Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:01
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2023-10-16 09:02:00
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 9074.24 | 799.82 | 799.82 |
Net Site Energy | 9074.24 | 799.82 | 799.82 |
Total Source Energy | 21225.38 | 1870.85 | 1870.85 |
Net Source Energy | 21225.38 | 1870.85 | 1870.85 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 686.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 992.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 542.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 174.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 641.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 590.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 106.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 150.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 496.90 | 1131.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 43.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5467.55 | 3606.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 686.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 992.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 542.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 174.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 952.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 22.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 590.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 106.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 150.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.74 | 1131.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Other | 406.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 20.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 686.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 992.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 542.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 174.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1728.14 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 641.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 590.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 106.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 150.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 496.90 | 1131.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 43.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 63.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 192.75 | 160.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 225.96 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 481.92 | 317.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 63.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 192.75 | 160.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 225.96 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 481.92 | 317.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5467.549 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5467.549 | 100.00 |
Total On-Site and Utility Electric Sources | 5467.549 | 100.00 |
Total Electricity End Uses | 5467.549 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 95.88 | 4.04 |
Air to Air Heat Recovery for Heating | 2277.52 | 95.96 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2373.40 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 78.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7518.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWHSYSLAUNDRY HPWH TANK | SWHSYS1 HPWH TANK |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | SWHSYS1 HPWH DXCOIL | SWHSYSLAUNDRY HPWH DXCOIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| SWHSYS1 HPWH FAN | SWHSYSLAUNDRY HPWH FAN | FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:01 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 5.9798 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 8.7295 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 8.7295 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 4.1656 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 3.6813 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.1344 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 8.3313 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 8.1375 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 3.9719 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 3.9719 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 3.9719 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 3.9719 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 3.9719 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 8.3313 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 8.3313 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 10.5594 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 3.9719 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.2589 | 7.07 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 5.2589 | 7.07 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.9798 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 8.7295 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 8.7295 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 4.1656 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 3.6813 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.1344 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 8.3313 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 8.1375 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 3.9719 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 3.9719 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 3.9719 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 3.9719 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 3.9719 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 3.9719 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 3.9719 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 3.9719 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 3.9719 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 3.9719 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 8.3313 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 8.3313 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 10.5594 | 4.65 | 2931.5031 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 3.9719 | 18.58 | 0.0000 | |
Total | 11345.29 | 5.2589 | 3.54 | 41.0437 | |||||||
Conditioned Total | 11345.29 | 5.2589 | 3.54 | 41.0437 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 3.3293 | 8.82 | 37.1717 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 21-JUL-19:30 | 11-DEC-18:49 | - | - | - | - | - | - | - | - | - | - | 16-MAR-20:10 |
Heating | 0.00 | 187635.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 126741.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 45424.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 87982.85 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 31573.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 39722.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4130.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 38543.57 | 116032.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1323.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 396477.46 | 407916.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 187635.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 126741.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 45424.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58308.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1269.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 39722.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 4130.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3679.70 | 116032.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 428.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 653.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 744.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3143.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1719.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 552.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5473.02 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2031.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1871.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 336.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 475.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1573.70 | 1226.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 138.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 17315.73 | 3909.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 65.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 277.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 151.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 164.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 29.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 41.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 138.71 | 108.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1526.25 | 344.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 65.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 277.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 151.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 482.40 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 179.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 164.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 29.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 41.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 138.71 | 108.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1526.25 | 344.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.47 | 0.611386 | 0.471000 | 1.16 | 1.00 | 0.500000 | 0.000623 | 0.000044 | 1.16 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.387785 | 0.131796 | 0.471000 | 0.182647 | 0.471000 | 0.500000 | 0.002891 | 0.000028 | 0.182647 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.258058 | 0.229343 | 0.471000 | 0.121545 | 0.611580 | 0.500000 | 0.001661 | 0.000012 | 0.121545 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.216503 | 0.578068 | 0.471000 | 0.101973 | 1.00 | 0.500000 | 0.000659 | 0.000017 | 0.101973 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.117349 | 0.615314 | 0.471000 | 0.055271 | 1.00 | 0.500000 | 0.000619 | 0.000011 | 0.055271 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.95 | 0.059694 | 0.471000 | 1.86 | 0.471000 | 0.500000 | 0.025327 | 0.000088 | 1.86 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.71 | 0.084222 | 0.471000 | 0.804817 | 0.471000 | 0.500000 | 0.004524 | 0.000083 | 0.804817 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.44 | 0.183213 | 0.471000 | 2.56 | 0.488568 | 0.500000 | 0.002080 | 0.000222 | 2.56 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.40 | 0.849514 | 0.471000 | 0.658061 | 1.00 | 0.500000 | 0.000448 | 0.000101 | 0.658061 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.60 | 0.097178 | 0.471000 | 1.22 | 0.471000 | 0.500000 | 0.003921 | 0.000095 | 1.22 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.73 | 0.092563 | 0.471000 | 1.29 | 0.471000 | 0.500000 | 0.004116 | 0.000099 | 1.29 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.64 | 0.053695 | 0.471000 | 1.24 | 0.471000 | 0.500000 | 0.012762 | 0.000068 | 1.24 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.836374 | 0.375477 | 0.471000 | 0.393932 | 1.00 | 0.500000 | 0.001015 | 0.000066 | 0.393932 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 5044.63 | 0.000044 | 105.20 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3175.36 | 0.000028 | 78.70 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1339.25 | 0.000012 | 30.37 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1938.96 | 0.000017 | 49.25 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1204.68 | 0.000011 | 31.96 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10030.77 | 0.000088 | 211.82 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 9494.12 | 0.000083 | 217.52 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 25396.02 | 0.000222 | 567.54 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 5320.35 | 0.000047 | 152.01 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 5320.06 | 0.000047 | 152.00 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 30845.27 | 0.000270 | 881.28 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 30854.82 | 0.000270 | 881.55 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 5320.35 | 0.000047 | 152.01 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 5320.06 | 0.000047 | 152.00 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 11567.97 | 0.000101 | 287.52 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1664.03 | 0.000015 | 47.54 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1664.97 | 0.000015 | 47.57 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8000.37 | 0.000070 | 228.57 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 10887.06 | 0.000095 | 240.12 |
DINING_FLR_6 VAV BOX REHEAT COIL | 11288.02 | 0.000099 | 248.61 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7721.86 | 0.000068 | 164.72 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7595.64 | 0.000066 | 193.70 |
VAV WITH REHEAT HEATING COIL | 180762.21 | 0.001581 | 3024.97 |
FLR_3_DOAS HEATING COIL | 15066.37 | 0.000132 | 252.13 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.32 | 0.000047 | 0.000435 |
ROOM_2_FLR_3 FAN COIL | 1.30 | 0.000047 | 0.000429 |
ROOM_3_MULT19_FLR_3 FAN COIL | 6.63 | 0.000270 | 0.002156 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.69 | 0.000270 | 0.002322 |
ROOM_5_FLR_3 FAN COIL | 1.16 | 0.000047 | 0.000382 |
ROOM_6_FLR_3 FAN COIL | 1.15 | 0.000047 | 0.000379 |
ROOM_1_FLR_6 FAN COIL | 0.351141 | 0.000015 | 0.000116 |
ROOM_2_FLR_6 FAN COIL | 0.346248 | 0.000015 | 0.000114 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.42 | 0.000070 | 0.000478 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.32 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.30 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.63 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.69 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.16 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.15 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.351141 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.346248 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.42 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008557 | 12.80 | 0.008500 | 0.000435 | 1.32 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008557 | 12.80 | 0.008500 | 0.000429 | 1.30 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008488 | 12.80 | 0.008488 | 0.002156 | 6.63 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008743 | 12.80 | 0.008500 | 0.002322 | 6.69 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008564 | 12.80 | 0.008500 | 0.000382 | 1.16 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008565 | 12.80 | 0.008500 | 0.000379 | 1.15 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008553 | 12.80 | 0.008500 | 0.000116 | 0.351141 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008554 | 12.80 | 0.008500 | 0.000114 | 0.346248 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21.81 | 6.70 | 0.008630 | 12.80 | 0.008500 | 0.000478 | 1.42 | |
VAV WITH REHEAT COOLING COIL | 29.25 | 6.70 | 0.007819 | 10.58 | 0.007819 | 0.016572 | 24.61 | 463959.27 |
FLR_3_DOAS COOLING COIL | 35.10 | 6.70 | 0.005699 | 11.74 | 0.005699 | 0.001722 | 2.05 | 48199.93 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 12.37 | 11.66 | 24.75 | 11.66 | 24.61 | 24.61 | 0.300000 | 0.473656 | 24.61 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 24.61 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 11.66 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 24.61 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.016572 | 0.000029 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001581 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001722 | 0.000277 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000132 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Size Rated Evaporator Air Flow Rate [m3/s] | Design Size Rated Condenser Water Flow Rate [m3/s] | |
SWHSYSLAUNDRY HPWH DXCOIL | 4.90 | 0.004370 |
SWHSYS1 HPWH DXCOIL | 3.87 | 0.003451 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
SWHSYSLAUNDRY HPWH FAN | 4.90 | 700.51 |
SWHSYS1 HPWH FAN | 3.87 | 553.22 |
Condenser water flow rate [m3/s] | Evaporator air flow rate [m3/s] | |
SWHSYS1 HPWH | 0.003451 | 3.87 |
SWHSYSLAUNDRY HPWH | 0.004370 | 4.90 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.025104 | 5121.84 | |
HEATSYS1 PUMP | 0.003472 | 1035.14 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003472 | 0.416590 |
COOLSYS1 | 0.025104 | 3.01 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 396823.21 | 396823.21 | 0.003472 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.025104 | 3546.02 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.025104 | 702852.82 | 703517.62 | 80.20 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 HPWH TANK | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 5.980 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 11.360 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 8.730 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 19.490 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 8.730 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 19.490 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 4.166 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 9.546 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 3.681 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.371 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.134 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.664 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 8.331 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 13.711 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 8.138 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.208 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 3.972 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.492 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 3.972 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.492 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 3.972 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.972 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 3.972 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 10.722 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 3.972 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.492 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 8.331 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 76.151 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 8.331 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 76.151 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 10.559 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2942.062 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 3.972 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.972 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 11832.934 | 5.980 | 111.108 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 11832.934 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 585.501 | 8.730 | 54.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 585.501 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 678.012 | 8.730 | 54.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 678.012 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 684.177 | 4.166 | 257.985 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 684.177 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 348.833 | 3.681 | 170.996 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 348.833 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 400.685 | 5.134 | 47.701 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 400.685 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 1573.457 | 8.331 | 11.057 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1573.457 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 10645.380 | 8.138 | 25.200 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10645.380 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 154.991 | 3.972 | 103.327 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.991 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 154.973 | 3.972 | 103.315 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.973 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 97.406 | 3.972 | 64.937 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 97.406 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 97.432 | 3.972 | 64.955 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 97.432 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 154.991 | 3.972 | 103.327 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.991 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 154.973 | 3.972 | 103.315 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.973 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1546.669 | 3.972 | 73.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1546.669 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 154.991 | 3.972 | 103.327 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.991 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 154.973 | 3.972 | 103.315 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 154.973 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 97.432 | 3.972 | 64.955 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 97.432 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 2763.123 | 8.331 | 11.057 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2763.123 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 2763.123 | 8.331 | 11.057 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2763.123 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1090.832 | 10.559 | 49.053 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1090.832 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1636.910 | 3.972 | 73.801 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1636.910 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.9242 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.217 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.286 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.107 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.174 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9147 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6546 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6103 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7359 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6841 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602615 | 1.7602615 | 1.7602615 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
25 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
26 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
27 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
28 | 9 | -0.28612306E-14 | 0.35438919E-16 | -0.14997333E-09 | 0.48037931E-16 |
29 | 8 | 0.21910456E-07 | 0.12451452E-12 | 0.37817107E-03 | -0.24912943E-09 |
30 | 7 | -0.12252860E-01 | 0.64616398E-08 | -0.23102096E-01 | 0.13931948E-03 |
31 | 6 | 0.40565756 | 0.22511349E-05 | 0.47235308 | -0.47513834E-02 |
32 | 5 | -5.1935619 | 0.84157732E-04 | -4.4432762 | 0.63221026E-01 |
33 | 4 | 33.016121 | 0.68920660E-03 | 21.448225 | -0.42229901 |
34 | 3 | -111.25447 | 0.15035857E-02 | -55.639617 | 1.5156026 |
35 | 2 | 197.15924 | 0.84653085E-03 | 77.889127 | -2.9011628 |
36 | 1 | -171.17492 | 0.90445513E-04 | -55.258822 | 2.7457697 |
37 | 0 | 57.057407 | 0.51539406E-06 | 15.557951 | |
38 | 9 | 0.12430042E-14 | 0.43603463E-16 | -0.13615479E-09 | -0.52742981E-17 |
39 | 8 | 0.19963588E-07 | 0.16114398E-12 | 0.35741204E-03 | -0.22699287E-09 |
40 | 7 | -0.11632381E-01 | 0.85488282E-08 | -0.22208377E-01 | 0.13226440E-03 |
41 | 6 | 0.38879653 | 0.30047059E-05 | 0.45796739 | -0.45526330E-02 |
42 | 5 | -5.0290001 | 0.11318598E-03 | -4.3326723 | 0.61180550E-01 |
43 | 4 | 32.288109 | 0.93328928E-03 | 21.015642 | -0.41263319 |
44 | 3 | -109.70522 | 0.20484795E-02 | -54.784283 | 1.4932205 |
45 | 2 | 195.62339 | 0.11595496E-02 | 77.105128 | -2.8767741 |
46 | 1 | -170.60747 | 0.12450863E-03 | -55.031726 | 2.7358244 |
47 | 0 | 57.057407 | 0.71328115E-06 | 15.596176 | |
48 | 9 | 0.10418955E-14 | 0.45554749E-16 | -0.13285794E-09 | -0.34221686E-17 |
49 | 8 | 0.19498290E-07 | 0.16949498E-12 | 0.35235048E-03 | -0.22170227E-09 |
50 | 7 | -0.11480752E-01 | 0.90423087E-08 | -0.21989859E-01 | 0.13054032E-03 |
51 | 6 | 0.38467563 | 0.31853038E-05 | 0.45444290 | -0.45040579E-02 |
52 | 5 | -4.9887746 | 0.12022067E-03 | -4.3055366 | 0.60681782E-01 |
53 | 4 | 32.110117 | 0.99300969E-03 | 20.909427 | -0.41027004 |
54 | 3 | -109.32633 | 0.21828955E-02 | -54.574228 | 1.4877470 |
55 | 2 | 195.24766 | 0.12373115E-02 | 76.912747 | -2.8708078 |
56 | 1 | -170.46860 | 0.13302463E-03 | -54.976289 | 2.7333905 |
57 | 0 | 57.057407 | 0.76310210E-06 | 15.605744 | |
58 | 9 | -0.19728226E-15 | 0.38070760E-16 | -0.14134637E-09 | 0.10329039E-17 |
59 | 8 | 0.20696804E-07 | 0.14765672E-12 | 0.36530744E-03 | -0.23532978E-09 |
60 | 7 | -0.11868633E-01 | 0.77667999E-08 | -0.22548754E-01 | 0.13495068E-03 |
61 | 6 | 0.39521686 | 0.27204939E-05 | 0.46345169 | -0.46283129E-02 |
62 | 5 | -5.0916664 | 0.10217830E-03 | -4.3748670 | 0.61957574E-01 |
63 | 4 | 32.565369 | 0.84029717E-03 | 21.180735 | -0.41631434 |
64 | 3 | -110.29532 | 0.18400486E-02 | -55.110745 | 1.5017457 |
65 | 2 | 196.20849 | 0.10394005E-02 | 77.404245 | -2.8860650 |
66 | 1 | -170.82368 | 0.11139293E-03 | -55.118150 | 2.7396138 |
67 | 0 | 57.057407 | 0.63685742E-06 | 15.581450 | |
68 | 9 | 0.13059652E-14 | 0.41030072E-16 | -0.13816519E-09 | -0.47111965E-17 |
69 | 8 | 0.20247126E-07 | 0.15597406E-12 | 0.36047671E-03 | -0.23021680E-09 |
70 | 7 | -0.11724123E-01 | 0.82470298E-08 | -0.22340566E-01 | 0.13330755E-03 |
71 | 6 | 0.39128975 | 0.28947446E-05 | 0.46009809 | -0.45820219E-02 |
72 | 5 | -5.0533361 | 0.10891817E-03 | -4.3490697 | 0.61482301E-01 |
73 | 4 | 32.395785 | 0.89717001E-03 | 21.079809 | -0.41406279 |
74 | 3 | -109.93440 | 0.19673976E-02 | -54.911173 | 1.4965315 |
75 | 2 | 195.85064 | 0.11127485E-02 | 77.221372 | -2.8803827 |
76 | 1 | -170.69145 | 0.11939355E-03 | -55.065279 | 2.7372963 |
77 | 0 | 57.057407 | 0.68346468E-06 | 15.590432 | |
78 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
79 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
80 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
81 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
82 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
83 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
84 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
85 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
86 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
87 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
88 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
89 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
90 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
91 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
92 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
93 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3672_SHGC_0.36 | 37 | 1 | VerySmooth | 2.086 | 2.086 | 1.000 | 0.361 | ||
2 | RESWINDOW_U_0.3672_SHGC_0.36 | 38 | 1 | VerySmooth | 2.086 | 2.086 | 1.000 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.58639E-002 | 0.27318 | 0.51921 | 0.51921 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11691 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.58639E-002 | 0.27318 | 0.51921 | 0.51921 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11691 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | "DX Coil Total Cooling Rate {W | HPWH Only}" | |
1 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | 1.1400 | 72098.5 | 48.891 | 1.6574 | 76621 | |
2 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | 2.8400 | 59724.5 | 4.608 | 9.3676 | 53264 |
Node Number | Height {m} | Volume {m3} | Maximum Capacity {W} | Off-Cycle UA {W/K} | On-Cycle UA {W/K} | Number Of Inlets | Number Of Outlets | |
1 | 1 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 0 | 1 |
2 | 2 | 0.2683 | 0.4733 | 46126.940 | 1.5573 | 1.5573 | 0 | 0 |
3 | 3 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
4 | 4 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 0 |
5 | 5 | 0.2683 | 0.4733 | 0.000 | 1.5573 | 1.5573 | 0 | 1 |
6 | 6 | 0.2683 | 0.4733 | 0.000 | 2.4569 | 2.4569 | 2 | 0 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 9.802E-003 | 1.461E-004 | 7.212E-005 | 0.133 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 3.784E-003 | 4.872E-005 | 1.327E-004 | 4.426E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 8.942E-003 | 5.445E-005 | 1.424E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 5.159E-003 | 5.445E-005 | 1.182E-004 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 1.221E-002 | 1.565E-004 | 1.392E-004 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 2.167E-002 | 1.147E-004 | 6.318E-005 | 0.104 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 6.191E-002 | 4.733E-005 | 9.051E-005 | 4.300E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.587E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.588E-003 | 6.472E-005 | 1.424E-004 | 7.644E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 1.424E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 6.879E-003 | 1.766E-005 | 1.424E-004 | 2.086E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 5.689E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 5.688E-003 | 1.458E-004 | 7.203E-005 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 2.910E-003 | 1.186E-004 | 6.472E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 1.389E-002 | 4.188E-005 | 3.236E-005 | 4.947E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1.243E-002 | 1.204E-004 | 6.523E-005 | 0.142 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1.217E-002 | 2.953E-005 | 2.446E-005 | 3.488E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1269 |
2 | Clear Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 6.0111E-002 |
3 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 0.1415 |
4 | Clear Turbid Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 6.6427E-002 |
5 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 9.4355E-002 |
6 | Intermediate Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 3.5888E-002 |
7 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT1 | 3.7870E-002 |
8 | Overcast Sky | 12/21 | LOBBY_FLR_1_DAYLCTRL | LOBBY_FLR_1 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_DAYLREFPT2 | 1.2581E-002 |
9 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1439 |
10 | Clear Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 7.3134E-002 |
11 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1610 |
12 | Clear Turbid Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 8.0683E-002 |
13 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 0.1045 |
14 | Intermediate Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 4.5101E-002 |
15 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT1 | 4.2527E-002 |
16 | Overcast Sky | 12/21 | CAFE_FLR_1_DAYLCTRL | CAFE_FLR_1 | CAFE_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_DAYLREFPT2 | 1.7207E-002 |
17 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.0815E-002 |
18 | Clear Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.7721E-002 |
19 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.3679E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3357E-002 |
21 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 2.2753E-002 |
22 | Intermediate Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 9.1119E-003 |
23 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT1 | 3.7278E-002 |
24 | Overcast Sky | 12/21 | DINING_FLR_6_DAYLCTRL | DINING_FLR_6 | DINING_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_DAYLREFPT2 | 1.3219E-002 |
25 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.0815E-002 |
26 | Clear Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.7721E-002 |
27 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.3679E-002 |
28 | Clear Turbid Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3357E-002 |
29 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 2.2753E-002 |
30 | Intermediate Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 9.1119E-003 |
31 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT1 | 3.7278E-002 |
32 | Overcast Sky | 12/21 | BANQUET_FLR_6_DAYLCTRL | BANQUET_FLR_6 | BANQUET_FLR_6_WALL_NORTH_WINDOW | BANQUET_FLR_6_DAYLREFPT2 | 1.3219E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 27918.25918 | 27918.25918 | 2.46631 | 2.46631 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:10:00 | 28.14750 | 5.68868E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4389.26004 | 4389.26004 | 0.38779 | 0.38779 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.76250 | 5.69886E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2382.39915 | 2382.39915 | 0.12415 | 0.12415 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 2920.82263 | 2920.82263 | 0.25806 | 0.25806 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 32.31000 | 5.69506E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 811.55456 | 811.55456 | 4.22931E-002 | 9.17347E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2451.07914 | 2451.07914 | 0.21650 | 0.21650 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:10:00 | 28.14750 | 5.68868E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1496.26871 | 1496.26871 | 7.79761E-002 | 7.79761E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1328.52399 | 1328.52399 | 0.11735 | 0.11735 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 32.08500 | 5.69471E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 964.72802 | 964.72802 | 5.02755E-002 | 5.77652E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44748.86259 | 44748.86259 | 3.95303 | 3.95303 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 34.69500 | 5.69875E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1948.32219 | 1948.32219 | 0.10153 | 0.10153 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 19323.08086 | 19323.08086 | 1.70874 | 1.70874 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.76250 | 5.69886E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 5999.85639 | 5999.85639 | 0.31267 | 0.67639 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 61563.20948 | 61563.20948 | 5.44087 | 5.44087 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.87500 | 5.69904E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 14269.97232 | 14269.97232 | 0.74366 | 1.89399 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11052.25190 | 11052.25190 | 1.31561 | 1.31561 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5320.36509 | 5320.36509 | 0.27889 | 0.27889 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10918.86292 | 10918.86292 | 1.29973 | 1.29973 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5320.07445 | 5320.07445 | 0.27887 | 0.27887 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 55690.79622 | 55690.79622 | 6.62889 | 6.62889 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.98750 | 5.69921E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 30845.31036 | 30845.31036 | 1.61691 | 1.61691 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 56208.35830 | 56208.35830 | 6.69107 | 6.69107 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 31.52250 | 5.69384E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 30854.86372 | 30854.86372 | 1.61741 | 1.61741 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 9707.02950 | 9707.02950 | 1.15548 | 1.15548 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 29.58750 | 5.69088E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5320.36509 | 5320.36509 | 0.27889 | 0.27889 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9619.76111 | 9619.76111 | 1.14509 | 1.14509 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 28.82250 | 5.68971E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5320.07445 | 5320.07445 | 0.27887 | 0.27887 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 15816.04392 | 15816.04392 | 1.39716 | 1.39716 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 35.10000 | 5.69938E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 8710.71303 | 8710.71303 | 0.45395 | 0.47476 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2949.88036 | 2949.88036 | 0.35114 | 0.35114 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 33.39000 | 5.69673E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1664.03917 | 1664.03917 | 8.72279E-002 | 8.72279E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2908.77501 | 2908.77501 | 0.34625 | 0.34625 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1664.97889 | 1664.97889 | 8.72772E-002 | 8.72772E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 11930.88760 | 11930.88760 | 1.42024 | 1.42024 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.98750 | 5.69921E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 8000.39110 | 8000.39110 | 0.41938 | 0.41938 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29399.70573 | 29399.70573 | 2.60063 | 2.60063 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 35.10000 | 5.69938E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5568.51019 | 5568.51019 | 0.29020 | 1.18780 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 30866.06404 | 30866.06404 | 2.73029 | 2.73029 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 35.10000 | 5.69938E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 5704.29847 | 5704.29847 | 0.29727 | 1.18780 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 29765.42088 | 29765.42088 | 2.63681 | 2.63681 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 33.88500 | 5.69749E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2336.43047 | 2336.43047 | 0.12175 | 0.36735 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -7.90000 | 2.34317E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 9468.01462 | 9468.01462 | 0.83637 | 0.83637 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 35.10000 | 5.69938E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 5885.12024 | 5885.12024 | 0.30670 | 0.30670 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 402993.09 | 24.61114 | 24.61114 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 181228.67 | 7.40240 | 7.40240 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 45524.16 | 19.09732 | 2.05125 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 50219.47 | 4.94373 | 2.05125 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.46631 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.61139 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47100 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.16163 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.23174E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.41326E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.16163 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5044.62961 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.41326E-005 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 105.19705 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.38779 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13180 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47100 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18265 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47100 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.89084E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.77795E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.18265 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3175.36492 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.77795E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 78.69734 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.25806 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22934 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47100 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12155 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61158 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.66127E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.17163E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12155 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1339.24894 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.17163E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 30.36728 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.21650 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.57807 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47100 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.10197 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.59092E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.69628E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.10197 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1938.95697 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69628E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 49.24518 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.11735 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.61531 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47100 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.52714E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.19196E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.05391E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.52714E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1204.68228 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.05391E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 31.95605 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.95303 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.96945E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47100 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.86188 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47100 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.53271E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.77536E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.86188 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10030.77037 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.77536E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 211.81840 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.70874 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.42216E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47100 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80482 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47100 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.52378E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.30587E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.80482 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9494.11529 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.30587E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 217.52044 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.44087 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18321 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47100 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.56265 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48857 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.07955E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.22175E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.56265 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25396.02121 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.22175E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 567.54176 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.31561 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.31561 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.65447E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.34518E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80668 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55668E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.34518E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.31561 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5320.34946 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.65447E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 152.00757 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.29973 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.29973 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.65422E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.29342E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80667 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55727E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.29342E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.29973 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5320.05883 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.65422E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 151.99927 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.62889 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.62889 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.69848E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.15566E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80713 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.48803E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.48803E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.15566E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.62889 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 30845.26707 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.69848E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 881.27532 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.69107 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.69107 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.69931E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.32162E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80609 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.74260E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.32162E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.69107 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 30854.82041 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.69931E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 881.54826 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.15548 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.15548 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.65447E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.82425E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80666 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56433E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.82425E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.15548 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5320.34946 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.65447E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 152.00757 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.14509 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.14509 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.65422E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.79036E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80666 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56480E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.79036E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.14509 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5320.05883 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.65422E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 151.99927 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.39716 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.84951 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47100 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.65806 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.48492E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.01202E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.65806 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11567.96995 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.01202E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 287.52083 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.35114 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.35114 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.45577E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.15860E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80668 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55308E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.15860E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.35114 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1664.03450 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.45577E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 47.54241 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.34625 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.34625 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.45659E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.14269E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80668 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55381E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.14269E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.34625 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1664.97422 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.45659E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 47.56925 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.42024 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.42024 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.99908E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.78407E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 21.80633 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62990E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.78407E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.42024 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 8000.37335 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.99908E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 228.57476 |
263 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.60063 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.71776E-002 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47100 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.22490 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47100 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.92066E-003 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.52447E-005 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.22490 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
274 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10887.05564 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.52447E-005 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 240.11714 |
277 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.73029 |
278 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.25627E-002 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47100 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28597 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47100 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.11613E-003 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.87526E-005 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28597 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
288 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11288.02432 |
289 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.87526E-005 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 248.61024 |
291 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.63681 |
292 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.36953E-002 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47100 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.24194 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47100 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.27623E-002 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.75542E-005 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.24194 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
302 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7721.85934 |
303 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.75542E-005 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 164.72050 |
305 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83637 |
306 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37548 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47100 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.39393 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.01471E-003 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.64499E-005 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.39393 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
316 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7595.63680 |
317 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.64499E-005 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 193.70231 |
319 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 12.37495 |
320 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.65721 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.74991 |
322 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.65721 |
323 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.61114 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 24.61114 |
325 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
326 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.47366 |
327 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
328 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
335 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 24.61114 |
336 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
337 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.61114 |
338 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.66146 |
339 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 29.25305 |
340 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
341 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.58066 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.81862E-003 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.81862E-003 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 463959.27093 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.65715E-002 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 24.61114 |
347 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 180762.21358 |
348 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.58139E-003 |
349 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 3024.96840 |
350 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 24.61114 |
351 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.65715E-002 |
352 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.87354E-005 |
353 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.58139E-003 |
354 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
355 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
356 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
357 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 35.10000 |
358 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.73601 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 5.69938E-003 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 5.69938E-003 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 48199.92810 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.72159E-003 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
365 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 15066.37152 |
366 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.31807E-004 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 252.12846 |
368 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
369 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.72159E-003 |
370 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.76599E-004 |
371 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.31807E-004 |
372 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 4.90359 |
373 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYSLAUNDRY HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 4.36989E-003 |
374 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.90359 |
375 | Fan:SystemModel | SWHSYSLAUNDRY HPWH FAN | Design Electric Power Consumption [W] | 700.51236 |
376 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Evaporator Air Flow Rate [m3/s] | 3.87257 |
377 | Coil:WaterHeating:AirToWaterHeatPump:Pumped | SWHSYS1 HPWH DXCOIL | Design Size Rated Condenser Water Flow Rate [m3/s] | 3.45109E-003 |
378 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.87257 |
379 | Fan:SystemModel | SWHSYS1 HPWH FAN | Design Electric Power Consumption [W] | 553.22422 |
380 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Condenser water flow rate [m3/s] | 3.45109E-003 |
381 | WaterHeater:HeatPump:PumpedCondenser | SWHSYS1 HPWH | Evaporator air flow rate [m3/s] | 3.87257 |
382 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.51043E-002 |
383 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 5121.84203 |
384 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.47158E-003 |
385 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.41659 |
386 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.47158E-003 |
387 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1035.13683 |
388 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
389 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 396823.20687 |
390 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 396823.21000 |
391 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.47158E-003 |
392 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.51043E-002 |
393 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.01251 |
394 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.51043E-002 |
395 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3546.02399 |
396 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.51043E-002 |
397 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 702852.81817 |
398 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 703517.62000 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 80.20101 |
400 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
401 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
402 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
403 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
404 | WaterHeater:Stratified | SWHSYS1 HPWH TANK | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
405 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Condenser water flow rate [m3/s] | 4.36989E-003 |
406 | WaterHeater:HeatPump:PumpedCondenser | SWHSYSLAUNDRY HPWH | Evaporator air flow rate [m3/s] | 4.90359 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 5071.13 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3189.98 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1345.85 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 1947.76 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1209.93 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 10083.07 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 9540.58 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 25522.29 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 5732.28 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 5731.97 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 33233.43 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 33243.72 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 5732.28 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 5731.97 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 11621.13 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1792.86 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1793.87 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8619.73 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 10941.66 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 11344.69 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 7761.88 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7630.05 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 132092.56 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 11009.80 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 22534.89 | 16434.98 | 6099.91 | 0.73 | 4917.22 | 49.87 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 22265.24 | 16237.36 | 6027.88 | 0.73 | 4857.32 | 49.27 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 112530.26 | 82512.39 | 30017.86 | 0.73 | 25332.01 | 256.93 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 118321.68 | 84769.22 | 33552.47 | 0.72 | 24310.50 | 246.57 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 19818.82 | 14443.02 | 5375.80 | 0.73 | 4312.33 | 43.74 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 19642.28 | 14313.69 | 5328.59 | 0.73 | 4273.17 | 43.34 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 6010.80 | 4385.34 | 1625.46 | 0.73 | 1313.35 | 13.32 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 5927.81 | 4324.48 | 1603.34 | 0.73 | 1294.86 | 13.13 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 24641.96 | 17841.92 | 6800.04 | 0.72 | 5243.90 | 53.19 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 680347.49 | 401094.37 | 279253.12 | 0.59 | 145779.11 | 1478.57 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 47472.21 | 29284.36 | 18187.85 | 0.62 | 4618.55 | 46.84 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.93 | 13.40 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.217 | 1.029 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.217 | 1.029 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.217 | 1.029 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.217 | 1.029 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.174 | 0.999 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.174 | 0.999 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.174 | 0.999 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.174 | 0.999 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.174 | 0.999 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3672_SHGC_0.36 | N/A | 2.086 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.7955638991E-002 | 2.3271220993E-002 | Pass | Pass | 6.8995804639E-003 | 1.0297035249E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.7847444346E-002 | 8.0931349524E-002 | Pass | Pass | 2.6500745912E-002 | 3.2175587700E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.5852625264E-002 | 2.7259454469E-002 | Pass | Pass | 7.9402158045E-003 | 9.8046289286E-003 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.3936298799E-002 | 1.3424159580E-002 | Pass | Pass | 8.7342857799E-003 | 1.2613236636E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.0860122115E-002 | 7.8331452671E-003 | Pass | Pass | 8.7510096321E-003 | 1.2728846331E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.7906363476E-002 | 0.1647273913 | Pass | Pass | 2.0154865995E-002 | 5.2536330853E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.9848956960E-002 | 5.6983218205E-002 | Pass | Pass | 1.8814329893E-002 | 2.4112806458E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.0519496957E-002 | 3.5893818738E-002 | Pass | Pass | 1.3195824009E-002 | 2.2163024011E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.4754049053E-002 | 0.2475447135 | Pass | Pass | 0.2012356952 | 0.4059449665 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.4098667954E-002 | 0.1991177183 | Pass | Pass | 0.1609966792 | 0.4246025115 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.9419624824E-003 | 2.8493693587E-002 | Pass | Pass | 7.3036719432E-002 | 0.1802595619 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.2993000527E-002 | 7.0478188592E-002 | Pass | Pass | 0.3187729559 | 0.8995487848 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.8508816202E-002 | 0.3078049749 | Pass | Pass | 0.3685440967 | 2.1081720378 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.7663147804E-002 | 0.1821867017 | Pass | Pass | 0.5978121773 | 2.9839173898 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.4520414796E-002 | 1.1337864274E-002 | Pass | Pass | 8.3390817161E-003 | 1.1277322690E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.4275507260E-002 | 0.2157557401 | Pass | Pass | 0.1502025861 | 0.3454138617 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.6561290546E-002 | 0.2444208399 | Pass | Pass | 0.1844668930 | 0.6389140265 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2695099837E-002 | 0.3483222674 | Pass | Pass | 0.1505194546 | 0.2884077231 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.3249503703E-002 | 5.5131506834E-002 | Pass | Pass | 1.5206429516E-002 | 4.1546032353E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.6017605859E-002 | 3.7562339871E-002 | Pass | Pass | 1.5150461120E-002 | 4.0083816236E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.1237413196E-002 | 5.9330945696E-002 | Pass | Pass | 2.1558820416E-002 | 4.2763771716E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.4597120484E-002 | 2.2171173301E-002 | Pass | Pass | 1.4009270559E-002 | 1.5643350230E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5178.82 | 29.56 | 1188.88 | 6393.72 | 4487.78 | 17278.77 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 9.00 | 6 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 5.00 | 4 | |||
Nov | 9.00 | 7 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.086 | 0.361 | 0.361 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.086 | 0.361 | 0.361 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.086 | 0.361 | 0.361 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.086 | 0.361 | 0.361 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.086 | 0.361 | 0.361 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.086 | 0.361 | 0.361 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.086 | 0.361 | 0.361 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.086 | 0.361 | 0.361 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.086 | 0.361 | 0.361 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.086 | 0.361 | 0.361 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.086 | 0.361 | 0.361 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.086 | 0.361 | 0.361 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.086 | 0.361 | 0.361 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.086 | 0.361 | 0.361 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.086 | 0.361 | 0.361 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.086 | 0.361 | 0.361 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.086 | 0.361 | 0.361 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.086 | 0.361 | 0.361 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.086 | 0.361 | 0.361 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.086 | 0.361 | 0.361 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.086 | 0.361 | 0.361 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3672_SHGC_0.36 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.086 | 0.361 | 0.361 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.086 | 0.361 | 0.361 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.086 | 0.361 | 0.361 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.086 | 0.361 | 0.361 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.086 | 0.361 | 0.361 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.086 | 0.361 | 0.361 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.086 | 0.361 | 0.361 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.086 | 0.361 | 0.361 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3672_SHGC_0.36 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.086 | 0.361 | 0.361 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.086 | 0.361 | 0.361 | |||||||||||||||||
North Total or Average | 432.95 | 2.086 | 0.361 | 0.361 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.086 | 0.361 | 0.361 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.9798 | 1978.83 | 11832.93 | LightsWired | LTG_SCH_BASEMENT | 45.99 | 168.00 | 45.94 | 0.0000 | Y | 102.03 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 8.7295 | 67.07 | 585.50 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 5.64 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 8.7295 | 77.67 | 678.01 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 6.53 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 4.1656 | 164.24 | 684.18 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 7.53 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 3.6813 | 94.76 | 348.83 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 1.68 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.1344 | 78.04 | 400.68 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.41 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 8.3313 | 188.86 | 1573.46 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 39.08 | 0.0000 | Y | 11.54 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 8.1375 | 1308.19 | 10645.38 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 55.29 | 0.0000 | Y | 110.48 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 3.9719 | 156.09 | 619.96 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 5.55 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 3.9719 | 156.07 | 619.89 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 5.55 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 3.9719 | 1863.81 | 7402.84 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 66.32 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 3.9719 | 1864.32 | 7404.86 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 66.33 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 3.9719 | 156.09 | 619.96 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 5.55 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 3.9719 | 156.07 | 619.89 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 5.55 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 3.9719 | 1557.62 | 6186.67 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 51.06 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 3.9719 | 39.02 | 154.99 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.39 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 3.9719 | 39.02 | 154.97 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 1.39 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 3.9719 | 220.77 | 876.89 | LightsWired | LTG_SCH_GUESTROOM | 47.59 | 168.00 | 47.72 | 0.0000 | Y | 7.86 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 8.3313 | 331.66 | 2763.12 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.06 | 0.0000 | Y | 25.45 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 8.3313 | 331.66 | 2763.12 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 49.06 | 0.0000 | Y | 25.45 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 10.5594 | 103.30 | 1090.83 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.00 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 3.9719 | 412.12 | 1636.91 | LightsWired | LTG_SCH_CORRIDOR | 44.02 | 168.00 | 43.97 | 0.0000 | Y | 13.51 |
Interior Lighting Total | 5.2589 | 11345.29 | 59663.90 | 349.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 10645.38 | 745.18 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 10645.38 | 745.18 |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1573.46 | 613.65 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1573.46 | 613.65 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2763.12 | 552.62 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2763.12 | 552.62 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2763.12 | 552.62 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2763.12 | 552.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 11096.45 | AstronomicalClock | - | 83.71 | 83.71 | 174.36 | |
Exterior Lighting Total | 11096.45 | 174.36 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 396823.21 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 703517.62 | 2.96 | 703641.28 | 2.96 | 3.93 | 13.40 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12165.57 | 22534.89 | 16434.98 | 6099.91 | 0.73 | - | 4917.22 | 49.87 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12020.66 | 22265.24 | 16237.36 | 6027.88 | 0.73 | - | 4857.32 | 49.27 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 60353.91 | 112530.26 | 82512.39 | 30017.86 | 0.73 | - | 25332.01 | 256.93 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 65000.28 | 118321.68 | 84769.22 | 33552.47 | 0.72 | - | 24310.50 | 246.57 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10707.09 | 19818.82 | 14443.02 | 5375.80 | 0.73 | - | 4312.33 | 43.74 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 10612.19 | 19642.28 | 14313.69 | 5328.59 | 0.73 | - | 4273.17 | 43.34 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3243.85 | 6010.80 | 4385.34 | 1625.46 | 0.73 | - | 1313.35 | 13.32 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3199.28 | 5927.81 | 4324.48 | 1603.34 | 0.73 | - | 1294.86 | 13.13 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 13394.36 | 24641.96 | 17841.92 | 6800.04 | 0.72 | - | 5243.90 | 53.19 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 463959.27 | 680347.49 | 401094.37 | 279253.12 | 0.59 | - | 145779.11 | 1478.57 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 48199.93 | 47472.21 | 29284.36 | 18187.85 | 0.62 | - | 4618.55 | 46.84 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 5044.63 | 5071.13 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3175.36 | 3189.98 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1339.25 | 1345.85 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1938.96 | 1947.76 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1204.68 | 1209.93 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10030.77 | 10083.07 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9494.12 | 9540.58 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 25396.02 | 25522.29 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5320.35 | 5732.28 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5320.06 | 5731.97 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 30845.27 | 33233.43 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 30854.82 | 33243.72 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5320.35 | 5732.28 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5320.06 | 5731.97 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 11567.97 | 11621.13 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1664.03 | 1792.86 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1664.97 | 1793.87 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 8000.37 | 8619.73 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10887.06 | 10941.66 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11288.02 | 11344.69 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7721.86 | 7761.88 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7595.64 | 7630.05 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 180762.21 | 132092.56 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 15066.37 | 11009.80 | - |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 75921.46 | 3.40 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | 54370.95 | 3.40 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.32 | 925.71 | 703.64 | 1.00 | 1.14 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.30 | 914.54 | 703.64 | 1.00 | 1.14 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.63 | 4664.33 | 703.64 | 1.00 | 0.95 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 6.69 | 4708.08 | 703.64 | 1.00 | 0.95 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.16 | 813.04 | 703.64 | 1.00 | 1.16 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.15 | 805.73 | 703.64 | 1.00 | 1.17 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.35 | 247.08 | 703.64 | 1.00 | 1.61 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 0.35 | 243.63 | 703.64 | 1.00 | 1.62 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.39 | 270.90 | 1.42 | 999.34 | 703.64 | 1.00 | 1.12 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 24.61 | 55144.68 | 2240.64 | 1.00 | 1.11 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 4.90 | 700.51 | 142.86 | 0.00 | 2.78 | General | ||
SWHSYS1 HPWH FAN | Fan:SystemModel | 0.70 | 100.00 | 3.87 | 553.22 | 142.86 | 0.00 | 2.84 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.025104 | 5121.84 | 204022.71 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003472 | 1035.14 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.025104 | 3546.02 | 141251.80 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWHSYSLAUNDRY HPWH | WaterHeater:HeatPump:PumpedCondenser | 1.14 | 72098.52 | 0.80 | 48.89 | 1.66 |
SWHSYS1 HPWH | WaterHeater:HeatPump:PumpedCondenser | 2.84 | 59724.55 | 0.80 | 4.61 | 9.37 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 27918.26 | 27918.26 | 14.11 | 2.466 | 2.466 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:10:00 | 24.00 | 24.00 | 0.00936 | 28.15 | 0.00569 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4389.26 | 4389.26 | 65.44 | 0.388 | 0.388 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00904 | 34.76 | 0.00570 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 2920.82 | 2920.82 | 37.61 | 0.258 | 0.258 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 24.00 | 24.00 | 0.00946 | 32.31 | 0.00570 | 0.092 | 0.00 |
MECH_FLR_1 | 2451.08 | 2451.08 | 14.92 | 0.217 | 0.217 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:10:00 | 24.00 | 24.00 | 0.00872 | 28.15 | 0.00569 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1328.52 | 1328.52 | 14.02 | 0.117 | 0.117 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 24.00 | 24.00 | 0.00882 | 32.09 | 0.00569 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44748.86 | 44748.86 | 573.41 | 3.953 | 3.953 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00854 | 34.70 | 0.00570 | 0.000 | 0.00 |
CAFE_FLR_1 | 19323.08 | 19323.08 | 102.31 | 1.709 | 1.709 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.01015 | 34.76 | 0.00570 | 0.676 | 0.00 |
LOBBY_FLR_1 | 61563.21 | 61563.21 | 47.06 | 5.441 | 5.441 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 23.99 | 0.01004 | 34.88 | 0.00570 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 11052.25 | 11052.25 | 283.23 | 1.316 | 1.316 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00856 | 33.21 | 0.00570 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10918.86 | 10918.86 | 279.85 | 1.300 | 1.300 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00856 | 33.21 | 0.00570 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 55690.80 | 55690.80 | 2270.88 | 6.629 | 6.629 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 21.11 | 21.11 | 0.00849 | 34.99 | 0.00570 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 56208.36 | 56208.36 | 2291.36 | 6.691 | 6.691 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 21.11 | 21.11 | 0.00874 | 31.52 | 0.00569 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9707.03 | 9707.03 | 248.76 | 1.155 | 1.155 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 21.11 | 21.11 | 0.00856 | 29.59 | 0.00569 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9619.76 | 9619.76 | 246.55 | 1.145 | 1.145 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 21.11 | 21.11 | 0.00856 | 28.82 | 0.00569 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 15816.04 | 15816.04 | 40.62 | 1.397 | 1.397 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00969 | 35.10 | 0.00570 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2949.88 | 2949.88 | 75.60 | 0.351 | 0.351 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00855 | 33.39 | 0.00570 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2908.78 | 2908.78 | 74.55 | 0.346 | 0.346 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00855 | 33.21 | 0.00570 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11930.89 | 11930.89 | 486.37 | 1.420 | 1.420 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 21.11 | 21.11 | 0.00863 | 34.99 | 0.00570 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29399.71 | 29399.71 | 88.64 | 2.601 | 2.601 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 23.98 | 0.01041 | 35.10 | 0.00570 | 1.188 | 0.00 |
DINING_FLR_6 | 30866.06 | 30866.06 | 93.07 | 2.730 | 2.730 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 23.98 | 0.01032 | 35.10 | 0.00570 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 29765.42 | 29765.42 | 288.13 | 2.637 | 2.637 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01013 | 33.89 | 0.00570 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9468.01 | 9468.01 | 22.97 | 0.836 | 0.836 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00902 | 35.10 | 0.00570 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.63 | 0.00234 | -7.90 | 0.00234 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2382.40 | 2382.40 | 35.52 | 0.124 | 0.124 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00788 | -7.90 | 0.00234 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 811.55 | 811.55 | 10.45 | 0.042 | 0.092 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00786 | -7.90 | 0.00234 | 0.092 | 0.00 |
MECH_FLR_1 | 1496.27 | 1496.27 | 9.11 | 0.078 | 0.078 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00783 | -7.90 | 0.00234 | 0.000 | 0.00 |
STORAGE_FLR_1 | 964.73 | 964.73 | 10.18 | 0.050 | 0.058 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00784 | -7.90 | 0.00234 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1948.32 | 1948.32 | 24.97 | 0.102 | 0.102 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00782 | -7.90 | 0.00234 | 0.000 | 0.00 |
CAFE_FLR_1 | 5999.86 | 5999.86 | 31.77 | 0.313 | 0.676 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00789 | -7.90 | 0.00234 | 0.676 | 0.00 |
LOBBY_FLR_1 | 14269.97 | 14269.97 | 10.91 | 0.744 | 1.894 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00787 | -7.90 | 0.00234 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5320.37 | 5320.37 | 136.34 | 0.279 | 0.279 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00788 | -7.90 | 0.00234 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5320.07 | 5320.07 | 136.35 | 0.279 | 0.279 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00788 | -7.90 | 0.00234 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 30845.31 | 30845.31 | 1257.77 | 1.617 | 1.617 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00789 | -7.90 | 0.00234 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 30854.86 | 30854.86 | 1257.81 | 1.617 | 1.617 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00789 | -7.90 | 0.00234 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5320.37 | 5320.37 | 136.34 | 0.279 | 0.279 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00788 | -7.90 | 0.00234 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5320.07 | 5320.07 | 136.35 | 0.279 | 0.279 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00788 | -7.90 | 0.00234 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 8710.71 | 8710.71 | 22.37 | 0.454 | 0.475 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00791 | -7.90 | 0.00234 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1664.04 | 1664.04 | 42.64 | 0.087 | 0.087 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00790 | -7.90 | 0.00234 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1664.98 | 1664.98 | 42.67 | 0.087 | 0.087 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00790 | -7.90 | 0.00234 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8000.39 | 8000.39 | 326.14 | 0.419 | 0.419 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00790 | -7.90 | 0.00234 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5568.51 | 5568.51 | 16.79 | 0.290 | 1.188 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00793 | -7.90 | 0.00234 | 1.188 | 0.00 |
DINING_FLR_6 | 5704.30 | 5704.30 | 17.20 | 0.297 | 1.188 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00793 | -7.90 | 0.00234 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 2336.43 | 2336.43 | 22.62 | 0.122 | 0.367 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00740 | -7.90 | 0.00234 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 5885.12 | 5885.12 | 14.28 | 0.307 | 0.307 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00794 | -7.90 | 0.00234 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 24.61 | 24.61 | 7.40 | 7.40 | 24.6111 | 11.6572 | 24.6111 | 0.4737 | 0.3000 |
FLR_3_DOAS | 19.10 | 2.05 | 4.94 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 5044.630 | 5044.630 | 1.161633 | 0.00004413 | 105.197 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5044.63 | 5044.63 | 1.161633 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 5072.98 | 5072.98 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3175.365 | 3175.365 | 0.182647 | 0.00002778 | 78.697 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3175.36 | 3175.36 | 0.182647 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00787969 | 41.9056 | 2382.40 | 0.00 | 3191.78 | 3191.78 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1339.249 | 1339.249 | 0.121545 | 0.00001172 | 30.367 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1339.25 | 1339.25 | 0.121545 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00786402 | 41.8230 | 811.55 | 0.00 | 1346.47 | 1346.47 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1938.957 | 1938.957 | 0.101973 | 0.00001696 | 49.245 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1938.96 | 1938.96 | 0.101973 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00782684 | 41.6277 | 1496.27 | 0.00 | 1948.91 | 1948.91 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1204.682 | 1204.682 | 0.055271 | 0.00001054 | 31.956 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1204.68 | 1204.68 | 0.055271 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00784457 | 41.7208 | 964.73 | 0.00 | 1210.70 | 1210.70 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10030.770 | 10030.770 | 1.861875 | 0.00008775 | 211.818 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10030.77 | 10030.77 | 1.861875 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00781876 | 41.5856 | 1948.32 | 0.00 | 10086.90 | 10086.90 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 9494.115 | 9494.115 | 0.804817 | 0.00008306 | 217.520 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 9494.12 | 9494.12 | 0.804817 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00789412 | 41.9813 | 5999.86 | 0.00 | 9545.10 | 9545.10 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 25396.021 | 25396.021 | 2.562651 | 0.00022218 | 567.542 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 25396.02 | 25396.02 | 2.562651 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00787325 | 41.8714 | 14269.97 | 0.00 | 25533.67 | 25533.67 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12165.566 | -999.000 | 1.315611 | 0.00043452 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 12165.57 | 12036.17 | 1.315611 | 21.81 | 13.69 | 0.00855668 | 12.80 | 10.33 | 0.00850000 | 33.21 | 0.00569645 | 15.16 | 0.0000 | 21.11 | 0.00855668 | 45.1485 | 11052.25 | 0.00 | 15033.64 | 14033.97 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5320.349 | 5320.349 | 0.278890 | 0.00004654 | 152.008 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5320.35 | 5320.35 | 0.278890 | 21.11 | 12.86 | 0.00787574 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00787574 | 41.6003 | 5320.37 | 0.00 | 5735.50 | 5735.50 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 12020.662 | -999.000 | 1.299733 | 0.00042934 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 12020.66 | 11891.50 | 1.299733 | 21.81 | 13.69 | 0.00855727 | 12.80 | 10.33 | 0.00850000 | 33.21 | 0.00569645 | 15.16 | 0.0000 | 21.11 | 0.00855727 | 45.1515 | 10918.86 | 0.00 | 14854.30 | 13864.65 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5320.059 | 5320.059 | 0.278875 | 0.00004654 | 151.999 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5320.06 | 5320.06 | 0.278875 | 21.11 | 12.86 | 0.00787574 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00787574 | 41.6003 | 5320.07 | 0.00 | 5735.19 | 5735.19 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 60353.909 | -999.000 | 6.628890 | 0.00215566 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | 7/21 13:50:00 | 60353.91 | 60353.91 | 6.628890 | 21.81 | 13.63 | 0.00848803 | 12.80 | 10.32 | 0.00848803 | 34.99 | 0.00569921 | 15.74 | 0.0000 | 21.11 | 0.00848803 | 44.7901 | 55690.80 | 0.00 | 74739.08 | 70791.18 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 30845.267 | 30845.267 | 1.616906 | 0.00026985 | 881.275 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 30845.27 | 30845.27 | 1.616906 | 21.11 | 12.87 | 0.00788616 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00788616 | 41.6543 | 30845.31 | 0.00 | 33252.25 | 33252.25 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 65000.276 | -999.000 | 6.691074 | 0.00232162 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | unknown | 7/21 18:10:00 | 65000.28 | 62140.74 | 6.691074 | 21.81 | 13.84 | 0.00874260 | 12.80 | 10.33 | 0.00850000 | 31.52 | 0.00569384 | 14.61 | 0.0000 | 21.11 | 0.00874260 | 46.1168 | 56208.36 | 0.00 | 79898.95 | 71493.17 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 30854.820 | 30854.820 | 1.617407 | 0.00026993 | 881.548 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 30854.82 | 30854.82 | 1.617407 | 21.11 | 12.87 | 0.00788617 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00788617 | 41.6543 | 30854.86 | 0.00 | 33262.55 | 33262.55 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 10707.087 | -999.000 | 1.155482 | 0.00038243 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | unknown | 7/21 09:50:00 | 10707.09 | 10578.01 | 1.155482 | 21.81 | 13.69 | 0.00856433 | 12.80 | 10.33 | 0.00850000 | 29.59 | 0.00569088 | 13.95 | 0.0000 | 21.11 | 0.00856433 | 45.1883 | 9707.03 | 0.00 | 13228.15 | 12326.54 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5320.349 | 5320.349 | 0.278890 | 0.00004654 | 152.008 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5320.35 | 5320.35 | 0.278890 | 21.11 | 12.86 | 0.00787574 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00787574 | 41.6003 | 5320.37 | 0.00 | 5735.50 | 5735.50 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10612.187 | -999.000 | 1.145094 | 0.00037904 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | unknown | 7/21 09:30:00 | 10612.19 | 10483.33 | 1.145094 | 21.81 | 13.69 | 0.00856480 | 12.80 | 10.33 | 0.00850000 | 28.82 | 0.00568971 | 13.69 | 0.0000 | 21.11 | 0.00856480 | 45.1908 | 9619.76 | 0.00 | 13110.71 | 12215.77 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5320.059 | 5320.059 | 0.278875 | 0.00004654 | 151.999 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5320.06 | 5320.06 | 0.278875 | 21.11 | 12.86 | 0.00787574 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00787574 | 41.6003 | 5320.07 | 0.00 | 5735.19 | 5735.19 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 11567.970 | 11567.970 | 0.658061 | 0.00010120 | 287.521 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 11567.97 | 11567.97 | 0.658061 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00790713 | 42.0493 | 8710.71 | 0.00 | 11627.71 | 11627.71 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3243.845 | -999.000 | 0.351141 | 0.00011586 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 3243.85 | 3211.51 | 0.351141 | 21.81 | 13.68 | 0.00855308 | 12.80 | 10.33 | 0.00850000 | 33.39 | 0.00569673 | 15.22 | 0.0000 | 21.11 | 0.00855308 | 45.1297 | 2949.88 | 0.00 | 4009.04 | 3745.61 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1664.035 | 1664.035 | 0.087228 | 0.00001456 | 47.542 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1664.03 | 1664.03 | 0.087228 | 21.11 | 12.89 | 0.00790022 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00790022 | 41.7279 | 1664.04 | 0.00 | 1793.88 | 1793.88 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3199.283 | -999.000 | 0.346248 | 0.00011427 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3199.28 | 3166.96 | 0.346248 | 21.81 | 13.69 | 0.00855381 | 12.80 | 10.33 | 0.00850000 | 33.21 | 0.00569645 | 15.16 | 0.0000 | 21.11 | 0.00855381 | 45.1335 | 2908.78 | 0.00 | 3953.88 | 3693.43 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1664.974 | 1664.974 | 0.087277 | 0.00001457 | 47.569 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1664.97 | 1664.97 | 0.087277 | 21.11 | 12.89 | 0.00790028 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00790028 | 41.7283 | 1664.98 | 0.00 | 1794.89 | 1794.89 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 13394.365 | -999.000 | 1.420244 | 0.00047841 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | 7/21 13:50:00 | 13394.36 | 13072.28 | 1.420244 | 21.81 | 13.75 | 0.00862990 | 12.80 | 10.33 | 0.00850000 | 34.99 | 0.00569921 | 15.74 | 0.0000 | 21.11 | 0.00862990 | 45.5302 | 11930.89 | 0.00 | 16517.36 | 15159.79 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 8000.373 | 8000.373 | 0.419377 | 0.00006999 | 228.575 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 8000.37 | 8000.37 | 0.419377 | 21.11 | 12.89 | 0.00790436 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00790436 | 41.7494 | 8000.39 | 0.00 | 8624.66 | 8624.66 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10887.056 | 10887.056 | 1.224897 | 0.00009524 | 240.117 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 10887.06 | 10887.06 | 1.224897 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00792642 | 42.1506 | 5568.51 | 0.00 | 10946.37 | 10946.37 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11288.024 | 11288.024 | 1.285966 | 0.00009875 | 248.610 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 11288.02 | 11288.02 | 1.285966 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00792815 | 42.1597 | 5704.30 | 0.00 | 11349.56 | 11349.56 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 7721.859 | 7721.859 | 1.241937 | 0.00006755 | 164.720 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 7721.86 | 7721.86 | 1.241937 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00739599 | 39.3668 | 2336.43 | 0.00 | 7764.92 | 7764.92 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7595.637 | 7595.637 | 0.393932 | 0.00006645 | 193.702 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 7595.64 | 7595.64 | 0.393932 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00793886 | 42.2159 | 5885.12 | 0.00 | 7634.58 | 7634.58 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 463959.271 | -999.000 | 24.611144 | 0.01657155 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 463959.27 | 463959.25 | 24.611144 | 29.25 | 15.56 | 0.00781862 | 10.58 | 8.78 | 0.00781862 | 35.10 | 0.00569938 | 15.77 | 47.3828 | 23.99 | 0.00972337 | 42.9891 | 278391.31 | 0.00 | 541304.53 | 500996.18 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 180762.214 | 180762.214 | 7.383343 | 0.00158139 | 3024.968 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 180762.21 | 180762.21 | 7.383343 | -7.90 | -7.90 | 0.00234317 | 16.70 | 11.36 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 157.9428 | 21.12 | 0.00692469 | 36.6189 | 55731.19 | 0.00 | 159660.69 | 159660.69 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 48199.928 | -999.000 | 2.051317 | 0.00172159 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 48199.93 | 48199.93 | 2.051317 | 35.10 | 15.77 | 0.00569938 | 11.74 | 7.07 | 0.00569938 | 35.10 | 0.00569938 | 15.77 | 99.9965 | 21.11 | 0.00861749 | 45.4650 | 160429.88 | 0.00 | 48236.96 | 48236.96 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 15066.372 | 15066.372 | 0.615395 | 0.00013181 | 252.128 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 15066.37 | 15066.37 | 0.615395 | -7.90 | -7.90 | 0.00234317 | 16.70 | 11.36 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 333.3216 | 21.11 | 0.00788626 | 41.6548 | 94310.46 | 0.00 | 13307.58 | 13307.58 |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 46409.656 | 34157.507 | 4.903586 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 75921.46 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | 36680.052 | 26996.518 | 3.872570 | -999.0 | -999.000 | unknown | unknown | unknown | unknown | 54370.95 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.00 | -999.0 | -999.00 | -999.0000 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 5044.630 | 5044.630 | 1.161633 | 0.00004413 | 105.197 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 1.2462 | 1.271254 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5044.63 | 5044.63 | 1.0000 | 1.15049165 | 1.161633 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.04412812 | 60.00 | 32.22 | 27.78 | 0.000 | 5044.63 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 5072.98 | 5072.98 | 1.15049165 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3175.365 | 3175.365 | 0.182647 | 0.00002778 | 78.697 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 0.7844 | 0.800196 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3175.36 | 3175.36 | 1.0000 | 0.18089496 | 0.182647 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.02777664 | 60.00 | 32.22 | 27.78 | 0.000 | 3175.36 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00787969 | 21.00 | 0.00787969 | 41.9056 | 2382.40 | 0.00 | 3191.78 | 3191.78 | 0.18089496 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 33.90 | 19.31 | 0.00800000 | 54579.1 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1339.249 | 1339.249 | 0.121545 | 0.00001172 | 30.367 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 0.3308 | 0.337493 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1339.25 | 1339.25 | 1.0000 | 0.12037955 | 0.121545 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01171514 | 60.00 | 32.22 | 27.78 | 0.000 | 1339.25 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00786402 | 21.00 | 0.00786402 | 41.8230 | 811.55 | 0.00 | 1346.47 | 1346.47 | 0.12037955 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.57 | 17.21 | 0.00800000 | 48119.9 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1938.957 | 1938.957 | 0.101973 | 0.00001696 | 49.245 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 0.4790 | 0.488620 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1938.96 | 1938.96 | 1.0000 | 0.10099478 | 0.101973 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01696111 | 60.00 | 32.22 | 27.78 | 0.000 | 1938.96 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00782684 | 21.00 | 0.00782684 | 41.6277 | 1496.27 | 0.00 | 1948.91 | 1948.91 | 0.10099478 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.52 | 19.82 | 0.00800000 | 56231.8 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1204.682 | 1204.682 | 0.055271 | 0.00001054 | 31.956 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 0.2976 | 0.303582 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1204.68 | 1204.68 | 1.0000 | 0.05474131 | 0.055271 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01053801 | 60.00 | 32.22 | 27.78 | 0.000 | 1204.68 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00784457 | 21.00 | 0.00784457 | 41.7208 | 964.73 | 0.00 | 1210.70 | 1210.70 | 0.05474131 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 38.29 | 20.67 | 0.00800000 | 59051.5 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10030.770 | 10030.770 | 1.861875 | 0.00008775 | 211.818 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 2.4779 | 2.527768 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10030.77 | 10030.77 | 1.0000 | 1.84401777 | 1.861875 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.08774460 | 60.00 | 32.22 | 27.78 | 0.000 | 10030.77 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00781876 | 21.00 | 0.00781876 | 41.5856 | 1948.32 | 0.00 | 10086.90 | 10086.90 | 1.84401777 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.96 | 15.21 | 0.00800000 | 42404.8 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9494.115 | 9494.115 | 0.804817 | 0.00008306 | 217.520 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 2.3453 | 2.392530 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 9494.12 | 9494.12 | 1.0000 | 0.79709746 | 0.804817 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.08305019 | 60.00 | 32.22 | 27.78 | 0.000 | 9494.12 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00789412 | 21.00 | 0.00789412 | 41.9813 | 5999.86 | 0.00 | 9545.10 | 9545.10 | 0.79709746 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.34 | 17.48 | 0.00800000 | 48909.6 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25396.021 | 25396.021 | 2.562651 | 0.00022218 | 567.542 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 6.2736 | 6.399833 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 25396.02 | 25396.02 | 1.0000 | 2.53807265 | 2.562651 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.22215281 | 60.00 | 32.22 | 27.78 | 0.000 | 25396.02 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00787325 | 21.00 | 0.00787325 | 41.8714 | 14269.97 | 0.00 | 25533.67 | 25533.67 | 2.53807265 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.47 | 16.83 | 0.00800000 | 46995.0 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12165.566 | -999.000 | 1.315611 | 0.00043452 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7464 | 1004.8586 | 0.9904 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.315611 | 1.30299293 | 4197.9300 | 999.8980 | 25.10171325 | 13.37 | 6.70 | 6.67 | 702852.82 | 1.7309 | 1.730852 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 12165.57 | 12036.17 | 1.0000 | 1.30299293 | 1.315611 | 21.81 | 13.69 | 0.00855668 | 43658.8 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.43447338 | 6.70 | 13.37 | 6.67 | 0.000 | 12165.57 | 33.21 | 0.00569645 | 15.16 | 0.00000000 | 0.0000 | 21.11 | 0.00855668 | 21.11 | 0.00855668 | 45.1485 | 11052.25 | 0.00 | 15033.64 | 14033.97 | 1.30299293 | 21.81 | 15.65 | 0.00855668 | 43658.8 | 11.26 | 11.20 | 0.00825246 | 32121.1 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5320.349 | 5320.349 | 0.278890 | 0.00004654 | 152.008 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.315611 | 1.30299293 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 1.3143 | 1.340735 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5320.35 | 5320.35 | 1.0000 | 0.27621533 | 0.278890 | 21.11 | 12.86 | 0.00787574 | 41218.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.04653999 | 60.00 | 32.22 | 27.78 | 0.000 | 5320.35 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00787574 | 21.11 | 0.00787574 | 41.6003 | 5320.37 | 0.00 | 5735.50 | 5735.50 | 0.27621533 | 16.60 | 13.03 | 0.00787574 | 36620.1 | 36.97 | 20.18 | 0.00787574 | 57384.7 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12020.662 | -999.000 | 1.299733 | 0.00042934 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7475 | 1004.8586 | 0.9904 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.299733 | 1.28726749 | 4197.9300 | 999.8980 | 25.10171325 | 13.37 | 6.70 | 6.67 | 702852.82 | 1.7103 | 1.710235 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 12020.66 | 11891.50 | 1.0000 | 1.28726749 | 1.299733 | 21.81 | 13.69 | 0.00855727 | 43660.3 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.42929837 | 6.70 | 13.37 | 6.67 | 0.000 | 12020.66 | 33.21 | 0.00569645 | 15.16 | 0.00000000 | 0.0000 | 21.11 | 0.00855727 | 21.11 | 0.00855727 | 45.1515 | 10918.86 | 0.00 | 14854.30 | 13864.65 | 1.28726749 | 21.81 | 15.65 | 0.00855727 | 43660.3 | 11.25 | 11.20 | 0.00825241 | 32120.9 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5320.059 | 5320.059 | 0.278875 | 0.00004654 | 151.999 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.299733 | 1.28726749 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 1.3142 | 1.340662 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5320.06 | 5320.06 | 1.0000 | 0.27620025 | 0.278875 | 21.11 | 12.86 | 0.00787574 | 41218.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.04653745 | 60.00 | 32.22 | 27.78 | 0.000 | 5320.06 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00787574 | 21.11 | 0.00787574 | 41.6003 | 5320.07 | 0.00 | 5735.19 | 5735.19 | 0.27620025 | 16.60 | 13.03 | 0.00787574 | 36620.1 | 36.97 | 20.18 | 0.00787574 | 57384.8 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 60353.909 | -999.000 | 6.628890 | 0.00215566 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6188 | 1004.8586 | 0.9904 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.628890 | 6.56531203 | 4197.9300 | 999.8980 | 25.10171325 | 13.37 | 6.70 | 6.67 | 702852.82 | 8.5870 | 8.586831 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | unknown | unknown | 7/21 13:50:00 | Sensible | 60353.91 | 60353.91 | 1.0000 | 6.56531203 | 6.628890 | 21.81 | 13.63 | 0.00848803 | 43484.8 | 12.80 | 10.32 | 0.00848803 | 34292.0 | 2.15544162 | 6.70 | 13.37 | 6.67 | 0.000 | 60353.91 | 34.99 | 0.00569921 | 15.74 | 0.00000000 | 0.0000 | 21.11 | 0.00848803 | 21.11 | 0.00848803 | 44.7901 | 55690.80 | 0.00 | 74739.08 | 70791.18 | 6.56531203 | 21.81 | 15.59 | 0.00848803 | 43484.8 | 11.24 | 11.19 | 0.00824958 | 32100.9 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30845.267 | 30845.267 | 1.616906 | 0.00026985 | 881.275 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.628890 | 6.56531203 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 7.6197 | 7.773050 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 30845.27 | 30845.27 | 1.0000 | 1.60139836 | 1.616906 | 21.11 | 12.87 | 0.00788616 | 41245.4 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.26982032 | 60.00 | 32.22 | 27.78 | 0.000 | 30845.27 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00788616 | 21.11 | 0.00788616 | 41.6543 | 30845.31 | 0.00 | 33252.25 | 33252.25 | 1.60139836 | 16.60 | 13.04 | 0.00788616 | 36646.5 | 36.97 | 20.18 | 0.00788616 | 57411.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 65000.276 | -999.000 | 6.691074 | 0.00232162 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0921 | 1004.8586 | 0.9904 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.691074 | 6.62689969 | 4197.9300 | 999.8980 | 25.10171325 | 13.37 | 6.70 | 6.67 | 702852.82 | 9.2481 | 9.247891 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | unknown | unknown | unknown | 7/21 18:10:00 | Sensible | 65000.28 | 62140.74 | 1.0000 | 6.62689969 | 6.691074 | 21.81 | 13.84 | 0.00874260 | 44130.7 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 2.32137908 | 6.70 | 13.37 | 6.67 | 0.000 | 65000.28 | 31.52 | 0.00569384 | 14.61 | 0.00000000 | 0.0000 | 21.11 | 0.00874260 | 21.11 | 0.00874260 | 46.1168 | 56208.36 | 0.00 | 79898.95 | 71493.17 | 6.62689969 | 21.81 | 15.81 | 0.00874260 | 44130.7 | 11.24 | 11.18 | 0.00823962 | 32074.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30854.820 | 30854.820 | 1.617407 | 0.00026993 | 881.548 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.691074 | 6.62689969 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 7.6221 | 7.775458 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 30854.82 | 30854.82 | 1.0000 | 1.60189434 | 1.617407 | 21.11 | 12.87 | 0.00788617 | 41245.4 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.26990389 | 60.00 | 32.22 | 27.78 | 0.000 | 30854.82 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00788617 | 21.11 | 0.00788617 | 41.6543 | 30854.86 | 0.00 | 33262.55 | 33262.55 | 1.60189434 | 16.60 | 13.04 | 0.00788617 | 36646.5 | 36.97 | 20.18 | 0.00788617 | 57411.0 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10707.087 | -999.000 | 1.155482 | 0.00038243 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7607 | 1004.8586 | 0.9904 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.155482 | 1.14439999 | 4197.9300 | 999.8980 | 25.10171325 | 13.37 | 6.70 | 6.67 | 702852.82 | 1.5234 | 1.523347 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | unknown | unknown | unknown | 7/21 09:50:00 | Sensible | 10707.09 | 10578.01 | 1.0000 | 1.14439999 | 1.155482 | 21.81 | 13.69 | 0.00856433 | 43678.3 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.38238620 | 6.70 | 13.37 | 6.67 | 0.000 | 10707.09 | 29.59 | 0.00569088 | 13.95 | 0.00000000 | 0.0000 | 21.11 | 0.00856433 | 21.11 | 0.00856433 | 45.1883 | 9707.03 | 0.00 | 13228.15 | 12326.54 | 1.14439999 | 21.81 | 15.66 | 0.00856433 | 43678.3 | 11.25 | 11.20 | 0.00825193 | 32119.2 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5320.349 | 5320.349 | 0.278890 | 0.00004654 | 152.008 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.155482 | 1.14439999 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 1.3143 | 1.340735 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5320.35 | 5320.35 | 1.0000 | 0.27621533 | 0.278890 | 21.11 | 12.86 | 0.00787574 | 41218.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.04653999 | 60.00 | 32.22 | 27.78 | 0.000 | 5320.35 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00787574 | 21.11 | 0.00787574 | 41.6003 | 5320.37 | 0.00 | 5735.50 | 5735.50 | 0.27621533 | 16.60 | 13.03 | 0.00787574 | 36620.1 | 36.97 | 20.18 | 0.00787574 | 57384.7 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10612.187 | -999.000 | 1.145094 | 0.00037904 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7615 | 1004.8586 | 0.9904 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.145094 | 1.13411176 | 4197.9300 | 999.8980 | 25.10171325 | 13.37 | 6.70 | 6.67 | 702852.82 | 1.5099 | 1.509845 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | unknown | unknown | unknown | 7/21 09:30:00 | Sensible | 10612.19 | 10483.33 | 1.0000 | 1.13411176 | 1.145094 | 21.81 | 13.69 | 0.00856480 | 43679.5 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.37899700 | 6.70 | 13.37 | 6.67 | 0.000 | 10612.19 | 28.82 | 0.00568971 | 13.69 | 0.00000000 | 0.0000 | 21.11 | 0.00856480 | 21.11 | 0.00856480 | 45.1908 | 9619.76 | 0.00 | 13110.71 | 12215.77 | 1.13411176 | 21.81 | 15.66 | 0.00856480 | 43679.5 | 11.25 | 11.20 | 0.00825190 | 32119.1 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5320.059 | 5320.059 | 0.278875 | 0.00004654 | 151.999 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.145094 | 1.13411176 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 1.3142 | 1.340662 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5320.06 | 5320.06 | 1.0000 | 0.27620025 | 0.278875 | 21.11 | 12.86 | 0.00787574 | 41218.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.04653745 | 60.00 | 32.22 | 27.78 | 0.000 | 5320.06 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00787574 | 21.11 | 0.00787574 | 41.6003 | 5320.07 | 0.00 | 5735.19 | 5735.19 | 0.27620025 | 16.60 | 13.03 | 0.00787574 | 36620.1 | 36.97 | 20.18 | 0.00787574 | 57384.8 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11567.970 | 11567.970 | 0.658061 | 0.00010120 | 287.521 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 2.8576 | 2.915145 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 11567.97 | 11567.97 | 1.0000 | 0.65174983 | 0.658061 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.10119132 | 60.00 | 32.22 | 27.78 | 0.000 | 11567.97 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00790713 | 21.00 | 0.00790713 | 42.0493 | 8710.71 | 0.00 | 11627.71 | 11627.71 | 0.65174983 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.10 | 19.37 | 0.00800000 | 54775.5 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3243.845 | -999.000 | 0.351141 | 0.00011586 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7397 | 1004.8586 | 0.9904 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.351141 | 0.34777273 | 4197.9300 | 999.8980 | 25.10171325 | 13.37 | 6.70 | 6.67 | 702852.82 | 0.4615 | 0.461517 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 3243.85 | 3211.51 | 1.0000 | 0.34777273 | 0.351141 | 21.81 | 13.68 | 0.00855308 | 43649.7 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.11584865 | 6.70 | 13.37 | 6.67 | 0.000 | 3243.85 | 33.39 | 0.00569673 | 15.22 | 0.00000000 | 0.0000 | 21.11 | 0.00855308 | 21.11 | 0.00855308 | 45.1297 | 2949.88 | 0.00 | 4009.04 | 3745.61 | 0.34777273 | 21.81 | 15.65 | 0.00855308 | 43649.7 | 11.26 | 11.20 | 0.00825270 | 32121.9 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1664.035 | 1664.035 | 0.087228 | 0.00001456 | 47.542 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.351141 | 0.34777273 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 0.4111 | 0.419339 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1664.03 | 1664.03 | 1.0000 | 0.08639132 | 0.087228 | 21.11 | 12.89 | 0.00790022 | 41280.9 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01455621 | 60.00 | 32.22 | 27.78 | 0.000 | 1664.03 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00790022 | 21.11 | 0.00790022 | 41.7279 | 1664.04 | 0.00 | 1793.88 | 1793.88 | 0.08639132 | 16.60 | 13.05 | 0.00790022 | 36682.1 | 36.97 | 20.19 | 0.00790022 | 57446.7 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3199.283 | -999.000 | 0.346248 | 0.00011427 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7411 | 1004.8586 | 0.9904 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.346248 | 0.34292669 | 4197.9300 | 999.8980 | 25.10171325 | 13.37 | 6.70 | 6.67 | 702852.82 | 0.4552 | 0.455177 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 3199.28 | 3166.96 | 1.0000 | 0.34292669 | 0.346248 | 21.81 | 13.69 | 0.00855381 | 43651.5 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.11425720 | 6.70 | 13.37 | 6.67 | 0.000 | 3199.28 | 33.21 | 0.00569645 | 15.16 | 0.00000000 | 0.0000 | 21.11 | 0.00855381 | 21.11 | 0.00855381 | 45.1335 | 2908.78 | 0.00 | 3953.88 | 3693.43 | 0.34292669 | 21.81 | 15.65 | 0.00855381 | 43651.5 | 11.26 | 11.20 | 0.00825265 | 32121.7 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1664.974 | 1664.974 | 0.087277 | 0.00001457 | 47.569 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.346248 | 0.34292669 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 0.4113 | 0.419576 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1664.97 | 1664.97 | 1.0000 | 0.08644011 | 0.087277 | 21.11 | 12.89 | 0.00790028 | 41281.1 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01456443 | 60.00 | 32.22 | 27.78 | 0.000 | 1664.97 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00790028 | 21.11 | 0.00790028 | 41.7283 | 1664.98 | 0.00 | 1794.89 | 1794.89 | 0.08644011 | 16.60 | 13.05 | 0.00790028 | 36682.3 | 36.97 | 20.19 | 0.00790028 | 57446.9 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13394.365 | -999.000 | 1.420244 | 0.00047841 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8825 | 1004.8586 | 0.9904 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.420244 | 1.40662252 | 4197.9300 | 999.8980 | 25.10171325 | 13.37 | 6.70 | 6.67 | 702852.82 | 1.9057 | 1.905678 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | unknown | unknown | 7/21 13:50:00 | Sensible | 13394.36 | 13072.28 | 1.0000 | 1.40662252 | 1.420244 | 21.81 | 13.75 | 0.00862990 | 43844.6 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.47835793 | 6.70 | 13.37 | 6.67 | 0.000 | 13394.36 | 34.99 | 0.00569921 | 15.74 | 0.00000000 | 0.0000 | 21.11 | 0.00862990 | 21.11 | 0.00862990 | 45.5302 | 11930.89 | 0.00 | 16517.36 | 15159.79 | 1.40662252 | 21.81 | 15.71 | 0.00862990 | 43844.6 | 11.25 | 11.19 | 0.00824719 | 32102.0 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8000.373 | 8000.373 | 0.419377 | 0.00006999 | 228.575 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.420244 | 1.40662252 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 1.9763 | 2.016105 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 8000.37 | 8000.37 | 1.0000 | 0.41535474 | 0.419377 | 21.11 | 12.89 | 0.00790436 | 41291.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.06998362 | 60.00 | 32.22 | 27.78 | 0.000 | 8000.37 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00790436 | 21.11 | 0.00790436 | 41.7494 | 8000.39 | 0.00 | 8624.66 | 8624.66 | 0.41535474 | 16.60 | 13.06 | 0.00790436 | 36692.6 | 36.97 | 20.20 | 0.00790436 | 57457.2 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10887.056 | 10887.056 | 1.224897 | 0.00009524 | 240.117 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 2.6894 | 2.743553 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 10887.06 | 10887.06 | 1.0000 | 1.21314896 | 1.224897 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.09523500 | 60.00 | 32.22 | 27.78 | 0.000 | 10887.06 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00792642 | 21.00 | 0.00792642 | 42.1506 | 5568.51 | 0.00 | 10946.37 | 10946.37 | 1.21314896 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.45 | 16.47 | 0.00800000 | 45957.8 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11288.024 | 11288.024 | 1.285966 | 0.00009875 | 248.610 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 2.7885 | 2.844598 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 11288.02 | 11288.02 | 1.0000 | 1.27363233 | 1.285966 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.09874249 | 60.00 | 32.22 | 27.78 | 0.000 | 11288.02 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00792815 | 21.00 | 0.00792815 | 42.1597 | 5704.30 | 0.00 | 11349.56 | 11349.56 | 1.27363233 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.34 | 16.43 | 0.00800000 | 45845.9 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7721.859 | 7721.859 | 1.241937 | 0.00006755 | 164.720 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 1.9075 | 1.945919 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 7721.86 | 7721.86 | 1.0000 | 1.23002570 | 1.241937 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.06754730 | 60.00 | 32.22 | 27.78 | 0.000 | 7721.86 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.57 | 0.00739599 | 21.00 | 0.00739599 | 39.3668 | 2336.43 | 0.00 | 7764.92 | 7764.92 | 1.23002570 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.79 | 15.52 | 0.00800000 | 43247.5 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7595.637 | 7595.637 | 0.393932 | 0.00006645 | 193.702 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 1.8763 | 1.914111 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 7595.64 | 7595.64 | 1.0000 | 0.39015396 | 0.393932 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.06644317 | 60.00 | 32.22 | 27.78 | 0.000 | 7595.64 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00793886 | 21.00 | 0.00793886 | 42.2159 | 5885.12 | 0.00 | 7634.58 | 7634.58 | 0.39015396 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 35.79 | 19.90 | 0.00800000 | 56502.8 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 463959.271 | -999.000 | 24.611144 | 0.01657155 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3744 | 1004.8586 | 0.9904 | VAV WITH REHEAT FAN | Fan:VariableVolume | 24.611144 | 24.37509629 | 4197.9300 | 999.8980 | 25.10171325 | 13.37 | 6.70 | 6.67 | 702852.82 | 66.0109 | 66.010872 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | Sensible | 463959.27 | 463959.25 | 1.0000 | 24.37509629 | 24.611144 | 29.25 | 15.56 | 0.00781862 | 49373.7 | 10.58 | 8.78 | 0.00781862 | 30339.6 | 16.56985969 | 6.70 | 13.37 | 6.67 | 55144.680 | 408814.59 | 35.10 | 0.00569938 | 15.77 | 11.66146000 | 47.3828 | 23.99 | 0.00972705 | 23.99 | 0.00972337 | 42.9891 | 278391.31 | 0.00 | 541304.53 | 500996.18 | 24.37509629 | 29.25 | 17.64 | 0.00781862 | 49373.7 | 9.09 | 9.08 | 0.00716184 | 27166.4 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 180762.214 | 180762.214 | 7.383343 | 0.00158139 | 3024.968 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV WITH REHEAT FAN | Fan:VariableVolume | 24.611144 | 24.37509629 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 44.6537 | 45.552329 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 180762.21 | 180762.21 | 1.0000 | 7.31252889 | 7.383343 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 1.58122538 | 60.00 | 32.22 | 27.78 | 0.000 | 180762.21 | -7.90 | 0.00234317 | -7.90 | 11.66146000 | 157.9428 | 18.56 | 0.00723455 | 21.12 | 0.00692469 | 36.6189 | 55731.19 | 0.00 | 159660.69 | 159660.69 | 7.31252889 | 2.80 | -0.65 | 0.00234317 | 8685.9 | 24.43 | 10.64 | 0.00234317 | 30519.7 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 48199.928 | -999.000 | 2.051317 | 0.00172159 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1015.4349 | 1004.8586 | 0.9904 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.03157141 | 4197.9300 | 999.8980 | 25.10171325 | 13.37 | 6.70 | 6.67 | 702852.82 | 6.8578 | 6.857756 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 48199.93 | 48199.93 | 1.0000 | 2.03164284 | 2.051317 | 35.10 | 15.77 | 0.00569938 | 49895.6 | 11.74 | 7.07 | 0.00569938 | 26171.0 | 1.72141413 | 6.70 | 13.37 | 6.67 | 2195.006 | 46004.92 | 35.10 | 0.00569938 | 15.77 | 2.05124512 | 99.9965 | 21.11 | 0.00860812 | 21.11 | 0.00861749 | 45.4650 | 160429.88 | 0.00 | 48236.96 | 48236.96 | 2.03164284 | 35.10 | 17.86 | 0.00569938 | 49895.6 | 11.72 | 8.65 | 0.00569938 | 26152.7 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 15066.372 | 15066.372 | 0.615395 | 0.00013181 | 252.128 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.03157141 | 4197.9300 | 999.8980 | 3.47122839 | 54.44 | 82.22 | 27.78 | 404809.43 | 3.7218 | 3.796747 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 15066.37 | 15066.37 | 1.0000 | 0.60949285 | 0.615395 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 0.13179374 | 60.00 | 32.22 | 27.78 | 0.000 | 15066.37 | -7.90 | 0.00234317 | -7.90 | 2.05124512 | 333.3216 | 21.11 | 0.00788585 | 21.11 | 0.00788626 | 41.6548 | 94310.46 | 0.00 | 13307.58 | 13307.58 | 0.60949285 | 2.80 | -0.65 | 0.00234317 | 8685.9 | 24.43 | 10.64 | 0.00234317 | 30519.7 | |
SWHSYSLAUNDRY HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 46409.656 | 34157.507 | 4.903586 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 0.9904 | SWHSYSLAUNDRY HPWH FAN | Fan:SystemModel | 4.903586 | 4.85655568 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 75921.46 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 75921.46 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
SWHSYS1 HPWH DXCOIL | Coil:WaterHeating:AirToWaterHeatPump:Pumped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 36680.052 | 26996.518 | 3.872570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1004.8586 | 1004.8586 | 0.9904 | SWHSYS1 HPWH FAN | Fan:SystemModel | 3.872570 | 3.83542732 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 54370.95 | -999.00 | 1.0000 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54370.95 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | -999.0 | -999.00 | -999.0 | -999.0000 | -999.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 24.61 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1058.83 | 7052.33 | 600.50 |
RETAIL_1_FLR_1 | 2609.83 | 5427.17 | 566.00 |
RETAIL_2_FLR_1 | 2132.50 | 5973.33 | 596.00 |
MECH_FLR_1 | 1222.67 | 6805.67 | 329.50 |
STORAGE_FLR_1 | 1139.67 | 7081.33 | 403.83 |
LAUNDRY_FLR_1 | 7780.00 | 3241.17 | 2858.83 |
CAFE_FLR_1 | 4129.33 | 3648.83 | 973.00 |
LOBBY_FLR_1 | 2788.83 | 4187.00 | 862.83 |
ROOM_1_FLR_3 | 570.00 | 7924.33 | 328.17 |
ROOM_2_FLR_3 | 1532.50 | 7738.00 | 1141.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 350.83 | 8717.00 | 346.67 |
ROOM_5_FLR_3 | 530.83 | 7804.83 | 336.83 |
ROOM_6_FLR_3 | 1549.50 | 7660.17 | 1228.33 |
CORRIDOR_FLR_3 | 1430.17 | 7088.67 | 796.17 |
ROOM_1_FLR_6 | 1306.33 | 7795.50 | 937.67 |
ROOM_2_FLR_6 | 2606.00 | 7624.33 | 2109.67 |
ROOM_3_MULT9_FLR_6 | 513.67 | 7551.17 | 106.33 |
BANQUET_FLR_6 | 3597.33 | 2948.00 | 908.50 |
DINING_FLR_6 | 3904.50 | 1723.67 | 864.67 |
KITCHEN_FLR_6 | 8353.83 | 6366.33 | 6331.67 |
CORRIDOR_FLR_6 | 1688.17 | 6548.67 | 448.00 |
Facility | 8736.50 | 8760.00 | 7518.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 7.50 | 0.00 | 7.50 |
ROOM_2_FLR_3 | 0.00 | 6.67 | 0.00 | 6.67 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 13.17 | 0.00 | 13.17 |
ROOM_5_FLR_3 | 0.00 | 5.00 | 0.00 | 5.00 |
ROOM_6_FLR_3 | 0.00 | 35.83 | 0.00 | 35.83 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 12.67 | 0.00 | 12.67 |
ROOM_2_FLR_6 | 0.00 | 12.00 | 0.00 | 12.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 19.17 | 0.00 | 19.17 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 78.83 | 0.00 | 78.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.926 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.786 | 0.034 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.540 | 0.011 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.582 | 0.013 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.537 | 0.013 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 26.524 | 0.037 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 4.506 | 0.027 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 2.034 | 0.011 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.044 | 0.000 | 0.058 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.354 | 0.044 | 0.000 | 0.057 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.401 | 0.020 | 0.000 | 0.094 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.354 | 0.044 | 0.000 | 0.058 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.354 | 0.044 | 0.000 | 0.057 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.512 | 0.005 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.354 | 0.044 | 0.000 | 0.070 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.354 | 0.044 | 0.000 | 0.064 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.402 | 0.036 | 0.000 | 0.111 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 5.691 | 0.013 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 6.151 | 0.013 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 25.137 | 0.037 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.180 | 0.009 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.486 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.600 | 0.001 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.098 | 0.000 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.472 | 0.000 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.418 | 0.000 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 13.713 | 0.001 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 2.818 | 0.000 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.375 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.000 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.372 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.097 | 0.000 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.317 | 0.000 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 11.265 | 0.001 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.758 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.80 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.58 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.14 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.39 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 38588464.27 | 0.00 | 38588464.27 | 0.00 | 38588464.27 | 26946214.98 | 155.15 | 11.79 | 8593.06 | 0.00 |
RETAIL_1_FLR_1 | 6408692.34 | 0.00 | 6408692.34 | 78993.97 | 6487686.31 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 4090946.49 | 0.00 | 4090946.49 | 30491.77 | 4121438.26 | 2892943.94 | 0.00 | 0.33 | 8759.67 | 0.00 |
MECH_FLR_1 | 3280685.17 | 0.00 | 3280685.17 | 72064.44 | 3352749.61 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1746638.53 | 0.00 | 1746638.53 | 41577.21 | 1788215.74 | 1821682.01 | 8435.99 | 78.44 | 245.57 | 0.00 |
LAUNDRY_FLR_1 | 70903723.03 | 0.00 | 70903723.03 | 98400.31 | 71002123.34 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 29062346.15 | 0.00 | 29062346.15 | 174620.65 | 29236966.80 | 21330615.53 | 94.99 | 14.87 | 8650.14 | 0.00 |
LOBBY_FLR_1 | 90795298.95 | 0.00 | 90795298.95 | 498931.07 | 91294230.02 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1460156.71 | 59840.54 | 1519997.25 | 45850.46 | 1565847.72 | 1946875.62 | 2190.00 | 5920.33 | 649.67 | 0.00 |
ROOM_2_FLR_3 | 1459985.63 | 58631.29 | 1518616.93 | 45846.96 | 1564463.89 | 1946647.51 | 2190.00 | 5960.36 | 609.64 | 0.00 |
ROOM_3_MULT19_FLR_3 | 1099911.97 | 0.00 | 1099911.97 | 12792.79 | 1112704.76 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 365.00 |
ROOM_4_MULT19_FLR_3 | 19803829.30 | 60676.35 | 19864505.64 | 12796.29 | 19877301.94 | 26405105.73 | 2190.00 | 5937.01 | 632.99 | 0.00 |
ROOM_5_FLR_3 | 1460156.71 | 59994.84 | 1520151.55 | 45850.46 | 1566002.02 | 1946875.62 | 2190.00 | 5920.33 | 649.67 | 0.00 |
ROOM_6_FLR_3 | 1459985.63 | 58320.48 | 1518306.11 | 45846.96 | 1564153.08 | 1946647.51 | 2189.83 | 5941.47 | 628.70 | 0.00 |
CORRIDOR_FLR_3 | 21036718.50 | 0.00 | 21036718.50 | 55442.43 | 21092160.94 | 14972100.18 | 0.00 | 0.33 | 8759.67 | 0.00 |
ROOM_1_FLR_6 | 365039.18 | 71774.41 | 436813.59 | 45859.99 | 482673.58 | 486718.90 | 2049.72 | 5921.09 | 789.19 | 0.00 |
ROOM_2_FLR_6 | 364996.41 | 65920.99 | 430917.40 | 45856.49 | 476773.89 | 486661.88 | 2073.04 | 5980.63 | 706.33 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2345190.31 | 71777.08 | 2416967.39 | 23463.58 | 2440430.97 | 3126920.42 | 2190.00 | 5919.50 | 650.50 | 0.00 |
BANQUET_FLR_6 | 49506635.84 | 0.00 | 49506635.84 | 111978.57 | 49618614.42 | 37458366.31 | 5.67 | 6.17 | 8748.17 | 0.00 |
DINING_FLR_6 | 53515628.90 | 0.00 | 53515628.90 | 111978.57 | 53627607.47 | 37458366.31 | 0.00 | 0.67 | 8759.33 | 0.00 |
KITCHEN_FLR_6 | 68178296.49 | 0.00 | 68178296.49 | 100246.78 | 68278543.28 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 12834387.21 | 0.00 | 12834387.21 | 98115.96 | 12932503.17 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.21E+10 | 6342240.28 | 0.22E+10 | 4620407.55 | 0.22E+10 | 0.43E+10 | 8760.00 | 6405.90 | 8760.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.2236 | 0.0000 | 1.2236 | 0.0000 | 1.2236 | 0.8545 | 155.15 | 11.79 | 8593.06 |
RETAIL_1_FLR_1 | 0.2032 | 0.0000 | 0.2032 | 0.0025 | 0.2057 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1297 | 0.0000 | 0.1297 | 0.0010 | 0.1307 | 0.0917 | 0.00 | 0.33 | 8759.67 |
MECH_FLR_1 | 0.1040 | 0.0000 | 0.1040 | 0.0023 | 0.1063 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0554 | 0.0000 | 0.0554 | 0.0013 | 0.0567 | 0.0578 | 8435.99 | 78.44 | 245.57 |
LAUNDRY_FLR_1 | 2.2483 | 0.0000 | 2.2483 | 0.0031 | 2.2515 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 0.9216 | 0.0000 | 0.9216 | 0.0055 | 0.9271 | 0.6764 | 94.99 | 14.87 | 8650.14 |
LOBBY_FLR_1 | 2.8791 | 0.0000 | 2.8791 | 0.0158 | 2.8949 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0463 | 0.0019 | 0.0482 | 0.0015 | 0.0497 | 0.0617 | 2190.00 | 5920.33 | 649.67 |
ROOM_2_FLR_3 | 0.0463 | 0.0019 | 0.0482 | 0.0015 | 0.0496 | 0.0617 | 2190.00 | 5960.36 | 609.64 |
ROOM_4_MULT19_FLR_3 | 0.6280 | 0.0019 | 0.6299 | 0.0004 | 0.6303 | 0.8373 | 2190.00 | 5937.01 | 632.99 |
ROOM_5_FLR_3 | 0.0463 | 0.0019 | 0.0482 | 0.0015 | 0.0497 | 0.0617 | 2190.00 | 5920.33 | 649.67 |
ROOM_6_FLR_3 | 0.0463 | 0.0018 | 0.0481 | 0.0015 | 0.0496 | 0.0617 | 2189.83 | 5941.47 | 628.70 |
CORRIDOR_FLR_3 | 0.6671 | 0.0000 | 0.6671 | 0.0018 | 0.6688 | 0.4748 | 0.00 | 0.33 | 8759.67 |
ROOM_1_FLR_6 | 0.0116 | 0.0023 | 0.0139 | 0.0015 | 0.0153 | 0.0154 | 2049.72 | 5921.09 | 789.19 |
ROOM_2_FLR_6 | 0.0116 | 0.0021 | 0.0137 | 0.0015 | 0.0151 | 0.0154 | 2073.04 | 5980.63 | 706.33 |
ROOM_3_MULT9_FLR_6 | 0.0744 | 0.0023 | 0.0766 | 0.0007 | 0.0774 | 0.0992 | 2190.00 | 5919.50 | 650.50 |
BANQUET_FLR_6 | 1.5698 | 0.0000 | 1.5698 | 0.0036 | 1.5734 | 1.1878 | 5.67 | 6.17 | 8748.17 |
DINING_FLR_6 | 1.6970 | 0.0000 | 1.6970 | 0.0036 | 1.7005 | 1.1878 | 0.00 | 0.67 | 8759.33 |
KITCHEN_FLR_6 | 2.1619 | 0.0000 | 2.1619 | 0.0032 | 2.1651 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.4070 | 0.0000 | 0.4070 | 0.0031 | 0.4101 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 65.4283 | 0.2011 | 65.6294 | 0.1157 | 65.7451 | 73.9670 | 8760.00 | 6405.90 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.44E+09 | 0.00 | 0.44E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 29249995.70 | 506935.98 | 29756931.68 | 64690340.46 | 8760.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 13.9954 | 0.0000 | 13.9954 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 0.9275 | 0.0161 | 0.9436 | 2.0513 | 8760.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 0.00 | 4472.29 | 0.00 | 0.00 | 0.00 | 4287.71 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 0.00 | 0.00 | 0.00 | 6935.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 0.0000 | 14.3940 | 0.0000 | 0.0000 | 0.0000 | 13.5828 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1716 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1363 |
Defaulted Fields | 1208 |
Fields with Defaults | 4115 |
Autosized Fields | 353 |
Autosizable Fields | 407 |
Autocalculated Fields | 289 |
Autocalculatable Fields | 549 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5467.55 | 68424.21 | 02-DEC-02:10 | 396477.46 | 21-JUL-19:30 |
Electricity:Building | 2278.04 | 30187.97 | 17-JUN-05:00 | 133648.28 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 245.14 | 2955.01 | 02-JAN-02:10 | 17976.64 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2270.95 | 30046.83 | 17-JUN-05:00 | 133406.95 | 02-JAN-20:10 |
InteriorLights:Electricity | 542.81 | 4764.65 | 17-JUN-05:00 | 45424.10 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 102.03 | 927.11 | 02-JAN-02:10 | 8344.11 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 542.81 | 4764.65 | 17-JUN-05:00 | 45424.10 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 542.81 | 4764.65 | 17-JUN-05:00 | 45424.10 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 102.03 | 927.11 | 02-JAN-02:10 | 8344.11 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 542.81 | 4764.65 | 17-JUN-05:00 | 45424.10 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 15.82 | 195.57 | 02-JAN-02:10 | 1146.69 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 5.64 | 51.23 | 02-JAN-02:10 | 461.08 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 5.64 | 51.23 | 02-JAN-02:10 | 461.08 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 18.32 | 226.47 | 02-JAN-02:10 | 1327.87 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 6.53 | 59.33 | 02-JAN-02:10 | 533.93 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 6.53 | 59.33 | 02-JAN-02:10 | 533.93 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 20.00 | 245.14 | 02-JAN-02:10 | 1455.21 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 7.53 | 68.42 | 02-JAN-02:10 | 615.76 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 7.53 | 68.42 | 02-JAN-02:10 | 615.76 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.28 | 66.24 | 02-JAN-02:10 | 379.51 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.68 | 15.26 | 02-JAN-02:10 | 137.35 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.68 | 15.26 | 02-JAN-02:10 | 137.35 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.35 | 1002.76 | 02-JAN-02:10 | 4933.42 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.41 | 40.07 | 02-JAN-02:10 | 360.62 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.41 | 40.07 | 02-JAN-02:10 | 360.62 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 25.88 | 308.39 | 17-JUN-05:00 | 2381.38 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 11.54 | 69.23 | 01-JAN-13:10 | 1416.11 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 11.54 | 69.23 | 01-JAN-13:10 | 1416.11 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 259.48 | 3132.64 | 17-JUN-05:00 | 19610.05 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.48 | 1021.23 | 17-JUN-05:00 | 9580.84 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 110.48 | 1021.23 | 17-JUN-05:00 | 9580.84 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 17.85 | 257.74 | 01-JAN-02:10 | 1187.62 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 5.55 | 47.02 | 01-JAN-02:10 | 427.46 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 5.55 | 47.02 | 01-JAN-02:10 | 427.46 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 17.84 | 257.71 | 01-JAN-02:10 | 1187.48 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 5.55 | 47.01 | 01-JAN-02:10 | 427.41 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 5.55 | 47.01 | 01-JAN-02:10 | 427.41 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 295.07 | 4482.89 | 01-JAN-02:10 | 20504.95 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 66.32 | 561.43 | 01-JAN-02:10 | 5104.26 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 66.32 | 561.43 | 01-JAN-02:10 | 5104.26 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 295.15 | 4484.12 | 01-JAN-02:10 | 20510.57 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 66.33 | 561.58 | 01-JAN-02:10 | 5105.65 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 66.33 | 561.58 | 01-JAN-02:10 | 5105.65 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 17.85 | 257.74 | 01-JAN-02:10 | 1187.62 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 5.55 | 47.02 | 01-JAN-02:10 | 427.46 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 5.55 | 47.02 | 01-JAN-02:10 | 427.46 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 17.84 | 257.71 | 01-JAN-02:10 | 1187.48 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 5.55 | 47.01 | 01-JAN-02:10 | 427.41 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 5.55 | 47.01 | 01-JAN-02:10 | 427.41 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 51.07 | 464.00 | 02-JAN-02:10 | 4176.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 51.07 | 464.00 | 02-JAN-02:10 | 4176.01 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 51.07 | 464.00 | 02-JAN-02:10 | 4176.01 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.46 | 64.43 | 01-JAN-02:10 | 296.90 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.39 | 11.75 | 01-JAN-02:10 | 106.87 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.39 | 11.75 | 01-JAN-02:10 | 106.87 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.46 | 64.43 | 01-JAN-02:10 | 296.87 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.39 | 11.75 | 01-JAN-02:10 | 106.85 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.39 | 11.75 | 01-JAN-02:10 | 106.85 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 34.95 | 531.01 | 01-JAN-02:10 | 2428.88 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 7.86 | 66.50 | 01-JAN-02:10 | 604.62 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 7.86 | 66.50 | 01-JAN-02:10 | 604.62 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 201.30 | 2439.25 | 17-JUN-05:00 | 9234.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 25.45 | 189.95 | 17-JUN-05:00 | 2486.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 25.45 | 189.95 | 17-JUN-05:00 | 2486.81 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 201.30 | 2439.25 | 17-JUN-05:00 | 9234.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 25.45 | 189.95 | 17-JUN-05:00 | 2486.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 25.45 | 189.95 | 17-JUN-05:00 | 2486.81 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 443.12 | 5932.71 | 02-JAN-02:10 | 18599.73 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.01 | 109.08 | 02-JAN-02:10 | 981.75 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.01 | 109.08 | 02-JAN-02:10 | 981.75 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 13.51 | 122.77 | 02-JAN-02:10 | 1104.91 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 13.51 | 122.77 | 02-JAN-02:10 | 1104.91 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 13.51 | 122.77 | 02-JAN-02:10 | 1104.91 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1728.14 | 25282.18 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 952.41 | 15101.09 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 43.71 | 732.81 | 09-MAY-22:30 | 2786.20 | 02-JUL-10:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1632.51 | 2132.27 | 25-MAR-02:20 | 198757.19 | 21-JUL-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 15.76 | 0.00 | 01-JAN-11:10 | 1311.42 | 22-JUL-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 20.86 | 615.40 | 15-DEC-04:10 | 715.17 | 23-AUG-13:50 |
WaterSystems:Electricity | 496.90 | 1086.56 | 14-JUN-01:50 | 43743.96 | 06-SEP-20:40 |
Electricity:HVAC | 763.61 | 11996.84 | 10-NOV-15:00 | 58867.73 | 18-AUG-21:10 |
Fans:Electricity | 590.93 | 11195.11 | 26-MAR-03:50 | 48094.33 | 18-AUG-21:10 |
General:Fans:Electricity | 590.93 | 11195.11 | 26-MAR-03:50 | 48094.33 | 18-AUG-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ExteriorEquipment:Electricity | 641.45 | 9451.13 | 02-JAN-02:20 | 39153.57 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 22.42 | 386.32 | 02-JAN-02:20 | 1279.09 | 16-MAR-20:10 |
ElectricityPurchased:Facility | 5467.55 | 68424.21 | 02-DEC-02:10 | 396477.46 | 21-JUL-19:30 |
ElectricityPurchased:Plant | 5467.55 | 68424.21 | 02-DEC-02:10 | 396477.46 | 21-JUL-19:30 |
Cogeneration:ElectricityPurchased | 5467.55 | 68424.21 | 02-DEC-02:10 | 396477.46 | 21-JUL-19:30 |
General:Cogeneration:ElectricityPurchased | 5467.55 | 68424.21 | 02-DEC-02:10 | 396477.46 | 21-JUL-19:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5467.55 | 68424.21 | 02-DEC-02:10 | 396477.46 | 21-JUL-19:30 |
ElectricityNet:Plant | 5467.55 | 68424.21 | 02-DEC-02:10 | 396477.46 | 21-JUL-19:30 |
Cogeneration:ElectricityNet | 5467.55 | 68424.21 | 02-DEC-02:10 | 396477.46 | 21-JUL-19:30 |
General:Cogeneration:ElectricityNet | 5467.55 | 68424.21 | 02-DEC-02:10 | 396477.46 | 21-JUL-19:30 |
ExteriorLights:Electricity | 174.36 | 0.00 | 01-JAN-07:20 | 11096.45 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 174.36 | 0.00 | 01-JAN-07:20 | 11096.45 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.80 | 01-JAN-00:10 | 188.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 150.25 | 0.00 | 01-JAN-11:10 | 9938.94 | 12-APR-16:30 |
General:HeatRecovery:Electricity | 150.25 | 0.00 | 01-JAN-11:10 | 9938.94 | 12-APR-16:30 |
Water Heater:WaterSystems:Electricity | 90.74 | 1086.56 | 14-JUN-01:50 | 4738.75 | 05-OCT-18:10 |
Water Heater Parasitic:WaterSystems:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 992.67 | 0.00 | 01-JAN-03:10 | 156194.44 | 28-JUN-15:20 |
General:Cooling:Electricity | 992.67 | 0.00 | 01-JAN-03:10 | 156194.44 | 28-JUN-15:20 |
Pumps:Electricity | 106.32 | 47.91 | 11-JAN-16:00 | 5292.19 | 28-JUN-18:20 |
General:Pumps:Electricity | 106.32 | 47.91 | 11-JAN-16:00 | 5292.19 | 28-JUN-18:20 |
WIRED_LTG_ELECTRICITY | 19.11 | 0.00 | 01-JAN-00:10 | 1598.93 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 3606.69 | 29270.80 | 13-APR-01:30 | 407916.14 | 11-DEC-18:50 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 1817.85 | 15908.90 | 09-MAR-11:10 | 303667.82 | 11-DEC-18:50 |
WaterSystems:NaturalGas | 1131.13 | 15908.90 | 01-JAN-16:10 | 124704.37 | 27-JAN-21:40 |
Water Heater:WaterSystems:NaturalGas | 1131.13 | 15908.90 | 01-JAN-16:10 | 124704.37 | 27-JAN-21:40 |
Heating:NaturalGas | 686.72 | 0.00 | 01-JAN-08:50 | 187635.00 | 11-DEC-18:50 |
Boiler:Heating:NaturalGas | 686.72 | 0.00 | 01-JAN-08:50 | 187635.00 | 11-DEC-18:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 3052.60 | 0.00 | 01-JAN-03:10 | 441555.96 | 21-JUL-18:20 |
PlantLoopCoolingDemand:HVAC | 3052.60 | 0.00 | 01-JAN-03:10 | 441555.96 | 21-JUL-18:20 |
CoolingCoils:PlantLoopCoolingDemand | 3052.60 | 0.00 | 01-JAN-03:10 | 441555.96 | 21-JUL-18:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 16-MAR-20:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 16-MAR-20:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 16-MAR-20:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 16-MAR-20:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 16-MAR-20:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 16-MAR-20:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 19-MAY-06:20 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 19-MAY-06:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 20979.17 | 133175.56 | 28-MAR-14:10 | 2011806.35 | 20-JUL-18:10 |
EnergyTransfer:Building | 5276.09 | 81660.12 | 19-JAN-11:10 | 350958.42 | 20-JUL-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 708.43 | 10321.50 | 15-DEC-04:00 | 35483.88 | 23-JUL-10:50 |
Refrigeration:EnergyTransfer | 180.16 | 4016.69 | 09-MAY-22:30 | 10350.17 | 15-AUG-06:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.08 | 2008.34 | 09-MAY-22:30 | 5175.09 | 15-AUG-06:20 |
General:Refrigeration:EnergyTransfer | 90.08 | 2008.34 | 09-MAY-22:30 | 5175.09 | 15-AUG-06:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.08 | 2008.34 | 09-MAY-22:30 | 5175.09 | 15-AUG-06:20 |
EnergyTransfer:Plant | 8611.37 | 15937.50 | 04-NOV-01:30 | 1071900.84 | 21-JUL-18:20 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.52 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.56 | 1852.51 | 15-DEC-04:10 | 2548.87 | 23-AUG-13:50 |
EnergyTransfer:HVAC | 7091.71 | 3056.99 | 28-MAR-14:10 | 617283.52 | 28-JUN-18:10 |
CoolingCoils:EnergyTransfer | 4210.94 | 0.00 | 01-JAN-03:10 | 565271.62 | 21-JUL-18:10 |
EnergyTransfer:Zone:BASEMENT | 326.92 | 7643.54 | 03-APR-14:10 | 18568.40 | 12-OCT-21:00 |
Heating:EnergyTransfer | 52.32 | 0.00 | 01-JAN-08:10 | 37876.31 | 21-DEC-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 52.32 | 0.00 | 01-JAN-08:10 | 37876.31 | 21-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 5133.69 | 78362.74 | 19-JAN-11:10 | 347470.05 | 20-JUL-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 326.92 | 7643.54 | 03-APR-14:10 | 18568.40 | 12-OCT-21:00 |
General:Cooling:EnergyTransfer | 5133.69 | 78362.74 | 19-JAN-11:10 | 347470.05 | 20-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 326.92 | 7643.54 | 03-APR-14:10 | 18568.40 | 12-OCT-21:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 49.37 | 0.18 | 17-JAN-09:40 | 4401.60 | 05-OCT-13:00 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 449.31 | 09-DEC-07:30 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 449.31 | 09-DEC-07:30 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 49.34 | 0.00 | 17-JAN-04:20 | 4401.60 | 05-OCT-13:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 49.34 | 0.00 | 17-JAN-04:20 | 4401.60 | 05-OCT-13:00 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 35.06 | 665.43 | 19-JAN-12:00 | 2216.87 | 21-JUL-21:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 35.06 | 665.43 | 19-JAN-12:00 | 2216.87 | 21-JUL-21:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 35.06 | 665.43 | 19-JAN-12:00 | 2216.87 | 21-JUL-21:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 25.33 | 35.53 | 19-JAN-11:40 | 1912.38 | 21-JUL-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 25.33 | 35.53 | 19-JAN-11:40 | 1912.38 | 21-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 25.33 | 35.53 | 19-JAN-11:40 | 1912.38 | 21-JUL-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 13.01 | 0.05 | 18-JAN-15:20 | 881.74 | 21-JUL-19:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 52.85 | 19-JAN-11:40 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 52.85 | 19-JAN-11:40 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 13.01 | 0.00 | 18-JAN-11:30 | 881.74 | 21-JUL-19:10 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 13.01 | 0.00 | 18-JAN-11:30 | 881.74 | 21-JUL-19:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 605.23 | 9917.20 | 21-JAN-06:00 | 39326.58 | 21-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 605.23 | 9917.20 | 21-JAN-06:00 | 39326.58 | 21-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 605.23 | 9917.20 | 21-JAN-06:00 | 39326.58 | 21-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 253.91 | 2436.85 | 19-JAN-09:20 | 16139.69 | 31-DEC-13:00 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 253.91 | 2436.85 | 19-JAN-09:20 | 16139.69 | 31-DEC-13:00 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 253.91 | 2436.85 | 19-JAN-09:20 | 16139.69 | 31-DEC-13:00 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 803.09 | 15122.86 | 19-JAN-11:30 | 43022.68 | 21-JUL-21:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 803.09 | 15122.86 | 19-JAN-11:30 | 43022.68 | 21-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 803.09 | 15122.86 | 19-JAN-11:30 | 43022.68 | 21-JUL-21:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 73.74 | 0.00 | 01-JAN-08:10 | 12142.26 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 4.82 | 0.00 | 01-JAN-00:10 | 3992.53 | 17-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 4.82 | 0.00 | 01-JAN-00:10 | 3992.53 | 17-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 68.92 | 0.00 | 01-JAN-01:00 | 12142.26 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 68.92 | 0.00 | 01-JAN-01:00 | 12142.26 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 59.12 | 0.00 | 01-JAN-08:10 | 12233.01 | 20-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 9.19 | 0.00 | 01-JAN-08:10 | 4287.43 | 15-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 9.19 | 0.00 | 01-JAN-08:10 | 4287.43 | 15-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 49.93 | 0.00 | 01-JAN-00:10 | 12233.01 | 20-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 49.93 | 0.00 | 01-JAN-00:10 | 12233.01 | 20-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 452.68 | 0.00 | 01-JAN-01:50 | 57775.67 | 31-DEC-13:40 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 452.68 | 0.00 | 01-JAN-01:50 | 57775.67 | 31-DEC-13:40 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 452.68 | 0.00 | 01-JAN-01:50 | 57775.67 | 31-DEC-13:40 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 390.35 | 0.00 | 01-JAN-08:10 | 69552.09 | 03-JUL-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 13.67 | 0.00 | 01-JAN-00:10 | 17594.33 | 21-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 13.67 | 0.00 | 01-JAN-00:10 | 17594.33 | 21-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 376.67 | 0.00 | 01-JAN-02:10 | 69552.09 | 03-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 376.67 | 0.00 | 01-JAN-02:10 | 69552.09 | 03-JUL-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 78.59 | 0.00 | 01-JAN-08:10 | 11547.40 | 23-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 5.14 | 0.00 | 01-JAN-00:10 | 3949.94 | 20-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 5.14 | 0.00 | 01-JAN-00:10 | 3949.94 | 20-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 73.45 | 0.00 | 01-JAN-00:20 | 11547.40 | 23-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 73.45 | 0.00 | 01-JAN-00:20 | 11547.40 | 23-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 63.04 | 0.00 | 01-JAN-08:10 | 13144.91 | 26-JUN-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 9.34 | 0.00 | 01-JAN-08:00 | 4054.18 | 17-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 9.34 | 0.00 | 01-JAN-08:00 | 4054.18 | 17-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 53.70 | 0.00 | 01-JAN-00:10 | 13144.91 | 26-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 53.70 | 0.00 | 01-JAN-00:10 | 13144.91 | 26-JUN-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 163.49 | 2.25 | 17-JAN-14:20 | 11187.08 | 21-JUL-18:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.04 | 0.00 | 01-JAN-00:10 | 1288.44 | 19-JAN-09:20 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.04 | 0.00 | 01-JAN-00:10 | 1288.44 | 19-JAN-09:20 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 163.45 | 0.00 | 17-JAN-09:10 | 11187.08 | 21-JUL-18:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 163.45 | 0.00 | 17-JAN-09:10 | 11187.08 | 21-JUL-18:30 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 19.50 | 0.00 | 01-JAN-08:10 | 3306.58 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.54 | 0.00 | 01-JAN-08:10 | 1204.71 | 21-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.54 | 0.00 | 01-JAN-08:10 | 1204.71 | 21-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 16.96 | 0.00 | 01-JAN-00:10 | 3306.58 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 16.96 | 0.00 | 01-JAN-00:10 | 3306.58 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 16.71 | 0.00 | 01-JAN-08:10 | 3430.02 | 25-APR-16:40 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 4.19 | 0.00 | 01-JAN-08:10 | 1414.18 | 22-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 4.19 | 0.00 | 01-JAN-08:10 | 1414.18 | 22-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 12.52 | 0.00 | 01-JAN-00:10 | 3430.02 | 25-APR-16:40 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 12.52 | 0.00 | 01-JAN-00:10 | 3430.02 | 25-APR-16:40 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 118.40 | 0.00 | 01-JAN-08:10 | 17296.25 | 31-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 3.30 | 0.00 | 01-JAN-00:10 | 4547.60 | 17-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 3.30 | 0.00 | 01-JAN-00:10 | 4547.60 | 17-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 115.10 | 0.00 | 01-JAN-04:40 | 17296.25 | 31-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 115.10 | 0.00 | 01-JAN-04:40 | 17296.25 | 31-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 443.32 | 8366.39 | 21-DEC-15:00 | 23457.06 | 21-JUL-21:20 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 443.32 | 8366.39 | 21-DEC-15:00 | 23457.06 | 21-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 443.32 | 8366.39 | 21-DEC-15:00 | 23457.06 | 21-JUL-21:20 |
EnergyTransfer:Zone:DINING_FLR_6 | 481.63 | 9338.14 | 21-DEC-15:00 | 24642.75 | 21-JUL-21:20 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 481.63 | 9338.14 | 21-DEC-15:00 | 24642.75 | 21-JUL-21:20 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 481.63 | 9338.14 | 21-DEC-15:00 | 24642.75 | 21-JUL-21:20 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 618.34 | 8224.82 | 15-DEC-04:00 | 30430.43 | 23-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 618.34 | 8224.82 | 15-DEC-04:00 | 30430.43 | 23-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 95.18 | 1.80 | 17-JAN-10:40 | 6997.47 | 21-AUG-14:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.05 | 0.00 | 01-JAN-00:10 | 814.59 | 15-DEC-07:30 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.05 | 0.00 | 01-JAN-00:10 | 814.59 | 15-DEC-07:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 95.13 | 0.00 | 12-JAN-07:10 | 6997.47 | 21-AUG-14:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 95.13 | 0.00 | 12-JAN-07:10 | 6997.47 | 21-AUG-14:10 |
PlantLoopHeatingDemand:Facility | 2799.88 | 8664.50 | 08-AUG-01:20 | 295150.32 | 03-MAR-19:00 |
PlantLoopHeatingDemand:Plant | 2292.52 | 8664.50 | 08-AUG-01:20 | 209847.16 | 03-JUL-20:30 |
WaterSystems:PlantLoopHeatingDemand | 2292.52 | 8664.50 | 08-AUG-01:20 | 209847.16 | 03-JUL-20:30 |
General:WaterSystems:PlantLoopHeatingDemand | 739.21 | 8660.45 | 08-AUG-00:10 | 55932.55 | 06-FEB-07:10 |
HeatingCoils:EnergyTransfer | 507.36 | 0.00 | 01-JAN-08:50 | 132578.72 | 23-DEC-17:40 |
PlantLoopHeatingDemand:HVAC | 507.36 | 0.00 | 01-JAN-08:50 | 132578.72 | 23-DEC-17:40 |
HeatingCoils:PlantLoopHeatingDemand | 507.36 | 0.00 | 01-JAN-08:50 | 132578.72 | 23-DEC-17:40 |
HeatRecoveryForHeating:EnergyTransfer | 2277.52 | 0.00 | 01-JAN-11:10 | 409112.58 | 15-DEC-06:40 |
HeatRecoveryForCooling:EnergyTransfer | 95.88 | 0.00 | 01-JAN-00:10 | 91768.96 | 27-JUN-16:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 1553.31 | 0.00 | 01-JAN-00:10 | 175237.66 | 03-JUL-20:30 |
WaterSystems:EnergyTransfer | 739.21 | 8660.45 | 08-AUG-00:10 | 55932.55 | 06-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 739.21 | 8660.45 | 08-AUG-00:10 | 55932.55 | 06-FEB-07:10 |
Boilers:EnergyTransfer | 502.61 | 0.00 | 01-JAN-08:50 | 136508.33 | 20-JAN-16:10 |
Chillers:EnergyTransfer | 3143.40 | 0.00 | 01-JAN-03:10 | 444231.06 | 21-JUL-18:20 |
HeatRejection:EnergyTransfer | 4136.06 | 0.00 | 01-JAN-03:10 | 597468.30 | 21-JUL-18:20 |
General:HeatRejection:EnergyTransfer | 4136.06 | 0.00 | 01-JAN-03:10 | 597468.30 | 21-JUL-18:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -326.925 | 0.000 | 0.000 | 138.064 | 102.033 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -56.278 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.032 | -49.335 | 0.000 | 0.000 | 14.811 | 5.638 | 10.186 | 33.848 | 0.000 | 0.057 | 0.002 | 0.000 | -9.857 | 0.000 | -0.806 | -4.574 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -35.065 | 0.000 | 0.000 | 16.193 | 6.529 | 11.795 | 0.000 | 0.000 | 0.023 | 0.857 | 0.000 | 0.000 | 0.000 | -0.332 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -25.332 | 0.000 | 0.000 | 3.601 | 7.530 | 12.471 | 0.000 | 0.000 | 0.055 | 2.405 | 0.000 | 0.000 | 0.000 | -0.729 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.001 | -13.013 | 0.000 | 0.000 | 2.797 | 1.680 | 3.598 | 0.000 | 0.000 | 0.032 | 5.322 | 0.000 | 0.000 | 0.000 | -0.415 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -605.229 | 0.000 | 0.000 | 11.040 | 4.410 | 658.131 | 0.000 | 0.000 | 0.080 | 0.000 | 0.000 | 0.000 | 0.000 | -1.069 | -67.362 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -253.911 | 0.000 | 0.000 | 182.232 | 11.543 | 14.341 | 94.322 | 0.000 | 0.127 | 0.002 | 0.000 | -29.544 | 0.000 | -1.933 | -17.177 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -803.099 | 0.000 | 0.000 | 535.783 | 110.478 | 148.998 | 124.816 | 0.000 | 0.366 | 0.000 | 0.000 | -39.167 | 0.000 | -5.590 | -72.586 |
ROOM_1_FLR_3 | 6.801 | -61.184 | 0.000 | -9.710 | 0.000 | 0.000 | 9.660 | 5.554 | 12.292 | 66.087 | 0.000 | 0.273 | 0.000 | 0.000 | -21.036 | 0.000 | -2.262 | -6.475 |
ROOM_2_FLR_3 | 11.934 | -42.519 | 0.000 | -10.158 | 0.000 | 0.000 | 9.537 | 5.553 | 12.291 | 46.178 | 0.000 | 0.202 | 0.000 | 0.000 | -21.894 | 0.000 | -2.695 | -8.430 |
ROOM_3_MULT19_FLR_3 | 0.000 | -438.918 | 0.000 | -13.752 | 0.000 | 0.000 | 0.000 | 66.316 | 228.754 | 386.872 | 0.000 | 0.348 | 0.025 | 0.000 | -156.131 | 0.000 | -13.253 | -60.236 |
ROOM_4_MULT19_FLR_3 | 36.454 | -264.573 | 0.000 | -134.869 | 0.000 | 0.000 | 182.523 | 66.334 | 228.817 | 108.954 | 0.000 | 1.417 | 0.000 | 0.000 | -117.728 | 0.000 | -23.487 | -83.842 |
ROOM_5_FLR_3 | 7.133 | -65.722 | 0.000 | -9.713 | 0.000 | 0.000 | 9.649 | 5.554 | 12.292 | 69.405 | 0.000 | 0.273 | 0.000 | 0.000 | -20.409 | 0.000 | -2.279 | -6.182 |
ROOM_6_FLR_3 | 11.993 | -46.163 | 0.000 | -10.188 | 0.000 | 0.000 | 9.529 | 5.553 | 12.291 | 48.870 | 0.000 | 0.203 | 0.001 | 0.000 | -20.729 | 0.000 | -2.678 | -8.680 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.037 | -163.453 | 0.000 | 0.000 | 113.496 | 51.065 | 0.000 | 57.917 | 0.000 | 0.161 | 0.000 | 0.000 | -27.637 | 0.000 | -2.265 | -29.321 |
ROOM_1_FLR_6 | 3.195 | -15.184 | 0.000 | -2.427 | 0.000 | 0.000 | 2.418 | 1.388 | 3.073 | 16.445 | 0.000 | 0.071 | 0.000 | 0.000 | -5.193 | 0.000 | -0.588 | -3.199 |
ROOM_2_FLR_6 | 4.985 | -10.773 | 0.000 | -2.536 | 0.000 | 0.000 | 2.387 | 1.388 | 3.073 | 11.499 | 0.000 | 0.051 | 0.000 | 0.000 | -5.406 | 0.000 | -0.693 | -3.976 |
ROOM_3_MULT9_FLR_6 | 5.412 | -101.574 | 0.000 | -15.628 | 0.000 | 0.000 | 21.694 | 7.855 | 27.097 | 89.528 | 0.000 | 0.430 | 0.001 | 0.000 | -24.127 | 0.000 | -3.407 | -7.281 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -443.323 | 0.000 | 0.000 | 315.139 | 25.447 | 175.857 | 11.075 | 0.000 | 0.077 | 0.000 | 0.000 | -16.210 | 0.000 | -1.274 | -66.790 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -481.634 | 0.000 | 0.000 | 314.514 | 25.447 | 175.857 | 10.869 | 0.000 | 0.077 | 0.000 | 0.000 | -16.603 | 0.000 | -1.281 | -27.247 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -618.327 | 0.000 | 0.000 | 28.188 | 12.005 | 540.650 | 32.759 | 0.000 | 0.069 | 16.646 | 0.000 | -10.848 | 0.000 | -1.143 | -0.002 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.049 | -95.134 | 0.000 | 0.000 | 30.435 | 13.511 | 0.000 | 28.658 | 0.000 | 0.068 | 35.647 | 0.000 | -12.245 | 0.000 | -0.989 | -0.000 |
Total Facility | 87.907 | -1046.610 | 0.118 | -4122.760 | 0.000 | 0.000 | 1953.691 | 542.813 | 2434.967 | 1238.102 | 0.000 | 4.461 | 60.909 | 0.000 | -554.763 | 0.000 | -69.167 | -529.638 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 12-OCT-21:00 | 0.00 | 0.00 | 0.00 | -18570.61 | 0.00 | 0.00 | 5924.38 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3896.33 |
RETAIL_1_FLR_1 | 05-OCT-13:00 | 0.00 | 0.00 | 0.00 | -4401.35 | 0.00 | 0.00 | 150.09 | 128.08 | 252.59 | 5630.33 | 0.00 | 3.72 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1763.46 |
RETAIL_2_FLR_1 | 21-JUL-21:00 | 0.00 | 0.00 | 0.00 | -2217.88 | 0.00 | 0.00 | 697.57 | 474.61 | 752.15 | 0.00 | 0.00 | 5.51 | 288.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 21-JUL-20:00 | 0.00 | 0.00 | 0.00 | -1912.47 | 0.00 | 0.00 | 129.08 | 615.76 | 839.45 | 0.00 | 0.00 | 14.26 | 313.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 21-JUL-19:10 | 0.00 | 0.00 | 0.00 | -881.81 | 0.00 | 0.00 | 99.29 | 137.35 | 242.16 | 0.00 | 0.00 | 12.05 | 390.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 21-JUL-20:00 | 0.00 | 0.00 | 0.00 | -39326.43 | 0.00 | 0.00 | 408.86 | 360.62 | 44299.38 | 0.00 | 0.00 | 19.47 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5761.90 |
CAFE_FLR_1 | 31-DEC-13:00 | 0.00 | 0.00 | 0.00 | -16138.86 | 0.00 | 0.00 | 2968.81 | 103.85 | 406.43 | 20426.64 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -88.92 | -7677.96 |
LOBBY_FLR_1 | 21-JUL-21:10 | 0.00 | 0.00 | 0.00 | -43045.49 | 0.00 | 0.00 | 26438.30 | 6387.23 | 7389.94 | 379.79 | 0.00 | 85.92 | 2364.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 19-JUN-18:01 | 0.00 | -16198.26 | 0.00 | -600.22 | 0.00 | 0.00 | 335.50 | 380.45 | 516.26 | 8695.60 | 0.00 | 33.90 | 6836.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 25-APR-16:21 | 0.00 | -18235.44 | 0.00 | -754.90 | 0.00 | 0.00 | 193.47 | 119.68 | 537.27 | 10602.43 | 0.00 | 0.00 | 7540.79 | 0.00 | -0.00 | 0.00 | -3.30 | 0.00 |
ROOM_3_MULT19_FLR_3 | 31-DEC-13:40 | 0.00 | -57776.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1684.44 | 5686.12 | 82586.74 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -542.22 | -31638.88 |
ROOM_4_MULT19_FLR_3 | 17-JUN-08:31 | 0.00 | -88804.67 | 0.00 | -9034.99 | 0.00 | 0.00 | 2379.25 | 2859.17 | 12159.85 | 9379.79 | 0.00 | 80.33 | 70981.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 14-JUN-08:61 | 0.00 | -14165.44 | 0.00 | -608.34 | 0.00 | 0.00 | 87.14 | 188.08 | 453.05 | 10024.72 | 0.00 | 15.42 | 4005.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 20-JUN-08:32 | 0.00 | -16914.86 | 0.00 | -841.36 | 0.00 | 0.00 | 58.78 | 188.06 | 452.99 | 9722.45 | 0.00 | 0.00 | 7356.51 | 0.00 | -0.00 | 0.00 | -22.57 | 0.00 |
CORRIDOR_FLR_3 | 21-JUL-18:25 | 0.00 | 0.00 | 0.00 | -11188.09 | 0.00 | 0.00 | 4080.27 | 3712.00 | 0.00 | 2677.28 | 0.00 | 73.40 | 645.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 20-JUN-15:01 | 0.00 | -4316.37 | 0.00 | -149.84 | 0.00 | 0.00 | 58.82 | 29.92 | 68.48 | 2482.16 | 0.00 | 11.80 | 1815.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 25-APR-16:21 | 0.00 | -4857.80 | 0.00 | -188.76 | 0.00 | 0.00 | 48.37 | 29.92 | 134.32 | 2628.48 | 0.00 | 0.00 | 2206.37 | 0.00 | -0.00 | 0.00 | -0.91 | 0.00 |
ROOM_3_MULT9_FLR_6 | 31-OCT-15:01 | 0.00 | -17629.55 | 0.00 | -1004.15 | 0.00 | 0.00 | 529.38 | 169.29 | 603.86 | 10396.98 | 0.00 | 300.84 | 6633.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 21-JUL-21:20 | 0.00 | 0.00 | 0.00 | -23468.24 | 0.00 | 0.00 | 15604.26 | 1657.87 | 6747.90 | 181.42 | 0.00 | 17.97 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -741.20 |
DINING_FLR_6 | 21-JUL-21:20 | 0.00 | 0.00 | 0.00 | -24654.50 | 0.00 | 0.00 | 15600.13 | 1657.87 | 6747.90 | 169.25 | 0.00 | 17.97 | 461.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 23-JUL-10:40 | 0.00 | 0.00 | 0.00 | -30438.33 | 0.00 | 0.00 | 464.29 | 327.25 | 23951.61 | 3613.78 | 0.00 | 22.75 | 2058.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 21-AUG-14:10 | 0.00 | 0.00 | 0.00 | -6997.30 | 0.00 | 0.00 | 462.68 | 306.92 | 0.00 | 2817.30 | 0.00 | 23.87 | 3386.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 19-JUN-18:01 | 0.00 | -189117.50 | 0.00 | -184042.60 | 0.00 | 0.00 | 74257.48 | 36821.50 | 121562.63 | 62892.05 | 0.00 | 651.10 | 76975.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 09-DEC-07:30 | 0.00 | 0.00 | 449.14 | 0.00 | 0.00 | 0.00 | 447.48 | 153.69 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -964.51 | 0.00 | -63.48 | -311.01 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 19-JAN-11:40 | 0.00 | 0.00 | 52.85 | 0.00 | 0.00 | 0.00 | 33.72 | 38.16 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -28.91 | -185.04 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 17-JAN-09:01 | 8529.82 | 257.40 | 0.00 | -257.40 | 0.00 | 0.00 | 108.88 | 188.08 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -699.79 | 0.00 | -138.58 | -8441.45 |
ROOM_2_FLR_3 | 15-DEC-09:01 | 8649.75 | 254.94 | 0.00 | -254.94 | 0.00 | 0.00 | 108.88 | 188.06 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1408.23 | 0.00 | -164.35 | -7827.11 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 15-DEC-09:01 | 47353.74 | 4447.37 | 0.00 | -4447.37 | 0.00 | 0.00 | 1936.43 | 2246.49 | 8433.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8197.66 | 0.00 | -911.08 | -50861.37 |
ROOM_5_FLR_3 | 20-JAN-09:01 | 8358.59 | 256.92 | 0.00 | -256.92 | 0.00 | 0.00 | 108.88 | 188.08 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -521.47 | 0.00 | -141.76 | -8445.37 |
ROOM_6_FLR_3 | 20-JAN-09:01 | 8364.37 | 255.82 | 0.00 | -255.82 | 0.00 | 0.00 | 108.88 | 188.06 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -613.44 | 0.00 | -141.65 | -8359.21 |
CORRIDOR_FLR_3 | 19-JAN-09:03 | 0.00 | 0.00 | 1326.77 | 0.00 | 0.00 | 0.00 | 1385.74 | 1856.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -569.42 | 0.00 | -173.28 | -3825.81 |
ROOM_1_FLR_6 | 17-JAN-09:01 | 2574.87 | 65.78 | 0.00 | -65.78 | 0.00 | 0.00 | 27.22 | 47.02 | 113.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -172.34 | 0.00 | -34.89 | -2555.15 |
ROOM_2_FLR_6 | 15-DEC-09:01 | 2617.22 | 64.83 | 0.00 | -64.83 | 0.00 | 0.00 | 27.22 | 47.02 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -350.07 | 0.00 | -41.30 | -2413.34 |
ROOM_3_MULT9_FLR_6 | 17-JAN-09:01 | 11829.25 | 475.59 | 0.00 | -475.59 | 0.00 | 0.00 | 238.68 | 266.03 | 998.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -490.16 | 0.00 | -164.46 | -12678.04 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 15-DEC-07:30 | 0.00 | 0.00 | 814.37 | 0.00 | 0.00 | 0.00 | 733.30 | 613.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1494.84 | 0.00 | -97.53 | -569.14 |
Total Facility | 20-JAN-09:01 | 11066.48 | 92468.03 | 1532.98 | -92468.03 | 0.00 | 0.00 | 22831.70 | 18160.56 | 87870.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20105.69 | 0.00 | -3879.49 | -117477.17 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 24.7499 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 24.6111 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 12.3750 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6572 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4663 | 2.4663 | 1.1616 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3878 | 0.3878 | 0.1826 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2581 | 0.2581 | 0.1215 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2165 | 0.2165 | 0.1020 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1173 | 0.1173 | 0.0553 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.9530 | 3.9530 | 1.8619 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7087 | 1.7087 | 0.8048 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4409 | 5.4409 | 2.5627 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3972 | 1.3972 | 0.6581 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6006 | 2.6006 | 1.2249 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7303 | 2.7303 | 1.2860 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6368 | 2.6368 | 1.2419 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8364 | 0.8364 | 0.3939 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 24.7499 | 24.6111 | 24.7499 | 11.6572 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2332 | 1.2332 | 1.1616 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1939 | 0.1939 | 0.1826 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1290 | 0.1290 | 0.1215 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1083 | 0.1083 | 0.1020 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0587 | 0.0587 | 0.0553 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9765 | 1.9765 | 1.8619 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8544 | 0.8544 | 0.8048 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7204 | 2.7204 | 2.5627 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6986 | 0.6986 | 0.6581 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3003 | 1.3003 | 1.2249 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3651 | 1.3651 | 1.2860 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3184 | 1.3184 | 1.2419 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4182 | 0.4182 | 0.3939 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 12.3750 | 11.6572 | 11.6572 | 11.6572 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 78.83 |
Number of hours not met | 78.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 686.72 | 187635.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 992.67 | 156194.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 542.81 | 45424.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 174.36 | 11096.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 952.41 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 22.42 | 1279.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 188.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 590.93 | 48094.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 106.32 | 5292.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 150.25 | 9938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.74 | 4738.75 | 1131.13 | 124704.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Other | 0.00 | 39005.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.76 | 1311.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 20.86 | 715.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1771.85 | 5467.55 |
Natural Gas | 1788.84 | 3606.69 |
Additional | 0.00 | 0.00 |
Total | 3560.69 | 9074.24 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 47.84 |
Space Heating | 0.00 |
Space Cooling | 87.50 |
Fans (All) | 52.09 |
Service Water Heating | 43.80 |
Receptacle Equipment | 152.32 |
Miscellaneous (All) | 481.92 |
Subtotal | 481.92 |
Natural Gas [MJ/m2] | |
Space Heating | 60.53 |
Service Water Heating | 99.70 |
Miscellaneous (All) | 317.90 |
Subtotal | 317.90 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.98 |
Space Heating | 7.57 |
Space Cooling | 10.94 |
Fans (All) | 6.51 |
Service Water Heating | 17.94 |
Receptacle Equipment | 38.76 |
Miscellaneous | 12.30 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2398. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 2482. | 8760. |
LTG_SCH_CORRIDOR | 2295. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8752.67 | 7.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8666.33 | 93.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8745.50 | 14.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8666.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 93.67 | 0.00 | 0.00 | 0.00 |
Average | 8754.47 | 5.53 | 0.00 | 0.00 | 0.00 |
Sum | 192598.33 | 121.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4151.67 | 2.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4149.33 | 4.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 4.67 | 0.00 | 0.00 | 0.00 |
Average | 288886.73 | 0.32 | 0.00 | 0.00 | 0.00 |
Sum | 6355508.00 | 7.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8635.83 | 124.17 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8690.00 | 70.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8740.33 | 19.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8744.00 | 16.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8637.33 | 122.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8736.00 | 24.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8736.83 | 23.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8674.17 | 85.83 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8687.00 | 73.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8635.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 124.17 | 0.00 | 0.00 | 0.00 |
Average | 8734.54 | 25.46 | 0.00 | 0.00 | 0.00 |
Sum | 192159.83 | 560.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59150.50 | 5.50 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 696010.00 | 14407.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2091477.17 | 23951.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4147.67 | 6.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4149.83 | 4.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 99945.00 | 413.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4143.83 | 10.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1228071.67 | 17643.33 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1230771.33 | 14943.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108266.00 | 3.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2091477.17 | 23951.83 | 0.00 | 0.00 | 0.00 |
Average | 285642.14 | 3244.91 | 0.00 | 0.00 | 0.00 |
Sum | 6284127.00 | 71388.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:02:00
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 1592.73 | 0.00 | 0.00 |
Sum | 0.00 | 35040.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 710417.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 2115429.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 1245715.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 2115429.00 | 0.00 | 0.00 |
Average | 0.00 | 241694.36 | 0.00 | 0.00 |
Sum | 0.00 | 5317276.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265639E+11 | 13919.20 | 27-JAN-22:00 | 0.60 | -4.2 | 0.805393E+10 | 4836.96 | 05-JAN-23:30 | 0.60 | -4.2 |
February | 0.222144E+11 | 12619.33 | 01-FEB-22:00 | -0.6 | -1.1 | 0.699328E+10 | 4836.92 | 02-FEB-22:19 | 0.00 | -2.9 |
March | 0.231546E+11 | 10653.31 | 12-MAR-10:33 | 12.23 | 3.02 | 0.739631E+10 | 4687.82 | 01-MAR-22:19 | 12.23 | 3.02 |
April | 0.226767E+11 | 10933.74 | 29-APR-10:33 | 20.20 | 8.15 | 0.708594E+10 | 4536.62 | 07-APR-22:10 | 20.20 | 8.15 |
May | 0.240697E+11 | 11179.43 | 20-MAY-10:33 | 22.40 | 8.51 | 0.740428E+10 | 4591.10 | 12-MAY-22:10 | 22.40 | 8.51 |
June | 0.250220E+11 | 11887.83 | 25-JUN-10:33 | 29.43 | 16.91 | 0.743731E+10 | 4766.28 | 09-JUN-22:10 | 29.43 | 16.91 |
July | 0.277736E+11 | 13328.34 | 28-JUL-21:00 | 25.00 | 14.27 | 0.796476E+10 | 4837.14 | 21-JUL-21:19 | 25.00 | 14.27 |
August | 0.296536E+11 | 15648.26 | 23-AUG-21:00 | 21.10 | 15.01 | 0.816809E+10 | 4837.13 | 04-AUG-21:10 | 21.10 | 15.01 |
September | 0.312292E+11 | 17729.10 | 08-SEP-21:00 | 16.10 | 12.69 | 0.793762E+10 | 4837.46 | 22-SEP-21:00 | 19.40 | 14.15 |
October | 0.333473E+11 | 18568.40 | 12-OCT-21:00 | 7.20 | 0.52 | 0.821127E+10 | 4837.24 | 20-OCT-21:10 | 14.22 | 8.62 |
November | 0.312094E+11 | 18079.09 | 03-NOV-21:00 | 5.60 | 2.41 | 0.794407E+10 | 4837.47 | 01-NOV-01:10 | 5.60 | 2.41 |
December | 0.300086E+11 | 17418.10 | 01-DEC-22:00 | 9.40 | 2.31 | 0.820004E+10 | 4837.03 | 15-DEC-04:19 | -7.6 | -10.7 |
Annual Sum or Average | 0.326923E+12 | 0.927969E+11 | ||||||||
Minimum of Months | 0.222144E+11 | 10653.31 | -0.6 | -4.2 | 0.699328E+10 | 4536.62 | -7.6 | -10.7 | ||
Maximum of Months | 0.333473E+11 | 18568.40 | 29.43 | 16.91 | 0.821127E+10 | 4837.47 | 29.43 | 16.91 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.330874E+10 | 4124.12 | 03-JAN-13:00 | 13.90 | 5.34 | 0.669235E+09 | 437.84 | 09-JAN-22:19 | 6.50 | 0.58 |
February | 0.320040E+10 | 4346.74 | 14-FEB-13:20 | 19.80 | 6.75 | 0.615066E+09 | 472.30 | 14-FEB-22:30 | 10.60 | 3.54 |
March | 0.357887E+10 | 3835.98 | 08-MAR-13:30 | 21.40 | 9.29 | 0.690509E+09 | 469.30 | 08-MAR-22:19 | 10.53 | 4.18 |
April | 0.370322E+10 | 2994.47 | 13-APR-13:05 | 23.98 | 9.13 | 0.701545E+09 | 491.80 | 13-APR-21:40 | 19.23 | 6.82 |
May | 0.379448E+10 | 2317.51 | 13-MAY-13:10 | 28.40 | 11.85 | 0.735246E+09 | 491.84 | 19-MAY-22:10 | 21.93 | 7.53 |
June | 0.421122E+10 | 2738.64 | 29-JUN-14:30 | 37.25 | 15.80 | 0.755310E+09 | 491.85 | 23-JUN-21:10 | 37.25 | 15.80 |
July | 0.486720E+10 | 2936.88 | 22-JUL-13:30 | 36.95 | 17.78 | 0.807675E+09 | 491.85 | 21-JUL-21:19 | 36.95 | 17.78 |
August | 0.519489E+10 | 3659.95 | 22-AUG-13:20 | 31.13 | 16.59 | 0.813316E+09 | 491.85 | 21-AUG-00:40 | 31.13 | 16.59 |
September | 0.513151E+10 | 4359.96 | 28-SEP-13:05 | 29.08 | 15.59 | 0.769891E+09 | 491.88 | 22-SEP-21:00 | 29.08 | 15.59 |
October | 0.490762E+10 | 4401.60 | 05-OCT-13:00 | 25.60 | 13.44 | 0.756280E+09 | 491.84 | 04-OCT-22:10 | 25.60 | 13.44 |
November | 0.401517E+10 | 4284.10 | 01-NOV-12:30 | 13.30 | 7.71 | 0.677945E+09 | 468.01 | 02-NOV-21:19 | 11.87 | 5.90 |
December | 0.342192E+10 | 4255.30 | 31-DEC-13:00 | 8.30 | 1.00 | 0.671572E+09 | 429.84 | 29-DEC-22:19 | 8.30 | 1.00 |
Annual Sum or Average | 0.493352E+11 | 0.866359E+10 | ||||||||
Minimum of Months | 0.320040E+10 | 2317.51 | 8.30 | 1.00 | 0.615066E+09 | 429.84 | 6.50 | 0.58 | ||
Maximum of Months | 0.519489E+10 | 4401.60 | 37.25 | 17.78 | 0.813316E+09 | 491.88 | 37.25 | 17.78 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244755E+10 | 1279.36 | 03-JAN-21:50 | 0.65 | -1.9 | 0.883352E+09 | 569.51 | 24-JAN-22:19 | 0.37 | -3.8 |
February | 0.228013E+10 | 1537.20 | 15-FEB-21:10 | 7.62 | 2.97 | 0.810091E+09 | 569.52 | 13-FEB-22:19 | 7.62 | 2.97 |
March | 0.262546E+10 | 1562.68 | 08-MAR-22:00 | 12.20 | 4.97 | 0.917987E+09 | 569.52 | 09-MAR-23:49 | 3.07 | -1.0 |
April | 0.277576E+10 | 1818.86 | 13-APR-21:00 | 21.10 | 7.69 | 0.909531E+09 | 569.55 | 11-APR-22:10 | 21.10 | 7.69 |
May | 0.299926E+10 | 1880.71 | 19-MAY-20:54 | 23.30 | 8.29 | 0.947246E+09 | 569.63 | 01-MAY-01:10 | 23.30 | 8.29 |
June | 0.329339E+10 | 2141.72 | 28-JUN-21:00 | 28.90 | 15.97 | 0.931524E+09 | 569.64 | 01-JUN-01:10 | 28.90 | 15.97 |
July | 0.362213E+10 | 2216.87 | 21-JUL-21:00 | 30.00 | 14.72 | 0.965298E+09 | 569.63 | 01-JUL-00:40 | 30.00 | 14.72 |
August | 0.363516E+10 | 2160.29 | 18-AUG-20:10 | 27.02 | 13.59 | 0.970060E+09 | 569.56 | 21-AUG-00:40 | 25.17 | 16.57 |
September | 0.331308E+10 | 1999.22 | 13-SEP-20:04 | 23.53 | 12.84 | 0.934025E+09 | 569.60 | 22-SEP-21:00 | 19.40 | 14.15 |
October | 0.305639E+10 | 1937.36 | 05-OCT-20:10 | 18.90 | 9.66 | 0.946870E+09 | 569.56 | 20-OCT-21:10 | 14.22 | 8.62 |
November | 0.257426E+10 | 1555.83 | 02-NOV-21:00 | 12.80 | 4.93 | 0.889344E+09 | 569.59 | 01-NOV-01:10 | 12.80 | 4.93 |
December | 0.244226E+10 | 1215.53 | 29-DEC-22:00 | 2.20 | -1.3 | 0.884596E+09 | 569.52 | 01-DEC-22:40 | 2.20 | -1.3 |
Annual Sum or Average | 0.350648E+11 | 0.109899E+11 | ||||||||
Minimum of Months | 0.228013E+10 | 1215.53 | 0.65 | -1.9 | 0.810091E+09 | 569.51 | 0.37 | -3.8 | ||
Maximum of Months | 0.363516E+10 | 2216.87 | 30.00 | 15.97 | 0.970060E+09 | 569.64 | 30.00 | 16.57 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153414E+10 | 818.92 | 01-JAN-13:00 | 13.30 | 4.92 | 0.158756E+09 | 102.53 | 05-JAN-22:10 | 3.72 | -1.3 |
February | 0.148368E+10 | 898.70 | 14-FEB-13:00 | 19.40 | 6.65 | 0.145932E+09 | 107.86 | 15-FEB-22:10 | 6.60 | 2.40 |
March | 0.183674E+10 | 878.47 | 26-MAR-10:33 | 14.80 | 5.60 | 0.171005E+09 | 108.47 | 09-MAR-22:10 | 14.80 | 5.60 |
April | 0.198935E+10 | 1027.96 | 29-APR-10:33 | 20.20 | 8.15 | 0.176022E+09 | 118.53 | 14-APR-21:19 | 20.20 | 8.15 |
May | 0.223473E+10 | 1224.51 | 19-MAY-20:54 | 23.30 | 8.29 | 0.191512E+09 | 120.46 | 17-MAY-21:00 | 23.30 | 8.29 |
June | 0.261572E+10 | 1899.41 | 29-JUN-20:00 | 26.70 | 13.56 | 0.195272E+09 | 120.46 | 23-JUN-21:10 | 26.70 | 13.56 |
July | 0.296345E+10 | 1912.38 | 21-JUL-20:00 | 30.60 | 12.57 | 0.204443E+09 | 120.46 | 01-JUL-00:40 | 30.60 | 12.57 |
August | 0.282588E+10 | 1804.51 | 18-AUG-20:00 | 27.20 | 13.67 | 0.204564E+09 | 120.46 | 21-AUG-00:00 | 24.40 | 16.61 |
September | 0.238865E+10 | 1449.80 | 01-SEP-20:00 | 22.80 | 14.95 | 0.193338E+09 | 120.46 | 22-SEP-21:00 | 19.40 | 14.15 |
October | 0.214398E+10 | 1253.22 | 02-OCT-20:00 | 18.90 | 14.94 | 0.185291E+09 | 120.45 | 04-OCT-22:10 | 17.70 | 10.79 |
November | 0.176679E+10 | 952.51 | 01-NOV-12:30 | 13.30 | 7.71 | 0.163986E+09 | 110.84 | 01-NOV-21:10 | 7.88 | 4.75 |
December | 0.154927E+10 | 840.60 | 31-DEC-13:00 | 8.30 | 1.00 | 0.157603E+09 | 103.69 | 01-DEC-22:10 | 8.30 | 1.00 |
Annual Sum or Average | 0.253324E+11 | 0.214773E+10 | ||||||||
Minimum of Months | 0.148368E+10 | 818.92 | 8.30 | 1.00 | 0.145932E+09 | 102.53 | 3.72 | -1.3 | ||
Maximum of Months | 0.296345E+10 | 1912.38 | 30.60 | 14.95 | 0.204564E+09 | 120.46 | 30.60 | 16.61 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.758757E+09 | 442.69 | 01-JAN-13:00 | 13.30 | 4.92 | 0.119647E+09 | 75.41 | 05-JAN-22:40 | 3.17 | -1.3 |
February | 0.753472E+09 | 489.45 | 14-FEB-13:20 | 19.80 | 6.75 | 0.109944E+09 | 79.57 | 15-FEB-22:40 | 6.30 | 2.24 |
March | 0.965720E+09 | 470.36 | 26-MAR-10:33 | 14.80 | 5.60 | 0.128461E+09 | 80.29 | 16-MAR-21:40 | 14.80 | 5.60 |
April | 0.105114E+10 | 551.22 | 29-APR-10:33 | 20.20 | 8.15 | 0.132526E+09 | 88.06 | 14-APR-22:10 | 20.20 | 8.15 |
May | 0.117834E+10 | 576.54 | 20-MAY-10:33 | 22.40 | 8.51 | 0.144272E+09 | 91.70 | 19-MAY-21:00 | 22.40 | 8.51 |
June | 0.133747E+10 | 844.61 | 28-JUN-20:30 | 29.45 | 16.12 | 0.148773E+09 | 92.66 | 23-JUN-21:10 | 29.45 | 16.12 |
July | 0.148909E+10 | 881.74 | 21-JUL-19:10 | 33.77 | 14.01 | 0.156942E+09 | 92.66 | 01-JUL-00:40 | 33.77 | 14.01 |
August | 0.142379E+10 | 794.64 | 18-AUG-20:10 | 27.02 | 13.59 | 0.156704E+09 | 92.66 | 21-AUG-00:00 | 24.40 | 16.61 |
September | 0.123943E+10 | 607.74 | 03-SEP-10:33 | 28.53 | 16.32 | 0.146548E+09 | 92.66 | 01-SEP-22:10 | 28.53 | 16.32 |
October | 0.112894E+10 | 587.79 | 01-OCT-12:00 | 25.60 | 14.51 | 0.139598E+09 | 91.91 | 02-OCT-21:40 | 18.30 | 13.96 |
November | 0.929217E+09 | 513.01 | 01-NOV-12:30 | 13.30 | 7.71 | 0.123247E+09 | 81.92 | 02-NOV-21:40 | 10.93 | 6.67 |
December | 0.757749E+09 | 454.17 | 31-DEC-13:00 | 8.30 | 1.00 | 0.118971E+09 | 76.52 | 01-DEC-22:40 | 8.30 | 1.00 |
Annual Sum or Average | 0.130131E+11 | 0.162563E+10 | ||||||||
Minimum of Months | 0.753472E+09 | 442.69 | 8.30 | 1.00 | 0.109944E+09 | 75.41 | 3.17 | -1.3 | ||
Maximum of Months | 0.148909E+10 | 881.74 | 33.77 | 16.32 | 0.156942E+09 | 92.66 | 33.77 | 16.61 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.489888E+11 | 37272.32 | 05-JAN-21:00 | 5.00 | -0.9 | 0.601836E+09 | 381.78 | 12-JAN-22:10 | 2.02 | 0.39 |
February | 0.446054E+11 | 37648.88 | 14-FEB-21:00 | 10.00 | 3.10 | 0.544723E+09 | 381.80 | 13-FEB-22:10 | 10.00 | 3.10 |
March | 0.504400E+11 | 37959.75 | 08-MAR-21:00 | 13.90 | 5.15 | 0.608141E+09 | 381.81 | 30-MAR-21:10 | 10.40 | 4.53 |
April | 0.498528E+11 | 38598.36 | 28-APR-20:00 | 22.20 | 8.52 | 0.590878E+09 | 381.84 | 07-APR-21:10 | 22.20 | 8.52 |
May | 0.522154E+11 | 38780.76 | 19-MAY-20:00 | 25.60 | 9.31 | 0.612164E+09 | 381.82 | 22-MAY-21:10 | 21.83 | 11.87 |
June | 0.517364E+11 | 39304.05 | 28-JUN-20:00 | 30.00 | 16.25 | 0.595282E+09 | 382.04 | 23-JUN-21:10 | 30.00 | 16.25 |
July | 0.537691E+11 | 39326.58 | 21-JUL-20:00 | 30.60 | 12.57 | 0.614083E+09 | 382.05 | 21-JUL-21:10 | 29.72 | 14.71 |
August | 0.537680E+11 | 39166.81 | 17-AUG-20:00 | 28.30 | 14.86 | 0.614912E+09 | 382.00 | 22-AUG-21:10 | 21.52 | 15.46 |
September | 0.511098E+11 | 38798.01 | 01-SEP-20:00 | 22.80 | 14.95 | 0.591507E+09 | 381.95 | 22-SEP-21:10 | 18.98 | 11.47 |
October | 0.514676E+11 | 38502.62 | 02-OCT-20:00 | 18.90 | 14.94 | 0.607551E+09 | 381.89 | 05-OCT-21:10 | 18.98 | 9.83 |
November | 0.484386E+11 | 37589.11 | 09-NOV-21:00 | 12.20 | 8.48 | 0.585818E+09 | 381.85 | 02-NOV-21:10 | 12.20 | 8.48 |
December | 0.488339E+11 | 37252.21 | 01-DEC-21:00 | 9.40 | 2.54 | 0.602149E+09 | 381.79 | 29-DEC-22:10 | 2.12 | -1.4 |
Annual Sum or Average | 0.605226E+12 | 0.716904E+10 | ||||||||
Minimum of Months | 0.446054E+11 | 37252.21 | 5.00 | -0.9 | 0.544723E+09 | 381.78 | 2.02 | -1.4 | ||
Maximum of Months | 0.537691E+11 | 39326.58 | 30.60 | 16.25 | 0.614912E+09 | 382.05 | 30.00 | 16.25 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.195499E+11 | 15548.85 | 01-JAN-13:00 | 13.30 | 4.92 | 0.103466E+11 | 6461.51 | 31-JAN-00:20 | 2.43 | 0.07 |
February | 0.181265E+11 | 15447.65 | 14-FEB-13:10 | 19.60 | 6.70 | 0.946926E+10 | 6461.81 | 11-FEB-02:20 | 19.60 | 6.70 |
March | 0.196169E+11 | 14107.45 | 11-MAR-13:30 | 16.40 | 4.98 | 0.106325E+11 | 6461.99 | 14-MAR-04:19 | 6.83 | 1.48 |
April | 0.194431E+11 | 11660.21 | 01-APR-13:30 | 21.65 | 7.61 | 0.104186E+11 | 6462.66 | 11-APR-22:10 | 17.02 | 5.74 |
May | 0.198226E+11 | 10486.97 | 19-MAY-21:05 | 23.12 | 8.19 | 0.107630E+11 | 6462.78 | 17-MAY-22:10 | 23.12 | 8.19 |
June | 0.208924E+11 | 11572.04 | 28-JUN-21:10 | 28.62 | 15.82 | 0.105376E+11 | 6462.77 | 01-JUN-00:00 | 28.62 | 15.82 |
July | 0.233169E+11 | 11832.93 | 21-JUL-21:10 | 29.72 | 14.71 | 0.109359E+11 | 6463.27 | 01-JUL-00:40 | 29.72 | 14.71 |
August | 0.244147E+11 | 12474.75 | 20-AUG-12:00 | 32.80 | 17.08 | 0.109933E+11 | 6462.70 | 23-AUG-22:10 | 19.40 | 14.62 |
September | 0.239799E+11 | 14297.04 | 28-SEP-13:10 | 29.08 | 15.59 | 0.105979E+11 | 6462.78 | 22-SEP-22:10 | 29.08 | 15.59 |
October | 0.238283E+11 | 15412.37 | 15-OCT-12:00 | 16.70 | 6.24 | 0.108243E+11 | 6462.64 | 06-OCT-22:10 | 16.70 | 6.24 |
November | 0.208963E+11 | 15963.22 | 23-NOV-11:00 | 8.90 | 2.63 | 0.103200E+11 | 6462.01 | 01-NOV-00:00 | 8.90 | 2.63 |
December | 0.200209E+11 | 16139.69 | 31-DEC-13:00 | 8.30 | 1.00 | 0.103977E+11 | 6461.43 | 20-DEC-00:20 | 8.30 | 1.00 |
Annual Sum or Average | 0.253908E+12 | 0.126237E+12 | ||||||||
Minimum of Months | 0.181265E+11 | 10486.97 | 8.30 | 1.00 | 0.946926E+10 | 6461.43 | 2.43 | 0.07 | ||
Maximum of Months | 0.244147E+11 | 16139.69 | 32.80 | 17.08 | 0.109933E+11 | 6463.27 | 29.72 | 15.82 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.583249E+11 | 33648.38 | 03-JAN-19:04 | 5.92 | 1.15 | 0.316594E+11 | 19185.05 | 28-JAN-02:20 | -2.4 | -5.6 |
February | 0.540059E+11 | 35366.03 | 14-FEB-22:10 | 10.60 | 3.54 | 0.288234E+11 | 19185.05 | 11-FEB-02:20 | 10.60 | 3.54 |
March | 0.617747E+11 | 35390.38 | 08-MAR-22:10 | 11.37 | 4.58 | 0.322219E+11 | 19185.19 | 14-MAR-04:19 | 6.83 | 1.48 |
April | 0.638417E+11 | 38014.37 | 13-APR-21:10 | 20.63 | 7.48 | 0.312351E+11 | 19186.10 | 11-APR-22:10 | 20.63 | 7.48 |
May | 0.682934E+11 | 38623.73 | 19-MAY-21:05 | 23.12 | 8.19 | 0.322918E+11 | 19188.52 | 01-MAY-01:10 | 23.12 | 8.19 |
June | 0.723429E+11 | 42286.57 | 28-JUN-21:10 | 28.62 | 15.82 | 0.314780E+11 | 19188.69 | 01-JUN-01:10 | 28.62 | 15.82 |
July | 0.787306E+11 | 43022.68 | 21-JUL-21:10 | 29.72 | 14.71 | 0.325360E+11 | 19188.64 | 01-JUL-00:40 | 29.72 | 14.71 |
August | 0.795559E+11 | 42641.71 | 18-AUG-21:10 | 25.73 | 12.99 | 0.327113E+11 | 19186.15 | 23-AUG-22:10 | 19.40 | 14.62 |
September | 0.747924E+11 | 41085.45 | 13-SEP-21:10 | 21.60 | 12.51 | 0.315719E+11 | 19186.54 | 22-SEP-21:00 | 19.40 | 14.15 |
October | 0.712623E+11 | 40348.54 | 06-OCT-21:10 | 19.90 | 11.23 | 0.324657E+11 | 19186.06 | 06-OCT-22:10 | 19.22 | 11.09 |
November | 0.617073E+11 | 35654.33 | 01-NOV-21:10 | 7.88 | 4.75 | 0.311853E+11 | 19186.69 | 01-NOV-01:10 | 7.88 | 4.75 |
December | 0.584580E+11 | 31706.79 | 29-DEC-22:10 | 2.12 | -1.4 | 0.317630E+11 | 19184.94 | 30-DEC-02:20 | -1.8 | -4.8 |
Annual Sum or Average | 0.803090E+12 | 0.379943E+12 | ||||||||
Minimum of Months | 0.540059E+11 | 31706.79 | 2.12 | -1.4 | 0.288234E+11 | 19184.94 | -2.4 | -5.6 | ||
Maximum of Months | 0.795559E+11 | 43022.68 | 29.72 | 15.82 | 0.327113E+11 | 19188.69 | 29.72 | 15.82 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.336116E+09 | 3689.21 | 01-JAN-16:01 | 14.95 | 5.48 | 96813289.70 | 56.69 | 24-JAN-04:19 | -1.7 | -4.2 |
February | 0.470074E+09 | 4013.98 | 14-FEB-16:01 | 22.02 | 7.76 | 87962728.51 | 56.69 | 15-FEB-22:10 | 6.60 | 2.40 |
March | 0.758172E+09 | 4018.33 | 08-MAR-16:01 | 22.70 | 8.91 | 98050432.96 | 56.69 | 13-MAR-21:19 | 12.07 | 3.61 |
April | 0.140095E+10 | 4142.18 | 26-APR-15:01 | 25.50 | 10.03 | 95472886.39 | 56.69 | 22-APR-23:30 | 25.50 | 10.03 |
May | 0.171276E+10 | 4187.38 | 20-MAY-15:01 | 26.78 | 10.96 | 98816564.29 | 56.69 | 26-MAY-21:40 | 17.07 | 10.41 |
June | 0.235031E+10 | 4199.66 | 19-JUN-18:01 | 28.62 | 10.19 | 95897760.61 | 56.69 | 24-JUN-04:00 | 20.00 | 14.66 |
July | 0.269876E+10 | 3532.25 | 06-JUL-08:61 | 25.87 | 16.03 | 99114844.01 | 56.70 | 21-JUL-21:10 | 29.72 | 14.71 |
August | 0.269845E+10 | 3521.26 | 17-AUG-08:61 | 25.78 | 17.70 | 99181108.64 | 56.69 | 10-AUG-04:00 | 25.78 | 17.70 |
September | 0.226173E+10 | 3698.60 | 21-SEP-08:61 | 18.77 | 10.46 | 95812012.78 | 56.69 | 04-SEP-00:49 | 18.77 | 10.46 |
October | 0.160365E+10 | 4084.04 | 31-OCT-15:01 | 23.80 | 8.59 | 98558910.31 | 56.69 | 03-OCT-00:10 | 23.80 | 8.59 |
November | 0.643192E+09 | 3710.78 | 03-NOV-15:01 | 12.70 | 2.73 | 94753861.69 | 56.69 | 01-NOV-01:49 | 12.70 | 2.73 |
December | 0.294807E+09 | 3679.31 | 30-DEC-16:01 | 10.82 | 2.31 | 96751089.36 | 56.69 | 26-DEC-04:19 | 10.82 | 2.31 |
Annual Sum or Average | 0.172290E+11 | 0.115719E+10 | ||||||||
Minimum of Months | 0.294807E+09 | 3521.26 | 10.82 | 2.31 | 87962728.51 | 56.69 | -1.7 | -4.2 | ||
Maximum of Months | 0.269876E+10 | 4199.66 | 28.62 | 17.70 | 99181108.64 | 56.70 | 29.72 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 70015220.61 | 3564.50 | 01-JAN-16:01 | 14.95 | 5.48 | 94870655.29 | 56.69 | 12-JAN-05:19 | -2.1 | -2.7 |
February | 0.149234E+09 | 3891.29 | 14-FEB-16:01 | 22.02 | 7.76 | 86724334.88 | 56.69 | 15-FEB-05:19 | 7.60 | 2.62 |
March | 0.319278E+09 | 4195.12 | 30-MAR-18:11 | 13.50 | 4.61 | 99027213.55 | 71.98 | 24-MAR-18:10 | 13.50 | 4.61 |
April | 0.919085E+09 | 4747.58 | 25-APR-16:21 | 24.40 | 9.58 | 0.101077E+09 | 80.65 | 24-APR-18:10 | 24.40 | 9.58 |
May | 0.142323E+10 | 4241.42 | 20-MAY-21:51 | 21.10 | 7.48 | 0.104589E+09 | 86.58 | 26-MAY-18:10 | 22.43 | 11.72 |
June | 0.219894E+10 | 4497.50 | 14-JUN-08:21 | 26.10 | 11.81 | 0.100214E+09 | 88.46 | 09-JUN-18:10 | 26.10 | 11.81 |
July | 0.246353E+10 | 3935.03 | 06-JUL-08:61 | 25.87 | 16.03 | 0.103510E+09 | 83.37 | 31-JUL-21:30 | 21.60 | 17.59 |
August | 0.228272E+10 | 4108.85 | 23-AUG-17:01 | 24.32 | 16.96 | 0.104492E+09 | 87.12 | 23-AUG-21:10 | 20.82 | 14.97 |
September | 0.160255E+10 | 4021.87 | 21-SEP-21:51 | 18.90 | 9.64 | 0.102425E+09 | 79.58 | 12-SEP-21:10 | 18.90 | 9.64 |
October | 0.818730E+09 | 3982.72 | 05-OCT-21:51 | 19.40 | 9.99 | 0.103155E+09 | 77.35 | 04-OCT-21:10 | 19.40 | 9.99 |
November | 0.186774E+09 | 3609.18 | 03-NOV-15:01 | 12.70 | 2.73 | 93334364.71 | 57.99 | 02-NOV-18:10 | 12.70 | 2.73 |
December | 48569695.65 | 3556.39 | 30-DEC-16:01 | 10.82 | 2.31 | 94495774.23 | 56.69 | 12-DEC-04:19 | 10.82 | 2.31 |
Annual Sum or Average | 0.124827E+11 | 0.118791E+10 | ||||||||
Minimum of Months | 48569695.65 | 3556.39 | 10.82 | 2.31 | 86724334.88 | 56.69 | -2.1 | -2.7 | ||
Maximum of Months | 0.246353E+10 | 4747.58 | 26.10 | 16.96 | 0.104589E+09 | 88.46 | 26.10 | 17.59 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.383327E+09 | 738.53 | 03-JAN-12:40 | 13.17 | 5.04 | 0.00 | 0.00 | 01-JAN-00:10 | 13.17 | 5.04 |
February | 0.366509E+09 | 755.59 | 14-FEB-13:00 | 19.40 | 6.65 | 0.00 | 0.00 | 01-FEB-00:10 | 19.40 | 6.65 |
March | 0.356128E+09 | 640.14 | 08-MAR-13:30 | 21.40 | 9.29 | 0.00 | 0.00 | 01-MAR-00:10 | 21.40 | 9.29 |
April | 0.376219E+09 | 473.65 | 13-APR-13:15 | 24.07 | 9.13 | 0.00 | 0.00 | 01-APR-00:10 | 24.07 | 9.13 |
May | 0.355278E+09 | 340.17 | 13-MAY-13:10 | 28.40 | 11.85 | 0.00 | 0.00 | 01-MAY-00:10 | 28.40 | 11.85 |
June | 0.461525E+09 | 378.04 | 29-JUN-14:30 | 37.25 | 15.80 | 0.00 | 0.00 | 01-JUN-00:10 | 37.25 | 15.80 |
July | 0.613955E+09 | 419.83 | 23-JUL-13:30 | 36.15 | 17.47 | 0.00 | 0.00 | 01-JUL-00:10 | 36.15 | 17.47 |
August | 0.688816E+09 | 543.15 | 22-AUG-13:30 | 31.40 | 16.68 | 0.00 | 0.00 | 01-AUG-00:10 | 31.40 | 16.68 |
September | 0.716852E+09 | 696.53 | 28-SEP-13:30 | 29.45 | 15.27 | 0.00 | 0.00 | 01-SEP-00:10 | 29.45 | 15.27 |
October | 0.689247E+09 | 749.62 | 19-OCT-12:30 | 20.55 | 8.60 | 0.00 | 0.00 | 01-OCT-00:10 | 20.55 | 8.60 |
November | 0.524053E+09 | 744.46 | 20-NOV-13:30 | 13.85 | 4.44 | 0.00 | 0.00 | 01-NOV-00:10 | 13.85 | 4.44 |
December | 0.424379E+09 | 760.21 | 31-DEC-13:40 | 9.43 | 1.41 | 0.00 | 0.00 | 01-DEC-00:10 | 9.43 | 1.41 |
Annual Sum or Average | 0.595629E+10 | 0.00 | ||||||||
Minimum of Months | 0.355278E+09 | 340.17 | 9.43 | 1.41 | 0.00 | 0.00 | 9.43 | 1.41 | ||
Maximum of Months | 0.716852E+09 | 760.21 | 37.25 | 17.47 | 0.00 | 0.00 | 37.25 | 17.47 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 42889996.06 | 824.14 | 01-JAN-09:02 | 2.67 | -1.3 | 95386949.29 | 56.69 | 20-JAN-04:19 | -4.8 | -4.8 |
February | 85597455.60 | 1066.58 | 14-FEB-16:01 | 22.02 | 7.76 | 86584230.41 | 56.69 | 15-FEB-22:19 | 6.50 | 2.35 |
March | 0.230547E+09 | 1112.29 | 08-MAR-16:01 | 22.70 | 8.91 | 97303205.62 | 58.95 | 13-MAR-20:49 | 12.35 | 3.74 |
April | 0.403654E+09 | 1209.89 | 29-APR-15:01 | 25.60 | 10.24 | 97528872.65 | 73.03 | 27-APR-21:49 | 25.60 | 10.24 |
May | 0.579941E+09 | 1226.11 | 15-MAY-18:01 | 27.85 | 10.46 | 0.102028E+09 | 75.91 | 26-MAY-21:49 | 16.88 | 10.38 |
June | 0.800847E+09 | 1287.37 | 17-JUN-08:31 | 26.27 | 12.41 | 98644744.34 | 75.92 | 05-JUN-21:49 | 26.27 | 12.41 |
July | 0.893374E+09 | 1160.45 | 06-JUL-08:61 | 25.87 | 16.03 | 0.102337E+09 | 77.38 | 31-JUL-21:49 | 21.53 | 17.38 |
August | 0.806547E+09 | 1121.47 | 01-AUG-08:31 | 26.13 | 15.31 | 0.102730E+09 | 77.25 | 23-AUG-21:00 | 19.40 | 14.71 |
September | 0.584162E+09 | 1154.16 | 30-SEP-21:51 | 18.00 | 8.68 | 0.100104E+09 | 73.85 | 12-SEP-21:10 | 18.00 | 8.68 |
October | 0.353581E+09 | 1158.93 | 09-OCT-15:01 | 22.98 | 12.17 | 99768838.08 | 74.05 | 02-OCT-21:49 | 22.98 | 12.17 |
November | 0.141398E+09 | 1010.06 | 02-NOV-18:11 | 15.00 | 7.63 | 93115314.79 | 56.69 | 02-NOV-22:10 | 10.00 | 7.26 |
December | 33677682.54 | 957.76 | 01-DEC-19:02 | 11.52 | 3.77 | 95083824.01 | 56.69 | 26-DEC-04:19 | 0.03 | -1.1 |
Annual Sum or Average | 0.495622E+10 | 0.117061E+10 | ||||||||
Minimum of Months | 33677682.54 | 824.14 | 2.67 | -1.3 | 86584230.41 | 56.69 | -4.8 | -4.8 | ||
Maximum of Months | 0.893374E+09 | 1287.37 | 27.85 | 16.03 | 0.102730E+09 | 77.38 | 26.27 | 17.38 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.330824E+09 | 3242.55 | 02-JAN-09:01 | 1.65 | -1.2 | 97105846.51 | 56.69 | 25-JAN-05:19 | -3.0 | -5.1 |
February | 0.423975E+09 | 3507.19 | 14-FEB-16:01 | 22.02 | 7.76 | 88219924.03 | 56.69 | 14-FEB-22:30 | 10.60 | 3.54 |
March | 0.824973E+09 | 3482.64 | 13-MAR-15:01 | 21.32 | 7.47 | 98476201.50 | 56.69 | 08-MAR-22:49 | 21.32 | 7.47 |
April | 0.157988E+10 | 3633.36 | 29-APR-15:01 | 25.60 | 10.24 | 95853606.51 | 56.69 | 15-APR-01:00 | 25.60 | 10.24 |
May | 0.190028E+10 | 3668.12 | 20-MAY-15:01 | 26.78 | 10.96 | 99115265.96 | 56.69 | 22-MAY-01:10 | 19.82 | 13.13 |
June | 0.256512E+10 | 3693.44 | 14-JUN-08:61 | 25.37 | 11.65 | 95999183.05 | 56.69 | 05-JUN-21:30 | 25.37 | 11.65 |
July | 0.296657E+10 | 3233.10 | 04-JUL-08:61 | 24.78 | 18.10 | 99135473.54 | 56.69 | 11-JUL-02:20 | 21.47 | 15.73 |
August | 0.289658E+10 | 3182.24 | 17-AUG-08:61 | 25.78 | 17.70 | 99239288.04 | 56.69 | 14-AUG-04:49 | 25.78 | 17.70 |
September | 0.232937E+10 | 3453.48 | 21-SEP-08:61 | 18.77 | 10.46 | 95928058.04 | 56.69 | 01-SEP-03:00 | 18.77 | 10.46 |
October | 0.161206E+10 | 3578.72 | 31-OCT-15:01 | 23.80 | 8.59 | 98802000.97 | 56.69 | 03-OCT-01:30 | 23.80 | 8.59 |
November | 0.650295E+09 | 3290.07 | 07-NOV-09:01 | 4.87 | 0.96 | 95019243.43 | 56.69 | 01-NOV-01:49 | 4.87 | 0.96 |
December | 0.281982E+09 | 3233.59 | 19-DEC-09:01 | 0.87 | -3.3 | 97133274.71 | 56.69 | 08-DEC-04:19 | 0.87 | -3.3 |
Annual Sum or Average | 0.183619E+11 | 0.116003E+10 | ||||||||
Minimum of Months | 0.281982E+09 | 3182.24 | 0.87 | -3.3 | 88219924.03 | 56.69 | -3.0 | -5.1 | ||
Maximum of Months | 0.296657E+10 | 3693.44 | 26.78 | 18.10 | 99239288.04 | 56.69 | 25.78 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 64028709.20 | 3085.96 | 01-JAN-09:02 | 2.67 | -1.3 | 94843477.38 | 56.69 | 20-JAN-04:19 | -4.8 | -4.8 |
February | 0.120097E+09 | 3405.53 | 14-FEB-16:01 | 22.02 | 7.76 | 86548220.10 | 56.69 | 14-FEB-22:10 | 10.60 | 3.54 |
March | 0.400442E+09 | 3405.15 | 13-MAR-15:01 | 21.32 | 7.47 | 98751393.38 | 60.41 | 13-MAR-20:40 | 13.00 | 4.07 |
April | 0.114695E+10 | 4021.85 | 28-APR-08:51 | 18.30 | 7.75 | 99768225.04 | 76.12 | 27-APR-21:40 | 18.30 | 7.75 |
May | 0.160422E+10 | 4135.83 | 14-MAY-08:51 | 21.10 | 9.79 | 0.104286E+09 | 77.56 | 26-MAY-21:40 | 17.07 | 10.41 |
June | 0.233179E+10 | 4439.04 | 20-JUN-08:32 | 22.40 | 10.18 | 0.101605E+09 | 79.07 | 13-JUN-21:00 | 22.40 | 10.18 |
July | 0.263245E+10 | 4113.04 | 04-JUL-08:61 | 24.78 | 18.10 | 0.105559E+09 | 81.56 | 31-JUL-21:30 | 21.60 | 17.59 |
August | 0.238930E+10 | 3990.85 | 07-AUG-08:32 | 24.47 | 14.90 | 0.106097E+09 | 83.22 | 03-AUG-21:10 | 24.47 | 14.90 |
September | 0.162654E+10 | 3859.75 | 03-SEP-08:32 | 24.83 | 14.60 | 0.102875E+09 | 78.65 | 12-SEP-21:10 | 21.32 | 12.19 |
October | 0.867277E+09 | 3494.30 | 02-OCT-08:51 | 20.60 | 13.98 | 0.101930E+09 | 77.10 | 02-OCT-21:40 | 18.30 | 13.96 |
November | 0.195184E+09 | 3202.43 | 07-NOV-09:01 | 4.87 | 0.96 | 93378087.19 | 56.69 | 01-NOV-01:30 | 4.87 | 0.96 |
December | 47107848.88 | 3078.35 | 30-DEC-09:02 | 1.15 | -2.7 | 94343610.37 | 56.69 | 15-DEC-04:19 | 1.15 | -2.7 |
Annual Sum or Average | 0.134254E+11 | 0.118998E+10 | ||||||||
Minimum of Months | 47107848.88 | 3078.35 | 1.15 | -2.7 | 86548220.10 | 56.69 | -4.8 | -4.8 | ||
Maximum of Months | 0.263245E+10 | 4439.04 | 24.83 | 18.10 | 0.106097E+09 | 83.22 | 24.47 | 17.59 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.246727E+10 | 1463.05 | 01-JAN-13:00 | 13.30 | 4.92 | 0.125999E+10 | 809.76 | 03-JAN-22:40 | 0.00 | -2.3 |
February | 0.242380E+10 | 1570.25 | 14-FEB-13:30 | 20.00 | 6.81 | 0.115384E+10 | 841.46 | 15-FEB-22:40 | 6.30 | 2.24 |
March | 0.299048E+10 | 1492.57 | 12-MAR-10:33 | 12.23 | 3.02 | 0.135243E+10 | 854.66 | 13-MAR-21:49 | 12.62 | 3.92 |
April | 0.327883E+10 | 1695.99 | 29-APR-10:33 | 20.20 | 8.15 | 0.140603E+10 | 917.86 | 28-APR-21:49 | 20.20 | 8.15 |
May | 0.360657E+10 | 1756.47 | 20-MAY-10:33 | 22.40 | 8.51 | 0.151165E+10 | 949.85 | 19-MAY-21:00 | 22.40 | 8.51 |
June | 0.405134E+10 | 2640.29 | 23-JUN-18:17 | 33.17 | 12.63 | 0.153494E+10 | 951.90 | 23-JUN-21:10 | 26.60 | 15.77 |
July | 0.452232E+10 | 2796.98 | 21-JUL-18:25 | 35.25 | 14.38 | 0.161510E+10 | 951.88 | 01-JUL-00:40 | 35.25 | 14.38 |
August | 0.453466E+10 | 2632.01 | 18-AUG-18:15 | 31.67 | 15.79 | 0.162110E+10 | 951.87 | 21-AUG-00:49 | 24.78 | 16.59 |
September | 0.398598E+10 | 2141.93 | 29-SEP-15:03 | 29.63 | 15.11 | 0.154867E+10 | 951.88 | 22-SEP-21:00 | 29.63 | 15.11 |
October | 0.364570E+10 | 2141.91 | 02-OCT-15:03 | 26.65 | 15.17 | 0.150491E+10 | 951.85 | 06-OCT-22:10 | 19.22 | 11.09 |
November | 0.290499E+10 | 1631.26 | 01-NOV-12:30 | 13.30 | 7.71 | 0.130468E+10 | 862.69 | 01-NOV-21:40 | 8.13 | 4.88 |
December | 0.245112E+10 | 1457.99 | 31-DEC-13:00 | 8.30 | 1.00 | 0.124175E+10 | 785.82 | 01-DEC-00:10 | 8.30 | 1.00 |
Annual Sum or Average | 0.408631E+11 | 0.170551E+11 | ||||||||
Minimum of Months | 0.242380E+10 | 1457.99 | 8.30 | 1.00 | 0.115384E+10 | 785.82 | 0.00 | -2.3 | ||
Maximum of Months | 0.453466E+10 | 2796.98 | 35.25 | 15.79 | 0.162110E+10 | 951.90 | 35.25 | 16.59 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.299672E+09 | 3918.34 | 09-JAN-16:01 | 14.45 | 4.55 | 96302802.86 | 56.69 | 19-JAN-05:19 | -3.0 | -3.1 |
February | 0.443925E+09 | 4268.16 | 14-FEB-16:01 | 22.02 | 7.76 | 87615400.41 | 56.69 | 15-FEB-22:19 | 6.50 | 2.35 |
March | 0.696967E+09 | 4248.58 | 07-MAR-16:01 | 21.52 | 8.96 | 97735188.67 | 56.69 | 13-MAR-00:30 | 2.50 | -2.1 |
April | 0.135216E+10 | 4403.81 | 13-APR-15:01 | 25.10 | 9.79 | 95308208.01 | 56.70 | 17-APR-04:00 | 10.00 | 2.64 |
May | 0.169003E+10 | 4459.32 | 20-MAY-15:01 | 26.78 | 10.96 | 98676946.46 | 56.69 | 21-MAY-02:39 | 16.30 | 11.85 |
June | 0.241755E+10 | 4466.28 | 20-JUN-15:01 | 31.10 | 11.59 | 95870450.72 | 56.70 | 06-JUN-22:40 | 31.10 | 11.59 |
July | 0.279734E+10 | 3809.49 | 06-JUL-08:61 | 25.87 | 16.03 | 99109949.84 | 56.70 | 07-JUL-21:30 | 18.05 | 16.01 |
August | 0.276887E+10 | 3715.54 | 17-AUG-08:61 | 25.78 | 17.70 | 99146576.04 | 56.70 | 29-AUG-21:40 | 19.60 | 14.88 |
September | 0.221234E+10 | 3812.63 | 21-SEP-08:61 | 18.77 | 10.46 | 95711159.96 | 56.70 | 06-SEP-22:40 | 18.77 | 10.46 |
October | 0.148026E+10 | 4335.51 | 31-OCT-15:01 | 23.80 | 8.59 | 98303319.59 | 56.69 | 02-OCT-21:00 | 23.80 | 8.59 |
November | 0.541686E+09 | 3945.86 | 06-NOV-16:01 | 14.40 | 4.29 | 94351578.70 | 56.69 | 01-NOV-03:49 | 14.40 | 4.29 |
December | 0.256275E+09 | 3913.95 | 31-DEC-16:01 | 9.82 | 1.41 | 96220396.59 | 56.69 | 22-DEC-04:19 | 9.82 | 1.41 |
Annual Sum or Average | 0.169571E+11 | 0.115435E+10 | ||||||||
Minimum of Months | 0.256275E+09 | 3715.54 | 9.82 | 1.41 | 87615400.41 | 56.69 | -3.0 | -3.1 | ||
Maximum of Months | 0.279734E+10 | 4466.28 | 31.10 | 17.70 | 99146576.04 | 56.70 | 31.10 | 16.01 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 60836558.30 | 3771.52 | 05-JAN-16:01 | 15.63 | 6.64 | 94203630.33 | 56.69 | 20-JAN-04:19 | -4.8 | -4.8 |
February | 0.132166E+09 | 4117.31 | 14-FEB-16:01 | 22.02 | 7.76 | 86308844.59 | 56.69 | 14-FEB-05:19 | 22.02 | 7.76 |
March | 0.269296E+09 | 4558.62 | 30-MAR-18:11 | 13.50 | 4.61 | 98893408.08 | 76.64 | 24-MAR-18:10 | 13.50 | 4.61 |
April | 0.875876E+09 | 5046.55 | 25-APR-16:21 | 24.40 | 9.58 | 0.101598E+09 | 86.21 | 24-APR-18:10 | 24.40 | 9.58 |
May | 0.142584E+10 | 4516.02 | 20-MAY-21:51 | 21.10 | 7.48 | 0.104761E+09 | 91.77 | 26-MAY-18:10 | 22.43 | 11.72 |
June | 0.230005E+10 | 4752.96 | 14-JUN-08:21 | 26.10 | 11.81 | 0.100232E+09 | 93.24 | 09-JUN-18:10 | 26.10 | 11.81 |
July | 0.260208E+10 | 4141.70 | 06-JUL-08:61 | 25.87 | 16.03 | 0.103167E+09 | 84.19 | 31-JUL-21:40 | 21.57 | 17.49 |
August | 0.238975E+10 | 4358.44 | 23-AUG-17:01 | 24.32 | 16.96 | 0.104207E+09 | 89.72 | 23-AUG-21:10 | 20.82 | 14.97 |
September | 0.157905E+10 | 4225.08 | 21-SEP-21:51 | 18.90 | 9.64 | 0.102031E+09 | 79.23 | 12-SEP-21:10 | 18.90 | 9.64 |
October | 0.707781E+09 | 4198.38 | 19-OCT-15:01 | 22.80 | 8.67 | 0.103061E+09 | 76.84 | 04-OCT-21:10 | 22.80 | 8.67 |
November | 0.135403E+09 | 3915.61 | 02-NOV-18:11 | 15.00 | 7.63 | 92724719.61 | 58.70 | 02-NOV-18:10 | 15.00 | 7.63 |
December | 39376896.12 | 3753.56 | 30-DEC-16:01 | 10.82 | 2.31 | 93818253.77 | 56.69 | 08-DEC-04:19 | 10.82 | 2.31 |
Annual Sum or Average | 0.125175E+11 | 0.118501E+10 | ||||||||
Minimum of Months | 39376896.12 | 3753.56 | 10.82 | 2.31 | 86308844.59 | 56.69 | -4.8 | -4.8 | ||
Maximum of Months | 0.260208E+10 | 5046.55 | 26.10 | 16.96 | 0.104761E+09 | 93.24 | 26.10 | 17.49 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.748631E+09 | 1880.71 | 09-JAN-16:01 | 14.45 | 4.55 | 98113681.48 | 56.69 | 03-JAN-23:10 | 14.45 | 4.55 |
February | 0.732664E+09 | 2029.23 | 14-FEB-16:01 | 22.02 | 7.76 | 88826323.67 | 56.69 | 15-FEB-23:00 | 5.60 | 2.15 |
March | 0.736300E+09 | 1994.15 | 13-MAR-15:01 | 21.32 | 7.47 | 98460887.49 | 56.69 | 12-MAR-23:30 | 21.32 | 7.47 |
April | 0.839080E+09 | 2055.24 | 13-APR-15:01 | 25.10 | 9.79 | 95472113.35 | 56.69 | 22-APR-23:10 | 12.93 | 4.47 |
May | 0.866962E+09 | 2062.34 | 20-MAY-15:01 | 26.78 | 10.96 | 98709314.87 | 56.69 | 21-MAY-23:10 | 21.78 | 14.19 |
June | 0.113683E+10 | 2049.47 | 19-JUN-15:01 | 27.88 | 9.73 | 95817701.35 | 56.69 | 24-JUN-04:10 | 20.92 | 14.70 |
July | 0.145875E+10 | 1782.21 | 06-JUL-08:61 | 25.87 | 16.03 | 99077569.03 | 56.69 | 11-JUL-02:30 | 21.10 | 15.61 |
August | 0.156368E+10 | 1794.43 | 17-AUG-08:61 | 25.78 | 17.70 | 99124567.88 | 56.69 | 09-AUG-21:10 | 25.78 | 17.70 |
September | 0.151396E+10 | 1855.17 | 21-SEP-08:61 | 18.77 | 10.46 | 95771913.95 | 56.69 | 05-SEP-00:49 | 18.77 | 10.46 |
October | 0.137823E+10 | 2070.88 | 31-OCT-15:01 | 23.80 | 8.59 | 98788542.19 | 56.69 | 11-OCT-02:39 | 23.80 | 8.59 |
November | 0.994927E+09 | 1878.10 | 20-NOV-16:01 | 14.63 | 5.01 | 95488412.68 | 56.69 | 01-NOV-02:30 | 14.63 | 5.01 |
December | 0.818689E+09 | 1882.24 | 31-DEC-16:01 | 9.82 | 1.41 | 98087970.43 | 56.69 | 28-DEC-22:10 | 9.82 | 1.41 |
Annual Sum or Average | 0.127887E+11 | 0.116174E+10 | ||||||||
Minimum of Months | 0.732664E+09 | 1782.21 | 9.82 | 1.41 | 88826323.67 | 56.69 | 5.60 | 1.41 | ||
Maximum of Months | 0.156368E+10 | 2070.88 | 27.88 | 17.70 | 99124567.88 | 56.69 | 25.78 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.308023E+11 | 17191.18 | 05-JAN-22:50 | 2.98 | -1.4 | 0.190349E+11 | 11347.60 | 20-JAN-04:19 | -4.8 | -4.8 |
February | 0.288407E+11 | 18519.41 | 14-FEB-23:00 | 10.60 | 3.54 | 0.172748E+11 | 11347.53 | 03-FEB-04:19 | 10.60 | 3.54 |
March | 0.344763E+11 | 19102.19 | 16-MAR-21:10 | 14.17 | 4.07 | 0.193036E+11 | 11347.56 | 14-MAR-04:19 | 14.17 | 4.07 |
April | 0.366800E+11 | 21133.33 | 28-APR-21:10 | 19.90 | 7.11 | 0.186882E+11 | 11348.93 | 11-APR-22:10 | 19.90 | 7.11 |
May | 0.403959E+11 | 21965.33 | 19-MAY-21:05 | 23.12 | 8.19 | 0.193361E+11 | 11372.75 | 31-MAY-21:19 | 21.37 | 8.56 |
June | 0.425625E+11 | 23314.51 | 28-JUN-21:20 | 28.33 | 15.66 | 0.187591E+11 | 11388.40 | 16-JUN-21:19 | 28.33 | 15.66 |
July | 0.452329E+11 | 23457.06 | 21-JUL-21:20 | 29.43 | 14.70 | 0.193101E+11 | 11391.27 | 18-JUL-21:19 | 29.43 | 14.70 |
August | 0.444004E+11 | 22744.20 | 17-AUG-22:00 | 27.20 | 14.57 | 0.193905E+11 | 11381.22 | 22-AUG-21:19 | 21.33 | 15.41 |
September | 0.402991E+11 | 21770.18 | 01-SEP-21:20 | 20.73 | 13.98 | 0.187018E+11 | 11352.00 | 01-SEP-21:19 | 20.73 | 13.98 |
October | 0.372797E+11 | 21237.71 | 02-OCT-21:52 | 18.30 | 13.73 | 0.192428E+11 | 11348.91 | 06-OCT-22:10 | 19.22 | 11.09 |
November | 0.319324E+11 | 18819.77 | 02-NOV-21:10 | 12.33 | 5.44 | 0.185207E+11 | 11347.52 | 28-NOV-04:19 | -0.8 | -3.5 |
December | 0.304150E+11 | 17703.25 | 01-DEC-22:20 | 8.50 | 2.01 | 0.190058E+11 | 11347.56 | 15-DEC-04:19 | -7.6 | -10.7 |
Annual Sum or Average | 0.443317E+12 | 0.226569E+12 | ||||||||
Minimum of Months | 0.288407E+11 | 17191.18 | 2.98 | -1.4 | 0.172748E+11 | 11347.52 | -7.6 | -10.7 | ||
Maximum of Months | 0.452329E+11 | 23457.06 | 29.43 | 15.66 | 0.193905E+11 | 11391.27 | 29.43 | 15.66 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.343747E+11 | 18973.23 | 05-JAN-22:10 | 3.72 | -1.3 | 0.191757E+11 | 11347.62 | 20-JAN-04:19 | -4.8 | -4.8 |
February | 0.320964E+11 | 20072.23 | 14-FEB-23:00 | 10.60 | 3.54 | 0.173755E+11 | 11347.60 | 03-FEB-04:19 | 10.60 | 3.54 |
March | 0.381336E+11 | 20715.50 | 16-MAR-21:10 | 14.17 | 4.07 | 0.193678E+11 | 11347.64 | 14-MAR-04:19 | 14.17 | 4.07 |
April | 0.400070E+11 | 22422.38 | 28-APR-21:10 | 19.90 | 7.11 | 0.187115E+11 | 11348.93 | 11-APR-22:10 | 19.90 | 7.11 |
May | 0.436116E+11 | 23182.57 | 19-MAY-21:05 | 23.12 | 8.19 | 0.193472E+11 | 11389.96 | 31-MAY-21:19 | 21.37 | 8.56 |
June | 0.454347E+11 | 24501.69 | 27-JUN-21:20 | 28.30 | 13.90 | 0.187610E+11 | 11398.16 | 16-JUN-21:19 | 28.30 | 13.90 |
July | 0.480394E+11 | 24642.75 | 21-JUL-21:20 | 29.43 | 14.70 | 0.193110E+11 | 11398.93 | 18-JUL-21:19 | 29.43 | 14.70 |
August | 0.471981E+11 | 23922.26 | 17-AUG-21:20 | 26.87 | 14.49 | 0.193918E+11 | 11388.80 | 22-AUG-21:19 | 21.33 | 15.41 |
September | 0.430508E+11 | 22955.65 | 01-SEP-21:20 | 20.73 | 13.98 | 0.187083E+11 | 11363.29 | 01-SEP-21:19 | 20.73 | 13.98 |
October | 0.403833E+11 | 22379.31 | 02-OCT-21:52 | 18.30 | 13.73 | 0.192819E+11 | 11348.91 | 06-OCT-22:10 | 19.22 | 11.09 |
November | 0.353338E+11 | 20472.99 | 08-NOV-22:20 | 13.33 | 7.14 | 0.186057E+11 | 11347.57 | 28-NOV-04:19 | -0.8 | -3.5 |
December | 0.339646E+11 | 19549.53 | 01-DEC-22:10 | 8.95 | 2.17 | 0.191568E+11 | 11347.61 | 26-DEC-04:19 | 0.03 | -1.1 |
Annual Sum or Average | 0.481628E+12 | 0.227194E+12 | ||||||||
Minimum of Months | 0.320964E+11 | 18973.23 | 3.72 | -1.3 | 0.173755E+11 | 11347.57 | -4.8 | -4.8 | ||
Maximum of Months | 0.480394E+11 | 24642.75 | 29.43 | 14.70 | 0.193918E+11 | 11398.93 | 29.43 | 15.41 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.476945E+11 | 26506.96 | 01-JAN-11:40 | 9.83 | 3.02 | 0.188211E+11 | 11319.53 | 14-JAN-18:19 | 3.30 | -2.2 |
February | 0.439066E+11 | 27235.55 | 14-FEB-11:40 | 16.47 | 5.70 | 0.170048E+11 | 11319.54 | 18-FEB-18:19 | 9.63 | 3.33 |
March | 0.504793E+11 | 28224.16 | 12-MAR-10:33 | 12.23 | 3.02 | 0.188466E+11 | 11319.63 | 25-MAR-17:19 | 19.27 | 5.85 |
April | 0.513375E+11 | 29390.36 | 29-APR-10:33 | 20.20 | 8.15 | 0.182473E+11 | 11319.64 | 08-APR-17:19 | 20.20 | 8.15 |
May | 0.542712E+11 | 29508.92 | 20-MAY-10:33 | 22.40 | 8.51 | 0.188635E+11 | 11319.63 | 13-MAY-17:19 | 22.40 | 8.51 |
June | 0.547874E+11 | 30159.20 | 29-JUN-10:40 | 32.60 | 16.86 | 0.182635E+11 | 11319.64 | 10-JUN-17:19 | 32.60 | 16.86 |
July | 0.575530E+11 | 30445.55 | 23-JUL-10:40 | 31.83 | 17.15 | 0.188681E+11 | 11319.63 | 29-JUL-17:19 | 29.80 | 16.42 |
August | 0.571327E+11 | 30405.98 | 20-AUG-10:40 | 30.17 | 17.03 | 0.188750E+11 | 11319.63 | 19-AUG-17:19 | 30.17 | 17.03 |
September | 0.535040E+11 | 30217.25 | 03-SEP-10:40 | 28.53 | 16.32 | 0.182583E+11 | 11319.83 | 23-SEP-17:19 | 19.63 | 15.23 |
October | 0.523798E+11 | 29460.09 | 01-OCT-10:33 | 22.97 | 13.29 | 0.188528E+11 | 11319.84 | 28-OCT-17:19 | 16.87 | 5.69 |
November | 0.478053E+11 | 27609.10 | 01-NOV-10:40 | 13.13 | 7.69 | 0.182263E+11 | 11319.91 | 04-NOV-17:19 | 5.93 | 2.84 |
December | 0.474922E+11 | 26457.27 | 30-DEC-11:50 | 8.03 | 1.40 | 0.188203E+11 | 11319.76 | 02-DEC-18:19 | 8.03 | 1.40 |
Annual Sum or Average | 0.618344E+12 | 0.221948E+12 | ||||||||
Minimum of Months | 0.439066E+11 | 26457.27 | 8.03 | 1.40 | 0.170048E+11 | 11319.53 | 3.30 | -2.2 | ||
Maximum of Months | 0.575530E+11 | 30445.55 | 32.60 | 17.15 | 0.188750E+11 | 11319.91 | 32.60 | 17.03 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.485218E+10 | 3529.09 | 01-JAN-13:00 | 13.30 | 4.92 | 0.129858E+10 | 802.08 | 02-JAN-22:30 | 2.80 | -0.5 |
February | 0.508149E+10 | 3989.04 | 14-FEB-13:30 | 20.00 | 6.81 | 0.119617E+10 | 873.02 | 14-FEB-22:40 | 10.60 | 3.54 |
March | 0.679681E+10 | 3571.93 | 08-MAR-11:33 | 17.07 | 7.88 | 0.138592E+10 | 886.98 | 13-MAR-21:40 | 12.43 | 3.82 |
April | 0.768644E+10 | 4277.73 | 13-APR-15:01 | 25.10 | 9.79 | 0.145112E+10 | 980.43 | 13-APR-21:40 | 19.23 | 6.82 |
May | 0.864732E+10 | 5047.72 | 20-MAY-14:20 | 25.97 | 10.20 | 0.157562E+10 | 1007.37 | 19-MAY-21:19 | 25.97 | 10.20 |
June | 0.101352E+11 | 6870.34 | 28-JUN-15:03 | 38.40 | 14.30 | 0.161119E+10 | 1007.46 | 23-JUN-21:10 | 38.40 | 14.30 |
July | 0.115354E+11 | 6934.32 | 22-JUL-13:30 | 36.95 | 17.78 | 0.169747E+10 | 1007.49 | 01-JUL-00:40 | 36.95 | 17.78 |
August | 0.113486E+11 | 6997.47 | 21-AUG-14:10 | 32.20 | 18.41 | 0.169818E+10 | 1007.44 | 21-AUG-00:40 | 32.20 | 18.41 |
September | 0.967050E+10 | 6865.97 | 03-SEP-13:30 | 31.95 | 16.76 | 0.160058E+10 | 1007.40 | 12-SEP-22:10 | 19.22 | 11.92 |
October | 0.828775E+10 | 6143.87 | 01-OCT-13:30 | 27.75 | 13.90 | 0.152509E+10 | 1004.08 | 02-OCT-21:40 | 18.30 | 13.96 |
November | 0.639128E+10 | 3926.49 | 01-NOV-12:30 | 13.30 | 7.71 | 0.131330E+10 | 881.61 | 02-NOV-21:30 | 11.40 | 6.31 |
December | 0.470074E+10 | 3622.90 | 31-DEC-13:00 | 8.30 | 1.00 | 0.129231E+10 | 794.75 | 01-DEC-22:40 | 8.30 | 1.00 |
Annual Sum or Average | 0.951337E+11 | 0.176455E+11 | ||||||||
Minimum of Months | 0.470074E+10 | 3529.09 | 8.30 | 1.00 | 0.119617E+10 | 794.75 | 2.80 | -0.5 | ||
Maximum of Months | 0.115354E+11 | 6997.47 | 38.40 | 18.41 | 0.169818E+10 | 1007.49 | 38.40 | 18.41 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 17929336.24 | 378.72 | 19-JAN-07:10 | -2.8 |
February | 1637261.74 | 209.17 | 06-FEB-07:10 | -5.4 |
March | 4043.32 | 4.16 | 04-MAR-06:04 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 388594.99 | 175.27 | 26-OCT-06:20 | -1.7 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 11704526.39 | 449.31 | 09-DEC-07:30 | -2.8 |
Annual Sum or Average | 31663762.68 | |||
Minimum of Months | 0.00 | 0.00 | -5.4 | |
Maximum of Months | 17929336.24 | 449.31 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 916642.56 | 52.85 | 19-JAN-11:40 | 0.20 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.13 |
Annual Sum or Average | 916642.56 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 916642.56 | 52.85 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.372247E+09 | 2132.53 | 17-JAN-09:01 | -2.5 |
February | 0.229984E+09 | 2092.25 | 05-FEB-09:01 | -5.0 |
March | 72823016.23 | 1422.84 | 03-MAR-16:03 | 9.40 |
April | 6281736.71 | 1155.72 | 21-APR-08:03 | 12.67 |
May | 3078734.03 | 1010.93 | 25-MAY-08:03 | 13.68 |
June | 1126734.87 | 887.44 | 09-JUN-08:03 | 12.88 |
July | 673289.89 | 570.63 | 02-JUL-08:04 | 21.97 |
August | 692968.11 | 611.24 | 23-AUG-08:04 | 19.13 |
September | 1261242.26 | 786.76 | 08-SEP-08:03 | 15.10 |
October | 35850035.51 | 2063.39 | 25-OCT-08:61 | 0.22 |
November | 97891141.54 | 1425.72 | 10-NOV-19:02 | 6.10 |
December | 0.383229E+09 | 2112.28 | 21-DEC-16:01 | -1.1 |
Annual Sum or Average | 0.120514E+10 | |||
Minimum of Months | 673289.89 | 570.63 | -5.0 | |
Maximum of Months | 0.383229E+09 | 2132.53 | 21.97 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.673717E+09 | 2135.04 | 17-JAN-09:01 | -2.5 |
February | 0.426873E+09 | 2131.05 | 05-FEB-09:01 | -5.0 |
March | 0.125365E+09 | 2050.44 | 04-MAR-09:01 | 2.15 |
April | 9488791.71 | 1288.41 | 24-APR-21:53 | 15.60 |
May | 3911602.40 | 1510.36 | 20-MAY-08:53 | 18.90 |
June | 1081676.14 | 1352.25 | 19-JUN-08:53 | 19.40 |
July | 767234.74 | 1016.38 | 15-JUL-08:54 | 27.20 |
August | 923387.54 | 1084.36 | 31-AUG-08:53 | 22.20 |
September | 1753602.10 | 1242.69 | 17-SEP-08:53 | 17.80 |
October | 59151178.20 | 2096.07 | 26-OCT-08:61 | 1.97 |
November | 0.237263E+09 | 2096.84 | 27-NOV-09:01 | -1.2 |
December | 0.756386E+09 | 2162.50 | 15-DEC-09:01 | -6.5 |
Annual Sum or Average | 0.229668E+10 | |||
Minimum of Months | 767234.74 | 1016.38 | -6.5 | |
Maximum of Months | 0.756386E+09 | 2162.50 | 27.20 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 54686517.60 | 612.02 | 20-JAN-09:01 | -3.2 |
February | 32384101.81 | 618.80 | 19-FEB-16:03 | 15.82 |
March | 2539033.92 | 463.48 | 06-MAR-16:03 | 17.62 |
April | 738031.02 | 535.46 | 05-APR-15:04 | 18.48 |
May | 303528.02 | 517.24 | 06-MAY-15:04 | 17.88 |
June | 130173.71 | 277.05 | 19-JUN-08:54 | 19.40 |
July | 37658.95 | 142.19 | 08-JUL-18:06 | 26.65 |
August | 129640.47 | 231.69 | 31-AUG-08:54 | 22.20 |
September | 321247.58 | 404.27 | 21-SEP-08:53 | 21.10 |
October | 1549604.70 | 423.58 | 30-OCT-08:03 | 6.75 |
November | 7676555.95 | 592.47 | 27-NOV-16:01 | 6.52 |
December | 79433413.56 | 623.09 | 15-DEC-09:01 | -6.5 |
Annual Sum or Average | 0.179930E+09 | |||
Minimum of Months | 37658.95 | 142.19 | -6.5 | |
Maximum of Months | 79433413.56 | 623.09 | 26.65 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.400964E+09 | 2089.72 | 20-JAN-09:01 | -3.2 |
February | 0.253507E+09 | 2022.66 | 16-FEB-16:01 | 1.70 |
March | 72860409.28 | 1380.64 | 22-MAR-08:62 | 4.87 |
April | 5194069.38 | 1003.03 | 23-APR-18:04 | 8.12 |
May | 1239161.85 | 832.71 | 03-MAY-18:03 | 15.73 |
June | 342138.01 | 854.63 | 01-JUN-18:04 | 12.30 |
July | 57800.71 | 296.82 | 17-JUL-08:04 | 20.87 |
August | 82187.47 | 607.90 | 23-AUG-08:04 | 19.13 |
September | 455250.91 | 815.79 | 08-SEP-18:04 | 18.22 |
October | 36516007.52 | 2018.13 | 25-OCT-08:61 | 0.22 |
November | 0.108718E+09 | 1414.78 | 04-NOV-18:02 | 5.60 |
December | 0.405923E+09 | 2060.13 | 08-DEC-09:01 | -0.5 |
Annual Sum or Average | 0.128586E+10 | |||
Minimum of Months | 57800.71 | 296.82 | -3.2 | |
Maximum of Months | 0.405923E+09 | 2089.72 | 20.87 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.692011E+09 | 2091.16 | 20-JAN-09:01 | -3.2 |
February | 0.447081E+09 | 2050.06 | 05-FEB-19:01 | -1.2 |
March | 0.119884E+09 | 1564.01 | 22-MAR-08:62 | 4.87 |
April | 10531868.26 | 1433.74 | 20-APR-20:43 | 14.18 |
May | 2145853.22 | 1359.17 | 11-MAY-21:53 | 16.70 |
June | 234910.78 | 750.89 | 08-JUN-18:04 | 11.60 |
July | 153052.76 | 428.04 | 13-JUL-21:54 | 23.30 |
August | 140224.95 | 391.45 | 04-AUG-21:54 | 23.30 |
September | 913295.29 | 1137.93 | 25-SEP-21:53 | 17.80 |
October | 56759759.46 | 2020.61 | 25-OCT-08:61 | 0.22 |
November | 0.239220E+09 | 1965.76 | 27-NOV-16:01 | 6.52 |
December | 0.766242E+09 | 2076.49 | 21-DEC-16:01 | -1.1 |
Annual Sum or Average | 0.233532E+10 | |||
Minimum of Months | 140224.95 | 391.45 | -3.2 | |
Maximum of Months | 0.766242E+09 | 2091.16 | 23.30 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8176618.76 | 331.70 | 19-JAN-09:03 | -2.1 |
February | 46791.96 | 38.36 | 06-FEB-07:05 | -5.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 938588.63 | 110.15 | 08-DEC-09:03 | -0.5 |
Annual Sum or Average | 9161999.35 | |||
Minimum of Months | 0.00 | 0.00 | -5.4 | |
Maximum of Months | 8176618.76 | 331.70 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.705678E+09 | 2574.95 | 17-JAN-09:01 | -2.5 |
February | 0.467753E+09 | 2554.55 | 05-FEB-09:01 | -5.0 |
March | 0.218621E+09 | 2381.81 | 23-MAR-08:62 | 7.07 |
April | 40674870.37 | 1234.71 | 02-APR-08:03 | 14.45 |
May | 15016983.00 | 1321.50 | 12-MAY-08:03 | 12.77 |
June | 2594698.37 | 938.97 | 19-JUN-08:03 | 18.07 |
July | 701694.23 | 900.61 | 06-JUL-08:03 | 25.87 |
August | 691609.80 | 709.40 | 28-AUG-08:03 | 19.08 |
September | 1138729.32 | 842.12 | 25-SEP-08:03 | 16.57 |
October | 98469303.61 | 2524.04 | 25-OCT-08:61 | 0.22 |
November | 0.274478E+09 | 2428.97 | 27-NOV-09:01 | -1.2 |
December | 0.715905E+09 | 2561.37 | 22-DEC-09:01 | -5.2 |
Annual Sum or Average | 0.254172E+10 | |||
Minimum of Months | 691609.80 | 709.40 | -5.2 | |
Maximum of Months | 0.715905E+09 | 2574.95 | 25.87 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113245E+10 | 2580.03 | 17-JAN-09:01 | -2.5 |
February | 0.749386E+09 | 2585.12 | 05-FEB-09:01 | -5.0 |
March | 0.318322E+09 | 2494.50 | 04-MAR-09:01 | 2.15 |
April | 49486461.40 | 1347.26 | 07-APR-08:61 | 5.37 |
May | 15114143.28 | 1377.80 | 31-MAY-21:53 | 20.70 |
June | 2350364.98 | 1424.78 | 20-JUN-08:53 | 23.30 |
July | 543698.56 | 993.17 | 17-JUL-21:54 | 21.70 |
August | 994850.30 | 1223.16 | 28-AUG-08:53 | 20.00 |
September | 2400237.57 | 1350.79 | 27-SEP-21:53 | 18.90 |
October | 0.152142E+09 | 2543.16 | 26-OCT-08:61 | 1.97 |
November | 0.538755E+09 | 2552.65 | 27-NOV-09:01 | -1.2 |
December | 0.123160E+10 | 2617.30 | 15-DEC-09:01 | -6.5 |
Annual Sum or Average | 0.419355E+10 | |||
Minimum of Months | 543698.56 | 993.17 | -6.5 | |
Maximum of Months | 0.123160E+10 | 2617.30 | 23.30 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111114E+09 | 1314.42 | 17-JAN-09:01 | -2.5 |
February | 69667518.71 | 1277.50 | 16-FEB-16:01 | 1.70 |
March | 27538149.16 | 834.86 | 22-MAR-08:62 | 4.87 |
April | 5793185.05 | 563.53 | 25-APR-08:03 | 12.57 |
May | 2682035.15 | 564.99 | 24-MAY-15:04 | 16.52 |
June | 875984.86 | 545.23 | 08-JUN-15:04 | 15.50 |
July | 954669.61 | 431.29 | 05-JUL-08:04 | 25.87 |
August | 851439.66 | 473.66 | 02-AUG-08:04 | 24.78 |
September | 420412.02 | 465.08 | 23-SEP-18:04 | 18.35 |
October | 17195703.28 | 1280.66 | 25-OCT-08:61 | 0.22 |
November | 25979208.51 | 671.62 | 09-NOV-16:04 | 16.52 |
December | 0.104010E+09 | 1297.48 | 08-DEC-09:01 | -0.5 |
Annual Sum or Average | 0.367082E+09 | |||
Minimum of Months | 420412.02 | 431.29 | -2.5 | |
Maximum of Months | 0.111114E+09 | 1314.42 | 25.87 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22469364.40 | 807.20 | 21-JAN-07:10 | -7.8 |
February | 4732436.54 | 613.02 | 06-FEB-07:10 | -5.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 12.83 |
December | 21321070.04 | 814.59 | 15-DEC-07:30 | -7.8 |
Annual Sum or Average | 48522870.98 | |||
Minimum of Months | 0.00 | 0.00 | -7.8 | |
Maximum of Months | 22469364.40 | 814.59 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.866285E+10 | 8344.11 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.782177E+10 | 8344.11 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.868956E+10 | 8344.11 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.836914E+10 | 8344.11 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.867788E+10 | 8344.11 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.840753E+10 | 8344.11 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.863949E+10 | 8344.11 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.869290E+10 | 8344.11 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.837248E+10 | 8344.11 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.865952E+10 | 8344.11 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.840085E+10 | 8344.11 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.863949E+10 | 8344.11 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.102033E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.782177E+10 | 8344.11 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.869290E+10 | 8344.11 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.478695E+09 | 461.08 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.432218E+09 | 461.08 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.480171E+09 | 461.08 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.462465E+09 | 461.08 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.479525E+09 | 461.08 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.464586E+09 | 461.08 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.477404E+09 | 461.08 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.480355E+09 | 461.08 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.462650E+09 | 461.08 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.478511E+09 | 461.08 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.464217E+09 | 461.08 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.477404E+09 | 461.08 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.563820E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.432218E+09 | 461.08 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.480355E+09 | 461.08 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.554331E+09 | 533.93 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.500510E+09 | 533.93 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.556040E+09 | 533.93 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.535537E+09 | 533.93 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.555292E+09 | 533.93 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.537993E+09 | 533.93 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.552836E+09 | 533.93 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.556253E+09 | 533.93 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.535750E+09 | 533.93 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.554117E+09 | 533.93 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.537566E+09 | 533.93 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.552836E+09 | 533.93 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.652906E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.500510E+09 | 533.93 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.556253E+09 | 533.93 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.639281E+09 | 615.76 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.577212E+09 | 615.76 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.641251E+09 | 615.76 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.617606E+09 | 615.76 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.640389E+09 | 615.76 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.620439E+09 | 615.76 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.637557E+09 | 615.76 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.641498E+09 | 615.76 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.617853E+09 | 615.76 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.639035E+09 | 615.76 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.619946E+09 | 615.76 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.637557E+09 | 615.76 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.752962E+10 | 0.124712E+11 | ||||
Minimum of Months | 0.577212E+09 | 615.76 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.641498E+09 | 615.76 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.142601E+09 | 137.35 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.128756E+09 | 137.35 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.143041E+09 | 137.35 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.137766E+09 | 137.35 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.142848E+09 | 137.35 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.138398E+09 | 137.35 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.142217E+09 | 137.35 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.143096E+09 | 137.35 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.137821E+09 | 137.35 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.142546E+09 | 137.35 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.138288E+09 | 137.35 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.142217E+09 | 137.35 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.167960E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.128756E+09 | 137.35 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.143096E+09 | 137.35 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.374392E+09 | 360.62 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.338042E+09 | 360.62 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.375546E+09 | 360.62 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.361698E+09 | 360.62 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.375041E+09 | 360.62 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.363357E+09 | 360.62 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.373382E+09 | 360.62 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.375690E+09 | 360.62 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.361842E+09 | 360.62 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.374247E+09 | 360.62 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.363068E+09 | 360.62 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.373382E+09 | 360.62 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.440969E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.338042E+09 | 360.62 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.375690E+09 | 360.62 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.108411E+10 | 1416.11 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.955001E+09 | 1416.11 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.100591E+10 | 1416.11 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.895404E+09 | 1416.11 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.893605E+09 | 1416.11 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.812517E+09 | 1416.11 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.866919E+09 | 1416.11 | 03-JUL-19:19 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.899700E+09 | 1416.11 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.942445E+09 | 1416.11 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.104368E+10 | 1416.11 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.103786E+10 | 1416.11 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.110601E+10 | 1416.11 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.115432E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.812517E+09 | 1416.11 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.110601E+10 | 1416.11 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.948680E+10 | 9580.84 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.854029E+10 | 9580.84 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.943483E+10 | 9580.84 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.899954E+10 | 9580.84 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.929951E+10 | 9580.84 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.898079E+10 | 9580.84 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.924289E+10 | 9580.84 | 03-JUL-19:19 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.931763E+10 | 9580.84 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.906218E+10 | 9580.84 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.944070E+10 | 9580.84 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.918344E+10 | 9580.84 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.948978E+10 | 9580.84 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.110478E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.854029E+10 | 9580.84 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.948978E+10 | 9580.84 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118113E+09 | 106.87 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.106667E+09 | 106.87 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.117174E+09 | 106.87 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.114438E+09 | 106.87 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.117643E+09 | 106.87 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113531E+09 | 106.87 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.118566E+09 | 106.87 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.117174E+09 | 106.87 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.114469E+09 | 106.87 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.118097E+09 | 106.87 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113984E+09 | 106.87 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.118582E+09 | 106.87 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.138844E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.106667E+09 | 106.87 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.118582E+09 | 106.87 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118099E+09 | 106.85 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.106655E+09 | 106.85 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.117160E+09 | 106.85 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.114425E+09 | 106.85 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.117629E+09 | 106.85 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113517E+09 | 106.85 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.118553E+09 | 106.85 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.117160E+09 | 106.85 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.114456E+09 | 106.85 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.118083E+09 | 106.85 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113971E+09 | 106.85 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.118568E+09 | 106.85 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.138828E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.106655E+09 | 106.85 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.118568E+09 | 106.85 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 74229181.22 | 67.16 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 67036196.95 | 67.16 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 73639243.64 | 67.16 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 71920171.51 | 67.16 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 73934212.43 | 67.16 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 71349576.37 | 67.16 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 74514478.79 | 67.16 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 73639243.64 | 67.16 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 71939513.95 | 67.16 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 74219510.00 | 67.16 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 71634873.94 | 67.16 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 74524150.01 | 67.16 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.872580E+09 | 0.300992E+10 | ||||
Minimum of Months | 67036196.95 | 67.16 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 74524150.01 | 67.16 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 74249479.06 | 67.18 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 67054527.88 | 67.18 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 73659380.16 | 67.18 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 71939837.95 | 67.18 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 73954429.61 | 67.18 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 71369086.78 | 67.18 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 74534854.64 | 67.18 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 73659380.16 | 67.18 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 71959185.68 | 67.18 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 74239805.19 | 67.18 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 71654462.37 | 67.18 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 74544528.51 | 67.18 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.872819E+09 | 0.301074E+10 | ||||
Minimum of Months | 67054527.88 | 67.18 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 74544528.51 | 67.18 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118113E+09 | 106.87 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.106667E+09 | 106.87 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.117174E+09 | 106.87 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.114438E+09 | 106.87 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.117643E+09 | 106.87 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113531E+09 | 106.87 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.118566E+09 | 106.87 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.117174E+09 | 106.87 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.114469E+09 | 106.87 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.118097E+09 | 106.87 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113984E+09 | 106.87 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.118582E+09 | 106.87 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.138844E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.106667E+09 | 106.87 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.118582E+09 | 106.87 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118099E+09 | 106.85 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.106655E+09 | 106.85 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.117160E+09 | 106.85 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.114425E+09 | 106.85 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.117629E+09 | 106.85 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113517E+09 | 106.85 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.118553E+09 | 106.85 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.117160E+09 | 106.85 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.114456E+09 | 106.85 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.118083E+09 | 106.85 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113971E+09 | 106.85 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.118568E+09 | 106.85 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.138828E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.106655E+09 | 106.85 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.118568E+09 | 106.85 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.108388E+10 | 1044.00 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.978647E+09 | 1044.00 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.108722E+10 | 1044.00 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.104713E+10 | 1044.00 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.108576E+10 | 1044.00 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.105194E+10 | 1044.00 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.108096E+10 | 1044.00 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.108764E+10 | 1044.00 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.104755E+10 | 1044.00 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.108346E+10 | 1044.00 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.105110E+10 | 1044.00 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.108096E+10 | 1044.00 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.127663E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.978647E+09 | 1044.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108764E+10 | 1044.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118113E+09 | 106.87 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.106667E+09 | 106.87 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.117174E+09 | 106.87 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.114438E+09 | 106.87 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.117643E+09 | 106.87 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113531E+09 | 106.87 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.118566E+09 | 106.87 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.117174E+09 | 106.87 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.114469E+09 | 106.87 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.118097E+09 | 106.87 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113984E+09 | 106.87 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.118582E+09 | 106.87 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.138844E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.106667E+09 | 106.87 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.118582E+09 | 106.87 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118099E+09 | 106.85 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.106655E+09 | 106.85 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.117160E+09 | 106.85 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.114425E+09 | 106.85 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.117629E+09 | 106.85 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113517E+09 | 106.85 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.118553E+09 | 106.85 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.117160E+09 | 106.85 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.114456E+09 | 106.85 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.118083E+09 | 106.85 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113971E+09 | 106.85 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.118568E+09 | 106.85 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.138828E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.106655E+09 | 106.85 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.118568E+09 | 106.85 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 74249479.06 | 67.18 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 67054527.88 | 67.18 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 73659380.16 | 67.18 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 71939837.95 | 67.18 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 73954429.61 | 67.18 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 71369086.78 | 67.18 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 74534854.64 | 67.18 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 73659380.16 | 67.18 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 71959185.68 | 67.18 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 74239805.19 | 67.18 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 71654462.37 | 67.18 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 74544528.51 | 67.18 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.872819E+09 | 0.301074E+10 | ||||
Minimum of Months | 67054527.88 | 67.18 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 74544528.51 | 67.18 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.228861E+10 | 2486.81 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.203255E+10 | 2486.81 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.219683E+10 | 2486.81 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.202205E+10 | 2486.81 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.205351E+10 | 2486.81 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.193371E+10 | 2486.81 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.202373E+10 | 2486.81 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.206922E+10 | 2486.81 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.208318E+10 | 2486.81 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.224706E+10 | 2486.81 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.218968E+10 | 2486.81 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.230708E+10 | 2486.81 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.254472E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.193371E+10 | 2486.81 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.230708E+10 | 2486.81 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.228861E+10 | 2486.81 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.203255E+10 | 2486.81 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.219683E+10 | 2486.81 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.202205E+10 | 2486.81 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.205351E+10 | 2486.81 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.193371E+10 | 2486.81 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.202373E+10 | 2486.81 | 03-JUL-19:19 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.206922E+10 | 2486.81 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.208318E+10 | 2486.81 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.224706E+10 | 2486.81 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.218968E+10 | 2486.81 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.230708E+10 | 2486.81 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.254472E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.193371E+10 | 2486.81 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.230708E+10 | 2486.81 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101925E+10 | 981.75 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.920291E+09 | 981.75 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.102239E+10 | 981.75 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.984694E+09 | 981.75 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.102102E+10 | 981.75 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.989210E+09 | 981.75 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.101650E+10 | 981.75 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.102279E+10 | 981.75 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.985086E+09 | 981.75 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.101886E+10 | 981.75 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.988424E+09 | 981.75 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.101650E+10 | 981.75 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.120050E+11 | 0.424019E+12 | ||||
Minimum of Months | 0.920291E+09 | 981.75 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.102279E+10 | 981.75 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.114712E+10 | 1104.91 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.103575E+10 | 1104.91 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.115066E+10 | 1104.91 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.110823E+10 | 1104.91 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.114911E+10 | 1104.91 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.111331E+10 | 1104.91 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.114403E+10 | 1104.91 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.115110E+10 | 1104.91 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.110867E+10 | 1104.91 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.114668E+10 | 1104.91 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.111243E+10 | 1104.91 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.114403E+10 | 1104.91 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.135111E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.103575E+10 | 1104.91 | 0.00 | 0.00 | |
Maximum of Months | 0.115110E+10 | 1104.91 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.866285E+10 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.782177E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.868956E+10 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.836914E+10 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.867788E+10 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.840753E+10 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.863949E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.869290E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.837248E+10 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.865952E+10 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.840085E+10 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.863949E+10 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.102033E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.782177E+10 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.869290E+10 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.478695E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136850E+09 |
February | 0.179968E+10 | 0.432218E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113113E+09 |
March | 0.199990E+10 | 0.480171E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92416594.71 |
April | 0.192973E+10 | 0.462465E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 317371.96 | 57653963.20 |
May | 0.199475E+10 | 0.479525E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3058575.57 | 36005857.95 |
June | 0.193394E+10 | 0.464586E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15441192.48 | 16612622.22 |
July | 0.199054E+10 | 0.477404E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19566079.93 | 7382205.78 |
August | 0.199896E+10 | 0.480355E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13456215.38 | 11438874.39 |
September | 0.192879E+10 | 0.462650E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4822005.73 | 24668645.98 |
October | 0.199148E+10 | 0.478511E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 813054.61 | 64759559.83 |
November | 0.192552E+10 | 0.464217E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104121E+09 |
December | 0.199054E+10 | 0.477404E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140939E+09 |
Annual Sum or Average | 0.234744E+11 | 0.563820E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57474495.66 | 0.805961E+09 |
Minimum of Months | 0.179968E+10 | 0.432218E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7382205.78 |
Maximum of Months | 0.199990E+10 | 0.480355E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19566079.93 | 0.140939E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.554331E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55166054.84 |
February | 0.208403E+10 | 0.500510E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45716876.19 |
March | 0.231589E+10 | 0.556040E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38379548.45 |
April | 0.223463E+10 | 0.535537E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 163564.74 | 24468103.85 |
May | 0.230993E+10 | 0.555292E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1239138.31 | 16228788.90 |
June | 0.223950E+10 | 0.537993E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5985634.90 | 7770792.38 |
July | 0.230505E+10 | 0.552836E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7627530.47 | 3554961.18 |
August | 0.231480E+10 | 0.556253E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5316230.33 | 5124320.75 |
September | 0.223354E+10 | 0.535750E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1984458.85 | 10544774.07 |
October | 0.230614E+10 | 0.554117E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 351777.06 | 26530514.03 |
November | 0.222975E+10 | 0.537566E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42396762.37 |
December | 0.230505E+10 | 0.552836E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56596694.61 |
Annual Sum or Average | 0.271834E+11 | 0.652906E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22668334.66 | 0.332478E+09 |
Minimum of Months | 0.208403E+10 | 0.500510E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3554961.18 |
Maximum of Months | 0.231589E+10 | 0.556253E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7627530.47 | 56596694.61 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.639281E+09 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120745E+09 |
February | 0.440737E+09 | 0.577212E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1642.30 | 99410819.12 |
March | 0.489771E+09 | 0.641251E+09 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12567.00 | 83297077.15 |
April | 0.472586E+09 | 0.617606E+09 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 729493.77 | 53170209.27 |
May | 0.488511E+09 | 0.640389E+09 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3310761.70 | 36275973.55 |
June | 0.473617E+09 | 0.620439E+09 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14025918.90 | 17979009.14 |
July | 0.487480E+09 | 0.637557E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17737910.94 | 8403299.44 |
August | 0.489542E+09 | 0.641498E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12530376.71 | 12008766.39 |
September | 0.472357E+09 | 0.617853E+09 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5165907.29 | 24080775.57 |
October | 0.487709E+09 | 0.639035E+09 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1059963.58 | 58144030.67 |
November | 0.471555E+09 | 0.619946E+09 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92149390.44 |
December | 0.487480E+09 | 0.637557E+09 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123510E+09 |
Annual Sum or Average | 0.574883E+10 | 0.752962E+10 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54574542.20 | 0.729174E+09 |
Minimum of Months | 0.440737E+09 | 0.577212E+09 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8403299.44 |
Maximum of Months | 0.489771E+09 | 0.641498E+09 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17737910.94 | 0.123510E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.142601E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69059075.46 |
February | 0.339028E+09 | 0.128756E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 666.00 | 56803420.00 |
March | 0.376747E+09 | 0.143041E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6613.48 | 47326280.88 |
April | 0.363528E+09 | 0.137766E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 433048.44 | 30035183.91 |
May | 0.375778E+09 | 0.142848E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1975398.55 | 20322741.84 |
June | 0.364321E+09 | 0.138398E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8133289.76 | 10097135.85 |
July | 0.374985E+09 | 0.142217E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10243380.77 | 4784393.71 |
August | 0.376571E+09 | 0.143096E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7244754.08 | 6789658.80 |
September | 0.363352E+09 | 0.137821E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3022645.12 | 13459105.19 |
October | 0.375161E+09 | 0.142546E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 621354.16 | 32880361.56 |
November | 0.362735E+09 | 0.138288E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52462654.15 |
December | 0.374985E+09 | 0.142217E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70711593.97 |
Annual Sum or Average | 0.442217E+10 | 0.167960E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31681150.35 | 0.414732E+09 |
Minimum of Months | 0.339028E+09 | 0.128756E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4784393.71 |
Maximum of Months | 0.376747E+09 | 0.143096E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10243380.77 | 70711593.97 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.374392E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181446E+09 |
February | 0.139600E+10 | 0.338042E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149543E+09 |
March | 0.155131E+10 | 0.375546E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124990E+09 |
April | 0.149688E+10 | 0.361698E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 615319.13 | 78166911.67 |
May | 0.154732E+10 | 0.375041E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 4257514.12 | 51134066.44 |
June | 0.150015E+10 | 0.363357E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 20271752.38 | 23104137.37 |
July | 0.154405E+10 | 0.373382E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 26259526.30 | 9199354.43 |
August | 0.155059E+10 | 0.375690E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 18859343.75 | 14072633.26 |
September | 0.149615E+10 | 0.361842E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 7955366.26 | 31441164.97 |
October | 0.154478E+10 | 0.374247E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 1707073.83 | 83433760.80 |
November | 0.149361E+10 | 0.363068E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136907E+09 |
December | 0.154405E+10 | 0.373382E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185929E+09 |
Annual Sum or Average | 0.182090E+11 | 0.440969E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 79925895.76 | 0.106937E+10 |
Minimum of Months | 0.139600E+10 | 0.338042E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9199354.43 |
Maximum of Months | 0.155131E+10 | 0.375690E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 26259526.30 | 0.185929E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.108411E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322332E+09 |
February | 0.236489E+11 | 0.955001E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267562E+09 |
March | 0.262800E+11 | 0.100591E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223701E+09 |
April | 0.253579E+11 | 0.895404E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 587659.00 | 0.141991E+09 |
May | 0.262123E+11 | 0.893605E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6349551.53 | 92360668.40 |
June | 0.254132E+11 | 0.812517E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34156767.03 | 43530916.99 |
July | 0.261570E+11 | 0.866919E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43533131.22 | 19902215.17 |
August | 0.262677E+11 | 0.899700E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29946875.20 | 28688945.01 |
September | 0.253456E+11 | 0.942445E+09 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10663323.45 | 60072095.53 |
October | 0.261693E+11 | 0.104368E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1802130.84 | 0.153753E+09 |
November | 0.253025E+11 | 0.103786E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247382E+09 |
December | 0.261570E+11 | 0.110601E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331301E+09 |
Annual Sum or Average | 0.308468E+12 | 0.115432E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127039E+09 | 0.193258E+10 |
Minimum of Months | 0.236489E+11 | 0.812517E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19902215.17 |
Maximum of Months | 0.262800E+11 | 0.110601E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43533131.22 | 0.331301E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.948680E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.932100E+09 |
February | 0.702046E+11 | 0.854029E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.771861E+09 |
March | 0.780153E+11 | 0.943483E+10 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647628E+09 |
April | 0.752779E+11 | 0.899954E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2096095.90 | 0.409289E+09 |
May | 0.778146E+11 | 0.929951E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19309412.50 | 0.270387E+09 |
June | 0.754422E+11 | 0.898079E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97720054.11 | 0.128304E+09 |
July | 0.776503E+11 | 0.924289E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124527E+09 | 58235368.88 |
August | 0.779788E+11 | 0.931763E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86124949.46 | 83923817.14 |
September | 0.752414E+11 | 0.906218E+10 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30852098.35 | 0.173870E+09 |
October | 0.776868E+11 | 0.944070E+10 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5185565.46 | 0.443931E+09 |
November | 0.751137E+11 | 0.918344E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.713971E+09 |
December | 0.776503E+11 | 0.948978E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.956798E+09 |
Annual Sum or Average | 0.915726E+12 | 0.110478E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365815E+09 | 0.559030E+10 |
Minimum of Months | 0.702046E+11 | 0.854029E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58235368.88 |
Maximum of Months | 0.780153E+11 | 0.948978E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124527E+09 | 0.956798E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118113E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77005385.38 |
February | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2341.28 | 63223994.43 |
March | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7666.90 | 51299409.64 |
April | 0.293479E+09 | 0.114438E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 648761.27 | 30465491.88 |
May | 0.303504E+09 | 0.117643E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2948473.87 | 18340247.50 |
June | 0.293842E+09 | 0.113531E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12046318.42 | 7309258.80 |
July | 0.303141E+09 | 0.118566E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15775818.92 | 1677464.65 |
August | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11608786.90 | 3246567.99 |
September | 0.293479E+09 | 0.114469E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4579298.54 | 9625769.25 |
October | 0.303322E+09 | 0.118097E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 939455.60 | 32719058.16 |
November | 0.293661E+09 | 0.113984E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57102628.88 |
December | 0.303141E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79074076.66 |
Annual Sum or Average | 0.357224E+10 | 0.138844E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48556921.69 | 0.431089E+09 |
Minimum of Months | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677464.65 |
Maximum of Months | 0.303685E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15775818.92 | 79074076.66 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118099E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75422772.64 |
February | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 868.33 | 62099340.02 |
March | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1588.47 | 51269632.26 |
April | 0.293479E+09 | 0.114425E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 519260.30 | 31893247.29 |
May | 0.303504E+09 | 0.117629E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2734165.42 | 19839398.60 |
June | 0.293842E+09 | 0.113517E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11656936.82 | 8491554.88 |
July | 0.303141E+09 | 0.118553E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15206923.42 | 2815836.14 |
August | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11171669.16 | 4722626.69 |
September | 0.293479E+09 | 0.114456E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4360627.90 | 11387428.68 |
October | 0.303322E+09 | 0.118083E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 821818.79 | 33797333.64 |
November | 0.293661E+09 | 0.113971E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55986715.21 |
December | 0.303141E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77201136.76 |
Annual Sum or Average | 0.357224E+10 | 0.138828E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46473858.61 | 0.434927E+09 |
Minimum of Months | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2815836.14 |
Maximum of Months | 0.303685E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15206923.42 | 77201136.76 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 74229181.22 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26838250.89 |
February | 0.00 | 67036196.95 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22600875.61 |
March | 0.00 | 73639243.64 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19758777.88 |
April | 0.00 | 71920171.51 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13501522.96 |
May | 0.00 | 73934212.43 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81697.00 | 9681031.93 |
June | 0.00 | 71349576.37 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1382114.33 | 5115267.84 |
July | 0.00 | 74514478.79 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1775707.68 | 3014544.27 |
August | 0.00 | 73639243.64 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091001.92 | 3963651.60 |
September | 0.00 | 71939513.95 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 238416.03 | 6759522.36 |
October | 0.00 | 74219510.00 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12157.81 | 14256151.26 |
November | 0.00 | 71634873.94 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21286524.75 |
December | 0.00 | 74524150.01 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27606445.17 |
Annual Sum or Average | 0.00 | 0.872580E+09 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4581094.78 | 0.174383E+09 |
Minimum of Months | 0.00 | 67036196.95 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3014544.27 |
Maximum of Months | 0.00 | 74524150.01 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1775707.68 | 27606445.17 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 74249479.06 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21144631.46 |
February | 0.273974E+09 | 67054527.88 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 530.93 | 17319895.80 |
March | 0.303685E+09 | 73659380.16 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2433.60 | 14115470.13 |
April | 0.293479E+09 | 71939837.95 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 160789.05 | 8561850.61 |
May | 0.303504E+09 | 73954429.61 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 785307.56 | 5315027.91 |
June | 0.293842E+09 | 71369086.78 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3280938.03 | 2238102.39 |
July | 0.303141E+09 | 74534854.64 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4277151.88 | 690121.61 |
August | 0.303685E+09 | 73659380.16 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3151715.02 | 1167132.57 |
September | 0.293479E+09 | 71959185.68 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1259357.29 | 2996050.73 |
October | 0.303322E+09 | 74239805.19 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 255725.06 | 9096011.21 |
November | 0.293661E+09 | 71654462.37 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15560688.47 |
December | 0.303141E+09 | 74544528.51 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21650890.83 |
Annual Sum or Average | 0.357224E+10 | 0.872819E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13173948.41 | 0.119856E+09 |
Minimum of Months | 0.273974E+09 | 67054527.88 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 690121.61 |
Maximum of Months | 0.303685E+09 | 74544528.51 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4277151.88 | 21650890.83 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118113E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77189936.42 |
February | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2367.63 | 63427609.28 |
March | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7571.73 | 51620264.09 |
April | 0.293479E+09 | 0.114438E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 652487.89 | 30721585.30 |
May | 0.303504E+09 | 0.117643E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2947452.32 | 18549541.46 |
June | 0.293842E+09 | 0.113531E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12028612.88 | 7382865.55 |
July | 0.303141E+09 | 0.118566E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15756749.49 | 1701228.88 |
August | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11601678.17 | 3296532.54 |
September | 0.293479E+09 | 0.114469E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4586714.54 | 9710212.07 |
October | 0.303322E+09 | 0.118097E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 945774.74 | 32885617.37 |
November | 0.293661E+09 | 0.113984E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57277863.17 |
December | 0.303141E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79337162.59 |
Annual Sum or Average | 0.357224E+10 | 0.138844E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48529409.39 | 0.433100E+09 |
Minimum of Months | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1701228.88 |
Maximum of Months | 0.303685E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15756749.49 | 79337162.59 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118099E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75423709.49 |
February | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 900.92 | 62094718.78 |
March | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1660.01 | 51532292.44 |
April | 0.293479E+09 | 0.114425E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 529128.08 | 31777551.84 |
May | 0.303504E+09 | 0.117629E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2731400.70 | 20080055.86 |
June | 0.293842E+09 | 0.113517E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11597733.93 | 9253157.69 |
July | 0.303141E+09 | 0.118553E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15125249.29 | 3688259.83 |
August | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11114339.32 | 5593846.66 |
September | 0.293479E+09 | 0.114456E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4346053.97 | 11865343.42 |
October | 0.303322E+09 | 0.118083E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 833462.09 | 33662386.20 |
November | 0.293661E+09 | 0.113971E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56020840.83 |
December | 0.303141E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77079108.03 |
Annual Sum or Average | 0.357224E+10 | 0.138828E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46279928.32 | 0.438071E+09 |
Minimum of Months | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3688259.83 |
Maximum of Months | 0.303685E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15125249.29 | 77079108.03 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.108388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93523970.43 |
February | 0.348285E+10 | 0.978647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76895835.80 |
March | 0.387034E+10 | 0.108722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1053.73 | 64505722.36 |
April | 0.373454E+10 | 0.104713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413663.73 | 41620046.77 |
May | 0.386038E+10 | 0.108576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2359603.02 | 27999961.37 |
June | 0.374269E+10 | 0.105194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10643757.54 | 13679407.97 |
July | 0.385223E+10 | 0.108096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13464862.08 | 6485556.02 |
August | 0.386853E+10 | 0.108764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9352371.60 | 9348434.05 |
September | 0.373273E+10 | 0.104755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3416793.58 | 18965299.71 |
October | 0.385404E+10 | 0.108346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 586549.48 | 46232990.32 |
November | 0.372639E+10 | 0.105110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71635010.74 |
December | 0.385223E+10 | 0.108096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95336328.26 |
Annual Sum or Average | 0.454292E+11 | 0.127663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40238654.77 | 0.566229E+09 |
Minimum of Months | 0.348285E+10 | 0.978647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6485556.02 |
Maximum of Months | 0.387034E+10 | 0.108764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13464862.08 | 95336328.26 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118113E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76911109.45 |
February | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2006.01 | 63207602.79 |
March | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6975.64 | 51331736.10 |
April | 0.293479E+09 | 0.114438E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 627893.64 | 30581338.68 |
May | 0.303504E+09 | 0.117643E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2888585.64 | 18434595.95 |
June | 0.293842E+09 | 0.113531E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11916408.03 | 7384143.33 |
July | 0.303141E+09 | 0.118566E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15604576.42 | 1730027.96 |
August | 0.303685E+09 | 0.117174E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11462632.79 | 3310200.41 |
September | 0.293479E+09 | 0.114469E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4498104.08 | 9716216.39 |
October | 0.303322E+09 | 0.118097E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 915976.36 | 32771075.09 |
November | 0.293661E+09 | 0.113984E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57099175.94 |
December | 0.303141E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78967382.96 |
Annual Sum or Average | 0.357224E+10 | 0.138844E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47923158.61 | 0.431445E+09 |
Minimum of Months | 0.273974E+09 | 0.106667E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1730027.96 |
Maximum of Months | 0.303685E+09 | 0.118582E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15604576.42 | 78967382.96 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.118099E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75175746.63 |
February | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 783.36 | 61996350.68 |
March | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1440.15 | 51332855.64 |
April | 0.293479E+09 | 0.114425E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 504716.74 | 32210317.16 |
May | 0.303504E+09 | 0.117629E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2682290.39 | 20006795.12 |
June | 0.293842E+09 | 0.113517E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11535810.95 | 8552335.70 |
July | 0.303141E+09 | 0.118553E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15054235.48 | 2754580.34 |
August | 0.303685E+09 | 0.117160E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11041763.65 | 4685266.64 |
September | 0.293479E+09 | 0.114456E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4292021.21 | 11371383.32 |
October | 0.303322E+09 | 0.118083E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 804157.07 | 33867031.11 |
November | 0.293661E+09 | 0.113971E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55795624.89 |
December | 0.303141E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76945423.61 |
Annual Sum or Average | 0.357224E+10 | 0.138828E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45917219.00 | 0.434694E+09 |
Minimum of Months | 0.273974E+09 | 0.106655E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2754580.34 |
Maximum of Months | 0.303685E+09 | 0.118568E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15054235.48 | 76945423.61 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 74249479.06 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39970524.31 |
February | 0.273974E+09 | 67054527.88 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 844.35 | 32760077.04 |
March | 0.303685E+09 | 73659380.16 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3216.43 | 26529978.43 |
April | 0.293479E+09 | 71939837.95 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 322033.46 | 15714147.57 |
May | 0.303504E+09 | 73954429.61 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1480456.49 | 9454028.29 |
June | 0.293842E+09 | 71369086.78 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6113442.62 | 3777207.36 |
July | 0.303141E+09 | 74534854.64 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7995214.80 | 885604.80 |
August | 0.303685E+09 | 73659380.16 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5868902.99 | 1693574.13 |
September | 0.293479E+09 | 71959185.68 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2298995.83 | 4991059.33 |
October | 0.303322E+09 | 74239805.19 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 463503.07 | 16930251.84 |
November | 0.293661E+09 | 71654462.37 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29557269.50 |
December | 0.303141E+09 | 74544528.51 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41022220.86 |
Annual Sum or Average | 0.357224E+10 | 0.872819E+09 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24546610.06 | 0.223286E+09 |
Minimum of Months | 0.273974E+09 | 67054527.88 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 885604.80 |
Maximum of Months | 0.303685E+09 | 74544528.51 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7995214.80 | 41022220.86 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.228861E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211443E+09 |
February | 0.415303E+11 | 0.203255E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175161E+09 |
March | 0.461508E+11 | 0.219683E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148245E+09 |
April | 0.445315E+11 | 0.202205E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 311622.38 | 94667800.32 |
May | 0.460320E+11 | 0.205351E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3509831.76 | 63196724.13 |
June | 0.446286E+11 | 0.193371E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20625359.82 | 29950050.40 |
July | 0.459349E+11 | 0.202373E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26699452.89 | 13553303.62 |
August | 0.461292E+11 | 0.206922E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18539973.06 | 19544385.34 |
September | 0.445099E+11 | 0.208318E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6651249.64 | 39969843.33 |
October | 0.459565E+11 | 0.224706E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1139776.76 | 0.100690E+09 |
November | 0.444343E+11 | 0.218968E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161082E+09 |
December | 0.459349E+11 | 0.230708E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216100E+09 |
Annual Sum or Average | 0.541708E+12 | 0.254472E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 77477266.30 | 0.127360E+10 |
Minimum of Months | 0.415303E+11 | 0.193371E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13553303.62 |
Maximum of Months | 0.461508E+11 | 0.230708E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26699452.89 | 0.216100E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.228861E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212950E+09 |
February | 0.415303E+11 | 0.203255E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176300E+09 |
March | 0.461508E+11 | 0.219683E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149073E+09 |
April | 0.445315E+11 | 0.202205E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 311601.11 | 94994606.76 |
May | 0.460320E+11 | 0.205351E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3505153.74 | 63347035.12 |
June | 0.446286E+11 | 0.193371E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20620666.45 | 29970167.32 |
July | 0.459349E+11 | 0.202373E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26692123.52 | 13553792.55 |
August | 0.461292E+11 | 0.206922E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18532627.50 | 19550994.34 |
September | 0.445099E+11 | 0.208318E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6615255.53 | 40025228.55 |
October | 0.459565E+11 | 0.224706E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1115699.65 | 0.101180E+09 |
November | 0.444343E+11 | 0.218968E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162103E+09 |
December | 0.459349E+11 | 0.230708E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217675E+09 |
Annual Sum or Average | 0.541708E+12 | 0.254472E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 77393127.51 | 0.128072E+10 |
Minimum of Months | 0.415303E+11 | 0.193371E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13553792.55 |
Maximum of Months | 0.461508E+11 | 0.230708E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26692123.52 | 0.217675E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.101925E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190366E+09 |
February | 0.369574E+10 | 0.920291E+09 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157311E+09 |
March | 0.410691E+10 | 0.102239E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132739E+09 |
April | 0.396281E+10 | 0.984694E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 282978.00 | 84561615.24 |
May | 0.409635E+10 | 0.102102E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3150568.95 | 56434750.22 |
June | 0.397146E+10 | 0.989210E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 18483586.29 | 26728501.80 |
July | 0.408770E+10 | 0.101650E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 23920554.40 | 12120103.90 |
August | 0.410499E+10 | 0.102279E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 16606458.44 | 17472174.33 |
September | 0.396089E+10 | 0.985086E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 5919927.00 | 35709463.58 |
October | 0.408962E+10 | 0.101886E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 981768.39 | 90397644.22 |
November | 0.395417E+10 | 0.988424E+09 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144758E+09 |
December | 0.408770E+10 | 0.101650E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194776E+09 |
Annual Sum or Average | 0.482060E+11 | 0.120050E+11 | 0.382987E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 69345841.47 | 0.114337E+10 |
Minimum of Months | 0.369574E+10 | 0.920291E+09 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12120103.90 |
Maximum of Months | 0.410691E+10 | 0.102279E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 23920554.40 | 0.194776E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.114712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164609E+09 |
February | 0.368610E+10 | 0.103575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135755E+09 |
March | 0.409620E+10 | 0.115066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112763E+09 |
April | 0.395248E+10 | 0.110823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434701.56 | 72467798.42 |
May | 0.408566E+10 | 0.114911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3371010.18 | 48583045.24 |
June | 0.396110E+10 | 0.111331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18200988.54 | 23750972.50 |
July | 0.407704E+10 | 0.114403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23429571.44 | 11151129.46 |
August | 0.409429E+10 | 0.115110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16259553.66 | 16029805.41 |
September | 0.395056E+10 | 0.110867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5803130.60 | 32193073.55 |
October | 0.407896E+10 | 0.114668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 990821.05 | 79173353.78 |
November | 0.394385E+10 | 0.111243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124061E+09 |
December | 0.407704E+10 | 0.114403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168594E+09 |
Annual Sum or Average | 0.480803E+11 | 0.135111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68489777.02 | 0.989130E+09 |
Minimum of Months | 0.368610E+10 | 0.103575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11151129.46 |
Maximum of Months | 0.409620E+10 | 0.115110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23429571.44 | 0.168594E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 8344.11 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 8344.11 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 8344.11 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 8344.11 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 8344.11 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 8344.11 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 8344.11 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 8344.11 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 8344.11 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 8344.11 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 8344.11 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 8344.11 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 8344.11 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 8344.11 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 461.08 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 80.16 | 21-JAN-07:00 |
February | 1169.53 | 01-FEB-00:10 | 461.08 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 74.88 | 04-FEB-06:50 |
March | 1169.53 | 01-MAR-00:10 | 461.08 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 67.09 | 05-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 461.08 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.16 | 26-APR-17:00 | 50.96 | 08-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 461.08 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.72 | 22-MAY-13:00 | 43.04 | 07-MAY-05:00 |
June | 1169.53 | 01-JUN-00:10 | 461.08 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.42 | 28-JUN-16:00 | 34.15 | 09-JUN-04:10 |
July | 1169.53 | 01-JUL-00:10 | 461.08 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.01 | 22-JUL-15:00 | 16.45 | 08-JUL-03:00 |
August | 1169.53 | 01-AUG-00:10 | 461.08 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.79 | 20-AUG-15:00 | 24.90 | 31-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 461.08 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 03-SEP-14:00 | 30.49 | 20-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 461.08 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.70 | 01-OCT-16:00 | 63.66 | 26-OCT-07:00 |
November | 1169.53 | 01-NOV-00:10 | 461.08 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 68.24 | 27-NOV-06:50 |
December | 1169.53 | 01-DEC-00:10 | 461.08 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 83.70 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 461.08 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.45 | |||||
Maximum of Months | 1169.53 | 461.08 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 34.42 | 83.70 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 533.93 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 32.21 | 21-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 533.93 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 30.61 | 05-FEB-08:00 |
March | 1354.32 | 01-MAR-00:10 | 533.93 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 27.71 | 05-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 533.93 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 13-APR-17:00 | 21.84 | 08-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 533.93 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 22-MAY-13:00 | 18.78 | 07-MAY-05:00 |
June | 1354.32 | 01-JUN-00:10 | 533.93 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.29 | 28-JUN-16:00 | 15.64 | 09-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 533.93 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.74 | 22-JUL-15:00 | 7.61 | 08-JUL-04:00 |
August | 1354.32 | 01-AUG-00:10 | 533.93 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.01 | 20-AUG-16:00 | 10.91 | 31-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 533.93 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.08 | 03-SEP-14:00 | 13.17 | 25-SEP-05:00 |
October | 1354.32 | 01-OCT-23:10 | 533.93 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.70 | 01-OCT-16:00 | 26.42 | 27-OCT-07:00 |
November | 1354.32 | 01-NOV-00:10 | 533.93 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 28.37 | 27-NOV-06:00 |
December | 1354.32 | 01-DEC-00:10 | 533.93 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 34.15 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 533.93 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 | |||||
Maximum of Months | 1354.32 | 533.93 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 13.29 | 34.15 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 615.76 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 73.13 | 21-JAN-07:00 |
February | 286.42 | 01-FEB-00:10 | 615.76 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 | 14-FEB-16:00 | 68.31 | 04-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 615.76 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.98 | 08-MAR-14:00 | 62.05 | 05-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 615.76 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.12 | 13-APR-17:00 | 48.76 | 08-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 615.76 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.51 | 22-MAY-13:00 | 42.23 | 07-MAY-05:00 |
June | 286.42 | 01-JUN-00:10 | 615.76 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.40 | 28-JUN-16:00 | 36.19 | 09-JUN-04:50 |
July | 286.42 | 01-JUL-00:10 | 615.76 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.11 | 22-JUL-15:00 | 17.79 | 08-JUL-03:00 |
August | 286.42 | 01-AUG-00:10 | 615.76 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.68 | 20-AUG-16:00 | 25.39 | 31-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 615.76 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.49 | 03-SEP-14:00 | 30.10 | 20-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 615.76 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 | 01-OCT-16:00 | 59.74 | 27-OCT-07:00 |
November | 286.42 | 01-NOV-00:10 | 615.76 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 63.46 | 27-NOV-07:00 |
December | 286.42 | 01-DEC-00:10 | 615.76 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 76.34 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.79 | |||||
Maximum of Months | 286.42 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 31.40 | 76.34 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 137.35 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 42.19 | 21-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 137.35 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 14-FEB-16:00 | 39.41 | 04-FEB-06:50 |
March | 220.32 | 01-MAR-00:10 | 137.35 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 | 08-MAR-14:00 | 35.39 | 05-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 137.35 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.11 | 13-APR-17:00 | 27.78 | 08-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 137.35 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 22-MAY-13:00 | 24.04 | 07-MAY-05:00 |
June | 220.32 | 01-JUN-00:10 | 137.35 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 | 28-JUN-16:00 | 20.55 | 09-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 137.35 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.37 | 22-JUL-15:00 | 10.14 | 08-JUL-03:00 |
August | 220.32 | 01-AUG-00:10 | 137.35 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.59 | 01-AUG-15:50 | 14.31 | 31-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 137.35 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.15 | 03-SEP-14:00 | 16.98 | 20-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 137.35 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.77 | 01-OCT-16:00 | 33.93 | 27-OCT-07:00 |
November | 220.32 | 01-NOV-00:10 | 137.35 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 36.19 | 27-NOV-06:30 |
December | 220.32 | 01-DEC-00:10 | 137.35 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 44.05 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 137.35 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.14 | |||||
Maximum of Months | 220.32 | 137.35 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 | 44.05 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 360.62 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 108.04 | 21-JAN-07:00 |
February | 907.20 | 01-FEB-00:10 | 360.62 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 103.22 | 05-FEB-08:00 |
March | 907.20 | 01-MAR-00:10 | 360.62 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 93.38 | 05-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 360.62 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 10.07 | 13-APR-17:00 | 72.53 | 08-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 360.62 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 21.52 | 19-MAY-17:00 | 61.71 | 07-MAY-05:10 |
June | 907.20 | 01-JUN-00:10 | 360.62 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 46.35 | 28-JUN-16:00 | 50.56 | 09-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 360.62 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 43.84 | 21-JUL-17:00 | 21.42 | 02-JUL-05:10 |
August | 907.20 | 01-AUG-00:10 | 360.62 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 37.73 | 20-AUG-16:00 | 35.18 | 31-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 360.62 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 29.84 | 03-SEP-13:50 | 42.55 | 09-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 360.62 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 20.13 | 01-OCT-16:00 | 89.27 | 26-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 360.62 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 95.02 | 27-NOV-07:00 |
December | 907.20 | 01-DEC-00:10 | 360.62 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 109.63 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 21.42 | ||||||
Maximum of Months | 907.20 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 46.35 | 109.63 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1416.11 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 186.23 | 26-JAN-04:00 |
February | 15368.40 | 01-FEB-00:10 | 1416.11 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 177.44 | 04-FEB-06:00 |
March | 15368.40 | 01-MAR-00:10 | 1416.11 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 158.89 | 06-MAR-06:00 |
April | 15368.40 | 01-APR-00:10 | 1416.11 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.12 | 13-APR-17:00 | 123.60 | 08-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 1416.11 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.51 | 22-MAY-13:00 | 106.24 | 07-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 1416.11 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.11 | 28-JUN-16:00 | 91.05 | 09-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1416.11 | 03-JUL-19:19 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.98 | 22-JUL-15:00 | 43.57 | 08-JUL-03:20 |
August | 15368.40 | 01-AUG-00:10 | 1416.11 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.01 | 20-AUG-15:00 | 62.45 | 31-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 1416.11 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.74 | 03-SEP-14:00 | 75.37 | 25-SEP-05:00 |
October | 15368.40 | 01-OCT-23:10 | 1416.11 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.87 | 01-OCT-16:00 | 150.96 | 26-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 1416.11 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 164.42 | 27-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 1416.11 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 197.78 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 1416.11 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.57 | |||||
Maximum of Months | 15368.40 | 1416.11 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 76.11 | 197.78 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 9580.84 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 542.60 | 20-JAN-02:00 |
February | 45622.98 | 01-FEB-00:10 | 9580.84 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 516.88 | 04-FEB-06:00 |
March | 45622.98 | 01-MAR-00:10 | 9580.84 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 465.34 | 05-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 9580.84 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.98 | 13-APR-17:00 | 366.49 | 08-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 9580.84 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.95 | 22-MAY-13:00 | 315.92 | 07-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 9580.84 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.44 | 28-JUN-16:00 | 263.17 | 09-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 9580.84 | 03-JUL-19:19 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.51 | 22-JUL-15:00 | 124.54 | 08-JUL-03:50 |
August | 45622.98 | 01-AUG-00:10 | 9580.84 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.82 | 20-AUG-16:00 | 178.48 | 31-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 9580.84 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.68 | 03-SEP-14:00 | 216.47 | 09-SEP-06:00 |
October | 45622.98 | 01-OCT-23:10 | 9580.84 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.30 | 01-OCT-16:00 | 445.76 | 26-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 9580.84 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 479.85 | 27-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 9580.84 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 574.90 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 9580.84 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.54 | |||||
Maximum of Months | 45622.98 | 9580.84 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 217.44 | 574.90 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.87 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 46.77 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 106.87 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | 14-FEB-16:09 | 43.70 | 04-FEB-06:06 |
March | 180.00 | 01-MAR-00:10 | 106.87 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 | 08-MAR-16:07 | 39.18 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 106.87 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 | 13-APR-17:00 | 29.81 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 106.87 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.19 | 19-MAY-16:00 | 25.21 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 106.87 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.56 | 28-JUN-16:00 | 19.94 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 106.87 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.36 | 22-JUL-15:10 | 8.05 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 106.87 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.81 | 01-AUG-15:10 | 12.24 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 106.87 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 02-SEP-15:10 | 15.67 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 106.87 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.74 | 01-OCT-16:00 | 37.18 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 106.87 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 39.84 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 106.87 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 48.82 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.05 | |||||
Maximum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 23.56 | 48.82 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.85 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 46.77 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 106.85 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | 14-FEB-16:09 | 43.70 | 04-FEB-06:06 |
March | 180.00 | 01-MAR-00:10 | 106.85 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 | 08-MAR-16:10 | 39.18 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 106.85 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 | 13-APR-17:00 | 29.81 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 106.85 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.18 | 19-MAY-15:10 | 25.21 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 106.85 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.44 | 28-JUN-16:00 | 19.94 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 106.85 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.38 | 22-JUL-15:10 | 9.50 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 106.85 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.81 | 01-AUG-15:10 | 12.24 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 106.85 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 02-SEP-15:10 | 15.67 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 106.85 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.74 | 01-OCT-16:00 | 37.18 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 106.85 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 39.84 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 106.85 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 48.81 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | |||||
Maximum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 23.44 | 48.81 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 67.16 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 14.71 | 26-JAN-04:00 |
February | 0.00 | 01-FEB-00:10 | 67.16 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 14.16 | 05-FEB-08:10 |
March | 0.00 | 01-MAR-00:10 | 67.16 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 12.79 | 05-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 67.16 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 10.36 | 06-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 67.16 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.27 | 22-MAY-13:00 | 9.01 | 07-MAY-05:00 |
June | 0.00 | 01-JUN-00:10 | 67.16 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 | 28-JUN-16:00 | 7.63 | 09-JUN-05:10 |
July | 0.00 | 01-JUL-00:10 | 67.16 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 22-JUL-15:00 | 4.29 | 08-JUL-04:00 |
August | 0.00 | 01-AUG-00:10 | 67.16 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.15 | 20-AUG-15:00 | 5.68 | 31-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 67.16 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.32 | 03-SEP-14:00 | 6.67 | 09-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 67.16 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 | 01-OCT-16:00 | 12.76 | 27-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 67.16 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 13.22 | 27-NOV-07:10 |
December | 0.00 | 01-DEC-00:10 | 67.16 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 15.45 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 67.16 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.29 | |||||
Maximum of Months | 0.00 | 67.16 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 | 15.45 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 67.18 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 13.05 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 67.18 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 | 14-FEB-16:06 | 12.20 | 04-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 67.18 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 | 08-MAR-16:07 | 10.93 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 67.18 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.92 | 13-APR-17:00 | 8.32 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 67.18 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.40 | 19-MAY-15:10 | 7.04 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 67.18 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.64 | 28-JUN-16:00 | 5.56 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 67.18 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.32 | 22-JUL-15:10 | 2.47 | 07-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 67.18 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 | 20-AUG-15:10 | 3.42 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 67.18 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 | 02-SEP-15:09 | 4.37 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 67.18 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 01-OCT-16:00 | 10.38 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 67.18 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 11.12 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 67.18 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 13.62 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 67.18 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 | |||||
Maximum of Months | 180.00 | 67.18 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6.64 | 13.62 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.87 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 46.77 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 106.87 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | 14-FEB-16:09 | 43.70 | 04-FEB-06:06 |
March | 180.00 | 01-MAR-00:10 | 106.87 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 | 08-MAR-16:10 | 39.18 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 106.87 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 | 13-APR-17:00 | 31.25 | 08-APR-07:20 |
May | 180.00 | 01-MAY-00:10 | 106.87 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.19 | 19-MAY-15:08 | 25.21 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 106.87 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.80 | 28-JUN-16:00 | 19.94 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 106.87 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.64 | 22-JUL-15:10 | 8.05 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 106.87 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 | 20-AUG-15:10 | 12.24 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 106.87 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.28 | 02-SEP-15:09 | 15.67 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 106.87 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.74 | 01-OCT-16:00 | 37.18 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 106.87 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 39.91 | 28-NOV-08:10 |
December | 180.00 | 01-DEC-00:10 | 106.87 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 48.82 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.05 | |||||
Maximum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 23.80 | 48.82 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.85 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 46.77 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 106.85 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | 14-FEB-16:06 | 43.70 | 04-FEB-06:06 |
March | 180.00 | 01-MAR-00:10 | 106.85 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 | 08-MAR-16:07 | 39.18 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 106.85 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 | 13-APR-17:00 | 31.25 | 08-APR-07:20 |
May | 180.00 | 01-MAY-00:10 | 106.85 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.18 | 19-MAY-15:08 | 25.21 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 106.85 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.80 | 28-JUN-16:00 | 19.94 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 106.85 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.63 | 22-JUL-15:10 | 11.46 | 08-JUL-07:40 |
August | 180.00 | 01-AUG-00:10 | 106.85 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 20-AUG-15:10 | 13.44 | 11-AUG-07:50 |
September | 180.00 | 01-SEP-00:10 | 106.85 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 02-SEP-15:07 | 15.67 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 106.85 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.74 | 01-OCT-16:00 | 37.18 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 106.85 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 39.84 | 27-NOV-06:50 |
December | 180.00 | 01-DEC-00:10 | 106.85 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 48.81 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.46 | |||||
Maximum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 23.80 | 48.81 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1044.00 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 56.34 | 21-JAN-07:00 |
February | 2263.36 | 01-FEB-00:10 | 1044.00 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 52.64 | 04-FEB-06:30 |
March | 2263.36 | 01-MAR-00:10 | 1044.00 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 | 08-MAR-14:00 | 47.46 | 05-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1044.00 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.71 | 13-APR-17:00 | 37.77 | 08-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1044.00 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.11 | 22-MAY-13:00 | 32.64 | 07-MAY-05:00 |
June | 2263.36 | 01-JUN-00:10 | 1044.00 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.09 | 28-JUN-16:00 | 27.64 | 09-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1044.00 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 | 22-JUL-15:00 | 13.77 | 08-JUL-03:00 |
August | 2263.36 | 01-AUG-00:10 | 1044.00 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.03 | 20-AUG-15:00 | 19.40 | 31-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1044.00 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 | 03-SEP-14:00 | 23.41 | 20-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 1044.00 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.14 | 01-OCT-16:00 | 45.86 | 26-OCT-04:15 |
November | 2263.36 | 01-NOV-00:10 | 1044.00 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 49.25 | 27-NOV-06:00 |
December | 2263.36 | 01-DEC-00:10 | 1044.00 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 58.93 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1044.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 | ||||
Maximum of Months | 2263.36 | 1044.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.09 | 58.93 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.87 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 46.87 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 106.87 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 | 14-FEB-16:09 | 43.80 | 04-FEB-06:06 |
March | 180.00 | 01-MAR-00:10 | 106.87 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.08 | 08-MAR-16:09 | 39.28 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 106.87 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.79 | 13-APR-17:00 | 29.91 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 106.87 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.11 | 19-MAY-15:10 | 25.30 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 106.87 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 28-JUN-16:00 | 20.03 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 106.87 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.13 | 22-JUL-15:10 | 8.13 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 106.87 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.70 | 01-AUG-16:00 | 12.33 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 106.87 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.10 | 02-SEP-15:10 | 15.76 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 106.87 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.66 | 01-OCT-16:00 | 37.28 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 106.87 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 39.95 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 106.87 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 48.92 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 | |||||
Maximum of Months | 180.00 | 106.87 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 48.92 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 106.85 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 46.87 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 106.85 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 | 14-FEB-16:09 | 43.80 | 04-FEB-06:06 |
March | 180.00 | 01-MAR-00:10 | 106.85 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.08 | 08-MAR-16:07 | 39.28 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 106.85 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.79 | 13-APR-17:00 | 29.91 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 106.85 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.11 | 19-MAY-15:10 | 25.30 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 106.85 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.05 | 28-JUN-16:00 | 20.03 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 106.85 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.09 | 22-JUL-15:10 | 9.09 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 106.85 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.69 | 01-AUG-16:00 | 12.32 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 106.85 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.20 | 02-SEP-15:10 | 15.76 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 106.85 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.66 | 01-OCT-16:00 | 37.28 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 106.85 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 39.94 | 27-NOV-06:10 |
December | 180.00 | 01-DEC-00:10 | 106.85 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 48.92 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 | |||||
Maximum of Months | 180.00 | 106.85 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 23.05 | 48.92 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 67.18 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 23.98 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 67.18 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 | 14-FEB-16:10 | 22.41 | 04-FEB-06:10 |
March | 180.00 | 01-MAR-00:10 | 67.18 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 | 08-MAR-16:10 | 20.10 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 67.18 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.48 | 13-APR-17:00 | 15.30 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 67.18 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.19 | 19-MAY-15:10 | 12.95 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 67.18 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.14 | 28-JUN-16:00 | 10.25 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 67.18 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 | 22-JUL-15:10 | 4.16 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 67.18 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.59 | 20-AUG-15:10 | 6.31 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 67.18 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.26 | 02-SEP-15:10 | 8.06 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 67.18 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 01-OCT-16:00 | 19.07 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 67.18 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 20.44 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 67.18 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 25.03 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 67.18 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.16 | |||||
Maximum of Months | 180.00 | 67.18 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 12.14 | 25.03 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2486.81 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 125.64 | 21-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 2486.81 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 118.02 | 04-FEB-06:10 |
March | 26988.77 | 01-MAR-00:10 | 2486.81 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 106.93 | 05-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2486.81 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.79 | 13-APR-17:00 | 83.82 | 08-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2486.81 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 22-MAY-13:00 | 72.39 | 07-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2486.81 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.47 | 28-JUN-16:00 | 59.42 | 09-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2486.81 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.47 | 22-JUL-15:00 | 28.30 | 08-JUL-03:30 |
August | 26988.77 | 01-AUG-00:10 | 2486.81 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.22 | 20-AUG-15:00 | 40.41 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2486.81 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.99 | 03-SEP-14:00 | 48.94 | 09-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2486.81 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.25 | 01-OCT-16:00 | 101.84 | 26-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2486.81 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 108.53 | 27-NOV-06:10 |
December | 26988.77 | 01-DEC-00:10 | 2486.81 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 130.71 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2486.81 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 | |||||
Maximum of Months | 26988.77 | 2486.81 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 48.47 | 130.71 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2486.81 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 125.64 | 21-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 2486.81 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 118.02 | 04-FEB-06:10 |
March | 26988.77 | 01-MAR-00:10 | 2486.81 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 106.93 | 05-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 2486.81 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.79 | 13-APR-17:00 | 83.82 | 08-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2486.81 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 22-MAY-13:00 | 72.39 | 07-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2486.81 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.47 | 28-JUN-16:00 | 59.42 | 09-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 2486.81 | 03-JUL-19:19 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.47 | 22-JUL-15:00 | 28.30 | 08-JUL-03:30 |
August | 26988.77 | 01-AUG-00:10 | 2486.81 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.22 | 20-AUG-15:00 | 40.41 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2486.81 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.99 | 03-SEP-14:00 | 48.94 | 09-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 2486.81 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.25 | 01-OCT-16:00 | 101.84 | 26-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 2486.81 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 108.53 | 27-NOV-06:10 |
December | 26988.77 | 01-DEC-00:10 | 2486.81 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 130.71 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 2486.81 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 | |||||
Maximum of Months | 26988.77 | 2486.81 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 48.47 | 130.71 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 981.75 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 112.46 | 21-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 981.75 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 105.65 | 04-FEB-06:10 |
March | 2401.70 | 01-MAR-00:10 | 981.75 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 95.71 | 05-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 981.75 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 6.12 | 13-APR-17:00 | 75.02 | 08-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 981.75 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 17.94 | 22-MAY-13:00 | 64.42 | 07-MAY-05:00 |
June | 2401.70 | 01-JUN-00:10 | 981.75 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 43.44 | 28-JUN-16:00 | 53.20 | 09-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 981.75 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 41.63 | 22-JUL-15:00 | 25.34 | 08-JUL-04:00 |
August | 2401.70 | 01-AUG-00:10 | 981.75 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 32.46 | 20-AUG-15:00 | 36.16 | 31-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 981.75 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 25.98 | 03-SEP-14:00 | 43.80 | 09-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 981.75 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 14.59 | 01-OCT-16:00 | 91.26 | 26-OCT-07:00 |
November | 2401.70 | 01-NOV-00:10 | 981.75 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 97.13 | 27-NOV-07:00 |
December | 2401.70 | 01-DEC-00:10 | 981.75 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 116.00 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 981.75 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 25.34 | ||||||
Maximum of Months | 2401.70 | 981.75 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 43.44 | 116.00 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1104.91 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 99.92 | 21-JAN-07:00 |
February | 2395.44 | 01-FEB-00:10 | 1104.91 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 93.35 | 04-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1104.91 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 83.68 | 05-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1104.91 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.54 | 17-APR-15:00 | 64.21 | 08-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1104.91 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.39 | 22-MAY-13:00 | 55.21 | 07-MAY-05:00 |
June | 2395.44 | 01-JUN-00:10 | 1104.91 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.46 | 28-JUN-16:00 | 47.03 | 09-JUN-04:03 |
July | 2395.44 | 01-JUL-00:10 | 1104.91 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.71 | 22-JUL-15:00 | 23.33 | 08-JUL-03:00 |
August | 2395.44 | 01-AUG-00:10 | 1104.91 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.73 | 20-AUG-15:00 | 32.84 | 31-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1104.91 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.40 | 03-SEP-14:00 | 39.53 | 20-SEP-06:00 |
October | 2395.44 | 01-OCT-23:10 | 1104.91 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.23 | 01-OCT-16:00 | 79.40 | 26-OCT-07:00 |
November | 2395.44 | 01-NOV-00:10 | 1104.91 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 85.10 | 27-NOV-06:50 |
December | 2395.44 | 01-DEC-00:10 | 1104.91 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 104.30 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1104.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | ||||
Maximum of Months | 2395.44 | 1104.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.46 | 104.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13919.20 | 27-JAN-22:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12619.33 | 01-FEB-22:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10653.31 | 12-MAR-10:33 | 11501.89 | 8343.99 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10933.74 | 29-APR-10:33 | 11501.89 | 6953.51 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11179.43 | 20-MAY-10:33 | 11501.89 | 6953.51 | 10646.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11887.83 | 25-JUN-10:33 | 11501.89 | 8343.99 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13328.34 | 28-JUL-21:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15648.26 | 23-AUG-21:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17729.10 | 08-SEP-21:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18568.40 | 12-OCT-21:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18079.09 | 03-NOV-21:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17418.10 | 01-DEC-22:00 | 10223.90 | 7417.00 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 10653.31 | 10223.90 | 6953.51 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18568.40 | 11501.89 | 8343.99 | 12167.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4124.12 | 03-JAN-13:00 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.48 |
February | 4346.74 | 14-FEB-13:20 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.30 |
March | 3835.98 | 08-MAR-13:30 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.31 |
April | 2994.47 | 13-APR-13:05 | 519.79 | 256.16 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
May | 2317.51 | 13-MAY-13:10 | 389.84 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 10.49 | 0.00 |
June | 2738.64 | 29-JUN-14:30 | 389.84 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 30.81 | 0.00 |
July | 2936.88 | 22-JUL-13:30 | 389.84 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 30.09 | 0.00 |
August | 3659.95 | 22-AUG-13:20 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 16.94 | 0.00 |
September | 4359.96 | 28-SEP-13:05 | 519.79 | 256.16 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 12.16 | 0.00 |
October | 4401.60 | 05-OCT-13:00 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 3.72 | 0.00 |
November | 4284.10 | 01-NOV-12:30 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 |
December | 4255.30 | 31-DEC-13:00 | 389.84 | 153.69 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2317.51 | 259.90 | 128.08 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4401.60 | 519.79 | 256.16 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 30.81 | 40.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1279.36 | 03-JAN-21:50 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.85 |
February | 1537.20 | 15-FEB-21:10 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.18 |
March | 1562.68 | 08-MAR-22:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.41 |
April | 1818.86 | 13-APR-21:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 |
May | 1880.71 | 19-MAY-20:54 | 6019.20 | 2373.04 | 3760.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
June | 2141.72 | 28-JUN-21:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 4.53 | 0.00 |
July | 2216.87 | 21-JUL-21:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.51 | 0.00 |
August | 2160.29 | 18-AUG-20:10 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.81 | 0.00 |
September | 1999.22 | 13-SEP-20:04 | 6019.20 | 2373.04 | 3760.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 1937.36 | 05-OCT-20:10 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 |
November | 1555.83 | 02-NOV-21:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.88 |
December | 1215.53 | 29-DEC-22:00 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1215.53 | 1203.84 | 474.61 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2216.87 | 6019.20 | 2373.04 | 3760.73 | 0.00 | 0.00 | 0.00 | 0.00 | 5.51 | 23.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 818.92 | 01-JAN-13:00 | 95.47 | 205.25 | 353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.90 |
February | 898.70 | 14-FEB-13:00 | 63.65 | 171.04 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.94 |
March | 878.47 | 26-MAR-10:33 | 286.42 | 615.76 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.19 |
April | 1027.96 | 29-APR-10:33 | 286.42 | 513.13 | 927.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 |
May | 1224.51 | 19-MAY-20:54 | 1272.96 | 2736.71 | 3976.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.55 |
June | 1899.41 | 29-JUN-20:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 | 0.00 |
July | 1912.38 | 21-JUL-20:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 14.26 | 0.00 |
August | 1804.51 | 18-AUG-20:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 7.03 | 0.00 |
September | 1449.80 | 01-SEP-20:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 |
October | 1253.22 | 02-OCT-20:00 | 222.77 | 615.76 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.46 |
November | 952.51 | 01-NOV-12:30 | 63.65 | 171.04 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.71 |
December | 840.60 | 31-DEC-13:00 | 95.47 | 205.25 | 353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 818.92 | 63.65 | 171.04 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1912.38 | 1272.96 | 2736.71 | 3976.33 | 0.00 | 0.00 | 0.00 | 0.00 | 14.26 | 30.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 442.69 | 01-JAN-13:00 | 73.44 | 45.78 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.88 |
February | 489.45 | 14-FEB-13:20 | 48.96 | 38.16 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.38 |
March | 470.36 | 26-MAR-10:33 | 220.32 | 137.35 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.20 |
April | 551.22 | 29-APR-10:33 | 220.32 | 114.47 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.40 |
May | 576.54 | 20-MAY-10:33 | 220.32 | 114.47 | 267.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 |
June | 844.61 | 28-JUN-20:30 | 195.84 | 122.09 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 6.85 | 0.00 |
July | 881.74 | 21-JUL-19:10 | 171.36 | 137.35 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 12.05 | 0.00 |
August | 794.64 | 18-AUG-20:10 | 195.84 | 122.09 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 0.00 |
September | 607.74 | 03-SEP-10:33 | 220.32 | 137.35 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 6.13 | 0.00 |
October | 587.79 | 01-OCT-12:00 | 73.44 | 45.78 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 | 0.00 |
November | 513.01 | 01-NOV-12:30 | 48.96 | 38.16 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.87 |
December | 454.17 | 31-DEC-13:00 | 73.44 | 45.78 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 442.69 | 48.96 | 38.16 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 881.74 | 220.32 | 137.35 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 12.05 | 17.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37272.32 | 05-JAN-21:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 61.22 |
February | 37648.88 | 14-FEB-21:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 44.11 |
March | 37959.75 | 08-MAR-21:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 31.32 |
April | 38598.36 | 28-APR-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 5.46 |
May | 38780.76 | 19-MAY-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 4.78 | 0.00 |
June | 39304.05 | 28-JUN-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 17.79 | 0.00 |
July | 39326.58 | 21-JUL-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 19.47 | 0.00 |
August | 39166.81 | 17-AUG-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 12.83 | 0.00 |
September | 38798.01 | 01-SEP-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 3.65 |
October | 38502.62 | 02-OCT-20:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 15.66 |
November | 37589.11 | 09-NOV-21:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 36.82 |
December | 37252.21 | 01-DEC-21:00 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 46.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37252.21 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39326.58 | 705.60 | 360.62 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 19.47 | 61.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15548.85 | 01-JAN-13:00 | 5122.80 | 103.85 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.92 |
February | 15447.65 | 14-FEB-13:10 | 3415.20 | 86.54 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.81 |
March | 14107.45 | 11-MAR-13:30 | 5122.80 | 86.54 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.99 |
April | 11660.21 | 01-APR-13:30 | 5122.80 | 86.54 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.72 |
May | 10486.97 | 19-MAY-21:05 | 61473.60 | 3776.30 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 |
June | 11572.04 | 28-JUN-21:10 | 15368.40 | 944.07 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 24.46 | 0.00 |
July | 11832.93 | 21-JUL-21:10 | 15368.40 | 944.07 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 30.08 | 0.00 |
August | 12474.75 | 20-AUG-12:00 | 5122.80 | 103.85 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 46.07 | 0.00 |
September | 14297.04 | 28-SEP-13:10 | 6830.40 | 173.08 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 26.89 | 0.00 |
October | 15412.37 | 15-OCT-12:00 | 5122.80 | 103.85 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.49 |
November | 15963.22 | 23-NOV-11:00 | 8538.00 | 103.85 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.46 |
December | 16139.69 | 31-DEC-13:00 | 5122.80 | 103.85 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10486.97 | 3415.20 | 86.54 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16139.69 | 61473.60 | 3776.30 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 46.07 | 88.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 33648.38 | 03-JAN-19:04 | 248391.78 | 59614.13 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.28 |
February | 35366.03 | 14-FEB-22:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.61 |
March | 35390.38 | 08-MAR-22:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.39 |
April | 38014.37 | 13-APR-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.20 |
May | 38623.73 | 19-MAY-21:05 | 182491.92 | 25548.91 | 29559.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.56 |
June | 42286.57 | 28-JUN-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 69.86 | 0.00 |
July | 43022.68 | 21-JUL-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 85.92 | 0.00 |
August | 42641.71 | 18-AUG-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 26.52 | 0.00 |
September | 41085.45 | 13-SEP-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.10 |
October | 40348.54 | 06-OCT-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.28 |
November | 35654.33 | 01-NOV-21:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.08 |
December | 31706.79 | 29-DEC-22:10 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 31706.79 | 45622.98 | 6387.23 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43022.68 | 248391.78 | 59614.13 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 85.92 | 360.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3689.21 | 01-JAN-16:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.88 |
February | 4013.98 | 14-FEB-16:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
March | 4018.33 | 08-MAR-16:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 | 0.00 |
April | 4142.18 | 26-APR-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 | 0.00 |
May | 4187.38 | 20-MAY-15:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 | 0.00 |
June | 4199.66 | 19-JUN-18:01 | 970.20 | 665.78 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 8.47 | 0.00 |
July | 3532.25 | 06-JUL-08:61 | 360.00 | 470.21 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 4.64 | 0.00 |
August | 3521.26 | 17-AUG-08:61 | 252.00 | 329.15 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 | 0.00 |
September | 3698.60 | 21-SEP-08:61 | 252.00 | 329.15 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.68 |
October | 4084.04 | 31-OCT-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 1.84 | 0.00 |
November | 3710.78 | 03-NOV-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.31 |
December | 3679.31 | 30-DEC-16:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3521.26 | 252.00 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4199.66 | 970.20 | 665.78 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 8.47 | 17.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3564.50 | 01-JAN-16:01 | 378.00 | 246.84 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.53 |
February | 3891.29 | 14-FEB-16:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
March | 4195.12 | 30-MAR-18:11 | 1386.00 | 951.00 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.88 |
April | 4747.58 | 25-APR-16:21 | 972.00 | 299.19 | 1343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 |
May | 4241.42 | 20-MAY-21:51 | 1386.00 | 908.26 | 921.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 |
June | 4497.50 | 14-JUN-08:21 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 3.07 | 0.00 |
July | 3935.03 | 06-JUL-08:61 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 2.03 | 0.00 |
August | 4108.85 | 23-AUG-17:01 | 777.60 | 572.74 | 1074.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 |
September | 4021.87 | 21-SEP-21:51 | 1620.00 | 644.33 | 829.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 |
October | 3982.72 | 05-OCT-21:51 | 1620.00 | 644.33 | 829.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.14 |
November | 3609.18 | 03-NOV-15:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 |
December | 3556.39 | 30-DEC-16:01 | 378.00 | 246.84 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3556.39 | 360.00 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4747.58 | 1620.00 | 951.00 | 1343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 3.07 | 16.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 738.53 | 03-JAN-12:40 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 |
February | 755.59 | 14-FEB-13:00 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.90 |
March | 640.14 | 08-MAR-13:30 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.09 |
April | 473.65 | 13-APR-13:15 | 0.00 | 37.61 | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 |
May | 340.17 | 13-MAY-13:10 | 0.00 | 22.16 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 | 0.00 |
June | 378.04 | 29-JUN-14:30 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 | 0.00 |
July | 419.83 | 23-JUL-13:30 | 0.00 | 22.16 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 3.56 | 0.00 |
August | 543.15 | 22-AUG-13:30 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 | 0.00 |
September | 696.53 | 28-SEP-13:30 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 | 0.00 |
October | 749.62 | 19-OCT-12:30 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 |
November | 744.46 | 20-NOV-13:30 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.30 |
December | 760.21 | 31-DEC-13:40 | 0.00 | 22.16 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 340.17 | 0.00 | 18.81 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 760.21 | 0.00 | 37.61 | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 | 7.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 824.14 | 01-JAN-09:02 | 324.00 | 225.72 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.90 |
February | 1066.58 | 14-FEB-16:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 | 0.00 |
March | 1112.29 | 08-MAR-16:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 | 0.00 |
April | 1209.89 | 29-APR-15:01 | 378.00 | 155.19 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 | 0.00 |
May | 1226.11 | 15-MAY-18:01 | 970.20 | 418.53 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.97 | 0.00 |
June | 1287.37 | 17-JUN-08:31 | 540.00 | 376.21 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 | 0.00 |
July | 1160.45 | 06-JUL-08:61 | 360.00 | 295.59 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 | 0.00 |
August | 1121.47 | 01-AUG-08:31 | 360.00 | 295.59 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 | 0.00 |
September | 1154.16 | 30-SEP-21:51 | 1108.80 | 456.83 | 722.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.08 |
October | 1158.93 | 09-OCT-15:01 | 378.00 | 155.19 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 | 0.00 |
November | 1010.06 | 02-NOV-18:11 | 1108.80 | 478.32 | 1011.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.79 |
December | 957.76 | 01-DEC-19:02 | 831.60 | 358.74 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 824.14 | 324.00 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1287.37 | 1108.80 | 478.32 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.97 | 7.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3242.55 | 02-JAN-09:01 | 252.00 | 329.15 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.73 |
February | 3507.19 | 14-FEB-16:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
March | 3482.64 | 13-MAR-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 |
April | 3633.36 | 29-APR-15:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 0.00 |
May | 3668.12 | 20-MAY-15:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 0.00 |
June | 3693.44 | 14-JUN-08:61 | 252.00 | 329.15 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 3.86 | 0.00 |
July | 3233.10 | 04-JUL-08:61 | 378.00 | 418.92 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 | 0.00 |
August | 3182.24 | 17-AUG-08:61 | 252.00 | 329.15 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 4.11 | 0.00 |
September | 3453.48 | 21-SEP-08:61 | 252.00 | 329.15 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.57 |
October | 3578.72 | 31-OCT-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 1.97 | 0.00 |
November | 3290.07 | 07-NOV-09:01 | 252.00 | 329.15 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.70 |
December | 3233.59 | 19-DEC-09:01 | 252.00 | 329.15 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3182.24 | 252.00 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3693.44 | 680.40 | 418.92 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 32.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3085.96 | 01-JAN-09:02 | 324.00 | 359.03 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.41 |
February | 3405.53 | 14-FEB-16:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
March | 3405.15 | 13-MAR-15:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.24 |
April | 4021.85 | 28-APR-08:51 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.86 |
May | 4135.83 | 14-MAY-08:51 | 540.00 | 598.38 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.75 |
June | 4439.04 | 20-JUN-08:32 | 216.00 | 282.09 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 |
July | 4113.04 | 04-JUL-08:61 | 378.00 | 418.87 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.08 |
August | 3990.85 | 07-AUG-08:32 | 216.00 | 282.09 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.86 |
September | 3859.75 | 03-SEP-08:32 | 324.00 | 359.03 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 |
October | 3494.30 | 02-OCT-08:51 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.62 |
November | 3202.43 | 07-NOV-09:01 | 252.00 | 329.11 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.40 |
December | 3078.35 | 30-DEC-09:02 | 324.00 | 359.03 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3078.35 | 216.00 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 | |
Maximum of Months | 4439.04 | 680.40 | 598.38 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1463.05 | 01-JAN-13:00 | 754.45 | 348.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.13 |
February | 1570.25 | 14-FEB-13:30 | 502.97 | 290.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.08 |
March | 1492.57 | 12-MAR-10:33 | 2263.36 | 1044.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.02 |
April | 1695.99 | 29-APR-10:33 | 2263.36 | 870.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 |
May | 1756.47 | 20-MAY-10:33 | 2263.36 | 870.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.92 |
June | 2640.29 | 23-JUN-18:17 | 5281.16 | 2784.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.02 | 0.00 |
July | 2796.98 | 21-JUL-18:25 | 3520.78 | 1856.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.35 | 0.00 |
August | 2632.01 | 18-AUG-18:15 | 3520.78 | 1856.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.70 | 0.00 |
September | 2141.93 | 29-SEP-15:03 | 8801.94 | 2030.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.32 | 0.00 |
October | 2141.91 | 02-OCT-15:03 | 8801.94 | 2030.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.38 | 0.00 |
November | 1631.26 | 01-NOV-12:30 | 502.97 | 290.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.01 |
December | 1457.99 | 31-DEC-13:00 | 754.45 | 348.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1457.99 | 502.97 | 290.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2796.98 | 8801.94 | 2784.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.35 | 24.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3918.34 | 09-JAN-16:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.63 |
February | 4268.16 | 14-FEB-16:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 |
March | 4248.58 | 07-MAR-16:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 |
April | 4403.81 | 13-APR-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 3.56 | 0.00 |
May | 4459.32 | 20-MAY-15:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 5.95 | 0.00 |
June | 4466.28 | 20-JUN-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 11.80 | 0.00 |
July | 3809.49 | 06-JUL-08:61 | 360.00 | 470.21 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 4.65 | 0.00 |
August | 3715.54 | 17-AUG-08:61 | 252.00 | 329.15 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 0.00 |
September | 3812.63 | 21-SEP-08:61 | 252.00 | 329.15 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 |
October | 4335.51 | 31-OCT-15:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 1.81 | 0.00 |
November | 3945.86 | 06-NOV-16:01 | 680.40 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.92 |
December | 3913.95 | 31-DEC-16:01 | 378.00 | 246.87 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3715.54 | 252.00 | 209.46 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4466.28 | 680.40 | 470.21 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 11.80 | 18.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3771.52 | 05-JAN-16:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.35 |
February | 4117.31 | 14-FEB-16:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
March | 4558.62 | 30-MAR-18:11 | 1386.00 | 951.00 | 1290.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.48 |
April | 5046.55 | 25-APR-16:21 | 972.00 | 299.19 | 1343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.91 |
May | 4516.02 | 20-MAY-21:51 | 1386.00 | 908.26 | 921.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.79 |
June | 4752.96 | 14-JUN-08:21 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 3.10 | 0.00 |
July | 4141.70 | 06-JUL-08:61 | 360.00 | 470.16 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 2.10 | 0.00 |
August | 4358.44 | 23-AUG-17:01 | 777.60 | 572.74 | 1074.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.52 |
September | 4225.08 | 21-SEP-21:51 | 1620.00 | 644.33 | 829.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 |
October | 4198.38 | 19-OCT-15:01 | 680.40 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 | 0.00 |
November | 3915.61 | 02-NOV-18:11 | 1108.80 | 760.80 | 1032.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.09 |
December | 3753.56 | 30-DEC-16:01 | 378.00 | 246.84 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3753.56 | 360.00 | 209.43 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5046.55 | 1620.00 | 951.00 | 1343.18 | 0.00 | 0.00 | 0.00 | 0.00 | 3.10 | 16.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1880.71 | 09-JAN-16:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.32 |
February | 2029.23 | 14-FEB-16:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
March | 1994.15 | 13-MAR-15:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 |
April | 2055.24 | 13-APR-15:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 1.70 | 0.00 |
May | 2062.34 | 20-MAY-15:01 | 378.00 | 155.19 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 3.01 | 0.00 |
June | 2049.47 | 19-JUN-15:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 | 0.00 |
July | 1782.21 | 06-JUL-08:61 | 360.00 | 295.59 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 2.24 | 0.00 |
August | 1794.43 | 17-AUG-08:61 | 252.00 | 206.91 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 2.38 | 0.00 |
September | 1855.17 | 21-SEP-08:61 | 252.00 | 206.91 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.62 |
October | 2070.88 | 31-OCT-15:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 | 0.00 |
November | 1878.10 | 20-NOV-16:01 | 680.40 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.24 |
December | 1882.24 | 31-DEC-16:01 | 378.00 | 155.19 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1782.21 | 252.00 | 131.67 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2070.88 | 680.40 | 295.59 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 | 9.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17191.18 | 05-JAN-22:50 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.16 |
February | 18519.41 | 14-FEB-23:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.29 |
March | 19102.19 | 16-MAR-21:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 |
April | 21133.33 | 28-APR-21:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.58 |
May | 21965.33 | 19-MAY-21:05 | 107955.07 | 6631.49 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.39 |
June | 23314.51 | 28-JUN-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 14.37 | 0.00 |
July | 23457.06 | 21-JUL-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 17.97 | 0.00 |
August | 22744.20 | 17-AUG-22:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 10.59 | 0.00 |
September | 21770.18 | 01-SEP-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 |
October | 21237.71 | 02-OCT-21:52 | 215910.14 | 13262.99 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.30 |
November | 18819.77 | 02-NOV-21:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.04 |
December | 17703.25 | 01-DEC-22:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17191.18 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23457.06 | 215910.14 | 13262.99 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 17.97 | 78.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18973.23 | 05-JAN-22:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.18 |
February | 20072.23 | 14-FEB-23:00 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.29 |
March | 20715.50 | 16-MAR-21:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 |
April | 22422.38 | 28-APR-21:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.58 |
May | 23182.57 | 19-MAY-21:05 | 107955.07 | 6631.49 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.39 |
June | 24501.69 | 27-JUN-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 14.25 | 0.00 |
July | 24642.75 | 21-JUL-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 17.97 | 0.00 |
August | 23922.26 | 17-AUG-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 9.44 | 0.00 |
September | 22955.65 | 01-SEP-21:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.71 |
October | 22379.31 | 02-OCT-21:52 | 215910.14 | 13262.99 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.30 |
November | 20472.99 | 08-NOV-22:20 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.19 |
December | 19549.53 | 01-DEC-22:10 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18973.23 | 26988.77 | 1657.87 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24642.75 | 215910.14 | 13262.99 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 17.97 | 75.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26506.96 | 01-JAN-11:40 | 1601.14 | 654.50 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 46.46 |
February | 27235.55 | 14-FEB-11:40 | 1067.42 | 545.42 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 23.99 |
March | 28224.16 | 12-MAR-10:33 | 2401.70 | 981.75 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 38.04 |
April | 29390.36 | 29-APR-10:33 | 2401.70 | 818.12 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 12.10 |
May | 29508.92 | 20-MAY-10:33 | 2401.70 | 818.12 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 |
June | 30159.20 | 29-JUN-10:40 | 1601.14 | 818.12 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 25.37 | 0.00 |
July | 30445.55 | 23-JUL-10:40 | 1601.14 | 654.50 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 22.75 | 0.00 |
August | 30405.98 | 20-AUG-10:40 | 1601.14 | 654.50 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 17.98 | 0.00 |
September | 30217.25 | 03-SEP-10:40 | 2401.70 | 981.75 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 13.21 | 0.00 |
October | 29460.09 | 01-OCT-10:33 | 2401.70 | 981.75 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 |
November | 27609.10 | 01-NOV-10:40 | 1067.42 | 545.42 | 29209.11 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 35.09 |
December | 26457.27 | 30-DEC-11:50 | 800.57 | 272.71 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 52.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26457.27 | 800.57 | 272.71 | 14604.56 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30445.55 | 2401.70 | 981.75 | 43813.67 | 56232.08 | 0.00 | 0.00 | 0.00 | 25.37 | 52.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3529.09 | 01-JAN-13:00 | 798.48 | 368.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.98 |
February | 3989.04 | 14-FEB-13:30 | 532.32 | 306.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.20 |
March | 3571.93 | 08-MAR-11:33 | 1596.96 | 920.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 |
April | 4277.73 | 13-APR-15:01 | 9315.60 | 2148.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 | 0.00 |
May | 5047.72 | 20-MAY-14:20 | 798.48 | 306.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 0.00 |
June | 6870.34 | 28-JUN-15:03 | 7984.80 | 1841.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.14 | 0.00 |
July | 6934.32 | 22-JUL-13:30 | 798.48 | 306.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.08 | 0.00 |
August | 6997.47 | 21-AUG-14:10 | 798.48 | 306.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.87 | 0.00 |
September | 6865.97 | 03-SEP-13:30 | 532.32 | 245.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.98 | 0.00 |
October | 6143.87 | 01-OCT-13:30 | 532.32 | 245.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.87 | 0.00 |
November | 3926.49 | 01-NOV-12:30 | 532.32 | 306.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.47 |
December | 3622.90 | 31-DEC-13:00 | 798.48 | 368.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3529.09 | 532.32 | 245.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6997.47 | 9315.60 | 2148.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.14 | 44.61 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.397965E+12 | 263056.02 | 05-JAN-20:10 | 0.387283E+12 | 405780.39 | 28-JAN-18:40 |
February | 0.360706E+12 | 264295.88 | 15-FEB-20:10 | 0.338071E+12 | 369459.73 | 07-FEB-18:40 |
March | 0.401344E+12 | 275488.66 | 13-MAR-19:19 | 0.355458E+12 | 356531.45 | 03-MAR-18:00 |
April | 0.418686E+12 | 320611.81 | 28-APR-18:49 | 0.312119E+12 | 319724.68 | 15-APR-19:10 |
May | 0.465056E+12 | 360759.35 | 19-MAY-19:10 | 0.279435E+12 | 278060.10 | 04-MAY-21:10 |
June | 0.524283E+12 | 388062.03 | 27-JUN-19:30 | 0.228966E+12 | 200511.79 | 08-JUN-19:10 |
July | 0.589347E+12 | 396477.46 | 21-JUL-19:30 | 0.218760E+12 | 153363.14 | 01-JUL-17:30 |
August | 0.570394E+12 | 386082.86 | 18-AUG-19:10 | 0.219912E+12 | 153437.21 | 30-AUG-17:00 |
September | 0.496614E+12 | 358617.81 | 13-SEP-19:19 | 0.225890E+12 | 164644.70 | 30-SEP-17:10 |
October | 0.448614E+12 | 314818.67 | 10-OCT-19:19 | 0.307329E+12 | 319804.93 | 27-OCT-19:00 |
November | 0.392821E+12 | 275947.20 | 01-NOV-19:19 | 0.342870E+12 | 351105.33 | 15-NOV-18:30 |
December | 0.401719E+12 | 262775.96 | 18-DEC-20:10 | 0.390598E+12 | 407916.14 | 11-DEC-18:49 |
Annual Sum or Average | 0.546755E+13 | 0.360669E+13 | ||||
Minimum of Months | 0.360706E+12 | 262775.96 | 0.218760E+12 | 153363.14 | ||
Maximum of Months | 0.589347E+12 | 396477.46 | 0.390598E+12 | 407916.14 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.465807E+11 | 0.173770E+11 | 0.146779E+12 | 0.544792E+11 | 0.430377E+11 | 0.627358E+10 | 0.00 | 0.144805E+11 | 0.00 | 0.00 | 0.198346E+11 | 0.454347E+11 | 0.00 |
February | 0.419438E+11 | 0.148004E+11 | 0.132565E+12 | 0.492071E+11 | 0.391724E+11 | 0.635861E+10 | 0.00 | 0.168438E+11 | 0.00 | 0.00 | 0.162257E+11 | 0.402564E+11 | 0.00 |
March | 0.462086E+11 | 0.150934E+11 | 0.146789E+12 | 0.544810E+11 | 0.443312E+11 | 0.868747E+10 | 0.00 | 0.269936E+11 | 0.00 | 0.00 | 0.117960E+11 | 0.432704E+11 | 0.00 |
April | 0.443453E+11 | 0.132825E+11 | 0.142011E+12 | 0.527212E+11 | 0.460489E+11 | 0.961358E+10 | 0.00 | 0.598691E+11 | 0.00 | 0.00 | 0.642407E+10 | 0.408033E+11 | 0.00 |
May | 0.457069E+11 | 0.125967E+11 | 0.146789E+12 | 0.544797E+11 | 0.498635E+11 | 0.100256E+11 | 0.00 | 0.940107E+11 | 0.00 | 0.00 | 0.687652E+10 | 0.409948E+11 | 0.00 |
June | 0.440357E+11 | 0.115914E+11 | 0.142058E+12 | 0.527229E+11 | 0.541552E+11 | 0.100210E+11 | 0.00 | 0.155903E+12 | 0.00 | 0.00 | 0.116800E+11 | 0.385005E+11 | 0.00 |
July | 0.455972E+11 | 0.122904E+11 | 0.146742E+12 | 0.544777E+11 | 0.588592E+11 | 0.106570E+11 | 0.00 | 0.203482E+12 | 0.00 | 0.00 | 0.144797E+11 | 0.390105E+11 | 0.00 |
August | 0.457367E+11 | 0.132159E+11 | 0.146800E+12 | 0.544807E+11 | 0.595319E+11 | 0.106642E+11 | 0.00 | 0.184637E+12 | 0.00 | 0.00 | 0.122438E+11 | 0.393201E+11 | 0.00 |
September | 0.445876E+11 | 0.140481E+11 | 0.142022E+12 | 0.527215E+11 | 0.549810E+11 | 0.996596E+10 | 0.00 | 0.128758E+12 | 0.00 | 0.00 | 0.708891E+10 | 0.388137E+11 | 0.00 |
October | 0.464026E+11 | 0.158590E+11 | 0.146768E+12 | 0.544791E+11 | 0.518451E+11 | 0.961237E+10 | 0.00 | 0.703519E+11 | 0.00 | 0.00 | 0.761600E+10 | 0.419692E+11 | 0.00 |
November | 0.450163E+11 | 0.165049E+11 | 0.142074E+12 | 0.527223E+11 | 0.450570E+11 | 0.810055E+10 | 0.00 | 0.223085E+11 | 0.00 | 0.00 | 0.148013E+11 | 0.426676E+11 | 0.00 |
December | 0.466517E+11 | 0.176966E+11 | 0.146742E+12 | 0.544784E+11 | 0.440514E+11 | 0.633802E+10 | 0.00 | 0.150284E+11 | 0.00 | 0.00 | 0.211844E+11 | 0.458635E+11 | 0.00 |
Annual Sum or Average | 0.542813E+12 | 0.174356E+12 | 0.172814E+13 | 0.641451E+12 | 0.590934E+12 | 0.106318E+12 | 0.00 | 0.992668E+12 | 0.00 | 0.00 | 0.150251E+12 | 0.496905E+12 | 0.00 |
Minimum of Months | 0.419438E+11 | 0.115914E+11 | 0.132565E+12 | 0.492071E+11 | 0.391724E+11 | 0.627358E+10 | 0.00 | 0.144805E+11 | 0.00 | 0.00 | 0.642407E+10 | 0.385005E+11 | 0.00 |
Maximum of Months | 0.466517E+11 | 0.176966E+11 | 0.146800E+12 | 0.544810E+11 | 0.595319E+11 | 0.106642E+11 | 0.00 | 0.203482E+12 | 0.00 | 0.00 | 0.211844E+11 | 0.458635E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.110802E+12 | 0.00 | 0.124562E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.906586E+11 | 0.00 | 0.110208E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.905035E+11 | 0.00 | 0.112931E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.666103E+11 | 0.00 | 0.985533E+11 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.386239E+11 | 0.00 | 0.888326E+11 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.874679E+10 | 0.00 | 0.731055E+11 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 73145520.35 | 0.00 | 0.668664E+11 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.162448E+09 | 0.00 | 0.677113E+11 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.648518E+10 | 0.00 | 0.724337E+11 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.651279E+11 | 0.00 | 0.902979E+11 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.919359E+11 | 0.00 | 0.103843E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.116990E+12 | 0.00 | 0.121788E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.686719E+12 | 0.00 | 0.113113E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 73145520.35 | 0.00 | 0.668664E+11 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.116990E+12 | 0.00 | 0.124562E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 45424.10 | 02-JAN-20:10 | 11096.45 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 39153.57 | 02-JAN-07:19 | 29003.85 | 09-JAN-22:10 | 4171.67 | 09-JAN-10:30 | 0.00 | 01-JAN-00:10 |
February | 45424.10 | 01-FEB-20:10 | 11096.45 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 39153.57 | 01-FEB-07:19 | 32777.62 | 14-FEB-22:10 | 4162.94 | 04-FEB-16:10 | 0.00 | 01-FEB-00:10 |
March | 45424.10 | 01-MAR-20:10 | 11096.45 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 39153.57 | 13-MAR-06:19 | 33476.02 | 13-MAR-21:10 | 4133.82 | 04-MAR-10:30 | 0.00 | 01-MAR-00:10 |
April | 45424.10 | 03-APR-19:10 | 11096.45 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 39152.05 | 05-APR-06:19 | 37933.97 | 13-APR-21:10 | 4119.52 | 23-APR-08:09 | 0.00 | 01-APR-00:10 |
May | 45424.10 | 01-MAY-19:10 | 11096.45 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 39152.77 | 22-MAY-06:19 | 38499.92 | 19-MAY-21:00 | 4371.18 | 21-MAY-18:10 | 0.00 | 01-MAY-00:10 |
June | 45424.10 | 01-JUN-19:10 | 11096.45 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 39152.27 | 08-JUN-06:19 | 44439.85 | 23-JUN-21:10 | 5292.19 | 28-JUN-18:19 | 0.00 | 01-JUN-00:10 |
July | 45424.10 | 03-JUL-19:19 | 11096.45 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 39152.36 | 28-JUL-06:19 | 46539.67 | 21-JUL-21:10 | 5142.21 | 20-JUL-20:19 | 0.00 | 01-JUL-00:10 |
August | 45424.10 | 01-AUG-19:10 | 11096.45 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 39152.17 | 23-AUG-06:19 | 48094.33 | 18-AUG-21:10 | 5174.77 | 16-AUG-18:10 | 0.00 | 01-AUG-00:10 |
September | 45424.10 | 01-SEP-19:10 | 11096.45 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 39153.46 | 27-SEP-06:19 | 45555.41 | 13-SEP-21:10 | 4896.70 | 28-SEP-18:10 | 0.00 | 01-SEP-00:10 |
October | 45424.10 | 02-OCT-19:10 | 11096.45 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 39153.57 | 10-OCT-06:19 | 45259.00 | 05-OCT-21:10 | 4583.98 | 11-OCT-16:19 | 0.00 | 01-OCT-00:10 |
November | 45424.10 | 01-NOV-19:10 | 11096.45 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 39153.57 | 01-NOV-06:19 | 36242.38 | 02-NOV-21:10 | 4159.25 | 27-NOV-16:30 | 0.00 | 01-NOV-00:10 |
December | 45424.10 | 01-DEC-20:10 | 11096.45 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 39153.57 | 01-DEC-07:19 | 30349.45 | 01-DEC-22:10 | 4168.41 | 05-DEC-16:19 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 45424.10 | 11096.45 | 88863.15 | 39152.05 | 29003.85 | 4119.52 | 0.00 | |||||||
Maximum of Months | 45424.10 | 11096.45 | 88863.15 | 39153.57 | 48094.33 | 5292.19 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 37627.70 | 01-JAN-14:09 | 0.00 | 0.00 | 9938.94 | 01-JAN-00:10 | 39484.05 | 03-JAN-19:00 | 0.00 |
February | 68823.18 | 14-FEB-16:10 | 0.00 | 0.00 | 9938.94 | 01-FEB-00:10 | 39313.32 | 27-FEB-19:10 | 0.00 |
March | 71667.83 | 08-MAR-16:10 | 0.00 | 0.00 | 9938.94 | 01-MAR-00:10 | 40272.39 | 31-MAR-18:49 | 0.00 |
April | 87890.50 | 13-APR-18:10 | 0.00 | 0.00 | 9938.94 | 01-APR-04:00 | 41275.75 | 27-APR-18:40 | 0.00 |
May | 107570.99 | 19-MAY-18:10 | 0.00 | 0.00 | 9938.94 | 01-MAY-21:10 | 42554.72 | 31-MAY-20:00 | 0.00 |
June | 156194.44 | 28-JUN-15:20 | 0.00 | 0.00 | 9938.94 | 03-JUN-12:09 | 43379.47 | 30-JUN-20:30 | 0.00 |
July | 153237.25 | 21-JUL-18:19 | 0.00 | 0.00 | 9938.94 | 02-JUL-09:20 | 42711.79 | 28-JUL-20:49 | 0.00 |
August | 142124.45 | 01-AUG-15:09 | 0.00 | 0.00 | 9938.94 | 01-AUG-08:30 | 43027.37 | 04-AUG-20:49 | 0.00 |
September | 115425.30 | 02-SEP-15:09 | 0.00 | 0.00 | 9938.94 | 01-SEP-09:39 | 43743.96 | 06-SEP-20:40 | 0.00 |
October | 103974.74 | 06-OCT-15:09 | 0.00 | 0.00 | 9938.94 | 01-OCT-12:20 | 43217.74 | 02-OCT-17:49 | 0.00 |
November | 46956.65 | 02-NOV-15:09 | 0.00 | 0.00 | 9938.94 | 01-NOV-05:19 | 42168.79 | 01-NOV-18:19 | 0.00 |
December | 25381.49 | 31-DEC-14:09 | 0.00 | 0.00 | 9938.94 | 01-DEC-00:10 | 40585.57 | 01-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 25381.49 | 0.00 | 0.00 | 9938.94 | 39313.32 | 0.00 | |||
Maximum of Months | 156194.44 | 0.00 | 0.00 | 9938.94 | 43743.96 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 263056.02 | 05-JAN-20:10 | 45424.10 | 87982.85 | 11096.45 | 31569.36 | 24805.23 | 3631.42 | 0.00 | 8699.53 | 0.00 |
February | 264295.88 | 15-FEB-20:10 | 45424.10 | 87982.85 | 11096.45 | 31569.36 | 27328.24 | 3916.68 | 0.00 | 15459.64 | 0.00 |
March | 275488.66 | 13-MAR-19:19 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 26328.03 | 3661.73 | 0.00 | 29258.44 | 0.00 |
April | 320611.81 | 28-APR-18:49 | 40391.24 | 78653.57 | 11096.45 | 31363.90 | 29815.65 | 3933.18 | 0.00 | 78164.37 | 0.00 |
May | 360759.35 | 19-MAY-19:10 | 45424.10 | 87982.85 | 11096.45 | 31569.36 | 33352.15 | 4069.93 | 0.00 | 95711.84 | 0.00 |
June | 388062.03 | 27-JUN-19:30 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 37824.65 | 4075.26 | 0.00 | 119549.41 | 0.00 |
July | 396477.46 | 21-JUL-19:30 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 39722.90 | 4130.28 | 0.00 | 126741.49 | 0.00 |
August | 386082.86 | 18-AUG-19:10 | 45424.10 | 87982.85 | 11096.45 | 31569.36 | 39148.65 | 4517.89 | 0.00 | 115792.14 | 0.00 |
September | 358617.81 | 13-SEP-19:19 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 35513.08 | 4761.66 | 0.00 | 90978.77 | 0.00 |
October | 314818.67 | 10-OCT-19:19 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 31902.26 | 4053.69 | 0.00 | 60277.73 | 0.00 |
November | 275947.20 | 01-NOV-19:19 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 28969.97 | 3646.62 | 0.00 | 14620.37 | 0.00 |
December | 262775.96 | 18-DEC-20:10 | 45424.10 | 87982.85 | 11096.45 | 31569.36 | 25078.19 | 3657.04 | 0.00 | 7377.62 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 262775.96 | 40391.24 | 78653.57 | 11096.45 | 31363.90 | 24805.23 | 3631.42 | 0.00 | 7377.62 | 0.00 | |
Maximum of Months | 396477.46 | 45424.10 | 87982.85 | 11096.45 | 31573.56 | 39722.90 | 4761.66 | 0.00 | 126741.49 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 179480.05 | 28-JAN-18:00 | 0.00 | 124704.37 | 27-JAN-21:40 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 177831.31 | 04-FEB-16:10 | 0.00 | 120582.50 | 09-FEB-18:49 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 162624.12 | 17-MAR-04:00 | 0.00 | 109252.01 | 01-MAR-19:10 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 178020.98 | 24-APR-06:49 | 0.00 | 95973.97 | 01-APR-16:49 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 158070.26 | 04-MAY-02:20 | 0.00 | 80035.08 | 01-MAY-20:49 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 151196.60 | 09-JUN-04:00 | 0.00 | 62363.94 | 01-JUN-22:10 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 6455.42 | 08-JUL-18:10 | 0.00 | 49115.04 | 01-JUL-16:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 29666.47 | 31-AUG-05:00 | 0.00 | 49446.15 | 31-AUG-22:19 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 92713.69 | 09-SEP-05:00 | 0.00 | 60396.51 | 30-SEP-20:19 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 180660.53 | 23-OCT-06:19 | 0.00 | 81581.62 | 31-OCT-20:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 178181.83 | 02-NOV-06:00 | 0.00 | 103488.25 | 30-NOV-19:19 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 187635.00 | 11-DEC-18:49 | 0.00 | 123258.07 | 28-DEC-21:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 6455.42 | 0.00 | 49115.04 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 187635.00 | 0.00 | 124704.37 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.76 | 1.17 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.74 | 1.83 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.78 | 1.50 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.78 | 1.67 | 21.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.78 | 1.33 | 21.78 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.50 | 21.77 | 7.50 | 21.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.78 | 1.83 | 21.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.84 | 0.17 | 21.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.74 | 3.17 | 21.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.77 | 2.17 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.75 | 1.17 | 21.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.67 | 21.75 | 6.67 | 21.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.84 | 3.17 | 21.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.76 | 0.50 | 21.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.77 | 4.33 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.76 | 3.50 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.77 | 2.17 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.72 | 2.17 | 21.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 13.17 | 21.76 | 13.17 | 21.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.77 | 4.33 | 21.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.79 | 0.17 | 21.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.77 | 0.50 | 21.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.82 | 1.33 | 21.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.81 | 1.50 | 21.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.74 | 0.83 | 21.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.00 | 21.78 | 5.00 | 21.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.82 | 1.50 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.93 | 0.50 | 21.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 22.19 | 2.67 | 22.19 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 22.34 | 9.00 | 22.34 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 22.23 | 9.33 | 22.23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 22.21 | 8.67 | 22.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 22.17 | 5.17 | 22.17 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 22.00 | 0.50 | 22.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 35.83 | 22.23 | 35.83 | 22.23 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 22.34 | 9.33 | 22.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.76 | 2.50 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.77 | 3.50 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.79 | 3.00 | 21.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.78 | 2.50 | 21.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.79 | 1.17 | 21.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.67 | 21.78 | 12.67 | 21.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.79 | 3.50 | 21.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.86 | 0.17 | 21.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.79 | 5.17 | 21.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.79 | 4.33 | 21.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.78 | 2.00 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.00 | 21.79 | 12.00 | 21.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.86 | 5.17 | 21.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 22.00 | 1.50 | 22.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.94 | 1.67 | 21.94 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.89 | 0.83 | 21.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.76 | 0.17 | 21.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.68 | 0.67 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.71 | 2.33 | 21.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.82 | 3.33 | 21.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.94 | 5.17 | 21.94 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 22.06 | 1.67 | 22.06 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 22.11 | 1.67 | 22.11 |
Annual Sum or Average | 0.00 | 0.00 | 19.17 | 21.91 | 19.17 | 21.91 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 22.11 | 5.17 | 22.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 23.68 | 0.00 | 23.68 | 0.00 | 23.68 |
February | 672.00 | 23.24 | 0.00 | 23.24 | 0.00 | 23.24 |
March | 744.00 | 22.72 | 0.00 | 22.72 | 0.00 | 22.72 |
April | 720.00 | 22.65 | 0.00 | 22.65 | 0.00 | 22.65 |
May | 744.00 | 22.76 | 0.00 | 22.76 | 0.00 | 22.76 |
June | 705.83 | 23.10 | 22.83 | 23.11 | 22.83 | 23.11 |
July | 544.00 | 23.46 | 376.17 | 23.54 | 312.83 | 23.56 |
August | 286.17 | 23.76 | 385.67 | 23.85 | 204.50 | 23.85 |
September | 147.50 | 23.83 | 225.17 | 23.90 | 60.33 | 23.91 |
October | 451.33 | 23.91 | 49.00 | 23.92 | 0.00 | 23.92 |
November | 589.83 | 23.93 | 0.00 | 23.93 | 0.00 | 23.93 |
December | 703.67 | 23.91 | 0.00 | 23.91 | 0.00 | 23.91 |
Annual Sum or Average | 7052.33 | 23.32 | 1058.83 | 23.39 | 600.50 | 23.41 |
Minimum of Months | 147.50 | 22.65 | 0.00 | 22.65 | 0.00 | 22.65 |
Maximum of Months | 744.00 | 23.93 | 385.67 | 23.93 | 312.83 | 23.93 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 601.67 | 21.57 | 133.17 | 21.74 | 65.00 | 21.68 |
February | 525.67 | 21.70 | 74.33 | 21.89 | 19.33 | 21.86 |
March | 620.00 | 21.84 | 40.33 | 21.95 | 4.17 | 21.95 |
April | 570.33 | 22.31 | 8.83 | 22.33 | 0.83 | 22.33 |
May | 579.00 | 22.40 | 30.50 | 22.47 | 2.17 | 22.46 |
June | 348.33 | 22.67 | 225.67 | 23.15 | 15.17 | 23.16 |
July | 228.00 | 23.34 | 646.17 | 23.62 | 207.67 | 23.57 |
August | 196.00 | 23.31 | 598.00 | 23.69 | 136.17 | 23.66 |
September | 241.00 | 22.85 | 418.50 | 23.49 | 43.17 | 23.47 |
October | 401.67 | 22.34 | 216.33 | 22.89 | 6.33 | 22.87 |
November | 536.67 | 21.95 | 91.67 | 22.25 | 0.00 | 22.25 |
December | 578.83 | 21.57 | 126.33 | 21.72 | 66.00 | 21.66 |
Annual Sum or Average | 5427.17 | 22.14 | 2609.83 | 22.63 | 566.00 | 22.64 |
Minimum of Months | 196.00 | 21.57 | 8.83 | 21.72 | 0.00 | 21.66 |
Maximum of Months | 620.00 | 23.34 | 646.17 | 23.69 | 207.67 | 23.66 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.88 | 0.00 | 22.88 | 0.00 | 22.88 |
February | 667.50 | 23.02 | 0.00 | 23.02 | 0.00 | 23.02 |
March | 726.00 | 23.19 | 0.00 | 23.19 | 0.00 | 23.19 |
April | 676.67 | 23.46 | 0.00 | 23.46 | 0.00 | 23.46 |
May | 505.00 | 23.43 | 44.33 | 23.47 | 1.50 | 23.47 |
June | 190.50 | 23.46 | 207.33 | 23.72 | 24.83 | 23.73 |
July | 297.83 | 23.91 | 695.67 | 23.91 | 297.83 | 23.91 |
August | 198.67 | 23.93 | 686.83 | 23.93 | 198.67 | 23.93 |
September | 92.50 | 23.76 | 408.33 | 23.90 | 69.67 | 23.90 |
October | 446.50 | 23.45 | 90.00 | 23.53 | 3.50 | 23.53 |
November | 684.17 | 23.28 | 0.00 | 23.28 | 0.00 | 23.28 |
December | 744.00 | 22.91 | 0.00 | 22.91 | 0.00 | 22.91 |
Annual Sum or Average | 5973.33 | 23.26 | 2132.50 | 23.43 | 596.00 | 23.47 |
Minimum of Months | 92.50 | 22.88 | 0.00 | 22.88 | 0.00 | 22.88 |
Maximum of Months | 744.00 | 23.93 | 695.67 | 23.93 | 297.83 | 23.93 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.37 | 14.33 | 21.36 | 14.33 | 21.36 |
February | 672.00 | 21.52 | 18.17 | 21.51 | 18.17 | 21.49 |
March | 744.00 | 22.02 | 0.00 | 22.02 | 0.00 | 22.02 |
April | 720.00 | 22.65 | 0.00 | 22.65 | 0.00 | 22.65 |
May | 723.00 | 23.16 | 0.00 | 23.16 | 0.00 | 23.16 |
June | 404.33 | 23.59 | 57.00 | 23.64 | 3.67 | 23.64 |
July | 131.50 | 23.94 | 571.00 | 23.95 | 129.00 | 23.95 |
August | 88.33 | 23.83 | 424.50 | 23.91 | 77.67 | 23.91 |
September | 422.00 | 23.53 | 74.17 | 23.57 | 28.67 | 23.58 |
October | 692.50 | 22.79 | 5.50 | 22.80 | 0.00 | 22.80 |
November | 720.00 | 22.00 | 0.00 | 22.00 | 0.00 | 22.00 |
December | 744.00 | 21.31 | 58.00 | 21.29 | 58.00 | 21.27 |
Annual Sum or Average | 6805.67 | 22.33 | 1222.67 | 22.54 | 329.50 | 22.57 |
Minimum of Months | 88.33 | 21.31 | 0.00 | 21.29 | 0.00 | 21.27 |
Maximum of Months | 744.00 | 23.94 | 571.00 | 23.95 | 129.00 | 23.95 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.21 | 15.83 | 21.20 | 15.83 | 21.20 |
February | 672.00 | 21.35 | 19.67 | 21.34 | 19.67 | 21.33 |
March | 744.00 | 21.81 | 0.00 | 21.81 | 0.00 | 21.81 |
April | 720.00 | 22.46 | 0.00 | 22.46 | 0.00 | 22.46 |
May | 744.00 | 22.99 | 0.00 | 22.99 | 0.00 | 22.99 |
June | 456.00 | 23.48 | 42.00 | 23.52 | 4.83 | 23.53 |
July | 151.83 | 23.87 | 564.83 | 23.91 | 151.33 | 23.90 |
August | 118.00 | 23.73 | 363.33 | 23.85 | 95.17 | 23.84 |
September | 534.83 | 23.44 | 48.17 | 23.46 | 34.33 | 23.46 |
October | 732.67 | 22.65 | 3.17 | 22.66 | 0.00 | 22.66 |
November | 720.00 | 21.80 | 0.00 | 21.80 | 0.00 | 21.80 |
December | 744.00 | 21.16 | 82.67 | 21.14 | 82.67 | 21.13 |
Annual Sum or Average | 7081.33 | 22.22 | 1139.67 | 22.41 | 403.83 | 22.44 |
Minimum of Months | 118.00 | 21.16 | 0.00 | 21.14 | 0.00 | 21.13 |
Maximum of Months | 744.00 | 23.87 | 564.83 | 23.91 | 151.33 | 23.90 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 209.67 | 23.14 | 588.67 | 23.50 | 141.33 | 23.58 |
February | 194.17 | 23.22 | 551.50 | 23.51 | 137.00 | 23.59 |
March | 216.17 | 23.41 | 629.33 | 23.57 | 165.67 | 23.64 |
April | 201.50 | 23.56 | 617.00 | 23.61 | 164.17 | 23.67 |
May | 254.83 | 23.83 | 673.00 | 23.63 | 236.33 | 23.70 |
June | 312.83 | 23.97 | 694.83 | 23.63 | 312.67 | 23.71 |
July | 440.83 | 23.82 | 744.00 | 23.57 | 440.83 | 23.64 |
August | 412.17 | 23.85 | 744.00 | 23.56 | 412.17 | 23.64 |
September | 336.00 | 23.93 | 698.50 | 23.57 | 336.00 | 23.66 |
October | 243.67 | 23.73 | 655.50 | 23.56 | 217.67 | 23.65 |
November | 207.83 | 23.39 | 594.17 | 23.56 | 157.67 | 23.63 |
December | 211.50 | 23.08 | 589.50 | 23.50 | 137.33 | 23.57 |
Annual Sum or Average | 3241.17 | 23.64 | 7780.00 | 23.57 | 2858.83 | 23.64 |
Minimum of Months | 194.17 | 23.08 | 551.50 | 23.50 | 137.00 | 23.57 |
Maximum of Months | 440.83 | 23.97 | 744.00 | 23.63 | 440.83 | 23.71 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 466.50 | 22.90 | 138.00 | 23.15 | 0.00 | 23.15 |
February | 368.83 | 23.03 | 140.33 | 23.30 | 0.00 | 23.30 |
March | 390.83 | 23.04 | 116.00 | 23.26 | 0.00 | 23.26 |
April | 293.33 | 23.26 | 111.17 | 23.46 | 0.00 | 23.46 |
May | 248.83 | 23.12 | 253.17 | 23.50 | 22.17 | 23.50 |
June | 110.33 | 23.34 | 487.33 | 23.78 | 56.83 | 23.78 |
July | 425.83 | 23.89 | 744.00 | 23.89 | 425.83 | 23.89 |
August | 322.67 | 23.89 | 743.00 | 23.90 | 322.67 | 23.90 |
September | 135.67 | 23.79 | 668.67 | 23.91 | 126.17 | 23.91 |
October | 161.83 | 23.12 | 383.00 | 23.72 | 19.33 | 23.73 |
November | 266.17 | 23.05 | 189.17 | 23.44 | 0.00 | 23.44 |
December | 458.00 | 23.00 | 155.50 | 23.26 | 0.00 | 23.26 |
Annual Sum or Average | 3648.83 | 23.26 | 4129.33 | 23.61 | 973.00 | 23.64 |
Minimum of Months | 110.33 | 22.90 | 111.17 | 23.15 | 0.00 | 23.15 |
Maximum of Months | 466.50 | 23.89 | 744.00 | 23.91 | 425.83 | 23.91 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 560.33 | 23.40 | 0.00 | 23.40 | 0.00 | 23.40 |
February | 423.00 | 23.43 | 0.00 | 23.43 | 0.00 | 23.43 |
March | 461.67 | 23.47 | 0.00 | 23.47 | 0.00 | 23.47 |
April | 468.67 | 23.59 | 0.67 | 23.59 | 0.00 | 23.59 |
May | 313.50 | 23.49 | 143.83 | 23.63 | 8.00 | 23.63 |
June | 106.17 | 23.58 | 355.50 | 23.86 | 44.67 | 23.87 |
July | 393.50 | 23.92 | 728.67 | 23.91 | 393.50 | 23.92 |
August | 294.83 | 23.94 | 742.50 | 23.94 | 294.83 | 23.94 |
September | 110.17 | 23.92 | 613.00 | 23.95 | 109.00 | 23.95 |
October | 147.00 | 23.52 | 200.50 | 23.78 | 12.83 | 23.79 |
November | 299.67 | 23.55 | 4.17 | 23.55 | 0.00 | 23.55 |
December | 608.50 | 23.52 | 0.00 | 23.52 | 0.00 | 23.52 |
Annual Sum or Average | 4187.00 | 23.58 | 2788.83 | 23.72 | 862.83 | 23.74 |
Minimum of Months | 106.17 | 23.40 | 0.00 | 23.40 | 0.00 | 23.40 |
Maximum of Months | 608.50 | 23.94 | 742.50 | 23.95 | 393.50 | 23.95 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 728.83 | 21.34 | 100.33 | 21.27 | 100.33 | 21.22 |
February | 650.00 | 21.42 | 46.33 | 21.38 | 45.67 | 21.35 |
March | 723.67 | 21.51 | 4.50 | 21.50 | 4.33 | 21.50 |
April | 690.50 | 21.60 | 0.00 | 21.60 | 0.00 | 21.60 |
May | 689.17 | 21.56 | 5.33 | 21.57 | 0.50 | 21.57 |
June | 608.17 | 21.44 | 33.17 | 21.54 | 0.33 | 21.54 |
July | 588.67 | 21.34 | 59.17 | 21.52 | 2.50 | 21.53 |
August | 581.00 | 21.31 | 67.67 | 21.52 | 1.67 | 21.52 |
September | 573.00 | 21.33 | 57.00 | 21.51 | 1.50 | 21.51 |
October | 665.50 | 21.46 | 31.67 | 21.51 | 8.83 | 21.50 |
November | 689.33 | 21.48 | 6.83 | 21.49 | 4.50 | 21.48 |
December | 736.50 | 21.37 | 158.00 | 21.28 | 158.00 | 21.22 |
Annual Sum or Average | 7924.33 | 21.43 | 570.00 | 21.47 | 328.17 | 21.44 |
Minimum of Months | 573.00 | 21.31 | 0.00 | 21.27 | 0.00 | 21.22 |
Maximum of Months | 736.50 | 21.60 | 158.00 | 21.60 | 158.00 | 21.60 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.99 | 333.00 | 20.90 | 333.00 | 20.85 |
February | 669.00 | 21.15 | 143.67 | 21.06 | 143.67 | 21.00 |
March | 721.17 | 21.44 | 25.33 | 21.47 | 17.33 | 21.46 |
April | 664.83 | 21.84 | 27.00 | 22.02 | 1.50 | 22.03 |
May | 661.67 | 21.89 | 25.33 | 22.03 | 5.00 | 22.06 |
June | 545.17 | 21.64 | 74.17 | 21.96 | 4.17 | 21.99 |
July | 547.17 | 21.73 | 144.67 | 22.18 | 64.00 | 22.34 |
August | 535.00 | 21.69 | 146.17 | 22.18 | 48.33 | 22.30 |
September | 534.00 | 21.76 | 67.17 | 21.98 | 12.17 | 22.01 |
October | 654.83 | 21.64 | 52.33 | 21.80 | 19.67 | 21.78 |
November | 717.17 | 21.26 | 49.67 | 21.24 | 48.67 | 21.22 |
December | 744.00 | 20.93 | 444.00 | 20.84 | 444.00 | 20.80 |
Annual Sum or Average | 7738.00 | 21.47 | 1532.50 | 21.55 | 1141.50 | 21.50 |
Minimum of Months | 534.00 | 20.93 | 25.33 | 20.84 | 1.50 | 20.80 |
Maximum of Months | 744.00 | 21.89 | 444.00 | 22.18 | 444.00 | 22.34 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.07 | 55.83 | 21.04 | 55.83 | 21.01 |
February | 672.00 | 21.15 | 28.00 | 21.13 | 28.00 | 21.11 |
March | 744.00 | 21.37 | 0.83 | 21.37 | 0.83 | 21.37 |
April | 720.00 | 21.75 | 0.00 | 21.75 | 0.00 | 21.75 |
May | 743.33 | 21.90 | 0.00 | 21.90 | 0.00 | 21.90 |
June | 711.67 | 21.97 | 0.17 | 21.97 | 0.17 | 21.97 |
July | 727.83 | 22.03 | 43.17 | 22.11 | 42.33 | 22.18 |
August | 726.67 | 22.02 | 29.00 | 22.07 | 25.67 | 22.11 |
September | 719.50 | 22.04 | 4.00 | 22.05 | 4.00 | 22.05 |
October | 744.00 | 21.63 | 0.67 | 21.63 | 0.67 | 21.63 |
November | 720.00 | 21.21 | 8.17 | 21.21 | 8.17 | 21.20 |
December | 744.00 | 21.01 | 181.00 | 20.96 | 181.00 | 20.93 |
Annual Sum or Average | 8717.00 | 21.60 | 350.83 | 21.59 | 346.67 | 21.57 |
Minimum of Months | 672.00 | 21.01 | 0.00 | 20.96 | 0.00 | 20.93 |
Maximum of Months | 744.00 | 22.04 | 181.00 | 22.11 | 181.00 | 22.18 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.43 | 114.33 | 21.34 | 114.33 | 21.28 |
February | 671.33 | 21.53 | 46.67 | 21.49 | 46.67 | 21.46 |
March | 738.67 | 21.62 | 4.83 | 21.62 | 4.83 | 21.62 |
April | 690.83 | 21.67 | 0.00 | 21.67 | 0.00 | 21.67 |
May | 663.00 | 21.55 | 3.00 | 21.56 | 0.00 | 21.56 |
June | 556.67 | 21.30 | 23.00 | 21.38 | 0.00 | 21.38 |
July | 538.50 | 21.17 | 53.67 | 21.37 | 0.83 | 21.37 |
August | 543.00 | 21.18 | 75.67 | 21.45 | 0.00 | 21.45 |
September | 554.17 | 21.28 | 31.67 | 21.39 | 0.33 | 21.39 |
October | 647.00 | 21.45 | 15.67 | 21.47 | 7.50 | 21.46 |
November | 713.67 | 21.59 | 4.67 | 21.59 | 4.67 | 21.59 |
December | 744.00 | 21.45 | 157.67 | 21.36 | 157.67 | 21.29 |
Annual Sum or Average | 7804.83 | 21.45 | 530.83 | 21.47 | 336.83 | 21.45 |
Minimum of Months | 538.50 | 21.17 | 0.00 | 21.34 | 0.00 | 21.28 |
Maximum of Months | 744.00 | 21.67 | 157.67 | 21.67 | 157.67 | 21.67 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.98 | 322.50 | 20.93 | 322.50 | 20.90 |
February | 672.00 | 21.16 | 152.50 | 21.10 | 152.50 | 21.06 |
March | 743.83 | 21.62 | 12.50 | 21.61 | 12.50 | 21.60 |
April | 705.00 | 22.02 | 2.00 | 22.03 | 0.00 | 22.03 |
May | 635.50 | 21.92 | 30.00 | 22.08 | 5.33 | 22.11 |
June | 507.17 | 21.84 | 92.00 | 22.41 | 33.00 | 22.69 |
July | 510.00 | 21.96 | 160.50 | 22.66 | 75.00 | 23.00 |
August | 491.83 | 21.90 | 163.00 | 22.64 | 66.67 | 22.95 |
September | 494.83 | 21.77 | 64.67 | 22.13 | 17.00 | 22.22 |
October | 692.17 | 21.81 | 21.00 | 21.83 | 15.00 | 21.83 |
November | 719.83 | 21.28 | 55.33 | 21.26 | 55.33 | 21.24 |
December | 744.00 | 20.89 | 473.50 | 20.85 | 473.50 | 20.83 |
Annual Sum or Average | 7660.17 | 21.56 | 1549.50 | 21.67 | 1228.33 | 21.67 |
Minimum of Months | 491.83 | 20.89 | 2.00 | 20.85 | 0.00 | 20.83 |
Maximum of Months | 744.00 | 22.02 | 473.50 | 22.66 | 473.50 | 23.00 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.46 | 3.83 | 21.46 | 3.83 | 21.45 |
February | 672.00 | 21.57 | 5.17 | 21.57 | 5.17 | 21.57 |
March | 744.00 | 22.07 | 0.00 | 22.07 | 0.00 | 22.07 |
April | 720.00 | 22.80 | 0.00 | 22.80 | 0.00 | 22.80 |
May | 734.00 | 23.19 | 0.00 | 23.19 | 0.00 | 23.19 |
June | 482.17 | 23.57 | 71.33 | 23.61 | 35.17 | 23.62 |
July | 373.17 | 23.93 | 616.83 | 23.94 | 371.50 | 23.94 |
August | 268.83 | 23.92 | 528.17 | 23.93 | 268.83 | 23.93 |
September | 278.50 | 23.73 | 163.83 | 23.77 | 84.83 | 23.76 |
October | 608.00 | 23.03 | 25.00 | 23.06 | 10.83 | 23.07 |
November | 720.00 | 22.11 | 0.00 | 22.11 | 0.00 | 22.11 |
December | 744.00 | 21.33 | 16.00 | 21.32 | 16.00 | 21.32 |
Annual Sum or Average | 7088.67 | 22.49 | 1430.17 | 22.72 | 796.17 | 22.82 |
Minimum of Months | 268.83 | 21.33 | 0.00 | 21.32 | 0.00 | 21.32 |
Maximum of Months | 744.00 | 23.93 | 616.83 | 23.94 | 371.50 | 23.94 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 726.33 | 21.25 | 280.17 | 21.14 | 280.17 | 21.08 |
February | 645.00 | 21.33 | 130.00 | 21.26 | 127.33 | 21.20 |
March | 718.67 | 21.44 | 39.50 | 21.41 | 38.00 | 21.39 |
April | 677.67 | 21.54 | 11.17 | 21.54 | 10.33 | 21.53 |
May | 668.67 | 21.48 | 23.17 | 21.52 | 7.67 | 21.52 |
June | 582.50 | 21.38 | 55.17 | 21.54 | 0.83 | 21.54 |
July | 569.33 | 21.30 | 97.83 | 21.58 | 9.50 | 21.58 |
August | 566.17 | 21.27 | 103.50 | 21.57 | 9.17 | 21.57 |
September | 564.33 | 21.29 | 87.00 | 21.53 | 11.50 | 21.53 |
October | 656.83 | 21.40 | 65.83 | 21.45 | 32.67 | 21.42 |
November | 685.50 | 21.41 | 84.67 | 21.36 | 82.17 | 21.32 |
December | 734.50 | 21.27 | 328.33 | 21.15 | 328.33 | 21.08 |
Annual Sum or Average | 7795.50 | 21.36 | 1306.33 | 21.40 | 937.67 | 21.35 |
Minimum of Months | 564.33 | 21.25 | 11.17 | 21.14 | 0.83 | 21.08 |
Maximum of Months | 734.50 | 21.54 | 328.33 | 21.58 | 328.33 | 21.58 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.86 | 577.33 | 20.80 | 577.33 | 20.78 |
February | 667.67 | 21.05 | 301.50 | 20.95 | 301.17 | 20.89 |
March | 715.17 | 21.36 | 122.17 | 21.38 | 107.17 | 21.32 |
April | 642.83 | 21.80 | 50.67 | 22.02 | 21.50 | 22.05 |
May | 641.00 | 21.83 | 45.67 | 22.03 | 15.17 | 22.08 |
June | 520.83 | 21.59 | 96.33 | 21.99 | 7.17 | 22.04 |
July | 536.83 | 21.70 | 174.33 | 22.18 | 73.00 | 22.34 |
August | 524.67 | 21.65 | 171.00 | 22.17 | 55.00 | 22.28 |
September | 525.83 | 21.69 | 95.50 | 21.97 | 22.67 | 21.98 |
October | 644.33 | 21.54 | 118.17 | 21.69 | 77.17 | 21.62 |
November | 717.17 | 21.15 | 244.50 | 21.08 | 243.50 | 21.03 |
December | 744.00 | 20.80 | 608.83 | 20.75 | 608.83 | 20.73 |
Annual Sum or Average | 7624.33 | 21.38 | 2606.00 | 21.44 | 2109.67 | 21.37 |
Minimum of Months | 520.83 | 20.80 | 45.67 | 20.75 | 7.17 | 20.73 |
Maximum of Months | 744.00 | 21.83 | 608.83 | 22.18 | 608.83 | 22.34 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 654.67 | 21.36 | 87.33 | 21.45 | 40.67 | 21.41 |
February | 580.67 | 21.37 | 49.50 | 21.48 | 12.33 | 21.47 |
March | 668.50 | 21.44 | 9.33 | 21.46 | 1.00 | 21.46 |
April | 676.33 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
May | 701.83 | 21.58 | 0.83 | 21.58 | 0.83 | 21.58 |
June | 634.83 | 21.50 | 0.67 | 21.50 | 0.67 | 21.50 |
July | 607.83 | 21.39 | 8.17 | 21.40 | 7.83 | 21.42 |
August | 591.33 | 21.32 | 55.33 | 21.49 | 4.33 | 21.49 |
September | 573.00 | 21.32 | 98.33 | 21.62 | 1.50 | 21.62 |
October | 613.83 | 21.36 | 90.33 | 21.60 | 3.67 | 21.59 |
November | 614.33 | 21.39 | 50.67 | 21.54 | 0.00 | 21.54 |
December | 634.00 | 21.30 | 63.17 | 21.37 | 33.50 | 21.35 |
Annual Sum or Average | 7551.17 | 21.41 | 513.67 | 21.50 | 106.33 | 21.50 |
Minimum of Months | 573.00 | 21.30 | 0.00 | 21.37 | 0.00 | 21.35 |
Maximum of Months | 701.83 | 21.58 | 98.33 | 21.62 | 40.67 | 21.62 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 486.00 | 23.48 | 0.00 | 23.48 | 0.00 | 23.48 |
February | 314.67 | 23.46 | 0.00 | 23.46 | 0.00 | 23.46 |
March | 192.17 | 23.52 | 28.00 | 23.58 | 0.00 | 23.58 |
April | 62.83 | 23.67 | 39.33 | 23.80 | 0.00 | 23.80 |
May | 34.33 | 23.79 | 373.67 | 23.97 | 9.50 | 23.97 |
June | 46.67 | 24.00 | 659.83 | 23.99 | 46.67 | 23.99 |
July | 409.83 | 24.00 | 744.00 | 24.00 | 409.83 | 24.00 |
August | 310.17 | 24.00 | 744.00 | 23.99 | 310.17 | 23.99 |
September | 113.67 | 23.99 | 709.50 | 23.98 | 113.67 | 23.98 |
October | 117.67 | 23.50 | 270.17 | 23.82 | 18.67 | 23.83 |
November | 301.17 | 23.49 | 28.83 | 23.54 | 0.00 | 23.54 |
December | 558.83 | 23.51 | 0.00 | 23.51 | 0.00 | 23.51 |
Annual Sum or Average | 2948.00 | 23.65 | 3597.33 | 23.84 | 908.50 | 23.86 |
Minimum of Months | 34.33 | 23.46 | 0.00 | 23.46 | 0.00 | 23.46 |
Maximum of Months | 558.83 | 24.00 | 744.00 | 24.00 | 409.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 238.00 | 23.45 | 0.00 | 23.45 | 0.00 | 23.45 |
February | 135.00 | 23.45 | 31.83 | 23.56 | 0.00 | 23.56 |
March | 26.50 | 23.55 | 66.50 | 23.87 | 0.00 | 23.87 |
April | 5.50 | 23.66 | 100.17 | 23.98 | 0.00 | 23.98 |
May | 12.00 | 23.89 | 419.33 | 23.99 | 8.17 | 23.99 |
June | 43.00 | 24.00 | 690.50 | 24.00 | 43.00 | 24.00 |
July | 396.83 | 24.00 | 744.00 | 24.00 | 396.83 | 24.00 |
August | 294.50 | 24.00 | 744.00 | 24.00 | 294.50 | 24.00 |
September | 106.33 | 23.99 | 720.00 | 23.99 | 106.33 | 23.99 |
October | 46.17 | 23.61 | 324.33 | 23.93 | 15.83 | 23.94 |
November | 126.33 | 23.50 | 63.83 | 23.66 | 0.00 | 23.66 |
December | 293.50 | 23.49 | 0.00 | 23.49 | 0.00 | 23.49 |
Annual Sum or Average | 1723.67 | 23.74 | 3904.50 | 23.92 | 864.67 | 23.93 |
Minimum of Months | 5.50 | 23.45 | 0.00 | 23.45 | 0.00 | 23.45 |
Maximum of Months | 396.83 | 24.00 | 744.00 | 24.00 | 396.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 482.33 | 23.96 | 641.33 | 23.94 | 472.33 | 23.96 |
February | 449.33 | 23.96 | 606.00 | 23.93 | 440.50 | 23.95 |
March | 503.33 | 23.99 | 711.83 | 23.94 | 503.33 | 23.95 |
April | 500.33 | 23.99 | 701.67 | 23.96 | 500.33 | 23.97 |
May | 535.50 | 23.99 | 739.00 | 23.97 | 535.50 | 23.98 |
June | 555.00 | 23.99 | 720.00 | 23.98 | 555.00 | 23.99 |
July | 666.33 | 23.99 | 744.00 | 23.99 | 666.33 | 23.99 |
August | 632.83 | 23.99 | 744.00 | 23.99 | 632.83 | 23.99 |
September | 556.67 | 23.99 | 720.00 | 23.98 | 556.67 | 23.98 |
October | 521.17 | 23.99 | 730.33 | 23.96 | 521.17 | 23.97 |
November | 482.17 | 23.99 | 666.33 | 23.94 | 481.17 | 23.96 |
December | 481.33 | 23.94 | 629.33 | 23.95 | 466.50 | 23.96 |
Annual Sum or Average | 6366.33 | 23.98 | 8353.83 | 23.96 | 6331.67 | 23.97 |
Minimum of Months | 449.33 | 23.94 | 606.00 | 23.93 | 440.50 | 23.95 |
Maximum of Months | 666.33 | 23.99 | 744.00 | 23.99 | 666.33 | 23.99 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.30 | 5.33 | 21.30 | 5.33 | 21.29 |
February | 672.00 | 21.48 | 6.33 | 21.47 | 6.33 | 21.47 |
March | 744.00 | 21.85 | 0.00 | 21.85 | 0.00 | 21.85 |
April | 718.83 | 22.63 | 0.00 | 22.63 | 0.00 | 22.63 |
May | 649.00 | 23.01 | 2.83 | 23.02 | 0.00 | 23.02 |
June | 307.67 | 23.34 | 137.83 | 23.53 | 13.33 | 23.54 |
July | 194.83 | 23.79 | 648.33 | 23.89 | 194.83 | 23.87 |
August | 144.83 | 23.72 | 576.33 | 23.87 | 129.83 | 23.86 |
September | 287.00 | 23.31 | 222.67 | 23.55 | 45.50 | 23.54 |
October | 622.50 | 22.62 | 35.67 | 22.69 | 0.00 | 22.69 |
November | 720.00 | 21.73 | 0.00 | 21.73 | 0.00 | 21.73 |
December | 744.00 | 21.26 | 52.83 | 21.24 | 52.83 | 21.22 |
Annual Sum or Average | 6548.67 | 22.18 | 1688.17 | 22.51 | 448.00 | 22.55 |
Minimum of Months | 144.83 | 21.26 | 0.00 | 21.24 | 0.00 | 21.22 |
Maximum of Months | 744.00 | 23.79 | 648.33 | 23.89 | 194.83 | 23.87 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.67747 | 22.19495 | 0.12371 | 5.43679 |
February | 672.00000 | 23.23503 | 23.80079 | 0.02147 | 5.17524 |
March | 744.00000 | 22.72233 | 22.70656 | -0.1130 | 5.42552 |
April | 720.00000 | 22.64786 | 19.39124 | -0.1525 | 5.63593 |
May | 744.00000 | 22.75515 | 28.15027 | -1.1097 | 31.18983 |
June | 720.00000 | 23.11514 | 38.03901 | -0.9153 | 22.95958 |
July | 744.00000 | 23.53933 | 52.16495 | -0.6655 | 14.55137 |
August | 744.00000 | 23.78484 | 49.88181 | -0.5866 | 12.37227 |
September | 720.00000 | 23.89630 | 41.66804 | -0.5913 | 12.45966 |
October | 744.00000 | 23.93166 | 27.01263 | 0.23949 | 6.30428 |
November | 720.00000 | 23.94288 | 21.46240 | 0.20066 | 5.89788 |
December | 744.00000 | 23.91291 | 19.85744 | 0.17569 | 5.70787 |
Annual Sum or Average | 8760.00000 | 23.43200 | 30.58704 | -0.2826 | 11.13459 |
Minimum of Months | 672.00000 | 22.64786 | 19.39124 | -1.1097 | 5.17524 |
Maximum of Months | 744.00000 | 23.94288 | 52.16495 | 0.23949 | 31.18983 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.02950 | 22.35377 | -0.2100 | 8.55785 |
February | 672.00000 | 22.19638 | 23.37597 | -0.1492 | 7.95908 |
March | 744.00000 | 22.19729 | 21.73708 | -0.1524 | 7.42865 |
April | 720.00000 | 22.64247 | 17.78563 | -0.0542 | 6.57532 |
May | 744.00000 | 22.70648 | 26.64930 | -0.9817 | 27.32191 |
June | 720.00000 | 23.25288 | 36.06699 | -0.6973 | 16.94997 |
July | 744.00000 | 23.65436 | 50.08301 | -0.4315 | 9.59041 |
August | 744.00000 | 23.68353 | 48.43310 | -0.4150 | 9.54811 |
September | 720.00000 | 23.51919 | 41.30642 | -0.5185 | 12.50132 |
October | 744.00000 | 23.07360 | 27.03013 | 0.15148 | 7.83968 |
November | 720.00000 | 22.46639 | 22.05031 | -0.0649 | 7.46156 |
December | 744.00000 | 22.10622 | 20.32264 | -0.1990 | 8.64154 |
Annual Sum or Average | 8760.00000 | 22.79701 | 29.82380 | -0.3113 | 10.88842 |
Minimum of Months | 672.00000 | 22.02950 | 17.78563 | -0.9817 | 6.57532 |
Maximum of Months | 744.00000 | 23.68353 | 50.08301 | 0.15148 | 27.32191 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.87675 | 23.59037 | -0.0430 | 5.38790 |
February | 672.00000 | 23.02654 | 24.49773 | 0.00314 | 5.30482 |
March | 744.00000 | 23.20724 | 22.72503 | 0.04013 | 5.33110 |
April | 720.00000 | 23.49536 | 19.05875 | 0.09664 | 5.44697 |
May | 744.00000 | 23.58217 | 27.28263 | -0.7607 | 17.73615 |
June | 720.00000 | 23.78540 | 36.60168 | -0.6030 | 12.95928 |
July | 744.00000 | 23.89980 | 50.80713 | -0.4518 | 9.36218 |
August | 744.00000 | 23.91076 | 49.29273 | -0.4577 | 9.46619 |
September | 720.00000 | 23.87540 | 42.13524 | -0.5306 | 11.03330 |
October | 744.00000 | 23.63447 | 28.27355 | 0.20249 | 6.29132 |
November | 720.00000 | 23.31324 | 23.26791 | 0.07095 | 5.34438 |
December | 744.00000 | 22.90811 | 21.74728 | -0.0475 | 5.31871 |
Annual Sum or Average | 8760.00000 | 23.46143 | 30.83048 | -0.2081 | 8.26782 |
Minimum of Months | 672.00000 | 22.87675 | 19.05875 | -0.7607 | 5.30482 |
Maximum of Months | 744.00000 | 23.91076 | 50.80713 | 0.20249 | 17.73615 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.26827 | 18.35930 | 0.62120 | 15.22724 |
February | 672.00000 | 23.28431 | 19.42547 | 0.64204 | 15.77470 |
March | 744.00000 | 23.34477 | 17.79854 | 0.66969 | 16.41633 |
April | 720.00000 | 23.38723 | 14.44433 | 0.68511 | 16.78204 |
May | 744.00000 | 23.40233 | 22.95302 | 0.08087 | 9.03697 |
June | 720.00000 | 23.41519 | 33.09354 | 0.19405 | 9.67973 |
July | 744.00000 | 23.41535 | 48.19921 | 0.30942 | 10.64598 |
August | 744.00000 | 23.39818 | 46.74499 | 0.28940 | 10.51335 |
September | 720.00000 | 23.35475 | 39.15981 | 0.19601 | 9.63840 |
October | 744.00000 | 23.30127 | 24.29161 | 0.72921 | 18.29666 |
November | 720.00000 | 23.32404 | 18.45107 | 0.66063 | 16.21227 |
December | 744.00000 | 23.28453 | 16.58418 | 0.61091 | 14.94234 |
Annual Sum or Average | 8760.00000 | 23.34864 | 26.68831 | 0.47310 | 13.58496 |
Minimum of Months | 672.00000 | 23.26827 | 14.44433 | 0.08087 | 9.03697 |
Maximum of Months | 744.00000 | 23.41535 | 48.19921 | 0.72921 | 18.29666 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.29703 | 26.45707 | 0.16579 | 6.99690 |
February | 672.00000 | 23.44544 | 27.32259 | 0.21979 | 7.06635 |
March | 744.00000 | 23.47045 | 25.80050 | 0.21461 | 6.77114 |
April | 720.00000 | 23.65316 | 22.24178 | 0.25038 | 6.77826 |
May | 744.00000 | 23.59575 | 30.66578 | -0.6102 | 13.68050 |
June | 720.00000 | 23.72658 | 40.03227 | -0.4561 | 9.92405 |
July | 744.00000 | 23.87960 | 53.92041 | -0.2640 | 6.68312 |
August | 744.00000 | 23.90121 | 52.18389 | -0.2472 | 6.65584 |
September | 720.00000 | 23.90462 | 44.85255 | -0.2949 | 7.57077 |
October | 744.00000 | 23.77270 | 30.86887 | 0.39266 | 9.22256 |
November | 720.00000 | 23.62359 | 26.02096 | 0.28122 | 7.60619 |
December | 744.00000 | 23.37345 | 24.58648 | 0.17888 | 7.06086 |
Annual Sum or Average | 8760.00000 | 23.63755 | 33.80392 | -0.0156 | 8.00941 |
Minimum of Months | 672.00000 | 23.29703 | 22.24178 | -0.6102 | 6.65584 |
Maximum of Months | 744.00000 | 23.90462 | 53.92041 | 0.39266 | 13.68050 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.54156 | 25.73357 | 0.15507 | 5.82463 |
February | 672.00000 | 23.62599 | 26.61088 | 0.18720 | 5.93527 |
March | 744.00000 | 23.66203 | 24.86704 | 0.19136 | 5.97767 |
April | 720.00000 | 23.72611 | 21.24814 | 0.19680 | 5.96193 |
May | 744.00000 | 23.71974 | 29.36442 | -0.6546 | 14.40309 |
June | 720.00000 | 23.81917 | 38.73286 | -0.5272 | 11.08556 |
July | 744.00000 | 23.90842 | 52.91107 | -0.3802 | 8.10029 |
August | 744.00000 | 23.93392 | 51.32881 | -0.3793 | 8.06390 |
September | 720.00000 | 23.94912 | 44.01863 | -0.4332 | 9.02222 |
October | 744.00000 | 23.87700 | 30.17326 | 0.31245 | 7.29382 |
November | 720.00000 | 23.79141 | 25.25479 | 0.23208 | 6.27603 |
December | 744.00000 | 23.60077 | 23.93831 | 0.15803 | 5.76112 |
Annual Sum or Average | 8760.00000 | 23.76342 | 32.90561 | -0.0801 | 7.82115 |
Minimum of Months | 672.00000 | 23.54156 | 21.24814 | -0.6546 | 5.76112 |
Maximum of Months | 744.00000 | 23.94912 | 52.91107 | 0.31245 | 14.40309 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.38200 | 38.19818 | -0.3949 | 9.37891 |
February | 672.00000 | 21.47787 | 38.82019 | -0.3401 | 8.59272 |
March | 744.00000 | 21.55520 | 35.39251 | -0.3023 | 7.94030 |
April | 720.00000 | 21.67055 | 29.98960 | -0.2400 | 7.39592 |
May | 744.00000 | 21.68691 | 37.28715 | -1.2705 | 40.14354 |
June | 720.00000 | 21.72861 | 44.34290 | -1.1384 | 33.95915 |
July | 744.00000 | 21.74657 | 47.78221 | -1.0810 | 31.34335 |
August | 744.00000 | 21.74194 | 47.93199 | -1.0807 | 31.39712 |
September | 720.00000 | 21.73019 | 46.76248 | -1.1276 | 33.66813 |
October | 744.00000 | 21.65489 | 39.18768 | -0.1794 | 7.04530 |
November | 720.00000 | 21.56262 | 37.83845 | -0.2963 | 7.99905 |
December | 744.00000 | 21.38879 | 36.68469 | -0.4067 | 9.63128 |
Annual Sum or Average | 8760.00000 | 21.61092 | 40.03114 | -0.6569 | 19.10832 |
Minimum of Months | 672.00000 | 21.38200 | 29.98960 | -1.2705 | 7.04530 |
Maximum of Months | 744.00000 | 21.74657 | 47.93199 | -0.1794 | 40.14354 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.98661 | 39.00930 | -0.5431 | 11.62723 |
February | 672.00000 | 21.16778 | 39.39177 | -0.4678 | 10.30164 |
March | 744.00000 | 21.55369 | 35.34644 | -0.3482 | 8.59684 |
April | 720.00000 | 22.09456 | 29.66907 | -0.1818 | 7.65487 |
May | 744.00000 | 22.13600 | 36.66831 | -1.1562 | 35.66725 |
June | 720.00000 | 22.15387 | 43.63971 | -1.0187 | 29.47750 |
July | 744.00000 | 22.19409 | 47.98191 | -0.9564 | 26.69883 |
August | 744.00000 | 22.24222 | 48.13780 | -0.9551 | 26.76358 |
September | 720.00000 | 22.26376 | 46.63125 | -1.0210 | 29.16950 |
October | 744.00000 | 21.97083 | 39.04899 | -0.1708 | 7.61360 |
November | 720.00000 | 21.27513 | 38.27744 | -0.4257 | 9.38694 |
December | 744.00000 | 20.92582 | 37.68206 | -0.5751 | 12.39763 |
Annual Sum or Average | 8760.00000 | 21.74960 | 40.13593 | -0.6531 | 17.99842 |
Minimum of Months | 672.00000 | 20.92582 | 29.66907 | -1.1562 | 7.61360 |
Maximum of Months | 744.00000 | 22.26376 | 48.13780 | -0.1708 | 35.66725 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.06544 | 34.80108 | -0.5202 | 10.68807 |
February | 672.00000 | 21.14994 | 35.43891 | -0.4830 | 9.94829 |
March | 744.00000 | 21.36818 | 31.59391 | -0.4208 | 8.82923 |
April | 720.00000 | 21.74915 | 26.06532 | -0.3327 | 7.83025 |
May | 744.00000 | 21.90612 | 33.72478 | -1.3390 | 42.98492 |
June | 720.00000 | 21.99898 | 42.74428 | -1.2077 | 36.70924 |
July | 744.00000 | 22.07278 | 49.82181 | -1.1281 | 33.20765 |
August | 744.00000 | 22.06867 | 49.91835 | -1.1422 | 33.73372 |
September | 720.00000 | 22.04612 | 46.23947 | -1.2097 | 36.66306 |
October | 744.00000 | 21.62954 | 36.28148 | -0.3099 | 7.63197 |
November | 720.00000 | 21.21168 | 34.31867 | -0.4618 | 9.54599 |
December | 744.00000 | 21.01495 | 33.42031 | -0.5451 | 11.28193 |
Annual Sum or Average | 8760.00000 | 21.60896 | 37.88968 | -0.7601 | 20.82217 |
Minimum of Months | 672.00000 | 21.01495 | 26.06532 | -1.3390 | 7.63197 |
Maximum of Months | 744.00000 | 22.07278 | 49.91835 | -0.3099 | 42.98492 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.42684 | 38.20066 | -0.3859 | 9.26355 |
February | 672.00000 | 21.53295 | 38.74913 | -0.3329 | 8.49696 |
March | 744.00000 | 21.63552 | 35.31324 | -0.2748 | 7.78370 |
April | 720.00000 | 21.73647 | 29.99934 | -0.2058 | 7.28598 |
May | 744.00000 | 21.74090 | 36.89863 | -1.2297 | 38.34008 |
June | 720.00000 | 21.75304 | 43.99262 | -1.1063 | 32.63199 |
July | 744.00000 | 21.75773 | 47.42874 | -1.0508 | 30.18014 |
August | 744.00000 | 21.75672 | 47.60324 | -1.0561 | 30.46315 |
September | 720.00000 | 21.75061 | 46.54209 | -1.1125 | 33.05481 |
October | 744.00000 | 21.69487 | 39.09468 | -0.1670 | 7.03874 |
November | 720.00000 | 21.60716 | 37.81190 | -0.2854 | 7.90621 |
December | 744.00000 | 21.45264 | 36.66110 | -0.3944 | 9.39647 |
Annual Sum or Average | 8760.00000 | 21.65414 | 39.87004 | -0.6355 | 18.54993 |
Minimum of Months | 672.00000 | 21.42684 | 29.99934 | -1.2297 | 7.03874 |
Maximum of Months | 744.00000 | 21.75773 | 47.60324 | -0.1670 | 38.34008 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.98390 | 38.95141 | -0.5445 | 11.50228 |
February | 672.00000 | 21.16346 | 39.33398 | -0.4737 | 10.14416 |
March | 744.00000 | 21.61720 | 35.18129 | -0.3246 | 8.04646 |
April | 720.00000 | 22.05678 | 29.55535 | -0.1696 | 7.01453 |
May | 744.00000 | 22.19770 | 36.17849 | -1.1138 | 33.91401 |
June | 720.00000 | 22.37596 | 43.25840 | -0.9275 | 28.42141 |
July | 744.00000 | 22.44470 | 47.37726 | -0.8543 | 25.99032 |
August | 744.00000 | 22.48498 | 47.47314 | -0.8629 | 25.99162 |
September | 720.00000 | 22.39585 | 46.02599 | -0.9743 | 28.27503 |
October | 744.00000 | 21.92936 | 38.81218 | -0.1760 | 7.14309 |
November | 720.00000 | 21.28176 | 38.22648 | -0.4227 | 9.18422 |
December | 744.00000 | 20.89291 | 37.63538 | -0.5819 | 12.36440 |
Annual Sum or Average | 8760.00000 | 21.82181 | 39.84444 | -0.6199 | 17.38194 |
Minimum of Months | 672.00000 | 20.89291 | 29.55535 | -1.1138 | 7.01453 |
Maximum of Months | 744.00000 | 22.48498 | 47.47314 | -0.1696 | 33.91401 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.29496 | 39.05954 | -0.4465 | 10.48820 |
February | 672.00000 | 21.41028 | 39.69416 | -0.3809 | 9.47399 |
March | 744.00000 | 21.50131 | 36.04350 | -0.3358 | 8.61593 |
April | 720.00000 | 21.64613 | 30.25256 | -0.2564 | 7.82379 |
May | 744.00000 | 21.66699 | 37.67568 | -1.2837 | 41.06990 |
June | 720.00000 | 21.72555 | 44.66710 | -1.1325 | 34.04648 |
July | 744.00000 | 21.74750 | 48.25340 | -1.0680 | 31.09489 |
August | 744.00000 | 21.73856 | 48.51714 | -1.0720 | 31.34382 |
September | 720.00000 | 21.71700 | 47.62192 | -1.1356 | 34.36123 |
October | 744.00000 | 21.61378 | 39.83999 | -0.2063 | 7.57307 |
November | 720.00000 | 21.49912 | 38.57737 | -0.3395 | 8.78498 |
December | 744.00000 | 21.29879 | 37.44493 | -0.4595 | 10.80869 |
Annual Sum or Average | 8760.00000 | 21.57217 | 40.64894 | -0.6784 | 19.68930 |
Minimum of Months | 672.00000 | 21.29496 | 30.25256 | -1.2837 | 7.57307 |
Maximum of Months | 744.00000 | 21.74750 | 48.51714 | -0.2063 | 41.06990 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.86057 | 40.03830 | -0.6067 | 13.23571 |
February | 672.00000 | 21.07590 | 40.37394 | -0.5180 | 11.51954 |
March | 744.00000 | 21.50785 | 36.12618 | -0.3814 | 9.44257 |
April | 720.00000 | 22.12277 | 30.03501 | -0.1841 | 8.25782 |
May | 744.00000 | 22.13314 | 37.06300 | -1.1594 | 36.45239 |
June | 720.00000 | 22.14457 | 43.95998 | -1.0106 | 29.62569 |
July | 744.00000 | 22.16035 | 48.29363 | -0.9513 | 26.65811 |
August | 744.00000 | 22.20829 | 48.46722 | -0.9532 | 26.92908 |
September | 720.00000 | 22.21859 | 47.35599 | -1.0364 | 30.05237 |
October | 744.00000 | 21.93293 | 39.77578 | -0.1979 | 8.33891 |
November | 720.00000 | 21.16276 | 39.23030 | -0.4847 | 10.60365 |
December | 744.00000 | 20.79822 | 38.59704 | -0.6403 | 14.12390 |
Annual Sum or Average | 8760.00000 | 21.69652 | 40.78659 | -0.6783 | 18.82009 |
Minimum of Months | 672.00000 | 20.79822 | 30.03501 | -1.1594 | 8.25782 |
Maximum of Months | 744.00000 | 22.21859 | 48.46722 | -0.1841 | 36.45239 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.59429 | 38.87619 | -0.2708 | 8.42865 |
February | 672.00000 | 21.63666 | 39.38837 | -0.2433 | 8.03859 |
March | 744.00000 | 21.63343 | 35.64983 | -0.2656 | 7.90287 |
April | 720.00000 | 21.68026 | 30.38317 | -0.2614 | 7.81433 |
May | 744.00000 | 21.67669 | 37.62668 | -1.3370 | 43.45994 |
June | 720.00000 | 21.71599 | 44.89507 | -1.2256 | 37.96403 |
July | 744.00000 | 21.74164 | 48.81735 | -1.1453 | 34.20948 |
August | 744.00000 | 21.73627 | 48.90236 | -1.1306 | 33.75586 |
September | 720.00000 | 21.72862 | 47.61626 | -1.1428 | 34.81025 |
October | 744.00000 | 21.69695 | 39.48940 | -0.1474 | 7.25296 |
November | 720.00000 | 21.67205 | 38.65560 | -0.2060 | 7.67569 |
December | 744.00000 | 21.59676 | 37.50212 | -0.2684 | 8.48598 |
Annual Sum or Average | 8760.00000 | 21.67587 | 40.66345 | -0.6395 | 20.05857 |
Minimum of Months | 672.00000 | 21.59429 | 30.38317 | -1.3370 | 7.25296 |
Maximum of Months | 744.00000 | 21.74164 | 48.90236 | -0.1474 | 43.45994 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.65999 | 26.50317 | 0.18064 | 5.93716 |
February | 672.00000 | 23.73812 | 27.26693 | 0.22024 | 6.22374 |
March | 744.00000 | 23.85984 | 25.13770 | 0.26822 | 6.60136 |
April | 720.00000 | 23.94754 | 21.34350 | 0.30591 | 7.04393 |
May | 744.00000 | 23.97427 | 29.14222 | -0.4601 | 9.66614 |
June | 720.00000 | 23.99309 | 38.49647 | -0.3323 | 7.44011 |
July | 744.00000 | 23.99580 | 52.87170 | -0.2106 | 5.96923 |
August | 744.00000 | 23.99428 | 51.50776 | -0.2344 | 6.19535 |
September | 720.00000 | 23.98177 | 44.49452 | -0.3291 | 7.37976 |
October | 744.00000 | 23.88658 | 30.90150 | 0.35007 | 7.84360 |
November | 720.00000 | 23.77757 | 26.12955 | 0.23647 | 6.35865 |
December | 744.00000 | 23.63297 | 24.84833 | 0.15744 | 5.81176 |
Annual Sum or Average | 8760.00000 | 23.87064 | 33.27583 | 0.01145 | 6.87589 |
Minimum of Months | 672.00000 | 23.63297 | 21.34350 | -0.4601 | 5.81176 |
Maximum of Months | 744.00000 | 23.99580 | 52.87170 | 0.35007 | 9.66614 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.81310 | 25.55915 | 0.25734 | 6.51645 |
February | 672.00000 | 23.86723 | 26.35666 | 0.29030 | 6.86565 |
March | 744.00000 | 23.94616 | 24.33346 | 0.32639 | 7.26714 |
April | 720.00000 | 23.98296 | 20.71487 | 0.34813 | 7.59811 |
May | 744.00000 | 23.99069 | 28.61814 | -0.4097 | 8.70595 |
June | 720.00000 | 23.99583 | 38.08226 | -0.2916 | 6.90910 |
July | 744.00000 | 23.99666 | 52.50538 | -0.1733 | 5.67744 |
August | 744.00000 | 23.99579 | 51.12797 | -0.1967 | 5.86163 |
September | 720.00000 | 23.99193 | 44.04636 | -0.2869 | 6.83167 |
October | 744.00000 | 23.94038 | 30.27514 | 0.39362 | 8.45215 |
November | 720.00000 | 23.88591 | 25.28921 | 0.29947 | 6.97889 |
December | 744.00000 | 23.79219 | 23.91575 | 0.23580 | 6.32676 |
Annual Sum or Average | 8760.00000 | 23.93344 | 32.62562 | 0.06476 | 6.99947 |
Minimum of Months | 672.00000 | 23.79219 | 20.71487 | -0.4097 | 5.67744 |
Maximum of Months | 744.00000 | 23.99666 | 52.50538 | 0.39362 | 8.70595 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.78804 | 24.55959 | 0.89544 | 24.21752 |
February | 672.00000 | 23.80675 | 25.45702 | 0.92609 | 25.35363 |
March | 744.00000 | 23.86646 | 23.74451 | 0.97047 | 26.88890 |
April | 720.00000 | 23.92530 | 20.51965 | 1.01871 | 28.90720 |
May | 744.00000 | 23.95700 | 28.52923 | 0.55476 | 15.69229 |
June | 720.00000 | 23.98054 | 38.04997 | 0.69522 | 19.13979 |
July | 744.00000 | 23.99194 | 52.18337 | 0.82112 | 22.82321 |
August | 744.00000 | 23.99027 | 50.78249 | 0.79717 | 22.13225 |
September | 720.00000 | 23.97741 | 43.70811 | 0.69176 | 19.05617 |
October | 744.00000 | 23.92278 | 29.81405 | 1.06614 | 30.89514 |
November | 720.00000 | 23.84582 | 24.51461 | 0.94819 | 26.01705 |
December | 744.00000 | 23.78509 | 22.89524 | 0.87940 | 23.65161 |
Annual Sum or Average | 8760.00000 | 23.90359 | 32.12145 | 0.85498 | 23.72284 |
Minimum of Months | 672.00000 | 23.78509 | 20.51965 | 0.55476 | 15.69229 |
Maximum of Months | 744.00000 | 23.99194 | 52.18337 | 1.06614 | 30.89514 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.20676 | 22.07791 | -0.4767 | 9.80326 |
February | 672.00000 | 21.35415 | 23.14745 | -0.4324 | 9.02988 |
March | 744.00000 | 21.81491 | 20.92934 | -0.3317 | 7.38683 |
April | 720.00000 | 22.46177 | 16.80910 | -0.2003 | 6.07870 |
May | 744.00000 | 22.98503 | 24.97074 | -1.0319 | 28.04659 |
June | 720.00000 | 23.64811 | 34.15417 | -0.7348 | 16.74051 |
July | 744.00000 | 23.92851 | 48.27039 | -0.5351 | 11.02598 |
August | 744.00000 | 23.85550 | 47.05945 | -0.5725 | 11.93434 |
September | 720.00000 | 23.50869 | 40.37944 | -0.7449 | 16.89293 |
October | 744.00000 | 22.66971 | 26.56513 | -0.0842 | 5.94888 |
November | 720.00000 | 21.79631 | 21.61021 | -0.3316 | 7.43922 |
December | 744.00000 | 21.15870 | 20.13475 | -0.4990 | 10.26381 |
Annual Sum or Average | 8760.00000 | 22.53851 | 28.89577 | -0.4984 | 11.73720 |
Minimum of Months | 672.00000 | 21.15870 | 16.80910 | -1.0319 | 5.94888 |
Maximum of Months | 744.00000 | 23.92851 | 48.27039 | -0.0842 | 28.04659 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.45822 | 26.10150 | -0.4111 | 8.68047 |
February | 672.00000 | 21.57470 | 27.19088 | -0.3735 | 8.09615 |
March | 744.00000 | 22.06701 | 25.03165 | -0.2657 | 6.63189 |
April | 720.00000 | 22.80025 | 20.96865 | -0.1128 | 5.47402 |
May | 744.00000 | 23.19495 | 29.21654 | -0.9625 | 25.04590 |
June | 720.00000 | 23.69951 | 38.41973 | -0.7206 | 16.21254 |
July | 744.00000 | 23.95213 | 52.31588 | -0.5323 | 10.95914 |
August | 744.00000 | 23.94475 | 50.87703 | -0.5447 | 11.24566 |
September | 720.00000 | 23.83133 | 44.06183 | -0.6366 | 13.62867 |
October | 744.00000 | 23.18553 | 30.28214 | 0.04621 | 5.87085 |
November | 720.00000 | 22.11111 | 25.66575 | -0.2506 | 6.45749 |
December | 744.00000 | 21.32902 | 24.23865 | -0.4527 | 9.35124 |
Annual Sum or Average | 8760.00000 | 22.76832 | 32.91723 | -0.4353 | 10.66086 |
Minimum of Months | 672.00000 | 21.32902 | 20.96865 | -0.9625 | 5.47402 |
Maximum of Months | 744.00000 | 23.95213 | 52.31588 | 0.04621 | 25.04590 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.29852 | 23.02888 | -0.4448 | 9.32201 |
February | 672.00000 | 21.47741 | 24.07545 | -0.3873 | 8.45369 |
March | 744.00000 | 21.84944 | 21.95432 | -0.2992 | 7.20008 |
April | 720.00000 | 22.63714 | 17.64797 | -0.1268 | 5.89644 |
May | 744.00000 | 23.12194 | 25.81412 | -0.9372 | 24.66796 |
June | 720.00000 | 23.66651 | 35.01490 | -0.6664 | 14.89097 |
July | 744.00000 | 23.90326 | 49.10580 | -0.4738 | 9.80994 |
August | 744.00000 | 23.85974 | 47.79929 | -0.5008 | 10.43730 |
September | 720.00000 | 23.63367 | 41.01513 | -0.6430 | 14.18064 |
October | 744.00000 | 22.82161 | 27.30874 | -0.0153 | 6.25086 |
November | 720.00000 | 21.72850 | 22.75025 | -0.3252 | 7.53200 |
December | 744.00000 | 21.25650 | 21.05100 | -0.4678 | 9.73729 |
Annual Sum or Average | 8760.00000 | 22.61037 | 29.76681 | -0.4411 | 10.71752 |
Minimum of Months | 672.00000 | 21.25650 | 17.64797 | -0.9372 | 5.89644 |
Maximum of Months | 744.00000 | 23.90326 | 49.10580 | -0.0153 | 24.66796 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.36967 | 21.40505 | -0.4410 | 9.15955 |
February | 672.00000 | 21.51993 | 22.44645 | -0.3966 | 8.46350 |
March | 744.00000 | 22.01696 | 20.19816 | -0.2882 | 6.86393 |
April | 720.00000 | 22.65223 | 16.12996 | -0.1586 | 5.79910 |
May | 744.00000 | 23.17683 | 24.17937 | -0.9695 | 25.49658 |
June | 720.00000 | 23.74170 | 33.44447 | -0.6991 | 15.59498 |
July | 744.00000 | 23.94958 | 47.68748 | -0.5200 | 10.69852 |
August | 744.00000 | 23.89969 | 46.37497 | -0.5513 | 11.42738 |
September | 720.00000 | 23.64932 | 39.48177 | -0.6968 | 15.43039 |
October | 744.00000 | 22.85893 | 25.77722 | -0.0424 | 5.83637 |
November | 720.00000 | 21.99516 | 20.87595 | -0.2888 | 6.91762 |
December | 744.00000 | 21.30664 | 19.49864 | -0.4663 | 9.64133 |
Annual Sum or Average | 8760.00000 | 22.68394 | 28.17867 | -0.4604 | 10.96459 |
Minimum of Months | 672.00000 | 21.30664 | 16.12996 | -0.9695 | 5.79910 |
Maximum of Months | 744.00000 | 23.94958 | 47.68748 | -0.0424 | 25.49658 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.144805E+11 | 46045.90 | 05-JAN-16:01 | 441.88 | 0.459115E+11 | 0.00 | 0.603920E+11 | 1.89 | 3.21 | 05-JAN-16:01 | 0.00 | 0.00 |
February | 0.168438E+11 | 80590.99 | 14-FEB-16:01 | 456.39 | 0.534390E+11 | 0.00 | 0.702828E+11 | 2.16 | 3.90 | 13-FEB-16:01 | 0.00 | 0.00 |
March | 0.269936E+11 | 83801.66 | 08-MAR-16:01 | 640.30 | 0.831856E+11 | 0.00 | 0.110179E+12 | 2.71 | 3.95 | 13-MAR-15:01 | 0.00 | 0.00 |
April | 0.598691E+11 | 100165.76 | 28-APR-18:03 | 714.05 | 0.185885E+12 | 0.00 | 0.245754E+12 | 3.10 | 3.91 | 10-APR-15:01 | 0.00 | 0.00 |
May | 0.940107E+11 | 117036.65 | 19-MAY-18:03 | 743.39 | 0.294250E+12 | 0.00 | 0.388261E+12 | 3.11 | 3.94 | 19-MAY-21:51 | 0.00 | 0.00 |
June | 0.155903E+12 | 160578.42 | 28-JUN-15:03 | 720.00 | 0.481910E+12 | 0.00 | 0.637814E+12 | 3.08 | 3.94 | 15-JUN-21:52 | 0.00 | 0.00 |
July | 0.203482E+12 | 159817.77 | 21-JUL-18:03 | 744.00 | 0.646368E+12 | 0.00 | 0.849850E+12 | 3.17 | 4.25 | 15-JUL-21:53 | 0.00 | 0.00 |
August | 0.184637E+12 | 158107.67 | 01-AUG-15:07 | 744.00 | 0.593883E+12 | 0.00 | 0.778520E+12 | 3.19 | 4.10 | 13-AUG-08:52 | 0.00 | 0.00 |
September | 0.128758E+12 | 124832.21 | 02-SEP-15:03 | 720.00 | 0.414741E+12 | 0.00 | 0.543500E+12 | 3.16 | 3.98 | 13-SEP-21:51 | 0.00 | 0.00 |
October | 0.703519E+11 | 113093.06 | 01-OCT-15:03 | 706.40 | 0.225328E+12 | 0.00 | 0.295680E+12 | 3.01 | 4.02 | 16-OCT-15:03 | 0.00 | 0.00 |
November | 0.223085E+11 | 53422.60 | 02-NOV-15:03 | 593.78 | 0.706088E+11 | 0.00 | 0.929173E+11 | 2.62 | 3.58 | 02-NOV-15:03 | 0.00 | 0.00 |
December | 0.150284E+11 | 36008.73 | 02-DEC-16:01 | 444.36 | 0.478863E+11 | 0.00 | 0.629147E+11 | 1.90 | 3.19 | 04-DEC-20:40 | 0.00 | 0.00 |
Annual Sum or Average | 0.992668E+12 | 7668.55 | 0.314340E+13 | 0.00 | 0.413606E+13 | 2.76 | 0.00 | 0.00 | ||||
Minimum of Months | 0.144805E+11 | 36008.73 | 441.88 | 0.459115E+11 | 0.00 | 0.603920E+11 | 1.89 | 3.19 | 0.00 | 0.00 | ||
Maximum of Months | 0.203482E+12 | 160578.42 | 744.00 | 0.646368E+12 | 0.00 | 0.849850E+12 | 3.19 | 4.25 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.782322E+11 | 0.00 | 709.48 | 168747.61 | 20-JAN-16:01 | 0.00 | 49.10 | 78.64 | 0.21 | 0.00 | 0.07 | 0.43 | 20-JAN-16:01 |
February | 0.652500E+11 | 0.00 | 621.61 | 166143.01 | 04-FEB-16:01 | 0.00 | 48.54 | 77.43 | 0.19 | 0.00 | 0.07 | 0.42 | 04-FEB-16:01 |
March | 0.676413E+11 | 0.00 | 573.00 | 183782.07 | 04-MAR-19:03 | 0.00 | 39.86 | 68.59 | 0.14 | 0.00 | 0.06 | 0.46 | 04-MAR-19:03 |
April | 0.515975E+11 | 0.00 | 381.16 | 126044.70 | 16-APR-08:05 | 0.00 | 31.26 | 55.25 | 0.10 | 0.00 | 0.05 | 0.32 | 16-APR-08:05 |
May | 0.298507E+11 | 0.00 | 239.02 | 117307.76 | 06-MAY-08:05 | 0.00 | 28.77 | 44.81 | 0.05 | 0.00 | 0.03 | 0.30 | 06-MAY-08:05 |
June | 0.672601E+10 | 0.00 | 73.34 | 94127.49 | 09-JUN-05:00 | 0.00 | 28.97 | 34.40 | 0.01 | 0.00 | 0.01 | 0.24 | 09-JUN-05:00 |
July | 45657942.26 | 0.00 | 2.03 | 24789.31 | 08-JUL-18:06 | 0.00 | 49.45 | 49.53 | 0.00 | 0.00 | 0.00 | 0.06 | 08-JUL-18:06 |
August | 0.116710E+09 | 0.00 | 4.44 | 42388.05 | 31-AUG-08:54 | 0.00 | 58.01 | 58.18 | 0.00 | 0.00 | 0.00 | 0.11 | 31-AUG-08:54 |
September | 0.499558E+10 | 0.00 | 69.01 | 60486.37 | 20-SEP-06:00 | 0.00 | 32.18 | 37.19 | 0.01 | 0.00 | 0.00 | 0.15 | 20-SEP-06:00 |
October | 0.491086E+11 | 0.00 | 367.03 | 139986.87 | 26-OCT-18:03 | 0.00 | 33.26 | 54.25 | 0.10 | 0.00 | 0.05 | 0.35 | 26-OCT-18:03 |
November | 0.664212E+11 | 0.00 | 639.95 | 167028.34 | 16-NOV-19:03 | 0.00 | 45.92 | 75.45 | 0.16 | 0.00 | 0.06 | 0.42 | 16-NOV-19:03 |
December | 0.826294E+11 | 0.00 | 716.58 | 178594.96 | 07-DEC-16:01 | 0.00 | 52.26 | 79.79 | 0.23 | 0.00 | 0.08 | 0.45 | 07-DEC-16:01 |
Annual Sum or Average | 0.502615E+12 | 0.00 | 4396.65 | 0.00 | 41.48 | 59.41 | 0.10 | 0.00 | 0.04 | ||||
Minimum of Months | 45657942.26 | 0.00 | 2.03 | 24789.31 | 0.00 | 28.77 | 34.40 | 0.00 | 0.00 | 0.00 | 0.06 | ||
Maximum of Months | 0.826294E+11 | 0.00 | 716.58 | 183782.07 | 0.00 | 58.01 | 79.79 | 0.23 | 0.00 | 0.08 | 0.46 |
Report: DXReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.523182E+11 | 0.00 | 468.19 | 0.523182E+11 | -0.0 | 0.00 | 1.00 | 01-JAN-06:15 | 0.00 | 01-JAN-00:10 | 36909.62 | 31-JAN-05:15 | 36909.62 | 31-JAN-05:15 | 0.00 | 31-JAN-13:40 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.487120E+11 | 0.00 | 414.42 | 0.487120E+11 | 0.00 | 0.00 | 1.00 | 01-FEB-05:15 | 0.00 | 01-FEB-00:05 | 39578.47 | 06-FEB-18:00 | 39578.47 | 06-FEB-06:15 | 0.00 | 02-FEB-07:30 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 0.544587E+11 | 0.00 | 432.14 | 0.544587E+11 | 0.00 | 0.00 | 1.00 | 01-MAR-05:15 | 0.00 | 01-MAR-00:10 | 44472.02 | 01-MAR-11:17 | 44472.02 | 01-MAR-05:15 | 0.00 | 16-MAR-20:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.509727E+11 | 0.00 | 396.40 | 0.509727E+11 | -0.0 | 0.00 | 1.00 | 01-APR-01:10 | 0.00 | 01-APR-00:20 | 48818.79 | 01-APR-09:20 | 48818.79 | 01-APR-07:50 | 0.00 | 09-APR-05:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.499123E+11 | 0.00 | 385.47 | 0.499123E+11 | 0.00 | 0.00 | 1.00 | 01-MAY-05:05 | 0.00 | 01-MAY-00:05 | 53526.34 | 01-MAY-05:05 | 53526.34 | 01-MAY-17:25 | 0.00 | 25-MAY-06:30 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.457749E+11 | 0.00 | 359.99 | 0.457737E+11 | 1186783.15 | 0.00 | 1.00 | 01-JUN-04:07 | 0.00 | 01-JUN-00:05 | 58772.08 | 01-JUN-04:07 | 58772.08 | 01-JUN-10:15 | 722.15 | 30-JUN-23:10 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.453848E+11 | 0.00 | 359.93 | 0.440648E+11 | 0.131997E+10 | 0.00 | 1.00 | 01-JUL-05:08 | 0.00 | 01-JUL-00:20 | 62036.44 | 01-JUL-10:15 | 60069.43 | 01-JUL-05:08 | 1967.12 | 01-JUL-15:07 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.445830E+11 | 0.00 | 362.06 | 0.430883E+11 | 0.149468E+10 | 0.00 | 1.00 | 01-AUG-05:13 | 0.00 | 01-AUG-00:05 | 60381.34 | 31-AUG-06:20 | 58280.99 | 31-AUG-06:52 | 2101.32 | 31-AUG-17:15 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.440486E+11 | 0.00 | 354.56 | 0.440486E+11 | 0.00 | 0.00 | 1.00 | 01-SEP-04:20 | 0.00 | 01-SEP-00:05 | 57082.01 | 30-SEP-05:08 | 57082.01 | 30-SEP-18:34 | 0.00 | 02-SEP-05:08 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.468845E+11 | 0.00 | 389.07 | 0.468845E+11 | -0.0 | 0.00 | 1.00 | 01-OCT-06:20 | 0.00 | 01-OCT-00:10 | 49358.44 | 31-OCT-04:15 | 49358.44 | 31-OCT-04:15 | 0.00 | 16-OCT-19:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.467772E+11 | 0.00 | 411.05 | 0.467772E+11 | -0.0 | 0.00 | 1.00 | 01-NOV-04:07 | 0.00 | 01-NOV-00:05 | 41566.90 | 30-NOV-08:13 | 41566.90 | 30-NOV-09:25 | 0.00 | 09-NOV-06:07 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.493823E+11 | 0.00 | 463.20 | 0.493823E+11 | 0.00 | 0.00 | 1.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:20 | 35698.64 | 31-DEC-06:15 | 35698.64 | 31-DEC-08:63 | 0.00 | 02-DEC-23:50 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.579209E+12 | 0.00 | 4796.45 | 0.576393E+12 | 0.281583E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.440486E+11 | 0.00 | 354.56 | 0.430883E+11 | -0.0 | 0.00 | 1.00 | 0.00 | 35698.64 | 35698.64 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.544587E+11 | 0.00 | 468.19 | 0.544587E+11 | 0.149468E+10 | 0.00 | 1.00 | 0.00 | 62036.44 | 60069.43 | 2101.32 | 0.00 | 0.00 |
Report: DXReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.370871E+11 | 0.00 | 384.46 | 0.370871E+11 | -0.0 | 0.00 | 1.00 | 01-JAN-17:10 | 0.00 | 01-JAN-00:10 | 46700.35 | 31-JAN-23:50 | 46700.35 | 31-JAN-23:40 | 0.00 | 03-JAN-21:50 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.359957E+11 | 0.00 | 346.87 | 0.359957E+11 | 0.00 | 0.00 | 1.00 | 01-FEB-17:10 | 0.00 | 01-FEB-00:10 | 50079.74 | 06-FEB-20:00 | 50079.74 | 06-FEB-20:00 | 0.00 | 21-FEB-18:00 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 0.446998E+11 | 0.00 | 359.67 | 0.446998E+11 | 0.00 | 0.00 | 1.00 | 01-MAR-17:05 | 0.00 | 01-MAR-00:20 | 56276.13 | 01-MAR-17:05 | 56276.13 | 01-MAR-21:40 | 0.00 | 02-MAR-22:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.473355E+11 | 0.00 | 349.37 | 0.473355E+11 | 0.00 | 0.00 | 1.00 | 01-APR-16:10 | 0.00 | 01-APR-00:20 | 61780.16 | 01-APR-16:10 | 61780.16 | 01-APR-16:30 | 0.00 | 02-APR-16:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.535113E+11 | 0.00 | 353.44 | 0.535113E+11 | 0.00 | 0.00 | 1.00 | 01-MAY-16:10 | 0.00 | 01-MAY-00:05 | 67741.03 | 01-MAY-16:30 | 67741.03 | 01-MAY-16:30 | 0.00 | 01-MAY-16:50 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.568871E+11 | 0.00 | 335.40 | 0.568863E+11 | 816796.01 | 0.00 | 1.00 | 01-JUN-16:10 | 0.00 | 01-JUN-00:05 | 74383.37 | 01-JUN-16:10 | 74383.37 | 01-JUN-17:12 | 1335.92 | 30-JUN-23:10 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.622217E+11 | 0.00 | 363.05 | 0.604316E+11 | 0.179011E+10 | 0.00 | 1.00 | 01-JUL-16:10 | 0.00 | 01-JUL-00:10 | 78516.82 | 01-JUL-16:10 | 76050.59 | 01-JUL-21:51 | 2466.36 | 01-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.607106E+11 | 0.00 | 346.07 | 0.586926E+11 | 0.201799E+10 | 0.00 | 1.00 | 01-AUG-16:10 | 0.00 | 01-AUG-00:05 | 76421.08 | 31-AUG-16:10 | 73785.09 | 31-AUG-21:00 | 2636.58 | 31-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.553453E+11 | 0.00 | 338.87 | 0.553453E+11 | 0.00 | 0.00 | 1.00 | 01-SEP-16:10 | 0.00 | 01-SEP-00:05 | 72243.34 | 30-SEP-16:20 | 72243.34 | 30-SEP-18:32 | 0.00 | 02-SEP-20:55 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.493556E+11 | 0.00 | 361.17 | 0.493556E+11 | -0.0 | 0.00 | 1.00 | 01-OCT-16:10 | 0.00 | 01-OCT-00:20 | 62463.48 | 31-OCT-21:00 | 62463.48 | 31-OCT-19:50 | 0.00 | 11-OCT-21:21 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.402341E+11 | 0.00 | 367.83 | 0.402341E+11 | -0.0 | 0.00 | 1.00 | 01-NOV-16:10 | 0.00 | 01-NOV-00:10 | 52597.55 | 30-NOV-17:10 | 52597.55 | 30-NOV-17:20 | 0.00 | 14-NOV-19:20 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.357524E+11 | 0.00 | 382.27 | 0.357524E+11 | 0.00 | 0.00 | 1.00 | 01-DEC-17:10 | 0.00 | 01-DEC-00:10 | 45166.95 | 31-DEC-17:10 | 45166.95 | 31-DEC-20:10 | 0.00 | 21-DEC-21:10 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.579136E+12 | 0.00 | 4288.45 | 0.575327E+12 | 0.380891E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.357524E+11 | 0.00 | 335.40 | 0.357524E+11 | -0.0 | 0.00 | 1.00 | 0.00 | 45166.95 | 45166.95 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.622217E+11 | 0.00 | 384.46 | 0.604316E+11 | 0.201799E+10 | 0.00 | 1.00 | 0.00 | 78516.82 | 76050.59 | 2636.58 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.113883E+10 | 0.00 | 22.02 | 0.113883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37457.00 | 01-JAN-14:00 | 37457.00 | 01-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.638581E+10 | 0.00 | 37.83 | 0.638581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 121215.04 | 14-FEB-16:03 | 121215.04 | 14-FEB-16:03 | 0.00 | 0.00 | 0.00 |
March | 0.230089E+11 | 0.00 | 145.00 | 0.230089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 128031.73 | 08-MAR-16:03 | 128031.73 | 08-MAR-16:03 | 0.00 | 0.00 | 0.00 |
April | 0.944036E+11 | 0.00 | 328.00 | 0.944036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 192474.67 | 28-APR-18:03 | 192474.67 | 28-APR-18:03 | 0.00 | 0.00 | 0.00 |
May | 0.177214E+12 | 0.00 | 508.17 | 0.177214E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 223243.61 | 19-MAY-18:20 | 223243.61 | 19-MAY-18:20 | 0.00 | 0.00 | 0.00 |
June | 0.313086E+12 | 0.00 | 649.00 | 0.312872E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 259692.47 | 21-JUN-18:17 | 259692.47 | 21-JUN-18:17 | 0.00 | 0.00 | 0.00 |
July | 0.430432E+12 | 0.00 | 744.00 | 0.407888E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 325466.77 | 31-JUL-20:00 | 270923.83 | 21-JUL-18:20 | 0.00 | 0.00 | 0.00 |
August | 0.384622E+12 | 0.00 | 742.17 | 0.372824E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 278330.46 | 14-AUG-21:00 | 251995.58 | 18-AUG-18:40 | 0.00 | 0.00 | 0.00 |
September | 0.247725E+12 | 0.00 | 654.83 | 0.246783E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 223911.29 | 13-SEP-18:03 | 223911.29 | 13-SEP-18:03 | 0.00 | 0.00 | 0.00 |
October | 0.106274E+12 | 0.00 | 362.44 | 0.106181E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 194619.06 | 05-OCT-18:03 | 194619.06 | 05-OCT-18:03 | 0.00 | 0.00 | 0.00 |
November | 0.336714E+10 | 0.00 | 56.50 | 0.336714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60652.80 | 09-NOV-14:00 | 60652.80 | 09-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178766E+13 | 0.00 | 4249.97 | 0.175207E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.430432E+12 | 0.00 | 744.00 | 0.407888E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 325466.77 | 270923.83 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 28569562.60 | 0.00 | 9.50 | 28569562.60 | 0.00 | 0.00 | 0.00 | 0.00 | 2387.63 | 05-JAN-14:00 | 2387.63 | 05-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.354954E+09 | 0.00 | 21.67 | 0.354954E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12481.87 | 14-FEB-16:01 | 12481.87 | 14-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.140659E+10 | 0.00 | 85.67 | 0.140659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13330.12 | 08-MAR-16:01 | 13330.12 | 08-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.583698E+10 | 0.00 | 233.67 | 0.583698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14834.76 | 29-APR-15:01 | 14834.76 | 29-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.112270E+11 | 0.00 | 378.83 | 0.112268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16219.97 | 19-MAY-15:02 | 16219.97 | 19-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.190095E+11 | 0.00 | 502.33 | 0.189913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18773.38 | 28-JUN-15:02 | 18773.38 | 28-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.293128E+11 | 0.00 | 589.00 | 0.257760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28688.40 | 01-JUL-01:10 | 18707.60 | 22-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.254886E+11 | 0.00 | 587.50 | 0.234413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24430.19 | 13-AUG-08:53 | 17789.86 | 01-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.154881E+11 | 0.00 | 508.83 | 0.151791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23975.55 | 05-SEP-12:30 | 16776.92 | 02-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.632881E+10 | 0.00 | 253.17 | 0.629081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15887.79 | 02-OCT-16:50 | 15759.44 | 01-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.142365E+09 | 0.00 | 25.33 | 0.142365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8394.05 | 09-NOV-14:00 | 8394.05 | 09-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114624E+12 | 0.00 | 3195.50 | 0.108675E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.293128E+11 | 0.00 | 589.00 | 0.257760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28688.40 | 18773.38 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.118834E+10 | 0.00 | 200.28 | 0.116796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16607.54 | 05-JAN-16:01 | 16607.54 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.170876E+10 | 0.00 | 239.94 | 0.165629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17568.74 | 14-FEB-16:01 | 17568.74 | 14-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.272423E+10 | 0.00 | 387.52 | 0.267772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17688.16 | 08-MAR-16:01 | 17688.16 | 08-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.520770E+10 | 0.00 | 592.11 | 0.516547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18122.97 | 29-APR-15:01 | 18122.97 | 29-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.651506E+10 | 0.00 | 653.31 | 0.539106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18302.20 | 15-MAY-18:01 | 18302.20 | 15-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.939100E+10 | 0.00 | 676.92 | 0.670457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18300.12 | 20-JUN-15:01 | 18300.12 | 20-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.114386E+11 | 0.00 | 718.51 | 0.715766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18008.02 | 09-JUL-08:61 | 15941.98 | 07-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.114219E+11 | 0.00 | 714.89 | 0.719476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17477.88 | 26-AUG-08:61 | 15941.72 | 17-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.923131E+10 | 0.00 | 681.65 | 0.609177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16962.79 | 21-SEP-08:61 | 16962.79 | 21-SEP-08:61 | 0.00 | 0.00 | 0.00 |
October | 0.620084E+10 | 0.00 | 597.42 | 0.508112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17849.83 | 31-OCT-15:01 | 17849.83 | 31-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.230197E+10 | 0.00 | 368.16 | 0.214880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16560.28 | 05-NOV-15:01 | 16560.28 | 05-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.101536E+10 | 0.00 | 194.48 | 0.997396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16558.83 | 04-DEC-16:01 | 16558.83 | 04-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.683451E+11 | 0.00 | 6025.19 | 0.514346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.101536E+10 | 0.00 | 194.48 | 0.997396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16558.83 | 15941.72 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.114386E+11 | 0.00 | 718.51 | 0.719476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18302.20 | 18302.20 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.216814E+09 | 0.00 | 41.11 | 0.213180E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16408.57 | 05-JAN-16:01 | 16408.57 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.478393E+09 | 0.00 | 87.15 | 0.467046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17354.67 | 14-FEB-16:01 | 17354.67 | 14-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.946371E+09 | 0.00 | 207.86 | 0.929081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18589.62 | 30-MAR-18:11 | 18589.62 | 30-MAR-18:11 | 0.00 | 0.00 | 0.00 |
April | 0.311724E+10 | 0.00 | 433.58 | 0.308194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20530.67 | 25-APR-16:21 | 20530.67 | 25-APR-16:21 | 0.00 | 0.00 | 0.00 |
May | 0.521143E+10 | 0.00 | 526.16 | 0.427864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18608.00 | 20-MAY-21:51 | 18608.00 | 20-MAY-21:51 | 0.00 | 0.00 | 0.00 |
June | 0.867770E+10 | 0.00 | 572.72 | 0.636050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19739.55 | 14-JUN-08:21 | 19739.55 | 14-JUN-08:21 | 0.00 | 0.00 | 0.00 |
July | 0.102535E+11 | 0.00 | 590.96 | 0.673441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20665.55 | 04-JUL-08:31 | 17942.87 | 23-JUL-07:51 | 0.00 | 0.00 | 0.00 |
August | 0.943399E+10 | 0.00 | 572.34 | 0.602488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19837.57 | 14-AUG-08:51 | 19048.24 | 23-AUG-17:01 | 0.00 | 0.00 | 0.00 |
September | 0.625284E+10 | 0.00 | 512.21 | 0.384030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17896.85 | 21-SEP-21:51 | 17896.85 | 21-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.282335E+10 | 0.00 | 380.66 | 0.202370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17724.78 | 05-OCT-21:51 | 17724.78 | 05-OCT-21:51 | 0.00 | 0.00 | 0.00 |
November | 0.565994E+09 | 0.00 | 139.32 | 0.511787E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16361.17 | 05-NOV-15:01 | 16361.17 | 05-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.140817E+09 | 0.00 | 26.81 | 0.137432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16358.60 | 29-DEC-16:01 | 16358.60 | 29-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.481185E+11 | 0.00 | 4090.88 | 0.346029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.140817E+09 | 0.00 | 26.81 | 0.137432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16358.60 | 16358.60 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.102535E+11 | 0.00 | 590.96 | 0.673441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20665.55 | 20530.67 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.293638E+11 | 0.00 | 395.50 | 0.293638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58603.71 | 03-JAN-12:40 | 58603.71 | 03-JAN-12:40 | 0.00 | 0.00 | 0.00 |
February | 0.280725E+11 | 0.00 | 407.93 | 0.280725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59885.15 | 14-FEB-13:00 | 59885.15 | 14-FEB-13:00 | 0.00 | 0.00 | 0.00 |
March | 0.270912E+11 | 0.00 | 484.20 | 0.270912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50752.96 | 08-MAR-13:30 | 50752.96 | 08-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.286174E+11 | 0.00 | 597.73 | 0.286174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37332.78 | 13-APR-13:15 | 37332.78 | 13-APR-13:15 | 0.00 | 0.00 | 0.00 |
May | 0.270427E+11 | 0.00 | 660.49 | 0.208158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26820.63 | 13-MAY-13:10 | 26820.63 | 13-MAY-13:10 | 0.00 | 0.00 | 0.00 |
June | 0.356929E+11 | 0.00 | 695.33 | 0.180487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29655.65 | 29-JUN-14:00 | 27682.54 | 28-JUN-17:13 | 0.00 | 0.00 | 0.00 |
July | 0.486341E+11 | 0.00 | 744.00 | 0.240784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33742.66 | 23-JUL-13:30 | 25819.50 | 23-JUL-13:30 | 0.00 | 0.00 | 0.00 |
August | 0.545676E+11 | 0.00 | 744.00 | 0.311159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43465.16 | 22-AUG-13:20 | 42562.94 | 22-AUG-13:30 | 0.00 | 0.00 | 0.00 |
September | 0.565180E+11 | 0.00 | 715.50 | 0.358866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55457.92 | 28-SEP-13:30 | 45430.89 | 28-SEP-13:30 | 0.00 | 0.00 | 0.00 |
October | 0.536119E+11 | 0.00 | 659.11 | 0.466300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59392.61 | 19-OCT-12:30 | 59392.61 | 19-OCT-12:30 | 0.00 | 0.00 | 0.00 |
November | 0.405322E+11 | 0.00 | 518.59 | 0.405322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59074.51 | 20-NOV-13:30 | 59074.51 | 20-NOV-13:30 | 0.00 | 0.00 | 0.00 |
December | 0.326054E+11 | 0.00 | 405.26 | 0.326054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60315.49 | 31-DEC-13:40 | 60315.49 | 31-DEC-13:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.462350E+12 | 0.00 | 7027.63 | 0.362858E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.270427E+11 | 0.00 | 395.50 | 0.180487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26820.63 | 25819.50 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.565180E+11 | 0.00 | 744.00 | 0.466300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60315.49 | 60315.49 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.665157E+09 | 0.00 | 65.11 | 0.665157E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65333.98 | 01-JAN-09:02 | 65333.98 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.241951E+10 | 0.00 | 142.05 | 0.239211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82560.36 | 14-FEB-16:01 | 82560.36 | 14-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.931585E+10 | 0.00 | 354.79 | 0.908770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85823.96 | 08-MAR-16:01 | 85823.96 | 08-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.214308E+11 | 0.00 | 427.62 | 0.213782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92816.71 | 29-APR-15:01 | 92816.71 | 29-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.349759E+11 | 0.00 | 478.53 | 0.307150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93833.68 | 13-MAY-15:01 | 93833.68 | 13-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.533195E+11 | 0.00 | 542.31 | 0.421814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96824.68 | 17-JUN-08:31 | 96824.68 | 17-JUN-08:31 | 0.00 | 0.00 | 0.00 |
July | 0.641590E+11 | 0.00 | 571.62 | 0.435663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100825.65 | 31-JUL-21:51 | 87279.59 | 23-JUL-07:51 | 0.00 | 0.00 | 0.00 |
August | 0.568277E+11 | 0.00 | 533.54 | 0.375138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96122.10 | 14-AUG-08:51 | 84063.08 | 18-AUG-08:51 | 0.00 | 0.00 | 0.00 |
September | 0.373679E+11 | 0.00 | 446.53 | 0.259134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90480.22 | 05-SEP-21:51 | 88630.51 | 30-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.182900E+11 | 0.00 | 389.46 | 0.149770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89146.17 | 09-OCT-15:01 | 89146.17 | 09-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.463838E+10 | 0.00 | 246.45 | 0.434521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80727.98 | 09-NOV-19:02 | 80727.98 | 09-NOV-19:02 | 0.00 | 0.00 | 0.00 |
December | 0.459772E+09 | 0.00 | 44.77 | 0.459772E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77242.74 | 02-DEC-09:02 | 77242.74 | 02-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.303870E+12 | 0.00 | 4242.78 | 0.233195E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.459772E+09 | 0.00 | 44.77 | 0.459772E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65333.98 | 65333.98 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.641590E+11 | 0.00 | 571.62 | 0.435663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100825.65 | 96824.68 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.117208E+10 | 0.00 | 211.35 | 0.112944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14593.35 | 05-JAN-16:01 | 14593.35 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.151826E+10 | 0.00 | 247.51 | 0.142565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15437.57 | 14-FEB-16:01 | 15437.57 | 14-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.300491E+10 | 0.00 | 427.37 | 0.286816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15382.69 | 07-MAR-16:01 | 15382.69 | 07-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.597147E+10 | 0.00 | 636.63 | 0.588887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15920.79 | 29-APR-15:01 | 15920.79 | 29-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.733419E+10 | 0.00 | 699.82 | 0.613189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16080.91 | 15-MAY-18:01 | 16080.91 | 15-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.103142E+11 | 0.00 | 702.86 | 0.765906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16077.57 | 20-JUN-15:01 | 16077.57 | 20-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.126094E+11 | 0.00 | 733.86 | 0.839558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14839.39 | 17-JUL-08:61 | 13753.78 | 04-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.122951E+11 | 0.00 | 732.79 | 0.825276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13979.64 | 23-AUG-08:61 | 13518.38 | 17-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.954486E+10 | 0.00 | 701.03 | 0.656336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14942.43 | 21-SEP-08:61 | 14942.43 | 21-SEP-08:61 | 0.00 | 0.00 | 0.00 |
October | 0.625176E+10 | 0.00 | 620.12 | 0.512674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15684.45 | 31-OCT-15:01 | 15684.45 | 31-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.234599E+10 | 0.00 | 383.12 | 0.217780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14549.48 | 06-NOV-09:02 | 14549.48 | 06-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 0.971707E+09 | 0.00 | 183.94 | 0.935924E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14550.77 | 10-DEC-09:01 | 14550.77 | 10-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.733338E+11 | 0.00 | 6280.40 | 0.565552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.971707E+09 | 0.00 | 183.94 | 0.935924E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13979.64 | 13518.38 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.126094E+11 | 0.00 | 733.86 | 0.839558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16080.91 | 16080.91 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.180227E+09 | 0.00 | 40.67 | 0.159972E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14251.08 | 01-JAN-09:02 | 14251.08 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.350033E+09 | 0.00 | 73.78 | 0.309908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15299.02 | 14-FEB-16:01 | 15299.02 | 14-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.127154E+10 | 0.00 | 261.51 | 0.121133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15244.33 | 07-MAR-16:01 | 15244.33 | 07-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.410732E+10 | 0.00 | 507.25 | 0.403822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17226.86 | 28-APR-08:51 | 17226.86 | 28-APR-08:51 | 0.00 | 0.00 | 0.00 |
May | 0.601397E+10 | 0.00 | 573.77 | 0.497803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17613.66 | 13-MAY-08:51 | 17613.66 | 13-MAY-08:51 | 0.00 | 0.00 | 0.00 |
June | 0.926975E+10 | 0.00 | 596.45 | 0.687981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19672.89 | 20-JUN-08:32 | 19672.89 | 20-JUN-08:32 | 0.00 | 0.00 | 0.00 |
July | 0.110397E+11 | 0.00 | 606.14 | 0.746151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20898.07 | 04-JUL-08:61 | 18000.72 | 04-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.995475E+10 | 0.00 | 587.62 | 0.654651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19993.10 | 14-AUG-08:32 | 17691.79 | 07-AUG-08:32 | 0.00 | 0.00 | 0.00 |
September | 0.640231E+10 | 0.00 | 531.68 | 0.402528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17038.12 | 03-SEP-08:32 | 17038.12 | 03-SEP-08:32 | 0.00 | 0.00 | 0.00 |
October | 0.306644E+10 | 0.00 | 430.08 | 0.224310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15605.21 | 11-OCT-08:51 | 15543.91 | 31-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.585536E+09 | 0.00 | 134.94 | 0.504024E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14419.82 | 07-NOV-09:01 | 14419.82 | 07-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 0.114483E+09 | 0.00 | 36.51 | 0.102221E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14232.70 | 30-DEC-09:02 | 14232.70 | 30-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.523560E+11 | 0.00 | 4380.41 | 0.384599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.114483E+09 | 0.00 | 36.51 | 0.102221E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14232.70 | 14232.70 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.110397E+11 | 0.00 | 606.14 | 0.746151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20898.07 | 19672.89 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.276078E+09 | 0.00 | 143.11 | 0.271467E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4432.17 | 05-JAN-16:01 | 4432.17 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.416462E+09 | 0.00 | 193.29 | 0.401127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4688.83 | 14-FEB-16:01 | 4688.83 | 14-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.647944E+09 | 0.00 | 303.33 | 0.634926E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4671.93 | 07-MAR-16:01 | 4671.93 | 07-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.126918E+10 | 0.00 | 527.18 | 0.125835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4836.55 | 29-APR-15:01 | 4836.55 | 29-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.161243E+10 | 0.00 | 616.45 | 0.134547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4884.26 | 15-MAY-18:01 | 4884.26 | 15-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.241934E+10 | 0.00 | 671.47 | 0.173606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4884.69 | 20-JUN-18:02 | 4884.69 | 20-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.296472E+10 | 0.00 | 718.12 | 0.185728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4972.10 | 09-JUL-08:61 | 4249.48 | 23-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.292828E+10 | 0.00 | 713.65 | 0.184632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4894.55 | 26-AUG-08:61 | 4250.49 | 17-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.225025E+10 | 0.00 | 672.10 | 0.147512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4464.98 | 24-SEP-08:61 | 4420.55 | 21-SEP-08:61 | 0.00 | 0.00 | 0.00 |
October | 0.143680E+10 | 0.00 | 530.85 | 0.116704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4763.71 | 31-OCT-15:01 | 4763.71 | 31-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.497237E+09 | 0.00 | 275.01 | 0.466428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4417.83 | 13-NOV-16:01 | 4417.83 | 13-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.232046E+09 | 0.00 | 135.24 | 0.227159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4419.48 | 04-DEC-16:01 | 4419.48 | 04-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169508E+11 | 0.00 | 5499.81 | 0.126867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.232046E+09 | 0.00 | 135.24 | 0.227159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4417.83 | 4249.48 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.296472E+10 | 0.00 | 718.12 | 0.185728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4972.10 | 4884.69 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 47366672.55 | 0.00 | 32.52 | 46543612.55 | 0.00 | 0.00 | 0.00 | 0.00 | 4371.04 | 05-JAN-16:01 | 4371.04 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.110620E+09 | 0.00 | 66.23 | 0.106570E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4623.06 | 14-FEB-16:01 | 4623.06 | 14-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.211020E+09 | 0.00 | 141.51 | 0.207430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5074.32 | 30-MAR-18:11 | 5074.32 | 30-MAR-18:11 | 0.00 | 0.00 | 0.00 |
April | 0.748327E+09 | 0.00 | 386.01 | 0.739966E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5468.57 | 25-APR-16:21 | 5468.57 | 25-APR-16:21 | 0.00 | 0.00 | 0.00 |
May | 0.131284E+10 | 0.00 | 501.02 | 0.108401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4988.38 | 20-MAY-21:51 | 4988.38 | 20-MAY-21:51 | 0.00 | 0.00 | 0.00 |
June | 0.227854E+10 | 0.00 | 569.47 | 0.167252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5250.37 | 14-JUN-08:21 | 5250.37 | 14-JUN-08:21 | 0.00 | 0.00 | 0.00 |
July | 0.271278E+10 | 0.00 | 593.14 | 0.179052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5526.95 | 04-JUL-08:31 | 4734.61 | 23-JUL-07:51 | 0.00 | 0.00 | 0.00 |
August | 0.247241E+10 | 0.00 | 574.52 | 0.158722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5336.41 | 14-AUG-08:51 | 5058.57 | 23-AUG-17:01 | 0.00 | 0.00 | 0.00 |
September | 0.153442E+10 | 0.00 | 511.77 | 0.937495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4738.23 | 21-SEP-21:51 | 4738.23 | 21-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.605469E+09 | 0.00 | 318.70 | 0.419857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4697.29 | 31-OCT-15:01 | 4697.29 | 31-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.110341E+09 | 0.00 | 78.00 | 0.101248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4489.19 | 02-NOV-18:11 | 4489.19 | 02-NOV-18:11 | 0.00 | 0.00 | 0.00 |
December | 28682467.13 | 0.00 | 22.39 | 27465739.87 | 0.00 | 0.00 | 0.00 | 0.00 | 4357.61 | 29-DEC-16:01 | 4357.61 | 29-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121728E+11 | 0.00 | 3795.29 | 0.872084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 28682467.13 | 0.00 | 22.39 | 27465739.87 | 0.00 | 0.00 | 0.00 | 0.00 | 4357.61 | 4357.61 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.271278E+10 | 0.00 | 593.14 | 0.179052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5526.95 | 5468.57 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.648821E+10 | 0.00 | 386.51 | 0.635434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17996.42 | 05-JAN-16:01 | 17996.42 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.630759E+10 | 0.00 | 397.64 | 0.613195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19037.96 | 14-FEB-16:01 | 19037.96 | 14-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.609083E+10 | 0.00 | 487.90 | 0.596018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18934.52 | 13-MAR-15:01 | 18934.52 | 13-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.682926E+10 | 0.00 | 586.91 | 0.675052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19629.54 | 26-APR-15:01 | 19629.54 | 26-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.706779E+10 | 0.00 | 633.57 | 0.571591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19820.04 | 20-MAY-15:01 | 19820.04 | 20-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.983963E+10 | 0.00 | 671.86 | 0.658516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19818.47 | 19-JUN-18:01 | 19818.47 | 19-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.137864E+11 | 0.00 | 713.87 | 0.857346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19928.21 | 09-JUL-08:61 | 17158.90 | 23-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.147583E+11 | 0.00 | 712.24 | 0.965763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19580.80 | 26-AUG-08:61 | 17577.06 | 17-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.137750E+11 | 0.00 | 681.75 | 0.978559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18281.19 | 21-SEP-08:61 | 18281.19 | 21-SEP-08:61 | 0.00 | 0.00 | 0.00 |
October | 0.121282E+11 | 0.00 | 645.69 | 0.106752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19339.53 | 31-OCT-15:01 | 19339.53 | 31-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.859966E+10 | 0.00 | 523.75 | 0.831025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18016.16 | 08-NOV-16:01 | 18016.16 | 08-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.714957E+10 | 0.00 | 391.49 | 0.703840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17937.76 | 29-DEC-19:01 | 17937.76 | 29-DEC-19:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112820E+12 | 0.00 | 6833.18 | 0.915386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.609083E+10 | 0.00 | 386.51 | 0.571591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17937.76 | 17158.90 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.147583E+11 | 0.00 | 713.87 | 0.106752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19928.21 | 19820.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1186.63 | 922.80 | 263.83 | 1375.97 | 558.03 | 0.00 | 0.00 | 0.00 |
February | 1169.68 | 856.05 | 313.63 | 1383.58 | 513.82 | 0.00 | 0.00 | 0.00 |
March | 869.77 | 530.74 | 339.03 | 1056.98 | 406.21 | 0.00 | 0.00 | 0.00 |
April | 667.98 | 273.75 | 394.23 | 845.23 | 281.22 | 0.00 | 0.00 | 0.00 |
May | 449.56 | 101.70 | 347.85 | 583.64 | 197.10 | 0.00 | 0.00 | 0.00 |
June | 375.82 | 45.13 | 330.69 | 570.53 | 127.17 | 0.00 | 0.00 | 0.00 |
July | 416.00 | 65.27 | 350.73 | 682.36 | 78.64 | 0.00 | 0.00 | 0.00 |
August | 565.91 | 178.49 | 387.42 | 881.10 | 96.44 | 0.00 | 0.00 | 0.00 |
September | 803.38 | 452.23 | 351.15 | 1156.92 | 177.10 | 0.00 | 0.00 | 0.00 |
October | 1082.35 | 796.16 | 286.19 | 1400.40 | 309.75 | 0.00 | 0.00 | 0.00 |
November | 1220.92 | 939.64 | 281.28 | 1457.67 | 444.84 | 0.00 | 0.00 | 0.00 |
December | 1294.03 | 1068.21 | 225.82 | 1506.87 | 572.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 839.96 | 517.41 | 322.55 | 1073.31 | 312.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 375.82 | 45.13 | 225.82 | 570.53 | 78.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1294.03 | 1068.21 | 394.23 | 1506.87 | 572.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3341.48 | 2598.55 | 742.93 | 3832.63 | 1670.49 | 0.00 | 0.00 | 0.00 |
February | 3293.74 | 2410.57 | 883.17 | 3854.03 | 1542.69 | 0.00 | 0.00 | 0.00 |
March | 2449.21 | 1494.52 | 954.68 | 2933.03 | 1235.43 | 0.00 | 0.00 | 0.00 |
April | 1880.99 | 770.86 | 1110.14 | 2341.61 | 855.35 | 0.00 | 0.00 | 0.00 |
May | 1265.92 | 286.39 | 979.54 | 1607.06 | 604.61 | 0.00 | 0.00 | 0.00 |
June | 1058.28 | 127.08 | 931.20 | 1585.69 | 379.03 | 0.00 | 0.00 | 0.00 |
July | 1171.44 | 183.81 | 987.63 | 1908.23 | 226.70 | 0.00 | 0.00 | 0.00 |
August | 1593.56 | 502.60 | 1090.96 | 2466.57 | 276.78 | 0.00 | 0.00 | 0.00 |
September | 2262.26 | 1273.45 | 988.81 | 3236.93 | 515.71 | 0.00 | 0.00 | 0.00 |
October | 3047.83 | 2241.93 | 805.90 | 3914.61 | 917.50 | 0.00 | 0.00 | 0.00 |
November | 3438.04 | 2645.98 | 792.06 | 4065.39 | 1338.56 | 0.00 | 0.00 | 0.00 |
December | 3643.92 | 3008.01 | 635.91 | 4205.16 | 1716.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2365.28 | 1457.01 | 908.27 | 2990.92 | 936.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1058.28 | 127.08 | 635.91 | 1585.69 | 226.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3643.92 | 3008.01 | 1110.14 | 4205.16 | 1716.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4340.77 | 3375.67 | 965.10 | 5054.56 | 2225.76 | 0.00 | 0.00 | 0.00 |
February | 4278.76 | 3131.47 | 1147.29 | 5091.34 | 2051.38 | 0.00 | 0.00 | 0.00 |
March | 3181.66 | 1941.47 | 1240.19 | 3876.76 | 1645.06 | 0.00 | 0.00 | 0.00 |
April | 2443.51 | 1001.39 | 1442.13 | 3111.12 | 1134.61 | 0.00 | 0.00 | 0.00 |
May | 1644.50 | 372.03 | 1272.47 | 2135.39 | 806.95 | 0.00 | 0.00 | 0.00 |
June | 1374.76 | 165.08 | 1209.68 | 2111.61 | 504.80 | 0.00 | 0.00 | 0.00 |
July | 1521.77 | 238.78 | 1282.99 | 2545.25 | 296.06 | 0.00 | 0.00 | 0.00 |
August | 2070.13 | 652.91 | 1417.22 | 3279.64 | 358.01 | 0.00 | 0.00 | 0.00 |
September | 2938.80 | 1654.29 | 1284.51 | 4286.19 | 669.20 | 0.00 | 0.00 | 0.00 |
October | 3959.30 | 2912.39 | 1046.91 | 5171.02 | 1205.50 | 0.00 | 0.00 | 0.00 |
November | 4466.21 | 3437.27 | 1028.93 | 5364.18 | 1771.31 | 0.00 | 0.00 | 0.00 |
December | 4733.66 | 3907.58 | 826.08 | 5546.54 | 2284.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3072.63 | 1892.73 | 1179.90 | 3957.90 | 1241.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1374.76 | 165.08 | 826.08 | 2111.61 | 296.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4733.66 | 3907.58 | 1442.13 | 5546.54 | 2284.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 234.62 | 182.45 | 52.16 | 276.13 | 108.97 | 0.00 | 0.00 | 0.00 |
February | 231.27 | 169.26 | 62.01 | 277.25 | 99.98 | 0.00 | 0.00 | 0.00 |
March | 171.97 | 104.94 | 67.03 | 211.15 | 78.71 | 0.00 | 0.00 | 0.00 |
April | 132.07 | 54.12 | 77.95 | 169.30 | 52.17 | 0.00 | 0.00 | 0.00 |
May | 88.89 | 20.11 | 68.78 | 117.74 | 34.93 | 0.00 | 0.00 | 0.00 |
June | 74.31 | 8.92 | 65.38 | 118.77 | 19.90 | 0.00 | 0.00 | 0.00 |
July | 82.25 | 12.91 | 69.35 | 142.97 | 9.20 | 0.00 | 0.00 | 0.00 |
August | 111.89 | 35.29 | 76.60 | 181.38 | 12.02 | 0.00 | 0.00 | 0.00 |
September | 158.84 | 89.41 | 69.43 | 234.12 | 27.34 | 0.00 | 0.00 | 0.00 |
October | 214.00 | 157.41 | 56.59 | 282.19 | 55.35 | 0.00 | 0.00 | 0.00 |
November | 241.40 | 185.78 | 55.61 | 292.92 | 84.40 | 0.00 | 0.00 | 0.00 |
December | 255.85 | 211.20 | 44.65 | 302.90 | 111.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 166.08 | 102.30 | 63.77 | 216.89 | 57.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.31 | 8.92 | 44.65 | 117.74 | 9.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 255.85 | 211.20 | 77.95 | 302.90 | 111.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.72 | 96.79 | 72.93 | 161.14 | 223.24 | 0.00 | 0.00 | 0.00 |
February | 218.05 | 125.81 | 92.23 | 223.07 | 200.21 | 0.00 | 0.00 | 0.00 |
March | 243.30 | 129.24 | 114.06 | 268.12 | 151.86 | 0.00 | 0.00 | 0.00 |
April | 311.27 | 165.66 | 145.61 | 373.74 | 95.21 | 0.00 | 0.00 | 0.00 |
May | 296.00 | 152.94 | 143.06 | 381.72 | 64.05 | 0.00 | 0.00 | 0.00 |
June | 315.40 | 175.65 | 139.75 | 460.95 | 37.05 | 0.00 | 0.00 | 0.00 |
July | 284.77 | 139.15 | 145.62 | 439.09 | 17.13 | 0.00 | 0.00 | 0.00 |
August | 291.29 | 134.53 | 156.75 | 430.60 | 22.42 | 0.00 | 0.00 | 0.00 |
September | 264.29 | 139.54 | 124.75 | 365.12 | 51.45 | 0.00 | 0.00 | 0.00 |
October | 241.87 | 150.65 | 91.21 | 294.32 | 111.19 | 0.00 | 0.00 | 0.00 |
November | 189.00 | 111.18 | 77.82 | 191.32 | 170.84 | 0.00 | 0.00 | 0.00 |
December | 162.29 | 101.34 | 60.95 | 150.28 | 229.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 248.96 | 135.15 | 113.81 | 311.95 | 114.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.29 | 96.79 | 60.95 | 150.28 | 17.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 315.40 | 175.65 | 156.75 | 460.95 | 229.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.79 | 0.00 | 31.79 | 8.01 | 120.78 | 0.00 | 0.00 | 0.00 |
February | 39.73 | 0.00 | 39.73 | 15.79 | 108.28 | 0.00 | 0.00 | 0.00 |
March | 50.13 | 0.00 | 50.13 | 33.50 | 82.56 | 0.00 | 0.00 | 0.00 |
April | 63.94 | 0.86 | 63.08 | 55.08 | 51.91 | 0.00 | 0.00 | 0.00 |
May | 69.21 | 4.50 | 64.71 | 77.14 | 34.42 | 0.00 | 0.00 | 0.00 |
June | 78.79 | 13.10 | 65.69 | 119.51 | 19.43 | 0.00 | 0.00 | 0.00 |
July | 72.25 | 6.16 | 66.09 | 119.88 | 9.69 | 0.00 | 0.00 | 0.00 |
August | 67.05 | 1.64 | 65.41 | 100.99 | 12.65 | 0.00 | 0.00 | 0.00 |
September | 53.53 | 0.04 | 53.49 | 68.32 | 29.38 | 0.00 | 0.00 | 0.00 |
October | 39.90 | 0.00 | 39.90 | 31.61 | 61.40 | 0.00 | 0.00 | 0.00 |
November | 33.89 | 0.00 | 33.89 | 11.78 | 92.26 | 0.00 | 0.00 | 0.00 |
December | 27.06 | 0.00 | 27.06 | 2.77 | 124.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.32 | 2.19 | 50.12 | 53.90 | 62.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.06 | 0.00 | 27.06 | 2.77 | 9.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.79 | 13.10 | 66.09 | 119.88 | 124.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.72 | 96.79 | 72.93 | 168.16 | 218.23 | 0.00 | 0.00 | 0.00 |
February | 218.05 | 125.81 | 92.23 | 229.95 | 196.02 | 0.00 | 0.00 | 0.00 |
March | 243.30 | 129.24 | 114.06 | 271.81 | 150.40 | 0.00 | 0.00 | 0.00 |
April | 311.27 | 165.66 | 145.61 | 374.13 | 97.70 | 0.00 | 0.00 | 0.00 |
May | 296.00 | 152.94 | 143.06 | 380.49 | 67.14 | 0.00 | 0.00 | 0.00 |
June | 315.40 | 175.65 | 139.75 | 458.05 | 38.80 | 0.00 | 0.00 | 0.00 |
July | 284.77 | 139.15 | 145.62 | 436.45 | 18.62 | 0.00 | 0.00 | 0.00 |
August | 291.29 | 134.53 | 156.75 | 429.00 | 24.53 | 0.00 | 0.00 | 0.00 |
September | 264.29 | 139.54 | 124.75 | 366.48 | 54.77 | 0.00 | 0.00 | 0.00 |
October | 241.87 | 150.65 | 91.21 | 297.57 | 111.98 | 0.00 | 0.00 | 0.00 |
November | 189.00 | 111.18 | 77.82 | 197.76 | 166.36 | 0.00 | 0.00 | 0.00 |
December | 162.29 | 101.34 | 60.95 | 157.16 | 222.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 248.96 | 135.15 | 113.81 | 314.22 | 113.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.29 | 96.79 | 60.95 | 157.16 | 18.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 315.40 | 175.65 | 156.75 | 458.05 | 222.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 187.66 | 145.93 | 41.72 | 208.86 | 110.40 | 0.00 | 0.00 | 0.00 |
February | 184.98 | 135.38 | 49.60 | 209.86 | 103.41 | 0.00 | 0.00 | 0.00 |
March | 137.55 | 83.93 | 53.62 | 157.10 | 84.69 | 0.00 | 0.00 | 0.00 |
April | 105.64 | 43.29 | 62.35 | 124.09 | 60.44 | 0.00 | 0.00 | 0.00 |
May | 71.09 | 16.08 | 55.01 | 82.44 | 44.83 | 0.00 | 0.00 | 0.00 |
June | 59.43 | 7.14 | 52.30 | 82.16 | 29.80 | 0.00 | 0.00 | 0.00 |
July | 65.79 | 10.32 | 55.47 | 100.66 | 19.93 | 0.00 | 0.00 | 0.00 |
August | 89.49 | 28.23 | 61.27 | 132.23 | 23.47 | 0.00 | 0.00 | 0.00 |
September | 127.05 | 71.52 | 55.53 | 175.97 | 38.85 | 0.00 | 0.00 | 0.00 |
October | 171.17 | 125.91 | 45.26 | 214.07 | 63.95 | 0.00 | 0.00 | 0.00 |
November | 193.08 | 148.60 | 44.48 | 222.27 | 90.39 | 0.00 | 0.00 | 0.00 |
December | 204.64 | 168.93 | 35.71 | 230.66 | 113.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 132.83 | 81.83 | 51.01 | 161.42 | 65.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 59.43 | 7.14 | 35.71 | 82.16 | 19.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.64 | 168.93 | 62.35 | 230.66 | 113.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.44 | 0.00 | 25.44 | 6.05 | 98.70 | 0.00 | 0.00 | 0.00 |
February | 31.79 | 0.00 | 31.79 | 12.93 | 87.58 | 0.00 | 0.00 | 0.00 |
March | 40.11 | 0.00 | 40.11 | 28.25 | 65.58 | 0.00 | 0.00 | 0.00 |
April | 51.16 | 0.69 | 50.47 | 47.37 | 39.68 | 0.00 | 0.00 | 0.00 |
May | 55.37 | 3.60 | 51.77 | 65.29 | 26.03 | 0.00 | 0.00 | 0.00 |
June | 63.04 | 10.48 | 52.56 | 100.19 | 14.14 | 0.00 | 0.00 | 0.00 |
July | 57.81 | 4.93 | 52.88 | 100.63 | 6.40 | 0.00 | 0.00 | 0.00 |
August | 53.65 | 1.31 | 52.34 | 85.50 | 8.50 | 0.00 | 0.00 | 0.00 |
September | 42.83 | 0.03 | 42.80 | 58.13 | 21.24 | 0.00 | 0.00 | 0.00 |
October | 31.93 | 0.00 | 31.93 | 27.49 | 46.97 | 0.00 | 0.00 | 0.00 |
November | 27.11 | 0.00 | 27.11 | 9.70 | 74.28 | 0.00 | 0.00 | 0.00 |
December | 21.65 | 0.00 | 21.65 | 1.92 | 102.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.86 | 1.76 | 40.10 | 45.46 | 49.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.65 | 0.00 | 21.65 | 1.92 | 6.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.04 | 10.48 | 52.88 | 100.63 | 102.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 164.57 | 92.11 | 72.46 | 140.49 | 210.78 | 0.00 | 0.00 | 0.00 |
February | 199.30 | 107.13 | 92.17 | 188.16 | 189.82 | 0.00 | 0.00 | 0.00 |
March | 264.85 | 150.88 | 113.96 | 288.11 | 142.29 | 0.00 | 0.00 | 0.00 |
April | 359.28 | 204.45 | 154.83 | 437.25 | 89.71 | 0.00 | 0.00 | 0.00 |
May | 343.23 | 195.50 | 147.73 | 445.41 | 61.32 | 0.00 | 0.00 | 0.00 |
June | 370.16 | 228.00 | 142.16 | 534.35 | 34.08 | 0.00 | 0.00 | 0.00 |
July | 342.34 | 195.70 | 146.64 | 519.47 | 16.45 | 0.00 | 0.00 | 0.00 |
August | 338.83 | 186.76 | 152.07 | 495.03 | 21.14 | 0.00 | 0.00 | 0.00 |
September | 282.54 | 158.10 | 124.45 | 387.08 | 48.46 | 0.00 | 0.00 | 0.00 |
October | 246.16 | 156.32 | 89.85 | 292.37 | 103.23 | 0.00 | 0.00 | 0.00 |
November | 191.45 | 112.31 | 79.14 | 187.30 | 163.89 | 0.00 | 0.00 | 0.00 |
December | 155.95 | 95.12 | 60.82 | 135.09 | 222.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 271.83 | 157.07 | 114.76 | 338.20 | 108.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 155.95 | 92.11 | 60.82 | 135.09 | 16.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 370.16 | 228.00 | 154.83 | 534.35 | 222.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 234.62 | 182.45 | 52.16 | 275.45 | 108.52 | 0.00 | 0.00 | 0.00 |
February | 231.27 | 169.26 | 62.01 | 276.50 | 99.28 | 0.00 | 0.00 | 0.00 |
March | 171.97 | 104.94 | 67.03 | 209.64 | 78.36 | 0.00 | 0.00 | 0.00 |
April | 132.07 | 54.12 | 77.95 | 167.50 | 51.95 | 0.00 | 0.00 | 0.00 |
May | 88.89 | 20.11 | 68.78 | 115.96 | 34.75 | 0.00 | 0.00 | 0.00 |
June | 74.31 | 8.92 | 65.38 | 117.24 | 19.58 | 0.00 | 0.00 | 0.00 |
July | 82.25 | 12.91 | 69.35 | 141.65 | 9.12 | 0.00 | 0.00 | 0.00 |
August | 111.89 | 35.29 | 76.60 | 180.23 | 11.86 | 0.00 | 0.00 | 0.00 |
September | 158.84 | 89.41 | 69.43 | 233.30 | 27.00 | 0.00 | 0.00 | 0.00 |
October | 214.00 | 157.41 | 56.59 | 281.24 | 54.86 | 0.00 | 0.00 | 0.00 |
November | 241.40 | 185.78 | 55.61 | 292.09 | 83.93 | 0.00 | 0.00 | 0.00 |
December | 255.85 | 211.20 | 44.65 | 302.16 | 110.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 166.08 | 102.30 | 63.77 | 215.73 | 57.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.31 | 8.92 | 44.65 | 115.96 | 9.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 255.85 | 211.20 | 77.95 | 302.16 | 110.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.79 | 0.00 | 31.79 | 7.42 | 120.19 | 0.00 | 0.00 | 0.00 |
February | 39.73 | 0.00 | 39.73 | 15.25 | 107.46 | 0.00 | 0.00 | 0.00 |
March | 50.13 | 0.00 | 50.13 | 32.26 | 82.36 | 0.00 | 0.00 | 0.00 |
April | 63.94 | 0.86 | 63.08 | 53.37 | 51.20 | 0.00 | 0.00 | 0.00 |
May | 69.21 | 4.50 | 64.71 | 75.07 | 33.96 | 0.00 | 0.00 | 0.00 |
June | 78.79 | 13.10 | 65.69 | 116.59 | 19.14 | 0.00 | 0.00 | 0.00 |
July | 72.25 | 6.16 | 66.09 | 117.08 | 9.78 | 0.00 | 0.00 | 0.00 |
August | 67.05 | 1.64 | 65.41 | 98.32 | 12.50 | 0.00 | 0.00 | 0.00 |
September | 53.53 | 0.04 | 53.49 | 66.69 | 29.02 | 0.00 | 0.00 | 0.00 |
October | 39.90 | 0.00 | 39.90 | 30.67 | 60.36 | 0.00 | 0.00 | 0.00 |
November | 33.89 | 0.00 | 33.89 | 11.05 | 91.70 | 0.00 | 0.00 | 0.00 |
December | 27.06 | 0.00 | 27.06 | 2.39 | 124.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.32 | 2.19 | 50.12 | 52.38 | 61.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.06 | 0.00 | 27.06 | 2.39 | 9.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.79 | 13.10 | 66.09 | 117.08 | 124.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 164.57 | 92.11 | 72.46 | 146.81 | 204.47 | 0.00 | 0.00 | 0.00 |
February | 199.30 | 107.13 | 92.17 | 194.89 | 184.62 | 0.00 | 0.00 | 0.00 |
March | 264.85 | 150.88 | 113.96 | 292.01 | 140.52 | 0.00 | 0.00 | 0.00 |
April | 359.28 | 204.45 | 154.83 | 438.43 | 91.43 | 0.00 | 0.00 | 0.00 |
May | 343.23 | 195.50 | 147.73 | 443.78 | 64.04 | 0.00 | 0.00 | 0.00 |
June | 370.16 | 228.00 | 142.16 | 528.46 | 35.77 | 0.00 | 0.00 | 0.00 |
July | 342.34 | 195.70 | 146.64 | 513.46 | 18.10 | 0.00 | 0.00 | 0.00 |
August | 338.83 | 186.76 | 152.07 | 490.01 | 23.17 | 0.00 | 0.00 | 0.00 |
September | 282.54 | 158.10 | 124.45 | 386.56 | 51.50 | 0.00 | 0.00 | 0.00 |
October | 246.16 | 156.32 | 89.85 | 295.99 | 103.05 | 0.00 | 0.00 | 0.00 |
November | 191.45 | 112.31 | 79.14 | 193.10 | 158.25 | 0.00 | 0.00 | 0.00 |
December | 155.95 | 95.12 | 60.82 | 139.82 | 212.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 271.83 | 157.07 | 114.76 | 339.27 | 106.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 155.95 | 92.11 | 60.82 | 139.82 | 18.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 370.16 | 228.00 | 154.83 | 528.46 | 212.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.26 | 0.00 | 40.26 | 7.63 | 163.74 | 0.00 | 0.00 | 0.00 |
February | 50.32 | 0.00 | 50.32 | 18.25 | 145.59 | 0.00 | 0.00 | 0.00 |
March | 63.49 | 0.00 | 63.48 | 41.95 | 111.20 | 0.00 | 0.00 | 0.00 |
April | 80.97 | 1.08 | 79.89 | 70.64 | 70.39 | 0.00 | 0.00 | 0.00 |
May | 87.64 | 5.69 | 81.95 | 97.74 | 48.49 | 0.00 | 0.00 | 0.00 |
June | 99.79 | 16.59 | 83.19 | 150.27 | 29.65 | 0.00 | 0.00 | 0.00 |
July | 91.50 | 7.80 | 83.70 | 149.63 | 17.73 | 0.00 | 0.00 | 0.00 |
August | 84.92 | 2.08 | 82.84 | 125.78 | 21.68 | 0.00 | 0.00 | 0.00 |
September | 67.79 | 0.05 | 67.74 | 84.54 | 44.52 | 0.00 | 0.00 | 0.00 |
October | 50.54 | 0.00 | 50.54 | 37.73 | 86.95 | 0.00 | 0.00 | 0.00 |
November | 42.92 | 0.00 | 42.92 | 12.44 | 128.31 | 0.00 | 0.00 | 0.00 |
December | 34.27 | 0.00 | 34.27 | 2.13 | 170.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.26 | 2.78 | 63.48 | 66.82 | 86.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.27 | 0.00 | 34.27 | 2.13 | 17.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 99.79 | 16.59 | 83.70 | 150.27 | 170.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.84 | 0.00 | 14.84 | 2.81 | 60.36 | 0.00 | 0.00 | 0.00 |
February | 18.55 | 0.00 | 18.55 | 6.73 | 53.67 | 0.00 | 0.00 | 0.00 |
March | 23.40 | 0.00 | 23.40 | 15.46 | 40.99 | 0.00 | 0.00 | 0.00 |
April | 29.85 | 0.40 | 29.45 | 26.04 | 25.95 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 2.10 | 30.21 | 36.03 | 17.87 | 0.00 | 0.00 | 0.00 |
June | 36.79 | 6.12 | 30.67 | 55.39 | 10.93 | 0.00 | 0.00 | 0.00 |
July | 33.73 | 2.88 | 30.86 | 55.16 | 6.53 | 0.00 | 0.00 | 0.00 |
August | 31.30 | 0.77 | 30.54 | 46.37 | 7.99 | 0.00 | 0.00 | 0.00 |
September | 24.99 | 0.02 | 24.97 | 31.17 | 16.41 | 0.00 | 0.00 | 0.00 |
October | 18.63 | 0.00 | 18.63 | 13.91 | 32.05 | 0.00 | 0.00 | 0.00 |
November | 15.82 | 0.00 | 15.82 | 4.59 | 47.30 | 0.00 | 0.00 | 0.00 |
December | 12.63 | 0.00 | 12.63 | 0.79 | 62.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.43 | 1.02 | 23.40 | 24.63 | 31.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.63 | 0.00 | 12.63 | 0.79 | 6.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 36.79 | 6.12 | 30.86 | 55.39 | 62.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.47 | 85.13 | 24.34 | 129.51 | 52.80 | 0.00 | 0.00 | 0.00 |
February | 107.91 | 78.97 | 28.93 | 130.43 | 48.41 | 0.00 | 0.00 | 0.00 |
March | 80.24 | 48.96 | 31.28 | 99.23 | 38.80 | 0.00 | 0.00 | 0.00 |
April | 61.62 | 25.25 | 36.37 | 79.46 | 26.79 | 0.00 | 0.00 | 0.00 |
May | 41.47 | 9.38 | 32.09 | 54.75 | 19.07 | 0.00 | 0.00 | 0.00 |
June | 34.67 | 4.16 | 30.51 | 54.44 | 11.89 | 0.00 | 0.00 | 0.00 |
July | 38.38 | 6.02 | 32.36 | 65.25 | 6.79 | 0.00 | 0.00 | 0.00 |
August | 52.21 | 16.47 | 35.74 | 83.48 | 8.37 | 0.00 | 0.00 | 0.00 |
September | 74.12 | 41.72 | 32.40 | 108.62 | 16.25 | 0.00 | 0.00 | 0.00 |
October | 99.85 | 73.45 | 26.40 | 131.47 | 29.18 | 0.00 | 0.00 | 0.00 |
November | 112.64 | 86.69 | 25.95 | 137.27 | 41.82 | 0.00 | 0.00 | 0.00 |
December | 119.38 | 98.55 | 20.83 | 142.28 | 53.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 77.49 | 47.73 | 29.76 | 101.18 | 29.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.67 | 4.16 | 20.83 | 54.44 | 6.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.38 | 98.55 | 36.37 | 142.28 | 53.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 297.13 | 231.07 | 66.06 | 351.52 | 143.30 | 0.00 | 0.00 | 0.00 |
February | 292.88 | 214.35 | 78.53 | 354.01 | 131.39 | 0.00 | 0.00 | 0.00 |
March | 217.79 | 132.89 | 84.89 | 269.33 | 105.32 | 0.00 | 0.00 | 0.00 |
April | 167.26 | 68.55 | 98.72 | 215.67 | 72.70 | 0.00 | 0.00 | 0.00 |
May | 112.57 | 25.47 | 87.10 | 148.60 | 51.77 | 0.00 | 0.00 | 0.00 |
June | 94.10 | 11.30 | 82.80 | 147.77 | 32.26 | 0.00 | 0.00 | 0.00 |
July | 104.17 | 16.34 | 87.82 | 177.09 | 18.42 | 0.00 | 0.00 | 0.00 |
August | 141.70 | 44.69 | 97.01 | 226.57 | 22.72 | 0.00 | 0.00 | 0.00 |
September | 201.16 | 113.24 | 87.93 | 294.83 | 44.11 | 0.00 | 0.00 | 0.00 |
October | 271.02 | 199.35 | 71.66 | 356.82 | 79.19 | 0.00 | 0.00 | 0.00 |
November | 305.72 | 235.28 | 70.43 | 372.57 | 113.51 | 0.00 | 0.00 | 0.00 |
December | 324.02 | 267.48 | 56.55 | 386.19 | 145.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 210.32 | 129.56 | 80.77 | 274.62 | 79.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.10 | 11.30 | 56.55 | 147.77 | 18.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 324.02 | 267.48 | 98.72 | 386.19 | 145.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 234.62 | 182.45 | 52.16 | 275.37 | 108.23 | 0.00 | 0.00 | 0.00 |
February | 231.27 | 169.26 | 62.01 | 276.16 | 99.39 | 0.00 | 0.00 | 0.00 |
March | 171.97 | 104.94 | 67.03 | 210.14 | 78.07 | 0.00 | 0.00 | 0.00 |
April | 132.07 | 54.12 | 77.95 | 168.12 | 51.49 | 0.00 | 0.00 | 0.00 |
May | 88.89 | 20.11 | 68.78 | 116.88 | 34.24 | 0.00 | 0.00 | 0.00 |
June | 74.31 | 8.92 | 65.38 | 118.18 | 19.32 | 0.00 | 0.00 | 0.00 |
July | 82.25 | 12.91 | 69.35 | 142.20 | 8.71 | 0.00 | 0.00 | 0.00 |
August | 111.89 | 35.29 | 76.60 | 180.31 | 11.52 | 0.00 | 0.00 | 0.00 |
September | 158.84 | 89.41 | 69.43 | 232.88 | 26.60 | 0.00 | 0.00 | 0.00 |
October | 214.00 | 157.41 | 56.59 | 281.31 | 54.46 | 0.00 | 0.00 | 0.00 |
November | 241.40 | 185.78 | 55.61 | 292.17 | 83.40 | 0.00 | 0.00 | 0.00 |
December | 255.85 | 211.20 | 44.65 | 302.25 | 110.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 166.08 | 102.30 | 63.77 | 215.99 | 56.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.31 | 8.92 | 44.65 | 116.88 | 8.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 255.85 | 211.20 | 77.95 | 302.25 | 110.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.72 | 96.79 | 72.93 | 160.35 | 221.34 | 0.00 | 0.00 | 0.00 |
February | 218.05 | 125.81 | 92.23 | 221.51 | 198.88 | 0.00 | 0.00 | 0.00 |
March | 243.30 | 129.24 | 114.06 | 266.40 | 150.40 | 0.00 | 0.00 | 0.00 |
April | 311.27 | 165.66 | 145.61 | 371.14 | 93.81 | 0.00 | 0.00 | 0.00 |
May | 296.00 | 152.94 | 143.06 | 379.36 | 62.76 | 0.00 | 0.00 | 0.00 |
June | 315.40 | 175.65 | 139.75 | 458.79 | 36.03 | 0.00 | 0.00 | 0.00 |
July | 284.77 | 139.15 | 145.62 | 436.94 | 16.23 | 0.00 | 0.00 | 0.00 |
August | 291.29 | 134.53 | 156.75 | 428.41 | 21.50 | 0.00 | 0.00 | 0.00 |
September | 264.29 | 139.54 | 124.75 | 363.28 | 50.06 | 0.00 | 0.00 | 0.00 |
October | 241.87 | 150.65 | 91.21 | 293.02 | 109.11 | 0.00 | 0.00 | 0.00 |
November | 189.00 | 111.18 | 77.82 | 190.34 | 168.43 | 0.00 | 0.00 | 0.00 |
December | 162.29 | 101.34 | 60.95 | 149.46 | 227.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 248.96 | 135.15 | 113.81 | 310.25 | 112.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.29 | 96.79 | 60.95 | 149.46 | 16.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 315.40 | 175.65 | 156.75 | 458.79 | 227.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.79 | 0.00 | 31.79 | 8.39 | 119.56 | 0.00 | 0.00 | 0.00 |
February | 39.73 | 0.00 | 39.73 | 15.98 | 107.48 | 0.00 | 0.00 | 0.00 |
March | 50.13 | 0.00 | 50.13 | 33.55 | 81.91 | 0.00 | 0.00 | 0.00 |
April | 63.94 | 0.86 | 63.08 | 54.54 | 51.71 | 0.00 | 0.00 | 0.00 |
May | 69.21 | 4.50 | 64.71 | 76.53 | 34.08 | 0.00 | 0.00 | 0.00 |
June | 78.79 | 13.10 | 65.69 | 118.90 | 19.12 | 0.00 | 0.00 | 0.00 |
July | 72.25 | 6.16 | 66.09 | 119.39 | 9.27 | 0.00 | 0.00 | 0.00 |
August | 67.05 | 1.64 | 65.41 | 100.51 | 12.29 | 0.00 | 0.00 | 0.00 |
September | 53.53 | 0.04 | 53.49 | 68.08 | 28.72 | 0.00 | 0.00 | 0.00 |
October | 39.90 | 0.00 | 39.90 | 31.74 | 60.48 | 0.00 | 0.00 | 0.00 |
November | 33.89 | 0.00 | 33.89 | 12.17 | 90.73 | 0.00 | 0.00 | 0.00 |
December | 27.06 | 0.00 | 27.06 | 2.99 | 123.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.32 | 2.19 | 50.12 | 53.76 | 61.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.06 | 0.00 | 27.06 | 2.99 | 9.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.79 | 13.10 | 66.09 | 119.39 | 123.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.72 | 96.79 | 72.93 | 168.22 | 216.05 | 0.00 | 0.00 | 0.00 |
February | 218.05 | 125.81 | 92.23 | 229.14 | 194.45 | 0.00 | 0.00 | 0.00 |
March | 243.30 | 129.24 | 114.06 | 270.39 | 149.03 | 0.00 | 0.00 | 0.00 |
April | 311.27 | 165.66 | 145.61 | 371.30 | 97.10 | 0.00 | 0.00 | 0.00 |
May | 296.00 | 152.94 | 143.06 | 377.96 | 66.39 | 0.00 | 0.00 | 0.00 |
June | 315.40 | 175.65 | 139.75 | 455.82 | 38.06 | 0.00 | 0.00 | 0.00 |
July | 284.77 | 139.15 | 145.62 | 434.40 | 17.77 | 0.00 | 0.00 | 0.00 |
August | 291.29 | 134.53 | 156.75 | 426.93 | 23.77 | 0.00 | 0.00 | 0.00 |
September | 264.29 | 139.54 | 124.75 | 364.84 | 53.51 | 0.00 | 0.00 | 0.00 |
October | 241.87 | 150.65 | 91.21 | 296.64 | 110.17 | 0.00 | 0.00 | 0.00 |
November | 189.00 | 111.18 | 77.82 | 197.76 | 163.43 | 0.00 | 0.00 | 0.00 |
December | 162.29 | 101.34 | 60.95 | 157.31 | 220.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 248.96 | 135.15 | 113.81 | 312.86 | 112.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.29 | 96.79 | 60.95 | 157.31 | 17.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 315.40 | 175.65 | 156.75 | 455.82 | 220.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 344.09 | 267.59 | 76.50 | 396.81 | 164.85 | 0.00 | 0.00 | 0.00 |
February | 339.17 | 248.23 | 90.95 | 399.26 | 150.53 | 0.00 | 0.00 | 0.00 |
March | 252.21 | 153.90 | 98.31 | 304.96 | 116.60 | 0.00 | 0.00 | 0.00 |
April | 193.70 | 79.38 | 114.32 | 246.85 | 74.57 | 0.00 | 0.00 | 0.00 |
May | 130.36 | 29.49 | 100.87 | 173.73 | 48.71 | 0.00 | 0.00 | 0.00 |
June | 108.98 | 13.09 | 95.89 | 178.05 | 26.73 | 0.00 | 0.00 | 0.00 |
July | 120.63 | 18.93 | 101.70 | 213.08 | 11.56 | 0.00 | 0.00 | 0.00 |
August | 164.10 | 51.76 | 112.34 | 267.78 | 15.66 | 0.00 | 0.00 | 0.00 |
September | 232.96 | 131.13 | 101.82 | 342.01 | 38.21 | 0.00 | 0.00 | 0.00 |
October | 313.85 | 230.86 | 82.99 | 409.77 | 81.26 | 0.00 | 0.00 | 0.00 |
November | 354.03 | 272.47 | 81.56 | 422.84 | 126.84 | 0.00 | 0.00 | 0.00 |
December | 375.23 | 309.75 | 65.48 | 435.89 | 168.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 243.57 | 150.04 | 93.53 | 315.44 | 85.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 108.98 | 13.09 | 65.48 | 173.73 | 11.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 375.23 | 309.75 | 114.32 | 435.89 | 168.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 222.53 | 0.00 | 222.53 | 28.68 | 989.54 | 0.00 | 0.00 | 0.00 |
February | 278.13 | 0.00 | 278.13 | 78.19 | 885.25 | 0.00 | 0.00 | 0.00 |
March | 350.89 | 0.01 | 350.88 | 199.30 | 673.18 | 0.00 | 0.00 | 0.00 |
April | 447.55 | 6.00 | 441.55 | 356.19 | 416.97 | 0.00 | 0.00 | 0.00 |
May | 484.42 | 31.47 | 452.95 | 506.70 | 283.93 | 0.00 | 0.00 | 0.00 |
June | 551.53 | 91.72 | 459.81 | 810.34 | 170.99 | 0.00 | 0.00 | 0.00 |
July | 505.75 | 43.11 | 462.64 | 815.51 | 101.31 | 0.00 | 0.00 | 0.00 |
August | 469.36 | 11.49 | 457.87 | 684.69 | 122.44 | 0.00 | 0.00 | 0.00 |
September | 374.68 | 0.27 | 374.42 | 457.55 | 246.58 | 0.00 | 0.00 | 0.00 |
October | 279.31 | 0.00 | 279.31 | 198.63 | 497.92 | 0.00 | 0.00 | 0.00 |
November | 237.20 | 0.00 | 237.20 | 54.95 | 766.06 | 0.00 | 0.00 | 0.00 |
December | 189.41 | 0.00 | 189.41 | 6.05 | 1035.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 366.21 | 15.36 | 350.85 | 351.20 | 514.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 189.41 | 0.00 | 189.41 | 6.05 | 101.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 551.53 | 91.72 | 462.64 | 815.51 | 1035.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 222.53 | 0.00 | 222.53 | 24.07 | 1013.07 | 0.00 | 0.00 | 0.00 |
February | 278.13 | 0.00 | 278.13 | 71.28 | 904.88 | 0.00 | 0.00 | 0.00 |
March | 350.89 | 0.01 | 350.88 | 190.11 | 687.32 | 0.00 | 0.00 | 0.00 |
April | 447.55 | 6.00 | 441.55 | 347.37 | 426.07 | 0.00 | 0.00 | 0.00 |
May | 484.42 | 31.47 | 452.95 | 498.23 | 290.65 | 0.00 | 0.00 | 0.00 |
June | 551.53 | 91.72 | 459.81 | 802.84 | 175.72 | 0.00 | 0.00 | 0.00 |
July | 505.75 | 43.11 | 462.64 | 808.46 | 105.44 | 0.00 | 0.00 | 0.00 |
August | 469.36 | 11.49 | 457.87 | 677.92 | 127.06 | 0.00 | 0.00 | 0.00 |
September | 374.68 | 0.27 | 374.42 | 451.57 | 253.25 | 0.00 | 0.00 | 0.00 |
October | 279.31 | 0.00 | 279.31 | 192.40 | 509.21 | 0.00 | 0.00 | 0.00 |
November | 237.20 | 0.00 | 237.20 | 49.44 | 784.49 | 0.00 | 0.00 | 0.00 |
December | 189.41 | 0.00 | 189.41 | 4.57 | 1062.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 366.21 | 15.36 | 350.85 | 344.66 | 526.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 189.41 | 0.00 | 189.41 | 4.57 | 105.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 551.53 | 91.72 | 462.64 | 808.46 | 1062.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.79 | 0.00 | 31.79 | 10.75 | 121.93 | 0.00 | 0.00 | 0.00 |
February | 39.73 | 0.00 | 39.73 | 20.40 | 110.31 | 0.00 | 0.00 | 0.00 |
March | 50.13 | 0.00 | 50.13 | 42.61 | 85.09 | 0.00 | 0.00 | 0.00 |
April | 63.94 | 0.86 | 63.08 | 71.45 | 53.78 | 0.00 | 0.00 | 0.00 |
May | 69.21 | 4.50 | 64.71 | 97.13 | 37.84 | 0.00 | 0.00 | 0.00 |
June | 78.79 | 13.10 | 65.69 | 144.41 | 23.76 | 0.00 | 0.00 | 0.00 |
July | 72.25 | 6.16 | 66.09 | 146.26 | 14.44 | 0.00 | 0.00 | 0.00 |
August | 67.05 | 1.64 | 65.41 | 126.76 | 16.92 | 0.00 | 0.00 | 0.00 |
September | 53.53 | 0.04 | 53.49 | 89.35 | 30.24 | 0.00 | 0.00 | 0.00 |
October | 39.90 | 0.00 | 39.90 | 44.52 | 60.30 | 0.00 | 0.00 | 0.00 |
November | 33.89 | 0.00 | 33.89 | 16.46 | 91.99 | 0.00 | 0.00 | 0.00 |
December | 27.06 | 0.00 | 27.06 | 4.22 | 125.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.32 | 2.19 | 50.12 | 68.11 | 64.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.06 | 0.00 | 27.06 | 4.22 | 14.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.79 | 13.10 | 66.09 | 146.26 | 125.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 329.12 | 184.21 | 144.91 | 314.65 | 420.90 | 0.00 | 0.00 | 0.00 |
February | 398.57 | 214.25 | 184.32 | 417.64 | 383.54 | 0.00 | 0.00 | 0.00 |
March | 529.66 | 301.74 | 227.91 | 631.49 | 296.70 | 0.00 | 0.00 | 0.00 |
April | 718.50 | 408.87 | 309.63 | 950.30 | 195.64 | 0.00 | 0.00 | 0.00 |
May | 686.42 | 390.98 | 295.44 | 971.04 | 142.05 | 0.00 | 0.00 | 0.00 |
June | 740.27 | 455.98 | 284.29 | 1160.36 | 89.00 | 0.00 | 0.00 | 0.00 |
July | 684.63 | 391.38 | 293.26 | 1136.41 | 54.15 | 0.00 | 0.00 | 0.00 |
August | 677.61 | 373.49 | 304.12 | 1087.13 | 63.60 | 0.00 | 0.00 | 0.00 |
September | 565.05 | 316.17 | 248.88 | 861.67 | 111.22 | 0.00 | 0.00 | 0.00 |
October | 492.29 | 312.61 | 179.68 | 653.39 | 212.05 | 0.00 | 0.00 | 0.00 |
November | 382.88 | 224.61 | 158.27 | 415.99 | 322.69 | 0.00 | 0.00 | 0.00 |
December | 311.87 | 190.23 | 121.64 | 296.86 | 435.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 543.62 | 314.11 | 229.50 | 742.91 | 226.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 311.87 | 184.21 | 121.64 | 296.86 | 54.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 740.27 | 455.98 | 309.63 | 1160.36 | 435.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 234.62 | 182.45 | 52.16 | 288.35 | 110.17 | 0.00 | 0.00 | 0.00 |
February | 231.27 | 169.26 | 62.01 | 290.55 | 101.51 | 0.00 | 0.00 | 0.00 |
March | 171.97 | 104.94 | 67.03 | 224.85 | 81.37 | 0.00 | 0.00 | 0.00 |
April | 132.07 | 54.12 | 77.95 | 186.32 | 55.27 | 0.00 | 0.00 | 0.00 |
May | 88.89 | 20.11 | 68.78 | 136.61 | 39.42 | 0.00 | 0.00 | 0.00 |
June | 74.31 | 8.92 | 65.38 | 141.30 | 24.91 | 0.00 | 0.00 | 0.00 |
July | 82.25 | 12.91 | 69.35 | 167.44 | 14.55 | 0.00 | 0.00 | 0.00 |
August | 111.89 | 35.29 | 76.60 | 206.03 | 17.21 | 0.00 | 0.00 | 0.00 |
September | 158.84 | 89.41 | 69.43 | 256.30 | 30.20 | 0.00 | 0.00 | 0.00 |
October | 214.00 | 157.41 | 56.59 | 300.76 | 56.64 | 0.00 | 0.00 | 0.00 |
November | 241.40 | 185.78 | 55.61 | 307.33 | 84.62 | 0.00 | 0.00 | 0.00 |
December | 255.85 | 211.20 | 44.65 | 315.19 | 111.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 166.08 | 102.30 | 63.77 | 234.76 | 60.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.31 | 8.92 | 44.65 | 136.61 | 14.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 255.85 | 211.20 | 77.95 | 315.19 | 111.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.26 | 0.00 | 40.26 | 6.43 | 164.95 | 0.00 | 0.00 | 0.00 |
February | 50.32 | 0.00 | 50.32 | 16.17 | 147.09 | 0.00 | 0.00 | 0.00 |
March | 63.49 | 0.00 | 63.48 | 39.70 | 111.27 | 0.00 | 0.00 | 0.00 |
April | 80.97 | 1.08 | 79.89 | 67.73 | 70.27 | 0.00 | 0.00 | 0.00 |
May | 87.64 | 5.69 | 81.95 | 94.37 | 49.00 | 0.00 | 0.00 | 0.00 |
June | 99.79 | 16.59 | 83.19 | 146.67 | 30.63 | 0.00 | 0.00 | 0.00 |
July | 91.50 | 7.80 | 83.70 | 146.13 | 18.83 | 0.00 | 0.00 | 0.00 |
August | 84.92 | 2.08 | 82.84 | 122.53 | 22.76 | 0.00 | 0.00 | 0.00 |
September | 67.79 | 0.05 | 67.74 | 82.05 | 44.83 | 0.00 | 0.00 | 0.00 |
October | 50.54 | 0.00 | 50.54 | 35.97 | 85.81 | 0.00 | 0.00 | 0.00 |
November | 42.92 | 0.00 | 42.92 | 11.23 | 127.43 | 0.00 | 0.00 | 0.00 |
December | 34.27 | 0.00 | 34.27 | 1.56 | 172.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.26 | 2.78 | 63.48 | 64.47 | 86.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.27 | 0.00 | 34.27 | 1.56 | 18.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 99.79 | 16.59 | 83.70 | 146.67 | 172.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.02 | 0.00 | 36.02 | 5.75 | 147.55 | 0.00 | 0.00 | 0.00 |
February | 45.02 | 0.00 | 45.02 | 14.47 | 131.60 | 0.00 | 0.00 | 0.00 |
March | 56.80 | 0.00 | 56.80 | 35.52 | 99.56 | 0.00 | 0.00 | 0.00 |
April | 72.45 | 0.97 | 71.48 | 60.60 | 62.87 | 0.00 | 0.00 | 0.00 |
May | 78.42 | 5.09 | 73.32 | 84.43 | 43.84 | 0.00 | 0.00 | 0.00 |
June | 89.28 | 14.85 | 74.43 | 131.23 | 27.40 | 0.00 | 0.00 | 0.00 |
July | 81.87 | 6.98 | 74.89 | 130.74 | 16.85 | 0.00 | 0.00 | 0.00 |
August | 75.98 | 1.86 | 74.12 | 109.63 | 20.36 | 0.00 | 0.00 | 0.00 |
September | 60.65 | 0.04 | 60.61 | 73.41 | 40.11 | 0.00 | 0.00 | 0.00 |
October | 45.21 | 0.00 | 45.21 | 32.18 | 76.78 | 0.00 | 0.00 | 0.00 |
November | 38.40 | 0.00 | 38.40 | 10.05 | 114.00 | 0.00 | 0.00 | 0.00 |
December | 30.66 | 0.00 | 30.66 | 1.39 | 154.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 59.28 | 2.49 | 56.79 | 57.68 | 77.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 0.00 | 30.66 | 1.39 | 16.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.28 | 14.85 | 74.89 | 131.23 | 154.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 875.90 | 681.16 | 194.74 | 1025.93 | 423.73 | 0.00 | 0.00 | 0.00 |
February | 863.39 | 631.88 | 231.51 | 1031.38 | 389.77 | 0.00 | 0.00 | 0.00 |
March | 642.01 | 391.76 | 250.25 | 783.45 | 310.94 | 0.00 | 0.00 | 0.00 |
April | 493.07 | 202.06 | 291.00 | 624.55 | 214.44 | 0.00 | 0.00 | 0.00 |
May | 331.84 | 75.07 | 256.77 | 426.86 | 154.38 | 0.00 | 0.00 | 0.00 |
June | 277.41 | 33.31 | 244.10 | 425.03 | 98.02 | 0.00 | 0.00 | 0.00 |
July | 307.07 | 48.18 | 258.89 | 511.00 | 57.80 | 0.00 | 0.00 | 0.00 |
August | 417.72 | 131.75 | 285.97 | 656.69 | 70.40 | 0.00 | 0.00 | 0.00 |
September | 593.01 | 333.81 | 259.20 | 858.81 | 131.25 | 0.00 | 0.00 | 0.00 |
October | 798.93 | 587.67 | 211.25 | 1043.68 | 230.73 | 0.00 | 0.00 | 0.00 |
November | 901.21 | 693.59 | 207.62 | 1090.36 | 331.36 | 0.00 | 0.00 | 0.00 |
December | 955.18 | 788.49 | 166.69 | 1127.90 | 431.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 620.01 | 381.92 | 238.09 | 799.13 | 236.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 277.41 | 33.31 | 166.69 | 425.03 | 57.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 955.18 | 788.49 | 291.00 | 1127.90 | 431.70 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.317828E+10 | 0.247164E+10 | 0.706641E+09 | 0.368541E+10 | 0.149462E+10 |
February | 0.282969E+10 | 0.207095E+10 | 0.758744E+09 | 0.334715E+10 | 0.124303E+10 |
March | 0.232958E+10 | 0.142153E+10 | 0.908056E+09 | 0.283103E+10 | 0.108799E+10 |
April | 0.173141E+10 | 0.709555E+09 | 0.102185E+10 | 0.219083E+10 | 0.728918E+09 |
May | 0.120409E+10 | 0.272398E+09 | 0.931695E+09 | 0.156322E+10 | 0.527919E+09 |
June | 0.974117E+09 | 0.116970E+09 | 0.857147E+09 | 0.147882E+10 | 0.329637E+09 |
July | 0.111423E+10 | 0.174830E+09 | 0.939397E+09 | 0.182764E+10 | 0.210629E+09 |
August | 0.151573E+10 | 0.478055E+09 | 0.103767E+10 | 0.235994E+10 | 0.258303E+09 |
September | 0.208236E+10 | 0.117218E+10 | 0.910172E+09 | 0.299874E+10 | 0.459053E+09 |
October | 0.289897E+10 | 0.213243E+10 | 0.766540E+09 | 0.375082E+10 | 0.829639E+09 |
November | 0.316463E+10 | 0.243556E+10 | 0.729074E+09 | 0.377828E+10 | 0.115303E+10 |
December | 0.346594E+10 | 0.286110E+10 | 0.604848E+09 | 0.403601E+10 | 0.153386E+10 |
Annual Sum or Average | 0.264890E+11 | 0.163172E+11 | 0.101718E+11 | 0.338479E+11 | 0.985663E+10 |
Minimum of Months | 0.974117E+09 | 0.116970E+09 | 0.604848E+09 | 0.147882E+10 | 0.210629E+09 |
Maximum of Months | 0.346594E+10 | 0.286110E+10 | 0.103767E+10 | 0.403601E+10 | 0.153386E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.894982E+10 | 0.695996E+10 | 0.198985E+10 | 0.102653E+11 | 0.447425E+10 |
February | 0.796823E+10 | 0.583165E+10 | 0.213657E+10 | 0.932366E+10 | 0.373208E+10 |
March | 0.655995E+10 | 0.400293E+10 | 0.255702E+10 | 0.785583E+10 | 0.330898E+10 |
April | 0.487553E+10 | 0.199806E+10 | 0.287747E+10 | 0.606944E+10 | 0.221707E+10 |
May | 0.339065E+10 | 0.767054E+09 | 0.262359E+10 | 0.430436E+10 | 0.161940E+10 |
June | 0.274305E+10 | 0.329380E+09 | 0.241367E+10 | 0.411012E+10 | 0.982445E+09 |
July | 0.313759E+10 | 0.492310E+09 | 0.264528E+10 | 0.511100E+10 | 0.607194E+09 |
August | 0.426819E+10 | 0.134617E+10 | 0.292202E+10 | 0.660647E+10 | 0.741319E+09 |
September | 0.586378E+10 | 0.330079E+10 | 0.256298E+10 | 0.839011E+10 | 0.133671E+10 |
October | 0.816330E+10 | 0.600478E+10 | 0.215853E+10 | 0.104849E+11 | 0.245743E+10 |
November | 0.891139E+10 | 0.685837E+10 | 0.205302E+10 | 0.105375E+11 | 0.346955E+10 |
December | 0.975987E+10 | 0.805665E+10 | 0.170321E+10 | 0.112631E+11 | 0.459784E+10 |
Annual Sum or Average | 0.745913E+11 | 0.459481E+11 | 0.286432E+11 | 0.943218E+11 | 0.295443E+11 |
Minimum of Months | 0.274305E+10 | 0.329380E+09 | 0.170321E+10 | 0.411012E+10 | 0.607194E+09 |
Maximum of Months | 0.975987E+10 | 0.805665E+10 | 0.292202E+10 | 0.112631E+11 | 0.459784E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116263E+11 | 0.904139E+10 | 0.258493E+10 | 0.135381E+11 | 0.596147E+10 |
February | 0.103512E+11 | 0.757565E+10 | 0.277553E+10 | 0.123170E+11 | 0.496270E+10 |
March | 0.852175E+10 | 0.520003E+10 | 0.332172E+10 | 0.103835E+11 | 0.440612E+10 |
April | 0.633359E+10 | 0.259559E+10 | 0.373800E+10 | 0.806403E+10 | 0.294090E+10 |
May | 0.440464E+10 | 0.996447E+09 | 0.340819E+10 | 0.571943E+10 | 0.216133E+10 |
June | 0.356338E+10 | 0.427884E+09 | 0.313549E+10 | 0.547329E+10 | 0.130845E+10 |
July | 0.407591E+10 | 0.639539E+09 | 0.343637E+10 | 0.681719E+10 | 0.792960E+09 |
August | 0.554462E+10 | 0.174875E+10 | 0.379587E+10 | 0.878419E+10 | 0.958904E+09 |
September | 0.761738E+10 | 0.428792E+10 | 0.332946E+10 | 0.111098E+11 | 0.173458E+10 |
October | 0.106046E+11 | 0.780055E+10 | 0.280405E+10 | 0.138501E+11 | 0.322882E+10 |
November | 0.115764E+11 | 0.890941E+10 | 0.266700E+10 | 0.139040E+11 | 0.459123E+10 |
December | 0.126786E+11 | 0.104661E+11 | 0.221257E+10 | 0.148558E+11 | 0.611989E+10 |
Annual Sum or Average | 0.968984E+11 | 0.596892E+11 | 0.372092E+11 | 0.124816E+12 | 0.391674E+11 |
Minimum of Months | 0.356338E+10 | 0.427884E+09 | 0.221257E+10 | 0.547329E+10 | 0.792960E+09 |
Maximum of Months | 0.126786E+11 | 0.104661E+11 | 0.379587E+10 | 0.148558E+11 | 0.611989E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.628401E+09 | 0.488685E+09 | 0.139716E+09 | 0.739585E+09 | 0.291871E+09 |
February | 0.559480E+09 | 0.409462E+09 | 0.150018E+09 | 0.670723E+09 | 0.241879E+09 |
March | 0.460600E+09 | 0.281060E+09 | 0.179540E+09 | 0.565550E+09 | 0.210828E+09 |
April | 0.342331E+09 | 0.140291E+09 | 0.202040E+09 | 0.438818E+09 | 0.135235E+09 |
May | 0.238072E+09 | 53857719.31 | 0.184215E+09 | 0.315356E+09 | 93558412.32 |
June | 0.192602E+09 | 23127003.62 | 0.169475E+09 | 0.307841E+09 | 51577501.77 |
July | 0.220305E+09 | 34566908.48 | 0.185738E+09 | 0.382931E+09 | 24630535.49 |
August | 0.299688E+09 | 94519723.41 | 0.205168E+09 | 0.485809E+09 | 32196004.07 |
September | 0.411720E+09 | 0.231761E+09 | 0.179959E+09 | 0.606832E+09 | 70853760.04 |
October | 0.573177E+09 | 0.421618E+09 | 0.151560E+09 | 0.755808E+09 | 0.148257E+09 |
November | 0.625703E+09 | 0.481552E+09 | 0.144152E+09 | 0.759237E+09 | 0.218777E+09 |
December | 0.685278E+09 | 0.565688E+09 | 0.119590E+09 | 0.811296E+09 | 0.297508E+09 |
Annual Sum or Average | 0.523736E+10 | 0.322619E+10 | 0.201117E+10 | 0.683979E+10 | 0.181717E+10 |
Minimum of Months | 0.192602E+09 | 23127003.62 | 0.119590E+09 | 0.307841E+09 | 24630535.49 |
Maximum of Months | 0.685278E+09 | 0.565688E+09 | 0.205168E+09 | 0.811296E+09 | 0.297508E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454587E+09 | 0.259253E+09 | 0.195335E+09 | 0.431610E+09 | 0.597932E+09 |
February | 0.527495E+09 | 0.304370E+09 | 0.223125E+09 | 0.539656E+09 | 0.484358E+09 |
March | 0.651650E+09 | 0.346153E+09 | 0.305497E+09 | 0.718127E+09 | 0.406736E+09 |
April | 0.806811E+09 | 0.429395E+09 | 0.377416E+09 | 0.968723E+09 | 0.246776E+09 |
May | 0.792803E+09 | 0.409630E+09 | 0.383173E+09 | 0.102239E+10 | 0.171560E+09 |
June | 0.817524E+09 | 0.455297E+09 | 0.362227E+09 | 0.119477E+10 | 96035358.93 |
July | 0.762720E+09 | 0.372697E+09 | 0.390023E+09 | 0.117605E+10 | 45875023.04 |
August | 0.780187E+09 | 0.360335E+09 | 0.419852E+09 | 0.115331E+10 | 60047762.65 |
September | 0.685042E+09 | 0.361685E+09 | 0.323357E+09 | 0.946396E+09 | 0.133368E+09 |
October | 0.647817E+09 | 0.403510E+09 | 0.244307E+09 | 0.788315E+09 | 0.297822E+09 |
November | 0.489878E+09 | 0.288175E+09 | 0.201704E+09 | 0.495889E+09 | 0.442823E+09 |
December | 0.434675E+09 | 0.271434E+09 | 0.163241E+09 | 0.402503E+09 | 0.614265E+09 |
Annual Sum or Average | 0.785119E+10 | 0.426193E+10 | 0.358926E+10 | 0.983775E+10 | 0.359760E+10 |
Minimum of Months | 0.434675E+09 | 0.259253E+09 | 0.163241E+09 | 0.402503E+09 | 45875023.04 |
Maximum of Months | 0.817524E+09 | 0.455297E+09 | 0.419852E+09 | 0.119477E+10 | 0.614265E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85149799.43 | 0.00 | 85149799.43 | 21448656.72 | 0.323498E+09 |
February | 96123964.78 | 0.00 | 96123964.78 | 38194458.17 | 0.261943E+09 |
March | 0.134266E+09 | 4667.24 | 0.134261E+09 | 89728126.04 | 0.221115E+09 |
April | 0.165726E+09 | 2219973.94 | 0.163506E+09 | 0.142766E+09 | 0.134561E+09 |
May | 0.185361E+09 | 12043444.04 | 0.173317E+09 | 0.206622E+09 | 92203693.31 |
June | 0.204232E+09 | 33964118.59 | 0.170267E+09 | 0.309776E+09 | 50355929.43 |
July | 0.193520E+09 | 16494758.22 | 0.177025E+09 | 0.321098E+09 | 25952936.04 |
August | 0.179595E+09 | 4395223.56 | 0.175200E+09 | 0.270490E+09 | 33881782.10 |
September | 0.138746E+09 | 98869.42 | 0.138647E+09 | 0.177090E+09 | 76160431.93 |
October | 0.106878E+09 | 0.00 | 0.106878E+09 | 84676255.91 | 0.164443E+09 |
November | 87836488.38 | 0.00 | 87836488.38 | 30537393.75 | 0.239126E+09 |
December | 72475366.39 | 0.00 | 72475366.39 | 7420228.05 | 0.334229E+09 |
Annual Sum or Average | 0.164991E+10 | 69221055.01 | 0.158069E+10 | 0.169985E+10 | 0.195747E+10 |
Minimum of Months | 72475366.39 | 0.00 | 72475366.39 | 7420228.05 | 25952936.04 |
Maximum of Months | 0.204232E+09 | 33964118.59 | 0.177025E+09 | 0.321098E+09 | 0.334229E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454587E+09 | 0.259253E+09 | 0.195335E+09 | 0.450389E+09 | 0.584512E+09 |
February | 0.527495E+09 | 0.304370E+09 | 0.223125E+09 | 0.556296E+09 | 0.474210E+09 |
March | 0.651650E+09 | 0.346153E+09 | 0.305497E+09 | 0.728029E+09 | 0.402839E+09 |
April | 0.806811E+09 | 0.429395E+09 | 0.377416E+09 | 0.969741E+09 | 0.253246E+09 |
May | 0.792803E+09 | 0.409630E+09 | 0.383173E+09 | 0.101909E+10 | 0.179824E+09 |
June | 0.817524E+09 | 0.455297E+09 | 0.362227E+09 | 0.118726E+10 | 0.100570E+09 |
July | 0.762720E+09 | 0.372697E+09 | 0.390023E+09 | 0.116900E+10 | 49876614.78 |
August | 0.780187E+09 | 0.360335E+09 | 0.419852E+09 | 0.114903E+10 | 65713859.81 |
September | 0.685042E+09 | 0.361685E+09 | 0.323357E+09 | 0.949905E+09 | 0.141957E+09 |
October | 0.647817E+09 | 0.403510E+09 | 0.244307E+09 | 0.797014E+09 | 0.299919E+09 |
November | 0.489878E+09 | 0.288175E+09 | 0.201704E+09 | 0.512597E+09 | 0.431197E+09 |
December | 0.434675E+09 | 0.271434E+09 | 0.163241E+09 | 0.420925E+09 | 0.596680E+09 |
Annual Sum or Average | 0.785119E+10 | 0.426193E+10 | 0.358926E+10 | 0.990927E+10 | 0.358055E+10 |
Minimum of Months | 0.434675E+09 | 0.259253E+09 | 0.163241E+09 | 0.420925E+09 | 49876614.78 |
Maximum of Months | 0.817524E+09 | 0.455297E+09 | 0.419852E+09 | 0.118726E+10 | 0.596680E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.502621E+09 | 0.390870E+09 | 0.111751E+09 | 0.559403E+09 | 0.295692E+09 |
February | 0.447495E+09 | 0.327504E+09 | 0.119991E+09 | 0.507684E+09 | 0.250181E+09 |
March | 0.368407E+09 | 0.224804E+09 | 0.143603E+09 | 0.420766E+09 | 0.226829E+09 |
April | 0.273811E+09 | 0.112211E+09 | 0.161600E+09 | 0.321637E+09 | 0.156672E+09 |
May | 0.190420E+09 | 43077608.47 | 0.147342E+09 | 0.220797E+09 | 0.120073E+09 |
June | 0.154051E+09 | 18497924.16 | 0.135553E+09 | 0.212955E+09 | 77252727.65 |
July | 0.176209E+09 | 27648028.33 | 0.148561E+09 | 0.269610E+09 | 53369579.98 |
August | 0.239703E+09 | 75600743.78 | 0.164102E+09 | 0.354163E+09 | 62859998.47 |
September | 0.329310E+09 | 0.185372E+09 | 0.143938E+09 | 0.456116E+09 | 0.100703E+09 |
October | 0.458451E+09 | 0.337227E+09 | 0.121224E+09 | 0.573372E+09 | 0.171272E+09 |
November | 0.500463E+09 | 0.385165E+09 | 0.115298E+09 | 0.576122E+09 | 0.234283E+09 |
December | 0.548113E+09 | 0.452460E+09 | 95652933.86 | 0.617796E+09 | 0.305172E+09 |
Annual Sum or Average | 0.418905E+10 | 0.258044E+10 | 0.160862E+10 | 0.509042E+10 | 0.205436E+10 |
Minimum of Months | 0.154051E+09 | 18497924.16 | 95652933.86 | 0.212955E+09 | 53369579.98 |
Maximum of Months | 0.548113E+09 | 0.452460E+09 | 0.164102E+09 | 0.617796E+09 | 0.305172E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68128869.22 | 0.00 | 68128869.22 | 16195445.37 | 0.264368E+09 |
February | 76909365.24 | 0.00 | 76909365.24 | 31276159.92 | 0.211867E+09 |
March | 0.107427E+09 | 3734.29 | 0.107423E+09 | 75669462.80 | 0.175642E+09 |
April | 0.132599E+09 | 1776214.57 | 0.130822E+09 | 0.122772E+09 | 0.102844E+09 |
May | 0.148308E+09 | 9636032.37 | 0.138672E+09 | 0.174864E+09 | 69720318.94 |
June | 0.163407E+09 | 27174896.58 | 0.136232E+09 | 0.259682E+09 | 36660193.15 |
July | 0.154837E+09 | 13197555.76 | 0.141639E+09 | 0.269529E+09 | 17130947.83 |
August | 0.143695E+09 | 3516644.93 | 0.140179E+09 | 0.229001E+09 | 22759690.22 |
September | 0.111011E+09 | 79106.02 | 0.110932E+09 | 0.150681E+09 | 55058644.99 |
October | 85513450.69 | 0.00 | 85513450.69 | 73634662.50 | 0.125813E+09 |
November | 70278505.29 | 0.00 | 70278505.29 | 25141523.85 | 0.192545E+09 |
December | 57987978.73 | 0.00 | 57987978.73 | 5153042.91 | 0.274638E+09 |
Annual Sum or Average | 0.132010E+10 | 55384184.52 | 0.126472E+10 | 0.143360E+10 | 0.154905E+10 |
Minimum of Months | 57987978.73 | 0.00 | 57987978.73 | 5153042.91 | 17130947.83 |
Maximum of Months | 0.163407E+09 | 27174896.58 | 0.141639E+09 | 0.269529E+09 | 0.274638E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.440793E+09 | 0.246716E+09 | 0.194077E+09 | 0.376301E+09 | 0.564546E+09 |
February | 0.482140E+09 | 0.259172E+09 | 0.222967E+09 | 0.455186E+09 | 0.459215E+09 |
March | 0.709366E+09 | 0.404124E+09 | 0.305242E+09 | 0.771678E+09 | 0.381119E+09 |
April | 0.931246E+09 | 0.529931E+09 | 0.401315E+09 | 0.113335E+10 | 0.232528E+09 |
May | 0.919320E+09 | 0.523637E+09 | 0.395684E+09 | 0.119298E+10 | 0.164231E+09 |
June | 0.959453E+09 | 0.590986E+09 | 0.368467E+09 | 0.138502E+10 | 88346517.43 |
July | 0.916926E+09 | 0.524167E+09 | 0.392759E+09 | 0.139135E+10 | 44061328.95 |
August | 0.907525E+09 | 0.500213E+09 | 0.407312E+09 | 0.132590E+10 | 56611474.10 |
September | 0.732353E+09 | 0.409787E+09 | 0.322566E+09 | 0.100332E+10 | 0.125614E+09 |
October | 0.659325E+09 | 0.418683E+09 | 0.240642E+09 | 0.783081E+09 | 0.276484E+09 |
November | 0.496245E+09 | 0.291116E+09 | 0.205129E+09 | 0.485486E+09 | 0.424800E+09 |
December | 0.417691E+09 | 0.254778E+09 | 0.162912E+09 | 0.361835E+09 | 0.596075E+09 |
Annual Sum or Average | 0.857238E+10 | 0.495331E+10 | 0.361907E+10 | 0.106655E+11 | 0.341363E+10 |
Minimum of Months | 0.417691E+09 | 0.246716E+09 | 0.162912E+09 | 0.361835E+09 | 44061328.95 |
Maximum of Months | 0.959453E+09 | 0.590986E+09 | 0.407312E+09 | 0.139135E+10 | 0.596075E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.628401E+09 | 0.488685E+09 | 0.139716E+09 | 0.737754E+09 | 0.290647E+09 |
February | 0.559480E+09 | 0.409462E+09 | 0.150018E+09 | 0.668918E+09 | 0.240171E+09 |
March | 0.460600E+09 | 0.281060E+09 | 0.179540E+09 | 0.561510E+09 | 0.209869E+09 |
April | 0.342331E+09 | 0.140291E+09 | 0.202040E+09 | 0.434152E+09 | 0.134656E+09 |
May | 0.238072E+09 | 53857719.31 | 0.184215E+09 | 0.310584E+09 | 93068157.78 |
June | 0.192602E+09 | 23127003.62 | 0.169475E+09 | 0.303891E+09 | 50757424.27 |
July | 0.220305E+09 | 34566908.48 | 0.185738E+09 | 0.379390E+09 | 24421393.10 |
August | 0.299688E+09 | 94519723.41 | 0.205168E+09 | 0.482735E+09 | 31754021.56 |
September | 0.411720E+09 | 0.231761E+09 | 0.179959E+09 | 0.604722E+09 | 69991318.26 |
October | 0.573177E+09 | 0.421618E+09 | 0.151560E+09 | 0.753260E+09 | 0.146925E+09 |
November | 0.625703E+09 | 0.481552E+09 | 0.144152E+09 | 0.757089E+09 | 0.217535E+09 |
December | 0.685278E+09 | 0.565688E+09 | 0.119590E+09 | 0.809304E+09 | 0.296344E+09 |
Annual Sum or Average | 0.523736E+10 | 0.322619E+10 | 0.201117E+10 | 0.680331E+10 | 0.180614E+10 |
Minimum of Months | 0.192602E+09 | 23127003.62 | 0.119590E+09 | 0.303891E+09 | 24421393.10 |
Maximum of Months | 0.685278E+09 | 0.565688E+09 | 0.205168E+09 | 0.809304E+09 | 0.296344E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85149799.43 | 0.00 | 85149799.43 | 19871142.74 | 0.321916E+09 |
February | 96123964.78 | 0.00 | 96123964.78 | 36886678.21 | 0.259956E+09 |
March | 0.134266E+09 | 4667.24 | 0.134261E+09 | 86403142.80 | 0.220580E+09 |
April | 0.165726E+09 | 2219973.94 | 0.163506E+09 | 0.138331E+09 | 0.132717E+09 |
May | 0.185361E+09 | 12043444.04 | 0.173317E+09 | 0.201069E+09 | 90963326.60 |
June | 0.204232E+09 | 33964118.59 | 0.170267E+09 | 0.302207E+09 | 49599903.36 |
July | 0.193520E+09 | 16494758.22 | 0.177025E+09 | 0.313590E+09 | 26190110.96 |
August | 0.179595E+09 | 4395223.56 | 0.175200E+09 | 0.263335E+09 | 33474835.88 |
September | 0.138746E+09 | 98869.42 | 0.138647E+09 | 0.172856E+09 | 75213645.13 |
October | 0.106878E+09 | 0.00 | 0.106878E+09 | 82140661.21 | 0.161675E+09 |
November | 87836488.38 | 0.00 | 87836488.38 | 28653442.74 | 0.237699E+09 |
December | 72475366.39 | 0.00 | 72475366.39 | 6391620.95 | 0.333280E+09 |
Annual Sum or Average | 0.164991E+10 | 69221055.01 | 0.158069E+10 | 0.165173E+10 | 0.194327E+10 |
Minimum of Months | 72475366.39 | 0.00 | 72475366.39 | 6391620.95 | 26190110.96 |
Maximum of Months | 0.204232E+09 | 33964118.59 | 0.177025E+09 | 0.313590E+09 | 0.333280E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.440793E+09 | 0.246716E+09 | 0.194077E+09 | 0.393214E+09 | 0.547659E+09 |
February | 0.482140E+09 | 0.259172E+09 | 0.222967E+09 | 0.471472E+09 | 0.446638E+09 |
March | 0.709366E+09 | 0.404124E+09 | 0.305242E+09 | 0.782126E+09 | 0.376366E+09 |
April | 0.931246E+09 | 0.529931E+09 | 0.401315E+09 | 0.113641E+10 | 0.236998E+09 |
May | 0.919320E+09 | 0.523637E+09 | 0.395684E+09 | 0.118862E+10 | 0.171538E+09 |
June | 0.959453E+09 | 0.590986E+09 | 0.368467E+09 | 0.136978E+10 | 92709936.60 |
July | 0.916926E+09 | 0.524167E+09 | 0.392759E+09 | 0.137526E+10 | 48484421.37 |
August | 0.907525E+09 | 0.500213E+09 | 0.407312E+09 | 0.131244E+10 | 62049591.95 |
September | 0.732353E+09 | 0.409787E+09 | 0.322566E+09 | 0.100195E+10 | 0.133490E+09 |
October | 0.659325E+09 | 0.418683E+09 | 0.240642E+09 | 0.792785E+09 | 0.276020E+09 |
November | 0.496245E+09 | 0.291116E+09 | 0.205129E+09 | 0.500520E+09 | 0.410192E+09 |
December | 0.417691E+09 | 0.254778E+09 | 0.162912E+09 | 0.374481E+09 | 0.570208E+09 |
Annual Sum or Average | 0.857238E+10 | 0.495331E+10 | 0.361907E+10 | 0.106991E+11 | 0.337235E+10 |
Minimum of Months | 0.417691E+09 | 0.246716E+09 | 0.162912E+09 | 0.374481E+09 | 48484421.37 |
Maximum of Months | 0.959453E+09 | 0.590986E+09 | 0.407312E+09 | 0.137526E+10 | 0.570208E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107837E+09 | 0.00 | 0.107837E+09 | 20427888.15 | 0.438566E+09 |
February | 0.121735E+09 | 0.00 | 0.121735E+09 | 44147163.79 | 0.352221E+09 |
March | 0.170039E+09 | 5910.77 | 0.170034E+09 | 0.112362E+09 | 0.297836E+09 |
April | 0.209882E+09 | 2811456.93 | 0.207070E+09 | 0.183091E+09 | 0.182454E+09 |
May | 0.234747E+09 | 15252261.97 | 0.219495E+09 | 0.261774E+09 | 0.129865E+09 |
June | 0.258646E+09 | 43013413.18 | 0.215633E+09 | 0.389494E+09 | 76855717.08 |
July | 0.245081E+09 | 20889570.53 | 0.224191E+09 | 0.400759E+09 | 47480380.18 |
August | 0.227446E+09 | 5566273.31 | 0.221880E+09 | 0.336894E+09 | 58064335.93 |
September | 0.175713E+09 | 125211.88 | 0.175587E+09 | 0.219137E+09 | 0.115384E+09 |
October | 0.135354E+09 | 0.00 | 0.135354E+09 | 0.101055E+09 | 0.232882E+09 |
November | 0.111239E+09 | 0.00 | 0.111239E+09 | 32248353.21 | 0.332590E+09 |
December | 91785478.59 | 0.00 | 91785478.59 | 5703598.66 | 0.456180E+09 |
Annual Sum or Average | 0.208951E+10 | 87664098.56 | 0.200184E+10 | 0.210709E+10 | 0.272038E+10 |
Minimum of Months | 91785478.59 | 0.00 | 91785478.59 | 5703598.66 | 47480380.18 |
Maximum of Months | 0.258646E+09 | 43013413.18 | 0.224191E+09 | 0.400759E+09 | 0.456180E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 39753127.47 | 0.00 | 39753127.47 | 7530565.42 | 0.161673E+09 |
February | 44876538.17 | 0.00 | 44876538.17 | 16274472.56 | 0.129842E+09 |
March | 62683574.03 | 2178.95 | 62681395.08 | 41421362.45 | 0.109795E+09 |
April | 77371112.45 | 1036419.44 | 76334693.01 | 67494974.19 | 67259988.98 |
May | 86537607.89 | 5622615.31 | 80914992.58 | 96500753.05 | 47873676.53 |
June | 95347742.98 | 15856525.14 | 79491217.84 | 0.143584E+09 | 28332199.66 |
July | 90346984.62 | 7700760.67 | 82646223.96 | 0.147737E+09 | 17503234.14 |
August | 83846123.30 | 2051958.82 | 81794164.48 | 0.124193E+09 | 21404918.48 |
September | 64774917.93 | 46158.28 | 64728759.65 | 80782880.69 | 42535143.68 |
October | 49897013.47 | 0.00 | 49897013.47 | 37253095.06 | 85850062.03 |
November | 41007437.97 | 0.00 | 41007437.97 | 11888078.29 | 0.122606E+09 |
December | 33835927.95 | 0.00 | 33835927.95 | 2102582.63 | 0.168167E+09 |
Annual Sum or Average | 0.770278E+09 | 32316616.61 | 0.737961E+09 | 0.776762E+09 | 0.100284E+10 |
Minimum of Months | 33835927.95 | 0.00 | 33835927.95 | 2102582.63 | 17503234.14 |
Maximum of Months | 95347742.98 | 15856525.14 | 82646223.96 | 0.147737E+09 | 0.168167E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.293209E+09 | 0.228018E+09 | 65190972.91 | 0.346887E+09 | 0.141412E+09 |
February | 0.261051E+09 | 0.191053E+09 | 69997867.18 | 0.315535E+09 | 0.117109E+09 |
March | 0.214914E+09 | 0.131142E+09 | 83772641.65 | 0.265774E+09 | 0.103935E+09 |
April | 0.159730E+09 | 65459272.62 | 94271166.94 | 0.205964E+09 | 69429883.88 |
May | 0.111084E+09 | 25129794.80 | 85953812.25 | 0.146644E+09 | 51083306.66 |
June | 89867461.62 | 10790966.69 | 79076494.93 | 0.141116E+09 | 30807773.76 |
July | 0.102793E+09 | 16128780.20 | 86664444.25 | 0.174755E+09 | 18179258.50 |
August | 0.139833E+09 | 44102522.06 | 95730758.02 | 0.223581E+09 | 22416345.62 |
September | 0.192107E+09 | 0.108139E+09 | 83967969.21 | 0.281553E+09 | 42120180.85 |
October | 0.267442E+09 | 0.196725E+09 | 70717194.11 | 0.352118E+09 | 78144853.72 |
November | 0.291951E+09 | 0.224690E+09 | 67260585.57 | 0.355800E+09 | 0.108396E+09 |
December | 0.319748E+09 | 0.263948E+09 | 55800186.81 | 0.381091E+09 | 0.143680E+09 |
Annual Sum or Average | 0.244373E+10 | 0.150533E+10 | 0.938404E+09 | 0.319082E+10 | 0.926713E+09 |
Minimum of Months | 89867461.62 | 10790966.69 | 55800186.81 | 0.141116E+09 | 18179258.50 |
Maximum of Months | 0.319748E+09 | 0.263948E+09 | 95730758.02 | 0.381091E+09 | 0.143680E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.795830E+09 | 0.618889E+09 | 0.176942E+09 | 0.941521E+09 | 0.383821E+09 |
February | 0.708546E+09 | 0.518558E+09 | 0.189989E+09 | 0.856425E+09 | 0.317857E+09 |
March | 0.583321E+09 | 0.355945E+09 | 0.227376E+09 | 0.721365E+09 | 0.282100E+09 |
April | 0.433541E+09 | 0.177670E+09 | 0.255871E+09 | 0.559028E+09 | 0.188447E+09 |
May | 0.301504E+09 | 68207403.27 | 0.233296E+09 | 0.398022E+09 | 0.138651E+09 |
June | 0.243919E+09 | 29288890.85 | 0.214630E+09 | 0.383019E+09 | 83618599.59 |
July | 0.279002E+09 | 43776808.53 | 0.235225E+09 | 0.474322E+09 | 49342226.07 |
August | 0.379536E+09 | 0.119703E+09 | 0.259833E+09 | 0.606844E+09 | 60842344.81 |
September | 0.521417E+09 | 0.293511E+09 | 0.227906E+09 | 0.764192E+09 | 0.114323E+09 |
October | 0.725893E+09 | 0.533952E+09 | 0.191941E+09 | 0.955719E+09 | 0.212101E+09 |
November | 0.792414E+09 | 0.609855E+09 | 0.182559E+09 | 0.965714E+09 | 0.294209E+09 |
December | 0.867861E+09 | 0.716408E+09 | 0.151453E+09 | 0.103436E+10 | 0.389977E+09 |
Annual Sum or Average | 0.663278E+10 | 0.408576E+10 | 0.254702E+10 | 0.866053E+10 | 0.251529E+10 |
Minimum of Months | 0.243919E+09 | 29288890.85 | 0.151453E+09 | 0.383019E+09 | 49342226.07 |
Maximum of Months | 0.867861E+09 | 0.716408E+09 | 0.259833E+09 | 0.103436E+10 | 0.389977E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.628401E+09 | 0.488685E+09 | 0.139716E+09 | 0.737550E+09 | 0.289891E+09 |
February | 0.559480E+09 | 0.409462E+09 | 0.150018E+09 | 0.668095E+09 | 0.240441E+09 |
March | 0.460600E+09 | 0.281060E+09 | 0.179540E+09 | 0.562834E+09 | 0.209104E+09 |
April | 0.342331E+09 | 0.140291E+09 | 0.202040E+09 | 0.435778E+09 | 0.133462E+09 |
May | 0.238072E+09 | 53857719.31 | 0.184215E+09 | 0.313062E+09 | 91703466.59 |
June | 0.192602E+09 | 23127003.62 | 0.169475E+09 | 0.306319E+09 | 50082382.92 |
July | 0.220305E+09 | 34566908.48 | 0.185738E+09 | 0.380860E+09 | 23335344.65 |
August | 0.299688E+09 | 94519723.41 | 0.205168E+09 | 0.482936E+09 | 30863282.41 |
September | 0.411720E+09 | 0.231761E+09 | 0.179959E+09 | 0.603626E+09 | 68949163.71 |
October | 0.573177E+09 | 0.421618E+09 | 0.151560E+09 | 0.753461E+09 | 0.145863E+09 |
November | 0.625703E+09 | 0.481552E+09 | 0.144152E+09 | 0.757299E+09 | 0.216176E+09 |
December | 0.685278E+09 | 0.565688E+09 | 0.119590E+09 | 0.809545E+09 | 0.295095E+09 |
Annual Sum or Average | 0.523736E+10 | 0.322619E+10 | 0.201117E+10 | 0.681136E+10 | 0.179496E+10 |
Minimum of Months | 0.192602E+09 | 23127003.62 | 0.119590E+09 | 0.306319E+09 | 23335344.65 |
Maximum of Months | 0.685278E+09 | 0.565688E+09 | 0.205168E+09 | 0.809545E+09 | 0.295095E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454587E+09 | 0.259253E+09 | 0.195335E+09 | 0.429481E+09 | 0.592829E+09 |
February | 0.527495E+09 | 0.304370E+09 | 0.223125E+09 | 0.535867E+09 | 0.481142E+09 |
March | 0.651650E+09 | 0.346153E+09 | 0.305497E+09 | 0.713535E+09 | 0.402830E+09 |
April | 0.806811E+09 | 0.429395E+09 | 0.377416E+09 | 0.961992E+09 | 0.243158E+09 |
May | 0.792803E+09 | 0.409630E+09 | 0.383173E+09 | 0.101609E+10 | 0.168085E+09 |
June | 0.817524E+09 | 0.455297E+09 | 0.362227E+09 | 0.118917E+10 | 93380964.41 |
July | 0.762720E+09 | 0.372697E+09 | 0.390023E+09 | 0.117030E+10 | 43483749.03 |
August | 0.780187E+09 | 0.360335E+09 | 0.419852E+09 | 0.114745E+10 | 57592097.52 |
September | 0.685042E+09 | 0.361685E+09 | 0.323357E+09 | 0.941616E+09 | 0.129752E+09 |
October | 0.647817E+09 | 0.403510E+09 | 0.244307E+09 | 0.784821E+09 | 0.292241E+09 |
November | 0.489878E+09 | 0.288175E+09 | 0.201704E+09 | 0.493373E+09 | 0.436564E+09 |
December | 0.434675E+09 | 0.271434E+09 | 0.163241E+09 | 0.400309E+09 | 0.608062E+09 |
Annual Sum or Average | 0.785119E+10 | 0.426193E+10 | 0.358926E+10 | 0.978400E+10 | 0.354912E+10 |
Minimum of Months | 0.434675E+09 | 0.259253E+09 | 0.163241E+09 | 0.400309E+09 | 43483749.03 |
Maximum of Months | 0.817524E+09 | 0.455297E+09 | 0.419852E+09 | 0.118917E+10 | 0.608062E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85149799.43 | 0.00 | 85149799.43 | 22480249.31 | 0.320233E+09 |
February | 96123964.78 | 0.00 | 96123964.78 | 38651348.79 | 0.260026E+09 |
March | 0.134266E+09 | 4667.24 | 0.134261E+09 | 89850928.60 | 0.219391E+09 |
April | 0.165726E+09 | 2219973.94 | 0.163506E+09 | 0.141369E+09 | 0.134028E+09 |
May | 0.185361E+09 | 12043444.04 | 0.173317E+09 | 0.204982E+09 | 91270486.36 |
June | 0.204232E+09 | 33964118.59 | 0.170267E+09 | 0.308177E+09 | 49570754.42 |
July | 0.193520E+09 | 16494758.22 | 0.177025E+09 | 0.319779E+09 | 24823637.59 |
August | 0.179595E+09 | 4395223.56 | 0.175200E+09 | 0.269203E+09 | 32912369.12 |
September | 0.138746E+09 | 98869.42 | 0.138647E+09 | 0.176471E+09 | 74450334.05 |
October | 0.106878E+09 | 0.00 | 0.106878E+09 | 85001228.32 | 0.161993E+09 |
November | 87836488.38 | 0.00 | 87836488.38 | 31542234.92 | 0.235177E+09 |
December | 72475366.39 | 0.00 | 72475366.39 | 8019145.58 | 0.330170E+09 |
Annual Sum or Average | 0.164991E+10 | 69221055.01 | 0.158069E+10 | 0.169553E+10 | 0.193404E+10 |
Minimum of Months | 72475366.39 | 0.00 | 72475366.39 | 8019145.58 | 24823637.59 |
Maximum of Months | 0.204232E+09 | 33964118.59 | 0.177025E+09 | 0.319779E+09 | 0.330170E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454587E+09 | 0.259253E+09 | 0.195335E+09 | 0.450550E+09 | 0.578663E+09 |
February | 0.527495E+09 | 0.304370E+09 | 0.223125E+09 | 0.554332E+09 | 0.470407E+09 |
March | 0.651650E+09 | 0.346153E+09 | 0.305497E+09 | 0.724224E+09 | 0.399169E+09 |
April | 0.806811E+09 | 0.429395E+09 | 0.377416E+09 | 0.962404E+09 | 0.251678E+09 |
May | 0.792803E+09 | 0.409630E+09 | 0.383173E+09 | 0.101232E+10 | 0.177807E+09 |
June | 0.817524E+09 | 0.455297E+09 | 0.362227E+09 | 0.118149E+10 | 98642930.46 |
July | 0.762720E+09 | 0.372697E+09 | 0.390023E+09 | 0.116350E+10 | 47599606.92 |
August | 0.780187E+09 | 0.360335E+09 | 0.419852E+09 | 0.114348E+10 | 63660673.93 |
September | 0.685042E+09 | 0.361685E+09 | 0.323357E+09 | 0.945668E+09 | 0.138708E+09 |
October | 0.647817E+09 | 0.403510E+09 | 0.244307E+09 | 0.794514E+09 | 0.295070E+09 |
November | 0.489878E+09 | 0.288175E+09 | 0.201704E+09 | 0.512590E+09 | 0.423603E+09 |
December | 0.434675E+09 | 0.271434E+09 | 0.163241E+09 | 0.421348E+09 | 0.589937E+09 |
Annual Sum or Average | 0.785119E+10 | 0.426193E+10 | 0.358926E+10 | 0.986641E+10 | 0.353495E+10 |
Minimum of Months | 0.434675E+09 | 0.259253E+09 | 0.163241E+09 | 0.421348E+09 | 47599606.92 |
Maximum of Months | 0.817524E+09 | 0.455297E+09 | 0.419852E+09 | 0.118149E+10 | 0.589937E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.921610E+09 | 0.716703E+09 | 0.204907E+09 | 0.106281E+10 | 0.441532E+09 |
February | 0.820531E+09 | 0.600515E+09 | 0.220016E+09 | 0.965883E+09 | 0.364166E+09 |
March | 0.675515E+09 | 0.412202E+09 | 0.263313E+09 | 0.816806E+09 | 0.312301E+09 |
April | 0.502062E+09 | 0.205750E+09 | 0.296311E+09 | 0.639830E+09 | 0.193292E+09 |
May | 0.349156E+09 | 78987514.10 | 0.270168E+09 | 0.465316E+09 | 0.130470E+09 |
June | 0.282470E+09 | 33917970.31 | 0.248552E+09 | 0.461504E+09 | 69275107.72 |
July | 0.323098E+09 | 50695688.68 | 0.272402E+09 | 0.570702E+09 | 30970245.91 |
August | 0.439521E+09 | 0.138622E+09 | 0.300899E+09 | 0.717231E+09 | 41945788.89 |
September | 0.603826E+09 | 0.339900E+09 | 0.263927E+09 | 0.886492E+09 | 99039860.73 |
October | 0.840620E+09 | 0.618343E+09 | 0.222277E+09 | 0.109754E+10 | 0.217650E+09 |
November | 0.917654E+09 | 0.706242E+09 | 0.211412E+09 | 0.109600E+10 | 0.328773E+09 |
December | 0.100503E+10 | 0.829635E+09 | 0.175390E+09 | 0.116748E+10 | 0.451332E+09 |
Annual Sum or Average | 0.768109E+10 | 0.473151E+10 | 0.294957E+10 | 0.994760E+10 | 0.268075E+10 |
Minimum of Months | 0.282470E+09 | 33917970.31 | 0.175390E+09 | 0.461504E+09 | 30970245.91 |
Maximum of Months | 0.100503E+10 | 0.829635E+09 | 0.300899E+09 | 0.116748E+10 | 0.451332E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.596026E+09 | 0.00 | 0.596026E+09 | 76805015.87 | 0.265040E+10 |
February | 0.672842E+09 | 0.00 | 0.672842E+09 | 0.189159E+09 | 0.214159E+10 |
March | 0.939826E+09 | 32669.46 | 0.939794E+09 | 0.533815E+09 | 0.180304E+10 |
April | 0.116004E+10 | 15539229.06 | 0.114450E+10 | 0.923233E+09 | 0.108077E+10 |
May | 0.129747E+10 | 84300915.40 | 0.121317E+10 | 0.135714E+10 | 0.760487E+09 |
June | 0.142957E+10 | 0.237740E+09 | 0.119183E+10 | 0.210040E+10 | 0.443199E+09 |
July | 0.135459E+10 | 0.115459E+09 | 0.123913E+10 | 0.218427E+10 | 0.271345E+09 |
August | 0.125712E+10 | 30765399.66 | 0.122636E+10 | 0.183387E+10 | 0.327947E+09 |
September | 0.971182E+09 | 692059.69 | 0.970490E+09 | 0.118598E+10 | 0.639141E+09 |
October | 0.748115E+09 | 0.00 | 0.748115E+09 | 0.532000E+09 | 0.133364E+10 |
November | 0.614832E+09 | 0.00 | 0.614832E+09 | 0.142438E+09 | 0.198562E+10 |
December | 0.507308E+09 | 0.00 | 0.507308E+09 | 16199926.95 | 0.277261E+10 |
Annual Sum or Average | 0.115489E+11 | 0.484529E+09 | 0.110644E+11 | 0.110753E+11 | 0.162098E+11 |
Minimum of Months | 0.507308E+09 | 0.00 | 0.507308E+09 | 16199926.95 | 0.271345E+09 |
Maximum of Months | 0.142957E+10 | 0.237740E+09 | 0.123913E+10 | 0.218427E+10 | 0.277261E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.596026E+09 | 0.00 | 0.596026E+09 | 64470130.52 | 0.271340E+10 |
February | 0.672842E+09 | 0.00 | 0.672842E+09 | 0.172443E+09 | 0.218908E+10 |
March | 0.939826E+09 | 32669.46 | 0.939794E+09 | 0.509191E+09 | 0.184092E+10 |
April | 0.116004E+10 | 15539229.06 | 0.114450E+10 | 0.900380E+09 | 0.110436E+10 |
May | 0.129747E+10 | 84300915.40 | 0.121317E+10 | 0.133445E+10 | 0.778483E+09 |
June | 0.142957E+10 | 0.237740E+09 | 0.119183E+10 | 0.208097E+10 | 0.455473E+09 |
July | 0.135459E+10 | 0.115459E+09 | 0.123913E+10 | 0.216539E+10 | 0.282406E+09 |
August | 0.125712E+10 | 30765399.66 | 0.122636E+10 | 0.181574E+10 | 0.340312E+09 |
September | 0.971182E+09 | 692059.69 | 0.970490E+09 | 0.117047E+10 | 0.656422E+09 |
October | 0.748115E+09 | 0.00 | 0.748115E+09 | 0.515328E+09 | 0.136386E+10 |
November | 0.614832E+09 | 0.00 | 0.614832E+09 | 0.128148E+09 | 0.203339E+10 |
December | 0.507308E+09 | 0.00 | 0.507308E+09 | 12244213.16 | 0.284485E+10 |
Annual Sum or Average | 0.115489E+11 | 0.484529E+09 | 0.110644E+11 | 0.108692E+11 | 0.166030E+11 |
Minimum of Months | 0.507308E+09 | 0.00 | 0.507308E+09 | 12244213.16 | 0.282406E+09 |
Maximum of Months | 0.142957E+10 | 0.237740E+09 | 0.123913E+10 | 0.216539E+10 | 0.284485E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85149799.43 | 0.00 | 85149799.43 | 28782753.88 | 0.326583E+09 |
February | 96123964.78 | 0.00 | 96123964.78 | 49354608.13 | 0.266872E+09 |
March | 0.134266E+09 | 4667.24 | 0.134261E+09 | 0.114120E+09 | 0.227900E+09 |
April | 0.165726E+09 | 2219973.94 | 0.163506E+09 | 0.185205E+09 | 0.139388E+09 |
May | 0.185361E+09 | 12043444.04 | 0.173317E+09 | 0.260160E+09 | 0.101350E+09 |
June | 0.204232E+09 | 33964118.59 | 0.170267E+09 | 0.374306E+09 | 61581756.99 |
July | 0.193520E+09 | 16494758.22 | 0.177025E+09 | 0.391736E+09 | 38683510.37 |
August | 0.179595E+09 | 4395223.56 | 0.175200E+09 | 0.339525E+09 | 45311118.47 |
September | 0.138746E+09 | 98869.42 | 0.138647E+09 | 0.231589E+09 | 78390691.07 |
October | 0.106878E+09 | 0.00 | 0.106878E+09 | 0.119248E+09 | 0.161507E+09 |
November | 87836488.38 | 0.00 | 87836488.38 | 42661180.96 | 0.238445E+09 |
December | 72475366.39 | 0.00 | 72475366.39 | 11306459.08 | 0.335488E+09 |
Annual Sum or Average | 0.164991E+10 | 69221055.01 | 0.158069E+10 | 0.214799E+10 | 0.202150E+10 |
Minimum of Months | 72475366.39 | 0.00 | 72475366.39 | 11306459.08 | 38683510.37 |
Maximum of Months | 0.204232E+09 | 33964118.59 | 0.177025E+09 | 0.391736E+09 | 0.335488E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.881523E+09 | 0.493396E+09 | 0.388127E+09 | 0.842760E+09 | 0.112735E+10 |
February | 0.964211E+09 | 0.518308E+09 | 0.445903E+09 | 0.101037E+10 | 0.927867E+09 |
March | 0.141863E+10 | 0.808191E+09 | 0.610440E+09 | 0.169139E+10 | 0.794668E+09 |
April | 0.186236E+10 | 0.105979E+10 | 0.802573E+09 | 0.246319E+10 | 0.507096E+09 |
May | 0.183851E+10 | 0.104720E+10 | 0.791311E+09 | 0.260083E+10 | 0.380462E+09 |
June | 0.191877E+10 | 0.118189E+10 | 0.736882E+09 | 0.300764E+10 | 0.230688E+09 |
July | 0.183372E+10 | 0.104826E+10 | 0.785462E+09 | 0.304377E+10 | 0.145027E+09 |
August | 0.181492E+10 | 0.100036E+10 | 0.814565E+09 | 0.291178E+10 | 0.170340E+09 |
September | 0.146460E+10 | 0.819516E+09 | 0.645087E+09 | 0.223344E+10 | 0.288282E+09 |
October | 0.131856E+10 | 0.837307E+09 | 0.481250E+09 | 0.175004E+10 | 0.567968E+09 |
November | 0.992419E+09 | 0.582190E+09 | 0.410229E+09 | 0.107824E+10 | 0.836409E+09 |
December | 0.835322E+09 | 0.509521E+09 | 0.325801E+09 | 0.795097E+09 | 0.116554E+10 |
Annual Sum or Average | 0.171435E+11 | 0.990592E+10 | 0.723763E+10 | 0.234285E+11 | 0.714170E+10 |
Minimum of Months | 0.835322E+09 | 0.493396E+09 | 0.325801E+09 | 0.795097E+09 | 0.145027E+09 |
Maximum of Months | 0.191877E+10 | 0.118189E+10 | 0.814565E+09 | 0.304377E+10 | 0.116554E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.628401E+09 | 0.488685E+09 | 0.139716E+09 | 0.772315E+09 | 0.295086E+09 |
February | 0.559480E+09 | 0.409462E+09 | 0.150018E+09 | 0.702900E+09 | 0.245567E+09 |
March | 0.460600E+09 | 0.281060E+09 | 0.179540E+09 | 0.602237E+09 | 0.217951E+09 |
April | 0.342331E+09 | 0.140291E+09 | 0.202040E+09 | 0.482935E+09 | 0.143251E+09 |
May | 0.238072E+09 | 53857719.31 | 0.184215E+09 | 0.365899E+09 | 0.105587E+09 |
June | 0.192602E+09 | 23127003.62 | 0.169475E+09 | 0.366238E+09 | 64573848.47 |
July | 0.220305E+09 | 34566908.48 | 0.185738E+09 | 0.448469E+09 | 38982116.13 |
August | 0.299688E+09 | 94519723.41 | 0.205168E+09 | 0.551834E+09 | 46101832.39 |
September | 0.411720E+09 | 0.231761E+09 | 0.179959E+09 | 0.664322E+09 | 78285096.31 |
October | 0.573177E+09 | 0.421618E+09 | 0.151560E+09 | 0.805555E+09 | 0.151717E+09 |
November | 0.625703E+09 | 0.481552E+09 | 0.144152E+09 | 0.796602E+09 | 0.219332E+09 |
December | 0.685278E+09 | 0.565688E+09 | 0.119590E+09 | 0.844203E+09 | 0.298533E+09 |
Annual Sum or Average | 0.523736E+10 | 0.322619E+10 | 0.201117E+10 | 0.740351E+10 | 0.190497E+10 |
Minimum of Months | 0.192602E+09 | 23127003.62 | 0.119590E+09 | 0.365899E+09 | 38982116.13 |
Maximum of Months | 0.685278E+09 | 0.565688E+09 | 0.205168E+09 | 0.844203E+09 | 0.298533E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107837E+09 | 0.00 | 0.107837E+09 | 17212513.10 | 0.441792E+09 |
February | 0.121735E+09 | 0.00 | 0.121735E+09 | 39112194.34 | 0.355844E+09 |
March | 0.170039E+09 | 5910.77 | 0.170034E+09 | 0.106342E+09 | 0.298037E+09 |
April | 0.209882E+09 | 2811456.93 | 0.207070E+09 | 0.175550E+09 | 0.182134E+09 |
May | 0.234747E+09 | 15252261.97 | 0.219495E+09 | 0.252765E+09 | 0.131232E+09 |
June | 0.258646E+09 | 43013413.18 | 0.215633E+09 | 0.380174E+09 | 79391557.03 |
July | 0.245081E+09 | 20889570.53 | 0.224191E+09 | 0.391395E+09 | 50433833.67 |
August | 0.227446E+09 | 5566273.31 | 0.221880E+09 | 0.328194E+09 | 60959677.52 |
September | 0.175713E+09 | 125211.88 | 0.175587E+09 | 0.212677E+09 | 0.116204E+09 |
October | 0.135354E+09 | 0.00 | 0.135354E+09 | 96338137.72 | 0.229839E+09 |
November | 0.111239E+09 | 0.00 | 0.111239E+09 | 29103342.70 | 0.330294E+09 |
December | 91785478.59 | 0.00 | 91785478.59 | 4167500.59 | 0.462943E+09 |
Annual Sum or Average | 0.208951E+10 | 87664098.56 | 0.200184E+10 | 0.203303E+10 | 0.273910E+10 |
Minimum of Months | 91785478.59 | 0.00 | 91785478.59 | 4167500.59 | 50433833.67 |
Maximum of Months | 0.258646E+09 | 43013413.18 | 0.224191E+09 | 0.391395E+09 | 0.462943E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 96482036.79 | 0.00 | 96482036.79 | 15400100.69 | 0.395210E+09 |
February | 0.108917E+09 | 0.00 | 0.108917E+09 | 34993828.47 | 0.318377E+09 |
March | 0.152135E+09 | 5288.39 | 0.152130E+09 | 95144185.44 | 0.266655E+09 |
April | 0.187782E+09 | 2515421.16 | 0.185267E+09 | 0.157065E+09 | 0.162956E+09 |
May | 0.210029E+09 | 13646256.58 | 0.196383E+09 | 0.226149E+09 | 0.117414E+09 |
June | 0.231412E+09 | 38484263.75 | 0.192928E+09 | 0.340143E+09 | 71031926.89 |
July | 0.219275E+09 | 18689977.90 | 0.200585E+09 | 0.350182E+09 | 45123342.08 |
August | 0.203497E+09 | 4980165.82 | 0.198517E+09 | 0.293636E+09 | 54540854.46 |
September | 0.157211E+09 | 112027.54 | 0.157099E+09 | 0.190283E+09 | 0.103968E+09 |
October | 0.121102E+09 | 0.00 | 0.121102E+09 | 86194096.84 | 0.205637E+09 |
November | 99526286.15 | 0.00 | 99526286.15 | 26038870.98 | 0.295498E+09 |
December | 82120815.47 | 0.00 | 82120815.47 | 3728678.57 | 0.414167E+09 |
Annual Sum or Average | 0.186949E+10 | 78433401.14 | 0.179105E+10 | 0.181896E+10 | 0.245058E+10 |
Minimum of Months | 82120815.47 | 0.00 | 82120815.47 | 3728678.57 | 45123342.08 |
Maximum of Months | 0.231412E+09 | 38484263.75 | 0.200585E+09 | 0.350182E+09 | 0.414167E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.234601E+10 | 0.182441E+10 | 0.521602E+09 | 0.274785E+10 | 0.113492E+10 |
February | 0.208871E+10 | 0.152864E+10 | 0.560062E+09 | 0.249511E+10 | 0.942932E+09 |
March | 0.171956E+10 | 0.104928E+10 | 0.670276E+09 | 0.209840E+10 | 0.832831E+09 |
April | 0.127803E+10 | 0.523749E+09 | 0.754276E+09 | 0.161884E+10 | 0.555837E+09 |
May | 0.888795E+09 | 0.201067E+09 | 0.687728E+09 | 0.114330E+10 | 0.413498E+09 |
June | 0.719042E+09 | 86339996.01 | 0.632702E+09 | 0.110167E+10 | 0.254080E+09 |
July | 0.822463E+09 | 0.129049E+09 | 0.693414E+09 | 0.136866E+10 | 0.154813E+09 |
August | 0.111883E+10 | 0.352870E+09 | 0.765955E+09 | 0.175888E+10 | 0.188549E+09 |
September | 0.153707E+10 | 0.865233E+09 | 0.671839E+09 | 0.222603E+10 | 0.340199E+09 |
October | 0.213984E+10 | 0.157402E+10 | 0.565818E+09 | 0.279540E+10 | 0.617999E+09 |
November | 0.233594E+10 | 0.179778E+10 | 0.538161E+09 | 0.282622E+10 | 0.858882E+09 |
December | 0.255835E+10 | 0.211188E+10 | 0.446465E+09 | 0.302096E+10 | 0.115627E+10 |
Annual Sum or Average | 0.195526E+11 | 0.120443E+11 | 0.750830E+10 | 0.252013E+11 | 0.745081E+10 |
Minimum of Months | 0.719042E+09 | 86339996.01 | 0.446465E+09 | 0.110167E+10 | 0.154813E+09 |
Maximum of Months | 0.255835E+10 | 0.211188E+10 | 0.765955E+09 | 0.302096E+10 | 0.115627E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1375.97 | 558.03 | 1186.63 | 922.80 | 263.83 | 0.00 | 0.00 |
February | 1383.58 | 513.82 | 1169.68 | 856.05 | 313.63 | 0.00 | 0.00 |
March | 1056.98 | 406.21 | 869.77 | 530.74 | 339.03 | 0.00 | 0.00 |
April | 845.23 | 281.22 | 667.98 | 273.75 | 394.23 | 0.00 | 0.00 |
May | 583.64 | 197.10 | 449.56 | 101.70 | 347.85 | 0.00 | 0.00 |
June | 570.53 | 127.17 | 375.82 | 45.13 | 330.69 | 0.00 | 0.00 |
July | 682.36 | 78.64 | 416.00 | 65.27 | 350.73 | 0.00 | 0.00 |
August | 881.10 | 96.44 | 565.91 | 178.49 | 387.42 | 0.00 | 0.00 |
September | 1156.92 | 177.10 | 803.38 | 452.23 | 351.15 | 0.00 | 0.00 |
October | 1400.40 | 309.75 | 1082.35 | 796.16 | 286.19 | 0.00 | 0.00 |
November | 1457.67 | 444.84 | 1220.92 | 939.64 | 281.28 | 0.00 | 0.00 |
December | 1506.87 | 572.68 | 1294.03 | 1068.21 | 225.82 | 0.00 | 0.00 |
Annual Sum or Average | 1073.31 | 312.55 | 839.96 | 517.41 | 322.55 | 0.00 | 0.00 |
Minimum of Months | 570.53 | 78.64 | 375.82 | 45.13 | 225.82 | 0.00 | 0.00 |
Maximum of Months | 1506.87 | 572.68 | 1294.03 | 1068.21 | 394.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3832.63 | 1670.49 | 3341.48 | 2598.55 | 742.93 | 0.00 | 0.00 |
February | 3854.03 | 1542.69 | 3293.74 | 2410.57 | 883.17 | 0.00 | 0.00 |
March | 2933.03 | 1235.43 | 2449.21 | 1494.52 | 954.68 | 0.00 | 0.00 |
April | 2341.61 | 855.35 | 1880.99 | 770.86 | 1110.14 | 0.00 | 0.00 |
May | 1607.06 | 604.61 | 1265.92 | 286.39 | 979.54 | 0.00 | 0.00 |
June | 1585.69 | 379.03 | 1058.28 | 127.08 | 931.20 | 0.00 | 0.00 |
July | 1908.23 | 226.70 | 1171.44 | 183.81 | 987.63 | 0.00 | 0.00 |
August | 2466.57 | 276.78 | 1593.56 | 502.60 | 1090.96 | 0.00 | 0.00 |
September | 3236.93 | 515.71 | 2262.26 | 1273.45 | 988.81 | 0.00 | 0.00 |
October | 3914.61 | 917.50 | 3047.83 | 2241.93 | 805.90 | 0.00 | 0.00 |
November | 4065.39 | 1338.56 | 3438.04 | 2645.98 | 792.06 | 0.00 | 0.00 |
December | 4205.16 | 1716.64 | 3643.92 | 3008.01 | 635.91 | 0.00 | 0.00 |
Annual Sum or Average | 2990.92 | 936.84 | 2365.28 | 1457.01 | 908.27 | 0.00 | 0.00 |
Minimum of Months | 1585.69 | 226.70 | 1058.28 | 127.08 | 635.91 | 0.00 | 0.00 |
Maximum of Months | 4205.16 | 1716.64 | 3643.92 | 3008.01 | 1110.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5054.56 | 2225.76 | 4340.77 | 3375.67 | 965.10 | 0.00 | 0.00 |
February | 5091.34 | 2051.38 | 4278.76 | 3131.47 | 1147.29 | 0.00 | 0.00 |
March | 3876.76 | 1645.06 | 3181.66 | 1941.47 | 1240.19 | 0.00 | 0.00 |
April | 3111.12 | 1134.61 | 2443.51 | 1001.39 | 1442.13 | 0.00 | 0.00 |
May | 2135.39 | 806.95 | 1644.50 | 372.03 | 1272.47 | 0.00 | 0.00 |
June | 2111.61 | 504.80 | 1374.76 | 165.08 | 1209.68 | 0.00 | 0.00 |
July | 2545.25 | 296.06 | 1521.77 | 238.78 | 1282.99 | 0.00 | 0.00 |
August | 3279.64 | 358.01 | 2070.13 | 652.91 | 1417.22 | 0.00 | 0.00 |
September | 4286.19 | 669.20 | 2938.80 | 1654.29 | 1284.51 | 0.00 | 0.00 |
October | 5171.02 | 1205.50 | 3959.30 | 2912.39 | 1046.91 | 0.00 | 0.00 |
November | 5364.18 | 1771.31 | 4466.21 | 3437.27 | 1028.93 | 0.00 | 0.00 |
December | 5546.54 | 2284.91 | 4733.66 | 3907.58 | 826.08 | 0.00 | 0.00 |
Annual Sum or Average | 3957.90 | 1241.99 | 3072.63 | 1892.73 | 1179.90 | 0.00 | 0.00 |
Minimum of Months | 2111.61 | 296.06 | 1374.76 | 165.08 | 826.08 | 0.00 | 0.00 |
Maximum of Months | 5546.54 | 2284.91 | 4733.66 | 3907.58 | 1442.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 424.20 | 319.14 | 404.34 | 279.25 | 125.09 | 0.00 | 0.00 |
February | 491.98 | 291.85 | 449.31 | 295.07 | 154.24 | 0.00 | 0.00 |
March | 475.20 | 226.50 | 415.27 | 234.17 | 181.09 | 0.00 | 0.00 |
April | 541.54 | 145.88 | 443.34 | 219.79 | 223.56 | 0.00 | 0.00 |
May | 498.78 | 98.30 | 384.88 | 173.05 | 211.84 | 0.00 | 0.00 |
June | 579.68 | 56.92 | 389.71 | 184.58 | 205.13 | 0.00 | 0.00 |
July | 582.06 | 26.32 | 367.02 | 152.05 | 214.96 | 0.00 | 0.00 |
August | 611.97 | 34.43 | 403.18 | 169.82 | 233.36 | 0.00 | 0.00 |
September | 598.99 | 78.54 | 423.13 | 228.95 | 194.18 | 0.00 | 0.00 |
October | 571.95 | 161.98 | 455.87 | 308.07 | 147.80 | 0.00 | 0.00 |
November | 474.58 | 245.59 | 430.39 | 296.96 | 133.43 | 0.00 | 0.00 |
December | 436.02 | 323.25 | 418.14 | 312.55 | 105.60 | 0.00 | 0.00 |
Annual Sum or Average | 523.90 | 166.76 | 415.04 | 237.45 | 177.59 | 0.00 | 0.00 |
Minimum of Months | 424.20 | 26.32 | 367.02 | 152.05 | 105.60 | 0.00 | 0.00 |
Maximum of Months | 611.97 | 323.25 | 455.87 | 312.55 | 233.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 172.71 | 335.56 | 201.51 | 96.79 | 104.72 | 0.00 | 0.00 |
February | 242.48 | 301.04 | 257.78 | 125.81 | 131.96 | 0.00 | 0.00 |
March | 303.30 | 230.95 | 293.43 | 129.24 | 164.19 | 0.00 | 0.00 |
April | 427.82 | 148.23 | 375.21 | 166.52 | 208.69 | 0.00 | 0.00 |
May | 456.51 | 100.44 | 365.20 | 157.43 | 207.77 | 0.00 | 0.00 |
June | 575.41 | 56.08 | 394.20 | 188.76 | 205.44 | 0.00 | 0.00 |
July | 555.92 | 27.89 | 357.02 | 145.31 | 211.71 | 0.00 | 0.00 |
August | 529.47 | 36.67 | 358.34 | 136.17 | 222.17 | 0.00 | 0.00 |
September | 434.70 | 84.05 | 317.82 | 139.58 | 178.24 | 0.00 | 0.00 |
October | 327.74 | 171.93 | 281.77 | 150.65 | 131.12 | 0.00 | 0.00 |
November | 206.41 | 255.48 | 222.88 | 111.18 | 111.71 | 0.00 | 0.00 |
December | 154.27 | 341.90 | 189.35 | 101.34 | 88.01 | 0.00 | 0.00 |
Annual Sum or Average | 366.07 | 173.56 | 301.28 | 137.34 | 163.94 | 0.00 | 0.00 |
Minimum of Months | 154.27 | 27.89 | 189.35 | 96.79 | 88.01 | 0.00 | 0.00 |
Maximum of Months | 575.41 | 341.90 | 394.20 | 188.76 | 222.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 208.86 | 110.40 | 187.66 | 145.93 | 41.72 | 0.00 | 0.00 |
February | 209.86 | 103.41 | 184.98 | 135.38 | 49.60 | 0.00 | 0.00 |
March | 157.10 | 84.69 | 137.55 | 83.93 | 53.62 | 0.00 | 0.00 |
April | 124.09 | 60.44 | 105.64 | 43.29 | 62.35 | 0.00 | 0.00 |
May | 82.44 | 44.83 | 71.09 | 16.08 | 55.01 | 0.00 | 0.00 |
June | 82.16 | 29.80 | 59.43 | 7.14 | 52.30 | 0.00 | 0.00 |
July | 100.66 | 19.93 | 65.79 | 10.32 | 55.47 | 0.00 | 0.00 |
August | 132.23 | 23.47 | 89.49 | 28.23 | 61.27 | 0.00 | 0.00 |
September | 175.97 | 38.85 | 127.05 | 71.52 | 55.53 | 0.00 | 0.00 |
October | 214.07 | 63.95 | 171.17 | 125.91 | 45.26 | 0.00 | 0.00 |
November | 222.27 | 90.39 | 193.08 | 148.60 | 44.48 | 0.00 | 0.00 |
December | 230.66 | 113.94 | 204.64 | 168.93 | 35.71 | 0.00 | 0.00 |
Annual Sum or Average | 161.42 | 65.14 | 132.83 | 81.83 | 51.01 | 0.00 | 0.00 |
Minimum of Months | 82.16 | 19.93 | 59.43 | 7.14 | 35.71 | 0.00 | 0.00 |
Maximum of Months | 230.66 | 113.94 | 204.64 | 168.93 | 62.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.05 | 98.70 | 25.44 | 0.00 | 25.44 | 0.00 | 0.00 |
February | 12.93 | 87.58 | 31.79 | 0.00 | 31.79 | 0.00 | 0.00 |
March | 28.25 | 65.58 | 40.11 | 0.00 | 40.11 | 0.00 | 0.00 |
April | 47.37 | 39.68 | 51.16 | 0.69 | 50.47 | 0.00 | 0.00 |
May | 65.29 | 26.03 | 55.37 | 3.60 | 51.77 | 0.00 | 0.00 |
June | 100.19 | 14.14 | 63.04 | 10.48 | 52.56 | 0.00 | 0.00 |
July | 100.63 | 6.40 | 57.81 | 4.93 | 52.88 | 0.00 | 0.00 |
August | 85.50 | 8.50 | 53.65 | 1.31 | 52.34 | 0.00 | 0.00 |
September | 58.13 | 21.24 | 42.83 | 0.03 | 42.80 | 0.00 | 0.00 |
October | 27.49 | 46.97 | 31.93 | 0.00 | 31.93 | 0.00 | 0.00 |
November | 9.70 | 74.28 | 27.11 | 0.00 | 27.11 | 0.00 | 0.00 |
December | 1.92 | 102.54 | 21.65 | 0.00 | 21.65 | 0.00 | 0.00 |
Annual Sum or Average | 45.46 | 49.12 | 41.86 | 1.76 | 40.10 | 0.00 | 0.00 |
Minimum of Months | 1.92 | 6.40 | 21.65 | 0.00 | 21.65 | 0.00 | 0.00 |
Maximum of Months | 100.63 | 102.54 | 63.04 | 10.48 | 52.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 409.45 | 312.80 | 399.19 | 274.57 | 124.62 | 0.00 | 0.00 |
February | 459.87 | 284.31 | 430.56 | 276.39 | 154.18 | 0.00 | 0.00 |
March | 494.55 | 217.45 | 436.82 | 255.82 | 181.00 | 0.00 | 0.00 |
April | 600.72 | 137.64 | 491.35 | 258.57 | 232.78 | 0.00 | 0.00 |
May | 559.46 | 94.16 | 432.12 | 215.61 | 216.51 | 0.00 | 0.00 |
June | 650.26 | 52.34 | 444.47 | 236.93 | 207.54 | 0.00 | 0.00 |
July | 660.90 | 25.35 | 424.59 | 208.61 | 215.99 | 0.00 | 0.00 |
August | 674.76 | 32.48 | 450.72 | 222.05 | 228.67 | 0.00 | 0.00 |
September | 619.31 | 74.39 | 441.39 | 247.51 | 193.88 | 0.00 | 0.00 |
October | 571.84 | 156.32 | 460.16 | 313.73 | 146.43 | 0.00 | 0.00 |
November | 473.44 | 241.87 | 432.85 | 298.10 | 134.75 | 0.00 | 0.00 |
December | 423.74 | 319.68 | 411.80 | 306.33 | 105.47 | 0.00 | 0.00 |
Annual Sum or Average | 550.20 | 161.79 | 437.90 | 259.37 | 178.53 | 0.00 | 0.00 |
Minimum of Months | 409.45 | 25.35 | 399.19 | 208.61 | 105.47 | 0.00 | 0.00 |
Maximum of Months | 674.76 | 319.68 | 491.35 | 313.73 | 232.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 144.86 | 315.29 | 196.36 | 92.11 | 104.25 | 0.00 | 0.00 |
February | 202.50 | 284.44 | 239.03 | 107.13 | 131.90 | 0.00 | 0.00 |
March | 317.59 | 216.20 | 314.98 | 150.88 | 164.09 | 0.00 | 0.00 |
April | 488.98 | 139.82 | 423.21 | 205.31 | 217.91 | 0.00 | 0.00 |
May | 517.96 | 97.12 | 412.44 | 200.00 | 212.44 | 0.00 | 0.00 |
June | 644.96 | 54.80 | 448.95 | 241.11 | 207.85 | 0.00 | 0.00 |
July | 630.52 | 27.85 | 414.59 | 201.86 | 212.73 | 0.00 | 0.00 |
August | 588.25 | 35.59 | 405.88 | 188.40 | 217.49 | 0.00 | 0.00 |
September | 451.85 | 79.13 | 336.07 | 158.13 | 177.94 | 0.00 | 0.00 |
October | 321.55 | 158.31 | 286.07 | 156.32 | 129.75 | 0.00 | 0.00 |
November | 197.34 | 243.14 | 225.34 | 112.31 | 113.03 | 0.00 | 0.00 |
December | 132.23 | 327.35 | 183.01 | 95.12 | 87.88 | 0.00 | 0.00 |
Annual Sum or Average | 387.41 | 164.33 | 324.15 | 159.26 | 164.88 | 0.00 | 0.00 |
Minimum of Months | 132.23 | 27.85 | 183.01 | 92.11 | 87.88 | 0.00 | 0.00 |
Maximum of Months | 644.96 | 327.35 | 448.95 | 241.11 | 217.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 470.98 | 399.71 | 461.70 | 316.20 | 145.51 | 0.00 | 0.00 |
February | 496.74 | 366.38 | 469.66 | 293.32 | 176.34 | 0.00 | 0.00 |
March | 421.79 | 292.14 | 384.92 | 181.86 | 203.06 | 0.00 | 0.00 |
April | 391.16 | 195.18 | 339.71 | 95.28 | 244.42 | 0.00 | 0.00 |
May | 335.01 | 135.09 | 274.00 | 42.64 | 231.35 | 0.00 | 0.00 |
June | 404.73 | 81.58 | 265.35 | 38.18 | 227.17 | 0.00 | 0.00 |
July | 446.34 | 48.69 | 267.78 | 33.04 | 234.74 | 0.00 | 0.00 |
August | 481.41 | 59.97 | 310.13 | 64.00 | 246.13 | 0.00 | 0.00 |
September | 518.88 | 121.01 | 368.06 | 155.02 | 213.04 | 0.00 | 0.00 |
October | 533.22 | 220.66 | 440.03 | 272.80 | 167.23 | 0.00 | 0.00 |
November | 510.57 | 314.64 | 477.09 | 321.97 | 155.12 | 0.00 | 0.00 |
December | 502.09 | 403.05 | 490.30 | 366.02 | 124.28 | 0.00 | 0.00 |
Annual Sum or Average | 459.14 | 219.09 | 378.50 | 181.10 | 197.40 | 0.00 | 0.00 |
Minimum of Months | 335.01 | 48.69 | 265.35 | 33.04 | 124.28 | 0.00 | 0.00 |
Maximum of Months | 533.22 | 403.05 | 490.30 | 366.02 | 246.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 423.05 | 316.90 | 404.34 | 279.25 | 125.09 | 0.00 | 0.00 |
February | 489.55 | 290.15 | 449.31 | 295.07 | 154.24 | 0.00 | 0.00 |
March | 472.58 | 224.51 | 415.27 | 234.17 | 181.09 | 0.00 | 0.00 |
April | 537.74 | 143.78 | 443.34 | 219.79 | 223.56 | 0.00 | 0.00 |
May | 495.56 | 96.30 | 384.88 | 173.05 | 211.84 | 0.00 | 0.00 |
June | 576.93 | 55.31 | 389.71 | 184.58 | 205.13 | 0.00 | 0.00 |
July | 579.13 | 24.94 | 367.02 | 152.05 | 214.96 | 0.00 | 0.00 |
August | 608.71 | 33.01 | 403.18 | 169.82 | 233.36 | 0.00 | 0.00 |
September | 595.92 | 76.42 | 423.13 | 228.95 | 194.18 | 0.00 | 0.00 |
October | 570.03 | 159.27 | 455.87 | 308.07 | 147.80 | 0.00 | 0.00 |
November | 473.28 | 242.59 | 430.39 | 296.96 | 133.43 | 0.00 | 0.00 |
December | 435.07 | 320.56 | 418.14 | 312.55 | 105.60 | 0.00 | 0.00 |
Annual Sum or Average | 521.46 | 164.68 | 415.04 | 237.45 | 177.59 | 0.00 | 0.00 |
Minimum of Months | 423.05 | 24.94 | 367.02 | 152.05 | 105.60 | 0.00 | 0.00 |
Maximum of Months | 608.71 | 320.56 | 455.87 | 312.55 | 233.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 173.27 | 332.27 | 201.51 | 96.79 | 104.72 | 0.00 | 0.00 |
February | 241.86 | 298.68 | 257.78 | 125.81 | 131.96 | 0.00 | 0.00 |
March | 301.84 | 228.84 | 293.43 | 129.24 | 164.19 | 0.00 | 0.00 |
April | 424.37 | 147.34 | 375.21 | 166.52 | 208.69 | 0.00 | 0.00 |
May | 453.39 | 99.36 | 365.20 | 157.43 | 207.77 | 0.00 | 0.00 |
June | 572.68 | 55.15 | 394.20 | 188.76 | 205.44 | 0.00 | 0.00 |
July | 553.45 | 26.69 | 357.02 | 145.31 | 211.71 | 0.00 | 0.00 |
August | 526.98 | 35.60 | 358.34 | 136.17 | 222.17 | 0.00 | 0.00 |
September | 432.82 | 82.13 | 317.82 | 139.58 | 178.24 | 0.00 | 0.00 |
October | 326.88 | 169.15 | 281.77 | 150.65 | 131.12 | 0.00 | 0.00 |
November | 206.83 | 251.06 | 222.88 | 111.18 | 111.71 | 0.00 | 0.00 |
December | 154.90 | 338.12 | 189.35 | 101.34 | 88.01 | 0.00 | 0.00 |
Annual Sum or Average | 364.62 | 171.41 | 301.28 | 137.34 | 163.94 | 0.00 | 0.00 |
Minimum of Months | 154.90 | 26.69 | 189.35 | 96.79 | 88.01 | 0.00 | 0.00 |
Maximum of Months | 572.68 | 338.12 | 394.20 | 188.76 | 222.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 396.81 | 164.85 | 344.09 | 267.59 | 76.50 | 0.00 | 0.00 |
February | 399.26 | 150.53 | 339.17 | 248.23 | 90.95 | 0.00 | 0.00 |
March | 304.96 | 116.60 | 252.21 | 153.90 | 98.31 | 0.00 | 0.00 |
April | 246.85 | 74.57 | 193.70 | 79.38 | 114.32 | 0.00 | 0.00 |
May | 173.73 | 48.71 | 130.36 | 29.49 | 100.87 | 0.00 | 0.00 |
June | 178.05 | 26.73 | 108.98 | 13.09 | 95.89 | 0.00 | 0.00 |
July | 213.08 | 11.56 | 120.63 | 18.93 | 101.70 | 0.00 | 0.00 |
August | 267.78 | 15.66 | 164.10 | 51.76 | 112.34 | 0.00 | 0.00 |
September | 342.01 | 38.21 | 232.96 | 131.13 | 101.82 | 0.00 | 0.00 |
October | 409.77 | 81.26 | 313.85 | 230.86 | 82.99 | 0.00 | 0.00 |
November | 422.84 | 126.84 | 354.03 | 272.47 | 81.56 | 0.00 | 0.00 |
December | 435.89 | 168.51 | 375.23 | 309.75 | 65.48 | 0.00 | 0.00 |
Annual Sum or Average | 315.44 | 85.01 | 243.57 | 150.04 | 93.53 | 0.00 | 0.00 |
Minimum of Months | 173.73 | 11.56 | 108.98 | 13.09 | 65.48 | 0.00 | 0.00 |
Maximum of Months | 435.89 | 168.51 | 375.23 | 309.75 | 114.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 28.68 | 989.54 | 222.53 | 0.00 | 222.53 | 0.00 | 0.00 |
February | 78.19 | 885.25 | 278.13 | 0.00 | 278.13 | 0.00 | 0.00 |
March | 199.30 | 673.18 | 350.89 | 0.01 | 350.88 | 0.00 | 0.00 |
April | 356.19 | 416.97 | 447.55 | 6.00 | 441.55 | 0.00 | 0.00 |
May | 506.70 | 283.93 | 484.42 | 31.47 | 452.95 | 0.00 | 0.00 |
June | 810.34 | 170.99 | 551.53 | 91.72 | 459.81 | 0.00 | 0.00 |
July | 815.51 | 101.31 | 505.75 | 43.11 | 462.64 | 0.00 | 0.00 |
August | 684.69 | 122.44 | 469.36 | 11.49 | 457.87 | 0.00 | 0.00 |
September | 457.55 | 246.58 | 374.68 | 0.27 | 374.42 | 0.00 | 0.00 |
October | 198.63 | 497.92 | 279.31 | 0.00 | 279.31 | 0.00 | 0.00 |
November | 54.95 | 766.06 | 237.20 | 0.00 | 237.20 | 0.00 | 0.00 |
December | 6.05 | 1035.17 | 189.41 | 0.00 | 189.41 | 0.00 | 0.00 |
Annual Sum or Average | 351.20 | 514.01 | 366.21 | 15.36 | 350.85 | 0.00 | 0.00 |
Minimum of Months | 6.05 | 101.31 | 189.41 | 0.00 | 189.41 | 0.00 | 0.00 |
Maximum of Months | 815.51 | 1035.17 | 551.53 | 91.72 | 462.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 24.07 | 1013.07 | 222.53 | 0.00 | 222.53 | 0.00 | 0.00 |
February | 71.28 | 904.88 | 278.13 | 0.00 | 278.13 | 0.00 | 0.00 |
March | 190.11 | 687.32 | 350.89 | 0.01 | 350.88 | 0.00 | 0.00 |
April | 347.37 | 426.07 | 447.55 | 6.00 | 441.55 | 0.00 | 0.00 |
May | 498.23 | 290.65 | 484.42 | 31.47 | 452.95 | 0.00 | 0.00 |
June | 802.84 | 175.72 | 551.53 | 91.72 | 459.81 | 0.00 | 0.00 |
July | 808.46 | 105.44 | 505.75 | 43.11 | 462.64 | 0.00 | 0.00 |
August | 677.92 | 127.06 | 469.36 | 11.49 | 457.87 | 0.00 | 0.00 |
September | 451.57 | 253.25 | 374.68 | 0.27 | 374.42 | 0.00 | 0.00 |
October | 192.40 | 509.21 | 279.31 | 0.00 | 279.31 | 0.00 | 0.00 |
November | 49.44 | 784.49 | 237.20 | 0.00 | 237.20 | 0.00 | 0.00 |
December | 4.57 | 1062.14 | 189.41 | 0.00 | 189.41 | 0.00 | 0.00 |
Annual Sum or Average | 344.66 | 526.48 | 366.21 | 15.36 | 350.85 | 0.00 | 0.00 |
Minimum of Months | 4.57 | 105.44 | 189.41 | 0.00 | 189.41 | 0.00 | 0.00 |
Maximum of Months | 808.46 | 1062.14 | 551.53 | 91.72 | 462.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 598.85 | 638.12 | 595.53 | 366.67 | 228.87 | 0.00 | 0.00 |
February | 717.72 | 584.49 | 669.57 | 383.50 | 286.06 | 0.00 | 0.00 |
March | 891.10 | 455.30 | 751.75 | 406.68 | 345.07 | 0.00 | 0.00 |
April | 1203.23 | 299.84 | 914.51 | 463.85 | 450.66 | 0.00 | 0.00 |
May | 1202.66 | 217.19 | 844.51 | 415.58 | 428.93 | 0.00 | 0.00 |
June | 1444.84 | 136.45 | 893.37 | 478.00 | 415.36 | 0.00 | 0.00 |
July | 1449.99 | 83.02 | 839.14 | 410.44 | 428.70 | 0.00 | 0.00 |
August | 1419.61 | 97.40 | 856.56 | 410.42 | 446.14 | 0.00 | 0.00 |
September | 1206.07 | 170.43 | 777.42 | 405.62 | 371.79 | 0.00 | 0.00 |
October | 994.14 | 324.47 | 746.20 | 470.03 | 276.17 | 0.00 | 0.00 |
November | 728.96 | 488.48 | 658.16 | 410.39 | 247.77 | 0.00 | 0.00 |
December | 591.12 | 646.74 | 594.79 | 401.44 | 193.35 | 0.00 | 0.00 |
Annual Sum or Average | 1038.80 | 343.98 | 762.01 | 418.61 | 343.40 | 0.00 | 0.00 |
Minimum of Months | 591.12 | 83.02 | 594.79 | 366.67 | 193.35 | 0.00 | 0.00 |
Maximum of Months | 1449.99 | 646.74 | 914.51 | 478.00 | 450.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1007.01 | 705.13 | 952.18 | 681.16 | 271.03 | 0.00 | 0.00 |
February | 1042.33 | 648.79 | 958.73 | 631.88 | 326.85 | 0.00 | 0.00 |
March | 852.35 | 515.45 | 762.30 | 391.76 | 370.53 | 0.00 | 0.00 |
April | 751.81 | 346.52 | 646.48 | 204.12 | 442.37 | 0.00 | 0.00 |
May | 601.79 | 243.34 | 497.90 | 85.86 | 412.04 | 0.00 | 0.00 |
June | 696.69 | 149.82 | 466.47 | 64.75 | 401.72 | 0.00 | 0.00 |
July | 786.23 | 91.84 | 480.44 | 62.96 | 417.48 | 0.00 | 0.00 |
August | 887.34 | 112.00 | 578.62 | 135.68 | 442.93 | 0.00 | 0.00 |
September | 1013.87 | 215.79 | 721.45 | 333.90 | 387.55 | 0.00 | 0.00 |
October | 1102.04 | 383.53 | 894.67 | 587.67 | 307.00 | 0.00 | 0.00 |
November | 1087.55 | 548.71 | 982.52 | 693.59 | 288.94 | 0.00 | 0.00 |
December | 1085.92 | 714.26 | 1020.11 | 788.49 | 231.62 | 0.00 | 0.00 |
Annual Sum or Average | 908.73 | 388.28 | 745.55 | 387.19 | 358.36 | 0.00 | 0.00 |
Minimum of Months | 601.79 | 91.84 | 466.47 | 62.96 | 231.62 | 0.00 | 0.00 |
Maximum of Months | 1102.04 | 714.26 | 1020.11 | 788.49 | 442.93 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.368541E+10 | 0.149462E+10 | 0.317828E+10 | 0.247164E+10 | 0.706641E+09 | 0.00 | 0.00 |
February | 0.334715E+10 | 0.124303E+10 | 0.282969E+10 | 0.207095E+10 | 0.758744E+09 | 0.00 | 0.00 |
March | 0.283103E+10 | 0.108799E+10 | 0.232958E+10 | 0.142153E+10 | 0.908056E+09 | 0.00 | 0.00 |
April | 0.219083E+10 | 0.728918E+09 | 0.173141E+10 | 0.709555E+09 | 0.102185E+10 | 0.00 | 0.00 |
May | 0.156322E+10 | 0.527919E+09 | 0.120409E+10 | 0.272398E+09 | 0.931695E+09 | 0.00 | 0.00 |
June | 0.147882E+10 | 0.329637E+09 | 0.974117E+09 | 0.116970E+09 | 0.857147E+09 | 0.00 | 0.00 |
July | 0.182764E+10 | 0.210629E+09 | 0.111423E+10 | 0.174830E+09 | 0.939397E+09 | 0.00 | 0.00 |
August | 0.235994E+10 | 0.258303E+09 | 0.151573E+10 | 0.478055E+09 | 0.103767E+10 | 0.00 | 0.00 |
September | 0.299874E+10 | 0.459053E+09 | 0.208236E+10 | 0.117218E+10 | 0.910172E+09 | 0.00 | 0.00 |
October | 0.375082E+10 | 0.829639E+09 | 0.289897E+10 | 0.213243E+10 | 0.766540E+09 | 0.00 | 0.00 |
November | 0.377828E+10 | 0.115303E+10 | 0.316463E+10 | 0.243556E+10 | 0.729074E+09 | 0.00 | 0.00 |
December | 0.403601E+10 | 0.153386E+10 | 0.346594E+10 | 0.286110E+10 | 0.604848E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.338479E+11 | 0.985663E+10 | 0.264890E+11 | 0.163172E+11 | 0.101718E+11 | 0.00 | 0.00 |
Minimum of Months | 0.147882E+10 | 0.210629E+09 | 0.974117E+09 | 0.116970E+09 | 0.604848E+09 | 0.00 | 0.00 |
Maximum of Months | 0.403601E+10 | 0.153386E+10 | 0.346594E+10 | 0.286110E+10 | 0.103767E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.102653E+11 | 0.447425E+10 | 0.894982E+10 | 0.695996E+10 | 0.198985E+10 | 0.00 | 0.00 |
February | 0.932366E+10 | 0.373208E+10 | 0.796823E+10 | 0.583165E+10 | 0.213657E+10 | 0.00 | 0.00 |
March | 0.785583E+10 | 0.330898E+10 | 0.655995E+10 | 0.400293E+10 | 0.255702E+10 | 0.00 | 0.00 |
April | 0.606944E+10 | 0.221707E+10 | 0.487553E+10 | 0.199806E+10 | 0.287747E+10 | 0.00 | 0.00 |
May | 0.430436E+10 | 0.161940E+10 | 0.339065E+10 | 0.767054E+09 | 0.262359E+10 | 0.00 | 0.00 |
June | 0.411012E+10 | 0.982445E+09 | 0.274305E+10 | 0.329380E+09 | 0.241367E+10 | 0.00 | 0.00 |
July | 0.511100E+10 | 0.607194E+09 | 0.313759E+10 | 0.492310E+09 | 0.264528E+10 | 0.00 | 0.00 |
August | 0.660647E+10 | 0.741319E+09 | 0.426819E+10 | 0.134617E+10 | 0.292202E+10 | 0.00 | 0.00 |
September | 0.839011E+10 | 0.133671E+10 | 0.586378E+10 | 0.330079E+10 | 0.256298E+10 | 0.00 | 0.00 |
October | 0.104849E+11 | 0.245743E+10 | 0.816330E+10 | 0.600478E+10 | 0.215853E+10 | 0.00 | 0.00 |
November | 0.105375E+11 | 0.346955E+10 | 0.891139E+10 | 0.685837E+10 | 0.205302E+10 | 0.00 | 0.00 |
December | 0.112631E+11 | 0.459784E+10 | 0.975987E+10 | 0.805665E+10 | 0.170321E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.943218E+11 | 0.295443E+11 | 0.745913E+11 | 0.459481E+11 | 0.286432E+11 | 0.00 | 0.00 |
Minimum of Months | 0.411012E+10 | 0.607194E+09 | 0.274305E+10 | 0.329380E+09 | 0.170321E+10 | 0.00 | 0.00 |
Maximum of Months | 0.112631E+11 | 0.459784E+10 | 0.975987E+10 | 0.805665E+10 | 0.292202E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.135381E+11 | 0.596147E+10 | 0.116263E+11 | 0.904139E+10 | 0.258493E+10 | 0.00 | 0.00 |
February | 0.123170E+11 | 0.496270E+10 | 0.103512E+11 | 0.757565E+10 | 0.277553E+10 | 0.00 | 0.00 |
March | 0.103835E+11 | 0.440612E+10 | 0.852175E+10 | 0.520003E+10 | 0.332172E+10 | 0.00 | 0.00 |
April | 0.806403E+10 | 0.294090E+10 | 0.633359E+10 | 0.259559E+10 | 0.373800E+10 | 0.00 | 0.00 |
May | 0.571943E+10 | 0.216133E+10 | 0.440464E+10 | 0.996447E+09 | 0.340819E+10 | 0.00 | 0.00 |
June | 0.547329E+10 | 0.130845E+10 | 0.356338E+10 | 0.427884E+09 | 0.313549E+10 | 0.00 | 0.00 |
July | 0.681719E+10 | 0.792960E+09 | 0.407591E+10 | 0.639539E+09 | 0.343637E+10 | 0.00 | 0.00 |
August | 0.878419E+10 | 0.958904E+09 | 0.554462E+10 | 0.174875E+10 | 0.379587E+10 | 0.00 | 0.00 |
September | 0.111098E+11 | 0.173458E+10 | 0.761738E+10 | 0.428792E+10 | 0.332946E+10 | 0.00 | 0.00 |
October | 0.138501E+11 | 0.322882E+10 | 0.106046E+11 | 0.780055E+10 | 0.280405E+10 | 0.00 | 0.00 |
November | 0.139040E+11 | 0.459123E+10 | 0.115764E+11 | 0.890941E+10 | 0.266700E+10 | 0.00 | 0.00 |
December | 0.148558E+11 | 0.611989E+10 | 0.126786E+11 | 0.104661E+11 | 0.221257E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.124816E+12 | 0.391674E+11 | 0.968984E+11 | 0.596892E+11 | 0.372092E+11 | 0.00 | 0.00 |
Minimum of Months | 0.547329E+10 | 0.792960E+09 | 0.356338E+10 | 0.427884E+09 | 0.221257E+10 | 0.00 | 0.00 |
Maximum of Months | 0.148558E+11 | 0.611989E+10 | 0.126786E+11 | 0.104661E+11 | 0.379587E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113617E+10 | 0.854779E+09 | 0.108299E+10 | 0.747937E+09 | 0.335051E+09 | 0.00 | 0.00 |
February | 0.119019E+10 | 0.706046E+09 | 0.108697E+10 | 0.713832E+09 | 0.373143E+09 | 0.00 | 0.00 |
March | 0.127276E+10 | 0.606651E+09 | 0.111225E+10 | 0.627213E+09 | 0.485037E+09 | 0.00 | 0.00 |
April | 0.140366E+10 | 0.378128E+09 | 0.114914E+10 | 0.569686E+09 | 0.579457E+09 | 0.00 | 0.00 |
May | 0.133592E+10 | 0.263287E+09 | 0.103088E+10 | 0.463488E+09 | 0.567388E+09 | 0.00 | 0.00 |
June | 0.150253E+10 | 0.147529E+09 | 0.101013E+10 | 0.478424E+09 | 0.531702E+09 | 0.00 | 0.00 |
July | 0.155898E+10 | 70498757.10 | 0.983024E+09 | 0.407264E+09 | 0.575761E+09 | 0.00 | 0.00 |
August | 0.163909E+10 | 92215205.09 | 0.107988E+10 | 0.454855E+09 | 0.625021E+09 | 0.00 | 0.00 |
September | 0.155259E+10 | 0.203580E+09 | 0.109676E+10 | 0.593446E+09 | 0.503316E+09 | 0.00 | 0.00 |
October | 0.153190E+10 | 0.433855E+09 | 0.122099E+10 | 0.825128E+09 | 0.395867E+09 | 0.00 | 0.00 |
November | 0.123011E+10 | 0.636582E+09 | 0.111558E+10 | 0.769726E+09 | 0.345855E+09 | 0.00 | 0.00 |
December | 0.116783E+10 | 0.865800E+09 | 0.111995E+10 | 0.837122E+09 | 0.282831E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.165217E+11 | 0.525895E+10 | 0.130885E+11 | 0.748812E+10 | 0.560043E+10 | 0.00 | 0.00 |
Minimum of Months | 0.113617E+10 | 70498757.10 | 0.983024E+09 | 0.407264E+09 | 0.282831E+09 | 0.00 | 0.00 |
Maximum of Months | 0.163909E+10 | 0.865800E+09 | 0.122099E+10 | 0.837122E+09 | 0.625021E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.462596E+09 | 0.898768E+09 | 0.539737E+09 | 0.259253E+09 | 0.280485E+09 | 0.00 | 0.00 |
February | 0.586611E+09 | 0.728273E+09 | 0.623619E+09 | 0.304370E+09 | 0.319249E+09 | 0.00 | 0.00 |
March | 0.812368E+09 | 0.618565E+09 | 0.785916E+09 | 0.346157E+09 | 0.439758E+09 | 0.00 | 0.00 |
April | 0.110892E+10 | 0.384215E+09 | 0.972537E+09 | 0.431614E+09 | 0.540923E+09 | 0.00 | 0.00 |
May | 0.122271E+10 | 0.269023E+09 | 0.978164E+09 | 0.421674E+09 | 0.556490E+09 | 0.00 | 0.00 |
June | 0.149146E+10 | 0.145351E+09 | 0.102176E+10 | 0.489261E+09 | 0.532494E+09 | 0.00 | 0.00 |
July | 0.148897E+10 | 74708624.12 | 0.956240E+09 | 0.389192E+09 | 0.567048E+09 | 0.00 | 0.00 |
August | 0.141813E+10 | 98208978.24 | 0.959782E+09 | 0.364730E+09 | 0.595052E+09 | 0.00 | 0.00 |
September | 0.112674E+10 | 0.217865E+09 | 0.823788E+09 | 0.361784E+09 | 0.462004E+09 | 0.00 | 0.00 |
October | 0.877831E+09 | 0.460503E+09 | 0.754694E+09 | 0.403510E+09 | 0.351184E+09 | 0.00 | 0.00 |
November | 0.535008E+09 | 0.662196E+09 | 0.577715E+09 | 0.288175E+09 | 0.289540E+09 | 0.00 | 0.00 |
December | 0.413192E+09 | 0.915757E+09 | 0.507150E+09 | 0.271434E+09 | 0.235716E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115445E+11 | 0.547343E+10 | 0.950110E+10 | 0.433116E+10 | 0.516994E+10 | 0.00 | 0.00 |
Minimum of Months | 0.413192E+09 | 74708624.12 | 0.507150E+09 | 0.259253E+09 | 0.235716E+09 | 0.00 | 0.00 |
Maximum of Months | 0.149146E+10 | 0.915757E+09 | 0.102176E+10 | 0.489261E+09 | 0.595052E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.559403E+09 | 0.295692E+09 | 0.502621E+09 | 0.390870E+09 | 0.111751E+09 | 0.00 | 0.00 |
February | 0.507684E+09 | 0.250181E+09 | 0.447495E+09 | 0.327504E+09 | 0.119991E+09 | 0.00 | 0.00 |
March | 0.420766E+09 | 0.226829E+09 | 0.368407E+09 | 0.224804E+09 | 0.143603E+09 | 0.00 | 0.00 |
April | 0.321637E+09 | 0.156672E+09 | 0.273811E+09 | 0.112211E+09 | 0.161600E+09 | 0.00 | 0.00 |
May | 0.220797E+09 | 0.120073E+09 | 0.190420E+09 | 43077608.47 | 0.147342E+09 | 0.00 | 0.00 |
June | 0.212955E+09 | 77252727.65 | 0.154051E+09 | 18497924.16 | 0.135553E+09 | 0.00 | 0.00 |
July | 0.269610E+09 | 53369579.98 | 0.176209E+09 | 27648028.33 | 0.148561E+09 | 0.00 | 0.00 |
August | 0.354163E+09 | 62859998.47 | 0.239703E+09 | 75600743.78 | 0.164102E+09 | 0.00 | 0.00 |
September | 0.456116E+09 | 0.100703E+09 | 0.329310E+09 | 0.185372E+09 | 0.143938E+09 | 0.00 | 0.00 |
October | 0.573372E+09 | 0.171272E+09 | 0.458451E+09 | 0.337227E+09 | 0.121224E+09 | 0.00 | 0.00 |
November | 0.576122E+09 | 0.234283E+09 | 0.500463E+09 | 0.385165E+09 | 0.115298E+09 | 0.00 | 0.00 |
December | 0.617796E+09 | 0.305172E+09 | 0.548113E+09 | 0.452460E+09 | 95652933.86 | 0.00 | 0.00 |
Annual Sum or Average | 0.509042E+10 | 0.205436E+10 | 0.418905E+10 | 0.258044E+10 | 0.160862E+10 | 0.00 | 0.00 |
Minimum of Months | 0.212955E+09 | 53369579.98 | 0.154051E+09 | 18497924.16 | 95652933.86 | 0.00 | 0.00 |
Maximum of Months | 0.617796E+09 | 0.305172E+09 | 0.548113E+09 | 0.452460E+09 | 0.164102E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 16195445.37 | 0.264368E+09 | 68128869.22 | 0.00 | 68128869.22 | 0.00 | 0.00 |
February | 31276159.92 | 0.211867E+09 | 76909365.24 | 0.00 | 76909365.24 | 0.00 | 0.00 |
March | 75669462.80 | 0.175642E+09 | 0.107427E+09 | 3734.29 | 0.107423E+09 | 0.00 | 0.00 |
April | 0.122772E+09 | 0.102844E+09 | 0.132599E+09 | 1776214.57 | 0.130822E+09 | 0.00 | 0.00 |
May | 0.174864E+09 | 69720318.94 | 0.148308E+09 | 9636032.37 | 0.138672E+09 | 0.00 | 0.00 |
June | 0.259682E+09 | 36660193.15 | 0.163407E+09 | 27174896.58 | 0.136232E+09 | 0.00 | 0.00 |
July | 0.269529E+09 | 17130947.83 | 0.154837E+09 | 13197555.76 | 0.141639E+09 | 0.00 | 0.00 |
August | 0.229001E+09 | 22759690.22 | 0.143695E+09 | 3516644.93 | 0.140179E+09 | 0.00 | 0.00 |
September | 0.150681E+09 | 55058644.99 | 0.111011E+09 | 79106.02 | 0.110932E+09 | 0.00 | 0.00 |
October | 73634662.50 | 0.125813E+09 | 85513450.69 | 0.00 | 85513450.69 | 0.00 | 0.00 |
November | 25141523.85 | 0.192545E+09 | 70278505.29 | 0.00 | 70278505.29 | 0.00 | 0.00 |
December | 5153042.91 | 0.274638E+09 | 57987978.73 | 0.00 | 57987978.73 | 0.00 | 0.00 |
Annual Sum or Average | 0.143360E+10 | 0.154905E+10 | 0.132010E+10 | 55384184.52 | 0.126472E+10 | 0.00 | 0.00 |
Minimum of Months | 5153042.91 | 17130947.83 | 57987978.73 | 0.00 | 57987978.73 | 0.00 | 0.00 |
Maximum of Months | 0.269529E+09 | 0.274638E+09 | 0.163407E+09 | 27174896.58 | 0.141639E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.109667E+10 | 0.837809E+09 | 0.106919E+10 | 0.735400E+09 | 0.333794E+09 | 0.00 | 0.00 |
February | 0.111253E+10 | 0.687809E+09 | 0.104162E+10 | 0.668634E+09 | 0.372986E+09 | 0.00 | 0.00 |
March | 0.132462E+10 | 0.582416E+09 | 0.116997E+10 | 0.685185E+09 | 0.484782E+09 | 0.00 | 0.00 |
April | 0.155707E+10 | 0.356751E+09 | 0.127358E+10 | 0.670222E+09 | 0.603355E+09 | 0.00 | 0.00 |
May | 0.149847E+10 | 0.252207E+09 | 0.115739E+10 | 0.577494E+09 | 0.579898E+09 | 0.00 | 0.00 |
June | 0.168548E+10 | 0.135669E+09 | 0.115205E+10 | 0.614113E+09 | 0.537942E+09 | 0.00 | 0.00 |
July | 0.177016E+10 | 67907684.45 | 0.113723E+10 | 0.558734E+09 | 0.578497E+09 | 0.00 | 0.00 |
August | 0.180727E+10 | 87004453.57 | 0.120721E+10 | 0.594733E+09 | 0.612480E+09 | 0.00 | 0.00 |
September | 0.160525E+10 | 0.192813E+09 | 0.114407E+10 | 0.641548E+09 | 0.502525E+09 | 0.00 | 0.00 |
October | 0.153161E+10 | 0.418680E+09 | 0.123250E+10 | 0.840301E+09 | 0.392202E+09 | 0.00 | 0.00 |
November | 0.122716E+10 | 0.626925E+09 | 0.112195E+10 | 0.772667E+09 | 0.349281E+09 | 0.00 | 0.00 |
December | 0.113495E+10 | 0.856233E+09 | 0.110297E+10 | 0.820466E+09 | 0.282502E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.173512E+11 | 0.510222E+10 | 0.138097E+11 | 0.817950E+10 | 0.563024E+10 | 0.00 | 0.00 |
Minimum of Months | 0.109667E+10 | 67907684.45 | 0.104162E+10 | 0.558734E+09 | 0.282502E+09 | 0.00 | 0.00 |
Maximum of Months | 0.180727E+10 | 0.856233E+09 | 0.127358E+10 | 0.840301E+09 | 0.612480E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.387991E+09 | 0.844481E+09 | 0.525943E+09 | 0.246716E+09 | 0.279227E+09 | 0.00 | 0.00 |
February | 0.489883E+09 | 0.688119E+09 | 0.578264E+09 | 0.259172E+09 | 0.319091E+09 | 0.00 | 0.00 |
March | 0.850646E+09 | 0.579062E+09 | 0.843632E+09 | 0.404129E+09 | 0.439503E+09 | 0.00 | 0.00 |
April | 0.126743E+10 | 0.362408E+09 | 0.109697E+10 | 0.532151E+09 | 0.564821E+09 | 0.00 | 0.00 |
May | 0.138731E+10 | 0.260120E+09 | 0.110468E+10 | 0.535680E+09 | 0.569001E+09 | 0.00 | 0.00 |
June | 0.167173E+10 | 0.142051E+09 | 0.116368E+10 | 0.624950E+09 | 0.538734E+09 | 0.00 | 0.00 |
July | 0.168878E+10 | 74606360.71 | 0.111045E+10 | 0.540662E+09 | 0.569784E+09 | 0.00 | 0.00 |
August | 0.157557E+10 | 95314247.31 | 0.108712E+10 | 0.504609E+09 | 0.582512E+09 | 0.00 | 0.00 |
September | 0.117120E+10 | 0.205094E+09 | 0.871099E+09 | 0.409886E+09 | 0.461213E+09 | 0.00 | 0.00 |
October | 0.861251E+09 | 0.424020E+09 | 0.766203E+09 | 0.418683E+09 | 0.347520E+09 | 0.00 | 0.00 |
November | 0.511512E+09 | 0.630229E+09 | 0.584081E+09 | 0.291116E+09 | 0.292966E+09 | 0.00 | 0.00 |
December | 0.354161E+09 | 0.876776E+09 | 0.490166E+09 | 0.254778E+09 | 0.235388E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.122175E+11 | 0.518228E+10 | 0.102223E+11 | 0.502253E+10 | 0.519976E+10 | 0.00 | 0.00 |
Minimum of Months | 0.354161E+09 | 74606360.71 | 0.490166E+09 | 0.246716E+09 | 0.235388E+09 | 0.00 | 0.00 |
Maximum of Months | 0.168878E+10 | 0.876776E+09 | 0.116368E+10 | 0.624950E+09 | 0.582512E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.126147E+10 | 0.107058E+10 | 0.123663E+10 | 0.846907E+09 | 0.389723E+09 | 0.00 | 0.00 |
February | 0.120170E+10 | 0.886349E+09 | 0.113621E+10 | 0.709611E+09 | 0.426598E+09 | 0.00 | 0.00 |
March | 0.112971E+10 | 0.782455E+09 | 0.103096E+10 | 0.487095E+09 | 0.543864E+09 | 0.00 | 0.00 |
April | 0.101389E+10 | 0.505904E+09 | 0.880524E+09 | 0.246977E+09 | 0.633547E+09 | 0.00 | 0.00 |
May | 0.897304E+09 | 0.361835E+09 | 0.733872E+09 | 0.114212E+09 | 0.619660E+09 | 0.00 | 0.00 |
June | 0.104906E+10 | 0.211467E+09 | 0.687780E+09 | 98949795.87 | 0.588830E+09 | 0.00 | 0.00 |
July | 0.119548E+10 | 0.130411E+09 | 0.717223E+09 | 88495919.93 | 0.628727E+09 | 0.00 | 0.00 |
August | 0.128941E+10 | 0.160624E+09 | 0.830662E+09 | 0.171424E+09 | 0.659238E+09 | 0.00 | 0.00 |
September | 0.134495E+10 | 0.313647E+09 | 0.954011E+09 | 0.401821E+09 | 0.552190E+09 | 0.00 | 0.00 |
October | 0.142818E+10 | 0.591017E+09 | 0.117859E+10 | 0.730677E+09 | 0.447909E+09 | 0.00 | 0.00 |
November | 0.132339E+10 | 0.815536E+09 | 0.123661E+10 | 0.834545E+09 | 0.402066E+09 | 0.00 | 0.00 |
December | 0.134479E+10 | 0.107953E+10 | 0.131323E+10 | 0.980355E+09 | 0.332875E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.144793E+11 | 0.690936E+10 | 0.119363E+11 | 0.571107E+10 | 0.622523E+10 | 0.00 | 0.00 |
Minimum of Months | 0.897304E+09 | 0.130411E+09 | 0.687780E+09 | 88495919.93 | 0.332875E+09 | 0.00 | 0.00 |
Maximum of Months | 0.142818E+10 | 0.107953E+10 | 0.131323E+10 | 0.980355E+09 | 0.659238E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113309E+10 | 0.848781E+09 | 0.108299E+10 | 0.747937E+09 | 0.335051E+09 | 0.00 | 0.00 |
February | 0.118432E+10 | 0.701938E+09 | 0.108697E+10 | 0.713832E+09 | 0.373143E+09 | 0.00 | 0.00 |
March | 0.126577E+10 | 0.601331E+09 | 0.111225E+10 | 0.627213E+09 | 0.485037E+09 | 0.00 | 0.00 |
April | 0.139383E+10 | 0.372683E+09 | 0.114914E+10 | 0.569686E+09 | 0.579457E+09 | 0.00 | 0.00 |
May | 0.132730E+10 | 0.257941E+09 | 0.103088E+10 | 0.463488E+09 | 0.567388E+09 | 0.00 | 0.00 |
June | 0.149540E+10 | 0.143375E+09 | 0.101013E+10 | 0.478424E+09 | 0.531702E+09 | 0.00 | 0.00 |
July | 0.155115E+10 | 66812064.94 | 0.983024E+09 | 0.407264E+09 | 0.575761E+09 | 0.00 | 0.00 |
August | 0.163036E+10 | 88425369.98 | 0.107988E+10 | 0.454855E+09 | 0.625021E+09 | 0.00 | 0.00 |
September | 0.154462E+10 | 0.198082E+09 | 0.109676E+10 | 0.593446E+09 | 0.503316E+09 | 0.00 | 0.00 |
October | 0.152677E+10 | 0.426595E+09 | 0.122099E+10 | 0.825128E+09 | 0.395867E+09 | 0.00 | 0.00 |
November | 0.122674E+10 | 0.628804E+09 | 0.111558E+10 | 0.769726E+09 | 0.345855E+09 | 0.00 | 0.00 |
December | 0.116529E+10 | 0.858592E+09 | 0.111995E+10 | 0.837122E+09 | 0.282831E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.164446E+11 | 0.519336E+10 | 0.130885E+11 | 0.748812E+10 | 0.560043E+10 | 0.00 | 0.00 |
Minimum of Months | 0.113309E+10 | 66812064.94 | 0.983024E+09 | 0.407264E+09 | 0.282831E+09 | 0.00 | 0.00 |
Maximum of Months | 0.163036E+10 | 0.858592E+09 | 0.122099E+10 | 0.837122E+09 | 0.625021E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.464076E+09 | 0.889942E+09 | 0.539737E+09 | 0.259253E+09 | 0.280485E+09 | 0.00 | 0.00 |
February | 0.585115E+09 | 0.722564E+09 | 0.623619E+09 | 0.304370E+09 | 0.319249E+09 | 0.00 | 0.00 |
March | 0.808448E+09 | 0.612933E+09 | 0.785916E+09 | 0.346157E+09 | 0.439758E+09 | 0.00 | 0.00 |
April | 0.109997E+10 | 0.381903E+09 | 0.972537E+09 | 0.431614E+09 | 0.540923E+09 | 0.00 | 0.00 |
May | 0.121436E+10 | 0.266137E+09 | 0.978164E+09 | 0.421674E+09 | 0.556490E+09 | 0.00 | 0.00 |
June | 0.148440E+10 | 0.142946E+09 | 0.102176E+10 | 0.489261E+09 | 0.532494E+09 | 0.00 | 0.00 |
July | 0.148235E+10 | 71492577.29 | 0.956240E+09 | 0.389192E+09 | 0.567048E+09 | 0.00 | 0.00 |
August | 0.141147E+10 | 95362169.64 | 0.959782E+09 | 0.364730E+09 | 0.595052E+09 | 0.00 | 0.00 |
September | 0.112187E+10 | 0.212889E+09 | 0.823788E+09 | 0.361784E+09 | 0.462004E+09 | 0.00 | 0.00 |
October | 0.875504E+09 | 0.453052E+09 | 0.754694E+09 | 0.403510E+09 | 0.351184E+09 | 0.00 | 0.00 |
November | 0.536110E+09 | 0.650758E+09 | 0.577715E+09 | 0.288175E+09 | 0.289540E+09 | 0.00 | 0.00 |
December | 0.414876E+09 | 0.905616E+09 | 0.507150E+09 | 0.271434E+09 | 0.235716E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.114985E+11 | 0.540559E+10 | 0.950110E+10 | 0.433116E+10 | 0.516994E+10 | 0.00 | 0.00 |
Minimum of Months | 0.414876E+09 | 71492577.29 | 0.507150E+09 | 0.259253E+09 | 0.235716E+09 | 0.00 | 0.00 |
Maximum of Months | 0.148440E+10 | 0.905616E+09 | 0.102176E+10 | 0.489261E+09 | 0.595052E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.106281E+10 | 0.441532E+09 | 0.921610E+09 | 0.716703E+09 | 0.204907E+09 | 0.00 | 0.00 |
February | 0.965883E+09 | 0.364166E+09 | 0.820531E+09 | 0.600515E+09 | 0.220016E+09 | 0.00 | 0.00 |
March | 0.816806E+09 | 0.312301E+09 | 0.675515E+09 | 0.412202E+09 | 0.263313E+09 | 0.00 | 0.00 |
April | 0.639830E+09 | 0.193292E+09 | 0.502062E+09 | 0.205750E+09 | 0.296311E+09 | 0.00 | 0.00 |
May | 0.465316E+09 | 0.130470E+09 | 0.349156E+09 | 78987514.10 | 0.270168E+09 | 0.00 | 0.00 |
June | 0.461504E+09 | 69275107.72 | 0.282470E+09 | 33917970.31 | 0.248552E+09 | 0.00 | 0.00 |
July | 0.570702E+09 | 30970245.91 | 0.323098E+09 | 50695688.68 | 0.272402E+09 | 0.00 | 0.00 |
August | 0.717231E+09 | 41945788.89 | 0.439521E+09 | 0.138622E+09 | 0.300899E+09 | 0.00 | 0.00 |
September | 0.886492E+09 | 99039860.73 | 0.603826E+09 | 0.339900E+09 | 0.263927E+09 | 0.00 | 0.00 |
October | 0.109754E+10 | 0.217650E+09 | 0.840620E+09 | 0.618343E+09 | 0.222277E+09 | 0.00 | 0.00 |
November | 0.109600E+10 | 0.328773E+09 | 0.917654E+09 | 0.706242E+09 | 0.211412E+09 | 0.00 | 0.00 |
December | 0.116748E+10 | 0.451332E+09 | 0.100503E+10 | 0.829635E+09 | 0.175390E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.994760E+10 | 0.268075E+10 | 0.768109E+10 | 0.473151E+10 | 0.294957E+10 | 0.00 | 0.00 |
Minimum of Months | 0.461504E+09 | 30970245.91 | 0.282470E+09 | 33917970.31 | 0.175390E+09 | 0.00 | 0.00 |
Maximum of Months | 0.116748E+10 | 0.451332E+09 | 0.100503E+10 | 0.829635E+09 | 0.300899E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 76805015.87 | 0.265040E+10 | 0.596026E+09 | 0.00 | 0.596026E+09 | 0.00 | 0.00 |
February | 0.189159E+09 | 0.214159E+10 | 0.672842E+09 | 0.00 | 0.672842E+09 | 0.00 | 0.00 |
March | 0.533815E+09 | 0.180304E+10 | 0.939826E+09 | 32669.46 | 0.939794E+09 | 0.00 | 0.00 |
April | 0.923233E+09 | 0.108077E+10 | 0.116004E+10 | 15539229.06 | 0.114450E+10 | 0.00 | 0.00 |
May | 0.135714E+10 | 0.760487E+09 | 0.129747E+10 | 84300915.40 | 0.121317E+10 | 0.00 | 0.00 |
June | 0.210040E+10 | 0.443199E+09 | 0.142957E+10 | 0.237740E+09 | 0.119183E+10 | 0.00 | 0.00 |
July | 0.218427E+10 | 0.271345E+09 | 0.135459E+10 | 0.115459E+09 | 0.123913E+10 | 0.00 | 0.00 |
August | 0.183387E+10 | 0.327947E+09 | 0.125712E+10 | 30765399.66 | 0.122636E+10 | 0.00 | 0.00 |
September | 0.118598E+10 | 0.639141E+09 | 0.971182E+09 | 692059.69 | 0.970490E+09 | 0.00 | 0.00 |
October | 0.532000E+09 | 0.133364E+10 | 0.748115E+09 | 0.00 | 0.748115E+09 | 0.00 | 0.00 |
November | 0.142438E+09 | 0.198562E+10 | 0.614832E+09 | 0.00 | 0.614832E+09 | 0.00 | 0.00 |
December | 16199926.95 | 0.277261E+10 | 0.507308E+09 | 0.00 | 0.507308E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110753E+11 | 0.162098E+11 | 0.115489E+11 | 0.484529E+09 | 0.110644E+11 | 0.00 | 0.00 |
Minimum of Months | 16199926.95 | 0.271345E+09 | 0.507308E+09 | 0.00 | 0.507308E+09 | 0.00 | 0.00 |
Maximum of Months | 0.218427E+10 | 0.277261E+10 | 0.142957E+10 | 0.237740E+09 | 0.123913E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 64470130.52 | 0.271340E+10 | 0.596026E+09 | 0.00 | 0.596026E+09 | 0.00 | 0.00 |
February | 0.172443E+09 | 0.218908E+10 | 0.672842E+09 | 0.00 | 0.672842E+09 | 0.00 | 0.00 |
March | 0.509191E+09 | 0.184092E+10 | 0.939826E+09 | 32669.46 | 0.939794E+09 | 0.00 | 0.00 |
April | 0.900380E+09 | 0.110436E+10 | 0.116004E+10 | 15539229.06 | 0.114450E+10 | 0.00 | 0.00 |
May | 0.133445E+10 | 0.778483E+09 | 0.129747E+10 | 84300915.40 | 0.121317E+10 | 0.00 | 0.00 |
June | 0.208097E+10 | 0.455473E+09 | 0.142957E+10 | 0.237740E+09 | 0.119183E+10 | 0.00 | 0.00 |
July | 0.216539E+10 | 0.282406E+09 | 0.135459E+10 | 0.115459E+09 | 0.123913E+10 | 0.00 | 0.00 |
August | 0.181574E+10 | 0.340312E+09 | 0.125712E+10 | 30765399.66 | 0.122636E+10 | 0.00 | 0.00 |
September | 0.117047E+10 | 0.656422E+09 | 0.971182E+09 | 692059.69 | 0.970490E+09 | 0.00 | 0.00 |
October | 0.515328E+09 | 0.136386E+10 | 0.748115E+09 | 0.00 | 0.748115E+09 | 0.00 | 0.00 |
November | 0.128148E+09 | 0.203339E+10 | 0.614832E+09 | 0.00 | 0.614832E+09 | 0.00 | 0.00 |
December | 12244213.16 | 0.284485E+10 | 0.507308E+09 | 0.00 | 0.507308E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108692E+11 | 0.166030E+11 | 0.115489E+11 | 0.484529E+09 | 0.110644E+11 | 0.00 | 0.00 |
Minimum of Months | 12244213.16 | 0.282406E+09 | 0.507308E+09 | 0.00 | 0.507308E+09 | 0.00 | 0.00 |
Maximum of Months | 0.216539E+10 | 0.284485E+10 | 0.142957E+10 | 0.237740E+09 | 0.123913E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.160397E+10 | 0.170913E+10 | 0.159507E+10 | 0.982081E+09 | 0.612993E+09 | 0.00 | 0.00 |
February | 0.173630E+10 | 0.141399E+10 | 0.161981E+10 | 0.927770E+09 | 0.692045E+09 | 0.00 | 0.00 |
March | 0.238671E+10 | 0.121949E+10 | 0.201350E+10 | 0.108926E+10 | 0.924242E+09 | 0.00 | 0.00 |
April | 0.311878E+10 | 0.777193E+09 | 0.237042E+10 | 0.120230E+10 | 0.116812E+10 | 0.00 | 0.00 |
May | 0.322121E+10 | 0.581714E+09 | 0.226194E+10 | 0.111310E+10 | 0.114884E+10 | 0.00 | 0.00 |
June | 0.374502E+10 | 0.353677E+09 | 0.231560E+10 | 0.123898E+10 | 0.107662E+10 | 0.00 | 0.00 |
July | 0.388365E+10 | 0.222368E+09 | 0.224755E+10 | 0.109932E+10 | 0.114823E+10 | 0.00 | 0.00 |
August | 0.380227E+10 | 0.260887E+09 | 0.229420E+10 | 0.109927E+10 | 0.119493E+10 | 0.00 | 0.00 |
September | 0.312615E+10 | 0.441754E+09 | 0.201507E+10 | 0.105138E+10 | 0.963692E+09 | 0.00 | 0.00 |
October | 0.266271E+10 | 0.869065E+09 | 0.199861E+10 | 0.125892E+10 | 0.739687E+09 | 0.00 | 0.00 |
November | 0.188945E+10 | 0.126614E+10 | 0.170596E+10 | 0.106374E+10 | 0.642217E+09 | 0.00 | 0.00 |
December | 0.158326E+10 | 0.173222E+10 | 0.159307E+10 | 0.107521E+10 | 0.517867E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.327595E+11 | 0.108476E+11 | 0.240308E+11 | 0.132013E+11 | 0.108295E+11 | 0.00 | 0.00 |
Minimum of Months | 0.158326E+10 | 0.222368E+09 | 0.159307E+10 | 0.927770E+09 | 0.517867E+09 | 0.00 | 0.00 |
Maximum of Months | 0.388365E+10 | 0.173222E+10 | 0.237042E+10 | 0.125892E+10 | 0.119493E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.269717E+10 | 0.188862E+10 | 0.255033E+10 | 0.182441E+10 | 0.725921E+09 | 0.00 | 0.00 |
February | 0.252160E+10 | 0.156954E+10 | 0.231936E+10 | 0.152864E+10 | 0.790714E+09 | 0.00 | 0.00 |
March | 0.228293E+10 | 0.138057E+10 | 0.204173E+10 | 0.104929E+10 | 0.992439E+09 | 0.00 | 0.00 |
April | 0.194870E+10 | 0.898167E+09 | 0.167569E+10 | 0.529075E+09 | 0.114661E+10 | 0.00 | 0.00 |
May | 0.161183E+10 | 0.651756E+09 | 0.133357E+10 | 0.229965E+09 | 0.110361E+10 | 0.00 | 0.00 |
June | 0.180583E+10 | 0.388344E+09 | 0.120910E+10 | 0.167838E+09 | 0.104126E+10 | 0.00 | 0.00 |
July | 0.210584E+10 | 0.245977E+09 | 0.128682E+10 | 0.168628E+09 | 0.111819E+10 | 0.00 | 0.00 |
August | 0.237665E+10 | 0.299992E+09 | 0.154977E+10 | 0.363417E+09 | 0.118635E+10 | 0.00 | 0.00 |
September | 0.262794E+10 | 0.559327E+09 | 0.187000E+10 | 0.865470E+09 | 0.100453E+10 | 0.00 | 0.00 |
October | 0.295169E+10 | 0.102724E+10 | 0.239630E+10 | 0.157402E+10 | 0.822273E+09 | 0.00 | 0.00 |
November | 0.281894E+10 | 0.142225E+10 | 0.254670E+10 | 0.179778E+10 | 0.748927E+09 | 0.00 | 0.00 |
December | 0.290854E+10 | 0.191306E+10 | 0.273225E+10 | 0.211188E+10 | 0.620371E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.286577E+11 | 0.122448E+11 | 0.235116E+11 | 0.122104E+11 | 0.113012E+11 | 0.00 | 0.00 |
Minimum of Months | 0.161183E+10 | 0.245977E+09 | 0.120910E+10 | 0.167838E+09 | 0.620371E+09 | 0.00 | 0.00 |
Maximum of Months | 0.295169E+10 | 0.191306E+10 | 0.273225E+10 | 0.211188E+10 | 0.118635E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770476E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161972393.7 | 81.21 | 0.00 | 0.00 |
February | 0.696222E+10 | -0.681597E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146250937.4 | 81.21 | 0.00 | 0.00 |
March | 0.770321E+10 | -0.754145E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161755825.3 | 81.21 | 0.00 | 0.00 |
April | 0.746496E+10 | -0.730858E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156381881.2 | 81.21 | 0.00 | 0.00 |
May | 0.770430E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161507281.8 | 81.21 | 0.00 | 0.00 |
June | 0.745677E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156235073.0 | 81.21 | 0.00 | 0.00 |
July | 0.771226E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161411183.4 | 81.21 | 0.00 | 0.00 |
August | 0.770422E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161416007.6 | 81.21 | 0.00 | 0.00 |
September | 0.746617E+10 | -0.730993E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156243832.4 | 81.21 | 0.00 | 0.00 |
October | 0.770303E+10 | -0.754143E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161601345.6 | 81.21 | 0.00 | 0.00 |
November | 0.744902E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156592906.6 | 81.21 | 0.00 | 0.00 |
December | 0.771285E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161980275.0 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907438E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190335E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696222E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161980275.0 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771285E+10 | -0.681597E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146250937.4 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYSLAUNDRY HPWH TANK
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.654010E+11 | -0.117112E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -869612573.4 | 81.67 | 0.00 | 0.00 |
February | 0.571225E+11 | -0.106339E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -773114089.6 | 81.67 | 0.00 | 0.00 |
March | 0.560211E+11 | -0.115728E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -821079035.9 | 81.67 | 0.00 | 0.00 |
April | 0.455310E+11 | -0.107909E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -756141867.0 | 81.67 | 0.00 | 0.00 |
May | 0.365372E+11 | -0.106197E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -751517518.5 | 81.68 | 0.00 | 0.00 |
June | 0.249494E+11 | -0.979677E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -687634961.0 | 81.68 | 0.00 | 0.00 |
July | 0.187601E+11 | -0.979634E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -691983342.1 | 81.68 | 0.00 | 0.00 |
August | 0.194566E+11 | -0.972599E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -703175472.7 | 81.68 | 0.00 | 0.00 |
September | 0.244285E+11 | -0.961322E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -708169200.9 | 81.68 | 0.00 | 0.00 |
October | 0.378239E+11 | -0.103618E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -783948460.9 | 81.67 | 0.00 | 0.00 |
November | 0.499767E+11 | -0.105422E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -809101122.8 | 81.67 | 0.00 | 0.00 |
December | 0.631403E+11 | -0.113863E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -873334644.2 | 81.67 | 0.00 | 0.00 |
Annual Sum or Average | 0.499148E+12 | -0.126551E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.922881E+10 | 81.68 | 0.00 | 0.00 |
Minimum of Months | 0.187601E+11 | -0.117112E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -873334644.2 | 81.67 | 0.00 | 0.00 |
Maximum of Months | 0.654010E+11 | -0.961322E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -687634961.0 | 81.68 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 HPWH TANK
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | -0.131203E+10 | -0.710309E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.141572E+10 | 59.21 | 0.00 | 0.00 |
February | -0.135565E+10 | -0.646706E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.124812E+10 | 59.18 | 0.00 | 0.00 |
March | -0.207597E+10 | -0.699601E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.130046E+10 | 59.26 | 0.00 | 0.00 |
April | -0.227876E+10 | -0.641669E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.116706E+10 | 59.30 | 0.00 | 0.00 |
May | -0.243554E+10 | -0.617459E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.113543E+10 | 59.34 | 0.00 | 0.00 |
June | -0.235084E+10 | -0.556340E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.100500E+10 | 59.39 | 0.00 | 0.00 |
July | -0.236322E+10 | -0.546095E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -994399693.2 | 59.41 | 0.00 | 0.00 |
August | -0.226654E+10 | -0.540579E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102160E+10 | 59.41 | 0.00 | 0.00 |
September | -0.224679E+10 | -0.540219E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.105478E+10 | 59.40 | 0.00 | 0.00 |
October | -0.220218E+10 | -0.594823E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.121439E+10 | 59.37 | 0.00 | 0.00 |
November | -0.176574E+10 | -0.619760E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.129511E+10 | 59.32 | 0.00 | 0.00 |
December | -0.120613E+10 | -0.682291E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.142502E+10 | 59.22 | 0.00 | 0.00 |
Annual Sum or Average | -0.238594E+11 | -0.739585E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.142771E+11 | 59.32 | 0.00 | 0.00 |
Minimum of Months | -0.243554E+10 | -0.710309E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.142502E+10 | 59.18 | 0.00 | 0.00 |
Maximum of Months | -0.120613E+10 | -0.540219E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -994399693.2 | 59.41 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.86 | 0.86 | 01-JAN-07:40 | 8519.94 | 37.80 | 292.33 | 288.17 | 1442.65 | 28.28 | 212.00 | 274.83 |
February | 282.00 | 0.87 | 0.86 | 01-FEB-07:40 | 9951.19 | 36.65 | 261.17 | 273.50 | 842.00 | 24.70 | 181.67 | 252.50 |
March | 351.33 | 0.87 | 0.86 | 01-MAR-07:10 | 1573.32 | 21.20 | 83.17 | 330.33 | 533.48 | 21.60 | 169.83 | 272.17 |
April | 381.83 | 0.87 | 0.86 | 01-APR-06:00 | 1138.72 | 20.26 | 63.00 | 351.67 | 477.88 | 21.99 | 287.33 | 303.33 |
May | 378.00 | 0.87 | 0.86 | 01-MAY-06:40 | 864.57 | 19.79 | 4.67 | 370.50 | 373.00 | 21.55 | 248.33 | 293.67 |
June | 412.83 | 0.88 | 0.86 | 01-JUN-06:19 | 672.90 | 18.98 | 5.00 | 366.50 | 289.67 | 20.80 | 117.00 | 176.50 |
July | 395.33 | 0.87 | 0.86 | 01-JUL-07:10 | 833.43 | 19.50 | 14.00 | 373.50 | 355.47 | 21.29 | 192.17 | 260.33 |
August | 408.83 | 0.87 | 0.86 | 01-AUG-06:49 | 1066.56 | 19.98 | 59.83 | 371.67 | 445.87 | 21.72 | 272.67 | 310.00 |
September | 359.33 | 0.87 | 0.86 | 01-SEP-06:49 | 1177.96 | 19.94 | 64.50 | 327.83 | 494.38 | 21.73 | 204.00 | 276.17 |
October | 329.00 | 0.87 | 0.86 | 01-OCT-07:10 | 5359.33 | 29.03 | 183.67 | 320.33 | 612.94 | 22.36 | 153.17 | 288.33 |
November | 284.17 | 0.86 | 0.86 | 01-NOV-06:49 | 9714.08 | 38.52 | 278.67 | 283.83 | 1316.38 | 27.87 | 217.67 | 270.00 |
December | 265.67 | 0.86 | 0.86 | 01-DEC-07:49 | 9714.49 | 39.95 | 263.67 | 269.67 | 2399.22 | 31.49 | 196.50 | 255.83 |
Annual Sum or Average | 4149.83 | 0.87 | 3677.36 | 25.64 | 1573.67 | 3927.50 | 726.89 | 23.37 | 2452.33 | 3233.67 | ||
Minimum of Months | 265.67 | 0.86 | 0.86 | 672.90 | 18.98 | 4.67 | 269.67 | 289.67 | 20.80 | 117.00 | 176.50 | |
Maximum of Months | 412.83 | 0.88 | 0.86 | 9951.19 | 39.95 | 292.33 | 373.50 | 2399.22 | 31.49 | 287.33 | 310.00 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.24 | 0.22 | 01-JAN-07:40 | 9034.01 | 37.88 | 292.33 | 293.67 | 1955.34 | 27.76 | 202.50 | 283.33 |
February | 282.00 | 0.24 | 0.22 | 01-FEB-07:40 | 10463.85 | 36.70 | 259.17 | 280.67 | 1353.15 | 24.20 | 169.83 | 266.00 |
March | 351.33 | 0.25 | 0.22 | 01-MAR-06:00 | 1931.36 | 21.24 | 89.67 | 341.00 | 890.78 | 21.54 | 175.67 | 311.00 |
April | 381.83 | 0.26 | 0.22 | 01-APR-06:40 | 1401.73 | 20.64 | 102.17 | 361.17 | 740.25 | 22.20 | 291.67 | 338.67 |
May | 378.00 | 0.26 | 0.22 | 01-MAY-06:19 | 1056.65 | 20.39 | 62.67 | 385.67 | 564.61 | 21.96 | 279.50 | 351.33 |
June | 412.83 | 0.25 | 0.22 | 01-JUN-05:49 | 822.83 | 19.76 | 34.83 | 391.17 | 439.22 | 21.36 | 175.00 | 340.83 |
July | 395.33 | 0.25 | 0.22 | 01-JUL-06:49 | 1010.06 | 20.18 | 61.33 | 389.33 | 531.63 | 21.77 | 256.17 | 351.00 |
August | 408.83 | 0.26 | 0.22 | 01-AUG-06:10 | 1292.08 | 20.48 | 125.33 | 383.17 | 670.83 | 22.05 | 286.17 | 355.50 |
September | 359.33 | 0.25 | 0.22 | 01-SEP-06:30 | 1499.93 | 20.12 | 85.83 | 340.33 | 815.64 | 21.76 | 191.33 | 313.67 |
October | 329.00 | 0.25 | 0.22 | 01-OCT-06:49 | 5811.23 | 28.93 | 182.50 | 324.83 | 1063.67 | 21.98 | 135.67 | 309.67 |
November | 284.17 | 0.24 | 0.22 | 01-NOV-06:49 | 10260.56 | 38.59 | 278.67 | 288.67 | 1863.77 | 27.32 | 178.00 | 278.00 |
December | 265.67 | 0.24 | 0.22 | 01-DEC-07:49 | 10330.76 | 40.00 | 263.83 | 274.83 | 3017.92 | 30.86 | 175.17 | 265.83 |
Annual Sum or Average | 4149.83 | 0.25 | 4016.09 | 25.95 | 1838.33 | 4054.50 | 1065.18 | 23.37 | 2516.67 | 3764.83 | ||
Minimum of Months | 265.67 | 0.24 | 0.22 | 822.83 | 19.76 | 34.83 | 274.83 | 439.22 | 21.36 | 135.67 | 265.83 | |
Maximum of Months | 412.83 | 0.26 | 0.22 | 10463.85 | 40.00 | 292.33 | 391.17 | 3017.92 | 30.86 | 291.67 | 355.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.66 | 0.60 | 01-JAN-11:30 | 365.67 | 14.60 | 0.00 | 233.00 | 181.84 | 18.21 | 0.00 | 103.83 |
February | 282.00 | 0.65 | 0.60 | 01-FEB-08:20 | 416.40 | 15.36 | 0.00 | 255.33 | 213.49 | 18.89 | 0.67 | 125.83 |
March | 351.33 | 0.64 | 0.60 | 01-MAR-07:30 | 514.26 | 16.20 | 0.00 | 324.33 | 243.63 | 19.54 | 12.67 | 171.33 |
April | 381.83 | 0.62 | 0.60 | 01-APR-06:00 | 651.92 | 17.77 | 0.00 | 364.17 | 310.02 | 21.00 | 117.17 | 329.50 |
May | 378.00 | 0.61 | 0.60 | 01-MAY-06:19 | 788.44 | 18.13 | 4.33 | 396.00 | 334.15 | 21.28 | 138.17 | 353.00 |
June | 412.83 | 0.61 | 0.60 | 01-JUN-05:40 | 828.04 | 20.03 | 73.50 | 405.67 | 317.73 | 21.57 | 138.50 | 307.17 |
July | 395.33 | 0.61 | 0.60 | 01-JUL-06:49 | 800.77 | 18.83 | 27.00 | 399.50 | 344.89 | 21.36 | 153.83 | 348.00 |
August | 408.83 | 0.62 | 0.60 | 01-AUG-05:49 | 705.93 | 17.82 | 0.00 | 387.17 | 343.15 | 21.09 | 169.33 | 349.00 |
September | 359.33 | 0.63 | 0.60 | 01-SEP-06:40 | 533.26 | 16.70 | 0.00 | 331.33 | 261.28 | 20.02 | 41.67 | 225.83 |
October | 329.00 | 0.66 | 0.60 | 01-OCT-09:30 | 363.88 | 15.14 | 0.00 | 284.33 | 192.26 | 18.66 | 0.00 | 121.83 |
November | 284.17 | 0.65 | 0.60 | 01-NOV-07:30 | 376.92 | 15.10 | 0.00 | 255.33 | 198.40 | 18.69 | 0.00 | 131.17 |
December | 265.67 | 0.67 | 0.60 | 01-DEC-08:30 | 302.77 | 13.83 | 0.00 | 224.17 | 166.83 | 17.59 | 0.00 | 73.67 |
Annual Sum or Average | 4149.83 | 0.63 | 578.63 | 16.87 | 104.83 | 3860.33 | 267.71 | 20.01 | 772.00 | 2640.17 | ||
Minimum of Months | 265.67 | 0.61 | 0.60 | 302.77 | 13.83 | 0.00 | 224.17 | 166.83 | 17.59 | 0.00 | 73.67 | |
Maximum of Months | 412.83 | 0.67 | 0.60 | 828.04 | 20.03 | 73.50 | 405.67 | 344.89 | 21.57 | 169.33 | 353.00 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.66 | 0.60 | 01-JAN-11:30 | 365.67 | 14.60 | 0.00 | 233.00 | 181.84 | 18.21 | 0.00 | 103.83 |
February | 282.00 | 0.65 | 0.60 | 01-FEB-08:20 | 416.40 | 15.36 | 0.00 | 255.33 | 213.49 | 18.89 | 0.67 | 125.83 |
March | 351.33 | 0.64 | 0.60 | 01-MAR-07:30 | 514.26 | 16.20 | 0.00 | 324.33 | 243.63 | 19.54 | 12.67 | 171.33 |
April | 381.83 | 0.62 | 0.60 | 01-APR-06:00 | 651.92 | 17.77 | 0.00 | 364.17 | 310.02 | 21.00 | 117.17 | 329.50 |
May | 378.00 | 0.61 | 0.60 | 01-MAY-06:19 | 788.44 | 18.13 | 4.33 | 396.00 | 334.15 | 21.28 | 138.17 | 353.00 |
June | 412.83 | 0.61 | 0.60 | 01-JUN-05:40 | 828.04 | 20.03 | 73.50 | 405.67 | 317.73 | 21.57 | 138.50 | 307.17 |
July | 395.33 | 0.61 | 0.60 | 01-JUL-06:49 | 800.77 | 18.83 | 27.00 | 399.50 | 344.89 | 21.36 | 153.83 | 348.00 |
August | 408.83 | 0.62 | 0.60 | 01-AUG-05:49 | 705.93 | 17.82 | 0.00 | 387.17 | 343.15 | 21.09 | 169.33 | 349.00 |
September | 359.33 | 0.63 | 0.60 | 01-SEP-06:40 | 533.26 | 16.70 | 0.00 | 331.33 | 261.28 | 20.02 | 41.67 | 225.83 |
October | 329.00 | 0.66 | 0.60 | 01-OCT-09:30 | 363.88 | 15.14 | 0.00 | 284.33 | 192.26 | 18.66 | 0.00 | 121.83 |
November | 284.17 | 0.65 | 0.60 | 01-NOV-07:30 | 376.92 | 15.10 | 0.00 | 255.33 | 198.40 | 18.69 | 0.00 | 131.17 |
December | 265.67 | 0.67 | 0.60 | 01-DEC-08:30 | 302.77 | 13.83 | 0.00 | 224.17 | 166.83 | 17.59 | 0.00 | 73.67 |
Annual Sum or Average | 4149.83 | 0.63 | 578.63 | 16.87 | 104.83 | 3860.33 | 267.71 | 20.01 | 772.00 | 2640.17 | ||
Minimum of Months | 265.67 | 0.61 | 0.60 | 302.77 | 13.83 | 0.00 | 224.17 | 166.83 | 17.59 | 0.00 | 73.67 | |
Maximum of Months | 412.83 | 0.67 | 0.60 | 828.04 | 20.03 | 73.50 | 405.67 | 344.89 | 21.57 | 169.33 | 353.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.518396E+11 | 126043.38 | 21-JAN-11:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.489949E+11 | 126997.30 | 07-FEB-11:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.633411E+11 | 127070.97 | 07-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.513192E+11 | 125529.76 | 04-APR-07:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.298380E+11 | 115549.24 | 06-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.671742E+10 | 94473.19 | 09-JUN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 94698466.68 | 27234.78 | 31-AUG-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.496598E+10 | 60747.06 | 20-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471928E+11 | 123847.88 | 14-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.584179E+11 | 125971.25 | 24-NOV-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.536657E+11 | 131962.95 | 28-DEC-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.416387E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.633411E+11 | 131962.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.545075E+09 | 1370.00 | 19-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.327588E+09 | 1197.30 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169953E+09 | 992.98 | 04-MAR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 26294288.29 | 496.28 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16835739.81 | 485.34 | 05-MAY-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 369180.96 | 129.14 | 09-JUN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 77726144.35 | 1165.11 | 26-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146533E+09 | 866.36 | 11-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.516640E+09 | 1438.49 | 09-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.545075E+09 | 1438.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 97093695.90 | 570.15 | 19-JAN-11:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 36587478.48 | 412.38 | 06-FEB-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 55878379.20 | 355.30 | 08-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 97093695.90 | 570.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102242E+09 | 379.88 | 19-JAN-11:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 48403427.35 | 266.59 | 06-FEB-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 90414686.43 | 272.48 | 08-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.241060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102242E+09 | 379.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 838227.39 | 185.35 | 21-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 167770.59 | 139.19 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 167918.63 | 139.27 | 09-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1173916.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 838227.39 | 185.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 76692736.45 | 1937.70 | 19-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9558678.84 | 1148.42 | 16-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 78330.04 | 86.82 | 22-MAR-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10650464.14 | 1078.50 | 25-OCT-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 811621.93 | 318.07 | 10-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 34132424.43 | 2458.99 | 08-DEC-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131924E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76692736.45 | 2458.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.863005E+09 | 4890.38 | 19-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.219058E+09 | 3714.90 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 270329.27 | 423.34 | 04-MAR-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.612936E+09 | 3995.00 | 08-DEC-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.863005E+09 | 4890.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.139781E+10 | 2938.94 | 21-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.756878E+09 | 2743.47 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123990E+09 | 1626.80 | 04-MAR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 70834396.64 | 2059.43 | 26-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163292E+09 | 1709.34 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146954E+10 | 2938.63 | 15-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.398234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.146954E+10 | 2938.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.542712E+09 | 2622.80 | 20-JAN-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.281245E+09 | 2033.01 | 01-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10415872.30 | 1008.95 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11603.19 | 0.34 | 17-APR-15:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18918.41 | 0.34 | 29-MAY-08:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 18356.35 | 0.34 | 22-JUN-18:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20899.22 | 0.34 | 10-JUL-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20658.66 | 0.34 | 25-AUG-21:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23209.11 | 0.34 | 11-SEP-08:59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7750088.26 | 608.86 | 26-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 27158126.01 | 1190.04 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.487066E+09 | 3010.50 | 15-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 11603.19 | 0.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.542712E+09 | 3010.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.181953E+10 | 8843.40 | 17-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118421E+10 | 8765.00 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.482958E+09 | 5801.77 | 03-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 63967886.45 | 4637.88 | 21-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25666927.63 | 4105.11 | 25-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6320298.15 | 3659.08 | 09-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3867836.31 | 2618.44 | 02-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3863335.89 | 2719.85 | 23-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5918239.64 | 3218.06 | 08-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.201355E+09 | 8634.33 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.597034E+09 | 6069.39 | 10-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186262E+10 | 8785.39 | 21-DEC-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.625732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3863335.89 | 2618.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.186262E+10 | 8843.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.308815E+10 | 8836.24 | 20-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.203833E+10 | 8859.66 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.768188E+09 | 8578.13 | 04-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 89455490.50 | 5181.86 | 24-APR-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28451437.06 | 5900.81 | 20-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5545027.46 | 5549.12 | 19-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4019798.22 | 4308.32 | 15-JUL-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4500690.34 | 4555.73 | 31-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7992264.18 | 5089.17 | 17-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.334145E+09 | 8718.35 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129005E+10 | 8731.21 | 27-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.341460E+10 | 8921.18 | 15-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4019798.22 | 4308.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.341460E+10 | 8921.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.101408E+11 | 48774.42 | 20-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.627978E+10 | 48666.11 | 06-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101927E+10 | 37720.89 | 06-MAR-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108297E+09 | 41944.95 | 05-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 46347309.95 | 41663.32 | 06-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20771268.64 | 26026.81 | 19-JUN-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9013025.89 | 16795.43 | 08-JUL-18:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22611145.80 | 23384.85 | 31-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41514909.65 | 34908.42 | 21-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.594264E+09 | 34153.90 | 30-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.302863E+10 | 47302.36 | 27-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123850E+11 | 49440.87 | 15-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.336963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9013025.89 | 16795.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.123850E+11 | 49440.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.194487E+10 | 8651.03 | 20-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128274E+10 | 8424.65 | 16-FEB-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.479802E+09 | 5858.97 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 64883222.88 | 4085.47 | 23-APR-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16393301.27 | 3466.27 | 03-MAY-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1656608.16 | 3553.02 | 01-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 364597.95 | 1570.32 | 17-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 502999.35 | 2714.57 | 23-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2196303.22 | 3485.85 | 08-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.206047E+09 | 8423.41 | 25-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.652392E+09 | 6009.72 | 04-NOV-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.196796E+10 | 8555.04 | 08-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.661980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 364597.95 | 1570.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.196796E+10 | 8651.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.316885E+10 | 8635.80 | 20-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.212214E+10 | 8564.56 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.724590E+09 | 6653.16 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 98402894.47 | 5586.13 | 20-APR-20:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20991503.53 | 5528.39 | 11-MAY-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1280864.12 | 3157.48 | 08-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 812101.96 | 2085.20 | 13-JUL-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 760483.46 | 1941.74 | 04-AUG-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4841523.20 | 4689.86 | 25-SEP-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.320096E+09 | 8425.59 | 25-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129086E+10 | 8296.58 | 26-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.345621E+10 | 8577.94 | 21-DEC-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 760483.46 | 1941.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.345621E+10 | 8635.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.789398E+09 | 2690.99 | 20-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.537769E+09 | 2698.38 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.285816E+09 | 2605.18 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 64550640.23 | 1243.13 | 02-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25593892.60 | 1327.08 | 12-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4459400.49 | 976.27 | 19-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 966826.18 | 968.19 | 06-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 943580.37 | 758.03 | 28-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1648688.96 | 875.81 | 25-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125511E+09 | 2662.82 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.342062E+09 | 2585.01 | 10-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.800819E+09 | 2706.08 | 22-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.297954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 943580.37 | 758.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.800819E+09 | 2706.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.121606E+10 | 2684.86 | 20-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.827129E+09 | 2703.67 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.399201E+09 | 2633.40 | 04-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 74106250.04 | 1414.30 | 07-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24634829.47 | 1420.70 | 31-MAY-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3897868.99 | 1471.17 | 20-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 738052.64 | 1054.21 | 17-JUL-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1187311.18 | 1271.17 | 28-AUG-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2660818.86 | 1381.15 | 27-SEP-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.187920E+09 | 2665.53 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.630012E+09 | 2675.93 | 27-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131389E+10 | 2710.49 | 15-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.468144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 738052.64 | 1054.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131389E+10 | 2710.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.140352E+10 | 12343.42 | 17-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.932804E+09 | 12074.42 | 16-FEB-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.475235E+09 | 8047.25 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139057E+09 | 5338.95 | 25-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 66769518.92 | 5412.88 | 24-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11605407.08 | 5182.87 | 08-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10191960.46 | 4459.96 | 05-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9218906.27 | 4821.18 | 02-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4917350.80 | 4630.81 | 23-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.219814E+09 | 12117.12 | 25-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.422554E+09 | 6354.02 | 09-NOV-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133513E+10 | 12228.21 | 08-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.503082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4917350.80 | 4459.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.140352E+10 | 12343.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SWHSYS1 HPWH DXCOIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.523182E+11 | 0.523182E+11 | 36909.62 | 31-JAN-05:15 | 36909.62 | 0.00 |
February | 0.00 | 0.00 | 0.487120E+11 | 0.487120E+11 | 39578.47 | 06-FEB-18:00 | 39578.47 | 0.00 |
March | 0.00 | 0.00 | 0.544587E+11 | 0.544587E+11 | 44472.02 | 01-MAR-11:17 | 44472.02 | 0.00 |
April | 0.00 | 0.00 | 0.509727E+11 | 0.509727E+11 | 48818.79 | 01-APR-09:20 | 48818.79 | 0.00 |
May | 0.00 | 0.00 | 0.499123E+11 | 0.499123E+11 | 53526.34 | 01-MAY-05:05 | 53526.34 | 0.00 |
June | 0.00 | 0.00 | 0.457749E+11 | 0.457737E+11 | 58772.08 | 01-JUN-04:07 | 58772.08 | 0.00 |
July | 0.00 | 0.00 | 0.453848E+11 | 0.440648E+11 | 62036.44 | 01-JUL-10:15 | 60069.39 | 0.00 |
August | 0.00 | 0.00 | 0.445830E+11 | 0.430883E+11 | 60381.34 | 31-AUG-06:20 | 58280.83 | 0.00 |
September | 0.00 | 0.00 | 0.440486E+11 | 0.440486E+11 | 57082.01 | 30-SEP-05:08 | 57082.01 | 0.00 |
October | 0.00 | 0.00 | 0.468845E+11 | 0.468845E+11 | 49358.44 | 31-OCT-04:15 | 49358.44 | 0.00 |
November | 0.00 | 0.00 | 0.467772E+11 | 0.467772E+11 | 41566.90 | 30-NOV-08:13 | 41566.90 | 0.00 |
December | 0.00 | 0.00 | 0.493823E+11 | 0.493823E+11 | 35698.64 | 31-DEC-06:15 | 35698.64 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.579209E+12 | 0.576393E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.440486E+11 | 0.430883E+11 | 35698.64 | 35698.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.544587E+11 | 0.544587E+11 | 62036.44 | 60069.39 | 0.00 |
Report: CoilReportMonthly
For: SWHSYSLAUNDRY HPWH DXCOIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.370871E+11 | 0.370871E+11 | 46700.35 | 31-JAN-23:50 | 46700.35 | 0.00 |
February | 0.00 | 0.00 | 0.359957E+11 | 0.359957E+11 | 50079.74 | 06-FEB-20:00 | 50079.74 | 0.00 |
March | 0.00 | 0.00 | 0.446998E+11 | 0.446998E+11 | 56276.13 | 01-MAR-17:05 | 56276.13 | 0.00 |
April | 0.00 | 0.00 | 0.473355E+11 | 0.473355E+11 | 61780.16 | 01-APR-16:10 | 61780.16 | 0.00 |
May | 0.00 | 0.00 | 0.535113E+11 | 0.535113E+11 | 67741.03 | 01-MAY-16:30 | 67741.03 | 0.00 |
June | 0.00 | 0.00 | 0.568871E+11 | 0.568863E+11 | 74383.37 | 01-JUN-16:10 | 74383.37 | 0.00 |
July | 0.00 | 0.00 | 0.622217E+11 | 0.604316E+11 | 78516.82 | 01-JUL-16:10 | 76050.46 | 0.00 |
August | 0.00 | 0.00 | 0.607106E+11 | 0.586926E+11 | 76421.08 | 31-AUG-16:10 | 73784.50 | 0.00 |
September | 0.00 | 0.00 | 0.553453E+11 | 0.553453E+11 | 72243.34 | 30-SEP-16:20 | 72243.34 | 0.00 |
October | 0.00 | 0.00 | 0.493556E+11 | 0.493556E+11 | 62463.48 | 31-OCT-21:00 | 62463.48 | 0.00 |
November | 0.00 | 0.00 | 0.402341E+11 | 0.402341E+11 | 52597.55 | 30-NOV-17:10 | 52597.55 | 0.00 |
December | 0.00 | 0.00 | 0.357524E+11 | 0.357524E+11 | 45166.95 | 31-DEC-17:10 | 45166.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.579136E+12 | 0.575327E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.357524E+11 | 0.357524E+11 | 45166.95 | 45166.95 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.622217E+11 | 0.604316E+11 | 78516.82 | 76050.46 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.113883E+10 | 0.113883E+10 | 37457.00 | 01-JAN-14:00 | 37457.00 | 0.00 |
February | 0.00 | 0.00 | 0.638581E+10 | 0.638581E+10 | 121215.04 | 14-FEB-16:03 | 121215.04 | 0.00 |
March | 0.00 | 0.00 | 0.230089E+11 | 0.230089E+11 | 128031.73 | 08-MAR-16:03 | 128031.73 | 0.00 |
April | 0.00 | 0.00 | 0.944036E+11 | 0.944036E+11 | 192474.67 | 28-APR-18:03 | 192474.67 | 0.00 |
May | 0.00 | 0.00 | 0.177214E+12 | 0.177214E+12 | 223243.61 | 19-MAY-18:20 | 223243.61 | 0.12 |
June | 0.00 | 0.00 | 0.313086E+12 | 0.312872E+12 | 259692.47 | 21-JUN-18:17 | 259692.47 | 0.37 |
July | 0.00 | 0.00 | 0.430432E+12 | 0.407888E+12 | 325466.77 | 31-JUL-20:00 | 177102.73 | 0.94 |
August | 0.00 | 0.00 | 0.384622E+12 | 0.372824E+12 | 278330.46 | 14-AUG-21:00 | 230292.74 | 0.95 |
September | 0.00 | 0.00 | 0.247725E+12 | 0.246783E+12 | 223911.29 | 13-SEP-18:03 | 223911.29 | 0.58 |
October | 0.00 | 0.00 | 0.106274E+12 | 0.106181E+12 | 194619.06 | 05-OCT-18:03 | 194619.06 | 0.13 |
November | 0.00 | 0.00 | 0.336714E+10 | 0.336714E+10 | 60652.80 | 09-NOV-14:00 | 60652.80 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.178766E+13 | 0.175207E+13 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.430432E+12 | 0.407888E+12 | 325466.77 | 259692.47 | 0.95 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 28569562.60 | 28569562.60 | 2387.63 | 05-JAN-14:00 | 2387.63 | 0.00 |
February | 0.00 | 0.00 | 0.354954E+09 | 0.354954E+09 | 12481.87 | 14-FEB-16:01 | 12481.87 | 0.00 |
March | 0.00 | 0.00 | 0.140659E+10 | 0.140659E+10 | 13330.12 | 08-MAR-16:01 | 13330.12 | 0.00 |
April | 0.00 | 0.00 | 0.583698E+10 | 0.583698E+10 | 14834.76 | 29-APR-15:01 | 14834.76 | 0.00 |
May | 0.00 | 0.00 | 0.112270E+11 | 0.112268E+11 | 16219.97 | 19-MAY-15:02 | 16219.97 | 0.10 |
June | 0.00 | 0.00 | 0.190095E+11 | 0.189913E+11 | 18773.38 | 28-JUN-15:02 | 18773.38 | 0.34 |
July | 0.00 | 0.00 | 0.293128E+11 | 0.257760E+11 | 28688.40 | 01-JUL-01:10 | 11556.11 | 0.75 |
August | 0.00 | 0.00 | 0.254886E+11 | 0.234413E+11 | 24430.19 | 13-AUG-08:53 | 12961.27 | 0.77 |
September | 0.00 | 0.00 | 0.154881E+11 | 0.151791E+11 | 23975.55 | 05-SEP-12:30 | 14001.59 | 0.45 |
October | 0.00 | 0.00 | 0.632881E+10 | 0.629081E+10 | 15887.79 | 02-OCT-16:50 | 11609.35 | 0.10 |
November | 0.00 | 0.00 | 0.142365E+09 | 0.142365E+09 | 8394.05 | 09-NOV-14:00 | 8394.05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.114624E+12 | 0.108675E+12 | 0.21 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.293128E+11 | 0.257760E+11 | 28688.40 | 18773.38 | 0.77 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.118834E+10 | 0.116796E+10 | 16607.54 | 05-JAN-16:01 | 16607.54 | 0.01 |
February | 0.00 | 0.00 | 0.170876E+10 | 0.165629E+10 | 17568.74 | 14-FEB-16:01 | 17568.74 | 0.03 |
March | 0.00 | 0.00 | 0.272423E+10 | 0.267772E+10 | 17688.16 | 08-MAR-16:01 | 17688.16 | 0.03 |
April | 0.00 | 0.00 | 0.520770E+10 | 0.516547E+10 | 18122.97 | 29-APR-15:01 | 18122.97 | 0.02 |
May | 0.00 | 0.00 | 0.651506E+10 | 0.539106E+10 | 18302.20 | 15-MAY-18:01 | 18302.20 | 0.36 |
June | 0.00 | 0.00 | 0.939100E+10 | 0.670457E+10 | 18300.12 | 20-JUN-15:01 | 18300.12 | 0.78 |
July | 0.00 | 0.00 | 0.114386E+11 | 0.715766E+10 | 18008.02 | 09-JUL-08:61 | 14210.50 | 0.97 |
August | 0.00 | 0.00 | 0.114219E+11 | 0.719476E+10 | 17477.88 | 26-AUG-08:61 | 13847.66 | 0.96 |
September | 0.00 | 0.00 | 0.923131E+10 | 0.609177E+10 | 16962.79 | 21-SEP-08:61 | 16962.79 | 0.85 |
October | 0.00 | 0.00 | 0.620084E+10 | 0.508112E+10 | 17849.83 | 31-OCT-15:01 | 17849.83 | 0.34 |
November | 0.00 | 0.00 | 0.230197E+10 | 0.214880E+10 | 16560.28 | 05-NOV-15:01 | 16560.28 | 0.08 |
December | 0.00 | 0.00 | 0.101536E+10 | 0.997396E+09 | 16558.83 | 04-DEC-16:01 | 16558.83 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.683451E+11 | 0.514346E+11 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 0.101536E+10 | 0.997396E+09 | 16558.83 | 13847.66 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.114386E+11 | 0.719476E+10 | 18302.20 | 18302.20 | 0.97 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.216814E+09 | 0.213180E+09 | 16408.57 | 05-JAN-16:01 | 16408.57 | 0.00 |
February | 0.00 | 0.00 | 0.478393E+09 | 0.467046E+09 | 17354.67 | 14-FEB-16:01 | 17354.67 | 0.01 |
March | 0.00 | 0.00 | 0.946371E+09 | 0.929081E+09 | 18589.62 | 30-MAR-18:11 | 18589.62 | 0.02 |
April | 0.00 | 0.00 | 0.311724E+10 | 0.308194E+10 | 20530.67 | 25-APR-16:21 | 20530.67 | 0.02 |
May | 0.00 | 0.00 | 0.521143E+10 | 0.427864E+10 | 18608.00 | 20-MAY-21:51 | 18608.00 | 0.30 |
June | 0.00 | 0.00 | 0.867770E+10 | 0.636050E+10 | 19739.55 | 14-JUN-08:21 | 19739.55 | 0.68 |
July | 0.00 | 0.00 | 0.102535E+11 | 0.673441E+10 | 20665.55 | 04-JUL-08:31 | 15708.93 | 0.79 |
August | 0.00 | 0.00 | 0.943399E+10 | 0.602488E+10 | 19837.57 | 14-AUG-08:51 | 14211.35 | 0.77 |
September | 0.00 | 0.00 | 0.625284E+10 | 0.384030E+10 | 17896.85 | 21-SEP-21:51 | 17896.85 | 0.64 |
October | 0.00 | 0.00 | 0.282335E+10 | 0.202370E+10 | 17724.78 | 05-OCT-21:51 | 17724.78 | 0.25 |
November | 0.00 | 0.00 | 0.565994E+09 | 0.511787E+09 | 16361.17 | 05-NOV-15:01 | 16361.17 | 0.04 |
December | 0.00 | 0.00 | 0.140817E+09 | 0.137432E+09 | 16358.60 | 29-DEC-16:01 | 16358.60 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.481185E+11 | 0.346029E+11 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 0.140817E+09 | 0.137432E+09 | 16358.60 | 14211.35 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.102535E+11 | 0.673441E+10 | 20665.55 | 20530.67 | 0.79 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.293638E+11 | 0.293638E+11 | 58603.71 | 03-JAN-12:40 | 58603.71 | 0.00 |
February | 0.00 | 0.00 | 0.280725E+11 | 0.280725E+11 | 59885.15 | 14-FEB-13:00 | 59885.15 | 0.00 |
March | 0.00 | 0.00 | 0.270912E+11 | 0.270912E+11 | 50752.96 | 08-MAR-13:30 | 50752.96 | 0.00 |
April | 0.00 | 0.00 | 0.286174E+11 | 0.286174E+11 | 37332.78 | 13-APR-13:15 | 37332.78 | 0.00 |
May | 0.00 | 0.00 | 0.270427E+11 | 0.208158E+11 | 26820.63 | 13-MAY-13:10 | 26820.63 | 0.33 |
June | 0.00 | 0.00 | 0.356929E+11 | 0.180487E+11 | 29655.65 | 29-JUN-14:00 | 20349.33 | 0.85 |
July | 0.00 | 0.00 | 0.486341E+11 | 0.240784E+11 | 33742.66 | 23-JUL-13:30 | 25819.50 | 1.00 |
August | 0.00 | 0.00 | 0.545676E+11 | 0.311159E+11 | 43465.16 | 22-AUG-13:20 | 42495.52 | 1.00 |
September | 0.00 | 0.00 | 0.565180E+11 | 0.358866E+11 | 55457.92 | 28-SEP-13:30 | 45430.89 | 0.99 |
October | 0.00 | 0.00 | 0.536119E+11 | 0.466300E+11 | 59392.61 | 19-OCT-12:30 | 59392.61 | 0.34 |
November | 0.00 | 0.00 | 0.405322E+11 | 0.405322E+11 | 59074.51 | 20-NOV-13:30 | 59074.51 | 0.00 |
December | 0.00 | 0.00 | 0.326054E+11 | 0.326054E+11 | 60315.49 | 31-DEC-13:40 | 60315.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.462350E+12 | 0.362858E+12 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 0.270427E+11 | 0.180487E+11 | 26820.63 | 20349.33 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.565180E+11 | 0.466300E+11 | 60315.49 | 60315.49 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.665157E+09 | 0.665157E+09 | 65333.98 | 01-JAN-09:02 | 65333.98 | 0.00 |
February | 0.00 | 0.00 | 0.241951E+10 | 0.239211E+10 | 82560.36 | 14-FEB-16:01 | 82560.36 | 0.01 |
March | 0.00 | 0.00 | 0.931585E+10 | 0.908770E+10 | 85823.96 | 08-MAR-16:01 | 85823.96 | 0.03 |
April | 0.00 | 0.00 | 0.214308E+11 | 0.213782E+11 | 92816.71 | 29-APR-15:01 | 92816.71 | 0.00 |
May | 0.00 | 0.00 | 0.349759E+11 | 0.307150E+11 | 93833.68 | 13-MAY-15:01 | 93833.68 | 0.23 |
June | 0.00 | 0.00 | 0.533195E+11 | 0.421814E+11 | 96824.68 | 17-JUN-08:31 | 96824.68 | 0.58 |
July | 0.00 | 0.00 | 0.641590E+11 | 0.435663E+11 | 100825.65 | 31-JUL-21:51 | 75412.00 | 0.77 |
August | 0.00 | 0.00 | 0.568277E+11 | 0.375138E+11 | 96122.10 | 14-AUG-08:51 | 72774.79 | 0.72 |
September | 0.00 | 0.00 | 0.373679E+11 | 0.259134E+11 | 90480.22 | 05-SEP-21:51 | 71331.43 | 0.54 |
October | 0.00 | 0.00 | 0.182900E+11 | 0.149770E+11 | 89146.17 | 09-OCT-15:01 | 89146.17 | 0.18 |
November | 0.00 | 0.00 | 0.463838E+10 | 0.434521E+10 | 80727.98 | 09-NOV-19:02 | 80727.98 | 0.04 |
December | 0.00 | 0.00 | 0.459772E+09 | 0.459772E+09 | 77242.74 | 02-DEC-09:02 | 77242.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.303870E+12 | 0.233195E+12 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 0.459772E+09 | 0.459772E+09 | 65333.98 | 65333.98 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.641590E+11 | 0.435663E+11 | 100825.65 | 96824.68 | 0.77 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.117208E+10 | 0.112944E+10 | 14593.35 | 05-JAN-16:01 | 14593.35 | 0.02 |
February | 0.00 | 0.00 | 0.151826E+10 | 0.142565E+10 | 15437.57 | 14-FEB-16:01 | 15437.57 | 0.05 |
March | 0.00 | 0.00 | 0.300491E+10 | 0.286816E+10 | 15382.69 | 07-MAR-16:01 | 15382.69 | 0.06 |
April | 0.00 | 0.00 | 0.597147E+10 | 0.588887E+10 | 15920.79 | 29-APR-15:01 | 15920.79 | 0.04 |
May | 0.00 | 0.00 | 0.733419E+10 | 0.613189E+10 | 16080.91 | 15-MAY-18:01 | 16080.91 | 0.39 |
June | 0.00 | 0.00 | 0.103142E+11 | 0.765906E+10 | 16077.57 | 20-JUN-15:01 | 16077.57 | 0.81 |
July | 0.00 | 0.00 | 0.126094E+11 | 0.839558E+10 | 14839.39 | 17-JUL-08:61 | 12722.87 | 0.99 |
August | 0.00 | 0.00 | 0.122951E+11 | 0.825276E+10 | 13979.64 | 23-AUG-08:61 | 12926.38 | 0.98 |
September | 0.00 | 0.00 | 0.954486E+10 | 0.656336E+10 | 14942.43 | 21-SEP-08:61 | 14942.43 | 0.87 |
October | 0.00 | 0.00 | 0.625176E+10 | 0.512674E+10 | 15684.45 | 31-OCT-15:01 | 15684.45 | 0.36 |
November | 0.00 | 0.00 | 0.234599E+10 | 0.217780E+10 | 14549.48 | 06-NOV-09:02 | 14549.48 | 0.09 |
December | 0.00 | 0.00 | 0.971707E+09 | 0.935924E+09 | 14550.77 | 10-DEC-09:01 | 14550.77 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.733338E+11 | 0.565552E+11 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 0.971707E+09 | 0.935924E+09 | 13979.64 | 12722.87 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.126094E+11 | 0.839558E+10 | 16080.91 | 16080.91 | 0.99 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.180227E+09 | 0.159972E+09 | 14251.08 | 01-JAN-09:02 | 14251.08 | 0.01 |
February | 0.00 | 0.00 | 0.350033E+09 | 0.309908E+09 | 15299.02 | 14-FEB-16:01 | 15299.02 | 0.02 |
March | 0.00 | 0.00 | 0.127154E+10 | 0.121133E+10 | 15244.33 | 07-MAR-16:01 | 15244.33 | 0.04 |
April | 0.00 | 0.00 | 0.410732E+10 | 0.403822E+10 | 17226.86 | 28-APR-08:51 | 17226.86 | 0.04 |
May | 0.00 | 0.00 | 0.601397E+10 | 0.497803E+10 | 17613.66 | 13-MAY-08:51 | 17613.66 | 0.33 |
June | 0.00 | 0.00 | 0.926975E+10 | 0.687981E+10 | 19672.89 | 20-JUN-08:32 | 19672.89 | 0.72 |
July | 0.00 | 0.00 | 0.110397E+11 | 0.746151E+10 | 20898.07 | 04-JUL-08:61 | 18000.72 | 0.81 |
August | 0.00 | 0.00 | 0.995475E+10 | 0.654651E+10 | 19993.10 | 14-AUG-08:32 | 15921.82 | 0.79 |
September | 0.00 | 0.00 | 0.640231E+10 | 0.402528E+10 | 17038.12 | 03-SEP-08:32 | 17038.12 | 0.67 |
October | 0.00 | 0.00 | 0.306644E+10 | 0.224310E+10 | 15605.21 | 11-OCT-08:51 | 14597.68 | 0.29 |
November | 0.00 | 0.00 | 0.585536E+09 | 0.504024E+09 | 14419.82 | 07-NOV-09:01 | 14419.82 | 0.05 |
December | 0.00 | 0.00 | 0.114483E+09 | 0.102221E+09 | 14232.70 | 30-DEC-09:02 | 14232.70 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.523560E+11 | 0.384599E+11 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 0.114483E+09 | 0.102221E+09 | 14232.70 | 14232.70 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.110397E+11 | 0.746151E+10 | 20898.07 | 19672.89 | 0.81 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.276078E+09 | 0.271467E+09 | 4432.17 | 05-JAN-16:01 | 4432.17 | 0.01 |
February | 0.00 | 0.00 | 0.416462E+09 | 0.401127E+09 | 4688.83 | 14-FEB-16:01 | 4688.83 | 0.04 |
March | 0.00 | 0.00 | 0.647944E+09 | 0.634926E+09 | 4671.93 | 07-MAR-16:01 | 4671.93 | 0.03 |
April | 0.00 | 0.00 | 0.126918E+10 | 0.125835E+10 | 4836.55 | 29-APR-15:01 | 4836.55 | 0.02 |
May | 0.00 | 0.00 | 0.161243E+10 | 0.134547E+10 | 4884.26 | 15-MAY-18:01 | 4884.26 | 0.34 |
June | 0.00 | 0.00 | 0.241934E+10 | 0.173606E+10 | 4884.69 | 20-JUN-18:02 | 4884.69 | 0.77 |
July | 0.00 | 0.00 | 0.296472E+10 | 0.185728E+10 | 4972.10 | 09-JUL-08:61 | 3692.12 | 0.97 |
August | 0.00 | 0.00 | 0.292828E+10 | 0.184632E+10 | 4894.55 | 26-AUG-08:61 | 3557.93 | 0.96 |
September | 0.00 | 0.00 | 0.225025E+10 | 0.147512E+10 | 4464.98 | 24-SEP-08:61 | 3368.58 | 0.84 |
October | 0.00 | 0.00 | 0.143680E+10 | 0.116704E+10 | 4763.71 | 31-OCT-15:01 | 4763.71 | 0.33 |
November | 0.00 | 0.00 | 0.497237E+09 | 0.466428E+09 | 4417.83 | 13-NOV-16:01 | 4417.83 | 0.06 |
December | 0.00 | 0.00 | 0.232046E+09 | 0.227159E+09 | 4419.48 | 04-DEC-16:01 | 4419.48 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.169508E+11 | 0.126867E+11 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 0.232046E+09 | 0.227159E+09 | 4417.83 | 3368.58 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.296472E+10 | 0.185728E+10 | 4972.10 | 4884.69 | 0.97 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 47366672.55 | 46543612.55 | 4371.04 | 05-JAN-16:01 | 4371.04 | 0.00 |
February | 0.00 | 0.00 | 0.110620E+09 | 0.106570E+09 | 4623.06 | 14-FEB-16:01 | 4623.06 | 0.01 |
March | 0.00 | 0.00 | 0.211020E+09 | 0.207430E+09 | 5074.32 | 30-MAR-18:11 | 5074.32 | 0.01 |
April | 0.00 | 0.00 | 0.748327E+09 | 0.739966E+09 | 5468.57 | 25-APR-16:21 | 5468.57 | 0.02 |
May | 0.00 | 0.00 | 0.131284E+10 | 0.108401E+10 | 4988.38 | 20-MAY-21:51 | 4988.38 | 0.29 |
June | 0.00 | 0.00 | 0.227854E+10 | 0.167252E+10 | 5250.37 | 14-JUN-08:21 | 5250.37 | 0.67 |
July | 0.00 | 0.00 | 0.271278E+10 | 0.179052E+10 | 5526.95 | 04-JUL-08:31 | 4181.51 | 0.80 |
August | 0.00 | 0.00 | 0.247241E+10 | 0.158722E+10 | 5336.41 | 14-AUG-08:51 | 3772.90 | 0.77 |
September | 0.00 | 0.00 | 0.153442E+10 | 0.937495E+09 | 4738.23 | 21-SEP-21:51 | 4738.23 | 0.64 |
October | 0.00 | 0.00 | 0.605469E+09 | 0.419857E+09 | 4697.29 | 31-OCT-15:01 | 4697.29 | 0.24 |
November | 0.00 | 0.00 | 0.110341E+09 | 0.101248E+09 | 4489.19 | 02-NOV-18:11 | 4489.19 | 0.02 |
December | 0.00 | 0.00 | 28682467.13 | 27465739.87 | 4357.61 | 29-DEC-16:01 | 4357.61 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.121728E+11 | 0.872084E+10 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 28682467.13 | 27465739.87 | 4357.61 | 3772.90 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.271278E+10 | 0.179052E+10 | 5526.95 | 5468.57 | 0.80 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.648821E+10 | 0.635434E+10 | 17996.42 | 05-JAN-16:01 | 17996.42 | 0.05 |
February | 0.00 | 0.00 | 0.630759E+10 | 0.613195E+10 | 19037.96 | 14-FEB-16:01 | 19037.96 | 0.08 |
March | 0.00 | 0.00 | 0.609083E+10 | 0.596018E+10 | 18934.52 | 13-MAR-15:01 | 18934.52 | 0.06 |
April | 0.00 | 0.00 | 0.682926E+10 | 0.675052E+10 | 19629.54 | 26-APR-15:01 | 19629.54 | 0.03 |
May | 0.00 | 0.00 | 0.706779E+10 | 0.571591E+10 | 19820.04 | 20-MAY-15:01 | 19820.04 | 0.36 |
June | 0.00 | 0.00 | 0.983963E+10 | 0.658516E+10 | 19818.47 | 19-JUN-18:01 | 19818.47 | 0.79 |
July | 0.00 | 0.00 | 0.137864E+11 | 0.857346E+10 | 19928.21 | 09-JUL-08:61 | 15284.08 | 0.96 |
August | 0.00 | 0.00 | 0.147583E+11 | 0.965763E+10 | 19580.80 | 26-AUG-08:61 | 14759.63 | 0.96 |
September | 0.00 | 0.00 | 0.137750E+11 | 0.978559E+10 | 18281.19 | 21-SEP-08:61 | 18281.19 | 0.85 |
October | 0.00 | 0.00 | 0.121282E+11 | 0.106752E+11 | 19339.53 | 31-OCT-15:01 | 19339.53 | 0.37 |
November | 0.00 | 0.00 | 0.859966E+10 | 0.831025E+10 | 18016.16 | 08-NOV-16:01 | 18016.16 | 0.12 |
December | 0.00 | 0.00 | 0.714957E+10 | 0.703840E+10 | 17937.76 | 29-DEC-19:01 | 17937.76 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.112820E+12 | 0.915386E+11 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 0.609083E+10 | 0.571591E+10 | 17937.76 | 14759.63 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.147583E+11 | 0.106752E+11 | 19928.21 | 19820.04 | 0.96 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 29208.55 | 168747.61 | 20-JAN-16:01 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 26971.71 | 166143.01 | 04-FEB-16:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25254.37 | 183782.07 | 04-MAR-19:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 19906.43 | 126044.70 | 16-APR-08:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 11144.99 | 117307.76 | 06-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 2594.92 | 94127.49 | 09-JUN-05:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 17.05 | 24789.31 | 08-JUL-18:06 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 43.57 | 42388.05 | 31-AUG-08:54 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 1927.31 | 60486.37 | 20-SEP-06:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18335.04 | 139986.87 | 26-OCT-18:03 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25625.45 | 167028.34 | 16-NOV-19:03 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 30850.27 | 178594.96 | 07-DEC-16:01 |
Annual Sum or Average | 0.00 | 15937.81 | ||||
Minimum of Months | 0.00 | 0.00 | 17.05 | 24789.31 | ||
Maximum of Months | 0.00 | 0.00 | 30850.27 | 183782.07 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 17141.39 | 148018.40 | 05-JAN-16:01 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 22089.52 | 314177.98 | 14-FEB-16:01 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 31057.95 | 324070.95 | 08-MAR-16:01 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 71714.85 | 384605.75 | 13-APR-18:01 | 0.00 | 0.00 | 01-APR-00:10 |
May | 109860.48 | 411704.96 | 15-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 185922.24 | 477364.47 | 28-JUN-18:08 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 241326.08 | 461059.30 | 21-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 221730.53 | 483635.92 | 16-AUG-18:02 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 160008.22 | 423177.55 | 13-SEP-18:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 84127.94 | 398367.51 | 06-OCT-15:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 27241.06 | 191121.63 | 02-NOV-15:03 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 17878.69 | 114739.50 | 02-DEC-16:01 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 99676.47 | 0.00 | ||||
Minimum of Months | 17141.39 | 114739.50 | 0.00 | 0.00 | ||
Maximum of Months | 241326.08 | 483635.92 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 26615.35 | 56111.32 | 31-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 26813.52 | 56130.70 | 07-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 26170.85 | 55632.40 | 01-MAR-07:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 24786.53 | 53198.80 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 23074.15 | 49947.09 | 01-MAY-06:50 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 21478.39 | 46231.69 | 01-JUN-06:47 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20402.17 | 43235.71 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 20197.26 | 42487.24 | 31-AUG-06:58 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 20858.23 | 44570.85 | 29-SEP-06:47 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22232.27 | 48148.22 | 31-OCT-06:40 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 23956.49 | 51720.21 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 25563.50 | 54520.35 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 23493.40 | ||||
Minimum of Months | 0.00 | 0.00 | 20197.26 | 42487.24 | ||
Maximum of Months | 0.00 | 0.00 | 26813.52 | 56130.70 |
Report: FanReportMonthly
For: SWHSYS1 HPWH FAN
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.810717E+09 | 0.08 | 553.22 | 01-JAN-06:15 | 0.12 |
February | 0.705047E+09 | 0.08 | 553.22 | 01-FEB-05:15 | 0.12 |
March | 0.709386E+09 | 0.07 | 553.22 | 01-MAR-05:15 | 0.12 |
April | 0.612783E+09 | 0.07 | 553.22 | 01-APR-01:10 | 0.12 |
May | 0.554765E+09 | 0.07 | 553.22 | 01-MAY-05:05 | 0.12 |
June | 0.469771E+09 | 0.07 | 553.22 | 01-JUN-04:07 | 0.12 |
July | 0.443665E+09 | 0.07 | 553.22 | 01-JUL-05:08 | 0.12 |
August | 0.446421E+09 | 0.07 | 553.22 | 01-AUG-05:13 | 0.12 |
September | 0.464339E+09 | 0.07 | 553.22 | 01-SEP-04:20 | 0.12 |
October | 0.564312E+09 | 0.07 | 553.22 | 01-OCT-06:20 | 0.12 |
November | 0.657691E+09 | 0.07 | 553.22 | 01-NOV-04:07 | 0.12 |
December | 0.795243E+09 | 0.08 | 553.22 | 01-DEC-00:05 | 0.12 |
Annual Sum or Average | 0.723414E+10 | 0.07 | |||
Minimum of Months | 0.443665E+09 | 0.07 | 553.22 | 0.12 | |
Maximum of Months | 0.810717E+09 | 0.08 | 553.22 | 0.12 |
Report: FanReportMonthly
For: SWHSYSLAUNDRY HPWH FAN
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.560313E+09 | 0.07 | 700.51 | 01-JAN-17:10 | 0.12 |
February | 0.506157E+09 | 0.07 | 700.51 | 01-FEB-17:10 | 0.12 |
March | 0.561543E+09 | 0.07 | 700.51 | 01-MAR-17:05 | 0.12 |
April | 0.543126E+09 | 0.07 | 700.51 | 01-APR-16:10 | 0.12 |
May | 0.560625E+09 | 0.06 | 700.51 | 01-MAY-16:10 | 0.12 |
June | 0.541852E+09 | 0.06 | 700.51 | 01-JUN-16:10 | 0.12 |
July | 0.559636E+09 | 0.07 | 700.51 | 01-JUL-16:10 | 0.12 |
August | 0.559738E+09 | 0.06 | 700.51 | 01-AUG-16:10 | 0.12 |
September | 0.542095E+09 | 0.06 | 700.51 | 01-SEP-16:10 | 0.12 |
October | 0.560733E+09 | 0.07 | 700.51 | 01-OCT-16:10 | 0.12 |
November | 0.542795E+09 | 0.07 | 700.51 | 01-NOV-16:10 | 0.12 |
December | 0.560750E+09 | 0.07 | 700.51 | 01-DEC-17:10 | 0.12 |
Annual Sum or Average | 0.659936E+10 | 0.07 | |||
Minimum of Months | 0.506157E+09 | 0.06 | 700.51 | 0.12 | |
Maximum of Months | 0.561543E+09 | 0.07 | 700.51 | 0.12 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.271000E+10 | 0.84 | 1299.30 | 01-JAN-10:30 | 1.07 |
February | 0.244774E+10 | 0.84 | 1299.30 | 01-FEB-03:30 | 1.07 |
March | 0.271000E+10 | 0.84 | 1299.30 | 04-MAR-16:06 | 1.07 |
April | 0.262258E+10 | 0.85 | 1299.30 | 01-APR-15:09 | 1.07 |
May | 0.271000E+10 | 0.84 | 1299.30 | 01-MAY-08:03 | 1.06 |
June | 0.262258E+10 | 0.84 | 1299.30 | 01-JUN-09:03 | 1.06 |
July | 0.271000E+10 | 0.84 | 1299.30 | 01-JUL-08:55 | 1.05 |
August | 0.271000E+10 | 0.84 | 1299.30 | 01-AUG-08:55 | 1.06 |
September | 0.262258E+10 | 0.84 | 1299.30 | 01-SEP-08:53 | 1.06 |
October | 0.271000E+10 | 0.84 | 1299.30 | 01-OCT-08:30 | 1.06 |
November | 0.262258E+10 | 0.84 | 1299.30 | 01-NOV-08:40 | 1.06 |
December | 0.271000E+10 | 0.84 | 1299.30 | 02-DEC-10:20 | 1.07 |
Annual Sum or Average | 0.319080E+11 | 0.84 | |||
Minimum of Months | 0.244774E+10 | 0.84 | 1299.30 | 1.05 | |
Maximum of Months | 0.271000E+10 | 0.85 | 1299.30 | 1.07 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.339626E+11 | 0.92 | 24731.32 | 09-JAN-22:10 | 1.36 |
February | 0.311089E+11 | 0.93 | 27687.13 | 14-FEB-22:10 | 1.45 |
March | 0.359211E+11 | 0.95 | 28370.28 | 08-MAR-22:10 | 1.47 |
April | 0.368967E+11 | 0.98 | 33337.31 | 13-APR-21:10 | 1.63 |
May | 0.395894E+11 | 1.00 | 32917.55 | 31-MAY-21:10 | 1.62 |
June | 0.420099E+11 | 1.04 | 36929.40 | 29-JUN-21:10 | 1.72 |
July | 0.455206E+11 | 1.07 | 38609.64 | 21-JUL-21:10 | 1.77 |
August | 0.464148E+11 | 1.08 | 40593.33 | 18-AUG-21:10 | 1.82 |
September | 0.431951E+11 | 1.06 | 40824.66 | 29-SEP-21:10 | 1.84 |
October | 0.412930E+11 | 1.02 | 40676.25 | 06-OCT-21:10 | 1.83 |
November | 0.362287E+11 | 0.97 | 31111.93 | 02-NOV-21:10 | 1.56 |
December | 0.347093E+11 | 0.93 | 26183.51 | 01-DEC-22:10 | 1.40 |
Annual Sum or Average | 0.466850E+12 | 1.00 | |||
Minimum of Months | 0.311089E+11 | 0.92 | 24731.32 | 1.36 | |
Maximum of Months | 0.464148E+11 | 1.08 | 40824.66 | 1.84 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.32 | 76.61 | 01-JAN-00:10 | 0.32 |
February | 0.185347E+09 | 0.32 | 76.61 | 01-FEB-00:05 | 0.32 |
March | 0.205205E+09 | 0.32 | 76.61 | 01-MAR-00:10 | 0.32 |
April | 0.198586E+09 | 0.32 | 76.61 | 01-APR-00:10 | 0.32 |
May | 0.205205E+09 | 0.32 | 76.61 | 01-MAY-00:05 | 0.33 |
June | 0.198586E+09 | 0.32 | 76.61 | 01-JUN-00:05 | 0.32 |
July | 0.205205E+09 | 0.32 | 76.61 | 01-JUL-00:10 | 0.32 |
August | 0.205205E+09 | 0.32 | 76.61 | 01-AUG-00:05 | 0.32 |
September | 0.198586E+09 | 0.32 | 76.61 | 01-SEP-00:05 | 0.32 |
October | 0.205205E+09 | 0.32 | 76.61 | 01-OCT-00:10 | 0.32 |
November | 0.198586E+09 | 0.32 | 76.61 | 01-NOV-00:05 | 0.32 |
December | 0.205205E+09 | 0.32 | 76.61 | 01-DEC-00:05 | 0.32 |
Annual Sum or Average | 0.241613E+10 | 0.32 | |||
Minimum of Months | 0.185347E+09 | 0.32 | 76.61 | 0.32 | |
Maximum of Months | 0.205205E+09 | 0.32 | 76.61 | 0.33 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.23 | 612.92 | 01-JAN-07:10 | 0.32 |
February | 0.105030E+10 | 0.23 | 612.92 | 01-FEB-07:05 | 0.32 |
March | 0.116283E+10 | 0.23 | 612.92 | 01-MAR-07:05 | 0.32 |
April | 0.112532E+10 | 0.23 | 612.92 | 01-APR-06:05 | 0.32 |
May | 0.116283E+10 | 0.23 | 612.92 | 01-MAY-06:05 | 0.32 |
June | 0.112532E+10 | 0.23 | 612.92 | 01-JUN-06:05 | 0.32 |
July | 0.116283E+10 | 0.23 | 612.92 | 01-JUL-06:10 | 0.32 |
August | 0.116283E+10 | 0.23 | 612.92 | 01-AUG-06:05 | 0.32 |
September | 0.112532E+10 | 0.23 | 612.92 | 01-SEP-06:10 | 0.32 |
October | 0.116283E+10 | 0.23 | 612.92 | 01-OCT-06:10 | 0.32 |
November | 0.112532E+10 | 0.23 | 612.92 | 01-NOV-06:05 | 0.32 |
December | 0.116283E+10 | 0.23 | 612.92 | 01-DEC-07:05 | 0.32 |
Annual Sum or Average | 0.136914E+11 | 0.23 | |||
Minimum of Months | 0.105030E+10 | 0.23 | 612.92 | 0.32 | |
Maximum of Months | 0.116283E+10 | 0.23 | 612.92 | 0.32 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.219166E+09 | 0.56 | 925.71 | 01-JAN-16:01 | 0.70 |
February | 0.203593E+09 | 0.57 | 925.71 | 01-FEB-09:01 | 0.70 |
March | 0.214534E+09 | 0.58 | 925.71 | 01-MAR-16:01 | 0.70 |
April | 0.305406E+09 | 0.63 | 925.71 | 01-APR-15:01 | 0.70 |
May | 0.365027E+09 | 0.63 | 925.71 | 01-MAY-08:61 | 0.69 |
June | 0.512881E+09 | 0.66 | 925.71 | 01-JUN-08:62 | 0.70 |
July | 0.567780E+09 | 0.67 | 925.71 | 01-JUL-08:61 | 0.69 |
August | 0.568907E+09 | 0.67 | 925.71 | 01-AUG-08:61 | 0.69 |
September | 0.486585E+09 | 0.66 | 925.71 | 01-SEP-08:61 | 0.69 |
October | 0.369766E+09 | 0.63 | 925.71 | 01-OCT-08:61 | 0.69 |
November | 0.200302E+09 | 0.59 | 925.71 | 01-NOV-08:62 | 0.69 |
December | 0.212553E+09 | 0.56 | 925.71 | 01-DEC-16:01 | 0.70 |
Annual Sum or Average | 0.422650E+10 | 0.62 | |||
Minimum of Months | 0.200302E+09 | 0.56 | 925.71 | 0.69 | |
Maximum of Months | 0.568907E+09 | 0.67 | 925.71 | 0.70 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.242574E+09 | 0.51 | 914.54 | 01-JAN-16:01 | 0.70 |
February | 0.189320E+09 | 0.51 | 914.54 | 01-FEB-09:01 | 0.70 |
March | 0.137574E+09 | 0.49 | 914.54 | 04-MAR-09:01 | 0.70 |
April | 0.194277E+09 | 0.49 | 914.54 | 01-APR-15:01 | 0.70 |
May | 0.292638E+09 | 0.51 | 914.54 | 01-MAY-08:61 | 0.69 |
June | 0.476677E+09 | 0.56 | 914.54 | 01-JUN-08:51 | 0.69 |
July | 0.513534E+09 | 0.55 | 914.54 | 01-JUL-08:51 | 0.69 |
August | 0.470109E+09 | 0.54 | 914.54 | 01-AUG-08:31 | 0.69 |
September | 0.326413E+09 | 0.50 | 914.54 | 01-SEP-08:51 | 0.69 |
October | 0.194564E+09 | 0.47 | 914.54 | 01-OCT-08:61 | 0.69 |
November | 0.155993E+09 | 0.52 | 914.54 | 01-NOV-15:01 | 0.69 |
December | 0.256286E+09 | 0.50 | 914.54 | 01-DEC-16:01 | 0.70 |
Annual Sum or Average | 0.344996E+10 | 0.51 | |||
Minimum of Months | 0.137574E+09 | 0.47 | 914.54 | 0.69 | |
Maximum of Months | 0.513534E+09 | 0.56 | 914.54 | 0.70 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.124118E+10 | 0.37 | 2475.32 | 03-JAN-12:40 | 0.70 |
February | 0.116982E+10 | 0.42 | 2460.59 | 14-FEB-13:00 | 0.70 |
March | 0.113132E+10 | 0.46 | 2105.14 | 08-MAR-13:10 | 0.70 |
April | 0.118351E+10 | 0.58 | 1336.09 | 13-APR-13:15 | 0.70 |
May | 0.114620E+10 | 0.62 | 990.00 | 14-MAY-12:40 | 0.70 |
June | 0.145030E+10 | 0.67 | 1104.27 | 29-JUN-15:03 | 0.70 |
July | 0.184931E+10 | 0.70 | 1200.41 | 23-JUL-13:30 | 0.70 |
August | 0.205990E+10 | 0.70 | 1530.34 | 22-AUG-13:30 | 0.70 |
September | 0.228667E+10 | 0.69 | 2521.86 | 28-SEP-13:30 | 0.70 |
October | 0.224274E+10 | 0.62 | 2814.00 | 09-OCT-12:40 | 0.70 |
November | 0.170414E+10 | 0.50 | 2495.32 | 20-NOV-13:30 | 0.70 |
December | 0.136831E+10 | 0.38 | 2539.82 | 31-DEC-13:40 | 0.70 |
Annual Sum or Average | 0.188334E+11 | 0.56 | |||
Minimum of Months | 0.113132E+10 | 0.37 | 990.00 | 0.70 | |
Maximum of Months | 0.228667E+10 | 0.70 | 2814.00 | 0.70 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.865459E+09 | 0.49 | 4708.08 | 17-JAN-09:01 | 0.70 |
February | 0.688201E+09 | 0.49 | 4708.08 | 04-FEB-16:01 | 0.70 |
March | 0.708153E+09 | 0.45 | 4708.08 | 01-MAR-16:01 | 0.70 |
April | 0.125160E+10 | 0.42 | 4708.08 | 01-APR-08:62 | 0.70 |
May | 0.197637E+10 | 0.45 | 4708.08 | 01-MAY-08:61 | 0.70 |
June | 0.293084E+10 | 0.52 | 4708.08 | 01-JUN-08:51 | 0.70 |
July | 0.321779E+10 | 0.53 | 4708.08 | 01-JUL-08:51 | 0.69 |
August | 0.284199E+10 | 0.50 | 4708.08 | 01-AUG-08:31 | 0.69 |
September | 0.196248E+10 | 0.43 | 4708.08 | 01-SEP-08:51 | 0.69 |
October | 0.111624E+10 | 0.42 | 4708.08 | 01-OCT-08:61 | 0.70 |
November | 0.622710E+09 | 0.49 | 4708.08 | 01-NOV-08:62 | 0.70 |
December | 0.978087E+09 | 0.49 | 4708.08 | 01-DEC-19:02 | 0.70 |
Annual Sum or Average | 0.191599E+11 | 0.47 | |||
Minimum of Months | 0.622710E+09 | 0.42 | 4708.08 | 0.69 | |
Maximum of Months | 0.321779E+10 | 0.53 | 4708.08 | 0.70 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.211877E+09 | 0.57 | 813.04 | 01-JAN-09:02 | 0.70 |
February | 0.191562E+09 | 0.58 | 813.04 | 02-FEB-09:01 | 0.70 |
March | 0.227637E+09 | 0.61 | 813.04 | 01-MAR-09:02 | 0.70 |
April | 0.346964E+09 | 0.67 | 813.04 | 01-APR-08:62 | 0.70 |
May | 0.407483E+09 | 0.67 | 813.04 | 01-MAY-08:61 | 0.69 |
June | 0.552172E+09 | 0.68 | 813.04 | 01-JUN-08:62 | 0.70 |
July | 0.623645E+09 | 0.69 | 813.04 | 01-JUL-08:61 | 0.69 |
August | 0.610809E+09 | 0.68 | 813.04 | 01-AUG-08:61 | 0.70 |
September | 0.504296E+09 | 0.68 | 813.04 | 01-SEP-08:61 | 0.69 |
October | 0.373386E+09 | 0.65 | 813.04 | 01-OCT-08:61 | 0.69 |
November | 0.202690E+09 | 0.61 | 813.04 | 01-NOV-08:62 | 0.69 |
December | 0.202851E+09 | 0.55 | 813.04 | 01-DEC-09:02 | 0.70 |
Annual Sum or Average | 0.445537E+10 | 0.64 | |||
Minimum of Months | 0.191562E+09 | 0.55 | 813.04 | 0.69 | |
Maximum of Months | 0.623645E+09 | 0.69 | 813.04 | 0.70 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.222531E+09 | 0.51 | 805.73 | 01-JAN-09:02 | 0.70 |
February | 0.171238E+09 | 0.49 | 805.73 | 01-FEB-16:01 | 0.70 |
March | 0.146086E+09 | 0.51 | 805.73 | 02-MAR-09:01 | 0.70 |
April | 0.251329E+09 | 0.56 | 805.73 | 01-APR-08:62 | 0.70 |
May | 0.336329E+09 | 0.55 | 805.73 | 01-MAY-08:61 | 0.69 |
June | 0.494868E+09 | 0.58 | 805.73 | 01-JUN-08:51 | 0.69 |
July | 0.545248E+09 | 0.57 | 805.73 | 01-JUL-08:51 | 0.69 |
August | 0.490387E+09 | 0.55 | 805.73 | 01-AUG-08:31 | 0.69 |
September | 0.331853E+09 | 0.51 | 805.73 | 01-SEP-08:51 | 0.69 |
October | 0.206464E+09 | 0.51 | 805.73 | 01-OCT-08:61 | 0.69 |
November | 0.144585E+09 | 0.50 | 805.73 | 01-NOV-08:62 | 0.69 |
December | 0.232554E+09 | 0.50 | 805.73 | 03-DEC-16:01 | 0.70 |
Annual Sum or Average | 0.357347E+10 | 0.53 | |||
Minimum of Months | 0.144585E+09 | 0.49 | 805.73 | 0.69 | |
Maximum of Months | 0.545248E+09 | 0.58 | 805.73 | 0.70 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 69669736.25 | 0.56 | 247.08 | 01-JAN-16:01 | 0.70 |
February | 62642586.67 | 0.57 | 247.08 | 01-FEB-09:01 | 0.70 |
March | 62569171.71 | 0.58 | 247.08 | 04-MAR-16:01 | 0.70 |
April | 78285912.76 | 0.62 | 247.08 | 01-APR-15:01 | 0.70 |
May | 92125385.95 | 0.63 | 247.08 | 01-MAY-08:61 | 0.69 |
June | 0.133794E+09 | 0.66 | 247.08 | 01-JUN-08:62 | 0.70 |
July | 0.149826E+09 | 0.67 | 247.08 | 01-JUL-08:61 | 0.69 |
August | 0.148041E+09 | 0.67 | 247.08 | 01-AUG-08:61 | 0.69 |
September | 0.120222E+09 | 0.65 | 247.08 | 01-SEP-08:61 | 0.69 |
October | 91841293.00 | 0.63 | 247.08 | 01-OCT-08:61 | 0.69 |
November | 57513084.95 | 0.58 | 247.08 | 01-NOV-15:01 | 0.70 |
December | 67857249.99 | 0.56 | 247.08 | 01-DEC-16:01 | 0.70 |
Annual Sum or Average | 0.113439E+10 | 0.62 | |||
Minimum of Months | 57513084.95 | 0.56 | 247.08 | 0.69 | |
Maximum of Months | 0.149826E+09 | 0.67 | 247.08 | 0.70 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 78301149.39 | 0.52 | 243.63 | 01-JAN-09:02 | 0.70 |
February | 60842041.27 | 0.51 | 243.63 | 01-FEB-09:01 | 0.70 |
March | 45142292.57 | 0.49 | 243.63 | 03-MAR-09:02 | 0.69 |
April | 50592007.65 | 0.49 | 243.63 | 01-APR-15:01 | 0.70 |
May | 75291234.52 | 0.51 | 243.63 | 01-MAY-08:61 | 0.69 |
June | 0.126786E+09 | 0.56 | 243.63 | 01-JUN-08:51 | 0.69 |
July | 0.138408E+09 | 0.55 | 243.63 | 01-JUL-08:51 | 0.69 |
August | 0.125077E+09 | 0.54 | 243.63 | 01-AUG-08:31 | 0.69 |
September | 81083674.88 | 0.50 | 243.63 | 01-SEP-08:51 | 0.69 |
October | 49542461.24 | 0.47 | 243.63 | 01-OCT-08:61 | 0.69 |
November | 53366950.25 | 0.51 | 243.63 | 01-NOV-15:01 | 0.69 |
December | 82251136.97 | 0.54 | 243.63 | 02-DEC-09:02 | 0.70 |
Annual Sum or Average | 0.966684E+09 | 0.52 | |||
Minimum of Months | 45142292.57 | 0.47 | 243.63 | 0.69 | |
Maximum of Months | 0.138408E+09 | 0.56 | 243.63 | 0.70 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.475322E+09 | 0.62 | 999.34 | 01-JAN-09:02 | 0.70 |
February | 0.431678E+09 | 0.63 | 999.34 | 01-FEB-16:01 | 0.70 |
March | 0.388198E+09 | 0.62 | 999.34 | 01-MAR-09:02 | 0.70 |
April | 0.387871E+09 | 0.64 | 999.34 | 01-APR-08:62 | 0.70 |
May | 0.389211E+09 | 0.63 | 999.34 | 01-MAY-08:61 | 0.69 |
June | 0.508808E+09 | 0.65 | 999.34 | 01-JUN-15:01 | 0.69 |
July | 0.651744E+09 | 0.67 | 999.34 | 01-JUL-08:61 | 0.69 |
August | 0.717731E+09 | 0.67 | 999.34 | 01-AUG-08:61 | 0.69 |
September | 0.733357E+09 | 0.66 | 999.34 | 01-SEP-08:61 | 0.69 |
October | 0.704416E+09 | 0.65 | 999.34 | 01-OCT-08:61 | 0.69 |
November | 0.539989E+09 | 0.64 | 999.34 | 01-NOV-08:62 | 0.69 |
December | 0.507329E+09 | 0.62 | 999.34 | 01-DEC-09:02 | 0.70 |
Annual Sum or Average | 0.643565E+10 | 0.64 | |||
Minimum of Months | 0.387871E+09 | 0.62 | 999.34 | 0.69 | |
Maximum of Months | 0.733357E+09 | 0.67 | 999.34 | 0.70 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.480176E+09 | 0.436480E+09 | 591.47 | 20-JAN-16:01 | 537.65 | 537.65 | 35.42 | 0.91 |
February | 0.382306E+09 | 0.347516E+09 | 584.76 | 04-FEB-16:01 | 531.55 | 531.55 | 35.21 | 0.89 |
March | 0.325427E+09 | 0.295813E+09 | 619.57 | 04-MAR-19:03 | 563.19 | 563.19 | 35.33 | 0.98 |
April | 0.219499E+09 | 0.199524E+09 | 517.72 | 23-APR-08:03 | 470.60 | 470.60 | 42.32 | 0.73 |
May | 0.124540E+09 | 0.113207E+09 | 483.82 | 06-MAY-06:05 | 439.79 | 439.79 | 54.88 | 0.66 |
June | 27668868.55 | 25151001.51 | 396.75 | 09-JUN-04:50 | 360.65 | 360.65 | 35.45 | 0.51 |
July | 353622.99 | 321443.29 | 152.30 | 08-JUL-18:06 | 138.44 | 138.44 | 43.96 | 0.17 |
August | 871183.01 | 791905.36 | 185.12 | 31-AUG-08:54 | 168.27 | 168.27 | 30.63 | 0.21 |
September | 20715478.15 | 18830369.64 | 246.71 | 20-SEP-06:00 | 224.26 | 224.26 | 28.96 | 0.29 |
October | 0.221603E+09 | 0.201438E+09 | 561.57 | 28-OCT-08:03 | 510.46 | 510.46 | 55.05 | 0.82 |
November | 0.352355E+09 | 0.320290E+09 | 586.33 | 24-NOV-09:03 | 532.98 | 532.98 | 39.73 | 0.89 |
December | 0.513052E+09 | 0.466364E+09 | 600.63 | 05-DEC-16:02 | 545.97 | 545.97 | 35.94 | 0.93 |
Annual Sum or Average | 0.266857E+10 | 0.242573E+10 | ||||||
Minimum of Months | 353622.99 | 321443.29 | 152.30 | 138.44 | 138.44 | 28.96 | 0.17 | |
Maximum of Months | 0.513052E+09 | 0.466364E+09 | 619.57 | 563.19 | 563.19 | 55.05 | 0.98 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 24176880.74 | 21976784.59 | 244.48 | 05-JAN-16:01 | 222.23 | 222.23 | 8.35 | 6.84 |
February | 34285080.19 | 31165137.90 | 412.36 | 14-FEB-16:01 | 374.83 | 374.83 | 7.42 | 8.71 |
March | 59895372.90 | 54444893.96 | 457.27 | 08-MAR-16:01 | 415.65 | 415.65 | 7.32 | 9.12 |
April | 0.154604E+09 | 0.140535E+09 | 522.07 | 13-APR-18:01 | 474.56 | 474.56 | 7.02 | 9.68 |
May | 0.282924E+09 | 0.257178E+09 | 960.22 | 21-MAY-18:01 | 872.84 | 872.84 | 6.91 | 12.63 |
June | 0.677883E+09 | 0.616195E+09 | 1811.90 | 28-JUN-18:13 | 1647.02 | 1647.02 | 6.73 | 16.49 |
July | 0.103063E+10 | 0.936843E+09 | 1548.28 | 20-JUL-20:20 | 1407.38 | 1407.38 | 6.73 | 15.45 |
August | 0.103739E+10 | 0.942991E+09 | 1797.27 | 16-AUG-18:02 | 1633.72 | 1633.72 | 6.73 | 16.44 |
September | 0.629779E+09 | 0.572469E+09 | 1528.64 | 28-SEP-18:02 | 1389.54 | 1389.54 | 6.92 | 15.37 |
October | 0.244711E+09 | 0.222442E+09 | 1046.77 | 03-OCT-15:13 | 951.52 | 951.52 | 6.90 | 13.10 |
November | 44005554.99 | 40001049.49 | 283.38 | 02-NOV-15:01 | 257.60 | 257.60 | 8.16 | 7.33 |
December | 24148459.26 | 21950949.47 | 169.85 | 02-DEC-16:01 | 154.39 | 154.39 | 8.40 | 5.75 |
Annual Sum or Average | 0.424444E+10 | 0.385819E+10 | ||||||
Minimum of Months | 24148459.26 | 21950949.47 | 169.85 | 154.39 | 154.39 | 6.73 | 5.75 | |
Maximum of Months | 0.103739E+10 | 0.942991E+09 | 1811.90 | 1647.02 | 1647.02 | 8.40 | 16.49 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.564091E+10 | 0.512759E+10 | 3546.02 | 01-JAN-00:10 | 3223.34 | 3223.34 | 8.45 | 25.10 |
February | 0.582613E+10 | 0.529595E+10 | 3546.02 | 01-FEB-09:01 | 3223.34 | 3223.34 | 8.44 | 25.10 |
March | 0.817383E+10 | 0.743001E+10 | 3546.02 | 01-MAR-00:10 | 3223.34 | 3223.34 | 8.41 | 25.10 |
April | 0.911530E+10 | 0.828581E+10 | 3546.02 | 01-APR-00:10 | 3223.34 | 3223.34 | 8.43 | 25.10 |
May | 0.948987E+10 | 0.862629E+10 | 3546.02 | 01-MAY-00:05 | 3223.34 | 3223.34 | 8.76 | 25.10 |
June | 0.919129E+10 | 0.835489E+10 | 3546.02 | 01-JUN-00:05 | 3223.34 | 3223.34 | 9.00 | 25.10 |
July | 0.949767E+10 | 0.863338E+10 | 3546.02 | 01-JUL-00:10 | 3223.34 | 3223.34 | 9.20 | 25.10 |
August | 0.949767E+10 | 0.863338E+10 | 3546.02 | 01-AUG-00:05 | 3223.34 | 3223.34 | 9.51 | 25.10 |
September | 0.919129E+10 | 0.835489E+10 | 3546.02 | 01-SEP-00:05 | 3223.34 | 3223.34 | 9.18 | 25.10 |
October | 0.901774E+10 | 0.819713E+10 | 3546.02 | 01-OCT-00:10 | 3223.34 | 3223.34 | 9.04 | 25.10 |
November | 0.758002E+10 | 0.689023E+10 | 3546.02 | 01-NOV-00:05 | 3223.34 | 3223.34 | 8.65 | 25.10 |
December | 0.567251E+10 | 0.515631E+10 | 3546.02 | 01-DEC-00:05 | 3223.34 | 3223.34 | 8.41 | 25.10 |
Annual Sum or Average | 0.978942E+11 | 0.889859E+11 | ||||||
Minimum of Months | 0.564091E+10 | 0.512759E+10 | 3546.02 | 3223.34 | 3223.34 | 8.41 | 25.10 | |
Maximum of Months | 0.949767E+10 | 0.863338E+10 | 3546.02 | 3223.34 | 3223.34 | 9.51 | 25.10 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 49.13 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:05 | 14.37 | 14.37 | 49.67 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:10 | 14.37 | 14.37 | 50.00 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.73 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:05 | 14.37 | 14.37 | 52.98 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 53.49 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 54.07 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:05 | 14.37 | 14.37 | 54.09 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:05 | 14.37 | 14.37 | 54.02 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 53.17 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 53.21 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:05 | 14.37 | 14.37 | 50.44 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 49.13 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.09 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 65.10 | 80.69 | 29208.55 | 168747.61 | 20-JAN-16:01 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 51.35 | 81.63 | 26971.71 | 166143.01 | 04-FEB-16:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 67.95 | 80.67 | 25254.37 | 183782.07 | 04-MAR-19:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 36.38 | 79.90 | 19906.43 | 126044.70 | 16-APR-08:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 29.99 | 79.40 | 11144.99 | 117307.76 | 06-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.71 | 26.71 | 2594.92 | 94127.49 | 09-JUN-05:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 38.30 | 38.30 | 17.05 | 24789.31 | 08-JUL-18:06 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 56.80 | 56.80 | 43.57 | 42388.05 | 31-AUG-08:54 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 33.58 | 33.58 | 1927.31 | 60486.37 | 20-SEP-06:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 34.56 | 34.56 | 18335.04 | 139986.87 | 26-OCT-18:03 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.74 | 79.40 | 25625.45 | 167028.34 | 16-NOV-19:03 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 67.25 | 80.22 | 30850.27 | 178594.96 | 07-DEC-16:01 |
Annual Sum or Average | 0.00 | 15937.81 | ||||||
Minimum of Months | 0.00 | 0.00 | 25.74 | 26.71 | 17.05 | 24789.31 | ||
Maximum of Months | 0.00 | 0.00 | 67.95 | 81.63 | 30850.27 | 183782.07 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 17141.39 | 148018.40 | 05-JAN-16:01 | 9.77 | 8.36 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 22089.52 | 314177.98 | 14-FEB-16:01 | 10.39 | 7.40 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 31057.95 | 324070.95 | 08-MAR-16:01 | 10.38 | 7.30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 71714.85 | 384605.75 | 13-APR-18:01 | 10.70 | 7.04 | 0.00 | 0.00 | 01-APR-00:10 |
May | 109860.48 | 411704.96 | 15-MAY-18:03 | 10.61 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 185922.24 | 477364.47 | 28-JUN-18:08 | 11.24 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 241326.08 | 461059.30 | 21-JUL-18:03 | 11.08 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 221730.53 | 483635.92 | 16-AUG-18:02 | 11.30 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 160008.22 | 423177.55 | 13-SEP-18:03 | 10.72 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 84127.94 | 398367.51 | 06-OCT-15:03 | 10.49 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 27241.06 | 191121.63 | 02-NOV-15:03 | 9.96 | 8.14 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 17878.69 | 114739.50 | 02-DEC-16:01 | 9.46 | 8.37 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 99676.47 | 0.00 | ||||||
Minimum of Months | 17141.39 | 114739.50 | 9.46 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 241326.08 | 483635.92 | 11.30 | 8.37 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 49.13 | 59.99 | 26615.35 | 56111.32 | 31-JAN-08:00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 49.67 | 59.99 | 26813.52 | 56130.70 | 07-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 50.00 | 59.99 | 26170.85 | 55632.40 | 01-MAR-07:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.73 | 59.96 | 24786.53 | 53198.80 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 52.98 | 59.99 | 23074.15 | 49947.09 | 01-MAY-06:50 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 53.49 | 59.97 | 21478.39 | 46231.69 | 01-JUN-06:47 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 54.07 | 59.97 | 20402.17 | 43235.71 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 54.09 | 60.00 | 20197.26 | 42487.24 | 31-AUG-06:58 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 54.02 | 60.00 | 20858.23 | 44570.85 | 29-SEP-06:47 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.17 | 59.99 | 22232.27 | 48148.22 | 31-OCT-06:40 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 53.21 | 59.96 | 23956.49 | 51720.21 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 50.44 | 59.96 | 25563.50 | 54520.35 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 23493.40 | ||||||
Minimum of Months | 0.00 | 0.00 | 49.13 | 59.96 | 20197.26 | 42487.24 | ||
Maximum of Months | 0.00 | 0.00 | 54.09 | 60.00 | 26813.52 | 56130.70 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.549223E+11 | 0.00 | 0.113883E+10 | 0.339626E+11 | 0.00 | 0.00 |
February | 0.503931E+11 | 0.00 | 0.638581E+10 | 0.311089E+11 | 0.00 | 0.00 |
March | 0.636354E+11 | 0.00 | 0.230089E+11 | 0.359211E+11 | 0.00 | 0.00 |
April | 0.513455E+11 | 0.00 | 0.944036E+11 | 0.368967E+11 | 0.00 | 0.00 |
May | 0.298548E+11 | 0.00 | 0.177214E+12 | 0.395894E+11 | 0.00 | 0.00 |
June | 0.671779E+10 | 0.00 | 0.313086E+12 | 0.420099E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.430432E+12 | 0.455206E+11 | 0.00 | 0.00 |
August | 94698466.68 | 0.00 | 0.384622E+12 | 0.464148E+11 | 0.00 | 0.00 |
September | 0.496598E+10 | 0.00 | 0.247725E+12 | 0.431951E+11 | 0.00 | 0.00 |
October | 0.473520E+11 | 0.00 | 0.106274E+12 | 0.412930E+11 | 0.00 | 0.00 |
November | 0.587286E+11 | 0.00 | 0.336714E+10 | 0.362287E+11 | 0.00 | 0.00 |
December | 0.564454E+11 | 0.00 | 0.00 | 0.347093E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.424456E+12 | 0.00 | 0.178766E+13 | 0.466850E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.311089E+11 | 0.00 | 0.00 |
Maximum of Months | 0.636354E+11 | 0.00 | 0.430432E+12 | 0.464148E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.542712E+09 | 0.00 | 28569562.60 | 0.271000E+10 | 0.00 | 0.00 |
February | 0.281245E+09 | 0.00 | 0.354954E+09 | 0.244774E+10 | 0.00 | 0.00 |
March | 10415872.30 | 0.00 | 0.140659E+10 | 0.271000E+10 | 0.00 | 0.00 |
April | 11603.19 | 0.00 | 0.583698E+10 | 0.262258E+10 | 0.00 | 0.00 |
May | 18918.41 | 0.00 | 0.112270E+11 | 0.271000E+10 | 0.00 | 0.00 |
June | 18356.35 | 0.00 | 0.190095E+11 | 0.262258E+10 | 0.00 | 0.00 |
July | 20899.22 | 0.00 | 0.293128E+11 | 0.271000E+10 | 0.00 | 0.00 |
August | 20658.66 | 0.00 | 0.254886E+11 | 0.271000E+10 | 0.00 | 0.00 |
September | 23209.11 | 0.00 | 0.154881E+11 | 0.262258E+10 | 0.00 | 0.00 |
October | 7750088.26 | 0.00 | 0.632881E+10 | 0.271000E+10 | 0.00 | 0.00 |
November | 27158126.01 | 0.00 | 0.142365E+09 | 0.262258E+10 | 0.00 | 0.00 |
December | 0.487066E+09 | 0.00 | 0.00 | 0.271000E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.135646E+10 | 0.00 | 0.114624E+12 | 0.319080E+11 | 0.00 | 0.00 |
Minimum of Months | 11603.19 | 0.00 | 0.00 | 0.244774E+10 | 0.00 | 0.00 |
Maximum of Months | 0.542712E+09 | 0.00 | 0.293128E+11 | 0.271000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.339626E+11 | 0.113883E+10 | 0.549223E+11 | 0.480537E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311089E+11 | 0.638581E+10 | 0.503931E+11 | 0.369549E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.359211E+11 | 0.230089E+11 | 0.636354E+11 | 0.214698E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.368967E+11 | 0.944036E+11 | 0.513455E+11 | 0.656242E+11 | 1087401.58 | 0.00 | 0.00 | 0.00 |
May | 0.395894E+11 | 0.177214E+12 | 0.298548E+11 | 0.185084E+11 | 0.107792E+10 | 0.00 | 0.00 | 0.00 |
June | 0.420099E+11 | 0.313086E+12 | 0.671779E+10 | 0.107111E+11 | 0.243801E+11 | 0.00 | 0.00 | 0.00 |
July | 0.455206E+11 | 0.430432E+12 | 0.00 | 0.104037E+11 | 0.334898E+11 | 0.00 | 0.00 | 0.00 |
August | 0.464148E+11 | 0.384622E+12 | 94698466.68 | 0.102019E+11 | 0.197526E+11 | 0.00 | 0.00 | 0.00 |
September | 0.431951E+11 | 0.247725E+12 | 0.496598E+10 | 0.774094E+10 | 0.375258E+10 | 0.00 | 0.00 | 0.00 |
October | 0.412930E+11 | 0.106274E+12 | 0.473520E+11 | 0.916393E+11 | 93101590.25 | 0.00 | 0.00 | 0.00 |
November | 0.362287E+11 | 0.336714E+10 | 0.587286E+11 | 0.275735E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.347093E+11 | 0.00 | 0.564454E+11 | 0.503857E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.466850E+12 | 0.178766E+13 | 0.424456E+12 | 0.205921E+13 | 0.825472E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.311089E+11 | 0.00 | 0.00 | 0.774094E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.464148E+11 | 0.430432E+12 | 0.636354E+11 | 0.503857E+12 | 0.334898E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.271000E+10 | 28569562.60 | 0.542712E+09 | 0.458787E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.354954E+09 | 0.281245E+09 | 0.365745E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 0.140659E+10 | 10415872.30 | 0.258344E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 0.583698E+10 | 11603.19 | 0.115249E+11 | 461624.76 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 0.112270E+11 | 18918.41 | 0.550186E+10 | 43485308.90 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 0.190095E+11 | 18356.35 | 0.176307E+10 | 0.190471E+10 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 0.293128E+11 | 20899.22 | 0.129797E+09 | 0.649734E+10 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 0.254886E+11 | 20658.66 | 0.206425E+09 | 0.416092E+10 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 0.154881E+11 | 23209.11 | 0.925611E+09 | 0.687368E+09 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 0.632881E+10 | 7750088.26 | 0.130422E+11 | 40818345.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 0.142365E+09 | 27158126.01 | 0.297779E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.00 | 0.487066E+09 | 0.471536E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.114624E+12 | 0.135646E+10 | 0.218313E+12 | 0.133351E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 0.00 | 11603.19 | 0.129797E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.293128E+11 | 0.542712E+09 | 0.471536E+11 | 0.649734E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.339626E+11 | 0.549223E+11 | 0.113883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311089E+11 | 0.503931E+11 | 0.638581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.359211E+11 | 0.636354E+11 | 0.230089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.368967E+11 | 0.513455E+11 | 0.944036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.395894E+11 | 0.298548E+11 | 0.177214E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.420099E+11 | 0.671779E+10 | 0.313086E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455206E+11 | 0.00 | 0.430432E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.464148E+11 | 94698466.68 | 0.384622E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.431951E+11 | 0.496598E+10 | 0.247725E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.412930E+11 | 0.473520E+11 | 0.106274E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.362287E+11 | 0.587286E+11 | 0.336714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.347093E+11 | 0.564454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.466850E+12 | 0.424456E+12 | 0.178766E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.311089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.464148E+11 | 0.636354E+11 | 0.430432E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.271000E+10 | 0.542712E+09 | 28569562.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244774E+10 | 0.281245E+09 | 0.354954E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271000E+10 | 10415872.30 | 0.140659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262258E+10 | 11603.19 | 0.583698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271000E+10 | 18918.41 | 0.112270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262258E+10 | 18356.35 | 0.190095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271000E+10 | 20899.22 | 0.293128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.271000E+10 | 20658.66 | 0.254886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262258E+10 | 23209.11 | 0.154881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271000E+10 | 7750088.26 | 0.632881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262258E+10 | 27158126.01 | 0.142365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271000E+10 | 0.487066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319080E+11 | 0.135646E+10 | 0.114624E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244774E+10 | 11603.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.271000E+10 | 0.542712E+09 | 0.293128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.180374E+11 | 0.00 | 0.00 | 18391746.55 | 0.00 | 0.00 | 0.251932E+11 | 0.00 | 0.90 |
February | 0.317504E+11 | 0.00 | 0.00 | 2754176.05 | 0.00 | 0.00 | 0.620941E+10 | 0.00 | 0.88 |
March | 0.412867E+11 | 0.00 | 0.00 | 36381.20 | 0.00 | 0.00 | 0.298431E+09 | 0.00 | 0.88 |
April | 0.346406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 |
May | 0.280094E+11 | 0.00 | 0.00 | 0.00 | 3193539.91 | 0.00 | 0.00 | 0.00 | 0.88 |
June | 0.151975E+11 | 8138080.43 | 0.00 | 1011884.81 | 0.479611E+09 | 0.00 | 0.105908E+10 | 0.00 | 0.85 |
July | 0.240427E+10 | 44518935.47 | 0.00 | 14191744.57 | 0.801257E+09 | 0.00 | 0.688506E+10 | 0.00 | 0.84 |
August | 0.866004E+09 | 18024074.75 | 0.00 | 37307048.04 | 0.312253E+09 | 0.00 | 0.122813E+11 | 0.00 | 0.89 |
September | 0.370895E+09 | 35206941.90 | 0.00 | 61047257.06 | 12663043.07 | 0.00 | 0.243964E+11 | 0.00 | 1.01 |
October | 0.555476E+09 | 192107.55 | 0.00 | 65981433.12 | 0.00 | 0.00 | 0.431024E+11 | 0.00 | 1.06 |
November | 0.767428E+09 | 0.00 | 0.00 | 58855027.66 | 0.00 | 0.00 | 0.491943E+11 | 0.00 | 1.05 |
December | 0.211415E+10 | 0.00 | 0.00 | 52228823.49 | 0.00 | 0.00 | 0.455838E+11 | 0.00 | 0.99 |
Annual Sum or Average | 0.176000E+12 | 0.106080E+09 | 0.00 | 0.311806E+09 | 0.160898E+10 | 0.00 | 0.214203E+12 | 0.00 | 0.93 |
Minimum of Months | 0.370895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 |
Maximum of Months | 0.412867E+11 | 44518935.47 | 0.00 | 65981433.12 | 0.801257E+09 | 0.00 | 0.491943E+11 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.471327E+10 | 0.00 | 0.00 | 3650868.33 | 0.00 | 0.321079E+09 | 0.250357E+10 | 0.00 | 2.82 |
February | 0.417447E+10 | 0.00 | 0.00 | 3551063.82 | 0.00 | 47424402.99 | 0.242656E+10 | 0.00 | 2.81 |
March | 0.517925E+10 | 0.00 | 0.00 | 3035357.22 | 0.00 | 2049384.55 | 0.173853E+10 | 0.00 | 2.72 |
April | 0.428505E+10 | 0.00 | 0.00 | 2741994.47 | 0.00 | 0.00 | 0.124131E+10 | 0.00 | 2.60 |
May | 0.368622E+10 | 479808.81 | 0.00 | 2164978.90 | 48395.42 | 0.00 | 0.722481E+09 | 0.00 | 2.54 |
June | 0.181484E+10 | 94918989.52 | 0.00 | 2674157.92 | 340282.28 | 0.00 | 0.748999E+09 | 0.00 | 2.52 |
July | 0.488789E+09 | 0.167422E+09 | 0.00 | 3925104.18 | 1307561.66 | 0.00 | 0.977317E+09 | 0.00 | 2.62 |
August | 0.673363E+09 | 80422319.14 | 0.00 | 7090898.46 | 73135.78 | 0.00 | 0.133275E+10 | 0.00 | 2.85 |
September | 0.147126E+10 | 15168520.59 | 0.00 | 9281881.25 | 0.00 | 0.00 | 0.195990E+10 | 0.00 | 3.08 |
October | 0.307474E+10 | 37749.49 | 0.00 | 8590719.24 | 0.00 | 19371367.31 | 0.314753E+10 | 0.00 | 3.06 |
November | 0.435165E+10 | 0.00 | 0.00 | 4759338.30 | 0.00 | 0.00 | 0.344916E+10 | 0.00 | 2.94 |
December | 0.467865E+10 | 0.00 | 0.00 | 4034520.25 | 0.00 | 0.164698E+09 | 0.293584E+10 | 0.00 | 2.87 |
Annual Sum or Average | 0.385916E+11 | 0.358449E+09 | 0.00 | 55500882.33 | 1769375.13 | 0.554622E+09 | 0.231839E+11 | 0.00 | 2.79 |
Minimum of Months | 0.488789E+09 | 0.00 | 0.00 | 2164978.90 | 0.00 | 0.00 | 0.722481E+09 | 0.00 | 2.52 |
Maximum of Months | 0.517925E+10 | 0.167422E+09 | 0.00 | 9281881.25 | 1307561.66 | 0.321079E+09 | 0.344916E+10 | 0.00 | 3.08 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.362009E+10 | 0.00 | 0.00 | 486888.97 | 0.00 | 0.00 | 0.800484E+09 | 0.00 | 1.44 |
February | 0.293863E+10 | 0.00 | 0.00 | 678268.15 | 0.00 | 0.00 | 0.106105E+10 | 0.00 | 1.45 |
March | 0.262085E+10 | 0.00 | 0.00 | 1235396.82 | 0.00 | 0.00 | 0.179893E+10 | 0.00 | 1.46 |
April | 0.137759E+10 | 0.00 | 0.00 | 2664326.29 | 0.00 | 0.00 | 0.239825E+10 | 0.00 | 1.51 |
May | 0.840770E+09 | 300391.34 | 0.00 | 3724057.85 | 33758.75 | 0.00 | 0.226493E+10 | 0.00 | 1.55 |
June | 0.208341E+09 | 50507853.32 | 0.00 | 5080996.25 | 2670375.58 | 0.00 | 0.174561E+10 | 0.00 | 1.60 |
July | 6327013.58 | 88117244.45 | 0.00 | 6058792.72 | 4545334.11 | 0.00 | 0.120839E+10 | 0.00 | 1.63 |
August | 27094438.06 | 32868067.77 | 0.00 | 7037958.81 | 2467117.35 | 0.00 | 0.160465E+10 | 0.00 | 1.68 |
September | 99049336.76 | 5009375.20 | 0.00 | 6689982.27 | 0.00 | 0.00 | 0.248502E+10 | 0.00 | 1.69 |
October | 0.988254E+09 | 20100.82 | 0.00 | 4136553.03 | 0.00 | 0.00 | 0.300847E+10 | 0.00 | 1.57 |
November | 0.255932E+10 | 0.00 | 0.00 | 1223566.54 | 0.00 | 0.00 | 0.189554E+10 | 0.00 | 1.46 |
December | 0.366362E+10 | 0.00 | 0.00 | 472062.60 | 0.00 | 0.00 | 0.773925E+09 | 0.00 | 1.44 |
Annual Sum or Average | 0.189499E+11 | 0.176823E+09 | 0.00 | 39488850.31 | 9716585.79 | 0.00 | 0.210452E+11 | 0.00 | 1.54 |
Minimum of Months | 6327013.58 | 0.00 | 0.00 | 472062.60 | 0.00 | 0.00 | 0.773925E+09 | 0.00 | 1.44 |
Maximum of Months | 0.366362E+10 | 88117244.45 | 0.00 | 7037958.81 | 4545334.11 | 0.00 | 0.300847E+10 | 0.00 | 1.69 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.369995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
February | 0.332883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
March | 0.365051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
April | 0.301687E+10 | 0.00 | 0.00 | 10455.65 | 0.00 | 0.00 | 24006265.72 | 0.00 | 0.57 |
May | 0.226134E+10 | 0.00 | 0.00 | 416219.00 | 280341.77 | 0.00 | 0.202090E+09 | 0.00 | 0.57 |
June | 0.701466E+09 | 38541935.34 | 0.00 | 3071233.73 | 6470331.48 | 0.00 | 0.810881E+09 | 0.00 | 0.60 |
July | 6746380.83 | 73586805.38 | 0.00 | 5070936.21 | 4498762.24 | 0.00 | 0.936463E+09 | 0.00 | 0.62 |
August | 0.155663E+09 | 22493080.87 | 0.00 | 4550557.07 | 6850978.88 | 0.00 | 0.106096E+10 | 0.00 | 0.62 |
September | 0.110394E+10 | 966561.17 | 0.00 | 1452497.44 | 3235658.57 | 0.00 | 0.768770E+09 | 0.00 | 0.59 |
October | 0.291912E+10 | 0.00 | 0.00 | 276611.23 | 16863.97 | 0.00 | 0.194456E+09 | 0.00 | 0.57 |
November | 0.367669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
December | 0.371991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Annual Sum or Average | 0.282410E+11 | 0.135588E+09 | 0.00 | 14848510.35 | 21352936.92 | 0.00 | 0.399763E+10 | 0.00 | 0.58 |
Minimum of Months | 6746380.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.371991E+10 | 73586805.38 | 0.00 | 5070936.21 | 6850978.88 | 0.00 | 0.106096E+10 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.197824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27214999.09 | 0.00 | 0.00 | 0.53 |
February | 0.180430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
March | 0.197865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
April | 0.164823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
May | 0.132210E+10 | 0.00 | 0.00 | 5786.83 | 151951.18 | 0.00 | 10605043.74 | 0.00 | 0.54 |
June | 0.516318E+09 | 20509347.75 | 0.00 | 1075770.88 | 3949960.28 | 0.00 | 0.275436E+09 | 0.00 | 0.54 |
July | 35210710.12 | 38426658.37 | 0.00 | 1916578.44 | 3549048.88 | 0.00 | 0.434562E+09 | 0.00 | 0.55 |
August | 0.183271E+09 | 12060120.65 | 0.00 | 1553966.02 | 3950800.35 | 0.00 | 0.431273E+09 | 0.00 | 0.54 |
September | 0.848206E+09 | 556362.37 | 0.00 | 181484.35 | 1721329.75 | 0.00 | 0.141468E+09 | 0.00 | 0.54 |
October | 0.166125E+10 | 0.00 | 0.00 | 11789.92 | 9140.63 | 0.00 | 22147783.92 | 0.00 | 0.54 |
November | 0.199284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
December | 0.201627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.159849E+11 | 71552489.13 | 0.00 | 4745376.43 | 13332231.07 | 27214999.09 | 0.131549E+10 | 0.00 | 0.54 |
Minimum of Months | 35210710.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.201627E+10 | 38426658.37 | 0.00 | 1916578.44 | 3950800.35 | 27214999.09 | 0.434562E+09 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 41135568.77 | 0.00 | 0.00 | 0.103146E+09 | 0.00 | 0.00 | 0.821211E+11 | 0.00 | 26.74 |
February | 55871521.87 | 0.00 | 0.00 | 92940026.93 | 0.00 | 0.00 | 0.741661E+11 | 0.00 | 26.85 |
March | 2907191.19 | 0.00 | 0.00 | 0.110351E+09 | 0.00 | 0.00 | 0.829610E+11 | 0.00 | 27.06 |
April | 0.00 | 0.00 | 0.00 | 0.122193E+09 | 0.00 | 0.00 | 0.678318E+11 | 0.00 | 26.98 |
May | 0.00 | 5126096.65 | 0.00 | 0.136755E+09 | 0.00 | 0.00 | 0.546445E+11 | 0.00 | 27.01 |
June | 0.00 | 0.830047E+09 | 0.00 | 0.120351E+09 | 0.00 | 0.00 | 0.311713E+11 | 0.00 | 25.58 |
July | 0.00 | 0.145252E+10 | 0.00 | 0.108178E+09 | 0.00 | 0.00 | 0.172977E+11 | 0.00 | 24.83 |
August | 0.00 | 0.539721E+09 | 0.00 | 0.127643E+09 | 0.00 | 0.00 | 0.240121E+11 | 0.00 | 25.66 |
September | 0.00 | 76726417.99 | 0.00 | 0.134968E+09 | 0.00 | 0.00 | 0.411302E+11 | 0.00 | 27.02 |
October | 0.00 | 307911.61 | 0.00 | 0.121016E+09 | 0.00 | 0.00 | 0.698473E+11 | 0.00 | 27.00 |
November | 14959932.58 | 0.00 | 0.00 | 0.102473E+09 | 0.00 | 0.00 | 0.823079E+11 | 0.00 | 26.85 |
December | 0.102458E+09 | 0.00 | 0.00 | 0.104124E+09 | 0.00 | 0.00 | 0.821036E+11 | 0.00 | 26.74 |
Annual Sum or Average | 0.217332E+09 | 0.290445E+10 | 0.00 | 0.138414E+10 | 0.00 | 0.00 | 0.709595E+12 | 0.00 | 26.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 92940026.93 | 0.00 | 0.00 | 0.172977E+11 | 0.00 | 24.83 |
Maximum of Months | 0.102458E+09 | 0.145252E+10 | 0.00 | 0.136755E+09 | 0.00 | 0.00 | 0.829610E+11 | 0.00 | 27.06 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.530855E+10 | 0.00 | 0.00 | 30228048.97 | 0.00 | 0.00 | 0.278527E+11 | 0.00 | 4.43 |
February | 0.355874E+10 | 0.00 | 0.00 | 29932787.24 | 0.00 | 0.00 | 0.261305E+11 | 0.00 | 4.46 |
March | 0.459099E+10 | 0.00 | 0.00 | 33042572.49 | 0.00 | 0.00 | 0.265507E+11 | 0.00 | 4.34 |
April | 0.253854E+10 | 0.00 | 0.00 | 36368612.14 | 0.00 | 0.00 | 0.230848E+11 | 0.00 | 4.28 |
May | 0.270538E+10 | 2242152.38 | 0.00 | 34169300.96 | 36531.18 | 0.00 | 0.179473E+11 | 0.00 | 4.21 |
June | 0.101414E+10 | 0.367050E+09 | 0.00 | 31458746.09 | 2716870.05 | 0.00 | 0.116340E+11 | 0.00 | 4.23 |
July | 0.101574E+09 | 0.653635E+09 | 0.00 | 34732995.32 | 3324202.02 | 0.00 | 0.773833E+10 | 0.00 | 4.37 |
August | 0.278427E+09 | 0.291411E+09 | 0.00 | 45633681.16 | 361988.67 | 0.00 | 0.103307E+11 | 0.00 | 4.69 |
September | 0.456806E+09 | 51205237.45 | 0.00 | 56015935.32 | 0.00 | 0.00 | 0.168516E+11 | 0.00 | 4.98 |
October | 0.169486E+10 | 155356.31 | 0.00 | 53852129.03 | 0.00 | 0.00 | 0.274971E+11 | 0.00 | 4.92 |
November | 0.265892E+10 | 0.00 | 0.00 | 39692525.56 | 0.00 | 0.00 | 0.319349E+11 | 0.00 | 4.65 |
December | 0.466844E+10 | 0.00 | 0.00 | 32566622.06 | 0.00 | 0.00 | 0.294831E+11 | 0.00 | 4.52 |
Annual Sum or Average | 0.295754E+11 | 0.136570E+10 | 0.00 | 0.457694E+09 | 6439591.92 | 0.00 | 0.257036E+12 | 0.00 | 4.51 |
Minimum of Months | 0.101574E+09 | 0.00 | 0.00 | 29932787.24 | 0.00 | 0.00 | 0.773833E+10 | 0.00 | 4.21 |
Maximum of Months | 0.530855E+10 | 0.653635E+09 | 0.00 | 56015935.32 | 3324202.02 | 0.00 | 0.319349E+11 | 0.00 | 4.98 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.229126E+11 | 0.00 | 0.00 | 66934516.15 | 0.00 | 0.00 | 0.733430E+11 | 0.00 | 1.87 |
February | 0.172667E+11 | 0.00 | 0.00 | 66334061.87 | 0.00 | 0.00 | 0.703228E+11 | 0.00 | 1.89 |
March | 0.190511E+11 | 0.00 | 0.00 | 84803048.16 | 0.00 | 0.00 | 0.794569E+11 | 0.00 | 1.94 |
April | 0.107437E+11 | 0.00 | 0.00 | 97893198.48 | 0.00 | 0.00 | 0.749514E+11 | 0.00 | 2.01 |
May | 0.794132E+10 | 6896125.03 | 0.00 | 0.112210E+09 | 149068.50 | 0.00 | 0.636869E+11 | 0.00 | 2.07 |
June | 0.226345E+10 | 0.107546E+10 | 0.00 | 0.123003E+09 | 36427442.77 | 0.00 | 0.429964E+11 | 0.00 | 2.09 |
July | 0.112418E+09 | 0.189292E+10 | 0.00 | 0.135511E+09 | 59958472.68 | 0.00 | 0.278588E+11 | 0.00 | 2.12 |
August | 0.422773E+09 | 0.742822E+09 | 0.00 | 0.159938E+09 | 19086035.53 | 0.00 | 0.367853E+11 | 0.00 | 2.20 |
September | 0.725178E+09 | 0.109099E+09 | 0.00 | 0.174243E+09 | 0.00 | 0.00 | 0.587924E+11 | 0.00 | 2.25 |
October | 0.505053E+10 | 424340.63 | 0.00 | 0.152033E+09 | 0.00 | 0.00 | 0.866896E+11 | 0.00 | 2.12 |
November | 0.868745E+10 | 0.00 | 0.00 | 0.103032E+09 | 0.00 | 0.00 | 0.919194E+11 | 0.00 | 1.96 |
December | 0.183196E+11 | 0.00 | 0.00 | 68693152.53 | 0.00 | 0.00 | 0.784072E+11 | 0.00 | 1.87 |
Annual Sum or Average | 0.113497E+12 | 0.382763E+10 | 0.00 | 0.134463E+10 | 0.115621E+09 | 0.00 | 0.785210E+12 | 0.00 | 2.03 |
Minimum of Months | 0.112418E+09 | 0.00 | 0.00 | 66334061.87 | 0.00 | 0.00 | 0.278588E+11 | 0.00 | 1.87 |
Maximum of Months | 0.229126E+11 | 0.189292E+10 | 0.00 | 0.174243E+09 | 59958472.68 | 0.00 | 0.919194E+11 | 0.00 | 2.25 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 34184192.89 | 0.00 | 0.00 | 3400532.62 | 0.00 | 0.917537E+09 | 0.497059E+09 | 0.00 | 0.35 |
February | 32328652.78 | 0.00 | 0.00 | 4933601.68 | 0.00 | 0.674009E+09 | 0.578442E+09 | 0.00 | 0.35 |
March | 39985751.30 | 0.00 | 0.00 | 8454390.61 | 0.00 | 0.381996E+09 | 0.931667E+09 | 0.00 | 0.35 |
April | 10368978.96 | 0.00 | 0.00 | 14762813.47 | 0.00 | 54850877.81 | 0.108798E+10 | 0.00 | 0.35 |
May | 11302736.01 | 387954.49 | 0.00 | 17501652.02 | 0.00 | 18434711.55 | 0.919393E+09 | 0.00 | 0.35 |
June | 2060143.82 | 14864880.09 | 15599.36 | 18451599.60 | 0.00 | 915471.62 | 0.536822E+09 | 122.58 | 0.35 |
July | 0.00 | 0.186592E+09 | 45772.22 | 6330475.51 | 0.00 | 158587.76 | 56076740.70 | 6748.44 | 0.35 |
August | 0.00 | 0.101517E+09 | 11227.42 | 10029447.08 | 0.00 | 437893.66 | 0.144097E+09 | 869.09 | 0.35 |
September | 0.00 | 11506088.18 | 0.00 | 17568455.03 | 0.00 | 1135120.80 | 0.587661E+09 | 0.00 | 0.35 |
October | 15141882.64 | 678928.11 | 0.00 | 15779291.50 | 0.00 | 0.122371E+09 | 0.993829E+09 | 0.00 | 0.35 |
November | 15927351.89 | 0.00 | 0.00 | 6223838.55 | 0.00 | 0.462546E+09 | 0.902344E+09 | 0.00 | 0.35 |
December | 30259411.51 | 0.00 | 0.00 | 3096073.02 | 0.00 | 0.934094E+09 | 0.481070E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.191559E+09 | 0.315547E+09 | 72599.00 | 0.126532E+09 | 0.00 | 0.356848E+10 | 0.771645E+10 | 7740.12 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3096073.02 | 0.00 | 158587.76 | 56076740.70 | 0.00 | 0.35 |
Maximum of Months | 39985751.30 | 0.186592E+09 | 45772.22 | 18451599.60 | 0.00 | 0.934094E+09 | 0.108798E+10 | 6748.44 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 89739610.98 | 0.00 | 0.00 | 1250926.27 | 0.00 | 0.123200E+10 | 0.129018E+09 | 0.00 | 0.35 |
February | 99443852.42 | 0.00 | 0.00 | 2049750.30 | 0.00 | 0.929774E+09 | 0.258294E+09 | 0.00 | 0.35 |
March | 0.174396E+09 | 0.00 | 0.00 | 3869633.11 | 0.00 | 0.579006E+09 | 0.604672E+09 | 0.00 | 0.35 |
April | 0.193853E+09 | 0.00 | 0.00 | 9305980.15 | 0.00 | 82930992.44 | 0.881739E+09 | 0.00 | 0.35 |
May | 0.178681E+09 | 387909.04 | 0.00 | 13870332.20 | 0.00 | 20869741.76 | 0.753098E+09 | 0.00 | 0.35 |
June | 0.109220E+09 | 14846057.56 | 15643.77 | 15002336.22 | 12210.76 | 710764.34 | 0.433251E+09 | 4946.46 | 0.35 |
July | 29580539.41 | 0.172418E+09 | 93501.21 | 3805363.59 | 14075959.81 | 26749.00 | 29145821.47 | 35009.73 | 0.35 |
August | 71077952.93 | 94925920.76 | 21741.28 | 6418878.81 | 6552387.35 | 164232.72 | 76885628.48 | 17063.94 | 0.35 |
September | 0.172779E+09 | 10698256.02 | 1830.27 | 12199263.34 | 802727.43 | 1244513.97 | 0.420071E+09 | 1926.35 | 0.35 |
October | 0.204196E+09 | 295051.50 | 0.00 | 7921885.12 | 383797.06 | 0.211777E+09 | 0.723093E+09 | 0.00 | 0.35 |
November | 0.101706E+09 | 0.00 | 0.00 | 2475357.44 | 0.00 | 0.834438E+09 | 0.448259E+09 | 0.00 | 0.35 |
December | 77348645.51 | 0.00 | 0.00 | 1025549.28 | 0.00 | 0.127797E+10 | 92003645.27 | 0.00 | 0.35 |
Annual Sum or Average | 0.150202E+10 | 0.293572E+09 | 132716.53 | 79195255.86 | 21827082.42 | 0.517092E+10 | 0.484953E+10 | 58946.48 | 0.35 |
Minimum of Months | 29580539.41 | 0.00 | 0.00 | 1025549.28 | 0.00 | 26749.00 | 29145821.47 | 0.00 | 0.35 |
Maximum of Months | 0.204196E+09 | 0.172418E+09 | 93501.21 | 15002336.22 | 14075959.81 | 0.127797E+10 | 0.881739E+09 | 35009.73 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.238132E+09 | 0.00 | 0.00 | 5045359.73 | 0.00 | 0.00 | 0.140052E+10 | 0.00 | 0.02 |
February | 81023894.69 | 0.00 | 0.00 | 4910146.82 | 0.00 | 0.00 | 0.139489E+10 | 0.00 | 0.02 |
March | 0.118149E+09 | 0.00 | 0.00 | 4419829.86 | 0.00 | 0.00 | 0.144990E+10 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.00 | 4057094.42 | 0.00 | 0.00 | 0.125129E+10 | 0.00 | 0.02 |
May | 77862581.57 | 0.00 | 0.00 | 3093468.50 | 0.00 | 0.00 | 0.773192E+09 | 0.00 | 0.02 |
June | 0.00 | 12563108.86 | 0.00 | 2957705.32 | 0.00 | 0.00 | 0.321454E+09 | 0.00 | 0.02 |
July | 0.00 | 0.188144E+09 | 0.00 | 613696.68 | 0.00 | 0.00 | 17560363.48 | 0.00 | 0.02 |
August | 0.00 | 0.149998E+09 | 0.00 | 834238.61 | 0.00 | 0.00 | 4699185.96 | 0.00 | 0.02 |
September | 0.00 | 45039425.69 | 0.00 | 5654027.05 | 0.00 | 0.00 | 0.136047E+09 | 0.00 | 0.02 |
October | 83188386.55 | 0.00 | 0.00 | 7404449.15 | 0.00 | 0.00 | 0.103333E+10 | 0.00 | 0.02 |
November | 0.121709E+09 | 0.00 | 0.00 | 5909085.88 | 0.00 | 0.00 | 0.152597E+10 | 0.00 | 0.02 |
December | 0.209615E+09 | 0.00 | 0.00 | 5563813.23 | 0.00 | 0.00 | 0.142148E+10 | 0.00 | 0.02 |
Annual Sum or Average | 0.929679E+09 | 0.395745E+09 | 0.00 | 50462915.22 | 0.00 | 0.00 | 0.107303E+11 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 613696.68 | 0.00 | 0.00 | 4699185.96 | 0.00 | 0.02 |
Maximum of Months | 0.238132E+09 | 0.188144E+09 | 0.00 | 7404449.15 | 0.00 | 0.00 | 0.152597E+10 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.124116E+10 | 0.00 | 0.00 | 7056614.19 | 0.00 | 0.113615E+11 | 0.708591E+10 | 0.00 | 0.40 |
February | 0.135537E+10 | 0.00 | 0.00 | 16137052.15 | 0.00 | 0.630551E+10 | 0.981511E+10 | 0.00 | 0.40 |
March | 0.238084E+10 | 0.00 | 0.00 | 47111040.12 | 0.00 | 0.658557E+09 | 0.153874E+11 | 0.00 | 0.40 |
April | 0.289331E+10 | 0.00 | 0.00 | 94068552.72 | 0.00 | 47546526.61 | 0.128060E+11 | 0.00 | 0.40 |
May | 0.265886E+10 | 5255341.80 | 1459.85 | 0.139382E+09 | 0.00 | 17362010.12 | 0.102947E+11 | 4951.71 | 0.40 |
June | 0.154441E+10 | 0.201176E+09 | 257737.90 | 0.137496E+09 | 375312.35 | 4562447.47 | 0.588496E+10 | 13915.14 | 0.40 |
July | 0.401242E+09 | 0.234012E+10 | 343349.95 | 31766188.56 | 0.190932E+09 | 6574.99 | 0.415553E+09 | 37166.16 | 0.40 |
August | 0.964339E+09 | 0.128554E+10 | 645672.40 | 64441616.99 | 90745380.72 | 383602.06 | 0.106717E+10 | 83983.49 | 0.40 |
September | 0.241586E+10 | 0.130111E+09 | 43659.56 | 0.121729E+09 | 25878362.52 | 4712936.88 | 0.568171E+10 | 22082.77 | 0.40 |
October | 0.289875E+10 | 3999092.44 | 1967.91 | 77292956.57 | 5205976.94 | 0.487819E+09 | 0.120943E+11 | 1136.28 | 0.40 |
November | 0.137958E+10 | 0.00 | 0.00 | 27408405.18 | 0.00 | 0.234346E+10 | 0.150617E+11 | 0.00 | 0.40 |
December | 0.109571E+10 | 0.00 | 0.00 | 5618122.82 | 0.00 | 0.126711E+11 | 0.587352E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.212294E+11 | 0.396620E+10 | 1293847.57 | 0.769507E+09 | 0.313137E+09 | 0.339026E+11 | 0.101468E+12 | 163235.55 | 0.40 |
Minimum of Months | 0.401242E+09 | 0.00 | 0.00 | 5618122.82 | 0.00 | 6574.99 | 0.415553E+09 | 0.00 | 0.40 |
Maximum of Months | 0.289875E+10 | 0.234012E+10 | 645672.40 | 0.139382E+09 | 0.190932E+09 | 0.126711E+11 | 0.153874E+11 | 83983.49 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 37541765.22 | 0.00 | 0.00 | 3907985.84 | 0.00 | 0.936511E+09 | 0.474220E+09 | 0.00 | 0.35 |
February | 35769756.31 | 0.00 | 0.00 | 4755830.48 | 0.00 | 0.690912E+09 | 0.558275E+09 | 0.00 | 0.35 |
March | 25075790.52 | 0.00 | 0.00 | 8652622.97 | 0.00 | 0.375424E+09 | 0.952951E+09 | 0.00 | 0.35 |
April | 0.00 | 0.00 | 0.00 | 15461167.33 | 0.00 | 64011317.52 | 0.108849E+10 | 0.00 | 0.35 |
May | 1078802.91 | 387954.49 | 0.00 | 19643623.93 | 0.00 | 11017280.60 | 0.934893E+09 | 0.00 | 0.35 |
June | 0.00 | 14880602.03 | 0.00 | 20777228.12 | 0.00 | 399167.34 | 0.537073E+09 | 0.00 | 0.35 |
July | 0.00 | 0.186638E+09 | 7137.76 | 7051434.22 | 0.00 | 32062.86 | 55482306.89 | 25.76 | 0.35 |
August | 0.00 | 0.101522E+09 | 6353.98 | 11901762.43 | 0.00 | 74629.30 | 0.142588E+09 | 590.04 | 0.35 |
September | 0.00 | 11502559.74 | 3496.29 | 19768448.83 | 0.00 | 369662.61 | 0.586226E+09 | 32.15 | 0.35 |
October | 7813297.59 | 678928.11 | 0.00 | 15639071.07 | 0.00 | 0.129330E+09 | 0.994339E+09 | 0.00 | 0.35 |
November | 18446451.21 | 0.00 | 0.00 | 6826578.89 | 0.00 | 0.487038E+09 | 0.874730E+09 | 0.00 | 0.35 |
December | 39664939.25 | 0.00 | 0.00 | 3703366.02 | 0.00 | 0.947213E+09 | 0.457937E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.165391E+09 | 0.315610E+09 | 16988.03 | 0.138089E+09 | 0.00 | 0.364233E+10 | 0.765721E+10 | 647.95 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3703366.02 | 0.00 | 32062.86 | 55482306.89 | 0.00 | 0.35 |
Maximum of Months | 39664939.25 | 0.186638E+09 | 7137.76 | 20777228.12 | 0.00 | 0.947213E+09 | 0.108849E+10 | 590.04 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 87478138.41 | 0.00 | 0.00 | 900418.96 | 0.00 | 0.122107E+10 | 0.142558E+09 | 0.00 | 0.35 |
February | 99921317.87 | 0.00 | 0.00 | 1610814.85 | 0.00 | 0.917235E+09 | 0.270795E+09 | 0.00 | 0.35 |
March | 0.159480E+09 | 0.00 | 0.00 | 4606120.26 | 0.00 | 0.515922E+09 | 0.681936E+09 | 0.00 | 0.35 |
April | 0.153324E+09 | 0.00 | 0.00 | 11175865.98 | 0.00 | 0.101835E+09 | 0.901494E+09 | 0.00 | 0.35 |
May | 0.157514E+09 | 387909.04 | 0.00 | 16095225.11 | 0.00 | 13248715.46 | 0.779661E+09 | 0.00 | 0.35 |
June | 0.102396E+09 | 14871626.99 | 0.00 | 16005478.94 | 7231.56 | 456189.46 | 0.439327E+09 | 0.00 | 0.35 |
July | 29214042.24 | 0.173201E+09 | 7583.18 | 3466726.48 | 13409420.33 | 3434.11 | 29874270.65 | 4797.13 | 0.35 |
August | 68864018.20 | 95274475.63 | 0.00 | 6676106.14 | 6242637.70 | 134665.41 | 78871903.18 | 0.00 | 0.35 |
September | 0.167644E+09 | 10692928.75 | 7061.51 | 13301837.85 | 802727.43 | 896366.97 | 0.424452E+09 | 2022.37 | 0.35 |
October | 0.184558E+09 | 294346.55 | 366.81 | 8658124.27 | 383797.06 | 0.200528E+09 | 0.753244E+09 | 338.14 | 0.35 |
November | 0.101223E+09 | 0.00 | 0.00 | 2594950.57 | 0.00 | 0.788824E+09 | 0.494237E+09 | 0.00 | 0.35 |
December | 79233423.14 | 0.00 | 0.00 | 683763.51 | 0.00 | 0.124079E+10 | 0.127642E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.139085E+10 | 0.294722E+09 | 15011.50 | 85775432.92 | 20845814.09 | 0.500095E+10 | 0.512409E+10 | 7157.64 | 0.35 |
Minimum of Months | 29214042.24 | 0.00 | 0.00 | 683763.51 | 0.00 | 3434.11 | 29874270.65 | 0.00 | 0.35 |
Maximum of Months | 0.184558E+09 | 0.173201E+09 | 7583.18 | 16095225.11 | 13409420.33 | 0.124079E+10 | 0.901494E+09 | 4797.13 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.232829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593941E+09 | 0.00 | 0.00 | 0.50 |
February | 0.214626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19354342.19 | 0.00 | 0.00 | 0.50 |
March | 0.235578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
April | 0.196238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
May | 0.154411E+11 | 0.00 | 0.00 | 329560.75 | 1809130.12 | 0.00 | 0.425816E+09 | 0.00 | 0.51 |
June | 0.585448E+10 | 0.274359E+09 | 0.00 | 13475531.84 | 30100578.89 | 0.00 | 0.360141E+10 | 0.00 | 0.51 |
July | 0.485197E+09 | 0.506635E+09 | 0.00 | 22119572.30 | 20491727.44 | 0.00 | 0.514552E+10 | 0.00 | 0.53 |
August | 0.108654E+10 | 0.208105E+09 | 0.00 | 26959681.93 | 9762296.67 | 0.00 | 0.648514E+10 | 0.00 | 0.54 |
September | 0.500892E+10 | 29532835.28 | 0.00 | 18972532.35 | 0.00 | 0.00 | 0.707047E+10 | 0.00 | 0.53 |
October | 0.177718E+11 | 109630.82 | 0.00 | 6041972.74 | 0.00 | 0.00 | 0.238733E+10 | 0.00 | 0.51 |
November | 0.237268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
December | 0.238862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119532E+09 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.181188E+12 | 0.101874E+10 | 0.00 | 87898851.92 | 62163733.12 | 0.732828E+09 | 0.251157E+11 | 0.00 | 0.51 |
Minimum of Months | 0.485197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.238862E+11 | 0.506635E+09 | 0.00 | 26959681.93 | 30100578.89 | 0.593941E+09 | 0.707047E+10 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 8425974.24 | 0.00 | 0.00 | 780944.43 | 0.00 | 0.269170E+09 | 84668422.09 | 0.00 | 0.35 |
February | 9123919.36 | 0.00 | 0.00 | 1176625.07 | 0.00 | 0.206092E+09 | 0.106036E+09 | 0.00 | 0.35 |
March | 9904350.15 | 0.00 | 0.00 | 1995894.15 | 0.00 | 0.164169E+09 | 0.164457E+09 | 0.00 | 0.35 |
April | 3396689.31 | 0.00 | 0.00 | 3561513.48 | 0.00 | 49626583.58 | 0.235407E+09 | 0.00 | 0.35 |
May | 2957799.11 | 96988.62 | 0.00 | 4229053.57 | 0.00 | 21354907.63 | 0.213116E+09 | 0.00 | 0.35 |
June | 686438.21 | 3720150.51 | 0.00 | 4527047.56 | 0.00 | 3618652.12 | 0.130730E+09 | 0.00 | 0.35 |
July | 0.00 | 46650693.90 | 9013.50 | 1509348.65 | 0.00 | 39646.94 | 14092455.41 | 1494.39 | 0.35 |
August | 0.00 | 25379228.11 | 2833.80 | 2333798.33 | 0.00 | 105808.21 | 36201594.08 | 190.32 | 0.35 |
September | 0.00 | 2876521.98 | 0.00 | 4092714.60 | 0.00 | 270767.12 | 0.147228E+09 | 0.00 | 0.35 |
October | 3625614.79 | 169732.03 | 0.00 | 3639514.53 | 0.00 | 62297606.93 | 0.217218E+09 | 0.00 | 0.35 |
November | 5560825.55 | 0.00 | 0.00 | 1303362.25 | 0.00 | 0.175412E+09 | 0.164485E+09 | 0.00 | 0.35 |
December | 9627924.90 | 0.00 | 0.00 | 686933.05 | 0.00 | 0.273279E+09 | 78535778.04 | 0.00 | 0.35 |
Annual Sum or Average | 53309535.62 | 78893315.15 | 11847.31 | 29836749.66 | 0.00 | 0.122544E+10 | 0.159217E+10 | 1684.72 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 686933.05 | 0.00 | 39646.94 | 14092455.41 | 0.00 | 0.35 |
Maximum of Months | 9904350.15 | 46650693.90 | 9013.50 | 4527047.56 | 0.00 | 0.273279E+09 | 0.235407E+09 | 1494.39 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 21722162.69 | 0.00 | 0.00 | 285235.89 | 0.00 | 0.316459E+09 | 24536507.21 | 0.00 | 0.35 |
February | 24500837.34 | 0.00 | 0.00 | 463720.47 | 0.00 | 0.256711E+09 | 40714790.26 | 0.00 | 0.35 |
March | 43693687.09 | 0.00 | 0.00 | 877714.79 | 0.00 | 0.206911E+09 | 89003639.61 | 0.00 | 0.35 |
April | 47667170.64 | 0.00 | 0.00 | 2205382.95 | 0.00 | 54561464.29 | 0.187523E+09 | 0.00 | 0.35 |
May | 43770814.28 | 96948.10 | 0.00 | 3390825.78 | 0.00 | 19544186.17 | 0.174924E+09 | 29.16 | 0.35 |
June | 27451771.36 | 3715444.42 | 0.00 | 3766711.84 | 3052.69 | 2768226.43 | 0.105559E+09 | 1217.53 | 0.35 |
July | 7395134.85 | 43111807.03 | 19468.47 | 949832.99 | 3518989.95 | 2110.92 | 7292539.61 | 5469.30 | 0.35 |
August | 17769488.23 | 23734001.82 | 4073.60 | 1546001.18 | 1638096.84 | 41349.26 | 19279834.57 | 3106.07 | 0.35 |
September | 43194676.31 | 2674124.14 | 748.33 | 2846094.09 | 200681.86 | 330872.67 | 0.105202E+09 | 630.63 | 0.35 |
October | 50775485.34 | 73762.88 | 0.00 | 1705114.63 | 95949.27 | 89211450.74 | 0.145055E+09 | 0.00 | 0.35 |
November | 25426403.96 | 0.00 | 0.00 | 488603.76 | 0.00 | 0.262581E+09 | 58223892.87 | 0.00 | 0.35 |
December | 17564906.42 | 0.00 | 0.00 | 210958.18 | 0.00 | 0.326505E+09 | 17806310.35 | 0.00 | 0.35 |
Annual Sum or Average | 0.370933E+09 | 73406088.38 | 24290.40 | 18736196.56 | 5456770.61 | 0.153563E+10 | 0.975121E+09 | 10452.70 | 0.35 |
Minimum of Months | 7395134.85 | 0.00 | 0.00 | 210958.18 | 0.00 | 2110.92 | 7292539.61 | 0.00 | 0.35 |
Maximum of Months | 50775485.34 | 43111807.03 | 19468.47 | 3766711.84 | 3518989.95 | 0.326505E+09 | 0.187523E+09 | 5469.30 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 13994784.13 | 0.00 | 0.00 | 14160958.27 | 0.00 | 0.926395E+09 | 0.137783E+10 | 0.00 | 0.40 |
February | 7112850.38 | 0.00 | 0.00 | 14190868.29 | 0.00 | 0.677599E+09 | 0.137253E+10 | 0.00 | 0.40 |
March | 18458956.14 | 0.00 | 0.00 | 15882057.16 | 0.00 | 0.399390E+09 | 0.175397E+10 | 0.00 | 0.40 |
April | 3804301.40 | 0.00 | 0.00 | 18907995.88 | 0.00 | 0.126855E+09 | 0.172633E+10 | 0.00 | 0.40 |
May | 9426715.30 | 623102.37 | 0.00 | 20445839.26 | 0.00 | 52856970.75 | 0.146980E+10 | 0.00 | 0.40 |
June | 1455609.17 | 23874815.92 | 22550.34 | 20761157.97 | 0.00 | 1549438.76 | 0.872851E+09 | 2701.02 | 0.40 |
July | 0.00 | 0.299742E+09 | 7594.05 | 7643469.94 | 0.00 | 254711.34 | 92590153.92 | 25226.18 | 0.40 |
August | 0.00 | 0.163049E+09 | 13348.08 | 13189402.85 | 0.00 | 581147.48 | 0.234479E+09 | 6080.39 | 0.40 |
September | 0.00 | 18480185.22 | 0.00 | 26019504.53 | 0.00 | 1336546.16 | 0.946540E+09 | 0.00 | 0.40 |
October | 3717796.55 | 1090441.61 | 0.00 | 28519375.84 | 0.00 | 0.143327E+09 | 0.166685E+10 | 0.00 | 0.40 |
November | 12096663.06 | 0.00 | 0.00 | 18453504.21 | 0.00 | 0.339485E+09 | 0.185772E+10 | 0.00 | 0.40 |
December | 18114015.12 | 0.00 | 0.00 | 15009658.54 | 0.00 | 0.906182E+09 | 0.138719E+10 | 0.00 | 0.40 |
Annual Sum or Average | 88181691.24 | 0.506859E+09 | 43492.47 | 0.213184E+09 | 0.00 | 0.357581E+10 | 0.147587E+11 | 34007.60 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 7643469.94 | 0.00 | 254711.34 | 92590153.92 | 0.00 | 0.40 |
Maximum of Months | 18458956.14 | 0.299742E+09 | 22550.34 | 28519375.84 | 0.00 | 0.926395E+09 | 0.185772E+10 | 25226.18 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.178921E+10 | 0.00 | 0.00 | 52627860.44 | 0.00 | 0.00 | 0.481003E+11 | 0.00 | 4.98 |
February | 0.986210E+09 | 0.00 | 0.00 | 53054903.40 | 0.00 | 0.00 | 0.450469E+11 | 0.00 | 5.11 |
March | 0.310011E+09 | 0.00 | 0.00 | 72453643.41 | 0.00 | 0.00 | 0.537442E+11 | 0.00 | 5.42 |
April | 55615248.93 | 0.00 | 0.00 | 90299283.49 | 0.00 | 0.00 | 0.484068E+11 | 0.00 | 5.81 |
May | 23217405.87 | 4069606.45 | 0.00 | 0.106353E+09 | 0.00 | 0.00 | 0.416757E+11 | 0.00 | 6.12 |
June | 0.00 | 0.678454E+09 | 0.00 | 98253286.14 | 0.00 | 0.00 | 0.263058E+11 | 0.00 | 6.22 |
July | 0.00 | 0.115587E+10 | 0.00 | 89963288.27 | 0.00 | 0.00 | 0.158063E+11 | 0.00 | 6.22 |
August | 0.00 | 0.434559E+09 | 0.00 | 0.104627E+09 | 0.00 | 0.00 | 0.206781E+11 | 0.00 | 6.27 |
September | 0.00 | 55117354.02 | 0.00 | 0.106075E+09 | 0.00 | 0.00 | 0.325836E+11 | 0.00 | 6.22 |
October | 0.274971E+09 | 237025.76 | 0.00 | 86744174.34 | 0.00 | 0.00 | 0.483955E+11 | 0.00 | 5.71 |
November | 0.669256E+09 | 0.00 | 0.00 | 60478055.94 | 0.00 | 0.00 | 0.513333E+11 | 0.00 | 5.22 |
December | 0.198189E+10 | 0.00 | 0.00 | 51017626.89 | 0.00 | 0.00 | 0.478525E+11 | 0.00 | 4.96 |
Annual Sum or Average | 0.609038E+10 | 0.232830E+10 | 0.00 | 0.971947E+09 | 0.00 | 0.00 | 0.479929E+12 | 0.00 | 5.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 51017626.89 | 0.00 | 0.00 | 0.158063E+11 | 0.00 | 4.96 |
Maximum of Months | 0.198189E+10 | 0.115587E+10 | 0.00 | 0.106353E+09 | 0.00 | 0.00 | 0.537442E+11 | 0.00 | 6.27 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.459048E+09 | 0.00 | 0.00 | 67678741.90 | 0.00 | 0.00 | 0.542679E+11 | 0.00 | 5.47 |
February | 0.176500E+09 | 0.00 | 0.00 | 66230722.19 | 0.00 | 0.00 | 0.503698E+11 | 0.00 | 5.61 |
March | 2904717.35 | 0.00 | 0.00 | 85763486.49 | 0.00 | 0.00 | 0.592626E+11 | 0.00 | 5.95 |
April | 0.00 | 0.00 | 0.00 | 0.101704E+09 | 0.00 | 0.00 | 0.525961E+11 | 0.00 | 6.32 |
May | 0.00 | 4412124.79 | 0.00 | 0.116374E+09 | 0.00 | 0.00 | 0.448528E+11 | 0.00 | 6.60 |
June | 0.00 | 0.728285E+09 | 0.00 | 0.105334E+09 | 0.00 | 0.00 | 0.279438E+11 | 0.00 | 6.64 |
July | 0.00 | 0.124013E+10 | 0.00 | 95560039.29 | 0.00 | 0.00 | 0.166236E+11 | 0.00 | 6.60 |
August | 0.00 | 0.467155E+09 | 0.00 | 0.111576E+09 | 0.00 | 0.00 | 0.218191E+11 | 0.00 | 6.66 |
September | 0.00 | 59266590.76 | 0.00 | 0.114714E+09 | 0.00 | 0.00 | 0.346177E+11 | 0.00 | 6.63 |
October | 52833418.42 | 256014.13 | 0.00 | 97885659.95 | 0.00 | 0.00 | 0.524678E+11 | 0.00 | 6.15 |
November | 0.134890E+09 | 0.00 | 0.00 | 73697062.93 | 0.00 | 0.00 | 0.567688E+11 | 0.00 | 5.71 |
December | 0.485459E+09 | 0.00 | 0.00 | 66268660.12 | 0.00 | 0.00 | 0.541374E+11 | 0.00 | 5.44 |
Annual Sum or Average | 0.131164E+10 | 0.249951E+10 | 0.00 | 0.110279E+10 | 0.00 | 0.00 | 0.525727E+12 | 0.00 | 6.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 66230722.19 | 0.00 | 0.00 | 0.166236E+11 | 0.00 | 5.44 |
Maximum of Months | 0.485459E+09 | 0.124013E+10 | 0.00 | 0.116374E+09 | 0.00 | 0.00 | 0.592626E+11 | 0.00 | 6.66 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.112815E+09 | 0.00 | 0.00 | 0.761853E+11 | 0.00 | 24.17 |
February | 0.00 | 0.00 | 0.00 | 0.103423E+09 | 0.00 | 0.00 | 0.690969E+11 | 0.00 | 24.53 |
March | 0.00 | 0.00 | 0.00 | 0.123338E+09 | 0.00 | 0.00 | 0.761889E+11 | 0.00 | 25.18 |
April | 0.00 | 0.00 | 0.00 | 0.139570E+09 | 0.00 | 0.00 | 0.621731E+11 | 0.00 | 25.77 |
May | 0.00 | 7224882.39 | 0.00 | 0.154077E+09 | 0.00 | 0.00 | 0.487957E+11 | 0.00 | 26.02 |
June | 0.00 | 0.110541E+10 | 0.00 | 0.131780E+09 | 0.00 | 0.00 | 0.269568E+11 | 0.00 | 25.38 |
July | 0.00 | 0.190027E+10 | 0.00 | 0.113664E+09 | 0.00 | 0.00 | 0.144947E+11 | 0.00 | 25.03 |
August | 0.00 | 0.747601E+09 | 0.00 | 0.141122E+09 | 0.00 | 0.00 | 0.206308E+11 | 0.00 | 25.50 |
September | 0.00 | 0.100227E+09 | 0.00 | 0.152409E+09 | 0.00 | 0.00 | 0.354513E+11 | 0.00 | 26.00 |
October | 0.00 | 434832.08 | 0.00 | 0.139434E+09 | 0.00 | 0.00 | 0.629247E+11 | 0.00 | 25.25 |
November | 0.00 | 0.00 | 0.00 | 0.113221E+09 | 0.00 | 0.00 | 0.769307E+11 | 0.00 | 24.62 |
December | 0.00 | 0.00 | 0.00 | 0.113342E+09 | 0.00 | 0.00 | 0.764375E+11 | 0.00 | 24.19 |
Annual Sum or Average | 0.00 | 0.386117E+10 | 0.00 | 0.153820E+10 | 0.00 | 0.00 | 0.646266E+12 | 0.00 | 25.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.103423E+09 | 0.00 | 0.00 | 0.144947E+11 | 0.00 | 24.17 |
Maximum of Months | 0.00 | 0.190027E+10 | 0.00 | 0.154077E+09 | 0.00 | 0.00 | 0.769307E+11 | 0.00 | 26.02 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.137251E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.568177E+09 | 0.00 | 0.00 | 1.13 |
February | 0.127116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148072E+09 | 0.00 | 0.00 | 1.14 |
March | 0.141023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 |
April | 0.113790E+11 | 0.00 | 0.00 | 898986.80 | 0.00 | 0.00 | 0.369151E+09 | 0.00 | 1.14 |
May | 0.848907E+10 | 1023015.76 | 0.00 | 3941003.56 | 104379.16 | 0.00 | 0.101689E+10 | 0.00 | 1.16 |
June | 0.365236E+10 | 0.247263E+09 | 0.00 | 8718261.76 | 45629.72 | 0.00 | 0.191645E+10 | 0.00 | 1.22 |
July | 0.687217E+09 | 0.409849E+09 | 0.00 | 12575738.50 | 201206.52 | 0.00 | 0.252385E+10 | 0.00 | 1.28 |
August | 0.134016E+10 | 0.169544E+09 | 0.00 | 15740109.88 | 269124.61 | 0.00 | 0.299254E+10 | 0.00 | 1.30 |
September | 0.423469E+10 | 23540086.70 | 0.00 | 11519526.40 | 0.00 | 0.00 | 0.287202E+10 | 0.00 | 1.23 |
October | 0.107543E+11 | 73555.25 | 0.00 | 3877077.85 | 0.00 | 0.00 | 0.125831E+10 | 0.00 | 1.16 |
November | 0.142034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 |
December | 0.138832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487230E+09 | 0.00 | 0.00 | 1.13 |
Annual Sum or Average | 0.109162E+12 | 0.851292E+09 | 0.00 | 57270704.75 | 620340.01 | 0.120348E+10 | 0.129492E+11 | 0.00 | 1.18 |
Minimum of Months | 0.687217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 |
Maximum of Months | 0.142034E+11 | 0.409849E+09 | 0.00 | 15740109.88 | 269124.61 | 0.568177E+09 | 0.299254E+10 | 0.00 | 1.30 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:02:00
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.256128E+12 | 0.438069E+10 | 0.191275E+12 | 0.978130E+12 | 0.105758E+12 |
February | 0.325444E+12 | 0.368209E+10 | 0.157918E+12 | 0.821799E+12 | 0.107185E+12 |
March | 0.449032E+12 | 0.339924E+10 | 0.133213E+12 | 0.721304E+12 | 0.146012E+12 |
April | 0.563428E+12 | 0.258826E+10 | 0.905068E+11 | 0.495319E+12 | 0.274304E+12 |
May | 0.609443E+12 | 0.197261E+10 | 0.652809E+11 | 0.369637E+12 | 0.411963E+12 |
June | 0.569711E+12 | 0.100226E+10 | 0.274614E+11 | 0.190853E+12 | 0.655252E+12 |
July | 0.572293E+12 | 0.152758E+09 | 0.915721E+10 | 0.704583E+11 | 0.865872E+12 |
August | 0.545594E+12 | 0.534777E+09 | 0.227127E+11 | 0.135388E+12 | 0.794784E+12 |
September | 0.434828E+12 | 0.137186E+10 | 0.450773E+11 | 0.270476E+12 | 0.560112E+12 |
October | 0.346502E+12 | 0.260575E+10 | 0.978445E+11 | 0.540778E+12 | 0.325677E+12 |
November | 0.273939E+12 | 0.339747E+10 | 0.149661E+12 | 0.791771E+12 | 0.130704E+12 |
December | 0.232481E+12 | 0.447593E+10 | 0.198773E+12 | 0.100758E+13 | 0.110143E+12 |
Annual Sum or Average | 0.517882E+13 | 0.295637E+11 | 0.118888E+13 | 0.639349E+13 | 0.448777E+13 |
Minimum of Months | 0.232481E+12 | 0.152758E+09 | 0.915721E+10 | 0.704583E+11 | 0.105758E+12 |
Maximum of Months | 0.609443E+12 | 0.447593E+10 | 0.198773E+12 | 0.100758E+13 | 0.865872E+12 |