Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 09:02:49
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 8882.13 | 782.89 | 782.89 |
Net Site Energy | 8882.13 | 782.89 | 782.89 |
Total Source Energy | 19646.22 | 1731.66 | 1731.66 |
Net Source Energy | 19646.22 | 1731.66 | 1731.66 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1106.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 436.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 543.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 174.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 641.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 530.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 89.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 131.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 490.92 | 1177.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 43.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4809.40 | 4072.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1106.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 436.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 543.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 174.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 952.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 22.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 530.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 89.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 131.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.75 | 1177.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Other | 400.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 21.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1106.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 436.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 543.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 174.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 641.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 530.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 89.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 131.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 490.92 | 1177.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 43.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 63.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 136.40 | 201.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 224.28 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 423.91 | 358.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 63.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 136.40 | 201.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 224.28 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 423.91 | 358.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 4809.402 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 4809.402 | 100.00 |
Total On-Site and Utility Electric Sources | 4809.402 | 100.00 |
Total Electricity End Uses | 4809.402 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 15.50 | 0.68 |
Air to Air Heat Recovery for Heating | 2248.85 | 99.32 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2264.35 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 72.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7022.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYSLAUNDRY HPWH TANK | SWHSYS1 HPWH TANK |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| SWHSYS1 HPWH FAN | SWHSYSLAUNDRY HPWH FAN | FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:02 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 5.9798 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 8.7295 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 8.7295 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.1656 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 3.6813 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.1344 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 8.3313 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 8.1375 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 3.9719 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 3.9719 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 3.9719 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 3.9719 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 8.3313 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 8.3313 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 10.5594 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 3.9719 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.2589 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.2589 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.9798 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 8.7295 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 8.7295 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.1656 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 3.6813 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.1344 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 8.3313 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 8.1375 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 3.9719 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 3.9719 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 3.9719 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 3.9719 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 3.9719 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 3.9719 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 3.9719 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 3.9719 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 3.9719 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 3.9719 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 8.3313 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 8.3313 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 10.5594 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 3.9719 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.2589 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.2589 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.3293 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-19:40 | 26-JAN-18:40 | - | - | - | - | - | - | - | - | - | - | 08-MAY-20:10 |
Heating | 0.00 | 159732.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 107808.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 45424.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 87982.85 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31573.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28389.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4713.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 38828.57 | 112881.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1682.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 367439.50 | 376862.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 159732.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 107808.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 45424.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58308.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1269.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 28389.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 4713.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3774.63 | 112881.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 771.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 669.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1199.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1382.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1721.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 551.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5473.02 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2031.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1680.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 283.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 414.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1554.75 | 1276.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 138.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 15231.38 | 4414.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 105.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 121.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 151.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 148.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 25.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 36.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 137.04 | 112.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1342.53 | 389.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 105.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 121.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 151.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 148.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 25.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 36.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 137.04 | 112.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1342.53 | 389.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.05 | 0.736103 | 0.549000 | 1.12 | 1.00 | 0.500000 | 0.000518 | 0.000065 | 1.12 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.428489 | 0.119276 | 0.549000 | 0.235240 | 0.549000 | 0.500000 | 0.003194 | 0.000029 | 0.235240 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.215058 | 0.275198 | 0.549000 | 0.118067 | 0.733862 | 0.500000 | 0.001384 | 0.000011 | 0.118067 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.163533 | 0.765311 | 0.549000 | 0.089779 | 1.00 | 0.500000 | 0.000498 | 0.000015 | 0.089779 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.087956 | 0.820942 | 0.549000 | 0.048288 | 1.00 | 0.500000 | 0.000464 | 0.000009 | 0.048288 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.29 | 0.071767 | 0.549000 | 1.81 | 0.549000 | 0.500000 | 0.021067 | 0.000096 | 1.81 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.74 | 0.082718 | 0.549000 | 0.955148 | 0.549000 | 0.500000 | 0.004606 | 0.000089 | 0.955148 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.89 | 0.203775 | 0.549000 | 2.69 | 0.549000 | 0.500000 | 0.001870 | 0.000230 | 2.69 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.24 | 0.953457 | 0.549000 | 0.683420 | 1.00 | 0.500000 | 0.000400 | 0.000097 | 0.683420 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.07 | 0.121968 | 0.549000 | 1.14 | 0.549000 | 0.500000 | 0.003124 | 0.000094 | 1.14 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.17 | 0.116202 | 0.549000 | 1.19 | 0.549000 | 0.500000 | 0.003279 | 0.000097 | 1.19 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.18 | 0.064832 | 0.549000 | 1.20 | 0.549000 | 0.500000 | 0.010570 | 0.000070 | 1.20 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.711740 | 0.441227 | 0.549000 | 0.390745 | 1.00 | 0.500000 | 0.000864 | 0.000062 | 0.390745 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 7414.02 | 0.000065 | 156.78 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3277.52 | 0.000029 | 74.92 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1304.15 | 0.000011 | 28.88 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1715.55 | 0.000015 | 41.63 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1073.11 | 0.000009 | 27.06 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10994.55 | 0.000096 | 231.31 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 10192.06 | 0.000089 | 224.83 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 26256.14 | 0.000230 | 573.79 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 4626.70 | 0.000040 | 132.19 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 4629.90 | 0.000041 | 132.28 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 26844.46 | 0.000235 | 766.98 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 26918.00 | 0.000235 | 769.08 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 4633.68 | 0.000041 | 132.39 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 4636.88 | 0.000041 | 132.48 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 11113.61 | 0.000097 | 260.84 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1444.90 | 0.000013 | 41.28 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1446.56 | 0.000013 | 41.33 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 6954.55 | 0.000061 | 198.70 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 10731.37 | 0.000094 | 233.67 |
DINING_FLR_6 VAV BOX REHEAT COIL | 11144.12 | 0.000097 | 242.41 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8026.54 | 0.000070 | 169.90 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7122.63 | 0.000062 | 171.04 |
VAV WITH REHEAT HEATING COIL | 158108.88 | 0.001383 | 2699.27 |
FLR_3_DOAS HEATING COIL | 15340.96 | 0.000134 | 261.90 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.11 | 0.000040 | 0.000436 |
ROOM_2_FLR_3 FAN COIL | 0.998185 | 0.000041 | 0.000392 |
ROOM_3_MULT19_FLR_3 FAN COIL | 7.50 | 0.000235 | 0.002888 |
ROOM_4_MULT19_FLR_3 FAN COIL | 4.76 | 0.000235 | 0.001987 |
ROOM_5_FLR_3 FAN COIL | 0.996337 | 0.000041 | 0.000392 |
ROOM_6_FLR_3 FAN COIL | 0.904211 | 0.000041 | 0.000356 |
ROOM_1_FLR_6 FAN COIL | 0.291153 | 0.000013 | 0.000114 |
ROOM_2_FLR_6 FAN COIL | 0.259624 | 0.000013 | 0.000102 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.59 | 0.000061 | 0.000629 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.11 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 0.998185 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 7.50 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 4.76 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 0.996337 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.904211 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.291153 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.259624 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.59 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008569 | 12.80 | 0.008500 | 0.000436 | 1.11 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008577 | 12.80 | 0.008500 | 0.000392 | 0.998185 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008501 | 12.80 | 0.008500 | 0.002888 | 7.50 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008800 | 12.80 | 0.008500 | 0.001987 | 4.76 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008577 | 12.80 | 0.008500 | 0.000392 | 0.996337 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008584 | 12.80 | 0.008500 | 0.000356 | 0.904211 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008565 | 12.80 | 0.008500 | 0.000114 | 0.291153 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008574 | 12.80 | 0.008500 | 0.000102 | 0.259624 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.69 | 6.70 | 0.008607 | 12.80 | 0.008500 | 0.000629 | 1.59 | |
VAV WITH REHEAT COOLING COIL | 26.97 | 6.70 | 0.009214 | 10.95 | 0.008500 | 0.016291 | 21.14 | 456100.66 |
FLR_3_DOAS COOLING COIL | 29.40 | 6.70 | 0.008822 | 11.92 | 0.008500 | 0.001623 | 2.05 | 45447.84 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.67 | 11.67 | 21.25 | 11.67 | 21.14 | 21.14 | 0.300000 | 0.551831 | 21.14 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 21.14 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 21.14 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.016291 | 0.000029 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001383 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001623 | 0.000293 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000134 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Size Rated Evaporator Air Flow Rate [m3/s] | Design Size Rated Condenser Water Flow Rate [m3/s] | |
SWHSYSLAUNDRY HPWH DXCOIL | 4.90 | 0.004370 |
SWHSYS1 HPWH DXCOIL | 3.87 | 0.003451 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
SWHSYSLAUNDRY HPWH FAN | 4.90 | 700.51 |
SWHSYS1 HPWH FAN | 3.87 | 553.22 |
Condenser water flow rate [m3/s] | Evaporator air flow rate [m3/s] | |
SWHSYS1 HPWH | 0.003451 | 3.87 |
SWHSYSLAUNDRY HPWH | 0.004370 | 4.90 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.025210 | 5143.42 | |
HEATSYS1 PUMP | 0.003201 | 954.60 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003201 | 0.384180 |
COOLSYS1 | 0.025210 | 3.03 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 365950.86 | 365950.86 | 0.003201 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.025210 | 3560.96 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.025210 | 705813.51 | 706409.94 | 80.53 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 HPWH TANK | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 5.980 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 11.360 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 8.730 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 19.490 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 8.730 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 19.490 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.166 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 9.546 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 3.681 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.371 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.134 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.664 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 8.331 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 13.711 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 8.138 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.208 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 3.972 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.492 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 3.972 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.492 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 3.972 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.972 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 3.972 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.492 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 8.331 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 76.151 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 8.331 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 76.151 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 10.559 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2942.062 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 3.972 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.972 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 11832.934 | 5.980 | 111.108 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11832.934 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 585.501 | 8.730 | 54.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 585.501 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 678.012 | 8.730 | 54.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 678.012 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 684.177 | 4.166 | 257.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 684.177 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 348.833 | 3.681 | 170.996 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 348.833 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 400.685 | 5.134 | 47.701 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 400.685 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1573.457 | 8.331 | 11.057 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1573.457 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 10645.380 | 8.138 | 25.200 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10645.380 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 154.991 | 3.972 | 103.327 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.991 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 154.973 | 3.972 | 103.315 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.973 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 97.406 | 3.972 | 64.937 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 97.406 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 97.432 | 3.972 | 64.955 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 97.432 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 154.991 | 3.972 | 103.327 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.991 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 154.973 | 3.972 | 103.315 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.973 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1546.669 | 3.972 | 73.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1546.669 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 154.991 | 3.972 | 103.327 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.991 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 154.973 | 3.972 | 103.315 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.973 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 97.432 | 3.972 | 64.955 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 97.432 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 2763.123 | 8.331 | 11.057 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2763.123 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 2763.123 | 8.331 | 11.057 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2763.123 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1090.832 | 10.559 | 49.053 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1090.832 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1636.910 | 3.972 | 73.801 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1636.910 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.8226 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.107 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.174 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.031 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.097 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.048 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7359 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6841 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8028 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7445 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.17638513E-14 | 0.32473881E-16 | -0.15472737E-09 | 0.39084990E-16 |
29 | 8 | 0.22578286E-07 | 0.11136169E-12 | 0.38514655E-03 | -0.25672286E-09 |
30 | 7 | -0.12460867E-01 | 0.57383191E-08 | -0.23401545E-01 | 0.14168460E-03 |
31 | 6 | 0.41130930 | 0.19934685E-05 | 0.47716306 | -0.48180040E-02 |
32 | 5 | -5.2487139 | 0.74343025E-04 | -4.4802041 | 0.63904887E-01 |
33 | 4 | 33.260058 | 0.60748543E-03 | 21.592533 | -0.42553784 |
34 | 3 | -111.77343 | 0.13226915E-02 | -55.924898 | 1.5231004 |
35 | 2 | 197.67353 | 0.74337769E-03 | 78.150831 | -2.9093300 |
36 | 1 | -171.36487 | 0.79295509E-04 | -55.335031 | 2.7490988 |
37 | 0 | 57.057407 | 0.45097929E-06 | 15.545453 | |
38 | 9 | -0.19728226E-15 | 0.38070760E-16 | -0.14134637E-09 | 0.10329039E-17 |
39 | 8 | 0.20696804E-07 | 0.14765672E-12 | 0.36530744E-03 | -0.23532978E-09 |
40 | 7 | -0.11868633E-01 | 0.77667999E-08 | -0.22548754E-01 | 0.13495068E-03 |
41 | 6 | 0.39521686 | 0.27204939E-05 | 0.46345169 | -0.46283129E-02 |
42 | 5 | -5.0916664 | 0.10217830E-03 | -4.3748670 | 0.61957574E-01 |
43 | 4 | 32.565369 | 0.84029717E-03 | 21.180735 | -0.41631434 |
44 | 3 | -110.29532 | 0.18400486E-02 | -55.110745 | 1.5017457 |
45 | 2 | 196.20849 | 0.10394005E-02 | 77.404245 | -2.8860650 |
46 | 1 | -170.82368 | 0.11139293E-03 | -55.118150 | 2.7396138 |
47 | 0 | 57.057407 | 0.63685742E-06 | 15.581450 | |
48 | 9 | 0.13059652E-14 | 0.41030072E-16 | -0.13816519E-09 | -0.47111965E-17 |
49 | 8 | 0.20247126E-07 | 0.15597406E-12 | 0.36047671E-03 | -0.23021680E-09 |
50 | 7 | -0.11724123E-01 | 0.82470298E-08 | -0.22340566E-01 | 0.13330755E-03 |
51 | 6 | 0.39128975 | 0.28947446E-05 | 0.46009809 | -0.45820219E-02 |
52 | 5 | -5.0533361 | 0.10891817E-03 | -4.3490697 | 0.61482301E-01 |
53 | 4 | 32.395785 | 0.89717001E-03 | 21.079809 | -0.41406279 |
54 | 3 | -109.93440 | 0.19673976E-02 | -54.911173 | 1.4965315 |
55 | 2 | 195.85064 | 0.11127485E-02 | 77.221372 | -2.8803827 |
56 | 1 | -170.69145 | 0.11939355E-03 | -55.065279 | 2.7372963 |
57 | 0 | 57.057407 | 0.68346468E-06 | 15.590432 | |
58 | 9 | -0.20590843E-15 | 0.37601014E-16 | -0.14495918E-09 | 0.53749011E-17 |
59 | 8 | 0.21205398E-07 | 0.13808064E-12 | 0.37072834E-03 | -0.24111267E-09 |
60 | 7 | -0.12030653E-01 | 0.72214098E-08 | -0.22782120E-01 | 0.13679291E-03 |
61 | 6 | 0.39961963 | 0.25236359E-05 | 0.46720788 | -0.46802108E-02 |
62 | 5 | -5.1346368 | 0.94596970E-04 | -4.4037454 | 0.62490383E-01 |
63 | 4 | 32.755467 | 0.77656360E-03 | 21.293679 | -0.41883826 |
64 | 3 | -110.69986 | 0.16977958E-02 | -55.334066 | 1.5075900 |
65 | 2 | 196.60952 | 0.95769584E-03 | 77.608945 | -2.8924333 |
66 | 1 | -170.97185 | 0.10250317E-03 | -55.177451 | 2.7422106 |
67 | 0 | 57.057407 | 0.58520576E-06 | 15.571474 | |
68 | 9 | -0.13316196E-15 | 0.35962645E-16 | -0.14184186E-09 | 0.33595795E-17 |
69 | 8 | 0.20766565E-07 | 0.14634888E-12 | 0.36605364E-03 | -0.23612300E-09 |
70 | 7 | -0.11890945E-01 | 0.76921302E-08 | -0.22580893E-01 | 0.13520437E-03 |
71 | 6 | 0.39582317 | 0.26934781E-05 | 0.46396918 | -0.46354598E-02 |
72 | 5 | -5.0975841 | 0.10113583E-03 | -4.3788466 | 0.62030949E-01 |
73 | 4 | 32.591550 | 0.83151862E-03 | 21.196301 | -0.41666193 |
74 | 3 | -110.35104 | 0.18204263E-02 | -55.141525 | 1.5025506 |
75 | 2 | 196.26372 | 0.10281160E-02 | 77.432455 | -2.8869422 |
76 | 1 | -170.84409 | 0.11016374E-03 | -55.126315 | 2.7399715 |
77 | 0 | 57.057407 | 0.62970739E-06 | 15.580070 | |
78 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
79 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
80 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
81 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
82 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
83 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
84 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
85 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
86 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
87 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
88 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
89 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
90 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
91 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
92 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
93 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3672_SHGC_0.36 | 37 | 1 | VerySmooth | 2.086 | 2.086 | 1.000 | 0.361 | ||
2 | RESWINDOW_U_0.3672_SHGC_0.36 | 38 | 1 | VerySmooth | 2.086 | 2.086 | 1.000 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.58639E-002 | 0.27318 | 0.51921 | 0.51921 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11691 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.58639E-002 | 0.27318 | 0.51921 | 0.51921 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11691 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | "DX Coil Total Cooling Rate {W | HPWH Only}" | |
1 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | 1.1400 | 77316.4 | 48.891 | 1.7257 | 76621 | |
2 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | 2.8400 | 62832.8 | 4.644 | 11.1267 | 53264 |
Node Number | Height {m} | Volume {m3} | Maximum Capacity {W} | Off-Cycle UA {W/K} | On-Cycle UA {W/K} | Number Of Inlets | Number Of Outlets | |
1 | 1 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 0 | 1 |
2 | 2 | 0.2683 | 0.4733 | 39973.900 | 1.5573 | 1.5573 | 0 | 0 |
3 | 3 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
4 | 4 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
5 | 5 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 1 |
6 | 6 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 2 | 0 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 9.802E-003 | 1.461E-004 | 7.212E-005 | 0.133 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 3.784E-003 | 4.872E-005 | 1.327E-004 | 4.426E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 8.942E-003 | 5.445E-005 | 1.424E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 5.159E-003 | 5.445E-005 | 1.182E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 1.221E-002 | 1.565E-004 | 1.392E-004 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 2.167E-002 | 1.147E-004 | 6.318E-005 | 0.104 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 6.191E-002 | 4.733E-005 | 9.051E-005 | 4.300E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.587E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.588E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 6.879E-003 | 1.766E-005 | 1.424E-004 | 2.086E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 2.910E-003 | 1.186E-004 | 6.472E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1.243E-002 | 1.204E-004 | 6.523E-005 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1.217E-002 | 2.953E-005 | 2.446E-005 | 3.488E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1355 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 8.0366E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1546 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 9.3938E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.0036E-002 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.6879E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 3.7870E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.2581E-002 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1553 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 9.6223E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1780 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 0.1121 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 9.9657E-002 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.5964E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 4.2527E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.7207E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.5575E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 2.0569E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.7389E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.5576E-002 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.5971E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.0341E-002 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.7278E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3219E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.5575E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 2.0569E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.7389E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.5576E-002 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.5971E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.0341E-002 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.7278E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3219E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 27791.02522 | 27791.02522 | 2.04845 | 2.04845 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 25.86400 | 8.81585E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1561.27466 | 1561.27466 | 6.78892E-002 | 0.85446 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 5812.75979 | 5812.75979 | 0.42849 | 0.42849 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.82094E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2053.58069 | 2053.58069 | 8.92948E-002 | 8.92948E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -4.20000 | 2.69032E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 2917.34337 | 2917.34337 | 0.21506 | 0.21506 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 29.08800 | 8.82100E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 689.86238 | 689.86238 | 2.99972E-002 | 9.17347E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -4.20000 | 2.69032E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2218.86460 | 2218.86460 | 0.16353 | 0.16353 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 28.98400 | 8.82083E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1248.48143 | 1248.48143 | 5.42876E-002 | 5.42876E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -4.20000 | 2.69032E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1193.40141 | 1193.40141 | 8.79557E-002 | 8.79557E-002 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40000 | 8.82150E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 821.88721 | 821.88721 | 3.57380E-002 | 5.77652E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -4.20000 | 2.69032E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44609.27971 | 44609.27971 | 3.28806 | 3.28806 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1604.02626 | 1604.02626 | 6.97469E-002 | 6.97469E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -4.20000 | 2.69032E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 23582.53199 | 23582.53199 | 1.73980 | 1.73980 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.82094E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 5222.25516 | 5222.25516 | 0.22708 | 0.67639 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -4.20000 | 2.69032E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 66341.81027 | 66341.81027 | 4.89186 | 4.89186 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.82122E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 12282.71000 | 12282.71000 | 0.53409 | 1.89399 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -4.20000 | 2.69032E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11182.81519 | 11182.81519 | 1.11070 | 1.11070 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 28.22133 | 8.81961E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 4626.71691 | 4626.71691 | 0.20236 | 0.20236 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | -4.20000 | 2.69032E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10049.96194 | 10049.96194 | 0.99819 | 0.99819 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 4629.92017 | 4629.92017 | 0.20250 | 0.20250 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | -4.20000 | 2.69032E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 75558.71548 | 75558.71548 | 7.50432 | 7.50432 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 26844.50387 | 26844.50387 | 1.17414 | 1.17414 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | -4.20000 | 2.69032E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 47961.26464 | 47961.26464 | 4.76379 | 4.76379 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 29.29600 | 8.82133E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 26918.04855 | 26918.04855 | 1.17735 | 1.17735 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | -4.20000 | 2.69032E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10031.36283 | 10031.36283 | 0.99634 | 0.99634 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 4633.69661 | 4633.69661 | 0.20267 | 0.20267 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | -4.20000 | 2.69032E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9103.80564 | 9103.80564 | 0.90421 | 0.90421 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 4636.89883 | 4636.89883 | 0.20281 | 0.20281 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | -4.20000 | 2.69032E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 16889.03156 | 16889.03156 | 1.24484 | 1.24484 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 29.40000 | 8.82150E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 7557.43598 | 7557.43598 | 0.32862 | 0.47476 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -4.20000 | 2.69032E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2931.40438 | 2931.40438 | 0.29115 | 0.29115 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 28.36000 | 8.81983E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1444.90668 | 1444.90668 | 6.31975E-002 | 6.31975E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | -4.20000 | 2.69032E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2613.95353 | 2613.95353 | 0.25962 | 0.25962 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1446.56126 | 1446.56126 | 6.32699E-002 | 6.32699E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | -4.20000 | 2.69032E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 15989.01939 | 15989.01939 | 1.58810 | 1.58810 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.82122E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 6954.56960 | 6954.56960 | 0.30418 | 0.30418 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | -4.20000 | 2.69032E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 28076.75887 | 28076.75887 | 2.07205 | 2.07205 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 4811.87228 | 4811.87228 | 0.20923 | 1.18780 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | -4.20000 | 2.69032E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 29470.34586 | 29470.34586 | 2.17486 | 2.17486 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 4930.92297 | 4930.92297 | 0.21441 | 1.18780 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | -4.20000 | 2.69032E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 29551.49818 | 29551.49818 | 2.18386 | 2.18386 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 28.46400 | 8.82000E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1802.87477 | 1802.87477 | 7.83858E-002 | 0.36735 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -4.20000 | 2.69032E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 9656.41010 | 9656.41010 | 0.71174 | 0.71174 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 29.40000 | 8.82150E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 5089.25307 | 5089.25307 | 0.22130 | 0.22130 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | -4.20000 | 2.69032E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 357287.67 | 21.14153 | 21.14153 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 180150.72 | 7.22666 | 7.22666 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 40614.20 | 17.18276 | 2.05125 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 51134.75 | 3.59249 | 2.05125 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.04845 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.73610 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.12460 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.17591E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.48610E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.12460 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7414.01588 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.48610E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 156.77606 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.42849 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11928 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23524 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54900 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.19427E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.86732E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23524 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3277.52205 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.86732E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 74.91946 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.21506 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27520 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11807 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73386 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.38446E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.14093E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11807 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1304.15404 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.14093E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 28.88479 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.16353 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.76531 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.97794E-002 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.97837E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.50084E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.97794E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1715.55019 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.50084E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 41.63263 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.79557E-002 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.82094 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.82877E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.64101E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.38805E-006 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.82877E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1073.11167 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.38805E-006 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 27.06008 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.28806 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.17670E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.80514 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54900 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.10666E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.61851E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.80514 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10994.54561 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.61851E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 231.31447 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.73980 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.27182E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.95515 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54900 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.60600E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.91646E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.95515 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10192.06067 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.91646E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 224.83283 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.89186 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20377 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.68563 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54900 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.86971E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.29700E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.68563 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26256.14329 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.29700E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 573.78978 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.11070 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.11070 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.04764E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.35546E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69135 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56868E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.35546E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.11070 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4626.70078 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.04764E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 132.19200 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.99819 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.99819 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.05044E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.92271E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69134 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57656E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.92271E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.99819 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4629.90403 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.05044E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 132.28351 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.50432 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 7.50432 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.34847E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.88832E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69180 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50123E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.88832E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.50432 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 26844.45930 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.34847E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 766.98272 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 4.76379 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 4.76379 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.35490E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.98671E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69081 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.80009E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.98671E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 4.76379 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 26918.00387 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.35490E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 769.08383 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.99634 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.99634 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.05375E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.91560E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69134 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57670E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.91560E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.99634 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4633.68045 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.05375E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 132.39140 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.90421 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.90421 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.05655E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.56111E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69133 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58447E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.56111E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.90421 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 4636.88267 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.05655E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 132.48288 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.24484 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.95346 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.68342 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.99599E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.72267E-005 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.68342 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11113.61242 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.72267E-005 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 260.84125 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.29115 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.29115 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.26406E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.14072E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69136 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56549E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.14072E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.29115 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1444.90183 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.26406E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 41.28234 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.25962 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.25962 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.26551E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.01946E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69135 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57364E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.01946E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.25962 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1446.55640 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.26551E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 41.32961 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.58810 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.58810 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.08414E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 6.29338E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.69111 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.60727E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.29338E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.58810 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6954.55105 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.08414E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 198.69817 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.07205 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12197 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.13756 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54900 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.12378E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.38827E-005 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.13756 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10731.36562 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.38827E-005 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 233.67321 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.17486 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11620 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.19400 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54900 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.27877E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.74936E-005 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.19400 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11144.12314 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.74936E-005 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 242.40559 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.18386 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.48322E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.19894 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54900 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05700E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.02196E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.19894 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8026.53515 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.02196E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 169.90407 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71174 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.44123 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54900 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.39075 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.63500E-004 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.23119E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.39075 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7122.63440 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.23119E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 171.04415 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.66655 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.66655 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.25055 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.66655 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.14153 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 21.14153 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.55183 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 21.14153 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.14153 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.97486 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.95292 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.21438E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 456100.65561 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.62909E-002 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 21.14153 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 158108.87784 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.38321E-003 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2699.27053 |
350 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 21.14153 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.62909E-002 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.92305E-005 |
353 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.38321E-003 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
356 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 29.40000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.91727 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.82150E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 45447.83718 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.62329E-003 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 15340.96456 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.34209E-004 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 261.90442 |
368 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.62329E-003 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.93349E-004 |
371 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.34209E-004 |
372 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 4.90359 |
373 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 4.36989E-003 |
374 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.90359 |
375 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Electric Power Consumption [W] | 700.51236 |
376 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 3.87257 |
377 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 3.45109E-003 |
378 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.87257 |
379 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Electric Power Consumption [W] | 553.22422 |
380 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Condenser water flow rate [m3/s] | 3.45109E-003 |
381 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Evaporator air flow rate [m3/s] | 3.87257 |
382 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.52100E-002 |
383 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 5143.41726 |
384 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.20150E-003 |
385 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.38418 |
386 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.20150E-003 |
387 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 954.60448 |
388 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
389 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 365950.85692 |
390 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 365950.86000 |
391 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.20150E-003 |
392 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.52100E-002 |
393 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.02520 |
394 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.52100E-002 |
395 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3560.96125 |
396 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.52100E-002 |
397 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 705813.51250 |
398 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 706409.94000 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 80.53073 |
400 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
401 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
402 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
403 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
404 | WaterHeater:Stratified | SWHSYS1 HPWH TANK | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
405 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Condenser water flow rate [m3/s] | 4.36989E-003 |
406 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Evaporator air flow rate [m3/s] | 4.90359 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 7451.86 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3292.83 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1310.44 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 1723.00 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1077.59 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11050.92 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 10241.40 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 26386.29 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 4982.92 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 4986.37 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 28911.22 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 28990.42 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 4990.44 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 4993.89 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 11164.23 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1556.13 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1557.91 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 7489.92 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 10784.72 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 11199.58 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8067.46 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7153.91 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 120430.39 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 11685.10 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 18359.46 | 14808.12 | 3551.34 | 0.81 | 2104.85 | 21.35 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 16522.94 | 13319.42 | 3203.52 | 0.81 | 1893.88 | 19.21 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 122532.59 | 99310.47 | 23222.12 | 0.81 | 14076.09 | 142.77 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 81942.93 | 65069.95 | 16872.97 | 0.79 | 9339.92 | 94.73 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 16492.78 | 13294.97 | 3197.81 | 0.81 | 1890.41 | 19.17 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 14988.59 | 12075.82 | 2912.77 | 0.81 | 1717.62 | 17.42 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 4809.89 | 3880.37 | 929.52 | 0.81 | 551.49 | 5.59 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 4295.30 | 3463.23 | 832.07 | 0.81 | 492.37 | 4.99 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 26431.70 | 21261.30 | 5170.39 | 0.80 | 3027.04 | 30.70 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 526774.49 | 366699.36 | 160075.14 | 0.70 | 63010.52 | 639.09 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 49660.04 | 34741.99 | 14918.05 | 0.70 | 5487.20 | 55.65 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.732 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.031 | 0.893 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.107 | 0.950 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.107 | 0.950 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.107 | 0.950 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.107 | 0.950 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.097 | 0.942 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.174 | 0.999 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.6597197146E-002 | 2.0758600755E-002 | Pass | Pass | 4.9030221178E-003 | 1.3476574063E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.8253476733E-003 | 1.4057580601E-003 | Pass | Pass | 0.3639277042 | 0.8333799723 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.8739191804E-002 | 2.8444853150E-002 | Pass | Pass | 1.2012093230E-002 | 3.2313314158E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.3606959506E-003 | 8.9571614424E-003 | Pass | Pass | 2.9536099940E-002 | 6.4299893966E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.2374212535E-004 | 2.3056870487E-004 | Pass | Pass | 0.1203923441 | 0.2785814816 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.6721128728E-002 | 0.2191855106 | Pass | Pass | 1.8828833649E-002 | 4.9821016073E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.0530638387E-002 | 3.3578515808E-002 | Pass | Pass | 2.5960183842E-002 | 8.0014060775E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.8636128758E-002 | 4.7127716281E-002 | Pass | Pass | 1.2812246278E-002 | 3.2483752109E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.3276752558E-002 | 0.2353877355 | Pass | Pass | 9.1901478146E-002 | 0.3504196096 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.3709893898E-002 | 0.2364611060 | Pass | Pass | 9.4222268247E-002 | 0.3426973071 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.2152521603E-002 | 3.4333746076E-002 | Pass | Pass | 7.3966058072E-003 | 6.7376202961E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.4806036666E-002 | 7.4139660324E-002 | Pass | Pass | 0.1840678564 | 0.5166656589 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.2882866100E-002 | 0.2341551450 | Pass | Pass | 9.2992110172E-002 | 0.3483506962 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.3253664115E-002 | 0.2349963891 | Pass | Pass | 9.4388948518E-002 | 0.3325549380 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.8653383726E-004 | 2.9587098446E-004 | Pass | Pass | 0.1215117064 | 0.3912381554 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.5135661203E-002 | 0.2858319682 | Pass | Pass | 6.9369818062E-002 | 0.1903377144 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.5231909262E-002 | 0.2859535801 | Pass | Pass | 7.3074915101E-002 | 0.2090117647 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.5508164012E-002 | 0.1882106235 | Pass | Pass | 7.7606366961E-002 | 0.2464424916 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.5051621431E-002 | 7.1807917830E-002 | Pass | Pass | 1.1469720471E-002 | 3.4973539199E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.4173751600E-002 | 5.7741513362E-002 | Pass | Pass | 1.2669690393E-002 | 3.7849976023E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.8594702195E-002 | 8.7549280394E-002 | Pass | Pass | 2.0849522827E-002 | 3.9115413870E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.2019654917E-004 | 5.3905644634E-004 | Pass | Pass | 3.5543590821E-002 | 5.2421377834E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3532.08 | 35.72 | 1688.18 | 7380.32 | 2322.20 | 14958.51 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.732 | 0.823 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.893 | 1.031 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.942 | 1.097 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.086 | 0.361 | 0.361 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.086 | 0.361 | 0.361 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.086 | 0.361 | 0.361 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.086 | 0.361 | 0.361 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.086 | 0.361 | 0.361 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.086 | 0.361 | 0.361 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.086 | 0.361 | 0.361 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.086 | 0.361 | 0.361 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.086 | 0.361 | 0.361 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.086 | 0.361 | 0.361 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.086 | 0.361 | 0.361 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.086 | 0.361 | 0.361 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.086 | 0.361 | 0.361 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.086 | 0.361 | 0.361 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.086 | 0.361 | 0.361 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.086 | 0.361 | 0.361 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.086 | 0.361 | 0.361 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.086 | 0.361 | 0.361 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.086 | 0.361 | 0.361 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.086 | 0.361 | 0.361 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.086 | 0.361 | 0.361 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.086 | 0.361 | 0.361 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.086 | 0.361 | 0.361 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.086 | 0.361 | 0.361 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.086 | 0.361 | 0.361 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.086 | 0.361 | 0.361 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.086 | 0.361 | 0.361 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.086 | 0.361 | 0.361 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.086 | 0.361 | 0.361 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.086 | 0.361 | 0.361 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.086 | 0.361 | 0.361 | |||||||||||||||||
North Total or Average | 432.95 | 2.086 | 0.361 | 0.361 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.086 | 0.361 | 0.361 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.9798 | 1978.83 | 11832.93 | LightsWired | LTG_SCH_BASEMENT | 45.99 | 168.00 | 45.94 | 0.0000 | Y | 102.03 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 8.7295 | 67.07 | 585.50 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 5.64 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 8.7295 | 77.67 | 678.01 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 6.53 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.1656 | 164.24 | 684.18 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 7.53 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 3.6813 | 94.76 | 348.83 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 1.68 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.1344 | 78.04 | 400.68 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.41 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 8.3313 | 188.86 | 1573.46 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.51 | 0.0000 | Y | 11.67 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 8.1375 | 1308.19 | 10645.38 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 55.42 | 0.0000 | Y | 110.74 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 3.9719 | 156.09 | 619.96 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 5.55 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 3.9719 | 156.07 | 619.89 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 5.55 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 3.9719 | 1863.81 | 7402.84 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 66.32 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 3.9719 | 1864.32 | 7404.86 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 66.33 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 3.9719 | 156.09 | 619.96 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 5.55 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 3.9719 | 156.07 | 619.89 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 5.55 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 3.9719 | 1557.62 | 6186.67 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 51.06 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 3.9719 | 39.02 | 154.99 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.39 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 3.9719 | 39.02 | 154.97 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.39 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 3.9719 | 220.77 | 876.89 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 7.86 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 8.3313 | 331.66 | 2763.12 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.28 | 0.0000 | Y | 25.56 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 8.3313 | 331.66 | 2763.12 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.28 | 0.0000 | Y | 25.56 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 10.5594 | 103.30 | 1090.83 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.00 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 3.9719 | 412.12 | 1636.91 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 13.51 |
Interior Lighting Total | 5.2589 | 11345.29 | 59663.90 | 350.57 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 10645.38 | 745.18 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 10645.38 | 745.18 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1573.46 | 613.65 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1573.46 | 613.65 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2763.12 | 552.62 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2763.12 | 552.62 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2763.12 | 552.62 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2763.12 | 552.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 11096.45 | AstronomicalClock | - | 83.55 | 83.55 | 174.02 | |
Exterior Lighting Total | 11096.45 | 174.02 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 365950.86 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 706409.94 | 2.96 | 706534.11 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12194.36 | 18359.46 | 14808.12 | 3551.34 | 0.81 | - | 2104.85 | 21.35 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10982.74 | 16522.94 | 13319.42 | 3203.52 | 0.81 | - | 1893.88 | 19.21 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 80866.81 | 122532.59 | 99310.47 | 23222.12 | 0.81 | - | 14076.09 | 142.77 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 55623.57 | 81942.93 | 65069.95 | 16872.97 | 0.79 | - | 9339.92 | 94.73 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10962.85 | 16492.78 | 13294.97 | 3197.81 | 0.81 | - | 1890.41 | 19.17 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 9970.35 | 14988.59 | 12075.82 | 2912.77 | 0.81 | - | 1717.62 | 17.42 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3193.77 | 4809.89 | 3880.37 | 929.52 | 0.81 | - | 551.49 | 5.59 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 2854.28 | 4295.30 | 3463.23 | 832.07 | 0.81 | - | 492.37 | 4.99 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 17620.11 | 26431.70 | 21261.30 | 5170.39 | 0.80 | - | 3027.04 | 30.70 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 456100.66 | 526774.49 | 366699.36 | 160075.14 | 0.70 | - | 63010.52 | 639.09 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 45447.84 | 49660.04 | 34741.99 | 14918.05 | 0.70 | - | 5487.20 | 55.65 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 7414.02 | 7451.86 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3277.52 | 3292.83 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1304.15 | 1310.44 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1715.55 | 1723.00 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1073.11 | 1077.59 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10994.55 | 11050.92 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10192.06 | 10241.40 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 26256.14 | 26386.29 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4626.70 | 4982.92 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4629.90 | 4986.37 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 26844.46 | 28911.22 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 26918.00 | 28990.42 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4633.68 | 4990.44 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 4636.88 | 4993.89 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 11113.61 | 11164.23 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1444.90 | 1556.13 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1446.56 | 1557.91 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 6954.55 | 7489.92 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10731.37 | 10784.72 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11144.12 | 11199.58 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8026.54 | 8067.46 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7122.63 | 7153.91 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 158108.88 | 120430.39 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 15340.96 | 11685.10 | - |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 75921.46 | 3.40 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 54370.95 | 3.40 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.11 | 781.53 | 703.64 | 1.00 | 1.17 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.00 | 702.36 | 703.64 | 1.00 | 1.20 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 7.50 | 5280.31 | 703.64 | 1.00 | 0.95 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 4.76 | 3351.97 | 703.64 | 1.00 | 0.97 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.00 | 701.06 | 703.64 | 1.00 | 1.20 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.90 | 636.24 | 703.64 | 1.00 | 1.22 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.29 | 204.87 | 703.64 | 1.00 | 1.73 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.26 | 182.68 | 703.64 | 1.00 | 1.82 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.59 | 1117.45 | 703.64 | 1.00 | 1.10 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 21.14 | 47370.53 | 2240.64 | 1.00 | 1.11 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 |
SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 4.90 | 700.51 | 142.86 | 0.00 | 2.78 | General | ||
SWHSYS1 HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 3.87 | 553.22 | 142.86 | 0.00 | 2.84 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.025210 | 5143.42 | 204022.71 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003201 | 954.60 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.025210 | 3560.96 | 141251.80 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYSLAUNDRY HPWH | WaterHeater:HeatPump:PumpedCondenser | 1.14 | 77316.50 | 0.80 | 48.89 | 1.73 |
SWHSYS1 HPWH | WaterHeater:HeatPump:PumpedCondenser | 2.84 | 62832.84 | 0.80 | 4.64 | 11.13 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 27791.03 | 27791.03 | 14.04 | 2.048 | 2.048 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 24.00 | 24.00 | 0.00937 | 25.86 | 0.00882 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 5812.76 | 5812.76 | 86.67 | 0.428 | 0.428 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00892 | 29.05 | 0.00882 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 2917.34 | 2917.34 | 37.56 | 0.215 | 0.215 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 24.00 | 24.00 | 0.00947 | 29.09 | 0.00882 | 0.092 | 0.00 |
MECH_FLR_1 | 2218.86 | 2218.86 | 13.51 | 0.164 | 0.164 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 24.00 | 24.00 | 0.00877 | 28.98 | 0.00882 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1193.40 | 1193.40 | 12.59 | 0.088 | 0.088 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00889 | 29.40 | 0.00882 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44609.28 | 44609.28 | 571.62 | 3.288 | 3.288 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00854 | 29.40 | 0.00882 | 0.000 | 0.00 |
CAFE_FLR_1 | 23582.53 | 23582.53 | 124.87 | 1.740 | 1.740 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 23.99 | 0.00986 | 29.05 | 0.00882 | 0.676 | 0.00 |
LOBBY_FLR_1 | 66341.81 | 66341.81 | 50.71 | 4.892 | 4.892 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 23.99 | 0.00994 | 29.23 | 0.00882 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 11182.82 | 11182.82 | 286.58 | 1.111 | 1.111 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 21.11 | 21.11 | 0.00857 | 28.22 | 0.00882 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10049.96 | 10049.96 | 257.58 | 0.998 | 0.998 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 21.11 | 21.11 | 0.00858 | 27.94 | 0.00882 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 75558.72 | 75558.72 | 3081.03 | 7.504 | 7.504 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 21.11 | 21.11 | 0.00850 | 29.14 | 0.00882 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 47961.26 | 47961.26 | 1955.16 | 4.764 | 4.764 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 21.11 | 21.11 | 0.00880 | 29.30 | 0.00882 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10031.36 | 10031.36 | 257.07 | 0.996 | 0.996 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 21.11 | 21.11 | 0.00858 | 25.45 | 0.00882 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9103.81 | 9103.81 | 233.33 | 0.904 | 0.904 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.11 | 21.11 | 0.00858 | 23.68 | 0.00881 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 16889.03 | 16889.03 | 43.37 | 1.245 | 1.245 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00964 | 29.40 | 0.00882 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2931.40 | 2931.40 | 75.12 | 0.291 | 0.291 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00857 | 28.36 | 0.00882 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2613.95 | 2613.95 | 66.99 | 0.260 | 0.260 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 21.11 | 21.11 | 0.00857 | 27.94 | 0.00882 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 15989.02 | 15989.02 | 651.80 | 1.588 | 1.588 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 21.11 | 21.11 | 0.00861 | 29.23 | 0.00882 | 0.099 | 0.00 |
BANQUET_FLR_6 | 28076.76 | 28076.76 | 84.66 | 2.072 | 2.072 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 23.98 | 0.01051 | 29.40 | 0.00882 | 1.188 | 0.00 |
DINING_FLR_6 | 29470.35 | 29470.35 | 88.86 | 2.175 | 2.175 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 23.98 | 0.01041 | 29.40 | 0.00882 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 29551.50 | 29551.50 | 286.06 | 2.184 | 2.184 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 24.00 | 23.97 | 0.01014 | 28.46 | 0.00882 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9656.41 | 9656.41 | 23.43 | 0.712 | 0.712 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00902 | 29.40 | 0.00882 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1561.27 | 1561.27 | 0.79 | 0.068 | 0.854 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00796 | -4.20 | 0.00269 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2053.58 | 2053.58 | 30.62 | 0.089 | 0.089 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00785 | -4.20 | 0.00269 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 689.86 | 689.86 | 8.88 | 0.030 | 0.092 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00782 | -4.20 | 0.00269 | 0.092 | 0.00 |
MECH_FLR_1 | 1248.48 | 1248.48 | 7.60 | 0.054 | 0.054 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00777 | -4.20 | 0.00269 | 0.000 | 0.00 |
STORAGE_FLR_1 | 821.89 | 821.89 | 8.67 | 0.036 | 0.058 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00780 | -4.20 | 0.00269 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1604.03 | 1604.03 | 20.55 | 0.070 | 0.070 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00776 | -4.20 | 0.00269 | 0.000 | 0.00 |
CAFE_FLR_1 | 5222.26 | 5222.26 | 27.65 | 0.227 | 0.676 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00787 | -4.20 | 0.00269 | 0.676 | 0.00 |
LOBBY_FLR_1 | 12282.71 | 12282.71 | 9.39 | 0.534 | 1.894 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00784 | -4.20 | 0.00269 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 4626.72 | 4626.72 | 118.57 | 0.202 | 0.202 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | 21.11 | 21.11 | 0.00784 | -4.20 | 0.00269 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 4629.92 | 4629.92 | 118.66 | 0.203 | 0.203 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | 21.11 | 21.11 | 0.00784 | -4.20 | 0.00269 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26844.50 | 26844.50 | 1094.63 | 1.174 | 1.174 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | 21.11 | 21.11 | 0.00786 | -4.20 | 0.00269 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 26918.05 | 26918.05 | 1097.33 | 1.177 | 1.177 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | 21.11 | 21.11 | 0.00786 | -4.20 | 0.00269 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 4633.70 | 4633.70 | 118.75 | 0.203 | 0.203 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | 21.11 | 21.11 | 0.00784 | -4.20 | 0.00269 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 4636.90 | 4636.90 | 118.84 | 0.203 | 0.203 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | 21.11 | 21.11 | 0.00784 | -4.20 | 0.00269 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 7557.44 | 7557.44 | 19.41 | 0.329 | 0.475 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00788 | -4.20 | 0.00269 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1444.91 | 1444.91 | 37.03 | 0.063 | 0.063 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | 21.11 | 21.11 | 0.00787 | -4.20 | 0.00269 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1446.56 | 1446.56 | 37.07 | 0.063 | 0.063 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | 21.11 | 21.11 | 0.00787 | -4.20 | 0.00269 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 6954.57 | 6954.57 | 283.51 | 0.304 | 0.304 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | 21.11 | 21.11 | 0.00788 | -4.20 | 0.00269 | 0.099 | 0.00 |
BANQUET_FLR_6 | 4811.87 | 4811.87 | 14.51 | 0.209 | 1.188 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | 21.00 | 21.00 | 0.00791 | -4.20 | 0.00269 | 1.188 | 0.00 |
DINING_FLR_6 | 4930.92 | 4930.92 | 14.87 | 0.214 | 1.188 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | 21.00 | 21.00 | 0.00791 | -4.20 | 0.00269 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 1802.87 | 1802.87 | 17.45 | 0.078 | 0.367 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00684 | -4.20 | 0.00269 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 5089.25 | 5089.25 | 12.35 | 0.221 | 0.221 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | 21.00 | 21.00 | 0.00792 | -4.20 | 0.00269 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 21.14 | 21.14 | 7.23 | 7.23 | 21.1415 | 11.6666 | 21.1415 | 0.5518 | 0.3000 |
FLR_3_DOAS | 17.18 | 2.05 | 3.59 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 7414.016 | 7414.016 | 1.124598 | 0.00006486 | 156.776 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 7414.02 | 7414.02 | 1.124598 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00796088 | 50.7335 | 1561.27 | 0.00 | 7455.48 | 7455.48 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3277.522 | 3277.522 | 0.235240 | 0.00002867 | 74.919 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 3277.52 | 3277.52 | 0.235240 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00784643 | 50.0139 | 2053.58 | 0.00 | 3295.14 | 3295.14 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1304.154 | 1304.154 | 0.118067 | 0.00001141 | 28.885 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 1304.15 | 1304.15 | 0.118067 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00782429 | 49.8741 | 689.86 | 0.00 | 1311.25 | 1311.25 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1715.550 | 1715.550 | 0.089779 | 0.00001501 | 41.633 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 1715.55 | 1715.55 | 0.089779 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00777283 | 49.5502 | 1248.48 | 0.00 | 1724.48 | 1724.48 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1073.112 | 1073.112 | 0.048288 | 0.00000939 | 27.060 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 1073.11 | 1073.11 | 0.048288 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00779985 | 49.7203 | 821.89 | 0.00 | 1078.63 | 1078.63 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10994.546 | 10994.546 | 1.805142 | 0.00009619 | 231.314 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 10994.55 | 10994.55 | 1.805142 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00775922 | 49.4650 | 1604.03 | 0.00 | 11056.14 | 11056.14 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 10192.061 | 10192.061 | 0.955148 | 0.00008916 | 224.833 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 10192.06 | 10192.06 | 0.955148 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00786600 | 50.1370 | 5222.26 | 0.00 | 10247.59 | 10247.59 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 26256.143 | 26256.143 | 2.685632 | 0.00022970 | 573.790 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 26256.14 | 26256.14 | 2.685632 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00783808 | 49.9610 | 12282.71 | 0.00 | 26401.53 | 26401.53 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12194.364 | -999.000 | 1.110702 | 0.00043555 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | unknown | 8/21 16:40:00 | 12194.36 | 11995.40 | 1.110702 | 21.69 | 15.47 | 0.00856868 | 12.80 | 11.97 | 0.00850000 | 28.22 | 0.00881961 | 17.95 | 0.0000 | 21.11 | 0.00856868 | 54.1848 | 11182.82 | 0.00 | 12363.70 | 11949.17 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 4626.701 | 4626.701 | 0.202364 | 0.00004048 | 132.192 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | 4626.70 | 4626.70 | 0.202364 | 21.11 | 14.61 | 0.00784278 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00784278 | 49.6511 | 4626.72 | 0.00 | 4987.73 | 4987.73 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 10982.744 | -999.000 | 0.998185 | 0.00039227 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | 8/21 17:00:00 | 10982.74 | 10783.37 | 0.998185 | 21.69 | 15.48 | 0.00857656 | 12.80 | 11.97 | 0.00850000 | 27.94 | 0.00881916 | 17.86 | 0.0000 | 21.11 | 0.00857656 | 54.2339 | 10049.96 | 0.00 | 11135.08 | 10742.37 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 4629.904 | 4629.904 | 0.202504 | 0.00004050 | 132.284 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | 4629.90 | 4629.90 | 0.202504 | 21.11 | 14.61 | 0.00784289 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00784289 | 49.6518 | 4629.92 | 0.00 | 4991.19 | 4991.19 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 80866.808 | -999.000 | 7.504316 | 0.00288832 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | 8/21 13:30:00 | 80866.81 | 80842.83 | 7.504316 | 21.69 | 15.41 | 0.00850123 | 12.80 | 11.97 | 0.00850000 | 29.14 | 0.00882108 | 18.26 | 0.0000 | 21.11 | 0.00850123 | 53.7628 | 75558.72 | 0.00 | 82000.47 | 80495.18 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 26844.459 | 26844.459 | 1.174137 | 0.00023485 | 766.983 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | 26844.46 | 26844.46 | 1.174137 | 21.11 | 14.62 | 0.00785598 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00785598 | 49.7333 | 26844.50 | 0.00 | 28939.25 | 28939.25 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 55623.566 | -999.000 | 4.763786 | 0.00198671 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | unknown | 8/21 15:10:00 | 55623.57 | 51864.65 | 4.763786 | 21.69 | 15.68 | 0.00880009 | 12.80 | 11.97 | 0.00850000 | 29.30 | 0.00882133 | 18.31 | 0.0000 | 21.11 | 0.00880009 | 55.6287 | 47961.26 | 0.00 | 56372.13 | 51739.99 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 26918.004 | 26918.004 | 1.177354 | 0.00023549 | 769.084 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | 26918.00 | 26918.00 | 1.177354 | 21.11 | 14.62 | 0.00785632 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00785632 | 49.7355 | 26918.05 | 0.00 | 29018.54 | 29018.54 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 10962.853 | -999.000 | 0.996337 | 0.00039156 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | unknown | 8/21 10:00:00 | 10962.85 | 10763.47 | 0.996337 | 21.69 | 15.48 | 0.00857670 | 12.80 | 11.97 | 0.00850000 | 25.45 | 0.00881519 | 17.01 | 0.0000 | 21.11 | 0.00857670 | 54.2348 | 10031.36 | 0.00 | 11114.91 | 10722.55 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 4633.680 | 4633.680 | 0.202669 | 0.00004054 | 132.391 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | 4633.68 | 4633.68 | 0.202669 | 21.11 | 14.61 | 0.00784301 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00784301 | 49.6525 | 4633.70 | 0.00 | 4995.26 | 4995.26 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 9970.346 | -999.000 | 0.904211 | 0.00035611 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | unknown | 8/21 09:00:00 | 9970.35 | 9771.02 | 0.904211 | 21.69 | 15.49 | 0.00858447 | 12.80 | 11.97 | 0.00850000 | 23.68 | 0.00881240 | 16.40 | 0.0000 | 21.11 | 0.00858447 | 54.2833 | 9103.81 | 0.00 | 10108.49 | 9734.37 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 4636.883 | 4636.883 | 0.202809 | 0.00004057 | 132.483 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | 4636.88 | 4636.88 | 0.202809 | 21.11 | 14.61 | 0.00784312 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00784312 | 49.6533 | 4636.90 | 0.00 | 4998.71 | 4998.71 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 11113.612 | 11113.612 | 0.683420 | 0.00009723 | 260.841 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 11113.61 | 11113.61 | 0.683420 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00788203 | 50.2375 | 7557.44 | 0.00 | 11172.85 | 11172.85 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3193.767 | -999.000 | 0.291153 | 0.00011407 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 3193.77 | 3144.04 | 0.291153 | 21.69 | 15.47 | 0.00856549 | 12.80 | 11.97 | 0.00850000 | 28.36 | 0.00881983 | 18.00 | 0.0000 | 21.11 | 0.00856549 | 54.1649 | 2931.40 | 0.00 | 3238.14 | 3131.86 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1444.902 | 1444.902 | 0.063198 | 0.00001264 | 41.282 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | 1444.90 | 1444.90 | 0.063198 | 21.11 | 14.64 | 0.00787336 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00787336 | 49.8423 | 1444.91 | 0.00 | 1557.65 | 1557.65 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2854.281 | -999.000 | 0.259624 | 0.00010195 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | 8/21 17:00:00 | 2854.28 | 2804.41 | 0.259624 | 21.69 | 15.48 | 0.00857364 | 12.80 | 11.97 | 0.00850000 | 27.94 | 0.00881916 | 17.86 | 0.0000 | 21.11 | 0.00857364 | 54.2157 | 2613.95 | 0.00 | 2893.89 | 2793.69 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1446.556 | 1446.556 | 0.063270 | 0.00001266 | 41.330 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | 1446.56 | 1446.56 | 0.063270 | 21.11 | 14.64 | 0.00787351 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00787351 | 49.8433 | 1446.56 | 0.00 | 1559.43 | 1559.43 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 17620.106 | -999.000 | 1.588102 | 0.00062934 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | 8/21 13:40:00 | 17620.11 | 17175.17 | 1.588102 | 21.69 | 15.51 | 0.00860727 | 12.80 | 11.97 | 0.00850000 | 29.23 | 0.00882122 | 18.29 | 0.0000 | 21.11 | 0.00860727 | 54.4261 | 15989.02 | 0.00 | 17863.47 | 17113.29 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 6954.551 | 6954.551 | 0.304181 | 0.00006084 | 198.698 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | 6954.55 | 6954.55 | 0.304181 | 21.11 | 14.64 | 0.00787872 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00787872 | 49.8757 | 6954.57 | 0.00 | 7497.24 | 7497.24 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10731.366 | 10731.366 | 1.137555 | 0.00009388 | 233.673 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | 10731.37 | 10731.37 | 1.137555 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00790602 | 50.3885 | 4811.87 | 0.00 | 10790.85 | 10790.85 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11144.123 | 11144.123 | 1.193998 | 0.00009749 | 242.406 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | 11144.12 | 11144.12 | 1.193998 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00790825 | 50.4026 | 4930.92 | 0.00 | 11205.91 | 11205.91 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 8026.535 | 8026.535 | 1.198938 | 0.00007022 | 169.904 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 8026.54 | 8026.54 | 1.198938 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00684307 | 43.6935 | 1802.87 | 0.00 | 8071.41 | 8071.41 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7122.634 | 7122.634 | 0.390745 | 0.00006231 | 171.044 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | 7122.63 | 7122.63 | 0.390745 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00792190 | 50.4884 | 5089.25 | 0.00 | 7159.87 | 7159.87 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 456100.656 | -999.000 | 21.141530 | 0.01629086 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 456100.66 | 409238.71 | 21.141530 | 26.97 | 17.86 | 0.00921438 | 10.95 | 10.95 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 55.1590 | 23.99 | 0.00968974 | 51.3437 | 286510.96 | 0.00 | 460950.44 | 394605.21 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 158108.878 | 158108.878 | 6.342459 | 0.00138321 | 2699.271 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 158108.88 | 158108.88 | 6.342459 | -4.20 | -4.20 | 0.00269032 | 16.70 | 13.06 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 183.8634 | 21.01 | 0.00785307 | 50.0251 | 49417.97 | 0.00 | 145662.32 | 145662.32 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 45447.837 | -999.000 | 2.051317 | 0.00162329 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 45447.84 | 43504.21 | 2.051317 | 29.40 | 18.34 | 0.00882150 | 11.92 | 11.61 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 99.9965 | 21.11 | 0.00861837 | 54.4944 | 173001.40 | 0.00 | 45923.42 | 42707.30 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 15340.965 | 15340.965 | 0.615395 | 0.00013421 | 261.904 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | 15340.96 | 15340.96 | 0.615395 | -4.20 | -4.20 | 0.00269032 | 16.70 | 13.06 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 333.3216 | 21.11 | 0.00785627 | 49.7351 | 82135.82 | 0.00 | 14133.30 | 14133.30 |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 52787.223 | 38851.396 | 4.903586 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 75921.46 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 41716.686 | 30703.481 | 3.872570 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 54370.95 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 7414.016 | 7414.016 | 1.124598 | 0.00006486 | 156.776 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 1.9860 | 2.025959 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 7414.02 | 7414.02 | 1.0000 | 1.33488764 | 1.124598 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.06485443 | 60.00 | 32.22 | 27.78 | 0.000 | 7414.02 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00796088 | 21.00 | 0.00796088 | 50.7335 | 1561.27 | 0.00 | 7455.48 | 7455.48 | 1.33488764 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.08 | 15.25 | 0.00800000 | 42519.8 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3277.522 | 3277.522 | 0.235240 | 0.00002867 | 74.919 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 0.8779 | 0.895618 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 3277.52 | 3277.52 | 1.0000 | 0.27922808 | 0.235240 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.02867027 | 60.00 | 32.22 | 27.78 | 0.000 | 3277.52 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00784643 | 21.00 | 0.00784643 | 50.0139 | 2053.58 | 0.00 | 3295.14 | 3295.14 | 0.27922808 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.17 | 17.42 | 0.00800000 | 48735.6 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1304.154 | 1304.154 | 0.118067 | 0.00001141 | 28.885 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 0.3493 | 0.356374 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 1304.15 | 1304.15 | 1.0000 | 0.14014453 | 0.118067 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.01140814 | 60.00 | 32.22 | 27.78 | 0.000 | 1304.15 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00782429 | 21.00 | 0.00782429 | 49.8741 | 689.86 | 0.00 | 1311.25 | 1311.25 | 0.14014453 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.78 | 16.59 | 0.00800000 | 46291.1 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1715.550 | 1715.550 | 0.089779 | 0.00001501 | 41.633 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 0.4595 | 0.468793 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 1715.55 | 1715.55 | 1.0000 | 0.10656737 | 0.089779 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.01500685 | 60.00 | 32.22 | 27.78 | 0.000 | 1715.55 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00777283 | 21.00 | 0.00777283 | 49.5502 | 1248.48 | 0.00 | 1724.48 | 1724.48 | 0.10656737 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.47 | 18.85 | 0.00800000 | 53116.8 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1073.112 | 1073.112 | 0.048288 | 0.00000939 | 27.060 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 0.2875 | 0.293239 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 1073.11 | 1073.11 | 1.0000 | 0.05731705 | 0.048288 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.00938709 | 60.00 | 32.22 | 27.78 | 0.000 | 1073.11 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00779985 | 21.00 | 0.00779985 | 49.7203 | 821.89 | 0.00 | 1078.63 | 1078.63 | 0.05731705 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.05 | 19.67 | 0.00800000 | 55753.4 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10994.546 | 10994.546 | 1.805142 | 0.00009619 | 231.314 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 2.9451 | 3.004378 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 10994.55 | 10994.55 | 1.0000 | 2.14268736 | 1.805142 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09617527 | 60.00 | 32.22 | 27.78 | 0.000 | 10994.55 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00775922 | 21.00 | 0.00775922 | 49.4650 | 1604.03 | 0.00 | 11056.14 | 11056.14 | 2.14268736 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.66 | 15.10 | 0.00800000 | 42094.7 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10192.061 | 10192.061 | 0.955148 | 0.00008916 | 224.833 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 2.7301 | 2.785090 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 10192.06 | 10192.06 | 1.0000 | 1.13375186 | 0.955148 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.08915550 | 60.00 | 32.22 | 27.78 | 0.000 | 10192.06 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00786600 | 21.00 | 0.00786600 | 50.1370 | 5222.26 | 0.00 | 10247.59 | 10247.59 | 1.13375186 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.46 | 16.48 | 0.00800000 | 45973.4 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26256.143 | 26256.143 | 2.685632 | 0.00022970 | 573.790 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 7.0332 | 7.174773 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 26256.14 | 26256.14 | 1.0000 | 3.18782036 | 2.685632 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.22967676 | 60.00 | 32.22 | 27.78 | 0.000 | 26256.14 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00783808 | 21.00 | 0.00783808 | 49.9610 | 12282.71 | 0.00 | 26401.53 | 26401.53 | 3.18782036 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.72 | 16.21 | 0.00800000 | 45216.7 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12194.364 | -999.000 | 1.110702 | 0.00043555 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7688 | 1004.8586 | 1.1870 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.110702 | 1.31839263 | 4197.9300 | 999.8980 | 25.20745160 | 13.37 | 6.70 | 6.67 | 705813.51 | 1.7277 | 1.727671 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | unknown | unknown | unknown | 8/21 16:40:00 | Sensible | 12194.36 | 11995.40 | 1.0000 | 1.31839263 | 1.110702 | 21.69 | 15.47 | 0.00856868 | 43571.6 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.43550186 | 6.70 | 13.37 | 6.67 | 0.000 | 12194.36 | 28.22 | 0.00881961 | 17.95 | 0.00000000 | 0.0000 | 21.11 | 0.00856868 | 21.11 | 0.00856868 | 54.1848 | 11182.82 | 0.00 | 12363.70 | 11949.17 | 1.31839263 | 21.69 | 15.62 | 0.00856868 | 43571.6 | 12.81 | 12.05 | 0.00844415 | 34193.8 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4626.701 | 4626.701 | 0.202364 | 0.00004048 | 132.192 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.110702 | 1.31839263 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 1.2394 | 1.264296 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | Sensible | 4626.70 | 4626.70 | 1.0000 | 0.24020405 | 0.202364 | 21.11 | 14.61 | 0.00784278 | 41135.1 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04047227 | 60.00 | 32.22 | 27.78 | 0.000 | 4626.70 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00784278 | 21.11 | 0.00784278 | 49.6511 | 4626.72 | 0.00 | 4987.73 | 4987.73 | 0.24020405 | 16.60 | 13.00 | 0.00784278 | 36536.7 | 36.97 | 20.15 | 0.00784278 | 57301.2 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10982.744 | -999.000 | 0.998185 | 0.00039227 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7834 | 1004.8586 | 1.1870 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.998185 | 1.18483647 | 4197.9300 | 999.8980 | 25.20745160 | 13.37 | 6.70 | 6.67 | 705813.51 | 1.5560 | 1.556011 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | unknown | unknown | 8/21 17:00:00 | Sensible | 10982.74 | 10783.37 | 1.0000 | 1.18483647 | 0.998185 | 21.69 | 15.48 | 0.00857656 | 43591.6 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.39223084 | 6.70 | 13.37 | 6.67 | 0.000 | 10982.74 | 27.94 | 0.00881916 | 17.86 | 0.00000000 | 0.0000 | 21.11 | 0.00857656 | 21.11 | 0.00857656 | 54.2339 | 10049.96 | 0.00 | 11135.08 | 10742.37 | 1.18483647 | 21.69 | 15.62 | 0.00857656 | 43591.6 | 12.81 | 12.05 | 0.00844528 | 34193.6 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4629.904 | 4629.904 | 0.202504 | 0.00004050 | 132.284 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.998185 | 1.18483647 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 1.2402 | 1.265171 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | Sensible | 4629.90 | 4629.90 | 1.0000 | 0.24037035 | 0.202504 | 21.11 | 14.61 | 0.00784289 | 41135.4 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04050029 | 60.00 | 32.22 | 27.78 | 0.000 | 4629.90 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00784289 | 21.11 | 0.00784289 | 49.6518 | 4629.92 | 0.00 | 4991.19 | 4991.19 | 0.24037035 | 16.60 | 13.00 | 0.00784289 | 36537.0 | 36.97 | 20.15 | 0.00784289 | 57301.5 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 80866.808 | -999.000 | 7.504316 | 0.00288832 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6434 | 1004.8586 | 1.1870 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.504316 | 8.90755377 | 4197.9300 | 999.8980 | 25.20745160 | 13.37 | 6.70 | 6.67 | 705813.51 | 11.4572 | 11.457035 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | unknown | unknown | 8/21 13:30:00 | Sensible | 80866.81 | 80842.83 | 1.0000 | 8.90755377 | 7.504316 | 21.69 | 15.41 | 0.00850123 | 43400.6 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 2.88802643 | 6.70 | 13.37 | 6.67 | 0.000 | 80866.81 | 29.14 | 0.00882108 | 18.26 | 0.00000000 | 0.0000 | 21.11 | 0.00850123 | 21.11 | 0.00850123 | 53.7628 | 75558.72 | 0.00 | 82000.47 | 80495.18 | 8.90755377 | 21.69 | 15.56 | 0.00850123 | 43400.6 | 12.84 | 12.05 | 0.00843430 | 34194.9 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26844.459 | 26844.459 | 1.174137 | 0.00023485 | 766.983 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.504316 | 8.90755377 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 7.1908 | 7.335537 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | Sensible | 26844.46 | 26844.46 | 1.0000 | 1.39368984 | 1.174137 | 21.11 | 14.62 | 0.00785598 | 41168.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.23482308 | 60.00 | 32.22 | 27.78 | 0.000 | 26844.46 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00785598 | 21.11 | 0.00785598 | 49.7333 | 26844.50 | 0.00 | 28939.25 | 28939.25 | 1.39368984 | 16.60 | 13.01 | 0.00785598 | 36570.1 | 36.97 | 20.16 | 0.00785598 | 57334.6 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 55623.566 | -999.000 | 4.763786 | 0.00198671 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1989 | 1004.8586 | 1.1870 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 4.763786 | 5.65457055 | 4197.9300 | 999.8980 | 25.20745160 | 13.37 | 6.70 | 6.67 | 705813.51 | 7.8808 | 7.880627 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | unknown | unknown | unknown | 8/21 15:10:00 | Sensible | 55623.57 | 51864.65 | 1.0000 | 5.65457055 | 4.763786 | 21.69 | 15.68 | 0.00880009 | 44159.1 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 1.98650513 | 6.70 | 13.37 | 6.67 | 0.000 | 55623.57 | 29.30 | 0.00882133 | 18.31 | 0.00000000 | 0.0000 | 21.11 | 0.00880009 | 21.11 | 0.00880009 | 55.6287 | 47961.26 | 0.00 | 56372.13 | 51739.99 | 5.65457055 | 21.69 | 15.82 | 0.00880009 | 44159.1 | 12.73 | 12.05 | 0.00847561 | 34189.8 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26918.004 | 26918.004 | 1.177354 | 0.00023549 | 769.084 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 4.763786 | 5.65457055 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 7.2105 | 7.355634 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | Sensible | 26918.00 | 26918.00 | 1.0000 | 1.39750807 | 1.177354 | 21.11 | 14.62 | 0.00785632 | 41169.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.23546642 | 60.00 | 32.22 | 27.78 | 0.000 | 26918.00 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00785632 | 21.11 | 0.00785632 | 49.7355 | 26918.05 | 0.00 | 29018.54 | 29018.54 | 1.39750807 | 16.60 | 13.01 | 0.00785632 | 36571.0 | 36.97 | 20.16 | 0.00785632 | 57335.5 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10962.853 | -999.000 | 0.996337 | 0.00039156 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7837 | 1004.8586 | 1.1870 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.996337 | 1.18264314 | 4197.9300 | 999.8980 | 25.20745160 | 13.37 | 6.70 | 6.67 | 705813.51 | 1.5532 | 1.553193 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | unknown | unknown | unknown | 8/21 10:00:00 | Sensible | 10962.85 | 10763.47 | 1.0000 | 1.18264314 | 0.996337 | 21.69 | 15.48 | 0.00857670 | 43592.0 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.39152045 | 6.70 | 13.37 | 6.67 | 0.000 | 10962.85 | 25.45 | 0.00881519 | 17.01 | 0.00000000 | 0.0000 | 21.11 | 0.00857670 | 21.11 | 0.00857670 | 54.2348 | 10031.36 | 0.00 | 11114.91 | 10722.55 | 1.18264314 | 21.69 | 15.62 | 0.00857670 | 43592.0 | 12.81 | 12.05 | 0.00844530 | 34193.6 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4633.680 | 4633.680 | 0.202669 | 0.00004054 | 132.391 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.996337 | 1.18264314 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 1.2412 | 1.266203 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | Sensible | 4633.68 | 4633.68 | 1.0000 | 0.24056641 | 0.202669 | 21.11 | 14.61 | 0.00784301 | 41135.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04053332 | 60.00 | 32.22 | 27.78 | 0.000 | 4633.68 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00784301 | 21.11 | 0.00784301 | 49.6525 | 4633.70 | 0.00 | 4995.26 | 4995.26 | 0.24056641 | 16.60 | 13.00 | 0.00784301 | 36537.3 | 36.97 | 20.15 | 0.00784301 | 57301.8 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9970.346 | -999.000 | 0.904211 | 0.00035611 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7981 | 1004.8586 | 1.1870 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.904211 | 1.07329038 | 4197.9300 | 999.8980 | 25.20745160 | 13.37 | 6.70 | 6.67 | 705813.51 | 1.4126 | 1.412577 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | unknown | unknown | unknown | 8/21 09:00:00 | Sensible | 9970.35 | 9771.02 | 1.0000 | 1.07329038 | 0.904211 | 21.69 | 15.49 | 0.00858447 | 43611.7 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.35607467 | 6.70 | 13.37 | 6.67 | 0.000 | 9970.35 | 23.68 | 0.00881240 | 16.40 | 0.00000000 | 0.0000 | 21.11 | 0.00858447 | 21.11 | 0.00858447 | 54.2833 | 9103.81 | 0.00 | 10108.49 | 9734.37 | 1.07329038 | 21.69 | 15.63 | 0.00858447 | 43611.7 | 12.81 | 12.05 | 0.00844641 | 34193.5 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4636.883 | 4636.883 | 0.202809 | 0.00004057 | 132.483 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.904211 | 1.07329038 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 1.2421 | 1.267078 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | Sensible | 4636.88 | 4636.88 | 1.0000 | 0.24073266 | 0.202809 | 21.11 | 14.61 | 0.00784312 | 41135.9 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04056133 | 60.00 | 32.22 | 27.78 | 0.000 | 4636.88 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00784312 | 21.11 | 0.00784312 | 49.6533 | 4636.90 | 0.00 | 4998.71 | 4998.71 | 0.24073266 | 16.60 | 13.00 | 0.00784312 | 36537.5 | 36.97 | 20.15 | 0.00784312 | 57302.1 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11113.612 | 11113.612 | 0.683420 | 0.00009723 | 260.841 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 2.9770 | 3.036914 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 11113.61 | 11113.61 | 1.0000 | 0.81121269 | 0.683420 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09721681 | 60.00 | 32.22 | 27.78 | 0.000 | 11113.61 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00788203 | 21.00 | 0.00788203 | 50.2375 | 7557.44 | 0.00 | 11172.85 | 11172.85 | 0.81121269 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.11 | 18.07 | 0.00800000 | 50707.8 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3193.767 | -999.000 | 0.291153 | 0.00011407 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7628 | 1004.8586 | 1.1870 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.291153 | 0.34559645 | 4197.9300 | 999.8980 | 25.20745160 | 13.37 | 6.70 | 6.67 | 705813.51 | 0.4525 | 0.452486 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | Sensible | 3193.77 | 3144.04 | 1.0000 | 0.34559645 | 0.291153 | 21.69 | 15.47 | 0.00856549 | 43563.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.11406018 | 6.70 | 13.37 | 6.67 | 0.000 | 3193.77 | 28.36 | 0.00881983 | 18.00 | 0.00000000 | 0.0000 | 21.11 | 0.00856549 | 21.11 | 0.00856549 | 54.1649 | 2931.40 | 0.00 | 3238.14 | 3131.86 | 0.34559645 | 21.69 | 15.62 | 0.00856549 | 43563.5 | 12.81 | 12.05 | 0.00844369 | 34193.8 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1444.902 | 1444.902 | 0.063198 | 0.00001264 | 41.282 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.291153 | 0.34559645 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 0.3870 | 0.394835 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | Sensible | 1444.90 | 1444.90 | 1.0000 | 0.07501486 | 0.063198 | 21.11 | 14.64 | 0.00787336 | 41212.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.01263934 | 60.00 | 32.22 | 27.78 | 0.000 | 1444.90 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00787336 | 21.11 | 0.00787336 | 49.8423 | 1444.91 | 0.00 | 1557.65 | 1557.65 | 0.07501486 | 16.60 | 13.03 | 0.00787336 | 36614.1 | 36.97 | 20.17 | 0.00787336 | 57378.7 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2854.281 | -999.000 | 0.259624 | 0.00010195 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7780 | 1004.8586 | 1.1870 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.259624 | 0.30817096 | 4197.9300 | 999.8980 | 25.20745160 | 13.37 | 6.70 | 6.67 | 705813.51 | 0.4044 | 0.404388 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | unknown | unknown | 8/21 17:00:00 | Sensible | 2854.28 | 2804.41 | 1.0000 | 0.30817096 | 0.259624 | 21.69 | 15.48 | 0.00857364 | 43584.2 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.10193600 | 6.70 | 13.37 | 6.67 | 0.000 | 2854.28 | 27.94 | 0.00881916 | 17.86 | 0.00000000 | 0.0000 | 21.11 | 0.00857364 | 21.11 | 0.00857364 | 54.2157 | 2613.95 | 0.00 | 2893.89 | 2793.69 | 0.30817096 | 21.69 | 15.62 | 0.00857364 | 43584.2 | 12.81 | 12.05 | 0.00844486 | 34193.7 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1446.556 | 1446.556 | 0.063270 | 0.00001266 | 41.330 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.259624 | 0.30817096 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 0.3875 | 0.395287 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | Sensible | 1446.56 | 1446.56 | 1.0000 | 0.07510076 | 0.063270 | 21.11 | 14.64 | 0.00787351 | 41213.1 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.01265382 | 60.00 | 32.22 | 27.78 | 0.000 | 1446.56 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00787351 | 21.11 | 0.00787351 | 49.8433 | 1446.56 | 0.00 | 1559.43 | 1559.43 | 0.07510076 | 16.60 | 13.03 | 0.00787351 | 36614.5 | 36.97 | 20.17 | 0.00787351 | 57379.1 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17620.106 | -999.000 | 1.588102 | 0.00062934 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8405 | 1004.8586 | 1.1870 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.588102 | 1.88506274 | 4197.9300 | 999.8980 | 25.20745160 | 13.37 | 6.70 | 6.67 | 705813.51 | 2.4964 | 2.496378 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | unknown | unknown | 8/21 13:40:00 | Sensible | 17620.11 | 17175.17 | 1.0000 | 1.88506274 | 1.588102 | 21.69 | 15.51 | 0.00860727 | 43669.4 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.62927339 | 6.70 | 13.37 | 6.67 | 0.000 | 17620.11 | 29.23 | 0.00882122 | 18.29 | 0.00000000 | 0.0000 | 21.11 | 0.00860727 | 21.11 | 0.00860727 | 54.4261 | 15989.02 | 0.00 | 17863.47 | 17113.29 | 1.88506274 | 21.69 | 15.65 | 0.00860727 | 43669.4 | 12.80 | 12.05 | 0.00844964 | 34193.1 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6954.551 | 6954.551 | 0.304181 | 0.00006084 | 198.698 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.588102 | 1.88506274 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 1.8629 | 1.900406 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | Sensible | 6954.55 | 6954.55 | 1.0000 | 0.36105966 | 0.304181 | 21.11 | 14.64 | 0.00787872 | 41226.4 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.06083524 | 60.00 | 32.22 | 27.78 | 0.000 | 6954.55 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00787872 | 21.11 | 0.00787872 | 49.8757 | 6954.57 | 0.00 | 7497.24 | 7497.24 | 0.36105966 | 16.60 | 13.03 | 0.00787872 | 36627.7 | 36.97 | 20.18 | 0.00787872 | 57392.2 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10731.366 | 10731.366 | 1.137555 | 0.00009388 | 233.673 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 2.8746 | 2.932461 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | Sensible | 10731.37 | 10731.37 | 1.0000 | 1.35026749 | 1.137555 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09387309 | 60.00 | 32.22 | 27.78 | 0.000 | 10731.37 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00790602 | 21.00 | 0.00790602 | 50.3885 | 4811.87 | 0.00 | 10790.85 | 10790.85 | 1.35026749 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.44 | 16.11 | 0.00800000 | 44926.4 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11144.123 | 11144.123 | 1.193998 | 0.00009749 | 242.406 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 2.9852 | 3.045251 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | Sensible | 11144.12 | 11144.12 | 1.0000 | 1.41726462 | 1.193998 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09748371 | 60.00 | 32.22 | 27.78 | 0.000 | 11144.12 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00790825 | 21.00 | 0.00790825 | 50.4026 | 4930.92 | 0.00 | 11205.91 | 11205.91 | 1.41726462 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.35 | 16.08 | 0.00800000 | 44841.4 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8026.535 | 8026.535 | 1.198938 | 0.00007022 | 169.904 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 2.1501 | 2.193337 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 8026.54 | 8026.54 | 1.0000 | 1.42312823 | 1.198938 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.07021247 | 60.00 | 32.22 | 27.78 | 0.000 | 8026.54 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.43 | 0.00684307 | 21.00 | 0.00684307 | 43.6935 | 1802.87 | 0.00 | 8071.41 | 8071.41 | 1.42312823 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.16 | 15.28 | 0.00800000 | 42606.3 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7122.634 | 7122.634 | 0.390745 | 0.00006231 | 171.044 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 1.9079 | 1.946336 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | Sensible | 7122.63 | 7122.63 | 1.0000 | 0.46381086 | 0.390745 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.06230556 | 60.00 | 32.22 | 27.78 | 0.000 | 7122.63 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00792190 | 21.00 | 0.00792190 | 50.4884 | 5089.25 | 0.00 | 7159.87 | 7159.87 | 0.46381086 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.74 | 18.61 | 0.00800000 | 52371.8 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 456100.656 | -999.000 | 21.141530 | 0.01629086 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9691 | 1004.8586 | 1.1870 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.141530 | 25.09480159 | 4197.9300 | 999.8980 | 25.20745160 | 13.37 | 6.70 | 6.67 | 705813.51 | 64.6206 | 64.620562 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | Sensible | 456100.66 | 409238.71 | 1.0000 | 25.09480159 | 21.141530 | 26.97 | 17.86 | 0.00921438 | 50612.1 | 10.95 | 10.95 | 0.00850000 | 32437.0 | 16.28919679 | 6.70 | 13.37 | 6.67 | 47370.529 | 408730.13 | 29.40 | 0.00882150 | 18.34 | 11.66146000 | 55.1590 | 23.99 | 0.00969814 | 23.99 | 0.00968974 | 51.3437 | 286510.96 | 0.00 | 460950.44 | 394605.21 | 25.09480159 | 26.97 | 18.01 | 0.00921438 | 50612.1 | 11.59 | 11.25 | 0.00816630 | 32243.7 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 158108.878 | 158108.878 | 6.342459 | 0.00138321 | 2699.271 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.141530 | 25.09480159 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 42.3526 | 43.204948 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 158108.88 | 158108.88 | 1.0000 | 7.52844048 | 6.342459 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 1.38306434 | 60.00 | 32.22 | 27.78 | 0.000 | 158108.88 | -4.20 | 0.00269032 | -4.20 | 11.66146000 | 183.8634 | 20.97 | 0.00783390 | 21.01 | 0.00785307 | 50.0251 | 49417.97 | 0.00 | 145662.32 | 145662.32 | 7.52844048 | 2.80 | 0.07 | 0.00269032 | 9555.9 | 21.96 | 9.93 | 0.00269032 | 28904.2 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 45447.837 | -999.000 | 2.051317 | 0.00162329 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2387 | 1004.8586 | 1.1870 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.43480905 | 4197.9300 | 999.8980 | 25.20745160 | 13.37 | 6.70 | 6.67 | 705813.51 | 6.4391 | 6.439072 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | Sensible | 45447.84 | 43504.21 | 1.0000 | 2.43489466 | 2.051317 | 29.40 | 18.34 | 0.00882150 | 52086.5 | 11.92 | 11.61 | 0.00850000 | 33421.2 | 1.62312585 | 6.70 | 13.37 | 6.67 | 2195.006 | 43252.83 | 29.40 | 0.00882150 | 18.34 | 2.05124512 | 99.9965 | 21.11 | 0.00861358 | 21.11 | 0.00861837 | 54.4944 | 173001.40 | 0.00 | 45923.42 | 42707.30 | 2.43489466 | 29.40 | 18.50 | 0.00882150 | 52086.5 | 12.23 | 11.66 | 0.00829812 | 33225.9 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 15340.965 | 15340.965 | 0.615395 | 0.00013421 | 261.904 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.43480905 | 4197.9300 | 999.8980 | 3.20117115 | 54.44 | 82.22 | 27.78 | 373315.76 | 4.1094 | 4.192083 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:10:00 | Sensible | 15340.96 | 15340.96 | 1.0000 | 0.73046840 | 0.615395 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 0.13419576 | 60.00 | 32.22 | 27.78 | 0.000 | 15340.96 | -4.20 | 0.00269032 | -4.20 | 2.05124512 | 333.3216 | 21.11 | 0.00785569 | 21.11 | 0.00785627 | 49.7351 | 82135.82 | 0.00 | 14133.30 | 14133.30 | 0.73046840 | 2.80 | 0.07 | 0.00269032 | 9555.9 | 21.96 | 9.93 | 0.00269032 | 28904.2 | |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 52787.223 | 38851.396 | 4.903586 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 1.1870 | SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 4.903586 | 5.82051198 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 75921.46 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 75921.46 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 41716.686 | 30703.481 | 3.872570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 1.1870 | SWHSYS1 HPWH FAN | Fan:SystemModel | 3.872570 | 4.59670436 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 54370.95 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54370.95 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 21.14 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2.50 | 8698.83 | 0.00 |
RETAIL_1_FLR_1 | 960.50 | 8158.83 | 605.00 |
RETAIL_2_FLR_1 | 241.83 | 7972.33 | 0.00 |
MECH_FLR_1 | 49.33 | 8679.67 | 49.33 |
STORAGE_FLR_1 | 127.83 | 8752.17 | 127.83 |
LAUNDRY_FLR_1 | 6734.00 | 3377.83 | 2474.00 |
CAFE_FLR_1 | 878.83 | 7298.33 | 40.33 |
LOBBY_FLR_1 | 866.50 | 6758.33 | 29.00 |
ROOM_1_FLR_3 | 963.83 | 8398.00 | 919.67 |
ROOM_2_FLR_3 | 1698.83 | 8167.67 | 1404.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 126.83 | 8750.67 | 126.83 |
ROOM_5_FLR_3 | 931.33 | 8379.33 | 921.17 |
ROOM_6_FLR_3 | 1466.33 | 8386.83 | 1384.50 |
CORRIDOR_FLR_3 | 57.50 | 8753.17 | 57.50 |
ROOM_1_FLR_6 | 1814.33 | 8288.17 | 1704.17 |
ROOM_2_FLR_6 | 2638.50 | 8075.33 | 2296.00 |
ROOM_3_MULT9_FLR_6 | 572.83 | 8169.83 | 472.33 |
BANQUET_FLR_6 | 4042.17 | 2198.17 | 42.50 |
DINING_FLR_6 | 5508.83 | 1106.83 | 24.50 |
KITCHEN_FLR_6 | 8223.67 | 6277.67 | 6170.00 |
CORRIDOR_FLR_6 | 172.00 | 8454.17 | 95.33 |
Facility | 8743.67 | 8760.00 | 7022.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 7.17 | 0.00 | 7.17 |
ROOM_2_FLR_3 | 0.00 | 13.00 | 0.00 | 13.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 49.83 | 0.00 | 49.83 |
ROOM_5_FLR_3 | 0.00 | 3.00 | 0.00 | 3.00 |
ROOM_6_FLR_3 | 0.00 | 14.00 | 0.00 | 14.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 10.17 | 0.00 | 10.17 |
ROOM_2_FLR_6 | 0.00 | 21.17 | 0.00 | 21.17 |
ROOM_3_MULT9_FLR_6 | 0.00 | 2.33 | 0.00 | 2.33 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 72.00 | 0.00 | 72.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.76 | 106.50 | 4826.41 | 0.854 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 3.238 | 0.034 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.408 | 0.012 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.504 | 0.013 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.469 | 0.013 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 24.186 | 0.037 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.52 | 142.30 | 748.35 | 4.679 | 0.027 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.96 | 422.44 | 5183.56 | 1.910 | 0.011 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.045 | 0.000 | 0.042 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.356 | 0.045 | 0.000 | 0.041 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.404 | 0.020 | 0.000 | 0.075 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.045 | 0.000 | 0.042 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.356 | 0.045 | 0.000 | 0.048 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.526 | 0.005 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.355 | 0.045 | 0.000 | 0.050 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.356 | 0.045 | 0.000 | 0.042 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.404 | 0.036 | 0.000 | 0.079 |
BANQUET_FLR_6 | 144.91 | 249.90 | 1010.89 | 4.761 | 0.013 | 0.000 | 0.000 |
DINING_FLR_6 | 144.91 | 249.90 | 1010.89 | 5.172 | 0.013 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 21.319 | 0.037 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 1.136 | 0.009 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.76 | 106.50 | 4826.41 | 0.831 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 3.136 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.361 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.489 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.456 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 20.739 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.52 | 142.30 | 748.35 | 4.523 | 0.000 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.96 | 422.44 | 5183.56 | 1.839 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.000 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.510 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.91 | 249.90 | 1010.89 | 4.009 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 144.91 | 249.90 | 1010.89 | 4.214 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 13.590 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 1.102 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.76 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.52 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 244.96 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.15 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.91 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.91 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.86 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 872.83 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 35465592.70 | 0.00 | 35465592.70 | 0.00 | 35465592.70 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 7444531.07 | 0.00 | 7444531.07 | 79114.98 | 7523646.05 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3733089.87 | 0.00 | 3733089.87 | 30538.48 | 3763628.35 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 2831341.70 | 0.00 | 2831341.70 | 72174.83 | 2903516.53 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1522800.84 | 0.00 | 1522800.84 | 41640.90 | 1564441.74 | 1821682.01 | 8760.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 64386501.01 | 0.00 | 64386501.01 | 98551.04 | 64485052.05 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 30185504.92 | 0.00 | 30185504.92 | 174888.14 | 30360393.06 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 85109536.19 | 0.00 | 85109536.19 | 499695.36 | 85609231.55 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 43582.80 | 1503739.51 | 45920.75 | 1549660.26 | 1946875.62 | 2190.00 | 6018.50 | 551.50 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 41417.61 | 1501403.24 | 45917.24 | 1547320.48 | 1946647.51 | 2190.00 | 6119.68 | 450.32 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 66.70 | 1099978.67 | 12812.40 | 1112791.08 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.83 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 48021.90 | 19851851.19 | 12815.91 | 19864667.10 | 26405105.73 | 2190.00 | 6027.81 | 542.19 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 43542.62 | 1503699.34 | 45920.75 | 1549620.08 | 1946875.62 | 2190.00 | 6018.50 | 551.50 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 48720.67 | 1508706.30 | 45917.24 | 1554623.54 | 1946647.51 | 2190.00 | 6019.08 | 550.92 | 0.00 |
CORRIDOR_FLR_3 | 21552318.48 | 0.00 | 21552318.48 | 55527.42 | 21607845.90 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 50868.78 | 415907.96 | 45930.36 | 461838.32 | 486718.90 | 2073.97 | 6019.50 | 666.54 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 43287.86 | 408284.26 | 45926.85 | 454211.12 | 486661.88 | 2105.03 | 6160.80 | 494.17 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 50799.72 | 2395990.03 | 23499.58 | 2419489.61 | 3126920.42 | 2190.00 | 6017.83 | 552.17 | 0.00 |
BANQUET_FLR_6 | 41213173.06 | 0.00 | 41213173.06 | 112150.39 | 41325323.44 | 37458366.31 | 3967.55 | 195.70 | 4596.75 | 0.00 |
DINING_FLR_6 | 44759535.95 | 0.00 | 44759535.95 | 112150.39 | 44871686.33 | 37458366.31 | 0.00 | 2958.14 | 5801.86 | 0.00 |
KITCHEN_FLR_6 | 57506475.56 | 0.00 | 57506475.56 | 100400.60 | 57606876.16 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12325306.52 | 0.00 | 12325306.52 | 98266.50 | 12423573.02 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 4915142.41 | 0.21E+10 | 4627490.16 | 0.21E+10 | 0.43E+10 | 8760.00 | 7855.30 | 8760.00 | 365.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.1246 | 0.0000 | 1.1246 | 0.0000 | 1.1246 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.2361 | 0.0000 | 0.2361 | 0.0025 | 0.2386 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1184 | 0.0000 | 0.1184 | 0.0010 | 0.1193 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.0898 | 0.0000 | 0.0898 | 0.0023 | 0.0921 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0483 | 0.0000 | 0.0483 | 0.0013 | 0.0496 | 0.0578 | 8760.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 2.0417 | 0.0000 | 2.0417 | 0.0031 | 2.0448 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.9572 | 0.0000 | 0.9572 | 0.0055 | 0.9627 | 0.6764 | 0.00 | 0.00 | 8760.00 |
LOBBY_FLR_1 | 2.6988 | 0.0000 | 2.6988 | 0.0158 | 2.7147 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0014 | 0.0477 | 0.0015 | 0.0491 | 0.0617 | 2190.00 | 6018.50 | 551.50 |
ROOM_2_FLR_3 | 0.0463 | 0.0013 | 0.0476 | 0.0015 | 0.0491 | 0.0617 | 2190.00 | 6119.68 | 450.32 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0015 | 0.6295 | 0.0004 | 0.6299 | 0.8373 | 2190.00 | 6027.81 | 542.19 |
ROOM_5_FLR_3 | 0.0463 | 0.0014 | 0.0477 | 0.0015 | 0.0491 | 0.0617 | 2190.00 | 6018.50 | 551.50 |
ROOM_6_FLR_3 | 0.0463 | 0.0015 | 0.0478 | 0.0015 | 0.0493 | 0.0617 | 2190.00 | 6019.08 | 550.92 |
CORRIDOR_FLR_3 | 0.6834 | 0.0000 | 0.6834 | 0.0018 | 0.6852 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0116 | 0.0016 | 0.0132 | 0.0015 | 0.0146 | 0.0154 | 2073.97 | 6019.50 | 666.54 |
ROOM_2_FLR_6 | 0.0116 | 0.0014 | 0.0129 | 0.0015 | 0.0144 | 0.0154 | 2105.03 | 6160.80 | 494.17 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0016 | 0.0760 | 0.0007 | 0.0767 | 0.0992 | 2190.00 | 6017.83 | 552.17 |
BANQUET_FLR_6 | 1.3069 | 0.0000 | 1.3069 | 0.0036 | 1.3104 | 1.1878 | 3967.55 | 195.70 | 4596.75 |
DINING_FLR_6 | 1.4193 | 0.0000 | 1.4193 | 0.0036 | 1.4229 | 1.1878 | 0.00 | 2958.14 | 5801.86 |
KITCHEN_FLR_6 | 1.8235 | 0.0000 | 1.8235 | 0.0032 | 1.8267 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.3908 | 0.0000 | 0.3908 | 0.0031 | 0.3939 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 64.1483 | 0.1557 | 64.3040 | 0.1159 | 64.4199 | 73.9670 | 8760.00 | 7855.30 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.57E+09 | 0.00 | 0.57E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 42013749.02 | 370308.65 | 42384057.67 | 64690340.46 | 8754.17 | 4.95 | 0.88 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 18.2300 | 0.0000 | 18.2300 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 1.3322 | 0.0117 | 1.3440 | 2.0513 | 8754.17 | 4.95 | 0.88 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 5004.79 | 0.00 | 0.00 | 0.00 | 3755.21 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 18.4012 | 0.0000 | 0.0000 | 0.0000 | 18.0067 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.6828 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1363 |
Defaulted Fields | 1208 |
Fields with Defaults | 4115 |
Autosized Fields | 353 |
Autosizable Fields | 407 |
Autocalculated Fields | 289 |
Autocalculatable Fields | 549 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 4809.40 | 68674.42 | 27-NOV-03:40 | 367439.50 | 10-AUG-19:40 |
Electricity:Building | 2278.66 | 30036.56 | 01-JUL-05:00 | 133648.28 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 245.14 | 2955.01 | 02-JAN-02:10 | 17976.64 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2271.57 | 29895.42 | 01-JUL-05:00 | 133406.95 | 02-JAN-20:10 |
InteriorLights:Electricity | 543.43 | 4613.24 | 01-JUL-05:00 | 45424.10 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 102.03 | 927.11 | 02-JAN-02:10 | 8344.11 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 543.43 | 4613.24 | 01-JUL-05:00 | 45424.10 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 543.43 | 4613.24 | 01-JUL-05:00 | 45424.10 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 102.03 | 927.11 | 02-JAN-02:10 | 8344.11 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 543.43 | 4613.24 | 01-JUL-05:00 | 45424.10 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 15.82 | 195.57 | 02-JAN-02:10 | 1146.69 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 5.64 | 51.23 | 02-JAN-02:10 | 461.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 5.64 | 51.23 | 02-JAN-02:10 | 461.08 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 18.32 | 226.47 | 02-JAN-02:10 | 1327.87 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 6.53 | 59.33 | 02-JAN-02:10 | 533.93 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 6.53 | 59.33 | 02-JAN-02:10 | 533.93 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.00 | 245.14 | 02-JAN-02:10 | 1455.21 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 7.53 | 68.42 | 02-JAN-02:10 | 615.76 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 7.53 | 68.42 | 02-JAN-02:10 | 615.76 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.28 | 66.24 | 02-JAN-02:10 | 379.51 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.68 | 15.26 | 02-JAN-02:10 | 137.35 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.68 | 15.26 | 02-JAN-02:10 | 137.35 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.35 | 1002.76 | 02-JAN-02:10 | 4933.42 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.41 | 40.07 | 02-JAN-02:10 | 360.62 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.41 | 40.07 | 02-JAN-02:10 | 360.62 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 26.01 | 263.03 | 01-JUL-05:00 | 2381.38 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 11.67 | 59.82 | 01-JUL-05:00 | 1416.11 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 11.67 | 59.82 | 01-JUL-05:00 | 1416.11 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 259.74 | 3074.91 | 01-JUL-05:00 | 19610.05 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.74 | 963.50 | 01-JUL-05:00 | 9580.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.74 | 963.50 | 01-JUL-05:00 | 9580.84 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 17.85 | 257.74 | 01-JAN-02:10 | 1187.62 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 5.55 | 47.02 | 01-JAN-02:10 | 427.46 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 5.55 | 47.02 | 01-JAN-02:10 | 427.46 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 17.84 | 257.71 | 01-JAN-02:10 | 1187.48 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 5.55 | 47.01 | 01-JAN-02:10 | 427.41 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 5.55 | 47.01 | 01-JAN-02:10 | 427.41 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 295.07 | 4482.89 | 01-JAN-02:10 | 20504.95 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 66.32 | 561.43 | 01-JAN-02:10 | 5104.26 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 66.32 | 561.43 | 01-JAN-02:10 | 5104.26 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 295.15 | 4484.12 | 01-JAN-02:10 | 20510.57 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 66.33 | 561.58 | 01-JAN-02:10 | 5105.65 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 66.33 | 561.58 | 01-JAN-02:10 | 5105.65 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 17.85 | 257.74 | 01-JAN-02:10 | 1187.62 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 5.55 | 47.02 | 01-JAN-02:10 | 427.46 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 5.55 | 47.02 | 01-JAN-02:10 | 427.46 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 17.84 | 257.71 | 01-JAN-02:10 | 1187.48 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 5.55 | 47.01 | 01-JAN-02:10 | 427.41 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 5.55 | 47.01 | 01-JAN-02:10 | 427.41 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 51.07 | 464.00 | 02-JAN-02:10 | 4176.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 51.07 | 464.00 | 02-JAN-02:10 | 4176.01 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 51.07 | 464.00 | 02-JAN-02:10 | 4176.01 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.46 | 64.43 | 01-JAN-02:10 | 296.90 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.39 | 11.75 | 01-JAN-02:10 | 106.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.39 | 11.75 | 01-JAN-02:10 | 106.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.46 | 64.43 | 01-JAN-02:10 | 296.87 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.39 | 11.75 | 01-JAN-02:10 | 106.85 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.39 | 11.75 | 01-JAN-02:10 | 106.85 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 34.95 | 531.01 | 01-JAN-02:10 | 2428.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 7.86 | 66.50 | 01-JAN-02:10 | 604.62 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 7.86 | 66.50 | 01-JAN-02:10 | 604.62 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 201.42 | 2415.09 | 10-JUN-05:00 | 9234.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 25.56 | 165.79 | 10-JUN-05:00 | 2486.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 25.56 | 165.79 | 10-JUN-05:00 | 2486.81 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 201.42 | 2415.09 | 10-JUN-05:00 | 9234.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 25.56 | 165.79 | 10-JUN-05:00 | 2486.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 25.56 | 165.79 | 10-JUN-05:00 | 2486.81 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 443.12 | 5932.71 | 02-JAN-02:10 | 18599.73 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.01 | 109.08 | 02-JAN-02:10 | 981.75 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.01 | 109.08 | 02-JAN-02:10 | 981.75 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 13.51 | 122.77 | 02-JAN-02:10 | 1104.91 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 13.51 | 122.77 | 02-JAN-02:10 | 1104.91 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 13.51 | 122.77 | 02-JAN-02:10 | 1104.91 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 43.88 | 733.73 | 11-FEB-23:30 | 2787.04 | 01-OCT-10:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1053.74 | 2148.33 | 17-OCT-02:50 | 175071.46 | 10-AUG-18:20 |
LowTempRefrigeration:Refrigeration:Electricity | 15.73 | 0.00 | 01-JAN-11:10 | 1306.52 | 25-AUG-04:20 |
MedTempRefrigeration:Refrigeration:Electricity | 21.06 | 614.48 | 12-FEB-04:10 | 716.01 | 30-AUG-13:40 |
WaterSystems:Electricity | 490.92 | 1086.62 | 09-AUG-00:30 | 41773.87 | 07-SEP-18:00 |
Electricity:HVAC | 683.95 | 13214.02 | 14-DEC-15:00 | 42273.78 | 10-AUG-20:30 |
Fans:Electricity | 530.52 | 12480.25 | 09-DEC-08:10 | 32360.00 | 24-AUG-22:00 |
General:Fans:Electricity | 530.52 | 12480.25 | 09-DEC-08:10 | 32360.00 | 24-AUG-22:00 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ExteriorEquipment:Electricity | 641.45 | 9451.13 | 02-JAN-02:20 | 39153.57 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 22.42 | 386.26 | 17-JUN-05:00 | 1279.09 | 08-MAY-20:10 |
ElectricityPurchased:Facility | 4809.40 | 68674.42 | 27-NOV-03:40 | 367439.50 | 10-AUG-19:40 |
ElectricityPurchased:Plant | 4809.40 | 68674.42 | 27-NOV-03:40 | 367439.50 | 10-AUG-19:40 |
Cogeneration:ElectricityPurchased | 4809.40 | 68674.42 | 27-NOV-03:40 | 367439.50 | 10-AUG-19:40 |
General:Cogeneration:ElectricityPurchased | 4809.40 | 68674.42 | 27-NOV-03:40 | 367439.50 | 10-AUG-19:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 4809.40 | 68674.42 | 27-NOV-03:40 | 367439.50 | 10-AUG-19:40 |
ElectricityNet:Plant | 4809.40 | 68674.42 | 27-NOV-03:40 | 367439.50 | 10-AUG-19:40 |
Cogeneration:ElectricityNet | 4809.40 | 68674.42 | 27-NOV-03:40 | 367439.50 | 10-AUG-19:40 |
General:Cogeneration:ElectricityNet | 4809.40 | 68674.42 | 27-NOV-03:40 | 367439.50 | 10-AUG-19:40 |
ExteriorLights:Electricity | 174.02 | 0.00 | 01-JAN-08:10 | 11096.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 174.02 | 0.00 | 01-JAN-08:10 | 11096.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 131.00 | 0.00 | 01-JAN-11:10 | 9938.94 | 22-JUN-16:30 |
General:HeatRecovery:Electricity | 131.00 | 0.00 | 01-JAN-11:10 | 9938.94 | 22-JUN-16:30 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.62 | 09-AUG-00:30 | 4738.77 | 26-APR-18:10 |
Water Heater Parasitic:WaterSystems:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 436.38 | 0.00 | 01-JAN-00:10 | 132918.33 | 10-AUG-18:10 |
General:Cooling:Electricity | 436.38 | 0.00 | 01-JAN-00:10 | 132918.33 | 10-AUG-18:10 |
Pumps:Electricity | 89.65 | 49.72 | 01-MAR-08:50 | 5060.00 | 10-AUG-18:10 |
General:Pumps:Electricity | 89.65 | 49.72 | 01-MAR-08:50 | 5060.00 | 10-AUG-18:10 |
WIRED_LTG_ELECTRICITY | 19.13 | 0.00 | 01-JAN-00:10 | 1598.93 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4072.73 | 29270.80 | 05-MAY-01:10 | 376862.71 | 26-JAN-18:40 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 2283.89 | 15908.90 | 27-APR-10:10 | 280043.50 | 26-JAN-19:10 |
WaterSystems:NaturalGas | 1177.67 | 15908.90 | 01-JAN-16:10 | 112926.47 | 31-JAN-21:30 |
Water Heater:WaterSystems:NaturalGas | 1177.67 | 15908.90 | 01-JAN-16:10 | 112926.47 | 31-JAN-21:30 |
Heating:NaturalGas | 1106.22 | 0.00 | 27-FEB-11:20 | 168851.31 | 26-NOV-19:10 |
Boiler:Heating:NaturalGas | 1106.22 | 0.00 | 27-FEB-11:20 | 168851.31 | 26-NOV-19:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 1308.28 | 0.00 | 01-JAN-00:10 | 439469.90 | 10-AUG-18:20 |
PlantLoopCoolingDemand:HVAC | 1308.28 | 0.00 | 01-JAN-00:10 | 439469.90 | 10-AUG-18:20 |
CoolingCoils:PlantLoopCoolingDemand | 1308.28 | 0.00 | 01-JAN-00:10 | 439469.90 | 10-AUG-18:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-MAY-20:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-MAY-20:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-MAY-20:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-MAY-20:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-MAY-20:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-MAY-20:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 28-JUN-07:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 28-JUN-07:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 15004.97 | 132853.84 | 09-MAR-14:40 | 2005763.91 | 10-AUG-18:20 |
EnergyTransfer:Building | 4601.45 | 78891.58 | 16-JAN-15:00 | 324767.56 | 10-AUG-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 688.76 | 10834.07 | 19-FEB-04:00 | 34814.31 | 13-AUG-10:40 |
Refrigeration:EnergyTransfer | 183.08 | 4028.97 | 11-FEB-23:20 | 10348.09 | 29-AUG-06:50 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.54 | 2014.49 | 11-FEB-23:20 | 5174.04 | 29-AUG-06:50 |
General:Refrigeration:EnergyTransfer | 91.54 | 2014.49 | 11-FEB-23:20 | 5174.04 | 29-AUG-06:50 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.54 | 2014.49 | 11-FEB-23:20 | 5174.04 | 29-AUG-06:50 |
EnergyTransfer:Plant | 4842.83 | 17446.64 | 17-OCT-02:50 | 1051917.67 | 10-AUG-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.61 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.93 | 1846.04 | 12-FEB-04:10 | 2554.73 | 30-AUG-13:40 |
EnergyTransfer:HVAC | 5560.69 | 1079.65 | 10-OCT-14:40 | 629572.70 | 10-AUG-18:20 |
CoolingCoils:EnergyTransfer | 2523.71 | 0.00 | 01-JAN-00:10 | 552765.22 | 10-AUG-18:20 |
EnergyTransfer:Zone:BASEMENT | 316.83 | 8166.78 | 23-APR-15:00 | 13325.24 | 10-SEP-10:40 |
Heating:EnergyTransfer | 76.98 | 0.00 | 01-JAN-08:10 | 49146.07 | 26-DEC-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 76.98 | 0.00 | 01-JAN-08:10 | 49146.07 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4432.93 | 70538.41 | 26-DEC-15:00 | 321161.26 | 10-AUG-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 316.83 | 8166.78 | 23-APR-15:00 | 13325.24 | 10-SEP-10:40 |
General:Cooling:EnergyTransfer | 4432.93 | 70538.41 | 26-DEC-15:00 | 321161.26 | 10-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 316.83 | 8166.78 | 23-APR-15:00 | 13325.24 | 10-SEP-10:40 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 37.99 | 0.06 | 18-FEB-23:10 | 3930.50 | 04-OCT-12:50 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.19 | 0.00 | 01-JAN-00:10 | 599.72 | 26-DEC-10:50 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.19 | 0.00 | 01-JAN-00:10 | 599.72 | 26-DEC-10:50 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 37.80 | 0.00 | 01-JAN-02:30 | 3930.50 | 04-OCT-12:50 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 37.80 | 0.00 | 01-JAN-02:30 | 3930.50 | 04-OCT-12:50 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 31.96 | 376.61 | 26-DEC-15:00 | 1847.44 | 10-AUG-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 31.96 | 376.61 | 26-DEC-15:00 | 1847.44 | 10-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 31.96 | 376.61 | 26-DEC-15:00 | 1847.44 | 10-AUG-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 21.38 | 0.93 | 15-JAN-17:10 | 1147.93 | 10-AUG-21:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 68.05 | 16-JAN-16:00 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 68.05 | 16-JAN-16:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 21.38 | 0.00 | 15-JAN-15:30 | 1147.93 | 10-AUG-21:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 21.38 | 0.00 | 15-JAN-15:30 | 1147.93 | 10-AUG-21:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 10.44 | 0.06 | 23-JAN-15:00 | 600.40 | 10-AUG-10:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 151.74 | 16-JAN-17:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 151.74 | 16-JAN-17:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 10.42 | 0.00 | 01-JAN-14:30 | 600.40 | 10-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 10.42 | 0.00 | 01-JAN-14:30 | 600.40 | 10-AUG-10:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 594.92 | 9718.63 | 17-JAN-05:00 | 38564.68 | 10-AUG-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 594.92 | 9718.63 | 17-JAN-05:00 | 38564.68 | 10-AUG-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 594.92 | 9718.63 | 17-JAN-05:00 | 38564.68 | 10-AUG-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 235.77 | 696.33 | 26-DEC-12:20 | 13939.68 | 04-OCT-12:50 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 235.77 | 696.33 | 26-DEC-12:20 | 13939.68 | 04-OCT-12:50 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 235.77 | 696.33 | 26-DEC-12:20 | 13939.68 | 04-OCT-12:50 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 765.54 | 10613.04 | 26-DEC-15:00 | 38667.66 | 10-AUG-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 765.54 | 10613.04 | 26-DEC-15:00 | 38667.66 | 10-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 765.54 | 10613.04 | 26-DEC-15:00 | 38667.66 | 10-AUG-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 47.25 | 0.00 | 01-JAN-08:10 | 11717.58 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 10.96 | 0.00 | 01-JAN-08:10 | 4722.93 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 10.96 | 0.00 | 01-JAN-08:10 | 4722.93 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 36.29 | 0.00 | 01-JAN-00:10 | 11717.58 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 36.29 | 0.00 | 01-JAN-00:10 | 11717.58 | 10-AUG-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 37.51 | 0.00 | 01-JAN-08:10 | 11070.72 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 13.75 | 0.00 | 01-JAN-08:10 | 4799.76 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 13.75 | 0.00 | 01-JAN-08:10 | 4799.76 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 23.76 | 0.00 | 01-JAN-00:10 | 11070.72 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 23.76 | 0.00 | 01-JAN-00:10 | 11070.72 | 10-AUG-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 231.87 | 0.00 | 01-JAN-00:10 | 54524.73 | 04-OCT-12:40 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 231.87 | 0.00 | 01-JAN-00:10 | 54524.73 | 04-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 231.87 | 0.00 | 01-JAN-00:10 | 54524.73 | 04-OCT-12:40 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 294.41 | 0.00 | 01-JAN-08:10 | 58532.56 | 24-JUL-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 7.36 | 0.00 | 01-JAN-00:10 | 18301.97 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 7.36 | 0.00 | 01-JAN-00:10 | 18301.97 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 287.05 | 0.00 | 01-JAN-08:10 | 58532.56 | 24-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 287.05 | 0.00 | 01-JAN-08:10 | 58532.56 | 24-JUL-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 45.50 | 0.00 | 01-JAN-08:10 | 10261.68 | 10-AUG-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 11.01 | 0.00 | 01-JAN-08:10 | 4718.10 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 11.01 | 0.00 | 01-JAN-08:10 | 4718.10 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 34.50 | 0.00 | 01-JAN-00:10 | 10261.68 | 10-AUG-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 34.50 | 0.00 | 01-JAN-00:10 | 10261.68 | 10-AUG-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 37.03 | 0.00 | 01-JAN-08:10 | 10446.69 | 24-JUL-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 13.71 | 0.00 | 01-JAN-08:10 | 4788.65 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 13.71 | 0.00 | 01-JAN-08:10 | 4788.65 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 23.32 | 0.00 | 01-JAN-00:10 | 10446.69 | 24-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 23.32 | 0.00 | 01-JAN-00:10 | 10446.69 | 24-JUL-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 143.40 | 0.58 | 19-JAN-10:20 | 8636.04 | 13-AUG-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.45 | 0.00 | 01-JAN-00:10 | 2483.92 | 26-DEC-15:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.45 | 0.00 | 01-JAN-00:10 | 2483.92 | 26-DEC-15:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 142.95 | 0.00 | 01-JAN-13:10 | 8636.04 | 13-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 142.95 | 0.00 | 01-JAN-13:10 | 8636.04 | 13-AUG-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 13.56 | 0.00 | 01-JAN-08:10 | 3188.17 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 4.67 | 0.00 | 01-JAN-08:10 | 1559.62 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 4.67 | 0.00 | 01-JAN-08:10 | 1559.62 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 8.89 | 0.00 | 01-JAN-00:10 | 3188.17 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 8.89 | 0.00 | 01-JAN-00:10 | 3188.17 | 10-AUG-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 11.45 | 0.00 | 01-JAN-08:10 | 2996.37 | 14-JUL-16:30 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.63 | 0.00 | 01-JAN-08:10 | 1571.34 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.63 | 0.00 | 01-JAN-08:10 | 1571.34 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.82 | 0.00 | 01-JAN-00:10 | 2996.37 | 14-JUL-16:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.82 | 0.00 | 01-JAN-00:10 | 2996.37 | 14-JUL-16:30 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 72.18 | 0.00 | 01-JAN-08:10 | 17138.77 | 14-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 9.18 | 0.00 | 01-JAN-08:10 | 6902.40 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 9.18 | 0.00 | 01-JAN-08:10 | 6902.40 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 63.00 | 0.00 | 01-JAN-00:10 | 17138.77 | 14-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 63.00 | 0.00 | 01-JAN-00:10 | 17138.77 | 14-SEP-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 420.07 | 8602.30 | 26-DEC-15:00 | 21892.99 | 24-JUL-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 420.07 | 8602.30 | 26-DEC-15:00 | 21892.99 | 24-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 420.07 | 8602.30 | 26-DEC-15:00 | 21892.99 | 24-JUL-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 462.45 | 9656.27 | 26-DEC-15:00 | 23198.95 | 24-JUL-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 462.45 | 9656.27 | 26-DEC-15:00 | 23198.95 | 24-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 462.45 | 9656.27 | 26-DEC-15:00 | 23198.95 | 24-JUL-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 597.22 | 8735.69 | 19-FEB-04:00 | 29726.32 | 13-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 597.22 | 8735.69 | 19-FEB-04:00 | 29726.32 | 13-AUG-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 81.18 | 0.81 | 16-JAN-01:50 | 5774.41 | 10-AUG-15:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.06 | 0.00 | 01-JAN-00:10 | 786.15 | 19-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.06 | 0.00 | 01-JAN-00:10 | 786.15 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 81.12 | 0.00 | 06-JAN-07:10 | 5774.41 | 10-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 81.12 | 0.00 | 06-JAN-07:10 | 5774.41 | 10-AUG-15:10 |
PlantLoopHeatingDemand:Facility | 3158.40 | 9874.09 | 11-AUG-01:20 | 293277.32 | 09-NOV-18:50 |
PlantLoopHeatingDemand:Plant | 2385.78 | 9874.09 | 11-AUG-01:20 | 208806.21 | 31-AUG-20:20 |
WaterSystems:PlantLoopHeatingDemand | 2385.78 | 9874.09 | 11-AUG-01:20 | 208806.21 | 31-AUG-20:20 |
General:WaterSystems:PlantLoopHeatingDemand | 780.84 | 9869.59 | 12-AUG-01:10 | 55579.99 | 14-FEB-08:00 |
HeatingCoils:EnergyTransfer | 772.62 | 0.00 | 27-FEB-11:20 | 127305.83 | 25-NOV-19:10 |
PlantLoopHeatingDemand:HVAC | 772.62 | 0.00 | 27-FEB-11:20 | 127305.83 | 25-NOV-19:10 |
HeatingCoils:PlantLoopHeatingDemand | 772.62 | 0.00 | 27-FEB-11:20 | 127305.83 | 25-NOV-19:10 |
HeatRecoveryForHeating:EnergyTransfer | 2248.85 | 0.00 | 01-JAN-11:10 | 372652.22 | 19-FEB-06:30 |
HeatRecoveryForCooling:EnergyTransfer | 15.50 | 0.00 | 01-JAN-00:10 | 86317.59 | 29-AUG-13:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 1604.94 | 0.00 | 01-JAN-00:10 | 170398.80 | 31-AUG-20:20 |
WaterSystems:EnergyTransfer | 780.84 | 9869.59 | 12-AUG-01:10 | 55579.99 | 14-FEB-08:00 |
WaterUse:WaterSystems:EnergyTransfer | 780.84 | 9869.59 | 12-AUG-01:10 | 55579.99 | 14-FEB-08:00 |
Boilers:EnergyTransfer | 765.55 | 0.00 | 27-FEB-11:20 | 131276.04 | 25-NOV-19:10 |
Chillers:EnergyTransfer | 1384.26 | 0.00 | 01-JAN-00:10 | 442096.70 | 10-AUG-18:20 |
HeatRejection:EnergyTransfer | 1820.65 | 0.00 | 01-JAN-00:10 | 574988.38 | 10-AUG-18:10 |
General:HeatRejection:EnergyTransfer | 1820.65 | 0.00 | 01-JAN-00:10 | 574988.38 | 10-AUG-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -316.830 | 0.000 | 0.000 | 144.258 | 102.033 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -72.566 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.188 | -37.798 | 0.000 | 0.000 | 15.947 | 5.638 | 10.186 | 20.825 | 0.000 | 0.008 | 0.000 | 0.000 | -9.624 | 0.000 | -0.987 | -4.383 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -31.963 | 0.000 | 0.000 | 17.187 | 6.529 | 11.795 | 0.000 | 0.000 | 0.003 | 0.000 | 0.000 | 0.000 | 0.000 | -0.419 | -3.131 |
MECH_FLR_1 | 0.000 | 0.000 | 0.001 | -21.378 | 0.000 | 0.000 | 3.754 | 7.530 | 12.471 | 0.000 | 0.000 | 0.008 | 0.000 | 0.000 | 0.000 | 0.000 | -0.951 | -1.436 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.027 | -10.417 | 0.000 | 0.000 | 2.918 | 1.680 | 3.598 | 0.000 | 0.000 | 0.005 | 2.730 | 0.000 | 0.000 | 0.000 | -0.540 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -594.919 | 0.000 | 0.000 | 11.368 | 4.410 | 658.131 | 0.000 | 0.000 | 0.012 | 0.000 | 0.000 | 0.000 | 0.000 | -1.405 | -77.598 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -235.769 | 0.000 | 0.000 | 199.304 | 11.670 | 14.341 | 57.887 | 0.000 | 0.017 | 0.000 | 0.000 | -28.717 | 0.000 | -2.325 | -16.408 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -765.546 | 0.000 | 0.000 | 565.372 | 110.739 | 148.998 | 75.915 | 0.000 | 0.049 | 0.000 | 0.000 | -40.158 | 0.000 | -7.061 | -88.309 |
ROOM_1_FLR_3 | 15.230 | -30.048 | 0.000 | -10.508 | 0.000 | 0.000 | 9.724 | 5.554 | 12.292 | 39.222 | 0.000 | 0.075 | 0.000 | 0.000 | -22.102 | 0.000 | -2.929 | -16.510 |
ROOM_2_FLR_3 | 18.424 | -17.440 | 0.000 | -10.990 | 0.000 | 0.000 | 9.599 | 5.553 | 12.291 | 27.160 | 0.000 | 0.029 | 0.000 | 0.000 | -22.670 | 0.000 | -3.345 | -18.610 |
ROOM_3_MULT19_FLR_3 | 0.000 | -217.658 | 0.000 | -14.209 | 0.000 | 0.000 | 0.000 | 66.316 | 228.754 | 227.722 | 0.000 | 0.016 | 0.002 | 0.000 | -160.995 | 0.000 | -16.932 | -113.014 |
ROOM_4_MULT19_FLR_3 | 32.093 | -165.793 | 0.000 | -145.980 | 0.000 | 0.000 | 183.262 | 66.334 | 228.817 | 65.795 | 0.000 | 0.380 | 0.000 | 0.000 | -126.050 | 0.000 | -29.121 | -109.737 |
ROOM_5_FLR_3 | 15.276 | -28.256 | 0.000 | -10.511 | 0.000 | 0.000 | 9.720 | 5.554 | 12.292 | 37.428 | 0.000 | 0.076 | 0.000 | 0.000 | -21.649 | 0.000 | -2.927 | -17.004 |
ROOM_6_FLR_3 | 18.384 | -17.155 | 0.000 | -10.840 | 0.000 | 0.000 | 9.649 | 5.553 | 12.291 | 25.359 | 0.000 | 0.031 | 0.000 | 0.000 | -22.010 | 0.000 | -3.327 | -17.936 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.445 | -142.952 | 0.000 | 0.000 | 120.288 | 51.065 | 0.000 | 35.375 | 0.000 | 0.023 | 0.000 | 0.000 | -28.421 | 0.000 | -2.877 | -32.946 |
ROOM_1_FLR_6 | 5.890 | -7.493 | 0.000 | -2.623 | 0.000 | 0.000 | 2.435 | 1.388 | 3.073 | 9.741 | 0.000 | 0.020 | 0.000 | 0.000 | -5.476 | 0.000 | -0.756 | -6.199 |
ROOM_2_FLR_6 | 6.927 | -4.361 | 0.000 | -2.761 | 0.000 | 0.000 | 2.398 | 1.388 | 3.073 | 6.730 | 0.000 | 0.008 | 0.000 | 0.000 | -5.628 | 0.000 | -0.851 | -6.922 |
ROOM_3_MULT9_FLR_6 | 14.484 | -51.351 | 0.000 | -16.955 | 0.000 | 0.000 | 21.818 | 7.855 | 27.097 | 53.394 | 0.000 | 0.158 | 0.000 | 0.000 | -25.846 | 0.000 | -4.291 | -26.363 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -420.075 | 0.000 | 0.000 | 317.020 | 25.560 | 175.857 | 6.529 | 0.000 | 0.007 | 0.000 | 0.000 | -17.427 | 0.000 | -1.723 | -85.749 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -462.456 | 0.000 | 0.000 | 315.595 | 25.560 | 175.857 | 6.306 | 0.000 | 0.007 | 0.000 | 0.000 | -17.999 | 0.000 | -1.741 | -41.130 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -597.205 | 0.000 | 0.000 | 28.590 | 12.005 | 540.650 | 17.990 | 0.000 | 0.006 | 10.934 | 0.000 | -11.421 | 0.000 | -1.550 | -0.002 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.060 | -81.117 | 0.000 | 0.000 | 31.938 | 13.511 | 0.000 | 17.293 | 0.000 | 0.008 | 32.435 | 0.000 | -12.851 | 0.000 | -1.276 | -0.000 |
Total Facility | 126.709 | -539.556 | 0.721 | -3943.802 | 0.000 | 0.000 | 2022.146 | 543.427 | 2434.967 | 730.668 | 0.000 | 0.947 | 46.102 | 0.000 | -579.043 | 0.000 | -87.333 | -755.953 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 10-SEP-10:33 | 0.00 | 0.00 | 0.00 | -13393.50 | 0.00 | 0.00 | 2388.04 | 2781.33 | 4055.80 | 0.00 | 0.00 | 0.00 | 4168.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 04-OCT-12:50 | 0.00 | 0.00 | 0.00 | -3930.06 | 0.00 | 0.00 | 150.60 | 128.08 | 252.59 | 6357.14 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -9.91 | -2948.43 |
RETAIL_2_FLR_1 | 10-AUG-20:55 | 0.00 | 0.00 | 0.00 | -1847.64 | 0.00 | 0.00 | 697.58 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1.12 | -75.58 |
MECH_FLR_1 | 10-AUG-20:57 | 0.00 | 0.00 | 0.00 | -1147.96 | 0.00 | 0.00 | 147.52 | 547.34 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2.64 | -339.53 |
STORAGE_FLR_1 | 10-AUG-10:35 | 0.00 | 0.00 | 0.00 | -601.40 | 0.00 | 0.00 | 30.09 | 38.16 | 89.22 | 0.00 | 0.00 | 1.33 | 442.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 10-AUG-20:00 | 0.00 | 0.00 | 0.00 | -38566.09 | 0.00 | 0.00 | 408.86 | 360.62 | 44299.38 | 0.00 | 0.00 | 5.69 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6508.45 |
CAFE_FLR_1 | 04-OCT-12:50 | 0.00 | 0.00 | 0.00 | -13938.11 | 0.00 | 0.00 | 1979.10 | 86.54 | 355.63 | 17832.70 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -21.91 | -6293.95 |
LOBBY_FLR_1 | 10-AUG-21:05 | 0.00 | 0.00 | 0.00 | -38681.12 | 0.00 | 0.00 | 26437.40 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -643.27 | 0.00 | -19.77 | -870.42 |
ROOM_1_FLR_3 | 24-AUG-18:02 | 0.00 | -12339.89 | 0.00 | -743.32 | 0.00 | 0.00 | 335.50 | 380.45 | 516.26 | 6316.64 | 0.00 | 33.00 | 5501.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 25-JUL-16:51 | 0.00 | -12782.63 | 0.00 | -933.51 | 0.00 | 0.00 | 193.82 | 119.68 | 537.27 | 4952.49 | 0.00 | 1.97 | 7910.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 04-OCT-12:40 | 0.00 | -54524.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1429.19 | 5097.90 | 76246.36 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -219.26 | -28029.25 |
ROOM_4_MULT19_FLR_3 | 24-JUL-18:02 | 0.00 | -56144.27 | 0.00 | -10300.00 | 0.00 | 0.00 | 6374.46 | 4544.07 | 9610.21 | 13720.01 | 0.00 | 200.29 | 31995.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 09-AUG-18:02 | 0.00 | -10916.85 | 0.00 | -728.99 | 0.00 | 0.00 | 335.49 | 380.45 | 516.26 | 859.23 | 0.00 | 32.94 | 9521.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 24-JUL-08:32 | 0.00 | -11743.06 | 0.00 | -1062.31 | 0.00 | 0.00 | 58.94 | 188.06 | 452.99 | 9326.50 | 0.00 | 0.00 | 2804.57 | 0.00 | -0.00 | 0.00 | -25.70 | 0.00 |
CORRIDOR_FLR_3 | 13-AUG-10:33 | 0.00 | 0.00 | 0.00 | -8653.06 | 0.00 | 0.00 | 1836.63 | 1392.00 | 0.00 | 7042.72 | 0.00 | 7.29 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1625.60 |
ROOM_1_FLR_6 | 10-AUG-18:02 | 0.00 | -3235.98 | 0.00 | -188.16 | 0.00 | 0.00 | 83.87 | 95.11 | 129.07 | 2042.18 | 0.00 | 12.41 | 1061.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 25-JUL-16:51 | 0.00 | -3306.35 | 0.00 | -234.05 | 0.00 | 0.00 | 48.37 | 29.92 | 134.32 | 1224.45 | 0.00 | 0.33 | 2103.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 24-AUG-15:02 | 0.00 | -17343.07 | 0.00 | -1200.15 | 0.00 | 0.00 | 529.39 | 169.29 | 603.86 | 7964.83 | 0.00 | 50.90 | 9224.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 24-JUL-21:10 | 0.00 | 0.00 | 0.00 | -21894.51 | 0.00 | 0.00 | 15643.59 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -204.50 | 0.00 | -6.87 | -1943.49 |
DINING_FLR_6 | 24-JUL-21:20 | 0.00 | 0.00 | 0.00 | -23200.46 | 0.00 | 0.00 | 15636.41 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -241.23 | 0.00 | -8.40 | -592.11 |
KITCHEN_FLR_6 | 13-AUG-10:33 | 0.00 | 0.00 | 0.00 | -29719.15 | 0.00 | 0.00 | 464.22 | 327.25 | 23951.61 | 3672.65 | 0.00 | 0.27 | 1303.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 10-AUG-15:03 | 0.00 | 0.00 | 0.00 | -5775.46 | 0.00 | 0.00 | 771.14 | 306.92 | 0.00 | 2443.69 | 0.00 | 21.90 | 2231.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-AUG-18:02 | 0.00 | -151966.16 | 0.00 | -195285.46 | 0.00 | 0.00 | 75765.42 | 36835.53 | 121562.63 | 47371.05 | 0.00 | 1092.63 | 64624.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 26-DEC-10:10 | 0.00 | 0.00 | 600.15 | 0.00 | 0.00 | 0.00 | 179.03 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -631.61 | 0.00 | -66.76 | -461.48 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 16-JAN-16:00 | 0.00 | 0.00 | 68.05 | 0.00 | 0.00 | 0.00 | 43.84 | 136.84 | 265.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -54.29 | -459.53 |
STORAGE_FLR_1 | 16-JAN-17:00 | 0.00 | 0.00 | 151.74 | 0.00 | 0.00 | 0.00 | 50.59 | 30.52 | 76.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -32.21 | -277.11 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 15-JAN-09:01 | 7547.42 | 326.15 | 0.00 | -326.15 | 0.00 | 0.00 | 160.52 | 239.38 | 653.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -476.41 | 0.00 | -168.37 | -7955.77 |
ROOM_2_FLR_3 | 19-FEB-09:01 | 7523.16 | 293.88 | 0.00 | -293.88 | 0.00 | 0.00 | 163.31 | 239.35 | 653.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1381.26 | 0.00 | -165.82 | -7031.90 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 26-DEC-16:02 | 38766.47 | 4894.35 | 0.00 | -4894.35 | 0.00 | 0.00 | 5323.22 | 1429.58 | 5099.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8305.18 | 0.00 | -659.28 | -41654.10 |
ROOM_5_FLR_3 | 26-DEC-09:02 | 7407.21 | 297.88 | 0.00 | -297.88 | 0.00 | 0.00 | 108.88 | 188.08 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1664.66 | 0.00 | -151.68 | -6340.89 |
ROOM_6_FLR_3 | 08-JAN-09:01 | 7329.12 | 308.85 | 0.00 | -308.85 | 0.00 | 0.00 | 161.99 | 239.35 | 653.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -806.19 | 0.00 | -158.31 | -7419.11 |
CORRIDOR_FLR_3 | 26-DEC-15:00 | 0.00 | 0.00 | 2483.91 | 0.00 | 0.00 | 0.00 | 1385.81 | 1160.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1721.35 | 0.00 | -166.34 | -3142.03 |
ROOM_1_FLR_6 | 15-JAN-09:01 | 2301.76 | 75.07 | 0.00 | -75.07 | 0.00 | 0.00 | 40.83 | 59.85 | 163.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -110.51 | 0.00 | -41.56 | -2413.67 |
ROOM_2_FLR_6 | 19-FEB-09:01 | 2274.92 | 74.27 | 0.00 | -74.27 | 0.00 | 0.00 | 40.83 | 59.84 | 163.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -342.25 | 0.00 | -41.65 | -2154.97 |
ROOM_3_MULT9_FLR_6 | 26-DEC-16:02 | 11041.99 | 479.10 | 0.00 | -479.10 | 0.00 | 0.00 | 661.46 | 169.29 | 603.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1672.99 | 0.00 | -136.59 | -10667.03 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 19-FEB-06:00 | 0.00 | 0.00 | 786.13 | 0.00 | 0.00 | 0.00 | 1283.23 | 245.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1462.64 | 0.00 | -105.69 | -746.56 |
Total Facility | 26-DEC-09:02 | -3960.10 | 94815.56 | 3060.79 | -94815.56 | 0.00 | 0.00 | 23397.68 | 19336.35 | 87870.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -40749.63 | 0.00 | -4021.97 | -84933.74 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 21.2505 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 21.1415 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6666 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6666 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0484 | 2.0484 | 1.1246 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4285 | 0.4285 | 0.2352 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2151 | 0.2151 | 0.1181 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1635 | 0.1635 | 0.0898 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0880 | 0.0880 | 0.0483 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2881 | 3.2881 | 1.8051 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7398 | 1.7398 | 0.9551 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.8919 | 4.8919 | 2.6856 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2448 | 1.2448 | 0.6834 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0720 | 2.0720 | 1.1376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1749 | 2.1749 | 1.1940 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1839 | 2.1839 | 1.1989 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7117 | 0.7117 | 0.3907 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 21.2505 | 21.1415 | 21.2505 | 11.6666 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1246 | 1.1246 | 1.1246 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2352 | 0.2352 | 0.2352 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1181 | 0.1181 | 0.1181 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0898 | 0.0898 | 0.0898 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0483 | 0.0483 | 0.0483 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8051 | 1.8051 | 1.8051 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9551 | 0.9551 | 0.9551 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6856 | 2.6856 | 2.6856 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6834 | 0.6834 | 0.6834 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1376 | 1.1376 | 1.1376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1940 | 1.1940 | 1.1940 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1989 | 1.1989 | 1.1989 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3907 | 0.3907 | 0.3907 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6666 | 11.6666 | 11.6666 | 11.6666 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 72.00 |
Number of hours not met | 72.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1106.22 | 168851.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 436.38 | 132918.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 543.43 | 45424.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 174.02 | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 952.41 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 22.42 | 1279.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 530.52 | 32360.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 89.65 | 5060.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 131.00 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4738.77 | 1177.67 | 112926.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Other | 0.00 | 37035.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.73 | 1306.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 21.06 | 716.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1772.02 | 4809.40 |
Natural Gas | 1788.84 | 4072.73 |
Additional | 0.00 | 0.00 |
Total | 3560.86 | 8882.13 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 47.90 |
Space Heating | 0.00 |
Space Cooling | 38.46 |
Fans (All) | 46.76 |
Service Water Heating | 43.27 |
Receptacle Equipment | 152.32 |
Miscellaneous (All) | 423.91 |
Subtotal | 423.91 |
Natural Gas [MJ/m2] | |
Space Heating | 97.51 |
Service Water Heating | 103.80 |
Miscellaneous (All) | 358.98 |
Subtotal | 358.98 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.12 |
Space Heating | 12.45 |
Space Cooling | 4.91 |
Fans (All) | 5.97 |
Service Water Heating | 18.79 |
Receptacle Equipment | 39.60 |
Miscellaneous | 12.16 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2398. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 2482. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8696.83 | 63.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7909.00 | 851.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8749.17 | 10.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8647.00 | 113.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 851.00 | 0.00 | 0.00 | 0.00 |
Average | 8712.82 | 47.18 | 0.00 | 0.00 | 0.00 |
Sum | 191682.00 | 1038.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4135.17 | 18.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4113.67 | 40.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 40.33 | 0.00 | 0.00 | 0.00 |
Average | 288884.36 | 2.69 | 0.00 | 0.00 | 0.00 |
Sum | 6355455.83 | 59.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8754.67 | 5.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8735.83 | 24.17 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8674.17 | 85.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7288.50 | 1471.50 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8736.83 | 23.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8616.83 | 143.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8715.33 | 44.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8737.00 | 23.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8753.33 | 6.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7288.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1471.50 | 0.00 | 0.00 | 0.00 |
Average | 8676.93 | 83.07 | 0.00 | 0.00 | 0.00 |
Sum | 190892.50 | 1827.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 709734.33 | 682.67 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2106373.17 | 9055.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4117.17 | 36.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4085.33 | 68.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1235976.33 | 9738.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1240663.00 | 5052.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108230.00 | 39.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2106373.17 | 9738.67 | 0.00 | 0.00 | 0.00 |
Average | 287765.52 | 1121.53 | 0.00 | 0.00 | 0.00 |
Sum | 6330841.33 | 24673.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:49
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259652E+11 | 11460.79 | 11-JAN-21:00 | 11.10 | 10.22 | 0.730737E+10 | 4540.02 | 13-JAN-22:10 | 0.60 | 0.60 |
February | 0.228926E+11 | 11338.77 | 01-FEB-21:00 | 6.70 | 5.41 | 0.647238E+10 | 4484.84 | 01-FEB-22:10 | 6.60 | 5.31 |
March | 0.247932E+11 | 11251.95 | 25-MAR-10:33 | 8.87 | 1.80 | 0.703227E+10 | 4384.50 | 01-MAR-23:10 | 8.87 | 1.80 |
April | 0.239433E+11 | 11703.49 | 27-APR-18:10 | 25.55 | 15.86 | 0.670077E+10 | 4279.15 | 06-APR-22:10 | 25.55 | 15.86 |
May | 0.253915E+11 | 12044.34 | 14-MAY-10:33 | 20.03 | 12.68 | 0.699467E+10 | 4330.19 | 18-MAY-22:10 | 8.80 | 7.20 |
June | 0.255553E+11 | 12431.82 | 25-JUN-10:33 | 18.87 | 13.09 | 0.691346E+10 | 4423.77 | 23-JUN-22:10 | 18.87 | 13.09 |
July | 0.275196E+11 | 13019.74 | 30-JUL-10:33 | 23.33 | 16.24 | 0.728890E+10 | 4527.33 | 28-JUL-22:10 | 23.33 | 16.24 |
August | 0.283659E+11 | 13305.11 | 13-AUG-10:33 | 24.17 | 17.28 | 0.747716E+10 | 4628.46 | 18-AUG-22:10 | 15.65 | 12.22 |
September | 0.279286E+11 | 13393.70 | 10-SEP-10:33 | 18.33 | 13.89 | 0.740543E+10 | 4728.46 | 15-SEP-22:10 | 14.32 | 13.32 |
October | 0.290091E+11 | 13135.42 | 07-OCT-10:33 | 14.63 | 10.97 | 0.780741E+10 | 4829.98 | 13-OCT-21:10 | 9.40 | 8.82 |
November | 0.279392E+11 | 12853.58 | 04-NOV-10:33 | 17.23 | 14.47 | 0.759138E+10 | 4837.00 | 16-NOV-22:10 | 5.40 | 4.66 |
December | 0.275261E+11 | 12214.45 | 01-DEC-21:00 | 5.00 | 5.00 | 0.761202E+10 | 4795.34 | 01-DEC-22:10 | 4.82 | 4.54 |
Annual Sum or Average | 0.316830E+12 | 0.866032E+11 | ||||||||
Minimum of Months | 0.228926E+11 | 11251.95 | 5.00 | 1.80 | 0.647238E+10 | 4279.15 | 0.60 | 0.60 | ||
Maximum of Months | 0.290091E+11 | 13393.70 | 25.55 | 17.28 | 0.780741E+10 | 4837.00 | 25.55 | 16.24 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.972427E+09 | 2300.06 | 20-JAN-11:50 | 5.60 | 3.57 | 0.620766E+09 | 364.17 | 30-JAN-05:00 | 6.10 | 5.29 |
February | 0.173883E+10 | 2767.04 | 08-FEB-13:30 | 6.40 | 3.77 | 0.564807E+09 | 381.50 | 27-FEB-22:40 | 12.20 | 10.25 |
March | 0.271246E+10 | 3385.42 | 02-MAR-13:20 | 12.57 | 7.60 | 0.631545E+09 | 398.56 | 14-MAR-21:30 | 12.50 | 8.53 |
April | 0.340943E+10 | 3091.17 | 27-APR-13:05 | 26.10 | 16.37 | 0.615297E+09 | 426.74 | 27-APR-21:30 | 15.80 | 11.30 |
May | 0.400825E+10 | 2989.28 | 04-MAY-13:20 | 22.77 | 15.31 | 0.639727E+09 | 423.83 | 04-MAY-21:40 | 18.53 | 12.19 |
June | 0.423815E+10 | 2581.31 | 28-JUN-10:35 | 21.50 | 14.65 | 0.622241E+09 | 419.12 | 28-JUN-21:30 | 17.50 | 13.87 |
July | 0.492644E+10 | 2879.13 | 31-JUL-13:30 | 27.75 | 18.58 | 0.661252E+09 | 438.65 | 24-JUL-21:30 | 27.75 | 18.58 |
August | 0.509315E+10 | 3714.56 | 24-AUG-13:10 | 28.93 | 19.36 | 0.675307E+09 | 452.59 | 10-AUG-21:19 | 28.93 | 19.36 |
September | 0.441600E+10 | 3881.61 | 14-SEP-13:15 | 23.17 | 17.52 | 0.637157E+09 | 441.64 | 12-SEP-21:30 | 23.17 | 17.52 |
October | 0.336612E+10 | 3930.50 | 04-OCT-12:50 | 20.60 | 11.27 | 0.635283E+09 | 425.45 | 04-OCT-21:30 | 15.00 | 9.56 |
November | 0.171811E+10 | 3188.39 | 04-NOV-13:30 | 20.85 | 16.00 | 0.602189E+09 | 364.18 | 29-NOV-02:09 | 9.40 | 8.39 |
December | 0.119885E+10 | 2561.80 | 05-DEC-11:50 | 9.72 | 5.97 | 0.622095E+09 | 364.18 | 19-DEC-04:10 | 3.40 | 2.14 |
Annual Sum or Average | 0.377982E+11 | 0.752767E+10 | ||||||||
Minimum of Months | 0.972427E+09 | 2300.06 | 5.60 | 3.57 | 0.564807E+09 | 364.17 | 3.40 | 2.14 | ||
Maximum of Months | 0.509315E+10 | 3930.50 | 28.93 | 19.36 | 0.675307E+09 | 452.59 | 28.93 | 19.36 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225486E+10 | 1109.20 | 11-JAN-21:00 | 11.10 | 10.22 | 0.775857E+09 | 509.49 | 11-JAN-23:10 | 9.22 | 8.15 |
February | 0.217370E+10 | 1215.81 | 27-FEB-21:00 | 12.20 | 10.06 | 0.721227E+09 | 540.42 | 27-FEB-23:10 | 12.20 | 10.40 |
March | 0.258084E+10 | 1246.25 | 02-MAR-21:00 | 6.70 | 5.56 | 0.830349E+09 | 549.24 | 02-MAR-23:10 | 7.12 | 6.08 |
April | 0.264762E+10 | 1464.95 | 27-APR-21:00 | 17.20 | 11.44 | 0.824592E+09 | 569.55 | 26-APR-21:00 | 17.20 | 11.44 |
May | 0.287036E+10 | 1438.29 | 04-MAY-21:00 | 17.80 | 12.21 | 0.875313E+09 | 569.55 | 15-MAY-21:30 | 13.35 | 11.02 |
June | 0.286436E+10 | 1505.23 | 28-JUN-21:00 | 16.70 | 13.67 | 0.860539E+09 | 569.55 | 27-JUN-22:10 | 16.70 | 13.67 |
July | 0.311349E+10 | 1694.71 | 31-JUL-21:00 | 21.70 | 16.73 | 0.909872E+09 | 569.55 | 06-JUL-22:10 | 21.70 | 16.73 |
August | 0.316397E+10 | 1847.60 | 10-AUG-20:55 | 23.00 | 16.96 | 0.917806E+09 | 569.55 | 15-AUG-22:10 | 18.18 | 14.52 |
September | 0.289620E+10 | 1669.12 | 14-SEP-21:00 | 18.30 | 14.89 | 0.866015E+09 | 569.55 | 11-SEP-22:10 | 18.30 | 14.89 |
October | 0.271741E+10 | 1440.60 | 04-OCT-21:00 | 13.90 | 9.05 | 0.851899E+09 | 569.55 | 04-OCT-21:30 | 15.00 | 9.56 |
November | 0.237585E+10 | 1231.87 | 04-NOV-18:10 | 15.00 | 13.34 | 0.778702E+09 | 527.68 | 06-NOV-23:10 | 15.40 | 14.28 |
December | 0.230463E+10 | 1161.51 | 05-DEC-21:00 | 5.60 | 1.73 | 0.784243E+09 | 523.66 | 05-DEC-23:10 | 4.03 | 2.13 |
Annual Sum or Average | 0.319633E+11 | 0.999641E+10 | ||||||||
Minimum of Months | 0.217370E+10 | 1109.20 | 5.60 | 1.73 | 0.721227E+09 | 509.49 | 4.03 | 2.13 | ||
Maximum of Months | 0.316397E+10 | 1847.60 | 23.00 | 16.96 | 0.917806E+09 | 569.55 | 21.70 | 16.73 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106622E+10 | 743.32 | 11-JAN-21:00 | 11.10 | 10.22 | 0.152894E+09 | 96.19 | 11-JAN-22:10 | 10.82 | 10.11 |
February | 0.120211E+10 | 818.51 | 28-FEB-21:00 | 9.40 | 7.97 | 0.140064E+09 | 102.06 | 28-FEB-22:10 | 8.12 | 7.00 |
March | 0.172449E+10 | 817.61 | 18-MAR-18:10 | 18.03 | 9.10 | 0.160407E+09 | 101.36 | 10-MAR-22:10 | 18.03 | 9.10 |
April | 0.182679E+10 | 975.09 | 27-APR-18:10 | 25.55 | 15.86 | 0.161366E+09 | 110.28 | 28-APR-21:19 | 12.20 | 10.91 |
May | 0.205930E+10 | 1026.27 | 06-MAY-10:33 | 20.93 | 16.16 | 0.175725E+09 | 113.34 | 05-MAY-21:19 | 20.93 | 16.16 |
June | 0.210836E+10 | 1055.10 | 28-JUN-18:10 | 25.40 | 16.48 | 0.175930E+09 | 116.29 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.230043E+10 | 1115.60 | 24-JUL-18:10 | 28.72 | 17.86 | 0.187549E+09 | 120.12 | 24-JUL-21:10 | 22.43 | 16.40 |
August | 0.233540E+10 | 1147.94 | 10-AUG-20:57 | 23.00 | 16.96 | 0.190227E+09 | 120.45 | 10-AUG-21:10 | 22.92 | 16.74 |
September | 0.209147E+10 | 1059.33 | 14-SEP-10:33 | 19.43 | 16.41 | 0.175400E+09 | 117.26 | 14-SEP-21:19 | 17.93 | 14.75 |
October | 0.190724E+10 | 953.51 | 07-OCT-10:33 | 14.63 | 10.97 | 0.168781E+09 | 110.78 | 04-OCT-21:19 | 14.63 | 10.97 |
November | 0.152952E+10 | 864.95 | 04-NOV-10:33 | 17.23 | 14.47 | 0.152791E+09 | 103.34 | 06-NOV-22:10 | 15.10 | 14.35 |
December | 0.122628E+10 | 746.93 | 05-DEC-21:00 | 5.60 | 1.73 | 0.153309E+09 | 96.02 | 04-DEC-22:10 | 5.60 | 1.73 |
Annual Sum or Average | 0.213776E+11 | 0.199444E+10 | ||||||||
Minimum of Months | 0.106622E+10 | 743.32 | 5.60 | 1.73 | 0.140064E+09 | 96.02 | 5.60 | 1.73 | ||
Maximum of Months | 0.233540E+10 | 1147.94 | 28.72 | 17.86 | 0.190227E+09 | 120.45 | 22.92 | 16.74 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.323386E+09 | 376.09 | 11-JAN-21:00 | 11.10 | 10.22 | 0.116772E+09 | 71.27 | 11-JAN-23:10 | 9.22 | 8.15 |
February | 0.481632E+09 | 421.63 | 27-FEB-19:10 | 15.73 | 11.89 | 0.106396E+09 | 75.22 | 27-FEB-23:10 | 12.20 | 10.40 |
March | 0.855782E+09 | 430.97 | 18-MAR-10:33 | 11.27 | 7.86 | 0.120407E+09 | 74.79 | 10-MAR-23:10 | 11.27 | 7.86 |
April | 0.947939E+09 | 515.27 | 27-APR-18:10 | 25.55 | 15.86 | 0.121082E+09 | 81.91 | 27-APR-22:10 | 14.40 | 11.00 |
May | 0.107449E+10 | 548.76 | 06-MAY-10:33 | 20.93 | 16.16 | 0.131976E+09 | 84.34 | 05-MAY-22:10 | 20.93 | 16.16 |
June | 0.110431E+10 | 557.86 | 28-JUN-18:10 | 25.40 | 16.48 | 0.132426E+09 | 86.49 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.120794E+10 | 592.13 | 24-JUL-18:10 | 28.72 | 17.86 | 0.141347E+09 | 89.47 | 24-JUL-22:10 | 20.40 | 15.71 |
August | 0.122634E+10 | 601.38 | 10-AUG-10:35 | 23.93 | 17.55 | 0.143390E+09 | 90.64 | 10-AUG-22:10 | 21.82 | 15.74 |
September | 0.109315E+10 | 563.28 | 14-SEP-10:33 | 19.43 | 16.41 | 0.131892E+09 | 87.09 | 14-SEP-22:10 | 17.12 | 14.45 |
October | 0.987532E+09 | 505.38 | 04-OCT-10:33 | 18.33 | 11.02 | 0.126479E+09 | 82.30 | 04-OCT-22:10 | 15.73 | 10.00 |
November | 0.684222E+09 | 456.65 | 04-NOV-10:33 | 17.23 | 14.47 | 0.115312E+09 | 76.41 | 06-NOV-23:10 | 15.40 | 14.28 |
December | 0.429925E+09 | 392.52 | 03-DEC-11:33 | 11.33 | 5.78 | 0.116833E+09 | 70.69 | 05-DEC-23:10 | 4.03 | 2.13 |
Annual Sum or Average | 0.104166E+11 | 0.150431E+10 | ||||||||
Minimum of Months | 0.323386E+09 | 376.09 | 11.10 | 5.78 | 0.106396E+09 | 70.69 | 4.03 | 2.13 | ||
Maximum of Months | 0.122634E+10 | 601.38 | 28.72 | 17.86 | 0.143390E+09 | 90.64 | 21.82 | 16.16 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.484958E+11 | 36756.86 | 11-JAN-21:00 | 11.10 | 10.22 | 0.576368E+09 | 381.61 | 10-JAN-22:49 | 11.10 | 10.22 |
February | 0.443036E+11 | 37206.35 | 27-FEB-21:00 | 12.20 | 10.06 | 0.522201E+09 | 381.64 | 28-FEB-22:10 | 8.12 | 7.00 |
March | 0.499492E+11 | 37330.66 | 14-MAR-20:00 | 14.40 | 9.49 | 0.581214E+09 | 381.68 | 28-MAR-21:10 | 7.70 | 4.73 |
April | 0.489831E+11 | 38105.55 | 27-APR-20:00 | 19.40 | 13.66 | 0.562467E+09 | 381.67 | 07-APR-21:10 | 19.40 | 13.66 |
May | 0.513044E+11 | 38047.78 | 15-MAY-20:00 | 17.20 | 11.19 | 0.582208E+09 | 381.68 | 05-MAY-21:10 | 17.20 | 11.19 |
June | 0.502971E+11 | 38236.56 | 28-JUN-19:55 | 21.70 | 15.30 | 0.564918E+09 | 381.69 | 20-JUN-21:10 | 21.70 | 15.30 |
July | 0.522116E+11 | 38494.54 | 24-JUL-20:00 | 23.90 | 16.63 | 0.583195E+09 | 381.70 | 10-JUL-21:10 | 23.90 | 16.63 |
August | 0.526116E+11 | 38564.68 | 10-AUG-20:00 | 25.60 | 17.66 | 0.585132E+09 | 381.70 | 31-AUG-21:10 | 16.58 | 13.11 |
September | 0.499197E+11 | 38191.83 | 14-SEP-20:00 | 18.90 | 14.81 | 0.563943E+09 | 381.70 | 07-SEP-21:10 | 18.90 | 14.81 |
October | 0.504137E+11 | 37814.42 | 04-OCT-20:00 | 17.20 | 10.66 | 0.581532E+09 | 381.65 | 06-OCT-21:10 | 12.70 | 10.58 |
November | 0.478232E+11 | 37090.94 | 02-NOV-20:00 | 12.80 | 10.42 | 0.560409E+09 | 381.64 | 08-NOV-22:19 | 8.70 | 7.31 |
December | 0.486043E+11 | 36704.01 | 05-DEC-21:00 | 5.60 | 1.73 | 0.576928E+09 | 381.64 | 22-DEC-22:10 | 2.10 | 1.63 |
Annual Sum or Average | 0.594917E+12 | 0.684051E+10 | ||||||||
Minimum of Months | 0.443036E+11 | 36704.01 | 5.60 | 1.73 | 0.522201E+09 | 381.61 | 2.10 | 1.63 | ||
Maximum of Months | 0.526116E+11 | 38564.68 | 25.60 | 17.66 | 0.585132E+09 | 381.70 | 23.90 | 16.63 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152667E+11 | 9609.34 | 08-JAN-11:35 | 1.33 | 0.94 | 0.857280E+10 | 5637.44 | 11-JAN-22:40 | 9.97 | 8.97 |
February | 0.158648E+11 | 10904.38 | 08-FEB-13:30 | 6.40 | 3.77 | 0.798116E+10 | 6075.04 | 27-FEB-22:40 | 12.20 | 10.25 |
March | 0.191970E+11 | 12624.37 | 02-MAR-13:20 | 12.57 | 7.60 | 0.914009E+10 | 6232.61 | 14-MAR-21:40 | 12.40 | 8.44 |
April | 0.201228E+11 | 11410.15 | 27-APR-14:10 | 26.28 | 16.91 | 0.901091E+10 | 6427.49 | 27-APR-21:40 | 15.33 | 11.23 |
May | 0.215582E+11 | 11206.75 | 04-MAY-15:07 | 24.32 | 14.81 | 0.945262E+10 | 6415.41 | 04-MAY-21:40 | 18.53 | 12.19 |
June | 0.215214E+11 | 10855.73 | 28-JUN-18:10 | 25.40 | 16.48 | 0.929093E+10 | 6319.15 | 28-JUN-21:40 | 17.77 | 13.93 |
July | 0.233481E+11 | 11584.33 | 30-JUL-10:33 | 23.33 | 16.24 | 0.980403E+10 | 6462.13 | 31-JUL-22:10 | 20.05 | 15.96 |
August | 0.239436E+11 | 13013.71 | 24-AUG-15:03 | 29.62 | 19.18 | 0.998546E+10 | 6462.73 | 09-AUG-22:10 | 29.62 | 19.18 |
September | 0.221850E+11 | 13851.58 | 23-SEP-13:15 | 22.57 | 17.43 | 0.944137E+10 | 6462.74 | 11-SEP-22:10 | 22.57 | 17.43 |
October | 0.205120E+11 | 13939.68 | 04-OCT-12:50 | 20.60 | 11.27 | 0.932855E+10 | 6462.47 | 04-OCT-21:30 | 15.00 | 9.56 |
November | 0.164968E+11 | 12532.59 | 04-NOV-13:30 | 20.85 | 16.00 | 0.852257E+10 | 5839.81 | 02-NOV-21:40 | 20.85 | 16.00 |
December | 0.157508E+11 | 10603.03 | 02-DEC-11:33 | 11.83 | 6.03 | 0.863373E+10 | 5779.31 | 05-DEC-22:40 | 4.60 | 2.18 |
Annual Sum or Average | 0.235767E+12 | 0.109164E+12 | ||||||||
Minimum of Months | 0.152667E+11 | 9609.34 | 1.33 | 0.94 | 0.798116E+10 | 5637.44 | 4.60 | 2.18 | ||
Maximum of Months | 0.239436E+11 | 13939.68 | 29.62 | 19.18 | 0.998546E+10 | 6462.74 | 29.62 | 19.18 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.558828E+11 | 26634.88 | 11-JAN-22:00 | 11.10 | 10.49 | 0.276589E+11 | 18285.78 | 11-JAN-23:10 | 9.22 | 8.15 |
February | 0.533425E+11 | 28679.11 | 27-FEB-21:00 | 12.20 | 10.06 | 0.256571E+11 | 19182.10 | 27-FEB-23:10 | 12.20 | 10.40 |
March | 0.623762E+11 | 29307.13 | 02-MAR-22:20 | 7.60 | 6.29 | 0.293778E+11 | 19183.15 | 02-MAR-22:49 | 7.30 | 6.16 |
April | 0.632842E+11 | 33653.23 | 27-APR-21:10 | 16.73 | 11.41 | 0.289279E+11 | 19186.08 | 26-APR-21:00 | 16.73 | 11.41 |
May | 0.678978E+11 | 33707.90 | 04-MAY-21:52 | 18.90 | 12.17 | 0.304691E+11 | 19186.32 | 15-MAY-21:30 | 13.35 | 11.02 |
June | 0.676537E+11 | 34432.11 | 28-JUN-21:52 | 18.30 | 14.03 | 0.299067E+11 | 19186.26 | 27-JUN-22:10 | 18.30 | 14.03 |
July | 0.727006E+11 | 37088.92 | 24-JUL-21:10 | 22.43 | 16.40 | 0.312516E+11 | 19186.24 | 21-JUL-22:10 | 22.43 | 16.40 |
August | 0.740836E+11 | 38680.16 | 10-AUG-21:05 | 22.92 | 16.74 | 0.315399E+11 | 19186.22 | 15-AUG-22:10 | 18.18 | 14.52 |
September | 0.684255E+11 | 37325.29 | 14-SEP-21:10 | 18.12 | 14.82 | 0.300130E+11 | 19186.19 | 11-SEP-22:10 | 18.12 | 14.82 |
October | 0.653409E+11 | 34847.22 | 04-OCT-21:10 | 14.27 | 9.23 | 0.299943E+11 | 19185.88 | 04-OCT-21:30 | 15.00 | 9.56 |
November | 0.577230E+11 | 28938.83 | 04-NOV-10:33 | 17.23 | 14.47 | 0.276470E+11 | 18833.26 | 02-NOV-22:10 | 17.23 | 14.47 |
December | 0.568309E+11 | 27573.40 | 05-DEC-21:00 | 5.60 | 1.73 | 0.279105E+11 | 18674.79 | 05-DEC-22:49 | 4.50 | 2.23 |
Annual Sum or Average | 0.765542E+12 | 0.350354E+12 | ||||||||
Minimum of Months | 0.533425E+11 | 26634.88 | 5.60 | 1.73 | 0.256571E+11 | 18285.78 | 4.50 | 2.23 | ||
Maximum of Months | 0.740836E+11 | 38680.16 | 22.92 | 16.74 | 0.315399E+11 | 19186.32 | 22.43 | 16.40 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13466597.98 | 2324.45 | 05-JAN-16:02 | 5.73 | 4.38 | 93919194.22 | 56.69 | 24-JAN-04:19 | 5.00 | 3.79 |
February | 83767926.81 | 2868.48 | 12-FEB-16:02 | 6.52 | 1.59 | 86040428.00 | 56.69 | 28-FEB-00:20 | 12.03 | 10.57 |
March | 0.249964E+09 | 2984.65 | 18-MAR-18:01 | 18.03 | 9.10 | 96566216.80 | 56.69 | 18-MAR-23:40 | 9.80 | 8.00 |
April | 0.649394E+09 | 3027.13 | 01-APR-15:01 | 26.28 | 14.25 | 94574483.45 | 56.69 | 28-APR-21:49 | 12.20 | 10.91 |
May | 0.114172E+10 | 3216.03 | 14-MAY-18:02 | 21.83 | 11.88 | 98452473.33 | 56.69 | 31-MAY-21:19 | 15.77 | 12.64 |
June | 0.131876E+10 | 3030.06 | 30-JUN-15:02 | 20.60 | 14.39 | 95574025.52 | 56.69 | 21-JUN-21:40 | 20.60 | 14.39 |
July | 0.193312E+10 | 3253.12 | 31-JUL-18:02 | 26.42 | 18.31 | 98823229.92 | 56.70 | 24-JUL-22:40 | 26.42 | 18.31 |
August | 0.186036E+10 | 3270.78 | 24-AUG-18:02 | 27.77 | 18.38 | 98890724.30 | 56.70 | 09-AUG-22:49 | 27.77 | 18.38 |
September | 0.128774E+10 | 2996.83 | 29-SEP-15:02 | 20.18 | 14.29 | 95187924.50 | 56.70 | 14-SEP-21:49 | 20.18 | 14.29 |
October | 0.447496E+09 | 2981.08 | 08-OCT-15:01 | 19.50 | 13.11 | 96998645.34 | 56.69 | 05-OCT-00:10 | 19.50 | 13.11 |
November | 64781953.00 | 2929.47 | 04-NOV-15:02 | 20.92 | 15.94 | 91965030.31 | 56.69 | 05-NOV-01:19 | 12.97 | 12.22 |
December | 21065501.93 | 2714.18 | 03-DEC-16:02 | 10.92 | 4.95 | 94210604.87 | 56.69 | 12-DEC-04:19 | 1.33 | 1.33 |
Annual Sum or Average | 0.907163E+10 | 0.114120E+10 | ||||||||
Minimum of Months | 13466597.98 | 2324.45 | 5.73 | 1.59 | 86040428.00 | 56.69 | 1.33 | 1.33 | ||
Maximum of Months | 0.193312E+10 | 3270.78 | 27.77 | 18.38 | 98890724.30 | 56.70 | 27.77 | 18.38 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8413456.55 | 713.91 | 30-JAN-16:04 | 5.50 | 4.53 | 93229263.73 | 56.69 | 31-JAN-04:19 | 4.60 | 4.02 |
February | 29249271.53 | 2533.87 | 26-FEB-16:02 | 14.40 | 10.25 | 85157136.42 | 56.69 | 28-FEB-00:20 | 12.03 | 10.57 |
March | 0.103837E+09 | 2598.36 | 18-MAR-15:02 | 20.10 | 10.35 | 95829976.12 | 57.08 | 14-MAR-18:10 | 20.10 | 10.35 |
April | 0.396510E+09 | 3020.51 | 25-APR-17:41 | 14.60 | 8.96 | 95231976.23 | 73.23 | 27-APR-21:40 | 15.33 | 11.23 |
May | 0.764362E+09 | 3132.34 | 20-MAY-19:11 | 13.33 | 8.60 | 0.103410E+09 | 83.61 | 31-MAY-18:10 | 20.40 | 14.89 |
June | 0.950150E+09 | 3198.58 | 22-JUN-16:21 | 24.40 | 15.53 | 0.102267E+09 | 86.36 | 19-JUN-18:10 | 24.40 | 15.53 |
July | 0.138103E+10 | 3429.04 | 25-JUL-16:51 | 25.60 | 18.36 | 0.109436E+09 | 90.38 | 21-JUL-18:10 | 25.60 | 18.36 |
August | 0.133535E+10 | 3001.77 | 08-AUG-21:31 | 23.70 | 15.01 | 0.105695E+09 | 79.63 | 08-AUG-21:10 | 23.70 | 15.01 |
September | 0.737068E+09 | 3323.20 | 22-SEP-16:11 | 24.43 | 17.44 | 0.100645E+09 | 79.39 | 08-SEP-18:10 | 24.43 | 17.44 |
October | 0.198181E+09 | 2610.33 | 24-OCT-15:01 | 17.20 | 11.66 | 96837613.20 | 70.18 | 04-OCT-21:10 | 17.20 | 11.66 |
November | 27084763.82 | 2452.80 | 04-NOV-15:02 | 20.92 | 15.94 | 91375831.71 | 56.69 | 19-NOV-02:20 | 10.00 | 9.58 |
December | 8690798.70 | 1040.69 | 02-DEC-16:02 | 10.40 | 4.47 | 93419490.25 | 56.69 | 10-DEC-02:20 | 6.10 | 5.88 |
Annual Sum or Average | 0.593992E+10 | 0.117253E+10 | ||||||||
Minimum of Months | 8413456.55 | 713.91 | 5.50 | 4.47 | 85157136.42 | 56.69 | 4.60 | 4.02 | ||
Maximum of Months | 0.138103E+10 | 3429.04 | 25.60 | 18.36 | 0.109436E+09 | 90.38 | 25.60 | 18.36 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8834885.98 | 131.41 | 08-JAN-15:15 | 5.20 | 2.41 | 0.00 | 0.00 | 01-JAN-00:10 | 5.20 | 2.41 |
February | 62529139.78 | 489.77 | 08-FEB-13:40 | 6.50 | 3.79 | 0.00 | 0.00 | 01-FEB-00:10 | 6.50 | 3.79 |
March | 0.166074E+09 | 621.98 | 02-MAR-13:00 | 12.20 | 7.34 | 0.00 | 0.00 | 01-MAR-00:10 | 12.20 | 7.34 |
April | 0.260093E+09 | 565.55 | 27-APR-13:05 | 26.10 | 16.37 | 0.00 | 0.00 | 01-APR-00:10 | 26.10 | 16.37 |
May | 0.325103E+09 | 547.31 | 04-MAY-13:20 | 22.77 | 15.31 | 0.00 | 0.00 | 01-MAY-00:10 | 22.77 | 15.31 |
June | 0.358451E+09 | 415.99 | 28-JUN-13:05 | 24.50 | 15.71 | 0.00 | 0.00 | 01-JUN-00:10 | 24.50 | 15.71 |
July | 0.485165E+09 | 515.91 | 31-JUL-13:20 | 27.57 | 18.47 | 0.00 | 0.00 | 01-JUL-00:10 | 27.57 | 18.47 |
August | 0.546496E+09 | 643.11 | 24-AUG-13:05 | 28.93 | 19.36 | 0.00 | 0.00 | 01-AUG-00:10 | 28.93 | 19.36 |
September | 0.469021E+09 | 691.70 | 14-SEP-13:30 | 23.35 | 17.43 | 0.00 | 0.00 | 01-SEP-00:10 | 23.35 | 17.43 |
October | 0.279290E+09 | 717.43 | 04-OCT-12:40 | 20.60 | 11.32 | 0.00 | 0.00 | 01-OCT-00:10 | 20.60 | 11.32 |
November | 57015345.39 | 553.49 | 04-NOV-13:40 | 20.93 | 15.98 | 0.00 | 0.00 | 01-NOV-00:10 | 20.93 | 15.98 |
December | 32869094.38 | 437.12 | 05-DEC-12:30 | 10.30 | 6.13 | 0.00 | 0.00 | 01-DEC-00:10 | 10.30 | 6.13 |
Annual Sum or Average | 0.305094E+10 | 0.00 | ||||||||
Minimum of Months | 8834885.98 | 131.41 | 5.20 | 2.41 | 0.00 | 0.00 | 5.20 | 2.41 | ||
Maximum of Months | 0.546496E+09 | 717.43 | 28.93 | 19.36 | 0.00 | 0.00 | 28.93 | 19.36 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 65510877.46 | 635.00 | 12-JAN-09:02 | 6.70 | 5.79 | 95279671.13 | 56.69 | 11-JAN-22:10 | 6.70 | 5.79 |
February | 0.102748E+09 | 687.93 | 26-FEB-09:02 | 9.60 | 8.77 | 86508064.36 | 56.69 | 28-FEB-22:10 | 8.12 | 7.00 |
March | 0.218693E+09 | 722.40 | 20-MAR-18:02 | 9.82 | 6.66 | 96667720.37 | 56.69 | 18-MAR-23:30 | 9.82 | 6.66 |
April | 0.335212E+09 | 866.16 | 27-APR-15:02 | 27.20 | 17.22 | 94761089.74 | 69.34 | 27-APR-21:00 | 14.40 | 11.03 |
May | 0.457092E+09 | 841.07 | 04-MAY-15:02 | 24.32 | 14.81 | 0.100029E+09 | 74.90 | 15-MAY-21:10 | 13.72 | 10.88 |
June | 0.516810E+09 | 853.10 | 28-JUN-15:02 | 26.10 | 15.67 | 98889137.61 | 73.71 | 22-JUN-21:49 | 26.10 | 15.67 |
July | 0.585538E+09 | 874.25 | 24-JUL-18:02 | 28.72 | 17.86 | 0.103524E+09 | 75.55 | 26-JUL-21:10 | 20.68 | 16.76 |
August | 0.573224E+09 | 869.82 | 08-AUG-18:02 | 27.67 | 16.27 | 0.102595E+09 | 73.19 | 18-AUG-21:10 | 15.13 | 12.34 |
September | 0.419168E+09 | 823.42 | 11-SEP-15:02 | 23.30 | 15.89 | 97264936.07 | 71.57 | 13-SEP-21:49 | 18.30 | 14.68 |
October | 0.283296E+09 | 756.44 | 09-OCT-15:01 | 17.88 | 13.24 | 97049005.67 | 67.53 | 04-OCT-21:10 | 17.88 | 13.24 |
November | 0.153567E+09 | 722.03 | 04-NOV-15:02 | 20.92 | 15.94 | 93000780.84 | 56.69 | 03-NOV-21:10 | 20.92 | 15.94 |
December | 66098191.07 | 678.00 | 03-DEC-09:02 | 7.98 | 3.60 | 95327214.97 | 56.69 | 23-DEC-00:20 | 1.87 | 1.62 |
Annual Sum or Average | 0.377696E+10 | 0.116090E+10 | ||||||||
Minimum of Months | 65510877.46 | 635.00 | 6.70 | 3.60 | 86508064.36 | 56.69 | 1.87 | 1.62 | ||
Maximum of Months | 0.585538E+09 | 874.25 | 28.72 | 17.86 | 0.103524E+09 | 75.55 | 26.10 | 16.76 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13807225.04 | 837.80 | 20-JAN-16:02 | 5.40 | 3.78 | 93841286.41 | 56.69 | 03-JAN-04:19 | 5.40 | 3.78 |
February | 77174506.81 | 2480.02 | 27-FEB-16:02 | 19.32 | 12.38 | 86108082.06 | 56.69 | 28-FEB-00:20 | 12.03 | 10.57 |
March | 0.244902E+09 | 2630.29 | 25-MAR-08:62 | 4.78 | 0.26 | 96782652.75 | 56.69 | 18-MAR-23:10 | 4.78 | 0.26 |
April | 0.668013E+09 | 2826.15 | 01-APR-15:01 | 26.28 | 14.25 | 94914124.52 | 56.69 | 26-APR-21:40 | 13.73 | 10.41 |
May | 0.100398E+10 | 2844.32 | 14-MAY-18:02 | 21.83 | 11.88 | 98505550.13 | 56.69 | 07-MAY-00:20 | 21.83 | 11.88 |
June | 0.138508E+10 | 2808.22 | 28-JUN-18:02 | 25.40 | 16.48 | 95743235.06 | 56.69 | 28-JUN-21:00 | 18.30 | 14.03 |
July | 0.169376E+10 | 2858.93 | 24-JUL-18:02 | 28.72 | 17.86 | 98891772.14 | 56.69 | 24-JUL-23:10 | 18.95 | 15.23 |
August | 0.182931E+10 | 2911.41 | 09-AUG-18:02 | 27.55 | 18.54 | 99009770.86 | 56.70 | 24-AUG-22:40 | 20.77 | 16.72 |
September | 0.117317E+10 | 2767.41 | 22-SEP-15:02 | 23.58 | 17.29 | 95153170.89 | 56.69 | 13-SEP-21:00 | 23.58 | 17.29 |
October | 0.439017E+09 | 2669.11 | 04-OCT-18:02 | 17.52 | 10.01 | 97115778.01 | 56.69 | 04-OCT-21:00 | 16.10 | 10.03 |
November | 67758269.02 | 2606.99 | 04-NOV-15:02 | 20.92 | 15.94 | 91945962.20 | 56.69 | 04-NOV-23:10 | 13.30 | 12.93 |
December | 28386491.86 | 2005.44 | 05-DEC-16:01 | 6.10 | 4.53 | 94138672.94 | 56.69 | 08-DEC-04:19 | 4.63 | 3.82 |
Annual Sum or Average | 0.862435E+10 | 0.114215E+10 | ||||||||
Minimum of Months | 13807225.04 | 837.80 | 4.78 | 0.26 | 86108082.06 | 56.69 | 4.63 | 0.26 | ||
Maximum of Months | 0.182931E+10 | 2911.41 | 28.72 | 18.54 | 99009770.86 | 56.70 | 23.58 | 17.29 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7609044.98 | 674.03 | 25-JAN-19:05 | 7.20 | 6.09 | 93155537.99 | 56.69 | 31-JAN-04:19 | 4.60 | 4.02 |
February | 25200513.36 | 2181.37 | 12-FEB-09:01 | 1.97 | -1.0 | 85097689.62 | 56.69 | 07-FEB-04:19 | 1.97 | -1.0 |
March | 94840077.86 | 2395.24 | 25-MAR-08:62 | 4.78 | 0.26 | 95890525.81 | 56.69 | 19-MAR-01:19 | 4.78 | 0.26 |
April | 0.421257E+09 | 2660.64 | 27-APR-15:02 | 27.20 | 17.22 | 95194998.41 | 70.62 | 27-APR-21:40 | 15.33 | 11.23 |
May | 0.711276E+09 | 2862.92 | 06-MAY-08:51 | 19.40 | 15.38 | 0.100848E+09 | 75.41 | 15-MAY-21:10 | 13.72 | 10.88 |
June | 0.106003E+10 | 2769.54 | 28-JUN-08:51 | 18.90 | 13.39 | 0.100423E+09 | 73.98 | 21-JUN-21:40 | 18.90 | 13.39 |
July | 0.124404E+10 | 3201.66 | 24-JUL-08:32 | 23.17 | 16.50 | 0.105308E+09 | 76.95 | 24-JUL-21:19 | 22.07 | 16.28 |
August | 0.132369E+10 | 3151.19 | 13-AUG-08:32 | 20.43 | 15.63 | 0.104640E+09 | 76.91 | 08-AUG-21:10 | 20.43 | 15.63 |
September | 0.705119E+09 | 2919.33 | 13-SEP-08:51 | 18.30 | 15.25 | 98176218.81 | 73.92 | 13-SEP-21:40 | 18.30 | 14.73 |
October | 0.199237E+09 | 2376.66 | 06-OCT-15:01 | 17.30 | 12.22 | 96629391.45 | 66.46 | 04-OCT-21:10 | 17.30 | 12.22 |
November | 27980335.92 | 2062.59 | 04-NOV-15:02 | 20.92 | 15.94 | 91278280.29 | 56.69 | 19-NOV-02:20 | 10.00 | 9.58 |
December | 9308830.58 | 743.92 | 13-DEC-09:04 | 5.47 | 3.61 | 93323979.09 | 56.69 | 10-DEC-02:20 | 5.47 | 3.61 |
Annual Sum or Average | 0.582959E+10 | 0.115997E+10 | ||||||||
Minimum of Months | 7609044.98 | 674.03 | 1.97 | -1.0 | 85097689.62 | 56.69 | 1.97 | -1.0 | ||
Maximum of Months | 0.132369E+10 | 3201.66 | 27.20 | 17.22 | 0.105308E+09 | 76.95 | 22.07 | 16.28 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118619E+10 | 1230.56 | 11-JAN-22:00 | 11.10 | 10.49 | 0.119889E+10 | 713.63 | 11-JAN-22:49 | 9.68 | 8.60 |
February | 0.174935E+10 | 1463.06 | 27-FEB-19:10 | 15.73 | 11.89 | 0.108801E+10 | 748.34 | 27-FEB-23:10 | 12.20 | 10.40 |
March | 0.281853E+10 | 1548.27 | 18-MAR-17:20 | 19.03 | 9.50 | 0.122790E+10 | 759.69 | 02-MAR-22:49 | 19.03 | 9.50 |
April | 0.328586E+10 | 1853.12 | 27-APR-18:10 | 25.55 | 15.86 | 0.123197E+10 | 834.84 | 27-APR-21:49 | 14.87 | 11.14 |
May | 0.380440E+10 | 1923.81 | 06-MAY-10:33 | 20.93 | 16.16 | 0.135430E+10 | 860.12 | 15-MAY-21:00 | 12.80 | 11.20 |
June | 0.388566E+10 | 1994.65 | 28-JUN-18:10 | 25.40 | 16.48 | 0.135283E+10 | 880.36 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.426954E+10 | 2122.56 | 24-JUL-18:10 | 28.72 | 17.86 | 0.144853E+10 | 911.37 | 24-JUL-21:49 | 20.97 | 15.91 |
August | 0.434376E+10 | 2163.31 | 13-AUG-10:33 | 24.17 | 17.28 | 0.147114E+10 | 923.01 | 14-AUG-21:40 | 18.83 | 12.89 |
September | 0.385676E+10 | 2053.35 | 14-SEP-10:33 | 19.43 | 16.41 | 0.135022E+10 | 906.38 | 14-SEP-21:49 | 17.38 | 14.54 |
October | 0.320383E+10 | 1801.07 | 07-OCT-10:33 | 14.63 | 10.97 | 0.126815E+10 | 834.00 | 04-OCT-22:10 | 14.63 | 10.97 |
November | 0.193620E+10 | 1545.63 | 04-NOV-10:45 | 17.52 | 14.63 | 0.116595E+10 | 742.00 | 05-NOV-23:00 | 11.10 | 9.31 |
December | 0.139770E+10 | 1395.46 | 03-DEC-11:33 | 11.33 | 5.78 | 0.119918E+10 | 716.57 | 05-DEC-22:49 | 4.50 | 2.23 |
Annual Sum or Average | 0.357378E+11 | 0.153571E+11 | ||||||||
Minimum of Months | 0.118619E+10 | 1230.56 | 11.10 | 5.78 | 0.108801E+10 | 713.63 | 4.50 | 2.23 | ||
Maximum of Months | 0.434376E+10 | 2163.31 | 28.72 | 17.86 | 0.147114E+10 | 923.01 | 20.97 | 15.91 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9362071.17 | 2415.89 | 05-JAN-16:02 | 5.73 | 4.38 | 93243014.04 | 56.69 | 03-JAN-04:19 | 5.73 | 4.38 |
February | 71096737.49 | 2987.67 | 12-FEB-16:02 | 6.52 | 1.59 | 85514553.66 | 56.69 | 28-FEB-00:20 | 12.03 | 10.57 |
March | 0.231411E+09 | 3115.31 | 18-MAR-18:01 | 18.03 | 9.10 | 96161058.18 | 56.69 | 20-MAR-21:10 | 7.88 | 5.73 |
April | 0.630040E+09 | 3122.50 | 01-APR-15:01 | 26.28 | 14.25 | 94354982.26 | 56.69 | 26-APR-21:40 | 13.73 | 10.41 |
May | 0.112055E+10 | 3370.56 | 14-MAY-18:02 | 21.83 | 11.88 | 98315658.43 | 56.69 | 14-MAY-04:00 | 21.83 | 11.88 |
June | 0.131424E+10 | 3153.37 | 22-JUN-18:02 | 23.80 | 16.23 | 95492600.27 | 56.69 | 28-JUN-21:49 | 18.03 | 13.98 |
July | 0.197048E+10 | 3410.06 | 31-JUL-18:02 | 26.42 | 18.31 | 98744920.74 | 56.70 | 27-JUL-21:49 | 26.42 | 18.31 |
August | 0.185492E+10 | 3424.04 | 10-AUG-18:02 | 30.57 | 19.31 | 98801021.81 | 56.70 | 24-AUG-22:40 | 20.77 | 16.72 |
September | 0.123769E+10 | 3126.42 | 13-SEP-18:02 | 22.43 | 16.15 | 95002601.43 | 56.70 | 11-SEP-21:19 | 22.43 | 16.15 |
October | 0.383670E+09 | 3084.45 | 04-OCT-18:02 | 17.52 | 10.01 | 96630060.51 | 56.69 | 04-OCT-21:19 | 14.63 | 9.40 |
November | 56180914.86 | 2980.28 | 04-NOV-15:02 | 20.92 | 15.94 | 91416060.12 | 56.69 | 05-NOV-01:19 | 12.97 | 12.22 |
December | 14174427.47 | 2594.60 | 10-DEC-16:02 | 9.72 | 8.43 | 93637320.44 | 56.69 | 26-DEC-04:19 | -0.9 | -0.9 |
Annual Sum or Average | 0.889382E+10 | 0.113731E+10 | ||||||||
Minimum of Months | 9362071.17 | 2415.89 | 5.73 | 1.59 | 85514553.66 | 56.69 | -0.9 | -0.9 | ||
Maximum of Months | 0.197048E+10 | 3424.04 | 30.57 | 19.31 | 98801021.81 | 56.70 | 26.42 | 18.31 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3249007.06 | 754.68 | 05-JAN-16:03 | 5.73 | 4.38 | 92687351.73 | 56.69 | 17-JAN-04:19 | 1.70 | -0.1 |
February | 20553930.48 | 2614.39 | 27-FEB-16:02 | 19.32 | 12.38 | 84628031.61 | 56.69 | 14-FEB-04:19 | 19.32 | 12.38 |
March | 87661709.36 | 2761.06 | 18-MAR-15:02 | 20.10 | 10.35 | 95396692.93 | 60.40 | 14-MAR-18:10 | 20.10 | 10.35 |
April | 0.372333E+09 | 3148.22 | 25-APR-17:41 | 14.60 | 8.96 | 95206874.07 | 75.19 | 26-APR-21:19 | 14.67 | 10.66 |
May | 0.741746E+09 | 3196.32 | 15-MAY-16:32 | 24.23 | 12.96 | 0.104346E+09 | 90.13 | 31-MAY-18:10 | 20.40 | 14.89 |
June | 0.957979E+09 | 3274.36 | 22-JUN-16:21 | 24.40 | 15.53 | 0.103339E+09 | 93.22 | 19-JUN-21:10 | 24.40 | 15.53 |
July | 0.144511E+10 | 3540.40 | 25-JUL-16:51 | 25.60 | 18.36 | 0.111107E+09 | 96.59 | 21-JUL-21:10 | 25.60 | 18.36 |
August | 0.134591E+10 | 3144.99 | 06-AUG-21:51 | 17.90 | 14.41 | 0.106164E+09 | 83.39 | 11-AUG-18:10 | 20.88 | 15.38 |
September | 0.679855E+09 | 3451.36 | 22-SEP-16:11 | 24.43 | 17.44 | 0.101432E+09 | 86.39 | 08-SEP-18:10 | 24.43 | 17.44 |
October | 0.143817E+09 | 2682.93 | 02-OCT-15:02 | 17.20 | 10.69 | 96441041.17 | 70.70 | 04-OCT-21:10 | 14.27 | 9.23 |
November | 20280753.06 | 2525.16 | 04-NOV-15:02 | 20.92 | 15.94 | 90809495.54 | 56.69 | 02-NOV-23:19 | 20.92 | 15.94 |
December | 4666490.93 | 772.26 | 28-DEC-16:05 | 11.02 | 9.74 | 92861045.87 | 56.69 | 22-DEC-04:19 | 11.02 | 9.74 |
Annual Sum or Average | 0.582316E+10 | 0.117442E+10 | ||||||||
Minimum of Months | 3249007.06 | 754.68 | 5.73 | 4.38 | 84628031.61 | 56.69 | 1.70 | -0.1 | ||
Maximum of Months | 0.144511E+10 | 3540.40 | 25.60 | 18.36 | 0.111107E+09 | 96.59 | 25.60 | 18.36 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 70285245.31 | 1649.75 | 05-JAN-16:02 | 5.73 | 4.38 | 95241347.48 | 56.69 | 11-JAN-22:10 | 10.82 | 10.11 |
February | 0.230510E+09 | 1800.16 | 26-FEB-16:02 | 14.40 | 10.25 | 87172720.61 | 56.69 | 27-FEB-22:10 | 12.20 | 10.11 |
March | 0.399958E+09 | 1916.24 | 18-MAR-18:01 | 18.03 | 9.10 | 97446024.36 | 56.69 | 18-MAR-23:19 | 10.20 | 8.02 |
April | 0.595320E+09 | 2001.73 | 27-APR-18:02 | 25.55 | 15.86 | 95018780.48 | 56.69 | 13-APR-21:19 | 25.55 | 15.86 |
May | 0.739328E+09 | 2002.98 | 14-MAY-18:02 | 21.83 | 11.88 | 98492870.65 | 56.69 | 06-MAY-23:10 | 21.83 | 11.88 |
June | 0.822012E+09 | 1980.37 | 28-JUN-18:02 | 25.40 | 16.48 | 95560388.91 | 56.69 | 08-JUN-21:19 | 25.40 | 16.48 |
July | 0.108142E+10 | 2046.19 | 30-JUL-18:02 | 26.32 | 17.50 | 98725069.38 | 56.70 | 24-JUL-21:00 | 26.32 | 17.50 |
August | 0.118232E+10 | 2060.33 | 24-AUG-15:02 | 29.62 | 19.18 | 98821449.60 | 56.70 | 23-AUG-21:00 | 29.62 | 19.18 |
September | 0.988672E+09 | 2043.95 | 12-SEP-15:02 | 24.40 | 16.76 | 95280349.90 | 56.70 | 13-SEP-21:00 | 18.30 | 14.64 |
October | 0.587361E+09 | 1900.82 | 04-OCT-18:02 | 17.52 | 10.01 | 97750430.78 | 56.69 | 25-OCT-21:49 | 14.22 | 12.69 |
November | 0.169968E+09 | 1940.71 | 04-NOV-15:02 | 20.92 | 15.94 | 93045721.56 | 56.69 | 04-NOV-23:19 | 13.30 | 12.93 |
December | 0.132902E+09 | 1757.26 | 10-DEC-16:02 | 9.72 | 8.43 | 95404831.33 | 56.69 | 04-DEC-00:20 | 9.72 | 8.43 |
Annual Sum or Average | 0.700006E+10 | 0.114796E+10 | ||||||||
Minimum of Months | 70285245.31 | 1649.75 | 5.73 | 4.38 | 87172720.61 | 56.69 | 9.72 | 8.02 | ||
Maximum of Months | 0.118232E+10 | 2060.33 | 29.62 | 19.18 | 98821449.60 | 56.70 | 29.62 | 19.18 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.312482E+11 | 17531.72 | 11-JAN-22:50 | 9.68 | 8.60 | 0.187575E+11 | 11347.91 | 12-JAN-00:20 | 8.30 | 7.82 |
February | 0.290123E+11 | 18585.48 | 27-FEB-23:00 | 12.20 | 10.35 | 0.170413E+11 | 11347.79 | 18-FEB-00:20 | 12.20 | 10.35 |
March | 0.338575E+11 | 18461.38 | 10-MAR-23:00 | 11.10 | 10.84 | 0.190906E+11 | 11347.89 | 31-MAR-23:19 | 8.20 | 7.64 |
April | 0.345500E+11 | 20338.57 | 27-APR-21:10 | 16.73 | 11.41 | 0.185310E+11 | 11348.87 | 27-APR-22:10 | 14.40 | 11.00 |
May | 0.377123E+11 | 20713.94 | 05-MAY-21:53 | 17.80 | 12.72 | 0.192455E+11 | 11349.23 | 15-MAY-21:30 | 13.35 | 11.02 |
June | 0.380503E+11 | 21173.73 | 28-JUN-21:52 | 18.30 | 14.03 | 0.186884E+11 | 11349.21 | 27-JUN-22:10 | 18.30 | 14.03 |
July | 0.404630E+11 | 21892.99 | 24-JUL-21:10 | 22.43 | 16.40 | 0.192568E+11 | 11349.21 | 21-JUL-22:10 | 22.43 | 16.40 |
August | 0.404555E+11 | 21881.78 | 10-AUG-21:52 | 22.50 | 15.63 | 0.193259E+11 | 11349.11 | 11-AUG-22:10 | 15.85 | 13.74 |
September | 0.366635E+11 | 20585.90 | 12-SEP-21:52 | 18.30 | 14.27 | 0.185943E+11 | 11349.11 | 11-SEP-22:10 | 18.30 | 14.27 |
October | 0.348361E+11 | 19375.14 | 04-OCT-22:00 | 16.10 | 10.03 | 0.190665E+11 | 11348.59 | 04-OCT-21:30 | 16.10 | 10.03 |
November | 0.318021E+11 | 18480.15 | 06-NOV-23:00 | 15.60 | 14.58 | 0.182862E+11 | 11347.98 | 27-NOV-00:20 | 8.30 | 6.77 |
December | 0.314217E+11 | 17314.31 | 29-DEC-23:00 | 8.90 | 7.76 | 0.188035E+11 | 11347.88 | 26-DEC-00:20 | 8.90 | 7.76 |
Annual Sum or Average | 0.420073E+12 | 0.224687E+12 | ||||||||
Minimum of Months | 0.290123E+11 | 17314.31 | 8.90 | 7.76 | 0.170413E+11 | 11347.79 | 8.20 | 6.77 | ||
Maximum of Months | 0.404630E+11 | 21892.99 | 22.50 | 16.40 | 0.193259E+11 | 11349.23 | 22.43 | 16.40 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.348986E+11 | 19593.61 | 11-JAN-22:30 | 10.25 | 9.35 | 0.189808E+11 | 11347.94 | 12-JAN-00:20 | 8.30 | 7.82 |
February | 0.323532E+11 | 20453.18 | 27-FEB-23:00 | 12.20 | 10.35 | 0.172217E+11 | 11347.83 | 18-FEB-00:20 | 12.20 | 10.35 |
March | 0.376388E+11 | 20417.85 | 08-MAR-23:00 | 13.90 | 9.29 | 0.192495E+11 | 11347.90 | 31-MAR-23:19 | 8.20 | 7.64 |
April | 0.382063E+11 | 21899.68 | 27-APR-21:20 | 16.27 | 11.36 | 0.186375E+11 | 11351.76 | 27-APR-21:19 | 16.27 | 11.36 |
May | 0.413529E+11 | 22260.73 | 05-MAY-21:20 | 18.53 | 12.90 | 0.193049E+11 | 11368.77 | 05-MAY-21:19 | 18.53 | 12.90 |
June | 0.414361E+11 | 22579.28 | 28-JUN-21:20 | 17.23 | 13.81 | 0.187288E+11 | 11370.38 | 09-JUN-21:19 | 17.23 | 13.81 |
July | 0.437637E+11 | 23198.95 | 24-JUL-21:20 | 22.07 | 16.28 | 0.192880E+11 | 11369.30 | 21-JUL-21:19 | 22.07 | 16.28 |
August | 0.436944E+11 | 23114.44 | 10-AUG-21:05 | 22.92 | 16.74 | 0.193610E+11 | 11369.59 | 22-AUG-21:19 | 19.43 | 13.92 |
September | 0.400089E+11 | 21957.52 | 12-SEP-21:52 | 18.30 | 14.27 | 0.186557E+11 | 11350.49 | 12-SEP-21:19 | 18.30 | 14.27 |
October | 0.385620E+11 | 20961.62 | 04-OCT-22:00 | 16.10 | 10.03 | 0.191982E+11 | 11348.61 | 04-OCT-21:30 | 16.10 | 10.03 |
November | 0.354394E+11 | 20424.18 | 06-NOV-23:00 | 15.60 | 14.58 | 0.184701E+11 | 11348.02 | 27-NOV-00:20 | 8.30 | 6.77 |
December | 0.350995E+11 | 19363.09 | 29-DEC-23:00 | 8.90 | 7.76 | 0.190161E+11 | 11347.94 | 26-DEC-00:20 | 8.90 | 7.76 |
Annual Sum or Average | 0.462454E+12 | 0.226112E+12 | ||||||||
Minimum of Months | 0.323532E+11 | 19363.09 | 8.90 | 7.76 | 0.172217E+11 | 11347.83 | 8.20 | 6.77 | ||
Maximum of Months | 0.437637E+11 | 23198.95 | 22.92 | 16.74 | 0.193610E+11 | 11370.38 | 22.07 | 16.28 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.468089E+11 | 25139.84 | 30-JAN-11:35 | 8.13 | 6.36 | 0.187912E+11 | 11319.71 | 28-JAN-18:19 | 8.13 | 6.36 |
February | 0.432565E+11 | 26254.16 | 27-FEB-11:50 | 16.23 | 10.66 | 0.169780E+11 | 11319.69 | 04-FEB-18:19 | 16.23 | 10.66 |
March | 0.493828E+11 | 27419.82 | 14-MAR-10:50 | 11.42 | 8.58 | 0.188126E+11 | 11319.63 | 11-MAR-18:19 | 11.42 | 8.58 |
April | 0.495379E+11 | 28752.21 | 27-APR-10:35 | 20.37 | 13.53 | 0.182091E+11 | 11319.65 | 29-APR-17:19 | 20.57 | 14.52 |
May | 0.523904E+11 | 28869.83 | 14-MAY-10:33 | 20.03 | 12.68 | 0.188243E+11 | 11319.65 | 13-MAY-17:19 | 20.03 | 12.68 |
June | 0.519515E+11 | 29174.89 | 10-JUN-10:33 | 20.20 | 14.80 | 0.182282E+11 | 11319.61 | 24-JUN-17:19 | 19.23 | 11.83 |
July | 0.543338E+11 | 29647.80 | 24-JUL-10:40 | 25.93 | 17.48 | 0.188338E+11 | 11319.69 | 29-JUL-17:19 | 23.17 | 15.48 |
August | 0.545739E+11 | 29744.25 | 13-AUG-10:33 | 24.17 | 17.28 | 0.188438E+11 | 11319.68 | 12-AUG-17:19 | 24.17 | 17.28 |
September | 0.510642E+11 | 29080.28 | 10-SEP-10:33 | 18.33 | 13.89 | 0.182224E+11 | 11319.66 | 23-SEP-17:19 | 21.67 | 16.65 |
October | 0.502020E+11 | 27882.76 | 07-OCT-10:33 | 14.63 | 10.97 | 0.188143E+11 | 11319.61 | 28-OCT-17:19 | 10.73 | 7.68 |
November | 0.466449E+11 | 27370.66 | 04-NOV-10:45 | 17.52 | 14.63 | 0.181949E+11 | 11319.70 | 25-NOV-18:19 | 7.40 | 6.48 |
December | 0.470740E+11 | 25632.50 | 03-DEC-11:50 | 11.52 | 5.93 | 0.187928E+11 | 11319.71 | 16-DEC-18:19 | 7.20 | 6.61 |
Annual Sum or Average | 0.597221E+12 | 0.221545E+12 | ||||||||
Minimum of Months | 0.432565E+11 | 25139.84 | 8.13 | 5.93 | 0.169780E+11 | 11319.61 | 7.20 | 6.36 | ||
Maximum of Months | 0.545739E+11 | 29744.25 | 25.93 | 17.48 | 0.188438E+11 | 11319.71 | 24.17 | 17.28 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.279920E+10 | 2800.40 | 20-JAN-11:50 | 5.60 | 3.57 | 0.126887E+10 | 752.91 | 11-JAN-22:40 | 5.60 | 3.57 |
February | 0.389419E+10 | 3469.26 | 27-FEB-19:10 | 15.73 | 11.89 | 0.115202E+10 | 804.88 | 27-FEB-22:40 | 12.20 | 10.25 |
March | 0.627551E+10 | 3723.73 | 14-MAR-17:13 | 16.33 | 10.62 | 0.129586E+10 | 818.58 | 14-MAR-21:40 | 12.40 | 8.44 |
April | 0.739977E+10 | 4492.63 | 27-APR-17:12 | 26.10 | 16.52 | 0.129950E+10 | 904.12 | 27-APR-21:30 | 15.80 | 11.30 |
May | 0.861810E+10 | 4584.14 | 06-MAY-10:33 | 20.93 | 16.16 | 0.141334E+10 | 912.37 | 15-MAY-21:30 | 13.35 | 11.02 |
June | 0.892297E+10 | 4769.97 | 28-JUN-18:10 | 25.40 | 16.48 | 0.142565E+10 | 944.42 | 28-JUN-21:30 | 17.50 | 13.87 |
July | 0.978360E+10 | 5043.54 | 24-JUL-18:10 | 28.72 | 17.86 | 0.152427E+10 | 980.23 | 24-JUL-21:30 | 21.70 | 16.16 |
August | 0.987602E+10 | 5775.54 | 10-AUG-15:03 | 30.37 | 18.88 | 0.153815E+10 | 993.97 | 10-AUG-21:30 | 22.75 | 16.30 |
September | 0.862693E+10 | 4729.82 | 14-SEP-10:33 | 19.43 | 16.41 | 0.139847E+10 | 944.83 | 14-SEP-21:40 | 17.57 | 14.62 |
October | 0.716768E+10 | 4193.21 | 04-OCT-10:33 | 18.33 | 11.02 | 0.132213E+10 | 871.40 | 04-OCT-22:10 | 15.73 | 10.00 |
November | 0.460252E+10 | 3718.96 | 04-NOV-10:50 | 17.52 | 14.63 | 0.123493E+10 | 792.18 | 05-NOV-23:19 | 11.10 | 9.49 |
December | 0.315053E+10 | 3299.97 | 03-DEC-11:33 | 11.33 | 5.78 | 0.126936E+10 | 745.60 | 19-DEC-05:10 | 3.80 | 2.28 |
Annual Sum or Average | 0.811170E+11 | 0.161426E+11 | ||||||||
Minimum of Months | 0.279920E+10 | 2800.40 | 5.60 | 3.57 | 0.115202E+10 | 745.60 | 3.80 | 2.28 | ||
Maximum of Months | 0.987602E+10 | 5775.54 | 30.37 | 18.88 | 0.153815E+10 | 993.97 | 22.75 | 16.30 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 70535479.68 | 444.74 | 16-JAN-17:00 | 1.70 |
February | 28686237.66 | 561.74 | 19-FEB-06:00 | -5.6 |
March | 70987.90 | 40.10 | 05-MAR-18:00 | 5.60 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 9433379.76 | 268.44 | 30-NOV-16:00 | 4.40 |
December | 79622808.19 | 600.15 | 26-DEC-10:10 | 0.02 |
Annual Sum or Average | 0.188349E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 79622808.19 | 600.15 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 965073.28 | 68.05 | 16-JAN-16:00 | 2.20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 195244.45 | 22.30 | 26-DEC-14:40 | 1.87 |
Annual Sum or Average | 1160317.73 | |||
Minimum of Months | 0.00 | 0.00 | 1.87 | |
Maximum of Months | 965073.28 | 68.05 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13316795.36 | 151.74 | 16-JAN-17:00 | 1.70 |
February | 5850751.80 | 96.47 | 19-FEB-06:00 | -5.6 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 8119844.28 | 139.70 | 26-DEC-14:20 | 1.53 |
Annual Sum or Average | 27287391.44 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 13316795.36 | 151.74 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.792198E+09 | 1886.90 | 15-JAN-09:01 | -2.5 |
February | 0.448840E+09 | 1872.90 | 18-FEB-19:01 | -0.8 |
March | 0.195000E+09 | 1824.38 | 05-MAR-16:01 | 6.02 |
April | 59178799.54 | 1743.88 | 18-APR-08:62 | 4.50 |
May | 8368922.55 | 1115.45 | 26-MAY-15:04 | 13.30 |
June | 2344102.55 | 1091.55 | 05-JUN-15:04 | 13.80 |
July | 1665480.47 | 962.19 | 31-JUL-08:04 | 21.28 |
August | 2168285.05 | 1009.22 | 01-AUG-08:04 | 11.85 |
September | 4803387.84 | 868.20 | 18-SEP-15:04 | 16.10 |
October | 86572745.65 | 1695.36 | 31-OCT-08:62 | 11.70 |
November | 0.415229E+09 | 1865.64 | 30-NOV-16:01 | 4.50 |
December | 0.723592E+09 | 1879.14 | 26-DEC-09:02 | -0.9 |
Annual Sum or Average | 0.273996E+10 | |||
Minimum of Months | 1665480.47 | 868.20 | -2.5 | |
Maximum of Months | 0.792198E+09 | 1886.90 | 21.28 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.934597E+09 | 1877.67 | 15-JAN-09:01 | -2.5 |
February | 0.595423E+09 | 1880.84 | 19-FEB-09:01 | -3.1 |
March | 0.281123E+09 | 1804.06 | 05-MAR-16:01 | 6.02 |
April | 82327969.52 | 1754.74 | 19-APR-08:62 | 5.87 |
May | 9050083.31 | 983.29 | 01-MAY-15:04 | 14.40 |
June | 2413397.74 | 909.93 | 07-JUN-08:03 | 11.88 |
July | 1528261.40 | 820.95 | 19-JUL-08:05 | 15.97 |
August | 1199029.85 | 724.70 | 16-AUG-08:05 | 15.87 |
September | 5561319.08 | 940.87 | 27-SEP-15:03 | 13.30 |
October | 0.134556E+09 | 1704.93 | 30-OCT-08:62 | 7.30 |
November | 0.520491E+09 | 1837.36 | 30-NOV-16:01 | 4.50 |
December | 0.869961E+09 | 1858.71 | 22-DEC-09:01 | 0.78 |
Annual Sum or Average | 0.343823E+10 | |||
Minimum of Months | 1199029.85 | 724.70 | -3.1 | |
Maximum of Months | 0.934597E+09 | 1880.84 | 15.97 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 41868767.79 | 509.66 | 15-JAN-16:02 | 1.60 |
February | 22635689.47 | 506.91 | 13-FEB-16:01 | 0.60 |
March | 1056527.51 | 324.81 | 14-MAR-15:05 | 16.28 |
April | 338503.14 | 259.14 | 13-APR-15:06 | 17.80 |
May | 150860.36 | 188.27 | 21-MAY-15:07 | 16.10 |
June | 67569.30 | 224.15 | 12-JUN-15:07 | 16.78 |
July | 79590.51 | 270.70 | 04-JUL-15:07 | 17.02 |
August | 39947.43 | 108.35 | 02-AUG-15:07 | 18.37 |
September | 178798.02 | 218.29 | 28-SEP-08:05 | 10.28 |
October | 724970.32 | 248.50 | 03-OCT-15:06 | 18.80 |
November | 4650644.31 | 499.61 | 30-NOV-16:01 | 4.50 |
December | 25080495.89 | 510.09 | 26-DEC-16:02 | 3.27 |
Annual Sum or Average | 96872364.05 | |||
Minimum of Months | 39947.43 | 108.35 | 0.60 | |
Maximum of Months | 41868767.79 | 510.09 | 18.80 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.797555E+09 | 1847.67 | 15-JAN-19:01 | 0.73 |
February | 0.450736E+09 | 1841.20 | 18-FEB-19:01 | -0.8 |
March | 0.188530E+09 | 1793.26 | 05-MAR-16:01 | 6.02 |
April | 55091851.42 | 1718.39 | 18-APR-08:62 | 4.50 |
May | 10576748.58 | 1037.30 | 01-MAY-15:04 | 14.40 |
June | 1432416.51 | 909.56 | 06-JUN-18:04 | 10.78 |
July | 1184246.46 | 787.21 | 25-JUL-08:05 | 15.18 |
August | 1199253.85 | 1039.59 | 20-AUG-18:04 | 18.83 |
September | 6856446.38 | 1056.02 | 03-SEP-18:04 | 17.62 |
October | 89201377.77 | 1683.95 | 31-OCT-08:62 | 11.70 |
November | 0.418565E+09 | 1836.76 | 30-NOV-16:01 | 4.50 |
December | 0.730544E+09 | 1851.86 | 26-DEC-09:02 | -0.9 |
Annual Sum or Average | 0.275147E+10 | |||
Minimum of Months | 1184246.46 | 787.21 | -0.9 | |
Maximum of Months | 0.797555E+09 | 1851.86 | 18.83 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.941860E+09 | 1832.32 | 08-JAN-09:01 | -1.7 |
February | 0.594917E+09 | 1831.47 | 19-FEB-19:01 | -1.1 |
March | 0.265439E+09 | 1773.21 | 05-MAR-16:01 | 6.02 |
April | 75667327.29 | 1697.31 | 18-APR-08:62 | 4.50 |
May | 12062017.65 | 927.75 | 01-MAY-15:04 | 14.40 |
June | 1272297.40 | 871.88 | 06-JUN-18:04 | 10.78 |
July | 679219.50 | 753.41 | 03-JUL-08:05 | 13.48 |
August | 718695.35 | 736.39 | 18-AUG-21:24 | 15.40 |
September | 7709623.98 | 869.77 | 18-SEP-15:04 | 16.10 |
October | 0.136590E+09 | 1685.20 | 30-OCT-08:62 | 7.30 |
November | 0.517965E+09 | 1808.95 | 30-NOV-16:01 | 4.50 |
December | 0.871852E+09 | 1825.20 | 26-DEC-09:02 | -0.9 |
Annual Sum or Average | 0.342673E+10 | |||
Minimum of Months | 679219.50 | 736.39 | -1.7 | |
Maximum of Months | 0.941860E+09 | 1832.32 | 16.10 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38400050.10 | 490.71 | 16-JAN-16:00 | 2.20 |
February | 6226592.68 | 279.52 | 17-FEB-10:07 | 0.78 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 7362193.78 | 299.71 | 30-NOV-14:50 | 4.90 |
December | 59291945.44 | 620.98 | 26-DEC-15:00 | 2.20 |
Annual Sum or Average | 0.111281E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.78 | |
Maximum of Months | 59291945.44 | 620.98 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123178E+10 | 2301.82 | 15-JAN-09:01 | -2.5 |
February | 0.749636E+09 | 2284.92 | 19-FEB-09:01 | -3.1 |
March | 0.400174E+09 | 2227.94 | 05-MAR-16:01 | 6.02 |
April | 0.150342E+09 | 2141.73 | 19-APR-08:62 | 5.87 |
May | 39237990.15 | 1430.91 | 18-MAY-08:63 | 6.28 |
June | 6017528.94 | 1061.23 | 05-JUN-15:04 | 13.80 |
July | 1378434.47 | 983.94 | 31-JUL-08:04 | 21.28 |
August | 2068724.61 | 955.52 | 25-AUG-08:04 | 19.83 |
September | 17041001.11 | 1008.09 | 06-SEP-18:04 | 14.90 |
October | 0.212242E+09 | 2087.59 | 30-OCT-08:62 | 7.30 |
November | 0.717343E+09 | 2261.99 | 30-NOV-16:01 | 4.50 |
December | 0.113985E+10 | 2277.86 | 22-DEC-09:01 | 0.78 |
Annual Sum or Average | 0.466711E+10 | |||
Minimum of Months | 1378434.47 | 955.52 | -3.1 | |
Maximum of Months | 0.123178E+10 | 2301.82 | 21.28 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141030E+10 | 2274.58 | 07-JAN-09:01 | -3.1 |
February | 0.942104E+09 | 2274.97 | 19-FEB-09:01 | -3.1 |
March | 0.529011E+09 | 2191.22 | 05-MAR-16:01 | 6.02 |
April | 0.195103E+09 | 2126.32 | 19-APR-08:62 | 5.87 |
May | 41544823.64 | 1365.26 | 18-MAY-08:63 | 6.28 |
June | 6498019.84 | 815.18 | 05-JUN-15:04 | 13.80 |
July | 1112103.98 | 726.97 | 19-JUL-08:05 | 15.97 |
August | 1343944.94 | 825.68 | 23-AUG-08:53 | 21.20 |
September | 19775483.63 | 1560.19 | 28-SEP-08:62 | 10.28 |
October | 0.302788E+09 | 2074.88 | 16-OCT-08:62 | 8.07 |
November | 0.852637E+09 | 2223.16 | 13-NOV-09:01 | 1.70 |
December | 0.132567E+10 | 2245.72 | 22-DEC-09:01 | 0.78 |
Annual Sum or Average | 0.562790E+10 | |||
Minimum of Months | 1112103.98 | 726.97 | -3.1 | |
Maximum of Months | 0.141030E+10 | 2274.97 | 21.20 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.322894E+09 | 1223.63 | 18-JAN-16:01 | 3.80 |
February | 0.158970E+09 | 1210.86 | 17-FEB-09:01 | 1.02 |
March | 49972546.75 | 1179.79 | 05-MAR-16:01 | 6.02 |
April | 17801994.39 | 850.38 | 18-APR-08:62 | 4.50 |
May | 4468170.18 | 612.60 | 08-MAY-18:04 | 17.93 |
June | 1630453.20 | 660.23 | 29-JUN-15:04 | 17.30 |
July | 1079660.57 | 703.33 | 16-JUL-15:04 | 17.80 |
August | 1289248.62 | 587.28 | 20-AUG-18:04 | 18.83 |
September | 2542722.38 | 685.69 | 18-SEP-15:04 | 16.10 |
October | 15578832.20 | 632.84 | 19-OCT-15:04 | 13.53 |
November | 0.138392E+09 | 1225.14 | 30-NOV-16:01 | 4.50 |
December | 0.304976E+09 | 1226.91 | 26-DEC-16:02 | 3.27 |
Annual Sum or Average | 0.101960E+10 | |||
Minimum of Months | 1079660.57 | 587.28 | 1.02 | |
Maximum of Months | 0.322894E+09 | 1226.91 | 18.83 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26015243.39 | 449.13 | 16-JAN-06:00 | -2.2 |
February | 16485053.70 | 786.15 | 19-FEB-06:00 | -5.6 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
December | 17056138.12 | 621.01 | 26-DEC-10:05 | 0.02 |
Annual Sum or Average | 59556435.21 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 26015243.39 | 786.15 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.866285E+10 | 8344.11 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.782177E+10 | 8344.11 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.868956E+10 | 8344.11 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.836914E+10 | 8344.11 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.867788E+10 | 8344.11 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.840753E+10 | 8344.11 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.863949E+10 | 8344.11 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.869290E+10 | 8344.11 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.837248E+10 | 8344.11 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.865952E+10 | 8344.11 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.840085E+10 | 8344.11 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.863949E+10 | 8344.11 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.102033E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.782177E+10 | 8344.11 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.869290E+10 | 8344.11 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.478695E+09 | 461.08 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.432218E+09 | 461.08 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.480171E+09 | 461.08 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.462465E+09 | 461.08 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.479525E+09 | 461.08 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.464586E+09 | 461.08 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.477404E+09 | 461.08 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.480355E+09 | 461.08 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.462650E+09 | 461.08 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.478511E+09 | 461.08 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.464217E+09 | 461.08 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.477404E+09 | 461.08 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.563820E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.432218E+09 | 461.08 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.480355E+09 | 461.08 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.554331E+09 | 533.93 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.500510E+09 | 533.93 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.556040E+09 | 533.93 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.535537E+09 | 533.93 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.555292E+09 | 533.93 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.537993E+09 | 533.93 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.552836E+09 | 533.93 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.556253E+09 | 533.93 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.535750E+09 | 533.93 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.554117E+09 | 533.93 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.537566E+09 | 533.93 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.552836E+09 | 533.93 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.652906E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.500510E+09 | 533.93 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.556253E+09 | 533.93 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.639281E+09 | 615.76 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.577212E+09 | 615.76 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.641251E+09 | 615.76 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.617606E+09 | 615.76 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.640389E+09 | 615.76 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.620439E+09 | 615.76 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.637557E+09 | 615.76 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.641498E+09 | 615.76 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.617853E+09 | 615.76 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.639035E+09 | 615.76 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.619946E+09 | 615.76 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.637557E+09 | 615.76 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.752962E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.577212E+09 | 615.76 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.641498E+09 | 615.76 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142601E+09 | 137.35 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.128756E+09 | 137.35 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.143041E+09 | 137.35 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.137766E+09 | 137.35 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.142848E+09 | 137.35 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.138398E+09 | 137.35 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.142217E+09 | 137.35 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.143096E+09 | 137.35 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.137821E+09 | 137.35 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.142546E+09 | 137.35 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.138288E+09 | 137.35 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.142217E+09 | 137.35 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.167960E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.128756E+09 | 137.35 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.143096E+09 | 137.35 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.374392E+09 | 360.62 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.338042E+09 | 360.62 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.375546E+09 | 360.62 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.361698E+09 | 360.62 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.375041E+09 | 360.62 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.363357E+09 | 360.62 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.373382E+09 | 360.62 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.375690E+09 | 360.62 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.361842E+09 | 360.62 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.374247E+09 | 360.62 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.363068E+09 | 360.62 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.373382E+09 | 360.62 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.440969E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.338042E+09 | 360.62 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.375690E+09 | 360.62 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.117180E+10 | 1416.11 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.996669E+09 | 1416.11 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.102775E+10 | 1416.11 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.888175E+09 | 1416.11 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.843594E+09 | 1416.11 | 01-MAY-19:19 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.743916E+09 | 1416.11 | 01-JUN-19:00 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.794898E+09 | 1416.11 | 10-JUL-19:00 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.865787E+09 | 1416.11 | 01-AUG-19:40 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.963503E+09 | 1416.11 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.108756E+10 | 1416.11 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.111032E+10 | 1416.11 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.117600E+10 | 1416.11 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.116700E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.743916E+09 | 1416.11 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.117600E+10 | 1416.11 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.960419E+10 | 9580.84 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.859549E+10 | 9580.84 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.946711E+10 | 9580.84 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.900410E+10 | 9580.84 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.924895E+10 | 9580.84 | 01-MAY-19:19 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.888669E+10 | 9580.84 | 01-JUN-19:00 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.917496E+10 | 9580.84 | 10-JUL-19:00 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.929582E+10 | 9580.84 | 01-AUG-19:40 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.908762E+10 | 9580.84 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.950145E+10 | 9580.84 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.928292E+10 | 9580.84 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.959005E+10 | 9580.84 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.110739E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.859549E+10 | 9580.84 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.960419E+10 | 9580.84 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118113E+09 | 106.87 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.106667E+09 | 106.87 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.117174E+09 | 106.87 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.114438E+09 | 106.87 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.117643E+09 | 106.87 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113531E+09 | 106.87 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.118566E+09 | 106.87 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.117174E+09 | 106.87 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.114469E+09 | 106.87 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.118097E+09 | 106.87 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113984E+09 | 106.87 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.118582E+09 | 106.87 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.138844E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.106667E+09 | 106.87 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.118582E+09 | 106.87 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118099E+09 | 106.85 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.106655E+09 | 106.85 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.117160E+09 | 106.85 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.114425E+09 | 106.85 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.117629E+09 | 106.85 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113517E+09 | 106.85 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.118553E+09 | 106.85 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.117160E+09 | 106.85 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.114456E+09 | 106.85 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.118083E+09 | 106.85 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113971E+09 | 106.85 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.118568E+09 | 106.85 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.138828E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.106655E+09 | 106.85 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.118568E+09 | 106.85 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 74229181.22 | 67.16 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 67036196.95 | 67.16 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 73639243.64 | 67.16 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 71920171.51 | 67.16 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 73934212.43 | 67.16 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 71349576.37 | 67.16 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 74514478.79 | 67.16 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 73639243.64 | 67.16 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 71939513.95 | 67.16 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 74219510.00 | 67.16 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 71634873.94 | 67.16 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 74524150.01 | 67.16 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.872580E+09 | 0.300992E+10 | ||||
Minimum of Months | 67036196.95 | 67.16 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 74524150.01 | 67.16 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 74249479.06 | 67.18 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 67054527.88 | 67.18 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 73659380.16 | 67.18 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 71939837.95 | 67.18 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 73954429.61 | 67.18 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 71369086.78 | 67.18 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 74534854.64 | 67.18 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 73659380.16 | 67.18 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 71959185.68 | 67.18 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 74239805.19 | 67.18 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 71654462.37 | 67.18 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 74544528.51 | 67.18 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.872819E+09 | 0.301074E+10 | ||||
Minimum of Months | 67054527.88 | 67.18 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 74544528.51 | 67.18 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118113E+09 | 106.87 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.106667E+09 | 106.87 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.117174E+09 | 106.87 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.114438E+09 | 106.87 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.117643E+09 | 106.87 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113531E+09 | 106.87 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.118566E+09 | 106.87 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.117174E+09 | 106.87 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.114469E+09 | 106.87 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.118097E+09 | 106.87 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113984E+09 | 106.87 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.118582E+09 | 106.87 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.138844E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.106667E+09 | 106.87 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.118582E+09 | 106.87 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118099E+09 | 106.85 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.106655E+09 | 106.85 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.117160E+09 | 106.85 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.114425E+09 | 106.85 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.117629E+09 | 106.85 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113517E+09 | 106.85 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.118553E+09 | 106.85 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.117160E+09 | 106.85 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.114456E+09 | 106.85 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.118083E+09 | 106.85 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113971E+09 | 106.85 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.118568E+09 | 106.85 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.138828E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.106655E+09 | 106.85 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.118568E+09 | 106.85 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.108388E+10 | 1044.00 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.978647E+09 | 1044.00 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.108722E+10 | 1044.00 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.104713E+10 | 1044.00 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.108576E+10 | 1044.00 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.105194E+10 | 1044.00 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.108096E+10 | 1044.00 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.108764E+10 | 1044.00 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.104755E+10 | 1044.00 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.108346E+10 | 1044.00 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.105110E+10 | 1044.00 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.108096E+10 | 1044.00 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.127663E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.978647E+09 | 1044.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108764E+10 | 1044.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118113E+09 | 106.87 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.106667E+09 | 106.87 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.117174E+09 | 106.87 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.114438E+09 | 106.87 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.117643E+09 | 106.87 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113531E+09 | 106.87 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.118566E+09 | 106.87 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.117174E+09 | 106.87 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.114469E+09 | 106.87 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.118097E+09 | 106.87 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113984E+09 | 106.87 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.118582E+09 | 106.87 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.138844E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.106667E+09 | 106.87 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.118582E+09 | 106.87 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118099E+09 | 106.85 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.106655E+09 | 106.85 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.117160E+09 | 106.85 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.114425E+09 | 106.85 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.117629E+09 | 106.85 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113517E+09 | 106.85 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.118553E+09 | 106.85 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.117160E+09 | 106.85 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.114456E+09 | 106.85 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.118083E+09 | 106.85 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113971E+09 | 106.85 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.118568E+09 | 106.85 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.138828E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.106655E+09 | 106.85 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.118568E+09 | 106.85 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 74249479.06 | 67.18 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 67054527.88 | 67.18 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 73659380.16 | 67.18 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 71939837.95 | 67.18 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 73954429.61 | 67.18 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 71369086.78 | 67.18 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 74534854.64 | 67.18 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 73659380.16 | 67.18 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 71959185.68 | 67.18 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 74239805.19 | 67.18 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 71654462.37 | 67.18 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 74544528.51 | 67.18 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.872819E+09 | 0.301074E+10 | ||||
Minimum of Months | 67054527.88 | 67.18 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 74544528.51 | 67.18 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.236593E+10 | 2486.81 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.207034E+10 | 2486.81 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.221587E+10 | 2486.81 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.202316E+10 | 2486.81 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.201280E+10 | 2486.81 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.187212E+10 | 2486.81 | 01-JUN-19:00 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.194402E+10 | 2486.81 | 10-JUL-19:00 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.203749E+10 | 2486.81 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.210191E+10 | 2486.81 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.227334E+10 | 2486.81 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.226909E+10 | 2486.81 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.237424E+10 | 2486.81 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.255603E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.187212E+10 | 2486.81 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.237424E+10 | 2486.81 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.236593E+10 | 2486.81 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.207034E+10 | 2486.81 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.221587E+10 | 2486.81 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.202316E+10 | 2486.81 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.201280E+10 | 2486.81 | 01-MAY-19:19 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.187212E+10 | 2486.81 | 01-JUN-19:00 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.194402E+10 | 2486.81 | 10-JUL-19:00 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.203749E+10 | 2486.81 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.210191E+10 | 2486.81 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.227334E+10 | 2486.81 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.226909E+10 | 2486.81 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.237424E+10 | 2486.81 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.255603E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.187212E+10 | 2486.81 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.237424E+10 | 2486.81 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101925E+10 | 981.75 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.920291E+09 | 981.75 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.102239E+10 | 981.75 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.984694E+09 | 981.75 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.102102E+10 | 981.75 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.989210E+09 | 981.75 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.101650E+10 | 981.75 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.102279E+10 | 981.75 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.985086E+09 | 981.75 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.101886E+10 | 981.75 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.988424E+09 | 981.75 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.101650E+10 | 981.75 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.120050E+11 | 0.424019E+12 | ||||
Minimum of Months | 0.920291E+09 | 981.75 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.102279E+10 | 981.75 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.114712E+10 | 1104.91 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.103575E+10 | 1104.91 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.115066E+10 | 1104.91 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.110823E+10 | 1104.91 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.114911E+10 | 1104.91 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.111331E+10 | 1104.91 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.114403E+10 | 1104.91 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.115110E+10 | 1104.91 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.110867E+10 | 1104.91 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.114668E+10 | 1104.91 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.111243E+10 | 1104.91 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.114403E+10 | 1104.91 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.135111E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.103575E+10 | 1104.91 | 0.00 | 0.00 | |
Maximum of Months | 0.115110E+10 | 1104.91 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.866285E+10 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.782177E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.868956E+10 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.836914E+10 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.867788E+10 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.840753E+10 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.863949E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.869290E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.837248E+10 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.865952E+10 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.840085E+10 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.863949E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.102033E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.782177E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.869290E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.478695E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137912E+09 |
February | 0.179968E+10 | 0.432218E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114316E+09 |
March | 0.199990E+10 | 0.480171E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106006E+09 |
April | 0.192973E+10 | 0.462465E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 417459.91 | 83308537.55 |
May | 0.199475E+10 | 0.479525E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 195793.35 | 68514527.07 |
June | 0.193394E+10 | 0.464586E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 639961.76 | 45907376.36 |
July | 0.199054E+10 | 0.477404E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2463177.45 | 35166389.02 |
August | 0.199896E+10 | 0.480355E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4474185.24 | 29322220.48 |
September | 0.192879E+10 | 0.462650E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63199.97 | 51539088.69 |
October | 0.199148E+10 | 0.478511E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80559572.18 |
November | 0.192552E+10 | 0.464217E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103851E+09 |
December | 0.199054E+10 | 0.477404E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130210E+09 |
Annual Sum or Average | 0.234744E+11 | 0.563820E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8253777.68 | 0.986612E+09 |
Minimum of Months | 0.179968E+10 | 0.432218E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29322220.48 |
Maximum of Months | 0.199990E+10 | 0.480355E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4474185.24 | 0.137912E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.554331E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54913618.27 |
February | 0.208403E+10 | 0.500510E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46049427.83 |
March | 0.231589E+10 | 0.556040E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43858392.37 |
April | 0.223463E+10 | 0.535537E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 195537.52 | 35594854.75 |
May | 0.230993E+10 | 0.555292E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71453.50 | 30578289.22 |
June | 0.223950E+10 | 0.537993E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 184251.13 | 22008778.54 |
July | 0.230505E+10 | 0.552836E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 864054.21 | 17832085.96 |
August | 0.231480E+10 | 0.556253E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1727601.57 | 15341014.49 |
September | 0.223354E+10 | 0.535750E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42579.21 | 23732191.89 |
October | 0.230614E+10 | 0.554117E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34577576.14 |
November | 0.222975E+10 | 0.537566E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42614331.04 |
December | 0.230505E+10 | 0.552836E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52160770.47 |
Annual Sum or Average | 0.271834E+11 | 0.652906E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3085477.14 | 0.419261E+09 |
Minimum of Months | 0.208403E+10 | 0.500510E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15341014.49 |
Maximum of Months | 0.231589E+10 | 0.556253E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1727601.57 | 54913618.27 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.639281E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125877E+09 |
February | 0.440737E+09 | 0.577212E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104244E+09 |
March | 0.489771E+09 | 0.641251E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98004829.05 |
April | 0.472586E+09 | 0.617606E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 618042.02 | 79600447.64 |
May | 0.488511E+09 | 0.640389E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 252403.92 | 69332205.22 |
June | 0.473617E+09 | 0.620439E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 500077.24 | 50488761.62 |
July | 0.487480E+09 | 0.637557E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2091288.12 | 41071824.47 |
August | 0.489542E+09 | 0.641498E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4172313.41 | 35601718.61 |
September | 0.472357E+09 | 0.617853E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 205437.90 | 53851635.27 |
October | 0.487709E+09 | 0.639035E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77762365.25 |
November | 0.471555E+09 | 0.619946E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96442912.22 |
December | 0.487480E+09 | 0.637557E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118684E+09 |
Annual Sum or Average | 0.574883E+10 | 0.752962E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7839562.61 | 0.950962E+09 |
Minimum of Months | 0.440737E+09 | 0.577212E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35601718.61 |
Maximum of Months | 0.489771E+09 | 0.641498E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4172313.41 | 0.125877E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.142601E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72416022.26 |
February | 0.339028E+09 | 0.128756E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59775353.88 |
March | 0.376747E+09 | 0.143041E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55658187.05 |
April | 0.363528E+09 | 0.137766E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 360473.26 | 45025761.92 |
May | 0.375778E+09 | 0.142848E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 150861.62 | 39099565.60 |
June | 0.364321E+09 | 0.138398E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 304920.73 | 28341467.34 |
July | 0.374985E+09 | 0.142217E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1247076.38 | 22945298.50 |
August | 0.376571E+09 | 0.143096E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2473842.95 | 19818092.08 |
September | 0.363352E+09 | 0.137821E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 122405.11 | 30211831.32 |
October | 0.375161E+09 | 0.142546E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43848218.68 |
November | 0.362735E+09 | 0.138288E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54998028.08 |
December | 0.374985E+09 | 0.142217E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68189940.07 |
Annual Sum or Average | 0.442217E+10 | 0.167960E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4659580.06 | 0.540328E+09 |
Minimum of Months | 0.339028E+09 | 0.128756E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19818092.08 |
Maximum of Months | 0.376747E+09 | 0.143096E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2473842.95 | 72416022.26 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.374392E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189582E+09 |
February | 0.139600E+10 | 0.338042E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157465E+09 |
March | 0.155131E+10 | 0.375546E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148157E+09 |
April | 0.149688E+10 | 0.361698E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 650039.51 | 0.118536E+09 |
May | 0.154732E+10 | 0.375041E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 440444.47 | 99997692.42 |
June | 0.150015E+10 | 0.363357E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 797457.78 | 71020998.96 |
July | 0.154405E+10 | 0.373382E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 3460578.18 | 55281805.19 |
August | 0.155059E+10 | 0.375690E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 6622432.66 | 47189642.03 |
September | 0.149615E+10 | 0.361842E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 521926.42 | 75879311.55 |
October | 0.154478E+10 | 0.374247E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115375E+09 |
November | 0.149361E+10 | 0.363068E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146480E+09 |
December | 0.154405E+10 | 0.373382E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179654E+09 |
Annual Sum or Average | 0.182090E+11 | 0.440969E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 12492879.02 | 0.140462E+10 |
Minimum of Months | 0.139600E+10 | 0.338042E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47189642.03 |
Maximum of Months | 0.155131E+10 | 0.375690E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 6622432.66 | 0.189582E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.117180E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310726E+09 |
February | 0.236489E+11 | 0.996669E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260789E+09 |
March | 0.262800E+11 | 0.102775E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246464E+09 |
April | 0.253579E+11 | 0.888175E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 817283.61 | 0.197529E+09 |
May | 0.262123E+11 | 0.843594E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 352527.36 | 0.166382E+09 |
June | 0.254132E+11 | 0.743916E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1134659.36 | 0.117129E+09 |
July | 0.261570E+11 | 0.794898E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5142608.79 | 93065923.97 |
August | 0.262677E+11 | 0.865787E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9412324.91 | 79580985.47 |
September | 0.253456E+11 | 0.963503E+09 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 106699.71 | 0.128959E+09 |
October | 0.261693E+11 | 0.108756E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192160E+09 |
November | 0.253025E+11 | 0.111032E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238177E+09 |
December | 0.261570E+11 | 0.117600E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294467E+09 |
Annual Sum or Average | 0.308468E+12 | 0.116700E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16966103.73 | 0.232543E+10 |
Minimum of Months | 0.236489E+11 | 0.743916E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79580985.47 |
Maximum of Months | 0.262800E+11 | 0.117600E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9412324.91 | 0.310726E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.960419E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921684E+09 |
February | 0.702046E+11 | 0.859549E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.774833E+09 |
March | 0.780153E+11 | 0.946711E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739111E+09 |
April | 0.752779E+11 | 0.900410E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2862618.50 | 0.599550E+09 |
May | 0.778146E+11 | 0.924895E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1024056.70 | 0.514311E+09 |
June | 0.754422E+11 | 0.888669E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2789679.28 | 0.372629E+09 |
July | 0.776503E+11 | 0.917496E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13955978.71 | 0.299730E+09 |
August | 0.779788E+11 | 0.929582E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27368104.45 | 0.258616E+09 |
September | 0.752414E+11 | 0.908762E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 505151.00 | 0.400378E+09 |
October | 0.776868E+11 | 0.950145E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585392E+09 |
November | 0.751137E+11 | 0.928292E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718388E+09 |
December | 0.776503E+11 | 0.959005E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876185E+09 |
Annual Sum or Average | 0.915726E+12 | 0.110739E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 48505588.64 | 0.706081E+10 |
Minimum of Months | 0.702046E+11 | 0.859549E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258616E+09 |
Maximum of Months | 0.780153E+11 | 0.960419E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27368104.45 | 0.921684E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118113E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79112779.75 |
February | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66149440.14 |
March | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61944612.28 |
April | 0.293479E+09 | 0.114438E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 331553.88 | 49437406.67 |
May | 0.303504E+09 | 0.117643E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 193860.35 | 41149304.83 |
June | 0.293842E+09 | 0.113531E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 456919.36 | 28135269.81 |
July | 0.303141E+09 | 0.118566E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1817239.54 | 20881515.34 |
August | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3446556.12 | 17254560.55 |
September | 0.293479E+09 | 0.114469E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 263144.76 | 30003775.93 |
October | 0.303322E+09 | 0.118097E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 564.64 | 47074388.75 |
November | 0.293661E+09 | 0.113984E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60104149.67 |
December | 0.303141E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74755193.60 |
Annual Sum or Average | 0.357224E+10 | 0.138844E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6509838.65 | 0.576002E+09 |
Minimum of Months | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17254560.55 |
Maximum of Months | 0.303685E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3446556.12 | 79112779.75 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118099E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78362366.54 |
February | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65216207.96 |
March | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61097370.45 |
April | 0.293479E+09 | 0.114425E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 321287.86 | 49325845.31 |
May | 0.303504E+09 | 0.117629E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81920.31 | 42840445.08 |
June | 0.293842E+09 | 0.113517E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 300550.09 | 30386869.33 |
July | 0.303141E+09 | 0.118553E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1480781.96 | 24358846.32 |
August | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3108110.07 | 19453071.62 |
September | 0.293479E+09 | 0.114456E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 104299.26 | 31849777.71 |
October | 0.303322E+09 | 0.118083E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 278.91 | 46566709.13 |
November | 0.293661E+09 | 0.113971E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59468629.52 |
December | 0.303141E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73933643.61 |
Annual Sum or Average | 0.357224E+10 | 0.138828E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5397228.46 | 0.582860E+09 |
Minimum of Months | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19453071.62 |
Maximum of Months | 0.303685E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3108110.07 | 78362366.54 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 74229181.22 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22857081.52 |
February | 0.00 | 67036196.95 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22117886.84 |
March | 0.00 | 73639243.64 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23653828.58 |
April | 0.00 | 71920171.51 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1762.32 | 20026172.97 |
May | 0.00 | 73934212.43 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17895662.73 |
June | 0.00 | 71349576.37 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13947878.99 |
July | 0.00 | 74514478.79 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46836.69 | 11752251.07 |
August | 0.00 | 73639243.64 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 167630.53 | 10376466.04 |
September | 0.00 | 71939513.95 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14597374.68 |
October | 0.00 | 74219510.00 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19747282.94 |
November | 0.00 | 71634873.94 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21890338.95 |
December | 0.00 | 74524150.01 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23237398.18 |
Annual Sum or Average | 0.00 | 0.872580E+09 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 216229.54 | 0.222100E+09 |
Minimum of Months | 0.00 | 67036196.95 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10376466.04 |
Maximum of Months | 0.00 | 74524150.01 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 167630.53 | 23653828.58 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 74249479.06 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22393354.61 |
February | 0.273974E+09 | 67054527.88 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18530191.95 |
March | 0.303685E+09 | 73659380.16 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17283586.85 |
April | 0.293479E+09 | 71939837.95 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98767.11 | 13760598.37 |
May | 0.303504E+09 | 73954429.61 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30745.07 | 11581441.29 |
June | 0.293842E+09 | 71369086.78 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93487.89 | 8124957.03 |
July | 0.303141E+09 | 74534854.64 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 437577.72 | 6208163.54 |
August | 0.303685E+09 | 73659380.16 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 904275.27 | 5105869.46 |
September | 0.293479E+09 | 71959185.68 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44823.28 | 8509300.12 |
October | 0.303322E+09 | 74239805.19 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74.23 | 13101033.84 |
November | 0.293661E+09 | 71654462.37 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16997623.30 |
December | 0.303141E+09 | 74544528.51 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21111657.17 |
Annual Sum or Average | 0.357224E+10 | 0.872819E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1609750.57 | 0.162708E+09 |
Minimum of Months | 0.273974E+09 | 67054527.88 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5105869.46 |
Maximum of Months | 0.303685E+09 | 74544528.51 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 904275.27 | 22393354.61 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118113E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79050439.77 |
February | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66225270.65 |
March | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62220014.66 |
April | 0.293479E+09 | 0.114438E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 335834.95 | 49782740.76 |
May | 0.303504E+09 | 0.117643E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 198476.10 | 41228072.99 |
June | 0.293842E+09 | 0.113531E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 462712.57 | 28296713.64 |
July | 0.303141E+09 | 0.118566E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1832924.71 | 20955430.29 |
August | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3456286.13 | 17357563.32 |
September | 0.293479E+09 | 0.114469E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 269229.87 | 30019455.03 |
October | 0.303322E+09 | 0.118097E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1017.54 | 47209380.00 |
November | 0.293661E+09 | 0.113984E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60090722.15 |
December | 0.303141E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74685219.05 |
Annual Sum or Average | 0.357224E+10 | 0.138844E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6556481.88 | 0.577121E+09 |
Minimum of Months | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17357563.32 |
Maximum of Months | 0.303685E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3456286.13 | 79050439.77 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118099E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78295172.50 |
February | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65196735.23 |
March | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61358721.34 |
April | 0.293479E+09 | 0.114425E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 323931.20 | 49670652.57 |
May | 0.303504E+09 | 0.117629E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89021.56 | 42013812.74 |
June | 0.293842E+09 | 0.113517E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 314856.44 | 29971085.06 |
July | 0.303141E+09 | 0.118553E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1497172.12 | 23201869.30 |
August | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3096366.72 | 19401288.30 |
September | 0.293479E+09 | 0.114456E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 125115.60 | 30992119.49 |
October | 0.303322E+09 | 0.118083E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 320.64 | 46637818.58 |
November | 0.293661E+09 | 0.113971E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59400476.94 |
December | 0.303141E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73831019.81 |
Annual Sum or Average | 0.357224E+10 | 0.138828E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5446784.28 | 0.579971E+09 |
Minimum of Months | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19401288.30 |
Maximum of Months | 0.303685E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3096366.72 | 78295172.50 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.108388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96793449.67 |
February | 0.348285E+10 | 0.978647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79754174.77 |
March | 0.387034E+10 | 0.108722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74166189.46 |
April | 0.373454E+10 | 0.104713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446880.81 | 59794623.49 |
May | 0.386038E+10 | 0.108576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157963.48 | 52312937.60 |
June | 0.374269E+10 | 0.105194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355443.50 | 37701637.42 |
July | 0.385223E+10 | 0.108096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1529085.21 | 30595722.35 |
August | 0.386853E+10 | 0.108764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3102522.34 | 26453111.38 |
September | 0.373273E+10 | 0.104755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97362.28 | 40284586.83 |
October | 0.385404E+10 | 0.108346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57490568.71 |
November | 0.372639E+10 | 0.105110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72861617.65 |
December | 0.385223E+10 | 0.108096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91150498.93 |
Annual Sum or Average | 0.454292E+11 | 0.127663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5689257.61 | 0.719359E+09 |
Minimum of Months | 0.348285E+10 | 0.978647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26453111.38 |
Maximum of Months | 0.387034E+10 | 0.108764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3102522.34 | 96793449.67 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118113E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78775522.00 |
February | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65939220.13 |
March | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61873285.59 |
April | 0.293479E+09 | 0.114438E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 323556.95 | 49533506.95 |
May | 0.303504E+09 | 0.117643E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 180260.21 | 41318895.17 |
June | 0.293842E+09 | 0.113531E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 439909.80 | 28335528.58 |
July | 0.303141E+09 | 0.118566E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1773919.30 | 21070167.02 |
August | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3373519.23 | 17396527.92 |
September | 0.293479E+09 | 0.114469E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 251119.93 | 30118823.08 |
October | 0.303322E+09 | 0.118097E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.65 | 47046112.80 |
November | 0.293661E+09 | 0.113984E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59888412.41 |
December | 0.303141E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74540001.55 |
Annual Sum or Average | 0.357224E+10 | 0.138844E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6342332.07 | 0.575836E+09 |
Minimum of Months | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17396527.92 |
Maximum of Months | 0.303685E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3373519.23 | 78775522.00 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118099E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78160233.34 |
February | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64994645.70 |
March | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60977261.40 |
April | 0.293479E+09 | 0.114425E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 312305.14 | 49487686.86 |
May | 0.303504E+09 | 0.117629E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75834.49 | 43388014.38 |
June | 0.293842E+09 | 0.113517E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 287194.98 | 30984466.59 |
July | 0.303141E+09 | 0.118553E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1445604.14 | 25095976.27 |
August | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3041444.83 | 19768290.51 |
September | 0.293479E+09 | 0.114456E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98657.05 | 32322515.52 |
October | 0.303322E+09 | 0.118083E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 245.18 | 46479416.38 |
November | 0.293661E+09 | 0.113971E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59224900.39 |
December | 0.303141E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73726863.39 |
Annual Sum or Average | 0.357224E+10 | 0.138828E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5261285.82 | 0.584610E+09 |
Minimum of Months | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19768290.51 |
Maximum of Months | 0.303685E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3041444.83 | 78160233.34 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 74249479.06 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41283163.07 |
February | 0.273974E+09 | 67054527.88 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34498527.40 |
March | 0.303685E+09 | 73659380.16 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32253734.09 |
April | 0.293479E+09 | 71939837.95 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 166497.64 | 25644103.88 |
May | 0.303504E+09 | 73954429.61 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 96457.87 | 21224817.88 |
June | 0.293842E+09 | 71369086.78 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 228586.50 | 14535888.94 |
July | 0.303141E+09 | 74534854.64 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 916251.35 | 10779868.60 |
August | 0.303685E+09 | 73659380.16 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1734237.56 | 8920101.79 |
September | 0.293479E+09 | 71959185.68 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 131535.95 | 15540466.00 |
October | 0.303322E+09 | 74239805.19 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24554849.58 |
November | 0.293661E+09 | 71654462.37 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31413464.01 |
December | 0.303141E+09 | 74544528.51 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38969989.59 |
Annual Sum or Average | 0.357224E+10 | 0.872819E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3273566.87 | 0.299619E+09 |
Minimum of Months | 0.273974E+09 | 67054527.88 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8920101.79 |
Maximum of Months | 0.303685E+09 | 74544528.51 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1734237.56 | 41283163.07 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.236593E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224532E+09 |
February | 0.415303E+11 | 0.207034E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187652E+09 |
March | 0.461508E+11 | 0.221587E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179196E+09 |
April | 0.445315E+11 | 0.202316E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 381255.56 | 0.145940E+09 |
May | 0.460320E+11 | 0.201280E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21256.55 | 0.126133E+09 |
June | 0.446286E+11 | 0.187212E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 192793.24 | 92743905.62 |
July | 0.459349E+11 | 0.194402E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2076932.54 | 74273295.90 |
August | 0.461292E+11 | 0.203749E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4694435.20 | 63773068.96 |
September | 0.445099E+11 | 0.210191E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29952.62 | 97686476.99 |
October | 0.459565E+11 | 0.227334E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142039E+09 |
November | 0.444343E+11 | 0.226909E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175941E+09 |
December | 0.459349E+11 | 0.237424E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213493E+09 |
Annual Sum or Average | 0.541708E+12 | 0.255603E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 7396625.71 | 0.172340E+10 |
Minimum of Months | 0.415303E+11 | 0.187212E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63773068.96 |
Maximum of Months | 0.461508E+11 | 0.237424E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4694435.20 | 0.224532E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.236593E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226987E+09 |
February | 0.415303E+11 | 0.207034E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189667E+09 |
March | 0.461508E+11 | 0.221587E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181114E+09 |
April | 0.445315E+11 | 0.202316E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 362204.90 | 0.147318E+09 |
May | 0.460320E+11 | 0.201280E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20960.56 | 0.127028E+09 |
June | 0.446286E+11 | 0.187212E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 191729.07 | 93389449.62 |
July | 0.459349E+11 | 0.194402E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2043442.35 | 74737854.99 |
August | 0.461292E+11 | 0.203749E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4602144.46 | 64235581.28 |
September | 0.445099E+11 | 0.210191E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28977.30 | 98572945.80 |
October | 0.459565E+11 | 0.227334E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143665E+09 |
November | 0.444343E+11 | 0.226909E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178034E+09 |
December | 0.459349E+11 | 0.237424E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215851E+09 |
Annual Sum or Average | 0.541708E+12 | 0.255603E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 7249458.64 | 0.174060E+10 |
Minimum of Months | 0.415303E+11 | 0.187212E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64235581.28 |
Maximum of Months | 0.461508E+11 | 0.237424E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4602144.46 | 0.226987E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.101925E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203590E+09 |
February | 0.369574E+10 | 0.920291E+09 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169654E+09 |
March | 0.410691E+10 | 0.102239E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161391E+09 |
April | 0.396281E+10 | 0.984694E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 320953.09 | 0.130670E+09 |
May | 0.409635E+10 | 0.102102E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 19252.83 | 0.112289E+09 |
June | 0.397146E+10 | 0.989210E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 173564.49 | 82434399.60 |
July | 0.408770E+10 | 0.101650E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 1816424.94 | 65699190.15 |
August | 0.410499E+10 | 0.102279E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 4056204.02 | 56526047.12 |
September | 0.396089E+10 | 0.985086E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 26596.67 | 87324352.68 |
October | 0.408962E+10 | 0.101886E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127859E+09 |
November | 0.395417E+10 | 0.988424E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159182E+09 |
December | 0.408770E+10 | 0.101650E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193417E+09 |
Annual Sum or Average | 0.482060E+11 | 0.120050E+11 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 6412996.04 | 0.155004E+10 |
Minimum of Months | 0.369574E+10 | 0.920291E+09 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56526047.12 |
Maximum of Months | 0.410691E+10 | 0.102279E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 4056204.02 | 0.203590E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.114712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171920E+09 |
February | 0.368610E+10 | 0.103575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141889E+09 |
March | 0.409620E+10 | 0.115066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132071E+09 |
April | 0.395248E+10 | 0.110823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 589340.12 | 0.106517E+09 |
May | 0.408566E+10 | 0.114911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109876.95 | 92390410.20 |
June | 0.396110E+10 | 0.111331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334029.66 | 67317514.00 |
July | 0.407704E+10 | 0.114403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2133612.13 | 54322785.28 |
August | 0.409429E+10 | 0.115110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4614074.02 | 45888734.44 |
September | 0.395056E+10 | 0.110867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65817.73 | 70329839.53 |
October | 0.407896E+10 | 0.114668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101435E+09 |
November | 0.394385E+10 | 0.111243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129723E+09 |
December | 0.407704E+10 | 0.114403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161992E+09 |
Annual Sum or Average | 0.480803E+11 | 0.135111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7846750.61 | 0.127580E+10 |
Minimum of Months | 0.368610E+10 | 0.103575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45888734.44 |
Maximum of Months | 0.409620E+10 | 0.115110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4614074.02 | 0.171920E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 8344.11 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 8344.11 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 8344.11 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 8344.11 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 8344.11 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 8344.11 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 8344.11 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 8344.11 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 8344.11 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 8344.11 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 8344.11 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 8344.11 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 8344.11 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 8344.11 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 461.08 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 80.83 | 15-JAN-08:00 |
February | 1169.53 | 01-FEB-00:10 | 461.08 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 84.76 | 19-FEB-06:00 |
March | 1169.53 | 01-MAR-00:10 | 461.08 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 68.88 | 01-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 461.08 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 01-APR-17:00 | 60.98 | 19-APR-05:00 |
May | 1169.53 | 01-MAY-00:10 | 461.08 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.44 | 05-MAY-16:00 | 51.55 | 11-MAY-03:20 |
June | 1169.53 | 01-JUN-00:10 | 461.08 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.11 | 28-JUN-17:00 | 38.75 | 15-JUN-04:00 |
July | 1169.53 | 01-JUL-00:10 | 461.08 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 24-JUL-15:00 | 30.12 | 07-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 461.08 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.45 | 10-AUG-17:00 | 30.49 | 01-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 461.08 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.38 | 14-SEP-17:00 | 42.48 | 27-SEP-05:00 |
October | 1169.53 | 01-OCT-23:10 | 461.08 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 47.57 | 13-OCT-05:00 |
November | 1169.53 | 01-NOV-00:10 | 461.08 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 66.24 | 11-NOV-08:00 |
December | 1169.53 | 01-DEC-00:10 | 461.08 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 72.82 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 461.08 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.12 | |||||
Maximum of Months | 1169.53 | 461.08 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 24.45 | 84.76 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 533.93 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 31.89 | 15-JAN-08:00 |
February | 1354.32 | 01-FEB-00:10 | 533.93 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 32.92 | 19-FEB-05:00 |
March | 1354.32 | 01-MAR-00:10 | 533.93 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 28.33 | 01-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 533.93 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 | 01-APR-16:00 | 25.05 | 19-APR-05:00 |
May | 1354.32 | 01-MAY-00:10 | 533.93 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.48 | 05-MAY-16:00 | 21.91 | 11-MAY-03:00 |
June | 1354.32 | 01-JUN-00:10 | 533.93 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.26 | 28-JUN-17:00 | 16.92 | 15-JUN-03:00 |
July | 1354.32 | 01-JUL-00:10 | 533.93 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.10 | 24-JUL-15:00 | 14.35 | 07-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 533.93 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.20 | 29-AUG-16:00 | 14.49 | 01-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 533.93 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.30 | 22-SEP-16:00 | 18.26 | 27-SEP-05:00 |
October | 1354.32 | 01-OCT-23:10 | 533.93 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 20.57 | 13-OCT-05:00 |
November | 1354.32 | 01-NOV-00:10 | 533.93 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 26.87 | 11-NOV-08:00 |
December | 1354.32 | 01-DEC-00:10 | 533.93 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 28.69 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 533.93 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 | |||||
Maximum of Months | 1354.32 | 533.93 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 9.20 | 32.92 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 615.76 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 73.74 | 15-JAN-08:00 |
February | 286.42 | 01-FEB-00:10 | 615.76 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 77.32 | 19-FEB-06:00 |
March | 286.42 | 01-MAR-00:10 | 615.76 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 64.79 | 01-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 615.76 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.34 | 01-APR-16:00 | 56.43 | 19-APR-05:00 |
May | 286.42 | 01-MAY-00:10 | 615.76 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.65 | 05-MAY-16:00 | 50.22 | 11-MAY-03:00 |
June | 286.42 | 01-JUN-00:10 | 615.76 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.47 | 28-JUN-17:00 | 38.64 | 15-JUN-03:00 |
July | 286.42 | 01-JUL-00:10 | 615.76 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.31 | 24-JUL-15:00 | 32.53 | 19-JUL-05:00 |
August | 286.42 | 01-AUG-00:10 | 615.76 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.93 | 29-AUG-16:00 | 33.40 | 01-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 615.76 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.86 | 22-SEP-16:00 | 41.54 | 27-SEP-05:00 |
October | 286.42 | 01-OCT-23:10 | 615.76 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 46.18 | 13-OCT-05:00 |
November | 286.42 | 01-NOV-00:10 | 615.76 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 61.07 | 11-NOV-08:00 |
December | 286.42 | 01-DEC-00:10 | 615.76 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 66.43 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.53 | |||||
Maximum of Months | 286.42 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 21.93 | 77.32 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 137.35 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 42.54 | 15-JAN-08:00 |
February | 220.32 | 01-FEB-00:10 | 137.35 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 44.61 | 19-FEB-06:00 |
March | 220.32 | 01-MAR-00:10 | 137.35 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 36.77 | 01-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 137.35 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.78 | 01-APR-16:00 | 32.16 | 19-APR-05:00 |
May | 220.32 | 01-MAY-00:10 | 137.35 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.86 | 05-MAY-16:00 | 28.60 | 11-MAY-03:00 |
June | 220.32 | 01-JUN-00:10 | 137.35 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.06 | 28-JUN-17:00 | 21.99 | 15-JUN-03:00 |
July | 220.32 | 01-JUL-00:10 | 137.35 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.11 | 24-JUL-15:00 | 18.56 | 19-JUL-05:00 |
August | 220.32 | 01-AUG-00:10 | 137.35 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.62 | 29-AUG-16:00 | 18.91 | 01-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 137.35 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 | 22-SEP-16:00 | 23.61 | 27-SEP-05:00 |
October | 220.32 | 01-OCT-23:10 | 137.35 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 26.32 | 13-OCT-05:00 |
November | 220.32 | 01-NOV-00:10 | 137.35 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 34.86 | 11-NOV-07:40 |
December | 220.32 | 01-DEC-00:10 | 137.35 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 38.33 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 137.35 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 | |||||
Maximum of Months | 220.32 | 137.35 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 12.62 | 44.61 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 360.62 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 112.73 | 15-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 360.62 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 114.87 | 19-FEB-08:00 |
March | 907.20 | 01-MAR-00:10 | 360.62 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 97.58 | 01-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 360.62 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 19.46 | 01-APR-16:00 | 85.83 | 19-APR-05:40 |
May | 907.20 | 01-MAY-00:10 | 360.62 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 11.47 | 05-MAY-16:00 | 71.61 | 11-MAY-05:20 |
June | 907.20 | 01-JUN-00:10 | 360.62 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 18.69 | 28-JUN-17:00 | 56.10 | 01-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 360.62 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 29.09 | 24-JUL-15:08 | 46.69 | 07-JUL-05:10 |
August | 907.20 | 01-AUG-00:10 | 360.62 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 36.11 | 10-AUG-17:00 | 47.84 | 01-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 360.62 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 12.28 | 14-SEP-17:00 | 62.04 | 27-SEP-05:10 |
October | 907.20 | 01-OCT-23:10 | 360.62 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 69.01 | 16-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 360.62 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 94.26 | 11-NOV-08:00 |
December | 907.20 | 01-DEC-00:10 | 360.62 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 102.06 | 26-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 46.69 | ||||||
Maximum of Months | 907.20 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 36.11 | 114.87 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1416.11 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 178.69 | 15-JAN-08:00 |
February | 15368.40 | 01-FEB-00:10 | 1416.11 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 187.39 | 19-FEB-06:00 |
March | 15368.40 | 01-MAR-00:10 | 1416.11 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 155.46 | 01-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 1416.11 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.95 | 01-APR-16:00 | 141.93 | 19-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 1416.11 | 01-MAY-19:19 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.93 | 05-MAY-16:00 | 123.04 | 11-MAY-03:00 |
June | 15368.40 | 01-JUN-00:10 | 1416.11 | 01-JUN-19:00 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 | 28-JUN-17:00 | 94.88 | 15-JUN-03:00 |
July | 15368.40 | 01-JUL-00:10 | 1416.11 | 10-JUL-19:00 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.93 | 24-JUL-15:00 | 80.08 | 19-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 1416.11 | 01-AUG-19:40 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.54 | 10-AUG-17:00 | 80.07 | 01-AUG-05:00 |
September | 15368.40 | 01-SEP-00:10 | 1416.11 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.81 | 14-SEP-17:00 | 102.25 | 27-SEP-05:00 |
October | 15368.40 | 01-OCT-23:10 | 1416.11 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 116.52 | 13-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1416.11 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 148.97 | 11-NOV-08:00 |
December | 15368.40 | 01-DEC-00:10 | 1416.11 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 161.01 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1416.11 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.07 | |||||
Maximum of Months | 15368.40 | 1416.11 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 53.54 | 187.39 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9580.84 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 533.61 | 15-JAN-08:00 |
February | 45622.98 | 01-FEB-00:10 | 9580.84 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 550.48 | 19-FEB-05:00 |
March | 45622.98 | 01-MAR-00:10 | 9580.84 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 472.60 | 01-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 9580.84 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.26 | 01-APR-16:00 | 424.66 | 19-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 9580.84 | 01-MAY-19:19 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.21 | 05-MAY-16:00 | 370.57 | 11-MAY-03:00 |
June | 45622.98 | 01-JUN-00:10 | 9580.84 | 01-JUN-19:00 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.41 | 28-JUN-17:00 | 289.14 | 15-JUN-03:00 |
July | 45622.98 | 01-JUL-00:10 | 9580.84 | 10-JUL-19:00 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.67 | 24-JUL-15:00 | 243.75 | 19-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 9580.84 | 01-AUG-19:40 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.74 | 10-AUG-17:00 | 242.46 | 01-AUG-05:00 |
September | 45622.98 | 01-SEP-00:10 | 9580.84 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.71 | 22-SEP-16:00 | 311.82 | 27-SEP-05:00 |
October | 45622.98 | 01-OCT-23:10 | 9580.84 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 349.23 | 13-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 9580.84 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 450.62 | 11-NOV-08:00 |
December | 45622.98 | 01-DEC-00:10 | 9580.84 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 481.78 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9580.84 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.46 | |||||
Maximum of Months | 45622.98 | 9580.84 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 151.74 | 550.48 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.87 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 47.20 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 106.87 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 49.48 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 106.87 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 40.26 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 106.87 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.01 | 27-APR-16:00 | 35.67 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 106.87 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.43 | 05-MAY-16:00 | 30.19 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 106.87 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.24 | 28-JUN-17:00 | 22.76 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 106.87 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.03 | 24-JUL-15:10 | 18.02 | 04-JUL-07:20 |
August | 180.00 | 01-AUG-00:10 | 106.87 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 | 10-AUG-17:00 | 20.29 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 106.87 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.44 | 14-SEP-17:00 | 24.93 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 106.87 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 | 04-OCT-15:10 | 27.88 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 106.87 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 38.72 | 11-NOV-07:10 |
December | 180.00 | 01-DEC-00:10 | 106.87 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 42.55 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.02 | |||||
Maximum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 | 49.48 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.85 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 47.20 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 106.85 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 49.47 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 106.85 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 40.25 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 106.85 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.01 | 27-APR-15:10 | 35.67 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 106.85 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.43 | 05-MAY-16:00 | 30.19 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 106.85 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.24 | 28-JUN-17:00 | 22.76 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 106.85 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.03 | 24-JUL-15:10 | 20.20 | 11-JUL-19:55 |
August | 180.00 | 01-AUG-00:10 | 106.85 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 | 10-AUG-17:00 | 20.29 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 106.85 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.44 | 14-SEP-17:00 | 24.92 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 106.85 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 | 04-OCT-15:10 | 27.88 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 106.85 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 38.72 | 11-NOV-07:20 |
December | 180.00 | 01-DEC-00:10 | 106.85 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 42.55 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.20 | |||||
Maximum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 | 49.47 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 67.16 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 13.51 | 15-JAN-08:10 |
February | 0.00 | 01-FEB-00:10 | 67.16 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 14.23 | 09-FEB-08:00 |
March | 0.00 | 01-MAR-00:10 | 67.16 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 13.55 | 01-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 67.16 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 | 27-APR-15:13 | 12.05 | 19-APR-05:10 |
May | 0.00 | 01-MAY-00:10 | 67.16 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 10.84 | 11-MAY-03:00 |
June | 0.00 | 01-JUN-00:10 | 67.16 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 8.84 | 01-JUN-04:40 |
July | 0.00 | 01-JUL-00:10 | 67.16 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 | 24-JUL-15:00 | 7.69 | 07-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 67.16 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.31 | 10-AUG-17:00 | 7.74 | 06-AUG-05:00 |
September | 0.00 | 01-SEP-00:10 | 67.16 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 9.18 | 27-SEP-05:10 |
October | 0.00 | 01-OCT-00:10 | 67.16 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 10.43 | 13-OCT-05:10 |
November | 0.00 | 01-NOV-00:10 | 67.16 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 13.04 | 11-NOV-23:00 |
December | 0.00 | 01-DEC-00:10 | 67.16 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 13.29 | 06-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 67.16 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 | |||||
Maximum of Months | 0.00 | 67.16 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 2.31 | 14.23 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 67.18 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 13.17 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 67.18 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 13.81 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 67.18 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 11.24 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 67.18 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.79 | 27-APR-15:10 | 9.96 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 67.18 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 | 05-MAY-16:00 | 8.43 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 67.18 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 28-JUN-17:00 | 6.35 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 67.18 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 | 24-JUL-15:10 | 5.27 | 04-JUL-07:20 |
August | 180.00 | 01-AUG-00:10 | 67.18 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 10-AUG-17:00 | 5.55 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 67.18 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 | 14-SEP-17:00 | 6.96 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 67.18 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 | 04-OCT-15:10 | 7.81 | 29-OCT-08:00 |
November | 180.00 | 01-NOV-00:10 | 67.18 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 10.94 | 11-NOV-08:20 |
December | 180.00 | 01-DEC-00:10 | 67.18 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 11.88 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 67.18 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.27 | |||||
Maximum of Months | 180.00 | 67.18 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 13.81 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.87 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 47.20 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 106.87 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 49.48 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 106.87 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 40.26 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 106.87 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.01 | 27-APR-15:10 | 35.67 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 106.87 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.43 | 05-MAY-16:00 | 30.19 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 106.87 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.24 | 28-JUN-17:00 | 22.76 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 106.87 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.03 | 24-JUL-15:10 | 17.97 | 04-JUL-07:20 |
August | 180.00 | 01-AUG-00:10 | 106.87 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 | 10-AUG-17:00 | 20.78 | 01-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 106.87 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.45 | 14-SEP-17:00 | 24.93 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 106.87 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 | 04-OCT-15:10 | 27.88 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 106.87 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 38.72 | 11-NOV-07:10 |
December | 180.00 | 01-DEC-00:10 | 106.87 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 42.55 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.97 | |||||
Maximum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 | 49.48 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.85 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 47.20 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 106.85 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 49.47 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 106.85 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 40.25 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 106.85 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.01 | 27-APR-15:10 | 35.67 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 106.85 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.43 | 05-MAY-16:00 | 30.19 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 106.85 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.24 | 28-JUN-17:00 | 22.76 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 106.85 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.03 | 24-JUL-15:10 | 18.04 | 04-JUL-07:20 |
August | 180.00 | 01-AUG-00:10 | 106.85 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 | 10-AUG-17:00 | 20.78 | 01-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 106.85 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.44 | 14-SEP-17:00 | 24.92 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 106.85 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 | 04-OCT-15:10 | 27.88 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 106.85 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 38.72 | 11-NOV-07:20 |
December | 180.00 | 01-DEC-00:10 | 106.85 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 42.55 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.04 | |||||
Maximum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 | 49.47 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1044.00 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 56.83 | 15-JAN-08:00 |
February | 2263.36 | 01-FEB-00:10 | 1044.00 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 59.59 | 19-FEB-06:00 |
March | 2263.36 | 01-MAR-00:10 | 1044.00 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 48.43 | 01-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1044.00 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.35 | 01-APR-16:00 | 42.93 | 19-APR-05:00 |
May | 2263.36 | 01-MAY-00:10 | 1044.00 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.94 | 05-MAY-16:00 | 38.45 | 11-MAY-03:00 |
June | 2263.36 | 01-JUN-00:10 | 1044.00 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 | 28-JUN-17:00 | 29.39 | 15-JUN-03:00 |
July | 2263.36 | 01-JUL-00:10 | 1044.00 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.31 | 24-JUL-15:00 | 24.73 | 19-JUL-05:00 |
August | 2263.36 | 01-AUG-00:10 | 1044.00 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.59 | 29-AUG-16:00 | 25.25 | 01-AUG-05:00 |
September | 2263.36 | 01-SEP-00:10 | 1044.00 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 22-SEP-16:00 | 31.24 | 27-SEP-04:40 |
October | 2263.36 | 01-OCT-23:10 | 1044.00 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 35.05 | 13-OCT-05:00 |
November | 2263.36 | 01-NOV-00:10 | 1044.00 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 46.58 | 11-NOV-07:20 |
December | 2263.36 | 01-DEC-00:10 | 1044.00 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 51.21 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1044.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.73 | ||||
Maximum of Months | 2263.36 | 1044.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.59 | 59.59 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.87 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 47.32 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 106.87 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 49.60 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 106.87 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 40.37 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 106.87 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.91 | 27-APR-16:00 | 35.79 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 106.87 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 | 05-MAY-16:00 | 30.30 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 106.87 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 | 28-JUN-17:00 | 22.87 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 106.87 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.92 | 24-JUL-15:10 | 17.86 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 106.87 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.20 | 10-AUG-17:00 | 20.08 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 106.87 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.35 | 14-SEP-17:00 | 25.04 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 106.87 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 | 04-OCT-15:10 | 27.99 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 106.87 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 38.84 | 11-NOV-07:40 |
December | 180.00 | 01-DEC-00:10 | 106.87 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 42.67 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.86 | |||||
Maximum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 17.20 | 49.60 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.85 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 47.32 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 106.85 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 49.60 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 106.85 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 40.37 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 106.85 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.91 | 27-APR-15:50 | 35.79 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 106.85 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 05-MAY-16:00 | 30.30 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 106.85 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 | 28-JUN-17:00 | 22.87 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 106.85 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.81 | 24-JUL-15:10 | 22.41 | 11-JUL-19:55 |
August | 180.00 | 01-AUG-00:10 | 106.85 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.18 | 10-AUG-17:00 | 20.18 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 106.85 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.35 | 14-SEP-17:00 | 25.03 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 106.85 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 | 04-OCT-15:10 | 27.99 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 106.85 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 38.84 | 11-NOV-07:10 |
December | 180.00 | 01-DEC-00:10 | 106.85 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 42.67 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.18 | |||||
Maximum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 17.18 | 49.60 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 67.18 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 24.21 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 67.18 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 25.38 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 67.18 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 20.66 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 67.18 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.07 | 27-APR-16:00 | 18.31 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 67.18 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 | 05-MAY-16:00 | 15.50 | 11-MAY-03:10 |
June | 180.00 | 01-JUN-00:10 | 67.18 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.68 | 28-JUN-17:00 | 11.70 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 67.18 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.64 | 24-JUL-15:10 | 9.30 | 04-JUL-07:20 |
August | 180.00 | 01-AUG-00:10 | 67.18 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.80 | 10-AUG-17:00 | 10.30 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 67.18 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.25 | 14-SEP-17:00 | 12.81 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 67.18 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 14.32 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 67.18 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 19.87 | 11-NOV-07:10 |
December | 180.00 | 01-DEC-00:10 | 67.18 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 21.83 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 67.18 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.30 | |||||
Maximum of Months | 180.00 | 67.18 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 8.80 | 25.38 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2486.81 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 128.82 | 15-JAN-08:00 |
February | 26988.77 | 01-FEB-00:10 | 2486.81 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 131.83 | 19-FEB-06:10 |
March | 26988.77 | 01-MAR-00:10 | 2486.81 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 111.62 | 01-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2486.81 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 01-APR-16:00 | 100.30 | 19-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 2486.81 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 05-MAY-16:00 | 86.69 | 11-MAY-03:10 |
June | 26988.77 | 01-JUN-00:10 | 2486.81 | 01-JUN-19:00 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.58 | 28-JUN-17:00 | 68.32 | 15-JUN-03:10 |
July | 26988.77 | 01-JUL-00:10 | 2486.81 | 10-JUL-19:00 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.02 | 24-JUL-15:00 | 56.05 | 07-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2486.81 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.55 | 10-AUG-17:00 | 56.51 | 21-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 2486.81 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 | 14-SEP-17:00 | 73.71 | 27-SEP-05:00 |
October | 26988.77 | 01-OCT-23:10 | 2486.81 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 80.97 | 13-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2486.81 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 107.74 | 11-NOV-07:10 |
December | 26988.77 | 01-DEC-00:10 | 2486.81 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 117.31 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2486.81 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.05 | |||||
Maximum of Months | 26988.77 | 2486.81 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 30.55 | 131.83 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2486.81 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 128.83 | 15-JAN-08:00 |
February | 26988.77 | 01-FEB-00:10 | 2486.81 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 132.78 | 19-FEB-06:10 |
March | 26988.77 | 01-MAR-00:10 | 2486.81 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 111.62 | 01-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2486.81 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.26 | 01-APR-16:00 | 100.31 | 19-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 2486.81 | 01-MAY-19:19 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 05-MAY-16:00 | 86.70 | 11-MAY-03:10 |
June | 26988.77 | 01-JUN-00:10 | 2486.81 | 01-JUN-19:00 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.58 | 28-JUN-17:00 | 68.32 | 15-JUN-03:10 |
July | 26988.77 | 01-JUL-00:10 | 2486.81 | 10-JUL-19:00 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.02 | 24-JUL-15:00 | 56.05 | 07-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 2486.81 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.55 | 10-AUG-17:00 | 56.51 | 21-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 2486.81 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 | 14-SEP-17:00 | 73.71 | 27-SEP-05:00 |
October | 26988.77 | 01-OCT-23:10 | 2486.81 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 80.97 | 13-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2486.81 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 107.74 | 11-NOV-07:10 |
December | 26988.77 | 01-DEC-00:10 | 2486.81 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 117.31 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2486.81 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.05 | |||||
Maximum of Months | 26988.77 | 2486.81 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 30.55 | 132.78 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 981.75 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 115.30 | 15-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 981.75 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 119.12 | 19-FEB-06:20 |
March | 2401.70 | 01-MAR-00:10 | 981.75 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 99.90 | 01-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 981.75 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 11.27 | 27-APR-15:40 | 89.13 | 19-APR-05:10 |
May | 2401.70 | 01-MAY-00:10 | 981.75 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 3.33 | 05-MAY-16:00 | 74.65 | 11-MAY-05:10 |
June | 2401.70 | 01-JUN-00:10 | 981.75 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 9.51 | 28-JUN-17:00 | 58.42 | 15-JUN-05:10 |
July | 2401.70 | 01-JUL-00:10 | 981.75 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 23.32 | 24-JUL-15:00 | 50.18 | 07-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 981.75 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 27.39 | 10-AUG-17:00 | 49.91 | 06-AUG-05:10 |
September | 2401.70 | 01-SEP-00:10 | 981.75 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 3.34 | 14-SEP-17:00 | 65.22 | 27-SEP-05:10 |
October | 2401.70 | 01-OCT-23:10 | 981.75 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 72.48 | 13-OCT-05:00 |
November | 2401.70 | 01-NOV-00:10 | 981.75 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 96.43 | 11-NOV-07:10 |
December | 2401.70 | 01-DEC-00:10 | 981.75 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 105.00 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 981.75 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 49.91 | ||||||
Maximum of Months | 2401.70 | 981.75 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 27.39 | 119.12 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1104.91 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 100.81 | 15-JAN-08:00 |
February | 2395.44 | 01-FEB-00:10 | 1104.91 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 105.69 | 19-FEB-06:00 |
March | 2395.44 | 01-MAR-00:10 | 1104.91 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 85.95 | 01-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1104.91 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.09 | 01-APR-16:00 | 76.14 | 19-APR-05:00 |
May | 2395.44 | 01-MAY-00:10 | 1104.91 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.84 | 05-MAY-16:00 | 65.70 | 11-MAY-03:00 |
June | 2395.44 | 01-JUN-00:10 | 1104.91 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.22 | 28-JUN-17:00 | 50.24 | 15-JUN-03:00 |
July | 2395.44 | 01-JUL-00:10 | 1104.91 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.79 | 24-JUL-15:00 | 42.78 | 19-JUL-05:00 |
August | 2395.44 | 01-AUG-00:10 | 1104.91 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.80 | 29-AUG-16:00 | 43.55 | 01-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1104.91 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.57 | 22-SEP-16:00 | 53.17 | 27-SEP-04:05 |
October | 2395.44 | 01-OCT-23:10 | 1104.91 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 59.96 | 13-OCT-05:00 |
November | 2395.44 | 01-NOV-00:10 | 1104.91 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 82.67 | 11-NOV-08:00 |
December | 2395.44 | 01-DEC-00:10 | 1104.91 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 90.86 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1104.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.78 | ||||
Maximum of Months | 2395.44 | 1104.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.80 | 105.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11460.79 | 11-JAN-21:00 | 8945.92 | 8344.11 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11338.77 | 01-FEB-21:00 | 8945.92 | 8344.11 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11251.95 | 25-MAR-10:33 | 11501.89 | 6953.51 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11703.49 | 27-APR-18:10 | 53675.50 | 44502.01 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12044.34 | 14-MAY-10:33 | 11501.89 | 8343.99 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12431.82 | 25-JUN-10:33 | 11501.89 | 8343.99 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13019.74 | 30-JUL-10:33 | 11501.89 | 8343.99 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13305.11 | 13-AUG-10:33 | 11501.89 | 8343.99 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13393.70 | 10-SEP-10:33 | 11501.89 | 8343.99 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13135.42 | 07-OCT-10:33 | 11501.89 | 6953.51 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12853.58 | 04-NOV-10:33 | 11501.89 | 6953.51 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12214.45 | 01-DEC-21:00 | 8945.92 | 8344.11 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11251.95 | 8945.92 | 6953.51 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13393.70 | 53675.50 | 44502.01 | 54753.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2300.06 | 20-JAN-11:50 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.08 |
February | 2767.04 | 08-FEB-13:30 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.37 |
March | 3385.42 | 02-MAR-13:20 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.47 |
April | 3091.17 | 27-APR-13:05 | 519.79 | 256.16 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 6.01 | 0.00 |
May | 2989.28 | 04-MAY-13:20 | 519.79 | 256.16 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 |
June | 2581.31 | 28-JUN-10:35 | 519.79 | 256.16 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.71 |
July | 2879.13 | 31-JUL-13:30 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 10.75 | 0.00 |
August | 3714.56 | 24-AUG-13:10 | 519.79 | 256.16 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 14.02 | 0.00 |
September | 3881.61 | 14-SEP-13:15 | 519.79 | 256.16 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.44 |
October | 3930.50 | 04-OCT-12:50 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.91 |
November | 3188.39 | 04-NOV-13:30 | 779.69 | 256.16 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.25 |
December | 2561.80 | 05-DEC-11:50 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2300.06 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3930.50 | 779.69 | 256.16 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 14.02 | 54.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1109.20 | 11-JAN-21:00 | 1053.36 | 533.93 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.30 |
February | 1215.81 | 27-FEB-21:00 | 1053.36 | 533.93 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.76 |
March | 1246.25 | 02-MAR-21:00 | 1053.36 | 533.93 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.70 |
April | 1464.95 | 27-APR-21:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.73 |
May | 1438.29 | 04-MAY-21:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.08 |
June | 1505.23 | 28-JUN-21:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.38 |
July | 1694.71 | 31-JUL-21:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.60 |
August | 1847.60 | 10-AUG-20:55 | 4815.36 | 1898.43 | 3008.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 |
September | 1669.12 | 14-SEP-21:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 |
October | 1440.60 | 04-OCT-21:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.59 |
November | 1231.87 | 04-NOV-18:10 | 5417.28 | 2491.70 | 4011.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.98 |
December | 1161.51 | 05-DEC-21:00 | 1053.36 | 533.93 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1109.20 | 1053.36 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 | |
Maximum of Months | 1847.60 | 5417.28 | 2491.70 | 4011.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 743.32 | 11-JAN-21:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.94 |
February | 818.51 | 28-FEB-21:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.50 |
March | 817.61 | 18-MAR-18:10 | 1336.61 | 3352.47 | 4948.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.88 |
April | 975.09 | 27-APR-18:10 | 1336.61 | 3284.05 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 8.08 | 0.00 |
May | 1026.27 | 06-MAY-10:33 | 286.42 | 513.13 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 |
June | 1055.10 | 28-JUN-18:10 | 1336.61 | 3284.05 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 6.21 | 0.00 |
July | 1115.60 | 24-JUL-18:10 | 1336.61 | 3284.05 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 13.86 | 0.00 |
August | 1147.94 | 10-AUG-20:57 | 1018.37 | 2189.37 | 3181.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.64 |
September | 1059.33 | 14-SEP-10:33 | 190.94 | 513.13 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 |
October | 953.51 | 07-OCT-10:33 | 286.42 | 513.13 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.84 |
November | 864.95 | 04-NOV-10:33 | 286.42 | 513.13 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.97 |
December | 746.93 | 05-DEC-21:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 743.32 | 190.94 | 513.13 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1147.94 | 1336.61 | 3352.47 | 4948.32 | 0.00 | 0.00 | 0.00 | 0.00 | 13.86 | 44.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 376.09 | 11-JAN-21:00 | 171.36 | 137.35 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.05 |
February | 421.63 | 27-FEB-19:10 | 856.80 | 610.46 | 1147.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.93 |
March | 430.97 | 18-MAR-10:33 | 220.32 | 114.47 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.72 |
April | 515.27 | 27-APR-18:10 | 1028.16 | 732.55 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 4.90 | 0.00 |
May | 548.76 | 06-MAY-10:33 | 220.32 | 114.47 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 |
June | 557.86 | 28-JUN-18:10 | 1028.16 | 732.55 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 3.84 | 0.00 |
July | 592.13 | 24-JUL-18:10 | 1028.16 | 732.55 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 | 0.00 |
August | 601.38 | 10-AUG-10:35 | 97.92 | 76.31 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 0.00 |
September | 563.28 | 14-SEP-10:33 | 146.88 | 114.47 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.11 |
October | 505.38 | 04-OCT-10:33 | 146.88 | 114.47 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 |
November | 456.65 | 04-NOV-10:33 | 220.32 | 114.47 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.68 |
December | 392.52 | 03-DEC-11:33 | 220.32 | 137.35 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 376.09 | 97.92 | 76.31 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 601.38 | 1028.16 | 732.55 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 | 16.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36756.86 | 11-JAN-21:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 48.51 |
February | 37206.35 | 27-FEB-21:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 44.42 |
March | 37330.66 | 14-MAR-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 35.82 |
April | 38105.55 | 27-APR-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 16.76 |
May | 38047.78 | 15-MAY-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 |
June | 38236.56 | 28-JUN-19:55 | 1411.20 | 721.23 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 8.38 |
July | 38494.54 | 24-JUL-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 38564.68 | 10-AUG-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 5.69 | 0.00 |
September | 38191.83 | 14-SEP-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 18.73 |
October | 37814.42 | 04-OCT-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 24.92 |
November | 37090.94 | 02-NOV-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 42.19 |
December | 36704.01 | 05-DEC-21:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 70.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36704.01 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38564.68 | 1411.20 | 721.23 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 5.69 | 70.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9609.34 | 08-JAN-11:35 | 10245.60 | 207.70 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.77 |
February | 10904.38 | 08-FEB-13:30 | 3415.20 | 86.54 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.19 |
March | 12624.37 | 02-MAR-13:20 | 3415.20 | 86.54 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.20 |
April | 11410.15 | 27-APR-14:10 | 5122.80 | 86.54 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 14.44 | 0.00 |
May | 11206.75 | 04-MAY-15:07 | 51228.00 | 519.24 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 2.01 | 0.00 |
June | 10855.73 | 28-JUN-18:10 | 71719.20 | 1661.57 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 17.26 | 0.00 |
July | 11584.33 | 30-JUL-10:33 | 15368.40 | 311.54 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 3.25 | 0.00 |
August | 13013.71 | 24-AUG-15:03 | 51228.00 | 519.24 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 35.15 | 0.00 |
September | 13851.58 | 23-SEP-13:15 | 10245.60 | 173.08 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.20 |
October | 13939.68 | 04-OCT-12:50 | 3415.20 | 86.54 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.91 |
November | 12532.59 | 04-NOV-13:30 | 10245.60 | 173.08 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.44 |
December | 10603.03 | 02-DEC-11:33 | 15368.40 | 259.62 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9609.34 | 3415.20 | 86.54 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13939.68 | 71719.20 | 1661.57 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 35.15 | 150.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26634.88 | 11-JAN-22:00 | 40553.76 | 8516.30 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.31 |
February | 28679.11 | 27-FEB-21:00 | 35484.54 | 9580.84 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.60 |
March | 29307.13 | 02-MAR-22:20 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.21 |
April | 33653.23 | 27-APR-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.40 |
May | 33707.90 | 04-MAY-21:52 | 410606.82 | 57485.05 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.92 |
June | 34432.11 | 28-JUN-21:52 | 364983.84 | 51097.83 | 59119.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.46 |
July | 37088.92 | 24-JUL-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.78 |
August | 38680.16 | 10-AUG-21:05 | 91245.96 | 12774.46 | 14779.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.77 |
September | 37325.29 | 14-SEP-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.80 |
October | 34847.22 | 04-OCT-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.49 |
November | 28938.83 | 04-NOV-10:33 | 45622.98 | 6866.27 | 11084.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.30 |
December | 27573.40 | 05-DEC-21:00 | 35484.54 | 9580.84 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 26634.88 | 35484.54 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.77 | |
Maximum of Months | 38680.16 | 410606.82 | 57485.05 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2324.45 | 05-JAN-16:02 | 583.20 | 179.54 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.42 |
February | 2868.48 | 12-FEB-16:02 | 324.00 | 211.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.06 |
March | 2984.65 | 18-MAR-18:01 | 819.00 | 748.06 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 |
April | 3027.13 | 01-APR-15:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 | 0.00 |
May | 3216.03 | 14-MAY-18:02 | 702.00 | 641.20 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 |
June | 3030.06 | 30-JUN-15:02 | 583.20 | 179.54 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.42 |
July | 3253.12 | 31-JUL-18:02 | 831.60 | 570.67 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 6.01 | 0.00 |
August | 3270.78 | 24-AUG-18:02 | 831.60 | 570.67 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 8.25 | 0.00 |
September | 2996.83 | 29-SEP-15:02 | 583.20 | 179.54 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.95 |
October | 2981.08 | 08-OCT-15:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 |
November | 2929.47 | 04-NOV-15:02 | 324.00 | 211.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.93 |
December | 2714.18 | 03-DEC-16:02 | 324.00 | 211.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2324.45 | 324.00 | 179.54 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3270.78 | 831.60 | 748.06 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 8.25 | 28.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 713.91 | 30-JAN-16:04 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.98 |
February | 2533.87 | 26-FEB-16:02 | 324.00 | 211.57 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.95 |
March | 2598.36 | 18-MAR-15:02 | 324.00 | 211.57 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.10 |
April | 3020.51 | 25-APR-17:41 | 777.60 | 572.74 | 1074.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.52 |
May | 3132.34 | 20-MAY-19:11 | 1170.00 | 1068.54 | 1738.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.02 |
June | 3198.58 | 22-JUN-16:21 | 972.00 | 299.19 | 1343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 |
July | 3429.04 | 25-JUL-16:51 | 972.00 | 299.19 | 1343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 | 0.00 |
August | 3001.77 | 08-AUG-21:31 | 1620.00 | 644.33 | 829.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
September | 3323.20 | 22-SEP-16:11 | 972.00 | 299.19 | 1343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.95 |
October | 2610.33 | 24-OCT-15:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.21 |
November | 2452.80 | 04-NOV-15:02 | 324.00 | 211.57 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.85 |
December | 1040.69 | 02-DEC-16:02 | 324.00 | 211.57 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 713.91 | 324.00 | 209.43 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3429.04 | 1620.00 | 1068.54 | 1738.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 | 27.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 131.41 | 08-JAN-15:15 | 0.00 | 44.33 | 149.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.20 |
February | 489.77 | 08-FEB-13:40 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.11 |
March | 621.98 | 02-MAR-13:00 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.10 |
April | 565.55 | 27-APR-13:05 | 0.00 | 37.61 | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
May | 547.31 | 04-MAY-13:20 | 0.00 | 37.61 | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.86 |
June | 415.99 | 28-JUN-13:05 | 0.00 | 37.61 | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 |
July | 515.91 | 31-JUL-13:20 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 | 0.00 |
August | 643.11 | 24-AUG-13:05 | 0.00 | 37.61 | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 | 0.00 |
September | 691.70 | 14-SEP-13:30 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.58 |
October | 717.43 | 04-OCT-12:40 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.89 |
November | 553.49 | 04-NOV-13:40 | 0.00 | 22.16 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.74 |
December | 437.12 | 05-DEC-12:30 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 131.41 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 717.43 | 0.00 | 44.33 | 149.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 | 10.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 635.00 | 12-JAN-09:02 | 216.00 | 177.35 | 665.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.19 |
February | 687.93 | 26-FEB-09:02 | 216.00 | 150.48 | 639.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 |
March | 722.40 | 20-MAR-18:02 | 831.60 | 358.74 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.05 |
April | 866.16 | 27-APR-15:02 | 583.20 | 112.86 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.98 | 0.00 |
May | 841.07 | 04-MAY-15:02 | 583.20 | 112.86 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 | 0.00 |
June | 853.10 | 28-JUN-15:02 | 583.20 | 112.86 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 | 0.00 |
July | 874.25 | 24-JUL-18:02 | 831.60 | 358.74 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 2.64 | 0.00 |
August | 869.82 | 08-AUG-18:02 | 831.60 | 358.74 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 2.18 | 0.00 |
September | 823.42 | 11-SEP-15:02 | 583.20 | 112.86 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 0.00 |
October | 756.44 | 09-OCT-15:01 | 378.00 | 155.19 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.18 |
November | 722.03 | 04-NOV-15:02 | 324.00 | 133.02 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
December | 678.00 | 03-DEC-09:02 | 216.00 | 150.48 | 639.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 635.00 | 216.00 | 112.86 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 874.25 | 831.60 | 358.74 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 2.64 | 7.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 837.80 | 20-JAN-16:02 | 583.20 | 179.54 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.52 |
February | 2480.02 | 27-FEB-16:02 | 583.20 | 179.54 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.43 |
March | 2630.29 | 25-MAR-08:62 | 324.00 | 359.07 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 |
April | 2826.15 | 01-APR-15:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 6.03 | 0.00 |
May | 2844.32 | 14-MAY-18:02 | 702.00 | 641.20 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 |
June | 2808.22 | 28-JUN-18:02 | 831.60 | 570.67 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 4.70 | 0.00 |
July | 2858.93 | 24-JUL-18:02 | 831.60 | 570.67 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 | 0.00 |
August | 2911.41 | 09-AUG-18:02 | 831.60 | 570.67 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 8.23 | 0.00 |
September | 2767.41 | 22-SEP-15:02 | 583.20 | 179.54 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 | 0.00 |
October | 2669.11 | 04-OCT-18:02 | 831.60 | 570.67 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.38 |
November | 2606.99 | 04-NOV-15:02 | 324.00 | 211.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.78 |
December | 2005.44 | 05-DEC-16:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 837.80 | 324.00 | 179.54 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2911.41 | 831.60 | 641.20 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 | 32.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 674.03 | 25-JAN-19:05 | 831.60 | 570.60 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.94 |
February | 2181.37 | 12-FEB-09:01 | 378.00 | 418.87 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.81 |
March | 2395.24 | 25-MAR-08:62 | 324.00 | 359.03 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.26 |
April | 2660.64 | 27-APR-15:02 | 583.20 | 179.51 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 7.58 | 0.00 |
May | 2862.92 | 06-MAY-08:51 | 540.00 | 598.38 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.72 |
June | 2769.54 | 28-JUN-08:51 | 324.00 | 423.14 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 |
July | 3201.66 | 24-JUL-08:32 | 216.00 | 282.09 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.42 |
August | 3151.19 | 13-AUG-08:32 | 270.00 | 299.19 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 |
September | 2919.33 | 13-SEP-08:51 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.27 |
October | 2376.66 | 06-OCT-15:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 |
November | 2062.59 | 04-NOV-15:02 | 324.00 | 211.57 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 |
December | 743.92 | 13-DEC-09:04 | 252.00 | 329.11 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 674.03 | 216.00 | 179.51 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3201.66 | 831.60 | 598.38 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 7.58 | 34.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1230.56 | 11-JAN-22:00 | 2011.87 | 928.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.10 |
February | 1463.06 | 27-FEB-19:10 | 8801.94 | 4640.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.70 |
March | 1548.27 | 18-MAR-17:20 | 4526.71 | 2088.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 |
April | 1853.12 | 27-APR-18:10 | 10562.33 | 5568.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.18 | 0.00 |
May | 1923.81 | 06-MAY-10:33 | 2263.36 | 870.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.18 |
June | 1994.65 | 28-JUN-18:10 | 10562.33 | 5568.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.85 | 0.00 |
July | 2122.56 | 24-JUL-18:10 | 10562.33 | 5568.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.60 | 0.00 |
August | 2163.31 | 13-AUG-10:33 | 2263.36 | 1044.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.82 | 0.00 |
September | 2053.35 | 14-SEP-10:33 | 1508.90 | 870.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.49 |
October | 1801.07 | 07-OCT-10:33 | 2263.36 | 870.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.97 |
November | 1545.63 | 04-NOV-10:45 | 1508.90 | 580.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.64 |
December | 1395.46 | 03-DEC-11:33 | 2263.36 | 1044.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1230.56 | 1508.90 | 580.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2163.31 | 10562.33 | 5568.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.60 | 21.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2415.89 | 05-JAN-16:02 | 583.20 | 179.54 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.90 |
February | 2987.67 | 12-FEB-16:02 | 324.00 | 211.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.12 |
March | 3115.31 | 18-MAR-18:01 | 819.00 | 748.06 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 |
April | 3122.50 | 01-APR-15:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 5.68 | 0.00 |
May | 3370.56 | 14-MAY-18:02 | 702.00 | 641.20 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.61 |
June | 3153.37 | 22-JUN-18:02 | 831.60 | 570.67 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 1.48 | 0.00 |
July | 3410.06 | 31-JUL-18:02 | 831.60 | 570.67 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 5.86 | 0.00 |
August | 3424.04 | 10-AUG-18:02 | 831.60 | 570.67 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 | 0.00 |
September | 3126.42 | 13-SEP-18:02 | 831.60 | 570.67 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
October | 3084.45 | 04-OCT-18:02 | 831.60 | 570.67 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.46 |
November | 2980.28 | 04-NOV-15:02 | 324.00 | 211.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.13 |
December | 2594.60 | 10-DEC-16:02 | 324.00 | 211.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2415.89 | 324.00 | 179.54 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3424.04 | 831.60 | 748.06 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 | 28.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 754.68 | 05-JAN-16:03 | 583.20 | 179.51 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.65 |
February | 2614.39 | 27-FEB-16:02 | 583.20 | 179.51 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.56 |
March | 2761.06 | 18-MAR-15:02 | 324.00 | 211.57 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.11 |
April | 3148.22 | 25-APR-17:41 | 777.60 | 572.74 | 1074.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 |
May | 3196.32 | 15-MAY-16:32 | 583.20 | 179.51 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 |
June | 3274.36 | 22-JUN-16:21 | 972.00 | 299.19 | 1343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.98 |
July | 3540.40 | 25-JUL-16:51 | 972.00 | 299.19 | 1343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 0.00 |
August | 3144.99 | 06-AUG-21:51 | 1386.00 | 908.26 | 921.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 |
September | 3451.36 | 22-SEP-16:11 | 972.00 | 299.19 | 1343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.64 |
October | 2682.93 | 02-OCT-15:02 | 583.20 | 179.51 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.34 |
November | 2525.16 | 04-NOV-15:02 | 324.00 | 211.57 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.96 |
December | 772.26 | 28-DEC-16:05 | 583.20 | 179.51 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 754.68 | 324.00 | 179.51 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3540.40 | 1386.00 | 908.26 | 1343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1649.75 | 05-JAN-16:02 | 583.20 | 112.86 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.38 |
February | 1800.16 | 26-FEB-16:02 | 324.00 | 133.02 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.24 |
March | 1916.24 | 18-MAR-18:01 | 819.00 | 470.26 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.93 |
April | 2001.73 | 27-APR-18:02 | 831.60 | 358.74 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 2.54 | 0.00 |
May | 2002.98 | 14-MAY-18:02 | 702.00 | 403.08 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
June | 1980.37 | 28-JUN-18:02 | 831.60 | 358.74 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 | 0.00 |
July | 2046.19 | 30-JUL-18:02 | 702.00 | 403.08 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 3.25 | 0.00 |
August | 2060.33 | 24-AUG-15:02 | 583.20 | 112.86 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 | 0.00 |
September | 2043.95 | 12-SEP-15:02 | 583.20 | 112.86 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.28 | 0.00 |
October | 1900.82 | 04-OCT-18:02 | 831.60 | 358.74 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.35 |
November | 1940.71 | 04-NOV-15:02 | 324.00 | 133.02 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.70 |
December | 1757.26 | 10-DEC-16:02 | 324.00 | 133.02 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1649.75 | 324.00 | 112.86 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2060.33 | 831.60 | 470.26 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 | 15.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17531.72 | 11-JAN-22:50 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.84 |
February | 18585.48 | 27-FEB-23:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.96 |
March | 18461.38 | 10-MAR-23:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.67 |
April | 20338.57 | 27-APR-21:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.80 |
May | 20713.94 | 05-MAY-21:53 | 188921.38 | 11605.12 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.42 |
June | 21173.73 | 28-JUN-21:52 | 215910.14 | 13262.99 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.32 |
July | 21892.99 | 24-JUL-21:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 |
August | 21881.78 | 10-AUG-21:52 | 215910.14 | 13262.99 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.56 |
September | 20585.90 | 12-SEP-21:52 | 215910.14 | 13262.99 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.20 |
October | 19375.14 | 04-OCT-22:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.44 |
November | 18480.15 | 06-NOV-23:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.24 |
December | 17314.31 | 29-DEC-23:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17314.31 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.56 | |
Maximum of Months | 21892.99 | 215910.14 | 13262.99 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19593.61 | 11-JAN-22:30 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.29 |
February | 20453.18 | 27-FEB-23:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.96 |
March | 20417.85 | 08-MAR-23:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.32 |
April | 21899.68 | 27-APR-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.82 |
May | 22260.73 | 05-MAY-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.30 |
June | 22579.28 | 28-JUN-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.90 |
July | 23198.95 | 24-JUL-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.40 |
August | 23114.44 | 10-AUG-21:05 | 53977.54 | 3315.75 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.85 |
September | 21957.52 | 12-SEP-21:52 | 215910.14 | 13262.99 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.20 |
October | 20961.62 | 04-OCT-22:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.44 |
November | 20424.18 | 06-NOV-23:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.24 |
December | 19363.09 | 29-DEC-23:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19363.09 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.85 | |
Maximum of Months | 23198.95 | 215910.14 | 13262.99 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25139.84 | 30-JAN-11:35 | 1067.42 | 545.42 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 61.74 |
February | 26254.16 | 27-FEB-11:50 | 533.71 | 272.71 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 |
March | 27419.82 | 14-MAR-10:50 | 533.71 | 272.71 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 48.91 |
April | 28752.21 | 27-APR-10:35 | 1067.42 | 545.42 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 13.85 |
May | 28869.83 | 14-MAY-10:33 | 2401.70 | 981.75 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 15.09 |
June | 29174.89 | 10-JUN-10:33 | 2401.70 | 818.12 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 14.54 |
July | 29647.80 | 24-JUL-10:40 | 1067.42 | 545.42 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 6.71 | 0.00 |
August | 29744.25 | 13-AUG-10:33 | 2401.70 | 981.75 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.27 | 0.00 |
September | 29080.28 | 10-SEP-10:33 | 2401.70 | 981.75 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 21.57 |
October | 27882.76 | 07-OCT-10:33 | 2401.70 | 818.12 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 36.12 |
November | 27370.66 | 04-NOV-10:45 | 1601.14 | 545.42 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 24.80 |
December | 25632.50 | 03-DEC-11:50 | 800.57 | 327.25 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 48.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 25139.84 | 533.71 | 272.71 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29744.25 | 2401.70 | 981.75 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 6.71 | 61.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2800.40 | 20-JAN-11:50 | 532.32 | 306.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.06 |
February | 3469.26 | 27-FEB-19:10 | 9315.60 | 4910.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.89 |
March | 3723.73 | 14-MAR-17:13 | 3992.40 | 2209.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.36 |
April | 4492.63 | 27-APR-17:12 | 5323.20 | 2946.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.60 | 0.00 |
May | 4584.14 | 06-MAY-10:33 | 2395.44 | 920.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.27 |
June | 4769.97 | 28-JUN-18:10 | 11178.72 | 5892.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.79 | 0.00 |
July | 5043.54 | 24-JUL-18:10 | 11178.72 | 5892.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.11 | 0.00 |
August | 5775.54 | 10-AUG-15:03 | 7984.80 | 1841.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.90 | 0.00 |
September | 4729.82 | 14-SEP-10:33 | 1596.96 | 920.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.76 |
October | 4193.21 | 04-OCT-10:33 | 1596.96 | 920.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.96 |
November | 3718.96 | 04-NOV-10:50 | 1596.96 | 613.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.18 |
December | 3299.97 | 03-DEC-11:33 | 2395.44 | 1104.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2800.40 | 532.32 | 306.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5775.54 | 11178.72 | 5892.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.90 | 60.06 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.383986E+12 | 254180.72 | 02-JAN-20:10 | 0.381692E+12 | 376862.71 | 26-JAN-18:40 |
February | 0.346375E+12 | 259030.11 | 27-FEB-20:10 | 0.350391E+12 | 351132.74 | 22-FEB-18:40 |
March | 0.385406E+12 | 262924.28 | 14-MAR-19:30 | 0.382480E+12 | 340043.14 | 03-MAR-20:00 |
April | 0.385261E+12 | 318378.53 | 27-APR-18:19 | 0.356216E+12 | 361992.94 | 18-APR-17:00 |
May | 0.409065E+12 | 304814.55 | 04-MAY-19:19 | 0.348814E+12 | 318417.06 | 23-MAY-18:40 |
June | 0.413064E+12 | 325097.89 | 28-JUN-18:19 | 0.293892E+12 | 267490.20 | 13-JUN-21:10 |
July | 0.457006E+12 | 350715.13 | 24-JUL-19:49 | 0.257567E+12 | 187229.60 | 04-JUL-20:00 |
August | 0.476290E+12 | 367439.50 | 10-AUG-19:40 | 0.250996E+12 | 171615.00 | 03-AUG-17:49 |
September | 0.410028E+12 | 301615.37 | 14-SEP-19:19 | 0.292360E+12 | 266229.41 | 27-SEP-21:10 |
October | 0.389741E+12 | 283257.61 | 04-OCT-19:00 | 0.399897E+12 | 316504.10 | 31-OCT-16:00 |
November | 0.369397E+12 | 259666.39 | 04-NOV-19:19 | 0.375598E+12 | 357003.08 | 15-NOV-18:49 |
December | 0.383784E+12 | 255128.06 | 05-DEC-20:30 | 0.382825E+12 | 354904.65 | 31-DEC-19:10 |
Annual Sum or Average | 0.480940E+13 | 0.407273E+13 | ||||
Minimum of Months | 0.346375E+12 | 254180.72 | 0.250996E+12 | 171615.00 | ||
Maximum of Months | 0.476290E+12 | 367439.50 | 0.399897E+12 | 376862.71 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.469404E+11 | 0.189217E+11 | 0.146779E+12 | 0.544794E+11 | 0.420295E+11 | 0.252604E+10 | 0.00 | 0.999183E+09 | 0.00 | 0.00 | 0.237663E+11 | 0.438395E+11 | 0.00 |
February | 0.421163E+11 | 0.155994E+11 | 0.132565E+12 | 0.492072E+11 | 0.382811E+11 | 0.408831E+10 | 0.00 | 0.457591E+10 | 0.00 | 0.00 | 0.174951E+11 | 0.390987E+11 | 0.00 |
March | 0.463008E+11 | 0.152265E+11 | 0.146789E+12 | 0.544810E+11 | 0.432149E+11 | 0.709841E+10 | 0.00 | 0.110277E+11 | 0.00 | 0.00 | 0.150386E+11 | 0.425170E+11 | 0.00 |
April | 0.443449E+11 | 0.126832E+11 | 0.142011E+12 | 0.527213E+11 | 0.433220E+11 | 0.908229E+10 | 0.00 | 0.272319E+11 | 0.00 | 0.00 | 0.994618E+10 | 0.403227E+11 | 0.00 |
May | 0.455249E+11 | 0.112651E+11 | 0.146789E+12 | 0.544795E+11 | 0.463659E+11 | 0.100995E+11 | 0.00 | 0.436649E+11 | 0.00 | 0.00 | 0.610451E+10 | 0.410380E+11 | 0.00 |
June | 0.437498E+11 | 0.991357E+10 | 0.142058E+12 | 0.527227E+11 | 0.461626E+11 | 0.984675E+10 | 0.00 | 0.629446E+11 | 0.00 | 0.00 | 0.286310E+10 | 0.391796E+11 | 0.00 |
July | 0.452978E+11 | 0.106992E+11 | 0.146742E+12 | 0.544775E+11 | 0.491245E+11 | 0.102303E+11 | 0.00 | 0.929743E+11 | 0.00 | 0.00 | 0.381505E+10 | 0.399097E+11 | 0.00 |
August | 0.456174E+11 | 0.122838E+11 | 0.146800E+12 | 0.544806E+11 | 0.494024E+11 | 0.103389E+11 | 0.00 | 0.108582E+12 | 0.00 | 0.00 | 0.545381E+10 | 0.395697E+11 | 0.00 |
September | 0.446716E+11 | 0.138417E+11 | 0.142022E+12 | 0.527215E+11 | 0.455361E+11 | 0.972585E+10 | 0.00 | 0.561459E+11 | 0.00 | 0.00 | 0.261005E+10 | 0.391204E+11 | 0.00 |
October | 0.465597E+11 | 0.164250E+11 | 0.146768E+12 | 0.544792E+11 | 0.440663E+11 | 0.897210E+10 | 0.00 | 0.208812E+11 | 0.00 | 0.00 | 0.625928E+10 | 0.416018E+11 | 0.00 |
November | 0.453471E+11 | 0.177565E+11 | 0.142074E+12 | 0.527225E+11 | 0.409751E+11 | 0.481128E+10 | 0.00 | 0.556774E+10 | 0.00 | 0.00 | 0.153925E+11 | 0.411541E+11 | 0.00 |
December | 0.469563E+11 | 0.194077E+11 | 0.146742E+12 | 0.544786E+11 | 0.420436E+11 | 0.283018E+10 | 0.00 | 0.179002E+10 | 0.00 | 0.00 | 0.222577E+11 | 0.435693E+11 | 0.00 |
Annual Sum or Average | 0.543427E+12 | 0.174023E+12 | 0.172814E+13 | 0.641451E+12 | 0.530524E+12 | 0.896500E+11 | 0.00 | 0.436385E+12 | 0.00 | 0.00 | 0.131002E+12 | 0.490921E+12 | 0.00 |
Minimum of Months | 0.421163E+11 | 0.991357E+10 | 0.132565E+12 | 0.492072E+11 | 0.382811E+11 | 0.252604E+10 | 0.00 | 0.999183E+09 | 0.00 | 0.00 | 0.261005E+10 | 0.390987E+11 | 0.00 |
Maximum of Months | 0.469563E+11 | 0.194077E+11 | 0.146800E+12 | 0.544810E+11 | 0.494024E+11 | 0.103389E+11 | 0.00 | 0.108582E+12 | 0.00 | 0.00 | 0.237663E+11 | 0.438395E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.112203E+12 | 0.00 | 0.117571E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.108586E+12 | 0.00 | 0.104601E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.119620E+12 | 0.00 | 0.110836E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.108940E+12 | 0.00 | 0.100320E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.100205E+12 | 0.00 | 0.966309E+11 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.598027E+11 | 0.00 | 0.869759E+11 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.215216E+11 | 0.00 | 0.842250E+11 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.174451E+11 | 0.00 | 0.815120E+11 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.610289E+11 | 0.00 | 0.843603E+11 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.151854E+12 | 0.00 | 0.961398E+11 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.127239E+12 | 0.00 | 0.101268E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.117779E+12 | 0.00 | 0.113226E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.110622E+13 | 0.00 | 0.117767E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.174451E+11 | 0.00 | 0.815120E+11 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.151854E+12 | 0.00 | 0.117571E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 45424.10 | 02-JAN-20:10 | 11096.45 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 39153.57 | 02-JAN-07:19 | 22889.55 | 11-JAN-21:19 | 4065.12 | 26-JAN-20:49 | 0.00 | 01-JAN-00:10 |
February | 45424.10 | 01-FEB-20:10 | 11096.45 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 39153.57 | 01-FEB-07:19 | 24329.80 | 27-FEB-21:19 | 4107.69 | 04-FEB-09:09 | 0.00 | 01-FEB-00:10 |
March | 45424.10 | 01-MAR-20:10 | 11096.45 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 39153.57 | 13-MAR-06:19 | 25591.74 | 18-MAR-20:49 | 4126.66 | 02-MAR-10:30 | 0.00 | 01-MAR-00:10 |
April | 45424.10 | 03-APR-19:10 | 11096.45 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 39153.12 | 04-APR-06:19 | 30595.94 | 27-APR-21:00 | 4623.38 | 26-APR-15:30 | 0.00 | 01-APR-00:10 |
May | 45424.10 | 01-MAY-19:19 | 11096.45 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 39153.03 | 01-MAY-06:19 | 31522.84 | 15-MAY-21:19 | 4576.31 | 04-MAY-15:30 | 0.00 | 01-MAY-00:10 |
June | 45424.10 | 01-JUN-19:00 | 11096.45 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 39152.19 | 22-JUN-06:19 | 31005.37 | 21-JUN-21:00 | 4625.88 | 20-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 45424.10 | 10-JUL-19:00 | 11096.45 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 39152.23 | 10-JUL-06:19 | 31619.18 | 25-JUL-21:00 | 4897.28 | 27-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 45424.10 | 01-AUG-19:40 | 11096.45 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 39152.72 | 16-AUG-06:19 | 32360.00 | 24-AUG-21:00 | 5060.00 | 10-AUG-18:10 | 0.00 | 01-AUG-00:10 |
September | 45424.10 | 01-SEP-19:10 | 11096.45 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 39153.56 | 25-SEP-06:19 | 31974.89 | 14-SEP-21:00 | 4784.73 | 08-SEP-15:09 | 0.00 | 01-SEP-00:10 |
October | 45424.10 | 02-OCT-19:10 | 11096.45 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 39153.57 | 02-OCT-06:19 | 29742.73 | 04-OCT-21:19 | 4113.86 | 08-OCT-15:09 | 0.00 | 01-OCT-00:10 |
November | 45424.10 | 01-NOV-19:10 | 11096.45 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 39153.57 | 01-NOV-06:19 | 23801.35 | 06-NOV-21:19 | 4125.31 | 04-NOV-15:09 | 0.00 | 01-NOV-00:10 |
December | 45424.10 | 01-DEC-20:10 | 11096.45 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 39153.57 | 01-DEC-07:19 | 22726.93 | 28-DEC-21:10 | 4108.84 | 05-DEC-10:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 45424.10 | 11096.45 | 88863.15 | 39152.19 | 22726.93 | 4065.12 | 0.00 | |||||||
Maximum of Months | 45424.10 | 11096.45 | 88863.15 | 39153.57 | 32360.00 | 5060.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 5117.80 | 20-JAN-16:10 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 39660.07 | 02-JAN-19:10 | 0.00 |
February | 50903.74 | 27-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:20 | 39452.04 | 27-FEB-19:10 | 0.00 |
March | 57593.69 | 18-MAR-15:09 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:20 | 39895.35 | 31-MAR-18:49 | 0.00 |
April | 95830.22 | 27-APR-15:09 | 0.00 | 0.00 | 9938.94 | 01-APR-00:10 | 40308.45 | 21-APR-18:40 | 0.00 |
May | 84445.22 | 04-MAY-15:09 | 0.00 | 0.00 | 9938.94 | 02-MAY-01:00 | 41242.43 | 30-MAY-18:40 | 0.00 |
June | 94418.77 | 28-JUN-18:10 | 0.00 | 0.00 | 9938.94 | 01-JUN-03:00 | 41518.48 | 29-JUN-20:49 | 0.00 |
July | 117138.80 | 24-JUL-18:10 | 0.00 | 0.00 | 9938.94 | 07-JUL-12:09 | 41758.49 | 25-JUL-20:49 | 0.00 |
August | 132918.33 | 10-AUG-18:10 | 0.00 | 0.00 | 9938.94 | 06-AUG-15:39 | 41755.85 | 11-AUG-20:19 | 0.00 |
September | 95129.02 | 14-SEP-15:20 | 0.00 | 0.00 | 9938.94 | 08-SEP-16:40 | 41773.87 | 07-SEP-17:00 | 0.00 |
October | 71243.03 | 04-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 03-OCT-04:40 | 41664.71 | 03-OCT-18:49 | 0.00 |
November | 65631.68 | 04-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 08-NOV-22:10 | 41111.65 | 03-NOV-18:10 | 0.00 |
December | 14394.35 | 05-DEC-12:30 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:20 | 40303.11 | 04-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5117.80 | 0.00 | 0.00 | 9938.94 | 39452.04 | 0.00 | |||
Maximum of Months | 132918.33 | 0.00 | 0.00 | 9938.94 | 41773.87 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 254180.72 | 02-JAN-20:10 | 45424.10 | 87982.85 | 11096.45 | 31569.36 | 21931.41 | 3765.20 | 0.00 | 2086.74 | 0.00 |
February | 259030.11 | 27-FEB-20:10 | 45424.10 | 87982.85 | 11096.45 | 31569.36 | 24235.53 | 3667.30 | 0.00 | 13277.95 | 0.00 |
March | 262924.28 | 14-MAR-19:30 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 23539.14 | 3719.27 | 0.00 | 19727.35 | 0.00 |
April | 318378.53 | 27-APR-18:19 | 37054.00 | 78653.57 | 0.00 | 31361.58 | 26287.71 | 4460.89 | 0.00 | 88647.88 | 0.00 |
May | 304814.55 | 04-MAY-19:19 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 23902.31 | 4253.76 | 0.00 | 59075.45 | 0.00 |
June | 325097.89 | 28-JUN-18:19 | 36593.16 | 78653.57 | 0.00 | 31361.38 | 27591.88 | 4505.01 | 0.00 | 93436.32 | 0.00 |
July | 350715.13 | 24-JUL-19:49 | 45424.10 | 87982.85 | 11096.45 | 31573.20 | 28144.65 | 4518.19 | 0.00 | 90917.21 | 0.00 |
August | 367439.50 | 10-AUG-19:40 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 28389.79 | 4713.79 | 0.00 | 107808.87 | 0.00 |
September | 301615.37 | 14-SEP-19:19 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 24881.61 | 3963.98 | 0.00 | 55315.34 | 0.00 |
October | 283257.61 | 04-OCT-19:00 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 24037.74 | 3750.67 | 0.00 | 37609.66 | 0.00 |
November | 259666.39 | 04-NOV-19:19 | 38160.55 | 83599.54 | 11096.45 | 31467.39 | 22053.41 | 3762.70 | 0.00 | 27597.47 | 0.00 |
December | 255128.06 | 05-DEC-20:30 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 21103.00 | 3680.59 | 0.00 | 3855.58 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 254180.72 | 36593.16 | 78653.57 | 0.00 | 31361.38 | 21103.00 | 3667.30 | 0.00 | 2086.74 | 0.00 | |
Maximum of Months | 367439.50 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 28389.79 | 4713.79 | 0.00 | 107808.87 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 167161.61 | 26-JAN-19:10 | 0.00 | 112926.47 | 31-JAN-21:30 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 153957.68 | 06-FEB-14:30 | 0.00 | 110610.12 | 11-FEB-23:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 162139.92 | 12-MAR-08:09 | 0.00 | 105437.74 | 01-MAR-19:30 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 162954.21 | 18-APR-17:00 | 0.00 | 96328.51 | 01-APR-17:40 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 160886.89 | 28-MAY-07:00 | 0.00 | 88205.74 | 01-MAY-17:10 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 141486.70 | 01-JUN-04:00 | 0.00 | 79336.03 | 01-JUN-17:10 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 90213.66 | 03-JUL-03:00 | 0.00 | 70954.93 | 01-JUL-22:30 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 92230.42 | 21-AUG-04:00 | 0.00 | 67164.86 | 31-AUG-16:00 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 144312.09 | 27-SEP-07:30 | 0.00 | 75391.58 | 30-SEP-17:19 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 163117.36 | 15-OCT-08:09 | 0.00 | 87684.17 | 31-OCT-17:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 168851.31 | 26-NOV-19:10 | 0.00 | 98537.94 | 30-NOV-18:40 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 163771.80 | 02-DEC-23:40 | 0.00 | 109261.53 | 31-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 90213.66 | 0.00 | 67164.86 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 168851.31 | 0.00 | 112926.47 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.80 | 0.83 | 21.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.71 | 1.67 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.80 | 2.33 | 21.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.82 | 1.50 | 21.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.76 | 0.33 | 21.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.17 | 21.77 | 7.17 | 21.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.82 | 2.33 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 22.02 | 2.50 | 22.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.86 | 2.17 | 21.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 21.87 | 5.00 | 21.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.75 | 3.00 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.89 | 0.33 | 21.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 13.00 | 21.87 | 13.00 | 21.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 22.02 | 5.00 | 22.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.77 | 1.83 | 21.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 21.83 | 7.33 | 21.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 21.84 | 11.00 | 21.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 21.87 | 14.00 | 21.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 21.77 | 10.83 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.74 | 4.83 | 21.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 49.83 | 21.82 | 49.83 | 21.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 21.87 | 14.00 | 21.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.73 | 1.17 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.71 | 1.17 | 21.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.00 | 21.71 | 3.00 | 21.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.73 | 1.17 | 21.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.61 | 0.17 | 22.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.88 | 0.83 | 21.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 22.16 | 1.83 | 22.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 22.34 | 4.67 | 22.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 22.40 | 5.50 | 22.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.98 | 1.00 | 21.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 14.00 | 22.29 | 14.00 | 22.29 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 22.61 | 5.50 | 22.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.73 | 0.33 | 21.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.91 | 1.00 | 21.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.73 | 1.00 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.76 | 2.50 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.83 | 3.33 | 21.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.88 | 1.67 | 21.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.79 | 0.33 | 21.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.17 | 21.81 | 10.17 | 21.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.91 | 3.33 | 21.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 22.18 | 3.33 | 22.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.97 | 3.50 | 21.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 21.96 | 7.33 | 21.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 21.81 | 5.00 | 21.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.79 | 1.83 | 21.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 21.17 | 21.94 | 21.17 | 21.94 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 22.18 | 7.33 | 22.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.78 | 0.50 | 21.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.72 | 0.83 | 21.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.80 | 0.67 | 21.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.33 | 21.75 | 2.33 | 21.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.80 | 0.83 | 21.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.66 | 0.00 | 22.66 | 0.00 | 22.66 |
February | 672.00 | 22.45 | 0.00 | 22.45 | 0.00 | 22.45 |
March | 744.00 | 22.22 | 0.00 | 22.22 | 0.00 | 22.22 |
April | 720.00 | 22.10 | 0.00 | 22.10 | 0.00 | 22.10 |
May | 744.00 | 22.19 | 0.00 | 22.19 | 0.00 | 22.19 |
June | 720.00 | 22.38 | 0.00 | 22.38 | 0.00 | 22.38 |
July | 744.00 | 22.62 | 0.00 | 22.62 | 0.00 | 22.62 |
August | 744.00 | 22.84 | 0.00 | 22.84 | 0.00 | 22.84 |
September | 703.33 | 23.10 | 0.00 | 23.10 | 0.00 | 23.10 |
October | 723.17 | 23.32 | 0.00 | 23.32 | 0.00 | 23.32 |
November | 696.33 | 23.38 | 2.50 | 23.38 | 0.00 | 23.38 |
December | 744.00 | 23.08 | 0.00 | 23.08 | 0.00 | 23.08 |
Annual Sum or Average | 8698.83 | 22.69 | 2.50 | 22.69 | 0.00 | 22.69 |
Minimum of Months | 672.00 | 22.10 | 0.00 | 22.10 | 0.00 | 22.10 |
Maximum of Months | 744.00 | 23.38 | 2.50 | 23.38 | 0.00 | 23.38 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 741.00 | 21.03 | 233.00 | 21.03 | 233.00 | 21.02 |
February | 653.33 | 21.09 | 135.33 | 21.10 | 127.83 | 21.09 |
March | 716.17 | 21.14 | 25.33 | 21.19 | 11.17 | 21.19 |
April | 683.17 | 21.22 | 19.50 | 21.29 | 0.00 | 21.29 |
May | 698.33 | 21.27 | 24.33 | 21.35 | 0.00 | 21.35 |
June | 687.67 | 21.32 | 8.50 | 21.35 | 0.00 | 21.35 |
July | 644.50 | 21.50 | 58.33 | 21.67 | 0.00 | 21.67 |
August | 594.67 | 21.50 | 96.67 | 21.81 | 0.00 | 21.81 |
September | 608.67 | 21.35 | 87.67 | 21.65 | 0.00 | 21.65 |
October | 686.50 | 21.17 | 32.67 | 21.30 | 0.00 | 21.30 |
November | 707.50 | 21.04 | 42.83 | 21.06 | 37.17 | 21.06 |
December | 737.33 | 21.07 | 196.33 | 21.05 | 195.83 | 21.04 |
Annual Sum or Average | 8158.83 | 21.22 | 960.50 | 21.30 | 605.00 | 21.28 |
Minimum of Months | 594.67 | 21.03 | 8.50 | 21.03 | 0.00 | 21.02 |
Maximum of Months | 741.00 | 21.50 | 233.00 | 21.81 | 233.00 | 21.81 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
February | 672.00 | 21.84 | 0.00 | 21.84 | 0.00 | 21.84 |
March | 744.00 | 22.16 | 0.00 | 22.16 | 0.00 | 22.16 |
April | 704.50 | 22.42 | 0.00 | 22.42 | 0.00 | 22.42 |
May | 707.00 | 22.66 | 0.00 | 22.66 | 0.00 | 22.66 |
June | 654.33 | 22.76 | 7.17 | 22.77 | 0.00 | 22.77 |
July | 532.17 | 22.90 | 68.50 | 23.02 | 0.00 | 23.02 |
August | 448.83 | 22.84 | 119.33 | 23.07 | 0.00 | 23.07 |
September | 566.67 | 22.76 | 46.83 | 22.85 | 0.00 | 22.85 |
October | 734.83 | 22.46 | 0.00 | 22.46 | 0.00 | 22.46 |
November | 720.00 | 21.91 | 0.00 | 21.91 | 0.00 | 21.91 |
December | 744.00 | 21.68 | 0.00 | 21.68 | 0.00 | 21.68 |
Annual Sum or Average | 7972.33 | 22.29 | 241.83 | 22.33 | 0.00 | 22.33 |
Minimum of Months | 448.83 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
Maximum of Months | 744.00 | 22.90 | 119.33 | 23.07 | 0.00 | 23.07 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.05 | 20.33 | 21.05 | 20.33 | 21.05 |
February | 672.00 | 21.16 | 23.17 | 21.15 | 23.17 | 21.15 |
March | 744.00 | 21.41 | 5.83 | 21.41 | 5.83 | 21.40 |
April | 720.00 | 21.80 | 0.00 | 21.80 | 0.00 | 21.80 |
May | 744.00 | 22.31 | 0.00 | 22.31 | 0.00 | 22.31 |
June | 720.00 | 22.63 | 0.00 | 22.63 | 0.00 | 22.63 |
July | 723.83 | 22.96 | 0.00 | 22.96 | 0.00 | 22.96 |
August | 688.00 | 23.03 | 0.00 | 23.03 | 0.00 | 23.03 |
September | 715.83 | 22.63 | 0.00 | 22.63 | 0.00 | 22.63 |
October | 744.00 | 21.94 | 0.00 | 21.94 | 0.00 | 21.94 |
November | 720.00 | 21.33 | 0.00 | 21.33 | 0.00 | 21.33 |
December | 744.00 | 21.07 | 0.00 | 21.07 | 0.00 | 21.07 |
Annual Sum or Average | 8679.67 | 21.94 | 49.33 | 21.93 | 49.33 | 21.93 |
Minimum of Months | 672.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
Maximum of Months | 744.00 | 23.03 | 23.17 | 23.03 | 23.17 | 23.03 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 53.83 | 21.00 | 53.83 | 21.00 |
February | 672.00 | 21.06 | 54.00 | 21.06 | 54.00 | 21.06 |
March | 744.00 | 21.20 | 13.33 | 21.20 | 13.33 | 21.20 |
April | 720.00 | 21.58 | 0.00 | 21.58 | 0.00 | 21.58 |
May | 744.00 | 22.10 | 0.00 | 22.10 | 0.00 | 22.10 |
June | 720.00 | 22.43 | 0.00 | 22.43 | 0.00 | 22.43 |
July | 743.50 | 22.80 | 0.00 | 22.80 | 0.00 | 22.80 |
August | 736.67 | 22.89 | 0.00 | 22.89 | 0.00 | 22.89 |
September | 720.00 | 22.42 | 0.00 | 22.42 | 0.00 | 22.42 |
October | 744.00 | 21.70 | 0.00 | 21.70 | 0.00 | 21.70 |
November | 720.00 | 21.17 | 0.00 | 21.17 | 0.00 | 21.17 |
December | 744.00 | 21.01 | 6.67 | 21.01 | 6.67 | 21.01 |
Annual Sum or Average | 8752.17 | 21.78 | 127.83 | 21.77 | 127.83 | 21.76 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.89 | 54.00 | 22.89 | 54.00 | 22.89 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 267.33 | 22.70 | 447.50 | 23.18 | 142.67 | 23.31 |
February | 244.83 | 22.82 | 445.00 | 23.18 | 142.50 | 23.32 |
March | 265.67 | 22.93 | 520.50 | 23.20 | 167.67 | 23.34 |
April | 265.50 | 23.14 | 548.50 | 23.22 | 188.83 | 23.36 |
May | 303.33 | 23.33 | 610.00 | 23.22 | 234.83 | 23.38 |
June | 306.33 | 23.49 | 615.50 | 23.24 | 254.50 | 23.40 |
July | 305.83 | 23.65 | 658.67 | 23.25 | 270.67 | 23.41 |
August | 307.67 | 23.77 | 672.67 | 23.26 | 286.17 | 23.43 |
September | 303.33 | 23.55 | 628.17 | 23.24 | 258.33 | 23.40 |
October | 285.00 | 23.22 | 606.17 | 23.20 | 210.50 | 23.36 |
November | 264.67 | 23.01 | 519.67 | 23.20 | 173.50 | 23.34 |
December | 258.33 | 22.75 | 461.67 | 23.19 | 143.83 | 23.32 |
Annual Sum or Average | 3377.83 | 23.22 | 6734.00 | 23.22 | 2474.00 | 23.37 |
Minimum of Months | 244.83 | 22.70 | 445.00 | 23.18 | 142.50 | 23.31 |
Maximum of Months | 307.67 | 23.77 | 672.67 | 23.26 | 286.17 | 23.43 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 736.17 | 21.34 | 10.00 | 21.35 | 7.50 | 21.34 |
February | 641.33 | 21.57 | 15.17 | 21.62 | 0.67 | 21.62 |
March | 699.00 | 21.80 | 23.00 | 21.87 | 0.00 | 21.87 |
April | 640.17 | 21.96 | 37.33 | 22.05 | 0.00 | 22.05 |
May | 633.50 | 22.07 | 47.50 | 22.16 | 0.00 | 22.16 |
June | 586.83 | 22.17 | 36.50 | 22.23 | 0.00 | 22.23 |
July | 435.67 | 22.24 | 161.00 | 22.53 | 1.50 | 22.53 |
August | 400.67 | 22.22 | 277.17 | 22.75 | 22.50 | 22.78 |
September | 456.00 | 22.07 | 188.67 | 22.52 | 0.00 | 22.52 |
October | 641.00 | 21.94 | 55.67 | 22.08 | 0.00 | 22.08 |
November | 702.00 | 21.53 | 14.33 | 21.57 | 1.17 | 21.58 |
December | 726.00 | 21.40 | 12.50 | 21.42 | 7.00 | 21.41 |
Annual Sum or Average | 7298.33 | 21.81 | 878.83 | 21.99 | 40.33 | 22.00 |
Minimum of Months | 400.67 | 21.34 | 10.00 | 21.35 | 0.00 | 21.34 |
Maximum of Months | 736.17 | 22.24 | 277.17 | 22.75 | 22.50 | 22.78 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.01 | 0.00 | 22.01 | 0.00 | 22.01 |
February | 666.83 | 22.28 | 0.00 | 22.28 | 0.00 | 22.28 |
March | 731.17 | 22.56 | 0.00 | 22.56 | 0.00 | 22.56 |
April | 637.17 | 22.69 | 12.50 | 22.72 | 0.00 | 22.72 |
May | 570.83 | 22.77 | 34.17 | 22.84 | 0.00 | 22.84 |
June | 459.00 | 22.75 | 85.67 | 22.93 | 0.00 | 22.93 |
July | 312.50 | 22.78 | 204.33 | 23.22 | 0.00 | 23.22 |
August | 239.67 | 22.79 | 324.17 | 23.40 | 25.00 | 23.42 |
September | 325.67 | 22.70 | 192.17 | 23.12 | 2.33 | 23.12 |
October | 626.67 | 22.69 | 9.67 | 22.71 | 0.00 | 22.71 |
November | 700.83 | 22.30 | 3.83 | 22.31 | 1.67 | 22.32 |
December | 744.00 | 22.11 | 0.00 | 22.11 | 0.00 | 22.11 |
Annual Sum or Average | 6758.33 | 22.48 | 866.50 | 22.63 | 29.00 | 22.64 |
Minimum of Months | 239.67 | 22.01 | 0.00 | 22.01 | 0.00 | 22.01 |
Maximum of Months | 744.00 | 22.79 | 324.17 | 23.40 | 25.00 | 23.42 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.81 | 350.17 | 20.69 | 350.17 | 20.63 |
February | 670.33 | 21.07 | 180.50 | 20.97 | 180.50 | 20.91 |
March | 740.33 | 21.27 | 18.33 | 21.25 | 18.33 | 21.23 |
April | 702.50 | 21.47 | 1.50 | 21.47 | 0.83 | 21.47 |
May | 701.67 | 21.53 | 2.83 | 21.54 | 0.00 | 21.54 |
June | 677.67 | 21.57 | 1.00 | 21.57 | 0.00 | 21.57 |
July | 653.83 | 21.48 | 12.50 | 21.52 | 0.00 | 21.52 |
August | 657.33 | 21.49 | 17.50 | 21.54 | 0.00 | 21.54 |
September | 658.17 | 21.46 | 9.33 | 21.48 | 0.00 | 21.48 |
October | 730.17 | 21.35 | 0.33 | 21.35 | 0.00 | 21.35 |
November | 718.00 | 21.00 | 100.33 | 20.90 | 100.33 | 20.83 |
December | 744.00 | 20.87 | 269.50 | 20.73 | 269.50 | 20.65 |
Annual Sum or Average | 8398.00 | 21.27 | 963.83 | 21.20 | 919.67 | 21.13 |
Minimum of Months | 653.83 | 20.81 | 0.33 | 20.69 | 0.00 | 20.63 |
Maximum of Months | 744.00 | 21.57 | 350.17 | 21.57 | 350.17 | 21.57 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.65 | 464.83 | 20.55 | 464.83 | 20.51 |
February | 672.00 | 20.86 | 288.33 | 20.75 | 288.33 | 20.70 |
March | 743.67 | 21.10 | 55.67 | 21.06 | 55.67 | 21.02 |
April | 702.00 | 21.42 | 6.83 | 21.45 | 1.50 | 21.45 |
May | 664.17 | 21.69 | 53.50 | 22.02 | 9.17 | 22.09 |
June | 622.50 | 21.84 | 55.67 | 22.15 | 4.33 | 22.18 |
July | 581.00 | 22.02 | 111.50 | 22.61 | 23.50 | 22.78 |
August | 621.50 | 21.90 | 55.33 | 22.16 | 5.50 | 22.21 |
September | 613.17 | 21.67 | 57.17 | 21.97 | 3.83 | 22.00 |
October | 739.67 | 21.26 | 2.83 | 21.27 | 1.00 | 21.27 |
November | 720.00 | 20.87 | 162.67 | 20.74 | 162.67 | 20.65 |
December | 744.00 | 20.70 | 384.50 | 20.58 | 384.50 | 20.52 |
Annual Sum or Average | 8167.67 | 21.30 | 1698.83 | 21.32 | 1404.83 | 21.23 |
Minimum of Months | 581.00 | 20.65 | 2.83 | 20.55 | 1.00 | 20.51 |
Maximum of Months | 744.00 | 22.02 | 464.83 | 22.61 | 464.83 | 22.78 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.04 | 60.33 | 21.00 | 60.33 | 20.96 |
February | 672.00 | 21.13 | 30.00 | 21.11 | 30.00 | 21.09 |
March | 744.00 | 21.28 | 0.00 | 21.28 | 0.00 | 21.28 |
April | 720.00 | 21.48 | 0.00 | 21.48 | 0.00 | 21.48 |
May | 744.00 | 21.72 | 0.00 | 21.72 | 0.00 | 21.72 |
June | 719.67 | 21.92 | 0.00 | 21.92 | 0.00 | 21.92 |
July | 735.33 | 22.03 | 0.00 | 22.03 | 0.00 | 22.03 |
August | 743.67 | 21.97 | 0.00 | 21.97 | 0.00 | 21.97 |
September | 720.00 | 21.75 | 0.00 | 21.75 | 0.00 | 21.75 |
October | 744.00 | 21.36 | 0.00 | 21.36 | 0.00 | 21.36 |
November | 720.00 | 21.18 | 5.67 | 21.18 | 5.67 | 21.17 |
December | 744.00 | 21.06 | 30.83 | 21.03 | 30.83 | 21.00 |
Annual Sum or Average | 8750.67 | 21.49 | 126.83 | 21.48 | 126.83 | 21.47 |
Minimum of Months | 672.00 | 21.04 | 0.00 | 21.00 | 0.00 | 20.96 |
Maximum of Months | 744.00 | 22.03 | 60.33 | 22.03 | 60.33 | 22.03 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.79 | 357.50 | 20.69 | 357.50 | 20.63 |
February | 672.00 | 21.09 | 172.83 | 21.00 | 172.83 | 20.94 |
March | 744.00 | 21.34 | 13.67 | 21.32 | 13.67 | 21.31 |
April | 704.50 | 21.55 | 0.33 | 21.55 | 0.33 | 21.55 |
May | 700.83 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
June | 655.67 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
July | 656.50 | 21.50 | 2.50 | 21.51 | 0.00 | 21.51 |
August | 642.83 | 21.47 | 6.50 | 21.49 | 0.00 | 21.49 |
September | 659.00 | 21.46 | 1.17 | 21.46 | 0.00 | 21.46 |
October | 736.00 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
November | 720.00 | 21.01 | 103.83 | 20.90 | 103.83 | 20.82 |
December | 744.00 | 20.86 | 273.00 | 20.73 | 273.00 | 20.65 |
Annual Sum or Average | 8379.33 | 21.29 | 931.33 | 21.21 | 921.17 | 21.14 |
Minimum of Months | 642.83 | 20.79 | 0.00 | 20.69 | 0.00 | 20.63 |
Maximum of Months | 744.00 | 21.55 | 357.50 | 21.55 | 357.50 | 21.55 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.64 | 463.67 | 20.53 | 463.67 | 20.48 |
February | 672.00 | 20.85 | 283.17 | 20.76 | 283.17 | 20.71 |
March | 744.00 | 21.16 | 34.17 | 21.13 | 34.17 | 21.10 |
April | 718.00 | 21.56 | 1.50 | 21.56 | 0.67 | 21.56 |
May | 722.67 | 21.78 | 1.83 | 21.79 | 0.00 | 21.79 |
June | 652.50 | 21.93 | 13.67 | 21.99 | 0.00 | 21.99 |
July | 621.17 | 21.97 | 33.00 | 22.13 | 4.33 | 22.16 |
August | 621.33 | 21.93 | 34.33 | 22.11 | 5.00 | 22.15 |
September | 683.17 | 21.77 | 7.50 | 21.80 | 0.00 | 21.80 |
October | 744.00 | 21.29 | 2.17 | 21.29 | 2.17 | 21.29 |
November | 720.00 | 20.86 | 177.33 | 20.73 | 177.33 | 20.64 |
December | 744.00 | 20.68 | 414.00 | 20.57 | 414.00 | 20.51 |
Annual Sum or Average | 8386.83 | 21.35 | 1466.33 | 21.25 | 1384.50 | 21.14 |
Minimum of Months | 621.17 | 20.64 | 1.50 | 20.53 | 0.00 | 20.48 |
Maximum of Months | 744.00 | 21.97 | 463.67 | 22.13 | 463.67 | 22.16 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 28.00 | 21.00 | 28.00 | 21.00 |
February | 672.00 | 21.03 | 22.17 | 21.03 | 22.17 | 21.03 |
March | 744.00 | 21.15 | 0.00 | 21.15 | 0.00 | 21.15 |
April | 720.00 | 21.50 | 0.00 | 21.50 | 0.00 | 21.50 |
May | 744.00 | 22.09 | 0.00 | 22.09 | 0.00 | 22.09 |
June | 720.00 | 22.38 | 0.00 | 22.38 | 0.00 | 22.38 |
July | 744.00 | 22.78 | 0.00 | 22.78 | 0.00 | 22.78 |
August | 737.17 | 22.89 | 0.00 | 22.89 | 0.00 | 22.89 |
September | 720.00 | 22.39 | 0.00 | 22.39 | 0.00 | 22.39 |
October | 744.00 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
November | 720.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
December | 744.00 | 21.00 | 7.33 | 21.00 | 7.33 | 21.00 |
Annual Sum or Average | 8753.17 | 21.73 | 57.50 | 21.73 | 57.50 | 21.72 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.89 | 28.00 | 22.89 | 28.00 | 22.89 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.67 | 558.67 | 20.61 | 558.67 | 20.58 |
February | 670.17 | 20.96 | 293.00 | 20.84 | 293.00 | 20.78 |
March | 737.83 | 21.19 | 91.17 | 21.10 | 91.17 | 21.04 |
April | 694.33 | 21.40 | 7.17 | 21.41 | 3.17 | 21.40 |
May | 684.33 | 21.46 | 13.17 | 21.50 | 0.00 | 21.50 |
June | 655.33 | 21.50 | 7.33 | 21.52 | 0.00 | 21.52 |
July | 628.00 | 21.40 | 28.67 | 21.49 | 0.00 | 21.49 |
August | 639.50 | 21.43 | 34.17 | 21.52 | 1.00 | 21.53 |
September | 648.17 | 21.39 | 29.17 | 21.46 | 6.50 | 21.46 |
October | 725.00 | 21.27 | 11.50 | 21.25 | 10.33 | 21.23 |
November | 717.50 | 20.89 | 256.17 | 20.78 | 256.17 | 20.71 |
December | 744.00 | 20.77 | 484.17 | 20.67 | 484.17 | 20.63 |
Annual Sum or Average | 8288.17 | 21.18 | 1814.33 | 21.09 | 1704.17 | 21.01 |
Minimum of Months | 628.00 | 20.67 | 7.17 | 20.61 | 0.00 | 20.58 |
Maximum of Months | 744.00 | 21.50 | 558.67 | 21.52 | 558.67 | 21.53 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.55 | 636.50 | 20.50 | 636.50 | 20.49 |
February | 672.00 | 20.75 | 407.00 | 20.65 | 407.00 | 20.61 |
March | 742.17 | 21.01 | 158.83 | 20.92 | 158.83 | 20.85 |
April | 690.17 | 21.35 | 15.33 | 21.38 | 8.17 | 21.37 |
May | 660.83 | 21.77 | 68.50 | 22.20 | 22.83 | 22.37 |
June | 604.00 | 21.87 | 75.00 | 22.31 | 14.33 | 22.42 |
July | 561.83 | 22.13 | 132.33 | 22.86 | 39.67 | 23.15 |
August | 602.00 | 21.88 | 75.00 | 22.23 | 12.83 | 22.33 |
September | 597.00 | 21.63 | 86.83 | 22.08 | 15.33 | 22.15 |
October | 737.50 | 21.17 | 25.67 | 21.14 | 23.00 | 21.11 |
November | 719.83 | 20.76 | 334.67 | 20.65 | 334.67 | 20.59 |
December | 744.00 | 20.60 | 622.83 | 20.55 | 622.83 | 20.54 |
Annual Sum or Average | 8075.33 | 21.24 | 2638.50 | 21.27 | 2296.00 | 21.18 |
Minimum of Months | 561.83 | 20.55 | 15.33 | 20.50 | 8.17 | 20.49 |
Maximum of Months | 744.00 | 22.13 | 636.50 | 22.86 | 636.50 | 23.15 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 736.67 | 21.05 | 190.83 | 20.94 | 190.83 | 20.87 |
February | 647.17 | 21.23 | 96.17 | 21.18 | 96.17 | 21.13 |
March | 714.67 | 21.37 | 14.50 | 21.39 | 7.00 | 21.38 |
April | 673.50 | 21.48 | 2.83 | 21.49 | 0.00 | 21.49 |
May | 684.67 | 21.49 | 2.50 | 21.50 | 0.00 | 21.50 |
June | 653.83 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
July | 642.83 | 21.43 | 1.17 | 21.44 | 0.00 | 21.44 |
August | 649.67 | 21.45 | 29.17 | 21.53 | 0.00 | 21.53 |
September | 640.83 | 21.43 | 42.67 | 21.55 | 0.00 | 21.55 |
October | 688.83 | 21.38 | 11.33 | 21.41 | 0.00 | 21.41 |
November | 706.17 | 21.19 | 37.17 | 21.14 | 33.83 | 21.09 |
December | 731.00 | 21.07 | 144.50 | 20.94 | 144.50 | 20.85 |
Annual Sum or Average | 8169.83 | 21.33 | 572.83 | 21.31 | 472.33 | 21.27 |
Minimum of Months | 640.83 | 21.05 | 0.00 | 20.94 | 0.00 | 20.85 |
Maximum of Months | 736.67 | 21.51 | 190.83 | 21.55 | 190.83 | 21.55 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 437.33 | 23.01 | 18.33 | 23.05 | 0.00 | 23.05 |
February | 343.50 | 23.06 | 71.83 | 23.22 | 0.00 | 23.22 |
March | 298.33 | 23.15 | 93.00 | 23.35 | 0.00 | 23.35 |
April | 143.50 | 23.12 | 221.00 | 23.63 | 0.00 | 23.63 |
May | 34.00 | 23.13 | 508.83 | 23.92 | 0.17 | 23.92 |
June | 6.33 | 23.13 | 619.17 | 23.95 | 0.00 | 23.95 |
July | 2.17 | 23.92 | 706.67 | 23.94 | 2.00 | 23.94 |
August | 28.17 | 23.99 | 725.67 | 23.92 | 28.17 | 23.92 |
September | 33.17 | 23.31 | 613.33 | 23.89 | 9.67 | 23.89 |
October | 182.67 | 23.01 | 297.50 | 23.61 | 0.00 | 23.61 |
November | 303.17 | 22.99 | 143.83 | 23.31 | 2.50 | 23.31 |
December | 385.83 | 22.95 | 23.00 | 23.01 | 0.00 | 23.01 |
Annual Sum or Average | 2198.17 | 23.05 | 4042.17 | 23.63 | 42.50 | 23.63 |
Minimum of Months | 2.17 | 22.95 | 18.33 | 23.01 | 0.00 | 23.01 |
Maximum of Months | 437.33 | 23.99 | 725.67 | 23.95 | 28.17 | 23.95 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 292.33 | 23.10 | 122.33 | 23.36 | 0.00 | 23.36 |
February | 210.17 | 23.17 | 175.50 | 23.54 | 0.00 | 23.54 |
March | 136.83 | 23.20 | 295.67 | 23.74 | 0.00 | 23.74 |
April | 24.83 | 23.20 | 458.50 | 23.93 | 0.00 | 23.93 |
May | 0.33 | 23.07 | 662.67 | 23.97 | 0.00 | 23.97 |
June | 0.00 | 0.00 | 690.33 | 23.96 | 0.00 | 23.96 |
July | 0.00 | 0.00 | 740.00 | 23.96 | 0.00 | 23.96 |
August | 19.17 | 24.00 | 744.00 | 23.95 | 19.17 | 23.95 |
September | 4.00 | 23.99 | 684.33 | 23.94 | 4.00 | 23.94 |
October | 38.50 | 23.13 | 500.00 | 23.92 | 0.00 | 23.92 |
November | 141.50 | 23.05 | 305.83 | 23.68 | 1.33 | 23.69 |
December | 239.17 | 23.04 | 129.67 | 23.38 | 0.00 | 23.38 |
Annual Sum or Average | 1106.83 | 23.13 | 5508.83 | 23.82 | 24.50 | 23.83 |
Minimum of Months | 0.00 | 0.00 | 122.33 | 23.36 | 0.00 | 23.36 |
Maximum of Months | 292.33 | 24.00 | 744.00 | 23.97 | 19.17 | 23.97 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 526.33 | 23.84 | 624.00 | 23.87 | 484.67 | 23.91 |
February | 477.83 | 23.87 | 578.50 | 23.88 | 446.83 | 23.91 |
March | 519.50 | 23.98 | 674.67 | 23.90 | 516.00 | 23.93 |
April | 511.00 | 23.99 | 685.33 | 23.89 | 511.00 | 23.92 |
May | 534.50 | 23.99 | 736.67 | 23.88 | 534.50 | 23.91 |
June | 528.00 | 23.99 | 720.00 | 23.90 | 528.00 | 23.92 |
July | 554.67 | 23.99 | 744.00 | 23.91 | 554.67 | 23.93 |
August | 561.00 | 23.99 | 744.00 | 23.92 | 561.00 | 23.94 |
September | 524.83 | 23.99 | 719.67 | 23.89 | 524.83 | 23.92 |
October | 525.50 | 23.99 | 721.50 | 23.88 | 525.50 | 23.91 |
November | 501.17 | 23.96 | 649.67 | 23.89 | 493.17 | 23.92 |
December | 513.33 | 23.90 | 625.67 | 23.90 | 489.83 | 23.93 |
Annual Sum or Average | 6277.67 | 23.96 | 8223.67 | 23.89 | 6170.00 | 23.92 |
Minimum of Months | 477.83 | 23.84 | 578.50 | 23.87 | 446.83 | 23.91 |
Maximum of Months | 561.00 | 23.99 | 744.00 | 23.92 | 561.00 | 23.94 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 48.50 | 21.00 | 48.50 | 21.00 |
February | 672.00 | 21.05 | 38.33 | 21.05 | 38.33 | 21.05 |
March | 744.00 | 21.17 | 2.83 | 21.17 | 2.83 | 21.17 |
April | 720.00 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
May | 742.33 | 22.03 | 0.00 | 22.03 | 0.00 | 22.03 |
June | 705.83 | 22.40 | 0.00 | 22.40 | 0.00 | 22.40 |
July | 641.33 | 22.68 | 18.67 | 22.71 | 0.00 | 22.71 |
August | 595.50 | 22.64 | 47.17 | 22.73 | 0.00 | 22.73 |
September | 681.17 | 22.17 | 10.83 | 22.19 | 0.00 | 22.19 |
October | 744.00 | 21.40 | 0.00 | 21.40 | 0.00 | 21.40 |
November | 720.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
December | 744.00 | 21.01 | 5.67 | 21.01 | 5.67 | 21.01 |
Annual Sum or Average | 8454.17 | 21.65 | 172.00 | 21.66 | 95.33 | 21.66 |
Minimum of Months | 595.50 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 22.68 | 48.50 | 22.73 | 48.50 | 22.73 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.65648 | 34.98073 | -0.0414 | 5.14774 |
February | 672.00000 | 22.44879 | 36.19758 | -0.0865 | 5.29861 |
March | 744.00000 | 22.22129 | 36.90972 | -0.1392 | 5.55849 |
April | 720.00000 | 22.09718 | 40.66278 | -0.1477 | 5.61402 |
May | 744.00000 | 22.19058 | 44.72565 | -1.1908 | 34.92887 |
June | 720.00000 | 22.37989 | 47.10753 | -1.1065 | 30.97911 |
July | 744.00000 | 22.62382 | 51.10426 | -0.9916 | 25.96252 |
August | 744.00000 | 22.83755 | 54.81272 | -0.8901 | 21.89359 |
September | 720.00000 | 23.11344 | 50.57615 | -0.8176 | 19.32291 |
October | 744.00000 | 23.33592 | 41.25861 | 0.17682 | 5.76346 |
November | 720.00000 | 23.39671 | 39.61646 | 0.18027 | 5.79224 |
December | 744.00000 | 23.07699 | 35.77595 | 0.07181 | 5.22089 |
Annual Sum or Average | 8760.00000 | 22.69974 | 42.84662 | -0.4173 | 14.35165 |
Minimum of Months | 672.00000 | 22.09718 | 34.98073 | -1.1908 | 5.14774 |
Maximum of Months | 744.00000 | 23.39671 | 54.81272 | 0.18027 | 34.92887 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.04339 | 35.47278 | -0.4913 | 10.31241 |
February | 672.00000 | 21.16545 | 36.24392 | -0.4015 | 9.21141 |
March | 744.00000 | 21.23699 | 36.49823 | -0.3382 | 8.26005 |
April | 720.00000 | 21.33827 | 39.96131 | -0.2507 | 7.40835 |
May | 744.00000 | 21.39549 | 44.31341 | -1.3087 | 42.05929 |
June | 720.00000 | 21.40148 | 47.32384 | -1.2626 | 39.33123 |
July | 744.00000 | 21.73277 | 51.19347 | -1.0903 | 32.09351 |
August | 744.00000 | 21.88146 | 55.32071 | -1.0064 | 29.31883 |
September | 720.00000 | 21.69414 | 52.16755 | -1.1253 | 34.98090 |
October | 744.00000 | 21.36225 | 43.37507 | -0.2343 | 7.38405 |
November | 720.00000 | 21.08906 | 42.12621 | -0.3924 | 8.79401 |
December | 744.00000 | 21.08843 | 37.09470 | -0.4602 | 9.88514 |
Annual Sum or Average | 8760.00000 | 21.37064 | 43.46169 | -0.6986 | 19.97826 |
Minimum of Months | 672.00000 | 21.04339 | 35.47278 | -1.3087 | 7.38405 |
Maximum of Months | 744.00000 | 21.88146 | 55.32071 | -0.2343 | 42.05929 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.56760 | 37.28823 | -0.2848 | 6.95256 |
February | 672.00000 | 21.83526 | 37.68878 | -0.2088 | 6.34357 |
March | 744.00000 | 22.16378 | 37.51582 | -0.1211 | 5.66508 |
April | 720.00000 | 22.45436 | 40.40458 | -0.0241 | 5.48973 |
May | 744.00000 | 22.71782 | 44.05915 | -0.9544 | 24.86826 |
June | 720.00000 | 22.85372 | 46.49914 | -0.8858 | 22.19403 |
July | 744.00000 | 23.14023 | 50.23020 | -0.7515 | 17.54957 |
August | 744.00000 | 23.18891 | 54.25890 | -0.7057 | 16.16963 |
September | 720.00000 | 22.96310 | 51.44318 | -0.8121 | 19.76444 |
October | 744.00000 | 22.47422 | 43.60275 | 0.00052 | 5.38525 |
November | 720.00000 | 21.91485 | 43.05080 | -0.1545 | 5.92462 |
December | 744.00000 | 21.68103 | 38.75546 | -0.2462 | 6.53068 |
Annual Sum or Average | 8760.00000 | 22.41619 | 43.76505 | -0.4304 | 11.93303 |
Minimum of Months | 672.00000 | 21.56760 | 37.28823 | -0.9544 | 5.38525 |
Maximum of Months | 744.00000 | 23.18891 | 54.25890 | 0.00052 | 24.86826 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.76344 | 30.43159 | 0.56560 | 14.57077 |
February | 672.00000 | 22.79358 | 31.23335 | 0.59217 | 15.24648 |
March | 744.00000 | 22.81475 | 31.51112 | 0.61936 | 15.91747 |
April | 720.00000 | 22.82667 | 34.89560 | 0.66165 | 17.02519 |
May | 744.00000 | 22.82848 | 39.00002 | -0.0408 | 10.82269 |
June | 720.00000 | 22.83383 | 41.72261 | 0.00050 | 10.87218 |
July | 744.00000 | 22.84427 | 46.23194 | 0.04479 | 10.72463 |
August | 744.00000 | 22.84650 | 50.47343 | 0.08192 | 10.87000 |
September | 720.00000 | 22.84824 | 46.97434 | 0.02989 | 10.76072 |
October | 744.00000 | 22.84973 | 37.92753 | 0.68228 | 17.54068 |
November | 720.00000 | 22.81783 | 36.38716 | 0.63894 | 16.42548 |
December | 744.00000 | 22.77733 | 31.92075 | 0.58253 | 14.93613 |
Annual Sum or Average | 8760.00000 | 22.82048 | 38.26387 | 0.37018 | 13.79798 |
Minimum of Months | 672.00000 | 22.76344 | 30.43159 | -0.0408 | 10.72463 |
Maximum of Months | 744.00000 | 22.84973 | 50.47343 | 0.68228 | 17.54068 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.36331 | 39.58216 | -0.3076 | 7.42013 |
February | 672.00000 | 21.65737 | 39.99948 | -0.1877 | 6.77042 |
March | 744.00000 | 21.90556 | 40.03400 | -0.0939 | 6.14387 |
April | 720.00000 | 22.11157 | 43.15422 | 0.00741 | 5.98435 |
May | 744.00000 | 22.23357 | 47.20574 | -0.9486 | 25.45147 |
June | 720.00000 | 22.32904 | 49.84016 | -0.8800 | 22.33592 |
July | 744.00000 | 22.61630 | 53.70072 | -0.7267 | 17.46764 |
August | 744.00000 | 22.74720 | 57.65980 | -0.6437 | 15.81339 |
September | 720.00000 | 22.56947 | 54.56874 | -0.7526 | 19.89825 |
October | 744.00000 | 22.14826 | 46.35196 | 0.03009 | 6.22649 |
November | 720.00000 | 21.58061 | 45.72854 | -0.1802 | 6.51228 |
December | 744.00000 | 21.45043 | 41.14402 | -0.2690 | 7.12163 |
Annual Sum or Average | 8760.00000 | 22.06173 | 46.61579 | -0.4141 | 12.29172 |
Minimum of Months | 672.00000 | 21.36331 | 39.58216 | -0.9486 | 5.98435 |
Maximum of Months | 744.00000 | 22.74720 | 57.65980 | 0.03009 | 25.45147 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.00800 | 38.96377 | -0.1477 | 5.95539 |
February | 672.00000 | 22.28942 | 39.33914 | -0.0636 | 5.70488 |
March | 744.00000 | 22.57819 | 39.27776 | 0.01969 | 5.52766 |
April | 720.00000 | 22.80472 | 42.23024 | 0.10582 | 5.74542 |
May | 744.00000 | 22.99342 | 45.96736 | -0.7985 | 19.18721 |
June | 720.00000 | 23.11321 | 48.39445 | -0.7310 | 16.97861 |
July | 744.00000 | 23.30102 | 52.29420 | -0.6257 | 13.83632 |
August | 744.00000 | 23.35782 | 56.19295 | -0.5747 | 12.55599 |
September | 720.00000 | 23.21246 | 53.24917 | -0.6597 | 15.06327 |
October | 744.00000 | 22.85743 | 45.26007 | 0.13877 | 5.91294 |
November | 720.00000 | 22.33473 | 44.64961 | -0.0168 | 5.66683 |
December | 744.00000 | 22.11375 | 40.41766 | -0.1095 | 5.76440 |
Annual Sum or Average | 8760.00000 | 22.74947 | 45.55284 | -0.2900 | 9.84739 |
Minimum of Months | 672.00000 | 22.00800 | 38.96377 | -0.7985 | 5.52766 |
Maximum of Months | 744.00000 | 23.35782 | 56.19295 | 0.13877 | 19.18721 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.80574 | 50.94821 | -0.5371 | 11.33520 |
February | 672.00000 | 21.07558 | 50.80707 | -0.4353 | 9.61913 |
March | 744.00000 | 21.28190 | 50.49535 | -0.3429 | 8.07304 |
April | 720.00000 | 21.51176 | 51.86014 | -0.2240 | 6.94716 |
May | 744.00000 | 21.63000 | 53.53360 | -1.2614 | 39.65277 |
June | 720.00000 | 21.67179 | 54.07328 | -1.2128 | 37.20926 |
July | 744.00000 | 21.70511 | 53.68643 | -1.1403 | 34.00585 |
August | 744.00000 | 21.69907 | 55.83455 | -1.1386 | 33.90146 |
September | 720.00000 | 21.61575 | 57.56734 | -1.2185 | 37.56825 |
October | 744.00000 | 21.38583 | 55.86227 | -0.2556 | 7.08441 |
November | 720.00000 | 21.00932 | 55.89444 | -0.4229 | 9.23477 |
December | 744.00000 | 20.87415 | 52.16101 | -0.5069 | 10.85513 |
Annual Sum or Average | 8760.00000 | 21.35674 | 53.56882 | -0.7266 | 20.52127 |
Minimum of Months | 672.00000 | 20.80574 | 50.49535 | -1.2614 | 6.94716 |
Maximum of Months | 744.00000 | 21.70511 | 57.56734 | -0.2240 | 39.65277 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.65169 | 51.40147 | -0.5847 | 12.47752 |
February | 672.00000 | 20.85992 | 51.44447 | -0.5068 | 10.83348 |
March | 744.00000 | 21.10384 | 50.99160 | -0.4083 | 8.81195 |
April | 720.00000 | 21.49295 | 52.05109 | -0.2540 | 7.25997 |
May | 744.00000 | 22.02452 | 52.94321 | -1.1734 | 37.71039 |
June | 720.00000 | 22.21530 | 52.86565 | -1.0768 | 32.86429 |
July | 744.00000 | 22.53893 | 52.22486 | -0.9224 | 28.34157 |
August | 744.00000 | 22.25494 | 55.46598 | -1.0070 | 29.36922 |
September | 720.00000 | 22.06933 | 57.47801 | -1.1268 | 34.94573 |
October | 744.00000 | 21.27898 | 56.41857 | -0.3088 | 7.50920 |
November | 720.00000 | 20.87269 | 56.46502 | -0.4684 | 9.97907 |
December | 744.00000 | 20.70293 | 52.66795 | -0.5611 | 11.89753 |
Annual Sum or Average | 8760.00000 | 21.50909 | 53.53907 | -0.7011 | 19.38205 |
Minimum of Months | 672.00000 | 20.65169 | 50.99160 | -1.1734 | 7.25997 |
Maximum of Months | 744.00000 | 22.53893 | 57.47801 | -0.2540 | 37.71039 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.04093 | 46.57164 | -0.4519 | 9.34203 |
February | 672.00000 | 21.13329 | 46.95109 | -0.4151 | 8.77893 |
March | 744.00000 | 21.27753 | 46.66745 | -0.3567 | 7.75735 |
April | 720.00000 | 21.47745 | 48.44215 | -0.2766 | 6.90687 |
May | 744.00000 | 21.72417 | 50.14621 | -1.3260 | 42.19667 |
June | 720.00000 | 21.91930 | 50.56674 | -1.2383 | 37.93744 |
July | 744.00000 | 22.05678 | 52.10821 | -1.1699 | 34.85209 |
August | 744.00000 | 21.97147 | 54.72804 | -1.1876 | 35.48556 |
September | 720.00000 | 21.74827 | 55.12814 | -1.2908 | 40.36454 |
October | 744.00000 | 21.35658 | 52.33908 | -0.2919 | 6.89467 |
November | 720.00000 | 21.18305 | 51.64974 | -0.3647 | 7.92240 |
December | 744.00000 | 21.05830 | 47.96234 | -0.4379 | 9.06222 |
Annual Sum or Average | 8760.00000 | 21.49762 | 50.28615 | -0.7359 | 20.69331 |
Minimum of Months | 672.00000 | 21.04093 | 46.57164 | -1.3260 | 6.89467 |
Maximum of Months | 744.00000 | 22.05678 | 55.12814 | -0.2766 | 42.19667 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.79276 | 50.96305 | -0.5403 | 11.36490 |
February | 672.00000 | 21.09279 | 50.78291 | -0.4321 | 9.50153 |
March | 744.00000 | 21.33963 | 50.31019 | -0.3288 | 7.92870 |
April | 720.00000 | 21.58598 | 51.38572 | -0.2041 | 6.86943 |
May | 744.00000 | 21.64561 | 53.24514 | -1.2717 | 40.15517 |
June | 720.00000 | 21.70628 | 53.35867 | -1.1947 | 36.46493 |
July | 744.00000 | 21.71756 | 53.69703 | -1.1581 | 34.84067 |
August | 744.00000 | 21.71912 | 55.32952 | -1.1351 | 33.80383 |
September | 720.00000 | 21.61765 | 57.65410 | -1.2307 | 38.17329 |
October | 744.00000 | 21.41436 | 55.57705 | -0.2509 | 7.07448 |
November | 720.00000 | 21.00641 | 55.87243 | -0.4233 | 9.21186 |
December | 744.00000 | 20.85939 | 52.20057 | -0.5100 | 10.85429 |
Annual Sum or Average | 8760.00000 | 21.37597 | 53.37273 | -0.7253 | 20.58716 |
Minimum of Months | 672.00000 | 20.79276 | 50.31019 | -1.2717 | 6.86943 |
Maximum of Months | 744.00000 | 21.71912 | 57.65410 | -0.2041 | 40.15517 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.63765 | 51.42868 | -0.5885 | 12.59901 |
February | 672.00000 | 20.85467 | 51.43826 | -0.5083 | 10.77282 |
March | 744.00000 | 21.15804 | 50.79452 | -0.3953 | 8.51365 |
April | 720.00000 | 21.56652 | 51.68183 | -0.2337 | 6.97203 |
May | 744.00000 | 21.84192 | 53.08763 | -1.2407 | 38.74375 |
June | 720.00000 | 22.11757 | 52.62409 | -1.0961 | 32.38234 |
July | 744.00000 | 22.28164 | 53.13106 | -1.0170 | 29.56881 |
August | 744.00000 | 22.24556 | 55.09390 | -1.0107 | 29.33387 |
September | 720.00000 | 21.87073 | 58.16687 | -1.1976 | 36.68988 |
October | 744.00000 | 21.29342 | 56.20525 | -0.3073 | 7.40266 |
November | 720.00000 | 20.85765 | 56.47985 | -0.4713 | 10.01113 |
December | 744.00000 | 20.68126 | 52.71454 | -0.5659 | 12.01370 |
Annual Sum or Average | 8760.00000 | 21.45378 | 53.57527 | -0.7208 | 19.63490 |
Minimum of Months | 672.00000 | 20.63765 | 50.79452 | -1.2407 | 6.97203 |
Maximum of Months | 744.00000 | 22.28164 | 58.16687 | -0.2337 | 38.74375 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.67235 | 52.74778 | -0.5959 | 12.83734 |
February | 672.00000 | 20.96380 | 52.52042 | -0.4839 | 10.72205 |
March | 744.00000 | 21.20460 | 52.18945 | -0.3755 | 8.70898 |
April | 720.00000 | 21.47302 | 53.21812 | -0.2402 | 7.28026 |
May | 744.00000 | 21.60809 | 54.70115 | -1.2750 | 40.58859 |
June | 720.00000 | 21.65963 | 54.96046 | -1.2169 | 37.64510 |
July | 744.00000 | 21.69527 | 54.63921 | -1.1372 | 34.13247 |
August | 744.00000 | 21.68611 | 57.11863 | -1.1399 | 34.21151 |
September | 720.00000 | 21.58344 | 59.31843 | -1.2340 | 38.55462 |
October | 744.00000 | 21.31836 | 57.69234 | -0.2839 | 7.52184 |
November | 720.00000 | 20.90035 | 58.00938 | -0.4669 | 10.20208 |
December | 744.00000 | 20.76622 | 53.98307 | -0.5588 | 12.11038 |
Annual Sum or Average | 8760.00000 | 21.29578 | 55.09859 | -0.7524 | 21.27157 |
Minimum of Months | 672.00000 | 20.67235 | 52.18945 | -1.2750 | 7.28026 |
Maximum of Months | 744.00000 | 21.69527 | 59.31843 | -0.2402 | 40.58859 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.54610 | 53.14482 | -0.6397 | 14.01179 |
February | 672.00000 | 20.74544 | 53.21622 | -0.5580 | 12.12850 |
March | 744.00000 | 21.01625 | 52.74080 | -0.4453 | 9.58648 |
April | 720.00000 | 21.46939 | 53.43216 | -0.2681 | 7.66675 |
May | 744.00000 | 22.08312 | 54.00502 | -1.1593 | 38.52213 |
June | 720.00000 | 22.29171 | 53.46503 | -1.0491 | 32.88070 |
July | 744.00000 | 22.64689 | 52.53013 | -0.8774 | 28.52533 |
August | 744.00000 | 22.27847 | 56.39233 | -0.9943 | 29.63025 |
September | 720.00000 | 22.11612 | 58.90928 | -1.1170 | 35.66751 |
October | 744.00000 | 21.19881 | 58.39712 | -0.3416 | 8.07383 |
November | 720.00000 | 20.75766 | 58.64046 | -0.5149 | 11.09324 |
December | 744.00000 | 20.59660 | 54.53231 | -0.6143 | 13.30450 |
Annual Sum or Average | 8760.00000 | 21.48294 | 54.95200 | -0.7159 | 20.13734 |
Minimum of Months | 672.00000 | 20.54610 | 52.53013 | -1.1593 | 7.66675 |
Maximum of Months | 744.00000 | 22.64689 | 58.90928 | -0.2681 | 38.52213 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.06954 | 50.33481 | -0.4546 | 9.97563 |
February | 672.00000 | 21.30999 | 50.29096 | -0.3472 | 8.61039 |
March | 744.00000 | 21.45124 | 50.03410 | -0.2759 | 7.61772 |
April | 720.00000 | 21.60143 | 51.42508 | -0.1943 | 6.95782 |
May | 744.00000 | 21.64133 | 53.30477 | -1.2835 | 40.93436 |
June | 720.00000 | 21.67469 | 53.89886 | -1.2418 | 38.77623 |
July | 744.00000 | 21.69128 | 54.07363 | -1.1936 | 36.62490 |
August | 744.00000 | 21.69063 | 55.89163 | -1.1693 | 35.52078 |
September | 720.00000 | 21.63846 | 57.05221 | -1.2150 | 37.80042 |
October | 744.00000 | 21.52027 | 54.68044 | -0.2003 | 6.87951 |
November | 720.00000 | 21.22743 | 54.81972 | -0.3511 | 8.35344 |
December | 744.00000 | 21.10562 | 51.55963 | -0.4270 | 9.74539 |
Annual Sum or Average | 8760.00000 | 21.46906 | 53.12403 | -0.6984 | 20.72322 |
Minimum of Months | 672.00000 | 21.06954 | 50.03410 | -1.2835 | 6.87951 |
Maximum of Months | 744.00000 | 21.69128 | 57.05221 | -0.1943 | 40.93436 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.40802 | 38.95933 | 0.20753 | 6.45587 |
February | 672.00000 | 23.49524 | 39.43838 | 0.24458 | 6.80699 |
March | 744.00000 | 23.62388 | 39.28766 | 0.29849 | 7.21685 |
April | 720.00000 | 23.74824 | 42.01525 | 0.37186 | 8.14757 |
May | 744.00000 | 23.84771 | 45.33406 | -0.4369 | 9.22693 |
June | 720.00000 | 23.88502 | 47.56004 | -0.3813 | 8.21330 |
July | 744.00000 | 23.91719 | 51.51753 | -0.3227 | 7.32684 |
August | 744.00000 | 23.89821 | 55.53764 | -0.3037 | 7.06430 |
September | 720.00000 | 23.83000 | 52.85342 | -0.3875 | 8.41371 |
October | 744.00000 | 23.68460 | 45.13935 | 0.36688 | 8.07735 |
November | 720.00000 | 23.53779 | 44.22533 | 0.29750 | 7.33669 |
December | 744.00000 | 23.44358 | 40.37727 | 0.22819 | 6.59545 |
Annual Sum or Average | 8760.00000 | 23.69429 | 45.21818 | 0.01380 | 7.57481 |
Minimum of Months | 672.00000 | 23.40802 | 38.95933 | -0.4369 | 6.45587 |
Maximum of Months | 744.00000 | 23.91719 | 55.53764 | 0.37186 | 9.22693 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.61684 | 37.77155 | 0.29853 | 7.22406 |
February | 672.00000 | 23.68717 | 38.28312 | 0.33105 | 7.66780 |
March | 744.00000 | 23.78974 | 38.18715 | 0.37767 | 8.19694 |
April | 720.00000 | 23.87407 | 40.98292 | 0.43984 | 9.20031 |
May | 744.00000 | 23.92636 | 44.43143 | -0.3581 | 7.81646 |
June | 720.00000 | 23.94426 | 46.76091 | -0.3124 | 7.14189 |
July | 744.00000 | 23.96159 | 50.79896 | -0.2624 | 6.54923 |
August | 744.00000 | 23.94794 | 54.80350 | -0.2423 | 6.31299 |
September | 720.00000 | 23.91092 | 51.95628 | -0.3108 | 7.17842 |
October | 744.00000 | 23.82692 | 44.04659 | 0.43903 | 9.18035 |
November | 720.00000 | 23.72361 | 43.02521 | 0.38242 | 8.37671 |
December | 744.00000 | 23.64462 | 39.16683 | 0.31729 | 7.42932 |
Annual Sum or Average | 8760.00000 | 23.82181 | 44.21664 | 0.09014 | 7.68660 |
Minimum of Months | 672.00000 | 23.61684 | 37.77155 | -0.3581 | 6.31299 |
Maximum of Months | 744.00000 | 23.96159 | 54.80350 | 0.43984 | 9.20031 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.65533 | 36.50706 | 0.92431 | 25.71299 |
February | 672.00000 | 23.67476 | 37.08258 | 0.95624 | 27.02465 |
March | 744.00000 | 23.72060 | 37.20127 | 1.00037 | 28.51808 |
April | 720.00000 | 23.75558 | 40.17417 | 1.06638 | 31.36296 |
May | 744.00000 | 23.78907 | 43.86935 | 0.53750 | 16.47369 |
June | 720.00000 | 23.82661 | 46.27685 | 0.60478 | 17.72596 |
July | 744.00000 | 23.84488 | 50.37427 | 0.65923 | 19.20824 |
August | 744.00000 | 23.85843 | 54.17954 | 0.69315 | 19.90450 |
September | 720.00000 | 23.81877 | 51.14538 | 0.60646 | 17.74640 |
October | 744.00000 | 23.75560 | 43.04116 | 1.06523 | 31.13925 |
November | 720.00000 | 23.70490 | 41.82586 | 1.00257 | 28.68810 |
December | 744.00000 | 23.66412 | 37.86554 | 0.94084 | 26.28975 |
Annual Sum or Average | 8760.00000 | 23.75616 | 43.32922 | 0.83731 | 24.12886 |
Minimum of Months | 672.00000 | 23.65533 | 36.50706 | 0.53750 | 16.47369 |
Maximum of Months | 744.00000 | 23.85843 | 54.17954 | 1.06638 | 31.36296 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00443 | 35.29431 | -0.4718 | 9.68678 |
February | 672.00000 | 21.06488 | 36.14018 | -0.4411 | 9.19865 |
March | 744.00000 | 21.20304 | 36.25176 | -0.3911 | 8.29858 |
April | 720.00000 | 21.58443 | 39.08477 | -0.2774 | 6.90190 |
May | 744.00000 | 22.09509 | 42.31347 | -1.2285 | 36.88258 |
June | 720.00000 | 22.43210 | 44.36836 | -1.0968 | 30.58250 |
July | 744.00000 | 22.79768 | 47.97030 | -0.9441 | 24.09465 |
August | 744.00000 | 22.89721 | 51.98693 | -0.8833 | 21.76902 |
September | 720.00000 | 22.42107 | 49.82261 | -1.0660 | 29.34444 |
October | 744.00000 | 21.69976 | 42.31763 | -0.2289 | 6.29831 |
November | 720.00000 | 21.17212 | 41.66778 | -0.3737 | 8.13599 |
December | 744.00000 | 21.00808 | 36.97126 | -0.4554 | 9.35287 |
Annual Sum or Average | 8760.00000 | 21.78623 | 42.04522 | -0.6561 | 16.75171 |
Minimum of Months | 672.00000 | 21.00443 | 35.29431 | -1.2285 | 6.29831 |
Maximum of Months | 744.00000 | 22.89721 | 51.98693 | -0.2289 | 36.88258 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00083 | 39.04800 | -0.4685 | 9.61132 |
February | 672.00000 | 21.03041 | 39.95377 | -0.4421 | 9.16074 |
March | 744.00000 | 21.15135 | 40.13134 | -0.3978 | 8.36703 |
April | 720.00000 | 21.50409 | 43.04105 | -0.2880 | 7.02265 |
May | 744.00000 | 22.09184 | 46.16730 | -1.2255 | 36.72345 |
June | 720.00000 | 22.38298 | 48.35357 | -1.1088 | 31.13504 |
July | 744.00000 | 22.78009 | 51.91206 | -0.9447 | 24.17648 |
August | 744.00000 | 22.89582 | 55.91853 | -0.8780 | 21.59954 |
September | 720.00000 | 22.39177 | 53.73852 | -1.0709 | 29.78955 |
October | 744.00000 | 21.48503 | 46.56360 | -0.2736 | 6.83309 |
November | 720.00000 | 21.04168 | 45.72308 | -0.4051 | 8.51983 |
December | 744.00000 | 21.00332 | 40.73139 | -0.4551 | 9.34695 |
Annual Sum or Average | 8760.00000 | 21.73459 | 45.96995 | -0.6644 | 16.89563 |
Minimum of Months | 672.00000 | 21.00083 | 39.04800 | -1.2255 | 6.83309 |
Maximum of Months | 744.00000 | 22.89582 | 55.91853 | -0.2736 | 36.72345 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00191 | 36.07525 | -0.4638 | 9.52777 |
February | 672.00000 | 21.05257 | 36.92883 | -0.4288 | 8.97273 |
March | 744.00000 | 21.17378 | 37.09407 | -0.3766 | 8.07955 |
April | 720.00000 | 21.54033 | 39.95588 | -0.2564 | 6.83358 |
May | 744.00000 | 22.03471 | 43.20650 | -1.1960 | 35.64746 |
June | 720.00000 | 22.41984 | 45.14710 | -1.0432 | 28.51666 |
July | 744.00000 | 22.80054 | 48.68582 | -0.8812 | 22.15285 |
August | 744.00000 | 22.83615 | 52.88934 | -0.8416 | 20.79942 |
September | 720.00000 | 22.24661 | 51.03164 | -1.0697 | 30.14034 |
October | 744.00000 | 21.39617 | 43.73998 | -0.2738 | 6.84242 |
November | 720.00000 | 21.06175 | 42.68268 | -0.3881 | 8.30412 |
December | 744.00000 | 21.01034 | 37.74546 | -0.4484 | 9.22526 |
Annual Sum or Average | 8760.00000 | 21.71888 | 42.96179 | -0.6401 | 16.28930 |
Minimum of Months | 672.00000 | 21.00191 | 36.07525 | -1.1960 | 6.83358 |
Maximum of Months | 744.00000 | 22.83615 | 52.88934 | -0.2564 | 35.64746 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.05246 | 34.64682 | -0.4532 | 9.34522 |
February | 672.00000 | 21.15930 | 35.38070 | -0.4153 | 8.78675 |
March | 744.00000 | 21.40813 | 35.27399 | -0.3450 | 7.62951 |
April | 720.00000 | 21.80207 | 38.04313 | -0.2295 | 6.40979 |
May | 744.00000 | 22.30810 | 41.23064 | -1.1601 | 33.61726 |
June | 720.00000 | 22.62938 | 43.28540 | -1.0328 | 27.80067 |
July | 744.00000 | 22.98647 | 46.86928 | -0.8821 | 21.75131 |
August | 744.00000 | 23.08622 | 50.83376 | -0.8212 | 19.56523 |
September | 720.00000 | 22.63175 | 48.64224 | -0.9978 | 26.43638 |
October | 744.00000 | 21.93827 | 41.17490 | -0.1762 | 5.86122 |
November | 720.00000 | 21.32694 | 40.73234 | -0.3360 | 7.63928 |
December | 744.00000 | 21.07337 | 36.29239 | -0.4340 | 8.96929 |
Annual Sum or Average | 8760.00000 | 21.95509 | 41.06227 | -0.6081 | 15.35212 |
Minimum of Months | 672.00000 | 21.05246 | 34.64682 | -1.1601 | 5.86122 |
Maximum of Months | 744.00000 | 23.08622 | 50.83376 | -0.1762 | 33.61726 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.999183E+09 | 9374.52 | 11-JAN-16:03 | 147.63 | 0.318366E+10 | 0.00 | 0.418284E+10 | 0.63 | 3.19 | 02-JAN-20:00 | 0.00 | 0.00 |
February | 0.457591E+10 | 59323.50 | 27-FEB-16:02 | 275.76 | 0.143288E+11 | 0.00 | 0.189047E+11 | 1.30 | 3.62 | 27-FEB-16:02 | 0.00 | 0.00 |
March | 0.110277E+11 | 65659.33 | 18-MAR-15:03 | 508.62 | 0.347308E+11 | 0.00 | 0.457585E+11 | 2.17 | 3.76 | 18-MAR-15:03 | 0.00 | 0.00 |
April | 0.272319E+11 | 102415.39 | 27-APR-15:03 | 661.79 | 0.857904E+11 | 0.00 | 0.113022E+12 | 2.91 | 3.85 | 29-APR-15:03 | 0.00 | 0.00 |
May | 0.436649E+11 | 89903.71 | 04-MAY-15:03 | 738.89 | 0.137283E+12 | 0.00 | 0.180948E+12 | 3.13 | 3.86 | 03-MAY-15:03 | 0.00 | 0.00 |
June | 0.629446E+11 | 101748.11 | 28-JUN-18:03 | 720.00 | 0.195988E+12 | 0.00 | 0.258933E+12 | 3.11 | 3.81 | 09-JUN-15:03 | 0.00 | 0.00 |
July | 0.929743E+11 | 123591.78 | 24-JUL-18:03 | 744.00 | 0.296277E+12 | 0.00 | 0.389251E+12 | 3.13 | 3.94 | 11-JUL-15:03 | 0.00 | 0.00 |
August | 0.108582E+12 | 141050.59 | 10-AUG-18:03 | 744.00 | 0.349327E+12 | 0.00 | 0.457909E+12 | 3.14 | 3.95 | 24-AUG-21:52 | 0.00 | 0.00 |
September | 0.561459E+11 | 98728.06 | 14-SEP-15:03 | 712.67 | 0.179162E+12 | 0.00 | 0.235308E+12 | 3.12 | 3.90 | 22-SEP-15:03 | 0.00 | 0.00 |
October | 0.208812E+11 | 75931.14 | 04-OCT-15:03 | 647.86 | 0.650093E+11 | 0.00 | 0.858906E+11 | 2.75 | 3.85 | 04-OCT-15:03 | 0.00 | 0.00 |
November | 0.556774E+10 | 74095.22 | 04-NOV-15:03 | 329.11 | 0.174768E+11 | 0.00 | 0.230445E+11 | 1.45 | 3.90 | 04-NOV-15:03 | 0.00 | 0.00 |
December | 0.179002E+10 | 14394.35 | 05-DEC-12:30 | 171.71 | 0.570379E+10 | 0.00 | 0.749381E+10 | 0.74 | 3.19 | 05-DEC-11:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.436385E+12 | 6402.04 | 0.138426E+13 | 0.00 | 0.182065E+13 | 2.30 | 0.00 | 0.00 | ||||
Minimum of Months | 0.999183E+09 | 9374.52 | 147.63 | 0.318366E+10 | 0.00 | 0.418284E+10 | 0.63 | 3.19 | 0.00 | 0.00 | ||
Maximum of Months | 0.108582E+12 | 141050.59 | 744.00 | 0.349327E+12 | 0.00 | 0.457909E+12 | 3.14 | 3.95 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.776982E+11 | 0.00 | 744.00 | 173278.78 | 26-JAN-19:03 | 0.00 | 49.54 | 80.33 | 0.22 | 0.00 | 0.08 | 0.47 | 26-JAN-19:03 |
February | 0.739232E+11 | 0.00 | 663.76 | 157562.30 | 15-FEB-16:01 | 0.00 | 47.15 | 79.57 | 0.21 | 0.00 | 0.08 | 0.43 | 15-FEB-16:01 |
March | 0.833860E+11 | 0.00 | 724.22 | 131915.19 | 07-MAR-09:02 | 0.00 | 43.98 | 78.39 | 0.18 | 0.00 | 0.09 | 0.36 | 07-MAR-09:02 |
April | 0.786185E+11 | 0.00 | 606.76 | 120914.30 | 06-APR-08:05 | 0.00 | 37.02 | 71.47 | 0.16 | 0.00 | 0.08 | 0.33 | 06-APR-08:05 |
May | 0.717211E+11 | 0.00 | 525.49 | 122012.91 | 28-MAY-08:04 | 0.00 | 30.82 | 63.74 | 0.13 | 0.00 | 0.07 | 0.33 | 28-MAY-08:04 |
June | 0.408395E+11 | 0.00 | 386.47 | 88682.43 | 01-JUN-04:20 | 0.00 | 26.20 | 54.41 | 0.07 | 0.00 | 0.04 | 0.24 | 01-JUN-04:20 |
July | 0.155116E+11 | 0.00 | 260.00 | 57158.19 | 19-JUL-05:00 | 0.00 | 25.51 | 44.48 | 0.03 | 0.00 | 0.02 | 0.16 | 19-JUL-05:00 |
August | 0.119682E+11 | 0.00 | 219.60 | 67955.28 | 01-AUG-08:04 | 0.00 | 28.82 | 44.26 | 0.02 | 0.00 | 0.01 | 0.19 | 01-AUG-08:04 |
September | 0.423344E+11 | 0.00 | 422.82 | 113298.88 | 28-SEP-08:05 | 0.00 | 27.50 | 57.79 | 0.08 | 0.00 | 0.04 | 0.31 | 28-SEP-08:05 |
October | 0.104700E+12 | 0.00 | 651.03 | 137740.61 | 22-OCT-08:07 | 0.00 | 34.91 | 73.17 | 0.21 | 0.00 | 0.11 | 0.38 | 22-OCT-08:07 |
November | 0.841497E+11 | 0.00 | 705.33 | 163277.69 | 26-NOV-19:03 | 0.00 | 44.22 | 79.00 | 0.21 | 0.00 | 0.09 | 0.45 | 26-NOV-19:03 |
December | 0.806980E+11 | 0.00 | 744.00 | 155543.95 | 31-DEC-19:03 | 0.00 | 48.61 | 80.18 | 0.22 | 0.00 | 0.08 | 0.43 | 31-DEC-19:03 |
Annual Sum or Average | 0.765549E+12 | 0.00 | 6653.48 | 0.00 | 36.98 | 67.15 | 0.14 | 0.00 | 0.07 | ||||
Minimum of Months | 0.119682E+11 | 0.00 | 219.60 | 57158.19 | 0.00 | 25.51 | 44.26 | 0.02 | 0.00 | 0.01 | 0.16 | ||
Maximum of Months | 0.104700E+12 | 0.00 | 744.00 | 173278.78 | 0.00 | 49.54 | 80.33 | 0.22 | 0.00 | 0.11 | 0.47 |
Report: DXReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.542296E+11 | 0.00 | 444.32 | 0.542296E+11 | 0.00 | 0.00 | 1.00 | 01-JAN-06:15 | 0.00 | 01-JAN-00:10 | 41889.89 | 31-JAN-11:15 | 41889.89 | 31-JAN-00:07 | 0.00 | 01-JAN-21:50 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.500762E+11 | 0.00 | 396.19 | 0.500762E+11 | 0.00 | 0.00 | 1.00 | 01-FEB-00:07 | 0.00 | 01-FEB-00:03 | 43800.54 | 11-FEB-17:05 | 43800.54 | 11-FEB-06:05 | 0.00 | 01-FEB-08:50 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 0.558722E+11 | 0.00 | 426.74 | 0.558722E+11 | 0.00 | 0.00 | 1.00 | 01-MAR-00:20 | 0.00 | 01-MAR-00:03 | 50231.45 | 31-MAR-23:07 | 50231.45 | 31-MAR-23:07 | 0.00 | 21-MAR-22:10 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 0.534427E+11 | 0.00 | 401.20 | 0.534407E+11 | 1996751.41 | 0.00 | 1.00 | 01-APR-05:05 | 0.00 | 01-APR-00:20 | 50219.24 | 01-APR-05:05 | 50219.24 | 01-APR-13:05 | 2262.43 | 30-APR-23:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.537667E+11 | 0.00 | 396.17 | 0.512887E+11 | 0.247798E+10 | 0.00 | 1.00 | 01-MAY-05:15 | 0.00 | 01-MAY-00:05 | 54991.61 | 31-MAY-23:07 | 52046.76 | 31-MAY-23:07 | 2944.85 | 31-MAY-23:07 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.504844E+11 | 0.00 | 373.36 | 0.480193E+11 | 0.246513E+10 | 0.00 | 1.00 | 01-JUN-04:10 | 0.00 | 01-JUN-00:05 | 54974.02 | 01-JUN-05:50 | 52292.24 | 02-JUN-07:00 | 3587.04 | 30-JUN-23:20 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.510583E+11 | 0.00 | 376.12 | 0.469310E+11 | 0.412723E+10 | 0.00 | 1.00 | 01-JUL-05:15 | 0.00 | 01-JUL-00:10 | 57263.85 | 01-JUL-05:15 | 52704.88 | 01-JUL-20:53 | 5821.03 | 31-JUL-23:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.509452E+11 | 0.00 | 374.83 | 0.441378E+11 | 0.680742E+10 | 0.00 | 1.00 | 01-AUG-05:15 | 0.00 | 01-AUG-00:05 | 58691.65 | 31-AUG-06:15 | 50946.53 | 31-AUG-07:00 | 8183.43 | 31-AUG-08:20 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.492481E+11 | 0.00 | 369.58 | 0.412980E+11 | 0.795013E+10 | 0.00 | 1.00 | 01-SEP-05:15 | 0.00 | 01-SEP-00:05 | 55236.94 | 30-SEP-05:15 | 46354.62 | 30-SEP-15:17 | 9281.32 | 28-SEP-10:37 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.513978E+11 | 0.00 | 399.77 | 0.485292E+11 | 0.286856E+10 | 0.00 | 1.00 | 01-OCT-05:15 | 0.00 | 01-OCT-00:10 | 50508.12 | 31-OCT-07:15 | 47658.50 | 30-OCT-04:10 | 3201.96 | 29-OCT-21:40 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.507322E+11 | 0.00 | 406.54 | 0.486366E+11 | 0.209568E+10 | 0.00 | 1.00 | 01-NOV-05:13 | 0.00 | 01-NOV-00:05 | 46928.66 | 30-NOV-00:07 | 45093.15 | 24-NOV-06:04 | 2262.90 | 27-NOV-09:20 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.532634E+11 | 0.00 | 434.55 | 0.532634E+11 | 0.00 | 0.00 | 1.00 | 01-DEC-00:07 | 0.00 | 01-DEC-00:03 | 43124.35 | 31-DEC-08:40 | 43124.35 | 31-DEC-13:07 | 0.00 | 01-DEC-19:30 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.624517E+12 | 0.00 | 4799.36 | 0.595723E+12 | 0.287941E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.492481E+11 | 0.00 | 369.58 | 0.412980E+11 | 0.00 | 0.00 | 1.00 | 0.00 | 41889.89 | 41889.89 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.558722E+11 | 0.00 | 444.32 | 0.558722E+11 | 0.795013E+10 | 0.00 | 1.00 | 0.00 | 58691.65 | 52704.88 | 9281.32 | 0.00 | 0.00 |
Report: DXReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.420045E+11 | 0.00 | 383.94 | 0.420045E+11 | 0.00 | 0.00 | 1.00 | 01-JAN-17:10 | 0.00 | 01-JAN-00:10 | 53006.54 | 31-JAN-17:30 | 53006.54 | 31-JAN-23:20 | 0.00 | 04-JAN-23:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.397177E+11 | 0.00 | 347.24 | 0.397177E+11 | 0.00 | 0.00 | 1.00 | 01-FEB-17:10 | 0.00 | 01-FEB-00:07 | 55425.87 | 11-FEB-20:30 | 55425.87 | 11-FEB-20:20 | 0.00 | 11-FEB-20:30 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 0.468524E+11 | 0.00 | 383.53 | 0.468524E+11 | 0.00 | 0.00 | 1.00 | 01-MAR-17:10 | 0.00 | 01-MAR-00:07 | 59232.14 | 01-MAR-17:10 | 59232.14 | 01-MAR-17:10 | 0.00 | 05-MAR-21:05 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 0.485431E+11 | 0.00 | 369.89 | 0.485428E+11 | 349802.38 | 0.00 | 1.00 | 01-APR-16:05 | 0.00 | 01-APR-00:10 | 63553.46 | 01-APR-16:05 | 63553.46 | 01-APR-16:05 | 1634.92 | 30-APR-23:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.525437E+11 | 0.00 | 351.83 | 0.501622E+11 | 0.238146E+10 | 0.00 | 1.00 | 01-MAY-16:10 | 0.00 | 01-MAY-00:05 | 66676.24 | 01-MAY-21:40 | 63590.30 | 03-MAY-16:05 | 3494.71 | 06-MAY-21:20 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.530525E+11 | 0.00 | 336.39 | 0.505048E+11 | 0.254769E+10 | 0.00 | 1.00 | 01-JUN-16:05 | 0.00 | 01-JUN-00:05 | 69574.14 | 01-JUN-16:05 | 66196.32 | 02-JUN-23:00 | 3721.72 | 07-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.571922E+11 | 0.00 | 345.78 | 0.526232E+11 | 0.456897E+10 | 0.00 | 1.00 | 01-JUL-16:10 | 0.00 | 01-JUL-00:20 | 72473.60 | 01-JUL-20:05 | 66722.79 | 01-JUL-20:53 | 6202.49 | 10-JUL-18:40 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.586967E+11 | 0.00 | 344.80 | 0.508975E+11 | 0.779922E+10 | 0.00 | 1.00 | 01-AUG-16:10 | 0.00 | 01-AUG-00:05 | 74281.53 | 31-AUG-16:03 | 64496.78 | 31-AUG-16:03 | 10302.69 | 05-AUG-21:20 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.534013E+11 | 0.00 | 340.29 | 0.448002E+11 | 0.860110E+10 | 0.00 | 1.00 | 01-SEP-16:10 | 0.00 | 01-SEP-00:05 | 69907.06 | 30-SEP-16:40 | 58679.85 | 30-SEP-17:00 | 11731.00 | 28-SEP-19:12 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.504090E+11 | 0.00 | 382.18 | 0.476118E+11 | 0.279715E+10 | 0.00 | 1.00 | 01-OCT-16:10 | 0.00 | 01-OCT-00:20 | 63919.25 | 31-OCT-16:10 | 60331.03 | 30-OCT-19:50 | 4045.28 | 30-OCT-19:40 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.453440E+11 | 0.00 | 371.62 | 0.435013E+11 | 0.184263E+10 | 0.00 | 1.00 | 01-NOV-16:10 | 0.00 | 01-NOV-00:05 | 59386.81 | 30-NOV-19:50 | 57006.81 | 25-NOV-17:05 | 2765.01 | 26-NOV-24:00 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.431583E+11 | 0.00 | 382.77 | 0.431583E+11 | 0.00 | 0.00 | 1.00 | 01-DEC-17:10 | 0.00 | 01-DEC-00:07 | 54569.66 | 31-DEC-17:10 | 54569.66 | 31-DEC-18:35 | 0.00 | 12-DEC-20:00 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.590915E+12 | 0.00 | 4340.27 | 0.560377E+12 | 0.305386E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.397177E+11 | 0.00 | 336.39 | 0.397177E+11 | 0.00 | 0.00 | 1.00 | 0.00 | 53006.54 | 53006.54 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.586967E+11 | 0.00 | 383.94 | 0.526232E+11 | 0.860110E+10 | 0.00 | 1.00 | 0.00 | 74281.53 | 66722.79 | 11731.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.176666E+10 | 0.00 | 11.33 | 0.176666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78745.58 | 27-FEB-15:00 | 78745.58 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.394506E+10 | 0.00 | 34.00 | 0.394506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103396.31 | 18-MAR-16:00 | 103396.31 | 18-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.281106E+11 | 0.00 | 123.17 | 0.281106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 198574.72 | 27-APR-18:10 | 198574.72 | 27-APR-18:10 | 0.00 | 0.00 | 0.00 |
May | 0.547785E+11 | 0.00 | 245.33 | 0.542516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 204795.82 | 05-MAY-18:00 | 172720.58 | 04-MAY-18:03 | 0.00 | 0.00 | 0.00 |
June | 0.975925E+11 | 0.00 | 393.67 | 0.974157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 209292.46 | 28-JUN-18:10 | 202976.83 | 28-JUN-18:10 | 0.00 | 0.00 | 0.00 |
July | 0.165184E+12 | 0.00 | 539.67 | 0.159039E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 263933.75 | 27-JUL-18:33 | 228675.09 | 24-JUL-18:10 | 0.00 | 0.00 | 0.00 |
August | 0.207650E+12 | 0.00 | 592.83 | 0.198114E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 283274.26 | 10-AUG-18:10 | 241085.18 | 10-AUG-18:10 | 0.00 | 0.00 | 0.00 |
September | 0.800163E+11 | 0.00 | 345.50 | 0.774187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 197901.80 | 14-SEP-17:15 | 174755.79 | 14-SEP-17:15 | 0.00 | 0.00 | 0.00 |
October | 0.149968E+11 | 0.00 | 121.67 | 0.149813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 122238.88 | 04-OCT-15:15 | 122238.88 | 04-OCT-15:15 | 0.00 | 0.00 | 0.00 |
November | 0.339029E+10 | 0.00 | 25.92 | 0.339029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 102497.58 | 04-NOV-15:20 | 102497.58 | 04-NOV-15:20 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.657431E+12 | 0.00 | 2433.08 | 0.638433E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.207650E+12 | 0.00 | 592.83 | 0.198114E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 283274.26 | 241085.18 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.108440E+09 | 0.00 | 5.00 | 0.108440E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9635.15 | 27-FEB-16:02 | 9635.15 | 27-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.232539E+09 | 0.00 | 18.33 | 0.232539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12388.66 | 18-MAR-16:00 | 12388.66 | 18-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.179866E+10 | 0.00 | 73.00 | 0.179842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18216.45 | 27-APR-15:02 | 18216.45 | 27-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.358834E+10 | 0.00 | 145.50 | 0.343697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21148.09 | 05-MAY-18:07 | 17249.75 | 05-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.631575E+10 | 0.00 | 267.83 | 0.631105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18083.89 | 22-JUN-18:20 | 17796.10 | 28-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.118421E+11 | 0.00 | 399.17 | 0.109131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24080.93 | 15-JUL-18:07 | 19377.12 | 24-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.155328E+11 | 0.00 | 453.17 | 0.141125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25119.38 | 30-AUG-12:40 | 19656.64 | 29-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.552409E+10 | 0.00 | 235.33 | 0.511606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23375.10 | 14-SEP-12:50 | 17206.80 | 12-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.905033E+09 | 0.00 | 70.50 | 0.903628E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14148.85 | 04-OCT-15:02 | 14148.85 | 04-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.222488E+09 | 0.00 | 15.50 | 0.196313E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16088.96 | 04-NOV-15:02 | 13200.11 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.460702E+11 | 0.00 | 1683.33 | 0.431290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.155328E+11 | 0.00 | 453.17 | 0.141125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25119.38 | 19656.64 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 16209681.83 | 0.00 | 2.65 | 9619263.97 | 0.00 | 0.00 | 0.00 | 0.00 | 10750.01 | 05-JAN-16:02 | 10750.01 | 05-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.224369E+09 | 0.00 | 55.38 | 0.126920E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13122.12 | 28-FEB-16:02 | 13018.47 | 12-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.782222E+09 | 0.00 | 148.35 | 0.549490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13330.13 | 18-MAR-18:01 | 13330.13 | 18-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.225003E+10 | 0.00 | 350.19 | 0.145604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14383.38 | 30-APR-15:01 | 13278.16 | 02-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.419965E+10 | 0.00 | 545.37 | 0.271689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13865.31 | 05-MAY-18:02 | 13815.67 | 14-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.491770E+10 | 0.00 | 610.99 | 0.296908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14514.90 | 12-JUN-15:01 | 13289.53 | 10-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.771746E+10 | 0.00 | 681.61 | 0.497059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14481.18 | 16-JUL-15:01 | 13803.36 | 31-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.748544E+10 | 0.00 | 675.63 | 0.466990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15141.64 | 29-AUG-08:62 | 13931.69 | 24-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.498751E+10 | 0.00 | 567.82 | 0.298797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14422.48 | 25-SEP-15:02 | 13274.44 | 29-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.146195E+10 | 0.00 | 279.71 | 0.840356E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14043.36 | 01-OCT-08:62 | 13277.39 | 04-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.168243E+09 | 0.00 | 44.71 | 75755473.15 | 0.00 | 0.00 | 0.00 | 0.00 | 14740.62 | 05-NOV-15:01 | 12762.16 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 34504806.93 | 0.00 | 11.92 | 22271538.02 | 0.00 | 0.00 | 0.00 | 0.00 | 12567.92 | 10-DEC-16:02 | 12508.30 | 03-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342453E+11 | 0.00 | 3974.34 | 0.213949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 16209681.83 | 0.00 | 2.65 | 9619263.97 | 0.00 | 0.00 | 0.00 | 0.00 | 10750.01 | 10750.01 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.771746E+10 | 0.00 | 681.61 | 0.497059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15141.64 | 13931.69 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 6658095.13 | 0.00 | 1.64 | 2792111.06 | 0.00 | 0.00 | 0.00 | 0.00 | 2748.62 | 30-JAN-16:04 | 1640.31 | 30-JAN-16:04 | 0.00 | 0.00 | 0.00 |
February | 49246137.06 | 0.00 | 14.42 | 24792927.23 | 0.00 | 0.00 | 0.00 | 0.00 | 11462.04 | 28-FEB-16:02 | 11429.27 | 26-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.254685E+09 | 0.00 | 61.90 | 0.171953E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11602.09 | 25-MAR-15:02 | 11602.09 | 25-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.122006E+10 | 0.00 | 230.22 | 0.748034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13768.94 | 25-APR-17:41 | 13768.94 | 25-APR-17:41 | 0.00 | 0.00 | 0.00 |
May | 0.249494E+10 | 0.00 | 423.92 | 0.140932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13772.34 | 21-MAY-17:41 | 13772.34 | 21-MAY-17:41 | 0.00 | 0.00 | 0.00 |
June | 0.324203E+10 | 0.00 | 455.75 | 0.183080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13317.60 | 22-JUN-21:51 | 13240.70 | 22-JUN-16:21 | 0.00 | 0.00 | 0.00 |
July | 0.516869E+10 | 0.00 | 504.52 | 0.321036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14900.08 | 15-JUL-21:51 | 14355.41 | 25-JUL-16:51 | 0.00 | 0.00 | 0.00 |
August | 0.504129E+10 | 0.00 | 496.33 | 0.308778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14087.69 | 24-AUG-21:51 | 12711.53 | 08-AUG-21:31 | 0.00 | 0.00 | 0.00 |
September | 0.245942E+10 | 0.00 | 403.37 | 0.120954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13905.81 | 22-SEP-16:11 | 13905.81 | 22-SEP-16:11 | 0.00 | 0.00 | 0.00 |
October | 0.469506E+09 | 0.00 | 150.60 | 0.225717E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13493.92 | 01-OCT-15:01 | 11553.73 | 24-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 36128277.74 | 0.00 | 11.97 | 14881235.65 | 0.00 | 0.00 | 0.00 | 0.00 | 13874.65 | 04-NOV-15:02 | 10737.39 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 8023473.03 | 0.00 | 1.64 | 4181858.42 | 0.00 | 0.00 | 0.00 | 0.00 | 4844.44 | 10-DEC-16:02 | 4057.57 | 02-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204507E+11 | 0.00 | 2756.27 | 0.119401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6658095.13 | 0.00 | 1.64 | 2792111.06 | 0.00 | 0.00 | 0.00 | 0.00 | 2748.62 | 1640.31 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.516869E+10 | 0.00 | 504.52 | 0.321036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14900.08 | 14355.41 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.405767E+10 | 0.00 | 92.94 | 0.360554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38705.24 | 08-FEB-13:40 | 38705.24 | 08-FEB-13:40 | 0.00 | 0.00 | 0.00 |
March | 0.120522E+11 | 0.00 | 267.84 | 0.973717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50166.21 | 02-MAR-13:00 | 41688.02 | 02-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.195621E+11 | 0.00 | 476.41 | 0.117442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46067.82 | 27-APR-12:50 | 39948.93 | 27-APR-13:05 | 0.00 | 0.00 | 0.00 |
May | 0.247492E+11 | 0.00 | 573.77 | 0.117288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45000.13 | 04-MAY-13:00 | 38688.36 | 04-MAY-13:15 | 0.00 | 0.00 | 0.00 |
June | 0.273152E+11 | 0.00 | 632.63 | 0.115982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34192.86 | 28-JUN-13:00 | 22866.19 | 28-JUN-13:05 | 0.00 | 0.00 | 0.00 |
July | 0.377074E+11 | 0.00 | 721.27 | 0.176558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42461.33 | 31-JUL-12:50 | 33689.35 | 31-JUL-13:20 | 0.00 | 0.00 | 0.00 |
August | 0.427580E+11 | 0.00 | 714.96 | 0.224714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52379.27 | 24-AUG-13:30 | 50400.11 | 24-AUG-13:30 | 0.00 | 0.00 | 0.00 |
September | 0.365441E+11 | 0.00 | 635.86 | 0.206059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55183.91 | 14-SEP-13:30 | 48101.82 | 15-SEP-14:00 | 0.00 | 0.00 | 0.00 |
October | 0.210935E+11 | 0.00 | 442.86 | 0.121303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57434.76 | 04-OCT-12:40 | 47958.83 | 04-OCT-12:40 | 0.00 | 0.00 | 0.00 |
November | 0.355482E+10 | 0.00 | 100.85 | 0.178537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45820.75 | 04-NOV-13:25 | 39895.95 | 04-NOV-13:25 | 0.00 | 0.00 | 0.00 |
December | 0.179057E+10 | 0.00 | 44.40 | 0.167858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34578.61 | 05-DEC-12:30 | 34578.61 | 05-DEC-12:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.231185E+12 | 0.00 | 4703.80 | 0.124741E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.427580E+11 | 0.00 | 721.27 | 0.224714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57434.76 | 50400.11 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.937499E+09 | 0.00 | 88.05 | 0.426819E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47995.37 | 12-JAN-09:02 | 47995.37 | 12-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.283652E+10 | 0.00 | 150.29 | 0.138540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57364.92 | 25-FEB-09:02 | 52390.28 | 26-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.724077E+10 | 0.00 | 334.25 | 0.457146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57127.83 | 11-MAR-09:02 | 53917.38 | 20-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.158311E+11 | 0.00 | 439.99 | 0.110239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62386.22 | 27-APR-18:02 | 61604.66 | 27-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.251211E+11 | 0.00 | 470.84 | 0.181195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63991.21 | 07-MAY-15:02 | 59590.10 | 04-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.302159E+11 | 0.00 | 432.85 | 0.223584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62094.27 | 28-JUN-15:02 | 60361.15 | 28-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.356534E+11 | 0.00 | 443.37 | 0.265079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65937.91 | 30-JUL-15:02 | 61723.40 | 24-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.357243E+11 | 0.00 | 439.73 | 0.249125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65794.08 | 24-AUG-15:02 | 61534.15 | 08-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.238773E+11 | 0.00 | 410.81 | 0.150952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66943.05 | 23-SEP-15:02 | 58258.06 | 09-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.114512E+11 | 0.00 | 449.25 | 0.642434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62439.96 | 01-OCT-15:01 | 55038.10 | 09-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.478779E+10 | 0.00 | 243.60 | 0.216710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62842.80 | 04-NOV-15:02 | 51200.71 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 0.792363E+09 | 0.00 | 85.05 | 0.412453E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52220.56 | 03-DEC-09:02 | 52220.56 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194469E+12 | 0.00 | 3988.08 | 0.133405E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.792363E+09 | 0.00 | 85.05 | 0.412453E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47995.37 | 47995.37 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.357243E+11 | 0.00 | 470.84 | 0.265079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66943.05 | 61723.40 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 12500064.22 | 0.00 | 4.60 | 5099345.23 | 0.00 | 0.00 | 0.00 | 0.00 | 3191.02 | 20-JAN-16:02 | 2354.93 | 20-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.194821E+09 | 0.00 | 48.35 | 0.109442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11452.58 | 28-FEB-16:02 | 11223.91 | 12-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.748704E+09 | 0.00 | 168.41 | 0.513827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11691.48 | 28-MAR-15:02 | 11691.48 | 28-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.233041E+10 | 0.00 | 384.54 | 0.144043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12812.77 | 30-APR-15:01 | 12212.74 | 27-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.363958E+10 | 0.00 | 534.65 | 0.222373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12658.83 | 05-MAY-15:02 | 12404.97 | 14-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.524337E+10 | 0.00 | 635.25 | 0.322757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12545.93 | 12-JUN-15:01 | 12152.91 | 28-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.668937E+10 | 0.00 | 693.63 | 0.411385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13402.70 | 16-JUL-15:01 | 12348.74 | 31-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.738291E+10 | 0.00 | 692.54 | 0.462977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13530.19 | 20-AUG-15:02 | 12577.01 | 09-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.448413E+10 | 0.00 | 562.72 | 0.266987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13445.76 | 01-SEP-15:02 | 11969.77 | 14-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.143984E+10 | 0.00 | 296.15 | 0.822997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13833.01 | 01-OCT-15:01 | 11922.15 | 04-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.170471E+09 | 0.00 | 49.48 | 67328463.16 | 0.00 | 0.00 | 0.00 | 0.00 | 13065.23 | 05-NOV-15:01 | 11406.03 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 59104896.78 | 0.00 | 15.51 | 30709468.27 | 0.00 | 0.00 | 0.00 | 0.00 | 9168.15 | 02-DEC-09:02 | 9168.15 | 02-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.323952E+11 | 0.00 | 4085.83 | 0.198546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 12500064.22 | 0.00 | 4.60 | 5099345.23 | 0.00 | 0.00 | 0.00 | 0.00 | 3191.02 | 2354.93 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.738291E+10 | 0.00 | 693.63 | 0.462977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13833.01 | 12577.01 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 6312359.70 | 0.00 | 1.56 | 2765643.68 | 0.00 | 0.00 | 0.00 | 0.00 | 2835.13 | 25-JAN-19:05 | 1608.58 | 25-JAN-19:05 | 0.00 | 0.00 | 0.00 |
February | 27476609.01 | 0.00 | 15.08 | 14162480.52 | 0.00 | 0.00 | 0.00 | 0.00 | 9674.74 | 12-FEB-09:01 | 9674.74 | 12-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.199180E+09 | 0.00 | 57.22 | 0.133924E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10608.19 | 25-MAR-08:62 | 10608.19 | 25-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.130747E+10 | 0.00 | 269.42 | 0.776222E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11599.60 | 30-APR-15:01 | 11374.75 | 27-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.232154E+10 | 0.00 | 417.30 | 0.136522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12587.01 | 06-MAY-08:51 | 11867.30 | 06-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.374691E+10 | 0.00 | 495.81 | 0.226907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11489.58 | 10-JUN-08:51 | 11489.58 | 10-JUN-08:51 | 0.00 | 0.00 | 0.00 |
July | 0.456620E+10 | 0.00 | 523.60 | 0.274840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15037.00 | 24-JUL-08:32 | 13531.36 | 24-JUL-08:32 | 0.00 | 0.00 | 0.00 |
August | 0.502384E+10 | 0.00 | 522.37 | 0.303342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15272.62 | 10-AUG-08:32 | 13560.66 | 13-AUG-08:32 | 0.00 | 0.00 | 0.00 |
September | 0.233657E+10 | 0.00 | 398.95 | 0.126550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12614.78 | 22-SEP-15:02 | 12118.70 | 13-SEP-08:51 | 0.00 | 0.00 | 0.00 |
October | 0.496147E+09 | 0.00 | 141.90 | 0.271363E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12485.35 | 01-OCT-15:01 | 10401.53 | 06-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 34024690.40 | 0.00 | 12.89 | 13010488.11 | 0.00 | 0.00 | 0.00 | 0.00 | 12267.37 | 04-NOV-15:02 | 9032.11 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 7327202.99 | 0.00 | 2.37 | 3373345.54 | 0.00 | 0.00 | 0.00 | 0.00 | 3136.38 | 16-DEC-19:05 | 1954.79 | 13-DEC-09:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200730E+11 | 0.00 | 2858.46 | 0.118964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6312359.70 | 0.00 | 1.56 | 2765643.68 | 0.00 | 0.00 | 0.00 | 0.00 | 2835.13 | 1608.58 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.502384E+10 | 0.00 | 523.60 | 0.303342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15272.62 | 13560.66 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3390754.19 | 0.00 | 1.87 | 2032263.04 | 0.00 | 0.00 | 0.00 | 0.00 | 2816.41 | 05-JAN-16:02 | 2816.41 | 05-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 54576608.50 | 0.00 | 37.59 | 32415420.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3556.12 | 28-FEB-16:02 | 3411.42 | 12-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.195500E+09 | 0.00 | 117.89 | 0.142139E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3492.40 | 18-MAR-18:01 | 3492.40 | 18-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.569262E+09 | 0.00 | 289.12 | 0.388575E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3862.73 | 30-APR-08:62 | 3478.99 | 02-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.106027E+10 | 0.00 | 473.29 | 0.721400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3789.55 | 07-MAY-08:62 | 3619.59 | 14-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.124183E+10 | 0.00 | 571.37 | 0.780571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3820.14 | 12-JUN-15:01 | 3481.71 | 01-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.197035E+10 | 0.00 | 675.20 | 0.129504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3871.12 | 31-JUL-08:61 | 3616.31 | 31-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.186328E+10 | 0.00 | 656.65 | 0.118916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4069.57 | 29-AUG-08:62 | 3628.47 | 24-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.120816E+10 | 0.00 | 516.71 | 0.753739E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3938.40 | 23-SEP-08:62 | 3439.50 | 23-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.330526E+09 | 0.00 | 210.98 | 0.202902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3845.06 | 01-OCT-08:62 | 3478.69 | 04-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 42189229.58 | 0.00 | 32.49 | 20821576.44 | 0.00 | 0.00 | 0.00 | 0.00 | 3946.99 | 05-NOV-15:01 | 3243.45 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 6873484.33 | 0.00 | 7.12 | 4455485.78 | 0.00 | 0.00 | 0.00 | 0.00 | 3395.94 | 10-DEC-16:02 | 3007.96 | 10-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.854621E+10 | 0.00 | 3590.26 | 0.553325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3390754.19 | 0.00 | 1.87 | 2032263.04 | 0.00 | 0.00 | 0.00 | 0.00 | 2816.41 | 2816.41 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.197035E+10 | 0.00 | 675.20 | 0.129504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4069.57 | 3628.47 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1203999.39 | 0.00 | 0.85 | 533456.75 | 0.00 | 0.00 | 0.00 | 0.00 | 769.11 | 12-JAN-09:05 | 447.88 | 05-JAN-16:03 | 0.00 | 0.00 | 0.00 |
February | 9887565.72 | 0.00 | 11.57 | 4682223.49 | 0.00 | 0.00 | 0.00 | 0.00 | 3052.52 | 28-FEB-16:02 | 2902.96 | 27-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 58706926.70 | 0.00 | 46.37 | 39406183.37 | 0.00 | 0.00 | 0.00 | 0.00 | 3062.05 | 18-MAR-15:02 | 3062.05 | 18-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.302895E+09 | 0.00 | 182.62 | 0.196544E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3579.98 | 25-APR-17:41 | 3579.98 | 25-APR-17:41 | 0.00 | 0.00 | 0.00 |
May | 0.628378E+09 | 0.00 | 365.36 | 0.371774E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3604.59 | 31-MAY-21:51 | 3580.77 | 21-MAY-17:41 | 0.00 | 0.00 | 0.00 |
June | 0.833672E+09 | 0.00 | 435.21 | 0.485568E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3642.39 | 22-JUN-21:51 | 3386.20 | 22-JUN-16:21 | 0.00 | 0.00 | 0.00 |
July | 0.136333E+10 | 0.00 | 511.14 | 0.863329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3943.80 | 26-JUL-21:51 | 3709.95 | 25-JUL-16:51 | 0.00 | 0.00 | 0.00 |
August | 0.126929E+10 | 0.00 | 491.37 | 0.798452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3721.91 | 24-AUG-21:51 | 3331.95 | 06-AUG-21:51 | 0.00 | 0.00 | 0.00 |
September | 0.570203E+09 | 0.00 | 358.01 | 0.289791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3661.49 | 13-SEP-21:51 | 3617.31 | 22-SEP-16:11 | 0.00 | 0.00 | 0.00 |
October | 88294859.83 | 0.00 | 95.42 | 45728911.97 | 0.00 | 0.00 | 0.00 | 0.00 | 3537.69 | 01-OCT-15:01 | 3009.37 | 04-OCT-21:12 | 0.00 | 0.00 | 0.00 |
November | 9126558.43 | 0.00 | 7.13 | 3536109.83 | 0.00 | 0.00 | 0.00 | 0.00 | 3638.97 | 04-NOV-15:02 | 2772.83 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 1136698.87 | 0.00 | 0.96 | 519604.47 | 0.00 | 0.00 | 0.00 | 0.00 | 954.68 | 28-DEC-16:05 | 487.95 | 28-DEC-16:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.513612E+10 | 0.00 | 2506.01 | 0.309986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1136698.87 | 0.00 | 0.85 | 519604.47 | 0.00 | 0.00 | 0.00 | 0.00 | 769.11 | 447.88 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.136333E+10 | 0.00 | 511.14 | 0.863329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3943.80 | 3709.95 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.477742E+09 | 0.00 | 63.82 | 0.287482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16829.16 | 05-JAN-16:02 | 16829.16 | 05-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.177903E+10 | 0.00 | 175.67 | 0.119997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19081.66 | 28-FEB-16:02 | 18257.28 | 26-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.306693E+10 | 0.00 | 303.51 | 0.224080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19146.40 | 18-MAR-18:01 | 19146.40 | 18-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.471531E+10 | 0.00 | 454.37 | 0.300766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20801.73 | 30-APR-15:01 | 19663.95 | 27-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.596287E+10 | 0.00 | 563.83 | 0.364080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20568.52 | 05-MAY-18:02 | 19844.54 | 14-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.671660E+10 | 0.00 | 621.54 | 0.378625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20792.77 | 12-JUN-15:01 | 19477.15 | 28-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.944516E+10 | 0.00 | 676.20 | 0.554307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21313.10 | 16-JUL-15:01 | 20136.96 | 30-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.105751E+11 | 0.00 | 675.11 | 0.642770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21316.90 | 29-AUG-08:62 | 20104.14 | 29-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.865810E+10 | 0.00 | 590.20 | 0.546912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20709.76 | 01-SEP-15:02 | 19339.42 | 12-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.466753E+10 | 0.00 | 442.34 | 0.305193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19852.74 | 01-OCT-08:62 | 19073.71 | 04-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.121662E+10 | 0.00 | 149.36 | 0.673744E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19550.97 | 05-NOV-08:62 | 18491.72 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 0.100021E+10 | 0.00 | 103.67 | 0.677586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18360.87 | 10-DEC-16:02 | 17930.53 | 10-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.582812E+11 | 0.00 | 4819.62 | 0.360061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.477742E+09 | 0.00 | 63.82 | 0.287482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16829.16 | 16829.16 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.105751E+11 | 0.00 | 676.20 | 0.642770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21316.90 | 20136.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 381.12 | 226.72 | 154.40 | 341.79 | 493.22 | 0.00 | 0.00 | 0.00 |
February | 586.49 | 363.88 | 222.60 | 601.83 | 433.19 | 0.00 | 0.00 | 0.00 |
March | 622.14 | 328.93 | 293.21 | 675.42 | 359.66 | 0.00 | 0.00 | 0.00 |
April | 657.40 | 282.14 | 375.26 | 763.58 | 288.86 | 0.00 | 0.00 | 0.00 |
May | 612.50 | 186.73 | 425.76 | 731.09 | 229.14 | 0.00 | 0.00 | 0.00 |
June | 554.17 | 148.32 | 405.85 | 685.15 | 168.53 | 0.00 | 0.00 | 0.00 |
July | 602.08 | 218.62 | 383.46 | 808.78 | 148.59 | 0.00 | 0.00 | 0.00 |
August | 641.87 | 294.94 | 346.93 | 880.70 | 143.48 | 0.00 | 0.00 | 0.00 |
September | 711.91 | 389.37 | 322.54 | 908.13 | 215.48 | 0.00 | 0.00 | 0.00 |
October | 643.99 | 394.27 | 249.72 | 748.84 | 303.82 | 0.00 | 0.00 | 0.00 |
November | 385.41 | 220.61 | 164.80 | 377.06 | 390.26 | 0.00 | 0.00 | 0.00 |
December | 403.36 | 260.85 | 142.51 | 399.11 | 495.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 566.59 | 275.74 | 290.86 | 660.35 | 305.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 381.12 | 148.32 | 142.51 | 341.79 | 143.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 711.91 | 394.27 | 425.76 | 908.13 | 495.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1073.21 | 638.43 | 434.78 | 948.33 | 1427.91 | 0.00 | 0.00 | 0.00 |
February | 1651.51 | 1024.67 | 626.84 | 1673.77 | 1264.82 | 0.00 | 0.00 | 0.00 |
March | 1751.91 | 926.24 | 825.67 | 1879.22 | 1068.75 | 0.00 | 0.00 | 0.00 |
April | 1851.19 | 794.48 | 1056.71 | 2122.82 | 868.68 | 0.00 | 0.00 | 0.00 |
May | 1724.75 | 525.83 | 1198.93 | 2029.58 | 698.34 | 0.00 | 0.00 | 0.00 |
June | 1560.51 | 417.65 | 1142.85 | 1894.65 | 529.06 | 0.00 | 0.00 | 0.00 |
July | 1695.42 | 615.61 | 1079.81 | 2247.45 | 467.73 | 0.00 | 0.00 | 0.00 |
August | 1807.46 | 830.52 | 976.94 | 2451.82 | 455.92 | 0.00 | 0.00 | 0.00 |
September | 2004.70 | 1096.43 | 908.26 | 2531.54 | 663.42 | 0.00 | 0.00 | 0.00 |
October | 1813.42 | 1110.24 | 703.18 | 2084.70 | 918.48 | 0.00 | 0.00 | 0.00 |
November | 1085.28 | 621.22 | 464.06 | 1045.58 | 1147.10 | 0.00 | 0.00 | 0.00 |
December | 1135.85 | 734.54 | 401.31 | 1109.98 | 1437.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1595.49 | 776.46 | 819.03 | 1835.58 | 910.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1073.21 | 417.65 | 401.31 | 948.33 | 455.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2004.70 | 1110.24 | 1198.93 | 2531.54 | 1437.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1394.16 | 829.35 | 564.80 | 1239.09 | 1986.53 | 0.00 | 0.00 | 0.00 |
February | 2145.41 | 1331.11 | 814.30 | 2196.59 | 1751.54 | 0.00 | 0.00 | 0.00 |
March | 2275.84 | 1203.24 | 1072.60 | 2469.94 | 1488.24 | 0.00 | 0.00 | 0.00 |
April | 2404.80 | 1032.08 | 1372.72 | 2789.18 | 1211.50 | 0.00 | 0.00 | 0.00 |
May | 2240.55 | 683.08 | 1557.47 | 2660.01 | 985.28 | 0.00 | 0.00 | 0.00 |
June | 2027.19 | 542.56 | 1484.63 | 2474.85 | 752.81 | 0.00 | 0.00 | 0.00 |
July | 2202.45 | 799.71 | 1402.74 | 2947.67 | 662.93 | 0.00 | 0.00 | 0.00 |
August | 2348.00 | 1078.89 | 1269.10 | 3220.65 | 640.61 | 0.00 | 0.00 | 0.00 |
September | 2604.21 | 1424.33 | 1179.88 | 3326.91 | 927.61 | 0.00 | 0.00 | 0.00 |
October | 2355.74 | 1442.27 | 913.47 | 2736.56 | 1286.51 | 0.00 | 0.00 | 0.00 |
November | 1409.84 | 807.00 | 602.84 | 1362.97 | 1613.17 | 0.00 | 0.00 | 0.00 |
December | 1475.53 | 954.20 | 521.33 | 1452.54 | 2001.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2072.64 | 1008.67 | 1063.97 | 2407.24 | 1273.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1394.16 | 542.56 | 521.33 | 1239.09 | 640.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2604.21 | 1442.27 | 1557.47 | 3326.91 | 2001.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.35 | 44.83 | 30.53 | 68.34 | 98.92 | 0.00 | 0.00 | 0.00 |
February | 115.96 | 71.95 | 44.01 | 119.69 | 86.85 | 0.00 | 0.00 | 0.00 |
March | 123.01 | 65.03 | 57.97 | 133.85 | 72.31 | 0.00 | 0.00 | 0.00 |
April | 129.98 | 55.78 | 74.20 | 149.93 | 58.68 | 0.00 | 0.00 | 0.00 |
May | 121.10 | 36.92 | 84.18 | 142.31 | 46.73 | 0.00 | 0.00 | 0.00 |
June | 109.57 | 29.33 | 80.24 | 132.97 | 33.94 | 0.00 | 0.00 | 0.00 |
July | 119.04 | 43.22 | 75.82 | 158.45 | 29.09 | 0.00 | 0.00 | 0.00 |
August | 126.91 | 58.31 | 68.60 | 174.03 | 27.05 | 0.00 | 0.00 | 0.00 |
September | 140.76 | 76.98 | 63.77 | 180.35 | 42.23 | 0.00 | 0.00 | 0.00 |
October | 127.33 | 77.95 | 49.37 | 148.58 | 60.15 | 0.00 | 0.00 | 0.00 |
November | 76.20 | 43.62 | 32.58 | 75.28 | 77.70 | 0.00 | 0.00 | 0.00 |
December | 79.75 | 51.57 | 28.18 | 79.81 | 98.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.03 | 54.52 | 57.51 | 130.34 | 60.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.35 | 29.33 | 28.18 | 68.34 | 27.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.76 | 77.95 | 84.18 | 180.35 | 98.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.10 | 16.09 | 38.01 | 22.92 | 199.73 | 0.00 | 0.00 | 0.00 |
February | 96.50 | 36.23 | 60.27 | 66.92 | 173.03 | 0.00 | 0.00 | 0.00 |
March | 135.19 | 45.71 | 89.48 | 115.55 | 137.70 | 0.00 | 0.00 | 0.00 |
April | 205.42 | 78.44 | 126.98 | 213.14 | 106.94 | 0.00 | 0.00 | 0.00 |
May | 264.84 | 107.82 | 157.02 | 302.69 | 84.55 | 0.00 | 0.00 | 0.00 |
June | 254.15 | 98.49 | 155.66 | 299.56 | 61.40 | 0.00 | 0.00 | 0.00 |
July | 314.18 | 165.10 | 149.08 | 403.32 | 52.76 | 0.00 | 0.00 | 0.00 |
August | 260.02 | 132.62 | 127.39 | 338.74 | 49.74 | 0.00 | 0.00 | 0.00 |
September | 212.43 | 102.19 | 110.24 | 254.55 | 78.77 | 0.00 | 0.00 | 0.00 |
October | 121.48 | 49.94 | 71.54 | 115.45 | 115.93 | 0.00 | 0.00 | 0.00 |
November | 60.16 | 17.10 | 43.06 | 34.63 | 153.68 | 0.00 | 0.00 | 0.00 |
December | 50.78 | 17.63 | 33.15 | 27.33 | 197.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 169.55 | 72.56 | 96.99 | 183.66 | 117.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.78 | 16.09 | 33.15 | 22.92 | 49.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 314.18 | 165.10 | 157.02 | 403.32 | 199.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.99 | 0.00 | 16.99 | 0.66 | 110.35 | 0.00 | 0.00 | 0.00 |
February | 26.44 | 0.00 | 26.44 | 5.61 | 95.50 | 0.00 | 0.00 | 0.00 |
March | 38.96 | 0.00 | 38.96 | 18.06 | 74.85 | 0.00 | 0.00 | 0.00 |
April | 55.32 | 0.34 | 54.98 | 38.45 | 57.44 | 0.00 | 0.00 | 0.00 |
May | 70.97 | 2.13 | 68.84 | 60.14 | 44.95 | 0.00 | 0.00 | 0.00 |
June | 74.69 | 5.00 | 69.70 | 71.14 | 32.65 | 0.00 | 0.00 | 0.00 |
July | 71.09 | 5.72 | 65.37 | 75.40 | 29.00 | 0.00 | 0.00 | 0.00 |
August | 57.63 | 1.73 | 55.90 | 64.10 | 26.98 | 0.00 | 0.00 | 0.00 |
September | 44.60 | 0.03 | 44.57 | 37.20 | 44.18 | 0.00 | 0.00 | 0.00 |
October | 30.54 | 0.00 | 30.54 | 15.97 | 62.74 | 0.00 | 0.00 | 0.00 |
November | 19.24 | 0.00 | 19.24 | 3.43 | 83.76 | 0.00 | 0.00 | 0.00 |
December | 14.44 | 0.00 | 14.44 | 0.36 | 107.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.49 | 1.26 | 42.24 | 32.71 | 64.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.44 | 0.00 | 14.44 | 0.36 | 26.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.69 | 5.72 | 69.70 | 75.40 | 110.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.10 | 16.09 | 38.01 | 24.47 | 197.76 | 0.00 | 0.00 | 0.00 |
February | 96.50 | 36.23 | 60.27 | 69.96 | 170.40 | 0.00 | 0.00 | 0.00 |
March | 135.19 | 45.71 | 89.48 | 119.21 | 135.77 | 0.00 | 0.00 | 0.00 |
April | 205.42 | 78.44 | 126.98 | 215.91 | 106.34 | 0.00 | 0.00 | 0.00 |
May | 264.84 | 107.82 | 157.02 | 301.30 | 86.04 | 0.00 | 0.00 | 0.00 |
June | 254.15 | 98.49 | 155.66 | 296.87 | 63.93 | 0.00 | 0.00 | 0.00 |
July | 314.18 | 165.10 | 149.08 | 398.89 | 56.83 | 0.00 | 0.00 | 0.00 |
August | 260.02 | 132.62 | 127.39 | 337.62 | 52.67 | 0.00 | 0.00 | 0.00 |
September | 212.43 | 102.19 | 110.24 | 254.56 | 80.84 | 0.00 | 0.00 | 0.00 |
October | 121.48 | 49.94 | 71.54 | 118.73 | 114.26 | 0.00 | 0.00 | 0.00 |
November | 60.16 | 17.10 | 43.06 | 36.40 | 151.87 | 0.00 | 0.00 | 0.00 |
December | 50.78 | 17.63 | 33.15 | 29.09 | 195.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 169.55 | 72.56 | 96.99 | 184.33 | 117.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.78 | 16.09 | 33.15 | 24.47 | 52.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 314.18 | 165.10 | 157.02 | 398.89 | 197.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.27 | 35.85 | 24.42 | 52.43 | 84.69 | 0.00 | 0.00 | 0.00 |
February | 92.75 | 57.55 | 35.20 | 88.92 | 86.15 | 0.00 | 0.00 | 0.00 |
March | 98.39 | 52.02 | 46.37 | 97.30 | 82.59 | 0.00 | 0.00 | 0.00 |
April | 103.96 | 44.62 | 59.34 | 108.27 | 68.99 | 0.00 | 0.00 | 0.00 |
May | 96.86 | 29.53 | 67.33 | 102.18 | 56.96 | 0.00 | 0.00 | 0.00 |
June | 87.64 | 23.46 | 64.18 | 93.46 | 44.92 | 0.00 | 0.00 | 0.00 |
July | 95.22 | 34.57 | 60.64 | 114.71 | 40.19 | 0.00 | 0.00 | 0.00 |
August | 101.51 | 46.64 | 54.87 | 127.06 | 39.13 | 0.00 | 0.00 | 0.00 |
September | 112.58 | 61.58 | 51.01 | 133.50 | 53.96 | 0.00 | 0.00 | 0.00 |
October | 101.84 | 62.35 | 39.49 | 108.60 | 73.48 | 0.00 | 0.00 | 0.00 |
November | 60.95 | 34.89 | 26.06 | 53.29 | 85.20 | 0.00 | 0.00 | 0.00 |
December | 63.79 | 41.25 | 22.54 | 60.13 | 91.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.60 | 43.61 | 46.00 | 95.01 | 67.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.27 | 23.46 | 22.54 | 52.43 | 39.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 112.58 | 62.35 | 67.33 | 133.50 | 91.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.60 | 0.00 | 13.60 | 0.31 | 93.88 | 0.00 | 0.00 | 0.00 |
February | 21.15 | 0.00 | 21.15 | 3.85 | 80.14 | 0.00 | 0.00 | 0.00 |
March | 31.17 | 0.00 | 31.17 | 13.92 | 62.02 | 0.00 | 0.00 | 0.00 |
April | 44.26 | 0.27 | 43.99 | 31.57 | 46.44 | 0.00 | 0.00 | 0.00 |
May | 56.79 | 1.71 | 55.08 | 51.02 | 35.29 | 0.00 | 0.00 | 0.00 |
June | 59.76 | 4.00 | 55.77 | 60.09 | 25.30 | 0.00 | 0.00 | 0.00 |
July | 56.88 | 4.58 | 52.30 | 65.04 | 21.41 | 0.00 | 0.00 | 0.00 |
August | 46.11 | 1.38 | 44.72 | 54.83 | 20.07 | 0.00 | 0.00 | 0.00 |
September | 35.69 | 0.03 | 35.66 | 31.97 | 33.83 | 0.00 | 0.00 | 0.00 |
October | 24.44 | 0.00 | 24.44 | 12.64 | 51.59 | 0.00 | 0.00 | 0.00 |
November | 15.39 | 0.00 | 15.39 | 2.27 | 71.26 | 0.00 | 0.00 | 0.00 |
December | 11.55 | 0.00 | 11.55 | 0.14 | 91.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 34.80 | 1.00 | 33.80 | 27.45 | 52.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.55 | 0.00 | 11.55 | 0.14 | 20.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.76 | 4.58 | 55.77 | 65.04 | 93.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.77 | 12.72 | 38.05 | 17.09 | 197.88 | 0.00 | 0.00 | 0.00 |
February | 93.53 | 33.13 | 60.40 | 59.81 | 169.82 | 0.00 | 0.00 | 0.00 |
March | 140.17 | 50.83 | 89.34 | 117.63 | 133.20 | 0.00 | 0.00 | 0.00 |
April | 216.49 | 89.84 | 126.65 | 223.56 | 102.78 | 0.00 | 0.00 | 0.00 |
May | 230.51 | 80.26 | 150.25 | 253.81 | 81.99 | 0.00 | 0.00 | 0.00 |
June | 275.89 | 120.08 | 155.81 | 328.15 | 58.93 | 0.00 | 0.00 | 0.00 |
July | 257.29 | 115.68 | 141.62 | 321.96 | 48.43 | 0.00 | 0.00 | 0.00 |
August | 252.57 | 126.34 | 126.23 | 325.48 | 46.39 | 0.00 | 0.00 | 0.00 |
September | 187.04 | 86.42 | 100.63 | 215.08 | 75.31 | 0.00 | 0.00 | 0.00 |
October | 122.30 | 52.26 | 70.05 | 114.17 | 112.91 | 0.00 | 0.00 | 0.00 |
November | 59.85 | 16.95 | 42.90 | 32.49 | 151.56 | 0.00 | 0.00 | 0.00 |
December | 48.96 | 15.74 | 33.22 | 22.12 | 194.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.58 | 66.83 | 94.75 | 169.84 | 114.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.96 | 12.72 | 33.22 | 17.09 | 46.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 275.89 | 126.34 | 155.81 | 328.15 | 197.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.35 | 44.83 | 30.53 | 68.31 | 98.78 | 0.00 | 0.00 | 0.00 |
February | 115.96 | 71.95 | 44.01 | 119.40 | 86.65 | 0.00 | 0.00 | 0.00 |
March | 123.01 | 65.03 | 57.97 | 133.11 | 72.12 | 0.00 | 0.00 | 0.00 |
April | 129.98 | 55.78 | 74.20 | 148.83 | 58.46 | 0.00 | 0.00 | 0.00 |
May | 121.10 | 36.92 | 84.18 | 142.19 | 46.10 | 0.00 | 0.00 | 0.00 |
June | 109.57 | 29.33 | 80.24 | 131.93 | 33.63 | 0.00 | 0.00 | 0.00 |
July | 119.04 | 43.22 | 75.82 | 158.49 | 28.28 | 0.00 | 0.00 | 0.00 |
August | 126.91 | 58.31 | 68.60 | 173.53 | 26.63 | 0.00 | 0.00 | 0.00 |
September | 140.76 | 76.98 | 63.77 | 180.22 | 41.50 | 0.00 | 0.00 | 0.00 |
October | 127.33 | 77.95 | 49.37 | 148.11 | 59.86 | 0.00 | 0.00 | 0.00 |
November | 76.20 | 43.62 | 32.58 | 75.15 | 77.57 | 0.00 | 0.00 | 0.00 |
December | 79.75 | 51.57 | 28.18 | 79.76 | 98.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.03 | 54.52 | 57.51 | 129.96 | 60.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.35 | 29.33 | 28.18 | 68.31 | 26.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.76 | 77.95 | 84.18 | 180.22 | 98.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.99 | 0.00 | 16.99 | 0.63 | 110.25 | 0.00 | 0.00 | 0.00 |
February | 26.44 | 0.00 | 26.44 | 5.49 | 95.34 | 0.00 | 0.00 | 0.00 |
March | 38.96 | 0.00 | 38.96 | 17.41 | 74.69 | 0.00 | 0.00 | 0.00 |
April | 55.32 | 0.34 | 54.98 | 37.42 | 57.31 | 0.00 | 0.00 | 0.00 |
May | 70.97 | 2.13 | 68.84 | 60.86 | 43.87 | 0.00 | 0.00 | 0.00 |
June | 74.69 | 5.00 | 69.70 | 70.62 | 32.01 | 0.00 | 0.00 | 0.00 |
July | 71.09 | 5.72 | 65.37 | 76.51 | 27.35 | 0.00 | 0.00 | 0.00 |
August | 57.63 | 1.73 | 55.90 | 63.31 | 26.15 | 0.00 | 0.00 | 0.00 |
September | 44.60 | 0.03 | 44.57 | 37.52 | 42.61 | 0.00 | 0.00 | 0.00 |
October | 30.54 | 0.00 | 30.54 | 15.47 | 62.28 | 0.00 | 0.00 | 0.00 |
November | 19.24 | 0.00 | 19.24 | 3.31 | 83.56 | 0.00 | 0.00 | 0.00 |
December | 14.44 | 0.00 | 14.44 | 0.32 | 107.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.49 | 1.26 | 42.24 | 32.57 | 63.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.44 | 0.00 | 14.44 | 0.32 | 26.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.69 | 5.72 | 69.70 | 76.51 | 110.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 50.77 | 12.72 | 38.05 | 17.73 | 194.98 | 0.00 | 0.00 | 0.00 |
February | 93.53 | 33.13 | 60.40 | 61.87 | 165.89 | 0.00 | 0.00 | 0.00 |
March | 140.17 | 50.83 | 89.34 | 121.08 | 130.92 | 0.00 | 0.00 | 0.00 |
April | 216.49 | 89.84 | 126.65 | 226.24 | 101.94 | 0.00 | 0.00 | 0.00 |
May | 230.51 | 80.26 | 150.25 | 254.50 | 82.74 | 0.00 | 0.00 | 0.00 |
June | 275.89 | 120.08 | 155.81 | 327.14 | 61.13 | 0.00 | 0.00 | 0.00 |
July | 257.29 | 115.68 | 141.62 | 320.15 | 51.27 | 0.00 | 0.00 | 0.00 |
August | 252.57 | 126.34 | 126.23 | 324.16 | 48.78 | 0.00 | 0.00 | 0.00 |
September | 187.04 | 86.42 | 100.63 | 216.66 | 76.12 | 0.00 | 0.00 | 0.00 |
October | 122.30 | 52.26 | 70.05 | 117.45 | 110.84 | 0.00 | 0.00 | 0.00 |
November | 59.85 | 16.95 | 42.90 | 33.70 | 148.98 | 0.00 | 0.00 | 0.00 |
December | 48.96 | 15.74 | 33.22 | 22.94 | 190.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.58 | 66.83 | 94.75 | 170.86 | 113.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.96 | 12.72 | 33.22 | 17.73 | 48.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 275.89 | 126.34 | 155.81 | 327.14 | 194.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.52 | 0.00 | 21.52 | 0.48 | 151.15 | 0.00 | 0.00 | 0.00 |
February | 33.48 | 0.00 | 33.48 | 6.11 | 129.03 | 0.00 | 0.00 | 0.00 |
March | 49.34 | 0.00 | 49.34 | 22.16 | 99.52 | 0.00 | 0.00 | 0.00 |
April | 70.06 | 0.43 | 69.63 | 50.20 | 75.68 | 0.00 | 0.00 | 0.00 |
May | 89.88 | 2.70 | 87.19 | 80.07 | 59.81 | 0.00 | 0.00 | 0.00 |
June | 94.60 | 6.33 | 88.27 | 93.87 | 43.69 | 0.00 | 0.00 | 0.00 |
July | 90.04 | 7.25 | 82.79 | 100.22 | 38.50 | 0.00 | 0.00 | 0.00 |
August | 72.98 | 2.19 | 70.79 | 82.83 | 37.66 | 0.00 | 0.00 | 0.00 |
September | 56.49 | 0.04 | 56.45 | 48.53 | 59.32 | 0.00 | 0.00 | 0.00 |
October | 38.68 | 0.00 | 38.68 | 19.44 | 84.67 | 0.00 | 0.00 | 0.00 |
November | 24.36 | 0.00 | 24.36 | 3.69 | 113.99 | 0.00 | 0.00 | 0.00 |
December | 18.29 | 0.00 | 18.29 | 0.20 | 147.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.08 | 1.59 | 53.49 | 42.54 | 86.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.29 | 0.00 | 18.29 | 0.20 | 37.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.60 | 7.25 | 88.27 | 100.22 | 151.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.93 | 0.00 | 7.93 | 0.18 | 55.72 | 0.00 | 0.00 | 0.00 |
February | 12.34 | 0.00 | 12.34 | 2.25 | 47.56 | 0.00 | 0.00 | 0.00 |
March | 18.19 | 0.00 | 18.19 | 8.17 | 36.69 | 0.00 | 0.00 | 0.00 |
April | 25.83 | 0.16 | 25.67 | 18.51 | 27.90 | 0.00 | 0.00 | 0.00 |
May | 33.14 | 0.99 | 32.14 | 29.52 | 22.05 | 0.00 | 0.00 | 0.00 |
June | 34.87 | 2.33 | 32.54 | 34.60 | 16.10 | 0.00 | 0.00 | 0.00 |
July | 33.19 | 2.67 | 30.52 | 36.94 | 14.19 | 0.00 | 0.00 | 0.00 |
August | 26.90 | 0.81 | 26.10 | 30.53 | 13.88 | 0.00 | 0.00 | 0.00 |
September | 20.82 | 0.02 | 20.81 | 17.89 | 21.87 | 0.00 | 0.00 | 0.00 |
October | 14.26 | 0.00 | 14.26 | 7.17 | 31.21 | 0.00 | 0.00 | 0.00 |
November | 8.98 | 0.00 | 8.98 | 1.36 | 42.02 | 0.00 | 0.00 | 0.00 |
December | 6.74 | 0.00 | 6.74 | 0.07 | 54.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.31 | 0.59 | 19.72 | 15.68 | 31.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.74 | 0.00 | 6.74 | 0.07 | 13.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.87 | 2.67 | 32.54 | 36.94 | 55.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.16 | 20.92 | 14.24 | 31.38 | 48.88 | 0.00 | 0.00 | 0.00 |
February | 54.11 | 33.57 | 20.54 | 55.91 | 42.28 | 0.00 | 0.00 | 0.00 |
March | 57.40 | 30.35 | 27.05 | 63.06 | 34.91 | 0.00 | 0.00 | 0.00 |
April | 60.65 | 26.03 | 34.62 | 71.14 | 28.29 | 0.00 | 0.00 | 0.00 |
May | 56.51 | 17.23 | 39.28 | 67.54 | 23.31 | 0.00 | 0.00 | 0.00 |
June | 51.12 | 13.68 | 37.44 | 62.88 | 17.52 | 0.00 | 0.00 | 0.00 |
July | 55.54 | 20.17 | 35.38 | 74.71 | 15.48 | 0.00 | 0.00 | 0.00 |
August | 59.22 | 27.21 | 32.01 | 81.62 | 14.83 | 0.00 | 0.00 | 0.00 |
September | 65.68 | 35.92 | 29.76 | 84.77 | 21.56 | 0.00 | 0.00 | 0.00 |
October | 59.41 | 36.37 | 23.04 | 69.91 | 29.48 | 0.00 | 0.00 | 0.00 |
November | 35.56 | 20.35 | 15.20 | 35.03 | 38.25 | 0.00 | 0.00 | 0.00 |
December | 37.21 | 24.06 | 13.15 | 37.07 | 48.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.27 | 25.44 | 26.83 | 61.27 | 30.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.16 | 13.68 | 13.15 | 31.38 | 14.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.68 | 36.37 | 39.28 | 84.77 | 48.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.43 | 56.77 | 38.66 | 85.17 | 132.67 | 0.00 | 0.00 | 0.00 |
February | 146.85 | 91.12 | 55.74 | 151.75 | 114.75 | 0.00 | 0.00 | 0.00 |
March | 155.78 | 82.36 | 73.42 | 171.16 | 94.75 | 0.00 | 0.00 | 0.00 |
April | 164.61 | 70.65 | 93.96 | 193.10 | 76.78 | 0.00 | 0.00 | 0.00 |
May | 153.37 | 46.76 | 106.61 | 183.33 | 63.28 | 0.00 | 0.00 | 0.00 |
June | 138.76 | 37.14 | 101.62 | 170.67 | 47.54 | 0.00 | 0.00 | 0.00 |
July | 150.76 | 54.74 | 96.02 | 202.77 | 42.02 | 0.00 | 0.00 | 0.00 |
August | 160.72 | 73.85 | 86.87 | 221.54 | 40.24 | 0.00 | 0.00 | 0.00 |
September | 178.26 | 97.50 | 80.76 | 230.09 | 58.52 | 0.00 | 0.00 | 0.00 |
October | 161.25 | 98.72 | 62.53 | 189.75 | 80.01 | 0.00 | 0.00 | 0.00 |
November | 96.50 | 55.24 | 41.26 | 95.07 | 103.83 | 0.00 | 0.00 | 0.00 |
December | 101.00 | 65.32 | 35.69 | 100.63 | 132.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 141.87 | 69.04 | 72.83 | 166.31 | 82.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 95.43 | 37.14 | 35.69 | 85.17 | 40.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 178.26 | 98.72 | 106.61 | 230.09 | 132.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.35 | 44.83 | 30.53 | 68.50 | 98.14 | 0.00 | 0.00 | 0.00 |
February | 115.96 | 71.95 | 44.01 | 119.48 | 86.24 | 0.00 | 0.00 | 0.00 |
March | 123.01 | 65.03 | 57.97 | 133.25 | 71.88 | 0.00 | 0.00 | 0.00 |
April | 129.98 | 55.78 | 74.20 | 148.74 | 58.56 | 0.00 | 0.00 | 0.00 |
May | 121.10 | 36.92 | 84.18 | 140.91 | 46.58 | 0.00 | 0.00 | 0.00 |
June | 109.57 | 29.33 | 80.24 | 131.52 | 33.77 | 0.00 | 0.00 | 0.00 |
July | 119.04 | 43.22 | 75.82 | 156.93 | 28.93 | 0.00 | 0.00 | 0.00 |
August | 126.91 | 58.31 | 68.60 | 172.82 | 26.70 | 0.00 | 0.00 | 0.00 |
September | 140.76 | 76.98 | 63.77 | 179.51 | 41.77 | 0.00 | 0.00 | 0.00 |
October | 127.33 | 77.95 | 49.37 | 147.97 | 59.52 | 0.00 | 0.00 | 0.00 |
November | 76.20 | 43.62 | 32.58 | 75.27 | 76.92 | 0.00 | 0.00 | 0.00 |
December | 79.75 | 51.57 | 28.18 | 79.87 | 97.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.03 | 54.52 | 57.51 | 129.60 | 60.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.35 | 29.33 | 28.18 | 68.50 | 26.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.76 | 77.95 | 84.18 | 179.51 | 98.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.10 | 16.09 | 38.01 | 23.27 | 197.72 | 0.00 | 0.00 | 0.00 |
February | 96.50 | 36.23 | 60.27 | 66.82 | 171.43 | 0.00 | 0.00 | 0.00 |
March | 135.19 | 45.71 | 89.48 | 114.82 | 136.58 | 0.00 | 0.00 | 0.00 |
April | 205.42 | 78.44 | 126.98 | 210.98 | 106.57 | 0.00 | 0.00 | 0.00 |
May | 264.84 | 107.82 | 157.02 | 299.69 | 84.12 | 0.00 | 0.00 | 0.00 |
June | 254.15 | 98.49 | 155.66 | 296.48 | 60.95 | 0.00 | 0.00 | 0.00 |
July | 314.18 | 165.10 | 149.08 | 399.88 | 52.32 | 0.00 | 0.00 | 0.00 |
August | 260.02 | 132.62 | 127.39 | 336.30 | 48.98 | 0.00 | 0.00 | 0.00 |
September | 212.43 | 102.19 | 110.24 | 252.97 | 77.74 | 0.00 | 0.00 | 0.00 |
October | 121.48 | 49.94 | 71.54 | 114.80 | 114.45 | 0.00 | 0.00 | 0.00 |
November | 60.16 | 17.10 | 43.06 | 34.80 | 151.74 | 0.00 | 0.00 | 0.00 |
December | 50.78 | 17.63 | 33.15 | 27.51 | 195.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 169.55 | 72.56 | 96.99 | 182.28 | 116.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.78 | 16.09 | 33.15 | 23.27 | 48.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 314.18 | 165.10 | 157.02 | 399.88 | 197.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.99 | 0.00 | 16.99 | 0.74 | 109.02 | 0.00 | 0.00 | 0.00 |
February | 26.44 | 0.00 | 26.44 | 5.79 | 94.51 | 0.00 | 0.00 | 0.00 |
March | 38.96 | 0.00 | 38.96 | 18.17 | 74.19 | 0.00 | 0.00 | 0.00 |
April | 55.32 | 0.34 | 54.98 | 38.05 | 57.25 | 0.00 | 0.00 | 0.00 |
May | 70.97 | 2.13 | 68.84 | 58.99 | 45.14 | 0.00 | 0.00 | 0.00 |
June | 74.69 | 5.00 | 69.70 | 69.75 | 32.94 | 0.00 | 0.00 | 0.00 |
July | 71.09 | 5.72 | 65.37 | 73.90 | 29.53 | 0.00 | 0.00 | 0.00 |
August | 57.63 | 1.73 | 55.90 | 63.45 | 26.99 | 0.00 | 0.00 | 0.00 |
September | 44.60 | 0.03 | 44.57 | 36.76 | 44.25 | 0.00 | 0.00 | 0.00 |
October | 30.54 | 0.00 | 30.54 | 16.20 | 61.84 | 0.00 | 0.00 | 0.00 |
November | 19.24 | 0.00 | 19.24 | 3.58 | 82.50 | 0.00 | 0.00 | 0.00 |
December | 14.44 | 0.00 | 14.44 | 0.43 | 105.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.49 | 1.26 | 42.24 | 32.31 | 63.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.44 | 0.00 | 14.44 | 0.43 | 26.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.69 | 5.72 | 69.70 | 73.90 | 109.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 54.10 | 16.09 | 38.01 | 24.86 | 195.90 | 0.00 | 0.00 | 0.00 |
February | 96.50 | 36.23 | 60.27 | 70.20 | 168.78 | 0.00 | 0.00 | 0.00 |
March | 135.19 | 45.71 | 89.48 | 118.82 | 134.52 | 0.00 | 0.00 | 0.00 |
April | 205.42 | 78.44 | 126.98 | 213.86 | 106.07 | 0.00 | 0.00 | 0.00 |
May | 264.84 | 107.82 | 157.02 | 297.66 | 86.40 | 0.00 | 0.00 | 0.00 |
June | 254.15 | 98.49 | 155.66 | 292.92 | 64.44 | 0.00 | 0.00 | 0.00 |
July | 314.18 | 165.10 | 149.08 | 394.32 | 57.77 | 0.00 | 0.00 | 0.00 |
August | 260.02 | 132.62 | 127.39 | 334.87 | 52.60 | 0.00 | 0.00 | 0.00 |
September | 212.43 | 102.19 | 110.24 | 252.60 | 80.71 | 0.00 | 0.00 | 0.00 |
October | 121.48 | 49.94 | 71.54 | 118.47 | 112.65 | 0.00 | 0.00 | 0.00 |
November | 60.16 | 17.10 | 43.06 | 36.77 | 149.85 | 0.00 | 0.00 | 0.00 |
December | 50.78 | 17.63 | 33.15 | 29.48 | 192.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 169.55 | 72.56 | 96.99 | 182.80 | 116.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.78 | 16.09 | 33.15 | 24.86 | 52.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 314.18 | 165.10 | 157.02 | 394.32 | 195.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.51 | 65.74 | 44.77 | 96.26 | 150.20 | 0.00 | 0.00 | 0.00 |
February | 170.06 | 105.52 | 64.55 | 170.25 | 131.92 | 0.00 | 0.00 | 0.00 |
March | 180.40 | 95.38 | 85.02 | 191.49 | 109.44 | 0.00 | 0.00 | 0.00 |
April | 190.63 | 81.81 | 108.82 | 215.77 | 87.46 | 0.00 | 0.00 | 0.00 |
May | 177.61 | 54.15 | 123.46 | 206.77 | 68.11 | 0.00 | 0.00 | 0.00 |
June | 160.69 | 43.01 | 117.69 | 193.67 | 48.93 | 0.00 | 0.00 | 0.00 |
July | 174.59 | 63.39 | 111.20 | 232.15 | 40.94 | 0.00 | 0.00 | 0.00 |
August | 186.12 | 85.52 | 100.60 | 254.38 | 38.22 | 0.00 | 0.00 | 0.00 |
September | 206.43 | 112.91 | 93.53 | 262.25 | 61.41 | 0.00 | 0.00 | 0.00 |
October | 186.74 | 114.33 | 72.41 | 213.30 | 90.83 | 0.00 | 0.00 | 0.00 |
November | 111.76 | 63.97 | 47.79 | 106.86 | 118.36 | 0.00 | 0.00 | 0.00 |
December | 116.96 | 75.64 | 41.33 | 113.42 | 149.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 164.30 | 79.96 | 84.34 | 188.12 | 91.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 110.51 | 43.01 | 41.33 | 96.26 | 38.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 206.43 | 114.33 | 123.46 | 262.25 | 150.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.94 | 0.00 | 118.94 | 0.83 | 955.77 | 0.00 | 0.00 | 0.00 |
February | 185.07 | 0.00 | 185.07 | 21.29 | 826.05 | 0.00 | 0.00 | 0.00 |
March | 272.70 | 0.00 | 272.70 | 92.08 | 647.69 | 0.00 | 0.00 | 0.00 |
April | 387.23 | 2.38 | 384.85 | 230.94 | 492.51 | 0.00 | 0.00 | 0.00 |
May | 496.80 | 14.92 | 481.88 | 390.70 | 376.41 | 0.00 | 0.00 | 0.00 |
June | 522.84 | 34.98 | 487.86 | 464.89 | 275.64 | 0.00 | 0.00 | 0.00 |
July | 497.64 | 40.06 | 457.58 | 511.92 | 238.05 | 0.00 | 0.00 | 0.00 |
August | 403.39 | 12.11 | 391.28 | 425.06 | 232.06 | 0.00 | 0.00 | 0.00 |
September | 312.22 | 0.23 | 311.99 | 239.25 | 366.85 | 0.00 | 0.00 | 0.00 |
October | 213.77 | 0.00 | 213.77 | 81.77 | 554.64 | 0.00 | 0.00 | 0.00 |
November | 134.66 | 0.00 | 134.66 | 11.10 | 747.20 | 0.00 | 0.00 | 0.00 |
December | 101.07 | 0.00 | 101.07 | 0.24 | 934.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 304.45 | 8.79 | 295.66 | 207.02 | 552.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.07 | 0.00 | 101.07 | 0.24 | 232.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 522.84 | 40.06 | 487.86 | 511.92 | 955.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.94 | 0.00 | 118.94 | 0.50 | 987.72 | 0.00 | 0.00 | 0.00 |
February | 185.07 | 0.00 | 185.07 | 18.55 | 854.49 | 0.00 | 0.00 | 0.00 |
March | 272.70 | 0.00 | 272.70 | 83.79 | 668.45 | 0.00 | 0.00 | 0.00 |
April | 387.23 | 2.38 | 384.85 | 219.57 | 506.99 | 0.00 | 0.00 | 0.00 |
May | 496.80 | 14.92 | 481.88 | 378.96 | 386.10 | 0.00 | 0.00 | 0.00 |
June | 522.84 | 34.98 | 487.86 | 453.08 | 283.11 | 0.00 | 0.00 | 0.00 |
July | 497.64 | 40.06 | 457.58 | 501.71 | 244.87 | 0.00 | 0.00 | 0.00 |
August | 403.39 | 12.11 | 391.28 | 415.25 | 239.51 | 0.00 | 0.00 | 0.00 |
September | 312.22 | 0.23 | 311.99 | 230.30 | 378.10 | 0.00 | 0.00 | 0.00 |
October | 213.77 | 0.00 | 213.77 | 74.46 | 574.48 | 0.00 | 0.00 | 0.00 |
November | 134.66 | 0.00 | 134.66 | 9.17 | 775.78 | 0.00 | 0.00 | 0.00 |
December | 101.07 | 0.00 | 101.07 | 0.13 | 965.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 304.45 | 8.79 | 295.66 | 199.95 | 570.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.07 | 0.00 | 101.07 | 0.13 | 239.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 522.84 | 40.06 | 487.86 | 501.71 | 987.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.99 | 0.00 | 16.99 | 1.32 | 111.49 | 0.00 | 0.00 | 0.00 |
February | 26.44 | 0.00 | 26.44 | 8.29 | 97.20 | 0.00 | 0.00 | 0.00 |
March | 38.96 | 0.00 | 38.96 | 24.14 | 76.94 | 0.00 | 0.00 | 0.00 |
April | 55.32 | 0.34 | 54.98 | 50.45 | 60.43 | 0.00 | 0.00 | 0.00 |
May | 70.97 | 2.13 | 68.84 | 79.07 | 47.70 | 0.00 | 0.00 | 0.00 |
June | 74.69 | 5.00 | 69.70 | 92.64 | 36.32 | 0.00 | 0.00 | 0.00 |
July | 71.09 | 5.72 | 65.37 | 100.42 | 30.98 | 0.00 | 0.00 | 0.00 |
August | 57.63 | 1.73 | 55.90 | 86.62 | 29.55 | 0.00 | 0.00 | 0.00 |
September | 44.60 | 0.03 | 44.57 | 54.49 | 42.39 | 0.00 | 0.00 | 0.00 |
October | 30.54 | 0.00 | 30.54 | 23.08 | 64.09 | 0.00 | 0.00 | 0.00 |
November | 19.24 | 0.00 | 19.24 | 6.26 | 84.40 | 0.00 | 0.00 | 0.00 |
December | 14.44 | 0.00 | 14.44 | 1.15 | 108.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.49 | 1.26 | 42.24 | 44.21 | 65.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.44 | 0.00 | 14.44 | 1.15 | 29.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.69 | 5.72 | 69.70 | 100.42 | 111.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.53 | 25.44 | 76.09 | 41.95 | 400.59 | 0.00 | 0.00 | 0.00 |
February | 187.04 | 66.25 | 120.79 | 139.39 | 344.42 | 0.00 | 0.00 | 0.00 |
March | 280.32 | 101.65 | 178.67 | 272.17 | 275.04 | 0.00 | 0.00 | 0.00 |
April | 432.94 | 179.66 | 253.29 | 506.46 | 219.34 | 0.00 | 0.00 | 0.00 |
May | 460.98 | 160.51 | 300.48 | 577.32 | 179.18 | 0.00 | 0.00 | 0.00 |
June | 551.74 | 240.14 | 311.60 | 735.55 | 136.79 | 0.00 | 0.00 | 0.00 |
July | 514.55 | 231.34 | 283.21 | 728.73 | 114.85 | 0.00 | 0.00 | 0.00 |
August | 505.11 | 252.66 | 252.44 | 736.59 | 110.39 | 0.00 | 0.00 | 0.00 |
September | 374.06 | 172.82 | 201.24 | 501.05 | 155.28 | 0.00 | 0.00 | 0.00 |
October | 244.59 | 104.51 | 140.08 | 268.80 | 233.22 | 0.00 | 0.00 | 0.00 |
November | 119.70 | 33.90 | 85.80 | 82.03 | 307.29 | 0.00 | 0.00 | 0.00 |
December | 97.92 | 31.47 | 66.44 | 54.15 | 392.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 323.14 | 133.66 | 189.48 | 388.29 | 238.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 97.92 | 25.44 | 66.44 | 41.95 | 110.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 551.74 | 252.66 | 311.60 | 736.59 | 400.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.35 | 44.83 | 30.53 | 72.12 | 101.41 | 0.00 | 0.00 | 0.00 |
February | 115.96 | 71.95 | 44.01 | 127.01 | 89.20 | 0.00 | 0.00 | 0.00 |
March | 123.01 | 65.03 | 57.97 | 143.98 | 74.56 | 0.00 | 0.00 | 0.00 |
April | 129.98 | 55.78 | 74.20 | 164.11 | 61.79 | 0.00 | 0.00 | 0.00 |
May | 121.10 | 36.92 | 84.18 | 160.21 | 49.73 | 0.00 | 0.00 | 0.00 |
June | 109.57 | 29.33 | 80.24 | 152.56 | 38.53 | 0.00 | 0.00 | 0.00 |
July | 119.04 | 43.22 | 75.82 | 180.56 | 32.61 | 0.00 | 0.00 | 0.00 |
August | 126.91 | 58.31 | 68.60 | 195.84 | 30.73 | 0.00 | 0.00 | 0.00 |
September | 140.76 | 76.98 | 63.77 | 199.31 | 42.14 | 0.00 | 0.00 | 0.00 |
October | 127.33 | 77.95 | 49.37 | 160.10 | 62.43 | 0.00 | 0.00 | 0.00 |
November | 76.20 | 43.62 | 32.58 | 81.14 | 79.63 | 0.00 | 0.00 | 0.00 |
December | 79.75 | 51.57 | 28.18 | 84.56 | 100.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.03 | 54.52 | 57.51 | 143.53 | 63.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.35 | 29.33 | 28.18 | 72.12 | 30.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.76 | 77.95 | 84.18 | 199.31 | 101.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.52 | 0.00 | 21.52 | 0.37 | 154.92 | 0.00 | 0.00 | 0.00 |
February | 33.48 | 0.00 | 33.48 | 5.30 | 132.67 | 0.00 | 0.00 | 0.00 |
March | 49.34 | 0.00 | 49.34 | 20.09 | 102.15 | 0.00 | 0.00 | 0.00 |
April | 70.06 | 0.43 | 69.63 | 46.94 | 77.69 | 0.00 | 0.00 | 0.00 |
May | 89.88 | 2.70 | 87.19 | 76.45 | 60.78 | 0.00 | 0.00 | 0.00 |
June | 94.60 | 6.33 | 88.27 | 89.51 | 44.97 | 0.00 | 0.00 | 0.00 |
July | 90.04 | 7.25 | 82.79 | 95.96 | 39.63 | 0.00 | 0.00 | 0.00 |
August | 72.98 | 2.19 | 70.79 | 79.51 | 38.53 | 0.00 | 0.00 | 0.00 |
September | 56.49 | 0.04 | 56.45 | 46.07 | 59.84 | 0.00 | 0.00 | 0.00 |
October | 38.68 | 0.00 | 38.68 | 17.76 | 86.30 | 0.00 | 0.00 | 0.00 |
November | 24.36 | 0.00 | 24.36 | 3.11 | 117.57 | 0.00 | 0.00 | 0.00 |
December | 18.29 | 0.00 | 18.29 | 0.13 | 150.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55.08 | 1.59 | 53.49 | 40.32 | 88.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.29 | 0.00 | 18.29 | 0.13 | 38.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.60 | 7.25 | 88.27 | 95.96 | 154.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.25 | 0.00 | 19.25 | 0.33 | 138.60 | 0.00 | 0.00 | 0.00 |
February | 29.96 | 0.00 | 29.96 | 4.74 | 118.70 | 0.00 | 0.00 | 0.00 |
March | 44.14 | 0.00 | 44.14 | 17.98 | 91.40 | 0.00 | 0.00 | 0.00 |
April | 62.68 | 0.39 | 62.30 | 42.00 | 69.51 | 0.00 | 0.00 | 0.00 |
May | 80.42 | 2.41 | 78.01 | 68.40 | 54.38 | 0.00 | 0.00 | 0.00 |
June | 84.63 | 5.66 | 78.97 | 80.08 | 40.23 | 0.00 | 0.00 | 0.00 |
July | 80.56 | 6.48 | 74.07 | 85.86 | 35.46 | 0.00 | 0.00 | 0.00 |
August | 65.30 | 1.96 | 63.34 | 71.14 | 34.47 | 0.00 | 0.00 | 0.00 |
September | 50.54 | 0.04 | 50.50 | 41.22 | 53.54 | 0.00 | 0.00 | 0.00 |
October | 34.60 | 0.00 | 34.60 | 15.89 | 77.21 | 0.00 | 0.00 | 0.00 |
November | 21.80 | 0.00 | 21.80 | 2.78 | 105.18 | 0.00 | 0.00 | 0.00 |
December | 16.36 | 0.00 | 16.36 | 0.12 | 134.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.28 | 1.42 | 47.86 | 36.07 | 79.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.36 | 0.00 | 16.36 | 0.12 | 34.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.63 | 6.48 | 78.97 | 85.86 | 138.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 281.32 | 167.35 | 113.97 | 246.56 | 401.30 | 0.00 | 0.00 | 0.00 |
February | 432.91 | 268.60 | 164.31 | 439.53 | 346.83 | 0.00 | 0.00 | 0.00 |
March | 459.23 | 242.79 | 216.43 | 495.09 | 287.16 | 0.00 | 0.00 | 0.00 |
April | 485.25 | 208.26 | 277.00 | 556.58 | 233.24 | 0.00 | 0.00 | 0.00 |
May | 452.11 | 137.83 | 314.28 | 527.71 | 190.47 | 0.00 | 0.00 | 0.00 |
June | 409.06 | 109.48 | 299.58 | 488.75 | 145.07 | 0.00 | 0.00 | 0.00 |
July | 444.42 | 161.37 | 283.05 | 583.36 | 128.18 | 0.00 | 0.00 | 0.00 |
August | 473.79 | 217.70 | 256.09 | 640.99 | 121.92 | 0.00 | 0.00 | 0.00 |
September | 525.49 | 287.41 | 238.08 | 669.03 | 174.53 | 0.00 | 0.00 | 0.00 |
October | 475.35 | 291.03 | 184.33 | 550.75 | 240.98 | 0.00 | 0.00 | 0.00 |
November | 284.48 | 162.84 | 121.64 | 274.70 | 315.83 | 0.00 | 0.00 | 0.00 |
December | 297.74 | 192.54 | 105.20 | 292.33 | 398.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 418.23 | 203.53 | 214.69 | 480.60 | 248.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 281.32 | 109.48 | 105.20 | 246.56 | 121.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 525.49 | 291.03 | 314.28 | 669.03 | 401.30 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102079E+10 | 0.607247E+09 | 0.413543E+09 | 0.915460E+09 | 0.132105E+10 |
February | 0.141883E+10 | 0.880309E+09 | 0.538522E+09 | 0.145594E+10 | 0.104797E+10 |
March | 0.166635E+10 | 0.881003E+09 | 0.785345E+09 | 0.180903E+10 | 0.963321E+09 |
April | 0.170398E+10 | 0.731303E+09 | 0.972674E+09 | 0.197919E+10 | 0.748717E+09 |
May | 0.164051E+10 | 0.500145E+09 | 0.114037E+10 | 0.195815E+10 | 0.613733E+09 |
June | 0.143641E+10 | 0.384441E+09 | 0.105197E+10 | 0.177590E+10 | 0.436840E+09 |
July | 0.161261E+10 | 0.585540E+09 | 0.102707E+10 | 0.216622E+10 | 0.397984E+09 |
August | 0.171918E+10 | 0.789956E+09 | 0.929228E+09 | 0.235888E+10 | 0.384289E+09 |
September | 0.184527E+10 | 0.100924E+10 | 0.836033E+09 | 0.235386E+10 | 0.558527E+09 |
October | 0.172485E+10 | 0.105602E+10 | 0.668837E+09 | 0.200570E+10 | 0.813750E+09 |
November | 0.998973E+09 | 0.571820E+09 | 0.427153E+09 | 0.977350E+09 | 0.101156E+10 |
December | 0.108037E+10 | 0.698661E+09 | 0.381712E+09 | 0.106898E+10 | 0.132652E+10 |
Annual Sum or Average | 0.178681E+11 | 0.869568E+10 | 0.917246E+10 | 0.208247E+11 | 0.962425E+10 |
Minimum of Months | 0.998973E+09 | 0.384441E+09 | 0.381712E+09 | 0.915460E+09 | 0.384289E+09 |
Maximum of Months | 0.184527E+10 | 0.105602E+10 | 0.114037E+10 | 0.235888E+10 | 0.132652E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287448E+10 | 0.170997E+10 | 0.116451E+10 | 0.254001E+10 | 0.382451E+10 |
February | 0.399533E+10 | 0.247889E+10 | 0.151644E+10 | 0.404919E+10 | 0.305984E+10 |
March | 0.469233E+10 | 0.248085E+10 | 0.221148E+10 | 0.503330E+10 | 0.286255E+10 |
April | 0.479829E+10 | 0.205930E+10 | 0.273898E+10 | 0.550235E+10 | 0.225162E+10 |
May | 0.461958E+10 | 0.140838E+10 | 0.321120E+10 | 0.543602E+10 | 0.187043E+10 |
June | 0.404484E+10 | 0.108256E+10 | 0.296227E+10 | 0.491093E+10 | 0.137133E+10 |
July | 0.454101E+10 | 0.164884E+10 | 0.289217E+10 | 0.601957E+10 | 0.125278E+10 |
August | 0.484111E+10 | 0.222446E+10 | 0.261664E+10 | 0.656696E+10 | 0.122114E+10 |
September | 0.519617E+10 | 0.284196E+10 | 0.235421E+10 | 0.656175E+10 | 0.171958E+10 |
October | 0.485707E+10 | 0.297367E+10 | 0.188340E+10 | 0.558367E+10 | 0.246005E+10 |
November | 0.281304E+10 | 0.161021E+10 | 0.120283E+10 | 0.271014E+10 | 0.297328E+10 |
December | 0.304226E+10 | 0.196738E+10 | 0.107488E+10 | 0.297297E+10 | 0.384963E+10 |
Annual Sum or Average | 0.503155E+11 | 0.244865E+11 | 0.258290E+11 | 0.578869E+11 | 0.287168E+11 |
Minimum of Months | 0.281304E+10 | 0.108256E+10 | 0.107488E+10 | 0.254001E+10 | 0.122114E+10 |
Maximum of Months | 0.519617E+10 | 0.297367E+10 | 0.321120E+10 | 0.656696E+10 | 0.384963E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373411E+10 | 0.222134E+10 | 0.151276E+10 | 0.331878E+10 | 0.532073E+10 |
February | 0.519017E+10 | 0.322022E+10 | 0.196994E+10 | 0.531398E+10 | 0.423733E+10 |
March | 0.609560E+10 | 0.322276E+10 | 0.287284E+10 | 0.661549E+10 | 0.398609E+10 |
April | 0.623325E+10 | 0.267515E+10 | 0.355810E+10 | 0.722956E+10 | 0.314022E+10 |
May | 0.600109E+10 | 0.182956E+10 | 0.417153E+10 | 0.712458E+10 | 0.263897E+10 |
June | 0.525447E+10 | 0.140631E+10 | 0.384816E+10 | 0.641481E+10 | 0.195129E+10 |
July | 0.589903E+10 | 0.214194E+10 | 0.375709E+10 | 0.789503E+10 | 0.177559E+10 |
August | 0.628888E+10 | 0.288971E+10 | 0.339917E+10 | 0.862619E+10 | 0.171582E+10 |
September | 0.675012E+10 | 0.369187E+10 | 0.305826E+10 | 0.862335E+10 | 0.240436E+10 |
October | 0.630961E+10 | 0.386297E+10 | 0.244665E+10 | 0.732961E+10 | 0.344579E+10 |
November | 0.365430E+10 | 0.209175E+10 | 0.156255E+10 | 0.353282E+10 | 0.418135E+10 |
December | 0.395207E+10 | 0.255574E+10 | 0.139632E+10 | 0.389049E+10 | 0.536003E+10 |
Annual Sum or Average | 0.653627E+11 | 0.318093E+11 | 0.335534E+11 | 0.759147E+11 | 0.401576E+11 |
Minimum of Months | 0.365430E+10 | 0.140631E+10 | 0.139632E+10 | 0.331878E+10 | 0.171582E+10 |
Maximum of Months | 0.675012E+10 | 0.386297E+10 | 0.417153E+10 | 0.862619E+10 | 0.536003E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201828E+09 | 0.120063E+09 | 81764855.83 | 0.183047E+09 | 0.264950E+09 |
February | 0.280528E+09 | 0.174052E+09 | 0.106476E+09 | 0.289551E+09 | 0.210110E+09 |
March | 0.329467E+09 | 0.174190E+09 | 0.155277E+09 | 0.358492E+09 | 0.193687E+09 |
April | 0.336907E+09 | 0.144591E+09 | 0.192316E+09 | 0.388614E+09 | 0.152090E+09 |
May | 0.324360E+09 | 98887279.29 | 0.225472E+09 | 0.381170E+09 | 0.125167E+09 |
June | 0.284005E+09 | 76010646.67 | 0.207994E+09 | 0.344660E+09 | 87978712.67 |
July | 0.318843E+09 | 0.115771E+09 | 0.203072E+09 | 0.424398E+09 | 77924101.96 |
August | 0.339914E+09 | 0.156188E+09 | 0.183726E+09 | 0.466132E+09 | 72461517.02 |
September | 0.364844E+09 | 0.199544E+09 | 0.165299E+09 | 0.467471E+09 | 0.109454E+09 |
October | 0.341034E+09 | 0.208792E+09 | 0.132241E+09 | 0.397963E+09 | 0.161101E+09 |
November | 0.197514E+09 | 0.113059E+09 | 84455881.64 | 0.195123E+09 | 0.201394E+09 |
December | 0.213609E+09 | 0.138137E+09 | 75471285.47 | 0.213762E+09 | 0.263770E+09 |
Annual Sum or Average | 0.353285E+10 | 0.171929E+10 | 0.181357E+10 | 0.411038E+10 | 0.192009E+10 |
Minimum of Months | 0.197514E+09 | 76010646.67 | 75471285.47 | 0.183047E+09 | 72461517.02 |
Maximum of Months | 0.364844E+09 | 0.208792E+09 | 0.225472E+09 | 0.467471E+09 | 0.264950E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144896E+09 | 43103720.32 | 0.101793E+09 | 61381468.81 | 0.534967E+09 |
February | 0.233458E+09 | 87642964.17 | 0.145815E+09 | 0.161896E+09 | 0.418606E+09 |
March | 0.362082E+09 | 0.122417E+09 | 0.239665E+09 | 0.309496E+09 | 0.368821E+09 |
April | 0.532452E+09 | 0.203310E+09 | 0.329141E+09 | 0.552458E+09 | 0.277196E+09 |
May | 0.709342E+09 | 0.288786E+09 | 0.420557E+09 | 0.810720E+09 | 0.226455E+09 |
June | 0.658756E+09 | 0.255289E+09 | 0.403468E+09 | 0.776451E+09 | 0.159150E+09 |
July | 0.841502E+09 | 0.442194E+09 | 0.399308E+09 | 0.108026E+10 | 0.141305E+09 |
August | 0.696429E+09 | 0.355219E+09 | 0.341210E+09 | 0.907274E+09 | 0.133217E+09 |
September | 0.550628E+09 | 0.264873E+09 | 0.285755E+09 | 0.659790E+09 | 0.204165E+09 |
October | 0.325383E+09 | 0.133761E+09 | 0.191622E+09 | 0.309218E+09 | 0.310507E+09 |
November | 0.155943E+09 | 44331374.38 | 0.111611E+09 | 89753277.94 | 0.398341E+09 |
December | 0.136017E+09 | 47217705.85 | 88798972.09 | 73212434.11 | 0.529476E+09 |
Annual Sum or Average | 0.534689E+10 | 0.228814E+10 | 0.305874E+10 | 0.579191E+10 | 0.370221E+10 |
Minimum of Months | 0.136017E+09 | 43103720.32 | 88798972.09 | 61381468.81 | 0.133217E+09 |
Maximum of Months | 0.841502E+09 | 0.442194E+09 | 0.420557E+09 | 0.108026E+10 | 0.534967E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45510498.67 | 0.00 | 45510498.67 | 1760384.81 | 0.295554E+09 |
February | 63962484.45 | 0.00 | 63962484.45 | 13562117.93 | 0.231031E+09 |
March | 0.104345E+09 | 340.22 | 0.104345E+09 | 48372113.54 | 0.200468E+09 |
April | 0.143391E+09 | 882204.25 | 0.142509E+09 | 99667721.49 | 0.148879E+09 |
May | 0.190097E+09 | 5707817.87 | 0.184389E+09 | 0.161088E+09 | 0.120385E+09 |
June | 0.193607E+09 | 12952148.54 | 0.180655E+09 | 0.184385E+09 | 84641462.17 |
July | 0.190420E+09 | 15329272.49 | 0.175090E+09 | 0.201958E+09 | 77665024.16 |
August | 0.154354E+09 | 4635653.25 | 0.149719E+09 | 0.171697E+09 | 72262243.62 |
September | 0.115615E+09 | 86607.59 | 0.115529E+09 | 96429832.14 | 0.114514E+09 |
October | 81798730.60 | 0.00 | 81798730.60 | 42764942.49 | 0.168045E+09 |
November | 49862977.19 | 0.00 | 49862977.19 | 8897671.32 | 0.217107E+09 |
December | 38672190.66 | 0.00 | 38672190.66 | 954405.79 | 0.288134E+09 |
Annual Sum or Average | 0.137164E+10 | 39594044.20 | 0.133204E+10 | 0.103154E+10 | 0.201869E+10 |
Minimum of Months | 38672190.66 | 0.00 | 38672190.66 | 954405.79 | 72262243.62 |
Maximum of Months | 0.193607E+09 | 15329272.49 | 0.184389E+09 | 0.201958E+09 | 0.295554E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144896E+09 | 43103720.32 | 0.101793E+09 | 65551396.30 | 0.529689E+09 |
February | 0.233458E+09 | 87642964.17 | 0.145815E+09 | 0.169247E+09 | 0.412228E+09 |
March | 0.362082E+09 | 0.122417E+09 | 0.239665E+09 | 0.319300E+09 | 0.363646E+09 |
April | 0.532452E+09 | 0.203310E+09 | 0.329141E+09 | 0.559638E+09 | 0.275632E+09 |
May | 0.709342E+09 | 0.288786E+09 | 0.420557E+09 | 0.807005E+09 | 0.230453E+09 |
June | 0.658756E+09 | 0.255289E+09 | 0.403468E+09 | 0.769499E+09 | 0.165714E+09 |
July | 0.841502E+09 | 0.442194E+09 | 0.399308E+09 | 0.106838E+10 | 0.152207E+09 |
August | 0.696429E+09 | 0.355219E+09 | 0.341210E+09 | 0.904271E+09 | 0.141061E+09 |
September | 0.550628E+09 | 0.264873E+09 | 0.285755E+09 | 0.659809E+09 | 0.209532E+09 |
October | 0.325383E+09 | 0.133761E+09 | 0.191622E+09 | 0.317994E+09 | 0.306033E+09 |
November | 0.155943E+09 | 44331374.38 | 0.111611E+09 | 94350988.11 | 0.393639E+09 |
December | 0.136017E+09 | 47217705.85 | 88798972.09 | 77920269.19 | 0.523585E+09 |
Annual Sum or Average | 0.534689E+10 | 0.228814E+10 | 0.305874E+10 | 0.581296E+10 | 0.370342E+10 |
Minimum of Months | 0.136017E+09 | 43103720.32 | 88798972.09 | 65551396.30 | 0.141061E+09 |
Maximum of Months | 0.841502E+09 | 0.442194E+09 | 0.420557E+09 | 0.106838E+10 | 0.529689E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161430E+09 | 96031370.32 | 65398878.59 | 0.140435E+09 | 0.226834E+09 |
February | 0.224378E+09 | 0.139214E+09 | 85163535.41 | 0.215113E+09 | 0.208411E+09 |
March | 0.263521E+09 | 0.139324E+09 | 0.124197E+09 | 0.260612E+09 | 0.221219E+09 |
April | 0.269472E+09 | 0.115650E+09 | 0.153822E+09 | 0.280630E+09 | 0.178822E+09 |
May | 0.259436E+09 | 79094093.75 | 0.180342E+09 | 0.273678E+09 | 0.152550E+09 |
June | 0.227159E+09 | 60796426.56 | 0.166362E+09 | 0.242242E+09 | 0.116424E+09 |
July | 0.255024E+09 | 92598617.16 | 0.162425E+09 | 0.307237E+09 | 0.107641E+09 |
August | 0.271877E+09 | 0.124925E+09 | 0.146952E+09 | 0.340313E+09 | 0.104803E+09 |
September | 0.291817E+09 | 0.159604E+09 | 0.132213E+09 | 0.346032E+09 | 0.139874E+09 |
October | 0.272773E+09 | 0.167001E+09 | 0.105772E+09 | 0.290875E+09 | 0.196811E+09 |
November | 0.157980E+09 | 90428875.66 | 67551271.18 | 0.138135E+09 | 0.220833E+09 |
December | 0.170853E+09 | 0.110488E+09 | 60365023.40 | 0.161041E+09 | 0.244134E+09 |
Annual Sum or Average | 0.282572E+10 | 0.137516E+10 | 0.145056E+10 | 0.299634E+10 | 0.211836E+10 |
Minimum of Months | 0.157980E+09 | 60796426.56 | 60365023.40 | 0.138135E+09 | 0.104803E+09 |
Maximum of Months | 0.291817E+09 | 0.167001E+09 | 0.180342E+09 | 0.346032E+09 | 0.244134E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 36413225.08 | 0.00 | 36413225.08 | 842581.78 | 0.251435E+09 |
February | 51176770.43 | 0.00 | 51176770.43 | 9322485.39 | 0.193871E+09 |
March | 83487367.90 | 272.21 | 83487095.69 | 37288028.32 | 0.166114E+09 |
April | 0.114728E+09 | 705856.95 | 0.114022E+09 | 81833603.55 | 0.120377E+09 |
May | 0.152098E+09 | 4566859.58 | 0.147531E+09 | 0.136653E+09 | 94531743.51 |
June | 0.154906E+09 | 10363092.34 | 0.144543E+09 | 0.155766E+09 | 65574223.31 |
July | 0.152356E+09 | 12265043.58 | 0.140091E+09 | 0.174205E+09 | 57355181.66 |
August | 0.123500E+09 | 3709014.18 | 0.119791E+09 | 0.146850E+09 | 53746967.46 |
September | 92504439.09 | 69295.25 | 92435143.84 | 82859686.73 | 87676059.20 |
October | 65447658.79 | 0.00 | 65447658.79 | 33846883.98 | 0.138176E+09 |
November | 39895669.45 | 0.00 | 39895669.45 | 5874765.62 | 0.184698E+09 |
December | 30941853.50 | 0.00 | 30941853.50 | 387576.70 | 0.245003E+09 |
Annual Sum or Average | 0.109745E+10 | 31679434.09 | 0.106578E+10 | 0.865729E+09 | 0.165856E+10 |
Minimum of Months | 30941853.50 | 0.00 | 30941853.50 | 387576.70 | 53746967.46 |
Maximum of Months | 0.154906E+09 | 12265043.58 | 0.147531E+09 | 0.174205E+09 | 0.251435E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135983E+09 | 34077660.85 | 0.101905E+09 | 45778809.94 | 0.529994E+09 |
February | 0.226258E+09 | 80141237.88 | 0.146117E+09 | 0.144699E+09 | 0.410828E+09 |
March | 0.375425E+09 | 0.136136E+09 | 0.239289E+09 | 0.315068E+09 | 0.356772E+09 |
April | 0.561134E+09 | 0.232853E+09 | 0.328282E+09 | 0.579473E+09 | 0.266408E+09 |
May | 0.617389E+09 | 0.214964E+09 | 0.402426E+09 | 0.679798E+09 | 0.219613E+09 |
June | 0.715100E+09 | 0.311241E+09 | 0.403858E+09 | 0.850558E+09 | 0.152737E+09 |
July | 0.689138E+09 | 0.309834E+09 | 0.379304E+09 | 0.862333E+09 | 0.129709E+09 |
August | 0.676486E+09 | 0.338392E+09 | 0.338094E+09 | 0.871755E+09 | 0.124260E+09 |
September | 0.484815E+09 | 0.223992E+09 | 0.260822E+09 | 0.557475E+09 | 0.195198E+09 |
October | 0.327581E+09 | 0.139970E+09 | 0.187611E+09 | 0.305789E+09 | 0.302420E+09 |
November | 0.155138E+09 | 43931896.31 | 0.111207E+09 | 84211931.02 | 0.392831E+09 |
December | 0.131139E+09 | 42150042.10 | 88988570.02 | 59247185.81 | 0.520200E+09 |
Annual Sum or Average | 0.509559E+10 | 0.210768E+10 | 0.298790E+10 | 0.535618E+10 | 0.360097E+10 |
Minimum of Months | 0.131139E+09 | 34077660.85 | 88988570.02 | 45778809.94 | 0.124260E+09 |
Maximum of Months | 0.715100E+09 | 0.338392E+09 | 0.403858E+09 | 0.871755E+09 | 0.529994E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201828E+09 | 0.120063E+09 | 81764855.83 | 0.182960E+09 | 0.264574E+09 |
February | 0.280528E+09 | 0.174052E+09 | 0.106476E+09 | 0.288854E+09 | 0.209618E+09 |
March | 0.329467E+09 | 0.174190E+09 | 0.155277E+09 | 0.356517E+09 | 0.193157E+09 |
April | 0.336907E+09 | 0.144591E+09 | 0.192316E+09 | 0.385778E+09 | 0.151537E+09 |
May | 0.324360E+09 | 98887279.29 | 0.225472E+09 | 0.380855E+09 | 0.123481E+09 |
June | 0.284005E+09 | 76010646.67 | 0.207994E+09 | 0.341952E+09 | 87180650.33 |
July | 0.318843E+09 | 0.115771E+09 | 0.203072E+09 | 0.424506E+09 | 75746862.31 |
August | 0.339914E+09 | 0.156188E+09 | 0.183726E+09 | 0.464776E+09 | 71339112.04 |
September | 0.364844E+09 | 0.199544E+09 | 0.165299E+09 | 0.467122E+09 | 0.107560E+09 |
October | 0.341034E+09 | 0.208792E+09 | 0.132241E+09 | 0.396698E+09 | 0.160332E+09 |
November | 0.197514E+09 | 0.113059E+09 | 84455881.64 | 0.194780E+09 | 0.201068E+09 |
December | 0.213609E+09 | 0.138137E+09 | 75471285.47 | 0.213639E+09 | 0.263354E+09 |
Annual Sum or Average | 0.353285E+10 | 0.171929E+10 | 0.181357E+10 | 0.409844E+10 | 0.190895E+10 |
Minimum of Months | 0.197514E+09 | 76010646.67 | 75471285.47 | 0.182960E+09 | 71339112.04 |
Maximum of Months | 0.364844E+09 | 0.208792E+09 | 0.225472E+09 | 0.467122E+09 | 0.264574E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45510498.67 | 0.00 | 45510498.67 | 1693288.55 | 0.295288E+09 |
February | 63962484.45 | 0.00 | 63962484.45 | 13289509.29 | 0.230657E+09 |
March | 0.104345E+09 | 340.22 | 0.104345E+09 | 46639533.43 | 0.200047E+09 |
April | 0.143391E+09 | 882204.25 | 0.142509E+09 | 97001557.18 | 0.148535E+09 |
May | 0.190097E+09 | 5707817.87 | 0.184389E+09 | 0.163019E+09 | 0.117504E+09 |
June | 0.193607E+09 | 12952148.54 | 0.180655E+09 | 0.183041E+09 | 82965423.00 |
July | 0.190420E+09 | 15329272.49 | 0.175090E+09 | 0.204918E+09 | 73254670.98 |
August | 0.154354E+09 | 4635653.25 | 0.149719E+09 | 0.169573E+09 | 70041816.13 |
September | 0.115615E+09 | 86607.59 | 0.115529E+09 | 97246638.54 | 0.110444E+09 |
October | 81798730.60 | 0.00 | 81798730.60 | 41440148.37 | 0.166809E+09 |
November | 49862977.19 | 0.00 | 49862977.19 | 8569988.56 | 0.216577E+09 |
December | 38672190.66 | 0.00 | 38672190.66 | 848535.53 | 0.287714E+09 |
Annual Sum or Average | 0.137164E+10 | 39594044.20 | 0.133204E+10 | 0.102728E+10 | 0.199984E+10 |
Minimum of Months | 38672190.66 | 0.00 | 38672190.66 | 848535.53 | 70041816.13 |
Maximum of Months | 0.193607E+09 | 15329272.49 | 0.184389E+09 | 0.204918E+09 | 0.295288E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135983E+09 | 34077660.85 | 0.101905E+09 | 47494331.10 | 0.522242E+09 |
February | 0.226258E+09 | 80141237.88 | 0.146117E+09 | 0.149665E+09 | 0.401312E+09 |
March | 0.375425E+09 | 0.136136E+09 | 0.239289E+09 | 0.324291E+09 | 0.350650E+09 |
April | 0.561134E+09 | 0.232853E+09 | 0.328282E+09 | 0.586422E+09 | 0.264235E+09 |
May | 0.617389E+09 | 0.214964E+09 | 0.402426E+09 | 0.681651E+09 | 0.221610E+09 |
June | 0.715100E+09 | 0.311241E+09 | 0.403858E+09 | 0.847937E+09 | 0.158454E+09 |
July | 0.689138E+09 | 0.309834E+09 | 0.379304E+09 | 0.857492E+09 | 0.137317E+09 |
August | 0.676486E+09 | 0.338392E+09 | 0.338094E+09 | 0.868227E+09 | 0.130650E+09 |
September | 0.484815E+09 | 0.223992E+09 | 0.260822E+09 | 0.561586E+09 | 0.197296E+09 |
October | 0.327581E+09 | 0.139970E+09 | 0.187611E+09 | 0.314569E+09 | 0.296867E+09 |
November | 0.155138E+09 | 43931896.31 | 0.111207E+09 | 87349006.79 | 0.386153E+09 |
December | 0.131139E+09 | 42150042.10 | 88988570.02 | 61451744.12 | 0.511496E+09 |
Annual Sum or Average | 0.509559E+10 | 0.210768E+10 | 0.298790E+10 | 0.538814E+10 | 0.357828E+10 |
Minimum of Months | 0.131139E+09 | 34077660.85 | 88988570.02 | 47494331.10 | 0.130650E+09 |
Maximum of Months | 0.715100E+09 | 0.338392E+09 | 0.403858E+09 | 0.868227E+09 | 0.522242E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57636175.01 | 0.00 | 57636175.01 | 1273314.38 | 0.404850E+09 |
February | 81004450.75 | 0.00 | 81004450.75 | 14780276.41 | 0.312142E+09 |
March | 0.132147E+09 | 430.86 | 0.132146E+09 | 59353678.16 | 0.266558E+09 |
April | 0.181596E+09 | 1117256.01 | 0.180479E+09 | 0.130130E+09 | 0.196161E+09 |
May | 0.240746E+09 | 7228591.19 | 0.233517E+09 | 0.214449E+09 | 0.160203E+09 |
June | 0.245191E+09 | 16403078.89 | 0.228788E+09 | 0.243311E+09 | 0.113233E+09 |
July | 0.241154E+09 | 19413556.39 | 0.221741E+09 | 0.268425E+09 | 0.103128E+09 |
August | 0.195480E+09 | 5870762.35 | 0.189609E+09 | 0.221852E+09 | 0.100863E+09 |
September | 0.146419E+09 | 109683.05 | 0.146310E+09 | 0.125797E+09 | 0.153757E+09 |
October | 0.103593E+09 | 0.00 | 0.103593E+09 | 52072487.71 | 0.226780E+09 |
November | 63148314.43 | 0.00 | 63148314.43 | 9576681.38 | 0.295451E+09 |
December | 48975889.39 | 0.00 | 48975889.39 | 531894.76 | 0.394621E+09 |
Annual Sum or Average | 0.173709E+10 | 50143358.74 | 0.168695E+10 | 0.134155E+10 | 0.272775E+10 |
Minimum of Months | 48975889.39 | 0.00 | 48975889.39 | 531894.76 | 0.100863E+09 |
Maximum of Months | 0.245191E+09 | 19413556.39 | 0.233517E+09 | 0.268425E+09 | 0.404850E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 21247080.64 | 0.00 | 21247080.64 | 469396.40 | 0.149244E+09 |
February | 29861594.68 | 0.00 | 29861594.68 | 5448621.89 | 0.115068E+09 |
March | 48714796.18 | 158.83 | 48714637.34 | 21880223.41 | 98264286.02 |
April | 66943790.08 | 411866.83 | 66531923.25 | 47971336.25 | 72313144.00 |
May | 88748888.58 | 2664758.02 | 86084130.55 | 79054625.35 | 59057498.08 |
June | 90387603.67 | 6046854.08 | 84340749.59 | 89694516.15 | 41742276.92 |
July | 88899508.73 | 7156640.74 | 81742867.99 | 98952717.99 | 38017213.89 |
August | 72062069.48 | 2164206.09 | 69897863.39 | 81783679.99 | 37182436.20 |
September | 53976248.26 | 40433.71 | 53935814.54 | 46374069.85 | 56681079.97 |
October | 38188643.85 | 0.00 | 38188643.85 | 19196075.12 | 83600541.83 |
November | 23279083.47 | 0.00 | 23279083.47 | 3530361.29 | 0.108916E+09 |
December | 18054540.76 | 0.00 | 18054540.76 | 196078.43 | 0.145474E+09 |
Annual Sum or Average | 0.640364E+09 | 18484918.30 | 0.621879E+09 | 0.494552E+09 | 0.100556E+10 |
Minimum of Months | 18054540.76 | 0.00 | 18054540.76 | 196078.43 | 37182436.20 |
Maximum of Months | 90387603.67 | 7156640.74 | 86084130.55 | 98952717.99 | 0.149244E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94172104.10 | 56020951.86 | 38151152.24 | 84049815.21 | 0.130916E+09 |
February | 0.130893E+09 | 81212052.17 | 49681081.31 | 0.135255E+09 | 0.102279E+09 |
March | 0.153728E+09 | 81276128.21 | 72451757.76 | 0.168905E+09 | 93498179.98 |
April | 0.157199E+09 | 67465641.93 | 89733781.59 | 0.184408E+09 | 73326044.54 |
May | 0.151345E+09 | 46140406.03 | 0.105205E+09 | 0.180908E+09 | 62445161.43 |
June | 0.132516E+09 | 35466261.44 | 97049331.00 | 0.162988E+09 | 45400840.71 |
July | 0.148771E+09 | 54018417.70 | 94752617.30 | 0.200096E+09 | 41464764.80 |
August | 0.158603E+09 | 72876646.06 | 85725869.59 | 0.218621E+09 | 39713793.22 |
September | 0.170235E+09 | 93106622.21 | 77128015.79 | 0.219726E+09 | 55885171.63 |
October | 0.159125E+09 | 97421719.72 | 61703299.94 | 0.187251E+09 | 78955997.12 |
November | 92159449.27 | 52752675.23 | 39406774.04 | 90792301.29 | 99151413.46 |
December | 99668866.61 | 64454268.94 | 35214597.67 | 99301182.93 | 0.130405E+09 |
Annual Sum or Average | 0.164841E+10 | 0.802212E+09 | 0.846203E+09 | 0.193230E+10 | 0.953441E+09 |
Minimum of Months | 92159449.27 | 35466261.44 | 35214597.67 | 84049815.21 | 39713793.22 |
Maximum of Months | 0.170235E+09 | 97421719.72 | 0.105205E+09 | 0.219726E+09 | 0.130916E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.255602E+09 | 0.152052E+09 | 0.103550E+09 | 0.228128E+09 | 0.355332E+09 |
February | 0.355271E+09 | 0.220426E+09 | 0.134845E+09 | 0.367110E+09 | 0.277607E+09 |
March | 0.417249E+09 | 0.220600E+09 | 0.196649E+09 | 0.458444E+09 | 0.253773E+09 |
April | 0.426671E+09 | 0.183116E+09 | 0.243556E+09 | 0.500520E+09 | 0.199022E+09 |
May | 0.410781E+09 | 0.125234E+09 | 0.285547E+09 | 0.491022E+09 | 0.169489E+09 |
June | 0.359674E+09 | 96262688.00 | 0.263412E+09 | 0.442384E+09 | 0.123227E+09 |
July | 0.403795E+09 | 0.146617E+09 | 0.257178E+09 | 0.543102E+09 | 0.112544E+09 |
August | 0.430480E+09 | 0.197802E+09 | 0.232678E+09 | 0.593383E+09 | 0.107791E+09 |
September | 0.462052E+09 | 0.252710E+09 | 0.209341E+09 | 0.596382E+09 | 0.151684E+09 |
October | 0.431898E+09 | 0.264422E+09 | 0.167475E+09 | 0.508237E+09 | 0.214303E+09 |
November | 0.250140E+09 | 0.143182E+09 | 0.106958E+09 | 0.246429E+09 | 0.269117E+09 |
December | 0.270522E+09 | 0.174942E+09 | 95579621.07 | 0.269524E+09 | 0.353946E+09 |
Annual Sum or Average | 0.447413E+10 | 0.217737E+10 | 0.229677E+10 | 0.524466E+10 | 0.258783E+10 |
Minimum of Months | 0.250140E+09 | 96262688.00 | 95579621.07 | 0.228128E+09 | 0.107791E+09 |
Maximum of Months | 0.462052E+09 | 0.264422E+09 | 0.285547E+09 | 0.596382E+09 | 0.355332E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201828E+09 | 0.120063E+09 | 81764855.83 | 0.183467E+09 | 0.262866E+09 |
February | 0.280528E+09 | 0.174052E+09 | 0.106476E+09 | 0.289048E+09 | 0.208632E+09 |
March | 0.329467E+09 | 0.174190E+09 | 0.155277E+09 | 0.356888E+09 | 0.192529E+09 |
April | 0.336907E+09 | 0.144591E+09 | 0.192316E+09 | 0.385526E+09 | 0.151788E+09 |
May | 0.324360E+09 | 98887279.29 | 0.225472E+09 | 0.377404E+09 | 0.124747E+09 |
June | 0.284005E+09 | 76010646.67 | 0.207994E+09 | 0.340912E+09 | 87521275.80 |
July | 0.318843E+09 | 0.115771E+09 | 0.203072E+09 | 0.420323E+09 | 77492773.76 |
August | 0.339914E+09 | 0.156188E+09 | 0.183726E+09 | 0.462872E+09 | 71516671.98 |
September | 0.364844E+09 | 0.199544E+09 | 0.165299E+09 | 0.465284E+09 | 0.108256E+09 |
October | 0.341034E+09 | 0.208792E+09 | 0.132241E+09 | 0.396326E+09 | 0.159429E+09 |
November | 0.197514E+09 | 0.113059E+09 | 84455881.64 | 0.195108E+09 | 0.199368E+09 |
December | 0.213609E+09 | 0.138137E+09 | 75471285.47 | 0.213922E+09 | 0.261203E+09 |
Annual Sum or Average | 0.353285E+10 | 0.171929E+10 | 0.181357E+10 | 0.408708E+10 | 0.190535E+10 |
Minimum of Months | 0.197514E+09 | 76010646.67 | 75471285.47 | 0.183467E+09 | 71516671.98 |
Maximum of Months | 0.364844E+09 | 0.208792E+09 | 0.225472E+09 | 0.465284E+09 | 0.262866E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144896E+09 | 43103720.32 | 0.101793E+09 | 62322547.91 | 0.529586E+09 |
February | 0.233458E+09 | 87642964.17 | 0.145815E+09 | 0.161652E+09 | 0.414717E+09 |
March | 0.362082E+09 | 0.122417E+09 | 0.239665E+09 | 0.307536E+09 | 0.365813E+09 |
April | 0.532452E+09 | 0.203310E+09 | 0.329141E+09 | 0.546872E+09 | 0.276232E+09 |
May | 0.709342E+09 | 0.288786E+09 | 0.420557E+09 | 0.802686E+09 | 0.225297E+09 |
June | 0.658756E+09 | 0.255289E+09 | 0.403468E+09 | 0.768485E+09 | 0.157982E+09 |
July | 0.841502E+09 | 0.442194E+09 | 0.399308E+09 | 0.107105E+10 | 0.140128E+09 |
August | 0.696429E+09 | 0.355219E+09 | 0.341210E+09 | 0.900754E+09 | 0.131193E+09 |
September | 0.550628E+09 | 0.264873E+09 | 0.285755E+09 | 0.655699E+09 | 0.201499E+09 |
October | 0.325383E+09 | 0.133761E+09 | 0.191622E+09 | 0.307475E+09 | 0.306550E+09 |
November | 0.155943E+09 | 44331374.38 | 0.111611E+09 | 90212461.37 | 0.393299E+09 |
December | 0.136017E+09 | 47217705.85 | 88798972.09 | 73684461.24 | 0.522715E+09 |
Annual Sum or Average | 0.534689E+10 | 0.228814E+10 | 0.305874E+10 | 0.574842E+10 | 0.366501E+10 |
Minimum of Months | 0.136017E+09 | 43103720.32 | 88798972.09 | 62322547.91 | 0.131193E+09 |
Maximum of Months | 0.841502E+09 | 0.442194E+09 | 0.420557E+09 | 0.107105E+10 | 0.529586E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45510498.67 | 0.00 | 45510498.67 | 1982442.46 | 0.291992E+09 |
February | 63962484.45 | 0.00 | 63962484.45 | 14002943.79 | 0.228633E+09 |
March | 0.104345E+09 | 340.22 | 0.104345E+09 | 48655728.02 | 0.198699E+09 |
April | 0.143391E+09 | 882204.25 | 0.142509E+09 | 98623439.21 | 0.148394E+09 |
May | 0.190097E+09 | 5707817.87 | 0.184389E+09 | 0.158005E+09 | 0.120904E+09 |
June | 0.193607E+09 | 12952148.54 | 0.180655E+09 | 0.180797E+09 | 85379379.99 |
July | 0.190420E+09 | 15329272.49 | 0.175090E+09 | 0.197933E+09 | 79091284.35 |
August | 0.154354E+09 | 4635653.25 | 0.149719E+09 | 0.169955E+09 | 72281205.68 |
September | 0.115615E+09 | 86607.59 | 0.115529E+09 | 95270722.58 | 0.114701E+09 |
October | 81798730.60 | 0.00 | 81798730.60 | 43401119.42 | 0.165629E+09 |
November | 49862977.19 | 0.00 | 49862977.19 | 9276546.41 | 0.213846E+09 |
December | 38672190.66 | 0.00 | 38672190.66 | 1138371.59 | 0.283791E+09 |
Annual Sum or Average | 0.137164E+10 | 39594044.20 | 0.133204E+10 | 0.101904E+10 | 0.200334E+10 |
Minimum of Months | 38672190.66 | 0.00 | 38672190.66 | 1138371.59 | 72281205.68 |
Maximum of Months | 0.193607E+09 | 15329272.49 | 0.184389E+09 | 0.197933E+09 | 0.291992E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144896E+09 | 43103720.32 | 0.101793E+09 | 66585145.75 | 0.524707E+09 |
February | 0.233458E+09 | 87642964.17 | 0.145815E+09 | 0.169825E+09 | 0.408316E+09 |
March | 0.362082E+09 | 0.122417E+09 | 0.239665E+09 | 0.318250E+09 | 0.360296E+09 |
April | 0.532452E+09 | 0.203310E+09 | 0.329141E+09 | 0.554325E+09 | 0.274923E+09 |
May | 0.709342E+09 | 0.288786E+09 | 0.420557E+09 | 0.797258E+09 | 0.231405E+09 |
June | 0.658756E+09 | 0.255289E+09 | 0.403468E+09 | 0.759253E+09 | 0.167018E+09 |
July | 0.841502E+09 | 0.442194E+09 | 0.399308E+09 | 0.105615E+10 | 0.154738E+09 |
August | 0.696429E+09 | 0.355219E+09 | 0.341210E+09 | 0.896921E+09 | 0.140872E+09 |
September | 0.550628E+09 | 0.264873E+09 | 0.285755E+09 | 0.654727E+09 | 0.209203E+09 |
October | 0.325383E+09 | 0.133761E+09 | 0.191622E+09 | 0.317305E+09 | 0.301710E+09 |
November | 0.155943E+09 | 44331374.38 | 0.111611E+09 | 95296252.20 | 0.388409E+09 |
December | 0.136017E+09 | 47217705.85 | 88798972.09 | 78954537.90 | 0.516859E+09 |
Annual Sum or Average | 0.534689E+10 | 0.228814E+10 | 0.305874E+10 | 0.576485E+10 | 0.367846E+10 |
Minimum of Months | 0.136017E+09 | 43103720.32 | 88798972.09 | 66585145.75 | 0.140872E+09 |
Maximum of Months | 0.841502E+09 | 0.442194E+09 | 0.420557E+09 | 0.105615E+10 | 0.524707E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.296000E+09 | 0.176084E+09 | 0.119916E+09 | 0.257829E+09 | 0.402286E+09 |
February | 0.411421E+09 | 0.255264E+09 | 0.156157E+09 | 0.411868E+09 | 0.319138E+09 |
March | 0.483195E+09 | 0.255466E+09 | 0.227729E+09 | 0.512884E+09 | 0.293114E+09 |
April | 0.494106E+09 | 0.212057E+09 | 0.282050E+09 | 0.559273E+09 | 0.226695E+09 |
May | 0.475705E+09 | 0.145028E+09 | 0.330677E+09 | 0.553816E+09 | 0.182415E+09 |
June | 0.416521E+09 | 0.111477E+09 | 0.305044E+09 | 0.501989E+09 | 0.126816E+09 |
July | 0.467614E+09 | 0.169790E+09 | 0.297825E+09 | 0.621798E+09 | 0.109646E+09 |
August | 0.498517E+09 | 0.229065E+09 | 0.269452E+09 | 0.681337E+09 | 0.102379E+09 |
September | 0.535078E+09 | 0.292651E+09 | 0.242427E+09 | 0.679743E+09 | 0.159172E+09 |
October | 0.500159E+09 | 0.306214E+09 | 0.193945E+09 | 0.571299E+09 | 0.243292E+09 |
November | 0.289674E+09 | 0.165811E+09 | 0.123863E+09 | 0.276992E+09 | 0.306779E+09 |
December | 0.313277E+09 | 0.202591E+09 | 0.110686E+09 | 0.303794E+09 | 0.400053E+09 |
Annual Sum or Average | 0.518127E+10 | 0.252150E+10 | 0.265977E+10 | 0.593262E+10 | 0.287178E+10 |
Minimum of Months | 0.289674E+09 | 0.111477E+09 | 0.110686E+09 | 0.257829E+09 | 0.102379E+09 |
Maximum of Months | 0.535078E+09 | 0.306214E+09 | 0.330677E+09 | 0.681337E+09 | 0.402286E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.318561E+09 | 0.00 | 0.318561E+09 | 2233121.73 | 0.255992E+10 |
February | 0.447720E+09 | 0.00 | 0.447720E+09 | 51507234.31 | 0.199839E+10 |
March | 0.730390E+09 | 2381.43 | 0.730388E+09 | 0.246619E+09 | 0.173476E+10 |
April | 0.100370E+10 | 6175195.84 | 0.997525E+09 | 0.598602E+09 | 0.127658E+10 |
May | 0.133063E+10 | 39953211.88 | 0.129068E+10 | 0.104645E+10 | 0.100816E+10 |
June | 0.135520E+10 | 90661606.03 | 0.126454E+10 | 0.120499E+10 | 0.714453E+09 |
July | 0.133289E+10 | 0.107301E+09 | 0.122559E+10 | 0.137112E+10 | 0.637601E+09 |
August | 0.108044E+10 | 32448343.77 | 0.104799E+10 | 0.113848E+10 | 0.621536E+09 |
September | 0.809276E+09 | 606230.16 | 0.808670E+09 | 0.620149E+09 | 0.950862E+09 |
October | 0.572569E+09 | 0.00 | 0.572569E+09 | 0.219010E+09 | 0.148554E+10 |
November | 0.349028E+09 | 0.00 | 0.349028E+09 | 28779805.81 | 0.193675E+10 |
December | 0.270695E+09 | 0.00 | 0.270695E+09 | 655137.40 | 0.250223E+10 |
Annual Sum or Average | 0.960109E+10 | 0.277148E+09 | 0.932395E+10 | 0.652859E+10 | 0.174268E+11 |
Minimum of Months | 0.270695E+09 | 0.00 | 0.270695E+09 | 655137.40 | 0.621536E+09 |
Maximum of Months | 0.135520E+10 | 0.107301E+09 | 0.129068E+10 | 0.137112E+10 | 0.255992E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.318561E+09 | 0.00 | 0.318561E+09 | 1329375.59 | 0.264550E+10 |
February | 0.447720E+09 | 0.00 | 0.447720E+09 | 44880015.42 | 0.206719E+10 |
March | 0.730390E+09 | 2381.43 | 0.730388E+09 | 0.224414E+09 | 0.179038E+10 |
April | 0.100370E+10 | 6175195.84 | 0.997525E+09 | 0.569130E+09 | 0.131412E+10 |
May | 0.133063E+10 | 39953211.88 | 0.129068E+10 | 0.101500E+10 | 0.103414E+10 |
June | 0.135520E+10 | 90661606.03 | 0.126454E+10 | 0.117439E+10 | 0.733826E+09 |
July | 0.133289E+10 | 0.107301E+09 | 0.122559E+10 | 0.134378E+10 | 0.655865E+09 |
August | 0.108044E+10 | 32448343.77 | 0.104799E+10 | 0.111220E+10 | 0.641492E+09 |
September | 0.809276E+09 | 606230.16 | 0.808670E+09 | 0.596926E+09 | 0.980048E+09 |
October | 0.572569E+09 | 0.00 | 0.572569E+09 | 0.199446E+09 | 0.153870E+10 |
November | 0.349028E+09 | 0.00 | 0.349028E+09 | 23771224.84 | 0.201082E+10 |
December | 0.270695E+09 | 0.00 | 0.270695E+09 | 357563.91 | 0.258702E+10 |
Annual Sum or Average | 0.960109E+10 | 0.277148E+09 | 0.932395E+10 | 0.630563E+10 | 0.179991E+11 |
Minimum of Months | 0.270695E+09 | 0.00 | 0.270695E+09 | 357563.91 | 0.641492E+09 |
Maximum of Months | 0.135520E+10 | 0.107301E+09 | 0.129068E+10 | 0.134378E+10 | 0.264550E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45510498.67 | 0.00 | 45510498.67 | 3539192.70 | 0.298609E+09 |
February | 63962484.45 | 0.00 | 63962484.45 | 20046274.61 | 0.235153E+09 |
March | 0.104345E+09 | 340.22 | 0.104345E+09 | 64665758.79 | 0.206081E+09 |
April | 0.143391E+09 | 882204.25 | 0.142509E+09 | 0.130760E+09 | 0.156628E+09 |
May | 0.190097E+09 | 5707817.87 | 0.184389E+09 | 0.211777E+09 | 0.127761E+09 |
June | 0.193607E+09 | 12952148.54 | 0.180655E+09 | 0.240129E+09 | 94138404.67 |
July | 0.190420E+09 | 15329272.49 | 0.175090E+09 | 0.268952E+09 | 82973359.11 |
August | 0.154354E+09 | 4635653.25 | 0.149719E+09 | 0.231996E+09 | 79153379.49 |
September | 0.115615E+09 | 86607.59 | 0.115529E+09 | 0.141233E+09 | 0.109868E+09 |
October | 81798730.60 | 0.00 | 81798730.60 | 61817709.65 | 0.171663E+09 |
November | 49862977.19 | 0.00 | 49862977.19 | 16236138.66 | 0.218768E+09 |
December | 38672190.66 | 0.00 | 38672190.66 | 3090795.07 | 0.289840E+09 |
Annual Sum or Average | 0.137164E+10 | 39594044.20 | 0.133204E+10 | 0.139424E+10 | 0.207064E+10 |
Minimum of Months | 38672190.66 | 0.00 | 38672190.66 | 3090795.07 | 79153379.49 |
Maximum of Months | 0.193607E+09 | 15329272.49 | 0.184389E+09 | 0.268952E+09 | 0.298609E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271947E+09 | 68150481.81 | 0.203796E+09 | 0.112355E+09 | 0.107295E+10 |
February | 0.452484E+09 | 0.160271E+09 | 0.292213E+09 | 0.337220E+09 | 0.833215E+09 |
March | 0.750798E+09 | 0.272253E+09 | 0.478545E+09 | 0.728986E+09 | 0.736664E+09 |
April | 0.112219E+10 | 0.465673E+09 | 0.656516E+09 | 0.131274E+10 | 0.568528E+09 |
May | 0.123469E+10 | 0.429897E+09 | 0.804794E+09 | 0.154629E+10 | 0.479916E+09 |
June | 0.143010E+10 | 0.622438E+09 | 0.807660E+09 | 0.190654E+10 | 0.354558E+09 |
July | 0.137818E+10 | 0.619625E+09 | 0.758553E+09 | 0.195183E+10 | 0.307622E+09 |
August | 0.135288E+10 | 0.676736E+09 | 0.676140E+09 | 0.197288E+10 | 0.295677E+09 |
September | 0.969561E+09 | 0.447953E+09 | 0.521608E+09 | 0.129872E+10 | 0.402498E+09 |
October | 0.655116E+09 | 0.279920E+09 | 0.375195E+09 | 0.719963E+09 | 0.624669E+09 |
November | 0.310255E+09 | 87857553.18 | 0.222397E+09 | 0.212632E+09 | 0.796493E+09 |
December | 0.262259E+09 | 84294097.83 | 0.177965E+09 | 0.145042E+09 | 0.105051E+10 |
Annual Sum or Average | 0.101905E+11 | 0.421507E+10 | 0.597538E+10 | 0.122452E+11 | 0.752330E+10 |
Minimum of Months | 0.262259E+09 | 68150481.81 | 0.177965E+09 | 0.112355E+09 | 0.295677E+09 |
Maximum of Months | 0.143010E+10 | 0.676736E+09 | 0.807660E+09 | 0.197288E+10 | 0.107295E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201828E+09 | 0.120063E+09 | 81764855.83 | 0.193173E+09 | 0.271619E+09 |
February | 0.280528E+09 | 0.174052E+09 | 0.106476E+09 | 0.307269E+09 | 0.215784E+09 |
March | 0.329467E+09 | 0.174190E+09 | 0.155277E+09 | 0.385645E+09 | 0.199709E+09 |
April | 0.336907E+09 | 0.144591E+09 | 0.192316E+09 | 0.425379E+09 | 0.160159E+09 |
May | 0.324360E+09 | 98887279.29 | 0.225472E+09 | 0.429110E+09 | 0.133210E+09 |
June | 0.284005E+09 | 76010646.67 | 0.207994E+09 | 0.395423E+09 | 99881037.49 |
July | 0.318843E+09 | 0.115771E+09 | 0.203072E+09 | 0.483603E+09 | 87333928.45 |
August | 0.339914E+09 | 0.156188E+09 | 0.183726E+09 | 0.524530E+09 | 82314267.07 |
September | 0.364844E+09 | 0.199544E+09 | 0.165299E+09 | 0.516614E+09 | 0.109236E+09 |
October | 0.341034E+09 | 0.208792E+09 | 0.132241E+09 | 0.428802E+09 | 0.167203E+09 |
November | 0.197514E+09 | 0.113059E+09 | 84455881.64 | 0.210325E+09 | 0.206396E+09 |
December | 0.213609E+09 | 0.138137E+09 | 75471285.47 | 0.226484E+09 | 0.269959E+09 |
Annual Sum or Average | 0.353285E+10 | 0.171929E+10 | 0.181357E+10 | 0.452636E+10 | 0.200280E+10 |
Minimum of Months | 0.197514E+09 | 76010646.67 | 75471285.47 | 0.193173E+09 | 82314267.07 |
Maximum of Months | 0.364844E+09 | 0.208792E+09 | 0.225472E+09 | 0.524530E+09 | 0.271619E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57636175.01 | 0.00 | 57636175.01 | 992274.26 | 0.414940E+09 |
February | 81004450.75 | 0.00 | 81004450.75 | 12813949.31 | 0.320953E+09 |
March | 0.132147E+09 | 430.86 | 0.132146E+09 | 53811169.31 | 0.273607E+09 |
April | 0.181596E+09 | 1117256.01 | 0.180479E+09 | 0.121667E+09 | 0.201368E+09 |
May | 0.240746E+09 | 7228591.19 | 0.233517E+09 | 0.204750E+09 | 0.162806E+09 |
June | 0.245191E+09 | 16403078.89 | 0.228788E+09 | 0.232007E+09 | 0.116550E+09 |
July | 0.241154E+09 | 19413556.39 | 0.221741E+09 | 0.257023E+09 | 0.106155E+09 |
August | 0.195480E+09 | 5870762.35 | 0.189609E+09 | 0.212969E+09 | 0.103203E+09 |
September | 0.146419E+09 | 109683.05 | 0.146310E+09 | 0.119407E+09 | 0.155103E+09 |
October | 0.103593E+09 | 0.00 | 0.103593E+09 | 47556709.43 | 0.231137E+09 |
November | 63148314.43 | 0.00 | 63148314.43 | 8056960.01 | 0.304730E+09 |
December | 48975889.39 | 0.00 | 48975889.39 | 361037.40 | 0.403893E+09 |
Annual Sum or Average | 0.173709E+10 | 50143358.74 | 0.168695E+10 | 0.127142E+10 | 0.279445E+10 |
Minimum of Months | 48975889.39 | 0.00 | 48975889.39 | 361037.40 | 0.103203E+09 |
Maximum of Months | 0.245191E+09 | 19413556.39 | 0.233517E+09 | 0.257023E+09 | 0.414940E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51567304.17 | 0.00 | 51567304.17 | 887791.54 | 0.371227E+09 |
February | 72474989.01 | 0.00 | 72474989.01 | 11464689.00 | 0.287157E+09 |
March | 0.118232E+09 | 385.50 | 0.118232E+09 | 48145057.08 | 0.244797E+09 |
April | 0.162475E+09 | 999613.19 | 0.161475E+09 | 0.108856E+09 | 0.180165E+09 |
May | 0.215396E+09 | 6467447.92 | 0.208929E+09 | 0.183191E+09 | 0.145663E+09 |
June | 0.219373E+09 | 14675896.84 | 0.204698E+09 | 0.207578E+09 | 0.104278E+09 |
July | 0.215762E+09 | 17369382.46 | 0.198392E+09 | 0.229959E+09 | 94976977.87 |
August | 0.174897E+09 | 5252593.31 | 0.169644E+09 | 0.190544E+09 | 92335965.53 |
September | 0.131002E+09 | 98133.84 | 0.130904E+09 | 0.106834E+09 | 0.138771E+09 |
October | 92684987.96 | 0.00 | 92684987.96 | 42549168.12 | 0.206799E+09 |
November | 56499036.19 | 0.00 | 56499036.19 | 7208592.65 | 0.272634E+09 |
December | 43818913.81 | 0.00 | 43818913.81 | 323021.53 | 0.361322E+09 |
Annual Sum or Average | 0.155418E+10 | 44863453.06 | 0.150932E+10 | 0.113754E+10 | 0.250013E+10 |
Minimum of Months | 43818913.81 | 0.00 | 43818913.81 | 323021.53 | 92335965.53 |
Maximum of Months | 0.219373E+09 | 17369382.46 | 0.208929E+09 | 0.229959E+09 | 0.371227E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.753484E+09 | 0.448231E+09 | 0.305253E+09 | 0.660376E+09 | 0.107485E+10 |
February | 0.104729E+10 | 0.649789E+09 | 0.397505E+09 | 0.106331E+10 | 0.839056E+09 |
March | 0.123000E+10 | 0.650301E+09 | 0.579696E+09 | 0.132605E+10 | 0.769140E+09 |
April | 0.125777E+10 | 0.539802E+09 | 0.717972E+09 | 0.144266E+10 | 0.604566E+09 |
May | 0.121093E+10 | 0.369176E+09 | 0.841756E+09 | 0.141343E+10 | 0.510142E+09 |
June | 0.106028E+10 | 0.283770E+09 | 0.776505E+09 | 0.126683E+10 | 0.376033E+09 |
July | 0.119034E+10 | 0.432209E+09 | 0.758129E+09 | 0.156246E+10 | 0.343307E+09 |
August | 0.126900E+10 | 0.583096E+09 | 0.685904E+09 | 0.171682E+10 | 0.326558E+09 |
September | 0.136207E+10 | 0.744959E+09 | 0.617112E+09 | 0.173412E+10 | 0.452381E+09 |
October | 0.127318E+10 | 0.779484E+09 | 0.493697E+09 | 0.147514E+10 | 0.645444E+09 |
November | 0.737380E+09 | 0.422081E+09 | 0.315299E+09 | 0.712010E+09 | 0.818620E+09 |
December | 0.797464E+09 | 0.515707E+09 | 0.281757E+09 | 0.782983E+09 | 0.106866E+10 |
Annual Sum or Average | 0.131892E+11 | 0.641861E+10 | 0.677058E+10 | 0.151562E+11 | 0.782875E+10 |
Minimum of Months | 0.737380E+09 | 0.283770E+09 | 0.281757E+09 | 0.660376E+09 | 0.326558E+09 |
Maximum of Months | 0.136207E+10 | 0.779484E+09 | 0.841756E+09 | 0.173412E+10 | 0.107485E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 341.79 | 493.22 | 381.12 | 226.72 | 154.40 | 0.00 | 0.00 |
February | 601.83 | 433.19 | 586.49 | 363.88 | 222.60 | 0.00 | 0.00 |
March | 675.42 | 359.66 | 622.14 | 328.93 | 293.21 | 0.00 | 0.00 |
April | 763.58 | 288.86 | 657.40 | 282.14 | 375.26 | 0.00 | 0.00 |
May | 731.09 | 229.14 | 612.50 | 186.73 | 425.76 | 0.00 | 0.00 |
June | 685.15 | 168.53 | 554.17 | 148.32 | 405.85 | 0.00 | 0.00 |
July | 808.78 | 148.59 | 602.08 | 218.62 | 383.46 | 0.00 | 0.00 |
August | 880.70 | 143.48 | 641.87 | 294.94 | 346.93 | 0.00 | 0.00 |
September | 908.13 | 215.48 | 711.91 | 389.37 | 322.54 | 0.00 | 0.00 |
October | 748.84 | 303.82 | 643.99 | 394.27 | 249.72 | 0.00 | 0.00 |
November | 377.06 | 390.26 | 385.41 | 220.61 | 164.80 | 0.00 | 0.00 |
December | 399.11 | 495.27 | 403.36 | 260.85 | 142.51 | 0.00 | 0.00 |
Annual Sum or Average | 660.35 | 305.18 | 566.59 | 275.74 | 290.86 | 0.00 | 0.00 |
Minimum of Months | 341.79 | 143.48 | 381.12 | 148.32 | 142.51 | 0.00 | 0.00 |
Maximum of Months | 908.13 | 495.27 | 711.91 | 394.27 | 425.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 948.33 | 1427.91 | 1073.21 | 638.43 | 434.78 | 0.00 | 0.00 |
February | 1673.77 | 1264.82 | 1651.51 | 1024.67 | 626.84 | 0.00 | 0.00 |
March | 1879.22 | 1068.75 | 1751.91 | 926.24 | 825.67 | 0.00 | 0.00 |
April | 2122.82 | 868.68 | 1851.19 | 794.48 | 1056.71 | 0.00 | 0.00 |
May | 2029.58 | 698.34 | 1724.75 | 525.83 | 1198.93 | 0.00 | 0.00 |
June | 1894.65 | 529.06 | 1560.51 | 417.65 | 1142.85 | 0.00 | 0.00 |
July | 2247.45 | 467.73 | 1695.42 | 615.61 | 1079.81 | 0.00 | 0.00 |
August | 2451.82 | 455.92 | 1807.46 | 830.52 | 976.94 | 0.00 | 0.00 |
September | 2531.54 | 663.42 | 2004.70 | 1096.43 | 908.26 | 0.00 | 0.00 |
October | 2084.70 | 918.48 | 1813.42 | 1110.24 | 703.18 | 0.00 | 0.00 |
November | 1045.58 | 1147.10 | 1085.28 | 621.22 | 464.06 | 0.00 | 0.00 |
December | 1109.98 | 1437.29 | 1135.85 | 734.54 | 401.31 | 0.00 | 0.00 |
Annual Sum or Average | 1835.58 | 910.60 | 1595.49 | 776.46 | 819.03 | 0.00 | 0.00 |
Minimum of Months | 948.33 | 455.92 | 1073.21 | 417.65 | 401.31 | 0.00 | 0.00 |
Maximum of Months | 2531.54 | 1437.29 | 2004.70 | 1110.24 | 1198.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1239.09 | 1986.53 | 1394.16 | 829.35 | 564.80 | 0.00 | 0.00 |
February | 2196.59 | 1751.54 | 2145.41 | 1331.11 | 814.30 | 0.00 | 0.00 |
March | 2469.94 | 1488.24 | 2275.84 | 1203.24 | 1072.60 | 0.00 | 0.00 |
April | 2789.18 | 1211.50 | 2404.80 | 1032.08 | 1372.72 | 0.00 | 0.00 |
May | 2660.01 | 985.28 | 2240.55 | 683.08 | 1557.47 | 0.00 | 0.00 |
June | 2474.85 | 752.81 | 2027.19 | 542.56 | 1484.63 | 0.00 | 0.00 |
July | 2947.67 | 662.93 | 2202.45 | 799.71 | 1402.74 | 0.00 | 0.00 |
August | 3220.65 | 640.61 | 2348.00 | 1078.89 | 1269.10 | 0.00 | 0.00 |
September | 3326.91 | 927.61 | 2604.21 | 1424.33 | 1179.88 | 0.00 | 0.00 |
October | 2736.56 | 1286.51 | 2355.74 | 1442.27 | 913.47 | 0.00 | 0.00 |
November | 1362.97 | 1613.17 | 1409.84 | 807.00 | 602.84 | 0.00 | 0.00 |
December | 1452.54 | 2001.21 | 1475.53 | 954.20 | 521.33 | 0.00 | 0.00 |
Annual Sum or Average | 2407.24 | 1273.39 | 2072.64 | 1008.67 | 1063.97 | 0.00 | 0.00 |
Minimum of Months | 1239.09 | 640.61 | 1394.16 | 542.56 | 521.33 | 0.00 | 0.00 |
Maximum of Months | 3326.91 | 2001.21 | 2604.21 | 1442.27 | 1557.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 83.10 | 290.49 | 129.45 | 60.92 | 68.53 | 0.00 | 0.00 |
February | 179.45 | 252.72 | 212.46 | 108.17 | 104.29 | 0.00 | 0.00 |
March | 246.75 | 207.37 | 258.19 | 110.74 | 147.45 | 0.00 | 0.00 |
April | 361.51 | 164.06 | 335.40 | 134.22 | 201.18 | 0.00 | 0.00 |
May | 443.92 | 130.20 | 385.94 | 144.74 | 241.20 | 0.00 | 0.00 |
June | 431.81 | 94.62 | 363.72 | 127.82 | 235.90 | 0.00 | 0.00 |
July | 561.14 | 81.22 | 433.22 | 208.32 | 224.90 | 0.00 | 0.00 |
August | 512.40 | 76.42 | 386.93 | 190.94 | 195.99 | 0.00 | 0.00 |
September | 433.98 | 120.08 | 353.19 | 179.17 | 174.02 | 0.00 | 0.00 |
October | 261.73 | 173.77 | 248.81 | 127.89 | 120.92 | 0.00 | 0.00 |
November | 105.75 | 227.22 | 136.36 | 60.72 | 75.64 | 0.00 | 0.00 |
December | 99.78 | 288.80 | 130.54 | 69.20 | 61.33 | 0.00 | 0.00 |
Annual Sum or Average | 310.93 | 175.21 | 281.57 | 127.07 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 83.10 | 76.42 | 129.45 | 60.72 | 61.33 | 0.00 | 0.00 |
Maximum of Months | 561.14 | 290.49 | 433.22 | 208.32 | 241.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 21.92 | 304.90 | 71.09 | 16.09 | 55.00 | 0.00 | 0.00 |
February | 72.36 | 262.69 | 122.94 | 36.23 | 86.71 | 0.00 | 0.00 |
March | 135.51 | 208.85 | 174.14 | 45.71 | 128.44 | 0.00 | 0.00 |
April | 253.39 | 162.81 | 260.74 | 78.78 | 181.96 | 0.00 | 0.00 |
May | 360.37 | 129.92 | 335.81 | 109.95 | 225.86 | 0.00 | 0.00 |
June | 366.40 | 94.98 | 328.84 | 103.49 | 225.36 | 0.00 | 0.00 |
July | 472.90 | 84.44 | 385.28 | 170.82 | 214.46 | 0.00 | 0.00 |
August | 400.85 | 78.78 | 317.65 | 134.35 | 183.29 | 0.00 | 0.00 |
September | 290.85 | 124.11 | 257.04 | 102.22 | 154.82 | 0.00 | 0.00 |
October | 133.29 | 175.60 | 152.02 | 49.94 | 102.08 | 0.00 | 0.00 |
November | 37.98 | 233.78 | 79.40 | 17.10 | 62.30 | 0.00 | 0.00 |
December | 26.83 | 300.44 | 65.22 | 17.63 | 47.59 | 0.00 | 0.00 |
Annual Sum or Average | 215.31 | 179.71 | 213.04 | 73.81 | 139.23 | 0.00 | 0.00 |
Minimum of Months | 21.92 | 78.78 | 65.22 | 16.09 | 47.59 | 0.00 | 0.00 |
Maximum of Months | 472.90 | 304.90 | 385.28 | 170.82 | 225.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 52.43 | 84.69 | 60.27 | 35.85 | 24.42 | 0.00 | 0.00 |
February | 88.92 | 86.15 | 92.75 | 57.55 | 35.20 | 0.00 | 0.00 |
March | 97.30 | 82.59 | 98.39 | 52.02 | 46.37 | 0.00 | 0.00 |
April | 108.27 | 68.99 | 103.96 | 44.62 | 59.34 | 0.00 | 0.00 |
May | 102.18 | 56.96 | 96.86 | 29.53 | 67.33 | 0.00 | 0.00 |
June | 93.46 | 44.92 | 87.64 | 23.46 | 64.18 | 0.00 | 0.00 |
July | 114.71 | 40.19 | 95.22 | 34.57 | 60.64 | 0.00 | 0.00 |
August | 127.06 | 39.13 | 101.51 | 46.64 | 54.87 | 0.00 | 0.00 |
September | 133.50 | 53.96 | 112.58 | 61.58 | 51.01 | 0.00 | 0.00 |
October | 108.60 | 73.48 | 101.84 | 62.35 | 39.49 | 0.00 | 0.00 |
November | 53.29 | 85.20 | 60.95 | 34.89 | 26.06 | 0.00 | 0.00 |
December | 60.13 | 91.15 | 63.79 | 41.25 | 22.54 | 0.00 | 0.00 |
Annual Sum or Average | 95.01 | 67.17 | 89.60 | 43.61 | 46.00 | 0.00 | 0.00 |
Minimum of Months | 52.43 | 39.13 | 60.27 | 23.46 | 22.54 | 0.00 | 0.00 |
Maximum of Months | 133.50 | 91.15 | 112.58 | 62.35 | 67.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.31 | 93.88 | 13.60 | 0.00 | 13.60 | 0.00 | 0.00 |
February | 3.85 | 80.14 | 21.15 | 0.00 | 21.15 | 0.00 | 0.00 |
March | 13.92 | 62.02 | 31.17 | 0.00 | 31.17 | 0.00 | 0.00 |
April | 31.57 | 46.44 | 44.26 | 0.27 | 43.99 | 0.00 | 0.00 |
May | 51.02 | 35.29 | 56.79 | 1.71 | 55.08 | 0.00 | 0.00 |
June | 60.09 | 25.30 | 59.76 | 4.00 | 55.77 | 0.00 | 0.00 |
July | 65.04 | 21.41 | 56.88 | 4.58 | 52.30 | 0.00 | 0.00 |
August | 54.83 | 20.07 | 46.11 | 1.38 | 44.72 | 0.00 | 0.00 |
September | 31.97 | 33.83 | 35.69 | 0.03 | 35.66 | 0.00 | 0.00 |
October | 12.64 | 51.59 | 24.44 | 0.00 | 24.44 | 0.00 | 0.00 |
November | 2.27 | 71.26 | 15.39 | 0.00 | 15.39 | 0.00 | 0.00 |
December | 0.14 | 91.47 | 11.55 | 0.00 | 11.55 | 0.00 | 0.00 |
Annual Sum or Average | 27.45 | 52.59 | 34.80 | 1.00 | 33.80 | 0.00 | 0.00 |
Minimum of Months | 0.14 | 20.07 | 11.55 | 0.00 | 11.55 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 93.88 | 59.76 | 4.58 | 55.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 77.84 | 289.10 | 126.12 | 57.55 | 68.57 | 0.00 | 0.00 |
February | 173.42 | 250.67 | 209.48 | 105.07 | 104.41 | 0.00 | 0.00 |
March | 248.67 | 203.25 | 263.18 | 115.86 | 147.31 | 0.00 | 0.00 |
April | 369.62 | 158.46 | 346.47 | 145.62 | 200.85 | 0.00 | 0.00 |
May | 394.38 | 126.48 | 351.61 | 117.18 | 234.43 | 0.00 | 0.00 |
June | 458.57 | 91.05 | 385.46 | 149.40 | 236.05 | 0.00 | 0.00 |
July | 479.03 | 75.29 | 376.34 | 158.90 | 217.43 | 0.00 | 0.00 |
August | 497.38 | 71.40 | 379.48 | 184.65 | 194.83 | 0.00 | 0.00 |
September | 393.88 | 115.39 | 327.80 | 163.40 | 164.40 | 0.00 | 0.00 |
October | 260.78 | 171.27 | 249.63 | 130.21 | 119.42 | 0.00 | 0.00 |
November | 104.05 | 225.54 | 136.05 | 60.57 | 75.49 | 0.00 | 0.00 |
December | 95.46 | 286.12 | 128.71 | 67.31 | 61.40 | 0.00 | 0.00 |
Annual Sum or Average | 296.71 | 171.62 | 273.61 | 121.35 | 152.25 | 0.00 | 0.00 |
Minimum of Months | 77.84 | 71.40 | 126.12 | 57.55 | 61.40 | 0.00 | 0.00 |
Maximum of Months | 497.38 | 289.10 | 385.46 | 184.65 | 236.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 14.68 | 301.54 | 67.76 | 12.72 | 55.04 | 0.00 | 0.00 |
February | 62.52 | 256.39 | 119.97 | 33.13 | 86.84 | 0.00 | 0.00 |
March | 134.84 | 201.96 | 179.13 | 50.83 | 128.30 | 0.00 | 0.00 |
April | 261.02 | 156.60 | 271.81 | 90.18 | 181.63 | 0.00 | 0.00 |
May | 314.44 | 125.69 | 301.48 | 82.39 | 219.09 | 0.00 | 0.00 |
June | 396.96 | 92.35 | 350.58 | 125.07 | 225.51 | 0.00 | 0.00 |
July | 395.50 | 77.46 | 328.39 | 121.40 | 206.99 | 0.00 | 0.00 |
August | 386.94 | 74.40 | 310.20 | 128.07 | 182.13 | 0.00 | 0.00 |
September | 252.30 | 116.85 | 231.65 | 86.45 | 145.20 | 0.00 | 0.00 |
October | 130.28 | 170.48 | 152.84 | 52.26 | 100.59 | 0.00 | 0.00 |
November | 34.48 | 230.01 | 79.09 | 16.95 | 62.14 | 0.00 | 0.00 |
December | 19.55 | 294.68 | 63.40 | 15.74 | 47.66 | 0.00 | 0.00 |
Annual Sum or Average | 201.03 | 174.48 | 205.07 | 68.09 | 136.98 | 0.00 | 0.00 |
Minimum of Months | 14.68 | 74.40 | 63.40 | 12.72 | 47.66 | 0.00 | 0.00 |
Maximum of Months | 396.96 | 301.54 | 350.58 | 128.07 | 225.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 101.66 | 372.88 | 160.04 | 77.69 | 82.36 | 0.00 | 0.00 |
February | 203.80 | 321.40 | 246.79 | 124.69 | 122.10 | 0.00 | 0.00 |
March | 261.83 | 263.14 | 280.70 | 112.71 | 168.00 | 0.00 | 0.00 |
April | 332.54 | 208.24 | 321.15 | 97.26 | 223.88 | 0.00 | 0.00 |
May | 358.67 | 166.68 | 332.89 | 67.68 | 265.22 | 0.00 | 0.00 |
June | 359.49 | 122.31 | 319.36 | 59.48 | 259.87 | 0.00 | 0.00 |
July | 412.05 | 107.60 | 329.53 | 84.83 | 244.70 | 0.00 | 0.00 |
August | 415.33 | 105.41 | 319.83 | 104.06 | 215.77 | 0.00 | 0.00 |
September | 380.79 | 160.77 | 321.25 | 133.47 | 187.78 | 0.00 | 0.00 |
October | 282.96 | 222.06 | 273.60 | 135.10 | 138.50 | 0.00 | 0.00 |
November | 127.16 | 290.08 | 165.40 | 75.59 | 89.81 | 0.00 | 0.00 |
December | 124.03 | 368.54 | 163.24 | 89.38 | 73.86 | 0.00 | 0.00 |
Annual Sum or Average | 280.43 | 225.31 | 269.53 | 96.66 | 172.88 | 0.00 | 0.00 |
Minimum of Months | 101.66 | 105.41 | 160.04 | 59.48 | 73.86 | 0.00 | 0.00 |
Maximum of Months | 415.33 | 372.88 | 332.89 | 135.10 | 265.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 83.80 | 287.90 | 129.45 | 60.92 | 68.53 | 0.00 | 0.00 |
February | 179.36 | 250.72 | 212.46 | 108.17 | 104.29 | 0.00 | 0.00 |
March | 245.47 | 205.87 | 258.19 | 110.74 | 147.45 | 0.00 | 0.00 |
April | 358.14 | 163.55 | 335.40 | 134.22 | 201.18 | 0.00 | 0.00 |
May | 439.47 | 129.56 | 385.94 | 144.74 | 241.20 | 0.00 | 0.00 |
June | 427.25 | 93.96 | 363.72 | 127.82 | 235.90 | 0.00 | 0.00 |
July | 556.14 | 80.57 | 433.22 | 208.32 | 224.90 | 0.00 | 0.00 |
August | 508.73 | 75.29 | 386.93 | 190.94 | 195.99 | 0.00 | 0.00 |
September | 431.55 | 118.58 | 353.19 | 179.17 | 174.02 | 0.00 | 0.00 |
October | 260.56 | 171.76 | 248.81 | 127.89 | 120.92 | 0.00 | 0.00 |
November | 106.06 | 224.64 | 136.36 | 60.72 | 75.64 | 0.00 | 0.00 |
December | 100.28 | 285.58 | 130.54 | 69.20 | 61.33 | 0.00 | 0.00 |
Annual Sum or Average | 308.88 | 173.63 | 281.57 | 127.07 | 154.50 | 0.00 | 0.00 |
Minimum of Months | 83.80 | 75.29 | 129.45 | 60.72 | 61.33 | 0.00 | 0.00 |
Maximum of Months | 556.14 | 287.90 | 433.22 | 208.32 | 241.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 22.51 | 301.83 | 71.09 | 16.09 | 55.00 | 0.00 | 0.00 |
February | 72.93 | 260.23 | 122.94 | 36.23 | 86.71 | 0.00 | 0.00 |
March | 135.20 | 206.92 | 174.14 | 45.71 | 128.44 | 0.00 | 0.00 |
April | 250.89 | 162.30 | 260.74 | 78.78 | 181.96 | 0.00 | 0.00 |
May | 355.55 | 130.44 | 335.81 | 109.95 | 225.86 | 0.00 | 0.00 |
June | 361.07 | 95.77 | 328.84 | 103.49 | 225.36 | 0.00 | 0.00 |
July | 466.85 | 85.93 | 385.28 | 170.82 | 214.46 | 0.00 | 0.00 |
August | 397.43 | 78.69 | 317.65 | 134.35 | 183.29 | 0.00 | 0.00 |
September | 288.32 | 123.93 | 257.04 | 102.22 | 154.82 | 0.00 | 0.00 |
October | 133.26 | 173.07 | 152.02 | 49.94 | 102.08 | 0.00 | 0.00 |
November | 38.60 | 230.61 | 79.40 | 17.10 | 62.30 | 0.00 | 0.00 |
December | 27.46 | 296.49 | 65.22 | 17.63 | 47.59 | 0.00 | 0.00 |
Annual Sum or Average | 213.41 | 178.46 | 213.04 | 73.81 | 139.23 | 0.00 | 0.00 |
Minimum of Months | 22.51 | 78.69 | 65.22 | 16.09 | 47.59 | 0.00 | 0.00 |
Maximum of Months | 466.85 | 301.83 | 385.28 | 170.82 | 225.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 96.26 | 150.20 | 110.51 | 65.74 | 44.77 | 0.00 | 0.00 |
February | 170.25 | 131.92 | 170.06 | 105.52 | 64.55 | 0.00 | 0.00 |
March | 191.49 | 109.44 | 180.40 | 95.38 | 85.02 | 0.00 | 0.00 |
April | 215.77 | 87.46 | 190.63 | 81.81 | 108.82 | 0.00 | 0.00 |
May | 206.77 | 68.11 | 177.61 | 54.15 | 123.46 | 0.00 | 0.00 |
June | 193.67 | 48.93 | 160.69 | 43.01 | 117.69 | 0.00 | 0.00 |
July | 232.15 | 40.94 | 174.59 | 63.39 | 111.20 | 0.00 | 0.00 |
August | 254.38 | 38.22 | 186.12 | 85.52 | 100.60 | 0.00 | 0.00 |
September | 262.25 | 61.41 | 206.43 | 112.91 | 93.53 | 0.00 | 0.00 |
October | 213.30 | 90.83 | 186.74 | 114.33 | 72.41 | 0.00 | 0.00 |
November | 106.86 | 118.36 | 111.76 | 63.97 | 47.79 | 0.00 | 0.00 |
December | 113.42 | 149.36 | 116.96 | 75.64 | 41.33 | 0.00 | 0.00 |
Annual Sum or Average | 188.12 | 91.06 | 164.30 | 79.96 | 84.34 | 0.00 | 0.00 |
Minimum of Months | 96.26 | 38.22 | 110.51 | 43.01 | 41.33 | 0.00 | 0.00 |
Maximum of Months | 262.25 | 150.20 | 206.43 | 114.33 | 123.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.83 | 955.77 | 118.94 | 0.00 | 118.94 | 0.00 | 0.00 |
February | 21.29 | 826.05 | 185.07 | 0.00 | 185.07 | 0.00 | 0.00 |
March | 92.08 | 647.69 | 272.70 | 0.00 | 272.70 | 0.00 | 0.00 |
April | 230.94 | 492.51 | 387.23 | 2.38 | 384.85 | 0.00 | 0.00 |
May | 390.70 | 376.41 | 496.80 | 14.92 | 481.88 | 0.00 | 0.00 |
June | 464.89 | 275.64 | 522.84 | 34.98 | 487.86 | 0.00 | 0.00 |
July | 511.92 | 238.05 | 497.64 | 40.06 | 457.58 | 0.00 | 0.00 |
August | 425.06 | 232.06 | 403.39 | 12.11 | 391.28 | 0.00 | 0.00 |
September | 239.25 | 366.85 | 312.22 | 0.23 | 311.99 | 0.00 | 0.00 |
October | 81.77 | 554.64 | 213.77 | 0.00 | 213.77 | 0.00 | 0.00 |
November | 11.10 | 747.20 | 134.66 | 0.00 | 134.66 | 0.00 | 0.00 |
December | 0.24 | 934.22 | 101.07 | 0.00 | 101.07 | 0.00 | 0.00 |
Annual Sum or Average | 207.02 | 552.60 | 304.45 | 8.79 | 295.66 | 0.00 | 0.00 |
Minimum of Months | 0.24 | 232.06 | 101.07 | 0.00 | 101.07 | 0.00 | 0.00 |
Maximum of Months | 511.92 | 955.77 | 522.84 | 40.06 | 487.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.50 | 987.72 | 118.94 | 0.00 | 118.94 | 0.00 | 0.00 |
February | 18.55 | 854.49 | 185.07 | 0.00 | 185.07 | 0.00 | 0.00 |
March | 83.79 | 668.45 | 272.70 | 0.00 | 272.70 | 0.00 | 0.00 |
April | 219.57 | 506.99 | 387.23 | 2.38 | 384.85 | 0.00 | 0.00 |
May | 378.96 | 386.10 | 496.80 | 14.92 | 481.88 | 0.00 | 0.00 |
June | 453.08 | 283.11 | 522.84 | 34.98 | 487.86 | 0.00 | 0.00 |
July | 501.71 | 244.87 | 497.64 | 40.06 | 457.58 | 0.00 | 0.00 |
August | 415.25 | 239.51 | 403.39 | 12.11 | 391.28 | 0.00 | 0.00 |
September | 230.30 | 378.10 | 312.22 | 0.23 | 311.99 | 0.00 | 0.00 |
October | 74.46 | 574.48 | 213.77 | 0.00 | 213.77 | 0.00 | 0.00 |
November | 9.17 | 775.78 | 134.66 | 0.00 | 134.66 | 0.00 | 0.00 |
December | 0.13 | 965.88 | 101.07 | 0.00 | 101.07 | 0.00 | 0.00 |
Annual Sum or Average | 199.95 | 570.75 | 304.45 | 8.79 | 295.66 | 0.00 | 0.00 |
Minimum of Months | 0.13 | 239.51 | 101.07 | 0.00 | 101.07 | 0.00 | 0.00 |
Maximum of Months | 501.71 | 987.72 | 522.84 | 40.06 | 487.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 99.41 | 597.51 | 193.88 | 70.27 | 123.61 | 0.00 | 0.00 |
February | 262.45 | 518.57 | 329.44 | 138.20 | 191.24 | 0.00 | 0.00 |
March | 435.90 | 422.14 | 442.28 | 166.68 | 275.60 | 0.00 | 0.00 |
April | 716.94 | 337.47 | 618.24 | 235.78 | 382.46 | 0.00 | 0.00 |
May | 814.55 | 274.57 | 653.06 | 199.56 | 453.50 | 0.00 | 0.00 |
June | 978.82 | 209.72 | 736.00 | 274.46 | 461.54 | 0.00 | 0.00 |
July | 1008.01 | 176.75 | 704.69 | 280.29 | 424.40 | 0.00 | 0.00 |
August | 1017.56 | 169.20 | 689.64 | 312.71 | 376.94 | 0.00 | 0.00 |
September | 752.88 | 237.84 | 559.42 | 249.84 | 309.58 | 0.00 | 0.00 |
October | 449.24 | 357.01 | 402.46 | 182.46 | 220.00 | 0.00 | 0.00 |
November | 162.90 | 464.78 | 215.14 | 77.51 | 137.62 | 0.00 | 0.00 |
December | 127.61 | 588.97 | 192.11 | 83.05 | 109.06 | 0.00 | 0.00 |
Annual Sum or Average | 570.45 | 362.15 | 478.66 | 189.43 | 289.22 | 0.00 | 0.00 |
Minimum of Months | 99.41 | 169.20 | 192.11 | 70.27 | 109.06 | 0.00 | 0.00 |
Maximum of Months | 1017.56 | 597.51 | 736.00 | 312.71 | 461.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 223.69 | 671.25 | 322.09 | 167.35 | 154.74 | 0.00 | 0.00 |
February | 430.33 | 578.97 | 496.35 | 268.60 | 227.75 | 0.00 | 0.00 |
March | 528.78 | 476.34 | 552.71 | 242.80 | 309.91 | 0.00 | 0.00 |
April | 644.84 | 379.76 | 618.00 | 209.07 | 408.92 | 0.00 | 0.00 |
May | 669.35 | 302.43 | 622.41 | 142.95 | 479.47 | 0.00 | 0.00 |
June | 653.20 | 225.14 | 588.29 | 121.47 | 466.82 | 0.00 | 0.00 |
July | 759.84 | 197.94 | 615.01 | 175.10 | 439.91 | 0.00 | 0.00 |
August | 789.55 | 192.83 | 612.07 | 221.86 | 390.22 | 0.00 | 0.00 |
September | 755.54 | 287.14 | 632.52 | 287.49 | 345.03 | 0.00 | 0.00 |
October | 579.15 | 399.24 | 548.63 | 291.03 | 257.61 | 0.00 | 0.00 |
November | 267.81 | 525.80 | 330.64 | 162.84 | 167.80 | 0.00 | 0.00 |
December | 271.03 | 663.13 | 332.38 | 192.54 | 139.84 | 0.00 | 0.00 |
Annual Sum or Average | 548.37 | 407.52 | 522.59 | 206.55 | 316.05 | 0.00 | 0.00 |
Minimum of Months | 223.69 | 192.83 | 322.09 | 121.47 | 139.84 | 0.00 | 0.00 |
Maximum of Months | 789.55 | 671.25 | 632.52 | 291.03 | 479.47 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.915460E+09 | 0.132105E+10 | 0.102079E+10 | 0.607247E+09 | 0.413543E+09 | 0.00 | 0.00 |
February | 0.145594E+10 | 0.104797E+10 | 0.141883E+10 | 0.880309E+09 | 0.538522E+09 | 0.00 | 0.00 |
March | 0.180903E+10 | 0.963321E+09 | 0.166635E+10 | 0.881003E+09 | 0.785345E+09 | 0.00 | 0.00 |
April | 0.197919E+10 | 0.748717E+09 | 0.170398E+10 | 0.731303E+09 | 0.972674E+09 | 0.00 | 0.00 |
May | 0.195815E+10 | 0.613733E+09 | 0.164051E+10 | 0.500145E+09 | 0.114037E+10 | 0.00 | 0.00 |
June | 0.177590E+10 | 0.436840E+09 | 0.143641E+10 | 0.384441E+09 | 0.105197E+10 | 0.00 | 0.00 |
July | 0.216622E+10 | 0.397984E+09 | 0.161261E+10 | 0.585540E+09 | 0.102707E+10 | 0.00 | 0.00 |
August | 0.235888E+10 | 0.384289E+09 | 0.171918E+10 | 0.789956E+09 | 0.929228E+09 | 0.00 | 0.00 |
September | 0.235386E+10 | 0.558527E+09 | 0.184527E+10 | 0.100924E+10 | 0.836033E+09 | 0.00 | 0.00 |
October | 0.200570E+10 | 0.813750E+09 | 0.172485E+10 | 0.105602E+10 | 0.668837E+09 | 0.00 | 0.00 |
November | 0.977350E+09 | 0.101156E+10 | 0.998973E+09 | 0.571820E+09 | 0.427153E+09 | 0.00 | 0.00 |
December | 0.106898E+10 | 0.132652E+10 | 0.108037E+10 | 0.698661E+09 | 0.381712E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.208247E+11 | 0.962425E+10 | 0.178681E+11 | 0.869568E+10 | 0.917246E+10 | 0.00 | 0.00 |
Minimum of Months | 0.915460E+09 | 0.384289E+09 | 0.998973E+09 | 0.384441E+09 | 0.381712E+09 | 0.00 | 0.00 |
Maximum of Months | 0.235888E+10 | 0.132652E+10 | 0.184527E+10 | 0.105602E+10 | 0.114037E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.254001E+10 | 0.382451E+10 | 0.287448E+10 | 0.170997E+10 | 0.116451E+10 | 0.00 | 0.00 |
February | 0.404919E+10 | 0.305984E+10 | 0.399533E+10 | 0.247889E+10 | 0.151644E+10 | 0.00 | 0.00 |
March | 0.503330E+10 | 0.286255E+10 | 0.469233E+10 | 0.248085E+10 | 0.221148E+10 | 0.00 | 0.00 |
April | 0.550235E+10 | 0.225162E+10 | 0.479829E+10 | 0.205930E+10 | 0.273898E+10 | 0.00 | 0.00 |
May | 0.543602E+10 | 0.187043E+10 | 0.461958E+10 | 0.140838E+10 | 0.321120E+10 | 0.00 | 0.00 |
June | 0.491093E+10 | 0.137133E+10 | 0.404484E+10 | 0.108256E+10 | 0.296227E+10 | 0.00 | 0.00 |
July | 0.601957E+10 | 0.125278E+10 | 0.454101E+10 | 0.164884E+10 | 0.289217E+10 | 0.00 | 0.00 |
August | 0.656696E+10 | 0.122114E+10 | 0.484111E+10 | 0.222446E+10 | 0.261664E+10 | 0.00 | 0.00 |
September | 0.656175E+10 | 0.171958E+10 | 0.519617E+10 | 0.284196E+10 | 0.235421E+10 | 0.00 | 0.00 |
October | 0.558367E+10 | 0.246005E+10 | 0.485707E+10 | 0.297367E+10 | 0.188340E+10 | 0.00 | 0.00 |
November | 0.271014E+10 | 0.297328E+10 | 0.281304E+10 | 0.161021E+10 | 0.120283E+10 | 0.00 | 0.00 |
December | 0.297297E+10 | 0.384963E+10 | 0.304226E+10 | 0.196738E+10 | 0.107488E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.578869E+11 | 0.287168E+11 | 0.503155E+11 | 0.244865E+11 | 0.258290E+11 | 0.00 | 0.00 |
Minimum of Months | 0.254001E+10 | 0.122114E+10 | 0.281304E+10 | 0.108256E+10 | 0.107488E+10 | 0.00 | 0.00 |
Maximum of Months | 0.656696E+10 | 0.384963E+10 | 0.519617E+10 | 0.297367E+10 | 0.321120E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.331878E+10 | 0.532073E+10 | 0.373411E+10 | 0.222134E+10 | 0.151276E+10 | 0.00 | 0.00 |
February | 0.531398E+10 | 0.423733E+10 | 0.519017E+10 | 0.322022E+10 | 0.196994E+10 | 0.00 | 0.00 |
March | 0.661549E+10 | 0.398609E+10 | 0.609560E+10 | 0.322276E+10 | 0.287284E+10 | 0.00 | 0.00 |
April | 0.722956E+10 | 0.314022E+10 | 0.623325E+10 | 0.267515E+10 | 0.355810E+10 | 0.00 | 0.00 |
May | 0.712458E+10 | 0.263897E+10 | 0.600109E+10 | 0.182956E+10 | 0.417153E+10 | 0.00 | 0.00 |
June | 0.641481E+10 | 0.195129E+10 | 0.525447E+10 | 0.140631E+10 | 0.384816E+10 | 0.00 | 0.00 |
July | 0.789503E+10 | 0.177559E+10 | 0.589903E+10 | 0.214194E+10 | 0.375709E+10 | 0.00 | 0.00 |
August | 0.862619E+10 | 0.171582E+10 | 0.628888E+10 | 0.288971E+10 | 0.339917E+10 | 0.00 | 0.00 |
September | 0.862335E+10 | 0.240436E+10 | 0.675012E+10 | 0.369187E+10 | 0.305826E+10 | 0.00 | 0.00 |
October | 0.732961E+10 | 0.344579E+10 | 0.630961E+10 | 0.386297E+10 | 0.244665E+10 | 0.00 | 0.00 |
November | 0.353282E+10 | 0.418135E+10 | 0.365430E+10 | 0.209175E+10 | 0.156255E+10 | 0.00 | 0.00 |
December | 0.389049E+10 | 0.536003E+10 | 0.395207E+10 | 0.255574E+10 | 0.139632E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.759147E+11 | 0.401576E+11 | 0.653627E+11 | 0.318093E+11 | 0.335534E+11 | 0.00 | 0.00 |
Minimum of Months | 0.331878E+10 | 0.171582E+10 | 0.365430E+10 | 0.140631E+10 | 0.139632E+10 | 0.00 | 0.00 |
Maximum of Months | 0.862619E+10 | 0.536003E+10 | 0.675012E+10 | 0.386297E+10 | 0.417153E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.222571E+09 | 0.778059E+09 | 0.346724E+09 | 0.163167E+09 | 0.183558E+09 | 0.00 | 0.00 |
February | 0.434122E+09 | 0.611389E+09 | 0.513985E+09 | 0.261695E+09 | 0.252290E+09 | 0.00 | 0.00 |
March | 0.660891E+09 | 0.555411E+09 | 0.691549E+09 | 0.296606E+09 | 0.394943E+09 | 0.00 | 0.00 |
April | 0.937032E+09 | 0.425245E+09 | 0.869359E+09 | 0.347902E+09 | 0.521457E+09 | 0.00 | 0.00 |
May | 0.118899E+10 | 0.348723E+09 | 0.103370E+10 | 0.387673E+09 | 0.646029E+09 | 0.00 | 0.00 |
June | 0.111924E+10 | 0.245258E+09 | 0.942761E+09 | 0.331299E+09 | 0.611462E+09 | 0.00 | 0.00 |
July | 0.150296E+10 | 0.217533E+09 | 0.116035E+10 | 0.557965E+09 | 0.602380E+09 | 0.00 | 0.00 |
August | 0.137242E+10 | 0.204693E+09 | 0.103634E+10 | 0.511407E+09 | 0.524936E+09 | 0.00 | 0.00 |
September | 0.112488E+10 | 0.311242E+09 | 0.915471E+09 | 0.464417E+09 | 0.451054E+09 | 0.00 | 0.00 |
October | 0.701005E+09 | 0.465433E+09 | 0.666417E+09 | 0.342553E+09 | 0.323863E+09 | 0.00 | 0.00 |
November | 0.274096E+09 | 0.588954E+09 | 0.353457E+09 | 0.157390E+09 | 0.196067E+09 | 0.00 | 0.00 |
December | 0.267247E+09 | 0.773518E+09 | 0.349625E+09 | 0.185355E+09 | 0.164270E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.980546E+10 | 0.552546E+10 | 0.887974E+10 | 0.400743E+10 | 0.487231E+10 | 0.00 | 0.00 |
Minimum of Months | 0.222571E+09 | 0.204693E+09 | 0.346724E+09 | 0.157390E+09 | 0.164270E+09 | 0.00 | 0.00 |
Maximum of Months | 0.150296E+10 | 0.778059E+09 | 0.116035E+10 | 0.557965E+09 | 0.646029E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 58700648.78 | 0.816633E+09 | 0.190407E+09 | 43103720.32 | 0.147303E+09 | 0.00 | 0.00 |
February | 0.175061E+09 | 0.635511E+09 | 0.297420E+09 | 87642964.17 | 0.209777E+09 | 0.00 | 0.00 |
March | 0.362952E+09 | 0.559394E+09 | 0.466427E+09 | 0.122417E+09 | 0.344011E+09 | 0.00 | 0.00 |
April | 0.656786E+09 | 0.421991E+09 | 0.675843E+09 | 0.204193E+09 | 0.471650E+09 | 0.00 | 0.00 |
May | 0.965220E+09 | 0.347965E+09 | 0.899439E+09 | 0.294493E+09 | 0.604946E+09 | 0.00 | 0.00 |
June | 0.949712E+09 | 0.246183E+09 | 0.852363E+09 | 0.268241E+09 | 0.584122E+09 | 0.00 | 0.00 |
July | 0.126662E+10 | 0.226155E+09 | 0.103192E+10 | 0.457523E+09 | 0.574398E+09 | 0.00 | 0.00 |
August | 0.107364E+10 | 0.210996E+09 | 0.850783E+09 | 0.359854E+09 | 0.490929E+09 | 0.00 | 0.00 |
September | 0.753892E+09 | 0.321699E+09 | 0.666243E+09 | 0.264960E+09 | 0.401283E+09 | 0.00 | 0.00 |
October | 0.357001E+09 | 0.470321E+09 | 0.407182E+09 | 0.133761E+09 | 0.273421E+09 | 0.00 | 0.00 |
November | 98447350.89 | 0.605945E+09 | 0.205806E+09 | 44331374.38 | 0.161474E+09 | 0.00 | 0.00 |
December | 71851722.47 | 0.804696E+09 | 0.174689E+09 | 47217705.85 | 0.127471E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.678988E+10 | 0.566749E+10 | 0.671852E+10 | 0.232774E+10 | 0.439079E+10 | 0.00 | 0.00 |
Minimum of Months | 58700648.78 | 0.210996E+09 | 0.174689E+09 | 43103720.32 | 0.127471E+09 | 0.00 | 0.00 |
Maximum of Months | 0.126662E+10 | 0.816633E+09 | 0.103192E+10 | 0.457523E+09 | 0.604946E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.140435E+09 | 0.226834E+09 | 0.161430E+09 | 96031370.32 | 65398878.59 | 0.00 | 0.00 |
February | 0.215113E+09 | 0.208411E+09 | 0.224378E+09 | 0.139214E+09 | 85163535.41 | 0.00 | 0.00 |
March | 0.260612E+09 | 0.221219E+09 | 0.263521E+09 | 0.139324E+09 | 0.124197E+09 | 0.00 | 0.00 |
April | 0.280630E+09 | 0.178822E+09 | 0.269472E+09 | 0.115650E+09 | 0.153822E+09 | 0.00 | 0.00 |
May | 0.273678E+09 | 0.152550E+09 | 0.259436E+09 | 79094093.75 | 0.180342E+09 | 0.00 | 0.00 |
June | 0.242242E+09 | 0.116424E+09 | 0.227159E+09 | 60796426.56 | 0.166362E+09 | 0.00 | 0.00 |
July | 0.307237E+09 | 0.107641E+09 | 0.255024E+09 | 92598617.16 | 0.162425E+09 | 0.00 | 0.00 |
August | 0.340313E+09 | 0.104803E+09 | 0.271877E+09 | 0.124925E+09 | 0.146952E+09 | 0.00 | 0.00 |
September | 0.346032E+09 | 0.139874E+09 | 0.291817E+09 | 0.159604E+09 | 0.132213E+09 | 0.00 | 0.00 |
October | 0.290875E+09 | 0.196811E+09 | 0.272773E+09 | 0.167001E+09 | 0.105772E+09 | 0.00 | 0.00 |
November | 0.138135E+09 | 0.220833E+09 | 0.157980E+09 | 90428875.66 | 67551271.18 | 0.00 | 0.00 |
December | 0.161041E+09 | 0.244134E+09 | 0.170853E+09 | 0.110488E+09 | 60365023.40 | 0.00 | 0.00 |
Annual Sum or Average | 0.299634E+10 | 0.211836E+10 | 0.282572E+10 | 0.137516E+10 | 0.145056E+10 | 0.00 | 0.00 |
Minimum of Months | 0.138135E+09 | 0.104803E+09 | 0.157980E+09 | 60796426.56 | 60365023.40 | 0.00 | 0.00 |
Maximum of Months | 0.346032E+09 | 0.244134E+09 | 0.291817E+09 | 0.167001E+09 | 0.180342E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 842581.78 | 0.251435E+09 | 36413225.08 | 0.00 | 36413225.08 | 0.00 | 0.00 |
February | 9322485.39 | 0.193871E+09 | 51176770.43 | 0.00 | 51176770.43 | 0.00 | 0.00 |
March | 37288028.32 | 0.166114E+09 | 83487367.90 | 272.21 | 83487095.69 | 0.00 | 0.00 |
April | 81833603.55 | 0.120377E+09 | 0.114728E+09 | 705856.95 | 0.114022E+09 | 0.00 | 0.00 |
May | 0.136653E+09 | 94531743.51 | 0.152098E+09 | 4566859.58 | 0.147531E+09 | 0.00 | 0.00 |
June | 0.155766E+09 | 65574223.31 | 0.154906E+09 | 10363092.34 | 0.144543E+09 | 0.00 | 0.00 |
July | 0.174205E+09 | 57355181.66 | 0.152356E+09 | 12265043.58 | 0.140091E+09 | 0.00 | 0.00 |
August | 0.146850E+09 | 53746967.46 | 0.123500E+09 | 3709014.18 | 0.119791E+09 | 0.00 | 0.00 |
September | 82859686.73 | 87676059.20 | 92504439.09 | 69295.25 | 92435143.84 | 0.00 | 0.00 |
October | 33846883.98 | 0.138176E+09 | 65447658.79 | 0.00 | 65447658.79 | 0.00 | 0.00 |
November | 5874765.62 | 0.184698E+09 | 39895669.45 | 0.00 | 39895669.45 | 0.00 | 0.00 |
December | 387576.70 | 0.245003E+09 | 30941853.50 | 0.00 | 30941853.50 | 0.00 | 0.00 |
Annual Sum or Average | 0.865729E+09 | 0.165856E+10 | 0.109745E+10 | 31679434.09 | 0.106578E+10 | 0.00 | 0.00 |
Minimum of Months | 387576.70 | 53746967.46 | 30941853.50 | 0.00 | 30941853.50 | 0.00 | 0.00 |
Maximum of Months | 0.174205E+09 | 0.251435E+09 | 0.154906E+09 | 12265043.58 | 0.147531E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.208500E+09 | 0.774329E+09 | 0.337811E+09 | 0.154141E+09 | 0.183670E+09 | 0.00 | 0.00 |
February | 0.419539E+09 | 0.606432E+09 | 0.506786E+09 | 0.254193E+09 | 0.252592E+09 | 0.00 | 0.00 |
March | 0.666034E+09 | 0.544379E+09 | 0.704892E+09 | 0.310326E+09 | 0.394567E+09 | 0.00 | 0.00 |
April | 0.958047E+09 | 0.410741E+09 | 0.898041E+09 | 0.377444E+09 | 0.520597E+09 | 0.00 | 0.00 |
May | 0.105631E+10 | 0.338754E+09 | 0.941749E+09 | 0.313851E+09 | 0.627898E+09 | 0.00 | 0.00 |
June | 0.118860E+10 | 0.236009E+09 | 0.999105E+09 | 0.387252E+09 | 0.611853E+09 | 0.00 | 0.00 |
July | 0.128303E+10 | 0.201649E+09 | 0.100798E+10 | 0.425606E+09 | 0.582376E+09 | 0.00 | 0.00 |
August | 0.133217E+10 | 0.191239E+09 | 0.101640E+10 | 0.494580E+09 | 0.521820E+09 | 0.00 | 0.00 |
September | 0.102092E+10 | 0.299085E+09 | 0.849659E+09 | 0.423537E+09 | 0.426122E+09 | 0.00 | 0.00 |
October | 0.698478E+09 | 0.458742E+09 | 0.668615E+09 | 0.348763E+09 | 0.319852E+09 | 0.00 | 0.00 |
November | 0.269703E+09 | 0.584610E+09 | 0.352653E+09 | 0.156990E+09 | 0.195662E+09 | 0.00 | 0.00 |
December | 0.255671E+09 | 0.766339E+09 | 0.344747E+09 | 0.180287E+09 | 0.164460E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.935701E+10 | 0.541231E+10 | 0.862844E+10 | 0.382697E+10 | 0.480147E+10 | 0.00 | 0.00 |
Minimum of Months | 0.208500E+09 | 0.191239E+09 | 0.337811E+09 | 0.154141E+09 | 0.164460E+09 | 0.00 | 0.00 |
Maximum of Months | 0.133217E+10 | 0.774329E+09 | 0.101640E+10 | 0.494580E+09 | 0.627898E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 39311435.69 | 0.807653E+09 | 0.181494E+09 | 34077660.85 | 0.147416E+09 | 0.00 | 0.00 |
February | 0.151238E+09 | 0.620252E+09 | 0.290220E+09 | 80141237.88 | 0.210079E+09 | 0.00 | 0.00 |
March | 0.361154E+09 | 0.540922E+09 | 0.479771E+09 | 0.136136E+09 | 0.343635E+09 | 0.00 | 0.00 |
April | 0.676560E+09 | 0.405907E+09 | 0.704526E+09 | 0.233735E+09 | 0.470791E+09 | 0.00 | 0.00 |
May | 0.842195E+09 | 0.336638E+09 | 0.807486E+09 | 0.220672E+09 | 0.586815E+09 | 0.00 | 0.00 |
June | 0.102892E+10 | 0.239359E+09 | 0.908707E+09 | 0.324193E+09 | 0.584513E+09 | 0.00 | 0.00 |
July | 0.105930E+10 | 0.207463E+09 | 0.879557E+09 | 0.325164E+09 | 0.554394E+09 | 0.00 | 0.00 |
August | 0.103637E+10 | 0.199266E+09 | 0.830840E+09 | 0.343027E+09 | 0.487813E+09 | 0.00 | 0.00 |
September | 0.653970E+09 | 0.302877E+09 | 0.600430E+09 | 0.224079E+09 | 0.376351E+09 | 0.00 | 0.00 |
October | 0.348941E+09 | 0.456608E+09 | 0.409380E+09 | 0.139970E+09 | 0.269410E+09 | 0.00 | 0.00 |
November | 89376710.08 | 0.596188E+09 | 0.205001E+09 | 43931896.31 | 0.161070E+09 | 0.00 | 0.00 |
December | 52373888.82 | 0.789284E+09 | 0.169811E+09 | 42150042.10 | 0.127661E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.633971E+10 | 0.550242E+10 | 0.646722E+10 | 0.214728E+10 | 0.431995E+10 | 0.00 | 0.00 |
Minimum of Months | 39311435.69 | 0.199266E+09 | 0.169811E+09 | 34077660.85 | 0.127661E+09 | 0.00 | 0.00 |
Maximum of Months | 0.105930E+10 | 0.807653E+09 | 0.908707E+09 | 0.343027E+09 | 0.586815E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.272297E+09 | 0.998718E+09 | 0.428658E+09 | 0.208073E+09 | 0.220584E+09 | 0.00 | 0.00 |
February | 0.493022E+09 | 0.777525E+09 | 0.597030E+09 | 0.301638E+09 | 0.295392E+09 | 0.00 | 0.00 |
March | 0.701276E+09 | 0.704787E+09 | 0.751838E+09 | 0.301877E+09 | 0.449962E+09 | 0.00 | 0.00 |
April | 0.861952E+09 | 0.539746E+09 | 0.832411E+09 | 0.252110E+09 | 0.580300E+09 | 0.00 | 0.00 |
May | 0.960669E+09 | 0.446431E+09 | 0.891621E+09 | 0.181268E+09 | 0.710352E+09 | 0.00 | 0.00 |
June | 0.931790E+09 | 0.317015E+09 | 0.827769E+09 | 0.154179E+09 | 0.673590E+09 | 0.00 | 0.00 |
July | 0.110362E+10 | 0.288199E+09 | 0.882620E+09 | 0.227206E+09 | 0.655414E+09 | 0.00 | 0.00 |
August | 0.111241E+10 | 0.282319E+09 | 0.856624E+09 | 0.278714E+09 | 0.577911E+09 | 0.00 | 0.00 |
September | 0.987001E+09 | 0.416728E+09 | 0.832682E+09 | 0.345967E+09 | 0.486715E+09 | 0.00 | 0.00 |
October | 0.757872E+09 | 0.594756E+09 | 0.732804E+09 | 0.361844E+09 | 0.370960E+09 | 0.00 | 0.00 |
November | 0.329587E+09 | 0.751895E+09 | 0.428726E+09 | 0.195934E+09 | 0.232792E+09 | 0.00 | 0.00 |
December | 0.332214E+09 | 0.987107E+09 | 0.437221E+09 | 0.239396E+09 | 0.197825E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.884371E+10 | 0.710523E+10 | 0.850000E+10 | 0.304821E+10 | 0.545180E+10 | 0.00 | 0.00 |
Minimum of Months | 0.272297E+09 | 0.282319E+09 | 0.428658E+09 | 0.154179E+09 | 0.197825E+09 | 0.00 | 0.00 |
Maximum of Months | 0.111241E+10 | 0.998718E+09 | 0.891621E+09 | 0.361844E+09 | 0.710352E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.224442E+09 | 0.771104E+09 | 0.346724E+09 | 0.163167E+09 | 0.183558E+09 | 0.00 | 0.00 |
February | 0.433903E+09 | 0.606553E+09 | 0.513985E+09 | 0.261695E+09 | 0.252290E+09 | 0.00 | 0.00 |
March | 0.657471E+09 | 0.551390E+09 | 0.691549E+09 | 0.296606E+09 | 0.394943E+09 | 0.00 | 0.00 |
April | 0.928307E+09 | 0.423928E+09 | 0.869359E+09 | 0.347902E+09 | 0.521457E+09 | 0.00 | 0.00 |
May | 0.117707E+10 | 0.347021E+09 | 0.103370E+10 | 0.387673E+09 | 0.646029E+09 | 0.00 | 0.00 |
June | 0.110743E+10 | 0.243541E+09 | 0.942761E+09 | 0.331299E+09 | 0.611462E+09 | 0.00 | 0.00 |
July | 0.148956E+10 | 0.215811E+09 | 0.116035E+10 | 0.557965E+09 | 0.602380E+09 | 0.00 | 0.00 |
August | 0.136258E+10 | 0.201660E+09 | 0.103634E+10 | 0.511407E+09 | 0.524936E+09 | 0.00 | 0.00 |
September | 0.111859E+10 | 0.307359E+09 | 0.915471E+09 | 0.464417E+09 | 0.451054E+09 | 0.00 | 0.00 |
October | 0.697873E+09 | 0.460050E+09 | 0.666417E+09 | 0.342553E+09 | 0.323863E+09 | 0.00 | 0.00 |
November | 0.274910E+09 | 0.582256E+09 | 0.353457E+09 | 0.157390E+09 | 0.196067E+09 | 0.00 | 0.00 |
December | 0.268584E+09 | 0.764895E+09 | 0.349625E+09 | 0.185355E+09 | 0.164270E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.974071E+10 | 0.547557E+10 | 0.887974E+10 | 0.400743E+10 | 0.487231E+10 | 0.00 | 0.00 |
Minimum of Months | 0.224442E+09 | 0.201660E+09 | 0.346724E+09 | 0.157390E+09 | 0.164270E+09 | 0.00 | 0.00 |
Maximum of Months | 0.148956E+10 | 0.771104E+09 | 0.116035E+10 | 0.557965E+09 | 0.646029E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 60302649.15 | 0.808434E+09 | 0.190407E+09 | 43103720.32 | 0.147303E+09 | 0.00 | 0.00 |
February | 0.176427E+09 | 0.629549E+09 | 0.297420E+09 | 87642964.17 | 0.209777E+09 | 0.00 | 0.00 |
March | 0.362119E+09 | 0.554209E+09 | 0.466427E+09 | 0.122417E+09 | 0.344011E+09 | 0.00 | 0.00 |
April | 0.650306E+09 | 0.420674E+09 | 0.675843E+09 | 0.204193E+09 | 0.471650E+09 | 0.00 | 0.00 |
May | 0.952312E+09 | 0.349358E+09 | 0.899439E+09 | 0.294493E+09 | 0.604946E+09 | 0.00 | 0.00 |
June | 0.935888E+09 | 0.248236E+09 | 0.852363E+09 | 0.268241E+09 | 0.584122E+09 | 0.00 | 0.00 |
July | 0.125042E+10 | 0.230165E+09 | 0.103192E+10 | 0.457523E+09 | 0.574398E+09 | 0.00 | 0.00 |
August | 0.106448E+10 | 0.210756E+09 | 0.850783E+09 | 0.359854E+09 | 0.490929E+09 | 0.00 | 0.00 |
September | 0.747324E+09 | 0.321230E+09 | 0.666243E+09 | 0.264960E+09 | 0.401283E+09 | 0.00 | 0.00 |
October | 0.356918E+09 | 0.463551E+09 | 0.407182E+09 | 0.133761E+09 | 0.273421E+09 | 0.00 | 0.00 |
November | 0.100057E+09 | 0.597740E+09 | 0.205806E+09 | 44331374.38 | 0.161474E+09 | 0.00 | 0.00 |
December | 73554540.72 | 0.794112E+09 | 0.174689E+09 | 47217705.85 | 0.127471E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.673011E+10 | 0.562801E+10 | 0.671852E+10 | 0.232774E+10 | 0.439079E+10 | 0.00 | 0.00 |
Minimum of Months | 60302649.15 | 0.210756E+09 | 0.174689E+09 | 43103720.32 | 0.127471E+09 | 0.00 | 0.00 |
Maximum of Months | 0.125042E+10 | 0.808434E+09 | 0.103192E+10 | 0.457523E+09 | 0.604946E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.257829E+09 | 0.402286E+09 | 0.296000E+09 | 0.176084E+09 | 0.119916E+09 | 0.00 | 0.00 |
February | 0.411868E+09 | 0.319138E+09 | 0.411421E+09 | 0.255264E+09 | 0.156157E+09 | 0.00 | 0.00 |
March | 0.512884E+09 | 0.293114E+09 | 0.483195E+09 | 0.255466E+09 | 0.227729E+09 | 0.00 | 0.00 |
April | 0.559273E+09 | 0.226695E+09 | 0.494106E+09 | 0.212057E+09 | 0.282050E+09 | 0.00 | 0.00 |
May | 0.553816E+09 | 0.182415E+09 | 0.475705E+09 | 0.145028E+09 | 0.330677E+09 | 0.00 | 0.00 |
June | 0.501989E+09 | 0.126816E+09 | 0.416521E+09 | 0.111477E+09 | 0.305044E+09 | 0.00 | 0.00 |
July | 0.621798E+09 | 0.109646E+09 | 0.467614E+09 | 0.169790E+09 | 0.297825E+09 | 0.00 | 0.00 |
August | 0.681337E+09 | 0.102379E+09 | 0.498517E+09 | 0.229065E+09 | 0.269452E+09 | 0.00 | 0.00 |
September | 0.679743E+09 | 0.159172E+09 | 0.535078E+09 | 0.292651E+09 | 0.242427E+09 | 0.00 | 0.00 |
October | 0.571299E+09 | 0.243292E+09 | 0.500159E+09 | 0.306214E+09 | 0.193945E+09 | 0.00 | 0.00 |
November | 0.276992E+09 | 0.306779E+09 | 0.289674E+09 | 0.165811E+09 | 0.123863E+09 | 0.00 | 0.00 |
December | 0.303794E+09 | 0.400053E+09 | 0.313277E+09 | 0.202591E+09 | 0.110686E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.593262E+10 | 0.287178E+10 | 0.518127E+10 | 0.252150E+10 | 0.265977E+10 | 0.00 | 0.00 |
Minimum of Months | 0.257829E+09 | 0.102379E+09 | 0.289674E+09 | 0.111477E+09 | 0.110686E+09 | 0.00 | 0.00 |
Maximum of Months | 0.681337E+09 | 0.402286E+09 | 0.535078E+09 | 0.306214E+09 | 0.330677E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 2233121.73 | 0.255992E+10 | 0.318561E+09 | 0.00 | 0.318561E+09 | 0.00 | 0.00 |
February | 51507234.31 | 0.199839E+10 | 0.447720E+09 | 0.00 | 0.447720E+09 | 0.00 | 0.00 |
March | 0.246619E+09 | 0.173476E+10 | 0.730390E+09 | 2381.43 | 0.730388E+09 | 0.00 | 0.00 |
April | 0.598602E+09 | 0.127658E+10 | 0.100370E+10 | 6175195.84 | 0.997525E+09 | 0.00 | 0.00 |
May | 0.104645E+10 | 0.100816E+10 | 0.133063E+10 | 39953211.88 | 0.129068E+10 | 0.00 | 0.00 |
June | 0.120499E+10 | 0.714453E+09 | 0.135520E+10 | 90661606.03 | 0.126454E+10 | 0.00 | 0.00 |
July | 0.137112E+10 | 0.637601E+09 | 0.133289E+10 | 0.107301E+09 | 0.122559E+10 | 0.00 | 0.00 |
August | 0.113848E+10 | 0.621536E+09 | 0.108044E+10 | 32448343.77 | 0.104799E+10 | 0.00 | 0.00 |
September | 0.620149E+09 | 0.950862E+09 | 0.809276E+09 | 606230.16 | 0.808670E+09 | 0.00 | 0.00 |
October | 0.219010E+09 | 0.148554E+10 | 0.572569E+09 | 0.00 | 0.572569E+09 | 0.00 | 0.00 |
November | 28779805.81 | 0.193675E+10 | 0.349028E+09 | 0.00 | 0.349028E+09 | 0.00 | 0.00 |
December | 655137.40 | 0.250223E+10 | 0.270695E+09 | 0.00 | 0.270695E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.652859E+10 | 0.174268E+11 | 0.960109E+10 | 0.277148E+09 | 0.932395E+10 | 0.00 | 0.00 |
Minimum of Months | 655137.40 | 0.621536E+09 | 0.270695E+09 | 0.00 | 0.270695E+09 | 0.00 | 0.00 |
Maximum of Months | 0.137112E+10 | 0.255992E+10 | 0.135520E+10 | 0.107301E+09 | 0.129068E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1329375.59 | 0.264550E+10 | 0.318561E+09 | 0.00 | 0.318561E+09 | 0.00 | 0.00 |
February | 44880015.42 | 0.206719E+10 | 0.447720E+09 | 0.00 | 0.447720E+09 | 0.00 | 0.00 |
March | 0.224414E+09 | 0.179038E+10 | 0.730390E+09 | 2381.43 | 0.730388E+09 | 0.00 | 0.00 |
April | 0.569130E+09 | 0.131412E+10 | 0.100370E+10 | 6175195.84 | 0.997525E+09 | 0.00 | 0.00 |
May | 0.101500E+10 | 0.103414E+10 | 0.133063E+10 | 39953211.88 | 0.129068E+10 | 0.00 | 0.00 |
June | 0.117439E+10 | 0.733826E+09 | 0.135520E+10 | 90661606.03 | 0.126454E+10 | 0.00 | 0.00 |
July | 0.134378E+10 | 0.655865E+09 | 0.133289E+10 | 0.107301E+09 | 0.122559E+10 | 0.00 | 0.00 |
August | 0.111220E+10 | 0.641492E+09 | 0.108044E+10 | 32448343.77 | 0.104799E+10 | 0.00 | 0.00 |
September | 0.596926E+09 | 0.980048E+09 | 0.809276E+09 | 606230.16 | 0.808670E+09 | 0.00 | 0.00 |
October | 0.199446E+09 | 0.153870E+10 | 0.572569E+09 | 0.00 | 0.572569E+09 | 0.00 | 0.00 |
November | 23771224.84 | 0.201082E+10 | 0.349028E+09 | 0.00 | 0.349028E+09 | 0.00 | 0.00 |
December | 357563.91 | 0.258702E+10 | 0.270695E+09 | 0.00 | 0.270695E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.630563E+10 | 0.179991E+11 | 0.960109E+10 | 0.277148E+09 | 0.932395E+10 | 0.00 | 0.00 |
Minimum of Months | 357563.91 | 0.641492E+09 | 0.270695E+09 | 0.00 | 0.270695E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134378E+10 | 0.264550E+10 | 0.135520E+10 | 0.107301E+09 | 0.129068E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.266248E+09 | 0.160036E+10 | 0.519285E+09 | 0.188214E+09 | 0.331072E+09 | 0.00 | 0.00 |
February | 0.634910E+09 | 0.125453E+10 | 0.796974E+09 | 0.334323E+09 | 0.462651E+09 | 0.00 | 0.00 |
March | 0.116750E+10 | 0.113066E+10 | 0.118461E+10 | 0.446443E+09 | 0.738167E+09 | 0.00 | 0.00 |
April | 0.185830E+10 | 0.874732E+09 | 0.160249E+10 | 0.611146E+09 | 0.991341E+09 | 0.00 | 0.00 |
May | 0.218170E+10 | 0.735412E+09 | 0.174915E+10 | 0.534492E+09 | 0.121466E+10 | 0.00 | 0.00 |
June | 0.253711E+10 | 0.543599E+09 | 0.190771E+10 | 0.711401E+09 | 0.119631E+10 | 0.00 | 0.00 |
July | 0.269987E+10 | 0.473409E+09 | 0.188744E+10 | 0.750725E+09 | 0.113672E+10 | 0.00 | 0.00 |
August | 0.272545E+10 | 0.453179E+09 | 0.184714E+10 | 0.837559E+09 | 0.100959E+10 | 0.00 | 0.00 |
September | 0.195146E+10 | 0.616488E+09 | 0.145002E+10 | 0.647584E+09 | 0.802436E+09 | 0.00 | 0.00 |
October | 0.120325E+10 | 0.956204E+09 | 0.107795E+10 | 0.488713E+09 | 0.589235E+09 | 0.00 | 0.00 |
November | 0.422239E+09 | 0.120470E+10 | 0.557632E+09 | 0.200916E+09 | 0.356716E+09 | 0.00 | 0.00 |
December | 0.341793E+09 | 0.157748E+10 | 0.514539E+09 | 0.222431E+09 | 0.292108E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.179898E+11 | 0.114208E+11 | 0.150949E+11 | 0.597395E+10 | 0.912099E+10 | 0.00 | 0.00 |
Minimum of Months | 0.266248E+09 | 0.453179E+09 | 0.514539E+09 | 0.188214E+09 | 0.292108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.272545E+10 | 0.160036E+10 | 0.190771E+10 | 0.837559E+09 | 0.121466E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.599131E+09 | 0.179789E+10 | 0.862687E+09 | 0.448231E+09 | 0.414456E+09 | 0.00 | 0.00 |
February | 0.104106E+10 | 0.140064E+10 | 0.120077E+10 | 0.649789E+09 | 0.550985E+09 | 0.00 | 0.00 |
March | 0.141629E+10 | 0.127583E+10 | 0.148038E+10 | 0.650302E+09 | 0.830075E+09 | 0.00 | 0.00 |
April | 0.167143E+10 | 0.984344E+09 | 0.160184E+10 | 0.541919E+09 | 0.105993E+10 | 0.00 | 0.00 |
May | 0.179278E+10 | 0.810021E+09 | 0.166707E+10 | 0.382872E+09 | 0.128420E+10 | 0.00 | 0.00 |
June | 0.169310E+10 | 0.583550E+09 | 0.152484E+10 | 0.314849E+09 | 0.120999E+10 | 0.00 | 0.00 |
July | 0.203516E+10 | 0.530152E+09 | 0.164725E+10 | 0.468992E+09 | 0.117826E+10 | 0.00 | 0.00 |
August | 0.211472E+10 | 0.516479E+09 | 0.163938E+10 | 0.594219E+09 | 0.104516E+10 | 0.00 | 0.00 |
September | 0.195836E+10 | 0.744261E+09 | 0.163949E+10 | 0.745167E+09 | 0.894325E+09 | 0.00 | 0.00 |
October | 0.155120E+10 | 0.106934E+10 | 0.146946E+10 | 0.779484E+09 | 0.689974E+09 | 0.00 | 0.00 |
November | 0.694154E+09 | 0.136286E+10 | 0.857028E+09 | 0.422081E+09 | 0.434946E+09 | 0.00 | 0.00 |
December | 0.725915E+09 | 0.177612E+10 | 0.890259E+09 | 0.515707E+09 | 0.374552E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.172933E+11 | 0.128515E+11 | 0.164805E+11 | 0.651361E+10 | 0.996685E+10 | 0.00 | 0.00 |
Minimum of Months | 0.599131E+09 | 0.516479E+09 | 0.857028E+09 | 0.314849E+09 | 0.374552E+09 | 0.00 | 0.00 |
Maximum of Months | 0.211472E+10 | 0.179789E+10 | 0.166707E+10 | 0.779484E+09 | 0.128420E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770514E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162347976.7 | 81.21 | 0.00 | 0.00 |
February | 0.696255E+10 | -0.681597E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146587187.6 | 81.21 | 0.00 | 0.00 |
March | 0.770364E+10 | -0.754147E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162163882.5 | 81.21 | 0.00 | 0.00 |
April | 0.746544E+10 | -0.730860E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156837990.7 | 81.21 | 0.00 | 0.00 |
May | 0.770478E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161972424.2 | 81.21 | 0.00 | 0.00 |
June | 0.745718E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156646089.4 | 81.21 | 0.00 | 0.00 |
July | 0.771267E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161817215.2 | 81.21 | 0.00 | 0.00 |
August | 0.770458E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161779229.8 | 81.21 | 0.00 | 0.00 |
September | 0.746661E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156666528.7 | 81.21 | 0.00 | 0.00 |
October | 0.770352E+10 | -0.754145E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162065879.8 | 81.21 | 0.00 | 0.00 |
November | 0.744941E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156976190.2 | 81.21 | 0.00 | 0.00 |
December | 0.771317E+10 | -0.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162323116.2 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907487E+11 | -0.888405E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190818E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696255E+10 | -0.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162347976.7 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771317E+10 | -0.681597E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146587187.6 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYSLAUNDRY HPWH TANK
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.600324E+11 | -0.116777E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -854707817.3 | 81.67 | 0.00 | 0.00 |
February | 0.529784E+11 | -0.105983E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -763019401.6 | 81.67 | 0.00 | 0.00 |
March | 0.547255E+11 | -0.116422E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -824863976.4 | 81.67 | 0.00 | 0.00 |
April | 0.473589E+11 | -0.110526E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -779018605.4 | 81.67 | 0.00 | 0.00 |
May | 0.433069E+11 | -0.111285E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -788805580.8 | 81.67 | 0.00 | 0.00 |
June | 0.366550E+11 | -0.104940E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -744129335.0 | 81.67 | 0.00 | 0.00 |
July | 0.332990E+11 | -0.106439E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -752796923.9 | 81.67 | 0.00 | 0.00 |
August | 0.311362E+11 | -0.105824E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -744151971.0 | 81.68 | 0.00 | 0.00 |
September | 0.345136E+11 | -0.103329E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -747801699.9 | 81.67 | 0.00 | 0.00 |
October | 0.429221E+11 | -0.109023E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -801317898.7 | 81.68 | 0.00 | 0.00 |
November | 0.481552E+11 | -0.108344E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -800688824.9 | 81.67 | 0.00 | 0.00 |
December | 0.566353E+11 | -0.114785E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -847254451.9 | 81.67 | 0.00 | 0.00 |
Annual Sum or Average | 0.541718E+12 | -0.131368E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.944856E+10 | 81.67 | 0.00 | 0.00 |
Minimum of Months | 0.311362E+11 | -0.116777E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -854707817.3 | 81.67 | 0.00 | 0.00 |
Maximum of Months | 0.600324E+11 | -0.103329E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -744129335.0 | 81.68 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 HPWH TANK
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | -0.179824E+10 | -0.707749E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.138036E+10 | 59.23 | 0.00 | 0.00 |
February | -0.180636E+10 | -0.643869E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.122539E+10 | 59.24 | 0.00 | 0.00 |
March | -0.227602E+10 | -0.705655E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.130933E+10 | 59.26 | 0.00 | 0.00 |
April | -0.237736E+10 | -0.664202E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.122149E+10 | 59.28 | 0.00 | 0.00 |
May | -0.263419E+10 | -0.661296E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.122376E+10 | 59.30 | 0.00 | 0.00 |
June | -0.254649E+10 | -0.616493E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.113875E+10 | 59.32 | 0.00 | 0.00 |
July | -0.255494E+10 | -0.619224E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.113855E+10 | 59.34 | 0.00 | 0.00 |
August | -0.254756E+10 | -0.614571E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.111817E+10 | 59.36 | 0.00 | 0.00 |
September | -0.243172E+10 | -0.602307E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.114825E+10 | 59.34 | 0.00 | 0.00 |
October | -0.245293E+10 | -0.641386E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.125463E+10 | 59.32 | 0.00 | 0.00 |
November | -0.208089E+10 | -0.645093E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.127451E+10 | 59.31 | 0.00 | 0.00 |
December | -0.197266E+10 | -0.690736E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.136373E+10 | 59.28 | 0.00 | 0.00 |
Annual Sum or Average | -0.274794E+11 | -0.781258E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.147969E+11 | 59.30 | 0.00 | 0.00 |
Minimum of Months | -0.263419E+10 | -0.707749E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.138036E+10 | 59.23 | 0.00 | 0.00 |
Maximum of Months | -0.179824E+10 | -0.602307E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.111817E+10 | 59.36 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.87 | 0.86 | 01-JAN-10:09 | 2103.55 | 32.25 | 221.83 | 218.83 | 1594.23 | 33.22 | 225.83 | 170.33 |
February | 259.50 | 0.87 | 0.86 | 01-FEB-08:39 | 3702.56 | 32.91 | 239.50 | 243.33 | 1596.05 | 28.89 | 202.50 | 205.17 |
March | 247.00 | 0.87 | 0.86 | 01-MAR-07:30 | 5447.48 | 30.22 | 173.00 | 312.17 | 685.22 | 21.96 | 158.00 | 242.50 |
April | 379.50 | 0.87 | 0.86 | 01-APR-07:10 | 1422.23 | 19.40 | 44.83 | 345.00 | 550.51 | 21.14 | 224.33 | 279.67 |
May | 427.83 | 0.87 | 0.86 | 01-MAY-07:30 | 1311.24 | 19.22 | 66.33 | 384.83 | 502.06 | 20.93 | 239.33 | 302.33 |
June | 375.17 | 0.87 | 0.86 | 01-JUN-06:40 | 1111.15 | 19.21 | 21.83 | 393.00 | 445.48 | 20.97 | 235.00 | 305.83 |
July | 471.00 | 0.88 | 0.86 | 01-JUL-06:30 | 957.62 | 18.17 | 27.33 | 390.00 | 383.70 | 19.94 | 193.33 | 272.50 |
August | 366.67 | 0.87 | 0.86 | 01-AUG-06:19 | 1107.39 | 19.26 | 17.33 | 371.83 | 450.70 | 21.02 | 204.67 | 289.67 |
September | 301.17 | 0.87 | 0.86 | 01-SEP-07:49 | 3102.74 | 24.50 | 126.17 | 319.67 | 621.02 | 22.01 | 216.67 | 260.50 |
October | 245.33 | 0.87 | 0.86 | 01-OCT-08:09 | 5783.33 | 34.49 | 221.17 | 284.67 | 830.19 | 23.91 | 166.83 | 235.67 |
November | 242.67 | 0.87 | 0.86 | 01-NOV-08:20 | 2375.09 | 31.98 | 225.17 | 225.33 | 1575.19 | 32.27 | 221.17 | 178.50 |
December | 160.33 | 0.87 | 0.86 | 01-DEC-09:39 | 2819.93 | 35.50 | 150.17 | 207.33 | 2300.31 | 36.55 | 150.33 | 145.83 |
Annual Sum or Average | 3714.00 | 0.87 | 2305.62 | 24.60 | 1534.67 | 3696.00 | 818.84 | 23.95 | 2438.00 | 2888.50 | ||
Minimum of Months | 160.33 | 0.87 | 0.86 | 957.62 | 18.17 | 17.33 | 207.33 | 383.70 | 19.94 | 150.33 | 145.83 | |
Maximum of Months | 471.00 | 0.88 | 0.86 | 5783.33 | 35.50 | 239.50 | 393.00 | 2300.31 | 36.55 | 239.33 | 305.83 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.26 | 0.22 | 01-JAN-09:30 | 2307.19 | 32.36 | 223.17 | 230.33 | 1796.22 | 33.31 | 226.67 | 202.33 |
February | 259.50 | 0.25 | 0.22 | 01-FEB-08:30 | 3980.55 | 33.03 | 241.17 | 252.00 | 1871.88 | 29.03 | 208.67 | 229.33 |
March | 247.00 | 0.26 | 0.22 | 01-MAR-07:19 | 5789.72 | 30.49 | 174.83 | 325.50 | 1025.33 | 22.10 | 158.17 | 284.83 |
April | 379.50 | 0.26 | 0.22 | 01-APR-06:00 | 1682.51 | 19.92 | 73.83 | 358.83 | 809.79 | 21.49 | 243.00 | 322.67 |
May | 427.83 | 0.26 | 0.22 | 01-MAY-07:10 | 1538.46 | 19.84 | 94.67 | 401.00 | 728.37 | 21.37 | 269.33 | 358.67 |
June | 375.17 | 0.27 | 0.22 | 01-JUN-05:49 | 1321.89 | 19.82 | 74.83 | 412.50 | 655.55 | 21.39 | 260.33 | 363.67 |
July | 471.00 | 0.29 | 0.22 | 01-JUL-05:19 | 1158.84 | 18.80 | 71.50 | 413.83 | 584.35 | 20.38 | 210.17 | 356.83 |
August | 366.67 | 0.27 | 0.22 | 01-AUG-05:49 | 1361.55 | 19.67 | 56.67 | 389.83 | 704.17 | 21.26 | 217.17 | 345.00 |
September | 301.17 | 0.25 | 0.22 | 01-SEP-07:40 | 3432.33 | 24.74 | 143.00 | 330.00 | 949.72 | 22.15 | 213.33 | 299.33 |
October | 245.33 | 0.26 | 0.22 | 01-OCT-07:49 | 6130.82 | 34.66 | 221.33 | 295.83 | 1177.94 | 23.94 | 176.00 | 265.83 |
November | 242.67 | 0.25 | 0.22 | 01-NOV-07:00 | 2578.41 | 32.09 | 226.17 | 235.83 | 1777.54 | 32.36 | 222.33 | 210.33 |
December | 160.33 | 0.25 | 0.22 | 01-DEC-09:39 | 3098.21 | 35.63 | 150.17 | 219.50 | 2576.90 | 36.66 | 150.33 | 187.00 |
Annual Sum or Average | 3714.00 | 0.26 | 2560.49 | 24.99 | 1751.33 | 3865.00 | 1072.71 | 24.21 | 2555.50 | 3425.83 | ||
Minimum of Months | 160.33 | 0.25 | 0.22 | 1158.84 | 18.80 | 56.67 | 219.50 | 584.35 | 20.38 | 150.33 | 187.00 | |
Maximum of Months | 471.00 | 0.29 | 0.22 | 6130.82 | 35.63 | 241.17 | 413.83 | 2576.90 | 36.66 | 269.33 | 363.67 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.69 | 0.60 | 02-JAN-11:30 | 318.36 | 13.33 | 0.00 | 192.00 | 136.11 | 16.58 | 0.00 | 13.67 |
February | 259.50 | 0.66 | 0.60 | 01-FEB-09:30 | 394.92 | 14.61 | 0.00 | 224.83 | 174.55 | 17.91 | 0.00 | 89.83 |
March | 247.00 | 0.64 | 0.60 | 01-MAR-08:50 | 511.93 | 16.02 | 0.00 | 308.83 | 236.32 | 19.28 | 0.17 | 176.67 |
April | 379.50 | 0.62 | 0.60 | 01-APR-07:10 | 613.26 | 16.81 | 0.00 | 357.00 | 273.96 | 19.98 | 21.33 | 286.33 |
May | 427.83 | 0.62 | 0.60 | 01-MAY-07:19 | 766.41 | 18.01 | 17.50 | 405.83 | 339.18 | 21.62 | 140.33 | 357.00 |
June | 375.17 | 0.62 | 0.60 | 01-JUN-05:19 | 796.72 | 19.30 | 39.83 | 422.83 | 371.58 | 23.25 | 177.67 | 384.17 |
July | 471.00 | 0.63 | 0.60 | 01-JUL-04:00 | 668.50 | 18.25 | 47.83 | 432.00 | 312.88 | 22.35 | 168.50 | 318.33 |
August | 366.67 | 0.62 | 0.60 | 01-AUG-05:40 | 570.15 | 17.52 | 13.17 | 396.17 | 267.01 | 20.71 | 53.50 | 300.00 |
September | 301.17 | 0.63 | 0.60 | 01-SEP-07:40 | 546.29 | 16.85 | 0.00 | 320.83 | 259.77 | 20.07 | 9.00 | 238.83 |
October | 245.33 | 0.65 | 0.60 | 01-OCT-08:30 | 410.78 | 15.21 | 0.00 | 270.17 | 196.22 | 18.56 | 0.00 | 122.67 |
November | 242.67 | 0.68 | 0.60 | 01-NOV-11:20 | 344.37 | 13.80 | 0.00 | 204.17 | 146.28 | 17.02 | 0.00 | 27.33 |
December | 160.33 | 0.69 | 0.60 | 01-DEC-10:20 | 288.02 | 13.46 | 0.00 | 169.00 | 135.96 | 16.95 | 0.00 | 13.17 |
Annual Sum or Average | 3714.00 | 0.64 | 560.89 | 16.58 | 118.33 | 3703.67 | 256.72 | 20.05 | 570.50 | 2328.00 | ||
Minimum of Months | 160.33 | 0.62 | 0.60 | 288.02 | 13.33 | 0.00 | 169.00 | 135.96 | 16.58 | 0.00 | 13.17 | |
Maximum of Months | 471.00 | 0.69 | 0.60 | 796.72 | 19.30 | 47.83 | 432.00 | 371.58 | 23.25 | 177.67 | 384.17 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.69 | 0.60 | 02-JAN-11:30 | 318.36 | 13.33 | 0.00 | 192.00 | 136.11 | 16.58 | 0.00 | 13.67 |
February | 259.50 | 0.66 | 0.60 | 01-FEB-09:30 | 394.92 | 14.61 | 0.00 | 224.83 | 174.55 | 17.91 | 0.00 | 89.83 |
March | 247.00 | 0.64 | 0.60 | 01-MAR-08:50 | 511.93 | 16.02 | 0.00 | 308.83 | 236.32 | 19.28 | 0.17 | 176.67 |
April | 379.50 | 0.62 | 0.60 | 01-APR-07:10 | 613.26 | 16.81 | 0.00 | 357.00 | 273.96 | 19.98 | 21.33 | 286.33 |
May | 427.83 | 0.62 | 0.60 | 01-MAY-07:19 | 766.41 | 18.01 | 17.50 | 405.83 | 339.18 | 21.62 | 140.50 | 357.00 |
June | 375.17 | 0.62 | 0.60 | 01-JUN-05:19 | 796.72 | 19.30 | 39.83 | 422.83 | 371.58 | 23.25 | 177.67 | 384.17 |
July | 471.00 | 0.63 | 0.60 | 01-JUL-04:00 | 668.50 | 18.25 | 47.83 | 432.00 | 312.88 | 22.35 | 168.50 | 318.33 |
August | 366.67 | 0.62 | 0.60 | 01-AUG-05:40 | 570.15 | 17.52 | 13.17 | 396.17 | 267.01 | 20.72 | 53.50 | 300.00 |
September | 301.17 | 0.63 | 0.60 | 01-SEP-07:40 | 546.29 | 16.85 | 0.00 | 320.83 | 259.77 | 20.07 | 9.00 | 238.83 |
October | 245.33 | 0.65 | 0.60 | 01-OCT-08:30 | 410.78 | 15.21 | 0.00 | 270.17 | 196.22 | 18.56 | 0.00 | 122.67 |
November | 242.67 | 0.68 | 0.60 | 01-NOV-11:20 | 344.37 | 13.80 | 0.00 | 204.17 | 146.28 | 17.02 | 0.00 | 27.33 |
December | 160.33 | 0.69 | 0.60 | 01-DEC-10:20 | 288.02 | 13.46 | 0.00 | 169.00 | 135.96 | 16.95 | 0.00 | 13.17 |
Annual Sum or Average | 3714.00 | 0.64 | 560.89 | 16.58 | 118.33 | 3703.67 | 256.72 | 20.05 | 570.67 | 2328.00 | ||
Minimum of Months | 160.33 | 0.62 | 0.60 | 288.02 | 13.33 | 0.00 | 169.00 | 135.96 | 16.58 | 0.00 | 13.17 | |
Maximum of Months | 471.00 | 0.69 | 0.60 | 796.72 | 19.30 | 47.83 | 432.00 | 371.58 | 23.25 | 177.67 | 384.17 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.259956E+11 | 104404.95 | 25-JAN-18:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427424E+11 | 116878.27 | 12-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.695411E+11 | 108840.05 | 01-MAR-19:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.742032E+11 | 107519.96 | 18-APR-17:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.704756E+11 | 104465.14 | 27-MAY-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.405149E+11 | 88525.90 | 01-JUN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153781E+11 | 56243.10 | 07-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117653E+11 | 56871.27 | 21-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.414526E+11 | 95736.89 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.977017E+11 | 106194.39 | 31-OCT-22:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.565553E+11 | 108704.64 | 24-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.336303E+11 | 108590.84 | 02-DEC-23:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.579956E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.117653E+11 | 56243.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.977017E+11 | 116878.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.329767E+10 | 1967.98 | 16-JAN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.219649E+10 | 2087.52 | 19-FEB-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174059E+10 | 1632.55 | 05-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104256E+10 | 1345.02 | 18-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.697140E+09 | 1144.49 | 18-MAY-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.381144E+09 | 964.24 | 14-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149533E+09 | 774.85 | 01-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.176170E+09 | 717.25 | 22-AUG-07:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.489851E+09 | 1294.45 | 26-SEP-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123605E+10 | 1403.98 | 27-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.243414E+10 | 1871.18 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.312067E+10 | 2194.68 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.149533E+09 | 717.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.329767E+10 | 2194.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 55834319.31 | 386.21 | 16-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18549672.45 | 299.97 | 17-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 576956.39 | 101.83 | 13-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9070714.41 | 202.34 | 30-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 52380917.60 | 394.42 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55834319.31 | 394.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.540368E+09 | 649.55 | 16-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285878E+09 | 553.90 | 20-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17063280.89 | 291.22 | 05-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116699E+09 | 394.83 | 26-NOV-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.387903E+09 | 621.10 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.540368E+09 | 649.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.545977E+09 | 464.46 | 16-JAN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311243E+09 | 409.67 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 49050532.69 | 272.59 | 05-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1879100.83 | 128.80 | 19-APR-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1178361.23 | 75.65 | 31-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.177860E+09 | 314.97 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.436091E+09 | 460.02 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.545977E+09 | 464.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.313794E+09 | 2018.19 | 17-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.245141E+09 | 1958.20 | 18-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.202805E+09 | 1675.86 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134997E+09 | 1431.98 | 01-APR-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 91449325.09 | 1098.47 | 18-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 52382619.99 | 873.82 | 14-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31558008.93 | 742.68 | 17-JUL-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31135981.75 | 830.34 | 03-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 63344938.88 | 1009.36 | 27-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139740E+09 | 1386.21 | 28-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.219474E+09 | 1702.47 | 13-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.310229E+09 | 1953.56 | 26-DEC-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 31135981.75 | 742.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.313794E+09 | 2018.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.280308E+10 | 4975.02 | 26-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139631E+10 | 4924.81 | 17-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.968670E+09 | 4007.86 | 05-MAR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.288684E+09 | 3136.33 | 11-APR-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164655E+09 | 2838.40 | 17-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 49679056.06 | 2547.42 | 14-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 23359295.08 | 2243.18 | 12-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18922700.79 | 1963.57 | 01-AUG-10:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.212712E+09 | 3567.72 | 26-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.592029E+09 | 3730.73 | 27-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182650E+10 | 5080.60 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261376E+10 | 5840.43 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 18922700.79 | 1963.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.280308E+10 | 5840.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.550650E+09 | 6398.96 | 16-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133126E+09 | 4524.40 | 17-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4701966.76 | 1591.54 | 05-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111585E+09 | 3669.87 | 30-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.592169E+09 | 6903.45 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.592169E+09 | 6903.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.752212E+10 | 6387.43 | 16-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.410517E+10 | 5662.86 | 17-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142953E+10 | 4193.54 | 05-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141875E+09 | 2891.40 | 18-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.716775E+09 | 3647.71 | 31-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.421417E+10 | 5644.15 | 30-NOV-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.678377E+10 | 6920.94 | 26-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.249134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.752212E+10 | 6920.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.415146E+10 | 2985.83 | 16-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.247746E+10 | 3320.90 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.100992E+10 | 1822.17 | 05-MAR-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.233364E+09 | 1573.36 | 18-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2065797.32 | 285.55 | 18-MAY-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6603780.89 | 597.21 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.449981E+09 | 1385.88 | 31-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223865E+10 | 2478.13 | 30-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.381193E+10 | 3244.98 | 26-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.415146E+10 | 3320.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106765E+09 | 1482.44 | 07-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 93373363.91 | 2210.99 | 19-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15235.68 | 21.79 | 01-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3889.58 | 0.42 | 29-APR-21:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10242.39 | 0.43 | 04-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20863.51 | 0.43 | 12-JUN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 23469.91 | 0.43 | 15-JUL-03:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30023.96 | 0.43 | 12-AUG-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16784.32 | 0.43 | 01-SEP-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6267.19 | 0.42 | 08-OCT-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 52295.84 | 86.29 | 30-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13572972.26 | 2104.91 | 26-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213891E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3889.58 | 0.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106765E+09 | 2210.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.372904E+10 | 7838.69 | 15-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.226837E+10 | 7802.01 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123810E+10 | 7603.31 | 05-MAR-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.471155E+09 | 7571.88 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112126E+09 | 4606.77 | 26-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22293044.25 | 4517.38 | 05-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7804677.21 | 4203.43 | 31-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10800429.24 | 4258.47 | 28-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 56781898.73 | 3705.58 | 18-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.663857E+09 | 7387.61 | 31-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.219695E+10 | 7713.11 | 30-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.345402E+10 | 7847.28 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 7804677.21 | 3705.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.372904E+10 | 7847.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.430062E+10 | 7768.75 | 07-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.288969E+10 | 7778.10 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165961E+10 | 7523.31 | 24-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.628548E+09 | 7456.03 | 19-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125068E+09 | 4129.79 | 01-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24488597.30 | 3849.34 | 07-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7150506.31 | 3508.02 | 19-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6740784.21 | 3141.53 | 16-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 66094473.43 | 3967.39 | 27-SEP-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.945303E+09 | 7383.51 | 16-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.264380E+10 | 7604.14 | 13-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.405130E+10 | 7721.34 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173484E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6740784.21 | 3141.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.430062E+10 | 7778.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.976957E+10 | 42203.17 | 06-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.629237E+10 | 42049.01 | 19-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133819E+10 | 28835.79 | 14-MAR-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.235753E+09 | 25454.10 | 13-APR-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 51781848.23 | 19386.84 | 21-MAY-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20296197.62 | 22416.60 | 12-JUN-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 19825357.24 | 25938.10 | 04-JUL-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 27789134.80 | 14657.47 | 02-AUG-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 51855089.97 | 21317.09 | 28-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.338043E+09 | 25113.92 | 03-OCT-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.354725E+10 | 41488.40 | 30-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.837527E+10 | 42063.05 | 26-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.300680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 19825357.24 | 14657.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.976957E+10 | 42203.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.376286E+10 | 7673.11 | 08-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.228796E+10 | 7668.80 | 18-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121133E+10 | 7476.00 | 05-MAR-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.446839E+09 | 7444.45 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144881E+09 | 4368.41 | 08-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 23632085.16 | 3856.89 | 06-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5893106.80 | 3364.32 | 25-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6119788.12 | 4461.87 | 20-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 69353563.62 | 4481.29 | 03-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.687573E+09 | 7307.90 | 31-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.221193E+10 | 7592.27 | 30-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.349156E+10 | 7724.26 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5893106.80 | 3364.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.376286E+10 | 7724.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.434699E+10 | 7597.10 | 08-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.289618E+10 | 7592.61 | 19-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159482E+10 | 7378.75 | 05-MAR-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.580801E+09 | 7331.35 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166294E+09 | 3928.01 | 01-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24740895.86 | 3720.46 | 06-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3700831.56 | 3262.29 | 03-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4169284.07 | 3195.75 | 18-AUG-21:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87102373.04 | 3741.87 | 18-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.966628E+09 | 7270.58 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.263996E+10 | 7471.47 | 30-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.407073E+10 | 7601.26 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3700831.56 | 3195.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.434699E+10 | 7601.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.136142E+10 | 2398.92 | 07-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.867920E+09 | 2399.94 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.523425E+09 | 2332.55 | 05-MAR-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.227422E+09 | 2319.87 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82203244.09 | 1572.58 | 18-MAY-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19474826.14 | 1104.14 | 05-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1838858.93 | 1077.21 | 31-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3957914.31 | 1047.99 | 10-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 39840118.63 | 1049.25 | 06-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.313769E+09 | 2284.14 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.848708E+09 | 2350.98 | 13-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127129E+10 | 2382.45 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.556127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1838858.93 | 1047.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.136142E+10 | 2399.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.154165E+10 | 2351.56 | 07-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106482E+10 | 2352.53 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.665172E+09 | 2297.16 | 24-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.285981E+09 | 2275.57 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 84768022.99 | 1498.83 | 18-MAY-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 18794007.36 | 865.47 | 05-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1391219.23 | 790.44 | 19-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2260104.17 | 934.34 | 23-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45613194.81 | 1660.51 | 28-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.423233E+09 | 2254.20 | 16-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.989109E+09 | 2318.61 | 13-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145868E+10 | 2335.43 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.658147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1391219.23 | 790.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.154165E+10 | 2352.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.381014E+10 | 11536.47 | 16-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.207784E+10 | 11484.72 | 17-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.955668E+09 | 11230.87 | 05-MAR-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.405270E+09 | 8306.85 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143366E+09 | 5977.22 | 08-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33898780.12 | 6349.54 | 29-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 12880906.04 | 6753.74 | 16-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15377776.47 | 5810.97 | 20-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 60199326.82 | 6512.68 | 18-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.427464E+09 | 6008.27 | 19-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.195126E+10 | 11505.08 | 30-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.358761E+10 | 11663.84 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 12880906.04 | 5810.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.381014E+10 | 11663.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.542296E+11 | 0.542296E+11 | 41889.89 | 31-JAN-11:15 | 41889.89 | 0.00 |
February | 0.00 | 0.00 | 0.500762E+11 | 0.500762E+11 | 43800.54 | 11-FEB-17:05 | 43800.54 | 0.00 |
March | 0.00 | 0.00 | 0.558722E+11 | 0.558722E+11 | 50231.45 | 31-MAR-23:07 | 50231.45 | 0.00 |
April | 0.00 | 0.00 | 0.534427E+11 | 0.534407E+11 | 50219.24 | 01-APR-05:05 | 50219.24 | 0.00 |
May | 0.00 | 0.00 | 0.537667E+11 | 0.512887E+11 | 54991.61 | 31-MAY-23:07 | 52046.76 | 0.00 |
June | 0.00 | 0.00 | 0.504844E+11 | 0.480193E+11 | 54974.02 | 01-JUN-05:50 | 52032.36 | 0.00 |
July | 0.00 | 0.00 | 0.510583E+11 | 0.469310E+11 | 57263.85 | 01-JUL-05:15 | 52700.05 | 0.00 |
August | 0.00 | 0.00 | 0.509452E+11 | 0.441378E+11 | 58691.65 | 31-AUG-06:15 | 50944.62 | 0.00 |
September | 0.00 | 0.00 | 0.492481E+11 | 0.412980E+11 | 55236.94 | 30-SEP-05:15 | 46054.00 | 0.00 |
October | 0.00 | 0.00 | 0.513978E+11 | 0.485292E+11 | 50508.12 | 31-OCT-07:15 | 47646.77 | 0.00 |
November | 0.00 | 0.00 | 0.507322E+11 | 0.486366E+11 | 46928.66 | 30-NOV-00:07 | 44987.18 | 0.00 |
December | 0.00 | 0.00 | 0.532634E+11 | 0.532634E+11 | 43124.35 | 31-DEC-08:40 | 43124.35 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.624517E+12 | 0.595723E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.492481E+11 | 0.412980E+11 | 41889.89 | 41889.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.558722E+11 | 0.558722E+11 | 58691.65 | 52700.05 | 0.00 |
Report: CoilReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.420045E+11 | 0.420045E+11 | 53006.54 | 31-JAN-17:30 | 53006.54 | 0.00 |
February | 0.00 | 0.00 | 0.397177E+11 | 0.397177E+11 | 55425.87 | 11-FEB-20:30 | 55425.87 | 0.00 |
March | 0.00 | 0.00 | 0.468524E+11 | 0.468524E+11 | 59232.14 | 01-MAR-17:10 | 59232.14 | 0.00 |
April | 0.00 | 0.00 | 0.485431E+11 | 0.485428E+11 | 63553.46 | 01-APR-16:05 | 63553.46 | 0.00 |
May | 0.00 | 0.00 | 0.525437E+11 | 0.501622E+11 | 66676.24 | 01-MAY-21:40 | 63233.12 | 0.00 |
June | 0.00 | 0.00 | 0.530525E+11 | 0.505048E+11 | 69574.14 | 01-JUN-16:05 | 65967.56 | 0.00 |
July | 0.00 | 0.00 | 0.571922E+11 | 0.526232E+11 | 72473.60 | 01-JUL-20:05 | 66721.10 | 0.00 |
August | 0.00 | 0.00 | 0.586967E+11 | 0.508975E+11 | 74281.53 | 31-AUG-16:03 | 64496.78 | 0.00 |
September | 0.00 | 0.00 | 0.534013E+11 | 0.448002E+11 | 69907.06 | 30-SEP-16:40 | 58678.32 | 0.00 |
October | 0.00 | 0.00 | 0.504090E+11 | 0.476118E+11 | 63919.25 | 31-OCT-16:10 | 60322.59 | 0.00 |
November | 0.00 | 0.00 | 0.453440E+11 | 0.435013E+11 | 59386.81 | 30-NOV-19:50 | 56953.18 | 0.00 |
December | 0.00 | 0.00 | 0.431583E+11 | 0.431583E+11 | 54569.66 | 31-DEC-17:10 | 54569.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.590915E+12 | 0.560377E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.397177E+11 | 0.397177E+11 | 53006.54 | 53006.54 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.586967E+11 | 0.526232E+11 | 74281.53 | 66721.10 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.176666E+10 | 0.176666E+10 | 78745.58 | 27-FEB-15:00 | 78745.58 | 0.01 |
March | 0.00 | 0.00 | 0.394506E+10 | 0.394506E+10 | 103396.31 | 18-MAR-16:00 | 103396.31 | 0.01 |
April | 0.00 | 0.00 | 0.281106E+11 | 0.281106E+11 | 198574.72 | 27-APR-18:10 | 198574.72 | 0.06 |
May | 0.00 | 0.00 | 0.547785E+11 | 0.542516E+11 | 204795.82 | 05-MAY-18:00 | 165986.84 | 0.18 |
June | 0.00 | 0.00 | 0.975925E+11 | 0.974157E+11 | 209292.46 | 28-JUN-18:10 | 202976.83 | 0.38 |
July | 0.00 | 0.00 | 0.165184E+12 | 0.159039E+12 | 263933.75 | 27-JUL-18:33 | 189129.74 | 0.61 |
August | 0.00 | 0.00 | 0.207650E+12 | 0.198114E+12 | 283274.26 | 10-AUG-18:10 | 241085.18 | 0.79 |
September | 0.00 | 0.00 | 0.800163E+11 | 0.774187E+11 | 197901.80 | 14-SEP-17:15 | 174755.79 | 0.45 |
October | 0.00 | 0.00 | 0.149968E+11 | 0.149813E+11 | 122238.88 | 04-OCT-15:15 | 122238.88 | 0.07 |
November | 0.00 | 0.00 | 0.339029E+10 | 0.339029E+10 | 102497.58 | 04-NOV-15:20 | 102497.58 | 0.04 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.657431E+12 | 0.638433E+12 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.207650E+12 | 0.198114E+12 | 283274.26 | 241085.18 | 0.79 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.108440E+09 | 0.108440E+09 | 9635.15 | 27-FEB-16:02 | 9635.15 | 0.00 |
March | 0.00 | 0.00 | 0.232539E+09 | 0.232539E+09 | 12388.66 | 18-MAR-16:00 | 12388.66 | 0.00 |
April | 0.00 | 0.00 | 0.179866E+10 | 0.179842E+10 | 18216.45 | 27-APR-15:02 | 18216.45 | 0.04 |
May | 0.00 | 0.00 | 0.358834E+10 | 0.343697E+10 | 21148.09 | 05-MAY-18:07 | 16125.48 | 0.12 |
June | 0.00 | 0.00 | 0.631575E+10 | 0.631105E+10 | 18083.89 | 22-JUN-18:20 | 16905.99 | 0.26 |
July | 0.00 | 0.00 | 0.118421E+11 | 0.109131E+11 | 24080.93 | 15-JUL-18:07 | 15807.76 | 0.45 |
August | 0.00 | 0.00 | 0.155328E+11 | 0.141125E+11 | 25119.38 | 30-AUG-12:40 | 15889.86 | 0.60 |
September | 0.00 | 0.00 | 0.552409E+10 | 0.511606E+10 | 23375.10 | 14-SEP-12:50 | 15655.25 | 0.31 |
October | 0.00 | 0.00 | 0.905033E+09 | 0.903628E+09 | 14148.85 | 04-OCT-15:02 | 14148.85 | 0.04 |
November | 0.00 | 0.00 | 0.222488E+09 | 0.196313E+09 | 16088.96 | 04-NOV-15:02 | 13200.11 | 0.02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.460702E+11 | 0.431290E+11 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.155328E+11 | 0.141125E+11 | 25119.38 | 18216.45 | 0.60 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 16209681.83 | 9619263.97 | 10750.01 | 05-JAN-16:02 | 10750.01 | 0.00 |
February | 0.00 | 0.00 | 0.224369E+09 | 0.126920E+09 | 13122.12 | 28-FEB-16:02 | 11893.46 | 0.08 |
March | 0.00 | 0.00 | 0.782222E+09 | 0.549490E+09 | 13330.13 | 18-MAR-18:01 | 13330.13 | 0.15 |
April | 0.00 | 0.00 | 0.225003E+10 | 0.145604E+10 | 14383.38 | 30-APR-15:01 | 11488.47 | 0.44 |
May | 0.00 | 0.00 | 0.419965E+10 | 0.271689E+10 | 13865.31 | 05-MAY-18:02 | 13235.38 | 0.70 |
June | 0.00 | 0.00 | 0.491770E+10 | 0.296908E+10 | 14514.90 | 12-JUN-15:01 | 11636.90 | 0.84 |
July | 0.00 | 0.00 | 0.771746E+10 | 0.497059E+10 | 14481.18 | 16-JUL-15:01 | 11866.64 | 0.92 |
August | 0.00 | 0.00 | 0.748544E+10 | 0.466990E+10 | 15141.64 | 29-AUG-08:62 | 11632.41 | 0.91 |
September | 0.00 | 0.00 | 0.498751E+10 | 0.298797E+10 | 14422.48 | 25-SEP-15:02 | 10308.20 | 0.79 |
October | 0.00 | 0.00 | 0.146195E+10 | 0.840356E+09 | 14043.36 | 01-OCT-08:62 | 10893.34 | 0.36 |
November | 0.00 | 0.00 | 0.168243E+09 | 75755473.15 | 14740.62 | 05-NOV-15:01 | 11291.76 | 0.06 |
December | 0.00 | 0.00 | 34504806.93 | 22271538.02 | 12567.92 | 10-DEC-16:02 | 11686.95 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.342453E+11 | 0.213949E+11 | 0.44 | |||
Minimum of Months | 0.00 | 0.00 | 16209681.83 | 9619263.97 | 10750.01 | 10308.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.771746E+10 | 0.497059E+10 | 15141.64 | 13330.13 | 0.92 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6658095.13 | 2792111.06 | 2748.62 | 30-JAN-16:04 | 1640.31 | 0.00 |
February | 0.00 | 0.00 | 49246137.06 | 24792927.23 | 11462.04 | 28-FEB-16:02 | 10104.47 | 0.02 |
March | 0.00 | 0.00 | 0.254685E+09 | 0.171953E+09 | 11602.09 | 25-MAR-15:02 | 11602.09 | 0.06 |
April | 0.00 | 0.00 | 0.122006E+10 | 0.748034E+09 | 13768.94 | 25-APR-17:41 | 13768.94 | 0.29 |
May | 0.00 | 0.00 | 0.249494E+10 | 0.140932E+10 | 13772.34 | 21-MAY-17:41 | 13772.34 | 0.57 |
June | 0.00 | 0.00 | 0.324203E+10 | 0.183080E+10 | 13317.60 | 22-JUN-21:51 | 11914.55 | 0.63 |
July | 0.00 | 0.00 | 0.516869E+10 | 0.321036E+10 | 14900.08 | 15-JUL-21:51 | 11959.65 | 0.68 |
August | 0.00 | 0.00 | 0.504129E+10 | 0.308778E+10 | 14087.69 | 24-AUG-21:51 | 11911.49 | 0.67 |
September | 0.00 | 0.00 | 0.245942E+10 | 0.120954E+10 | 13905.81 | 22-SEP-16:11 | 13905.81 | 0.56 |
October | 0.00 | 0.00 | 0.469506E+09 | 0.225717E+09 | 13493.92 | 01-OCT-15:01 | 10215.03 | 0.20 |
November | 0.00 | 0.00 | 36128277.74 | 14881235.65 | 13874.65 | 04-NOV-15:02 | 10737.39 | 0.02 |
December | 0.00 | 0.00 | 8023473.03 | 4181858.42 | 4844.44 | 10-DEC-16:02 | 3003.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.204507E+11 | 0.119401E+11 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 6658095.13 | 2792111.06 | 2748.62 | 1640.31 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.516869E+10 | 0.321036E+10 | 14900.08 | 13905.81 | 0.68 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.405767E+10 | 0.360554E+10 | 38705.24 | 08-FEB-13:40 | 38705.24 | 0.04 |
March | 0.00 | 0.00 | 0.120522E+11 | 0.973717E+10 | 50166.21 | 02-MAR-13:00 | 41688.02 | 0.15 |
April | 0.00 | 0.00 | 0.195621E+11 | 0.117442E+11 | 46067.82 | 27-APR-12:50 | 39776.30 | 0.51 |
May | 0.00 | 0.00 | 0.247492E+11 | 0.117288E+11 | 45000.13 | 04-MAY-13:00 | 38563.63 | 0.76 |
June | 0.00 | 0.00 | 0.273152E+11 | 0.115982E+11 | 34192.86 | 28-JUN-13:00 | 22768.61 | 0.88 |
July | 0.00 | 0.00 | 0.377074E+11 | 0.176558E+11 | 42461.33 | 31-JUL-12:50 | 33232.03 | 0.97 |
August | 0.00 | 0.00 | 0.427580E+11 | 0.224714E+11 | 52379.27 | 24-AUG-13:30 | 50400.11 | 0.96 |
September | 0.00 | 0.00 | 0.365441E+11 | 0.206059E+11 | 55183.91 | 14-SEP-13:30 | 41409.42 | 0.88 |
October | 0.00 | 0.00 | 0.210935E+11 | 0.121303E+11 | 57434.76 | 04-OCT-12:40 | 47958.83 | 0.59 |
November | 0.00 | 0.00 | 0.355482E+10 | 0.178537E+10 | 45820.75 | 04-NOV-13:25 | 39895.95 | 0.13 |
December | 0.00 | 0.00 | 0.179057E+10 | 0.167858E+10 | 34578.61 | 05-DEC-12:30 | 34578.61 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.231185E+12 | 0.124741E+12 | 0.49 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.427580E+11 | 0.224714E+11 | 57434.76 | 50400.11 | 0.97 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.937499E+09 | 0.426819E+09 | 47995.37 | 12-JAN-09:02 | 47995.37 | 0.10 |
February | 0.00 | 0.00 | 0.283652E+10 | 0.138540E+10 | 57364.92 | 25-FEB-09:02 | 50337.77 | 0.20 |
March | 0.00 | 0.00 | 0.724077E+10 | 0.457146E+10 | 57127.83 | 11-MAR-09:02 | 50465.11 | 0.35 |
April | 0.00 | 0.00 | 0.158311E+11 | 0.110239E+11 | 62386.22 | 27-APR-18:02 | 60011.65 | 0.52 |
May | 0.00 | 0.00 | 0.251211E+11 | 0.181195E+11 | 63991.21 | 07-MAY-15:02 | 55267.61 | 0.60 |
June | 0.00 | 0.00 | 0.302159E+11 | 0.223584E+11 | 62094.27 | 28-JUN-15:02 | 60361.15 | 0.60 |
July | 0.00 | 0.00 | 0.356534E+11 | 0.265079E+11 | 65937.91 | 30-JUL-15:02 | 58398.26 | 0.60 |
August | 0.00 | 0.00 | 0.357243E+11 | 0.249125E+11 | 65794.08 | 24-AUG-15:02 | 58841.88 | 0.59 |
September | 0.00 | 0.00 | 0.238773E+11 | 0.150952E+11 | 66943.05 | 23-SEP-15:02 | 55401.19 | 0.57 |
October | 0.00 | 0.00 | 0.114512E+11 | 0.642434E+10 | 62439.96 | 01-OCT-15:01 | 50772.86 | 0.58 |
November | 0.00 | 0.00 | 0.478779E+10 | 0.216710E+10 | 62842.80 | 04-NOV-15:02 | 51200.71 | 0.33 |
December | 0.00 | 0.00 | 0.792363E+09 | 0.412453E+09 | 52220.56 | 03-DEC-09:02 | 52220.56 | 0.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.194469E+12 | 0.133405E+12 | 0.43 | |||
Minimum of Months | 0.00 | 0.00 | 0.792363E+09 | 0.412453E+09 | 47995.37 | 47995.37 | 0.09 | |
Maximum of Months | 0.00 | 0.00 | 0.357243E+11 | 0.265079E+11 | 66943.05 | 60361.15 | 0.60 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 12500064.22 | 5099345.23 | 3191.02 | 20-JAN-16:02 | 2354.93 | 0.01 |
February | 0.00 | 0.00 | 0.194821E+09 | 0.109442E+09 | 11452.58 | 28-FEB-16:02 | 10147.23 | 0.07 |
March | 0.00 | 0.00 | 0.748704E+09 | 0.513827E+09 | 11691.48 | 28-MAR-15:02 | 11691.48 | 0.16 |
April | 0.00 | 0.00 | 0.233041E+10 | 0.144043E+10 | 12812.77 | 30-APR-15:01 | 10263.28 | 0.49 |
May | 0.00 | 0.00 | 0.363958E+10 | 0.222373E+10 | 12658.83 | 05-MAY-15:02 | 11991.97 | 0.69 |
June | 0.00 | 0.00 | 0.524337E+10 | 0.322757E+10 | 12545.93 | 12-JUN-15:01 | 10731.88 | 0.88 |
July | 0.00 | 0.00 | 0.668937E+10 | 0.411385E+10 | 13402.70 | 16-JUL-15:01 | 10425.07 | 0.93 |
August | 0.00 | 0.00 | 0.738291E+10 | 0.462977E+10 | 13530.19 | 20-AUG-15:02 | 10629.46 | 0.93 |
September | 0.00 | 0.00 | 0.448413E+10 | 0.266987E+10 | 13445.76 | 01-SEP-15:02 | 10588.26 | 0.78 |
October | 0.00 | 0.00 | 0.143984E+10 | 0.822997E+09 | 13833.01 | 01-OCT-15:01 | 9982.32 | 0.38 |
November | 0.00 | 0.00 | 0.170471E+09 | 67328463.16 | 13065.23 | 05-NOV-15:01 | 10005.64 | 0.07 |
December | 0.00 | 0.00 | 59104896.78 | 30709468.27 | 9168.15 | 02-DEC-09:02 | 9168.15 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.323952E+11 | 0.198546E+11 | 0.45 | |||
Minimum of Months | 0.00 | 0.00 | 12500064.22 | 5099345.23 | 3191.02 | 2354.93 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.738291E+10 | 0.462977E+10 | 13833.01 | 11991.97 | 0.93 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6312359.70 | 2765643.68 | 2835.13 | 25-JAN-19:05 | 1608.58 | 0.00 |
February | 0.00 | 0.00 | 27476609.01 | 14162480.52 | 9674.74 | 12-FEB-09:01 | 9674.74 | 0.02 |
March | 0.00 | 0.00 | 0.199180E+09 | 0.133924E+09 | 10608.19 | 25-MAR-08:62 | 10608.19 | 0.06 |
April | 0.00 | 0.00 | 0.130747E+10 | 0.776222E+09 | 11599.60 | 30-APR-15:01 | 9240.82 | 0.35 |
May | 0.00 | 0.00 | 0.232154E+10 | 0.136522E+10 | 12587.01 | 06-MAY-08:51 | 11867.30 | 0.54 |
June | 0.00 | 0.00 | 0.374691E+10 | 0.226907E+10 | 11489.58 | 10-JUN-08:51 | 11489.58 | 0.69 |
July | 0.00 | 0.00 | 0.456620E+10 | 0.274840E+10 | 15037.00 | 24-JUL-08:32 | 13531.36 | 0.70 |
August | 0.00 | 0.00 | 0.502384E+10 | 0.303342E+10 | 15272.62 | 10-AUG-08:32 | 13225.43 | 0.70 |
September | 0.00 | 0.00 | 0.233657E+10 | 0.126550E+10 | 12614.78 | 22-SEP-15:02 | 10089.03 | 0.55 |
October | 0.00 | 0.00 | 0.496147E+09 | 0.271363E+09 | 12485.35 | 01-OCT-15:01 | 8548.53 | 0.18 |
November | 0.00 | 0.00 | 34024690.40 | 13010488.11 | 12267.37 | 04-NOV-15:02 | 9032.11 | 0.02 |
December | 0.00 | 0.00 | 7327202.99 | 3373345.54 | 3136.38 | 16-DEC-19:05 | 1600.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.200730E+11 | 0.118964E+11 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 6312359.70 | 2765643.68 | 2835.13 | 1600.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.502384E+10 | 0.303342E+10 | 15272.62 | 13531.36 | 0.70 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3390754.19 | 2032263.04 | 2816.41 | 05-JAN-16:02 | 2816.41 | 0.00 |
February | 0.00 | 0.00 | 54576608.50 | 32415420.98 | 3556.12 | 28-FEB-16:02 | 3095.32 | 0.05 |
March | 0.00 | 0.00 | 0.195500E+09 | 0.142139E+09 | 3492.40 | 18-MAR-18:01 | 3492.40 | 0.12 |
April | 0.00 | 0.00 | 0.569262E+09 | 0.388575E+09 | 3862.73 | 30-APR-08:62 | 2763.79 | 0.36 |
May | 0.00 | 0.00 | 0.106027E+10 | 0.721400E+09 | 3789.55 | 07-MAY-08:62 | 2913.50 | 0.60 |
June | 0.00 | 0.00 | 0.124183E+10 | 0.780571E+09 | 3820.14 | 12-JUN-15:01 | 3039.19 | 0.78 |
July | 0.00 | 0.00 | 0.197035E+10 | 0.129504E+10 | 3871.12 | 31-JUL-08:61 | 3207.25 | 0.91 |
August | 0.00 | 0.00 | 0.186328E+10 | 0.118916E+10 | 4069.57 | 29-AUG-08:62 | 2898.53 | 0.88 |
September | 0.00 | 0.00 | 0.120816E+10 | 0.753739E+09 | 3938.40 | 23-SEP-08:62 | 2795.40 | 0.72 |
October | 0.00 | 0.00 | 0.330526E+09 | 0.202902E+09 | 3845.06 | 01-OCT-08:62 | 2641.87 | 0.27 |
November | 0.00 | 0.00 | 42189229.58 | 20821576.44 | 3946.99 | 05-NOV-15:01 | 2908.93 | 0.05 |
December | 0.00 | 0.00 | 6873484.33 | 4455485.78 | 3395.94 | 10-DEC-16:02 | 3007.96 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.854621E+10 | 0.553325E+10 | 0.40 | |||
Minimum of Months | 0.00 | 0.00 | 3390754.19 | 2032263.04 | 2816.41 | 2641.87 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.197035E+10 | 0.129504E+10 | 4069.57 | 3492.40 | 0.91 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1203999.39 | 533456.75 | 769.11 | 12-JAN-09:05 | 302.43 | 0.00 |
February | 0.00 | 0.00 | 9887565.72 | 4682223.49 | 3052.52 | 28-FEB-16:02 | 2580.48 | 0.02 |
March | 0.00 | 0.00 | 58706926.70 | 39406183.37 | 3062.05 | 18-MAR-15:02 | 3062.05 | 0.05 |
April | 0.00 | 0.00 | 0.302895E+09 | 0.196544E+09 | 3579.98 | 25-APR-17:41 | 3579.98 | 0.23 |
May | 0.00 | 0.00 | 0.628378E+09 | 0.371774E+09 | 3604.59 | 31-MAY-21:51 | 3098.33 | 0.49 |
June | 0.00 | 0.00 | 0.833672E+09 | 0.485568E+09 | 3642.39 | 22-JUN-21:51 | 3201.01 | 0.60 |
July | 0.00 | 0.00 | 0.136333E+10 | 0.863329E+09 | 3943.80 | 26-JUL-21:51 | 3118.23 | 0.69 |
August | 0.00 | 0.00 | 0.126929E+10 | 0.798452E+09 | 3721.91 | 24-AUG-21:51 | 3100.76 | 0.66 |
September | 0.00 | 0.00 | 0.570203E+09 | 0.289791E+09 | 3661.49 | 13-SEP-21:51 | 2954.18 | 0.50 |
October | 0.00 | 0.00 | 88294859.83 | 45728911.97 | 3537.69 | 01-OCT-15:01 | 2638.49 | 0.12 |
November | 0.00 | 0.00 | 9126558.43 | 3536109.83 | 3638.97 | 04-NOV-15:02 | 2772.83 | 0.01 |
December | 0.00 | 0.00 | 1136698.87 | 519604.47 | 954.68 | 28-DEC-16:05 | 487.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.513612E+10 | 0.309986E+10 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 1136698.87 | 519604.47 | 769.11 | 302.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.136333E+10 | 0.863329E+09 | 3943.80 | 3579.98 | 0.69 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.477742E+09 | 0.287482E+09 | 16829.16 | 05-JAN-16:02 | 16829.16 | 0.08 |
February | 0.00 | 0.00 | 0.177903E+10 | 0.119997E+10 | 19081.66 | 28-FEB-16:02 | 17436.50 | 0.24 |
March | 0.00 | 0.00 | 0.306693E+10 | 0.224080E+10 | 19146.40 | 18-MAR-18:01 | 19146.40 | 0.32 |
April | 0.00 | 0.00 | 0.471531E+10 | 0.300766E+10 | 20801.73 | 30-APR-15:01 | 16453.78 | 0.59 |
May | 0.00 | 0.00 | 0.596287E+10 | 0.364080E+10 | 20568.52 | 05-MAY-18:02 | 18651.63 | 0.72 |
June | 0.00 | 0.00 | 0.671660E+10 | 0.378625E+10 | 20792.77 | 12-JUN-15:01 | 16769.58 | 0.84 |
July | 0.00 | 0.00 | 0.944516E+10 | 0.554307E+10 | 21313.10 | 16-JUL-15:01 | 16770.42 | 0.90 |
August | 0.00 | 0.00 | 0.105751E+11 | 0.642770E+10 | 21316.90 | 29-AUG-08:62 | 17195.57 | 0.91 |
September | 0.00 | 0.00 | 0.865810E+10 | 0.546912E+10 | 20709.76 | 01-SEP-15:02 | 17417.38 | 0.82 |
October | 0.00 | 0.00 | 0.466753E+10 | 0.305193E+10 | 19852.74 | 01-OCT-08:62 | 16267.38 | 0.57 |
November | 0.00 | 0.00 | 0.121662E+10 | 0.673744E+09 | 19550.97 | 05-NOV-08:62 | 16394.45 | 0.21 |
December | 0.00 | 0.00 | 0.100021E+10 | 0.677586E+09 | 18360.87 | 10-DEC-16:02 | 17930.53 | 0.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.582812E+11 | 0.360061E+11 | 0.53 | |||
Minimum of Months | 0.00 | 0.00 | 0.477742E+09 | 0.287482E+09 | 16829.16 | 16267.38 | 0.08 | |
Maximum of Months | 0.00 | 0.00 | 0.105751E+11 | 0.642770E+10 | 21316.90 | 19146.40 | 0.91 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 29009.19 | 173278.78 | 26-JAN-19:03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 30556.88 | 157562.30 | 15-FEB-16:01 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 31132.76 | 131915.19 | 07-MAR-09:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 30331.21 | 120914.30 | 06-APR-08:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26777.60 | 122012.91 | 28-MAY-08:04 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 15756.00 | 88682.43 | 01-JUN-04:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 5791.37 | 57158.19 | 19-JUL-05:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 4468.43 | 67955.28 | 01-AUG-08:04 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16332.70 | 113298.88 | 28-SEP-08:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 39090.67 | 137740.61 | 22-OCT-08:07 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 32465.16 | 163277.69 | 26-NOV-19:03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 30129.20 | 155543.95 | 31-DEC-19:03 |
Annual Sum or Average | 0.00 | 24275.40 | ||||
Minimum of Months | 0.00 | 0.00 | 4468.43 | 57158.19 | ||
Maximum of Months | 0.00 | 0.00 | 39090.67 | 173278.78 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1188.64 | 29384.37 | 11-JAN-16:03 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 5922.96 | 214877.52 | 27-FEB-16:02 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 12967.00 | 247171.88 | 18-MAR-15:03 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 33098.14 | 372869.95 | 27-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 51255.71 | 336755.00 | 04-MAY-15:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 75612.65 | 379905.14 | 28-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 110617.08 | 442591.33 | 31-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 130423.86 | 472578.45 | 10-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 69121.08 | 383496.72 | 14-SEP-15:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 24271.71 | 292575.86 | 04-OCT-15:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 6742.60 | 288652.55 | 04-NOV-15:03 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 2129.55 | 45866.68 | 05-DEC-12:30 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 43894.62 | 0.00 | ||||
Minimum of Months | 1188.64 | 29384.37 | 0.00 | 0.00 | ||
Maximum of Months | 130423.86 | 472578.45 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 26493.51 | 55715.73 | 31-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26675.55 | 55800.57 | 10-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 26393.32 | 55588.51 | 01-MAR-07:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25659.47 | 54355.55 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 24717.24 | 52623.09 | 01-MAY-06:50 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 23806.46 | 50505.70 | 01-JUN-06:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 23138.14 | 48719.86 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 22961.99 | 47994.99 | 31-AUG-06:30 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23258.58 | 49075.37 | 29-SEP-06:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 23975.39 | 51028.38 | 31-OCT-06:50 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 24925.22 | 52980.43 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 25844.25 | 54740.19 | 29-DEC-07:40 |
Annual Sum or Average | 0.00 | 24809.99 | ||||
Minimum of Months | 0.00 | 0.00 | 22961.99 | 47994.99 | ||
Maximum of Months | 0.00 | 0.00 | 26675.55 | 55800.57 |
Report: FanReportMonthly
For: SWHSYS1 HPWH FAN
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.744382E+09 | 0.06 | 553.22 | 01-JAN-06:15 | 0.10 |
February | 0.657836E+09 | 0.06 | 553.22 | 01-FEB-00:07 | 0.10 |
March | 0.692041E+09 | 0.06 | 553.22 | 01-MAR-00:20 | 0.10 |
April | 0.622321E+09 | 0.06 | 553.22 | 01-APR-05:05 | 0.10 |
May | 0.599306E+09 | 0.06 | 553.22 | 01-MAY-05:15 | 0.10 |
June | 0.542630E+09 | 0.06 | 553.22 | 01-JUN-04:10 | 0.10 |
July | 0.528879E+09 | 0.06 | 553.22 | 01-JUL-05:15 | 0.10 |
August | 0.515716E+09 | 0.06 | 553.22 | 01-AUG-05:15 | 0.10 |
September | 0.528121E+09 | 0.06 | 553.22 | 01-SEP-05:15 | 0.10 |
October | 0.598942E+09 | 0.06 | 553.22 | 01-OCT-05:15 | 0.10 |
November | 0.632619E+09 | 0.06 | 553.22 | 01-NOV-05:13 | 0.10 |
December | 0.714901E+09 | 0.06 | 553.22 | 01-DEC-00:07 | 0.10 |
Annual Sum or Average | 0.737769E+10 | 0.06 | |||
Minimum of Months | 0.515716E+09 | 0.06 | 553.22 | 0.10 | |
Maximum of Months | 0.744382E+09 | 0.06 | 553.22 | 0.10 |
Report: FanReportMonthly
For: SWHSYSLAUNDRY HPWH FAN
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.558343E+09 | 0.06 | 700.51 | 01-JAN-17:10 | 0.10 |
February | 0.504098E+09 | 0.06 | 700.51 | 01-FEB-17:10 | 0.10 |
March | 0.557428E+09 | 0.06 | 700.51 | 01-MAR-17:10 | 0.10 |
April | 0.539125E+09 | 0.06 | 700.51 | 01-APR-16:05 | 0.10 |
May | 0.556625E+09 | 0.05 | 700.51 | 01-MAY-16:10 | 0.10 |
June | 0.538136E+09 | 0.05 | 700.51 | 01-JUN-16:05 | 0.10 |
July | 0.555982E+09 | 0.05 | 700.51 | 01-JUL-16:10 | 0.10 |
August | 0.555584E+09 | 0.05 | 700.51 | 01-AUG-16:10 | 0.10 |
September | 0.538495E+09 | 0.05 | 700.51 | 01-SEP-16:10 | 0.10 |
October | 0.556974E+09 | 0.06 | 700.51 | 01-OCT-16:10 | 0.10 |
November | 0.539383E+09 | 0.06 | 700.51 | 01-NOV-16:10 | 0.10 |
December | 0.558388E+09 | 0.06 | 700.51 | 01-DEC-17:10 | 0.10 |
Annual Sum or Average | 0.655856E+10 | 0.06 | |||
Minimum of Months | 0.504098E+09 | 0.05 | 700.51 | 0.10 | |
Maximum of Months | 0.558388E+09 | 0.06 | 700.51 | 0.10 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.70 | 1299.30 | 01-JAN-16:30 | 0.89 |
February | 0.244774E+10 | 0.70 | 1299.30 | 01-FEB-06:20 | 0.89 |
March | 0.271000E+10 | 0.70 | 1299.30 | 01-MAR-01:50 | 0.89 |
April | 0.262258E+10 | 0.70 | 1299.30 | 01-APR-01:00 | 0.89 |
May | 0.271000E+10 | 0.70 | 1299.30 | 01-MAY-05:00 | 0.88 |
June | 0.262258E+10 | 0.70 | 1299.30 | 01-JUN-01:40 | 0.88 |
July | 0.271000E+10 | 0.70 | 1299.30 | 01-JUL-02:40 | 0.89 |
August | 0.271000E+10 | 0.70 | 1299.30 | 01-AUG-03:20 | 0.88 |
September | 0.262258E+10 | 0.70 | 1299.30 | 01-SEP-00:40 | 0.88 |
October | 0.271000E+10 | 0.70 | 1299.30 | 01-OCT-01:00 | 0.88 |
November | 0.262258E+10 | 0.70 | 1299.30 | 01-NOV-05:17 | 0.88 |
December | 0.271000E+10 | 0.70 | 1299.30 | 01-DEC-22:30 | 0.89 |
Annual Sum or Average | 0.319080E+11 | 0.70 | |||
Minimum of Months | 0.244774E+10 | 0.70 | 1299.30 | 0.88 | |
Maximum of Months | 0.271000E+10 | 0.70 | 1299.30 | 0.89 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.345523E+11 | 0.84 | 18849.74 | 11-JAN-21:10 | 1.05 |
February | 0.315696E+11 | 0.85 | 19692.57 | 27-FEB-22:10 | 1.07 |
March | 0.356828E+11 | 0.86 | 19800.75 | 14-MAR-21:10 | 1.08 |
April | 0.351511E+11 | 0.86 | 24222.78 | 27-APR-21:10 | 1.22 |
May | 0.370901E+11 | 0.87 | 24181.49 | 04-MAY-21:10 | 1.22 |
June | 0.365436E+11 | 0.88 | 24012.35 | 28-JUN-21:10 | 1.21 |
July | 0.382486E+11 | 0.89 | 24669.21 | 31-JUL-21:10 | 1.22 |
August | 0.385596E+11 | 0.89 | 25753.08 | 24-AUG-21:10 | 1.26 |
September | 0.361827E+11 | 0.87 | 25878.13 | 14-SEP-21:10 | 1.26 |
October | 0.360895E+11 | 0.86 | 23645.36 | 04-OCT-21:10 | 1.20 |
November | 0.340888E+11 | 0.85 | 19349.02 | 02-NOV-21:10 | 1.06 |
December | 0.345966E+11 | 0.84 | 18621.88 | 28-DEC-21:10 | 1.04 |
Annual Sum or Average | 0.428355E+12 | 0.86 | |||
Minimum of Months | 0.315696E+11 | 0.84 | 18621.88 | 1.04 | |
Maximum of Months | 0.385596E+11 | 0.89 | 25878.13 | 1.26 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:10 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:03 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:03 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.27 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:05 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:05 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:05 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:05 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:10 | 0.27 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:05 | 0.27 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:03 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:05 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:10 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:05 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:05 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.245211E+09 | 0.42 | 781.53 | 01-JAN-09:02 | 0.58 |
February | 0.175789E+09 | 0.42 | 781.53 | 01-FEB-09:02 | 0.58 |
March | 0.160984E+09 | 0.44 | 781.53 | 01-MAR-16:02 | 0.58 |
April | 0.190019E+09 | 0.46 | 781.53 | 01-APR-15:01 | 0.58 |
May | 0.273759E+09 | 0.50 | 781.53 | 01-MAY-15:01 | 0.58 |
June | 0.293285E+09 | 0.51 | 781.53 | 01-JUN-08:62 | 0.58 |
July | 0.435319E+09 | 0.53 | 781.53 | 01-JUL-08:62 | 0.58 |
August | 0.405113E+09 | 0.53 | 781.53 | 01-AUG-08:61 | 0.58 |
September | 0.291206E+09 | 0.50 | 781.53 | 01-SEP-15:02 | 0.58 |
October | 0.160030E+09 | 0.45 | 781.53 | 01-OCT-08:62 | 0.58 |
November | 0.174990E+09 | 0.42 | 781.53 | 02-NOV-15:02 | 0.58 |
December | 0.234255E+09 | 0.43 | 781.53 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.303996E+10 | 0.47 | |||
Minimum of Months | 0.160030E+09 | 0.42 | 781.53 | 0.58 | |
Maximum of Months | 0.435319E+09 | 0.53 | 781.53 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.250350E+09 | 0.43 | 702.36 | 01-JAN-09:02 | 0.58 |
February | 0.182049E+09 | 0.42 | 702.36 | 01-FEB-09:02 | 0.58 |
March | 0.143036E+09 | 0.41 | 702.36 | 01-MAR-09:02 | 0.58 |
April | 0.132893E+09 | 0.41 | 702.36 | 01-APR-15:01 | 0.58 |
May | 0.167059E+09 | 0.41 | 702.36 | 01-MAY-15:01 | 0.58 |
June | 0.191110E+09 | 0.39 | 702.36 | 01-JUN-08:62 | 0.58 |
July | 0.283791E+09 | 0.39 | 702.36 | 01-JUL-08:62 | 0.58 |
August | 0.271088E+09 | 0.39 | 702.36 | 01-AUG-08:61 | 0.58 |
September | 0.145920E+09 | 0.37 | 702.36 | 01-SEP-08:52 | 0.58 |
October | 0.113228E+09 | 0.40 | 702.36 | 01-OCT-08:62 | 0.58 |
November | 0.176689E+09 | 0.41 | 702.36 | 04-NOV-15:02 | 0.58 |
December | 0.242059E+09 | 0.44 | 702.36 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.229927E+10 | 0.41 | |||
Minimum of Months | 0.113228E+09 | 0.37 | 702.36 | 0.58 | |
Maximum of Months | 0.283791E+09 | 0.44 | 702.36 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.201974E+09 | 0.08 | 1482.48 | 08-FEB-13:40 | 0.58 |
March | 0.620310E+09 | 0.21 | 2896.03 | 02-MAR-13:00 | 0.58 |
April | 0.100592E+10 | 0.39 | 1573.86 | 02-APR-13:30 | 0.58 |
May | 0.122350E+10 | 0.45 | 1563.56 | 04-MAY-13:05 | 0.58 |
June | 0.131499E+10 | 0.51 | 1213.67 | 28-JUN-13:05 | 0.58 |
July | 0.166396E+10 | 0.56 | 1444.02 | 31-JUL-13:20 | 0.58 |
August | 0.179565E+10 | 0.56 | 2531.90 | 24-AUG-13:05 | 0.58 |
September | 0.163983E+10 | 0.51 | 2659.25 | 10-SEP-12:30 | 0.58 |
October | 0.104753E+10 | 0.35 | 2910.03 | 04-OCT-12:40 | 0.58 |
November | 0.180664E+09 | 0.08 | 1592.82 | 04-NOV-13:25 | 0.58 |
December | 91553949.77 | 0.03 | 1357.54 | 05-DEC-12:30 | 0.58 |
Annual Sum or Average | 0.107859E+11 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.179565E+10 | 0.56 | 2910.03 | 0.58 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.691957E+09 | 0.41 | 3351.97 | 01-JAN-09:02 | 0.58 |
February | 0.602019E+09 | 0.41 | 3351.97 | 01-FEB-09:02 | 0.58 |
March | 0.625773E+09 | 0.41 | 3351.97 | 01-MAR-09:02 | 0.58 |
April | 0.100140E+10 | 0.39 | 3351.97 | 01-APR-08:62 | 0.58 |
May | 0.150464E+10 | 0.37 | 3351.97 | 01-MAY-08:62 | 0.58 |
June | 0.175540E+10 | 0.35 | 3351.97 | 01-JUN-08:62 | 0.58 |
July | 0.202299E+10 | 0.35 | 3351.97 | 01-JUL-08:62 | 0.58 |
August | 0.185321E+10 | 0.34 | 3351.97 | 01-AUG-08:61 | 0.58 |
September | 0.126459E+10 | 0.33 | 3351.97 | 01-SEP-08:52 | 0.58 |
October | 0.752772E+09 | 0.39 | 3351.97 | 01-OCT-08:62 | 0.58 |
November | 0.571790E+09 | 0.41 | 3351.97 | 01-NOV-08:62 | 0.58 |
December | 0.627283E+09 | 0.41 | 3351.97 | 01-DEC-16:02 | 0.58 |
Annual Sum or Average | 0.132738E+11 | 0.38 | |||
Minimum of Months | 0.571790E+09 | 0.33 | 3351.97 | 0.58 | |
Maximum of Months | 0.202299E+10 | 0.41 | 3351.97 | 0.58 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.226637E+09 | 0.42 | 701.06 | 01-JAN-09:02 | 0.58 |
February | 0.161862E+09 | 0.42 | 701.06 | 02-FEB-09:02 | 0.58 |
March | 0.147816E+09 | 0.44 | 701.06 | 01-MAR-09:02 | 0.58 |
April | 0.185311E+09 | 0.48 | 701.06 | 01-APR-08:62 | 0.58 |
May | 0.231999E+09 | 0.51 | 701.06 | 01-MAY-15:01 | 0.58 |
June | 0.303723E+09 | 0.53 | 701.06 | 01-JUN-08:62 | 0.58 |
July | 0.364692E+09 | 0.54 | 701.06 | 01-JUL-08:62 | 0.58 |
August | 0.388520E+09 | 0.54 | 701.06 | 01-AUG-08:61 | 0.58 |
September | 0.259298E+09 | 0.50 | 701.06 | 01-SEP-15:02 | 0.58 |
October | 0.152562E+09 | 0.46 | 701.06 | 01-OCT-08:62 | 0.58 |
November | 0.161961E+09 | 0.42 | 701.06 | 02-NOV-15:02 | 0.58 |
December | 0.218584E+09 | 0.43 | 701.06 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.280296E+10 | 0.48 | |||
Minimum of Months | 0.147816E+09 | 0.42 | 701.06 | 0.58 | |
Maximum of Months | 0.388520E+09 | 0.54 | 701.06 | 0.58 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.235761E+09 | 0.44 | 636.24 | 01-JAN-09:02 | 0.58 |
February | 0.168207E+09 | 0.41 | 636.24 | 01-FEB-09:02 | 0.58 |
March | 0.126109E+09 | 0.41 | 636.24 | 01-MAR-09:02 | 0.58 |
April | 0.130526E+09 | 0.42 | 636.24 | 01-APR-08:62 | 0.58 |
May | 0.159807E+09 | 0.42 | 636.24 | 01-MAY-15:01 | 0.58 |
June | 0.222567E+09 | 0.42 | 636.24 | 01-JUN-08:62 | 0.58 |
July | 0.252203E+09 | 0.41 | 636.24 | 01-JUL-08:62 | 0.58 |
August | 0.264433E+09 | 0.41 | 636.24 | 01-AUG-08:61 | 0.58 |
September | 0.144520E+09 | 0.38 | 636.24 | 01-SEP-08:52 | 0.58 |
October | 0.109553E+09 | 0.40 | 636.24 | 01-OCT-08:62 | 0.58 |
November | 0.163556E+09 | 0.41 | 636.24 | 04-NOV-15:02 | 0.58 |
December | 0.225796E+09 | 0.44 | 636.24 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.220304E+10 | 0.42 | |||
Minimum of Months | 0.109553E+09 | 0.38 | 636.24 | 0.58 | |
Maximum of Months | 0.264433E+09 | 0.44 | 636.24 | 0.58 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 75584013.26 | 0.45 | 204.87 | 01-JAN-09:02 | 0.58 |
February | 54835496.69 | 0.44 | 204.87 | 01-FEB-09:02 | 0.58 |
March | 49689401.37 | 0.43 | 204.87 | 01-MAR-16:02 | 0.58 |
April | 53820809.95 | 0.46 | 204.87 | 01-APR-15:01 | 0.58 |
May | 73100474.61 | 0.50 | 204.87 | 01-MAY-15:01 | 0.58 |
June | 76254567.50 | 0.51 | 204.87 | 01-JUN-08:62 | 0.58 |
July | 0.113469E+09 | 0.53 | 204.87 | 01-JUL-08:62 | 0.58 |
August | 0.102353E+09 | 0.52 | 204.87 | 01-AUG-08:61 | 0.58 |
September | 73437231.49 | 0.49 | 204.87 | 01-SEP-15:02 | 0.58 |
October | 45580335.59 | 0.45 | 204.87 | 01-OCT-08:62 | 0.58 |
November | 55208253.86 | 0.43 | 204.87 | 02-NOV-15:02 | 0.58 |
December | 72594595.92 | 0.46 | 204.87 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.845927E+09 | 0.47 | |||
Minimum of Months | 45580335.59 | 0.43 | 204.87 | 0.58 | |
Maximum of Months | 0.113469E+09 | 0.53 | 204.87 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 77126869.22 | 0.49 | 182.68 | 01-JAN-09:02 | 0.58 |
February | 56295778.32 | 0.44 | 182.68 | 01-FEB-09:02 | 0.58 |
March | 44686270.58 | 0.41 | 182.68 | 01-MAR-09:02 | 0.58 |
April | 38883317.93 | 0.41 | 182.68 | 01-APR-15:01 | 0.58 |
May | 45097122.34 | 0.41 | 182.68 | 01-MAY-15:01 | 0.58 |
June | 49920724.52 | 0.40 | 182.68 | 01-JUN-08:62 | 0.58 |
July | 75345774.11 | 0.40 | 182.68 | 01-JUL-08:62 | 0.58 |
August | 69222326.72 | 0.39 | 182.68 | 01-AUG-08:61 | 0.58 |
September | 35976771.24 | 0.37 | 182.68 | 01-SEP-08:52 | 0.58 |
October | 34948122.49 | 0.40 | 182.68 | 01-OCT-08:62 | 0.58 |
November | 55016909.23 | 0.43 | 182.68 | 02-NOV-08:62 | 0.58 |
December | 74114837.00 | 0.48 | 182.68 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.656635E+09 | 0.42 | |||
Minimum of Months | 34948122.49 | 0.37 | 182.68 | 0.58 | |
Maximum of Months | 77126869.22 | 0.49 | 182.68 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.293881E+09 | 0.43 | 1117.45 | 01-JAN-16:01 | 0.58 |
February | 0.263196E+09 | 0.46 | 1117.45 | 01-FEB-16:02 | 0.58 |
March | 0.286247E+09 | 0.47 | 1117.45 | 01-MAR-09:02 | 0.58 |
April | 0.324182E+09 | 0.50 | 1117.45 | 01-APR-15:01 | 0.58 |
May | 0.362962E+09 | 0.51 | 1117.45 | 01-MAY-15:01 | 0.58 |
June | 0.384504E+09 | 0.52 | 1117.45 | 01-JUN-08:62 | 0.58 |
July | 0.501207E+09 | 0.53 | 1117.45 | 01-JUL-08:62 | 0.58 |
August | 0.543829E+09 | 0.53 | 1117.45 | 01-AUG-08:61 | 0.58 |
September | 0.485566E+09 | 0.50 | 1117.45 | 01-SEP-15:02 | 0.58 |
October | 0.326693E+09 | 0.49 | 1117.45 | 01-OCT-08:62 | 0.58 |
November | 0.227864E+09 | 0.44 | 1117.45 | 02-NOV-15:02 | 0.58 |
December | 0.309455E+09 | 0.45 | 1117.45 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.430958E+10 | 0.49 | |||
Minimum of Months | 0.227864E+09 | 0.43 | 1117.45 | 0.58 | |
Maximum of Months | 0.543829E+09 | 0.53 | 1117.45 | 0.58 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.504102E+09 | 0.458229E+09 | 570.65 | 26-JAN-19:03 | 518.72 | 518.72 | 33.82 | 0.90 |
February | 0.426955E+09 | 0.388102E+09 | 523.86 | 15-FEB-16:01 | 476.19 | 476.19 | 31.18 | 0.78 |
March | 0.416783E+09 | 0.378856E+09 | 508.37 | 12-MAR-08:07 | 462.11 | 462.11 | 37.36 | 0.74 |
April | 0.352801E+09 | 0.320696E+09 | 484.62 | 08-APR-08:07 | 440.52 | 440.52 | 44.85 | 0.69 |
May | 0.303472E+09 | 0.275856E+09 | 470.72 | 28-MAY-08:04 | 427.88 | 427.88 | 35.52 | 0.66 |
June | 0.168727E+09 | 0.153373E+09 | 386.11 | 15-JUN-05:00 | 350.97 | 350.97 | 49.37 | 0.50 |
July | 63279637.04 | 57521190.07 | 230.55 | 07-JUL-05:00 | 209.57 | 209.57 | 29.05 | 0.27 |
August | 49171438.03 | 44696837.17 | 267.45 | 01-AUG-08:04 | 243.11 | 243.11 | 28.46 | 0.32 |
September | 0.177776E+09 | 0.161598E+09 | 436.16 | 28-SEP-08:05 | 396.47 | 396.47 | 33.70 | 0.59 |
October | 0.463083E+09 | 0.420943E+09 | 525.45 | 22-OCT-08:07 | 477.63 | 477.63 | 37.72 | 0.78 |
November | 0.453628E+09 | 0.412348E+09 | 559.68 | 25-NOV-19:03 | 508.75 | 508.75 | 35.20 | 0.87 |
December | 0.497415E+09 | 0.452150E+09 | 532.35 | 31-DEC-19:03 | 483.90 | 483.90 | 33.20 | 0.80 |
Annual Sum or Average | 0.387719E+10 | 0.352437E+10 | ||||||
Minimum of Months | 49171438.03 | 44696837.17 | 230.55 | 209.57 | 209.57 | 28.46 | 0.27 | |
Maximum of Months | 0.504102E+09 | 0.458229E+09 | 570.65 | 518.72 | 518.72 | 49.37 | 0.90 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1138688.62 | 1035067.95 | 32.95 | 11-JAN-16:03 | 29.95 | 29.95 | 8.40 | 2.45 |
February | 10322638.17 | 9383278.10 | 320.61 | 27-FEB-16:02 | 291.43 | 291.43 | 7.83 | 7.78 |
March | 33116081.79 | 30102518.35 | 456.66 | 18-MAR-15:02 | 415.11 | 415.11 | 7.73 | 9.14 |
April | 0.121498E+09 | 0.110442E+09 | 1126.64 | 26-APR-15:13 | 1024.11 | 1024.11 | 7.01 | 13.55 |
May | 0.195565E+09 | 0.177769E+09 | 1025.62 | 04-MAY-15:13 | 932.29 | 932.29 | 7.10 | 13.02 |
June | 0.323839E+09 | 0.294370E+09 | 1097.30 | 20-JUN-18:03 | 997.45 | 997.45 | 7.10 | 13.40 |
July | 0.501046E+09 | 0.455451E+09 | 1390.25 | 27-JUL-18:03 | 1263.74 | 1263.74 | 7.03 | 14.81 |
August | 0.623767E+09 | 0.567004E+09 | 1580.72 | 10-AUG-18:03 | 1436.88 | 1436.88 | 6.73 | 15.62 |
September | 0.287897E+09 | 0.261698E+09 | 1349.78 | 08-SEP-15:02 | 1226.95 | 1226.95 | 7.32 | 14.63 |
October | 75437953.54 | 68573099.77 | 651.63 | 08-OCT-15:03 | 592.33 | 592.33 | 7.82 | 10.70 |
November | 14520040.98 | 13198717.25 | 633.09 | 04-NOV-15:02 | 575.48 | 575.48 | 7.58 | 10.57 |
December | 3184845.67 | 2895024.71 | 53.47 | 02-DEC-09:02 | 48.60 | 48.60 | 8.40 | 3.20 |
Annual Sum or Average | 0.219133E+10 | 0.199192E+10 | ||||||
Minimum of Months | 1138688.62 | 1035067.95 | 32.95 | 29.95 | 29.95 | 6.73 | 2.45 | |
Maximum of Months | 0.623767E+09 | 0.567004E+09 | 1580.72 | 1436.88 | 1436.88 | 8.40 | 15.62 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.189248E+10 | 0.172027E+10 | 3560.96 | 01-JAN-09:02 | 3236.91 | 3236.91 | 8.57 | 25.21 |
February | 0.353514E+10 | 0.321344E+10 | 3560.96 | 01-FEB-06:03 | 3236.91 | 3236.91 | 8.41 | 25.21 |
March | 0.652020E+10 | 0.592686E+10 | 3560.96 | 01-MAR-00:03 | 3236.91 | 3236.91 | 8.43 | 25.21 |
April | 0.848381E+10 | 0.771179E+10 | 3560.96 | 01-APR-00:10 | 3236.91 | 3236.91 | 8.41 | 25.21 |
May | 0.947216E+10 | 0.861019E+10 | 3560.96 | 01-MAY-00:05 | 3236.91 | 3236.91 | 8.49 | 25.21 |
June | 0.923001E+10 | 0.839008E+10 | 3560.96 | 01-JUN-00:05 | 3236.91 | 3236.91 | 8.74 | 25.21 |
July | 0.953768E+10 | 0.866975E+10 | 3560.96 | 01-JUL-00:10 | 3236.91 | 3236.91 | 8.88 | 25.21 |
August | 0.953768E+10 | 0.866975E+10 | 3560.96 | 01-AUG-00:05 | 3236.91 | 3236.91 | 9.07 | 25.21 |
September | 0.913600E+10 | 0.830463E+10 | 3560.96 | 01-SEP-00:05 | 3236.91 | 3236.91 | 8.96 | 25.21 |
October | 0.830527E+10 | 0.754949E+10 | 3560.96 | 01-OCT-00:10 | 3236.91 | 3236.91 | 8.55 | 25.21 |
November | 0.421896E+10 | 0.383504E+10 | 3560.96 | 01-NOV-00:05 | 3236.91 | 3236.91 | 8.40 | 25.21 |
December | 0.220127E+10 | 0.200095E+10 | 3560.96 | 01-DEC-07:20 | 3236.91 | 3236.91 | 8.41 | 25.21 |
Annual Sum or Average | 0.820707E+11 | 0.746022E+11 | ||||||
Minimum of Months | 0.189248E+10 | 0.172027E+10 | 3560.96 | 3236.91 | 3236.91 | 8.40 | 25.21 | |
Maximum of Months | 0.953768E+10 | 0.866975E+10 | 3560.96 | 3236.91 | 3236.91 | 9.07 | 25.21 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 49.12 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 49.51 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 49.54 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.58 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 52.61 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 52.89 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 53.35 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 53.27 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 53.25 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 52.50 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 52.83 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 50.00 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 49.12 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 53.35 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 56.25 | 80.09 | 29009.19 | 173278.78 | 26-JAN-19:03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 58.37 | 79.90 | 30556.88 | 157562.30 | 15-FEB-16:01 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 57.92 | 80.09 | 31132.76 | 131915.19 | 07-MAR-09:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.33 | 79.75 | 30331.21 | 120914.30 | 06-APR-08:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 31.96 | 79.40 | 26777.60 | 122012.91 | 28-MAY-08:04 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 24.88 | 79.40 | 15756.00 | 88682.43 | 01-JUN-04:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.03 | 27.03 | 5791.37 | 57158.19 | 19-JUL-05:00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.21 | 28.21 | 4468.43 | 67955.28 | 01-AUG-08:04 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 30.41 | 30.41 | 16332.70 | 113298.88 | 28-SEP-08:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.43 | 79.40 | 39090.67 | 137740.61 | 22-OCT-08:07 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 37.98 | 79.53 | 32465.16 | 163277.69 | 26-NOV-19:03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 56.03 | 80.34 | 30129.20 | 155543.95 | 31-DEC-19:03 |
Annual Sum or Average | 0.00 | 24275.40 | ||||||
Minimum of Months | 0.00 | 0.00 | 24.88 | 27.03 | 4468.43 | 57158.19 | ||
Maximum of Months | 0.00 | 0.00 | 58.37 | 80.34 | 39090.67 | 173278.78 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1188.64 | 29384.37 | 11-JAN-16:03 | 8.65 | 8.37 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 5922.96 | 214877.52 | 27-FEB-16:02 | 9.84 | 7.81 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 12967.00 | 247171.88 | 18-MAR-15:03 | 10.03 | 7.69 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 33098.14 | 372869.95 | 27-APR-18:03 | 10.40 | 6.87 | 0.00 | 0.00 | 01-APR-00:10 |
May | 51255.71 | 336755.00 | 04-MAY-15:03 | 10.25 | 7.06 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 75612.65 | 379905.14 | 28-JUN-18:03 | 10.49 | 6.90 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 110617.08 | 442591.33 | 31-JUL-18:03 | 10.93 | 6.74 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 130423.86 | 472578.45 | 10-AUG-18:03 | 11.17 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 69121.08 | 383496.72 | 14-SEP-15:03 | 10.74 | 7.11 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 24271.71 | 292575.86 | 04-OCT-15:03 | 10.24 | 7.47 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 6742.60 | 288652.55 | 04-NOV-15:03 | 10.30 | 7.57 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 2129.55 | 45866.68 | 05-DEC-12:30 | 8.80 | 8.37 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 43894.62 | 0.00 | ||||||
Minimum of Months | 1188.64 | 29384.37 | 8.65 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 130423.86 | 472578.45 | 11.17 | 8.37 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 49.12 | 59.99 | 26493.51 | 55715.73 | 31-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 49.51 | 59.97 | 26675.55 | 55800.57 | 10-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 49.54 | 60.00 | 26393.32 | 55588.51 | 01-MAR-07:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.58 | 59.96 | 25659.47 | 54355.55 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 52.61 | 59.99 | 24717.24 | 52623.09 | 01-MAY-06:50 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 52.89 | 59.97 | 23806.46 | 50505.70 | 01-JUN-06:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 53.35 | 59.99 | 23138.14 | 48719.86 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 53.27 | 59.99 | 22961.99 | 47994.99 | 31-AUG-06:30 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 53.25 | 59.99 | 23258.58 | 49075.37 | 29-SEP-06:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 52.50 | 59.99 | 23975.39 | 51028.38 | 31-OCT-06:50 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 52.83 | 59.99 | 24925.22 | 52980.43 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 50.00 | 59.97 | 25844.25 | 54740.19 | 29-DEC-07:40 |
Annual Sum or Average | 0.00 | 24809.99 | ||||||
Minimum of Months | 0.00 | 0.00 | 49.12 | 59.96 | 22961.99 | 47994.99 | ||
Maximum of Months | 0.00 | 0.00 | 53.35 | 60.00 | 26675.55 | 55800.57 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.457766E+11 | 0.00 | 0.00 | 0.345523E+11 | 0.00 | 0.00 |
February | 0.539118E+11 | 0.00 | 0.176666E+10 | 0.315696E+11 | 0.00 | 0.00 |
March | 0.749640E+11 | 0.00 | 0.394506E+10 | 0.356828E+11 | 0.00 | 0.00 |
April | 0.760465E+11 | 0.00 | 0.281106E+11 | 0.351511E+11 | 0.00 | 0.00 |
May | 0.714309E+11 | 0.00 | 0.547785E+11 | 0.370901E+11 | 0.00 | 0.00 |
June | 0.409981E+11 | 0.00 | 0.975925E+11 | 0.365436E+11 | 0.00 | 0.00 |
July | 0.155825E+11 | 0.00 | 0.165184E+12 | 0.382486E+11 | 0.00 | 0.00 |
August | 0.119915E+11 | 0.00 | 0.207650E+12 | 0.385596E+11 | 0.00 | 0.00 |
September | 0.422252E+11 | 0.00 | 0.800163E+11 | 0.361827E+11 | 0.00 | 0.00 |
October | 0.100837E+12 | 0.00 | 0.149968E+11 | 0.360895E+11 | 0.00 | 0.00 |
November | 0.679034E+11 | 0.00 | 0.339029E+10 | 0.340888E+11 | 0.00 | 0.00 |
December | 0.517392E+11 | 0.00 | 0.00 | 0.345966E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.653407E+12 | 0.00 | 0.657431E+12 | 0.428355E+12 | 0.00 | 0.00 |
Minimum of Months | 0.119915E+11 | 0.00 | 0.00 | 0.315696E+11 | 0.00 | 0.00 |
Maximum of Months | 0.100837E+12 | 0.00 | 0.207650E+12 | 0.385596E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.106765E+09 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
February | 93373363.91 | 0.00 | 0.108440E+09 | 0.244774E+10 | 0.00 | 0.00 |
March | 15235.68 | 0.00 | 0.232539E+09 | 0.271000E+10 | 0.00 | 0.00 |
April | 3889.58 | 0.00 | 0.179866E+10 | 0.262258E+10 | 0.00 | 0.00 |
May | 10242.39 | 0.00 | 0.358834E+10 | 0.271000E+10 | 0.00 | 0.00 |
June | 20863.51 | 0.00 | 0.631575E+10 | 0.262258E+10 | 0.00 | 0.00 |
July | 23469.91 | 0.00 | 0.118421E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 30023.96 | 0.00 | 0.155328E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 16784.32 | 0.00 | 0.552409E+10 | 0.262258E+10 | 0.00 | 0.00 |
October | 6267.19 | 0.00 | 0.905033E+09 | 0.271000E+10 | 0.00 | 0.00 |
November | 52295.84 | 0.00 | 0.222488E+09 | 0.262258E+10 | 0.00 | 0.00 |
December | 13572972.26 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.213891E+09 | 0.00 | 0.460702E+11 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 3889.58 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106765E+09 | 0.00 | 0.155328E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.345523E+11 | 0.00 | 0.457766E+11 | 0.478539E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.315696E+11 | 0.176666E+10 | 0.539118E+11 | 0.351225E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.356828E+11 | 0.394506E+10 | 0.749640E+11 | 0.242078E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.351511E+11 | 0.281106E+11 | 0.760465E+11 | 0.127945E+12 | 0.289002E+09 | 0.00 | 0.00 | 0.00 |
May | 0.370901E+11 | 0.547785E+11 | 0.714309E+11 | 0.532595E+11 | 2109050.17 | 0.00 | 0.00 | 0.00 |
June | 0.365436E+11 | 0.975925E+11 | 0.409981E+11 | 0.368859E+10 | 32826019.22 | 0.00 | 0.00 | 0.00 |
July | 0.382486E+11 | 0.165184E+12 | 0.155825E+11 | 0.171863E+10 | 0.342520E+10 | 0.00 | 0.00 | 0.00 |
August | 0.385596E+11 | 0.207650E+12 | 0.119915E+11 | 0.280517E+10 | 0.907795E+10 | 0.00 | 0.00 | 0.00 |
September | 0.361827E+11 | 0.800163E+11 | 0.422252E+11 | 0.474169E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.360895E+11 | 0.149968E+11 | 0.100837E+12 | 0.575822E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.340888E+11 | 0.339029E+10 | 0.679034E+11 | 0.256993E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.345966E+11 | 0.00 | 0.517392E+11 | 0.427297E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.428355E+12 | 0.657431E+12 | 0.653407E+12 | 0.200787E+13 | 0.128271E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.315696E+11 | 0.00 | 0.119915E+11 | 0.171863E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.385596E+11 | 0.207650E+12 | 0.100837E+12 | 0.478539E+12 | 0.907795E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 0.00 | 0.106765E+09 | 0.440264E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.108440E+09 | 93373363.91 | 0.352418E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.232539E+09 | 15235.68 | 0.293423E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.179866E+10 | 3889.58 | 0.202074E+11 | 51243075.12 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.358834E+10 | 10242.39 | 0.132401E+11 | 41714883.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.631575E+10 | 20863.51 | 0.496109E+10 | 53047438.95 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.118421E+11 | 23469.91 | 0.179940E+10 | 0.736848E+09 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.155328E+11 | 30023.96 | 0.124361E+10 | 0.169070E+10 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.552409E+10 | 16784.32 | 0.498505E+10 | 0.100127E+09 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.905033E+09 | 6267.19 | 0.165874E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.222488E+09 | 52295.84 | 0.285569E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.00 | 13572972.26 | 0.407892E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.460702E+11 | 0.213891E+09 | 0.240981E+12 | 0.267368E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.00 | 3889.58 | 0.124361E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.155328E+11 | 0.106765E+09 | 0.440264E+11 | 0.169070E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.345523E+11 | 0.457766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.315696E+11 | 0.539118E+11 | 0.176666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.356828E+11 | 0.749640E+11 | 0.394506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.351511E+11 | 0.760465E+11 | 0.281106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.370901E+11 | 0.714309E+11 | 0.547785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.365436E+11 | 0.409981E+11 | 0.975925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.382486E+11 | 0.155825E+11 | 0.165184E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.385596E+11 | 0.119915E+11 | 0.207650E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.361827E+11 | 0.422252E+11 | 0.800163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.360895E+11 | 0.100837E+12 | 0.149968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.340888E+11 | 0.679034E+11 | 0.339029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.345966E+11 | 0.517392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.428355E+12 | 0.653407E+12 | 0.657431E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.315696E+11 | 0.119915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.385596E+11 | 0.100837E+12 | 0.207650E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.106765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 93373363.91 | 0.108440E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 15235.68 | 0.232539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 3889.58 | 0.179866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 10242.39 | 0.358834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 20863.51 | 0.631575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 23469.91 | 0.118421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 30023.96 | 0.155328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 16784.32 | 0.552409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 6267.19 | 0.905033E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 52295.84 | 0.222488E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 13572972.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.213891E+09 | 0.460702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 3889.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.106765E+09 | 0.155328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.401358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 |
February | 0.383290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 |
March | 0.449845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 |
April | 0.429038E+11 | 0.00 | 0.00 | 0.00 | 7716345.38 | 0.00 | 0.00 | 0.00 | 0.85 |
May | 0.425008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 |
June | 0.357761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 |
July | 0.302504E+11 | 0.00 | 0.00 | 0.00 | 0.118828E+09 | 0.00 | 0.00 | 0.00 | 0.85 |
August | 0.269693E+11 | 0.00 | 0.00 | 0.00 | 0.369549E+09 | 0.00 | 0.00 | 0.00 | 0.86 |
September | 0.344418E+11 | 0.00 | 0.00 | 921942.08 | 137574.64 | 0.00 | 0.311891E+10 | 0.00 | 0.86 |
October | 0.383397E+11 | 0.00 | 0.00 | 4361412.94 | 0.00 | 0.00 | 0.935038E+10 | 0.00 | 0.86 |
November | 0.331670E+11 | 0.00 | 0.00 | 5537101.35 | 0.00 | 0.00 | 0.922403E+10 | 0.00 | 0.85 |
December | 0.384110E+11 | 0.00 | 0.00 | 784069.05 | 0.00 | 0.00 | 0.282340E+10 | 0.00 | 0.85 |
Annual Sum or Average | 0.446209E+12 | 0.00 | 0.00 | 11604525.43 | 0.496230E+09 | 0.00 | 0.245167E+11 | 0.00 | 0.85 |
Minimum of Months | 0.269693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 |
Maximum of Months | 0.449845E+11 | 0.00 | 0.00 | 5537101.35 | 0.369549E+09 | 0.00 | 0.935038E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.669863E+10 | 0.00 | 0.00 | 28772.05 | 0.00 | 0.164886E+10 | 47984033.13 | 0.00 | 3.21 |
February | 0.719707E+10 | 0.00 | 0.00 | 258134.97 | 0.00 | 0.577472E+09 | 0.247307E+09 | 0.00 | 3.24 |
March | 0.896073E+10 | 0.00 | 0.00 | 478791.67 | 0.00 | 7345533.31 | 0.466206E+09 | 0.00 | 3.23 |
April | 0.873080E+10 | 1900822.55 | 0.00 | 360043.05 | 0.00 | 0.00 | 0.243978E+09 | 0.00 | 3.23 |
May | 0.867808E+10 | 0.00 | 0.00 | 396276.57 | 0.00 | 0.00 | 0.212425E+09 | 0.00 | 3.23 |
June | 0.739400E+10 | 0.00 | 0.00 | 131285.70 | 0.00 | 0.00 | 89411521.50 | 0.00 | 3.23 |
July | 0.615231E+10 | 16010221.07 | 0.00 | 459956.92 | 9179985.55 | 0.00 | 0.174921E+09 | 0.00 | 3.23 |
August | 0.545654E+10 | 72106445.09 | 0.00 | 753629.38 | 12155755.61 | 0.00 | 0.185801E+09 | 0.00 | 3.28 |
September | 0.733066E+10 | 42570.32 | 0.00 | 2026947.48 | 0.00 | 0.00 | 0.559621E+09 | 0.00 | 3.29 |
October | 0.943417E+10 | 0.00 | 0.00 | 866858.65 | 0.00 | 0.00 | 0.573107E+09 | 0.00 | 3.25 |
November | 0.852635E+10 | 0.00 | 0.00 | 156587.94 | 0.00 | 0.226820E+09 | 0.116736E+09 | 0.00 | 3.22 |
December | 0.689512E+10 | 0.00 | 0.00 | 85511.37 | 0.00 | 0.155207E+10 | 0.178432E+09 | 0.00 | 3.21 |
Annual Sum or Average | 0.914545E+11 | 90060059.03 | 0.00 | 6002795.75 | 21335741.17 | 0.401257E+10 | 0.309593E+10 | 0.00 | 3.24 |
Minimum of Months | 0.545654E+10 | 0.00 | 0.00 | 28772.05 | 0.00 | 0.00 | 47984033.13 | 0.00 | 3.21 |
Maximum of Months | 0.943417E+10 | 72106445.09 | 0.00 | 2026947.48 | 12155755.61 | 0.164886E+10 | 0.573107E+09 | 0.00 | 3.29 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.421370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 |
February | 0.400936E+10 | 0.00 | 0.00 | 1858.18 | 0.00 | 0.00 | 14649153.87 | 0.00 | 1.41 |
March | 0.463792E+10 | 0.00 | 0.00 | 15798.24 | 0.00 | 0.00 | 84800412.96 | 0.00 | 1.40 |
April | 0.417360E+10 | 0.00 | 0.00 | 159971.15 | 810108.31 | 0.00 | 0.331992E+09 | 0.00 | 1.40 |
May | 0.375460E+10 | 0.00 | 0.00 | 397450.49 | 0.00 | 0.00 | 0.709510E+09 | 0.00 | 1.41 |
June | 0.292960E+10 | 0.00 | 0.00 | 601113.08 | 0.00 | 0.00 | 0.831036E+09 | 0.00 | 1.41 |
July | 0.187775E+10 | 1120403.99 | 0.00 | 1543300.96 | 11355807.41 | 0.00 | 0.131849E+10 | 0.00 | 1.42 |
August | 0.158399E+10 | 8421027.34 | 0.00 | 1817945.93 | 30443757.75 | 0.00 | 0.127515E+10 | 0.00 | 1.43 |
September | 0.290654E+10 | 0.00 | 0.00 | 905176.42 | 14443.41 | 0.00 | 0.105556E+10 | 0.00 | 1.42 |
October | 0.462421E+10 | 0.00 | 0.00 | 167894.80 | 0.00 | 0.00 | 0.384529E+09 | 0.00 | 1.41 |
November | 0.444248E+10 | 0.00 | 0.00 | 529.89 | 0.00 | 0.00 | 8132948.72 | 0.00 | 1.40 |
December | 0.432912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 |
Annual Sum or Average | 0.434829E+11 | 9541431.32 | 0.00 | 5611039.15 | 42624116.89 | 0.00 | 0.601384E+10 | 0.00 | 1.41 |
Minimum of Months | 0.158399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 |
Maximum of Months | 0.463792E+10 | 8421027.34 | 0.00 | 1817945.93 | 30443757.75 | 0.00 | 0.131849E+10 | 0.00 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.317445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29695067.37 | 0.00 | 0.00 | 0.50 |
February | 0.305990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
March | 0.359122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
April | 0.342511E+10 | 0.00 | 0.00 | 0.00 | 616014.88 | 0.00 | 0.00 | 0.00 | 0.50 |
May | 0.339294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
June | 0.285609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
July | 0.238188E+10 | 0.00 | 0.00 | 27407.49 | 9486292.50 | 0.00 | 33056047.09 | 0.00 | 0.51 |
August | 0.208823E+10 | 225145.52 | 0.00 | 108457.32 | 29276861.97 | 0.00 | 64921743.27 | 0.00 | 0.51 |
September | 0.299757E+10 | 0.00 | 0.00 | 55.81 | 10982.92 | 0.00 | 1065050.64 | 0.00 | 0.51 |
October | 0.380756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
November | 0.338430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
December | 0.327513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16781907.68 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.374344E+11 | 225145.52 | 0.00 | 135920.62 | 39390152.27 | 46476975.06 | 99042841.00 | 0.00 | 0.50 |
Minimum of Months | 0.208823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.380756E+10 | 225145.52 | 0.00 | 108457.32 | 29276861.97 | 29695067.37 | 64921743.27 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.150360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219745E+09 | 0.00 | 0.00 | 0.47 |
February | 0.151322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132540E+09 | 0.00 | 0.00 | 0.47 |
March | 0.193153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
April | 0.184219E+10 | 0.00 | 0.00 | 0.00 | 331322.40 | 0.00 | 0.00 | 0.00 | 0.47 |
May | 0.182489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.153614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.129888E+10 | 0.00 | 0.00 | 0.00 | 5102183.83 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 0.115762E+10 | 0.00 | 0.00 | 92.46 | 15867596.91 | 0.00 | 380575.69 | 0.00 | 0.47 |
September | 0.161281E+10 | 0.00 | 0.00 | 0.00 | 5907.14 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 0.204789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
November | 0.182024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
December | 0.165557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114974E+09 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.197446E+11 | 0.00 | 0.00 | 92.46 | 21307010.29 | 0.467259E+09 | 380575.69 | 0.00 | 0.47 |
Minimum of Months | 0.115762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.204789E+10 | 0.00 | 0.00 | 92.46 | 15867596.91 | 0.219745E+09 | 380575.69 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.447150E+09 | 0.00 | 0.00 | 90301758.26 | 0.00 | 0.00 | 0.727351E+11 | 0.00 | 24.09 |
February | 0.288676E+09 | 0.00 | 0.00 | 80929831.20 | 0.00 | 0.00 | 0.696535E+11 | 0.00 | 24.27 |
March | 0.203353E+09 | 0.00 | 0.00 | 90531733.45 | 0.00 | 0.00 | 0.820529E+11 | 0.00 | 24.22 |
April | 0.225191E+09 | 12385848.26 | 0.00 | 95438011.58 | 0.00 | 0.00 | 0.780358E+11 | 0.00 | 24.16 |
May | 0.330669E+09 | 0.00 | 0.00 | 0.107195E+09 | 0.00 | 0.00 | 0.772834E+11 | 0.00 | 24.20 |
June | 0.251691E+09 | 0.00 | 0.00 | 0.110602E+09 | 0.00 | 0.00 | 0.645030E+11 | 0.00 | 24.22 |
July | 0.187468E+09 | 0.200258E+09 | 0.00 | 0.117079E+09 | 3043918.31 | 0.00 | 0.541177E+11 | 0.00 | 24.11 |
August | 0.100761E+09 | 0.613934E+09 | 0.00 | 0.113714E+09 | 4986930.73 | 0.00 | 0.484937E+11 | 0.00 | 24.29 |
September | 0.287087E+09 | 220827.15 | 0.00 | 0.105180E+09 | 0.00 | 0.00 | 0.678596E+11 | 0.00 | 24.22 |
October | 0.250133E+09 | 0.00 | 0.00 | 93138834.34 | 0.00 | 0.00 | 0.869473E+11 | 0.00 | 24.27 |
November | 0.348362E+09 | 0.00 | 0.00 | 86208045.63 | 0.00 | 0.00 | 0.769317E+11 | 0.00 | 24.16 |
December | 0.448854E+09 | 0.00 | 0.00 | 89694959.42 | 0.00 | 0.00 | 0.744303E+11 | 0.00 | 24.04 |
Annual Sum or Average | 0.336940E+10 | 0.826800E+09 | 0.00 | 0.118001E+10 | 8030849.05 | 0.00 | 0.853044E+12 | 0.00 | 24.19 |
Minimum of Months | 0.100761E+09 | 0.00 | 0.00 | 80929831.20 | 0.00 | 0.00 | 0.484937E+11 | 0.00 | 24.04 |
Maximum of Months | 0.448854E+09 | 0.613934E+09 | 0.00 | 0.117079E+09 | 4986930.73 | 0.00 | 0.869473E+11 | 0.00 | 24.29 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.316833E+11 | 0.00 | 0.00 | 441519.04 | 0.00 | 0.00 | 0.240463E+10 | 0.00 | 4.65 |
February | 0.248975E+11 | 0.00 | 0.00 | 2579564.72 | 0.00 | 0.00 | 0.767039E+10 | 0.00 | 4.68 |
March | 0.241019E+11 | 0.00 | 0.00 | 5177685.17 | 0.00 | 0.00 | 0.141839E+11 | 0.00 | 4.67 |
April | 0.207796E+11 | 7062574.17 | 0.00 | 6383671.19 | 0.00 | 0.00 | 0.156548E+11 | 0.00 | 4.67 |
May | 0.180984E+11 | 0.00 | 0.00 | 8007096.87 | 0.00 | 0.00 | 0.179920E+11 | 0.00 | 4.67 |
June | 0.128488E+11 | 0.00 | 0.00 | 8307634.27 | 0.00 | 0.00 | 0.175284E+11 | 0.00 | 4.68 |
July | 0.902916E+10 | 79670726.39 | 0.00 | 12829099.35 | 21334762.98 | 0.00 | 0.166505E+11 | 0.00 | 4.68 |
August | 0.770365E+10 | 0.301539E+09 | 0.00 | 16471948.16 | 23994912.70 | 0.00 | 0.151962E+11 | 0.00 | 4.72 |
September | 0.128291E+11 | 148863.33 | 0.00 | 18577363.79 | 0.00 | 0.00 | 0.191466E+11 | 0.00 | 4.74 |
October | 0.214177E+11 | 0.00 | 0.00 | 9131698.55 | 0.00 | 0.00 | 0.191730E+11 | 0.00 | 4.70 |
November | 0.281552E+11 | 0.00 | 0.00 | 1937197.85 | 0.00 | 0.00 | 0.785870E+10 | 0.00 | 4.66 |
December | 0.313812E+11 | 0.00 | 0.00 | 1011504.43 | 0.00 | 0.00 | 0.364219E+10 | 0.00 | 4.64 |
Annual Sum or Average | 0.242926E+12 | 0.388421E+09 | 0.00 | 90855983.38 | 45329675.67 | 0.00 | 0.157101E+12 | 0.00 | 4.68 |
Minimum of Months | 0.770365E+10 | 0.00 | 0.00 | 441519.04 | 0.00 | 0.00 | 0.240463E+10 | 0.00 | 4.64 |
Maximum of Months | 0.316833E+11 | 0.301539E+09 | 0.00 | 18577363.79 | 23994912.70 | 0.00 | 0.191730E+11 | 0.00 | 4.74 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.914423E+11 | 0.00 | 0.00 | 715163.96 | 0.00 | 0.00 | 0.440460E+10 | 0.00 | 1.89 |
February | 0.791272E+11 | 0.00 | 0.00 | 3848744.56 | 0.00 | 0.00 | 0.124018E+11 | 0.00 | 1.90 |
March | 0.775838E+11 | 0.00 | 0.00 | 10344006.69 | 0.00 | 0.00 | 0.298429E+11 | 0.00 | 1.90 |
April | 0.623292E+11 | 10789464.28 | 0.00 | 19739538.04 | 7637796.75 | 0.00 | 0.402301E+11 | 0.00 | 1.90 |
May | 0.490973E+11 | 0.00 | 0.00 | 34535132.01 | 0.00 | 0.00 | 0.526262E+11 | 0.00 | 1.91 |
June | 0.329952E+11 | 0.00 | 0.00 | 46845703.43 | 0.00 | 0.00 | 0.528372E+11 | 0.00 | 1.91 |
July | 0.214668E+11 | 0.134272E+09 | 0.00 | 66493429.52 | 0.149498E+09 | 0.00 | 0.517619E+11 | 0.00 | 1.93 |
August | 0.179801E+11 | 0.558646E+09 | 0.00 | 72822741.42 | 0.324479E+09 | 0.00 | 0.478008E+11 | 0.00 | 1.95 |
September | 0.335335E+11 | 328539.44 | 0.00 | 51787585.21 | 0.00 | 0.00 | 0.570978E+11 | 0.00 | 1.93 |
October | 0.637981E+11 | 0.00 | 0.00 | 23934328.72 | 0.00 | 0.00 | 0.503250E+11 | 0.00 | 1.91 |
November | 0.819393E+11 | 0.00 | 0.00 | 4983979.41 | 0.00 | 0.00 | 0.192924E+11 | 0.00 | 1.89 |
December | 0.916422E+11 | 0.00 | 0.00 | 1504797.60 | 0.00 | 0.00 | 0.682933E+10 | 0.00 | 1.89 |
Annual Sum or Average | 0.702935E+12 | 0.704035E+09 | 0.00 | 0.337555E+09 | 0.481615E+09 | 0.00 | 0.425450E+12 | 0.00 | 1.91 |
Minimum of Months | 0.179801E+11 | 0.00 | 0.00 | 715163.96 | 0.00 | 0.00 | 0.440460E+10 | 0.00 | 1.89 |
Maximum of Months | 0.916422E+11 | 0.558646E+09 | 0.00 | 72822741.42 | 0.324479E+09 | 0.00 | 0.570978E+11 | 0.00 | 1.95 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 73330475.51 | 0.00 | 0.00 | 205657.86 | 0.00 | 0.146172E+10 | 11967958.29 | 0.00 | 0.35 |
February | 70702566.02 | 0.00 | 0.00 | 1016511.89 | 0.00 | 0.110107E+10 | 0.224845E+09 | 0.00 | 0.36 |
March | 82601731.66 | 0.00 | 0.00 | 3098426.92 | 0.00 | 0.922304E+09 | 0.540450E+09 | 0.00 | 0.36 |
April | 62784080.93 | 594482.88 | 0.00 | 7212808.69 | 0.00 | 0.402292E+09 | 0.950374E+09 | 0.00 | 0.36 |
May | 28801068.31 | 1128374.64 | 0.00 | 13685452.04 | 0.00 | 88838146.58 | 0.124370E+10 | 0.00 | 0.36 |
June | 19445731.94 | 469118.55 | 0.00 | 14748908.48 | 0.00 | 3337733.12 | 0.114299E+10 | 0.00 | 0.36 |
July | 1968496.26 | 14239227.23 | 0.00 | 17257399.74 | 0.00 | 2071819.47 | 0.946033E+09 | 0.00 | 0.35 |
August | 3863613.98 | 34443340.87 | 10215.45 | 13173708.09 | 0.00 | 2058343.45 | 0.717007E+09 | 572.94 | 0.36 |
September | 29105569.43 | 2908730.88 | 0.00 | 12906546.20 | 0.00 | 39214964.83 | 0.104892E+10 | 0.00 | 0.36 |
October | 58080621.65 | 0.00 | 0.00 | 5008418.97 | 0.00 | 0.566299E+09 | 0.867460E+09 | 0.00 | 0.36 |
November | 70932642.43 | 0.00 | 0.00 | 790372.77 | 0.00 | 0.122610E+10 | 0.178536E+09 | 0.00 | 0.35 |
December | 68536400.40 | 0.00 | 0.00 | 340571.83 | 0.00 | 0.140189E+10 | 72841597.71 | 0.00 | 0.35 |
Annual Sum or Average | 0.570153E+09 | 53783275.06 | 10215.45 | 89444783.48 | 0.00 | 0.721720E+10 | 0.794513E+10 | 572.94 | 0.36 |
Minimum of Months | 1968496.26 | 0.00 | 0.00 | 205657.86 | 0.00 | 2058343.45 | 11967958.29 | 0.00 | 0.35 |
Maximum of Months | 82601731.66 | 34443340.87 | 10215.45 | 17257399.74 | 0.00 | 0.146172E+10 | 0.124370E+10 | 572.94 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 65636033.68 | 0.00 | 0.00 | 92482.03 | 0.00 | 0.147511E+10 | 6209891.29 | 0.00 | 0.35 |
February | 78775075.59 | 0.00 | 0.00 | 390660.46 | 0.00 | 0.120616E+10 | 0.112144E+09 | 0.00 | 0.36 |
March | 0.107999E+09 | 0.00 | 0.00 | 1518622.60 | 0.00 | 0.111953E+10 | 0.319227E+09 | 0.00 | 0.36 |
April | 0.136898E+09 | 594413.23 | 0.00 | 4820124.19 | 0.00 | 0.543506E+09 | 0.737273E+09 | 0.00 | 0.36 |
May | 0.193826E+09 | 871655.48 | 0.00 | 10434826.43 | 256586.96 | 0.104568E+09 | 0.106604E+10 | 0.00 | 0.36 |
June | 0.225441E+09 | 428388.19 | 0.00 | 11437536.89 | 40675.39 | 3535244.56 | 0.939971E+09 | 0.00 | 0.36 |
July | 0.210478E+09 | 12112904.99 | 0.00 | 13784467.10 | 2124320.06 | 1860798.57 | 0.741094E+09 | 333.85 | 0.36 |
August | 0.183946E+09 | 32038009.26 | 13817.27 | 8952592.66 | 2397873.60 | 1964455.41 | 0.541153E+09 | 392.32 | 0.36 |
September | 0.218795E+09 | 2126531.04 | 0.00 | 8029332.61 | 781859.04 | 48457005.93 | 0.854730E+09 | 0.00 | 0.36 |
October | 0.136710E+09 | 0.00 | 0.00 | 2418942.61 | 0.00 | 0.762882E+09 | 0.594662E+09 | 0.00 | 0.36 |
November | 80609788.12 | 0.00 | 0.00 | 308396.29 | 0.00 | 0.129694E+10 | 98326466.81 | 0.00 | 0.35 |
December | 62644280.51 | 0.00 | 0.00 | 103142.32 | 0.00 | 0.147369E+10 | 6996626.58 | 0.00 | 0.35 |
Annual Sum or Average | 0.170176E+10 | 48171902.18 | 13817.27 | 62291126.20 | 5601315.05 | 0.803819E+10 | 0.601783E+10 | 726.17 | 0.36 |
Minimum of Months | 62644280.51 | 0.00 | 0.00 | 92482.03 | 0.00 | 1860798.57 | 6209891.29 | 0.00 | 0.35 |
Maximum of Months | 0.225441E+09 | 32038009.26 | 13817.27 | 13784467.10 | 2397873.60 | 0.147511E+10 | 0.106604E+10 | 392.32 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
February | 0.863856E+09 | 0.00 | 0.00 | 903675.75 | 0.00 | 0.00 | 0.407083E+09 | 0.00 | 0.02 |
March | 0.658823E+09 | 0.00 | 0.00 | 2297521.32 | 0.00 | 0.00 | 0.106540E+10 | 0.00 | 0.02 |
April | 0.222459E+09 | 4580594.27 | 0.00 | 2789681.48 | 0.00 | 0.00 | 0.129968E+10 | 0.00 | 0.02 |
May | 0.163918E+09 | 273938.27 | 0.00 | 3367782.28 | 0.00 | 0.00 | 0.125924E+10 | 0.00 | 0.02 |
June | 7579020.29 | 0.00 | 0.00 | 3327097.02 | 0.00 | 0.00 | 0.120950E+10 | 0.00 | 0.02 |
July | 0.00 | 29598768.46 | 0.00 | 3819456.65 | 0.00 | 0.00 | 0.613389E+09 | 0.00 | 0.02 |
August | 0.00 | 97282879.11 | 0.00 | 2331969.08 | 0.00 | 0.00 | 0.455876E+09 | 0.00 | 0.02 |
September | 0.242438E+09 | 14159983.38 | 0.00 | 3814645.02 | 0.00 | 0.00 | 0.740542E+09 | 0.00 | 0.02 |
October | 0.562449E+09 | 0.00 | 0.00 | 3082184.21 | 0.00 | 0.00 | 0.108427E+10 | 0.00 | 0.02 |
November | 0.107596E+10 | 0.00 | 0.00 | 597079.87 | 0.00 | 0.00 | 0.300851E+09 | 0.00 | 0.02 |
December | 0.978099E+09 | 0.00 | 0.00 | 276309.16 | 0.00 | 0.00 | 0.203807E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.578697E+10 | 0.145896E+09 | 0.00 | 26607401.83 | 0.00 | 0.00 | 0.863963E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.107596E+10 | 97282879.11 | 0.00 | 3819456.65 | 0.00 | 0.00 | 0.129968E+10 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.102595E+10 | 0.00 | 0.00 | 10851600.95 | 0.00 | 0.854365E+10 | 0.114043E+11 | 0.00 | 0.40 |
February | 0.106854E+10 | 0.00 | 0.00 | 18460385.73 | 0.00 | 0.608078E+10 | 0.117880E+11 | 0.00 | 0.41 |
March | 0.146494E+10 | 0.00 | 0.00 | 44470204.53 | 0.00 | 0.248647E+09 | 0.192433E+11 | 0.00 | 0.40 |
April | 0.187932E+10 | 7795219.14 | 0.00 | 85198510.72 | 267639.67 | 92144782.24 | 0.172386E+11 | 0.00 | 0.40 |
May | 0.286520E+10 | 9699562.50 | 103814.18 | 0.140522E+09 | 5496748.02 | 28311776.98 | 0.156152E+11 | 3807.13 | 0.40 |
June | 0.342069E+10 | 5810828.86 | 0.00 | 0.161796E+09 | 551737.27 | 6483831.20 | 0.124222E+11 | 0.00 | 0.40 |
July | 0.324706E+10 | 0.148810E+09 | 192714.99 | 0.172100E+09 | 44120520.75 | 3595787.53 | 0.969696E+10 | 1032.00 | 0.40 |
August | 0.265343E+10 | 0.373234E+09 | 606508.93 | 0.115224E+09 | 93448040.75 | 3578973.45 | 0.721138E+10 | 6273.62 | 0.40 |
September | 0.305431E+10 | 14583432.67 | 0.00 | 0.109139E+09 | 24867134.04 | 24649306.43 | 0.121398E+11 | 0.00 | 0.40 |
October | 0.184854E+10 | 0.00 | 0.00 | 60106447.33 | 0.00 | 0.183588E+09 | 0.182092E+11 | 0.00 | 0.40 |
November | 0.112205E+10 | 0.00 | 0.00 | 27817156.00 | 0.00 | 0.230654E+10 | 0.165672E+11 | 0.00 | 0.40 |
December | 0.104877E+10 | 0.00 | 0.00 | 11035049.85 | 0.00 | 0.824024E+10 | 0.116356E+11 | 0.00 | 0.40 |
Annual Sum or Average | 0.246988E+11 | 0.559933E+09 | 903038.10 | 0.956720E+09 | 0.168752E+09 | 0.257622E+11 | 0.163172E+12 | 11112.75 | 0.40 |
Minimum of Months | 0.102595E+10 | 0.00 | 0.00 | 10851600.95 | 0.00 | 3578973.45 | 0.721138E+10 | 0.00 | 0.40 |
Maximum of Months | 0.342069E+10 | 0.373234E+09 | 606508.93 | 0.172100E+09 | 93448040.75 | 0.854365E+10 | 0.192433E+11 | 6273.62 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 73076605.08 | 0.00 | 0.00 | 142566.62 | 0.00 | 0.144943E+10 | 24576290.42 | 0.00 | 0.35 |
February | 71182372.65 | 0.00 | 0.00 | 951039.68 | 0.00 | 0.110158E+10 | 0.223919E+09 | 0.00 | 0.36 |
March | 71382745.97 | 0.00 | 0.00 | 2970555.46 | 0.00 | 0.905146E+09 | 0.568954E+09 | 0.00 | 0.36 |
April | 36689734.93 | 594482.88 | 0.00 | 7666195.32 | 0.00 | 0.371565E+09 | 0.100674E+10 | 0.00 | 0.36 |
May | 28672591.56 | 1128374.64 | 0.00 | 11619756.65 | 0.00 | 0.120874E+09 | 0.121386E+10 | 0.00 | 0.36 |
June | 15904228.63 | 469118.55 | 0.00 | 15410027.16 | 0.00 | 10519357.52 | 0.113869E+10 | 0.00 | 0.36 |
July | 3247194.93 | 14239227.23 | 0.00 | 16297612.25 | 0.00 | 1505901.11 | 0.946280E+09 | 0.00 | 0.35 |
August | 4481105.92 | 34454129.26 | 0.00 | 14276520.25 | 0.00 | 1395716.78 | 0.715949E+09 | 0.00 | 0.36 |
September | 31343181.04 | 2908730.88 | 0.00 | 11852072.85 | 0.00 | 48904213.59 | 0.103804E+10 | 0.00 | 0.36 |
October | 46889601.30 | 0.00 | 0.00 | 4884403.98 | 0.00 | 0.581362E+09 | 0.863712E+09 | 0.00 | 0.36 |
November | 70932642.43 | 0.00 | 0.00 | 744157.49 | 0.00 | 0.121075E+10 | 0.193937E+09 | 0.00 | 0.35 |
December | 69210579.11 | 0.00 | 0.00 | 310560.61 | 0.00 | 0.141326E+10 | 60831699.32 | 0.00 | 0.35 |
Annual Sum or Average | 0.523013E+09 | 53794063.44 | 0.00 | 87125468.33 | 0.00 | 0.721629E+10 | 0.799550E+10 | 0.00 | 0.36 |
Minimum of Months | 3247194.93 | 0.00 | 0.00 | 142566.62 | 0.00 | 1395716.78 | 24576290.42 | 0.00 | 0.35 |
Maximum of Months | 73076605.08 | 34454129.26 | 0.00 | 16297612.25 | 0.00 | 0.144943E+10 | 0.121386E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 59451302.08 | 0.00 | 0.00 | 86855.72 | 0.00 | 0.148047E+10 | 7033622.15 | 0.00 | 0.35 |
February | 78775075.59 | 0.00 | 0.00 | 253760.05 | 0.00 | 0.120271E+10 | 0.115732E+09 | 0.00 | 0.36 |
March | 0.107999E+09 | 0.00 | 0.00 | 1157253.15 | 0.00 | 0.106166E+10 | 0.377458E+09 | 0.00 | 0.36 |
April | 0.131371E+09 | 594413.23 | 0.00 | 5431508.32 | 0.00 | 0.485678E+09 | 0.800016E+09 | 0.00 | 0.36 |
May | 0.177010E+09 | 871655.48 | 0.00 | 8780034.86 | 256586.96 | 0.143770E+09 | 0.104531E+10 | 0.00 | 0.36 |
June | 0.212917E+09 | 428388.19 | 0.00 | 12865620.69 | 40675.39 | 11041714.96 | 0.943560E+09 | 0.00 | 0.36 |
July | 0.209773E+09 | 11988054.38 | 0.00 | 13328439.60 | 2249504.52 | 1557933.52 | 0.742558E+09 | 0.00 | 0.36 |
August | 0.176761E+09 | 32109442.85 | 2956.27 | 9943857.74 | 2337193.33 | 1450799.89 | 0.547861E+09 | 500.00 | 0.36 |
September | 0.211682E+09 | 2091981.10 | 5702.37 | 7678202.11 | 808932.34 | 52716896.66 | 0.857935E+09 | 1774.27 | 0.36 |
October | 0.135775E+09 | 0.00 | 0.00 | 2419353.75 | 0.00 | 0.776235E+09 | 0.582243E+09 | 0.00 | 0.36 |
November | 80609788.12 | 0.00 | 0.00 | 277860.64 | 0.00 | 0.127348E+10 | 0.121826E+09 | 0.00 | 0.35 |
December | 62786532.07 | 0.00 | 0.00 | 105476.47 | 0.00 | 0.145393E+10 | 26606179.39 | 0.00 | 0.35 |
Annual Sum or Average | 0.164491E+10 | 48083935.23 | 8658.64 | 62328223.11 | 5692892.54 | 0.794469E+10 | 0.616814E+10 | 2274.27 | 0.36 |
Minimum of Months | 59451302.08 | 0.00 | 0.00 | 86855.72 | 0.00 | 1450799.89 | 7033622.15 | 0.00 | 0.35 |
Maximum of Months | 0.212917E+09 | 32109442.85 | 5702.37 | 13328439.60 | 2337193.33 | 0.148047E+10 | 0.104531E+10 | 1774.27 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.218458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254477E+10 | 0.00 | 0.00 | 0.52 |
February | 0.227174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575156E+09 | 0.00 | 0.00 | 0.53 |
March | 0.273371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
April | 0.260727E+11 | 0.00 | 0.00 | 0.00 | 4689231.60 | 0.00 | 0.00 | 0.00 | 0.52 |
May | 0.258278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
June | 0.217412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
July | 0.183832E+11 | 0.00 | 0.00 | 0.00 | 72211603.83 | 0.00 | 0.00 | 0.00 | 0.53 |
August | 0.163893E+11 | 0.00 | 0.00 | 0.00 | 0.224575E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
September | 0.228262E+11 | 0.00 | 0.00 | 0.00 | 83604.26 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 0.289840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
November | 0.252559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506043E+09 | 0.00 | 0.00 | 0.52 |
December | 0.224760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258270E+10 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.279857E+12 | 0.00 | 0.00 | 0.00 | 0.301560E+09 | 0.620867E+10 | 0.00 | 0.00 | 0.53 |
Minimum of Months | 0.163893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.289840E+11 | 0.00 | 0.00 | 0.00 | 0.224575E+09 | 0.258270E+10 | 0.00 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 12997970.16 | 0.00 | 0.00 | 37092.19 | 0.00 | 0.371903E+09 | 1868904.72 | 0.00 | 0.35 |
February | 16344524.11 | 0.00 | 0.00 | 222013.05 | 0.00 | 0.300193E+09 | 32647731.17 | 0.00 | 0.36 |
March | 20601377.47 | 0.00 | 0.00 | 729170.51 | 0.00 | 0.274880E+09 | 90902844.63 | 0.00 | 0.36 |
April | 15813341.27 | 148620.72 | 0.00 | 1718234.90 | 0.00 | 0.149048E+09 | 0.189087E+09 | 0.00 | 0.36 |
May | 6505107.44 | 282093.66 | 0.00 | 3397627.64 | 0.00 | 68858337.02 | 0.264996E+09 | 0.00 | 0.36 |
June | 4751417.59 | 117279.64 | 0.00 | 3610881.22 | 0.00 | 16027081.45 | 0.270741E+09 | 0.00 | 0.36 |
July | 492124.07 | 3559806.81 | 0.00 | 4222324.87 | 0.00 | 512329.98 | 0.236606E+09 | 0.00 | 0.36 |
August | 1411304.96 | 8610835.22 | 2644.02 | 3061693.09 | 0.00 | 483203.15 | 0.179069E+09 | 53.08 | 0.36 |
September | 7675978.09 | 727182.72 | 0.00 | 3055140.79 | 0.00 | 30826911.67 | 0.240978E+09 | 0.00 | 0.36 |
October | 15156035.89 | 0.00 | 0.00 | 1100570.97 | 0.00 | 0.201175E+09 | 0.156781E+09 | 0.00 | 0.36 |
November | 16588385.46 | 0.00 | 0.00 | 182404.53 | 0.00 | 0.326841E+09 | 25478339.05 | 0.00 | 0.36 |
December | 12474741.36 | 0.00 | 0.00 | 67081.89 | 0.00 | 0.366535E+09 | 6825815.87 | 0.00 | 0.35 |
Annual Sum or Average | 0.130812E+09 | 13445818.76 | 2644.02 | 21404235.65 | 0.00 | 0.210728E+10 | 0.169598E+10 | 53.08 | 0.36 |
Minimum of Months | 492124.07 | 0.00 | 0.00 | 37092.19 | 0.00 | 483203.15 | 1868904.72 | 0.00 | 0.35 |
Maximum of Months | 20601377.47 | 8610835.22 | 2644.02 | 4222324.87 | 0.00 | 0.371903E+09 | 0.270741E+09 | 53.08 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 6554982.27 | 0.00 | 0.00 | 14374.25 | 0.00 | 0.378942E+09 | 1250270.81 | 0.00 | 0.35 |
February | 15011308.10 | 0.00 | 0.00 | 69496.13 | 0.00 | 0.321350E+09 | 12935665.24 | 0.00 | 0.36 |
March | 27098279.07 | 0.00 | 0.00 | 331116.70 | 0.00 | 0.310259E+09 | 49379068.72 | 0.00 | 0.36 |
April | 33951605.54 | 148603.31 | 0.00 | 1133480.75 | 0.00 | 0.178979E+09 | 0.141560E+09 | 0.00 | 0.36 |
May | 46636603.35 | 217913.87 | 0.00 | 2684641.00 | 64146.74 | 69526420.11 | 0.224869E+09 | 0.00 | 0.36 |
June | 53717277.48 | 107097.05 | 0.00 | 2909407.62 | 10168.85 | 16577064.61 | 0.221892E+09 | 0.00 | 0.36 |
July | 51669958.23 | 3028309.71 | 0.00 | 3609156.61 | 531080.01 | 445427.19 | 0.186080E+09 | 0.00 | 0.36 |
August | 45865158.33 | 8009318.11 | 3155.83 | 2104806.83 | 599468.40 | 417118.59 | 0.135617E+09 | 580.77 | 0.36 |
September | 53946235.35 | 534951.19 | 0.00 | 1876331.52 | 192146.33 | 36423130.10 | 0.190257E+09 | 0.00 | 0.36 |
October | 34175356.76 | 0.00 | 0.00 | 465643.21 | 0.00 | 0.246226E+09 | 93301438.61 | 0.00 | 0.36 |
November | 17949138.93 | 0.00 | 0.00 | 64551.79 | 0.00 | 0.339960E+09 | 11073127.69 | 0.00 | 0.36 |
December | 8493509.42 | 0.00 | 0.00 | 14844.06 | 0.00 | 0.376041E+09 | 1308164.30 | 0.00 | 0.35 |
Annual Sum or Average | 0.395069E+09 | 12046193.24 | 3155.83 | 15277850.47 | 1397010.33 | 0.227515E+10 | 0.126952E+10 | 580.77 | 0.36 |
Minimum of Months | 6554982.27 | 0.00 | 0.00 | 14374.25 | 0.00 | 417118.59 | 1250270.81 | 0.00 | 0.35 |
Maximum of Months | 53946235.35 | 8009318.11 | 3155.83 | 3609156.61 | 599468.40 | 0.378942E+09 | 0.224869E+09 | 580.77 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 99794365.05 | 0.00 | 0.00 | 1479981.83 | 0.00 | 0.206967E+10 | 0.314096E+09 | 0.00 | 0.40 |
February | 65629889.22 | 0.00 | 0.00 | 4418835.03 | 0.00 | 0.132248E+10 | 0.852238E+09 | 0.00 | 0.41 |
March | 60318665.30 | 0.00 | 0.00 | 8462115.37 | 0.00 | 0.816088E+09 | 0.160214E+10 | 0.00 | 0.40 |
April | 33991922.33 | 954812.23 | 0.00 | 13037834.34 | 0.00 | 0.346323E+09 | 0.189162E+10 | 0.00 | 0.40 |
May | 21170866.13 | 1812307.72 | 0.00 | 17965429.18 | 0.00 | 98270574.51 | 0.207106E+10 | 0.00 | 0.40 |
June | 21370685.36 | 753461.78 | 0.00 | 19742206.01 | 0.00 | 7810933.47 | 0.184714E+10 | 0.00 | 0.40 |
July | 3161645.81 | 22869940.90 | 0.00 | 21223490.71 | 0.00 | 4036367.58 | 0.152523E+10 | 0.00 | 0.40 |
August | 7116383.17 | 55320219.09 | 17205.27 | 17911720.86 | 0.00 | 3458983.38 | 0.115378E+10 | 122.20 | 0.40 |
September | 38568773.91 | 4671777.64 | 0.00 | 20183992.85 | 0.00 | 43854663.68 | 0.171254E+10 | 0.00 | 0.40 |
October | 56025648.93 | 0.00 | 0.00 | 12260452.31 | 0.00 | 0.414751E+09 | 0.192108E+10 | 0.00 | 0.40 |
November | 87681954.64 | 0.00 | 0.00 | 3352509.13 | 0.00 | 0.138579E+10 | 0.894393E+09 | 0.00 | 0.40 |
December | 81781482.16 | 0.00 | 0.00 | 2525585.78 | 0.00 | 0.190928E+10 | 0.485643E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.576612E+09 | 86382519.35 | 17205.27 | 0.142564E+09 | 0.00 | 0.842180E+10 | 0.162710E+11 | 122.20 | 0.40 |
Minimum of Months | 3161645.81 | 0.00 | 0.00 | 1479981.83 | 0.00 | 3458983.38 | 0.314096E+09 | 0.00 | 0.40 |
Maximum of Months | 99794365.05 | 55320219.09 | 17205.27 | 21223490.71 | 0.00 | 0.206967E+10 | 0.207106E+10 | 122.20 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.595903E+10 | 0.00 | 0.00 | 42257140.61 | 0.00 | 0.00 | 0.376734E+11 | 0.00 | 4.42 |
February | 0.354196E+10 | 0.00 | 0.00 | 41993590.60 | 0.00 | 0.00 | 0.386426E+11 | 0.00 | 4.50 |
March | 0.221328E+10 | 0.00 | 0.00 | 55256378.40 | 0.00 | 0.00 | 0.485184E+11 | 0.00 | 4.61 |
April | 0.130013E+10 | 7951922.89 | 0.00 | 65695532.30 | 0.00 | 0.00 | 0.487635E+11 | 0.00 | 4.74 |
May | 0.367163E+09 | 0.00 | 0.00 | 85275939.53 | 0.00 | 0.00 | 0.515387E+11 | 0.00 | 4.91 |
June | 0.148357E+09 | 0.00 | 0.00 | 91100042.71 | 0.00 | 0.00 | 0.453134E+11 | 0.00 | 5.05 |
July | 62112516.68 | 0.133884E+09 | 0.00 | 0.100186E+09 | 608968.73 | 0.00 | 0.395332E+11 | 0.00 | 5.15 |
August | 68312102.09 | 0.402165E+09 | 0.00 | 90728060.88 | 1801833.03 | 0.00 | 0.353246E+11 | 0.00 | 5.16 |
September | 0.390843E+09 | 140842.73 | 0.00 | 81800741.23 | 0.00 | 0.00 | 0.458696E+11 | 0.00 | 4.93 |
October | 0.169210E+10 | 0.00 | 0.00 | 60850062.95 | 0.00 | 0.00 | 0.535621E+11 | 0.00 | 4.70 |
November | 0.301167E+10 | 0.00 | 0.00 | 47828617.60 | 0.00 | 0.00 | 0.444729E+11 | 0.00 | 4.54 |
December | 0.562096E+10 | 0.00 | 0.00 | 43479917.10 | 0.00 | 0.00 | 0.391303E+11 | 0.00 | 4.41 |
Annual Sum or Average | 0.243759E+11 | 0.544141E+09 | 0.00 | 0.806452E+09 | 2410801.76 | 0.00 | 0.528343E+12 | 0.00 | 4.76 |
Minimum of Months | 62112516.68 | 0.00 | 0.00 | 41993590.60 | 0.00 | 0.00 | 0.353246E+11 | 0.00 | 4.41 |
Maximum of Months | 0.595903E+10 | 0.402165E+09 | 0.00 | 0.100186E+09 | 1801833.03 | 0.00 | 0.535621E+11 | 0.00 | 5.16 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.169839E+10 | 0.00 | 0.00 | 57200817.73 | 0.00 | 0.00 | 0.458958E+11 | 0.00 | 4.81 |
February | 0.110958E+10 | 0.00 | 0.00 | 55614507.99 | 0.00 | 0.00 | 0.449453E+11 | 0.00 | 4.90 |
March | 0.552802E+09 | 0.00 | 0.00 | 70753935.25 | 0.00 | 0.00 | 0.548486E+11 | 0.00 | 5.03 |
April | 0.183162E+09 | 8702777.81 | 0.00 | 80811656.11 | 0.00 | 0.00 | 0.544794E+11 | 0.00 | 5.17 |
May | 12593837.00 | 0.00 | 0.00 | 99692618.73 | 0.00 | 0.00 | 0.564715E+11 | 0.00 | 5.34 |
June | 0.00 | 0.00 | 0.00 | 0.104521E+09 | 0.00 | 0.00 | 0.491782E+11 | 0.00 | 5.47 |
July | 0.00 | 0.145041E+09 | 0.00 | 0.113137E+09 | 0.00 | 0.00 | 0.425771E+11 | 0.00 | 5.55 |
August | 1811576.67 | 0.434855E+09 | 0.00 | 0.102957E+09 | 35393.70 | 0.00 | 0.380146E+11 | 0.00 | 5.55 |
September | 26779762.82 | 149362.54 | 0.00 | 95400724.79 | 0.00 | 0.00 | 0.500784E+11 | 0.00 | 5.34 |
October | 0.250169E+09 | 0.00 | 0.00 | 75776600.57 | 0.00 | 0.00 | 0.600943E+11 | 0.00 | 5.12 |
November | 0.731204E+09 | 0.00 | 0.00 | 62508160.74 | 0.00 | 0.00 | 0.511572E+11 | 0.00 | 4.96 |
December | 0.174918E+10 | 0.00 | 0.00 | 58395947.16 | 0.00 | 0.00 | 0.470910E+11 | 0.00 | 4.81 |
Annual Sum or Average | 0.631567E+10 | 0.588747E+09 | 0.00 | 0.976770E+09 | 35393.70 | 0.00 | 0.594832E+12 | 0.00 | 5.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 55614507.99 | 0.00 | 0.00 | 0.380146E+11 | 0.00 | 4.81 |
Maximum of Months | 0.174918E+10 | 0.434855E+09 | 0.00 | 0.113137E+09 | 35393.70 | 0.00 | 0.600943E+11 | 0.00 | 5.55 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.104427E+09 | 0.00 | 0.00 | 0.619237E+11 | 0.00 | 20.41 |
February | 0.00 | 0.00 | 0.00 | 94576538.36 | 0.00 | 0.00 | 0.600792E+11 | 0.00 | 20.85 |
March | 0.00 | 0.00 | 0.00 | 0.107807E+09 | 0.00 | 0.00 | 0.722036E+11 | 0.00 | 21.08 |
April | 0.00 | 14966234.35 | 0.00 | 0.116541E+09 | 0.00 | 0.00 | 0.689257E+11 | 0.00 | 21.48 |
May | 0.00 | 0.00 | 0.00 | 0.136438E+09 | 0.00 | 0.00 | 0.673087E+11 | 0.00 | 21.69 |
June | 0.00 | 0.00 | 0.00 | 0.140601E+09 | 0.00 | 0.00 | 0.556938E+11 | 0.00 | 21.93 |
July | 0.00 | 0.230408E+09 | 0.00 | 0.148471E+09 | 0.00 | 0.00 | 0.461013E+11 | 0.00 | 21.98 |
August | 0.00 | 0.716646E+09 | 0.00 | 0.135907E+09 | 0.00 | 0.00 | 0.408364E+11 | 0.00 | 22.08 |
September | 0.00 | 266863.23 | 0.00 | 0.133929E+09 | 0.00 | 0.00 | 0.586774E+11 | 0.00 | 21.76 |
October | 0.00 | 0.00 | 0.00 | 0.112225E+09 | 0.00 | 0.00 | 0.755137E+11 | 0.00 | 21.32 |
November | 0.00 | 0.00 | 0.00 | 0.100530E+09 | 0.00 | 0.00 | 0.661934E+11 | 0.00 | 20.77 |
December | 0.00 | 0.00 | 0.00 | 0.104438E+09 | 0.00 | 0.00 | 0.639948E+11 | 0.00 | 20.45 |
Annual Sum or Average | 0.00 | 0.962288E+09 | 0.00 | 0.143589E+10 | 0.00 | 0.00 | 0.737452E+12 | 0.00 | 21.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 94576538.36 | 0.00 | 0.00 | 0.408364E+11 | 0.00 | 20.41 |
Maximum of Months | 0.00 | 0.716646E+09 | 0.00 | 0.148471E+09 | 0.00 | 0.00 | 0.755137E+11 | 0.00 | 22.08 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.131981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747219E+09 | 0.00 | 0.00 | 1.13 |
February | 0.130118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305732E+09 | 0.00 | 0.00 | 1.14 |
March | 0.156300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 |
April | 0.149071E+11 | 0.00 | 0.00 | 0.00 | 2681068.20 | 0.00 | 0.00 | 0.00 | 1.13 |
May | 0.147618E+11 | 0.00 | 0.00 | 5320.79 | 0.00 | 0.00 | 5222875.15 | 0.00 | 1.14 |
June | 0.124112E+11 | 0.00 | 0.00 | 41674.92 | 0.00 | 0.00 | 19240478.25 | 0.00 | 1.14 |
July | 0.103855E+11 | 30694809.38 | 0.00 | 285443.08 | 10878876.08 | 0.00 | 0.124777E+09 | 0.00 | 1.14 |
August | 0.913800E+10 | 97972700.93 | 0.00 | 567476.56 | 33459099.60 | 0.00 | 0.232137E+09 | 0.00 | 1.15 |
September | 0.129691E+11 | 47800.74 | 0.00 | 328368.39 | 0.00 | 0.00 | 81504107.17 | 0.00 | 1.14 |
October | 0.165716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 |
November | 0.147294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 |
December | 0.140692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258129E+09 | 0.00 | 0.00 | 1.13 |
Annual Sum or Average | 0.161783E+12 | 0.128715E+09 | 0.00 | 1228283.74 | 47019043.87 | 0.131108E+10 | 0.462882E+09 | 0.00 | 1.14 |
Minimum of Months | 0.913800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 |
Maximum of Months | 0.165716E+11 | 97972700.93 | 0.00 | 567476.56 | 33459099.60 | 0.747219E+09 | 0.232137E+09 | 0.00 | 1.15 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:02:49
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.608185E+11 | 0.434656E+10 | 0.219441E+12 | 0.929119E+12 | 0.513833E+11 |
February | 0.132574E+12 | 0.364764E+10 | 0.182547E+12 | 0.786190E+12 | 0.648414E+11 |
March | 0.251708E+12 | 0.353668E+10 | 0.171802E+12 | 0.760512E+12 | 0.943919E+11 |
April | 0.404977E+12 | 0.297803E+10 | 0.138788E+12 | 0.625694E+12 | 0.156123E+12 |
May | 0.531324E+12 | 0.273874E+10 | 0.120716E+12 | 0.548542E+12 | 0.223746E+12 |
June | 0.546971E+12 | 0.230557E+10 | 0.935821E+11 | 0.420339E+12 | 0.292299E+12 |
July | 0.569100E+12 | 0.189791E+10 | 0.750662E+11 | 0.345442E+12 | 0.411057E+12 |
August | 0.448619E+12 | 0.164833E+10 | 0.639868E+11 | 0.295723E+12 | 0.479125E+12 |
September | 0.285406E+12 | 0.221739E+10 | 0.987715E+11 | 0.434482E+12 | 0.268134E+12 |
October | 0.190368E+12 | 0.287682E+10 | 0.139176E+12 | 0.606629E+12 | 0.145758E+12 |
November | 0.710661E+11 | 0.338559E+10 | 0.175249E+12 | 0.736805E+12 | 0.781193E+11 |
December | 0.391480E+11 | 0.413712E+10 | 0.209057E+12 | 0.890633E+12 | 0.572141E+11 |
Annual Sum or Average | 0.353208E+13 | 0.357164E+11 | 0.168818E+13 | 0.738011E+13 | 0.232219E+13 |
Minimum of Months | 0.391480E+11 | 0.164833E+10 | 0.639868E+11 | 0.295723E+12 | 0.513833E+11 |
Maximum of Months | 0.569100E+12 | 0.434656E+10 | 0.219441E+12 | 0.929119E+12 | 0.479125E+12 |