.00 01-SEP-00:10 67.16 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 16.64 29-SEP-11:00 30.18 20-SEP-03:00
October 0.00 01-OCT-00:10 67.16 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 18.40 16-OCT-11:00 34.78 30-OCT-03:00
November 0.00 01-NOV-00:10 67.16 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 0.53 19-NOV-13:00 39.13 23-NOV-22:00
December 0.00 01-DEC-00:10 67.16 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 43.39 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   67.16   232.19   0.00 0.00 0.00 0.00 0.00   24.49  
Maximum of Months 0.00   67.16   232.19   0.00 0.00 0.00 0.00 18.40   50.17  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 67.18 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 9.03 14-JAN-11:00 40.95 08-JAN-07:00
February 180.00 01-FEB-00:10 67.18 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 6.94 01-FEB-11:55 32.21 04-FEB-06:00
March 180.00 01-MAR-00:10 67.18 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 5.31 11-MAR-11:00 34.45 08-MAR-04:00
April 180.00 01-APR-00:10 67.18 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 8.34 26-APR-13:00 27.98 01-APR-06:00
May 180.00 01-MAY-00:10 67.18 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 3.46 03-MAY-10:00 26.05 15-MAY-05:00
June 180.00 01-JUN-00:10 67.18 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 5.31 30-JUN-10:00 19.93 13-JUN-04:40
July 180.00 01-JUL-00:10 67.18 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 10.80 19-JUL-10:00 17.22 07-JUL-21:00
August 180.00 01-AUG-00:10 67.18 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 10.80 15-AUG-10:00 16.36 21-AUG-20:10
September 180.00 01-SEP-00:10 67.18 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 24.88 29-SEP-10:00 19.79 20-SEP-03:10
October 180.00 01-OCT-00:10 67.18 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 25.20 16-OCT-10:01 23.96 30-OCT-04:00
November 180.00 01-NOV-00:10 67.18 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 9.00 19-NOV-09:58 28.11 24-NOV-01:00
December 180.00 01-DEC-00:10 67.18 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 9.02 05-DEC-10:00 32.29 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   67.18   232.26   0.00 0.00 0.00 0.00 3.46   16.36  
Maximum of Months 180.00   67.18   232.26   0.00 0.00 0.00 0.00 25.20   40.95  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 106.87 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 32.34 14-JAN-11:00 146.71 08-JAN-07:00
February 180.00 01-FEB-00:10 106.87 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 19.02 01-FEB-09:51 115.41 04-FEB-06:00
March 180.00 01-MAR-00:10 106.87 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 19.03 11-MAR-11:00 123.45 08-MAR-04:00
April 180.00 01-APR-00:10 106.87 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 25.70 30-APR-10:00 100.25 01-APR-06:00
May 180.00 01-MAY-00:10 106.87 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 12.41 03-MAY-10:00 93.35 15-MAY-05:00
June 180.00 01-JUN-00:10 106.87 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 19.03 30-JUN-10:00 71.39 13-JUN-05:00
July 180.00 01-JUL-00:10 106.87 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 38.70 19-JUL-10:00 56.57 06-JUL-01:00
August 180.00 01-AUG-00:10 106.87 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 38.71 15-AUG-10:00 59.86 28-AUG-07:20
September 180.00 01-SEP-00:10 106.87 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 89.14 29-SEP-10:00 70.90 20-SEP-03:10
October 180.00 01-OCT-00:10 106.87 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 89.32 16-OCT-10:00 85.84 30-OCT-04:00
November 180.00 01-NOV-00:10 106.87 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 32.26 19-NOV-09:58 100.72 24-NOV-01:00
December 180.00 01-DEC-00:10 106.87 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 32.32 05-DEC-10:00 115.70 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   106.87   237.06   0.00 0.00 0.00 0.00 12.41   56.57  
Maximum of Months 180.00   106.87   237.06   0.00 0.00 0.00 0.00 89.32   146.71  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 106.85 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 32.34 14-JAN-11:00 146.70 08-JAN-07:00
February 180.00 01-FEB-00:10 106.85 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 19.52 01-FEB-11:55 115.40 04-FEB-05:55
March 180.00 01-MAR-00:10 106.85 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 19.03 11-MAR-11:00 123.44 08-MAR-02:00
April 180.00 01-APR-00:10 106.85 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 25.70 30-APR-10:00 100.25 01-APR-06:00
May 180.00 01-MAY-00:10 106.85 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 12.41 03-MAY-10:00 93.35 15-MAY-05:00
June 180.00 01-JUN-00:10 106.85 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 19.03 30-JUN-10:00 71.39 13-JUN-05:00
July 180.00 01-JUL-00:10 106.85 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 38.69 19-JUL-10:00 58.54 07-JUL-21:00
August 180.00 01-AUG-00:10 106.85 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 38.70 15-AUG-10:00 59.86 28-AUG-07:20
September 180.00 01-SEP-00:10 106.85 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 89.14 29-SEP-10:00 70.89 20-SEP-03:10
October 180.00 01-OCT-00:10 106.85 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 89.31 16-OCT-10:00 85.84 30-OCT-04:00
November 180.00 01-NOV-00:10 106.85 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 32.25 19-NOV-10:20 100.71 24-NOV-01:00
December 180.00 01-DEC-00:10 106.85 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 32.29 05-DEC-10:00 115.69 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   106.85   237.03   0.00 0.00 0.00 0.00 12.41   58.54  
Maximum of Months 180.00   106.85   237.03   0.00 0.00 0.00 0.00 89.31   146.70  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 1044.00 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 32.70 13-JAN-14:00 176.44 08-JAN-07:00
February 2263.36 01-FEB-00:10 1044.00 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 31.78 01-FEB-11:55 147.69 04-FEB-05:55
March 2263.36 01-MAR-00:10 1044.00 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 17.01 11-MAR-11:50 149.49 08-MAR-02:00
April 2263.36 01-APR-00:10 1044.00 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 38.31 26-APR-13:00 120.29 01-APR-06:00
May 2263.36 01-MAY-00:10 1044.00 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 13.13 03-MAY-12:00 120.49 27-MAY-03:00
June 2263.36 01-JUN-00:10 1044.00 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 20.39 29-JUN-10:55 94.54 13-JUN-05:00
July 2263.36 01-JUL-00:10 1044.00 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 42.78 19-JUL-10:55 82.61 06-JUL-01:00
August 2263.36 01-AUG-00:10 1044.00 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 41.94 14-AUG-10:55 74.20 24-AUG-02:00
September 2263.36 01-SEP-00:10 1044.00 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 101.99 29-SEP-11:00 96.67 20-SEP-03:00
October 2263.36 01-OCT-23:10 1044.00 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 106.13 16-OCT-11:00 115.37 30-OCT-03:00
November 2263.36 01-NOV-00:10 1044.00 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 35.20 19-NOV-13:00 132.93 29-NOV-23:00
December 2263.36 01-DEC-00:10 1044.00 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 32.47 16-DEC-13:00 146.21 23-DEC-04:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   1044.00   0.00 0.00 0.00 0.00 0.00 13.13   74.20  
Maximum of Months 2263.36   1044.00   0.00 0.00 0.00 0.00 0.00 106.13   176.44  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 106.87 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 31.95 14-JAN-11:00 147.18 08-JAN-07:00
February 180.00 01-FEB-00:10 106.87 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 18.63 01-FEB-09:51 115.86 04-FEB-06:00
March 180.00 01-MAR-00:10 106.87 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 18.64 11-MAR-11:00 123.90 08-MAR-04:00
April 180.00 01-APR-00:10 106.87 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 25.31 30-APR-10:00 100.69 01-APR-06:00
May 180.00 01-MAY-00:10 106.87 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 12.01 03-MAY-10:00 93.80 15-MAY-05:00
June 180.00 01-JUN-00:10 106.87 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 18.64 30-JUN-10:00 71.82 13-JUN-04:40
July 180.00 01-JUL-00:10 106.87 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 38.31 19-JUL-10:00 56.99 06-JUL-01:00
August 180.00 01-AUG-00:10 106.87 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 38.32 15-AUG-10:00 52.54 28-AUG-07:20
September 180.00 01-SEP-00:10 106.87 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 88.78 29-SEP-10:00 71.33 20-SEP-03:10
October 180.00 01-OCT-00:10 106.87 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 88.95 16-OCT-10:00 86.28 30-OCT-04:00
November 180.00 01-NOV-00:10 106.87 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 31.87 19-NOV-09:53 101.16 24-NOV-01:00
December 180.00 01-DEC-00:10 106.87 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 31.93 05-DEC-10:00 116.15 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   106.87   237.06   0.00 0.00 0.00 0.00 12.01   52.54  
Maximum of Months 180.00   106.87   237.06   0.00 0.00 0.00 0.00 88.95   147.18  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 106.85 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 31.95 14-JAN-11:00 147.16 08-JAN-07:00
February 180.00 01-FEB-00:10 106.85 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 23.34 01-FEB-11:55 115.85 04-FEB-06:00
March 180.00 01-MAR-00:10 106.85 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 18.64 11-MAR-11:00 123.89 08-MAR-04:00
April 180.00 01-APR-00:10 106.85 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 25.31 30-APR-10:00 100.69 01-APR-06:00
May 180.00 01-MAY-00:10 106.85 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 12.01 03-MAY-10:00 93.79 15-MAY-05:00
June 180.00 01-JUN-00:10 106.85 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 18.64 30-JUN-10:00 72.34 02-JUN-20:00
July 180.00 01-JUL-00:10 106.85 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 38.31 19-JUL-10:00 69.10 10-JUL-18:01
August 180.00 01-AUG-00:10 106.85 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 38.32 15-AUG-10:00 67.24 26-AUG-18:00
September 180.00 01-SEP-00:10 106.85 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 88.77 29-SEP-10:00 71.32 20-SEP-03:10
October 180.00 01-OCT-00:10 106.85 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 89.22 16-OCT-10:01 86.27 30-OCT-04:00
November 180.00 01-NOV-00:10 106.85 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 31.87 19-NOV-09:58 101.16 24-NOV-01:00
December 180.00 01-DEC-00:10 106.85 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 31.92 05-DEC-10:00 116.14 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   106.85   237.03   0.00 0.00 0.00 0.00 12.01   67.24  
Maximum of Months 180.00   106.85   237.03   0.00 0.00 0.00 0.00 89.22   147.16  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 67.18 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 16.35 14-JAN-11:00 75.30 08-JAN-07:00
February 180.00 01-FEB-00:10 67.18 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 9.53 01-FEB-09:51 59.28 04-FEB-06:00
March 180.00 01-MAR-00:10 67.18 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 9.53 11-MAR-11:00 63.39 08-MAR-04:00
April 180.00 01-APR-00:10 67.18 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 12.95 30-APR-10:00 51.52 01-APR-06:00
May 180.00 01-MAY-00:10 67.18 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 6.15 03-MAY-10:00 47.99 15-MAY-05:00
June 180.00 01-JUN-00:10 67.18 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 9.54 30-JUN-10:00 36.75 13-JUN-05:00
July 180.00 01-JUL-00:10 67.18 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 19.60 19-JUL-10:00 29.16 06-JUL-01:00
August 180.00 01-AUG-00:10 67.18 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 19.61 15-AUG-10:00 27.54 28-AUG-07:20
September 180.00 01-SEP-00:10 67.18 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 45.42 29-SEP-10:00 36.49 20-SEP-03:10
October 180.00 01-OCT-00:10 67.18 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 45.51 16-OCT-10:00 44.14 30-OCT-04:00
November 180.00 01-NOV-00:10 67.18 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 15.07 19-NOV-09:50 51.98 30-NOV-03:00
December 180.00 01-DEC-00:10 67.18 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 16.33 05-DEC-09:55 59.43 22-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   67.18   232.26   0.00 0.00 0.00 0.00 6.15   27.54  
Maximum of Months 180.00   67.18   232.26   0.00 0.00 0.00 0.00 45.51   75.30  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 2486.81 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 50.18 13-JAN-14:00 373.15 08-JAN-07:00
February 26988.77 01-FEB-00:10 2486.81 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 52.68 01-FEB-11:55 331.63 04-FEB-05:55
March 26988.77 01-MAR-00:10 2486.81 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 15.35 11-MAR-11:50 341.06 08-MAR-02:00
April 26988.77 01-APR-00:10 2486.81 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 57.79 26-APR-13:00 295.77 01-APR-06:00
May 26988.77 01-MAY-00:10 2486.81 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 11.21 03-MAY-12:00 278.99 15-MAY-05:00
June 26988.77 01-JUN-00:10 2486.81 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 30.62 29-JUN-10:55 224.89 13-JUN-04:40
July 26988.77 01-JUL-00:10 2486.81 03-JUL-19:10 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 78.02 19-JUL-10:50 188.00 06-JUL-01:00
August 26988.77 01-AUG-00:10 2486.81 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 78.96 14-AUG-10:55 170.32 31-AUG-04:00
September 26988.77 01-SEP-00:10 2486.81 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 201.28 29-SEP-11:00 223.35 20-SEP-03:10
October 26988.77 01-OCT-23:10 2486.81 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 216.62 16-OCT-11:00 260.40 30-OCT-04:00
November 26988.77 01-NOV-00:10 2486.81 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 56.29 19-NOV-13:00 297.12 24-NOV-01:00
December 26988.77 01-DEC-00:10 2486.81 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 47.63 19-DEC-13:00 328.02 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   2486.81   6747.90   0.00 0.00 0.00 0.00 11.21   170.32  
Maximum of Months 26988.77   2486.81   6747.90   0.00 0.00 0.00 0.00 216.62   373.15  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 2486.81 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 45.08 13-JAN-14:00 375.80 08-JAN-07:00
February 26988.77 01-FEB-00:10 2486.81 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 47.71 01-FEB-11:55 332.42 04-FEB-05:55
March 26988.77 01-MAR-00:10 2486.81 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 10.82 11-MAR-11:50 344.31 08-MAR-02:00
April 26988.77 01-APR-00:10 2486.81 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 53.40 26-APR-13:00 295.77 01-APR-06:00
May 26988.77 01-MAY-00:10 2486.81 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 7.21 03-MAY-12:00 278.99 15-MAY-05:00
June 26988.77 01-JUN-00:10 2486.81 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 27.04 29-JUN-10:55 224.89 13-JUN-04:40
July 26988.77 01-JUL-00:10 2486.81 03-JUL-19:10 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 74.66 19-JUL-10:50 188.00 06-JUL-01:00
August 26988.77 01-AUG-00:10 2486.81 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 75.57 14-AUG-10:55 170.32 31-AUG-04:00
September 26988.77 01-SEP-00:10 2486.81 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 198.08 29-SEP-10:50 223.35 20-SEP-03:10
October 26988.77 01-OCT-23:10 2486.81 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 214.25 16-OCT-11:00 260.41 30-OCT-04:00
November 26988.77 01-NOV-00:10 2486.81 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 52.57 19-NOV-13:00 297.13 24-NOV-01:00
December 26988.77 01-DEC-00:10 2486.81 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 43.54 19-DEC-13:00 330.16 23-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   2486.81   6747.90   0.00 0.00 0.00 0.00 7.21   170.32  
Maximum of Months 26988.77   2486.81   6747.90   0.00 0.00 0.00 0.00 214.25   375.80  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 981.75 02-JAN-20:10 14604.56 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 27.84 14-JAN-11:00 330.45 03-JAN-07:00
February 2401.70 01-FEB-00:10 981.75 01-FEB-20:10 14604.56 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 27.69 01-FEB-11:55 282.90 05-FEB-06:20
March 2401.70 01-MAR-00:10 981.75 01-MAR-20:10 14604.56 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 0.00 01-MAR-00:03 294.25 29-MAR-23:00
April 2401.70 01-APR-00:10 981.75 03-APR-19:10 14604.56 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 42.05 26-APR-13:00 264.66 01-APR-06:00
May 2401.70 01-MAY-00:10 981.75 01-MAY-19:10 14604.56 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 0.00 01-MAY-00:05 248.14 19-MAY-05:00
June 2401.70 01-JUN-00:10 981.75 01-JUN-19:10 14604.56 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 13.20 29-JUN-10:55 201.15 13-JUN-05:00
July 2401.70 01-JUL-00:10 981.75 03-JUL-19:10 14604.56 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 56.41 19-JUL-12:00 152.26 06-JUL-01:00
August 2401.70 01-AUG-00:10 981.75 01-AUG-19:10 14604.56 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 56.52 18-AUG-12:00 152.01 28-AUG-06:10
September 2401.70 01-SEP-00:10 981.75 01-SEP-19:10 14604.56 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 167.15 29-SEP-11:00 184.17 20-SEP-06:00
October 2401.70 01-OCT-23:10 981.75 02-OCT-19:10 14604.56 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 180.95 16-OCT-11:00 232.83 29-OCT-06:00
November 2401.70 01-NOV-00:10 981.75 01-NOV-19:10 14604.56 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 42.11 19-NOV-13:00 265.89 23-NOV-22:00
December 2401.70 01-DEC-00:10 981.75 01-DEC-20:10 14604.56 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 27.93 16-DEC-13:00 298.99 22-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   981.75   14604.56   22492.83   0.00 0.00 0.00 0.00   152.01  
Maximum of Months 2401.70   981.75   14604.56   22492.83   0.00 0.00 0.00 180.95   330.45  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 1104.91 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 53.39 14-JAN-11:00 313.20 08-JAN-07:00
February 2395.44 01-FEB-00:10 1104.91 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 52.49 01-FEB-11:55 250.11 04-FEB-05:55
March 2395.44 01-MAR-00:10 1104.91 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 22.96 11-MAR-11:00 263.40 08-MAR-02:00
April 2395.44 01-APR-00:10 1104.91 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 57.66 26-APR-13:00 213.77 01-APR-06:00
May 2395.44 01-MAY-00:10 1104.91 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 15.04 03-MAY-12:00 205.79 27-MAY-03:00
June 2395.44 01-JUN-00:10 1104.91 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 30.65 29-JUN-10:55 161.23 13-JUN-04:00
July 2395.44 01-JUL-00:10 1104.91 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 70.81 19-JUL-10:55 140.41 06-JUL-01:00
August 2395.44 01-AUG-00:10 1104.91 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 70.02 14-AUG-10:55 126.24 28-AUG-03:00
September 2395.44 01-SEP-00:10 1104.91 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 172.65 29-SEP-11:00 162.26 20-SEP-03:00
October 2395.44 01-OCT-23:10 1104.91 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 180.57 16-OCT-11:00 194.26 27-OCT-04:00
November 2395.44 01-NOV-00:10 1104.91 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 54.81 19-NOV-13:00 229.09 29-NOV-23:00
December 2395.44 01-DEC-00:10 1104.91 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 51.04 05-DEC-09:55 247.85 03-DEC-01:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   1104.91   0.00 0.00 0.00 0.00 0.00 15.04   126.24  
Maximum of Months 2395.44   1104.91   0.00 0.00 0.00 0.00 0.00 180.57   313.20  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 15861.34 08-JAN-07:00 8945.92 2781.33 4055.80 0.00 0.00 0.00 0.00 0.00 0.00
February 12102.54 01-FEB-11:35 5111.95 4635.67 7097.65 0.00 0.00 0.00 0.00 0.00 0.00
March 11656.91 08-MAR-02:00 11501.89 1390.72 2534.88 0.00 0.00 0.00 0.00 0.00 0.00
April 11575.87 30-APR-10:33 11501.89 8343.99 12167.41 0.00 0.00 0.00 0.00 0.00 0.00
May 11417.12 04-MAY-18:10 62621.41 51919.01 63878.88 0.00 0.00 0.00 0.00 0.00 0.00
June 11462.08 25-JUN-10:33 11501.89 8343.99 12167.41 0.00 0.00 0.00 0.00 0.00 0.00
July 12341.08 23-JUL-10:33 11501.89 8343.99 12167.41 0.00 0.00 0.00 0.00 0.00 0.00
August 12316.24 13-AUG-10:33 11501.89 8343.99 12167.41 0.00 0.00 0.00 0.00 0.00 0.00
September 12988.76 30-SEP-10:35 7667.93 4635.67 7097.65 0.00 0.00 0.00 0.00 0.00 0.00
October 13474.76 15-OCT-10:33 11501.89 8343.99 12167.41 0.00 0.00 0.00 0.00 0.00 0.00
November 12998.52 19-NOV-11:33 11501.89 8343.99 12167.41 0.00 0.00 0.00 0.00 0.00 0.00
December 12295.82 12-DEC-22:00 10223.90 7417.00 9125.55 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11417.12   5111.95 1390.72 2534.88 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15861.34   62621.41 51919.01 63878.88 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3161.42 14-JAN-12:40 389.84 128.08 252.59 0.00 0.00 0.00 0.00 15.30 0.00
February 2741.89 02-FEB-12:40 259.90 128.08 252.59 0.00 0.00 0.00 0.00 0.00 54.64
March 2448.53 11-MAR-13:00 389.84 128.08 252.59 0.00 0.00 0.00 0.00 0.00 0.03
April 1999.71 08-APR-10:35 779.69 256.16 505.18 0.00 0.00 0.00 0.00 0.00 11.27
May 1939.41 04-MAY-10:35 519.79 256.16 505.18 0.00 0.00 0.00 0.00 0.00 3.74
June 1856.46 25-JUN-10:33 1169.53 461.08 866.03 0.00 0.00 0.00 0.00 14.05 0.00
July 2044.19 30-JUL-10:33 1169.53 461.08 866.03 0.00 0.00 0.00 0.00 24.42 0.00
August 2119.38 27-AUG-10:33 1169.53 461.08 866.03 0.00 0.00 0.00 0.00 4.01 0.00
September 3398.01 30-SEP-13:10 389.84 128.08 252.59 0.00 0.00 0.00 0.00 89.26 0.00
October 3998.47 16-OCT-12:10 259.90 128.08 252.59 0.00 0.00 0.00 0.00 129.44 0.00
November 3489.96 19-NOV-12:30 389.84 153.69 288.68 0.00 0.00 0.00 0.00 28.55 0.00
December 3335.61 19-DEC-12:50 259.90 128.08 252.59 0.00 0.00 0.00 0.00 21.01 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1856.46   259.90 128.08 252.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3998.47   1169.53 461.08 866.03 0.00 0.00 0.00 0.00 129.44 54.64



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1551.65 08-JAN-07:00 1053.36 177.98 334.29 0.00 0.00 0.00 0.00 0.00 96.90
February 1362.14 03-FEB-21:00 1053.36 533.93 793.93 0.00 0.00 0.00 0.00 0.00 49.39
March 1384.25 23-MAR-18:10 6320.16 2847.65 4512.87 0.00 0.00 0.00 0.00 0.00 29.66
April 1428.50 26-APR-18:10 6320.16 2847.65 4512.87 0.00 0.00 0.00 0.00 0.00 19.87
May 1428.99 04-MAY-18:10 7373.52 3322.26 5265.02 0.00 0.00 0.00 0.00 0.00 19.14
June 1456.41 29-JUN-18:10 6320.16 2847.65 4512.87 0.00 0.00 0.00 0.00 0.00 7.35
July 1513.89 31-JUL-21:00 1203.84 474.61 752.15 0.00 0.00 0.00 0.00 0.00 22.61
August 1594.46 18-AUG-21:00 1203.84 474.61 752.15 0.00 0.00 0.00 0.00 0.00 22.63
September 1805.05 29-SEP-21:00 1203.84 474.61 752.15 0.00 0.00 0.00 0.00 2.64 0.00
October 1854.00 16-OCT-20:10 1203.84 474.61 752.15 0.00 0.00 0.00 0.00 0.00 15.74
November 1436.15 19-NOV-11:33 1354.32 533.93 1002.86 0.00 0.00 0.00 0.00 13.68 0.00
December 1381.16 05-DEC-21:00 1053.36 533.93 793.93 0.00 0.00 0.00 0.00 0.00 35.47
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1362.14   1053.36 177.98 334.29 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1854.00   7373.52 3322.26 5265.02 0.00 0.00 0.00 0.00 13.68 96.90



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1064.80 28-JAN-07:00 222.77 205.25 353.45 0.00 0.00 0.00 0.00 0.00 205.22
February 994.91 02-FEB-11:33 190.94 513.13 927.81 0.00 0.00 0.00 0.00 0.00 26.62
March 1014.73 19-MAR-10:33 286.42 615.76 1060.35 0.00 0.00 0.00 0.00 0.00 24.05
April 1085.13 30-APR-10:33 286.42 615.76 1060.35 0.00 0.00 0.00 0.00 38.73 0.00
May 1105.27 04-MAY-18:10 1559.38 3831.39 5566.86 0.00 0.00 0.00 0.00 0.00 39.85
June 1154.89 25-JUN-10:33 286.42 615.76 1060.35 0.00 0.00 0.00 0.00 5.32 0.00
July 1212.39 23-JUL-10:33 286.42 615.76 1060.35 0.00 0.00 0.00 0.00 30.47 0.00
August 1202.25 19-AUG-10:35 190.94 342.09 618.54 0.00 0.00 0.00 0.00 20.34 0.00
September 1252.29 30-SEP-10:35 190.94 342.09 618.54 0.00 0.00 0.00 0.00 77.47 0.00
October 1241.63 16-OCT-10:35 127.30 342.09 618.54 0.00 0.00 0.00 0.00 134.68 0.00
November 1068.15 19-NOV-11:33 286.42 615.76 1060.35 0.00 0.00 0.00 0.00 41.21 0.00
December 1037.39 19-DEC-11:35 127.30 342.09 618.54 0.00 0.00 0.00 0.00 31.02 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 994.91   127.30 205.25 353.45 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1252.29   1559.38 3831.39 5566.86 0.00 0.00 0.00 0.00 134.68 205.22



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 552.97 20-JAN-11:35 97.92 76.31 178.43 0.00 0.00 0.00 0.00 0.00 2.35
February 528.43 04-FEB-11:33 220.32 114.47 267.65 0.00 0.00 0.00 0.00 0.00 7.00
March 538.24 23-MAR-10:35 97.92 76.31 178.43 0.00 0.00 0.00 0.00 2.54 0.00
April 576.83 30-APR-10:33 220.32 137.35 305.88 0.00 0.00 0.00 0.00 22.42 0.00
May 585.63 04-MAY-10:35 97.92 76.31 178.43 0.00 0.00 0.00 0.00 0.00 1.25
June 611.30 25-JUN-10:33 220.32 137.35 305.88 0.00 0.00 0.00 0.00 3.39 0.00
July 642.86 23-JUL-10:33 220.32 137.35 305.88 0.00 0.00 0.00 0.00 17.81 0.00
August 637.83 19-AUG-10:35 146.88 76.31 178.43 0.00 0.00 0.00 0.00 11.93 0.00
September 668.69 30-SEP-10:35 146.88 76.31 178.43 0.00 0.00 0.00 0.00 44.50 0.00
October 665.51 16-OCT-10:35 97.92 76.31 178.43 0.00 0.00 0.00 0.00 77.29 0.00
November 572.44 19-NOV-11:33 220.32 137.35 305.88 0.00 0.00 0.00 0.00 23.42 0.00
December 554.70 19-DEC-11:35 97.92 76.31 178.43 0.00 0.00 0.00 0.00 17.65 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 528.43   97.92 76.31 178.43 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 668.69   220.32 137.35 305.88 0.00 0.00 0.00 0.00 77.29 7.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 37428.41 24-JAN-21:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 103.34
February 37314.88 03-FEB-21:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 164.38
March 37539.82 23-MAR-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 148.51
April 37832.76 26-APR-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 102.91
May 37854.53 04-MAY-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 103.02
June 37865.34 30-JUN-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 117.91
July 38124.39 19-JUL-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 73.00
August 38082.93 18-AUG-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 73.08
September 38384.54 29-SEP-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 14.22 0.00
October 38223.91 16-OCT-20:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 43.45
November 37314.36 28-NOV-21:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 164.64
December 37569.15 05-DEC-21:00 705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 118.47
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 37314.36   705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 38384.54   705.60 360.62 4572.80 39726.58 0.00 0.00 0.00 14.22 164.64



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 12632.85 14-JAN-12:40 5122.80 86.54 355.63 0.00 0.00 0.00 0.00 33.85 0.00
February 10599.02 04-FEB-12:30 5122.80 86.54 355.63 0.00 0.00 0.00 0.00 0.00 77.17
March 10471.12 11-MAR-12:50 5122.80 86.54 355.63 0.00 0.00 0.00 0.00 0.00 0.04
April 9278.63 08-APR-10:35 10245.60 173.08 711.25 0.00 0.00 0.00 0.00 0.00 31.90
May 8811.40 04-MAY-18:10 83672.40 5022.30 6401.28 0.00 0.00 0.00 0.00 0.00 100.16
June 8771.21 29-JUN-18:10 71719.20 3054.18 5486.82 0.00 0.00 0.00 0.00 0.00 27.12
July 9335.90 30-JUL-10:33 15368.40 311.54 1219.29 0.00 0.00 0.00 0.00 50.86 0.00
August 9671.00 27-AUG-10:33 15368.40 311.54 1219.29 0.00 0.00 0.00 0.00 5.84 0.00
September 12075.89 30-SEP-12:00 5122.80 86.54 355.63 0.00 0.00 0.00 0.00 197.59 0.00
October 13648.97 15-OCT-12:00 5122.80 103.85 406.43 0.00 0.00 0.00 0.00 198.53 0.00
November 13854.22 19-NOV-11:00 8538.00 103.85 406.43 0.00 0.00 0.00 0.00 50.65 0.00
December 12513.62 16-DEC-13:00 5122.80 86.54 355.63 0.00 0.00 0.00 0.00 50.92 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8771.21   5122.80 86.54 355.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13854.22   83672.40 5022.30 6401.28 0.00 0.00 0.00 0.00 198.53 100.16



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 33315.50 08-JAN-07:00 35484.54 3050.31 4222.82 0.00 0.00 0.00 0.00 0.00 1608.97
February 30893.74 03-FEB-21:20 40553.76 8516.30 9501.36 0.00 0.00 0.00 0.00 0.00 938.58
March 29915.33 24-MAR-21:10 45622.98 6387.23 7389.94 0.00 0.00 0.00 0.00 0.00 829.84
April 30487.90 26-APR-21:52 364983.84 51097.83 59119.55 0.00 0.00 0.00 0.00 0.00 599.08
May 31535.99 04-MAY-21:53 319360.86 44710.60 51729.60 0.00 0.00 0.00 0.00 0.00 522.32
June 31561.52 30-JUN-21:52 410606.82 57485.05 66509.49 0.00 0.00 0.00 0.00 0.00 590.32
July 32990.25 19-JUL-21:52 364983.84 51097.83 59119.55 0.00 0.00 0.00 0.00 0.00 445.54
August 33772.15 18-AUG-21:10 45622.98 6387.23 7389.94 0.00 0.00 0.00 0.00 0.00 370.31
September 37786.55 29-SEP-21:10 45622.98 6387.23 7389.94 0.00 0.00 0.00 0.00 42.15 0.00
October 38344.96 16-OCT-21:10 45622.98 6387.23 7389.94 0.00 0.00 0.00 0.00 0.00 419.88
November 32274.65 19-NOV-11:33 45622.98 8239.52 12668.47 0.00 0.00 0.00 0.00 170.94 0.00
December 33179.01 05-DEC-22:10 45622.98 6387.23 7389.94 0.00 0.00 0.00 0.00 0.00 510.89
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 29915.33   35484.54 3050.31 4222.82 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 38344.96   410606.82 57485.05 66509.49 0.00 0.00 0.00 0.00 170.94 1608.97



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2750.24 14-JAN-16:01 378.00 246.87 534.70 0.00 0.00 0.00 0.00 2.01 0.00
February 2708.39 03-FEB-16:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 0.00 15.44
March 2498.79 07-MAR-16:02 583.20 179.54 410.90 0.00 0.00 0.00 0.00 0.00 61.26
April 2543.88 11-APR-15:02 583.20 179.54 410.90 0.00 0.00 0.00 0.00 0.01 0.00
May 2615.10 28-MAY-15:01 378.00 246.87 534.70 0.00 0.00 0.00 0.00 0.00 13.20
June 2637.56 18-JUN-15:02 324.00 211.60 458.31 0.00 0.00 0.00 0.00 0.62 0.00
July 2745.57 22-JUL-15:02 324.00 211.60 458.31 0.00 0.00 0.00 0.00 19.55 0.00
August 2685.55 06-AUG-15:02 324.00 211.60 458.31 0.00 0.00 0.00 0.00 13.77 0.00
September 2620.57 09-SEP-15:02 324.00 211.60 458.31 0.00 0.00 0.00 0.00 0.00 5.67
October 2888.68 13-OCT-15:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 31.86 0.00
November 2648.20 27-NOV-16:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 0.00 20.61
December 2764.27 05-DEC-16:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 0.00 0.60
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2498.79   324.00 179.54 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2888.68   680.40 246.87 534.70 0.00 0.00 0.00 0.00 31.86 61.26



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2621.32 14-JAN-16:01 378.00 246.84 534.64 0.00 0.00 0.00 0.00 2.56 0.00
February 2579.95 03-FEB-16:01 680.40 209.43 479.33 0.00 0.00 0.00 0.00 0.00 14.87
March 2491.60 23-MAR-15:02 583.20 179.51 410.85 0.00 0.00 0.00 0.00 0.00 6.16
April 2599.43 23-APR-18:11 1170.00 1068.54 1290.50 0.00 0.00 0.00 0.00 0.00 65.81
May 2515.41 17-MAY-15:02 583.20 179.51 410.85 0.00 0.00 0.00 0.00 0.00 7.23
June 2538.84 13-JUN-15:02 583.20 179.51 410.85 0.00 0.00 0.00 0.00 0.00 6.15
July 2609.10 22-JUL-15:02 324.00 211.57 458.26 0.00 0.00 0.00 0.00 19.09 0.00
August 2602.21 06-AUG-15:02 324.00 211.57 458.26 0.00 0.00 0.00 0.00 13.60 0.00
September 2575.53 30-SEP-08:61 486.00 538.54 1469.59 0.00 0.00 0.00 0.00 9.14 0.00
October 2848.89 14-OCT-08:61 540.00 598.38 1632.88 0.00 0.00 0.00 0.00 29.04 0.00
November 2524.83 27-NOV-16:01 680.40 209.43 479.33 0.00 0.00 0.00 0.00 0.00 20.10
December 2635.48 05-DEC-16:01 680.40 209.43 479.33 0.00 0.00 0.00 0.00 0.00 0.07
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2491.60   324.00 179.51 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2848.89   1170.00 1068.54 1632.88 0.00 0.00 0.00 0.00 29.04 65.81



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 591.66 14-JAN-12:40 0.00 22.16 74.82 0.00 0.00 0.00 0.00 0.00 2.57
February 519.18 02-FEB-12:40 0.00 18.81 67.08 0.00 0.00 0.00 0.00 0.00 13.98
March 443.09 11-MAR-13:20 0.00 22.16 74.82 0.00 0.00 0.00 0.00 0.00 5.06
April 315.82 08-APR-12:50 0.00 22.16 74.82 0.00 0.00 0.00 0.00 0.00 8.56
May 250.78 02-MAY-15:03 0.00 112.83 402.47 0.00 0.00 0.00 0.00 0.00 9.81
June 230.86 28-JUN-15:05 0.00 112.83 402.47 0.00 0.00 0.00 0.00 0.00 7.25
July 259.06 18-JUL-15:03 0.00 112.83 402.47 0.00 0.00 0.00 0.00 0.00 1.32
August 303.94 30-AUG-13:00 0.00 18.81 67.08 0.00 0.00 0.00 0.00 0.00 5.06
September 563.61 30-SEP-13:10 0.00 22.16 74.82 0.00 0.00 0.00 0.00 9.56 0.00
October 668.68 16-OCT-12:30 0.00 18.81 67.08 0.00 0.00 0.00 0.00 14.99 0.00
November 630.35 19-NOV-13:00 0.00 22.16 74.82 0.00 0.00 0.00 0.00 0.53 0.00
December 605.49 19-DEC-13:00 0.00 18.81 67.08 0.00 0.00 0.00 0.00 0.00 1.32
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 230.86   0.00 18.81 67.08 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 668.68   0.00 112.83 402.47 0.00 0.00 0.00 0.00 14.99 13.98



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 878.30 15-JAN-16:01 378.00 155.19 523.86 0.00 0.00 0.00 0.00 0.00 1.56
February 838.64 03-FEB-16:01 680.40 131.67 469.67 0.00 0.00 0.00 0.00 0.00 3.33
March 841.83 10-MAR-16:02 583.20 112.86 402.58 0.00 0.00 0.00 0.00 0.00 0.86
April 863.00 01-APR-15:02 324.00 133.02 449.03 0.00 0.00 0.00 0.00 0.93 0.00
May 858.77 03-MAY-15:02 583.20 112.86 402.58 0.00 0.00 0.00 0.00 0.00 2.03
June 844.56 20-JUN-15:02 583.20 112.86 402.58 0.00 0.00 0.00 0.00 0.00 2.04
July 869.08 18-JUL-18:02 831.60 358.74 758.70 0.00 0.00 0.00 0.00 0.69 0.00
August 845.11 19-AUG-15:02 324.00 133.02 449.03 0.00 0.00 0.00 0.00 5.33 0.00
September 829.99 01-SEP-15:02 583.20 112.86 402.58 0.00 0.00 0.00 0.00 0.00 4.20
October 962.32 14-OCT-08:61 540.00 376.21 1599.98 0.00 0.00 0.00 0.00 7.90 0.00
November 872.84 19-NOV-09:41 432.00 300.96 1279.98 0.00 0.00 0.00 0.00 6.57 0.00
December 880.10 05-DEC-16:01 680.40 131.67 469.67 0.00 0.00 0.00 0.00 0.16 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 829.99   324.00 112.86 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 962.32   831.60 376.21 1599.98 0.00 0.00 0.00 0.00 7.90 4.20



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2438.42 14-JAN-16:01 378.00 246.87 534.70 0.00 0.00 0.00 0.00 1.93 0.00
February 2403.80 01-FEB-09:02 216.00 282.13 679.57 0.00 0.00 0.00 0.00 0.00 2.16
March 2318.61 23-MAR-15:02 583.20 179.54 410.90 0.00 0.00 0.00 0.00 0.00 6.04
April 2346.25 30-APR-15:02 324.00 211.60 458.31 0.00 0.00 0.00 0.00 0.90 0.00
May 2303.81 24-MAY-08:62 216.00 282.13 679.57 0.00 0.00 0.00 0.00 0.00 32.41
June 2285.31 30-JUN-15:02 583.20 179.54 410.90 0.00 0.00 0.00 0.00 1.55 0.00
July 2410.67 19-JUL-15:02 583.20 179.54 410.90 0.00 0.00 0.00 0.00 26.00 0.00
August 2433.56 14-AUG-15:02 583.20 179.54 410.90 0.00 0.00 0.00 0.00 20.52 0.00
September 2356.63 13-SEP-15:02 583.20 179.54 410.90 0.00 0.00 0.00 0.00 0.62 0.00
October 2591.41 14-OCT-08:61 540.00 598.45 1633.07 0.00 0.00 0.00 0.00 30.98 0.00
November 2389.28 27-NOV-09:02 216.00 282.13 679.57 0.00 0.00 0.00 0.00 0.00 10.46
December 2474.12 05-DEC-09:02 216.00 282.13 679.57 0.00 0.00 0.00 0.00 10.60 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2285.31   216.00 179.54 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2591.41   583.20 598.45 1633.07 0.00 0.00 0.00 0.00 30.98 32.41



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2324.13 14-JAN-16:01 378.00 246.84 534.64 0.00 0.00 0.00 0.00 2.62 0.00
February 2369.17 01-FEB-09:51 252.00 329.11 792.74 0.00 0.00 0.00 0.00 8.36 0.00
March 2372.21 23-MAR-08:51 324.00 423.14 1019.23 0.00 0.00 0.00 0.00 0.00 34.35
April 2551.76 26-APR-08:51 324.00 423.14 1019.23 0.00 0.00 0.00 0.00 0.00 12.98
May 2544.50 04-MAY-08:51 360.00 470.16 1132.48 0.00 0.00 0.00 0.00 0.00 32.16
June 2608.02 23-JUN-08:51 360.00 470.16 1132.48 0.00 0.00 0.00 0.00 0.00 26.91
July 2606.57 04-JUL-08:51 540.00 598.38 1632.88 0.00 0.00 0.00 0.00 0.00 23.77
August 2462.42 14-AUG-08:51 324.00 423.14 1019.23 0.00 0.00 0.00 0.00 0.00 3.42
September 2493.60 30-SEP-08:61 486.00 538.54 1469.59 0.00 0.00 0.00 0.00 0.00 0.89
October 2896.67 17-OCT-08:21 360.00 470.16 1132.48 0.00 0.00 0.00 0.00 13.64 0.00
November 2246.88 27-NOV-09:52 216.00 282.09 679.49 0.00 0.00 0.00 0.00 0.00 2.20
December 2541.12 05-DEC-09:41 288.00 376.12 905.99 0.00 0.00 0.00 0.00 14.22 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2246.88   216.00 246.84 534.64 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2896.67   540.00 598.38 1632.88 0.00 0.00 0.00 0.00 14.22 34.35



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1806.72 09-JAN-06:00 2263.36 232.00 0.00 0.00 0.00 0.00 0.00 0.00 167.53
February 1620.41 04-FEB-11:33 2263.36 870.00 0.00 0.00 0.00 0.00 0.00 0.00 13.20
March 1627.04 12-MAR-10:33 2263.36 1044.00 0.00 0.00 0.00 0.00 0.00 0.00 4.84
April 1727.95 30-APR-10:33 2263.36 1044.00 0.00 0.00 0.00 0.00 0.00 27.54 0.00
May 1735.63 04-MAY-10:35 1005.94 580.00 0.00 0.00 0.00 0.00 0.00 0.00 3.30
June 1794.07 25-JUN-10:33 2263.36 1044.00 0.00 0.00 0.00 0.00 0.00 3.61 0.00
July 1883.94 23-JUL-10:33 2263.36 1044.00 0.00 0.00 0.00 0.00 0.00 22.94 0.00
August 1901.25 19-AUG-10:35 1508.90 580.00 0.00 0.00 0.00 0.00 0.00 13.73 0.00
September 1974.64 30-SEP-10:35 1508.90 580.00 0.00 0.00 0.00 0.00 0.00 57.90 0.00
October 1976.23 16-OCT-10:35 1005.94 580.00 0.00 0.00 0.00 0.00 0.00 101.17 0.00
November 1736.41 19-NOV-11:33 2263.36 1044.00 0.00 0.00 0.00 0.00 0.00 27.97 0.00
December 1661.66 05-DEC-11:35 1005.94 580.00 0.00 0.00 0.00 0.00 0.00 7.76 0.00
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1620.41   1005.94 232.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1976.23   2263.36 1044.00 0.00 0.00 0.00 0.00 0.00 101.17 167.53



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2858.48 14-JAN-16:01 378.00 246.87 534.70 0.00 0.00 0.00 0.00 1.54 0.00
February 2809.84 03-FEB-16:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 0.00 15.80
March 2593.19 07-MAR-16:02 583.20 179.54 410.90 0.00 0.00 0.00 0.00 0.00 61.63
April 2578.95 11-APR-15:02 583.20 179.54 410.90 0.00 0.00 0.00 0.00 0.00 0.68
May 2689.80 06-MAY-15:01 378.00 246.87 534.70 0.00 0.00 0.00 0.00 0.00 19.04
June 2689.83 13-JUN-15:02 583.20 179.54 410.90 0.00 0.00 0.00 0.00 0.00 6.44
July 2765.89 22-JUL-15:02 324.00 211.60 458.31 0.00 0.00 0.00 0.00 18.86 0.00
August 2713.70 06-AUG-15:02 324.00 211.60 458.31 0.00 0.00 0.00 0.00 13.09 0.00
September 2740.96 21-SEP-15:02 583.20 179.54 410.90 0.00 0.00 0.00 0.00 32.83 0.00
October 3002.77 13-OCT-15:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 31.41 0.00
November 2744.41 27-NOV-16:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 0.00 20.90
December 2872.54 05-DEC-16:01 680.40 209.46 479.39 0.00 0.00 0.00 0.00 0.00 1.05
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2578.95   324.00 179.54 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3002.77   680.40 246.87 534.70 0.00 0.00 0.00 0.00 32.83 61.63



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2711.76 14-JAN-16:01 378.00 246.84 534.64 0.00 0.00 0.00 0.00 2.21 0.00
February 2664.01 03-FEB-16:01 680.40 209.43 479.33 0.00 0.00 0.00 0.00 0.00 15.10
March 2627.72 23-MAR-15:02 583.20 179.51 410.85 0.00 0.00 0.00 0.00 0.00 6.53
April 2739.41 23-APR-18:11 1170.00 1068.54 1290.50 0.00 0.00 0.00 0.00 0.00 69.05
May 2615.33 24-MAY-19:11 1247.40 961.68 1564.40 0.00 0.00 0.00 0.00 0.00 67.08
June 2616.97 04-JUN-19:31 936.00 854.83 1390.58 0.00 0.00 0.00 0.00 0.00 60.83
July 2665.97 18-JUL-18:02 831.60 570.60 774.30 0.00 0.00 0.00 0.00 3.18 0.00
August 2617.61 06-AUG-15:02 324.00 211.57 458.26 0.00 0.00 0.00 0.00 12.89 0.00
September 2634.48 30-SEP-08:61 486.00 538.54 1469.59 0.00 0.00 0.00 0.00 9.98 0.00
October 2866.61 14-OCT-08:61 540.00 598.38 1632.88 0.00 0.00 0.00 0.00 31.44 0.00
November 2603.72 27-NOV-16:01 680.40 209.43 479.33 0.00 0.00 0.00 0.00 0.00 20.26
December 2725.09 05-DEC-16:01 680.40 209.43 479.33 0.00 0.00 0.00 0.00 0.00 0.38
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2603.72   324.00 179.51 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2866.61   1247.40 1068.54 1632.88 0.00 0.00 0.00 0.00 31.44 69.05



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1552.94 14-JAN-16:01 378.00 155.19 523.86 0.00 0.00 0.00 0.00 0.04 0.00
February 1515.19 03-FEB-16:01 680.40 131.67 469.67 0.00 0.00 0.00 0.00 0.00 8.58
March 1353.64 18-MAR-15:01 378.00 155.19 523.86 0.00 0.00 0.00 0.00 0.00 20.82
April 1456.03 30-APR-15:02 324.00 133.02 449.03 0.00 0.00 0.00 0.00 0.16 0.00
May 1444.98 02-MAY-15:02 583.20 112.86 402.58 0.00 0.00 0.00 0.00 0.00 4.38
June 1401.64 30-JUN-15:02 583.20 112.86 402.58 0.00 0.00 0.00 0.00 0.56 0.00
July 1491.92 31-JUL-15:02 583.20 112.86 402.58 0.00 0.00 0.00 0.00 9.70 0.00
August 1495.79 13-AUG-15:02 324.00 133.02 449.03 0.00 0.00 0.00 0.00 6.90 0.00
September 1495.13 30-SEP-15:02 270.00 110.85 374.19 0.00 0.00 0.00 0.00 28.03 0.00
October 1600.39 14-OCT-08:61 540.00 376.21 1599.98 0.00 0.00 0.00 0.00 15.89 0.00
November 1554.04 19-NOV-09:02 324.00 225.72 959.99 0.00 0.00 0.00 0.00 4.94 0.00
December 1542.08 05-DEC-09:02 216.00 177.35 665.80 0.00 0.00 0.00 0.00 5.16 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1353.64   216.00 110.85 374.19 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1600.39   680.40 376.21 1599.98 0.00 0.00 0.00 0.00 28.03 20.82



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 18977.69 18-JAN-22:54 134943.84 8289.37 33739.51 0.00 0.00 0.00 0.00 0.00 136.88
February 18398.79 01-FEB-23:00 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 187.92
March 18773.49 24-MAR-22:00 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 187.73
April 19779.09 26-APR-21:52 215910.14 13262.99 53983.22 0.00 0.00 0.00 0.00 0.00 136.16
May 20215.54 04-MAY-21:53 188921.38 11605.12 47235.32 0.00 0.00 0.00 0.00 0.00 118.92
June 20468.06 27-JUN-21:52 215910.14 13262.99 53983.22 0.00 0.00 0.00 0.00 0.00 118.73
July 20712.58 19-JUL-21:52 215910.14 13262.99 53983.22 0.00 0.00 0.00 0.00 0.00 101.68
August 20551.07 17-AUG-21:52 215910.14 13262.99 53983.22 0.00 0.00 0.00 0.00 0.00 84.90
September 21011.37 29-SEP-22:00 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 6.51 0.00
October 20724.42 16-OCT-21:53 188921.38 11605.12 47235.32 0.00 0.00 0.00 0.00 0.00 67.84
November 18639.95 10-NOV-23:00 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 153.67
December 19122.75 05-DEC-22:54 134943.84 8289.37 33739.51 0.00 0.00 0.00 0.00 0.00 102.18
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 18398.79   26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21011.37   215910.14 13262.99 53983.22 0.00 0.00 0.00 0.00 6.51 187.92



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 20724.66 18-JAN-22:10 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 122.39
February 20138.11 01-FEB-23:00 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 187.92
March 20442.85 24-MAR-22:00 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 187.73
April 21401.12 26-APR-21:52 215910.14 13262.99 53983.22 0.00 0.00 0.00 0.00 0.00 136.16
May 21731.08 04-MAY-21:53 188921.38 11605.12 47235.32 0.00 0.00 0.00 0.00 0.00 118.92
June 21941.07 27-JUN-21:52 215910.14 13262.99 53983.22 0.00 0.00 0.00 0.00 0.00 118.73
July 22143.09 19-JUL-21:52 215910.14 13262.99 53983.22 0.00 0.00 0.00 0.00 0.00 101.68
August 21933.42 17-AUG-21:52 215910.14 13262.99 53983.22 0.00 0.00 0.00 0.00 0.00 84.90
September 22414.40 29-SEP-21:10 26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 7.86 0.00
October 22137.05 04-OCT-21:53 161932.61 9947.24 40487.42 0.00 0.00 0.00 0.00 0.00 51.18
November 20376.00 10-NOV-22:14 134943.84 8289.37 33739.51 0.00 0.00 0.00 0.00 0.00 153.74
December 20776.75 05-DEC-22:54 134943.84 8289.37 33739.51 0.00 0.00 0.00 0.00 0.00 102.18
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 20138.11   26988.77 1657.87 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22414.40   215910.14 13262.99 53983.22 0.00 0.00 0.00 0.00 7.86 187.92



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 26908.00 14-JAN-11:50 800.57 272.71 14604.56 18744.03 0.00 0.00 0.00 27.82 0.00
February 26760.36 01-FEB-11:50 533.71 272.71 14604.56 18744.03 0.00 0.00 0.00 20.50 0.00
March 27567.08 12-MAR-10:40 2401.70 981.75 43813.67 56232.08 0.00 0.00 0.00 0.00 40.82
April 28037.77 30-APR-10:33 2401.70 981.75 43813.67 56232.08 0.00 0.00 0.00 22.90 0.00
May 27745.47 04-MAY-10:50 533.71 272.71 14604.56 18744.03 0.00 0.00 0.00 0.00 30.83
June 28117.27 25-JUN-10:33 2401.70 981.75 43813.67 56232.08 0.00 0.00 0.00 0.00 16.03
July 28602.39 23-JUL-10:33 2401.70 981.75 43813.67 56232.08 0.00 0.00 0.00 22.97 0.00
August 28462.65 19-AUG-10:40 1601.14 545.42 29209.11 37488.05 0.00 0.00 0.00 8.38 0.00
September 29031.83 30-SEP-10:50 800.57 272.71 14604.56 18744.03 0.00 0.00 0.00 94.66 0.00
October 28877.81 15-OCT-10:37 2401.70 981.75 43813.67 56232.08 0.00 0.00 0.00 107.98 0.00
November 27545.46 19-NOV-11:45 1601.14 654.50 29209.11 37488.05 0.00 0.00 0.00 27.70 0.00
December 26847.71 05-DEC-11:50 533.71 272.71 14604.56 18744.03 0.00 0.00 0.00 0.00 13.61
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 26760.36   533.71 272.71 14604.56 18744.03 0.00 0.00 0.00 0.00 0.00
Maximum of Months 29031.83   2401.70 981.75 43813.67 56232.08 0.00 0.00 0.00 107.98 40.82



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3932.96 20-JAN-11:35 1064.64 613.84 0.00 0.00 0.00 0.00 0.00 0.00 15.03
February 3731.19 02-FEB-11:33 1596.96 920.76 0.00 0.00 0.00 0.00 0.00 0.00 44.39
March 3924.35 11-MAR-11:35 1596.96 613.84 0.00 0.00 0.00 0.00 0.00 21.33 0.00
April 4057.80 30-APR-10:33 2395.44 1104.91 0.00 0.00 0.00 0.00 0.00 44.68 0.00
May 4131.69 04-MAY-10:35 1064.64 613.84 0.00 0.00 0.00 0.00 0.00 0.00 11.76
June 4208.99 30-JUN-10:35 1064.64 613.84 0.00 0.00 0.00 0.00 0.00 5.71 0.00
July 4436.77 30-JUL-10:33 2395.44 1104.91 0.00 0.00 0.00 0.00 0.00 20.42 0.00
August 4428.78 19-AUG-10:35 1596.96 613.84 0.00 0.00 0.00 0.00 0.00 21.01 0.00
September 4881.41 30-SEP-13:50 798.48 306.92 0.00 0.00 0.00 0.00 0.00 109.47 0.00
October 4745.49 16-OCT-12:20 532.32 306.92 0.00 0.00 0.00 0.00 0.00 156.21 0.00
November 4136.44 19-NOV-11:33 2395.44 1104.91 0.00 0.00 0.00 0.00 0.00 43.57 0.00
December 3986.35 19-DEC-11:35 1064.64 613.84 0.00 0.00 0.00 0.00 0.00 30.84 0.00
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 3731.19   532.32 306.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4881.41   2395.44 1104.91 0.00 0.00 0.00 0.00 0.00 156.21 44.39



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.402451E+12 286927.05 17-JAN-20:19 0.402886E+12 340621.35 02-JAN-20:49
February 0.353024E+12 262605.36 01-FEB-20:10 0.341379E+12 315444.51 26-FEB-20:00
March 0.386350E+12 272758.76 23-MAR-19:30 0.413230E+12 341650.43 29-MAR-19:49
April 0.396672E+12 286687.69 26-APR-19:19 0.304676E+12 253729.54 15-APR-21:00
May 0.408567E+12 286425.63 04-MAY-19:19 0.300162E+12 241644.58 13-MAY-19:00
June 0.424621E+12 295631.17 27-JUN-19:10 0.234123E+12 197192.82 12-JUN-20:00
July 0.490196E+12 321643.10 19-JUL-19:10 0.225287E+12 159908.04 01-JUL-17:00
August 0.503602E+12 316747.33 14-AUG-19:19 0.224065E+12 157818.80 31-AUG-17:40
September 0.450185E+12 357486.34 29-SEP-19:10 0.225849E+12 163377.52 30-SEP-17:30
October 0.473196E+12 327749.42 04-OCT-19:10 0.257406E+12 202221.74 12-OCT-05:00
November 0.393892E+12 273022.80 27-NOV-20:19 0.332893E+12 307440.37 23-NOV-21:00
December 0.407660E+12 286891.59 05-DEC-20:10 0.396257E+12 327278.71 12-DEC-21:00
             
Annual Sum or Average 0.509042E+13     0.365821E+13    
Minimum of Months 0.353024E+12 262605.36   0.224065E+12 157818.80  
Maximum of Months 0.503602E+12 357486.34   0.413230E+12 341650.43  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.465878E+11 0.171906E+11 0.146779E+12 0.544792E+11 0.459526E+11 0.861418E+10 0.00 0.378489E+11 0.00 0.00 0.00 0.412840E+11 0.00
February 0.419239E+11 0.146939E+11 0.132565E+12 0.492070E+11 0.411276E+11 0.779400E+10 0.00 0.251833E+11 0.00 0.00 0.00 0.371662E+11 0.00
March 0.463059E+11 0.150601E+11 0.146789E+12 0.544810E+11 0.451634E+11 0.824706E+10 0.00 0.253839E+11 0.00 0.00 0.00 0.411889E+11 0.00
April 0.445334E+11 0.133890E+11 0.142011E+12 0.527214E+11 0.448915E+11 0.895549E+10 0.00 0.474003E+11 0.00 0.00 0.00 0.391518E+11 0.00
May 0.458107E+11 0.127831E+11 0.146789E+12 0.544798E+11 0.463940E+11 0.926449E+10 0.00 0.488337E+11 0.00 0.00 0.00 0.404673E+11 0.00
June 0.442654E+11 0.118510E+11 0.142058E+12 0.527230E+11 0.460976E+11 0.904072E+10 0.00 0.764370E+11 0.00 0.00 0.00 0.385043E+11 0.00
July 0.457536E+11 0.124768E+11 0.146742E+12 0.544779E+11 0.489688E+11 0.979173E+10 0.00 0.129012E+12 0.00 0.00 0.00 0.392188E+11 0.00
August 0.459349E+11 0.133623E+11 0.146800E+12 0.544809E+11 0.493185E+11 0.992928E+10 0.00 0.140947E+12 0.00 0.00 0.00 0.390554E+11 0.00
September 0.447703E+11 0.140681E+11 0.142022E+12 0.527216E+11 0.468508E+11 0.926292E+10 0.00 0.985347E+11 0.00 0.00 0.00 0.383095E+11 0.00
October 0.464700E+11 0.157658E+11 0.146768E+12 0.544791E+11 0.492134E+11 0.967648E+10 0.00 0.107221E+12 0.00 0.00 0.00 0.398604E+11 0.00
November 0.450472E+11 0.163318E+11 0.142074E+12 0.527223E+11 0.450908E+11 0.884067E+10 0.00 0.404623E+11 0.00 0.00 0.00 0.397251E+11 0.00
December 0.465590E+11 0.174836E+11 0.146742E+12 0.544784E+11 0.464771E+11 0.890345E+10 0.00 0.418181E+11 0.00 0.00 0.00 0.414906E+11 0.00
                           
Annual Sum or Average 0.543962E+12 0.174456E+12 0.172814E+13 0.641452E+12 0.555546E+12 0.108320E+12 0.00 0.819082E+12 0.00 0.00 0.00 0.475422E+12 0.00
Minimum of Months 0.419239E+11 0.118510E+11 0.132565E+12 0.492070E+11 0.411276E+11 0.779400E+10 0.00 0.251833E+11 0.00 0.00 0.00 0.371662E+11 0.00
Maximum of Months 0.465878E+11 0.174836E+11 0.146800E+12 0.544810E+11 0.493185E+11 0.992928E+10 0.00 0.140947E+12 0.00 0.00 0.00 0.414906E+11 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.159431E+12 0.00 0.915367E+11 0.00 0.00
February 0.137204E+12 0.00 0.122128E+12 0.00 0.820472E+11 0.00 0.00
March 0.152024E+12 0.00 0.171268E+12 0.00 0.899385E+11 0.00 0.00
April 0.146956E+12 0.00 0.760773E+11 0.00 0.816429E+11 0.00 0.00
May 0.151978E+12 0.00 0.660904E+11 0.00 0.820930E+11 0.00 0.00
June 0.147114E+12 0.00 0.129286E+11 0.00 0.740808E+11 0.00 0.00
July 0.151820E+12 0.00 0.115718E+10 0.00 0.723098E+11 0.00 0.00
August 0.152039E+12 0.00 0.777538E+09 0.00 0.712487E+11 0.00 0.00
September 0.146971E+12 0.00 0.627467E+10 0.00 0.726034E+11 0.00 0.00
October 0.151903E+12 0.00 0.270906E+11 0.00 0.784123E+11 0.00 0.00
November 0.147091E+12 0.00 0.101576E+12 0.00 0.842257E+11 0.00 0.00
December 0.151820E+12 0.00 0.153222E+12 0.00 0.912148E+11 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.898021E+12 0.00 0.971354E+12 0.00 0.00
Minimum of Months 0.137204E+12 0.00 0.777538E+09 0.00 0.712487E+11 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.171268E+12 0.00 0.915367E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 45424.10 02-JAN-20:10 11096.45 01-JAN-00:10 88863.15 02-JAN-07:10 39153.41 18-JAN-07:19 28744.49 18-JAN-22:00 4106.14 18-JAN-10:00 0.00 01-JAN-00:10
February 45424.10 01-FEB-20:10 11096.45 01-FEB-00:10 88863.15 01-FEB-07:10 39153.05 10-FEB-07:19 27285.41 01-FEB-22:10 3865.77 09-FEB-06:19 0.00 01-FEB-00:10
March 45424.10 01-MAR-20:10 11096.45 01-MAR-00:10 88863.15 01-MAR-07:10 39153.54 16-MAR-06:19 27414.30 23-MAR-21:10 4051.86 12-MAR-09:50 0.00 01-MAR-00:10
April 45424.10 03-APR-19:10 11096.45 01-APR-00:10 88863.15 03-APR-06:10 39152.98 05-APR-06:19 29665.26 26-APR-21:00 3985.20 13-APR-09:09 0.00 01-APR-00:10
May 45424.10 01-MAY-19:10 11096.45 01-MAY-00:10 88863.15 01-MAY-06:10 39152.58 09-MAY-06:19 30166.21 04-MAY-21:00 4067.47 18-MAY-15:09 0.00 01-MAY-00:10
June 45424.10 01-JUN-19:10 11096.45 01-JUN-00:10 88863.15 01-JUN-06:10 39152.58 16-JUN-06:19 30353.38 30-JUN-21:00 4411.00 29-JUN-18:10 0.00 01-JUN-00:10
July 45424.10 03-JUL-19:10 11096.45 01-JUL-00:10 88863.15 03-JUL-06:10 39152.57 12-JUL-06:19 31884.91 19-JUL-21:00 5297.20 18-JUL-18:10 0.00 01-JUL-00:10
August 45424.10 01-AUG-19:10 11096.45 01-AUG-00:10 88863.15 01-AUG-06:10 39152.91 29-AUG-06:19 32428.11 18-AUG-21:00 5332.53 14-AUG-10:50 0.00 01-AUG-00:10
September 45424.10 01-SEP-19:10 11096.45 01-SEP-00:10 88863.15 01-SEP-06:10 39153.23 18-SEP-06:19 34352.87 29-SEP-21:10 6784.48 29-SEP-15:20 0.00 01-SEP-00:10
October 45424.10 02-OCT-19:10 11096.45 01-OCT-00:10 88863.15 02-OCT-06:10 39153.53 23-OCT-06:19 36650.23 16-OCT-21:00 5872.19 17-OCT-10:50 0.00 01-OCT-00:10
November 45424.10 01-NOV-19:10 11096.45 01-NOV-00:10 88863.15 01-NOV-06:10 39153.57 03-NOV-06:19 27941.31 10-NOV-22:19 4820.84 19-NOV-10:00 0.00 01-NOV-00:10
December 45424.10 01-DEC-20:10 11096.45 01-DEC-00:10 88863.15 01-DEC-07:10 39153.32 08-DEC-07:19 29881.53 05-DEC-22:00 4049.77 16-DEC-16:10 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 45424.10   11096.45   88863.15   39152.57   27285.41   3865.77   0.00  
Maximum of Months 45424.10   11096.45   88863.15   39153.57   36650.23   6784.48   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 75883.73 14-JAN-10:00 0.00 0.00 0.00 42124.17 03-JAN-19:49 0.00
February 68341.38 01-FEB-11:50 0.00 0.00 0.00 42021.64 23-FEB-19:40 0.00
March 71751.22 23-MAR-15:09 0.00 0.00 0.00 42220.32 28-MAR-18:19 0.00
April 75834.71 26-APR-10:50 0.00 0.00 0.00 42408.07 28-APR-17:49 0.00
May 63777.74 04-MAY-15:09 0.00 0.00 0.00 42899.65 31-MAY-20:49 0.00
June 84001.63 29-JUN-10:50 0.00 0.00 0.00 43106.26 29-JUN-20:49 0.00
July 121576.32 19-JUL-15:20 0.00 0.00 0.00 43014.31 27-JUL-20:49 0.00
August 128265.19 18-AUG-15:09 0.00 0.00 0.00 42841.76 03-AUG-20:49 0.00
September 147928.32 29-SEP-12:00 0.00 0.00 0.00 43050.65 06-SEP-20:49 0.00
October 157368.80 16-OCT-10:50 0.00 0.00 0.00 42816.63 05-OCT-20:49 0.00
November 84105.27 19-NOV-10:00 0.00 0.00 0.00 42610.19 02-NOV-17:00 0.00
December 77120.49 05-DEC-09:50 0.00 0.00 0.00 42376.29 12-DEC-19:49 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 63777.74   0.00 0.00 0.00 42021.64   0.00
Maximum of Months 157368.80   0.00 0.00 0.00 43106.26   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 286927.05 17-JAN-20:19 45424.10 87982.85 11096.45 31573.56 23101.65 3522.10 0.00 42552.04 0.00
February 262605.36 01-FEB-20:10 45424.10 87982.85 11096.45 31569.36 23789.18 3487.59 0.00 16882.34 0.00
March 272758.76 23-MAR-19:30 45424.10 87982.85 11096.45 31573.56 25727.06 3477.32 0.00 25934.65 0.00
April 286687.69 26-APR-19:19 45424.10 87982.85 11096.45 31573.56 23313.15 3570.80 0.00 42494.67 0.00
May 286425.63 04-MAY-19:19 45424.10 87982.85 11096.45 31573.56 23414.84 3545.78 0.00 41745.31 0.00
June 295631.17 27-JUN-19:10 45424.10 87982.85 11096.45 31569.36 23993.72 3694.11 0.00 51162.20 0.00
July 321643.10 19-JUL-19:10 45424.10 87982.85 11096.45 31569.36 23353.27 4341.71 0.00 76676.83 0.00
August 316747.33 14-AUG-19:19 45424.10 87982.85 11096.45 31573.56 23615.15 4203.29 0.00 72439.24 0.00
September 357486.34 29-SEP-19:10 45424.10 87982.85 11096.45 31569.36 29112.15 4233.61 0.00 107030.07 0.00
October 327749.42 04-OCT-19:10 45424.10 87982.85 11096.45 31569.36 23159.70 4473.37 0.00 82390.48 0.00
November 273022.80 27-NOV-20:19 45424.10 87982.85 11096.45 31573.56 23148.75 3438.96 0.00 28416.39 0.00
December 286891.59 05-DEC-20:10 45424.10 87982.85 11096.45 31569.36 24121.77 3498.95 0.00 41037.61 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 262605.36   45424.10 87982.85 11096.45 31569.36 23101.65 3438.96 0.00 16882.34 0.00
Maximum of Months 357486.34   45424.10 87982.85 11096.45 31573.56 29112.15 4473.37 0.00 107030.07 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 221129.21 08-JAN-06:00 0.00 79826.46 31-JAN-18:10 0.00
February 104248.32 01-FEB-18:10 0.00 180858.95 04-FEB-05:00 0.00 78894.52 02-FEB-19:10 0.00
March 104248.32 01-MAR-18:10 0.00 214853.31 30-MAR-02:00 0.00 78394.58 01-MAR-19:10 0.00
April 104248.32 01-APR-17:10 0.00 171761.70 01-APR-05:00 0.00 71160.41 01-APR-21:40 0.00
May 104248.32 01-MAY-17:10 0.00 150806.37 14-MAY-04:49 0.00 68435.22 01-MAY-22:40 0.00
June 104248.32 01-JUN-17:10 0.00 105349.96 13-JUN-03:00 0.00 61426.63 01-JUN-19:30 0.00
July 104248.32 01-JUL-17:10 0.00 47706.15 06-JUL-02:00 0.00 55675.48 01-JUL-16:40 0.00
August 104248.32 01-AUG-17:10 0.00 21115.47 28-AUG-03:00 0.00 53571.27 31-AUG-22:40 0.00
September 104248.32 01-SEP-17:10 0.00 102342.29 20-SEP-02:00 0.00 59129.72 30-SEP-16:19 0.00
October 104248.32 02-OCT-17:10 0.00 140412.08 12-OCT-05:00 0.00 63465.10 31-OCT-22:00 0.00
November 104248.32 01-NOV-17:10 0.00 169786.33 05-NOV-05:00 0.00 75084.17 30-NOV-19:19 0.00
December 104248.32 01-DEC-18:10 0.00 186243.17 13-DEC-05:00 0.00 80009.60 31-DEC-23:30 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 21115.47   0.00 53571.27   0.00
Maximum of Months 104248.32   0.00 221129.21   0.00 80009.60   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.17 21.74 0.17 21.74
March 0.00 0.00 0.00 0.00 0.33 21.85 0.33 21.85
April 0.00 0.00 0.00 0.00 0.33 21.70 0.33 21.70
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.50 21.67 0.50 21.67
September 0.00 0.00 0.00 0.00 1.67 21.85 1.67 21.85
October 0.00 0.00 0.00 0.00 4.67 22.01 4.67 22.01
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   7.67 21.92 7.67 21.92
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 4.67 22.01 4.67 22.01



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.83 21.81 0.83 21.81
May 0.00 0.00 0.00 0.00 0.67 22.01 0.67 22.01
June 0.00 0.00 0.00 0.00 2.17 21.75 2.17 21.75
July 0.00 0.00 0.00 0.00 4.67 21.74 4.67 21.74
August 0.00 0.00 0.00 0.00 3.67 21.73 3.67 21.73
September 0.00 0.00 0.00 0.00 0.83 21.86 0.83 21.86
October 0.00 0.00 0.00 0.00 2.00 21.89 2.00 21.89
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   14.83 21.78 14.83 21.78
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 4.67 22.01 4.67 22.01



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.17 21.71 1.17 21.71
May 0.00 0.00 0.00 0.00 2.83 21.74 2.83 21.74
June 0.00 0.00 0.00 0.00 7.83 21.81 7.83 21.81
July 0.00 0.00 0.00 0.00 12.83 21.83 12.83 21.83
August 0.00 0.00 0.00 0.00 10.50 21.79 10.50 21.79
September 0.00 0.00 0.00 0.00 5.00 21.74 5.00 21.74
October 0.00 0.00 0.00 0.00 4.33 21.81 4.33 21.81
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   44.50 21.79 44.50 21.79
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 12.83 21.83 12.83 21.83



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 21.67 0.17 21.67
February 0.00 0.00 0.00 0.00 0.67 21.71 0.67 21.71
March 0.00 0.00 0.00 0.00 0.50 21.78 0.50 21.78
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
August 0.00 0.00 0.00 0.00 0.33 21.70 0.33 21.70
September 0.00 0.00 0.00 0.00 0.83 21.84 0.83 21.84
October 0.00 0.00 0.00 0.00 2.00 21.82 2.00 21.82
November 0.00 0.00 0.00 0.00 0.33 21.87 0.33 21.87
December 0.00 0.00 0.00 0.00 0.33 21.69 0.33 21.69
                 
Annual Sum or Average 0.00   0.00   5.33 21.79 5.33 21.79
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.00 21.87 2.00 21.87



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.50 21.91 0.50 21.91
April 0.00 0.00 0.00 0.00 1.50 22.13 1.50 22.13
May 0.00 0.00 0.00 0.00 2.50 22.02 2.50 22.02
June 0.00 0.00 0.00 0.00 4.67 22.16 4.67 22.16
July 0.00 0.00 0.00 0.00 9.83 22.26 9.83 22.26
August 0.00 0.00 0.00 0.00 10.33 22.26 10.33 22.26
September 0.00 0.00 0.00 0.00 3.83 22.06 3.83 22.06
October 0.00 0.00 0.00 0.00 3.17 21.88 3.17 21.88
November 0.00 0.00 0.00 0.00 0.17 22.13 0.17 22.13
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   36.50 22.17 36.50 22.17
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 10.33 22.26 10.33 22.26



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.17 21.73 0.17 21.73
March 0.00 0.00 0.00 0.00 0.50 21.87 0.50 21.87
April 0.00 0.00 0.00 0.00 1.00 21.75 1.00 21.75
May 0.00 0.00 0.00 0.00 0.17 21.73 0.17 21.73
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.50 21.69 0.50 21.69
August 0.00 0.00 0.00 0.00 2.50 21.72 2.50 21.72
September 0.00 0.00 0.00 0.00 3.17 21.86 3.17 21.86
October 0.00 0.00 0.00 0.00 6.00 22.07 6.00 22.07
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   14.00 21.91 14.00 21.91
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 6.00 22.07 6.00 22.07



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
April 0.00 0.00 0.00 0.00 1.50 21.86 1.50 21.86
May 0.00 0.00 0.00 0.00 2.33 21.88 2.33 21.88
June 0.00 0.00 0.00 0.00 5.33 21.79 5.33 21.79
July 0.00 0.00 0.00 0.00 9.00 21.79 9.00 21.79
August 0.00 0.00 0.00 0.00 7.83 21.76 7.83 21.76
September 0.00 0.00 0.00 0.00 1.00 21.92 1.00 21.92
October 0.00 0.00 0.00 0.00 2.17 21.98 2.17 21.98
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   29.33 21.81 29.33 21.81
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 9.00 21.98 9.00 21.98



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 3.00 21.93 3.00 21.93
February 0.00 0.00 0.00 0.00 1.33 21.80 1.33 21.80
March 0.00 0.00 0.00 0.00 1.17 21.81 1.17 21.81
April 0.00 0.00 0.00 0.00 0.33 21.69 0.33 21.69
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 2.17 21.85 2.17 21.85
October 0.00 0.00 0.00 0.00 9.00 22.06 9.00 22.06
November 0.00 0.00 0.00 0.00 2.00 21.77 2.00 21.77
December 0.00 0.00 0.00 0.00 3.50 21.84 3.50 21.84
                 
Annual Sum or Average 0.00   0.00   22.50 21.93 22.50 21.93
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 9.00 22.06 9.00 22.06



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 742.33 22.92 0.00 22.92 0.00 22.92
February 672.00 22.29 0.00 22.29 0.00 22.29
March 744.00 22.03 0.00 22.03 0.00 22.03
April 720.00 21.93 0.00 21.93 0.00 21.93
May 744.00 21.93 0.00 21.93 0.00 21.93
June 720.00 21.81 0.00 21.81 0.00 21.81
July 744.00 22.20 0.00 22.20 0.00 22.20
August 744.00 22.32 0.00 22.32 0.00 22.32
September 720.00 22.70 0.00 22.70 0.00 22.70
October 733.50 23.03 0.00 23.03 0.00 23.03
November 704.00 23.16 0.00 23.16 0.00 23.16
December 744.00 23.00 0.00 23.00 0.00 23.00
             
Annual Sum or Average 8731.83 22.44 0.00 22.44 0.00 22.44
Minimum of Months 672.00 21.81 0.00 21.81 0.00 21.81
Maximum of Months 744.00 23.16 0.00 23.16 0.00 23.16



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 605.50 21.55 83.33 21.81 7.50 21.80
February 581.00 21.43 47.00 21.60 3.17 21.60
March 681.00 21.31 43.33 21.43 7.33 21.42
April 673.67 21.54 9.17 21.56 1.17 21.56
May 741.83 21.32 0.00 21.32 0.00 21.32
June 720.00 21.51 0.00 21.51 0.00 21.51
July 720.50 21.91 1.50 21.91 0.00 21.91
August 607.67 22.12 68.00 22.25 0.00 22.25
September 542.83 21.96 124.17 22.28 0.00 22.28
October 536.33 22.02 136.33 22.40 0.00 22.40
November 576.17 21.67 80.00 21.94 2.50 21.93
December 586.67 21.63 75.33 21.89 1.50 21.88
             
Annual Sum or Average 7573.17 21.65 668.17 21.82 23.17 21.81
Minimum of Months 536.33 21.31 0.00 21.32 0.00 21.32
Maximum of Months 741.83 22.12 136.33 22.40 7.50 22.40



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 732.83 22.47 1.00 22.47 0.00 22.47
February 662.33 22.44 0.00 22.44 0.00 22.44
March 733.00 22.27 1.50 22.27 0.00 22.27
April 654.00 22.52 12.33 22.54 0.50 22.55
May 703.33 22.50 9.67 22.52 0.00 22.52
June 598.33 22.62 49.83 22.71 11.83 22.72
July 503.83 22.81 178.17 23.03 70.33 23.07
August 457.17 22.90 252.67 23.18 96.50 23.21
September 480.50 22.83 113.50 23.00 23.00 23.01
October 556.83 22.94 96.00 23.05 26.83 23.07
November 685.17 22.72 3.33 22.72 0.00 22.72
December 735.00 22.66 0.00 22.66 0.00 22.66
             
Annual Sum or Average 7502.33 22.61 718.00 22.71 229.00 22.73
Minimum of Months 457.17 22.27 0.00 22.27 0.00 22.27
Maximum of Months 735.00 22.94 252.67 23.18 96.50 23.21



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.58 0.00 21.58 0.00 21.58
February 672.00 21.58 0.00 21.58 0.00 21.58
March 744.00 21.46 0.00 21.46 0.00 21.46
April 720.00 21.85 0.00 21.85 0.00 21.85
May 744.00 22.04 0.00 22.04 0.00 22.04
June 720.00 22.45 0.00 22.45 0.00 22.45
July 743.17 22.78 0.00 22.78 0.00 22.78
August 742.67 22.77 0.00 22.77 0.00 22.77
September 715.83 22.52 0.00 22.52 0.00 22.52
October 733.17 22.63 0.00 22.63 0.00 22.63
November 720.00 21.90 0.00 21.90 0.00 21.90
December 744.00 21.71 0.00 21.71 0.00 21.71
             
Annual Sum or Average 8742.83 22.11 0.00 22.11 0.00 22.11
Minimum of Months 672.00 21.46 0.00 21.46 0.00 21.46
Maximum of Months 744.00 22.78 0.00 22.78 0.00 22.78



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.47 3.00 21.47 3.00 21.47
February 672.00 21.46 0.00 21.46 0.00 21.46
March 744.00 21.34 0.00 21.34 0.00 21.34
April 720.00 21.73 0.00 21.73 0.00 21.73
May 744.00 21.90 0.00 21.90 0.00 21.90
June 720.00 22.31 0.00 22.31 0.00 22.31
July 744.00 22.65 0.00 22.65 0.00 22.65
August 744.00 22.64 0.00 22.64 0.00 22.64
September 720.00 22.40 0.00 22.40 0.00 22.40
October 744.00 22.52 0.00 22.52 0.00 22.52
November 720.00 21.78 0.00 21.78 0.00 21.78
December 744.00 21.59 0.00 21.59 0.00 21.59
             
Annual Sum or Average 8760.00 21.99 3.00 21.99 3.00 21.99
Minimum of Months 672.00 21.34 0.00 21.34 0.00 21.34
Maximum of Months 744.00 22.65 3.00 22.65 3.00 22.65



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 287.00 22.94 521.33 23.05 185.33 23.22
February 256.33 23.01 492.83 23.04 171.50 23.22
March 293.50 23.05 561.50 23.02 201.67 23.20
April 280.67 23.38 593.33 23.05 225.33 23.24
May 296.83 23.39 617.33 23.07 239.00 23.25
June 280.83 23.68 634.67 23.09 255.33 23.27
July 277.17 23.90 682.50 23.09 274.67 23.28
August 281.17 23.92 685.83 23.09 280.17 23.28
September 271.33 23.74 641.33 23.09 253.17 23.28
October 273.33 23.42 606.00 23.10 222.00 23.27
November 276.17 23.10 535.67 23.08 192.67 23.25
December 271.00 22.86 503.83 23.06 164.83 23.22
             
Annual Sum or Average 3345.33 23.37 7076.17 23.07 2665.67 23.25
Minimum of Months 256.33 22.86 492.83 23.02 164.83 23.20
Maximum of Months 296.83 23.92 685.83 23.10 280.17 23.28



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 458.00 22.63 177.17 22.96 14.50 22.97
February 458.00 22.42 116.00 22.69 5.33 22.69
March 579.00 22.23 93.67 22.41 1.00 22.42
April 495.50 22.43 95.00 22.59 22.50 22.63
May 681.83 22.28 36.83 22.35 26.50 22.39
June 639.17 22.41 124.00 22.59 103.50 22.69
July 589.17 22.72 281.33 22.96 233.33 23.08
August 466.67 23.15 457.17 23.29 300.17 23.38
September 358.67 23.05 439.83 23.32 187.67 23.38
October 304.50 22.91 371.83 23.38 79.50 23.43
November 387.33 22.79 215.50 23.13 17.83 23.14
December 445.00 22.79 175.33 23.10 0.00 23.10
             
Annual Sum or Average 5862.83 22.60 2583.67 22.91 991.83 22.99
Minimum of Months 304.50 22.23 36.83 22.35 0.00 22.39
Maximum of Months 681.83 23.15 457.17 23.38 300.17 23.43



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 581.83 22.85 40.83 22.92 7.33 22.93
February 557.50 22.79 26.67 22.84 4.33 22.84
March 642.83 22.61 27.17 22.66 0.00 22.66
April 508.33 22.66 95.17 22.84 13.17 22.86
May 557.17 22.63 79.50 22.78 16.33 22.80
June 462.83 22.74 218.50 23.08 92.00 23.17
July 518.00 23.07 355.17 23.37 216.17 23.46
August 548.50 23.26 387.83 23.50 277.00 23.58
September 404.50 23.17 306.17 23.45 162.33 23.53
October 352.67 23.18 229.17 23.45 61.83 23.50
November 512.67 23.04 79.83 23.14 16.17 23.15
December 623.67 23.09 25.67 23.12 0.00 23.12
             
Annual Sum or Average 6270.50 22.91 1871.67 23.12 866.67 23.19
Minimum of Months 352.67 22.61 25.67 22.66 0.00 22.66
Maximum of Months 642.83 23.26 387.83 23.50 277.00 23.58



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 728.50 21.55 18.67 21.53 18.67 21.52
February 655.83 21.47 8.83 21.46 8.83 21.46
March 725.33 21.44 12.83 21.42 12.83 21.41
April 679.83 21.54 0.00 21.54 0.00 21.54
May 720.33 21.57 0.00 21.57 0.00 21.57
June 668.83 21.54 0.00 21.54 0.00 21.54
July 654.50 21.49 0.00 21.49 0.00 21.49
August 644.50 21.46 0.83 21.46 0.83 21.47
September 646.83 21.51 1.17 21.51 0.17 21.51
October 691.00 21.56 0.33 21.56 0.17 21.56
November 686.83 21.54 8.17 21.54 8.17 21.53
December 735.50 21.59 15.00 21.58 15.00 21.57
             
Annual Sum or Average 8237.83 21.52 65.83 21.52 64.67 21.51
Minimum of Months 644.50 21.44 0.00 21.42 0.00 21.41
Maximum of Months 735.50 21.59 18.67 21.58 18.67 21.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.41 61.50 21.38 61.50 21.35
February 672.00 21.40 20.33 21.39 20.33 21.38
March 731.00 21.41 23.50 21.41 16.67 21.40
April 632.17 21.64 45.50 21.84 1.00 21.84
May 647.83 21.72 51.50 21.94 0.00 21.94
June 548.00 21.92 116.17 22.48 6.50 22.50
July 511.00 22.09 197.83 22.88 52.67 22.98
August 521.33 22.05 191.00 22.75 62.50 22.84
September 589.17 21.93 75.33 22.19 15.00 22.21
October 689.83 22.01 41.17 22.10 30.00 22.14
November 719.00 21.56 26.33 21.54 26.33 21.53
December 744.00 21.45 58.33 21.42 58.33 21.39
             
Annual Sum or Average 7749.33 21.69 908.50 21.92 350.83 21.94
Minimum of Months 511.00 21.40 20.33 21.38 0.00 21.35
Maximum of Months 744.00 22.09 197.83 22.88 62.50 22.98



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.39 13.17 21.39 13.17 21.38
February 672.00 21.38 11.33 21.38 11.33 21.37
March 744.00 21.41 0.00 21.41 0.00 21.41
April 720.00 21.63 0.00 21.63 0.00 21.63
May 744.00 21.74 0.00 21.74 0.00 21.74
June 713.50 22.07 1.33 22.08 0.00 22.08
July 730.17 22.27 22.83 22.31 21.17 22.34
August 736.67 22.22 22.33 22.25 22.17 22.28
September 720.00 21.95 5.50 21.95 5.50 21.96
October 743.50 21.92 17.17 21.95 17.17 21.98
November 720.00 21.43 18.67 21.42 18.67 21.42
December 744.00 21.38 26.83 21.37 26.83 21.36
             
Annual Sum or Average 8731.83 21.73 139.17 21.74 136.00 21.75
Minimum of Months 672.00 21.38 0.00 21.37 0.00 21.36
Maximum of Months 744.00 22.27 26.83 22.31 26.83 22.34



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 743.83 21.63 18.67 21.62 18.67 21.61
February 672.00 21.53 9.33 21.52 9.33 21.52
March 742.00 21.52 12.83 21.51 12.83 21.50
April 718.33 21.68 0.00 21.68 0.00 21.68
May 742.33 21.65 0.00 21.65 0.00 21.65
June 715.50 21.67 0.00 21.67 0.00 21.67
July 683.67 21.59 0.00 21.59 0.00 21.59
August 639.83 21.48 0.00 21.48 0.00 21.48
September 674.50 21.58 0.00 21.58 0.00 21.58
October 709.67 21.62 0.17 21.62 0.17 21.62
November 720.00 21.65 8.67 21.65 8.67 21.64
December 744.00 21.64 17.83 21.63 17.83 21.61
             
Annual Sum or Average 8505.67 21.61 67.50 21.60 67.50 21.60
Minimum of Months 639.83 21.48 0.00 21.48 0.00 21.48
Maximum of Months 744.00 21.68 18.67 21.68 18.67 21.68



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.43 48.00 21.41 48.00 21.39
February 672.00 21.39 18.83 21.38 18.83 21.37
March 742.00 21.46 22.17 21.44 21.67 21.43
April 705.50 21.82 8.67 21.86 0.33 21.86
May 721.33 21.88 9.17 21.92 0.00 21.92
June 632.67 22.05 47.50 22.23 2.50 22.24
July 529.00 22.15 135.17 22.62 52.33 22.75
August 558.33 22.25 127.67 22.64 66.17 22.80
September 686.50 22.05 29.50 22.13 14.67 22.16
October 734.17 22.07 34.00 22.13 30.17 22.17
November 719.00 21.52 30.17 21.50 30.17 21.48
December 743.83 21.46 52.00 21.44 52.00 21.41
             
Annual Sum or Average 8188.33 21.77 562.83 21.87 336.83 21.90
Minimum of Months 529.00 21.39 8.67 21.38 0.00 21.37
Maximum of Months 744.00 22.25 135.17 22.64 66.17 22.80



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.78 0.00 21.78 0.00 21.78
February 672.00 21.76 0.00 21.76 0.00 21.76
March 744.00 21.57 0.00 21.57 0.00 21.57
April 720.00 21.98 2.00 21.98 2.00 21.99
May 744.00 22.06 0.00 22.06 0.00 22.06
June 720.00 22.38 18.00 22.39 18.00 22.40
July 744.00 22.78 105.17 22.79 105.17 22.80
August 744.00 22.89 139.17 22.90 139.17 22.90
September 720.00 22.65 37.50 22.65 37.50 22.65
October 740.67 22.80 40.67 22.82 40.67 22.83
November 720.00 22.14 0.00 22.14 0.00 22.14
December 744.00 22.00 0.00 22.00 0.00 22.00
             
Annual Sum or Average 8756.67 22.23 342.50 22.26 342.50 22.28
Minimum of Months 672.00 21.57 0.00 21.57 0.00 21.57
Maximum of Months 744.00 22.89 139.17 22.90 139.17 22.90



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 721.33 21.49 58.67 21.46 58.67 21.43
February 652.67 21.41 27.67 21.40 27.67 21.38
March 716.83 21.38 35.50 21.34 35.50 21.32
April 666.67 21.50 4.33 21.50 4.33 21.49
May 702.50 21.51 0.67 21.51 0.67 21.51
June 651.33 21.48 0.50 21.49 0.50 21.49
July 634.50 21.43 3.33 21.44 2.33 21.44
August 625.33 21.40 9.50 21.42 8.17 21.43
September 628.67 21.44 9.00 21.46 5.67 21.46
October 678.00 21.51 7.33 21.53 1.83 21.53
November 682.17 21.50 32.00 21.48 32.00 21.46
December 731.17 21.53 61.33 21.50 61.33 21.47
             
Annual Sum or Average 8091.17 21.47 249.83 21.46 238.67 21.45
Minimum of Months 625.33 21.38 0.50 21.34 0.50 21.32
Maximum of Months 731.17 21.53 61.33 21.53 61.33 21.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.33 131.50 21.27 131.50 21.23
February 671.83 21.33 52.17 21.30 52.17 21.27
March 725.67 21.36 58.33 21.36 48.67 21.32
April 608.50 21.58 64.33 21.87 7.83 21.87
May 621.83 21.65 69.17 21.97 0.33 21.97
June 541.67 22.03 134.83 22.72 29.83 22.87
July 516.50 22.31 217.50 23.16 94.33 23.38
August 520.67 22.15 217.83 22.94 101.67 23.10
September 561.17 21.82 105.33 22.17 34.00 22.21
October 682.33 21.92 52.67 22.03 37.67 22.09
November 718.50 21.48 62.83 21.44 62.83 21.41
December 744.00 21.35 147.17 21.28 147.17 21.24
             
Annual Sum or Average 7656.67 21.65 1313.67 21.93 748.00 21.96
Minimum of Months 516.50 21.33 52.17 21.27 0.33 21.23
Maximum of Months 744.00 22.31 217.83 23.16 147.17 23.38



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 657.67 21.48 9.50 21.50 1.83 21.50
February 625.00 21.48 3.33 21.48 2.50 21.48
March 694.17 21.44 12.33 21.43 12.33 21.42
April 682.17 21.56 0.00 21.56 0.00 21.56
May 743.67 21.59 0.00 21.59 0.00 21.59
June 720.00 21.62 0.00 21.62 0.00 21.62
July 726.17 21.64 0.83 21.65 0.83 21.65
August 660.83 21.49 2.33 21.50 2.33 21.50
September 619.17 21.41 3.67 21.42 0.17 21.42
October 647.00 21.47 16.83 21.51 0.67 21.51
November 641.50 21.51 11.17 21.53 2.67 21.53
December 659.33 21.50 7.33 21.51 2.50 21.51
             
Annual Sum or Average 8076.67 21.52 67.33 21.53 25.83 21.53
Minimum of Months 619.17 21.41 0.00 21.42 0.00 21.42
Maximum of Months 743.67 21.64 16.83 21.65 12.33 21.65



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 324.50 23.09 194.50 23.41 14.83 23.43
February 247.50 23.12 232.67 23.52 12.67 23.53
March 196.33 22.92 306.50 23.52 1.50 23.52
April 65.33 23.24 507.17 23.80 14.67 23.81
May 46.83 23.38 555.67 23.85 19.50 23.86
June 99.83 23.96 672.33 23.87 96.67 23.88
July 221.17 24.00 740.83 23.89 221.17 23.91
August 283.00 23.99 738.17 23.88 283.00 23.90
September 181.17 23.98 673.67 23.85 180.00 23.88
October 119.50 23.59 481.00 23.81 64.67 23.82
November 241.17 23.22 265.17 23.59 20.33 23.61
December 355.50 23.20 131.83 23.40 0.00 23.40
             
Annual Sum or Average 2381.83 23.44 5499.50 23.74 929.00 23.77
Minimum of Months 46.83 22.92 131.83 23.40 0.00 23.40
Maximum of Months 355.50 24.00 740.83 23.89 283.00 23.91



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 147.83 23.13 335.00 23.67 6.67 23.67
February 80.33 23.24 373.50 23.78 6.50 23.78
March 54.17 22.98 477.33 23.79 0.00 23.79
April 11.17 24.00 628.17 23.87 11.17 23.88
May 9.83 23.97 689.33 23.89 9.67 23.89
June 75.00 24.00 713.17 23.90 75.00 23.91
July 199.17 24.00 744.00 23.93 199.17 23.94
August 263.83 24.00 744.00 23.92 263.83 23.94
September 155.33 24.00 715.17 23.89 155.33 23.90
October 77.00 23.80 575.83 23.87 58.00 23.88
November 83.00 23.43 393.00 23.81 15.17 23.82
December 155.67 23.21 241.50 23.64 0.00 23.64
             
Annual Sum or Average 1312.33 23.67 6630.00 23.85 800.50 23.87
Minimum of Months 9.83 22.98 241.50 23.64 0.00 23.64
Maximum of Months 263.83 24.00 744.00 23.93 263.83 23.94



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 550.50 23.84 650.00 23.84 513.83 23.88
February 482.50 23.94 611.67 23.87 469.83 23.90
March 545.67 23.90 684.17 23.84 525.00 23.88
April 521.17 23.98 705.67 23.85 519.67 23.89
May 540.83 23.99 730.33 23.86 540.83 23.90
June 540.33 23.99 720.00 23.87 540.33 23.91
July 566.17 23.99 744.00 23.88 566.17 23.92
August 567.33 23.99 744.00 23.89 567.33 23.92
September 538.67 23.99 720.00 23.87 538.67 23.91
October 539.50 23.99 721.00 23.89 539.50 23.92
November 514.33 23.96 653.50 23.88 505.17 23.91
December 537.83 23.89 641.67 23.88 509.00 23.91
             
Annual Sum or Average 6444.83 23.95 8326.00 23.87 6335.33 23.90
Minimum of Months 482.50 23.84 611.67 23.84 469.83 23.88
Maximum of Months 567.33 23.99 744.00 23.89 567.33 23.92



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.58 9.83 21.58 9.83 21.57
February 672.00 21.52 2.50 21.51 2.50 21.51
March 744.00 21.47 0.00 21.47 0.00 21.47
April 720.00 21.93 0.00 21.93 0.00 21.93
May 744.00 21.94 0.00 21.94 0.00 21.94
June 720.00 22.34 0.00 22.34 0.00 22.34
July 715.83 22.72 0.00 22.72 0.00 22.72
August 687.17 22.78 0.00 22.78 0.00 22.78
September 703.17 22.49 0.00 22.49 0.00 22.49
October 703.83 22.51 5.17 22.52 0.00 22.52
November 720.00 21.79 0.00 21.79 0.00 21.79
December 744.00 21.66 3.17 21.66 3.17 21.65
             
Annual Sum or Average 8618.00 22.06 20.67 22.05 15.50 22.05
Minimum of Months 672.00 21.47 0.00 21.47 0.00 21.47
Maximum of Months 744.00 22.78 9.83 22.78 9.83 22.78



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.91787 39.99367 0.06196 5.32178
February 672.00000 22.28861 44.14821 -0.0761 5.30605
March 744.00000 22.02638 48.49102 -0.1162 5.40607
April 720.00000 21.92517 53.65262 -0.1111 5.42089
May 744.00000 21.92994 53.26701 -1.2316 36.93257
June 720.00000 21.80978 60.74327 -1.2282 36.75480
July 744.00000 22.20090 62.98484 -1.0702 29.34186
August 744.00000 22.32394 63.38922 -1.0229 27.25965
September 720.00000 22.70342 58.85806 -0.9125 22.82482
October 744.00000 23.03938 47.45979 0.14310 5.65671
November 720.00000 23.16848 41.22774 0.13372 5.61402
December 744.00000 22.99609 34.80631 0.04706 5.30264
           
Annual Sum or Average 8760.00000 22.44591 50.77465 -0.4508 15.99689
Minimum of Months 672.00000 21.80978 34.80631 -1.2316 5.30264
Maximum of Months 744.00000 23.16848 63.38922 0.14310 36.93257



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.97312 40.26239 -0.0765 7.13157
February 672.00000 21.74519 43.77341 -0.1286 6.94030
March 744.00000 21.49774 48.06236 -0.1779 7.00019
April 720.00000 21.64453 52.71126 -0.0883 6.08131
May 744.00000 21.32157 53.25189 -1.3183 41.63755
June 720.00000 21.51052 60.07115 -1.1909 35.19449
July 744.00000 21.94039 62.48177 -1.0046 26.77053
August 744.00000 22.30553 62.14821 -0.8668 21.70278
September 720.00000 22.33551 58.50021 -0.8778 23.22044
October 744.00000 22.50046 47.24833 0.13009 6.95820
November 720.00000 22.10038 41.80672 -0.0236 6.80884
December 744.00000 22.10272 34.77704 -0.0692 7.11973
           
Annual Sum or Average 8760.00000 21.91639 50.44802 -0.4764 16.44224
Minimum of Months 672.00000 21.32157 34.77704 -1.3183 6.08131
Maximum of Months 744.00000 22.50046 62.48177 0.13009 41.63755



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.48998 40.96279 0.00284 5.47623
February 672.00000 22.46025 43.96931 0.01081 5.35726
March 744.00000 22.28692 47.96040 -0.0081 5.47193
April 720.00000 22.61832 51.84311 0.10570 5.69751
May 744.00000 22.55876 51.66683 -0.9498 24.68162
June 720.00000 22.78083 57.86128 -0.8260 20.04852
July 744.00000 23.05665 60.48433 -0.7029 15.93266
August 744.00000 23.16970 60.93519 -0.6568 14.55695
September 720.00000 23.08432 57.92354 -0.7095 16.09211
October 744.00000 23.12486 47.42007 0.21501 6.40416
November 720.00000 22.75923 42.22072 0.08044 5.47622
December 744.00000 22.66792 35.62048 0.01309 5.27982
           
Annual Sum or Average 8760.00000 22.75662 49.92645 -0.2873 10.90778
Minimum of Months 672.00000 22.28692 35.62048 -0.9498 5.27982
Maximum of Months 744.00000 23.16970 60.93519 0.21501 24.68162



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.59389 36.30854 0.62057 16.36157
February 672.00000 22.60904 39.06840 0.63821 16.73070
March 744.00000 22.57762 42.85314 0.65587 17.22435
April 720.00000 22.59740 47.57295 0.70935 18.69432
May 744.00000 22.61287 47.11077 -0.0504 11.38547
June 720.00000 22.61691 53.97166 0.01487 11.30978
July 744.00000 22.61778 57.41344 0.05479 11.11995
August 744.00000 22.61701 58.21072 0.06497 11.28922
September 720.00000 22.62138 54.89869 0.02354 11.18291
October 744.00000 22.63890 44.13229 0.71393 18.86727
November 720.00000 22.64929 37.93566 0.65214 17.11718
December 744.00000 22.62689 31.12872 0.59678 15.62179
           
Annual Sum or Average 8760.00000 22.61489 45.91006 0.38964 14.72752
Minimum of Months 672.00000 22.57762 31.12872 -0.0504 11.11995
Maximum of Months 744.00000 22.64929 58.21072 0.71393 18.86727



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.02424 43.62348 0.24463 7.37332
February 672.00000 22.79499 46.99016 0.18836 6.77229
March 744.00000 22.48780 51.10536 0.12523 6.42959
April 720.00000 22.66445 55.40366 0.21148 6.50580
May 744.00000 22.36026 55.83384 -0.9114 23.35063
June 720.00000 22.51617 62.33873 -0.7987 19.25531
July 744.00000 22.77406 65.00631 -0.6663 14.97233
August 744.00000 23.05646 64.93100 -0.5483 11.83426
September 720.00000 23.17082 61.27622 -0.5269 11.76320
October 744.00000 23.34344 50.55057 0.39628 9.08979
November 720.00000 23.17834 45.03982 0.29815 7.64956
December 744.00000 23.17400 38.49867 0.25514 7.26273
           
Annual Sum or Average 8760.00000 22.87940 53.40686 -0.1464 11.05351
Minimum of Months 672.00000 22.36026 38.49867 -0.9114 6.42959
Maximum of Months 744.00000 23.34344 65.00631 0.39628 23.35063



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.03019 42.90733 0.17261 6.10727
February 672.00000 22.95149 45.89133 0.16635 5.97974
March 744.00000 22.75294 49.83553 0.13891 5.93537
April 720.00000 22.94685 53.97067 0.22199 6.50198
May 744.00000 22.88283 53.79523 -0.7962 19.21164
June 720.00000 23.04735 60.01496 -0.6873 15.78823
July 744.00000 23.21529 62.84281 -0.5976 13.22886
August 744.00000 23.31600 63.29167 -0.5539 12.04872
September 720.00000 23.32321 60.05660 -0.5752 12.49322
October 744.00000 23.43296 49.51406 0.33537 7.72560
November 720.00000 23.22952 44.23759 0.23511 6.50164
December 744.00000 23.19175 37.75537 0.18047 5.95322
           
Annual Sum or Average 8760.00000 23.11104 52.03165 -0.1486 9.81511
Minimum of Months 672.00000 22.75294 37.75537 -0.7962 5.93537
Maximum of Months 744.00000 23.43296 63.29167 0.33537 19.21164



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.58291 46.71224 -0.2284 7.06441
February 672.00000 21.51254 49.83239 -0.2292 6.90659
March 744.00000 21.48369 53.30433 -0.2214 6.90133
April 720.00000 21.64227 55.66768 -0.1183 6.20536
May 744.00000 21.62230 55.79888 -1.2549 39.03115
June 720.00000 21.66532 58.65225 -1.1815 35.54031
July 744.00000 21.70989 58.72116 -1.1226 32.92833
August 744.00000 21.71186 58.98321 -1.1153 32.66341
September 720.00000 21.69070 58.37545 -1.1519 34.36945
October 744.00000 21.68506 50.70953 -0.1041 6.18591
November 720.00000 21.62638 47.68524 -0.1876 6.73202
December 744.00000 21.60509 41.32200 -0.2441 7.22911
           
Annual Sum or Average 8760.00000 21.62881 52.98306 -0.5990 18.55044
Minimum of Months 672.00000 21.48369 41.32200 -1.2549 6.18591
Maximum of Months 744.00000 21.71186 58.98321 -0.1041 39.03115



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.40824 47.65986 -0.3164 7.77922
February 672.00000 21.40070 50.55802 -0.2878 7.31746
March 744.00000 21.45081 53.96517 -0.2527 7.18385
April 720.00000 21.94525 55.54342 -0.0739 6.66897
May 744.00000 22.03964 54.74684 -1.1420 34.84244
June 720.00000 22.53550 56.85116 -0.9316 27.48830
July 744.00000 22.82752 57.42639 -0.7978 23.05366
August 744.00000 22.73926 58.76824 -0.8273 23.57530
September 720.00000 22.29437 58.86999 -1.0034 28.70116
October 744.00000 22.12939 51.24152 -0.0415 6.30057
November 720.00000 21.55812 48.73319 -0.2463 7.03401
December 744.00000 21.44719 42.00886 -0.3337 7.93366
           
Annual Sum or Average 8760.00000 21.98499 53.02981 -0.5227 15.70518
Minimum of Months 672.00000 21.40070 42.00886 -1.1420 6.30057
Maximum of Months 744.00000 22.82752 58.86999 -0.0415 34.84244



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.39392 45.11847 -0.3279 7.57506
February 672.00000 21.38270 48.18222 -0.3055 7.17000
March 744.00000 21.40871 51.75126 -0.2759 6.84876
April 720.00000 21.62675 54.62268 -0.1899 6.15207
May 744.00000 21.74385 53.57429 -1.2927 40.39630
June 720.00000 22.08935 57.10204 -1.1355 33.15627
July 744.00000 22.30353 59.46503 -1.0381 29.04619
August 744.00000 22.23457 60.78876 -1.0628 29.99575
September 720.00000 21.94630 58.89574 -1.1861 35.30854
October 744.00000 21.92008 49.85554 -0.1359 6.11377
November 720.00000 21.43166 46.62411 -0.2993 7.17154
December 744.00000 21.38106 39.70574 -0.3621 7.96790
           
Annual Sum or Average 8760.00000 21.74108 52.14924 -0.6363 18.13882
Minimum of Months 672.00000 21.38106 39.70574 -1.2927 6.11377
Maximum of Months 744.00000 22.30353 60.78876 -0.1359 40.39630



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.63192 46.58514 -0.2140 6.90445
February 672.00000 21.52920 49.85608 -0.2293 6.88318
March 744.00000 21.52688 53.01838 -0.2137 6.84660
April 720.00000 21.68015 55.54088 -0.1156 6.21108
May 744.00000 21.65397 55.63863 -1.2589 39.22916
June 720.00000 21.67930 59.08347 -1.1936 36.10951
July 744.00000 21.73550 59.00425 -1.1261 33.12689
August 744.00000 21.73706 59.01123 -1.1140 32.63049
September 720.00000 21.69045 59.08972 -1.1689 35.11974
October 744.00000 21.69885 50.88470 -0.1042 6.14521
November 720.00000 21.65314 47.83846 -0.1856 6.65357
December 744.00000 21.63894 41.28150 -0.2367 7.09623
           
Annual Sum or Average 8760.00000 21.65541 53.07037 -0.5990 18.64903
Minimum of Months 672.00000 21.52688 41.28150 -1.2589 6.14521
Maximum of Months 744.00000 21.73706 59.08972 -0.1042 39.22916



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.42855 47.40626 -0.3081 7.55569
February 672.00000 21.38747 50.60497 -0.2951 7.24638
March 744.00000 21.46694 53.76611 -0.2508 7.03049
April 720.00000 21.87495 55.81744 -0.0936 6.23269
May 744.00000 21.95719 55.16854 -1.1781 35.72167
June 720.00000 22.31007 58.20224 -1.0106 28.91236
July 744.00000 22.64134 58.62516 -0.8606 23.75194
August 744.00000 22.61528 59.60186 -0.8670 23.89576
September 720.00000 22.14931 60.37126 -1.0616 30.53394
October 744.00000 22.10307 51.55379 -0.0506 6.08309
November 720.00000 21.52067 48.85822 -0.2594 6.94277
December 744.00000 21.45928 42.04022 -0.3307 7.72420
           
Annual Sum or Average 8760.00000 21.91321 53.49982 -0.5486 16.01699
Minimum of Months 672.00000 21.38747 42.04022 -1.1781 6.08309
Maximum of Months 744.00000 22.64134 60.37126 -0.0506 35.72167



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.54570 47.60970 -0.2568 7.51433
February 672.00000 21.46493 50.91052 -0.2582 7.34460
March 744.00000 21.44651 54.46093 -0.2430 7.30220
April 720.00000 21.63384 56.68625 -0.1226 6.40596
May 744.00000 21.61468 56.76199 -1.2644 39.72460
June 720.00000 21.66091 59.69352 -1.1804 35.69597
July 744.00000 21.70755 59.75625 -1.1156 32.81231
August 744.00000 21.70720 60.24544 -1.1111 32.67181
September 720.00000 21.68103 59.92510 -1.1565 34.77942
October 744.00000 21.66781 51.81231 -0.1160 6.39732
November 720.00000 21.59251 48.76456 -0.2133 7.09911
December 744.00000 21.56319 42.10796 -0.2765 7.72653
           
Annual Sum or Average 8760.00000 21.60794 54.06293 -0.6118 18.85941
Minimum of Months 672.00000 21.44651 42.10796 -1.2644 6.39732
Maximum of Months 744.00000 21.70755 60.24544 -0.1160 39.72460



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.32622 48.72852 -0.3591 8.46048
February 672.00000 21.32993 51.76628 -0.3248 7.91157
March 744.00000 21.42137 55.14423 -0.2742 7.64328
April 720.00000 21.99450 56.31134 -0.0655 7.10447
May 744.00000 22.07951 55.42480 -1.1333 35.18857
June 720.00000 22.63745 57.09737 -0.8930 27.48588
July 744.00000 22.94289 57.26914 -0.7497 22.92401
August 744.00000 22.82005 58.86991 -0.7937 23.58777
September 720.00000 22.29493 60.02366 -1.0018 29.16224
October 744.00000 22.06622 52.33617 -0.0626 6.54970
November 720.00000 21.47968 49.96391 -0.2858 7.59107
December 744.00000 21.34624 42.94568 -0.3841 8.76551
           
Annual Sum or Average 8760.00000 21.98223 53.81813 -0.5286 16.07817
Minimum of Months 672.00000 21.32622 42.94568 -1.1333 6.54970
Maximum of Months 744.00000 22.94289 60.02366 -0.0626 35.18857



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.69709 46.36832 -0.1526 6.81619
February 672.00000 21.61323 49.58843 -0.1845 6.79720
March 744.00000 21.56701 52.79116 -0.1984 6.90118
April 720.00000 21.65189 55.69618 -0.1386 6.38734
May 744.00000 21.59373 56.66914 -1.3229 42.37952
June 720.00000 21.62246 60.82988 -1.2609 39.26418
July 744.00000 21.68419 61.55359 -1.1991 36.42406
August 744.00000 21.69737 60.58581 -1.1710 35.22832
September 720.00000 21.68047 58.32400 -1.1808 35.86528
October 744.00000 21.70722 50.58083 -0.0926 6.35400
November 720.00000 21.70806 47.23347 -0.1372 6.68486
December 744.00000 21.70973 41.25288 -0.1697 6.99138
           
Annual Sum or Average 8760.00000 21.66138 53.46530 -0.6032 19.75426
Minimum of Months 672.00000 21.56701 41.25288 -1.3229 6.35400
Maximum of Months 744.00000 21.70973 61.55359 -0.0926 42.37952



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.49596 43.50041 0.30922 7.49207
February 672.00000 23.55715 45.86292 0.34317 7.82002
March 744.00000 23.55192 49.38661 0.36859 8.17579
April 720.00000 23.69506 53.15927 0.45355 9.53278
May 744.00000 23.73196 52.57722 -0.4278 9.10673
June 720.00000 23.80191 58.46674 -0.3346 7.55263
July 744.00000 23.84881 61.36594 -0.2789 6.74491
August 744.00000 23.82725 62.19312 -0.2845 6.83107
September 720.00000 23.77267 59.49764 -0.3457 7.73671
October 744.00000 23.74505 49.65133 0.45918 9.74883
November 720.00000 23.59880 44.71612 0.35277 7.99735
December 744.00000 23.54465 38.55142 0.28781 7.08902
           
Annual Sum or Average 8760.00000 23.68155 51.59825 0.07351 7.98462
Minimum of Months 672.00000 23.49596 38.55142 -0.4278 6.74491
Maximum of Months 744.00000 23.84881 62.19312 0.45918 9.74883



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.65742 42.49775 0.38314 8.45264
February 672.00000 23.71233 44.81002 0.41636 8.89585
March 744.00000 23.71274 48.28970 0.44365 9.35058
April 720.00000 23.82297 52.16358 0.51851 10.78788
May 744.00000 23.85113 51.60482 -0.3363 7.52915
June 720.00000 23.88748 57.58765 -0.2573 6.50767
July 744.00000 23.91139 60.58440 -0.2129 6.01352
August 744.00000 23.89310 61.41762 -0.2187 6.07850
September 720.00000 23.86153 58.63061 -0.2699 6.67726
October 744.00000 23.83537 48.85541 0.51099 10.74370
November 720.00000 23.73779 43.74571 0.42024 9.00969
December 744.00000 23.69600 37.59065 0.35886 7.96998
           
Annual Sum or Average 8760.00000 23.79866 50.67002 0.14465 8.16120
Minimum of Months 672.00000 23.65742 37.59065 -0.3363 6.01352
Maximum of Months 744.00000 23.91139 61.41762 0.51851 10.78788



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.62977 41.37848 1.02636 30.54257
February 672.00000 23.68359 43.72074 1.05185 31.19066
March 744.00000 23.65578 47.11162 1.07295 32.30456
April 720.00000 23.72794 51.28264 1.15205 35.35720
May 744.00000 23.73587 50.88442 0.55494 17.18550
June 720.00000 23.77848 56.97208 0.64075 18.76855
July 744.00000 23.80431 59.99477 0.70045 20.11789
August 744.00000 23.80964 60.68759 0.70687 20.21514
September 720.00000 23.78442 57.76729 0.64512 18.75133
October 744.00000 23.77228 48.14481 1.15491 35.31691
November 720.00000 23.69488 42.74874 1.05975 31.51130
December 744.00000 23.66913 36.59298 1.00350 29.35917
           
Annual Sum or Average 8760.00000 23.72902 49.79709 0.89644 26.68845
Minimum of Months 672.00000 23.62977 36.59298 0.55494 17.18550
Maximum of Months 744.00000 23.80964 60.68759 1.15491 35.35720



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.47412 40.06721 -0.2894 7.18086
February 672.00000 21.45928 43.27097 -0.2746 6.71467
March 744.00000 21.34457 47.35134 -0.2796 6.85858
April 720.00000 21.72690 51.33446 -0.1577 5.75120
May 744.00000 21.89596 50.50636 -1.2338 37.06732
June 720.00000 22.31297 56.34114 -1.0503 28.44557
July 744.00000 22.64520 59.17146 -0.9142 22.74100
August 744.00000 22.63813 60.16360 -0.9110 22.60037
September 720.00000 22.40434 57.22725 -1.0127 26.81705
October 744.00000 22.51578 46.02696 0.01100 5.40848
November 720.00000 21.78109 41.37455 -0.2040 6.10036
December 744.00000 21.59461 34.44821 -0.2927 7.02033
           
Annual Sum or Average 8760.00000 21.98624 48.95808 -0.5524 15.27841
Minimum of Months 672.00000 21.34457 34.44821 -1.2338 5.40848
Maximum of Months 744.00000 22.64520 60.16360 0.01100 37.06732



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.77842 43.78065 -0.2144 6.32999
February 672.00000 21.76397 46.96333 -0.2006 5.96650
March 744.00000 21.57095 51.04329 -0.2235 6.29939
April 720.00000 21.98284 54.94279 -0.0958 5.42864
May 744.00000 22.05868 54.41412 -1.1897 34.93639
June 720.00000 22.37749 60.49554 -1.0386 27.96198
July 744.00000 22.77670 62.90997 -0.8798 21.41994
August 744.00000 22.88674 63.43992 -0.8374 19.84311
September 720.00000 22.65029 60.75445 -0.9390 23.75731
October 744.00000 22.80439 49.69446 0.08192 5.47003
November 720.00000 22.13618 45.02821 -0.1177 5.47021
December 744.00000 21.99961 38.14200 -0.1946 5.95849
           
Annual Sum or Average 8760.00000 22.23544 52.65140 -0.4891 14.11941
Minimum of Months 672.00000 21.57095 38.14200 -1.1897 5.42864
Maximum of Months 744.00000 22.88674 63.43992 0.08192 34.93639



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.58335 41.01871 -0.2427 6.71707
February 672.00000 21.51561 44.25953 -0.2403 6.49509
March 744.00000 21.47102 48.14558 -0.2287 6.49817
April 720.00000 21.93429 51.88296 -0.0824 5.53989
May 744.00000 21.94452 51.49417 -1.1839 34.83378
June 720.00000 22.34348 57.35200 -1.0015 26.55292
July 744.00000 22.73869 59.69471 -0.8414 20.13988
August 744.00000 22.82435 60.26868 -0.8070 18.93377
September 720.00000 22.51782 57.87697 -0.9352 23.88412
October 744.00000 22.57206 46.92343 0.05354 5.65123
November 720.00000 21.79205 42.47998 -0.1780 6.02405
December 744.00000 21.65884 35.54350 -0.2562 6.70147
           
Annual Sum or Average 8760.00000 22.07848 49.76103 -0.4968 14.04282
Minimum of Months 672.00000 21.47102 35.54350 -1.1839 5.53989
Maximum of Months 744.00000 22.82435 60.26868 0.05354 34.83378



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.57646 39.33060 -0.2658 6.97030
February 672.00000 21.58161 42.47785 -0.2468 6.44657
March 744.00000 21.45815 46.56138 -0.2532 6.60723
April 720.00000 21.85075 50.48153 -0.1291 5.62267
May 744.00000 22.03876 49.60284 -1.1855 34.75872
June 720.00000 22.45273 55.38960 -1.0021 26.43942
July 744.00000 22.78283 58.16927 -0.8664 20.99510
August 744.00000 22.77075 59.15854 -0.8650 20.92765
September 720.00000 22.52792 56.30482 -0.9700 25.08501
October 744.00000 22.64383 45.15897 0.04121 5.48211
November 720.00000 21.90475 40.57797 -0.1759 5.91321
December 744.00000 21.71313 33.70938 -0.2659 6.75311
           
Annual Sum or Average 8760.00000 22.11198 48.09430 -0.5170 14.38256
Minimum of Months 672.00000 21.45815 33.70938 -1.1855 5.48211
Maximum of Months 744.00000 22.78283 59.15854 0.04121 34.75872



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.378489E+11 78797.02 15-JAN-09:53 661.07 0.122814E+12 0.00 0.160663E+12 2.91 4.04 14-JAN-16:03 0.00 0.00
February 0.251833E+11 75033.05 01-FEB-09:51 607.17 0.812331E+11 0.00 0.106416E+12 2.96 4.06 03-FEB-16:03 0.00 0.00
March 0.253839E+11 77136.29 23-MAR-15:03 632.61 0.827918E+11 0.00 0.108176E+12 2.80 4.22 23-MAR-15:03 0.00 0.00
April 0.474003E+11 75834.71 26-APR-10:50 708.82 0.152959E+12 0.00 0.200360E+12 3.21 4.07 08-APR-15:03 0.00 0.00
May 0.488337E+11 77749.52 18-MAY-15:02 737.33 0.153671E+12 0.00 0.202504E+12 3.18 4.23 18-MAY-15:02 0.00 0.00
June 0.764370E+11 90944.82 28-JUN-15:05 720.00 0.253415E+12 0.00 0.329852E+12 3.25 4.35 29-JUN-18:03 0.00 0.00
July 0.129012E+12 126695.22 19-JUL-15:03 744.00 0.473313E+12 0.00 0.602325E+12 3.53 4.59 31-JUL-21:54 0.00 0.00
August 0.140947E+12 133897.96 18-AUG-15:03 744.00 0.529195E+12 0.00 0.670142E+12 3.63 4.50 18-AUG-21:54 0.00 0.00
September 0.985347E+11 147928.32 29-SEP-13:00 720.00 0.342030E+12 0.00 0.440564E+12 3.36 4.47 21-SEP-21:52 0.00 0.00
October 0.107221E+12 157368.80 16-OCT-10:50 744.00 0.378924E+12 0.00 0.486145E+12 3.41 4.55 01-OCT-21:53 0.00 0.00
November 0.404623E+11 93350.03 19-NOV-09:41 694.00 0.131591E+12 0.00 0.172054E+12 3.15 4.02 18-NOV-16:01 0.00 0.00
December 0.418181E+11 90877.62 05-DEC-09:41 687.14 0.137769E+12 0.00 0.179587E+12 3.04 4.09 19-DEC-16:03 0.00 0.00
                         
Annual Sum or Average 0.819082E+12     8400.14 0.283971E+13 0.00 0.365879E+13 3.21     0.00 0.00
Minimum of Months 0.251833E+11 75033.05   607.17 0.812331E+11 0.00 0.106416E+12 2.80 4.02   0.00 0.00
Maximum of Months 0.140947E+12 157368.80   744.00 0.529195E+12 0.00 0.670142E+12 3.63 4.59   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.115001E+12 0.00 554.58 175069.70 08-JAN-07:00 0.00 40.82 70.70 0.27 0.00 0.16 0.63 08-JAN-07:00
February 0.830717E+11 0.00 531.89 141382.69 04-FEB-06:00 0.00 37.41 70.51 0.20 0.00 0.12 0.51 04-FEB-06:00
March 0.119351E+12 0.00 605.39 168884.07 30-MAR-03:00 0.00 35.93 71.01 0.27 0.00 0.16 0.61 30-MAR-03:00
April 0.471808E+11 0.00 422.35 135442.55 01-APR-06:00 0.00 31.02 59.50 0.09 0.00 0.07 0.49 01-APR-06:00
May 0.415729E+11 0.00 418.81 111864.07 15-MAY-02:00 0.00 30.49 57.75 0.08 0.00 0.06 0.41 15-MAY-02:00
June 0.780820E+10 0.00 222.10 63289.34 13-JUN-04:00 0.00 30.21 45.77 0.01 0.00 0.01 0.23 13-JUN-04:00
July 0.748678E+09 0.00 101.33 28659.63 06-JUL-03:00 0.00 29.35 36.19 0.00 0.00 0.00 0.10 06-JUL-03:00
August 0.520235E+09 0.00 100.80 28062.88 22-AUG-08:54 0.00 29.01 35.85 0.00 0.00 0.00 0.10 22-AUG-08:54
September 0.382106E+10 0.00 144.42 61482.47 20-SEP-03:00 0.00 32.81 42.38 0.01 0.00 0.01 0.22 20-SEP-03:00
October 0.168589E+11 0.00 215.85 94516.68 12-OCT-05:00 0.00 32.56 46.18 0.03 0.00 0.02 0.34 12-OCT-05:00
November 0.681789E+11 0.00 462.04 131764.70 29-NOV-22:50 0.00 36.86 64.75 0.15 0.00 0.10 0.48 29-NOV-22:50
December 0.109647E+12 0.00 524.78 146582.49 23-DEC-06:00 0.00 40.84 69.44 0.26 0.00 0.15 0.53 23-DEC-06:00
                           
Annual Sum or Average 0.613761E+12 0.00 4304.36     0.00 33.93 55.74 0.12 0.00 0.07    
Minimum of Months 0.520235E+09 0.00 100.80 28062.88   0.00 29.01 35.85 0.00 0.00 0.00 0.10  
Maximum of Months 0.119351E+12 0.00 605.39 175069.70   0.00 40.84 71.01 0.27 0.00 0.16 0.63  



Table of Contents

Report: DXReportMonthly

For: SWHSYS1 HPWH DXCOIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.499176E+11 0.00 390.94 0.499156E+11 2051905.14 0.00 1.00 01-JAN-06:15 0.00 01-JAN-00:10 51441.99 31-JAN-06:15 51441.99 31-JAN-06:15 69.19 31-JAN-07:15 0.00 0.00 01-JAN-00:10
February 0.453013E+11 0.00 353.43 0.433881E+11 0.191326E+10 0.00 1.00 01-FEB-06:15 0.00 01-FEB-00:03 52092.34 02-FEB-18:15 49885.96 03-FEB-09:00 2210.73 02-FEB-14:10 0.00 0.00 01-FEB-00:03
March 0.495808E+11 0.00 390.04 0.434254E+11 0.615536E+10 0.00 1.00 01-MAR-06:15 0.00 01-MAR-00:03 52029.53 01-MAR-06:15 45547.99 01-MAR-08:00 6989.37 31-MAR-23:20 0.00 0.00 01-MAR-00:03
April 0.475319E+11 0.00 366.63 0.399168E+11 0.761519E+10 0.00 1.00 01-APR-05:15 0.00 01-APR-00:10 55011.12 01-APR-07:13 46149.53 03-APR-09:05 8885.27 01-APR-15:05 0.00 0.00 01-APR-00:10
May 0.477518E+11 0.00 376.55 0.407837E+11 0.696814E+10 0.00 1.00 01-MAY-05:15 0.00 01-MAY-00:05 54908.46 01-MAY-05:15 46833.60 01-MAY-07:00 9162.55 31-MAY-23:20 0.00 0.00 01-MAY-00:05
June 0.456842E+11 0.00 352.47 0.356037E+11 0.100805E+11 0.00 1.00 01-JUN-05:15 0.00 01-JUN-00:05 59585.55 30-JUN-23:07 44903.08 01-JUN-08:03 18100.67 30-JUN-23:07 0.00 0.00 01-JUN-00:05
July 0.469601E+11 0.00 353.16 0.327211E+11 0.142390E+11 0.00 1.00 01-JUL-05:08 0.00 01-JUL-00:20 59997.65 01-JUL-05:08 41789.84 01-JUL-10:15 18216.88 01-JUL-15:07 0.00 0.00 01-JUL-00:10
August 0.470845E+11 0.00 352.44 0.308136E+11 0.162709E+11 0.00 1.00 01-AUG-05:15 0.00 01-AUG-00:05 60747.00 31-AUG-08:15 39744.14 02-AUG-07:55 21048.26 28-AUG-15:07 0.00 0.00 01-AUG-00:05
September 0.456922E+11 0.00 348.41 0.346820E+11 0.110102E+11 0.00 1.00 01-SEP-05:15 0.00 01-SEP-00:05 58600.87 30-SEP-05:08 44431.27 25-SEP-08:54 14188.06 30-SEP-15:06 0.00 0.00 01-SEP-00:05
October 0.480308E+11 0.00 371.59 0.448275E+11 0.320338E+10 0.00 1.00 01-OCT-05:07 0.00 01-OCT-00:20 57525.04 31-OCT-18:03 53603.77 31-OCT-08:03 3925.09 31-OCT-15:18 0.00 0.00 01-OCT-00:10
November 0.466177E+11 0.00 372.84 0.466016E+11 16126570.43 0.00 1.00 01-NOV-05:05 0.00 01-NOV-00:05 52402.95 30-NOV-06:15 52368.77 30-NOV-06:15 413.74 28-NOV-06:15 0.00 0.00 01-NOV-00:05
December 0.489460E+11 0.00 391.18 0.489460E+11 0.00 0.00 1.00 01-DEC-06:15 0.00 01-DEC-00:03 50696.46 31-DEC-02:10 50696.46 31-DEC-02:10 0.00 04-DEC-20:50 0.00 0.00 01-DEC-00:03
                                       
Annual Sum or Average 0.569099E+12 0.00 4419.68 0.491625E+12 0.774740E+11 0.00                     0.00    
Minimum of Months 0.453013E+11 0.00 348.41 0.308136E+11 0.00 0.00 1.00   0.00   50696.46   39744.14   0.00   0.00 0.00  
Maximum of Months 0.499176E+11 0.00 391.18 0.499156E+11 0.162709E+11 0.00 1.00   0.00   60747.00   53603.77   21048.26   0.00 0.00  



Table of Contents

Report: DXReportMonthly

For: SWHSYSLAUNDRY HPWH DXCOIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.515170E+11 0.00 360.52 0.515156E+11 1383845.01 0.00 1.00 01-JAN-17:10 0.00 01-JAN-00:10 65101.75 31-JAN-17:10 65101.75 31-JAN-20:10 67.30 31-JAN-20:20 0.00 0.00 01-JAN-00:10
February 0.471456E+11 0.00 323.59 0.451680E+11 0.197750E+10 0.00 1.00 01-FEB-17:10 0.00 01-FEB-00:07 65925.25 02-FEB-19:50 63151.14 03-FEB-17:10 2778.62 10-FEB-23:00 0.00 0.00 01-FEB-00:03
March 0.520521E+11 0.00 381.73 0.456038E+11 0.644835E+10 0.00 1.00 01-MAR-17:05 0.00 01-MAR-00:07 65845.71 01-MAR-23:40 57648.86 01-MAR-17:05 8207.61 04-MAR-17:05 0.00 0.00 01-MAR-00:03
April 0.531873E+11 0.00 337.93 0.446769E+11 0.851037E+10 0.00 1.00 01-APR-16:05 0.00 01-APR-00:20 69621.11 01-APR-18:00 58417.85 02-APR-21:00 11225.47 01-APR-16:05 0.00 0.00 01-APR-00:10
May 0.548344E+11 0.00 350.82 0.468482E+11 0.798618E+10 0.00 1.00 01-MAY-16:10 0.00 01-MAY-00:05 69491.12 01-MAY-16:10 59279.90 03-MAY-21:00 10211.26 01-MAY-16:10 0.00 0.00 01-MAY-00:05
June 0.557210E+11 0.00 336.99 0.434388E+11 0.122822E+11 0.00 1.00 01-JUN-16:10 0.00 01-JUN-00:05 72970.63 01-JUN-16:10 56838.09 01-JUN-21:00 16138.83 01-JUN-16:10 0.00 0.00 01-JUN-00:05
July 0.599842E+11 0.00 344.61 0.418049E+11 0.181793E+11 0.00 1.00 01-JUL-16:05 0.00 01-JUL-00:20 75935.24 01-JUL-16:05 52898.92 14-JUL-20:00 23043.65 01-JUL-16:05 0.00 0.00 01-JUL-00:10
August 0.607275E+11 0.00 344.14 0.397433E+11 0.209842E+11 0.00 1.00 01-AUG-16:10 0.00 01-AUG-00:05 76884.09 31-AUG-16:10 50310.30 22-AUG-21:00 26628.62 28-AUG-16:05 0.00 0.00 01-AUG-00:05
September 0.566682E+11 0.00 336.67 0.430168E+11 0.136514E+11 0.00 1.00 01-SEP-16:10 0.00 01-SEP-00:05 74166.58 30-SEP-16:10 56241.36 28-SEP-20:00 17942.64 30-SEP-16:10 0.00 0.00 01-SEP-00:05
October 0.574231E+11 0.00 349.52 0.536066E+11 0.381657E+10 0.00 1.00 01-OCT-16:10 0.00 01-OCT-00:20 72804.33 31-OCT-17:25 67858.12 31-OCT-18:00 4947.81 31-OCT-16:10 0.00 0.00 01-OCT-00:10
November 0.506655E+11 0.00 343.83 0.506541E+11 11379199.02 0.00 1.00 01-NOV-16:10 0.00 01-NOV-00:05 66318.56 30-NOV-17:10 66295.79 30-NOV-17:10 420.69 27-NOV-19:00 0.00 0.00 01-NOV-00:05
December 0.507275E+11 0.00 358.89 0.507275E+11 0.00 0.00 1.00 01-DEC-17:10 0.00 01-DEC-00:07 64157.74 31-DEC-18:13 64157.74 31-DEC-18:13 0.00 31-DEC-20:40 0.00 0.00 01-DEC-00:03
                                       
Annual Sum or Average 0.650653E+12 0.00 4169.25 0.556805E+12 0.938489E+11 0.00                     0.00    
Minimum of Months 0.471456E+11 0.00 323.59 0.397433E+11 0.00 0.00 1.00   0.00   64157.74   50310.30   0.00   0.00 0.00  
Maximum of Months 0.607275E+11 0.00 381.73 0.536066E+11 0.209842E+11 0.00 1.00   0.00   76884.09   67858.12   26628.62   0.00 0.00  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.573504E+11 0.00 285.50 0.571755E+11 0.00 0.00 0.00 0.00 205399.86 14-JAN-11:50 205399.86 14-JAN-11:50 0.00 0.00 0.00
February 0.321104E+11 0.00 232.25 0.313603E+11 0.00 0.00 0.00 0.00 193334.14 01-FEB-11:50 193334.14 01-FEB-11:50 0.00 0.00 0.00
March 0.358885E+11 0.00 211.83 0.351008E+11 0.00 0.00 0.00 0.00 180673.77 23-MAR-10:50 173668.29 11-MAR-11:50 0.00 0.00 0.00
April 0.849640E+11 0.00 357.00 0.831206E+11 0.00 0.00 0.00 0.00 248967.52 26-APR-10:50 205589.44 30-APR-10:45 0.00 0.00 0.00
May 0.906417E+11 0.00 434.67 0.895254E+11 0.00 0.00 0.00 0.00 158913.85 18-MAY-10:50 157310.80 04-MAY-12:00 0.00 0.00 0.00
June 0.168642E+12 0.00 613.50 0.145683E+12 0.00 0.00 0.00 0.00 308917.12 29-JUN-10:50 189236.04 29-JUN-10:50 0.00 0.00 0.00
July 0.344426E+12 0.00 735.00 0.222488E+12 0.00 0.00 0.00 0.00 377369.04 31-JUL-10:50 238850.42 19-JUL-10:50 0.00 0.00 0.00
August 0.387778E+12 0.00 736.50 0.232064E+12 0.00 0.00 0.00 0.00 405083.85 14-AUG-10:50 238685.32 14-AUG-10:50 0.00 0.00 0.00
September 0.228692E+12 0.00 673.83 0.174737E+12 0.00 0.00 0.00 0.00 374121.42 22-SEP-12:00 360765.21 29-SEP-10:50 0.00 0.00 0.00
October 0.256993E+12 0.00 617.75 0.206204E+12 0.00 0.00 0.00 0.00 379535.83 16-OCT-10:50 379535.83 16-OCT-10:50 0.00 0.00 0.00
November 0.597973E+11 0.00 342.83 0.590271E+11 0.00 0.00 0.00 0.00 210358.07 19-NOV-13:00 210358.07 19-NOV-13:00 0.00 0.00 0.00
December 0.660005E+11 0.00 296.08 0.660005E+11 0.00 0.00 0.00 0.00 191476.99 16-DEC-13:00 191476.99 16-DEC-13:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.181328E+13 0.00 5536.75 0.140249E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.321104E+11 0.00 211.83 0.313603E+11 0.00 0.00 0.00 0.00 158913.85   157310.80   0.00 0.00 0.00
Maximum of Months 0.387778E+12 0.00 736.50 0.232064E+12 0.00 0.00 0.00 0.00 405083.85   379535.83   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.353274E+10 0.00 171.17 0.349906E+10 0.00 0.00 0.00 0.00 20880.62 17-JAN-14:00 20570.95 13-JAN-14:00 0.00 0.00 0.00
February 0.189886E+10 0.00 130.67 0.184037E+10 0.00 0.00 0.00 0.00 17583.53 01-FEB-10:00 17583.53 01-FEB-10:00 0.00 0.00 0.00
March 0.215372E+10 0.00 109.83 0.197542E+10 0.00 0.00 0.00 0.00 22325.57 22-MAR-13:00 17622.68 11-MAR-11:00 0.00 0.00 0.00
April 0.541905E+10 0.00 211.67 0.504769E+10 0.00 0.00 0.00 0.00 22090.94 26-APR-13:00 22090.94 26-APR-13:00 0.00 0.00 0.00
May 0.572637E+10 0.00 273.33 0.557752E+10 0.00 0.00 0.00 0.00 19286.16 04-MAY-13:00 17662.36 03-MAY-12:50 0.00 0.00 0.00
June 0.129295E+11 0.00 460.00 0.101515E+11 0.00 0.00 0.00 0.00 31088.77 29-JUN-12:30 17826.99 29-JUN-12:30 0.00 0.00 0.00
July 0.288160E+11 0.00 581.00 0.167818E+11 0.00 0.00 0.00 0.00 40512.87 31-JUL-12:30 23766.96 31-JUL-12:30 0.00 0.00 0.00
August 0.328487E+11 0.00 582.67 0.176856E+11 0.00 0.00 0.00 0.00 39040.56 14-AUG-10:00 22286.25 18-AUG-12:20 0.00 0.00 0.00
September 0.187456E+11 0.00 518.17 0.130117E+11 0.00 0.00 0.00 0.00 39773.96 22-SEP-12:15 35123.78 29-SEP-13:00 0.00 0.00 0.00
October 0.207096E+11 0.00 461.00 0.151881E+11 0.00 0.00 0.00 0.00 39092.82 01-OCT-12:10 34150.23 16-OCT-12:20 0.00 0.00 0.00
November 0.355504E+10 0.00 209.17 0.347970E+10 0.00 0.00 0.00 0.00 21516.86 19-NOV-13:10 21516.86 19-NOV-13:10 0.00 0.00 0.00
December 0.428780E+10 0.00 177.33 0.428430E+10 0.00 0.00 0.00 0.00 20480.74 05-DEC-10:00 20480.74 05-DEC-10:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.140623E+12 0.00 3886.00 0.985227E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.189886E+10 0.00 109.83 0.184037E+10 0.00 0.00 0.00 0.00 17583.53   17583.53   0.00 0.00 0.00
Maximum of Months 0.328487E+11 0.00 582.67 0.176856E+11 0.00 0.00 0.00 0.00 40512.87   35123.78   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.194362E+10 0.00 410.11 0.124811E+10 0.00 0.00 0.00 0.00 12267.56 17-JAN-16:02 11682.53 14-JAN-16:01 0.00 0.00 0.00
February 0.171243E+10 0.00 325.24 0.113632E+10 0.00 0.00 0.00 0.00 12337.28 11-FEB-16:02 11440.85 03-FEB-16:01 0.00 0.00 0.00
March 0.183779E+10 0.00 336.59 0.108350E+10 0.00 0.00 0.00 0.00 11703.88 18-MAR-15:01 10921.32 10-MAR-19:02 0.00 0.00 0.00
April 0.380165E+10 0.00 553.74 0.223085E+10 0.00 0.00 0.00 0.00 12399.20 26-APR-08:62 10806.02 01-APR-15:05 0.00 0.00 0.00
May 0.351563E+10 0.00 562.00 0.195087E+10 0.00 0.00 0.00 0.00 11943.06 06-MAY-08:62 11053.84 28-MAY-15:01 0.00 0.00 0.00
June 0.516800E+10 0.00 617.47 0.287498E+10 0.00 0.00 0.00 0.00 12620.70 30-JUN-08:62 11183.42 18-JUN-15:02 0.00 0.00 0.00
July 0.755183E+10 0.00 688.69 0.432903E+10 0.00 0.00 0.00 0.00 13492.94 30-JUL-08:62 11630.98 22-JUL-15:02 0.00 0.00 0.00
August 0.786982E+10 0.00 693.39 0.451424E+10 0.00 0.00 0.00 0.00 13963.03 06-AUG-08:62 11339.84 06-AUG-15:02 0.00 0.00 0.00
September 0.605016E+10 0.00 652.70 0.342398E+10 0.00 0.00 0.00 0.00 13601.53 22-SEP-08:62 11208.06 21-SEP-15:02 0.00 0.00 0.00
October 0.556702E+10 0.00 643.22 0.380141E+10 0.00 0.00 0.00 0.00 13760.72 01-OCT-08:62 12068.63 13-OCT-15:01 0.00 0.00 0.00
November 0.263422E+10 0.00 487.71 0.165767E+10 0.00 0.00 0.00 0.00 12140.34 11-NOV-16:01 11347.07 28-NOV-16:01 0.00 0.00 0.00
December 0.225175E+10 0.00 433.73 0.179916E+10 0.00 0.00 0.00 0.00 11797.99 05-DEC-09:02 11797.99 05-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.499039E+11 0.00 6404.59 0.300501E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.171243E+10 0.00 325.24 0.108350E+10 0.00 0.00 0.00 0.00 11703.88   10806.02   0.00 0.00 0.00
Maximum of Months 0.786982E+10 0.00 693.39 0.451424E+10 0.00 0.00 0.00 0.00 13963.03   12068.63   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.384029E+09 0.00 139.34 0.221313E+09 0.00 0.00 0.00 0.00 11679.88 17-JAN-16:02 11200.97 14-JAN-16:01 0.00 0.00 0.00
February 0.528896E+09 0.00 163.16 0.292288E+09 0.00 0.00 0.00 0.00 11638.76 13-FEB-16:02 10968.93 03-FEB-16:01 0.00 0.00 0.00
March 0.754464E+09 0.00 195.92 0.380304E+09 0.00 0.00 0.00 0.00 11314.36 18-MAR-15:01 10535.68 23-MAR-15:02 0.00 0.00 0.00
April 0.209014E+10 0.00 406.83 0.100535E+10 0.00 0.00 0.00 0.00 12333.81 26-APR-21:51 11006.97 23-APR-18:11 0.00 0.00 0.00
May 0.234008E+10 0.00 432.11 0.116867E+10 0.00 0.00 0.00 0.00 12002.10 02-MAY-21:51 10640.89 17-MAY-15:02 0.00 0.00 0.00
June 0.330350E+10 0.00 403.02 0.174135E+10 0.00 0.00 0.00 0.00 13047.09 28-JUN-21:51 10731.90 13-JUN-15:02 0.00 0.00 0.00
July 0.490845E+10 0.00 423.42 0.282720E+10 0.00 0.00 0.00 0.00 14162.46 23-JUL-08:51 10948.83 22-JUL-15:02 0.00 0.00 0.00
August 0.466390E+10 0.00 418.48 0.258226E+10 0.00 0.00 0.00 0.00 14365.78 19-AUG-08:51 10921.27 06-AUG-15:02 0.00 0.00 0.00
September 0.324571E+10 0.00 406.58 0.163213E+10 0.00 0.00 0.00 0.00 13183.38 21-SEP-21:52 10779.05 30-SEP-08:61 0.00 0.00 0.00
October 0.257501E+10 0.00 388.97 0.162680E+10 0.00 0.00 0.00 0.00 13912.06 01-OCT-08:52 11927.46 14-OCT-08:61 0.00 0.00 0.00
November 0.704060E+09 0.00 250.91 0.352745E+09 0.00 0.00 0.00 0.00 11517.85 11-NOV-16:01 10879.12 28-NOV-16:01 0.00 0.00 0.00
December 0.416406E+09 0.00 163.81 0.310686E+09 0.00 0.00 0.00 0.00 11192.91 05-DEC-16:01 11192.91 05-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.259146E+11 0.00 3792.55 0.141411E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.384029E+09 0.00 139.34 0.221313E+09 0.00 0.00 0.00 0.00 11192.91   10535.68   0.00 0.00 0.00
Maximum of Months 0.490845E+10 0.00 432.11 0.282720E+10 0.00 0.00 0.00 0.00 14365.78   11927.46   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.326152E+11 0.00 547.13 0.258181E+11 0.00 0.00 0.00 0.00 46972.19 14-JAN-12:40 46972.19 14-JAN-12:40 0.00 0.00 0.00
February 0.205274E+11 0.00 393.64 0.156660E+11 0.00 0.00 0.00 0.00 41522.17 02-FEB-12:40 39865.55 03-FEB-13:40 0.00 0.00 0.00
March 0.147235E+11 0.00 384.61 0.898851E+10 0.00 0.00 0.00 0.00 34888.40 11-MAR-13:20 34888.40 11-MAR-13:20 0.00 0.00 0.00
April 0.167736E+11 0.00 496.93 0.752603E+10 0.00 0.00 0.00 0.00 27010.95 08-APR-12:40 18608.39 02-APR-13:05 0.00 0.00 0.00
May 0.931344E+10 0.00 435.80 0.287577E+10 0.00 0.00 0.00 0.00 21163.58 02-MAY-15:03 12158.02 02-MAY-15:03 0.00 0.00 0.00
June 0.130068E+11 0.00 509.12 0.395092E+10 0.00 0.00 0.00 0.00 21323.35 28-JUN-15:05 10558.88 28-JUN-15:05 0.00 0.00 0.00
July 0.219749E+11 0.00 649.13 0.789329E+10 0.00 0.00 0.00 0.00 24335.81 18-JUL-15:03 12849.08 18-JUL-15:03 0.00 0.00 0.00
August 0.304265E+11 0.00 729.42 0.131417E+11 0.00 0.00 0.00 0.00 26690.37 27-AUG-12:05 17134.67 30-AUG-13:00 0.00 0.00 0.00
September 0.331957E+11 0.00 698.26 0.178444E+11 0.00 0.00 0.00 0.00 44979.95 30-SEP-13:10 38454.58 30-SEP-13:10 0.00 0.00 0.00
October 0.422584E+11 0.00 683.72 0.308985E+11 0.00 0.00 0.00 0.00 53000.92 16-OCT-12:30 53000.92 16-OCT-12:30 0.00 0.00 0.00
November 0.338877E+11 0.00 575.32 0.253913E+11 0.00 0.00 0.00 0.00 50299.12 19-NOV-13:00 47982.42 19-NOV-12:30 0.00 0.00 0.00
December 0.373254E+11 0.00 577.06 0.326407E+11 0.00 0.00 0.00 0.00 48054.29 19-DEC-13:00 48054.29 19-DEC-13:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.306029E+12 0.00 6680.15 0.192635E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.931344E+10 0.00 384.61 0.287577E+10 0.00 0.00 0.00 0.00 21163.58   10558.88   0.00 0.00 0.00
Maximum of Months 0.422584E+11 0.00 729.42 0.326407E+11 0.00 0.00 0.00 0.00 53000.92   53000.92   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.914762E+10 0.00 307.32 0.552040E+10 0.00 0.00 0.00 0.00 64555.87 20-JAN-19:02 63090.33 15-JAN-16:01 0.00 0.00 0.00
February 0.102801E+11 0.00 374.80 0.600996E+10 0.00 0.00 0.00 0.00 64332.53 13-FEB-16:02 60621.11 03-FEB-16:01 0.00 0.00 0.00
March 0.130887E+11 0.00 398.29 0.760548E+10 0.00 0.00 0.00 0.00 65956.55 23-MAR-15:02 61009.26 10-MAR-16:02 0.00 0.00 0.00
April 0.201689E+11 0.00 415.28 0.118604E+11 0.00 0.00 0.00 0.00 69109.26 26-APR-21:51 62479.00 01-APR-15:02 0.00 0.00 0.00
May 0.244213E+11 0.00 419.19 0.156710E+11 0.00 0.00 0.00 0.00 67949.54 02-MAY-21:51 61478.99 03-MAY-15:02 0.00 0.00 0.00
June 0.287382E+11 0.00 359.55 0.186262E+11 0.00 0.00 0.00 0.00 73040.59 28-JUN-21:51 60331.09 20-JUN-15:02 0.00 0.00 0.00
July 0.354845E+11 0.00 372.42 0.228854E+11 0.00 0.00 0.00 0.00 77230.93 23-JUL-08:51 61857.70 18-JUL-18:02 0.00 0.00 0.00
August 0.329199E+11 0.00 360.75 0.203461E+11 0.00 0.00 0.00 0.00 78872.53 19-AUG-08:51 60077.18 19-AUG-15:02 0.00 0.00 0.00
September 0.252553E+11 0.00 343.88 0.152253E+11 0.00 0.00 0.00 0.00 76055.74 21-SEP-21:52 59540.86 01-SEP-15:02 0.00 0.00 0.00
October 0.227923E+11 0.00 361.48 0.162911E+11 0.00 0.00 0.00 0.00 76975.55 01-OCT-08:52 68215.87 14-OCT-08:61 0.00 0.00 0.00
November 0.119630E+11 0.00 387.13 0.726671E+10 0.00 0.00 0.00 0.00 65080.76 09-NOV-22:53 62510.99 19-NOV-09:41 0.00 0.00 0.00
December 0.853929E+10 0.00 323.20 0.600918E+10 0.00 0.00 0.00 0.00 63189.89 05-DEC-16:01 63189.89 05-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.242799E+12 0.00 4423.30 0.153317E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.853929E+10 0.00 307.32 0.552040E+10 0.00 0.00 0.00 0.00 63189.89   59540.86   0.00 0.00 0.00
Maximum of Months 0.354845E+11 0.00 419.19 0.228854E+11 0.00 0.00 0.00 0.00 78872.53   68215.87   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.206698E+10 0.00 427.75 0.139942E+10 0.00 0.00 0.00 0.00 10652.26 17-JAN-16:02 10248.17 14-JAN-16:01 0.00 0.00 0.00
February 0.161494E+10 0.00 314.87 0.111165E+10 0.00 0.00 0.00 0.00 10480.83 13-FEB-16:02 10170.90 01-FEB-09:02 0.00 0.00 0.00
March 0.181248E+10 0.00 342.34 0.108475E+10 0.00 0.00 0.00 0.00 10225.50 15-MAR-15:01 9750.09 23-MAR-15:02 0.00 0.00 0.00
April 0.344062E+10 0.00 555.59 0.198211E+10 0.00 0.00 0.00 0.00 10326.30 24-APR-15:02 9892.17 30-APR-15:02 0.00 0.00 0.00
May 0.299429E+10 0.00 548.86 0.164239E+10 0.00 0.00 0.00 0.00 10833.32 06-MAY-15:01 9787.66 24-MAY-08:62 0.00 0.00 0.00
June 0.433381E+10 0.00 625.31 0.229069E+10 0.00 0.00 0.00 0.00 10998.94 28-JUN-15:02 9629.53 30-JUN-15:02 0.00 0.00 0.00
July 0.685807E+10 0.00 706.99 0.379083E+10 0.00 0.00 0.00 0.00 11386.71 29-JUL-18:02 10106.21 19-JUL-15:02 0.00 0.00 0.00
August 0.746865E+10 0.00 709.27 0.419165E+10 0.00 0.00 0.00 0.00 11525.49 08-AUG-08:62 10196.09 14-AUG-15:02 0.00 0.00 0.00
September 0.518679E+10 0.00 648.56 0.285366E+10 0.00 0.00 0.00 0.00 11755.09 21-SEP-15:02 9889.86 13-SEP-15:02 0.00 0.00 0.00
October 0.527552E+10 0.00 647.65 0.365729E+10 0.00 0.00 0.00 0.00 12086.74 01-OCT-08:62 10586.70 13-OCT-15:01 0.00 0.00 0.00
November 0.242908E+10 0.00 483.68 0.161821E+10 0.00 0.00 0.00 0.00 10575.20 12-NOV-09:02 10061.28 27-NOV-09:02 0.00 0.00 0.00
December 0.226423E+10 0.00 443.85 0.189412E+10 0.00 0.00 0.00 0.00 10349.10 05-DEC-09:02 10349.10 05-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.457455E+11 0.00 6454.72 0.275168E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.161494E+10 0.00 314.87 0.108475E+10 0.00 0.00 0.00 0.00 10225.50   9629.53   0.00 0.00 0.00
Maximum of Months 0.746865E+10 0.00 709.27 0.419165E+10 0.00 0.00 0.00 0.00 12086.74   10586.70   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.513647E+09 0.00 147.82 0.333529E+09 0.00 0.00 0.00 0.00 10205.24 17-JAN-16:02 9801.66 14-JAN-16:01 0.00 0.00 0.00
February 0.527902E+09 0.00 144.91 0.347030E+09 0.00 0.00 0.00 0.00 9927.93 01-FEB-09:51 9927.93 01-FEB-09:51 0.00 0.00 0.00
March 0.813781E+09 0.00 204.87 0.457313E+09 0.00 0.00 0.00 0.00 10419.20 23-MAR-15:02 9779.35 23-MAR-08:51 0.00 0.00 0.00
April 0.201059E+10 0.00 395.06 0.110526E+10 0.00 0.00 0.00 0.00 11236.06 26-APR-08:51 10393.87 30-APR-08:51 0.00 0.00 0.00
May 0.207603E+10 0.00 422.77 0.111569E+10 0.00 0.00 0.00 0.00 10963.81 03-MAY-08:51 10369.64 04-MAY-08:51 0.00 0.00 0.00
June 0.291299E+10 0.00 411.61 0.154879E+10 0.00 0.00 0.00 0.00 12333.29 30-JUN-08:51 10578.52 23-JUN-08:51 0.00 0.00 0.00
July 0.457421E+10 0.00 434.50 0.257910E+10 0.00 0.00 0.00 0.00 13359.16 19-JUL-08:51 10520.12 04-JUL-08:51 0.00 0.00 0.00
August 0.453295E+10 0.00 433.66 0.250279E+10 0.00 0.00 0.00 0.00 13436.00 19-AUG-08:51 10022.32 23-AUG-08:51 0.00 0.00 0.00
September 0.268351E+10 0.00 414.76 0.137809E+10 0.00 0.00 0.00 0.00 12484.07 10-SEP-08:51 10204.02 03-SEP-08:51 0.00 0.00 0.00
October 0.240871E+10 0.00 396.50 0.160400E+10 0.00 0.00 0.00 0.00 12182.25 01-OCT-08:52 11756.18 17-OCT-08:21 0.00 0.00 0.00
November 0.678726E+09 0.00 196.51 0.416259E+09 0.00 0.00 0.00 0.00 10084.93 12-NOV-09:02 9534.05 27-NOV-09:52 0.00 0.00 0.00
December 0.452476E+09 0.00 143.53 0.365541E+09 0.00 0.00 0.00 0.00 10524.91 05-DEC-09:41 10524.91 05-DEC-09:41 0.00 0.00 0.00
                               
Annual Sum or Average 0.241855E+11 0.00 3746.50 0.137534E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.452476E+09 0.00 143.53 0.333529E+09 0.00 0.00 0.00 0.00 9927.93   9534.05   0.00 0.00 0.00
Maximum of Months 0.457421E+10 0.00 434.50 0.257910E+10 0.00 0.00 0.00 0.00 13436.00   11756.18   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.410415E+09 0.00 318.34 0.273472E+09 0.00 0.00 0.00 0.00 3219.96 17-JAN-16:02 3040.32 14-JAN-16:01 0.00 0.00 0.00
February 0.375053E+09 0.00 240.67 0.255219E+09 0.00 0.00 0.00 0.00 3208.16 13-FEB-16:02 2977.47 03-FEB-16:01 0.00 0.00 0.00
March 0.438612E+09 0.00 266.02 0.272384E+09 0.00 0.00 0.00 0.00 3110.50 24-MAR-08:62 2842.13 07-MAR-16:02 0.00 0.00 0.00
April 0.934056E+09 0.00 489.11 0.577964E+09 0.00 0.00 0.00 0.00 3327.90 26-APR-08:62 2833.05 01-APR-18:02 0.00 0.00 0.00
May 0.844999E+09 0.00 489.80 0.496865E+09 0.00 0.00 0.00 0.00 3265.13 06-MAY-08:62 2870.47 06-MAY-15:01 0.00 0.00 0.00
June 0.127777E+10 0.00 598.29 0.729885E+09 0.00 0.00 0.00 0.00 3381.46 30-JUN-08:62 2890.77 10-JUN-15:02 0.00 0.00 0.00
July 0.190438E+10 0.00 692.56 0.109756E+10 0.00 0.00 0.00 0.00 3642.17 30-JUL-08:62 2937.69 23-JUL-18:02 0.00 0.00 0.00
August 0.195387E+10 0.00 691.38 0.111691E+10 0.00 0.00 0.00 0.00 3812.33 06-AUG-08:62 2903.00 05-AUG-15:02 0.00 0.00 0.00
September 0.143264E+10 0.00 641.75 0.822463E+09 0.00 0.00 0.00 0.00 3700.58 22-SEP-08:62 2948.58 21-SEP-15:02 0.00 0.00 0.00
October 0.127122E+10 0.00 581.95 0.872003E+09 0.00 0.00 0.00 0.00 3734.01 01-OCT-08:62 3140.86 13-OCT-15:01 0.00 0.00 0.00
November 0.549489E+09 0.00 375.39 0.352004E+09 0.00 0.00 0.00 0.00 3187.40 11-NOV-16:01 2953.06 28-NOV-16:01 0.00 0.00 0.00
December 0.467626E+09 0.00 341.71 0.381890E+09 0.00 0.00 0.00 0.00 3063.45 05-DEC-09:02 3063.45 05-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.118601E+11 0.00 5726.96 0.724862E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.375053E+09 0.00 240.67 0.255219E+09 0.00 0.00 0.00 0.00 3063.45   2833.05   0.00 0.00 0.00
Maximum of Months 0.195387E+10 0.00 692.56 0.111691E+10 0.00 0.00 0.00 0.00 3812.33   3140.86   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 65259177.77 0.00 73.89 41893494.96 0.00 0.00 0.00 0.00 3041.33 17-JAN-16:02 2906.97 14-JAN-16:01 0.00 0.00 0.00
February 97036857.53 0.00 103.30 56778708.93 0.00 0.00 0.00 0.00 3022.05 13-FEB-16:02 2846.75 03-FEB-16:01 0.00 0.00 0.00
March 0.167171E+09 0.00 146.37 89766846.89 0.00 0.00 0.00 0.00 2984.14 22-MAR-18:51 2783.92 23-MAR-15:02 0.00 0.00 0.00
April 0.498978E+09 0.00 345.08 0.254190E+09 0.00 0.00 0.00 0.00 3306.68 26-APR-21:51 2903.72 23-APR-18:11 0.00 0.00 0.00
May 0.558116E+09 0.00 388.74 0.291771E+09 0.00 0.00 0.00 0.00 3201.48 02-MAY-21:51 2783.86 24-MAY-19:11 0.00 0.00 0.00
June 0.861797E+09 0.00 401.59 0.465008E+09 0.00 0.00 0.00 0.00 3500.09 28-JUN-21:51 2815.93 04-JUN-19:31 0.00 0.00 0.00
July 0.132056E+10 0.00 425.58 0.769859E+09 0.00 0.00 0.00 0.00 3753.28 23-JUL-08:51 2805.56 18-JUL-18:02 0.00 0.00 0.00
August 0.121996E+10 0.00 422.08 0.677363E+09 0.00 0.00 0.00 0.00 3804.49 19-AUG-08:51 2796.66 05-AUG-15:02 0.00 0.00 0.00
September 0.761411E+09 0.00 411.07 0.378106E+09 0.00 0.00 0.00 0.00 3514.67 21-SEP-21:52 2773.10 30-SEP-08:61 0.00 0.00 0.00
October 0.556636E+09 0.00 332.98 0.354473E+09 0.00 0.00 0.00 0.00 3683.88 01-OCT-08:52 3019.93 14-OCT-08:61 0.00 0.00 0.00
November 0.108367E+09 0.00 142.33 57914235.35 0.00 0.00 0.00 0.00 3010.45 11-NOV-16:01 2823.48 28-NOV-16:01 0.00 0.00 0.00
December 63195266.71 0.00 69.51 51164054.65 0.00 0.00 0.00 0.00 2904.87 05-DEC-16:01 2904.87 05-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.627848E+10 0.00 3262.52 0.348829E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 63195266.71 0.00 69.51 41893494.96 0.00 0.00 0.00 0.00 2904.87   2773.10   0.00 0.00 0.00
Maximum of Months 0.132056E+10 0.00 425.58 0.769859E+09 0.00 0.00 0.00 0.00 3804.49   3019.93   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.753731E+10 0.00 583.16 0.606394E+10 0.00 0.00 0.00 0.00 14927.36 17-JAN-16:02 14168.79 14-JAN-16:01 0.00 0.00 0.00
February 0.492442E+10 0.00 455.68 0.381510E+10 0.00 0.00 0.00 0.00 15149.47 11-FEB-16:02 14056.99 01-FEB-09:02 0.00 0.00 0.00
March 0.420152E+10 0.00 437.41 0.277951E+10 0.00 0.00 0.00 0.00 14180.24 20-MAR-15:01 12931.34 18-MAR-15:01 0.00 0.00 0.00
April 0.507348E+10 0.00 563.22 0.289581E+10 0.00 0.00 0.00 0.00 14782.59 26-APR-08:62 13589.24 30-APR-15:02 0.00 0.00 0.00
May 0.313762E+10 0.00 492.16 0.150009E+10 0.00 0.00 0.00 0.00 15013.43 28-MAY-15:01 13516.32 02-MAY-15:02 0.00 0.00 0.00
June 0.428970E+10 0.00 580.40 0.190891E+10 0.00 0.00 0.00 0.00 15603.60 29-JUN-18:02 13099.75 30-JUN-15:02 0.00 0.00 0.00
July 0.706576E+10 0.00 669.15 0.333731E+10 0.00 0.00 0.00 0.00 16860.53 29-JUL-18:02 13874.64 31-JUL-15:02 0.00 0.00 0.00
August 0.900963E+10 0.00 680.25 0.469963E+10 0.00 0.00 0.00 0.00 17233.58 19-AUG-08:62 13903.85 13-AUG-15:02 0.00 0.00 0.00
September 0.870610E+10 0.00 644.22 0.520498E+10 0.00 0.00 0.00 0.00 16610.84 22-SEP-08:62 13647.68 21-SEP-15:02 0.00 0.00 0.00
October 0.101616E+11 0.00 662.58 0.767812E+10 0.00 0.00 0.00 0.00 16978.85 01-OCT-08:62 14628.50 16-OCT-08:62 0.00 0.00 0.00
November 0.766692E+10 0.00 612.41 0.593616E+10 0.00 0.00 0.00 0.00 14962.86 11-NOV-16:01 14314.23 19-NOV-09:02 0.00 0.00 0.00
December 0.818868E+10 0.00 599.27 0.719816E+10 0.00 0.00 0.00 0.00 14303.18 05-DEC-09:02 14303.18 05-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.799627E+11 0.00 6979.92 0.530177E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.313762E+10 0.00 437.41 0.150009E+10 0.00 0.00 0.00 0.00 14180.24   12931.34   0.00 0.00 0.00
Maximum of Months 0.101616E+11 0.00 680.25 0.767812E+10 0.00 0.00 0.00 0.00 17233.58   14628.50   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 691.88 507.95 183.94 1021.34 343.16 0.00 0.00 0.00
February 546.53 338.18 208.36 773.76 308.05 0.00 0.00 0.00
March 435.89 212.33 223.56 615.55 317.98 0.00 0.00 0.00
April 364.49 140.88 223.62 551.13 254.34 0.00 0.00 0.00
May 256.82 31.10 225.72 337.95 222.97 0.00 0.00 0.00
June 225.30 13.21 212.09 302.55 165.41 0.00 0.00 0.00
July 237.61 25.41 212.20 357.92 145.51 0.00 0.00 0.00
August 305.17 94.83 210.34 505.46 157.81 0.00 0.00 0.00
September 419.06 208.19 210.87 681.35 189.12 0.00 0.00 0.00
October 548.73 368.52 180.22 887.82 211.68 0.00 0.00 0.00
November 666.54 472.26 194.28 987.55 307.82 0.00 0.00 0.00
December 740.41 564.21 176.20 1097.96 344.50 0.00 0.00 0.00
                 
Annual Sum or Average 452.81 247.78 205.03 676.40 247.06 0.00 0.00 0.00
Minimum of Months 225.30 13.21 176.20 302.55 145.51 0.00 0.00 0.00
Maximum of Months 740.41 564.21 225.72 1097.96 344.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1948.30 1430.34 517.96 2835.66 1053.46 0.00 0.00 0.00
February 1539.00 952.28 586.71 2139.03 956.83 0.00 0.00 0.00
March 1227.43 597.91 629.52 1696.18 979.50 0.00 0.00 0.00
April 1026.39 396.71 629.69 1517.65 794.02 0.00 0.00 0.00
May 723.18 87.58 635.60 913.80 700.68 0.00 0.00 0.00
June 634.43 37.21 597.22 815.57 530.63 0.00 0.00 0.00
July 669.08 71.55 597.53 979.93 460.95 0.00 0.00 0.00
August 859.34 267.03 592.31 1401.37 495.94 0.00 0.00 0.00
September 1180.05 586.24 593.81 1893.49 593.93 0.00 0.00 0.00
October 1545.20 1037.72 507.48 2469.37 659.22 0.00 0.00 0.00
November 1876.94 1329.86 547.08 2739.56 952.13 0.00 0.00 0.00
December 2084.94 1588.78 496.16 3049.74 1057.58 0.00 0.00 0.00
                 
Annual Sum or Average 1275.09 697.73 577.36 1870.16 768.60 0.00 0.00 0.00
Minimum of Months 634.43 37.21 496.16 815.57 460.95 0.00 0.00 0.00
Maximum of Months 2084.94 1588.78 635.60 3049.74 1057.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2530.95 1858.09 672.86 3768.83 1395.77 0.00 0.00 0.00
February 1999.24 1237.07 762.17 2839.55 1287.28 0.00 0.00 0.00
March 1594.50 776.72 817.79 2246.82 1329.20 0.00 0.00 0.00
April 1333.34 515.34 818.00 2012.08 1079.11 0.00 0.00 0.00
May 939.45 113.77 825.68 1190.33 975.11 0.00 0.00 0.00
June 824.17 48.34 775.83 1056.64 744.58 0.00 0.00 0.00
July 869.17 92.94 776.23 1283.37 642.68 0.00 0.00 0.00
August 1116.33 346.89 769.44 1857.16 673.73 0.00 0.00 0.00
September 1532.95 761.56 771.39 2515.66 797.02 0.00 0.00 0.00
October 2007.30 1348.05 659.24 3277.19 874.31 0.00 0.00 0.00
November 2438.25 1727.56 710.69 3639.08 1264.61 0.00 0.00 0.00
December 2708.45 2063.92 644.54 4050.23 1400.68 0.00 0.00 0.00
                 
Annual Sum or Average 1656.41 906.39 750.02 2477.00 1037.37 0.00 0.00 0.00
Minimum of Months 824.17 48.34 644.54 1056.64 642.68 0.00 0.00 0.00
Maximum of Months 2708.45 2063.92 825.68 4050.23 1400.68 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 136.80 100.43 36.37 204.95 66.16 0.00 0.00 0.00
February 108.06 66.86 41.20 153.68 60.24 0.00 0.00 0.00
March 86.18 41.98 44.20 121.36 63.70 0.00 0.00 0.00
April 72.07 27.85 44.21 107.88 50.78 0.00 0.00 0.00
May 50.78 6.15 44.63 63.91 45.76 0.00 0.00 0.00
June 44.55 2.61 41.93 57.36 33.11 0.00 0.00 0.00
July 46.98 5.02 41.96 69.91 27.56 0.00 0.00 0.00
August 60.34 18.75 41.59 100.80 28.60 0.00 0.00 0.00
September 82.86 41.16 41.69 136.24 34.52 0.00 0.00 0.00
October 108.49 72.86 35.63 178.42 37.71 0.00 0.00 0.00
November 131.79 93.37 38.41 197.67 58.75 0.00 0.00 0.00
December 146.39 111.55 34.84 220.37 65.84 0.00 0.00 0.00
                 
Annual Sum or Average 89.53 48.99 40.54 134.33 47.66 0.00 0.00 0.00
Minimum of Months 44.55 2.61 34.84 57.36 27.56 0.00 0.00 0.00
Maximum of Months 146.39 111.55 44.63 220.37 66.16 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.13 49.99 49.14 126.88 133.47 0.00 0.00 0.00
February 118.40 54.72 63.67 146.02 117.90 0.00 0.00 0.00
March 135.41 59.84 75.57 171.46 120.24 0.00 0.00 0.00
April 186.62 97.02 89.60 266.69 91.84 0.00 0.00 0.00
May 183.33 84.55 98.78 257.03 81.39 0.00 0.00 0.00
June 194.16 96.95 97.21 288.77 58.22 0.00 0.00 0.00
July 205.59 109.90 95.69 322.63 48.59 0.00 0.00 0.00
August 192.92 104.46 88.46 304.85 51.34 0.00 0.00 0.00
September 165.33 88.43 76.90 251.98 62.72 0.00 0.00 0.00
October 127.00 69.58 57.41 198.36 73.28 0.00 0.00 0.00
November 114.28 59.82 54.46 151.14 116.77 0.00 0.00 0.00
December 100.52 53.75 46.77 130.76 133.21 0.00 0.00 0.00
                 
Annual Sum or Average 152.02 77.52 74.51 218.40 90.62 0.00 0.00 0.00
Minimum of Months 99.13 49.99 46.77 126.88 48.59 0.00 0.00 0.00
Maximum of Months 205.59 109.90 98.78 322.63 133.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.68 0.00 20.68 15.76 71.27 0.00 0.00 0.00
February 25.96 0.00 25.96 18.15 63.80 0.00 0.00 0.00
March 31.81 0.00 31.81 25.78 65.89 0.00 0.00 0.00
April 36.84 0.30 36.55 34.61 50.27 0.00 0.00 0.00
May 44.32 2.31 42.01 44.01 43.37 0.00 0.00 0.00
June 46.98 4.64 42.34 54.57 32.91 0.00 0.00 0.00
July 44.50 3.78 40.73 56.85 29.36 0.00 0.00 0.00
August 37.00 0.82 36.18 46.14 31.11 0.00 0.00 0.00
September 31.23 0.01 31.23 36.69 37.10 0.00 0.00 0.00
October 24.77 0.00 24.77 32.81 41.70 0.00 0.00 0.00
November 22.43 0.00 22.43 18.00 63.37 0.00 0.00 0.00
December 19.25 0.00 19.25 14.34 71.45 0.00 0.00 0.00
                 
Annual Sum or Average 32.17 0.99 31.18 33.23 50.07 0.00 0.00 0.00
Minimum of Months 19.25 0.00 19.25 14.34 29.36 0.00 0.00 0.00
Maximum of Months 46.98 4.64 42.34 56.85 71.45 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.13 49.99 49.14 132.51 130.02 0.00 0.00 0.00
February 118.40 54.72 63.67 150.10 115.58 0.00 0.00 0.00
March 135.41 59.84 75.57 174.14 118.93 0.00 0.00 0.00
April 186.62 97.02 89.60 265.92 92.81 0.00 0.00 0.00
May 183.33 84.55 98.78 253.74 83.52 0.00 0.00 0.00
June 194.16 96.95 97.21 281.79 63.27 0.00 0.00 0.00
July 205.59 109.90 95.69 314.64 55.45 0.00 0.00 0.00
August 192.92 104.46 88.46 299.28 57.93 0.00 0.00 0.00
September 165.33 88.43 76.90 250.47 66.21 0.00 0.00 0.00
October 127.00 69.58 57.41 199.52 75.66 0.00 0.00 0.00
November 114.28 59.82 54.46 155.85 114.46 0.00 0.00 0.00
December 100.52 53.75 46.77 136.48 129.72 0.00 0.00 0.00
                 
Annual Sum or Average 152.02 77.52 74.51 218.20 91.85 0.00 0.00 0.00
Minimum of Months 99.13 49.99 46.77 132.51 55.45 0.00 0.00 0.00
Maximum of Months 205.59 109.90 98.78 314.64 130.02 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 109.42 80.33 29.09 150.79 78.04 0.00 0.00 0.00
February 86.43 53.48 32.95 110.03 73.50 0.00 0.00 0.00
March 68.93 33.58 35.35 84.74 75.06 0.00 0.00 0.00
April 57.64 22.28 35.36 74.45 62.70 0.00 0.00 0.00
May 40.61 4.92 35.70 38.88 57.23 0.00 0.00 0.00
June 35.63 2.09 33.54 33.22 45.44 0.00 0.00 0.00
July 37.58 4.02 33.56 43.23 39.96 0.00 0.00 0.00
August 48.26 15.00 33.26 68.14 42.02 0.00 0.00 0.00
September 66.27 32.92 33.35 96.90 48.68 0.00 0.00 0.00
October 86.78 58.28 28.50 129.86 52.04 0.00 0.00 0.00
November 105.41 74.68 30.72 144.90 71.44 0.00 0.00 0.00
December 117.09 89.23 27.86 162.80 77.82 0.00 0.00 0.00
                 
Annual Sum or Average 71.61 39.18 32.42 94.78 60.25 0.00 0.00 0.00
Minimum of Months 35.63 2.09 27.86 33.22 39.96 0.00 0.00 0.00
Maximum of Months 117.09 89.23 35.70 162.80 78.04 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.54 0.00 16.54 12.85 57.64 0.00 0.00 0.00
February 20.77 0.00 20.77 14.96 51.38 0.00 0.00 0.00
March 25.45 0.00 25.45 21.31 52.90 0.00 0.00 0.00
April 29.48 0.24 29.24 30.50 38.60 0.00 0.00 0.00
May 35.46 1.85 33.61 38.29 33.58 0.00 0.00 0.00
June 37.59 3.71 33.88 47.71 24.67 0.00 0.00 0.00
July 35.61 3.02 32.58 50.15 21.16 0.00 0.00 0.00
August 29.60 0.66 28.95 41.08 22.10 0.00 0.00 0.00
September 24.99 0.00 24.98 32.16 27.13 0.00 0.00 0.00
October 19.82 0.00 19.82 28.09 31.58 0.00 0.00 0.00
November 17.95 0.00 17.95 15.21 50.13 0.00 0.00 0.00
December 15.40 0.00 15.40 11.87 57.36 0.00 0.00 0.00
                 
Annual Sum or Average 25.74 0.79 24.95 28.76 38.96 0.00 0.00 0.00
Minimum of Months 15.40 0.00 15.40 11.87 21.16 0.00 0.00 0.00
Maximum of Months 37.59 3.71 33.88 50.15 57.64 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 104.03 55.59 48.45 129.50 126.73 0.00 0.00 0.00
February 109.78 50.23 59.54 128.11 112.85 0.00 0.00 0.00
March 133.98 59.84 74.14 165.20 114.97 0.00 0.00 0.00
April 170.78 85.69 85.09 239.35 88.05 0.00 0.00 0.00
May 160.86 67.04 93.82 220.40 78.82 0.00 0.00 0.00
June 160.04 69.48 90.57 235.35 57.55 0.00 0.00 0.00
July 181.24 90.04 91.20 284.89 48.44 0.00 0.00 0.00
August 179.13 95.20 83.93 283.71 50.06 0.00 0.00 0.00
September 130.78 60.15 70.63 196.31 61.26 0.00 0.00 0.00
October 115.26 59.16 56.10 176.72 69.85 0.00 0.00 0.00
November 104.83 53.07 51.76 131.74 112.18 0.00 0.00 0.00
December 100.77 56.17 44.61 125.13 126.63 0.00 0.00 0.00
                 
Annual Sum or Average 137.81 66.94 70.87 193.48 87.16 0.00 0.00 0.00
Minimum of Months 100.77 50.23 44.61 125.13 48.44 0.00 0.00 0.00
Maximum of Months 181.24 95.20 93.82 284.89 126.73 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 136.80 100.43 36.37 204.12 65.97 0.00 0.00 0.00
February 108.06 66.86 41.20 153.24 59.65 0.00 0.00 0.00
March 86.18 41.98 44.20 120.55 63.18 0.00 0.00 0.00
April 72.07 27.85 44.21 107.08 49.87 0.00 0.00 0.00
May 50.78 6.15 44.63 63.37 44.80 0.00 0.00 0.00
June 44.55 2.61 41.93 57.08 32.06 0.00 0.00 0.00
July 46.98 5.02 41.96 69.34 26.59 0.00 0.00 0.00
August 60.34 18.75 41.59 100.13 27.73 0.00 0.00 0.00
September 82.86 41.16 41.69 136.19 33.41 0.00 0.00 0.00
October 108.49 72.86 35.63 178.07 37.14 0.00 0.00 0.00
November 131.79 93.37 38.41 197.25 58.18 0.00 0.00 0.00
December 146.39 111.55 34.84 219.72 65.46 0.00 0.00 0.00
                 
Annual Sum or Average 89.53 48.99 40.54 133.79 46.94 0.00 0.00 0.00
Minimum of Months 44.55 2.61 34.84 57.08 26.59 0.00 0.00 0.00
Maximum of Months 146.39 111.55 44.63 219.72 65.97 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.68 0.00 20.68 14.95 70.86 0.00 0.00 0.00
February 25.96 0.00 25.96 17.58 62.85 0.00 0.00 0.00
March 31.81 0.00 31.81 24.97 65.16 0.00 0.00 0.00
April 36.84 0.30 36.55 34.10 48.80 0.00 0.00 0.00
May 44.32 2.31 42.01 44.05 42.09 0.00 0.00 0.00
June 46.98 4.64 42.34 55.40 31.09 0.00 0.00 0.00
July 44.50 3.78 40.73 57.01 27.42 0.00 0.00 0.00
August 37.00 0.82 36.18 45.58 29.16 0.00 0.00 0.00
September 31.23 0.01 31.23 36.69 34.86 0.00 0.00 0.00
October 24.77 0.00 24.77 32.14 40.47 0.00 0.00 0.00
November 22.43 0.00 22.43 17.42 62.17 0.00 0.00 0.00
December 19.25 0.00 19.25 13.52 70.72 0.00 0.00 0.00
                 
Annual Sum or Average 32.17 0.99 31.18 32.87 48.74 0.00 0.00 0.00
Minimum of Months 19.25 0.00 19.25 13.52 27.42 0.00 0.00 0.00
Maximum of Months 46.98 4.64 42.34 57.01 70.86 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 104.03 55.59 48.45 134.69 122.48 0.00 0.00 0.00
February 109.78 50.23 59.54 132.15 109.94 0.00 0.00 0.00
March 133.98 59.84 74.14 168.10 113.35 0.00 0.00 0.00
April 170.78 85.69 85.09 239.97 88.39 0.00 0.00 0.00
May 160.86 67.04 93.82 218.56 80.44 0.00 0.00 0.00
June 160.04 69.48 90.57 230.88 61.44 0.00 0.00 0.00
July 181.24 90.04 91.20 278.72 53.94 0.00 0.00 0.00
August 179.13 95.20 83.93 278.80 55.08 0.00 0.00 0.00
September 130.78 60.15 70.63 195.85 63.40 0.00 0.00 0.00
October 115.26 59.16 56.10 177.88 71.48 0.00 0.00 0.00
November 104.83 53.07 51.76 136.19 108.64 0.00 0.00 0.00
December 100.77 56.17 44.61 130.24 122.20 0.00 0.00 0.00
                 
Annual Sum or Average 137.81 66.94 70.87 193.93 87.46 0.00 0.00 0.00
Minimum of Months 100.77 50.23 44.61 130.24 53.94 0.00 0.00 0.00
Maximum of Months 181.24 95.20 93.82 278.80 122.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.19 0.00 26.19 18.74 96.96 0.00 0.00 0.00
February 32.87 0.00 32.87 22.34 86.77 0.00 0.00 0.00
March 40.29 0.00 40.29 33.34 87.25 0.00 0.00 0.00
April 46.66 0.38 46.28 47.60 65.57 0.00 0.00 0.00
May 56.13 2.93 53.20 60.48 56.88 0.00 0.00 0.00
June 59.50 5.88 53.62 75.90 42.13 0.00 0.00 0.00
July 56.36 4.78 51.58 78.52 37.31 0.00 0.00 0.00
August 46.86 1.04 45.82 62.86 40.26 0.00 0.00 0.00
September 39.55 0.01 39.55 48.71 49.24 0.00 0.00 0.00
October 31.37 0.00 31.37 41.32 58.08 0.00 0.00 0.00
November 28.41 0.00 28.41 21.59 87.41 0.00 0.00 0.00
December 24.38 0.00 24.38 16.45 98.63 0.00 0.00 0.00
                 
Annual Sum or Average 40.75 1.26 39.49 44.12 67.11 0.00 0.00 0.00
Minimum of Months 24.38 0.00 24.38 16.45 37.31 0.00 0.00 0.00
Maximum of Months 59.50 5.88 53.62 78.52 98.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.65 0.00 9.65 6.91 35.74 0.00 0.00 0.00
February 12.12 0.00 12.12 8.24 31.99 0.00 0.00 0.00
March 14.85 0.00 14.85 12.29 32.16 0.00 0.00 0.00
April 17.20 0.14 17.06 17.55 24.17 0.00 0.00 0.00
May 20.69 1.08 19.61 22.29 20.97 0.00 0.00 0.00
June 21.93 2.17 19.77 27.98 15.53 0.00 0.00 0.00
July 20.78 1.76 19.01 28.95 13.75 0.00 0.00 0.00
August 17.27 0.38 16.89 23.17 14.84 0.00 0.00 0.00
September 14.58 0.00 14.58 17.96 18.15 0.00 0.00 0.00
October 11.57 0.00 11.57 15.23 21.41 0.00 0.00 0.00
November 10.47 0.00 10.47 7.96 32.22 0.00 0.00 0.00
December 8.99 0.00 8.99 6.07 36.36 0.00 0.00 0.00
                 
Annual Sum or Average 15.02 0.46 14.56 16.26 24.74 0.00 0.00 0.00
Minimum of Months 8.99 0.00 8.99 6.07 13.75 0.00 0.00 0.00
Maximum of Months 21.93 2.17 19.77 28.95 36.36 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 63.83 46.86 16.97 96.60 32.32 0.00 0.00 0.00
February 50.42 31.20 19.22 72.48 29.69 0.00 0.00 0.00
March 40.21 19.59 20.62 57.59 30.88 0.00 0.00 0.00
April 33.63 13.00 20.63 51.66 24.75 0.00 0.00 0.00
May 23.69 2.87 20.82 30.82 22.62 0.00 0.00 0.00
June 20.79 1.22 19.57 27.59 16.89 0.00 0.00 0.00
July 21.92 2.34 19.58 33.15 14.69 0.00 0.00 0.00
August 28.15 8.75 19.41 47.43 15.46 0.00 0.00 0.00
September 38.66 19.21 19.45 64.18 18.05 0.00 0.00 0.00
October 50.62 34.00 16.63 83.42 20.17 0.00 0.00 0.00
November 61.49 43.57 17.92 92.94 29.32 0.00 0.00 0.00
December 68.31 52.05 16.25 103.56 32.55 0.00 0.00 0.00
                 
Annual Sum or Average 41.77 22.86 18.92 63.43 23.92 0.00 0.00 0.00
Minimum of Months 20.79 1.22 16.25 27.59 14.69 0.00 0.00 0.00
Maximum of Months 68.31 52.05 20.82 103.56 32.55 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 173.25 127.19 46.06 262.18 87.73 0.00 0.00 0.00
February 136.85 84.68 52.17 196.74 80.59 0.00 0.00 0.00
March 109.15 53.17 55.98 156.32 83.81 0.00 0.00 0.00
April 91.27 35.28 55.99 140.21 67.18 0.00 0.00 0.00
May 64.31 7.79 56.52 83.65 61.40 0.00 0.00 0.00
June 56.42 3.31 53.11 74.88 45.84 0.00 0.00 0.00
July 59.50 6.36 53.13 89.98 39.86 0.00 0.00 0.00
August 76.41 23.74 52.67 128.74 41.95 0.00 0.00 0.00
September 104.93 52.13 52.80 174.20 48.99 0.00 0.00 0.00
October 137.40 92.28 45.13 226.42 54.73 0.00 0.00 0.00
November 166.90 118.25 48.65 252.26 79.59 0.00 0.00 0.00
December 185.40 141.28 44.12 281.08 88.35 0.00 0.00 0.00
                 
Annual Sum or Average 113.38 62.04 51.34 172.15 64.92 0.00 0.00 0.00
Minimum of Months 56.42 3.31 44.12 74.88 39.86 0.00 0.00 0.00
Maximum of Months 185.40 141.28 56.52 281.08 88.35 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 136.80 100.43 36.37 204.08 65.31 0.00 0.00 0.00
February 108.06 66.86 41.20 152.55 59.41 0.00 0.00 0.00
March 86.18 41.98 44.20 120.29 63.21 0.00 0.00 0.00
April 72.07 27.85 44.21 106.50 50.44 0.00 0.00 0.00
May 50.78 6.15 44.63 62.76 45.48 0.00 0.00 0.00
June 44.55 2.61 41.93 56.32 32.91 0.00 0.00 0.00
July 46.98 5.02 41.96 68.86 27.33 0.00 0.00 0.00
August 60.34 18.75 41.59 99.60 28.29 0.00 0.00 0.00
September 82.86 41.16 41.69 134.94 34.06 0.00 0.00 0.00
October 108.49 72.86 35.63 177.30 36.99 0.00 0.00 0.00
November 131.79 93.37 38.41 196.57 57.87 0.00 0.00 0.00
December 146.39 111.55 34.84 219.42 64.80 0.00 0.00 0.00
                 
Annual Sum or Average 89.53 48.99 40.54 133.21 47.11 0.00 0.00 0.00
Minimum of Months 44.55 2.61 34.84 56.32 27.33 0.00 0.00 0.00
Maximum of Months 146.39 111.55 44.63 219.42 65.31 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.13 49.99 49.14 125.72 131.32 0.00 0.00 0.00
February 118.40 54.72 63.67 144.55 115.95 0.00 0.00 0.00
March 135.41 59.84 75.57 169.25 118.98 0.00 0.00 0.00
April 186.62 97.02 89.60 263.05 91.03 0.00 0.00 0.00
May 183.33 84.55 98.78 253.31 80.67 0.00 0.00 0.00
June 194.16 96.95 97.21 284.71 57.69 0.00 0.00 0.00
July 205.59 109.90 95.69 318.82 48.00 0.00 0.00 0.00
August 192.92 104.46 88.46 301.31 50.65 0.00 0.00 0.00
September 165.33 88.43 76.90 249.00 61.76 0.00 0.00 0.00
October 127.00 69.58 57.41 196.70 71.71 0.00 0.00 0.00
November 114.28 59.82 54.46 149.81 114.66 0.00 0.00 0.00
December 100.52 53.75 46.77 129.90 130.66 0.00 0.00 0.00
                 
Annual Sum or Average 152.02 77.52 74.51 215.86 89.29 0.00 0.00 0.00
Minimum of Months 99.13 49.99 46.77 125.72 48.00 0.00 0.00 0.00
Maximum of Months 205.59 109.90 98.78 318.82 131.32 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.68 0.00 20.68 16.13 69.80 0.00 0.00 0.00
February 25.96 0.00 25.96 18.39 62.59 0.00 0.00 0.00
March 31.81 0.00 31.81 25.55 65.28 0.00 0.00 0.00
April 36.84 0.30 36.55 33.70 50.33 0.00 0.00 0.00
May 44.32 2.31 42.01 42.83 43.45 0.00 0.00 0.00
June 46.98 4.64 42.34 52.88 33.53 0.00 0.00 0.00
July 44.50 3.78 40.73 55.26 30.14 0.00 0.00 0.00
August 37.00 0.82 36.18 45.10 31.78 0.00 0.00 0.00
September 31.23 0.01 31.23 36.15 37.04 0.00 0.00 0.00
October 24.77 0.00 24.77 32.93 40.83 0.00 0.00 0.00
November 22.43 0.00 22.43 18.40 61.94 0.00 0.00 0.00
December 19.25 0.00 19.25 14.94 69.66 0.00 0.00 0.00
                 
Annual Sum or Average 32.17 0.99 31.18 32.78 49.64 0.00 0.00 0.00
Minimum of Months 19.25 0.00 19.25 14.94 30.14 0.00 0.00 0.00
Maximum of Months 46.98 4.64 42.34 55.26 69.80 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.13 49.99 49.14 132.19 127.24 0.00 0.00 0.00
February 118.40 54.72 63.67 149.22 113.28 0.00 0.00 0.00
March 135.41 59.84 75.57 172.11 117.66 0.00 0.00 0.00
April 186.62 97.02 89.60 261.83 92.61 0.00 0.00 0.00
May 183.33 84.55 98.78 249.40 83.49 0.00 0.00 0.00
June 194.16 96.95 97.21 276.57 64.24 0.00 0.00 0.00
July 205.59 109.90 95.69 309.60 56.71 0.00 0.00 0.00
August 192.92 104.46 88.46 294.92 58.85 0.00 0.00 0.00
September 165.33 88.43 76.90 247.33 65.82 0.00 0.00 0.00
October 127.00 69.58 57.41 198.27 74.00 0.00 0.00 0.00
November 114.28 59.82 54.46 155.33 111.75 0.00 0.00 0.00
December 100.52 53.75 46.77 136.64 126.41 0.00 0.00 0.00
                 
Annual Sum or Average 152.02 77.52 74.51 215.61 90.90 0.00 0.00 0.00
Minimum of Months 99.13 49.99 46.77 132.19 56.71 0.00 0.00 0.00
Maximum of Months 205.59 109.90 98.78 309.60 127.24 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 200.63 147.29 53.34 294.61 100.00 0.00 0.00 0.00
February 158.48 98.06 60.42 220.30 90.18 0.00 0.00 0.00
March 126.40 61.57 64.83 174.15 94.55 0.00 0.00 0.00
April 105.69 40.85 64.84 156.62 72.92 0.00 0.00 0.00
May 74.47 9.02 65.45 94.10 64.70 0.00 0.00 0.00
June 65.33 3.83 61.50 85.88 45.56 0.00 0.00 0.00
July 68.90 7.37 61.53 104.70 37.07 0.00 0.00 0.00
August 88.49 27.50 60.99 148.47 39.08 0.00 0.00 0.00
September 121.52 60.37 61.15 198.30 48.77 0.00 0.00 0.00
October 159.12 106.86 52.26 258.66 54.83 0.00 0.00 0.00
November 193.28 136.94 56.34 284.59 87.94 0.00 0.00 0.00
December 214.70 163.60 51.09 317.01 99.23 0.00 0.00 0.00
                 
Annual Sum or Average 131.30 71.85 59.45 194.72 69.46 0.00 0.00 0.00
Minimum of Months 65.33 3.83 51.09 85.88 37.07 0.00 0.00 0.00
Maximum of Months 214.70 163.60 65.45 317.01 100.00 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 144.74 0.00 144.74 80.25 608.70 0.00 0.00 0.00
February 181.69 0.00 181.69 93.51 561.16 0.00 0.00 0.00
March 222.66 0.00 222.66 143.21 567.69 0.00 0.00 0.00
April 257.88 2.08 255.81 213.55 424.39 0.00 0.00 0.00
May 310.23 16.18 294.05 272.16 367.06 0.00 0.00 0.00
June 328.85 32.49 296.36 358.22 273.78 0.00 0.00 0.00
July 311.50 26.43 285.07 384.49 235.66 0.00 0.00 0.00
August 258.99 5.75 253.24 308.14 253.26 0.00 0.00 0.00
September 218.62 0.04 218.58 235.41 311.94 0.00 0.00 0.00
October 173.40 0.00 173.40 205.85 358.76 0.00 0.00 0.00
November 157.00 0.00 157.00 96.36 543.53 0.00 0.00 0.00
December 134.74 0.00 134.74 71.54 609.76 0.00 0.00 0.00
                 
Annual Sum or Average 225.21 6.95 218.26 205.92 425.62 0.00 0.00 0.00
Minimum of Months 134.74 0.00 134.74 71.54 235.66 0.00 0.00 0.00
Maximum of Months 328.85 32.49 296.36 384.49 609.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 144.74 0.00 144.74 72.41 630.15 0.00 0.00 0.00
February 181.69 0.00 181.69 84.48 582.32 0.00 0.00 0.00
March 222.66 0.00 222.66 132.25 587.40 0.00 0.00 0.00
April 257.88 2.08 255.81 200.77 438.56 0.00 0.00 0.00
May 310.23 16.18 294.05 256.99 378.46 0.00 0.00 0.00
June 328.85 32.49 296.36 344.34 282.96 0.00 0.00 0.00
July 311.50 26.43 285.07 372.33 243.61 0.00 0.00 0.00
August 258.99 5.75 253.24 297.08 262.27 0.00 0.00 0.00
September 218.62 0.04 218.58 225.11 323.88 0.00 0.00 0.00
October 173.40 0.00 173.40 196.93 371.94 0.00 0.00 0.00
November 157.00 0.00 157.00 87.93 562.48 0.00 0.00 0.00
December 134.74 0.00 134.74 64.07 630.75 0.00 0.00 0.00
                 
Annual Sum or Average 225.21 6.95 218.26 195.24 440.50 0.00 0.00 0.00
Minimum of Months 134.74 0.00 134.74 64.07 243.61 0.00 0.00 0.00
Maximum of Months 328.85 32.49 296.36 372.33 630.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.68 0.00 20.68 19.00 74.97 0.00 0.00 0.00
February 25.96 0.00 25.96 21.25 70.69 0.00 0.00 0.00
March 31.81 0.00 31.81 30.10 72.64 0.00 0.00 0.00
April 36.84 0.30 36.55 44.12 54.88 0.00 0.00 0.00
May 44.32 2.31 42.01 55.68 49.03 0.00 0.00 0.00
June 46.98 4.64 42.34 70.22 36.63 0.00 0.00 0.00
July 44.50 3.78 40.73 74.83 31.38 0.00 0.00 0.00
August 37.00 0.82 36.18 62.12 33.00 0.00 0.00 0.00
September 31.23 0.01 31.23 48.33 37.98 0.00 0.00 0.00
October 24.77 0.00 24.77 42.43 43.44 0.00 0.00 0.00
November 22.43 0.00 22.43 22.22 66.54 0.00 0.00 0.00
December 19.25 0.00 19.25 17.66 75.12 0.00 0.00 0.00
                 
Annual Sum or Average 32.17 0.99 31.18 42.46 53.77 0.00 0.00 0.00
Minimum of Months 19.25 0.00 19.25 17.66 31.38 0.00 0.00 0.00
Maximum of Months 46.98 4.64 42.34 74.83 75.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 208.05 111.16 96.89 289.90 263.75 0.00 0.00 0.00
February 219.54 100.46 119.08 280.33 251.55 0.00 0.00 0.00
March 267.94 119.67 148.26 358.57 257.15 0.00 0.00 0.00
April 341.54 171.37 170.17 520.58 200.42 0.00 0.00 0.00
May 321.70 134.06 187.64 480.40 185.48 0.00 0.00 0.00
June 320.07 138.95 181.12 516.63 141.44 0.00 0.00 0.00
July 362.45 180.07 182.38 624.15 120.86 0.00 0.00 0.00
August 358.23 190.39 167.84 621.48 124.48 0.00 0.00 0.00
September 261.54 120.30 141.24 439.03 140.75 0.00 0.00 0.00
October 230.50 118.31 112.19 398.15 156.62 0.00 0.00 0.00
November 209.64 106.13 103.51 293.88 236.27 0.00 0.00 0.00
December 201.53 112.32 89.21 280.16 263.89 0.00 0.00 0.00
                 
Annual Sum or Average 275.60 133.87 141.73 426.27 194.93 0.00 0.00 0.00
Minimum of Months 201.53 100.46 89.21 280.16 120.86 0.00 0.00 0.00
Maximum of Months 362.45 190.39 187.64 624.15 263.89 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 136.80 100.43 36.37 214.71 69.62 0.00 0.00 0.00
February 108.06 66.86 41.20 161.09 67.24 0.00 0.00 0.00
March 86.18 41.98 44.20 128.69 70.73 0.00 0.00 0.00
April 72.07 27.85 44.21 118.02 56.02 0.00 0.00 0.00
May 50.78 6.15 44.63 73.35 52.06 0.00 0.00 0.00
June 44.55 2.61 41.93 69.08 38.94 0.00 0.00 0.00
July 46.98 5.02 41.96 83.66 32.73 0.00 0.00 0.00
August 60.34 18.75 41.59 114.48 33.86 0.00 0.00 0.00
September 82.86 41.16 41.69 148.82 38.01 0.00 0.00 0.00
October 108.49 72.86 35.63 190.84 41.98 0.00 0.00 0.00
November 131.79 93.37 38.41 207.60 62.41 0.00 0.00 0.00
December 146.39 111.55 34.84 230.21 69.37 0.00 0.00 0.00
                 
Annual Sum or Average 89.53 48.99 40.54 145.01 52.67 0.00 0.00 0.00
Minimum of Months 44.55 2.61 34.84 69.08 32.73 0.00 0.00 0.00
Maximum of Months 146.39 111.55 44.63 230.21 70.73 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.19 0.00 26.19 17.12 97.10 0.00 0.00 0.00
February 32.87 0.00 32.87 20.70 86.62 0.00 0.00 0.00
March 40.29 0.00 40.29 30.80 88.22 0.00 0.00 0.00
April 46.66 0.38 46.28 44.17 66.46 0.00 0.00 0.00
May 56.13 2.93 53.20 57.14 57.38 0.00 0.00 0.00
June 59.50 5.88 53.62 71.79 43.01 0.00 0.00 0.00
July 56.36 4.78 51.58 74.56 38.04 0.00 0.00 0.00
August 46.86 1.04 45.82 59.32 41.10 0.00 0.00 0.00
September 39.55 0.01 39.55 45.91 49.77 0.00 0.00 0.00
October 31.37 0.00 31.37 39.41 57.94 0.00 0.00 0.00
November 28.41 0.00 28.41 20.31 86.32 0.00 0.00 0.00
December 24.38 0.00 24.38 15.31 97.37 0.00 0.00 0.00
                 
Annual Sum or Average 40.75 1.26 39.49 41.50 67.35 0.00 0.00 0.00
Minimum of Months 24.38 0.00 24.38 15.31 38.04 0.00 0.00 0.00
Maximum of Months 59.50 5.88 53.62 74.56 97.37 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.43 0.00 23.43 15.32 86.87 0.00 0.00 0.00
February 29.41 0.00 29.41 18.52 77.50 0.00 0.00 0.00
March 36.04 0.00 36.04 27.56 78.93 0.00 0.00 0.00
April 41.74 0.34 41.41 39.52 59.46 0.00 0.00 0.00
May 50.22 2.62 47.60 51.12 51.34 0.00 0.00 0.00
June 53.23 5.26 47.97 64.23 38.48 0.00 0.00 0.00
July 50.42 4.28 46.15 66.70 34.04 0.00 0.00 0.00
August 41.92 0.93 40.99 53.08 36.77 0.00 0.00 0.00
September 35.39 0.01 35.38 41.08 44.53 0.00 0.00 0.00
October 28.07 0.00 28.07 35.26 51.84 0.00 0.00 0.00
November 25.41 0.00 25.41 18.17 77.23 0.00 0.00 0.00
December 21.81 0.00 21.81 13.69 87.10 0.00 0.00 0.00
                 
Annual Sum or Average 36.46 1.13 35.33 37.13 60.26 0.00 0.00 0.00
Minimum of Months 21.81 0.00 21.81 13.69 34.04 0.00 0.00 0.00
Maximum of Months 53.23 5.26 47.97 66.70 87.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 510.71 374.93 135.77 763.75 259.13 0.00 0.00 0.00
February 403.42 249.62 153.80 570.52 237.76 0.00 0.00 0.00
March 321.75 156.73 165.02 449.99 250.57 0.00 0.00 0.00
April 269.05 103.99 165.06 401.05 201.50 0.00 0.00 0.00
May 189.57 22.96 166.61 235.94 183.55 0.00 0.00 0.00
June 166.31 9.75 156.55 209.22 138.81 0.00 0.00 0.00
July 175.39 18.75 156.63 253.69 120.67 0.00 0.00 0.00
August 225.26 70.00 155.26 367.68 126.83 0.00 0.00 0.00
September 309.33 153.67 155.66 502.58 146.33 0.00 0.00 0.00
October 405.04 272.02 133.03 658.08 161.50 0.00 0.00 0.00
November 492.00 348.59 143.41 735.51 232.21 0.00 0.00 0.00
December 546.52 416.47 130.06 820.75 257.56 0.00 0.00 0.00
                 
Annual Sum or Average 334.24 182.90 151.34 497.18 192.81 0.00 0.00 0.00
Minimum of Months 166.31 9.75 130.06 209.22 120.67 0.00 0.00 0.00
Maximum of Months 546.52 416.47 166.61 820.75 259.13 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.185314E+10 0.136048E+10 0.492663E+09 0.273556E+10 0.919112E+09
February 0.132217E+10 0.818116E+09 0.504052E+09 0.187187E+10 0.745236E+09
March 0.116748E+10 0.568705E+09 0.598776E+09 0.164869E+10 0.851687E+09
April 0.944769E+09 0.365158E+09 0.579611E+09 0.142852E+10 0.659237E+09
May 0.687861E+09 83301651.90 0.604559E+09 0.905167E+09 0.597207E+09
June 0.583982E+09 34251187.10 0.549731E+09 0.784202E+09 0.428736E+09
July 0.636401E+09 68053370.08 0.568348E+09 0.958664E+09 0.389723E+09
August 0.817369E+09 0.253989E+09 0.563379E+09 0.135382E+10 0.422674E+09
September 0.108621E+10 0.539619E+09 0.546586E+09 0.176606E+10 0.490195E+09
October 0.146973E+10 0.987033E+09 0.482692E+09 0.237794E+10 0.566976E+09
November 0.172768E+10 0.122410E+10 0.503575E+09 0.255973E+10 0.797858E+09
December 0.198311E+10 0.151118E+10 0.471925E+09 0.294077E+10 0.922702E+09
           
Annual Sum or Average 0.142799E+11 0.781399E+10 0.646590E+10 0.213310E+11 0.779134E+10
Minimum of Months 0.583982E+09 34251187.10 0.471925E+09 0.784202E+09 0.389723E+09
Maximum of Months 0.198311E+10 0.151118E+10 0.604559E+09 0.294077E+10 0.922702E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.521833E+10 0.383102E+10 0.138731E+10 0.759503E+10 0.282159E+10
February 0.372314E+10 0.230376E+10 0.141938E+10 0.517473E+10 0.231476E+10
March 0.328755E+10 0.160144E+10 0.168611E+10 0.454304E+10 0.262349E+10
April 0.266041E+10 0.102826E+10 0.163215E+10 0.393374E+10 0.205809E+10
May 0.193697E+10 0.234572E+09 0.170240E+10 0.244752E+10 0.187671E+10
June 0.164445E+10 96449084.55 0.154801E+10 0.211396E+10 0.137540E+10
July 0.179206E+10 0.191634E+09 0.160043E+10 0.262464E+10 0.123461E+10
August 0.230166E+10 0.715217E+09 0.158644E+10 0.375343E+10 0.132832E+10
September 0.305868E+10 0.151953E+10 0.153915E+10 0.490793E+10 0.153946E+10
October 0.413865E+10 0.277942E+10 0.135923E+10 0.661395E+10 0.176566E+10
November 0.486503E+10 0.344700E+10 0.141803E+10 0.710095E+10 0.246792E+10
December 0.558430E+10 0.425539E+10 0.132891E+10 0.816841E+10 0.283261E+10
           
Annual Sum or Average 0.402112E+11 0.220037E+11 0.182075E+11 0.589773E+11 0.242386E+11
Minimum of Months 0.164445E+10 96449084.55 0.132891E+10 0.211396E+10 0.123461E+10
Maximum of Months 0.558430E+10 0.425539E+10 0.170240E+10 0.816841E+10 0.283261E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.677891E+10 0.497672E+10 0.180219E+10 0.100944E+11 0.373843E+10
February 0.483657E+10 0.299272E+10 0.184385E+10 0.686944E+10 0.311419E+10
March 0.427071E+10 0.208036E+10 0.219036E+10 0.601789E+10 0.356013E+10
April 0.345602E+10 0.133577E+10 0.212025E+10 0.521532E+10 0.279706E+10
May 0.251623E+10 0.304722E+09 0.221151E+10 0.318818E+10 0.261172E+10
June 0.213624E+10 0.125293E+09 0.201095E+10 0.273880E+10 0.192996E+10
July 0.232799E+10 0.248943E+09 0.207905E+10 0.343739E+10 0.172135E+10
August 0.298998E+10 0.929108E+09 0.206087E+10 0.497422E+10 0.180452E+10
September 0.397340E+10 0.197396E+10 0.199944E+10 0.652059E+10 0.206588E+10
October 0.537634E+10 0.361063E+10 0.176572E+10 0.877761E+10 0.234175E+10
November 0.631995E+10 0.447785E+10 0.184211E+10 0.943251E+10 0.327788E+10
December 0.725432E+10 0.552799E+10 0.172633E+10 0.108481E+11 0.375159E+10
           
Annual Sum or Average 0.522367E+11 0.285840E+11 0.236526E+11 0.781145E+11 0.327145E+11
Minimum of Months 0.213624E+10 0.125293E+09 0.172633E+10 0.273880E+10 0.172135E+10
Maximum of Months 0.725432E+10 0.552799E+10 0.221151E+10 0.108481E+11 0.375159E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.366399E+09 0.268990E+09 97408702.42 0.548939E+09 0.177210E+09
February 0.261416E+09 0.161756E+09 99660556.79 0.371787E+09 0.145733E+09
March 0.230832E+09 0.112443E+09 0.118389E+09 0.325052E+09 0.170608E+09
April 0.186798E+09 72197917.93 0.114600E+09 0.279637E+09 0.131625E+09
May 0.136003E+09 16470167.27 0.119533E+09 0.171185E+09 0.122556E+09
June 0.115465E+09 6772047.95 0.108693E+09 0.148678E+09 85810327.27
July 0.125829E+09 13455320.07 0.112374E+09 0.187244E+09 73818499.54
August 0.161609E+09 50218052.04 0.111391E+09 0.269976E+09 76589819.33
September 0.214763E+09 0.106692E+09 0.108071E+09 0.353125E+09 89479612.62
October 0.290591E+09 0.195153E+09 95437466.31 0.477871E+09 0.101016E+09
November 0.341593E+09 0.242027E+09 99566205.17 0.512360E+09 0.152291E+09
December 0.392095E+09 0.298787E+09 93308334.56 0.590227E+09 0.176347E+09
           
Annual Sum or Average 0.282339E+10 0.154496E+10 0.127843E+10 0.423608E+10 0.150308E+10
Minimum of Months 0.115465E+09 6772047.95 93308334.56 0.148678E+09 73818499.54
Maximum of Months 0.392095E+09 0.298787E+09 0.119533E+09 0.590227E+09 0.177210E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.265521E+09 0.133901E+09 0.131620E+09 0.339833E+09 0.357489E+09
February 0.286426E+09 0.132386E+09 0.154039E+09 0.353256E+09 0.285223E+09
March 0.362688E+09 0.160278E+09 0.202410E+09 0.459233E+09 0.322043E+09
April 0.483730E+09 0.251482E+09 0.232247E+09 0.691273E+09 0.238047E+09
May 0.491022E+09 0.226458E+09 0.264564E+09 0.688434E+09 0.218000E+09
June 0.503264E+09 0.251292E+09 0.251972E+09 0.748500E+09 0.150918E+09
July 0.550654E+09 0.294353E+09 0.256300E+09 0.864140E+09 0.130132E+09
August 0.516705E+09 0.279782E+09 0.236923E+09 0.816522E+09 0.137496E+09
September 0.428535E+09 0.229221E+09 0.199314E+09 0.653121E+09 0.162570E+09
October 0.340146E+09 0.186368E+09 0.153778E+09 0.531293E+09 0.196280E+09
November 0.296219E+09 0.155051E+09 0.141168E+09 0.391760E+09 0.302663E+09
December 0.269240E+09 0.143959E+09 0.125281E+09 0.350235E+09 0.356794E+09
           
Annual Sum or Average 0.479415E+10 0.244453E+10 0.234962E+10 0.688760E+10 0.285766E+10
Minimum of Months 0.265521E+09 0.132386E+09 0.125281E+09 0.339833E+09 0.130132E+09
Maximum of Months 0.550654E+09 0.294353E+09 0.264564E+09 0.864140E+09 0.357489E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 55383852.68 0.00 55383852.68 42198579.58 0.190894E+09
February 62793579.01 0.00 62793579.01 43898697.48 0.154336E+09
March 85200912.64 780.17 85200132.47 69061548.72 0.176487E+09
April 95493362.34 768414.00 94724948.34 89715068.81 0.130294E+09
May 0.118708E+09 6190456.55 0.112517E+09 0.117873E+09 0.116161E+09
June 0.121773E+09 12029988.47 0.109743E+09 0.141455E+09 85298910.69
July 0.119193E+09 10114061.15 0.109079E+09 0.152259E+09 78640608.48
August 99102290.78 2201816.78 96900474.00 0.123584E+09 83320278.60
September 80955510.48 16100.43 80939410.05 95107828.21 96172740.95
October 66349884.71 0.00 66349884.71 87882234.51 0.111690E+09
November 58137116.95 0.00 58137116.95 46645770.27 0.164251E+09
December 51557659.69 0.00 51557659.69 38410052.94 0.191374E+09
           
Annual Sum or Average 0.101465E+10 31321617.54 0.983326E+09 0.104809E+10 0.157892E+10
Minimum of Months 51557659.69 0.00 51557659.69 38410052.94 78640608.48
Maximum of Months 0.121773E+09 12029988.47 0.112517E+09 0.152259E+09 0.191374E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.265521E+09 0.133901E+09 0.131620E+09 0.354908E+09 0.348253E+09
February 0.286426E+09 0.132386E+09 0.154039E+09 0.363119E+09 0.279601E+09
March 0.362688E+09 0.160278E+09 0.202410E+09 0.466411E+09 0.318531E+09
April 0.483730E+09 0.251482E+09 0.232247E+09 0.689272E+09 0.240557E+09
May 0.491022E+09 0.226458E+09 0.264564E+09 0.679623E+09 0.223707E+09
June 0.503264E+09 0.251292E+09 0.251972E+09 0.730395E+09 0.163986E+09
July 0.550654E+09 0.294353E+09 0.256300E+09 0.842737E+09 0.148521E+09
August 0.516705E+09 0.279782E+09 0.236923E+09 0.801582E+09 0.155152E+09
September 0.428535E+09 0.229221E+09 0.199314E+09 0.649209E+09 0.171604E+09
October 0.340146E+09 0.186368E+09 0.153778E+09 0.534396E+09 0.202660E+09
November 0.296219E+09 0.155051E+09 0.141168E+09 0.403959E+09 0.296674E+09
December 0.269240E+09 0.143959E+09 0.125281E+09 0.365544E+09 0.347450E+09
           
Annual Sum or Average 0.479415E+10 0.244453E+10 0.234962E+10 0.688115E+10 0.289670E+10
Minimum of Months 0.265521E+09 0.132386E+09 0.125281E+09 0.354908E+09 0.148521E+09
Maximum of Months 0.550654E+09 0.294353E+09 0.264564E+09 0.842737E+09 0.348253E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.293061E+09 0.215149E+09 77911467.45 0.403882E+09 0.209015E+09
February 0.209091E+09 0.129379E+09 79712592.74 0.266189E+09 0.177809E+09
March 0.184629E+09 89936327.87 94692605.60 0.226980E+09 0.201047E+09
April 0.149409E+09 57746850.06 91662135.38 0.192964E+09 0.162515E+09
May 0.108781E+09 13173513.96 95607483.13 0.104127E+09 0.153279E+09
June 92353413.13 5416561.15 86936851.98 86108758.40 0.117789E+09
July 0.100643E+09 10762115.76 89881160.52 0.115779E+09 0.107018E+09
August 0.129262E+09 40166453.60 89095338.36 0.182510E+09 0.112543E+09
September 0.171776E+09 85336561.19 86439337.30 0.251153E+09 0.126185E+09
October 0.232427E+09 0.156092E+09 76334792.12 0.347818E+09 0.139397E+09
November 0.273220E+09 0.193583E+09 79637126.46 0.375585E+09 0.185165E+09
December 0.313614E+09 0.238982E+09 74631825.39 0.436032E+09 0.208425E+09
           
Annual Sum or Average 0.225827E+10 0.123572E+10 0.102254E+10 0.298913E+10 0.190019E+10
Minimum of Months 92353413.13 5416561.15 74631825.39 86108758.40 0.107018E+09
Maximum of Months 0.313614E+09 0.238982E+09 95607483.13 0.436032E+09 0.209015E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 44312955.30 0.00 44312955.30 34429030.77 0.154378E+09
February 50241522.13 0.00 50241522.13 36185647.17 0.124308E+09
March 68169765.21 624.22 68169140.99 57064302.36 0.141696E+09
April 76404816.42 614812.68 75790003.74 79051900.17 0.100040E+09
May 94978755.02 4953021.70 90025733.32 0.102564E+09 89940366.93
June 97431324.50 9625266.49 87806058.00 0.123665E+09 63954343.57
July 95367114.15 8092321.46 87274792.68 0.134315E+09 56665831.42
August 79292341.88 1761686.91 77530654.97 0.110022E+09 59188812.50
September 64772993.27 12882.05 64760111.22 83365031.91 70326485.10
October 53086943.81 0.00 53086943.81 75246115.35 84578663.03
November 46515858.69 0.00 46515858.69 39416776.62 0.129933E+09
December 41251595.16 0.00 41251595.16 31791562.81 0.153646E+09
           
Annual Sum or Average 0.811826E+09 25060615.52 0.786765E+09 0.907117E+09 0.122866E+10
Minimum of Months 41251595.16 0.00 41251595.16 31791562.81 56665831.42
Maximum of Months 97431324.50 9625266.49 90025733.32 0.134315E+09 0.154378E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.278642E+09 0.148882E+09 0.129760E+09 0.346848E+09 0.339433E+09
February 0.265576E+09 0.121526E+09 0.144050E+09 0.309917E+09 0.273008E+09
March 0.358848E+09 0.160278E+09 0.198570E+09 0.442475E+09 0.307947E+09
April 0.442664E+09 0.222110E+09 0.220555E+09 0.620398E+09 0.228213E+09
May 0.430846E+09 0.179547E+09 0.251299E+09 0.590318E+09 0.211113E+09
June 0.414835E+09 0.180091E+09 0.234745E+09 0.610036E+09 0.149164E+09
July 0.485425E+09 0.241161E+09 0.244264E+09 0.763062E+09 0.129746E+09
August 0.479775E+09 0.254984E+09 0.224791E+09 0.759876E+09 0.134090E+09
September 0.338985E+09 0.155919E+09 0.183066E+09 0.508829E+09 0.158796E+09
October 0.308711E+09 0.158449E+09 0.150261E+09 0.473333E+09 0.187074E+09
November 0.271708E+09 0.137555E+09 0.134153E+09 0.341464E+09 0.290781E+09
December 0.269909E+09 0.150433E+09 0.119475E+09 0.335157E+09 0.339162E+09
           
Annual Sum or Average 0.434593E+10 0.211093E+10 0.223499E+10 0.610171E+10 0.274853E+10
Minimum of Months 0.265576E+09 0.121526E+09 0.119475E+09 0.309917E+09 0.129746E+09
Maximum of Months 0.485425E+09 0.254984E+09 0.251299E+09 0.763062E+09 0.339433E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.366399E+09 0.268990E+09 97408702.42 0.546703E+09 0.176683E+09
February 0.261416E+09 0.161756E+09 99660556.79 0.370713E+09 0.144304E+09
March 0.230832E+09 0.112443E+09 0.118389E+09 0.322871E+09 0.169212E+09
April 0.186798E+09 72197917.93 0.114600E+09 0.277539E+09 0.129275E+09
May 0.136003E+09 16470167.27 0.119533E+09 0.169725E+09 0.119994E+09
June 0.115465E+09 6772047.95 0.108693E+09 0.147961E+09 83091860.65
July 0.125829E+09 13455320.07 0.112374E+09 0.185719E+09 71207200.92
August 0.161609E+09 50218052.04 0.111391E+09 0.268179E+09 74284671.48
September 0.214763E+09 0.106692E+09 0.108071E+09 0.352998E+09 86608487.91
October 0.290591E+09 0.195153E+09 95437466.31 0.476952E+09 99476860.35
November 0.341593E+09 0.242027E+09 99566205.17 0.511259E+09 0.150802E+09
December 0.392095E+09 0.298787E+09 93308334.56 0.588500E+09 0.175324E+09
           
Annual Sum or Average 0.282339E+10 0.154496E+10 0.127843E+10 0.421912E+10 0.148026E+10
Minimum of Months 0.115465E+09 6772047.95 93308334.56 0.147961E+09 71207200.92
Maximum of Months 0.392095E+09 0.298787E+09 0.119533E+09 0.588500E+09 0.176683E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 55383852.68 0.00 55383852.68 40044959.51 0.189794E+09
February 62793579.01 0.00 62793579.01 42525077.15 0.152052E+09
March 85200912.64 780.17 85200132.47 66881951.03 0.174527E+09
April 95493362.34 768414.00 94724948.34 88380542.10 0.126485E+09
May 0.118708E+09 6190456.55 0.112517E+09 0.117985E+09 0.112724E+09
June 0.121773E+09 12029988.47 0.109743E+09 0.143605E+09 80577631.49
July 0.119193E+09 10114061.15 0.109079E+09 0.152692E+09 73437759.86
August 99102290.78 2201816.78 96900474.00 0.122086E+09 78094549.34
September 80955510.48 16100.43 80939410.05 95102006.11 90358341.73
October 66349884.71 0.00 66349884.71 86087433.75 0.108402E+09
November 58137116.95 0.00 58137116.95 45146673.29 0.161134E+09
December 51557659.69 0.00 51557659.69 36201285.54 0.189420E+09
           
Annual Sum or Average 0.101465E+10 31321617.54 0.983326E+09 0.103674E+10 0.153701E+10
Minimum of Months 51557659.69 0.00 51557659.69 36201285.54 73437759.86
Maximum of Months 0.121773E+09 12029988.47 0.112517E+09 0.152692E+09 0.189794E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.278642E+09 0.148882E+09 0.129760E+09 0.360764E+09 0.328057E+09
February 0.265576E+09 0.121526E+09 0.144050E+09 0.319689E+09 0.265973E+09
March 0.358848E+09 0.160278E+09 0.198570E+09 0.450246E+09 0.303591E+09
April 0.442664E+09 0.222110E+09 0.220555E+09 0.621996E+09 0.229113E+09
May 0.430846E+09 0.179547E+09 0.251299E+09 0.585378E+09 0.215440E+09
June 0.414835E+09 0.180091E+09 0.234745E+09 0.598451E+09 0.159255E+09
July 0.485425E+09 0.241161E+09 0.244264E+09 0.746523E+09 0.144479E+09
August 0.479775E+09 0.254984E+09 0.224791E+09 0.746733E+09 0.147535E+09
September 0.338985E+09 0.155919E+09 0.183066E+09 0.507642E+09 0.164323E+09
October 0.308711E+09 0.158449E+09 0.150261E+09 0.476424E+09 0.191462E+09
November 0.271708E+09 0.137555E+09 0.134153E+09 0.353015E+09 0.281586E+09
December 0.269909E+09 0.150433E+09 0.119475E+09 0.348826E+09 0.327312E+09
           
Annual Sum or Average 0.434593E+10 0.211093E+10 0.223499E+10 0.611569E+10 0.275813E+10
Minimum of Months 0.265576E+09 0.121526E+09 0.119475E+09 0.319689E+09 0.144479E+09
Maximum of Months 0.485425E+09 0.254984E+09 0.251299E+09 0.746733E+09 0.328057E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70140154.89 0.00 70140154.89 50198156.66 0.259700E+09
February 79524105.76 0.00 79524105.76 54055116.78 0.209922E+09
March 0.107902E+09 988.04 0.107901E+09 89293467.68 0.233684E+09
April 0.120936E+09 973147.84 0.119963E+09 0.123382E+09 0.169955E+09
May 0.150336E+09 7839822.62 0.142496E+09 0.161978E+09 0.152348E+09
June 0.154218E+09 15235221.35 0.138983E+09 0.196725E+09 0.109189E+09
July 0.150951E+09 12808820.29 0.138142E+09 0.210317E+09 99930375.56
August 0.125507E+09 2788462.02 0.122718E+09 0.168361E+09 0.107835E+09
September 0.102525E+09 20390.18 0.102505E+09 0.126251E+09 0.127624E+09
October 84027942.54 0.00 84027942.54 0.110683E+09 0.155550E+09
November 73626990.37 0.00 73626990.37 55959190.27 0.226554E+09
December 65294522.88 0.00 65294522.88 44067607.10 0.264161E+09
           
Annual Sum or Average 0.128499E+10 39666852.34 0.124532E+10 0.139127E+10 0.211645E+10
Minimum of Months 65294522.88 0.00 65294522.88 44067607.10 99930375.56
Maximum of Months 0.154218E+09 15235221.35 0.142496E+09 0.210317E+09 0.264161E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 25856565.37 0.00 25856565.37 18505119.09 95736197.65
February 29315878.22 0.00 29315878.22 19926954.29 77386075.97
March 39776990.23 364.23 39776626.00 32917269.54 86145463.21
April 44582134.43 358742.59 44223391.84 45483653.27 62652578.92
May 55420009.14 2890083.24 52529925.90 59711660.70 56161881.93
June 56851080.99 5616333.43 51234747.56 72520806.57 40251764.12
July 55646616.31 4721861.53 50924754.78 77531692.12 36838474.22
August 46267002.67 1027942.56 45239060.11 62064916.28 39752499.77
September 37794977.19 7516.66 37787460.52 46541224.86 47047638.96
October 30976178.94 0.00 30976178.94 40802356.77 57342184.46
November 27141957.31 0.00 27141957.31 20628874.62 83517143.33
December 24070264.77 0.00 24070264.77 16245144.67 97380510.19
           
Annual Sum or Average 0.473700E+09 14622844.25 0.459077E+09 0.512880E+09 0.780212E+09
Minimum of Months 24070264.77 0.00 24070264.77 16245144.67 36838474.22
Maximum of Months 56851080.99 5616333.43 52529925.90 77531692.12 97380510.19



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.170960E+09 0.125510E+09 45450508.02 0.258726E+09 86577581.44
February 0.121976E+09 75474510.52 46501214.20 0.175354E+09 71826412.75
March 0.107705E+09 52465342.08 55239968.79 0.154260E+09 82704797.69
April 87159368.36 33687257.57 53472110.79 0.133901E+09 64156617.20
May 63458586.31 7684913.68 55773672.63 82547320.10 60590007.41
June 53875375.24 3159810.28 50715564.96 71504752.30 43778797.84
July 58711357.72 6278198.12 52433159.60 88792333.72 39335915.28
August 75406282.36 23431540.72 51974741.64 0.127042E+09 41398532.30
September 0.100207E+09 49782017.80 50425334.32 0.166356E+09 46783044.77
October 0.135589E+09 91057819.93 44530737.20 0.223434E+09 54011539.12
November 0.159386E+09 0.112929E+09 46457190.11 0.240901E+09 76005897.61
December 0.182950E+09 0.139413E+09 43537292.90 0.277374E+09 87185390.58
           
Annual Sum or Average 0.131738E+10 0.720873E+09 0.596511E+09 0.200019E+10 0.754355E+09
Minimum of Months 53875375.24 3159810.28 43537292.90 71504752.30 39335915.28
Maximum of Months 0.182950E+09 0.139413E+09 55773672.63 0.277374E+09 87185390.58



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.464021E+09 0.340659E+09 0.123362E+09 0.702234E+09 0.234989E+09
February 0.331067E+09 0.204853E+09 0.126214E+09 0.475946E+09 0.194952E+09
March 0.292334E+09 0.142402E+09 0.149933E+09 0.418692E+09 0.224478E+09
April 0.236568E+09 91434107.63 0.145134E+09 0.363435E+09 0.174135E+09
May 0.172240E+09 20858427.64 0.151381E+09 0.224050E+09 0.164454E+09
June 0.146229E+09 8576371.43 0.137652E+09 0.194079E+09 0.118825E+09
July 0.159355E+09 17040313.89 0.142314E+09 0.241001E+09 0.106766E+09
August 0.204668E+09 63597994.32 0.141070E+09 0.344818E+09 0.112364E+09
September 0.271983E+09 0.135119E+09 0.136865E+09 0.451523E+09 0.126979E+09
October 0.368015E+09 0.247150E+09 0.120866E+09 0.606445E+09 0.146598E+09
November 0.432606E+09 0.306511E+09 0.126094E+09 0.653854E+09 0.206296E+09
December 0.496564E+09 0.378395E+09 0.118169E+09 0.752850E+09 0.236639E+09
           
Annual Sum or Average 0.357565E+10 0.195660E+10 0.161905E+10 0.542893E+10 0.204747E+10
Minimum of Months 0.146229E+09 8576371.43 0.118169E+09 0.194079E+09 0.106766E+09
Maximum of Months 0.496564E+09 0.378395E+09 0.151381E+09 0.752850E+09 0.236639E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.366399E+09 0.268990E+09 97408702.42 0.546609E+09 0.174923E+09
February 0.261416E+09 0.161756E+09 99660556.79 0.369049E+09 0.143724E+09
March 0.230832E+09 0.112443E+09 0.118389E+09 0.322184E+09 0.169302E+09
April 0.186798E+09 72197917.93 0.114600E+09 0.276037E+09 0.130744E+09
May 0.136003E+09 16470167.27 0.119533E+09 0.168109E+09 0.121820E+09
June 0.115465E+09 6772047.95 0.108693E+09 0.145980E+09 85292424.53
July 0.125829E+09 13455320.07 0.112374E+09 0.184439E+09 73213091.33
August 0.161609E+09 50218052.04 0.111391E+09 0.266773E+09 75775111.88
September 0.214763E+09 0.106692E+09 0.108071E+09 0.349758E+09 88281102.13
October 0.290591E+09 0.195153E+09 95437466.31 0.474880E+09 99067307.49
November 0.341593E+09 0.242027E+09 99566205.17 0.509497E+09 0.150011E+09
December 0.392095E+09 0.298787E+09 93308334.56 0.587705E+09 0.173548E+09
           
Annual Sum or Average 0.282339E+10 0.154496E+10 0.127843E+10 0.420102E+10 0.148570E+10
Minimum of Months 0.115465E+09 6772047.95 93308334.56 0.145980E+09 73213091.33
Maximum of Months 0.392095E+09 0.298787E+09 0.119533E+09 0.587705E+09 0.174923E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.265521E+09 0.133901E+09 0.131620E+09 0.336726E+09 0.351735E+09
February 0.286426E+09 0.132386E+09 0.154039E+09 0.349684E+09 0.280496E+09
March 0.362688E+09 0.160278E+09 0.202410E+09 0.453330E+09 0.318668E+09
April 0.483730E+09 0.251482E+09 0.232247E+09 0.681830E+09 0.235944E+09
May 0.491022E+09 0.226458E+09 0.264564E+09 0.678471E+09 0.216077E+09
June 0.503264E+09 0.251292E+09 0.251972E+09 0.737973E+09 0.149540E+09
July 0.550654E+09 0.294353E+09 0.256300E+09 0.853922E+09 0.128571E+09
August 0.516705E+09 0.279782E+09 0.236923E+09 0.807039E+09 0.135652E+09
September 0.428535E+09 0.229221E+09 0.199314E+09 0.645420E+09 0.160075E+09
October 0.340146E+09 0.186368E+09 0.153778E+09 0.526845E+09 0.192055E+09
November 0.296219E+09 0.155051E+09 0.141168E+09 0.388307E+09 0.297208E+09
December 0.269240E+09 0.143959E+09 0.125281E+09 0.347927E+09 0.349950E+09
           
Annual Sum or Average 0.479415E+10 0.244453E+10 0.234962E+10 0.680747E+10 0.281597E+10
Minimum of Months 0.265521E+09 0.132386E+09 0.125281E+09 0.336726E+09 0.128571E+09
Maximum of Months 0.550654E+09 0.294353E+09 0.264564E+09 0.853922E+09 0.351735E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 55383852.68 0.00 55383852.68 43211357.54 0.186942E+09
February 62793579.01 0.00 62793579.01 44477428.38 0.151420E+09
March 85200912.64 780.17 85200132.47 68436056.35 0.174848E+09
April 95493362.34 768414.00 94724948.34 87351261.90 0.130468E+09
May 0.118708E+09 6190456.55 0.112517E+09 0.114725E+09 0.116385E+09
June 0.121773E+09 12029988.47 0.109743E+09 0.137073E+09 86910193.39
July 0.119193E+09 10114061.15 0.109079E+09 0.148017E+09 80735724.71
August 99102290.78 2201816.78 96900474.00 0.120790E+09 85131447.38
September 80955510.48 16100.43 80939410.05 93699572.23 96018549.41
October 66349884.71 0.00 66349884.71 88208090.38 0.109369E+09
November 58137116.95 0.00 58137116.95 47683572.33 0.160555E+09
December 51557659.69 0.00 51557659.69 40019311.68 0.186574E+09
           
Annual Sum or Average 0.101465E+10 31321617.54 0.983326E+09 0.103369E+10 0.156536E+10
Minimum of Months 51557659.69 0.00 51557659.69 40019311.68 80735724.71
Maximum of Months 0.121773E+09 12029988.47 0.112517E+09 0.148017E+09 0.186942E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.265521E+09 0.133901E+09 0.131620E+09 0.354058E+09 0.340802E+09
February 0.286426E+09 0.132386E+09 0.154039E+09 0.360986E+09 0.274037E+09
March 0.362688E+09 0.160278E+09 0.202410E+09 0.460981E+09 0.315141E+09
April 0.483730E+09 0.251482E+09 0.232247E+09 0.678661E+09 0.240044E+09
May 0.491022E+09 0.226458E+09 0.264564E+09 0.667999E+09 0.223620E+09
June 0.503264E+09 0.251292E+09 0.251972E+09 0.716866E+09 0.166511E+09
July 0.550654E+09 0.294353E+09 0.256300E+09 0.829245E+09 0.151890E+09
August 0.516705E+09 0.279782E+09 0.236923E+09 0.789903E+09 0.157623E+09
September 0.428535E+09 0.229221E+09 0.199314E+09 0.641090E+09 0.170593E+09
October 0.340146E+09 0.186368E+09 0.153778E+09 0.531056E+09 0.198212E+09
November 0.296219E+09 0.155051E+09 0.141168E+09 0.402619E+09 0.289666E+09
December 0.269240E+09 0.143959E+09 0.125281E+09 0.365986E+09 0.338566E+09
           
Annual Sum or Average 0.479415E+10 0.244453E+10 0.234962E+10 0.679945E+10 0.286671E+10
Minimum of Months 0.265521E+09 0.132386E+09 0.125281E+09 0.354058E+09 0.151890E+09
Maximum of Months 0.550654E+09 0.294353E+09 0.264564E+09 0.829245E+09 0.340802E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.537359E+09 0.394500E+09 0.142859E+09 0.789075E+09 0.267842E+09
February 0.383392E+09 0.237230E+09 0.146162E+09 0.532951E+09 0.218153E+09
March 0.338537E+09 0.164908E+09 0.173629E+09 0.466431E+09 0.253231E+09
April 0.273958E+09 0.105885E+09 0.168073E+09 0.405949E+09 0.189010E+09
May 0.199462E+09 24155080.95 0.175307E+09 0.252048E+09 0.173284E+09
June 0.169340E+09 9931858.23 0.159408E+09 0.222605E+09 0.118079E+09
July 0.184540E+09 19733518.19 0.164807E+09 0.280419E+09 99281129.80
August 0.237016E+09 73649592.75 0.163366E+09 0.397664E+09 0.104683E+09
September 0.314970E+09 0.156474E+09 0.158496E+09 0.514004E+09 0.126419E+09
October 0.426179E+09 0.286211E+09 0.139968E+09 0.692787E+09 0.146866E+09
November 0.500979E+09 0.354955E+09 0.146023E+09 0.737660E+09 0.227937E+09
December 0.575045E+09 0.438199E+09 0.136846E+09 0.849091E+09 0.265771E+09
           
Annual Sum or Average 0.414078E+10 0.226583E+10 0.187494E+10 0.614068E+10 0.219056E+10
Minimum of Months 0.169340E+09 9931858.23 0.136846E+09 0.222605E+09 99281129.80
Maximum of Months 0.575045E+09 0.438199E+09 0.175307E+09 0.849091E+09 0.267842E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.387672E+09 0.00 0.387672E+09 0.214931E+09 0.163035E+10
February 0.439538E+09 0.00 0.439538E+09 0.226228E+09 0.135756E+10
March 0.596384E+09 5460.98 0.596378E+09 0.383566E+09 0.152050E+10
April 0.668428E+09 5378694.26 0.663050E+09 0.553527E+09 0.110003E+10
May 0.830922E+09 43331554.67 0.787591E+09 0.728954E+09 0.983134E+09
June 0.852379E+09 84206730.00 0.768172E+09 0.928518E+09 0.709632E+09
July 0.834320E+09 70795746.72 0.763524E+09 0.102982E+10 0.631185E+09
August 0.693690E+09 15412133.73 0.678278E+09 0.825330E+09 0.678339E+09
September 0.566667E+09 112698.72 0.566554E+09 0.610184E+09 0.808543E+09
October 0.464432E+09 0.00 0.464432E+09 0.551343E+09 0.960916E+09
November 0.406944E+09 0.00 0.406944E+09 0.249774E+09 0.140884E+10
December 0.360890E+09 0.00 0.360890E+09 0.191617E+09 0.163317E+10
           
Annual Sum or Average 0.710227E+10 0.219243E+09 0.688302E+10 0.649379E+10 0.134222E+11
Minimum of Months 0.360890E+09 0.00 0.360890E+09 0.191617E+09 0.631185E+09
Maximum of Months 0.852379E+09 84206730.00 0.787591E+09 0.102982E+10 0.163317E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.387672E+09 0.00 0.387672E+09 0.193938E+09 0.168781E+10
February 0.439538E+09 0.00 0.439538E+09 0.204366E+09 0.140874E+10
March 0.596384E+09 5460.98 0.596378E+09 0.354207E+09 0.157328E+10
April 0.668428E+09 5378694.26 0.663050E+09 0.520387E+09 0.113674E+10
May 0.830922E+09 43331554.67 0.787591E+09 0.688334E+09 0.101366E+10
June 0.852379E+09 84206730.00 0.768172E+09 0.892540E+09 0.733428E+09
July 0.834320E+09 70795746.72 0.763524E+09 0.997246E+09 0.652480E+09
August 0.693690E+09 15412133.73 0.678278E+09 0.795691E+09 0.702455E+09
September 0.566667E+09 112698.72 0.566554E+09 0.583486E+09 0.839505E+09
October 0.464432E+09 0.00 0.464432E+09 0.527463E+09 0.996212E+09
November 0.406944E+09 0.00 0.406944E+09 0.227911E+09 0.145795E+10
December 0.360890E+09 0.00 0.360890E+09 0.171607E+09 0.168941E+10
           
Annual Sum or Average 0.710227E+10 0.219243E+09 0.688302E+10 0.615718E+10 0.138917E+11
Minimum of Months 0.360890E+09 0.00 0.360890E+09 0.171607E+09 0.652480E+09
Maximum of Months 0.852379E+09 84206730.00 0.787591E+09 0.997246E+09 0.168941E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 55383852.68 0.00 55383852.68 50901666.14 0.200791E+09
February 62793579.01 0.00 62793579.01 51420040.81 0.171014E+09
March 85200912.64 780.17 85200132.47 80629349.39 0.194565E+09
April 95493362.34 768414.00 94724948.34 0.114350E+09 0.142240E+09
May 0.118708E+09 6190456.55 0.112517E+09 0.149138E+09 0.131325E+09
June 0.121773E+09 12029988.47 0.109743E+09 0.182014E+09 94957656.43
July 0.119193E+09 10114061.15 0.109079E+09 0.200431E+09 84042537.38
August 99102290.78 2201816.78 96900474.00 0.166370E+09 88399406.38
September 80955510.48 16100.43 80939410.05 0.125260E+09 98442429.33
October 66349884.71 0.00 66349884.71 0.113640E+09 0.116342E+09
November 58137116.95 0.00 58137116.95 57605925.33 0.172469E+09
December 51557659.69 0.00 51557659.69 47307726.01 0.201207E+09
           
Annual Sum or Average 0.101465E+10 31321617.54 0.983326E+09 0.133907E+10 0.169579E+10
Minimum of Months 51557659.69 0.00 51557659.69 47307726.01 84042537.38
Maximum of Months 0.121773E+09 12029988.47 0.112517E+09 0.200431E+09 0.201207E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.557245E+09 0.297743E+09 0.259502E+09 0.776472E+09 0.706431E+09
February 0.531115E+09 0.243035E+09 0.288080E+09 0.678178E+09 0.608540E+09
March 0.717645E+09 0.320532E+09 0.397113E+09 0.960386E+09 0.688758E+09
April 0.885266E+09 0.444188E+09 0.441078E+09 0.134935E+10 0.519500E+09
May 0.861631E+09 0.359068E+09 0.502562E+09 0.128671E+10 0.496798E+09
June 0.829612E+09 0.360156E+09 0.469456E+09 0.133910E+10 0.366601E+09
July 0.970781E+09 0.482287E+09 0.488494E+09 0.167172E+10 0.323712E+09
August 0.959482E+09 0.509932E+09 0.449550E+09 0.166456E+10 0.333398E+09
September 0.677922E+09 0.311816E+09 0.366105E+09 0.113796E+10 0.364817E+09
October 0.617378E+09 0.316876E+09 0.300501E+09 0.106641E+10 0.419485E+09
November 0.543378E+09 0.275091E+09 0.268287E+09 0.761730E+09 0.612417E+09
December 0.539779E+09 0.300845E+09 0.238934E+09 0.750393E+09 0.706807E+09
           
Annual Sum or Average 0.869123E+10 0.422157E+10 0.446966E+10 0.134430E+11 0.614726E+10
Minimum of Months 0.531115E+09 0.243035E+09 0.238934E+09 0.678178E+09 0.323712E+09
Maximum of Months 0.970781E+09 0.509932E+09 0.502562E+09 0.167172E+10 0.706807E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.366399E+09 0.268990E+09 97408702.42 0.575082E+09 0.186461E+09
February 0.261416E+09 0.161756E+09 99660556.79 0.389719E+09 0.162657E+09
March 0.230832E+09 0.112443E+09 0.118389E+09 0.344686E+09 0.189436E+09
April 0.186798E+09 72197917.93 0.114600E+09 0.305900E+09 0.145202E+09
May 0.136003E+09 16470167.27 0.119533E+09 0.196450E+09 0.139437E+09
June 0.115465E+09 6772047.95 0.108693E+09 0.179051E+09 0.100945E+09
July 0.125829E+09 13455320.07 0.112374E+09 0.224085E+09 87667294.35
August 0.161609E+09 50218052.04 0.111391E+09 0.306611E+09 90691416.97
September 0.214763E+09 0.106692E+09 0.108071E+09 0.385746E+09 98526403.97
October 0.290591E+09 0.195153E+09 95437466.31 0.511159E+09 0.112435E+09
November 0.341593E+09 0.242027E+09 99566205.17 0.538096E+09 0.161774E+09
December 0.392095E+09 0.298787E+09 93308334.56 0.616599E+09 0.185792E+09
           
Annual Sum or Average 0.282339E+10 0.154496E+10 0.127843E+10 0.457318E+10 0.166102E+10
Minimum of Months 0.115465E+09 6772047.95 93308334.56 0.179051E+09 87667294.35
Maximum of Months 0.392095E+09 0.298787E+09 0.119533E+09 0.616599E+09 0.189436E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70140154.89 0.00 70140154.89 45866653.86 0.260082E+09
February 79524105.76 0.00 79524105.76 50066724.60 0.209555E+09
March 0.107902E+09 988.04 0.107901E+09 82494111.03 0.236296E+09
April 0.120936E+09 973147.84 0.119963E+09 0.114481E+09 0.172270E+09
May 0.150336E+09 7839822.62 0.142496E+09 0.153034E+09 0.153693E+09
June 0.154218E+09 15235221.35 0.138983E+09 0.186082E+09 0.111475E+09
July 0.150951E+09 12808820.29 0.138142E+09 0.199688E+09 0.101896E+09
August 0.125507E+09 2788462.02 0.122718E+09 0.158894E+09 0.110074E+09
September 0.102525E+09 20390.18 0.102505E+09 0.119008E+09 0.128995E+09
October 84027942.54 0.00 84027942.54 0.105568E+09 0.155195E+09
November 73626990.37 0.00 73626990.37 52632630.80 0.223730E+09
December 65294522.88 0.00 65294522.88 40993054.13 0.260792E+09
           
Annual Sum or Average 0.128499E+10 39666852.34 0.124532E+10 0.130881E+10 0.212405E+10
Minimum of Months 65294522.88 0.00 65294522.88 40993054.13 0.101896E+09
Maximum of Months 0.154218E+09 15235221.35 0.142496E+09 0.199688E+09 0.260792E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 62754662.34 0.00 62754662.34 41037068.99 0.232673E+09
February 71150518.74 0.00 71150518.74 44794888.20 0.187489E+09
March 96539952.45 884.00 96539068.45 73807793.71 0.211415E+09
April 0.108202E+09 870679.06 0.107332E+09 0.102427E+09 0.154131E+09
May 0.134506E+09 7014319.00 0.127492E+09 0.136920E+09 0.137510E+09
June 0.137979E+09 13631010.27 0.124348E+09 0.166489E+09 99736765.23
July 0.135056E+09 11460100.04 0.123596E+09 0.178662E+09 91166850.26
August 0.112291E+09 2494847.54 0.109797E+09 0.142163E+09 98483307.57
September 91729547.13 18243.17 91711303.96 0.106477E+09 0.115413E+09
October 75180118.57 0.00 75180118.57 94451944.23 0.138853E+09
November 65874347.26 0.00 65874347.26 47090614.20 0.200170E+09
December 58419257.03 0.00 58419257.03 36676640.85 0.233298E+09
           
Annual Sum or Average 0.114968E+10 35490083.08 0.111419E+10 0.117100E+10 0.190034E+10
Minimum of Months 58419257.03 0.00 58419257.03 36676640.85 91166850.26
Maximum of Months 0.137979E+09 13631010.27 0.127492E+09 0.178662E+09 0.233298E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.136788E+10 0.100422E+10 0.363656E+09 0.204563E+10 0.694063E+09
February 0.975944E+09 0.603882E+09 0.372063E+09 0.138021E+10 0.575179E+09
March 0.861765E+09 0.419782E+09 0.441983E+09 0.120526E+10 0.671135E+09
April 0.697374E+09 0.269536E+09 0.427838E+09 0.103953E+10 0.522279E+09
May 0.507741E+09 61488042.30 0.446253E+09 0.631932E+09 0.491621E+09
June 0.431064E+09 25282072.96 0.405782E+09 0.542300E+09 0.359808E+09
July 0.469758E+09 50232719.31 0.419525E+09 0.679470E+09 0.323197E+09
August 0.603336E+09 0.187479E+09 0.415857E+09 0.984803E+09 0.339714E+09
September 0.801773E+09 0.398313E+09 0.403460E+09 0.130269E+10 0.379287E+09
October 0.108486E+10 0.728566E+09 0.356297E+09 0.176261E+10 0.432567E+09
November 0.127527E+10 0.903557E+09 0.371710E+09 0.190645E+10 0.601876E+09
December 0.146381E+10 0.111546E+10 0.348348E+09 0.219829E+10 0.689852E+09
           
Annual Sum or Average 0.105406E+11 0.576780E+10 0.477277E+10 0.156792E+11 0.608058E+10
Minimum of Months 0.431064E+09 25282072.96 0.348348E+09 0.542300E+09 0.323197E+09
Maximum of Months 0.146381E+10 0.111546E+10 0.446253E+09 0.219829E+10 0.694063E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1021.34 343.16 691.88 507.95 183.94 0.00 0.00
February 773.76 308.05 546.53 338.18 208.36 0.00 0.00
March 615.55 317.98 435.89 212.33 223.56 0.00 0.00
April 551.13 254.34 364.49 140.88 223.62 0.00 0.00
May 337.95 222.97 256.82 31.10 225.72 0.00 0.00
June 302.55 165.41 225.30 13.21 212.09 0.00 0.00
July 357.92 145.51 237.61 25.41 212.20 0.00 0.00
August 505.46 157.81 305.17 94.83 210.34 0.00 0.00
September 681.35 189.12 419.06 208.19 210.87 0.00 0.00
October 887.82 211.68 548.73 368.52 180.22 0.00 0.00
November 987.55 307.82 666.54 472.26 194.28 0.00 0.00
December 1097.96 344.50 740.41 564.21 176.20 0.00 0.00
               
Annual Sum or Average 676.40 247.06 452.81 247.78 205.03 0.00 0.00
Minimum of Months 302.55 145.51 225.30 13.21 176.20 0.00 0.00
Maximum of Months 1097.96 344.50 740.41 564.21 225.72 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2835.66 1053.46 1948.30 1430.34 517.96 0.00 0.00
February 2139.03 956.83 1539.00 952.28 586.71 0.00 0.00
March 1696.18 979.50 1227.43 597.91 629.52 0.00 0.00
April 1517.65 794.02 1026.39 396.71 629.69 0.00 0.00
May 913.80 700.68 723.18 87.58 635.60 0.00 0.00
June 815.57 530.63 634.43 37.21 597.22 0.00 0.00
July 979.93 460.95 669.08 71.55 597.53 0.00 0.00
August 1401.37 495.94 859.34 267.03 592.31 0.00 0.00
September 1893.49 593.93 1180.05 586.24 593.81 0.00 0.00
October 2469.37 659.22 1545.20 1037.72 507.48 0.00 0.00
November 2739.56 952.13 1876.94 1329.86 547.08 0.00 0.00
December 3049.74 1057.58 2084.94 1588.78 496.16 0.00 0.00
               
Annual Sum or Average 1870.16 768.60 1275.09 697.73 577.36 0.00 0.00
Minimum of Months 815.57 460.95 634.43 37.21 496.16 0.00 0.00
Maximum of Months 3049.74 1057.58 2084.94 1588.78 635.60 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3768.83 1395.77 2530.95 1858.09 672.86 0.00 0.00
February 2839.55 1287.28 1999.24 1237.07 762.17 0.00 0.00
March 2246.82 1329.20 1594.50 776.72 817.79 0.00 0.00
April 2012.08 1079.11 1333.34 515.34 818.00 0.00 0.00
May 1190.33 975.11 939.45 113.77 825.68 0.00 0.00
June 1056.64 744.58 824.17 48.34 775.83 0.00 0.00
July 1283.37 642.68 869.17 92.94 776.23 0.00 0.00
August 1857.16 673.73 1116.33 346.89 769.44 0.00 0.00
September 2515.66 797.02 1532.95 761.56 771.39 0.00 0.00
October 3277.19 874.31 2007.30 1348.05 659.24 0.00 0.00
November 3639.08 1264.61 2438.25 1727.56 710.69 0.00 0.00
December 4050.23 1400.68 2708.45 2063.92 644.54 0.00 0.00
               
Annual Sum or Average 2477.00 1037.37 1656.41 906.39 750.02 0.00 0.00
Minimum of Months 1056.64 642.68 824.17 48.34 644.54 0.00 0.00
Maximum of Months 4050.23 1400.68 2708.45 2063.92 825.68 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 325.96 193.76 235.93 150.42 85.51 0.00 0.00
February 296.58 175.01 226.46 121.59 104.87 0.00 0.00
March 290.65 181.76 221.59 101.82 119.77 0.00 0.00
April 372.90 140.94 258.69 124.88 133.81 0.00 0.00
May 319.08 125.28 234.10 90.70 143.41 0.00 0.00
June 344.32 89.51 238.71 99.56 139.15 0.00 0.00
July 391.15 74.75 252.57 114.92 137.65 0.00 0.00
August 404.64 78.92 253.25 123.21 130.05 0.00 0.00
September 387.13 96.16 248.19 129.60 118.59 0.00 0.00
October 375.33 109.55 235.49 142.44 93.05 0.00 0.00
November 344.75 171.46 246.07 153.19 92.88 0.00 0.00
December 344.52 192.45 246.91 165.30 81.61 0.00 0.00
               
Annual Sum or Average 350.05 135.60 241.55 126.51 115.04 0.00 0.00
Minimum of Months 290.65 74.75 221.59 90.70 81.61 0.00 0.00
Maximum of Months 404.64 193.76 258.69 165.30 143.41 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 146.50 199.53 119.81 49.99 69.82 0.00 0.00
February 166.37 177.50 144.35 54.72 89.63 0.00 0.00
March 197.85 182.74 167.22 59.84 107.38 0.00 0.00
April 299.32 141.87 223.47 97.32 126.15 0.00 0.00
May 296.51 125.65 227.65 86.86 140.79 0.00 0.00
June 335.28 95.09 241.14 101.59 139.55 0.00 0.00
July 370.74 84.06 250.09 113.68 136.42 0.00 0.00
August 344.67 88.28 229.92 105.28 124.64 0.00 0.00
September 285.57 101.72 196.56 88.44 108.12 0.00 0.00
October 231.24 116.27 151.77 69.58 82.19 0.00 0.00
November 171.75 175.73 136.71 59.82 76.89 0.00 0.00
December 148.80 199.16 119.77 53.75 66.02 0.00 0.00
               
Annual Sum or Average 249.98 140.46 184.20 78.51 105.69 0.00 0.00
Minimum of Months 146.50 84.06 119.77 49.99 66.02 0.00 0.00
Maximum of Months 370.74 199.53 250.09 113.68 140.79 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 150.79 78.04 109.42 80.33 29.09 0.00 0.00
February 110.03 73.50 86.43 53.48 32.95 0.00 0.00
March 84.74 75.06 68.93 33.58 35.35 0.00 0.00
April 74.45 62.70 57.64 22.28 35.36 0.00 0.00
May 38.88 57.23 40.61 4.92 35.70 0.00 0.00
June 33.22 45.44 35.63 2.09 33.54 0.00 0.00
July 43.23 39.96 37.58 4.02 33.56 0.00 0.00
August 68.14 42.02 48.26 15.00 33.26 0.00 0.00
September 96.90 48.68 66.27 32.92 33.35 0.00 0.00
October 129.86 52.04 86.78 58.28 28.50 0.00 0.00
November 144.90 71.44 105.41 74.68 30.72 0.00 0.00
December 162.80 77.82 117.09 89.23 27.86 0.00 0.00
               
Annual Sum or Average 94.78 60.25 71.61 39.18 32.42 0.00 0.00
Minimum of Months 33.22 39.96 35.63 2.09 27.86 0.00 0.00
Maximum of Months 162.80 78.04 117.09 89.23 35.70 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 12.85 57.64 16.54 0.00 16.54 0.00 0.00
February 14.96 51.38 20.77 0.00 20.77 0.00 0.00
March 21.31 52.90 25.45 0.00 25.45 0.00 0.00
April 30.50 38.60 29.48 0.24 29.24 0.00 0.00
May 38.29 33.58 35.46 1.85 33.61 0.00 0.00
June 47.71 24.67 37.59 3.71 33.88 0.00 0.00
July 50.15 21.16 35.61 3.02 32.58 0.00 0.00
August 41.08 22.10 29.60 0.66 28.95 0.00 0.00
September 32.16 27.13 24.99 0.00 24.98 0.00 0.00
October 28.09 31.58 19.82 0.00 19.82 0.00 0.00
November 15.21 50.13 17.95 0.00 17.95 0.00 0.00
December 11.87 57.36 15.40 0.00 15.40 0.00 0.00
               
Annual Sum or Average 28.76 38.96 25.74 0.79 24.95 0.00 0.00
Minimum of Months 11.87 21.16 15.40 0.00 15.40 0.00 0.00
Maximum of Months 50.15 57.64 37.59 3.71 33.88 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 330.78 189.86 240.83 156.02 84.82 0.00 0.00
February 279.29 170.45 217.84 117.10 100.74 0.00 0.00
March 283.13 175.53 220.16 101.82 118.34 0.00 0.00
April 344.21 135.71 242.85 113.54 129.30 0.00 0.00
May 281.51 121.36 211.64 73.18 138.45 0.00 0.00
June 291.33 88.50 204.59 72.09 132.50 0.00 0.00
July 353.73 74.53 228.22 95.06 133.15 0.00 0.00
August 383.04 77.01 239.47 113.95 125.52 0.00 0.00
September 331.85 94.04 213.64 101.32 112.32 0.00 0.00
October 353.78 105.97 223.75 132.02 91.73 0.00 0.00
November 326.42 167.80 236.61 146.44 90.17 0.00 0.00
December 341.86 189.10 247.16 167.72 79.44 0.00 0.00
               
Annual Sum or Average 325.47 132.30 227.34 115.93 111.41 0.00 0.00
Minimum of Months 279.29 74.53 204.59 72.09 79.44 0.00 0.00
Maximum of Months 383.04 189.86 247.16 167.72 138.45 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 144.80 188.50 124.71 55.59 69.12 0.00 0.00
February 146.23 169.30 135.73 50.23 85.50 0.00 0.00
March 188.97 174.40 165.79 59.84 105.95 0.00 0.00
April 272.17 135.29 207.62 85.99 121.64 0.00 0.00
May 261.46 121.37 205.18 69.35 135.83 0.00 0.00
June 284.65 90.89 207.02 74.12 132.90 0.00 0.00
July 334.41 80.05 225.74 93.82 131.92 0.00 0.00
August 323.77 83.63 216.13 96.02 120.11 0.00 0.00
September 231.76 97.48 162.01 60.16 101.85 0.00 0.00
October 207.91 109.85 140.03 59.16 80.87 0.00 0.00
November 149.84 167.03 127.26 53.07 74.19 0.00 0.00
December 138.79 187.96 120.02 56.17 63.86 0.00 0.00
               
Annual Sum or Average 224.25 133.64 169.98 67.93 102.05 0.00 0.00
Minimum of Months 138.79 80.05 120.02 50.23 63.86 0.00 0.00
Maximum of Months 334.41 188.50 225.74 96.02 135.83 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 375.54 243.87 272.92 174.05 98.87 0.00 0.00
February 295.07 224.31 232.26 115.88 116.38 0.00 0.00
March 257.82 232.38 204.49 72.76 131.74 0.00 0.00
April 256.70 181.36 188.75 48.79 139.97 0.00 0.00
May 195.24 159.87 164.82 14.66 150.16 0.00 0.00
June 203.48 117.52 158.63 12.57 146.06 0.00 0.00
July 228.52 103.53 158.55 15.25 143.30 0.00 0.00
August 261.53 111.84 168.70 33.92 134.78 0.00 0.00
September 304.93 134.31 197.73 71.35 126.38 0.00 0.00
October 364.02 152.01 230.96 126.27 104.69 0.00 0.00
November 367.99 221.78 267.27 161.82 105.45 0.00 0.00
December 396.93 245.66 287.07 193.33 93.74 0.00 0.00
               
Annual Sum or Average 292.39 177.13 210.92 86.62 124.30 0.00 0.00
Minimum of Months 195.24 103.53 158.55 12.57 93.74 0.00 0.00
Maximum of Months 396.93 245.66 287.07 193.33 150.16 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 324.24 191.07 235.93 150.42 85.51 0.00 0.00
February 294.13 172.39 226.46 121.59 104.87 0.00 0.00
March 287.39 180.03 221.59 101.82 119.77 0.00 0.00
April 367.80 139.73 258.69 124.88 133.81 0.00 0.00
May 314.16 124.24 234.10 90.70 143.41 0.00 0.00
June 339.12 88.69 238.71 99.56 139.15 0.00 0.00
July 386.21 73.87 252.57 114.92 137.65 0.00 0.00
August 399.86 77.88 253.25 123.21 130.05 0.00 0.00
September 382.83 94.71 248.19 129.60 118.59 0.00 0.00
October 372.65 107.34 235.49 142.44 93.05 0.00 0.00
November 342.52 168.69 246.07 153.19 92.88 0.00 0.00
December 343.10 189.22 246.91 165.30 81.61 0.00 0.00
               
Annual Sum or Average 346.46 133.79 241.55 126.51 115.04 0.00 0.00
Minimum of Months 287.39 73.87 221.59 90.70 81.61 0.00 0.00
Maximum of Months 399.86 191.07 258.69 165.30 143.41 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 146.57 195.28 119.81 49.99 69.82 0.00 0.00
February 165.70 173.97 144.35 54.72 89.63 0.00 0.00
March 195.49 180.77 167.22 59.84 107.38 0.00 0.00
April 294.16 141.57 223.47 97.32 126.15 0.00 0.00
May 290.96 125.66 227.65 86.86 140.79 0.00 0.00
June 328.30 96.62 241.14 101.59 139.55 0.00 0.00
July 364.07 86.05 250.09 113.68 136.42 0.00 0.00
August 339.13 89.75 229.92 105.28 124.64 0.00 0.00
September 281.75 101.12 196.56 88.44 108.12 0.00 0.00
October 230.09 113.72 151.77 69.58 82.19 0.00 0.00
November 171.62 171.59 136.71 59.82 76.89 0.00 0.00
December 149.60 194.08 119.77 53.75 66.02 0.00 0.00
               
Annual Sum or Average 246.87 139.02 184.20 78.51 105.69 0.00 0.00
Minimum of Months 146.57 86.05 119.77 49.99 66.02 0.00 0.00
Maximum of Months 364.07 195.28 250.09 113.68 140.79 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 294.61 100.00 200.63 147.29 53.34 0.00 0.00
February 220.30 90.18 158.48 98.06 60.42 0.00 0.00
March 174.15 94.55 126.40 61.57 64.83 0.00 0.00
April 156.62 72.92 105.69 40.85 64.84 0.00 0.00
May 94.10 64.70 74.47 9.02 65.45 0.00 0.00
June 85.88 45.56 65.33 3.83 61.50 0.00 0.00
July 104.70 37.07 68.90 7.37 61.53 0.00 0.00
August 148.47 39.08 88.49 27.50 60.99 0.00 0.00
September 198.30 48.77 121.52 60.37 61.15 0.00 0.00
October 258.66 54.83 159.12 106.86 52.26 0.00 0.00
November 284.59 87.94 193.28 136.94 56.34 0.00 0.00
December 317.01 99.23 214.70 163.60 51.09 0.00 0.00
               
Annual Sum or Average 194.72 69.46 131.30 71.85 59.45 0.00 0.00
Minimum of Months 85.88 37.07 65.33 3.83 51.09 0.00 0.00
Maximum of Months 317.01 100.00 214.70 163.60 65.45 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 80.25 608.70 144.74 0.00 144.74 0.00 0.00
February 93.51 561.16 181.69 0.00 181.69 0.00 0.00
March 143.21 567.69 222.66 0.00 222.66 0.00 0.00
April 213.55 424.39 257.88 2.08 255.81 0.00 0.00
May 272.16 367.06 310.23 16.18 294.05 0.00 0.00
June 358.22 273.78 328.85 32.49 296.36 0.00 0.00
July 384.49 235.66 311.50 26.43 285.07 0.00 0.00
August 308.14 253.26 258.99 5.75 253.24 0.00 0.00
September 235.41 311.94 218.62 0.04 218.58 0.00 0.00
October 205.85 358.76 173.40 0.00 173.40 0.00 0.00
November 96.36 543.53 157.00 0.00 157.00 0.00 0.00
December 71.54 609.76 134.74 0.00 134.74 0.00 0.00
               
Annual Sum or Average 205.92 425.62 225.21 6.95 218.26 0.00 0.00
Minimum of Months 71.54 235.66 134.74 0.00 134.74 0.00 0.00
Maximum of Months 384.49 609.76 328.85 32.49 296.36 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 72.41 630.15 144.74 0.00 144.74 0.00 0.00
February 84.48 582.32 181.69 0.00 181.69 0.00 0.00
March 132.25 587.40 222.66 0.00 222.66 0.00 0.00
April 200.77 438.56 257.88 2.08 255.81 0.00 0.00
May 256.99 378.46 310.23 16.18 294.05 0.00 0.00
June 344.34 282.96 328.85 32.49 296.36 0.00 0.00
July 372.33 243.61 311.50 26.43 285.07 0.00 0.00
August 297.08 262.27 258.99 5.75 253.24 0.00 0.00
September 225.11 323.88 218.62 0.04 218.58 0.00 0.00
October 196.93 371.94 173.40 0.00 173.40 0.00 0.00
November 87.93 562.48 157.00 0.00 157.00 0.00 0.00
December 64.07 630.75 134.74 0.00 134.74 0.00 0.00
               
Annual Sum or Average 195.24 440.50 225.21 6.95 218.26 0.00 0.00
Minimum of Months 64.07 243.61 134.74 0.00 134.74 0.00 0.00
Maximum of Months 372.33 630.75 328.85 32.49 296.36 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 516.18 400.89 365.53 211.59 153.93 0.00 0.00
February 457.61 384.41 353.56 167.32 186.23 0.00 0.00
March 511.35 394.51 385.93 161.65 224.28 0.00 0.00
April 679.15 307.75 450.45 199.52 250.93 0.00 0.00
May 606.45 283.60 416.79 142.52 274.27 0.00 0.00
June 653.25 214.34 411.59 146.20 265.39 0.00 0.00
July 780.84 183.16 453.93 188.87 265.06 0.00 0.00
August 796.98 190.26 455.57 209.96 245.61 0.00 0.00
September 635.21 215.77 375.63 161.47 214.16 0.00 0.00
October 629.03 239.63 363.77 191.17 172.60 0.00 0.00
November 517.70 359.22 363.85 199.51 164.35 0.00 0.00
December 520.26 400.61 367.17 223.88 143.29 0.00 0.00
               
Annual Sum or Average 609.77 297.39 397.30 183.85 213.45 0.00 0.00
Minimum of Months 457.61 183.16 353.56 142.52 143.29 0.00 0.00
Maximum of Months 796.98 400.89 455.57 223.88 274.27 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 782.83 429.74 560.32 374.93 185.39 0.00 0.00
February 602.61 394.75 465.70 249.62 216.08 0.00 0.00
March 505.61 415.00 398.08 156.73 241.35 0.00 0.00
April 484.23 326.92 357.45 104.70 252.75 0.00 0.00
May 340.63 288.71 295.92 28.50 267.41 0.00 0.00
June 339.93 214.98 279.04 20.89 258.15 0.00 0.00
July 390.95 188.76 282.17 27.82 254.35 0.00 0.00
August 478.89 203.51 314.04 71.97 242.07 0.00 0.00
September 589.39 240.43 384.27 153.68 230.58 0.00 0.00
October 729.21 267.73 464.48 272.02 192.47 0.00 0.00
November 763.96 385.73 545.82 348.59 197.23 0.00 0.00
December 834.85 427.14 592.71 416.47 176.25 0.00 0.00
               
Annual Sum or Average 570.27 314.88 411.44 185.28 226.16 0.00 0.00
Minimum of Months 339.93 188.76 279.04 20.89 176.25 0.00 0.00
Maximum of Months 834.85 429.74 592.71 416.47 267.41 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.273556E+10 0.919112E+09 0.185314E+10 0.136048E+10 0.492663E+09 0.00 0.00
February 0.187187E+10 0.745236E+09 0.132217E+10 0.818116E+09 0.504052E+09 0.00 0.00
March 0.164869E+10 0.851687E+09 0.116748E+10 0.568705E+09 0.598776E+09 0.00 0.00
April 0.142852E+10 0.659237E+09 0.944769E+09 0.365158E+09 0.579611E+09 0.00 0.00
May 0.905167E+09 0.597207E+09 0.687861E+09 83301651.90 0.604559E+09 0.00 0.00
June 0.784202E+09 0.428736E+09 0.583982E+09 34251187.10 0.549731E+09 0.00 0.00
July 0.958664E+09 0.389723E+09 0.636401E+09 68053370.08 0.568348E+09 0.00 0.00
August 0.135382E+10 0.422674E+09 0.817369E+09 0.253989E+09 0.563379E+09 0.00 0.00
September 0.176606E+10 0.490195E+09 0.108621E+10 0.539619E+09 0.546586E+09 0.00 0.00
October 0.237794E+10 0.566976E+09 0.146973E+10 0.987033E+09 0.482692E+09 0.00 0.00
November 0.255973E+10 0.797858E+09 0.172768E+10 0.122410E+10 0.503575E+09 0.00 0.00
December 0.294077E+10 0.922702E+09 0.198311E+10 0.151118E+10 0.471925E+09 0.00 0.00
               
Annual Sum or Average 0.213310E+11 0.779134E+10 0.142799E+11 0.781399E+10 0.646590E+10 0.00 0.00
Minimum of Months 0.784202E+09 0.389723E+09 0.583982E+09 34251187.10 0.471925E+09 0.00 0.00
Maximum of Months 0.294077E+10 0.922702E+09 0.198311E+10 0.151118E+10 0.604559E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.759503E+10 0.282159E+10 0.521833E+10 0.383102E+10 0.138731E+10 0.00 0.00
February 0.517473E+10 0.231476E+10 0.372314E+10 0.230376E+10 0.141938E+10 0.00 0.00
March 0.454304E+10 0.262349E+10 0.328755E+10 0.160144E+10 0.168611E+10 0.00 0.00
April 0.393374E+10 0.205809E+10 0.266041E+10 0.102826E+10 0.163215E+10 0.00 0.00
May 0.244752E+10 0.187671E+10 0.193697E+10 0.234572E+09 0.170240E+10 0.00 0.00
June 0.211396E+10 0.137540E+10 0.164445E+10 96449084.55 0.154801E+10 0.00 0.00
July 0.262464E+10 0.123461E+10 0.179206E+10 0.191634E+09 0.160043E+10 0.00 0.00
August 0.375343E+10 0.132832E+10 0.230166E+10 0.715217E+09 0.158644E+10 0.00 0.00
September 0.490793E+10 0.153946E+10 0.305868E+10 0.151953E+10 0.153915E+10 0.00 0.00
October 0.661395E+10 0.176566E+10 0.413865E+10 0.277942E+10 0.135923E+10 0.00 0.00
November 0.710095E+10 0.246792E+10 0.486503E+10 0.344700E+10 0.141803E+10 0.00 0.00
December 0.816841E+10 0.283261E+10 0.558430E+10 0.425539E+10 0.132891E+10 0.00 0.00
               
Annual Sum or Average 0.589773E+11 0.242386E+11 0.402112E+11 0.220037E+11 0.182075E+11 0.00 0.00
Minimum of Months 0.211396E+10 0.123461E+10 0.164445E+10 96449084.55 0.132891E+10 0.00 0.00
Maximum of Months 0.816841E+10 0.283261E+10 0.558430E+10 0.425539E+10 0.170240E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.100944E+11 0.373843E+10 0.677891E+10 0.497672E+10 0.180219E+10 0.00 0.00
February 0.686944E+10 0.311419E+10 0.483657E+10 0.299272E+10 0.184385E+10 0.00 0.00
March 0.601789E+10 0.356013E+10 0.427071E+10 0.208036E+10 0.219036E+10 0.00 0.00
April 0.521532E+10 0.279706E+10 0.345602E+10 0.133577E+10 0.212025E+10 0.00 0.00
May 0.318818E+10 0.261172E+10 0.251623E+10 0.304722E+09 0.221151E+10 0.00 0.00
June 0.273880E+10 0.192996E+10 0.213624E+10 0.125293E+09 0.201095E+10 0.00 0.00
July 0.343739E+10 0.172135E+10 0.232799E+10 0.248943E+09 0.207905E+10 0.00 0.00
August 0.497422E+10 0.180452E+10 0.298998E+10 0.929108E+09 0.206087E+10 0.00 0.00
September 0.652059E+10 0.206588E+10 0.397340E+10 0.197396E+10 0.199944E+10 0.00 0.00
October 0.877761E+10 0.234175E+10 0.537634E+10 0.361063E+10 0.176572E+10 0.00 0.00
November 0.943251E+10 0.327788E+10 0.631995E+10 0.447785E+10 0.184211E+10 0.00 0.00
December 0.108481E+11 0.375159E+10 0.725432E+10 0.552799E+10 0.172633E+10 0.00 0.00
               
Annual Sum or Average 0.781145E+11 0.327145E+11 0.522367E+11 0.285840E+11 0.236526E+11 0.00 0.00
Minimum of Months 0.273880E+10 0.172135E+10 0.213624E+10 0.125293E+09 0.172633E+10 0.00 0.00
Maximum of Months 0.108481E+11 0.375159E+10 0.725432E+10 0.552799E+10 0.221151E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.873038E+09 0.518965E+09 0.631920E+09 0.402891E+09 0.229029E+09 0.00 0.00
February 0.717481E+09 0.423395E+09 0.547842E+09 0.294142E+09 0.253700E+09 0.00 0.00
March 0.778469E+09 0.486834E+09 0.593520E+09 0.272721E+09 0.320799E+09 0.00 0.00
April 0.966552E+09 0.365315E+09 0.670528E+09 0.323680E+09 0.346848E+09 0.00 0.00
May 0.854614E+09 0.335552E+09 0.627025E+09 0.242928E+09 0.384097E+09 0.00 0.00
June 0.892468E+09 0.232019E+09 0.618729E+09 0.258064E+09 0.360665E+09 0.00 0.00
July 0.104764E+10 0.200212E+09 0.676483E+09 0.307809E+09 0.368674E+09 0.00 0.00
August 0.108378E+10 0.211370E+09 0.678314E+09 0.330001E+09 0.348314E+09 0.00 0.00
September 0.100345E+10 0.249248E+09 0.643298E+09 0.335913E+09 0.307385E+09 0.00 0.00
October 0.100528E+10 0.293409E+09 0.630737E+09 0.381522E+09 0.249215E+09 0.00 0.00
November 0.893582E+09 0.444415E+09 0.637811E+09 0.397077E+09 0.240734E+09 0.00 0.00
December 0.922769E+09 0.515447E+09 0.661336E+09 0.442746E+09 0.218589E+09 0.00 0.00
               
Annual Sum or Average 0.110391E+11 0.427618E+10 0.761754E+10 0.398949E+10 0.362805E+10 0.00 0.00
Minimum of Months 0.717481E+09 0.200212E+09 0.547842E+09 0.242928E+09 0.218589E+09 0.00 0.00
Maximum of Months 0.108378E+10 0.518965E+09 0.678314E+09 0.442746E+09 0.384097E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.392394E+09 0.534434E+09 0.320905E+09 0.133901E+09 0.187004E+09 0.00 0.00
February 0.402489E+09 0.429409E+09 0.349219E+09 0.132386E+09 0.216833E+09 0.00 0.00
March 0.529913E+09 0.489458E+09 0.447889E+09 0.160279E+09 0.287610E+09 0.00 0.00
April 0.775850E+09 0.367715E+09 0.579223E+09 0.252251E+09 0.326972E+09 0.00 0.00
May 0.794176E+09 0.336548E+09 0.609729E+09 0.232648E+09 0.377081E+09 0.00 0.00
June 0.869041E+09 0.246477E+09 0.625037E+09 0.263322E+09 0.361715E+09 0.00 0.00
July 0.992992E+09 0.225158E+09 0.669847E+09 0.304467E+09 0.365379E+09 0.00 0.00
August 0.923152E+09 0.236459E+09 0.615807E+09 0.281984E+09 0.333823E+09 0.00 0.00
September 0.740186E+09 0.263646E+09 0.509491E+09 0.229238E+09 0.280253E+09 0.00 0.00
October 0.619351E+09 0.311423E+09 0.406496E+09 0.186368E+09 0.220128E+09 0.00 0.00
November 0.445169E+09 0.455489E+09 0.354356E+09 0.155051E+09 0.199305E+09 0.00 0.00
December 0.398547E+09 0.533417E+09 0.320798E+09 0.143959E+09 0.176839E+09 0.00 0.00
               
Annual Sum or Average 0.788326E+10 0.442963E+10 0.580880E+10 0.247585E+10 0.333294E+10 0.00 0.00
Minimum of Months 0.392394E+09 0.225158E+09 0.320798E+09 0.132386E+09 0.176839E+09 0.00 0.00
Maximum of Months 0.992992E+09 0.534434E+09 0.669847E+09 0.304467E+09 0.377081E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.403882E+09 0.209015E+09 0.293061E+09 0.215149E+09 77911467.45 0.00 0.00
February 0.266189E+09 0.177809E+09 0.209091E+09 0.129379E+09 79712592.74 0.00 0.00
March 0.226980E+09 0.201047E+09 0.184629E+09 89936327.87 94692605.60 0.00 0.00
April 0.192964E+09 0.162515E+09 0.149409E+09 57746850.06 91662135.38 0.00 0.00
May 0.104127E+09 0.153279E+09 0.108781E+09 13173513.96 95607483.13 0.00 0.00
June 86108758.40 0.117789E+09 92353413.13 5416561.15 86936851.98 0.00 0.00
July 0.115779E+09 0.107018E+09 0.100643E+09 10762115.76 89881160.52 0.00 0.00
August 0.182510E+09 0.112543E+09 0.129262E+09 40166453.60 89095338.36 0.00 0.00
September 0.251153E+09 0.126185E+09 0.171776E+09 85336561.19 86439337.30 0.00 0.00
October 0.347818E+09 0.139397E+09 0.232427E+09 0.156092E+09 76334792.12 0.00 0.00
November 0.375585E+09 0.185165E+09 0.273220E+09 0.193583E+09 79637126.46 0.00 0.00
December 0.436032E+09 0.208425E+09 0.313614E+09 0.238982E+09 74631825.39 0.00 0.00
               
Annual Sum or Average 0.298913E+10 0.190019E+10 0.225827E+10 0.123572E+10 0.102254E+10 0.00 0.00
Minimum of Months 86108758.40 0.107018E+09 92353413.13 5416561.15 74631825.39 0.00 0.00
Maximum of Months 0.436032E+09 0.209015E+09 0.313614E+09 0.238982E+09 95607483.13 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 34429030.77 0.154378E+09 44312955.30 0.00 44312955.30 0.00 0.00
February 36185647.17 0.124308E+09 50241522.13 0.00 50241522.13 0.00 0.00
March 57064302.36 0.141696E+09 68169765.21 624.22 68169140.99 0.00 0.00
April 79051900.17 0.100040E+09 76404816.42 614812.68 75790003.74 0.00 0.00
May 0.102564E+09 89940366.93 94978755.02 4953021.70 90025733.32 0.00 0.00
June 0.123665E+09 63954343.57 97431324.50 9625266.49 87806058.00 0.00 0.00
July 0.134315E+09 56665831.42 95367114.15 8092321.46 87274792.68 0.00 0.00
August 0.110022E+09 59188812.50 79292341.88 1761686.91 77530654.97 0.00 0.00
September 83365031.91 70326485.10 64772993.27 12882.05 64760111.22 0.00 0.00
October 75246115.35 84578663.03 53086943.81 0.00 53086943.81 0.00 0.00
November 39416776.62 0.129933E+09 46515858.69 0.00 46515858.69 0.00 0.00
December 31791562.81 0.153646E+09 41251595.16 0.00 41251595.16 0.00 0.00
               
Annual Sum or Average 0.907117E+09 0.122866E+10 0.811826E+09 25060615.52 0.786765E+09 0.00 0.00
Minimum of Months 31791562.81 56665831.42 41251595.16 0.00 41251595.16 0.00 0.00
Maximum of Months 0.134315E+09 0.154378E+09 97431324.50 9625266.49 90025733.32 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.885962E+09 0.508527E+09 0.645041E+09 0.417872E+09 0.227169E+09 0.00 0.00
February 0.675666E+09 0.412349E+09 0.526993E+09 0.283282E+09 0.243711E+09 0.00 0.00
March 0.758323E+09 0.470137E+09 0.589680E+09 0.272720E+09 0.316960E+09 0.00 0.00
April 0.892201E+09 0.351752E+09 0.629463E+09 0.294307E+09 0.335155E+09 0.00 0.00
May 0.753993E+09 0.325057E+09 0.566849E+09 0.196017E+09 0.370832E+09 0.00 0.00
June 0.755120E+09 0.229380E+09 0.530300E+09 0.186863E+09 0.343438E+09 0.00 0.00
July 0.947442E+09 0.199613E+09 0.611254E+09 0.254616E+09 0.356638E+09 0.00 0.00
August 0.102595E+10 0.206266E+09 0.641384E+09 0.305202E+09 0.336182E+09 0.00 0.00
September 0.860165E+09 0.243743E+09 0.553748E+09 0.262611E+09 0.291136E+09 0.00 0.00
October 0.947563E+09 0.283828E+09 0.599302E+09 0.353603E+09 0.245699E+09 0.00 0.00
November 0.846081E+09 0.434941E+09 0.613301E+09 0.379582E+09 0.233719E+09 0.00 0.00
December 0.915650E+09 0.506478E+09 0.662004E+09 0.449220E+09 0.212784E+09 0.00 0.00
               
Annual Sum or Average 0.102641E+11 0.417207E+10 0.716932E+10 0.365590E+10 0.351342E+10 0.00 0.00
Minimum of Months 0.675666E+09 0.199613E+09 0.526993E+09 0.186863E+09 0.212784E+09 0.00 0.00
Maximum of Months 0.102595E+10 0.508527E+09 0.662004E+09 0.449220E+09 0.370832E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.387842E+09 0.504884E+09 0.334026E+09 0.148882E+09 0.185144E+09 0.00 0.00
February 0.353754E+09 0.409566E+09 0.328370E+09 0.121526E+09 0.206844E+09 0.00 0.00
March 0.506124E+09 0.467114E+09 0.444049E+09 0.160278E+09 0.283771E+09 0.00 0.00
April 0.705458E+09 0.350679E+09 0.538158E+09 0.222878E+09 0.315280E+09 0.00 0.00
May 0.700282E+09 0.325083E+09 0.549554E+09 0.185737E+09 0.363816E+09 0.00 0.00
June 0.737821E+09 0.235597E+09 0.536608E+09 0.192121E+09 0.344488E+09 0.00 0.00
July 0.895693E+09 0.214395E+09 0.604618E+09 0.251275E+09 0.353343E+09 0.00 0.00
August 0.867192E+09 0.224002E+09 0.578877E+09 0.257186E+09 0.321691E+09 0.00 0.00
September 0.600732E+09 0.252669E+09 0.419941E+09 0.155935E+09 0.264005E+09 0.00 0.00
October 0.556864E+09 0.294216E+09 0.375061E+09 0.158449E+09 0.216611E+09 0.00 0.00
November 0.388394E+09 0.432954E+09 0.329845E+09 0.137555E+09 0.192290E+09 0.00 0.00
December 0.371725E+09 0.503430E+09 0.321466E+09 0.150433E+09 0.171033E+09 0.00 0.00
               
Annual Sum or Average 0.707188E+10 0.421459E+10 0.536057E+10 0.214226E+10 0.321832E+10 0.00 0.00
Minimum of Months 0.353754E+09 0.214395E+09 0.321466E+09 0.121526E+09 0.171033E+09 0.00 0.00
Maximum of Months 0.895693E+09 0.504884E+09 0.604618E+09 0.257186E+09 0.363816E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.100584E+10 0.653180E+09 0.730978E+09 0.466169E+09 0.264809E+09 0.00 0.00
February 0.713838E+09 0.542643E+09 0.561883E+09 0.280328E+09 0.281555E+09 0.00 0.00
March 0.690555E+09 0.622404E+09 0.547718E+09 0.194868E+09 0.352850E+09 0.00 0.00
April 0.665378E+09 0.470076E+09 0.489246E+09 0.126453E+09 0.362793E+09 0.00 0.00
May 0.522928E+09 0.428195E+09 0.441454E+09 39273247.18 0.402181E+09 0.00 0.00
June 0.527409E+09 0.304625E+09 0.411173E+09 32587736.49 0.378585E+09 0.00 0.00
July 0.612056E+09 0.277285E+09 0.424663E+09 40849193.83 0.383814E+09 0.00 0.00
August 0.700478E+09 0.299542E+09 0.451848E+09 90845939.63 0.361002E+09 0.00 0.00
September 0.790379E+09 0.348142E+09 0.512511E+09 0.184929E+09 0.327582E+09 0.00 0.00
October 0.974999E+09 0.407137E+09 0.618608E+09 0.338207E+09 0.280400E+09 0.00 0.00
November 0.953823E+09 0.574852E+09 0.692760E+09 0.419440E+09 0.273320E+09 0.00 0.00
December 0.106315E+10 0.657977E+09 0.768878E+09 0.517807E+09 0.251071E+09 0.00 0.00
               
Annual Sum or Average 0.922083E+10 0.558606E+10 0.665172E+10 0.273176E+10 0.391996E+10 0.00 0.00
Minimum of Months 0.522928E+09 0.277285E+09 0.411173E+09 32587736.49 0.251071E+09 0.00 0.00
Maximum of Months 0.106315E+10 0.657977E+09 0.768878E+09 0.517807E+09 0.402181E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.868437E+09 0.511760E+09 0.631920E+09 0.402891E+09 0.229029E+09 0.00 0.00
February 0.711570E+09 0.417058E+09 0.547842E+09 0.294142E+09 0.253700E+09 0.00 0.00
March 0.769738E+09 0.482193E+09 0.593520E+09 0.272721E+09 0.320799E+09 0.00 0.00
April 0.953350E+09 0.362171E+09 0.670528E+09 0.323680E+09 0.346848E+09 0.00 0.00
May 0.841436E+09 0.332753E+09 0.627025E+09 0.242928E+09 0.384097E+09 0.00 0.00
June 0.879011E+09 0.229890E+09 0.618729E+09 0.258064E+09 0.360665E+09 0.00 0.00
July 0.103442E+10 0.197841E+09 0.676483E+09 0.307809E+09 0.368674E+09 0.00 0.00
August 0.107097E+10 0.208588E+09 0.678314E+09 0.330001E+09 0.348314E+09 0.00 0.00
September 0.992299E+09 0.245478E+09 0.643298E+09 0.335913E+09 0.307385E+09 0.00 0.00
October 0.998114E+09 0.287511E+09 0.630737E+09 0.381522E+09 0.249215E+09 0.00 0.00
November 0.887819E+09 0.437234E+09 0.637811E+09 0.397077E+09 0.240734E+09 0.00 0.00
December 0.918953E+09 0.506819E+09 0.661336E+09 0.442746E+09 0.218589E+09 0.00 0.00
               
Annual Sum or Average 0.109261E+11 0.421930E+10 0.761754E+10 0.398949E+10 0.362805E+10 0.00 0.00
Minimum of Months 0.711570E+09 0.197841E+09 0.547842E+09 0.242928E+09 0.218589E+09 0.00 0.00
Maximum of Months 0.107097E+10 0.511760E+09 0.678314E+09 0.442746E+09 0.384097E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.392574E+09 0.523049E+09 0.320905E+09 0.133901E+09 0.187004E+09 0.00 0.00
February 0.400868E+09 0.420862E+09 0.349219E+09 0.132386E+09 0.216833E+09 0.00 0.00
March 0.523607E+09 0.484179E+09 0.447889E+09 0.160279E+09 0.287610E+09 0.00 0.00
April 0.762451E+09 0.366951E+09 0.579223E+09 0.252251E+09 0.326972E+09 0.00 0.00
May 0.779300E+09 0.336580E+09 0.609729E+09 0.232648E+09 0.377081E+09 0.00 0.00
June 0.850956E+09 0.250439E+09 0.625037E+09 0.263322E+09 0.361715E+09 0.00 0.00
July 0.975112E+09 0.230476E+09 0.669847E+09 0.304467E+09 0.365379E+09 0.00 0.00
August 0.908327E+09 0.240389E+09 0.615807E+09 0.281984E+09 0.333823E+09 0.00 0.00
September 0.730285E+09 0.262106E+09 0.509491E+09 0.229238E+09 0.280253E+09 0.00 0.00
October 0.616263E+09 0.304580E+09 0.406496E+09 0.186368E+09 0.220128E+09 0.00 0.00
November 0.444830E+09 0.444749E+09 0.354356E+09 0.155051E+09 0.199305E+09 0.00 0.00
December 0.400694E+09 0.519830E+09 0.320798E+09 0.143959E+09 0.176839E+09 0.00 0.00
               
Annual Sum or Average 0.778527E+10 0.438419E+10 0.580880E+10 0.247585E+10 0.333294E+10 0.00 0.00
Minimum of Months 0.392574E+09 0.230476E+09 0.320798E+09 0.132386E+09 0.176839E+09 0.00 0.00
Maximum of Months 0.975112E+09 0.523049E+09 0.669847E+09 0.304467E+09 0.377081E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.789075E+09 0.267842E+09 0.537359E+09 0.394500E+09 0.142859E+09 0.00 0.00
February 0.532951E+09 0.218153E+09 0.383392E+09 0.237230E+09 0.146162E+09 0.00 0.00
March 0.466431E+09 0.253231E+09 0.338537E+09 0.164908E+09 0.173629E+09 0.00 0.00
April 0.405949E+09 0.189010E+09 0.273958E+09 0.105885E+09 0.168073E+09 0.00 0.00
May 0.252048E+09 0.173284E+09 0.199462E+09 24155080.95 0.175307E+09 0.00 0.00
June 0.222605E+09 0.118079E+09 0.169340E+09 9931858.23 0.159408E+09 0.00 0.00
July 0.280419E+09 99281129.80 0.184540E+09 19733518.19 0.164807E+09 0.00 0.00
August 0.397664E+09 0.104683E+09 0.237016E+09 73649592.75 0.163366E+09 0.00 0.00
September 0.514004E+09 0.126419E+09 0.314970E+09 0.156474E+09 0.158496E+09 0.00 0.00
October 0.692787E+09 0.146866E+09 0.426179E+09 0.286211E+09 0.139968E+09 0.00 0.00
November 0.737660E+09 0.227937E+09 0.500979E+09 0.354955E+09 0.146023E+09 0.00 0.00
December 0.849091E+09 0.265771E+09 0.575045E+09 0.438199E+09 0.136846E+09 0.00 0.00
               
Annual Sum or Average 0.614068E+10 0.219056E+10 0.414078E+10 0.226583E+10 0.187494E+10 0.00 0.00
Minimum of Months 0.222605E+09 99281129.80 0.169340E+09 9931858.23 0.136846E+09 0.00 0.00
Maximum of Months 0.849091E+09 0.267842E+09 0.575045E+09 0.438199E+09 0.175307E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.214931E+09 0.163035E+10 0.387672E+09 0.00 0.387672E+09 0.00 0.00
February 0.226228E+09 0.135756E+10 0.439538E+09 0.00 0.439538E+09 0.00 0.00
March 0.383566E+09 0.152050E+10 0.596384E+09 5460.98 0.596378E+09 0.00 0.00
April 0.553527E+09 0.110003E+10 0.668428E+09 5378694.26 0.663050E+09 0.00 0.00
May 0.728954E+09 0.983134E+09 0.830922E+09 43331554.67 0.787591E+09 0.00 0.00
June 0.928518E+09 0.709632E+09 0.852379E+09 84206730.00 0.768172E+09 0.00 0.00
July 0.102982E+10 0.631185E+09 0.834320E+09 70795746.72 0.763524E+09 0.00 0.00
August 0.825330E+09 0.678339E+09 0.693690E+09 15412133.73 0.678278E+09 0.00 0.00
September 0.610184E+09 0.808543E+09 0.566667E+09 112698.72 0.566554E+09 0.00 0.00
October 0.551343E+09 0.960916E+09 0.464432E+09 0.00 0.464432E+09 0.00 0.00
November 0.249774E+09 0.140884E+10 0.406944E+09 0.00 0.406944E+09 0.00 0.00
December 0.191617E+09 0.163317E+10 0.360890E+09 0.00 0.360890E+09 0.00 0.00
               
Annual Sum or Average 0.649379E+10 0.134222E+11 0.710227E+10 0.219243E+09 0.688302E+10 0.00 0.00
Minimum of Months 0.191617E+09 0.631185E+09 0.360890E+09 0.00 0.360890E+09 0.00 0.00
Maximum of Months 0.102982E+10 0.163317E+10 0.852379E+09 84206730.00 0.787591E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.193938E+09 0.168781E+10 0.387672E+09 0.00 0.387672E+09 0.00 0.00
February 0.204366E+09 0.140874E+10 0.439538E+09 0.00 0.439538E+09 0.00 0.00
March 0.354207E+09 0.157328E+10 0.596384E+09 5460.98 0.596378E+09 0.00 0.00
April 0.520387E+09 0.113674E+10 0.668428E+09 5378694.26 0.663050E+09 0.00 0.00
May 0.688334E+09 0.101366E+10 0.830922E+09 43331554.67 0.787591E+09 0.00 0.00
June 0.892540E+09 0.733428E+09 0.852379E+09 84206730.00 0.768172E+09 0.00 0.00
July 0.997246E+09 0.652480E+09 0.834320E+09 70795746.72 0.763524E+09 0.00 0.00
August 0.795691E+09 0.702455E+09 0.693690E+09 15412133.73 0.678278E+09 0.00 0.00
September 0.583486E+09 0.839505E+09 0.566667E+09 112698.72 0.566554E+09 0.00 0.00
October 0.527463E+09 0.996212E+09 0.464432E+09 0.00 0.464432E+09 0.00 0.00
November 0.227911E+09 0.145795E+10 0.406944E+09 0.00 0.406944E+09 0.00 0.00
December 0.171607E+09 0.168941E+10 0.360890E+09 0.00 0.360890E+09 0.00 0.00
               
Annual Sum or Average 0.615718E+10 0.138917E+11 0.710227E+10 0.219243E+09 0.688302E+10 0.00 0.00
Minimum of Months 0.171607E+09 0.652480E+09 0.360890E+09 0.00 0.360890E+09 0.00 0.00
Maximum of Months 0.997246E+09 0.168941E+10 0.852379E+09 84206730.00 0.787591E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.138253E+10 0.107376E+10 0.979027E+09 0.566733E+09 0.412294E+09 0.00 0.00
February 0.110706E+10 0.929953E+09 0.855325E+09 0.404791E+09 0.450534E+09 0.00 0.00
March 0.136961E+10 0.105667E+10 0.103368E+10 0.432976E+09 0.600702E+09 0.00 0.00
April 0.176036E+10 0.797698E+09 0.116756E+10 0.517154E+09 0.650404E+09 0.00 0.00
May 0.162432E+10 0.759585E+09 0.111634E+10 0.381729E+09 0.734613E+09 0.00 0.00
June 0.169323E+10 0.555569E+09 0.106685E+10 0.378958E+09 0.687892E+09 0.00 0.00
July 0.209139E+10 0.490576E+09 0.121580E+10 0.505857E+09 0.709947E+09 0.00 0.00
August 0.213464E+10 0.509584E+09 0.122019E+10 0.562352E+09 0.657842E+09 0.00 0.00
September 0.164645E+10 0.559274E+09 0.973640E+09 0.418524E+09 0.555116E+09 0.00 0.00
October 0.168478E+10 0.641836E+09 0.974319E+09 0.512030E+09 0.462289E+09 0.00 0.00
November 0.134188E+10 0.931109E+09 0.943108E+09 0.517117E+09 0.425991E+09 0.00 0.00
December 0.139348E+10 0.107298E+10 0.983432E+09 0.599632E+09 0.383800E+09 0.00 0.00
               
Annual Sum or Average 0.192297E+11 0.937859E+10 0.125293E+11 0.579785E+10 0.673142E+10 0.00 0.00
Minimum of Months 0.110706E+10 0.490576E+09 0.855325E+09 0.378958E+09 0.383800E+09 0.00 0.00
Maximum of Months 0.213464E+10 0.107376E+10 0.122019E+10 0.599632E+09 0.734613E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.209672E+10 0.115101E+10 0.150077E+10 0.100422E+10 0.496551E+09 0.00 0.00
February 0.145782E+10 0.954978E+09 0.112662E+10 0.603882E+09 0.522737E+09 0.00 0.00
March 0.135424E+10 0.111153E+10 0.106621E+10 0.419784E+09 0.646422E+09 0.00 0.00
April 0.125513E+10 0.847371E+09 0.926512E+09 0.271380E+09 0.655132E+09 0.00 0.00
May 0.912340E+09 0.773279E+09 0.792583E+09 76342183.92 0.716240E+09 0.00 0.00
June 0.881090E+09 0.557238E+09 0.723261E+09 54148304.57 0.669113E+09 0.00 0.00
July 0.104713E+10 0.505571E+09 0.755764E+09 74501639.64 0.681262E+09 0.00 0.00
August 0.128267E+10 0.545077E+09 0.841134E+09 0.192762E+09 0.648372E+09 0.00 0.00
September 0.152769E+10 0.623203E+09 0.996027E+09 0.398351E+09 0.597676E+09 0.00 0.00
October 0.195311E+10 0.717093E+09 0.124407E+10 0.728566E+09 0.515505E+09 0.00 0.00
November 0.198019E+10 0.999800E+09 0.141477E+10 0.903557E+09 0.511212E+09 0.00 0.00
December 0.223606E+10 0.114404E+10 0.158752E+10 0.111546E+10 0.472062E+09 0.00 0.00
               
Annual Sum or Average 0.179842E+11 0.993018E+10 0.129752E+11 0.584296E+10 0.713228E+10 0.00 0.00
Minimum of Months 0.881090E+09 0.505571E+09 0.723261E+09 54148304.57 0.472062E+09 0.00 0.00
Maximum of Months 0.223606E+10 0.115101E+10 0.158752E+10 0.111546E+10 0.716240E+09 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 13.22 9.61 5.99 2.23 0.81 45.19 208.20 0.00
February 13.28 10.20 7.03 3.12 2.96 66.07 175.60 0.04
March 12.64 10.61 8.97 2.93 3.55 84.90 179.28 0.03
April 15.30 12.62 10.61 2.62 4.76 81.20 282.81 0.02
May 15.56 12.65 10.56 2.92 6.17 105.80 234.18 0.01
June 17.67 14.80 13.02 2.53 9.03 98.05 261.27 0.00
July 19.43 16.76 15.28 2.35 9.62 86.54 312.15 0.00
August 19.66 17.23 15.95 2.55 9.62 74.58 307.55 0.00
September 18.47 15.50 13.65 2.19 8.99 70.75 240.05 0.00
October 18.77 13.72 9.60 2.71 7.74 53.88 216.36 0.00
November 14.32 10.43 6.22 2.47 2.41 50.75 207.87 0.01
December 13.59 8.82 3.19 2.50 0.05 39.49 221.83 0.00
                 
Annual Sum or Average 16.01 12.76 10.02 2.59 5.49 71.44 237.65 0.01
Minimum of Months 12.64 8.82 3.19 2.19 0.05 39.49 175.60 0.00
Maximum of Months 19.66 17.23 15.95 3.12 9.62 105.80 312.15 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 26.00 13-JAN-13:00 15.46 8.00 3.10 11.84 120.00 725.00
February 26.00 01-FEB-11:00 14.67 6.00 4.10 10.11 166.00 715.50
March 24.00 11-MAR-10:00 13.82 6.00 2.60 8.15 120.00 907.00
April 27.00 26-APR-12:00 17.13 11.00 4.10 12.22 159.00 884.00
May 24.00 03-MAY-11:00 15.05 9.00 4.10 12.98 187.00 842.50
June 25.00 29-JUN-10:00 19.59 17.00 4.60 11.65 177.50 829.00
July 28.00 19-JUL-10:00 20.49 17.00 3.60 14.65 173.00 813.00
August 28.00 14-AUG-10:00 21.19 18.00 3.60 14.84 148.00 840.00
September 36.00 29-SEP-10:00 17.91 5.00 3.60 19.35 159.50 790.00
October 37.00 16-OCT-10:00 17.87 4.00 5.70 20.05 122.00 871.50
November 27.00 19-NOV-12:00 14.96 6.00 4.10 11.07 128.50 796.00
December 26.00 05-DEC-09:00 13.09 1.00 3.60 8.94 75.50 857.00
                 
Annual Sum or Average                
Minimum of Months 24.00   13.09 1.00 2.60 8.15 75.50 715.50
Maximum of Months 37.00   21.19 18.00 5.70 20.05 187.00 907.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 1.00 08-JAN-06:00 -0.3 -2.0 3.10 -15.5 11.50 193.50
February 5.00 04-FEB-05:00 0.22 -8.0 4.10 -10.9 0.00 0.00
March 4.00 07-MAR-04:00 3.53 3.00 0.00 -11.4 0.00 0.00
April 7.00 01-APR-05:00 4.33 1.00 4.10 -9.0 23.50 211.00
May 8.00 14-MAY-03:00 7.45 7.00 1.50 -6.6 0.00 0.00
June 11.00 13-JUN-03:00 9.85 9.00 2.10 -3.4 0.00 0.00
July 13.00 06-JUL-00:00 13.00 13.00 0.00 -0.6 0.00 0.00
August 14.00 24-AUG-01:00 14.00 14.00 0.00 0.51 0.00 0.00
September 11.00 20-SEP-02:00 9.85 9.00 1.50 -3.4 0.00 0.00
October 9.00 12-OCT-04:00 6.56 4.00 3.10 -6.4 0.00 0.00
November 7.00 05-NOV-01:00 5.54 4.00 3.10 -8.3 0.00 0.00
December 5.00 03-DEC-00:00 5.00 5.00 2.10 -0.4 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 1.00   -0.3 -8.0 0.00 -15.5 0.00 0.00
Maximum of Months 14.00   14.00 14.00 4.10 0.51 23.50 211.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 17.04 17-JAN-11:00 24.00 13.00 3.10 12.79 223.50 9.00
February 16.80 11-FEB-13:00 18.00 16.20 1.10 15.02 241.00 12.50
March 17.41 22-MAR-12:00 22.00 15.00 3.10 8.35 145.50 876.00
April 18.33 26-APR-10:00 26.00 14.00 4.10 12.03 141.50 915.50
May 16.69 05-MAY-14:00 18.00 16.00 5.10 8.74 303.50 269.00
June 19.59 29-JUN-10:00 25.00 17.00 4.60 11.65 177.50 829.00
July 21.19 19-JUL-11:00 28.00 18.00 4.60 14.84 182.50 808.00
August 21.20 18-AUG-11:00 28.00 18.00 3.60 17.21 244.00 667.50
September 21.85 22-SEP-11:00 26.00 20.00 2.60 20.05 284.00 21.00
October 21.09 01-OCT-11:00 26.00 19.00 3.60 13.16 102.00 899.50
November 16.52 10-NOV-12:00 21.00 14.00 5.10 7.15 131.00 808.50
December 15.64 07-DEC-12:00 20.00 13.00 5.10 5.94 89.00 868.50
                 
Annual Sum or Average                
Minimum of Months 15.64   18.00 13.00 1.10 5.94 89.00 9.00
Maximum of Months 21.85   28.00 20.00 5.10 20.05 303.50 915.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.00 17-JAN-12:00 22.00 16.85 2.10 11.65 241.50 67.50
February 16.20 11-FEB-13:00 18.00 16.80 1.10 15.02 241.00 12.50
March 15.00 23-MAR-15:20 21.67 17.34 3.77 8.02 112.00 809.83
April 15.00 26-APR-21:19 16.00 15.39 2.23 6.15 0.00 0.00
May 16.00 05-MAY-14:00 18.00 16.69 5.10 8.74 303.50 269.00
June 17.00 28-JUN-08:00 19.00 17.66 1.50 16.12 285.00 428.50
July 18.00 18-JUL-10:00 26.00 20.47 4.60 12.79 169.00 819.00
August 18.10 14-AUG-09:00 26.90 20.93 3.40 13.73 139.00 817.00
September 20.00 22-SEP-09:00 22.00 20.55 1.50 16.30 296.00 18.00
October 19.00 01-OCT-07:10 19.17 19.06 0.25 16.82 53.33 0.00
November 15.00 10-NOV-17:19 16.67 15.62 2.77 3.34 0.00 0.00
December 13.00 07-DEC-12:00 20.00 15.64 5.10 5.94 89.00 868.50
                 
Annual Sum or Average                
Minimum of Months 13.00   16.00 15.39 0.25 3.34 0.00 0.00
Maximum of Months 20.00   26.90 20.93 5.10 16.82 303.50 868.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 17.43 27.46 0.00
February 18.00 13.00 16.00 17.38 30.87 0.00
March 18.00 13.00 16.00 17.83 38.09 0.00
April 18.00 13.00 16.00 18.69 55.75 0.00
May 18.00 13.00 16.00 19.73 55.13 0.00
June 18.00 13.00 16.00 20.65 58.21 0.00
July 18.00 13.00 16.00 21.22 63.49 0.00
August 18.00 13.00 16.00 21.28 59.02 0.00
September 18.00 13.00 16.00 20.81 46.26 0.00
October 18.00 13.00 16.00 19.94 34.64 0.00
November 18.00 13.00 16.00 18.91 29.25 0.00
December 18.00 13.00 16.00 17.99 26.27 0.00
             
Annual Sum or Average 18.00 13.00 16.00 19.33 43.77 0.00
Minimum of Months 18.00 13.00 16.00 17.38 26.27 0.00
Maximum of Months 18.00 13.00 16.00 21.28 63.49 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770520E+10 -0.754278E+10 0.00 0.00 744.00 0.00 -162420451.8 81.21 0.00 0.00
February 0.696254E+10 -0.681597E+10 0.00 0.00 672.00 0.00 -146565333.1 81.21 0.00 0.00
March 0.770382E+10 -0.754147E+10 0.00 0.00 744.00 0.00 -162346752.0 81.21 0.00 0.00
April 0.746551E+10 -0.730859E+10 0.00 0.00 720.00 0.00 -156913760.9 81.21 0.00 0.00
May 0.770493E+10 -0.754281E+10 0.00 0.00 744.00 0.00 -162122149.0 81.21 0.00 0.00
June 0.745732E+10 -0.730054E+10 0.00 0.00 720.00 0.00 -156776567.9 81.21 0.00 0.00
July 0.771280E+10 -0.755087E+10 0.00 0.00 744.00 0.00 -161929683.2 81.21 0.00 0.00
August 0.770473E+10 -0.754282E+10 0.00 0.00 744.00 0.00 -161914552.8 81.21 0.00 0.00
September 0.746671E+10 -0.730995E+10 0.00 0.00 720.00 0.00 -156759874.7 81.21 0.00 0.00
October 0.770346E+10 -0.754144E+10 0.00 0.00 744.00 0.00 -162019322.6 81.21 0.00 0.00
November 0.744944E+10 -0.729243E+10 0.00 0.00 720.00 0.00 -157003793.4 81.21 0.00 0.00
December 0.771317E+10 -0.755086E+10 0.00 0.00 744.00 0.00 -162308775.9 81.21 0.00 0.00
                     
Annual Sum or Average 0.907496E+11 -0.888405E+11 0.00 0.00 8760.00 0.00 -0.190908E+10 81.21 0.00 0.00
Minimum of Months 0.696254E+10 -0.755087E+10 0.00 0.00 672.00 0.00 -162420451.8 81.21 0.00 0.00
Maximum of Months 0.771317E+10 -0.681597E+10 0.00 0.00 744.00 0.00 -146565333.1 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYSLAUNDRY HPWH TANK

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.392331E+11 -0.106704E+12 0.00 0.00 744.00 0.00 -787601211.6 81.67 0.00 0.00
February 0.348996E+11 -0.964486E+11 0.00 0.00 672.00 0.00 -710257027.3 81.67 0.00 0.00
March 0.379360E+11 -0.106015E+12 0.00 0.00 744.00 0.00 -791322928.9 81.68 0.00 0.00
April 0.323458E+11 -0.101188E+12 0.00 0.00 720.00 0.00 -746554523.0 81.67 0.00 0.00
May 0.316002E+11 -0.102814E+12 0.00 0.00 744.00 0.00 -768941402.3 81.67 0.00 0.00
June 0.262699E+11 -0.979800E+11 0.00 0.00 720.00 0.00 -728513761.2 81.68 0.00 0.00
July 0.237001E+11 -0.100282E+12 0.00 0.00 744.00 0.00 -739150471.2 81.68 0.00 0.00
August 0.228695E+11 -0.100183E+12 0.00 0.00 744.00 0.00 -737921488.2 81.68 0.00 0.00
September 0.250372E+11 -0.977202E+11 0.00 0.00 720.00 0.00 -722516812.0 81.68 0.00 0.00
October 0.286270E+11 -0.102449E+12 0.00 0.00 744.00 0.00 -744166351.3 81.68 0.00 0.00
November 0.344538E+11 -0.100835E+12 0.00 0.00 720.00 0.00 -753775111.3 81.67 0.00 0.00
December 0.389424E+11 -0.105750E+12 0.00 0.00 744.00 0.00 -783872080.2 81.67 0.00 0.00
                     
Annual Sum or Average 0.375915E+12 -0.121837E+13 0.00 0.00 8760.00 0.00 -0.901459E+10 81.67 0.00 0.00
Minimum of Months 0.228695E+11 -0.106704E+12 0.00 0.00 672.00 0.00 -791322928.9 81.67 0.00 0.00
Maximum of Months 0.392331E+11 -0.964486E+11 0.00 0.00 744.00 0.00 -710257027.3 81.68 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 HPWH TANK

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January -0.241249E+10 -0.621486E+11 0.00 0.00 744.00 0.00 -0.122219E+10 59.34 0.00 0.00
February -0.219412E+10 -0.562069E+11 0.00 0.00 672.00 0.00 -0.110123E+10 59.34 0.00 0.00
March -0.240630E+10 -0.616095E+11 0.00 0.00 744.00 0.00 -0.123139E+10 59.35 0.00 0.00
April -0.233235E+10 -0.583781E+11 0.00 0.00 720.00 0.00 -0.114592E+10 59.37 0.00 0.00
May -0.234404E+10 -0.588259E+11 0.00 0.00 744.00 0.00 -0.117869E+10 59.38 0.00 0.00
June -0.232712E+10 -0.556432E+11 0.00 0.00 720.00 0.00 -0.110341E+10 59.40 0.00 0.00
July -0.249305E+10 -0.566117E+11 0.00 0.00 744.00 0.00 -0.110713E+10 59.39 0.00 0.00
August -0.250877E+10 -0.565835E+11 0.00 0.00 744.00 0.00 -0.110401E+10 59.38 0.00 0.00
September -0.239212E+10 -0.553921E+11 0.00 0.00 720.00 0.00 -0.108864E+10 59.38 0.00 0.00
October -0.243812E+10 -0.584812E+11 0.00 0.00 744.00 0.00 -0.111920E+10 59.39 0.00 0.00
November -0.222809E+10 -0.580478E+11 0.00 0.00 720.00 0.00 -0.116334E+10 59.37 0.00 0.00
December -0.233055E+10 -0.613220E+11 0.00 0.00 744.00 0.00 -0.121352E+10 59.35 0.00 0.00
                     
Annual Sum or Average -0.284071E+11 -0.699251E+12 0.00 0.00 8760.00 0.00 -0.137787E+11 59.37 0.00 0.00
Minimum of Months -0.250877E+10 -0.621486E+11 0.00 0.00 672.00 0.00 -0.123139E+10 59.34 0.00 0.00
Maximum of Months -0.219412E+10 -0.553921E+11 0.00 0.00 744.00 0.00 -0.108864E+10 59.40 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: LOBBY_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.87 0.86 01-JAN-07:19 6411.39 37.26 284.83 280.00 922.74 26.85 188.50 262.67
February 279.67 0.87 0.86 01-FEB-07:19 4458.45 31.97 218.17 274.67 609.14 23.53 166.67 242.83
March 338.17 0.87 0.86 01-MAR-07:30 1168.52 19.66 14.00 320.33 435.63 20.93 153.50 258.00
April 358.33 0.87 0.86 01-APR-07:19 803.80 19.17 0.00 332.33 339.22 20.93 142.83 259.50
May 393.83 0.87 0.86 01-MAY-06:00 730.15 18.66 0.00 363.33 297.49 20.40 116.67 254.50
June 381.00 0.87 0.86 01-JUN-06:00 631.55 18.47 0.00 354.33 265.96 20.23 65.50 229.17
July 408.67 0.87 0.86 01-JUL-07:40 622.22 18.59 0.00 363.67 271.55 20.36 95.83 243.00
August 390.67 0.87 0.86 01-AUG-07:40 676.69 18.85 0.00 353.33 294.84 20.61 140.67 263.83
September 328.83 0.87 0.86 01-SEP-07:10 908.83 19.16 0.00 308.00 378.48 20.94 142.83 252.67
October 296.17 0.87 0.86 01-OCT-09:39 3075.66 27.00 136.33 304.17 448.06 21.45 101.83 248.00
November 300.00 0.87 0.86 01-NOV-06:49 6241.58 37.10 294.67 280.17 808.97 26.43 201.33 266.83
December 297.00 0.87 0.86 01-DEC-07:19 6274.56 37.68 289.17 280.67 1131.34 28.40 185.67 265.33
                         
Annual Sum or Average 4065.67 0.87     2411.25 24.44 1237.17 3815.00 489.56 22.32 1701.83 3046.33
Minimum of Months 279.67 0.87 0.86   622.22 18.47 0.00 274.67 265.96 20.23 65.50 229.17
Maximum of Months 408.67 0.87 0.86   6411.39 37.68 294.67 363.67 1131.34 28.40 201.33 266.83



Table of Contents

Report: DaylightingReportMonthly

For: CAFE_FLR_1_DAYLCTRL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.24 0.22 01-JAN-07:19 6782.76 37.34 285.00 284.67 1295.92 26.60 174.33 272.50
February 279.67 0.25 0.22 01-FEB-07:19 4753.37 32.08 218.50 281.50 903.67 23.62 167.33 262.00
March 338.17 0.27 0.22 01-MAR-07:10 1396.04 20.17 29.67 328.67 662.32 21.27 185.33 298.33
April 358.33 0.26 0.22 01-APR-06:40 987.44 19.80 14.67 345.50 522.42 21.35 195.83 313.00
May 393.83 0.26 0.22 01-MAY-06:30 860.02 19.52 0.00 378.50 426.94 21.03 208.50 339.17
June 381.00 0.27 0.22 01-JUN-06:30 748.47 19.36 0.00 367.83 382.50 20.89 196.83 329.50
July 408.67 0.27 0.22 01-JUL-06:10 745.77 19.44 0.00 377.17 394.74 20.98 246.67 344.50
August 390.67 0.27 0.22 01-AUG-06:00 830.15 19.56 0.17 367.17 447.92 21.11 208.33 333.83
September 328.83 0.26 0.22 01-SEP-06:49 1128.27 19.66 18.17 321.33 597.42 21.26 157.83 289.33
October 296.17 0.25 0.22 01-OCT-09:39 3376.77 27.08 137.00 315.83 747.20 21.45 102.67 281.00
November 300.00 0.26 0.22 01-NOV-06:40 6591.11 37.15 294.83 285.83 1155.94 26.24 191.83 275.17
December 297.00 0.25 0.22 01-DEC-07:10 6661.12 37.76 289.17 286.50 1517.25 28.09 172.00 275.67
                         
Annual Sum or Average 4065.67 0.26     2637.86 24.92 1287.17 3940.50 715.59 22.60 2207.50 3614.00
Minimum of Months 279.67 0.24 0.22   745.77 19.36 0.00 281.50 382.50 20.89 102.67 262.00
Maximum of Months 408.67 0.27 0.22   6782.76 37.76 294.83 378.50 1517.25 28.09 246.67 344.50



Table of Contents

Report: DaylightingReportMonthly

For: DINING_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.67 0.60 01-JAN-09:09 301.36 14.31 0.00 238.83 156.01 17.88 0.00 33.67
February 279.67 0.65 0.60 01-FEB-09:09 376.92 15.19 0.00 255.67 180.84 18.52 0.00 90.33
March 338.17 0.64 0.60 01-MAR-09:30 451.38 15.76 0.00 313.17 207.38 18.97 0.00 177.17
April 358.33 0.62 0.60 01-APR-07:30 475.61 16.70 0.00 343.00 232.82 19.97 14.00 269.17
May 393.83 0.62 0.60 01-MAY-06:40 639.55 17.65 12.50 386.67 287.88 20.86 61.17 345.50
June 381.00 0.61 0.60 01-JUN-06:40 677.31 19.68 58.83 380.83 313.34 22.08 109.67 340.17
July 408.67 0.62 0.60 01-JUL-05:49 615.82 18.94 44.67 390.00 271.44 20.54 86.50 357.83
August 390.67 0.62 0.60 01-AUG-07:10 487.91 16.78 0.00 370.33 234.53 20.07 34.00 297.17
September 328.83 0.63 0.60 01-SEP-06:00 419.01 16.05 0.00 310.83 208.00 19.34 0.00 183.50
October 296.17 0.67 0.60 01-OCT-09:39 312.26 14.67 0.00 253.17 158.55 18.12 0.00 56.50
November 300.00 0.67 0.60 01-NOV-08:09 309.11 14.12 0.00 243.67 157.57 17.57 0.00 51.67
December 297.00 0.68 0.60 01-DEC-08:50 271.81 13.78 0.00 229.83 144.72 17.41 0.00 19.33
                         
Annual Sum or Average 4065.67 0.64     460.64 16.35 116.00 3716.00 219.11 19.44 305.33 2222.00
Minimum of Months 279.67 0.61 0.60   271.81 13.78 0.00 229.83 144.72 17.41 0.00 19.33
Maximum of Months 408.67 0.68 0.60   677.31 19.68 58.83 390.00 313.34 22.08 109.67 357.83



Table of Contents

Report: DaylightingReportMonthly

For: BANQUET_FLR_6_DAYLCTRL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.67 0.60 01-JAN-09:09 301.36 14.31 0.00 238.83 156.01 17.88 0.00 33.67
February 279.67 0.65 0.60 01-FEB-09:09 376.92 15.19 0.00 255.67 180.84 18.52 0.00 90.33
March 338.17 0.64 0.60 01-MAR-09:30 451.38 15.76 0.00 313.17 207.38 18.97 0.00 177.17
April 358.33 0.62 0.60 01-APR-07:30 475.61 16.70 0.00 343.00 232.82 19.97 14.00 269.17
May 393.83 0.62 0.60 01-MAY-06:40 639.55 17.65 12.50 386.67 287.88 20.86 61.17 345.50
June 381.00 0.61 0.60 01-JUN-06:40 677.31 19.68 58.83 380.83 313.34 22.08 109.67 340.17
July 408.67 0.62 0.60 01-JUL-05:49 615.82 18.94 44.67 390.00 271.44 20.54 86.50 357.83
August 390.67 0.62 0.60 01-AUG-07:10 487.91 16.78 0.00 370.33 234.53 20.07 34.00 297.17
September 328.83 0.63 0.60 01-SEP-06:00 419.01 16.05 0.00 310.83 208.00 19.34 0.00 183.50
October 296.17 0.67 0.60 01-OCT-09:39 312.26 14.67 0.00 253.17 158.55 18.12 0.00 56.50
November 300.00 0.67 0.60 01-NOV-08:09 309.11 14.12 0.00 243.67 157.57 17.57 0.00 51.67
December 297.00 0.68 0.60 01-DEC-08:50 271.81 13.78 0.00 229.83 144.72 17.41 0.00 19.33
                         
Annual Sum or Average 4065.67 0.64     460.64 16.35 116.00 3716.00 219.11 19.44 305.33 2222.00
Minimum of Months 279.67 0.61 0.60   271.81 13.78 0.00 229.83 144.72 17.41 0.00 19.33
Maximum of Months 408.67 0.68 0.60   677.31 19.68 58.83 390.00 313.34 22.08 109.67 357.83



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.994880E+11 122816.98 08-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 0.727768E+11 119938.66 06-FEB-22:50 0.00 0.00 0.00 0.00 0.00
March 0.103810E+12 120751.78 29-MAR-20:10 0.00 0.00 0.00 0.00 0.00
April 0.421306E+11 111269.01 01-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 0.370273E+11 98112.05 19-MAY-05:00 0.00 0.00 0.00 0.00 0.00
June 0.677493E+10 54893.16 13-JUN-05:00 0.00 0.00 0.00 0.00 0.00
July 0.426280E+09 25669.20 06-JUL-01:00 0.00 0.00 0.00 0.00 0.00
August 0.219728E+09 10997.47 28-AUG-05:05 0.00 0.00 0.00 0.00 0.00
September 0.318056E+10 54514.69 20-SEP-03:00 0.00 0.00 0.00 0.00 0.00
October 0.150465E+11 84502.07 12-OCT-06:00 0.00 0.00 0.00 0.00 0.00
November 0.605945E+11 120532.55 29-NOV-23:00 0.00 0.00 0.00 0.00 0.00
December 0.966803E+11 120544.37 12-DEC-22:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.538156E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.219728E+09 10997.47   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.103810E+12 122816.98   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.314304E+09 1951.42 08-JAN-06:50 0.00 0.00 0.00 0.00 0.00
February 0.375560E+09 1049.69 25-FEB-18:00 0.00 0.00 0.00 0.00 0.00
March 0.618301E+09 1676.77 30-MAR-03:00 0.00 0.00 0.00 0.00 0.00
April 0.179099E+09 1082.20 01-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.249317E+09 857.76 14-MAY-04:50 0.00 0.00 0.00 0.00 0.00
June 60751049.14 397.55 11-JUN-17:00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 2221114.34 334.36 18-SEP-10:37 0.00 0.00 0.00 0.00 0.00
October 22348688.63 507.61 25-OCT-06:05 0.00 0.00 0.00 0.00 0.00
November 97674345.21 551.49 05-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.195960E+09 1085.07 13-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.211553E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.618301E+09 1951.42   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 1987261.64 224.78 30-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1987261.64     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1987261.64 224.78   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 57769433.67 705.60 03-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 11378712.15 320.18 28-FEB-11:50 0.00 0.00 0.00 0.00 0.00
March 70145430.49 674.86 30-MAR-03:00 0.00 0.00 0.00 0.00 0.00
April 3698091.26 292.39 01-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 521098.89 197.93 14-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.143513E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 70145430.49 705.60   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 51359523.28 500.75 08-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 13745421.08 214.14 28-FEB-11:50 0.00 0.00 0.00 0.00 0.00
March 62978804.87 424.98 30-MAR-03:00 0.00 0.00 0.00 0.00 0.00
April 3003163.96 147.09 01-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 3154835.46 114.11 14-DEC-11:37 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.134242E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 62978804.87 500.75   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.760240E+09 9899.27 03-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 0.377500E+09 5136.65 04-FEB-06:00 0.00 0.00 0.00 0.00 0.00
March 0.667953E+09 7792.83 30-MAR-03:00 0.00 0.00 0.00 0.00 0.00
April 0.373509E+09 2401.14 01-APR-05:00 0.00 0.00 0.00 0.00 0.00
May 0.360380E+09 2231.13 13-MAY-04:50 0.00 0.00 0.00 0.00 0.00
June 0.298769E+09 1828.74 12-JUN-04:00 0.00 0.00 0.00 0.00 0.00
July 0.262850E+09 1577.33 23-JUL-17:00 0.00 0.00 0.00 0.00 0.00
August 0.254904E+09 1463.60 19-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.280920E+09 1662.46 18-SEP-04:00 0.00 0.00 0.00 0.00 0.00
October 0.274354E+09 1751.12 28-OCT-05:00 0.00 0.00 0.00 0.00 0.00
November 0.351205E+09 2155.91 06-NOV-04:50 0.00 0.00 0.00 0.00 0.00
December 0.416865E+09 5480.37 23-DEC-06:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.467945E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.254904E+09 1463.60   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.760240E+09 9899.27   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 33100155.80 2632.22 08-JAN-06:50 0.00 0.00 0.00 0.00 0.00
February 95274382.69 2151.48 12-FEB-16:00 0.00 0.00 0.00 0.00 0.00
March 0.146158E+09 3402.50 29-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 1353846.11 1217.57 22-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 17205345.98 1898.57 09-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 4473159.21 1466.31 08-JUN-10:37 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 1265244.86 1316.35 18-SEP-10:37 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 3792707.61 1029.37 12-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.302623E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.146158E+09 3402.50   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 1705105.59 2123.07 29-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1705105.59     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1705105.59 2123.07   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.145288E+09 4207.15 03-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 31803796.02 2233.96 28-FEB-11:35 0.00 0.00 0.00 0.00 0.00
March 0.201781E+09 3646.89 30-MAR-06:07 0.00 0.00 0.00 0.00 0.00
April 6415290.55 1530.32 01-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.385288E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.201781E+09 4207.15   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.375222E+09 3835.17 08-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 0.136652E+09 1141.13 28-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.380648E+09 2674.47 30-MAR-03:00 0.00 0.00 0.00 0.00 0.00
April 20157311.33 1379.23 01-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 4515218.36 607.97 14-MAY-04:50 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 1557810.50 253.01 05-NOV-05:15 0.00 0.00 0.00 0.00 0.00
December 0.123807E+09 1611.88 13-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.104256E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.380648E+09 3835.17   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 32013077.22 2759.45 09-JAN-06:00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 14564470.78 2085.46 30-MAR-03:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 86497.44 144.16 24-DEC-04:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 46664045.43     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 32013077.22 2759.45   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.928991E+10 12726.37 08-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 0.678991E+10 12048.34 05-FEB-06:00 0.00 0.00 0.00 0.00 0.00
March 0.958200E+10 12222.32 30-MAR-03:00 0.00 0.00 0.00 0.00 0.00
April 0.408463E+10 11051.50 01-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 0.364901E+10 9650.74 19-MAY-05:00 0.00 0.00 0.00 0.00 0.00
June 0.639388E+09 5275.71 13-JUN-04:00 0.00 0.00 0.00 0.00 0.00
July 37018068.72 2368.99 06-JUL-01:00 0.00 0.00 0.00 0.00 0.00
August 17472305.07 904.59 24-AUG-02:00 0.00 0.00 0.00 0.00 0.00
September 0.319026E+09 5276.32 20-SEP-03:00 0.00 0.00 0.00 0.00 0.00
October 0.143957E+10 8174.98 28-OCT-05:00 0.00 0.00 0.00 0.00 0.00
November 0.588912E+10 11073.07 05-NOV-02:00 0.00 0.00 0.00 0.00 0.00
December 0.908993E+10 12052.33 24-DEC-04:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.508270E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 17472305.07 904.59   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.958200E+10 12726.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.481639E+09 3936.49 29-JAN-16:05 0.00 0.00 0.00 0.00 0.00
February 0.367750E+09 4692.72 25-FEB-16:03 0.00 0.00 0.00 0.00 0.00
March 0.567297E+09 6451.41 29-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 90704360.71 3712.23 06-APR-18:05 0.00 0.00 0.00 0.00 0.00
May 67438185.89 5344.64 12-MAY-15:04 0.00 0.00 0.00 0.00 0.00
June 10108355.51 3604.19 11-JUN-15:05 0.00 0.00 0.00 0.00 0.00
July 6458386.44 3475.47 05-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 5507041.02 3124.60 08-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 7310825.21 3065.96 21-SEP-18:05 0.00 0.00 0.00 0.00 0.00
October 21210084.76 3752.25 02-OCT-18:05 0.00 0.00 0.00 0.00 0.00
November 0.156938E+09 4269.48 11-NOV-16:04 0.00 0.00 0.00 0.00 0.00
December 0.352627E+09 4620.36 17-DEC-16:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.213499E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 5507041.02 3065.96   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.567297E+09 6451.41   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.984534E+09 6369.48 03-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.588007E+09 5650.46 25-FEB-16:03 0.00 0.00 0.00 0.00 0.00
March 0.758714E+09 6416.34 29-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 0.105090E+09 3744.68 06-APR-18:05 0.00 0.00 0.00 0.00 0.00
May 55185843.05 4196.91 08-MAY-15:05 0.00 0.00 0.00 0.00 0.00
June 4369245.08 3866.82 11-JUN-15:05 0.00 0.00 0.00 0.00 0.00
July 753443.35 1677.27 13-JUL-08:54 0.00 0.00 0.00 0.00 0.00
August 831720.61 1352.66 11-AUG-08:55 0.00 0.00 0.00 0.00 0.00
September 4774938.53 3245.09 03-SEP-08:53 0.00 0.00 0.00 0.00 0.00
October 26756276.43 4060.05 17-OCT-08:24 0.00 0.00 0.00 0.00 0.00
November 0.361553E+09 3807.96 24-NOV-16:03 0.00 0.00 0.00 0.00 0.00
December 0.784635E+09 6364.27 13-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.367520E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 753443.35 1352.66   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.984534E+09 6416.34   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:05 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.163564E+10 30170.93 03-JAN-16:03 0.00 0.00 0.00 0.00 0.00
February 0.335100E+09 36112.35 20-FEB-16:05 0.00 0.00 0.00 0.00 0.00
March 0.845262E+09 32175.65 01-MAR-16:04 0.00 0.00 0.00 0.00 0.00
April 96892747.36 26708.82 18-APR-15:06 0.00 0.00 0.00 0.00 0.00
May 37677610.83 21231.85 08-MAY-15:07 0.00 0.00 0.00 0.00 0.00
June 21352958.63 16432.84 04-JUN-15:07 0.00 0.00 0.00 0.00 0.00
July 9528578.63 9454.45 08-JUL-08:57 0.00 0.00 0.00 0.00 0.00
August 15846597.29 15283.42 22-AUG-08:54 0.00 0.00 0.00 0.00 0.00
September 26854909.51 23088.61 20-SEP-08:54 0.00 0.00 0.00 0.00 0.00
October 31979505.74 21474.13 13-OCT-08:54 0.00 0.00 0.00 0.00 0.00
November 0.272020E+09 36129.59 14-NOV-16:04 0.00 0.00 0.00 0.00 0.00
December 0.972280E+09 36118.02 31-DEC-16:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.430043E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 9528578.63 9454.45   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.163564E+10 36129.59   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.473510E+09 3658.12 18-JAN-19:05 0.00 0.00 0.00 0.00 0.00
February 0.437284E+09 4544.29 25-FEB-19:03 0.00 0.00 0.00 0.00 0.00
March 0.623415E+09 6295.55 29-MAR-18:03 0.00 0.00 0.00 0.00 0.00
April 0.111563E+09 4529.06 22-APR-15:04 0.00 0.00 0.00 0.00 0.00
May 0.101622E+09 4164.28 12-MAY-15:04 0.00 0.00 0.00 0.00 0.00
June 11689181.61 3477.29 11-JUN-15:05 0.00 0.00 0.00 0.00 0.00
July 561694.46 2130.08 09-JUL-18:05 0.00 0.00 0.00 0.00 0.00
August 230031.35 1562.51 21-AUG-18:05 0.00 0.00 0.00 0.00 0.00
September 7775093.83 2782.62 05-SEP-18:05 0.00 0.00 0.00 0.00 0.00
October 24375144.27 2934.40 02-OCT-18:05 0.00 0.00 0.00 0.00 0.00
November 0.195363E+09 3565.96 11-NOV-16:04 0.00 0.00 0.00 0.00 0.00
December 0.386072E+09 3871.12 10-DEC-16:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.237346E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 230031.35 1562.51   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.623415E+09 6295.55   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.939200E+09 6213.05 02-JAN-19:02 0.00 0.00 0.00 0.00 0.00
February 0.681237E+09 5629.16 25-FEB-16:03 0.00 0.00 0.00 0.00 0.00
March 0.827154E+09 6265.15 29-MAR-18:03 0.00 0.00 0.00 0.00 0.00
April 0.140279E+09 3919.83 22-APR-15:04 0.00 0.00 0.00 0.00 0.00
May 89751265.80 4058.48 08-MAY-15:05 0.00 0.00 0.00 0.00 0.00
June 6016963.17 3644.71 11-JUN-15:05 0.00 0.00 0.00 0.00 0.00
July 509313.94 1341.25 11-JUL-21:55 0.00 0.00 0.00 0.00 0.00
August 350439.48 930.02 21-AUG-20:15 0.00 0.00 0.00 0.00 0.00
September 7520434.04 1985.25 26-SEP-21:55 0.00 0.00 0.00 0.00 0.00
October 37908569.39 2495.60 24-OCT-15:04 0.00 0.00 0.00 0.00 0.00
November 0.440070E+09 4417.28 29-NOV-16:04 0.00 0.00 0.00 0.00 0.00
December 0.812937E+09 6185.28 12-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.398293E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 350439.48 930.02   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.939200E+09 6265.15   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.247927E+09 1627.00 02-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.207015E+09 1934.50 25-FEB-16:03 0.00 0.00 0.00 0.00 0.00
March 0.270377E+09 1960.09 29-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 58604395.85 816.47 06-APR-18:05 0.00 0.00 0.00 0.00 0.00
May 52081920.51 1415.14 12-MAY-15:04 0.00 0.00 0.00 0.00 0.00
June 8358802.40 900.62 13-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 1524940.01 817.67 26-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 1503855.61 764.14 03-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 3212155.97 832.15 21-SEP-18:05 0.00 0.00 0.00 0.00 0.00
October 26839872.66 1065.98 23-OCT-15:04 0.00 0.00 0.00 0.00 0.00
November 0.122360E+09 934.33 11-NOV-16:04 0.00 0.00 0.00 0.00 0.00
December 0.213974E+09 1257.61 12-DEC-19:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.121378E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1503855.61 764.14   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.270377E+09 1960.09   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.456130E+09 1934.04 03-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.302057E+09 1924.00 25-FEB-16:03 0.00 0.00 0.00 0.00 0.00
March 0.343077E+09 1945.83 29-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 64335796.87 1334.34 01-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 39045685.38 1271.90 12-MAY-15:04 0.00 0.00 0.00 0.00 0.00
June 3850467.13 933.37 11-JUN-15:05 0.00 0.00 0.00 0.00 0.00
July 142942.58 457.14 06-JUL-08:54 0.00 0.00 0.00 0.00 0.00
August 301907.43 523.74 23-AUG-08:53 0.00 0.00 0.00 0.00 0.00
September 2555113.11 810.07 11-SEP-08:53 0.00 0.00 0.00 0.00 0.00
October 34057920.86 1142.21 24-OCT-15:04 0.00 0.00 0.00 0.00 0.00
November 0.231483E+09 1635.18 05-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 0.406229E+09 1932.38 13-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.188327E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 142942.58 457.14   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.456130E+09 1945.83   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.209317E+09 4230.69 25-JAN-16:05 0.00 0.00 0.00 0.00 0.00
February 0.251730E+09 4799.87 13-FEB-16:05 0.00 0.00 0.00 0.00 0.00
March 0.568174E+09 8970.89 29-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 0.121836E+09 4930.15 01-APR-18:05 0.00 0.00 0.00 0.00 0.00
May 0.182632E+09 8341.55 12-MAY-15:04 0.00 0.00 0.00 0.00 0.00
June 31314481.66 5049.78 14-JUN-18:05 0.00 0.00 0.00 0.00 0.00
July 9919008.18 4155.11 05-JUL-18:05 0.00 0.00 0.00 0.00 0.00
August 5080723.99 3648.02 09-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 9417678.20 3594.93 22-SEP-18:05 0.00 0.00 0.00 0.00 0.00
October 18946057.04 3529.29 21-OCT-18:05 0.00 0.00 0.00 0.00 0.00
November 47573645.89 3398.22 09-NOV-09:05 0.00 0.00 0.00 0.00 0.00
December 0.131181E+09 3090.49 12-DEC-19:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.158712E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 5080723.99 3090.49   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.568174E+09 8970.89   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: SWHSYS1 HPWH DXCOIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.499176E+11 0.499156E+11 51441.99 31-JAN-06:15 51441.99 0.00
February 0.00 0.00 0.453013E+11 0.433881E+11 52092.34 02-FEB-18:15 49882.34 0.00
March 0.00 0.00 0.495808E+11 0.434254E+11 52029.53 01-MAR-06:15 45545.26 0.00
April 0.00 0.00 0.475319E+11 0.399168E+11 55011.12 01-APR-07:13 46133.68 0.00
May 0.00 0.00 0.477518E+11 0.407837E+11 54908.46 01-MAY-05:15 46830.36 0.00
June 0.00 0.00 0.456842E+11 0.356037E+11 59585.55 30-JUN-23:07 41484.88 0.00
July 0.00 0.00 0.469601E+11 0.327211E+11 59997.65 01-JUL-05:08 41781.91 0.00
August 0.00 0.00 0.470845E+11 0.308136E+11 60747.00 31-AUG-08:15 39735.19 0.00
September 0.00 0.00 0.456922E+11 0.346820E+11 58600.87 30-SEP-05:08 44423.69 0.00
October 0.00 0.00 0.480308E+11 0.448275E+11 57525.04 31-OCT-18:03 53601.22 0.00
November 0.00 0.00 0.466177E+11 0.466016E+11 52402.95 30-NOV-06:15 52368.77 0.00
December 0.00 0.00 0.489460E+11 0.489460E+11 50696.46 31-DEC-02:10 50696.46 0.00
                 
Annual Sum or Average 0.00 0.00 0.569099E+12 0.491625E+12       0.00
Minimum of Months 0.00 0.00 0.453013E+11 0.308136E+11 50696.46   39735.19 0.00
Maximum of Months 0.00 0.00 0.499176E+11 0.499156E+11 60747.00   53601.22 0.00



Table of Contents

Report: CoilReportMonthly

For: SWHSYSLAUNDRY HPWH DXCOIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.515170E+11 0.515156E+11 65101.75 31-JAN-17:10 65101.75 0.00
February 0.00 0.00 0.471456E+11 0.451680E+11 65925.25 02-FEB-19:50 63148.28 0.00
March 0.00 0.00 0.520521E+11 0.456038E+11 65845.71 01-MAR-23:40 57646.56 0.00
April 0.00 0.00 0.531873E+11 0.446769E+11 69621.11 01-APR-18:00 58400.21 0.00
May 0.00 0.00 0.548344E+11 0.468482E+11 69491.12 01-MAY-16:10 59279.86 0.00
June 0.00 0.00 0.557210E+11 0.434388E+11 72970.63 01-JUN-16:10 56831.80 0.00
July 0.00 0.00 0.599842E+11 0.418049E+11 75935.24 01-JUL-16:05 52891.60 0.00
August 0.00 0.00 0.607275E+11 0.397433E+11 76884.09 31-AUG-16:10 50290.11 0.00
September 0.00 0.00 0.566682E+11 0.430168E+11 74166.58 30-SEP-16:10 56223.94 0.00
October 0.00 0.00 0.574231E+11 0.536066E+11 72804.33 31-OCT-17:25 67857.32 0.00
November 0.00 0.00 0.506655E+11 0.506541E+11 66318.56 30-NOV-17:10 66295.79 0.00
December 0.00 0.00 0.507275E+11 0.507275E+11 64157.74 31-DEC-18:13 64157.74 0.00
                 
Annual Sum or Average 0.00 0.00 0.650653E+12 0.556805E+12       0.00
Minimum of Months 0.00 0.00 0.471456E+11 0.397433E+11 64157.74   50290.11 0.00
Maximum of Months 0.00 0.00 0.607275E+11 0.536066E+11 76884.09   67857.32 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.573504E+11 0.571755E+11 205399.86 14-JAN-11:50 205399.86 0.21
February 0.00 0.00 0.321104E+11 0.313603E+11 193334.14 01-FEB-11:50 193334.14 0.21
March 0.00 0.00 0.358885E+11 0.351008E+11 180673.77 23-MAR-10:50 144388.88 0.22
April 0.00 0.00 0.849640E+11 0.831206E+11 248967.52 26-APR-10:50 202376.11 0.44
May 0.00 0.00 0.906417E+11 0.895254E+11 158913.85 18-MAY-10:50 140481.95 0.52
June 0.00 0.00 0.168642E+12 0.145683E+12 308917.12 29-JUN-10:50 189236.04 0.85
July 0.00 0.00 0.344426E+12 0.222488E+12 377369.04 31-JUL-10:50 221814.48 0.99
August 0.00 0.00 0.387778E+12 0.232064E+12 405083.85 14-AUG-10:50 238685.32 0.99
September 0.00 0.00 0.228692E+12 0.174737E+12 374121.42 22-SEP-12:00 184702.99 0.90
October 0.00 0.00 0.256993E+12 0.206204E+12 379535.83 16-OCT-10:50 379535.83 0.59
November 0.00 0.00 0.597973E+11 0.590271E+11 210358.07 19-NOV-13:00 210358.07 0.28
December 0.00 0.00 0.660005E+11 0.660005E+11 191476.99 16-DEC-13:00 191476.99 0.10
                 
Annual Sum or Average 0.00 0.00 0.181328E+13 0.140249E+13       0.53
Minimum of Months 0.00 0.00 0.321104E+11 0.313603E+11 158913.85   140481.95 0.10
Maximum of Months 0.00 0.00 0.387778E+12 0.232064E+12 405083.85   379535.83 0.99



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.353274E+10 0.349906E+10 20880.62 17-JAN-14:00 17732.61 0.13
February 0.00 0.00 0.189886E+10 0.184037E+10 17583.53 01-FEB-10:00 17583.53 0.12
March 0.00 0.00 0.215372E+10 0.197542E+10 22325.57 22-MAR-13:00 14832.90 0.11
April 0.00 0.00 0.541905E+10 0.504769E+10 22090.94 26-APR-13:00 22090.94 0.26
May 0.00 0.00 0.572637E+10 0.557752E+10 19286.16 04-MAY-13:00 16265.35 0.32
June 0.00 0.00 0.129295E+11 0.101515E+11 31088.77 29-JUN-12:30 17826.99 0.64
July 0.00 0.00 0.288160E+11 0.167818E+11 40512.87 31-JUL-12:30 23766.96 0.78
August 0.00 0.00 0.328487E+11 0.176856E+11 39040.56 14-AUG-10:00 22143.05 0.78
September 0.00 0.00 0.187456E+11 0.130117E+11 39773.96 22-SEP-12:15 19372.98 0.69
October 0.00 0.00 0.207096E+11 0.151881E+11 39092.82 01-OCT-12:10 20585.81 0.45
November 0.00 0.00 0.355504E+10 0.347970E+10 21516.86 19-NOV-13:10 21516.86 0.17
December 0.00 0.00 0.428780E+10 0.428430E+10 20480.74 05-DEC-10:00 20480.74 0.04
                 
Annual Sum or Average 0.00 0.00 0.140623E+12 0.985227E+11       0.38
Minimum of Months 0.00 0.00 0.189886E+10 0.184037E+10 17583.53   14832.90 0.04
Maximum of Months 0.00 0.00 0.328487E+11 0.176856E+11 40512.87   23766.96 0.78



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.194362E+10 0.124811E+10 12267.56 17-JAN-16:02 10135.39 0.40
February 0.00 0.00 0.171243E+10 0.113632E+10 12337.28 11-FEB-16:02 8818.84 0.37
March 0.00 0.00 0.183779E+10 0.108350E+10 11703.88 18-MAR-15:01 10052.10 0.43
April 0.00 0.00 0.380165E+10 0.223085E+10 12399.20 26-APR-08:62 10163.10 0.75
May 0.00 0.00 0.351563E+10 0.195087E+10 11943.06 06-MAY-08:62 8801.06 0.75
June 0.00 0.00 0.516800E+10 0.287498E+10 12620.70 30-JUN-08:62 9930.52 0.86
July 0.00 0.00 0.755183E+10 0.432903E+10 13492.94 30-JUL-08:62 9525.43 0.93
August 0.00 0.00 0.786982E+10 0.451424E+10 13963.03 06-AUG-08:62 9555.13 0.93
September 0.00 0.00 0.605016E+10 0.342398E+10 13601.53 22-SEP-08:62 9237.62 0.91
October 0.00 0.00 0.556702E+10 0.380141E+10 13760.72 01-OCT-08:62 9343.70 0.68
November 0.00 0.00 0.263422E+10 0.165767E+10 12140.34 11-NOV-16:01 9248.91 0.52
December 0.00 0.00 0.225175E+10 0.179916E+10 11797.99 05-DEC-09:02 11797.99 0.27
                 
Annual Sum or Average 0.00 0.00 0.499039E+11 0.300501E+11       0.65
Minimum of Months 0.00 0.00 0.171243E+10 0.108350E+10 11703.88   8801.06 0.27
Maximum of Months 0.00 0.00 0.786982E+10 0.451424E+10 13963.03   11797.99 0.93



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.384029E+09 0.221313E+09 11679.88 17-JAN-16:02 9399.14 0.15
February 0.00 0.00 0.528896E+09 0.292288E+09 11638.76 13-FEB-16:02 8494.15 0.21
March 0.00 0.00 0.754464E+09 0.380304E+09 11314.36 18-MAR-15:01 9543.54 0.25
April 0.00 0.00 0.209014E+10 0.100535E+10 12333.81 26-APR-21:51 9309.74 0.56
May 0.00 0.00 0.234008E+10 0.116867E+10 12002.10 02-MAY-21:51 9298.31 0.58
June 0.00 0.00 0.330350E+10 0.174135E+10 13047.09 28-JUN-21:51 9521.43 0.56
July 0.00 0.00 0.490845E+10 0.282720E+10 14162.46 23-JUL-08:51 9712.61 0.57
August 0.00 0.00 0.466390E+10 0.258226E+10 14365.78 19-AUG-08:51 9237.51 0.56
September 0.00 0.00 0.324571E+10 0.163213E+10 13183.38 21-SEP-21:52 8798.68 0.56
October 0.00 0.00 0.257501E+10 0.162680E+10 13912.06 01-OCT-08:52 8640.04 0.40
November 0.00 0.00 0.704060E+09 0.352745E+09 11517.85 11-NOV-16:01 8574.27 0.29
December 0.00 0.00 0.416406E+09 0.310686E+09 11192.91 05-DEC-16:01 11192.91 0.11
                 
Annual Sum or Average 0.00 0.00 0.259146E+11 0.141411E+11       0.40
Minimum of Months 0.00 0.00 0.384029E+09 0.221313E+09 11192.91   8494.15 0.11
Maximum of Months 0.00 0.00 0.490845E+10 0.282720E+10 14365.78   11192.91 0.58



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.326152E+11 0.258181E+11 46972.19 14-JAN-12:40 46972.19 0.47
February 0.00 0.00 0.205274E+11 0.156660E+11 41522.17 02-FEB-12:40 34156.85 0.40
March 0.00 0.00 0.147235E+11 0.898851E+10 34888.40 11-MAR-13:20 34888.40 0.44
April 0.00 0.00 0.167736E+11 0.752603E+10 27010.95 08-APR-12:40 18474.72 0.66
May 0.00 0.00 0.931344E+10 0.287577E+10 21163.58 02-MAY-15:03 12158.02 0.59
June 0.00 0.00 0.130068E+11 0.395092E+10 21323.35 28-JUN-15:05 10558.88 0.71
July 0.00 0.00 0.219749E+11 0.789329E+10 24335.81 18-JUL-15:03 12849.08 0.87
August 0.00 0.00 0.304265E+11 0.131417E+11 26690.37 27-AUG-12:05 16685.20 0.98
September 0.00 0.00 0.331957E+11 0.178444E+11 44979.95 30-SEP-13:10 38454.58 0.97
October 0.00 0.00 0.422584E+11 0.308985E+11 53000.92 16-OCT-12:30 53000.92 0.70
November 0.00 0.00 0.338877E+11 0.253913E+11 50299.12 19-NOV-13:00 47944.76 0.60
December 0.00 0.00 0.373254E+11 0.326407E+11 48054.29 19-DEC-13:00 48054.29 0.34
                 
Annual Sum or Average 0.00 0.00 0.306029E+12 0.192635E+12       0.64
Minimum of Months 0.00 0.00 0.931344E+10 0.287577E+10 21163.58   10558.88 0.34
Maximum of Months 0.00 0.00 0.422584E+11 0.326407E+11 53000.92   53000.92 0.98



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.914762E+10 0.552040E+10 64555.87 20-JAN-19:02 51640.52 0.32
February 0.00 0.00 0.102801E+11 0.600996E+10 64332.53 13-FEB-16:02 50783.01 0.45
March 0.00 0.00 0.130887E+11 0.760548E+10 65956.55 23-MAR-15:02 57242.73 0.47
April 0.00 0.00 0.201689E+11 0.118604E+11 69109.26 26-APR-21:51 51984.97 0.56
May 0.00 0.00 0.244213E+11 0.156710E+11 67949.54 02-MAY-21:51 52880.87 0.56
June 0.00 0.00 0.287382E+11 0.186262E+11 73040.59 28-JUN-21:51 53142.40 0.50
July 0.00 0.00 0.354845E+11 0.228854E+11 77230.93 23-JUL-08:51 57024.53 0.50
August 0.00 0.00 0.329199E+11 0.203461E+11 78872.53 19-AUG-08:51 53628.39 0.48
September 0.00 0.00 0.252553E+11 0.152253E+11 76055.74 21-SEP-21:52 52013.57 0.48
October 0.00 0.00 0.227923E+11 0.162911E+11 76975.55 01-OCT-08:52 50595.25 0.35
November 0.00 0.00 0.119630E+11 0.726671E+10 65080.76 09-NOV-22:53 49043.57 0.42
December 0.00 0.00 0.853929E+10 0.600918E+10 63189.89 05-DEC-16:01 63189.89 0.25
                 
Annual Sum or Average 0.00 0.00 0.242799E+12 0.153317E+12       0.44
Minimum of Months 0.00 0.00 0.853929E+10 0.552040E+10 63189.89   49043.57 0.25
Maximum of Months 0.00 0.00 0.354845E+11 0.228854E+11 78872.53   63189.89 0.56



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.206698E+10 0.139942E+10 10652.26 17-JAN-16:02 9032.78 0.41
February 0.00 0.00 0.161494E+10 0.111165E+10 10480.83 13-FEB-16:02 7467.73 0.36
March 0.00 0.00 0.181248E+10 0.108475E+10 10225.50 15-MAR-15:01 8842.74 0.43
April 0.00 0.00 0.344062E+10 0.198211E+10 10326.30 24-APR-15:02 9063.59 0.75
May 0.00 0.00 0.299429E+10 0.164239E+10 10833.32 06-MAY-15:01 8922.55 0.73
June 0.00 0.00 0.433381E+10 0.229069E+10 10998.94 28-JUN-15:02 9237.27 0.87
July 0.00 0.00 0.685807E+10 0.379083E+10 11386.71 29-JUL-18:02 8710.01 0.95
August 0.00 0.00 0.746865E+10 0.419165E+10 11525.49 08-AUG-08:62 8092.52 0.95
September 0.00 0.00 0.518679E+10 0.285366E+10 11755.09 21-SEP-15:02 9323.47 0.90
October 0.00 0.00 0.527552E+10 0.365729E+10 12086.74 01-OCT-08:62 8190.00 0.68
November 0.00 0.00 0.242908E+10 0.161821E+10 10575.20 12-NOV-09:02 7208.44 0.51
December 0.00 0.00 0.226423E+10 0.189412E+10 10349.10 05-DEC-09:02 10349.10 0.26
                 
Annual Sum or Average 0.00 0.00 0.457455E+11 0.275168E+11       0.65
Minimum of Months 0.00 0.00 0.161494E+10 0.108475E+10 10225.50   7208.44 0.26
Maximum of Months 0.00 0.00 0.746865E+10 0.419165E+10 12086.74   10349.10 0.95



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.513647E+09 0.333529E+09 10205.24 17-JAN-16:02 8368.96 0.15
February 0.00 0.00 0.527902E+09 0.347030E+09 9927.93 01-FEB-09:51 9927.93 0.18
March 0.00 0.00 0.813781E+09 0.457313E+09 10419.20 23-MAR-15:02 8800.61 0.26
April 0.00 0.00 0.201059E+10 0.110526E+10 11236.06 26-APR-08:51 10392.71 0.54
May 0.00 0.00 0.207603E+10 0.111569E+10 10963.81 03-MAY-08:51 9626.66 0.56
June 0.00 0.00 0.291299E+10 0.154879E+10 12333.29 30-JUN-08:51 9864.82 0.57
July 0.00 0.00 0.457421E+10 0.257910E+10 13359.16 19-JUL-08:51 9970.05 0.58
August 0.00 0.00 0.453295E+10 0.250279E+10 13436.00 19-AUG-08:51 9642.40 0.58
September 0.00 0.00 0.268351E+10 0.137809E+10 12484.07 10-SEP-08:51 9749.73 0.58
October 0.00 0.00 0.240871E+10 0.160400E+10 12182.25 01-OCT-08:52 7548.45 0.40
November 0.00 0.00 0.678726E+09 0.416259E+09 10084.93 12-NOV-09:02 6822.53 0.22
December 0.00 0.00 0.452476E+09 0.365541E+09 10524.91 05-DEC-09:41 10524.91 0.09
                 
Annual Sum or Average 0.00 0.00 0.241855E+11 0.137534E+11       0.39
Minimum of Months 0.00 0.00 0.452476E+09 0.333529E+09 9927.93   6822.53 0.09
Maximum of Months 0.00 0.00 0.457421E+10 0.257910E+10 13436.00   10524.91 0.58



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.410415E+09 0.273472E+09 3219.96 17-JAN-16:02 2627.49 0.30
February 0.00 0.00 0.375053E+09 0.255219E+09 3208.16 13-FEB-16:02 2318.67 0.28
March 0.00 0.00 0.438612E+09 0.272384E+09 3110.50 24-MAR-08:62 2201.92 0.34
April 0.00 0.00 0.934056E+09 0.577964E+09 3327.90 26-APR-08:62 2542.49 0.66
May 0.00 0.00 0.844999E+09 0.496865E+09 3265.13 06-MAY-08:62 2081.42 0.65
June 0.00 0.00 0.127777E+10 0.729885E+09 3381.46 30-JUN-08:62 2508.94 0.83
July 0.00 0.00 0.190438E+10 0.109756E+10 3642.17 30-JUL-08:62 2399.94 0.93
August 0.00 0.00 0.195387E+10 0.111691E+10 3812.33 06-AUG-08:62 2338.44 0.93
September 0.00 0.00 0.143264E+10 0.822463E+09 3700.58 22-SEP-08:62 2253.46 0.89
October 0.00 0.00 0.127122E+10 0.872003E+09 3734.01 01-OCT-08:62 2338.48 0.62
November 0.00 0.00 0.549489E+09 0.352004E+09 3187.40 11-NOV-16:01 2343.57 0.41
December 0.00 0.00 0.467626E+09 0.381890E+09 3063.45 05-DEC-09:02 3063.45 0.21
                 
Annual Sum or Average 0.00 0.00 0.118601E+11 0.724862E+10       0.59
Minimum of Months 0.00 0.00 0.375053E+09 0.255219E+09 3063.45   2081.42 0.21
Maximum of Months 0.00 0.00 0.195387E+10 0.111691E+10 3812.33   3063.45 0.93



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 65259177.77 41893494.96 3041.33 17-JAN-16:02 2406.72 0.07
February 0.00 0.00 97036857.53 56778708.93 3022.05 13-FEB-16:02 2142.46 0.13
March 0.00 0.00 0.167171E+09 89766846.89 2984.14 22-MAR-18:51 2444.80 0.19
April 0.00 0.00 0.498978E+09 0.254190E+09 3306.68 26-APR-21:51 2432.07 0.48
May 0.00 0.00 0.558116E+09 0.291771E+09 3201.48 02-MAY-21:51 2391.79 0.52
June 0.00 0.00 0.861797E+09 0.465008E+09 3500.09 28-JUN-21:51 2491.94 0.56
July 0.00 0.00 0.132056E+10 0.769859E+09 3753.28 23-JUL-08:51 2514.43 0.57
August 0.00 0.00 0.121996E+10 0.677363E+09 3804.49 19-AUG-08:51 2355.13 0.57
September 0.00 0.00 0.761411E+09 0.378106E+09 3514.67 21-SEP-21:52 2196.58 0.57
October 0.00 0.00 0.556636E+09 0.354473E+09 3683.88 01-OCT-08:52 2150.37 0.35
November 0.00 0.00 0.108367E+09 57914235.35 3010.45 11-NOV-16:01 2140.11 0.16
December 0.00 0.00 63195266.71 51164054.65 2904.87 05-DEC-16:01 2904.87 0.03
                 
Annual Sum or Average 0.00 0.00 0.627848E+10 0.348829E+10       0.35
Minimum of Months 0.00 0.00 63195266.71 41893494.96 2904.87   2140.11 0.03
Maximum of Months 0.00 0.00 0.132056E+10 0.769859E+09 3804.49   2904.87 0.57



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.753731E+10 0.606394E+10 14927.36 17-JAN-16:02 12568.33 0.56
February 0.00 0.00 0.492442E+10 0.381510E+10 15149.47 11-FEB-16:02 11018.54 0.53
March 0.00 0.00 0.420152E+10 0.277951E+10 14180.24 20-MAR-15:01 12002.75 0.56
April 0.00 0.00 0.507348E+10 0.289581E+10 14782.59 26-APR-08:62 12230.94 0.76
May 0.00 0.00 0.313762E+10 0.150009E+10 15013.43 28-MAY-15:01 12507.76 0.65
June 0.00 0.00 0.428970E+10 0.190891E+10 15603.60 29-JUN-18:02 12332.69 0.81
July 0.00 0.00 0.706576E+10 0.333731E+10 16860.53 29-JUL-18:02 11401.36 0.90
August 0.00 0.00 0.900963E+10 0.469963E+10 17233.58 19-AUG-08:62 11438.55 0.91
September 0.00 0.00 0.870610E+10 0.520498E+10 16610.84 22-SEP-08:62 11165.21 0.89
October 0.00 0.00 0.101616E+11 0.767812E+10 16978.85 01-OCT-08:62 11189.29 0.70
November 0.00 0.00 0.766692E+10 0.593616E+10 14962.86 11-NOV-16:01 11764.04 0.66
December 0.00 0.00 0.818868E+10 0.719816E+10 14303.18 05-DEC-09:02 14303.18 0.40
                 
Annual Sum or Average 0.00 0.00 0.799627E+11 0.530177E+11       0.70
Minimum of Months 0.00 0.00 0.313762E+10 0.150009E+10 14180.24   11018.54 0.40
Maximum of Months 0.00 0.00 0.101616E+11 0.767812E+10 17233.58   14303.18 0.91



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 42936.45 175069.70 08-JAN-07:00
February 0.00 0.00 01-FEB-00:03 34338.52 141382.69 04-FEB-06:00
March 0.00 0.00 01-MAR-00:03 44560.61 168884.07 30-MAR-03:00
April 0.00 0.00 01-APR-00:10 18202.46 135442.55 01-APR-06:00
May 0.00 0.00 01-MAY-00:05 15521.56 111864.07 15-MAY-02:00
June 0.00 0.00 01-JUN-00:05 3012.44 63289.34 13-JUN-04:00
July 0.00 0.00 01-JUL-00:10 279.54 28659.63 06-JUL-03:00
August 0.00 0.00 01-AUG-00:05 194.25 28062.88 22-AUG-08:54
September 0.00 0.00 01-SEP-00:05 1474.19 61482.47 20-SEP-03:00
October 0.00 0.00 01-OCT-00:10 6294.39 94516.68 12-OCT-05:00
November 0.00 0.00 01-NOV-00:05 26303.59 131764.70 29-NOV-22:50
December 0.00 0.00 01-DEC-00:03 40937.63 146582.49 23-DEC-06:00
             
Annual Sum or Average 0.00     19462.24    
Minimum of Months 0.00 0.00   194.25 28062.88  
Maximum of Months 0.00 0.00   44560.61 175069.70  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 45853.37 305663.19 14-JAN-16:03 0.00 0.00 01-JAN-00:10
February 33578.51 292561.59 01-FEB-09:51 0.00 0.00 01-FEB-00:03
March 30910.93 325473.59 23-MAR-15:03 0.00 0.00 01-MAR-00:03
April 59012.11 308341.99 11-APR-15:03 0.00 0.00 01-APR-00:10
May 57374.04 328844.61 18-MAY-15:02 0.00 0.00 01-MAY-00:05
June 97768.22 387939.80 28-JUN-15:05 0.00 0.00 01-JUN-00:05
July 176714.90 508677.19 18-JUL-18:03 0.00 0.00 01-JUL-00:10
August 197578.70 533429.11 18-AUG-15:03 0.00 0.00 01-AUG-00:05
September 131955.92 488776.39 29-SEP-15:03 0.00 0.00 01-SEP-00:05
October 141474.00 479352.33 14-OCT-15:03 0.00 0.00 01-OCT-00:10
November 50768.23 365598.59 19-NOV-09:41 0.00 0.00 01-NOV-00:05
December 51436.98 353815.03 05-DEC-09:41 0.00 0.00 01-DEC-00:03
             
Annual Sum or Average 90046.47     0.00    
Minimum of Months 30910.93 292561.59   0.00 0.00  
Maximum of Months 197578.70 533429.11   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 23227.75 48614.09 31-JAN-07:40
February 0.00 0.00 01-FEB-00:03 23257.66 48612.52 02-FEB-07:40
March 0.00 0.00 01-MAR-00:03 23026.32 48372.71 01-MAR-07:40
April 0.00 0.00 01-APR-00:10 22543.26 47475.08 03-APR-06:40
May 0.00 0.00 01-MAY-00:05 21983.01 46415.18 01-MAY-06:30
June 0.00 0.00 01-JUN-00:05 21484.24 45225.79 01-JUN-07:00
July 0.00 0.00 01-JUL-00:10 21152.28 44309.71 03-JUL-07:00
August 0.00 0.00 01-AUG-00:05 21141.87 44222.92 31-AUG-07:00
September 0.00 0.00 01-SEP-00:05 21387.16 44972.49 29-SEP-07:00
October 0.00 0.00 01-OCT-00:10 21851.24 46152.29 31-OCT-07:00
November 0.00 0.00 01-NOV-00:05 22418.00 47334.44 30-NOV-07:40
December 0.00 0.00 01-DEC-00:03 22919.02 48205.49 29-DEC-07:40
             
Annual Sum or Average 0.00     22193.26    
Minimum of Months 0.00 0.00   21141.87 44222.92  
Maximum of Months 0.00 0.00   23257.66 48614.09  



Table of Contents

Report: FanReportMonthly

For: SWHSYS1 HPWH FAN

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.571016E+09 0.06 553.22 01-JAN-06:15 0.10
February 0.512394E+09 0.06 553.22 01-FEB-06:15 0.10
March 0.562903E+09 0.06 553.22 01-MAR-06:15 0.10
April 0.513294E+09 0.06 553.22 01-APR-05:15 0.10
May 0.518192E+09 0.06 553.22 01-MAY-05:15 0.10
June 0.472905E+09 0.05 553.22 01-JUN-05:15 0.10
July 0.466910E+09 0.05 553.22 01-JUL-05:08 0.10
August 0.462710E+09 0.05 553.22 01-AUG-05:15 0.10
September 0.465519E+09 0.05 553.22 01-SEP-05:15 0.10
October 0.499273E+09 0.06 553.22 01-OCT-05:07 0.10
November 0.527592E+09 0.06 553.22 01-NOV-05:05 0.10
December 0.569368E+09 0.06 553.22 01-DEC-06:15 0.10
           
Annual Sum or Average 0.614208E+10 0.06      
Minimum of Months 0.462710E+09 0.05 553.22   0.10
Maximum of Months 0.571016E+09 0.06 553.22   0.10



Table of Contents

Report: FanReportMonthly

For: SWHSYSLAUNDRY HPWH FAN

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.556544E+09 0.06 700.51 01-JAN-17:10 0.10
February 0.502830E+09 0.05 700.51 01-FEB-17:10 0.10
March 0.556614E+09 0.06 700.51 01-MAR-17:05 0.10
April 0.538285E+09 0.05 700.51 01-APR-16:05 0.10
May 0.556167E+09 0.05 700.51 01-MAY-16:10 0.10
June 0.537784E+09 0.05 700.51 01-JUN-16:10 0.10
July 0.555649E+09 0.05 700.51 01-JUL-16:05 0.10
August 0.555381E+09 0.05 700.51 01-AUG-16:10 0.10
September 0.538019E+09 0.05 700.51 01-SEP-16:10 0.10
October 0.555827E+09 0.05 700.51 01-OCT-16:10 0.10
November 0.538406E+09 0.05 700.51 01-NOV-16:10 0.10
December 0.556894E+09 0.06 700.51 01-DEC-17:10 0.10
           
Annual Sum or Average 0.654840E+10 0.05      
Minimum of Months 0.502830E+09 0.05 700.51   0.10
Maximum of Months 0.556894E+09 0.06 700.51   0.10



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.271000E+10 0.71 1299.30 01-JAN-02:30 0.89
February 0.244774E+10 0.70 1299.30 01-FEB-01:20 0.89
March 0.271000E+10 0.70 1299.30 01-MAR-01:30 0.89
April 0.262258E+10 0.70 1299.30 01-APR-03:50 0.89
May 0.271000E+10 0.70 1299.30 01-MAY-00:30 0.88
June 0.262258E+10 0.70 1299.30 01-JUN-05:03 0.89
July 0.271000E+10 0.70 1299.30 01-JUL-02:00 0.88
August 0.271000E+10 0.70 1299.30 01-AUG-04:00 0.88
September 0.262258E+10 0.70 1299.30 29-SEP-16:10 0.89
October 0.271000E+10 0.70 1299.30 16-OCT-16:40 0.89
November 0.262258E+10 0.70 1299.30 01-NOV-01:50 0.89
December 0.271000E+10 0.71 1299.30 01-DEC-00:50 0.89
           
Annual Sum or Average 0.319080E+11 0.70      
Minimum of Months 0.244774E+10 0.70 1299.30   0.88
Maximum of Months 0.271000E+10 0.71 1299.30   0.89



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.374631E+11 0.92 23242.54 18-JAN-22:10 1.24
February 0.339587E+11 0.92 22221.32 01-FEB-22:10 1.20
March 0.375236E+11 0.91 22172.62 24-MAR-21:10 1.20
April 0.369684E+11 0.92 23202.02 26-APR-21:10 1.23
May 0.384667E+11 0.93 24152.71 04-MAY-21:10 1.26
June 0.379067E+11 0.93 24152.35 27-JUN-21:10 1.26
July 0.395370E+11 0.94 24684.67 31-JUL-21:10 1.28
August 0.396896E+11 0.94 25212.94 18-AUG-21:10 1.30
September 0.378979E+11 0.93 27729.34 29-SEP-21:20 1.39
October 0.395283E+11 0.94 28310.90 16-OCT-21:10 1.40
November 0.367578E+11 0.92 23128.27 27-NOV-22:10 1.25
December 0.377833E+11 0.92 25115.66 05-DEC-22:10 1.31
           
Annual Sum or Average 0.453481E+12 0.93      
Minimum of Months 0.339587E+11 0.91 22172.62   1.20
Maximum of Months 0.396896E+11 0.94 28310.90   1.40



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205205E+09 0.27 76.61 01-JAN-00:10 0.27
February 0.185347E+09 0.27 76.61 01-FEB-00:03 0.27
March 0.205205E+09 0.27 76.61 01-MAR-00:03 0.27
April 0.198586E+09 0.27 76.61 01-APR-00:10 0.27
May 0.205205E+09 0.27 76.61 01-MAY-00:05 0.27
June 0.198586E+09 0.27 76.61 01-JUN-00:05 0.27
July 0.205205E+09 0.27 76.61 01-JUL-00:10 0.27
August 0.205205E+09 0.27 76.61 01-AUG-00:05 0.27
September 0.198586E+09 0.27 76.61 01-SEP-00:05 0.27
October 0.205205E+09 0.27 76.61 01-OCT-00:10 0.27
November 0.198586E+09 0.27 76.61 01-NOV-00:05 0.27
December 0.205205E+09 0.27 76.61 01-DEC-00:03 0.27
           
Annual Sum or Average 0.241613E+10 0.27      
Minimum of Months 0.185347E+09 0.27 76.61   0.27
Maximum of Months 0.205205E+09 0.27 76.61   0.27



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:10 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:10 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 -0.0 0.00 01-MAR-00:03 0.00
April 0.00 -0.0 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:05 0.00
June 0.00 0.00 0.00 01-JUN-00:05 0.00
July 0.00 -0.0 0.00 01-JUL-00:10 0.00
August 0.00 -0.0 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:10 0.00
February 0.00 -0.0 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 -0.0 0.00 01-MAY-00:05 0.00
June 0.00 -0.0 0.00 01-JUN-00:05 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00
October 0.00 -0.0 0.00 01-OCT-00:10 0.00
November 0.00 -0.0 0.00 01-NOV-00:05 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 -0.0      
Minimum of Months 0.00 -0.0 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116283E+10 0.19 612.92 01-JAN-07:03 0.27
February 0.105030E+10 0.19 612.92 01-FEB-07:05 0.27
March 0.116283E+10 0.19 612.92 01-MAR-07:05 0.27
April 0.112532E+10 0.19 612.92 01-APR-06:05 0.27
May 0.116283E+10 0.19 612.92 01-MAY-06:05 0.27
June 0.112532E+10 0.19 612.92 01-JUN-06:05 0.27
July 0.116283E+10 0.19 612.92 01-JUL-06:05 0.27
August 0.116283E+10 0.19 612.92 01-AUG-06:05 0.27
September 0.112532E+10 0.19 612.92 01-SEP-06:05 0.27
October 0.116283E+10 0.19 612.92 01-OCT-06:05 0.27
November 0.112532E+10 0.19 612.92 01-NOV-06:05 0.27
December 0.116283E+10 0.19 612.92 01-DEC-07:05 0.27
           
Annual Sum or Average 0.136914E+11 0.19      
Minimum of Months 0.105030E+10 0.19 612.92   0.27
Maximum of Months 0.116283E+10 0.19 612.92   0.27



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.162857E+09 0.49 654.73 02-JAN-16:02 0.59
February 0.143276E+09 0.47 654.73 01-FEB-09:02 0.59
March 0.160592E+09 0.46 654.73 01-MAR-16:01 0.58
April 0.227419E+09 0.50 654.73 01-APR-15:02 0.59
May 0.213914E+09 0.48 654.73 01-MAY-08:62 0.58
June 0.274175E+09 0.51 654.73 01-JUN-15:02 0.58
July 0.374151E+09 0.54 654.73 01-JUL-08:62 0.58
August 0.385134E+09 0.54 654.73 01-AUG-08:62 0.58
September 0.313662E+09 0.53 654.73 01-SEP-08:62 0.58
October 0.309957E+09 0.52 654.73 01-OCT-08:62 0.58
November 0.174606E+09 0.50 654.73 01-NOV-08:62 0.58
December 0.174339E+09 0.50 654.73 01-DEC-09:02 0.58
           
Annual Sum or Average 0.291408E+10 0.50      
Minimum of Months 0.143276E+09 0.46 654.73   0.58
Maximum of Months 0.385134E+09 0.54 654.73   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.103972E+09 0.39 627.47 02-JAN-16:02 0.59
February 89702345.80 0.40 627.47 01-FEB-16:02 0.58
March 0.110133E+09 0.41 627.47 01-MAR-16:01 0.58
April 0.128382E+09 0.39 627.47 01-APR-15:02 0.59
May 0.139663E+09 0.37 627.47 01-MAY-08:51 0.58
June 0.165128E+09 0.33 627.47 01-JUN-08:51 0.58
July 0.231296E+09 0.33 627.47 01-JUL-08:51 0.58
August 0.216027E+09 0.33 627.47 01-AUG-08:51 0.58
September 0.162175E+09 0.33 627.47 01-SEP-08:51 0.58
October 0.147613E+09 0.33 627.47 01-OCT-08:52 0.58
November 84019857.33 0.39 627.47 01-NOV-08:62 0.58
December 96608922.36 0.39 627.47 02-DEC-16:02 0.58
           
Annual Sum or Average 0.167472E+10 0.37      
Minimum of Months 84019857.33 0.33 627.47   0.58
Maximum of Months 0.231296E+09 0.41 627.47   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.148425E+10 0.43 2180.84 22-JAN-13:30 0.58
February 0.931618E+09 0.34 2065.80 02-FEB-12:50 0.58
March 0.669817E+09 0.30 1216.32 12-MAR-12:30 0.59
April 0.769423E+09 0.40 933.50 08-APR-12:50 0.58
May 0.494261E+09 0.34 769.40 02-MAY-15:03 0.58
June 0.618402E+09 0.41 725.61 28-JUN-15:05 0.58
July 0.918285E+09 0.51 787.47 18-JUL-15:03 0.58
August 0.120981E+10 0.57 896.04 30-AUG-13:00 0.58
September 0.134880E+10 0.56 2145.87 30-SEP-13:30 0.58
October 0.177880E+10 0.54 2252.30 31-OCT-12:30 0.58
November 0.153546E+10 0.47 2396.26 19-NOV-12:30 0.59
December 0.170526E+10 0.45 2434.18 25-DEC-13:30 0.59
           
Annual Sum or Average 0.134642E+11 0.44      
Minimum of Months 0.494261E+09 0.30 725.61   0.58
Maximum of Months 0.177880E+10 0.57 2434.18   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.717903E+09 0.37 3541.55 01-JAN-09:02 0.58
February 0.694144E+09 0.38 3541.55 01-FEB-09:51 0.59
March 0.874056E+09 0.39 3541.55 01-MAR-09:02 0.59
April 0.109258E+10 0.34 3541.55 01-APR-08:62 0.59
May 0.133074E+10 0.33 3541.55 01-MAY-08:51 0.58
June 0.145765E+10 0.29 3541.55 01-JUN-08:51 0.58
July 0.175512E+10 0.29 3541.55 01-JUL-08:51 0.58
August 0.157208E+10 0.28 3541.55 01-AUG-08:51 0.58
September 0.122759E+10 0.28 3541.55 01-SEP-08:51 0.58
October 0.121535E+10 0.28 3541.55 01-OCT-08:52 0.58
November 0.751033E+09 0.35 3541.55 01-NOV-08:62 0.58
December 0.660896E+09 0.36 3541.55 01-DEC-09:02 0.58
           
Annual Sum or Average 0.133491E+11 0.33      
Minimum of Months 0.660896E+09 0.28 3541.55   0.58
Maximum of Months 0.175512E+10 0.39 3541.55   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.167738E+09 0.50 573.60 01-JAN-09:02 0.58
February 0.140533E+09 0.48 573.60 01-FEB-09:02 0.59
March 0.156171E+09 0.47 573.60 01-MAR-09:02 0.58
April 0.204505E+09 0.52 573.60 01-APR-08:62 0.58
May 0.181930E+09 0.50 573.60 01-MAY-08:62 0.58
June 0.228130E+09 0.52 573.60 01-JUN-08:62 0.58
July 0.336144E+09 0.55 573.60 01-JUL-08:62 0.58
August 0.362154E+09 0.55 573.60 01-AUG-08:62 0.58
September 0.266484E+09 0.53 573.60 01-SEP-08:62 0.58
October 0.291109E+09 0.53 573.60 01-OCT-08:62 0.58
November 0.170191E+09 0.51 573.60 01-NOV-08:62 0.58
December 0.176060E+09 0.51 573.60 01-DEC-09:02 0.58
           
Annual Sum or Average 0.268115E+10 0.52      
Minimum of Months 0.140533E+09 0.47 573.60   0.58
Maximum of Months 0.362154E+09 0.55 573.60   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 98995587.80 0.38 549.88 01-JAN-09:02 0.58
February 87980787.56 0.39 549.88 01-FEB-09:51 0.59
March 0.110585E+09 0.41 549.88 01-MAR-09:02 0.58
April 0.129842E+09 0.41 549.88 01-APR-08:62 0.58
May 0.129964E+09 0.39 549.88 01-MAY-08:51 0.58
June 0.152269E+09 0.34 549.88 01-JUN-08:51 0.58
July 0.221347E+09 0.34 549.88 01-JUL-08:51 0.58
August 0.216641E+09 0.34 549.88 01-AUG-08:51 0.58
September 0.142374E+09 0.34 549.88 01-SEP-08:51 0.58
October 0.139754E+09 0.35 549.88 01-OCT-08:52 0.58
November 81521136.52 0.36 549.88 01-NOV-08:62 0.58
December 91269646.51 0.37 549.88 01-DEC-09:02 0.58
           
Annual Sum or Average 0.160254E+10 0.37      
Minimum of Months 81521136.52 0.34 549.88   0.58
Maximum of Months 0.221347E+09 0.41 549.88   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 42915250.16 0.49 170.46 02-JAN-16:02 0.59
February 39304656.43 0.47 170.46 01-FEB-09:02 0.59
March 45567587.66 0.47 170.46 01-MAR-16:01 0.58
April 58816594.18 0.51 170.46 01-APR-15:02 0.59
May 54159383.62 0.49 170.46 01-MAY-08:62 0.58
June 69422064.39 0.52 170.46 01-JUN-15:02 0.58
July 96425423.33 0.54 170.46 01-JUL-08:62 0.58
August 97910476.01 0.54 170.46 01-AUG-08:62 0.58
September 75748731.03 0.53 170.46 01-SEP-08:62 0.58
October 73380107.09 0.52 170.46 01-OCT-08:62 0.58
November 42773843.85 0.50 170.46 01-NOV-08:62 0.58
December 45044615.34 0.50 170.46 01-DEC-16:02 0.58
           
Annual Sum or Average 0.741469E+09 0.51      
Minimum of Months 39304656.43 0.47 170.46   0.58
Maximum of Months 97910476.01 0.54 170.46   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 33460438.97 0.39 162.90 01-JAN-09:02 0.58
February 27832262.03 0.40 162.90 01-FEB-16:02 0.58
March 33298734.81 0.41 162.90 01-MAR-16:01 0.58
April 32970734.93 0.40 162.90 01-APR-15:02 0.59
May 35059248.08 0.38 162.90 01-MAY-08:51 0.58
June 43406811.05 0.34 162.90 01-JUN-08:51 0.58
July 62674552.65 0.33 162.90 01-JUL-08:51 0.58
August 56853832.46 0.33 162.90 01-AUG-08:51 0.58
September 38628208.67 0.34 162.90 01-SEP-08:51 0.58
October 34438243.53 0.33 162.90 01-OCT-08:52 0.58
November 24819036.95 0.39 162.90 01-NOV-15:01 0.58
December 31319295.74 0.39 162.90 02-DEC-16:02 0.58
           
Annual Sum or Average 0.454761E+09 0.37      
Minimum of Months 24819036.95 0.33 162.90   0.58
Maximum of Months 62674552.65 0.41 162.90   0.59



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.471819E+09 0.53 787.05 01-JAN-09:02 0.58
February 0.315918E+09 0.50 787.05 01-FEB-09:02 0.59
March 0.282008E+09 0.49 787.05 01-MAR-09:02 0.58
April 0.281122E+09 0.51 787.05 01-APR-08:62 0.59
May 0.195202E+09 0.48 787.05 01-MAY-08:62 0.58
June 0.225148E+09 0.49 787.05 01-JUN-15:02 0.58
July 0.335761E+09 0.53 787.05 01-JUL-08:62 0.58
August 0.416193E+09 0.53 787.05 01-AUG-08:62 0.58
September 0.427416E+09 0.52 787.05 01-SEP-08:62 0.58
October 0.561591E+09 0.53 787.05 01-OCT-08:62 0.58
November 0.456043E+09 0.54 787.05 01-NOV-08:62 0.58
December 0.508741E+09 0.54 787.05 01-DEC-09:02 0.58
           
Annual Sum or Average 0.447696E+10 0.52      
Minimum of Months 0.195202E+09 0.48 787.05   0.58
Maximum of Months 0.561591E+09 0.54 787.05   0.59



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.466853E+09 0.424370E+09 544.98 03-JAN-05:00 495.39 495.39 46.68 1.21
February 0.356753E+09 0.324289E+09 519.41 04-FEB-05:55 472.14 472.14 47.37 1.03
March 0.489790E+09 0.445219E+09 543.30 30-MAR-03:00 493.86 493.86 46.57 1.19
April 0.200345E+09 0.182114E+09 512.07 01-APR-06:00 465.47 465.47 47.11 0.99
May 0.176275E+09 0.160234E+09 452.26 14-MAY-04:50 411.11 411.11 44.12 0.74
June 32977826.48 29976844.27 273.34 13-JUN-04:00 248.46 248.46 35.97 0.35
July 3260071.81 2963405.27 117.40 06-JUL-03:00 106.72 106.72 27.00 0.13
August 2292018.56 2083444.87 121.61 22-AUG-08:54 110.54 110.54 29.99 0.14
September 16263356.58 14783391.13 261.36 20-SEP-04:00 237.57 237.57 34.84 0.33
October 71892894.03 65350640.67 396.70 12-OCT-05:00 360.60 360.60 41.31 0.59
November 0.290570E+09 0.264128E+09 504.28 05-NOV-06:00 458.39 458.39 47.26 0.95
December 0.453559E+09 0.412285E+09 526.05 13-DEC-06:00 478.18 478.18 47.81 1.07
                 
Annual Sum or Average 0.256083E+10 0.232780E+10            
Minimum of Months 2292018.56 2083444.87 117.40   106.72 106.72 27.00 0.13
Maximum of Months 0.489790E+09 0.445219E+09 544.98   495.39 495.39 47.81 1.21



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.140550E+09 0.127760E+09 884.62 24-JAN-16:03 804.12 804.12 7.19 11.72
February 85191454.95 77439032.55 494.71 01-FEB-13:10 449.69 449.69 7.24 9.10
March 89679250.06 81518438.30 726.93 23-MAR-15:03 660.78 660.78 7.46 10.77
April 0.183395E+09 0.166706E+09 778.62 13-APR-09:02 707.77 707.77 7.42 11.10
May 0.172504E+09 0.156806E+09 792.35 18-MAY-15:03 720.24 720.24 7.46 11.18
June 0.302748E+09 0.275198E+09 1106.96 29-JUN-18:03 1006.23 1006.23 7.50 12.90
July 0.793309E+09 0.721118E+09 2075.02 18-JUL-18:03 1886.20 1886.20 7.22 16.74
August 0.931820E+09 0.847024E+09 1969.52 14-AUG-10:50 1790.29 1790.29 6.73 16.39
September 0.541657E+09 0.492366E+09 3572.62 29-SEP-15:20 3247.51 3247.51 6.73 20.84
October 0.609420E+09 0.553963E+09 2511.84 17-OCT-10:45 2283.26 2283.26 6.73 18.10
November 0.154966E+09 0.140864E+09 1462.43 19-NOV-11:00 1329.35 1329.35 6.84 14.50
December 0.132388E+09 0.120341E+09 846.91 16-DEC-16:03 769.84 769.84 7.67 11.51
                 
Annual Sum or Average 0.413763E+10 0.376110E+10            
Minimum of Months 85191454.95 77439032.55 494.71   449.69 449.69 6.73 9.10
Maximum of Months 0.931820E+09 0.847024E+09 3572.62   3247.51 3247.51 7.67 20.84



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.787847E+10 0.716153E+10 3310.50 01-JAN-00:10 3009.25 3009.25 8.40 23.43
February 0.723616E+10 0.657767E+10 3310.50 01-FEB-00:03 3009.25 3009.25 8.47 23.43
March 0.753927E+10 0.685320E+10 3310.50 01-MAR-00:03 3009.25 3009.25 8.40 23.43
April 0.844758E+10 0.767885E+10 3310.50 01-APR-06:20 3009.25 3009.25 8.40 23.43
May 0.878740E+10 0.798775E+10 3310.50 01-MAY-00:05 3009.25 3009.25 8.84 23.43
June 0.858082E+10 0.779997E+10 3310.50 01-JUN-00:05 3009.25 3009.25 8.58 23.43
July 0.886685E+10 0.805997E+10 3310.50 01-JUL-00:10 3009.25 3009.25 9.33 23.43
August 0.886685E+10 0.805997E+10 3310.50 01-AUG-00:05 3009.25 3009.25 9.80 23.43
September 0.858082E+10 0.779997E+10 3310.50 01-SEP-00:05 3009.25 3009.25 8.99 23.43
October 0.886685E+10 0.805997E+10 3310.50 01-OCT-00:10 3009.25 3009.25 9.89 23.43
November 0.827096E+10 0.751830E+10 3310.50 01-NOV-00:05 3009.25 3009.25 8.74 23.43
December 0.818919E+10 0.744397E+10 3310.50 01-DEC-00:03 3009.25 3009.25 8.51 23.43
                 
Annual Sum or Average 0.100111E+12 0.910011E+11            
Minimum of Months 0.723616E+10 0.657767E+10 3310.50   3009.25 3009.25 8.40 23.43
Maximum of Months 0.886685E+10 0.805997E+10 3310.50   3009.25 3009.25 9.89 23.43



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:10 14.37 14.37 50.41 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:03 14.37 14.37 50.84 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:03 14.37 14.37 50.88 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 53.52 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:05 14.37 14.37 53.47 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:05 14.37 14.37 53.64 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 53.94 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:05 14.37 14.37 53.81 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:05 14.37 14.37 53.78 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 53.11 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:05 14.37 14.37 53.50 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:03 14.37 14.37 51.07 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 50.41 0.37
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 53.94 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 42.47 79.60 42936.45 175069.70 08-JAN-07:00
February 0.00 0.00 01-FEB-00:03 32.07 79.40 34338.52 141382.69 04-FEB-06:00
March 0.00 0.00 01-MAR-00:03 44.93 79.80 44560.61 168884.07 30-MAR-03:00
April 0.00 0.00 01-APR-00:10 41.62 79.46 18202.46 135442.55 01-APR-06:00
May 0.00 0.00 01-MAY-00:05 32.08 32.08 15521.56 111864.07 15-MAY-02:00
June 0.00 0.00 01-JUN-00:05 26.51 79.40 3012.44 63289.34 13-JUN-04:00
July 0.00 0.00 01-JUL-00:10 26.72 26.72 279.54 28659.63 06-JUL-03:00
August 0.00 0.00 01-AUG-00:05 26.22 26.22 194.25 28062.88 22-AUG-08:54
September 0.00 0.00 01-SEP-00:05 31.21 31.21 1474.19 61482.47 20-SEP-03:00
October 0.00 0.00 01-OCT-00:10 32.29 32.29 6294.39 94516.68 12-OCT-05:00
November 0.00 0.00 01-NOV-00:05 30.55 30.55 26303.59 131764.70 29-NOV-22:50
December 0.00 0.00 01-DEC-00:03 35.46 79.40 40937.63 146582.49 23-DEC-06:00
                 
Annual Sum or Average 0.00         19462.24    
Minimum of Months 0.00 0.00   26.22 26.22 194.25 28062.88  
Maximum of Months 0.00 0.00   44.93 79.80 44560.61 175069.70  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 45853.37 305663.19 14-JAN-16:03 10.37 7.26 0.00 0.00 01-JAN-00:10
February 33578.51 292561.59 01-FEB-09:51 10.09 7.11 0.00 0.00 01-FEB-00:03
March 30910.93 325473.59 23-MAR-15:03 10.75 7.43 0.00 0.00 01-MAR-00:03
April 59012.11 308341.99 11-APR-15:03 10.42 7.28 0.00 0.00 01-APR-00:10
May 57374.04 328844.61 18-MAY-15:02 10.78 7.43 0.00 0.00 01-MAY-00:05
June 97768.22 387939.80 28-JUN-15:05 11.23 7.28 0.00 0.00 01-JUN-00:05
July 176714.90 508677.19 18-JUL-18:03 12.39 7.21 0.00 0.00 01-JUL-00:10
August 197578.70 533429.11 18-AUG-15:03 12.16 6.73 0.00 0.00 01-AUG-00:05
September 131955.92 488776.39 29-SEP-15:03 11.68 6.70 0.00 0.00 01-SEP-00:05
October 141474.00 479352.33 14-OCT-15:03 11.58 6.70 0.00 0.00 01-OCT-00:10
November 50768.23 365598.59 19-NOV-09:41 10.58 6.86 0.00 0.00 01-NOV-00:05
December 51436.98 353815.03 05-DEC-09:41 10.46 6.86 0.00 0.00 01-DEC-00:03
                 
Annual Sum or Average 90046.47         0.00    
Minimum of Months 30910.93 292561.59   10.09 6.70 0.00 0.00  
Maximum of Months 197578.70 533429.11   12.39 7.43 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 50.41 59.99 23227.75 48614.09 31-JAN-07:40
February 0.00 0.00 01-FEB-00:03 50.84 60.00 23257.66 48612.52 02-FEB-07:40
March 0.00 0.00 01-MAR-00:03 50.88 60.00 23026.32 48372.71 01-MAR-07:40
April 0.00 0.00 01-APR-00:10 53.52 59.99 22543.26 47475.08 03-APR-06:40
May 0.00 0.00 01-MAY-00:05 53.47 59.99 21983.01 46415.18 01-MAY-06:30
June 0.00 0.00 01-JUN-00:05 53.64 59.99 21484.24 45225.79 01-JUN-07:00
July 0.00 0.00 01-JUL-00:10 53.94 59.97 21152.28 44309.71 03-JUL-07:00
August 0.00 0.00 01-AUG-00:05 53.81 59.99 21141.87 44222.92 31-AUG-07:00
September 0.00 0.00 01-SEP-00:05 53.78 59.99 21387.16 44972.49 29-SEP-07:00
October 0.00 0.00 01-OCT-00:10 53.11 59.97 21851.24 46152.29 31-OCT-07:00
November 0.00 0.00 01-NOV-00:05 53.50 59.97 22418.00 47334.44 30-NOV-07:40
December 0.00 0.00 01-DEC-00:03 51.07 60.00 22919.02 48205.49 29-DEC-07:40
                 
Annual Sum or Average 0.00         22193.26    
Minimum of Months 0.00 0.00   50.41 59.97 21141.87 44222.92  
Maximum of Months 0.00 0.00   53.94 60.00 23257.66 48614.09  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.101257E+12 0.00 0.573504E+11 0.374631E+11 0.00 0.00
February 0.738188E+11 0.00 0.321104E+11 0.339587E+11 0.00 0.00
March 0.105976E+12 0.00 0.358885E+11 0.375236E+11 0.00 0.00
April 0.427178E+11 0.00 0.849640E+11 0.369684E+11 0.00 0.00
May 0.376587E+11 0.00 0.906417E+11 0.384667E+11 0.00 0.00
June 0.713892E+10 0.00 0.168642E+12 0.379067E+11 0.00 0.00
July 0.689129E+09 0.00 0.344426E+12 0.395370E+11 0.00 0.00
August 0.474632E+09 0.00 0.387778E+12 0.396896E+11 0.00 0.00
September 0.346496E+10 0.00 0.228692E+12 0.378979E+11 0.00 0.00
October 0.153432E+11 0.00 0.256993E+12 0.395283E+11 0.00 0.00
November 0.610449E+11 0.00 0.597973E+11 0.367578E+11 0.00 0.00
December 0.974245E+11 0.00 0.660005E+11 0.377833E+11 0.00 0.00
             
Annual Sum or Average 0.547009E+12 0.00 0.181328E+13 0.453481E+12 0.00 0.00
Minimum of Months 0.474632E+09 0.00 0.321104E+11 0.339587E+11 0.00 0.00
Maximum of Months 0.105976E+12 0.00 0.387778E+12 0.396896E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.928991E+10 0.00 0.353274E+10 0.271000E+10 0.00 0.00
February 0.678991E+10 0.00 0.189886E+10 0.244774E+10 0.00 0.00
March 0.958200E+10 0.00 0.215372E+10 0.271000E+10 0.00 0.00
April 0.408463E+10 0.00 0.541905E+10 0.262258E+10 0.00 0.00
May 0.364901E+10 0.00 0.572637E+10 0.271000E+10 0.00 0.00
June 0.639388E+09 0.00 0.129295E+11 0.262258E+10 0.00 0.00
July 37018068.72 0.00 0.288160E+11 0.271000E+10 0.00 0.00
August 17472305.07 0.00 0.328487E+11 0.271000E+10 0.00 0.00
September 0.319026E+09 0.00 0.187456E+11 0.262258E+10 0.00 0.00
October 0.143957E+10 0.00 0.207096E+11 0.271000E+10 0.00 0.00
November 0.588912E+10 0.00 0.355504E+10 0.262258E+10 0.00 0.00
December 0.908993E+10 0.00 0.428780E+10 0.271000E+10 0.00 0.00
             
Annual Sum or Average 0.508270E+11 0.00 0.140623E+12 0.319080E+11 0.00 0.00
Minimum of Months 17472305.07 0.00 0.189886E+10 0.244774E+10 0.00 0.00
Maximum of Months 0.958200E+10 0.00 0.328487E+11 0.271000E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.374631E+11 0.573504E+11 0.101257E+12 0.00 0.00 0.00 0.00 0.00
February 0.339587E+11 0.321104E+11 0.738188E+11 0.00 0.00 0.00 0.00 0.00
March 0.375236E+11 0.358885E+11 0.105976E+12 0.00 0.00 0.00 0.00 0.00
April 0.369684E+11 0.849640E+11 0.427178E+11 0.00 0.00 0.00 0.00 0.00
May 0.384667E+11 0.906417E+11 0.376587E+11 0.00 0.00 0.00 0.00 0.00
June 0.379067E+11 0.168642E+12 0.713892E+10 0.00 0.00 0.00 0.00 0.00
July 0.395370E+11 0.344426E+12 0.689129E+09 0.00 0.00 0.00 0.00 0.00
August 0.396896E+11 0.387778E+12 0.474632E+09 0.00 0.00 0.00 0.00 0.00
September 0.378979E+11 0.228692E+12 0.346496E+10 0.00 0.00 0.00 0.00 0.00
October 0.395283E+11 0.256993E+12 0.153432E+11 0.00 0.00 0.00 0.00 0.00
November 0.367578E+11 0.597973E+11 0.610449E+11 0.00 0.00 0.00 0.00 0.00
December 0.377833E+11 0.660005E+11 0.974245E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.453481E+12 0.181328E+13 0.547009E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.339587E+11 0.321104E+11 0.474632E+09 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.396896E+11 0.387778E+12 0.105976E+12 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.271000E+10 0.353274E+10 0.928991E+10 0.00 0.00 0.00 0.00 0.00
February 0.244774E+10 0.189886E+10 0.678991E+10 0.00 0.00 0.00 0.00 0.00
March 0.271000E+10 0.215372E+10 0.958200E+10 0.00 0.00 0.00 0.00 0.00
April 0.262258E+10 0.541905E+10 0.408463E+10 0.00 0.00 0.00 0.00 0.00
May 0.271000E+10 0.572637E+10 0.364901E+10 0.00 0.00 0.00 0.00 0.00
June 0.262258E+10 0.129295E+11 0.639388E+09 0.00 0.00 0.00 0.00 0.00
July 0.271000E+10 0.288160E+11 37018068.72 0.00 0.00 0.00 0.00 0.00
August 0.271000E+10 0.328487E+11 17472305.07 0.00 0.00 0.00 0.00 0.00
September 0.262258E+10 0.187456E+11 0.319026E+09 0.00 0.00 0.00 0.00 0.00
October 0.271000E+10 0.207096E+11 0.143957E+10 0.00 0.00 0.00 0.00 0.00
November 0.262258E+10 0.355504E+10 0.588912E+10 0.00 0.00 0.00 0.00 0.00
December 0.271000E+10 0.428780E+10 0.908993E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.319080E+11 0.140623E+12 0.508270E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.244774E+10 0.189886E+10 17472305.07 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.271000E+10 0.328487E+11 0.958200E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.374631E+11 0.101257E+12 0.573504E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.339587E+11 0.738188E+11 0.321104E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.375236E+11 0.105976E+12 0.358885E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.369684E+11 0.427178E+11 0.849640E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.384667E+11 0.376587E+11 0.906417E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.379067E+11 0.713892E+10 0.168642E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.395370E+11 0.689129E+09 0.344426E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.396896E+11 0.474632E+09 0.387778E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.378979E+11 0.346496E+10 0.228692E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.395283E+11 0.153432E+11 0.256993E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.367578E+11 0.610449E+11 0.597973E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.377833E+11 0.974245E+11 0.660005E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.453481E+12 0.547009E+12 0.181328E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.339587E+11 0.474632E+09 0.321104E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.396896E+11 0.105976E+12 0.387778E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.271000E+10 0.928991E+10 0.353274E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.244774E+10 0.678991E+10 0.189886E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.271000E+10 0.958200E+10 0.215372E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.262258E+10 0.408463E+10 0.541905E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.271000E+10 0.364901E+10 0.572637E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.262258E+10 0.639388E+09 0.129295E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.271000E+10 37018068.72 0.288160E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.271000E+10 17472305.07 0.328487E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.262258E+10 0.319026E+09 0.187456E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.271000E+10 0.143957E+10 0.207096E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.262258E+10 0.588912E+10 0.355504E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.271000E+10 0.908993E+10 0.428780E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.319080E+11 0.508270E+11 0.140623E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.244774E+10 17472305.07 0.189886E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.271000E+10 0.958200E+10 0.328487E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.446849E+11 0.00 0.00 45661.10 65771774.86 0.00 0.807009E+09 0.00 0.85
February 0.404643E+11 0.00 0.00 0.00 14137019.00 0.00 0.00 0.00 0.86
March 0.465814E+11 0.00 0.00 0.00 329127.20 0.00 0.00 0.00 0.86
April 0.362092E+11 0.00 0.00 0.00 75786972.36 0.00 0.00 0.00 0.86
May 0.363905E+11 0.00 0.00 0.00 9624392.85 0.00 0.00 0.00 0.86
June 0.268399E+11 0.00 0.00 0.00 0.573865E+09 0.00 0.00 0.00 0.86
July 0.171892E+11 0.00 0.00 0.00 0.424089E+10 0.00 0.00 0.00 0.86
August 0.146318E+11 0.00 0.00 0.00 0.512157E+10 0.00 0.00 0.00 0.86
September 0.234114E+11 0.00 0.00 0.00 0.159360E+10 0.00 0.00 0.00 0.86
October 0.230399E+11 15728340.69 0.00 460843.48 0.270383E+10 0.00 0.189211E+10 0.00 0.86
November 0.355435E+11 0.00 0.00 1534608.53 46148912.90 0.00 0.521604E+10 0.00 0.86
December 0.428074E+11 0.00 0.00 180822.63 26427019.60 0.00 0.171813E+10 0.00 0.85
                   
Annual Sum or Average 0.387794E+12 15728340.69 0.00 2221935.74 0.144720E+11 0.00 0.963329E+10 0.00 0.86
Minimum of Months 0.146318E+11 0.00 0.00 0.00 329127.20 0.00 0.00 0.00 0.85
Maximum of Months 0.465814E+11 15728340.69 0.00 1534608.53 0.512157E+10 0.00 0.521604E+10 0.00 0.86



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.647654E+10 13810005.87 0.00 1859567.91 667844.10 0.00 0.748160E+09 0.00 2.49
February 0.593330E+10 2748500.27 0.00 1096603.99 0.00 0.00 0.456637E+09 0.00 2.47
March 0.707563E+10 17117.80 0.00 426805.02 34668.97 80899947.82 0.173467E+09 0.00 2.45
April 0.562290E+10 3916671.38 0.00 80988.50 8008087.79 0.00 74387536.82 0.00 2.44
May 0.572583E+10 256682.15 0.00 118.17 1257675.30 0.00 68320.27 0.00 2.44
June 0.422314E+10 0.00 0.00 0.00 90295286.65 0.00 0.00 0.00 2.45
July 0.270465E+10 30916515.54 0.00 0.00 0.636369E+09 0.00 0.00 0.00 2.45
August 0.228739E+10 0.311926E+09 0.00 19112.31 0.493931E+09 0.00 14851489.63 0.00 2.46
September 0.349544E+10 0.183931E+09 0.00 586506.88 0.103892E+09 0.00 0.188572E+09 0.00 2.49
October 0.349115E+10 0.430252E+09 0.00 1498825.08 0.121068E+09 0.00 0.449840E+09 0.00 2.58
November 0.583450E+10 10989542.17 0.00 2000301.73 0.00 0.00 0.637614E+09 0.00 2.51
December 0.636363E+10 6152621.54 0.00 2765808.90 0.00 0.00 0.719456E+09 0.00 2.54
                   
Annual Sum or Average 0.592341E+11 0.994916E+09 0.00 10334638.49 0.145552E+10 80899947.82 0.346305E+10 0.00 2.48
Minimum of Months 0.228739E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.44
Maximum of Months 0.707563E+10 0.430252E+09 0.00 2765808.90 0.636369E+09 80899947.82 0.748160E+09 0.00 2.58



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.464074E+10 0.00 0.00 90586.03 7279002.49 0.00 0.393797E+09 0.00 1.48
February 0.406421E+10 0.00 0.00 113026.29 1564552.53 0.00 0.413890E+09 0.00 1.49
March 0.488572E+10 0.00 0.00 74563.72 36424.71 0.00 0.269388E+09 0.00 1.49
April 0.342874E+10 0.00 0.00 252093.82 8387390.51 0.00 0.578334E+09 0.00 1.49
May 0.358427E+10 0.00 0.00 190972.57 1065137.43 0.00 0.442966E+09 0.00 1.49
June 0.232174E+10 0.00 0.00 488545.22 63510031.51 0.00 0.648922E+09 0.00 1.49
July 0.108103E+10 6880749.01 0.00 1077638.23 0.462465E+09 0.00 0.823375E+09 0.00 1.50
August 0.583495E+09 4591091.57 0.00 1485588.71 0.562216E+09 0.00 0.104395E+10 0.00 1.51
September 0.151333E+10 29334274.41 0.00 975237.80 0.147043E+09 0.00 0.108537E+10 0.00 1.51
October 0.168351E+10 35577334.57 0.00 1215488.17 0.265447E+09 0.00 0.109548E+10 0.00 1.50
November 0.377675E+10 0.00 0.00 253153.37 5107328.37 0.00 0.734050E+09 0.00 1.48
December 0.438302E+10 0.00 0.00 203593.93 2924694.40 0.00 0.544471E+09 0.00 1.48
                   
Annual Sum or Average 0.359466E+11 76383449.56 0.00 6420487.86 0.152705E+10 0.00 0.807400E+10 0.00 1.49
Minimum of Months 0.583495E+09 0.00 0.00 74563.72 36424.71 0.00 0.269388E+09 0.00 1.48
Maximum of Months 0.488572E+10 35577334.57 0.00 1485588.71 0.562216E+09 0.00 0.109548E+10 0.00 1.51



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.411629E+10 0.00 0.00 0.00 5951282.37 0.00 0.00 0.00 0.57
February 0.366137E+10 0.00 0.00 0.00 1279171.68 0.00 0.00 0.00 0.57
March 0.421486E+10 0.00 0.00 0.00 29780.69 0.00 0.00 0.00 0.57
April 0.327635E+10 0.00 0.00 0.00 6857495.84 0.00 0.00 0.00 0.57
May 0.329276E+10 0.00 0.00 0.00 870851.97 0.00 0.00 0.00 0.57
June 0.242858E+10 0.00 0.00 0.00 51925539.46 0.00 0.00 0.00 0.58
July 0.155535E+10 0.00 0.00 0.00 0.383732E+09 0.00 0.00 0.00 0.58
August 0.132394E+10 0.00 0.00 0.00 0.463419E+09 0.00 0.00 0.00 0.58
September 0.211691E+10 0.00 0.00 188.10 0.144195E+09 0.00 1442553.96 0.00 0.58
October 0.223861E+10 0.00 0.00 7165.86 0.246076E+09 0.00 17368352.95 0.00 0.58
November 0.368822E+10 0.00 0.00 0.00 4175730.58 0.00 0.00 0.00 0.57
December 0.402886E+10 0.00 0.00 0.00 2391218.06 0.00 0.00 0.00 0.57
                   
Annual Sum or Average 0.359421E+11 0.00 0.00 7353.96 0.131090E+10 0.00 18810906.91 0.00 0.57
Minimum of Months 0.132394E+10 0.00 0.00 0.00 29780.69 0.00 0.00 0.00 0.57
Maximum of Months 0.421486E+10 0.00 0.00 7165.86 0.463419E+09 0.00 17368352.95 0.00 0.58



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.219079E+10 0.00 0.00 0.00 3167422.78 0.00 0.00 0.00 0.53
February 0.194867E+10 0.00 0.00 0.00 680807.48 0.00 0.00 0.00 0.53
March 0.224325E+10 0.00 0.00 0.00 15850.04 0.00 0.00 0.00 0.53
April 0.174375E+10 0.00 0.00 0.00 3649732.48 0.00 0.00 0.00 0.53
May 0.175249E+10 0.00 0.00 0.00 463489.41 0.00 0.00 0.00 0.53
June 0.129255E+10 0.00 0.00 0.00 27636083.54 0.00 0.00 0.00 0.53
July 0.827794E+09 0.00 0.00 0.00 0.204232E+09 0.00 0.00 0.00 0.53
August 0.704636E+09 0.00 0.00 0.00 0.246643E+09 0.00 0.00 0.00 0.53
September 0.112744E+10 0.00 0.00 0.00 76744062.77 0.00 0.00 0.00 0.53
October 0.120069E+10 0.00 0.00 0.00 0.130968E+09 0.00 0.00 0.00 0.53
November 0.196296E+10 0.00 0.00 0.00 2222429.28 0.00 0.00 0.00 0.53
December 0.214426E+10 0.00 0.00 0.00 1272666.64 0.00 0.00 0.00 0.53
                   
Annual Sum or Average 0.191393E+11 0.00 0.00 0.00 0.697696E+09 0.00 0.00 0.00 0.53
Minimum of Months 0.704636E+09 0.00 0.00 0.00 15850.04 0.00 0.00 0.00 0.53
Maximum of Months 0.224325E+10 0.00 0.00 0.00 0.246643E+09 0.00 0.00 0.00 0.53



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.358541E+09 0.112764E+09 0.00 93234563.06 0.00 0.00 0.865667E+11 0.00 25.06
February 0.458637E+09 24183292.01 0.00 82694385.92 54272.11 0.00 0.768410E+11 0.00 25.24
March 0.457877E+09 564280.32 0.00 91144360.91 0.00 0.00 0.886009E+11 0.00 25.28
April 0.385002E+09 0.129762E+09 0.00 97991242.63 173011.29 0.00 0.689215E+11 0.00 25.20
May 0.460606E+09 16500779.90 0.00 0.105948E+09 0.00 0.00 0.692440E+11 0.00 25.24
June 0.304779E+09 0.973638E+09 0.00 0.106738E+09 15837741.16 0.00 0.512796E+11 0.00 25.30
July 0.178363E+09 0.723958E+10 0.00 90852496.26 0.177173E+09 0.00 0.322840E+11 0.00 25.24
August 0.115493E+09 0.857716E+10 0.00 84113377.57 0.292120E+09 0.00 0.278496E+11 0.00 25.37
September 0.249385E+09 0.273348E+10 0.00 93081132.59 40555882.25 0.00 0.444242E+11 0.00 25.36
October 0.248763E+09 0.466985E+10 0.00 87449950.27 0.106891E+09 0.00 0.474968E+11 0.00 25.27
November 0.424804E+09 79121152.47 0.00 91586089.74 0.00 0.00 0.775921E+11 0.00 25.19
December 0.389082E+09 44295603.18 0.00 93682686.73 1123597.70 0.00 0.849036E+11 0.00 25.09
                   
Annual Sum or Average 0.403133E+10 0.246009E+11 0.00 0.111852E+10 0.633928E+09 0.00 0.756004E+12 0.00 25.24
Minimum of Months 0.115493E+09 564280.32 0.00 82694385.92 0.00 0.00 0.278496E+11 0.00 25.06
Maximum of Months 0.460606E+09 0.857716E+10 0.00 0.106738E+09 0.292120E+09 0.00 0.886009E+11 0.00 25.37



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.826684E+10 56812991.81 0.00 19803536.11 1676269.48 0.00 0.242047E+11 0.00 3.98
February 0.943248E+10 11045399.27 0.00 14169160.76 0.00 0.00 0.193187E+11 0.00 3.95
March 0.150818E+11 77098.69 0.00 9372973.73 156149.26 0.00 0.179245E+11 0.00 3.93
April 0.916148E+10 35337969.31 0.00 9172776.20 18371222.00 0.00 0.164903E+11 0.00 3.92
May 0.113448E+11 3147937.85 0.00 6720946.40 3672737.80 0.00 0.144389E+11 0.00 3.92
June 0.664477E+10 15890654.54 0.00 9027736.92 0.390800E+09 0.00 0.123673E+11 0.00 3.93
July 0.299682E+10 0.118685E+10 0.00 12346441.26 0.181861E+10 0.00 0.917394E+10 0.00 3.94
August 0.163090E+10 0.217062E+10 0.00 16004857.82 0.145896E+10 0.00 0.873795E+10 0.00 3.96
September 0.326158E+10 0.889730E+09 0.00 17651827.51 0.301268E+09 0.00 0.133751E+11 0.00 3.99
October 0.293971E+10 0.186137E+10 0.00 23364763.42 0.302645E+09 0.00 0.150007E+11 0.00 4.08
November 0.541529E+10 43287192.56 0.00 21770770.58 0.00 0.00 0.236832E+11 0.00 4.00
December 0.698930E+10 23853207.74 0.00 25161409.16 0.00 0.00 0.248837E+11 0.00 4.04
                   
Annual Sum or Average 0.831658E+11 0.629802E+10 0.00 0.184567E+09 0.429616E+10 0.00 0.199599E+12 0.00 3.97
Minimum of Months 0.163090E+10 77098.69 0.00 6720946.40 0.00 0.00 0.873795E+10 0.00 3.92
Maximum of Months 0.150818E+11 0.217062E+10 0.00 25161409.16 0.181861E+10 0.00 0.248837E+11 0.00 4.08



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.516684E+11 48212763.13 0.00 26617114.36 0.103585E+09 0.00 0.535194E+11 0.00 1.84
February 0.463768E+11 0.00 0.00 21988754.06 32627434.12 0.00 0.472119E+11 0.00 1.85
March 0.624313E+11 0.00 0.00 17105652.38 759606.82 0.00 0.451341E+11 0.00 1.85
April 0.372222E+11 0.00 0.00 26671201.96 0.174912E+09 0.00 0.464991E+11 0.00 1.85
May 0.367798E+11 0.00 0.00 26929674.87 22212550.16 0.00 0.473160E+11 0.00 1.85
June 0.201402E+11 1453877.84 0.00 41629249.15 0.132299E+10 0.00 0.420840E+11 0.00 1.86
July 0.788195E+10 0.321369E+09 0.00 58051445.42 0.946664E+10 0.00 0.321715E+11 0.00 1.87
August 0.457800E+10 0.302807E+09 0.00 65981919.70 0.115175E+11 0.00 0.298359E+11 0.00 1.88
September 0.138515E+11 0.130680E+10 0.00 54391234.00 0.238481E+10 0.00 0.409234E+11 0.00 1.89
October 0.118142E+11 0.349857E+10 0.00 62361092.42 0.278953E+10 0.00 0.472827E+11 0.00 1.90
November 0.344933E+11 90272432.08 0.00 36125704.32 16236628.65 0.00 0.600780E+11 0.00 1.85
December 0.420514E+11 33554738.71 0.00 33279382.97 27437316.34 0.00 0.611870E+11 0.00 1.84
                   
Annual Sum or Average 0.369289E+12 0.560304E+10 0.00 0.471132E+09 0.278592E+11 0.00 0.553243E+12 0.00 1.86
Minimum of Months 0.457800E+10 0.00 0.00 17105652.38 759606.82 0.00 0.298359E+11 0.00 1.84
Maximum of Months 0.624313E+11 0.349857E+10 0.00 65981919.70 0.115175E+11 0.00 0.611870E+11 0.00 1.90



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 8966857.22 2715043.96 8410.09 6340855.10 769203.73 0.658878E+09 0.116213E+10 755.51 0.35
February 28358844.31 1762400.13 0.00 5903100.55 0.00 0.438387E+09 0.112373E+10 0.00 0.36
March 40023695.87 2275830.24 0.00 6155689.72 0.00 0.690727E+09 0.111742E+10 0.00 0.36
April 15718408.72 5221945.12 0.00 11803424.06 0.00 74503427.82 0.122744E+10 0.00 0.36
May 24960224.04 2056814.79 0.00 12357278.87 0.00 67797202.72 0.124024E+10 0.00 0.36
June 9127435.99 32113395.08 0.00 13222140.62 47259.05 1557198.52 0.785760E+09 0.00 0.36
July 0.00 0.206262E+09 13515.17 11645387.43 0.00 760337.24 0.368099E+09 2037.15 0.36
August 0.00 0.268876E+09 38731.14 9082956.62 0.00 563006.11 0.274184E+09 4703.83 0.36
September 1683118.48 84235520.51 13560.68 11682021.22 2557133.65 1682455.16 0.604722E+09 2498.19 0.36
October 3445396.43 0.171007E+09 93789.97 9491166.28 0.00 2978797.68 0.871217E+09 7064.57 0.36
November 10345046.91 2813923.70 0.00 7983739.39 228314.00 0.213681E+09 0.133897E+10 0.00 0.35
December 12932211.28 4899602.51 0.00 7116490.44 0.00 0.537280E+09 0.123219E+10 0.00 0.35
                   
Annual Sum or Average 0.155561E+09 0.784239E+09 168007.05 0.112784E+09 3601910.43 0.268880E+10 0.113461E+11 17059.25 0.36
Minimum of Months 0.00 1762400.13 0.00 5903100.55 0.00 563006.11 0.274184E+09 0.00 0.35
Maximum of Months 40023695.87 0.268876E+09 93789.97 13222140.62 2557133.65 0.690727E+09 0.133897E+10 7064.57 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.122528E+09 1315971.39 23730.50 2368977.73 2148196.15 0.107722E+10 0.633979E+09 5105.94 0.35
February 0.108180E+09 701894.05 643.06 2863265.76 1057417.39 0.697971E+09 0.787177E+09 2239.13 0.36
March 0.106105E+09 546522.40 0.00 3499576.83 1729041.20 0.852678E+09 0.891830E+09 0.00 0.36
April 0.163989E+09 3622265.14 0.00 7888375.51 1599068.16 93687352.61 0.106374E+10 0.00 0.36
May 0.230916E+09 1922758.65 0.00 9693515.23 133815.15 54632104.37 0.104995E+10 0.00 0.36
June 0.305189E+09 25533532.15 43498.81 9255009.56 6575649.56 1168300.91 0.493960E+09 4205.52 0.36
July 0.222907E+09 0.171273E+09 29374.82 7611673.12 34949495.53 141081.45 0.149801E+09 1762.98 0.36
August 0.178707E+09 0.219986E+09 109528.31 5182216.87 48789902.76 83113.08 99824001.52 2531.81 0.36
September 0.239699E+09 72625140.89 147146.33 6762124.56 14020540.38 1171009.36 0.372064E+09 5714.52 0.36
October 0.235811E+09 0.140572E+09 172070.09 4660310.25 30332436.78 9618756.18 0.636939E+09 11277.81 0.36
November 0.162202E+09 2484912.24 8929.97 3390490.82 546271.47 0.503930E+09 0.901271E+09 1767.58 0.35
December 0.132225E+09 3545917.87 54862.57 2478930.03 1290927.00 0.987951E+09 0.666654E+09 7321.01 0.35
                   
Annual Sum or Average 0.220846E+10 0.644129E+09 589784.46 65654466.29 0.143173E+09 0.428026E+10 0.774719E+10 41926.31 0.36
Minimum of Months 0.106105E+09 546522.40 0.00 2368977.73 133815.15 83113.08 99824001.52 0.00 0.35
Maximum of Months 0.305189E+09 0.219986E+09 172070.09 9693515.23 48789902.76 0.107722E+10 0.106374E+10 11277.81 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 86851048.36 3586082.41 0.00 4511992.94 0.00 0.00 0.976277E+09 0.00 0.02
February 0.371775E+09 0.00 0.00 2730446.31 0.00 0.00 0.725399E+09 0.00 0.02
March 0.529361E+09 4674217.23 0.00 1978387.24 0.00 0.00 0.631305E+09 0.00 0.02
April 0.150115E+09 792873.23 0.00 2234057.88 0.00 0.00 0.680434E+09 0.00 0.02
May 0.572937E+09 0.00 0.00 526068.95 0.00 0.00 0.328246E+09 0.00 0.02
June 0.301747E+09 2398456.45 0.00 438989.48 0.00 0.00 0.304506E+09 0.00 0.02
July 4074110.80 0.261831E+09 0.00 406127.27 0.00 0.00 0.182819E+09 0.00 0.02
August 0.00 0.418222E+09 0.00 305783.28 0.00 0.00 34650553.16 0.00 0.02
September 0.00 0.132009E+09 0.00 2059470.80 0.00 0.00 0.203058E+09 0.00 0.02
October 16467291.63 0.187293E+09 0.00 2792165.20 0.00 0.00 0.370441E+09 0.00 0.02
November 19980845.66 112927.93 0.00 4201130.31 0.00 0.00 0.985814E+09 0.00 0.02
December 61498022.43 282001.56 0.00 4808648.01 0.00 0.00 0.996272E+09 0.00 0.02
                   
Annual Sum or Average 0.211481E+10 0.101120E+10 0.00 26993267.66 0.00 0.00 0.641922E+10 0.00 0.02
Minimum of Months 0.00 0.00 0.00 305783.28 0.00 0.00 34650553.16 0.00 0.02
Maximum of Months 0.572937E+09 0.418222E+09 0.00 4808648.01 0.00 0.00 0.996272E+09 0.00 0.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.166375E+10 14062548.94 45144.44 50192739.12 33262206.37 0.609593E+09 0.225821E+11 10603.80 0.40
February 0.145908E+10 7997135.78 169939.30 53808732.73 15719337.14 0.113710E+09 0.200248E+11 16687.34 0.40
March 0.145108E+10 7399287.78 0.00 64260826.71 23453406.62 0.356190E+09 0.232784E+11 13960.69 0.40
April 0.225405E+10 31794246.09 104194.91 94775580.67 38916712.71 20735859.04 0.156617E+11 9100.18 0.40
May 0.322870E+10 8714294.03 0.00 0.120479E+09 19181895.92 15852384.46 0.148817E+11 0.00 0.40
June 0.422980E+10 0.241136E+09 116081.67 0.117972E+09 0.194937E+09 4515307.42 0.662907E+10 449.67 0.41
July 0.304440E+10 0.201994E+10 0.00 92777606.18 0.777762E+09 565786.41 0.202298E+10 0.00 0.41
August 0.242413E+10 0.244686E+10 0.00 62587711.22 0.120044E+10 1912698.38 0.136089E+10 0.00 0.41
September 0.330546E+10 0.819419E+09 653360.65 77432759.17 0.357292E+09 4364405.73 0.501856E+10 5565.01 0.41
October 0.322108E+10 0.167263E+10 95058.83 64869845.64 0.647960E+09 5302412.40 0.874076E+10 16925.15 0.40
November 0.222358E+10 21374116.19 469208.19 59629996.29 19399090.13 84312148.73 0.189393E+11 18879.90 0.40
December 0.179967E+10 45444792.55 829327.85 50028717.17 20115667.20 0.131256E+09 0.222899E+11 62594.44 0.40
                   
Annual Sum or Average 0.303048E+11 0.733677E+10 2482315.84 0.908815E+09 0.334844E+10 0.134831E+10 0.161430E+12 154766.18 0.40
Minimum of Months 0.145108E+10 7399287.78 0.00 50028717.17 15719337.14 565786.41 0.136089E+10 0.00 0.40
Maximum of Months 0.422980E+10 0.244686E+10 829327.85 0.120479E+09 0.120044E+10 0.609593E+09 0.232784E+11 62594.44 0.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 11624799.05 2726237.42 14740.32 7623297.25 751321.76 0.649308E+09 0.116776E+10 1113.79 0.35
February 29530163.06 1762400.13 0.00 5923080.90 0.00 0.515796E+09 0.104513E+10 0.00 0.36
March 41043605.62 2275830.24 0.00 6419167.08 0.00 0.695740E+09 0.111113E+10 0.00 0.36
April 10615840.82 5221945.12 0.00 11030224.93 0.00 0.116132E+09 0.119169E+10 0.00 0.36
May 21278611.37 2056814.79 0.00 11233305.08 0.00 0.105318E+09 0.120752E+10 0.00 0.36
June 8454647.20 32160654.13 0.00 11843351.77 0.00 4252056.37 0.785117E+09 0.00 0.36
July 0.00 0.206278E+09 0.00 10991098.89 0.00 127647.74 0.369386E+09 0.00 0.36
August 0.00 0.268919E+09 0.00 9083513.77 0.00 56787.79 0.274689E+09 0.00 0.36
September 1683118.48 83881311.58 0.00 10371609.91 2927401.45 1686745.71 0.606028E+09 0.00 0.36
October 3792642.89 0.170975E+09 0.00 9740985.70 132098.38 10929558.84 0.862669E+09 7.75 0.36
November 10746493.61 2720800.93 0.00 8335698.76 321436.77 0.294031E+09 0.125786E+10 0.00 0.35
December 14420946.58 4899602.51 0.00 7904463.57 0.00 0.576947E+09 0.119025E+10 0.00 0.35
                   
Annual Sum or Average 0.153191E+09 0.783878E+09 14740.32 0.110500E+09 4132258.36 0.297032E+10 0.110692E+11 1121.54 0.36
Minimum of Months 0.00 1762400.13 0.00 5923080.90 0.00 56787.79 0.274689E+09 0.00 0.35
Maximum of Months 41043605.62 0.268919E+09 14740.32 11843351.77 2927401.45 0.695740E+09 0.125786E+10 1113.79 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.122566E+09 1005310.45 31097.90 2898229.73 2452169.36 0.103897E+10 0.671666E+09 4426.26 0.35
February 0.107567E+09 694857.38 7637.22 2834557.27 1057417.39 0.824912E+09 0.660878E+09 2281.65 0.36
March 0.105586E+09 776544.04 0.00 3791042.63 1499019.56 0.903920E+09 0.840815E+09 0.00 0.36
April 0.158470E+09 4742490.44 23377.32 7853851.97 455366.19 0.150985E+09 0.101200E+10 99.34 0.36
May 0.227546E+09 2043327.03 0.00 9450733.81 13246.78 0.104721E+09 0.100348E+10 0.00 0.36
June 0.304840E+09 25622148.39 0.00 7986043.24 6534737.65 1205021.90 0.495540E+09 0.00 0.36
July 0.221462E+09 0.173222E+09 0.00 6464397.24 33031237.19 244523.47 0.152290E+09 0.00 0.36
August 0.178470E+09 0.223370E+09 0.00 4502108.86 45517588.15 132529.95 0.100691E+09 0.00 0.36
September 0.240163E+09 72011592.91 130416.01 5852292.13 14655088.00 1397478.38 0.372284E+09 1445.21 0.36
October 0.236145E+09 0.142496E+09 90766.66 4993022.12 28497214.62 39397841.45 0.606493E+09 3256.33 0.36
November 0.164438E+09 2186541.07 18777.28 3609626.37 835337.36 0.572698E+09 0.830048E+09 1225.55 0.35
December 0.132575E+09 3441293.38 32403.32 2702771.49 1420749.69 0.970467E+09 0.683564E+09 4582.07 0.35
                   
Annual Sum or Average 0.219983E+10 0.651613E+09 334475.70 62938676.84 0.135969E+09 0.460905E+10 0.742975E+10 17316.41 0.36
Minimum of Months 0.105586E+09 694857.38 0.00 2702771.49 13246.78 132529.95 0.100691E+09 0.00 0.35
Maximum of Months 0.304840E+09 0.223370E+09 130416.01 9450733.81 45517588.15 0.103897E+10 0.101200E+10 4582.07 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.254968E+11 0.00 0.00 0.00 36862995.47 0.00 0.00 0.00 0.48
February 0.226790E+11 0.00 0.00 0.00 7923351.14 0.00 0.00 0.00 0.49
March 0.261074E+11 0.00 0.00 0.00 184465.37 0.00 0.00 0.00 0.49
April 0.202941E+11 0.00 0.00 0.00 42476196.28 0.00 0.00 0.00 0.49
May 0.203957E+11 0.00 0.00 0.00 5394167.19 0.00 0.00 0.00 0.49
June 0.150429E+11 0.00 0.00 0.00 0.321633E+09 0.00 0.00 0.00 0.49
July 0.963400E+10 0.00 0.00 0.00 0.237688E+10 0.00 0.00 0.00 0.49
August 0.820068E+10 0.00 0.00 0.00 0.287048E+10 0.00 0.00 0.00 0.49
September 0.131214E+11 0.00 0.00 0.00 0.893160E+09 0.00 0.00 0.00 0.49
October 0.139739E+11 0.00 0.00 0.00 0.152423E+10 0.00 0.00 0.00 0.49
November 0.228453E+11 0.00 0.00 0.00 25865003.20 0.00 0.00 0.00 0.49
December 0.249552E+11 0.00 0.00 0.00 14811507.00 0.00 0.00 0.00 0.48
                   
Annual Sum or Average 0.222746E+12 0.00 0.00 0.00 0.811990E+10 0.00 0.00 0.00 0.49
Minimum of Months 0.820068E+10 0.00 0.00 0.00 184465.37 0.00 0.00 0.00 0.48
Maximum of Months 0.261074E+11 0.00 0.00 0.00 0.287048E+10 0.00 0.00 0.00 0.49



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 2633367.50 680193.97 417.63 1291211.46 192300.93 0.252364E+09 0.202790E+09 440.80 0.35
February 6904355.64 440600.03 0.00 1240392.42 0.00 0.212590E+09 0.178360E+09 0.00 0.36
March 9666961.85 568957.56 0.00 1396653.27 0.00 0.252675E+09 0.199844E+09 0.00 0.36
April 3070244.52 1305486.28 0.00 2849878.13 0.00 63198610.74 0.263247E+09 0.00 0.36
May 5206499.08 514203.70 0.00 2976593.97 0.00 53661286.91 0.274494E+09 0.00 0.36
June 2230197.98 8040163.53 0.00 3195625.01 0.00 5613193.15 0.191378E+09 0.00 0.36
July 0.00 51565513.80 3486.02 2832195.41 0.00 177733.34 92116357.71 402.06 0.36
August 0.00 67218988.63 9344.44 2138440.54 0.00 157195.83 68661777.98 1514.30 0.36
September 420779.62 21238198.70 3564.55 2689600.58 459706.69 373384.90 0.151459E+09 708.32 0.36
October 1273430.96 42751630.79 22920.10 2034299.25 0.00 31205421.51 0.187270E+09 2293.53 0.36
November 2886792.36 703480.93 0.00 1624789.53 57078.50 0.150073E+09 0.238159E+09 0.00 0.35
December 3406929.30 1224900.63 0.00 1440835.76 0.00 0.239232E+09 0.203300E+09 0.00 0.35
                   
Annual Sum or Average 37699558.81 0.196252E+09 39732.75 25710515.33 709086.12 0.126132E+10 0.225108E+10 5359.00 0.36
Minimum of Months 0.00 440600.03 0.00 1240392.42 0.00 157195.83 68661777.98 0.00 0.35
Maximum of Months 9666961.85 67218988.63 22920.10 3195625.01 459706.69 0.252675E+09 0.274494E+09 2293.53 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 30629933.42 328992.85 6119.24 431864.31 537049.04 0.362399E+09 65564363.13 1089.87 0.35
February 27025615.17 150111.08 690.46 554351.69 289716.78 0.277132E+09 94335884.07 30.08 0.36
March 26794139.57 136630.60 0.00 757973.45 432260.30 0.306829E+09 0.129147E+09 0.00 0.36
April 40153181.41 1109973.90 0.00 1904897.80 195359.43 64568054.99 0.225701E+09 0.00 0.36
May 56122359.61 510831.76 0.00 2422373.48 3311.69 40220501.93 0.237534E+09 0.00 0.36
June 76186090.53 6398392.34 879.84 2382449.71 1639578.87 2243741.11 0.121581E+09 370.46 0.36
July 55726693.86 42818201.44 7271.39 1994472.76 8737373.88 13379.90 37380594.50 513.06 0.36
August 44676767.78 55002677.15 21178.41 1298197.77 12197475.69 38516.40 24935618.70 639.17 0.36
September 59642661.79 18256708.87 42868.99 1543740.12 3398447.58 325812.40 93411993.52 1610.09 0.36
October 59263215.69 35179630.09 43966.50 901359.37 7544113.77 43263598.65 0.118329E+09 4122.14 0.36
November 40844607.09 621228.06 2256.99 584477.73 136567.87 0.234041E+09 0.117228E+09 417.40 0.35
December 33073839.24 871867.20 13120.99 428681.16 338360.78 0.339248E+09 74577032.13 1408.14 0.35
                   
Annual Sum or Average 0.550139E+09 0.161385E+09 138352.81 15204839.37 35449615.68 0.167032E+10 0.133973E+10 10200.42 0.36
Minimum of Months 26794139.57 136630.60 0.00 428681.16 3311.69 13379.90 24935618.70 0.00 0.35
Maximum of Months 76186090.53 55002677.15 43966.50 2422373.48 12197475.69 0.362399E+09 0.237534E+09 4122.14 0.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 7807401.50 5602403.98 8012.07 19626765.10 0.00 0.334232E+09 0.258768E+10 433.06 0.40
February 31509542.51 2830630.21 0.00 13928789.76 0.00 0.280500E+09 0.223804E+10 0.00 0.40
March 47377624.22 3655261.79 0.00 12311469.94 0.00 0.696513E+09 0.222208E+10 0.00 0.40
April 10821344.80 8387082.70 0.00 15352845.04 0.00 98649596.13 0.201046E+10 0.00 0.40
May 23813386.65 3303496.18 0.00 12548825.59 0.00 0.172248E+09 0.195219E+10 0.00 0.40
June 13268323.94 51611915.57 0.00 12832257.18 42029.36 4139013.68 0.127018E+10 0.00 0.40
July 0.00 0.331307E+09 0.00 11764573.44 0.00 1611116.85 0.597762E+09 0.00 0.41
August 0.00 0.431917E+09 0.00 10646038.80 0.00 990116.13 0.444229E+09 0.00 0.41
September 2703294.19 0.136949E+09 0.00 15687502.50 2475951.51 2824247.82 0.974211E+09 0.00 0.41
October 2036583.58 0.274819E+09 0.00 16484942.60 0.00 5131372.21 0.140119E+10 0.00 0.40
November 1350239.98 4886205.92 0.00 19448478.04 0.00 9867905.57 0.249251E+10 0.00 0.40
December 9278343.42 7869361.03 0.00 20672039.75 0.00 0.155168E+09 0.268907E+10 0.00 0.40
                   
Annual Sum or Average 0.149966E+09 0.126314E+10 8012.07 0.181305E+09 2517980.86 0.176187E+10 0.208796E+11 433.06 0.40
Minimum of Months 0.00 2830630.21 0.00 10646038.80 0.00 990116.13 0.444229E+09 0.00 0.40
Maximum of Months 47377624.22 0.431917E+09 8012.07 20672039.75 2475951.51 0.696513E+09 0.268907E+10 433.06 0.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.252094E+10 65106708.96 0.00 50371260.52 5858113.44 0.00 0.504047E+11 0.00 4.70
February 0.170843E+10 11777889.28 0.00 48030630.73 3475126.48 0.00 0.460514E+11 0.00 4.78
March 0.213680E+10 117379.11 0.00 54357520.11 237729.87 0.00 0.526668E+11 0.00 4.78
April 0.673239E+09 80144946.96 0.00 66469260.39 1624758.78 0.00 0.437404E+11 0.00 4.90
May 0.611950E+09 10384156.37 0.00 74552764.54 0.00 0.00 0.446517E+11 0.00 4.96
June 0.236526E+09 0.606379E+09 0.00 81627274.33 16900679.42 0.00 0.346178E+11 0.00 5.11
July 60496294.51 0.455617E+10 0.00 75999799.72 98416043.82 0.00 0.230672E+11 0.00 5.19
August 84494272.50 0.540837E+10 0.00 66418509.15 0.165811E+09 0.00 0.198384E+11 0.00 5.19
September 0.303541E+09 0.172316E+10 0.00 69396995.89 44367588.91 0.00 0.296344E+11 0.00 5.08
October 0.335887E+09 0.292778E+10 0.00 63273785.82 61993332.50 0.00 0.313474E+11 0.00 5.05
November 0.137958E+10 49329702.46 0.00 53732174.57 697413.63 0.00 0.472964E+11 0.00 4.80
December 0.170450E+10 23258734.86 0.00 52151800.95 5254471.95 0.00 0.505856E+11 0.00 4.73
                   
Annual Sum or Average 0.117564E+11 0.154620E+11 0.00 0.756382E+09 0.404636E+09 0.00 0.473902E+12 0.00 4.94
Minimum of Months 60496294.51 117379.11 0.00 48030630.73 0.00 0.00 0.198384E+11 0.00 4.70
Maximum of Months 0.252094E+10 0.540837E+10 0.00 81627274.33 0.165811E+09 0.00 0.526668E+11 0.00 5.19



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.121552E+10 74468201.76 0.00 65457084.79 94430.91 0.00 0.560861E+11 0.00 5.07
February 0.734792E+09 15869434.61 0.00 62192747.68 156726.70 0.00 0.511332E+11 0.00 5.16
March 0.772764E+09 373108.76 0.00 70517272.57 0.00 0.00 0.587748E+11 0.00 5.16
April 0.156633E+09 85167408.03 0.00 83239709.18 762822.00 0.00 0.480307E+11 0.00 5.29
May 79814646.64 10910508.95 0.00 91752879.35 0.00 0.00 0.490581E+11 0.00 5.36
June 15115766.10 0.660160E+09 0.00 95925905.10 16656.96 0.00 0.376977E+11 0.00 5.52
July 2163345.08 0.496377E+10 0.00 85851469.37 4232231.88 0.00 0.248816E+11 0.00 5.58
August 22234271.30 0.589370E+10 0.00 73869641.14 23566946.92 0.00 0.213539E+11 0.00 5.56
September 87869749.25 0.187029E+10 0.00 81664546.29 6700795.84 0.00 0.321782E+11 0.00 5.46
October 0.106487E+09 0.314966E+10 0.00 74132935.45 20552714.04 0.00 0.340170E+11 0.00 5.41
November 0.541113E+09 52963798.71 0.00 68547313.81 0.00 0.00 0.522133E+11 0.00 5.17
December 0.749999E+09 28381194.31 0.00 67635733.56 1577291.21 0.00 0.559392E+11 0.00 5.10
                   
Annual Sum or Average 0.448451E+10 0.168057E+11 0.00 0.920787E+09 57660616.45 0.00 0.521364E+12 0.00 5.32
Minimum of Months 2163345.08 373108.76 0.00 62192747.68 0.00 0.00 0.213539E+11 0.00 5.07
Maximum of Months 0.121552E+10 0.589370E+10 0.00 95925905.10 23566946.92 0.00 0.587748E+11 0.00 5.58



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 6364471.86 0.124064E+09 0.00 0.116876E+09 0.00 0.00 0.690347E+11 0.00 21.19
February 0.00 26787235.66 0.00 0.104646E+09 0.00 0.00 0.624305E+11 0.00 21.34
March 10977867.32 623974.00 0.00 0.114989E+09 0.00 0.00 0.713578E+11 0.00 21.35
April 0.00 0.143627E+09 0.00 0.127071E+09 0.00 0.00 0.554308E+11 0.00 21.64
May 0.00 18172905.53 0.00 0.134818E+09 0.00 0.00 0.557223E+11 0.00 21.67
June 0.00 0.108660E+10 0.00 0.130302E+09 0.00 0.00 0.407674E+11 0.00 21.86
July 0.00 0.803401E+10 0.00 0.104641E+09 0.00 0.00 0.251170E+11 0.00 22.00
August 0.00 0.970330E+10 0.00 85869824.96 0.00 0.00 0.210818E+11 0.00 22.04
September 0.00 0.298665E+10 0.00 0.114446E+09 0.00 0.00 0.353673E+11 0.00 21.90
October 0.00 0.507361E+10 0.00 0.102756E+09 0.00 0.00 0.372182E+11 0.00 21.74
November 0.00 87114178.90 0.00 0.115661E+09 0.00 0.00 0.625329E+11 0.00 21.41
December 0.00 49946110.98 0.00 0.118216E+09 0.00 0.00 0.678416E+11 0.00 21.27
                   
Annual Sum or Average 17342339.18 0.273345E+11 0.00 0.137029E+10 0.00 0.00 0.603902E+12 0.00 21.62
Minimum of Months 0.00 623974.00 0.00 85869824.96 0.00 0.00 0.210818E+11 0.00 21.19
Maximum of Months 10977867.32 0.970330E+10 0.00 0.134818E+09 0.00 0.00 0.713578E+11 0.00 22.04



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.146191E+11 0.00 0.00 0.00 21136104.13 0.00 0.00 0.00 1.05
February 0.130034E+11 0.00 0.00 0.00 4543005.06 0.00 0.00 0.00 1.05
March 0.149692E+11 0.00 0.00 0.00 105766.75 0.00 0.00 0.00 1.06
April 0.116360E+11 0.00 0.00 0.00 24354540.27 0.00 0.00 0.00 1.06
May 0.116943E+11 0.00 0.00 0.00 3092849.02 0.00 0.00 0.00 1.06
June 0.862514E+10 0.00 0.00 0.00 0.184415E+09 0.00 0.00 0.00 1.06
July 0.552384E+10 0.00 0.00 0.00 0.136283E+10 0.00 0.00 0.00 1.06
August 0.470201E+10 54054949.65 0.00 0.00 0.159179E+10 0.00 0.00 0.00 1.06
September 0.752278E+10 0.158738E+09 0.00 4113.83 0.358660E+09 0.00 612069.26 0.00 1.07
October 0.797638E+10 0.311832E+09 0.00 6410.49 0.564274E+09 0.00 35804742.88 0.00 1.06
November 0.130988E+11 0.00 0.00 0.00 14830194.72 0.00 0.00 0.00 1.05
December 0.143086E+11 0.00 0.00 0.00 8492461.08 0.00 0.00 0.00 1.05
                   
Annual Sum or Average 0.127680E+12 0.524625E+09 0.00 10524.33 0.413852E+10 0.00 36416812.14 0.00 1.06
Minimum of Months 0.470201E+10 0.00 0.00 0.00 105766.75 0.00 0.00 0.00 1.05
Maximum of Months 0.149692E+11 0.311832E+09 0.00 6410.49 0.159179E+10 0.00 35804742.88 0.00 1.07



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 09:02:48

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.160300E+12 0.927083E+10 0.113906E+12 0.501582E+12 0.218542E+12
February 0.209264E+12 0.819793E+10 0.106128E+12 0.447998E+12 0.157398E+12
March 0.298450E+12 0.939955E+10 0.120938E+12 0.515716E+12 0.173227E+12
April 0.387198E+12 0.743956E+10 0.932427E+11 0.402269E+12 0.243235E+12
May 0.415552E+12 0.771214E+10 0.945860E+11 0.406881E+12 0.241653E+12
June 0.409843E+12 0.564799E+10 0.686866E+11 0.291955E+12 0.350216E+12
July 0.434040E+12 0.250147E+10 0.307936E+11 0.140655E+12 0.619154E+12
August 0.394212E+12 0.171183E+10 0.210353E+11 0.101932E+12 0.686826E+12
September 0.310076E+12 0.450836E+10 0.550084E+11 0.238264E+12 0.457529E+12
October 0.211016E+12 0.471285E+10 0.526392E+11 0.248253E+12 0.510835E+12
November 0.176448E+12 0.832855E+10 0.102121E+12 0.451936E+12 0.218534E+12
December 0.140426E+12 0.915041E+10 0.110979E+12 0.493295E+12 0.236572E+12
           
Annual Sum or Average 0.354682E+13 0.785815E+11 0.970063E+12 0.424074E+13 0.411372E+13
Minimum of Months 0.140426E+12 0.171183E+10 0.210353E+11 0.101932E+12 0.157398E+12
Maximum of Months 0.434040E+12 0.939955E+10 0.120938E+12 0.515716E+12 0.686826E+12